Skip to main content

Full text of "Commonwealth of Massachusetts state building code"

See other formats


BOSTON  PUBLIC  LIBRARY 


3  9999  03290  947  3 


WARNING!! 


-th 


This  edition  (6  ,  updated  to  19  Sept.  1997)  of  the  Massachusetts 
State  Building  Code  was  bound  incorrectly. 

First  comes  the  User's  Guide  (3 Op.)  which  is  correct.  The  next 

section  are  the  amendments  and  then  the  final  section  is  the  text  of 

the  Building  Code  itself. 

Each  section  has  been  marked.  To  use  effectively  start  by  looking 

in  the  last  section  which  is  the  Building  Code  (6*  Edition,  updated 

to  1 9  Sept.  1997)  and  then  check  the  amendments  (updated  to  12 

Dec.  1997)  in  the  second  section  to  see  if  there  have  been  any 

changes. 


Sorry  for  the  confusion! 


Digitized  by  the  Internet  Archive 

in  2010  with  funding  from 

Boston  Public  Library 


http://www.archive.org/details/commonwealthofma06mass 


MASSACHUSETTS  STATE  BUILDING  CODE,  6th  Ed.  (to  9-19-97) 

700  Boylston  Street 
Boston,  MA  02117 


The  Commonwealth  of  Massachusetts 

William  Francis  Galvin,  Secretary  of  the  Commonwealth 
State  Publications  and  Regulations 

REGULATION  FILING  AND  PUBLICATION 

1.  Regulation  Chapter,  Number  and  Heading:  780  CMR 

The  Massachusetts  State  Building  Code 

2.  Name  of  Agency:  .  .  „ 

State  Board  of  Building  Regulations  and  Standards 

3.  This  document  is  reprinted  from  the  Code  of  Massachusetts  Regulations  and 
contains  the  following: 


This  is  the  Sixth  Edition  of  the  Massachusetts  State  Building  Code  as 
adopted  by  the  State  Board  of  Building  Regulations  and  Standards  and 
filed  with  the  Office  of  the  Secretary  of  the  Commonwealth. 


Under  the  provisions  of  Massachusetts  General  Laws,  Chapter  30A,  Section  6  and  Chapter  233,  Section 
75,  this  document  may  be  used  as  evidence  of  the  original  documents  on  file  with  the  Secretary  of  the 
Commonwealth. 

Compiled  as  in  full  force  and  effect  2/28/97   (Corrected  9/1 9/97) 

A  true  copy  attest 


^A^-^^C^W^^o^^^^ 


WILLIAM  FRANCIS  GALVIN 
$30.00  Secretary  of  the  Commonwealth 


THE  MASSACHUSETTS 
STATE  BUILDING  CODE 


780  CMR 

Sixth  Edition 


COMMONWEALTH  OF  MASSACHUSETTS 


Published  by 

William  F.  Gahin 

Secretary  of  the  Commonwealth 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

FOREWORD  and  ACKNOWLEDGMENTS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE  (780  CMR),  SIXTH  EDITION 

FOREWORD 

The  Sixth  Edition  of  780  CMR  ,the  Massachusetts  State  Building  Code  has  been  revised  from  the  Fifth  Edition  to  make 
it  consistent  with  the  common  code  format  of  the  National  Code,  the  Uniform  Building  Code  and  the  Southern  Building 
Code,  both  in  chapter  and  sub-chapter  numbering.  The  technical  content  is  based  on  the  1993  edition  of  the  Building 
Officials  and  Code  Administrators  (BOCA)  National  Building  Code.  Extensive  technical  changes  have  been  made  as 
a  result  of  reviews  by  the  BBRS  technical  advisory  committees,  listed  in  this  section,  and  also  as  required  by 
Massachusetts  General  Laws  and  Specialized  Codes  and  Regulations. 

Chapter  36,  the  One  and  Two  Family  Dwelling  Code,  has  been  revised  from  the  Fifth  to  the  Sixth  Edition  to  make  it 
consistent  with  the  1995  edition  of  the  CABO  One  and  Two  Family  Dwelling  Code  to  the  extent  practicable. 
Substantive  changes  have  been  made  as  a  result  of  reviews  by  the  BBRS  staff,  state  and  municipal  building  officials, 
and  technical  advisory  boards. 

The  following  chapters  are  considered  unique  to  the  Commonwealth  of  Massachusetts,  in  their  entirety: 

Chapter  1  -  Administration 

Chapter  9  -  Fire  Protection  Systems 

Chapter  1 1  -  Accessibility 

Chapter  13  .   -  Energy  Conservation 

Chapter  16  -  Structural  Loads 

Chapter  1 8  -  Foundations  and  Retaining  Walls 

Chapter  27  -  Electrical  Wiring  and  Equipment 

Chapter  29  -  Plumbing  and  Gasfitting 

Chapter  30  -  Elevator  and  Conveying  Systems 

Chapter  34  -  Repair,  Alteration  and  Change  of  Use  of  Existing  Buildings 

Chapter  35  -  Manufactured  Buildings,  Building  Components  and  Mobile  Homes 

Several  differences  appear  in  the  format  of  the  Sixth  Edition  from  that  of  the  Fifth  Edition;  a  major  change  pertaining 
to  the  numbering  system.  Other  changes  in  the  content  of  the  Sixth  Edition  that  are  different  from  that  of  national 
building  code,  are  shown  in  bold-faced,  italicized  type.  Chapters  which  are  significantly  different  than  the  national 
building  code  are  identified  with  the  parenthetical  statement  This  Chapter  is  Entirely  Unique  to  Massachusetts. 

The  Sixth  Edition  of  the  Massachusetts  State  Building  Code  (780  CMR)  becomes  effective  on  February  28,  1997. 

In  recognition  of  the  time  periods  involved  in  the  planning,  design  and  construction  of  buildings  and  building  related 
projects  and  in  order  to  effect  an  orderly  and  equitable  transition  between  the  Fifth  Edition  and  Sixth  Edition,  the  State 
Board  of  Building  Regulations  and  Standards  implements  the  following  policy; 

From  February  28,  1997  to  August  27,  1997  the  Fifth  and  Sixth  Editions  of  the  Massachusetts  State  Building  Code  shall 
be  considered  to  be  concurrently  effective.  During  this  period,  the  end  user  may  elect  to  utilize  the  provisions  of  either 
the  Fifth  Edition  in  its  entirety  oj  the  Sixth  Edition  in  its  entirety. 

The  Fifth  Edition  will  be  automatically  repealed  on  August  27,  1997  after  which  date  all  users  shall  comply  with  the 
provisions  of  the  Sixth  Edition. 

PURCHASING  OPTIONS 

The  One  and  Two-Family  Dwelling  Code,  identified  in  the  Sixth  Edition  as  Chapter  36,  may  be  purchased  as  a  separate 
package,  including  Chapter  1,  Administration  and  Enforcement  and  Appendix  A,  or  it  may  be  purchased  as  part  of  the 
entire  code  package. 

The  Rules  and  Regulations  of  the  Board  of  Building  Regulations  and  Standards  identified  as  780  CMR-R1  through 
780  CMR-R7,  may  be  purchased  as  a  separate  package  or  as  part  of  the  entire  code  package. 

Also  available  is  the  Guide  to  the  Sixth  Edition  of  the  Massachusetts  State  Building  Code,  This  guide  was  developed 
to  assist  code  users  in  making  the  transition  between  the  Fifth  Edition  and  Sixth  Edition  and  is  sold  as  part  of  the  code. 
It  includes  a  ChapterXArticle  Number  Cross  Reference-Index  and  a  Summary  of  Major  Changes  made  in  the  Sixth 
Edition  relative  to  the  Fifth  Edition  and  the  national  building  code. 

The  code  may  be  ordered  in  any  manner  identified  above  by  calling  the  State  House  Bookstore  (a),  (6 1 7)  727-2834, 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FORWARD  AND  ACKNOWLEDGEMENTS 

AMENDMENT  PROCESS 

Pursuant  to  M.GL.  c.  143,  §  97,  780  CMR  is  subject  to  change  by  amendment.  Amendments  shall  be  proposed  on 
forms  made  available  at  the  office  of  the  Board  of  Building  Regulations  and  Standards.  Proposals  are  offered  at  public 
hearing  where  the  Board  hears  testimony  both  for  and  against  the  proposals.  Proposals  are  then  studied  and  voted  upon 
by  the  Board.  Those  that  are  voted  "approved"  are  issued  as  amendments  to  780  CMR  and  become  effective  when 
published  in  the  Bi-weekly  MASSACHUSETTS  REGISTER. 

All  proposals  for  amendment  to  780  CMR  must  be  received  at  least  60  days  prior  to  the  public  hearing  date.  Changes 
that  are  voted  "approved"  are  issued  on  a  cycle  determined  by  the  Board;  generally  not  sooner  than  a  two  year  cycle. 

The  Board  convenes  public  hearings  to  entertain  changes  to  the  code  a  minimum  of  twice  each  calendar  year;  in  May 
and  November.  Other  public  hearings  may  be  scheduled  as  necessary. 

Anyone  wishing  to  present  a  code  change  proposal  should  contact  the  Office  of  the  Board  at  (617)  727-3200  extension 
614  for  information  on  how  to  file.  It  is  the  responsibility  of  the  code  user  to  check  the  MASSACHUSETTS 
REGISTER  periodically  to  determine  if  amendments  have  been  issued. 

BOARDS  AND  COMMITTEES 
STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

Professor  KcntaroTsutsumi,  P.E..  Chairman  Stanley  S.  Shuman.  P.E. 

Registered  Professional  Engineer  (Structural)  General  Contractor  of  Commercial  &  Industrial  Buildings 

Daniel  P.  O'SulIivan,  Vice  Chairman  Thomas  L.  Rogers  (Ex-Officio) 

Inspector  of  Buildings  (City)  Chief  of  Inspections 

(Gary  Moccia.  P.E.  -  Designee) 
Thomas  E.  Donovan,  General  Contractor 

of  One  and  Two  Family  Homes  Robert  E.  Banks 

Building  Trades  Representative 
Thomas  G.  Gatzunis,  P.E. 
Inspector  of  Buildings  (Town)  Chief  William  V.  Dolan 

Head  of  a  Local  Fire  Department 
William  P.  Kramer,  P.E. 

Registered  Professional  Engineer  Steven  Coan  (Ex  Officio) 

(Mechanical)  State  Fire  Marshal 

(Maurice  M.  Pilette,  P.E.  -  Designee) 
Alexander  H.  MacLeod,  R.A. 
Registered  Architect 

PAST  MEMBERS  CONTRIBUTING  TO  THIS  CODE: 

Richard  Mcintosh  Douglas  Cole  Smith.  R.A 

Inspector  of  Buildings  (Town)  Registered  Architect 

STAFF 

Thomas  L.  Rogers.  Administrator 

Robert  A.  Anderson,  Deputy  Administrator 

Brian  Gore,  PE.  CEng.,  Technical  Director  . 

Thomas  M.  Riley,  Code  Development  Manager 

Marian  Doyle,  Home  Improvement  Contractor  Program  Manager 

Patricia  A.  Brennan,  Building  Code  Board  of  Appeals  Manager 

Anne  Mane  Rose 

Mary  Kavanaugh 

Julie  Allan 
Jeffrey  Putnam 
Heather  McEwan 
Sean  MacDonald 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


RESEARCH  ASSISTANTS 

Andrew  Bodnar  (Legal  Research) 
Derek  Creaser  (Technical  Research) 


Professor  Kentaro  Tsutsumi,  P.E.,  Chairman 
College  of  Engineering 
Tufts  University 


CONSTRUCTION  MATERIALS  SAFETY  BOARD  (CMSB) 

Francis  Harvey.  P.E.,  RA. 
Harvey  and  Tracy- 


Charles  A.  J.  Theodore,  P.E. 
Hometech  Consulting  Group 

Terrence  Johnston.  Laboratory  Supervisor 

Testing  Laboratory 

Metropolitan  District  Commission 

Sanford  Kaplan 

Sanford  Constriction  Company 


Ara  Shrestinian.  P.E.,  Vice  President 
The  Thompson  &  Lichtner  Co..  Inc. 

Professor  Louis  C.  Tartaglione,  P  E. 

Department  of  Civil  Engineering  University  of  Lowell 

James  Keefe 

The  Beacon  Companies 


Staff  Liaison  -Thomas  M  Riley 


FIRE  PREVENTION  -  FIRE  PROTECTION  BOARD 


John  M.  Murphy,  Chairman 
International  Municipal  Signalmen's 
Association 

Lt.  Michael  P.  Astkin 

Massachusetts  Fire  Prevention  Association 


Harold  Cutler.  P.E. 

Registered  Professional  Engineer 

(Fire  Protection) 

Lt.  Robert  Bourke 

Massachusetts  Fire  Prevention  Association 


Chief  James  W.  Clarke 
Massachusetts  Fire  Chiefs  Association 


Chief  William  V.  Dolan 
Massachusetts  Fire  Chiefs  Association 


Walter  B.  Adams,  AIA 
Registered  Architect 


Steven  Coan,  State  Fire  Marshal 
(Maurice  M.  Pilette,  P.E.  -  Designee) 

Carlisle  V.  Smith,  PE 

Board  of  Fire  Prevention  Regulations 

Commissioner  Martin  Pierce 
Mass.  Fire  Chiefs  Association 
(Paul  M.  Donga  -  Designee) 


Staff  Liaison  -  Thomas  M.  Riley 
GEOTECHNICAL  ADVISORY  COMMITTEE 


Edmund  G.  Johnson,  P.E.,  Chairman 
Haley  &  Aldrich.  Inc. 

Nino  Catalano,  P.E. 
ICOS  Boston 

P  A.  O'Neill.  P.E. 

New  England  Foundation,  Co. 

Asaf  A.  Qazilbash,  P.E. 
Asaf  A.  Qazilbash  Associates 


Peter  K.  Taylor,  P.E.,  Vice  Chairman 
Stone  &  Webster  Engineering 


Eldon  L.  Abbot,  P.E. 

Parsons  Brinkerhoff  Quade  and  Douglas,  Inc. 


David  Shields.  P.E. 
Geotechnical  Engineers,  Inc. 


Dr.  Richard  M.  Simon,  P.E. 
GZA  Associates 


Robert  Hoyler.  P.E, 
McPhail  Associates 


Staff  Liaison  -  Robert  A.  Anderson 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FORWARD  AND  ACKNOWLEDGEMENTS 


SEISMIC  ADVISORY  COMMITTEE 


Norton  S.  Remmer,  P.E.,  Chairman 
Norton  S.  Remmer  Consulting  Engineers 

Dr.  John.  T.  Christian,  P.E. 
Consulting  Engineer 

Francis  D.  Leathers,  P.E. 
Geotechrucal  Engineers,  Inc. 

Nicholas  Mariani,  P.E. 
Charles  T.  Main,  Inc. 

Maurice  A.  Reidy,  Jr.,  P.E. 
Maurice  A.  Reidy  Engineers 

Professor  Kentaro  Tsutsumi,  P.E. 
BBRS  Representative 


Kenneth  B.  Weisner,  P.E.,  Vice  Chairman 
Le  Messurier  Consultants 

Joseph  J.  Zona,  P.E. 

Simpson,  Gumpertz,  &  Heger,  Inc. 

Dr.  Cetin  Soydemir,  P.E. 
Haley  and  Aldnch 

Wayne  Siladi,  P.E. 
Weidlinger  Associates,  Inc. 

Richard  Henige,  P.E. 

Le  Messuner  Consultants 


Staff  Liaison  -  Brian  Gore.  P.E.,  C.  Eng. 
MEMA  Liaison.  John  C.  Smith  -  Earthquake  Program  Manager 


Dr.  Frank  J  Heger,  P.E.,  Chairman 
Simpson,  Gumpertz  &  Heger,  Inc. 

Rubin  M.  Zallen,  P.E. 
Consulting  Engineer 

Hans  William  Hagen,  P.E. 
Lim  Consultants 

Arthur  L.  Brown,  P.E. 
Boston  Building  Consultants 


LOADS  ADVISORY  COMMITTEE 

Stanley  S.  Shuman,  P.E. 
BBRS  Member 


Michael  Joliffe,  P.E. 
Zaldastani  Associates 

Edward  LeNormand.  P.E. 
Chapui  Associates 

Tom  McGarrigle,  P.E. 
Amman  &  Whitney 

Staff  Liaison  -  Brian  Gore,  P.E.,  C.  Eng. 


BUILDING  OFFICIAL  CERTIFICATION  COMMTTTEE 

(The  Standing  Certification  Committee) 


Matthias  J.  Mulvey.  Chairman 
Massachusetts  Building  Commissioners 
and  Inspectors  Association  (Representative) 
Certified  Building  Code  Enforcement  Official 

Daniel  P.  O'Sullivan,  Vice  Chairman 

Building  Officials  of  Western  Massachusetts 

(Representative) 

Certified  Building  Code  Enforcement  Official 

Paul  J.  Nonni,  Member  at  Large 

Certified  Building  Code  Enforcement  Official 

Don  York,  Member  at  Large 

Certified  Building  Code  Enforcement  Official 

(Michael  Card) 


David  Thyng,  P.E. 

Southeastern  Massachusetts  Building  Officials 

Association  (Representative) 

Certified  Building  Code  Enforcement  Official 


Robert  Betit,  Member  at  Large 

Certified  Building  Code  Enforcement  Official 

(Peter  DePesa 

Fred  Hanack.  P.E.,  Member  from  Academia 

Robert  A  Anderson,  BBRS  Representative 
Certified  Building  Code  Enforcement  Official 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


ENERGY  ADVISORY  COMMITTEE 


Thomas  M.  Riley, 
BBRS  Representative 


Dale  Gigandet 

State  Fire  Marshal  Representative 

Anne  Gros 

DOER  Representative 

Michael  Andelman,  P.E., 
Shooshanian  Engineering,  Inc 

Jerard  Ives,  R.A. 

Jerard  Ives  Registered  Architect 

Robert  Figuerido,  P.  E. 
Digital  Equipment  Corp. 

Nick  Johnson.  P.  E. 

Bard,  Rao  &  Athanas  Consulting  Engineers,  Inc. 

Joel  Wedding 

Department  of  Labor  and  Industries 

Richard  Kramer 

Home  Builders  Association  of  Greater  Springfield 


William  Habib 

Home  Builders  Association  of  Massachusetts 

Melvin  Fink 

Home  Builders  Association 

Charles  E.  Wheeler 

New  England  Power  Service 

Ron  Moreira 
Bay  State  Gas  Co. 

Michael  Ferrante 
Massachusetts  Oil  Heat  Council 

Charles  Brewster 

Accent  Sales  and  Marketing 

Jack  Desmond 
Cox  Engineering 

Robert  Thorell 

Building  Commissioner,  Westminster 

Mike  Martin 

Waltham  Development  Co. 


HIC  ADVISORY  COMMITTEE 


Marian  Doyle 
BBRS  Representative 

Harry  Smith 
HIC  Registrant 

William  O'Brien 

NARI  Eastern  MA  Chapter 

Jack  Elliott 

NARI  Western  MA  Chapter 


Paul  Schlaver 

MA  Consumer  Coalition 

Arlie  Costine  Scott 

Representative  from  the  Office  of  the  AG 

Frank  Rosen 

Fund  Administrator 

Ken  Wade 

Representative  of  the  Attorney  General 


TECHNICAL  CODE  COUNCIL 

Pursuant  to  M.G.L.  c.  143,  §  3,  there  shall  be  an  advisory  board  known  as  the  technical  code  council 
which  shall  make  recommendations  relative  to  the  formulation,  promulgation  and  administration  of  the 
state  building  code.  The  make-up  of  the  council  is  available  at  the  Office  of  the  Board  of  Building 
Regulations  and  Standards. 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 


TABLE  OF  CONTENTS 


Page 


Chapter  1:   ADMINISTRATION 

(This  chapter  is  entirely  unique  to  Massachusetts) 


101.0 

Scope 

102.0 

Applicability 

103.0 

Maintenance 

104.0 

Validity 

105.0 

Office  of  the  inspector  of  buildings  or  building  commissioner 

106.0 

Duties  and  powers  of  the  building  official 

107.0 

Duties  and  powers  of  the  state  inspector 

108.0 

Rules  &  regulations 

109.0 

Approval 

110.0 

Application  for  permit 

111.0 

Permits 

112.0 

Demolition  of  structures 

113.0 

Conditions  of  permit 

114.0 

Fees 

115.0 

Inspection 

116.0 

Registered  architectural  and  professional  engineering  services 

construction  control 

117.0 

Workmanship 

118.0 

Violations 

119.0 

Stop  work  order 

120.0 

Certificate  of  occupancy 

121.0 

Unsafe  structures 

122.0 

Board  of  appeals 

123.0 

Construction  Materials  safety  Board 

124.0 

Fire  Prevention  -  Fire  Protection  Advisory  Committee 

125.0 

Structural  Peer  Review  Advisory  Committee 

13 
13 
14 
14 
14 
15 
17 
18 
19 
19 
21 
23 
23 
23 
24 

24 
26 
26 
26 
27 
27 
28 
32 
32 
32 


Chapter  2:    DEFINITIONS 

201.0:    General 

202.0:    General  Definitions 


Chapter  3:    USE  OR  OCCUPANCY 


301.0 

General 

302.0 

Classification 

303.0 

Assembly  use  groups 

304.0 

Business  use  group 

305.0 

Educational  use  group 

306.0 

Factory  and  industrial  use  groups 

307.0 

High  hazard  use  groups 

308.0 

Institutional  use  groups 

309.0 

Mercantile  use  group 

310.0 

Residential  use  groups 

311.0 

Storage  use  groups 

312.0 

Utility  and  miscellaneous  use  group 

313.0 

Mixed  use  groups 

apter 

4:    SPECIAL  USE  AND  OCCUP 

401.0 

General 

402.0 

Covered  mall  buildings 

403.0 

High  rise  buildings 

404.0 

Atriums 

405.0 

Underground  structures 

406.0 

Open  parking  structures 

407.0 

Private  garages 

408.0 

Public  garages 

409.0 

Use  Group  1-2 

47 

47 
47 
48 
49 
49 
49 
50 
54 
57 
58 
59 
59 
59 

63 

63 
63 
65 
67 
68 
69 
70 
70 
71 


2/7/97    (Effective  2/28/07) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 
Chapter  4:    SPECIAL  USE  AND  OCCUPANCY  -  continued 


410.0 
411.0 
412.0 
413.0 
414.0 
415.0 
416.0 
417.0 
418.0 
419.0 
420.0 
421.0 
422.0 
423.0 
424.0 
425.0 
426.0 
427.0 
428.0 
429.0 


Use  Group  1-3 

Motion  picture  projection  rooms,  screening  rooms  and  sound  stages 

Stages  and  platforms 

Special  amusement  buildings 

Airport  traffic  control  towers 

Outdoor  processing  facilities 

HPM  facilities 

Hazardous  materials 

Use  Groups  H-l,  H-2,  H-3  and  H-4 

Application  of  flammable  finishes 

Mobile  units 

Swimming  pools 

Existing  buildings 

Group  Residences 

Day  Care  Centers 

Summer  Camps  for  Children 

Bulk  Merchandising  Retail  Buildings 

Limited  Group  Residences 

Detoxification  Facilities 

Group  Dwelling  Units 


Chapter  5:    GENERAL  BUILDING  LIMITATIONS 


501.0 
502.0 
503.0 
504.0 
505.0 
506.0 
507.0 


General 

Definitions 

General  height  and  area  limitations 

Height  modifications 

Mezzanines 

Area  modifications 

Unlimited  areas 


Page 


72 
74 
75 
78 
78 
79 
79 
83 
85 


92 
93 
95 
99 
99 
104 
107 
109 

113 

113 
113 
113 
115 
116 
116 
117 


Chapter  6:    TYPES  OF  CONSTRUCTION 


601.0 
602.0 
603.0 
604.0 
605.0 
606.0 


General 

Construction  classification 
Types  1  and  2  construction 
Type  3  construction 
Type  4  construction 
Type  5  construction 


Chapter  7:    FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


701.0 
702.0 
703.0 
704.0 
705.0 
706.0 
707.0 
708.0 
709.0 
710.0 
711.0 
712.0 
713.0 
714.0 


General 

Definitions 

Construction  documents 

Fire  tests 

Exterior  walls 

Exterior  opening  protectives 

Fire  walls  and  party  walls 

Fire  wall  openings 

Fire  separation  assemblies 

Vertical  shafts 

Fire  partitions 

Smoke  barriers 

Floor/ceiling  and  roof/ceiling  assemblies 

Roof  construction 


119 

119 
119 
121 
121 
121 
121 

123 

123 
123 
124 
124 
125 
128 
128 
130 
130 
132 
133 
133 
134 
136 


750  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 


TABLE  OF  CONTENTS  -  continued 


Chapter  7:    FIRERESISTANT  MATERIALS  AND  CONSTRUCTION  -  continued 


715.0 
716.0 
717.0 
718.0 
719.0 
720.0 
721.0 
722.0 


Fireresistance  rating  of  structural  members 

Fire  door  assemblies 

Fire  dampers 

Fire  windows  and  shutters 

Wired  glass 

Firestopping  and  draftstopping 

Fireresistive  requirements  for  plaster 

Thermal-  and  sound-insulating  materials 


Chapter  8:    INTERIOR  FINISHES 


801.0 
802.0 
803.0 
804.0 
805.0 
806.0 


General 
Definitions 

Interior  finish  and  trim 

Application  of  interior  finish 

Floor  finish 

Combustible  materials  permitted  in  floors  of  type  1  and  2  construction 


807.0:    Interior  hangings  and  decorations 

Chapter  9:    FIRE  PROTECTION  SYSTEMS 
(This  chapter  is  entirely  unique  to  Massachusetts) 


901.0 
902.0 
903.0 
904.0 
905.0 
906.0 
907.0 
908.0 
909.0 
910.0 
911.0 
912.0 
913.0 
914.0 
915.0 
916.0 
917.0 
918.0 
919.0 
920.0 
921.0 
922.0 
923.0 
924.0 


General 

Definitions 

Fire  protection  systems  approval/acceptance 

Fire  suppression  systems 

Suppression  system  agent  compatibility 

Fire  sprinkler  system 

Limited  area  sprinkler  systems 

Water-spray  fixed  systems 

Carbon  dioxide  extinguishing  systems 

Dry-chemical  extinguishing  systems 

Foam  extinguishing  systems 

Halogenated  extinguishing  systems 

Wet-chemical  range  hood  extinguishing  systems 

Standpipe  systems 

Fire  department  connections 

Yard  hydrants/underground  fire  mains 

Fire  protective  signaling  systems  (Fire  alarm  systems) 

Automatic  fne  ietection  systems 

Single-  and  multiple-station  smoke  detectors 

Fire  extinguishers 

Smoke  control  systems 

Smoke  and  heat  vents 

Supervision 

Fire  pumps 


Chapter  10:    MEANS  OF  EGRESS 


1001.0 
1002.0 
1003.0 
1004.0 
1005.0 
1006.0 
1007.0 
1008.0 
1009.0 
1010.0 
1011.0 


Ggeneral 

Definitions 

Construction  documents 

Use  group  and  occupancy  requirements 

General  limitations 

Types  and  location  of  means  of  egress 

Accessible  means  of  egress 

Occupant  load 

Capacity  of  egress  components 

Number  of  exits 

Exit  access  passageways  and  corridors 


Page 


137 
137 
138 
139 
139 
140 
141 
142 


143 
143 
143 
144 
145 
146 
146 


147 
147 
149 
151 
153 
153 
154 
154 
155 
155 
156 
156 
157 
157 
158 
159 
159 
162 
164 
164 
165 
167 
168 
168 

171 

171 
171 
172 
172 
172 
173 
175 
176 
177 
177 
178 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


7^0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 

Chapter  10:    MEANS  OF  EGRESS  -  continued 

1012.0:  Assembly  aisles  and  aisle  accessways 

1013.0:  Grandstands 

1014.0:  Stairways 

1015.0:  Smokeproof enclosures 

1016.0:  Ramps 

1017.0:  Means  of  egress  doorways 

1018.0:  Revolving  doors 

1019.0:  Horizontal  exits 

1020.0:  Level  of  exit  discharge  passageways  used  as  an  exit  element 

1021.0:  Guards 

1022.0:  Handrails 

1 023.0:  Exit  signs  and  lights 

1024.0:  Means  of  egress  lighting 

1025.0:  Fire  escapes 

1026.0:  Slidescapes 

1027.0:  Access  to  roof 

1028.0:  Maintenance  of  exits 


Chapter  11:    ACCESSIBILITY 

(780  CMR  11  is  Entirety  Unique  to  Massachusetts) 

Chapter  12:    INTERIOR  ENVIRONMENT 


1201.0 
1202.0 
1203.0 
1204.0 
1205.0 
1206.0 
1207.0 
1208.0 
1209.0 
1210.0 
1211.0 
1212.0 
1213.0 
1214.0 
1215.0 


General 

Definitions 

Construction  documents 

Room  dimensions 

Light  and  ventilation  required 

Natural  light 

Artificial  light 

Natural  ventilation 

Mechanical  ventilation 

Ventilation  of  special  spaces 

Access  to  crawl  spaces  and  attics 

Courts  and  yards 

Obstruction  of  courts  and  yards 

Sound  transmission  control  in  residential  buildings 

Ratproofmg 


Chapter  13:    ENERGY  CONSERVATION 

(This  chapter  is  entirely  unique  to  Massachusetts) 

1300.0:  General 

1301.0:  Administrative 

1302.0:  Existing  buildings 

1303.0:  Plans  and  specifications 

1304.0:  Materials  and  equipment 

1305.0:  Design  conditions 

1306.0:  Building  insulation  specifications 

1307.0:  Air  infiltration  and  moisture  control 

1308.0:  Component  design 

1309.0:  Exterior  envelope  requirements  for  lowrise  residential  buildings 

1310.0:  Heating,  ventilation  and  air  conditioning  (HVAC)  systems 

1311.0:  Heating,  ventilation  and  air  conditioning  equipment 

1312.0:  Electrical  power  distribution 

1313.0:  Lighting  systems 

1314.0:  Building  envelop  requirements  for  commercial  and  high  rise  residential  buildings 

1315  0:  Building  design  by  systems  analysists 

13 16.0:  Buildings  utilizing  solar,  geotethermal,  wing,  or  other  nondepletable  energy  sources 
as  alternative  designs 


Page 


180 
182 
183 
187 
189 
189 
190 
194 
195 
195 
196 
196 
197 
197 
198 
198 
199 

201 


203 

203 
203 
203 
203 
204 
204 
204 
204 
205 
205 
205 
205 
206 
206 
207 

209 

209 
209 
209 
209 
209 
210 
211 
212 
212 
213 
214 
219 
222 
222 
232 
241 

242 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 


TABLE  OF  CONTENTS  -  continued 


Page 


Chapter  14:    EXTERIOR  WALL  COVERINGS 


1401.0 
1402.0 
1403.0 
1404.0 
1405.0 
1406.0 


General 

Definitions 

Performance  requirements 

Materials 

Veneers 

Combustible  materials  on  the  exterior  side  of  exterior  walls 


243 

243 
243 
243 
243 
244 
248 


Chapter  15:    ROOF  AND  ROOF  COVERINGS 


1501.0 
1502.0 
1503.0 
1504.0 
1505.0 
1506.0 
1507.0 
1508.0 
1509.0 
1510.0 
1511.0 
1512.0 


General 
Definitions 

Construction  documents 
Weather  protection 
Performance  requirements 
Fire  classification 
Prescriptive  requirements 
Flashings 
Roof  insulation 
Roof  structures 
Rooftop  heliports 
Reroofing 


Chapter  16:    STRUCTURAL  LOADS 

(This  chapter  is  entirely  unique  to  Massachusetts) 


1601.0 

General 

1602.0 

Definitions 

1603.0 

Construction  documents 

1604.0 

Design  safe  load 

1605.0 

Design  dead  load 

1606.0 

Uniformly  distributed  live  loads 

1607.0 

Design  live  load 

1608.0 

Live  load  reduction 

1609.0 

Roof  loads 

1610.0 

Snow  loads 

1611.0 

Wind  loads 

1612.0 

Earthquake  loads 

1613.0 

Concentrated  loads 

1614.0 

Impact  loads 

1615.0 

Special  loads 

1616.0 

Combination  of  loads 

1617.0 

Existing  buildings 

251 

251 
251 
251 
251 
251 
252 
252 
254 
255 
255 
256 
256 

257 

257 
257 
257 
258 
258 
258 
259 
259 
260 
261 
271 
278 
296 
297 
297 
298 
299 


Chapter  17:    STRUCTURAL  TESTS  AND  INSPECTIONS 

(Substantial  portions  of  this  chapter  are  unique  to  Massachusetts) 


1701.0 
1702.0 
1703.0 
1704.0 
1705.0 
1706.0 
1707.0 
1708.0 
1709.0 
1710.0 


General 

Definitions 

Information  required 

Approvals 

P„equirements  for  special  tests  and  inspections 

Design  strength  of  materials 

Alternative  test  procedure 

Test  safe  load 

In-situ  load  tests 

Preconstruction  load  tests 


301 

301 
301 
301 
302 
302 
306 
306 
306 
306 
307 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 


Chapter  18:    FOUNDATIONS  AND  RETAINING  WALLS 

(This  chapter  is  entirely  unique  to  Massachusetts) 

1801.0:  General 

1802.0:  Foundation  investigations 

1803.0:  Soil  bearing  test 

1804.0:  Load  bearing  value  of  soils 

1805.0:  Allowable  foundation  loads 

1 806.0:  Depth  of  footings 

1807.0:  Footing  design 

1 808.0:  Timber  footings  and  wood  foundations 

1809.0:  Steel  grillages 

1 8 1 0. 0:  Concrete  footings 

1811.0:  Masonry  unit  footings 

1812.0:  Foundation  walls 

1813.0:  Waterproofing  and  dampproofing 

1814.0:  Mat,  raft  and  float  foundation 

1815.0:  Pier  foundations 

1816.0:  Pile  foundations 

1817.0:  Allowable  pile  loads 

1818.0:  Structural  steel  piles 

1819.0:  Concrete-filled  steel  pipe  and  tube  piles 

1820.0:  Cast-in-place  concrete  piles 

1 82 1 .0:  Precast  concrete  piles 

1822.0:  Timber  piles 

1823.0:  Composite  piles 

1 824.0:  Concrete  filled  pipe  with  core  caissons 

1825.0:  Retaining  walls 

Chapter  19:    CONCRETE 


1901.0 
1902.0 
1903.0 
1904.0 
1905.0 
1906.0 
1907.0 
1908.0 
1909.0 
1910.0 
1911.0 
1912.0 


Concrete  design  standards 

Definitions 

Seismic  requirements  for  reinforced  concrete 

Seismic  requirements  for  plain  concrete 

Minimum  slab  thickness 

Materials 

Durability  requirements 

Concrete  quality,  mixing  and  placing 

Formwork,  embedded  pipes,  and  construction  joints 

Details  of  reinforcement 

Shotcrete 

Concrete-filled  pipe  columns 


Chapter  20:    LIGHTWEIGHT  METALS 

2001.0  General 
2002.0  Materials 


Page 


309 

309 
309 
310 
312 
313 
313 
314 
314 
314 
315 
315 
316 
318 
318 
320 
323 
326 
326 
327 
332 
332 
333 
333 
334 

335 

335 
335 
335 
338 
339 
339 
340 
343 
345 
346 
348 
348 


351 
351 


Chapter  21:    MASONRY 


2101.0 
2102.0 
2103.0 
2104.0 
2105.0 
2106.0 
2107.0 
2108.0 
2109.0 
2110.0 


General 

Definitions 

Construction  documents 

Seismic  requirements 

Masonry  construction  materials 

Lateral  stability 

Compressive  stress  requirements 

Lateral  support 

Thickness  of  masonry 

Bond 


353 

353 
253 
355 
355 
357 
359 
360 
360 
361 
361 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 

TABLE  OF  CONTENTS  -  continued 


Chapter  21:    MASONRY  -  continued 
2111.0:    Anchorage 
2112.0:    Masonry  construction 
2113.0:    Miscellaneous  requirements 
2114.0:    Fireplaces  and  chimneys 
2115.0:    Glass  block  walls 


362 
363 
364 
364 
365 


Chapter  22:    STEEL 


2201.0 
2202.0 
2203.0 
2204.0 
2205.0 
2206.0 
2207.0 
2208.0 
2209.0 
2210.0 


General 

Definitions 

Structural  steel  construction 

Seismic  requirements  for  structural  steel 

Open  web  steel  joist  construction 

Formed  steel  construction 

Special  steel  and  steel  cable  structural  systems 

Reinforcing  steel 

Cast  steel  construction 

Cast  iron  construction 


367 

367 
367 
367 
369 
369 
369 
370 
371 
371 
371 


Chapter  23:    WOOD 


2301.0 
2302.0 
2303.0 
2304.0 
2305.0 
2306.0 
2307.0 
2308.0 
2309.0 
2310.0 
2311.0 
2312.0 
2313.0 


General 

Definitions 

Performance  requirements 

Heavy  timber  construction 

Wood  frame  construction 

Seismic  requirements  for  wood  and  timber 

Wood  structural  panels 

Particleboard 

Fiber  boards 

Fireretardant  treated  wood 

Naturally  durable  and  preservative  treated  wood 

Joist  hangers 

Prefabricated  components 


Chapter  24:    GLASS  AND  GLAZING 


2401.0 
2402.0 
2403.0 
2404.0 
2405.0 
2406.0 
2407.0 


General 

General  requirements  for  glass 

Wind,  snow  and  dead  loads  on  glass 

Sloped  glazing  and  skylights 

Safety  glazing 

Glass  in  handrails  and  guardrails 

Glazing  in  racquetball  and  squash  courts 


Chapter  25:    GYPSUM  BOARD  AND  PLASTER 

2501.0:  General 

2502.0:  Shear  walls 

2503.0:  Gypsum  board  materials 

2504.0:  Gypsum  construction 

2505.0:  Interior  lathing  and  gypsum  plastering 

2506.0:  Portland  cement  stucco  lathing  and  plastering 


373 

373 
373 
373 
374 
375 
381 
388 
390 
391 
392 
393 
394 
395 

397 

397 
397 
397 
399 
399 
401 
401 

403 

403 
403 
403 
405 
405 
405 


2/7/97    (Effective  2/28/97) 


780  CMR -Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 


Chapter  26:    PLASTIC 


2601.0 
2602.0 
2603.0 
2604.0 
2605.0 
2606.0 
2607.0 
2608.0 


General 

Definitions 

Foam  plastic 

General  requirements  for  light  transmitting  plastics 

Light-transmitting  wall  panels 

Light-transmitting  plastic  glazing  of  unprotected  openings 

Light-transmitting  plastic  roof  panels 

Light-transmitting  skylight  glazing 


Chapter  27:    ELECTRICAL  WIRING,  EQUIPMENT  AND  SYSTEMS 
(This  chapter  is  entirely  unique  to  Massachusetts) 


Page 

407 

407 
407 
407 
409 
410 
411 
411 
412 

415 


Chapter  28:    MECHANICAL  SYSTEMS 


2801.0: 

General 

2802.0: 

Construction  documents 

2803.0: 

Fees 

2804.0: 

Inspections  and  tests 

2805.0: 

Plenums 

2806.0: 

Drying  rooms 

2807.0: 

Waste  and  linen  handling  systems 

2808.0: 

Refuse  vaults 

2809.0: 

Medical  gases 

2810.0: 

Oxygen  systems 

2811.0: 

Existing  buildings 

2812.0: 

Power  ventors 

28.13.0: 

Solid  fuel-fired  appliances 

417 

417 
417 
417 
417 
417 
418 
418 
419 
419 
419 
419 
419 
420 


Chapter  29:    PLUMBING  SYSTEMS 

(This  chapter  is  entirely  unique  to  Massachusetts) 


421 


Chapter  30:    ELEVATORS  AND  CONVEYING  SYSTEMS 

(This  chapter  is  entirely  unique  to  Massachusetts) 

3001.0:    General 


423 


Chapter  31 :    SPECIAL  CONSTRUCTION 


3101.0 
3102.0 
3103.0 
3104.0 
3105.0 
3106.0 
3107.0 
3108.0 
3109.0 
3110.0 


General 
Signs 

Membrane  structures 
Temporary  structures 
Canopies  cjrd  awnings 
Pedestrian  walkways 
Flood-resistant  construction 
Radio  and  television  towers 
Radio  and  television  antennas 
Window-cleaning  safeguards 


Chapter  32:    CONSTRUCTION  IN  THE  PUBLIC  RIGHT-  OF-  WAY 


3201.0 
3202.0 
3203.0 
3204.0 
3205.0 


General 

Street  encroachments 
Permissible  street  projections 
Special  and  temporary  projections 
Awnings  and  canopies 


425 

425 
425 
428 
430 
430 
431 
432 
436 
436 
436 

437 

437 
437 
437 
438 
438 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 

TABLE  OF  CONTENTS  -  continued 


Chapter  33    SITE  WORK,  DEMOLITION  AND  CONSTRUCTION 


3301.0 
3302.0 
3303.0 
3304.0 
3305.0 
3306.0 
3307.0 
3308.0 
3309.0 
3310.0 
3311.0 
3312.0 
3313.0 
33140 
3315.0 


General 

Construction  documents  and  special  permits 

Tests 

Protection  of  public 

Fire  hazards 

Maintenance 

Health  hazards 

Protection  of  adjoining  property 

Existing  buildings 

Demolition  and  excavation 

Retaining  walls  and  partition  fences 

Storage  of  materials  and  construction  equipment 

Removal  of  waste  material 

Stairways 

Lighting 


441 

441 
441 
441 
441 
442 
442 
442 
443 
443 
443 
444 
444 
444 
444 
444 


Chapter  34    REPAIR,  ALTERATION,  ADDITION  AND  CHANGE  OF  USE 
OF  EXISTING  STRUCTURES 

(This  chapter  is  entirely  unique  to  Massachusetts) 


3400.0 
3401.0 
3402.0 
3403.0 
3404.0 

3405.0 
3406.0 
3407.0 
3408.0 
3409.0 


Scope 
Definitions 
Implementation 
Hazard  index 

Requirements  for  continuation  of  the  same  use  group  or  change  to  a  use  group 
resulting  in  a  change  in  hazard  index  of  one  or  less 

Requirements  for  change  in  use  group  to  two  or  more  hazard  indices  greater 
Compliance  alternatives 
Energy  provisions  for  existing  buildings 
Structural  requirements  for  existing  buildings 
Historic  buildings 


Chapter  35:    MANUFACTURED  BUILDINGS,  MANUFACTURED 

BUELDrNG  COMPONENTS  AND  MANUFACTURED  HOUSENG 

(This  chapter  is  entirely  unique  to  Massachusetts) 


3501.0 
3502.0 
3503.0 
3504.0 
3505.0 
3506.0 
3507.0 
3508.0 
3509.0 


General 

Definitions 

Construction  documents 

Approval 

Certification 

Reciprocity 

Assurance  inspection 

Responsibility  of  the  local  enforcement  agencies 

Suspension  or  revocation  of  certification 


Chapter  36:     ONE  AND  TWO  FAMELY  DWELLINGS 

3601.0:     One  and  two  family  dwelling  code  -  general  administration 

3601.1:    General 

3601.2:    Purpose 
3602.0:     Building  definitions 

3602.1:    General 

3602.2:    General  building  definitions 
3603.0:     Building  Planning 

3603. 1 :    Structural  Design  Criteria 

3603.2:    Construction  in  Areas  Subject  to  Flooding 

3603.3:    Fireresistance  rating  of  exterior  walls 

3603.4:    Dwelling  unit  separation 

3603.5:    Garage  separation 


445 

445 
446 
447 
448 

448 
449 

449 
450 
451 

458 


461 

461 
461 
462 
462 
463 
463 
463 
463 
464 

465 

465 
465 
465 
467 
467 
467 
469 
469 
474 
474 
474 
474 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  ANT)  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 


Chapter  36:     ONE  AND  TWO  FAMILY  DWELLINGS  -  continued 

3603.6:    Light,  ventilation  and  heating 

3603.6.4:    Natural  light 

3603.6.5:    Artificial  light 

3603.6.6:    Natural  ventilation 

3603.6.7:    Mechanical  ventilation 

3603.6.8:    Ventilation  of  special  spaces 
3603.7:    Room  dimensions 
3603.8:    Ceiling  height  requirements 
3603.9:    Access  to  crawl  spaces  and  attics 
3603.10:    Means  of  Egress 
3603.11:    Doors  and  hallways 
3603.12:    Landings 
3603.13:    Stairways 
3603.14:    Handrails  and  guardrails 
3603.15:    Ramps 
3603. 1 6:    Fire  protection  systems 
3603. 1 7:    Foam  plastic 

3603. 1 8:    Interior  finish  requirements/flame  spread  and  smoke  developed 
3603. 19:    Insulation/flame  spread,  smoke  developed/critical  radiant  flux 
3603.20:    Glazing 

3603.20.4:    Safety  glazing 


3603.20.5:    Sloped  glazing  and  skylights 


3603.21 
3603.22 
3603.23 
3603.24 
3603.25 


3604.0:    Foundations 


Energy  conservation  requirements 

Protection  against  decay  and  termites 

Manufactured  buildings  and  manufactured  housing 

Sanitation 

Electrical  requirements 


3604.1 
3604.2 
3604.3 
3604.4 
3604.5 
3604.6 
3604.7 
3604.8 
3604.9 
:  Floors 
3605.1 
3605.2 
3605.3 
3605.4 
3605.5 
3605.6 


General 

Materials 

Footings 

Foundation  walls 

Foundation  drainage 

Foundation  waterproofing  and  dampproofing 

Foundation  insulation 

Columns 

Crawl  space 


General 

Floor  Framing 

Floor  sheathing 

Treated-wood  floors  (on  ground) 

Concrete  floors  (on  grade) 

Metal 

3606.0:    Wall  Construction 
3606. 1 .    General 
3606.2:    Wall  framing 
3606.3:    Mete! 

3606.4:    General  masonry  construction 
3606.5:    Unit  masonry 
3606.6:    Multiple  wythe  masonry 
3606.7:    Grouted  masonry 
3606.8:    Windows 
3606.9:    Sliding  glass  doors 
3606. 10:    Plywood  and  wood  structural  panels 
3606.11:    Particleboard 


Page 


474 
475 
475 
476 
476 
476 
477 
477 
477 
477 
478 
478 
478 
479 
479 
480 
481 
482 
482 
482 
483 
484 
485 
485 
486 
487 
487 
489 
489 
490 
490 
494 
497 
498 
499 
499 
499 
501 
501 
501 
525 
527 
527 
528 
529 
529 
529 
536 
536 
544 
544 
545 
547 
548 
548 
548 


780  CMR  -  Sixth  Edition 


2/7/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TABLE  OF  CONTENTS 

TABLE  OF  CONTENTS  -  continued 

Page 


Chapter  36:     01s 

JE  AND  TWO  FAMILY  DW 

3607.0:    WallCovenng 

3607.1 

General 

3607.2 

Interior  covering 

3607.3 

Exterior  covering 

3608.0:    Roof- 

ceiling  construction 

3608.1 

General 

3608.2 

Roof  framing 

3608.3 

Roof  sheathing 

3608.4 

Metal 

3608.5 

Ceiling  finishes 

3608.6 

Roof  ventilation 

3608.7 

Attic  access 

3609.0:    Roof 

;overings 

3609.1 

General 

3609.2 

Deck  preparation 

3609.3 

Asphalt  shingles 

3609.4 

Slate  shingles 

3609.5 

Metal 

3609.6 

Tile,  clay,  or  concrete  shingles 

3609.7 

Built-up  roofing 

3609.8 

Wood  shingles 

3609.9 

Wood  shakes 

3609.1 

0:    Reroofing 

■  continued 


3610.0:    Chimneys  and  fireplaces 
General 

3610.2  Masonry  chimneys 

3610.3  Factory-built  chimneys 

3610.4  Masonry  fireplaces 

3610.5  Factory-built  fireplaces 
3610.6 

36 11.0:    Mechanical  administration    (This  section  is  entirely  unique  to  Massachusetts) 

3611.1:    General 

3611.2:    Existing  mechanical  systems 
3612.0:    Mechanical  definitions 

3612.1:    General 

3612.2:    General  mechanical  definitions 
3613.0:    General  mechanical  system  requirements(77iw  section  is  entirely  unique  to  Massachusetts) 


3613.1 
3613.2 
3613.3 
3613.4 
3613.5 
3613.6 
3613.7 
3613.8 


General 

Approval 

Labeling  of  equipment  not  under  the  control  of  527  CMR  or  248  CMR 

Type  of  fuel 

Appliance  access 

Clearances  from  combustible  construction 

Appliance  installation 

Control  devices 


36 14.0:    Heating  and  cooling  equipment  (This  section  is  entirely  unique  to  Massachusetts) 


3614.1 
3614.2 
3614.3 


General 

Heat  pump  equipment 

Refrigeration  cooling  equipment 


3615.0:    Electric  resistance  heating 


3615.1 
3615.2 
3615.3 


General 

Radiant  heating  systems 

Duct  heaters 


3616.0:    Vented  floor,  wall  and  room  heaters 


3616.1 
3616.2 
3616.3 


General 

Vented  wall  furnaces/additional  requirements 

Vented  room  heaters/additional  requirements 


549 
549 
549 
552 
557 
557 
557 
559 
560 
561 
561 
561 
591 
591 
591 
591 
592 
593 
593 
593 
594 
594 
596 
599 
599 
599 
601 
601 
606 
617 

611 
611 
611 
613 
613 
613 

619 
619 
619 

619 
619 
619 
619 
620 
622 

623 
623 
624 
624 
625 
625 
625 
625 
627 
627 
627 
627 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  OF  CONTENTS  -  continued 


Chapter  36:     ONE  AND  TWO  FAMILY  DWELLINGS  -  continued 


3618.1 
3618.2 
3618.3 
3618.4 


3621.1 

General 

3621.2 

Vent  components 

3621.3 

Chimney  and  vent  connectors 

3621.4 

Vents 

3621.5 

Masonry  and  factory-built  chimneys 

Solar 

systems 

3622.1 

General 

3622.3 

Labeling 

3622.4 

Prohibited  heat  transfer  fluids 

Page 


3617.0:    Ventilation  air  supply  629 

3618.0:    Exhaust  systems  631 


Clothes  dryer  exhaust  63 1 

Range  hoods  63 1 

Installation  of  microwave  ovens  63 1 

Overhead  ventilating  hoods  63 1 


3619.0:    Duct  systems  633 

3619.1:    Duct  construction  633 

3619.2:    Return  air  634 

3619.3:    Supply  air  635 

3620.0:    Combustion  air  637 

3620.0:    General  637 

3620.2:    All  air  from  inside  the  building  637 

3620.3:    All  combustion  air  from  outside  the  building  637 

3620.4:    Combined  use  of  indoor  and  outdoor  air  for  combustion  638 

3621.0:    Chimneys  and  vents  643 

643 
643 
644 
644 
645 
647 
647 
627 
647 

LIST  OF  APPENDICES 

A:    Referenced  Standards  649 

B:    Sample  Building  Permit  Application  Forms  669 

State  Building  Code  Appeals  Application  Forms  677 

Official  Interpretations  682 

C:    Recommended  Fastening  Schedule  709 

D:    Guidance  For  Selection  of  Foundation  Material  Classes  in  Table  1804.3  713 

E:    ProcedurefFor  Accounting  for  Series  and  Parallel  Heat  Flows                                              715 
F:    Reference  Data  for  Repair,  Addition,  and  Change  of  Use  of 

Existing  Buildings  717 

G:    Unit  Dead  Loads  for  Design  Purposes  737 

H:    Historic  Buildings  745 

I:    Independent  Structural  Engineering  Review  75 1 

J:    Energy  provisions  753 

K:    Floor  protector  thermal  conductivity  calculations  761 

780  CMR  -  SPECIAL  RULES  AND  REGULATIONS 


Concrete  Testing  Laboratories  Licensing  763 

Concrete  Testing  Personnel  Licensing  767 

Manufactured  Buildings,  Building  Components  and  Mobile  Homes  769 

Use  of  Native  Lumber  783 

Construction  Supervisors  785 

Registration  and  Enforcement  of  Home  Improvement  Contractor  Program  789 

Certification  of  Inspectors  of  Buildings.  Building  Commissioners  and  Local  Inspectors  801 


INDEX  807 


780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  1 

ADMINISTRATION 

(Substantial  portions  of  this  Chapter  are  entirely  unique  to  Massachusetts) 


780  CMR  101.0  SCOPE 

101.1  Title:    780   CMR  shall   be   known   as  the 
Commonwealth  of  Massachusetts  State  Building 
Code. 

101.2  Scope:  780  CMR,  in  accordance  with  St. 
1984,  c.  348,  as  amended  shall  control  all  matters 
concerning; 

(a)  the  construction,  reconstruction,  alteration, 
repair,  demolition,  removal,  inspection,  issuance 
and  revocation  of  permits  or  licenses,  installation 
of  equipment,  classification  and  definition  of  any 
building  or  structure  and  use  or  occupancy  of  all 
buildings  and  structures  or  parts  thereof  except 
bridges  and  appurtenant  supporting  structures 
which  have  been  or  are  to  be  constructed  by,  or 
are  under  the  custody  and  control  of  the 
Department  of  Public  Works  (Massachusetts 
Highway  Department),  the  Massachusetts 
Turnpike  Authority,  the  Massachusetts  Bay 
Transportation  Authority,  the  Metropolitan 
District  Commission,  or  the  Massachusetts  Port 
Authority  or  for  which  said  agencies  have 
maintenance  responsibility; 

(b)  the  rehabilitation  and  maintenance  of  existing 
buildings; 

(c)  the  standards  or  requirements  for  materials  to 
be  used  in  connection  therewith,  including  but  not 
limited  to  provisions  for  safety,  ingress  and 
egress,  energy  conservation  and  sanitary 
conditions; 

(d)  the  establishment  of  reasonable  fees  for 
inspections  and  the  issuance  of  licenses  to 
individuals  engaged  as  construction  supervisors; 

(e)  the  certification  of  inspectors  of  buildings, 
building  commissioners  and  local  inspectors  and; 

(f)  the  registration  of  Home  Improvement 
Contractors  pursuant  to  MGL  c  142A,  except  as 
such  matters  are  otherwise  provided  for  in  the 
Massachusetts  General  Laws  Annotated,  or  in  the 
rules  and  regulations  authorized  for  promulgation 
under  the  provisions  of  780  CMR. 

(g)  other  duties  and  responsibilities  as  defined  in 
780  CMR  Rl  through  R7. 

101.3  Application  of  references:  Unless  otherwise 
specifically  provided  for  in  780  CMR,  all  references 
to  chapter  or  section  numbers,  or  to  provisions  not 
specifically  identified  by  number,  shall  be  construed 
to  refer  to  such  chapter,  section  or  provision  of 
780  CMR. 

101.4  Intent:  780  CMR  shall  be  construed  to  secure 
its  expressed  intent,  which  is  to  insure  public  safety, 
health  and  welfare  insofar  as  they  are  affected  by 


building  construction,  through  structural  strength, 
adequate  means  of  egress  facilities,  sanitary 
conditions,  light  and  ventilation,  energy 
conservation  and  fire  safety;  and,  in  general,  to 
secure  safety  to  life  and  property  from  all  hazards 
incident  to  the  design,  construction,  reconstruction, 
alteration,  repair,  demolition,  removal,  use  or 
occupancy  of  buildings,  structures  or  premises. 

101.5  Specialized  Codes:  Specialized  codes,  rules 
or  regulations  pertaining  to  building  construction, 
reconstruction,  alteration,  repair  or  demolition, 
promulgated,  and  under  the  authority  of  the  various 
boards  which  have  been  authorized  by  the  general 
court  shall  be  incorporated  into  780  CMR.  The  said 
specialized  codes,  rules  or  regulations  include,  but 
are  not  limited  to,  those  listed  in  Appendix  A. 

101.6  Referenced  standards:  The  standards 
referenced  in  780  CMR  and  listed  in  Appendix  A 
shall  be  considered  part  of  the  requirements  of 
780  CMR  to  the  prescribed  extent  of  each  such 
reference.  Where  differences  occur  between 
provisions  of  780  CMR  and  referenced  standards, 
the  provisions  of  780  CMR  shall  apply.  The 
administrative  provisions  of  780  CMR  shall  apply  to 
all  standards  referenced  in  Appendix  A,  other  than 
the  specialized  codes  in  780  CMR  101.5. 

780  CMR  102.0  APPLICABILITY 

102.1  General:  The  provisions  of  780  CMR  shall 

apply  to  all  matters  affecting  or  relating  to  buildings 
and  structures,  as  set  forth  in  780  CMR  101.0  and 
shall  apply  with  equal  force  to  municipal,  county, 
state  authorities  of  or  established  by  the  legislature 
and  private  buildings  and  structures,  except  where 
such  buildings  and  structures  are  otherwise  provided 
for  by  statute.  The  construction,  reconstruction, 
alteration,  repair,  addition,  change  in  use  or 
occupancy,  demolition,  removal  of  all  buildings  and 
structures  shall  comply  with  780  CMR. 

102.2  Matters  not  provided  for:  Any  requirements 
that  are  essential  for  the  structural,  fire  or  sanitary 
safety,  interior  climate  comfort  of  an  existing  or 
proposed  building  or  structure,  or  for  the  safety  of 
the  occupants  thereof,  which  are  not  specifically 
provided  for  by  780  CMR,  shall  be  determined  by 
the  building  official.  The  State  Board  of  Building 
Regulations  and  Standards  (hereinafter  referred  to  as 
the  BBRS)  and  the  Department  of  Public  Safety 
shall  be  notified  by  the  building  official  in  writing 
within  seven  working  days  of  any  action  taken 
pursuant  to  780  CMR  102.2. 


2/7/97    (Effective  2/28/971 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


102.3  Zoning  Bylaw  Restrictions:  When  the 
provisions  herein  specified  for  structural  strength, 
adequate  egress  facilities,  sanitary  conditions, 
equipment,  light  and  ventilation,  energy 
conservation  or  fire  safety  conflict  with  the  local 
zoning  bylaws  or  ordinances,  780  CMR  shall  control 
the  construction  or  al.jration  of  buildings  and 
structures  unless  such  bylaws  or  ordinances  are 
promulgated  in  accordance  with  the  provisions  of 
M.G.L.  c.  143,  §  98  . 

102.4  General  bylaw  restrictions:  When  the 
provisions  herein  specified  for  structural  strength, 
adequate  egress  facilities,  sanitary  conditions, 
equipment,  light  and  ventilation,  energy 
conservation  or  fire  safety  conflict  with  the  local 
general  bylaws  or  ordinances,  780  CMR  shall 
control  the  construction  or  alteration  of  buildings 
and  structures  unless  such  bylaws  or  ordinances  are 
promulgated  in  accordance  with  the  provisions 
M.G.L.  c.  143,  §  98. 

102.5  Applicability  to  Existing  Buildings 

102.5.1  General:  Existing  buildings  and 
structures  shall  comply  with  the  provisions  of 
780  CMR  102.5  and  all  other  applicable 
provisions  of  780  CMR. 

102.5.2  Unless  specifically  provided  otherwise  in 
780  CMR,  any  existing  building  or  structure  shall 
meet  and  shall  be  presumed  to  meet  the  provisions 
of  the  applicable  laws,  codes,  rules  or  regulations, 
bylaws  or  ordinances  in  effect  at  the  time  such 
building  or  structure  was  constructed  or  altered 
and  shall  be  allowed  to  continue  to  be  occupied 
pursuant  to  its  use  and  occupancy,  provided  that 
the  building  or  structure  shall  be  maintained  in 
accordance  with  780  CMR  103.0. 

102.5.3  In  cases  which  applicable  codes,  rules  or 
regulations,  bylaws  or  ordinances  were  not  in  use 
at  the  time  of  such  construction  or  alteration,  the 
provisions  of  780  CMR  103.0  shall  apply. 

102.5.4  In  cases  where  the  provisions  of 
780  CMR  are  less  stringent  than  the  applicable 
codes,  rules  or  regulations,  bylaws  or  ordinances 
at  the  time  of  such  construction  or  substantial 
alteration,  the  applicable  provisions  of  780  CMR 
shall  apply,  providing  such  application  of  these 
provisions  does  not  result  in  danger  to  the  public, 
as  determined  by  the  building  official. 

102.5.5  Existing  buildings  or  parts  or  portions 
thereof  which  are  proposed  to  be  enlarged, 
altered,  repaired  or  changed  in  use  or  occupancy 
shall  comply  with  the  provisions  of  780  CMR  34. 

102.5.6  Moved  Structures:  Buildings  or 
structures  moved  into  or  within  the  jurisdiction 
shall  comply  with  the  provisions  of  780  CMR  34 
provided  that  any  new  system  shall  comply  as  far 
as  practicable  with  the  requirements  for  new 


structures  and  provided  further  that  the  siting  and 
fire  separation  distance  comply  with  the 
requirements  for  new  structures. 

780  CMR  103.0  MAINTENANCE 

103.1  General:  All  buildings  and  structures  and  all 
parts  thereof,  both  existing  and  new,  and  all  systems 
and  equipment  therein  which  are  regulated  by 
780  CMR  shall  be  maintained  in  a  safe,  operable  and 
sanitary  condition.  All  service  equipment,  means  of 
egress,  devices  and  safeguards  which  are  required  by 
780  CMR  in  a  building  or  structure,  or  which  were 
required  by  a  previous  statute  in  a  building  or 
structure,  when  erected,  altered  or  repaired,  shall  be 
maintained  in  good  working  order. 

103.2  Owner  responsibility:  The  owner,  as 
defined  in  780  CMR  2,  shall  be  responsible  for 
compliance  with  provisions  of  780  CMR  103.0. 

780  CMR  104.0  VALIDITY 
104.1    General:    The  provisions. of  780  CMR  are 

severable,  and  if  any  of  its  provisions  shall  be  held 
unconstitutional  or  otherwise  invalid  by  any  court  of 
competent  jurisdiction,  the  decision  of  such  court 
shall  not  affect  or  impair  any  of  the  remaining 
provisions. 

780  CMR  105.0  OFFICE  OF  THE 

INSPECTOR  OF  BUILDINGS  OR 

BUILDING  COMMISSIONER 

105.1  Appointment:  The  chief  administrative 
officer  of  each  city  or  town  shall  employ  and 
designate  an  inspector  of  buildings  or  building 
commissioner  (hereinafter  inspector  of  buildings)  as 
well  as  such  other  local  inspectors  as  are  reasonably 
necessary  to  assist  the  inspector  of  buildings  to 
administer  and  enforce  780  CMR  and  of  M.G.L. 
c.  22,  §  13  A  and  the  rules  and  regulations  made 
under  the  authority  thereof.  The  inspector  of 
buildings  shall  report  directly  to  and  be  solely 
responsible  to  the  appointing  authority. 

105.2  Alternate:  The  inspector  of  buildings  is 
authorized  to  designate  an  alternate  who  shall 
exercise  all  the  powers  of  the  inspector  of  buildings 
during  the  temporary  absence,  disability  or  conflict 
of  interest  of  the  inspector  of  buildings.  Said 
alternate  shall  be  duly  qualified  pursuant  to 
780  CMR  105.3. 

105.3  Qualifications  of  the  Inspector  of  Buildings: 

In  accordance  with  the  provisions  of  M.G.L.  c.  143, 
§  3,  each  inspector  of  buildings  shall  have  had  at 
least  five  years  of  experience  in  the  supervision  of 
building  construction  or  design  or  in  the  alternative 
a  four  year  undergraduate  degree  in  a  field  related  to 
building  construction  or  design,  or  any  combination 
of  education  and  experience  which  would  confer 
equivalent  knowledge  and  ability,  as  determined  by 
the  BBRS.    In  addition  each  inspector  of  buildings 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


shall  have  had  general  knowledge  of  the  accepted 
requirements  for  building  construction,  fire 
prevention,  light,  ventilation  and  safe  egress;  as  well 
as  a  general  knowledge  of  other  equipment  and 
materials  essential  for  safety,  comfort  and 
convenience  of  the  occupants  of  a  building  or 
structure. 

Each  inspector  of  buildings  shall  be  certified  by 
the  BBRS  in  accordance  with  the  provisions  of 
780  CMR  R7,  the  Rules  and  Regulations  for  the 
Certification  of  Inspectors  of  Buildings,  Building 
Commissioners  and  Local  Inspectors. 

Municipalities  may  require  additional 
qualifications  or  experience  as  are  deemed 
necessary. 

105.4  Qualifications  of  the  local  inspector:     In 

accordance  with  the  provisions  of  M.G.L.  c.  143, 
§  3,  each  local  inspector  shall  have  had  at  least  five 
years  of  experience  in  the  supervision  of  building 
construction  or  design  or  in  the  alternative  a  two 
year  associates  degree  in  a  field  related  to  building 
construction  or  design,  or  any  combination  of 
education  and  experience  which  would  confer 
equivalent  knowledge  and  ability,  as  determined  by 
the  BBRS.  In  addition,  such  persons  shall  have  had 
general  knowledge  of  the  accepted  requirements  for 
building  construction,  fire  prevention,  light, 
ventilation  and  safe  egress;  as  well  as  a  general 
knowledge  of  other  equipment,  and  materials 
essential  for  safety,  comfort  and  convenience  of  the 
occupants  of  a  building  or  structure. 

Each  local  inspector  shall  be  certified  by  the 
BBRS  in  accordance  with  the  provisions  of 
780  CMR  R7,  the  Rules  and  Regulations  for  the 
Certification  of  Inspectors  of  Buildings,  Building 
Commissioners  and  Local  Inspectors. 

Municipalities  rhay  require  additional 
qualifications  or  experience  as  are  deemed 
necessary. 

105.5  Reporting  Requirements: 

105.5.1    Annual  report  by  city  or  town  clerk: 

In  accordance  with  the  provisions  of  M.G.L. 
c.  143,  §  3,  the  clerk  of  each  city  or  town  shall, 
annually,  not  later  than  April  first,  transmit  to  the 
BBRS  the  names  and  official  address  of  each 
inspector  of  buildings,  building  commissioner  and 
local  inspector  as  well  as  at  such  other  times  as 
required  pursuant  to  780  CMR  R7,  the  Rules  and 
Regulations  for  the  Certification  of  Inspectors  of 
Buildings,  Building  Commissioners  and  Local 
Inspectors.  Such  reports  shall  be  submitted  on 
forms  prescribed  by  the  BBRS  for  said  purpose. 

105.5.2.  New  appointments:  The  clerk  of  each 
city  or  town  shall  additionally  report  to  the  BBRS, 
the  name,  capacity  and  status  of  any  new 
appointee  within  the  time  periods  prescribed  in 
780  CMR  R7  on  forms  prescribed  by  the  BBRS 
for  said  purpose. 


105.6  Restriction  of  employees:  No  full-time  or 
part-time  building  commissioner,  inspector  of 
buildings,  or  full-time  or  part-time  local  inspector  as 
defined  herein  shall  be  engaged  in,  or  directly  or 
indirectly  connected  with,  the  furnishing  of  labor, 
materials  or  appliances  for  the  construction, 
alteration  or  maintenance  of  a  building  or  structure, 
or  the  preparation  of  plans  or  of  specifications 
therefore  within  the  city,  town  or  region  for  which 
he  or  she  is  appointed,  unless  he  or  she  is  the  owner 
of  the  building  or  structure;  nor  shall  any  officer  or 
employee  associated  with  the  building  department 
engage  in  any  work  which  conflicts  with  his  or  her 
official  duties  or  with  the  interests  of  the  department. 

Note:  See  M.G.L.  c.  143,  §  3Z  (Local  OptionTaw 
relative  to  part-time  employees). 

105.7  Relief  from  personal  liability:  Insofar  as  the 
law  allows,  while  acting  for  the  municipality,  the 
building  official,  charged  with  the  enforcement  of 
780  CMR  shall  not  be  deemed  personally  liable  in 
the  discharge  of  his  official  duties. 

105.8  Official  records:  An  official  record  shall  be 
kept  of  all  business  and  activities  of  the  department 
specified  in  the  provisions  of  780  CMR.  In 
accordance  with  the  provisions  of  M.G.L.  c.  66, 
§  10(b),  all  such  records  shall  be  open  to  public 
inspection  at  all  appropriate  times  and  according  to 
reasonable  rules  to  maintain  the  integrity  and 
security  of  such  records. 

780  CMR  106.0  DUTIES  AND  POWERS  OF 
THE  BUILDING  OFFICIAL 

106.1  General:  The  inspector  of  buildings  and  local 
inspector  (herein  after  building  official)  shall 
enforce  all  of  the  provisions  of  780  CMR,  521  CMR 
(Architectural  Access  Board)  and  any  other  state 
statutes,  rules  and  regulations,  or  ordinances  or 
bylaws  which  empower  the  building  official.  The 
building  official  shall  act  on  any  question  relative  to 
the  mode  or  manner  of  construction  and  materials  to 
be  used  in  the  construction,  reconstruction, 
alteration,  repair,  demolition,  removal,  installation  of 
equipment  and  the  location,  use,  occupancy  and 
maintenance  of  all  buildings  and  structures,  except 
as  otherwise  specifically  provided  for  by  statutory 
requirements  or  as  provided  for  in  780  CMR  109.0. 

106.2  Applications  and  permits:  The  building 
official  shall  receive  applications  and  issue  permits 
for  the  construction,  reconstruction,  alteration, 
repair,  demolition,  removal  or  change  in  use  or 
occupancy  of  buildings  and  structures;  inspect  the 
premises  for  which  such  permits  have  been  issued 
and  enforce  compliance  with  the  provisions  of 
780  CMR. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


15 


7S0  CMR:    STATE  BOARD  OF  BUILD[NG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


106.3  Notices  and  orders:  The  building  official 
shall  issue  all  necessary  notices  or  orders  to  ensure 
compliance  with  780  CMR. 

106.4  Inspections:  The  building  official  shall  make 
such  inspections  as  deemed  necessary  to  ensure 
compliance  with  780  CMR,  or  the  building  official 
may  accept  reports  of  inspection  by  qualified 
agencies  or  individuals,  which  reports  shall  be  in 
writing  and  be  certified  by  a  responsible  officer  of 
such  agency  or  by  the  responsible  individual. 

106.5  Inspection  and  certification  of  specified  use 
groups:  The  building  official  shall  periodically 
inspect  and  certify  buildings  and  structures  or  parts 
thereof  in  accordance  with  Table  106.  A  building  or 
structure  shall  not  be  occupied  or  continue  to  be 
occupied  without  the  posting  of  a  valid  certificate  of 


inspection  where  required  by  Table  106.  A 
certificate  of  inspection  as  herein  specified  shall  not 
be  issued  until  an  inspection  is  made  certifying  that 
the  building  or  structure  or  parts  thereof  complies 
with  all  the  applicable  requirements  of  780  CMR, 
and  until  the  fee  is  paid  as  specified  in  Table  106. 
Municipalities  may  increase  or  waive  only  in  their 
entirety  for  any  specific  use  group  the  fees  as 
specified  in  said  Table  106. 

Exception:  Municipalities  may  revise  or  modify, 
or  waive  in  part  those  fees  for  buildings  and 
structures  or  parts  thereof  owned  by  the 
municipality,  county  or  political  subdivision 
thereof  and  for  buildings  and  structures  or  parts 
thereof  used  solely  for  religious  purposes. 


TABLE  106 

REQUIRED  MINIMUM  INSPECTIONS  AND  CERTIFICATIONS  FOR  SPECIFIED  USE  GROUPS 
(See  Chapters  3  and  4  for  complete  description  of  use  groups) 


Use 
Group 

Use  Group 

Use  Group  Description 

Minimum 
Inspections 

Maximum 

Certification 

Period 

Fees  for  Maximum 

Certification 

Period 

A-l 

Assembly  -  Theaters 
over  400  capacity 

With  stage  and  scenery 
Movie  Theater 

Semi-  Annual 
Semi-  Annual 

One  Year 
One  Year 

$75 
$75 

A-l 

Assembly  -  Theaters 
400  or  less  capacity 

With  stage  and  scenery 
Movie  Theater 

Annual 
Annual 

One  Year 
One  Year 

$40 
$40 

A-2 

Assembly  -  Night  Clubs 
or  similar  uses 

Over  400  capacity 
400  or  less  capacity 

Semi  Annual 
Annual 

One  Year 
One  Year 

$75 
$40 

A-3 

Assembly  Lecture 
Halls,  recreation  centers, 
terminals,  etc. 

Over  400  capacity 
400  or  less  capacity 

Semi  Annual 
Annual 

One  Year 
One  Year 

note  a 

$40 

A-4 

Assembly 

Churches,  low  density,  recreation 
&  similar  uses 

Prior  to  issuance  of 
each  new  certificate 

Five  Years 

$40 

A-5 

Assembly 

Stadiums,  bleachers,  places  of 

outdoor  assembly 

Prior  to  issuance  of 
each  new  certificate 

One  Year 

noteb 

E 

Educational 

Educational 

Prior  to  issuance  of 
each  new  certificate 

One  Year 

$40 

E 

Day  Care 

Child  day  care  centers 
(see  Chapter  4) 

Prior  to  issuance  of 
each  new  certificate 

One  Year 

$40 

1-2 

Institutional 

Incapacitated  -  hospitals,  nursing 
homes,  mental  hospitals,  certain 
day  care  facilities  (see  Chapter  4) 

Prior  to  issuance  of 
each  new  certificate 

Two  Years 

note  d 

1-3 

Institutional 

Restrained  -  prisons,  jails, 
detention  centers,  etc. 

Prior  to  issuance  of 
each  new  certificate 

Two  Years 

notec 

R-l 

Residential 

Hotels,  motels,  lodging  houses, 
dormitories,  etc.  (note  g) 

Prior  to  issuance  of 
each  new  certificate 

One  Year 

note  e 

R-2 

Residential 

Multi  family  (note  g) 

Prior  to  issuance  of 
each  new  certificate 

Five  Years 

notef 

R-l 

Residential  Special 
Occupancy 

Detoxification  facilities 
(see  Chapter  4) 

Prior  to  issuance  of 
each  new  certificate 

Two  Years 

$75 

R-2 

Residential  Special 
Occupancy 

Summer  camps  for  children 
(see  chapter  41 

Annual 

One  Year 

noteh 

R-3or 
R-4 

Residential  Special 
Occupancy 

Group  Residence 
(see  Chapter  41 

Annual 

One  Year 

note  h 

R-5 

Residential  Special 
Occupancy 

Limited  Group  Residence 
(see  Chapter  4) 

Annual 

One  Year 

noteh 

Notes  applicable  to  Table  106 

General:  The  maximum  certification  period  specified  in  Table  106  is  intended  to  provide  administrative  flexibility. 
For  those  buildings  and  structures  or  parts  thereof  allowing  more  than  one  year  maximum  certification  period,  the 
building  official  may  determine  the  length  of  validity  of  the  certificate  issued.  For  example,  a  building  in  the  R-2  use 
group  could  be  issued  a  certificate  valid  for  one.  two.  three,  four  or  five  years.  The  total  amount  of  fees  charged  for 
a  certificate  or  certificates  issued  during  the  maximum  certification  period  can  exceed  the  fee  listed  or  referenced  in 


16 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 

column  4  of  Table  106.    For  example,  if  the  building  official  issues  a  certificate  valid  for  two  years  for  a  building  in 

the  R-2  use  group,  the  fee  charged  would  be  2/5  times  the  fee  per  maximum  certification  period  as  determined  for  the 

building  in  question  using  the  formula  in  Note  f. 

Note  a.   For  buildings  or  structures,  or  parts  thereof,  in  the  A-3  Use  Group  categories,  with  capacities  over  400.  the 

fee  to  be  charged  for  the  maximum  certification  period  of  one  year  is  $75  for  accommodations  for  up  to  5,000  pcsons. 

plus  S15  for  the  accommodations  for  each  additional  1,000  persons  or  fraction  thereof. 

Note  b.    For  all  buildings  or  structures,  or  parts  thereof,  in  A-5  use  group,  the  fee  to  be  charged  for  the  maximum 

certification  period  of  one  year  is  $40  for  seating  accommodations  for  up  to  5,000  persons,  plus  $8  for  the 

accommodation  for  each  additional  1 .000  persons  or  fraction  thereof. 

Note  c.   For  all  buildings  and  structures,  or  parts  thereof,  in  the  1-3  use  group,  the  fee  to  be  charged  for  the  maximum 

certification  period  of  two  years  is  $75  for  each  structure  containing  up  to  100  beds,  plus  a  $2  charge  for  each 

additional  ten  beds  or  fraction  thereof  over  the  initial  100  beds. 

Note  d.   For  hospitals,  nursing  homes,  sanitariums,  and  orphanages  in  the  1-2  use  group,  the  fee  to  be  charged  for  the 

maximum  certification  period  of  two  years  is  $75  for  each  structure  containing  up  to  100  beds,  plus  a  $2  charge  for 

each  additional  ten  beds  or  fraction  thereof  over  the  initial  100  beds.  All  other  buildings  or  structures  or  parts  thereof 

in  the  1-2  use  group  classification  shall  be  charged  a  fee  of  $75  for  a  two  year  maximum  certification  period. 

Note  e.   For  all  buildings  and  structures  or  parts  thereof  in  the  R- 1  use  group,  the  fee  to  be  charged  for  the  maximum 

certification  period  of  one  year  shall  be  $40  for  up  to  five  units  plus  $2  per  unit  for  all  over  five  units.  A  unit  shall  be 

defined  as  follows: 

two  hotel  guest  rooms: 

two  lodging  house  guest  rooms; 

two  boarding  house  guest  rooms;  or 

four  dormitory  beds 
Note  f.  For  all  buildings  and  structures  or  pans  thereof  in  the  R-2  use  group,  the  fee  to  be  charged  for  the  maximum 
certification  period  of  five  years  shall  be  $75,  plus  $2  per  dwelling  unit. 

Note  g.    For  purposes  of  determining  the  required  number  of  inspections,  the  maximum  certification  period,  and  the 
fees,  as  specified  in  Table  106,  dormitories  are  included  in  the  R-l  use  group  classification  rather  than  the  R-2. 
Note  h.   Summer  camps  for  children  in  use  group  R-2  shall  be  inspected  and  certified  annually  prior  to  the  beginning 
of  each  season.  The  annual  fee  shall  be  $  15  for  the  first  25  residential  units:  $8  for  each  additional  25  residential  units: 
and  $15  for  each  assembly  building  or  use.  (A  residential  unit  for  this  purpose  shall  be  defined  as  four  beds). 


106.6  Reports  by  the  Building  Official 

106.6.1  Report  to  Appointing  Authority:   The 

building  official  shall  submit  to  the  appointing 
authority  of  the  jurisdiction  a  written  report  of 
operations  in  a  form  and  content  and  at  intervals 
as  shall  be  prescribed  by  the  appointing  authority. 

106.6.2  Report  to  assessors:  Pursuant  to 
M.G.L.  c.  143,  §  $1,  the  building  official  shall 
give  to  the  assessors  of  the  municipality  written 
notice  of  the  granting  of  permits  for  the 
construction  of  any  buildings  or  structures,  or  for 
the  removal  or  demolition,  or  for  any  substantial 
alteration  or  addition  thereto.  Such  notice  shall  be 
given  within  seven  days  after  the  granting  of  each 
permit,  and  shall  state  the  name  of  the  person  to 
whom  the  permit  was  granted  and  the  location  of 
the  building  or  structure  to  be  constructed, 
reconstructed,  altered,  demolished  or  removed. 

106.6.3  Report  to  Local  United  States 
Postmaster:  Pursuant  to  M.G.L.  c.  143,  §  3X  the 
building  official  shall  notify  the  local  United 
States  Postmaster  of  the  issuance  of  a  building 
permit  authorizing  the  construction  of  any 
building  containing  ten  or  more  residential  units. 

106.7  Department  records:  The  building  official 
shall  maintain  official  records  of  applications 
received,  permits  and  certificates  issued,  inspections 
performed  fees  collected,  reports  of  inspections,  and 
notices  and  orders  issued      Such  records  shall  be 


retained  in  the  official  records  as  long  as  the 
building  or  structure  to  which  they  relate  remains  in 
existence  unless  otherwise  provided  for  by  law. 

780  CMR  107.0  DUTIES  AND  POWERS  OF 

THE  STATE  INSPECTOR 

(M.G.L.  c.  143,  §  3A) 

107.1  The  State  Inspector:  In  every  city  and  town 
780  CMR  shall  be  enforced  by  the  State  Inspector  of 
the  Department  of  Public  Safety,  Division  of 
Inspections,  as  to  any  structures  or  buildings  or  parts 
thereof  that  are  owned  by  the  Commonwealth  or  any 
departments,  commissions,  agencies,  or  authorities 
of  the  Commonwealth.  The  state  inspector  shall 
have  as  to  such  buildings  and  structures  all  the 
powers  of  a  building  commissioner  or  inspector  of 
buildings.  All  buildings  and  structures  owned  by 
any  authority  established  by  the  legislature  and  not 
owned  by  the  Commonwealth  shall  be  regulated  in 
accordance  with  780  CMR  106.0. 

107.2  Other  responsibilities:  The  state  inspector 
shall  make  periodic  reviews  of  all  local  building 
inspection  practices,  provide  technical  assistance 
and  advice  to  the  local  building  officials  in  the 
implementation  of  780  CMR,  and  report  in  writing 
his  findings  to  the  building  officials. 

107.3  Review  by  the  Commissioner  of  Public 
Safety:  The  Commissioner  of  the  Commonwealth 
of  Massachusetts,  Department  of  Public  Safety  shall 
establish  districts  which  shall  be  supervised  by  a 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  30ARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


state  inspector  of  the  Division  of  Inspections.  The 
Commissioner  may  review,  on  his  own  initiative,  or 
on  the  application  of  any  state  inspector,  any  action 
or  refusal  or  failure  of  action  by  any  building  official 
the  result  of  which  does  not  comply  with  the 
uniform  implementation  of  780  CMR;  and  may 
reverse,  modify  or  annul,  in  whole  or  in  part,  such 
action  except  with  respect  to  the  specialized  codes, 
provided  that  an  order  or  action  of  the  Commissioner 
shall  not  reverse,  modify,  annul,  or  contravene  any 
order,  action,  determination,  interpretation  or  any 
decision  by  the  BBRS  or  the  State  Building  Code 
Appeals  Board. 

107.4  Reports:  The  state  inspector  shall  file  with 
the  BBRS  reports  of  his  periodic  reviews  and 
recommendations  for  improvements  of  building 
inspection  practices.  The  format  and  due  dates  for 
these  reports  shall  be  determined  by  the  BBRS. 

780  CMR  108.0  RULES  AND  REGULATIONS 

108.1  Rule  making  authority:  Under  authority 
granted  by  St.  1984,  c.  348,  as  amended,  the  BBRS 
is  empowered  in  the  interest  of  public  safety,  health 
and  general  welfare,  to  adopt  and  promulgate  rules 
and  regulations,  and  to  interpret  and  implement  the 
provisions  of  780  CMR  to  secure  the  intent  thereof. 

108.2  Amendments  and  promulgation  of  rules: 

In  accordance  with  the  provisions  of  M.G.L.  c.  143, 
§  97,  any  person  may  propose  amendments  to 
780  CMR.  Public  hearings  shall  be  held  in  the  city 
of  Boston  in  May  and  November  of  each  year,  and 
at  such  other  times  and  places  as  the  BBRS  may 
determine,  to  consider  petitions  for  such 
amendments.  Amendments  adopted  by  the  BBRS 
shall  be  binding  and  have  the  full  force  and  effect  in 
all  cities  and  towns. 

108.3  Activities  requiring  licenses,  registration  or 
certification: 

108.3.1  Testing  laboratories:  A  testing 
laboratory,  branch  laboratory  and/or  project 
laboratory  shall  not  test  concrete  and/or  concrete 
materials  for  use  in  structures  subject  to 
construction  control  (780  CMR  116.0)  and/or 
controlled  materials  (780  CMR  17)  unless 
licensed  by  the  BBRS  in  accordance  with 
780  CMR  and  780  CMR  Rl:  the  Rules  and 
Regulations  for  Licensing  of  Concrete  Testing 
Laboratories. 

108.3.2  Field  technicians:  A  person  shall  not 
engage  in  the  activities  of  field  testing  of  concrete 
for  use  in  structures  subject  to  construction 
control  (780  CMR  116.0)  and/or  controlled 
materials  (780  CMR  17)  unless  such  person  is 
licensed  by  the  BBRS  in  accordance  with 
780  CMR  R2:  the  Rules  and  Regulations  for 
Concrete  Testing  Personnel. 


108.3.3  Manufactured  buildings:  No  individual, 
organization  or  firm  shall  be  engaged  in  the 
construction  of  manufactured  buildings  for  use  in 
the  Commonwealth  of  Massachusetts  unless 
approved  to  construct  same  by  the  BBRS  in 
accordance  with  780  CMR  R3. 

108.3.4  Native  Lumber:  No  individual, 
organization  or  firm  shall  engage  in  the 
production  of  native  lumber  for  use  in  structures 
within  the  Commonwealth  of  Massachusetts 
unless  registered  by  the  BBRS  in  accordance  with 
780  CMR  and  780  CMR  R4:  the  Rules  and 
Regulations  Controlling  the  Use  of  Native 
Lumber. 

108.3.5  Licensing  of  Construction  Supervisors: 

108.3.5.1  Except  for  those  structures  governed 
by  Construction  Control  in  780  CMR  116.0, 
effective  July  1,  1982,  no  individual  shall  be 
engaged  in  directly  supervising  persons 
engaged  in  construction,  reconstruction, 
alteration,  repair,  removal  or  demolition 
involving  any  activity  regulated  by  any 
provision  of  780  CMR,  unless  said  individual 
is  licensed  in  accordance  the  Rules  and 
Regulations  for  Licensing  Construction 
Supervisors  as  set  forth  in  780  CMR  R5. 

No  person  shall  be  engaged  in  the 
supervision  of  the  field  erection  of  a 
manufactured  building  unless  such  person  is 
licensed  in  accordance  with  780  CMR  R5:  The 
Rules  and  Regulations  for  the  Licensing  of 
Construction  Supervisors. 

Exception:  Any  Home  Owner  performing 
work  for  which  a  building  permit  is  required 
shall  be  exempt  from  the  licensing 
provisions  of  780  CMR  108.3.5;  provided 
that  if  a  Home  Owner  engages  a  person(s) 
for  hire  to  do  such  work,  that  such  Home 
Owner  shall  act  as  supervisor.  This 
exception  shall  not  apply  to  the  field 
erection  of  a  manufactured  buildings 
constructed  pursuant  to  780  CMR  35  and 
780  CMR  R3. 

108.3.5.2  Exemptions  from  Construction 
Supervisor  License  requirement;  A 
construction  supervisor's  license  is  not 
required  for:  roofing,  siding,  erection  of 
rooftop  solar  collectors,  construction  of 
swimming  pools,  the  erection  of  signs, 
installation  of  replacement  windows  not 
involving  structural  modifications,  the  erection 
of  tents  nor  for  projects  which  are  subject  to 
construction  control  (780  CMR  1 16.0). 

A  construction  supervisor's  license  is  not 
required  for  agricultural  buildings  which  are 
not  open  to  the  public  or  otherwise  made 
available  for  public  use. 

108.3.5.3  No  municipality  shall  be  prohibited 
from  requiring  a  license  for  those  individuals 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


engaged  in  directly  supervising  persons 
engaged  in  construction,  reconstruction, 
alteration,  repair,  removal  or  demolition  in 
those  categories  of  building  and  structures  for 
which  the  BBRS  does  not  require  a  license, 
provided  that  those  municipalities  which  have 
established  licensing  requirements  for 
construction  supervisors  prior  to  January  1, 
1975,  may  maintain  their  existing  licensing 
requirements. 

108.3.6  Registration  of  Home  Improvement 
Contractors:  In  accordance  with  the  provisions 
of  M.G.L.  c.  142A  no  home  improvement 
contractor,  or  organization  or  firm  shall  be 
involved  in  the  improvement  of  any  existing 
owner  occupied  one  to  four  family  residential 
building  unless  said  home  improvement 
contractor  has  registered  with  the  BBRS  in 
accordance  with  the  rules  and  regulations  for  the 
registration  of  Home  Improvement  Contractors  as 
set  forth  in  780  CMR  R6. 

108.3.7  Certification  of  Inspectors  of  Buildings, 
Building  Commissioners  and  Local  Inspectors; 

The  rules  and  regulations  for  the  Certification  of 
Inspectors  of  Buildings,  Building  Commissioners 
and  Local  Inspectors  shall  be  as  set  forth  in 
780  CMR  R7. 

108.4  Enforcement:  Whoever  violates  the 
provisions  of  780  CMR  108.0  or  any  rules  and 
regulations  promulgated  hereunder,  or  who  falsifies 
or  counterfeits  a  license,  registration  or  certification 
issued  by  the  BBRS,  or  who  fraudulently  issues  or 
accepts  such  a  license,  registration  or  certification 
shall  be  punished  as  provided  in  780  CMR  1 18.0  or 
shall  be  subject  to  any  other  penalty  provided  for  by 
law. 

780  CMR  109.0  APPROVAL 

109.1  Approved  materials  and  equipment:  All 

materials,  equipment  and  devices  approved  by  the 
building  official  shall  be  constructed  and  installed  in 
accordance  with  such  approval. 

109.2  Used  materials  and  equipment:  Used 
materials,  equipment  and  devices  which  meet  the 
minimum  requirements  of  780  CMR  for  new 
materials,  equipment  and  devices  shall  be  permitted; 
however,  the  building  official  may  require 
satisfactory  proof  that  such  materials,  equipment  and 
devices  have  been  reconditioned,  tested,  and/or 
placed  in  good  and  proper  working  condition  prior 
to  approval. 

109.3  Alternative  materials  and  equipment: 

109.3.1  General:  The  provisions  of  780  CMR 
are  not  intended  to  limit  the  appropriate  use  or 
installation  of  materials,  appliances,  equipment  or 
methods  of  design  or  construction  not  specifically 


prescribed  by  780  CMR,  provided  that  any  such 
alternative  has  been  approved.  Alternative 
materials,  appliances,  equipment  or  methods  of 
design  or  construction  shall  be  approved  when  the 
building  official  is  provided  acceptable  proof  and 
has  determined  that  said  alternative  is  satisfactory 
and  complies  with  the  intent  of  the  provisions  of 
780  CMR,  and  that  said  alternative  is,  for  the 
purpose  intended,  at  least  the  equivalent  of  that 
prescribed  in  780  CMR  in  quality,  strength, 
effectiveness,  fire  resistance,  durability  and 
safety.  Compliance  with  specific  performance 
based  provisions  of  780  CMR,  in  lieu  of  a 
prescriptive  requirement  shall  also  be  permitted  as 
an  alternate. 

109.3.2  Evidence  submitted:  The  building 
official  may  require  that  evidence  or  proof  be 
submitted  to  substantiate  any  claims  that  may  be 
made  regarding  the  proposed  alternate. 

109.3.3  Tests:  Determination  of  acceptance  shall 
be  based  on  design  or  test  methods  or  other  such 
standards  approved  by  the  BBRS.  In  the 
alternative,  where  the  BBRS  has  not  provided 
specific  approvals,  the  building  official  may 
accept,  as  supporting  data  to  assist  in  this 
determination,  duly  authenticated  engineering 
reports,  formal  reports  from  nationally 
acknowledged  testing/  listing  laboratories,  reports 
from  other  accredited  sources.  The  costs  of  all 
tests,  reports  and  investigations  required  under 
these  provisions  shall  be  borne  by  the  applicant. 

109.3.4  Approval  by  the  Construction 
Materials  Safety  Board:  The  building  official 
may  refer  such  matters  to  the  Construction 
Materials  Safety  Board  in  accordance  with 
780  CMR  123.0  for  approval. 

780  CMR  110.0  APPLICATION  FOR  PERMIT 

110.1  Permit  application:  It  shall  be  unlawful  to 
construct,  reconstruct,  alter,  repair,  remove  or 
demolish  a  building  or  structure;  or  to  change  the 
use  or  occupancy  of  a  building  or  structure;  or  to 
install  or  alter  any  equipment  for  which  provision  is 
made  or  the  installation  of  which  is  regulated  by 
780  CMR  without  fir„t  filing  a  written  application 
with  the  building  official  and  obtaining  the  required 
permit  therefor. 

110.2  Temporary  Structures: 

110.2.1  General:  A  building  permit  shall  be 
required  for  temporary  structures,  unless 
exempted  by  780  CMR  1 10.3.  Such  permits  shall 
be  limited  as  to  time  of  service,  but  such 
temporary  construction  shall  not  be  permitted  for 
more  than  one  year. 

110.2.2  Special  approval:  All  temporary 
construction  shall  conform  to  the  structural 
strength,    fire    safety,    means   of  egress,    light. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


19 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


ventilation,  energy  conservation  and  sanitary 
requirements  of  780  CMR  as  necessary  to  insure 
the  public  health,  safety  and  general  welfare. 

110.2.3  Termination  of  approval:  The  building 
official  may  terminate  such  special  approval  and 
order  the  demolition  of  any  such  construction  at 
the  discretion  of  the  building  official. 

110.3  Exemptions:  A  building  permit  is  not 
required  for  the  following  activities,  such  exemption, 
however,  shall  not  exempt  the  activity  from  any 
review  or  permit  which  may  be  required  pursuant  to 
other  laws,  by-laws,  rules  and  regulations  of  other 
jurisdictions  (e.g.  zoning,  conservation,  etc.). 

1 .  One  story  detached  accessory  buildings  used 
as  tool  or  storage  sheds,  playhouses  and  similar 
uses,  provided  the  floor  area  does  not  exceed  120 
square  feet. 

2.  Fences  six  feet  in  height  or  less. 

3.  Retaining  walls  which,  in  the  opinion  of  the 
building  official,  are  not  a  threat  to  the  public 
safety  health  or  welfare  and  which  retain  less  than 
four  feet  of  unbalanced  fill. 

4.  Ordinary  repairs  as  defined  in  780  CMR  2. 
Ordinary  repairs  shall  not  include  the  cutting 
away  of  any  wall,  partition  or  portion  thereof,  the 
removal  or  cutting  of  any  structural  beam,  column 
or  other  loadbearing  support,  or  the  removal  or 
change  of  any  required  means  of  egress,  or 
rearrangement  of  parts  of  a  structure  affecting  the 
egress  requirements;  nor  shall  ordinary  repairs 
include  addition  to,  alteration  of,  replacement  or 
relocation  of  any  standpipe,  water  supply, 
mechanical  system,  fire  protection  system,  energy 
conservation  system  or  other  work  affecting 
public  health  or  general  safety. 

5.  Greenhouses:  A  building  permit  or  notice  to 
the  building  official  is  not  required  for  the 
construction  of  greenhouses  covered  exclusively 
with  plastic  film  (in  accordance  with  St.  1983, 
c.  671).  (This  exemption  does  not  apply  if  the 
greenhouse  is  to  be  used  for  large  assemblies  of 
people  or  uses  other  than  normally  expected  for 
this  purpose.) 

110.4  Form  of  application:  The  application  for  a 
permit  shall  be  submitted  in  such  form  as  determined 
by  the  building  official  but  in  all  cases  shall  contain, 
as  a  minimum,  the  information  required  on  the 
appropriate  sample  uniform  building  permit 
application  forms  in  Appendix  B.  The  application 
for  a  permit  shall  be  accompanied  by  the  required 
fee  as  prescribed  in  780  CMR  114.0  and  the 
construction  documents  as  required  in  780  CMR 
1 10.7  and  1 10.8,  where  applicable. 

110.5  By  whom  application  is  maJe:  Application 
for  a  permit  shall  be  made  by  the  owner  or  lessee  of 
the  building  or  structure,  or  agent  of  either.  If 
application  is  made  other  than  by  the  owner,  the 
written  authorization  of  the  owner  shall  accompany 


the  application.  Such  written  authorization  shall  be 
signed  by  the  owner  and  shall  include  a  statement  of 
ownership  and  shall  identify  the  owner's  authorized 
agent,  or  shall  grant  permission  to  the  lessee  to  apply 
for  the  permit.  The  full  names  and  addresses  of  the 
owner,  lessee,  applicant  and  the  responsible  officers, 
if  the  owner  or  lessee  is  a  corporate  body,  shall  be 
stated  in  the  application. 

Note:  It  shall  be  the  responsibility  of  the 
registered  contractor  to  obtain  all  permits 
necessary  for  work  covered  by  the  Home 
Improvement  Contractor  Registration  Law, 
M.G.L.  c.  142A.  An  owner  who  secures  his  or 
her  own  permits  for  such  shall  be  excluded  from 
the  guaranty  fund  provisions  as  defined  in  M.G.L. 
c.  142A.  Refer  to  780  CMR  R6  and  M.G.L. 
c.  142 A  for  additional  information  regarding  the 
Home  Improvement  Contractor  Registration 
Program. 

110.6  The  securing  of  a  building  permit  by  the 
owner,  or  the  owner's  authorized  agent,  to  construct, 
reconstruct,  alter,  repair,  demolish,  remove,  install 
equipment  or  change  the  use  or  occupancy  of  a 
building  or  structure,  shall  not  be  construed  to 
relieve  or  otherwise  limit  the  duties  and 
responsibilities  of  the  licensed,  registered  or  certified 
individual  or  firm  under  the  rules  and  regulations 
governing  the  issuance  of  such  license  registration  or 
certification. 

110.7  Construction  documents:  The  application  for 
permit  shall  be  accompanied  by  not  less  than  three 
sets  of  construction  documents.  The  building 
official  is  permitted  to  waive,  or  modify  the 
requirements  for  filing  construction  documents  when 
the  building  official  determines  that  the  scope  of  the 
work  is  of  a  minor  nature.  When  the  quality  of  the 
materials  is  essential  for  conformity  to  780  CMR, 
specific  information  shall  be  given  to  establish  such 
quality,  and  780  CMR  shall  not  be  cited,  or  the  term 
"legal"  or  its  equivalent  used  as  a  substitute  for 
specific  information. 

110.8  Engineering  Details,  Reports,  Calculations, 
Plans  and  Specifications:  In  the  application  for  a 
permit  for  buildings  and  structures  subject  to 
construction  control  in  780  CMR  116.0,  the 
construction  documents  shall  contain  sufficient  plans 
and  details  to  fully  describe  the  work  intended, 
including,  but  not  limited  to  all  details  sufficient  to 
describe  the  structural,  fire  protection,  fire  alarm, 
mechanical,  light  and  ventilation,  energy 
conservation,  architectural  access  and  egress 
systems.  The  building  official  may  require  such 
calculations,  descriptions  narratives  and  reports 
deemed  necessary  to  fully  describe  the  basis  of 
design  for  each  system  regulated  by  780  CMR.  In 
accordance  with  the  provisions  of  M.G.L.  c.  143, 
§  54A  all  plans  and  specifications  shall  bear  the 
original     seal     and      original     signature     of     a 


20 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


Massachusetts  registered  professional  engineer  or 
registered  architect  responsible  for  the  design, 
except  as  provided  in  M.GL.  c.  143,  §  54A  and  any 
profession  or  trade  as  provided  in  M.GL.  c.  112, 
§  60L  and  M.GL.  c.  112,  §  81R. 

When  such  application  for  permit  must  comply 
with  the  provisions  of  780  CMR  4  or  780  CMR  9  or 
780  CMR  34,  the  building  official  shall  cause  one 
set  of  construction  documents  filed  pursuant  to 
780  CMR  1 10.7  to  be  transmitted  simultaneously  to 
the  head  of  the  local  fire  department  for  his  file, 
review  and  approval  of  the  items  specified  in 
780  CMR  903.0  as  they  relate  to  the  applicable 
sections  of  780  CMR  4,  780  CMR  9  or  780  CMR 
34.  The  head  of  the  local  fire  department  shall 
within  ten  working  days  from  the  date  of  receipt  by 
him,  approve  or  disapprove  such  construction 
documents.  If  the  head  of  the  local  fire  department 
disapproves  such  construction  documents,  he  or  she 
shall  do  so,  in  writing  citing  the  relevant  sections  of 
noncompliance  with  7S0  CMR  or  the  sections  of  the 
referenced  standards  of  Appendix  A.  Upon  the 
request  of  the  head  of  the  local  fire  department,  the 
building  official  may  grant  one  or  more  extensions 
of  time  for  such  review  provided,  however,  that  the 
total  review  by  said  head  of  the  local  fire  department 
shall  not  exceed  30  Calendar  days.  If  such  approval, 
disapproval  or  request  for  extension  of  time  is  not 
received  by  the  building  official  within  said  ten 
working  days,  the  building  official  may  deem  the 
construction  documents  to  be  in  full  compliance 
with  the  applicable  sections  of  780  CMR  4, 
780  CMR  9  or  780  CMR  34  and,  therefore  approved 
by  the  head  of  the  local  fire  department. 

110.9  Existing  Buildings:  The  application  for  a 
building  permit  to  reconstruct,  alter  or  change  the 
use  or  occupancy  of  existing  buildings  or  structures 
which  are  subject  to  construction  control  pursuant  to 
780  CMR  1 16.0,  shall  be  accompanied  by  a  building 
survey  where  required  by  780  CMR  34  and 
Appendix  F. 

110.10  Site  plan:  A  site  plan  shall  be  filed  showing, 
to  scale,  the  size  and  location  of  all  new  construction 
and  all  existing  structures  on  the  site,  distances  from 
lot  lines,  the  established  street  grades  and  the 
proposed  finished  grades;  and  it  shall  be  drawn  in 
accordance  with  an  accurate  boundary  line  survey. 
In  the  case  of  demolition,  the  site  plan  shall  show  all 
construction  to  be  demolished  and  the  location  and 
size  of  all  existing  structures  and  construction  that 
are  to  remain  on  the  site  or  plot. 

110.11  Independent  Structural  Engineering 
Review: 

110.11.1  As  a  condition  for  the  issuance  of  a 
building  permit,  the  structural  design  of  the 
following  described  structures  shall  be  reviewed 
by  an  independent  structural  engineer  to  verify 
that    the    design    of  the    primary    structure    is 


conceptually  correct  and  that  there  are  no  major 
errors  in  the  design: 

1 .  Buildings  which  are  five  stories  or  more  in 
height  above  the  lowest  floor,  including  stories 
below  grade. 

2.  Buildings  which  enclose  a  total  volume  of 
400,000  cubic  feet,  including  stories  below 
grade.  The  volume  shall  be  measured  using  the 
outside  dimensions  of  the  building. 

3 .  Structures  in  Use  Group  A,  or  structures 
which  are  partially  in  Use  Group  A,  which  will 
be  used  for  public  assembly  of  300  or  more 
persons. 

4.  Structures  of  unusual  complexity  or  design 
shall  be  determined  by  the  BBRS.  A  building 
official  may  apply  to  the  BBRS  for  such  a 
determination  on  a  specific  structure. 

ExemptionTemporary  structures  erected  for  a 
period  of  one  year  or  less. 

110.11.2  Requirements  for  the  review:    The 

independent  structural  engineering  review  shall  be 
in  accordance  with  the  requirements  of 
Appendix  I. 

110.11.3  Disputes  between  the  structural 
engineer  responsible  for  the  design  of  the  building 
or  structure  and  the  structural  engineering  peer 
shall  be  resolved  by  the  structural  peer  review 
advisory  committee  in  accordance  with  780  CMR 
125.0. 

110.12  Structures  subject  to  control:  In  those 
structures  subject  to  control  as  required  in  780  CMR 
1 16.0,  affidavits  must  be  submitted  with  the  permit 
application  that  the  individuals  and  testing 
laboratories  responsible  for  carrying  out  the  duties 
specified  in  780  CMR  1 16.0  have  been  licensed  by 
the  BBRS. 

110.13  Amendments  to  application:  Subject  to  the 
limitations  of  780  CMR  110.14,  amendments  to  a 
plan,  application  or  other  records  accompanying  the 
same  shall  be  filed  prior  to  the  commencement  of  the 
work  for  which  the  amendment  to  the  permit  is 
sought  or  issued.  Such  amendments  shall  be  deemed 
part  of  the  original  application  and  shall  be 
submitted  in  accordance  with  780  CMR  1 10.0. 

110.14  Time    limitation     of    application:     An 

application  for  a  permit  for  any  proposed  work  shall 
be  deemed  to  have  been  abandoned  six  months  after 
the  date  of  filing,  unless  such  application  has  been 
diligently  prosecuted  or  a  permit  shall  have  been 
issued;  except  that  the  building  official  shall  grant 
one  or  more  extensions  of  time  for  additional  periods 
not  exceeding  90  days  each  if  there  is  reasonable 
cause  and  upon  written  request  by  the  owner. 

780  CMR  111.0  PERMITS 

111.1  Action  on  application:  The  building  official 

shall    examine    or    cause    to    be    examined    all 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


21 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


applications  for  permits  and  amendments  thereto 
within  30  days  after  filing  thereof.  If  the  application 
or  the  construction  documents  do  not  conform  to  the 
requirements  of  780  CMR  and  all  pertinent  laws 
under  the  building  official's  jurisdiction,  the 
building  official  shall  reject  such  application  in 
writing,  stating  the  reasons  therefor.  If  the  building 
official  is  satisfied  that  the  proposed  work  conforms 
to  the  requirements  of  780  CMR  and  all  laws  and 
ordinances  applicable  thereto,  the  building  official 
shall  issue  a  permit  therefor. 

111.2  Zoning:  In  accordance  with  the  provisions  of 
M.G.L.  c.  40A  or  St.  1956,  c.  665  as  amended,  no 
permit  for  the  construction,  alteration,  change  of  use 
or  moving  of  any  building  or  structure  shall  be 
issued  if  such  building  or  structure  or  use  would  be 
in  violation  of  any  zoning  ordinance  or  by-law. 

111.3  Railroad  right-of-way:  No  permit  to  build  a 
structure  of  any  kind  on  land  formerly  used  as  a 
railroad  right-of-way  or  any  property  appurtenant 
thereto  formerly  used  by  any  railroad  company  in 
the  state  shall  be  issued  without  first  obtaining,  after 
public  hearing,  the  consent  in  writing  to  the  issuance 
of  such  permit  from  the  Secretary  of  the  Executive 
Office  of  Transportation  and  Construction,  all  in 
accordance  with  M.G.L.  c.  40,  §  54A. 

111.4  Water  Supply:  No  permit  shall  be  issued  for 
the  construction  of  a  building  or  structure  which 
would  necessitate  the  use  of  water  therein,  unless  a 
supply  of  water  is  available  therefor,  either  from  a 
water  system  operated  by  a  city,  town  or  district,  or 
from  a  well  located  on  the  land  where  the  building  or 
structure  is  to  be  constructed,  or  from  a  water 
corporation  or  company,  as  required  by  M.G.L. 
c.  40,  §  54. 

111.5  Debris:  As  a  condition  of  issuing  a  permit  for 
the  demolition,  renovation,  rehabilitation  or  other 
alteration  of  a  building  or  structure,  M.G.L.  c.  40, 
§  54  requires  that  the  debris  resulting  therefrom  shall 
be  disposed  of  in  a  properly  licensed  solid  waste 
disposal  facility  as  defined  by  M.G.L.  c.  Ill, 
§  150A.  Signature  of  the  permit  applicant,  date  and 
number  of  the  building  permit  to  be  issued  shall  be 
indicated  on  a  form  provided  by  the  building 
department,  and  attached  to  the  office  copy  of  the 
building  permit  retained  by  the  building  department. 
If  the  debris  will  not  be  disposed  of  as  indicated,  the 
holder  of  the  permit  shall  notify  the  building  official, 
in  writing,  as  to  the  location  where  the  debris  will  be 
disposed. 

111.6  Workers'  Compensation:  No  permit  shall  be 
issued  to  construct,  reconstruct,  alter  or  demolish  a 
building  or  structure  until  acceptable  proof  of 
insurance  pursuant  to  M.G.L.  c.  152,  §  25C(6)  has 
been  provided  to  the  building  official. 


111.7  Expiration  of  permit:  Any  permit  issued 
shall  be  deemed  abandoned  and  invalid  unless  the 
work  authorized  by  it  shall  have  been  commenced 
within  six  months  after  its  issuance;  however,  for 
cause,  and  upon  written  request  of  the  owner,  one  or 
more  extensions  of  time,  for  periods  not  exceeding 
six  months  each,  may  be  granted  in  writing  by  the 
building  commissioner  or  inspector  of  buildings. 
Work  under  such  a  permit  in  the  opinion  of  the 
building  commissioner  or  inspector  of  buildings, 
must  proceed  in  good  faith  continuously  to 
completion  so  far  as  is  reasonably  practicable  under 
the  circumstances.  It  is  the  sole  responsibility  of  the 
owner  to  inform,  in  writing,  the  building 
commissioner  or  inspector  of  buildings  of  any  facts 
which  support  an  extension  of  time.  The  building 
commissioner  or  inspector  of  buildings  has  no 
obligation  under  780  CMR  111.7  to  seek  out 
information  which  may  support  an  extension  of  time. 
The  owner  may  not  satisfy  this  requirement  by 
informing  any  other  municipal  and/or  state  official 
or  department. 

For  purposes  of  780  CMR  111.7  any  permit 
issued  shall  not  be  considered  invalid  if  such 
abandonment  or  suspension  of  work  is  due  to  a  court 
order  prohibiting  such  work  as  authorized  by  such 
permit;  provided,  however,  in  the  opinion  of  the 
building  commissioner  or  inspector  of  buildings,  the 
person  so  prohibited  by  such  court  order,  adequately 
defends  such  action  before  the  court. 

111.8  Previous  approvals:  780  CMR  shall  not 
require  changes  in  the  construction  documents, 
construction  or  designated  use  group  of  a  building 
for  which  a  lawful  permit  has  been  heretofore  issued 
or  otherwise  lawfully  authorized,  and  the 
construction  of  which  has  been  actively  prosecuted 
within  180  days  after  the  effective  date  of  780  CMR 
and  is  completed  with  dispatch. 

111.9  Signature  to  permit:  The  building  official's 
signature  shall  be  attached  to  every  permit;  or  the 
building  official  shall  authorize  a  subordinate  to 
affix  such  signature  thereto. 

111.10  Approved  construction  documents.  When 
the  building  official  has  determined  that  the 
proposed  construction  conforms  to  the  provisions  of 
780  CMR  and  other  applicable  laws,  by-laws,  rules 
and  regulations  under  his/her  jurisdiction,  the 
building  official  shall  stamp  or  endorse  in  writing 
the  three  sets  of  construction  documents 
"Approved".  One  set  of  the  approved  construction 
documents  shall  be  retained  by  the  building  official, 
one  set  by  the  head  of  the  local  fire  department  and 
the  other  set  shall  be  kept  at  the  construction  site, 
open  to  inspection  of  the  building  official  or  an 
authorized  representative  at  all  reasonable  times. 

111.12  Revocation  of  permits:  The  building  official 
shall  revoke  a  permit  or  approval  issued  under  the 


22 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/°7) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 

the    necessary       retaining  walls    and    fences    in 
'  "  the  provisions  of  780  CMR  33. 


provisions  of  780  CMR  in  case  of  any  false 
statement  or  misrepresentation  of  fact  in  the 
application  or  on  the  plans  on  which  the  permit  or 
approval  was  based. 

111.13  Approval  in  part:  The  building  official  may 
issue  a  permit  for  the  construction  of  foundations  or 
any  other  part  of  a  building  or  structure  before  the 
construction  documents  for  the  whole  building  or 
structure  have  been  submitted,  provided  that 
adequate  information  and  detailed  statements  have 
been  filed  complying  with  all  of  the  pertinent 
requirements  of  780  CMR.  Work  shall  be  limited  to 
that  work  approved  by  the  partial  approval  and 
further  work  shall  proceed  only  when  the  building 
permit  is  amended  in  accordance  with  780  CMR 
110.13.  The  holder  of  such  permit  for  the 
foundation  or  other  parts  of  a  building  or  structure 
shall  proceed  at  the  holder's  own  risk  with  the 
building  operation  and  without  assurance  that  a 
permit  for  the  entire  building  or  structure  will  be 
granted. 

111.14  Posting  of  permit:  A  true  copy  of  the 
building  permit  shall  be  kept  on  the  site  of 
operations,  open  to  public  inspection  during  the 
entire  time  of  prosecution  of  the  work  and  until  the 
completion  of  the  same. 

111.15  Notice  of  start:  At  least  24-hour  notice  of 
start  of  work  under  a  building  permit  shall  be  given 
to  the  building  official. 

780  CMR  112.0  DEMOLITION  OF 
STRUCTURES 

112.1  Service  connections:  Before  a  building  or 
structure  is  demolished  pr  removed,  the  owner  or 
agent  shall  notify  all  utilities  having  service 
connections  within  the  structure  such  as  water, 
electric,  gas,  sewer  and  other  connections.  A  permit 
to  demolish  or  remove  a  building  or  structure  shall 
not  be  issued  until  a  release  is  obtained  from  the 
utilities,  stating  that  their  respective  service 
connections  and  appurtenant  equipment,  such  as 
meters  and  regulators,  have  been  removed  or  sealed 
and  plugged  in  a  safe  manner. 

All  debris  shall  be  disposed  of  in  accordance  with 
780  CMR  11 1.5. 

112.2  Notice  to  adjoining  owners:  Only  when 
written  notice  has  been  given  by  the  applicant  to  the 
owners  of  adjoining  lots  and  to  the  owners  of  wired 
or  other  facilities,  of  which  the  temporary  removal  is 
necessitated  by  the  proposed  work,  shall  a  permit  be 
granted  for  the  removal  of  a  building  or  structure. 

112.3  Lot  regulation:  Whenever  a  building  or 
structure  is  demolished  or  removed,  the  premises 
shall  be  maintained  free  from  all  unsafe  or  hazardous 
conditions  by  the  proper  regulation  of  the  lot, 
restoration  of  established  grades  and  the  erection  of 


the    necessary       retaining  walls    and    fent 
accordance  with  the  provisions  of  780  CMR  '. 

780  CMR  113.0  CONDITIONS  OF  PERMIT 

113.1  Payment  of  fees:  A  permit  shall  not  be  issued 
until  the  fees  prescribed  in  780  CMR  114.0  have 
been  paid. 

113.2  Compliance  with  code:  The  permit  shall  be  a 
license  to  proceed  with  the  work  and  shall  not  be 
construed  as  authority  to  violate,  cancel  or  set  aside 
any  of  the  provisions  of  780  CMR  or  any  other  law 
or  regulation,  except  as  specifically  stipulated  by 
modification  or  legally  granted  variation  as 
described  in  the  application. 

113.3  Compliance  with  permit:  All  work  shall 
conform  to  the  approved  application  and  the 
approved  construction  documents  for  which  the 
permit  has  been  issued  and  any  approved 
amendments  to  the  approved  application  or  the 
approved  construction  documents. 

113.4  Compliance  with  site  plan:  All  new  work 
shall  be  located  strictly  in  accordance  with  the 
approved  site  plan. 

780  CMR  114.0  FEES 

114.1  General:  A  permit  to  begin  work  for  new 
construction,  alteration,  removal,  demolition  or  other 
building  operation  shall  not  be  issued  until  the  fees 
prescribed  in  780  CMR  1 14.0  shall  have  been  paid 
to  the  department  of  building  inspection  or  other 
authorized  agency  of  the  jurisdiction,  nor  shall  an 
amendment  to  a  permit  necessitating  an  additional 
fee  be  approved  until  the  additional  fee  has  been 
paid. 

114.2  Special  fees:  The  payment  of  the  fee  for  the 
construction,  alteration,  removal  or  demolition  for 
all  work  done  in  connection  with  or  concurrently 
with  the  work  contemplated  by  a  building  permit 
shall  not  relieve  the  applicant  or  holder  of  the  permit 
from  the  payment  of  other  fees  that  are  prescribed  by 
law  or  ordinance  for  water  taps,  sewer  connections, 
electrical  permits,  erection  of  signs  and  display 
structures,  marquees  or  other  appurtenant 
structures,  or  fees  of  inspections,  certificates  of 
occupancy  or  other  privileges  or  requirements,  both 
within  and  without  the  jurisdiction  of  the  department 
of  building  inspection. 

114.3  New  construction  and  alterations:  The  fees 
for  plan  examination,  building  permit  and 
inspections  shall  be  as  prescribed  in  780  CMR 
114.3.1  and  the  building  official  is  authorized  to 
establish  by  approved  rules  a  schedule  of  unit  rates 
for  buildings  and  structures  of  all  use  groups  and 
types  of  construction  as  classified  and  defined  in 
780  CMR  1,  3  and  6. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


23 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


114.3.1  Fee  schedule:  A  fee  for  each  plan 
examination,  building  permit  and  inspection  shall 
be  paid  in  accordance  with  the  fee  schedule  as 
established  by  the  municipality. 

114.4  Accounting:  The  building  official  shall  keep 
an  accurate  account  of  all  fees  collected;  and  such 
collected  fees  shall  be  deposited  in  the  jurisdiction 
treasury  in  accordance  with  procedures  established 
by  the  municipality,  or  otherwise  disposed  of  as 
required  by  law. 

780  CMR  115.0  INSPECTION 

115.1  Preliminary  inspection:  Before  issuing  a 
permit,  the  building  official  shall,  if  deemed 
necessary,  examine  or  cause  to  be  examined  all 
buildings,  structures  and  sites  for  which  an 
application  has  been  filed  for  a  permit  to  construct, 
enlarge,  alter,  repair,  remove,  demolish  or  change 
the  use  or  occupancy  thereof. 

115.2  Required  inspections:  After  issuing  a 
building  permit,  the  building  official  shall  conduct 
inspections  during  construction  at  intervals  sufficient 
to  ensure  compliance  with  the  provisions  of 
780  CMR.  The  building  official  shall  inform  the 
applicant  of  the  required  points  of  inspection  at  the 
time  of  application.  Upon  completion  of  the  work 
for  which  a  permit  has  been  issued,  the  building 
official  shall  conduct  a  final  inspection  pursuant  to 
780  CMR  115.5.  A  record  of  all  such  examinations 
and  inspections  and  of  all  violations  of  780  CMR 
shall  be  maintained  by  the  building  official.  For 
buildings  and  structures  subject  to  construction 
control,  the  owner  shall  provide  for  special 
inspections  in  accordance  with  780  CMR  1705.0. 

In  conjunction  with  specific  construction  projects, 
the  building  official  may  designate  specific 
inspection  points  in  the  course  of  construction  that 
require  the  contractor  or  builder  to  give  the  building 
official  24  hours  notice  prior  to  the  time  when  those 
inspections  need  to  be  performed.  The  building 
official  shall  make  the  inspections  within  48  hours 
after  notification. 

115.3  Approved  inspection  agencies:  The  building 
official  may  accept  reports  of  approved  inspection 
agencies  provided  such  agencies  satisfy  the 
requirements  as  to  qualifications  and  reliability. 

115.4  Plant  inspection:  Where  required  by  the 
provisions  of  780  CMR  or  by  the  approved  rules, 
materials  or  assemblies  shall  be  inspected  at  the 
point  of  manufacture  or  fabrication  in  accordance 
with  780  CMR  1703.3. 

115.5  Final  inspection:  Upon  completion  of  the 
building  or  structure,  and  before  issuance  of  the 
certificate  of  occupancy  required  by,  780  CMR 
120.0,    a    final    inspection    shall    be    made.       All 


variations  of  the  approved  construction  documents 
and  permit  shall  be  noted  and  the  holder  of  the 
permit  shall  be  notified  of  the  discrepancies. 

115.6  General:  In  the  discharge  of  his  duties,  the 
building  official  shall  have  the  authority  to  enter  at 
any  reasonable  hour  any  building,  structure  or 
premises  in  the  municipality  to  enforce  the 
provisions  of  780  CMR. 

If  any  owner,  occupant,  or  other  person  refuses, 
impedes,  inhibits,  interferes  with,  restricts,  or 
obstructs  entry  and  free  access  to  every  part  of  the 
structure,  operation  or  premises  where  inspection 
authorized  by  780  CMR  is  sought,  the  building 
official,  or  state  inspector  may  seek,  in  a  court  of 
competent  jurisdiction,  a  search  warrant  so  as  to 
apprise  the  owner,  occupant  or  other  person 
concerning  the  nature  of  the  inspection  and 
justification  for  it  and  may  seek  the  assistance  of 
police  authorities  in  presenting  said  warrant. 

115.7  Identification:  The  building  official  shall 
carry  proper  identification  when  inspecting 
structures  or  premises  in  the  performance  of  duties 
under  780  CMR. 

115.8  Jurisdictional  cooperation:  The  assistance 
and  cooperation  of  police,  fire,  and  health 
departments  and  all  other  officials  shall  be  available 
to  the  building  official  as  required  in  the 
performance  of  his  duties. 

115.9  Coordination  of  inspections:  Whenever  in 
the  enforcement  of  780  CMR  or  another  code  or 
ordinance,  the  responsibility  of  more  than  one 
building  official  of  the  jurisdiction  is  involved,  it 
shall  be  the  duty  of  the  building  officials  involved  to 
coordinate  their  inspections  and  administrative 
orders  as  fully  as  practicable  so  that  the  owners  and 
occupants  of  the  building  or  structure  sha'l  not  be 
subjected  to  visits  by  numerous  inspectors  or 
multiple  or  conflicting  orders.  Whenever  an  ■ 
inspector  from  any  agency  or  department  observes 
an  apparent  or  actual  violation  of  some  provision  of 
some  law,  ordinance  or  code  not  within  the 
inspector's  authority  to  enforce,  the  inspector  shall 
report  the  findings  to  the  building  official  having 
jurisdiction. 

780  CMR  116.0  REGISTERED 

ARCHITECTURAL  AND 

PROFESSIONAL  ENGINEERING 

SERVICES  -  CONSTRUCTION  CONTROL 

116.1  General:  The  provisions  of  780  CMR  1 16.0 
define  the  construction  controls  required  for  all 
buildings  and  structures  needing  registered 
architectural  or  registered  professional  engineering 
services,  and  delineate  the  responsibilities  of  such 
professional  services  together  with  those  services 
that  are  the  responsibility  of  the  contractor  during 
construction. 


24 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

.ADMINISTRATION 


i  he  following  structures  are  exempt  from  the 
requirements  of  7S0  CMR  1 16.0; 

1.  Any  building  containing  less  than  35,000 
cubic  feet  of  enclosed  space,  measured  to  the 
exterior  surfaces  of  walls  and  roofs  and  to  the  tcp 
of  a  ground  supported  floor,  or  in  the  case  of  a 
crawl  space,  to  the  bottom  surface  of  the  crawl 
space.  In  the  case  of  basement  floors  or  levels, 
the  calculation  of  enclosed  space  shall  include 
such  spaces. 

2.  Any  single  or  two  family  dwelling  or  any 
accessory  building  thereto; 

3.  Any  building  used  exclusively  for  farm 
purposes  (this  exemption  does  not  apply  if  the 
building  is  to  be  used  for  large  assemblies  of 
people  or  uses  other  than  farm  purposes);  and 

4.  Retaining  walls  less  than  ten  feet  in  height  at 
all  points  along  the  wall  as  measured  from  the 
base  of  the  footing  to  the  top  of  the  wall. 

Notwithstanding  the  exemptions  above,  professional 
engineering  services  shall  be  required  for  activities 
which  are  deemed  to  constitute  the  practice  of 
engineering  as  defined  in  M.GL.  c.  112,  §  SID, 
except  as  provided  in  M.GL.  c.  54A  and  any  legally 
required  profession  or  as  provided  in  M.GL.  c.  1 12, 
§S1R. 

116.2  Registered  architectural  and  engineering 
services: 

116.2.1  Design:  All  plans,  computations  and 
specifications  involving  new  construction, 
alterations,  repairs,  expansions  or  additions  or 
change  in  use  or  occupancy  of  existing  buildings 
shall  be  prepared  by  or  under  the  direct 
supervision  of  a  Massachusetts  registered 
architect  or  Massachusetts  registered  professional 
engineer  and  shall  bear  his  or  her  original 
signature  and  seal  or  by  the  legally  recognized 
professional  performing  the  work,  as  defined  by 
M.G.L.  c.  112,  §81R.  Said  signature  and  seal 
shall  signify  that  the  plans,  computations  and 
specifications  meet  the  applicable  provisions  of 
780  CMR  and  all  accepted  engineering  practices. 

116.2.2  Architect/engineer  responsibilities 
during  construction:  The  registered  architects 
and  registered  professional  engineers  who  have 
prepared  plans,  computations  and  specifications 
or  the  registered  architects  or  registered 
professional  engineers  who  have  been  retained  to 
perform  construction  phase  services,  shall 
perform  the  following  tasks  for  the  portion  of  the 
work  for  which  they  are  directly  responsible; 

1.  Review,  for  conformance  to  the  design 
concept,  shop  drawings,  samples  and  other 
submittals  which  are  submitted  by  the 
contractor  in  accordance  with  the  requirements 
of  the  construction  documents. 


2.  Review  and  approval  of  the  quality  control 
procedures  for  all  code-required  controlled 
materials. 

3.  Be  present  at  intervals  appropriate  to  the 
stage  of  construction  to  become,  generally 
familiar  with  the  progress  and  quality  of  the 
work  and  to  determine,  in  general,  if  the  work 
is  being  performed  in  a  manner  consistent  with 
the  construction  documents. 

116.2.3  Structural  Tests  and  Inspections: 

Structural  tests  and  inspection  shall  be  provided  in 
accordance  with  780  CMR  1705.0. 

116.2.4  Tests  and  Inspections  of  non  structural 

systems:  Tests  a. id  inspections  of  non  structural 
systems  shall  be  performed  in  accordance  with 
applicable  engineering  practice  standards  or 
referenced  standards  listed  in  Appendix  A. 

116.3  Construction  contractor  services      The 

actual  construction  of  the  work  shall  be  the 
responsibility  of  the  general  contractor  as  identified 
on  the  approved  building  permit  and  shall  involve 
the  following: 

1.  Execution  of  all  work  in  accordance  with  the 
approved  construction  documents. 

2.  Execution  and  control  of  all  methods  of 
construction  in  a  safe  and  satisfactory  manner  in 
accordance  with  all  applicable  local,  state,  and 
federal  statutes  and  regulations. 

3.  Upon  completion  of  the  construction,  he  shall 
certify  to  the  best  of  his  knowledge  and  belief  that 
such  has  been  done  in  substantial  accord  with 
780  CMR  116.3  items  1  and  2  and  with  all 
pertinent  deviations  specifically  noted. 

116.4  On  site  project  representation:  When 
applications  for  unusual  designs  or  magnitude  of 
construction  are  filed,  or  where  reference  standards 
require  special  architectural  or  engineering 
inspections,  the  building  official  may  require  full- 
time  project  representation  by  a  registered  architect 
or  professional  engineer  in  addition  to  that  provided 
in  780  CMR  116.2.2.  The  project  representative 
shall  keep  daily  records  and  submit  reports  as  may 
be  required  by  the  building  official.  Upon 
completion  of  the  work,  the  registered  architect  or 
professional  engineer  shall  file  a  final  report 
indicating  that  the  work  has  been  performed  in 
accordance  with  the  approved  plans  and  780  CMR. 

116.4.1  Building  permit  requirement:  This  on- 
site  project  representation  requirement  shall  be 
determined  prior  to  the  issuance  of  the  building 
permit  and  shall  be  a  requisite  for  the  permit 
issuance.  Refusal  by  the  applicant  to  provide 
such  service  as  required  by  the  building  official 
shall  result  in  the  denial  of  the  permit.  However, 
the  applicant  may  file  an  appeal  as  provided  in 
780  CMR  122.0. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


116.4.2  Fee  and  costs:  All  fees  and  costs  related 
to  the  performance  of  on-site  project 
representation  shall  be  borne  by  the  owner. 

116.5  Building  official  responsibility:  Nothing 
contained  in  780  CMR  1 16.0  shall  have  the  effect  of 
waiving  or  limiting  the  building  official's  authority 
to  enforce  780  CMR  with  respect  to  examination  of 
the  contract  documents,  including  plans, 
computations  and  specifications,  and  field 
inspections  (see  780  CMR  106.0). 

780  CMR  117.0  WORKMANSHIP 
117.1    General:    All   work   shall    be   conducted, 
installed   and   completed    in   a  workmanlike   and 
acceptable   manner  so   as  to   secure  the   results 
intended  by  780  CMR. 

780  CMR  118.0  VIOLATIONS 

118.1  Unlawful  acts:  It  shall  be  unlawful  for  any 
person,  firm  or  corporation  to  use,  occupy  or  change 
the  use  or  occupancy  of  any  building  or  structure  or 
to  erect,  construct,  alter,  extend,  repair,  remove, 
demolish  any  building  or  structure  or  any  equipment 
regulated  by  780  CMR  or  cause  same  to  be  done,  in 
conflict  with  or  in  violation  of  any  of  the  provisions 
of  780  CMR. 

118.2  Notice  of  violation:  The  building  official  shall 
serve  a  notice  of  violation  or  order  on  the  person 
responsible  for  the  erection,  construction,  alteration, 
extension,  repair,  removal,  demolition  or  occupancy 
of  a  building  or  structure  in  violation  of  the 
provisions  of  780  CMR  or  in  violation  of  a  detail 
statement  or  a  plan  approved  thereunder,  or  in 
violation  of  a  permit  or  certificate  issued  under  the 
provisions  of  780  CMR.  Such  order  shall  be  in 
writing  and  shall  direct  the  discontinuance  of  the 
illegal  action  or  condition  and  the  abatement  of  the 
violation. 

118.3  Prosecution  of  violation:  If  the  notice  of 
violation  is  not  complied  with  in  the  time  period 
specified  in  said  notice  of  violation,  the  building 
official  may  institute  the  appropriate  proceedings  at 
law  or  in  equity  to  restrain,  correct  or  abate  such 
violation  or  to  require  the  removal  or  termination  of 
the  unlawful  occupancy  of  the  building  or  structure 
in  violation  of  the  provisions  of  780  CMR  or  of  the 
order  or  direction  made  pursuant  thereto. 

118.4  Violation  penalties:  Whoever  violates  any 
provision  of  780  CMR,  except  any  specialized  code 
referenced  herein,  shall  be  punishable  by  a  fine  of 
not  more  than  $1,000  or  by  imprisonment  for  not 
more  than  one  year,  or  both  for  each  such  violation. 
Each  day  during  which  a  violation  exists  shall 
constitute  a  separate  offense.  The  building  official 
shall    not    begin    criminal    prosecution    for    such 


violations  until  the  lapse  of  30  days  after  the 
issuance  of  the  written  notice  of  violation. 

118.5  Abatement  of  violation:  The  imposition  of 
the  penalties  herein  prescribed  shall  not  preclude  the 
legal  officer  of  the  jurisdiction  from  instituting 
appropriate  action  to  prevent  unlawful  construction 
or  to  restrain,  correct  or  abate  a  violation,  or  to 
prevent  illegal  occupancy  of  a  building,  structure  or 
premises  or  to  stop  an  illegal  act,  conduct,  business 
or  occupancy  of  a  building  or  structure  on  or  about 
any  premises. 

118.6  Notice  or  orders,  service  and  content: 

Every  notice  or  order  authorized  by  780  CMR  shall 
be  in  writing  and  shall  be  served  on  the  person 
responsible: 

1 .  personally,  by  any  person  authorized  by  the 
building  official;  or 

2.  by  any  person  authorized  to  serve  civil 
process  by  leaving  a  copy  of  the  order  or  notice  at 
the  responsible  party's  last  and  usual  place  of 
abode;  or 

3.  by  sending  the  party  responsibile  a  copy  of  the 
order  by  registered  or  certified  mail  return  receipt 
requested,  if  he  is  within  the  Commonwealth;  or 

4.  if  the  responsibile  party's  last  and  usual  place 
of  abode  is  unknown,  by  posting  a  copy  of  this 
order  or  notice  in  a  conspicuous  place  on  or  about 
the  premises  in  violation  and  by  publishing  it  for 
at  least  three  out  of  five  consecutive  days  in  one 
or  more  newspapers  of  general  circulation 
wherein  the  building  or  premises  affected  is 
situated. 

780  CMR  1 19.0  STOP  WORK  ORDER 

119.1  Notice  to  owner:  Upon  notice  from  the 
building  official  that  work  on  any  building  or 
structure  is  being  prosecuted  contrary  to  the 
provisions  of  780  CMR  or  in  an  unsafe  and 
dangerous  manner  or  contrary  to  the  approved 
construction  documents  submitted  in  support  of  the 
building  permit  application,  such  work  shall  be 
immediately  stopped.  The  stop  work  order  shall  be 
in  writing  and  shall  be  given  to  the  owner  of  the 
property  involved,  or  to  the  owner's  agent,  or  to  the 
person  doing  the  work;  and  shall  state  the  conditions 
under  which  work  will  be  permitted  to  resume. 

119.2  Unlawful  continuance:  Any  person  who  shall 
continue  any  work  in  or  about  the  building  or 
structure  after  having  been  served  with  a  stop  work 
order,  except  such  work  as  that  person  is  directed  to 
perform  to  remove  a  violation  or  unsafe  condition, 
shall  be  liable  to  a  fine  of  not  more  than  $1,000  or 
by  imprisonment  for  not  more  than  one  year,  or  both 
for  each  such  violation.  Each  day  during  which  a 
violation  exists  shall  constitute  a  separate  offense. 


26 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


780  CMR  120.0  CERTIFICATE  OF 
OCCUPANCY 

120.1  General:   New  buildings  and  structures:  A 

building  or  structure  hereafter  shall  not  be  used  or 
occupied  in  whole  or  in  part  until  the  certificate  of 
use  and  occupancy  shall  have  been  issued  by  the 
building  commissioner  or  inspector  of  buildings  or, 
when  applicable,  the  state  inspector.  The  certificate 
shall  not  be  issued  until  all  the  work  has  been 
completed  in  accordance  with  the  provisions  of  the 
approved  permits  and  of  the  applicable  codes  for 
which  a  permit  is  required,  except  as  provided  in 
780  CMR  120.3. 

120.2  Buildings  or  structures  hereafter  altered: 

A  building  or  structure,  in  whole  or  in  part,  altered 
to  change  from  one  use  group  to  another;  to  a 
different  use  within  the  same  use  group;  the  fire 
grading:  the  maximum  live  load  capacity;  the 
occupancy  load  capacity  shall  not  be  occupied  or 
used  until  the  certificate  shall  have  been  issued 
certifying  that  the  work  has  been  completed  in 
accordance  with  the  provisions  of  the  approved 
permits  and  of  the  applicable  codes  for  which  a 
permit  is  required.  Any  use  or  occupancy,  which 
was  not  discontinued  during  the  work  of  alteration, 
shall  be  discontinued  within  30  days  after  the 
completion  of  the  alteration  unless  the  required 
certificate  is  issued. 

120.3  Temporary  occupancy:  Upon  the  request  of 
the  holder  of  a  permit,  a  temporary  certificate  of 
occupancy  may  be  issued  before  the  completion  of 
the  entire  work  covered  by  the  permit,  provided  that 
such  portion  or  portions  shall  be  occupied  safely 
prior  to  full  completion  of  the  building  or  structure 
without  endangering  life  or  public  welfare.  Any 
occupancy  permitted  to  continue  during  the  work 
shall  be  discontinued  within  30  days  after 
completion  of  the  work  unless  a  certificate  of 
occupancy  is  issued  by  the  building  official. 

120.4  Contents  of  certificate:  When  a  building  or 
structure  is  entitled  thereto,  the  building  official 
shall  issue  a  certificate  of  occupancy  within  ten  days 
after  written  application.  Upon  completion  of  the 
final  inspection  in  accordance  with  780  CMR  115.5 
and  correction  of  the  violations  and  discrepancies, 
and  compliance  with  780  CMR  903.4,  the  certificate 
of  occupancy  shall  be  issued.  The  certificate  of 
occupancy  shall  specify  the  following. 

1.  The  edition  of  the  code  under  which  the 
permit  was  issued. 

2.  The  use  group  and  occupancy,  in  accordance 
with  the  provisions  of  780  CMR  3. 

3         The  type  of  construction  as   defined   in 
780  CMR  6. 

4.  The  occupant  load  per  floor. 

5.  Any  special  stipulations  and  conditions  of  the 
building  permit. 


120.5  Posting  structures: 

120.5.1  Posted  use  and  occupancy:  A  suitably 
designed  placard  approved  by  the  building  official 
shall  be  posted  by  the  owner  on  all  floors  of  every 
building  and  structure  and  part  thereof  designed 
for  high  hazard,  storage,  mercantile,  factory  and 
industrial  or  business  use  (use  groups  H,  S,  M,  F 
and  B)  as  defined  in  780  CMR  3.  Said  placard 
shall  be  securely  fastened  to  the  building  or 
structure  in  a  readily  visible  place,  stating:  the 
use  group,  the  fire  grading,  the  live  load  and  the 
occupancy  load. 

120.5.2  Posted  occupancy  load:  A  suitably 
designed  placard  approved  by  the  building  official 
shall  be  posted  by  the  owner  in  every  room  where 
practicable  of  every  building  and  structure  and 
part  thereof  designed  for  use  as  a  place  of  public 
assembly  or  as  an  institutional  building  for 
harboring  people  for  penal,  correctional, 
educational,  medical  or  other  care  or  treatment,  or 
as  residential  buildings  used  for  hotels,  lodging 
houses,  boarding  houses,  dormitory  buildings, 
multiple  family  dwellings  (use  groups  A,  I,  R-l 
and  R-2).  Said  placard  shall  designate  the 
maximum  occupancy  load. 

120.5.3  Replacement  of  posted   signs:      All 

posting  signs  shall  be  furnished  by  the  owner  and 
shall  be  of  permanent  design;  they  shall  not  be 
removed  or  defaced,  and  if  lost,  removed  or 
defaced,  shall  be  immediately  replaced. 

120.5.4  Periodic  inspection  for  posting:    The 

building  official  may  periodically  inspect  all 
existing  buildings  and  structures  except  one  and 
two  family  dwellings  for  compliance  with 
780  CMR  in  respect  to  posting;  or  he  may  accept 
the  report  of  such  inspections  from  a  qualified 
registered  engineer  or  architect  or  others  certified 
by  the  BBRS;  and  such  inspections  and  reports 
shall  specify  any  violation  of  the  requirements  of 
780  CMR  in  respect  to  the  posting  of  floor  load, 
fire  grading,  occupancy  load  and  use  group  of  the 
building  or  structure. 

780  CMR  121.0  UNSAFE  STRUCTURES 

121.1  General  The  provisions  of  780  CMR  121.0 
are  established  by  M.G.L.  c.  143,  §§  6,  7,  8,  9  and 

10. 

121.2  Inspection:  The  building  official 
immediately  upon  being  informed  by  report  or 
otherwise  that  a  building  or  other  structure  or 
anything  attached  thereto  or  connected  therewith  is 
dangerous  to  life  or  limb  or  that  any  building  in  that 
city  or  town  is  unused,  uninhabited  or  abandoned, 
and  open  to  the  weather,  shall  inspect  the  same;  and 
he  shall  forthwith  in  writing  notify  the  owner  to 
remove  it  or  make  it  safe  if  it  appears  to  him  to  be 
dangerous,  or  to  make  it  secure  if  it  is  unused, 
uninhabited  or  abandoned  and  open  to  the  weather. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


27 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


If  it  appears  that  such  building  or  structure  would  be 
especially  unsafe  in  case  of  fire,  it  shall  be  deemed 
dangerous  within  the  meaning  hereof,  and  the 
building  official  may  affix  in  a  conspicuous  place 
upon  its  exterior  walls  a  notice  of  its  dangerous 
condition,  which  shall  not  be  removed  or  defaced 
without  authority  from  him. 

121.3  Removal   or  making  structure  safe:    Any 

person  so  notified  shall  be  allowed  until  12:00  noon 
of  the  day  following  the  service  of  the  notice  in 
which  to  begin  to  remove  such  building  or  structure 
or  make  it  safe,  or  to  make  it  secure,  and  he  shall 
employ  sufficient  labor  speedily  to  make  it  safe  or 
remove  it  or  to  make  it  secure;  but  if  the  public 
safety  so  requires  and  if  the  mayor  or  selectmen  so 
order,  the  building  official  may  immediately  enter 
upon  the  premises  with  the  necessary  workmen  and 
assistants  and  cause  such  unsafe  structure  to  be  made 
safe  or  demolished  without  delay  and  a  proper  fence 
put  up  for  the  protection  of  passersby,  or  to  be  made 
secure. 

121.4  Failure  to  remove  or  make  structure  safe, 
survey  board,  survey  report:  If  an  owner  of  such 
unsafe  structure  refuses  or  neglects  to  comply  with 
the  requirements  of  such  notice  within  the  specified 
time  limit,  and  such  structure  is  not  made  safe  or 
taken  down  as  ordered  therein,  a  careful  survey  of 
the  premises  shall  be  made  oy  a  board  consisting;  in 
a  city,  of  a  city  engineer,  the  head  of  the  fire 
department,  as  such  term  is  defined  in  M.G.L. 
c.  148,  §  1,  and  one  disinterested  person  to  be 
appointed  by  the  building  official;  and,  in  a  town  of 
a  surveyor,  the  head  of  the  fire  department  and  one 
disinterested  person  to  be  appointed  by  the  building 
official.  In  the  absence  of  any  of  the  above  officers 
or  individuals,  the  mayor  or  selectmen  shall 
designate  one  or  more  officers  or  other  suitable 
persons  in  place  of  the  officers  so  named  as 
members  of  said  board.  A  written  report  of  such 
survey  shall  be  made,  and  a  copy  thereof  served  on 
such  owner. 

121.5  Removal  of  dangerous  or  abandoned 
structures:  If  such  survey  report  as  outlined  in 
780  CMR  121.4  declares  such  structure  to  be 
dangerous  or  to  be  unused,  uninhabited  or 
abandoned,  and  open  to  the  weather,  and  if  the 
owner  continues  such  refusal  or  neglect,  the  building 
official  shall  cause  it  to  be  made  safe  or  taken  down 
or  to  be  made  secure;  and,  if  the  public  safety  so 
requires,  said  building  official  may  at  once  enter  the 
structure,  the  land  on  which  it  stands  or  the  abutting 
land  or  buildings,  with  such  assistance  as  he  may 
require,  and  secure  the  same;  and  may  remove  and 
evict,  under  the  pertinent  provisions  of  M.G.L. 
c.  239,  or  otherwise,  any  tenant  or  occupant  thereof; 
and  may  erect  such  protection  for  the  public  by 
proper  fence  or  otherwise  as  may  be  necessary,  and 
for  this  purpose  may  close  a  public  highway.  In  the 


case  of  such  demolition,  the  said  building  official 
shall  cause  such  lot  to  be  leveled  to  conform  with 
adjacent  grades  by  a  inorganic  fill.  The  costs  and 
charges  incurred  shall  constitute  a  lien  upon  the  land 
upon  which  the  structure  is  located,  and  shall  be 
enforced  in  an  action  of  contract;  and  such  owner 
shall,  for  every  day's  continuance  of  such  refusal  or 
neglect  after  being  so  notified,  be  punished  by  a  fine 
in  accordance  with  780  CMR  1 18.4.  The  provisions 
of  M.G.L.  c.  139,  §  3A  paragraph  two,  relative  to 
liens  for  such  debt  and  the  collection  of  claims  for 
such  debt  shall  apply  to  any  debt  referred  to  in  this 
section,  except  that  the  said  building  official  shall 
act  hereunder  in  place  of  the  mayor  or  board  of 
selectmen.  During  the  time  such  order  is  in  effect, 
it  shall  be  unlawful  to  use  or  occupy  such  structure 
or  any  portion  thereof  for  any  purpose. 

121.6  Remedy  of  person  ordered  to  remove  a 
dangerous      structure      or      make      it      safe: 

Notwithstanding  the  provisions  of  780  CMR  122,  an 
owner,  aggrieved  by  such  order  may  have  the 
remedy  prescribed  by  M.G.L.  c.  139,  §  2:  provided 
that  any  provision  of  M.G.L.  c.  139,  §  2  shall  not  be 
construed  so  as  to  hinder,  delay  or  prevent  the 
building  official  from  acting  and  proceeding  under 
780  CMR  121;  and  provided,  further,  that  this 
section  shall  not  prevent  the  city  or  town  from 
recovering  the  forfeiture  provided  in  said  780  CMR 
121.5  from  the  date  of  the  service  of  the  original 
notice,  unless  the  order  is  annulled  by  the  jury. 

780  CMR  122.0  BOARD  OF  APPEALS 
122.1      State  Building   Code  Appeals   Board: 

Except  for  actions  taken  pursuant  to  780  CMR 
121.0,  whoever  is  aggrieved  by  an  interpretation, 
order,  requirement,  direction  or  failure  to  act  under 
780  CMR  by  any  agency  or  official  of  the  city,  town 
or  region,  or  agency  or  official  of  the  State  charged 
with  the  administration  or  enforcement  of  780  CMR 
or  any  of  its  rules  or  regulations,  excepting  any 
specialized  codes,  may  appeal  directly  to  the  State 
Building  Code  Appeals  Board  as  provided  in 
780  CMR  122.0. 

Whoever  is  aggrieved  by  an  interpretation,  order, 
requirement,  direction  or  failure  to  act  under 
780  CMR  by  any  agency  or  official  of  a  city,  town 
or  region  charged  with  the  administration  or 
enforcement  of  780  CMR,  excepting  any  specialized 
codes,  may  appeal  directly  to  the  State  Building 
Code  Appeals  Board  or  may  appeal  first  to  a  local  or 
regional  building  code  appeals  board  and  if 
aggrieved  thereby  he  may  then  appeal  to  the  State 
Building  Code  Appeals  Board  as  provided  in 
780  CMR  122.0. 

In  the  event  an  appeal  is  taken  directly  to  the  State 
Building  Code  Appeals  Board  from  an 
interpretation,  order,  requirement  or  direction,  said 
appeal  shall  be  filed  as  specified  in  780  CMR 
122.3.1  with  the  State  Building  Code  Appeals  Board 
not  later  than  45  days  after  the  service  of  notice 


28 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


thereof  of  the  interpretation,  order,  requirement  or 
direction. 

In  the  event  the  appeal  is  taken  directly  to  the 
State  Building  Code  Appeals  Board  for  the  failure  to 
act,  the  appeal  shall  be  taken  not  later  than  45  days 
after  a  request  to  act  has  been  made  by  the  aggrieved 
person  in  writing  and  served  upon  the  appropriate 
building  official  or  chief  administrative  officer  of  the 
state  or  local  agency  which  fails  to  act. 

If  the  aggrieved  person  elects  to  appeal  before  the 
local  or  regional  building  code  appeals  board,  he 
shall  not  be  allowed  to  enter  such  appeal  with  the 
State  Building  Code  Appeals  Board  until  such  time 
as  the  said  local  or  regional  board  renders  a  decision, 
unless  the  reason  for  appeal  to  the  State  Building 
Code  Appeals  Board  is  the  failure  of  the  local  or 
regional  board  to  act. 

122.2  Membership: 

122.2.1  Three  member  panel:  The  State 
Building  Code  Appeals  Board  (hereinafter 
referred  to  in  780  CMR  122.0  as  the  Board)  shall 
consist  of  the  membership  of  the  BBRS.  The 
chairman  of  the  BBRS  shall  be  Chairman  of  the 
Board.  The  Chairman  of  the  Board  may  designate 
any  three  members  of  the  Board  to  act  as  a  three 
member  panel  to  hold  any  public  hearing  under 
780  CMR  122.0  and  to  hear  testimony  and  take 
evidence.  The  Chairman  of  the  Board  shall  select 
one  of  the  three  members  to  act  as  chairman  of  the 
said  three  member  panel.  If  a  three  member  panel 
is  so  designated,  the  three  member  panel  shall  act 
as  the  Appeals  Board  and  render  a  decision  as 
provided  in  780  CMR  122.0. 

122.2.2  Clerk:  The  administrator  of  the  BBRS 
shall  designate  a  clerk  to  the  BBRS.  The  clerk 
shall  keep  a  detailed  record  of  all  decisions  and 
appeals  and  a  docket  book  on  file  showing  the 
name  of  each  appeal  properly  indexed  and  the 
disposition  of  the  appeal.  Said  docket  book  shall 
be  open  to  public  inspection  at  all  times  during 
normal  business  hours. 

122.2.3  Quorum:  A  majority  of  the  Board  shall 
constitute  a  quorum  if  the  appeal  is  heard  by  the 
entire  Board. 

122.3  Appeals  procedure  for  State  Building  Code 
Appeals  Board: 

122.3.1  Entry:  Appeals  shall  be  entered  on 
forms  provided  by  the  BBRS  and  shall  be 
accompanied  by  an  entry  fee  of  SI 50  or  such 
other  amounts  as  may  be  determined  by  the  BBRS 
from  time  to  time. 

The  appeal  shall  be  signed  by  the  appellant  or 
his  attorney  or  agent  and  shall  note  the  name  and 
address  of  the  person  or  agency  in  whose  behalf 
the  appeal  is  taken  and  the  name  of  the  person  and 
address  wherein  service  of  notice  for  the  appellant 
is  to  be  made.  The  appeal  shall  also  state  in  detail 


the  interpretation,  order,  requirement,  direction  or 
failure  to  act  which  are  the  grounds  of  the  appeals 
as  well  as  the  particular  section  or  sections  of 
780  CMR  which  are  involved  in  the  appeal  and 
the  reasons  for  the  appellant  advances  supporting 
the  appeal. 

A  copy  of  the  appeal  shall  be  served  in 
accordance  with  780  CMR  1 18.6  by  the  appellant 
on  the  person  or  state,  regional  or  local  agency 
from  whose  action  or  inaction  the  appeal  is  taken, 
on  or  before  entry  of  the  appeal.  An  affidavit, 
under  oath,  that  such  copy  has  been  served  shall 
be  filed  with  the  Board  forthwith  by  the  appellant. 

122.3.2  Stay  of  Proceedings:  Entry  of  an  appeal 
shall  stay  all  proceedings  in  furtherance  of  the 
action  or  failure  to  act  appealed  from,  unless  the 
state,  regional  or  local  agency  or  any  person 
charged  with  the  administration  or  enforcement  of 
780  CMR  presents  evidence  and  the  Board  or  a 
three  member  panel  or  a  single  member  of  the 
Board,  appointed  by  the  chairman  for  said 
purpose,  finds  that  upon  the  evidence  presented  a 
stay  would  involve  imminent  peril  to  life  or 
property.  In  such  an  event,  stay  of  all  proceedings 
shall  be  waived  or  the  Board  or  three  member 
panel  or  single  member  may  order  such  other 
action  necessary  to  preserve  public  safety. 

Before  waiving  the  stay  or  proceedings,  the 
Board  or  three  member  panel  or  single  member  of 
the  Board,  appointed  by  the  chairman  for  said 
purpose,  shall  hold  a  hearing  and  give  the 
appellant  and  state,  regional  or  local  agency  or 
any  person  claiming  that  a  stay  would  involve 
imminent  peril  to  life  or  property,  notice  in 
writing  of  the  hearing  not  less  than  24  hours 
before  said  hearing. 

122.3.3  Documents:  Upon  entry,  the  clerk  shall 
request  in  writing  from  the  state,  city,  regional  or 
town  officer  in  charge  of  the  matter  on  appeal,  a 
copy  of  the  record  and  all  other  papers  and 
documents  relative  to  the  appeal  to  be  transmitted 
forthwith  to  the  Board.  Said  state,  city,  regional 
or  town  officer  shall  upon  receipt  of  the  request  of 
the  Board  transmit  forthwith  all  the  papers  and 
documents  and  a  copy  of  the  record  relating  to  the 
matter  on  appeal. 

122.3.4  Hearings:  The  chairman  of  the  Board 
shall  fix  a  convenient  time  and  place  for  a  public 
hearing.  Said  hearings  shall  be  held  not  later  than 
30  days  after  the  entry  of  such  appeal,  unless  such 
time  is  extended  by  agreement  with  the  appellant. 
Any  such  party  may  appear  in  person  or  by  agent 
or  attorney  at  such  hearing.  The  chairman  or 
clerk  shall  give  notice  of  the  time  and  place  of 
said  hearing  to  all  parties  to  the  hearing  and  to 
anyone  else  requesting  notice  in  writing  at  least 
ten  days  prior  thereto.  Failure  to  hold  a  public 
hearing  within  30  days  shall  not  affect  the  validity 
of  the  appeal  or  any  decision  rendered  The 
Board   or  three  member  panel   in   its  hearings 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


conducted  under  this  section  shall  not  be  bound 
by  strict  rules  of  evidence  prevailing  in  courts  of 
law  or  equity. 

122.3.5  Conduct  of  Hearing:  Hearing  shall  be 
conducted  in  accordance  with  the  informal/fair 
hearing  rules  as  set  forth  in  801  CMR  1.02. 

122.4  Decisions: 

122.4.1  Votes  required:  If  the  appeal  is 
conducted  by  a  three  member  panel,  then  the 
concurrence  of  two  of  the  three  members  holding 
the  public  hearing  shall  be  required.  If  the  appeal 
is  conducted  by  the  entire  Board,  then  a  majority 
vote  of  those  hearing  the  case  shall  be  required. 

122.4.2  Standard:  The  Board  or  a  three  member 
panel  may  vary  the  application  of  any  provision  of 
780  CMR  in  any  particular  case,  may  determine 
the  suitability  of  alternate  materials  and  methods 
of  construction,  and  provide  reasonable 
interpretations  of  the  provisions  of  780  CMR 
provided  that  the  Board  or  a  three-member  panel 
finds  that  the  decision  to  grant  a  variance  shall  not 
conflict  with  the  general  objectives  set  forth 
M.G.L.  c.  143,  §  95  or  with  the  general  objectives 
of  780  CMR. 

122.4.3  Time  for  decision:  The  Board  shall 
within  30  days  after  such  hearing,  unless  such 
time  is  extended  by  agreement  of  the  parties,  issue 
a  decision  or  order  reversing,  affirming  or 
modifying  in  whole  or  in  part  the  order, 
interpretation,  requirement,  direction  or  failure  to 
act  which  is  the  subject  matter  of  the  appeal. 

Failure  to  render  a  decision  within  30  days 
shall  not  affect  the  validity  of  any  such  decision 
or  appeal. 

Notice  of  and  a  copy  of  the  decision  shall  be 
sent  by  the  clerk  to  all  parties  to  the  appeal  and 
anyone  requesting  in  writing  a  copy  of  the 
decision. 

122.4.4  Contents  of  decision:  All  decisions 
shall  be  in  writing  and  state  findings  of  fact, 
conclusions  and  reasons  for  decisions.  Every 
decision  shall  indicate  thereon  the  vote  of  each 
member  and  shall  be  signed  by  each  member 
voting.  A  decision  shall  not  be  considered  by  any 
person  or  agency  as  a  precedent  for  future 
decisions. 

122.4.5  Additional  powers:  The  Board  or  a 
three  member  panel  may  impose  in  any  decision, 
limitations  both  as  to  time  and  use,  and  a 
continuation  of  any  use  permitted  may  be 
conditioned  upon  compliance  with  future 
amendments  to  780  CMR. 

122.5  Enforcement:  Upon  receipt  of  the  decision 
of  the  Board  or  a  three  member  panel,  the  parties  to 
the  appeal  shall  take  action  forthwith  to  comply  with 


the  decision  unless  a  later  time  is  specified  in  the 
decision. 

122.6  Appeals  from  State  Building  Code  Appeals 
Board:  Any  person  aggrieved  by  a  decision  of  the 
State  Building  Code  Appeals  Board  may  appeal  to  a 
court  of  law  or  equity  in  conformance  with  M.G.L. 
c.  30A,  §  14. 

122.7  Local  and  regional  board  of  appeals: 

122.7.1  Local  or  regional  board  of  appeals: 

Whoever  is  aggrieved  by  an  interpretation,  order, 
requirement,  direction  or  failure  to  act  under 
780  CMR  by  any  agency  or  official  of  a  city, 
region  or  town  charged  with  the  administration  or 
enforcement  of  780  CMR  or  any  of  its  rules  and 
regulations  may  appeal  first  to  the  appeals  board 
in  that  city,  region  or  town  or  to  the  State 
Building  Code  Appeals  Board  as  provided  in 
780  CMR  122.0. 

In  the  event  an  appeal  is  taken  from  an 
interpretation,  order,  requirement  or  direction, 
said  appeal  shall  be  filed  with  the  local  or  regional 
appeals  board  not  later  than  45  days  after  the 
service  of  notice  thereof  of  the  interpretation, 
order,  requirement  or  direction. 

In  the  event  the  appeal  is  taken  for  the  failure 
to  act,  the  appeal  shall  be  taken  not  later  than  45 
days  after  a  request  to  act  has  been  made  by  the 
aggrieved  person  in  writing  and  served  to  the 
appropriate  building  official  or  chief 
administrative  officer  of  the  city,  regional  or  town 
agency  which  fails  to  act. 

122.7.2  Membership:  Any  building  code  board 
of  appeals  duly  established  by  ordinance  or  by 
law  or  otherwise  in  a  city,  region  or  town  and  in 
existence  on  January  1,  1975,  shall  qualify  as  a 
local  board  of  appeals  under  780  CMR  122.0 
notwithstanding  anything  to  the  contrary 
contained  herein.  However,  the  procedure  and 
rights  for  appeals  for  such  board  of  appeals  shall 
be  governed  by  780  CMR. 

If  a  city,  region  or  town  had  not  duly 
established  by  ordinance  or  bylaw  or  otherwise  a 
local  or  regional  building  code  appeals  board 
prior  to  January  1,  1975,  said  city,  region  or  town 
may  establish  a  local  or  regional  board  of  appeals, 
hereinafter  referred  to  as  the  local  board  of 
appeals,  consisting  of  five  members  appointed  by 
the  chief  administrative  officer  of  the  city,  region 
or  town:  one  member  appointed  for  five  years, 
one  for  four  years,  one  for  three  years,  one  for  two 
years  and  one  to  serve  for  one  year;  and  thereafter 
each  new  member  to  serve  for  five  years  or  until 
his  successor  has  been  appointed. 

122.7.3  Qualifications  of  local  board  members: 

Each  member  of  a  local  board  of  appeals 
established  under  780  CMR  122.7.2  shall  have 
had  at  least  five  years  experience  in  the 
construction,  alteration,  repair  and  maintenance  of 


30 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


building  and  building  codes.  At  least  one  member 
shall  be  a  registered  structural  or  civil 
professional  engineer  and  one  member  a  licensed 
registered  architect. 

122.7.4  Chairman  of  local  or  regional  board: 

The  board  shall  select  one  of  its  members  to  serve 
as  chairman  and  a  detailed  record  of  all 
proceedings  shall  be  kept  on  file  in  the  building 
department. 

122.7.5  Absence  of  members:  During  the 
absence  of  a  member  of  a  local  board  of  appeals 
for  reason  of  disability  or  disqualification,  the 
chief  administrative  officer  of  the  city,  region  or 
town  shall  designate  a  substitute  who  shall  meet 
the  qualifications  as  outlined  in  780  CMR 
122.7.3. 

122.7.6  Quorum:  A  quorum  shall  be  three 
members. 

122.7.7  Procedures:  Entry  of  appeals  shall  be 
governed  by  780  CMR  122.3.1  excepting  that  a 
city,  region  or  town  may  set  its  own  entry  fee. 

Upon  notice  of  entry  of  appeal  the  local 
building  commissioner  or  inspector  of  buildings 
shall  transmit  a  copy  of  the  record  and  all  the 
papers  and  documents  to  the  local  board  of 
appeals. 

Entry  of  an  appeal  shall  stay  all  proceedings  in 
furtherance  of  the  action  or  failure  to  act  appealed 
from,  unless  the  building  commissioner  or 
inspector  of  buildings  certifies  in  writing  to  the 
local  board  of  appeals  that  a  stay  would  involve 
imminent  peril  to  life  or  property.  Notice  in 
writing  of  such  certification  by  the  building 
commissioner  or  inspector  of  buildings  shall  be 
given  the  appellant  at  least  24  hours  prior  to  the 
hearing.  In  such  an  event  a  hearing  on  such  stay 
shall  be  given  first  priority  and  be  the  first  matter 
heard  by  the  local  board  of  appeals  at  its  next 
scheduled  meeting.  The  hearing  on  the  appeal 
shall  be  held  as  soon  as  possible  thereafter  in 
accordance  with  780  CMR  122.7.8. 

The  local  board  of  appeals  may  establish  its 
own  rules  for  procedure  not  established  herein  or 
not  inconsistent  with  780  CMR  or  with  the 
general  objectives  set  forth  in  M.G.L.  c.  143, 
§95. 

122.7.8  Hearings:  All  hearings  shall  be  public 
and  notice  of  said  hearings  shall  be  advertised  in 
a  newspaper  of  general  circulation  in  the  city, 
region  or  town  in  which  the  appeal  is  taken  at 
least  ten  days  before  said  hearing.  Notice  of  the 
hearing,  setting  forth  the  date  and  time  of  said 
hearing,  shall  be  mailed  by  the  local  board  of 
appeals  to  all  parties  and  all  those  who  requested 
notice  in  writing  at  least  14  days  before  said 
hearing.  Said  hearings  shall  be  held  not  later  than 
30  days  after  the  entry  of  such  appeal,  unless  such 
time  is  extended  by  agreement  with  the  appellant. 
This  section  as  it  pertains  to  notice  shall  not  apply 


to  hearings  on  a  stay  as  provided  in  780  CMR 

122.7.7. 

122.7.9  Decisions  of  local  boards:  A  concurring 
vote  of  a  majority  of  all  the  members  present  shall 
be  required  for  any  decision.  The  local  board  of 
appeals  may  vary  the  application  of  780  CMR  to 
any  particular  case,  may  consider  the  suitability  of 
alternate  materials  and  methods  of  construction 
and  may  provide  reasonable  interpretations  of  the 
provisions  of  780  CMR;  provided  that  the 
decision  of  the  local  board  shall  not  conflict  with 
the  general  objectives  of  780  CMR  or  with  the 
general  objectives  of  M.G.L.  c.  143,  §  95.  The 
local  board  of  appeals  may  impose,  in  any 
decision,  limitations  both  as  to  time  and  use,  and 
a  continuation  of  any  use  permitted  may  be 
conditioned  upon  compliance  with  future 
amendments  to  780  CMR. 

122.7.10  Time  for  decision:  The  board  shall 
within  30  days  after  such  hearing,  unless  such 
time  is  extended  by  agreement  of  the  parties,  issue 
a  decision  or  order  reversing,  affirming  or 
modifying  in  whole  or  in  part  the  order, 
interpretation,  requirement,  direction  or  failure  to 
act  which  is  the  subject  matter  of  the  appeal. 

Failure  to  render  a  decision  within  30  days 
shall  not  affect  the  validity  of  any  such  decision 
or  appeal. 

Notice  of  and  a  copy  of  the  decision  shall  be 
sent  by  the  clerk  to  all  parties  to  the  appeal  and  to 
anyone  requesting  in  writing  a  copy  of  the 
decision. 

122.7.11  Contents  of  decision:  All  decisions 
shall  be  in  writing  and  state  findings  of  fact, 
conclusions  and  reasons  for  the  decisions.  Every 
decision  shall  indicate  thereon  the  vote  of  each 
member  and  shall  be  signed  by  each  member 
voting.  Any  decision  shall  not  be  considered  by 
any  person  or  agency  as  a  precedent  for  future 
decisions. 

122.7.12  Copy  of  decision:  A  copy  of  any 
decision  by  a  local  board  of  appeals  shall  be 
transmitted  to  the  State  Building  Code  Appeals 
Board  within  ten  days  after  the  rendering  of  such 
decision.  If  the  State  Building  Code  Appeals 
Board  disapproves  of  the  said  decision  of  the  local 
board,  it  may  on  its  own  motion  appeal  from  the 
dec'sion  of  the  local  board  of  appeals  according  to 
780  CMR  122.0  and  call  for  a  hearing  de  novo. 

If  the  State  Building  Code  Appeals  Board  does 
not  notify  the  local  board  in  writing  within  45 
days  from  the  date  of  the  local  board's  decision, 
the  said  decision  shall  be  deemed  approved; 
provided  that  the  decision  shall  not  conflict  with 
the  general  objectives  of  the  state  building  code 
and  the  objectives  of  M.G.L.  c.  143,  §  95. 

122.7.13  Enforcement  of  decision:  If  said 
decision  is  approved  by  the  State  Building  Code 
Appeals  Board,  all  parties  to  the  appeal  shall  take 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


31 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


immediate  action  in  accordance  with  the  decision 
of  the  local  board  unless  the  person  aggrieved  by 
such  decision  appeals  to  the  State  Building  Code 
Appeals  Board  as  provided  in  780  CMR  122.0. 

122.7.14  Review:  Any  person,  including  the 
State  Building  Code  Appeals  Board,  aggrieved  by 
a  decision  of  the  local  board  of  appeals,  whether 
or  not  a  previous  party  to  the  decision,  or  any 
municipal  officer  or  official  board  of  the 
municipality,  may,  not  later  than  45  days  after  the 
mailing  of  the  decision  of  the  local  board,  apply  to 
the  State  Building  Code  Appeals  Board  for  a 
hearing  de  novo  before  the  State  Board,  in 
accordance  with  the  regulations  contained  in 
780  CMR  122.0. 

780  CMR  123.0  CONSTRUCTION 
MATERIALS  SAFETY  BOARD 

123.1  Membership:  There  shall  be  a  board  under 
the  control  of  the  BBRS  called  the  Construction 
Materials  Safety  Board,  hereafter  in  780  CMR  123.0 
called  the  CMSB  which  shall  consist  of  nine 
members,  one  of  whom  shall  be  a  member  of  the 
BBRS  who  shall  be  ex-officio  and  a  voting  member 
of  the  Board  and  eight  members  to  be  appointed  by 
the  chairman  of  the  BBRS:  one  of  whom  shall  be  a 
registered  professional  engineer  who  is  a  structural 
engineer;  one  of  whom  shall  be  a  registered 
architect;  one  of  whom  shall  be  a  representative  of  a 
commercial  testing  laboratory;  one  of  whom  shall 
be  a  representative  of  a  public  testing  laboratory; 
two  of  whom  shall  be  representatives  from  the 
construction  industry;  one  of  whom  shall  be  a 
member  of  a  university  faculty  engaged  in  research 
and  teaching  in  structural  materials;  and  one  of 
whom  shall  be  a  member  of  a  university  faculty 
engaged  in  research  and  teaching  in  the  area  of 
theoretical  and  applied  mechanics. 

123.2  Duties:  The  CMSB  will  review  applications 
for  registration  or  licensing  of  individuals, 
laboratories  or  firms  responsible  for  the  inspection, 
control  and  testing  of  construction  materials,  and 
review  applications  and  pertinent  data  relevant  to  all 
materials,  devices,  products  and  methods  of 
construction  not  included  in  780  CMR;  and  report  to 
the  BBRS  their  recommendations.  The  CMSB  will 
collect  information  and  review  cases  where 
disciplinary  action  against  an  existing  license, 
whether  an  individual,  laboratory  or  firm,  has  been 
proposed;  and  make  recommendations  to  the  BBRS. 
The  BBRS  will  issue  applications,  receive  payment 
for  the  review  of  such  applications  and  approvals, 
registration  and  licensing  fees,  and  maintain  records 
for  the  efficient  dispatch  of  the  duties  of  the  CMSB. 

123.3  Testing  and  evaluation  groups:  The  BBRS 
shall  establish  and  maintain  testing  and  evaluation 
groups  who  will  have  the  responsibility  of 
administering  and  directing,  under  the  supervision  of 


the  BBRS,  the  testing  and  controls  for  evaluating 
individual  applicants,  laboratories  and  firms  wishing 
to  become  registered  or  licensed. 

780  CMR  124.0  FERE  PREVENTION  -FERE 
PROTECTION  ADVISORY  COMMOTEE 

124.1  Constitution  of  the  Fire  Prevention  -  Fire 
Protection  Advisory  Committee:  There  shall  be 
a  Committee  under  the  control  of  the  BBRS  called 
the  Fire  Prevention  -  Fire  Protection  Advisory 
Committee,  hereinafter  called  the  FPFP  Advisory 
Committee  which  shall  consist  of  16  members,  two 
of  whom  shall  be  members  of  the  BBRS;  one  of 
whom  shall  be  the  State  Fire  Marshal  or  his 
designee;  one  of  whom  shall  be  the  Commissioner  of 
the  City  of  Boston  Fire  Department  or  his  designee; 
all  four  of  whom  shall  be  ex-officio  and  voting 
members  of  the  Committee,  and  12  members  to  be 
appointed  by  the  chairman  of  the  BBRS  for  a  term  of 
one  year;  two  of  whom  shall  be  representatives  of 
the  Fire  Chiefs  Association  of  Massachusetts;  two  of 
whom  shall  be  representatives  of  the  Fire  Prevention 
Association  of  Massachusetts;  one  of  whom  shall  be 
a  representative  of  the  International  Municipal 
Signalmen's  Association;  one  of  whom  shall  be  a 
member  of  the  State  Board  of  Fire  Prevention 
Regulations;  one  of  whom  shall  be  a  member  of  the 
Board  of  State  Examiners  of  Electricians  who 
satisfies  the  requirements  of  that  Board  as  a  systems 
contractor  holding  a  certificate  C  license  and  is 
actively  engaged  in  the  business  of  fire  warning 
systems;  one  of  whom  shall  be  a  Massachusetts 
building  official;  one  of  whom  shall  be  a 
Massachusetts  registered  Fire  Protection  Engineer; 
one  of  whom  shall  be  a  Massachusetts  registered 
professional  engineer  or  architect;  one  of  whom 
shall  be  a  Massachusetts  registered  professional 
engineer  with  specific  experience  in  the  design  and 
installation  of  smoke  control  systems,  and;  one  of 
whom  shall  be  a  sprinkler  system  installer  who  shall 
be  certified  by  the  National  Institute  for  Certification 
in  Engineering  Technologies  (NICET). 

The  FPFP  Advisory  Committee  shall  elect  a 
chairman  and  a  vice  chairman  and  each  shall  serve 
for  a  term  one  year.  A  member  of  an  agency  or 
board  of  the  state  shall  not  be  eligible  for  the  office 
of  chairman  or  vice  chairman. 

124.2  Purpose:  The  FPFP  Advisory  Committee 
shall  review  and  recommend  to  the  BBRS  changes 
to  780  CMR  relating  to  fire  prevention  and  fire 
protection  and  more  specifically  those  matters 
contained  in  780  CMR  9. 

780  CMR  125.0  STRUCTURAL  PEER  REVIEW 

ADVISORY  COMMITTEE 
125.1  Membership:  There  shall  be  a  Board  under 
the  control  of  the  BBRS  called  the  Structural  Peer 
Review  Advisory  Committee,  which  shall  consist  of 
seven  members,  six  of  whom  shall  be  professional 
engineers,  registered  in  Massachusetts,  each  having 


32 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ADMINISTRATION 


a  minimum  of  ten  years  of  structural  design 
experience  and  shall  be  appointed  by  the  BBRS  from 
nominations  submitted  by  the  Boston  Association  of 
Structural  Engineers,  the  Boston  Society  of  Civil 
Engineers  and  the  American  Consulting  Engineers 
Council  of  New  England.  The  seventh  member  shall 
be  the  structural  engineer  member  of  the  BBRS  who 
shall  serve  as  chairman  of  said  Advisory  Board. 

125.2  Quorum:  The  chairman  of  said  Advisory 
Committee  shall  appoint  three  of  the  members  to 
mediate  the  disputes  by  a  majority  vote  of  the  three 
members. 

125.3  Purpose:  The  Structural  Peer  Review 
Advisory  Committee  shall  mediate  any  unresolved 


disputes  between  the  engineer  of  record  and  the 
reviewing  engineer  which  may  result  from  the 
independent  structural  engineer  review  specified  in 
780  CMR  110.11. 

125.4  Procedure:  The  structural  engineer  of  record 
or  the  reviewing  engineer  or  the  owner  or  the 
building  official  shall  submit  any  unresolved 
disputes  cited  in  Appendix  1-5  (3),  to  the  Structural 
Peer  Review  Advisory  Committee  on  a  form 
provided  for  this  purpose.  Said  Committee  shall 
convene  a  mediation  hearing  within  30  days  from 
the  receipt  of  the  application  and  render  a  decision 
in  writing  within  30  days  following  the  mediation 
hearing. 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


34  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  2 


DEFINITIONS 


780  CMR  201.0  GENERAL 

201.1  Scope:  Unless  otherwise  expressly  stated,  the 
following  words  and  terms  shall,  for  the  purposes  of 
780  CMR,  have  the  meanings  shown  in  780  CMR  2. 

201.2  Interchangeability  Words  used  in  the 
present  tense  include  the  future;  words  used  in  the 
masculine  gender  include  the  feminine  and  neuter; 
the  singular  number  includes  the  plural  and  the 
plural  the  singular. 

201.3  Terms  defined  in  other  codes:  Where  terms 
are  not  defined  in  780  CMR  and  are  defined  in  the 
plumbing  (248  CMR).  fire  prevention  (527  CMR)  or 
BOCA  mechanical  codes  or  other  reference  stan- 
dards listed  in  Appendix  A,  such  terms  shall  have 
the  meanings  ascribed  to  them  as  in  those  codes. 

201.4  Terms  not  defined:  Where  terms  are  not 
defined  through  the  methods  authorized  by 
780  CMR  201.0,  such  terms  shall  have  the  ordinarily 
accepted  meanings  such  as  the  context  implies. 

201.5  Applications  of  other  laws  :  Nothing  herein 
contained  shall  be  deemed  to  nullify  any  provisions 
of  the  zoning  by-laws  or  ordinance  of  any 
municipality  in  the  Commonwealth  of 
Massachusetts  insofar  as  those  provisions  deal 
exclusively  with  those  powers  of  regulating  zoning 
granted  by  the  provisions  ofM.G.L.  c.  40 A  and  41 
or  St  1956,  c  665,  as  amended 

780  CMR  202.0  GENERAL  DEFINITIONS 
Acceleration:  See  780  CMR  1612.3. 

Accepted  engineering  practice:  That  which 
conforms  to  accepted  principles,  tests  or  standards 
of  nationally  recognized  technical  or  scientific 
authorities. 

Accessible:  See  780  CMR  1 101.0. 

Accessible  route:  See  780  CMR  1101.0. 

Accessory  structure:  A  building,  the  occupancy  of 
which  is  incidental  to  that  of  the  main  building, 
that  is  located  on  the  same  lot  as  the  main 
building. 

Adaptability:  See  780  CMR  1101.0 

Addition:  An  increase  in  building  area,  aggregate 
floor  area,  height  or  number  of  stories  of  a 
structure  (see  780  CMR  3400.3(4)). 


Admixture:  See  780  CMR  1902.0. 

Aerosol:  See  780  CMR  307  2. 

Aerosol  container  See  780  CMR  307.2. 

Aisle  accessway:  See  780  CMR  1002.0. 

Alarm  verification:  See  780  CMR  902.0. 

Alteration:  A  change  or  modification  of  a  building 
or  structure,  or  the  service  equipment  thereof, 
that  affects  safety  or  health  and  that  is  not 
classified  as  an  ordinary  repair. 

Alternating  tread  stairway   See  780  CMR  1002.0. 

Alternate  Inspector:  A  person  appointed  to  act  in 
the  absence  of  the  inspector  of  buildings  or 
building  commissioner  in  case  of  illness, 
disability,  or  conflicting  interest  An  alternate 
inspector  shall  meet  or  exceed  the  minimum 
qualifications  defined  by  M.G.L.  c.  143,  § 3  for 
an  inspector  of  buildings/building  commissioner 
and  shall  be  certified  in  accordance  with 
780  CMR  R7.  See  also  780  CMR  105.2 

Anchor:  See  780  CMR  2102.0. 

Anchor  Store:  See  780  CMR  402.2. 

Approval:  When  used  in  780  CMR  35  for 
manufactured  buildings  or  building  components, 
approved  by  the  State  Board  of  Building 
Regulations  and  Standards,  hereinafter  known 
as  the  BBRS. 

Approved  agency:  See  780  CMR  1702.0. 

Approved   material,   equipment   and   methods: 

Material,  equipment  and  methods  evaluated  and 
approved  (see  780  CMR  109.0). 

Approved  rules:  The  legally  adopted  rules  of  the 
code  official  (see  780  CMR  106.0) 

Appurtenant  structure:  A  device  or  structure 
attached  to  the  exterior  or  erected  on  the  roof  of  a 
building  designed  to  support  service  equipment  or 
used  in  connection  therewith,  or  for  advertising  or 
display  purposes,  or  other  similar  uses. 

Architectural  terra  cotta:  See  780  CMR  2102.0 

Area,  building:  See  780  CMR  502.0. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


35 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Area,  gross  cross-sectional:  See  780  CMR  2102  0 

Areaway  (form  of  construction):  See  780  CMR 

3203.2. 

Attic:  See  780  CMR  1202.0 
Automatic:  See  780  CMR  902.0. 

Automatic  fire  suppression  system:  See  780  CMR 

902.0. 

Barricade:  See  780  CMR  307.2. 

Base:  See  780  CMR  1612.3. 

Base  shear:  See  780  CMR  1612.3. 

Basement:  See  780  CMR  502.0. 

Bay  (part  of  a  structure):  See  780  CMR  1612.3 

RB.RS.:  (Massachusetts)  Board  of  Building 
Regulations  and  Standards. 

Bed  joint:  See  780  CMR  2102.0. 

Bleachers:  See  780  CMR  1002.0. 

Blocked  diaphragm:  See  780  CMR  2306  2. 

Boiling  point:  See  780  CMR  307.2. 

Box  system:  A  structural  system  where  the  vertical 
load  is  carried  by  bearing  walls  and  structural 
framing  and  where  the  lateral  stability  and 
lateral  force  resisting  system  consists  of  shear 
walls  or  braced  wall 

Brick 

Calcium  silicate  brick  (sand  lime  brick):  See 

780  CMR  2102.0. 

Clay  or  shale:  See  780  CMR  2102.0. 
Concrete  brick:  See  780  CMR  2102.0 
Hollow  brick:  See  780  CMR  2102.0. 

Building:  A  structure  enclosed  within  exterior  walls 
or  firewalls,  built,  erected  and  framed  of  a 
combination  of  any  materials,  whether  portable 
or  fixed  having  a  roof,  to  form  a  structure  for 
the  shelter  of  persons,  animals  or  property.  For 
the  purpose  of  this  definition,  "roof"  shall 
include  an  awning  or  similar  covering,  whether 
or  not  permanent  in  nature.  The  word  "building 
shall  be  construed  where  the  context  requires  as 
though  followed  followed  by  the  words  "or  parts 
thereof".  For  application  of  780  CMR,  each 
portion  of  a  building  which  is  completely 
separated  from  other  portions  by  fire  walls 
complying  with  780  CMR  707.0  shall  be 
considered  as  a  separate  building. 


Building  Code  Enforcement  Official:  The  term 
used  to  collectively  refer  to  Inspector  of 
Buildings,  Building  Commissioners,  and  Local 
Inspectors.  All  building  code  enforcement 
officials  shall  meet  or  exceed  the  minimum 
qualifications  for  the  position  as  defined  by 
M.G.L.  c.143,  §  3  and  shall  be  certified  in 
accordance  with  780  CMR  R7. 

Building  Commissioner:  The  Administrative  chief 
of  the  building  department  in  a  municipality  who 
is  charged  with  the  administration  and 
enforcement  of  780  CMR  (See  also  "Inspector 
of  Buildings"  and  780  CMR  105. 0).  All  building 
commissioners  shall  meet  or  exceed  the 
minimum  qualifications  for  the  position  as 
defined  in  M.G.L  a  143  § 3  and  shall  be  certified 
in  accordance  with  780  CMR  R7. 

Building  Component:  Any  subsystem,  subassembly, 
or  other  system  designed  for  use  in  or  as  part  of 
a  structure  having  concealed  elements  such  as 
electrical,  mechanical,  plumbing  and  fire 
protection  systems  and  other  systems  protecting 
health  and  safety. 

Building,  existing:  Any  structure  occupied  prior  to 
the  date  of  adoption  of  the  appropriate  code,  or 
one  for  which  a  legal  building  permit  has  been 
issued    (See  also  780  CMR  34) 

Building  line:  The  line  established  by  law,  beyond 
which  a  building  shall  not  extend,  except  as 
specifically  provided  by  law. 

Building  service  equipment:  The  mechanical, 
electrical  and  elevator  equipment  including 
piping,  wiring,  fixtures  and  other  accessories, 
which  provides  sanitation,  lighting,  heating, 
ventilation,  fire  protection  and  transportation 
facilities  essential  for  the  habitable  occupancy  of 
the  building  or  structure  for  its  designated 
occupancy. 

Building  site:  The  area  occupied  by  a  building  or 
structure,  including  the  yards  and  courts  required 
for  light  and  ventilation,  and  such  areas  that  are 
prescribed  for  access  to  the  street. 

Bulk  Merchandiung  Retail  Building:  (See 
780  CMR  426.0.)  Mercantile  Buildings  where 
sales  areas  contain: 

1.  Combustible  materials  in  piles  greater 
than  12  feet  in  height,  or  combustible 
materials  on  pallets,  in  racks  or  on  shelves 
where  the  top  of  storage  is  greater  than  12 
feet  in  height,  or 

2.  Combustible  materials  such  as  rubber 
tires,  Group  A  plastics,  flammable  liquids, 
idle  pallets  and  commodities  with  similar  heat 


36 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780:    CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

DEFINITIONS 


release  characteristics,  where  the  top  storage 
is  greater  than  six  feet  in  height 

Buttress:  See  780  CMR  2102.0. 

Cellar:  that  portion  of  a  building  which  is  partly 
or  completely  below  grade  and  having  at  least  Vz 
its  height  below  grade. 

Cementitious  material:  See  780  CMR  1902.0. 

Central  Station,  Central  Station  Fire  Alarm  Systen 
and  Central  Station  Services:  See  NFPA  72,  as 
listed  in  Appendiz  A. 

Certificate  of  approval:  A  written  document  from 
the  appropriate  code  official  approving  an 
action,  type  of  material,  and  the  like. 

Certificate  of  use  and  occupancy:  The  certificate 
issued  by  the  code  official  which  permits  the  use 
of  a  building  in  accordance  with  the  approved 
plans  and  specifications  which  certifies 
compliance  with  provisions  of  law  for  the  use 
and  occupancy  of  the  building  in  its  several  parts 
together  with  any  special  stipulations  or 
conditions  of  the  building  permit 

Certification:  Any  manufactured  building  or 
building  component  that  meets  the  provisions  of 
780  CMR  35  and  the  rules  and  regulations 
pursuant  thereto  and  which  has  been  labeled 
accordingly.  See  also  780  CMR  R7  for  the 
certification  of  Building  Code  Enforcement 
Officials 

Change  of  use:  An  alteration  by  change  of  use  in 
a  building  heretofore  existing  to  a  new  use  group 
which  imposes  other  special  provisions  of  law 
governing  building  construction,  equipment  or 
means  of  egress. 

Child  day  care  center:  Any  facility  operated  on  a 
regular  basis  whether  known  as  a  day  nursery, 
nursery  school,  kindergarten,  child  play  school, 
progressive  school  child  development  center,  or 
preschool,  or  known  under  any  other  name, 
which  receives  children  not  of  common 
parentage  under  seven  years  of  age  or  under  16 
years  of  age  if  such  children  have  special  needs 
for  non-residential  custody  and  care  during  part 
or  all  of  the  day  separated  from  their  parents. 
Child  day  care  centers  shall  not  include:  any 
part  of  a  public  school  system;  any  part  of  a 
private,  organized  educational  system  unless  the 
services  of  such  a  system  are  primarily  limited  to 
a  kindergarten,  nursery  or  related  preschool 
services;  a  Sunday  school  conducted  by  a 
religious  institution;  a  facility  operated  by 
religious  organization  where  children  are  cared 
for  during  short  periods  of  time  while  persons 


responsible  for  such  children  are  attending 
religious  services;  a  family  day  care  home,  as 
defined  by  M.G.L.  c.  28 A,  §  9;  an  informal 
cooperative  arrangement  among  neighbors  or 
relatives:  or  the  occasional  care  of  children  with 
or  without  compensation  therefor. 

Chimney:  See  780  CMR  2102.0. 

Chimney,  masonry:  See  780  CMR  2102  0. 

Closed  system:  See  7S0  CMR  307.2. 

CMR:  Code  of  Massachusetts  Regulations: 
Appendix  A  contains  a  listing  of  various  CMR's 
for  Massachusetts  specialized  codes. 


Code  official     See 
Official'. 


Building  Code  Enforcement 


Combination  of  municipalities:  Any  two  or  more 
cities  and/or  tmvns  who  have  agreed  to  combine 
in  order  to  share  costs  necessary  for  the 
administration  and  enforcement  of  780  CMR  in 
said  cities  and/or  towns. 

Collar  joint:  See  780  CMR  2102.0. 

Combustible  dusts   See  780  CMR  307.2. 

Combustible  fibers:  See  780  CMR  307  2 

Combustible  liquids   See  "780  CMR  307.2. 

Combustible  material  A  combustible  material  is  a 
material  which  cannot  be  classified  as  non- 
combustible  in  accordance  with  780  CMR 
704  4.11 

Compliance  assurance  program:  The  system, 
documentation  and  methods  for  assuring  that 
manufactured  buildings,  building  components, 
building  systems  and  mobile  homes,  including 
their  manufacture,  storage  transportation  and 
assembly,  and  handling  and  installation, 
conform  with  780  CMR  35  and  the  rules  and 
regulations  promulgated  pursuant  thereto. 

Common  path  of  travel:  See  780  CMR  1002  0 

Compressed  gas:  See  780  CMR  307  2 

Concrete:  See  780  CMR  1902.0 

Concrete,  reinforced:  See  780  CMR  1902  0 

Connector.  See  780  CMR  2102.0. 

Construction  documents  All  of  the  written, 
graphic  and  pictorial  documents  prepared  or 
assembled  for  describing  the  design,  location  and 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


physical  characteristics  of  the  elements  of  the 
project  necessary  for  obtaining  a  building  permit. 
The  construction  drawings  shall  be  drawn  to  an 
appropriate  scale. 

Construction,  type  of:  See  780  CMR  602.0 
Type  1:  See  780  CMR  603.0. 
Type  2:  See  780  CMR  603.0. 
Type  3:  See  780  CMR  604.0. 
Type  4:  See  780  CMR  605.0. 
Type  5:  See  780  CMR  606.0 

Control  area:  See  780  CMR  307.2. 

Corridor:  See  780  CMR  1002.0. 

Corrosive:  See  780  CMR  307.2. 

Court:  See  780  CMR  1202.0. 
Inner:  See  780  CMR  1202.0. 
Outer:  See  780  CMR  1202.0. 

Court  width:  See  780  CMR  1202.0. 

Cryogenic  liquids  (flammable  or  oxidizing):  See 

780  CMR  307.2. 

Curb  level:  See  780  CMR  3203.2. 

Building  or  wall  height:  See  780  CMR  3203.2 

Damper,  fire:  See  780  CMR  702.0. 

Day  care  center  (child):     See  "Child  day  care 
center". 

Deflagration:  See  780  CMR  307.2. 

Deluge  system:  See  780  CMR  902.0. 

Department:    (DPS):    The  Department  of  Public 
Safety,  Division  of  Inspection. 

Design  earthquake:  See  780  CMR  1612.3 

Designated  seismic  systems:  See  780  CMR  1612.3. 

Detached  storage  building:  See  780  CMR  307  2. 

Detector,  heat:  See  780  CMR  902.0. 

Detector,  smoke:  See  780  CMR  902.0. 

Detonation:  See  780  CMR  307.2. 


of  Massachusetts,  and  shall  be  used  to  treat 
individuals  acceptable  to  the  program  in 
accordance  with  105  CMR  160.000. 

Diaphragm:  See  780  CMR  1612.3,  2102.0  and 
2306.2. 

Dimensions,  nominal:  See  780  CMR  2102  0 

Dispensing:  See  780  CMR  307.2. 

Door  assembly,  fire:  See  780  CMR  702.0 

Door,  fire:  See  780  CMR  702.0. 

DPS:  See  "Department". 

Draftstopping:  See  780  CMR  702.0 

Dumbwaiter  See  780  CMR  30 

Dwellings 

Boarding  house:  See  780  CMR  310.2. 

Dormitory:  See  780  CMR  310.2. 

Dwelling  unit:  See  780  CMR  310  2 

Hotel:  See  780  CMR  310  2 

Motel:  See  780  CMR  310.2. 

Multiple-family  dwelling  See  780  CMR  310.2 

Multiple  single-family  dwelling:  See  780  CMR 

310.2. 

One-family  dwelling:  See  780  CMR  310  2 

Two-family  dwelling:  See  780  CMR  310  2 

Effective  height:  See  780  CMR  2102.0. 

Elevator:  780  CMR  30  and  524  CMR. 
Freight  elevator:  See  524  CMR  17.00 
Hand  elevator:  See  524  CMR  18.00 
Hydraulic  elevator:  See  524CMR 
Passenger  elevator:  See  524CMR  17.00 
Power  elevator:  See  524CMR. 
Sidewalk  elevator:  See  524CMR  20.00 

Elevator  repairs:  780  CMR  30  and  524  CMR 

Emergency  control  station:  See  780  CMR  416  2 

Equipment,  existing:  Any  equipment  regulated  by 
780  CMR  which  was  legally  installed  prior  to  the 
effective  date  of  780  CMR,  or  for  which  a  permit 
to  install  has  been  issued. 

Escalator:  780  CMR  30  and  524  CMR. 


Detoxification  facility:     A  facility  licensed  or      Exit:  See  780  CMR  1002.0 
operated  by  the  Department  of  Public  Health, 

Division  of  Alcoholism  in  accordance  with      Exit  access:  See  780  CMR  1002  0 
105    CMR    160.000:    Acute    Care    Inpatient 

Substance    Abuse    Detoxification    Treatment      Exit  discharge:  See  780  CMR  1002.0. 
Services  issued  by  the  Department  of  Public 
Health,  Division  of  Alcoholism,  Commonwealth       Exit  discharge,  level  of  See  780  CMR  1002.0 


38 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780:    CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

DEFINITIONS 


Exit,  horizontal:  See  780  CMR  1002.0. 
Explosive:  See  780  CMR  307.2. 
Exterior  envelope:  See  780  CMR  1302.0. 
Exterior  wall  Finish:  See  780  CMR  1402.0. 
Fabric  awning:  See  780  CMR  1609.2. 
Fabric  canopy:  See  780  CMR  1609.2. 
Fabricated  item:  See  780  CMR  1702.0. 
Fabrication  area   See  780  CMR  416  2 
Fire  alarm  box,  manual:  See  780  CMR  902.0. 
Fire  area:  See  780  CMR  702.0. 
Fire  command  station:  See  7S0  CMR  902.0. 
Fire  detector,  automatic:  See  780  CMR  902.0. 


Fireresistance:  See  780  CMR  702.0. 

Fireresistance  rating:  See  780  CMR  702.0 

Firestopping:  See  780  CMR  702.0. 

Fire  separation  assembly:  See  780  CMR  702.0. 

Fire  separation  distance:  The  distance  in  feet 
measured  from  the  building  face  to  the  closest 
interior  lot  line,  to  the  center  line  of  u  street  or 
public  way  or  to  an  imaginary  line  between  tn>o 
buildings  on  the  same  property. 

Flame  spread:  See  780  CMR  802.0. 

Flame  spread  ra::ng:  See  780  CMR  802.0. 

Flameresistance:  See  780  CMR  802.0. 

Flammable:  See  780  CMR  307.2. 

Flammable  compressed  gas:  See  780  CMR  307.2. 


Fire  hazard:  The  potential  degree  of  fire  severity       Flammable  liquids:  See  780  CMR  307.2 
based  on  the  occupancy  of  a  structure,  classified 

as  high,  moderate  or  low.  Flammable  solid:  See  "SO  CMR  307.2. 

High:  All  occupancies  which  involve  the  storage, 

sale     manufacture     or     processing     of    highly       Flash  point:  See  780  CMR  307.2. 
combustible,    volatile    flammable    or    explosive 

products   which   are   capable   of  burning   with       Floor  area,  gross:  See  780  CMR  1002.0. 
extreme  rapidity  and  produce  explosions  or  large 

volumes  of  smoke,  poisonous  fumes  or  gases  in       Floor  area,  net:  See  780  CMR  1002.0. 
the  event  of  fire. 

Moderate:   All  occupancies  which  involve  the       Floor  finish:  See  780  CMR  802.0. 
storage,    sale,    manufacture    or   processing    of 
materials    which   are   capable   of  burning  with       Frame 

moderate  rapidity  and-  a  considerable  volume  of  Braced:  See  780  CMR  1612.3. 

smoke,  but  which  do  not  produce  either  poisonous 
fumes  or  explosions,  in  the  event  of  fire. 
Low:  All  occupancies  which  involve  the  storage, 
sale  or  manufacture  of  materials  that  do  not 
ordinarily  burn  rapidlv,  nor  produce  excessive 
smoke,  poisonous  fumes  or  explosions  in  the 
event  of  fire. 


Fire  partition:  See  780  CMR  702.0. 

Fire  protection:  The  provision  of  construction 
safeguards  and  exit  facilities,  and  the  installation 
of  fire  alarm,  fire-detecting  and  fire-extinguishing 
service  equipment  to  reduce  the  fire  risk, 
including  the  risk  involved  in  the  spread  of  fire  by 
exterior  exposure  to  and  from  adjoining  buildings 
and  structure. 

Fire  protection  rating:  See  780  CMR  702.0. 

Fire  protection  system:  See  780  CMR  902.0. 

Fire  window:  See  780  CMR  702.0. 


Concentrically  braced  frame:   See  780  CMR 

1612.3. 

Eccentrically    braced    frame:    See   780   CMR 

1612.3. 

Diagonal  brace:  See  780  CMR  1612  3. 

Lateral    support    members:    See    780    CMR 

1612.3. 

Link  beam:  See  780  CMR  1612.3. 

Link  beam  end  web  stiffeners:  See  780  CMR 

1612.3. 

Link  beam   intermediate  web  stiffener:    See 

780  CMR  1612.3. 

Link    beam    rotation    angle:    See    780    CMR 

1612.3. 

Intermediate  moment  frame:   See  7S0  CMR 

1612.3. 

Ordinary  moment  frame:  See  780  CMR  1612.3. 

Space  frame:  See  780  CMR  1612.3 

Special  moment  frame:  See  780  CMR  1612  3 

Frame  system 

Building:  See  780  CMR  1612.3. 
Dual:  See  780  CMR  1612.3. 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Moment  resisting:  See  780  CMR  1612.3. 
Garage,  private:  See  780  CMR  407.2. 
Garage,  public:  See  780  CMR  408.2. 

Grade  hallway,  grade  lobby,  grade  passageway: 

See  780  CMR  1002.0. 

Grade  plane:  See  780  CMR  502.0. 
Grandstand:  See  780  CMR  1002.0. 
Gross  leasable  area:  See  780  CMR  402.2. 


Hoisting  and  elevating  equipment,  miscellaneous: 

See  524  CMR. 

Incompatible  materials:  See  780  CMR  307.2. 

Inspection,  special:  See  780  CMR  1705. 

Inspector  of  buildings:  The  administrative  chief  of 
the  building  department  in  a  municipality  who  is 
charged  with  the  administration  and 
enforcement  of  780  CMR  (See  also  "Building 
commissioner  and  Building  Code  Enforcement 
Official").  All  inspectors  of  buildings  shall  meet 
or  exceed  the  minimum  qualifications  defined  by 
M.G.L.  c.  143,  §  3  and  shall  be  certified  in 
accordance  with  780  CMR  R7. 


Habitable  space:   Space  in  a  structure  for  living, 
sleeping,  eating,  or  cooking.   Bathrooms,  toilet 

compartments,  closets,  halls,  storage  or  utility      Installing  Contractor:  an  individual  or  firm  duly 

licensed  to  install  apparatus,  appliances,  devices 
or  accessories  relative  to  Heating,  pumping, 
process  piping  and  refrigeration  systems.  (See 
780  CMR  2801.2.1  and  1301.1.1). 
Master  and  Journeyman  Pipefitters: 

M.G.L  c  146,  §§81,  82,  83,  84,  85,  87 and  89. 

528  CMR  10.00,  11.00,  and  13.00 
Master      and      Journeyman      Refrigeration 
Technician: 

M.G.L.  c.  146,  §  45 A,  81,  82,  83,  84,  85,  86, 

88  and  89. 

528  CMR  10. 00,  11. 00  and  13. 00 
Exception:  heating,  pumping,  process  piping 
and  refrigeration  systems  regulated  by  M.G.L 
c.  142,  §§  4  and  13,  State  Board  of  Examiners 
of  Plumbers. 

Inverted  pendulum-type  structures:  See  780  CMR 

1612.3. 


space  and  similar  areas  are  not  considered 
habitable  space. 

Hazard  Index:  See  780  CMR  3401.0 

Hazardous  materials:  See  780  CMR  307.2. 

Hazardous    production    material    (HPM):    See 

780  CMR  4 16.2. 

Head  joint:  See  780  CMR  2102.0. 

Header  (Bonder):  See  780  CMR  2102.0. 

Health  hazard:  See  780  CMR  307.2. 

Heated  space:  See  780  CMR  1302.0. 

Height: 

Building:  See  780  CMR  502.0. 
Court:  See  780  CMR  1202.0. 
Story:  See  780  CMR  502.0. 
Walls:  See  780  CMR  2102.0. 

Hereafter:  After  the  time  that  780  CMR  becomes 
effective. 

Heretofore:  Before  the  time  that  780  CMR  became 
effective. 

High-temperature  energy  source:  See  780  CMR 

1612.3. 

Highly  toxic:  See  780  CMR  307.2. 

Hoist,  material  platform:  See  780  CMR  3002.0 

Hoisting  and  conveying  equipment,  special:  See 
524  CMR. 

Automotive  lift:  See  524  CMR 
Conveyors:  See  524  CMR. 
Freight  lift:  See  524  CMR 
Manlifts:  See  524  CMR. 


Irritant:  See  780  CMR  307.2. 

Jurisdiction:  The  governmental  unit  which  has 
adopted  780  CMR  under  due  legislative 
authority. 

Label:  See  780  CMR  1702.0. 

Light-framed    wall    with    shear    panels:     See 

780  CMR  1612.3. 

Listed  and  Listing:  Terms  referring  to  equipment 
which  is  shown  in  a  list  published  by  an  approved 
testing  agency  qualified  and  equipped  for 
experimental  testing  and  maintaining  an  adequate 
periodic  inspection  of  current  productions  and 
whose  listing  states  that  the  equipment  complies 
with  nationally  recognized  standards,  when 
installed  in  accordance  with  the  manufacturer's 
installation  instructions. 

Load:  See  780  CMR  1602.0. 


40 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780:    CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  ST  VNDARDS 

DEFINITIONS 


Dead  load:  See  780  CMR  1602.0. 
Duration  of  load:  See  780  CMR  1602.0. 
Earthquake  load:  See  780  CMR  1602.0. 
Impact  load:  See  780  CMR  1602.0. 
Internal  load:  See  780  CMR  1602.0. 
Lateral  soil  load:  See  780  CMR  1602.0. 
Live  load:  See  780  CMR  1602.0. 
Wind  load:  See  780  CMR  1602.0. 

Loadbearing  wall  system:  See  780  CMR  1612.3. 

Local  enforcement  agency:  A  department  or 
agency  in  a  municipality  charged  with  the 
enforcement  of  780  CMR  and  appropriate 
specialized  codes  which  include,  but  are  not 
limited  to,  248  CMR:  The  State  Plumbing  and 
Gas  Fitting  Code,  and  527  CMR  12. 00:  the  State 
Electrical  Code. 

Local  inspector:  A  person  in  the  municipality  who 
assists  the  building  commissioner  or  inspector  of 
buildings  in  the  performance  of  his  or  her  duties 
and  is  charged  with  the  enforcement  of 
780  CMR.  All  local  inspectors  shall  meet  or 
exceed  the  minimum  qualifications  defined  by 
M.G.L.  c.  143,  §  3  and  shall  be  certified  in 
accordance  with  780  CMR  R7. 

Lot:  A  portion  or  parcel  of  land  considered  as  a  unit. 

Lot,  corner:  A  lot  with  two  adjacent  sides  abutting 
upon  streets  or  other  public  spaces. 

Lot,  interior:  A  lot  which  faces  on  one  street  or  with 
opposite  sides  on  two  streets. 

Lot  line:  A  line  dividing  one  lot  from  another,  or 
from  a  street  or  any  public  place. 

Lot  line,  interior:  Any  lot  line  other  than  one 
adjoining  a  street  or  public  space. 

Lot  line,  street:  The  lot  line  dividing  a  lot  from  a 
street  or  other  public  way. 

Main  windforce-resisting  system:  See  780  CMR 

16. 


request  of  the  manufacturer. 

Masonry:  See  780  CMR  2102.0. 

Ashlar  facing  masonry:  See  780  CMR  2102.0. 
Ashlar  masonry:  See  780  CMR  2102.0. 
Solid  masonry:  See  780  CMR  2102.0. 

Masonry  unit 

Clay:  See  780  CMR  2102.0. 
Concrete:  See  780  CMR  2102.0. 
Hollow:  See  780  CMR  2102.0. 
Solid:  See  780  CMR  2102.0. 

Means  of  egress:  See  780  CMR  1002.0. 

Member: 

Primary:  See  780  CMR  1902.0. 
Secondary:  See  780  CMR  1902.0 

Membrane:  See  780  CMR  3 103.2. 

Membrane  structures: 

Air-inflated  structure:  See  780  CMR  3103.2. 

Air-supported  structure:  See  780  CMR  3  103.2. 

Double  skin:  See  780  CMR  3103.2. 

Single  skin:  See  780  CMR  3 103.2. 

Cable-restrained,  air-supported  structure:  See 

780  CMR  3  103.2. 

Membrane-covered      cable     structure:      See 

780  CMR  3 103.2. 

Membrane-covered     frame     structure:     See 

780  CMR  3 103.2. 

Noncombustible    membrane    structure:    See 

780  CMR  3 103.2. 

Tent:  See  780  CMR  3103.2. 

Mezzanine:  See  780  CMR  502.0. 

Mobile  home:  A  structure  transportable  in  one  or 
more  sections,  which  is  eight  body  feet  or  more 
in  width  and  is  32  body  feet  or  more  in  length, 
and  which  is  built  on  a  permanent  chassis,  and 
designed  to  be  used  as  a  dwelling  with 
permanent  foundation,  when  connected  to  the 
required  facilities,  and  includes  the  plumbing, 
heating,  air-conditioning  and  electrical  systems 
contained  therein. 


Mall:  See  780  CMR  402.2. 

Mall  building,  covered:  See  780  CMR  402.2. 

Manufactured  building:  Any  building  which  has 
concealed  elements,  such  as  electrical, 
mechanical,  plumbing,  fire  protection, 
insulation  and  other  systems  affecting  health 
and  safety,  and  which  is  manufactured  and 
assembled  in  manufacturing  facilities,  on  or  off 
the  building  site.  Also,  any  building  as  defined 
above  which  does  not  have  concealed  elements, 
but  which  has  been  approved  by  the  BBRS  at  the 


Mortar:  See  780  CMR  2102.0. 


Mortar,  surface-bonding:  See  780  CMR  2102.0. 

Moving  walk:  See  780  CMR  30. 

Native  lumber:  Native  lumber  is  wood  processed  in 
the  Commonwealth  of  Massachusetts  by  a  mill 
registered  in  accordance  with  780  CMR  R4. 
Such  wood  is  ungraded  but  is  stamped  or 
certified  in  accordance  with  the  requirements  of 
780  CMR  R4.  For  the  purpose  of  this  definition, 
native  lumber  shall  he  restricted  to  the  use  in 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


one-  and  two-story  dwellings,  barns,  sheds, 
agricultural  and  accessory  buildings  and  other 
structures  when  permitted  by  780  CMR  R4. 

Nominal  dimension 

Lumber:  See  780  CMR  2302.0. 

Noncombustible:  This  is  a  general,  relative  term.  Its 
precise  meaning  is  defined  in  7S0  CMR  for 
specific  applications. 

Noncombustible  building  material:  See  780  CMR 

704.4.1.1 

Occupancy:  The  purpose  for  which  a  building  or 
portion  thereof  is  used. 

Occupancy,  change  of:  A  change  in  the  purpose  or 
level  of  activity  within  a  structure  that  involves  a 
change  in  application  of  the  requirements  of 
780  CMR. 

Occupant  load:  See  780  CMR  1002.0. 

Occupiable  space:  See  780  CMR  1202.0. 

Occupied:  As  applied  to  a  building,  shall  be 
construed  as  though  followed  by  the  words  "or 
intended,  arranged  or  designed  to  be  occupied." 

Official  Interpretation:  A  written  interpretation  of 
any  provision  of  780  CMR,  or  to  its  referenced 
standards  listed  in  Appendix  A,  except 
specialized  codes,  made  by  the  BBRS,  under 
authority  of  M.G.L.  c.  143,  §  94(e),  or  by  the 
State  Building  Code  Appeals  Board  under 
authority  of  M.G.L.  c  143,  §  100. 

Open  system:  See  780  CMR  307.2. 

Organic  peroxide:  See  780  CMR  307.2. 

Oriel  window:  See  780  CMR  3203.2. 

Owner:  Every  person  who  alone  or  jointly  or 
severally  with  others  (a)  has  legal  title  to  any 
building  or  structure;  or  (b)  has  care,  charge,  or 
control  of  any  building  or  structure  in  any 
capacity  including  but  not  limited  to  agent, 
executor,  executrix,  administrator, 

administratrix,  trustee  or  guardian  of  the  estate 
of  the  holder  of  legal  title;  or  (c)  lessee  under  a 
written  letter  agreement;  or  (d)  mortgagee  in 
possession;  or  (e)  agent,  trustee  or  other  person 
appointed  by  the  courts.  Each  such  person  is 
bound  to  comply  with  the  provisions  of 
780  CMR 

Oxidizer:  See  780  CMR  307.2. 

P-Delta  effect:  See  780  CMR  1612.3. 


Panel  (part  of  a  structure):  See  780  CMR  1602.0. 

Particleboard:  See  780  CMR  2302.1. 

Penthouse:  See  780  CMR  1502.1. 

Permit:  An  official  document  or  certificate  issued  by 
the  authority  having  jurisdiction  which  authorizes 
performance  of  a  specified  activity  (see  780  CMR 
111.1). 

Person:  Includes  a  corporation,  firm,  partnership, 
association,  organization  and  any  other  group 
acting  as  a  unit  as  well  as  individuals.  It  shall 
also  include  an  executor,  administrator,  trustee, 
receiver  or  other  representative  appointed 
according  to  law.  Whenever  the  word  "person"  is 
used  in  any  section  of  780  CMR  prescribing  a 
penalty  or  fine,  as  to  partnerships  or  associations, 
the  word  shall  include  the  partners  or  members 
thereof,  and  as  to  corporations,  shall  include  the 
officer. 

Physical  hazard:  See  780  CMR  307.2. 

Physically  disabled  person:  See  780  CMR  1102.0. 

Place  of  assembly:  A  room  or  space 
accommodating  SO  or  more  individuals  for 
religious,  recreational,  educational,  political, 
social  or  amusement  purposes,  or  for  the 
consumption  of  food  or  drink,  including  all 
connected  rooms  or  space  with  a  common  means 
of  egress  and  entrance. 

Place  of  outdoor  assembly:  Premises  used  or 
intended  to  be  used  for  public  gatherings  of  200 
or  more  individuals  in  other  than  buildings. 

Plastic 

Light-diffusing  system:  See  780  CMR  2602.0. 
Plastic  glazing:  See  780  CMR  2602.0. 
Plastic  roof  panels:  See  780  CMR  2602.0. 
Plastic  wall  panels:  See  780  CMR  2602.0. 
Reinforced  plastic,  glass  fiber:  See  780  CMR 
2602.0. 

Thermoplastic  material:  See  780  CMR  2602.0. 
Thermosetting  material:  See  780  CMR  2602.0. 

Platform:  See  780  CMR  412.2. 

Plenum:  An  enclosed  portion  of  the  building 
structure,  so  designed  to  allow  the  movement  of  air, 
that  forms  part  of  an  air  distribution  system.  See 
BOCA  National  Mechanical  Code  listed  in 
Appendix  A. 

Pools,  swimming,  hot  tubs  and  spas 

Above-ground/on-ground  pool:  See  780  CMR 

421.2. 

Barrier:  See  780  CMR  421.2. 


42 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780:    CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

DEFINITIONS 


Hot  tub:  See  780  CMR  421.2. 
In-ground  pool:  See  780  CMR  421.2. 


Roof:  See  780  CMR  1502.0. 

Roof  covering:  See  780  CMR  1502.0. 


Private  swimming  pool:  See  780  CMR  421.2. 

Private  swimming  pool,  indoor:  See  780  CMR       Roof  structure:  See  780  CMR  1502.0. 

421.2. 

Private  swimming  pool,  outdoor:  See  780  CMR       Rubble  masonry:  See  780  CMR  2102.0. 


421.2. 

Public  swimming  pool: 

Public  outdoor  inground  swimming  pool,  Semi- 
public  outdoor  inground  swimming  pool:  See 

780  CMR  421.2. 

Spa:  See  780  CMR  421.2. 

Positive  heat  supply:  See  780  CMR  1302.0 

Preaction  system:  See  780  CMR  902.0. 

Premises:  A  lot,  plot  or  parcel  of  land,  including  any 
structure  thereon. 


Coursed  rubble:  See  780  CMR  2102.0. 
Random  rubble:  See  780  CMR  2102.0. 
Rough   or   ordinary    rubble:    See   780   CMR 

2102.0. 

Running  bond:  See  780  CMR  2102.0. 
Seismic-resisting  system:  See  780  CMR  1612.3 
Self-closing:  See  780  CMR  702.0. 
Sensitizer:  See  780  CMR  307.2. 
Service  passage,  HPM:  See  780  CMR  416.2. 


Preservative  treatment  (treated  material):  See       Shaft:  See  780  CMR  702.0. 
780  CMR  2302.0. 


Protected  construction:  See  780  CMR  702.0.. 

Public  way:  See  780  CMR  1002.0. 

Pyrophoric:  See  780  CMR  307.2. 

Radioactive  material:  See  780  CMR  307.2. 

Registered  design  professional:  An  architect  or 
engineer  registered  or  licensed  to  practice 
professional  architecture  or  engineering,  as 
defined  by  the  statutory  requirements  of  the 
professional  registration  laws  of  the 
Commonwealth  of  Massachusetts. 


Shall:  The  term,  where  used  in  780  CMR,  shall  be 
construed  as  mandatory. 

Shear  wall:  See  780  CMR  1612.3. 

Sign:  See  780  CMR  3 102.2. 

Closed  sign:  See  780  CMR  3102.2. 
Ground  sign:  See  780  CMR  3 102.2. 
Marquee  sign   See  780  CMR  3102.2. 
Open  sign:  See  780  CMR  3102.2. 
Portable  sign:  See  780  CMR  3 1 02.2. 
Projecting  sign:  See  780  CMR  3 102.2. 
Roof  sign:  See  780  CMR  3 1 02.2. 
Temporary  sign:  See  780  CMR  3 102.2. 
Wall  sign:  See  780  CMR  3 102.2. 


Repair:  The  reconstruction  or  renewal  of  any  part  of      Single   membrane   penetration:    See   780   CMR 

an   existing   structure   for  the   purpose   of  its  702.0. 

maintenance. 

Site:  A  parcel  of  land  bounded  by  a  lot  line  or  a 
Repairs,  ordinary:   Any  maintenance  which  does  designated  portion  of  a  public  right-of-way. 

not  affect  the  structure,  egress,  fire  protection 

systems,    fire    ratings,     energy    conservation       Slidescape:  See  780  CMR  1002  0. 

provisions,  plumbing,  sanitary,  gas,  electrical  or 

other  utilities.  A  building  permit  is  not  required       Smoke  barrier:  See  780  CMR  702.0. 

for  ordinary  repairs. 

Smoke  compartment:  See  780  CMR  702.0.. 

Smoke  detector,  multiple  station:  See  780  CMR 

902.0. 

Smoke  detector,  single  station:  See  780  CMR 

902.0. 


Required:  Shall  be  construed  to  be  mandatory  by 
provisions  of  780  CMR. 

Resilient  stable-mounting  system:  See  780  CMR 

1612.3. 


Restraining  device:  See  780  CMR  1612.3. 
Elastic:  See  780  CMR  1612.3. 
Fixed:  See  780  CMR  1612.3 
Seismic  activated:  See  780  CMR  1612.3 


2/7/97    (Effective  2/28/97) 


Smokeproof  enclosure:  See  780  CMR  1002  0. 
Specialized  code:     All  building  codes,   rules  or 

780  CMR  -  Sixth  Edition  43 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  416.2. 

HPM  cutoff  room:  See  780  CMR  416.2. 

HPM  inside  room:  See  780  CMR  416.2. 


regulations  pertaining  to  building  construction, 

reconstruction,  alteration,  repair  or  demolition 

promulgated  by  and  under  the  authority  of  the 

various  agencies  which  have  been  authorized 

from  time  to  time  by  the  General  Court  of  the       Story:  See  780  CMR  502.0 

Commonwealth  of  Massachusetts. 


Sprinkler:  See  780  CMR  902.0 

Sprinkler  system,  automatic:  See  780  CMR  902.0. 

Sprinkler  system,  limited   area:   See  780  CMR 

902.0. 

Stack  bond:  See  780  CMR  2102.0. 
Stage:  See  780  CMR  412.2. 
Stage,  legitimate:  See  780  CMR  412.2. 
Stage,  regular:  See  780  CMR  412.2. 
Stage,  thrust:  See  780  CMR  412.2. 
Stairway:  See  780  CMR  1002.0. 
Standpipe  system:  See  780  CMR  902.0. 


Story  above  grade:  See  780  CMR  502.0. 

Story  drift  ratio:  See  780  CMR  1612.3. 

Story  shear:  See  780  CMR  1612.3. 

Street:  A  public  thoroughfare  (such  as  a  street, 
avenue  or  boulevard)  which  has  been  dedicated 
for  public  use. 

Structure:  That  which  is  built  or  constructed  or  a 
portion  thereof. 

Structure,  existing:  A  structure  erected  prior  to  the 
date  of  adoption  of  the  appropriate  code  or  one  for 
which  a  legal  building  permit  has  been  issued. 
See  780  CMR  34  for  further  information 
regarding  existing  buildings. 

Supervisory  device:  See  780  CMR  902.0. 

Through-penetration    protection    system:     See 

780  CMR  702.0. 


State  Building  Code:  The  State  Building  Code  and 
amendments  and  rules  and  regulations  thereto 

as  promulgated  by  the  State  Board  of  Building       Tie,  wall:  See  780  CMR  2102.0. 
Regulations  and  Standards,  under  M.G.L.  c.  143 
§§  93  through  100.  Tile:  See  780  CMR  2102.0. 

State  Inspector:   An  employee  of  the  Division  of  Tile,  structural  clay:  See  780  CMR  2102.0. 
Inspection,  State  Department  of  Public  Safety, 

who    is    charged    with    administrating    and  Tires,  bulk  storage  of:  See  780  CMR  307.2. 
enforcing  780  CMR  relative  to  any  structure  or 

building  or  parts  thereof  that  are  owned  by  the  Travel  Trailer:     A  vehicular,  portable  structure 
Commonwealth        or        any        departments,  built  on  a  chassis  and  designed  to  be  used  for 


commissions,  agencies  or  authorities  of  the 
Commonwealth,  The  state  inspector  is  also 
charged  with  supervising  the  enforcement  of 
780  CMR  relative  to  all  buildings  and  structures 
other  than  those  owned  by  the  Commonwealtlu 
See  also  780  CMR  107.0. 

Steel  construction,  cold-formed:  See  780  CMR 

2202.0. 

Steel  joist:  See  780  CMR  2202.0. 

Steel  member,  structural:  See  780  CMR  2202.0. 

Stone  masonry:  See  780  CMR  2102.0. 

Stone  masonry,  ashlar:  See  780  CMR  2102.0. 

Stone  masonry,  rubble:  See  780  CMR  2102.0. 

Storage     room,     HPM,    separate     inside:     See 

44 


temporary  occupancy  for  travel,  recreational  or 
vocational  use;  with  the  manufacturer's 
permanent  identification  "Travel  Trailer," 
thereon;  and  when  factory  equipped  for  the 
road,  being  of  any  length  provided  its  gross 
weight  does  not  exceed  4500  pounds,  or  being  of 
any  weight  provided  its  overall  length  does  not 
exceed  28  feet 

Use  group:  The  classification  of  an  occupancy  in 
accordance  with  780  CMR  302.1. 

Vapor  retarder:  See  780  CMR  1202.0. 

Ventilation:  See  780  CMR  1202.0. 

Vertical  opening:  See  780  CMR  702.0. 

Voice/alarm    signaling   system:    See   780   CMR 

902.0. 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0:    CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

DEFINITIONS 


Wall 

Apron  wall:  See  780  CMR  1402.0. 

Cavity  wall:  See  780  CMR  2102.0. 

Composite  wall:  See  780  CMR  2102.0. 

Dry-stacked,      surface-bonded      walls:       See 

780  CMR  2102.0. 

Faced  wall:  See  780  CMR  2102.0. 

Fire  separation  wall:  See  780  CMR  702.0 

Fire  wall:  See  780  CMR  702.0. 

Foundation  wall   See  780  CMR  1812.2. 

Hollow  wall:  See  780  CMR  2102.0 

Loadbearing  wall   See  780  CMR  1602.1. 

Nonloadbearing  wall:  See  780  CMR  1602.1. 

Parapet  wall:  See  780  CMR  2102.0. 

Party  wall:  See  780  CMR  702.0. 

Retaining  wall:  See  7S0  CMR  1812  2 

Skeleton  or  panel  wall:  See  780  CMR  1402 .0. 

Spandrel  wall:  See  780  CMR  1402.0. 

Veneered  Wall:  See  780  CMR  1402.0 

Water-reactive  materials:  See  780  CMR  307.2 

Water  supply,  automatic:  See  780  CMR  902.0 

Winder:  See  780  CMR  1002.0. 


Wood  shear  panel:  See  7S0  CMR  2304.2. 

Writing  (written):  The  term  shall  be  construed  to 
include  hand-writing,  typewriting,  printing,  photo 
offset  or  any  other  form  of  reproduction  in  legible 
svmbols  or  characters. 


Written  notice:  A  notification  in  ivriting  delivered 
in  person  to  the  individual  or  parties  intended; 
or  delivered  at.  or  sent  by  certified  or  registered 
mail  to  the  last  residential  or  business  address  of 
legal  record 

Wythe:  See  780  CMR  2102.0. 

Yard:  See  7S0  CMR  1202.0. 

Zoning:  The  reservation  of  certain  specified  areas 
within  a  community  or  city  for  buildings  and 
structures,  or  use  of  land,  for  certain  purposes 
with  other  limitations  such  as  height,  lot  coverage 
and  other  stipulated  requirements.  (See  M.G.L. 
c.  40A  and  St.  1956,  c.  665,  as  amended.) 


2/7/97    (Effective  2/28/97) 


780  CMR -Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 
NON-TEXT  PAGE 


46  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  3 


USE  OR  OCCUPANCY 


780  CMR  301.0  GENERAL 

301.1  Scope:  The  provisions  of  780  CMR  3  shall 
control  the  classification  of  all  buildings  and 
structures  as  to  use  group. 

301.2  Application  of  other  laws:  The  provisions  of 
780  CMR  3  shall  not  be  deemed  to  nullify  any 
provisions  of  the  zoning  law,  ordinance  of  any 
municipality  in  the  Commonwealth  of 
Massachusetts,  or  any  other  statute  of  the 
jurisdiction  pertaining  to  the  location  or  occupancy 
of  buildings,  except  as  is  specifically  required  by  the 
provisions  of  780  CMR. 

780  CMR  302.0  CIASSTJICATTON 
302.1  General:  All  structures  shall  be  classified 
with  respect  to  occupancy  in  one  or  more  of  the  use 
groups  listed  below.  Where  a  structure  is  proposed 
for  a  purpose  which  is  not  specifically  provided  for 
in  780  CMR,  such  structure  shall  be  classified  in  the 
use  group  which  the  occupancy  most  nearly 
resembles 


comply  with  780  CMR  302. 1 . 1 . 

Table  302.1.1 
SPECIFIC  OCCUPANCY  AREAS 


1.  Assembly: 

(see  780  CMR  303.0) 

2.  Business: 

(see  780  CMR  304.0) 

3.  Educational: 

(see  780  CMR  305.0) 

4.  Factory  and  Industrial 

(see  780  CMR  306.0) 

5.  High  Hazard 

(see  780  CMR  307.0): 

6.  Institutional: 

(see  780  CMR  308.0) 

7.  Mercantile: 

(see  780  CMR  309.0) 

8.  Residential: 

(see  780  CMR  3 10.0) 

9.  Storage: 

(see  780  CMR  3 11.0) 
10.  Utility  and  Miscellane- 
ous (see  780  CMR  312.0) 


Use   Groups   A-l, 
A-3,  A-4  and  A-5 
Use  Group  B 


A-2. 


Use  Group  E 

Use  Groups  F-l  and  F-2 

Use   Groups    H-l.   H-2. 

H-3  and  H-4 

Use  Groups  1-1,  1-2  and 

1-3 

Use  Group  M 

Use  Groups  R-l.  R-2.  R- 

3,  R-4and.R-5 

Use  Groups  S-l  and  S-2 

Use  Group  U 


302.1.1  Specific  occupancy  areas:  Specific 
occupancy  areas  which  are  incidental  to  the  mam 
use  group  shall  be  separated  and  protected  in 
accordance  with  Table  302.1.1  and  shall  be 
classified  in  accordance  with  the  main  use  group 
of  the  portion  of  the  building  in  which  the  specific 
occupancy  area  is  iocated.  Where  the  building,  or 
portion  thereof,  containing  the  specific  occupancy 
area  is  required  to  be  protected  with  an  automatic 
fire  suppression  system,  the  separation  alternative 
of  Table  302.1.1  shall  not  apply. 

Exception:    Specific   occupancy   areas  within 
and  serving  a  dwelling  unit  are  not  reauired  to 


Room  or  area 


Separation  /protection 


All  use  groups: 

Paint  shops  in  occupancies  oth- 
er than  Use  Group  F  employ- 
ing hazardous  materials  in 
quantmes  less  than  those  which 
cause  classification  as  Use 
Group  H 

Waste  and  soiled  linen  collec- 
tion rooms  and  chute  term- 
ination rooms 
Waste  and  soiled  linen  chute 

access  rooms 
Boiler  and  furnacerooms  i 

Incinerator  rooms 


Use  Groups  A.  B.  E.  I- 1 .  R- 1 . 
R-2 

Storage  rooms  more  than  50 
square  feet  in  area  but  not 
more  than  1 00  square  feet  in 
area 
Storage  rooms  more  than 
1 00  square  feet  in  area 

Physical  plant  maintenance 
shop  and  workshop 


Use  Groups  1-2,1-3: 

Boiler  and  furnace  rooms 
Handicraft  shops,  kitchens, 
and  employee  locker  rooms 

Laundries  greater  than  1 00 

square  feet  in  area 
Storage  rooms  more  man  50 

square  feet  in  area  but  not 

morethan  100  square  feet  in 

area 
Storage  rooms  more  than  1 00 

square  feet  in  area 
Physical  plant  maintenance 

shop  and  workshop 
Use  Group  1-2: 

Gift/retail  shops  and  laborator- 
ies employing  hazardous 
quantities  less  than  those  which 
cause  classification  as  Use 
Group  H 

use  Group  1-3  padded  cells 


2  hours:  or  1  hour  and 
automatic  fire  sup- 
pression system 


1  hour  and  automatic  fire 
suppression  system 

1  hour 

1  hour,  or  automatic  fire 

suppression  system 

2  hours  and  automatic  fire 

suppression  system 

1  hour,  or  automatic  fire 
suppression  system 
with  smoke  partitions 


Automatic  fire  suppres- 
sion system  with  smoke 
partitions 
2  hours,  or  1  hour  and  au- 
tomatic fire  suppression 
system 

1  hour  and  automatic  fire 
suppression  system 

1  hour,  or  automatic  fire 
suppression  system  with 
smoke  partitions 

1  hour  and  automatic  fire 
suppression  system 

Automatic  fire  suppres- 
sion system  with  smoke 
partitions 

1  hour  and  automatic  fire 
suppression  system 

1  hour  and  automatic  fire 
suppression  system 

1  hour:  or  automatic  fire 
suppression  system  with 
smoke  Dartitions 


hour  and  automatic  fire 
.vstem 


Note   a.    For   requirements    for   fireresistance   rated 
separations  and  smoke  Dartitions  se;  780  CMR  302  ! . ! . : 
Note  b.  1  sauare  foot  =  0.093  rr,~. 


9/19/97  (Effective  2/28/97;  -  corrected    780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


302.1.1.1  Separation:  Where  Table  302.1.1 
requires  a  fireresistance  rated  separation,  the 
specific  occupancy  area  shall  be  separated  from 
the  remainder  of  the  building  with  fire 
separation  assemblies  (see  780  CMR  709.0). 
Where  Table  302.1. 1  requires  smoke  partitions, 
the  smoke  partitions  shall  be  constructed  of 
materials  consistent  with  the  type  of 
construction  and  shall  be  capable  of  resisting 
the  passage  of  smoke.  The  smoke  partitions 
shall  extend  from  the  floor  to  the  underside  of 
the  fireresistance  rated  floor/ceiling  or 
roof/ceiling  assembly  or  to  the  underside  of  the 
floor  or  roof  deck  above  All  doors  shall  be  self- 
closing  or  automatic-closing  upon  detection  of 
smoke. 

302.1.2  Accessory  areas:  Except  for  accessory 

areas   of  Use   Group   H   in   accordance   with 

780  CMR  302. 1 .2. 1  and  specific  occupancy  areas 

indicated  in  780  CMR  302.1.1,  where  the  area 

devoted  to  an  accessory  occupancy  does  not 

occupy  more  than  10%  of  any  fire  area  nor  more 

than   10%  of  the  allowable  area  permitted  by 

780  CMR  503.0  based  on  the  accessory  use  group, 

afire  separation  assembly  shall  not  be  required 

between  the  main  use  group  and  accessory  areas 

The    required    type    of   construction    and    the 

automatic    fire    suppression       requirements    in 

780  CMR  904.0  shall  be  based  on  the  main  use 

group  of  the  fire  area. 

302.1.2.1  High-hazard  uses:  In  buildings  that 

are  three  stories  or  less  in  height  and  equipped 

throughout  with  an  automatic  sprinkler  system 

in    accordance    with    780    CMR    904,    an 

occupancy  in  Use  Group  F  or  S  is  permitted  to 

have  accessory  areas  of  Use  Group  H-2,  H-3  or 

H-4,  provided  that  such  areas  do  not  occupy 

more  than  10%  of  any  fire  area  nor  more  than 

10%    of  the    allowable    area   permitted    by 

780  CMR  503.0  based  on  the  use  group  of  the 

accessory  area.  Afire  separation  assembly  shall 

not  be  required  between  the  F  or  S  use  group 

and  the  accessory  H  use  group.  The  maximum 

quantity   of  hazardous  materials  within  the 

accessory  H  use  group  shall  not  exceed  twice 

the  permitted  exempt  amount  specified  in  Table 

307.8(1)  or  Table  307.8(2).  The  required  type  of 

construction  shall  be  based  on  the  main  use 

group  of  the  fire  area. 

302.2  Mixed  use:  All  buildings  and  structures  that 
include  more  than  one  use  group  shall  be  further 
designated  as  a  mixed  use  and  shall  comply  with 
780  CMR  313.0  Specific  occupancy  areas  and 
accessory  areas  complying  with  780  CMR  302.1.1 
and  302.1.2,  respectively,  shall  be  classified  in 
accordance  with  the  main  use  group. 


780  CMR  303.0  ASSEMBLY  USE 
GROUPS 

303.1  General:  All  structures  which  are  designed  or 
occupied  for  the  gathering  together  of  persons  for 
purposes  such  as  civic,  social  or  religious  functions, 
recreation,  food  or  drink  consumption  or  awaiting 
transportation,  shall  be  classified  as  Use  Group  A-l, 
A-2,  A-3,  A-4  or  A-5.  A  room  or  space  used  for 
assembly  purposes  by  less  than  50  persons  and 
which  is  accessory  to  another  use  group  shall  be 
included  as  a  part  of  that  main  use  group  The  term 
"Use  Group  A"  shall  include  Use  Groups  A-l,  A-2, 
A-3,  A-4  and  A-5. 

303.2  Use  Group  A-l,  theaters:  This  use  group 
shall  include  all  theaters  and  all  other  buildings  and 
structures  intended  for  the  production  and  viewing 
of  performing  arts  or  motion  pictures;  and  which  are 
usually  provided  with  fixed  seats-including  theaters, 
motion  picture  theaters  and  television  and  radio 
studios  admitting  an  audience  Stages  and  platforms 
shall  comply  with  780  CMR  412.0. 

303.3  Use  Group  A-2  structures:  This  use  group 
shall  include  all  buildings  and  places  of  public 
assembly,  without  theatrical  stage  accessories, 
designed  for  occupancy  as  dance  halls,  nightclubs 
and  for  similar  purposes,  including  all  rooms, 
lobbies  and  other  spaces  connected  thereto  with  a 
common  means  of  egress  and  entrance. 

303.4  Use  Group  A-3  structures:  This  use  group 
shall  include  all  buildings  with  or  without  an 
auditorium  in  which  persons  assemble  for 
amusement,  entertainment  or  recreation  purposes  as 
well  as  incidental  motion  picture,  dramatic  or 
theatrical  presentations,  lectures  or  other  similar 
purposes  without  theatrical  stage  other  than  a  raised 
platform:  and  which  are  principally  occupied 
without  permanent  seating  facilities,  including  art 
galleries,  exhibition  halls,  museums,  lecture  halls, 
libraries,  restaurants  other  than  nightclubs,  and 
recreation  centers;  and  buildings  designed  for 
similar  assembly  purposes,  including  passenger 
terminals. 

303.5  Use  Group  A-4  structures:  This  use  group 
shall  include  all  buildings  and  structures  which  are 
occupied  exclusively  for  the  purpose  of  worship  or 
other  religious  services. 

303.6  Use  Group  A-5,  outdoor  assembly:  This  use 
group  shall  include  structures  utilized  for  outdoor 
assembly  intended  for  participation  in  or  reviewing 
activities,  including  grandstands  (780  CMR  1013.0), 
bleachers  (780  CMR  1013.0),  coliseums,  stadiums, 
amusement  park  structures  (780  CMR  413.0)  and 
fair  or  carnival  structures.  Such  structures  shall 
comply  with  all  pertinent  provisions  of  780  CMR. 


48 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 


780  CMR  304.0  BUSINESS  USE  GROUP 

304.1  General:  All  buildings  and  structures  which 
are  occupied  for  the  transaction  of  business,  for  the 
rendering  of  professional  services,  or  for  other 
services  that  involve  stocks  of  goods,  wares  or 
merchandise  in  limited  quantities  which  are 
incidental  to  office  occupancies  or  sample  purposes, 
shall  be  classified  as  Use  Group  B. 

304.2  List     of     business     occupancies:     The 

occupancies  listed  in  Table  304.2  are  indicative  of 
and  shall  be  classified  as  Use  Group  B. 

Table  304.2 
BUSINESS  OCCUPANCIES 


Airport  traffic  control 

towers 

Animal  hospitals,  kennels, 

pounds 
Automobile  and  other 
motor     vehicle  showrooms 
Banks 

Barber  shops 
Beauty  shops 
Car  wash 

Civic  administration 
Clinic,  outpatient 
Dry-cleaning;  pickup  and 

delivery  stations  and 

self-service 
Electronic  data  processing 


Fire  stations 
Florists  and  nurseries 
Laboratories;  testing  and 

research 
Laundries;  pickup  and 

delivery  stations  and 

self-service 
Police  stations 
Post  offices 
Print  shops 

Professional  services;  attor- 
ney, dentist,  physician, 

engineer,  etc. 
Radio  and  television 

stations 
Telecommunications 

equipment  building 


780  CMR  305.0  EDUCATIONAL  USE 
GROUP 

305.1  General.  All  structures  other  than  those 
occupied  for  business  training  or  vocational  training, 
which  accommodate  more  than  five  persons  for 
educational  purposes  through  the  12th  grade,  shall 
be  classified  as  Use  Group  E. 

Exception:  A  room  or  space  occupied  for 
educational  purposes  by  less  than  50  persons,  five 
years  of  age  or  more,  and  which  is  accessory  to 
another  use  group  shall  be  classified  as  a  part  of 
the  main  use  group. 

305.1.1  Day  care  facilities:  A  child  day  care 
center  which  provides  care  for  children  more 
than  two  years  nine  months  shall  be  classified  as 
use  Group  E. 

305.2  Business  or  vocational  training:  Structures 
occupied  for  business  training  or  vocational  training 
shall  be  classified  in  the  same  use  group  as  the 
business  or  vocation  taught. 

780  CMR  306.0  FACTORY  AND 
INDUSTRIAL  USE  GROUPS 

306.1  General:  All  structures  in  which  occupants 
are  engaged  in  work  or  labor  in  the  fabricating, 
assembling  or  processing  of  products  or  materials, 
shall  be  classified  as  Use  Group  F-l  or  F-2.  This 
includes,  among  others,  factories,  assembling  plants, 
industrial  laboratories  and  all  other  industrial  and 


manufacturing  occupancies.  The  term  "Use  Group 
F"  shall  include  Use  Groups  F-l  and  F-2. 

306.2  Use  Group  F-l  structures:  Factory  and 
industrial  occupancies  which  are  not  otherwise 
classified  as  low-hazard,  Use  Group  F-2,  shall  be 
classified  as  a  moderate-hazard  factory  and 
industrial  occupancy,  Use  Group  F-l.  The 
manufacturing  processes  listed  in  Table  306.2  are 
indicative  of  and  shall  be  classified  as  Use  Group  F- 
1. 

Table  306.2 

MODERATE-HAZARD  FACTORY  AND 

INDUSTRIAL  OCCUPANCDZS 


Aircraft 

Appliances 

Athletic  equipment 

Automobiles  and  other  motor 
vehjcles 

Bakeries 

Beverages,  alcoholic 

Bicycles 

Boat  building 

Boiler  works 

Brooms  or  brushes 

Business  machines 

Cameras  and  photo  equipment 

Canneries,  including  food 
products 

Clothing 

Condensed  and  powdered 
milk  manufacture 

Construction  and  agricultural 
machinery 

Disinfectants 

Dry  cleaning  using  other  than 
flammable  liquids  in  clean- 
ing or  dyeing  operations  or 
other  than  classified  in  780 
CMR  307.0 

Electric  light  plants  and 

power    houses 

Electrolytic  reducing  works 

Electronics 

Engines,  including  rebuilding 


Film,  photographic 

Food  processing 

Furniture 

Hemp  and  jute  products 

Laundries 

Leather  and  tanneries,  ex- 
cluding enameling  or 
japanning 

Machinery 

Millwork  and  woodworking, 
wood  distillation 

Motion  picture  and  television 
filming 

Musical  instruments 

Optical  goods 

Paper  mills  or  products 

Plastic  products 

Printing  or  publishing 

Recreational  vehicles 

Refuse  incinerators 

Shoes 

Soaps  and  detergents 

Sugar  refineries 

Textile  mills,  including 
canvas,  cotton,  cloth, 
bagging,  burlap,  carpets 
and  rags 

Tobacco 

Trailers 

Upholstery  and  manufacturing 
shops 


306.3  Use  Group  F-2  structures:  Factory  and 
industrial  occupancies  which  involve  the  fabrication 
or  manufacturing  of  noncombustible  materials  that, 
during  finishing,  packing  or  processing,  do  not 
contribute  to  a  significant  fire  hazard,  shall  be 
classified  as  Use  Group  F-2.  The  manufacturing 
processes  listed  in  Table  306.3  are  indicative  of  and 
shall  be  classified  as  Use  Group  F-2. 

Table  306.3 

LOW-HAZARD  FACTORY  AND 

INDUSTRIAL  OCCUPANCIES 


Beverages,  nonalcoholic 
Bnck  and  masonry 
Ceramic  products 
Foundries 

Glass  products 


Gvpsum 

Ice 

Metal  fabrication  and 

assembly 
Water  pumping  plants 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  307.0  HIGH-HAZARD  USE 
GROUPS 

307.1  General:  All  structures  which  are  occupied 
for  the  manufacturing,  processing,  generation, 
storage  or  other  use  of  hazardous  materials  in 
excess  of  the  exempt  quantities  specified  in 
780  CMR  307.8  shall  be  classified  as  Use  Group  H- 
1,  H-2,  H-3  or  H-4  in  accordance  with  the  hazards 
presented  by  each  material  as  described  in  780  CMR 
307.3  through  307.6.  The  term  "Use  Group  H"  shall 
include  Use  Groups  H-l,  H-2,  H-3  and  H-4. 

307.1.1  Information  required:  Separate  floor 
plans  shall  be  submitted  for  buildings  and 
structures  with  an  occupancy  in  Use  Group  H 
identifying  the  locations  of  anticipated  contents 
and  processes  so  as  to  reflect  the  nature  of  each 
occupied  portion  of  every  building  and  structure 
A  report  identifying  all  hazardous  materials 
including,  but  not  limited  to,  materials  of  Use 
Group  H  to  be  stored  or  utilized,  shall  be 
submitted  and  the  methods  of  protection  from 
such  hazards  shall  be  indicated  on  the 
construction  documents. 

307.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Aerosol:  A  product  that  is  dispensed  from  an 
aerosol  container  by  a  propellant. 

Aerosol  container:  Metal  cans,  glass  or  plastic 
bottles  designed  to  dispense  an  aerosol.  Metal 
cans  shall  be  limited  to  a  maximum  size  of  33.8 
fluid  ounces  (1000  ml).  Glass  or  plastic  bottles 
shall  be  limited  to  a  maximum  size  of  four  fluid 
ounces  (118  ml). 

Barricade:  A  structure  that  consists  of  a 
combination  of  walls,  floor  and  roof,  which  is 
designed  to  withstand  the  rapid  release  of  energy 
in  an  explosion  and  which  is  fully  confined, 
partially  vented  or  fully  vented;  or  other  effective 
method  of  shielding  from  explosive  materials  by 
a  natural  or  artificial  barrier. 

Boiling  point:  The  temperature  at  which  the  vapor 
pressure  of  a  liquid  equals  the  atmospheric 
pressure  of  14.7  pounds  per  square  inch  (psia)  or 
760  mm  of  mercury.  Where  an  accurate  boiling 
point  is  unavailable  for  the  material  in  question, 
or  for  mixtures  which  do  not  have  a  constant 
boiling  point,  for  the  purposes  of  this 
classification,  the  10%  of  a  distillation  performed 
in  accordance  with  ASTM  D86  listed  in 
Appendix  A  shall  be  used  as  the  boiling  point  of 
the  liquid. 

Closed    system:    The   use   of  a   solid   or  liquid 


hazardous  material  in  a  closed  vessel  or  system 
that  remains  closed  during  normal  operations 
where  vapors  emitted  by  the  product  are  not 
liberated  outside  of  the  vessel  or  system  and  the 
product  is  not  exposed  to  the  atmosphere  during 
normal  operations;  and  all  uses  of  compressed 
gases.  Examples  of  closed  systems  for  solids  and 
liquids  include  product  conveyed  through  a  piping 
system  into  a  closed  vessel,  system  or  piece  of 
equipment. 

Combustible  dusts:  Dusts  and  any  similar  solid 
material  sufficiently  comminuted  for  suspension 
in  still  air  which,  when  so  suspended,  is  capable 
of  self-sustained  combustion. 

Combustible  fibers:  Includes  readily  ignitable  and 
free-burning  fibers  such  as  cotton,  sisal, 
henequen,  jute,  hemp,  tow,  cocoa  fiber,  oakum, 
baled  waste,  baled  wastepaper.  kapok,  hay,  straw, 
excelsior,  Spanish  moss  and  other  like  material. 

Combustible  liquids:  Any  liquids  having  a  flash 
point  at  or  above  100°F  (38°C)  shall  be  known  as 
Class  II  or  EI  liquids.  Combustible  liquids  shall 
be  divided  into  the  following  classifications: 

Class  II:  Liquids  having  flash  points  at  or  above 
100°F  (38°C)  and  below  140°F  (60°C). 

Class  ITJA:  Liquids  ha\\ng  flash  points  at  or  above 
140°F  (60°C)  and  below  200°F  (93°C). 

Class  niB:  Liquids  having  flash  points  at  or  above 
200°F(93°C). 

Compressed  gas:  A  gas  or  mixture  of  gases  as 
contained  having  an  absolute  pressure  exceeding 
40  psi  at  70 °F  (276  kPa  at  21  °C)  or,  regardless  of 
the  pressure  at  70°F  (21  °C),  having  an  absolute 
pressure  exceeding  140  psi  at  130°F  (965  kPa  at 
54  °C);  or  any  liquid  material  having  a  vapor 
pressure  exceeding  40  psi  absolute  at  100°F  (276 
kPa  at  38°C)  as  determined  by  ASTM  D323  listed 
in  Appendix  A 

Control  area:  Spaces  within  a  building  which  are 
enclosed  and  bounded  by  exterior  walls,  fire 
walls,  fire  separation  assemblies  and  roofs,  or  a 
combination  thereof,  where  quantities  of 
hazardous  materials  not  exceeding  the  exempt 
amounts  are  stored,  dispensed,  used  or  handled. 

Corrosive:  A  chemical  that  causes  visible 
destruction  of,  or  irreversible  alterations  in,  living 
tissue  at  the  point  of  contact.  A  chemical  shall  be 
considered  a  corrosive  if,  when  tested  on  the 
intact  skin  of  albino  rabbits  by  the  test  method 
described  by  DOTn  49  CFR,  Part  173  listed  in 
Appendix  A,  such  chemical  destroys  or  changes 
irreversibly  the  structure  of  the  tissue  at  the  point 


50 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 


of  contact  following  an  exposure  period  of  four 
hours.  This  term  shall  not  refer  to  action  on 
inanimate  surface. 

Cryogenic  liquids  (flammable  or  oxidizing):  Any 

liquid  that  has  a  boiling  point  below  -200  °F 
(-129°C). 

Deflagration:  An  exothermic  reaction,  such  as  the 
extremely  rapid  oxidation  of a  flammable  dust  or 
vapor  in  air,  in  which  the  reaction  progresses 
through  the  unburned  material  at  a  rate  less  than 
the  velocity  of  sound.  A  deflagration  can  have  an 
explosive  effect. 

Detached  storage  building:  A  separate  single-story 
building,  without  a  basement  or  crawl  space,  used 
for  the  storage  of  hazardous  materials  and  located 
an  approved  distance  from  all  structures. 

Detonation:  An  exothermic  reaction  characterized 
by  the  presence  of  a  shock  wave  in  the  material 
which  establishes  and  maintains  the  reaction.  The 
reaction  zone  progresses  through  the  material  at  a 
rate  greater  than  the  velocity  of  sound.  The 
principal  heating  mechanism  is  one  of  shock 
compression,  detonations  have  an  explosive 
effect. 

Dispensing:  The  pouring  or  transferring  of  any 
material  from  a  container,  tank  or  similar  vessel, 
whereby  vapors,  dusts,  fumes,  mists  or  gases  are 
liberated  to  the  atmosphere. 

Explosive:  Any  chemical  compound,  mixture  or 
device,  the  primary  or  common  purpose  of  which 
is  to  function  by  explosion.  The  term  includes,  but 
is  not  limited  to,  dynamite,  black  powder,  pellet 
powder,  initiating  explosives,  detonators,  safety 
fuses,  squibs,  detonating  cord,  igniter  cord  and 
igniters. 

The  term  "explosive"  includes  any  material 
determined  to  be  within  the  scope  of  USC  Title 
18;  Chapter  40  listed  in  Appendix  A  and  also 
includes  any  material  classified  as  an  explosive  by 
the  Hazardous  Material  Regulations  of  DOTn  49 
CFR  listed  in  Appendix  A. 

Flammable:  Capable  of  being  readily  ignited  from 
common  sources  of  heat  or  at  a  temperature  of 
600°F(316°C)orless. 

Flammable  compressed-gas:  Either  a  mixture  of 
13%  or  less  (by  volume)  with  air  forms  a 
flammable  mixture,  or  the  flammable  range  with 
air  is  wider  than  12%,  regardless  of  the  lower 
limitation.  These  limitations  shall  be  determined 
at  atmospheric  temperature  and  pressure. 

Flammable  liquids  Any  liquid  that  has  a.  flash  point 
below  I00°F  (38°C),  and  has  a  vapor  pressure  not 


exceeding  40  psia  (276  kPa)  at  100°F  (38°C). 

Flammable  liquids  shall  be  known  as  Class  I 

liquids  and  shall  be  divided  into  the  following 

classifications: 

Class  IA:  Liquids  having  a  flashpoint  below  73  °F 

(23  °C)  and  having  a  boiling  point  below  100°F 

(38°C). 

Class  IB:   Liquids  having  a  flash  point  below 

73  °F  (23  °C)  and  having  a  boiling  point  at  or 

above  100°F.  (38°C). 

Class  IC:  Liquids  having  a.  flash  point  at  or  above 

73 °F  (23 °C)  and  below  100°F  (38  °C). 

Flammable  solid:  A  solid,  other  than  a  blasting 
agent  or  explosive,  that  is  capable  of  causing  fire 
through  friction,  absorption  of  moisture, 
spontaneous  chemical  change,  or  retained  heat 
from  manufacturing  or  processing,  or  which  has 
an  ignition  temperature  below  212°F  (  100°C)  or 
which  burns  so  vigorously  and  persistently  when 
ignited  as  to  create  a  serious  hazard.  A  chemical 
shall  be  considered  a  flammable  solid  as 
determined  in  accordance  with  the  test  method  of 
CPSC  16  CFR;  Part  1500.44  listed  in 
Appendix  A,  if  it  ignites  and  bums  with  a  self- 
sustained  flame  at  a  rate  greater  than  0. 1  inch  (3 
mm)  per  second  along  its  major  axis. 

Flash  point:  The  minimum  temperature  in  degrees 
Fahrenheit  at  which  a  flammable  liquid  will  give 
off  sufficient  vapors  to  form  an  ignitable  mixture 
with  air  near  the  surface  or  in  the  container,  but 
will  not  sustain  combustion.  The  flash  point  of  a 
liquid  shall  be  determined  by  appropriate  test 
procedure  and  apparatus  as  specified  in  ASTM 
D56  and  ASTM  D93  listed  in  Appendix  A. 

Hazardous  materials:  Those  chemicals  or 
substances  which  are  physical  hazards  or  health 
hazards  as  defined  and  classified  in  780  CMR  3 
and  the  fire  prevention  code  listed  in  Appendix  A, 
whether  the  materials  are  in  usable  or  waste 
condition. 

Health  hazard:  A  classification  of  a  chemical  for 
which  there  is  statistically  significant  evidence 
that  acute  or  chronic  health  effects  are  capable  of 
occurring  in  exposed  persons.  The  term  "health 
hazard"  includes  chemicals  which  are 
carcinogens,  toxic  or  highly  toxic  agents, 
reproductive  toxins,  irritants,  corrosives, 
sensitizers,  hepatotoxins,  nephrotoxins, 

neurotoxins,  agents  which  are  capable  of  acting 
on  the  hematopoietic  system,  and  agents  which 
damage  the  lungs,  skin,  eyes  or  mucous 
membranes. 

Highly  toxic:  A  chemical  falling  within  any  of  the 
following  categories  is  considered  highly  toxic 
1    A   chemical   that   has  a   median   lethal   dose 
(LD!0)  of  50  milligrams  or  less  per  kilogram  of 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixtn  Edition 


51 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


body  weight  when  administered  orally  to 
albino  rats  weighing  between  200  and  300 
grams  each. 

2.  A  chemical  that  has  a  median  lethal  dose 
(LDS0)  of  200  milligrams  or  less  per  kilogram 
of  body  weight  when  administered  by 
continuous  contact  for  24  hours  (or  less  if 
death  occurs  within  24  hours)  with  the  bare 
skin  of  albino  rabbits  weighing  between  two 
and  three  kilograms  each. 

3.  A  chemical  that  has  a  median  lethal 
concentration  (LC50)  in  air  of  200  parts  per 
million  by  volume  or  less  of  gas  or  vapor,  or 
two  milligrams  per  liter  or  less  of  mist,  fume  or 
dust,  when  administered  by  continuous 
inhalation  for  one  hour  (or  less  if  death  occurs 
within  one  hour)  to  albino  rats  weighing 
between  200  and  300  grams  each. 

Incompatible  materials:  Materials  which,  when 
mixed,  have  the  potential  to  react  in  a  manner  that 
generates  heat,  fumes,  gases  or  by-products  which 
are  hazardous  to  life  or  property. 

Irritant:  A  chemical,  which  is  not  corrosive,  but 
which  causes  a  reversible  inflammatory  effect  on 
living  tissue  by  chemical  action  at  the  point  of 
contact.  A  chemical  shall  be  considered  an  irritant 
if,  when  tested  on  the  intact  skin  of  albino  rabbits 
by  the  test  method  of  CPSC  16  CFR  Part  1500.41 
listed  in  Appendix  A  for  four  hours  exposure,  it 
results  in  an  empirical  score  of  five  or  more.  A 
chemical  is  an  eye  irritant  if  so  determined  by  the 
procedure  in  CPSC  16  CFR;  Part  1500.42  listed  in 
Appendix  A. 

Open  system:  The  use  of  a  solid  or  liquid  hazardous 
material  in  a  vessel  or  system  that  is  continuously 
open  to  the  atmosphere  during  normal  operations 
and  where  vapors  are  liberated,  or  the  product  is 
exposed  to  the  atmosphere  during  normal 
operations.  Examples  of  open  systems  for  solids 
and  liquids  include  dispensing  from  or  into  open 
beakers  or  containers,  dip  tank  and  plating  tank 
operations. 

Organic  peroxide:  An  organic  compound  that 
contains  the  bivalent  double-bonded  oxygen 
structure  and  which  is  considered  to  be  a 
structural  derivative  of  hydrogen  peroxide  where 
one  or  both  of  the  hydrogen  atoms  have  been 
replaced  by  an  organic  radical. 

Unclassified  detonable:  Organic  peroxides  which 
are  capable  of  detonation.  These  peroxides 
present  an  extremely  high  explosion  hazard 
through  rapid  explosive  decomposition. 
Class  I:  Class  I  organic  peroxides  are  capable  of 
deflagration,  but  not  detonation.  These  peroxides 
present  a  high  explosion  hazard  through  rapid 
decomposition. 


Class  II:  Class  II  organic  peroxides  burn  very 
rapidly  and  present  a  severe  reactivity  hazard. 
Class  EH:  Class  III  organic  peroxides  burn  rapidly 
and  present  a  moderate  reactivity  hazard. 

Oxidizer:  A  chemical  other  than  a  blasting  agent  or 
explosive  that  initiates  or  promotes  combustion  in 
other  materials,  thereby  causing  fire  either  of 
itself  or  through  the  release  of  oxygen  or  other 
gases. 

Class  4:  An  oxidizer  that  can  undergo  an 
explosive  reaction  due  to  contamination  or 
exposure  to  thermal  or  physical  shock. 
Additionally,  the  oxidizer  will  enhance  the 
burning  rate  and  is  capable  of  causing 
spontaneous  ignition  of  combustibles. 
Class  3:  An  oxidizer  that  will  cause  a  severe 
increase  in  the  burning  rate  of  combustible 
materials  with  which  the  oxidizer  comes  in 
contact  or  that  will  undergo  vigorous  self- 
sustained  decomposition  due  to  contamination  or 
exposure  to  heat. 

Class  2:  An  oxidizer  that  will  cause  a  moderate 
increase  in  the  burning  rate  or  that  is  capable  of 
causing  spontaneous  ignition  of  combustible 
materials  with  which  the  oxidizer  comes  in 
contact. 

Class  1:  An  oxidizer  whose  primary  hazard  is  a 
slight  increase  in  the  burning  rate  but  which  does 
not  cause  spontaneous  ignition  when  the  oxidizer 
comes  in  contact  with  combustible  material. 

Physical  hazard:  A  chemical  for  which  there  is 
evidence  in  the  referenced  standards  listed  in 
Appendix  A  that  it  is  a  combustible  liquid, 
compressed  gas,  cryogenic,  explosive,  flammable 
gas,  flammable  liquid,  flammable  solid,  organic 
peroxide,  oxidizer,  pyrophoric  or  unstable 
(reactive)  or  water-reactive  material. 

Pyrophoric:  A  material  that  will  spontaneously 
ignite  in  air  at  or  below  a  temperature  of  130°F 
(54°C). 

Radioactive  material:  Any  material  or  combination 
of  material  that  spontaneously  emits  ionizing 
radiation. 

Sensitizer:  A  chemical  that  causes  a  substantial 
proportion  of  exposed  people  or  animals  to 
develop  an  allergic  reaction  in  normal  tissue  after 
repeated  exposure  to  the  chemical. 

Tires,  bulk  storage  of:  Storage  of  10,000  or  more 
average-sized  passenger  vehicle  tires  weighing 
approximately  25  pounds  (11  kg)  each  (see 
780  CMR  307.5). 

Toxic:  A  chemical  that  is  within  any  of  the  following 
categories  shall  be  considered  toxic: 
1.   A  chemical  that  has  a  median  lethal  dose 


52 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 


(LD50)  of  more  than  50  milligrams  per 
kilogram  but  not  more  than  500  milligrams  per 
kilogram  of  body  weight  when  administered 
orally  to  albino  rats  weighing  between  200  and 
300  grams  each. 

2.  A  chemical  that  has  a  median  lethal  dose 
(LD50)  of  more  than  200  milligrams  per 
kilogram  but  not  more  than  1,000  milligrams 
per  kilogram  of  body  weight  when 
administered  by  continuous  contact  for  24 
hours  (or  less  if  death  occurs  within  24  hours) 
with  the  bare  skin  of  albino  rabbits  weighing 
between  two  and  three  kilograms  each. 

3.  A  chemical  that  has  a  median  lethal 
concentration  (LC50)  in  air  of  more  than  200 
parts  per  million  but  not  more  than  2,000  parts 
per  million  by  volume  of  gas  or  vapor,  or  more 
than  two  milligrams  per  liter  but  not  more  than 
20  milligrams  per  liter  of  mist,  fume  or  dust, 
when  administered  by  continuous  inhalation 
for  one  hour  (or  less  if  death  occurs  within  I 
hour)  to  albino  rats  weighing  between  200  and 
300  grams  each. 

Unstable  (reactive)  material:  A  material  which,  in 
the  pure  state  or  as  commercially  produced,  will 
vigorously  polymerize,  decompose  or  condense, 
become  self-reactive,  or  otherwise  undergo  a 
violent  chemical  change  under  conditions  of 
shock,  pressure  or  temperature. 
Class  4:  Materials  that  in  themselves  are  readily 
capable  of  detonation  or  explosive  decomposition 
or  explosive  reaction  at  normal  temperatures  and 
pressures.  This  class  includes,  among  others, 
materials  that  are  sensitive  to  localized  thermal  or 
mechanical  shock  at  normal  temperatures  and 
pressures. 

Class  3:  Materials  that  in  themselves  are  capable 
of  detonation  or  explosive  decomposition  or 
explosive  reaction,  but  that  require  a  strong 
initiating  source  or  that  must  be  heated  under 
confinement  before  initiation.  This  class  includes, 
among  others,  materials  that  are  sensitive  to 
thermal  or  mechanical  shock  at  elevated 
temperatures  and  pressures. 
Class  2:  Materials  that  readily  undergo  violent 
chemical  change  at  elevated  temperatures  and 
pressures.  This  class  includes,  among  others, 
materials  that  exhibit  an  exotherm  at  temperatures 
less  than  or  equal  to  150°C  when  tested  by 
differential  scanning  calorimetry. 
Class  1:  Materials  that  in  themselves  are  normally 
stable,  but  that  can  become  unstable  at  elevated 
temperatures  and  pressures.  This  class  includes, 
among  others,  materials  that  change  or  decompose 
on  exposure  to  air,  light  or  moisture,  and  materials 
that  exhibit  an  exotherm  at  temperatures  greater 
than  150°C,  but  less  than  or  equal  to  300°C, 
when  tested  by  differential  scanning  calorimetry. 

Water-reactive  materials:  A  chemical  that  reacts 


with   water    to    release    a   gas    that    is    either 
flammable  or  presents  a  health  hazard. 
Class  3:  Materials  which  react  explosively  with 
water  without  requiring  heat  or  confinement. 
Class  2:  Materials  which  are  capable  of  forming 
potentially  explosive  mixtures  with  water. 

307.3  Use  Group  H-l  structures:  All  buildings  and 
structures  which  contain  materials  that  present  a 
detonation  hazard,  shall  be  classified  as  Use  Group 
H-  1.  Such  materials  shall  include  but  are  not  limited 
to: 

Explosives 

Organic  Peroxides,  unclassified  detonable 

Oxidizers,  Class  4 

Unstable  (reactive)  materials.  Class  3  detonable, 

and  Class  4 

Detonable  pyrophoric  materials 

307.4  Use  Group  H-2  structures:  All  buildings  and 
structures  which  contain  materials  that  present  a 
deflagration  hazard  or  a  hazard  from  accelerated 
burning,  shall  be  classified  as  Use  Group  H-2.  Such 
materials  shall  include  but  are  not  limited  to: 

Combustible  dusts 

Combustible  liquids,  Class  II  and  Class  IIIA 

Cryogenic  liquids,  flammable  or  oxidizing 

Flammable  gases 

Flammable  liquids 

Organic  peroxides,  Class  I  and  Class  II 

Oxidizers,  Class  3 

Oxidizing  gases 

Pyrophoric       liquids,       solids       and       gases, 

nondetonable 

Unstable      (reactive)      materials,      Class      3, 

nondetonable 

307.5  Use  Group  H-3  structures:  All  buildings  and 
structures  which  contain  materials  that  readily 
support  combustion  or  present  a  physical  hazard, 
shall  be  classified  as  Use  Group  H-3.  Such  materials 
shall  include  but  are  not  limited  to: 

Aerosols,  except  that  Level  1  aerosols  defined  in 

the  fire  prevention  code  listed  in  Appendix  A  shall 

be  classified  as  Use  Group  S- 1  or  F- 1 

Combustible  fibers 

Combustible  liquids.  Class  IIEB 

Flammable  solids 

Organic  peroxides,  Class  III 

Oxidizers,  Class  1  and  Class  2 

Tires,  bulk  storage  of 

Unstable  (reactive)  materials.  Class  1  and  Class  2 

Water-reactive  materials.  Class  2  and  Class  3 

307.6  Use  Group  H-4  structures:  All  buildings  and 
structures  which  contain  materials  that  are  health 
hazards,  shall  be  classified  as  Use  Group  H-4.  Such 
materials  shall  include  but  are  not  limited  to: 

Corrosives 

Highly  toxic  materials 

Irritants 


111  191    (Effective  2/28/97-) 


780  CMR  -  Sixth  Edition 


53 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Radioactive  materials 

Sensitizers 

Toxic  materials 

307.7  Multiple  hazards:  All  buildings  and 
structures  containing  a  material  or  materials 
representing  hazards  that  are  classified  in  one  or 
more  of  Use  Groups  H-l,  H-2,  H-3  and  H-4,  shall 
conform  to  the  code  requirements  for  each  of  the  use 
groups  so  classified. 

307.8  Exceptions:  The  following  shall  not  be 
classified  in  Use  Group  H,  but  shall  be  classified  in 
the  use  group  which  they  most  nearly  resemble. 
High-hazard  materials  of  any  quantity  shall  conform 
to  the  requirements  of  780  CMR,  including 
780  CMR  417.0,  and  the  fire  prevention  code  listed 
in  Appendix  A. 

1.  All  buildings  and  structures  which  contain 
not  more  than  the  exempt  quantities  of  high- 
hazard  materials  as  shown  in  Tables  307  .8(1) 
and  307.8(2)  provided  that  such  buildings  are 
maintained  in  accordance  with  the  fire 
prevention  code  listed  in  Appendix  A. 

2.  Buildings  utilizing  control  areas  in 
accordance  with  780  CMR  417.2  which 
contain  not  more  than  the  exempt  quantities 
of  high-hazard  materials  as  shown  in  Tables 
307.8(1)  and  307.8(2). 

3.  Buildings  and  structures  occupied  for  the 
storage  of  10,000  or  more  vehicle  tires 
weighing  approximately  25  pounds  (11  kg) 
each,  provided  that  such  buildings  are 
equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with 
780  CMR  906.2.1. 

4.  Buildings  and  structures  occupied  for  the 
application  of  flammable  finishes,  provided 
that  such  buildings  or  areas  conform  to  the 
requirements  of  780  CMR  419.0  and  NFiPA 
33,  NFiPA  34  and  the  fire  prevention  code 
listed  in  Appendix  A. 

5.  Rooms  containing  flammable  liquids  in 
tightly  closed  containers  of  1 -gallon  capacity 
(0.0038  m)  or  less  for  retail  sale  or  private 
utilization  on  the  premises  and  in  quantities 
not  exceeding  two  gallons  per  square  foot 
(0.082  mVm2 )  of  room  area. 

6.  Retail  paint  salesrooms  with  quantities  of 
paint  not  exceeding  two-gallons  per  square 
foot  (0.082  nrVm2)  of  room  area. 

7.  Closed  systems  housing  flammable  or 
combustible  liquids  or  gases  utilized  for  the 
operation  of  machinery  or  equipment. 

8.  Cleaning  establishments  which  utilize 
combustible  liquid  solvents  having  a  flash 
point  of  140°F  (60°C)  or  higher  in  closed 
systems  employing  equipment  listed  by  an 
approved  testing  agency,  provided  that  this 
occupancy  is  separated  from  all  other  areas  of 
the  building  by  one-hour  fireresistance  rated 


fire  separation  assemblies. 
9      Cleaning    establishments    which    utilize    a 
liquid  solvent  having  a  flash  point  at  or  above 
200°F(93°C). 

10.  Liquor  stores  and  distributors  without  bulk 
storage. 

1 1 .  Refrigeration  systems. 

12.  The  storage  or  utilization  of  materials  for 
agricultural  purposes  on  the  premises. 

13.  Stationary  batteries  utilized  for  facility 
emergency  power,  uninterrupted  power 
supply  or  telecommunication  facilities 
provided  that  the  batteries  are  provided  with 
safety  venting  caps  and  ventilation  is 
provided  in  accordance  with  the  mechanical 
code  listed  in  Appendix  A. 

14.  Corrosives,  irritants  and  sensitizers  shall  not 
include  personal  or  household  products  in 
their  original  packaging  used  in  retail  display 
or  commonly  used  building  materials. 

15.  Buildings  and  structures  occupied  for  aerosol 
manufacturing  or  storage  shall  be  classified 
as  Use  Group  F-l  or  S-l,  provided  that  such 
buildings  conform  to  the  requirements  of 
NFiPA  30  and  the  fire  prevention  code  listed 
in  Appendix  A. 

780  CMR  308.0  INSTITUTIONAL  USE 
GROUPS 

308.1  General:  All  structures  in  which  people 
suffering  from  physical  limitations  because  of  health 
or  age  are  harbored  for  medical  or  other  care  or 
treatment,  or  in  which  people  are  detained  for  penal 
or  correction  purposes,  or  in  which  the  liberty  of  the 
inmates  is  restricted,  shall  be  classified  as  Use 
Group  1-1, 1-2  or  1-3.  The  term  "Use  Group  I"  shall 
include  Use  Groups  1-1, 1-2  and  1-3. 

308.2  Use  Group  1-1:  Except  as  modified  by  the 
provisions  of  780  CMR  4,  Special  Use  and 
Occupancy,  this  use  group  shall  include  buildings 
and  structures  which  house  six  or  more  individuals 
who,  because  of  age,  mental  disability  or  other 
reasons,  must  live  in  a  supervised  environment  but 
who  are  physically  capable  of  responding  to  an 
emergency  situation  without  personal  assistance. 
Except  as  specified  otherwise  by  the  requirements 
of  780  CMR  4,  Special  Use  and  Occupancy,  where 
accommodating  persons  of  the  above  description, 
the  following  types  of  facilities  shall  be  classified  as 
1-1  facilities,  board  and  care  facilities,  half-way 
houses,  group  homes,  social  rehabilitation  facilities, 
alcohol  and  drug  centers  and  convalescent  facilities. 
A  facility  such  as  the  above  with  five  or  less 
occupants  shall  be  classified  as  a  residential  use 
group. 

308.3  Use  Group  1-2:  This  use  group  shall  include 
buildings  and  structures  used  for  medical,  surgical, 
psychiatric,  nursing  or  custodial  care  on  a  24-hour 
basis  of  six  or  more  persons  who  are  not  capable  of 


54 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 


self-preservation.  Where  accommodating  persons  of 
the  above  description,  the  following  types  of 
facilities  shall  be  classified  as  1-2  facilities: 
hospitals,  nursing  homes  (both  intermediate  care 
facilities  and  skilled  nursing  facilities),  mental 
hospitals  and  detoxification  facilities.  A  facility  such 
as  the  above  with  five  or  less  occupants  shall  be 
classified  as  a  residential  use  group. 

308.3.1  Child  care  facility:  A  child  day  care 
center  which  accommodates  children  two  years 
nine  months  of  age  or  less  shall  be  classified  as 
Use  Group  1-2. 

308.4  Use  Group  1-3:  This  use  group  shall  include 
buildings  and  structures  which  are  inhabited  by  six 
or  more  persons  who  are  under  some  restraint  or 
security.  An  1-3  facility  is  occupied  by  persons  who 
are  generally  incapable  of  self-preservation  due  to 
security  measures  not  under  the  occupants'  control. 
Where  accommodating  persons  of  the  above 
description,  the  following  types  of  facilities  shall  be 
classified  as  1-3  facilities:  prisons,  jails, 
reformatories,  detention  centers,  correctional  centers 
and  prerelease  centers.  Buildings  of  Use  Group  1-3 
shall  be  classified  as  one  of  the  occupancy 
conditions  indicated  in  780  CMR  308.4.1  through 


308.4.5  (see  780  CMR  410.0). 

308.4.1  Occupancy  Condition  I:  This  occupancy 
condition  shall  include  all  buildings  in  which  free 
movement  is  allowed  from  sleeping  areas,  and 
other  spaces  where  access  or  occupancy  is 
permitted,  to  the  exterior  via  means  of  egress 
without  restraint.  An  Occupancy  Condition  I 
facility  shall  be  classified  as  Use  Group  R. 

308.4.2  Occupancy  Condition  II:  This 
occupancy  condition  shall  include  all  buildings  in 
which  free  movement  is  allowed  from  sleeping 
areas  and  any  other  occupied  smoke  compartment 
to  one  or  more  other  smoke  compartments.  Egress 
to  the  exterior  is  impeded  by  locked  exits 

308.4.3  Occupancy  Condition  HI:  This 
occupancy  condition  shall  include  all  buildings  in 
which  free  movement  is  allowed  within  individual 
smoke  compartments,  such  as  within  a  residential 
unit  comprised  of  individual  sleeping  rooms  and 
group  activity  spaces,  where  egress  is  impeded  by 
remote-controlled  release  of means  of  egress  from 
such  smoke  compartment  to  another  smoke 
compartment 


211191    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


55 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  307.8(1) 

EXEMPT  AMOUNTS  OF  HAZARDOUS  MATERIALS,  LIQUIDS 

AND  CHEMICALS  PRESENTING  A  PHYSICAL  HAZARD 

MAXIMUM  QUANTITIES  PER  CONTROL  AREA3 


Class 

Use 
Groups 

Storage 

Closed  systems 

Open  systems 

Material 

solid 
pounds 
(cubic 

feet) 

liquid 
gallons 
(pounds) 

gas 
(Cubic 
feet) 

Solid 
pounds 
(cubic 
feet) 

Liquid 
gallons 
(pounds) 

Gas  cubic 
feet 

Solid 

pounds 

(cubic 

feet) 

liquid 
gallons 
(pounds) 

Combustible 
liquid 

II 
IHA 

mB 

H-2 
H-2 
H-3 

NA 

120d'e 
330d'% 
13,200e' 

NA 

NA 

120d 
330d 
13,200 

NA 

NA 

30d 

80    f 

3,300 

Conbustible 
dust  pounds 
per  1,00  feet 

H-2 

I8 

NA 

NA 

lg 

NA 

NA 

lg 

NA 

Combustible 
fiber 

loose 
Baled 

H-3 

(100) 
(1,000) 

NA 

NA 

(100) 
(1,000) 

NA 

NA 

(20) 
(200) 

NA 

Cryogenics, 
flammible  or 
oxidizing 

H-2 

NA 

45d 

NA 

NA 

45d 

NA 

NA 

iod 

Explosives 

H-l 

.eji.i 

(De-h>1 

NA 

%h 

('/4)h 

NA 

fch 

(%)h 

Flammable 
gas 

Gaseous 
Liquified 

H-2 

NA 

NA 
30& 

i.oood,e 

NA 

NA 

^ 

de 
750  ' 

NA 

NA 

NA 

Flammible 
liquid 

IA 
IB 
IC 

H-2 

NA 

30f 

60f 
90d-e 

NA 

NA 

NA 

NA 

10d 

15d 
20d 

Combination 
(IA  IB,  IC) 

H-2 

NA 

120d-e'j 

NA 

NA 

120d° 

NA 

NA 

30dj 

Flammible 
solid 

H-2 

d,e 
125  ' 

NA 

NA 

25d 

NA 

NA 

25d 

NA 

Organic 
peroxide 

UD 
I 

n 
in 

H-l 
H-2 
H-3 
H-3 

^e 

50 : 

d  e 
125  ' 

< 

at 

(125) 

NA 

k 

125d 

<*4 

(50)  d 
(125) 

NA 

25d 

('/4).h 
^\ 

(io)d 

(25) 

Oxidizer 

4 
3 
2 
1 

H-l 
H-2 
H-3 
H-3 

iod:e 

250df 

i,oood-e 

<e 

(10)d,e 

<250>de 
(1,000)  ' 

NA 

i. 

250°. 
1.000° 

<2>d 

(250) 
(1,000) 

NA 

i 

< 

200 

(50) 

(200) 

Oxidizer  - 
gas 

Gaseous 
Liquified 

H-2 

NA 

NA 
15& 

d,e 
1,500  ' 

NA 

NA 

NA 
(15?'e 

d,e 

1,500  ' 

NA 

NA 

NA 

Pyrophoric 

H-2 

4e* 

(4)ei 

so6* 

lh 

(Dh 

ioeJl 

0 

0 

Unstable 
(reactive) 

4 
3 

2 
1 

H-l 
H-l  or 
H-2 
H-3 
H-3 

5d,e 

de 
50  : 

1254e 

K 

d,e 
(125)d'e 

lof 

50^e 

250de 
750d'e 

la 

(Dd 

(50)d 
(125) 

2? 
d,e 

10  ' 

250d'e 
750d'e 

(I)' 

(io)df 

(25) 

Water 
reactive 

3     - 
2 

H-3 
H-3 

5dd6 
50d'e 

d,e 

NA 

$ 

«dd 

NA 

,■; 

^ 

Note  a.  For  use  of  control  areas,  see  780  CMR  417.2 

Note  b.  The  aggregate  quantity  in  utilization  and  storage  shall  not  exceed  the  quantity  listed  for  storage. 

Note  c.  The  quantities  of  alcoholic  beverages  in  retail  sales  occupancies  shall  not  be  limited  provided  the  liquids 
are  packaged  in  individual  containers  not  exceeding  1  gallon.  In  retail  sales  and  storage  occupancies,  the  quantities 
of  medicines,  foodstuffs  and  cosmetics,  containing  not  more  than  50%  by  volume  of  water-miscible  liquids  and  with 
the  remainder  of  the  solutions  not  being  flammable,  shall  not  be  limited  provided  that  such  materials  are  packaged  in 
individual  containers  not  exceeding  one  gallon. 

Note  d.  Maximum  quantities  shall  be  increased  100%  in  buildings  equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1.  Where  note  e.  Also  applies,  the  increase  for  both  notes  shall  be  applied 
accumulatively. 

Note  e.  Quantities  shall  be  increased  100%  when  stored  in  approved  cabinets,  gas  cabinets,  fume  hoods,  exhausted 
enclosures,  or  safety  cans  as  specified  in  the  fire  prevention  code  listed  in  Appendix  A.  Where  note  d.  also  applies,  the 
increase  for  both  notes  shall  be  applied  accumulatively. 


56 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 

Note  f.  The  permitted  quantities  shall  not  be  limited  in  a  building  equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2. 1 . 

Note  g.  A  dust  explosion  potential  is  considered  to  exist  where  1  pound  or  more  of  combustible  dust  per  1.000  cubic 
feet  of  volume  is  normally  in  suspension  or  could  be  put  into  suspension  in  all  or  a  portion  of  an  enclosure  or  inside 
pieces  of  equipment.  This  also  includes  combustible  dust  which  accumulates  on  horizontal  surface  inside  buildings 
or  equipment  and  which  could  be  put  into  suspension  be  an  accident,  sudden  force  or  sudden  explosion. 

Note  h.  Permitted  only  in  buildings  equipped  throughout  with  an  automatic  sprinkler  svstem  in  accordance  with 
780  CMR  906.2.1. 

Note  i.  One  pound  of  black  sporting  powder  and  20  pounds  of  smokeless  powder  are  permitted  in  sprinklered  or 
unsprinklered  buildings. 

Note  j.  Containing  not  more  than  the  exempt  amounts  of  Class  I-A,  Class  1-B  or  Class  I-C  flammable  liquids 

Note  k.  Quantities  in  parenthesis  indicate  quantity  units  in  parenthesis  at  the  head  of  each  column.  1  cubic  foot  = 
0.028  m3;  1  pound  =  0.454  kg;  1  gallon  =  0.00379  mS 

Table  307.8(2) 

EXEMPT  AMOUNTS  OF  HAZARDOUS  MATERIALS,  LIQUIDS  AND  CHEMICALS 

PRESENTING  A  HEALTH  HAZARD 

MAXIMUM  QUANTmES  PER  CONTROL  AREA^*1 


Storage 

Closed  systems 

Open  systems 

Material 

Solidde 
pounds 

Liquid 

gallons 

(pounds) 

Gas  cubic 
feet 

Solid 
pounds 

Liquid 

gallons 

(pounds) 

Gas  cubic 
feet 

Solid 
pounds 

Liquid 

gallons 

(pounds) 

Corrosive 

5,000 

500 

810dx 

5,000 

500 

810d-e 

1,000 

100 

Highly  toxic 

1 

(1) 

20f 

! 

(1) 

20f 

V* 

(%) 

Irritant 

5,000 

500 

810d-e 

5,000 

500 

810d-c 

1,000 

100 

Radioactive8 

25  rem  -  unsealed  source 
100  rem  -  sealed  source 

1 00  rem  -  sealed  source 

25  rem  -  sealed  source 

Sensitizer 

5,000 

500 

810d-e 

5,000 

500 

810dx 

1,000 

100 

Toxic 

500 

(500) 

810de 

500 

(500) 

810d-e 

125 

(125) 

Other  health 
hazards 

5,000 

500 

810d'e 

5,000 

500 

810d'e 

1.000 

100 

Note  a.  For  use  of  control  areas,  see  780  CMR  4 1 7.2 

Note  b.  In  retail  sales  occupancies,  the  quantities  of  medicines,  foodstuffs  and  cosmetics,  containing  not  more  than 
50%  by  volume  of  water-miscible  liquids  and  with  the  remainder  of  the  solutions  not  being  flammable,  shall  not  be 
limited  provided  that  such  materials  are  packaged  in  individual  containers  not  exceeding  i  gallon 

Note  c  The  aggregate  quantity  in  utilization  and  storage  shall  not  exceed  the  quantity  listed  for  storage. 

Note  d.  Maximum  quantities  shall  be  increased  100%  in  buildings  equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2. 1.  Where  note  e.  also  applies,  the  increase  for  both  notes  shall  be  applied 
accumulatively. 

Note  e.  Maximum  quantities  shall  be  increased  100%  when  stored  in  approved  storage  cabinets,  gas  cabinets,  fume 
hoods,  exhausted  enclosures,  or  safety  cans  as  specified  in  the  fire  prevention  code  listed  in  Appendix  A  Where  note 
d.  also  applies,  the  increase  for  both  notes  shall  be  applies  accumulatively 

Note  f.  Permitted  only  when  stored  in  approved  exhausted  gas  cabinets,  exhausted  enclosures  or  fume  hoods 

Note  g.  Maximum  dosage  permitted  in  any  single  exposure. 

Note  h.  Quantities  in  parenthesis  indicate  quantity  units  in  parenthesis  at  the  head  of  each  column  1  cubic  foot  = 
0.028  m3;  1  pound  =  0.454  kg;  1  gallon  =  0.00379  m3 


308.4.4  Occupancy  Condition  IV:  This 
occupancy  condition  shall  include  all  buildings  in 
which  free  movement  is  restricted  from  an 
occupied  space.  Remote-controlled  release  is 
provided  to  permit  movement  from  all  sleeping 
rooms,  activity  spaces  and  other  occupied  areas 
within  the  smoke  compartment  to  other  smoke 
compartments. 

308.4.5  Occupancy  Condition  V:  This 
occupancy  condition  shall  include  all  buildings  in 
which  free  movement  is  restricted  from  an 
occupied  space.  Staff-controlled  release  is 
provided  to  permit  movement  from  all  sleeping 
rooms,  activity  spaces  and  other  occupied  areas 


within  the  smoke  compartment  to  other  smoke 
compartments. 

780  CMR  309.0  MERCANTILE  USE 
GROUP 

309.1  General:  All  buildings  and  structures  which 
are  occupied  for  display  and  sales  purposes 
involving  stocks  of  goods,  wares  or  merchandise 
incidental  to  such  purposes  and  open  to  the  public, 
shall  be  classified  as  Use  Group  M.  This  includes, 
among  others,  retail  stores,  automotive  service 
stations,  shops,  salesrooms  and  markets  An 
automotive  service  station  is  that  portion  of  a 
property  where  motor  fuels  are  stored  and  dispensed 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


57 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


from  fixed  equipment  into  the  fuel  tanks  of  motor 
vehicles  or  approved  containers,  including  any 
building  used  for  the  sale  of  automotive  accessories, 
or  for  minor  automotive  repair  work.  Minor  repairs 
include  the  exchange  of  parts,  oil  changes,  engine 
tune-ups  and  similar  routine  maintenance  work. 
Retail  sales  of  hazardous  materials  shall  comply 
with  780  CMR  307.8  or  780  CMR  426,  as 
applicable. 

780  CMR  310.0  RESIDENTIAL  USE 
GROUPS 

310.1  General:  All  structures  in  which  individuals 
live,  or  in  which  sleeping  accommodations  are 
provided  (with  or  without  dining  facilities), 
excluding  those  that  are  classified  as  institutional 
occupancies,  shall  be  classified  as  Use  Group  R-l, 
R-2,  R-3,  R-4  or  R-5  The  term  "Use  Group  R"  shall 
include  Use  Groups  R-l,  R-2  and  R-3.  R-4  and  R-5. 

Note:  Assisted  Living  Residences  which  are 
certified  as  such  by  the  Executive  Office  of  Elder 
Affairs  pursuant  to  M.G.L.  c.  19D  shall  be 
classified  in  the  residential  use  group  R-l,  R-2, 
R-3  or  R-4  as  applicable.  Portions  of  an  assisted 
Living  Residence  which  are  used  for  any  use 
other  than  residential  shall  be  classified  in 
accordance  with  the  intended  use 

310.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Dwellings: 
Assisted  Living  Residence:  A  residence  licensed 
by  the  Executive  Office  of  Elder  Affairs  pursuant 
toMG.L.  c  19D. 

Boarding  house:  A  building  arranged  or  used  for 
lodging  for  compensation,  with  or  without  meals, 
and  not  occupied  as  a  single  unit. 
Dormitory:  A  space  in  a  building  where  group 
sleeping  accommodations  are  provided  in  one 
room,  or  in  a  series  of  closely  associated  rooms. 
Dwelling  unit:  A  single  unit  providing  complete, 
independent   living   facilities   for  one  or  more 
persons,    including    permanent    provisions    for 
living,  sleeping,  eating,  cooking  and  sanitation. 
Hotel:  Any  building  containing  six  or  more  guest 
rooms,  intended  or  designed  to  be  used,  or  which 
are  used,  rented  or  hired  out  to  be  occupied  or 
which  are  occupied  for  sleeping  purposes  by 
guests. 

Motel:  A  hotel  as  defined  in  780  CMR. 
Multiple  dwelling:  A  building  or  portion  thereof 
containing  more  than  two  dwelling  units  and  not 
meeting  the  requirements  for  a  multiple  single 
dwelling. 

Multiple  single  dwelling:  A  building  or  portion 
thereof  containing  more  than  two  dwelling  units 
(see  780  CMR  310.5) 


One-family  dwelling:  A  building  containing  one 

dwelling  unit  with  not  more  than  five  lodgers  or 

boarders. 

Two-family  dwelling:  A  building  containing  two 

dwelling  units  with  not  more  than  five  lodgers  or 

boarders  per  family. 

310.3  Use  Group  R-l  structures:  This  use  group 
shall  include  all  hotels,  motels,  boarding  houses  and 
similar  buildings  arranged  for  shelter  and  sleeping 
accommodations  and  in  which  the  occupants  are 
primarily  transient  in  nature,  occupying  the  facilities 
for  a  period  of  less  than  30  days. 

310.4  Use  Group  R-2  structures:  This  use  group 
shall  include  all  multiple  dwellings  having  more  than 
two  dwelling  units,  except  as  provided  for  in 
780  CMR  310.5  for  multiple  single  dwelling  units, 
and  shall  also  include  all  boarding  houses  and 
similar  buildings  arranged  for  shelter  and  sleeping 
accommodations  in  which  the  occupants  are 
primarily  not  transient  in  nature. 

310.4.1  Dormitories:  A  dormitory  facility  which 
accommodates  more  than  five  persons  more  than 
2'/2  years  of  age  shall  be  classified  as  Use  Group 
R-2 

310.5  Use  Group  R-3  structures:  This  use  group 
shall  include  all  buildings  arranged  for  occupancy  as 
one-  or  two-family  dwelling  units,  including  not 
more  than  five  lodgers  or  boarders  per  family  and 
multiple  single-family  dwellings  where  each  unit  has 
an  independent  means  of  egress  and  is  separated  by 
a  two-hour  fire  separation  assembly  (see  780  CMR 
709.0). 

Exceptions 

1.  In  multiple  single-family  dwellings  that  are 
equipped  throughout  with  an  approved 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1  or 
906.2.2,  the  fireresistance  rating  of  the 
dwelling  unit  separation  shall  not  be  less  than 
one  hour.  Dwelling  unit  separation  walls 
shall  be  constructed  as  fire  partitions  (see 
780  CMR  71 1.0). 

2  In  multiple  single-family  dwellings  that  are 
equipped  throughout  with  an  approved 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.3,  a  two- 
hour  fire  separation  assembly  shall  be 
provided  between  each  pair  of  dwelling  units. 
The  fireresistance  rating  between  each 
dwelling  unit  shall  not  be  less  than  one  hour 
and  shall  be  constructed  as  afire  partition. 

310.5.1Famify  day-care  home:  A  family  day- 
care home  as  defined  by  M.G.L.  C.28A,  §.  9,  shall 
be  classified  as  use  group  R-3  or  R-4.  Such 
facility  shall  not  accommodate  more  than  six 
children. 


58 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 


310.6  Use  Group  R-4  structures  This  use  group 
shall  include  all  detached  one-  or  two-family 
dwellings  not  more  than  three  stories  in  height,  and 
the  accessory  structures..  All  such  structures  shall 
be  designed  in  accordance  with  780  CMR  36  or  in 
accordance  with  the  requirements  of  780  CMR 
applicable  to  Use  Group  R-3. 

310. 7  Use  Group  R-5  structures:  This  use  group 
shall  include  all  buildings  arranged  for  use  as 
limited  group  residences  in  accordance  with  the 
requirements  of  780  CMR  (see  780  CMR  4). 

780  CMR  311.0  STORAGE  USE  GROUPS 

311.1  General:  All  structures  which  are  primarily 
used  for  the  storage  of  goods,  wares  or  merchandise 
shall  be  classified  as  Use  Group  S-l  or  S-2.  This 
includes,  among  others,  warehouses,  storehouses  and 
freight  depots  The  quantity  of  hazardous  materials 
in  storage  shall  comply  with  780  CMR  307.8.  The 
term  "Use  Group  S"  shall  include  Use  Groups  S-l 
and  S-2. 

311.2  Moderate-hazard  storage,  Use  Group  S-l: 

Buildings  occupied  for  the  storage  of  moderate- 
hazard  contents  which  are  likely  to  burn  with 
moderate  rapidity,  but  which  do  not  produce  either 
poisonous  gases,  fumes  or  explosives  including, 
among  others,  the  materials  listed  in  Table  311.2, 
shall  be  classified  as  Use  Group  S-l.  A  motor 
vehicle  repair  garage  is  that  portion  of  a  property 
wherein  major  repairs,  such  as  engine  overhauls, 
painting  or  body  work,  are  performed  on  motorized 
vehicles. 

Table  311.2 

MODERATE-HAZARD  STORAGE 

OCCUPANCIES 


Bags,  cloth,  burlap  and  paper 

Bamboo  and  rattan 

Baskets 

Belting,  canvas  and  leather 

Books  and  papers  in  rolls  and 

packs 
Boots  and  shoes 
Buttons,  including  cloth 

covered,  pearl  or  bone 
Cardboard  and  cardboard 

boxes 
Clothing,  woolen  wearing 


Linoleum 

Livestock  shelters 

Lumber  yards 

Motor  vehicle  repair  garages 

Petroleum  warehouses  for 

storage  of  lubricating  oils 

with  a  flash  point  of  200°  F 

or  higher 
Photo  engraving 
Public  garages  (Group  1 )  and 

stables 
Silk 


Cordage  Sugar 

Furniture  Tobacco,  cigars,  cigarettes 

Furs  and  snuff 

Glue,  mucilage,  paste  and  size  Upholstering  and  mattress 

Hom  and  combs,  other  than       manufacturing 

celluloid  Wax  candles 

Leather,  enameling  or 

japanning   

311.3  Low-hazard  storage,  Use  Group  S-2:  Low- 
hazard  storage  occupancies  shall  include  buildings 
occupied  for  the  storage  of  noncombustible 
materials,  and  of  low-hazard  wares  that  do  not 


ordinarily  burn  rapidly  such  as  products  on  wood 
pallets  or  in  paper  cartons  without  significant 
amounts  of  combustible  wrappings,  but  with  a 
negligible  amount  of  plastic  trim  such  as  knobs, 
handles  or  film  wrapping.  Such  occupancies  shall  be 
classified  as  Use  Group  S-2  including,  among 
others,  the  materials  listed  in  Table  31 1.3. 

Table  311.3 
LOW-HAZARD  STORAGE  OCCUPANCIES 


Asbestos 

Beer  or  wine  up  to  1 2% 

alcohol  m  metal,  glass  or 

ceramic  containers 
Cement  in  bags 
Chalk  and  crayons 
Dairy  products  in  nonwaxed 

coated  paper  containers 
Dry  cell  batteries 
Electrical  coils 
Electrical  motors 
Food  products 
Foods  in  noncombustible 

containers 
Fresh  fruits  and  vegetables  in 

nonplasnc  trays  or 

containers 
Frozen  foods 
Glass 
Glass  bottles,  empty  or  filled 

with  noncombustible 

liquids 


Gypsum  board 

Inert  pigments 

Ivory 

Meats 

Metal  cabinets 

Metal  desks  with  plastic  tops 

and  trim 
Metal  parts 
Metals 
Mirrors 

New  empty  cans 
Oil  filled  and  other  types  of 

distribution  transformers 
Open  parking  structures 
Porcelain  and  pottery 
Public  garages  (Group  2) 
Stoves 

Talc  and  soapstone 
Washers  and  drvers 


780  CMR  312.0  UnLITY  AND 
MISCELLANEOUS  USE  GROUP 
312.1  General:  Buildings  and  structures  of  an 
accessory  character  and  miscellaneous  structures  not 
classified  in  any  specific  use  group  shall  be 
constructed,  equipped  and  maintained  to  conform  to 
the  requirements  of  780  CMR  commensurate  with 
the  fire  and  life  hazard  incidental  to  their  occupancy 
Use  Group  U  shall  include  fences  over  six  feet  (1 829 
mm)  high,  tanks,  cooling  towers,  retaining  walls  and 
buildings  such  as  private  garages,  carports,  sheds 
and  agricultural  buildings. 

780  CMR  313.0  MIXED  USE  GROUPS 
313.1  Two  or  more  use  groups:  Where  a  building 
is  occupied  by  two  or  more  occupancies  not  included 
in  the  same  use  group,  the  building  or  portion 
thereof  shall  comply  with  780  CMR  3 13. 1.1,  313.1.2 
or  313.1.3  or  with  combinations  of  780  CMR 
313.1.1,  313.1.2  and  313.1.3,  except  that 
occupancies  in  Use  Group  H  shall  be  separated  from 
all  other  use  groups  in  accordance  with  780  CMR 
313.1.2  or  313.1.3.  Buildings  that  include  an  open 
parking  structure  located  beneath  an  A  I,  B,  M  or  R 
Use  Group  shall  comply  with  780  CMR  313.1  1, 
313.1.2,313.1.3  or313.2. 
Exception  :fire  areas  of  Use  Group  H-l  shall  be 
in  separate  and  detached  buildings  and  structures 
in  accordance  with  780  CMR  707. 1.1. 

313.1.1  Nonseparated  use  groups:  Each  portion 
of  the  building  shall  be  individually  classified  as 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


59 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


to  use.  The  required  type  of  construction  for  the 
building  shall  be  determined  by  applying  the 
height  and  area  limitations  for  each  of  the 
applicable  use  groups  to  the  entire  building.  The 
most  restrictive  type  of  construction,  so 
determined,  shall  apply.  The  other  requirements 
of  780  CMR  shall  apply  to  each  portion  of  the 
building  based  on  the  use  group  of  that  occupancy 
except  that  the  most  restrictive  applicable 
provisions  of  780  CMR  403.0  and  780  CMR  9 
shall  apply  to  these  nonseparated  use  groups.  A 
fire  separation  assembly  is  not  required  between 
use  groups,  except  as  required  by  other  sections  of 
780  CMR. 

313.1.2  Separated  use  groups:  Each  portion  of 
the  building  shall  be  individually  classified  in  a 
use  group  and  shall  be  completely  separated  from 
adjacent  fire  areas  by  fire  separation  assemblies 
(see  780  CMR  709.0)  and  floor/ceiling  assemblies 
(see  780  CMR  713.0)  having  a  fireresistance 
rating  determined  in  accordance  with  Table 
313.1.2,  for  the  use  groups  being  separated.  Each 
fire  area  shall  comply  with  the  code  based  on  the 
use  group  of  that  space.  Each  fire  area  shall 
comply  with  the  height  limitations  of  780  CMR 
503.0  based  on  the  use  of  that  space  and  the  type 
of  construction  classification.  In  each  story,  the 
building  area  shall  be  such  that  the  sum  of  the 
ratios  of  the  floor  area  of  each  use  group  divided 
by  the  allowable  area  from  780  CMR  503.0  for 
each  use  group  shall  not  exceed  one. 

Exception:  Where  the  building  is  equipped 
throughout  with  an  automatic  sprinkler  system 
in  accordance  with  780  CMR  906.2.1,  the 
required  fireresistance  rating  of fire  separation 
assemblies  separating  areas  of  other  than  Use 
Group  H  shall  be  reduced  from  those  indicated 
in  Table  313.1.2  by  one  hour  but  to  not  less  than 
one  hour  and  to  not  less  than  that  required  by 
Table  602  for  floor  construction. 

313.1.3  Separate  buildings:  Each  use  group  shall 
be  considered  a  separate  building  where  each  such 
use  group  is  completely  separated  from  adjacent 
use  groups  by  fire  walls  having  a  fireresistance 
rating  corresponding  to  that  required  by  Table 


602.  Each  building  shall  then  comply  with  the 
provisions  of  780  CMR  applicable  to  the  use 
group  of  that  building. 

313.2  Open  parking  structures  beneath  other  use 
groups:  Open  parking  structures  constructed  under 
Use  Groups  A,  I,  B,  M  and  R  shall  not  exceed  the 
height  and  area  limitations  permitted  under 
780  CMR  406.0.  The  height  and  area  of  the  portion 
of  the  building  above  the  open  parking  structure 
shall  not  exceed  the  limitations  in  780  CMR  503.0 
for  the  upper  use  group  The  height,  in  both  feet  and 
stories,  of  the  portion  of  the  building  above  the  open 
parking  structure  shall  be  measured  from  grade 
plane  and  shall  include  both  the  open  parking 
structure  and  the  portion  of  the  building  above  the 
parking  structure. 

Fire  separation  assemblies  between  the  parking 
occupancy  and  the  upper  occupancy  shall 
correspond  to  the  required  fireresistance  rating 
prescribed  in  Table  313.1.2  for  the  uses  involved. 
The  type  of  construction  shall  apply  to  each 
occupancy  individually,  except  that  all  structural 
members-including  main  bracing  within  the  open 
parking  structure  which  is  necessary  to  support  the 
upper  occupancy-shall  be  protected  with  the  more 
restrictive  fire  resistive  assemblies  of  the 
occupancies  involved  as  shown  in  Table  602.  Exit 
facilities  for  the  upper  occupancy  shall  conform  to 
780  CMR  10  and  shall  be  separated  from  the  parking 
area  by  fire  separation  walls  having  at  least  a  two- 
hour  fireresistance  rating  as  required  by  Table  602 
and  self-closing  doors  complying  with  780  CMR 
716.0.  means  of  egress  from  the  open  parking 
facility  shall  comply  with  780  CMR  1010.5. 

313.3  Use  Group  R:  In  buildings  of  Type  2C,  3B  or 
5B  construction  with  an  occupancy  in  Use  Group  R 
the  first  floor  shall  not  be  occupied  for  Use  Groups 
B  and  M,  unless  the  floor/ceiling  assembly  and  the 
enclosure  walls  are  protected  to  afford  a  one-hour 
fireresistance  rating  and  the  exits  from  the  residential 
floors  are  separately  enclosed  in  accordance  with  the 
requirements  of  780  CMR  10. 


60 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

USE  OR  OCCUPANCY 

Table  313.1.2 

FIRERESISTANCE  RATING  REQUIREMENTS  FOR  FIRE  SEPARATION 

ASSEMBLIES  BETWEEN  FIRE  AREAS3 

Use  Group  NP-  Not  Permitted 

NA  -  Not  Applicable 


A-l 

A-2 

A-3 

A-4 

A-S 

B 

E 

F-l 

F-2 

H-l 

H-2 

H-3 

H-4 

1-1 

1-2 

1-3 

M 

R-l 

R-2 

R-3 

S-l 

S-2 

U 

A-l   2 

3 

2 

2 

2 

: 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

A-2 

3 

3 

3 

3 

3 

3 

3 

3 

NP 

4 

3 

3 

3 

3 

3 

3 

3 

3 

3 

3 

3 

NA 

A-3 

2 

2 

2 

: 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

A-4 

2 

2 

2 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

A-5 

NA 

2 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

B 

2 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

E 

2 

2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

F-l 

2 

2 

NT 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

F-2 

2 

NP 

4 

3 

2 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

u 

H-l 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NA 

s 

H-2 

4 

4 

4 

4 

J 

4 

4 

A 

4 

4 

4 

4 

NA 

E 

H-3 

3 

3 

3 

3 

3 

3 

3 

3 

3 

3 

3 

NA 

H-4 

2 

2 

2 

2 

2 

2 

2 

2 

1 

2 

NA 

G 

1-1 

2 

3 

3 

2 

2 

2 

2 

2 

2 

NA 

R 

1-2 

3 

3 

3 

3 

3 

3 

3 

3 

NA 

0 

1-3 

3 

3 

3 

3 

3 

3 

3 

NA 

U 

M 

2 

2 

2 

: 

2 

2 

NA 

P 

R-l 

2 

2 

2 

2 

2 

NA 

R-2 

2 

2 

2 

2 

NA 

R-3 

2 

2 

2 

NA 

S-l 

2 

2 

NA 

S-2 

2 

NA 

U 

NA 

Note  a.  Fire  resistance  ratings  are  expressed  in  hours. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  61 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


62  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  4 


SPECIAL  USE  AND  OCCUPANCY 


780  CMR  401.0  GENERAL 

401.1  Scope:  In  addition  to  the  general  requirements 
of  780  CMR  governing  the  location,  construction 
and  equipment  of  all  buildings  and  structures,  and 
the  fireresistance  ratings,  height  and  area  limitations 
of  Tables  503  and  602,  the  provisions  of  780  CMR 
4  shall  control  all  buildings  and  structures  designed 
for  special  occupancies  as  herein  provided. 

401.2  Applicable  Massachusetts  General  Law: 
Applicable  Massachusetts  General  Laws,  and 
applicable  rules  and  regulations,  specifically  (but 
not  limited  to)  the  referenced  portions  310  CMR, 
521  CMR,  522  CMR  and  527  CMR  series  as  listed 
in  Appendix  A  shall  be  adhered  to  in  the  design 
and  construction  of  buildings  and  and  structures 
subject  to  the  provisions  of  780  CMR  4. 

780  CMR  402.0  COVERED  MALL  BUILDINGS 

402.1  Scope:  The  provisions  of  780  CMR  402.0 
shall  apply  to  buildings  or  structures  defined  herein 
as  covered  mall  buildings  not  exceeding  three  floor 
levels  in  height  at  any  one  point.  Except  as 
specifically  required  by  780  CMR  402.0,  covered 
mall  buildings  shall  meet  all  applicable  provisions  of 
780  CMR. 

Exceptions:  Where  approved  by  the  code  official, 
the  following  occupancies  are  not  required  to 
comply  with  the  provisions  of  780  CMR  402.0. 

1.  Foyers  and  lobbies  in  occupancies  in  Use 
Group  B,  R-l  orR-2.    • 

2.  Buildings  which  comply  totally  with  all  other 
applicable  provisions  of  780  CMR. 

402.2  Definitions  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  402.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Anchor  store:  An  exterior  perimeter  department 
store  or  major  merchandising  or  magnet  center 
having  direct  access  to  a  mall  and  having  its 
required  exits  independent  of  the  mall. 

Gross  leasable  area:  The  gross  leasable  area  is  the 
total  floor  area  designed  exclusively  for  tenant 
occupancy.  The  area  of  tenant  occupancy  is 
measured  from  the  center  lines  of  joint  partitions 
to  the  outside  of  the  tenant  walls. 

Mall:  A  mall  is  a  roofed-over  common  pedestrian 
area  serving  more  than  one  tenant  located  within 
a  covered  mall  building. 


Mall  building,  covered:  A  building  enclosing  a 
number  of  tenants  and  occupancies  such  as  retail 
stores,  drinking  and  dining  establishments, 
entertainment  and  amusement  facilities,  passenger 
transportation  terminals,  offices  and  other  similar 
occupancies  wherein  two  or  more  tenants  have  a 
main  entrance  into  one  or  more  malls.  Anchor 
stores  shall  not  be  considered  as  part  of  the 
covered  mall  building. 

4023  Lease  plan:  The  owner  or  permit  holder  shall 
provide  both  the  building  and  fire  departments  with 
a  lease  plan  showing  the  locations  of  each 
occupancy  and  its  means  of  egress  after  the 
certificate  of  occupancy  has  been  issued.  Such  plans 
shall  be  kept  current.  Modifications  or  changes  in 
occupancy  shall  not  be  made  from  that  shown  on  the 
lease  plan  without  prior  approval 

402.4  Tenant  separations:  Each  tenant  space  shall 
be  separated  from  other  tenant  spaces  by  a  fire 
partition  having  a  fireresistance  rating  of  not  less 
than  one  hour.  The  fire  partition  shall  comply  with 
780  CMR  711.0  except  that  the  fire  partition  is  not 
required  to  extend  beyond  the  underside  of  a  ceiling 
that  is  not  part  of  a  fireresistance  rated  assembly.  A 
wall  is  not  required  in  attic  or  ceiling  spaces  above 
tenant  separation  walls  nor  is  a  tenant  separation 
wall  required  between  any  tenant  space  and  a  mall, 
except  for  occupancy  separations  required  elsewhere 
in  780  CMR. 

402.4.1  Anchor  store  openings:  Openings 
between  an  anchor  store  and  the  pedestrian  area  of 
a  mall  are  not  required  to  be  protected. 

402.4.2  Party  wall  exemption:  Anchor  stores 
located  on  separate  lots  shall  not  be  required  to 
provide  party  walls  between  the  anchor  store  and 
the  covered  mall  building. 

402.5  Egress:  Each  individual  occupancy  within  the 
covered  mall  building  shall  be  provided  with  a 
means  of  egress  in  accordance  with  other  provisions 
of  780  CMR.  Measurements  shall  be  made  to  the 
entrance  to  the  mall. 

402.5.1  Travel  distance:  The  maximum  length  of 
exit  access  travel  from  any  point  within  the  mall 
to  an  approved  exit  along  the  natural  and 
unobstructed  path  of  travel  shall  not  exceed  200 
feet  (60960  mm). 

402.5.2  Anchor  store  exits:  Anchor  stores  shall 
provide  the  required  number  of  exits  and  the 
minimum  width  for  the  required  exit  capacity 
directly  to  the  exterior.    The  occupant  load  of 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


63 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


anchor  stores  opening  into  the  mall  shall  not  be 
included  in  determining  exit  requirements  for  the 
mall. 

402.5.3  Dead  ends:  The  dead  end  of  a  mall  shall 
not  exceed  twice  the  width  of  the  mall. 

402.5.4  Design  occupant  load:  In  determining 
required  exit  facilities  of  the  mall,  the  number  of 
occupants  for  whom  exit  facilities  are  to  be 
provided  shall  be  based  on  gross  leasable  area  of 
the  covered  mall  building  (excluding  anchor 
stores)  and  the  occupant  load  factor  as  determined 
by  the  following  formula: 

OLF  =  (0.00007)  (GLA)  +  25 

where: 

OLF  =  The  occupant  load  factor  (square  feet  per 

person). 

GLA  =  The  gross  leasable  area  (square  feet). 

The  occupant  load  factor  (OLF)  is  not  required 
to  be  less  than  30  and  shall  not  exceed  50. 

402.5.5  Exit  access  width:  The  minimum  width 
of  exit  access  passageways  and  corridors  from  a 
mall  shall  be  66  inches  (1676  mm). 

402.5.6  Exit  distribution:  The  required  exits  and 
exit  widths  shall  be  distributed  equally  throughout 
the  mall. 

402.5.7  Storage  prohibited:  Storage  is  prohibited 
in  exit  corridors  that  are  used  for  service  to 
tenants.  Such  corridors  shall  be  posted  with 
conspicuous  signs  so  stating. 

402.5.8  Passenger  transportation  terminals:  A 

covered  mall  building  whose  primary  purpose  is 
a  passenger  transportation  terminal  shall  comply 
with  the  means  of  egress  requirements  for  Use 
Group  A-3. 

402.5.9  Service  areas  fronting  on  exit 
passageways  and  corridors:  Mechanical  rooms, 
electrical  rooms,  building  service  areas  and 
service  elevators  are  permitted  to  open  directly 
into  exit  passageways  and  exit  corridors  provided 
that  the  required  fireresi  stance  rating  of  the  exit 
enclosure  is  maintained. 

402.6  Mall  width:  The  minimum  width  of  the  mall 
shall  be  20  feet  (6096  mm)  There  shall  be  a 
minimum  often  feet  (3048  mm)  clear  exit  width  to 
a  height  of  eight  feet  (2438  mm)  between  any 
projection  of  a  tenant  space  bordering  the  mall  and 
the  nearest  kiosk,  vending  machine,  bench,  display 
opening  or  other  obstruction  to  means  of  egress 
travel.  The  mall  width  shall  be  sufficient  to 
accommodate  the  occupant  load  emptying  into  the 
immediately  adjacent  mall  as  determined  by 
780  CMR  402.5.4  for  all  occupancies  except  Use 
Groups  A  and  E  which  shall  be  determined  by 
780  CMR  1008.0. 


402.7  Structural  elements:  Covered  mall  buildings 
shall  be  of  Type  1,2  or  4  construction.  Covered  mall 
buildings  three  stories  or  less  in  height  are  exempt 
from  the  area  limitations  of  Table  503. 

402.7.1  Structural  elements,  anchor  stores:  An 

anchor  store  three  stories  or  less  in  height  shall  be 
of  Type  1,  2  or  4  construction  and  is  exempt  from 
the  area  limitations  of  Table  503,  provided  that  a 
smoke  control  system  conforming  to  780  CMR 
921.0  is  installed  in  the  anchor  store.  For  the 
purposes  of  the  design  and  operation  of  the  fire 
emergency  ventilation  system,  the  anchor  store 
shall  be  considered  a  tenant  space  zone. 

402.8  Roof  coverings:  Roof  coverings  for  covered 
mall  buildings  shall  be  of  Class  A,  B  or  C  as 
required  by  780  CMR  1506.0. 

402.9  Use  Groups  A-l  and  A-2:  Use  Group  A-l 
and  A-2  occupancies  shall  not  have  more  than  one- 
half  of  their  required  means  of  egress  opening 
directly  to  the  mall  (see  780  CMR  1006.2.2). 

402.10  Sprinkler  system:  The  mall  and  all 
buildings  connected  thereto  shall  be  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2.1.  The  system 
shall  be  installed  in  such  a  manner  that  when  any 
portion  of  the  system  serving  tenant  spaces  is  shut 
down,  the  portion  of  the  system  serving  the  mall  will 
remain  operational. 

402.11  Standpipes:  There  shall  be  a  standpipe  hose 
connection  located  within  the  mall  at  each  entrance 
to  an  exit  passageway,  exit  corridor  or  enclosed 
stairway  and  at  all  exterior  entrances  to  the  mall. 
The  hose  connection  shall  be  supplied  from  the 
automatic  sprinkler  system  of  the  mall  or  from  a 
separate  standpipe  system  The  water  supply  shall 
be  capable  of  delivering  250  gallons  per  minute 
(gpm)  (0.016  m3/s). 

402.12  Smoke  control:  The  mall  and  adjacent  tenant 
spaces  shall  be  equipped  with  a  smoke  control 
system  conforming  to  780  CMR  92 1 .0. 

402.13  Fire  department  access  to  equipment 
controls:  Fire  protection  system  and  HVAC  system 
controls  shall  be  identified,  and  the  fire  department 
shall  have  access  thereto. 

402.14  Plastic  panels  and  plastic  signs:  Within 
every  story  or  level  and  from  side  wall  to  side  wall 
of  each  tenant  space,  approved  plastic  panels  and 
signs  shall  be  limited  as  specified  in  780  CMR 
402.14.1  through  402. 14.4. 

402.14.1  Area:  The  panels  and  signs  shall  not 
exceed  20%  of  the  wall  area  facing  the  mall 

402.14.2  Height  and  width:  The  panels  and  signs 
shall  not  exceed  a  height  of  36  inches  (914  mm). 


bA 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


except  if  the  panel  or  sign  is  vertical,  the  height 
shall  not  exceed  96  inches  (2438  mm)  and  the 
width  shall  not  exceed  36  inches  (914  mm). 

402.14.3  Location:  The  panels  and  signs  shall  be 
located  a  minimum  distance  of  18  inches  (457 
mm)  from  adjacent  tenants. 

402.14.4  Encasement:  All  edges  and  the  backs 
shall  be  fully  encased  in  metal. 

402.15  Kiosks:  Kiosks  and  similar  structures 
(temporary  or  permanent)  shall  meet  the 
requirements  of  780  CMR  402.15.1  through 
402.15.4. 

402.15.1  Construction:  Combustible  kiosks  or 
other  structures  shall  not  be  located  within  the 
mall  unless  constructed  of  fireretardant-treated 
wood  throughout  conforming  to  780  CMR 
2310.0. 

402.15.2  Fire  suppression:  Kiosks  and  similar 
structures  that  are  covered  and  are  located  within 
the  mall  shall  be  protected  by  an  automatic 
sprinkler  system  installed  in  accordance  with 
780  CMR  9. 

402.15.3  Horizontal  separation:  The  minimum 
horizontal  separation  between  kiosks  and  other 
structures  within  the  mall  shall  be  20  feet  (6096 
mm). 

402.15.4  Maximum  area:  Kiosks  or  similar 
structures  shall  have  a  maximum  area  of  300 
square  feet  (27.90  m2). 

402.16  Parking  structures:  An  attached  garage  for 
the  storage  of  passenger  vehicles  that  have  a 
capacity  of  not  more  than  nine  persons,  or  an  open 
parking  structure,  shall  be  considered  as  a  separate 
building  where  it  is  separated  from  the  covered  mall 
building  by  a  fire  separation  assembly  having  a 
fireresistance  rating  of  not  less  than  two  hours  or 
shall  be  considered  as  part  of  the  covered  mall 
building. 

780  CMR  403.0  HIGH-RISE  BUILDINGS 

403.1  Applicability:  The  provisions  of  780  CMR 
403.0  shall  apply  to  all  buildings  having  occupied 
floors  located  more  than  70  feet  above  mean  grade. 
SeeM.G.L.  c.  148,  § 26A. 

Exception:  The  provisions  of  780  CMR  403.0 
shall  not  apply  to  the  following  buildings  and 
structures: 

1.  Airport  traffic  control  towers  conforming  to 
the  requirements  of  780  CMR  414.0. 

2.  Open  parking  structures  (see  780  CMR 
406.0). 

3.  Buildings  with  an  occupancy  in  Use  Group  A- 
5  (see  780  CMR  303.6). 


4.  Low-hazard  special  occupancies  where 
approved  by  the  code  official  (see  780  CMR 
503.1.1). 

5.  Buildings  with  an  occupancy  in  Use  Group  H- 
l,H-2orH-3. 

403.2  Sprinkler  system:  All  buildings  and 
structures  shall  be  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1  and  M.G.L.  c.  148,  §  26A 

Exception:  An  automatic  sprinkler  system  shall 
not  be  required  in  spaces  or  areas  of: 

1.  Open  parking  structures  complying  with 
780  CMR  406.0. 

2.  Telecommunications  equipment  buildings 
used  exclusively  for  telecommunications 
equipment,  associated  electrical  power 
distribution  equipment,  batteries  and  standby 
engines,  provided  that  those  spaces  or  areas  are 
equipped  throughout  with  an  automatic  fire 
detection  system  in  accordance  with  780  CMR 
918.0  and  are  separated  from  the  remainder  of  the 
building  with  fire  separation  assemblies 
consisting  of  one-hour  fireresistance  rated  walls 
and  two-hour  fireresistance  rated  floor/ceiling 
assemblies. 

403.3  Alternative  sprinkler  system:  Alternatively, 
to  qualify  for  the  fireresistance  rating  reduction  for 
certain  building  elements  listed  in  780  CMR  403.3.3, 
the  automatic  sprinkler  system  shall  comply  with 
780  CMR  906.2.1  and  the  optional  fire  protection 
features  listed  in  780  CMR  403.3.1  and  403.3.2. 

403.3.1  Control  valves  and  water-flow  devices: 

Sprinkler  control  valves  equipped  with 
supervisory  initiating  devices  and  water-flow 
initiating  devices  shall  be  provided  for  each  floor. 

403.3.2  Automatic  sprinkler  system  alternative: 

Where  a  complete  automatic  sprinkler  system 
with  the  additional  system  features  listed  in 
780  CMR  403.3.1  and  403.3.2  is  installed 
throughout,  modifications  to  780  CMR  are 
permitted  as  described  in  780  CMR  403.3.3.1  and 
403.3.3.2. 

403.3.3  Automatic  sprinkler  system  alternative: 
Where  a  complete  automatic  sprinkler  system 

with  additional  system  features  listed  in  780  CMR 
403.3.3.1  and  403.3.3.2. 

403.3.3.1  Type  of  construction:  Other  than  in 

buildings  with  an  occupancy  in  Use  Groups  F- 

I,  H-3,  M  and   S-l,   the  minimum  type  of 

construction  required  by  780  CMR  shall  be 

modified  as  indicated  in  Table  403.3.3.1. 

Exception:      The     Type      1A      to      IB 

modification     shall     be     permitted     for 

buildings  with  an  occupancy  in  Use  Groups 

F-l,  MandS-1. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


65 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  403.3.3.1 

TYPE  OF  CONSTRUCTION 

MODIFICATIONS  PERMITTED  FOR 

HIGH-RISE  BUILDINGS 


Type  of  Construction  set 
'  forth  in  Table  602 

Modified  type  of  construction 
permitted  hereunder 

1A 
IB 

2A 

IB 
2Aa 
2B 

Note  a.   The  minimum  fireresistance  rating  floor 
construction  shall  be  two  hours. 

403.3.3.2  Shaft  enclosures:  The  required 
fireresistance  rating  of  the  fire  separation 
assemblies  enclosing  vertical  shafts,  other 
than  stairway  enclosures  and  elevator 
hoistway  enclosures,  shall  be  reduced  to  one 
hour  where  automatic  sprinklers  are 
installed  within  the  shafts  at  the  top  and  at 
alternate  floor  levels. 

403.4  Automatic  fire  detection:  A  smoke  detector 
suitable  for  the  intended  application  shall  be 
installed  in  each  of  the  following  rooms:  mechanical 
equipment,  electrical;  transformer;  telephone 
equipment;  elevator  machine;  or  similar  room.  The 
actuation  of  any  detector  shall  sound  an  alarm  at  a 
constantly  attended  location. 

403.5  Voice/alarm      signaling      systems:      A 

voice/alarm  signaling  system  shall  be  provided  in 
accordance  with  780  CMR  917.9  and  activated  in 
accordance  with  780  CMR  917.7.1. 

403.6  Fire  department  communication  system:  A 

two-way  fire  department  communication  system 
shall  be  provided  for  fire  department  use.  The 
communication  system  shall  operate  between  the  fire 
command  station  and  every  elevator,  elevator  lobby 
and  enclosed  exit  stairway.  Acceptable  types  of  fire 
department  communications  shall  include: 

1  Telephone  or  fire  department  radio  in  lieu  of 
a  dedicated  system,  where  approved  by  the  fire 
department;  and 

2.  Intercom  or  two-way  public  address  system 
complying  with  NFiPA  72  listed  in  Appendix  A. 

403.7  Fire  command  station:  A  fire  command 
station  for  fire  department  operations  shall  be 
provided  in  a  location  approved  by  the  fire 
department.  The  fire  command  station  shall  contain: 
the  voice/alarm  signaling  system  controls;  the  fire 
department  communication  system  controls;  the 
automatic  fire  detection  and  protective  signaling 
system  annunciator  panels;  an  annunciator  that 
visually  indicates  the  floor  location  of  elevators  and 
whether  they  are  operational;  status  indicators  and 
controls  for  air-handling  systems;  controls  for 
unlocking  all  stairway  doors  simultaneously; 
sprinkler  valve  and  water-flow  detector  display 
panels;  emergency  and  standby  power;  status 
indicators;  and  a  telephone  for  fire  department  use 


with  controlled  access  to  the  public  telephone 
system. 

403.8  Elevators:  Elevator  operation  and  installation 
shall  be  in  accordance  with  524  CMR.  Elevator 
service  shall  be  provided  for  fire  department 
emergency  access  to  all  floors.  Elevator  cab 
dimensions  shall  conform  to  the  applicable 
requirements  of  524  CMR. 

Except  for  the  main  entrance  level,  all  elevators 
shall  open  into  a  lobby  separated  from  the  remainder 
of  the  building  by  one  hour  fireresistance  rated 
construction. 

Exit  stairways,  chutes,  janitor  closets,  tenant 
spaces  in  Use  Group  R  and  service  rooms  shall  not 
open  into  the  elevator  lobby.  In  Use  Groups  other 
than  R  tenant  spaces  opening  into  the  elevator  lobby 
shall  be  provided  with  other  means  of  exit  access 
that  do  not  require  passage  through  the  elevator 
lobby. 

Exception:  elevator  lobbies  are  not  required 
when  a  smoke  control  system  is  installed  in 
accordance  with  780  CMR  921.7. 

403.9  Standby  power,  light  and  emergency 
systems:  Standby  power,  light  and  emergency 
systems  shall  comply  with  the  requirements  of 
780  CMR  403.9. 1  through  403.9.3. 

403.9.1  Standby  power:  A  standby  power  system 
conforming  to  the  requirements  of  527  CMR  as 
listed  in  Appendix  A.  If  the  standby  system  is  a 
generator  set  inside  a  building,  the  system  shall  be 
located  in  a  separate  room  enclosed  with  two-hour 
fireresistance  rated  fire  separation  assemblies. 
System  supervision  with  manual  start  and  transfer 
features  shall  be  provided  at  the  fire  command 
station. 

403.9.1.1  Fuel  supply:  An  on-premises  fuel 
supply,  sufficient  for  not  less  than  two-hour 
full-demand  operation  of  the  system,  shall  be 
provided. 

Exception:  Where  the  system  is  supplied 
with  pipeline  natural  gas  and  is  approved. 

403.9.1.2  Capacity:  The  standby  system  shall 
have  a  capacity  and  rating  that  supplies  all 
equipment  required  to  be  operational  at  the 
same  time.  The  generating  capacity  is  not 
required  to  be  sized  to  operate  all  of  the 
connected  electrical  equipment  simultaneously. 

403.9.1.3  Connected  facilities:  All  power  and 
lighting  facilities  for  the  fire  command  station 
and  elevators  specified  in  780  CMR  403.7  and 
403.8,  as  applicable,  and  electrically  powered 
fire  pumps  required  to  maintain  pressure,  shall 
be  transferable  to  the  standby  source.  Standby 
power  shall  be  provided  for  at  least  one 
elevator  to  serve  all  floors  and  be  transferable 
to  any  elevator. 


66 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97; 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


403.9.2  Separate  circuits  and  fixtures:  Separate 
lighting  circuits  and  fixtures  shall  be  required  to 
provide  sufficient  light  with  an  intensity  of  not 
less  than  one  footcandle  (10.76  lux)  measured  at 
floor  level  in  all  means  of  egress  corridors, 
stairways,  smokeproof  enclosures,  elevator  cars 
and  lobbies,  and  other  areas  which  are  clearly  a 
part  of  the  escape  route. 

403.9.2.1  Other  circuits:  All  circuits 
supplying  lighting  for  the  fire  command  station 
and  mechanical  equipment  rooms  shall  be 
transferable  to  the  standby  source. 

403.9.3  Emergency  systems:  Exit  signs,  exit 
illumination  as  required  by  780  CMR  1024.0,  and 
elevator  car  lighting  are  classified  as  emergency 
systems  and  shall  operate  within  ten  seconds  of 
failure  of  the  normal  power  supply  and  shall  be 
capable  of  being  transferred  to  the  standby  source. 

Exception:  Exit  sign,  exit  and  means  of  egress 
illumination  are  permitted  to  be  powered  by  a 
standby  source  in  buildings  of  Use  Groups  F 
and  S. 

403.10  Stairway  door  operation:  All  stairway 
doors  which  are  to  be  locked  from  the  stairway  side 
shall  be  capable  of  being  unlocked  simultaneously 
without  unlatching  upon  a  signal  from  the  fire 
command  station. 

403.10.1  Stairway  communication  system:  A 

telephone  or  other  two-way  communication 
system  connected  to  an  approved  constantly 
attended  station  shall  be  provided  at  not  less  than 
every  fifth  floor  in  each  required  stairway  where 
the  doors  to  the  stairway  are  locked. 

403.11  Smokeproof  enclosures:  A  smokeproof 
enclosure,  as  set  forth  in  780  CMR  1015.0  is 
required  for  at  least  one  exit.  Other  required 
stairways  greater  than  70  feet  in  height  shall  be 
pressurized  to  a  minimum  of  0.15  inches  of  water 
column,  but  not  exceeding  0.35  inches  of  water 
column.  Such  required  stairway  pressurization 
being  relative  to  building  pressure  and  with  all 
stairway  doors  closed.  Pressurization  design  shall 
take  into  consideration  maximum  anticipated  stack 
pressure  effects  in  the  stairway. 

The  stairway  pressurization  system  shall  be 
activated  by  any  deuces  which  are  required  to 
activate  the  voice  alarm  system  described  in 
780  CMR  403.5. 

780  CMR  404.0  ATRIUMS 
404.1  General:  The  term  "atrium"  shall  mean  an 
occupied  space  that  includes  a  floor  opening  or 
series  of  floor  openings,  which  connects  two  or  more 
stories.  An  atrium  shall  comply  with  780  CMR 
404.0  where  a  shaft  enclosure  is  required  by 
780  CMR  713.3.    Atriums  shall  be  permitted  in  all 


occupancies,  other  than  Use  Group  H,  where 
provided  with  the  protection  herein  required. 

404.2  Automatic  sprinkler  system:  The  atrium  and 
all  stories  and  floor  areas  connected  to  the  atrium 
shall  be  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1.  The  automatic  sprinkler  system  shall  be 
supervised  in  accordance  with  780  CMR  923.1, 
method  1,  2  or  3. 

Exception:  An  automatic  sprinkler  system  shall 
not  be  required  in  areas  separated  from  the  atrium 
by  fire  separation  assemblies  in  accordance  with 
780  CMR  709.0. 

404.3  Atrium  occupancy:  The  floor  of  the  atrium 
shall  not  be  occupied  for  other  than  low  fire-hazard 
occupancies  and  only  approved  materials  and 
decorations  shall  be  located  in  the  atrium  space. 

Exception:  The  occupancy  of  the  atrium  floor 
area  for  any  approved  purpose  shall  not  be 
restricted  where  the  hazard  is  protected  with  an 
automatic  sprinkler  system  installed  in  accordance 
with  780  CMR  906.2.1. 

404.3.1  Exit  discharge:  Exit  discharge  in 
accordance  with  780  CMR  1020.0  is  permitted 
within  the  atrium. 

404.4  Smoke  control:  A  smoke  control  system 
complying  with  780  CMR  921.0  shall  be  installed  in 
all  atriums  that  connect  more  than  two  stories. 

404.5  Enclosure  of  atriums:  Atrium  spaces  shall  be 
separated  from  adjacent  spaces  by  a  one-hour  fire 
partition  as  required  for  corridors. 

Exceptions 

1.  In  residential  occupancies,  protected  openings 
are  not  required  where  the  floor  area  of  each  guest 
room  or  dwelling  unit  does  not  exceed  1,000 
square  feet  (93  m2)  and  each  room  or  unit  has  an 
approved  means  of  egress  not  entering  the  atrium. 

2.  Adjacent  spaces  shall  be  separated  from  the 
atrium  by  fire  windows  or  by  a  tempered,  wired, 
laminated  glass  or  glass-block  wall  subject  to  the 
following  criteria: 

2.1.  The  glass  shall  be  protected  by  a 
specially  designed  automatic  sprinkler  system. 
The  sprinkler  system  shall  completely  wet  the 
entire  surface  of  the  glass  wall  when  actuated. 
Where  there  are  walking  surfaces  on  both  sides 
of  the  glass,  both  sides  of  the  glass  shall  be  so 
protected; 

2.2.  The  tempered,  wired  or  laminated  glass 
shall  be  in  a  gasketed  frame  and  installed  in 
such  a  manner  that  the  framing  system  will 
deflect  without  breaking  (loading)  the  glass 
before  the  sprinkler  system  operates; 

2.3.  The  glass-block  wall  assembly  shall  be 
installed  in  accordance  with  the  listing  for  a  Vt- 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


67 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


hour  fireresistance  rating  and  the  requirements 
of780CMR2115.0;and 
2.4.        Obstructions,   such  as  curtain  rods, 
drapery   traverse   rods,    curtains,    drapes   or 
similar  materials  shall  not  be  installed  between 
the  automatic  sprinklers  and  the  glass. 
3.    The  adjacent  spaces  of  any  three  floors  of  the 
atrium  shall  not  be  required  to  be  separated  from 
the    atrium;    however,    these    spaces    shall    be 
included  in  the  atrium  volume  for  the  design  of 
the  smoke  control  system  (see  780  CMR  921.0). 

404.6  Signaling  system:  A  fire  protective  signaling 
system  shall  be  installed  in  all  occupancies  with  an 
atrium  that  connects  more  than  two  stories.  The 
system  shall  be  activated  in  accordance  with 
780  CMR  917.7.1.  Such  occupancies  in  Use  Group 
A,  E  or  M  shall  be  provided  with  a  voice/alarm 
signaling  system  complying  with  the  requirements  of 
780  CMR  917.9. 

404.7  Travel  distance:  In  other  than  the  lowest  level 
of  the  atrium,  where  the  required  means  of  egress  is 
through  the  atrium  space,  the  portion  of  exit  access 
travel  distance  within  the  atrium  space  shall  not 
exceed  150  feet  (45720  mm). 

780  CMR  405.0  UNDERGROUND 
STRUCTURES 

405.1  Applicability:  The  provisions  of  780  CMR 
405.0  apply  to  all  structures  having  a  floor  level 
used  for  human  occupancy  more  than  30  feet  (9144 
mm)  below,  or  more  than  one  story  below,  the 
lowest  level  of  exit  discharge  serving  that  floor  level. 

Exception:  The  provisions  of  780  CMR  405.0 
shall  not  apply  to  the  following  structures: 

1.  Occupancies  in  Use  Group  R-3  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.0. 

2.  Public  garages  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.0. 

3 .  Fixed  guideway  transit  systems. 

4.  Occupancies  in  Use  Group  A-5. 

5.  Structures  wherein  the  lowest  story  is  the  only 
story  that  qualifies  the  structure  as  an 
underground  structure  and  which  have  an  area  not 
exceeding  1,500  square  feet  (140  m2)  and  an 
occupant  load  less  than  ten. 

405.2  Construction:  The  underground  portion  of  the 
structure  shall  be  of  Type  1  construction. 

405.3  Automatic  sprinkler  system:  The  highest 
level  of  exit  discharge  serving  the  underground 
portions  of  the  structure  and  all  levels  below  shall  be 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.0. 


405.4  Compartmentation:  In  structures  that  have  a 
floor  level  more  than  60  feet  (18288  mm)  below  the 
lowest  level  of  exit  discharge,  the  highest  level  of 
exit  discharge  serving  the  underground  portions  of 
the  structure  and  all  levels  below  shall  each  be 
divided  into  a  minimum  of  two  compartments  of 
approximately  equal  size  by  a  smoke  barrier  in 
accordance  with  780  CMR  712.0. 

Exception:  Two  compartments  are  not  required  in 
the  lowest  story  where  such  story  has  an  area  of 
less  than  1,500  square  feet  (140  m2)  and  an 
occupant  load  of  less  than  ten. 

405.4.1  Smoke        barrier        penetrations: 

Penetrations  of  the  smoke  barrier  shall  be  limited 
to  plumbing  and  automatic  sprinkler  system 
piping  and  electrical  raceways.  The  air  supply, 
return  and  exhaust  system  provided  in  one 
compartment  shall  be  independent  of  such 
systems  provided  in  other  compartments. 

405.4.2  Elevators:  Where  elevators  are  provided, 
each  compartment  shall  have  direct  access  to  an 
elevator.  Where  an  elevator  serves  more  than  one 
compartment,  an  elevator  lobby  shall  be  provided 
and  shall  be  separated  from  both  compartments  by 
a  fire  separation  assembly  having  not  less  than  a 
one-hour  fireresistance  rating. 

405.4.3  Egress:  Each  compartment  shall  contain 
not  less  than  one  exit  and  shall  also  have  an  exit 
access  doorway  into  the  adjoining  compartment. 

405.5  Smoke  exhaust  system:  Where 
compartmentation  is  required  by  780  CMR  405.4, 
each  compartment  shall  have  an  independent 
automatically  activated  smoke  exhaust  system 
capable  of  manual  operation.  The  system  shall  have 
an  air  supply  and  smoke  exhaust  capability  which 
will  provide  a  minimum  of  six  air  changes  per  hour. 

405.5.1  Automatic  fire  detection:  A  smoke 
detector  complying  with  780  CMR  918.8  and 
suitable  for  the  intended  use  shall  be  installed  in 
each  of  the  following  rooms:  mechanical 
equipment;  electrical;  transformer;  telephone 
equipment;  elevator  machine;  or  similar  room. 
The  actuation  of  any  detector  shall  sound  an  alarm 
at  a  constantly  attended  location. 

405.5.2  Activation:  The  smoke  exhaust  system 
shall  be  activated  in  the  compartment  of  origin  by 
actuation  of  the  following,  independently  of  each 
other: 

1 .  Automatic  sprinkler  system; 

2.  Smoke  detectors  required  by  780  CMR 
405.5.1;  and 

3.  Manual    controls    provided    for    fire 
department  use. 

405.6  Fire  protective  signaling  system:  Where  the 
lowest  level  of  a  structure  is  more  than  60  feet 
(18288    mm)    below    the    lowest    level    of  exit 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


discharge,  the  structure  shall  be  equipped 
throughout  with  a  fire  protective  signaling  system  in 
accordance  with  780  CMR  917.0,  including  a 
voice/alarm  signaling  system  installed  in  accordance 
with  780  CMR  917.9  and  activated  in  accordance 
with  780  CMR  917.7.1. 

405.7  Public  address:  Where  a  fire  protective 
signaling  system  is  not  required  by  780  CMR  405.6 
or  917.4,  a  public  address  system  shall  be  provided 
which  shall  be  capable  of  transmitting  voice 
communications  to  the  highest  level  of  exit 
discharge  serving  the  underground  portions  of  the 
structure  and  all  levels  below. 

405.8  Standby  power:  A  standby  power  system  of 
sufficient  capacity  and  rating  and  conforming  to  the 
requirements  of  527  CMR  12.00  as  listed  in 
Appendix  A  shall  be  provided. 

405.8.1  Fuel  supply:  If  the  standby  system  is  a 
generator  set  inside  a  structure,  the  system  shall 
be  located  in  a  separate  room  enclosed  with  two- 
hour  fireresistance  fire  rated  fire  separation 
assemblies.  System  supervision  with  manual  start 
and  transfer  features  shall  be  provided  at  the 
central  station. 

405.8.2  Capacity:  The  standby  system  shall 
supply  the  following  required  systems: 

1.  Smoke  exhaust  system. 

2.  Smokeproof  enclosure. 

3.  Fire  pumps. 

4.  One  elevator  to  serve  all  floors  with  the 
capability  of  transferring  power  to  any 
elevator. 

5.  Emergency  electrical  system. 

405.9  Emergency  power:  An  emergency  electrical 
system  of  sufficient  capacity  and  rating  and 
conforming  to  the  requirements  of  527  CMR  12.00 
as  listed  in  Appendix  A  shall  be  provided.  The 
emergency  system  shall  supply  the  following 
required  systems: 

1 .  Voice  communication  system. 

2.  Fire  protective  signaling  system. 

3.  Fire  detection  systems. 

4.  Elevator  car  lighting. 

5.  Means  of  egress  lighting  and  exit  sign 
illumination. 

780  CMR  406.0  OPEN  PARKING 
STRUCTURES 

406.1  General:  Open  parking  structures  are  those 
structures  used  for  the  parking  or  storage  of 
passenger  motor  vehicles  designed  to  carry  not  more 
than  nine  persons,  wherein  provision  for  the  repair 
of  such  vehicles  is  not  made  and  where  the  exterior 
walls  of  the  structure  have  openings  on  not  less  than 
two  sides.  Open  parking  structures  are  not  required 
to  conform  to  780  CMR  408.0  for  public  garages. 


406.1.1  Openings:  The  exterior  walls  of  the  open 
parking  structure  shall  have  uniformly  distributed 
openings  on  not  less  than  two  sides  totaling  not 
less  than  40%  of  the  building  perimeter.  The 
aggregate  area  of  such  openings  in  exterior  walls 
in  each  level  shall  not  be  less  than  20%  of  the 
total  perimeter  wall  area  of  each  level.  Interior 
wall  lines  and  column  lines  shall  be  at  least  20% 
open  with  openings  distributed  to  provide 
ventilation. 

Exception:  Openings  are  not  required  to  be 
distributed  over  40%  of  the  building  perimeter 
where  the  required  openings  are  uniformly 
distributed  over  two  opposing  sides  of  the 
building. 

406.1.2  Separation:  Exterior  walls  containing 
openings  shall  have  afire  separation  distance  of 
greater  than  ten  feet  (3048  mm). 

406.2  Construction  requirements:  Passenger 
vehicle  structures  shall  be  constructed  of  approved 
non  combustible  materials  throughout,  including 
structural  framing,  floors,  roofs  and  walls.  Any 
enclosed  room  or  space  on  the  premises  shall 
comply  with  the  applicable  requirements  of 
780  CMR. 

406.3  Fuel  dispensing:  Areas  where  fuel  is 
dispensed  shall  conform  to  the  requirements  of 
780  CMR  408.4. 

406.4  Heights  and  areas:  Heights  and  areas  of  open 
parking  structures  shall  not  exceed  the  limitations 
specified  in  Table  406.4,  except  as  provided  for  in 
780  CMR  406.4.1.  The  heights  and  areas  are 
subject  to  the  increases  indicated  in  780  CMR  504.0 
and  506.0.  The  above  height  limitations  permit 
parking  on  the  roof. 

Table  406.4 

HEIGHT  AND  AREA  LIMITATIONS  FOR 

OPEN  PARKING  STRUCTURES 


Type  of 
construction 


Height 


Area  (square  feet) 


lAandlB  Unlimited  Unlimited 

2  A  12  Stories  -120  feet  Unlimited 

2B  10  Stories- 100  feet       :      50,000 

2C  8  Stories  -  85  feet  50.000 

Note  a.    1  foot  =  304.8  mm;  1  square  foot  =  0.093  m 

406.4.1  Unlimited  area:  Structures  with  all  sides 
open  shall  be  unlimited  in  area  provided  that  the 
height  does  not  exceed  75  feet  (22860  mm).  For 
a  side  to  be  considered  open,  the  total  area  of 
openings  along  the  side  shall  not  be  less  than  50% 
of  the  exterior  area  of  the  side  at  each  parking 
level  and  such  openings  shall  be  equally 
distributed  along  the  length  of  each  level.  All 
portions  of  each  parking  level  shall  be  within  200 
feet  (60960  mm)  horizontally  from  an  exterior 
wall  opening  on  any  permanent  open  space. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


406.5  Guards:  All  open-sided  floor  areas  shall  be 
provided  with  a  guard  in  accordance  with  780  CMR 
1021.0,  except  that  in  those  structures  wherein 
vehicles  are  hoisted  to  the  desired  level  and  placed 
in  the  parking  space  entirely  by  approved 
mechanical  means,  the  guard  is  not  required  on  the 
side  of  the  parking  levels  adjacent  to  the  space 
occupied  by  the  hoisting  and  placing  equipment. 

406.6  Wheel  guards:  Wheel  guards  made  of 
approved  noncombustible  material  shall  be  placed 
wherever  required. 

780  CMR  407.0  PRIVATE  GARAGES 

407.1  General:  Private  garages  shall  comply  with 
the  requirements  of  780  CMR  407.0.  All  private 
garages  not  falling  within  the  purview  of  780  CMR 
407.3  through  407.7  and  which  are  attached  to  or 
located  beneath  a  building  shall  comply  with  the 
requirements  of  780  CMR  3 13.0  for  public  garages. 

407.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  407.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Garage,  private:  A  garage  for  four  or  less  passenger 
motor  vehicles,  four  or  less  single  motor 
airplanes,  or  one  commercial  motor  vehicle, 
without  provision  for  repairing  or  servicing  such 
vehicles  for  profit. 

407.3  Beneath  rooms:  Private  garages  located 
beneath  habitable  rooms  in  occupancies  in  Use 
Group  R- 1 .  R-2,  R-3  or  I- 1  shall  be  separated  from 
adjacent  interior  spaces  by  fire  partitions  and 
floor/ceiling  assemblies  which  are  constructed  with 
not  less  than  a  one-hour  fireresistance  rating.  Wood 
structural  members  of  the  minimum  dimensions 
specified  in  780  CMR  2304.0  for  Type  4 
construction  shall  be  acceptable  without  any  further 
protection  where  a  one-hour  fireresistance  rating  is 
required. 

407.4  Attached  to  rooms:  Private  garages  attached 
side-by-side  to  rooms  in  occupancies  in  Use  Group 
R-l,  R-2,  R-3  or  1-1  shall  be  completely  separated 
from  the  interior  spaces  and  the  attic  area  by  means 
of  %-inch  Type-X  gypsum  board  or  the  equivalent 
applied  to  the  garage  side. 

407.5  Door  sills:  The  sills  of  all  door  openings 
between  private  garages  and  adjacent  interior  spaces 
shall  be  raised  not  less  than  four  inches  (102  mm) 
above  the  garage  floor. 

407.6  Opening  protectives:  The  door  opening 
protectives  shall  comply  with  one  of  the  following. 

1.     l3/4-inch  solid  core  wood  door. 


2.     l3/<i-inch  solid  or  honeycomb  core  steel  door 

407.7  Firestopping  of  concealed  spaces:  Where  a 
garage  is  connected  to  an  occupancy  in  Use  Group 
R-3  by  a  concealed  space,  such  as  a  breezeway,  that 
is  of  Type  5B  construction  and  ten  feet  (3048  mm) 
or  greater  in  length,  the  junction  of  the  garage  and 
the  concealed  space  shall  be  firestopped  to  comply 
with  780  CMR  720.0. 

407.8  Means  of  egress:  Where  living  quarters  are 
located  above  a  private  garage,  the  required  means 
of  egress  facilities  shall  be  separated  from  the  garage 
area  with  one-hour  fireresistance  rated  construction. 

780  CMR  408.0  PUBLIC  GARAGES 

408.1  General:  Public  garages  shall  comply  with 
the  applicable  requirements  of  780  CMR  408.0. 
Those  portions  of  public  garages  where  paint 
spraying  is  done  shall  comply  with  the  requirements 
of  780  CMR  419.0. 

408.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  408.0  and  as 
used  elsewhere  in  780  CMR  have  the  meanings 
shown  herein. 

Garage,  public  A  building  or  structure  for  the 
storage  or  parking  of  more  than  four  passenger 
motor  vehicles,  motor-powered  boats  or  private  or 
commercial  airplanes,  or  more  than  one 
commercial  motor  vehicle.  Public  garages  shall 
be  classified  in  one  of  the  following  groups 
according  to  their  specific  occupancies: 
Group  1:  A  public  garage  occupied  for  the 
storage,  parking,  repairing  or  the  painting  of,  or 
the  dispensing  of  fuel  to.  motor  vehicles. 
Group  2.  A  public  garage  occupied  exclusively 
for  passenger  vehicles  that  will  accommodate  not 
more  than  nine  passengers. 

408.3  Construction:  All  Group  I  public  garages 
hereafter  erected  shall  be  classified  as  Use  Group  S- 
1  and  all  Group  2  public  garages  shall  be  classified 
as  UseGroup  S-2;  both  shall  conform  to  the  height 
and  area  limitations  of  Table  503  except  as 
specifically  provided  for  herein. 

408.3.1  Sprinkler  system:  All  public  garages 
shall  be  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1: 

1.  Where  any  fire  area  exceeds  12,000  square 
feet  (11 16  nr); 

2.  Where  the  total  area  of  a\\fire  areas  on  all 
floors  exceeds  24.000  square  feet  (2232  nr); 

3 .  Where  any  fire  area  is  more  than  three 
stories  above  grade,  or 

4.  Where  located  beneath  other  use  groups. 


70 


780  CMR  -  Sixth  Edition 


2/7/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


For  the  purposes  of  780  CMR  408.0,  a  roof 
occupied  for  the  parking  or  storage  of  motor 
vehicles  shall  not  constitute  a  story. 

408.3.2  Roof  storage  of  motor  vehicles:  Where 
the  roof  of  a  building  is  occupied  for  the  parking 
or  storage  of  motor  vehicles,  such  roof  shall  be 
provided  with  a  parapet  wall  or  a  guard 
constructed  in  accordance  with  780  CMR  1021.0, 
and  with  a  wheel  guard  not  less  than  six  inches 
(152  mm)  in  height  that  is  located  so  as  to  prevent 
any  vehicle  from  striking  the  parapet  wall  or 
guard. 

408.3.3  Floor  construction:  The  floor  finish  of 
public  garages,  including  airplane  hangers,  shall 
be  of  concrete  or  other  approved  nonabsorbent, 
noncombustible  material. 

408.4  Fuel-dispensing  areas:  Fuel-dispensing  areas 
shall  be  located  on  the  level  nearest  grade.  Public 
garages  with  fuel-dispensing  areas  shall  be 
completely  separated  from  any  other  use  group  by 
fire  separation  assemblies  having  a  minimum 
fireresistance  rating  of  two  hours.  The  floors  of  the 
fuel-dispensing  areas  shall  be  graded  to  a  floor 
drainage  system  such  that  any  fuel  spill  or  leak  is 
contained  within  the  area.  The  drainage  system  shall 
conform  to  the  requirements  of  the  plumbing  code 
listed  in  Appendix  A.  The  fuel-dispensing  area  shall 
be  equipped  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  9. 

408.4.1  Fuel-dispensing  systems:  All  fuel- 
dispensing  and  fuel  storage  systems  shall  conform 
to  the  requirements  of  the  mechanical  code  listed 
in  Appendix  A. 

408.5  Ventilation:  All  public  garages  shall  be 
ventilated  in  accordance  with  the  mechanical  code 
listed  in  Appendix  A.  Fuel-dispensing  areas  shall  be 
mechanically  ventilated. 

408.6  Special  hazards:  Any  process  conducted  in 
conjunction  with  public  garages  which  involves 
volatile  flammable  solvents  shall  be  segregated  or 
located  in  a  detached  building  or  structure,  except  as 
provided  for  in  780  CMR  418.0  for  the  storage  and 
handling  of  gasoline  and  other  volatile  flammables. 
The  quantity  of  flammable  liquids  stored  or  handled 
in  public  garages  except  in  underground  storage 
tanks,  in  special  enclosures  where  permitted  in 
accordance  with  NFiPA  30A  and  the  fire  prevention 
code  listed  in  Appendix  A,  and  in  the  tanks  of  motor 
vehicles —  shall  not  be  more  than  five  gallons  (0.019 
m2)  in  approved  safety  cans. 

780  CMR  409.0  USE  GROUP  1-2 
409.1  General:  All  occupancies  in  Use  Group  1-2 
shall  comply  with  the  provisions  of  780  CMR  409.0 
and  all  other  applicable  provisions  of  780  CMR, 
except  that  780  CMR  409  0  shall  not  apply  to 


occupancies  in  Use  Group  1-2  that  are  not  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.0. 

Note:  Hospitals,  nursing  homes  and 
convalescent  homes  shall  be  constructed  of  Type 
1  construction,  in  accordance  with  M.G.L. 
c.  Ill,  §§51  and  71. 

409.2  Corridors:  All  corridors  in  occupancies  in 
Use  Group  1-2  shall  be  continuous  to  the  exits  and 
separated  from  all  other  areas  except  waiting  areas, 
nurses'  stations  and  mental  health  treatment  areas 
conforming  to  780  CMR  409.2.1  through  409.2.4. 

409.2.1  Waiting  areas:  Waiting  areas  shall  not  be 
open  to  the  corridor,  except  where  all  of-the 
following  criteria  are  met: 

1.  The  aggregate  area  of  waiting  areas  in  each 
smoke  compartment  does  not  exceed  600 
square  feet  (56m2); 

2.  Each  area  is  located  to  permit  direct  visual 
supervision  by  facility  staff; 

3.  Each  area  is  equipped  with  an  automatic 
fire  detection  system  installed  in  accordance 
with  780  CMR  918.0;  and 

4.  Each  area  is  arranged  so  as  not  to  obstruct 
access  to  the  required  exits. 

409.2.2  Waiting  areas  of  unlimited  area:  Spaces 
constructed  as  required  for  corridors  shall  not  be 
open  to  a  corridor,  except  where  all  of  the 
following  criteria  are  met: 

1.  The  spaces  are  not  occupied  for  patient 
sleeping  rooms,  treatment  rooms  or  specific 
occupancy  areas  as  defined  in  780  CMR 
302.1.1; 

2.  Each  space  is  located  to  permit  direct 
visual  supervision  by  the  facility  staff; 

3.  Both  the  space  and  corridors  that  the  space 
opens  into  in  the  same  smoke  compartment  are 
protected  by  an  automatic  fire  detection  system 
installed  in  accordance  with  780  CMR  918.0; 
and 

4.  The  space  is  arranged  so  as  not  to  obstruct 
access  to  the  required  exits. 

409.2.3  Nurses'  stations:  Spaces  for  doctors'  and 
nurses'  charting,  communications  and  related 
clerical  areas  shall  not  be  open  to  the  corridor, 
except  where  such  spaces  are  constructed  as 
required  for  corridors. 

409.2.4  Mental  health  treatment  areas:  Areas 
wherein  only  mental  health  patients  who  are 
capable  of  self-preservation  are  housed,  or  group 
meeting  or  multipurpose  therapeutic  spaces  other 
than  specific  occupancy  areas  as  defined  in 
780  CMR  302.1.1,  under  continuous  supervision 
by  facility  staff,  shall  not  be  open  to  the  corridor, 
except  where  all  of  the  following  criteria  are  met: 

1.  Each  area  does  not  exceed  1,500  square 
feet  (140  m2); 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


71 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2.  The  area  is  located  to  permit  supervision  by 
the  facility  staff; 

3.  The  area  is  arranged  so  as  not  to  obstruct 
any  access  to  the  required  exits; 

4.  The  area  is  equipped  with  an  automatic  fire 
detection  system  installed  in  accordance  with 
7S0CMR918.0; 

5.  Not  more  than  one  such  space  is  permitted 
in  any  one  smoke  compartment;  and 

6.  The  walls  and  ceilings  of  the  space  are 
constructed  as  required  for  corridors. 

409.3  Corridor  walls:  Corridor  walls  shall  form  a 
barrier  to  limit  the  transfer  of  smoke.  The  walls 
shall  extend  from  the  floor  to  the  underside  of  the 
floor  or  roof  deck  above  or  to  the  underside  of  the 
ceiling  above  where  the  ceiling  membrane  is 
constructed  to  limit  the  transfer  of  smoke. 

409.3.1  Corridor  doors:  Corridor  doors,  other 
than  those  in  a  wall  required  to  be  rated  by 
7S0  CMR  302.1.1  or  for  the  enclosure  of  a 
vertical  opening  or  an  exit,  shall  not  have  a 
required  fireresistance  rating  and  shall  not  be 
required  to  be  equipped  with  self-closing  or 
automatic-closing  devices,  but  shall  provide  an 
effective  barrier  to  limit  the  transfer  of  smoke  and 
shall  be  equipped  with  positive  latching.  Roller 
latches  are  not  permitted.  All  other  doors  shall 
conform  to  780  CMR  716.0. 

409.3.2  Locking  devices:  Locking  devices  which 
restrict  access  to  the  patient  room  from  the 
corridor,  and  which  are  operable  only  by  staff 
from  the  corridor  side,  shall  not  restrict  the  means 
of  egress  from  the  patient  room  except  for  patient 
rooms  in  mental  health  facilities.  Also  see 
780  CMR  1017.4.1.8(2). 

409.4  Smoke  barriers:  Smoke  barriers  shall  be 
provided  to  subdivide  every  story  used  by  patients 
for  sleeping  or  treatment  into  at  least  two  smoke 
compartments.  Such  stories  shall  be  divided  into 
smoke  compartments  with  an  area  of  not  more  than 
22,500  square  feet  (2092  nr)  and  the  travel  distance 
from  any  point  in  a  smoke  compartment  to  a  smoke 
barrier  door  shall  not  exceed  150  feet  (45720  mm). 
The  smoke  barrier  shall  be  in  accordance  with 
780  CMR  712.0. 

409.4.1  Refuge  area:  At  least  30  net  square  feet 
(2.8  nr)  per  patient  shall  be  provided  within  the 
aggregate  area  of  corridors,  patient  rooms, 
treatment  rooms,  lounge  or  dining  areas  and  other 
low-hazard  areas  on  each  side  of  each  smoke 
barrier.  On  floors  not  housing  patients  confined 
to  a  bed  or  litter,  at  least  six  net  square  feet  (0.56 
nr)  per  occupant  shall  be  provided  on  each  side  of 
each  smoke  barrier  for  the  total  number  of 
occupants  in  adjoining  smoke  compartments. 

409.4.2  Independent  egress:  A  means  of  egress 
shall  be  provided  from  each  smoke  compartment 


created  by  smoke  barriers  without  having  to 
return  through  the  smoke  compartment  from 
which  means  of  egress  originated. 

409.5  Automatic  sprinkler  system:  Smoke 
compartments  containing  patient  sleeping  rooms 
shall  be  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1.  Patient  sleeping  rooms  shall  be  equipped 
with  quick-response  sprinklers. 

409.5.1  Automatic  fire  detection:  Patient 
sleeping  rooms  in  nursing  homes  (both 
intermediate  care  and  skilled  nursing  facilities) 
and  detoxification  facilities  shall  be  provided  with 
a  smoke  detector  that  is  permanently  connected  to 
the  normal  power  supply  and  that  complies  with 
the  requirements  of  UL  217  or  UL  268  listed  in 
Appendix  A.  Such  detectors  shall  provide  a 
visual  display  on  the  corridor  side  of  each  patient 
room  and  shall  provide  an  audible  and  visual 
alarm  at  the  nursing  station  attending  that  room. 
Where  such  detectors  and  related  devices  are  not 
combined  with  the  nursing  call  system,  the 
detectors  shall  be  installed  in  accordance  with 
780  CMR  918.0. 

Exceptions: 

1 .  Smoke  detectors  are  not  required  in  patient 
rooms  equipped  with  automatic  door-closing 
devices  with  integral  smoke  detectors  on  the 
room  sides  installed  in  accordance  with  their 
listing,  provided  that  the  integral  detectors 
perform  the  required  alerting  function. 

2.  Patient-room  smoke  detectors  installed  in 
accordance  with  780  CMR  918.0  are  not 
required  to  activate  the  fire  protective  signaling 
system  where  the  visual  and  audible  alarms 
required  in  780  CMR  409.5. 1  are  provided. 

3.  Sleeping  rooms  of  a  child  care  facility  as 
specified  in  780  CMR  308.3. 1 . 

780  CMR  410.0  USE  GROUP  1-3 

410.1  General:  All  occupancies  in  Use  Group  1-3 
shall  comply  with  the  provisions  of  780  CMR  410.0 
and  all  other  applicable  provisions  of  780  CMR  (see 
780  CMR  308.4). 

410.2  Mixed  use  groups:  Portions  of  buildings  with 
an  occupancy  in  Use  Group  1-3  which  are  classified 
as  a  different  use  group  shall  meet  the  applicable 
requirements  of  780  CMR  for  such  use  groups. 
Where  security  operations  necessitate  the  locking  of 
required  means  of  egress,  provisions  shall  be  made 
for  the  release  of  occupants  at  all  times. 

410.3  Means  of  egress:  Except  as  modified  or  as 
provided  for  in  7S0  CMR  410.0,  the  provisions  of 
780  CMR  10  shall  apply. 

410.3.1  Door  width:  Doors  to  resident  sleeping 
rooms  shall  have  a  clear  width  of  not  less  than  28 
inches  (71 1  mm). 


72 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


410.3.2  Sliding  doors:  Where  doors  in  a  means  of 
egress  are  of  the  horizontal-sliding  type,  the  force 
to  slide  the  door  to  its  fully  open  position  shall  not 
exceed  50  pounds  (222  N)  with  a  perpendicular 
force  against  the  door  of  50  pounds  (222  N). 

410.3.3  Horizontal  exits:  Horizontal  exits  shall 
be  permitted  to  comprise  100%  of  the  exits 
required  provided  that  access  to  an  exit,  other  than 
a  horizontal  exit,  is  available  in  another  fire 
compartment  without  requiring  return  through  the 
compartment  of  origin.  At  least  six  square  feet 
(0.56  m2)  of  available  space  per  occupant  shall  be 
provided  on  each  side  of  the  horizontal  exit  for 
the  total  number  of  occupants  in  the  compartment 
served  by  that  exit. 

410.3.4  Spiral  stairs  and  alternating  tread 
stairways:  Spiral  stairs  that  conform  to  the 
requirements  of  780  CMR  1014.6.4  and 
alternating  tread  stairways  that  conform  to  the 
requirements  of  780  CMR  1014.6.6  are  permitted 
for  access  to  and  in  between  staff  locations. 

410.3.5  Exit  discharge:  Exits  are  permitted  to 
discharge  into  a  fenced  or  walled  courtyard. 
Enclosed  yards  or  courts  shall  be  of  a  size  to 
accommodate  all  occupants,  a  minimum  of  50  feet 
(15240  mm)  from  the  building  with  a  net  area  of 
15  square  feet  (1.4  m2)  per  person. 

410.3.6  Sallyports:  A  sallyport  shall  be  permitted 
in  a  means  of  egress  where  there  are  provisions 
for  continuous  and  unobstructed  passage  through 
the  sallyport  during  an  emergency  exiting 
condition.  A  sallyport  is  a  security  vestibule  with 
two  or  more  doors  where  the  intended  purpose  is 
to  prevent  continuous  and  unobstructed  passage 
by  allowing  the  release  of  only  one  door  at  a  time. 

410.3.7  Exit  stairways:  One  of  the  required  exit 
stairways  in  each  building  shall  be  permitted  to 
have  glazing  installed  in  doors  and  interior  walls 
at  each  landing  level  providing  access  to  the 
stairway,  provided  that  all  of  the  following 
conditions  are  met: 

1 .  The  stairway  shall  not  serve  more  than  four 
floor  levels. 

2.  Stair  doors  shall  not  be  less  than  3/i-hour 
fire  doors  complying  with  780  CMR  716.0. 

3.  The  total  area  of  glazing  at  each  floor  level 
shall  not  exceed  5,000  square  inches  (3.23  m2) 
and  individual  panels  of  glazing  shall  not 
exceed  1,296  square  inches  (0.84  m2). 

4.  The  glazing  shall  be  protected  on  both 
sides  by  an  automatic  sprinkler  system.  The 
sprinkler  system  shall  be  designed  to  wet 
completely  the  entire  surface  of  any  glazing 
affected  by  fire  when  actuated. 

5.  The  glazing  shall  be  in  a  gasketed  frame 
and  installed  in  such  a  manner  that  the  framing 
system  will  detlect  without  breaking  (loading) 
the  glass  before  the  sprinkler  system  operates 


6.  Obstructions,  such  as  curtain  rods,  drapery 
traverse  rods,  curtains,  drapes  or  similar 
materials  shall  not  be  installed  between  the 
automatic  sprinklers  and  the  glazing. 

410.4  Locks:  Egress  doors  are  permitted  to  be 
locked  in  accordance  with  the  applicable  use 
condition.  Doors  from  an  area  of  refuge  to  exterior 
are  permitted  to  be  locked  with  a  key  lock  the  in  lieu 
of  locking  methods  described  in  780  CMR  410.4.1. 
The  keys  to  unlock  the  exterior  doors  shall  be 
available  at  all  times  and  the  locks  shall  be  operable 
from  both  sides  of  the  door. 

410.4.1  Remote  release:  All  remote  release  of 
locks  on  doors  in  a  means  of  egress  shall  be 
provided  with  reliable  means  of  operation,  remote 
from  the  resident  living  areas,  to  release  locks  on 
all  required  doors.  In  Occupancy  Conditions  III 
or  IV,  the  arrangement,  accessibility  and  security 
of  the  release  mechanism(s)  required  for  egress 
shall  be  such  that  with  the  minimum  available 
staff  at  any  time,  the  lock  mechanisms  are  capable 
of  being  released  within  two  minutes. 

Exception:  Provisions  for  remote  locking  and 
unlocking  of  occupied  rooms  in  Occupancy 
Condition  IV  are  not  required  provided  that  not 
more  than  ten  locks  are  necessary  to  be 
unlocked  in  order  to  move  all  occupants  from 
one  smoke  compartment  to  an  area  of  refuge 
within  three  minutes.  The  opening  of  all 
necessary  locks  shall  be  accomplished  with  not 
more  than  two  separate  keys. 

410.4.2  Power-operated  doors  and  locks:  All 

power-operated  sliding  doors  or  power-operated 
locks  for  swinging  doors  shall  be  operable  by  a 
manual  release  mechanism  at  the  door,  and  either 
emergency  power  or  a  remote  mechanical 
operating  release  shall  be  provided. 

410.4.3  Redundant  operation:  Remote  release, 
mechanically  operated  sliding  doors  or  remote 
release,  mechanically  operated  locks  shall  be 
provided  with  a  mechanically  operated  release 
mechanism  at  each  door,  or  shall  be  provided  with 
a  redundant  remote  release  control. 

410.4.4  Relock  capability:  Doors  remotely 
unlocked  under  emergency  conditions  shall  not 
automatically  relock  when  closed  unless  specific 
action  is  taken  at  the  remote  location  to  enable 
doors  to  relock. 

410.4.5  Emergency  power:  Emergency  power  in 
accordance  with  527  CMR  12.00  as  listed  in 
Appendix  A  shall  be  provided  for  all  electrically 
power-operated  sliding  doors  and  power-operated 
locks. 

Exception:  Facilities  with  ten  locks  or  less 
complying  with  the  exception  to  780  CMR 
410.4.1. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


73 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


410.5  Vertical  openings:  Vertical  openings  shall  be 
enclosed  in  accordance  with  780  CMR  713.3. 

Exception:  A  floor  opening  between  floor  levels 
of  residential  housing  areas  is  permitted  without 
enclosure  protection  between  the  levels,  provided 
that  all  of  the  following  conditions  are  met: 

1.  The  entire  normally  occupied  areas  so 
interconnected  are  open  and  unobstructed  so  as 
to  enable  observation  of  the  areas  by 
supervisory  personnel. 

2.  Means  of  egress  capacity  is  sufficient  to 
provide  simultaneous  egress  for  all  occupants 
from  all  interconnected  levels  and  areas. 

3 .  The  height  difference  between  the  highest 
and  lowest  finished  floor  levels  shall  not 
exceed  23  feet  (7010  mm).  Each  story, 
considered  separately,  has  at  least  one-half  of 
its  individual  required  means  of  egress  capacity 
provided  by  exits  leading  directly  out  of  that 
story  without  traversing  another  story  within 
the  inter-connected  area. 

410.6  Smoke  barrier:  All  occupancies  in  Use 
Group  1-3  shall  have  smoke  barriers  complying  with 
780  CMR  712.0  to  divide  every  story  occupied  by 
residents  for  sleeping,  or  any  other  story  having  an 
occupant  load  of  50  or  more  persons,  into  at  least 
two  smoke  compartments. 

Exception:  Spaces  having  direct  exit  to  one  of  the 
following,  provided  that  the  locking  arrangement 
of  the  doors  involved  complies  with  the 
requirements  for  doors  at  the  compartment  barrier 
for  the  use  condition  involved: 

1.  A  public  way, 

2.  A  building  separated  from  the  resident 
housing  area  by  a  two-hour  fireresistance  rated 
assembly  or  50  feet  (15240  mm)  of  open  space;  or 

3.  A  secured  yard  or  court  having  a  holding 
space  50  feet  (15240  mm)  from  the  housing  area 
that  provides  six  square  feet  (0.56  nr)  or  more  of 
refuge  area  per  occupant  including  residents,  staff 
and  visitors. 

410.6.1  Smoke  compartments:  The  maximum 
number  of  residents  in  any  smoke  compartment 
shall  be  200.  The  travel  distance  to  a  door  in  a 
smoke  barrier  from  any  room  door  required  as  exit 
access  shall  not  exceed  150  feet  (45720  mm). 
The  travel  distance  to  a  door  in  a  smoke  barrier 
from  any  point  in  a  room  shall  not  exceed  200  feet 
(60960  mm). 

410.6.2  Refuge  area:  At  least  six  net  square  feet 
per  occupant  shall  be  provided  on  each  side  of 
each  smoke  barrier  for  the  total  number  of 
occupants  in  adjoining  smoke  compartments. 
This  space  shall  be  readily  available  whenever  the 
occupants  are  moved  across  the  smoke  barrier  in 
a  fire  emergency. 

410.6.3  Independent  egress:  A  means  of  egress 
shall  be  provided  from  each  smoke  compartment 


created  by  smoke  barriers  without  having  to 
return  through  the  smoke  compartment  from 
which  means  of  egress  originates. 

410.7  Subdivision  of  resident  housing  areas: 

Sleeping  areas  including  an  individual  cell  or 
dormitory  and  any  contiguous  day  room,  group 
activity  space  or  other  common  spaces  where 
residents  are  housed  shall  be  separated  from  all  other 
spaces  in  accordance  with  780  CMR  410.7.1  through 
410.7.4. 

410.7.1  Occupancy  Conditions  IH  and  IV:  Each 
sleeping  area  in  Occupancy  Conditions  HI  and  IV 
shall  be  separated  from  the  adjacent  common 
spaces  by  a  smoke-tight  partition  where  the  travel 
distance  from  the  dormitory  room  or  cell  through 
the  common  space  to  the  exit  access  corridor 
exceeds  50  feet  (15240  mm). 

410.7.2  Occupancy  Condition  V:  Each  sleeping 
area  in  Occupancy  Condition  V  shall  be  separated 
from  adjacent  sleeping  areas,  corridors  and 
common  spaces  by  a  smoke-tight  partition. 
Additionally,  common  spaces  shall  be  separated 
from  the  exit  access  corridor  by  a  smoke-tight 
partition. 

410.7.3  Openings  in  room  face:  The  aggregate 
area  of  all  openings  in  a  solid  sleeping  room  face 
in  Occupancy  Conditions  n,  III,  IV  and  V  shall 
not  exceed  120  square  inches  (77419  mm2).  The 
aggregate  area  shall  include  all  openings 
including  door  undercuts,  food  passes  and  grilles. 
All  openings  shall  be  not  more  than  36  inches 
(914  mm)  above  the  floor.  In  Occupancy 
Condition  V,  the  openings  shall  be  closable  from 
the  room  side. 

410.7.4  Smoke-tight  doors:  Doors  in  openings  in 
partitions  required  to  be  smoke  tight  by  780  CMR 
410.7  shall  be  substantial  doors,  of  construction 
that  will  resist  the  passage  of  smoke.  Latches  and 
door  closers  are  not  required  on  cell  doors. 

410.8  Windowless  buildings:  For  the  purposes  of 
780  CMR  410.8,  a  windowless  building  or  portion  of 
a  building  is  one  with  nonopenable  windows, 
windows  not  readily  breakable  or  without  windows. 
Windowless  buildings  shall  be  provided  with  vent 
openings,  smoke  shafts  or  an  engineered  smoke 
control  system  to  provide  ventilation  (mechanical  or 
natural)  for  each  windowless  smoke  compartment. 

780  CMR  41 1.0  MOTION  PICTURE 

PROJECTION  ROOMS,  SCREENING 

ROOMS  AND  SOUND  STAGES 

(Refer  to  M.G.L.  c.  143,  §  89  for  additional 
information  regarding  cellulose  nitrate  film  and 
Appendix  A  for  related  Code  of  Massachusetts 
Regulations  fCMR'sJ). 


74 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


411.1  General:  The  provisions  of  780  CMR  411.0 
shall  apply  to  rooms  in  which  ribbon-type  cellulose 
acetate  or  other  safety  film  is  utilized  in  conjunction 
with  electric  arc,  xenon  or  other  light-source 
projection  equipment  which  develops  hazardous 
gases,  dust  or  radiation.  Where  cellulose  nitrate  film 
is  utilized  or  stored,  such  rooms  shall  comply  with 
NFiPA  40  listed  in  Appendix  A. 

Every  motion  picture  machine  projecting  film  as 
mentioned  within  the  scope  of  780  CMR  41 1.0  shall 
be  enclosed  in  a  projection  room.  Appurtenant 
electrical  equipment,  such  as  rheostats,  transformers 
and  generators,  shall  be  within  the  projection  room 
or  in  an  adjacent  room  of  equivalent  construction. 
There  shall  be  posted  on  the  outside  of  each 
projection  room  door  and  within  the  projection  room 
itself,  a  conspicuous  sign  with  one-inch  (25  mm) 
block  letters  stating  "Safety  Film  Only  Permitted  in 
this  Room". 

411.2  Construction  of  projection  rooms:  Every 
projection  room  shall  be  of  permanent  construction 
consistent  with  the  construction  requirements  for  the 
type  of  building  in  which  the  projection  room  is 
located.  Openings  are  not  required  to  be  protected. 

The  room  shall  have  a  floor  area  of  not  less  than 
80  square  feet  (7.44  m2)  for  a  single  machine.  Each 
motion  picture  projector,  floodlight,  spotlight  or 
similar  piece  of  equipment  shall  have  a  clear 
working  space  of  not  less  than  30  inches  by  30 
inches  (762  mm  by  762  mm)  on  each  side  and  at  the 
rear  thereof,  but  only  one  such  space  shall  be 
required  between  two  adjacent  projectors.  The 
projection  room  and  the  rooms  appurtenant  thereto 
shall  have  a  ceiling  height  of  not  less  than  seven  feet 
six  inches  (2286  mm).  The  aggregate  of  openings 
for  projection  equipment  shall  not  exceed  25%  of  the 
area  of  the  wall  between  the  projection  room  and  the 
auditorium.  All  openings  shall  be  provided  with 
glass  or  other  approved  material,  so  as  to  close 
completely  the  opening. 
\ 

411.3  Projection  booth  and  equipment 
ventilation:  Projection  booths  and  equipment  shall 
be  ventilated  in  accordance  with  the  mechanical 
code  listed  in  Appendix  A. 

411.4  Lighting  control:  Provision  shall  be  made  for 
control  of  the  auditorium  lighting  and  the  means  of 
egress  lighting  systems  of  theaters  from  inside  of  the 
room  and  from  at  least  one  other  convenient  point  in 
the  building  as  required  in  780  CMR  1024.3.1. 

411.5  Miscellaneous  equipment:  Each  projection 
room  shall  be  provided  with  rewind  and  film  storage 
facilities. 

411.6  Screening  rooms:  Screening  rooms  shall 
provide  a  seating  capacity  of  not  more  than  30 
persons,  with  not  less  than  two  approved  means  of 
egress  complying  with  780  CMR  10.    Such  rooms 


shall  be  enclosed  in  one-hour  fire  separation 
assemblies.  All  seats  shall  be  permanently  fixed  in 
position  and  the  arrangement  shall  comply  with  the 
requirements  of  780  CMR  1012.0. 

411.7  Sound  stage  construction:  All  sound  stages 
for  motion  picture  or  television  productions  shall  be 
equipped  throughout  with  an  automatic  sprinkler 
system  installed  in  accordance  with  780  CMR  9. 

780  CMR  412.0  STAGES  AND  PLATFORMS 

412.1  Applicability:  The  provisions  of  780  CMR 
412.0  shall  apply  to  all  parts  of  buildings  and 
structures  which  contain  stages  or  platforms  and 
similar  appurtenances  as  herein  defined. 

412.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  412.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Platform:  A  platform  is  a  raised  area  within  a 
building  for:  the  presentation  of  music,  plays  or 
other  entertainment;  the  head  table  for  special 
guests;  the  raised  area  for  lectures  and  speakers; 
boxing  and  wrestling  rings;  theater-in-the-round; 
and  similar  purposes  wherein  there  are  no 
overhead  hanging  curtains,  drops,  scenery  or 
stage  effects  other  than  lighting.  A  temporary 
platform  is  one  installed  for  not  more  than  30 
days. 

Stage:  A  stage  is  a  partially  enclosed  portion  of  a 
building  which  is  designed  or  used  for  the 
presentation  of  plays,  demonstrations  or  other 
entertainment.  A  stage  shall  be  further  classified 
as  either  a  legitimate  stage,  regular  stage  or  thrust 
stage. 

Stage,  legitimate:  A  stage  wherein  curtains, 
drops,  leg  drops,  scenery,  lighting  devices  or  other 
stage  effects  are  retractable  horizontally  or 
suspended  overhead. 

Stage,  regular:  A  stage  wherein  curtains,  fixed 
leg  drops,  valances,   scenery  and  other  stage 
effects  are  hung  and  are  not  retractable. 
Stage,  thrust:  A  platform  extending  beyond  the 
proscenium  arch  and  into  the  audience. 

412.3  Stages:  Stage  construction  shall  comply  with 
780CMR412.3.1  through  412.3.9. 

412.3.1  Stage  floor  construction:  Openings 
through  all  stage  floors  shall  be  equipped  with 
tight-fitting,  solid  wood  trap  doors  not  less  than 
two  inches  in  nominal  thickness  with  approved 
safety  locks  or  other  materials  of  equal  physical 
and  fire  endurance  properties. 

412.3.1.1  Legitimate  stages:  Legitimate  stages 
shall  be  constructed  of  materials  as  required  for 
floors  for  the  type  of  construction,  but  not  less 
than  Type   IB  construction  except  that  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


75 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


portion  of  the  legitimate  stage  extending  back 
from  and  six  feet  (1829  mm)  beyond  the  full 
width  of  the  proscenium  opening  on  each  side 
shall  be  permitted  to  be  constructed  of 
noncombustible  or  heavy  timber  construction 
covered  with  a  wood  floor  of  not  less  than  two 
inches  nominal  in  thickness.  Except  for  the 
finished  floor,  combustible  construction  shall 
not  extend  beyond  the  plane  of  the  proscenium 
opening. 

412.3.1.2  Regular  and  thrust  stages:  Regular 
stages  and  thrust  stages  shall  be  constructed  of 
materials  as  required  for  floors  for  the  type  of 
construction  of  the  building  in  which  such 
stages  are  located. 

412.3.2  Stage  rigging  loft:  The  rigging  loft,  also 
referred  to  as  the  loft  or  fly,  is  the  space  over  the 
stage  where  scenery  and  equipment  is  out  of  view. 
The  fly  gallery  is  the  narrow  raised  platform  at  the 
side  of  the  legitimate  stage  from  which  the  lines 
for  flying  scenery  are  manipulated.  The  gridiron 
is  the  arrangement  of  beams  over  a  legitimate 
stage  supporting  the  machinery  for  flying  scenery 
and  hanging  battens  from  which  lighting  is  hung. 
The  pin  rail  is  the  beam  at  one  side  of  a  legitimate 
stage  through  which  wooden  or  metal  pins  are 
driven  and  to  which  lines  from  the  flies  are 
fastened.  The  rigging  loft,  fly  galleries,  gridiron 
and  pin  rails  shall  be  constructed  of  approved 
noncombustible  materials. 

412.3.3  Footlights  and  stage  electrical 
equipment:  Footlights  and  border  lights  shall  be 
installed  in  troughs  constructed  of  approved 
noncombustible  materials.  Ready  access  shall  be 
provided  at  all  times  to  the  switchboard.  The 
storage  or  placing  of  stage  equipment  against  the 
switchboard  shall  be  prohibited. 

412.3.4  Exterior  stage  doors:  Where  protection 
of  openings  is  required,  exit  discharge  door 
openings  to  the  outer  air  shall  be  protected  with 
fire  doors  that  comply  with  780  CMR  716.0.  All 
exterior  openings  which  are  located  on  the  stage 
for  means  of  egress  or  loading  and  unloading 
purposes,  and  which  are  likely  to  be  open  during 
occupancy  of  the  theater,  shall  be  constructed 
with  vestibules  to  prevent  air  drafts  into  the 
auditorium. 

412.3.5  Proscenium  wall:  Legitimate  stages  shall 
be  completely  separated  from  the  seating  area  by 
a  proscenium  wall  with  not  less  than  a  two-hour 
fireresistance  rating  extending  continuously  from 
the  foundation  to  the  roof.  There  shall  not  be 
other  openings  in  the  wall  separating  a  legitimate 
stage  from  the  auditorium  except:  the  main 
proscenium  opening;  two  doorways  at  the  stage 
level,  one  on  each  side  thereof;  and  one  doorway 
to  the  musician's  pit  from  the  space  below  the 
stage  floor.  Each  such  doorway  shall  not  exceed 
45  square  feet  (4.19  m2)  in  area  and  shall  be 


protected   with  fire   doors  that   comply   with 

780  CMR  716.0. 

412.3.5.1  Trim,  finish  and  decorative 
hangings:     All    moldings    and    decorations 

around    the    proscenium  opening    shall    be 

constructed  entirely  of  approved 
noncombustible  material. 

412.3.6  Proscenium  curtain:  The  proscenium 
opening  of  every  legitimate  stage  shall  be  provided 
with  a  curtain  of  approved  material  designed  and 
installed  to  intercept  hot  gases,  flames  and  smoke, 
and  to  prevent  a  glow  from  a  severe  fire  on  the  stage 
from  showing  on  the  auditorium  side  for  a  period  of 
30  minutes.  The  closing  of  the  curtain  from  the  full 
open  position  shall  be  effected  in  less  than  30 
seconds,  but  the  last  eight  feet  of  travel  shall  require 
not  less  than  five  seconds. 

412.3.6.1  Activation:  The  curtain  shall  be 
activated  by  rate-of-rise  heat  detection 
operating  at  a  rate  of  temperature  rise  of  15  to 
20°F  per  minute  (8°  to  1 1  °C  per  minute);  and 
by  an  auxiliary  manual  control. 

412.3.6.2  Fire  test:  A  sample  curtain  with  a 
minimum  of  two  vertical  seams  shall  be 
subjected  to  the  standard  fire  test  specified  in 
ASTM  El  19  listed  in  Appendix  A  for  a  period 
of  30  minutes.  The  curtain  shall  overlap  the 
furnace  edges  by  an  amount  that  is  appropriate 
to  seal  the  top  and  sides.  The  curtain  shall 
have  a  bottom  pocket  containing  a  minimum  of 
four  lbs.  per  linear  foot  (6  kg/m)  of  batten.  The 
exposed  surface  of  the  curtain  shall  not  glow, 
and  flame  or  smoke  shall  not  penetrate  the 
curtain  during  the  test  period.  Unexposed 
surface  temperature  and  hose  stream  test 
requirements  are  not  applicable  to  the 
proscenium  fire  safety  curtain  test. 

412.3.6.3  Smoke  test:  Curtain  fabrics  shall 
have  a  smoke-developed  rating  of  25  or  less 
when  tested  in  accordance  with  ASTM  E84 
listed  in  Appendix  A. 

412.3.6.4  Tests:  The  completed  proscenium 
curtain  shall  be  subjected  to  operating  tests 
prior  to  the  issuance  of  a  certificate  of 
occupancy. 

412.3.7  Scenery:  All  combustible  materials  used 
in  sets  and  scenery  shall  be  rendered  flame- 
resistant  to  comply  with  780  CMR  8. 

412.3.8  Stage  ventilation:  Emergency  ventilation 
shall  be  provided  for  stages  larger  than  1,000 
square  feet  (93  m  )  in  floor  area,  or  with  a  stage 
height  greater  than  50  feet  (15240  mm).  Such 
ventilation  shall  comply  with  780  CMR412.3.8.1 
or  412.3.8.2 

412.3.8.1  Roof  vents:  Two  or  more  vents 
constructed  to  open  automatically  by  approved 
heat-activated  devices  and  with  and  aggregate 
clear  opening  area  of  not  less  than  5%  of  the 


76 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


area  of  the  stage  shall  be  located  near  the 
center  and  above  the  highest  part  of  the  stage 
area,  except  as  otherwise  provided  for  in 
780  CMR  412.3.9.  Supplemental  means  shall 
be  provided  for  manual  operation  of  the 
ventilator.  Curbs  shall  be  provided  as  required 
for  skylights  in  780  CMR  2608.2. 
412.3.8.2  Smoke  control:  Smoke  control  in 
accordance  with  780  CMR  921.0  shall  be 
provided  to  maintain  the  smoke  layer  interface 
not  less  than  six  feet  (1829  mm)  above  the 
highest  level  of  the  assembly  seating  or  above 
the  top  of  the  proscenium  opening  where  a 
proscenium  wall  is  required  by  780  CMR 
412.3.5. 

412.3.9  Superimposed  theaters:  Additions  or 
extensions  shall  not  be  erected  over  the  stage 
section  of  a  theater,  nor  shall  a  second  theater  be 
erected  above  another.  Where  approved,  the 
prohibition  against  superimposed  theaters  and 
construction  above  the  stage  shall  not  apply 
where  approved  access  is  provided  for  fire 
fighting  with  direct  means  of  ventilation  to  the 
outer  air  from  the  stage  portion. 

412.4    Platforms:    Platform    construction    shall 
comply  with  780  CMR  412.4.1  and  412.4.2. 

412.4.1  Materials:  In  buildings  required  to  be  of 
Type  1  or  Type  2  construction  where  the 
platforms  are  not  more  than  30  inches  (762  mm) 
above  the  main  floor  level,  the  minimum  type  of 
construction  for  a  permanent  platform  shall  be 
Type  2C.  For  all  types  of  construction  where  the 
platforms  are  not  more  than  30  inches  (762  mm) 
above  the  main  floor  level,  not  larger  in  area  than 
10%  of  the  room  floor  area  and  not  more  than  200 
square  feet  (19  m2)  in  area;  the  minimum  type  of 
construction  for  a  permanent  platform  shall  be 
Type  5B  For  all  types  of  construction  where  the 
platforms  are  not  more  than  30  inches  (762  mm) 
above  the  main  floor  level,  not  larger  than  Va  of 
the  room  floor  area  and  not  more  than  3,000 
square  feet  (279  m2)  in  area,  the  minimum  type  of 
construction  for  a  permanent  platform  shall  be 
Type  4  or  the  platform  shall  be  constructed  of 
fireretardant-treated  wood.  All  other  permanent 
platforms  shall  be  constructed  of  approved 
materials  as  required  for  floors  for  the  required 
type  of  construction  of  the  building  in  which  it  is 
located.  Temporary  platforms  shall  be 
constructed  of  any  approved  material. 

412.4.2  Space  beneath:  The  space  between  the 
floor  and  a  temporary  platform  above  shall  not  be 
utilized  for  any  purpose  other  than  electrical 
wiring  to  platform  equipment.  Where  the  space 
between  the  floor  and  a  permanent  platform  above 
is  utilized  for  any  purpose  other  than  electrical 
wiring  or  plumbing,  the  platform  shall  provide  a 
one-hour  fireresistance  rating. 


412.5  Dressing  and  appurtenant  rooms:  Dressing 
and  appurtenant  rooms  shall  comply  with  780  CMR 
412.5.1  through  412.5.3. 

412.5.1  Construction:  Dressing  rooms,  scene 
docks,  property  rooms,  workshops,  storerooms 
and  all  compartments  appurtenant  to  the  stage 
shall  be  separated  from  each  other  and  from  the 
stage  and  all  other  parts  of  the  building  by  fire 
separation  assemblies  with  not  less  than  a  one- 
hour  fireresistance  rating  with  approved  opening 
protectives.  Such  rooms  shall  not  be  placed 
immediately  over  or  under  the  operating  stage 
area 

Exception:  Separation  from  the  stage  is  not 
required  for  stages  having  a  floor  area  of  500 
square  feet  (46.5  m2)  or  less. 

412.5.2  Opening  protectives:  Openings  other 
than  to  trunk  rooms  and  the  necessary  doorways 
at  stage  level  shall  not  connect  such  rooms  with 
the  stage,  and  such  openings  shall  be  protected 
with^re  doors  that  comply  with  780  CMR  716  0 

412.53  Dressing  room  and  stage  exits:  Each  tier 
of  dressing  rooms  shall  be  provided  with  at  least 
two  means  of  egress.  Means  of  egress  stairways 
from  dressing  and  storage  rooms  are  not  required 
to  be  enclosed  where  located  in  the  stage  area 
behind  the  proscenium  wall.  At  least  one 
approved  means  of  egress  shall  be  provided  from 
each  side  of  the  stage:  from  each  side  of  the  space 
under  the  stage;  from  each  fly  gallery;  and  from 
the  gridiron.  A  steel  ladder  shall  be  provided 
from  the  gridiron  to  a  scuttle  in  the  stage  roof. 

412.6  Automatic  sprinkler  system:  Stages  and 
enclosed  platforms  shall  be  equipped  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  412.0  and  780  CMR  906.0  or  780  CMR 
907.0.  The  system  shall  be  installed:  under  the  roof 
and  gridiron,  in  the  tie  and  fly  galleries  and  in  all 
places  behind  the  proscenium  wall  of  the  stage;  over 
and  within  enclosed  platforms  in  excess  of  500 
square  feet  (46.5  m2)  in  area;  and  in  dressing  rooms, 
lounges,  workshops  and  storerooms  accessory  to 
such  stages  or  enclosed  platforms. 

Exceptions: 

1.  Stages  or  enclosed  platforms  open  to  the 
auditorium  room  on  three  or  more  sides. 

2.  Altars,  pulpits  or  similar  platforms  and 
accessory  rooms 

3 .  Stage  gridirons  where  sidewall  sprinklers  with 
135°F  (57°C)  rated  heads  with  heat-baffle  plates 
are  installed  around  the  perimeter  of  the  stage 
except  for  the  proscenium  opening  at  points  not 
more  than  30  inches  (762  mm)  below  the  gridiron 
nor  more  than  six  inches  (152  mm)  below  the 
baffle  plate. 

4.  Under  stage  or  enclosed  platform  areas  less 
than  four  feet  (1219  mm)  in  clear  height  utilized 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


77 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


for  storage,  the  stage  and  supporting  structures 
shall  be  of  one-hour  fireresistance  rated 
construction. 

412.7  Standpipes:  A  wet  standpipe  system  in 
accordance  with  780  CMR  914.0  shall  be  provided 
and  equipped  with  1 '/2-inch  hose  connections  on 
each  side  of  the  stage. 

Exception:  Where  the  building  or  area  is 
equipped  throughout  with  an  automatic  sprinkler 
system,  the  hose  connections  that  are  supplied 
from  the  automatic  sprinkler  system  shall  have  a 
water  supply  of  not  less  than  that  required  by 
NFiPA  13  listed  in  Appendix  A. 

412.7.1  Hose  and  cabinet:  The  hose  connections 
shall  be  equipped  with  sufficient  lengths  of  1  Vi  - 
inch  hose  to  provide  fire  protection  for  the  stage 
area;  such  connections  shall  be  equipped  with  an 
approved  adjustable  fog  nozzle  and  be  mounted  in 
a  cabinet  or  a  rack. 

780  CMR  413.0  SPECIAL  AMUSEMENT 
BUILDINGS 

413.1  General:  Special  amusement  buildings  shall 
comply  with  the  requirements  for  buildings  of  the 
appropriate  assembly  use  group  in  addition  to  the 
requirements  of  780  CMR  413.0. 

Exception:  Buildings  or  portions  thereof  that  are 
essentially  open  to  the  outside  air,  such  as 
buildings  without  walls  or  without  a  roof  and 
arranged  to  prevent  the  accumulation  of  smoke  in 
the  building  or  structure  are  not  required  to 
comply  with  780  CMR  413.0. 

413.2  Special  amusement  building:  A  special 
amusement  building  is  any  temporary,  permanent  or 
mobile  building  or  portion  thereof  which  is  occupied 
for  amusement,  entertainment  or  educational 
purposes  and  which  contains  a  device  or  system 
which  conveys  passengers  or  provides  a  walkway 
along,  around  or  over  a  course  in  any  direction  so 
arranged  that  the  means  of  egress  path  is  not  readily 
apparent  due  to  visual  or  audio  distractions  or  is 
intentionally  confounded  or  is  not  readily  available 
due  to  the  nature  of  the  attraction  or  mode  of 
conveyance  through  the  building  or  structure. 

413.3  Fire  detection:  All  special  amusement 
buildings  shall  be  equipped  with  an  automatic  fire 
detection  system  in  accordance  with  780  CMR 
918.0. 

Exception:  In  areas  where  the  ambient  conditions 
will  cause  a  smoke  detector  to  activate,  an 
approved  alternative  type  of  automatic  detector 
shall  be  installed. 

413.4  Automatic  sprinklers:  All  special  amusement 
buildings  shall  be  equipped  throughout  with  an 
automatic   sprinkler  system    in   accordance   with 


780  CMR  906.0.  Where  the  special  amusement 
building  is  temporary  or  mobile,  the  sprinkler  water 
supply  shall  be  of  an  approved  temporary  means. 

Exception:  An  automatic  sprinkler  system  is  not 
required  where  the  total  floor  area  of  a  temporary 
special  amusement  building  is  less  than  1,000 
square  feet  (93  m  )  and  the  travel  distance  from 
any  point  to  an  exit  is  less  than  50  feet  (15240 
mm). 

413.5  System  response:  The  activation  of  the 
automatic  fire  detection  system  within  a  single 
protected  area  or  the  automatic  sprinkler  system 
shall  automatically: 

1 .  Cause  illumination  of  the  means  of  egress 
with  light  of  not  less  than  one  footcandle  (10.76 
lux)  at  the  walking  surface  level; 

2.  Stop  any  conflicting  or  confusing  sounds  and 
visual  distractions;  and 

3 .  Activate  an  approved  directional  exit  marking 
that  will  become  apparent  in  an  emergency. 

413.5.1  Alarm:  Activation  of  any  single  smoke 
detector,  the  automatic  sprinkler  system  or  any 
other  automatic  fire  detection  device  shall 
immediately  sound  an  alarm  at  the  building  at  a 
constantly  attended  location  from  which 
emergency  action  can  be  initiated  including  the 
capability  of  manual  initiation  of  requirements  in 
780  CMR  413.5. 

413.5.2  Public  address  system:  A  public  address 
system,  which  is  also  permitted  to  serve  as  an 
alarm  system,  shall  be  provided  and  shall  be 
audible  throughout  the  entire  special  amusement 
building. 

413.5.3  Exit  marking:  "Exit"  signs  shall  be 
installed  at  required  exit  doorways.  Approved 
directional  exit  markings  shall  also  be  provided 
and  shall  include  signs  as  required  by  780  CMR 
1023  0.  Where  mirrors,  mazes  or  other  designs 
are  used  that  confound  the  means  of  egress  paths, 
approved  low-level  "exit"  signs  and  directional 
path  markings  shall  be  provided  and  located  not 
more  than  eight  inches  (203  mm)  above  the 
walking  surface  and  on  or  near  the  means  of 
egress  path.  Such  markings  shall  become  visible 
when  activated  in  accordance  with  780  CMR 
413.5,  item  3. 

413.6  Interior  finish:  The  interior  finish  shall  be 
Class  I  in  accordance  with  780  CMR  803.2. 

780  CMR  414.0  AIRPORT  TRAFFIC 
CONTROL  TOWERS 

414.1  General:  The  provisions  of  780  CMR  414.0 
shall  apply  to  airport  traffic  control  towers  not 
exceeding  1,500  square  feet  per  floor  occupied  only 
for  air  traffic  control,  electrical  and  mechanical 
equipment   rooms,   radar  and   electronics  rooms, 


78 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


office  spaces  incidental  to  tower  operation  and 
lounges  for  employees,  including  restrooms. 

414.2  Type  of  construction:  Air  traffic  control 
towers  shall  be  constructed  to  conform  to  the  height 
and  area  limitations  of  Table  414.2. 

Table  414.2 
HEIGHT  AND  AREA  LIMITATIONS  FOR 
AIRPORT  TRAFFIC  CONTROL  TOWERS 


Type  of 
construction 

Height 

Maximum  area 
(square  feet) 

1A,  IB 
2A 
■  .    2B 
2C 

Unlimited 
240  feet 
100  feet 
85  feet 

1,500 
1,500 
1,500 
1.500 

Note  a.    Height  to  be  measured  from  grade  to  cab 

floor.  . 

Note  b.   1  foot  -  304.8  mm;  1  square  food  =  0.093m  . 

414.3  Egress:  A  minimum  of  one  exit  stairway  shall 
be  permitted  for  airport  traffic  control  towers  of  any 
height  provided  that  the  occupant  load  per  floor  does 
not  exceed  15.  The  stairway  shall  conform  to  the 
requirements  of  780  CMR  1014.0  and  1015.0.  The 
stairway  shall  be  separated  from  elevators  by  a 
minimum  distance  of  Vi  of  the  diagonal  of  the  area 
served. 

Exception:  Smokeproof  enclosures  as  set  forth  in 
780  CMR  1015.0  are  not  required  where  required 
stairways  are  pressurized  to  a  minimum  of  0.15 
inch  of  water  column  (37.33  P)  and  a  maximum  of 
0.35  inch  of  water  column  (87. 10  P)  in  the  shaft 
relative  to  the  building  with  all  stairway  doors 
closed. 

414.4  Automatic  fire  detection  systems:  Airport 
traffic  control  towers  shall  be  provided  with  an 
automatic  fire  detection  system  installed  in 
accordance  with  780  CMR  918.0. 

414.5  Standby  power:  A  standby  power  system  that 
conforms  to  780  CMR  403.9  and  527  CMR  12.00  as 
listed  in  Appendix  A  shall  be  provided  in  airport 
traffic  control  towers  more  than  65  feet  (19812  mm) 
in  height.  Power  shall  be  provided  to  mechanical 
equipment  servicing  smokeproof  enclosures  and 
stairway  pressurization  systems,  means  of  egress 
lighting,  elevator  operational  equipment  and  the 
automatic  fire  detection  system. 

780  CMR  415.0  OUTDOOR  PROCESSING 
FACnJTIES 

415.1  Industry  standards:  Outdoor  processing 
facilities  such  as  chemical  plants,  refineries  and 
grain  elevators  shall  be  constructed  in  accordance 
with  the  accepted  engineering  practice  of  the 
specific  industry  and  the  fire  prevention  code  listed 
in  Appendix  A,  subject  to  the  approval  of  the  the 
building  code  enforcement  official  and  the  fire 
prevention  officer. 


780  CMR  416.0  HPM  FACILITIES 

416.1  Scope:  The  provisions  of  780  CMR  416.0 
shall  apply  to  buildings  and  structures  using 
hazardous  production  materials  {HPM),  such  as  in 
semiconductor  fabrication  facilities  and  areas  of 
comparable  research  and  development.  Except  as 
specifically  required  by  780  CMR  416.0,  such 
buildings  shall  comply  with  the  applicable 
requirements  of  780  CMR.  The  specific  code 
provisions  of  780  CMR  307.0,  506.3  and  Table 
1009.2  applicable  to  high-hazard  use  groups  shall 
not  apply  unless  stated  herein. 

416.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  416.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Emergency  control  station:  An  approved  location  on 
the  premises  where  signals  from  emergency 
equipment  are  received  and  which  is  staffed  by 
trained  personnel. 

Fabrication  area:  A  fabrication  area  is  one  in  which 
there  are  processes  involving  hazardous 
production  materials  {HPM),  and  includes 
ancillary  rooms  or  areas,  such  as  dressing  rooms 
and  offices,  which  are  supplemental  to  the  area 
processes. 

Hazardous  production  material  (HPM):  A  solid, 
liquid  or  gas  that  has  a  degree  of  hazard  rating  in 
health,  flammability  or  reactivity  of  Class  3  or  4 
as  ranked  by  NFiPA  704  listed  in  Appendix  A  and 
which  is  used  directly  in  research,  laboratory  or 
production  processes  which  have  as  their  end 
product,  materials  which  are  not  hazardous. 

Service  passage,  HPM:  A  passage  in  which 
hazardous  production  materials  {HPM)  are 
transported  from  a  separate  inside  HPM  storage 
room  or  the  exterior  of  the  building  to  the 
perimeter  wall  of  the  fabrication  area,  for 
purposes  other  than  required  means  of  egress. 

Storage  room,  HPM,  separate  inside:  A  room  in 
which  hazardous  production  materials  {HPM)  are 
stored  in  containers,  tanks,  drums  or  other  means, 
and  which  is  separated  from  other  occupancies. 
Such  rooms  include: 

HPM  cutoff  room:  An  HPM  storage  room  within 
a  building  and  having  at  least  one  exterior  wall. 
HPM  inside  room:  An  HPM  storage  room  totally 
enclosed  within  a  building  and  not  having  exterior 
walls. 

416.3  Allowable  heights,  stories  and  area:  The 

allowable  height,  number  of  stories  and  basic  areas 
permitted  for  HPM  buildings  and  structures  shall  not 
exceed  the  limitations  specified  in  Table  416.3.  The 
provisions  of  780  CMR  507  0  shall  not  apply.   The 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


79 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


area  limitations  are  for  one-  or  two-story  buildings 
facing  on  a  street  or  public  space  not  less  than  30 
feet  (9144  mm)  wide.  The  increases  permitted  in 
780  CMR  506.2  and  506.3  shall  apply. 

Table  416.3 

HEIGHT,  NUMBER  OF  STORIES  AND 

AREA  LIMITATIONS  FOR  HPM  USE 

FACILITIES 


Type  of 
construction 

Number  of 
stories 

Height  (feet)3 

Area  (square 
feet/floor) 

lAand  IB 

3 

55 

Unlimited 

2A 

3 

55 

34,200 

2B 

3 

55 

22,500 

2C 

3 

40 

14,400 

3A 

3 

50 

19,800 

3B 

3 

40 

14,400 

4 

3 

55 

21,600 

5A 

3 

40 

15,300 

5B 

2 

30 

7.200 

Note  a.   1  foot  =  304.8  mm;  1  square  foot  =  0.093  nr 

416.4  Fire  suppression:  HPM  facilities  shall  be 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  9.  The  design 
for  the  fabrication  areas,  service  passages,  separate 
inside  HPM  storage  rooms  without  dispensing,  and 
means  of  egress  corridors  shall  meet  the 
requirements  for  Ordinary  Hazard  Group  2  in 
NFiPA  13  listed  in  Appendix  A.  The  design  for 
separate  inside  HPM  storage  rooms  with  dispensing 
shall  meet  the  requirements  for  Extra  Hazard  Group 
2  in  NFiPA  13  listed  in  Appendix  A. 

416.5  Amount  of  HPM  in  a  fabrication  area:  The 

total  amount  of  HPM  permitted  in  a  single 
fabrication  area  shall  be  based  on  the  densities  in 
Table  416.5(2),  or  the  quantities  in  Table  416.5(1), 
whichever  is  the  larger  amount. 


Table  416.5(1) 

PERMITTED  AMOUNTS  OF  HPM  IN  A 

SINGLE  FABRICATION  AREA- 

QUANTITY  BASIS 

Material  Maximum  quantity 


Flammable  liquids 

Class  I-A 

Class I-B 

Class  I-C 
Combination  flammable  liquids 

containing  not  more  than  the  exempt 

amounts  of  Class  I-A,  I-B  or  I-C 

flammable  liquids 
Combustible  liquids 

Class  n 

Class  III-A 
Flammable  gases 


Liquefied  flammable  gases 
Flammable  solids 
Corrosive  liquids 
Oxidizing  material  -  gases 
Oxidizing  material  -  liquids 
Oxidizing  material  -  solids 
Organic  peroxides 
Highly  toxic  material  and  poisonous  j 


90  gallons 
160  gallons 
270  gallons 


360  gallons 

360  gallons 

750  gallons 

9,000  cubic  feet  at 

one  atmosphere  of 

pressure  at  70°F 

180  gallons 

1 ,500  pounds 

165  gallons 

18,000  cubic  feet 

150  gallons 

1 ,500  pounds 

30  pounds 

Included  in  the 

aggregate  for 

flammables  as  noted 

above 


Note  a.    1  gallon  -  0.00379  m  ;  1  cubic  foot  =  0.028  m3; 
1  pound  =  0.454  kg;  degrees  C  =  {(degrees  F)-32}/1.8. 


Table  416.5(2) 

PERMITTED  AMOUNTS  OF  HPM  IN  A 

SINGLE  FABRICATION  AREA— DENSITY 

BASIS  a'  C 


State 

Units 

Flam- 
mable 

Oxi- 
dizer 

Cor- 
rosive 

Solid 

Liquid 

Gas 

Pounds  per  aquare  foot 
Gallons  per  square  foot 

Cubic  feet  per  square  foot 

0.001 
0.04b 
1  250 

0.003 
0.03 

1250 

0.003 
0.08 
3.000 

Note  a.    HPM  within  piping  shall  not  be  included  in  the 

calculated  quantities. 

Note  b.  The  maximum  permitted  quantities  of  flammable 

and  combustible  liquids  shall  not  exceed  the  following 

quantities: 

Class  (I-A)  +  (I-B)  +  (I  -  C)  (combination 

flammable  liquids  =  .025 

However  Class  I-A  shall  not  exceed  =  .0025 

Class  II  =  01 

Class  III-A  =  .02 

Note  c.  Highly  toxic  materials  and  poisonous  gases 
shall  be  limited  by  the  maximum  quantities  specified  in 
Table  416.5(1). 

Note  d.  Ten  pound  per  square  foot  =  4.882  kg/m2;  1 
gallon  per  square  foot  =  0.0407  m7m2;  1  cubic  foot  per 
square  foot  =  0.301  m3/m2. 


80 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


416.6  Egress:  There  shall  not  be  less  than  two 
means  of  egress  provided  for  any  fabrication  area  or 
any  HPM  facility  subdivision  thereof  larger  than  200 
square  feet  (18.62  m2).  The  maximum  length  of  exit 
access  travel  in  HPM  facilities  shall  be  100  feet 
(30480  mm). 

416.7  Separation:  Fabrication  areas  shall  be 
separated  from  each  other,  from  means  of  egress 
corridors,  and  from  other  parts  of  the  building  by 
not  less  than  one-hour  fire  separation  assemblies  in 
compliance  with  780  CMR  709.0,  with  fire  doors 
complying  with  780  CMR  716.0.  Floors  forming 
part  of  the  required  separation  shall  be  liquid  tight. 

416.8  Floors:  Floors  within  fabrication  areas  shall 
be  of  approved  noncombustible  construction. 
Unprotected  openings  through  floors  of  fabrication 
areas  are  permitted  where  the  interconnected  levels 
are  used  solely  for  mechanical  equipment  directly 
related  to  such  fabrication  areas. 

Mechanical,  duct  and  piping  penetrations  within 
a.  fabrication  area  shall  not  extend  through  more 
than  two  floors.  Penetrations  shall  be  effectively 
frestopped  in  accordance  with  780  CMR  720.6.4  at 
the  floor  level.  The  fabrication  area,  including  the 
areas  through  which  ductwork  and  piping  extend, 
shall  be  considered  a  single  conditioned  space  or  fire 
area. 

416.9  Ventilation,  general:  Ventilation  systems 
shall  comply  with  the  mechanical  code  listed  in 
Appendix  A  except  as  otherwise  provided  herein. 
Ventilation,  including  recalculated  air,  shall  be 
provided  throughout  the  fabrication  area  at  the  rate 
of  not  less  than  lcfrn  per  square  foot  (5074 
cm3/s/m2)  of  floor  area. 

416.9.1  Interconnection:  The  exhaust  system  of 
one  fabrication  area  shall  not  connect  to  another 
exhaust  system  outside  that  fabrication  area 
within  the  building.  The  return  air  system  from 
one  fabrication  area  shall  not  connect  to  any 
other  system. 

416.9.2  Smoke  detectors:  Smoke  detectors  shall 
be  installed  in  the  recirculating  air  stream  and 
shall  initiate  a  signal  at  the  emergency  control 
station. 

416.9.3  ShutofT switches:  Automatic  shutoffs  are 
not  required  to  be  installed  on  air-moving 
equipment.  A  manually  operated  remote  switch 
to  shut  off  the  fabrication  area  supply  or  the 
recirculation  air  system,  or  both,  shall  be  provided 
at  an  approved  location  outside  the  fabrication 
area. 

416.9.4  Gas  detection:  Where  HPM  gas  is  used 
or  dispensed  and  the  physiological  warning 
properties  for  the  gas  are  at  a  higher  level  than  the 
accepted  permissible  exposure  limitation  for  the 
gas,  a  continuous  gas-monitoring  system  shall  be 


provided  to  detect  the  presence  of  a  short-term 
hazard  condition.  Where  dispensing  occurs  and 
flammable  gases  or  vapors  are  liberated  in 
quantities  exceeding  20%  of  the  lower  explosive 
limitation,  a  continuous  gas-monitoring  system 
shall  be  provided.  The  monitoring  system  shall 
be  connected  to  the  emergency  control  station. 

416.10  Transporting  HPM:  HPM  shall  be 
transported  to  fabrication  areas  through  enclosed 
piping  or  tubing  systems  which  comply  with 
780  CMR  416.15,  through  service  passages,  or  in 
means  of  egress  corridors  as  permitted  in  the 
exception  to  780  CMR  416. 12. 

416.11  Electrical:  Electrical  equipment  and  devices 
within  the  fabrication  area  shall  comply  with 
NFiPA  70  listed  in  Appendix  A.  The  requirements 
for  hazardous  locations  are  not  required  to  be 
applied  where  the  average  rate  of  air  change  is  at 
least  four  cfm  per  square  foot  (20300  cm3/s/m2)  of 
floor  area  and  where  the  rate  of  air  change  at  any 
location  is  not  less  than  three  cfm  per  square  foot 
(15200  cmVs/m2). 

416.12  Means  of  egress  corridors:  Means  of  egress 
corridors  shall  comply  with  780  CMR  1011.4  and 
shall  be  separated  from  fabrication  areas  as 
specified  in  780  CMR  416.7.  Means  of  egress 
corridors  shall  not  be  used  for  transporting  HPM 
except  as  provided  for  in  780  CMR  416.12.1  and 
416.15.2. 

416.12.1  Existing  facilities:  In  existing  HPM 
facilities,  when  there  are  alterations  or 
modifications  to  existing  fabrication  areas,  the 
transportation  of  HPM  in  means  of  egress 
corridors  shall  be  permitted  provided  that  all  of 
the  requirements  of  780  CMR  416.12.1.1  and 
416.12.1.2  are  met. 

416.12.1.1  Corridors:  Corridors  adjacent  to 
the  fabrication  area  under  alteration  shall 
comply  with  Table  602,  item  4,  for  a  length 
determined  as  follows: 

1.  The  length  of  the  common  wall  of  the 
corridor  and  that  fabrication  area,  and 

2.  For  the  distance  along  the  corridor  to 
the  point  of  entry  of  HPM  mto  the  corridor 
serving  that  fabrication  area. 

416.12.1.2  Openings:  There  shall  not  be 
openings  between  the  corridor  and  an  HPM 
storage  cabinet  in  a  fabrication  area  other  than 
those  in  compliance  with  all  of  the  following. 

1.  one-hour  fire  doors  are  installed 
between  the  corridor  and  the  cabinet; 

2.  The  cabinet  is  separated  from  the 
corridor  with  a  one-hour  fireresistance  rated 
fire  partition,  and 

3.  Automatic  sprinklers  shall  be  provided 
inside  the  cabinets 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


416.13  Service  passages:  Service  passages  shall  be 
considered  as  HPM  facilities.  Service  passages  shall 
be  separated  from  means  of  egress  corridors  as 
required  by  780  CMR  416.7. 

416.13.1  Ventilation:  Service  passages  shall  be 
ventilated  as  required  by  780  CMR  416.9. 

416.13.2  Egress:  There  shall  not  be  less  than  two 
means  of  egress  from  a  service  passage.  Not 
more  than  one-half  of  the  required  means  of 
egress  shall  be  into  the  fabrication  area.  Doors 
from  service  passages  shall  be  self-closing  and 
swing  in  the  direction  of  means  of  egress  travel. 

416.13.3  Travel  distance:  The  maximum  distance 
of  travel  from  any  point  in  a  service  passage  to  an 
exit  or  door  into  a  fabrication  area  shall  not 
exceed  75  feet  (22860  mm).  Dead  ends  shall  not 
exceed  four  feet  (1219  mm)  in  length. 

416.13.4  Alarms:  Alarms  shall  be  provided  for  in 
accordance  with  780  CMR  416. 14.5. 

416.14  Storage  of  HPM,  general:  Rooms  used  for 
the  storage  of  HPM  in  quantities  greater  than  those 
set  forth  in  Tables  307.8(1)  and  307.8(2),  except  for 
those  quantities  permitted  within  a  fabrication  area, 
shall  comply  with  the  provisions  of  NFiPA  30  listed 
in  Appendix  A,  provided  that  the  area  of  an  HPM 
cutoff  room  shall  not  exceed  6,000  square  feet  (558 
m2).  The  storage  area  for  any  liquid  HPM  shall  be 
provided  with  drains. 

416.14.1  Location  within  building:  Where  HPM 
cutoff  rooms  are  provided,  such  rooms  shall  not 
be  less  than  30  feet  (9144  mm)  from  lot  lines. 

416.14.2  HPM  drainage  systems:  Drainage 
systems  shall  be  provided  to  direct  liquid  leakage 
and  fire  protection  water  to  a  safe  location  away 
from  the  building,  important  valves  or  adjoining 
property.  HPM  flammable  liquid  drains  shall  be 
separated  from  other  HPM  liquid  drains  Other 
HPM  liquids  in  drains  that  are  not  compatible 
shall  be  separated  from  each  other,  provided  that 
the  liquids  are  permitted  to  be  combined  when 
such  liquids  have  been  rendered  acceptable  for 
discharge  by  an  approved  means  into  the  public 
sewers. 

416.14.3  Egress:  There  shall  be  two  means  of 
egress  from  a  separate  inside  HPM  storage  room 
where  the  room  exceeds  200  square  feet  (186  m2) 
in  area.  Where  two  means  of  egress  are  required 
from  HPM  cutoff  rooms,  one  shall  be  directly  to 
the  outside  of  the  building.  All  storage  room 
means  of  egress  doors  shall  be  self-closing  and 
swing  in  the  direction  of  means  of  egress  travel 

416.14.4  Ventilation:  Exhaust  ventilation  shall  be 
provided  for  in  accordance  with  780  CMR  416.9 
for  all  categories  of  HPM. 

416.14.5  Emergency  alarm:  An  emergency 
telephone  system  or  local  fire  protective  signaling 


system  station  shall  be  installed  outside  of  each 
interior  egress  door  from  HPM  cutoff  rooms.  The 
signal  shall  be  relayed  to  the  emergency  control 
station  and  a  local  signaling  device  provided. 

416.14.6  Electrical:  HPM  cutoff  rooms 
containing  flammable  liquids  or  gases  shall  be 
classified  as  Class  I,  Division  1,  hazardous 
locations  in  accordance  with  NFiPA  70  listed  in 
Appendix  A. 

416.14.7  Gas  detection:  Gas  detection  shall  be 
provided  for  in  accordance  with  780  CMR 
416.9.4. 

416.15  Piping  and  tubing:  HPM  piping  and  tubing 
shall  comply  with  780  CMR  416.15  and  shall  be 
installed  in  accordance  with  ASME  B31.3  listed  in 
Appendix  A. 

416.15.1  General;  Piping  and  tubing  systems 
shall  be  metallic  unless  the  material  being 
transported  is  incompatible  with  such  system. 
Systems  supplying  gaseous  HPM,  having  a  health 
hazard  of '3  or  4  as  ranked  by  NFiPA  704  listed  in 
Appendix  A,  shall  be  welded  throughout,  except 
for  connections,  valves  and  fittings  which  are 
within  an  exhausted  enclosure.  HPM  supply 
piping  or  tubing  in  service  passages  shall  be 
exposed  to  view. 

416.15.2  Installation  in  egress  corridors  or 
above  other  use  groups:  HPM  shall  not  be 
located  within  means  of  egress  corridors  or  above 
areas  not  containing  HPM  facilities  except  as 
permitted  by  780  CMR  416.15.  HPM  piping  and 
tubing  shall  be  permitted  within  the  space  defined 
by  the  walls  of  means  of  egress  corridors  and  the 
floor  or  roof  above,  or  in  concealed  spaces  above 
other  use  groups  under  the  following  conditions: 

1.  Automatic  sprinklers  shall  be  installed 
within  the  space  unless  the  space  is  less  than  6 
inches  (152  mm)  in  least  dimension. 

2.  Ventilation  at  not  less  than  six  air  changes 
per  hour  shall  be  provided.  The  space  shall  not 
be  used  to  convey  air  from  any  other  area. 

3.  All  HPM  supply  piping  and  tubing  and 
HPM  non-metallic  waste  lines  shall  be 
separated  from  the  means  of  egress  corridor 
and  from  any  use  group  other  than  an  HPM  use 
facility  by  afire  separation  assembly  having  a 
fireresi  stance  rating  of  not  less  than  one  hour. 
Where  gypsum  wallboard  is  used,  joints  on  the 
piping  side  of  the  enclosure  are  not  required  to 
be  taped,  provided  that  the  joints  occur  over 
framing  members. 

4.  Where  piping  or  tubing  is  used  to  transport 
HPM  liquids,  a  receptor  shall  be  installed 
below  such  piping  or  tubing.  The  receptor 
shall  be  designed  to  collect  and  drain  any 
discharge  or  leakage  to  an  approved  location. 
The  one-hour  enclosure  required  by  780  CMR 


82 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


416.15.2,  item  3  shall  not  be  used  as  part  of  the 
receptor. 

5.  Manual  or  automatic  remotely  activated 
fail-safe  emergency  shutoff  valves,  with  ready 
access  thereto,  shall  be  installed  on  piping  and 
tubing,  other  than  waste  lines,  at  branch 
connections  into  the  fabrication  area,  and  at 
entries  into  means  of  egress  corridors. 

6.  Where  HPM  supply  gas  is  carried  in 
pressurized  piping,  a  fail-safe  system  for 
excess  flow  control  shall  shut  off  flow  due  to  a 
rupture  in  the  piping. 

7  Electrical  wiring  and  equipment  located  in 
the  piping  space  shall  be  approved  for  Class  I, 
Division  2,  hazardous  locations  in  accordance 
with  NFiPA  70  listed  in  Appendix  A 
8.  Gas  detection  shall  be  as  provided  for  in 
780  CMR  416.9.4 

Exception:  Conditions  1  through  8  shall  not 
apply  to  transverse  crossings  of  the 
corridors  by  supply  piping  that  is  coaxially 
enclosed  within  a  ferrous  pipe  or  tube  for 
the  width  of  the  corridor.  An  enclosing 
pipe  or  tube  open  to  an  HPM  use  facility  is 
permitted. 

416.15.3  Identification:  Piping,  tubing  and  HPM 
waste  lines  shall  be  identified  in  accordance  with 
ASME  A13. 1  listed  in  Appendix  A. 

780  CMR  417.0  HAZARDOUS  MATERIALS 

(See  also  780  CMR  426.0  for  the  design  and 
constriction  of  Bulk  Merchandising  Retail 
Buildings.) 

417.1  General:  The  provisions  of  780  CMR  417.0 
shall  apply  to  all  buildings  and  structures  occupied 
for  the  manufacturing,  processing,  dispensing,  use  or 
storage  of  hazardous  materials  All  buildings  and 
structures  with  an  occupancy  in  Use  Group  H  shall 
also  comply  with  the  applicable  provisions  of 
780  CMR  418.0  and  the  fire  prevention  code  listed 
in  Appendix  A. 

Note:  The  safe  design  of  hazardous  material 
occupancies  is  material  dependent.  Individual 
material  requirements  are  also  found  in  780  CMR 
307.0  and  418.0,  and  in  the  mechanical  and  fire 
prevention  codes  listed  in  Appendix  A.  Since  the 
fire  department  is  responsible  for  inspection  of 
these  occupancies  for  proper  utilization  and 
handling  of  hazardous  materials,  the 
administrative  authority  shall  cooperate  with  the 
fire  department  in  the  discharge  of  the 
responsibility  to  enforce  780  CMR  417.0 

417.2  Control  areas/exempt  amounts:  Control 
areas  shall  be  those  spaces  within  a  building  where 
quantities  of  hazardous  materials  not  exceeding  the 
allowable  exempt  amounts  are  stored,  dispensed, 
utilized  or  handled.  Control  areas  shall  be  separated 
from  all  adjacent  interior  spaces  by  fire  separation 
assemblies  in  accordance  with  780  CMR  709.0.  The 


number  of  permitted  control  areas  and  degree  of  fire 
separation  shall  be  in  accordance  with  Table  417.2. 
The  floor  construction  and  supporting  structure  for 
all  floors  within  the  control  area  shall  require  a 
minimum  two-hour  fireresistance  rating. 


Table  417.2 
PERMITTED  CONTROL  AREAS 


a,  b 


Floor  level 

Percent  of 

allowable 

exempt 

quantities  per 

control  area 

Control  areas 
per  floor 

Vertical  fire 

separation 

walls  (hours) 

1 
2 

4 
5 
6 

7-9 
Higher  than  9 

100 
75 
50 
12.5 
12.5 
12.5 

5 

5 

4 
3 
2 
2 
2 
2 

2 
1 

1 
1 
1 

■■     2 
2 
2 

2 

Note  a.  The  number  of  floor  levels  below  grade  shall 
not  exceed  two.  The  first  floor  level  before  grade  shall  be 
limited  to  75%  of  the  maximum  allowable  exempt 
quantity  per  control  area  with  a  maximum  of  three 
control  areas.  The  second  floor  level  below  grade  shall 
be  limited  to  50%  of  the  maximum  allowable  exempt 
quantity  per  control  area  with  a  maximum  of  two  control 
areas. 

Note  b.  In  mercantile  occupancies,  a  maximum  of  two 
control  areas  per  floor  shall  be  permitted  m  retail  sales 
rooms. 

417.2.1  Hazardous  material  in  mercantile 
display  areas:  Except  as  modified  by  780  CMR 
426,  the  aggregate  quantity  of  nonflammable  solid 
and  nonflammable  or  noncombustible  liquid 
hazardous  materials  permitted  within  a  single 
control  area  of  a  retail  sales  occupancy  is 
permitted  to  exceed  the  exempt  amounts  specified 
in  Tables  307.8(1)  and  307.8(2)  without 
classifying  the  building  as  a  high-hazard  use 
group,  provided  that  the  materials  are  stored  in 
accordance  with  the  fire  prevention  code  listed  in 
Appendix  A. 

417.3  Equipment  rooms:  Heating  and  ventilating 
equipment  in  occupancies  involving  fire  hazards 
from  flammable  vapors,  dusts,  combustible  fibers  or 
other  highly  combustible  substances  shall  be 
installed  and  protected  against  fire  and  explosion 
hazards  in  accordance  with  the  mechanical  code  and 
the  fire  prevention  code  listed  in  Appendix  A. 

417.4  Hazardous  material  systems:  Systems 
involving  hazardous  materials  shall  be  suitable  for 
the  intended  application  and  shall  be  designed  by 
persons  competent  in  such  design.  Controls  shall  be 
designed  to  prevent  materials  from  entering  or 
leaving  process  or  reaction  systems  at  other  than  the 
intended  time,  rate  or  path.  Automatic  controls, 
where  provided,  shall  be  designed  to  be  fail  safe. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


417.5  Inside  storage,  dispensing  and  utilization: 

The  inside  storage,  dispensing  and  utilization  of 
hazardous  materials  in  excess  of  the  allowable 
exempt  amounts  of  Tables  307.8(1)  and  307.8(2) 
shall  be  in  accordance  with  780  CMR  417.5.1 
through  417.5.5  and  the  fire  prevention  code  listed 
in  Appendix  A. 

417.5.1  Explosion  control:  Every  structure,  room 
or  space  occupied  for  purposes  involving 
explosion  hazards  shall  be  provided  with 
explosion  venting,  explosion  suppression  systems, 
barricades  or  equivalent  explosion  protective 
devices  in  accordance  with  780  CMR  417.0  and 
NFiPA  495  listed  in  Appendix  A  where  required 
by  780  CMR  418.0  and  the  fire  prevention  code 
listed  in  Appendix  A. 

Exception:  Explosion  venting  shall  not  be 
utilized  as  a  means  to  protect  buildings  from 
detonation  hazards. 

417.5.1.1  Explosion  venting:  Areas  which  are 
provided  with  explosion  venting  to  relieve 
deflagration  shall  comply  with  the  following: 

1.  Walls,  ceilings  and  roofs  exposing 
surrounding  areas  shall  be  designed  to  resist 
a  minimum  internal  pressure  of  100  pounds 
per  square  foot  (psf). 

2.  Explosion  venting  shall  be  permitted 
only  in  exterior  walls  or  roofs  or  through 
specially  designed  shafts  to  the  exterior  of 
the  building. 

3.  Venting  shall  be  designed  to  prevent 
serious  structural  damage  and  the 
production  of  lethal  projectiles. 

4.  The  aggregate  clear  vent  relief  area  shall 
be  governed  by  the  pressure  resistance  of 
the  nonrelieving  portions  of  the  building. 

5.  Vents  shall  be  designed  to  relieve  at  a 
maximum  internal  pressure  of  20  pounds 
per  square  foot  (psf)  and  shall  consist  of  any 
one  or  any  combination  of  the  following: 

5.1.  Walls  of  lightweight  material. 

5.2.  Lightly  fastened  hatch  covers. 

5.3.  Lightly  fastened,  outward-opening 
swinging  doors  in  exterior  walls. 

5.4.  Lightly  fastened  walls  or  roofs. 

6.  Venting  devices  shall  discharge  directly 
to  the  open  air  or  to  an  unoccupied  space 
not  less  than  50  feet  in  width  on  the  same 
lot. 

7.  Relieving  devices  shall  be  so  located 
that  the  discharge  shall  not  be  less  than  ten 
feet  vertically  and  20  feet  horizontally  from 
window  openings  or  exits  in  the  same  or 
adjoining  buildings  or  structures. 

8.  Discharge  shall  be  in  the  direction  of 
least  exposure  and  not  into  the  interior  of 
the  building. 

417.5.1.2  Explosion  suppression  systems: 
Explosion  suppression  systems  shall  be  of  an 
approved  type  and  installed  in  accordance  with 


the  provisions  of  780  CMR  and  NFiPA  69 
listed  in  Appendix  A 

417.5.2  Monitor  control  equipment:  Monitor 
control  equipment  shall  be  provided  where 
required  by  the  fire  prevention  code  listed  in 
Appendix  A. 

417.5.3  Detection  systems:  All  occupancies  in 
Use  Group  H  shall  be  provided  with  an  automatic 
fire  detection  system  in  accordance  with  NFiPA 
72  listed  in  Appendix  A  where  required  by  the  fire 
prevention  code  listed  in  Appendix  A.  The 
detection  system  shall  be  provided  in  the  areas 
where  the  high-hazard  materials  are  utilized  and 
stored 

417.5.4  Standby  power:  Where  mechanical 
ventilation,  treatment  systems,  temperature 
control,  alarm,  detection  or  other  electrically 
operated  systems  are  required,  such  systems  shall 
be  connected  to  an  emergency  electrical  system  in 
accordance  with  527  CMR  12.00  as  listed  in 
Appendix  A  or  a  standby  power  system  in 
accordance  with  527  CMR  12.00  as  listed  in 
Appendix  A.  Such  systems  shall  be  independent 
of  the  public  supply 

417.5.5  Spill  control,  drainage  and 
containment:  Rooms,  buildings  or  areas  occupied 
for  the  storage  of  solid  and  liquid  hazardous 
materials  shall  be  provided  with  a  means  to 
control  spillage  and  to  contain  or  drain  off 
spillage  and  fire  protection  water  discharged  in 
the  storage  area  where  required  in  780  CMR 
418.0  and  the  fire  prevention  code  listed  in 
Appendix  A . 

417.6  Outside  storage,  dispensing  and  utilization: 

The  outside  storage,  dispensing  and  utilization  of 
hazardous  materials  in  excess  of  the  exempt 
amounts  shall  be  in  accordance  with  780  CMR 
417.6.1  through  417.6.6  and  the  fire  prevention  code 
listed  in  Appendix  A 

417.6.1  Location:  In  addition  to  the  general 
requirements  of  780  CMR  417.6.2  through 
417.6.5.  the  outside  storage  of  hazardous 
materials  as  listed  in  780  CMR  307.0  shall  be 
separated  from  buildings  and  lot  lines  and  into 
individual  areas  as  specified  in  the  fire  prevention 
code  listed  in  Appendix  A. 

417.6.2  Protection  from  vehicles:  Guard  posts  or 
other  means  shall  be  provided  to  protect  outside 
storage  tanks  from  vehicular  damage. 

417.6.3  Fire  lanes  and  water  supply:  Fire  lanes 
and  approved  water  supplies  shall  be  provided  for 
outside  storage  areas  as  required  by  the  code 
official. 

'! .  Fire  lanes.  Fire  lanes  shall  be  provided  to 
within  150  feet  (45720  mm)  of  all  portions  of 
an  outside  storage  area.  Such  fire  lanes  shall 


84 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/9" 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


comply  with  the  provisions  of  the  fire 
prevention  code  listed  in  Appendix  A 
2.  Water  supply.  An  approved  water  supply 
shall  be  provided.  Fire  hydrants  capable  of 
supplying  the  required  fire  flow  shall  be 
provided  to  within  150  feet  (45720  mm)  of  an 
outside  storage  area.  The  Mater  supply  and  fire 
hydrants  shall  comply  with  the  provisions  of 
NFiPA  24  and  the  fire  prevention  code  listed  in 
Appendix  A 

417.6.4  Weather  protection:  Where  weather 
protection  is  provided  for  sheltering  outside 
hazardous  material  storage  areas,  such  storage 
shall  not  be  considered  inside  storage  provided 
that  all  of  the  following  conditions  are  met: 

1.  Structure  supports  and  walls  shall  not 
obstruct  more  than  one  side  of  the  perimeter  of 
the  storage  area. 

2.  The  distance  from  the  structure  and  the 
structure  supports  to  buildings,  lot  lines,  public 
ways  or  means  of  egress  to  a  public  way  shall 
not  be  less  than  the  distance  required  for  an 
outside  hazardous  material  storage  area 
without  weather  protection. 

3.  The  overhead  structure  shall  be  of 
approved  noncombustible  construction  with  a 
maximum  area  of  1,500  square  feet  (140  nr). 

417.6.5  Security:  Any  site  occupied  for  the 
storage,  utilization  or  handling  of  hazardous 
materials  shall  be  provided  with  a  fence  not  less 
than  six  feet  (1829  mm)  in  height  or  otherwise 
secured  from  public  access. 

417.6.6  Fire  suppression  system  Areas  occupied 
for  the  dispensing  or  utilization  of  flammable 
hazardous  materials  which  are  located  within  50 
feet  of  either  a  storage  area  or  building,  and 
vehicle-loading  racks  where  flammable  hazardous 
materials  are  dispensed,  shall  be  equipped  with  an 
approved  automatic  fire  suppression  system. 

Exception:  Motor  vehicle  service  stations  as 
defined  in  NFiPA  30A  listed  in  Appendix  A 

780  CMR  418.0  USE  GROUPS  HI,  H-2,  H-3 
ANDH-4 

418.1  Scope:  The  provisions  of  780  CMR  418.0 
shall  apply  to  the  storage  and  utilization  of 
hazardous  materials  in  excess  of  the  exempt 
amounts  listed  in  780  CMR  307.8  All  buildings  and 
structures  with  an  occupancy  in  Use  Group  H  shall 
also  comply  with  the  applicable  provisions  of 
780  CMR  417.0  and  the  fire  prevention  code  listed 
in  Appendix  A. 

418.2  Use  Group  H-l:  All  occupancies  in  Use 
Group  H-l  shall  be  constructed  in  accordance  with 
the  provisions  of  780  CMR  418.2.1  and  41 8.2.2  and 
the  fire  prevention  code  listed  in  Appendix  A 


418.2.1  Construction  Occupancies  in  Use  Group 
H-l  shall  not  be  located  in  buildings  that  are  more 
than  one  story  in  height,  have  basements  or  other 
spaces  below  grade,  or  which  are  attached  to  other 
buildings.  The  minimum  fire  separation  distance 
for  all  exterior  walls  of  occupancies  in  Use  Group 
H-l  shall  be  in  accordance  with  the  fire 
prevention  code  listed  in  Appendix  A  All  floor 
surfaces  shall  be  spark  resistant. 

418.2.2  Number  of  exits  There  shall  not  be  less 
than  two  exits  from  any  area  or  space  wherein  Use 
Group  H-l  materials  are  utilized  or  stored  .All 
required  exits  shall  discharge  directly  to  the 
exterior  of  the  building  or  structure 

418.3  Use  Group  H-2:  Occupancies  in  Use  Group 
H-2  shall  be  constructed  in  accordance  with 
780  CMR  418.3.1  through  418.3.4  and  the  fire 
prevention  code  listed  in  Appendix  A 

418.3.1  Combustible  dusts,  grain  processing 
and  storage  The  provisions  of  780  CMR 
418.3.1.1  through  418,3.1  6  shall  apply  to  all 
buildings  in  which  materials  that  produce 
combustible  dusts  are  stored  or  handled 
Buildings  which  store  or  handle  combustible  dusts 
shall  comply  with  the  applicable  provisions  of 
NFiPA  61A  61B.  61C.  61D.  65.  120.  651.  654. 
655.  664  and  8503  and  the  fire  prevention  code 
listed  in  Appendix  A 

418.3.1.1  Type  of  construction  and  height 
exceptions  .All  buildings  shall  be  of  Type  :. 
Type  2  or  Type  4  construction,  within  the 
height  and  area  limitations  of  Tabie  503  for 
Use  Group  H-2;  except  that  where  erected  of 
Type  1  or  Type  2  construction,  the  heights  and 
areas  of  grain  elevators  and  similar  structures 
shall  be  unlimited,  and  where  of  Type  4 
construction,  the  maximum  height  shall  be  65 
feet  (19812  mm)  and  except  further  that,  in 
isolated  areas,  the  maximum  height  of  Type  4 
structures  shall  be  increased  to  85  feet  (25908 
mm). 

418.3.1.2  Grinding  rooms  Every  room  or 
space  occupied  for  grinding  or  other  operations 
that  produce  combustible  dusts  shall  be 
enclosed  with  floors  and  walls  that  have  not 
less  than  a  two-hour  fireresistance  rating  where 
the  area  is  not  more  than  3,000  square  feet  (279 
m2),  and  not  less  than  a  four  hour  fireresistance 
rating  where  the  area  is  greater  than  3.000 
square  feet  (279  nr). 

418.3.1.3  Conveyors:  All  conveyors,  chutes, 
piping  and  similar  equipment  passing  through 
the  enclosures  of  rooms  or  spaces  shall  be 
constructed  dirt  tight  and  vapor  tight,  and  be  of 
approved  noncombustible  materials  complying 
with  780  CMR  3010.0. 

418.3.1.4  Explosion  relief:  Means  for 
explosion  relief  shall  be  provided  as  specified 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


85 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


in  780  CMR  417.5.1,  or  spaces  shall  be 
equipped  with  the  equivalent  mechanical 
ventilation  complying  with  the  mechanical 
code  listed  in  Appendix  A 

418.3.1.5  Grain  elevators:  Grain  elevators, 
malt  houses  and  buildings  for  similar 
occupancies  shall  not  be  located  within  30  feet 
(9144  mm)  of  interior  lot  lines  or  structures  on 
the  same  lot,  except  where  erected  along  a 
railroad  right-of-way. 

418.3.1.6  Coal  pockets:  Coal  pockets  located 
less  than  30  feet  (9144  mm)  from  interior  lot 
lines  or  from  structures  on  the  same  lot  shall  be 
constructed  of  not  less  than  Type  2A 
construction.  Where  more  than  30  feet  (9144 
mm)  from  interior  lot  lines,  or  where  erected 
along  a  railroad  right-of-way,  the  minimum 
type  of  construction  of  such  structures  not 
more  than  65  feet  (19812  mm)  in  height  shall 
be  Type  4. 

418.3.2  Flammable  and  combustible  liquids 

The  storage,  handling  processing  and  transporting 
of  flammable  and  combustible  liquids  shall  be  in 
accordance  with  the  mechanical  code  and  the  fire 
prevention  code  listed  in  Appendix  A.  Where  a 
Class  L  II  or  UlAflammable  or  combustible  liquid 
is  stored  in  tanks  inside  the  building,  the 
installation  shall  conform  to  780  CMR  418.3.2.1 
through  418.3.2.10  and  NFiPA  30  listed  in 
Appendix  A  The  requirements  shall  only  apply 
where  tanks  have  an  individual  storage  capacity 
that  exceeds  the  exempt  amounts  specified  in 
Tables  307.8(1)  and  307.8(2)  The  fire  area 
containing  the  tank(s)  shall  be  classified  as  Use 
Group  H-2. 

418.3.2.1  Mixed  use  groups:  Where  the 
storage  tank  area  is  located  in  a  building  of  two 
or  more  use  groups,  the  Use  Group  H-2  fire 
area  shall  be  completely  separated  from 
adjacent  fire  areas  in  accordance  with  the 
requirements  of  780  CMR  3 13. 1.2. 

418.3.2.1.1  Height  exception:  Where 
storage  tanks  are  located  within  only  a 
single  story,  the  height  limitation  of 
780  CMR  503.3  shall  not  apply  for  the  Use 
Group  H-2  fire  area. 

418.3.2.2  Tank  protection:  All  storage  tanks 
shall  be  noncombustible  and  protected  from 
physical  damage.  Pi.  fire  separation  assembly 
around  the  storage  tank(s)  shall  be  permitted  to 
be  classified  as  the  method  of  protection  from 
physical  damage. 

418.3.2.3  Tanks  for  Class  I  flammable 
liquid:  All  storage  tanks  for  Class  I  flammable 
liquids  shall  be  double-wall  tanks.  A  double- 
wall  tank  shall  consist  of  an  approved  tank 
conforming  to  the  requirements  of  the 
mechanical  code  listed  in  Appendix  A, 
installed     within     a     completely     enclosed 


noncombustible  containment  structure  The 
containment  structure  shall  prevent  the  stored 
liquid  from  escaping  into  the  room  or  area  in 
which  the  tank  is  located.  A  leak  detection 
alarm  shall  be  provided  to  identify  a  leak  of  the 
primary  wall  of  the  tank.  The  alarm  shall 
conform  to  780  CMR  418.3.2.6. 

418.3.2.4  Suppression:  The  Use  Group  H-2 
fire  area  shall  be  equipped  throughout  with  an 
approved  automatic  fire  sprinkler  system, 
installed  in  accordance  with  780  CMR  906.2.1, 
or  with  a  foam-extinguishing  system.  The 
automatic  fire  suppression  system  shall  be 
supervised  by  method  1,  2  or  3  of  780  CMR 
923.1. 

418.3.2.5  Leakage  containment  A  liquid- 
tight  containment  area  compatible  with  the 
stored  liquid  shall  be  provided  to  retain  1 10% 
of  the  entire  capacity  of  all  the  storage  liquid  in 
the  event  of  a  leak  in  a  tank  plus  the  capacity 
of  the  automatic  fire  suppression  system 
activated  for  a  period  of  30  minutes.  The 
storage  tanks  and  the  leakage  containment  area 
shall  be  provided  with  an  approved  method  to 
drain  manually  the  flammable  or  combustible 
liquid. 

Exception:  Rooms  where  only  double-wall 
storage  tanks  conforming  to  780  CMR 
418.3.2.3  are  used  to  store  Class  I.  II  and 
1TTA  Aflammable  and  combustible  liquids 
shall  not  be  required  to  have  a  leakage 
containment  area. 

418.3.2.6  Leakage  alarm:  An  approved 
automatic  alarm  shall  be  provided  to  indicate  a 
leak  in  a  storage  tank  and  room.  The  alarm 
shall  sound  an  audible  signal.  1 5  dBa  above  the 
ambient  sound  level,  at  every  point  of  entry 
into  the  room  in  which  the  leaking  storage  tank 
is  located.  An  approved  sign  shall  be  posted 
on  every  entry  door  to  the  tank  storage  room 
indicating  the  potential  hazard  of  the  interior 
room  environment,  or  the  sign  shall  state, 
"Warning,  when  alarm  sounds.  the 
environment  within  the  room  may  be 
hazardous."  The  leakage  alarm  shall  also  be 
supervised  in  accordance  with  780  CMR  923.2 
to  transmit  a  trouble  signal 

418.3.2.7  Tank  vent:  Storage  tank  vents  shall 
terminate  to  the  outdoor  air  The  vent 
termination  shall  be  in  an  approved  location  a 
minimum  of  12  feet  (3658  mm)  above  adjacent 
ground  level  and  ten  feet  (3048  mm)  from  a  lot 
line,  ventilation  intake  opening,  openable 
window  or  door. 

418.3.2.8  Room  ventilation:  Storage  tank 
areas  storing  Class  I  liquids,  or  Class  II  or  IIIA 
liquids  at  temperatures  above  flash  point,  shall 
be  ventilated  at  a  rate  sufficient  to  maintain  the 
concentration  of  vapors  within  the  area  at  or 
below   25%   of  the   lower   explosive   limit. 


86 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


Ventilation  requirements  shall  be  determined 
by  either  calculations  based  on  anticipated 
fugitive  emissions  or  by  sampling  of  the  actual 
vapor  concentration  levels  under  normal 
operating  conditions.  The  sampling  shall  be 
conducted  at  a  five-foot  radius  from  each 
potential  vapor  source  in  the  storage  area. 
Provision  shall  be  made  for  make-up  air  to 
avoid  short-circuiting  the  ventilation. 

418.3.2.9  Explosion  venting:  Where  Class  I 
liquids  are  being  stored,  explosion  venting 
shall  be  provided  in  accordance  with  780  CMR 
417.5 

418.3.2.10  Tank  openings  other  than  vents: 
Tank  openings  other  than  vents  from  tanks 
inside  buildings  shall  bedesigned  to  ensure  that 
liquids  or  vapor  concentrations  are  not  released 
inside  the  building  and  shall  conform  to 
780  CMR 418.3.2. 10.1  through  418.3.2.10.5. 

418.3.2.10.1  Liquid  tight:  All  tank 
openings  at  the  maximum  liquid  level  or 
below  shall  be  liquid  tight. 

418.3.2.10.2  Closed:  All  tank  openings 
above  the  maximum  liquid  level  shall  be 
normally  closed. 

418.3.2.10.3  External  valve:  Each 
connection  through  which  liquid  is  capable 
of  gravity  flow  from  a  tank  inside  a  building 
shall  be  provided  with  an  external  valve 
located  as  close  as  practical  to,  but  not  more 
than  two  feet  from,  the  shell  of  the  tank. 

418.3.2.10.4  Valves  on  transfer 
connections:  Tanks  storing  Class  I  or  Class 
II  liquids  shall  be  provided  with  either  a 
normally  closed,  remotely  activated  valve  or 
an  automatic-closing,  heat-activated  valve 
or  other  approved  device  on  each  liquid 
transfer  connection  below  the  liquid  level, 
except  for  connections  utilized  for 
emergency  disposal. 

418.3.2.10.5  Overflow  protection:  Tanks 
shall  be  equipped  with  a  device,  or  other 
means  provided,  to  prevent  overflow  into 
the  building. 

418.3.3  Liquefied  petroleum  gas  distribution 
facilities:  The  design  and  construction  of  propane, 
butane,  propylene,  butylene  and  other  liquefied 
petroleum  gas  distribution  facilities  shall  conform 
to  the  applicable  provisions  of  780  CMR 
418.3.3.1  through  418.3.3.5.2.  The  storage  and 
handling  of  liquefied  petroleum  gas  systems  shall 
conform  to  the  fire  prevention  code  listed  in 
Appendix  A.  The  design  and  installation  of 
piping,  equipment  and  systems  which  utilize 
liquefied  petroleum  gas  shall  be  in  accordance 
with  the  mechanical  code  listed  in  Appendix  A 
Liquefied  petroleum  gas  distribution  facilities 
shall    be    ventilated    in    accordance    with    the 


mechanical    code    listed    in   Appendix  A    and 
780  CMR  418.3.3.1. 

418.3.3.1  Air  movement:  Liquefied  petroleum 
gas  distribution  facilities  shall  be  provided 
with  air  inlets  and  outlets  arranged  so  that  air 
movement  across  the  floor  of  the  facility  will 
be  uniform.  The  total  area  of  both  inlet  and 
outlet  openings  shall  be  at  least  one  square  inch 
(0.00065  m2)  for  each  one  square  foot  (0.093 
m2)  of  floor  area.  The  bottom  of  such  openings 
shall  not  be  more  than  six  inches  (152  mm) 
above  the  floor. 

418.3.3.2  Construction:  Liquefied  petroleum 
gas  distribution  facilities  shall  be  constructed 
in  accordance  with  780  CMR  418.3.3.3  for 
separate  buildings,  780  CMR  418.3.3.4  for 
attached  buildings  or  780  CMR  418.3.3.5  for 
rooms  within  buildings. 

418.3.3.3  Separate  buildings:  Where  located 
in  separate  buildings,  liquefied  petroleum  gas 
distribution  facilities  shall  be  occupied 
exclusively  for  that  purpose  or  for  other 
purposes  having  similar  hazards.  Such 
buildings  shall  be  limited  to  one  story  in  height 
and  shall  conform  to  780  CMR  418.3.3.3.1  and 
418.3.3.3.2. 

418.3.3.3.1  Floors:  The  floor  shall  not  be 
located  below  ground  level  and  any  spaces 
beneath  the  floor  shall  be  solidly  filled  or 
shall  be  left  unenclosed. 

418.3.3.3.2  Materials:  Walls,  floors, 
ceilings,  columns  and  roofs  shall  be 
constructed  of  noncombustible  materials. 
Exterior  walls,  ceilings  and  roofs  shall  be 
constructed  of  material  designed  for 
explosion  venting  or,  if  of  heavy 
construction  such  as  solid  brick  masonry, 
concrete  block  or  reinforced  concrete, 
explosion-venting  windows  or  panels  in 
walls  or  roofs  shall  be  provided  having  an 
explosion-venting  area  of  at  least  one  square 
foot  (0.093  m)  for  each  50  cubic  feet 
(1.40  m)  of  enclosed  volume. 

418.3.3.4  Attached  buildings:  Where  liquefied 
petroleum  gas  distribution  facilities  are  located 
in  an  attached  structure,  the  attached  perimeter 
shall  not  exceed  50%  of  the  perimeter  of  the 
space  enclosed  and  the  facility  shall  comply 
with  780  CMR  418.3.3.3  and  418.3.3.4.1. 
Where  the  attached  perimeter  exceeds  50%, 
such  facilities  shall  comply  with  780  CMR 
418.3.3.5. 

418.3.3.4.1  Fire  separation  assemblies: 
Separation  of  the  attached  structures  shall  be 
provided  by  fire  separation  assemblies 
having  a  fireresistance  rating  of  not  less 
than  one  hour  and  shall  not  have  openings 
Fire  separation  assemblies  between 
attached  structures  occupied  only  for  the 


2/7;97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


87 


780  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


storage  of  LP-gas  are  permitted  to  have  fire 

doors  that  comply  with  780  CMR  716.0. 

Such  fire  separation  assemblies  shall  be 

designed  to  withstand  a  static  pressure  of  at 

least  100  pounds  per  square  foot  (psf)  (488.2 

kg/nr),  except  where  the  building  to  which 

the  structure  is  attached  is  occupied  by 

operations  or  processes  having  a  similar 

hazard. 

418.3.3.5  Rooms  within  buildings:  Where 

liquefied  petroleum  gas  distribution  facilities 

are  located  in  rooms  within  buildings,  such 

rooms  shall  be  located  in  the  first  story  and 

shall   have  at   least  one  exterior  wall  with 

sufficient  exposed  area  to  permit  explosion 

venting    as    provided    for    in    780    CMR 

418.3.3.5. 1.  The  building  in  which  the  room  is 

located    shall    not    have    a    basement    or 

unventilated  crawl  space  and  the  room  shall 

comply    with    780    CMR    418.3.3  5.1    and 

418.3.3.5.2. 

418.3.3.5.1  Materials:  Walls,  floors, 
ceilings  and  roofs  of  such  rooms  shall  be 
constructed  of  approved  noncombustible 
materials.  Exterior  walls  and  ceilings  shall 
be  either  of  lightweight  materials  designed 
for  explosion  venting  or,  if  of  heavy 
construction  such  as  solid  brick  masonry, 
concrete  block  or  reinforced  concrete, 
explosion-venting  windows  or  panels  in 
walls  or  roofs  shall  be  provided  having  an 
explosion-venting  area  of  at  least  one  square 
foot  (0.093  m2)  for  each  50  cubic  feet  (1.40 
m3)  of  enclosed  volume. 

418.3.3.5.2  Common  construction:  Walls 
and  floor/ceiling  assemblies  common  to  the 
room  and  to  the  building  within  which  the 
room  is  located  shall  have  a  fireresistance 
rating  of  not  less  than  one  hour  and  without 
openings.  Common  walls  for  rooms 
occupied  only  for  storage  of  LP-gas  are 
permitted  to  have  openings  which  shall  be 
equipped  with  3/4-hour  approved  opening 
protectives  complying  with  780  CMR  716.0 
or  718.0.  Such  walls  and  ceiling  shall  be 
designed  to  withstand  a  static  pressure  of  at 
least  100  psf  (488.2  kg/m).  Where 
approved.  780  CMR  418.3.3.5.2  shall  not 
apply  where  the  building,  within  which  the 
room  is  located,  is  occupied  by  operations 
or  processes  having  a  similar  hazard. 

418.3.4  Dry  cleaning  plants:  The  construction 
and  installation  of  dry  cleaning  plants  shall  be  in 
accordance  with  the  requirements  of  780  CMR, 
the  mechanical  code,  the  plumbing  code  and 
NFiPA  32  listed  in  Appendix  A 

418.4  Use  Group  H-3:  Occupancies  in  Use  Group 
H-3  shall  be  constructed  in  accordance  with  the 


applicable  provisions  of  780  CMR  and  the  fire 
prevention  code  listed  in  Appendix  A 

418.5  Use  Group  H-4:  Occupancies  in  Use  Group 
H-4  shall  be  constructed  in  accordance  with  the 
applicable  provisions  of  780  CMR  and  the  fire 
prevention  code  listed  in  Appendix  A. 

780  CMR  419.0  APPLICATION  OF 
FLAMMABLE  FINISHES 

419.1  General:  The  provisions  of  780  CMR  419  0 

shall  apply  to  the  construction,  installation  and  use 
of  buildings  and  structures,  or  parts  thereof,  for  the 
spraying  of  flammable  paints,  varnishes  and  lacquers 
or  other  flammable  materials  or  mixtures  or 
compounds  used  for  painting,  varnishing,  staining  or 
similar  purposes.  All  such  construction  and 
equipment  shall  comply  with  NFiPA  33  and  34 
listed  in  Appendix  A. 

419.2  Spray  spaces:  Ail  spray  spaces  shall  be 
ventilated  with  an  exhaust  system  to  prevent  the 
accumulation  of  flammable  mist  or  vapors  in 
accordance  with  the  mechanical  code  listed  in 
Appendix  A.  Where  such  spaces  are  not  separately 
enclosed,  noncombustible  spray  curtains  shall  be 
provided  to  restrict  the  spread  of  flammable  vapors. 

419.2.1  Spray  booths:  All  spray  booths  shall  be 
constructed  of  approved  noncombustible  materials 
and  equipped  with  mechanical  ventilating  systems 
in  accordance  with  the  mechanical  code  listed  in 
Appendix  A 

419.2.2  Spray  rooms:  All  spray  rooms  shall  be 
enclosed  in  fire  separation  assemblies  with  not 
less  than  a  one-hour  fireresistance  rating  Floors 
shall  be  waterproofed  and  drained  in  an  approved 
manner 

419.2.3  Spray  storage  rooms  Rooms  used  for 
the  storage  of  spraying  materials  essential  to  the 
flammable  finish  operation  shall  comply  with 
NFiPA  30  and  the  fire  prevention  code  listed  in 
Appendix  A 

419.3  Fire  protection:  An  automatic  fire 
suppression  system  shall  be  provided  in  all  spray, 
dip  and  immersing  spaces  and  storage  rooms,  and 
shall  be  installed  in  accordance  with  780  CMR  9 

780  CMR  420.0  MOBILE  UNITS 

420.1  For  regulations  pertaining  to  Mobile  Units,  see 
780  CMR  35,  and  780  CMR  R3 

780  CMR  421.0  SWIMMING  POOLS 
(Refer  to  M.G.L.  c  140,  §  206  for  further 
requirements  pertaining  to  public  or  semi-public, 
outdoor,  inground  swimming  pool  enclosures, 
safety  equipment,  inspection,  and  penalties  for 
violations.) 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


7S0  C.MR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


421.1  General:  Swimming  and  bathing  pools  shall 
conform  to  the  requirements  of  7S0  CMR  421.0 
provided  that  780  CMR421.0  shall  not  be  applicable 
to  any  such  pool  less  than  24  inches  (610  mm)  deep 
or  having  a  surface  area  less  than  250  square  feet 
(23.25  rrr),  except  where  such  pools  are  permanently 
equipped  with  a  water-recirculating  system  or 
involve  structural  materials.  For  the  purposes  of 
7S0  CMR,  pools  are  classified  as  private  swimming 
pools,  public  swimming  pools  or  semi-public 
swimming  pooh,  as  defined  in  7S0  CMR  421.2. 
Materials  and  constructions  used  in  swimming  pools 
shall  comply  with  the  applicable  requirements  of 
7S0CMR. 

421.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  7S0  CM.R  421.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Pools,  swimming,  hot  tubs  and  spas 

Above-ground/on-ground  pool:  See  definition  of 
private  swimming  pool 

Barrier:  A  fence,  a  wall,  a  building  wall  or  a 
combination  thereof  which  completely  surrounds 
the  swimming  pool  and  obstructs  access  to  the 
swimming  pool.  (Refer  to  M.G.L  c.  140,  §206 
for  required  enclosure  of  public  or  semi-public, 
outdoor,  inground  swimming  pools.) 
Hot  tub:  See  definition  of  private  swimming 
pool. 

In-ground  pool  See  definition  of  private 
swimming  pool. 

Private  swimming  pool:  Any  structure  that 
contains  water  over  24  inches  (610  mm)  in  depth 
and  which  is  used,  or  intended  to  be  used,  for 
swimming  or  recreational  bathing  in  connection 
with  an  occupancy  in  Use  Group  R-3  or  R-4  and 
which  is  available  only  to  the  family  and  guests  of 
the  householder  This  includes  in-ground,  above- 
ground  and  on-ground  Lwimming  pools,  hot  tubs 
and  spas 

Private  swimming  pool,  indoor:  Any  private 
swimming  pool  that  is  totally  contained  within  a 
private  structure  and  surrounded  on  all  four  sides 
by  walls  of  said  structure. 

Private  swimming  pool,  outdoor:  Any  private 
swimming  pool  that  is  not  an  indoor  pool. 
Public  outdoor,  inground  swimming  pool  Any 
swimming  pool  which  is  used,  or  intended  to  be 
used,  for  swimming  or  recreational  bathing  by 
the  general  public  Refer  to  M.G.L  c  140,  §  206 
for  requirements  pertaining  to  public  or  semi- 
public,  outdoor,  inground  swimming  pool 
enclosures,  safety  equipment,  inspection,  and 
penalties  for  violations. 

Public  swimming  pool,  outdoor:  Any  public 
swimming  pool  that  is  not  defined  as  an  outdoor, 
inground  swimming  pool. 

Semi-public  outdoor,  inground  swimming  pool: 
(as   defined  by   M.G.L    c.    140,    §  206)    any 


swimming  or  wading  pool  on  the  premises  of,  or 
used  in  connection  with,  a  hotel,  motel,  trailer 
court,  apartment  house,  country  club,  youth 
club,  school,  camp,  or  similar  establishment 
where  the  primary  purpose  of  the  establishment 
is  not  the  operation  of  the  swimming  facilities. 
Semi-public  outdoor,  inground  swimming  pool 
shall  also  mean  a  pool  constructed  and 
maintained  by  groups  for  the  purposes  of 
providing  bathing  facilities  for  members  and 
quests  only.  Refer  to  M.G.L  c.  140,  §  206  for 
requirements  pertaining  to  public  or  semi-public, 
outdoor,  inground  swimming  pool  enclosures, 
safety  equipment,  inspection,  and  penalties  for 
violations. 

Semi-public  swimming  pool,  outdoor:  Any  semi- 
public  swimming  pool  that  is  not  defined  as  a 
semi-public  outdoor,  inground  swimming  pool. 
Spa:  See  definition  of  private  swimming  pool. 

421.3  Permits  and  construction   documents    A 

swimming  pool  or  appurtenances  thereto  shall  not  be 
constructed,  installed,  enlarged  or  altered  until 
construction  documents  have  been  submitted  and  a 
permit  has  been  obtained  from  the  code  official.  The 
approval  of  all  city,  county  and  state  authorities 
having  jurisdiction  over  swimming  pools  shall  be 
obtained  before  applying  to  the  code  official  for  a 
permit.  Certified  copies  of  these  approvals  shall  be 
filed  as  part  of  the  supporting  data  for  the  permit 
application. 

421.3.1  Construction  documents  Construction 
documents  shall  accurately  show  dimensions  and 
construction  of  the  pool  and  appurtenances  and 
properly  established  distances  to  lot  lines. 
buildings,  walks  and  fences,  as  well  as  details  of 
the  water  supply  system,  drainage  and  water 
disposal  svstems,  and  all  appurtenances  pertaining 
to  the  swimming  pool.  Detailed  construction 
documents  of  structures,  vertical  elevations  and 
sections  through  the  pool  showing  depth  shall  be 
included 

421.4  Locations:  Private  swimming  pools  shall  not 
encroach  on  any  fror.t  or  side  yard  required  by 
780  CMR  or  by  the  governing  zoning  law,  unless  in 
accordance  with  specific  rules  of  the  jurisdiction  in 
which  the  pool  is  located.  A  wall  of  a  swimming 
pool  shall  not  be  located  less  than  six  feet  (1S29 
mm)  from  any  rear  or  side  property  line  or  ten  feet 
(3048  mm)  from  any  street  property  line,  unless  in 
accordance  with  specific  rules  of  the  jurisdiction  in 
which  the  poo!  is  located. 

421.5  Structural  design:  The  pool  structure  shall  be 
engineered  and  designed  to  withstand  the  expected 
forces  to  which  the  pool  will  be  subjected. 

421.5.1  Wall  slopes:  To  a  depth  up  to  two  feet 
nine  inches  (83 S  mm)  from  the  top,  the  wall  slope 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


89 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


shall  not  be  more  than  one  unit  horizontal  in  five 
units  vertical  (1:5). 

421.5.2  Floor  slopes:  The  slope  of  the  floor  on 
the  shallow  side  of  the  transition  point  shall  not 
exceed  one  unit  vertical  to  seven  units  horizontal 
(1:7).  For  public  pools  greater  than  1,200  square 
feet  (111.6  nr),  the  slope  of  the  floor  on  the 
shallow  side  of  the  transition  point  shall  not 
exceed  one  unit  vertical  to  ten  units  horizontal 
(1:10).  The  transition  point  between  shallow  and 
deep  water  shall  not  be  more  than  five  feet  (1524 
mm)  deep. 

421.5.3  Surface  cleaning:  All  swimming  pools 
shall  be  provided  with  a  recirculating  skimming 
device  or  overflow  gutters  to  remove  scum  and 
foreign  matter  from  the  surface  of  the  water. 
Where  skimmers  are  used  for  private  pools,  there 
shall  be  at  least  one  skimming  device  for  each 
1,000  square  feet  (93  m2)  of  surface  area  or 
fraction  thereof.  For  public  pools  where  water 
skimmers  are  used,  there  shall  be  at  least  one 
skimming  device  for  each  600  square  feet  (55.8 
nr)  of  surface  area  or  fraction  thereof  Overflow 
gutters  shall  not  be  less  than  three  inches  (76  mm) 
deep  and  shall  be  pitched  to  a  slope  of  one  unit 
vertical  to  48  units  horizontal  (1:48)  toward 
drains,  and  constructed  so  that  such  gutters  are 
safe,  cleanable  and  that  matter  entering  the  gutters 
will  not  be  washed  out  by  a  sudden  surge  of 
entering  water. 

421.5.4  Walkways:    All  public  and  semi-public 

swimming  pools  shall  have  walkways  not  less  than 
four  feet  (1219  mm)  in  width  extending  entirely 
around  the  pool.  Curbs  or  sidewalks  around  any 
swimming  pool  shall  have  a  slip-resistant  surface  for 
a  width  of  not  less  than  one  foot  (305  mm)  at  the 
edge  of  the  pool,  and  shall  be  so  arranged  as  to 
prevent  return  of  surface  water  to  the  pool. 

421.5.5  Steps  and  ladders:  At  least  one  means  of 
egress  shall  be  provided  from  private  pools.  All 
public  and  semi-public  pools  shall  provide 
ladders  to  other  means  of  egress  at  both  sides  of 
the  diving  section  and  at  least  one  means  of  egress 
at  the  shallow  section;  or  at  least  one  means  of 
egress  in  the  deep  section  and  the  shallow  section 
if  diving  boards  are  not  provided.  Treads  of  steps 
and  ladders  shall  have  slip-resistant  surfaces  and 
handrails  on  both  sides,  except  that  handrails  are 
not  required  where  there  are  not  more  than  four 
steps  or  where  the  steps  extend  the  full  width  of 
the  side  or  end  of  the  pool.  (Refer  to  521  CMR 
19.00,  the  Architectural  Access  Board's  rules 
and  regulations,  for  requirements  pertaining  to 
the  accessibility  of  all  public  and  semi-public 
swimming  pools.) 

421.6  Watersupply:  All  swimming  pools  shall  be 
provided  with  a  potable  water  supply,  free  of  cross 
connections  with  the  pool  or  its  equipment. 


421.6.1  Water  treatment:  All  public  and  semi- 
public  swimming  pools  shall  be  designed  and 
installed  so  that  there  is  a  pool  water  turnover  at 
least  once  every  eight  hours.  Filters  shall  not 
filter  water  at  a  rate  in  excess  of  three  gallons  per 
minute  per  square  foot  (0.0020  nrVs  nr)  of  surface 
area.  The  treatment  system  shall  be  designed  and 
installed  so  that  at  all  times  when  the  pool  is 
occupied,  the  water  is  provided  with  excess 
chlorine  of  not  less  than  0.4  parts  per  million 
(ppm)  or  more  than  0.6  ppm,  or  excess 
chloramine  between  0.7  and  1.0  ppm,  or 
disinfection  shall  be  provided  by  other  approved 
means.  Acidity/alkalinity  of  the  pool  water  shall 
not  be  below  7.0  or  more  than  7.5.  All 
recirculating  systems  shall  be  provided  with  an 
approved  hair  and  lint  strainer  installed  in  the 
system  ahead  of  the  pump. 

Private  swimming  pools  shall  be  designed  and 
installed  so  that  there  is  a  pool  water  turnover  at 
least  once  every  18  hours.  Filters  shall  not  filter 
water  at  a  rate  in  excess  of  five  gallons  per  minute 
per  square  foot  (0.0034  mVs  nr)  of  surface  area. 
The  pool  owner  shall  be  instructed  in  the  care  and 
maintenance  of  the  pool  by  the  supplier  or 
builder,  including  treatment  with  high-test 
calcium  hypochlorite  (dry  chlorine),  sodium 
hypochlorite  (liquid  chlorine)  or  equally  effective 
germicide  and  algicide,  and  the  importance  of 
proper  pH  (alkalinity  and  acidity)  control. 

421.6.2  Drainage  systems:  The  swimming  pool 
and  equipment  shall  be  equipped  to  be  emptied 
completely  of  water  and  the  discharged  water 
shall  be  disposed  of  in  an  approved  manner  that 
will  not  create  a  nuisance  to  adjoining  property. 

421.7  Appurtenant  structures:  All  appurtenant 
structures,  installations  and  equipment,  such  as 
showers,  dressing  rooms,  equipment  houses  or  other 
buildings  and  structures,  including  plumbing, 
heating  and  air  conditioning  systems,  shall  comply 
with  all  applicable  requirements  of  780  CMR 
applicable  zoning  Imvs  and  requirements,  105 CMR 
435.000:  Minimum  Standards  for  Swimming 
Pools  (State  Sanitary  Code:  Chapter  V),  248  CMR 
2.00  :  the  State  Plumbing  Code,  and  527  CMR 
12. 00:  the  State  Electrical  Code 

421.7.1  Accessories:  All  swimming  pool 
accessories  shall  be  designed,  constructed  and 
installed  so  as  not  to  be  a  safety  hazard. 
Installations  or  structures  for  diving  purposes 
shall  be  properly  anchored  to  insure  stability. 

421.8  Equipment  installations:  Pumps,  filters  and 
other  mechanical  and  electrical  equipment  for  public 
swimming  pools  shall  be  enclosed  in  such  a  manner 
as  to  provide  access  only  to  authorized  persons  and 
not  to  bathers.  Construction  and  drainage  shall  be 
arranged  to  avoid  the  entrance  and  accumulation  of 
water  in  the  vicinity  of  electrical  equipment. 


90 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  S I" ANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


421.9  Enclosures  for  outdoor,  inground  public  and 
semi-public  swimming  pools     Outdoor,  inground 

public  semi-public  swimming  poois  shall  be 
provided  with  an  enclosure  in  accordance  with 
M.G.L  c.  140,  §206. 

421.9.1  Enclosure  for  public  and  semi- public 
outdoor,  inground  swimming  pools .  Every  public 
and  semi-public  outdoor,  inground  shimming 
pool  shall  be  enclosed  by  a  fence  six  feet  in 
height  and  firmly  secured  at  ground  level 
provided  that  any  board  or  stockade  fence  or 
structure  shall  be  at  least  five  feet  in  height,  but 
if  over  five  feet  in  height,  the  fence  shall  be 
chain  link.  Such  enclosure,  including  gates 
therein,  shall  not  be  less  than  six  feet  above  the 
ground,  and  any  gate  shall  be  self-latching  with 
latches  placed  four  feet  above  the  ground  or 
otherwise  made  inaccessible  from  the  outside  to 
children  up  to  eight  years  of  age.  Such 
enclosure  shall  be  constructed  of  such  material 
and  maintained  so  as  not  to  permit  any  opening 
in  said  enclosure,  other  than  a  gate,  wider  than 
three  inches  at  any  point  along  the  enclosure 
Any  such  pool  shall  be  equipped  with  at  least 
one  life  ring  and  rescue  hook, 

421.9.1.1  Enclosure  for  all  other  public  and 
semi-public  swimming  pools:  The  enclosure 
shall  extend  not  less  than  four  feet  (1219  mm) 
above  the  ground  All  gates  shall  be  self- 
closing  and  self-latching  with  latches  placed 
at  least  four  feet  (1219  mm)  above  the 
ground. 

421.9.2  Construction  of  enclosure  for  all  other 
public     and     semi-public     shimming    pools 

Enclosure  fences  shall  be  constructed  so  as  to 
prohibit  the  passage  of  a  sphere  larger  than  four 
inches  (102  mm)  in  diameter  through  any  opening 
or  under  the  fence.  Fences  shall  be  designed  to 
withstand  a  horizontal  concentrated  load  of  200 
pounds  (91  kg)  applied  on  a  one-square-foot 
(0.093  m2)  area  at  any  point  of  the  fence. 

421.9.3  Alternative  devices  A  natural  barrier, 
pool  cover  or  other  protective  device  approved  by 
the  governing  body  shall  be  an  acceptable 
enclosure  as  long  as  the  degree  of  protection 
afforded  by  the  substituted  device  or  structure  is 
not  less  than  the  protection  afforded  by  the 
enclosure,  gate  and  latch  described  herein. 

421.10  Enclosures  for  private  swimming  pools, 
spas  and  hot  tubs  In  lieu  of  any  zoning  laws  or 
ordinances  to  the  contrary,  private  swimming  pools, 
spas  and  hot  tubs  shall  be  enclosed  in  accordance 
with  780  CMR  421.1  0.1  through  421.10.4  or  by 
other  approved  barriers. 

421.10.1  Outdoor  private  swimming  pool    An 

outdoor  private  swimming  pool,  including  an  in- 
ground,  aboveground  or  on-ground  pool,  hot  tub 


or  spa  shah  be  provided  with  a  barrier  which  shall 
comply  with  the  following. 

1.  The  top  of  the  barrier  shall  be  at  least  48 
inches  (1219  mm)  above  finished  ground  level 
measured  on  the  side  of  the  barrier  which  faces 
away  from  the  swimming  pool.  The  maximum 
vertical  clearance  between  finished  ground 
level  and  the  barrier  shall  be  two  inches  (51 
mm)  measured  on  the  side  of  the  barrier  which 
faces  away  from  the  swimming  pool.  Where 
the  top  of  the  pool  structure  is  above  finished 
ground  level,  such  as  an  above-ground  pool, 
the  barrier  shall  be  at  finished  ground  level, 
such  as  the  pool  structure,  or  shall  be  mounted 
on  top  of  the  pool  structure.  Where  the  barrier 
is  mounted  on  top  of  the  pool  structure,  the 
maximum  vertical  clearance  between  the  top  of 
the  pool  structure  and  the  bottom  of  the  barrier 
shall  be  four  inches  (102  mm). 

2.  Openings  in  the  barrier  shall  not  allow 
passage  of  a  four-inch  (102  mm)  diameter 
sphere. 

3.  Solid  barriers  shall  not  contain  indentations 
or  protrusions  except  for  normal  construction 
tolerances  and  tooled  masonry  joints. 

4.  Where  the  barrier  is  composed  of 
horizontal  and  vertical  members  and  the 
distance  between  the  tops  of  the  horizontal 
members  is  less  than  45  inches  (1 143  mm),  the 
horizontal  members  shall  be  located  on  the 
swimming  pool  side  of  the  fence.  Spacing 
between  vertical  members  shall  not  exceed  PA 
inches  (44  mm)  in  width.  Decorative  cutouts 
shall  not  exceed  PA  inches  (44  mm)  in  width. 

5.  Where  the  barrier  is  composed  of 
horizontal  and  vertical  members  and  the 
distance  between  the  tops  of  the  horizontal 
members  is  45  inches  (1143  mm)  or  more, 
spacing  between  vertical  members  shall  not 
exceed  four  inches  (102  mm).  Decorative 
cutouts  shall  ;:ot  exceed  PA  inches  (44  mm)  in 
width. 

6.  Maximum  mesh  size  for  chain  link  fences 
shall  be  a  l'/i-inch  (32  mm)  square  unless  the 
fence  is  provided  with  slats  fastened  at  the  top 
or  the  bottom  which  reduce  the  openings  to  not 
more  than  BVinches  (44  mm). 

7  Where  the  barrier  is  composed  of  diagonal 
members,  such  as  a  lattice  fence,  the  maximum 
opening  formed  by  the  diagonal  members  shall 
be  not  more  than  PA  inches  (44  mm). 
8.  Access  gates  shall  comply  with  the 
requirements  of  780  CMR  421  10.1  items  1 
through  7,  and  shall  be  equipped  to 
accommodate  a  locking  device.  Pedestrian 
access  gates  shall  open  outwards  away  from 
the  pool  and  shall  be  self-closing  and  have  a 
self-latching  device.  Gates  other  than 
pedestrian  access  gates  shall  have  a  self- 
latching  device  Where  the  release  mechanism 
of  the  self-latchinn  device  is  iocated  less  than 


Z7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


54  inches  (1372  mm)  from  the  bottom  of  the 
gate:  (a)  the  release  mechanism  shall  be 
located  on  the  pool  side  of  the  gate  at  least 
three  inches  (76  mm)  below  the  top  of  the  gate; 
and  (b)  the  gate  and  barrier  shall  not  have  an 
opening  greater  than  Vz  inch  (13  mm)  within  1 S 
inches  (457  mm)  of  the  release  mechanism. 

9.  Where  a  wall  of  a  dwelling  serves  as  part  of 
the  barrier,  one  of  the  following  shall  apply: 

9.1.  All  doors  with  direct  access  to  the  pool 
through  that  wall  shall  be  equipped  with  an 
alarm  which  produces  an  audible  warning 
when  the  door  and  its  screen,  if  present,  are 
opened.  The  alarm  shall  sound 
continuously  for  a  minimum  of  30  seconds 
immediately  after  the  door  is  opened.  The 
alarm  shall  have  a  minimum  sound  pressure 
rating  of  S5  dBA  at  ten  feet  (304S  mm)  and 
the  sound  of  the  alarm  shall  be  distinctive 
from  other  household  sounds  such  as  smoke 
alarms,  telephones  and  door  bells.  The 
alarm  shall  automatically  reset  under  all 
conditions.  The  alarm  shall  be  equipped 
with  manual  means,  such  as  touchpads  or 
switches,  to  deactivate  temporarily  the 
alarm  for  a  single  opening  from  either 
direction.  Such  deactivation  shall  last  for 
not  more  than  15  seconds.  The  deactivation 
touchpads  or  switches  shall  be  located  at 
least  54  inches  (1372  mm)  above  the 
threshold  of  the  door. 

9.2.  The  pool  shall  be  equipped  with  an 
approved  power  safety  cover. 

10.  Where  an  above-ground  pool  structure  is 
used  as  a  barrier  or  where  the  barrier  is 
mounted  on  top  of  the  pool  structure,  and  the 
means  of  access  is  a  fixed  or  removable  ladder 
or  steps,  the  ladder  or  steps  shall  be  surrounded 
by  a  barrier  which  meets  the  requirements  of 
780  CMR  421.10.1  items  1  through  9.  A 
removable  ladder  shall  not  constitute  an 
acceptable  alternative  to  enclosure 
requirements. 

421.10.2  Indoor  private  swimming  pool:  All 

walls  surrounding  an  indoor  private  swimming 
pool  shall  comply  with  780  CMR  421.10.1,  item 
9. 

421.10.3  Prohibited  locations:  Barriers  shall  be 
located  so  as  to  prohibit  permanent  structures, 
equipment  or  similar  objects  from  being  used  to 
climb  the  barriers. 

421.10.4  Exemptions:  The  following  shall  be 
exempt  from  the  provisions  of  780  CMR  421 .0. 

1.  A  spa  or  hot  tub  with  an  approved  safety 
cover. 

2.  Fixtures  which  are  drained  after  each  use. 

421.1 1  Diving  boards:  Minimum  water  depths  and 
distances  for  diving  hoppers  for  pools,  based  on 
board  height  above  water,  shall  comply  with  Table 


42 1 . 1 1(1)  for  public  pools  and  Table  42 1 . 1 1  (2)  for 
private  pools. 

The  maximum  slope  permitted  between  point  D; 
and  the  transition  point  shall  not  exceed  one  unit 
vertical  to  three  units  horizontal  (1:3)  in  private  and 
public  pools.  D,  is  the  point  directly  under  the  end 
of  the  diving  boards.  D2  is  the  point  at  which  the 
floor  begins  to  slope  upwards  to  the  transition  point. 
See  Figure  421 . 1 1. 

Figure  421.11 

MINIMUM  WATER  DEPTHS  AND 

DISTANCES  BASED  ON  BOARD  HEIGHT 

FOR  ALL  PUBLIC,  SEMI  PUBLIC  AND 

PRIVATE  POOLS 

-TYPICAL    POSITION    OF  TIP 
OF    BOARD    RELATIVE   TO    PT. 

WATER    LINE 

PT.    C      PT.    D 


Table  421.1  1(1) 

MINIMUM  WATER  DEPTHS  AND 

DISTANCES  BASED  ON  BOARD 

HEIGHT  FOR  ALL  PUBLIC  POOLS 


Board  height 

Minimum  depth   at 

D  j  directly  under 

end  of  board 

Distance 
between 
D,  andD2 

Minimum 

depth   at 

D^ 

2'2"  (%  meter) 
2'6"  CA  meter) 
1  meter 
3  meter 

7'0" 

7"6" 
S'6" 

1 1 1>" 

S'0" 
9'0" 
10'0" 
I0'0" 

8'6" 
9'0" 
I0'0" 

irrr 

Note  a.   1  foot  =  3Q4:i  mm. 


Table  421.11(2) 

MINIMUM  WATER  DEPTHS  AND 

DISTANCES  BASED  ON  BOARD  HEIGHT 

FOR  PRIVATE  POOLS 


Board  height 

Minimum 
depth   atD| 
dircctlv  under 
end  of  board 

Distance 

between  D  [ 

andD2 

Minimum 
deptha  at  D-, 

l'8"  ('/=  meter) 

6'0" 

7'0" 

7'6" 

2'2"  (%  meter) 
2'6"  (Va  meter) 

6' 10" 

7'5" 

7'6" 
S'0" 

S'0" 
8'0" 

3'4"  fl  meter! 

8'6" 

0'0" 

9'0" 

Note  a.   1  foot  =  304.8  mm. 

780  CMR  4210  EXISTING  BUILDINGS 

422.1  Existing  Buildings:  See  780  CMR  34. 

422.2  Places  of  assembly 

422.2.1  Change  of  use:  An  existing  building  or 
structure  or  part  thereof  shall  not  be  altered  or 


92 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


converted  into  a  place  of  assembly  unless  it 
complies  with  the  provisions  of  780  CMR  34 
applicable  to  places  of  assembly. 

780  CMR  423.0  GROUP  RESIDENCE 

423.1  Scope:  Except  as  may  otherwise  be 
specifically  provided  for  in  780  CMR  423.0  ,  the 
requirements  of  780  CMR,  in  its  entirety,  and  as 
applicable,  shall  apply. 

423. 1. 1  Department  of  Mental  Retardation  (DMR) 
Group  Homes:  780  CMR  423. 0  shall  not  apply  to 
premises  operated  or  licensed  by  the  Department 
of  Mental  Retardation  (DMR)  pursuant  to 
115  CMR  7.00  and  8.00,  upon  the  completion  of 
a  DMR  safety  assessment  for  each  individual  and 
an  approved  safety  plan  for  each  location  where 
services  and  supports  are  provided  Such 
premises  shall  be  treated  as  conventional  R-4,  R- 
3,  R-2  and  R-l  use  as  applicable. 

423.2  Definition:  A  group  residence  is  a  premise 
licensed  by  or  operated  by  an  agency  of  the 
Commonwealth  of  Massachusetts  or  subdivision 
thereof  as  a  special  residence  for  those  who  are 
capable  of  self-preservation  in  the  following 
categories: 

1.  not  more  than  12  unrelated  persons  between 
the  ages  of  seven  and  15  years  of  age  inclusive;  or 

2.  not  more  than  25  unrelated  persons,  16  years 
of  age  or  over;  or 

3.  a  combination  of  780  CMR  423. 2  category  1 
and  2  above  consisting  of  not  more  than  18 
unrelated  persons  over  seven  years  of  age 
calculated  at  the  rate  of  two  such  persons,  or 
portion  thereof  from  Category  2  being  equal  to 
one  such  person  in  Category  1  all  in  accordance 
with  Table  423.2. 

Note:  In  determining  the  classification  for 
proposed  use,  group  residence  shall  not  be 
construed  as  being  similar  in  any  way  to  a  multi- 
family  dwelling,  two-family  dwelling,  boarding 
house,  lodging  house,  dormitory,  hotel,  school  or 
institution  of  any  kind.  For  building  code 
purposes,  it  shall  be  treated  as  a  single-family 
residential  building. 

Table  423.2 

Group  Residence  -  Maximum  Capacity, 

Combination  of  Categories 


Category 

Number 

Number  of  Residents  per  Category 

Category  1 

12 

11 

10 

9 

8 

- 

6 

5 

4 

3 

2 

1 

0 

Category  2 

0 

: 

4 

6 

5 

in 

12 

13 

14 

15 

16 

17 

25 

Maximum  total 
residents 

12 

IS 

14 

1? 

16 

17 

18 

IS 

18 

18 

18 

18 

25 

423.2.1  Special  definitions:  For  the  purpose  of 
780  CMR  423. 0,  the  following  terms  shall  be  defined 
exclusively  for  use  with  group  residences: 


Self  preservation:  Having  the  capability,  both 
mentally  and  physically,  to  take  action  to  preserve 
one's  own  life.  Specifically,  to  egress  the  building 
within  2':  minutes.  (Reference  inspection 
procedures  in  780  CMR  423.8  and 423.9.) 

Egress:  A  continuous  unobstructed  path  of  travel 
from  any  space  in  a  building  to  the  open  air 
outside  at  grade. 

Principal  means  of  egress:  The  primary  choice  of 
two  routes  normally  used  by  occupants  to  enter  or 
leave  a  building. 

Escape  route:  To  reduce  the  possibility  of 
entrapment  in  the  event  that  the  principal  means 
of  egress  is  blocked  by  fire  or  smoke,  an  escape 
route  shall  be  available  which  performs  in 
accordance  with  780  CMR  423.6  and  423.9.  In 
an  existing  building  where  a  second  means  of 
egress  is  physically  impractical  from  above  grade 
floors,  any  proven,  usable  path  to  the  open  air 
outside  at  grade  shall  be  deemed  acceptable, 
including  but  not  limited  to  connecting  doors, 
porches,  windows  within  six  feet  of  grade,  ramps, 
fire  escapes,  balcony  evacuation  systems,  etc. 

Authorized  inspectors:  The  state  or  local  building 
official  having  jurisdiction  and  a  representative  of 
the  licensing  or  operating  agency  having 
jurisdiction. 

Room:  See  definition  of  "Habitable  space"  and 
"Occupiable  room"  in  780  CMR  201.0. 

423.3  Existing  buildings:  The  requirements  of 

780  CMR  423.0,  sltall  also  apply  to  existing 

aw'elling  units  which  are  to  be  converted  to  a 

group  residence  and  alternative  requirements  set 

forth  m   780  CMR  34  that  conflict  with  the 

requirements  of  780  CMR  423. 0  shall  not  apply. 

423.3.1  Height  limitations:  Existing  buildings, 

of  Type  5B  construction,   greater  than  2' '_- 

stories,  or  35  feet  in  height  may  be  allowed  to 

be  used  (as  an  exception  to  Table  503)  as  a 

group  residence. 

423.4  Plans  and  specifications:  Plans  shall  be  filed 
with  the  building  official  having  jurisdiction  in 
accordance  with  780  CMR  110. 0  for  any  building  to 
be  constructed  as,  or  altered  for  use  as,  a  group 
residence  under  780  CMR  423. 0.  The  floor  plans 
shall  show  all  rooms,  spaces,  closets,  doors, 
corridors,  windows,  stairs  and  stairways,  hazardous 
vertical  openings  and  the  location  of  all  required 
fire  warning  equipment  and  proposed  fire 
suppression  equipment. 

423.5  Hazardous  contents:  Any  contents  which 
represent  a  fire  hazard  greater  than  that  which 
could  be  expected  of  ordinary  household 
fitmishings,  shall  not  be  allowed.  Storage  shall  not 
be  allowed  above  the  second  floor. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


93 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


423. 5. 1  Interior  finish:  Only  Class  I  and  Class  II 
interior  finish  materials  shall  be  allowed  in  the 
principal  means  of  egress.  In  refinishing  any 
other  area,  material  having  a  Class  III  flame 
spread  rating  shall  be  allowed  provided  it  does 
not  decrease  the  existing  rating.  The  smoke 
contribution  rating  of  any  material  shall  not 
exceed 450  (see  780  CMR  704.0). 

423.5.2  Exception:  In  existing  buildings,  the 
required  flame  spread  or  smoke  development 
classification  of  interior  surfaces  may  be  obtained 
by  applying  approved  fire  retardant  paints  or 
solutions  to  existing  interior  surfaces  having  a 
higher  flame  spread  rating  than  permitted 

423.6  Egress:  In  existing  buildings  there  shall  be 
one  means  of  egress  and  one  escape  route  serving 
each  floor,  remote  as  possible  from  each  other  and 
leading  to  grade.  The  stairway  between  the  first  and 
second  floors,  if  unenclosed  may  remain  unenclosed 
to  preserve  functional  and  aesthetic  requirements. 
In  new  construction,  two  means  of  egress  are 
required  in  accordance  with  the  One-  and 
Two-Family  Dwelling  Code,  and  stairways  above 
the  grade  floor  shall  be  enclosed  with  one  hour 
fireresistive  construction. 

Exception: 

1.  Where  the  Group  Residence  is  protected  with 
a  fire  suppression  system  according  to  NFiPA 
1 3D  or  better  as  listed  in  Appendix  A  only  one 
means  of  egress  shall  be  required  from  floors 
above  the  grade  floor  in  existing  buildings  and 
new  construction. 

2.  Where  the  Group  Residence  is  protected  with 
a  fire  suppression  system  according  to  NFiPA 
J3D  or  better  as  listed  in  Appendix  A  the 
enclosure  of  stairways  is  not  required 

423. 7  Fire  protection  systems 

423. 7.1  Hazardous  vertical  openings:  Openings 
to  such  spaces  as  laundry  chutes,  dumbwaiters, 
heating  plenums  or  combustible  concealed  spaces 
shall  be  permanently  blocked  with  one  hour 
construction,  as  regulated  by  the  provisions  of 
780  CMR  7. 

423.7.2  Automatic  fire  warning  systems:  An 

approved  automatic  fire  warning  system  shall  be 
provided  in  accordance  with  780  CMR  9. 

423. 8  Inspections:  There  shall  be  three  mandatory 
types  of  inspections  as  described  below.  The  results 
of  such  inspections  shall  be  on  file  in  the  office  of  the 
building  official  with  copies  sent  to  the  licensing  or 
operating  agency  on  a  prepared  checklist  and  signed 
by  the  authorized  inspectors. 

423.8.1  Temporary  certificate:  The  building 
official  shall  perform  plan  review  and 
post-construction  inspection  to  ensure  that  the 
building  conforms  to  780  CMR  He  shall  issue  a 


temporary  certificate  of  occupancy  effective  for 
90  days  only. 

423.8.2  Final  certificate:  Before  issuance  of  the 
final  certificate  of  occupancy,  the  authorized 
inspectors  shall  mutually  conduct  a  test  (see 
780  CMR  423.9.1)  to  ensure  that  the  occupants 
are  capable  of  self-preservation.  Upon  complete 
satisfaction  of  all  requirements,  the  building 
official  shall  then  issue  a  permanent  certificate  of 
occupancy.  This  test  shall  be  conducted  once  a 
year  in  accordance  with  780  CMR  106.5  for 
purposes  of  recertifying  both  the  building  and  the 
occupants. 

423. 9  Inspection  procedure:  The  building  and  the 
occupants'  capability  of  self-preservation  constitute 
a  system  of  life  safety  which  are  unique  for  each 
building  and  for  each  occupant  in  a  group 
residence.  Therefore,  a  simple  direct  test  is 
specified  herein  to  determine  the  capability  of  the 
occupant  and/or  the  suitability  of  the  building  as  a 
life  safety  system. 

423.9.1  Direct  test/fire  drill:  Afire  drill  shall  be 
conducted  as  the  direct  test  required  by  780  CMR 
423.9.  The  building  official  may  require  that  he 
be  present  for  the  fire  drill,  or  may  accept  an 
affidavit  signed  by  the  residence  manager  citing 
the  names  of  the  authorized  inspectors  present, 
the  names  of  the  occupants  who  participated,  the 
name(s)  of  any  occupants  who  failed  to  egress  the 
building  within  2V2  minutes,  the  date,  time  and 
place  where  said  fire  drill  was  held  During  the 
conduct  of  the  drill,  all  staff  personnel  of  the 
group  residence  shall  isolate  themselves  from  the 
occupants.  The  authorized  inspector(s),  when 
present,  shall  then  cause  to  be  blocked  any  one 
point  in  an  egress  route  where  the  choice  of  an 
alternate  route  is  possible,  to  simulate  a 
hazardous  condition,  and  the  internal  alarm 
system  shall  be  activated  for  2V2  minutes. 

423.9.2  Evaluation:  Any  occupant  who  fails  to 
escape  from  the  building  and  achieve  egress 
outside  the  building  at  ground  level  within  the  2'h 
minute  period  shall  not  be  permitted  to  remain 
living  in  the  residence. 

Note:  The  occupant  or  the  building  may  be  at 
fault:  therefore,  the  system  has  failed  to 
perform  adequately  to  provide  life  safety  and 
is,  consequently,  unacceptable  for  that 
occupant. 

423.9.3  Other  tests:  Other  tests  are  not  necessary 
and  shall  not  be  required  by  the  building  official. 
It  shall  be  the  responsibility  of  the  residence 
manager  of  the  group  residence  to  provide 
immediate  suitable  accommodations  elsewhere 
for  any  occupant  deemed  unacceptable  by  the 
building  official.  Each  occupant  must  be  certified 
at  regular  intervals  but  not  less  than  every 
quarter  at  the  group  residence  by  the  licensing  or 


94 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


operating  agency.  The  building  official  may 
require  an  inspection  at  his  discretion  when  he 
feels  that  either  the  building  or  the  occupant  may 
not  conform. 

423.10  Certificate  of  occupancy:  Any  certificate  of 
occupancy  issued  for  a  building  intended  to  be  used 
as  a  group  residence,  as  defined  in  780  CMR  423.2, 
shall  become  invalid  if  the  premises  have  not  been 
licensed  or  authorized  by  an  agency  of  the 
Commonwealth  of  Massachusetts  within  90  days  of 
the  date  of  issuance  of  the  certificate  of  occupancy. 

780  CMR  424. ODAY CARE  CENTERS 

424.1  General:  Day  care  centers  in  new  or  existing 
buildings  shall  be  subject  to  the  applicable 
provisions  of  780  CMR  and  the  special  requirements 
of  780  CMR  424.0. 

424.2  Definitions: 

Day  Care  Center:  Special  occupancies  in  which 

clients      receive      care,      maintenance,      and 

supervision   by  other  than  relatives  or  legal 

guardians  for  less  than  24  hours  per  day.    Such 

day  care  centers  include  both  child  day  care 

centers  and  adult  day  care  centers  licensed  by  the 

office  for  children  or  other  state  agencies  or 

otherwise  functioning  as  a  day  care  center. 

Child  Day  Care  Centers:  Falling  under  the 

requirements  of  780  CMR  424  and  being  a 

sub-set  of  day  care  centers,  shall  be  those  child 

day  care  centers  so  defined  in  780  CMR  202. 

Smoke  Stop  Portion:  For  purposes  of  780  CMR 
424.0,  a  smoke  stop  portion  shall  satisfy  the 
requirements  of  780  CMR  711.  Ofor  afire  portion. 

424.3  Use  Group  Classifications: 

424.3.1  Less  than  two  years  and  nine  months  in 
age:  Buildings  and  portions  thereof  licensed  by 
the  Office  for  Children  as  child  day  care  centers 
for  children  two  years  and  nine  months  in  age  or 
younger  shall  be  classified  as  1-2  use  group. 

424.3.2  More  than  two  years  and  nine  months  in 
age:  Buildings  or  portions  thereof  licensed  by  the 
Office  for  Children  as  child  day  care  centers  for 
children  more  than  two  years  and  nine  months  in 
age  shall  be  classified  as  E-use  group. 

424.3.3  Adult  Day  Care  Centers:  Buildings  or 
portions  thereof  licensed  by  agencies  of  the  state 
or  otherwise  operating  as  day  care  centers  and 
otherwise  not  classified  1-2  use  or  E-use  shall  be 
classified  as  B-use. 

Exception:  In  adult  day  care  centers  in  which 
clients  and  staff  cannot  evacuate  the  building 
with  or  without  assistance  in  three  minutes, 
such  adult  day  care  centers  shall  be  classified 


in  the  1-2  category  and  subject  to  1-2  use 
provisions  of  780  CMR  424.0. 

424.4  General  Provisions: 

424.4.1  Means  of  Egress:  Day  Care  Centers  in 
new  and  existing  buildings  or  portions  thereof 
shall  conform  to  the  means  of  egress  requirements 
as  set  forth  in  780  CMR  10  and  780  CMR  34  as 
applicable  and  otherwise  noted  below  in 
780  CMR  424.0. 

424.4.1.1  Exit  Signs  and  Means  of  Egress 
Lighting:  Exit  signs  and  means  of  egress 
lighting  shall  conform  to  the  requirements  of 
780  CMR  1023. 0  and  1024. 0  as  applicable. 

424.4.1.2  Roof  Egress:  Where  the  roof  of-a 
building  is  used  as  part  of  the  day  care  center, 
required  means  of  egress  from  the  roof  shall 
consist  of  two  enclosed  stairways:  complying 
as  exits  and  providing  two  separate  protected 
ways  of  travel  to  exit  discharges:  or  the 
required  means  of  egress  from  the  roof  shall 
consist  of  one  enclosed  stairway  complying  as 
an  exit  providing  a  protected  way  of  travel  to 
an  exit  discharge  and  a  protected  stairway 
from  the  roof  leading  to  a  corridor  on  the 
floor  directly  below  the  roof  and  such  corridor 
shall  lead  to  two  remote  and  independent  exits. 
Stairways  shall  comply  with  the  requirements 
of  780  CMR  10  except  as  noted  on  780  CMR 
424.4.2. 

424.4.1.2.1  Additional  Roof  Space 
Requirements:  Where  a  roof  is  used  by  a 
day  care  center,  there  shall  be  a  solid 
smooth  non-climbable  fence  or  barrier  a 
minimum  of  seven  feet  high  on  all  sides  and 
separating  the  day  care  center  area  from 
any  other  uses.  Fences  shall  be  set  back  at 
least  three  feet  from  the  outside  edge  of  the 
exterior  wall  below.  A  waterproof  telephone 
or  equivalent  means  of  communication  shall 
be  located  on  the  roof  for  use  in 
emergencies  and  shall  be  openable  without 
keys,  coins,  or  special  knowledge. 

424.4.1.3  Doors:  All  required  means  of  egress 
doors  shall  be  at  least  36  inches  in  width.  All 
other  doors  shall  be  at  least  32  inches  in  width. 

Exception:  Where  the  occupant  load  as 

calculated  in  accordance  with  780  CMR 

1008,  requires  door  widths  in  excess  of  36 

inches;    door  widths  shall  conform  to  the 

requirements  of  780  CMR  1017.3. 

424.4.1.4 Handrails:  Handrails  shall  conform 

to  the  requirements  of  780  CMR  1022.0  and 

when   the  day  care   center  clients  include 

children,  in  addition  to  an  upper  handrail,  a 

lower  handrail  shall  be  installed  between  20  " 

and  24"  above  the  nosing  of  the  stair  tread. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


95 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


424.4.1.5  Guards:  Guards  shall  conform  to 
the  requirements  of  780  CMR  1021. 0. 

424.4.1.6  Stairways:  Stairways,  whether 
required  means  of  egress  interior  or 
exterior  stairways  or  supplemental 
stairways,  shall  comply  with  the 
requirements  of  780  CMR  1014.0  and 
780  CMR  34. 0  as  applicable. 

Exception:  Existing  stairways  shall  not 
be  required  to  satisfy  the  requirements  of 
780  CMR  1014.6  unless  so  required  by 
the  Building  Official  in  accordance  with 
780  CMR  3400.4  or  3400.5. 

424.4.2  Mixed  Use-  New  and  Existing  Buildings: 

424.4.2.1  Mixed  Use-  New  Construction:  In 
new  construction  mixed  use  buildings,  day  care 
centers  shall  conform  to  the  separation 
requirements  of  780  CMR  313. 0. 

424.4.2.2  Mixed  Use-  Existing  Buildings:  In 

mixed  use  existing  buildings  the  day  care 
center  walls  shall  conform  to  the  separation 
requirements  of  780  CMR  313.0  except  that  the 
floor  -  ceiling  assemblies  of  the  day  care  center 
for  the  780  CMR  313.1.2  separation  option 
shall,  as  a  minimum,  conform  as  follows: 

(a)  For  day  care  centers  located  above  any 
usable  space  -  the  floor  of  the  day  care 
center  shall  have  a  minimum  of  a  one  hour 
fireresistance  rating  in  buildings  of  Type 
2C,  3B  and  5  construction:  and  a  minimum 
of  a  two  hour  fireresistance  rating  in 
buildings  of  type  1,  2A,  2B,  3A  and  4 
construction. 

(b)  For  day  care  centers  located  below 
usable  space,  the  ceiling  of  the  day  care 
center  shall  have  at  least  a  one  hour 
fireresistance  rating  or  the  floor  above  shall 
be  equipped  with  smoke  detectors 
interconnected  to  the  day  care  center  fire 
warning  system  such  that  smoke  detector 
activation  on  the  floor  above  will  initiate 
alarm  in  the  day  care  center. 

424.4.2.3  Mixed  Day  Care  Use:  When  a  day 
care  center  contains  children  or  adults  of 
mixed  ages  such  that  it  would  be  classified  in 
both  1-2  and  B  or  E  and  B  use  groups,  the 
provisions  for  the  most  restrictive  use  shall 
apply  unless  the  building  or  portion  thereof 
satisfies  the  requirements  set  forth  in  780  CMR 
313.0. 

424.4.3  Elevator  Doors:      In   buildings  with 
elevators,  the  day  care  center: 

(1)  shall  not  be  exposed  directly  to  the 
elevator  doors  opening  from  the  elevator  shaft, 

(2)  at  least  one  of  the  required  means  of 
egress  shall  not  be  exposed  to  the  elevator 
openings. 

Elevator  door  openings  may  be  separated  by  two 
hour  fireresistance  rated  construction  creating 


elevator  lobbies  and  where  such  lobbies  exist,  of 
780  CMR  424.4.3(1)  and  (2)  are  deemed  satisfied. 

424. 4. 4  Fire  Protective  Signaling  Systems:  Fire 

protective  signaling  systems  shall  be  installed  m 
all  day  care  centers  and  shall  conform  to  the 
requirements  of  780  CMR  91 7. 0. 

Exception:  Residential  occupancies  identified 
in  780  CMR  424.4.5.  Exception  1. 

424.4.5  Automatic  Fire  Detection  Systems:  An 

automatic  fire  detection  system  shall  be  designed 
and  installed  in  accordance  with  the  requirements 
of  780  CMR  918.0;  780  CMR  424.4.2.2(b); 
780  CMR  424.4.5  and  780  CMR  424.5  as 
applicable. 

Exception  1:  Residential  occupancies  that 
incorporate  day  care  center  1-2  or  E-  or  B-Use 
and  otherwise  comply  with  all  applicable 
requirements  of  780  CMR  424.  have  a  day  care 
occupancy  not  exceeding  24  clients  and 
otherwise  do  not  have,  nor  are  required  to 
have,  fire  protection  systems  complying  with 
780  CMR  917  and  780  CMR  918  shall  be 
permitted  to  utilize  single  and  multiple  station 
smoke  detectors  in  accordance  with  780  CMR 
919.  In  such  instances  the  requirements  of 
780  CMR  923.2  shall  not  apply. 
Exception  2:  Single  story  buildings  or  portions 
thereof  with  day  care  occupancies  not 
exceeding  24  clients  and  which  otherwise 
comply  with  all  applicable  requirements  of 
780  CMR  424,  specifically  and  780  C.MR 
generally,  shall  be  required  to  utilize  fire 
protection  systems  complying  with  780  CMR 
917  and  780  CMR  918,  but  the  requirements  of 
780  CMR  923.2  shall  not  apply  unless  the 
building  fire  protection  systems  are  otherwise 
required  to  conform  to  the  requirements  of 
780  CMR  923. 

(Note  that  if  the  basement  or  cellar  of  such 
a  building  is  used  as  a  portion  of  the  day 
care  center,  this  exception  to  780  CMR 
424.4.4  shall  not  apply). 

424.4.5.1  Location  of  Detectors:  Smoke 
detectors  shall  be  installed  to  ensure  total 
coverage  of  the  day  care  center  and  also 
located  in  front  of  the  doors  to  the  stairways 
and  in  the  corridor  providing  required  means 
of  egress  on  all  floors  of  the  day  care  center, 
and  comply  with  the  smoke  detector 
manufacturers  listed  requirements. 

424.4.5.1.1  Zoning:  Specific  smoke 
detector  zoning  shall  be  in  accordance  with 
780  CMR  917.7.3  with  smoke  detectors 
spacing  no  greater  than  30 '  unless 
otherwise  allowed  via  manufacturer's 
listing  requirements. 

424.4.5.2  Compatibility:  Fire  protection 
signaling  systems  and/or  automatic  fire 
detection  systems  that  are  interfaced  shall 


96 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


be  listed  for  such  mechanical  and  electrical 
interfacing. 

424.4. 6  Story  Height  Limitations:  The  allowed 
basement  and  story  locations  of  day  care  centers 
in  new  and  existing  buildings  shall  be  limited  by 
the  provisions  of  780  CMR  424.5,  as  applicable  to 
the  use  group  classification  of  the  day  care 
center,  and  Table  780  CMR  424.4.6. 

Table  424.4.6 

PERMITTED  LOCATIONS  AND  REQUIRED 

SPRINKLER  PROTECTION  FOR 

DA  Y  CARE  CENTERS 

1-2  Child  Care  Occupancy  Children  Under  Two  Years  Nine 
Months  of  Age 


Floor  Level  of 
Child  Day  Care 
Center 

Building  Construction  Type 

1A 

IB 

2A 

2B 

2C 

3A 

3B 

4 

5A 

5B 

Basement   Cellar 

F 

P 

P 

P 

P 

P 

P 

P 

1 

P 

1st  Story 

P 

p 

P 

P 

P 

P 

P 

P 

P 

P 

2nd  Slon 

PS 

PS 

ps- 

S 

NP 

S 

NP 

S 

SP 

NP 

3rd  Slorv 

PS 

PS 

ps 

S 

\P 

S 

NP 

S 

NP 

NP 

4th  Story  and 
Higher 

NT 

NP 

NP 

NP 

NP 

NP 

NP 

XP 

NP 

NP 

E  Child  Care  Occupan 
Months  of  Age 

cy 

Children 

OverTM 

o  Years 

Nine 

Floor  Level  of 
Child  Day  Care 
Center 

Building  Construction  Type 

1A 

IB 

2A 

2B 

2C 

3A 

SB 

4 

5A 

5B 

Basement    Cellar 

P 

P 

F 

P 

P 

F 

P 

F 

F 

P 

1st  Story 

P 

P 

F 

F 

P 

F 

P 

P 

F 

P 

2nd  Story 

P 

P 

F 

P 

P 

F 

P 

F 

P 

P 

3rd  Story 

PS 

PS 

PS 

S 

NP 

S 

XP 

s 

XP 

XP 

4th  Slon 

PS 

PS 

PS 

S 

NP 

S 

XP 

S 

x: 

XP 

5th  to  7th  Story 

PS 

PS 

IS 

\P 

NP 

NP 

NP 

XP 

NP 

XP 

8th  Story  and 
Higher 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

NP 

B  -  Day  Care  Occupancy   Adult  (Elder)  Day  Care 


B-Use  day  care 
Facilities  are  not 
limited  in  where 
they  may  be 
located  in  a 
building 


Exception  (1): 

Adullt  day  care  centers  falling  under 
the  ■Exception  "  to  780  CMR  424.3.3 


Exception  (2): 

Adult  day  care  centers  of  mixed-care 
use  as  described  in  780  CMP.  424.4.2.3 


Key  to  Table 

P        =  Permitted 

NP     =  Not  Permitted 

S        =  Sprinklers  Required  /  See  780  CMR  424.5  for 

Special  Provisions 
PS      =  Partial  Sprinklers  Required  /  See  780  CMR 

424.5  for  Special  Provisions 

424.4.7  Heating  System:  Any  portable  or 
permanent  heater  in  spaces  occupied  by  clients 
shall  be  separated  from  the  occupied  space  by 
partitions,  guards,  screens,  or  other  means. 
Space  and  unit  heaters  using  combustible  fuels 
shall  be  prohibited  (Also  see  424.4.8) 

424. 4. 8  Boiler  Rooms:  Boilers,  furnaces  or  other 
fire  units  shall  be  enclosed  as  required  in  the 
BOCA  National  Mechanical  Code  listed  in 
Appendix  A.  Boiler  room  doors  shall  not  open 
into  occupied  areas. 


424.4.9  High  Hazard  Restrictions:  A  day  care 
center  shall  not  occupy  the  same  building  with,  or 
be  located  within  200  feet  of  a  high  hazard 
occupancy. 

424.4.10  Accessibility  for  Persons  with 
Disabilities:  Accessibility  requirements  shall  be 
in  accordance  with  521  CMR  as  listed  in 
Appendix  A. 

424.5  Special  Provisions: 

424.4.5.1  Application:  Special  provisions  for  1-2, 
E  and  B  use  day  care  centers  and  relating  to 
allowed  location,  special  egress  and  special 
alarm  requirements  are  found  in  780  CMR  424.5 

424.5.21-2  Use  Allowed  Basement/Cellar/Story 
Locations:  In  new  and  existing  buildings,  day 
care  centers  which  are  classified  in  the  1-2  use 
group  shall  comply  with  one  of  the  following 
compliance  options  listed  below.  All  required 
means  of  egress  for  day  care  centers  classified  in 
use  group  1-2  shall  lead  directly  to  grade. 

1.  The  location  of  the  day  care  center  shall 
be  limited  to  the  first  floor,  cellar  and/or 
basement;  or 

2.  In  buildings  of  Type  2B,  3 A  or  4 
construction  which  are  fully  sprinklered  and 
comply  with  the  special  provisions  of 
780  CMR  424.5.4.4,  the  day  care  center  shall 
be  located  no  higher  than  the  third  floor:  or 

3.  In  buildings  of  Types  1A,  IB  or  2A 
construction  and  are  either  fully  sprinklered, 
or  in  which  the  day  care  center  and  all  floors 
below  are  sprinklered.  the  day  care  center 
shall  be  located  no  higher  than  the  third 
floor. 

Notes: 

(1)  Also  see  780  CMR  Table  424.4.6. 

(2)  See  special  egress  requirements  of 
780  CMR  424.5.4. 

424.5.3  E-Use  Allowed  Basement/Cellar/Story 
Locations:  In  new  and  existing  buildings,  day 
care  centers  which  are  classified  in  the  E  use 
group  shall  comply  with  one  of  the  following 
compliance  options  listed  below.  All  required 
means  of  egress  for  day  care  centers  classified  in 
use  group  E  shall  lead  directly  to  grade 

1.  The  location  of  the  day  care  center  shall 
be  limited  to  the  second  floor;  first  floor  or 
cellar  and/or  basement,  or; 

2.  In  buildings  of  Type  2B,  3A  or  4 
construction  which  are  fully  sprinklered  and 
comply  with  the  special  provisions  of  Section 
780  CMR  424.5.4.4,  the  day  care  center  shall 
be  located  no  higher  than  the  fourth  floor; 
or; 

3.  In  buildings  of  Types  1A,  IB  or  2A 
construction  which  comply  with  the  special 
provisions  of  780  CMR  424.5.4.4  and  are 
either  fully  sprinklered,  or  in  which  the  day 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


97 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


care    center    and    all  floors    below    are 
sprinklered,   the  day  care  center  shall  be 
located  no  higher  than  the  seventh  floor. 
Notes: 

(1)  Also  see  780  CMR  Table  424. 4. 6. 

(2)  See  special  egress  requirements  of 
780  CMR  424.5.4. 

424.5.4  B-Use  Allowed  Basement/Cellar/Story 

Locations:  In  day  care  centers  classified  in  the 

B-Use  category  and  where  staff  and  clients  in  an 

emergency  can  exit  the  building  in  no  more  than 

three  minutes,  with  or  without  assistance,  there 

is  no  restriction  on  locating  of  the  day  care 

center  within  any  basement/cellar  or  story. 

Exception:       In    adult    day    care    centers 

classified  as  day  care  1-2  use  see  780  CMR 

424.3.3. 

424. 5.41-2  and  E  Use  Egress  Requirements  For 
Basement  and  Cellar  Use: 

424.5.4.1  Basement  or  Cellar  Use:  A 
basement  or  cellar,  as  defined  in  780  CMR  2, 
of  a  building  of  Type  3B  or  SB  construction 
may  be  used  for  a  day  care  center  in 
accordance  with  the  following  requirements: 

1.  There  shall  be  two  separate  and 
independent  means  of  egress,  remote  from 
each  other  and  leading  directly  to  grade, 
or; 

2.  there  shall  be  two  separate  and 
independent  means  of  egress,  remote  from 
each  other  and  leading  to  two  one  hour 
fire-rated  enclosed  stairways  not  more  than 
four  feet  in  height  vertically  which  lead 
directly  to  grade  and  are  separated  from 
any  other  use  as  an  egress  by  one  hour 
fire-rated  partitions  and  self-closing  doors, 
or; 

3.  A  combination  ofl  and  2. 

424.5.4.2  Fire  Protective  Systems:  Fire 
protection  systems  shall  comply  with  the 
requirements  of  780  CMR  424.4.4  and 
424.4.5;  additionally  in  basement  or  cellar 
use,  regardless  of  building  construction  type, 
smoke  detectors  shall  be  located  in  the  first 
story  above  the  basement  or  cellar  location 
and  in  any  story  below  grade  that  may  exist 
below  the  basement  or  cellar  day  care 
location.  Such  smoke  detectors  shall  be 
connected  to  the  day  care  automatic  fire 
detection  system. 

424.5.4.3  Common  Corridor  Exit  Access  in 
Buildings  of  Types  1,  2A  and  2B 
Construction:  In  buildings  equipped  with  a 
fire  suppression  system  in  conformance  with 

780  CMR  9,  a  common  exit  access  corridor 
shall  be  acceptable  for  providing  access  to  two 
means  of  egress  required  in  780  CMR 
424.4.1,  such  common  corridors  used  for 


exitway  access  may  be  subdivided,  to  provide 
separate  and  independent  exitway  access  by 
using  smoke  stop  portions  complying,  as 
applicable,  with  the  provisions  of  780  CMR 
711. 0  for  fire  partitions.  Access  through 
interconnected  rooms  to  either  side  of  the 
smoke  stop  partition,  as  provided  in  780  CMR 
424.4,  shall  be  allowed  as  a  method  of 
complying  with  780  CMR  424.5.4.3.  If  the 
doors  in  the  smoke  stop  partitions  are 
normally  open,  such  doors  shall  be  equipped 
with  an  automatic  hold  open  device,  actuated 
by  either  the  building  fire  protective  signaling 
system  and/or  the  building  automatic  fire 
detection  system  to  close  automatically. 

424.5.4.4  1-2  and  E  use  Day  Care  Centers 
Located  in  Upper  Stories  of  a  Building:  In 
new  and  existing  buildings  containing  1-2  day 
care  occupancies  where  the  day  care  center  is 
located  above  the  first  floor,  and  in  new  and 
existing  buildings  containing  E  use  day  care 
occupancies  and  where  the  day  care  center  is 
located  above  the  third  floor,  the  day  care 
center  shall  meet  also  the  requirements  of 
780  CMR  424. 5. 4. 5  thru  780  CMR  424. 5. 4. 7. 

424.5.4.5  Telephone  communication:  The 
day  care  center  shall  have  telephones  located 
in  every  occupied  room  of  the  day  care  center 
and  directly  connected  to  the  building  fire 
command  center  or  to  a  constantly  attended 
station  within  the  building,  if  such  exists,  or 
otherwise  such  telephones  shall  utilize 
standard  phone  service  with  such  phones 
having  the  capability  of  retaining,  and  upon 
manual  selection,  automatically  dialing  the 
emergency  number  of  the  fire  department 
having  jurisdiction. 

424.5.4.6  Alarm  requirements:  In  addition  to 
the  requirements  of  780  CMR  424.4.4  and 
424.4.5,  on  the  floor  of  the  day  care  center 
and/or  the  floor  below,  the  operation  of  any 
water  flow  device,  manual  pull  station,  smoke 
or  heat  detector  will  initiate  a  special 
announcement  for  the  day  care  center  to 
evacuate  or  proceed  to  a  specific  area.  The 
language  of  the  announcement  shall  be 
acceptable  to  the  building  official  and  head  of 
the  fire  department  Smoke  detectors  shall  be 
installed  on  the  ceiling  of  the  floor  below  the 
day  care  center.  Manual  pull  stations  shall  be 
required  on  the  floor  located  below  the  care 
center. 

424.5.4.7  Areas  of  refuge:  In  new  and 
existing  buildings  containing  E  use  care  oc- 
cupancies where  the  day  care  center  is  located 
on  the  fourth  through  seventh  floors,  the  day 
care  center  shall  have  direct  access  to  a  sepa- 
rate area  which  shall  have  a  minimum  of  two 
hour  fireresistance  rated  construction  separa- 
ting it  from  the  rest  of  the  building.  The  area 
shall  adjoin  an  enclosed  stairway  with  afire 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


resistance  rating  of  at  least  two  hours.  The 
area  shall  be  sized  at  nine  square  feet  per 
person  to  accommodate  the  licensed  client 
capacity  and  staff  of  the  day  care  center.  This 
provision  shall  apply  to  all  centers  located  on 
the  sixth  or  seventh  floors  of  a  building  and  to 
those  centers  on  the  fourth  or  fifth  floors 
whose  licensed  capacity  exceeds  50  clients. 
(Also  see  Table  424.4.6.) 

780  CMR  425.0  SUMMER  CAMPS  FOR 
CHILDREN 

425.1  Definition:  Summer  camps  for  children 
include  premises,  operated  solely  between  April 
and  October  of  each  year  for  recreational  or  other 
purposes,  and  having  residential  facilities.  The  use 
of  such  accommodations  for  purposes  of 
inspection,  certification  and  inspection  fees  shall 
be  considered  as  being  similar  to  a  dormitory  in 
Use  Group  R-2  and  subject  to  the  following 
provisions  of  780  CMR  425.0 

425.2  New  and  existing  occupancies:  780  CMR 
425.0  shall  apply  to  existing  and  new  summer 
camps  for  children  as  defined  in  780  CMR  425.1. 

425.3  Means  of  egress:  All  one-story,  one-room 
buildings  having  1,000  square  feet  or  less  and 
having  25  occupants  or  less  shall  require  only  one 
means  of  egress  provided  that: 

1.  the  length  of  travel  does  not  exceed  50  feet 
from  any  point  in  the  building  to  the  outside  at 
grade;  and, 

2.  the  minimum  width  for  aisles  and  corridors 
shall  be  three  feet 

425.3.1  Emergency  escape:  Every  sleeping  room 
shall  have  at  least  one  exterior  door  or  openable 
window  to  permit  emergency  exit  or  rescue;  the 
windows  shall  conform  to  the  following 
restrictions: 

1.  must  be  openable  from  the  inside  without 
the  use  of  separate  tools; 

2.  the  sill  height  shall  not  be  more  than  36 
inches  above  the  finish  floor  and  with  a 
maximum  six  foot  drop  from  the  window  sill 
to  grade  below  the  window;  and 

3.  provide  a  minimum  net  clear  opening  area 
5.  7  square  feet  The  minimum  net  clear 
opening  height  dimension  shall  be  24  inches, 
The  minimum  net  clear  opening  width 
dimension  shall  be  20  inches. 

425.4  Fire  protection:  Smoke  detectors  shall  be 
required  for  existing  and  new  residential  units  in 
accordance  with  780  CMR  918.0  (919.0)  of 
780  CMR . 

Exception:  Tents  and  other  temporary  shelters 
which  are  designed  to  sleep  less  than  eight 
persons  and  which  have  an  open  side  consisting 
of  greater  than  1/6  of  the  perimeter  of  the  shelter 


or  which  have  built-in  provisions  for  emergency 
escape. 

425.5  Mechanical:  If  camps  are  heated,  then  the 
building  must  conform  to  all  applicable  code 
sections  and  specialized  codes,  notwithstanding  any 
of  the  provisions  in  780  CMR  425.0. 

425. 6  Enforcement  and  inspections:  Enforcement 
shall  be  by  the  local  building  official  who  shall 
inspect  and  certify  the  summer  camps  yearly,  prior 
to  season  opening.  Fees  charged  shall  be  in 
accordance  with  780  CMR 

780  CMR  426. 0  BULK  MERCHANDISING 
RETAIL  BUILDINGS 

426.1  General:  Bulk  Merchandising  Retail 
Buildings  have  different  fire  and  life  safety  risks 
than  traditional  retail  buildings.  This  difference 
requires  special  attention  to  fire  protection  and  life 
safety.  The  purpose  of  780  CMR  426.0  is  to 
provide  standards  to  adequately  deal  with  these 
differences,  and  to  reduce  the  risk  of  life  loss, 
injury,  and  excessive  property  damage  from  fire. 

426.2  Scope:  The  provisions  of  780  CMR  426.0 
shall  apply  to  buildings  or  structures  defined 
herein  as  Bulk  Merchandising  Retail  Buildings  or 
portions  thereof  containing  high  piled  combustible 
storage  as  defined  in  780  CMR  426.2.1.  Unless 
otherwise  noted  in  780  CMR  426.0,  the 
requirements  for  Bulk  Merchandising  Retail 
Buildings  shall  be  in  accordance  with  the 
requirements  set  forth  for  Use  Group  M, 
Mercantile  as  defined  in  780  CMR  309.0  or 
780  CMR  41 7. 0  (if  applicable). 

426.2.1  Definitions:  Terms  used  in  780  CMR 
426. 0  shall  have  the  following  meanings: 

Aerosol:  A  product  that  is  dispensed  from  a  metal 
can,  up  to  a  maximum  size  of  33.8  fl  oz  (1000 
ml)  or  a  glass  or  plastic  bottle,  up  to  a  maximum 
size  of  four  fl  oz  (118  ml)  that  is  designed  and 
intended  to  dispense  an  aerosol  by  a  propellant 
Aerosols  shall  be  classified  by  means  of  the 
calculation  of  their  chemical  heats  of 
combustion  and  shall  be  designated  Level  1, 
Level  2,  or  Level  3  in  accordance  with  Table 
426.2. 

Table  426.2 
AEROSOL  CLASSIFICATION 


Chemical  Heat  of  Combustion 


0-8,600  BTU/lb  (0-20  kJ/g) 

8,600-13,000  BTU/lb  (20-30  kJ/g) 

13.000  or  preater  BTU/lb  (30  or  greater  fcftfr) 


Aerosol 
Level 


Group  A  Plastics:  Products  that  utilize  plastic,  or 
non  plastic  products   that  utilize  significant 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


99 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


plastic  packaging  materials,  that  have  a  high 
BTU  content;  ABS  (acrylonitrile-butadiene- 
styrene  copolymer),  Acetal  (poly formaldehyde), 
Acrylic  (polymethyl  methacrylate),  Butyl  rubber, 
EPDM  (ethylene-propylene  rubber),  FRP 
(fiberglass  reinforced  polyester),  Natural  rubber 
(expanded),  Nitrile  rubber  (acrylonitrile- 
butadiene  rubber),  PET  or  PETE  (polyethylene 
terephthalate),  Polybutadiene,  Polycarbonate, 
Polyester         elastomer,  Polyethylene, 

Polypropylene,  Polystyrene  (expanded  and 
unexpanded),  Polyurethane  (expanded  and 
unexpanded),  PVC  (polyvinyl  chloride  greater 
than  15%  plasticized,  e.g.,  coated  fabric 
unsupported  film),  SAN  (styrene  acrylonitrile), 
SBR  (styrene-butadiene  rubber). 

Bulk  Merchandising  Retail  Buildings:  A  building 
where  sales  areas  contain  high  piled  combustible 
commodities,  or  high  piled,  high  hazard 
commodities  as  defined  by  780  CMR  4  and 
780  CMR  3. 

Combustible  Liquids:  Any  liquids  having  a 
flashpoint  at  or  above  100  °F  (38  °C)  shall  be 
known  as  Class  II  or  III  liquids.  Combustible 
liquids  shall  be  divided  into  the  following 
classification: 

Class  II  -  Liquids  with  a  flash  point  at  or  above 
100  °F  (37.8  "Q  and  below  140  °F  (60  °C). 
Class  III-A  -  Liquids  with  a  flash  point  at  or 
above  140  "F  (60  °Q  and  below  200  °F  (93.3  °C). 
Class  II1-B  -  Liquids  with  a  flash  point  at  or 
above  200  "F  (93.3  "Q. 

Control  Area:  Is  a  building  or  portion  of  a  building 
within  which  the  exempted  amounts  of 
hazardous  materials  are  allowed  to  be  stored, 
dispensed,  used,  or  handled 

Corrosive:  A  chemical  that  causes  visible 
destruction  of,  or  irreversible  alterations  in 
tissue  by  chemical  action  at  the  site  of  contact 
A  chemical  is  considered  to  be  a  corrosive  if, 
when  tested  on  the  intact  skin  of  albino  rabbits 
by  the  method  described  in  Appendix  A  ofCFR 
49,  Part  1 73,  it  destroys  or  changes  irreversibly 
the  structure  of  the  tissue  at  the  site  of  contact 
following  an  exposure  period  of  four  hours. 
This  term  does  not  refer  to  action  on  inanimate 
surfaces.  [Source:  Uniform  Fire  Code] 

Flammable  Liquids:  Any  liquids  having  a  flash 
point  below  100  °F  (38  °C),  and  having  a  vapor 
pressure  not  exceeding  40  psia  (276  kPa)  at 
100  "F  (38  °C).  Flammable  liquids  shall  be 
known  as  Class  I  liquids  and  shall  be  divided 
into  the  following  classification: 
I-A  Liquid  -  A  liquid  with  a  flash  point  below 
73  °F  (22.8  °Q  and  a  boiling  point  below  100  °F 
(37.8  °C). 


I-B  Liquid  -  A  liquid  with  a  flash  point  below 
73  °F  (22. 8  °C)  and  a  boiling  point  at  or  above 
100  "F  (37.8  "Q. 

I-C  Liquid  -  A  liquid  with  a  flash  point  at  or 
above  73  °F  (22. 8"Qand  below  1 00  "F  (3  7. 8  °C). 

High  Piled  Combustible  Commodity:  Storage  of 
combustible  materials  in  piles  greater  than  12 
feet  (3.658  m)  in  height  or  combustible  materials 
on  pallets,  in  racks  or  on  shelves  where  the  top 
of  storage  is  greater  than  12  feet  (3.658  m)  in 
height 

High  Piled,  High  Hazard  Commodity:  Storage  of 
combustible  materials  such  as  rubber  tires, 
Group  A  plastics,  flammable  liquids,  idle  pallets 
and  commodities  with  similar  heat  release 
characteristics  where  the  top  of  storage  is 
greater  than  six  feet  (1.829  m)  in  height 

Highly  Toxic:  Material  which  produces  a  lethal 
dose  or  lethal  concentration  which  falls  within 
any  of  the  following  categories. 

1.  A  chemical  or  substance  that  has  a  median 
lethal  dose  (LD50)  of  50  milligrams  or  less  per 
kilograms  of  body  weight  when  administered 
orally  to  albino  rats  weighing  between  200  and 
300  grams  each. 

2.  A  chemical  or  substance  that  has  a  median 
lethal  dosage  of  more  than  200  milligrams  or 
less  per  kilogram  of  body  weight  when 
administered  by  continuous  contact  for  24 
hours,  or  less  if  death  occurs  within  24  hours, 
with  bare  skin  of  albino  rabbits  weighing 
between  two  and  three  kilograms  each. 

3.  A  chemical  or  substance  that  has  a  median 
lethal  concentration  (LC50)  in  air  of  200  parts 
per  million  by  volume  of  gas  or  vapor,  or  two 
milligrams  per  liter  or  less  of  mist,  fume  or  dust, 
when  administered  by  continuous  inhalation  for 
one  hour,  or  less  if  death  occurs  within  one 
hour,  to  albino  rats  weighing  between  200  and 
300  grams  each. 

Mixtures  of  these  materials  with  ordinary 
materials,  such  as  water,  might  not  warrant 
classification  as  highly  toxic.  While  this  system 
is  basically  simple  in  application,  any  hazard 
evaluation  which  is  required  for  the  precise 
categorization  of  this  type  of  material  shall  be 
performed  by  experienced,  technically  competent 
persons. 

Oxidizer:  A  chemical  other  than  a  blasting  agent 
or  explosive  that  initiates  or  promotes 
combustion  in  other  materials,  thereby  causing 
fire  either  of  itself  or  through  the  release  of 
oxygen  or  other  gases. 

Class  1:  An  oxidizer  whose  primary  hazard  is  a 
slight  increase  in  the  burning  rate  but  which 
does  not  cause  spontaneous  ignition  when  the 


100 


780  CMR  -  Sixth  Edition 


2/7/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


oxidizer  comes  in  contact  -with  combustible 
materials. 

Class  2:  An  oxidizer  that  will  cause  a  moderate 
increase  in  the  burning  rate  or  that  is  capable  of 
causing  spontaneous  ignition  of  combustible 
materials  with  which  the  oxidizer  comes  in 
contact 

Class  3:  An  oxidizer  that  will  cause  a  severe 
increase  in  the  burning  rate  of  combustible 
materials  with  which  the  oxidizer  comes  in 
contact  or  that  will  undergo  vigorous  self- 
sustained  decomposition  due  to  contamination 
or  exposure  to  heat 

Class  4:  An  oxidizer  that  is  capable  of  an 
explosive  reaction  due  to  contamination  or 
exposure  to  thermal  or  physical  shock. 
Additionally,  the  oxidizer  will  enhance  the 
burning  rate  and  is  capable  of  causing 
spontaneous  ignition  of  combustibles.  [Source: 
BOCA] 

Rack  Storage:  Combination  of  vertical,  horizontal 
and  diagonal  members  that  support  stored 
materials  infixed  or  portable  racks. 

Shelf  Storage:  Storage  on  structures  less  than  30 
in.  (76.2  cm)  deep  with  shelves  usually  two  ft 
(0.6  m)  apart  vertically  and  separated  by 
approximately  30  in.  (76.2  cm)  aisles. 

Toxics:  A  material  which  produces  a  lethal  dose  or 
lethal  concentration  within  any  of  the  following 
categories: 

1.  A  chemical  or  substance  that  has  a  median 
lethal  dose  (LB 50)  of  more  than  50  milligrams 
per  kilograms  but  not  more  than  500  milligrams 
per  kilograms  of  body  weight  when  administered 
orally  to  albino  rats  weighing  between  200  and 
300  grams  each. 

2.  A  chemical  or  substance  that  has  a  median 
lethal  dosage  of  more  than  200  milligrams  per 
kilogram  but  not  more  than  1, 000  milligrams  per 
kilogram  of  body  weight  when  administered  by 
continuous  contact  for  24  hours ,  or  less  if  death 


occurs  within  24  hours,  with  bare  skin  of  albino 
rabbits  weighing  between  2  and  3  kilograms 
each. 

3.  A  chemical  or  substance  that  has  a  median 
lethal  concentration  (LC50)  in  air  more  than 
200  parts  per  million  but  not  more  than  2,000 
parts  per  million  by  volume  of  gas  or  vapor,  or 
more  than  two  milligrams  per  liter  but  not  more 
than  20  milligrams  per  liter  of  mist,  fume  or 
dust,  when  administered  by  continuous 
inhalation  for  one  hour,  or  less  if  death  occurs 
within  one  hour,  to  albino  rats  weighing  between 
200  and  300  grams  each. 

Unstable  (Reactive):  A  chemical  which  in  the  pure 
state,  or  as  produced  or  transported,  will 
vigorously  polymerize,  decompose,  condense  or 
become  self-reactive  under  conditions  of  shock, 
pressure  or  temperature 

Water  Reactive  Material:  Material  which  explodes; 

violently  reacts;  produces  flammable,  toxic  or 

other  hazardous  gases;  or  evolves  enough  heat 

to  cause  self-ignition  or  ignition  of  nearby 

combustibles    upon     exposure    to    water    or 

moisture. 

4263  Commodity  Classification:  Commodities  in 

storage    and    display    shall    be    classified    in 

accordance  with  the  following  NFPA  Standards  as 

listed  in  Appendix  A. 

13:  Installation  of  Sprinkler  Systems 

30:  Flammable  and  Combustible  Liquids  Code 

30B:    Aerosol    Products,    Manufacture    and 

Storage 

231:  General  Storage 

23 1C:  Rack  Storage  of  Materials 

231D:  Storage  of  Rubber  Tire 

430:  Storage  of  Liquid  and  Solid  Oxidizers 

426.4  Fire  Protection  Requirements:  Fire 
protection  requirements  shall  be  in  accordance 
with  Table  426.4. 


Table  426.4. 
FIRE  PROTECTION  REQUIREMENTS 


Commodity 
Class 

Size  of  High- 
Piled  Display 
Area    (sqft) 
x  0.0929  form 

Fire  Protection  Requirements 

Fire  Suppression 

System 
(780  CMR  426.5) 

Fire 
Alarm/Notification 
(780  CMR  426.14) 

Fire  Department 

Access  Doors 
(780  CMR  426.8) 

Hose  Connections 
(780  CMR  426.7) 

Manual  Smoke 
and  Heat  Vents 
(780  CMR  426.16 

0-2,500 

NR 

NR 

NR 

NR 

NR 

I-IV 

2,501  - 12,000 

Yes 

NR 

NR 

NR 

NR 

over  12,000 

Yes 

Yes 

Yes 

Yes 

Yes 

0-500 

NR 

NR 

NR 

NR 

NR 

High 

501  -  2.500 

Yes 

NR 

NR 

NR 

NR 

Hazard 

2,501  -  12,000 

Yes 

NR 

Yes 

Yes 

NR 

over  12.000 

Yes 

Yes 

Yes 

Yes 

Yes 

NR  =  Not  required. 

1.  For  commodity  classifications  definitions,  see  426.3. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


101 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

2.  Areas  that  are  separated  by  60  ft  of  display  area  with  such  areas  not  used  for  high  piled  storage,  or  that  are 
separated  with  a  one-hour  ftreresistance-rated  separation  barrier,  can  be  considered  as  separated  high  piled  areas. 

3.  If  the  building  is  required  to  be  sprinklered  under  780  CMR,  then  the  sprinkler  system  protecting  the  high  piled 
storage  area  and  IS  ft  beyond  shall  be  designed  in  accordance  with  the  appropriate  NFPA  Standardly 


426.5  Fire  Suppression  Systems:  Fire  sprinkler 
design  and  installation  shall  be  provided  in 
accordance  with  the  applicable  requirements  set 
forth  by  NFPA  13,  30,  30B,  231,  231C,  231D,  430, 
as  listed  in  Appendix  A,  or  other  nationally 
recognized  codes  and  standards,  or  tests  conducted 
in  test  laboratories  as  defined  in  527  CMR  49.03, 
Appendix  C  as  listed  in  Appendix  A 

426. 6  Storage  Arrangement:  Storage  arrangements 
for  fire  protection  purposes  shall  comply  with 
requirements  set  forth  by  NFPA  13,  30,  30B,  231, 
231C,  231D,  430,  as  listed  in  Appendix  A,  or  other 
nationally  recognized  codes  and  standards,  or  tests 
conducted  in  test  laboratories  as  defined  in  527 
CMR  49. 03,  Appendix  C,  as  listed  in  Appendix  A. 

426. 7  Hose  Connections:  A  Class  I  automatic, 
wet-standpipe  system  shall  be  provided  in 
accordance  with  NFPA  14.  Hose  connections  shall 
be  located  around  the  interior  perimeter  of  the 
building  within  five  ft  of  all  required  fire 
department  access  doors,  adjacent  to  the  latch  side 
of  the  door.  Hose  connections  shall  be  installed  to 
accommodate  200  ft  of  travel  distance  to  any  point 
in  the  building.  Where  the  most  remote  portion  of 
the  building  exceeds  200  ft  of  travel  distance  from 
the  required  access  doors,  additional  hose 
connections  shall  be  provided  in  locations 
approved  by  the  head  of  the  fire  department  Hose 
connections  shall  be  readily  accessible  and  marked 
for  fire  department  use  only.  When  approved  by 
the  head  of  the  fire  department,  the  following 
exceptions  shall  be  permitted. 

Exception  1:  Hose  connections  may  be  omitted 
when  the  following  fire  department  building 
access  and  fire  hydrant  coverage  is  provided: 
minimum  18  ft  wide,  unobstructed  access 
roadways  located  within  20  ft  of  the  building  on 
at  least  three  sides;  minimum  ten  ft  wide, 
unobstructed  access  route  between  the  access 
roadway  and  the  fire  department  access  doors; 
and,  fire  hydrants  in  locations  approved  by  the 
head  of  the  fire  department 

Exception  2:  In  lieu  of  a  Class  I  standpipe 
system,  a  Class  II  automatic,  wet-standpipe 
system  in  accordance  with  NFPA  14  shall  be 
permitted  when  the  following  fire  department 
building  access  and  fire  hydrant  coverage  is 
provided:  minimum  18  ft  wide,  unobstructed 
access  roadways  located  within  50  ft  of  the 
building  on  at  least  three  sides;  minimum  ten  ft 
wide,  unobstructed  access  route  between  the 
access  roadway  and  the  fire  department  access 
doors;  and,  fire  hydrants  in  locations  approved 
by  the  head  of  the  fire  department    The  hose 


connections  shall  be  located  as  described  above 
for  the  Class  I  standpipe  system.  Occupant  hose 
shall  not  be  required,  and  the  hose  connections 
shall  be  marked  for  fire  department  use  only. 

426.8  Fire  Department  Access  Door:  Fire 
department  access  doors  shall  be  provided  for  fire 
department  emergency  access.  Access  doors  shall 
be: 

1.  located  adjacent  to  fire  department  access 
roadways, 

2.  provided  with  an  approved  exterior  fire 
department  accessible  key  cylinder  operable  lock 
device, 

3.  provided  with  approved  fire  department 
identification  signs,  and 

4.  provided  such  that  all  points  of  the  floor 
area  are  accessible  within  200  feet  of  travel 
distance 

Fire  department  access  doors  may  be  used  as 
occupant  egress  doors. 

426.9  Fire  Department  Access  Roadways:  Fire 
department  access  roadways  shall  be  provided  on  at 
least  two  sides  of  the  building  with  such  access  to 
be  approved  by  the  head  of  the  fire  department 
prior  to  any  construction.  Fire  hydrants  shall  be 
provided  in  locations  approved  by  the  head  of  the 
fire  department 

426.10  Means  of  Egress:  Means  of  egress  shall  be 
in  accordance  with  the  requirements  set  forth  in 
780  CMR  10  for  Use  Group  M,  Mercantile  unless 
otherwise  modified  herein: 

Exception:  Exit  access  travel  distance  shall  be 
limited  to  200  feet 

If  the  only  means  of  customer  entrance  is  through 
one  exterior  wall  of  the  building,  two  thirds  of  the 
required  egress  width  shall  be  located  in  this  wall 
At  least  one  half  of  the  required  exits  shall  be 
located  so  as  to  be  reached  without  passing  through 
checkout  stands.  In  no  case  shall  checkout  stands 
or  associated  railings  or  barriers  obstruct  exits, 
required  aisles,  or  approaches  thereto. 

426.11  Flammable/Combustible  Liquids:  The 
display,  storage,  protection,  and  maximum 
allowable  quantities  of  flammable  and  combustible 
liquids  permitted  in  mercantile  display  areas  shall 
be  in  accordance  with  NFPA  30,  as  listed  in 
Appendix  A. 

426.12  Aerosols:  The  display,  storage,  protection, 
and  maximum  allowable  quantities  of  aerosols 
permitted  in  mercantile  occupancies  shall  be  in 
accordance  with  of  NFPA  30B. 


102 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


Table  426.13. 
DENSITY  FACTOR  FOR  HAZARDOUS  MATERIALS  EXEMPTION  CALCULATIONS. 


Material 

Class 

Solids  pounds 
(cubic  feet) 

Liquid  gallons 
(pounds) 

Gas  cubic  feet 

x  0.4536  for  kg 
(x  28.32  for  liters) 

x 3.78  for  liters 
(x  0.4536  for  kg) 

x  28.32  for  liters 

Oxidizers 

4 
3 

2 
1 

Not  permitted 
0.75 
1.5 
12 

Not  Permitted 
(0.75) 
(1.5) 
(12) 

Not  Permitted 

112.5 

9 

4.5 

Unstable  (reactive) 

4 

3 
2 
1 

Not  Permitted 

0.375 

0.3 

Unlimited 

Not  Permitted 

(0.375) 

(0.3) 

Unlimited 

Not  Permitted 

3.75 
1.5 

2.25 

Toxics 

All 

0.65 

(0.65) 

1.053 

Corrosives 

All 

6.5 

0.65 

1.053 

Highlv  Toxic 

All 

0.0013 

(0.0013) 

0.026 

Water  Reactive 

3 

2 

I 

0.375 
0.3 

0.375 

(0.0375) 
(0.3) 

(0.375) 

Not  Applicable 

1.    Quantities  may  be  increased  by  100%  in  sprinkler ed  buildings 


426.13  Non-flammable  and  non-combustible 
hazardous  materials:  Non-flammable  and  non- 
combustible  hazardous  materials  such  as: 
Oxidizers,  Unstable  Materials,  Toxics,  Highly 
Toxics,  Corrosives,  and  Water  Reactives  shall  meet 
the  following  requirements: 

Q  =  FxA 

where: 

Q  —  the  maximum  quantity  in  a  single  control 

area  for  mercantile  display. 

F  =  the  density  factor  as  indicated  in  Table 

426.13. 

A  =  the  area  occupied  for  mercantile  display. 

For  computation  purposes,  the  area  shall  not 

exceed  1,500  square  feet  (139.39  m  )  per  control 


426. 14  Fire  Alarm  or  Notification  Systems:  Either 
a  fire  alarm  system  or  emergency  notification 
system,  as  described  below  and  approved  by  the 
head  of  the  fire  department,  shall  be  provided: 

1.     Fire  Alarm  System:   The  fire  alarm  system 

shall  include  the  following: 

a.  Afire  alarm  system  required  for  life  safety 
shall  be  installed,  tested,  and  maintained  in 
accordance  with  applicable  requirements  of 
NFPA  70  and  72,  as  listed  in  Appendix  A. 

b.  All  systems  and  components  shall  be 
approved  for  the  purpose  for  which  installed, 
and  all  installation  wiring  or  other 
transmission  paths  shall  be  monitored  for 
integrity  in  accordance  with  NFPA  72,  as 
listed  in  Appendix  A. 

c.  Manual  fire  alarm  stations  shall  be 
provided  in  the  natural  path  of  escape  near 
each  required  exit  from  an  area.  Each 
manual  fire  alarm  station  shall  be  accessible, 
unobstructed,  visible,  and  of  the  same  general 
type. 


d  Notification  signals  for  occupants  to 
evacuate  shall  be  by  audible  and  visible 
signals  in  accordance  with  NFPA  72  and 
CABO/ANSI  All  7.1,  as  listed  in  Appendix  A. 
The  general  evacuation  alarm  signal  shall 
operate  throughout  the  entire  building, 
e.  The  fire  alarm  system  shall  be  arranged  to 
transmit  the  alarm  automatically  via  any  of 
the  following  means  acceptable  to  head  of  the 
fire  department  and  in  accordance  with 
NFPA  72: 

L  Auxiliary  Alarm  System 

il   Central  Station  Connection 

Hi.  Proprietary  System,  or 

iv.  Remote  Station  Connection, 
f  The  fire  alarm  control  panel  location  shall 
be  located  in  an  area  acceptable  to  the  head 
of  the  fire  department  Where  required,  a 
remote  annunciator  shall  be  located  in  an 
area  acceptable  to  the  head  of  the  fire 
department 

g.  Other  control  systems  intended  to  make 
the  protected  premises  safer  for  building 
occupants  including,  but  not  limited  to,  duct 
smoke  detectors,  fire/smoke  dampers,  smoke 
management  systems,  fire  door  controls,  shall 
be  installed  and  monitored  for  integrity  in 
accordance  with  NFPA  72,  as  listed  in 
Appendix  A,  and  a  distinctive  supervisory 
signal  shall  be  provided  to  indicate  a 
condition  that  would  impair  the  satisfactory 
operation  of  the  equipment 
h.  Supervisory  attachments  including,  but 
not  limited  to,  control  valves,  fire  pump 
running  conditions,  float  valves,  shall  be 
installed  and  monitored  for  integrity  in 
accordance  with  NFPA  72  as  lisctd  in 
Appendix  A,  and  a  distinctive  supervisory 
signal    shall    be   provided    to    indicate    a 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


condition  that  would  impair  the  satisfactory 
operation  of  the  equipment 
L  All  building  HVA  Cfans  shall  be  arranged 
to  automatically  shut  down  on  any  general 
alarm  condition.  Duct  smoke  detectors  shall 
not  be  required 

j.        Water/low  initiating  devices  shall  be 

arranged  to  initiate  an  alarm  condition  within 

one  minute  of  being  activated    In  addition, 

provisions  shall  be  made  to  control  and 

prevent  false  alarms  due  to  water  surges. 

2.    Emergency  Notification  System:  During  a 

fire   emergency,    the   emergency    notification 

system  shall  sound  an   audible  alarm  in   a 

continuously  attended  location  for  the  purpose 

of  initiating  the  evacuation  plan  required  under 

780  CMR  426.15. 

426.15  Evacuation  Planning  and  Training:  An 
evacuation  plan  shall  be  submitted  at  the  time  of 
application  for  a  building  permit  as  part  of  the 
required  documentation  pursuant  to  780  CMR  1. 
The  Certificate  of  Use  and  Occupancy  shall  not  be 
issued  until  the  evacuation  plan  has  been  revietved 
and  approved  by  the  head  of  the  fire  department 
Any  changes  to  the  evacuation  plan  shall  not  be 
effected  until  a  revised  plan  has  been  submitted  to 
and  approved  by  the  head  of  the  fire  department 
The  evacuation  plan  shall  detail  procedures,  define 
roles  and  responsibilities  of  employees,  and  shall 
include  an  egress  plan  indicating  routes  of  travel  to 
all  exits.  The  evacuation  plan  shall  be  used  to 
ensure  the  safe  evacuation  of  all  customers  and 
employees.  All  employees  shall  be  instructed  and 
periodically  trained  with  respect  to  their  duties,  as 
required  by  527  CMR  10.25,  as  listed  in 
Appendix  A. 

426.16  Smoke  and  Heat  Venting:  Adequate 
methods  of  manual  heat  and  smoke  venting  shall 
be  provided  The  method  of  operation,  vent  area, 
spacing  layout,  construction  of  vents  and  curtain 
boards  or  other  acceptable  means  of  addressing 
methods  of  heat  and  smoke  venting  shall  be 
determined  by  an  engineering  evaluation  and 
analysis.  The  analysis  shall  be  reviewed  and 
approved  by  the  head  of  the  fire  department  and 
shall  contain  sufficient  detail  to  evaluate  the 
hazard  and  effectiveness  of  the  venting  system. 

780  CMR  427.0  LIMITED  GROUP 
RESIDENCE 
427.1  General:  A  building  licensed  by  or  operated 
by  the  Department  of  Mental  Health  or  the  Office 
for  Children,  Commonwealth  of  Massachusetts  as 
a  limited  group  residence:  this  is  a  special 
residence  to  include  residents  not  capable 
self-preservation. 

427.1.1  Scope:  A  limited  group  residence  shall 
have  a  maximum  of  12  residents  who  are  at  least 
four  years  of  age.    Not  more  than  four  of  the 


residents  shall  be  impaired;  provided,  however, 
that  more  than  four  such  residents  may  be 
impaired  if  the  structure  complies  with  780  CMR 
427.2.  A  limited  group  residence  shall  be 
classified  in  the  R-5  use  category  for  code 
purposes. 

427.1.1.1  Department  of  Mental  Retardation 
(DMR)  Group  Homes:  780  CMR  427.0  shall 
not  apply  to  premises  operated  or  licensed  by 
the  Department  of  Mental  Retardation  (DMR) 
pursuant  to  115  CMR  7. 00  and  8. 00,  upon  the 
completion  of  a  DMR  safety  assessment  for 
each  individual  and  an  approved  safety  plan 
for  each  location  where  services  and  supports 
are  provided  Such  premises  shall  be  treated 
as  conventional  R-4,  R-3,  R-2  and  R-l  use  as 
applicable. 

427.1.2  Definitions:  The  following  terms  shall 
have  the  meaning  indicated  for  the  purpose  of 
780  CMR  427.0: 

Existing  building  or  structure:  Any  completed 
building  or  structure  which  has  been  legally 
occupied  and/or  legally  used  for  a  period  of  at 
least  five  years.  Structures  which  fail  to 
qualify  with  this  definition  shall  comply  with 
780  CMR  427.2. 

Resident:  A  client  in  need  of  care  who  resides  in 
the  limited  group  residence  of  the  licensing  or 
operation  agency.  Staff  are  not  considered  as 
residents  under  the  provisions  of  780  CMR 
42  7. 0.  The  licensing  agency  shall  classify  all 
residents  in  one  of  the  following  three 
categories: 

Impaired:  All  residents  not  capable  of 
self-preservation  through  physical,  mental 
and/or  developmental  disability  and  requiring 
physical  assistance  to  exit  the  building.  All 
residents  under  seven  years  of  age  shall  be 
classified  as  impaired 

Partially  impaired:  All  residents  physically, 
mentally  and/or  developmentally  disabled  but 
capable  of  exiting  the  limited  group  residence 
with  either  supervision  and/or  instruction 
without  any  physical  assistance. 
Unimpaired:  All  residents  capable  of  exiting 
the  building  without  physical  assistance 
and/or  supervision  or  instruction  by  staff 
personnel  and  capable  of  negotiating  any 
exitway  of  the  limited  group  residence 

427.1.3  Application  of  building  code  and 
reference:  Except  as  may  otherwise  be 
specifically  provided  for  in  780  CMR  427.0,  the 
Massachusetts  State  Building  Code  shall  apply 
in  its  entirety. 

Exception:  Chapter  34  shall  not  apply. 

427.1.4  Mixed  use  occupancy:  A  limited  group 
residence  shall  not  be  housed  in  a  building  used 


104 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


for  any  occupancy  other  than  a  limited  group 

residence. 

Exception:  Dwelling  unit(s)  meeting  the 
requirements  of  780  CMR  427.0  may  be 
incorporated  within  a  building  in  residential 
use  provided  unit  separation  walls  and 
floor-ceiling  assemblies  shall  serve  to 
completely  separate  the  limited  group 
residence  and  provided  that  one  of  the  limited 
group  residence  exitways  is  separate  from  the 
other  uses. 

427.1.5  Plans  and  specifications:  Plans  shall  be 
filed  with  the  building  official  having 
jurisdiction  in  accordance  with  780  CMR  110.0 
for  any  building  to  be  constructed  as,  or  altered 
for  use  as,  a  limited  group  residence  under 

780  CMR  427.0. 

427.1.6  Temporary  certificate  of  occupancy: 
Upon  satisfactory  compliance  with  the  code 
sections  pertaining  to  building  requirements,  the 
building  official  shall  issue  a  temporary 
certificate  of  occupancy  in  accordance  with 
780  CMR  120.3  for  a  period  not  to  exceed  90 
days.  This  temporary  certificate  of  occupancy 
specifically  prohibits  residents  as  defined  in 
780  CMR  427.1.2  from  inhabiting  the  building 
overnight  until  the  building  official  issues  the 
certificate  of  occupancy  under  780  CMR 
427.1.8. 

427.1. 7  Rules  and  regulations  of  the  licensing  or 
operating  agency  pertaining  to  and  including, 
but  not  limited  to,  smoking  regulations,  staffing 
ratios,  and  resident  classifications  shall  be 
provided  to  the  building  official  by  the  licensing 
or  operating  agency  prior  to  the  issuance  of  a 
certificate  of  occupancy. 

427.1.8  Certificate  of  occupancy:  Certificates  of 
occupancy  shall  only  be  issued  when  a  license,  if 
appropriate,  and  an  affidavit  from  the 
Department  of  Mental  Health  or  the  Office  for 
Children,  Commonwealth  of  Massachusetts, 
have  been  accepted  by  the  building  official 
attesting  to  the  satisfactory  compliance  with  the 
applicable  rules  and  regulations  referenced  in 
780  CMR  427.1.7. 

427.1.9  Certificate  of  inspection:  Certificates  of 
inspection  shall  be  issued  by  the  building  official 
in  accordance  with  780  CMR  106.0  and  Table 
106. 

427.1.10  Failure  to  comply:  The  building  official 
immediately  upon  being  informed  by  written 
report  or  otherwise  that  a  building  or  structure 
or  anything  attached  thereto  or  connected 
therewith  is  being  occupied  in  violation  of 
780  CMR  may  revoke  or  suspend  any  permit, 
license,  certificate  or  other  permission  regulated 
by  780  CMR  and  granted  by  him,  and  no  such 
building  or  structure  shall  be  continued  to  be 


operated  after  such  revocation  or  suspension. 
Such  revocation  or  suspension  shall  not 
preclude  the  building  official  from  instituting 
appropriate  action  in  accordance  with  780  CMR 
118.0. 

427.2  New  structures:  All  new  structures  shall  be 
constructed,  equipped,  and  maintained  to  the 
requirements  of  the  One-  and  Two-Family 
Dwelling  Code  and  780  CMR  427.0,  shall  be 
limited  to  two  stories  in  height,  and  shall  have 
dwelling  unitfs)  limited  to  one  story  in  height  with 
direct  access  to  grade  without  steps  or  changes  in 
elevation  other  than  ramps  in  accordance  with 
780  CMR  11.  Corridors  shall  be  of  one  hour  fire 
resistive  construction. 

427.2.1  Other  requirements:  New  structures 
shall  also  satisfy  the  general  requirements 
contained  in  780  CMR  427.1  and  427.3. 

427.3  Existing  structures:  Existing  structures  of 
any  construction  up  to  three  stories  or  40  feet  in 
height  may  be  converted  and  used  for  limited  group 
residence  occupancies.  All  residents  classified  as 
impaired  as  defined  in  780  CMR  427.1.2  are 
restricted  to  those  stories  having  direct  access  to 
grade  without  steps  or  changes  in  elevation  other 
than  ramps  in  accordance  with  780  CMR  11. 

427.3.1  Third-story  utilization:  The  third  story  of 
buildings  permitted  by  780  CMR  427.3  may  be 
only  occupied  by  staff.  Other  use  of  the  third 
story  is  restricted  to  heating,  ventilation  units 
and  ordinary  storage.  All  doors  leading  to  non- 
resident areas  shall  be  maintained  locked 

427.3.2  Vertical  openings:  Openings  to  such 
spaces  as  laundry  chutes,  dumb-waiters,  heating 
plenums  or  combustible  concealed  spaces  shall 
be  permanently  blocked  with  one  hour 
fireresistance-rated  construction,  in  accordance 
with  the  provisions  of  780  CMR  7,  unless  such 
installation  is  in  compliance  with  the  pertinent 
provisions  of  other  sections  of  780  CMR. 

427.3.2.1  Firestopping  and  draftstopping: 
Firestopping  and  draftstopping  shall  be 
provided  in  accordance  with  780  CMR  720. 0 
and  the  One-  and  Two-Family  Dwelling  Code 
or  as  approved  by  the  building  official 

427.3.3  Exitway  Details: 

427.3.3.1  Corridor  width:  The  minimum  clear 
width  of  an  exitway  access  corridor  shall  be 
three  feet 

Exception:  In  new  structures  the  minimum 
clear  width  shall  be  four  feet 

427.3.3.2  Dead  ends:  In  no  case  shall  dead 
end  corridors  exceed  30  feet  Existing  dead 
end  corridors,  wherever  possible,  shall  be 
altered  so  that  exitways  shall  be  accessible  in 
at  least  two  different  directions  from  all  points 
in  corridors. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


105 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


427.3.3.3  Corridor  walls:  Corridor  walls  that 
separate  use  areas  from  exitway  access 
corridors  shall  be  of  construction  that  will 
resist  the  passage  of  smoke. 

Exception:  Existing  openings  to 
congregate  living  areas,  other  than 
kitchens,  shall  be  allowed  to  remain  open. 

427.3.3.4  Sleeping  room  doors:  All  sleeping 
room  doors  shall  be  of  construction  that  will 
resist  the  passage  of  smoke.  All  doors  shall  be 
equipped  with  approved  positive  latching 
hardware  and  approved  self-closing  devices. 

Exceptions: 

1.  Sleeping  room  doors  may  be  equipped 
with  approved  hold-open  smoke  activated 
devices  in  accordance  with  780  CMR 
1017.0. 

2.  Hollow  core  doors  shall  not  be 
permitted 

427.3.3.5  Means  of  Egress:  All  habitable 
floors  shall  be  provided  with  at  least  two 
means  of  egress,  located  as  remote  as 
practicable  from  one  another.  Exitways  shall 
be  located  to  provide  a  safe  path  of  travel  to  a 
public  way  without  traversing  any  corridor  or 
space  exposed  to  an  unprotected  open 
stairway. 

Exceptions: 

L     Open  stairs  may  be  used  as  one  of  the 

required  means  of  egress  when  permitted 

by    780    CMR   427.3.3.6,    Exception    3. 

However,  in  no  case  may  both  required 

means  of  egress  traverse  the  unprotected 

open  space. 

2.    Access  to  one  of  the  required  exitways 

on  sleeping  room  floors  may  be  through 

adjoining  rooms. 

427.3.3.6  Interior  exitway  stairs:  Every  story 
shall  be  provide  with  at  least  one  enclosed 
interior  stairway  which  discharge  directly  to 
grade  or  through  a  grade  passageway  to  a 
public  way.  The  enclosed  interior  stairway(s) 
shall  be  of  construction  having  a  minimum 
fireresistance  rating  of  one  hour,  properly 
firestopped  Spaces  below  the  stairway(s) 
shall  be  enclosed  to  maintain  the  integrity  of 
the  one  hour  fireresistive  construction  of  the 
stairway  enclosure.  Stairway(s)  openings 
shall  be  protected  by  at  least  Class  "B"  label 
one  hour  fire  door  assemblies. 

New  stair  construction  shall  comply  with 
780  CMR  1014.0.  Existing  stairs  shall 
comply  with  the  One-  and  Two-Family 
Dwelling  Code  or  as  approved  by  the  building 
official 

Exceptions: 

1.  Secondary  stairs  not  considered  an 
exitway  component  may  have  door 
openings  protected  by  a  minimum  1  %  inch 
solid     bonded    wood     core     doors     or 


equivalent;  however,  such  doors  shall  be 
equipped  with  approved  automatic  positive 
latching  hardware  and  approved 
self-closing  devices. 

2.  Basement/cellar:  Stairway(s)  shall  be 
separated  from  the  first  floor  by  a  20 
minute  fire  rated,  self-closing  door  or 
equivalent 

3.  One  stairway  may  be  allowed  to  remain 
unenclosed  to  preserve  functional  and 
aesthetic  requirements. 

427.3.3. 7 Door  widths:  No  single  egress  door 
in  a  doorway  shall  be  less  than  28  inches 
wide. 

Exceptions: 

1.  Exitway  door  leaves  shall  not  be  less 
than  34  inches  wide. 

2.  Door  leaves  to  resident  bedrooms 
occupied  by  residents  who  are  classified  as 
"Impaired"  shall  not  be  less  than  34 
inches  wide. 

427.3.3.8 Basement/ceUar:  Basements/cellars 
shall  be  provided  with  at  least  two  acceptable 
exitways,  one  of  which  shall  discharge 
directly  to  the  outside  of  the  building. 

Exception:  Basement/Cellar  areas  with 
only  one  existing  entrance  from  the  outside 
only,  and  used  solely  as  a  mechanical 
space  shall  be  permitted  to  maintain  only 
one  doorway  which  shall  be  maintained 
locked  as  an  entrance/exitway. 

427.3.3.9  Emergency  escape:  All  sleeping 
rooms  shall  have  at  least  one  openable 
window  or  exterior  door  to  permit  smoke 
control,  emergency  escape,  or  rescue  A 
required  door  or  window  must  be  openable 
from  the  inside  without  the  use  of  separate 
took,  and  shall  comply  with  780  CMR  1010.4. 

427.3.3.10  Means  of  egress  lighting:  Means 
of  egress  lighting  systems  shall  be  provided  in 
accordance  with  780  CMR  1024.0. 

427.3.3.11  Locks:  Locks  installed  in  resident 
sleeping  room  doors  shall  be  so  arranged  that 
they  can  be  locked  from  the  corridor  side.  All 
such  locks  shall  be  arranged  to  permit  exit 
from  the  room  by  a  simple  operation  without 
the  use  of  a  key.  Double  cylinder  dead  bolts 
requiring  key  operation  on  both  sides  are 
prohibited  throughout  this  occupancy. 

427.3.4  Interior  finish:  The  flame  spread  of 
interior  finish  shall  be  limited  to  Class  11  in 
exitways  or  exit  access  corridors.  Rooms  shall 
be  permitted  to  have  interior  finish  of  a  Class  III 
flame  spread  Floor  coverings  shall  conform  to 
the  requirements  of  780  CMR  805.0  except  that 
carpet  type  floor  coverings  shall  possess  a 
critical  radiant  flux  of  0.22  w/cm2  or  greater. 

427.3.5  Fire  suppression  systems:  Automatic  fire 
suppression   systems   shall   be  provided  and 


106 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUTLDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


installed  in  accordance  with  NFiPA  Standard 
No.  13D. 
Additions: 

1.  Exceptions  listed  in  NFiPA  Standard  No. 
13D  applicable  to  dwellings  shall  not  apply. 

2.  A  water  flow  detector,  connected  to  the 
fire  alarm  system,  shall  be  provided 

3.  NFiPA  Standard  No.  13D,  Sections  4 
through  6;  Exception  1  shall  not  apply. 

4.  The  control  valve(s)  shall  be  secured  in 
the  open  position. 

427.3.6  Fire  alarm  system:  A  manual  fire  alarm 
system  shall  be  provided  and  installed  in 
accordance  with  780  CMR  917.0  or  918.0  and 
specifically  NFiPA  Standard  No.  72 A  as  listed  in 
Appendix  A. 

427.3.7  Automatic  protection  alarm  system: 
Approved  smoke  detectors  shall  be  installed  in 
accordance  with  780  CMR  918. 0  and  specifically 
NFiPA  Standard  No.  72  as  listed  in  Appendix  A 
in  the  following  locations: 

1.  exitway  access  corridors  not  more  than  30 
feet  on  center; 

2.  congregate  living  areas  other  than 
kitchens; 

3.  at  least  one  detector  in  all  basement/cellar 
areas;  and 

4.  all  sleeping  rooms. 

Exception:  Smoke  detectors  used  in 
combination  with  automatic  closing 
devices  may  be  substituted  in  each  area 
aforementioned  for  the  protection  herein 
required 

427.3.8  Fire  department  connection:  All 
automatic  and  manual  fire  alarm  systems  shall 
be  electrically  interconnected;  this  combined 
system  shall  automatically  transmit  an  alarm  to 
the  municipal  fire  department  or  to  such  other 
outside  assistance  as  may  be  available.  Such 
connection  shall  be  made  in  accordance  with 
NFiPA  Standard  No.  72  as  listed  in  Appendix  A. 

427.3.9  Heating  devices:  Portable  comfort 
heating  devices  and  solid  fuel  burning 
appliances  are  prohibited  Any  heating  device, 
other  than  a  central  heating  plant,  shall  be  so 
designed  and  installed  that  combustible  material 
will  not  be  ignited  by  it  or  its  appurtenances.  If 
fuel-fired,  such  heating  devices  shall  be  chimney 
or  vent  connected,  shall  take  air  for  combustion 
directly  from  the  outside,  and  shall  be  so 
designed  and  installed  to  provide  for  complete 
separation  at  the  combustion  system  from  the 
atmosphere  of  the  occupied  area.  The  heating 
system  shall  have  safety  devices  to  immediately 
stop  the  flow  of  fuel  and  shut  down  the 
equipment  in  case  of  either  excessive 
temperature  or  ignition  failure 


Exceptions: 

1.  Approved  suspended  unit  heaters  may  be 
used  in  locations  other  than  means  of  egress 
and  sleeping  areas,  provided  such  heaters  are 
located  high  enough  to  be  out  of  the  reach  of 
persons  using  the  area  and  provided  they  are 
equipped  with  the  safety  devices  specified  in 
780  CMR  427.3.9. 

2.  Fireplaces  which  comply  with  780  CMR 
2114. 0  may  be  used  only  in  areas  other  than 
resident  sleeping  rooms.  The  fireplaces  shall 
be  equipped  with  a  heat  tempered  glass 
fireplace  enclosure  guaranteed  against 
breakage  up  to  a  temperature  of  650  "F.  A 
lock  on  the  enclosure  shall  be  required 

427.3.10  Fire  drills:  The  licensing  or  operating 
agency  shall  require  that  fire  drills  be  held  with 
sufficient  frequency  so  as  to  familiarize  all 
residents  and  staff  personnel  with  emergency 
procedures.  Drills  shall  be  held  at  unexpected 
times  under  varying  conditions  to  simulate  the 
unpredictable  conditions  which  may  occur  in 
case  of  fire,  including  blocking  of  any  point  of 
any  means  or  egress. 

427.3.10.1  Log:  A  log  shall  be  kept  of  all  fire 
drills  and  shall  be  available  for  inspection 
and  duplication  by  the  building  official,  fire 
official,  and  other  parties  having  jurisdiction. 

427.3.10.2  The  resident  manager  shall  record 
in  said  log  the  names  of  any  authorized 
inspectors  who  may  have  been  present  and 
the  names  or  identifying  numbers  of  the 
residents  who  participated 

780  cmr  428.0  detoxification 
facilities 

428.1  General:  A  detoxification  facility  is  a  facility 
licensed  or  operated  by  the  Department  of  Public 
Health,  Division  of  Alcoholism  in  accordance  with 
the  Rules  and  Regulations  for  Detoxification 
Facilities  issued  by  the  Department  of  Public 
Health,  Division  of  Alcoholism,  Commonwealth  of 
Massachusetts,  and  shall  be  used  to  treat 
individuals  acceptable  to  the  program  in 
accordance  with  those  Rules  and  Regulations. 

428.2  Scope:  Detoxification  facilities  shall  be 
subject  to  the  requirements  of  780  CMR  428. 0  for 
new  and  existing  buildings  which  are  to  be  used  or 
operated  as  licensed  facilities.  780  CMR  428.0 
shall  establish  the  requirements  applicable  to  such 
facilities.  Where  specific  reference  is  made  to 
other  sections  of  780  CMR,  to  reference  standards 
or  other  regulations,  those  requirements  cited  shall 
apply.  Where  no  reference  is  specifically  made, 
780  CMR,  including  780  CMR  34,  shall  apply. 

428.3  Classification  of  Residents:  All  residents 
enrolled  in  the  detoxification  program  shall  be 
identified   according   to   one   of  the  following 


2/7/97  .(Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


107 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


classifications  when  evaluated  by  the  facility 
personnel  in  accordance  with  the  Rules  and 
Regulations  for  Detoxification  Facilities  of  the 
Division  of  Alcoholism  of  the  Department  of  Public 
Health: 

1.  Impaired 

2.  Partially  Impaired 

3.  Unimpaired 

428.4  Definitions:  The  following  terms  shall  have 
the  meaning  indicated  for  the  purpose  of  780  CMR 
428.0  only: 

Impaired:  Anyone  who  will  require  assistance  to 
egress  the  building 

Partially  Impaired:    Anyone   who   may  require 
assistance  to  egress  the  building. 

Unimpaired:  Anyone  who  appears  able  to  egress 
the  building  without  assistance. 

4285  Use  group  classification:  Detoxification 
facilities  licensed  and  approved  in  accordance  with 
these  provisions  shall  be  classified  in  the  R-l  use 
group. 

4286  Mixed  use  occupancy:  A  portion  of  a 
building  may  be  used  for  a  detoxification  facility 
provided  that  it  is  completely  separated  from  the 
rest  of  the  building  by  both  horizontal  and  vertical 
fire  separation  assemblies  of  at  least  one  hour 
fireresistance  rating. 

Exception:  Detoxification  facilities  shall  not  be 
located  in  buildings  in  which  any  of  the 
following  use  groups  are  located:  A-2,  F,  H,  or 
S-l. 

4287  Submission  of  plans:  Plans  shall  be  filed 
with  the  building  official  in  accordance  with 
780  CMR  110.0  for  any  building  to  be  constructed 
as,  or  altered  for  use  as,  a  detoxification  facility 
under  780  CMR  428.0.  The  plans  shall  also 
identify  those  rooms  which  comply  with  780  CMR 
428.0  for  use  by  the  impaired 

428.8  Inspection  and  certification:  The  building 
official  shall  inspect  and  certify  detoxification 
facilities  once  every  two  years.  Fees  shall  be 
applied  in  accordance  with  Table  106  for  the  R-l 
Use  Group. 

4289  Resident  location  limitations:  In  buildings 
used  as  detoxification  facilities  in  accordance  with 
780  CMR  428.0,  resident  locations  shall  be  limited 
according  to  the  use  and  type  of  construction  as 
provided  in  Table  428. 9.  All  heights  are  in  stories 
above  grade.  All  buildings  used  as  detoxification 
facilities  in  accordance  with  780  CMR  428. 0  shall 
be  accessible  to  the  Fire  Department  wherever 
escape  windows  are  required 


Table  428  9 

RESIDENT  SLEEPING  ROOM  LOCA  TION 

LIMITATION  FOR  DIFFERENT  TYPES  OF 

CONSTRUCTION 


Classification 
of  Resident 

Type  of  Building  Construction 

IA 

IB 

2A 

28 

2C 

3A 

SB 

J 

SA 

SB 

Impaired 

No 
limit 

Ssl 

4 
St 

2 

St. 

1 

St. 

2 

St 

1 

St. 

2 
sL 

1 

St 

1 

SL 

Partially 
impaired 

No 
limit 

No 
limit 

8 

SL 

3 

St. 

1 

St 

3 

SI. 

2 

St 

3 

a. 

2 

SL 

1 

SL 

Unimpaired 

No 
limit 

No 
limit 

St 

4 

St. 

3 

St 

4 

St. 

3 

St. 

-i 

St. 

3 

St. 

2 
SL 

Note:  *  Impaired  sleeping  rooms  in  5B  construction 
require  either  full  building  sprinklering  or  one  hour  fire 
rated  separation  for  floor  and  ceiling  of  sleeping  room 
walls. 

428.9.1  Sprinklered  buildings:  Buildings  which 
are  completely  sprinklered  may  have  resident 
locations  one  story  higher  than  allowed  in  Table 
428.9. 

4289.2  Sleeping  room  limitations:  Sleeping 
facilities  in  building  licensed  for  use  as 
detoxification  facilities  shall  not  be  located 
below  thefirsi  story. 

42810  Egress:  At  least  two  exitways  located  as 
remote  as  practicable  from  each  other  shall  be 
provided  from  each  floor  of  the  building. 

42810.1  Every  room  used  for  sleeping  for  the 
impaired  and  partially  impaired  shall  have  an 
exitway   access   door  leading   directly   to   an 
exitway  access  corridor: 
Exceptions: 

1.  Rooms  having  a  means  of  egress  doorway 
leading  directly  to  the  exterior  of  the  building 
at  grade 

2.  Rooms  having  a  means  of  egress  doorway 
leading  directly  to  the  exterior  of  the  building 
above  grade  and  connected  directly  to  grade 
by  means  of  an  exterior  stairway  in 
accordance  with  780  CMR  1014.0. 

428.10.2  All  other  sleeping  rooms:  All  other 
sleeping  rooms  shall  comply  with  the 
requirements  of  780  CMR  10  in  accordance  with 
the  provisions  for  the  R-l  use  group. 

42810.3  Corridors  shall  provide  at  least  36 
inches  minimum  nominal  width. 

42810.4  All  means  of  egress  doorways  shall  be 
32  inches  minimum  nominal  width. 

Exception:  Egress  doorways  from  impaired 
sleeping  rooms  shall  36  inches  minimum 
nominal  width. 

428.10.5  Every  required  exitway  access  corridor 
shall  have  a  one  hour  fire-resistance  rating  and 
shall  provide  access  to  at  least  two  approve 
exitways      without     passing      through      any 


108 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


intervening  rooms  or  spaces  other  than  corridors 

and  lobbies. 

Exception:  In  buildings  with  a  complete 
sprinkler  system,  exitway  access  corridors  not 
required  for  the  impaired  or  partially 
impaired  may  be  separated  from  other  use 
areas  by  non-fire  rated  partitions 

428.10.6  Stairways:  Where  not  otherwise 
specified  in  780  CMR  428.2,  a  stairway  required 
as  a  means  of  egress  shall  be  subject  to  these 
requirements: 

428.10.6.1  Stairways  required  to  provide 
egress  for  the  impaired  shall  be  at  least  36 
inches  minimum  nominal  width.  The  total 
capacity  of  the  stairways  shall  be  adequate  for 
the  occupancy  load  served 

428.10.6.2  Stairway  enclosures  shall  have  a 
fireresistance  rating  of  one  hour  for  buildings 
not  exceeding  three  stories  in  height,  and  two 
hours  for  buildings  exceeding  three  stories  in 
height 

428.10.6.3  Doors  to  the  required  exitway 
stairways  shall  be  fire  doors  complying  with 
780  CMR  716.0  .  Labeled  fire  doors  shall 
have  a  maximum  transmitted  temperature  end 
point  of  not  more  than  450  °F  (232  °C)  above 
ambient  at  the  end  of  30  minutes  of  standard 
fire  test  exposure. 

42811  Interior  finish:  Interior  finish  requirements 
shall  comply  with  Table  428.11. 
Exceptions: 

1.  In  buildings  which  are  completely 
sprinklered,  the  interior  finish  requirements  may 
be  reduced  one  level  except  in  sleeping  rooms  for 
the  impaired 

2.  The  interior  finish  classifications  in  existing 
buildings  may  be  improved  one  level  by  the  use 
of  fire  retardant  coatings  which  have  been 
approved  when  tested  in  accordance  with  ASTM 
E-84. 

TABLE  428.11 
INTERIOR  FINISH  REQUIREMENTS 


Location 

Walls 

Floor 

Ceiling 

Sleeping  rooms,  Impaired 

II 

II2 

II 

Corridors,  Impaired 

I 

I1 

I 

Sleeping  rooms,  Partially  impaired 

I 

i 

I 

Corridors,  Partially  impaired 

I 

/ 

I 

All  other  exitway  access  corridors 

II 

II2 

II 

Stairwavs 

I 

t 

1 

Note  1:  Carpet  type  floor  coverings  shall  withstand  a 
test  exposure  of  0.45  watts  per  square  centimeter  when 
tested  in  accordance  with  780  CMR  805.0. 

Note  2:  Carpet  type  floor  coverings  shall  withstand  a 
test  exposure  of  0.22  watts  per  square  centimeter  when 
tested  in  accordance  with  780  CMR  805.  ft 

428.12  Fire  alarm  systems:  Manual  and  automatic 
fire  alarm  systems  shall  be  provided  in  accordance 


with  780  CMR  917.0  as  they  apply  to  Use  Group 
R-l. 

Exceptions: 

1.  In  rooms  for  the  impaired  and  partially 
impaired  the  heat  detectors  required  by 
780  CMR  918. 0  shall  be  replaced  with  approved 
smoke  detectors. 

2.  Buildings  or  portions  thereof  with  25  beds  or 
less  shall  have  as  a  minimum  a  Type  11  system  as 
described  in  780  CMR  918.0:  buildings  with  26 
beds  or  more  shall  have  as  a  minimum  a  Type  I 
system  as  described  in  780  CMR  918.  ft 

3.  All  buildings  or  portions  thereof  regardless 
of  the  number  of  beds  shall  incorporate  manual 
pull  stations  in  conformance  with  780  CMR 
917.0. 

42812.1  All  automatic  and  manual  fire  alarm 
systems  shall  be  electrically  interconnected;  this 
combined  system  shall  automatically  transmit  an 
alarm  to  the  municipal  fire  department  or  to 
another  approved  source  of  assistance  Such 
communication  shall  be  made  in  accordance 
with  NFiPA  Standards  No.  72  as  listed  in 
Appendix  A. 

42813  Means  of  egress  lighting:  Means  of  egress 
lighting  including  an  emergency  lighting  system 
shall  be  provided  throughout  the  facility  in 
accordance  with  780  CMR  91 7.  ft 

42814  Smoke  enclosure  doors:  Smoke  enclosure 
doors  shall  be  tight-fitting  with  approved  hardware. 

42815  Heating  apparatus:  The  use  of  portable 
heaters,  solid  fuel  burning  room  heaters  and 
fireplaces  shall  be  prohibited 

428.16  Sprinkler  systems:  Where  a  complete 
building  sprinkler  system  is  installed  it  shall 
comply  with  the  provisions  of  NFiPA  Standard 
No.  13,  as  listed  in  Appendix  A. 

42816.1  All  rooms  used  for  sleeping  for  the 

impaired  shall  be  sprinklered 

Exception:  A  partial  system  required  for 
sleeping  rooms  housing  impaired  individuals 
may  be  provided  with  a  sprinkler  system 
serving  no  more  than  six  sprinklers,  which 
may  be  connected  directly  to  a  domestic  water 
supply  system  having  capacity  sufficient  to 
provide  0.15  gallons  per  minute  per  square 
foot  of  floor  area  throughout  the  entire  area. 
An  indicating  shut-off  valve  shall  be  installed 
in  an  accessible  location  between  the 
sprinklers  and  the  connection  the  domestic 
water  supply. 

780  CMR429.0  GROUP  DWELLING  UNITS 
429.1   General:   A   Group   Dwelling   Unit  is   a 
dwelling  unit  licensed  by   or  operated  by   the 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


109 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Department  of  Mental  Retardation  or  the 
Department  of  Mental  Health  as  special  residence 
for  up  to  four  persons  who  may  or  may  not  be 
capable  of  self  preservation  from  fire  or  other 
related  hazards.  Note,  however,  780  CMR  429.1, 
Exceptions  1  and  2.  The  provisions  of  780  CMR 
429. 0  shall  apply  to  both  new  and  existing  Group 
Dwelling  Units. 

Exception  1:  780  CMR  429. 0  shall  not  apply  to  a 
group  dwelling  unit  operated  or  licensed  by  the 
Department  of  Mental  Retardation  (DMR) 
pursuant  to  J 15  CMR  7.00  and  8.00,  upon  the 
completion  of  a  DMR  safety  assessment  for  each 
individual  and  an  approved  safety  plan  for  each 
location  where  services  and  supports  are 
provided  Such  premise  shall  be  treated  as 
conventional  R-4,  R-3.  R-2  and  R-l  use  as 
applicable. 

Exception  2:  Apartment  programs  as  defined  in 
104  CMR  17.13(2)(c)  in  which  residents  therein 
are  also  capable  of  self  preservation  (unimpaired) 
shall  be  exempt  from  all  requirements  of 
780  CMR  429.0.  Such  apartment  programs  shall 
be  classified  as  R-l.  R-2.  R-3,  or  R-4,  as 
applicable. 

429.1.1  Classification  of  Use:  Group  Dwelling 
Units  shall  be  classified  as  follows: 

Use  Group  R-2  -  The  Group  Dwelling  Unit(s) 
is  (are)  one  or  more  of  three  or  more  dwelling 
units  contained  in  the  building. 
Use  Group  R-3  or  R-4  -  The  Group  Dwelling 
Unit(s)  is  (are)  contained  in  a  one  or  two 
family  dwelling. 

429.1.2  Classification  of  Residents:  Persons 
other  than  staff  of  the  facility  who  occupy  or 
intend  to  occupy  Group  Dwelling  Units  shall  be 
classified  by  the  Licensing  or  Operating  Agency 
in  one  of  the  following  three  categories 
according  to  their  capabilities  for  self 
preservation: 

Impaired:  Any  resident  who  is  incapable  of 
self  preservation  through  physical,  mental  or 
developmental  disability,  so  as  to  require 
physical  assistance  from  the  staff  of  the 
Group  Dwelling  Unit  to  exit  the  building  or  to 
reach  an  area  of  refuge  within  2'A  minutes. 

Partially  Impaired:  Any  resident  who  is 
capable  with  either  supervision  or  instruction 
from  the  staff  of  the  Group  Dwelling  Unit  but 
without  physical  assistance,  of  exiting  the 
building  or  reaching  an  area  of  refuge  within 
2'A  minutes. 

Unimpaired:  Any  resident  who  is  capable  of 
exiting  the  building  or  reaching  an  area  of 
refuge  within  2'A  minutes  without  physical 
assistance,  supervision  or  instruction. 


429.1.3  Application  of  building  code  and 
reference:  Except  as  may  otherwise  be 
specifically  provided  in  780  CMR  429.0, 
780  CMR  shall  apply  in  its  entirety. 

Exception:  780  CMR  34  shall  not  apply. 
However,  existing  buildings  may  be  used  to 
house  group  dwelling  units,  provided  that 
they  comply  with  the  applicable  portions  of 
780  CMR  429.0,  and  have  no  outstanding 
violations  of  780  CMR  or  the  specialized 
codes. 

429.1.4  Plans  and  specifications:  Plans  shall  be 
filed  with  the  building  official  having 
jurisdiction  in  accordance  with  780  CMR  110.0 
for  any  building  to  be  constructed  as,  or  altered 
for   use   as   a   Group   Dwelling   Unit   under 

780  CMR  429.0. 

429.1.5  Temporary  Certificate  of  Occupancy: 
Upon  satisfactory  compliance  with  the  code 
sections  pertaining  to  building  requirements,  the 
building  official  shall  issue  a  temporary 
certificate  of  occupancy  in  accordance  with 
780  CMR  120.3  for  a  period  not  to  exceed  90 
days.  This  temporary  certificate  of  occupancy 
specifically  prohibits  residents  as  defined  in 
780  CMR  429.1.2  from  inhabiting  the  building 
overnight  until  the  building  official  issues  the 
certificate  of  occupancy  under  780  CMR 
429.1.8. 

429.1.6  Corresponding  Rules  and  Regulations: 
115  CMR  (the  Department  of  Mental 
Retardation)  or  104  CMR  17.13  (the  Department 
of  Mental  Health)  as  listed  in  Appendix  A, 
pertaining  to  and  including,  but  not  limited  to, 
smoking  regulations,  staffing  ratios,  and 
resident  classifications  shall  be  provided  upon 
request  to  the  building  official  by  the  Licensing 
or  Operating  Agency  prior  to  the  issuance  of  a 
certificate  of  occupancy.  Note,  however, 
780  CMR  429.1,  Exceptions  1  and  2. 

429.1.7  Certification  of  Residents:  The 
Licensing  Agency  shall  certify  the  classification 
of  each  resident  prior  to  application  for  a 
Certificate  of  Occupancy  and  shall  regularly 
re-examine  and,  where  necessary,  reclassify 
residents  in  accordance  with  Department  of 
Mental  Retardation  or  Department  of  Mental 
Health  regulations  as  listed  in  Appendix  A. 
Copies  of  the  current  certification  of  each 
resident  shall  be  kept  on  file  at  the  Group 
Dwelling  Unit,  and  shall  be  made  available  to 
the  building  official  upon  request  Note, 
however,  780  CMR  429.1,  Exceptions  1  and  2. 

429.1.8  Certificate  of  Occupancy:  Certificates  of 
occupancy  shall  be  issued  only  when  a  license 
and/or  affidavit  from  the  Department  of  Mental 
Retardation  or  the  Department  of  Mental  Health 
have  been  provided  to  the  building  official 
attesting  to  the  satisfactory  compliance  with  the 


110 


780  CMR  -  Sixth  Edition 


2/7/97     (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  USE  AND  OCCUPANCY 


applicable  rules  and  regulations  referenced  in 
780  CMR  429.1.6,  the  capabilities  for  self 
preservation  of  all  residents,  and,  if  appropriate, 
the  intent  to  license  the  facility.  Upon 
compliance  with  all  building  requirements  of 
780  CMR  429. 0  and  receipt  of  the  Licensing 
Agency's  affidavit,  the  building  official  shall 
issue  a  certificate  of  occupancy  within  72  hours. 
In  addition  to  the  contents  specified  in  780  CMR 
120.4,  the  certificate  shall  indicate  the  category 
of  Group  Dwelling  Unit  for  which  the  building 
has  been  constructed  or  altered,  as  defined  in 
780  CMR  429.2.  Note,  however,  780  CMR 
429.1,  Exceptions  1  and  2. 

429.2  Category  of  Unit/Compliance  Options:  Nov 
and  existing  building  containing  Group  Dwelling 
Units  shall  be  required  to  satisfy  at  least  one 
compliance  option  presented  for  the  appropriate 
category  of  residency  as  defined  in  780  CMR 
429.2: 

Category  A  Group  Dwelling  Unit  -  May  contain 
any  or  all  of  the  resident  classifications. 

Category  B  Group  Dwelling  Unit  -  May  contain 
only  partially  impaired  or  unimpaired  residents. 

Category  C  Group  Divelling  Unit  -  Shall  contain 
only  unimpaired  residents. 

429.2.1  Category  A  Unit  Compliance  Options: 
Buildings  housing  Group  Dwelling  Units  classed 
as  "Category  A  "  shall  comply  with  any  one  of 
the  following  compliance  options: 

1.  The  entire  building  shall  be  equipped  with 
afire  suppression  system;  or 

2.  The  building  shall  be  of  a  protected 
construction  type  (Type  1,  2A,  2B,  3A,  4  or 
5 A).  All  interior  staipvays  shall  be  enclosed 
to  comply  with  the  requirements  of  780  CMR 
for  interior  exitway  stainvays  and  shall 
discharge  directly  to  the  exterior  of  the 
building  or  into  a  code  complying  grade 
passageway  or  lobby.  The  building  shall  also 
be  equipped  with  fire  alarms  complying  with 
780  CMR  9  for  the  appropriate  use  group 
classification;  or 

3.  The  Building  shall  comply  with  the 
provisions  of  780  CMR  427.0;  or 

4.  If  of  unprotected  construction  (Types  2C, 
3B  or  SB),  the  building  shall  be  equipped  with 
fire  alarms  complying  with  780  CMR  9  for  the 
appropriate  use  group  classification.  No 
Group  Dwelling  Unit(s)  shall  utilize  portions 
of  the  building  above  the  second  story.  All 
stories  in  the  building  shall  be  equipped  with 
two  approved,  independent  exitways  (even  if 
the  building  is  classified  in  Use  Group  R-3). 
Interior  exibvay  stairways  shall  be  enclosed  to 
comply  with  the  requirements  of  780  CMR  for 
interior  exitway  stainvays  and  shall  discharge 
directly  to  the  exterior  of  the  building  or  into 


a  code  complying  grade  passageway  or  lobby; 
or 

5.         In    those   buildings    of  unprotected 

constructed  (Types  2C,   3B  or  SB)  where 

enclosure  of  interior  exitway  stairways  is 

impractical  due  to  physical  limitations  of 

configuration  of  the  building  (e.g.  split  entry 

type    stainvays),    the    stainvay(s)    may    be 

permitted  to  remain  unenclosed,  provided  that 

all  sleeping  rooms  are  segregated  from  the 

open  stainvay  by  a  minimum  of  one  hour  fire 

resistive  construction  and  the  exitways  are 

arranged  so  that  a  second  means  of  egress  is 

available  from  each  sleeping  area  which  does 

not  pass  through  the  open  stainvay  area.    The 

building  shall  also  be  equipped  with  fire 

alarms  complying  with  780  CMR  9  for  the 

appropriate  use  group  classification.      No 

Group  Dwelling  Unit  shall  utilize  portions  of 

the  building  above  the  second  story.     All 

stories  in  the  building  shall  be  equipped  with 

two  approved,  independent  exitivays  (even  if 

the  building  is  classified  in  Use  Group  R-3). 

429.2.1.1     Limitation     on     location     of 

impaired  residents:  All  sleeping  rooms  of 

impaired  residents  shall  either  be  located 

on  the  first  story  or  on  a  story  containing  a 

horizontal  exit  complying  with  780  CMR 

1019.0. 

429.2.2  Category  B  Unit  Compliance  Options: 
Buildings  housing  Group  Dwelling  Units 
classified  as  "Category  B"  shall  comply  with  any 
one  of  the  following  compliance  options: 

1.  Any  Category  A  compliance  option;  or 

2.  All  stories  in  the  building  shall  be 
provided  with  two  approved,  independent 
exitways  (even  if  the  building  is  classified  in 
Use  Group  R-3).  All  interior  stairways  shall 
be  enclosed  to  comply  with  the  requirements 
of  780  CMR  for  interior  exitway  stainvays 
and  shall  discharge  directly  to  the  exterior  of 
the  building  or  into  a  code  complying  grade 
passageway  or  lobby.  The  building  also  shall 
be  equipped  with  fire  alarms  complying  with 
780  CMR  9  for  the  appropriate  use  group 
classification. 

429.2.3  Category  C  Unit  Compliance  Options: 
Buildings  housing  Group  Dwelling  Units 
classified  as  "Category  C"  shall  comply  with  any 
one  of  the  following  compliance  options: 

1.  Any  Category  A  compliance  option;  or 

2.  Any  Category  B  compliance  option;  or 

3.  The  building  shall  comply  with  the 
provisions  of  780  CMR  423. 0. 

429.3  Special  Fire  Safety  Items: 

429.3.1  Hazardous  Contents:  No  contents  which 
represent  afire  hazard  greater  than  that  which 
could    be    expected    of   ordinary    household 


211  111    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


furnishings  shall  be  permitted  within  a  Group 
Lhvelling  Unit 

429.3.2  Interior  Finish:  Interior  finish  in 
exitways  and  exitway  access  corridors  shall  be  a 
minimum  of  Class  II,  unless  the  building  is 
equipped  with  a  fire  suppression  system. 
Approved  fire  retardant  paints  may  be  used  to 
improve  the  interior  finish  classification  of 
existing  construction  to  satisfy  this  requirement 

429.3.3  Locks:  Double  cylinder  deadbolt  locks 
which  require  a  key  operation  on  the  side  from 
which  egress  is  to  be  made  are  not  permitted  in 
Group  Lhvelling  Units.  Locks  of  any  type  are 
prohibited  on  sleeping  room  doors  of  impaired  or 
partially  impaired  residents  or  on  any  door  which 
provides  access  to  an  exitway. 

429.4  Special  inspection/fire  drill:  Prior  to 
occupancy  of  the  group  dwelling  unit  the  Licensing 
Agency  shall  conduct  a  fire  drill  to  test  the 
capability  of  residents  to  exit  according  to  their 
residency  classification.  At  least  once  every  90 
days,  the  Operating  Agency  shall  also  conduct  a 
fire  drill  to  test  the  capability  of  residents  to  exit 
according  to  their  residency  classification.   Drills 


shall  be  held  at  unexpected  times  under  varying 
conditions  to  simulate  the  unpredictable  nature  of 
fire  emergencies.  The  building  official  may,  at  his 
option,  participate  in  or  witness  the  fire  drill,  or 
may  accept  an  affidavit  from  the  Operating  Agency 
attesting  to  the  performance  of  each  resident  or 
prospective  resident  The  affidavit  shall  also 
specify  the  date,  time  and  conditions  of  the  drill, 
and  shall  list  all  participants  and  witnesses. 

429.4.1  Conduct  of  the  Fire  Drill:  During  the 
conduct  of  the  drill,  one  exit  shall  be  blocked  to 
simulate  a  hazardous  condition  and  the  alarm 
system  shall  be  activated  Successful 
performance  for  each  resident  shall  be  defined 
as  his/her  ability  to  exit  the  building,  or  where 
horizontal  exits  are  provided  to  reach  an  area  of 
refuge  within  2V2  minutes  of  the  activation  of  the 
fire  alarm  system.  Only  those  staff  members 
who  are  normally  on  duty  shall  be  allowed  to 
assist  residents,  and  the  only  assistance 
permitted  shall  be  that  which  is  provided  by  the 
staff  of  the  Group  Dwelling  Unit  consistent  with 
the  classification  of  each  individual  resident 


112 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  5 


GENERAL  BUILDING  LIMITATIONS 


780  CMR  501.0  GENERAL 
501.1  Scope:  The  provisions  of  780  CMR  5  control 
the  height  and  area  of  all  structures  hereafter 
erected,  and  additions  to  existing  structures  based  on 
the  type  of  construction,  use  group,  frontage  on  open 
space  providing  exposure  protection  and  access  to 
structures  for  fire-fighting  purposes,  and  the 
presence  of  an  automatic  sprinkler  system. 

780  CMR  502.0  DEFINITIONS 
502.1   General:   The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  5  and  as  used 
elsewhere  in  780  CMR    have  the  meanings  shown 
herein. 

Area,  building  The  area  included  within 
surrounding  exterior  walls  (or  exterior  walls  and 
fire  walls)  exclusive  of  vent  shafts  and  courts. 
Areas  of  the  building  not  provided  with 
surrounding  walls  shall  be  included  in  the 
building  area  if  such  areas  are  included  within  the 
horizontal  projection  of  the  roof  or  floor  above 

Basement:  That  portion  of  a  building  which  is  partlv 
or  completely  below  grade  (see  "Story  above 
grade"). 

Grade  plane  A  reference  plane  representing  the 
average  of  finished  ground  level  adjoining  the 
building  at  all  exterior  walls.  Where  the  finished 
ground  level  slopes  away  from  the  exterior  walls, 
the  reference  plane  shall  be  established  by  the 
lowest  points  within  the  area  between  the  building 
and  the  lot  line  or,  where  the  lot  line  is  more  than 
six  feet  (1829  mm)  from  the  building,  between  the 
building  and  a  point  six  feet  (1829  mm)  from  the 
building. 

Height 

Building  The  vertical  distance  from  grade  plane 
to  the  average  height  of  the  highest  roof  surface. 
Story:  The  vertical  distance  from  top  to  top  of 
two  successive  tiers  of  beams  or  finished  floor 
surfaces;  and,  for  the  topmost  story,  from  the  top 
of  the  floor  finish  to  the  top  of  the  ceiling  joists  or. 
where  there  is  not  a  ceiling,  to  the  top  of  the  roof 
rafters. 

Mezzanine  An  intermediate  level  or  levels  between 
the  floor  and  ceiling  of  any  story  with  an 
aggregate  floor  area  of  not  more  than  Vb  of  the 
area  of  the  room  in  which  the  level  or  levels  are 
located  (see  780  CMR  505.0). 

Story:  That  portion  of  a  building  included  between 
the  upper  surface  of  a  floor  and  the  upper  surface 
of  the  floor  or  roof  next  above  (also  see 
"Mezzanine"). 


Story  above  grade  .Any  stop,'  having  its  finished 
floor  surface  entirelv  above  grade  except  that  a 
basement  shall  be  considered  as  a  story  above 
grade  where  the  finished  surface  of  the  floor 
above  the  basement  is 

1 .  More  than  six  feet  ( 1 829  mm)  above  grade 
plane, 

2.  More  than  six  feet  (1829  mm)  above  the 
finished  ground  level  for  more  than  50%  of  the 
total  building  perimeter;  or 

3.  More  than  12  feet  (3658  mm)  above  the 
finished  ground  level  at  any  point. 

780  CMR  503.0  GENERAL  HEIGHT 
AND  ARE\  LEVflTATIONS 

503.1  General:  The  heights  and  areas  of  all 
buildings  and  structures  between  exterior  walls  or 
between  exterior  walls  and  fire  walls,  shall  be 
governed  by  the  type  of  construction  and  the  use 
group  classification  as  defined  in  780  CMR  3  and  6 
and  shall  not  exceed  the  limitations  fixed  in  Table 
503,  except  as  specifically  modified  by  780  CMR  5 
and  the  following  sections: 

Section  Subject 

402.7  Covered  mall  buildings 

403.3.3.1  High-rise  buildings 

414.2  Airport  traffic  control  towers 

416.3  HPM  facilities 
418.3.1.1  Grain  elevators 

426. 0  Bulk  Merchandizing 

Retail  Buildings 
3 1 03 .3 . 5  Membrane  structures 

503.1.1  Special    industrial    occupancies     All 

buildings  and  structures  designed  to  house  low- 
hazard  industrial  processes  that  require  large 
areas  and  unusual  heights  to  accommodate 
craneways  or  special  machinery  and  equipment, 
including,  among  others,  rolling  mills,  structural 
metal  fabrication  shops  and  foundries,  or  the 
production  and  distribution  of  electric,  gas  or 
steam  power,  shall  be  exempt  from  the  height  and 
area  limitations  of  Table  503. 

503.1.2  Open  parking  structures  Open  parking 
structures  shall  conform  to  the  height  and  area 
limitations  specified  in  780  CMR  406.4. 

503.1.3  Buildings  on  same  lot:  Two  or  more 
buildings  on  the  same  lot  shall  be  regulated  as 
separate  buildings  or  shall  be  considered  as 
portions  of  one  building  if  the  height  of  each 
building  and  the  aggregate  area  of  all  buildings 
are  within  the  limitations  of  Table  503  as 
modified  by  780  CMR  504.0  and  506.0.  The 
provisions  of  780  CMR  applicable  to  the  aggre- 
gate building  shall  be  applicable  to  each  building. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  503 
HEIGHT  AND  AREA  LIMITATIONS  OF  BUILDINGS 

Height  limitations  of  buildings  (shown  in  upper  figure  as  stories  and  feet  above  grade  plane)  ,  and  area  limitations  of 
one-  or  two-story  buildings  facing  on  one  street  or  public  space  not  less  than  30  feet  wide  (shown  in  lower  figure  as 
area  in  square  feet  per  floor   ).  See  Note  a. 

Table  notes  appear  immediately  following  table. 

N.P.  =  Not  Permitted;  N.L.  =  Not  Limited 


USE  GROUPS 

Note  a 

Tvpe  of  Construction 

Noncombustible 

Noncombusuble/ 
Combustible 

Combustible 

Tvpe  1 

Type  2 

Tvpe  3 

Type  4 

Tv 

pe  5 

Protected 
Noteb 

Protected 

Unpro- 
tected 

Pro- 
tected 

Unpro- 
tected 

Heavy 
timber 

Pro- 
tected 

Unpro- 
tected 

1A 

IB 

2A 

2B 

2C 

3A 

3B 

4 

5A 

5B 

A-l  Assembly;  theaters 

N.L. 

N.L. 

5  St.  65' 
19,950 

3  St  40' 
13,125 

2  St  30' 
8,400 

3  St.  40' 
11,550 

2  St.  30' 
8,400 

3  St:  40' 
12,600 

1  St.  20' 
8,925 

1  St.  20' 
4,200 

A-2        Assembly;   night  clubs  and 
similar  uses 

N.L. 

N.L. 
7,200 

3  St.  40' 
5,700 

2  St.  30' 
3,750 

1  St.  20' 
2,400 

2  St.  30' 
3,300 

1  St.  20' 
2,400 

2  St.  30' 
3,600 

1  St.  20' 
2,550 

1  St.  20' 
1,200 

A-3    Assembly;  lecture  halls,  recre- 
ation centers,  terminals,  restaurants 
other  than  night  clubs 

N.L. 

N.L. 

5  St.  65' 
19,950 

3  St.  40' 
13,125 

2  St.  30' 
8.400 

3  St.  40' 

11.550 

2  St.  30' 

8,400 

3  St.  40' 
12,600 

1  St.  20' 
8,925 

1  St.  20' 
4,200 

A-4   Assembly;  churches 

Notec 

N.L. 

N.L. 

5  St.  65' 
34,200 

3  St.  40' 
22,500 

2  St.  30' 
14,400 

3  St.  40' 
19,800 

2  St.  30' 
14,400 

3  St.  40' 
21,600 

1  St.  20' 
15,300 

1  St.  20' 
7,200 

B   Business 

N.L. 

N.L. 

7  St.  85' 
34,200 

5  St  65' 
22,500 

3  St.  40' 
14,400 

4  St.  50' 
19,800 

3  St.  40' 
14,400 

5  St.  65' 
21,600 

3  St.  40' 
15,300 

2  St.  30' 
7,200 

E    Educational                          Note  c 

N.L. 

N.L. 

5  St.  65' 
34,200 

3  St.  40' 
22,500 

2  St.  30' 
14,400 

3  St.  40' 
19.800 

2  St.  30' 
14,400 

3  St.  40' 
21,600 

1  St.  20' 
15,300 
Noted 

1  St.  20' 
7,200 

Noted 

F-l    Factory  and  industrial 
Moderate 

N.L. 

N.L. 

6  St.  75' 
22,800 

4  St.  50' 
15,000 

2  St.  30' 
9,600 

3  St.  40' 
13,200 

2  St.  30' 
9,600 

4  St.  50' 
14,400 

2  St.  30' 
10,200 

1  St.  20' 
4,800 

F-2  Factory  and  Industrial 

low                                     Note  h 

N.L. 

N.L. 

7  St.  85' 
34,200 

5  St.  65' 
22,500 

3  St.  40' 
14,400 

4  St.  50' 
19,800 

3  St.  40' 
14,400 

5  St  65' 
21,600 

3  St.  40' 
15,300 

2  St.  30' 
7.200 

H-l  High  hazard, 

delonaton  hazards   Notes  e,  i,  k,  1 

1  St,20' 
16.800 

1  St.  20' 
14,400 

1  St.  20' 
11,400 

1  St.  20' 
7,500 

1  St.  20' 
4,800 

1  St  20' 
6,600 

1  St  20' 
4,800 

!  St  20' 
7,200 

1  St.  20' 
5,100 

N.P 

H-2   High  Hazard 

deflagration  hazards  Note  e,i,j,l 

5  St.  65' 
16,800 

3  St.  40' 
14,400 

3  St.  40' 
11,400 

2  St.  30' 

7,500 

1  St.  20' 
4,800 

2  St.  30' 
6,600 

1  St.  20' 
4,800 

2  St.  30' 
7,200 

1  St.  20' 
5,100 

N.P. 

H-3  High  Hazard 

physical  hazards            Note  e,l 

7  St.  85' 
33,600 

7  St.  85' 
28,800 

6  St.  75' 
22,800 

4  St.  50' 
15,000 

2  St.  30' 
9,600 

3  St.  40' 
13,200 

2  St,  30' 
9,600 

4  St.  50' 
14,400 

2  St.  30' 
10,200 

1  St.  20' 
4,800 

H-4   High  Hazard 

health  hazards                Note  e,l 

7  St.  85' 
N.L. 

7  St.  85' 
N.L. 

7  St.  85' 
34,200 

5  St.  65' 
22,500 

3  St.  40' 
14,400 

4  St.  50' 
19,800 

3  St.  40' 
14,400 

5  St.  65' 
21,600 

3  St.  40' 
15,300 

2  St.  30' 
7,200 

1-1  Institutional,  residential  care 

N.L. 

N.L. 

9  St.  100' 
19,950 

4  St.  50' 
13,125 

3  St.  40' 
8,200 

4  St.  50' 
11.550 

3  St.  40' 
8,400 

4  St.50' 
12,600 

3  St.  40' 
8,925 

2  St.  35' 
4,200 

1-2   Institutional,  incapacitated 

Notem 

N.L. 

NX. 

4  St.  50' 
17,100 

2  St.  30' 
11,250 

1  St.  20' 
7,200 

1  St.  20' 
9,900 

N.P. 

1  St.  20' 
10,800 

1  St.  20' 
7,650 

N.P 

1-3   Institutional,  restrained 

N.L. 

N.L. 

4  St.  50' 
14,250 

2  St.  30' 
9,375 

1  St.  20' 
6,000 

2  St.  30' 
8,250 

i  Si  20' 
6,000 

2  St.  30' 
9,000 

1  St.  20' 
6.375 

N.P. 

M    Mercantile 

N.L. 

N.L. 

6  St.  75' 
22,800 

4  St.  50' 
15,000 

2  St.  30' 
9,600 

3  St.  40' 
13,200 

2  St.  30' 
9,600 

4  St.  50' 
14,400 

2  St.  30' 
10,200 

1  St.  20' 
4,800 

R-l    Residential,  hotels 

N.L. 

N.L. 

9  St.  100' 
22,800 

4  St.  50' 
15,000 

3  St.  40' 
9,600 

4  St.  50' 
13,200 

3  St.  40' 
9,600 

4  St.  50' 
14,400 

3  St.  40' 
10,200 

2  St.  35' 
4,800 

R-2   Residential,  multi-family 

NX. 

N.L. 

9  St.  100' 
22,800 

4  St.  50' 
15,000 
Notef 

3  St.  40" 
9,600 

4  St.  50' 
13,200 
Notef 

3  St.  40' 
9,600 

4  St.  50' 
14,400 

3  St.  40' 
10,200 

2  St.  35' 
4,800 

R-3   Residential, 

multiple  single  family 

N.L. 

N.L. 

4  St.  50' 
22,800 

4  St.  50' 
15,000 

3  St.  40' 
9,600 

4  St.  50' 
13,200 

3  St.  40' 
9,600 

4  St.  50' 
14,400 

3  St  40' 
10.200 

2  St.  35' 
4,800 

S-l    Storage,  moderate 

N.L. 

N.L. 

5  St.  65' 
19,950 

4  St.  50' 
13,125 

2  St.  30' 
8,400 

3  St.  40' 
11,550 

2  St.  30' 
8.400 

4  St.  50' 
12,600 

2  St.  30' 
8,925 

1  St.  20' 
4,200 

S-2   Storage,  low                    Note  g 

N.L. 

N.L. 

7  St.  85' 
34,200 

5  St.  65' 
22,500 

3  St.  40' 
14,400 

4  St.  50' 
19,800 

3  St.  40' 
14,400 

5  St.  65' 
21,600 

3  St.  40' 
15,300 

2  St.  30' 
7,200 

TJ   Utility,  miscellaneous 

N.L. 

NX. 

Notes  applicable  to  Table  503: 

Note  a.  See  the  following  sections  for  general  exceptions  to  Table  503: 

780  CMR  504.2  Allowable  height  increase  due  to  automatic  sprinkler  system  installation. 


114 


780  CMR  -  Sixth  Edition    corrected  -  9/1 9/97  (Effective  2/28/97) 


780  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

GENERAL  BUILDING  LIMITATIONS 

780  CMR  506.2  Allowable  area  increase  due  to  street  frontage. 

780  CMR  506.3  Allowable  area  increase  due  to  automatic  fire  suppression  system  installation. 

780  CMR  506.4  Allowable  area  reduction  for  multi-story  buildings. 

780  CMR  507.0  Unlimited  area  one-story  buildings. 
Note  b.  Buildings  of  Type  1  construction  permitted  to  be  of  unlimited  tabular  heights  and  areas  are  not  subject  to 
special  requirements  that  allow  increased  heights  and  areas  for  other  types  of  construction  (see  780  CMR  503.1  4) 
Note  c.  For  height  exceptions  for  auditoriums  in  occupancies  in  Use  Groups  A-4  and  E,  see  780  CMR  504  3 
Note  d.  For  height  exceptions  for  day  care  centers  in  buildings  of  Type  5  construction,  see  780  CMR  504.4 
Note  e.  For  exceptions  to  height  and  area  limitations  of  buildings  for  Use  Group  H.  see  780  CMR  4  governing  the 
specific  use  groups. 

Note  f.   For  exceptions  to  height  of  buildings  for  Use  Group  R-2  of  Tvpes  2B  and  3  A  construction,  see  780  CMR 
504.6  and  504.7. 

Note  g.  For  height  and  area  exceptions  for  open  parking  structures,  see  780  CMR  406.0 
Note  h.  For  exceptions  to  height  and  area  limitations  for  special  industrial  occupancies,  see  780  CMR  503.1.1. 
Note  i.  Occupancies  in  Use  Groups  H-l  and  H-2  shall  not  be  permitted  below  grade 

Note  j.   Rooms  and  areas  of  Use  group  H-2  containing  pyrophonc  materials  shall  not  be  permitted  in  buildings  of 
Type  3. 4,  or  5  construction. 

Note  k.  Occupancies  in  Use  Group  H- 1  are  required  to  be  detached  one-story  buildings  (see  780  CMR  707  1.1). 
Note  I.  For  exceptions  to  height  for  buildings  with  occupancies  in  Use  Group  H.  see  780  CMR  504.5 
Note  m.    Hospitals,  other  than  college  or  school  infirmaries,  shall  be  constructed  of  Type  1-B  or  higher 
construction. 
Note  n.  1  foot  =  304.8  mm;  1  square  fool  =  0.093  m* 


503.1.4  Type  1  construction:  Buildings  of 
Type  1  construction  which  are  permitted  to  be  of 
unlimited  tabular  heights  and  areas  by  Table  503, 
are  not  subject  to  the  special  requirements  that 
allow  increased  heights  and  areas  for  other  types 
of  construction. 

503.2  Area  limitations:  The  area  limitations 
specified  in  Table  503  shall  apply  to  the  maximum 
horizontally  projected  area  of  all  buildings  fronting 
on  a  street  or  a  public  space  not  less  than  30  feet 
(9144  mm)  in  width  with  access  from  a  public  street 

503.3  Height  limitations:  The  height  in  feet  and  the 
number  of  stories  above  grade  specified  in  Table 
503  shall  apply  to  all  buildings  and  to  all  separate 
pans  of  a  building  that  are  enclosed  within_/?re  walls 
complying  with  the  provisions  of  780  CMR  7.  A 
basement  shall  be  considered  as  a  story  above  grade 
where  the  finished  surface  of  the  floor  above  the 
basement  is  more  than  six  feet  (1829  mm)  above 
grade  plane ;  or  more  than  six  feet  (1829  mm)  above 
the  finished  ground  level  for  more  than  50%  of  the 
total  building  perimeter;  or  more  than  12  feet  (3658 
mm)  above  the  finished  ground  level  at  any  point 

780  CMR  504.0  HEIGHT 
MODIFICATIONS 

504.1  General:  The  provisions  of  780  CMR  504.0 
shall  modify  the  height  limitations  of  Table  503  as 
herein  specified. 

504.2  Automatic  sprinkler  systems:  Where  a 
building  is  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1,  the  building  height  limitation  specified  in 
Table  503  shall  be  increased  one  story  and  20  feet 


(6096  mm).  This  increase  shall  not  apply  to 
buildings  of  Types  2C,  3A.  4  and  5 A  construction 
with  an  occupancy  in  Use  Group  1-2,  or  to  buildings 
with  an  occupancy  in  Use  Group  H-l,  H-2  or  H-3 
The  building  height  limitations  for  buildings  with  an 
occupancy  in  Use  Group  R  specified  in  Table  503 
shall  be  increased  one  story  and  20  feet  (6096  mm) 
but  not  to  exceed  a  height  of  four  stones  and  60  feet 
(18288  mm)  where  the  building  is  equipped 
throughout  with  an  automatic  sprinkler  system 
installed  in  accordance  with  780  CMR  906.2.2  and 
the  system  is  supervised  in  accordance  with 
780  CMR  923.1,  method  1,  2  or  3. 

504.3  Auditoriums:  The  maximum  height  of 
auditoriums  in  Use  Groups  A-4  and  E  shall  be  65 
feet  (19812  mm)  in  buildings  of  Type  2B,  3A.4  or 
5A  construction  and  45  feet  (13716  mm)  in 
buildings  of  Type  2C,  3B  or  5B  construction. 

504.4  Day  care  centers:  The  height  limitations  of 
Table  503  for  day  care  centers  classified  as  Use 
Group  E.  in  buildings  of  Type  5  construction,  shall 
be  increased  one  story  and  20  feet  (6096  mm) 
provided  that  the  total  occupant  load  is  less  than  50 
persons. 

504.5  High-hazard  use  groups:  Buildings  and 
structures  with  an  occupancy  in  Use  Group  H  that 
requires  unusual  heights  necessary  to  accommodate 
special  manufacturing  processes  and  equipment  shall 
be  exempt  from  the  tabular  height  limitations,  in 
feet,  of  Table  503. 

504.6  Type  3A  construction:  The  height  limitation 
for  buildings  of  Type  3  A  construction  with 
occupancies  in  Use  Group  R-2  shall  be  increased  to 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


1 1 5 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


six  stories  and  75  feet  (22860  mm)  where  the  first 
floor  construction  above  the  basement  has  a 
fireresistance  rating  of  not  less  than  three  hours  and 
the  floor  area  is  subdivided  by  two-hour 
fireresistance  rated  fire  walls  into  fire  areas  of  not 
more  than  3,000  square  feet  (279  m2). 

504.7  Type  2B  construction:  The  height  limitation 
for  buildings  of  Type  2B  construction  with 
occupancies  in  Use  Group  R-2  shall  be  increased  to 
nine  stories  and  100  feet  (30480  mrn)  where  the 
building  is  separated  by  not  less  than  50  feet  (15240 
mm)  from  any  other  building  on  the  lot  and  from 
interior  lot  lines,  the  exits  are  segregated  in  afire 
area  enclosed  by  a  2-hour  fire  resistance  rated  fire 
wall  and  the  first  floor  construction  has  a  fire- 
resistance rating  of  not  less  than  1  Vi  hours 

780  CMR  505.0  MEZZANINES 

505.1  General:  A  mezzanine  or  mezzanines  in 
compliance  with  780  CMR  505.0  shall  be  considered 
a  portion  of  the  floor  below.  Such  mezzanines  shall 
not  contribute  to  the  building  area  as  regulated  by 
780  CMR  503.2.  Such  mezzanines  shall  not 
contribute  to  the  number  of  stories  as  regulated  by 
780  CMR  503.3.  The  area  of  the  mezzanine  shall  be 
included  in  determining  the^re  area. 

505.2  Area  limitation:  The  aggregate  area  of  a 
mezzanine  or  mezzanines  within  a  room  shall  not 
exceed  Vz  of  the  area  of  that  room.  The  enclosed 
portions  of  rooms  shall  not  be  included  in  a 
determination  of  the  size  of  the  room  in  which  the 
mezzanine  is  located  In  determining  the  allowable 
mezzanine  area,  the  area  of  the  mezzanine  shall  not 
be  included  in  the  area  of  the  room. 

Exception:  The  aggregate  area  of  mezzanines  in 
buildings  and  structures  of  Type  1  or  2 
construction  for  special  industrial  occupancies  in 
accordance  with  780  CMR  503.1.1  shall  not 
exceed  %  of  the  area  of  that  room. 

505.3  Egress:  Each  occupant  of  a  mezzanine  shall 
have  access  to  at  least  two  independent  means  of 
egress  where  such  spaces  require  two  means  of 
egress  in  accordance  with  780  CMR  1017.2.  Where 
a  stairway  provides  a  means  of  exit  access  from  a 
mezzanine,  the  maximum  travel  distance  required  by 
780  CMR  1017.2  shall  be  measured  to  the  bottom  of 
the  stairway. 


505.4  Openness:  A   mezzanine  shall  be  open  and 
unobstructed  to  the  room  in  which  such  mezzanine 
is  located  except  for  walls  not  more  than  42  inches 
(1067  mm)  high,  columns  and  posts 
Exceptions 

1 .  Mezzanines  or  portions  thereof  are  not  required 
to  be  open  to  the  room  in  which  the  mezzanines 
are  located,  provided  that  the  occupant  load  of  the 
aggregate  area  of  the  enclosed  space  does  not 
exceed  ten. 

2  A  mezzanine  having  two  or  more  means  of 
egress  is  not  required  to  be  open  to  the  room  in 
which  the  mezzanine  is  located,  if  at  least  one  of 
the  means  of  egress  provides  direct  access  to  an 
exit  from  the  mezzanine  level. 

780  CMR  506.0  AREA  MODIFICATIONS 

506.1  General:  The  provisions  of  780  CMR  506.0 
shall  modify  the  area  limitations  of  Table  503  as 
herein  specified 

506.2  Street  frontage  increase:  Where  a  building  or 
structure  has  more  than  25%  of  the  building 
perimeter  fronting  on  a  street  or  other  unoccupied 
space,  the  area  limitations  specified  in  Table  503 
shall  be  increased  2%  for  each  1  %  of  such  excess 
frontage  The  unoccupied  space  shall  be  on  the  same 
lot  or  dedicated  for  public  use,  shall  not  be  less  than 
30  feet  (9144  mm)  in  width  and  shall  have  access 
from  a  street  by  a  posted  fire  lane  not  less  than  1 8 
feet  (5486  mm)  in  width. 

506.3  Automatic  sprinkler  system:  Where  a 
building,  other  than  those  with  an  occupancy  in  Use 
Group  H-l.  H-2  or  H-3,  is  equipped  throughout  with 
an  automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1.  the  area 
limitation  specified  in  Table  503  shall  be  increased 
200%  for  one-and  two-story  buildings  and  100% 
for  buildings  more  than  two  stories  in  height. 

506.4  Multistory  buildings:  The  area  limitations 
for  buildings  two  stories  in  height  shall  be  the  same 
as  the  area  limitations  provided  in  Table  503  for 
one-story  buildings.  In  buildings  over  two  stories  in 
height,  the  area  limitations  of  Table  503  for  one- 
story  buildings  shall  be  reduced  as  specified  in  Table 
506.4. 


116 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

GENERAL  BUILDING  LIMITATIONS 


Table  506.4 
REDUCTION  OF  AREA  LIMITATIONS 


Number  of 

Type  of  Construction 

stories 

1A&1B 

2A 

2B,  2C,  3A,  3B,  4,  5A. 
5B 

1 

None 

None 

None 

2 

None 

None 

None 

3 

None 

5% 

20% 

4 

None 

10% 

20% 

5 

None 

15% 

30% 

6 

None 

20% 

40% 

7 

None 

25% 

50% 

8 

None 

30% 

60% 

9 

None 

35% 

70% 

10 

None 

40% 

80% 

780  CMR  507.0  UNLIMITED  AREAS 
507.1  One-story  buildings:  For  all  occupancies 
other  than  Use  Groups  A-l.  A-2,  A-4,  A-5,  E,  H,  I-i, 
1-3  and  R  the  area  of  buildings  that  do  not  exceed 
one  story  and  85  feet  (25908  mm)  in  height,  other 
than  buildings  of  Type  5  construction,  shall  not  be 
limited,  provided  that  the  building  is  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2. 1 :  and  the  building 
is  isolated  as  specified  in  780  CMR  507.2.  Buildings 
with  an  occupancy  in  Use  Group  1-2  shall  not  be 
constructed  of  Type  3B  construction.  Except  as 
modified  by  780  CMR  9,  fire  areas  of  Use  Group  E 
are  permitted  in  unlimited  area  buildings  in 
accordance  with  780  CMR  507.1.1.  Except  as 
modified  by  780  CMR  9,  fire  areas  of  Use  Groups 
H-2,  H-3  and  H-4  are  permitted  in  unlimited  area 
buildings  in  accordance  with  780  CMR  507.1.2. 
Exceptions: 

1.  Buildings  and  structures  of  special  industrial 
occupancies  in  accordance  with  780  CMR  503. 1 . 1 
shall  be  exempt  from  the  above  height  limitations 
and  fire  separation  distance  requirements,  and  the 
automatic  fire  suppression  system  shall  not  be 
provided  where  such  installations  will  be 
detrimental  or  dangerous  to  the  specific 
occupancy  as  approved  by  the  code  official 
Where  located  with  afire  separation  distance  of 
less  than  30  feet  (9144  mm),  the  exterior  walls  of 
such  buildings  shall  be  protected  or  constructed  to 
provide  a  fireresistance  rating  of  not  less  than  two 
hours. 

2.  An  automatic  fire  suppression  system  shall  not 
.  be  required  for  buildings  of  Type  2  or  Type  4 

construction  which  are  occupied  exclusively  for 
the  storage  of  noncombustible  materials  that  are 
not  packed  or  crated  in  combustible  materials 

3.  Buildings  and  structures  of  Types  1  and  2 
construction  for  rack  storage  facilities  which  do 
not  have  access  by  the  public  shall  not  be  limited 
in  height  provided  that  such  buildings  conform  to 


the  requirements  of  780  CMR  507.1  and  NFiPA 
23 1  C  listed  in  Appendix  A. 

4.  The  automatic  sprinkler  system  shall  not  be 
required  in  areas  occupied  for  indoor  participant 
sports,  such  as  tennis,  skating,  swimming  and 
equestrian  activities,  in  occupancies  in  Use  Group 
A-3  provided  that: 

4.1.  Exit  doors  directly  to  the  outside  are 
provided  for  all  occupants  of  the  participant 
sport  areas;  and 

4.2.  The  building  is  equipped  with  a  fire 
protective  signaling  system  with  manual  fire 
alarm  boxes  installed  in  accordance  with 
780  CMR  917.0. 

5.  Bulk  Merchandi&ng  Retail  Buildings  are 
permitted  to  be  constructed  and  operated  as 
unlimited  area  buildings  in  accordance  with 
780  CMR  426.0 

507.1.1  School  buildings:  For  occupancies  in  Use 
Group  E.  one-story  buildings  of  Type  2,  3  A  or  4 
construction  shall  not  be  limited  in  area  where  a 
direct  exit  to  the  outside  of  the  building  is 
provided  from  each  classroom  and  the  building  is 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1 
Exterior  walls  on  all  sides  of  such  buildings  shall 
comply  with  780  CMR  507.2. 

507.1.2  High-hazard  use  groups  Use  Group  H- 
2.  H-3  and  H-4  fire  areas  shall  be  permitted  in 
occupancies  in  Use  Groups  F  and  S  except  as 
modified  by  780  CMR  9,  and  in  lecture  halls  and 
laboratories  in  Use  Groups  A-3.  B,  E  and  1-2  in 
accordance  with  the  limitations  of  780  CMR 

507.1.  Fire  areas  located  at  the  perimeter  of  the 
building  shall  not  exceed  the  area  limitations 
specified  in  Table  503  as  modified  by  780  CMR 

506.2,  based  upon  the  percentage  of  the  perimeter 
of  the  fire  area  that  fronts  on  a  street  or  other 
unoccupied  space.  Interior  fire  areas  shall  not 
exceed  25%  of  the  area  limitations  specified  in 
Table  503.  Fireresistance  rating  requirements  of 
fire  separation  assemblies  shall  be  in  accordance 
with  Table  313.1.2. 

507.2  Exterior  walls:  The  minimum  fireresistance 
rating  of  exterior  walls  of  one-story  buildings  of 
unlimited  area  shall  be  determined  by  the  use  group 
and  the  fire  separation  distance  as  specified  in  Table 
507.2,  but  shall  not  be  less  than  the  fireresistance 
rating  required  by  Table  602  for  the  type  of 
construction.  The  entire  perimeter  of  one-story 
unlimited  area  buildings  shall  have  a  minimum  fire 
separation  distance  of  30  feet  (9144  mm) 

Exception:  The  minimum  fire  separation 
distance  of  30  feet  (9144  mm)  shall  not  apply  to 
a  wall  facing  another  building  on  the  same  lot, 
provided  that: 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


117 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1 .  Such  wall  is  constructed  as  a  fire  wall  in 
accordance  with  780  CMR  707.0; 

2.  The  length  of  the  fire  wall  does  not  exceed 
25%  of  the  total  perimeter  of  the  unlimited  area 
building; 

3.  The  adjacent  building  has  a  minimum  fire 
separation  distance  of  30  feet  (9144  mm)  on 
all  sides,  except  for  the  side  that  faces  the 
unlimited  area  building,  and 

4.  The  adjacent  building  is  equipped 
throughout  with  an  automatic  sprinkler  system 
in  accordance  with  780  CMR  906.2.1. 

507.2.1  Opening  protective:  Openings  in 
exterior  walls  required  by  Table  507.2  to  have  a 
fire  resistance  rating  of  three  hours  or  more  shall 
be  protected  with  fire  assemblies  having  a  fire 
resistance  rating  of  not  less  than  three  hours. 


Openings  in  exterior  walls  required  by  Table 
507.2  to  have  a  fire  resistance  rating  of  two  hours 
shall  be  protected  with  fire  assemblies  having  a 
fire  protection  rating  of  not  less  than  1  'A  hours. 

Table  507.2 

MINIMUM  FIRE  RESISTANCE  RATING 

OF  EXTERIOR  WALLS 


Use  Group 

Fireresistance  rating  (hours)  based  on 
fire  separation  distance 

30  Feet  or  greater  but 
less  than  50  feet 

50  feet  or 
greater 

E 

VA 

0 

A-3,  B,  F-2, 1-2,  S-2 
F-l.M.  S-l 

2 
3 

0 

0 

Note  a  1  foot  =  304.8  mm. 


118 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


CHAPTER  6 


TYPES  OF  CONSTRUCTION 


780  CMR  601.0  GENERAL 

601.1  Scope:  The  provisions  780  CMR  6  shall 
control  the  classification  of  all  buildings  as  to  type 
of  construction 

601.2  Application  of  other  laws:  The  provisions  of 
780  CMR  6  shall  not  be  deemed  to  nullify  any 
provisions  of  the  zoning  law  or  any  other  statute  of 
the  jurisdiction  pertaining  to  the  location  or  type  of 
construction  of  buildings,  except  as  is  specifically 
required  by  the  provisions  of  780  CMR. 

601.3  Hospitals:  Pursuant  to  M.  G.L.  c.  Ill,  §  51, 
hospitals  other  than  college  and  school  infirmaries 
shall  be  constructed  of  at  least  Type  1-B 
construction. 

780  CMR  602.0  CONSTRUCTION 
CLASSIFICATION 

602.1  General:  All  buildings  and  structures  erected 
or  to  be  erected,  altered  or  extended  in  height  or 
area  shall  be  classified  in  one  of  the  five 
construction  types  defined  in  Table  602  and 
780  CMR  603.0  through  606.0 

602.2  False  designation:  A  building  shall  not  be 
designated  as  a  given  type  of  construction  unless  it 
conforms  to  the  minimum  requirements  for  that  type. 

602.3  Minimum  requirements:  Where  a  type  of 
construction  is  used  that  is  superior  to  the  minimum 
herein  required  for  any  specified  use,  height  and  area 
of  the  building,  nothing  in  780  CMR  shall  be 
construed  to  require  full  compliance  with  the 
specifications  for  the  higher  type;  but  the  designated 
construction  classification  of  the  building  shall  be 
that  of  the  lesser  type,  unless  all  of  the  requirements 
for  the  higher  type  are  fulfilled. 

602.4  Noncombustibility  requirements:  Where  a 
structure  or  a  part  of  a  structure  is  required  to  be 
constructed  of  noncombustible  construction,  the  use 
of  combustible  elements  shall  be  permitted  subject 
to  the  limitations  of  780  CMR  602.0  without  altering 


the  construction  classification. 

602.4.1  Roofs,  floors  and  wails:  Combustible 
elements  in  roofs,  floors  and  walls  are  permitted 
to  be  used  for  the  following  components: 

1.  Interior  finish  and  trim  materials  as 
regulated  by  780  CMR  803.0,  804.0  and  806.0. 

2.  Light-transmitting  plastics  as  permitted  by 
780  CMR  26. 

3 .  Fireretardant-treated  wood  complying  with 
780  CMR  2310.0  as  permitted  by  Table  602. 

4.  Mastics  and  caulking  materials  applied  to 
provide  flexible  seals  between  components  of 
exterior  wall  construction. 

5.  Roof  covering  materials  as  regulated  by 
780  CMR  15. 

6  Thermal  and  sound  insulation  as  permitted 
by  780  CMR  707.4.722.0.  1509.0.  2309.4  and 
2603.0. 

7.  Exterior  veneer  and  trim  as  permitted  by 
780  CMR  1406.0. 

8.  Nailing  or  furring  strips  as  permitted  by 
780  CMR  804.0. 

9.  Windows  and  doors  as  permitted  bv 
780  CMR  706.4. 

10.  Heavy  timber  as  permitted  by  780  CMR 
1006.3.1,  714.2  and  714.4 

11.  Partitions  as  permitted  by  780  CMR  603.2. 

12.  Roof  structures  as  permitted  by  780  CMR 
1510.0. 

13.  Platforms  as  permitted  by  780  CMR 
412.4.1. 

602.4.2  Ducts:  The  use  of  nonmetallic  ducts  is 
permitted  in  accordance  with  the  mechanical  code 
listed  in  Appendix  A. 

602.4.3  Piping:  The  use  of  combustible  piping 
materials  is  permitted  in  accordance  with  the 
mechanical  and  plumbing  codes  listed  in 
Appendix  A. 

602.4.4  Electrical:  The  use  of  insulated  electrical 
wiring  and  related  components  is  permitted  in 
accordance  with  NFiPA  70  listed  in  Appendix  A 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


119 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  602 
FIRE  RESISTANCE  RATINGS  OF  STRUCTURE  ELEMENTS 


Tvpe  ot  construction    780  CMR  602.0 

Noncombustible 

Noncombustible/Combustible 

Combustible 

Type! 

780  CMR 

603.0 

Type  2 
780  CMR  603.0 

Type  3 
780  CMR  604.0 

Type  4 

780  CMR 

605.0 

Type  5 
780  CMR  606.0 

Structure  element 

Protected 

Protected 

Unprotected 

Protected 

Unprotected 

Heavy  timber 
Notec 

Protected 

Unprotected 

Note  a 

1A  1  IB 

2A  |  2B 

2C 

3A 

3B 

4 

5A 

5B 

1    Exterior  walls 

Loadbearing 

4    |    3 

2    1    1              0                 2                 2                     2                    1                   0 
Mot  less  than  the  ratmg  based  on  fire  separation  distance  (see  780  CMR  705.2)  - 

Nonloadbearing 

-  Not  less  than  the  ratmg  based  on  fire  separation  distance  (see  780  CMR  705.2)  - 

2    Fire  walls  and  party  walls 
(780  CMR  707.0) 

4    |    3    |    2    |    2    |          2          |       2        |          2           |           2           |         2          |          2 
-Not  less  than  the  fireresistance  rating  required  bv  Table  707. 1  - 

Fire  enclosure  of 
exits  (780  CMR 
1014.11,709.0 
and  Note  b) 

2 

2 

2 

2 

2 

2 

2 

2 

2 

3    Fire  separation 
assemblies  (780 
CMR  709.0) 

Shafts  (other  than 
exits)  &  elevator 
hoistway  (780 
CMR  709,  710.0 
&  Note  b) 

2 

2 

2 

2 

1 

2 

2 

1 

1 

Mixed  use  &  fire 
area  separations 
(780  CMR  31 3. 01 

-  Not  less  than  the  fireresistance  ratmg  required  by  Table  3 1 3. 1 .2  - 

Other  Separation 
assemblies 

(Note  i) 

-Noted  - 

1 

1 

1 

1 

1 

4    Fire  partitions 

Exit  access 
corridors 
(Note  g) 

-  Not  less  then  the  fu 
-Note  d  - 

eresistanc 

:  ratmg  requir 

ed  by  780  CM} 

I  1011.4- 

711.0) 

Tenant  spaces 
separations  (Note 
0 

1    ,1     |,     |,     |          0 
-Note  d  - 

1 

0 

1 

i 

0 

5    Dwelling  unit  separations 

(780  CMR  71 1.0,  713.0  &  Notes  f 

-Noted  - 

I 

1 

1 

i 

1 

6    Smoke  barriers  (780CMR  7 12.0& 

Note  g) 

1 

1 

1 

1 

1 

1 

i 

1 

1 

1 

7    Other  nonloadbearing  partitions 

0 

0    |    0 

-N 

0 
3ted- 

0 

0 

0 

0 

0 

0 

8    Interior  load- 
bearing  walls, 
loadbearing  par- 
titions, col- 
umns, girders, 

Supporting  more 
than  one  floor 

4 

3 

2 

1     1         0 

» 

0 

See 

780  CMR 
605.0 

1 

0 

trusses  (other 
than  roof  truss- 
es) &  framing 
(780  CMR 
715.0) 

Supporting  one 
floor  only  or  a 
roof  only 

3 

2 

VA 

1 

0 

1 

0 

See 

780  CMR 
605.0 

1 

0 

9    Structural  members  supporting  wall 
(780  CMR  71 5.0  &  Note  g) 

3 

2 

1J4 

1 

0          j        1 
-Not  less  than  fireresi. 

0 
tance  rating  o 

1 
"wail  supporte 

1 

d- 

0 

10  Floor  construction  including  beams 
(780  CMR  71 3.0  &  Note  h) 

3 

2 

V/z 

I 

0          '        i 
1 

0 

See  780 

CMR 

605.0,  Note  c 

0 

1 1  Roof  construc- 
tion, including 
beams,  trusses 

1 5'  or  less  in 
height  to  lowest 
member 

2 

114 

1 

1 

-N 

otea  - 

0 

See  780 
CMR 

605.0.  Note  c 

1 

0 

and  framing, 
arches  &  roof 
deck  (780  CMR 
714.0  &  Notes 

More  than  1 5'  but 
less  than  20'  in 
height  to  lowest 
member 

1 

1 

1    !   0    |         0 

1                    o:o 

-Note  d  - 

1                I 

See 

780  CMR 

605.0 

1 

0 

e.i) 

20'  or  more  in 
height  to  lowest 
member 

0  |  0  1  0   |  o   i        o        i 

-Note  d  -                    i                ! 

J i i 

See 
780  CMR 
1        605  0 

!    » 

l 

i       o 
1 

120 


780  CMR  -  Sixth  Edition    corrected  -  9/1 9 '97  (Effective  2/28/9" 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

TYPES  OF  CONSTRUCTION 


Note   a.  For  fireresistance  rating  requirements   for  structural  membranes   and  assemblies  which  support  other 

fireresistance  rated  members  or  assemblies,  see  780  CMR  715.1. 

Note  b.  For  reductions  in  the  required  fireresistance  rating  of  exit  and  shaft  enclosures,  see  780  CMR  1014.11  and 

710.3 

Note  c.  For  substitution  of  other  structural  materials  for  timber  in  T>pe  4  construction,  see  780  CMR  2304.2. 

Note  d.  For  fire  retardant-treated  wood  permitted  in  roof  construction  and  nonloadbearing  walls  where  the  required 

fireresistance  rating  is  one  hour  or  less,  see  780  CMR  603.2  and  23 10.0. 

Note  e.  For  permitted  uses  of  heavy  timber  in  roof  construction  in  buildings  of  Tvpes  1  and  2  construction,  see 

780  CMR  714.4. 

Note  f.  For  reductions  in  required  fireresistance  ratings  of  tenant  separations  and  dwelling  unit  separations,  see 

780CMR  101 1.4  and  1011.4.1. 

Note  g.  For  exceptions  to  the  required  fireresistance  rating  of  construction  supporting  exit  access  corridor  walls,  tencnt 

separation  walls  in  covered  mall  buildings,  and  smoke  barriers,  see  780  CMR  71 1.4  and  712.2. 

Note  h.  For  buildings  having  habitable  or  occupiable  stories  or  basements  below  grade,  see  780  CMR  1006.3.1. 

Note  i.  Not  less  than  the  rating  required  by  780  CMR. 

Note  j.  For  Use  Group  R-3,  see  780  CMR  3 10.5. 

Note  k.  Fireresistance  ratings  are  expressed  in  hours. 

Note  I.  1  foot  =  304.8  mm. 


780  CMR  603.0  TYPES  1  AND  2 
CONSTRUCTION 

603.1  General:  Buildings  and  structures  of  Types  1 
and  2  construction  are  those  in  which  the  walls, 
partitions,  structure  elements,  floors,  ceilings,  roofs 
and  exits  are  constructed  of  approved 
noncombustible  materials.  Each  structure  element 
shall  not  be  less  than  the  required  fireresistance 
rating  specified  in  Table  602,  except  as  otherwise 
specifically  provided  for  in  780  CMR.  Buildings  of 
Types  1  and  2  construction  shall  be  further  classified 
as  Type  1A,  IB,  2A,  2B  or  2C.  Fireretardant- 
treatedwood  shall  only  be  used  as  specified  in  Table 
602  and  780  CMR  23 10.0. 

603.2  Interior  partitions:  In  buildings  or  structures 
of  Types  1,  2  A  and  2B  construction,  partitions  of  a 
single  thickness  of  wood  or  approved  composite 
panels,  and  glass  or  other  approved  materials  of 
similar  combustible  characteristics,  are  permitted  to 
subdivide  rooms  or  spaces  into  offices,  entries  or 
other  similar  compartments  in  all  occupancies  other 
than  Use  Groups  I  and  R,  provided  that  such 
partitions  neither  establish  a  corridor  serving  an 
occupant  load  of  more  than  30  in  areas  occupied  by 
a  single  tenant  nor  exceed  5,000  square  feet  (465  m2) 
between_/?re  separation  assemblies  ox  fire  walls.  The 
maximum  allowable  compartment  size  shall  be 
increased  to  7,500  square  feet  (700  m2)  where 
subdivided  with  fireretardant-treated  wood  that 
complies  with  780  CMR  23  10.0. 

780  CMR  6O4.0  TYPE  3  CONSTRUCTION 
604.1  General:  Buildings  and  structures  of  Type  3 
construction  are  those  in  which:  the  exterior  walls 


are  constructed  of  masonry  or  other  approved 
noncombustible  materials;  the  interior  structure 
elements,  loadbearing  walls,  partitions,  floors  and 
roofs  are  constructed  of  any  approved  materials. 
Each  structure  element  shall  have  not  less  than  the 
required  fireresistance  rating  specified  in  Table  602, 
except  as  otherwise  specifically  provided  for  in 
780  CMR.  Buildings  of  Type  3  construction  shall  be 
further  classified  as  Type  3A  or  3B. 

780  CMR  605.0  TYPE  4  CONSTRUCTION 

605.1  General:  Buildings  and  structures  of  Type  4 
construction  are  those  in  which  the  exterior  walls  are 
constructed  of  approved  noncombustible  materials 
and  the  interior  structural  members  are  of  solid  or 
laminated  wood  without  concealed  spaces  or  the 
loadbearing  walls,  partitions,  floors  and  roofs  are 
constructed  of  any  noncombustible  materials 
permitted  by  780  CMR.  Each  structure  element 
shall  have  not  less  than  the  required  fireresistance 
rating  specified  in  Table  602.  The  elements  of 
Type  4  construction  shall  comply  with  the 
provisions  of  780  CMR  2304.0. 

780  CMR  606.0  TYPE  5  CONSTRUCTION 

606.1  General:  Buildings  and  structures  of  Type  5 
construction  are  those  in  which  the  exterior  walls, 
loadbearing  walls,  partitions  floors  and  roofs  are 
constructed  of  any  approved  materials.  Each 
structure  element  shall  have  not  less  than  the 
required  fireresistance  rating  specified  in  Table  602. 
Buildings  of  Type  5  construction  shall  be  further 
classified  as  Type  5A  or  5B. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


< 


122  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  7 


FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


780  CMR  701.0  GENERAL 

701.1  Scope:  The  provisions  of  780  CMR  7  shall 
govern  the  design  and  installation  of  all  materials 
and  methods  of  construction  in  respect  to  required 
fireresistance  rating  and  flameresistance,  as 
determined  by  the  potential  fire  hazard  of  the  use 
and  occupancy  of  the  building  or  structure  and  the 
location  and  function  of  all  integral  structural  and 
other  fireresistive  elements  of  the  building;  and  the 
installation  of  safeguards  against  the  spread  of  fire  to 
and  from  adjoining  structures. 

701.2  Performance  standards:  The  requirements  of 
780  CMR  7  shall  constitute  the  minimum  functional 
performance  standards  for  fire  protection  purposes; 
and  shall  not  be  deemed  to  decrease  or  waive  any 
strength  provisions  or  in  any  other  manner  decrease 
the  requirements  of  780  CMR  in  respect  to  structural 
safety. 

701.3  Combustible  materials:  All  materials  and 
forms  of  construction  which  develop  the 
fireresistance  ratings  required  by  780  CMR  shall  be 
acceptable  for  fireproofing  and  structural  purposes, 
except  that  combustible  component  materials  in 
structural  units  or  structural  assemblies  shall  be 
limited  in  the  types  of  construction  specified  in 
780  CMR  603.0,604.0  and  605.0,  and  in  780  CMR 
701.3.1. 

701.3.1  Combustible  components:  Combustible 
aggregates  are  permitted  in  gypsum  concrete 
mixtures  approved  for  fireresistance  rated 
construction.  Any  approved  component  material 
or  admixture  is  permitted  in  assemblies  that  meet 
the  fireresistive  test  requirements  of  780  CMR. 

780  CMR  702.0  DEFINITIONS 
702.1   General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  7  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Damper,  fire.  A  damper  arranged  to  seal  off  air  flow 
automatically  through  part  of  an  air  duct  system, 
so  as  to  restrict  the  passage  of  heat.  The  fire 
damper  shall  not  be  used  as  a  smoke  damper 
unless  the  location  lends  itself  to  the  dual  purpose 
(see  780  CMR  717.0). 

Door  assembly,  fire.  A  combination  of  the  fire  door, 
frame,  hardware  and  other  accessories  which 
together  provide  a  specific  degree  of  fire 
protection  to  the  opening  (see  780  CMR  716.0). 


Door,  fire:  A  door  and  its  assembly,  so  constructed 
and  assembled  in  place  as  to  give  protection 
against  the  passage  of  fire  (see  780  CMR  716.0). 

Drafistopping:  Building  materials  installed  to 
prevent  the  movement  of  air,  smoke,  gases  and 
flame  to  other  areas  of  the  building  through  large 
concealed  passages  such  as  attic  spaces  and  floor 
assemblies  with  suspended  ceilings  or  openweb 
trusses  (see  780  CMR  720,-0). — 

Fire  area:  The  aggregate  floor  area  enclosed  and 
bounded  by  fire  walls,  exterior  walls  or  fire 
separation  assemblies  of  a  building  (see 
780  CMR  709.2). 

Fire  partition:  A  vertical  assembly  of  materials 
having  protected  openings  and  designed  to  restrict 
the  spread  of  fire  (see  780  CMR  71 1 .0). 

Fire  protection  rating:  The  time  in  hours,  or 
fractions  thereof,  that  an  opening  protective 
assembly  will  resist  fire  exposure  as  determined 
by  the  test  standard  specified  in  780  CMR  (see 
780  CMR  706.0,716.0  and  718.0). 

Fire  separation  assembly:  A  horizontal  or  vertical 
fireresistance  rated  assembly  of  materials  having 
protected  openings,  and  designed  to  restrict  the 
spread  of  fire  (see  780  CMR  709.0). 

Fire  separation  distance:  The  distance  in  feet 
measured  from  the  building  face  to  the  closest 
interior  lot  line,  to  the  center-line  of  a  street  or 
public  way  or  to  an  imaginary  line  between  two 
buildings  on  the  same  property. 

Fire  window:  A  window  constructed  and  glazed  to 
give  protection  against  the  passage  of  fire  (see 
780  CMR  718.0). 

Fireresistance:  That  property  of  materials  or  their 
assemblies  which  prevents  or  retards  the  passage 
of  excessive  heat,  hot  gases  or  flames  under 
conditions  of  use. 

Fireresistance  rating  The  time  in  hours  or  fractions 
thereof  that  materials  or  their  assemblies  will 
resist  fire  exposure  as  determined  by  the  fire  test 
specified  in  780  CMR  (see  780  CMR  704. 1.1). 

Firestopping:  Building  materials  installed  to  prevent 
the  movement  of  flame  and  gases  to  other  areas 
of  a  building  through  small  concealed  passages  in 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


123 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


building  components  such  as  floors  walls  and 
stairs  (see  780  CMR  720.0). 

Protected  construction:  That  in  which  all  structural 
members  are  constructed,  chemically  treated, 
covered  or  protected  so  that  the  individual  unit  or 
the  combined  assemblage  of  all  such  units  has  the 
required  fireresi stance  rating  specified  for  its 
particular  application  in  Table  602;  and  includes 
protected  combustible  and  protected 
noncombustible  construction. 

Self-closing:  As  applied  to  a  fire  door  or  other 
opening  protective,  means  normally  closed  and 
equipped  with  an  approved  device  which  will 
insure  closing  after  having  been  opened  for  use 
(see  780  CMR  716.5). 

Shaft.  An  enclosed  space  extending  through  one  or 
more  stories  of  a  building,  connecting  vertical 
openings  in  successive  floors,  or  floors  and  the 
roof  (see  780  CMR  710.0). 

Single  membrane  penetration.  An  opening  through 
a  single  membrane  (one  side)  of  a  fireresistance 
rated  wall,  roof/ceiling  or  floor/ceiling  assembly 
made  to  accommodate  pipes,  tubes,  conduits, 
vents,  wires,  cables,  electrical  outlet  boxes  and 
similar  items  (see  780  CMR  709.6.5). 

Smoke  barrier.  A  continuous  membrane  that  will 
resist  the  movement  of  smoke  (see  780  CMR 
712.0). 

Smoke  compartment:  A  space  within  a  building 
enclosed  by  smoke  barriers  or  fire  separation 
assemblies  on  all  sides,  including  top  and  bottom 
(see  780  CMR  712.0). 

Through-penetration  protection  system:  Specific 
building  materials  or  assemblies  of  materials  that 
are  designed  and  installed  to  prevent  the  spread  of 
fire  through  openings  that  are  made  in 
fireresistance  rated  floors  and  walls  to 
accommodate  through-penetrating  items  such  as 
pipes,  tubes,  conduits,  vents,  wires,  cables  and 
similar  items.  The  F  rating  indicates  the  period  of 
time  that  the  through-penetration  protection 
system  is  capable  of  preventing  the  passage  of 
flame  to  the  unexposed  (nonfire)  side  of  the 
assembly  in  conjunction  with  an  acceptable  hose 
stream  test  performance.  The  T  rating  indicates 
the  period  of  time  that  the  through-penetration 
protection  system  is  capable  of  preventing  the 
passage  of  flame  and  a  maximum  individual 
temperature  rise  of  325°F  (163°C)  above  ambient 
temperature  on  the  unexposed  (nonfire)  side  of 
the  assembly  in  conjunction  with  acceptable  hose 
stream  test  performance  (see  780  CMR  707.7.2, 
709.6.1  and  713.4.1). 


Vertical  opening:  An  opening  through  a  floor  or 
roof. 

Wall 

Fire   separation    wall:    A   fireresistance    rated 
assembly  of  materials       having       protected 
openings   which   is  designed   to   restrict  the 
spread  of  fire  (see  780  CMR  709.0). 
Fire  wall:   A  fireresistance  rated  wall  having 
protected  openings,      which    restricts    the 
spread  of  fire  and  extends  continuously  from 
the  foundation  to  or  through  the  roof  (see 
7S0  CMR  707.0). 
Party  wall:  Kfire  wall  on  an  interior  lot  line 
used  or  adapted  for  joint  service  between 
two  buildings  (see  780  CMR  707.0). 

780  CMR  703.0  CONSTRUCTION 
DOCUMENTS 

703.1  General:  Construction  documents  for  all 
buildings  shall  designate  the  type  of  construction 
and  the  fireresistance  rating  of  all  structure  elements 
as  required  by  780  CMR.  The  construction 
documents  shall  include  documentation  or 
supporting  data  substantiating  all  required 
fireresistance  ratings. 

703.2  Penetrations:  Construction  documents  for 
buildings  more  than  two  stories  in  height  shall 
indicate  where  penetrations  will  be  made  for 
electrical,  mechanical,  plumbing  and  communication 
conduits,  pipes  and  systems,  and  shall  also  indicate 
the  materials  and  methods  for  maintaining  the 
required  structural  integrity,  fireresistance  rating  and 
firestopping 

780  CMR  704.0  FIRE  TESTS 
704.1  General:  Building  elements  and  assemblies 
including  loadbearing  and  nonloadbearing  walls  and 
partitions,  columns,  girders,  beams,  slabs  and  floors 
and  roof  assemblies,  shall  provide  the  minimum 
fireresistance  ratings  specified  in  Table  602  for  the 
type  of  construction  unless  otherwise  required  by  the 
provisions  of  780  CMR. 

704.1.1        Fireresistance        ratings:        The 

fireresistance  ratings  of  building  assemblies  and 
structural  elements  shall  be  determined  in 
accordance  with  the  test  procedures  set  forth  in 
ASTM  El  19  listed  in  Appendix  A,  specific 
methods  as  provided  for  herein,  or  shall  be 
determined  in  accordance  with  an  approved 
analytical  method.  Where  an  approved 
analytical  method  is  utilized  to  establish  the 
fireresistance  rating  of  a  structural  element  or 
building  assembly,  the  calculations  shall  be 
based  upon  the  fire  exposure  and  acceptance 
criteria  specified  in  ASTM  E  119  listed  in 
Appendix  A. 

Exception:  In  determining  the  fireresistance 
rating     of     exterior     loadbearing     walls. 


124 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


compliance  with  the  ASTM  El  19  criteria  for 
unexposed  surface  temperature  rise  and 
ignition  of  cotton  waste  due  to  passage  of 
flame  or  hot  gases,  is  required  only  for  a 
period  of  time  corresponding  to  the  required 
fireresistance  rating  of  an  exterior 
nonloadbearing  wall  with  the  same  fire 
separation  distance,  and  in  a  building  of  the 
same  use  group.  Where  the  fireresistance 
rating  determined  in  accordance  with  this 
exception  exceeds  the  fireresistance  rating 
determined  in  accordance  with  ASTM  El  19 
listed  in  Appendix  A,  the  fire  exposure  time 
period,  water  pressure  and  application 
duration  criteria  for  the  hose  stream  test  of 
ASTM  El  19  listed  in  Appendix  A,  shall  be 
based  upon  the  fireresistance  rating 
determined  in  accordance  with  this 
exception. 

704.2  Alternative  protection  Where 
documentation  is  submitted  to  the  code  official  and 
approved,  fireresistive  coverings  or  insulating 
enclosing  materials  are  not  required  for  structural 
framing  elements.  Such  documentation  shall  show 
that  the  structural  integrity  of  structural  framing 
elements  will  not  be  reduced  below  a  safe  level  by  a 
fire  within  the  building  or  in  an  adjacent  building 
having  a  severity  corresponding  to  the  fireresistance 
rating  required  for  the  elements  through  the 
installation  of  heat  shields,  separations  or  other 
approved  means  of  protection. 

704.3  Opening  protectives:  Opening  protectives 
shall  include  the  fire  door,  fire  shutter,  fire  M'indow 
or  fire  damper  and  all  required  hardware,  anchorage, 
frames  and  sills  necessary  for  the  assembly 

704.4  Combustibility  tests:  Where  the  behavior  of 
materials  under  exposure  to  fire  is  specified  in 
780  CMR  the  characteristics  of  materials  shall  be 
determined  by  the  tests  and  criteria  set  forth  in 
780  CMR  704.4.1.  704.4.1.1  and  704.4.1.2. 

704.4.1  Tests:  The  tests  indicated  in  780  CMR 
704.4.1.1  and  704.4.1.2  shall  serve  as  criteria  for 
acceptance  of  building  materials  as  set  forth  in 
780  CMR  603.0,  604.0  and  605  governing  the 
combustibility  of  building  materials  in  Types  1 . 
2,  3  and  4  construction.  The  term 
"noncombustible"  does  not  apply  to  the  flame 
spread  characteristics  of  interior  finish  or  trim 
materials.  A  material  shall  not  be  classified  as  a 
noncombustible  building  construction  material 
which  is  subject  to  an  increase  in  the 
combustible  or  flame  spread  rating  beyond  the 
limitations  herein  established  through  the  effects 
of  age,  moisture  or  other  atmospheric  conditions. 

704.4.1.1  Elementary  materials  Materials 
which  are  intended  to  be  classified  as 
noncombustible  shall  be  tested  in  accordance 


with  ASTM  E136  listed  in  Appendix  A. 
Such  materials  shall  be  acceptable  as 
noncombustible  materials  when  at  least  three 
of  four  specimens  tested  conform  to  all  of 
the  following  criteria: 

1 .  The  recorded  temperature  of  the 
surface  and  interior  thermocouples  shall 
not  at  any  time  during  the  test  rise  more 
than  54°F  (30°C)  above  the  furnace 
temperature  at  the  beginning  of  the  test. 

2.  There  shall  not  be  flaming  from  the 
specimen  after  the  first  30  seconds. 

3  If  the  weight  loss  of  the  specimen 
during  testing  exceeds  50%,  the  recorded 
temperature  of  the  surface  and  interior 
thermocouples  shall  not  at  any  time 
during  the  test  rise  above  the  furnace  air 
temperature  at  the  beginning  of  the  test. 
and  there  shall  not  be  flaming  of  the 
specimen. 

"704.4.1.2  Composite  materials  Materials 
having  a  structural  base  of  noncombustible 
material  as  defined  in  780  CMR  704.4.1.1. 
with  a  surfacing  not  more  than  Vs  inch  thick 
which  has  a  flame  spread  rating  not  greater 
than  50  when  tested  in  accordance  with 
ASTM  E84  listed  in.  Appendix  A  shall  be 
acceptable  as  noncombustible  materials 

780  CMR  705.0  EXTERIOR  WALLS 
705.1  General:  All  exterior  walls  shall  comply  with 
the  applicable  provisions  of  780  CMR  and  with  the 
fireresistance  rating  requirements  of  780  CMR  705.0 
and  780  CMR  602.0. 

Exception:  The  provisions  of  780  CMR  705.2 
and  705.3  shall  not  apply  to  exterior  walls  which 
face  buildings  on  the  same  lot  where  the 
buildings  are  such  that,  if  combined  into  one 
structure,  the  resulting  building  will  otherwise 
comply  with  the  height  and  area  limitations  of 
780  CMR  503.0  (see  780  CMR  503.1.3) 

705.1.1  Omission    of    exterior    walls:    The 

provisions  of  780  CMR  shall  not  be  deemed  to 
prohibit  the  omission  of  exterior  walls  for  all  or 
part  of  a  story  where  the  provisions  of  780  CMR 
705.2  do  not  require  a  nonloadbearing  exterior 
wall  to  provide  a  fireresistance  rating,  and  where 
the  provisions  of  780  CMR  705.3  and  705.4  do 
not  limit  the  maximum  percentage  of 
unprotected  openings.  Except  as  otherwise 
specifically  permitted  in  780  CMR  715.5.  the 
piers,  columns  and  other  structural  elements 
within  the  open  portion  shall  be  constructed  with 
the  fireresistance  rating  required  for  exterior 
loadbearing  walls  in  Table  602. 

705.1.2  Combustible  exterior  wall  finish  and 

trim  In  addition  to  the  requirements  of 
780  CMR  705.0,  combustible  materials  installed 
as  exterior  wall  finish,  half-timbering,  balconies 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


125 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  similar  appendages,  bay  and  oriel  windows 
and  light-transmitting  plastic  panels,  shall  meet 
the  applicable  requirements  of  780  CMR  1406.0, 
2604.0,  2605.0  and  2606.0. 

705.2  Fireresistance  ratings:  The  fireresistance 
rating  of  exterior  walls  shall  comply  with  Table 
705.2.  Loadbearing  exterior  walls  shall  also  comply 
with  the  fireresistance  rating  requirements  of 
780  CMR  602.0.  The  fireresistance  rating  of 
exterior  walls  with  a  fire  separation  distance  of 
greater  than  five  feet  (1524  mm)  shall  be  rated  for 
exposure  to  fire  from  the  inside.  The  fireresistance 
rating  of  exterior  walls  with  a  fire  separation 
distance  of  five  feet  (1524  mm)  or  less  shall  be  rated 
for  exposure  to  fire  from  both  sides. 

Table  705.2 

EXTERIOR  WALL  FIRERESISTANCE 

RATINGS 


a 
Use  Group 

Fire  Separation 
distance  (feet) 

H-2 

F-l.H-3. 
M,  S-l 

R-2 

R-3 

A,  B.  E,  F-2, 

H-4.I.R-1. 

S-2 

0to5 

Greater  than  5  to  10 

Greater  than  10  to  15 
Greater  Shan  15to  30 

Greater  than  30 

4 

3 

2 

1 

0 

2 

1 

0 

0 

1 
1 

0 

'  0 

0 

1 
0 

0 

0 

0 

1 

0 
0 

0 

Note  a.     For  requirements  for  Use  Group  H-l,  see 
780  CMR  705.2.1. 

Note  b.  Fireresistance  ratings  are  expressed  in  hours 
Notec.  1  foot -304.8  mm. 

705.2.1  Use  Group  H-l:  Buildings  and 
structures  with  an  occupancy  in  Use  Group  H- 1 
shall  be  located  in  accordance  with  the 
requirements  for  the  storage  of  explosives  in  the 
fire  prevention  code  listed  in  Appendix  A.  The 
allowable  quantities  of  Use  Group  H-l  materials 
shall  be  based  on  the  TNT  equivalency  of  the 
materials  The  exterior  finish  surface  of  all 
exterior  walls  in  an  occupancy  in  Use  Group  H- 1 
shall  be  of  approved  noncombustible  materials 


or  fireretardant-treated  wood  complying  with 
780  CMR  23 10.0  for  exterior  installation 

705.2.2  Wall  support:  The  wall  shall  extend  to 
the  height  required  by  780  CMR  705.6,  and  shall 
be  supported  such  that  the  wall  will  remain  in 
place  for  the  duration  of  time  indicated  by  the 
required  fireresistance  rating. 

705.2.3  Automatic     fire     suppression:     In 

buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1.  the  required  fireresistance 
rating  of  nonloadbearing  exterior  walls  shall  be 
reduced  by  one  hour,  except  that  where  they?™? 
separation  distance  is  five  feet  (1524  mm)  or 
less,  the  fireresistance  rating  shall  not  be  reduced 
to  less  than  one  hour  This  reduction  shall  not 
apply  to  occupancies  in  Use  Group  H. 

705.2.4  Unexposed     surface    temperature 

Where  protected  openings  are  not  limited  by 
Table  705.3,  the  limitation  on  the  rise  of 
temperature  on  the  unexposed  surface  of  exterior 
walls  as  required  by  ASTM  El  19  listed  in 
Appendix  A  shall  not  apply.  Where  protected 
openings  are  limited  by  Table  705.3,  the 
limitation  on  the  rise  of  temperature  on  the 
unexposed  surface  of  exterior  walls  as  required 
by  ASTM  El  19  listed  in  Appendix  A  shall  not 
apply  provided  that  a  correction  is  made  for 
radiation  from  the  unexposed  exterior  wall 
surface  in  accordance  with  the  following 
formula: 

A,  -A  +(AfxFJ     where 

Ae  =  Equivalent  area  of  protected  openings 
A  =  Actual  area  of  protected  openings 
A  f  =  Area  of  exterior  wall  surface  in  the  story 
under  consideration  exclusive  of  openings,  on 
which  the  temperature  limitations  of  ASTM 
El  19  listed  in  Appendix  A  for  walls  is  exceeded 
¥eo  =  An  "equivalent  opening  factor" 
derived  from  Figure  705.2.4  based  on  the 
average  temperature  of  the  unexposed  wall 
surface  and  the  fireresistance  rating  of  the  wall 
required  by  780  CMR  705.2. 


126 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 

Figure  705.2.4 
EQUIVALENT  OPENING  FACTOR 


*00  600  800  t.KSO         IWO        1.-S0O        t.SOO 

Average  temperature  of  unexposed  surface  (degrees  F) 


705.3  Openings:  The  maximum  area  of  unprotected 
or  protected  openings  permitted  in  an  exterior  wall 
in  any  story  shall  not  exceed  the  values  set  forth  in 
Table  705.3.  Where  both  unprotected  and  protected 
openings  are  located  in  the  exterior  wall  in  any 
story,  the  total  area  of  the  openings  shall  comply 
with  the  following  formula: 


<:  1.0 


a 


where: 

A    =     Actual  area  of  protected  openings,  or  the 
equivalent  area  of  protected  openings  Ae  (see 
780  CMR  705.2.4). 
a    =     Allowable  area  of  protected  openings. 

A„  =    Actual  area  of  unprotected  openings. 
<2tf   =    Allowable  area  of  unprotected  openings. 

Table  705.3 

MAXIMUM  AREA  OF  EXTERIOR  WALL 

OPENINGS3 


Classifi- 

Fire separation  distance  (feet) 

cation  of 
opening 

Oto 
3 

>3 

to  5 

>5  to 

iod 

>  10  to 

15C'd 

>  15 

to20C 

>20 

to25C 

>25 

to  30° 

>30 

Un- 
protected 

NP 

NPb 

10% 

15% 

25% 

45% 

70% 

No 
limit 

Protected 

NP 

15% 

25% 

45% 

75% 

No 
'  imit 

No 
Limit 

No 
Limit 

Note  a.   Values  given  are  percentages  of  the  area  of  the 

exterior  wall.    This  table  assumes  that  the  openings  are 

reasonably  uniformly  distributed.     Where  openings  are 

not  reasonably  uniformly  distributed,  the  portion  of  the 

wall  utilized  to  calculate  compliance  with  table  705.3 

shall  be  approved. 

Note    b.      For  occupancies    in   Use   Group   R-3,   the 

maximum    percentage    of    unprotected    exterior    wall 

openings  shall  be  5%. 

Note   c.      The  area  of  openings   in   an  open  parking 

structure  with  a  fire  separation  distance  of  greater  than 

ten  feet  shall  not  be  limited. 

Note  d.     For  occupancies  in  Use  Group  H-2  or  H-3, 

unprotected  openings  shall  not  be  permitted  for  openings 

with  a  fire  separation  distance  of  15  feet  or  less. 

Note  e.  One  foot  =  304.8  mm. 

705.3.1  Automatic     fire     suppression:     In 

buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2. 1,  the  maximum  allowable  area 
of  unprotected  openings  in  all  occupancies  other 
than  Use  Groups  H-l,  H-2  and  H-3  shall  be  the 
same  as  the  tabulated  limitations  for  protected 
openings. 

705.3.2  First  story:  In  all  occupancies  other 
than  Use  Group  H,  unlimited  unprotected 
openings  are  permitted  in  the  first  story  of 
exterior  walls  facing  a  street  which  have  a  fire 
separation  distance  of  greater  than  15  feet  (4572 
mm). 


NP  (Not  permitted) 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


127 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


705.4  Vertical  separation  of  openings:  Openings  in 
exterior  walls  in  adjacent  stories  shall  be  separated 
vertically  to  protect  against  fire  spread  on  the 
exterior  of  the  buildings  where  the  openings  are 
within  five  feet  (1524  mm)  of  each  other 
horizontally  and  the  opening  in  the  lower  story  is  not 
a  protected  opening  in  accordance  with  780  CMR 
706.0.  Such  openings  shall  be  separated  vertically 
at  least  three  feet  (914  mm)  by  spandrel  girders, 
exterior  walls  or  other  similar  assemblies  which 
have  a  fireresistance  rating  of  at  least  one  hour  or  by 
flame  barriers  which  extend  horizontally  at  least  30 
inches  (762  mm)  beyond  the  exterior  wall.  Flame 
barriers  shall  also  have  a  fireresistance  rating  of  at 
least  one  hour.  The  unexposed  surface  temperature 
limitations  specified  in  ASTM  El  19  listed  in 
Appendix  A  shall  not  apply  to  the  flame  barriers  or 
vertical  separation  unless  otherwise  required  by  the 
provisions  of  7S0  CMR. 

Exceptions: 

1 .  780  CMR  705.4  shall  not  apply  to  buildings 
that  are  three  stories  or  less  in  height. 

2.  780  CMR  705.4  shall  not  apply  to  buildings 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1. 

705.5  Vertical  exposure:  Approved  protectives 
shall  be  provided  in  every  opening  that  is  less  than 
15  feet  (4572  mm)  vertically  above  the  roof  of  an 
adjoining  building  or  adjacent  structure  which  is 
within  a  horizontal  fire  separation  distance  of  1 5 
feet  (4572  mm)  of  the  wall  in  which  the  opening  is 
located,  unless  such  roof  construction  affords  a 
fireresistance  rating  of  not  less  than  one  hour. 

705.6  Continuity  of  exterior  walls:  Exterior  walls 
required  to  be  fireresistance  rated  by  780  CMR 
705.2  because  of  fire  separation  distance,  shall  be 
continuous  from  the  foundation  to  not  less  than  30 
inches  (762  mm)  above  the  roof  surface. 

Exceptions: 

1.  Where  the  roof  deck  or  sheathing  is 
constructed  of  approved  noncombustible 
materials  cr  of  fireretardant-treated  wood  or  of 
Va-inch  Type  X  gypsum  board  supported  directly 
beneath  the  underside  of  the  roof  sheathing  or 
deck,  using  minimum  two-inch  ledgers  attached 
to  the  sides  of  the  roof  framing  members  for  a 
minimum  distance  of  four  feet  (1219  mm)  from 
the  exterior  wall,  and  where  the  roof  covering 
has  a  minimum  of  a  Class  C  rating,  the  exterior 
wall  shall  be  permitted  to  stop  at  the  underside 
of  the  roof  deck  or  sheathing. 

2.  Exterior  walls  in  buildings  not  exceeding 
1,000  square  feet  (93  m3)  in  area. 

3.  Exterior  walls  of  occupancies  in  Use  Group 
R-3. 

4.  Exterior  walls  of  a  building  where  the  roof 
has  an  angle  of  more  than  20  degrees  (0.35  rad) 
with  the  horizontal. 


780  CMR  706.0  EXTERIOR  OPENING 
PROTECTIVES 

706.1  Where  required:  Exterior  opening 
protectives  shall  be  provided  in  all  exterior  wall 
openings  that  are  required  to  be  protected  by 
780  CMR  705.0. 

706.2  Automatic  protection:  Approved  fire 
protective  assemblies  shall  be  fixed,  self-closing  or 
equipped  with  approved  automatic-closing  devices 
and  shall  conform  to  the  requirements  of  780  CMR 

706.0  and  780  CMR  702.0,  716.0,717.0,  718.0  and 
719.0. 

Exception:  Fire  protective  assemblies  are  not 
required  where  outside  automatic  sprinklers  are 
installed  for  the  protection  of  the  exterior 
openings.  The  sprinklers  shall  be  installed  in 
accordance  with  NFiPA  13  listed  in  Appendix  A, 
and  shall  have  an  automatic  water  supply  and  be 
provided  with  a  fire  department  connection. 

706.3  Fireresistance  rating:  Exterior  openings 
required  to  be  protected  by  780  CMR  705.3,  when 
located  in  a  wall  required  by  780  CMR  705.2  to 
have  a  fireresistance  rating  of  greater  than  one  hour, 
shall  be  protected  with  an  assembly  having  afire 
protection  rating  of  not  less  than  V/z  hours.  Exterior 
openings  required  to  be  protected  by  780  CMR 
705.3,  when  located  in  a  wall  required  by  780  CMR 
705.2  to  have  a  fireresistance  rating  of  one  hour, 
shall  be  protected  with  an  assembly  having  afire 
protection  rating  of  not  less  than  2A  hour.  Exterior 
openings  required  to  be  protected  by  780  CMR 

705.4  or  705.5  shall  be  protected  with  an  assembly 
having  a  fire  protection  rating  of  not  less  than  3A 
hour. 

706.4  Unprotected  openings:  Where  protected 
openings  are  not  required  by  780  CMR  705.0, 
windows  and  doors  shall  be  constructed  of  any 
approved  materials.  Glazing  shall  conform  to  the 
requirements  of  780  CMR  14,  24  and  26. 

780  CMR  707.0  FIRE  WALLS 
AND  PARTY  WALLS 

707.1  General:  Walls  shall  have  sufficient  rtructural 
stability  under  fire  conditions  to  allow  collapse  of 
construction  on  either  side  without  collapse  of  the 
wall,  and  shall  be  constructed  of  any  approved 
noncombustible  materials  that  provide  the  required 
strength  and  fireresistance  rating  specified  in  Table 
602  for  the  type  of  construction,  but  not  less  than  the 
fireresistance  rating  of  the  use  group  specified  in 
Table  707.1.  Strength  and  stability  shall  comply 
with  the  provisions  of  780  CMR  14  and  16. 


128 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


Table  707.1 

FIRE  AND  PARTY  WALL 

FIRERESISTANCE  RATINGS 


Use  Group 

Minimum  Fireresistance 
rating  (hours) 

A-3,  A-4,  A-5,  B,  E,  F-2, 
H-4, 1-1,1-2,  R.S-2 

2 

A-1,A-2,F-1,H-3,I-3,M,                             3 
S-l 

H-2 

4 

Note  a.  For  requirements  for  Use  Group  H-l,  see  780 
CMR  707. 1.1. 

707.1.1  Use  Group  H-l:  Occupancies  in  Use 
Group  H-l  shall  not  be  located  in  a  building  that: 
is  more  than  one  story  in  height,  has  a  basement, 
or  is  attached  to  another  building.  An  occupancy 
in  any  use  group  other  than  H-l  shall  not  be 
located  in  a  building  with  an  occupancy  in  Use 
Group  H-l. 

Exception:  The  story  above  grade,  where 
provided  with  barricaded  construction  in 
accordance  with  the  fire  prevention  code 
listed  in  Appendix  A,  shall  not  be  considered 
a  basement. 

707.2  Cutting  wails:  A  wall  that  is  eight  inches  or 
less  in  thickness  shall  not  be  cut  for  chases  or 
socketed  for  insertion  of  structural  members 
subsequent  to  erection  (see  780  CMR  2109.1.1). 

707.3  Hollow  walls:  The  wall  shall  not  be  less  than 
the  minimum  thickness  specified  in  ACI  530/ASCE 
5/TMS  402  listed  in  Appendix  A. 

707.4  Combustible  insulation:  The  code  official 
shall  permit  the  application  of  cork,  fiberboard  or 
other  combustible  insulation  where  laid  up  without 
intervening  air  spaces  and  attached  directly  to  the 
face  of  the  wall,  and  where  protected  on  the  exposed 
surface  as  provided  for  in  780  CMR  722.0  and 
2309.1. 

707.5  Continuity  of  walls:  In  all  buildings  or 
structures,  walls  shall  be  continuous  from  foundation 
to  two  feet  eight  inches  (813  mm)  above  the  roof 
surface,  except  as  provided  for  in  780  CMR  707.5. 1 
through  707.5.3.  Fire  walls  shall  be  made  smoke 
tight  at  their  junction  with  exterior  walls.  In  exterior 
wall  construction  employing  studs,  the  wall  shall 
extend  through  the  stud  space  to  the  exterior 
sheathing. 

707.5.1  Noncombustible  roofs:  The  wall  is 
permitted  to  terminate  at  the  underside  of  the 
roof  deck  where  the  roof  is  of  approved 
noncombustible  construction  and  is  properly 
firestopped  at  the  wall. 

707.5.2  Combustible  roofs:  The  wall  is 
permitted  to  terminate  at  the  underside  of  the 
roof  deck  in  Types  3,  4  and  5  construction  where 
all  of  the  following  conditions  are  met: 


1.  The  wall  is  properly  firestopped  at  the 
deck. 

2.  The  roof  sheathing  or  deck  is  constructed 
of  approved  noncombustible  materials  or  of 
fireretardant-treated  wood,  for  a  distance  of 
four  feet  (1219  mm)  on  both  sides  of  the 
wall,  or  such  roof  sheathing  or  deck  is 
constructed  with  5/s-inch  Type  X  gypsum 
board  supported  directly  beneath  the 
underside  of  the  roof  sheathing  or  deck, 
using  minimum  two-inch  ledgers  attached  to 
the  sides  of  the  roof  framing  members,  for  a 
minimum  distance  of  four  feet  (1219  mm)  on 
both  sides  of  ihe  fire  wall. 

3.  Combustible  material  does  not  extend 
through  the  wall. 

4.  The  roof  covering  has  a  minimum  of  a 
Class  C  rating. 

707.5.3  Noncombustible  frame:  The  wall  shall 
not  be  supported  on  the  structural  frame  in 
buildings  of  noncombustible  construction  unless 
such  supporting  frame  has  a  fireresistance  rating 
at  least  equal  to  that  required  for  the  wall. 

707.6  Offset  fire  walls:  Where  fire  walls  are  offset 
at  intermediate  floor  levels  in  protected  skeleton- 
frame  construction,  the  offset  floor  construction  and 
the  intermediate  wall  supports  shall  be  constructed 
of  approved  noncombustible  materials  with  a 
fireresistance  rating  not  less  than  that  required  for 
the  fire  wall. 

707.7  Penetrations:  Penetrations  through  fire  walls 
shall  meet  the  limitations  specified  in  7S0  CMR 
707.7.1  through  707.7.4. 

707.7.1  Combustible  framing:  In  addition  to 
the  provisions  of  780  CMR  2305.6,  adjacent 
combustible  members  entering  into  a  masonry 
fire  wall  from  opposite  sides  shall  not  have  less 
than  a  four-inch  (102  mm)  distance  between 
embedded  ends.  Where  combustible  members 
frame  into  hollow  walls  or  walls  of  hollow  units, 
all  hollow  spaces  shall  be  solidly  filled  for  the 
full  thickness  of  the  wall  and  for  a  distance  not 
less  than  four  inches  (102  mm)  above,  below  and 
between  the  structural  members,  with 
noncombustible  materials  approved  for 
firestopping  in  accordance  with  780  CMR  720.0. 

707.7.2  Noncombustible  penetrations:  Cables 
and  wires  without  combustible  jackets  or 
insulation,  and  noncombustible  pipes,  tubes, 
conduits  and  vents  which  penetrate  afire  wall 
shall  be  tested  in  accordance  with  ASTM  El  19 
listed  in  Appendix  A  as  part  of  a  rated  assembly, 
or  shall  be  protected  by  an  approved  through- 
penetration  protection  system  that  has  been 
tested  in  accordance  with  ASTM  E814  listed  in 
Appendix  A,  or  the  annular  space  around  the 
penetrating  item  shall  be  protected  in  accordance 
with  780  CMR  707.8. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


129 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


The  through-penetration  protection  system 
shall  be  tested  in  accordance  with  ASTM  E814 
listed  in  Appendix  A,  with  a  minimum  positive 
pressure  differential  of  0.01  inch  of  water 
column  (2.5  P)  and  shall  have  an  "F"  rating  of 
not  less  than  the  required  rating  of  the  wall 
penetrated. 

707.7.3  Combustible  penetrations:  Cables  and 
wires  with  combustible  jackets  or  insulation,  and 
combustible  pipes,  tubes  and  conduits  which 
penetrate  afire  wall  shall  be  tested  in  accordance 
with  ASTM  El  19  listed  in  Appendix  A  as  part  of 
a  fireresistance  rated  assembly  or  shall  be 
protected  by  an,  approved  through-penetration 
protection  system  that  has  been  tested  in 
accordance  with  ASTM  E814  listed  in 
Appendix  A. 

The  through-penetration  protection  system 
shall  be  tested  in  accordance  with  ASTM  E814 
listed  in  Appendix  A,  with  a  minimum  positive 
pressure  differential  of  0.01  inch  of  water 
column  (2.5  P)  and  shall  have  an  "F"  rating  of 
not  less  than  the  required  rating  of  the  assembly 
penetrated. 

707.7.4  Electrical  outlet  boxes:  Openings  for 
steel  electrical  outlet  boxes  that  do  not  exceed  1 6 
square  inches  (10323  mm2)  in  area  are  permitted 
provided  that  the  area  of  such  openings  does  not 
exceed  100  square  inches  (64516  mm2)  for  any 
100  square  feet  (9.3  m2)  of  wall  area.  Outlet 
boxes  on  opposite  sides  of  the  wall  shall  be 
separated  by  a  horizontal  distance  of  not  less 
than  24  inches  (610  mm). 

Exception:  Openings  for  electrical  outlet 
boxes  of  any  material  are  permitted  provided 
that  such  boxes  are  tested  for  use  in 
fireresistance  rated  assemblies  and  installed 
in  accordance  with  the  tested  assembly. 

707.8  Annular  space  protection:  Where  permitted 
by  780  CMR  707.7.2  for  noncombustible  penetrating 
items,  the  annular  space  between  the  penetrating 
item  and  the  fireresistance  rated  assembly  being 
penetrated  shall  be  protected  as  specified  in 
780  CMR  707.8. 1  and  707.8.2. 

707.8.1  Material:  The  material  used  to  fill  the 
annular  space  shall  comply  with  780  CMR 
707.8.1.1  or  707.8. 1.2. 

707.8.1.1  Concrete  or  masonry  assemblies: 

Penetrations  of  concrete  or  masonry 
assemblies  by  a  maximum  six-inch  nominal 
diameter  copper,  iron  or  steel  pipe,  tube, 
conduit  or  wires  and  cables  with  steel  jackets 
shall  be  permitted  provided  that  the 
maximum  opening  size  is  144  square  inches 
(0.09  m2)  and  the  penetration  is  protected 
with  concrete,  grout  or  mortar  for  the  full 
thickness  of  the  assembly  or  the  thickness 
required  to  provide  a  fireresistance  rating 


equivalent  to  the  required  fireresistance 
rating  of  the  assembly  penetrated. 
707.8.1.2  All  assemblies:  In  all  assemblies 
the  material  shall  prevent  the  passage  of 
flame  and  hot  gases  sufficient  to  ignite 
cotton  waste  when  subjected  to  the  time- 
temperature  fire  conditions  of  ASTM  El  19 
listed  in  Appendix  A,  under  a  minimum 
positive  pressure  differential  of  0.01  inch  of 
water  column  (2.5  P)  at  the  location  of  the 
penetration  for  the  time  period  equivalent  to 
the  required  fireresistance  rating  of  the 
assembly  penetrated. 

707.8.2  Sleeves:  Where  sleeves  are  installed,  the 
sleeves  shall  be  noncombustible  and  shall  be 
securely  fastened  to  the  assembly  penetrated. 
All  space  between  the  item  contained  in  the 
sleeve  and  the  sleeve  itself,  and  any  space 
between  the  sleeve  and  the  assembly  penetrated, 
shall  be  filled  with  a  material  that  complies  with 
780  CMR  707.8.1. 

780  CMR  708.0  FERE  WALL  OPENINGS 

708.1  General:  Openings  in  fire  walls  shall  not 
exceed  the  limitations  in  size  and  area  herein 
prescribed. 

708.2  Size  of  opening:  Each  opening  through  afire 
wall  shall  not  exceed  120  square  feet  (11.16  m2). 
The  aggregate  width  of  all  openings  at  any  floor 
level  shall  not  exceed  25%  of  the  length  of  the  wall. 

Exception:  Openings  shall  not  be  limited  to  120 
square  feet  (11.16  m2)  where  both  buildings  are 
equipped  throughout  with  an  automatic  sprinkler 
system  installed  in  accordance  with780  CMR  9. 

708.2.1  First  story:  Where  the  entire  first-story 
floor  areas  on  both  sides  of  a  fire  wall  are 
equipped  throughout  with  an  approved 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1,  the 
maximum  allowable  size  of  openings  on  the  first 
story  of  the  building  shall  not  exceed  240  square 
feet  (22.32  m2)  with  a  minimum  distance  of  three 
feet  (914  mm)  between  adjacent  openings. 

708.3  Opening  protectives:  All  opening  protectives 
in  fire  walls  shall  comply  with  the  provisions  of 
780  CMR  704.0  and  shall  have  the  minimum  fire 
protection  rating  as  set  forth  in  780  CMR  716.0. 

780  CMR  709.0  FERE  SEPARATION 
ASSEMBLIES 

709.1  General:  Fire  separation  assemblies  installed 
for  purposes  of  the  enclosure  of  exits,  floor 
openings,  shafts,  areas  of  refuge  and  for  subdividing 
purposes  shall  be  constructed  of  approved  materials 
consistent  with  the  limitations  for  the  building  type 
of  construction  and  shall  have  not  less  than  the 
fireresistance  rating  prescribed  by  Table  602. 


130 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


709.2  Fire  area:  Afire  separation  assembly  which 
separates  adjacent  fire  areas  shall  have  a 
fireresistance  rating  of  not  less  than  the 
fireresistance  rating  required  by  Table  3 13. 1.2  based 
on  the  use  group  of  the  fire  areas  which  are 
separated. 

709.3  Openings:  Openings  located  in  a  fire 
separation  assembly  shall  be  limited  to  a  maximum 
aggregate  width  of  25%  of  the  length  of  the  wall, 
and  the  maximum  area  of  any  single  opening  shall 
not  exceed  120  square  feet  (1 1  m2).  Openings  in  exit 
enclosures,  other  than  unexposed  exterior  openings, 
shall  be  limited  to  those  necessary  for  exit  access  to 
the  enclosure  from  normally  occupied  spaces  and  for 
egress  from  the  enclosure. 

Exception:  Openings  shall  not  be  limited  to  120 
square  feet  (11  m:)  where  adjoining  fire  areas 
are  equipped  throughout  with  an  automatic 
sprinkler  system  installed  in  accordance  with 
780  CMR  9. 

709.3.1  Protectives:  .All  opening  protectives  in 
fire  separation  assemblies  shall  comply  with  the 
provisions  of  780  CMR  704.0  and  shall  have  the 
minimum  fire  protection  rating  as  set  forth  in 
780  CMR  716.0. 

709.4  Continuity:  All  vertical  fire  separation 
assemblies  shall  extend  from  the  top  of  the 
fireresistance  rated  floor/ceiling  assembly  below  to 
the  underside  of  the  floor  or  roof  slab  or  deck  above 
and  shall  be  securely  attached  thereto.  These  walls 
shall  be  continuous  through  all  concealed  spaces 
such  as  the  space  above  a  suspended  ceiling.  The 
supporting  construction  shall  be  protected  to  afford 
the  required  fireresistance  rating  of  the  fire 
separation  assembly  supported.  All  hollow  vertical 
spaces  shall  be  firestopped  at  every  floor  level  as 
required  in  780  CMR  720.0. 

709.5  Exterior  walls:  Except  as  provided  for  in 
780  CMR  1014.11.1  and  1014.12.2,  where  exterior 
walls  serve  as  a  part  of  a  required  fireresistance  rated 
enclosure,  such  walls  shall  comply  with  the 
requirements  of  780  CMR  705.0  for  exterior  walls 
and  the  fireresistance  rated  enclosure  requirements 
shall  not  apply. 

709.6  Penetrations:  Penetrations  through 
fireresistance  rated  wall  assemblies  shall  meet  the 
limitations  specified  in  780  CMR  709.6.1  through 
709.6.5.  Penetrations  through  floor/ceiling  and 
roof/ceiling  assemblies  shall  comply  with  780  CMR 
713  0.  Penetrations  of  an  exit  enclosure  shall  also 
comply  with  780  CMR  1014.11.2. 

709.6.1  Noncombustible  penetrations:  Cables 
and  wires  without  combustible  jackets  or 
insulation,  and  noncombustible  pipes,  tubes, 
conduits  and  vents  which  penetrate  an  assembly 
shall  be  tested  in  accordance  with  ASTM  El  19 


listed  in  Appendix  A  as  part  of  a  rated  assembly, 
or  shall  be  protected  by  an  approved  through- 
penetration  protection  system  that  has  been 
tested  in  accordance  with  ASST.  E814  listed  in 
Appendix  A,  or  the  annular  space  around  the 
penetrating  item  shall  be  protected  in  accordance 
with  780  CMR  709.7. 

The  through-penetration  protection  system 
shall  be  tested  in  accordance  with  ASTM  E814, 
with  a  minimum  positive  pressure  differential  of 
0.01  inch  of  water  column  (2.5  P)  and  shall  have 
an  "F"  rating  of  not  less  than  the  required  rating 
of  the  assembly  penetrated. 

709.6.2  Combustible  penetrations:  Cables  and 
wires  with  combustible  jackets  or  insulation,  and 
combustible  pipes,  tubes,  conduits  and  vents 
which  penetrate  an  assembly  shall  be  tested  in 
accordance  with  ASTM  El  19  listed  in  Appendix 
A  as  part  of  a  fireresistance  rated  assembly  or 
shall  be  protected  by  an  approved  through- 
penetration  protection  system  that  has  been 
tested  in  accordance  with  ASTM  E814  listed  in 
Appendix  A. 

The  through-penetration  protection  system 
shall  be  tested  in  accordance  with  ASTM  E814 
with  a  minimum  positive  pressure  differential  of 
0.01  inch  of  water  column  (2.5  P)  and  shall  have 
an  "F"  rating  of  not  less  than  the  required  rating 
of  the  assembly  penetrated. 

709.6.3  Electrical  outlet  boxes:  Openings  for 
steel  electrical  outlet  boxes  that  do  not  exceed  16 
square  inches  (10323  mm2)  in  area  are  permitted 
provided  that  the  area  of  such  openings  does  not 
exceed  100  square  inches  (64516  mm2)  for  any 
100  square  feet  (9.3  rrr)  of  enclosure  wall  area. 
Outlet  boxes  on  opposite  sides  of  the  assembly 
shall  be  separated  by  a  horizontal  distance  of  not 
less  than  24  inches  (610  mm). 

Exception:  Openings  for  electrical  outlet 
boxes  of  any  material  are  permitted  provided 
that  such  boxes  are  tested  for  installation  in 
fireresistance  rated  assemblies  and  installed 
in  accordance  with  the  tested  assembly. 

709.6.4  Ducts:  Ducts  that  penetrate  an  assembly 
shall  be  provided  with  approved  fire  dampers 
that  comply  with  780  CMR  717.0. 

Exception:  Fire  dampers  are  not  required: 

1 .  In  steel  exhaust  air  subducts  extending  at 
least  22  inches  (559  mm)  vertically  in  an 
exhaust  shaft  and  where  there  is  a  continuous 
airflow  upward  to  the  outside. 

2.  In  penetrations  tested  in  accordance  with 
ASTM  El  19  listed  in  Appendix  A  as  a  part 
of  the  fireresistance  rated  assembly. 

3  In  penetrations  of  walls  with  a  required 
one-hour  fireresistance  rating  or  less  by  a 
ducted  HVAC  system  in  areas  of  other  than 
Use  Group  H  where  the  building  is  equipped 
throughout    with    an   automatic   sprinkler 


llim    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


131 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


system    in    accordance    with    780    CMR 

906.2.1. 

4.    In  garage  exhaust  or  supply  shafts  which 

are  separated  from  all  other  building  shafts 

by  not  less  than  a  two-hour  fireresistance 

rated  fire  separation  assembly. 

709.6.5     Single     membrane     penetrations: 

Openings  to  accommodate  noncombustible 
conduits,  pipes  and  tubes  through  a  single 
membrane  that  is  an  integral  component  of  a 
fireresistance  rated  wall  assembly  shall  be 
permitted  provided  that  the  aggregate  area  of  all 
such  openings  does  not  exceed  100  square 
inches  (64516  mm2)  in  any  100  square  feet  (9.3 
m2)  of  wall  area  and  the  openings  zrtfirestopped 
with  approved  noncombustible  materials. 

709.7  Annular  space  protection:  Where  permitted 
by  780  CMR  709.6.1  for  noncombustible  penetrating 
items,  the  annular  space  between  the  penetrating 
item  and  the  fireresistance  rated  assembly  being 
penetrated  shall  be  protected  as  specified  in 
780  CMR  709.7. 1  through  709.7.3. 

709.7.1  Materials:  The  material  used  to  fill  the 
annular  space  shall  comply  with  780  CMR 
709.7.1.1  or  709.7.1.2. 

709.7.1.1  Concrete  or  masonry  assemblies: 

Penetrations  of  concrete  or  masonry 
assemblies  by  a  maximum  six-inch  nominal 
diameter  copper,  iron  or  steel  pipe,  tube, 
conduit  or  wires  and  cables  with  steel  jackets 
shall  be  permitted  provided  that  the 
maximum  opening  size  is  144  square  inches 
(0.09  m2)  and  the  penetration  is  protected 
with  concrete,  grout  or  mortar  for  the  full 
thickness  of  the  assembly  or  the  thickness 
required  to  provide  a  fireresistance  rating 
equivalent  to  the  required  fireresistance 
rating  of  the  assembly  penetrated. 

709.7.1.2  All  assemblies:  In  all  assemblies, 
the  material  shall  prevent  the  passage  of 
flame  and  hot  gases  sufficient  to  ignite 
cotton  waste  when  subjected  to  the  time- 
temperature  fire  conditions  of  ASTM  El  19 
listed  in  Appendix  A  under  a  minimum 
positive  pressure  differential  of  0.01  inch  of 
water  column  (2.5  P)  at  the  location  of  the 
penetration  for  the  time  period  equivalent  to 
the  required  fireresistance  rating  of  the 
assembly  penetrated. 

709.7.2  Sleeves:  Where  sleeves  are  installed,  the 
sleeves  shall  be  noncombustible  and  shall  be 
securely  fastened  to  the  assembly  penetrated. 
All  space  between  the  item  contained  in  the 
sleeve  and  the  sleeve  itself  and  any  space 
between  the  sleeve  and  the  assembly  penetrated 
shall  be  filled  with  a  material  that  complies  with 
780  CMR  709.7.1. 


709.7.3  Insulation:  Insulation  and  coverings  on 
the  penetrating  item  shall  not  pass  through  the 
assembly  unless  these  materials  maintain  the 
required  fireresistance  rating  of  the  assembly  in 
accordance  with  780  CMR  709.6.2. 

780  CIMR  710.0  VERTICAL  SHAFTS 

710.1  General:  The  provisions  of  780  CMR  710.0 
shall  apply  to  all  vertical  shafts  where  such  shafts 
are  required  to  protect  openings  and  penetrations 
through  floor/ceiling  and  roof/ceiling  assemblies  as 
required  by  780  CMR  713.3  and  713.4. 

710.2  Construction:  The  shaft  and  the  shaft 
enclosure  shall  be  constructed  of  materials  permitted 
by  780  CMR  602.0  for  the  type  of  construction  of 
the  building.  Shaft  walls  which  are  exterior  walls 
shall  be  constructed  of  materials  approved  for 
exterior  walls  in  accordance  with  780  CMR  14. 

710.3  Fireresistance  rating:  A  shaft  shall  be 
enclosed  W\i\\fire  separation  assemblies  complying 
with  780  CMR  709.0  having  a  fireresistance  rating 
of  not  less  than  two  hours  where  a  shaft  connects 
four  stories  or  more  and  one  hour  where  connecting 
less  than  four  stories.  A  shaft  enclosure  shall  have 
a  fireresistance  rating  of  not  less  than  the  required 
rating  of  the  floor  assembly  penetrated  but  shall  not 
be  required  to  exceed  two  hours. 

Exception:  The  fireresistance  rating  of  interior 
stairway  enclosures  shall  comply  with  780  CMR 
1014.11. 

710.3.1      Openings     in     shaft     enclosures: 

Openings  other  than  those  necessary  for  the 
purpose  of  the  shaft  shall  not  be  permitted  in 
shaft  enclosures.  Openings  in  shaft  enclosures 
shall  be  protected  with  approved  opening 
protectives  in  accordance  with  780  CMR  706.0, 
716.0,  717.0  and  718.0. 

710.4  Top  enclosure:  A  shaft  that  does  not  extend 
to  the  underside  of  the  roof  deck  of  the  building  shall 
be  enclosed  at  the  top  with  a  fire  separation 
assembly  having  a  fireresistance  rating  of  not  less 
than  that  required  for  the  shaft  enclosure  walls. 

710.5  Bottom  enclosure:  Shafts  which  do  not 
extend  to  the  bottom  of  the  building  shall  be 
enclosed  at  the  lowest  level  with  afire  separation 
assembly  having  a  fireresistance  rating  of  not  less 
than  that  required  for  the  shaft  enclosure  walls,  or 
shall  terminate  in  a  room  having  an  occupancy 
related  to  the  purpose  of  the  shaft.  The  room  shall 
be  separated  from  the  remainder  of  the  building  by 
fire  separation  assemblies  having  a  fireresistance 
rating  with  opening  protectives  of  not  less  than  that 
required  for  the  shaft  enclosure. 


132 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


Exceptions: 

1 .  The  fireresistance  rated  room  separation  is 
not  required  provided  that  there  are  not  any 
openings  in  or  penetrations  through  the  shaft 
enclosure  to  the  remainder  of  the  building  except 
at  the  bottom.  The  bottom  of  the  shaft  shall  be 
closed  off  around  the  penetrating  items  with 
materials  permitted  by  780  CMR  720.3  for 
draftstoppmg,  or  the  room  shall  be  equipped 
throughout  with  an  automatic  sprinkler  system 
installed  in  accordance  with  780  CMR  9. 

2.  The  fireresistance  rated  room  separation  and 
protection  at  the  bottom  of  the  shaft  are  not 
required  where  there  are  not  any  combustible 
materials  in  the  shaft  and  where  there  are  not  any 
openings  in  or  other  penetrations  through  the 
shaft  enclosure  to  the  remainder  of  the  building. 

780  CMR  711.0  FIRE  PARTITIONS 

711.1  General:  Fire  partitions  shall  be  constructed 
of  the  types  of  materials  and  have  the  minimum 
fireresistance  rating  as  prescribed  by  Table  602  for 
the  type  of  construction. 

Exception:  Dwelling  unit  separations  in 
buildings  of  Types  2C,  3B  and  5B  construction 
shall  have  fireresistance  ratings  of  not  less  than 
Vi  hour  in  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1  or  780  CMR  906.2.2, 
provided  that  sprinklers  are  installed  in  all 
closets  located  against  tenant  separation  walls 
and  in  all  bathrooms. 

711.2  Corridor  walls  and  tenant  and  dwelling 
unit  separations:  Wall  assemblies  that  are  installed 
as  required  by  Table  602  for  corridor  walls,  to 
separate  tenant  spaces  and  to  separate  dwelling  units, 
shall  be  fire  partitions. 

711.3  Protectives:  All  opening  protectives  in  fire 
partitions  shall  comply  with  the  provisions  of 
780  CMR  704.0  and  shall  have  the  minimum 
fireresistance  rating  as  set  forth  in  780  CMR  716.0 

711.4  Continuity:  All  fire  partitions  shall  extend 
from  the  top  of  the  floor  assembly  below  to  the 
underside  of  the  floor/roof  slab  or  deck  above  or  to 
the  fireresistance  rated  floor/ceiling  or  roof/ceiling 
assembly  above,  and  shall  be  securely  attached 
thereto  The  supporting  construction  shall  be 
protected  to  afford  the  required  fireresistance  rating 
of  the  wall  supported,  except  for  exit  access  corridor 
walls  in  buildings  of  Types  2C,  3B  and  5B 
construction  and  tenant  separation  walls  in  covered 
mall  buildings  of  Type  2C  construction  All  hollow 
vertical  spaces  shall  be  firestopped  at  every  floor 
level  as  required  in  780  CMR  720.0. 

711.5  Exterior  walls:  Where  exterior  walls  serve  as 
a  part  of  a  required  fireresistance  rated  enclosure. 


such  walls  shall  comply  with  the  requirements  of 
780  CMR  705.0  for  exterior  walls  and  the 
fireresistance  rated  enclosure  requirements  shall  not 
apply. 

711.6  Penetrations:  Penetrations  through 
assemblies  shall  comply  with  780  CMR  709.6 
through  780  CMR  709.7.3. 

Exception:  In  occupancies  in  other  than  Use 
Group  H,  fire  dampers  are  not  required: 

1 .  At  penetrations  of  tenant  separation  and 
corridor  walls  in  buildings  equipped  throughout 
with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2.1. 

2.  At  penetrations  of  corridor  walls  where  the 
ducts  are  constructed  of  steel  and  do  not  have 
openings  which  communicate  the  corridor  with 
adjacent  spaces  or  rooms 

780  CMR  712.0  SMOKE  BARRIERS 

712.1  Where  required:  Smoke  barriers  shall  be 
provided  as  required  in  780  CMR  409  4  for 
occupancies  in  Use  Group  1-2  and  780  CMR  410.6 
for  occupancies  in  Use  Group  1-3. 

712.2  Construction:  Smoke  barriers  shall  have  a 
fireresistance  rating  of  not  less  than  one  hour.  Such 
barriers  shall  form  an  effective  membrane 
continuous  from  outside  wall  to  outside  wall  and 
from  floor  slab  to  floor  or  roof  deck  above,  including 
continuity  through  all  concealed  spaces,  such  as  the 
space  above  suspended  ceilings,  and  including 
interstitial  structural  and  mechanical  spaces. 
Transfer  grilles,  whether  equipped  with  fusible  link- 
operated  dampers  or  not,  shall  not  be  installed  in 
these  partitions  The  supporting  construction  shall 
be  protected  to  afford  the  required  fireresistance 
rating  of  the  wall  supported  in  buildings  of  other 
than  Types  2C,  3B  and  5B  construction. 

Exceptions: 

1 .  Smoke  barriers  are  not  required  in  interstitial 
spaces  where  such  spaces  are  designed  and 
constructed  with  ceilings  that  provide  resistance 
to  the  passage  of  fire  and  smoke  equivalent  to 
that  provided  by  the  smoke  barriers. 

2.  Smoke  barriers  in  occupancies  in  Use  Group 
1-3  are  permitted  to  be  constructed  of  nominal 
0. 10-inch-thick  steel  plate 

712.3  Doors:  Doorways  separating  corridors  in 
adjoining  smoke  compartments  shall  be  equipped 
with  a  pair  of  swinging-type  doors,  each  swinging  in 
a  direction  opposite  from  the  other,  and  the 
minimum  width  of  each  door  leaf  shall  be  44  inches 
(1118  mm)  for  corridors  utilized  for  the  movement 
of  beds  and  34  inches  (864  mm)  for  other  corridors. 
Other  doors  in  smoke  barriers  shall  be  of  the 
swinging  type  of  required  width. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


133 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Exceptions: 

1.  Horizontal  sliding  doors  that  comply  with 
780  CMR  410.0  are  permitted  in  smoke  barriers 
in  occupancies  in  Use  Group  1-3 

2.  Horizontal  sliding  doors  that  comply  with 
780  CMR  1017.4.4. 

712.4  Opening  protectives:  Doors  in  smoke  barriers 
shall  have  a  fire  protection  rating  of  not  less  than  20 
minutes  in  accordance  with  780  CMR  716.0 
Double  means  of  egress  corridor  doors  shall  have 
vision  panels  of  '/i-inch-tnick  labeled  wired  glass 
mounted  in  approved  steel  frames  in  accordance 
with  780  CMR  716.0.  The  doors  shall  close  the 
openings  with  only  the  clearance  necessary  for 
proper  operation  under  self-closing  or  automatic- 
closing  operations  and  shall  be  without  undercuts, 
louvers  or  grilles  Rabbets  or  astragals  are  required 
at  the  meeting  edges  of  double  means  of  egress 
doors,  and  stops  are  required  on  the  head  and  jambs 
of  all  doors  in  smoke  barriers.  Positive  latching 
devices  are  required  on  double  means  of  egress 
corridor  doors. 

Exceptions: 

1.  In  occupancies  in  Use  Group  1-2.  double 
means  of  egress  cross-corridor  doors  shall  be 
1%-inch  solid  core  wood  or  steel  doors  Positive 
latching  devices  are  not  required  on  double 
means  of  egress  cross-corridor  doors,  and  center 
mullions  are  prohibited. 

2.  Security  glazing  protected  on  both  sides  by 
an  automatic  sprinkler  system  shall  be  permitted 
in  doors  and  windows  in  smoke  barriers  in 
occupancies  in  Use  Group  1-3 .  Individual  panels 
of  glazing  shall  not  exceed  1,296  square  inches 
(0.84  m2),  shall  be  in  a  gasketed  frame  and 
installed  in  such  a  manner  that  the  framing 
system  will  deflect  without  breaking  (loading) 
glazing  before  the  sprinkler  system  operates 
The  sprinkler  system  shall  be  designed  to  wet 
completely  the  entire  surface  of  the  affected 
glazing  when  actuated. 

712.4.1  Door  closers:  Doors  in  smoke  barriers 
shall  be  provided  with  approved  door  hold-open 
devices  of  the  failsafe  type  which  shall  release 
the  doors,   causing  them  to  close  upon  the 
actuation  of  smoke  detectors  as  well  as  upon  the 
application  of  a  maximum  manual  pull  of  50 
pounds  (244  N)  against  the  hold-open  device. 
Exception:    Doors   in   smoke   barriers   in 
occupancies  in  Use  Group  1-3  shall  be  self- 
closing    or    automatic-closing    by    smoke 
detection. 

712.5  Smoke  damper:  An  approved  damper 
designed  to  resist  the  passage  of  smoke  shall  be 
provided  at  each  point  a  duct  penetrates  a  smoke 
barrier  The  damper  shall  close  upon  detection  of 
smoke  by  an  approved  smoke  detector  located 
within  the  duct. 


Exceptions: 

1.  In  lieu  of  an  approved  smoke  detector 
located  within  the  duct,  ducts  that  penetrate 
smoke  barriers  above  smoke  barrier  doors  that 
are  required  by  780  CMR  712  4  shall  have  the 
approved  damper  arranged  to  close  upon 
detection  of  smoke  by  the  local  device  designed 
to  detect  smoke  on  either  side  of  the  smoke 
barrier  door  opening 

2  Dampers  at  the  smoke  barrier  in  a  fully 
ducted  system  are  not  required 

780  CMR  713.0  FLOOR/CEILING  AND 
ROOF/CEDLJNG  ASSEMBLIES 

"?13.1  General:  All  floor  and  roof  assemblies  shall 
comply  with  the  applicable  provisions  of  780  CMR 
and  shall  have  a  fireresistance  rating  of  not  less  than 
the  fireresistance  rating  required  in  780  CMR  602.0. 

Exception:  Dwelling  unit  separations  in 
buildings  of  Types  2C,  3B  and  5B  construction 
shall  have  fireresistance  ratings  of  not  less  than 
Vi  hour  in  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1  or  780  CMR  906.2.2, 
provided  that  sprinklers  are  installed  in  all 
closets  located  against  tenant  separation  walls 
and  in  all  bathrooms 

713.1.1  Ceiling  panels:  Where  the  weight  of 
lay-in  ceiling  panels,  used  as  part  of 
fireresistance  rated  floor/ceiling  or  roof/ceiling 
assemblies,  is  not  adequate  to  resist  an  upward 
force  of  1  psf  (5  kg/nr),  wire  or  other  approved 
devices  shall  be  installed  above  the  panels  to 
prevent  vertical  displacement  under  such  upward 
force. 

713.1.2  Unusable  space:  In  an  assembly 
required  to  have  a  one-hour  fireresistance  rating, 
the  ceiling  membrane  of  a  fireresistance  rated 
assembly  is  not  required  to  be  installed  where 
unusable  space  occurs  below  the  assembly,  or 
the  flooring  is  not  required  to  be  installed  where 
unusable  space  occurs  above  the  assembly. 

713.2  Continuity:  All  floor/ceiling  and  roof/ceiling 
assemblies  shall  be  continuous  without  openings  or 
penetrations  except  as  permitted  by  780  CMR  713  0 
Floor  assemblies  which  are  required  to  be 
fireresistance  rated  shall  extend  to  and  be  tight 
against  exterior  walls,  or  other  provisions  shall  be 
made  for  maintaining  the  fireresistance  rating  of  the 
assembly  at  such  locations.  Penetrations  through  a 
roof  deck  to  the  outside  are  permitted  provided  that 
the  required  fireresistance  rating  of  the  roof 
construction  is  maintained.  All  concealed  spaces 
and  openings  shall  be  firestopped  and  draftstopped 
in  accordance  with  780  CMR  720.0 

713.3  Floor  opening  enclosure:  All  floor  openings 
connecting  two  or  more  stories  shall  be  protected  by 


134 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


a  shaft  enclosure  that  complies  with  780  CMR 
710.0. 

Exceptions:  A  shaft  enclosure  is  not  required  for 
any  of  the  following  floor  openings: 

1 .  A  floor  opening  serving  and  contained  within 
a  single  dwelling  unit  and  connecting  four  stories 
or  less. 

2.  A  floor  opening  which: 

2.1.  Is  not  part  of  the  required  means  of 
egress; 

2.2.  Is  not  concealed  within  the  building 
construction; 

2.3.  Does  not  connect  more  than  two  stories; 

2.4.  Is  separated  from  other  floor  openings 
serving  other  floors  by  construction 
conforming  to  780  CMR  710.3;  and 

2.5.  Is  not  open  to  a  corridor  in  occupancies 
in  Use  Groups  I  and  R,  or  is  not  open  to  a 
corridor  on  a  floor  not  equipped  throughout 
with  an  approved  automatic  fire  suppression 
system  in  other  use  groups. 

3.  A  floor  opening  in  a  mall  that  complies  with 
780  CMR  402.0. 

4.  A  floor  opening  between  a  mezzanine  that 
complies  with  780  CMR  505.0,  and  the  floor 
below. 

5.  An  atrium  that  complies  with  780  CMR 
404.0. 

6.  A  floor  opening  in  an  open  parking  structure 
that  complies  with  780  CMR  406.0. 

7.  An  approved  masonry  chimney  where 
annular  space  protection  is  provided  for  in 
accordance  with  780  CMR  720.6.4. 

8.  A  floor  opening  containing  an  escalator  and 
complying  with  780  CMR  301 1.2. 

9.  A  floor  opening  that  complies  with 
780  CMR  410.5  in  an  occupancy  in  Use  Group 
1-3. 

10.  Noncombustible  shafts  connecting 
communicating  floor  levels  in  an  occupancy  in 
Use  Group  1-3  where  the  area  complies  with 
780  CMR  410  5.  Where  additional  stories  are 
located  above  or  below,  the  shaft  shall  be 
permitted  to  continue  with  fire  and  smoke 
damper  protection  provided  at  the  fireresistance 
rated  floor/ceiling  assembly  between  the 
noncommunicating  stories. 

11.  A  single  floor  opening  containing  a 
stairway  which  is  not  a  required  means  of  egress 
in  an  occupancy  in  Use  Group  B  and  complying 
with  the  following  parameters: 

11.1.  The  stairway  does  not  connect  more 
than  six  floor  levels. 

1 1.2.  The  stairway  does  not  connect  with 
an  exit  access  corridor. 

1 1.3.  The  stairway  floor  opening  shall  not 
exceed  160  square  feet  (15  m:). 

1 1 .4.  The  stairway  floor  opening  shall  be 
protected  in  the  same  manner  as  an  escalator 
floor  opening  complying  with  780  CMR 
3011.2. 


11.5.  The  building  is  equipped  throughout 
with  an  approved  automatic  sprinkler  system 
in  accordance  with  780  CMR  906.2. 1 

713.4  Penetration  protection:  All  penetrations  of  a 
floor/ceiling  assembly  or  the  ceiling  membrane  of  a 
roof/ceiling  assembly  shall  be  protected  by  a  shaft 
enclosure  that  complies  with  780  CMR  710:0. 

Exceptions: 

1.  Penetrations  within  and  through  a  floor 
opening  permitted  to  be  unenclosed  by 
780  CMR  713.3. 

2.  Penetrations  through  assemblies  required  to 
be  fireresistance  rated  and  complying  with 
780  CMR  713.4.1  or  780  CMR  713.4.2. 

3.  Penetrations  through  assemblies  without  a 
required  fireresistance  rating  and  complying 
with  780  CMR  713.4.1  or  780  CMR  713.4.3. 

713.4.1  Through-penetration  system:  A  shaft 
enclosure  shall  not  be  required  where  cables, 
cable  trays,  conduits,  tubes  or  pipes  penetrate  a 
floor  assembly  and  are  protected  with  an 
approved  through-penetration  protection  system 
tested  in  accordance  with  ASTM  E814  listed  in 
Appendix  A.  The  positive  pressure  differential 
between  the  exposed  and  unexposed  surfaces  of 
the  test  assembly  shall  not  be  less  than  0.01 -inch 
water  gage  (2.5  P).  The  system  shall  have  an 
"F"  rating  and  a  "T"  rating  of  not  less  than  1 
hour  but  not  less  than  the  required  fireresistance 
rating  of  the  assembly  being  penetrated.  All 
penetrations  through  a  ceiling  that  is  an  integral 
component  of  a  fireresistance  rated  floor/ceiling 
or  roof/ceiling  assembly,  shall  comply  with 
780  CMR  713.4.2. 

Exceptions: 

1.  A  "T"  rating  shall  not  be  required  for 
floor  penetrations  that  are  contained  and 
located  within  the  cavity  of  a  wall. 

2.  A  "T"  rating  shall  not  be  required  for 
floor  penetrations  by  pipe,  tube  and  conduit 
that  are  not  in  direct  contact  with 
combustible  material. 

713.4.2  Fireresistance  rated  assemblies:  The 

required  fireresistance  rating  of  floor/ceiling  and 
roof/ceiling  assemblies  shall  be  determined  in 
accordance  with  ASTM  El  19  listed  in 
Appendix  A.  Except  where  permitted  by 
780  CMR  713.4.2.1  through  713.4.2.3, 
penetrations  for  electrical,  mechanical,  plumbing 
and  communication  conduits,  pipes  and  systems 
shall  be  installed  in  accordance  with  the 
approved  ASTM  El  19  rated  assembly.  In  the 
case  of  ceilings  that  are  an  integral  component  of 
a  fireresistance  rated  floor/ceiling  or  roof/ceiling 
assembly,  all  penetrations  shall  be  installed  in 
accordance  with  the  approved  ASTM  E 1 1 9  rated 
assembly  or  780  CMR  713.4.2.3. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


135 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Exceptions: 

1 .  Outlet  boxes  and  fittings  are  permitted, 
provided  that  such  devices  are  listed  for 
installation  in  fireresistance  rated  assemblies 
and  are  installed  in  accordance  with  the 
listing. 

2.  Ceiling  dampers  shall  not  be  required 
where  fire  tests  have  shown  that  such 
dampers  are  not  necessary  in  order  to 
maintain  the  fireresistance  rating  of  the 
assembly. 

713.4.2.1  Noncombustible  penetrations: 
Penetrations  by  noncombustible  vents, 
chimneys,  conduits,  pipes  and  tubes  through 
a  fireresistance  rated  floor  assembly  which 
connect  not  more  than  two  stories  are 
permitted.  Penetrations  by  noncombustible 
conduit,  pipe  and  tubes  through  a  fireresis- 
tance rated  floor  assembly  which  connect 
more  than  two  stories  are  permitted  provided 
that  the  aggregate  area  of  the  penetrating 
items  shall  not  exceed  one  square  foot  (0.09 
m:)  in  any  100  square  feet  (9.3  rri  )  of  floor 
area.  In  all  cases,  the  annular  space  between 
the  penetrating  item  and  the  assembly  shall 
be  protected  in  accordance  with  780  CMR 
707.8. 

713.4.2.2  Air  ducts:  Penetrations  by  an  air 
duct  or  plenum  through  a  fireresistance  rated 
floor  assembly,  which  connect  not  more  than 
two  stories,  are  permitted  where  a  fire 
damper  that  complies  with  780  CMR  717.0 
is  installed  at  the  floor  line.  Afire  damper  is 
not  required  at  penetrations  of  a  roof/ceiling 
assembly  where  ducts  are  open  to  the 
atmosphere. 

713.4.2.3  Ceiling  penetrations:  In  the  case 
of  ceilings  that  are  an  integral  component  of 
a  fireresistance  rated  floor/ceiling  or 
roof7ceiling  assembly,  openings  to  accom- 
modate noncombustible  conduits,  pipes, 
tubes,  electrical  outlets  or  air  ducts  shall  be 
permitted  provided  that  the  aggregate  area  of 
such  openings  does  not  exceed  100  square 
inches  (0.065  nr)  in  any  100  square  feet  (9.3 
nr)  of  ceiling  area.  The  space  around 
noncombustible  conduits,  pipes,  tubes  and 
electrical  outlet  boxes  at  the  ceiling 
penetration  shall  be  firestopped  in 
accordance  with  780  CMR  720.6.4  or  shall 
be  protected  in  accordance  with  780  CMR 
709.7  or  780  CMR  713.4.1.  For 
noncombustible  air  duct  penetrations,  an 
approved  ceiling  damper  shall  be  installed  at 
the  ceiling  line.  Ceiling  dampers  shall  be 
constructed  in  accordance  with  the  details 
listed  in  a  fireresistance  rated  design  or  shall 
be  labeled  to  function  as  a  heat  barrier  for 
air-handling  outlet/inlet  penetrations  in  the 
ceiling  of  a  fireresistance  rated  assembly. 


713.4.3   Nonfireresistance   rated   assemblies: 

Penetrations  of  floor  assemblies  without  a 
required  fireresistance  rating  shall  conform  to 
780  CMR  713.4.3.1  through  713.4.3.3.  All 
penetrations  through  the  ceiling  membrane  of  a 
roof  assembly  without  a  required  fireresistance 
rating  shall  be  protected  in  accordance  with 
780  CMR  720.6.4. 

713.4.3.1  Noncombustible   penetrations: 

Penetrations  by  noncombustible  vents, 
chimneys,  conduits,  pipes  and  tubes  through 
unprotected  floor  assemblies  which  connect 
not  more  than  three  stories  are  permitted 
provided  that  the  annular  space  between  the 
penetrating  item  and  the  floor  is  protected  in 
accordance  with  780  CMR  720.6.4. 

713.4.3.2  Air  ducts:  Penetrations  by 
noncombustible  air  ducts  through  unprotect- 
ed floor  assemblies  which  connect  not  more 
than  three  stories  are  permitted  provided  that 
a  fire  damper  complying  with  780  CMR 
717.0  is  installed  at  each  floor  line. 

713.4.3.3  Noncombustible  or  combustible 
penetrations:  Penetrations  by  vents, 
chimneys,  cables,  wires,  air  ducts,  conduits, 
pipes  and  tubes  through  an  unprotected  floor 
assembly  which  connect  not  more  than  two 
stories  are  permitted  provided  that  the 
annular  space  is  protected  in  accordance 
with  780  CMR  720.6.4. 

780  CMR  714.0  ROOF  CONSTRUCTION 

714.1  General:  Roofs  shall  be  constructed  of 
materials  or  assemblies  of  materials  designed  to 
afford  the  fireresistance  rating  required  by  Table  602 
as  herein  modified. 

714.2  Stadiums:  The  roof  construction,  including 
beams,  trusses,  framing,  arches  and  roof  decks, 
enclosing  stadiums  of  Type  1  or  Type  2 
construction,  shall  be  of  approved  noncombustible 
materials  without  a  specified  fireresistance  rating  or 
of  Type  4  construction. 

714.3  Roofs  20  feet  or  higher:  Where  every  part  of 
the  structural  framework  of  roofs  in  buildings  of 
Type  1  or  Type  2  construction  is  20  feet  (6096  mm) 
or  more  above  the  floor  immediately  below, 
omission  of  all  fire  protection  of  the  structural 
members  is  permitted,  including  the  protection  of 
trusses,  roof  framing  and  decking. 

714.4  Roof  slabs,  arches  and  decking:  Where  the 
omission  of  fire  protection  from  roof  trusses,  roof 
framing  and  decking  is  permitted,  roofs  in  buildings 
of  Types  I  and  2  construction  shall  be  constructed  of 
noncombustible  materials,  or  of  fireretardant-  treated 
wood  as  permitted  in  Table  602,  without  a  specified 
fireresistance  rating,  or  of  Type  4  construction  in 


136 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  .AND  CONSTRUCTION 


buildings  not  over  five  stones  or  65  feet  (19812  mm) 
in  height 

714.5  Firestopping:  Firestopping  of  ceiling  and 
attic  spaces  shall  be  provided  as  required  by 
780  CMR  720.0. 

780  CMR  715.0  F1RERESISTANCE 
RATING  OF  STRUCTURAL  MEMBERS 

715.1  Requirements:  The  fireresistance  rating  of 
structural  members  and  assemblies  shall  comply 
with  the  requirements  for  the  type  of  construction 
and  shall  not  be  less  than  the  rating  required  for  the 
fireresistance  rated  assemblies  supported,  except  as 
provided  for  in  780  CMR  71 1.4  for  support  of  exit 
access  corridor  walls  and  tenant  separation  walls  in 
covered  mall  buildings,  and  in  780  CMR  712.2  for 
support  of  smoke  barriers  The  maximum  required 
fireresistance  rating  of  structural  members 
supporting  fire  separation  assemblies  of  tank  storage 
areas  as  provided  for  in  780  CMR  418.3.2.1  shall  be 
two  hours,  but  not  less  than  required  bv  Table  602 
for  the  building  construction  type. 

715.2  Protection  of  structural  members  Columns, 
girders,  trusses,  beams,  lintels  or  other  structural 
members  which  are  required  to  have  a  fireresistance 
rating  and  which  support  more  than  two  floors  or 
one  floor  and  roof,  or  support  a  loadbearing  wall  or 
a  nonloadbearing  wall  more  than  two  stories  high, 
shall  be  individually  protected  on  all  sides  for  the 
full  length  or  height  with  materials  having  the 
required  fireresistance  rating.  All  other  structural 
members  required  to  have  a  fireresistance  rating 
shall  be  protected  by  individual  encasement,  by  a 
membrane  or  ceiling  protection  as  specified  in 
780  CMR  713.0,  or  by  a  combination  of  both. 

715.3  Embedments  and  enclosures:  Pipes,  wires, 
conduits,  ducts  or  other  service  facilities  shall  not  be 
embedded  in  the  required  fire  protective  covering  of 
a  structural  member  that  is  required  to  be 
individually  encased. 

715.4  Impact  protection:  Where  the  fire  protective 
covering  of  a  structural  member  is  subject  to  impact 
damage  from  moving  vehicles,  the  handling  of 
merchandise  or  other  activity,  the  fire  protective 
covering  shall  be  protected  by  comer  guards  or  by  a 
substantial  jacket  of  metal  or  other  noncombustible 
material  to  a  height  adequate  to  provide  full 
protection,  but  not  less  than  five  feet  (1524  mm) 
from  the  finished  floor. 


715.5  Exterior  structural  members:  Structural 
members  located  in  exterior  walls  or  along  the  outer 
lines  of  a  building  or  structure  shall  be  protected  as 
required  by  Table  602  for  exterior  loadbearing  walls 
for  the  type  of  construction  involved  and  shall  be 
protected  against  corrosion  in  accordance  with 
780  CMR  2210.1.  The  interior  faces  of  exterior 
structural  members  shall  be  protected  with  coverings 
of  not  less  than  the  required  fireresistance  rating 
specified  for  interior  structural  members  in  Table 
602  Where  a  fireresistance  rating  is  required  in 
Table  602  for  exterior  loadbearing  walls  in  buildings 
of  Types  2C.  3B  and  5B  construction,  the  interior 
faces  of  any  exterior  structural  member  of  such 
buildings  shall  be  protected  to  provide  a 
fireresistance  rating  not  less  than  that  required  for 
exterior  load-  bearing  walls. 

715.6  Bottom  flange  protection  Fire  protection  is 
not  required  for  the  bottom  flange  of  lintels,  shelf 
angles  and  plates  which  are  not  a  pan  of  the 
structural  frame  or  which  have  a  span  of  six  feet 
(1829  mm)  or  less 

715.7  Stone  lintels  Stone  lintels  on  spans  exceeding 
four  feet  (1219  mm)  shall  not  be  permitted,  unless 
supplemented  by  fireresistance  rated  structural 
members  or  masonry  arches  of  the  required  strength 
to  support  the  superimposed  Ioads- 

780  CMR  716.0  FTRE  DOOR  ASSEMBLIES 
716.)  Fire  door  assemblies  Approved  fire  door 
assemblies  as  defined  in  780  CMR  shall  be 
constructed  of  any  material  or  assembly  of 
component  materials  which  conforms  to  the  test 
requirements  of  ASTM  El 52  listed  in  Appendix.  A 
and  the  fire  protection  rating  herein  required  in 
Table  716.":.  unless  otherwise  specifically  provided 
for  in  780  CMR. 

716.1.1  Twenty-minute    doors     Fire   doors 

having  a  fire  protection  rating  of  20  minutes 
shall  be  tested  in  accordance  with  ASTM  El 52 
listed  in  Appendix  A  without  the  hose  stream 
test. 

716.1.2  Doors  in  exit  enclosures:  All  doorway 
opening  protectives  for  exit  enclosures  shall  be 
labeled  means  of  egress  fire  doors  and  shall 
have  a  maximum  transmitted  temperature  end 
point  of  not  more  than  450°F  (232°C)  above 
ambient  at  the  end  of  30  minutes  of  standard  fire 
test  exposure 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


137 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  716.1 

OPENING  PROTECTIVE  FIRE 

PROTECTION  RATING 


Type  of  assembly 

Required 

assembly 

rating  (hour) 

Minimum 
opening 
protection 
assembly 
(hour) 

Fire  walls  and  fire  separation  4  3 

assemblies  havmg  a  required  3  3 

fireresistance  rating  greater  than  2  1  'A 

one  hour  \  y2  1 14 

Fire  separation  assemblies: 

Shaft  and  exit  enclosure  walls  1  1 

Other  fire  aeparation  assemblies  1  % 


Fire  partitions: 

Exit  access  corridor  enclosure 

wall 

1 

Va' 

Vi 

V3 

Other  fire  partitions 

1 

Vi 

Note  a.  For  testing  requirements,  see  780  CMR  716. 1. 1. 

716.2  Labeled  protective  assemblies:  Ml  fire  door 
assemblies  shall  be  labeled  by  an  approved  agency 
Labeled  protective  assemblies  that  conform  to  the 
requirements  of  780  CMR  716.0  or  UL  10A,  14B 
and  14C  for  tin-clad  fire  door  assemblies,  and 
NFiPA  80  listed  in  Appendix  A,  shall  be  approved 
for  use  as  provided  for  in  780  CMR. 

716.2.1  Labeling  requirements:  Fire  doors 
shall  have  a  label  or  other  identification  showing 
the  name  of  the  manufacturer,  the  fire  protection 
rating  and,  where  required  for  fire  doors  in  exit 
enclosures  by  780  CMRs  716.1.2  or  1014.8.3, 
the  maximum  transmitted  temperature  end  point. 
Such  label  shall  be  approved  and  shall  be 
permanently  affixed.  The  label  shall  be  applied 
at  the  factory  where  fabrication  and  assembly  are 
done.  Inspection  shall  be  made  by  an  approved 
agency 

716.2.2  Oversized  doors:  Approval  of  doors 
which  cannot  be  labeled  because  of  size  shall  be 
based  on  a  certificate  of  inspection  furnished  by 
an  approved  testing  agency  for  such  oversized 
doors.  The  certificate  shall  state  that  the  door 
conforms  to  the  requirements  of  design, 
materials  and  construction,  but  has  not  been 
subjected  to  the  fire  test. 

716.3  Multiple  doors  in  fire  walls:  Two  doors,  each 
with  afire  protection  rating  of  VA  hours,  installed 
on  opposite  sides  of  the  same  opening  in  a  fire  -wall, 
shall  be  deemed  equivalent  in  fire  protection  rating 
to  one  three-hour^re  door. 

716.4  Glass  panels:  Wired  glass  panels  shall  be 
permitted  in  fire  doors  within  the  limitations  of 


780  CMR  719.0  and  as  herein  specifically 
prescribed. 

716.5  Door  closing:  Fire  doors  shall  be  self-closing 
or  automatic-closing  in  accordance  with  the 
requirements  of  NFiPA  80  listed  in  Appendix  A  and 
the  requirements  of  780  CMR  716.5.1   through 

716.5.4. 

716.5.1  Smoke-activated  doors:  Fire  doors 
which  are  not  self-closing  and  which  protect 
openings  in  horizontal  exits,  exits  or  exit  access 
corridors  required  to  be  of  fireresistance  rated 
construction  shall  be  automatic-closing  by  the 
actuation  of  smoke  detectors  or  by  loss  of  power 
to  the  smoke  detector  or  the  hold-open  device. 

716.5.2  Doors  in  pedestrian  ways:  Vertical 
sliding  or  vertical  rolling  steel  fire  doors  in 
openings  through  which  pedestrians  travel  shall 
not  be  automatic-closing  by  actuation  of  smoke 
detectors. 

Exception:  Doors  that  are  activated  by 
smoke  detectors  arranged  on  an  alarm 
verification  circuit  in  accordance  with 
780  CMR  918.7. 

716.5.3  Swinging  fire  doors  The  door  closers 
for  swinging  fire  doors  that  are  not  required  to 
be  automatic-closing  by  smoke  detector 
activation  in  accordance  with  780  CMR  716.5.1, 
shall  be  permitted  to  be  activated  by  a  single 
fusible  link  incorporated  in  the  hold-open  arm  of 
an  approved  door  closer  where  the  ceiling  is  less 
than  three  feet  (914  mm)  above  each  side  of  the 
door  opening. 

716.5.4  Closing  time:  Doors  that  are  automatic- 
closing  by  automatic  fire  detectors  or  are  self- 
closing  shall  not  have  a  delay  in  the  initiation  of 
closing  or  reclosing  of  more  than  ten  seconds. 

780  CMR  717.0  FIRE  DAMPERS 
717.1  Approval:  Fire  dampers  shall  comply  with 
the  requirements  of  UL  555  listed  in  Appendix  A 
and  shall  bear  the  label  of  an  approved  testing 
agency.  Fire  dampers  shall  be  classified  and 
identified  in  accordance  with  UL  555.  Fire  dampers 
installed  in  systems  that  continue  to  operate  when 
smoke  or  heat  from  a  fire  is  detected  shall  be  labeled 
for  installation  in  dynamic  systems  as  required  by 
UL  555.  Fire  dampers  shall  be  installed  in 
accordance  with  manufacturer's  installation 
instructions.  Fire  dampers  shall  have  the  minimum 
fire  protection  rating  specified  in  Table  717. 1  for  the 
type  of  penetration. 


138 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


Table  717.1 
FIRE  DAMPER  RATING 


Type  of  Penetration 

Minimum 

damper  rating 

(hour) 

Fire  partitions  less  than  1  hour 

Unprotected  floor  assemblies  (see 
780  CMR  713.4.3.2) 

V2 

Single  membrane  of  a  1  -hour 
fireresistance  rated  assembly 

1  -hour  fireresistance  rated  assemblies 

1 

2-hour  fireresistance  rated  assemblies 

\Vi 

3 -hour  or  greater  fireresistance  rated 
assemblies 

3 

717.2  Where  required:  Fire  dampers  shall  be 
provided  at  locations  required  by  780  CMR  where 
atr  distribution  system  penetrate  assemblies  required 
to  have  a  fireresistance  rating.  Where  the 
installation  of  a  fire  damper  will  interfere  with  the 
operation  of  a  required  smoke  control  system  in 
accordance  with  780  CMR  921 .0  or  the  operation  of 
an  exhaust  svstem  conveying  hazardous  materials  as 
defined  in  the  mechanical  code  listed  in  Appendix  A. 
approved  alternative  protection  shall  be  utilized. 

717.3  Access.  Access  shall  be  provided  to  fire 
dampers  for  inspection  and  servicing. 

780  CMR  718.0  FIRE  WINDOWS 
AND  SHUTTERS 

718.1  Fireresistance  rating:  Approved  assemblies 
of  fire  windows  and  fire  shutters  shall  meet  the  test 
requirements  of  ASTM  E163  listed  in  Appendix  A 
Fire  windows  shall  be  in  the  fixed  closed  position  or 
be  automatic-closing. 

718.1.1  Exception:  Steel  window  frame 
assemblies  of  Vs-inch  (3  mm)  minimum  solid 
section  or  of  not  less  than  nominal  0.048-inch- 
thick  formed  sheet  steel  members  fabricated  by 
pressing,  mitering,  riveting,  interlocking  or 
welding  and  having  provision  for  glazing  with 
%-inch  wired  glass  as  required  in  780  CMR 
719.0  where  securely  installed  in  the  building 
construction  and  glazed  with  Vi-inch  labeled 
wired  glass,  shall  be  deemed  to  meet  the 
requirements  for  a  Va-\\ouz  fire  window  assembly. 

718.2  Window  mullions  All  metal  mullions  which 
exceed  a  nominal  height  of  1 2  feet  shall  be  protected 
with  materials  to  afford  the  same  fireresistance 
rating  as  required  for  the  wall  construction  in  which 
the  protective  is  located. 

718.3  Swinging  fire  shutters:  Where  fire  shutters  of 
the  swinging  type  are  installed  in  exterior  openings, 
not  less  than  one  row  in  every  three  vertical  rows 
shall  be  arranged  to  be  readily  opened  from  the 
outside,  and  shall  be  identified  by  distinguishing 


marks  or  letters  not  less  than  six  inches  (152  mm) 
high. 

718.4  Rolling  fire  shutters:  Where  fire  shutters  of 
the  rolling  type  are  installed,  such  shutters  shall  be 
of  approved  counter-balanced  construction  and 
capable  of  being  readily  opened  from  the  outside. 

780  CMR  719.0  WIRED  GLASS 

719.1  General:  Wired  glass  installed  as  an  opening 
protective  shall  be  tested  in  accordance  with  ASTM 
E163  listed  in  Appendix  A.  shall  bear  the  label  of  an 
approved  agency  and  shall  be  installed  in  approved 
frames.  Wired  glass  panels  shall  conform  to  the  size 
limitations  set  forth  in  Table  719.1. 

Table  719.1 

LIMITING  SIZE3  OF  WIRED  GLASS 

PANELS 


Opening  fire 

Maximum  area 

Maximum 

Maximum 

protection  ratmg 

(square  inches) 

height 

width 

(inches) 

(inches) 

3  hour 

0 

0 

0 

1  Vi-hour  doors  in 

exterior  walls 

0 

0 

0 

1  and  1  Vi  hours 

100 

33 

10 

3/4hour 

5,236 

54 

54 

Vb  hour 

not  limited 

not  limited 

not  limited 

Fire  windows 

1,296 

54 

54 

Note  a.  1  Inch  =  25.4  mm:  1  square  inch  =  0.0006452 
nr. 

719.1.1  Fire  walls:  Wired  glass  in  fire  doors 
located  in  fire  walls  shall  be  prohibited  except 
that  where  serving  as  a  horizontal  exit,  a  self- 
closing  swinging  door  shall  be  permitted  to  have 
a  vision  panel  of  not  more  than  100  square 
inches  (0.065  m2)  without  a  dimension 
exceeding  ten  inches  (254  mm). 

719.1.2  Fire  separation  assemblies:  Wired 
glass  vision  panels  shall  not  be  installed  in  fire 
doors  having  a  1  '/2-hour  fire  protection  ratmg 
intended  for  installation  in  fire  separation 
assemblies,  unless  the  glass  panels  are  not  more 
than  100  square  inches  (0.065  nr)  in  area. 

719.2  Exit  and  elevator  protectives  Except  where 
fire  doors  are  specifically  required  by  780  CMR  4  to 
be  solid  in  such  locations  where  unusually  hazardous 
conditions  prevail,  approved  wired  glass  vision 
panels  used  in  fire  doors  in  elevator  and  stairway 
shaft  enclosures  shall  be  so  located  as  to  furnish 
clear  vision  of  the  passageway  or  approach  to  the 
elevator  or  stairway  and  shall  not  exceed  the  size 
limitations  specified  in  Table  719.1. 

719.3  Fire  separation  assemblies:  Panels  of  %-inch 
wired  glass  shall  not  be  installed  in  fire  separation 
assemblies  intended  for  subdividing  purposes  as  set 
forth  in  780  CMR  709.1  where  the  required 
fireresistance  rating  of  the  wall  exceeds  one  hour. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


139 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


The  maximum  size  of  such  panels  shall  not  exceed 
the  limitations  for  a  %-hour  door. 

780  CMR  720.0  FIRESTOPPING 
AND  DRAFTSTOPPESG 

720.1  General:  To  prevent  the  free  passage  of  flame 
and  products  of  combustion  through  concealed 
spaces  or  openings  in  the  event  of  fire,  provisions 
shall  be  made  to  provide  effective  firestops  or 
draftsiops  as  herein  specified. 

720.2  Firestopping  materials:  Ail  firestopping 
shall  consist  of  approved  noncombustible  materials 
securely  fastened  in  place.  Firestops  of  approved 
noncombustible  materials  or  of  materials  of  two 
thicknesses  of  one-inch  lumber  with  broken  lap- 
joint,  or  one  thickness  of  23/32-inch  wood  structural 
panel  with  joints  backed  by  23/32-inch  wood 
structural  panel,  or  of  two-inch  lumber  installed  with 
tight  joints,  shall  be  installed  in  open  spaces  of  wood 
framing. 

720.3  Draftstopping  materials:  Draftstopping 
materials  shall  not  be  less  than  Vi  -inch  gypsum 
board,  3/s-inch  plywood  or  other  approved  materials 
adequately  supported. 

720.4  Integrity  The  integrity  of  all  firestopping  and 
draftstopping  shall  be  continuously  maintained. 

720.5  Required  inspection:  Firestopping  and 
draftstopping  shall  not  be  concealed  from  view  until 
inspected  and  approved. 

720.6  Firestopping  required:  Firestopping  shall  be 
installed  in  the  locations  specified  in  780  CMR 
720.6.1  through  720.6.7. 

720.6.1  Concealed  wall  spaces:  Firestopping 
shall  be  installed  in  concealed  spaces  of  stud 
walls  and  partitions,  including  furred  or  studded- 
off  spaces  of  masonry  or  concrete  walls,  and  at 
the  ceiling  and  floor  or  roof  levels.  Firestopping 
is  not  required  at  the  ceiling  level  of  walls, 
partitions  and  furred  spaces  constructed  of 
noncombustible  materials  as  defined  by 
780  CMR  704.4. 

720.6.2  Connections  between  horizontal  and 
vertical  spaces:  Firestopping  shall  be  installed 
at  all  interconnections  between  vertical  and 
horizontal  spaces  such  as  occur  at  soffits  over 
cabinets,  drop  ceilings,  cove  ceilings  and  similar 
locations. 

720.6.3  Stairways:  Firestopping  shall  be 
installed  in  concealed  spaces  between  stairway 
stringers  at  the  top  and  bottom  of  the  run 

720.6.4  Ceiling  and  floor  openings  Where 
permitted  by  Exception  7  of  780  CMR  713.3,  or 
by  780  CMR  713.4.2.3  or  7 13. 4. 3,  firestopping 
shall   be  installed   at   openings   around  vents, 


pipes,  ducts,  chimneys  and  fireplaces  at  ceiling 
and  floor  levels,  with  approved  noncombustible 
materials.  Factory  built  chimneys  and  fireplaces 
shall  be  fire  stopped  in  accordance  with  UL  103 
and  UL  127  listed  in  Appendix  A.  Where 
ceilings  or  floors  are  required  to  be  fireresistance 
rated,  the  openings  around  vents,  pipes,  ducts, 
chimneys  and  fireplaces  shall  be  protected  in 
accordance  with  the  requirements  of  780  CMR 
713.4  through  713.4.2.3. 

720.6.5  Architectural  trim:  Firestopping  shall 
be  installed  in  exterior  cornices  and  other 
exterior  architectural  elements  where  permitted 
of  combustible  construction  in  780  CMR  1406.0, 
or  where  erected  with  combustible  frames,  at 
maximum  intervals  of  20  feet  (6096  mm)  If 
noncontinuous,  such  elements  shall  have  closed 
ends,  with  at  least  four  inches  (102  mm)  of 
separation  between  sections. 

720.6.6  Combustible     finish      and      trim 

Firestopping  shall  be  installed  in  the  space 
behind  combustible  trim  and  finish  where 
permitted  under  780  CMR  and  all  other  hollow 
spaces  where  permitted  in  fireresistance  rated 
construction  at  ten-foot  (3048  mm)  intervals;  or 
the  space  shall  be  solidly  filled  with  approved 
noncombustible  materials. 

720.6.7  Concealed  sleeper  spaces:  Firestopping 
shall  be  installed  in  concealed  spaces  formed  by 
floor  sleepers  in  areas  of  not  more  than  100 
square  feet  (9.30  m:);  or  the  space  shall  be 
solidify'  filled  with  approved  noncombustible 
materials. 

720.7  Draftstopping  required  Draftstopping  shall 
be  installed  in  buildings  of  Types  3,  4  and  5 
construction  in  the  locations  specified  by  780  CMR 
720.7.1  and  720.7.2. 

720.7.1  Floors:  Where  ceilings  are  suspended 
below  solid  wood  joists  or  suspended  or  attached 
directly  to  the  bottom  of  open-web  wood  floor 
trusses,  the  space  between  the  ceiling  and  the 
floor  above  shall  be  divided  by  draftstopping  as 
specified  in  780  CMR  720.7.1.1  through 
720.7.1.3. 

720.7.1.1   Use  Groups  R-l   and  R-2:   In 

occupancies  in  Use  Groups  R-l  and  R-2, 

draftstopping  shall  be  installed  in  line  with 

tenant  and  dwelling  unit  separation  walls 

where   the   walls   do    not    extend   to    the 

underside  of  the  floor  sheathing  above. 

Exception:  Drafistopping  is  not  required 

in  buildings  equipped  throughout  with  an 

automatic  sprinkler  system    installed  in 

accordance  with  780  CMR  906.2.1  or 

906.2.2,      provided      that      automatic 

sprinklers    are    also    installed    in    the 

combustible  concealed  space. 


140 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRERESISTANT  MATERIALS  AND  CONSTRUCTION 


720.7.1.2  Use  Group  R-3:  In  occupancies  in 
Use  Group  R-3,  the  space  shall  be  divided 
into  approximately  equal  areas  not  greater 
than  500  square  feet  (46.5  nr).  The 
drqftslopping  shall  be  installed  parallel  to  the 
main  framing  members. 

Exception:  Drqftslopping  is  not  required 
in  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2. 1  or 
906.2.2,  provided  that  automatic 
sprinklers  are  also  installed  in  the 
combustible  concealed  space. 

720.7.1.3  Other  use  groups:  In  all  other  use 
groups,  draftstopping  shall  be  installed  so 
that  horizontal  areas  do  not  exceed  1,000 
square  feet  (93  nr). 

Exception:  Draftstopping  is  not  required 
in  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1  or 
906.2.2,  provided  that  automatic 
sprinklers  are  also  installed  in  the 
combustible  concealed  space  above  the 
ceiling. 

720.7.2  Attics  and  concealed  spaces:  Attics  and 
concealed  roof  spaces  shall  be  provided  with 
draftstopping  as  specified  in  780  CMR  720  7.2.1 
and  720.7.2.2. 

720.7.2.1  Use  Group  R:  In  occupancies  in 
Use  Group  R  in  attics,  mansards,  overhangs 
or  other  concealed  roof  spaces,  draftstopping 
shall  be  installed  above,  and  in  line  with, 
tenant  and  dwelling  unit  separation  walls  that 
do  not  extend  to  the  underside  of  the  roof 
sheathing  above. 
Exceptions: 

1 .  Where  corridor  walls  provide  a  tenant 
or  dwelling  unit  separation,  draftstopping 
shall  only  be  required  above  one  of  the 
corridor  walls. 

2.  Flat  roofs  with  solid  joist  construction 
are  not  required  to  be  provided  with 
draftstopping  over  tenant  and  dwelling 
unit  separation  walls  if  the  joists  form  a 
draftstop. 

3.  Draftstopping  is  not  required  in 
buildings  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1  or 
906.2.2,  provided  that  automatic 
sprinklers  are  also  installed  in  attics, 
mansards,  overhangs  and  other 
concealed  roof  spaces  of  combustible 
concealed  space. 

4.  Draftstopping  is  not  required  in 
detached  one-  and  two-family  dwellings. 

5.  In  occupancies  in  Use  Group  R-2 
which   do   not   exceed   four  stories   in 


height,     the     attic     space     shall     be 
subdivided  by  draftstops  into  areas  not 
exceeding  3,000  square  feet  (279  nr)  or 
above     every     two     dwelling     units, 
whichever  is  smaller. 
720.7.2.2  Other  use  groups:  Draftstopping 
shall  be  installed  in  attics  and  concealed  roof 
spaces,  such  that  any  horizontal  area  does 
not  exceed  3,000  square  feet  (279  m  ). 
Exceptions: 

1 .  Flat  roofs  with  solid  joist  construction 
are  not  required  to  be  provided  with 
draftstopping  over  tenant  separation 
walls  if  the  joists  form  a  draftstop. 

2.  Draftstopping  is  not  required  in 
buildings  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1  or 
906.2.2,  provided  that  automatic 
sprinklers  are  also  installed  in  attics  and 
other  concealed  roof  spaces  of 
combustion  construction. 

720.8  Ventilation:  Ventilation  of  concealed  roof 
spaces  shall  be  maintained  in  accordance  with 
780  CMR  1210.0. 

780  CMR  721.0  FERERESISTTVE 
REQUIREMENTS  FOR  PLASTER 

721.1  Thickness  of  plaster:  The  required  thickness 
of  fireresistance  rated  plaster  protection  shall  be 
determined  by  the  prescribed  fire  tests  for  the 
specified  use  group  and  type  of  construction  and  in 
accordance  with  the  provisions  of  7S0  CMR  2505.0 
for  interior  plastering  and  780  CMR  2506.0  for 
exterior  plastering.  The  thickness  in  all  cases  shall 
be  measured  from  the  face  of  the  lath  where  applied 
to  gypsum  lath  or  metal  lath. 

721.2  Plaster  equivalents:  For  fireresistive 
purposes,  Vi  inch  (13  mm)  of  unsanded  gypsum 
plaster  shall  be  deemed  equivalent  to  3A  inch  (19 
mm)  of  one-to-three  sanded  gypsum  or  one  inch  (25 
mm)  of  Portland  cement  sand  plaster. 

721.3  Noncombustible  furring:  In  buildings  of 
Types  1  and  2  construction,  plaster  shall  be  applied 
directly  on  masonry  or  on  approved  noncombustible 
plastering  base  and  furring. 

721.4  Double  reinforcement:  Except  in  solid 
plaster  partitions,  or  where  otherwise  determined  by 
the  prescribed  fire  tests,  plaster  protection  more  than 
one  inch  (25  mm)  in  thickness  shall  be  reinforced 
with  an  additional  layer  of  approved  lath  embedded 
at  least  3A  inch  (19  mm)  from  the  outer  surface  and 
fixed  securely  in  place. 

721.5  Plaster    alternatives    for    concrete:     In 

reinforced  concrete  construction,  gypsum  or  portland 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


141 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


cement  plaster  is  permitted  to  be  substituted  for  Vi 
inch  (13  mm)  of  the  required  poured  concrete 
protection,  except  that  a  minimum  thickness  of  3/s 
inch  (ten  mm)  of  poured  concrete  shall  be  provided 
in  all  reinforced  concrete  floors  and  one  inch  (25 
mm)  in  reinforced  concrete  columns  in  addition  to 
the  plaster  finish.  The  concrete  base  shall  be 
prepared  in  accordance  with  780  CMR  2506.0. 

780  CMR  722.0  THERMAL-  AND 
SOUND-INSULATING  MATERIALS 

722.1  General:  Insulating  batts,  blankets,  fills  or 
similar  types  of  materials — other  than  fiberboard  and 
foam  plastic  insulation  — including  vapor  retarders 
and  breather  papers  or  other  coverings  which  are 
incorporated  in  construction  elements,  shall  be 
installed  as  required  by  780  CMR  722.0.  Fiberboard 
insulation  shall  be  installed  as  required  by  780  CMR 
2309.0,  and  foam  plastic  insulation  shall  be  installed 
as  required  by  780  CMR  2603.0. 

722.2  Exposed  installations:  Such  materials,  where 
exposed  as  installed  in  rooms  or  spaces,  including 
attics  and  crawl  spaces  of  buildings  of  any  type 
construction,  shall  have  a  flame  spread  rating  of  25 
or  less  and  a  smoke-developed  rating  of  450  or  less 
when  tested  in  accordance  with  ASTM  E84  listed  in 
Appendix  A.  Plenum  installations  shall  comply  with 


the  requirements  of  780  CMR  2805.0  and  the 
mechanical  code  listed  in  Appendix  A. 

722.3  Concealed  installations:  Insulating  materials, 
where  concealed  as  installed  in  buildings  of  any  type 
of  construction,  shall  have  a  flame  spread  rating  of 
75  or  less  and  a  smoke-developed  rating  of  450  or 
less  when  tested  in  accordance  with  ASTM  E84 
listed  in  Appendix  A. 

722.3.1  Facings:  All  vapor  retarders,  whether 
integral  or  applied  separately,  shall  be  installed 
on  the  warm  side  of  the  building  element,  and 
shall  have  a  permeance  not  exceeding  one  perm. 
Where  insulation  materials  are  installed  in 
concealed  spaces  (such  as  wall,  floor  or  ceiling 
cavities),  attics  or  crawl  spaces  in  buildings  of 
Types  3,  4  and  5  construction,  the  flame  spread 
and  smoke-developed  rating  limitations  do  not 
apply  to  facings,  provided  that  the  facing  is 
installed  behind  and  in  substantial  contact  with 
the  unexposed  surface  of  the  ceiling,  floor  or 
wall  finish. 

722.4  Cellulosic  insulation:  Cellulosic  insulation 
shall  meet  the  requirements  of  CPSC  16  CFR  Parts 
1209  and  1404,  listed  in  Appendix  A. 


142 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  8 


INTERIOR  FINISHES 


780  CMR  801.0  GENERAL 

801.1  Scope:  Interior  finish  and  trim  of  buildings 
shall  conform  to  the  requirements  of  780  CMR  8. 
Interior  finish  shall  include  all  wall,  ceiling  and  floor 
finishes  and  wainscoting  and  paneling  or  other  finish 
applied  structurally  or  for  acoustical  treatment, 
insulation,  decoration  or  similar  purposes. 

801.2  Installation  and  classification  All  materials 
which  are  required  to  restrict  the  spread  of  flame  or 
to  be  flameresistant  under  the  provisions  of 
780  CMR  -  including,  but  not  limited  to,  interior 
finish  materials,  fireretardant-treated  wood,  tents  and 
tarpaulins,  and  interior  hangings  and  decorations 
shall  meet  the  requirements  for  installation  and 
classification  as  determined  by  the  applicable  test 
procedures  listed  in  780  CMR  8. 

780  CMR  802.0  DEFINITIONS 
802.1   General:   The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  8  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Flame  spread:  The  propagation  of  flame  over  a 
surface. 

Flame  spread  rating:  The  measurement  of  flame 
spread  on  the  surface  of  materials  or  their 
assemblies  as  determined  by  the  tests  specified  in 
780  CMR  (see  780  CMR  803.0). 

Flameresistance:  That  property  of  materials  or 
combinations  of  component  materials  which 
restricts  the  spread  of  flame  as  determined  by  the 
flameresistance  tests  specified  in  780  CMR  (also 
see  780  CMR  807.2). 

Floor  finish  The  finish  placed  on  top  of  the  floor, 
slab  or  other  structural  floor  element. 

780  CMR  803.0  INTERIOR  FINISH 
AND  TRIM 

803.1  Exposed  construction:  These  requirements 
shall  not  be  considered  as  requiring  the  installation 
of  interior  finish,  but  where  construction  or  fire 
protection  materials  are  exposed  in  the  use  groups 
specified  in  780  CMR  803.4,  the  hazard  from  rate  of 
flame  spread  of  such  exposed  materials  shall  not  be 
greater  than  that  of  the  interior  finish  permitted  for 
such  occupancy. 

803.1.1  Paper  finish:  The  use  of  a  surface  finish 
of  paper  or  of  material  that  does  not  have  a  greater 
fire  hazard  than  paper  shall  not  be  prohibited, 


provided  that  such  finish  does  not  exceed  1/28 
inch  (I  mm)  in  thickness  and  is  applied  directly  to 
a  noncombustible  base  or  substrate  that  conforms 
to  the  requirements  of  780  CMR  2310.0. 

803.1.2  Type  4  construction  Exposed  portions 
of  structural  members  complying  with  the 
requirements  for  buildings  of  Type  4  construction 
in  780  CMR  605.0  and  2304.0,  shall  not  be 
subject  to  interior  finish  regulations. 

803.1.3  Window  exception:  Show  windows  in 
the  first  story  of  buildings  are  permitted  to  be 
constructed  of  any  approved  materials 

803.2  Classification  All  materials  used  for  interior 
finish  and  trim  shall  be  classified  in  accordance  with 
ASTM  E84  listed  in  Appendix  A  The 
classifications  of  interior  finishes  referred  to  herein 
correspond  to  flame  spread  ratings  determined  by 
ASTM  E84  listed  in  Appendix  A  as  follows:  Class  I 
flame  spread,  0  -  25;  Class  II  flame  spread,  26  -  75; 
Class  IE  flame  spread,  76  -  200. 

803.3  Materials:  Materials  shall  only  be  installed  as 
interior  finish  and  trim  as  specifically  provided  for 
in  780  CMR  for  the  occupancy  of  the  space  in  which 
the  material  is  installed.  Installation  of  any  materia! 
for  floor  finish,  interior  finish  and  trim  in  a  building 
of  Type  1  or  2  construction  within  the  scope 
permitted  in  780  CMR  803.0  or  in  780  CMR  806.0 
shall  not  declassify  the  building  with  respect  to  the 
type  of  construction  classification. 

803.3.1  Foam  plastics:  Foam  plastics  shall  not  be 
installed  as  interior  trim  or  finish  except  in 
compliance  with  780  CMR  803.0  and  780  CMR 
2603". 0. 

803.3.2  Smoke  development:  Interior  wall  and 
ceiling  finish  materials  that  have  a  smoke- 
developed  rating  greater  than  450  when  tested  in 
accordance  with  ASTM  E84  listed  in  Appendix  A 
shall  not  be  permitted. 

803.4  Required  flame  spread  rating:  Interior  finish 
of  walls  and  ceilings  shall  have  a  flame  spread  rating 
not  greater  than  that  designated  by  the  class 
prescribed  for  the  various  use  groups  listed  in  Table 
803.4,  when  tested  in  accordance  with  780  CMR 
803.2. 

803.4.1  Basements:  In  occupancies  other  than 
Use  Group  R-3,  Class  I  or  II  interior  finish  shall 
be  required  in  all  basements  or  other  underground 
spaces  from  which  there  is  not  direct  exit  to  the 
outside  of  the  building,  if  subject  to  occupancy  for 
any  purpose  other  than  storage  or  service 
facilities. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


143 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


803.4.2  Maximum  flame  spread:  Interior  finish 
materials  with  flame  spread  classifications  greater 
than  200  shall  not  be  installed  in  any  room  or 
space  subject  to  human  occupancy,  except  to  such 
extent  as  specifically  approved  on  the  basis  of  a 
finding  that  such  installation  does  not 
significantly  increase  the  life  hazard. 

803.4.3  Rooms      and      enclosed      spaces 

Requirements  for  rooms  or  enclosed  spaces  are 
based  upon  spaces  enclosed  in  partitions  of  the 
building  or  structure,  and  where  a  fireresistanceis 
required  for  the  structural  elements,  the  enclosing 
partitions  shall  extend  from  the  floor  to  the 
ceiling.  Partitions  that  do  not  comply  with  this 
shall  be  considered  as  enclosing  spaces  and  rooms 
or  spaces  on  both  sides  thereof  shall  be  counted  as 
one.  In  determining  the  applicable  requirements 
for  rooms  or  enclosed  spaces,  the  specific 
occupancy  thereof  shall  be  the  governing  factor, 
regardless  of  the  use  group  classification  of  the 
building  or  structure  Where  an  automatic 
sprinkler  system  installed  in  accordance  with 
780  CMR  906.2.1  or  906.2.2  is  installed 
throughout  a  building,  Class  II  or  III  interior 
finish  shall  be  permitted  where  Class  I  or  II 
materials,  respectively,  are  required  in  Tabie 
803.4. 

Table  803.4 
INTERIOR  FINISH  REQUIREMENTS8 

Required 

vertical         Corridors       Rooms  or 
Use  Group  exits  and        providing       enclosed 

passage-        exjt  access        spaces 
wavs 


A-I.  A-2.A-3 

I 

ie 

nb 

A-4,B,E,E,1-], 

E 

in 

R-LR-2 

1 

in 

H 

II 

1-2 

h 

ih 

!h 

1-3 

i 

III 

M:  walls 

,  ii 

m„" 

ceilings 

n 

R-3 

m 

m 

in 

S 

n 

n 

m 

Note  a.  For  requirements  applicable  to  rooms  and 
enclosed  spaces,  see  780  CMR  803.4.3. 

Note  b.  Class  III  interior  finish  materials  are  permitted 
in  places  of  assembly  with  a  capacity  of  300  persons  or 
less. 

Note  c.  Class  III  interior  finish  materials  are  permitted 
for  wainscoting  or  paneling  for  not  more  than  1,000 
square  feet  (93m2)  of  applied  surface  area  in  the  grade 
lobby  where  applied  directly  to  a  noncombustible  base  or 
over  furring  strips  applied  to  a  noncombustible  base  and 
firestopped  as  required  by  780  CMR  804.0. 

Note  d.  Class  EH  interior  finish  materials  are  permitted 
in  mercantile  occupancies  of  3,000  square  feet  (279m  ) 
or  less  gross  area  occupied  for  sales  purposes  on  the 
street  floor  only  (balcony  permitted). 

Note  e.  Lobby  areas  shall  not  be  less  than  Class  II 


Note  f.  Where  building  height  is  over  two  stones. 
Class  II  shall  be  required. 

Note  g.  For  the  classifications  of  interior  finishes 
referred  to  herein,  see  780  CMR  803.2.  For  interior 
finish  requirements  for  exposed  insulation,  see  780  CMR 
722.2. 

Note  h  Walls  and  ceilings  shall  be  a  minimum  of 
Class  11  materials  in  individual  rooms  of  not  more  than 
four  persons  in  capacity  Where  a  building  is  equipped 
throughout  with  an  automatic  sprinkler  system  installed 
in  accordance  with  780  CMR  906.2.1  the  minimum 
requirement  for  interior  finish  shall  be  Class  II. 

Note  i.  In  Use  Groups  A.  1-2  and  1-3.  Class  II  ulterior 
wall  finish  material  shall  be  permitted  as  wainscoting 
extending  not  more  than  48  inches  (1219  mm)  above  the 
floor  in  corridors  providing  exit  access. 

803.5  Interior  trim  Baseboards,  chair  rails, 
moldings,  trim  around  openings  and  other  interior 
trim,  not  in  excess  of  10%  of  the  aggregate  wall  and 
ceiling  areas  of  any  room  or  space,  shall  be  of  Class 
I,  II  or  III  materials 

803.6  Carpet  and   carpet-like   wall   coverings 

Textile  wall  coverings  having  a  napped,   tufted. 

looped,  woven,  nonwoven  or  similar  surface,  shall 

comply  with  the  following: 

\  Such  materials  shall  have  a  Class  I  flame 
spread  classification  and  be  installed  only  in 
rooms  or  areas  protected  by  an  automatic 
sprinkler  system  installed  in  accordance  with 
780  CMR  9;  or 

2  Such  materials  shall  be  tested  in  accordance 
with  an  eight-foot  by  12-foot  by  eight-foot  high 
(2438  mm  by  3658  mm  by  2438  mm)  room/comer 
fire  test  procedure  utilizing  a  product-mounting 
system,  including  adhesive,  representative  of 
actual  installation  Prior  to  testing,  the  sample 
shall  be  conditioned  at  70°F  (21  °C)  ±  5%  and  at 
a  relative  humidity  of  50%  ±  5%  until  the  sample 
reaches  a  rate  of  weight  change  of  less  than  0. 1% 
per  day.  The  product  shall  be  exposed  to  a  flame 
from  a  gas  diffusion  burner  for  1 5  minutes.  The 
fire  exposure  shall  be  40  kW  for  the  first  five 
minutes,  followed  by  an  exposure  of  1 50  kW  for 
an  additional  ten  minutes.  Such  tests  shall 
demonstrate  that  a  product  will  not  spread  fire  to 
the  edge  of  the  specimen  or  cause  flashover  in  the 
test  room 

803.7  Design  load:  Interior  wall  finish  materials 
shall  be  capable  of  resisting  the  horizontal  load 
specified  in  780  CMR  1615  4 

780  CMR  804.0  APPLICATION  OF 
INTERIOR  FINISH 

804.1  Attachment:  Where  interior  finish  is 
regulated  by  the  requirements  of  780  CMR  8, 
interior  finish  materials  shall  be  applied  or  otherwise 
fastened  in  such  a  manner  that  such  materials  will 
not  readily  become  detached  when  subjected  to 


144 


780  CMR  -  Sixth  Edition    corrected  -  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 

INTERIOR  FINISHES 


room  temperatures  of  200°F  (93  °C)  for  not  less  than 
30  minutes. 

804.2  Fireresistive  and  noncombustible 
construction:  Interior  finish  materials  installed  on 
walls,  ceilings  or  structural  elements  which  are 
required  to  provide  a  fireresistance  rating  or  to  be  of 
noncombustible  construction,  shall  comply  with  the 
provisions  of  780  CMR  804.2.1  or  804.2.2. 

804.2.1  Application   to   structural   elements: 

Interior  finish  materials  applied  to  walls,  ceilings 
or  structural  elements  shall  be  applied  directly 
against  the  exposed  surface  of  such  structural 
elements  or  to  furring  attached  to  such  surfaces. 
In  concrete  or  masonry  construction,  furring  of 
wood  or  any  other  material  of  similar  combustible 
characteristics  is  permitted.  All  concealed  spaces 
created  by  furring  shall  bsfirestopped  at  not  more 
than  ten-foot  (3048  mm)  intervals  in  any  direction 
(see  780  CMR  720.6.6). 

804.2.2  Set-out  construction:  Where  the  interior 
finish  is  set  out  or  dropped  distances  greater  than 
V/t  inches  (44  mm)  from  the  surface  of  such 
elements,  only  material  of  which  both  faces 
qualify  as  Class  I  shall  be  installed. 

Exceptions: 

1.  In  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2. 1  or  906.2.2, 
Class  II  finish  materials  shall  be  permitted 
provided  that  automatic  sprinklers  are  also 
installed  in  combustible  concealed  spaces 
behind  the  interior  finish. 

2.  Class  II  or  III  materials  shall  be  permitted 
where  attached  to  a  backing  that  complies  with 
780  CMR  804.3  or  to  furring  applied  directly 
to  such  backing  as  provided  for  in  780  CMR 
804.2.1. 

804.3  Class  II  and  III  materials:  Class  II  and  III 

interior  finish  materials  which  are  less  than  Vt  inch 
in  thickness  shall  be  applied  directly  against  a 
noncombustible  backing  or  a  backing  that  complies 
with  the  requirements  of  780  CMR  2310.0,  unless 
the  tests  under  which  such  material  has  been 
classified  were  made  with  the  materials  suspended 
from  the  noncombustible  backing.  The  backing 
material  shall  provide  a  continuous  surface 
completely  behind  the  finish.  Where  the  backing 
does  not  constitute  an  integral  part  of  the  structural 
elements  or  system,  the  backing  shall  be  attached 
directly  to  the  structural  elements  or  to  the  furring  as 
required  for  the  application  of  finish  in  780  CMR 
804  2,  or  shall  be  suspended  from  the  structural 
members  at  any  distance  and  all  concealed  spaces 
created  thereby  shall  be  firestopped  in  accordance 
with  780  CMR  720.0. 

804.4  Type  4  construction:  Interior  finish  materials 
shall  be  applied  directly  to  the  wood  members  and 


decking  of  buildings  of  Type  4  construction,  or  to 
furring  strips  applied  to  such  members  or  wood 
decking  as  provided  for  in  780  CMR  804.2.1. 

780  CMR  805.0  FLOOR  FINISH 

805.1  General:  Finished  floors  or  floor  covering 
materials  of  a  traditional  type,  such  as  wood,  vinyl, 
linoleum,  terrazzo  and  other  resilient  floor  covering 
materials,  are  exempt  from  the  requirements  of 
780  CMR  805.0.  Floor  coverings  judged  by  the 
code  official  to  represent  an  unusual  hazard  shall 
meet  the  requirements  of  780  CMR  805.0. 

805.2  Classification:  Interior  floor  finish  required 
by  780  CMR  805.3  to  be  of  Class  I  or  Class  II 
materials  shall  be  classified  in  accordance  with 
ASTM  E648  listed  in  Appendix  A.  The 
classifications  referred  to  herein  correspond  to  the 
classifications  determined  by  ASTM  E648  listed  in 
Appendix  A  as  follows:  Class  I,  0.45  watts/cm2, 
Class  II,  0.22  watts/cm2. 

805.2.1  Test  report:  All  carpet  required  by 
780  CMR  805.0  to  meet  critical  radiant  flux 
limitations  in  accordance  with  780  CMR  805.2 
shall  be  tested  by  an  approved  agency.  A  copy  of 
the  test  report  identifying  and  representing  the 
style  to  be  installed  shall  be  provided  to  the  code 
official  upon  request.  The  test  report  shall 
identify  the  carpet  by  manufacturer  (or  supplier) 
and  style  name,  and  shall  be  representative  of  the 
current  construction  of  the  carpet. 

The  carpet  shall  be  identified  as  to 
manufacturer  (or  supplier)  and  style  by  a  hang  tag 
or  other  suitable  method,  which  shall  indicate  the 
classification  of  the  material  based  upon  the 
limitations  specified  in  780  CMR  805.2. 

805.3  Required  classification:  Interior  floor  finish 
in  vertical  exits,  exit  passageways  and  exit  access 
corridors  shall  not  be  less  than  Class  I  in  Use  Group 
1-2  and  not  less  than  Class  II  in  Use  Groups  A,  B,  E, 
1-1,  1-3,  M,  R-l  and  R-2.  In  all  other  areas,  the 
interior floor  finish  shall  comply  with  the  DOC  FF-1 
"pill  test"  (CPSC  16  CFR,  Part  1630)  listed  in 
Appendix  A. 

Exception:  Where  a  building  is  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2.1  or  906.2.2, 
Class  II  materials  are  permitted  in  any  area  where 
Class  I  materials  are  required  and  materials 
complying  with  the  DOC  FF-1  "pill  test"  (CPSC 
16  CFR,  Part  1630)  listed  in  Appendix  A  are 
permitted  in  any  area  where  Class  II  materials  are 
required. 

805.4  Rooms  and  enclosed  spaces:  Requirements 
for  rooms  or  enclosed  spaces  are  based  upon  the 
spaces  being  enclosed  with  partitions  extending  from 
the  floor  to  the  ceiling  Where  partitions  do  not 
satisfy  this  criterion,  the  room  or  space  is  considered 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


145 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


part  of  the  corridor. 

805.5  Other  materials:  All  carpet  manufactured  for 
sale  in  the  United  States  is  required  by  federal 
regulations  to  pass  the  DOC  FF-1  "pill  test"  (CPSC 
16  CFR  Part  1630)  listed  in  Appendix  A.  If  a 
material  other  than  carpet  is  installed,  the  material 
shall  be  shown  to  be  at  least  as  resistant  to  flame 
propagation  as  a  material  which  passes  DOC  FF-1 
(minimum  critical  radiant  flux  of  0.04  watts/cm2). 

780  CMR  806.0  COMBUSTIBLE  MATERIALS 

PERMITTED  IN  FLOORS  OF  TYPES  1  AND  2 

CONSTRUCTION 

806.1  General:  Except  as  provided  for  in  780  CMR 
1014.0  for  stairways  and  in  780  CMR  412.0  for 
stages  and  platforms,  combustible  materials  installed 
in  or  on  floors  of  buildings  of  Types  1  and  2 
construction  shall  be  as  herein  specified. 

806.2  Sleepers,  bucks  and  grounds:  Floor  sleepers, 
bucks,  nailing  blocks  and  grounds  shall  not  be 
constructed  of  combustible  materials,  unless  the 
space  between  the  fireresistance  rated  floor 
construction  and  the  flooring  is  either  solidly  filled 
with  approved  noncombustible  materials  or 
firestopped  in  accordance  with  780  CMR  720.6.7, 
and  provided  that  such  open  spaces  shall  not  extend 
under  or  through  permanent  partitions  or  walls. 

806.3  Flooring:  Wood  finish  flooring  is  permitted  to 
be  attached  directly  to  the  embedded  ox  firestopped 
wood  sleepers,  and  shall  be  permitted  where 
cemented  directly  to  the  top  surface  of  approved 
fireresistance  rated  construction  or  directly  to  a 
wood  subfloor  attached  to  sleepers  as  provided  for  in 
780  CMR  806.2.  Combustible  insulating  boards  not 
more  than  V2  inch  thick  and  covered  with  approved 
finished  flooring  are  permitted  for  sound  deadening 
or  heat  insulating  where  attached  directly  to  a  non- 
combustible  floor  assembly  or  to  wood  subflooring 
attached  to  sleepers  as  provided  for  in  780  CMR 
806.2. 


780  CMR  807.0  INTERIOR  HANGEVGS 
AND  DECORATIONS 

807.1  Decorative     material     restrictions:     In 

occupancies  in  Use  Groups  A,  E,  1-2,  1-3  and  R-l,  all 
curtains,  draperies,  hangings  and  other  decorative 
materials  suspended  from  walls  or  ceilings  shall  be 
noncombustible  or  be  maintained  flameresistant  in 
accordance  with  780  CMR  807.2  as  herein  specified 
and  527  CMR  21. 00  as  listed  in  Appendix  A. 

807.1.1  Noncombustible:  The  permissible 
amount  of  non-combustible  decorative  hangings 
shall  not  be  limited. 

807.1.2  Flameresistant:  The  permissible  amount 
of  flameresistant  decorative  hangings  shall  not 
exceed  10%  of  the  total  wall  and  ceiling  area. 

807.2  Acceptance  criteria:  Where  required  to  be 
flameresistant  under  the  provisions  of  780  CMR  all 
materials  used  for  artistic  enhancement,  decorations, 
draperies,  curtains,  scenery  and  hangings  shall 
comply  with  780  CMR  807.0.  If  treated  to  be 
flameresistant,  these  materials  shall  not  generate 
smoke  more  dense  than  that  given  off  by  untreated 
wood  or  paper  burning  under  comparable  conditions 
when  tested  in  accordance  with  both  the  small-scale 
and  large-scale  tests  in  NFLPA  701  listed  in 
Appendix  A. 

807.2.1  Limitation  of  approval:  All  approvals  of 
organic  decorative  material  shall  be  limited  to  one 
year.  The  owner  or  the  owner's  authorized  agent 
shall  file  an  affidavit  with  the  code  official  which 
certifies  that  the  process  and  materials  utilized 
comply  with  780  CMR  and  which  states  the  date 
of  treatment  and  the  warranted  period  of 
effectiveness  of  the  process. 

807.2.2  Field   test   for  decorative   materials: 

Where  documented  certification  of 
flameresistance  is  not  provided,  the  code  official 
shall  subject  decorative  materials  that  are  required 
to  be  flameresistant  to  a  field  test  in  accordance 
with  Chapter  10  of  NFiPA  701  listed  in 
Appendix  A. 

807.2.3  Replacement  of  defective  materials:  All 

treated  hangings,  draperies,  canvas  and  other 
decorative  and  tent  materials  which  fail  to 
conform  to  the  field  test  requirements  shall  be 
retreated  or  replaced  by  an  approved  installation. 


146 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  9 


FIRE  PROTECTION  SYSTEMS 
(This  Chapter  is  Entirely  Unique  to  Massachusetts) 


780  CMR  901.0  GENERAL 

901.1  Scope:  The  provisions  of  780  CMR  9  shall 
specify  where  fire  protection  systems  are  required 
and  shall  apply  to  the  design,  installation, 
maintenance  and  operation  of  all  fire  protection 
systems  in  all  buildings  and  structures. 

901.1.1  Seismic  Requirements:  All  "required" 
and  "non-required"  fire  protection  systems  shall 
be  installed  in  accordance  with  the  Seismic 
Criteria  requirements  of  780  CMR  1612.7, 
Architectural,  Mechanical  and  Electrical 
Components  and  Systems. 

901.2  Required  systems:  All  fire  protection  systems 
required  by  780  CMR  shall  be  installed,  repaired, 
operated  and  maintained  in  accordance  with  this 
code  and  the  applicable  reference  standards  listed  in 
Appendix  A.  All  required  fire  suppression  and 
standpipe  systems  shall  be  provided  with  at  least  one 
automatic  supply  of  fire-extinguishing  agent  of 
adequate  pressure,  capacity  and  reliability  to 
perform  the  function  intended. 

901.3  Nonrequired  systems:  Any  fire  protection 
system  or  portion  thereof  not  required  by  780  CMR 
shall  be  permitted  to  be  finished  for  partial  or 
complete  protection  provided  that  such  installed 
system  meets  applicable  requirements  of  780  CMR. 
A  building  permit  shall  be  required  for  systems 
installed  pursuant  to  780  CMR  901.3 

901.4  Maintenance:  All  water  based  fire  protection 
systems  shall  be  maintained  in  accordance  with 
NFPA  25  as  listed  in  Appendix  A.  All  other  fire 
protection  systems  shall  be  maintained  in  accordance 
with  the  requirements  of  the  applicable  reference 
standards  and  standards  listed  in  Appendix  A.  The 
owner,  tenant  or  lessee  of  every  building  or  structure 
shall  be  responsible  for  the  care  and  maintenance  of 
all  fire  protection  systems,  including  equipment  and 
devices,  to  ensure  the  safety  and  welfare  of  the 
occupants.  Fire  protection  systems  shall  not  be 
disconnected  or  otherwise  rendered  unserviceable 
without  first  notifying  the  local  fire  department  in 
accordance  with  M.G.L.  c.  148  §  27A. 

When  installations  of  fire  protection  systems  are 
interrupted  for  repairs  or  other  necessary  reasons, 
the  owner,  tenant  or  lessee  shall  immediately  advise 
the  local  fire  department  and  shall  diligently 
prosecute  the  restoration  of  the  protection. 

901.5  Threads:  All  threads  provided  for  fire 
department    connections    to    sprinkler    systems. 


standpipes,  yard  hydrants  or  any  other  fire  hose 
connection  shall  be  compatible  with  the  connections 
used  by  the  local  fire  department. 

901.6  Signs:  All  signs  required  to  identify  fire 
protection  equipment,  equipment  rooms  and 
equipment  locations  shall  be  constructed  of  durable 
materials,  be  permanently  installed  and  be  readily 
visible.  Letters  and  numbers  shall  contrast  with  the 
sign  background,  shall  be  at  least  two  inches  in 
height  and  shall  have  an  appropriate  width-t'o-height 
ratio  to  permit  the  sign  to  be  read  easily  from  a 
distance  of  ten  feet.  The  sign  and  location  shall  be 
approved  by  the  local  fire  department. 

Exception:  See  also  780  CMR  906.8  for  entrance 
doors  to  sprinkler  control  valve  rooms. 

780  CMR  902.0  DEFINITIONS 
902.1   General:   The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  9  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Alarm  verification:  A  feature  of  automatic  fire 
detection  systems  to  reduce  unwanted  alarms 
wherein  automatic  fire  detectors  report  alarm 
conditions  for  a  minimum  period  of  time,  or 
confirm  alarm  conditions  within  a  given  period, 
after  being  automatically  reset  to  be  accepted  as  a 
valid  alarm  initiation  signal  (see  780  CMR  918.0). 

Approval/Permit  To  Install:  The  term  refers  to 
permits  outside  the  jurisdiction  of  the  building 
official,  issued  under  authority  of  M.G.L.  c.  148, 
§  10Aor527CMR. 

Authority  Having  Jurisdiction:  The  term 
"Authority  Having  Jurisdiction"  as  used  in  the 
NFPA  Standards  as  referenced  in  780  CMR  9, 
shall  mean  the  building  official  for  enforcement  of 
780  CMR  and  the  BBRS  for  interpretation,  waiver 
or  variences  (see  780  CMR  122.0,  see  official 
interpretation  number  35-94  listed  in  Appendix  B) 

Automatic:  As  applied  to  fire  protection  devices, 
automatic  refers  to  a  device  or  system  that 
provides  an  emergency  function  without  the 
necessity  of  human  intervention  and  activated  as 
a  result  of  a  predetermined  temperature  rise,  rate 
of  temperature  rise  or  increase  in  the  level  of 
combustion  products  -  such  as  incorporated  in  an 
automatic  sprinkler  system,  automatic  fire  door, 
etc. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


147 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Automatic  fire  suppression  system:  An  engineered 
system  using  carbon  dioxide  (CO,),  foam,  wet  or 
dry  chemical,  a  halogenated  extinguishing  agent, 
or  an  automatic  sprinkler  system  to  detect 
automatically  and  suppress  a  fire  through  fixed 
piping  and  nozzles  (see  780  CMR  904.0). 

Construction  Documents:  As  defined  in  780  CMR  2. 

Deluge  system:  An  automatic  sprinkler  system 
consisting  of  open  sprinklers  with  water  supply 
valves  activated  by  a  separate  automatic  detection 
system  (see  780  CMR  908.0). 

Detector,  heat:  An  alarm-initiating  device  that 
detects  abnormally  high  temperature  or  rate  of 
temperature  rise  (see  780  CMR  918.0). 

Detector,  smoke:  An  alarm-initiating  device  that 
detects  the  visible  or  invisible  particles  of 
combustion  (see  780  CMR  918.0). 

Emergency    Voice/alarm    signaling    system:    A 

system  that  provides,  to  the  occupants  of  a 
building,  dedicated  manual  or  automatic  facilities, 
or  both,  for  originating  and  distributing  voice 
instructions,  as  well  as  alert  and  evacuation 
signals  that  pertain  to  a  fire  emergency  (see 
780  CMR  917.0). 

Fire  alarm  box,  manual:  A  manually  operated 
alarm-initiating  device  that  activates  a  fire 
protective  signaling  system  (see  780  CMR  917.0). 

Fire  command  station:  (Fire  command  center)  The 
principal  location  where  the  status  of  the 
detection,  alarm,  communications  and  control 
systems  is  displayed,  and  from  which  the 
system(s)  has  the  capability  for  manual  control 
(see  780  CMR  403.7  and  917.9). 

Fire  Department  Designee:  An  individual 
authorized  by  the  chief  of  the  fire  department  to 
review  and  approve  fire  protection  system  plans 
and  installation. 

Fire  detector,  automatic:  An  alarm-initiating  device 
that  automatically  detects  heat,  smoke  or  other 
products  of  combustion  (see  780  CMR  918.0). 

Fire      Protection      Construction      Documents: 

Documents  containing  the  requirements  of 
780  CMR  903.1.1,  903.1.2,  903.1  .3. 

Fire  protection  system:  Devices,  equipment  and 
systems  used  to  detect  a  fire,  activate  an  alarm, 
suppress  or  control  a  fire,  or  any  combination 
thereof. 

Fire  Protective  Signaling  System  (Fire  Alarm 
System):  A  system  or  portion  of  a  combination 


system  consisting  of  components  and  circuits 
arranged  to  monitor  and  annunciate  the  status  of 
fire  alarm  or  supervisory  signal  initiating  devices 
and  to  initiate  appropriate  response  to  those 
signals. 

Household  Fire  Warning  System:  A  household 
fire  warning  system  consists  of  single  or  multiple 
station  detectors  or  a  listed  control  unit  with 
automatic  fire  detectors  and  occupant  notification 
appliances.  The  household  fire  warning  system 
serves  only  one  dwelling  unit,  patient  room,  hotel 
room  or  other  single  area  depending  on  use  group 
requirements  in  780  CMR  9 19.1  through  919.3 

Installing  Contractor:  An  individual  or  firm  duly 
licensed  to  install  fire  protection  systems.  (See 
780  CMR  903.3) 

•  Automatic  Sprinklers  Systems  -  M.G.L. 
c.  146,  §§ 81  through  85 A,  528  CMR  12.00 

•  Fire  Extinguishing  systems  -  M.G.L.  c.  148, 
§§58,  527 CMR 23.00 

•  Fire  Alarm  Systems  -  M.G.L.  c.  141,  §§  I 
through  10,  M.G.L  c.  143,  §  3L  to  3P 
237  CMR  1. 00  through  6. 00 

Maintenance     of    Fire     Protections     Systems: 

Replacement  or  repair  of  any  component  or 
components  of  a  fire  protection  system,  where 
such  does  not  effect  system  performance  and 
compatibility.  (Also      see     Modifications, 

Alterations,  Additions  or  Deletions  to  Fire 
Protection  Systems).  No  building  permit  is 
required  for  maintenance.  Other  permits, 
however,  may  be  required  pursuant  to  M.G.L. 
c.148,  §  27A  and  527  CMR. 

Modifications,  Alterations,  Additions  or  Deletions 
to  Fire  Protection  Systems:  Any  changes  which 
effect  the  performance  of  the  fire  protection 
system.  (Also  see  maintenance).  Such  changes 
require  a  building  permit  and  are  subject  to  other 
permitting  requirements  pursuant  to  M.G.L. 
c.  148,  §  27A. 

Master  Box:  A  municipal  fire  alarm  box  that  may 
also  be  operated  by  remote  means. 

Municipal  Fire  Alarm  System:  A  system  of  alarm 
initiating  devices,  receiving  equipment,  and 
connecting  circuits  (other  than  a  public  telephone 
network)  used  to  transmit  alarms  from  street 
locations  to  the  public  fire  service 
communications  center. 

Preaclion  system:  A  fire  sprinkler  system  employing 
automatic  sprinklers  attached  to  a  piping  system 
containing  air  with  a  supplemental  fire  detection 
system  installed  in  the  same  areas  as  the 
sprinklers.  Actuation  of  the  fire  detection  system 
automatically  opens  a  valve  that  permits  water  to 


148 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


flow  into  the  sprinkler  piping  system  and  to  be 
discharged  from  any  open  sprinklers  (see 
780  CMR  906.9.6). 

Registered  Professional  Engineer:  A  Registered 
Professional  Engineer  registered  by  the  Board  of 
Registration  of  Professional  Engineers  and  of 
Land  Surveyors  in  accordance  with  M.G.L. 
c.  112,  §§  8 ID  through  8 IT  and  250  CMR  (see 
7S0  CMR  903.1.3  and  903.5). 

Shop  Drawings:  Scaled  detailed  working  drawings 
(system  layout)  and  equipment  specifications  (cut 
sheets)  indicating  all  information  in  accordance 
with  requirements  of  the  applicable  NFPA 
Standards  for  the  specific  fire  protection  systems 
to  be  installed  in  accordance  with  the  Registered 
Professional  Engineer's  plans  and  specifications. 

Smoke  detector,  multiple  station:  Single-station 
smoke  detectors  that  are  capable  of  being 
interconnected  such  that  actuation  of  one  causes 
all  integral  or  separate  audible  alarms  to  operate 
(see  780  CMR  919.0). 

Smoke  detector,  single  station:  An  assembly 
incorporating  the  detector,  the  control  equipment 
and  the  alarm-sounding  device  in  one  unit,  which 
is  operated  from  a  power  supply  either  in  the  unit 
or  obtained  at  the  point  of  installation  (see 
780  CMR  919.0). 

Sprinkler:  A  device,  connected  to  a  water  supply 
system,  that  discharges  water  in  a  specific  pattern 
for  extinguishment  or  control  of  fire  (see 
780  CMR  906.0). 

Sprinkler  system,  automatic:  A  sprinkler  system,  for 
fire  protection  purposes,  is  an  integrated  system  of 
underground  or  overhead  piping  designed  in 
accordance  with  fire  protection  engineering 
standards.  The  system  includes  a  suitable  water 
supply.  The  portion  of  the  system  above  the 
ground  is  a  network  of  specially  or  hydraulically 
designed  piping  installed  in  a  building,  structure 
or  area,  generally  overhead,  and  to  which 
automatic  sprinklers  are  connected  in  a  systematic 
pattern.  The  system  is  usually  activated  by  heat 
from  a  fire  and  discharges  water  over  the  fire  area 
(see  780  CMR  906.0). 

Sprinkler  system,  limited  area:  An  automatic 
sprinkler  system  consisting  of  not  more  than  20 
sprinklers  within  a  fire  area  (see  780  CMR 
907.0). 

Standpipe  system:  A  standpipe  system  is  a  fire 
protection  system  consisting  of  an  arrangement  of 
piping,  valves,  hose  outlets  and  allied  equipment 
installed  in  a  building  or  structure  (see  780  CMR 
914.0) 


Supervisory  device:  An  initiating  device  used  to 
monitor  the  conditions  that  are  essential  for  the 
proper  operation  of  automatic  fire-protection 
systems  (i.e.,  switches  used  to  monitor  the 
position  of  gate  valves,  a  low  air-pressure  switch 
on  a  dry-pipe  sprinkler  system,  etc.)  (see 
780  CMR  923.0). 

Water  supply,  automatic:  A  water  supply  that  is  not 
dependent  on  any  manual  operation,  such  as 
making  connections,  operating  valves  or  starting 
pumps  (see  780  CMR  914.5). 

780  CMR  903.0  FIRE  PROTECTION 
SYSTEMS  APPROVAL/ACCEPTANCE 

903.1  Required:  Complete  fire  protection 
construction  documents  shall  be  submitted  in 
accordance  with  780  CMR  110  and  a  building 
permit  obtained  prior  to  the  installation  of  all 
"required"  or  "non  required"  fire  protection  systems, 
including  modifications,  alterations,  additions  or 
deletions  to  an  existing  fire  protection  system.  The 
fire  protection  construction  documents  shall  contain 
sufficient  information  to  completely  describe  the  fire 
protection  systems,  including  operational  features. 
The  information  required  pursuant  to  780  CMR 
903.0  shall  include,  where  required,  the  items  listed 
in  780  CMR  903.1.1: 

Exception:    Maintenance;    no    building    permit 
required. 

903.1.1        Fire       Protection       Construction 
Documents: 

1.  Basis  (methodology)  of  design  for  the 
protection  of  the  occupancy  and  hazards  for 
compliance  with  780  CMR  and  applicable 
NFPA  Standards,  in  the  form  of  a  narrative 
report. 

2.  Building  and  site  access  for  fire  fighting 
and/or  rescue  vehicle(s)  and  personnel. 

3.  Fire  hydrant(s)  location  and  water  supply 
information. 

4.  Type/description  and  design  layout  of  the 
automatic  sprinkler  system(s). 

5.  Automatic  sprinkler  system(s)  control 
equipment  location. 

6.  Type/description  and  design  layout  of  the 
automatic  standpipe  system(s). 

7.  Standpipe  system  hose  valve(s)  type  and 
location. 

8.  Fire  department  Siamese  connection  type(s) 
and  location. 

9.  Type/description  and  design  layout  of  the 
fire  protective  signaling  system(s). 

10.  Fire  protective  signaling  system(s)  control 
equipment  and  remote  annunciator  location. 

1 1.  Type/description  and  design  layout  of  the 
smoke  control  or  exhaust  system(s). 

12.  Smoke  control  or  exhaust  system(s) 
control  equipment  location. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


149 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


13.  Building  life  safety  system  features 
(auxiliary  functions)  required  to  be  integrated 
as  part  of  the  fire  protective  signaling 
system(s). 

14.  Type/description  and  design  layout  of  the 
fire  extinguishing  system(s). 

15.  Fire  extinguishing  system(s)  control 
equipment  location. 

16.  Fire  protection  system(s)  equipment  room 
location. 

17.  Fire  protection  system(s)  equipment 
identification  and  operation  signs. 

18.  Fire  protection  system(s)  alarm/ 
supervisory  signal  transmission  method  and 
location. 

19.  Sequence  of  operation  of  all  fire  protection 
systems  and  operation  in  the  form  of  a 
narrative  report. 

20.  Testing  criteria  to  be  used  for  final  system 
acceptance  in  the  form  of  a  narrative  report. 

903.1.2  Plans:  All  fire  protection  system  plans 
shall  contain  sufficient  information  to  identify  the 
occupancy,  hazards,  system  and  equipment 
arrangements,  system  and  equipment  sizing, 
systems  specifications,  systems  sequence(s)  of 
operation  and  design/engineering  calculations. 

903.1.3  Design:  All  fire  protection  systems  and 
fire  protection  system  operation  including 
building  and  site  features  as  identified  in 
780  CMR  903.1  1  shall  be  designed  and  specified 
by  a  qualified  Registered  Professional  Engin- 
eers). All  plans  shall  bear  the  original  seal  and 
signature  of  the  Registered  Professional 
Engineer(s),  except  as  provided  in  M.G.L.  c.  143, 
§  54A  and  any  profession  or  trade  as  provided  in 
M.G.L.  c.  112,  §  60L  and  M.G.L.  c.  112,  §8 1R 
Specifications  shall  include  requirements  for  the 
preparation  of  shop  drawings  when  required  by 
780  CMR  or  applicable  NFPA  Standards.  The 
Registered  Professional  Engineer(s)  shall  be 
responsible  for  the  review  and  certify  that  all  shop 
drawings  conform  to  the  approved  fire  protection 
construction  documents  as  submitted  for  the 
building  permit  and  approved  by  the  building 
official. 

903.1.4  As-built  plans:  In  accordance  with  the 
applicable  referenced  standards,  as-built  plans 
shall  be  prepared  by  the  contractor  responsible  for 
the  installation  of  the  fire  protection  system  for 
those  occupancies  listed  in  780  CMR  923.2.1(a) 
through  (e).  As-built  plans  shall  be  provided  to 
the  owner  upon  completion. 

903.1.5  Safeguarding  Construction:  The  fire 
protection  construction  documents  shall  provide 
specifications  for  conformance  to  780  CMR  33 
and  NFPA-241  listed  in  Appendix  A  in  order  to 
safeguard  against  fires  during  construction, 
alterations  and  demolition  of  all  buildings  and 
structures  regulated  by  780  CMR. 


903.2  Authority:  In  accordance  with  the 
requirements  of  780  CMR  1 10  and  780  CMR  903.1 
the  building  of  official  shall  transmit  one  set  of  the 
fire  protection  construction  documents  (780  CMR 
903 .1.1)  and  building  construction  documents  to  the 
head  of  the  fire  department  or  his  designee  for 
review  and  approval  of  the  items  specified  in 
780  CMR  903.1.1. 

Note: 

1.  M.G.L.  c.  148  §§  26H,  26G  and  261,  when 
adopted  by  a  city  or  town,  will  impact  the  fire 
protection  requirements  of  780  CMR  9.  A 
building  official  should  consult  Official 
Interpretation  Number  45-96,  listed  in 
Appendix  B,  for  guidance. 

2.  In  addition  to  the  building  permit  requirements 
for  fire  protection  systems  in  780  CMR,  M.G.L. 
c.  148  §  10A  and  527  CMR  may  impose 
additional  installation  permitting  requirements. 

903.2.1  Alternative  Fire  Protection  Design 
Methodologies  -  Independent  Engineering 
Review:  Where  alternative  design  methodologies 
are  utilized  and  where  such  methodologies  result 
in  designs  which  vary  from  any  prescriptive 
requirement  of  780  CMR,  the  owner  shall  engage 
an  independent  registered  professional  engineer  to 
review  said  alternative  design  methodologies. 
The  scope  of  the  independent  registered 
professional  engineer  review  shall  include,  but  not 
be  limited  to  the  following; 

(a)  Review  of  the  design  assumptions, 
methodologies  and  resulting  proposed  system 
designs,  to  determine  whether  the  proposed  fire 
protection  system  designs  and  any  other 
systems  which  are  affected  by  the  design 
assumptions,  are  consistent  with  the  general 
objectives  and  prescriptive  provisions  of  this 
code  and  to  determine  whether  or  not  the 
methodologies  and  assumptions  conform  to 
accepted  engineering  practice; 

(b)  Preparation  of  a  written  report  to  the 
building  official  as  to  the  appropriateness  of 
the  proposed  design,  specifically  listing  any 
variances  from  the  prescriptive  provisions  of 
780  CMR  and  describing,  in  detail,  the  design 
provisions  used  to  achieve  compliance. 

If  the  reviewing  engineer  concurs  with  the 
proposed  design,  the  owner  shall  make 
application  for  a  variance,  to  the  State  Building 
Code  Appeals  Board  as  provided  in  780  CMR 
122.  In  addition  to  all  supporting  information  and 
materials,  the  reviewing  engineer's  report 
required  in  780  CMR  903.2. 1(b)  shall  be  included 
in  the  application  for  variance. 

A  building  permit  shall  not  be  issued  until  the 
variance,  if  required,  has  been  granted,  or  unless 
the  building  permit  is  issued  in  part,  as  provided 
for  in  780  CMR  111.13. 


150 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


903.3  Fire  Protection  Systems  Installation:  Fire 

protection  systems  shall  be  installed  by  contractors 
and  personnel  appropriately  licensed  in  the 
Commonwealth  of  Massachusetts  (licensed 
installing  contractor).  Shop  drawings  required  for 
submittals  and  reviews  by  the  Registered 
Professional  Engineer,  by  780  CMR  903.1.3  or  by 
applicable  NFPA  Standards  shall  note  the  name(s), 
license  number(s)  and  license  expiration  date(s)  of 
the  contractor(s)  installing  the  fire  protection 
systems. 

903.4  Acceptance:  In  accordance  with  the 
provisions  of  780  CMR  120,  a  Certificate  of 
Occupancy  shall  not  issue  until  the  building  official 
and  the  head  of  the  fire  department  or  their 
designees  have  witnessed  a  satisfactory  functional 
test  of  all  fire  protection  systems,  installed  in 
accordance  with  the  approved  fire  protection 
construction  documents.  All  fire  protection  systems 
shall  be  tested  in  accordance  with  the  applicable 
provisions  of  780  CMR  and  NFPA  Standards  and 
approved  testing  criteria  and  operational  sequence  as 
submitted  in  780  CMR  903 . 1 . 1 ,  items  1 9  and  20.  In 
addition,  the  following  documents  and/or 
information  shall  be  simultaneously  submitted  to  the 
building  official  and  head  of  the  fire  department  or 
their  designees  prior  to  the  witnessing  of  the 
operational  fire  protection  system(s)  testing: 

1.  Certification,  (PE  Seal  and  signature)  from  the 
Registered  Professional  Engineer  responsible  for  the 
design  in  accordance  with  780  CMR  903. 1.3  stating 
that  the  fire  protection  systems  have  been  installed 
in  accordance  with  the  approved  fire  protection 
construction  documents  and  that  he  has  reviewed  the 
shop  drawings  for  conformance  to  780  CMR903.3 
and  has  identified  deviations  if  any,  from  the 
approved  fire  protection  construction  documents. 

2.  Confirmation  by  the  building  owner/developer  or 
authorized  representative  that  they  have  received  the 
as-built  fire  protection  system  shop  drawings  from 
the  installing  contractor  and  that  the  Registered 
Professional  Engineer  has  certified  their  reasonable 
accuracy. 

3.  Material,  Test,  Performance  and  Completion 
Certificates,  properly  executed  by  the  installing 
contractor  in  accordance  with  the  applicable  NFPA 
Standards. 

Exception:  In  lieu  of  witnessing  a  satisfactory 
functional  test,  the  building  official  and  head  of 
the  fire  department  or  their  designees  may  accept 
a  final  performance  acceptance  test  report  from  a 
Registered  Professional  Engineer.  Said  report 
shall  certify  that  a  complete  satisfactory 
functional  test  of  all  fire  protection  systems  in 
accordance  with  the  approved  testing  criteria  and 
operational  sequence  have  been  witnessed. 

903.4.1       Conditional       Acceptance:       The 

requirements  of  780  CMR  903.4  shall  not 
preclude  the  issuance  of  a  temporary  Certificate 


of  occupancy  by  the  Building  Official  in 
accordance  with  780  CMR  120.3. 

780  CMR  904.0  FIRE  SUPPRESSION 
SYSTEMS 

904.1  Where  required:  Automatic  fire  suppression 
systems  shall  be  installed  where  required  by 
780  CMR,  and  in  the  locations  indicated  in 
780  CMR  904.2  through  904.9. 

Exceptions: 

1 .  An  automatic  fire  suppression  system  shall  not 
be  required  in  portions  of  buildings  that  comply 
with  780  CMR  406.0  for  open  parking  structures 
less  than  70  feet  in  height  above  mean  grade. 
— 2.-  -fa  telecommunications  equipment  buildings, 
an  automatic  fire  suppression  system  shall  not  be 
required  in  those  spaces  or  areas  occupied 
exclusively  for  telecommunications  equipment, 
associated  electrical  power  distribution 
equipment,  batteries  and  standby  engines, 
provided  that  those  spaces  or  areas  are  equipped 
throughout  with  an  automatic  fire  detection 
system  in  accordance  with  780  CMR  918.0  and 
are  separated  from  the  remainder  of  the  building 
with  fire  separation  assemblies  consisting  of  one- 
hour  fireresistance  rated  walls  and  two-hour 
fireresistance  rated  floor/ceiling  assemblies. 

904.1.1  Additional  requirements:  When  a 
building  or  structure  is  provided  with  a  fire  alarm 
system,  all  extinguishing  systems  installed  in 
accordance  with  the  provisions  of  780  CMR  904 
through  914,  shall  be  connected  to  the  fire  alarm 
system  in  accordance  with  the  requirements  of 
NFPA  72  as  listed  in  Appendix  A. 

904.1.1.1  Fire  pump  requirements:  Refer  to 

780  CMR  924. 

904.2  Use  Groups  A-l,  A-3,  A-4,  B,  E,  M,  S-l, 
F-l  in  buildings  of  12,000  sf  or  greater  in 
aggregate  floor  area:  An  automatic  fire  suppression 
system  shall  be  provided  throughout  all  portions  or 
uses  of  all  buildings  of  12,000  sf  or  greater  in 
aggregate  area  when  any  of  the  following  uses  are 
located  within  the  building; 

A-l,  A-3,  A-4,  B,  E,  M,  S-l,  F-l 
780  CMR  904.2  shall  apply  whether  or  not  the  use  is 
separated  from  any  other  use  within  the  building  by 
fire  separation  assemblies. 

Exceptions: 

1.  Existing  buildings:  Existing  buildings  which 
qualify  as  such  in  accordance  with  780  CMR 
3400.3.1  and  which  undergo  a  partial  change  in 
use  to  a  use  or  uses  specified  in  780  CMR  904.2 
or  are  mixed  use  buildings  which  undergo 
renovation  of  a  use  or  uses  specified  in  780  CMR 
904.2,  shall  be  provided  with  automatic  fire 
suppression  systems  in  accordance  with  the 
following: 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


151 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


(a)  only  in  those  portions  of  the  building 
which  have  been  changed  in  use  and  only  when 
such  space  or  spaces  exceed  12,000  sf  in 
aggregate  floor  area. 

(b)  only  in  those  portions  of  the  building 
which  have  been  altered  or  renovated  provided 
that  such  renovation  constitutes  substantial 
alterations  or  substantial  renovations,  in 
accordance  with  780  CMR  3401  and  only 
when  such  space  or  spaces  exceed  12,000  sf  in 
aggregate  floor  area. 

2.  Public  Garages:  Public  Garages  shall  conform 
to  780  CMR  408.0. 

Note:  See  also  M.G.L.  c.  148,  §  26G. 

904.3  Use  Group  A-2  in  buildings  of  5,000  sf  or 
greater  in  aggregate  floor  area:  An  automatic  fire 
suppression  system  shall  be  provided  throughout  all 
portions  or  uses  of  all  buildings  of  5,000  sf  or 
greater  in  aggregate  area  when  any  A-2  use  is 
located  within  the  building; 

780  CMR  904.3  shall  apply  whether  or  not  the 
A-2  use  is  separated  from  any  other  use  within  the 
building  by  fire  separation  assemblies. 

Exception: 

I.  Existing  buildings:  Existing  buildings  which 
qualify  as  such  in  accordance  with  780  CMR 
3400.3.1  which  undergo  a  partial  change  in  use  to 
an  A-2  use  or  partial  renovation  of  an  existing  A- 
2  use  shall  be  provided  with  an  automatic  fire 
suppression  system  only  in  those  portions  of  the 
building  which  have  been  changed  to  an  A-2  use 
or  those  existing  A-2  uses  which  have  been 
renovated  when  such  renovation  constitutes 
substantial  alterations  or  substantial  renovations, 
in  accordance  with  780  CMR  3401  and  only  when 
the  proposed  or  existing  A-2  use  exceeds  5,000  sf 
in  aggregate  floor  area. 

904.4  Use  Group  H:  An  automatic  fire  suppression 
system  shall  be  provided  throughout  all  buildings  of 
Use  Group  H. 

Exception:  Magazines  used  for  the  storage  of  Use 
Group  H-l  materials  which  are  constructed  and 
located  in  accordance  with  NFPA  495  and 
527  CMR  listed  in  Appendix  A. 

Note:  See  also  M.G.L.  c.  148,  §  26G. 

904.5  Use  Group  I:  An  automatic  fire  suppression 
system  shall  be  provided  throughout  all  buildings  of 
Use  Group  I. 

Note:  See  also  M.G.L.  c.  148,  §  26G. 


904.6  Use  Group  R-l:  An  automatic  fire 
suppression  system  shall  be  provided  throughout  all 
buildings  or  spaces  of  Use  Group  R-l  in  accordance 
with  780  CMR  906.2. 1  or  906.2.2. 

904.7  Use  Group  R-2:  An  automatic  fire 
suppression  system  shall  be  provided  throughout  all 
buildings  with  an  occupancy  in  Use  Group  R-2  in 
accordance  with  780  CMR  906.2.1  or  906.2.2. 

Note:  See  also  M.G.L.  c.  148,  §  26G. 

904.8  Windowless  story:  An  automatic  fire 
suppression  system  shall  be  provided  throughout 
every  story  or  basement  of  all  buildings  where  there 
is  not  provided  at  least  one  of  the  following  types  of 
openings: 

1.  An  exterior  stairway  that  conforms  to  the 
requirements  of  780  CMR  1014.0,  or  an  outside 
ramp  that  conforms  to  the  requirements  of 
780  CMR  1016.0,  leading  directly  to  grade  in 
each  50  linear  feet  (15240  mm)  or  fraction  thereof 
of  exterior  wall  in  the  story  or  basement,  on  at 
least  one  side  of  the  building. 

2.  Openings  entirely  above  the  adjoining  ground 
level  totaling  20  square  feet  (1.9  m  )  in  each  50 
linear  feet  (15240  mm)  or  fraction  thereof  of 
exterior  wall  in  the  story  or  basement,  on  at  least 
one  side  of  the  building.  Openings  shall  have  a 
least  dimension  of  not  less  than  22  inches  (559 
mm),  and  shall  have  a  minimum  net  clear  opening 
of  five  square  feet  (0.5m  ).  Access  to  such 
openings  from  the  exterior  shall  be  provided  to 
the  fire  department  and  such  openings  shall  be 
unobstructed  to  allow  fire-fighting  and  rescue 
operations  from  the  exterior. 

When  openings  in  a  story  are  provided  on  only 
one  side  and  the  opposite  wall  of  such  story  is  more 
than  75  feet  (22860  mm)  from  such  openings,  the 
story  shall  be  equipped  throughout  with  an 
automatic  sprinkler  system,  or  openings  as  specified 
herein  shall  be  provided  on  at  least  two  sides  of  the 
exterior  walls  of  the  story.  If  any  portion  of  a 
basement  is  located  more  than  75  feet  (22860  mm) 
from  the  openings  required  in  780  CMR  904.0,  the 
basement  shall  be  provided  with  an  automatic 
sprinkler  system. 

Exception:  Occupancies  in  Use  Group  R-3. 

904.9  Other  required  suppression  systems:  In 

addition  to  the  requirements  of  780  CMR  904.2 
through  904.8,  automatic  fire  suppression  systems 
for  certain  buildings  and  areas  shall  be  provided  in 
accordance  with  Table  904.9. 


152 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


Table  904.9 
ADDITIONAL  REQUIRED  SUPPRESSION 

SYSTEMS(1) 


780  CMR  Section 

Subject 

302.1.1 

Specific  occupancy  areas 

402.10;  402.15.2 

Covered  mall  buildings 

403.2 

High-rise  buildings 

404.2 

Atriums 

408.3.1 

Public  garages 

408.4 

Fuel-dispensing  areas 

4 

Bulk  Merchandizing/Warehouse 

Occupancies 

780  CMR  Section 

Subject 

411.7 

Sound  stages 

412.6 

Stages  and  enclosed  platforms 

413.4 

Special  amusement  buildings 

416.4 

HPM  facilities 

419.3 

Paint  spray  booths  and  storage 

rooms 

Open  parking  structures  more  than 

70  feet  in  height  above  the  mean 

grade  (M.G.L.  c.  148,  §  26A) 

507.1 

Unlimited  area  buildings 

1020.3 

Exit  lobbies 

2806.4 

Drying  rooms 

2807.6 

Waste  and  linen  chutes  and 

termination  and  incinerator 

rooms 

2808.4 

Refuse  vaults 

Note  (1)  See  also  M.G.L.  c.  148,  §§  26A.  26G,  26H,  and 
261. 

780  CMR  905.0  SUPPRESSION  SYSTEM 
AGENT  COMPATIBDLjTTY 

905.1  Agent  compatibility:  The  extinguishing  agent 
for  each  suppression  system  shall  be  compatible  with 
the  type  of  hazard  and  fire.  Each  fixed  fire 
suppression  system  shall  be  of  an  approved  type  and 
shall  be  designed  and  installed  in  accordance  with 
the  requirements  of  780  CMR. 

905.1.1  Special  hazards:  In  rooms  or  buildings 
containing  combustibles  (such  as  aluminum 
powder,  calcium  carbide,  calcium  phosphide, 
metallic  sodium  and  potassium,  quick-lime, 
magnesium  powder  or  sodium  peroxide)  that  are 
incompatible  with  water  as  an  extinguishing 
agent,  other  extinguishing  agents  shall  be  utilized. 

780  CMR  906.0  FIRE  SPRINKLER  SYSTEM 

906.1  General:  Automatic  sprinkler  systems  shall  be 
approved  and  shall  be  designed  and  installed  in 
accordance  with  the  provisions  of  780  CMR. 

906.2  Equipped  throughout:  Where  the  provisions 
of  780  CMR  require  that  a  building  or  portion 
thereof  be  equipped  throughout  with  an  automatic 
sprinkler  system,  the  system  shall  be  designed  and 
installed  in  accordance  with  780  CMR  906.2.1, 
906.2.2  or  906.2.3. 


Exception:  Where  water  as  an  extinguishing 
agent  is  not  compatible  with  the  fire  hazard  (see 
780  CMR  905. 1)  or  is  prohibited  by  a  law,  statute 
or  ordinance,  the  affected  area  shall  be  equipped 
with  an  approved  automatic  fire  suppression 
system  utilizing  a  suppression  agent  that  is 
compatible  with  the  fire  hazard. 

906.2.1  NFiPA  13  systems:  The  system  shall  be 
designed  and  installed  in  accordance  with  NFiPA 
13  listed  in  Appendix  A. 

906.2.2  NFiPA  13R  systems:  In  buildings  four 
stories  or  less  in  height,  systems  designed  and 
installed  in  accordance  with  NFiPA  13R  listed  in 
Appendix  A  shall  be  permitted  in  Use  Group  1-1 
buildings  with  not  more  than  16  occupants  and  in 
Use  Group  R  buildings. 

906.2.3  NFiPA  13D  systems:  In  Use  Group  R-3 

buildings  with  at  least  two-hour  fireresistance 
rated  fire  separation  assemblies  between  dwelling 
units,  or  in  Use  Group  1-1  buildings  with  not  more 
than  eight  occupants,  systems  designed  and 
installed  in  accordance  with  NfiPA  13D  listed  in 
Appendix  A  shall  be  permitted. 

906.3  Design:  Design  documentation  shall  be  in 
accordance  with  780  CMR  903. 

906.4  Actuation:  Water  sprinkler  systems  shall  be 
automatically  actuated  unless  otherwise  specifically 
provided  for  in  780  CMR. 

906.5  Sprinkler  alarms:  Approved  audible  or  visual 
alarm  devices  shall  be  connected  to  every  water 
sprinkler  system.  Such  alarm  devices  shall  be 
activated  by  water  flow  and  shall  be  located  in  an 
approved  location  on  the  exterior  of  the  building  and 
throughout  the  building  in  accordance  with  the 
requirements  ofNFPA-72  listed  in  Appendix  A. 

906.6  Water-control    valve    identification:    All 

valves  controlling  water  to  fire  protection  systems 
shall  be  provided  with  permanently  attached 
identification  tags  indicating  the  valves'  function  and 
what  is  controlled. 

906.7  Sprinkler  riser:  A  sprinkler  system  riser 
which  also  serves  as  the  wet  standpipe  riser  in 
buildings  required  to  have  or  having  both  systems, 
shall  conform  to  780  CMR  914.6. 

906.8  Signs:  Where  sprinkler  control  valves  are 
located  in  a  separate  room  or  building,  a  sign  shall 
be  provided  on  the  entrance  door.  The  lettering  shall 
be  at  least  four  inches  (102  mm)  in  height  and  shall 
otherwise  conform  to  780  CMR  901.6  and  shall  read 
"Sprinkler  Control  Valves." 

906.9  Acceptance  tests:  All  sprinkler  systems  shall 
be  tested  in  accordance  with  the  applicable  NFPA 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


153 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Standards  used  for  sprinkler  system  design  and 
Installation  and  listed  in  Appendix  A. 

906.9.1  Underground  connections:  Underground 
mains  and  lead-in  connections  shall  be  flushed 
and  tested  in  accordance  with  NFiPA  13  and  24 
list'-d  in  Appendix  A. 

906.9.2  Hydrostatic  test:  All  sprinkler  systems  shall 
be  tested  hydrostatically  in  accordance  with  the 
applicable  NFP  A  Standards  listed  in  Appendix  A. 

780  CMR  907.0  LIMITED  AREA  SPRINKLER 
SYSTEMS 

907.1  General:  A  limited  area  sprinkler  system  shall 
be  of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR  907.0. 
Complete  fire  protection  construction  documents 
shall  be  provided.  (See  780  CMR  903.0.) 

907.2  Where  permitted:  Where  the  provisions  of 
780  CMR  require  the  installation  of  a  fire 
suppression  system,  and  a  water  sprinkler 
extinguishing  system  is  used  with  a  limited  number 
of  sprinklers,  a  limited  area  sprinkler  system  that 
complies  with  the  requirements  of  780  CMR  907.0 
is  permitted  to  be  installed. 

907.2.1  Special  occupancy  areas:  A  limited  area 
sprinkler  system  shall  be  permitted  within  special 
occupancy  areas  as  designated  in  780  CMR  4  or 
within  specific  occupancy  areas  as  designated  in 
780  CMR  302.1.1,  provided  that  the  area  is 
enclosed  within  fire  separation  assemblies  as 
required  by  780  CMR,  and  20  sprinklers  or  less 
are  required  to  protect  each  separately  enclosed 
area.  Where  nonfireresistance  rated  separation 
walls  are  permitted  by  Table  302.1.1  to  enclose 
contiguous  specific  occupancy  areas  on  one  floor, 
the  areas  shall  be  considered  to  be  one  separately 
enclosed  area  for  the  purposes  of  determining  the 
number  of  sprinklers  based  on  the  spacing 
limitations  ofNFPA  13  listed  in  Appendix  A. 

907.2.2  Unenclosed  floor  openings,  waste  and 
linen  chutes,  and  kitchen  and  hazardous 
exhaust  systems:  A  limited  area  sprinkler  system 
shall  be  permitted  to  protect  unenclosed  escalator 
floor  openings  that  comply  with  780  CMR 
907.2.2.1,  chutes  used  for  waste  or  linen 
collection,  commercial  kitchen  exhaust  systems 
and  duct  systems  that  exhaust  hazardous 
materials. 

907.2.2.1  Water  curtain:  The  area  of  the  floor 
opening  shall  not  exceed  twice  the  horizontal 
projected  area  of  the  escalator  and  the  opening 
shall  not  connect  more  than  four  stories  in 
occupancies  in  other  than  Use  Groups  B  and  M 
and  the  opening  shall  be  protected  by  a  draft 
curtain  and  a  closed  sprinkler  water  system 
conforming  to  NfiPA  13  listed  in  Appendix  A 


907.3  Design:  Except  as  otherwise  provided  for  in 
780  CMR  907.0,  a  limited  area  sprinkler  system 
shall  be  designed  and  installed  in  accordance  with 
780  CMR  906.0. 

907.4  Actuation:  A  limited  area  sprinkler  system 
shall  be  automatically  actuated. 

907.5  Sprinkler  alarms:  Alarms  and  alarm 
attachments  shall  be  required  and  shall  be  located 
and  installed  in  accordance  with  the  requirements  of 
780  CMR  906.5. 

907.6  Standpipe  connection:  The  water  supply  for 
the  limited  area  sprinkler  system  shall  be  from  the 
building  standpipe  system  where  the  building  is 
equipped  with  a  standpipe  system  that  is  sized  for  a 
500-gallon-per-minute  (0.032  m  Is)  minimum  flow 
and  has  an  automatic  water  supply  (see  780  CMR 
914.5). 

907.6.1  Domestic  supply:  Where  limited  area 
sprinkler  systems  are  supplied  from  the  domestic 
water  system,  the  domestic  water  system  shall  be 
designed  to  support  adequately  the  design  flow  of 
the  largest  number  of  sprinklers  required  to  be 
hydraulically  calculated  by  NFiPA  13  listed  in 
Appendix  A  in  any  one  of  the  enclosed  areas  plus 
the  domestic  demand. 

907.6.2  Cross  connection:  The  potable  water 
supply  shall  be  protected  against  backflow  in 
accordance  with  the  requirements  of  the  Plumbing 
and  Gas  Code  (248  CMR),  the  Department  of 
Environmental  Protection  Regulations,  3 1 0  CMR 
as  listed  in  Appendix  A  as  well  as  any  cross- 
connection  protection  criteria  legally  set  forth  by 
the  water  supplier/purveyor  having  local 
jurisdiction. 

907.6.3  Domestic  connection:  Shutoff  valves 
shall  not  be  permitted  in  the  suppression  system 
piping.  Water  supply  shall  be  controlled  by  the 
riser  control  valve  to  the  domestic  water  piping. 

Exception:  Shutoff  valves  in  the  sprinkler 
system  piping  are  permitted  provided  that  such 
valves  are  supervised  in  accordance  with 
780  CMR  923.0. 

907.7  Acceptance  tests:  All  limited  area  sprinkler 
systems  shall  be  tested  as  stipulated  in  780  CMR 
906.9. 

780  CMR  908.0  WATER-SPRAY  FIXED 
SYSTEMS 

908.1  General:  Water-spray  fixed  systems  for  fire 
suppression  shall  be  of  an  approved  type  and  shall 
be  installed  in  accordance  with  the  provisions  of 
780  CMR  and  NFiPA  15  listed  in  Appendix  A.  A 
water-spray  fixed  system  is  a  system  connected  to  a 
reliable  source  of  water  supply  and  equipped  with 
normally    open   water-spray   nozzles   for   specific 


154 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


discharge  and  distribution  over  the  surface  or  area  to 
be  protected. 

908.2  Design:  Completefire  protection  construction 
documents  and  hydraulic  calculations  shall  be 
submitted  for  review  prior  to  installation.  The 
submittal  shall  include  nozzle  layouts,  friction  loss, 
calculations,  water  supply  data  and  a  detailed  layout 
of  the  entire  area  to  be  protected.  (See  780  CMR 
903.0.) 

908.3  Actuation:  Water-spray  systems  shall  be 
automatically  actuated  and  shall  be  provided  with  a 
manual  means  of  actuation. 

908.4  Acceptance  tests:  All  new  system  piping  shall 
be  flushed  and  tested  in  accordance  with  the 
provisions  of  NFiPA  15  listed  in  Appendix  A. 

780  CMR  909.0  CARBON  DIOXIDE 
EXTINGUISHING  SYSTEMS 

909.1  General:  Carbon  dioxide  extinguishing 
systems  shall  be  of  an  approved  type  and  shall  be 
installed  in  accordance  with  the  provisions  of 
780  CMR  and  NFiPA  12  listed  in  Appendix  A.  A 
carbon  dioxide  extinguishing  system  is  a  system 
which  supplies  CO,  from  a  pressurized  vessel 
through  fixed  pipes  and  nozzles. 

909.2  Design:  The  details  of  the  system  indicated  on 
the  fire  protection  construction  documents  shall 
include  information  and  calculations  of  the  amount 
of  carbon  dioxide;  the  location  and  flow  rate  of  each 
nozzle  including  equivalent  orifice  area;  and  the 
location  and  size  of  the  carbon  dioxide  storage 
facility.  Information  shall  be  submitted  pertaining  to 
the  location  and  function  of  detecting  devices, 
operating  devices,  auxiliary  equipment  and  electrical 
circuitry,  if  used.  Sufficient  information  shall  be 
indicated  to  identify  properly  the  apparatus  and 
devices  used.  Any  special  features  shall  be 
adequately  explained.  (See  780  CMR  903.0.) 

909.3  Actuation:  Carbon  dioxide  extinguishing 
systems  shall  be  automatically  actuated  and  shall  be 
provided  with  a  manual  means  of  actuation. 

909.4  Safety  requirements:  Where  persons  will 
enter  or  be  trapped  in  atmospheres  made  hazardous 
by  carbon  dioxide  discharge,  warning  signs  and 
discharge  alarms  shall  be  provided. 

909.5  Acceptance  tests:  All  carbon  dioxide 
extinguishing  systems  shall  be  tested  in  accordance 
with  NFiPA  12  listed  in  Appendix  A.  A  completed 
system  shall  be  tested  for  tightness  up  to  the  selector 
valve,  and  for  continuity  of  piping  with  free 
unobstructed  flow  beyond  the  selector  valve.  The 
labeling  of  devices  with  proper  designations  and 
instructions  shall  be  checked.  Operational  tests  shall 
be  conducted  on  all  devices  except  cylinder  valves 


in  multicylinder  high-pressure  systems.  Where 
conditions  prevail  that  make  it  difficult  to  determine 
adequately  the  system  requirements  or  design,  a 
suitable  discharge  test  and  concentration  analysis 
shall  be  made. 

780  CMR  910.0  DRY-CHEMICAL 
EXTINGUISHING  SYSTEMS 

910.1  General:  Dry-chemical  extinguishing  systems 
shall  be  of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR  and 
NFiPA  17  listed  in  Appendix  A.  A  dry-chemical 
extinguishing  system  is  a  system  consisting  of  dry 
chemical  and  expellant  gas  storage  tanks,  fixed 
piping  and  nozzles  used  to  assure  proper  distribution 
of  an  approved  extinguishing  agent  to  a  specific  fire 
hazard  or  into  an  area  of  potential  fire. 

910.2  Design:  The  details  of  the  system  indicated  on 
the  fire  protection  construction  documents  shall 
include  sufficient  information  and  calculations  of  the 
amount  of  dry  chemical;  the  size,  length  and 
arrangement  of  connected  piping,  or  piping  and 
hose;  and  a  description  and  location  of  nozzles  so 
that  the  adequacy  of  the  system  can  be  determined. 
Information  shall  be  submitted  pertaining  to  the 
location  and  function  of  detecting  devices,  operating 
devices,  auxiliary  equipment  and  electrical  circuitry, 
if  used.  Sufficient  information  shall  be  indicated  to 
identify  properly  the  apparatus  and  devices  used. 
Any  special  features  shall  be  adequately  explained. 
(See  780  CMR  903.0.) 

910.3  Actuation:  Dry-chemical  extinguishing 
systems  shall  be  automatically  actuated  and  shall  be 
provided  with  a  manual  means  of  actuation. 

910.4  Safety  requirements:  Where  persons  will  be 
exposed  to  a  dry-chemical  discharge,  warning  signs 
and  discharge  alarms  shall  be  provided. 

910.5  Acceptance  tests:  All  dry-chemical 
extinguishing  systems  shall  be  tested  in  accordance 
with  NFiPA  17  listed  in  Appendix  A.  A  completed 
system  shall  be  tested  by  a  discharge  of  expellant 
gas  through  the  piping  and  nozzles.  Observations  for 
gas  leakage  and  for  continuity  of  piping  with  free 
unobstructed  flow  shall  be  made.  Observations  shall 
be  made  of  the  flow  of  expellant  gas  through  all 
nozzles.  The  labeling  of  devices  with  proper 
designations  and  instructions  shall  be  checked.  After 
testing,  all  piping  and  nozzles  shall  be  blown  clean 
using  compressed  air  or  nitrogen,  and  the  system 
shall  be  properly  charged  and  placed  in  the  normal 
"set"  condition. 

910.5.1  Discharge  test:  All  systems  shall  be 
tested  by  a  discharge  of  expellant  gas  through  the 
piping  and  nozzles  with  observations  being  made 
of  the  flow  of  expellant  gas  through  all  nozzles  as 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


155 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


well  as  observing  for  leakage  and  continuity  of 
piping  with  free  unobstructed  flow. 

910.6  Range  hoods:  In  addition  to  the  requirements 
of  780  CMR  910.0  and  the  applicable  NFPA 
standards  listed  in  Appendix  A,  range  hood  dry- 
chemical  systems  shall  bear  the  label  of  an  approved 
agency. 

The  system  shall  be  installed  in  accordance  with 
the  manufacturer's  installation  instructions.  The  dry- 
chemical  agent  of  the  system  shall  be  nontoxic. 

780  CMR  911.0  FOAM-EXTINGUISHING 
SYSTEMS 

911.1  General:  Foam-extinguishing  systems  shall  be 
of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR  and 
NFiPA  11,  11A  and  16  listed  in  Appendix  A.  A 
foam-extinguishing  system  is  a  special  system 
designed  to  discharge,  either  mechanically  or 
chemically,  a  foam  made  from  concentrates,  over  the 
area  to  be  protected. 

911.2  Design:  The  details  of  the  system  indicated  on 
the  fire  protection  construction  documents  shall 
include  complete  computations  show-testing 
pressure  drop  in  all  system  piping,  friction  loss 
calculations  of  liquid  lines  and  a  detailed  layout  of 
the  entire  hazard  area  to  be  protected.  Hydraulic 
characteristics  of  foam  proportioners  and  foam 
makers  as  determined  by  tests  shall  be  supplied  by 
the  manufacturer  to  the  department  (including  the 
range  of  operating  conditions  required  for  the 
proposed  installation)  to  permit  determination  of  the 
adequacy  of  the  hydraulics  of  the  proposed 
protection.  (See  780  CMR  903.0.) 

911.3  Actuation:  A  foam-extinguishing  system  shall 
be  automatically  actuated  and  shall  be  provided  with 
a  manual  means  of  actuation. 

911.4  Safety  requirements:  In  any  proposed  use  of 
a  medium-  or  high-expansion  foam  where  persons 
will  be  exposed  to  the  foam  discharge,  warning  signs 
and  discharge  alarms  shall  be  provided. 

911.5  Acceptance  tests:  All  foam-extinguishing 
systems  shall  be  tested  in  accordance  with  NFiPA 
11, 1  1 1 A  and  16  listed  in  Appendix  A.  The  system 
shall  be  subjected  to  a  flow  test  to  insure  that  the 
hazard  area  is  fully  protected  in  compliance  with  the 
design  specifications,  and  to  determine  flow 
pressures,  actual  discharge  capacity,  foam  quality, 
consumption    rate    of  foam-producing    materials, 


manpower  requirements  and  other  operating 
characteristics. 

780  CMR  912.0  HALOGENATED 
EXTINGUISHING  SYSTEMS 

912.1  General:  Halogenated  extinguishing  systems 
shall  be  of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR  and 
NFiPA  12 A  and  12B  listed  in  Appendix  A.  A 
halogenated  extinguishing  system  is  a  system 
consisting  of  pipes,  open  nozzles  and  a  container  of 
halogenated  agent  under  pressure. 

912.2  Design:  The  details  of  the  system  indicated  on 
the  fire  protection  construction  documents  shall 
include  information  and  calculations  of  the  amount 
of  extinguishing  agent;  the  container  storage 
pressure;  the  location  and  flow  rate  of  each  nozzle 
including  equivalent  orifice  area;  the  location,  size 
and  equivalent  lengths  of  pipe,  fittings  and  hose;  and 
the  location  and  size  of  the  storage  facility. 
Information  shall  be  submitted  pertaining  to  the 
location  and  function  of  detecting  devices,  operating 
devices,  auxiliary  equipment  and  electrical  circuitry, 
if  used.  Sufficient  information  shall  be  indicated  to 
identify  properly  the  apparatus  and  devices  used. 
Any  special  features  shall  be  adequately  explained. 
(See  780  CMR  903.0.) 

912.3  Actuation:  Halogenated  extinguishing 
systems  shall  be  automatically  actuated  and  shall 
also  be  provided  with  a  manual  means  of  actuation. 

912.4  Safety  requirements:  Where  persons  will 
enter  or  be  trapped  in  atmospheres  made  hazardous 
by  a  halogenated  system  discharge,  warning  signs 
and  discharge  alarms  shall  be  provided. 

912.5  Acceptance  tests:  All  halogenated 
extinguishing  systems  shall  be  tested  in  accordance 
with  NFiPA  12A  and  12B  listed  in  Appendix  A. 
completed  system  shall  be  tested  for  tightness  up  to 
the  selector  valve,  and  for  continuity  of  piping  with 
free  unobstructed  flow  beyond  the  selector  valve. 
The  labeling  of  devices  with  proper  designations  and 
instructions  shall  be  checked.  Operational  tests  shall 
be  conducted  on  all  devices  except  cylinder  valves 
in  multicylinder  systems.  Where  conditions  prevail 
that  make  it  difficult  to  determine  adequately  the 
system  requirements  or  design,  a  suitable  discharge 
test  and  concentration  analysis  shall  be  made. 


I  56 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


780  CMR  913.0  WET-CHEMICAL  RANGE 
HOOD  EXTINGUISHING  SYSTEMS 

913.1  General:  Wet-chemical  extinguishing  systems 
shall  be  installed  in  accordance  with  the  provisions 
of  780  CMR  913.0,  and  the  BOCA  Mechanical  Code 
and  NFiPA  17A  listed  in  Appendix  A  The  system 
shall  bear  the  label  of  an  approved  agency  and  shall 
be  installed  in  accordance  with  the  manufacturer's 
installation  instructions.  A  wet-chemical  system  is  a 
solution  of  water  and  potassium-car-bonate-based 
chemical,  potassium-acetate-based  chemical  or  a 
combination  thereof  which  forms  the  extinguishing 
agent. 

913.2  Design:  The  details  of  the  system  indicated  on 
the  fire  protection  construction  documents  shall 
include  sufficient  information  and  calculations  on 
the  amount  of  wet  chemical;  the  size,  length  and 
arrangement  of  connected  piping;  and  a  description 
and  location  of  nozzles  so  that  the  adequacy  of  the 
system  can  be  determined.  Information  shall  be 
submitted  pertaining  to  the  location  and  function  of 
detecting  devices,  operating  devices,  auxiliary7 
equipment  and  electrical  circuitry,  if  used  Sufficient 
information  shall  be  indicated  to  identify  properly 
the  apparatus  and  devices  used.  Any  special  features 
shall  be  adequately  explained.  (See  780  CMR 
903.0.) 

913.3  Actuation:  Wet-chemical  extinguishing 
systems  shall  be  automatically  actuated  and  shall  be 
provided  with  a  manual  means  of  actuation. 

913.4  Safety  requirements  Where  persons  will  be 
exposed  to  a  wet-chemical  discharge,  warning  signs 
and  discharge  alarms  shall  be  provided 

913.5  Acceptance  tests:  All  wet-chemical 
extinguishing  systems  shall  be  tested  in  accordance 
with  NFiPA  1 7 A  listed  in  Appendix  A .  A  completed 
system  shall  be  tested  by  discharge  of  wet  chemical 
in  sufficient  amounts  to  verify  that  the  system  is 
properly  installed  and  functional.  Tests  shall  include 
a  check  of  the  detection  systems,  the  alarms  and  the 
releasing  devices,  including  manual  stations,  fuel 
and  power  shutoff  devices  and  other  associated 
equipment. 

913.5.1  Discharge  test:  All  systems  shall  be 
tested  by  a  discharge  of  expellant  gas  through  the 
piping  and  nozzles  with  observations  being  made 
of  the  flow  of  expellant  gas  through  all  nozzles  as 
well  as  observing  for  leakage  and  continuity  of 
piping  with  free  unobstructed  flow. 

780  CMR  914.0  STANDPIPE  SYSTEMS 
914.1  General:  Standpipe  systems  shall  be  designed, 
installed  and  maintained  in  accordance  with  the 
provisions  of  780  CMR  and  NFPA-14  listed  in 
Appendix  A.  Where  standpipe  systems  are  required 
by  780  CMR,  such  systems  shall  be  automatic  wet 


systems.  Automatic  dry  and  semi-automatic  dry 
standpipe  systems  shall  be  permitted  only  in  areas 
subject  to  freezing.  Complete  fire  protection 
construction  documents  shall  be  provided.  (See 
780  CMR  903.0.) 

914.2  Where  required:  Class  III  standpipe  systems 
shall  be  installed  where  required  by  780  CMR 
914.2.1  through  906.2.11  and  shall  be  located  in 
accordance  with  the  provisions  of  NFPA  14,  listed  in 
Appendix  A. 

914.2.1  Use  Group  A:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  A 
when: 

1 .  Two  or  more  stories  in  height  of  Use  Group 
A-l.  A-2,  or  A-3,  and  having  an  occupant  load 
or  more  than  300,  or; 

2.  Three  or  more  stories  in  height  regardless 
of  the  area  per  floor;  or; 

3  Having  an  auditorium  seating  over  500. 
Standpipes  shall  be  located  one  on  each  side  of 
the  auditorium  in  each  tier,  one  in  each 
mezzanine,  one  in  each  tier  of  dressing  rooms, 
and  protecting  each  property,  store  and  work 
room;  or: 

4  Having  a  stage.  Standpipes  shall  be  located 
on  each  side  of  the  stage. 

Such  standpipes  shall  be  not  less  that  2'/2-inch 
diameter,  equipped  with  approved  1 14  inch  hose 
station. 

914.2.2  Use  Group  B:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  B 
when: 

1 .  Three  or  more  stories  in  height,  and  more 
than  3,000  square  feet  in  area  per  floor;  or; 

2  Four  or  more  stories  in  height  regardless  of 
the  area  per  floor. 

914.2.3  Use  Group  E:  In  buildings  or  structures 
or  portions  thereof  of  Use  Group  E  when  three  or 
more  stories  in  height  regardless  of  the  area  per 
floor  or  when  having  a  stage  or  auditorium  in 
accordance  with  780  CMR  914.2.1(3)  and 
914.2.1(4). 

914.2.4  Use  Group  F:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  F 
when: 

i  Three  or  more  stories  in  height,  and  more 
than  3,000  square  feet  in  area  per  floor,  or; 

2.  Four  or  more  stories  in  height  regardless  of 
the  area  per  floor. 

914.2.5  Use  Group  H:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  H 
when: 

1 .  Three  or  more  stories  in  height,  and  more 
than  10,000  square  feet  in  area  per  floor;  or; 

2.  Four  or  more  stories  in  height,  regardless  of 
the  area  per  floor. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


157 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


914.2.6  Use  Group  I:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  I, 
three  or  more  stories  in  height,  regardless  of  the 
area  per  floor. 

914.2.7  Use  group  M:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  M 
when: 

1 .  Three  stories  or  more  in  height,  and  more 
than  3,000  square  feet  in  area  per  floor,  or; 

2.  Four  or  more  stories  in  height  regardless  of 
the  area  per  floor,  or, 

3         Classified  as  a  covered  mall  building 
within  the  mall  portions  (see  780  CMR  4). 
4.  Classified    as    a    bulk/merchandising 

warehouse.  (See  780  CMR  4.) 

914.2.8  Use  Group  R-l  and  R-2:  In  all  buildings 
or  structures  or  portions  thereof  of  Use  Group  R-l 
and  R-2  when: 

1  Three  or  more  stories  in  height  and  of  Use 
Group  R-l  regardless  of  the  area  per  floor;  or; 

2.  Three  or  more  stories  in  height  and  more 
than  10.000  square  feet  in  area  per  floor,  or; 

3.  Four  or  more  stories  in  height  regardless  of 
the  area  per  floor 

914.2.9  Use  Group  S:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  S, 
other  than  public  garages  which  shall  conform  to 
780  CMR  914.2. 10  when: 

1 .  Three  or  more  stories  in  height,  or  Use 
Group  S-l,  and  more  than  3,000  square  feet  in 
area  per  floor;  or; 

2.  Three  or  more  stories  in  height.  Use  Group 
S-2,  and  more  than  10,000  square  feet  in  area 
per  floor;  or; 

3.  Four  or  more  stories  in  height  of  Use 
Groups  S-l  or  S-2  regardless  of  the  area  per 
floor. 

914.2.10  Use  Group  U:  In  all  buildings  or 
structures  or  portions  thereof  of  Use  Group  U 
when: 

1 .  Three  or  more  stories  in  height  and  more 
than  10,000  square  feet  in  area  per  floor;  or; 

2.  Four  or  more  stories  in  height  regardless  of 
the  area  per  floor. 

914.2.11  Public  Garages:  In  all  Group  I  and  1 1 
public  garages  and  open  parking  structures  when: 

1.  More  than  10,000  square  feet  in  area  per 
floor;  or; 

2.  More  than  7,500  square  feet  in  area  per 
floor  and  more  than  one  story  in  height;  or; 

3.  More  than  5,000  square  feet  in  area  per 
floor,  and  more  than  two  stories  in  height;  or; 

4.  More  than  three  stories  in  height;  or; 

5.  Located  in  buildings  where  the  upper 
stories  are  designed  for  other  uses:  or; 

6  When  located  in  any  story  that  is  more  than 
50%  below  grade. 


Exception:  Standpipe  systems  can  be 
"Class  I  Manual  Dry  Type"  as  defined  by 
NFPA-14  for  open  parking  structures  less 
than  70'  in  height 

914.3  Standpipe  system  piping  sizes:  The  riser 
piping,  supply  piping,  and  the  water  service  piping 
shall  be  hydraulically  sized  in  accordance  with  the 
provisions  of  NFPA-14  listed  in  Appendix  A. 

Exception:  The  residual  pressure(s)  as  noted  in 
NFPA-14  are  not  required  to  be  maintained  in 
buildings  less  than  70  feet  in  height  which  are 
equipped  throughout  with  an  approved  automatic 
fire  suppression  system.  The  system  shall  be  sized 
based  on  a  150  psi  minimum  inlet  pressure  at  the 
Siamese  connection 

914.4  High-rise  buildings  All  buildings  more  than 
70  feet  in  height  above  the  mean  grade  shall  have 
each  floor  supplied  by  a  minimum  of  two 
combination  standpipe/sprinkler  risers  installed  in 
accordance  with  the  requirements  of  NFPA-14, 
listed  in  Appendix  A 

914.5  Outlets:  Standpipe  system  outlets  shall 
comply  with  the  provisions  for,  Class  III  Systems  of 
NFPA-14  as  listed  in  Appendix  A 

914.6  Acceptance  Tests:  All  Standpipe  systems 
shall  be  tested  in  accordance  with  NFPA  listed  in 
Appendix  A 

914.6.1  Underground  Connections: 

Underground  mains  and  lead-in  connections  shall 
be  flushed  and  tested  in  accordance  with  NFPA 
14  and  NFPA  24  listed  in  Appendix  A 

914.7  Standpipe  system  requirements  for 
buildings  under  construction  or  demolition: 

914.7.1  General:  Standpipes  required  by 
780  CMR  914.7  are  to  be  either  temporary  or 
permanent  in  nature,  with  or  without  a  water 
supply,  provided,  however,  that  such  standpipes 
conform  to  the  requirements  of  780  CMR  914.0  as 
to  number  of  risers,  capacity,  outlets  and 
materials. 

914.7.2  Buildings  under  construction  or 
demolition:  Standpipe  requirements  for  buildings 
under  construction  or  demolition  shall  be  in 
accordance  with  the  provisions  of  780  CMR 
3305.3  and  NFPA  241  as  listed  in  Appendix  A 

780  CMR  915.0  FIRE  DEPARTMENT 
CONNECTIONS 

915.1  Required:  All  required  water  fire- 
extinguishing  and  standpipe  systems  shall  be 
provided  with  a  fire  department  connection  in 
accordance  with  the  applicable  NFPA  standards 
Standpipes    in    buildings    under    construction    or 


158 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


demolition  shall  conform  to  780  CMR  3305.3  and 
NFPA  24 1  listed  in  Appendix  A. 

Exceptions: 

1 .  Limited  area  sprinkler  systems  supplied  from 
the  domestic  water  system. 

2.  Where  the  local  fire  department  approves  a 
single  connection  for  large  diameter  hose  of  at 
least  four  inches. 

3 .  An  automatic  sprinkler  system  with  less  than 
20  sprinklers. 

915.2  Connections:  Fire  department  connections 
shall  be  arranged  in  such  a  manner  that  the 
attachment  to  any  one  water  sprinkler  connection 
will  serve  all  sprinklers,  and  the  attachment  to  any 
one  standpipe  connection  will  serve  all  standpipes 
within  the  building. 

915.3  Location:  Fire  department  connections  shall 
be  located  and  shall  be  visible  on  a  street  front  or  in 
a  location  approved  by  the  fire  department.  Such 
connections  shall  be  located  so  that  immediate 
access  is  provided  to  the  fire  department.  Fire 
department  connections  shall  not  be  obstructed  by 
fences,  brushes,  trees,  walls  or  any  other  similar 
object. 

915.4  Height:  Fire  department  connections  shall  not 
be  less  than  18  inches  (457  mm)  and  not  more  than 
42  inches  (1067  mm)  in  elevation,  measured  from 
the  ground  level  to  the  centerline  of  the  inlets. 

915.5  Projection:  Where  the  fire  department 
connection  will  otherwise  project  beyond  the 
property  line  or  into  the  public  way,  a  flush-type  fire 
department  connection  shall  be  provided. 

915.6  Hose  thread:  Hose  thread  in  the  fire 
department  connection  shall  be  uniform  with  that 
used  by  the  local  fire  department. 

915.7  Fittings:  Fire  department  inlet  connections 
shall  be  fitted  with  check  valves,  ball  drip  valves  and 
plugs  with  chains  or  frangible  caps. 

915.8  Signs:  A  metal  sign  with  raised  letters  at  least 
one  inch  (25  mm)  in  height  shall  be  mounted  on  all 
fire  department  connections  serving  sprinklers  or 
standpipes.  Such  signs  shall  read  "Automatic 
Sprinklers"  or  "Standpipe,"  or  both,  as  applicable. 

780  CMR  916.0  YARD  HYDRANTS/ 
UNDERGROUND  FIRE  MAINS 

916.1  Fire  hydrants:  Fire  hydrants  and  underground 
fire  mains  installed  on  private  property  shall  be 
located  and  installed  as  directed  by  the  fire 
department.  Hydrants  shall  conform  to  the  standards 
of  the  administrative  authority  of  the  jurisdiction  and 
the  fire  department.  Hydrants  shall  not  be  installed 
on  a  water  main  less  than  six  inches  in  diameter 


Standards  of  construction  shall  be  in  accordance 
with  NFPA  24  as  listed  in  Appendix  A. 

780  CMR  917.0  FTRE  PROTECTIVE 
SIGNALING  SYSTEMS 

( Fire  Alarm  System ) 

917.1  General:  Fire  protective  signaling  systems 
shall  be  of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  7S0  CMR  and 
NFPA  72  listed  in  Appendix  A. 

917.2  Fire  Protection  Construction  documents: 

Where  a  fire  protective  signaling  system  is  required 
by  780  CMR,  the  fire  protection  construction 
documents  shall  show  the  location  and  number  of  all 
alarm-initiating  devices  and  alarm  notification 
appliances,  and  shall  provide  a  description  of  all 
equipment  to  be  used,  proposed  zoning,  a  list  of 
auxiliary  control  functions  (i.e.,  elevator  capture), 
location  of  the  control  panel(s)  and  annunciator(s), 
and  a  complete  sequence  of  operation  for  the  system. 
(Also  see  780  CMR  903.0) 

917.3  Approval:  All  devices,  combinations  of 
devices,  appliances  and  equipment  shall  be  approved 
for  the  fire  protective  signaling  purpose  for  which 
such  equipment  is  used. 

917.4  Where  required:  A  fire  protective  signaling 
system  shall  be  installed  and  maintained  in  full 
operating  condition  in  the  locations  described  in 
780  CMR  917.4.1  through  917.4.6. 

917.4.1  Use  Group  A  or  E:  A  fire  protective 
signaling  system  shall  be  installed  and  maintained 
in  all  occupancies  in  Use  Group  A  or  E. 

917.4.2  Use  Group  B:  A  fire  protective  signaling 
system  shall  be  installed  and  maintained  in  all 
occupancies  in  Use  Group  B  where  such  buildings 
have  occupied  floors  which  are  two  or  more 
stories  above  the  lowest  level  of  exit  discharge  or 
which  have  floors  two  or  more  stories  below  the 
highest  level  of  exit  discharge. 

917.4.3  Use  Group  H:  A  fire  protective  signaling 
system  shall  be  installed  and  maintained  in  all 
occupancies  in  Use  Groups  H. 

917.4.4  Use  Group  I:  A  fire  protective  signaling 
system  shall  be  installed  and  maintained  in  all 
occupancies  in  Use  Group  I. 

917.4.5  Use  Group  R-l:  A  fire  protective 
signaling  system  shall  be  installed  and  maintained 
in  all  occupancies  in  Use  Group  R-l. 

917.4.6  Use  Group  R-2:  A  fire  protective 
signaling  system  shall  be  installed  and  maintained 
in  all  occupancies  in  Use  Group  R-2  containing 
1 3  or  more  dwelling  units  or  where  any  dwelling 
unit  is  located  more  than  three  stories  above  the 
lowest  level  of  exit  discharge  or  more  than  one 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


159 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


story  below  the  highest  level  of  exit  discharge  of 
exits  serving  the  dwelling  unit. 

917.5  Location:  Manual  fire  alarm  boxes  shall  be 
located  not  more  than  five  feet  (1524  mm)  from  the 
entrance  to  each  exit.  Manual  fire  alarm  boxes  shall 
be  located  in  each  story  including  basements.  In 
buildings  of  use  group  A  where  a  stage  is  provided, 
a  manual  fire  alarm  box  shall  be  located  next  to  the 
lighting  control  panel. 

Exception: 

1.  In  buildings  of  use  group  A,  assembly 
occupancy,  and  where  approved  by  the  local  fire 
department,  manual  fire  alarm  boxes  may  be 
omitted  at  exits  and  any  other  required  locations, 
but  shall  be  provided  at  constantly  attended 
locations  such  as  ticket  booths,  refreshment 
facilities,  bars,  etc.  Where  the  building  official 
determines  that  it  is  impractical  to  have  a 
constantly  attended  location  in  an  assembly 
occupancy  other  than  a  theater,  manual  fire  alarm 
boxes  shall  be  provided  at  each  required  building 
exit. 

2.  Manual  fire  alarm  boxes  are  not  required  in  an 
occupancy  in  Use  Group  B  where  the  height  of 
the  building  is  70  feet  or  less  above  the  lowest 
level  of  fire  department  vehicle  access  and  the 
building  is  equipped  throughout  with  an 
automatic  sprinkler  system,  and/or  an  automatic 
fire  detection  system  or  combination  thereof,  in 
accordance  with  780  CMR  906.0 

917.5.1  Manual  fire  alarm  boxes:  The  height  of 
the  manual  fire  alarm  boxes  shall  be  a  minimum 
of  42  inches  (1067  mm)  and  a  maximum  of  54 
inches  (1372  mm)  measured  vertically,  from  the 
floor  level  to  the  activating  handle  or  lever  of  the 
box.  Manual  fire  alarm  boxes  shall  be  red  in 
color.  In  all  occupancies  in  Use  Group  1-3,  the 
manual  fire  alarm  boxes  shall  be  permitted  to  be 
locked  in  areas  where  staff  is  present  whenever 
such  areas  are  occupied  and  keys  are  readily 
available  to  unlock  the  boxes,  or  the  boxes  shall 
be  located  in  a  manned  staff  location  which  has 
direct  supervision  of  the  sleeping  area. 

Exception:  Where  521  CMR,  Architectural 
Access  Board  regulations  apply,  manual  fire 
alarm  box  height  shall  be  as  prescribed  in 
521  CMR. 

917.6  Power  supply:  The  primary  and  secondary 
power  supply  for  the  fire  protective  signaling  system 
shall  be  provided  in  accordance  with  NFPA  72  listed 
in  Appendix  A. 

917.7  Wiring:  All  wiring  shall  conform  to  the 
requirements  of  NFPA  72  and  527  CMR  12.00: 
Massachusetts  Electrical  Code  listed  in  Appendix  A 
Wireless  systems  utilizing  radio  frequency 
transmitting  devices  shall  comply  with  the  special 


requirements  for  supervision  of  low-power  wireless 
systems  in  NFPA  72  listed  in  Appendix  A. 

917.7.1  Activation:  The  alarm  notification 
appliances  shall  be  automatically  activated  by  all 
of  the  following  where  provided: 

1.  Smoke  detectors,  other  than  single-  and 
multiple-station  smoke  detectors,  as  required 
by  780  CMR  919.0; 

2.  Sprinkler  water-flow  devices; 

3.  Manual  fire  alarm  boxes;  and 

4       Other  approved  types  of  automatic  fire 
detection       devices,        extinguishing,        or 
suppression  systems. 
Exceptions: 

1.  Smoke  detectors  in  an  occupancy  in  Use 
Group  1-3  are  permitted  to  actuate  an  audible 
alarm-indicating  appliance  at  a  constantly 
attended  location  and  are  not  required  to 
activate  a  general  alarm. 

2.  Audible  alarms  in  buildings  of  Use 
Group  A  with  an  occupant  load  greater  than 
300  persons  shall  sound  only  in  a  constantly 
attended  receiving  station  within  the 
building  for  purposes  of  initiating  emergen- 
cy action.  Occupant  notification  shall  be  by 
means  of  either  voice  or  prerecorded 
message  announcement  initiated  by  the 
person  in  the  constantly  attended  receiving 
station  and  in  accordance  with  780  CMR 
917.9.  In  buildings  of  Use  Group  A  utilizing 
reduced  lighting  levels  on  a  regular  basis, 
lights  providing  normal  lighting  levels  shall 
be  activated  simultaneously  with  the 
beginning  of  the  voice  or  prerecorded 
message  announcement.  Where  the  building 
official  determines  that  it  is  impractical  to 
have  a  constantly  attended  location  in  an 
assembly  occupancy  the  fire  alarm  system 
shall  be  arranged  to  automatically  provide 
prerecorded  evacuation  instructions. 

3.  For  mixed  use  group  occupancies  that 
contain  an  A  use  group  the  use  group  A  area 
shall  be  in  accordance  with  780  CMR 
917.7.1  exception  2. 

917.7.1.1  Length  of  evacuation  signal: 
Automatic  deactivation  of  audible  and  visible 
alarms  shall  not  be  allowed. 

Exception:  Automatic  deactivation  of 
audible  alarms  after  a  period  of  operation  of 
15  minutes  shall  be  permitted  when 
approved  by  the  local  fire  department. 
Automatic  deactivation  of  audible  alarms 
shall  only  be  permitted  when  the  fire  alarm 
system  is  supervised  in  accordance  with 
780  CMR  923.2  or  by  an  approved  auxiliary 
fire  alarm  system  in  accordance  with  NFPA 
72. 

917.7.2  Presignal  or  positive  alarm  sequence 
system:    Presignal   or  positive  alarm   sequence 


160 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


systems  shall  not  be  installed  unless  approved  by 
the  code  official  and  by  the  local  fire  department. 
Where  a  presignal  or  positive  alarm  sequence 
system  is  installed,  24-hour  supervision  by 
trained  personnel  shall  be  provided  at  a  location 
approved  by  the  local  fire  department,  in  order 
that  the  alarm  signal  can  be  actuated  in  the  event 
of  fire  or  other  emergency. 

917.7.3  Zones:  Each  floor  shall  be  zoned 
separately  and  a  zone  shall  not  exceed  20,000 
square  feet  (1860  m2).  The  length  of  any  zone 
shall  not  exceed  300  feet  (91440  mm)  in  any 
direction.  A  zoning  indicator  panel  and  the 
associated  controls  shall  be  provided  in  a  location 
approved  by  the  local  fire  department.  Where 
individually  addressable  alarm  initiating  devices 
are  used,  a  single  circuit  (  or  pathway  )  shall  not 
exceed  the  above  size  limitations  unless  the 
circuit  is  a  Class  A  circuit,  and  the  style  and 
device  loading  meets  the  requirements  for 
proprietary  systems  as  listed  in  NFPA  72.  Where 
individually  addressable  alarm  initiating  devices 
are  logically  combined  into  groups  for 
annunciation  purposes,  the  above  zone  size 
limitations  shall  apply  to  the  group.  The  local  fire 
department  shall  approve  all  zone  and  point 
descriptions.  The  visual  zone  indication  shall  lock 
in  until  the  system  is  reset  and  shall  not  be 
canceled  by  the  operation  of  an  audible  alarm  - 
silencing  switch.  In  buildings  that  have  floors 
located  more  than  70  feet  above  the  lowest  level 
of  fire  department  vehicle  access  which  are 
occupied  for  human  occupancy,  a  separate  zone 
by  floor  shall  be  provided  for  the  following  types 
of  alarm-initiating  devices  where  provided: 

1.  Smoke  detectors; 

2.  Sprinkler  water-flow  devices; 

3.  Manual  fire  alarm  boxes;  and 

4.  Other  approved  types  of  automatic  fire 
detection  devices,  extinguishing,  or 
suppression  systems. 

Exceptions: 

1 .  Automatic  sprinkler  system  zones  shall  not 
exceed  the  area  permitted  by  NFPA  1 3  listed  in 
Appendix  A. 

2.  Duct  type  smoke  detectors  shall  be 
separately  identified  with  a  remote  test/ 
indicator  station.  The  location  of  the  remote 
test/indicator  shall  be  approved  by  the  local 
fire  department. 

917.8  Alarm  notification  appliances:  Alarm 
notification  appliances  of  the  approved  type  shall  be 
provided. 

917.8.1  Visible  alarms:  Visible  alarm  notification 
appliances  shall  be  provided  in  accordance  with 
NFPA  72  and  521  CMR  in  public  and  common 
areas  of  all  buildings  and  areas  of  buildings 
housing  the  hearing  impaired  and  where  required 
by  521  CMR.  In  occupancies  in  Use  Groups  I-  1 


and  R-  1,  all  required  accessible  sleeping  rooms 
and  suites  plus  an  additional  number  of  sleeping 
rooms  or  suites  in  accordance  with  Table  917.8.1 
shall  be  provided  with  a  visible  alarm  notification 
appliance,  activated  by  both  the  in-room  smoke 
detector  and  the  building  fire  protective  signaling 
system. -In  hospital  intensive  care  units,  special 
care  units  and  operating  rooms,  the  audible  signal 
need  not  be  sounded;  however  a  visual  alarm  shall 
be  displayed  with  an  approved  device. 


Table  917.8.1 
VISIBLE  AND  AUDIBLE  ALARMS 

Number  of  sleeping 
rooms  or  suites 

Sleeping 
visible 

rooms  or  suites  with 
and  audible  alarms 

6  to  25 
26  to  50 

1 

51  to  75 
76  to  100 

3 
4 

101  to  150 
151  to  200 
201  to  300 

5 
6 

7 

301  to  400 
40 1  to  500 

8 
9 

501  to  1,000 
1 ,00 1  and  over 

20  plus 

2%  of  total 
1  for  each  1 00  over 
1,000 

917.8.2  Audible  alarms:  Audible  alarm 
notification  appliances  shall  be  provided  and  shall 
sound  a  distinctive  sound  which  shall  not  be  used 
for  any  purpose  other  than  that  of  a  fire  alarm. 
The  audible  alarm  notification  appliances  shall 
provide  a  sound  pressure  level  of  15  dBA  above 
the  average  ambient  or  5  dBA  above  the  maxi- 
mum sound  level  having  a  duration  of  at  least  60 
seconds  (  whichever  is  greater  )  sound  level  in 
every  occupied  space  within  the  building.  The 
minimum  sound  pressure  levels  shall  be:  70  dBA 
in  occupancies  in  Use  Groups  R  and  1-1;  90  dBA 
in  mechanical  equipment  rooms;  and  60  dBA  in 
all  other  use  groups.  The  maximum  sound 
pressure  level  for  audible  alarm  notification 
appliances  shall  be  120  dBA  at  the  minimum 
hearing  distance  from  the  audible  appliance. 
917.8.2.1  All  audible  evacuation  signals  shall 
have  a  synchronized  three  -  pulse  temporal 
pattern  in  accordance  with  NFPA  72. 

917.9  Voice/alarm  signaling  system:  A  voice/alarm 
signaling  system  shall  be  provided  where  required 
by  other  sections  of  780  CMR.  When  activated  in 
accordance  with  780  CMR  917.7.1,  the  voice/alarm 
signaling  system  shall  automatically  sound  an  alert 
signal  to  all  occupants  within  the  building  on  a 
general  or  selective  basis  to  the  following  terminal 
areas:  elevators,  elevator  lobbies,  corridors,  exit 
stairways,  rooms  and  tenant  spaces  exceeding  1,000 
square  feet  (93  m2)  in  area;  dwelling  units  in 
occupancies  in  Use  Group  R-2;  and  guestrooms  or 
suites  in  occupancies  in  Use  Group  R-  1  The  fire 
command  station  shall  contain  controls  to  transmit 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


16! 


780  CMR:    STATE  BOARD  OF  BUTLDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


manually  an  evacuation  signal  and  voice  instructions 
on  a  selective  and  all-call  basis  to  the  terminal  areas 
indicated  herein.  The  voice/alarm  system  shall  be 
designed  and  installed  in  accordance  with  the 
provisions  of  780  CMR,  527  CMR  and  NFPA  72 
listed  in  Appendix  A. 

Exception:  A  distinctive  signal  in  lieu  of  a  voice 
alarm  is  permitted  in  an  occupancy  in  Use  Group 
ForS. 

917.9.1  The  sequence  of  operation  of  the  voice 
alarm  signaling  system  shall  be  as  follows: 

1.  Sound  an  alert  (pre-signal)  tone  (the  alert 
tone  shall  be  a  900  hertz  tone  pulsed  to 
produce  one  round  of  code  4  at  approximately 
one  second  intervals. 

2.  Activate  the  recorded  message  regarding 
the  evacuation  procedure.  The  alarm  and  com- 
munications system  shall  provide  a  pre-record- 
ed message  to  all  required  areas.  The  message 
shall  contain  the  following  information.  " 
attention  please.  The  signal  tone  you  have  just 
head  indicated  a  report  of  an  emergency  in  this 
building.  If  your  floor  evacuation  signal  sounds 
after  this  message,  walk  to  the  nearest  stairway 
and  leave  the  floor.  While  the  report  is  being 
verified,  occupants  on  other  floors  should 
await  further  instructions." 

This  message  shall  be  transmitted  three 
times. 

A  female  voice  shall  be  used  for  this 
message. 

3 .  Activate  the  evacuation  signal  on  the  floor 
of  incident  and  the  next  floor  above  and  below 
(the  evacuation  signal  shall  be  in  accordance 
with  780  CMR  917.8.2.1 

917.10  Acceptance  tests:  Upon  completion  of  the 
fire  protective  signaling  system,  all  alarm 
notification  devices  and  circuits,  alarm  indicating 
appliances  and  circuits,  supervisory-signal  initiating 
devices  and  circuits,  signaling  line  circuits,  and 
primary  and  secondary  power  supplies  shall  be 
subjected  to  a  100%  acceptance  test  in  accordance 
with  NFPA  72  listed  in  Appendix  A  and  780  CMR 
903.0. 

780  CMR  918.0  AUTOMATIC  FIRE 
DETECTION  SYSTEMS 

918.1  General:  Automatic  fire  detection  systems 
shall  be  of  an  approved  type  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR  and 
NFPA  72  listed  in  Appendix  A. 

918.2  Fire  Protection  Construction  documents: 

Where  an  automatic  fire  detection  system  is  required 
by   780   CMR,   the  fire  protection   construction 


doaimentsshail  show  the  location  and  number  of  all 
automatic  fire  detectors  with  specifications  of  the 
type  of  fire  detector,  proposed  zoning  and  a 
complete  sequence  of  operation  for  the  system.  The 
system  shall  be  installed  in  accordance  with 
780  CMR  918.0  and  shall  be  part  of  and  be  subject 
to  the  requirements  of  a  fire  protective  signaling 
system  specified  in  780  CMR  917.0.  (Also  see 
780  CMR  903.0) 

918.3  Approval:  All  devices,  combinations  of 
devices,  appliances  and  equipment  shall  be  approved 
for  the  fire  signaling  purpose  for  which  such 
equipment  is  used.  The  automatic  fire  detectors 
shall  be  smoke  detectors,  except  an  approved 
alternative  type  of  detector  shall  be  installed  in 
spaces  such  as  boiler  rooms  where,  during  normal 
operation,  products  of  combustion  are  present  in 
sufficient  quantity  to  actuate  a  smoke  detector. 

918.4  Where  required:  An  automatic  fire  detection 
system  shall  be  installed  and  maintained  in  full 
operating  condition  in  the  locations  described  in 
780  CMR  918.4.1  through  918.4.7. 

918.4.1  Use  Group  A-4:  An  automatic  fire 
detection  system  shall  be  installed  in  all 
occupancies  of  use  group  A-4. 

918.4.2  Use  Group  E:  An  automatic  fire 
detection  system  shall  be  installed  in  all 
occupancies  of  use  group  E. 

918.4.3  Use  Group  1-1:  An  automatic  fire 
detection  system  shall  be  installed  and  maintained 
in  all  occupancies  in  Use  Group  1-1 . 

918.4.4  Use  Group  1-2:  An  automatic  fire 
detection  system  shall  be  installed  and  maintained 
in  all  occupancies  in  Use  Group  1-2. 

Exception:  Occupancies  that  are  equipped 
throughout  with  an  automatic  sprinkler  system 
in  accordance  with  780  CMR  906.0  and  that 
comply  with  780  CMR  409.0. 

918.4.5  Use  Group  1-3:  An  automatic  fire 
detection  system  shall  be  installed  and  maintained 
in  all  resident  housing  areas  of  Use  Group  1-3. 
Smoke  detectors  shall  be  arranged  and  positioned 
to  prevent  damage  or  tampering  provided  that  the 
function  and  speed  of  detecting  a  fire  is  equivalent 
to  that  provided  by  the  spacing  and  arrangement 
requirements  of  NFPA  72  listed  in  Appendix  A. 

918.4.6  Use  Group  R-l:  An  automatic  fire 
detection  system  shall  be  installed  and  maintained 
throughout  all  occupancies  in  Use  Group  R-l  and 
in  accordance  with  table  918. 


162 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


TABLE  918 
RESIDENTIAL  FIRE  PROTECTION  REQUIREMENTS 


Use 
Group 

Number 
of  Units 

Umt  Occupant 
Protection 

Other  Occupant 
Protection 

Standby 
Power 

Manual 
Stations 

Zoned 

Provision  for  Fire 
Department  Notification 

R-3 

1  or  2 

Yes 
919.3.2 

Note  a 

Yes 
919.5 

N.A. 

N.A. 

N.A. 

R-i 

3  to  12 

Yes 
919.3.1 

Yes 

918.4.6 

Yes 
917.6 

Yes 
917.4  5 

N.A. 

N.A. 

R-2 

3  to  12 

Yes 
919.3.2 

Yes 
918.4.7 

Yes 
919.5 

Yes 
917.4.6 

N.A. 

N.A. 

R-l 

1 3  or  more 

Yes 
919.3.1 

Yes 
918.4.6 

Yes 
917.6 

Yes 

917.4.5 

Yes 
917.7.3 

Yes 
923.2 

R-2 

1 3  or  more 

Yes 
919.3.2 

Yes 
918.4.7 

Yes 
9195 

Yes 
917.4.6 

Yes 

917.7.3 

Yes 

923.2 

Note  a:  Where  common  areas  exist. 

Exceptions: 

1.  An  automatic  fire  detection  system  is  not 
required  in  buildings  that  do  not  have  interior 
corridors  serving  guestrooms  or  dwelling  units 
and  where  all  guestrooms  or  dwelling  units 
have  a  means  of  egress  door  opening  directly 
to  an  exterior  exit  access  which  leads  directly 
to  the  exits. 

2.  System  smoke  detectors  are  not  required  in 
guestrooms  or  dwelling  units  provided  that  the 
single-station  detectors  required  by  780  CMR 
919.3.1  are  connected  to  the  emergency 
electrical  system  and  are  annunciated  by 
guestroom  or  dwelling  unit  at  a  constantly 
attended  location  from  which  the  fire 
protective  signaling  system  is  capable  of  being 
manually  activated. 

3.  A  system  heat  detector  shall  be  required 
within  each  guest  room  or  dwelling  unit 
located  not  more  than  six  feet  from  each  door 
way  that  leads  to  an  interior  corridor  or  exit 
System  heat  detectors  shall  not  be  required 
where  the  guestroom,  or  dwelling  unit  is 
equipped  with  residential  sprinklers  that  when 
activated  will  activate  the  fire  protective 
signaling  system. 

918.4.7    Use   Group   R-2:    An  automatic  fire 
detection  system  shall  be  installed  and  maintained 
throughout  all  occupancies  in  use  group  R-2  and 
in  accordance  with  table  918. 
Exceptions: 

1.  An  automatic  fire  detection  system  is  not 
required  in  buildings  that  do  not  have  interior 
corridors  serving  guestrooms  or  dwelling  units 
and  where  all  guestrooms  or  dwelling  units 
have  a  means  of  egress  door  opening  directly 
to  an  exterior  exit  access  which  leads  directly 
to  the  exits. 

2.  System  smoke  detectors  are  not  required  in 
guestrooms  or  dwelling  units. 

3.  A  system  heat  detector  shall  be  required 
within  each  guest  room  or  dwelling  unit 
located  not  more  than  six  feet  from  each  door 
way  that  leads  to  an  interior  corridor  or  exit. 
System  heat  detectors  shall  not  be  required 


where  the  guestroom  or  dwelling  unit  is 
equipped  with  residential  sprinklers  that,  when 
activated,  will  activate  the  fire  protective 
signaling  system. 

918.5  Sprinklered  buildings  exception:  Buildings 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1  or 
780  CMR  906.2.2  are  not  required  to  be  equipped 
with  an  automatic  fire  detection  system,  but  are 
required  to  be  equipped  with  a  fire  protective 
signaling  system  that  conforms  to  780  CMR  917.0. 
This  exception  does  not  apply  to  Use  Groups  I,  R-l, 
R-2  ,  to  high-hazard  use  groups  in  accordance  with 
780  CMR  417.5.3,  to  special  amusement  buildings 
in  accordance  with  780  CMR  413.0,  or  to  single- 
station  smoke  detectors  as  required  in  780  CMR 
919.3 

918.6  Zones:  Zoning  shall  be  provided  in 
accordance  with  780  CMR  917.7.3. 

918.7  Alarm  verification:  Alarms  activated  by 
smoke  detectors  required  by  780  CMR  918.0  shall 
be  activated  by  a  single  smoke  detector  monitored 
by  an  alarm  verification  zone  or  an  approved 
equivalent  method. 

918.8  Local  control  functions:  Automatic  fire 
detectors  utilized  for  the  purpose  of  performing  local 
control  functions  shall  be  a  part  of  a  fire  protective 
signaling  system.  The  detector  shall,  upon 
actuation,  perform  the  intended  function  and  activate 
the  alarm  notification  devices  or  activate  a  visible 
and  audible  supervisory  signal  at  a  constantly 
attended  location. 

Exception:  In  buildings  not  required  to  be 
equipped  with  a  fire  protective  signaling  system, 
the  automatic  fire  detector  shall  be  powered  by 
normal  electrical  service  and,  upon  actuation, 
perform  the  intended  function.  The  detectors 
shall  be  located  in  accordance  with  NFPA  72 
listed  in  Appendix  A.  This  exception  does  not 
apply  to  smoke  detectors  required  for  elevator 
recall. 


9/1 9'97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


163 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


918.9  Access:  Access  shall  be  provided  to  each 
detector  for  periodic  inspection,  maintenance  and 
testing. 

780  CMR  919.0  SINGLE-  AND  MULTIPLE- 
STATION  SMOKE  DETECTORS 

919.1  General:  Single-  and  multiple-station  smoke 
detectors  shall  be  of  an  approved  type  and  shall  be 
installed  in  accordance  with  the  provisions  of 
780  CMR  and  NFPA  72  listed  in  Appendix  A. 

919.1.1  A  control  and  associated  equipment, 
single  or  multiple  station  alarm  devices  or  any 
combination  thereof  shall  be  permitted  to  be  used 
as  a  household  fire  warning  system  provided  that 
the  requirements  of  NFPA  72  Chapter  2  are  met. 

919.2  Fire  Protection  Construction  documents: 

Where  single-  and  multiple  station  smoke  detectors 
are  required  by  780  CMR,  the  fire  protection 
construction  documents  shall  show  the  location  and 
number  with  specifications  of  the  type  of  detector. 
(Also  see  780  CMR  903.0.) 

919.3  Where  required:  Single  and  multiple  station 
smoke  detectors  or  household  fire  warning  systems 
shall  be  installed  and  maintained  in  full  operating 
condition  in  the  locations  described  in  780  CMR 
919.3.1  through  919.3  3.  Any  smoke  detector 
located  within  20  feet  of  a  kitchen  or  within  20  feet 
of  a  bathroom  containing  a  tub  or  shower  shall  be  a 
photo  electric  type  smoke  detector. 

919.3.1  Use  Group  R-l:  Single  and  multiple 
station  smoke  detectors  or  household  fire  warning 
systems  shall  be  installed  and  maintained  in  the 
following  locations  in  Use  Group  R-  1 : 

1 .  In  all  sleeping  areas; 

2.  In  every  room  or  hallway  in  the  path  of  the 
means  of  egress  from  the  sleeping  area  to  the 
door  leading  from  the  guestroom  or  suite,  and 

3.  In  each  story  within  the  guestroom  or  suite, 
including  basements. 

Exception:  For  suites  or  guestrooms  or 
dwelling  unit  with  split  levels  and  without 
an  intervening  door  between  the  adjacent 
levels,  a  smoke  detector  installed  on  the 
upper  level  shall  suffice  for  the  adjacent 
lower  level  provided  that  the  lower  level  is 
less  than  one  full  story  below  the  upper 
level. 

919.3.2  Use  Groups  R-2,  R-3,  R-4  and  R-5 

Single  and  multiple  station  smoke  detectors  or 
household  fire  warning  systems  shall  be  installed 
and  maintained  in  all  occupancies  in  Use  Groups 
R-2,  R-3,  R-4  and  R-5  at  the  following  locations: 

1.  In  the  immediate  vicinity  of  bedrooms; 

2.  In  all  bedrooms;  and 

3.  In  each  story  within  a  dwelling  unit, 
including  basements 


4.  In  residential  units  1200  square  feet  or  more 
in  area  an  additional  automatic  fire  detector 
shall  be  provided  for  each  1200  square  feet  of 
area  or  part  thereof 

Exceptions: 

1  In  dwelling  units  with  split  levels  and 
without  an  intervening  door  between  the 
adjacent  levels,  a  smoke  detector  installed 
on  the  upper  level  shall  suffice  for  the 
adjacent  lower  level  provided  that  the  lower 
level  is  less  than  one  full  story  below  the 
upper  level. 

2.  In  buildings  equipped  throughout  with 
an  automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2  1,  906.2.2 
or  906.2.3,  smoke  detectors  are  not  required 
in  bedrooms  where  the  bedrooms  are 
equipped  with  residential  sprinklers. 

919.3.3   Use  Group   1-1:    Single  and   multiple 

station  smoke  detectors  or  household  fire  warning 

systems  shall  be  installed  and  maintained  in  all 

sleeping  areas  in  occupancies  in  Use  Group  I-  1 

Exception:  Where  the  building  is  equipped 

throughout  with  an  automatic  detection  system 

in  accordance  with  780  CMR  918  4. 

919.4  Interconnection:  Where  more  than  one 
detector  is  required  to  be  installed  within  an 
individual  dwelling  unit  in  an  occupancy  in  Use 
Group  R-2  or  R-3,  or  within  an  individual  guestroom 
or  suite  in  an  occupancy  in  Use  Group  R-l,  the 
detectors  shall  be  wired  in  such  a  manner  that  the 
actuation  of  one  alarm  will  actuate  all  of  the  alarms 
in  the  individual  unit. 

919.5  Battery  backup:  In  addition  to  the  required 
AC  primary  power  source,  required  smoke  detectors 
in  occupancies  in  Use  Groups  R-2,  R-3,  R-4,  R-5 
and  I- 1  shall  receive  power  from  a  battery  when  the 
AC  primary  power  source  is  interrupted. 

Exception:  In  buildings  equipped  throughout  with 
an  automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2.1,  906.2.2  or 

906.2.3. 

919.6  Acceptance  testing.  When  the  installation  of 
the  detectors  is  complete,  each  detector  -  and  all 
interconnecting  wiring  for  multiple-station  detectors 
shall  be  subject  to  a  100%  acceptance  test  in 
accordance  with  NFPA  72  listed  in  Appendix  A 

780  CMR  920.0  FTRE  EXTINGUISHERS 
920.1  Approval:  Portable  fire  extinguishers  shall 
bear  the  label  of  an  approved  agency,  be  of  an 
approved  type  and  be  installed  in  a  location  visible 
and  available  to  the  occupants. 


164 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


920.2  Where  required:  A  portable  fire  extinguisher 
shall  be  installed  in  the  following  locations  in 
accordance  with  NFiPA  10  listed  in  Appendix  A: 

1.  In  all  occupancies  in  Use  Group  A-  1,  A-2,  A- 
3,  B,  E,  1-2,  M,  R-  1  or  H; 

2.  In  all  areas  containing  commercial  kitchen 
exhaust  hood  systems; 

3.  In  all  areas  where  fuel  is  dispensed; 

4.  In  all  areas  where  a  flammable  or  combustible 
liquid  is  used  in  the  operation  of  spraying,  coating 
or  dipping; 

5.  In  all  occupancies  in  Use  Group  1-3  at  staff 
locations.  Access  to  portable  extinguishers  shall 
be  permitted  to  be  locked; 

6.  On  each  completed  floor  of  buildings  under 
construction,  other  than  occupancies  in  Use 
Group  R-3 . 

7.  In  any  laboratory,  shop  or  other  room 
occupied  for  similar  purposes;  and 

8.  Where  required  by  the  fire  prevention  code 
listed  in  Appendix  A. 

780  CMR  921.0  SMOKE  CONTROL 
SYSTEMS 

921.1  General:  Smoke  control  systems  required  by 
780  CMR  shall  conform  to  the  provisions  of 
780  CMR  921.0 

921.2  Design  criteria:  The  smoke  control  system 
shall  be  designed  to  keep  the  smoke  layer  interface 
above  the  highest  of  either  the  highest  unprotected 
opening  to  adjoining  spaces,  or  six  feet  (1829  mm) 
above  the  highest  floor  level  of  exit  access  open  to 
the  atrium  for  a  period  of  20  minutes.  The  limiting 
height  for  the  smoke  layer  interface  for  stages  shall 
be  in  accordance  with  780  CMR  412.3.8.2.  The 
limiting  height  of  the  smoke  interface  above  the 
floor  of  the  space  required  to  be  provided  with 
smoke  control  is  Zcr  .  Provisions  shall  also  be  made 
to  provide  for  smoke  removal  from  the  space  at  a 
rate  of  not  less  than  two  air  changes  per  hour  by 
means  of  natural  or  mechanical  ventilation. 

921.2.1  Passive  system:  Active  smoke  control  is 
not  required  where  it  is  shown  that  the  smoke 
interface  level  requirement  will  be  met  without 
operating  smoke  exhaust. 

921.2.1.1  Regular  spaces:  For  spaces  with  flat 
ceilings,  a  constant  horizontal  cross-sectional 
area  above  the  smoke  layer  interface,  and  an 
A/H  ratio  between  0.9  and  14,  the  following 
equation  shall  be  used  to  estimate  the  height  of 
the  interface  at  20  minutes 


Z=Q.67H-0.2m  In 

where: 


t  QV'H" 


Z  =    Height  from  floor  to  the  smoke  interface 

(feet). 
/  =     Time  for  interface  to  descent  to  Z;  Use 

1,200  seconds. 
H=  Height    of  the    space   required    to   be 

provided  with  smoke  control;  floor  to  flat 

ceiling  (feet). 
O  =  Steady  state  heat  release  rate;  Use  4,400 

Btu/sec.  where  the  primary  use  group  is 

M,    S-l    or  F-l.    Otherwise  use  2,000 

Btu/sec. 
A  =  Horizontal  cross-sectional   area  of  the 

above  ceiling-testing  space  being  filled 

(square  feet).  Maximum  A  to  be  used 

shall  be:  A=  \4H2. 
921.2.1.2  Irregular  spaces:  For  spaces  with 
sloped  or  irregular  ceilings,  A/H2  ratios  outside 
the  specified  range,  or  varying  cross  sections, 
the  filling  time  shall  be  determined  using 
numerical  integration  from  the  ceiling  to  the 
critical  smoke  interface.  The  following 
equations  shall  be  used  to  determine  the  rate  of 
smoke  production: 

Where   the   interface   level   is   above   the 
limiting  elevation  (Z[)  use: 

V  =  17.6QC'/3Z5/3  +  3.36Q 

Where   the   interface   level    is   below   the 
limiting  elevation  (z, )  use: 


V 


16.64QC3/5Z 


where: 

V  =  The  volumetric  rate  of  smoke  production 
(cubic  feet  per  minute). 

z,  =   Limiting  elevation  (ft)  =  0.533QC~5 

Qc  =  The  convective  portion  of  the  heat 
release  rate  shall  be  estimated  as  70 
percent  of  the  total  heat  release  rate,  Q. 

921.2.2  Mechanical  systems:  Where  the  smoke 
filling  predicted  in  780  CMR  921.2.1  does  not 
meet  the  design  criteria  of  780  CMR  921.2, 
mechanical  exhaust  shall  be  provided  to  maintain 
these  conditions. 

921.2.2.1  Exhaust  quantities:  Sufficient 
mechanical  exhaust  shall  be  provided  to 
maintain  the  smoke  layer  interface  at  or  above 
the  critical  elevation  for  the  20-minute  period. 
The  volumetric  rate  of  smoke  production  (V) 
shall  be  determined  by  the  equations  in 
780  CMR  921.2.1.2.  If  the  rate  of  smoke 
exhaust  is  less  than  the  rate  of  smoke 
production,  the  minimum  exhaust  rate  to  be 
supplied  for  smoke  control  shall  be  determined 
in  accordance  with  Table  921.2.2. 1. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


165 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  921.2.2.1 

MINIMUM  EXHAUST  RATE  ADJUSTMENT 

FACTOR3 


t/t0 

Z/H 

Ve/V 

0.25 

0.35 

0.50 

0.70 

0.85 

0.95 

0.2 

1.12 

0.19 

1.30 

1.55 

1.89 

2.49 

0.3 

1.14 

1.21 

1.35 

1.63 

2.05 

2.78 

0.4 

1,16 

1.24 

1.40 

1.72 

2.24 

3.15 

0.5 

1.17 

1.28 

1.45 

1.84 

2.48 

3.57 

0.6 

1.20 

1.32 

1.52 

2.00 

2.78 

4.11 

0.7 

0.23 

1.36 

1.61 

2.20 

3.17 

4.98 

08 

1  26 

1.41 

171 

:4n 

371 

6.25 

Note  a.  Notation: 

Z=     Design  height  of  smoke  layer  interface  above 

fire  source. 
H=    Ceiling  height  above  fire  source. 
/  =     Time  for  smoke  layer  interface  to  descend  to 

Z(vvith  exhaust)  (seconds). 
t0  =    Value  of  t  in  absence  of  smoke  exhaust  (see 

780  CMR  921.2.1.1  or  921  2.1.2)  (seconds). 
V  =  Smoke  control  exhaust  rate  (minus  any  airflow 

into  the  smoke  layer  other  than  that  from  the 

plume). 
V=    Volumetric  smoke  production  rate   (from  the 

equations  in  780  CMR  921.2.1.2). 

921.2.3  Operation:  The  smoke  control  system 
shall  be  a  dedicated  system  or  shall  be  integrated 
with  the  mechanical  ventilation  system  of  the 
building.  Operation  of  the  smoke  control  system 
shall  automatically  shut  down  all  systems  and 
devices  which  interfere  with  the  effective 
operation  of  the  smoke  control  system.  Where  the 
mechanical  ventilation  jry5tem  is  designed  for 
smoke  control,  the  return  air  shall  be  moved 
directly  to  the  outside  without  recirculation  to 
other  areas  of  the  building. 

921.2.4  Alternative  systems:  An  engineered 
design  which  will  achieve  the  same  level  of 
smoke  control  as  described  in  780  CMR  921  is 
permitted  in  lieu  of  these  requirements. 

921.3  Smoke  removal:  Provisions  shall  be  made  to 
provide  ventilation  at  a  rate  of  at  least  two  air 
changes  per  hour  from  the  space  required  to  be 
provided  with  smoke  control.  This  ventilation  shall 
be  through  openable  vents,  separate  mechanical 
exhaust,  or  through  the  building  mechanical 
ventilation  system.  The  exhaust  inlets  shall  be 
located  a  minimum  of  six  feet  (1829  mm)  above  any 
exit  access  walkway  and  above  any  openings  into 
adjoining  spaces.  The  smoke  removal  system  shall 
be  activated  by  manual  controls  provided  for  fire 
department  use  unless  it  is  part  of  the  smoke  control 
system. 

921.4  Activation:  The  smoke  control  system  shall 
be  activated  by  actuation  of  the  following: 

J .    A  utomatic  sprinkler  system ; 

2.     Smoke  detectors  required  by  780  CMR  921 

that  comply  with  NFPA  72  listed  in  Appendix  A; 

and 


3.  Manual  controls  provided  for  fire  department 
use. 

Note:  The  smoke  control  system  shall  not  be 
activated  by  a  manual  fire  alarm  system. 

921.4.1  Manual  control:  Manual  controls  shall 
be  provided  at  a  location  approved  by  the  fire 
department. 

921.4.2  Smoke  detector  activation:  Where  the 
height  of  the  ceiling  of  the  space  required  to  be 
provided  with  smoke  control  exceeds  30  feet 
(9144  mm)  above  the  floor  of  the  space,  approved 
smoke  detectors  shall  be  provided  to  detect  smoke 
above  the  highest  floor  open  to  an  atrium  or  at  the 
highest  point  of  another  space  required  to  be 
provided  with  smoke  control.  The  installation  of 
smoke  detectors  shall  comply  with  780  CMR 
918.0. 

921.5  Standby  power:  All  equipment  required  to 
provide  smoke  control  in  floor  openings  connecting 
three  or  more  stories  and  stage  areas  in  accordance 
with  780  CMR  412.3.8.2  shall  be  equipped  with  a 
standby  source  of  power  that  complies  with 
527  CMR  12.00  as  listed  in  Appendix  A. 

921.6  Acceptance:  Any  required  smoke  control 
design  that  requires  operation  of  mechanical 
equipment  shall  be  functionally  tested  in  accordance 
with  780  CMR  921.6.2  until  proper  operation  of  all 
required  mechanical  equipment  and  controls  is 
demonstrated. 

921.6.1  System  operation  report:  Prior  to 
acceptance  testing,  a  report  of  the  required  system 
operations  shall  be  provided  to  the  code  official. 
The  following  items  shall  be  included  in  the 
report  if  part  of  the  required  system: 

1.  Identify  type(s)  of  smoke  control  activation 
signal(s),  such  as  sprinkler  waterflow,  smoke 
detection,  manual,  etc.,  and  associated  smoke 
control  system  operation(s)  that  are  activated 
by  the  signals. 

2.  Identify  building  area(s)  where  maximum 
mechanical  exhaust  to  the  outside  is 
implemented  and  supply  air  is  not  provided. 

3 .  Identify  building  area(s)  where  maximum 
air  supply  is  implemented  and  exhaust  to  the 
outside  is  not  provided. 

4.  Identify  fan(s)  which  shall  be  "On"  as 
required  to  implement  the  smoke  control 
system.  If  multiple  speed  fans  are  used,  the 
capacity  at  which  the  fans  shall  operate  in  the 
smoke  control  mode  shall  be  identified. 

5.  Identify  fan(s)  which  shall  be  "Off'  as 
required  to  implement  the  smoke  control 
system. 

6.  Identify  damper(s)  which  shall  be  "Open" 
to  implement  the  smoke  control  system. 

7.  Identify  damper(s)  which  shall  be  "Closed" 
to  implement  the  smoke  control  system. 


166 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 


8.  Identify  other  functions  required  to 
implement  the  smoke  control  system. 

9.  Identify  building  areas  with  smoke  and 
heat  vents  and  method  of  operation  of  vents. 

10.  If  required,  identify  the  type(s)  of  standby 
power  and  the  equipment  that  is  served. 

921.6.2  Testing  procedures:  The  acceptance  test 
procedure  shall  be  approved.  Acceptance  testing 
shall  be  conducted  in  the  presence  of  the  code 
official  or  shall  include  documentation  indicating 
that  all  mechanical  equipment,  control  sequences, 
devices  and  components  have  been  operationally 
tested  and  are  functioning  properly  in  accordance 
with  the  system  operation  report.  All  documentation 
from  operational  testing  shall  be  available  for 
inspection.  Acceptance  testing  shall  include  the 
following: 

1.  Prior  to  beginning  acceptance  testing,  all 
building  smoke  control  equipment  shall  be 
placed  in  the  normal  operating  mode. 

2.  Acceptance  testing  shall  demonstrate  that 
each  initiating  device,  fan,  damper  and  other 
required  equipment  is  operational  and  performs 
to  the  limits  and  capacity  required. 

3.  Acceptance  testing  shall  demonstrate  that 
correct  control  outputs  are  produced  for  a 
given  control  input  for  each  control  sequence 
specified  by  the  system  operation  report. 

4.  If  standby  power  is  required  for  the 
operation  of  the  smoke  control  system, 
acceptance  tests  shall  be  conducted  while  on 
both  normal  building  power  and  standby 
power. 

5.  Opening  of  smoke/heat  vents  shall  be 
demonstrated  if  the  vent  is  capable  of  being 
opened  in  a  manner  that  does  not  require 
destructive  testing. 


921.7  Elevators:  Except  when  otherwise  required 
by  524  CMR,  where  buildings  are  equipped  with  a 
mechanical  smoke  control  system  that  will  restrict 
smoke  and  hot  gases  from  entering  the  elevator  shaft 
in  the  fire  floor,  hoistway  venting  is  not  required.  In 
high-rise  buildings  equipped  with  this  system  and 
equipped  throughout  with  an  automatic  fire 
suppression  system,  the  one-hour  fireresistance  rated 
elevator  lobby  as  specified  in  7S0  CMR  403.8  is  not 
required. 

780  CMR  922.0  SMOKE  AND  HEAT  VENTS 

922.1  General:  Where  exit  access  travel  distance  is 
increased  in  accordance  with  780  CMR  1006.5.1, 
smoke  and  heat  vents  shall  be  constructed  and 
installed  in  accordance  with  780  CMR  922.0. 

922.2  Vent  size  and  spacing:  The  vent  area  and  the 
spacing  of  the  vents  shall  comply  with  Table  922.2. 

922.2.1  Releasing  devices:  Smoke  and  heat  vents 
shall  open  automatically  by  activation  of  a  heat- 
responsive  device  rated  at  100°F  (38°C)  to  220°F 
(104°C)  above  ambient.  The  releasing  mechanism 
shall  be  capable  of  operation  such  that  the  vent 
shall  fully  open  when  the  vent  is  exposed  to  a 
time-temperature  gradient  that  reaches  an  air 
temperature  of  500°F  (260°C)  within  five 
minutes.  Vents  shall  be  capable  of  being  opened 
by  an  approved  manual  operation. 

922.3  Curtain  board  construction:  Curtain  boards 
shall  be  provided  to  subdivide  a  vented  building. 
Curtain  boards  shall  be  constructed  of  material  that 
will  resist  the  passage  of  smoke  and  is  consistent 
with  the  building  type  of  construction.  Curtain  board 
location  and  depth  shall  comply  with  Table  922.2. 
The  bottom  of  the  curtain  board  shall  be  level. 


Table  922.2 

SMOKE  AND  HEAT  VENT  SIZE  AND 

SPACINGb 


Use 
Group 

Hazard 

classsiftcation  of 

contents 

Vent  height 

above  the 

floor,  H 

(feet) 

Minimum 
curtain  board 

depth  from 

vent  bottom 

(feet) 

Maximum 
area  formed 

by  curtain 

boards 

(square  feet) 

Vent  area  to 

floor  area 

ratio 

Maximum 

spacing  of 

vent  centers 

(feet) 

Maximum 

distance 

from  wall  of 

curtain 
boards  (feet) 

Maximum 
distance 
between 
curtain 
boards 

F-l 

- 

- 

0.2XH 
but  24 

50,000 

1:100 

120 

60 

8XH 
but  s  250  feet 

S-l 

I  through  IV 

20  or  less 

6 

10.000 

1:100 

100 

60 

8XH 

S-l 

I  through  IV 

Over  20  to 
40 

6 

8,000 

1:75 

100 

55 

8XH 
but  <  250  feet 

S-l 

I  through  IV 

20  or  less 

4 

3,000 

1:75 

100 

55 

8XH 

S-l 

I  through  IV 

Over  20  to 
40 

4 

3,000 

1:50 

100 

50 

8XH 
but  s  250  feet 

S-l 

V 

20  or  less 

6 

6,000 

1:50 

100 

50 

8XH 

S-l 

V 

Over  20  to 
30 

6 

6,000 

1:40 

90 

45 

8XH 

S-l 

V 

30  or  more 

4 

2,000 

1:30 

75 

40 

8XH 
but  -_  100  feel 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


167 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Note  a.    See  NFiPA  23 1  C  listed  in  Appendix  A  for  classification  of  Contents  Class  1  through  IV  Class  V  commodities 
are  products  that  present  special  fire  hazards  beyond  those  of  Class  I,  II.  Ill  or  IV,  such  as  aerosols,  foam  plastic,  PVC, 
PU,  PS  and  asphalt  paper. 
Note  b.    1  foot  =  304.8  mm;  1  square  foot  =  0.093  m  . 


780  CMR  923.0  SUPERVISION 

923.1  Fire  suppression  systems:  All  automatic 
fire  suppression  systems  required  by  780  CMR  shall 
be  supervised  by  one  of  the  following  methods 
below. 

1.  A  UL  listed  or  FM  approved  Central-Station 
Service  in  accordance  with  NFPA  72  listed  in 
Appendix  A  only  for  those  occupancies  listed  in 
780  CMR  903.2.2. 

2.  Approved  proprietary  supervising  station 
system,  in  accordance  with  NFPA  72  or  an 
approved  remote  supervising  station  system  in 
accordance  with  NFPA  72  . 

3.  Alarm  signals  to  an  approved  Auxiliary  Fire 
Alarm  System  in  accordance  with  NFPA  72,  with 
supervisory  signals  supervised  by  one  or  two 
above  or  at  a  constantly  attended  location 
approved  by  the  local  fire  department,  having 
personnel  on  duty  trained  to  recognize  the  type  of 
signal  received  and  to  take  prescribed  action.  This 
shall  be  permitted  to  be  a  location  different  from 
that  at  which  alarm  signals  are  received. 

Exceptions: 

1.  Underground  gate  valves  with  roadway 
boxes. 

2.  Halogenated  extinguishing  systems  that  are 
not  an  integral  part  of  a  required  automatic  fire 
suppression  system. 

3.  Carbon  dioxide  extinguishing  systems  that 
are  not  an  integral  part  of  a  required  automatic 
fire  suppression  system. 

4.  Dry-  and  wet-chemical  extinguishing 
systems. 

5.  Limited  area  sprinkler  systems  (see 
780  CMR  907.6.3). 

6.  Occupancies  in  Use  Group  R  complying 
with  780  CMR  906.2.2  and  supervised  in 
accordance  with  NFPA  13R  listed  in 
Appendix  A. 

923.1.1  Re-transmission  of  alarm  signals 
received  by  central  stations:  In  all  cases,  central 
stations  shall  re-transmit  alarm  signals  within  90 
seconds  of  receipt,  to  the  fire  department  having 
jurisdiction. 

923.2  Fire  protective  signaling  systems:  All  fire 
protective  signaling  systems  required  by  780  CMR 
shall  be  supervised  by  one  of  the  following  methods 
below: 

1.  A  UL  listed  or  FM  approved  Central-Station 
Service  in  accordance  with  NFPA  72  listed  in 
Appendix  A  only  for  the  following  occupancies: 

Building  types  subject  to  the  provisions  of 

923.2.1: 

(a)    High-rise  buildings. 


(b)  Buildings  and  structures  of  Use  Group  A 
with  a  total  occupant  load  exceeding  1000. 

(c)  Buildings  and  structures  of  Use  Group  H. 

(d)  Use  Group  1-2  and  1-3  except  1-2  Uses 
provided  for  in  780  CMR  424. 

(e)  Bulk  Merchandising/Retail  occupancies 
(see  780  CMR  426.0). 

2.  Approved  proprietary  supervising  station 
system,  in  accordance  with  NFPA  72  or  an 
approved  remote  supervising  station  system  in 
accordance  with  NFPA  72  . 

3.  Alarm  signals  to  an  approved  Auxiliary  Fire 
Alarm  System  in  accordance  with  NFPA  72,  with 
supervisory  signals  supervised  by  one  or  two 
above  or  at  a  constantly  attended  location 
approved  by  the  local  fire  department,  having 
personnel  on  duty  trained  to  recognize  the  type  of 
signal  received  and  to  take  prescribed  action.  This 
shall  be  permitted  to  be  a  location  different  from 
that  at  which  alarm  signals  are  received. 

Exceptions: 

1 .  For  use  group  R  see  table  918 

2.  Single-  and  multiple-station  detectors  as 
required  by  780  CMR  919.0. 

3.  Smoke  detectors  in  occupancies  in  Use 
Group  1-3  (see  780  CMR  917.7.1). 

4.  Smoke  detectors  in  patient  sleeping  rooms 
in  occupancies  in  Use  Group  1-2  (see 
780  CMR  409.5.1). 

5.  Fire  protective  signaling  systems  in 
occupancies  in  Use  Groups  H. 

923.2.1  Re-transmission  of  alarm  signals 
received  by  central  stations:  In  all  cases,  central 
stations  shall  re-transmit  alarm  signals  within  90 
seconds  of  receipt,  to  the  fire  department  having 
jurisdiction. 

780  CMR  924.0  FIRE  PUMPS 

924.1  General  Where  fire  pumps  are  required  to  be 
installed  as  part  of  a  required  or  non-required 
system(s),  the  fire  pump(s)  shall  be  designed  and 
installed  in  accordance  with  527  CMR  12.00  and 
NFPA  20  as  listed  in  Appendix  A. 

924.2  Rooms:  Fire  pumps  and  all  related  equipment 
shall  be  located  in  a  dedicated  room  meeting  the 
physical  and  environmental  features  of  NFPA  20 
listed  in  Appendix  A,  and  enclosed  with  not  less 
than  two  hours  fire  resistive  construction.  Fire 
pumps  rooms  shall  have  either  direct  access  to  the 
room  from  grade  or  access  by  a  two  hour  rated 
passageway  and  shall  be  properly  secured  from 
unauthorized  entry. 


168 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FIRE  PROTECTION  SYSTEMS 

924.3  Emergency  power:  All  fire  pumps  shall  be  2.    Buildings  and  structures  of  Use  Group  A,  with 

provided  with  emergency  power  when  installed  in  a  total  occupant  load  of  more  than  300  occupants, 

the  following  types  of  buildings  or  use  groups.  3.    Buildings  and  structures  of  Use  Group  E,  with 

Emergency    power    equipment    installation    shall  a  total  occupant  load  of  more  than  300  occupants, 

conform  to  527  CMR  12.00  and  NFPA  20  as  listed  4.    Buildings  and  structures  of  Use  Group  H. 

in  Appendix  A  5.     Buildings  and  structures  of  Use  Group  I, 

1.       High-rise  buildings  as  defined  by  M.G.L.  having  surgery  or  treatment  areas. 

c.  148  §  26A  and  780  CMR. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  169 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


< 


{ 


170  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  10 


MEANS  OF  EGRESS 


780  CMR  1001.0  GENERAL 

1001.1  Scope:  The  provisions  of  780  CMR  10  shall 
control  the  design,  construction  and  arrangement  of 
building  elements  required  to  provide  a  reasonably 
safe  means  of  egress  from  all  structures. 

1001.2  Modification    of   egress    requirements 

Where  strict  compliance  with  the  provisions  of 
780  CMR  is  not  practical,  the  code  official  shall 
approve  alternative  means  of  egress  which  will 
accomplish  the  same  purpose,  by  the  procedure 
established  in  780  CMR  1  for  modification  of 
780  CMR  or  by  adoption  of  approved  rules 

1001.3  Minimum  requirements:  It  shall  be 
unlawful  to  alter  any  building  or  structure  in  any 
manner  that  will  reduce  the  number  of  exits  or  the 
capacity  of  exits  below  the  requirements  of 
780  CMR  for  new  buildings  of  the  proposed 
occupancy 

780  CMR  1002.0  DEFINITIONS 
1002.1  General     The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  10  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Aisle  accessway  That  portion  of  an  exit  access 
which  provides  a  path  of  travel  to  an  aisle  (see 
780  CMR  1012  0). 

Alternating  tread  stairway  A  stair  that  has  a  series 
of  steps  between  50°  and  7'0°  (0.87  and  1.22  rad) 
from  honzontal.  usually  attached  to  a  center 
support  rail  in  an  alternating  manner  so  that  the 
user  of  the  stairs  never  has  both  feet  on  the  same 
level  at  the  same  time  (see  780  CMR  1014.6.6). 

Bleachers  A  grandstand  where  the  seats  are  not 
provided  with  backrests  (see  780  CMR  1013.0.) 

Common  path  of  travel  That  portion  of  exit  access 
which  the  occupants  are  required  to  traverse 
before  two  separate  and  distinct  paths  of  travel  to 
two  exits  are  available.  Paths  that  merge  are 
common  paths  of  travel.  A  common  path  of  travel 
is  measured  the  same  as  travel  distance  but 
terminates  at  that  point  where  two  separate  and 
distinct  routes  become  available  (see  780  CMR 
1011.2.1). 

Corridor  .An  enclosed  passageway  which  limits  the 
means  of  egress  to  a  single  path  of  travel  (see 
780  CMR  1011.0). 


Exit  That  portion  of  a  means  of  egress  which  is 
separated  from  all  other  spaces  of  a  building  or 
structure  by  construction  and  opening  protectives 
as  required  for  exits  to  provide  a  protected  way  of 
travel  to  the  exit  discharge  (see  780  CMR 
1006.0).  Exits  include  exterior  exit  doors,  exit 
stairways  (see  780  CMR  1014.0  and  1015.0).  exit 
passageways  (see  780  CMR  1020.0)  and 
horizontal  exits  (see  780  CMR  1019.0). 

Exit  access.  Exit  access  is  that  portion  of  a  means  of 
egress  which  leads  to  an  entrance  to  an  exit  (see 
780  CMR  1011.0) 

Exit  discharge.  That  portion  of  a  means  of  egress 
between  the  termination  of  an  exit  and  a  public 
way  (see  780  CMR  1006.3). 

Exit  discharge,  level  of  The  horizontal  plane 
located  by  the  point  at  which  an  exit  terminates 
and  an  exit  discharge  begins  (see  780  CMR 
1006.3.1). 

Exit,  horizontal  A  way  of  passage  from  one 
building  to  an  area  of  refuge  in  another  building 
on  approximately  the  same  level,  or  a  way  of 
passage  through  or  around  a  wall  or  partition  to  an 
area  of  refuge  on  approximately  the  same  level  in 
the  same  building,  which  affords  safety  from  fire 
or  smoke  from  the  area  of  incidence  and  areas 
communicating  therewith  (see  780  CMR  1019.0). 

Floor  area,  gross  Gross  floor  area  shall  be  the  floor 
area  within  the  perimeter  of  the  outside  walls  of 
the  building  under  consideration,  without 
deduction  for  hallways,  stairs,  closets,  thickness 
of  walls,  columns  or  other  features  (see  780  CMR 
1008.0). 

Floor  area,  net:  To  determine  the  number  of 
persons  for  whom  exits  are  to  be  provided,  the  net 
floor  area  shall  be  the  actual  occupied  area  and 
shall  not  include  unoccupied  accessory  areas  or 
thickness  of  walls  (see  780  CMR  1008.0) 

Grade  halhvay,  grade  lobby,  grade  passageway:  An 

enclosed  hallway  or  corridor  that  is  an  element  of 
an  exit:  and  terminates  at  a  street  or  an  open  space 
or  court  communicating  with  a  street  (see 
780  CMR  1020.0). 

Grandstand  A  structure  providing  tiered  or  stepped 
seating  (see  780  CMR  1013.0). 

Means  of  egress:  A  continuous  and  unobstructed 
path  of  travel  from  any  point  in  a  building  or 


9;  1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


171 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


structure  to  a  public  way.  A  means  of  egress 
consists  of  three  separate  and  distinct  parts:  the 
exit  access,  the  exit,  and  the  exit  discharge  A 
means  of  egress  comprises  the  vertical  and 
horizontal  means  of  travel  and  shall  include 
intervening  room  spaces,  doors,  hallways, 
corridors,  passageways,  balconies,  ramps,  stairs, 
enclosures,  lobbies,  horizontal  exits,  courts  and 
yards  (see  780  CMR  1006.0). 

Occupant  load:  The  total  number  of  persons  that 
are  permitted  to  occupy  a  building  or  portion 
thereof  at  any  one  time  (see  780  CMR  1008.0) 

Public  way:  Any  street,  alley  or  other  parcel  of  land 
open  to  the  outside  air  leading  to  a  public  street, 
which  has  been  deeded,  dedicated  or  otherwise 
permanently  appropriated  to  the  public  for  public 
use  and  which  has  a  clear  width  and  height  of  not 
less  than  ten  feet  (3048  mm). 

Slidescape:  A  straight  or  spiral  chute,  erected  on  the 
interior  or  exterior  of  a  building,  which  is 
designed  as  a  means  of  egress  direct  to  a  street  or 
other  public  way  (see  780  CMR  1026.0). 

Smokeproof  enclosure  An  enclosed  stairway,  with 
access  from  the  floor  area  of  the  building  either 
through  outside  balconies  or  ventilated  vestibules, 
opening  on  a  street,  yard  or  open  court,  and  with 
a  separately  enclosed  direct  exit  to  the  street  at  the 
grade  floor  (see  780  CMR  1015.0). 

Stairway.  One  or  more  flights  of  stairs,  and  the 
necessary  landings  and  platforms  connecting 
them,  to  form  a  continuous  and  uninterrupted 
passage  from  one  floor  to  another  (see  780  CMR 
1014.0). 

Winder:  A  step  in  a  winding  stairway  (see 
780  CMR  1014.6.3). 

780  CMR  1003.0  CONSTRUCTION 
DOCUMENTS 

1003.1  Arrangement  of  egress:  The  construction 
documents  shall  show  in  sufficient  detail  the 
location,  construction,  size  and  character  of  all  exits, 
together  with  the  arrangement  of  aisles,  corridors, 
passageways  and  hallways  leading  thereto  in 
compliance  with  the  provisions  of  780  CMR. 

1003.2  Number  of  occupants:  fn  other  than 
occupancies  in  Use  Groups  R-2,  R-3  and  1-1,  the 
construction  documents  and  the  application  for  a 
permit  shall  designate  the  number  of  occupants  to  be 
accommodated  on  every  floor,  and  in  all  rooms  and 
spaces  as  required  by  the  code  official  Unless 
otherwise  specified,  the  minimum  number  of 
occupants  to  be  accommodated  by  the  exits  shall  be 
determined  by  the  occupant  load  prescribed  in 
780  CMR  1008.0.  The  posted  occupant  load  of  the 


building  shall  be  limited  to  that  number  The  fire 
prevention  code  official  shall  be  informed  in  writing 
of  the  calculated  occupant  load. 

1003.3  Posted  occupant  load:  Every  assembly 
room  or  space  in  an  assembly  occupancy  shall  have 
the  approved  occupant  load  of  the  room  or  space 
posted  in  a  conspicuous  place,  near  the  main 
entrance  to  the  room  or  space  Rooms  or  spaces 
which  have  multiple-use  capabilities  shall  be  posted 
for  all  such  occupancies  All  posted  signs  shall  be  of 
an  approved  legible  permanent  design. 

780  CMR  1004.0  USE  GROUP  AND 
OCCUPANCY  REQUIREMENTS 

1004.1  New  buildings:  Every  building  and 
structure,  and  part  thereof,  hereafter  erected  shall 
have  the  prescribed  number  of  exits  of  one  or  more 
of  the  approved  types  defined  in  780  CMR  10. 
Exits,  in  combination  with  the  exit  access  and  exit 
discharge,  shall  provide  safe  and  continuous  means 
of  egress  to  a  street  or  to  an  open  space  with  direct 
access  to  a  street 

1004.2  Hazardous  Means  of  Egress: 

1004.2.1  Exit  Order/Hazardous  Means  of 
Egress:  In  any  existing  building  or  structure  not 
provided  with  exit  facilities  as  herein  prescribed 
for  new  buildings  and  in  which  the  exits  are 
deemed  hazardous  or  dangerous  to  life  and  limb, 
the  building  official  shall  declare  such  building 
dangerous  and  unsafe  in  accordance  with  the 
provisions  of  780  CMR  121.0. 

1004.2.2  Appeal  from  exit  order  Any  person 
served  with  any  order  pursuant  to  780  CMR 
3400.5  shall  have  the  remedy  prescribed  in 
780  CMR  121. 

1004.3  Multiple  occupancies  Where  a  building  is 
occupied  by  two  or  more  occupancies,  the  means  of 
egress  requirements  shall  apply  to  each  portion  of 
the  building  based  on  the  occupancy  of  space 

1004.4  Multiple  tenants:  Where  more  than  one 
tenant  occupies  any  one  floor  of  a  building  or 
structure,  each  tenant  shall  be  provided  with  direct 
access  to  approved  exits. 

780  CMR  1005.0  GENERAL  LIMITATIONS 

1005.1  Exits:  An  exit  shall  not  be  utilized  for  any 
purpose  that  interferes  with  its  function  as  a  means 
of  egress. 

1005.2  Floor  openings:  Manholes  or  floor  access 
panels  which  reduce  the  clearance  to  less  than  32 
inches  (813  mm)  shall  not  be  located  in  the  line  of 
means  of  egress. 


172 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


1005.3  Protruding  objects:  A  minimum  headroom 
of  80  inches  (2032  mm)  shall  be  provided  for  any 
walking  surface,  including  walks,  halls,  corridors, 
aisles  and  passageways.  Structural  elements, 
fixtures  or  furnishings  shall  not  project  from  either 
side  more  than  four  inches  (102  mm)  over  any 
walking  surface  between  the  heights  of  27  (686  mm) 
and  80  inches  (2032  mm)  above  the  walking  surface. 
A  free-standing  object  mounted  on  a  post(s)  or 
pylon(s)  shall  not  overhang  that  post(s)  or  pylon(s) 
more  than  12  inches  (305  mm)  where  the  lowest 
point  of  the  leading  edge  is  more  than  27  inches  (686 
mm)  and  less  than  80  inches  (2032  mm)  above  the 
walking  surface.  Door  closers  and  stops  shall  not 
reduce  headroom  to  less  than  78  inches  (1981  mm). 

1005.4  Floor  surface:  All  floors  of  corridors  and 
lines  of  means  of  egress  shall  have  a  slip-resistant 
surface. 

1005.5  Open-sided  floor  areas:  Guards  shall  be 
located  along  open-sided  walking  surfaces, 
mezzanines  and  landings  which  are  located  more 
than  30  inches  (762  mm)  above  the  floor  or  grade 
below.  The  guards  shall  be  constructed  in 
accordance  with  780  CMR  1021.0. 

Exception:  Guards  are  not  required  on  the 
loading  side  of  loading  docks  and  the  auditorium 
side  of  stages  and  raised  platforms. 

1005.6  Elevation  change:  Where  changes  in 
elevation  exist  in  exit  access  corridors,  exits  or  exit 
discharge,  ramps  shall  be  used  where  the  difference 
in  elevation  is  less  than  12  inches  (305  mm). 

Exception:  A  maximum  step  height  of  eight 
inches  (203  mm)  shall  be  permitted  for  buildings 
with  occupancies  in  Use  Groups  F,  H,  R  and  S  at 
exterior  doors  not  required  to  be  accessible  by 
521  CMR,  the  Rules  and  Regulations  of  the 
Architectural  Access  Board,  referenced  in 
780  CMR  11,  and  listed  in  Appendix  A. 

1005.7  Egress  elements  for  air  movement:  Exits 
and  exit  access  corridors  shall  not  be  used  as  supply 
or  return  air  ducts  or  plenums. 

Exceptions: 

1 .  The  restriction  on  the  use  of  the  space 
between  the  corridor  ceiling  and  the  floor  or 
roof  structure  above  as  a  return  air  plenum 
shall  not  apply  where  the  corridor  is  not 
required  to  be  of  fireresistance  rated 
construction  or  is  separated  from  the  plenum 
by  fireresistance  rated  construction  or  is 
located  within  a  dwelling  unit. 

2.  This  restriction  shall  not  apply  to  exit 
access  corridors  located  within  tenant  spaces 
that  are  1,000  square  feet  (92  nr  )  or  less  in 
area. 


780  CMR  1006.0  TYPES  AND  LOCATION 
OF  MEANS  OF  EGRESS 

1006.1  General:  All  approved  means  of  egress, 
including  doorways,  passageways,  corridors. 
interior  stairways,  exterior  stairways,  smokeproof 
enclosures,  ramps,  horizontal  exits,  bridges, 
balconies,  fire  escapes  and  combinations  thereof, 
shall  be  arranged  and  constructed  as  provided  for  in 
780  CMR. 

1006.2  Arrangement:  All  required  exits  shall  be  so 
located  as  to  be  discernable  with  unobstructed  access 
thereto. 

1006.2.1  Egress    through    adjoining   spaces: 

Egress  from  a  room  or  space  shall  not  open  into 
an  adjoining  or  intervening  room  or  area,  except 
where  such  adjoining  room  or  area  is  accessory  to 
the  area  served,  is  not  a  high-hazard  occupancy 
and  provides  a  direct  means  of  egress  to  an  exit. 
A  maximum  of  one  exit  access  shall  be  permitted 
to  pass  through  a  kitchen,  storeroom,  restroom, 
closet  or  similar  space  provided  that  passage 
through  such  space  is  not  the  only  means  of 
access  to  an  exit.  An  exit  access  shall  not  pass 
through  a  room  subject  to  locking.  Means  of 
egress  from  dwelling  units,  rooming  units, 
guestrooms  and  dormitory  units  shall  not  lead 
through  other  such  units,  or  through  toilet  rooms 
or  bathrooms 

1006.2.2  Assembly  buildings:  All  buildings 
occupied  for  assembly  purposes  shall  front  on  at 
least  one  street  on  which  the  main  entrance  and 
exit  discharge  shall  be  located.  Where  there  is  a 
single  main  entrance,  the  entrance  shall  be 
capable  of  serving  as  the  main  exit  and  shall 
provide  an  egress  capacity  for  at  least  one-half  of 
the  total  occupant  load.  In  addition  to  having 
access  to  a  main  exit,  each  level  of  an  occupancy 
in  Use  Group  A  shall  be  provided  with  additional 
exits  which  shall  provide  a  means  of  egress 
capacity  for  at  least  one-half  of  the  total  occupant 
load  served  by  that  level. 

1006.2.3  Skating  rinks:  Places  of  assembly  used 
for  skating  rinks  shall  not  be  located  below  the 
floor  nearest  grade. 

1006.2.4  Foyers  and  waiting  spaces:  The  term 
"foyer"  shall  mean  an  enclosed  space  surrounding, 
or  in  the  rear  of,  the  auditorium  of  a  theater  or 
other  place  of  assembly  which  is  completely 
separated  from  the  auditorium  and  is  used  as  an 
assembly  or  waiting  space  for  the  occupants.  In 
Use  Group  A-l,  a  foyer,  waiting  space  or  lobby 
shall  be  provided  with  a  net  floor  area,  exclusive 
of  stairs  or  landings,  of  not  less  than  1  Vi  square 
feet  (0.14  nr)  for  each  occupant  having  access 
thereto.  The  use  of  foyers  and  lobbies  and  other 
available  spaces  for  harboring  occupants  until 
seats  become  available  shall  not  encroach  upon 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


173 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


the  clear  floor  area  herein  prescribed  or  upon  the 
required  clear  width  of  front  exits. 

1006.2.4.1  Egress:  Where  the  foyer  is  not 
directly  connected  to  the  public  street  through 
the  main  lobby,  an  unobstructed  corridor  or 
passage  shall  be  provided  which  leads  to,  and 
equals  the  required  minimum  width  of,  main 
entrances  and  exits  A  mirror  shall  not  be 
placed  so  as  to  give  the  appearance  of  a 
doorway,  exit  or  passageway. 

1006.2.4.2  Gradient:  The  rear  foyer  shall  be 
at  the  same  level  as  the  back  of  the  auditorium 
and  the  means  of  egress  leading  therefrom 
shall  not  have  a  steeper  gradient  than  one  unit 
vertical  in  eight  units  horizontal  (1 :8). 

1006.2.4.3  Construction:  In  occupancies  in 
Use  Group  A-l,  other  than  motion  picture 
theaters,  the  fire  separation  assemblies 
separating  the  foyer  from  the  auditorium  and 
other  adjoining  rooms  and  spaces  shall  be 
constructed  with  not  less  than  a  two-hour 
fireresistance  rating.  Where  opening 
protectives  are  constructed  of  noncombustible 
materials,  a  fireresistance  rating  of  the  opening 
protectives  is  not  required. 

1006.3  Exit  Discharge:  All  exits  shall  discharge 
directly  at  a  public  way  or  at  a  yard,  court  or  open 
space  of  the  required  width  and  size  to  provide  all 
occupants  with  a  safe  access  to  a  public  way. 

1006.3.1  Level  of  exit  discharge  protection:  In 

all  buildings  having  habitable  or  occupiable 
stories  or  basements  below  grade,  the  floor/ceiling 
assemblies  and  supports  which  are  constructed 
below  the  level  of  exit  discharge  shall  provide  a 
fireresistance  rating  of  not  less  than  one  hour 
Exceptions: 

1 .  Occupancies  in  Use  Group  R-3. 

2.  Buildings  of  Type  1  construction. 

3.  Where  floor/ceiling  assemblies  and  supports 
are  constructed  of  Type  4  construction. 

4  Where  the  floor  areas  below  the  level  of 
exit  discharge  are  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1  or  906.2.2. 
5.  Occupiable  stories  or  basements  below 
grade  which  have  exits  that  discharge  directly 
to  grade. 

1006.4  Remote  location:  Wherever  more  than  one 
exit  is  required  from  any  room,  space  or  floor  of  a 
building,  such  exits  shall  be  placed  as  remote  from 
each  other  as  practicable,  and  shall  be  arranged  and 
constructed  to  provide  direct  access  in  separate 
directions  from  any  point  in  the  area  served  so  as  to 
minimize  the  possibility  that  both  exits  will  be 
blocked  by  any  one  fire  or  other  emergency 
condition. 


1006.4.1  Remoteness:   Where  two  exits  or  two 
exit  access  doors  are  required,  each  shall  be 
placed  a  distance  apart  equal  to  not  less  than  one- 
half  of  the   length   of  the   maximum    overall 
diagonal  dimension  of  the  building  or  area  to  be 
served    Where  exit  enclosures  are  provided  as  a 
portion  of  the  required  means  of  egress  and  are 
interconnected  by  a  corridor  conforming  to  the 
requirements  for  corridor  construction,  the  exit 
separation  distance  shall  be  measured  along  the 
line  of  travel  within  the  corridor.    In  all  other 
cases,  the  separation  distance  shall  be  measured  in 
a  straight  line  between  exits  or  exit  access  doors. 
Exception:   In  buildings  equipped  throughout 
with    an    automatic    sprinkler    system    in 
accordance  with  780  CMR  906.2. 1  or  906.2.2, 
the  minimum  separation  distance  shall  be  Vi  of 
the  length  of  the  maximum  overall  diagonal 
dimension 

1006.4.1.1  Three  or  more:  Where  three  or 
more  exits  or  exit  access  doors  are  required,  at 
least  two  exits  or  exit  access  doors  shall  be 
separated  as  provided  for  in  780  CMR 
1006.4.1. 

1006.5  Length  of  travel:  All  exits  shall  be  so 
located  that  the  maximum  length  of  exit  access 
travel,  measured  from  the  most  remote  point  to  an 
approved  exit  along  the  natural  and  unobstructed  line 
of  travel,  shall  not  exceed  the  distances  given  in 
Table  1006.5 

Table  1006.5 
LENGTH  OF  EXIT  ACCESS  TRAVEL3 


Without 

With 

Use  Group 

sprinkler  sysiem 

sprinkler  system 

(feet)° 

(feet)c 

A,B,E,F-'.,I-1.M,R, 

200 

250 

S-! 

F-2,  S-2 

300 

400 

H-l 

25 

75 

H-2 

50 

100 

H-3 

100 

150 

H-4 

125 

175 

1-2. 1-3 

150 

200 

Note  a.  See  the  following  sections  for  modification  to 
travel  distance  requirements. 

780  CMR  402.5.1:  For  the  exit  access  travel  distance 

in  malls. 

780  CMR  404.7:    For  the  exit  access  travel  distance 

limitation  through  an  atrium  space. 

780  CMR  416.6:    For  the  exit  access  travel  distance 

limitation  in  HPM  use  facilities. 

780  CMR  1006.5 .1:    For  increased  limitation  in  Use 

Groups  F-l  and  S-l. 

780  CMR  1006.5.2:    For  increased  limitation  in  Use 

Group  A-5. 

780  CMR  1010.3:  For  buildings  with  one  exit. 

780  CMR  3104.9:   For  the  exit  access  travel  distance 

limitation  in  temporary  structures 

Note  b.  Buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with  780  CMR 
906.2.1  or  906.2.2. 

Note  c    1  foot  =  304.8  mm 


174 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


1006.5.1  Roof  vent  increase:  In  buildings  which 
are  one  story  in  height,  equipped  with  automatic 
heat  and  smoke  roof  vents  complying  with 
780  CMR  922.0  and  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2. 1,  the  exit  access  travel  distance 
limitation  in  Table  1006.5  for  occupancies  in  Use 
Group  F-l  or  S-l  shall  be  increased  to  400  feet 
(122  m). 

1006.5.2  Use  Group  A-5:  Occupancies  in  Use 
Group  A-5,  where  all  portions  of  the  means  of 
egress  are  essentially  open  to  the  outside,  shall 
have  an  exit  access  travel  distance  of  not  more 
than  400  feet  (122  m),  except  that  such 
occupancies  in  buildings  and  structures  of  Type  1 
or  2  construction  shall  not  have  an  exit  access 
travel  distance  limitation. 

1006.6  Elevators,  escalators  and  moving  walks: 

Elevators,  escalators  and  moving  walks  shall  not  be 
accepted  as  a  required  element  of  the  means  of 
egress. 

Exception:  An  elevator  conforming  to  780  CMR 
1007.3  shall  be  permitted  for  an  accessible  means 
of  egress. 

1006.7  Common  path  of  travel:  The  common  path 
of  exit  access  travel  distance  for  occupants  to  reach 
a  point  where  two  separate  and  distinct  paths  of 
travel  are  available  to  two  exits  shall  not  exceed  100 
feet  (30480  mm)  in  occupancies  in  Use  Group  1-3. 

780  CMR  1007.0  ACCESSIBLE  MEANS 
OF  EGRESS 

1007.1  General:  All  spaces  required  to  be 
accessible  by  521  CMR,  the  Rules  and  Regulations 
of  the  Architectural  Access  Board,  referenced  in 
780  CMR  11,  and  listed  in  Appendix  A  shall  be 
provided  with  not  less  than  one  accessible  means  of 
egress  that  complies  with  780  CMR  1007.0.  Where 
more  than  one  means  of  egress  is  required  from  any 
required  accessible  space,  each  accessible  portion  of 
the  space  shall  be  served  by  not  less  than  two 
accessible  means  of  egress.  Each  accessible  means 
of  egress  shall  provide  a  continuous  path  of  travel 
from  a  required  accessible  space  to  a  public  way 
which  is  usable  by  a  mobility  impaired  person  and 
shall  include  accessible  routes,  ramps,  exit 
stairways,  elevators,  horizontal  exits  or  smoke 
barriers. 

1007.2  Exit  stairways:  An  exit  stairway  to  be 
considered  part  of  an  accessible  means  of  egress 
shall  have  a  clear  width  of  at  least  48  inches  (1219 
mm)  between  handrails  and  shall  either  incorporate 
an  area  of  refuge  within  an  enlarged  story-level 
landing  or  shall  be  accessed  from  an  area  of  refuge 
complying  with  780  CMR  1007.5  or  a  horizontal 
exit. 


Exceptions: 

1.  Stairs  serving  a  single  dwelling  unit  or 
guestroom. 

2.  •  Occupancies  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1. 

3.  The  clear  width  of  48  inches  (1219  mm) 
between  handrails  is  not  required  for  exit 
stairways  accessed  from  a  horizontal  exit. 

1007.3  Elevators:  An  elevator,  to  be  considered 
part  of  an  accessible  means  of  egress,  shall  comply 
with  780  CMR  3006.0  and  standby  power  shall  be 
provided  in  accordance  with  780  CMR  2707.0.  The 
elevator  shall  be  accessed  from  an  area  of  refuge 
complying  with  780  CMR  1007.5  or  a  horizohfaT 
exit.  In  buildings  where  a  required  accessible  floor 
is  four  or  more  stories  above  or  below  a  level  of  exit 
discharge  serving  that  floor,  at  least  one  elevator 
shall  be  provided  and  shall  serve  as  one  required 
accessible  means  of  egress. 

Exceptions: 

1.  In  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1,  the  elevator  shall  not  be 
required  to  serve  floors  which  are  located  at  or 
above  the  level  of  exit  discharge  and  provided 
with  a  horizontal  exit  complying  with  780  CMR 
1019.0. 

2.  Elevators  are  not  required  to  be  accessed  from 
an  area  of  refuge  or  a  horizontal  exit  in 
occupancies  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1. 

1007.4  Platform  lifts:  Platform  (wheelchair)  lifts 
shall  not  serve  as  part  of  an  accessible  means  of 
egress  except  within  a  dwelling  unit. 

1007.5  Areas  of  refuge:  Every  required  area  of 
refuge  shall  be  accessible  from  the  space  it  serves  by 
an  accessible  means  of  egress.  The  maximum  travel 
distance  from  any  accessible  space  to  an  area  of 
refuge  shall  not  exceed  the  travel  distance  permitted 
for  the  occupancy  in  accordance  with  780  CMR 
1006.5.  Every  required  area  of  refuge  shall  have 
direct  access  to  an  exit  stairway  complying  with 
780  CMR  1007.2  or  an  elevator  complying  with 
780  CMR  1007.3.  Where  an  elevator  lobby  is  used 
as  an  area  of  refuge,  the  shaft  and  lobby  shall 
comply  with  780  CMR  1015.0  for  smokeproof 
enclosures  except  where  the  elevators  are  in  an  area 
of  refuge  formed  by  a  horizontal  exit  or  smoke 
barrier. 

Exception:  Areas  of  refuge  are  not  required  in 
open  parking  structures 

1007.5.1  Size:  Each  area  of  refuge  shall  be  sized 
to  accommodate  one  wheelchair  space  of  30 
inches  (762  mm)  by  48  inches  (1219  mm)  for 
each  200  occupants  or  portion  thereof,  based  on 
the  occupant  load  of  the  area  of  refuge  and  all 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


175 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


areas  served  by  the  area  of  refuge.  Such 
wheelchair  spaces  shall  not  reduce  the  required 
means  of  egress  width.  Access  to  any  of  the 
required  wheelchair  spaces  in  an  area  of  refuge 
shall  not  be  obstructed  by  more  than  one 
adjoining  wheelchair  space. 

1007.5.2  Separation:  Each  area  of  refuge  shall 
be  separated  from  the  remainder  of  the  story  by  a 
smoke  barrier  complying  with  780  CMR  712.0. 
Each  area  of  refuge  shall  be  designed  to  prevent 
the  intrusion  of  smoke,  except  those  areas  of 
refuge  located  within  a  stainvay  enclosure  or 
those  areas  of  refuge  where  the  area  of  refuge  and 
all  areas  served  by  the  area  of  refuge  are  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2. 1 . 

1007.5.3  Communication  system:  Every  area  of 
refuge  in  buildings  more  than  four  stories  in 
height  shall  be  provided  with  a  two-way 
emergency  communication  system  between  the 
area  of  refuge  and  a  central  control  point. 

In  each  area  of  refuge  provided  with  a  two- 
way  emergency  communication  system, 
instructions  on  the  use  of  the  area  under 
emergency  conditions  shall  be  posted  adjoining 
the  communication  system.  The  instructions  shall 
include: 

1 .  Directions  to  other  means  of  egress; 

2.  Advice  that  persons  able  to  use  the  exit 
stairs  do  so  as  soon  as  possible  unless  they  are 
assisting  others; 

3.  Information  on  how  to  summon  planned 
availability  of  assistance  in  the  use  of  stairs  or 
supervised  operation  of  elevators;  and 

4.  Directions  for  use  of  the  two-way 
emergency  communication  system. 

1007.5.4  Identification:  Each  door  providing 
access  to  an  area  of  refuge  from  an  adjacent  floor 
area  shall  be  identified  by  a  sign  complying  with 
CABO  Al  1 7. 1  listed  in  Appendix  A  stating  "Area 
of  Refuge"  and  the  International  Symbol  of 
Accessibility.  The  sign  shall  be  illuminated  as 
required  for  "Exit"  signs  where  "Exit"  sign 
illumination  is  required.  Additionally,  tactile 
signage  complying  with  CABO  All 7.1  listed  in 
Appendix  A  shall  be  located  at  each  door  to  an 
area  of  refuge. 

1007.6  Signage:  Signage  indicating  the  location  of 
accessible  means  of  egress  shall  be  installed  at  all 
exits  and  elevators  that  serve  a  required  accessible 
space,  but  which  are  not  an  approved  accessible 
means  of  egress. 

780  CMR  1008.0  OCCUPANT  LOAD 
1008.1    Design   occupant  load:      In  determining 
required   facilities,   the  number  of  occupants  for 
whom   exit   facilities   shall   be   provided    shall   be 
established   by  the   largest   number  computed   in 


accordance    with    780    CMR    1008  1.1    through 
1008.1.3. 

1008.1.1  Actual  number:  The  actual  number  of 
occupants  for  whom  each  occupied  space,  floor  or 
building  is  designed. 

1008.1.2  Number  by  Table   1008.1.2:      The 

number  of  occupants  computed  at  the  rate  of  one 
occupant  per  unit  of  area  as  prescribed  in  Table 
1008.1.2. 

1008.1.3  Number  by  combination:  The  number 
of  occupants  of  any  space  as  computed  in 
780  CMR  1008.1.1  or  1008.1.2  plus  the  number 
of  occupants  similarly  computed  for  all  spaces 
that  discharge  through  the  space  in  order  to  gain 
access  to  an  exit. 

1008.1.4  Increased    occupant    load:        The 

occupant  load  permitted  in  any  building  or  portion 
thereof  is  permitted  to  be  increased  from  that 
number  established  for  the  occupancies  in  Table 
1008.1.2  provided  that  all  other  requirements  of 
780  CMR  are  also  met  based  on  such  modified 
number.  Where  required  by  the  code  official,  an 
approved  aisle,  seating  or  fixed  equipment 
diagram  to  substantiate  any  increase  in  occupant 
load  shall  be  submitted.  Where  required  by  the 
code  official,  such  diagram  shall  be  posted. 

Table  1008.1.2 

MAXIMUM  FLOOR  AREA  ALLOWANCES 

PER  OCCUPANT 


Occupancy 


Floor  area  in 

square  feet  per 

occupant 


Assembly  with  fixed  seats 
Assembly  without  fixed  seats 

Concentrated  (chairs  only  -  not  fixed) 

Standing  space 

Unconcentrated  (tables  and  chairs) 
Bowling  centers,  allow  5  persons  for 

each  lane  including  1 5  feet  of 

runway,  and  for  additional  areas 


See780CMR  1008.1.6 


7  net 
3  net 
15  net 


Business  areas 

1 00  gross 

Courtrooms  -  other  than  fixed  seating 

40  net 

areas 

Educational 

Classroom  area 

20  net 

Shops  and  other  vocational  room 

50  net 

areas 

Industrial  areas 

1 00  gross 

Institutional  areas 

Inpatient  treatment  areas 

240  gross 

Outpatient  areas 

1 00  gross 

Sleeping  areas 

1 20  gross 

Library 

Reading  rooms 

50  net 

Stack  area 

100  gross 

Mercantile,  basement  and  grade  floor 

30  gross 

areas 

Areas  on  other  floors 

60  gross 

Storage  stock,  shipping  areas 

300  gross 

[76 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


Occupancy 


Floor  area   in 

square  feet  per 

occupant 


Parking  garages  200  gross 

Residential  200  gross 

Storage  areas,  mechanical  equipment  300  gross 

room 

Note  a.   1  foot  =  304.8  mm;  1  square  foot  =  0.093  rrr 

1008.1.5  Maximum    occupant    load:        The 

occupant  load  of  any  space  or  portion  thereof 
shall  not  exceed  one  occupant  per  three  square 
feet  (0.28  m2)  of  occupiable  floor  space. 

1008.1.6  Fixed  seats:  The  occupant  load  for  an 
assembly  or  educational  area  having  fixed  seats 
shall  be  determined  by  the  number  of  fixed  seats 
installed.  The  capacity  of  fixed  seats  without 
dividing  arms  shall  equal  one  person  per  18 
inches  (457  mm).  For  booths,  the  capacity  shall 
be  one  person  per  24  inches  (610  mm). 

1008.2  Mezzanine  levels:  The  occupant  load  of  a 
mezzanine  level  discharging  through  a  floor  below 
shall  be  added  to  that  floor's  occupant  load,  and  the 
capacity  of  the  exits  shall  be  designed  for  the  total 
occupant  load  thus  established. 

1008.3  Roofs:  Roof  areas  occupied  as  roof  gardens 
or  for  assembly,  educational,  storage  or  other 
purposes,  shall  be  provided  with  exit  facilities  to 
accommodate  the  required  occupant  load,  but  there 
shall  not  be  less  than  two  approved  means  of  egress 
from  roof  areas  of  Use  Groups  A  and  E. 

780  CMR  1009.0  CAPACITY  OF  EGRESS 
COMPONENTS 

1009.1  General:  The  capacity  of  means  of  egress 
for  a  floor,  balcony,  tier  ot  other  occupied  space 
shall  be  sufficient  for  the  occupant  load  thereof 

1009.2  Minimum  width:  The  width  of  each  means 
of  egress  component  shall  not  be  less  than  the  width 
computed  in  accordance  with  Table  1009.2  for  the 
required  capacity  of  the  component,  but  not  less  than 
the  minimum  width  as  prescribed  by  780  CMR  for 
each  such  component. 

Table  1009.2 
EGRESS  WIDTH  PER  OCCUPANT 


Without  sprinkler 

system  (inches  per 

person) 

With  sprinkler 

system 

(inches  per  person) 

Use  group 

Stairways 

Doors 
ramps  and 
corridors 

Stairways 

Doors 
ramps  and 
corridors 

A,  B,  E,  F,  M, 
R,S 
H 
1-1 
1-2 
1-3 

0.3 
0.7 
0.4 
1.0 
0,3 

0.2 
0.4 
0.2 
0.7 
0.2 

0.2 
0.3 
0.2 
0.3 
0  • 

0.15 

0.2 
0.2 
0.2 

0.2 

Note  a.  Buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with  780  CMR 
906.2.1  or  906.2.2. 

Note  b.   1  inch  =  25.4  mm. 

1009.3  Exit  design  per  floor:  Where  exits  serve 
more  than  one  floor,  only  the  occupant  load  of  each 
floor  considered  individually  shall  be  used  in 
computing  the  required  capacity  of  the  exits  at  that 
floor,  provided  that  the  exit  capacity  shall  not 
decrease  in  the  direction  of  means  of  egress  travel. 

1009.4  Egress  convergence:  Where  means  of 
egress  from  floors  above  and  below  converge  at  an 
intermediate  floor,  the  capacity  of  the  means  of 
egress  from  the  point  of  convergence  shall  not  be 
less  than  the  sum  of  the  two. 

780  CMR  1010.0  NUMBER  OF  EXITS 

1010.1  General:  The  general  requirements  of 
780  CMR  1010.0  apply  to  buildings  of  all  use 
groups.  Where  more  restrictive  requirements  are 
provided  in  780  CMR  such  requirements  shall  take 
precedence  over  the  general  provisions  of  780  CMR 
1010.0. 

1010.2  Minimum  number:  Every  floor  area  shall 
be  provided  with  the  minimum  number  of  approved 
independent  exits  as  required  by  Table  1010.2  based 
on  the  occupant  load,  except  as  modified  in 
780  CMR  1010.3. 

Exception:  In  buildings  with  occupancies  in  Use 
Group  R  having  multistory  dwelling  units,  the 
means  of  egress  from  a  dwelling  unit  to  the 
required  exits  is  permitted  to  be  provided  from 
one  level  only.  Within  the  dwelling  unit  access  to 
the  means  of  egress  from  the  unit  shall  conform  to 
the  applicable  provisions  of  780  CMR  10. 

Table  1010.2 

MINIMUM  NUMBER  OF  EXITS  FOR 

OCCUPANT  LOAD 


Occupant  load 

Minimum  number  of  exits 

500  or  less 

501  -  1,000 
over  1 ,000 

3 
4 

1010.3  Buildings  with  one  exit:   Only  one  exit  shall 

be  required  in: 

1.  Occupancies  in  the  use  groups  shown  in  Table 
1010.3,  provided  that  the  building  has  not  more 
than  one  level  below  the  level  of  exit  discharge. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


177 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1010.3 


Use  Group 

Maximum 
height 
above 
grade 

Max. 
Size 

Max. 

Exit 

travel 
distance 

Minimum  fire- 
resistance 
rating  of  exit 
enclosure 

Mm.  Fire- 
resistance 
rating  of 
opening 
protection 

Bb 
S-2a 

2  stories 

3,500 
sq.ft. 
per 
floor 

75  ft. 

1  hour 

1  hour 

Note  a.  For  the  required  number  of  exits  for  open 
parking  structures,  see  780  CMR  1010.5. 

Note  b.  For  the  required  number  of  exits  for  air  traffic 
control  towers,  see  780  CMR  414.0. 

Note  c.   1  foot  =  304.8  mm. 

1010.4  Emergency  escape:  Every  sleeping  room 
below  the  fourth  story  in  occupancies  in  Use  Groups 
R  and  1-1  shall  have  at  least  one  operable  window  or 
exterior  door  approved  for  emergency  egress  or 
rescue.  The  units  shall  be  operable  from  the  inside 
without  the  use  of  special  knowledge,  separate  tools 
or  force  greater  than  that  which  is  required  for 
normal  operation  of  the  window.  Where  windows 
are  provided  as  a  means  of  egress  or  rescue,  the 
windows  shall  have  the  bottom  of  the  clear  opening 
not  more  than  44  inches  (1118  mm)  above  the  floor. 
All  egress  or  rescue  windows  from  sleeping  rooms 
shall  have  a  minimum  net  clear  opening  of  5.7 
square  feet  (0.53  m2).  The  minimum  net  clear 
opening  height  dimension  shall  be  24  inches  (610 
mm).  The  minimum  net  clear  opening  width 
dimension  shall  be  20  inches  (508  mm). 

Bars,  grilles  or  screens  placed  over  emergency 
escape  windows  shall  be  releasable  or  removable 
from  the  inside  without  the  use  of  a  key,  tool  or 
force  greater  than  that  which  is  required  for  normal 
operation  of  the  window. 

Exceptions 

1.  The  minimum  net  clear  opening  for  grade  floor 
windows  shall  be  five  square  feet  (0.47  m 2). 

2.  An  outside  window  or  an  exterior  door  for 
emergency  escape  is  not  required  in  buildings 
where  the  sleeping  room  is  provided  with  a  door 
to  a  corridor  having  access  to  two  remote  exits  in 
opposite  directions. 

3.  An  outside  window  or  an  exterior  door  for 
emergency  escape  is  not  required  in  buildings 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2. 1  or 
906  2.2 

1010.5  Open  parking  structures:  Parking 
structures  shall  not  have  less  than  two  exits  from 
each  parking  tier,  except  that  only  one  exit  is 
required  where  vehicles  are  mechanically  parked. 
Unenclosed  vehicle  ramps  shall  not  be  considered  as 
required  exits  unless  pedestrian  facilities  are 
provided.  Interior  exit  stairways  are  not  required  to 
be  enclosed. 


780  CMR  1011.0  EXIT  ACCESS 
PASSAGEWAYS  AND  CORRIDORS 

1011.1  Access  passageway:  Direct  exit  access  shall 
be  provided  to  required  exits  through  continuous 
passageways,  aisle  accessways,  aisles  or  corridors 
which  are  conveniently  available  to  all  occupants 
and  maintained  free  of  obstruction.  In  every  area 
containing  seating,  displays,  exhibits,  counters, 
shelving  and  other  furnishings  or  fixtures,  a  path  of 
travel  that  connects  with  each  of  the  means  of  egress 
doorways  serving  the  area  and  which  complies  with 
the  minimum  width  requirements  of  aisles,  shall  be 
provided. 

101 1. 1. 1  Use  Groups  1-2  and  1-3:  Every 
sleeping  room  in  occupancies  in  Use  Group  1-2  or 
1-3  shall  have  an  exit  access  door  leading  directly 
to  an  exit  access  corridor. 

Exception:      Direct  corridor  access  is  not 

required: 

1.  Where  there  is  an  exit  door  opening  directly 
to  the  outside  from  the  room  at  ground  level. 

2.  In  occupancies  in  Use  Group  1-2,  where  one 
adjacent  room,  such  as  a  sitting  room  or 
anteroom,  intervenes  and  all  doors  along  the 
means  of  egress  are  equipped  with  nonlockable 
hardware  in  accordance  with  780  CMR 
409.3.2,  and  the  intervening  room  is  not  used 
as  an  exit  access  for  more  than  eight  patients. 

3.  In  occupancies  in  Use  Group  1-2,  where  a 
patient  sleeping  room  is  subdivided  with 
nonfireresistance  rated,  noncombustible 
partitions,  provided  that  the  arrangement 
allows  for  direct  and  constant  visual 
supervision  by  nursing  personnel  and  the  suite 
complies  with  780  CMR  101 1.1  and  780  CMR 
1017.0.  Such  rooms  which  are  so  subdivided 
shall  not  exceed  5,000  square  feet  (465  mr). 

4  In  occupancies  in  Use  Group  1-3,  where  a 
dayroom  or  group  activity  space  intervenes 
between  an  in  dividual  occupant  sleeping  room 
and  the  access  to  an  exit,  provided  that  the 
sleeping  room  opens  directly  to  the  day  space 
and  is  not  separated  in  elevation  by  more  than 
one  story. 

1011.1.2  Turnstiles  and  gates:  Access  through 
turnstiles,  gates,  rails  or  similar  devices  shall  not 
be  permitted  unless  such  a  device  is  equipped  to 
swing  readily  in  the  direction  of  exit  travel  under 
a  total  force  of  not  more  than  15  pounds  (73.23 
N). 

1011.1.3  Restrictions:  The  required  width  of 
passageways,  aisle  accessways,  aisles  and 
corridors  shall  be  maintained  free  of  projections 
and  restrictions;  except  that  the  minimum  clear 
width  resulting  from  doors  opening  into  such 
spaces  shall  be  one-half  of  the  required  width. 
When  fully  open,  the  door  shall  not  project  more 
than  seven  inches  (178  mm)  into  the  required 


178 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


width.  Handrail  projections  are  permitted  in 
accordance  with  780  CMR  1022.2.1. 

1011.2  Dead  ends:  exit  access  passageways  and 
corridors  in  all  stories  which  serve  more  than  one 
exit  shall  provide  direct  connection  to  such  exits  in 
opposite  directions  from  any  point  in  the 
passageway  or  corridor  insofar  as  practicable.  The 
length  of  a  dead-end  passageway  or  corridor  shall 
not  be  more  than  20  feet  (6096  mm). 

Exceptions: 

1 .  In  occupancies  in  Use  Group  1-3  of  Occupancy 
Conditions  H,  HI  or  IV  (see  780  CMR  308.4),  the 
dead  end  in  a  corridor,  hallway  or  aisle  shall  not 
exceed  50  feet  (15240  mm). 

2.  In  occupancies  in  Use  Group  B  where 
passageways  are  bounded  by  furniture,  counters, 
partitions  or  similar  dividers  not  more  than  six 
feet  (1829  mm)  in  height,  the  length  of  a  dead-end 
passageway  shall  not  be  more  than  50  feet  (15240 
mm). 

3 .  Passageways  or  corridors  within  spaces  with 
one  means  of  egress. 

4.  A  dead-end  passageway  or  corridor  shall  not 
be  limited  in  length  where  the  length  of  the  dead- 
end passageway  or  corridor  is  less  than  2.5  times 
the  least  width  of  the  dead-end  passageway  or 
corridor. 

1011.2.1     Common     path     of    travel:         In 

occupancies  in  Use  Group  B,  the  length  of  a 
common  path  of  travel  shall  not  exceed  75  feet 
(22860  mm). 
Exceptions 

1 .  The  length  of  a  common  path  of  travel  in  an 
occupancy  in  Use  Group  B  shall  not  be  more 
than  100  feet  (30480  mm),  provided  that  the 
building  is  equipped  throughout  with  an 
automatic  sprinkler  '  system  installed  in 
accordance  with  780  CMR  906.2.1. 

2.  Where  a  tenant  space  in  an  occupancy  in 
Use  Group  B  has  an  occupant  load  of  not  more 
than  30,  the  length  of  a  common  path  of  travel 
shall  not  be  more  than  100  feet  (30480  mm). 

1011.3  Width:  The  minimum  required  width  of 
passageways,  aisle  accessways,  aisles  and  corridors 
shall  be  determined  by  the  most  restrictive  of  the 
following  criteria: 

1  44  inches  (1118  mm)  where  serving  an 
occupant  load  of  greater  than  50. 

2.  36  inches  (914  mm)  where  serving  an  occupant 
load  of  50  or  less. 

3.  96  inches  (2438  mm)  in  an  occupancy  in  Use 
Group  1-2  used  for  the  movement  of  beds. 

4.  72  inches  (1829  mm)  in  an  occupancy  in  Use 
Group  E  with  more  than  1 00  occupants. 

5.  The  width  required  for  capacity  as  determined 
by  780  CMR  1009.0. 

Aisles  and  aisle  accessways  shall  conform  to  the 
requirements  of  780  CMR  1011.0  or  780  CMR 
1012.0. 


1011.3.1  Capacity:  The  required  capacity  of  a 
corridor  shall  be  determined  by  dividing  the 
occupant  load  that  utilizes  the  corridor  for  exit 
access  by  the  number  of  exits  to  which  the 
corridor  connects,  but  not  less  than  the  capacity 
of  the  exit  element  to  which  the  corridor  leads 

1011.4  Enclosure:  All  corridors  shall  be 
fireresistance  rated  in  accordance  with  Table  10114 
based  on  the  use  group  of  the  space  and  the  total 
required  capacity  of  all  of  the  exits  from  the 
corridor  The  corridor  walls  shall  comply  with 
780  CMR  71 1.0. 
Exceptions: 

1  A  fireresistance  rating  is  not  required  for 
corridors  in  an  occupancy  in  Use  Group  E  where 
each  room  that  is  occupied  for  instruction  or 
assembly  purposes  has  at  least  one-half  of  the 
required  means  of  egress  doors  opening  directly 
to  the  exterior  of  the  building  at  ground  level. 
2.  A  fireresistance  rating  is  not  required  for 
corridors  contained  within  a  dwelling  unit  or  a 
guestroom  in  an  occupancy  in  Use  Group  R. 

Table  1011.4 
CORRIDOR  FIRERESISTANCE  RATING 


Total  required 

capacity  of  all 

exits  from 

corridor 

Required  fireresistance  rating 
(flours) 

Use  Group 

Without 
sprinkler 
system 

With  sprinkler 
system 

H-i.H-2.H-3 
H-4 

A.B,E,F,M, 

S 

I-l,Ra 

1-2 
1-3 

All 
>30 
>30 

>  1:0 
All 
All 

1 
1 
1 

1 

1 
Not  permitted 

1 
1 
0 

/= 

ob 

oc 

Note  a  For  a  reduction  in  the  fireresistance  rating  for 
occupancies  in  Use  Group  R_  see  780  CMR  1011.4, 
Exception  2. 

Note  b.  For  requirements  for  occupancies  in  Use 
Group  1-2,  see  780  CMR  409.3. 

Note  c.  For  a  reduction  in  the  fireresistance  rating  for 
occupancies  in  Use  Group  1-3,  see  780  CMR410.7. 

Note  d.  buildings  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with  780  CMR 
906.2.1  or  906.2.2. 

1011.4.1  Corridor  walls  as  separation  walls: 

Tenant  and  dwelling  unit  separation  walls  which 
are  also  corridor  walls  shall  comply  with 
780  CMR  1011.0  and  the  requirements  of  Table 
602. 

Exception:  Tenant  separation  and  dwelling 
unit  separation  walls  which  are  also  corridor 
walls  shall  not  be  required  to  have  a 
fireresistance  rating  greater  than  that  required 
by  Table  1011.4  where  the  building  is 
equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1  or  906.2.2. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


179 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUTLDrNG  CODE 


1011.4.2  Opening  protectives:  All  door 
assemblies  from  rooms  opening  onto  a  corridor 
that  is  required  to  be  of  fireresistance  rated 
construction  shall  be  fire  doors  complying  with 
780  CMR  716.0. 

1011.5  Exterior  balconies:  Exterior  exit  access 
balconies  shall  conform  to  the  requirements  of 
780  CMR  1011.0  for  corridors  and  shall  be 
protected  to  prevent  the  accumulation  of  snow  and 
ice  in  climates  subject  to  those  elements 

1011.5.1  Wall  separation:  Exterior  exit  access 
balconies  shall  be  separated  from  the  interior  of 
the  building  by  walls  and  opening  protectives  as 
required  by  780  CMR  1011.4.  A  fireresistance 
rating  for  the  wall  is  not  required  where  the 
balcony  is  provided  with  not  less  than  two 
approved  stairways  or  other  approved  means  of 
egress  elements  and  a  dead  end  does  not  require 
travel  past  an  unprotected  opening  for  access  to 
the  stairway  or  means  of  egress  element 

780  CMR  1012.0  ASSEMBLY  AISLES 
AND  AISLE  ACCESSWAYS 

1012.1  Where  required:  In  occupancies  in  Use 
Group  A  which  contain  seats,  tables,  displays, 
equipment  or  other  material  shall  be  provided  with 
aisle  accessways  and  aisles  in  accordance  with 
780  CMR1012.0.  These  provisions  shall  also  apply 
to  tiered  or  stepped  seating  facilities  except  as 
modified  by  780  CMR  1013.0. 

1012.2  Aisle  and  aisle  accessway  width:  The  width 
of  aisle  accessways  and  aisles  shall  provide 
sufficient  means  of  egress  capacity  for  the  number  of 
persons  accommodated  by  the  catchment  area  served 
by  the  aisle  accessway  or  aisle  (see  780  CMR 
1012.2.5).  The  catchment  area  served  by  an  aisle 
accessway  or  aisle  is  the  portion  of  the  total  space 
which  is  naturally  served  by  that  section  of  the  aisle 
accessway  or  aisle.  In  establishing  catchment  areas 
the  assumption  shall  be  made  that  there  is  a  balanced 
use  of  all  means  of  egress,  with  the  number  of 
persons  in  proportion  to  means  of  egress  capacity. 

1012.2.1  Measurement  of  required  minimum 
width  of  aisles  and  aisle  accessways:  Where 
seating  is  located  at  a  table  or  counter  and  is 
adjacent  to  an  aisle  or  aisle  accessway,  the 
measurement  of  required  clear  width  of  the  aisle 
or  aisle  accessway  shall  be  made  to  a  line  19 
inches  (483  mm)  away  from  the  edge  of  the  table 
or  counter.  The  19-inch  (483  mm)  distance  shall 
be  measured  perpendicular  to  the  side  of  the  table 
or  counter.  In  the  case  of  other  side  boundaries 
for  aisles  or  aisle  accessways  the  clear  width  shall 
be  measured  to  walls,  edges  of  seating  and  tread 
edges,  except  that  handrail  projections  are 
permitted. 


1012.2.2  Converging  aisles  and  aisle 
accessways:  Where  aisle  accessways  or  aisles 
converge  to  form  a  single  path  of  means  of  egress 
travel,  the  required  means  of  egress  capacity  of 
such  path  shall  not  be  less  than  the  combined 
required  capacity  of  the  converging  aisle 
accessways  or  aisles 

1012.2.3  Uniform  width  of  aisles:  Those 
portions  of  aisles  where  means  of  egress  is 
possible  in  either  of  two  directions  shall  be 
uniform  in  required  width 

1012.2.4  Uniform  width  of  aisle  accessways: 

Those  portions  of  aisle  accessways  having  a 
required  width  exceeding  12  inches  (305  mm), 
where  means  of  egress  is  possible  in  more  than 
one  direction,  shall  be  uniform  in  required  width. 

1012.2.5  Capacity  of  aisles  and  aisle 
accessways:  The  width  of  aisles  and  aisle 
accessways  shall  provide  sufficient  capacity  in 
accordance  with  the  following  criteria  where  clear 
width  is  measured  in  accordance  with  780  CMR 
1012.2.1. 

1  At  least  0.3  inch  (7.5  mm)  of  width  for  each 
person  served  shall  be  provided  on  stairs 
having  riser  heights  of  seven  inches  (178  mm) 
or  less  and  tread  depths  of  1 1  inches  (279  mm) 
or  greater,  measured  horizontally  between 
tread  nosings. 

2.  At  least  0.005  inch  (0.1  mm)  of  additional 
stair  width  for  each  person  shall  be  provided 
for  each  0.10  inch  (2.5  mm)  of  riser  height 
above  seven  inches  (178  mm). 

3  Where  a  means  of  egress  requires  stair 
descent,  at  least  0.075  inch  (2  mm)  of 
additional  width  for  each  person  shall  be 
provided  on  those  portions  of  stair  width  not 
having  handrails  within  a  horizontal  distance  of 
30  inches  (762  mm). 

4  Level  or  ramped  means  of  egress  with 
slopes  less  than  one  unit  vertical  in  eight  units 
horizontal  (1:8),  shall  have  at  least  0.2  inch  (5 
mm)  of  clear  width  for  each  person  served. 

1012.2.6  Minimum    width    of   aisles:       The 

minimum  clear  width  of  aisles  shall  be:  48  inches 
(1219  mm)  for  stairs  having  seating  on  each  side; 
36  inches  (914  mm)  for  stairs  having  seating  on 
only  one  side;  23  inches  (584  mm)  between  a  stair 
handrail  or  guardrail  and  seating  where  the  aisle 
is  subdivided  by  a  handrail  (see  780  CMR 
1012.5);  42  inches  (1067  mm)  for  level  or  ramped 
aisles  having  theater-style  seating  on  both  sides; 
36  inches  (914  mm)  for  all  other  level  or  ramped 
aisles;  and  23  inches  (584  mm)  between  a  stair 
handrail  and  seating  where  an  aisle  does  not  serve 
more  than  five  rows  on  one  side. 

1012.2.7  Minimum  width  of  aisle  accessways: 

Aisle  accessways  shall  conform  to  the 
requirements  of  780  CMR  1012.6  in  the  case  of 
theater-type  seating  and  to  the  requirements  of 


180 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


780  CMR  1012.7  in  the  case  of  all  seating  at 
tables  or  counters. 

1012.3  Termination:  Each  end  of  a  cross  aisle  shall 
terminate  at  an  aisle,  foyer,  doorway  or  vomitory 
giving  access  to  an  exit  Dead-end  aisles  which 
terminate  only  at  one  end  with  a  cross  aisle,  foyer, 
doorway  or  vomitory  giving  access  to  an  exit  shall 
not  be  greater  than  20  feet  (6096  mm)  in  length. 

Exception:  A  longer  dead-end  aisle  is  permitted 
where  seats  served  by  the  dead-end  aisle  are  not 
more  than  24  seats  from  another  aisle,  measured 
along  a  row  of  seats  having  a  minimum  clear 
width  of  12  inches  (305  mm)  plus  0.6  inch  (15 
mm)  for  each  additional  seat  above  seven  in  the 
row. 

1012.4  Walking  surfaces:  Aisles  with  a  gradient  of 
one  unit  vertical  in  eight  units  horizontal  (1:8)  or 
less  shall  consist  of  a  ramp  having  a  slip-resistant 
walking  surface.  Aisles  with  a  gradient  exceeding 
one  unit  vertical  in  eight  units  horizontal  (1:8)  shall 
consist  of  a  series  of  risers  and  treads  which  extend 
across  the  full  width  of  aisles  and  comply  with 
780CMRs  1012.4.1  and  1012.4.2. 

1012.4.1  Treads:  Tread  depths  shall  be  a 
minimum  of  1 1  inches  (279  mm)  and  be  uniform 
within  each  aisle. 

Exception:  Nonuniformities  shall  not  exceed 
3/16  inch  (5  mm)  between  adjacent  treads. 

1012.4.2  Risers:  Where  the  gradient  of  aisle 
stairs  is  to  be  the  same  as  the  gradient  of  adjoining 
seating  areas,  the  riser  height  shall  not  be  less 
than  4  inches  (102  mm)  nor  more  than  eight 
inches  (203  mm)  and  shall  be  uniform  within  each 
flight. 

Exception:  Riser  height  nonuniformity  shall 
be  limited  to  the  extent  necessitated  by  changes 
in  the  gradient  of  the  adjoining  seating  area  to 
maintain      adequate      sightlines  Where 

nonuniformities  exceed  3/16  inch  (5  mm) 
between  adjacent  risers,  the  exact  location  of 
such  nonuniformities  shall  be  indicated  with  a 
distinctive  marking  stripe  on  each  tread  at  the 
nosing  or  leading  edge  adjacent  to  the  non- 
uniform risers.  Such  stripe  shall  be  a  minimum 
of  one  inch  (25  mm)  wide  and  a  maximum  of 
two  inches  (5 1  mm)  wide. 

1012.5  Handrails:  Ramped  aisles  having  a  gradient 
exceeding  one  unit  vertical  in  15  units  horizontal 
(1:15)  and  aisle  stairs  shall  be  provided  with 
handrails  located  either  at  the  side  or  within  the  aisle 
width. 

Exceptions: 

1.  Handrails  are  not  required  if,  at  the  side  of  the 
aisle,  there  is  a  guardrail  that  complies  with  the 
requirements  for  handrails. 

2.  Handrails  are  not  required  for  aisles  with 
seating  on  both  sides  unless  there  is  more  than 


one  riser  per  row  of  seating.  The  single  riser  shall 
be  indicated  by  a  distinctive  marking  stripe  on  the 
leading  edge  of  the  tread. 

1012.5.1  Discontinuous  rails:  Where  there  is 
seating  on  both  sides  of  the  aisle,  the  handrails 
shall  be  discontinuous  with  gaps  or  breaks  at 
intervals  not  exceeding  five  rows  to  facilitate 
access  to  seating  and  to  permit  crossing  from  one 
side  of  the  aisle  to  the  other.  These  gaps  or  breaks 
shall  have  a  clear  width  of  at  least  22  inches  (559 
mm)  and  not  greater  than  36  inches  (914  mm), 
measured  horizontally,  and  the  handrail  shall  have 
rounded  terminations  or  bends. 

1012.5.2  Intermediate  rails:  Where  handrails 
are  provided  in  the  middle  of  aisle  stairs,  there 
shall  be  an  additional  intermediate  handrail 
located  approximately  12  inches  (305  mm)  below 
the  main  handrail. 

1012.6  Row  width:  The  minimum  clear  row  width 
shall  not  be  less  than  12  inches  (305  mm)  measured 
as  the  clear  horizontal  distance  from  the  back  of  the 
row  ahead  and  the  nearest  projection  of  the  row 
behind.  Where  chairs  have  automatic  or  self-rising 
seats,  the  measurement  shall  be  made  with  the  seats 
in  the  raised  position.  Where  any  chair  in  the  row 
does  not  have  an  automatic  or  self-rising  seat,  the 
measurement  shall  be  made  with  the  seat  in  the 
down  position.  Where  tablet-arm  chair  seating  is 
used,  the  measurement  shall  be  made  with  the  tablet- 
arm  in  the  usable  position. 

1012.6.1  Dual  access:  For  rows  of  seating  served 
by  aisles  or  doorways  at  both  ends,  there  shall  not 
be  more  than  100  seats  per  row.  The  minimum 
clear  width  of  12  inches  (305  mm)  between  rows 
shall  be  increased  by  0.3  inch  (7.5  mm)  for  every 
additional  seat  beyond  14  seats,  but  the  minimum 
clear  width  is  not  required  to  exceed  22  inches 
(559  mm). 

1012.6.2  Single  access:  For  rows  of  seating 
served  by  an  aisle  or  doorway  at  only  one  end  of 
the  row,  the  minimum  clear  width  of  12  inches 
(305  mm)  between  rows  shall  be  increased  by  0.6 
inch  (15  mm)  for  every  additional  seat  beyond 
seven  seats,  but  the  minimum  clear  width  is  not 
required  to  exceed  22  inches  (559  mm). 
However,  the  path  of  travel  shall  not  exceed  30 
feet  (9144  mm)  from  any  seat  to  a  point  where  a 
person  has  a  choice  of  two  paths  of  travel  to  two 
exits. 

1012.7  Aisle  accessways  for  tables  and  seating: 

Aisle  accessways  serving  arrangements  of  seating  at 
tables  or  counters,  shall  have  sufficient  clear  width 
to  conform  to  the  capacity  requirements  of  780  CMR 
1012.2.5,  but  shall  not  have  less  than  the  appropriate 
minimum  clear  width  specified  in  780  CMR 
1012.7.1. 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1012.7.1  Width:  In  addition  to  the  width  required 
by  780  CMR  1012.2,  aisle  accessways  shall 
provide  a  minimum  of  12  inches  (305  mm)  plus 
0.5  inch  (13  mm)  of  width  for  each  additional  1 
foot  (305  mm),  or  fraction  thereof,  beyond  12  feet 
(3660  mm)  of  aisle  accessway  length  measured 
from  the  center  of  the  seat  farthest  from  an  aisle. 

Exception:  Portions  of  an  aisle  accessway 
having  a  length  not  exceeding  six  feet  (1830 
mm)  and  used  by  a  total  of  not  more  than  four 
persons. 

1012.7.2  Length:  The  length  of  travel  along  the 
aisle  accessway  shall  not  exceed  36  feet  (10973 
mm)  from  any  seat  to  the  closest  aisle.  The  path 
of  travel  shall  not  exceed  30  feet  (9144  mm)  from 
any  seat  to  the  point  where  a  person  has  a  choice 
of  two  or  more  paths  of  travel  to  separate  exits. 

1012.8  Railings:  Railings  shall  be  provided  on 
balconies  and  galleries  in  accordance  with  780  CMR 
1021.4. 

780  CMR  1013.0  GRANDSTANDS 

1013.1  Scope:  780  CMR  1013.0  shall  apply  to  all 
structures  with  an  occupancy  in  Use  Group  A  which 
provide  permanent,  temporary  or  portable  tiered  or 
stepped  seating  facilities,  such  as  grandstands, 
bleachers,  folding  and  telescopic  seating.  Except  as 
modified  by  780  CMR  1013.0,  780  CMR  1012.0 
shall  apply  to  all  such  structures. 

1013.2  Smoke-protected  assembly  seating: 
Assembly  seating  which  is  served  by  a  means  of 
egress  that  is  not  subject  to  blocking  by  smoke 
accumulation  within  or  under  a  structure  shall  be 
considered  smoke  protected  and  shall  comply  with 
the  requirements  of  780  CMR  1013.2.1  through 
1013.2.3. 

1013.2.1  Roof  height:  A  smoke-protected 
assembly  seating  area  with  a  roof  shall  have  the 
lowest  portion  of  the  roof  not  less  than  1 5  feet 
(4572  mm)  above  the  highest  aisle  or  aisle 
accessway. 

1013.2.2  Automatic  sprinklers:  All  areas 
enclosed  with  walls  and  ceilings  in  structures 
containing  smoke-protected  assembly  seating 
shall  be  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.0. 

Exception:  An  automatic  sprinkler  system  is 
not  required  for  either  of  the  following: 

1.  The  floor  area  used  for  a  contest, 
performance  or  entertainment  provided  that  the 
roof  construction  is  more  than  50  feet  (15240 
mm)  above  the  floor  level  and  the  use  of  the 
floor  is  restricted  to  low  fire-hazard 
occupancies. 

2.  Press  boxes  and  storage  facilities  less  than 
1,000  square  feet  (9.3  m2)  in  area  in 
conjunction    with    outdoor   seating   facilities 


where  all  means  of  egress  in  the  seating  area 
are  essentially  open  to  the  outside. 

1013.2.3  Smoke  control:  All  means  of  egress 
serving  a  smoke-protected  assembly  seating  area 
shall  be  provided  with  a  smoke  control  system 
complying  with  780  CMR  921.0  or  natural 
ventilation  designed  to  maintain  the  smoke  level 
at  least  six  feet  (1829  mm)  above  the  floor  of  the 
means  of  egress. 

1013.3  Travel  distance:  The  exit  access  travel 
distance  shall  comply  with  780  CMR  1006.5  except 
that  in  a  smoke-protected  assembly  seating  area,  the 
travel  distance  from  each  seat  to  the  nearest  entrance 
to  an  egress  vomitory  portal  or  egress  concourse 
shall  not  exceed  200  feet  (60960  mm).  The  travel 
distance  from  the  entrance  to  a  vomitory  portal  or 
egress  concourse  to  an  approved  egress  stair,  ramp 
or  walk  at  the  building  exterior  shall  not  exceed  200 
feet  (60960  mm).  Where  aisles  are  required,  the 
distance  shall  be  measured  along  the  aisles  and  aisle 
accessways  without  travel  over  or  on  the  seats. 

1013.4  Minimum  egress  widths:  The  minimum 
clear  width  of  stairways,  passageways,  doorways, 
ramps  and  other  means  of  egress  shall  provide 
sufficient  capacity  in  accordance  with  the  provisions 
of  780  CMR  10,  except  as  modified  by  Table 
1013.4. 

Table  1013.4 

MINIMUM  EGRESS  WIDTHS 

SMOKE-PROTECTED  ASSEMBLY 

SEATING 


Inches 

of  clear  w 

dth  per  seat  served 

Aisles, 

Number  of 
seats  in  the 

Stairs 
with 

Stairs 
without 

accessways, 
doorways 

Ramps 

space 

handrails 

handrails 

and  ramps 

steeper 

within  30 

within  30 

not  steeper 

1 0  slope 

inches 

inches 

than  1  in  10 

slope 

2,000  or  less 

0.300 

0.375 

0.200 

0.220 

5,000 

0.200 

0.250 

0.150 

0.165 

10,000 

0.130 

0.163 

0.100 

0.110 

15,000 

0.096 

0.120 

0.070 

0.077 

20,000 

0.076 

0.095 

0.056 

0.066 

25J300  or  more 

0.060 

0.075 

0.044 

0.048 

Note  a.  If  risers  exceed  7  inches  in  height,  the 
minimum  clear  width  of  stairs  determined  from  the  table 
shall  be  multiplied  by  factor  A  where  A  =  1  +  [(Riser 
Height  -7.0)  -5]. 

Note  b.   1  inch  =  25.4  mm. 

1013.5  Aisles:  Aisles  shall  be  provided  in  all 
seating  facilities  except  that  an  aisle  is  not  required 
where  all  of  the  following  conditions  exist. 

1 .  Seats  are  without  backrests. 

2.  The  rise  from  row  to  row  does  not  exceed  six 
inches  (152  mm)  per  row. 


182 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUTLDLNG  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


3  The  row  spacing  does  not  exceed  28  inches 
(711  mm)  unless  the  seatboards  and  footboards 
are  at  the  same  elevation. 

4  The  number  of  rows  does  not  exceed  16  in 
height. 

5.  The  first  seatboard  is  not  more  than  12  inches 
(305  mm)  above  the  ground,  floor  surface  or  cross 
aisle  below. 

6.  Seatboards  have  a  continuous  flat  surface. 

7.  Seatboards  provide  a  walking  surface  with  a 
minimum  width  of  1 1  inches  (279  mm). 

8  Egress  from  seating  is  not  restricted  by  rails, 
guards  or  other  obstructions. 

1013.5.1  Termination:  Where  seats  are  without 
backrests,  dead  ends  in  vertical  aisles  shall  not 
exceed  a  distance  of  16  rows.  For  smoke- 
protected  assembly  seating,  the  dead  ends  in 
vertical  aisles  shall  not  exceed  a  distance  of  21 
rows.  For  smoke-protected  assembly  seating,  a 
longer  dead-end  aisle  is  permitted  where  seats 
served  by  the  dead-end  aisle  are  not  more  than  40 
seats  from  another  aisle,  measured  along  a  row  of 
seats  having  an  aisle  accessway  with  a  minimum 
clear  width  of  12  inches  (305  mm)  plus  0.3  inch 
(8  mm)  for  each  additional  seat  above  seven  in  the 
row. 

1013.5.2  Row  width:  For  smoke  protected 
assembly  seating,  the  maximum  number  of  seats 
in  a  row  that  has  a  minimum  clear  aisle  accessway 
width  of  12  inches  (305  mm)  shall  be  as  specified 
in  Table  1013.5.2. 

Where  the  number  of  seats  per  row  exceeds 
that  specified  in  Table  1013.5.2,  the  minimum 
clear  aisle  accessway  width  for  rows  served  by 
aisles  or  doorways  at  both  ends  shall  be  12  inches 
(305  mm)  plus  0.3  inch  (7.5  mm)  for  every 
additional  seat  beyond  that  specified  in  Table 
1013.5.2  and  there  shall  be  not  more  than  100 
seats  per  row;  and  for  rows  served  by  an  aisle  or 
doorway  at  only  one  end  of  the  row,  the  minimum 
clear  aisle  accessway  width  shall  be  12  inches 
(305  mm)  plus  0.6  inch  (15  mm)  for  every 
additional  seat  beyond  that  specified  in  Table 
1013.5.2. 

Table  1013.5.2 

ROW  LENGTH  WITH  12-INCH  AISLE 

ACCESSWAY  SMOKE-PROTECTED 

ASSEMBLY  SEATING 


Total  number  of 
seats  in  the 

No.  Of  seats  per  row  permitted  to  have  a 

minimum  1 2-inch  clear  width  aisle 

accesswav 

space 

Ajsle  or  doorway  at 
both  ends  of  row 

Aisle  or  doorway  at 
one  end  of  row 

Less  than  4,000 

4,000 

7,000 

10,000 

13.000 

16.000 

19,000 
::.000ormore 

14 
15 
16 
17 
18 
19 
20 
21 

7 
7 
8 
8 
9 
9 
10 
11 

Note  a.   1  inch  =  25.4  mm. 

1013.5.3  Single  access  row  For  rows  of  seating 
served  by  an  aisle  or  doorway  at  only  one  end  of 
the  row  in  smoke-protected  assembly  seating,  the 
common  path  of  [ravel  from  any  seat  to  a  point 
where  a  person  has  a  choice  of  two  directions  of 
egress  travel  shall  not  exceed  50  feet  ( 1 5240  mm). 

1013.6  Bleacher  footboards:  Bleacher  footboards 
shall  be  provided  for  all  rows  of  seats  above  the 
third  row  or  beginning  at  such  a  point  where  the 
seatboard  is  more  than  two  feet  (610  mm)  above  the 
ground,  floor  surface  or  cross  aisle  below.  A 
separate  footboard  is  not  required  where  the  same 
platform  is  used  for  both  seating  and  the  footboard, 
provided  that  each  level  or  platform  is  not  less  than 
24  inches  (610  mm)  wide.  On  a  horizontally 
projected  plane,  horizontal  gaps  between  footboards 
and  seatboards  shall  not  exceed  '/«  inch  (6  mm). 
Openings  between  footboards  and  seatboards  which 
are  located  more  than  30  inches  (762  mm)  above  the 
floor  or  grade  below  shall  be  provided  with 
intermediate  construction  such  that  a  sphere  with  a 
diameter  of  four  inches  (102  mm)  cannot  pass 
through  the  opening. 

1013.7  Spaces  underneath  seats:  Spaces 
underneath  grandstand  seats  shall  be  kept  free  of  all 
combustible  and  flammable  materials  and  shall  not 
be  occupied  or  used  for  other  than  exits;  except  that 
where  enclosed  in  not  less  than  one-hour 
fireresistance  rated  construction,  the  code  official 
shall  approve  the  use  of  such  spaces  for  other 
purposes,  provided  that  the  safety  of  the  public  is  not 
endangered. 

780  CMR  1014.0  STAIRWAYS 

1014.1  General:  All  stairways  shall  comply  with 
the  provisions  of  780  CMR  1014.0.  780  CMR 
1014.11  shall  be  applicable  only  to  interior 
stairways.  780  CMR  1014.12  shall  be  applicable 
only  to  exterior  stairways. 

1014.1.1  Walking  surface:  The  maximum  slope 
of  the  walking  surface  of  treads  and  landings  shall 
be  one  unit  vertical  in  48  units  horizontal  (1:48). 

1014.2  Egress  capacity:  The  egress  capacity  of 
stairways  and  doors  shall  be  computed  in 
accordance  with  780  CMR  1009.0. 

1014.3  Width:  All  means  of  egress  stairways  shall 
not  be  less  than  44  inches  (1118  mm)  in  width. 

Exceptions: 

1.      Stairways  serving  buildings  of  single-exit 

construction  where  permitted  by  780  CMR  1010.3 

shall  not  be  less  than  36  inches  (914  mm)  in 

width. 

2    Spiral  stairways  as  provided  for  in  780  CMR 

1014.6.4. 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


183 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3.  Stairways  serving  an  occupancy  in  Use  Group 
R-3  shall  not  be  less  than  36  inches  (914  mm)  in 
width. 

4.  Stairways  serving  and  contained  within  a 
single  residential  dwelling  unit  shall  not  be  less 
than  36  inches  (914  mm)  in  width. 

5.  Stairways  serving  buildings  having  a  total 
occupant  load  of  50  or  less  shall  not  be  less  than 
36  inches  (914  mm)  in  width. 

6.  Where  a  stairway  lift  is  installed  on  stairways 
serving  occupancies  in  Use  Group  R-3  or  within 
dwelling  units  in  occupancies  in  Use  Group  R-2, 
a  clear  passage  width  not  less  than  20  inches  (508 
mm)  shall  be  provided. 

1014.3.1  Restrictions:  Means  of  egress  stairways 
shall  not  reduce  in  width  in  the  direction  of  egress 
travel.  Projections  into  a  required  stairway  width 
are  prohibited,  except  at  and  below  handrail 
height  where,  at  each  handrail,  the  projections 
shall  not  exceed  3  Vi  inches  (89  mm)  into  the 
required  width. 

1014.3.2  Landing  width:  The  least  dimension  of 
landings  and  platforms  in  means  of  egress 
stairways  shall  not  be  less  than  the  required  width 
of  the  stairway,  except  that  the  landing  dimension 
in  the  direction  of  egress  travel  is  not  required  to 
exceed  four  feet  (1219  mm)  where  the  travel  from 
one  stair  flight  to  the  next  stair  flight  is  a  straight 
run. 

1014.4  Headroom:  The  minimum  headroom  in  all 
parts  of  a  stairway  shall  not  be  less  than  80  inches 
(2032  mm)  measured  vertically  from  the  tread 
nosing  or  from  the  floor  surface  of  the  landing  or 
platform. 

1014.5  Vertical  rise:  A  means  of  egress  stairway 
shall  not  have  a  height  of  vertical  rise  of  more  than 
12  feet  (3658  mm)  between  landings  and 
intermediate  platforms. 

1014.6  Treads  and  risers:  Maximum  riser  height 
shall  be  seven  inches  (178  mm)  and  minimum  riser 
height  shall  be  four  inches  (102  mm).  Minimum 
tread  depth  shall  be  1 1  inches  (279  mm),  measured 
horizontally  between  the  vertical  planes  of  the 
foremost  projection  of  adjacent  treads  and  at  a  right 
angle  to  the  tread's  leading  edge. 

Exceptions: 

1.  Winders  in  accordance  with  780  CMR 
1014.6.3. 

2.  Spiral  stairways  in  accordance  with  780  CMR 
1014.6.4. 

3.  Circular  stairways  in  accordance  with 
780  CMR  1014.6.5. 

4.  Alternating  tread  stairways  in  accordance  with 
780  CMR  1014.6.6. 

5.  Stairways  serving  as  aisles  in  assembly  seating 
areas  where  the  stairway  pitch  or  slope  is  set,  for 


sightline  reasons,  by  the  slope  of  the  adjacent 
seating  area. 

6.  Any  stairway  replacing  an  existing  stairway 
within  a  space  where,  because  of  existing 
construction,  the  pitch  or  slope  cannot  be  reduced. 

7.  Existing  stairways. 

8.  In  occupancies  in  Use  Group  R-3  and  within 
dwelling  units  in  occupancies  in  Use  Group  R-2, 
the  maximum  riser  height  shall  be  S'A  inches  (210 
mm)  and  the  minimum  tread  depth  shall  be  nine 
inches  (229  mm).  A  one-inch  (25  mm)  nosing 
shall  be  provided  on  stairways  with  solid  risers. 

9.  Stairways  in  penal  facilities  serving  guard 
towers,  observation  stations  and  control  rooms  not 
more  than  250  square  feet  (23  m2 )  in  area  shall  be 
permitted  to  have  risers  not  exceeding  eight 
inches  (203  mm)  in  height  and  treads  not  less  than 
nine  inches  (229  mm)  in  depth. 

1014.6.1  Profile:  The  radius  of  curvature  at  the 
leading  edge  of  the  tread  shall  not  be  greater  than 
Vi  inch  (13  mm).  Bevelling  of  nosings  shall  not 
exceed  'A  inch  (13  mm).  Risers  shall  be  solid  and 
vertical  or  sloped  from  the  underside  of  the 
leading  edge  of  the  tread  above  at  an  angle  not 
more  than  30°  (0.52  rad)  from  the  vertical.  The 
leading  edge  of  tread  shall  not  project  more  than 
V/i  inches  (38  mm)  beyond  the  tread  below. 

Exception:  Solid  risers  are  not  required  for 
stairways  serving  dwelling  units  which  are  not 
required  to  be  accessible  or  adaptable  in 
accordance  with  521  CMR,  the  Rules  and 
Regulations  of  the  Architectural  Access 
Board,  referenced  in  780  CMR  11,  and  listed 
in  Appendix  A,  provided  that  the  opening 
between  treads  does  not  permit  the  passage  of 
a  sphere  with  a  diameter  of  four  inches  (102 
mm). 

1014.6.2  Dimensional  uniformity:  There  shall 
not  be  variation  exceeding  3/16  inch  (5  mm)  in  the 
depth  of  adjacent  treads  or  in  the  height  of 
adjacent  risers.  The  tolerance  between  the  largest 
and  smallest  riser  or  between  the  largest  and 
smallest  tread  shall  not  exceed  %  inch  (10  mm)  in 
any  flight  of  stairs. 

Exceptions: 

1.  Where  the  bottom  riser  adjoins  a  sloping 
public  way,  walk  or  driveway  which  has  an 
established  grade  and  serves  as  a  landing,  a 
variation  in  the  height  of  the  bottom  riser  shall 
not  exceed  three  inches  (76  mm)  in  every  three 
feet  (914  mm)  of  stairway  width. 

2.  On  stairways  serving  as  aisles  in  assembly 
seating,  where  necessitated  by  changes  in  the 
gradient  of  adjoining  seating  areas  to  maintain 
adequate  sightlines,  the  maximum 
nonuniformity  of  riser  heights  within  a  flight 
and  the  nonuniformity  between  adjacent  risers 
shall  not  apply.  Where  a  nonuniformity 
exceeds  3/16  inch  (5  mm)  between  adjacent 
risers,  the  exact  location  of  the  nonuniformity 


184 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


shall  be  indicated  with  a  distinctive  marking 
stripe  on  each  tread  at  the  nosing  or  leading 
edge  adjacent  to  the  nonuniform  risers. 

1014.6.3  Winders:  Winders  shall  not  be 
permitted  in  required  means  of  egress  stairways 
except  in  occupancies  in  Use  Group  R-3  and 
stairways  serving  a  single  dwelling  unit  Such 
winders  shall  have  a  tread  depth  of  not  less  than 
nine  inches  (229  mm)  at  a  point  not  more  than  12 
inches  (305  mm)  from  the  side  where  the  tread  is 
narrower  and  the  minimum  tread  depth  shall  not 
be  less  than  six  inches  (152  mm). 

1014.6.4  Spiral  stairways  Spiral  stairways  shall 
not  be  used  as  an  element  of  a  means  of  egress 
except:  in  occupancies  in  Use  Group  R-3;  within 
a  single  dwelling  unit;  from  a  mezzanine  area  not 
more  than  250  square  feet  (23.25  m2)  in  area 
which  serves  not  more  than  five  occupants;  and  in 
penal  facilities  from  a  guard  tower,  observation 
station  or  control  room  not  more  than  250  square 
feet  (23  m2)  in  area.  The  minimum  width  of  all 
spiral  stairways  shall  be  26  inches  (660  mm)  with 
each  tread  having  a  7y2-inch  (191  mm)  minimum 
tread  depth  at  12  inches  (305  mm)  from  the 
narrow  edge.  All  treads  shall  be  identical  and  the 
rise  shall  not  be  more  than  9'/2-inches  (241  mm) 
A  minimum  headroom  of  six  feet  six  inches  (198; 
mm)  shall  be  provided. 

1014.6.5  Circular  stairways.  Circular  stairways 
shall  have  a  minimum  tread  depth  and  a  maximum 
riser  height  in  accordance  with  780  CMR  1014.6 
and  the  smaller  radius  shall  not  be  less  than  twice 
the  width  of  the  stairway.  The  minimum  tread 
depth  measured  12  inches  (305  mm)  from  the 
narrower  end  of  the  tread  shall  not  be  less  than  1 1 
inches  (279  mm). 

1014.6.6  Alternating       tread       stairways: 

Alternating  tread  stairways  are  permitted  as  an 
element  of  a  means  of  egress  in  buildings  from  a 
mezzanine  area  not  more  than  250  square  feet  (23 
nr)  in  area  and  which  serves  not  more  than  five 
occupants;  and  in  penal  facilities,  from  a  guard 
tower,  observation  station  or  control  room  not 
more  than  250  square  feet  (23  m2)  in  area. 
Alternating  tread  stairways  are  also  permitted  for 
access  to  roofs  as  provided  for  in  780  CMR 
1027.0. 

1014.6.6.1  Handrails  of  alternating  tread 
stairways:  Handrails  shall  be  provided  on 
both  sides  of  alternating  tread  stairways  and 
shall  conform  to  780  CMR  1022.0. 

1014.6.6.2  Treads  of  alternating  tread 
stairways:  Alternating  tread  stairways  shall 
have  a  minimum  projected  tread  of  five  inches 
(127  mm),  a  minimum  tread  depth  of  8V2 
inches  (216  mm),  a  minimum  tread  width  of 
seven  inches  (178  mm)  and  a  maximum  riser 
to  the  next  surface  of  the  alternating  tread  of 


9Vi  inches  (241  mm).  The  initial  tread  of  the 
stairway  shall  begin  at  the  same  elevation  as 
the  platform,  landing  or  floor  surface. 
Exception:  Alternating  tread  stairways  used 
as  an  element  of  a  means  of  egress  in 
buildings  from  a  mezzanine  area  not  more 
than  250  square  feet  (23  m2)  in  area  which 
serves  not  more  than  five  occupants  shall 
have  a  minimum  projected  tread  of  8'/2 
inches  (216  mm)  with  a  minimum  tread 
depth  of  10V2  inches  (267  mm).  The  rise  to 
the  next  alternating  tread  surface  shall  not  be 
more  than  eight  inches  (203  mm) 

1014.7  Stairway  guards  and  handrails:  Stairways 
shall  have  continuous  guards  and  handrails  on  both 
sides.  Intermediate  handrails  are  required  so  that  all 
portions  of  the  required  width  of  stairs  are  within  30 
inches  (762  mm)  of  a  handrail  On  monumental 
stairs,  handrails  shall  be  located  along  the  most 
direct  path  of  egress  travel  Handrails  shall  be 
provided  for  alternating  tread  stairways  in 
accordance  with  780  CMR  1014.6.6.1.  Guards  shall 
be  constructed  in  accordance  with  780  CMR.  1021.0. 
Handrails  shall  be  constructed  in  accordance  with 
780  CMR  1022.0. 

Exceptions: 

1 .  Stairways  with  fewer  than  three  risers  are  not 
required  to  have  handrails  where  serving  a  single 
dwelling  unit  or  where  such  stairways  are  not  in 
an  exit  access  corridor  or  aisle,  exit  or  exit 
discharge. 

2.  Aisle  stairs  provided  with  a  center  handrail  or 
serving  seating  on  one  side  shail  be  equipped  with 
a  minimum  of  one  handrail. 

3.  Stairways  within  a  dwelling  unit  shall  be 
equipped  with  a  minimum  of  one  handrail. 

4.  Spiral  stairways  shall  be  equipped  with  a 
minimum  of  one  handrail 

1014.8  Egress  doors:  Means  of  egress  stairway 
doors  shall  provide  an  egress  capacity  of  not  less 
than  the  required  capacity  of  the  stairway  which 
serves  the  floor  or  area  from  which  the  egress  door 
leads. 

1014.8.1  Width:  The  minimum  required  width  of 
every  door  to  or  from  a  means  of  egress  stairway 
shall  be  determined  by  the  most  restrictive  of  the 
following  criteria: 

1     293/4-inch  (756  mm)  clear  width  within  a 

dwelling  unit   that    is    not    required    to    be 

accessible  or  adaptable. 

2.   36-inch  (914  mm)  minimum  width  of  door 

ieaf  in  an  occupancy  in  Use  Group  1-2. 

3     32-inch  (813  mm)  clear  width  in  all  other 

cases. 

1014.8.2  Direction  of  swing:  All  means  of  egress 
doors  shall  swing  on  a  landing  in  the  direction  of 
egress  travel.  When  opening,  egress  doors  shall 
not  reduce  the  width  of  landings  to  less  than  one- 


9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


185 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


half  of  the  required  width.  When  fully  open, 
means  of  egress  doors  shall  not  project  more  than 
seven  inches  (178  mm)  into  the  required  width. 
Exception:  Doors  leading  from  a  room  or 
tenant  space  to  a  stairway  in  buildings  in  which 
only  one  exit  is  required  are  not  required  to 
swing  in  the  direction  of  egress  travel. 

1014.8.3  Door  construction:  All  doorway 
opening  protectties  shall  be  fire  doors  complying 
with  780  CMR  716.0.  Labeled  means  of  egress 
fire  doors  shall  have  a  maximum  transmitted 
temperature  end  point  of  not  more  than  450°F 
(232°C)  above  ambient  at  the  end  of  30  minutes 
of  standard  fire  test  exposure. 

1014.9  Stairway  construction:  All  stairways  shall 
be  built  of  materials  consistent  with  the  types  of 
materials  permitted  for  the  type  of  construction  of 
the  building;  except  that  wood  handrails  shall  be 
permitted  for  all  types  of  construction.  Such 
stairways  shall  have  solid  treads  and  landing 
platforms,  and  all  finish  floor  surfaces  shall  be  of 
slip-resistant  materials 

1014.9.1  Strength:  All  stairways,  platforms  and 
landings  in  other  than  occupancies  in  Use  Group 
R-3  shall  be  adequate  to  support  a  live  load  of  1 00 
pounds  per  square  foot  (488.20  kg/m2)  and  a 
concentrated  load  of  300  pounds  (136.20  kg). 

1014.10  Discharge  identification  Exit  stairways 
which  continue  beyond  the  level  of  exit  discharge 
shall  be  interrupted  at  the  level  of  exit  discharge  by 
partitions,  doors  or  other  effective  means  of 
preventing  persons  from  continuing  past  the  floor  of 
discharge  while  egressing. 

1014.11  Interior  stairway  enclosures:  Interior  exit 
stairways  shall  be  enclosed  with  fire  separation 
assemblies  having  a  fireresistance  rating  of  not  less 
than  two  hours  except  that  such  stairways  in 
occupancies  in  Use  Group  A,  B,  E,  F,  H-4,  I,  M,  R 
or  S  which  connect  less  than  four  stories  shall  be 
enclosed  with  fire  separation  assemblies  having  a 
fireresistance  rating  of  not  less  than  one  hour.  An 
exit  stairway  enclosure  shall  not  be  used  for  any 
purpose  other  than  means  of  egress.  Openings  in 
exit  enclosures,  other  than  unexposed  exterior 
openings,  shall  be  limited  to  those  necessary  for  exit 
access  to  the  enclosure  from  normally  occupied 
spaces  and  for  egress  from  the  enclosure. 

Exceptions: 

1.  Stairways  are  not  required  to  be  enclosed  in 
occupancies  in  Use  Group  A-5  in  which  all 
portions  of  the  means  of  egress  are  essentially 
open  to  the  outside. 

2.  Stairways  serving  and  contained  within  a 
single  residential  dwelling  unit  in  occupancies  in 
Use  Group  R-2  or  R-3  are  not  required  to  be 
enclosed 


3.  Stairways  that  are  not  a  required  means  of 
egress  element  are  not  required  to  be  enclosed 
where  such  stairways  comply  with  780  CMR 
713.3. 

4.  Stairways  in  open  parking  structures  which 
serve  only  the  parking  structure  are  not  required 
to  be  encloed. 

5.  Stairways  in  occupancies  in  Use  Group  1-3  as 
provided  for  in  780  CMR  410.3.7. 

1014.11.1  Exterior  walls:  Exterior  walls  of  an 
enclosed  exit  stairway  shall  comply  with  the 
requirements  of  780  CMR  705.0  for  exterior 
walls.  Where  nonrated  walls  or  unprotected 
openings  enclose  the  exterior  of  the  stairway,  the 
building  exterior  walls  within  ten  feet  (3048  mm) 
horizontally  of  the  nonrated  wall  or  unprotected 
opening  shall  be  constructed  as  required  for 
stairway  enclosures,  including  opening 
protectives,  but  are  not  required  to  exceed  a  one- 
hour  fireresistance  rating  with  3/4-hour  opening 
protectives  This  construction  shall  extend 
vertically  from  a  point  ten  feet  (3048  mm)  above 
the  topmost  landing  of  the  stairway  or  to  the  roof 
line,  whichever  is  lower,  and  down  to  the  ground 

1014.11.2  Penetrations:  Penetrations  into  and 
openings  through  an  exit  enclosure  assembly  are 
prohibited  except  for  required  exit  doors, 
ductwork  and  equipment  necessary  for 
independent  stair  pressurization,  required 
ventilation  sprinkler  piping,  standpipes  and 
electrical  conduit  serving  the  stairway  and 
terminating  at  a  steel  box  that  does  not  exceed  1 6 
square  inches  (10323  mm2)  in  area.  There  shall 
not  be  any  penetrations  or  communicating 
openings,  whether  protected  or  not  between 
adjacent  stairway  enclosures. 

1014.11.3  Door  locks:  All  interior  stairway 
means  of  egress  doors  shall  be  openable  from 
both  sides  without  the  use  of  a  key  or  special 
knowledge  or  effort. 

Exceptions: 

1 .  Stairway  discharge  doors  shall  be  operable 
from  the  egress  side  and  shall  only  be  locked 
from  the  opposit  side. 

2.  780  CMR  1014.0  shall  not  apply  to  doors 
arranged  in  accordance  with  780  CMR  403. 10 
and  10174 

1014.11.4  Exit  signs:  Each  door  to  an  enclosed 
exit  stairway  shall  be  equipped  with  tactile 
signage  reading  "Exit"  complying  with  CABO 
Al  17.1  listed  in  Appendix  A  and  installed  on  the 
side  of  the  door  from  which  egress  is  to  be  made. 

1014.11.5  Stairway  floor  number  signs:  A  sign 
shall  be  provided  at  each  floor  landing  in  all 
interior  exit  stairways  connecting  more  than  three 
stones  designating  the  floor  level  above  and 
below  the  level  of  exit  discharge  the  identification 
of  the  stairway  and  the  availability  of  roof  access 
from  that  stairway.    The  sign  shall  be  located 


186 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


approximately  five  feet  (1524  mm)  above  the 
floor  landing  in  a  position  which  is  readily  visible 
when  the  doors  are  in  the  open  and  closed 
positions. 

1014.12  Exterior  stairways:  Exterior  stairways 
shall  have  openings  on  at  least  one  side  facing  an 
outer  court,  yard  or  public  way.  The  openings  shall 
have  an  aggregate  width  of  not  less  than  20%  of  the 
stairway  perimeter  and  an  aggregate  area  on  each 
level  of  not  less  than  12%  of  the  total  perimeter  wall 
area  of  each  level.  In  other  than  occupancies  in  Use 
Group  R-3,  treads,  platforms  and  landings  which  are 
part  of  exterior  stairways  in  climates  subject  to  snow 
or  ice  shall  be  protected  to  prevent  accumulation  of 
same.  Exterior  stairways  shall  not  be  accepted  as  an 
exit  in  the  following  cases: 

1.  Occupancies  in  Use  Groups  1-2  and  1-3  in 
buildings  that  exceed  four  stories  or  50  feet 
(15240  mm)  in  height. 

2.  Floors  that  exceed  five  stories  or  65  feet 
(19812  mm)  in  height  above  the  level  of  exit 
discharge. 

1014.12.1  Location:  Exterior  exit  stairways  shall 
not  project  beyond  the  street  lot  line.  Exterior 
exit  stairways  shall  be  located  at  least  ten  feet 
(3048  mm)  from  adjacent  lot  lines  and  from  other 
buildings  on  the  same  lot  unless  openings  in  such 
buildings  are  protected  by  %-hour  opening 
protectives. 

Exception:  Noncombustible       exterior 

stairways  constituting  not  more  than  50%  of 
the  required  means  of  egress  shall  be  exempt 
from  the  ten-foot  (3048  mm)  fire  separation 
distance  requirement. 

1014.12.2  Protection:  Exterior  exit  stairs  shall  be 
separated  from  the  interior  of  the  building  by 
walls  with  a  fireresistance  rating  of  not  less  than 
one  hour,  with  fixed  or  self-closing  opening 
protectives  as  required  in  780  CMR  1014.11. 
This  protection  shall  extend  vertically  from  a 
point  ten  feet  (3048  mm)  above  the  topmost 
landing  or  the  roof  line,  whichever  is  lower,  down 
to  the  ground,  and  shall  extend  horizontally  ten 
feet  (3048  mm)  from  each  side  of  the  stairway. 
Openings  within  the  horizontal  ten-foot  (3048 
mm)  extension  of  the  protected  walls  beyond  the 
stairway  shall  be  equipped  with  fixed  3/4-hour 
opening  protective  assemblies. 

Exceptions: 

1 .  Occupancies,  other  than  those  in  Use  Group 
R-l  or  R-2,  in  buildings  that  are  two  stories  or 
less  above  grade  where  the  level  of  exit 
discharge  is  the  first  story  above  grade. 

2.  Separation  from  the  interior  of  the  building 
is  not  required  where  the  exterior  stairway  is 
served  by  an  exterior  exit  access  balcony  that 
connects  tworemote  exterior  stairways  or  other 
approved  exits,  with  a  perimeter  which  is  not 
less  than  50%  open.    To  be  considered  open. 


the  opening  shall  be  a  minimum  of  50%  of  the 
height  of  the  enclosing  wall,  with  the  top  of  the 
openings  not  less  than  seven  feet  (2134  mm) 
above  the  top  of  the  balcony. 
3.  Separation  from  the  interior  of  the  building 
is  not  required  for  an  exterior  stairway  located 
in  a  building  or  structure  that  is  permitted  to 
have  unenclosed  interior  exit  stairways  in 
accordance  with  780  CMR  1014.11. 

780  CMR  1015.0  SMOKEPROOF 
ENCLOSURES 

1015.1  General:  A  smokeproof  enclosure  shall 
consist  of  an  enclosed  interior  exit  stairway  that 
conforms  to  7S0  CMR  1014.0  and  an  outside 
balcony  or  a  ventilated  vestibule  meeting  the 
requirements  of  780  CMR  1015.0.  Where  access  to 
the  roof  is  required  by  780  CMR  1027.0,  such  access 
shall  be  from  the  smokeproof  enclosure  where  a 
smokeproof  enclosure  is  required. 

1015.2  Where  required:  In  buildings  having  a 
height  of  70  feet  above  the  grade  plane,  at  least  one 
exit  stairwell  shall  be  protected  by  a  smokeproof 
enclosure  serving  all  floor  levels.  In  buildings 
having  exit  stairwells  more  than  30  feet  below  the 
level  of  exit  discharge,  at  least  one  exit  stairwell 
shall  be  protected  by  a  smokeproof  enclosure 
serving  all  floor  levels  located  below  the  level  of  exit 
discharge. 

Exception:   Occupancies  in  Use  Group  1-2. 

1015.3  Access:  Access  to  the  stair  shall  be  from 
every  story  and  shall  be  by  way  of  a  vestibule  or  by 
way  of  an  open  exterior  balcony,  except  that  a 
vestibule  or  balcony  is  not  required  for  a  smokeproof 
enclosure  that  consists  of  a  pressurized  stairway 
complying  with  780  CMR  1015.7.  The  minimum 
dimension  of  the  vestibule  shall  not  be  less  than  the 
required  width  of  the  corridor  leading  to  the 
vestibule  but  shall  not  have  a  width  of  less  than  44 
inches  (1118  mm)  and  shall  not  have  a  length  of  less 
than  72  inches  (1829  mm)  in  the  direction  of  egress 
travel. 

1015.4  Construction:  The  smokeproof  enclosure 
shall  be  separated  from  the  remainder  of  the  building 
by  not  less  than  a  two-hour  fireresistance  rated  fire 
separation  assembly  without  openings  other  than  the 
required  means  of  egress  doors.  The  vestibule  shall 
be  separated  from  the  stairway  by  not  less  than  a 
two-hour  fireresistance  rated  fire  separation 
assembly.  The  open  exterior  balcony  shall  be 
constructed  in  accordance  with  the  fireresistance 
rating  requirements  for  floor  construction. 

1015.4.1  Door  closers:  All  doors  in  a  smokeproof 
enclosure  shall  be  self-closing  or  shall  be 
automatic-closing  by  actuation  of  a  smoke 
detector  installed  at  the  floor  side  entrance  to  the 
smokeproof    enclosure     in     accordance     with 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


187 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  716.5.  The  actuation  of  the  smoke 
detector  on  any  door  shall  activate  the  closing 
devices  on  all  doors  in  the  smoke  proof  enclosure 
at  all  levels.  Smoke  detectors  shall  be  installed  in 
accordance  with  780  CMR  918.8. 

1015.5  Natural    ventilation    alternative:       The 

provisions  of  780  CMR  1015.5.1  through  1015.5.3 
shall  apply  to  ventilation  of  smokeproof  enclosures 
by  natural  means. 

1015.5.1  Balcony  doors:  Where  access  to  the 
stairway  is  by  way  of  an  open  exterior  balcony, 
the  door  assembly  into  the  enclosure  shall  be  a 
fire  door  in  accordance  with  780  CMR  716.0. 

1015.5.2  Vestibule  doors:  Where  access  to  the 
stairway  is  by  way  of  a  vestibule,  the  door 
assembly  into  the  vestibule  shall  be  a.  fire  door 
complying  with  780  CMR  716.0.  The  door 
assembly  from  the  vestibule  to  the  stairway  shall 
have  not  less  than  a  20-minute  fire  protection 
rating  complying  with  780  CMR  716.0. 

1015.5.3  Vestibule  ventilation:  Each  vestibule 
shall  have  a  minimum  net  area  of  16  square  feet 
(1.49  m2)  of  opening  in  a  wall  facing  an  outer 
court,  yard  or  public  way  which  is  at  least  20  feet 
(6096  mm)  in  width. 

1015.6  Mechanical  ventilation  alternative:    The 

provisions  of  780  CMR  1015.6.1  through  1015.6.4 
shall  apply  to  ventilation  of  smokeproof  enclosures 
by  mechanical  means. 

1015.6.1  Vestibule  doors:  The  door  assembly 
from  the  building  into  the  vestibule  shall  be  afire 
door  complying  with  780  CMR  716.0.  The  door 
assembly  from  the  vestibule  to  the  stairway  shall 
have  not  less  than  a  20-minute  fire  protection 
rating  in  accordance  with  780  CMR  716.0.  The 
door  from  the  building  into  the  vestibule  shall  be 
provided  with  gaskets  or  other  provisions  to 
minimize  air  leakage. 

1015.6.2  Vestibule  ventilation:  The  vestibule 
shall  be  supplied  with  not  less  than  one  air  change 
per  minute,  and  the  exhaust  shall  not  be  less  than 
150%  of  supply.  Supply  air  shall  enter  and 
exhaust  air  shall  discharge  from  the  vestibule 
through  separate,  tightly  constructed  ducts  used 
only  for  that  purpose.  Supply  air  shall  enter  the 
vestibule  within  six  inches  (152  mm)  of  the  floor 
level.  The  top  of  the  exhaust  register  shall  be 
located  at  the  top  of  the  smoke  trap  but  not  more 
than  six  inches  (152  mm)  down  from  the  top  of 
the  trap,  and  shall  be  entirely  within  the  smoke 
trap  area.  Doors  in  the  open  position  shall  not 
obstruct  duct  openings.  Duct  openings  with 
conti  oiling  dampers  are  permitted  where 
necessary  to  meet  the  design  requirements,  but 
dampers  are  not  otherwise  required. 


1015.6.2.1   Engineered  ventilation  system: 

Where  a  specially  engineered  system  is  used, 
the  systems  shall  exhaust  a  quantity  of  air 
equal  to  not  less  than  90  air  changes  per  hour 
from  any  vestibule  in  the  emergency  operation 
mode  and  shall  be  sized  to  handle  three 
vestibules  simultaneously.  Smoke  detectors 
shall  be  located  at  the  floor  side  entrance  to 
each  vestibule  and  shall  activate  the  system  for 
the  affected  vestibule.  Smoke  detectors  shall 
be  installed  in  accordance  with  780  CMR 
918.8. 

1015.6.3  Smoke  trap:  The  vestibule  ceiling  shall 
be  at  least  20  inches  (50S  mm)  higher  than  the 
door  opening  into  the  vestibule  to  serve  as  a 
smoke  and  heat  trap  and  to  provide  an  upward 
moving  air  column.  The  height  shall  not  be 
decreased  unless  approved  and  justified  by  design 
and  test. 

1015.6.4  Stair  shaft  air  movement  system:  The 

stair  shaft  shall  be  provided  with  a  dampered 
relief  opening  and  supplied  with  sufficient  air  to 
maintain  a  minimum  positive  pressure  of  0.10 
inch  of  water  column  (24.88  P)  in  the  shaft 
relative  to  the  vestibule  with  all  doors  closed. 

1015.7  Ventilating  equipment:  The  activation  of 
ventilating  equipment  required  by  the  alternatives  in 
780  CMR  1015.6  and  1015.7  shall  be  by  smoke 
detectors  installed  at  each  floor  level  at  an  approved 
location  at  the  entrance  to  the  smokeproof  enclosure . 
When  the  closing  device  for  the  stair  shaft  and 
vestibule  doors  is  activated  by  smoke  detection  or 
power  failure,  the  mechanical  equipment  shall 
activate  and  operate  at  the  required  performance 
levels.  Smoke  detectors  shall  be  installed  in 
accordance  with  780  CMR  918  8. 

1015.7.1  Ventilation  systems:  Smokeproof 
enclosure  ventilation  systems  shall  be 
independent  of  other  building  ventilation  systems. 
The  equipment  and  ductwork  shall  comply  with 
one  of  the  following: 

1.  Equipment  and  ductwork  shall  be  located 
exterior  to  the  building  and  shall  be  directly 
connected  to  the  smokeproof  enclosure  or 
connected  to  the  smokeproof  enclosure  by 
ductwork  enclosed  by  two-hour  fireresistance 
rated  fire  separation  assemblies. 

2.  Equipment  and  ductwork  shall  be  located 
within  the  smokeproof  enclosure  with  intake  or 
exhaust  directly  from  and  to  the  outside  or 
through  ductwork  enclosed  by  two-hour 
fireresistance  raxed  fire  separation  as  semblies. 

3.  Equipment  and  ductwork  shall  be  located 
within  the  building  if  separated  from  the 
remainder  of  the  building,  including  other 
mechanical  equipment,  by  two-hour 
fireresistance  rated  fire  separation  assemblies. 


188 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


1015.7.2  Standby  power:  Mechanical  vestibule 
and  stair  shaft  ventilation  systems  and  automatic 
fire  detection  systems  shall  be  powered  by  an 
approved  standby  power  system  conforming  to 
7S0  CMR  403.9.1  and  527  CMR  12.00,  the 
Massachusetts  Electrical  Code,  referenced  in 
780  CMR  27,  and  listed  in  Appendix  A. 

1015.7.3  Acceptance  and  testing:  Before  the 
mechanical  equipment  is  approved,  the  system 
shall  be  tested  in  the  code  official's  presence  to 
confirm  that  the  system  is  operating  in  compliance 
with  these  requirements. 

780  CMR  1016.0  RAMPS 

1016.1  Capacity:  The  capacity  of  a  ramp  used  as  a 
means  of  egress  component  shall  be  computed  in 
accordance  with  780  CMR  1009.0. 

1016.2  Minimum  dimensions:  The  minimum 
dimensions  of  means  of  egress  ramps  shall  comply 
with  780  CMR  1016.2.1  through  1016.2.3. 

1016.2.1  Width:  The  minimum  width  of  a  means 
of  egress  ramp  shall  not  be  less  than  that  required 
for  corridors  by  780  CMR  101 1.3. 

1016.2.2  Headroom:  The  minimum  headroom  in 
all  parts  of  the  means  of  egress  ramp  shall  not  be 
less  than  SO  inches  (2032  mm). 

1016.2.3  Restrictions:  Means  of  egress  ramps 
shall  not  reduce  in  width  in  the  direction  of  egress 
travel.  Projections  into  the  required  ramp  and 
landing  width  are  prohibited  except  at  and  below 
handrail  height  where,  at  each  handrail,  the 
projections  shall  not  exceed  VA  inches  (89  mm) 
into  the  required  width.  Doors  opening  onto  a 
landing  shall  not  reduce  the  clear  width  to  less 
than  42  inches  (1067  mm). 

1016.3  Maximum  slope:  The  maximum  slope  of 
means  of  egress  ramps  in  the  direction  of  travel  shall 
be  one  unit  vertical  in  12  units  horizontal  (1:12); 
except  the  maximum  slope  shall  be:  one  unit 
vertical  in  eight  units  horizontal  (1:8)  if  the  rise  is 
limited  to  three  inches  (76  mm);  one  unit  vertical  in 
ten  units  horizontal  ( 1 : 1 0)  if  the  rise  is  limited  to  six 
inches  (152  mm).  The  maximum  slope  across  the 
direction  of  travel  shall  be  one  unit  vertical  in  48 
units  horizontal  (1:48). 

Exception:  Aisles  in  areas  of  Use  Group  A  shall 
comply  with  780  CMR  1012.0. 

1016.4  Landings:  Ramp  slopes  of  one  unit  vertical 
in  12  units  horizontal  (1:12)  or  steeper  shall  have 
landings  at  the  top,  bottom,  all  points  of  turning, 
entrance,  exit  and  at  doors.  Ramps  shall  not  have  a 
vertical  rise  greater  than  30  inches  (762  mm) 
between  landings.  The  maximum  slope  of  landings 
shall  be  one  unit  vertical  in  48  units  horizontal 
(1:48)  The  least  dimension  of  a  landing  shall  not  be 
less  than  the  required  width  of  the  ramp  except  that 


the  landing  dimension  in  the  direction  of  travel  is  not 
required  to  exceed  four  feet  (1219  mm)  where  the 
travel  from  one  ramp  to  the  next  ramp  is  a  straight 
run. 

Exception:   Aisles  in  areas  of  Use  Group  A  shall 

comply  with  780  CMR  1012.0. 

1016.5  Guards  and  handrails:  Guards  shall  be 
provided  on  both  sides  of  the  ramp  and  shall  be 
constructed  in  accordance  with  780  CMR  1021.0. 
Handrails  conforming  to  780  CMR  1022.0  shall  be 
provided  on  both  sides  of  every  ramp  having  a  slope 
greater  than  one  unit  vertical  in  20  units  horizontal 
(1:20).  Handrails  are  not  required  on  ramps  where 
the  vertical  rise  between  landings  is  six  inches  (152 
mm)  or  less. 

Exception:  Handrails  in  aisles  in  occupancies  in 
Use  Group  A  shall  comply  with  780  CMR  1012.0. 

1016.5.1  Drop-offs:  The  sides  of  ramps  and 
landings  with  a  drop-off  shall  have  a  curb  with  a 
minimum  four-inch  (102  mm)  height  above  the 
walking  surface  or  shall  be  provided  with  a 
guardrail. 

1016.6  Ramp  construction:  Ramps  used  as  an  exit 
shall  conform  to  the  applicable  requirements  of 
780  CMR  1014.9  as  to  materials  of  construction  and 
enclosure. 

1016.6.1  Surface:  For  all  slopes  exceeding  one 
unit  vertical  in  20  units  horizontal  (1:20)  and 
where  the  use  is  such  as  to  involve  danger  of 
slipping,  the  ramp  shall  be  surfaced  with  approved 
slip-resistant  materials. 

1016.6.2  Exterior  ramps:  Exterior  ramps  and 
landings  shall  be  designed  and  constructed  to 
prevent  water  from  accumulating  on  the  walking 
surface. 

780  CMR  1017.0  MEANS  OF  EGRESS 
DOORWAYS 

1017.1  General:  The  requirements  of  7S0  CMR 
1017.0  shall  apply  to  all  doorways  serving  as  a 
component  or  element  of  a.  means  of  egress,  except 
as  provided  for  in  780  CMR  1014.8,  1014.12.2, 
1015.5.1.1015.5.2  and  1015.6.1. 

1017.1.1  Floor  surface.  The  floor  surface  on 
both  sides  of  a  door  shall  be  at  the  same  elevation. 
The  floor  surface  over  which  the  door  swings 
shall  be  at  the  same  elevation  as  the  floor  level  at 
the  threshold  and  shall  extend  from  the  door  in  the 
closed  position  a  distance  equal  to  the  door  width. 

Exception:    This  requirement  shall  not  apply 

to: 

1.  Exterior  doors,  as  provided  for  in  780  CMR 
1005.6,  which  are  not  on  an  accessible  route. 

2.  Variations  in  elevation  due  to  differences  in 
finish  materials,  but  not  more  than  Vi  inch  (13 
mm). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


189 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Thresholds  at  doorways  shall  not  exceed  V* 
inch  (19  mm)  in  height  above  the  finished  floor 
surface  for  exterior  residential  sliding  doors  or  Vz 
inch  (13  mm)  for  all  other  doors.  Raised 
thresholds  and  floor  level  changes  greater  than  V* 
inch  (6  mm)  at  doorways  shall  be  beveled  with  a 
slope  not  greater  than  one  unit  vertical  in  two 
units  horizontal  (1 :2). 

1017.2  Number  of  doorways:  Each  occupant  of  a 
room  or  space  shall  have  access  to  at  least  two  exits 
or  exit  access  doors  from  the  room  or  space  where 
the  occupant  load  of  the  space  exceeds  that  listed  in 
Table  1017.2,  or  where  the  travel  distance  from  any 
point  within  the  space  to  an  exit  or  exit  access  door 
exceeds  that  listed  in  Table  1017.2.  Where  the 
occupant  load  of  a  room  or  space  is  between  501  and 
1,000,  a  minimum  of  three  exits  or  exit  access  doors 
shall  be  provided.  Where  the  occupant  load  of  a 
room  or  space  exceeds  1,000,  a  minimum  of  four 
exits  or  exit  access  doors  shall  be  provided. 
Exceptions: 

1.  Boiler,  incinerator  and  furnace  rooms  shall  be 
provided  with  two  egress  doorways  where  the 
area  exceeds  500  square  feet  (47  m2)  and 
individual  fuel-fired  equipment  exceeds  400,000 
Btuh  (117  kW)  input  capacity.  Door  ways  shall 
be  separated  by  a  horizontal  distance  equal  to  not 
less  than  one-half  of  the  diagonal  dimension  of 
the  room.  Where  two  doorways  are  required  by 
this  exception,  a  fixed  ladder  access  out  of  the 
room  shall  be  permitted  in  lieu  of  one  doorway. 

2.  In  an  occupancy  in  Use  Group  1-2,  any  room 
and  any  suite  of  rooms  as  permitted  in  780  CMR 
1011.1.1,  Exception  No. 3,  of  more  than  1,000 
square  feet  (93  m2),  shall  have  at  least  two  exit 
access  doors  remote  from  each  other. 

Table  1017.2 
SPACES  WITH  ONE  MEANS  OF  EGRESS 


Use  Group 

Maximum 

Maximum  travel 
distance  (feet) 

occupant  load 

A.B.E.F.M 

50 

75 

H-la,H-2,H-3 

3 

25 

H-4 

10 

75 

LR 

10 

75 

s 

30 

100 

Note  a.   For  requirements  for  areas  and  spaces  in  Use 
Group  H-l,  see  780  CMR  418.2.2. 
Noteb.   1  foot  =  304.8  mm. 

1017.2.1  Entrance  and  egress  doorways:  Where 
separate  doors  are  provided  for  entrance  and 
means  of  egress,  the  entrance  door  shall  be  clearly 
marked  "Entrance  Only"  in  letters  not  less  than 
six  inches  (152  mm)  in  height  and  legible  from 
both  inside  and  outside. 

1017.2.2  Location  of  doors:  The  required 
doorways  opening  from  a  room  or  space  within  a 
building  and  leading  to  an  exit  access  shall  be 
located  as  remote  as  practicable  from  each  other 


and  shall  conform  to  780  CMR  1006.4.1.  The 
distance  of  exit  access  travel  from  any  point  in  a 
room  or  space  to  a  required  exit  door  shall  not 
exceed  the  limitations  of  780  CMR  1006.5. 

1017.2.3  Door  arrangement:  The  space  between 
doors  in  series  shall  not  be  less  than  seven  feet 
(2134  mm)  as  measured  when  the  doors  are  in  the 
closed  position. 

Exception:         Power-operated     doors    and 
occupancies  in  Use  Groups  1-1  and  R-3. 

1017.3  Size  of  doors:  The  minimum  width  of  each 
door  opening  shall  be  sufficient  for  the  occupant 
load  thereof  and  shall  provide  a  clear  width  of  not 
less  than  32  inches  (813  mm).  Where  780  CMR 
1017.0  requires  a  minimum  clear  width  of  32  inches 
(813  mm)  and  a  door  opening  includes  two  door 
leaves  without  a  mullion,  one  leaf  shall  provide  a 
clear  opening  width  of  32  inches  (813  mm).  The 
maximum  width  of  a  swinging  door  leaf  shall  be  48 
inches  nominal.  Means  of  egress  doors  in  an 
occupancy  in  Use  Group  1-2  used  for  the  movement 
of  beds  shall  be  at  least  44  inches  (1118  mm)  wide. 
The  height  of  doors  shall  not  be  less  than  80  inches 
(2032  mm). 

Exceptions: 

1 .  A  means  of  egress  door  serving  a  storage  area 
of  not  more  than  800  square  feet  (74  m2)  and 
which  is  normally  unoccupied  shall  have  a 
maximum  width  often  feet  (3048  mm). 

2.  The  minimum  and  maximum  width  shall  not 
apply  to  doors  that  are  not  required  for  means  of 
egress  in  occupancies  in  Use  Groups  R-2  and  R-3 . 

3.  Door  openings  to  resident  sleeping  rooms  in 
occupancies  in  Use  Group  1-3  shall  have  a  clear 
width  of  not  less  than  28  inches  (71 1  mm). 

4.  Door  openings  to  storage  closets  less  than  ten 
square  feet  (0.93  m2)  in  area  shall  not  be  limited 
by  the  minimum  width. 

5.  Width  of  door  leafs  in  revolving  doors  that 
comply  with  780  CMR  1018.0  shall  not  be 
limited. 

6.  Door  openings  within  a  dwelling  unit  shall  not 
be  less  than  78  inches  (1981  mm)  in  height. 

7.  Exterior  door  openings  in  dwelling  units,  other 
than  the  required  exit  door,  shall  not  be  less  than 
76  inches  (1930  mm)  in  height. 

8.  Interior  egress  doorways  within  a  dwelling  unit 
not  required  to  be  adaptable  or  accessible  shall 
have  a  minimum  clear  width  of  29%-inches  (755 
mm). 

1017.4  Door  hardware:  Door  handles,  pulls, 
latches,  locks  and  other  operating  devices  shall  be  at 
a  maximum  height  of  48  inches  (1219  mm)  above 
the  finished  floor  The  operating  devices  shall  be 
capable  of  operation  with  one  hand  and  shall  not 
require  tight  grasping,  tight  pinching  or  twisting  of 
the  wrist  to  operate.  All  means  of  egress  doors  shall 
be  of  a  side-swinging  type.  All  doors  shall  swing  in 
the  direction  of  egress  where  serving  an  occupant 


190 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


load  of  50  or  more  persons  or  where  serving  a  high- 
hazard  occupancy.  The  opening  force  for  interior 
sideswinging  doors  without  closers  shall  not  exceed 
a  five-pound  (24  N)  force.  For  all  other  side- 
swinging,  sliding  and  folding  doors,  the  door  latch 
shall  release  when  subjected  to  a  15-pound  (73  N) 
force.  The  door  shall  be  set  in  motion  when 
subjected  to  a  30-pound  (146  N)  force  The  door 
shall  swing  to  a  full-open  position  when  subjected  to 
a  1 5-pound  (73  N)  force.  Forces  shall  be  applied  to 
the  latch  side 
Exceptions: 

1 .  Doors  to  private  garages,  factory  and  storage 
areas  with  an  occupant  load  often  or  less. 

2.  Horizontal  sliding-type  doors  complying  with 
780  CMR  410.4.2  shall  be  permitted  in  a  means  of 
egress  in  occupancies  in  Use  Group  1-3 . 

3 .  Doors  within  or  serving  a  single  dwelling  unit 
which  is  not  required  to  be  accessible  or  adaptable 
by  780  CMR  1 1,  are  not  required  to  be  provided 
with  lever  handled  operating  devices. 

4.  Revolving  doors  conforming  to  780  CMR 
1018.0 

5.  Horizontal  sliding  doors  complying  with 
780  CMR  1017.4.4  shall  be  permitted  in  a  means 
of  egress  in  areas  of  refuge  as  described  in 
780  CMR  1007.5  and  areas,  other  than  high- 
hazard  occupancies,  that  serve  an  occupant  load 
of  less  than  50. 

1017.4.1  Locks  and  latches:  All  means  of  egress 
doors  shall  be  readily  openable  from  the  side  from 
which  egress  is  to  be  made  without  the  use  of  a 
key  or  special  knowledge  or  effort  Refer  to 
M.G.L.  c  143  §  3R  for  locking  devices  on  the 
exterior  doors  of  apartment  houses. 
Exceptions 

1  Key  operation  shall  be  permitted  from  a 
dwelling  unit  provided  that  the  key  cannot  be 
removed  from  the  lock  when  the  door  is  locked 
from  the  side  from  which  egress  is  to  be  made 

2  Locking  devices  conforming  to  780  CMR 
409.3.2  shall  be  permitted  in  occupancies  in 
Use  Group  1-2. 

3 .  Locks  conforming  to  780  CMR  410.4  shall 
be  permitted  in  occupancies  in  Use  Group  1-3 . 
4  Means  of  egress  doors  from  individual 
dwelling  units  and  guestrooms  of  occupancies 
in  Use  Group  R  having  an  occupant  load  often 
or  less  shall  be  permitted  to  be  equipped  with 
a  night  latch,  dead  bolt  or  security  chain, 
provided  that  such  devices  are  openable  from 
the  inside  without  the  use  of  a  key  or  tool  and 
are  mounted  at  a  height  not  to  exceed  48  inches 
(1219  mm)  above  the  finished  floor. 
5.  Special  locking  arrangements  conforming 
to  780  CMR  1017.4.1.2  or  780  CMR 
1017.4.1.3. 

6  In  occupancies  in  Use  Groups  B,  F,  M  and 
S,  the  main  exterior  means  of  egress  door  is 
permitted  to  be  equipped  with  a  key-operated 
locking  device  from  the  egress  side  where  in 


compliance  with  the  following  three 
conditions: 

6. 1 .  The  locking  device  is  of  a  type  that  is 
readily  distinguishable  as  locked 

6.2.  A  readily  visible,  durable  sign  is  posted 
on  the  egress  side  on  or  adjacent  to  the  door 
stating  "This  Door  To  Remain  Unlocked 
When  This  Building  Is  Occupied  "  The  sign 
shall  be  in  letters  not  less  than  one  inch  (25 
mm)  high  on  a  contrasting  background. 

6.3  The  main  exterior  door  is  a  single  door 
or  a  pair  of  doors  which,  when  unlocked,  the 
door  or  both  leafs  of  a  pair  of  doors  swing 
free. 

7        Locking    arrangements    conforming   to 

780  CMR  1017.4.5. 

S.    In  occupancies  in  Use  Group  l-l  and  1-2 

locks  shall  be  permitted  under  the  following 

conditions: 

a.  Patient  sleeping  room  doors  may  be 
provided  with  key  locking  devices  that 
restrict  access  to  the  room  from  the 
corridor  and  that  are  openable  only  by 
staff  from  the  corridor  side,  provided  such 
device  shall  not  restrict  egress  from  the 
sleeping  room. 

b.  All  other  means  of  egress  doors  may  be 
provided  with  key  locking  devices  where 
the  clinical  needs  of  the  patients  require 
specialized  security  measures  for  their 
safety,  or  for  the  protection  of  the  public, 
provided  keys  are  carried  24  hours  per  day 
by  staffing  at  all  times,  who  have  been 
trained  in  emergency  evacuation 
procedures. 

1017.4.1.1  Flush  and  surface  bolts:  Manually 
operated  edge  or  surface-mounted  flush  bolts 
and  surface  bolts  are  prohibited.  Where  means 
of  egress  doors  are  used  in  pairs  and  approved 
automatic  flush  bolts  are  used,  the  door  leafs 
having  the  automatic  flush  bolts  shall  not  have 
a  door  knob  or  surface-mounted  hardware 
The  unlatching  of  any  leaf  shall  not  require 
more  than  one  operation. 

1017.4.1.2  Special  locking  arrangements:   In 

buildings  that  are  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in 
accordance  with  780  CMR  906.2. 1  or  with  an 
automatic  fire  detection  system,  doors  in  a 
means  of  egress  serving  occupancies  in  Use 
Group  B,  E,  F,  I,  M  S  or  R,  shall  be  unlocked 
or  shall  be  equipped  with  approved  egress 
control  devices  which  shall  unlock  in 
accordance  with  items  780  CMR  1017.4. 1 .2. 1 
through  7.  A  building  occupant  shall  not  be 
required  to  pass  through  more  than  one  door 
equipped  with  a  special  locking  device  before 
entering  an  exit. 

1 .  Actuation  of  the  automatic  sprinkler 
system  or  automatic  fire  detection  system. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


191 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2.  Loss  of  power  to  the  egress  control 
device. 

3.  Loss  of  power  to  the  building. 

4.  Capability  of  being  unlocked  manually 
by  a  signal  from  an  emergency  control 
station. 

5.  The  initiation  of  an  irreversible  and 
automatic  process  that  will  release  the  latch 
within  15  seconds  when  a  force  of  not  more 
than  15  pounds  (73  N)  is  applied  for  one 
second  to  the  release  device  and  not  relock 
until  the  door  has  been  opened  and  returned 
to  the  closed  position  for  not  less  than  30 
seconds.  Any  reopening  of  the  door  shall 
restart  the  30-second  relocking  cycle.  Any 
attempt  to  exit  which  exceeds  one  second 
shall  render  the  door  openable.  The  time 
delay  and  the  minimum  relocking  cycle  time 
shall  not  be  field  adjustable. 

Exceptions: 

1 .  An  increase  in  the  time  delay  to  30 
seconds  shall  not  be  permitted  except  as 
approved  by  the  code  official.. 

2.  An  increase  in  the  relocking  cycle 
time  to  45  seconds  shall  not  be  permitted 
except  as  approved  by  the  code  official. 

3.  In  Use  Group  B  buildings  where  one 
tenant  occupies  the  entire  floor  and  the 
building  has  a  security  station  staffed  24 
hours  each  day,  the  installation  of  a 
door  release  device  described  in 
780  CMR  1017.4.1.2,  item  5,  may  be 
omitted  on  egress  doors  in  elevator 
lobbies  provided  that  all  other  items  in 
780  CMR  1017.4.1.2  are  met,  and  in 
addition,  the  following  items  are  met: 

a.  The  building  is  equipped 
throughout  with  both  a  supervised 
automatic  fire  sprinkler  system  and  a 
supervised  automatic  fire  alarm 
system. 

b.  The  supervised  automatic  fire 
sprinkler  system  and  the  supervised 
fire  alarm  system  shall  interface  with 
the  access  control  system  to  unlock  the 
doors  automatically  upon  activation  of 
either  system. 

c  The  elevator  lobby  shall  be 
equipped  with  a  telephone  connected 
directly  to  the  staffed  security  station 
and  a  sign  having  block  letters  one 
inch  in  height  shall  be  provided 
directly  above  the  telephone  and  shall 
state:  "In  case  of  emergency,  pick  up 
telephone  You  will  be  connected 
directly  to  security  personnel". 

6.  Initiation  of  the  irreversible  process  shall 
activate  an  audible  alarm  in  the  vicinity  of 
the  door. 

7.  A  sign  having  block  letters  of  one  inch 
(25  mm)  in  height  shall  be  provided  on  the 


door  above  and  within  12  inches  (305  mm) 
of  the  release  device  stating  "Push  until 
alarm  sounds.  Door  can  be  opened  in  15 
seconds." 

1017.4.1.3  Security  locking  arrangements  in 
penal  facilities:  In  occupancies  in  Use  Groups 
A-3,  A-4,  B,  E,  F,  1,  M  and  S  within  penal 
facilities,  doors  in  means  of  egress  serving 
rooms  or  spaces  occupied  by  persons  whose 
movements  must  be  controlled  for  security 
reasons  shall  be  permitted  to  be  locked  if 
equipped  with  egress  control  devices  which 
shall  unlock  manually  and  by  at  least  one  of 
the  following  means. 

1.  Actuation  of  an  automatic  fire 
suppression  system  required  by  780  CMR 
904.1. 

2.  Actuation  of  a  key-operated  manual 
alarm  station  required  by  780  CMR  917.4. 
3    A  signal  from  a  central  control  station. 

1017.4.2  Panic  hardware:  All  doors  equipped 
with  latching  devices  in  occupancies  in  Use 
Groups  A  and  E  or  portions  of  buildings  occupied 
for  assembly  or  educational  purposes  and  serving 
rooms  or  spaces  with  an  occupant  load  greater 
than  100,  shall  be  equipped  with  approved  panic 
hardware.  Acceptable  panic  hardware  shall  be  a 
door  latching  assembly  incorporating  a  device 
which  causes  the  door  latch  to  release  and  the  leaf 
to  open  when  a  force  of  15  pounds  (73  N)  is 
applied  in  the  direction  of  egress  to  a  bar  or  panel, 
the  activating  portion  of  which  extends  not  less 
than  one-half  of  the  width  of  the  door  leaf,  and  is 
applied  at  a  height  greater  than  30  inches  (762 
mm)  but  less  than  44  inches  (1118  mm)  above  the 
floor.  The  force  shall  be  applied  at  the  lock  side 
of  the  door  or  30  inches  (762  mm)  from  the 
hinged  side,  whichever  is  farther  from  the  hinge. 
Where  fire  door  assemblies  are  required  to  have 
panic  hardware,  approved  fire  exit  hardware  shall 
be  used 

1017.4.3  Power-operated  doors:  Where  means 
of  egress  doors  are  operated  by  power,  such  as 
doors  with  a  photoelectric-actuated  mechanism  to 
open  the  door  upon  the  approach  of  a  person,  or 
doors  with  power-assisted  manual  operation,  the 
design  shall  be  such  that  in  the  event  of  power 
failure,  the  door  is  capable  of  being  opened 
manually  to  permit  means  of  egress  travel  or 
closed  where  necessary  to  safeguard  means  of 
egress.  The  forces  required  to  open  these  doors 
manually  shall  not  exceed  those  specified  in 
780  CMR  1017.4  except  that  the  force  to  set  the 
door  in  motion  shall  not  exceed  50  pounds  (244 
N).  The  door  shall  be  capable  of  swinging  from 
any  position  to  the  full  width  of  the  opening  in 
which  such  door  is  installed  when  a  force  is 
applied  to  the  door  on  the  side  from  which  egress 
is  made. 


192 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


Exceptions: 

1.  Occupancies  in  Use  Group  1-3. 

2.  Horizontal  sliding  doors  complying  with 
780  CMR  1017.4.4. 

1017.4.4  Horizontal  sliding  doors:  In  other  than 
occupancies  in  Use  Group  FL  horizontal  sliding 
doors  that  are  considered  a  component  of  a  means 
of  egress  shall  comply  with  all  of  the  following 
criteria: 

1 .  The  door  serves  an  occupant  load  of  less 
than  50; 

2.  The  door  shall  be  power  operated  and  be 
capable  of  being  operated  manually  in  the 
event  of  power  failure; 

3  The  door  shall  be  openable  from  both  sides 
without  special  knowledge  or  effort. 

4  The  force  required  to  operate  the  door  shall 
not  exceed  30  pounds  (146  N)  to  set  the  door  in 
motion  and  15  pounds  (73  N)  to  close  the  door 
or  to  open  such  door  to  the  minimum  required 
width; 

5.  The  door  shall  be  openable  with  a  force  not 
to  exceed  one  ounds  (73  N)  when  a  force  of 
250  pounds  (12220  N)  is  applied  perpendicular 
to  the  door  adjacent  to  the  operating  device; 

6.  The  door  assembly  shall  comply  with  the 
applicable  fire  protection  rating  and,  where 
rated,  shall  be  self-closing  or  automatic-closing 
by  smoke  detection,  shall  be  installed  in 
accordance  with  NFiPA  80  listed  in  Appendix 
A.  and  shall  comply  with  780  CMR  716.0; 

7.  The  door  assembly  shall  have  a  standby 
power  supply; 

8       The  door  shall   open  to  the   minimum 

required    width    within    ten    seconds    after 

activation  of  the  operating  device;  and 

9.    The  door  assembly  power  supply  shall  be 

electrically  supervised  at  a  constantly  attended 

location. 

1017.4.5  Access-controlled  egress  doors:    The 

entrance  doors  in  a  means  of  egress  in  buildings 

ith  an  occupancy  in  Use  Group  A  B,  E,  M,  R-l  or 

R-2   and   entrance  doors  to  tenant   spaces  in 

occupancies  in  Use  Groups  A,  B,  E,  M,  R-l  and 

R-2    are    permitted   to    be    equipped   with   an 

approved   entrance   and   egress   access  control 

system  which  shall  be  installed  in  accordance 

with  items  780  CMR  1017.4.5.  1.  through  6. 

1      A  sensor  shall  be  provided  on  the  egress 

side     arranged     to     detect     an     occupant 

approaching  the  doors.     The  doors  shall  be 

arranged  to  unlock  by  a  signal  from  or  loss  of 

power  to  the  sensor. 

2.  Loss  of  power  to  that  part  of  the  access 
control  system  which  locks  the  doors  shall 
automatically  unlock  the  doors 
3  The  doors  shall  be  arranged  to  unlock  from 
a  manual  unlocking  device  located  40  inches 
(1016  mm)  to  48  inches  (1219  mm)  vertically 
above  the  floor  and  within  five  feet  (1524  mm) 


of  the  secured  doors  Ready  access  shall  be 
provided  to  the  manual  unlocking  device  and 
the  device  shall  be  clearly  identified  by  a  sign. 
When  operated,  the  manual  unlocking  device 
shall  result  in  direct  interruption  of  power  to 
the  lock  -  independent  of  the  access  control 
system  electronics  -  and  the  doors  shall  remain 
unlocked  for  a  minimum  of  30  seconds 
4.  Activation  of  the  building  fire  protective 
signaling  system.  if  provided.  shall 
automatically  unlock  the  doors,  and  the  doors 
shall  remain  unlocked  until  the  fire  protective 
signaling  system  has  been  reset. 

5  Activation  of  the  building  automatic 
sprinkler  or  fire  detection  system,  if  provided, 
shall  automatically  unlock  the  doors  The 
doors  shall  remain  unlocked  until  the  fire 
protective  signaling  system  has  been  reset. 

6  Entrance  doors  in  buildings  with  an 
occupancy  in  Use  Group  A  B,  E  or  M  shall  not 
be  secured  from  the  egress  side  during  periods 
that  the  building  is  open  to  the  general  public 

1017.5  Security  grilles:  Horizontal  sliding  or 
vertical  security  grilles  which  are  part  of  a  required 
means  of  egress  shall  be  openable  from  the  inside 
without  the  use  of  a  key  or  special  knowledge  or 
effort  during  periods  that  the  space  is  occupied.  The 
grilles  shall  remain  secured  in  the  full-open  position 
during  the  period  of  occupancy  by  the  general 
public  Grilles  shall  not  be  brought  to  the  closed 
position  when  there  are  more  than  ten  persons 
occupying  spaces  served  by  a  single  exit  or  50 
persons  occupying  spaces  served  by  more  than  one 
exit.  Where  two  or  more  exits  are  required,  not  more 
than  one-half  of  the  exits  shall  be  equipped  with 
horizontal  sliding  or  vertical  security  grilles 

1017.6  Level  of  exit  discharge  doors:  Where 
glazed,  doors  at  the  level  of  exit  discharge  shall  be 
glazed  with  approved  safety  glazing.  Approved 
doors  having  one  or  more  unframed  edges  shall  be 
constructed  of  safety  glazing  not  less  than  Vi  inch 
thick.  (Also  see  780  CMR  2405) 

780  CMR  1018.0  REVOLVING  DOORS 

1018.1  General:  All  revolving  doors  shall  comply 
with  780  CMR  1018.2  through  1018.5.  In  other  than 
occupancies  in  Use  Group  H,  revolving  doors  that 
are  considered  a  component  of  the  means  of  egress 
shall  comply  with  780  CMR  1018.2  through  1018.6. 

1018.2  Collapse:  Each  revolving  door  shall  be 
capable  of  collapsing  into  a  book-fold  position  with 
parallel  egress  paths  having  an  aggregate  width  of 
not  less  than  36  inches  (914  mm).  The  revolving 
door  shall  collapse  when  a  force  of  not  more  than 
180  pounds  (880  N)  is  applied  within  3  inches  (76 
mm)  of  the  outer  edge  of  a  wing. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


193 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


is  reduced  to  not  more  than  130  pounds  (635  N) 
when: 

1.  There  is  a  power  failure  or  power  is 
removed  to  the  device  holding  the  wings  in 
position. 

2.  There  is  an  actuation  of  the  automatic 
sprinkler  system  where  such  system  is 
provided. 

3.  There  is  an  actuation  of  an  automatic  fire 
detection  system  installed  in  accordance  with 
780  CMR  918.0  for  all  areas  within  the 
building  which  are  within  75  feet  (22860  mm) 
of  the  revolving  doors.  The  collapse  of  the 
door(s)  shall  not  be  delayed  by  the  alarm 
verification  required  by  780  CMR  918.7. 

4.  There  is  an  actuation  of  a  manual  control 
switch  which  reduces  the  holding  force  to  not 
more  than  the  130-pound  (635  N)  force  level. 
Such  switch  shall  be  in  an  approved  location 
and  shall  be  clearly  identified. 

1018.3  Dispersal  area:  A  revolving  door  shall  not 
be  located  within  ten  feet  (3048  mm)  of  the  foot  or 
top  of  stairways  or  escalators  A  dispersal  area  shall 
be  provided  between  the  stairways  or  escalators  and 
the  revolving  doors. 

1018.4  Speed  control:  The  revolutions  per  minute 
for  a  revolving  door  shall  not  exceed  the  speeds 
indicated  in  Table  1018  4 

Table  1018.4 
REVOLVING  DOOR  SPEED 


Inside  diameter 

Power-dnven  type 

speed  control 

(rpm) 

Manual-type  speed 
control  (rpm) 

6'6" 
7'0" 
7'6" 
8'0" 
8'6" 
9'0" 
9'6" 
lO'O" 

11 
10 
9 
9 
8 

8 

7 

12 
11 
11 
10 
9 
9 
8 
8 

Note  a.   1  foot  =  304.8  mm.  1  inch  =  25  4  mm. 

1018.5  Adjacent  area:  Each  revolving  door  shall 
have  a  conforming  side-hinged  swinging  door  in  the 
same  wall  as,  and  within  ten  feet  (3048  mm)  of,  the 
revolving  door. 

Exception:  The  adjacent  swinging  door  is  not 
required  for  street  floor  elevator  lobbies  if  a 
stairway,  escalator  or  door  from  other  parts  of  the 
building  does  not  discharge  through  the  lobby  and 
the  lobby  does  not  have  any  occupancy  other  than 
as  a  means  of  travel  between  the  elevators  and 
street 

1018.6  Means  of  egress:  A  revolving  door  to  be 
considered  as  a  component  of  a  means  of  egress 
shall  comply  with  780  CMR  1018.2  through  1018.5 
and  the  following  conditions: 


1  Revolving  doors  shall  not  be  given  credit  for 
more  than  50%  of  the  required  exit  capacity  of  the 
building. 

2.  Each  revolving  door  shall  not  be  credited  with 
more  than  a  50-person  capacity. 

3.  Each  revolving  door  shall  be  capable  of  being 
collapsed  when  a  force  of  not  more  than  130 
pounds  (635  N)  is  applied  within  three  inches  (76 
mm)  of  the  outer  edge  of  a  wing. 

780  CMR  1019.0  HORIZONTAL  EXITS 

1019.1  General:  Horizontal  exits  shall  be  accepted 
as  an  approved  exit  element  of  a  required  means  of 
egress.  The  connection  between  an  area  of  a 
building  which  the  horizontal  exit  serves  and  the 
area  of  refuge  as  herein  required  shall  be 
accomplished  by  protected  openings  in  a 
fireresistance  rated  wall,  or  by  an  open-air  balcony 
or  bridge. 

1019.2  Separation:  The  separation  between 
buildings  or  areas  of  refuge  connected  by  a 
horizontal  exit  shall  be  provided  by  at  least  a  two- 
hour  fireresistance  rated  fire  wall  or  fire  separation 
assembly  with  approved  opening  protectives 
complying  with  780  CMR  7  and  Table  602. 

1019.2.1  Doors:  All  doors  shall  swing  in  the 
direction  of  egress  travel  Where  the  horizontal 
exit  serves  as  an  exit  from  both  sides  of  the  wall, 
there  shall  be  adjacent  openings  with  swinging 
fire  doors  opening  in  opposite  directions. 

Exception:  Horizontal      sliding     doors 

complying  with  780  CMR   1017.4.4  where 
serving  an  occupant  load  of  less  than  50 

1019.3  Area  of  refuge:  The  discharge  area  of  a 
horizontal  exit  shall  be  either  public  areas  or  spaces 
occupied  by  the  same  tenant,  and  each  such  area  of 
refuge  shall  be  adequate  to  hold  the  total  occupant 
load  of  both  connected  areas  The  capacity  of  areas 
of  refuge  shall  be  computed  on  a  minimum  net  floor 
area  allowance  for  each  occupant  to  be 
accommodated  therein,  not  including  areas  of 
stairways,  elevators  and  other  shafts  or  courts,  as 
follows: 

1 .  30  square  feet  (2.8  m2)  per  patient  for  hospitals 
and  nursing  homes 

2.  Six  square  feet  (0  56  nr)  per  occupant  on 
stories  not  housing  patients  confined  to  a  bed  or 
litter  in  an  occupancy  in  Use  Group  1-2. 

3.  Six  square  feet  (0.56  nr)  per  occupant  in  an 
occupancy  in  Use  Group  1-3. 

4.  Three  square  feet  (0.28  nr1)  in  all  other  cases. 

1019.4  Egress  from  area  of  refuge  The  path  of 
egress  travel  from  the  horizontal  exit  through  the 
area  of  refuge  to  another  exit  shall  be  continuously 
available.  In  other  than  occupancies  in  Use  Group 
1-3,  there  shall  be  at  least  one  exit  on  each  side  of  the 
horizontal  exit  which  is  not  a  horizontal  exit.   Any 


194 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


area  of  refuge  not  having  access  to  an  exit,  other 
than  a  horizontal  exit,  shall  be  considered  as  part  of 
an  adjoining  area  of  refuge  with  such  exit.  In  the 
area(s)  served  by  the  horizontal  exit,  the  length  of 
exit  access  travel  distance  to  the  horizontal  exit  or 
another  exit  shall  not  exceed  the  requirements  of 
780  CMR  1006.5.  Occupancies  in  Use  Group  1-3 
shall  conform  to  780  CMR  410.3.3. 

780  CMR  1020.0  LEVEL  OF  EXIT 

DISCHARGE  PASSAGEWAYS  USED 

AS  AN  EXTT  ELEMENT 

1020.1  Passageways:  Every  required  interior  and 
exterior  exit  element  which  does  not  adjoin  a.  public 
way  shall  be  directly  connected  to  the  public  way  or 
to  an  open  court  leading  to  the  public  way  by  an 
enclosed  passageway  at  the  level  of  exit  discharge, 
constructed  in  accordance  with  the  requirements  for 
the  enclosure  of  the  exit  it  serves,  or  through  lobbies 
or  vestibules  as  provided  for  in  780  CMR  1020.0. 
Building  areas  below  the  level  of  exit  discharge 
shall  be  separated  from  the  passageway  in 
accordance  with  the  requirements  for  the  enclosure 
of  exits. 

1020.2  Vestibule:  Where  an  exit  discharges  into  an 
interior  vestibule,  the  vestibule  shall  be  used  for 
ingress  and  means  of  egress  only,  and  the  vestibule 
shall  comply  with  780  CMR  1020.2. 1  and  1020.2.2. 

1020.2.1  Depth  and  width:  The  vestibule  depth 
from  the  exterior  of  the  building  shall  not  be 
greater  than  ten  feet  (3048  mm)  and  the  width 
shall  not  be  greater  than  20  feet  (6096  mm). 

1020.2.2  Separation:  The  vestibule  shall  be 
separated  from  the  remainder  of  the  level  of  exit 
discharge  by  self-closing  doors  and  the  equivalent 
of ' .  4-inch-thick  wired  glass  in  steel  frames. 

1020.3  Lobby:  Where  an  exit  discharges  into  an 
interior  lobby  located  at  the  level  of  exit  discharge, 
the  story  containing  the  lobby  shall  be  equipped 
throughout  with  an  automatic  sprinkler  system 
installed  in  accordance  with  780  CMR  906.2. 1  or 
906.2.2.  Opening  protectives  shall  be  required  in 
accordance  with  Table  716. 1  at  the  point  in  which  an 
enclosed  exit  stairway  discharges  into  a  lobby. 

Exception:  An  automatic  sprinkler  system  is  not 
required  in  areas  that  are  separated  from  the  lobby 
by  fire  separation  assemblies  (see  780  CMR 
709.0)  having  a  fireresistance  rating  of  not  less 
than  that  required  for  exit  enclosures. 

1020.4  Width  and  height:  The  clear  width  of  the 
passageway  shall  not  be  less  than  the  width  required 
for  the  capacity  of  the  exit  stairways  leading  thereto 
and  all  required  exit  doorways  opening  into  the 
passageway  Such  passageway  shall  have  a 
minimum  width  of  44  inches  (1118  mm)  and  a 


minimum  clear  ceiling  height  of  eight  feet  (23438 
mm). 

1020.5  Maximum  stairway  limitations:  Not  more 
than  50%  of  the  required  stamvays  shall  discharge 
through  the  same  passageway.  Multiple  lobbies 
constructed  in  accordance  with  780  CMR  1020.3 
located  adjacent  to  one  another  shall  be  separated 
from  each  other  in  accordance  with  the  requirements 
for  enclosure  of  exits. 

780  CMR  1021.0  GUARDS 

1021.1  General:  Where  required  by  the  provisions 
of  780  CMR  406.5,  408.3.2,  1005.5,  1014.7,  1016.5 
and  1825.5,  guards  shall  be  designed  and 
constructed  in  accordance  with  the  requirements  of 
780  CMR  1021.0  and  780  CMR  1615.5  A  guardrail 
system  is  a  system  of  building  components  located 
near  the  open  sides  of  elevated  walking  surfaces  for 
the  purpose  of  minimizing  the  possibility  of  an 
accidental  fall  from  the  walking  surface  to  the  lower 
level. 

1021.2  Height:  The  guards  shall  be  at  least  42 
inches  (1067  mm)  in  height  measured  vertically 
above  the  leading  edge  of  the  tread  or  adjacent 
walking  surface. 

Exceptions: 

1.  In  other  than  occupancies  in  Use  Group  E, 
guards  shall  not  be  less  than  34  inches  (864  mm) 
in  height  above  the  leading  edge  of  the  tread 
along  stairs  which  are  not  more  than  20  feet  (6096 
mm)  in  height  or  which  reverse  direction  at  an 
intermediate  landing  with  12  inches  (305  mm)  or 
less  measured  horizontally  between  successive 
flights. 

2.  Guards  along  open-sided  floor  areas, 
mezzanines  and  landings  in  occupancies  in  Use 
Group  R-3  shall  not  be  less  than  36  inches  (914 
mm)  in  height. 

1021.3  Opening  limitations:  In  occupancies  in  Use 
Groups  A,  B,  E,  H-4,  1-1,  1-2,  M  and  R,  and  in 
public  garages  and  open  parking  structures,  open 
guards  shall  have  balusters  or  be  of  solid  material 
such  that  a  sphere  with  a  diameter  of  four  inches 
(102  mm)  cannot  pass  through  any  opening.  Guards 
shall  not  have  an  ornamental  pattern  that  would 
provide  a  ladder  effect. 

Exception:  The  triangular  openings  formed  by 
the  riser,  tread  and  bottom  rail  at  the  open  side  of 
a.  stairway  shall  be  of  a  maximum  size  such  that  a 
sphere  six  inches  (152  mm)  in  diameter  cannot 
pass  through  the  opening. 

In  occupancies  in  Use  Groups  1-3,  F,  H-l,  H-2,  H- 
3  and  S,  other  than  public  garages  and  open  parking 
structures,  balusters,  horizontal  intermediate  rails  or 
other  construction  shall  not  permit  a  sphere  with  a 
diameter  of  21  inches  (533  mm)  to  pass  through  any 
opening. 


Him    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


195 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1021.4  Railings:  Metal  or  other  approved 
noncombustible  railings  shall  be  provided  on 
balconies  and  galleries  as  prescribed  in  780  CMR 
1021.4.1  through  1021.4.3. 

1021.4.1  At  fascia:  Railings  shall  be  provided: 
at  the  fascia  of  boxes,  balconies  and  galleries  and 
shall  not  be  less  than  26  inches  (660  mm)  in 
height;  at  the  end  of  aisles  extending  to  the  fascia 
for  the  full  width  of  the  aisle  and  shall  not  be  less 
than  36  inches  (914  mm)  in  height;  and  at  the  foot 
of  steps  for  the  full  width  of  the  steps  and  shall 
not  be  less  than  42  inches  (1067  mm)  in  height. 

1021.4.2  At  cross  aisles:  Railings  shall  be 
provided  along  cross  aisles,  and  shall  not  be  less 
than  26  inches  (660  mm)  in  height  except  that 
railings  are  not  required  where  the  backs  of  the 
seats  along  the  front  of  the  aisles  project  24  inches 
(610  mm)  or  more  above  the  floor  of  the  aisle. 

1021.4.3  Successive  tiers:  Where  searings  are 
arranged  in  successive  tiers,  and  where  the  height 
of  rise  between  platforms  exceeds  18  inches  (457 
mm),  railings  not  less  than  26  inches  (660  mm)  in 
height  shall  be  provided  along  the  entire  row  of 
seats  at  the  edge  of  the  platform. 

780  CMR  1022.0  HANDRAILS 

1022.1  General:  Where  required  by  the  provisions 
of  780  CMR  1012.5.  1013.0, 1014.6.6.1,  1014.7  and 
1016.5,  handrails  shall  be  designed  and  constructed 
in  accordance  with  780  CMR  1022.0  and  780  CMR 

1615.5  A  handrail  is  a  horizontal  or  sloping  rail 
grasped  by  hand  for  guidance  or  support,  and  for 
arresting  falls  on  the  adjacent  walking  surface. 

1022.2  Handrail  details:  Handrail-gripping 
surfaces  shall  be  continuous,  without  interruption  by 
newel  posts,  other  structure  elements  or 
obstructions  A  handrail  and  any  wall  or  other 
surface  adjacent  to  the  handrail  shall  be  free  of  any 
sharp  or  abrasive  elements.  The  clear  space  between 
the  handrail  and  the  adjacent  wall  or  surface  shall 
not  be  less  than  VA  inches  (38  mm).  Edges  shall 
have  a  minimum  radius  of  1/a  inch  (3  mm). 

1022.2.1  Projection:  Handrails  shall  not  project 
more  than  VA  inches  (89  mm)  into  the  required 
passageway,  aisle,  corridor,  stair  or  ramp  width. 

1022.2.2  Height:  Handrails  shall  not  be  less  than 
34  inches  (864  mm)  nor  more  than  38  inches 
(965  mm),  measured  vertically,  above  the  leading 
edge  of  the  treads  or  above  the  finished  floor  of 
the  landing  or  walking  surfaces. 

Exceptions: 

1     Handrails  that  form  part  of  a  guard  shall 

have  a  height  not  less  than  34  inches  (864  mm) 

and  not  more  than  42  inches  (1067  mm). 

2.    Handrails  within  individual  dwelling  units 

shall  not  be  less  than  30  inches  (762  mm)  nor 

more  than  38   inches  (965  mm),   measured 


vertically,  above  the  leading  edge  of  the  treads 
or  above  the  finished  floor. 

1022.2.3  Handrails  in  guards  Handrails  that 
form  part  of  a  guard  shall  comply  with  780  CMR 
1021.3. 

1022.2.4  Handrail  ends:  At  locations  where 
handrails  are  not  continuous  between  stairway 
flights,  including  the  top  and  bottom  of  a 
stairway,  the  handrails  shall  extend  horizontally 
at  least  12  inches  (305  mm)  beyond  the  top  riser 
and  continue  to  slope  for  the  depth  of  one  tread 
beyond  the  bottom  riser.  The  handrail  ends  shall 
be  returned  to  a  wall  or  post 

Where  handrails  are  not  continuous  between 
ramp  segments,  including  the  top  and  bottom  of  a 
ramp,  the  handrails  shall  extend  at  least  12  inches 
(305  mm)  beyond  the  top  and  bottom  of  the  ramp 
segment  and  shall  be  parallel  with  the  floor  or 
ground  surface.  The  handrail  ends  shall  be 
returned  to  a  wall  or  post 

Exception:  Within  a  dwelling  unit,  the 
horizontal  extension  beyond  the  top  riser  of  the 
stairway  flight  or  top  of  the  ramp  segment,  and 
the  extension  beyond  the  bottom  riser  of  the 
stairway  flight  or  bottom  of  the  ramp  segment, 
is  not  required. 

1022.2.5  Handrail  grip  size:  All  stairway 
handrails  shall  have  a  circular  cross  section  with 
an  outside  diameter  of  at  least  1  Vi-inches  (32  mm) 
and  not  greater  than  two  inches  (51  mm) 

Exceptions 

1 .  Any  other  shape  with  a  perimeter  dimension 
of  at  least  four  inches  (100  mm),  but  not 
greater  than  6%  inches  (158  mm)  with  the 
largest  cross-sectional  dimension  not 
exceeding  2V*  inches  (57  mm). 

2.  Approved  rails  of  equivalent  graspability. 

1022.2.6  Handrails  of  alternating  tread 
stairways:  Stair  handrails  of  alternating  tread 
stairways  shall  be  of  such  a  configuration  as  to 
provide  an  adequate  hand-hold  for  a  person 
grasping  the  handrail  to  avoid  falling.  A 
minimum  distance  of  six  inches  (152  mm)  shall 
be  provided  between  the  stair  handrail  and  any 
other  object.  A  minimum  distance  of  12  inches 
(305  mm)  shall  be  provided  between  the  stair 
handrails  of  adjacent  alternating  tread  stairways. 
Handrails  on  alternating  tread  stairways  shall  be 
spaced  a  minimum  width  of  17  inches  (432  mm), 
not  to  exceed  24  inches  (610  mm),  between  the 
handrails. 

780  CMR  1023.0  EXIT  SIGNS  AND  LIGHTS 

1023.1  Location:  In  all  buildings,  rooms  or  spaces 
required  to  have  more  than  one  exit  or  exit  access, 
all  required  means  of  egress  shall  be  indicated  with 
approved  signs  reading  "Exit,"  visible  from  the  exit 
access  and,  where  necessary,  supplemented  by 
directional    signs    in    the    exit    access    corridors 


196 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MEANS  OF  EGRESS 


indicating  the  direction  and  way  of  egress  All 
"Exit"  signs  shall  be  located  at  exit  doors  or  exit 
access  areas,  so  as  to  be  readily  visible.  Sign 
placement  shall  be  such  that  any  point  in  the  exit 
access  shall  not  be  more  than  100  feet  (30480  mm) 
from  the  nearest  visible  sign- 
Exceptions: 

1 .  "Exit"  signs  are  not  required  in  sleeping  room 
areas  in  occupancies  in  Use  Group  1-3. 

2.  Main  exterior  exit  doors  which  are  obviously 
and  clearly  identifiable  as  exits  are  not  required  to 
have  "Exit"  signs  where  approved. 

1023.2  Size  and  color:  "Exit"  signs  shall  have  red 
letters  at  least  six  inches  (152  mm)  high  and  the 
minimum  width  of  each  stroke  shall  be  Vt  inch  (19 
mm)  on  a  white  background  or  in  other  approved 
distinguishable  colors.  The  word  "Exit,"  except  the 
letter  I,  shall  have  letters  having  a  width  of  not  less 
than  two  inches  (51  mm)  and  the  minimum  spacing 
between  letters  shall  not  be  less  than  %  inch  (10 
mm).  Signs  larger  than  the  minimum  size  herein 
required  shall  have  letter  widths  and  spacing  in  the 
same  proportions  to  the  height  as  indicated  in 
780  CMR  1023.0.  If  an  arrow  is  provided  as  part  of 
an  "Exit"  sign,  the  construction  shall  be  such  that  the 
arrow  direction  cannot  be  readily  changed.  The 
word  "Exit"  shall  be  clearly  discernible  when  the 
sign  illumination  means  is  not  energized 

1023.3  Illumination  Each  sign  shall  be  illuminated 
by  a  source  providing  not  less  than  five  footcandles 
(54  lux)  at  the  illuminated  surface  and  shall  have  a 
contrast  ratio  of  not  less  than  0.5. 

Exception:  Approved  self-luminous  signs  which 
provide  evenly  illuminated  letters  shall  have  a 
minimum  luminance  of  0.06  foot  lamberts  (0.21 
cd/nr). 

1023.4  Power  source:  All  "Exit"  signs  shall  be 
illuminated  at  all  times  that  the  building  is  occupied 
To  assure  continued  illumination  for  a  duration  of 
not  less  than  1  hour  in  case  of  primary  power  loss, 
the  "Exit"  signs  shall  be  connected  to  an  emergency 
electrical  system  that  complies  with  527  CMR 
12.00,  the  Massachusetts  Electrical  Code, 
referenced  in  780  CMR  27,  and  listed  in 
Appendix  A. 

Exceptions: 

1.  Approved  self-luminous  signs  which  provide 
continuous  illumination  independent  of  external 
power  sources  are  not  required  to  comply  with 
780  CMR  2706.0 

2.  All  exit  signs  tested  and  listed  to  UL-924  as 
listed  in  Appendix  A  and  satisfying  the  power 
source  requirements  of  780  CMR  1023. 4  shall  be 
permitted. 


780  CMR  1024.0  MEANS  OF  EGRESS 
LIGHTING 

1024.1  Artificial  lighting:  All  means  of  egress  in 
other  than  occupancies  in  Use  Group  R-3  shall  be 
equipped  with  artificial  lighting  facilities  to  provide 
the  intensity  of  illumination  herein  prescribed 
continuously  during  the  time  that  conditions  of 
occupancy  of  the  building  require  that  the  exits  be 
available.  Lighting  shall  also  be  provided  to 
illuminate  the  exit  discharge  Means  of  egress 
lighting  in  occupancies  in  Use  Group  R-2,  other  than 
lighting  within  a  dwelling  unit,  shall  be  wired  on  a 
circuit  independent  of  circuits  within  any  dwelling 
unit.  The  disconnecting  means  and  overcurrent 
protection  device  shall  not  be  located  within  a 
dM'elling  unit  or  such  that  access  to  such  devices 
must  be  obtained  by  going  through  a  dwelling  unit. 

1024.2  Intensity  of  illumination  The  intensity  of 
floor  lighting  shall  not  be  less  than  one  footcandle 
(1 1  lux)  except  as  provided  for  in  780  CMR  1024  3 

1024.3  Use  Groups  A  and  E  In  occupancies  in 
Use  Groups  A  and  E  for  the  exhibition  of  motion 
pictures  or  other  projections  by  means  of  directed 
light,  the  minimum  required  illumination  of  aisles 
during  such  period  of  projection  shall  be  0.2 
footcandle  (2  lux). 

1024.3.1  Control:  The  lighting  of  exits,  aisles 
and  auditoriums  shall  be  controlled  from  a 
location  that  does  not  provide  access  to 
unauthorized  persons.  Supplementary  control 
shall  be  provided  as  specified  in  780  CMR  411 .4 
in  the  motion  picture  projection  room. 

1024.4  Power  source:  Means  of  egress  lighting  in 
all  buildings,  rooms  or  spaces  required  to  have  more 
than  one  exit  or  exit  access  shall  be  connected  to  an 
emergency  electrical  system  that  complies  with 
527  CMR  12.00,  the  Massachusetts  Electrical 
Code,  referenced  in  780  CMR  27,  and  listed  in 
Appendix  A  to  assure  continued  illumination  for  a 
duration  of  not  less  than  one  hour  in  case  of 
emergency  or  primary  power  loss. 

780  CMR  1025.0  FIRE  ESCAPES 

1025.1  Where  permitted:  Fire  escapes  shall  be 
permitted  only  as  provided  for  in  780  CMR  1025. 1 . 1 
through  1025.1.4. 

1025.1.1  New  buildings:  Fire  escapes  shall  not 
constitute  any  part  of  the  required  means  of  egress 
in  new  buildings. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


197 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1025.1.2  Existing  fire  escapes:  Existing  fire 
escapes  shall  be  continued  to  be  accepted  as  a 
component  in  the  means  of  egress  in  existing 
buildings  only. 

1025.1.3  New  fire  escapes:  New  fire  escapes  for 
existing  buildings  shall  be  permitted  only  where 
exterior  stairs  cannot  be  utilized  due  to  lot  lines 
limiting  stair  size  or  due  to  the  sidewalks,  alleys 
or  roads  at  grade  level.  New  fire  escapes  shall  not 
incorporate  ladders  or  access  by  windows. 

1025.1.4  Limitations:  Fire  escapes  shall  comply 
with  780  CMR  1025.0  and  shall  not  constitute 
more  than  50%  of  the  required  number  of  exits 
nor  more  than  50%  of  the  required  exit  capacity. 

1025.2  Location:  Where  located  on  the  front  of  the 
building  and  where  projecting  beyond  the  building 
line,  the  lowest  landing  shall  not  be  less  than  seven 
feet  (2134  mm)  or  more  than  12  feet  (3658  mm) 
above  grade,  and  shall  be  equipped  with  a 
counterbalanced  stairway  to  the  street  In  alleyways 
and  thoroughfares  less  than  30  feet  (9144  mm)  wide, 
the  clearance  under  the  lowest  landing  shall  not  be 
less  than  12  feet  (3658  mm). 

1025.3  Construction:  The  fire  escape  shall  be 
designed  to  support  a  live  load  of  1 00  pounds  per 
square  foot  (488.20  kg/m2)  and  shall  be  constructed 
of  steel  or  other  approved  noncombustible  materials. 
Fire  escapes  constructed  of  wood  not  less  than 
nominal  two  inches  thick  are  permitted  on  buildings 
of  Type  5  construction.  Walkways  and  railings 
located  over  or  supported  by  combustible  roofs  in 
buildings  of  Types  3  and  4  construction  are 
permitted  to  be  of  wood  not  less  than  nominal  two 
inches  thick. 

1025.3.1  Dimensions:  Stairs  shall  be  at  least  22 
inches  (559  mm)  wide  with  risers  not  more  than, 
and  treads  not  less  than,  eight  inches  (203  mm) 
and  landings  at  the  foot  of  stairs  not  less  than  40 
inches  (1016  mm)  wide  by  36  inches  (914  mm) 
long,  located  not  more  than  eight  inches  (203  mm) 
below  the  door 

1025.3.2  Opening  protectives:  Doors  and 
windows  along  the  fire  escape  shall  be  protected 
with  3/4-hour  opening  protectives. 

780  CMR  1026.0  SLIDESCAPES 

1026.1  Where  permitted:  Existing  slidescapes  and 
safety  chutes  shall  be  permitted  in  existing 
occupancies  in  Use  Groups  E,  H  and  I  where 
approved.  Slidescapes  and  safety  chutes  shall  be 
permitted  in  occupancies  in  Use  Groups  H-l  and  H- 
2  where  constructed  in  an  approved  manner. 

1026.2  Location:  The  arrangement  and  location  of 
slidescapes  shall  conform  to  780  CMR  10  for  means 


of  egress  and  shall  be  designated  by  "Exit"  signs  and 
lights  as  provided  for  in  780  CMR  1023.0. 

1026.3  Construction  All  chutes  shall  be 
constructed  of  approved  noncombustible  materials 
with  a  pitch  in  the  line  of  travel  of  not  less  than  24 
nor  more  than  42°  (0.42  rad  to  0.73  rad),  measured 
on  the  developed  circumference  of  spiral  chutes. 
Straight  chutes  shall  not  be  less  than  24  inches  (610 
mm)  and  spiral  chutes  shall  not  be  less  than  28 
inches  (71 1  mm)  in  clear  width,  nor  more  than  44 
inches  (1118  mm)  wide  in  any  case.  Where  erected 
on  the  interior  of  a  building,  the  chutes  shall  be 
enclosed  as  required  in  780  CMR  1014.11  for 
interior  stairways  with  direct  means  of  egress  to  a 
street  or  other  public  way. 

1026.4  Capacity  Slidescapes  shall  have  a  rated 
egress  capacity  of  60  occupants  per  slide. 
Slidescapes,  except  as  permitted  for  occupancies  in 
Use  Groups  H-l  and  H-2,  shall  not  constitute  more 
than  25%  of  the  required  means  of  egress  capacity 
from  any  building  or  structure  or  any  individual 
story. 

780  CMR  1027.0  ACCESS  TO  ROOF 

1027.1  By  stairway  or  ladder  In  buildings  more 
than  three  stories  in  height  except  those  with  a  roof 
slope  greater  than  four  units  vertical  in  12  units 
horizontal  (4:12).  access  to  the  roof  shall  be 
provided  by  means  of  a  stairway,  an  alternating 
tread  stair  in  accordance  with  780  CMR  1014.6.6  or 
a  ladder  and  trap  door  The  ladder  shall  not  be  on 
the  exterior  of  the  building.  Where  the  roof  is  used 
as  a  roof  garden  or  for  other  habitable  purposes, 
sufficient  stairways  shall  extend  to  the  roof  to 
provide  the  necessity  exit  facilities  from  the  roof  as 
required  for  such  occupancy  Roof  trap  doors  shall 
be  constructed  to  comply  with  780  CMR  1510.2. 

1027.1.1    Optional   stairway   or  ladder:      In 

buildings  not  required  to  have  a  stairway, 
alternating  tread  stair  or  ladder  to  the  roof,  such 
devices,  if  provided,  shall  conform  to  the 
provisions  of  780  CMR  1027.0.  Ladders  placed 
on  the  exterior  of  the  building  shall  be  of  metal 
and,  if  exceeding  20  feet  (6096  mm)  in  height, 
shall  have  a  protective  cage  or  other  safety  device. 
The  siderails  of  exterior  ladders  shall  be  carried 
over  the  coping  or  parapet  to  serve  as  handrails 
Other  design  details  of  such  exterior  ladders  are 
subject  to  approval. 

1027.2  Roof  enclosures:  stairways  extending 
through  roofs  shall  be  enclosed  in  roof  structures  of 
fireresistance  rated  construction  which  conform  to 
the  requirements  of  780  CMR  1510.0. 


198 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


CHAPTER  11 

ACCESSIBILITY 

(780  CMR  11  is  Entirely  Unique  to  Massachusetts) 

780  CMR  1101.0  M.G.L.  c  22,  §  13 A  provides  that  Architectural  Access  Board,  Executive  Office  of 

all  public    buildings   shall   be   designed   to    be  Public  Safety. 

accessible  to,  functional  for  and  safe  for  the  use  by  In  accordance  with  M.G.L.   c.   143,  §3  and 

physically  handicapped  persons,  in  conformance  780  CMR  106.1,  said  regulations  shall  be  enforced 

with    the    Massachusetts    Architectural    Access  by    the   municipal   building   code    enforcement 

Board's  Rules  and  Regulations  (521  CMR  1.00)  official  or  state  inspector,  as  applicable 

listed  in  Appendix  A   and  promulgated  by  the 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  201 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1025.1.2  Existing  fire  escapes:  Existing  fire 
escapes  shall  be  continued  to  be  accepted  as  a 
component  in  the  means  of  egress  in  existing 
buildings  only 

1025.1.3  New  fire  escapes:  New  fire  escapes  for 
existing  buildings  shall  be  permitted  only  where 
exterior  stairs  cannot  be  utilized  due  to  lot  lines 
limiting  stair  size  or  due  to  the  sidewalks,  alleys 
or  roads  at  grade  level.  New  fire  escapes  shall  not 
incorporate  ladders  or  access  by  windows. 

1025.1.4  Limitations:  Fire  escapes  shall  comply 
with  780  CMR  1025.0  and  shall  not  constitute 
more  than  50%  of  the  required  number  of  exits 
nor  more  than  50%  of  the  required  exit  capacity. 

1025.2  Location:  Where  located  on  the  front  of  the 
building  and  where  projecting  beyond  the  building 
line,  the  lowest  landing  shall  not  be  less  than  seven 
feet  (2134  mm)  or  more  than  12  feet  (3658  mm) 
above  grade,  and  shall  be  equipped  with  a 
counterbalanced  stairway  to  the  street  In  alleyways 
and  thoroughfares  less  than  30  feet  (9144  mm)  wide, 
the  clearance  under  the  lowest  landing  shall  not  be 
less  than  12  feet  (3658  mm). 

1025.3  Construction:  The  fire  escape  shall  be 
designed  to  support  a  live  load  of  100  pounds  per 
square  foot  (488.20  kg/m2)  and  shall  be  constructed 
of  steel  or  other  approved  noncombustible  materials. 
Fire  escapes  constructed  of  wood  not  less  than 
nominal  two  inches  thick  are  permitted  on  buildings 
of  Type  5  construction.  Walkways  and  railings 
located  over  or  supported  by  combustible  roofs  in 
buildings  of  Types  3  and  4  construction  are 
permitted  to  be  of  wood  not  less  than  nominal  two 
inches  thick. 

1025.3.1  Dimensions:  Stairs  shall  be  at  least  22 
inches  (559  mm)  wide  with  risers  not  more  than, 
and  treads  not  less  than,  eight  inches  (203  mm) 
and  landings  at  the  foot  of  stairs  not  less  than  40 
inches  (1016  mm)  wide  by  36  inches  (914  mm) 
long,  located  not  more  than  eight  inches  (203  mm) 
below  the  door. 

1025.3.2  Opening  protectives:  Doors  and 
windows  along  the  fire  escape  shall  be  protected 
with  3/4-hour  opening  protectives. 

780  CMR  1026.0  SLEDESCAPES 

1026.1  Where  permitted:  Existing  slidescapes  and 
safety  chutes  shall  be  permitted  in  existing 
occupancies  in  Use  Groups  E,  H  and  I  where 
approved.  Slidescapes  and  safety  chutes  shall  be 
permitted  in  occupancies  in  Use  Groups  H-l  and  H- 
2  where  constructed  in  an  approved  manner. 

1026.2  Location:  The  arrangement  and  location  of 
slidescapes  shall  conform  to  780  CMR  10  for  means 


of  egress  and  shall  be  designated  by  "Exit"  signs  and 
lights  as  provided  for  in  780  CMR  1023.0. 

1026.3  Construction:  All  chutes  shall  be 
constructed  of  approved  noncombustible  materials 
with  a  pitch  in  the  line  of  travel  of  not  less  than  24 
nor  more  than  42°  (0  42  rad  to  0.73  rad),  measured 
on  the  developed  circumference  of  spiral  chutes. 
Straight  chutes  shall  not  be  less  than  24  inches  (6 1 0 
mm)  and  spiral  chutes  shall  not  be  less  than  28 
inches  (71 1  mm)  in  clear  width,  nor  more  than  44 
inches  (1118  mm)  wide  in  any  case.  Where  erected 
on  the  interior  of  a  building,  the  chutes  shall  be 
enclosed  as  required  in  780  CMR  1014.11  for 
interior  stairways  with  direct  means  of  egress  to  a 
street  or  other  public  way. 

1026.4  Capacity  Slidescapes  shall  have  a  rated 
egress  capacity  of  60  occupants  per  slide. 
Slidescapes,  except  as  permitted  for  occupancies  in 
Use  Groups  H-l  and  H-2.  shall  not  constitute  more 
than  25%  of  the  required  means  of  egress  capacity 
from  any  building  or  structure  or  any  individual 
story. 

780  CMR  1027.0  ACCESS  TO  ROOF 

1027.1  By  stairway  or  ladder:  In  buildings  more 
than  three  stories  in  height  except  those  with  a  roof 
slope  greater  than  four  units  vertical  in  12  units 
horizontal  (4:12).  access  to  the  roof  shall  be 
provided  by  means  of  a  stairway,  an  alternating 
tread  stair  in  accordance  with  780  CMR  1014.6.6  or 
a  ladder  and  trap  door  The  ladder  shall  not  be  on 
the  exterior  of  the  building.  Where  the  roof  is  used 
as  a  roof  garden  or  for  other  habitable  purposes, 
sufficient  stairways  shall  extend  to  the  roof  to 
provide  the  necessity  exit  facilities  from  the  roof  as 
required  for  such  occupancy  .  Roof  trap  doors  shall 
be  constructed  to  comply  with  780  CMR  1510.2. 

1027.1.1    Optional   stairway   or   ladder:      In 

buildings  not  required  to  have  a  stairway, 
alternating  tread  stair  or  ladder  to  the  roof,  such 
devices,  if  provided,  shall  conform  to  the 
provisions  of  780  CMR  1027.0.  Ladders  placed 
on  the  exterior  of  the  building  shall  be  of  metal 
and,  if  exceeding  20  feet  (6096  mm)  in  height, 
shall  have  a  protective  cage  or  other  safety  device. 
The  siderails  of  exterior  ladders  shall  be  carried 
over  the  coping  or  parapet  to  serve  as  handrails 
Other  design  details  of  such  exterior  ladders  are 
subject  to  approval. 

1027.2  Roof  enclosures:  stairways  extending 
through  roofs  shall  be  enclosed  in  roof  structures  of 
fireresistance  rated  construction  which  conform  to 
the  requirements  of  780  CMR  1510.0. 


198 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


CHAPTER  11 

ACCESSIBILITY 

(780  CMR  11  is  Entirely  Unique  to  Massachusetts) 

780  CMR  1101.0  M.G.L.  c.  22,  §  13A  provides  that  Architectural  Access  Board,  Executive  Office  of 

all  public    buildings   shall   be   designed   to    be  Public  Safety. 

accessible  to,  functional  for  and  safe  for  the  use  by  In  accordance  with  M.G.L  c.   143,  §3  and 

physically  handicapped  persons,  in  conformance  780  CMR  106.1,  said  regulations  shall  be  enforced 

with    the    Massachusetts    Architectural    Access  by   the   municipal    building   code    enforcement 

Board's  Rules  and  Regulations  (521  CMR  1. 00)  official  or  state  inspector,  as  applicable 

listed  in  Appendix  A   and  promulgated  by  the 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  201 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


202  780  CMR  -  Sixth  Edition  2/27/97    (Effective  2/28/97) 


CHAPTER  12 


INTERIOR  ENVIRONMENT 


780  CMR  1201,0  GENERAL 

1201.1  Scope:  The  provisions  of  780  CMR  12  shall 

govern  the  means  of  light,  ventilation,  sound 
transmission  control  and  rat-proofing  required  in  all 
buildings. 

1201.2  Buildings  on  same  lot:  Where  more  than  one 
building  is  hereafter  placed  on  a  lot,  or  where  a 
building  is  placed  on  the  same  lot  with  existing 
buildings  and  the  several  buildings  are  treated  as  a 
single  structure  for  the  purposes  of  780  CMR  12, 
equivalent  uncovered  lot  area  or  other  adequate 
sources  of  light  and  ventilation  shall  be  provided  for 
all  occupied  buildings. 

780  CMR  1202.0  DEFINITIONS 
1202.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  12  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Attic:  The  space  between  the  ceiling  beams  of  the 
top  story  and  the  roof  rafters. 

Court:  An  open,  uncovered  and  unoccupied  space 
on  the  same  lot  as  a  building  where  such  space  is 
enclosed  wholly  or  partly  by  buildings,  walls  or 
other  enclosing  devices  (see  780  CMR  1212.0). 
Inner:  Any  court  enclosed  wholly  by  buildings, 

M'alls  or  other  enclosing  devices. 
Outer:  A  court  extending  to  and  opening  upon  a 

street,  public  alley  or  other  approved  open 

space  that  is  not  less  than  15  feet  (4572  mm) 

wide,  or  upon  a  required  yard. 

Court  height:  The  vertical  distance  from  the  lowest 
level  of  the  court  to  the  mean  height  of  the  top  of 
the  enclosing  walls. 

Court  width:  As  applied  to  an  inner  court,  means 
the  least  horizontal  dimension.  As  applied  to  an 
outer  court,  means  the  shortest  horizontal 
dimension  measured  in  a  direction  substantially 
parallel  with  the  principal  open  end  of  such  court. 

Habitable  space:  Space  in  a  structure  for  living, 
sleeping,  eating  or  cooking.  Bathrooms,  toilet 
compartments,  closets,  halls,  storage  or  utility 
spaces  and  similar  areas  are  not  considered 
habitable  spaces. 

Occupiable  space:  A  room  or  enclosed  space 
designed  for  human  occupancy  in  which 
individuals       congregate        for       amusement. 


educational  or  similar  purposes,  or  in  which 
occupants  are  engaged  at  labor;  and  which  is 
equipped  with  means  of  egress  and  light  and 
ventilation  facilities  meeting  the  requirements  of 
780  CMR. 

Vapor  retarder:  A  material  having  a  perm  rating  of 
1 .0  or  less,  such  as  foil,  plastic  sheeting,  or 
insulation  facing,  installed  to  retard  the  passage  of 
water  vapor  or  moisture  through  the  exterior 
envelope. 

Ventilation:  The  natural  or  mechanical  process  of 
supplying  conditioned  or  unconditioned  air  to,  or 
removing  such  air  from,  any  space. 

Yard:  An  unoccupied  open  space  other  than  a  court 
(see  780  CMR  1212.0  and  1213.0). 

780  CMR  1203.0  CONSTRUCTION 
DOCUMENTS 

1203.1  General:  Construction  documents  for  all 
buildings  and  structures  that  are  designed  for  human 
occupancy,  other  than  buildings  with  occupancies  in 
Use  Groups  1-1,  R-2  and  R-3,  shall  designate  the 
number  of  occupants  to  be  accommodated  in  the 
various  rooms  and  spaces;  where  means  of  artificial 
lighting  and  ventilation  are  required,  the  application 
shall  include  sufficient  details  and  description  of  the 
mechanical  system  to  be  installed  as  herein  required 
or  as  specified  in  the  mechanical  code  listed  in 
Appendix  A. 

780  CMR  1204.0  ROOM  DIMENSIONS 

1204.1  Ceiling  heights:  Habitable  (spaces)  rooms 
other  than  kitchens  shall  have  a  ceiling  height  of  not 
less  than  seven  feet  six  inches  (2286  mm). 
Hallways,  corridors,  bathrooms,  toilet  rooms, 
kitchens,  laundry  rooms  and  habitable  basements 
that  are  only  used  as  recreation  rooms  shall  have  a 
ceiling  height  of  not  less  than  seven  feet  (2134  mm) 
measured  to  the  lowest  projection  from  the  ceiling. 

Exception.  In  occupancies  in  Use  Group  R-3,  the 
maximum  projection  below  the  required  ceiling 
height  of  beams  and  girders  spaced  not  less  than 
four  feet  (1219  mm)  on  center  shall  be  six  inches 
(152  mm). 

1204.1.1  Use  Groups  A,  B,  E  and  M:  A  clear 
height  from  the  finished  floor  to  the  finished 
ceiling  or  lowest  projection  of  not  less  than  seven 
feet  six  inches  (2286  mm)  shall  be  provided  in  all 
exit  access  and  occupiable  rooms  of  structures  of 
Use  Groups  A,  B,  E  and  M. 


2/7/97    (Effective  2/27/97) 


780  CMR  -  Sixth  Edition 


203 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1204.1.2  Sloping  ceilings:  If  any  room  in  a 
building  has  a  sloping  ceiling,  the  prescribed 
ceiling  height  for  the  room  is  required  in  one-half 
the  area  thereof.  Any  portion  of  the  room 
measuring  less  than  five  feet  (1524  mm)  from  the 
finished  floor  to  the  finished  ceiling  shall  not  be 
included  in  any  computation  of  the  minimum  area 
thereof. 

1204.1.3  Furred  ceilings:  If  any  room  has  a 
furred  ceiling,  the  prescribed  ceiling  height  is 
required  in  two-thirds  of  the  area  thereof,  but  the 
height  of  the  furred  ceiling  shall  not  be  less  than 
seven  feet  (2134  mm). 

1204.2  Floor  area:  Habitable  rooms,  except 
kitchens,  shall  have  an  area  of  not  less  than  70 
square  feet  (6.51  m2). 

1204.3  Width:  A  habitable  room  other  than  a 
kitchen  shall  not  be  less  than  seven  feet  (2134  mm) 
in  any  dimension. 

780  CMR  1205.0  LIGHT  AND  VENTILATION 
REQUIRED 

1205.1  Light  required:  Every  room  or  space 
intended  for  human  occupancy  shall  be  provided 
with  natural  or  artificial  light. 

1205.1.1  Bathroom  and  toilet  room  lighting: 

Every  bathroom  and  toilet  room  shall  be  provided 
with  artificial  light.  The  illumination  shall  have 
an  average  intensity  of  three  footcandles  (32.29 
lux)  measured  at  a  level  of  30  inches  (762  mm) 
above  the  floor. 

1205.2  Ventilation  required:  Every  room  or  space 
intended  for  human  occupancy  shall  be  provided 
with  natural  or  mechanical  ventilation. 

1205.2. 1:  Every  bathroom  and  toilet  room  shall 
be  equipped  with  a  mechanical  exhaust  fan  and 
associated  ductwork  with  the  fan  exhausting,  as 
a  minimum,  at  SO  cfm  if  operated  intermittently 
or  20  cfm  if  continuously  operated  Such 
bathroom  exhaust  shall  vent  directly  to  the 
outside  and  no  exhaust  vent  shall  terminate  in 
attics  or  other  interior  portions  of  the  building. 

780  CMR  1206.0  NATURAL  LIGHT 
1206.1  General:  Should  natural  lighting  be  chosen 
as  a  lighting  option,  in  the  application  of  the 
provisions  of  780  CMR  12,  the  standard  of  natural 
light  for  all  habitable  and  ocatpiable  rooms,  unless 
otherwise  specifically  required  by  the  provisions  of 
780  CMR  4  for  special  occupancies,  shall  be  based 
on  250  footcandles  (2691  lux)  of  illumination  on  the 
vertical  plane  adjacent  to  the  exterior  of  the  light- 
transmitting  device  in  the  enclosure  wall  and  shall 
be  adequate  to  provide  an  average  illumination  of  six 
footcandles  (64  58  lux)  over  the  area  of  the  room  at 


a  height  of  30  inches  (762  mm)  above  the  floor 
level. 

1206.2  Minimum  glazing  area:  Every  room  or 
space  intended  for  human  occupancy  shall  have  an 
exterior  glazing  area  of  not  less  than  8%  of  the  floor 
area.  Natural  light  shall  be  provided  by  glazing 
areas  that  open  onto  courts  or  yards  which  comply 
with  the  requirements  of  780  CMR  1212.0,  or  by 
other  approved  means. 

1206.2.1  Adjoining  spaces:  Where  natural  light 
for  rooms  or  spaces  without  exterior  glazing  areas 
is  provided  through  an  adjoining  room,  the 
unobstructed  opening  to  the  adjoining  room  shall 
be  at  least  8%  of  the  floor  area  of  the  interior 
room  or  space,  but  not  less  than  25  square  feet 
(2.33  m2).  The  exterior  glazing  area  shall  be 
based  on  the  total  floor  area  being  served. 

1206.3  Stairways:  Interior  stairways  shall  be 
provided  with  an  exterior  glazing  area  of  not  less 
than  ten  square  feet  (0.93  m2)  on  every  floor  through 
which  the  stairway  passes. 

1206.4  Hallways:  Natural  light  shall  be  capable  of 
penetrating  the  full  length  of  the  hallway. 

780  CMR  1207.0  ARTDFICIAL  LIGHT 
1207.1    General.    Should   artificial   lighting   be 
chosen  as  a  lighting  option,  artificial  light  shall  be 
capable    of  providing   the    minimum    illumination 
specified  for  natural  light. 

780  CMR  1208.0  NATURAL 
VENTILATION 

1208.1  General:  Should  natural  ventilation  be 
chosen  as  a  ventilation  option,  natural  ventilation  of 
an  occupied  space  shall  be  through  windows,  doors, 
louvers  or  other  natural  openings  to  the  outdoor  air. 

Exception:  All  occupancies  shall  have 
mechanical  ventilation  in  bathrooms  and  toilet 
rooms  as  specified  in  780  CMR  1205.2.1  or 
otherwise  in  accordance  with  the  mechanical 
ventilation  requirements  of  the  BOCA  National 
Mechanical  Code  listed  in  Appendix  A. 

1208.2  Ventilation  area  required:  The  minimum 
openable  area  to  the  outdoors  shall  be  4%  of  the 
floor  area  being  ventilated. 

1208.2.1  Adjoining  spaces:  Where  rooms  and 
spaces  without  openings  to  the  outdoors  are 
ventilated  through  an  adjoining  room,  the 
unobstructed  opening  to  the  adjoining  room  shall 
be  at  least  8%  of  the  floor  area  of  the  interior 
room  or  space,  but  not  less  than  25  square  feet 
(2.33  m2).  The  ventilation  openings  to  the 
outdoors  shall  be  based  on  the  total  floor  area 
being  ventilated. 


204 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

INTERIOR  ENVIRONMENT 


1208.2.2  Openings  below  grade:  Openings 
below  grade  shall  be  acceptable  for  natural 
ventilation  provided  that  the  outside  horizontal 
clear  space  measured  perpendicular  to  the  opening 
is  1  'A  times  the  depth  below  the  average  adjoining 
grade. 

1208.3  Contaminants  exhausted:  Contaminants  in 
the  breathing  atmosphere  shall  be  exhausted  to  the 
outdoor  air  in  accordance  with  the  mechanical  code 
listed  in  Appendix  A. 

1208.4  Openings  onto  yards  or  courts:  Natural 
ventilation  shall  be  provided  by  openings  onto  yards 
or  courts  which  comply  with  the  requirements  of 
780  CMR  1212.0,  or  by  other  approved  means. 

780  CMR  1209.0  MECHANICAL 
VENTILATION 

1209.1  General:  Should  mechanical  ventialtion  be 
chosen  as  the  ventialtion  option,  mechanical 
ventilation  shall  conform  to  the  requirements  of  the 
mechanical  code  listed  in  Appendix  A. 

780  CMR  1210.0  VENTILATION  OF 
SPECIAL  SPACES 

1210.1  Roof  spaces:  Enclosed  attics  and  enclosed 
rafter  spaces  formed  where  ceilings  are  applied 
directly  to  the  underside  of  roof  rafters,  shall  have 
cross  ventilation  for  each  separate  space  by 
ventilation  openings  that  are  protected  against  the 
entrance  of  rain  and  snow.  The  openings  shall  be 
covered  with  corrosion-resistant  mesh  not  less  than 
'A  inch  (6  mm)  nor  more  than  '/:  inch  (13  mm)  in  any 
direction. 

1210.1.1  Ventilating  area:  The  minimum 
required  net  free  ventilating  area  shall  be  1/150  of 
the  area  of  the  space  ventilated,  except  that  the 
minimum  required  area  shall  be  reduced  to  1/300, 
provided  that:  a  vapor  retarder  having  a 
permeance  not  exceeding  one  perm  is  installed  on 
the  warm  side  of  the  ceiling;  or  at  least  50%,  and 
not  more  than  80%,  of  the  required  ventilating 
area  is  provided  by  ventilators  located  in  the 
upper  portion  of  the  space  to  be  ventilated  at  least 
three  feet  (914  mm)  above  eave  or  cornice  vents, 
with  the  balance  of  the  required  ventilation 
provided  by  eave  or  cornice  vents. 

1210.2  Crawl  spaces:  Crawl  space  areas,  other  than 
those  used  as  an  underfloor  plenum,  shall  be 
ventilated  by  an  approved  mechanical  means  or  by 
openings  in  exterior  foundation  walls.  Openings 
shall  be  located  as  close  to  corners  as  practicable  and 
shall  provide  cross  ventilation  on  at  least  two 
approximately  opposite  sides.  The  openings  shall  be 
covered  with  corrosion-resistant  mesh  not  less  than 
Vt  inch  (6  mm)  nor  more  than  lA  inch  (13  mm)  in  any 
direction. 


1210.2.1  Opening  size:  Openings  shall  have  a  net 
area  of  not  less  than  one  square  foot  (0.093  m2) 
for  each  150  square  feet  (13.95  nr)  of  foundation 
space.  Where  an  approved  vapor  retarder  is 
installed  over  the  ground  surface,  the  required  net 
area  of  openings  shall  be  reduced  to  0. 1  square 
foot  (0.093  nr)  for  each  150  square  feet  (13.95 
nr)  and  vents  shall  have  manually  operable 
louvers. 

1210.3     Alternative     mechanical     ventilation: 

Enclosed  attic,  rafter  and  crawl  spaces  which  are  not 
ventilated  as  herein  required  shall  be  equipped  with 
a  mechanical  ventilation  system  conforming  to  the 
requirements  of  the  mechanical  code  listed  in 
Appendix  A. 

780  CMR  1211.0  ACCESS  TO  CRAWL 
SPACES  AND  ATTICS 

1211.1  Access  to  crawl  spaces:  Access  shall  be 
provided  to  crawl  spaces  by  an  opening  not  less  than 
18  inches  (457  mm)  by  24  inches  (610  mm).  Such 
access,  if  common  to  conditioned  space,  shall  be 
weatherstripped  and  shall  close  tightly. 

1211.2  Access  to  attics:  An  opening  not  less  than  22 
inches  by  30  inches  (559  mm  by  762  mm)  with 
ready  access  thereto  shall  be  provided  to  any  attic 
area  having  a  clear  height  of  over  30  inches  (762 
mm).  Such  access,  if  adjoining  conditioned  space, 
shall  be  weatherstripped,  and  close  tightly.  All 
such  access  opening  framing  joints  shall  be 
caulked,  gasketed,  weatherstripped,  foamed  or 
othenvise  sealed  to  limit  infiltration/exfdtration 
Where  doors  or  other  openings  are  installed  in  attic 
draftstopping,  such  doors  shall  be  self-closing  and 
be  of  approved  materials  as  specified  in  780  CMR 
1211.0,  and  the  construction  shall  be  tightly  fitted 
around  all  pipes,  ducts  or  other  assemblies  piercing 
the  draftstopping. 

780  CMR  1212.0  COURTS  AND  YARDS 

1212.1  General:  All  courts  and  yards  required  to 
serve  rooms  for  natural  light  or  ventilation  purposes 
shall  comply  with  the  requirements  of  780  CMR 
1212.0. 

1212.2  Minimum  width:  Every  such  court  or  yard 
shall  have  a  minimum  width  of  three  inches  (76  mm) 
for  each  one  foot  (305  mm)  of  height  or  fraction 
thereof,  but  not  less  than  five  feet  (1524  mm)  for 
outer  courts  and  twice  these  values  for  inner  courts. 

1212.2.1  Irregular  court  or  yard  width:  In  the 

case  of  irregular  or  gore-shaped  courts  or  yards, 
the  average  width  shall  not  be  less  than  the 
required  width  of  a  court  in  accordance  with 
780  CMR  1212.2,  but  shall  not  be  less  than  five 
feet  (1524  mm)  at  any  point. 


2/7/97    (Effective  2/27/97) 


780  CMR  •  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1212.3  Area  of  court:  The  cross-sectional  area  of  a 
required  court  shall  not  be  less  than  114  times  the 
square  of  its  width;  nor  shall  the  length  of  any  court 
be  more  than  twice  its  width. 

1212.4  Access  to  court:  A  door  or  other  means  of 
access  shall  be  provided  at  the  bottom  of  every  court 
that  is  not  otherwise  provided  with  convenient 
access  for  purposes  of  cleaning. 

1212.5  Air  intakes:  Every  court  which  serves  one  or 
more  habitable  rooms  and  which  does  not  open  for 
its  full  height  on  one  or  more  sides  to  a  street  or 
legal  yard,  shall  be  connected  at  or  near  the  bottom 
with  a  street  or  yard  by  a  horizontal  intake  or 
passage  of  fireresistance  rated  construction.  Such 
intake  or  passage  shall  have  a  cross-sectional  area  of 
not  less  than  21  square  feet  (1.95  nr)  and  shall 
remain  fully  open  at  both  ends  and  unobstructed  for 
its  full  size  and  length,  except  that  grilles  of 
noncombustible  construction  are  permitted  at  the 
ends  of  the  intake. 

1212.5.1  Fireresistance  rating:  The  walls,  floors 
and  ceilings  of  such  intakes  or  passages  shall  have 
a  fireresistance  rating  of  not  less  than  two  hours  in 
buildings  of  Type  1,  2,  3  or  4  construction  and  not 
less  than  a  one-hour  fireresistance  rating  in 
buildings  of  Type  5  construction. 

1212.6  Court  walls:  Where,  in  the  opinion  of  the 
code  official,  windows  facing  on  courts  do  not 
receive  adequate  direct  light  by  reason  of  peculiar 
arrangement  or  orientation,  the  code  official  shall 
require  the  walls  to  be  constructed  of  light-colored 
masonry,  or  to  be  painted  and  maintained  a  light 
color  to  furnish  additional  reflected  light,  or  shall 
require  other  approved  means  of  providing 
additional  light. 

1212.7  Court  drainage:  The  bottom  of  every  court 
shall  be  properly  graded  and  drained  to  a  public 
sewer  or  other  approved  disposal  system  complying 
with  the  plumbing  code  listed  in  Appendix  A;  and 
shall  be  paved  with  concrete  or  other  non-absorbent 
material  where  required  by  the  code  official. 

780  CMR  1213.0  OBSTRUCTION  OF 
COURTS  AND  YARDS 

1213.1  Permissible  projections:  Every  required 
court  and  yard  shall  remain  unobstructed  for  its 
required    area   and    full    height,    except    for   the 
projections  permitted  in  780  CMR  1213.2  through 
1213.7. 

1213.2  Maximum  encroachment:  A  part  of  any 
building  or  structure  shall  not  extend  into  side 
courts,  inner  courts  or  yards  required  for  light  and 
ventilation  of  habitable  and  occupiable  rooms  by  the 
zoning  law  or  other  statutes  controlling  building 


construction.  The  encroachment  shall  not  exceed 
20%  of  the  legal  area  of  the  yard  or  court  which  is 
required  for  light  and  ventilation  purposes. 

1213.3  Accessories:  In  Use  Groups  R  and  I,  clothes 
poles,  arbors,  garden  trellises  and  other  such 
accessories  shall  not  be  prohibited  in  the  open 
spaces  at  ground  level. 

1213.4  Roof  eaves:  Roof  eaves  shall  not  project 
more  than  three  feet  (914  mm)  beyond  the  face  of 
the  wall. 

1213.5  Steps  and  architectural  features:  Steps, 
window  sills,  belt  courses  and  similar  architectural 
features,  as  well  as  rain  leaders  and  chimneys,  shall 
not  project  more  than  two  feet  (610  mm)  beyond  the 
face  of  the  wall. 

1213.6  Exterior    stairways    and    fire    escapes: 

Outside  stairways,  smokeproof  tower  balconies,  fire 
escapes  or  other  required  elements  of  a  means  of 
egress  shall  not  project  more  than  four  feet  (1219 
mm)  beyond  the  face  of  the  wall. 

1213.7  Motor  vehicle  parking:  Where  approved, 
required  court  and  yard  areas  for  automobile  parking 
spaces  or  private  garages  not  exceeding  one  story  in 
height  where  accessory  to  and  only  for  the  occupants 
of  a  Use  Group  R  occupancy  are  permitted,  provided 
that  required  windows  for  light  and  ventilation  are 
not  obstructed  thereby. 

780  CMR  1214.0  SOUND  TRANSMISSION 
CONTROL  IN  RESIDENTIAL  BUILDINGS 

1214.1  Scope:  780  CMR  1214.0  shall  apply  to  all 
common  interior  walls,  partitions  and  floor/ceiling 
assemblies  between  adjacent  dwelling  units  or 
between  dwelling  units  and  adjacent  public  areas 
such  as  halls,  corridors,  stairs  or  service  areas  in  all 
occupancies  in  Use  Group  R. 

1214.2  Air-borne  noise:  Walls,  partitions  and 
floor/ceiling  assemblies  separating  dwelling  units 
from  each  other  or  from  public  or  service  areas  shall 
have  a  sound  transmission  class  (STC)  of  not  less 
than  45  for  air-bome  noise  when  tested  in 
accordance  with  ASTM  E90  listed  in  Appendix  A. 
This  requirement  shall  not  apply  to  dwelling  unit 
entrance  doors;  however,  such  doors  shall  be  tight 
fitting  to  the  frame  and  sill. 

1214.3  Structure-borne  sound:  Floor/ceiling 
assemblies  between  dwelling  units  or  between  a 
dwelling  unit  and  a  public  or  service  area  within  the 
structure  shall  have  an  impact  insulation  class  (IIC) 
rating  of  not  less  than  45  when  tested  in  accordance 
with  ASTM  E492  listed  in  Appendix  A. 


206 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

INTERIOR  ENVIRONMENT 


780  CMR  1215.0  RATPROOFING 

1215.1  Ratproofing:  All  buildings  or  structures  and 
the  walls  enclosing  habitable  or  occripiable  rooms 
and  spaces  in  which  persons  live,  sleep  or  work,  or 
in  which  feed,  food  or  foodstuffs  are  stored, 
prepared,  processed,  served  or  sold,  shall  be 
constructed  in  accordance  with  the  provisions  of 
780  CMR  1215.0. 

1215.2  Grade  protection:  Buildings  not  provided 
with  a  continuous  foundation  shall  be  provided  with 
protection  against  rodents  at  grade  in  accordance 
with  either  780  CMR  1215.2.1  or  1215.2.2. 

1215.2.1  Apron:  Where  an  apron  is  provided,  the 
apron  shall  not  be  less  than  eight  inches  (203  mm) 
above,  nor  less  than  24  inches  (610  mm)  below 
grade.  In  all  cases  the  apron  shall  not  terminate 
below  the  lower  edge  of  the  siding  material.  The 
apron  shall  be  constructed  of  an  approved 
nondecayable,  water-resistant  and  ratproofing 
material  of  required  strength  and  shall  be  installed 
around  the  entire  perimeter  of  the  building. 
Where  constructed  of  masonry  or  concrete 
materials,  the  apron  shall  not  be  less  than  four 
inches  (102  mm)  in  thickness. 

1215.2.2  Grade  floors:  Where  continuous 
concrete  grade  floor  slabs  are  provided,  open 


spaces  shall  not  be  left  between  the  slab  and 
walls,  and  all  openings  in  the  slab  shall  be 
protected. 

1215.3  Opening  protection.  Openings  shall  be 
protected  in  accordance  with  780  CMR  1215.3.1 
through  1215.3.3. 

1215.3.1  Wall  openings:  Openings  in  the  wall  or 
apron  required  for  ventilation  or  other  purposes 
shall  be  guarded  with  corrosion-resistant  ratproof 
shields  of  not  less  than  nominal  0.034-inch 
perforated  steel  sheets,  or  No.  20  B&S  Gage 
aluminum  (0.032  inch)  or  nominal  0.064-inch 
expanded  steel  or  wire  mesh  screens,  with  not 
more  than  14-inch  (13  mm)  mesh  openings. 

1215.3.2  Slab  openings:  Access  openings  in 
grade  floor  slabs  shall  be  protected  with  concrete, 
masonry,  metal  or  other  corrosion-resistant 
noncombustible  cover  of  adequate  strength  to 
support  the  floor  loads. 

1215.3.3  Pipe  and  conduit  openings:  All  openings 
for  pipe,  conduit,  cable  and  similar  purposes  at  or 
near  grade  shall  have  snugly  fitted  collars  to 
eliminate  all  open  spaces. 


2/7/97    (Effective  2/27/97) 


780  CMR  -  Sixth  Edition 


207 


730  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 
NON-TEXT  PAGE 


208  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  13 


ENERGY  CONSERVATION 

(This  Chapter  is  entirely  unique  to  Massachusetts) 


USER  NOTES: 

Note  1 :  The  Energy  Conservation  Requirements  for  New  Construction,  Low  Rise  Residential  Buildings 
(all  residential  uses  up  to  three  stories  in  height)  have  been  voted  "changed"  largely  to  reflect  the 
requirements  of  the  CABO  Model  Energy  Code,  1995  Edition  (MEC95)  Such  changes  will  become 
effective  on  March  1,  1998.  and  until  such  date,  the  applicable  Energy  Conservation  Requirements  of  the 
Fifth  Edition  of  the  Massachusetts  State  Building  Code  are  brought  forward  into  the  Sixth  Edition-  The 
reader  should  review  the  Massachusetts  Register  during  the  time  frame  of  August.  1997  through  March. 
1 998  for  further  information. 

The  requirements  driving  NFRC  listing/labeling  are  ties  to  the  BBRS  adoption  of  the  Council  of  American 
Building  Officials  1995  Model  Energy  Code  (CABO  MEC  95)  and  the  NFRC  listing/labeling  requirements 
set  forth  in  CABO  95  as  found  in  MEC  95,  Chapter  1,  Section  102.3  and  within  Tables  102.3a  and  103.3b  - 
such  explicit  requirements  will  apply  in  Massachusetts  as  of  January  1.  1999. 

Note  2:  Certain  Energy  Conservation  requirements  affecting  existing  building  "Replacement  Window" 
requirements  for  existing  low-rise  residential  buildings  have  been  voted  "changed"    Such  changes  include: 

1 .  Such  "replacement  windows"  to  be  NFRC  Certified  (becomes  effective  on  January  1 ,  1 999). 

2.  Such  NFRC  Certified  "Replacement  Windows"  have  a  maximum  allowed 

U-value  of  0.44 (Becomes  effective  January  1.  1999) 

h  -  ftz-°F 

Also  refer  to  "Notices  of  Public  Interest"  that  may  be  published  from  time  to  time  in  the  Massachusetts 
Register  during  the  months  of  August,  1997  through  January  1999. 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


780  CMR  -  Sixth  Edition 


CHAPTER  13 


ENERGY  CONSERVATION 

(This  Chapter  is  entirely  unique  to  Massachusetts) 


780  CMR  1300.0  GENERAL 

1300.1  Scope:  780  CMR  13  sets  forth  requirements 
for  the  effective  use  of  energy  in  structures. 

780  OVER  1301.0  ADMINISTRATIVE 

1301.1  Compliance:  Buildings  shall  be  deemed  to 
be  in  compliance  with  780  CMR  13  when  built  to 
the  provisions  of  the  following: 

1  component  design  (780  CMR  1308.0  through 
1314.0);  or 

2.  building  design  by  systems  analysis  (780  CMR 
1315.0);  or 

3.  buildings  utilizing  nondepletable  energy 
sources  (780  CMR  1316.0). 

1301.1.1  Heating,  Pumping,  Process  Piping 
and  Refrigeration  Systems:  Heating,  pumping, 
process  piping  and  refrigeration  systems  shall  be 
installed  by  contractors  and  personnel 
appropriately  licensed  in  the  Commonwealth  of 
Massachusetts  (Installing  Contractor)  Engineered 
designs  and  specifications  prepared  by  Registered 
Professional  Engineers  shall  identify  systems 
requiring  compliance  with  appropriate  sections  of 
M.G.L.  c.  146  and  528  CMR.  Shop  drawings  and 
design  layout  prepared  by  licensed  installing 
contractors  shall  note  the  name(s),  license 
number(s)  and  license  expiration  date(s)  of  the 
contractor(s)  installing  the  heating,  pumping, 
process  piping  and  refrigeration  systems.  (See 
Installing  Contractor  Definition  780  CMR  202.0). 

1301.2  Other  regulations:  780  CMR  13  is  not 

intended  to  abridge  any  safety  or  health  provisions 
required  under  any  other  applicable  codes  or  or- 
dinances. 

1301.3  Existing  buildings:  Nothing  in  780  CMR  13 
shall  require  the  removal,  alteration,  or 
abandonment,  or  prevent  the  continuance  of  the  use 
and  occupancy  of,  a  lawfully  existing  building, 
unless  provided  otherwise  specifically  by  780  CMR 
13. 

1301.4  Exempt  buildings:  The  following  buildings 
are  exempt  from  the  provisions  of  780  CMR  13, 
with  the  exception  of  780  CMR  1313.0  dealing  with 
lighting  requirements: 

'  1.  Buildings  and  structures  or  portions  thereof 
whose  peak  design  rate  of  energy  usage  is  less 
than  one  watt  per  square  foot  or  three  and  four 
tenths  (3.4)  Btu/h  per  square  foot  of  floor  area  for 
all  purposes; 
2.    Buildings  which  are  neither  heated  nor  cooled; 


3.  Greenhouses  that  are  free-standing,  or  attached 
to  a  building  and  separated  by  a  wall  having  the 
same  thermal  value  as  an  exterior  wall,  and 
provided  with  a  separate  temperature  control 
system; 

4.  Buildings  with  less  than  100  square  feet  of 
gross  floor  area. 

780  CMR  1302.0  EXISTING  BUILDINGS 

1302.1  Additions  to  existing  buildings:  Additions 
to  existing  buildings  or  structures  shall  be  made 
without  making  the  entire  building  or  structure 
comply.  The  new  construction  shall  conform  to  the 
provisions  of  780  CMR  13  as  they  relate  to  the 
addition  only. 

1302.2  Alterations   to   existing    buildings:    See 

780  CMR  34. 

780  CMR  1303.0  PLANS  AND 
SPECIFICATIONS 

1303.1  Scope:  780  CMR  1303.0  applies  to  all 
buildings 

1303.2  General:  Plans,  specifications  and  necessary 
computations  shall  be  submitted  to  indicate 
conformance  with  780  CMR  1303.0  and  other 
applicable  sections  of  780  CMR. 

1303.3  Details:  The  data  submitted  shall  show  all 
pertinent  information  and  features  to  be  incorporated 
into  the  building,  including  but  not  limited  to:  the 
exterior  envelope  component  materials;  the  R  values 
of  the  respective  elements;  the  U  values  of  the 
overall  assembly;  calculations  of  overall  Uo  of  the 
walls,  roof/ceiling,  and  floors;  the  size  and  type  of 
apparatus  and  equipment:  controls:  lighting 
requirements;  and  other  pertinent  data  to  indicate 
conformance  to  780  CMR  13  Where  required  by  the 
Board  of  Building  Regulations  and  Standards  or  the 
local  enforcement  official,  such  data  shall  be 
submitted  on  forms  specified. 

1303.4  Calculation  procedures.  Calculation 
procedures  shall  be  in  accordance  with  data  in  the 
ASHRAE  Handbook,  1993  Fundamentals  Volume 
or  as  otherwise  specified  in  780  CMR  13. 

780  CMR  1304.0  MATERIALS  AND 
EQUIPMENT 

1304.1  Identification:  Where  practicable,  all 
materials  and  equipment  referenced  in  780  CMR 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


209 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1303.0  shall  be  marked  in  order  to  show  compliance 
with  780  CMR  13 

1304.2  Maintenance  information:  Service  systems 
which  require  preventive  maintenance  to  maintain 
efficient  operation  shall  be  furnished  with  complete 
necessary  maintenance  information.  Required 
routine  maintenance  actions,  as  specified  by  the 
manufacturer,  shall  be  stated  clearly  and 
incorporated  on  a  readily  accessible  label  on  the 
equipment.  Such  label  may  be  limited  to  identifying, 
by  title  or  publication  number,  the  operation  and 
maintenance  manual  for  that  particular  model  and 
type  of  product. 

780  CMR  1305.0  DESIGN  CONDITIONS 

1305.1  Scope:  780  CMR  1305.0  applies  to  all 
buildings 

1305.2  General:  The  criteria  of  780  CMR  1305.0 
establishes  the  minimum  requirements  for  the 
thermal  design  of  the  exterior  envelope  of  buildings 
and  for  HVAC  systems  and  equipment. 

1305.3  Thermal  performance  A  building  that  is 
designed  to  be  both  heated  and  cooled  shall  meet  the 
more  stringent  of  the  heating  or  cooling 
requirements  as  provided  in  780  CMR  13  when 
requirements  differ 

1305.4  Design  parameters:  The  design  parameters 
listed  in  Tables  1305. 1  and  1305.2  shall  be  used  for 
calculations  required  under  780  CMR  13 

1305.4.1  Indoor  design  temperature  Indoor 
design  temperature  shall  be  72°F  for  heating  and 
78  °F  for  cooling. 

1305.4.2  Design  humidity:  Indoor  design  relative 
humidity  for  heating  shall  not  exceed  30%  For 
cooling,  the  actual  design  relative  humidity  within 
the  comfort  envelope  as  defined  in  ASHRAE 
Standard  55-92  listed  in  Appendix  A  shall  be 
selected  for  minimum  total  HVAC  system  energy 
use  in  accordance  with  accepted  practice. 

1305.5  Ventilation:  Ventilation  air  shall  conform  to 
the  requirements  specified  in  the  mechanical  code 
listed  in  Appendix  A. 


Table  1305.1 

DESIGN  TEMPERATURES 

HEATING  DEGREE  DAYS  BASE  65 

HDD65 

Outside  Ambient 


Heating 

Cooling 

Cooling 

Heating 

Degrees 

Degrees 

Degrees 

Deeree 

Location 

(°F) 

Drv  Bulb 

Wet  Bulb 

Days 

Winter 

Summer 

Summer 

Base  65 

Boston 

9 

88 

74 

5634 

Clinton 

2 

87 

73 

6517 

Fall  River 

9 

84 

73 

5774 

Fraimngham 

6 

86 

73 

6144 

Gloucester 

5 

86 

74 

Greenfield 

-2 

85 

73 

Lawrence 

0 

87 

74 

6195 

Lowell 

1 

88 

74 

6056 

New  Bedford 

9 

82 

73 

5395 

Pittsfield 

-3 

84 

72 

7578 

Springfield 

0 

87 

73 

5844 

Taunton 

9 

86 

74 

6184 

Worcester 

4 

84 

72 

6989 

Table  1305.21 

HEATING  DEGREE  DAYS  BASE  50 

HDD™ 


Location 

Heating  Degree  Days 
Base  50 

Amherst 

3171 

Birch  Hill  Dam 

3733 

Blue  Hill 

2926 

Boston 

2383 

Chatham 

2377 

Chestnut  Hill 

2658 

Clinton 

3107 

East  Wareham 

2780 

Edgartown 

2499 

Fitchburg 

3156 

Fraimngham 

2855 

Haverhill 

2734 

Hyannis 

2478 

Knightville  Dam 

3693 

Lawrence 

2867 

Middleton 

2676 

Nantucket 

2347 

New  Bedford 

2107 

Plymouth 

2619 

Rochester 

2807 

Rockport 

2726 

Springfield 

2706 

Stockbndge 

3551 

Taunton 

2800 

Tulley  Lake 

3786 

Worcester 

3364 

I .    This  Table  is  only  utilized  to  support  the  ACP  Tables. 
Tables  1314.4.1,  1314.4.2  and  1314.4.3 


210 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


780  CMR  1306.0  BUILDING  INSULATION 
SPECIFICATIONS 

1306.1  Scope:  780  CMR  1306.0  applies  to  all 
buildings. 

1306.2  General:  Insulating  materials  must  conform 
to  the  Federal  Specifications  (F.S.),  the  American 
Society  for  Testing  Materials  (ASTM)  Test 
Standards,  or  the  Code  of  Federal  Regulations  (CFR) 
as  listed  in  Table  1306. 

Table  1306 
INSULA  TTON  MATERIALS  STANDARDS 


Material 

Standard 

Mineral  Fiber 

blanket/batt 

ASTMC665-91 

loose-fill 

ASTM  C-764-94 

Mineral  Cellular 

perlite 

ASTM  C549-81/R 1986 

vermiculite 

ASTM  C516-8G7R 1990 

perlite  board 

ASTMC728-91 

cellular  glass  block 

ASTMC552-91 

Organic  Fiber 

cellulose  fiber  board 

ASTM  C208-94 

cellulose  loose  fill 

16  CFR  Pan  1209 

Organic  Cellular 

polvstyrene  board 

ASTM  C578-92 

urethane  board 

ASTMC591-85 

flexible  unicellular 

ASTM  C534-94 

polvurethane  or  polyiso- 

cvanurate  with  foil  face 

F.S.HH-1-1972-1 

polvurethane  or  polyiso- 

cvanurate  with  felt  face 

FS.HH-1-1 972-2 

1306.3  Moisture  control:  The  design  of  buildings 
for  energy  conservation  shall  not  create  conditions 
of  accelerated  deterioration  from  moisture 
condensation  (additionally,  see  780  CMR  12  for 
attic  and  under-floor  space  ventilation). 

1306.4  Installation: 

1306.4.1  Recessed  light  fixtures:  Only  IC  labeled 
recessed  lights  allowing  direct  contact  with 
insulating  materials  shall  be  used  in  areas 
separating  conditioned  and  unconditioned  spaces. 

1306.4.2  High  heat  sources:  A  clearance  of  three 
inches  from  any  high  heat  source,  including  but 
not  limited  to  chimneys,  flues  and  vents,  shall  be 
maintained  for  combustible  insulating  materials. 

1306.4.3  Urea  formaldehyde  foams:  Urea 
formaldehyde  foams  shall  not  be  used  in  any 
building. 

1306.4.4  Walls:  Batt/blanket  insulation  with  a 
vapor  barrier  attached  shall  be  stapled  to  the 
winter  warm  sides  or  faces  of  wall  studs  at 
intervals  of  eight  inches  on  center  vertically. 
Where  batt/blanket  insulation  is  of  a  "friction  fit" 
design  and  a  poly  vapor  barrier  is  employed,  the 
vapor  barrier  shall  be  affixed  to  the  interior  face 
of  the  wall  studs  in  accordance  with  the  insulation 
manufacturer's  recommendations. 


1306.4.5  Cavities:  All  cavities  between  rough 
framing  and  door  and  window  heads,  jambs,  and 
sills  shall  be  filled  with  insulation  and  covered 
with  a  vapor  barrier  meeting  the  criteria  of 
780  CMR  1307. 

1306.4.6: 

1306.4.6.1  Low  rise  residential  buildings/ 
perimeter  insulation:  Perimeter  insulation  for 
slab  on  grade  construction  in  buildings  of  Use 
Group  R  of  three  stories  or  less  shall  be  in- 
stalled so  that  the  concrete  to  concrete  contact 
between  the  foundation  wall  and  the  floor  slab 
is  broken  and  the  insulation  extends  downward 
the  thickness  of  the  slab  and  then  extends  four 
feet  vertically  down  from,  or  four  feet 
horizontally  beneath,  the  floor  slab.  Perimeter 
insulation  may  be  installed  in  alternative 
locations  if  installed  in  a  manner  to  thermally 
isolate  the  floor  from  the  exterior. 

1306.4.6.2  Commercial  and  high  rise 
residential  buildings/perimeter  insulation: 
Perimeter  Insulation  for  slab  on  grade  con- 
struction in  buildings  of  Use  Group  R  of  more 
than  three  stories  or  in  buildings  of  other  Use 
Groups  shall  be  installed  in  a  manner 
consistent  with  that  specified  in  780  CMR 
1306.4.6.1,  except  that  alternate  locations  and 
dimensions  may  be  permitted  by  the  provisions 
of  780  CMR  1314. 

1306.4.7  Foundation  wall  insulation: 

1 .  For  interior  foundation  wall  insulation,  the 
entire  gross  wall  area  extending  from  the  top  of 
the  band  joist  to  the  floor  shall  be  insulated  in 
accordance  with  Table  1309.1. 

2.  For  exterior  foundation  wall  insulation,  the 
insulation  shall  extend  from  the  top  of  the 
foundation  to  a  minimum  of  eight  feet  below 
grade  or  to  foundation  footing,  whichever  is 
less.  All  exterior  basement  and  foundation  wall 
insulation  shall  be  suitably  protected  so  as  to 
prevent  deterioration  caused  by  ultra-violet 
light  or  insect  damage  in  accordance  with 
manufacturer's  instructions. 

1306.5  Fire  safety  relating  to  insulation:     See 

780  CMR  722  and  2603. 

1306.6:  Labeling 

1306.6.1  Batt  and  blanket  and  rigid  board: 

Insulation  of  this  type  shall  be  labeled  according 
to  type,  manufacturer  or  distributor,  R  value  of  the 
insulation  at  the  labeled  thickness,  and  material 
specification  as  listed  in  Table  1306. 

1306.6.2  Blown,  poured,  or  sprayed  on  types 

Insulation  of  these  types  shall  be  labeled 
according  to  type,  manufacturer,  recommended 
insulation  density,  thickness  and  R  value,  fire 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


safety  requirements  and  material  specifications  as 
listed  in  Table  1306. 

780  CMR  1307.0  AIR  INFILTRATION 
AND  MOISTURE  CONTROL 

1307.1:  780  CMR  1307.0  applies  to  all  buildings. 

1307.2  Vapor  barriers:  A  vapor  barrier  of  one  point 
zero  (1.0)  perm  or  less  shall  be  installed  on  the 
winter  warm  side  of  walls,  ceilings  and  floors 
enclosing  a  conditioned  space. 

Exception:  Vapor  barriers  may  be  eliminated 
with  adequate  ventilation  as  defined  in  780  CMR 
12  (See  780  CMR  1210). 

1307.3  Taping:  All  tears  in  the  vapor  barrier  shall 
be  taped  or  sealed. 

3107.4  Air  leakage  for  all  buildings: 

1.  The  requirements  of  this  section  shall  apply 
to  those  locations  separating  outdoor  ambient 
conditions  from  interior  spaces  that  are  heated  or 
mechanically  cooled  and  are  not  applicable  to  the 
separation  of  interior  conditioned  spaces  from 
each  other. 

2.  The  following  openings  in  the  exterior 
building  envelope  shall  be  caulked,  gasketed, 
weatherstripped,  foamed  or  otherwise  sealed  to 
limit  infiltration: 

a.  Around  window  and  door  frames,  between 
the  unit  and  the  rough  framing; 

b.  Between  all  exterior  wall  soleplates  and  the 
structural  floor,  using  two  rows  of  caulking  or 
alternate  approved  procedure; 

c.  Over  all  framing  joints  where  floors  over 
conditioned  spaces  intersect  exterior  walls, 
using  a  water  vapor  permeable  infiltration 
barrier  or  alternate  approved  technique; 

d.  Around  openings  for  plumbing,  electricity, 
telephone  and  gas  lines  in  walls,  ceilings  and 
floors; 

e.  At  openings  in  the  ceiling,  such  as  where 
the  ceiling  panels  meet  interior  and  exterior 
walls,  at  exposed  beam  and  masonry  fireplaces; 

f.  At  the  mudsill,  in  addition  to  normal  sill 
sealer  in  conditioned  basements  and 
conditioned  crawlspaces;  and, 

g.  At  all  other  openings  in  the  exterior 
building  envelope. 

h.  See  additional  requirements  for  attic  and 
crawl  space  access,  780  CMR  1211. 

3.  Electrical  outlet  plate  gaskets  shall  be 
installed  on  all  receptacle,  switch,  or  other 
electrical  boxes  in  walls  separating  conditioned 
from  unconditioned  space. 

4.  Heating  ducts  shall  be  sealed  at  all  joints  and 
corners  as  specified  in  1310.9. 

5.  Interior  openings  between  conditioned  and 
non-conditioned    space    shall    be    sealed    using 


sealant,  closed-cell  gasket  material,  permanent 
tape,  or  another  method  that  limits  infiltration. 

1307.5  Air  leakage  requirements  for  fenestration 
and  doors: 

1307.5.1  Windows  shall  have  an  air  leakage  rate 
of  0.34  cfm  per  foot  of  operable  sash  crack  in 
accordance  with  the  following  standards  as 
applicable: 

ANSI/AANA      101-88,      Aluminum     Prime 
Windows, 

ASTM    D    4099-89,        Specifications    for 
Polyvinylchloride  (PCV)  Prime  Windows, 
ANSI/NWWDA  I.S.  2-87,  Wood  Window 
Units  (Improved  PerformanceRating  Only). 
AAMA  101V-1986,  Polyvinyl  Chloride  (PVC) 
Prime  Windows  and  Sliding  Glass  Doors, 
AAMA    1701.2-1985   Prime   Windows   and 
Sliding  Glass  Doors/Manufactured  Housing 

1307.5.2  Sliding  Doors  shall  meet  one  of  the 
following  standards  for  air  leakage: 

ANSI/AANA  101-88,  Aluminum  Sliding  Glass 

Doors,  or 

ANSI/NWWDA     I.S.  3-88,  Wood  Sliding 

Patio  Doors. 

AAMA  101V-1986,  Polyvinyl  Chloride  (PVC) 

Prime  Windows  and  Sliding  Glass  Doors, 

AAMA   1701.2-1985,  Prime  Windows  and 

Sliding  Glass  Doors/Manufactured  Housing 

1307.5.3  Commercial  entrance  swinging  or 
revolving  doors  shall  limit  air  leakage  to  a  rate  not 
to  exceed  1.2  cfm  per  square  foot  of  door  area,  at 
standard  test  conditions. 

1307.5.4  Residential  swinging  doors  shall  limit 
air  leakage  to  a  rate  not  to  exceed  0.5  cfm  per 
square  foot  of  door  area,  at  standard  test 
conditions. 

1307.5.5  Spaces  that  have  regular  high  volume 
traffic  through  the  building  envelopes  such  as 
retail  store  entrances  and  loading  bays,  shall  be 
designed  accounting  for  the  steady  state  air 
transfer  between  conditioned  and  unconditioned 
or  exterior  space. 

780  CMR  1308.0  COMPONENT  DESIGN 

1308.1  Scope:  All  low  rise  residential  buildings  that 
are  heated  or  mechanically  cooled  shall  be 
constructed  so  as  to  provide  the  required  thermal 
performance  of  the  various  components  listed  in 
780  CMR  1308.0  through  13 12.0,  and  to  provide  the 
lighting  switching  requirements  of  780  CMR 
1313.2.2.1. 

All  commercial  and  high  rise  residential  buildings 
that  are  mechanically  heated  and  cooled  shall  be 
constructed  so  as  to  provide  the  required  thermal  and 
lighting     system     performance     of    the    various 


212 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 

ENERGY  CONSERVATION 


components  listed  in  780  CMR  1308.0,  and  1310.0 
through  1314.0. 

1308.2  Thermal  Performance:  Information  on 
thermal  properties,  performance  of  building 
envelope  sections  and  components,  and  heat  transfer 
shall  be  obtained  from  laboratory  or  field  test 
measurements,  or  when  information  is  not  available 
from  these  sources,  then  such  information  may  be 
obtained  from  the  ASHRAE  Handbook,  1993 
Fundamentals. 

When  laboratory  or  field  test  measurements  are 
used,  they  shall  be  conducted  in  accordance  with 
ASTM  standards: 

1.  C-177-85/R1993,  Standard  Test  Method  for 
Steady-State  Thermal  Transmission  Properties  by 
Means  of  the  Guarded  Hot  Plate, 

2.  C-5 1 8-9 1 ,  Steady-State  Thermal  Transmission 
Properties  by  Means  of  the  Heat  Flow  Meter, 

3.  C-236-89/R1993,  Standard  Test  Method  for 
Steady-State  Thermal  Performance  of  Building 
Assemblies  by  Means  of  a  Guarded  Hot  Box,  or 

4.  C-976-90,  Thermal  Performance  of  Building 
Assemblies  by  Means  of  a  Calibrated  Hot  Box. 

To  determine  thermal  conductance  through  window 
assemblies  the  following  ASTM  or  American 
Architectural  Manufacturers  Association  (AAMA) 
standards  shall  be  used. 

1 .  AAMA  1503.1-1988,  Test  Method  of  Thermal 
Transmittance  of  Windows,  Doors  and  Glazed 
Wall  Sections, 

2.  ASTM  C-236-89/R1993,  Standard  Test 
Method  for  Steady-State  Thermal  Performance  of 
Building  Assemblies  by  Means  of  Guarded  Hot 
Box,  or 

3.  ASTM  C-976-90,  Thermal  Performance  of 
Building  Assemblies  by  .Means  of  a  Calibrated 
Hot  Box. 

When  using  any  of  the  three  test  procedures  above, 
a  15  mile  per  hour  wind  shall  be  applied 
perpendicular  to  the  glazing. 

1308.3  Gross  wall  area:  For  the  purposes  of 
780  CMR  13,  the  gross  area  of  exterior  walls 
consists  of  all  opaque  wall  areas,  including 
foundation  walls,  areas  between  floor  spandrels, 
peripheral  edges  of  floors,  window  areas  including 
sash,  and  door  areas,  where  such  surfaces  enclose  a 
heated  or  mechanically  cooled  space  including 
interstitial  areas  between  two  such  spaces,  but 
excluding  vents,  grills  and  pipes 

1308.4  Roof  assembly:  For  the  purpose  of 
780  CMR  13,  a  roof  assembly  shall  be  considered  as 


all  components  of  the  roof/ceiling  envelope  through 
which  heat  flows,  thereby  creating  a  building 
transmission  heat  loss  or  gain,  where  such  assembly 
encloses  a  heated  or  mechanically  cooled  space. 

1308.4.1  Gross  roof  area:  The  gross  area  of  a 
roof  assembly  consists  of  the  total  interior  surface 
of  such  assembly,  including  skylights,  exposed  to 
the  heated  or  mechanically  cooled  space. 

1308.4.2  Ceiling  plenums:  Where  air  ceiling 
plenums  are  employed,  the  roof/ceiling  assembly 
shall: 

1.  for  thermal  transmittance  purposes  not 
include  the  ceiling  proper  nor  the  plenum  space 
as  part  of  the  assembly;  and 

2.  for  gross  area  purposes  be  based  upon  the 
interior  face  of  the  upper  plenum  surface. 

1308.5  Swimming  pools  All  pool  enclosures  shall 
be  designed  in  accordance  with  the  1993  edition  of 
the  ASHRAE  Applications  Handbook. 

Such  pool   enclosures  shall  have  a  maximum 
overall  (roof/gables/sidewalls)  U  value  of  0.25. 

780  CMR  1309.0  EXTERIOR  ENVELOPE 

REQUIREMENTS  FOR  LOW  RISE 

RESDDENTIAL  BUILDINGS 

1309.1  Criteria  for  low  rise  residential  buildings: 

The  following  requirements  shall  apply  to  all 
buildings  and  structures  or  portions  thereof  in  use 
groups  R-l,  R-2,  R-3,  and  R-4  (hotels,  multi-family, 
and  one-  and  two-family)  that  are  heated  or 
mechanically  cooled  and  not  more  than  three  stories 
high. 

1.  All  buildings  in  these  use  groups  shall 
conform  to  the  thermal  transmittance  values  in 
Table  1309.1  or  shall  be  designed  to  satisfy  the 
requirements  of  780  CMR  1309.3  or  shall  be 
designed  to  satisfy  the  requirements  of  780  CMR 
1315. 

2.  An  overall  Uo  value  of  0.167  for  structures 
heated  by  oil,  gas  or  heat  pumps,  or  an  overall  Uo 
of  0.105  for  structures  heated  by  electric 
resistance  may  be  used  for  the  combination  of 
walls,  doors  and  windows  containing  heated  space 
in  lieu  of  the  separate  U  values  listed  for  walls, 
doors  and  windows.  The  overall  Uo  of  0.167  or 
0.105  shall  be  used  when  the  windows  exceed 
15%  of  the  gross  exterior  wall  area. 

3.  For  purposes  of  780  CMR  1309.0  only, 
framing  members  shall  not  be  included  in  the 
calculations  of  R  and  U  values. 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


213 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1309.1 

MAXIMUM  U  VALUES  AND  MINIMUM 

R  VALUES  OF  WALLS,  ROOF/CEDLING, 

AND  FLOORS  FOR  RES'DENTIAL 

BUILDINGS  OF  780  CMR  1309.1 


Element 

Description 

U 
Value 

Total 
R  Value 

Notes 

Walls 

All  wall  construction 
containing  heated  or 
mechanically  cooled 
space 

0.08 

12.5 

1 

Electric  resistance 
heatine 

0.05 

20.0 

1 

Foundation 
Walls 
Including 
Band  Joist 

Containing  heated  or 
mechanically  cooled 
space 

0.08 

12.5 

Containing  unhealed 
space 

0.08 

12.5 

4 

Roof/Ceiling 
Assembly 

All  roof  construction 
containing  heated  or 
mechanically  cooled 
space 

0.033 

30.0 

Windows 

All  construction 
enclosing  heated  or 
mechanically  cooled 
space 

0.65 

1.54 

2 

Electric  resistance 
heating 

0.40 

2.50 

6,7 

Doors 

All  construction 
enclosing  heated  or 
mechanically  cooled 
space 

0.40 

2.50 

Floors 

Floor  sections  over 
areas  exposed  to 
outside  air  or 
unheated  space 

0.05 

20.0 

3 

Slab  on  grade 
beneath  conditioned 

space 

10.0 

5 

Note  1 :  These  values  may  be  used  when  the  doors  and 
windows  do  not  exceed  15%  of  the  gross  exterior  wall 
area.  When  doors  and  windows  exceed  15%  of  the  gross 
wall  area,  see  780  CMR  1309.1,  item  2. 

Note  2:  Double  glazed  primary  windows  or  single 
glaze  primary  windows  with  storm  windows  will  satisfy 
the  required  U  value  of  0.65. 

Note  3:  Insulation  may  be  omitted  from  floors  over 
unheated  areas  when  foundation  walls  are  provided  with 
a  U  value  of  0.08. 

Note  4:  The  U  value  requirement  of  0.08  for 
foundation  walls  may  be  omitted  when  floors  over 
unheated  spaces  are  provided  with  a  U  value  of  0.05. 

Note  5:  R  value  for  perimeter  insulation  (see 
780  CMR  1306.4.6). 

Note  6:  When  doors  and  windows  do  not  exceed  15% 
of  the  gross  exterior  wall  area,  this  value  may  be  used. 
When  doors  and  windows  do  not  exceed  10%  of  the  gross 
exterior  wall  area,  windows  having  a  U  value  of  0.65  (R 
value  of  1.54)  may  be  used.  When  windows  and  doors 
exceed  15%  of  the  gross  exterior  wall  area,  see  780  CMR 
1309.1,  item  2. 

Note  7:  Double  glazed  primary  windows  with  storm 
windows  or  most  triple  glazed  primary  windows  or 
double  glazed  low  emissivity  primary  windows  will 
satisfy  the  required  U  value  of  0.40. 


1309.2  Calculation  of  Uo:  Separate  overall  thermal 
transmittance  values  shall  be  calculated  for  wall 
assemblies,  roof/ceiling  assemblies,  and  floors. 
Equation  1  is  provided  as  an  example  of  the  Uo 
calculation  for  walls. 


Equation  1: 
Overall  wall  Uo 


Uw  Aw  +  UgAg  =  Ud  Ad 


Where: 

Uo  =  average  or  combined  transmittance  of  the 

gross  exterior  wall;  (Btu/hr-ft"-°F). 
Aw  =  gross  exterior  wall  area,  (ft  ). 
Uw  =  thermal  transmittance  of  the  components  of 

the  opaque  wall;  (Btu/hr-ft"-°F). 
Aw  =  opaque  wall  area;  (ft  ). 
Ug  =  thermal    transmittance   of  the   windows; 

(Btu/hr-ft2-°F). 
Ag  =  window  area;  (ft  ). 
Ud  =  thermal  transmittance  of  the  door  or  similar 

opening;  (Btu/hr-ft2-°F). 
Ad  =  door  area;  (ft2). 

NOTE:  Where  Ug  is  determined  by  test,  it  shall  be 
calculated  using  the  procedure  contained  in 
780  CMR  1314.3.2.2  including  calculation  for 
framing,  sash,  edge  effects,  and  all  other  factors 
pertinent  to  the  complete  window  assembly. 

1309.3  Alternates:  The  stated  Uo  (or  U)  value  of 
any  one  assembly,  such  as  roof/ceiling,  wall,  or 
floor,  may  be  increased  and  the  Uo  (or  U)  value  for 
other  components  decreased  provided  that  the 
overall  heat  gain  or  loss  for  the  entire  building 
envelope  does  not  exceed  the  total  resulting  from 
conformance  to  the  stated  Uo  (or  U)  values. 

780  CMR  1310.0  HEATING,  VENTILATING 

AND  AIR  CONDITIONING 

(HVAQ  SYSTEMS 

1310.1  Scope:  780  CMR  1310.0  covers  the 
determination  of  heating  and  cooling  loads,  systems 
performance,  and  control  requirements  for  all  build- 
ings. Criteria  are  established  for  insulating  HVAC 
systems  and  for  duct  construction. 

Exception:  Special  applications,  including  but  not 
limited  to  hospitals,  museums,  laboratories,  rooms 
containing  thermally  sensitive  equipment  such  as 
computers,  open  refrigerated  display  cases,  may 
be  exempted  from  the  requirements  of  780  CMR 
1310.0,  when  calculations  and  requirements  are 
submitted  establishing  the  unique  environmental 
criteria  that  exist. 

1310.2  Calculation  of  heating  and  cooling  loads: 

1310.2.1     Calculation     procedures:     For    the 

purpose  of  sizing  HVAC  systems,  heating  and 
cooling  design  loads  shall  be  determined  in 
accordance  with  techniques  recommended  in  the 


214 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


1993  ASHRAE  Handbook  of  Fundamentals  or  the 
Air  Conditioning  Contractors  Association's 
Manual  "J"  The  design  parameters  specified  in 
780  CMR  1305.0  shall  apply  for  all  computations 

1310.3: 

1310.3.1  System  heating/cooling  capacity:  The 

rated  output  capacity  of  the  heating/cooling 
system  at  design  conditions  shall  not  be  greater 
than  125%  of  the  design  load  calculated  in 
accordance  with  780  CMR  13.  Equipment 
designed  for  standby  purposes  is  not  included  in 
the  capacity  limitation  requirement.  For  a  single 
piece  of  equipment  which  has  both  heating  and 
cooling  capability,  only  one  function,  either  the 
heating  or  the  cooling,  need  meet  the 
requirements  of  780  CMR  1310.0.  Capacity  for 
the  other  function  shall  be.  within  available 
equipment  options,  the  smallest  size  necessary  to 
meet  the  load. 

Exception:  Where  the  HVAC  system  for  the 
building  uses  interconnected  equipment 
designed  to  sequence  with  the  load  and  it  can 
be  shown  that  such  design  will  use  less  energy 
on  an  annual  basis  than  one  large  unit. 

1310.3.2  Heat  pump  supplementary  heating 
capacity:  The  rated  output  capacity  of  a  heat 
pump  supplementary  heating  source  shall  not  be 
greater  than  125%  of  the  design  load  as  calculated 
in  accordance  with  780  CMR  13. 

1310.4     Simultaneous     heating     and     cooling: 

Simultaneous  heating  and  cooling  by  reheating  or 
recooling  supply  air  or  by  concurrent  operation  of 
independent  heating  and  cooling  systems  serving  a 
common  zone  shall  be  restricted  as  delineated  in 
780  CMR  1310.4.1  through  3  10.4.3: 

1310.4.1  Recovered  energy:  Recovered  energy, 
provided  the  new  energy  expended  in  the 
recovery  process  is  less  than  the  amount 
recovered,  may  be  used  for  control  of  temperature 
and  humidity.  (New  energy  is  defined  as  energy, 
other  than  recovered,  utilized  for  the  purpose  of 
heating  or  cooling). 

1310.4.2  New  energy  for  humidity  control.  New 

energy  may  be  used,  when  necessary,  to  prevent 
relative  humidity  from  rising  above  53%  for 
comfort  control  or  to  prevent  condensation  on 
terminal  units  or  outlets. 

1310.4.3  New  energy  for  temperature  control: 

New  energy  may  be  used  for  control  of 
temperature  if  minimized  as  delineated  in 
780  CMR  1310.4.3  items  1  through  5: 

1.  Reheat  systems:  Systems  employing 
reheat  and  serving  more  than  one  zone,  other 
than  those  employing  variable  air  volume  for 
temperature  control,  shall  be  provided  with 
controls  that  will  automatically  reset  the  cold 


air  supply.  The  temperature  shall  be  controlled 
to  sequence  reheat  and  cooling. 

2.  Dual  duct  and  multi  zone  systems:  These 
systems  shall  be  provided  with  controls  that 
will  automatically  reset  the  cold  deck  air 
supply  to  the  highest  temperature  that  will 
satisfy  the  zone  requiring  the  coolest  air,  and 
the  hot  deck  air  supply  to  the  lowest 
temperature  that  will  satisfy  the  zone  requiring 
the  warmest  air. 

3.  Recooling  systems:  Systems  in  which 
heated  air  is  recooled,  directly  or  indirectly,  to 
maintain  space  temperature  shall  be  provided 
with  controls  that  will  automatically  reset  the 
temperature  to  which  the  supply  air  is  heated. 
The  temperature  shall  be  the  lowest  level  that 
will  satisfy  the  zone  requiring  the  warmest  air. 

4.  Multiple  zones:  For  systems  with  multiple 
zones,  one  or  more  zones  may  be  chosen  to 
represent  a  number  of  zones  with  similar 
heating/cooling  characteristics.  A  multiple 
zone  HVAC  system  that  employs  reheating  or 
recooling  for  control  of  not  more  than  5,000 
cubic  feet  per  minute  (cfin)  or  20%  of  the  total 
supply  air  of  the  system,  whichever  is  less, 
shall  be  exempt  from  the  supply  air 
temperature  reset  requirement  of  780  CMR 
1310.4.3  I  through  3. 

5.  Concurrent  operation:  Concurrent 
operation  of  independent  heating  and  cooling 
systems  serving  common  spaces  and  requiring 
the  use  of  new  energy  for  heating  or  cooling 
shall  be  minimized  by  one  or  both  of  the 
following: 

a.  by  providing  sequential  temperature 
control  of  both  heating  and  cooling 
capacity  in  each  zone;  and/or 

b.  by  limiting  the  heating  energy  input 
through  automatic  reset  control  of  the 
temperature  of  the  heating  medium  to  only 
that  necessary  to  offset  heat  loss  due  to 
transmission  and  infiltration  and,  where 
applicable,  to  heat  the  ventilation  air 
supply  to  the  space. 

1310.5  Mechanical  ventilation:  Each  mechanical 
ventilation  system  (supply  and/or  exhaust)  shall  be 
equipped  with  motorized  or  other  means  of 
automatic  volume  shutoff  or  reduction  during 
periods  of  non-use  or  alternate  use  of  the  spaces 
served  by  the  system. 

Exceptions: 

1.  For  one-  and  two-family  structures  gravity 
dampers  shall  be  allowed  for  bath  and  kitchen 
exhaust  systems. 

2.  Systems  serving  areas  expected  to  operate 
continuously 

3  For  Systems  which  have  a  design  air  flow  of 
300  cfrn  or  less,  gravity  dampers  shall  be  allowed. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


4.  Gravity  and  other  non-electrical  ventilation 
systems  may  be  controlled  by  readily  accessible 
manual  damper  controls. 

5.  Where  restricted  by  code,  such  as  combustion 
air  intakes. 

1310.6  Fan  system  design  criteria: 

1310.6.1  General:  The  following  design  criteria 
apply  to  all  HVAC  fan  systems  used  for  comfort 
heating,  ventilating,  and/or  air  conditioning.  For 
the  purposes  of  780  CMR  1310.0,  the  energy 
demand  of  a  fan  system  is  the  sum  of  the  demand 
of  all  fans  which  are  required  to  operate  at  design 
conditions  to  supply  air  from  the  heating  and/or 
cooling  source  to  the  conditioned  space(s)  and 
return  it  back  to  the  source  or  exhaust  it  to  the 
outdoors  while  bringing  in  outside  air  for 
ventilation. 
Exceptions: 

1.  Systems  with  total  fan  system  motor 
horsepower  of  10  HP  or  less. 

2.  Unitary  equipment  for  which  fan  energy  is 
included  in  780  CMR  1311  efficiency  ratings. 

1310.6.2  Constant  volume  fan  systems:  For  fan 

systems  which  provide  a  constant  air  volume 
whenever  the  fans  are  operating,  the  power  required 
by  the  motors  for  the  combined  fan  system  at  design 
conditions  shall  not  exceed  0.8  W/cfrn. 

1310.6.3  Variable  air  volume  (VAV)  fan  systems: 

1310.6.3.1For  fan  systems  which  are  able  to  vary 
system  air  volume  automatically  as  a  function  of 
load,  the  power  required  by  the  motors  for  the 
combined  fan  system  at  design  conditions  shall 
not  exceed  1.25  W/cfm. 

1310.6.3.2  Individual  VAV  fans  with  motors  75 
HP  and  larger  shall  include  controls  and  devices 
necessary  for  the  fan  motor  to  demand  no  more 
than  50%  of  design  wattage  at  50%  of  design  air 
volume,  based  on  manufacturer's  test  data. 

1310.7  Controls: 

1310.7.1  Temperature  control:  Each  HVAC 
system  shall  be  provided  with  at  least  one 
thermostat  for  the  regulation  of  temperature. 
Each  thermostat  shall  be  capable  of  being  set  as 
follows: 

1.  when  used  to  control  heating  only,  55  - 
75°F; 

2.  when  used  to  control  cooling  only,  70  - 
85°F;and 

3.  when  used  to  control  both  heating  and 
cooling  it  shall  be  capable  of  being  set  from 
55  -  85  °F,  and  shall  be  capable  of  operating  the 
system  heating  and  cooling  in  sequence.  It 
shall  be  adjustable  to  provide  a  temperature 
range  of  up  to  10°F  between  full  heating  and 


full  cooling,  except  as  allowed  in  780  CMR 
1310.4.3,  item  5. 

1310.7.2  Humidity  control:  If  an  HVAC  system 
is  equipped  with  a  means  for  adding  moisture  to 
maintain  specific  selected  relative  humidities  in 
spaces  or  zones,  a  humidistat  shall  be  provided. 
This  device  shall  be  capable  of  being  set  to 
prevent  new  energy  from  being  used  to  produce 
space  relative  humidity  above  30%  relative 
humidity.  When  a  humidistat  is  used  in  an  HVAC 
system  for  controlling  moisture  removal  to 
maintain  specific  selected  relative  humidities  in 
spaces  or  zones,  it  shall  be  capable  of  being  set  to 
prevent  new  energy  from  being  used  to  produce  a 
space  relative  humidity  less  than  53%. 

1310.7.3  Zoning  for  temperature  control: 

1.  One-  and  two-family  dwellings:  At  least 
one  thermostat  for  regulation  of  space 
temperature  shall  be  provided  for  each  separate 
HVAC  system.  As  a  minimum,  each  floor 
containing  conditioned  space  in  a  one-  and  two 
family  home,  shall  be  considered  as  a  separate 
zone  and  a  thermostat  shall  shall  be  provided 
for  each  zone. 

2.  Multi-family  dwellings:  For  multi-family 
dwellings,  each  individual  dwelling  unit  shall 
be  considered  separately  and  shall  meet  the 
above  requirements.  Spaces  other  than  living 
units  shall  meet  the  requirements  of  780  CMR 
1310.7.3  item  3. 

3.  In  all  other  types  of  buildings  or 
occupancies,  at  least  one  thermostat  for 
regulation  of  space  temperature  shall  be 
provided  for: 

a.  each  separate  HVAC  system;  and 

b.  as  a  minimum,  each  floor  containing 
conditioned  space  in  a  building  shall  be 
considered  as  a  separate  zone.  In  a  multi- 
story building  in  which  the  perimeter 
system  offsets  only  the  transmission  losses 
of  the  exterior  wall,  an  entire  side  of 
uniform  exposure  may  be  zoned  separately. 
A  readily  accessible  manual  or  automatic 
means  shall  be  provided  to  partially  restrict 
or  shut  off  the  heating  and/or  cooling  input 
(for  the  exposure)  to  each  floor. 

1310.7.4  Control  setback  and  shut-off:  Lowering 
thermostat  set  points  to  reduce  energy  consumption 
of  heating  systems  shall  not  cause  energy  to  be  ex- 
pended to  reach  the  reduced  setting. 

1310.7.4.1  Residential  occupancy  (use  groups 
R-2,  R-3,  and  R-4):  The  thermostat  required  in 
780  CMR  13 10.7.3  items  1  and  2,  or  an  alternate 
means  such  as  a  switch  or  a  clock,  shall  provide  a 
readily  accessible,  manual  or  automatic  means  for 
reducing  the  energy  required  for  heating  and 
cooling  during  periods  of  nonuse  or  reduced  need, 
such  as,  but  not  limited  to,  unoccupied  periods 
and  sleeping  hours. 


216 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


1310.7.4.2  Other  buildings  and  occupancies: 

Each  HVAC  system  shall  be  equipped  with  a 
readily  accessible  means  of  shutting  off  or 
reducing  the  energy  used  for  HVAC  during 
periods  of  nonuse  or  alternate  uses  of  the  building 
spaces  or  zones  served  by  the  system. 

1310.7.4.3  Swimming  pools: 

1.    Heated  swimming  pools  shall  be  equipped 
with     controls     to      limit     heating     water 
temperatures  to  not  more  than  80CF. 
Exceptions: 

1.  Pools  used  for  therapeutic  purposes  are 
exempt  from  780  CMR  1310.7.4.3  when 
approved  by  the  building  official. 

2.  Uncovered  (unenclosed)  heated  pools 
shall  be  controlled  so  that  the  electric  or 
fossil  fuel  pool  water  heating  systems  are 
inoperative  whenever  the  outdoor  air 
temperature  is  below  60°F. 

1310.8  Duct  construction:  All  air  handling 
ductwork  and  plenums  shall  be  constructed  and 
erected  in  accordance  with  the  applicable  Sheet 
Metal  and  Air  Conditioning  Contractors  National 
Association  (SMACNA)  Standards. 

1310.8.1  Ductwork  which  is  intended  to  operate 
at  static  pressures  in  excess  of  three  inches  W.C. 
shall  be  leak  tested  and  be  in  conformance  with 
the  following  sections  of  the  SMACNA  Duct 
Leakage  Test  Manual,  1985:  Test  procedures  shall 
be  in  accordance  with  those  outlined  in  Section  5, 
or  equivalent;  test  reports  shall  be  provided  in 
accordance  with  Section  6,  or  equivalent;  the 
tested  duct  leakage  class  at  a  test  pressure  equal  to 
the  design  duct  pressure  class  rating  shall  be  equal 
to  or  less  than  leakage  class  6  as  defined  in 
Section  4.1.  Leakage  testing  may  be  limited  to 
representative  sections  of  the  duct  system  but  in 
no  case  shall  such  tested  sections  include  less  than 
25%  of  the  total  installed  duct  area  for  the 
designated  pressure  class. 

1310.8.2  Where  supply  ductwork  and  plenums 
which  are  intended  to  operate  at  static  pressures 
from  V*  inch  to  three  inches  W.C.  inclusive,  are 
located  outside  of  the  conditioned  space  or  in 
return  plenums,  joints  shall  be  sealed  in 
accordance  with  Seal  Class  C,  as  defined  in  the 
SMACNA  manual  referenced  above.  Pressure 
sensitive  tape  shall  not  be  used  as  the  primary 
sealant  for  such  ducts  which  are  intended  to 
operate  at  static  pressures  of  one  inch  W.C.  or 
greater. 

1310.8.3  Dampers:  Automatic  or  manual 
dampers  installed  for  the  purpose  of  shutting  off 
outside  air  intakes  for  ventilation  air  shall  be 
designed  with  light  tight  shut-off  characteristics  to 
minimize  air  leakage. 


1310.9  Air  handling  duct  system  insulation:  All 

ducts,  plenums  and  enclosures  installed  in  or  on 
buildings  shall  be  thermally  insulated  as  follows: 
1.      Air  Handling  System  Insulation:    All  air 

handling  ducts  and  plenums  installed  as  part  of  an 
HVAC  air  distribution  system  shall  be  thermally 
insulated  in  accordance  with  Table  13 10.9. 

Exception:    Duct  insulation  is  not  required  in 
any  of  the  following  cases: 

a.  Ducts  located  within  the  conditioned 
space  they  serve. 

b.  Supply  or  return  air  ducts  installed  in 
unventilated  crawl  spaces  with  insulated 
walls,    and    basements    or    cellars    with 
insulated   walls   in  one-  and  two-family- 
dwellings; 

c.  When  the  heat  gain  or  loss  of  the  ducts, 
without  insulation,  will  not  increase  the 
energy  requirements  of  the  building; 

d.  Within  HVAC  equipment; 

e.  Exhaust  air  ducts. 

Table  1310.91 
MINIMUM  DUCT  INSULATION 


Duct  Location 

2 
Cooling  " 
Insulation 
R-Value 

•> 
Heating  " 
Insulation 
R-Value 

Outside  of  building  envelope  or 
in  spaces  vented  to  the  outside 

5.0 

6.5 

Inside  of  building  envelope: 
TD~<=15 

None 
Required 

None 
Required 

Inside  of  building  envelope: 
15<TD3<=30 

3.3 

3.3 

Inside  of  building  envelope: 
TD  >30 

5.0 

5.0 

Notes  to  Table  1310.9: 

1.  Insulation  R- values  shown  are  for  the  insulation  only 
and  do  not  include  film  resistance.  The  required 
minimum  thicknesses  do  not  consider  condensation.  For 
ducts  which  are  designed  to  convey  both  heated  and 
cooled  air,  duct  insulation  shall  be  as  required  by  the 
most  restrictive  condition.  Where  exterior  walls  are  used 
as  plenum  walls,  wall  insulation  shall  be  as  required  by 
the  most  restrictive  condition  of  780  CMR  1310  or 
780  CMR  1309  (low  rise  residential)  or  780  CMR  1314 
(high  rise  residential  and  commercial). 

2.  Includes  system  return  ducts. 

3.  TD  is  defined  as  the  temperature  difference  at  design 
conditions  (see  780  CMR  1305)  between  the  space  within 
which  the  duct  is  located  and  the  design  air  temperature 
in  the  duct. 

2.    Vapor   barriers    shall    be    provided,    where 
required,  to  prevent  condensation. 

1310.10  Cooling  with  outdoor  air  (economizer 
cycle):  Each  fan  system  shall  be  designed  to  use  up 
to  and  including  100%  of  the  fan  system  capacity  for 
cooling  with  outdoor  air  automatically  whenever  its 
use  will  result  in  lower  usage  of  new  energy. 
Activation  of  economizer  cycle  shall  be  controlled 
by    sensing   outdoor   air   enthalpy   and    dry   bulb 


2/7/97    (Effective  2/28/97) 


780  CMR -Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


temperature  jointly  or  outdoor  air  dry  bulb 
temperature  alone  to  accomplish  the  above. 

Exceptions:  Cooling  with  outdoor  air  is  not 
required  under  any  one  or  more  of  the  following 
conditions: 

1 .  Fan  system  capacity  less  than  5,000  cubic 
feet  per  minute  (cfm)  or  134,000  Btu/h  of  total 
cooling  capacity; 

2.  The  quality  of  the  outdoor  air  is  so  poor  as 
to  require  extensive  treatment  of  the  air; 

3.  The  need  for  humidification  or 
dehumidification  requires  the  use  of  more 
energy  than  is  conserved  by  the  outdoor  air 
cooling; 

4.  The  use  of  outdoor  air  cooling  may  affect 
the  operation  of  other  systems  so  as  to  increase 
the  overall  energy  consumption  of  the  building; 

5.  Internal/external  zone  heat  recovery  or 
other  energy  recovery  is  used; 

6.  When  all  space  cooling  is  accomplished  by 
a  circulating  liquid  which  transfers  space  heat 
directly  or  indirectly  to  a  heat  rejection  device 
such  as  a  cooling  tower  without  the  use  of  a 
refrigeration  system. 

1310.11  Balancing:  The  HVAC  system  design  shall 
provide  means  for  balancing  the  air  and  water 
systems  such  as  but  not  limited  to  dampers, 
temperature  and  pressure  test  connections,  flow 
measuring  stations  or  meters,  and  balancing  valves. 
The  HVAC  systems  shall  be  field  balanced  to 
achieve  conditions  stated  in  the  plans  and 
specifications  and  in  accordance  with  the  applicable 
reference  standards. 

1310.12  Piping  insulation:  All  piping  installed  to 
serve  buildings  and  within  buildings  shall  be 
thermally  insulated  in  accordance  with  Table 
1310.12. 

Exceptions:  Piping  insulation  is  not  required  in 
any  of  the  following  cases: 

1 .  Piping  installed  within  HVAC  equipment; 

2.  Piping  for  fluids  at  temperatures  between 
55°Fand  105°F; 


3.  When  the  heat  loss  and/or  heat  gain  of  the 
piping,  without  insulation,  does  not  increase 
the  heating  and/or  cooling  energy  requirements 
of  the  building; 

4.  Piping,  installed  in  unventilated  crawl 
spaces  with  insulated  walls,and  basements  or 
cellars  with  insulated  walls  in  one-  and  two- 
family  dwellings. 

1310.12.1  Other  insulation  thickness:  Insulation 
thicknesses  in  Table  13  10. 12  are  based  on  insulation 
with  thermal  conductivities  listed  in  Table  1310.12 
for  each  fluid  operating  temperature  range,  rated  in 
accordance  with  ASTM  C  335-95,  Test  Method  for 
Steady-State  Heat  Transfer  Properties  of  Horizontal 
Pipe  Insulations,  at  the  average  temperature  listed  in 
the  Table.  For  insulation  which  has  a  conductivity 
more  than  10%  in  excess  of  that  shown  in  Table 
1310.12  for  the  applicable  fluid  operation 
temperature  range  and  at  the  average  rating 
temperature  shown,  minimum  thicknesses  shall  be 
determined  in  accordance  with  equation  1310.12.1: 

Equation  1310.12.1 

T  =  PR  X  [(1  +  t/PR)™-1] 

Where: 

T       =     new    minimum    insulation    thickness    for 

material  with  conductivity  K,  inches. 
PR    =    pipe  actual  outside  radius,  inches 
t        =    insulation  thickness  from  Table  1310.12, 

inches. 
K      =    conductivity  of  alternate  material  at  the 

average  rating  temperature  indicated  in 

Table    1310.12   for   the   applicable   fluid 

temperature  range,  (Btu-inch/h-°F-ft  ). 
k       =     conductivity  listed  in  Table  13 10. 12  for  the 

applicable  fluid  temperature  range,  (Btu- 

inch/h-°F-ft2). 

1310.12.2  Vapor  barriers:  Vapor  barriers  shall 
be  provided  to  prevent  condensation  where 
required. 


218 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


Table   1310.12 

MINIMUM  PIPE  INSULATION1 

INSULATION  THICKNESS  IN  INCHES  FOR  PIPE  SIZES  (Note  2) 


Piping 
System 
Types 

Fluid 

Temperature 

Range 

(°F) 

Runouts  ~ 
Up  to  2" 

1" 
&less 

1 '/«" 
to  2" 

2/," 
to  4" 

5" 
to  6" 

8" 
and  larger 

Insulation 
Conductivity 

Heating  Systems 

Steam  &  Hot 

Water 

(B-in/F-hr-sf) 
at  temp  °F 

High 
Press./TVmp. 

351-450 

1.5 

2.5 

2.5 

3.0 

3.5 

3.5 

0.32  @  250° 

Med. 
Press./Temp. 

251-350 

1.5 

2.0 

2.5 

2.5 

3.5 

3.5 

0.29  @  200° 

Low 
Press/Temp. 

201-250 

1.0 

1.5 

1.5 

2.0 

2.0 

3.5 

0.27  @  150° 

Low  Temp. 

141-200 

0.5 

1.5 

1.5 

1.5 

1.5 

1.5 

0.25  @  125  = 

Low  Temp. 

105-140 

0.5 

1.0 

1.0 

1.0 

1.5 

1.5 

0.24  ©  100c 

Steam 
Condensate 
(for  feedwater) 

Any 

1.0 

1.5 

1.5 

2.0 

2.0 

2.0 

0.27  @  150" 

COOLrNG, 
SYSTEMS^ 

Chilled  Water 

40-55 

0.5 

0.5 

0.75 

1.0 

1.0 

1  0 

0.23  @75° 

Refrigerant  or 
Brine 

Below  55 

1.0 

1.0 

1.5 

1.5 

1.5 

1.5 

0.23®.  75° 

Notes: 

1.  For  minimum  thicknesses  of  alternative  insulation  types,  see  780  CMR  1310.12.1. 

2.  Runouts  to  individual  terminal  units  not  exceeding  12  ft.  in  length. 

3.  The  required  minimum  thicknesses  do  not  consider  condensation.  Additional  insulation  and/or  vapor  barriers  may 
be  required  to  prevent  condensation. 


780  CMR  1311.0  HEATING,  VENTILATING 
AND  AJDR  CONDITIONING  EQUTPMENT 

1311.1  Scope:  780  CMR  1311.0  applies  to  all 
buildings. 

1311.2  HVAC  equipment  performance 
requirements:  The  requirements  of  780  CMR 
1311.0  apply  to  equipment  and  component 
performance  for  heating,  ventilating,  and  air 
conditioning  systems.  Where  equipment  efficiency 
levels  are  specified,  data  furnished  by  the  equipment 
supplier,  or  certified  under  a  nationally  recognized 
certification  program  or  rating  procedure,  shall  be 
used  to  satisfy  these  requirements. 

1311.3  HVAC  system  combustion  heating 
equipment:  All  gas  and  oil  fired  comfort  heating 
equipment  shall  have  an  Annual  Fuel  Utilization 
Efficiency  (AFUE)  not  less  than  the  values  shown  in 
Tables  1311.3  through  1311.5.  Equipment  types  not 
covered  in  these  tables  shall  show  a  minimum 
combustion  efficiency  of  75%  at  maximum  rated 
output.  Combustion  efficiency  is  defined  as  100% 
minus  stack  losses  in  percent  of  heat  input.  Stack 
losses  are: 

1 .  loss  due  to  sensible  heat  in  dry  flue  gas; 

2.  loss  due  to  incomplete  combustion;  and 

3.  loss  due  to  sensible  and  latent  heat  in  moisture 
formed  by  combustion  of  hydrogen  in  the  flue. 


Table  1311.3(a) 

STANDARD  RATING  CONDITIONS  AND 

MINIMUM  PERFORMANCE  WARM  AIR 

FURNACES  AND  COMBINATION  WARM 

AIR  FURNACES/AIR-CONDITIONING  UNITS 


Reference 
Standards 

Category 

Rating  Condition 

Minimum 
Performance 

10CFR 

Gas-Fired 

<225,000 

Btu/h 

Seasonal  Rating 

AFUE    78%4 
£,3        80% 

430(B) 

Oil-Fired 

<225,000 

Bto/h 

Seasonal  Rating 

AFUE    78%" 
E?       30% 

ANSI 

Gas-Fired 

2225,000 

Btu/h 

1 .  Maximum  Rating 
Capacity" 
Steadv-State 

E,5       80% 

Z2 1.47-90 

2.  Minimum  Rating 
Capacity" 
Steadv-State 

E?       78% 

UL  727-86 

Oil-Fired 

2225,000 

Btu/h 

1 .  Maximum  Rating 
Capacity" 
Steady-State 

E,5       81% 

2.  Minimum  Rating 
Capacity" 
Steadv-State 

E,5       81% 

For  SI:  °F=  1.8°C  =  32.  1  Btu/h  =  0.2931  W 

1 .  Listed  in  Appendix  A 

2.  Minimum  and  maximum  ratings  as  provided  for  and 
allowed  by  the  unifs  controls 

3.  These  requirements  apply  to  combination  units  not 
covered  by  NAECA  (three  phase  power  or  cooling 
capacity  >  65,000  Btu/h). 

4.  This  is  used  to  be  consistent  wth  National  Appliance 
Energy  Conservation  Act  (NAECA)  of  1987  (Public  Law 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


219 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


100-2).    These  values  apply  to  furnace  and  combination 
units  covered  by  NAECA. 

5.       See  references  standard  for  detailed  definition  of 
themal  efficiency  (E,)  =  (100%  minus  flue  losses). 

Table  1311.3(b) 
STANDARD  RATING  CONDITIONS  AND 
MINIMUM  PERFORMANCE  WARM  AIR 
DUCT  FURNACES  AND  UNIT  HEATERS 


Reference 
Standards 

Category 

Rating  Condition 

Minimum 
Performance 

ANSI 

Duct 
Furnaces 
Gas-Fired 

I .  Maximum  Rating 
Capacity" 
Steady-State 

3              4 
E,        78% 

Z83.9-86 

2.  Minimum  Rating 
Capacity" 
Steady-State 

i               4 
£■/      75% 

ANSI 

Unit  Heaters 
Gas-Fired 

1 .  Maximum  Rating 
Capacity 
Steady-State 

E?       78% 

Z83.8-95 

2.  Minimum  Rating 
Capacity" 
Steady-State 

£•/       74% 

UL  73 1-88 

Unit  Heaters 
Oil-Fired 

1 .  Maximum  Rating 
Capacity" 
Steadv-State 

£,3       81% 

2.  Minimum  Rating 
Capacity" 
Steadv-State 

£,3       81% 

1.  Listed  in  Appendix  A 

2.  Provided  and  allowed  by  the  controls. 

3.  E,  =  themal  efficiency,  100%  minus  flue  losses.   See 
reference  standard  for  detailed  definition. 

Table  1311.3(b) 

STANDARD  RATING  CONDITIONS  AND 

MINIMUM  PERFORMANCE  GAS  AND  OEL- 

FIRED  STEAM  AND  HOT  WATER  BOILERS 


Reference 
Standards 

Category 

Rating  Condition 

Minimum 
Performance 

10CFR 

Gas-Fired 

<3000,000 

Btu/h 

Seasonal  Rating 

AFUE  80%4,5 

430(B) 

Oil-Fired 

<3000,000 

Btu/h 

Seasonal  Rating 

AFUE    80%" 

HI6 

Gas-Fired 

2  3000,000 

Btu/h 

1 .  Maximum  Rating 
Capacity" 
Steady-State 

Ec3       80% 

2.  Minimum  Rating 
Capacity" 
Steady-State 

m7 

Oil-Fired 

2  3000,000 

Btu/h 

1 .  Maximum  Rating 
Capacity" 
Steadv-State 

£,3        83% 

2.  Minimum  Rating 
Capacity" 
Steadv-State 

HI8 

Oil-Fired 

(Residual) 

2  3000,000 

Btu/h 

1 .  Maximum  Rating 
Capacity" 
Steady-State 

£,3        83% 

2.  Minimum  Rating 
Capacity 
Steadv-State 

2.  Provided  and  allowed  by  the  controls. 

3.  Et  =  themal  efficiency,  100%  minus  flue  losses.  See 
reference  standard  for  detailed  definition. 

4.  To  be  consistent  with  National  Appliance  Energy 
Conservation  Act  of  1987  (Public  Law  100-12). 

5.  Except  for  fas-fired  steam  boilers  for  which  minimum 
AFUE  is  75% 

6.  HI  =  Hydronics  Institute,  Test  &  Rating  Standard/ 
Heating  Boilers  -  1982;  ANSI  Z2 1.13-87;  ANSI/ASME 
Ptc  4.1-64;  UL  795-73. 

7.  Hydronics  Institute,  Test  &  Rating  Standard/  Heating 
Boiler's  -  1982;  ANSI/ASME  Ptc  4. 1  -  64;  UL  726-90 

8.  Hydronics  Institute,  Test  &  Rating  Standard/  Heating 
Boilers  -  1982;  ANSI/ASME  Ptc  4. 1  -  64. 

1311.4  HVAC  system  heating  equipment,  heat 
pumps  heating  mode:  Heat  pumps  whose  energy 
input  is  entirely  electric  shall  show  a  coefficient  of 
performance  (COP  heating,  as  defined  herein)  not 
less  than  the  values  shown  in  Table  13 1 1.4. 

1.  These  requirements  apply  to,  but  are  not 
limited  to,  unitary  heat  pumps  (air  source)  in  the 
heating  mode,  and  to  packaged  terminal  heat 
pumps  in  the  heating  mode.  Field  assembled 
unitary  heat  pumps,  consisting  of  one  or  more 
components,  shall  show  compliance  with 
780  CMR  1311.4 

2.  Coefficient  of  performance  heating:  the 
ratio  of  the  rate  of  net  heat  output  to  the  rate  of 
total  on-site  energy  input,  expressed  in  consistent 
units  and  under  designated  rating  conditions.  The 
rate  of  net  heat  output  shall  be  defined  as  the 
change  in  the  total  heat  content  of  the  air  between 
entering  and  leaving  the  equipment  (not  including 
supplementary  heat). 

3.  Supplementary  heater:  The  heat  pump  shall 
be  installed  with  a  control  to  prevent 
supplementary  heater  operation  when  the  heating 
load  can  be  met  by  the  heat  pump  alone. 
Supplementary  heater  operation  is  permitted 
during  transient  periods,  such  as  start-ups, 
following  room  thermostat  set-point  advance  and 
during  defrost.  A  two  stage  thermostat,  which 
controls  the  supplementary  heat  on  its  second 
stage,  shall  be  accepted  as  meeting  this 
requirement.  The  cut-on  temperature  for  the 
compression  heating  shall  be  higher  than  the  cut- 
on  temperature  for  the  supplementary  heat,  and 
the  cut-off  temperature  for  the  compression 
heating  shall  be  higher  than  the  cut-off 
temperature  for  the  supplementary  heat. 
Supplementary  heat  may  be  derived  from  any 
source  of  electric  resistance  heating  or 
combustion  heating. 


1 .    Listed  in  Appendix  A 


220 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


Table  1311.4 

MINIMUM  COP  FOR  HEAT  PUMPS, 

HEATING  MODE 


CATEGORY 

PERFORMANCE 

REFERENCE 
STAND  ARD(S) 

Air  Source,  single  phase: 
(Cooling  capacity  less 
than  65,000  Btu/hr) 

Hi-temp 

(47db/43\vb); 

(Mm.  COP  =  2.7) 

Low-temp 

(17db/15wb); 

(Min.  COP  =1.8) 

ARJ210/24/-89 

Air  Source,  three  phase: 
(Cooling  capacity  less 
than  35,000  Btu/hr) 

Hi-temp 

(47db/43wb); 

(Min.  COP  =  2.7) 

Low-temp 

(17db/15wb); 

(Mm.  COP  =  1.8) 

Packaged  Terminal  Heat 
Pumps 

Min.  COP  =  2.5 

1311.5  HVAC  system  equipment,  electrically 
operated  cooling  mode:  HVAC  system  equipment 
as  listed  below  whose  energy  input  in  the  cooling 
mode  is  entirely  electric  shall  show  a  Seasonal 
Energy  Efficiency  Ratio  (SEER)  or  Energy 
Efficiency  Ratio  (EER)  not  less  than  the  values 
shown  in  Table  1311.5. 

1311.5.1:  These  requirements  apply  to,  but  are 
not  limited  to,  unitary  cooling  equipment  (air- 
cooled,  water-cooled,  and  evaporatively  cooled); 
the  cooling  mode  of  unitary  heat  pumps;  and 
packaged  terminal  air  conditioners. 

TABLE  1311.5 

MINIMUM  SEER  AND  EER  FOR 

ELECTRICALLY  DRIVEN  AIR 

CONDITIONING  EQUIPMENT 


TYPE 


Air,  single  phase: 
(Cooling  capacity 

less  than  65,000 

Btu/hr) 


Mm.  SEER  =  7.8 


Air,  three  phase: 
(Cooling  capa-city 

less  than  65,000 

Btu/hr) 


Air: 

(Cooling  capacity 
greater  than 
65,000  Btu/hr 
but  less  than 
135,000  Btu/hr) 


Packaged  Terminal 
Heat  Pumo 


Packaged  Terminal 
Air  Conditioner 


PERFORMANCE 


Min.  EER  (Hi-temp)  = 
2 


Min.  EER  (Hi-temp)  = 
8.2 


Mm.  EER  =  7.8 


Min.  EER  =  7.8 


REFERENCE 
STAND  ARD(S) 


ARI  210/240-89 


1311.6  Applied  HVAC  system  components, 
electrically  operated  cooling  mode:  HVAC  system 
components,  as  listed  in  Table  1311 .6,  whose  energy 
input  is  entirely  electric  shall  show  a  coefficient  of 
performance  (COP)  cooling,  as  defined  herein,  not 
less  than  the  values  shown  in  Table  1311.6. 

1311.6.1        Coefficient       of       performance: 

Coefficient  of  Performance  (COP)  cooling  is  the 
ratio  of  the  rate  of  net  heat  removal  to  the  rate  of 
total  energy  input,  expressed  in  consistent  units 
and  under  designated  rating  conditions. 

The  rate  of  net  heat  removal  is  defined  as  the 
difference  in  total  heat  content  of  the  water  or 
refrigerant  entering  and  leaving  the  component 

Total  on-site  energy  input  shall  be  determined 
by  combining  the  energy  inputs  to  all  elements 
"  and  accessories  of  the  component,  including  but 
not  limited  to  compressors,  internal  circulating 
pumps,  purge,  and  the  HVAC  system  component 
control  circuit. 

Table  1311.6 

MINIMUM  EER  AND  COP  FOR 

ELECTRICALLY  DRIVEN  AIR 

CONDITIONING  SYSTEM  COMPONENTS 


Component 

Condensmg 
Means 

Coolant 

EER 

COP 

Reference 
Standard 

Self-Contained 
Chillers 

Centrifugal 

Air 

8.2 

2.4 

ARI  550- 
92 

Self-Contained 
Chillers 

Centrifugal 
<  250  Tons 

Water 

16.4 

4.8 

ARI  550- 
92 

Self-Contained 
Chillers 

Centrifugal 
>  250  Tons 

Water 

17.1 

5.0 

ARI  550- 
92 

Self-Contained 
Chillers 

Rotary 

Air 

8.2 

2.4 

ARI  550- 
92 

Self-Contained 
Chillers 

Rotary 

Water 

14.0 

4.1 

ARI  550- 
92 

Self-Contained 
Chillers  -  with 
Condenser 

Positive 
Displace- 
ment 

Air 

8.9 

2.6 

ARI  590- 
92 

Self-Contained 
Chillers  -  with 
Condenser 

Positive 
Displace- 
ment 

Water 

12.6 

3.7 

ARI  590- 
92 

Self-Contained 
Chillers  - 
without 
Condenser 

Positive 
Displace- 
ment 

Air 

10.1 

3.0 

ARI  590- 
92 

Condenser 
Units 

135,000  Btu/hr 
or  Less 

Air 

9.5 

2.8 

ARI  365- 
94 

Condenser 
Units 

135,000  Btu/hr 
or  Less 

Water 
(Evap) 

12.7 

3.7 

ARI  365- 
94 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


221 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1311.7  HVAC  system  equipment,  heat  operated, 
cooling  mode:  Heat  operated  cooling  equipment 
shall  show  a  coefficient  of  performance  (COP) 
cooling  not  less  than  the  values  shown  in  Table 
1311.7.  These  requirements  apply  to,  but  are  not 
limited  to,  absorption  equipment,  engine  driven 
equipment,  and  turbine  drive  equipment. 

When  the  refrigeration  components  are  supplied 
by  different  manufacturers,  it  shall  be  the 
responsibility  of  the  system  designer  to  determine 
compliance  with  these  requirements,  using  data 
provided  by  the  suppliers  of  the  elements. 

Table  1311.7 
MINIMUM  COP  FOR  HEAT  OPERATED 
AIR  CONDITIONING  SYSTEM  EQUIPMENT 


HEAT  SOURCE 


Direct  fired  (gas/oil) 


Indirect  fired  (steam/hot 
water) 


MINIMUM  COP 


0.' 


780  CMR  1312.0  ELECTRICAL  POWER 
DISTRIBUTION 

1312.1  Scope:  Electrical  distribution  systems  shall 
be  designed  for  the  efficient  distribution  of  electrical 
energy  from  the  service  entrance  to  the  points  of  use. 

1312.1.1  Exempt  buildings:  Buildings  in  use 
groups  R-3  and  R-4  (one-and  two-family 
dwellings)  shall  be  exempt  from  the  requirements 
of  780  CMR  1312.0 

1312.2  Power  factor:  Utilization  equipment  greater 
than  1,000  watts  and  lighting  equipment  greater  than 
15  watts  with  an  inductive  reactance  load  component 
shall  have  a  power  factor  of  not  less  than  85%  under 
rated  load  conditions.  Power  factor  of  less  than  85% 
shall  be  corrected  to  at  least  90%  under  rated  load 
conditions.  Power  factor  corrective  devices,  installed 
to  comply  with  this  code,  shall  be  switched  with  the 
utilization  equipment,  except  where  this  results  in  an 
unsafe  condition  or  interferes  with  the  intended 
operation  of  the  equipment. 

1312.3  Service  voltage:  Where  a  choice  of  service 
voltage  is  available,  a  computation  shall  be  made  to 
determine  which  service  voltage  would  produce  the 
least  energy  loss,  and  that  voltage  shall  be  selected. 

1312.4  Electric  energy  determination:  In  all  multi- 
family  dwellings,  each  dwelling  unit  shall  be 
separately  metered. 

Exceptions: 

1.  Publicly  financed  housing  for  the  elderly 
with  fuel  fired  heating  systems,  with  centrally 
operated  air  conditioning  systems,  or  without 
air  conditioning  systems  are  exempt  from  this 
requirement. 

2.  Publicly  financed  housing  for  the  elderly 
with    electric   resistance   or   storage   heating 


systems  are  exempt  from  780  CMR  1312.4 
provided  there  is  informational  metering  of  the 
individual  dwelling  units. 

780  CMR  1313.0    LIGHTING  SYSTEMS 
1313.1  Scope:  780  CMR  1313.0  establishes  the 
maximum  power  limits  and  control  requirements  for 
interior  and  exterior  illumination  systems. 

1313.1.1  The  rooms,  spaces  and  areas  covered 
by  780  CMR  1313.0  include: 

1.  Interior  spaces  of  buildings. 

2.  Building  exterior  areas  such  as:  entrances, 
exits,  loading  docks,  etc. 

3.  Roads,  grounds  and  other  exterior  areas 
including  open-air  covered  areas  where 
lighting  is  required  and  is  energized  through 
the  building  electrical  service. 

1313.1.2  Exempt  buildings  and  spaces:  The 

following  buildings  and  spaces  are  exempt  from 
the  provisions  of  780  CMR  13 13.0: 

1.  Lighting  for  dwellings  units  contained  in 
use  groups  R-2,  R-3  and  R-4,  except  for  the 
switching  requirements  in  1313.2.2.1. 

2.  Outdoor  activities  such  as  manufacturing, 
storage,  commercial  green  houses  and 
processing  facilities. 

3.  Lighting  power  for  theatrical  productions, 
television  broadcasting,  audio-visual 
presentations  and  those  portions  of 
entertainment  facilities  where  lighting  is  an 
essential  technical  element  for  the  function 
performed. 

4.  Specialized  luminaires  for  medical  and 
dental  purposes. 

5.  Outdoor  athletic  facilities. 

6.  Display  lighting  required  for  art  exhibits  or 
displays  in  galleries,  museums  and  monuments. 

7.  Exterior  lighting  for  public  monuments  and 
recognized  landmarks  such  as  buildings 
individually  listed  on  the  National  Register  of 
Historic  Places. 

8.  Special  lighting  needs  for  research. 

9.  Lighting  to  be  used  solely  for  indoor  plant 
growth  during  the  hours  of  1 0:00  P.M.  to  6:00 
A.M. 

10.  Emergency  lighting  that  is  automatically 
"off'  during  normal  operation. 

1 1 .  High  risk  security  areas  identified  by  local 
ordinances  or  regulations  or  by  security  or 
safety  personnel  as  requiring  additional 
lighting. 

12.  Classrooms  specifically  designed  for  the 
hard  of  seeing,  hard  of  hearing  (lip-reading), 
and  for  senior  citizens. 

13.  Lighting  for  signs. 

14.  Store-front  display  windows  in  retail 
facilities. 

15.  Spaces  regularly  used  for  religious 
services  or  worship. 


222 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


1313.2  Minimum  requirements:  This  780  CMR 

1313.2  establishes  the  minimum  requirements  which 
must  be  met  for  all  spaces  covered  by  780  CMR 
1313.0. 

1313.2.1  Building  Lighting  Power  Limit 
(BLPL):  A  Building  Lighting  Power  Limit 
(BLPL)  is  the  upper  limit  of  the  power  to  be 
available  to  provide  the  lighting  needs  of  a 
building. 

The  Building  Lighting  Power  Limit  (BLPL)  is 
the  sum  of  the  building  Exterior  Lighting  Power 
Allowance  (ELPA),  the  Roads  and  Grounds 
Lighting  Power  Allowance  (RLPA),  and  the 
building  Interior  Lighting  Power  Limit  (ILPL). 

1.  The  building  Exterior  Lighting  Power 
Allowance  (ELPA)  is  calculated  in  780  CMR 
1313.2.1.4. 

2.  The  Roads  and  Grounds  Lighting  Power 
Allowance  (RLPA)  is  calculated  in  780  CMR 
1313.2.1.5. 

3.  The  building  Interior  Lighting  Power  Limit 
(ILPL)  may  be  calculated  either  by  the 
prescriptive  criteria  in  780  CMR  1313.4  o_i  by 
the  system  performance  criteria  in  780  CMR 
1313.5. 

The  prescriptive  criteria  (1313.4)  provide  a 
simple  calculation  procedure  with  limited 
flexibility.  The  system  performance  criteria 
(780  CMR  1313.5)  provide  a  more  complex  and 
lengthy  calculation  procedure  with  greater 
flexibility  usually  suitable  for  complex  lighting 
systems  in  larger  buildings. 

When  using  the  system  performance  criteria 
(780  CMR  1313.5)  a  computer-based  procedure, 
approved  by  the  State  Board  of  Building 
Regulations  and  Standards,  may  be  used  to 
calculate  the  ILPL  compliance  value. 

1313.2.1.1    Compliance:   A  building  design 

shall    be    considered    in    compliance    with 

780  CMR  13 13.0  if: 

1.  The  exterior  lighting  power  to  be 
installed  is  no  greater  than  the  Exterior 
Lighting  Power  Allowance  (ELPA). 

2.  The  roads  and  ground  lighting  power  to 
be  installed  is  not  greater  than  the  Roads 
and  Grounds  Lighting  Power  Allowance 
(RLPA). 

3.  The  interior  lighting  power  to  be 
installed  is  not  greater  than  the  Interior 
Lighting  Power  Limit  (ILPL).  Tradeoffs 
between  ILPL  and  ELPA  or  RLPA  shall 


not  be  allowed  (also  see  780  CMR 
1313.2.1.2). 

1313.2.1.2  Compliance  for  multiple 
buildings  of  a  facility:  The  lighting  power 
limits  for  each  building  in  a  facility  shall  be 
calculated  separately.  Tradeoffs  among 
buildings  shall  be  restricted  as  described 
below: 

1.  Tradeoffs  of  Interior  Lighting  Power 
Limits  among  other  buildings  of  the  same 
facility  shall  not  be  allowed. 

2.  Tradeoffs  between  Interior  Lighting 
Power  Limits  and  Exterior  Lighting  Power 
Allowances  or  Roads  and  Grounds  Power 
Allowances  shall  not  be  allowed. 

3 .  Tradeoffs  of  Exterior  Lighting  Power 
Allowances  among  buildings  of  the  same 
facility  are  allowed. 

1313.2.1.3  Forms  for  compliance:  Forms 
approved  by  the  Board  of  Building  Regulations 
and  Standards,  when  such  Forms  exist,  shall  be 
completed  to  show  compliance  with  780  CMR 
1313.0,  as  follows: 

1.  To  summarize  the  total  Exterior 
Lighting  Power  Allowance  (ELPA). 

2.  To  summarize  the  maximum  Road  and 
Grounds  Lighting  Power  Allowance 
(RLPA). 

3.  To  summarize  the  maximum  Building 
or  Facility  Lighting  Power  Limit  (BLPL, 
FLPL).  The  BLPL  or  FLPL  shall  be  the 
sum  of  the  ILPL  and  the  ELPA  of  the 
building  (or  of  all  buildings)  and  the  RLPA 
of  the  road  and  grounds. 

4.  If  the  prescriptive  criteria  of  780  CMR 
1313.4  are  used  to  determine  the  Interior 
Lighting  Power  Limit  (ILPL),  then  an 
approved  form  shall  be  used  to  summarize 
the  maximum  Interior  Lighting  Power 
Limit. 

5.  If  the  system  performance  criteria  of 
780  CMR  1313.5  are  used  to  determined 
the  interior  lighting  power  limit  (ILPL), 
then  an  approved  form  (or  an  equivalent 
computer  generated  printout)  shall  be  used 
to  summarize  the  Interior  Lighting  Power 
Limit. 

1313.2.1.4  Exterior  Lighting  Power 
Allowance  (ELPA):  Lighting  power  for 
building  exteriors  shall  not  exceed  the  values 
given  in  Table  1313.2.1.4  in  accordance  with 
the  activities  to  be  performed. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


223 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1313.2.1.4 

MAXIMUM  LIGHTING  POWER 

ALLOWANCES  (CONNECTED  LOAD)  FOR 

BUILDING  EXTERIORS 


LOCATION 

ALLOWANCE  ' 

Exit  (with  or  without  a 
canopy) 

20  W/lin.  ft.  of  door  opening 

Entrance  (without  a  canopv) 

30  W/lin.  ft.  of  door  opening 

Entrance  (with  a  canopy) 

High  traffic  (retail,  hotel, 
airport,  theater,  etc.) 

1 0  W/ft  of  canopied  area 

Light  traffic  (hospital,  office, 
school,  etc.) 

4  W/ft  of  canopied  area 

Loading  area 

0.030  W/ft" 

Loading  door 

20  W/lin.  ft  of  door  opening 

NOTE:  Total  illumination  allowance  for  the  building  is 
10  W/Lin.  Ft.  exterior  (including  the  above  allowances) 
of  building  perimeter. 

1313.2.1.5  Roads  and  Grounds  Power 
Allowance  (RLPA):  Lighting  power  for  roads 
and  grounds  shall  not  exceed  the  values  in 
Table  1313.2.1.5. 

Table  1313.2.1.5 

MAXIMUM  LIGHTING  POWER 

ALLOWANCES  (CONNECTED  LOAD)  FOR 

ROADS  AND  GROUNDS 


LOCATION 

ALLOWANCE 

Storage  and  work  areas 

0.20  W/ft" 

Other  activity  areas  for  casual 
use  such  as  picnic  grounds, 
gardens,  parks,  and  other 
landscaped  areas 

0.10  W/ft" 

Private  drivewavs/walkways 

0.10  W/ft" 

Public  drivewavs/walkwavs 

0.15  W/ft" 

Private  parkins  lots 

0.12  W/ft" 

Public  parking  lots 

0.1 8  W/ft" 

1313.2.2  Interior  and  exterior  lighting  controls: 

All  lighting  systems  except  those  required  for 
emergency  or  exit  lightings  shall  be  provided  with 
manual,  automatic  or  programmable  controls. 

1313.2.2.1    Minimum    number  of  lighting 
controls: 

1.  Each  area  enclosed  by  ceiling  height 
partitions  shall  have  independent  control  of 
the  lighting  within  that  area. 

2.  The  maximum  area  to  be  controlled  by 
a  single  switch  shall  be  750  square  feet. 
The  total  number  of  switches  shall  be  not 
less  than  one  switch  for  each  1600  watts 
(@  277  volts)  of  connected  load,  or  one 
switch  for  each  1250  watts  (@  120  volts) 
of  connected  load. 

Exception:  Lighting  control  requirements 
for  spaces  which  must  be  used  as  a  whole 
may  be  controlled  by  a  lesser  number  of 
controls,  but  not  less  than  one  control  point 
for  each   1500  W  of  connected  lighting 


power,  or  a  total  of  three  control  points, 
whichever  is  greater.  Examples  of  such 
spaces  include  public  lobbies  of  office 
buildings,  hotels  and  hospitals:  retail  and 
department  stores;  warehouses;  and  store 
rooms  and  service  corridors  under 
centralized  supervision.  Lighting  in  such 
spaces  shall  be  controlled  in  accordance 
with  the  work  activities. 

3.  Hotel  and  motel  guest  rooms  excluding 
bathrooms  shall  have  one  or  more  master 
switches  at  the  door  that  turn  off  all 
permanently  wired  lighting  fixtures  and 
switched  receptacles.  For  multiple  room 
hotel  suites,  switches  at  the  entry  of  each 
room,  in  lieu  of  the  switch  at  the  main 
door,  will  be  acceptable  to  meet  these 
requirements. 

4.  Bathrooms  in  hotels  and  motels  shall 
have  a  switchable,  permanently  installed 
night  light  with  a  maximum  wattage  of  five 
watts. 

5.  Switches  controlling  the  same  load 
from  more  than  one  location  shall  not  be 
credited  as  increasing  the  number  of 
controls  to  meet  the  requirements  of 
780  CMR  1313. .2.2. 

6.  All  task  lighting  shall  be  separately 
controlled.  There  shall  be  at  least  one 
switch  per  task  area.  Switches  for  task 
lighting  may  be  incorporated  as  part  of  the 
lighting  fixture. 

Exceptions: 

1.  Lighting  controls  for  spaces  which 
must  be  used  as  a  whole,  such  as  public 
lobbies  of  office  buildings,  hotels,  and 
hospitals;  and  warehouses,  storerooms  and 
service  corridors  under  centralized  super- 
vision may  be  centralized  in  remote 
locations. 

2.  Manual  and  automatic  control  devices 
may  reduce  the  number  of  controls 
required  as  listed  in  Table  13 13.2.2. 

Table  1313.2.2 

REDUCTION  ALLOWANCE  FOR 

SELECTED  CONTROLS 


TYPE  OF  CONTROL 

EQUIVALENT  NUMBER 
OF  CONTROL  POINTS 

Occupancy  sensors 

2 

Timer  -  Programmable  from  the 
space  being  controlled 

2 

Three  level,  including  off,  step 
control  or  pre-set  dimming 

2 

Four  level,  including  off,  step 
control  or  pre-set  dimming 

3 

Automatic  or  continuous 
dimming 

3 

1313.2.2.2    Accessibility    of   switches:    All 

switching   devices   used   to   control    lighting 


224 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


within  an  area  shall  be  readily  accessible  to 

personnel  occupying  that  area. 
Exceptions: 

1 .  Lighting  controls  for  spaces  which 
must  be  used  a  whole,  such  as  public 
lobbies  of  office  buildings,  hotels,  and 
hospitals;  retail  and  department  stores 
and  warehouses,  storerooms  and  service 
corridors  under  centralized  supervision 
may  be  centralized  in  remote  locations. 

2.  Automatic  controls 

3.  Programmable  controls 

4.  Controls  requiring  trained  operators. 

5.  Controls  for  safety  hazards  and 
security 

1313.2.2.3  Exterior  lighting  controls:  In  all 
exterior  areas,  lighting  fixtures  shall  be 
automatically  switched  for  non-operation  when 
natural  light  is  available  except  where  security 
considerations  would  dictate  otherwise. 

1313.2.3  Ballasts 

1313.2.3.1      Fluorescent      lamp      ballasts: 

Fluorescent  lamp  ballasts  which  have  all  the 
following  characteristics  shall  meet  or  exceed 
the  minimum  ballast  efficiency  factor  as  shown 
in  Table  1313.2.3. 

1.  Operate  at  nominal  input  voltages  of 
120  or  277  volts; 

2.  Have  a  power  factor  equal  to  or  greater 
than  0.60  for  a  single  F40T 12  lamp; 

3.  Used  to  operate  either  F40T12  or 
F96T12  lamps  as  specified  in  Table 
1313.2.3; 

4.  Designed  for  use  at  temperatures  above 
0°F; 

5.  Not  specifically  designed  for  use  with 
dimming  controls. 

Table  1313.2.3 

MINIMUM  BALLAST  EFFICIENCY 

FACTOR 


BALLAST  TYPE 

BALLAST  EFFICIENCY 
FACTOR 

One  -  4  foot  lamp 

1.805 

Two  -  4  foot  lamps  ( 1 20  V) 

1.06 

Two  -  4  foot  lamps  (277  V) 

1.05 

Two  -  8  foot  slimline  lamps 

0.57 

Two  -  8  foot  high  output  rapid 
start  lamps 

0.39 

Note:        The  Ballast  efficiency  factor  shall  be  calculated 
in  accordance  with  Equation  13 13.2.3. 1 : 

Equation  1313.2.3.1 


BEF 


BF 


Power  Input 


where: 

BEF  =    Ballast  efficiency  factor 


BF    =    Ballast  factor,  expressed  as  a  percent  (also 

known  as  Relative  Light  Output) 
Power  Input  =  Total  wattage  of  combined  lamps 
and  ballasts 

Tests  for  ballast  factor  and  power  input 
shall  be  in  accordance  with  ANSI  Standard 
C82.2  1984  Method  of  Measurement  for 
Fluorescent  Lamps  Ballasts  using  Standard 
Lamps. 

1313.2.3.2  One-lamp  or  three-lamp  fluorescent 
luminaires  recess-mounted  within  ten  feet 
center-to-center  of  each  other  or  pendant- 
mounted  or  surface-mounted  within  one  foot  of 
each  other,  and  within  the  same  room,  shall  be 
tandem  wired  to  eliminate  unnecessary  use  of 
single-lamp  ballast. 

1313.2.3.3  Ballasts  shall  have  a  power  factor 
greater  than  90%. 

Exception: 

1      Ballasts    for    circline    and    compact 

fluorescent  lamps  and  low  wattage  high 

intensity  discharge  lamps  of  less  than  100 

watts. 

2.    Dimming  ballasts. 

1313.3    Interior    lighting    power    adjustment 
factors: 

1313.3.1  Adjusted    Lighting    Power    (ALP) 

When  determining  interior  lighting  compliance  in 
780  CMR  1313.4  or  1313.5,  the  Connected 
Lighting  Power  (CLP)  for  lights  controlled  by 
normal  switching  must  not  exceed  the  Interior 
Lighting  Power  Limit  (ILPL).  However,  when  the 
switching  controls  are  automatic  (i.e.  daylight 
sensors,  occupancy  sensors,  or  lumen 
maintenance  controls)  the  connected  lighting 
power  may  exceed  the  ILPL  provided  that  the 
Adjusted  Lighting  Power  (ALP),  calculated  using 
equation  1313.3.1  does  not  exceed  the  ILPL 

Equation  1313.3.1 

ALP  =  CLP  XPAF  ^^ 

ALP  =    Adjusted  Lighting  Power,  watts 

CLP  =    Connected     Lighting     Power     for     the 

luminaires   controlled   by   the   automatic 

control  device,  watts 
PAF  =    Power  Adjustment  Factor 

1313.3.2  Power  Adjustment  Factor  (PAF):  The 

Power  Adjustment  Factor  is  limited  to  the  specific 
area  controlled  by  the  automatic  control  device 
The  Power  Adjustment  Factor  shall  be  as  shown 
in  Table  1313.3.2 

1313.3.3  Daylighting  credits:  Where  daylighting 
credit  is  utilized,  based  on  the  procedures  in 
780  CMR  1313.2.2.1  or  1313  3  2,  automatic 
controls  such  as  photoelectric  switches  or 
automatic  dimmers  shall  be  provided  in  the 
daylighted  spaces. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


225 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1313.3.2 
POWER  AD JUSTMENT  FACTOR  (PAF) 


AUTOMATIC  CONTROL  DEVICE 

PAF 

1 .  Occupancy  sensors 

0  70 

2.  Daylighting  sensors 
a)  Continuous  dimming 
h)  Multiple  step  control 
c)  On-off  control 

0.70 
0.80 
0.90 

3-  Lumen  maintenance  control 

0.90 

4  Combination  of  1 .  and  2. 

0.60 

5.  Combination  of  1 .  and  3 

065 

6.  Combination  of  1.,  2  and  3. 

0.55 

7  Programmable  timing  control 

0.S5 

Notes: 

1.  PAF  credits  shall  not  be  applied  to  the  dimming 
controls  of  incandescent  lamps  or  luminaires. 

2.  Only  one  adjustment  factor  may  be  used  for  each 
building  space  or  lummaire.  and  50%  or  more  of  the 
luminaire  shall  be  within  the  applicable  space  to  qualify 
for  the  power  adjustment  factor  Controls  shall  be  in- 
stalled in  series  with  the  lights  and  in  series  with  all 
manual  switching  devices  in  order  to  qualify  for  an 
adjustment  factor. 

3.  Daylighting  controls  shall  be  able  to  reduce  electrical 
power  consumption  for  lighting,  continuously  or  in  two 
or  more  steps,  to  50%  or  less  of  maximum  power 
consumption:  shall  control  all  luminaires  more  than  50% 
within  a  dayiighted  space,  and  shall  not  control  any 
lummaire  more  than  50%  outside  a  dayiighted  space. 

4.  Programmable  tuning  controls  used  for  credit  in 
conjunction  with  Table  13 13.3.2  shall  be  capable  of: 

a.  programming  different  schedules  for  week  days 
and  weekends. 

b.  temporary  override  by  occupants  with  automatic 
return  to  the  original  schedules.  Override  controls 
shall  be  readily  accessible. 

c.  providing  independent  control  of  each  lighting  load 
which  is  required  to  be  separately  controlled. 

1313.4  Prescriptive  criteria:  These  prescriptive 
lighting  requirements  shall  be  used  with  780  CMR 
1313.2  and  1313.3.  780  CMR  1313.5  may  be  used 
instead  of  780  CMR  1313.4. 

1313.4.1  Interior  Lighting  Power  Limit  (ILPL) 
calculation:  Installed  adjusted  lighting  power, 
including  supplemental  or  task  lighting  provided 
by  fixtures  permanently  wired  in  place  but  not  by 
movable  fixtures  shall  comply  with  the  power 
limits  established  in  this  section.  To  establish  a 
lighting  power  allowance,  the  following 
procedure  shall  be  used: 

1.  Determine  the  space  use  categories  and 
Unit  Lighting  Power  Allowances  (ULPA)  for 
the  various  parts  of  the  building  from  Table 
1313.4.1.  If  a  space  use  intended  for  the 
building  is  not  listed  in  Table  1313.4.1,  then 
the  closest  related  building  or  space  type  listed 
in  the  Table  shall  be  used. 

2.  Multiply  the  Unit  Lighting  Power 
Allowance    (ULPA)    for    each    space    use 


category  by  the  gross  floor  area  included  in 
that  space  use  category. 

3 .  Add  the  total  number  of  watts  for  each  area 
to  arrive  at  the  Interior  Lighting  Power  Limit 
(ILPL)  for  the  building. 

4.  In  all  cases  of  alterations  or  additions  to 
existing  buildings,  the  unit  lighting  power 
allowance  for  the  new  or  altered  area  shall  be 
calculated  by  combining  the  square  footage  of 
each  category  represented  in  such  alterations  or 
additions  with  the  total  square  footage  of  the 
respective  categories  of  the  building  within 
which  such  alterations  or  additions  are 
planned 

1313.4.2  Compliance  A  building  shall  be 
considered  in  compliance  with  780  CMR  1313.4 
if  the  interior  Adjusted  Lighting  Power  (ALP)  to 
be  installed,  as  determined  in  1313.3.1,  does  not 
exceed  the  Interior  Lighting  Power  Limit  (ILPL) 
for  the  building,  as  determined  in  1313.4.1, 

Table  1313.4.1 

UNIT  LIGHTING  POWER  ALLOWANCE 

(ULPA),  W/fC 

BUILDING  SIZE  RANGE.  Ft2 


BUILDING 

Less 

6,001 

15.001 

30,001 

50,001 

SPACE/TYPE 

than 

to 

to 

to 

or 

6.000 

15.00(i 

30,000 

50,000 

more 

Food  Service 

Fast  Food/Cafetena 

1.5 

1.4 

1.3 

13 

1.3 

Leisure  Dining/Bar 

2.2 

1.9 

1.7 

1.5 

1.4 

Offices 

1.9 

1.8 

1.7 

1.6 

1.5 

Retail 

Type  B  &  C; 

3.3 

2.8 

2.5 

2.3 

2.1 

Tvpe  D  &  EJ 

3.0 

2.5 

2.2 

2.0 

1.8 

Mall  Concourse  at 

multi-store  shop- 

ping centers 

1.4 

1.4 

1.3 

1.3 

1.2 

Garages  &  Basements 

03 

0.3 

02 

0.2 

0.2 

Schools 

Pre-High  School 

1.8 

1.8 

1.7 

1.6 

1.5 

High  School/ 

Technical 

2.0 

2.0 

2.0 

1.9 

1.8 

University 

Warehouse/Storage 

0.8 

0.6 

05 

0.5 

0.4 

Factor.  &  Workshop 

1  2 

1.1 

1.0 

1  < 

1.0 

Notes: 

1  Includes  general  merchandising  and  display  lighting. 

2  Type  B  &  C  Retail:  Fme  Merchandising  and  Mass 
Merchandising. 

3  Type  D  &  E  Retail:  General  Merchandising  and  Food 
and  Miscellaneous  Merchandising. 

4  General  lighting. 

1313.5  System  performance  criteria:  These  system 
performance  lighting  requirements  shall  be  used 
with  the  minimum  requirements  specified  in 
780  CMR  1313.2  and  1313.3.  The  prescriptive 
criteria  listed  in  780  CMR  1313.4  may  be  used 
instead  of  780  CMR  1313  5  (Note  that  if  780  CMR 
1313.5,  "System  Performance  Criteria",  is  employed, 
a  supplemental  computer  program,  available  through 


226 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


the  State  House  Bookstore  must  be  utilized/the 
detailed  materials  in  780  CMR  1315.5.1  thru 
1315.5.3  and  Table  1315.5.1  are  provided  here  for 
information  only  -  see  notes  1  and  2. 

NOTE(l): 

A  COMPUTER  SOFTWARE  PROGRAM,  LGTSTD 
(LIGHTING  STANDARD)  IS  AVAILABLE  TO 
PERFORM  780  CMR  1333.5  EVALUATION.  THIS 
PROGRAM  PERFORMS  PASS/FAIL  ANALYSIS. 

THE  LGTSTD  SOFTWARE  PROGRAM.  ALONG 
WITH  THE  ENl'STD  SOFTWARE  PROGRAM  (SEE 
780  CMR  13 14.5)  ARE  COMBINED  ON  A  SINGLE 
5'A"  FLOPPY  DISC  AND  THIS  DISC,  PLUS  A 
USER'S  MANUAL  FOR  BOTH  PROGRAMS,  ARE 
AVAILABLE  THROUGH  THE  STATE 
BOOKSTORE  (617)  727-2834. 

NOTE  (2): 

USE  OF  THE  LIGHTING  COMPLIANCE 
CALCULATION  COMPUTER  PROGRAM 
(LTGSTD21)  OF  THE  CODIFIED  VERSION  OF 
ASHRAE/IES  90.1-1989  "ENERGY  CODE  FOR 
COMMERCIAL  AND  HIGH-RISE  RESIDENTIAL 
BUILDINGS"  SHALL  BE  AN  ACCEPTABLE 
OPTION  FOR  DEMONSTARTING  COMPLIANCE 
WITH  THE  LIGHTING  REQUIREMENTS  OF 
780  CMR. 

NOTE  (3): 

780  CMR  1313.5.1  THROUGH  1313.2.3.  TABLE 
780  CMR  1313.5.2  AND  FIGURES  1313.5.1  AND 
1313.5.2  ARE  INFORMATIONAL  -  THE 
SUPPLEMENTAL  COMPUTER  SOFTWARE 
LGTSTD1  AND  LGTSTD2I  ARE  ''PASS/FAIL" 
EVALUATIONS. 

1313.5.1     Unit     power     density     procedure: 

Installed  Adjusted  Lighting  Power  (ALP), 
including  supplemental  or  task  related  lighting 
provided  by  movable  fixtures  shall  comply  with 
the  power  allowances  established  in  780  CMR 
1313.5. 

1313.5.1.1  The  Lighting  Power  Budget  (LPB) 
of  each  interior  space  shall  be  determined  in 
accordance  with  equation  1313.5.1. 

Equation  1313.5.1 
LPB  =  A  X  Pb  XAF  where: 

LPB  =  Lighting  power  budget  of  the  space,  watts 

A  =  Area  of  the  space,  ft 

Pb  =  Base  UPD,  w/ft2  (Table  1313.5.1) 

AF  =  Area  factor  of  the  space  (Figure  1313.5.1) 

1 .  The  Room  Area  (A)  shall  be  calculated  from 
the  inside  dimensions  of  the  room. 


2.  The  Base  UPD  (Pb)  shall  be  selected  from 
Table  1313.5.1.  For  applications  to  areas  or 
activities  other  than  those  given,  select  values  for 
similar  areas  or  activities. 

3.  The  Area  Factor  (AF)  shall  be  determined 
from  Figure  1313.5.1  based  on  the  room  area  and 
ceiling  height.  Rooms  of  identical  ceiling  height 
and  activities  may  be  listed  as  a  group.  The  AF  of 
a  group  of  rooms  shall  be  determined  from  the 
average  area  of  these  rooms. 

1313.5.1.2  Special  Spaces  and  Activities 

1.  Multi-Function  Rooms.  For  rooms 
serving  multi-functions,  such  as  hotel 
banquet/meeting  rooms  and  office 
conference/presentation  rooms,  a  sup- 
plementary lighting  system  with 
independent  controls  may  be  installed.  The 
installed  power  for  the  supplementary 
system  shall  not  be  greater  than  50%  of  the 
base  LPB  calculated  in  accordance  with 
7S0CMR  1313.5.1.1. 

2.  Simultaneous  Activities.  In  rooms 
containing  multiple  simultaneous  activities 
such  as  a  large  general  office  having 
separate  accounting  and  drafting  areas 
within  the  same  room,  the  LPB  for  the 
rooms  shall  be  the  weighted  average  of  the 
activities  in  proportion  to  the  areas  being 
served. 

1313.5.2  The  Interior  Lighting  Power  Limit 
(ILPL)  shall  include  a  0.31  W/ft2  allowance  for 
unlisted  space  areas.  The  ILPL  shall  be  calculated 
in  accordance  with  equation  1313.5.2. 

Equation  1313.5.2: 
HPL=LPB(Listed  SpacesJ+tUOW/ft^XtXJnlisted  Space) 

where: 

ILPL  =  Interior  Lighting  Power  Limit 

Unlisted  space  =  (LBA  -  Area  of  listed  spaces), 

ft2 

LBA  =  Lighting  Building  Area,  ft" 

LPB  =  Lighting  Power  Budget 

1313.5.3  Compliance:  A  building  shall  be 
considered  in  compliance  with  this  section  if  the 
interior  Adjusted  Lighting  Power  (ALP)  to  be 
installed  in  the  building,  as  determined  in 
780  CMR  1313.3.1,  does  not  exceed  the  Interior 
Lighting  Power  Limit  (ILPL)  for  the  building,  as 
determined  in  780  CMR  1313.5.2. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


227 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  1313.5.1 
BASE  UNIT  POWER  DENSITY  (UPD  FOR  AREA/ACTIVITY-W/FT2) 


AREA/ACTIVITY                                                    UPD 

NOTE 

COMMON  ACTIVITY  AREAS 

Auditorium 

1.6 

(a) 

Corridor 

0.9 

(b) 

Classroom/Lecture  hall 

2.0 

Elec/Mech  equipment  room 

General 

0.7 

(b) 

Control  rooms 

1.5 

(b) 

Food  Service 

Fast  food/Cafeteria 

1.3 

Leisure  dining 

2.5 

Bar/Lounge 

2.5 

(c) 

Kitchen 

1.4 

(<=) 

Recreation/lounge 

0.7 

Stair 

Active  traffic 

0.6 

Emergency  exit 

0.4 

Toilet  &  Washroom 

0.8 

Garage 

Auto  &  Pedestrian 

Circulation 

0.3 

Parking  area 

0.2 

Laboratory 

2.3 

OFFICE  CATEGORY  1 

(d) 

Enclosed  offices,  all  open  plan  offices  without  partitions  or  with  partitions  lower 

than  4.5  ft.  below  the  ceiling 

Reading,  typing  and  filing 

1.6 

(e) 

Drafting 

2.5 

(e) 

Accounting 

2.0 

(e) 

OFFICE  CATEGORY  2 

(d> 

Open  plan  offices  900  square  feet  or  larger  with  partitions  3.5  to  4.5  feet  below  the 

ceiling.  (Offices  less  than  900  square  feet  shall  use  Category  0 

Reading,  typing  and  filing 

1.9 

(b) 

Drafting 

2.9 

(b) 

Accounting 

2.4 

(b) 

OFFICE  CATEGORY  3 

(d) 

Open  plan  offices  900  square  feet  or  larger  with  partitions  higher  than  3.5  feet 

below  the  ceiling.  (Offices  less  than  900  square  feet  shall  use  Category  1) 

Reading,  typing  and  filing 

2.1 

(b) 

Drafting 

3.4 

(b) 

Accounting 

2.7 

(b) 

COMMON  ACTIVITY  AREAS 


Library 

Audio  visual 

1.1 

Stack  area 

1.5 

Card  file  and  cataloging 

1.6 

Reading  area 

1.9 

Lobby  (General) 

Reception  and  waiting 

1.0 

Elevator  lobbies 

0.8 

Atrium  (multi-story) 

First  3  floors 

0.7 

Each  additional  floor 

0.2 

Locker  room  and  shower 

0.8 

228 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


AREA/ACTIVITY 

UPD 

NOTE 

Conference/meeting  room 

1  8 

(a) 

Computer/office  equipment 

2.1 

Filing,  inactive 

1.0 

Mail  room 

1.8 

Shop 

(Non-industrial) 

2.5 

Machiner 

2.5 

Electrical/electronic 

1.6 

Painting 

2.3 

Carpentry 

1.2 

Welding 

Storage  and  Warehouse 

Inactive  storage 

0.3 

Active  storage,  bulky 

0.3 

Active  storage,  fine 

1.0 

Material  handling 

1.0 

Unlisted  space 

0.2 

SPECIFIC  BUILDINGS 

Airport,  Bus  and  Rail  Station 

Baggage  area 

0.8 

Concourse/Main  thruway 

0.9 

Ticket  counter 

2.5 

Waiting  and  Lounge  area 

1.2 

Bank 

Customer  area 

1  0 

Banking  activitv  area 

2.8 

Barber  and  Beautv  parlor 

2.0 

Church,  Synagogue.  Chapel 

Worship/Congregational 

2.3 

Preaching  and  Sermon/Choir 

2.7 

Dormitorv 

Bedroom 

1.0 

Bedroom  with  studv 

1.2 

Studv  hall 

1.8 

Fire  and  Police  Department 

Fire  engine  room 

0.7 

Jail  cell 

0.8 

Hospital/Nursing  Home 

Corridor 

1.3 

(b) 

Dental  suite/Exam /Trea! 

1.6 

Emergency 

2.3 

Laboratory 

1.9 

Loundg/Waiting  room 

0.9 

Medical  supplies 

2.4 

Nurserv 

2.0 

Nurse  station 

2.1 

Occu./Physical  therapy 

1.6 

Patient  room 

1.4 

Pharmacv 

1.7 

Radiology 

2.1 

Surgical  and  O.B.  Suites 

Genral  area 

2.1 

Operating  room 

7.0 

Recovery 

3.0 

Hotel/Conference  Center 

Banquet  room  /Multi-purpose 

2.4 

(a) 

Bathroom/Powder  room 

1.2 

Guest  room 

1.4 

Public  area 

1.1 

Exhibition  hall 

2.6 

Conference/Meeting 

1.8 

(a) 

Lobby 

1.9 

Reception  desk 

2.4 

Laundry 

Washing 

0.9 

Ironing  and  Sorting 

1.3 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


229 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


AREA/ACTIVITY 

UPD 

NOTE 

Museum  and  Gallery 

General  exhibition 

1.9 

Inspect/Restoration 

3.9 

Storage  (Artifacts) 

Inactive 

0.6 

Active 

07 

Post  Office 

Lobbv 

1.1 

Sortina 

2.1 

Service  Station/Auto  Repair 

1.0 

Theater 

Performance  arts 

1.5 

Motion  picture 

1.0 

Lobbv 

1.5 

Retail  Establishments- 

(Merchandising  and  Circulation  Area) 

Applicable  to  all  lighting,  including  accent  and  display  lighting,  installed  i 

area 


merchandisiing  and  circulation 


Type  A 

4.0 

(0 

TypeB 

3  2 

(I) 

TvpeC 

3.0 

(0 

TvpeD 

2.8 

(f) 

Type# 

2.6 

(f) 

Mall  concourse 

1.4 

Retail  support  areas 

Tailoring 

2.1 

Dressing/Fitting  rooms 

1.4 

INDOOR  ATHLETIC  AREAS 

Seating  Area.  All  Sports 

0.4 

(?) 

Badminton 

Club 

0.5 

Tournament 

0.8 

Basketball/Vollevball 

Intramural 

0.8 

College 

1.3 

Professional 

1.9 

Bowling 

Approach  area 

0.5 

Lanes 

11 

Boxing  or  Wrestling  (platform) 

Amateur 

2.4 

Professional 

4.8 

Gvmnasium 

General  exercising  and 

Recreation  onlv 

1.0 

Handball/Racquetball/Squash 

Club 

1.3 

Toumment 

2.6 

Hockey,  ice 

Amateur 

1.3 

College  or  Professional 

2.7 

Skating  Rink 

Recreational 

0.6 

Exhibition/Professional 

2.7 

Swimming 

Recreational 

0.9 

Exhibition 

1.5 

Tennis 

Recreational  (Class  III) 

1.3 

Club/College  (Class  II) 

1.9 

Professional  (Glass  I) 

2.7 

Tennis,  Table 

Club 

1.0 

Toumment 

1.6 

230 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  ST.ANDARDS 

ENERGY  CONSERVATION 

Notes: 

(a)  A  1.5  adjustment  factor  is  applicable  for  multi-functional  spaces. 

(b)  Area  Factor  of  1.0  shall  be  used  for  these  spaces. 

(c)  Base  UPD  includes  lighting  power  required  for  clean-up  purpose. 

(d)  Not  less  than  90%  of  all  work  stations  shall  be  individually  enclosed  with  partitions  of  at  least  the  height 
described. 

(e)  Area  Factor  shall  not  exceed  1.55. 

(f)  See  Chapter  2  for  definitions  of  Retail  Facilities. 

(g)  Area  Factor  of  1 .0  shall  be  used  for  all  indoor  athletic  spaces. 


Figure  1313.5.1 
AREA  FACTOR  ADJUSTMENTS 


< 
o 
u. 

CO 

a 
< 

1 

\  :    \      \    : 

\j 

\p. 

1    7  j 

V      \!      V 

\ 

v     V      \       K 

S^o 

1 

\      l\        :\       1    \ 

sj 

1 

\ 

A1  \;  X  .  x- 

'ft, '           1 

r**^o 

^Ov       ' 

r~-\ 

\    \           \,l\ 

:^^-Ce 

ling    Height 

v 

v    Vl\      ^     X 

•^                  ^~~- 

1 

i 

\  \  \i,0     i\  : 

>*--^J 

"~^--^_ 

.    _  ! 

M  \  *<     !        >-. 

^_       p-- 

~-^_ 

"       ~— , 

-> 

\^  \^_~- — . 

__: 

"-^-^^  T— 

1          "~- 

1 

1.  o  : 

;                !                ! 

1 

0 

100 

200       3C0       400       500 

600      700 

800        900      100C 

Figure  1313.5.2 
AREA  OF  SPACE  (ft2) 


i.e 

1  .6 

£    1.5 
< 

3     '  ■ A 

8    1"3 

< 

1.2 
1.1 
1.0 

\      >\        ! 

'    .     \    l\ 

\      \i     \ 

«     l\      V       V 

— tCe     ■■     no    Hei  ah; 

o   !\     X      K 

5  A  i\  i  y. 

\    \  1     \ !       V 

t  :  \    Sj       V  .,.i  \ 

°  \   \i  \-?<     n-^^       r — -~^l 

*>    i  \     Nv?o  r*\  '         ^ .           ^~~~~~-^_ 

Z    f\\kX      >- 

•^.              i               — -— _ 

'          - 

T" -^__ 

nk  ^^^^-2 — —■— L 

8rv^>^rZr~; — _zr~2^~ 

0        1000     2000     3000    400C 

5000    6000    7000     8000 

9000    10 

300 

Area  Factor  Formula: 

Area  Factor  =  0.2  =  0.8  (1/0.9") 


where    W 


\0.2l(CH  -  2.5)  _ 


# 


A       =  Area  factor. 

CH   =  Ceiling  height  (ft). 

AT     =  room  area  (ft"). 

IfAF<1.0usel.0;ifAF>1.8use  1.8. 


9/19/97  (Effective  2/28/97)  -  corrected    7S0  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  1314.0    BUILDING  ENVELOPE 

REQUIREMENTS  FOR  COMMERCIAL 

AND  HIGH  RISE  RESIDENTIAL 

BUILDINGS 

1314.1  Scope:  780  CMR  1314.0  applies  to 
commercial  buildings  and  to  high  rise  residential 
buildings  over  three  stories. 

1314.2  Compliance:  The  envelope  design  of  a 
building  being  evaluated  is  in  compliance  with  the 
requirements  of  780  CMR  1314.0  provided  that: 

1.  The  minimum  requirements  and  calculation 
procedures  of  780  CMR  1314.3  are  met;  and, 

2.  Compliance  with  either  the  prescriptive 
criteria  (780  CMR  1314.4)  or  the  system 
performance  criteria  (780  CMR  13 14.5)  is  met. 

1314.2.1  The  prescriptive  criteria  (780  CMR 
1314.4)  provide  a  simple  calculation  procedure 
with  limited  flexibility.  The  system  performance 
criteria  (780  CMR  1314.5)  provide  a  more 
complex  and  lengthy  calculation  procedure  with 
greater  flexibility  usually  suitable  for  complex 
envelope  assemblies  in  larger  buildings. 

When  using  the  system  performance  criteria 
(780  CMR  1314.5)  a  computer-based  procedure, 
approved  by  the  State  Board  of  Building 
Regulations  and  Standards,  may  be  used  to 
calculate  the  exterior  envelope  compliance  values 

1314.3  Minimum  Requirements 

1314.3.1  Overall  thermal  transmittance  (Uo) 

The  overall  thermal  transmittance  of  building 
envelope  assemblies  shall  be  calculated  in 
accordance  with  Equation  1314.3.1: 

Uo  =  (UiAi  +  ...  UnAn)IAo 

where: 

Uo  =  the  average  thermal  transmittance  of  the 
gross  area  of  an  envelope  assembly,  e.g., 
the  exterior  wall  assembly,  including 
fenestration  and  doors;  roof  and/or 
ceiling  assembly,  or  floor  assembly, 
(Btu/h-ft2-°F). 

Ao  =  the  gross  area  of  the  envelope  assembly, 
(ft2). 

Ui  =  the  thermal  transmittance  of  each 
individual  element  of  the  envelope 
assembly,  e.g.,  the  opaque  portion  of  the 
wall  or  the  fenestration  -  see  780  CMR 
1314.3.2,  (Btu/h-ft2-°F). 

Ut  =  1/Rt,  the  total  resistance  of  the  envelope 
assembly,  (Btu/h-ft2-°F). 

A  =  the  area  of  each  individual  element  of  the 
envelope  assembly,  (ft  ). 

1314.3.2  Thermal  transmittance  (Ui)  of  an 
individual  element  of  an  envelope  assembly: 

The  thermal  transmittance  of  each  envelope 
assembly  shall  be  determined  accounting  for  all 
series  and  parallel  heat  flow  paths  through  the 


elements  of  the  assembly.  Compression  of 
insulation  shall  be  accounted  for  in  determining 
the  thermal  resistance. 

1314.3.2.1  The  thermal  transmittance  of 
opaque  elements  of  assemblies  shall  be 
determined  using  a  series  path  procedure  with 
correction  for  the  presence  of  parallel  paths 
within  an  element  of  the  envelope  assembly 
(such  as  parallel  paths  through  wall  cavities 
with  insulation  and  studs)  The  procedure  to  be 
used  in  meeting  the  requirements  of  780  CMR 

1 3 14.3.2. 1  is  given  in  Appendix  E. 

1314.3.2.2  The  thermal  transmittance  of 
fenestration  assemblies  shall  be  corrected  to 
account  for  the  presence  of  sash,  frames,  edge 
effects  and  spacers  in  multiple  glazed  units.  If 
thermal  transmittances  of  sash  and  frames  are 
known,  then  Equation  1314.3 . 1  shall  be  used 
for  calculation,  otherwise  Equation  1314.3.2 
shall  be  used: 

Equation  1314.3.2 
Uof=(Ug,l-Ff,l-Al=Ug,2-F£2-A2=...+Ug,n-Ffji-An) 

K 

Where: 

Uof  =  the  overall  thermal  transmittance  of  the 

fenestration   assemblies,   including   sash 

and  frames,  (Btu/h-ft  -°F). 
Ug     =  the  thermal  transmittance  of  the  central 

area  of  the  fenestration  excluding  edge 

effects,  spacers  in  multiple-glazed  units, 

and  the  sash  and  frame,  (Btu/h-ft  -°F). 
Ff     =  framing    adjustment    factor    for    sash, 

frames,  etc. 
Aof  =  the  area  all  fenestration  including  glazed 

portions,  sash,  frames,  etc.,  (ft  ). 
Values  for  Ug  shall  be  the  larger  of  the  winter  or 
summer  values  obtained  the  ASHRAE  Handbook, 
1993  Fundamentals  Volume.  Values  for  Ff  shall  be 
obtained  from  the  ASHRAE  Handbook,  1993 
Fundamentals  Volume.  Values  for  Ug  and  Ff  may 
also  be  obtained  from  manufacturer's  test  data  for 
specific  product  assemblies.  Where  a  range  of 
framing  adjustment  factors  is  provided,  the  average 
of  the  range  shall  be  used. 

1314.3.3  Shading  coefficients:  The  Shading 
Coefficient  (SC)  for  fenestration  shall  be  obtained 
from  the  ASHRAE  Handbook,  1993 
Fundamentals  Volume  or  from  manufacturers'  test 
data.  For  the  prescriptive  or  systems  performance 
envelope  compliance  calculations  in  780  CMR 
1314.4  and  1314  5  a  factor,  SCx,  is  used.  SCx  is 
the  Shading  Coefficient  of  the  fenestration, 
including  internal  and  external  shading  devices, 
but  excluding  the  effect  of  external  shading 
projections  which  is  calculated  separately.  The 
shading  coefficient  used  for  louvered  shade 
screens  shall  be  determined  using  a  profile  angle 


232 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


of  30°,  as  found  in  the  ASHRAE  Handbook,  1993 
Fundamentals  Volume. 

1314.3.4  Shell  buildings:  If  determination  of 
building  envelope  compliance  occurs  prior  to  the 
determination  of  lighting  power  density, 
equipment  power  density,  or  fenestration  shading 
device  characteristics,  then  the  following 
conditions  shall  be  assumed  when  determining 
building  envelope  compliance  by  either  the 
prescriptive  method  of  780  CMR  1314.4  or  the 
systems  performance  method  of  780  CMR  13 14.5. 

1.  Lighting  Power  Density  and  Equipment 
Power  Density:  For  780  CMR  13  14.4  the  total 
power  density  shall  be  assumed  to  be  those 
listed  in  Table  1314.3.4.  For  780  CMR  1314.5, 
the  values  in  Table  1314.4.3.4  shall  be 
apportioned  as  %  lighting  and  Vz  for  other 
equipment.  Note  that  these  are  not 
recommended  design  values,  but  are  for 
compliance  purposes  only. 

2.  Fenestration  shading  devices:  Only  those 
shading  devices  that  are  part  of  the  design 
when  it  is  being  evaluated  for  compliance  shall 
be  considered  when  determining  compliance. 

3.  Electric  lighting  controls  for  perimeter 
daylighting  utilization:  Only  those  controls 
that  are  part  of  the  design  when  it  is  being 
evaluated  for  compliance  shall  be  considered 
when  determining  compliance. 

Table  1314.3.4 

ASSUMED  COMBINED  LIGHTING  AND 

EQUTPMENT  POWER  DENSITIES  FOR 

SHELL  BUILDINGS 


LIGHTING  CONTROL 
TYPE 

FOR 

3000<HDD65 

>6000 

FOR 

HDD65> 

6000 

With  automatic  lighting 
controls  provided  for  the 
perimeter  area  to  be 
davliehted 

1.75  W/ft2 

1.50  W/ft2 

All  other  lighting  controls 

2.25  W/ft" 

1.50  W/ft" 

1314.4  Prescriptive  criteria: 

1314.4.1  Purpose:  780  CMR  1314.4  provides 
precalculated  prescriptive  requirements  for 
selected  exterior  envelope  configurations  of  new 
buildings.  There  are  four  different  sets  of 
precalculated  design  parameters,  including  a  base 
case  and  buildings  designed  with  perimeter 
daylighting,  with  high  performance  glazing  with 
perimeter   daylighting    or   with    increased   wall 


thermal  mass.  Any  one  set  of  parameters  will 
achieve  compliance. 

The  Alternate  Component  Packages  (ACP) 
provide  design  criteria  for  the  following: 

1.  "Base  Case  Buildings"  -  buildings  with 
envelopes  designed  without  perimeter 
daylighting. 

2.  "Perimeter  Daylighting  Buildings"  - 
buildings  which  are  allotted  additional 
fenestration  area  due  to  the  incorporation  of 
automatic  electric  lighting  controls  for  daylight 
utilization  in  the  perimeter  zones. 

Note:This  daylighting  credit  is  for  thermal 
benefits  of  daylighting  controls  on  the 
electric  lighting  system.  This  is  in  addition 
to  the  credit  provided  in  780  CMR  3 1 13  for 
the  reduction  in  lighting  energy. 

1314.4.2  Compliance:  The  basic  requirements 
and  procedures  of  780  CMR  1314.3  shall  be  used 
with  780  CMR  13 14.4.  The  systems  performance 
criteria  in  780  CMR  1314.5  may  be  used  instead 
of780CMR1314.4. 

The  envelope  design  of  the  building  being 
evaluated  is  in  compliance  with  the  prescriptive 
criteria  of  this  section  provided  that: 

1.  The  minimum  requirements  and  calculation 
procedures  of  780  CMR  1314.  are  met. 

2.  All  U  values  are  less  than  or  equal  to  those 
chosen  from  the  ACP  Table  selected. 

3.  All  R  values  are  greater  than  or  equal  to 
those  listed  in  the  ACP  Table  for  walls  below 
grade  and  for  slab-on-grade  floors. 

4.  The  percentage  of  fenestration  relative  to 
the  gross  external  wall  area  is  less  than  or 
equal  to  the  value  chosen  from  the  ACP  Table. 

Exception:  Portions  of  external  envelopes 
enclosing  atria  are  not  covered  by  the 
envelope  criteria  of  780  CMR  1 3 1 4.4  if  the 
atria  are  unconditioned  and  are  thermally 
isolated  from  conditioned  spaces. 

1314.4.3  Procedure  for  using  the  alternate 
component  package  (ACP):  The  prescriptive 
envelope  criteria  are  contained  in  Tables  1314.4.1 
through  1314.4.3. 

The  following  steps  shall  be  used  to  determine 
compliance  with  these  prescriptive  envelope 
criteria: 

1314.4.3.1  Determine  appropriate  ACP 
Table:  Based  upon  the  heating  degree  days 
(base  50)  of  Table  1305.2,  choose  the 
appropriate  ACP  Table  from  one  of  the  three 
ACP  Tables  found  on  the  following  pages. 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


233 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  1314.4.1 
ALTERNATE  COMPONENT  PACKAGES  FOR  HDD(1lasl,  ^  1751  -  2600 


INTERNAL 

PROJECTION 
FACTOR  (PF) 

Uof 

BASE  CASE 

PERIMETER 
DAYLIGHTING 

LOAD 
RANGE 

SHADING 
COEFF 

0.68 
to 

0.45 
to 

0.38 
to 

0.68 
to 

0.45 
to 

0.38 
to 

FOR  OPAQUE  WALLS 

RANGE 

0.46 

0.39 

0.0 

0.46 

0.39 

0,0 

0.00-  1.50 

0.000  -0.249 

1.000-0.71 

21 

24 

24 

22 

26 

27 

0.709  -  0.60 

25 

28 

30 

26 

31 

32 

0.599-0.50 

28 

33 

34 

29 

35 

37 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

31 

38 

40 

32 

40 

43 

HC<5) 

RANGE 

FEN 

INS 

INS 

0.379  -  0.25 

35 

46 

50 

36 

48 

53 

0.249-0.0 

41 

58 

65 

42 

59 

68 

0.250  -  0.499 

1.000  -0.71 

26 

30 

32 

27 

33 

34 

0.096 

HC;   5 

21 

0.10 

0.13 

0.709  -  0.60 

30 

36 

38 

31 

38 

41 

HCs  10 

21 

0.11 

0.15 

0.599-0.50 

33 

41 

44 

34 

43 

47 

HCs  15 

21 

0.12 

0.16 

0.499-0.38 

36 

46 

50 

36 

48 

53 

0.379-0  25 

40 

54 

60 

40 

56 

63 

HC>   5 
HC  >  10 

68 
68 

0.10 
0.11 

0.12 

0.500 

1.000-0.71 

31 

37 

40 

32 

40 

43 

0.14 

0.709  -  0.60 

34 

44 

47 

35 

46 

51 

HCs  15 

68 

0.12 

0.14 

0.599-0.50 

37 

49 

53 

38 

51 

57 

0.499-0.38 

40 

54 

60 

40 

56 

63 

1.51  -3.00 

0.00-0.249 

1.000-0.71 

17 

18 

18 

21 

24 

25 

0.709  -  0.60 

20 

22 

22 

25 

29 

31 

0.599-0.50 

22 

25 

26 

27 

33 

36 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

25 

30 

31 

30 

38 

42 

HC<5) 

RANGE 

FEN 

INS 

INS 

0.379-0.25 

30 

37 

39 

35 

45 

51 

0.249-0  00 

37 

49 

54 

41 

57 

67 

0.250-0  499 

1.000  -0.71 

21 

23 

24 

26 

31 

33 

0U96 

HC  j   5 

17 

0.10 

0.14 

0.709-0.60 

24 

28 

29 

29 

36 

40 

HCs  10 

17 

0.12 

0.17 

0.599-0.50 

27 

32 

34 

32 

41 

45 

HC2  15 

17 

0.13 

0.18 

0.499-0.38 

30 

37 

40 

35 

46 

52 

0.379-0.25 

35 

45 

49 

39 

53 

62 

HC2  5 
HCs  10 

67 
67 

0.10 
0.11 

0.12 

0.500 

1.000-0.71 

25 

29 

30 

30 

37 

41 

0.14 

0.709  -  0.60 

29 

35 

37 

34 

43 

49 

HC2  15 

67 

0.12 

0.15 

0.599-0.50 

32 

39 

42 

36 

48 

55 

0.499-0.38 

35 

45 

48 

39 

53 

62 

3.01  -3.50 

0.000-0.249 

1.000-0.71 

15 

16 

16 

20 

23 

25 

0.709  -  0.60 

17 

19 

20 

24 

28 

30 

0.599-0.50 

20 

22 

23 

26 

32 

35 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

23 

26 

27 

29 

36 

41 

HC<5) 

RANGE 

FEN 

INS 

INS 

0.379-0.25 

27 

33 

35 

34 

44 

50 

0.249  -  0  00 

34 

44 

48 

39 

55 

65 

0.250-0.499 

1.000-0.71 

18 

20 

21 

25 

29 

32 

0  096 

HC2  5 

15 

0.10 

0.14 

0.709  -  0.60 

22 

25 

25 

28 

35 

39 

HCi  10 

15 

0.12 

0.17 

0.599-0.50 

24 

28 

30 

31 

39 

44 

HC  >  15 

15 

0.14 

0.19 

0.499-0.38 

27 

33 

35 

34 

44 

51 

0.379-0.25 

32 

40 

43 

38 

51 

61 

HCi  5 
HCs  10 

65 
65 

0.10 
0.11 

0.12 

0.500 

1.000-0.71 

22 

25 

26 

29 

36 

40 

0.14 

0.709  -  0.60 

26 

30 

32 

32 

41 

48 

HC  2  15 

65 

0.12 

0.15 

0.599  -  0.50 

29 

35 

37 

35 

46 

54 

0.499-0.38 

32 

40 

43 

37 

51 

60 

|l  vt  >  sq 

■ 

Daylight 

Sensing 

LOCATIC 

)N 

MINIMUM 

LOCATION 

MINIMUI 

<A 

Wall  Below 

8 

Roof: 

0.060 

Grade: 

Wall  Adjacent  to 

Unhealed  S 

ab 

24"  36"    48" 

Unconditioned 

on  Grade: 

15    13       10 

Space: 

0.16 

Horizontal 

7      5       4 

Vertical 

Floor  Over  Un- 
conditioned 
Space: 

0  060 

234 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 

Table  1314.4.2 
ALTERNATE  COMPONENT  PACKAGES  FOR  HDD,,^,,^  2601  -  3200 


INTERNAL 

PROJECTION 
FACTOR  (PF) 

Uof 

BASE  CASE 

PERIMETER 
DAYLIGHTING 

LOAD 
RANGE 

SHADING 
COEFF 

0.68 
to 

0.45 
to 

0.38 
to 

0.68 
to 

0.45 

to 

0.38 
to 

FOR  OPAQUE  WALLS 

RANGE 

0.46 

0.39 

0.0 

0.46 

0.39 

0.0 

0.00-  1.50 

0.000  -  0.249 

1.000-0.71 
0.709  -  0.60 

21 
24 

25 
29 

26 
31 

22 
25 

26 
31 

27 
33 

0.599-0.50 

26 

33 

35 

27 

34 

37 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

29 

37 

40 

29 

3S 

42 

(HC<5) 

RANGE 

FEN 

INS 

INS 

0.379-0.25 

32 

43 

48 

32 

44 

SO 

0.249-0.0 

35 

52 

60 

35 

52 

60 

0.250  -  0.499 

1.000-0.71 

25 

31 

33 

26 

32 

35 

0.085 

HC2   5 

21 

0.096 

0.11 

0.709  -  0.60 

28 

36 

39 

28 

37 

41 

HCa  10 

21 

0.098 

0.12 

0.599  -  0.50 

30 

40 

44 

30 

41 

46 

HCi  15 

21 

0.10 

0.13 

0.499-0.38 

32 

44 

49 

32 

45 

51 

0.379-0.25 

35 

50 

57 

34 

50 

5S 

HCs   5 
HCa  10 

60 

60 

0.089 

0.095 

0.10 

0.500 

1.000-0.71 

29 

37 

40 

29 

39 

43 

0.11 

0.709  -  0.60 

31 

42 

47 

31 

43 

49 

HCa  15 

60 

0.099 

0.11 

0.599-0.50 

33 

46 

52 

33 

47 

53 

0.499-0.38 

35 

50 

57 

34 

50 

58 

1.51  -3.00 

0.00  -  0.249 

1.000-0.71 
0.709  -  0.60 

17 
20 

19 
23 

20 

24 

21 

24 

24 
29 

26 

31 

0.599  -  0.50 

22 

26 

28 

26 

32 

36 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

25 

30 

32 

28 

36 

41 

(HC<5) 

RANGE 

FEN 

INS 

INS 

0.379-0.25 

28 

37 

40 

31 

42 

49 

0.249-0.00 

33 

46 

52 

35 

51 

60 

0.250-0.499 

1.000-0.71 

21 

24 

25 

25 

31 

33 

0.085 

HC:    5 

17 

0.092 

0.12 

0.709  -  0.60 

24 

29 

31 

27 

35 

39 

HCi  10 

17 

0.10 

0.13 

0.599-0.50 

26 

33 

35 

29 

39 

44 

HCi  15 

17 

0.11 

0.14 

0.499  -  0.38 

29 

37 

40 

31 

43 

49 

0.379-0.25 

32 

43 

48 

34 

48 

56 

HCi   5 
HC2  10 

60 
60 

0.091 
0.098 

0.10 

0.500 

1.000-0.71 

25 

30 

32 

28 

36 

41 

0.12 

0.709  -  0.60 

27 

35 

38 

30 

41 

47 

HCi  15 

60 

0.10 

0.12 

0.599  -  0.50 

30 

39 

42 

32 

45 

52 

0.499-0.38 

32 

43 

48 

34 

48 

57 

3.01  -3.50 

0.000  -  0.249 

1.000-0.71 
0.709  -  0.60 

15 
18 

17 
20 

17 
21 

20 
23 

24 
28 

26 
31 

0.599-0.50 

20 

23 

25 

25 

32 

35 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

23 

27 

29 

27 

35 

40 

(HC<5) 

RANGE 

FEN 

INS 

INS 

0.379-0.25 

26 

33 

36 

30 

41 

48 

0.249-0.00 

31 

42 

47 

34 

50 

59 

0.250-0.499 

1.000-0.71 

19 

22 

22 

24 

30 

33 

0.085 

HC>  5 

15 

0092 

0.12 

0.709-0.60 

22 

26 

27 

26 

34 

39 

HC>  10 

15 

0.10 

0.14 

0.599-0.50 

24 

29 

31 

28 

38 

43 

HC>  15 

15 

0.11 

0.15 

0.499-0.38 

26 

33 

36 

30 

42 

48 

0.379-0.25 

30 

39 

43 

33 

47 

56 

HC>  5 
HC>I0 

59 
59 

0.090 
0.097 

0.10 

0.500 

i.000-0.71 

22 

27 

28 

27 

35 

40 

0.12 

0.709-0.60 

25 

31 

33 

29 

40 

46 

HC>  15 

59 

0.10 

0.12 

0.599  -  0.50 

27 

35 

38 

31 

43 

51 

0.499-0.38 

30 

39 

43 

33 

47 

56 

||  VT  >  SC  | 

Daylight 

Sensing 

Control's 

LOCAT1C 

)N 

MINIMUM 
R- VAT  TIF 

LOCATION 

MINIMUM 
Uo 

Wall  Below 

9 

Roof: 

0.056 

Grade: 

Wall  Adjacent  to 

Unhealed  S 

ab 

24"     36"     48" 

Unconditioned 

on  Grade: 

16      13       10 

Space: 

0.14 

Horizontal 

7       6       4 

Vertical 

Floor  Over 
Unconditioned 
Space: 

0.051 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


2?  5 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  1314.4.3 
ALTERNATE  COMPONENT  PACKAGES  FOR  HDD  ,w„<m  3201  -  4000 


INTERNAL 

PROJECTION 
FACTOR  (PF) 

Uof 

BASE  CASE 

PERIMETER 
DAYLIGHTING 

\SSAD 
VQUEV 

LOAD 
RANGE 

SHADING 
COEFF 

0.68 
to 

0.45 
to 

0.38 
to 

0.68 
to 

0.45 
to 

0.38 
to 

FOR  OP; 

/ALLS 

RANGE 

0.46 

0.39 

0.0 

0.46 

0.39 

0.0 

0.00-  1.50 

0.000  -  0.249 

1.000-0.71 
0.709  -  0.60 

20 
22 

25 
29 

26 
31 

20 
22 

26 

29 

27 
32 

0.599-0.50 

24 

32 

35 

23 

33 

36 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

25 

35 

39 

25 

35 

39 

TTC<5) 

RANGE 

FEN 

INS 

INS 

0.379  -  0.25 

27 

39 

45 

26 

38 

44 

0.249-0.0 

28 

44 

52 

28 

43 

51 

0.250-0.499 

1.000-0.71 

23 

31 

33 

23 

31 

34 

0.077 

HC>   5 

20 

O.OSO 

0.099 

0.709  -  0.60 

25 

34 

38 

25 

34 

39 

HCi  10 

20 

0.087 

0.11 

0.599  -  0.50 

26 

37 

42 

25 

37 

42 

HC  s  15 

20 

0.092 

0.11 

0.499-0.38 

0.379-0.25 

27 
28 

40 
43 

46 
51 

26 

39 

45 

27 

42 

49 

HCi   5 
HCi  10 

52 
52 

0.080 
0.085 

0095 

0.500 

1.000-0.71 

26 

36 

40 

25 

36 

41 

0.10 

0.709  -  0.60 

27 

39 

44 

26 

39 

45 

HC2  15 

52 

0.089 

0.10 

0.599-0.50 

28 

41 

48 

27 

41 

47 

0.499-0.38 

28 

43 

51 

28 

42 

50 

1.51  -3.00 

0.00  -  0.249 

1.000-0.71 
0.709  -  0.60 

17 
19 

20 
24 

21 
25 

20 

22 

24 
28 

26 
31 

0.599-0.50 

21 

27 

29 

23 

31 

34 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

23 

30 

33 

25 

34 

38 

TTC<5) 

RANGE 

FEN 

INS 

INS 

0.379  -  0.25 

26 

35 

39 

26 

38 

44 

0.249-0.00 

29 

42 

48 

29 

43 

51 

0.250-0.499 

1.000-0.71 

20 

25 

27 

22 

29 

33 

0.077 

HC2  5 

17 

0.081 

0.10 

0.709  -  0.60 

23 

29 

31 

24 

33 

37 

HC*  10 

17 

0.089 

0.12 

0.599-0.50 

24 

32 

35 

25 

36 

41 

HCi  15 

17 

0.096 

0.12 

0.499  -  0.38 

26 

35 

39 

27 

38 

44 

0.379-0.25 

28 

40 

45 

28 

42 

49 

HC2  5 
HCi  10 

51 

51 

0.080 
0.085 

0.096 

0.500 

1.000-071 

23 

30 

32 

25 

34 

39 

0.10 

0.709  -  0.60 

25 

34 

37 

26 

37 

43 

HC2  15 

51 

0.089 

0.11 

0.599-0.50 

27 

37 

41 

27 

39 

46 

0.499-0.38 

28 

40 

45 

28 

42 

49 

3.01  -3.50 

0.000  -  0.249 

1.000-071 
0.709  -  0.60 

16 
18 

18 
21 

19 

22 

19 
21 

24 
27 

26 
30 

0.599-0.50 

20 

24 

26 

23 

30 

34 

Uow 

HC 

PCT 

INT 

EXT 

0.499-0.38 

22 

27 

30 

24 

33 

38 

;hc<5) 

RANGE 

FEN 

INS 

INS 

0.379  -  0.25 

24 

32 

36 

26 

37 

43 

0.249-0.00 

28 

39 

45 

29 

43 

51 

0.250  -  0.499 

1.000-071 

19 

23 

24 

22 

29 

32 

0.077 

HC2  5 

16 

0.081 

0.10 

0.709  -  0.60 

21 

26 

28 

24 

32 

37 

HCs  10 

16 

0.090 

0.12 

0.599  -  0.50 

23 

29 

32 

25 

35 

41 

HCi  15 

16 

0.098 

0.13 

0.499  -  0.38 

24 

33 

36 

26 

38 

44 

0.379-0.25 

27 

37 

42 

28 

41 

49 

HC2  5 
HCi  10 

51 
51 

0.080 
0.086 

0.097 

0.500 

1.000-0.71 

22 

27 

29 

24 

33 

39 

0.10 

0.709-0.60 

24 

31 

34 

26 

37 

43 

HCi  15 

51 

0.090 

0.11 

0.599  -  0.50 

25 

34 

38 

27 

39 

46 

0.499-0.38 

27 

37 

42 

28 

41 

49 

|  VT  2  SC| 

Daylight 

Sensing 

rnntmk 

LOCATK 

DN 

MINIMUM 
R-VAI.UF. 

LOCATION 

M 

INIMUM 
Uo 

Wall  Below 

10 

Roof: 

0.052 

Grade: 

Wall  Adjacent  to 

Jnheated  SI 

ab 

24"     36"     48" 

Unconditioned 

on  Grade: 

17      14      11 

Space: 

0.13 

Horizontal 

8       6       4 

Vertical 

Floor  Over 

Unconditioned 

Space: 

0045 

236 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


1314.4.3.2  Determine  the  Maximum  Allowable 
Percent  Fenestration:  Using  the  appropriate  ACP 
Table  as  determined  in  780  CMR  1314.4.3.1, 
determine  the  maximum  allowable  percent 
fenestration.  The  maximum  allowable  percent 
fenestration  is  the  total  area  of  fenestration 
assemblies  divided  by  the  total  gross  external  wall 
area,  considering  all  elevations  of  the  building. 
Determining  the  maximum  allowable  percent 
fenestration  requires  the  following  five  steps: 

STEP  1  Based  on  the  Internal  Load  Density 
(TLD)  for  the  design  building,  select  one  of  the 
three  Internal  Load  Ranges  as  the  point  of  entry  to 
the  tables.  Note:  for  ILD's  greater  than  3.5  Watts 
per  ft  ,  use  the  3.5  Watts  per  ft*  range.  Determine 
the  Internal  Load  Density  (ILD)  of  the  design 
building,  based  on  the  sum  of  the  Internal 
Lighting  Power  Allowance  (ILPA),  the 
Equipment  Power  Density  (EPD)  and  the 
Occupant  Load  Adjustment  (OLA),  as  shown  in 
Equation  1314.4.3.2.1 

ILD  =  ILPA  +  EPD  +  OLA 

Where:  The  Internal  Lighting  Power  Allowance 
(ILPA)  shall  be  either: 

1.  The  building  average  Internal  Lighting 
Power  Allowance  (ILPA)  of  the  design 
building  in  W/ft*  as  determined  from  780  CMR 
1313.4  (for  dwelling  units  within  high  rise 
residential  buildings  the  limit  is  0.0  W/ft2);  or 

2.  The  average  of  the  Lighting  Power  Budgets 
(LPB)  for  all  activity  areas  within  15  feet  of 
each  exterior  wall  based  on  the  prodecures 
specified  by  the  Systems  Performance  Criteria 
of  780  CMR  1313.5. 

The  Equipment  Power  Density  (EPD)  shall 
be  either: 

1.  The  building  average  receptacle  power 
density  selected  from  Table  1314.4.4  is  W/ft": 
or 

2.  The  actual  average  receptacle  power 
density  for  all  activity  areas  within  15  feei  of 
each  exterior  wall  in  W/ft  ,  considering 
diversity.  For  determining  compliance  in 
Tables  1314.4.1  through  13144.3,  the  actual 
average  receptable  power  densities  calculated 
by  this  method  that  exceed  1.0  W/ft2  shall  be 
limited  to  1.0  W/ft2. 


Table  1314.4.4 

AVERAGE  RECEPTACLE  POWER 

DENSITIES 


BUILDING  TYPE 

WATTS/FT" 

1 .  Assembly 

0.25 

2.  Office 

0.75 

3.  Retail 

0.25 

4.  Warehouse 

0.1 

5.  School 

0.5 

6  Hotel/Motel 

0.25 

7  Restaurant 

0.1 

8.  Health 

1.0 

9  Multi -family 

075 

The  Occupant  Load   Adjustment   (OLA) 
shall  be  either: 

1.  0.0  W/ft  :  this  recognizes  the  assumed 
occupant  sensible  load  of  0.6  W/ft  that  is  built 
into  the  ACP  tables:  or 

2.  A  positive  or  negative  difference  between 
the  actual  occupant  load  and  0.6  W/ft  if  the 
design  building  has  a  larger  or  smaller 
occupant  load. 

STEP  2.  Select  external  shading  projection 
factor  (PF).  If  no  external  shading  projections  are 
used  in  the  proposed  design,  select  the 
row/column  designated  Proj.  Factor  =0.0  If 
external  shading  projections  are  used,  determine 
the  average  projection  factor  on  window  area 
weighted  basis.  Then  select  the  appropriate 
column  in  the  ACP  Table  using  Equation 
1314.4.3.2.2. 

PF  =  PdJH 

Where: 

PF  =  External  shading  projection  factor 

Pd  =External  shading  projection  depth,  inches 

or  feet 

H  =  Sum  of  height  of  the  fenestration  and  the 
distance  from  the  top  of  the  fenestration 
to  the  bottom  of  external  shading 
projection  in  units  consistent  with  Pd. 

STEP  3  Select  the  Shading  Coefficient  of  the 
fenestration  (SCx)  including  internal,  integral  and 
external  shading  devices,  but  excluding  the  effect 
of  external  shading  projections  (PF).  Note:  This 
includes  curtains,  shades,  or  blinds.  Reference 
ASHRAE  Handbook,  1993  Fundamentals 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


237 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


STEP  4.  Select  one  of  the  daylighting  options, 
either: 

1 .  Base  Case,  no  daylighting 

2.  Perimeter  Daylighting  (automatic  daylight 
controls  for  lighting  system  must  be  used). 

STEP  5  Select  appropriate  fenestration  type.  For 
most  options,  this  is  determined  by  the  thermal 
transmittance  value  (Uof)  of  the  fenestration 
assemble.  For  the  high  performance  fenestration 
options  (the  far  right  column  of  each  case),  the 
visible  transmittance  (VT)  of  the  fenestration 
should  not  be  less  than  the  shading  coefficient  of 
the  glazed  portion  of  the  fenestration  assemble, 
not  considering  any  shading  devices  The  ranges 
correspond  to  double  glazing,  triple  glazing,  and 
high  performance  glazing. 

1314.4.3.3  Determine  the  Maximum  Uow  for 
the  Opaque  Wall  Assembly:  In  the  appropriate 
ACP  Table  the  Maximum  Uow  for  the  opaque 
wall  assembly  is  determined  using  the 
applicable  following  steps  (Note  that  if  the 
wall  has  a  heat  capacity  of  5  BTU/ft  -°F  or 
greater,  the  "thermal  mass  adjustment" 
calculations  discussed  in  780  CMR  1314.4.3.3 
item  2,  allow  for  the  development  of  a  relaxed 
value  for  Uow): 

1.  For  a  lightweight  wall  assembly;  i.e.,  a 
wall  with  a  heat  capacity  (HC)  less  than  5 
BTU/ft  -°F,  use  the  value  indicated  under 
the  ACP  Table  column  labelled  Uow 
(HC<5).  This  Uow  is  constant  over  all 
internal  load  ranges. 

or 

2.  To  use  the  mass  wall  adjustment  (only 
for  walls  with  heat  capacities  of  5  BTU/ft  - 
"For  greater),  the  following  two  additional 
steps  are  necessary: 

A.  Select  the  same  internal  load  range  as 
that  used  in  determining  the  maximum 
allowable  percent  fenestration. 

B.  Select  the  mass  wall  heat  capacity 
(HC)  and  insulation  position.  If  the  wall 
insulation  is  positioned  internal  to  or 
integral  with  the  wall  mass,  use  the 
column  headed  Interior/Integral 
Insulation.  If  the  wall  insulation  is 
positioned  external  to  the  wall  mass,  use 
the  column  headed  Exterior  Insulation 
For  HC  less  that  5  BTU/ft2-°F,  this 
adjustment  table  cannot  be  used. 

3.  Select  or  interpolate  for  the  appropriate 
maximum  Uow  for  the  opaque  wall  based 
on  the  maximum  allowable  percent 
fenestration  determined  in  780  CMR 
1314.4.3.1  or  the  actual  building  percent 
fenestration  whichever  value  is  lower.  The 
Uow  shall  be  determined  by  straight  line 
interpolation  for  fenestration  percentages 
between  the  smallest  and  largest  values 
listed.   If  the  design  building  percentage 


fenestration  is  less  than  the  smallest  value 

listed,    select   the  Uow  for  the   smallest 

percentage  fenestration  listed.  If  the  design 

building  percentage  fenestration  is  greater 

than  the  largest  value  listed,  select  the  Uow 

for  the  largest  percentage  fenestration  listed. 

1314.4.3.4     Determine     Other     Envelope 

Criteria:  In  each  ACP  table,  the  criteria  for 

roof,  wall  adjacent  to  unconditioned  space, 

wall  below  grade,  floor  over  unconditioned 

space,  and  slab-on-grade  floors  shall  be  met 

For  heated  slabs-on-grade,  the  R-value  shall  be 

the  R-value  for  slab-on-grade  plus  R-2.0. 

1314.5  Systems  performance  criteria: 

1314.5.1  Purpose:  780  CMR  1314.5  provides  a 
systems  approach  to  envelope  compliance. 

1314.5.2  Compliance:  The  basic  requirements 
and  procedures  of  780  CMR  1314.3  shall  be  used 
with  780  CMR  13 14.5.  The  prescriptive  envelope 
criteria  in  780  CMR  1314.4  may  be  used  instead 
of  780  CMR  1314.5 

Note  that  portions  of  external  envelopes 
enclosing  atria  are  not  covered  by  the  envelope 
criteria  of  780  CMR  1314.5  if  the  atria  are 
unconditioned  and  are  thermally  isolated  from 
conditioned  spaces. 

NOTE  1:  A  COMPUTER  SOFTWARE 
PROGRAM,  ENT'STD  (ENVELOPE 
STANDARD)  IS  REQUIRED  TO  PERFORM 
780  CMR  1314.5  EVALUATION  (Certain 
data  is  only  available  in  the  libraries  of  the 
computer  software  program  and  are  not  found 
within  the  printed  780  CMR). 

THE  ENVSTD  SOFTWARE  PROGRAM, 
ALONG  WITH  THE  LTGSTD  SOFTWARE 
PROGRAM  (SEE  780  CMR  1313.5)  ARE 
COMBINED  ON  A  SINGLE  5Vi  "  FLOPPY 
DISC  AND  THIS  DISC,  PLUS  A  USER'S 
MANUAL  FOR  BOTH  PROGRAMS,  ARE 
AVAILABLE  THROUGH  THE  STATE 
BOOKSTORE  (617)  727-2834. 
NOTE  2:  THE  INFORMATION  PROVIDED 
EM  780  CMR  3 114.5.3  THROUGH  1314.5.8.6 
IS  ONLY  PRESENTED  TO  PROVIDE  THE 
READER  WITH  AN  OVERVIEW  OF 
ANALYSIS  TECHNIQUES  EMPLOYED  BY 
THE  ENVSTD  PROGRAM,  AND  SHOULD 
NOT  BE  UTILIZED  TO  PERFORM 
ANALYSIS  BY  HAND  -  THE  ENVSTD 
PROGRAM  MUST  BE  USED  FOR 
ANALYSIS  UNDER  780  CMR  1314.5  (THIS 
PROGRAM  PERFORMS  PASS/FAIL 
ANALYSIS). 

NOTE  3:  USE  OF  THE  ENVELOPE 
STANDARD  COMPUTER  PROGRAM 
(ENVSTD21)  OF  THE  CODIFIED  VERSION 
OF  ASHRAE/TES  90  1-1989  "ENERGY 
CODE  FOR  COMMERCIAL  AND  HIGH-RISE 


238 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


RESIDENTIAL  BUILDINGS"  SHALL  BE  AN 
ACCEPTABLE  OPTION  FOR 

DEMONSTRATING  COMPLIANCE  WITH 
THE  ENVELOPE  REQUIREMENTS  OF 
780  CMR.  ENVSTD21  ALSO  PERFORMS  A 
"PASS/FAIL"  ANALYSIS. 

1314.5.3  Roof  thermal  transmittance 
requirements:  Any  building  that  is  heated  and/or 
mechanically  cooled  shall  have  an  overall  thermal 
transmittance  value  (Uor)  for  the  gross  area  of  the 
roof  assembly  less  than  or  equal  to  the  value 
determined  by  Equation  1314.5.3.  The  provisions 
of  780  CMR  1314.3  shall  be  followed  in 
determining  acceptable  combinations  of  materials 
that  will  meet  the  required  Uor  values  of  Equation 
1314.5.3. 

Equation  13  14.5.3 
Uor=l/(5.3+1.8xl0"3xHDD65+1.3xl0"3xCDD65 
+2.6xl0x""*xCDH80) 

1314.5.3.1  Skylights  for  which  daylight  credit 
is  caken  may  be  excluded  from  the  calculation 
of  the  overall  thermal  transmittance  value 
(Uor)  of  the  roof  assembly,  if  all  of  the 
following  conditions  are  met: 

1.  The  opaque  roof  thermal  transmittance 
Uor  value  does  not  exceed  the  values 
determined  by  Equation  1314.5.3. 

2.  The  overall  thermal  transmittance  of  the 
skylight  assembly,  including  framing,  shall 
be  less  than  or  equal  to  0.7  Btu/h-ft"-°F. 

3.  Skylight  areas,  including  framing,  as  a 
percentage  of  the  roof  area  do  not  exceed 
the  values  specified  in  Tables  1314.5.3.1a 
and  1314.5.3.1b,  where  Visible 
Transmittance  (VT)  is  the  transmittance  of 
a  particular  glazing  material  over  the  visible 
portion  of  the  solar  .spectrum.  (Skylight 
areas  shall  only  be  interpolated  between 
visible  transmittance  values  of  0.75  and 
0.50). 

4.  The  skylight  area  for  which  daylight 
credit  can  be  taken  is  the  area  under  each 
skylight  whose  dimension  in  each  direction 
(centered  on  the  skylight)  is  equal  to  the 
skylight  dimension  in  that  direction  plus  the 
floor  to  ceiling  height. 

5.  Skylight  areas  that  have  already  taken 
daylight  credit  (perimeter  window  areas  or 
other  skylight  areas)  cannot  again  take 
daylight  credit. 

6.  All  electric  lighting  fixtures  within 
skylight  areas  shall  be  controlled  by 
automatic  daylighting  controls. 

7.  Skylight  curbs  shall  have  thermal 
transmittance  U  values  less  than  or  equal  to 
0.21  Btu/hr-ft2-°F. 

8.  The  infiltration  coefficient  of  the 
skylights  shall  be  less  than  or  equal  to  0.05 
cfm/ft2. 


Table  1314.5.3.1a 
MAXIMUM  PERCENT  SKYLIGHT  AREA 

(VT  =  0.75) 


LIGHT 

LEVEL 

INfc 

RANGE  OF  LIGHTING.P-OWER  DENSITY, 
W/fT 

<  1.0 

1.1  -  1.5 

1.6-2.0 

>2.0 

30 

2.3 

3.4 

4.5 

5.6 

50 

2.5 

4.0 

5.5 

7.0 

70 

2.S 

4.6 

6.4 

8.2 

Table  1314.5.3.1b 
MAXIMUM  PERCENT  SKYLIGHT  AREA 

(VT  =  0.50) 


LIGHT 

LEVEL 

INfc 

RANGE  OF  LIGHTING.POWER  DENSITY, 
W/ft" 

<1  0 

1.1  -  1.5 

1.6-2.0 

>2.0 

30 

3.6 

5.1 

6.6 

8.1 

50 

39 

6.0 

8.1 

10.2 

'0 

4 : 

6  9 

96 

12.3 

1314.5.3.2  Skylight  areas  in  Tables 
1314.5.3.1a  and  1314.5.3.  lb  may  be  increased 
by  50%  if  a  shading  device  is  used  that  blocks 
over  50%  of  the  solar  gain  during  the  peak 
cooling  design  condition. 

1314.5.3.3  Areas  for  vertical  glazing  in 
clerestories  and  roof  monitors  shall  be  included 
in  the  wall  fenestration  calculation. 

1314.5.4  Floor  thermal  transmittance  criteria: 

Any  building  that  is  heated  or  mechanically 
cooled  shall  have  floors  that  meet  the  following 
thermal  requirements: 

1.  Floors  of  conditioned  spaces  over 
unconditioned  spaces  shall  have  a  thermal 
transmittance  (Uof)  less  than  or  equal  to  that 
specified  in  Equation  1314.5.4: 

Equation  1314.5.4 
Uof  =  l/(0.840+0.00302xHDD65) 

2.  Slab-on-grade  floors  shall  have  insulation 
around  the  perimeter  of  the  floor  with  the 
thermal  resistance  (R)  of  the  insulation  as 
specified  in  Figure  1314.5.4.  The  insulation 
specified  in  Figure  13 14.5.4  shall  extend  either 
in  a  vertical  plane  downward  from  the  top  of 
the  slab  for  the  minimum  distance  shown  or 
downward  to  the  bottom  of  the  slab  then  in  a 
horizontal  plane  beneath  the  slab  for  the 
minimum  distance  shown.  The  horizontal 
length,  or  the  vertical  depth,  of  the  insulation 
required  varies  from  24  inches  to  48  inches 
depending  upon  the  R-value  selected.  For 
heated  slabs,  an  R  of  2  shall  be  added  to  the 
thermal  resistance  required  in  Figure  13  1 4.5.4. 

Vertical  insulation  shall  not  be  required  to 
extend  below  the  foundation  footing. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


239 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1314.5.5  Thermal  transmittance  requirements 
for  walls  below  grade:  For  walls  below  grade, 
the  thermal  resistance  calculated  in  accordance 
with  the  ASHRAE  Handbook,  1993 
Fundamentals  Volume  shall  be  greater  than  or 
equal  to  that  specified  in  Equation  1314.5.5: 

Equation  1314.5.5 
R  =  7.5  x  lCT4  HDD65  +  4.5 

1314.5.6  Thermal  transmittance  requirement 
for  opaque  walls  enclosing  conditioned  spaces 
exposed  to  interior  unconditioned  spaces:  All 

opaque  portions  of  walls  enclosing  conditioned 
spaces  exposed  to  interior  unconditioned  spaces 
shall  have  an  overall  thermal  transmittance  (Uow) 
not  greater  than  the  value  specified  in  Equation 
1314.5.6: 

Equation  1314.5.6 
Uow  =  0.0528  +  510.9/HDD65 

1314.5.7  External  wall  criteria  for  heating  and 
cooling:  The  external  wall  heating  criteria  (WCh) 
and  cooling  criteria  (WCc)  shall  be  determined  for 
a  building  envelope  design  per  the  cited  required 
software  program  discussed  in  780  CMR  13 14.5.2 
(For  additional  overview,  refer  to  ASHRAE 
STANDARD  90.1,  ENERGY  EFFICIENT 
DESIGN  OF  NEW  BUILDINGS  EXCEPT  NEW 
LOW-RISE  RESIDENTIAL  BUILDINGS). 

The  external  wall  heating  and  cooling  criteria 
are  determined  for  each  exterior  wall  orientation 
of  a  building  using  the  internal  load  range  as 
determined  in  780  CMR  1314.5.8.4  through 
1314.5.8.6. 

1314.5.8  Wall  heating  and  cooling  compliance 
values:  The  wall  heating  compliance  value  Hi  and 
the  wall  cooling  compliance  value  Ci  shall  be 
calculated  per  the  cited  required  software  program 
discussed  in  780  CMR  1314.5.2  (For  additional 
overview,  refer  to  ASHRAE  STANDARD  90.1, 
ENERGY  EFFICIENT  DESIGN  OF  NEW 
BUILDINGS  EXCEPT  NEW  LOW-RISE 
RESIDENTIAL  BUILDINGS). 

1314.5.8.1  Applying  the  criteria:  The  wall 
criteria  shall  be  applied  as  follows: 

1.  For  all  buildings  that  are  heated  and 
mechanically  cooled,  the  sum  ofthe 
calculated  wall  heating  (Hi)  and  cooling 
(Ci)  compliance  values  for  all  orientations 
of  the  proposed  design  as  determined  in 
780  CMR  1314.5.7  shall  not  exceed  the  sum 
of  the  corresponding  wall  heating  (WCh) 
and  wall  cooling  (WCc)  wall  criteria  for  all 
orientations  combined. 

2.  For  buildings  that  are  only  heated,  the 
sum  of  the  calculated  wall  heating 
compliance  values  (Hi)  for  all  orientations 
of  the  proposed  design,  as  determined  in 
780  CMR  1314.5.7,  shall  not  exceed  the 


sum  of  the  corresponding  wall  heating 
criteria,  (WCh)  criteria  for  all  orientations 
combined. 

1314.5.8.2  Constraints  on  thermal 
transmittance  values:  In  applying  the  wall 
criteria  as  described  in  780  CMR  1314.5.8.1 
two  constraints  are  imposed  on  thermal 
transmittance  values  for  opaque  wall 
assemblies  and  fenestration  assemblies 
comprising  the  Uo  term  as  follows: 

1.  Opaque  wall  assemblies:  The  opaque 
portion  of  walls  with  heat  capacity  (HC) 
less  that  7  Btu/ft  -°F  shall  have  an  overall 
thermal  transmittance  (Uow)  not  greater 
than  the  value  specified  in  equation 
1314.5.6. 

2.  Fenestration  Assemblies:  The  overall 
thermal  transmittance  (Uof)  of  fenestration 
assemblies  shall  be  less  than  or  equal  to 
0.81  Btu/ft2-h-°F  if  the  fenestration  area 
exceeds  10%  of  the  total  wall.  Thermal 
transmittance  for  the  fenestration  shall  be 
determined  using  the  calculation  procedures 
in  780  CMR  13 14.3.2  and  shall  include  the 
effects  of  sash,  frames,  edge  effects  and 
spacers  for  multiple-glazed  units. 

1314.5.8.3  Constraint  on  daylighting  credit: 
For  a  given  orientation,  daylight  credit  may  be 
used  in  the  ENVSTD  program  only  for  that 
portion  ofthe  fenestration  area  that  is  less  than 
or  equal  to  65%  ofthe  gross  wall  area  ofthe 
orientation. 

1314.5.8.4  Lighting  power  density:  The 
lighting  power  density  used  in  calculating  the 
compliance  value  shall  be  either: 

1 .  Building  average  unit  Interior  Lighting 
Power  Limit  in  W/ft  as  specified  by  the 
prescriptive  criteria  in  780  CMR  1313.4. 
(For  dwelling  units  in  high  rise  residential 
buildings,  if  Table  1314.4.1  is  used,  the 
limit  is"b.O  W/ft2). 

2.  Designed  building  average  lighting  Unit 
Power  Density  for  those  activity  areas 
within  15  feet  of  each  exterior  wall  based  on 
the  procedures  set  forth  by  the  system 
performance  criteria  in  780  CMR  1313.5. 

1314.5.8.5  Equipment  power  density:  The 
equipment  power  density  used  in  determining 
compliance  shall  be  either: 

1 .  The  "Average  Receptable  Power 
Densities"  from  Table  1314.4.1  or 

2.  The  actual  average  Equipment  Unit 
Power  Density,  considering  diversity  in  the 
activity  areas  within  15  feet  of  each  exterior 
wall,  not  to  exceed  1  W/ft*. 

1314.5.8.6  Loads  from  occupants:  Sensible 
load  from  occupants  is  assumed  to  be  0  6 
W/ft2.  Thus,  the  sensible  load  that  shall  be  used 
is  either  0.0  W/ft2  or  the  difference  between  0  6 
W/ft*  and  the  actual  sensible  load. 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  CONSERVATION 


780  CMR  1315.0  BUILDING  DESIGN  BY 
SYSTEMS  ANALYSIS 

1315.1  Scope:  780  CMR  1315.0  establishes  design 
criteria  in  terms  of  total  energy  use  by  a  building 
including  all  of  its  systems. 

1315.2  Compliance:  Compliance  with  780  CMR 
1315.0  is  optional  and  will  require  an  analysis  of  the 
annual  energy  consumption.  780  CMR  1307.0 
through  1312.0  establish  criteria  for  different  energy 
consuming  and  enclosure  elements  of  a  low  rise 
residential  building.  780  CMR  1307.0,  1308.0  and 
1310.0  through  1314.0  establish  criteria  for  different 
energy  consuming  and  enclosure  elements  of 
commercial  and  high  rise  residential  buildings. 
These  criteria  if  followed,  will  eliminate  the 
requirement  for  an  annual  energy  analysis  while 
meeting  the  intent  of  780  CMR  13. 

A  low  rise  residential  building  designed  in 
accordance  with  this  section  will  be  deemed  as 
complying  with  780  CMR  13  if  the  annual  energy 
consumption  is  not  greater  than  if  the  building  were 
designed  with  enclosure  elements  and  energy 
consuming  systems  in  compliance  with  780  CMR 
1307.0  through  1312.0. 

A  commercial  or  high  rise  residential  designed  in 
accordance  with  780  CMR  1315  0  will  be  deemed  as 
complying  with  780  CMR  13  if  the  annual  energy 
consumption  is  not  greater  than  if  the  building  were 
designed  with  enclosure  elements  and  energy 
consuming  systems  in  compliance  with  780  CMR 
1307.0,  780  CMR  1308.0  and  780  CMR  1310.0 
through  1314.0. 

1315.3  Standard  design:  The  standard  design, 
conforming  to  the  criteria  of  780  CMR  1308.0,  and 
the  proposed  alternative  design,  shall  be  designed  on 
a  common  basis  as  specified  herein.  The  comparison 
shall  be  expressed  as  Btu  input  per  square  foot  of 
gross  floor  area  per  year. 

Identical  energy  sources  must  serve  the  same 
purpose  in  both  the  standard  and  the  proposed 
alternative  design.  If  the  proposed  alternative  design 
results  in  an  increase  in  consumption  of  one  energy 
source  and  a  decrease  in  another  energy  source,  each 
energy  source  shall  be  converted  to  equivalent  Btu 
units  for  purposes  of  comparing  the  total  energy 
used. 

1315.4  Analysis  procedure:  The  analysis  of  the 
annual  energy  usage  of  the  standard  and  the 
proposed  alternative  building  and  system  design 
shall  meet  the  following  criteria: 

1.  The  building  heating/cooling  load  calculation 
procedure  used  for  annual  energy  consumption 
analysis  shall  be  of  sufficient  detail  to  permit  the 
evaluation  of  the  effect  of  the  factors  specified  in 
780  CMR  1315.4.1. 

2.  The  calculation  procedure  used  to  simulate  the 
operation  of  the  building  and  its  service  systems 
through  a  full  year  operating  period  shall  be  of 


sufficient  detail  to  permit  the  evaluation  of  the 
effect  of  system  design,  climatic  factors, 
operational  characteristics,  and  mechanical 
equipment  on  annual  energy  usage. 
Manufacturer's  data  or  comparable  field  test  data 
shall  be  used  when  available  in  the  simulation  of 
all  systems  and  equipment.  The  calculation 
procedure  shall  be  based  upon  8760  hours  of 
operation  of  the  building  and  its  service  systems 
and  shall  utilize  techniques  recommended  in  the 
ASHRAE  Handbook,  1993  Fundamentals 
Volume. 

1315.4.1  Calculation  procedure:  The  calculation 
procedure  shall  cover  the  following  items: 

1 .  Environmental  requirements  as  indicated  in 
780  CMR  1305.0. 

2.  Climatic  data:  coincident  hourly  data  for 
temperatures,  solar  radiation,  wind  and 
humidity  of  typical  days  in  the  year 
representing  seasonal  variation. 

3.  Building  data:  orientation,  size,  shape, 
transfer  characteristics  of  mass,  air,  moisture 
and  heat. 

4.  Operational  characteristics:  temperature, 
humidity,  ventilation,  illumination,  control 
sequence  for  occupied  and  unoccupied  hours. 

5.  Mechanical  equipment:  design  capacity, 
part  load  profile. 

6.  Internal  heat  generation  from  lighting, 
equipment,  number  of  people  during  occupied 
and  unoccupied  periods. 

7.  Electrical  equipment:  lighting,  power 
consumption. 

1315.4.2  Documentation:  Proposed  alternative 
designs,  submitted  as  requests  for  exception  to  the 
standard  design  criteria,  shall  be  accompanied  by 
an  energy  analysis  comparison  report  prepared  by 
a  professional  registered  engineer  or  registered 
architect.  The  report  shall  provide  sufficient 
technical  detail  on  the  two  buildings  and  systems 
designs,  and  on  the  data  used  in  and  resulting 
from  the  comparative  analysis,  to  verify  that  both 
the  analysis  and  the  designs  meet  the  criteria  of 
780  CMR  13.  The  documentation  shall 
demonstrate  that  the  analysis  used  is  consistent 
with  ASFfllAE  calculation  procedures  and 
accepted  engineering  practice. 

Exception:  Proposed  alternative  designs  for 
buildings  having  an  area  of  5,000  square  feet 
or  less  and  having  the  indoor  temperature 
controlled  from  a  single  point  are  exempted 
from  the  full  year  energy  analysis  as  described 
above.  A  comparison  of  energy  consumption 
between  the  alternative  design  and  the  standard 
design  shall  be  provided  in  a  report  prepared 
by  a  registered  professional  engineer  or 
architect.  Such  analysis  shall  follow  the  bin  or 
degree  day  methods  or  other  simplified 
analysis  procedures  consistent  with  accepted 
engineering  practice. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


241 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  1316.0  BUILDINGS  UTILIZING 

SOLAR,  GEOTHERMAL,  WIND,  OR 

OTHER  NONDEPLETABLE  ENERGY 

SOURCES  AS  ALTERNATIVE  DESIGNS 

1316.1  General:  When  a  proposed  alternative 
building,  submitted  in  accordance  with  780  CMR 
1315.0,  utilizes  solar,  geothermal,  wind,  or  other 
nondepletable  energy,  that  portion  supplied  to  the 
building  shall  be  excluded  from  the  total  energy 
chargeable  to  the  proposed  alternative  design. 

1316.2  Passive  solar  energy:  The  solar  energy 
passing  through  windows  shall  be  considered  if  there 
is  a  net  Btu/year  saving  over  fossil  fuel  or  electric 
energy  systems. 

1316.2.1  Nocturnal  cooling:  780  CMR  1316.0 
shall  also  apply  to  nocturnal  cooling  processes  in 
lieu  of  energy  consuming  processes. 

1316.2.2  Other  criteria:  All  other  criteria 
covered  in  780  CMR  1315.0  shall  apply  to  the 
proposed  alternative  designs  utilizing 
nondepletable  sources  of  energy. 

1316.3  Documentation:  Proposed  alternative 
designs,  submitted  as  requests  for  exception  to  the 
standard  design  criteria  shall  be  accompanied  by  an 
energy  analysis,  as  specified  in  780  CMR  1315.0. 
The  report  shall  provide  sufficient  technical  detail  on 
the  alternative  building  and  system  designs  and  on 


the  data  employed  in  and  resulting  from  the 
comparative  analysis  to  verify  that  both  the  analysis 
and  the  designs  meet  the  criteria  of  780  CMR  13. 
The  documentation  shall  demonstrate  that  the 
analysis  used  is  consistent  with  ASHRAE 
calculation  procedures. 

Exception:  Proposed  alternative  designs  that 
derive  over  50%  of  their  annual  thermal 
requirements  (heating,  cooling,  service  water 
heating)  or  over  30%  of  their  annual  total  energy 
requirements  from  nondepletable  sources  shall  be 
exempted  from  the  necessity  of  comparing  the 
proposed  design  to  a  standard  design. 
Documentation,  verifying  the  percentage  of 
annual  energy  use  derived  from  such 
nondepletable  sources  shall  be  required  as 
provided  in  780  CMR  1316.3  and  shall  be 
prepared  by  a  registered  professional  engineer  or 
architect. 

1316.3.1  Performance  data:  The  energy  derived 
from  nondepletable  sources  and  the  reduction  in 
conventional  energy  requirements  derived  shall  be 
separately  identified  from  the  overall  building 
energy  use.  Supporting  documentation,  on  the 
basis  of  the  performance  estimates  for  the 
aforementioned  nondepletable  energy  sources  or 
nocturnal  cooling  means,  must  be  submitted. 


242 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  14 


EXTERIOR  WALL  COVERINGS 


780  CMR  1401.0  GENERAL 
1401.1  Scope:  The  provisions  of  780  CMR  14  shall 
establish  the  minimum  requirements  for  exterior 
walls.       Exterior    walls    shall    be    designed    and 
constructed  in  accordance  with  780  CMR. 

780  CMR  1402.0  DEFINITIONS 
1402.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  14  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Exterior  wall  finish.  A  material  or  assembly  of 
materials  applied  on  the  exterior  side  of  exterior 
walls  for  the  purpose  of  providing  a  weather- 
resisting  barrier,  insulation  or  for  aesthetics, 
including  veneers,  siding,  exterior  insulation  and 
finish  systems,  architectural  trim  and 
embellishments  such  as  cornices,  soffits,  facias, 
gutters  and  leaders. 

Wall 

Apron  wall:   That  portion  of  a  skeleton  wall 

below  the  sill  of  a  window. 
Skeleton    or   panel   wall:    A   nonbearing   wall 

supported  by  each  story  on  a  skeleton  frame. 
Spandrel  wall:  That  portion  of  a  skeleton  wall 

above  the  head  of  a  window  or  door. 
Veneered    wall:    A   wall    having   a   facing   of 

masonry        or        other        weather-resistant 

noncombustible    material    that    is    securely 

attached  to  the  backing,  but  not  so  bonded  as  to 

exert  common  action  under  load. 

780  CMR  1403.0  PERFORMANCE 
REQUIREMENTS 

1403.1  General:  The  provisions  of  780  CMR  1403.0 
shall  apply  to  exterior  walls  and  components  thereof. 

1403.2  Durability:  All  exterior  walls  and 
components  thereof  shall  be  of  approved  materials 
which  maintain  the  performance  characteristics 
required  herein  for  the  duration  of  use. 

1403.3  Weather  resistance:  The  exterior  walls  shall 
be  faced  with  an  approved  weather-resistant 
covering  that  is  properly  attached  to  resist  wind  and 
rain.  The  cellular  spaces  shall  be  so  ventilated  as  not 
to  vitiate  the  firestopping  at  floor,  attic  and  roof 
levels,  or  shall  be  provided  with  an  approved  interior 
noncorrodible  vapor  relarder,  or  other  approved 
means  to  avoid  condensation  and  leakage  of 
moisture. 


1403.4  Structural:  Exterior  walls  shall  be  designed 
and  constructed  to  resist  safely  all  superimposed 
loads  as  required  by  780  CMR  16. 

1403.4.1  Structural  strength  against  wind 
forces:  In  all  buildings  required  to  resist  the  wind 
pressures  described  in  780  CMR  1611.0,  glazing 
in  exterior  window  openings  shall  be  designed  to 
resist  the  wind  loads  specified  in  780  CMR 
161 1.0  for  components  and  cladding. 

1403.4.2  Structural  strength  of  sash  or  frames: 

Mullions,  sash  and  frames  of  glazed  exterior 
window  openings  shall  be  designed  to  resist  the 
wind  loads  specified  in  780  CMR  1611.0  for 
components  and  cladding. 

1403.5  Fireresistance:  All  exterior  walls  shall 
comply  with  the  fireresistance  rating  requirements  of 
780  CMR  705.0. 

1403.5.1      Fireresistance      rated      openings: 

Openings  in  exterior  walls,  where  required  to 
have  a  fire  protection  rating,  shall  comply  with 
the  provisions  of  780  CMR  7. 

1403.6  Flood-resistant  construction:  Exterior  walls 
of  structures  that  are  erected  in  areas  prone  to 
flooding  shall  comply  with  the  provisions  of 
780  CMR  3107.0. 

1403.7  Ratproofing:  Exterior  walls  of  buildings  that 
are  required  to  be  ratproofed  shall  comply  with  the 
provisions  of  780  CMR  1215.0. 

780  CMR  14O4.0  MATERIALS 

1404.1  Wood:  Exterior  walls  of  wood  construction 
shall  be  designed  and  constructed  in  accordance  with 
780  CMR  23. 

1404.2  Masonry:  Exterior  walls  of  masonry 
construction  shall  be  designed  and  constructed  in 
accordance  with  780  CMR  2 1 . 

1404.3  Metal:  Exterior  walls  of  formed  steel 
construction  structural  steel  or  lightweight  metal 
alloys  shall  be  assigned  in  accordance  with 
780  CMR  22  and  780  CMR  20,  respectively. 

1404.4  Concrete:  Exterior  walls  of  concrete 
construction  shall  be  designed  and  constructed  in 
accordance  with  780  CMR  19 

1404.5  Structural  glass:  Exterior  walls  of  structural 
glass  block  shall  be  designed  and  constructed  in 
accordance  with  780  CMR  21 15.0. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


243 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1404.6  Plastics:  Plastic  panel,  apron  or  spandrel 
walls  as  defined  in  780  CMR  shall  not  be  limited  in 
thickness,  provided  that  such  plastics  and  their 
assemblies  conform  to  the  requirements  of  780  CMR 
26  and  are  constructed  of  approved  weather-resistant 
materials  of  adequate  strength  to  resist  the  wind 
loads  specified  in  780  CMR  161 1.0. 

1404.7  Other:  Materials  not  prescribed  herein  shall 
be  permitted  provided  that  any  such  alternative  has 
been  approved.  Exterior  walls  constructed  of 
alternative  materials  shall  be  shown  to  be  durable, 
weather  resistant,  structurally  adequate,  fireresistant, 
flood  resistant  and  ratproof  as  required  herein. 

780  CMR  1405.0  VENEERS 

1405.1  General:  All  veneers  consisting  of 
nonstructural  facing  of  brick,  concrete,  stone,  tile, 
metal,  plastic,  synthetic  stucco  or  other  approved 
exterior  coverings  attached  to  a  backing,  shall  be 
designed  and  constructed  in  accordance  with  the 
applicable  provisions  of  780  CMR  1405. 

1405.2  Structural  support:  Surfaces  to  which 
veneer  is  attached  shall  be  designed  to  support  the 
additional  loads  imposed  by  the  veneer. 

1405.2.1  Backing  surfaces  for  veneers:  Veneers 
for  other  than  buildings  of  Type  5  construction 
shall  be  attached  only  to  substantial,  rigid  and 
noncombustible  surfaces  which  are  plumb, 
straight  and  of  true  plane.  Wood  backing  surfaces 
shall  not  be  used,  except  in  buildings  of  Type  5 
construction.  The  backing  shall  provide  sufficient 
rigidity,  stability  and  weather  resistance,  and  the 
veneer  shall  be  installed  and  anchored  as  required 
in  780  CMR  for  the  specific  material. 

1405.3  Materials:  The  materials  of  the  minimum 
nominal  thickness  specified  in  Table  1405.3  shall  be 
acceptable  as  approved  weather  coverings. 

Table  1405.3 

MINIMUM  THICKNESS  OF  WEATHER 

COVERINGS 


Covering  type 


Minimum 
thickness 


Aluminum  siding 

0.019  inch 

Asbestos  cement  boards 

Va  inch 

Asbestos  shingles 

5/32  inch 

Brick  and  concrete  masonry  veneers 

2  inches 

Ceramic  veneer  (architectural  terra  cotta. 

1  inch 

anchored  type) 

Clay  tile  (flat  slab) 

V*  to  1  inch 

Clay  tile  (structural) 

\V*  inches 

Exterior  plywood  (with  sheathing)  5/16  inch 

Exterior  plywood  (without  sheathing)  See  780  CMR  2307.0 

Glass  fiber  reinforced  concrete  panels  a/a  jncn 

Hardboard siding  ,/  ■     , 


Covering  type 


Minimum 
thickness 


1  inch 
See  780  CMR  2308.5 
See  780  CMR  2308.5 

%  inch 

Vz  inch 

0.035  inch 

0.017  inch 

I  Vz  inches 
2  inches 
ti/32  inch 

7/e  inch 
%  inch 
%  inch 

'/iinch 
%inch 

%  inch 
Vz  inch 


Marble  slabs 

Particleboard  (with  sheathing) 

Particleboard  (without  sheathing) 

Precast  stone  facing 

Protected  fiber  board  siding 

Rigid  PVC  siding0 

Steel  (approved  corrosion-resistive) 

Stone  (cast  artificial) 
Stone  (natural) 
Structural  glass 

Stucco  or  exterior  portland  cement  plaster 
three-coat  work  over 
metal  plaster  base 
unit  masonry 
cast-in-place  or  precast  concrete 

Two-coar  work  over 

unit  masonry 

cast-in-place  or  precast  concrete 
Wood  shingles 
Wood  siding  (without  sheathing) 

Note  a.     For  wood  siding  of  a  lesser  thickness,  see 

780  CMR  1405.3.5. 

Note  b.  Exclusive  of  texture 

1405.3.1  Basic  hardboard:  Basic  hardboard  shall 
conform  to  the  requirements  of  AHA  A135.4 
listed  in  Appendix  A. 

1405.3.2  Hardboard  siding:  Hardboard  siding 
shall  conform  to  the  requirements  of  AHA  A 
135.6  listed  in  Appendix  A  and,  where  used 
structurally,  shall  be  so  identified  by  an  approved 
agency. 

1405.3.3  Rigid  PVC  siding:  Rigid  PVC  siding 
shall  conform  to  the  requirements  of  ASTM 
D3679  listed  in  Appendix  A. 

1405.3.4  Aluminum  siding:  Aluminum  siding 
shall  conform  to  the  requirements  of  AAMA  1402 
listed  in  Appendix  A. 

1405.3.5  Wood  siding:  Wood  siding  of 
thicknesses  less  than  Vz  inch  shall  be  placed  over 
sheathing  which  conforms  to  780  CMR  2305.13. 

1405.3.6  Building  paper:  Where  veneers  of 
brick,  clay  tile,  concrete  or  natural  or  artificial 
stone  are  used,  14-pound  felt  or  paper  shall  be 
attached  to  the  sheathing  with  flashing  wherever 
necessary  to  prevent  moisture  penetration  behind 
the  veneer. 

1405.3.7  Nailing:  All  weather  boarding  and  wall 
coverings  shall  be  securely  nailed  with  aluminum, 
copper,  zinc,  zinc-coated  or  other  approved 
corrosion-resistant  nails  in  accordance  with  the 
nailing  schedule  in  Table  2305.2  or  the  approved 
manufacturer's  installation  instructions.  Shingles 
and  other  weather  coverings  shall  be  attached 
with  appropriate  standard-shingle  nails  to  furring 
strips  securely  nailed  to  studs,  or  with  approved 
mechanically     bonding     nails,     except     where 


244 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

EXTERIOR  WALL  COVERINGS 


sheathing  is  of  wood  not  less  than  one-inch  nominal 
thickness  or  of  wood  structural  panels  not  less  than 
5/16  inch  thick.  Where  wood  shingles  or  shakes 
are  applied  over  fiberboard  shingle  backer  and 
fiberboard  sheathing,  such  shingles  or  shakes 
shall  be  attached  with  approved  corrosion- 
resistant  annular-grooved  nails  and  the  installation 
shall  be  done  in  accordance  with  the  approved 
manufacturer's  installation  instructions.  Where 
wood  shingles  or  shakes  and  asbestos  shingles  or 
siding  are  nailed  directly  to  nail  base  fiberboard 
sheathing,  the  sheathing  shall  not  be  less  than  V=- 
inch  nominal  thickness,  the  shingles,  shakes  and 
siding  shall  be  attached  with  approved  corrosion- 
resistant  annular-grooved  nails,  and  the 
installation  shall  be  done  in  accordance  with  the 
approved  manufacturer's  installation  instructions. 

1405.3.8  Metal  siding:  Exposed  metal  siding  or 
sheathing  shall  be  protected  from  corrosion  at  the 
ground  level  by  supporting  the  foundation  channel 
at  sufficient  height  above  grade  on  the  concrete 
aprcn  or  other  approved  water-resistant 
foundation. 

1405.3.9  Exterior  wall  pockets:  In  exterior  walls 
of  all  buildings  or  structures,  wall  pockets  or 
crevices  in  which  moisture  can  accumulate  shall 
be  avoided  or  protected  with  adequate  caps  or 
drips,  or  other  approved  means  shall  be  provided 
to  prevent  water  damage. 

1405.3.10  Flashings:  Approved  corrosion- 
resistant  flashings  shall  be  provided  at  the  top  and 
sides  of  all  exterior  window  and  door  openings  in 
such  a  manner  as  to  be  leakproof  Approved 
corrosion-resistant  flashings  shall  be  installed:  at 
the  intersection  of  chimneys  or  other  masonry 
construction  with  frame  or  stucco  walls,  with 
projecting  lips  on  both  sides  under  stucco 
copings;  under  and  at  the  ends  of  masonry,  wood 
or  metal  copings  and  sills;  continuously  above  all 
projecting  wood  trim;  at  the  intersection  of 
exterior  walls  and  porches  and  decks;  at  wall  and 
roof  intersections;  and  at  built-in  gutters. 

Exception:  When  approved,  flashing  is  not 
required  where  an  approved  water-resistant 
sheathing  is  installed  and  an  approved  water- 
resistant  caulking  is  applied  at  the  top  and 
sides  of  all  window  and  door  openings  in  such 
a  manner  as  to  be  leakproof. 

1405.4  Metal  veneers:  Veneers  of  metal  shall  be 
fabricated  from  approved  corrosion-resistant 
materials  or  shall  be  protected  front  and  back  with 
porcelain  enamel  or  shall  otherwise  be  treated  to 
render  the  metal  resistant  to  corrosion.  Such  veneers 
shall  not  be  less  than  0.017-inch  nominal  thickness 
galvanized  sheet  steel  mounted  on  wood  or  metal 
furring  strips  or  approved  sheathing  on  the  wood 
construction. 


1405.4.1  Construction:  Metal  veneer  for 
buildings  of  other  than  Type  5  construction  shall 
be:  securely  attached  to  masonry;  supported  on 
approved  metal  framing  protected  by  painting, 
galvanizing  or  other  approved  protection;  or 
supported  by  wood  furring  strips  treated  with  an 
approved  preservative  process  that  complies  with 
780  CMR  23 11.3. 

1405.4.2  Waterproofing:  All  joints  and  edges 
exposed  to  the  weather  shall  be  caulked  with 
approved  durable  waterproofing  material  or  by 
other  approved  means  to  prevent  penetration  of 
moisture. 

1405.4.3  Grounding  metal  veneers:  Grounding 
of  metal  veneers  on  all  buildings  shall  comply 
with  the  requirements  of  780  CMR  27  and  NFiPA 
70  listed  in  Appendix  A. 

1405.5  Anchored  masonry  veneer:  Anchored 
veneer  is  veneer  secured  with  approved  mechanical 
fasteners  to  an  approved  backing.  All  masonry 
units,  mortar  and  metal  accessories  used  in  anchored 
veneer  shall  meet  the  physical  requirements  of 
780  CMR  21.  Anchored  veneer  units  shall  not  be 
less  than  1%  inches  (41  mm)  in  actual  thickness  for 
solid  masonry  units  and  not  less  than  2%  inches  (67 
mm)  in  actual  thickness  for  hollow  masonry  units. 

1405.5.1  Height  of  anchored  veneer:  Anchored 
veneer  shall  be  supported  on  footings,  foundation 
walls  or  other  approved  noncombustible  structural 
supports  or  on  wood  foundations  meeting  the 
requirements  of  780  CMR  1808.3.  The  weight  of 
all  anchored  veneer  installed  on  structures  more 
than  30  feet  (9144  mm)  in  height  above  the 
noncombustible  foundation  or  support,  with  the 
exception  of  concrete  masonry  veneers,  shall  be 
supported  by  noncombustible  construction.  The 
construction  shall  have  horizontal  supports 
located  at  each  story  height  above  the  initial  30 
feet  (9144  mm). 

Exception:  Height  increases  are  permitted 
where  an  engineering  analysis  is  prepared  by  a 
registered  design  professional  and  approved. 

1405.5.2  Horizontal  supports:  Noncombustible 
lintels  and  noncombustible  supports  shall  be 
provided  over  all  openings.  Beams  and  lintels 
supporting  unreinforced  masonry  veneer  shall  not 
exceed  1/600  of  the  span  nor  0.3  inches  (8  mm). 

1405.5.3  Wood  frame:  Masonry  veneer  anchored 
to  wood  framing  shall  be  attached  with  corrosion- 
resistant  corrugated  sheet  metal  not  less  than 
0.029  inch  (No.  22  gage)  by  7/s  inch  wide,  or 
corrosion-resistant  ties  of  strand  wire  not  less  than 
0.148-inch  (No. 9  W&M  gage)  wire  with  the  ends 
of  the  wire  bent  to  a  90-degree  (1 .57  rad)  angle  to 
form  a  hook  not  less  than  two  inches  (5  1  mm) 
long.  The  metal  ties  shall  be  embedded  in  the 
mortar  joint  a  minimum  of  one-half  the  veneer 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


245 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


thickness.  Each  metal  tie  shall  support  not  more 
than  three  square  feet  (0.28  m2)  of  wall  area  with 
a  maximum  spacing  of  16  inches  (406  mm) 
vertically  and  32  inches  (813  mm)  horizontally. 
Where  anchored  veneer  is  applied  over  wood 
frame,  the  studs  shall  be  spaced  a  maximum  of  24 
inches  (610  mm)  on  center  and  be  faced  with 
sheathing  on  both  sides.  A  one-inch  (25  mm) 
minimum  air  space  shall  be  maintained  between 
the  anchored  veneer  and  the  sheathing.  Moisture 
protection  shall  be  provided  as  required  by 
780  CMR  1405.3.6. 

1405.5.4  Steel  frame:  Masonry  veneer  anchored 
to  corrosion-resistant  steel  framing  shall  be 
attached  with  corrosion-resistant  ties  of  strand 
wire  not  less  than  0. 148-inch  (No.  9  W&M  gage) 
wire  with  the  ends  of  the  wire  bent  to  a  90-degree 
(1.57  rad)  angle  to  form  a  hook  not  less  than  two 
inches  (51  mm)  long.  The  wire  ties  shall  be 
embedded  in  the  mortar  joint  a  minimum  of  one- 
half  the  veneer  thickness.  Each  metal  tie  shall 
support  not  more  than  2.67  square  feet  (0.25  m2) 
of  wall  area  with  a  maximum  spacing  of  16  inches 
(406  mm)  vertically  and  24  inches  (610  mm) 
horizontally.  Where  anchored  veneer  is  applied 
over  steel  frame,  the  studs  shall  be  spaced  a 
maximum  of  24  inches  (610  mm)  on  center  and  be 
faced  with  sheathing  on  both  sides.  A  one-inch 
(25  mm)  minimum  air  space  shall  be  maintained 
between  the  anchored  veneer  and  the  sheathing. 
Moisture  protection  shall  be  provided  as  required 
by  780  CMR  1405.3.6. 

1405.5.5  Masonry  or  concrete  walls:  Masonry 
veneer  anchored  to  masonry  or  concrete  walls 
shall  be  attached  with  corrosion-resistant  ties  of 
strand  wire  not  less  than  0.148-inch  (No.  9  W&M 
gage)  wire  with  the  ends  of  the  wire  bent  to  a  90- 
degree  (1.57  rad)  angle  to  form  a  hook  not  less 
than  two  inches  (51  mm)  long.  The  metal  ties 
shall  be  embedded  in  the  mortar  joint  a  minimum 
of  one-half  the  veneer  thickness.  Each  metal  tie 
shall  support  not  more  than  three  square  feet  (0.28 
m2)  of  wall  area  with  a  maximum  spacing  of  1 6 
inches  (406  mm)  vertically  and  32  inches  (813 
mm)  horizontally.  A  one-inch  (25  mm) 
minimum  air  space  shall  be  maintained  between 
the  anchored  veneer  and  the  supporting  masonry 
or  concrete  walls. 

1405.5.6  Stone  veneer:  Stone  veneer  units  not 
exceeding  ten  inches  in  thickness  are  permitted  to 
be  anchored  directly  to  masonry,  concrete  or  to 
stud  construction  by  one  of  the  following 
methods. 

1.  With  concrete  or  masonry  backing,  anchor 
ties  shall  not  be  less  than  No.  12  gage 
corrosion-resistant  wire  formed  beyond  the 
base  of  the  backing.  The  legs  of  the  loops  shall 
not  be  less  than  six  inches  (153  mm)  in  length 
bent  at  right  angles  and  laid  in  the  mortar  joint 
and  spaced  so  that  the  eyes  or  loops  are  12 


inches  (305  mm)  maximum  on  center  in  both 
directions.  There  shall  be  provided  not  less 
than  a  No.  12  gage  corrosion-resistant  wire  tie 
threaded  through  the  exposed  loops  for  every 
two  square  feet  (0.186  m2)  of  stone  veneer. 
This  tie  shall  be  a  loop  having  legs  not  less 
than  15  inches  (381  mm)  in  length  bent  so  that 
the  tie  will  lie  in  the  stone  veneer  mortar  joint. 
The  last  two  inches  (5 1  mm)  of  each  wire  leg 
shall  have  a  right-angle  bend.  One  inch  (25 
mm)  of  cement  grout  shall  be  placed  between 
the  backing  and  the  stone  veneer. 
2.  With  stud  backing,  a  two-inch  by  two-inch 
No.  16  gage  corrosion-resistant  wire  mesh  with 
two  layers  of  waterproof  paper  backing  shall 
be  applied  directly  to  wood  studs  spaced  a 
maximum  of  16  inches  (406  mm)  on  center. 
On  studs,  the  mesh  shall  be  attached  with  two- 
inch-long  (51mm)  corrosion-resistant  steel 
wire  furring  nails  at  four  inches  (102  mm)  on 
center  providing  a  minimum  1  Ve-inch  (28  mm) 
penetration  into  each  stud  and  with  8d  common 
nails  at  eight  inches  (200  mm)  on  center  into 
top  and  bottom  plates.  The  corrosion-resistant 
wire  mesh  is  permitted  to  be  attached  to  steel 
studs  with  equivalent  wire  ties.  There  shall  not 
be  less  than  a  No.  12  gage  corrosion-resistant 
wire,  looped  through  the  mesh  for  every  two 
square  feet  (0. 1 S6  m2)  of  stone  veneer.  This  tie 
shall  be  a  loop  having  legs  not  less  than  15 
inches  (38  mm)  in  length,  so  bent  that  the  tie 
will  lie  in  the  stone  veneer  mortar  joint.  The 
last  two  inches  (5 1  mm)  of  each  wire  leg  shall 
have  a  right-angle  bend.  One-inch  (25  mm) 
minimum  thickness  of  cement  grout  shall  be 
placed  between  the  backing  and  the  stone 
veneer. 

1405.5.7  Slab-type  veneer:  Slab-type  veneer 
units  not  exceeding  two  inches  (51  mm)  in 
thickness  are  permitted  to  be  anchored  directly  to 
masonry,  concrete  or  stud  construction.  For 
veneer  units  of  marble,  travertine,  granite  or  other 
stone  units  of  slab  form,  ties  of  corrosion-resistant 
dowels  in  drilled  holes  shall  be  located  in  the 
middle  third  of  the  edge  of  the  units  spaced  a 
maximum  of  24  inches  (610  mm)  apart  around  the 
perimeter  of  each  unit  with  not  less  than  four  ties 
per  veneer  unit.  Units  shall  not  exceed  20  square 
feet  (1.86  m2)  in  area. 

If  the  dowels  are  not  tight  fitting,  the  holes  are 
permitted  to  be  drilled  not  more  than  1/16  inch 
(1.6  mm)  larger  in  diameter  than  the  dowel  with 
the  hole  countersunk  to  a  diameter  and  depth 
equal  to  twice  the  diameter  of  the  dowel  in  order 
to  provide  a  tight-fitting  key  of  cement  mortar  at 
the  dowel  locations  when  the  mortar  in  the  joint 
has  set.  All  veneer  ties  shall  be  corrosion- 
resistant  metal  capable  of  resisting  in  tension  or 
compression  a  force  equal  to  two  times  the  weight 
of  the  attached  veneer. 


246 


780  CMR-  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

EXTERIOR  WALL  COVERINGS 


Sheet  metal  veneer  ties  shall  not  be  smaller  in 
area  than  No.  22  gage  by  one  inch.  Wire  veneer 
ties  shall  not  be  smaller  in  diameter  than  No.  9 
gage  wire. 

1405.5.8    Terra    cotta    or    ceramic    veneer: 

Anchored  terra  cotta  or  ceramic  units  not  less  than 
l5/8  inches  thick  are  permitted  to  be  anchored 
directly  to  masonry,  concrete  or  stud  construction. 
Tied  terra  cotta  or  ceramic  veneer  units  shall  not 
be  less  than  1%  inches  thick  with  projecting 
dovetail  webs  on  the  back  surface  spaced 
approximately  eight  inches  (203  mm)  on  center. 
The  facing  shall  be  tied  to  the  backing  wall  with 
corrosion-resistant  metal  anchors  of  not  less  than 
No.  8  gage  wire  installed  at  the  top  of  each  piece 
in  horizontal  bed  joints  not  less  than  12  inches 
(305  mm)  nor  more  than  18  inches  (457  mm)  on 
center.  These  anchors  shall  be  secured  to  '/4-inch 
corrosion-resistant  pencil  rods  which  pass  through 
the  vertical  aligned  loop  anchors  in  the  backing 
wall.  The  veneer  ties  shall  have  sufficient 
strength  to  support  the  full  weight  of  the  veneer  in 
tension.  The  facing  shall  be  set  with  not  less  than 
a  two-inch  (5 1  mm)  space  from  the  backing  wall 
and  the  space  shall  be  filled  solidly  with  portland 
cement  grout  and  pea  gravel.  Immediately  prior 
to  setting,  the  backing  wall  and  the  facing  shall  be 
drenched  with  clean  water  and  shall  be  damp 
when  the  grout  is  poured. 

1405.6  Adhered  masonry  veneer:  Adhered  veneer 
is  a  veneer  secured  and  supported  through  the 
adhesion  of  an  approved  bonding  material  applied  to 
an  approved  backing.  All  masonry  units  used  in 
adhered  veneer  walls  shall  meet  the  physical 
requirements  of  780  CMR  2 1 .  Adhered  veneer  units 
shall  be  less  than  1%  inches  thick  and  the  units  shall 
not  support  any  super-imposed  loads.  With  the 
exception-'of  ceramic  tile,  adhered  veneer  and 
backing  shall  be  designed  to  provide  a  bond  to  the 
supporting  element  sufficient  to  withstand  a  shearing 
stress  of  50  psi  (344  kPa)  after  curing  28  days. 

1405.6.1  Backing  surface:  Backing  permitted  for 
adhered  veneer  shall  be  continuous  and  shall  be  of 
any  approved  material.  The  backing  shall  have 
surfaces  prepared  to  secure  and  support  the 
imposed  loads  of  the  adhered  veneer. 

1405.6.2  Height  of  adhered  veneer:  Exterior 
adhered  veneer  shall  not  be  attached  to  wood 
frame  construction  at  a  point  more  than  30  feet 
(9144  mm)  in  height  above  the  noncombustible 
foundation.  Height  increases  are  permitted  where 


an  engineering  analysis  is  prepared  by  a 
registered  design  professional  and  approved. 

1405.6.3  Sizing  of  adhered  veneer:  Adhered 
veneer  units  shall  not  exceed  36  inches  (914  mm) 
in  the  greatest  dimension  nor  more  than  720 
square  inches  (0.46  m2)  in  total  area  and  shall  not 
weigh  more  than  15  pounds  per  square  foot  (73 
kg/mm2)  unless  approved. 

Exception:  Adhered  veneer  units  weighing 
less  than  three  pounds  per  square  foot  (15 
kg/mm2)  shall  not  be  limited  in  dimension  or 
area. 

1405.6.4  Construction:  Adhered  veneer  units 
shall  be  adhered  directly  to  the  backing  by  one  of 
the  following  methods. 

1.  A  paste  of  neat  portland  cement  shall  be 
brushed  on  the  backing  and  the  back  of  the 
veneer  unit.  Type  S  mortar  shall  then  be 
applied  to  the  backing  and  the  veneer  unit. 
Sufficient  mortar  shall  be  used  to  create  a 
slight  excess  to  be  forced  out  the  edges  of  the 
units.  The  units  shall  be  tapped  into  place  so 
as  to  fill  completely  the  space  between  the 
units  and  the  backing.  The  resulting  thickness 
of  mortar  in  back  of  the  units  shall  not  be  less 
than  Vz  inch  (13  mm)  nor  more  than  1%  inches 
(32  mm). 

2.  Units  of  masonry,  stone  or  terra  cotta,  not 
over  one  inch  in  thickness  shall  be  restricted  to 
81  square  inches  (0.052  m2)  in  area  unless  the 
back  side  of  each  unit  is  ground  or  box 
screened  to  true  up  any  deviation  from  plane. 
Those  units  not  over  two  inches  by  two  inches 
by  %  inch  in  size  are  permitted  to  be  adhered 
by  means  of  portland  cement.  Backing  shall  be 
of  masonry,  concrete  or  portland  cement 
plaster  on  metal  lath.  Metal  lath  shall  be 
fastened  to  the  supports  in  accordance  with  the 
requirements  of  780  CMR  25.  Mortar  that 
complies  with  Table  1405.6.4  shall  be  applied 
to  the  backing  as  a  setting  bed.  The  setting  bed 
shall  be  a  minimum  of  %  inch  (9  mm)  thick 
and  a  maximum  of  %  inch  (19  mm)  thick.  A 
paste  of  neat  portland  cement  or  half  portland 
cement  and  half  graded  sand  shall  be  applied  to 
the  back  of  the  exterior  veneer  units  and  to  the 
setting  bed  and  the  veneer  pressed  and  tapped 
into  place  to  provide  complete  coverage 
between  the  mortar  bed  and  veneer  unit.  A 
portland  cement  grout  shall  be  used  to  point  the 
veneer. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


247 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1405.6.4 
ADHERED  VENEER  SETTING  MORTAR 


Wall 

Coat 

Volume 
Type  I 
Portland 
cement 

Volume 
TypeS 
Portland 
hydrated 
lime 

Volume 
sand 

Maximum 
thickness 
of  coat 
(inches) 

Maximum 

interval 

between 

coats 

(hours) 

Area 

Dry 

Damp 

Walls 
over 

Scratch 

1 
1 

54 

0 

4 
3 

5 

4 

3/a 

24 
24 

ft. 

Float  or 
level- 

inc 

1 
1 

54 

1 

4 
6 

5 
7 

24 
24 

Walls 
10  sq. 
ft.  or 

less 

Scratch 
&  float 

1 

54 

254 

3 

% 

Va 

24 

Note  a.    one  inch  =  25.4mm;  one  sq.  Ft.  =  0.093m" 

1405.6.5  Adhered  ceramic  tile:  Adhered  veneer 
of  ceramic  tile  shall  be  bonded  to  the  backing  as 
provided  for  in  780  CMR  2105. 10. 

1405.6.6  Building  paper:  Adhered  veneer  over 
wood  frame  construction  shall  be  backed  by  solid 
sheathing  covered  with  14-pound  felt  building 
paper  as  required  by  780  CMR  1405.3.6. 

1405.7  Structural  glass  veneers:  The  minimum 
thickness  of  glass  veneer  shall  be  11/32  inch  and  the 
area  of  individual  panels  shall  not  exceed  ten  square 
feet  (0.93  m2),  with  a  maximum  length  of  four  feet 
(1219  mm).  The  edge  of  each  unit  shall  be  ground 
square  with  a  slight  arise.  All  exposed  external 
corners  and  angles  shall  he  rounded  to  a  radius  of 
not  more  than  3/16  inch  (5  mm). 

1405.7.1  Backing  surface:  The  glass  veneer  shall 
be  set  in  mastic  cement  on  a  float  coat  of  1 -inch- 
thick  (25  mm)  cement  mortar  reinforced  with  wire 
lath  attached  to  noncombustible  furring  spaced 
not  more  than  12  inches  (305  mm)  on  center. 

1405.7.2  Support  of  veneer:  The  base  course  of 
glass  units  shall  be  supported  on  a  corrosion- 
resistant  metal  frame  anchored  to  the  backing  and 
caulked  with  a  waterproof  compound  at  grade. 

1405.7.3  Reinforcement:  Metal  reinforcing  of 
cold-formed  corrosion-resistant  angles  of  not  less 
than  0.064-inch  nominal  thickness  galvanized 
sheet  steel  or  other  approved  reinforcement  shall 
be  provided  in  all  horizontal  joints  anchored  into 
the  masonry  wall  with  expansion  or  toggle  bolts. 

1405.7.4  Expansion  joints:  Expansion  joints 
shall  be  provided  at  ends  and  at  intermediate 
sections  which  are  caulked  with  an  approved 
waterproofing  compound.  Where  necessary  for 
water  tightness,  exposed  edges  shall  be  protected 
with  corrosion-resistant  metal  or  other  approved 
noncombustible  flashing. 

1405.7.5  Other  loads:  Signs,  awning  brackets  or 
other  loads  shall  not  be  hung  directly  from  glass 
veneers,    but    shall    be    supported    on    framing 


anchored  to  or  otherwise  supported  by  the 
masonry  wall,  free  from  contact  with  the  glass. 

780  CMR  1406.0  COMBUSTIBLE 

MATERIALS  ON  THE  EXTERIOR  SIDE 

OF  EXTERIOR  WALL 

1406.1  General:  780  CMR  1406.0  shall  apply  to 
exterior  wall  finish,  half-timbering,  balconies  and 
similar  appendages,  and  bay  and  oriel  windows 
constructed  of  combustible  materials  including  light- 
transmitting  plastic  panels  and  foam  plastic. 

1406.2  Combustible      exterior     wall      finish: 

Combustible  exterior  wall  finish  shall  be  tested  and 
installed  in  accordance  with  780  CMR  1406.2.1 
through  1406.2.4. 

Exceptions 

1.  Light-transmitting  plastic  panels  shall  be 
constructed  and  installed  in  accordance  with 
780  CMR  26. 

2.  Foam  plastic  installed  in  or  on  the  exterior 
side  of  walls  of  buildings  in  accordance  with 
780  CMR  2603.6  shall  not  be  required  to  comply 
with  780  CMR  1406.2.1  provided  that  the  foam 
plastic  is  protected  on  the  out  side  by: 

2.1.  A  thermal  barrier  complying  with 
780  CMR  2603.4; 

2.2.  A  minimum  one-inch  (25  mm)  thickness 
of  masonry  or  concrete; 

2.3.  A  minimum  Vs-inch  (22  mm)  thickness 
of  stucco  complying  with  780  CMR  2506.0; 

2.4.  A  minimum  0.019-inch  thickness  of 
aluminum;  or 

2.5.  A  minimum  0.016-inch  thickness  or 
corrosion-resistant  steel. 

1406.2.1  Radiant  heat  exposure:  Combustible 
exterior  wall  finish  shall  be  tested  for  exposure  to 
radiant  heat.  Test  specimens  shall  be  prepared  in 
accordance  with  780  CMR  1406.2. 1.1  and  tested 
in  accordance  with  780  CMR  1406.2.1.2.  The 
criteria  for  acceptance  shall  be  as  given  by 
780  CMR  1406.2.1.3. 

Exceptions:  The  testing  shall  not  be  required 

for: 

1 .  Wood  or  wood-based  products. 

2.  Other  combustible  materials  covered  with 
a  material  listed  in  Table  1405.3. 

3.  Aluminum  having  a  minimum  thickness  of 
0.019  inch. 

4.  Exterior  wall  finish  on  exterior  walls  of 
Type  5  construction. 

1406.2.1.1  Test  specimen:  The  test  specimen 
shall  be  constructed  to  reflect  the  end-use 
configuration.  Where  a  material  is  intended  to 
be  installed  in  more  than  one  thickness,  tests  of 
the  minimum  and  maximum  thickness  intended 
to  be  used  shall  be  performed.  Test  specimens 
shall  consist  of  a  minimum  four-foot-wide  by 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUTLDrNG  REGULATIONS  AND  STANDARDS 

EXTERIOR  WALL  COVERINGS 


eight-foot-high  assembly  which  shall  be 
mounted  in  a  vertical  position. 

1406.2.1.2  Test  exposure  and  apparatus:  The 
test  exposure  and  apparatus  shall  conform  to 
780  CMR  1406.2.1.2.1  through  1406.2.1.2.4. 

1406.2.1.2.1  Apparatus:  A  three-foot  by 
three-foot  propane-fired  radiant  panel  shall 
be  provided  and  shall  operate  at  a  constant 
temperature  of  1,600°F  (871  °C)  ±  50°F 
(28°C). 

1406.2.1.2.2  Configuration:  The  radiant 
panel  and  the  test  specimen  shall  be 
configured  in  a  parallel  plate  orientation 
such  that  the  axis  perpendicular  to,  and 
running  through,  the  center  of  the  radiant 
panel  face  and  the  test  specimen  are 
concurrent. 

1406.2.1.2.3  Heat  flux:  The  temperature  of 
the  radiant  heat  panel  shall  be  fixed  to 
produce  an  average  heat  flux  of  12.5  ±  5% 
kW/nr  over  the  center  square  foot  of  the  test 
assembly.  Average  heat  flux  shall  be 
determined  as  the  average  of  four 
calorimeter  readings  located  at  the  comers 
of  the  center  square  foot  of  the  test 
assembly. 

1406.2.1.2.4  Exposure:  The  four-foot  by 
eight-foot  test  specimen  shall  be  exposed  to 
a  "square  wave"  exposure  for  a  period  of  20 
minutes.  A  spark  igniter  shall  be  installed 
and  located  at  a  point  18  inches  vertically 
above  the  center  point  of  the  test  specimen 
and  s/a  inch  off  the  face  of  the  test 
specimen.  The  spark  igniter  shall  be 
operated  throughout  the  20-minute  test 
period.  If  the  spark  igniter  is  operated  in  an 
intermittent  mode,  the.  "off'  portion  of  the 
cycle  shall  not  be  longer  than  two  seconds 
and  the  "on"  portion  of  each  cycle  shall  be 
at  least  five  seconds  in  duration. 

1406.2.1.3  Conditions  of  acceptance: 
Materials  shall  qualify  for  installation  under 
the  provisions  of  780  CMR  1406.2.1.3.1  or 
1406.2.1.3.2. 

1406.2.1.3.1  Unrestricted  installation:  For 
any  fire  separation  distance,  an  assembly 
shall  be  acceptable  for  installation  in 
accordance  with  780  CMR  1406.0  and 
780  CMR  1405.0  and  2603.6  if,  during  the 
exposure  described  in  780  CMR  1406.2. 1.2, 
continuous  flaming  ignition  does  not  occur 
for  a  time  period  greater  than  five  seconds. 
Continuous  flaming  ignition  shall  be  judged 
to  occur  when  continuous  flaming  is 
visually  observed  by  laboratory  personnel 
for  greater  than  five  seconds. 

1406.2.1.3.2  Restricted  installation:  For 
fire  separation  distances  greater  than  five 
feet    (1524    mm),    an    assembly    shall    be 


permitted  with  increased  fire  separation 
distance  if  a  test  specimen  in  accordance 
with  780  CMR  1406.2.1.1,  while  being 
exposed  to  a  reduced  level  of  incident 
radiant  heat  energy  in  accordance  with 
780  CMR  1406.2.1.2,  meets  the  conditions 
of  acceptance  in  780  CMR  1406.2.1.3.1. 
The  minimum  fire  separation  distance 
required  for  the  assembly  shall  be 
determined  from  Table  1406.2.1.3.2  based 
on  the  maximum  tolerable  level  of  incident 
radiant  heat  energy  determined  by  780  CMR 
1406.2.1.3.2 

1406.2.2  Construction  requirements: 

Combustible   exterior  wall  finishr  other   than 

fireretardant-treated     wood      complying     with 

780  CMR  2310.0  for  exterior  installation,  shall 

not  exceed  10%  of  an  exterior  wall  surface  area 

where  the  fire  separation  distance  is  five  feet  or 

less.      In  buildings   of  Types    1,   2,    3    and   4 

construction,  all  architectural  trim  which  exceeds 

40  feet  ( 1 2 1 92  mm)  in  height  above  grade  plane 

shall  be  constructed  of  approved  noncombustible 

materials  and  shall  be  secured  to  the  wall  with 

metal  or  other  approved  noncombustible  brackets. 

Exception:      Foam     plastics,      installed     in 

accordance  with  780  CMR  2603.6,  as  required, 

shall  not  be  subject  to  these  limitations. 

Table  1406.2.1.3.2 

MINIMUM  FIRE  SEPARATION  DISTANCE 

FOR  COMBUSTIBLE  VENEERS  BASED 

ON  MAXIMUM  TOLERABLE  LEVEL  OF 

INCTDENT  RADIANT  HEAT  ENERGY 


Tolerable  level 

Tolerable  level 

Fire  Separation 

incident  radient 

Fire  separation 

incident  radiant 

Distance  (feet) 

heat  energy 

distance  (feet) 

heat  energy 

(kW/m2) 

(kW/m2) 

5 

12.5 

16 

5.9 

6 

11.8 

17 

5.5 

7 

11.0 

18 

5.2 

8 

10.3 

19 

4.9 

9 

9.6 

20 

4.6 

10 

8.9 

21 

4.4 

11 

8.3 

22 

4.1 

12 

7.7 

23 

3.9 

13 

7.2 

24 

3.7 

14 
15 

6.7 
6.3 

25 

3.5 

Note  a.    one  foot  =  304.8mm. 

1406.2.3  Location:  Where  combustible  exterior 
wall  finish  is  located  along  the  top  of  exterior 
walls,  such  trim  shall  be  completely  backed  up  by 
the  exterior  wall  and  shall  not  extend  over  or 
above  the  top  of  exterior  walls. 

1406.2.4  Firestopping:  Continuous  exterior  wall 
finish  constructed  of  combustible  materials  shall 
befirestoppedas  required  in  780  CMR  720.0. 

1406.3  Combustible  half-timbering:  In  buildings 
of  Types  3  and  4  construction  which  do  not  exceed 


2/7/9/    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


249 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


three  stories  or  40  ft  (12192  mm)  in  height  above 
grade  plane,  exterior  half-timbering  and  similar 
architectural  decorations  are  permitted  to  be 
constructed  of  wood  or  other  equivalent  combustible 
material,  provided  that  such  trim  is  backed  up 
solidly  with  approved  noncombustible  materials. 

1406.4  Balconies  and  similar  appendages:   All 

balconies,  porches,  decks  and  supplemental  exterior 
stairways  attached  to  or  supported  by  buildings  of 
Types  1  and  2  construction  shall  be  constructed  of 
approved     noncombustible     materials.  Such 

appendages  attached  to  or  supported  by  buildings  of 
Types  3,  4  and  5  construction  shall  be  of  either 
noncombustible  or  combustible  construction.  Such 
appendages  of  combustible  construction,  other  than 
fireretardant-treated  wood,  shall  afford  the 
fireresistance  rating  required  by  Table  602  for  floor 
construction  or  shall  be  of  Type  4  construction  as 
described  in  780  CMR  2304.0  and  the  aggregate 
length  shall  not  exceed  50%  of  the  building  diameter 
on  each  floor. 


Exceptions: 

1 .  Untreated  wood  is  permitted  for  pickets  and 
rails,  or  similar  guardrail  devices  which  are 
limited  to  42  inches  (1067  mm)  in  height. 

2.  Balconies  and  similar  appendages  on 
buildings  of  Types  3,  4  and  5  construction  shall  be 
permitted  to  be  of  Type  5  construction,  and  shall 
not  be  required  to  have  a  fireresistance  rating 
where  sprinkler  protection  is  extended  to  these 
areas. 

1406.5  Bay  and  oriel  windows:  A  bay  window  is  a 
window  that  projects  beyond  the  wall  line  of  a 
building  and  extends  down  to  the  foundation.  All 
bay  and  oriel  windows  attached  to  or  supported  by 
walls  in  other  than  buildings  of  Type  5  construction, 
shall  be  of  noncombustible  construction  and  be 
framed  with  brackets  of  steel,  concrete  or  other 
approved  noncombustible  materials. 


250 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  15 


ROOFS  AND  ROOF  STRUCTURES 


780  CMR  1501.0  GENERAL 

1501.1  Scope:  The  provisions  of  780  CMR  15  shall 
govern  the  materials,  design,  construction  and 
quality  of  roofs  and  roof  coverings. 

1501.2  Applicability:  All  roofs  and  roof  coverings 
shall  meet  either  the  performance  requirements  of 
780  CMR  1505.0  or  the  prescriptive  requirements  of 
780  CMR  1507.0. 

780  CMR  1502.0  DEFINITIONS 
1502.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  1 5  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Penthouse  An  enclosed  structure  above  the  roof  of 
a  building,  other  than  a  roof  structure  or  bulkhead, 
occupying  not  more  than  331/3%  of  the  roof  area 
(see  780  CMR  1510.3). 

Roof:  The  roof  slab  or  deck  with  its  supporting 
members,  not  including  vertical  supports 

Roof  covering:  The  covering  applied  to  the  roof  for 
weather  resistance,  fireresistance  or  appearance. 

Roof  structure:  An  enclosed  structure  on  or  above 
the  roof  of  any  part  of  a  building  (see  780  CMR 
1510.0). 

780  CMR  1503.0  CONSTRUCTION 
DOCUMENTS 

1503.1  General:  For  all  roofs  and  roof  coverings 
required  by  780  CMR,  the  construction  documents 
shall  illustrate,  describe  and  clearly  delineate  the 
type  of  roofing  system,  materials,  fastening 
requirements  and  flashing  requirements  which  are  to 
be  installed 

780  CMR  15O4.0  WEATHER  PROTECTION 
1504.1  General:  All  roofs  shall  be  covered  with 
approved  roof  coverings  properly  secured  to  the 
building  or  structure  to  resist  wind  and  rain  Roof 
coverings  shall  be  designed,  installed  and 
maintained  in  accordance  with  approved 
manufacturer's  installation  instructions  such  that  the 
roof  covering  shall  serve  to  protect  the  building  or 
structure. 

780  CMR  1505.0  PERFORMANCE 
REQUIREMENTS 

1505.1  Performance  requirements:  All  roofs  and 
roof  coverings  approved  under  780  CMR  1505.0 
shall  comply  with  780  CMR  1505.2  through  1505.5. 


1505.2  Wind  resistance:  All  roofs  and  roof 
coverings  shall  be  secured  in  place  to  the  building  or 
structure  to  withstand  the  wind  loads  of  780  CMR 
1611.0  in  accordance  with  the  requirements  of 
780  CMR  1505.2.1  through  1505.2.3. 

1505.2.1  Ballasted  systems  All  loosely  laid 
ballasted  roof  coverings  shall  be  designed  to  resist 
the  wind  pressures  as  determined  by  780  CMR 
1611.0. 

1505.2.2  Low-slope  systems  other  than 
ballasted:  The  low-slope  roof  systems 
(coverings)  described  in  780  CMR  1507.3  which 
are  mechanically  attached  or  adhered  to  the  roof 
deck  shall  be  designed  to  meet  the  design  wind 
load  of  780  CMR  161 1.0  and  shall  be  tested  in 
accordance  with  FM  4450,  FM  4470  or  UL  580 
listed  in  Appendix  A 

1505.2.3  Steep-slope  systems:  The  steep-slope 
roof  coverings  described  in  780  CMR  1507.2 
which  are  mechanically  attached  to  the  roof  slab 
or  deck  in  accordance  with  780  CMR  1507.2.1 
through  1507.2.9  shall  resist  the  basic  wind 
speeds  of  Figure  1611.3,  adjusted  for  building 
height  above  grade  and  building  exposure. 

Exception:  Asphalt  shingles  shall  be  tested  in 
accordance  with  ASTM  D3161  or  UL  997 
listed  in  Appendix  A. 

1505.3  Durability:  All  roofs  and  roof  coverings 
shall  be  of  approved  materials  such  that  those 
properties  which  establish  fire  classification,  wind 
resistance  and  weather  protection  shall  be 
maintained  in  accordance  with  780  CMR  1505.3  1 
and  1505.3.2. 

1505.3.1  Physical  properties  Roof  coverings 
shall  demonstrate  physical  integrity  over  the 
working  life  of  the  roof  based  upon  2,000  hours  of 
exposure  to  accelerated  weathering  tests 
conducted  in  accordance  with  ASTM  E838,  G23, 
G26  or  G53  listed  in  Appendix  A.  Those  roof 
coverings  which  are  subject  to  cyclical  flexural 
response  due  to  wind  loads  shall  not  demonstrate 
any  significant  loss  of  tensile  strength  for 
unreinforced  membranes  or  breaking  strength  for 
reinforced  membranes  when  tested  as  herein 
required. 

1505.3.2  Impact  resistance:  Roof  coverings  shall 
resist  impact  damage  based  on  the  results  of  tests 
conducted  in  accordance  with  ASTM  D3746  or 
D4272,  or  CGSB  37-GP-52M  or  FM  4470  listed 
in  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1505.4  Compatibility  of  materials:  All  roofs  and 
roof  coverings  shall  be  of  materials  that  are 
compatible  with  each  other  and  with  the  building  or 
structure  to  which  the  materials  are  applied. 

1505.5  Material  specifications  and  physical 
characteristics:  All  materials  for  roofs  and  roof 
coverings  shall  conform  to  the  applicable  standards 
listed  in  780  CMR  15.  In  the  absence  of  applicable 
standards  or  where  materials  are  of  questionable 
suitability,  testing  by  an  approved  testing  agency 
shall  be  required  by  the  code  official  to  determine 
the  character,  quality  and  limitations  of  application 
of  the  materials. 

780  CMR  1506.0  FIRE  CLASSIFICATION 

1506.1  Classification  Roof  covering  materials  shall 
be  classified  in  accordance  with  780  CMR  1506.1.1 
through  1506.1.4  when  tested  in  accordance  with 
ASTM  El  08  listed  in  Appendix  A 

1506.1.1  Class  A  roof  coverings:  Class  A  roof 
coverings  are  those  which  are  effective  against 
severe  fire  test  exposure.  Class  A  roof  coverings 
shall  include  the  following:  masonry,  concrete, 
slate,  tile,  cement-asbestos  or  assemblies  listed 
and  identified  as  Class  A  by  an  approved  testing 
agency  Class  A  roof  coverings  shall  be  permitted 
for  use  in  buildings  or  structures  of  all  types  of 
construction. 

1506.1.2  Class  B  roof  coverings:  Class  B  roof 
coverings  are  those  which  are  effective  against 
moderate  fire  test  exposure.  Class  B  roof 
coverings  shall  include  metal  sheets  and  shingles 
or  assemblies  listed  and  identified  as  Class  B  by 
an  approved  testing  agency.  Class  B  roof 
coverings  shall  be  permitted  as  the  minimum  for 
use  in  buildings  or  structures  of  Type  1 
construction. 

1506.1.3  Class  C  roof  coverings:  Class  C  roof 
coverings  are  those  which  are  effective  against 
light  fire  test  exposure  Class  C  roof  coverings 
shall  include  assemblies  listed  and  identified  as 
Class  C  by  an  approved  testing  agency.  Class  C 
roof  coverings  shall  be  permitted  as  the  minimum 
for  use  in  buildings  or  structures  of  Types  2,  3,  4 
and  5A  construction. 

1506.1.4  Nonclassified       roof      coverings: 

Nonclassified     roof    coverings     shall     not    be 
permitted. 
Exceptions: 

1.  Buildings  and  structures  of  Type  5B 
construction  with  a.  fire  separation  distance  of 
not  less  than  30  feet  (9144  mm)  from  the 
leading  edge  of  the  roof. 

2.  Occupancies  in  Use  Group  R-3  located  in 
detached  buildings  and  accessory  buildings 
thereto  which  have  afire  separation  distance 
of  not  less  than  six  feet  (1829  mm)  from  the 
leading  edge  of  the  roof. 


1506.2  Testing:  When  testing  wood  shingles  and 
shakes  in  accordance  with  ASTM  E  108  (including 
the  rain  test)  and  ASTM  D2898  listed  in 
Appendix  A,  the  fire  tests  shall  include  the 
intermittent  flame  test,  spread  of  flame  test,  burning 
brand  test  and  flying  brand  test,  additionally,  at  the 
conclusion  of  the  rain  test,  test  panels  shall  be 
subjected  to  the  intermittent  flame  test,  burning 
brand  test  and  flying  brand  test 

1506.3  Fireretardant-treated  shingles  and  shakes 

Fireretardant-treated  wood  shakes  and  shingles  shall 
be  treated  by  impregnation  with  chemicals  by  the 
full-cell  vacuum-pressure  process,  in  accordance 
with  AWPA  CI  listed  in  Appendix  A.  Each  bundle 
shall  have  two  labels,  one  identifying  the 
manufactured  unit  and  the  manufacturer,  and  the 
other  identifying  the  classification  of  the  material  in 
accordance  with  the  testing  required  in  780  CMR 
1506.2  (Class  B  or  C),  the  treating  company  and  the 
quality  control  agency 

780  CMR  1507.0  PRESCRIPTIVE 
REQUIREMENTS 

1507.1  Prescriptive       requirements:        The 

requirements  of  780  CMR  1507.2  and  1507.3  shall 
apply  to  all  roofs  and  roof  coverings  unless 
specifically  approved  in  accordance  with  780  CMR 
1505.0  Unless  otherwise  noted,  all  required 
underlayment  shall  be  of  Type  1 5  asphalt-saturated 
felt 

1507.2  Steep-slope  roof  coverings:  Steep-slope  roof 
covering  materials  and  installations  shall  comply 
with  780  CMR  1507.2.1  through  1507.2.9.  Where 
there  is  a  possibility  of  ice  forming  along  the  eaves 
causing  a  backup  of  water,  an  ice  shield  that  consists 
of  at  least  two  layers  of  underlayment  cemented 
together  or  of  a  waterproofing  membrane,  shall 
extend  from  the  eave's  edge  to  a  point  at  least  24 
inches  (610  mm)  inside  the  exterior  wall  line  of  the 
building 

1507.2.1  Asbestos-cement  shingles:  Asbestos- 
cement  shingles  shall  conform  to  ASTM  C222 
listed  in  Appendix  A.  Asbestos-cement  shingles 
shall  not  be  installed  on  roof  slopes  below  four 
units  vertical  in  12  units  horizontal  (4:12). 
Single-layer  underlayment  is  required  for  all  roof 
applications.  Asbestos-cement  shingles  shall  be 
secured  to  the  roof  with  two  fasteners  per  shingle 

1507.2.2  Asphalt  roll  roofing:  Asphalt  roll 
roofing  shall  conform  to  ASTM  D224,  D249, 
D371  or  D3909  listed  in  Appendix  A  Asphalt 
roll  roofing  shall  not  be  installed  on  roof  slopes 
below  one  unit  vertical  in  12  units  horizontal 
(1:12),  and  shall  not  be  installed  on  roof  slopes 
below  three  units  vertical  in  12  units  horizontal 
(3:12)  unless  applied  parallel  to  the  eaves. 
Single-layer  underlayment  is  required  or  all  roof 


252 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ROOFS  AND  ROOF  STRUCTURES 


slopes.  Asphalt  roll  roofing  shall  be  secured  to 
the  roof  in  accordance  with  approved 
manufacturer's  installation  instructions. 

1507.2.3  Asphalt  shingles:  Asphalt  shingles  shall 
conform  to  ASTM  D225  or  D3462  listed  in 
Appendix  A  Asphalt  shingles  shall  not  be 
installed  on  roof  slopes  below  two  units  vertical  in 
12  units  horizontal  (2:12).  Double-layer 
underlayment  shall  be  required  on  roof  slopes 
below  four  units  vertical  in  12  units  horizontal 
(4:12).  Single-layer  underlayment  is  required  on 
all  other  roof  slopes.  Asphalt  shingles  shall  be 
secured  to  the  roof  with  not  less  than  four 
fasteners  per  strip  shingle,  or  not  less  than  two 
fasteners  per  individual  shingle  Shingle  headlap 
shall  not  be  less  than  two  inches  (5 1  mm). 

1507.2.4  Interlocking    clay    or    cement    tile: 

Interlocking  clay  or  cement  tile  shall  be  installed 
only  over  solid  sheathing  or  spaced  structural 
sheathing  boards.  Interlocking  clay  or  cement  tile 
shall  not  be  installed  on  roof  slopes  below  four 
units  vertical  in  12  units  horizontal  (4:12). 
Horizontal  battens  shall  be  required  on  roof  slopes 
over  seven  units  vertical  in  12  units  horizontal 
(7:12).  Single-layer  underlayment  is  required 
over  solid  sheathing  on  all  roof  slopes 
Reinforced  underlayment  shall  be  required  where 
spaced  sheathing  is  installed.  Regardless  of  roof 
slope,  the  first  three  tile  courses  and  all  tile  within 
three  feet  (914  mm)  of  roof  edges,  changes  in  roof 
slope  or  changes  in  slope  direction,  shall  be 
fastened  to  the  roof.  For  the  field  of  the  roof, 
fastening  is  not  required  on  roof  slopes  below  five 
units  vertical  in  12  units  horizontal  (5:12);  every 
tile  course  shall  be  fastened  on  roof  slopes  five 
units  vertical  in  12  units  horizontal  (5:12)  to  less 
than  12  units  vertical  in  12  units  horizontal 
(12:12);  and  every  tile  shall. be  fastened  on  roof 
slopes  12  units  vertical  in  12  units  horizontal 
(12:12)  and  over.  Tile  overlap  shall  be  in 
accordance  with  approved  manufacturer's 
installation  instructions. 

1507.2.5  Noninterlocking  clay  or  cement  tile: 

Noninterlocking  clay  or  cement  tile  shall  not  be 
installed  on  roof  slopes  below  two  and  one-half 
units  vertical  in  12  units  horizontal  (2'A:12). 
Double-layer  underlayment  is  required  on  roof 
slopes  below  three  units  vertical  in  12  units 
horizontal  (3:12).  Single-layer  underlayment  is 
required  on  all  other  roof  slopes.  Noninterlocking 
clay  or  cement  tile  shall  be  secured  to  the  roof 
with  two  fasteners  per  tile.  The  minimum  tile 
overlap  shall  be  three  inches  (76  mm). 

1507.2.6  Metal  shingles:  Metal  shingles  shall  not 
be  installed  on  roof  slopes  below  four  units 
vertical  in  12  units  horizontal  (4:12)  Single-layer 
underlayment  is  required  for  all  metal  shingles 
other  than  flat  metal  shingles  on  all  roof  slopes. 
Metal  shingles  shall  be  secured  to  the  roof  in 


accordance  with  approved  manufacturer's 
installation  instructions. 

1507.2.7  Slate  shingles:  Slate  shingles  shall 
conform  to  ASTM  C406  listed  in  Appendix  A 
Slate  shingles  shall  not  be  installed  on  roof  slopes 
below  two  units  vertical  in  12  units  horizontal 
(2:12).  Double-layer  underlayment  shall  be  re- 
quired on  roof  slopes  below  four  units  vertical  in 
12  units  horizontal  (4:12)  Single-layer 
underlayment  shall  be  required  on  all  other  roof 
slopes.  Slate  shingles  shall  be  secured  to  the  roof 
with  two  fasteners  per  slate.  The  minimum  slate 
headlap  shall  be  three  inches  (76  mm). 

1507.2.8  Wood  shingles:  Wood  shingles  shall  be 
identified  by  a  label  and  subject  to  a  quality 
control  program  administered  by  an  approved 
agency-  Wood  shingles  shall  not  be  installed  on 
roof  slopes  below  three  units  vertical  in  1 2  units 
horizontal  (3:12).  A  single  layer  of  underlayment 
is  required  at  eaves,  ridges,  hips,  valleys  and  all 
other  changes  of  roof  slope  or  direction.  Wood 
shingles  shall  be  secured  to  the  roof  with  a 
maximum  of  two  approved  fasteners  per  shingle. 
The  maximum  weather  exposures  for  wood 
shingles  shall  be  in  accordance  with  Table 
1507.2.8. 

Table  1507.2.8 

MAXIMUM  WEATHER  EXPOSURES 

FOR  WOOD  SHINGLES 


Grade 


No.  3  grade 


Shingle 

length 

(inches) 


Exposure  (inches)  based  on  slope 
(units  verticalumts  horizontal) 


33/i 
4% 


3V4 


4:12  and  steeper 


5Vz 
VA 


4Vz 


SVi 


Note  a    1  inch  =  25.4  mm 

1507.2.9  Wood  shakes:  Wood  shakes,  other  than 
preservative-treated  southern  yellow  pine  taper 
sawn  shakes,  shall  be  identified  by  a  label  and 
subject  to  a  quality  control  program  administered 
by  an  approved  agency.  Preservative-treated 
southern  yellow  pine  taper  sawn  shakes  shall  be 
identified  by  a  label  and  subject  to  the  TFS 
Grading  Rules  for  Preservative  Treated  Southern 
Yellow  Pine  Tapersawn  Shakes,  listed  in 
Appendix  A,  administered  by  an  approved 
agency.  Wood  shakes  shall  not  be  installed  on 
roof  slopes  less  than  four  units  vertical  in  12  units 
horizontal  (4:12).  A  single  layer  of  felt 
interlayment  shall  be  shingled  between  each 
course  of  wood  shakes  on  all  roof  slopes.  Wood 
shakes   shall   be   secured   to   the   roof  with   a 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


253 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


maximum  of  two  fasteners  per  shake.  The 
maximum  weather  exposure  shall  be  7V2  inches 
(191  mm)  for  18-inch-long  shakes  and  ten  inches 
(254  mm)  for  24-inch-long  shakes. 

1507.3  Low  -Slope  roof  coverings:  Low  slope  roof 
covering  materials  and  installations  shall  comply 
with  780  CMR  1507.3.1  through  1507.3.7.  Roofs 
shall  have  a  design  slope  of  a  minimum  of  one- 
fourth  unit  vertical  in  12  units  horizontal  ( V*:  12)  for 
drainage  except  for  coal-tar  built-up  roofs  which 
shall  have  a  design  slope  of  a  minimum  one-eighth 
unit  vertical  in  12  units  horizontal  (1/s:l2).  The 
attachment  of  insulation  above  the  roof  deck,  the 
weight  and  distribution  of  ballast,  the  fastener  type 
and  fastening  pattern,  and  the  bitumen  or  adhesive 
application  utilized  in  the  installation  of  low-slope 
roof  coverings  shall  meet  the  wind  resistance 
requirements  of  780  CMR  1505.2. 

1507.3.1  Built-up  roofing:  Built-up  roof  covering 
materials  shall  comply  with  the  standards  in  Table 
1507.3.1.  Provisions  shall  be  made  at  deck  edges, 
terminations  and  penetrations  for  mechanical 
fastening  of  the  built-up  roof  covering  and 
flashing  materials.  On  slopes  greater  than  two 
units  vertical  in  12  units  horizontal  (2:12). 
provisions  shall  be  made  for  blind  nailing  the 
built-up  roof  covering  to  the  roof  to  prevent 
slipping.  Aggregate  surfacing  shall  not  be 
installed,  and  plies  shall  be  applied  parallel  to  the 
slope  of  the  deck  (strapping  method)  on  roof 
slopes  above  three  units  vertical  in  12  units 
horizontal  (3:12).  Built-up  roof  coverings  shall  be 
installed  in  accordance  with  approved 
manufacturer's  installation  instructions. 

Table  1507.3.1 

BUILT-UP  ROOFING  MATERIAL 

STANDARDS 


Material 

Standard 

Aggregate  surfacing 

ASTMD1863 

Asphalt-coated  glass  fiber  venting  base  sheet 

ASTMD4601 

Asphalt  glass  felt 

ASTMD2178 

Asphalt-saturated  and  asphalt-coated  organic 

ASTMD2626 

felt  base  sheet 

Asphalt-saturated  organic  felt  (perforated) 

ASTM  D226 

Asphalt  used  in  roofing 

ASTMD312 

Coal-tar  saturated  organic  felt 

ASTM  D227 

Coal-tar  used  in  roofing 

ASTMD450 

Types  I  or  in 

Mineral-surfaced  inorganic  cap  sheet 

ASTM  D3909 

Venting,  asphalt-saturated  and  asphalt- 

coated  inorpanic  felt  based  sheet 

ASTMD3672 

Note  a.   Specific  standards  referenced  are  those  listed 
in  Appendix  A 

1507.3.2  Thermoset  single-ply  roof  coverings: 

Thermoset  single-ply  roof  coverings  shall  comply 
with  RMA  RP-I,  RP-2  or  RP-3,  or  ASTM  D4637 
or  CGSB  37-GP-52M  listed  in  Appendix  A. 
Provisions  shall  be  made  at  deck  edges, 
terminations    and    penetrations   for    mechanical 


fastening  of  the  thermoset  single-ply  roof 
covering  and  flashing  materials.  Ballasted  roof 
coverings  shall  not  be  installed  on  roof  slopes 
above  two  units  vertical  in  12  units  horizontal 
(2: 12).  Thermoset  single-ply  roof  coverings  shall 
be  installed  in  accordance  with  approved 
manufacturer's  installation  instructions. 

1507.3.3  Thermoplastic  single-ply  roof 
coverings:  Thermoplastic  single-ply  roof 
coverings  shall  comply  with  ASTM  D4434  or 
CGSB    37-GP-54M    listed    in    Appendix    A 

Provisions  shall  be  made  at  deck  edges, 
terminations  and  penetrations  for  mechanical 
fastening  of  the  thermoplastic  single-ply  roof 
covering  and  flashing  materials.  Ballasted  roof 
coverings  shall  not  be  installed  on  roof  slopes 
above  two  units  vertical  in  12  units  horizontal 
(2:12).  Thermoplastic  single-ply  roof  coverings 
shall  be  installed  in  accordance  with  approved 
manufacturer's  installation  instructions 

1507.3.4  Modified   bitumen    roof  coverings 

Modified  bitumen  roof  coverings  shall  comply 
with  CGSB  37-GP-56M  listed  in  Appendix  A 
Provisions  shall  be  made  at  deck  edges, 
terminations  and  penetrations  for  mechanical 
fastening  of  the  modified  bitumen  roof  covering 
and  flashing  materials  Modified  bitumen  roof 
coverings  shall  be  installed  in  accordance  with 
approved  manufacturer's  installation  instructions. 

1507.3.5  Spray-applied  polyurethane-foam 
roof  covering  systems:  Spray-applied 
polyurethane-foam  insulation  shall  comply  with 
ASTM  CI 029  listed  in  Appendix  A  A  liquid- 
applied  roof  coating  that  complies  with  780  CMR 

1507.3.6  shall  be  applied  to  the  top  surface  of  the 
cured  foam  insulation  in  accordance  with 
approved  manufacturer's  installation  instructions 
Foam  plastics  shall  also  conform  to  780  CMR 
2603.  o" 

1507.3.6  Liquid-applied  roof  coatings  Liquid- 
applied  roof  coatings  shall  comply  with  ASTM 
C836,  C957,  D1227  or  D3468  listed  in 
Appendix  A  Liquid-applied  roof  coatings  shall 
be  applied  in  accordance  with  approved 
manufacturer's  installation  instructions. 

1507.3.7  Metal-sheet  roof  coverings:  Metal- 
sheet  roof  covering  systems  which  incorporate 
supporting  structural  members  shall  be  designed 
in  accordance  with  780  CMR  2206.0.  Metal- 
sheet  roof  coverings  installed  over  structural 
decking  shall  comply  with  ASTM  A361,  A755  or 
B101  listed  in  Appendix  A.  Metal-sheet  roof 
coverings  shall  be  installed  in  accordance  with 
approved  manufacturer's  installation  instructions 

780  CMR  1508.0  FLASHINGS 
1508.1  General:  Flashings  shall  be  installed:  at  wall 
and  roof  intersections,  at  gutters,  wherever  there  is 


254 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ROOFS  AND  ROOF  STRUCTURES 


a  change  in  roof  slope  or  direction:  and  around  all 
roof  openings. 

780  CMR  1509.0  ROOF  INSULATION 
1509.1  General:  Rigid  combustible  roof  insulation 
shall  be  permitted,  provided  that  the  insulation  is 
covered    with    approved    roof  coverings   directly 
applied  thereto  (see  780  CMR  2603.4.1.5). 

780  CMR  1510.0  ROOF  STRUCTURES 

1510.1  General:  All  construction,  other  than  aerial 
supports,  clothes  dryers  and  similar  structures  less 
than  12  feet  (3658  mm)  high,  water  tanks  and 
cooling  towers  as  hereinafter  provided  and  flag  poles 
erected  above  the  roof  of  any  part  of  any  building  or 
structure  more  than  40  feet  (12192  mm)  in  height, 
shall  be  constructed  of  approved  noncombustible 
materials. 

1510.2  Scuttles:  Trap  doors  and  scuttles  as  required 
by  780  CMR  1027.0  shall  not  be  less  than  two  feet 
by  three  feet  (610  mm  by  914  mm)  in  size.  In 
buildings  of  Types  1  and  2  construction,  trap  doors 
and  scuttles  shall  be  of  approved  noncombustible 
materials. 

1510.3  Penthouses:  Penthouses  shall  be  considered 
a  part  of  the  next  lower  story,  and  the  enclosure  shall 
conform  to  the  requirements  for  exterior  walls  of  the 
building  type  as  regulated  by  Table  602  and 
780  CMR  14  except  as  modified  herein. 

1510.3.1  Recessed  walls:  Where  the  exterior  wall 
of  a.  penthouse  is  recessed  five  feet  (1524  mm)  or 
more  from  the  exterior  wall  of  the  next  lower 
story  and  the  exterior  wall  of  the  next  lower  story 
is  required  to  have  a  fireresistance  rating  of 
greater  than  VA  hours,  the  penthouse  exterior  wall 
shall  be:  constructed  with  a  fireresistance  rating  of 
not  less  than  VA  hours;  covered  on  the  outside 
with  noncombustible,  weatherproof  material,  and 
supported  on  protected  steel  or  reinforced 
concrete  construction. 

1510.3.2  Unprotected  openings:  Where 
protected  openings  are  not  required  by  780  CMR 
705.0,  windows  and  doors  shall  be  constructed  of 
any  approved  materials.  Glazing  shall  conform  to 
the  requirements  of  780  CMR  14,  24  and  26. 

1510.4  Other  enclosed  roof  structures:  Enclosed 
roof  structures,  other  than  penthouses,  shall  be 
considered  a  story  of  the  building  and  shall  conform 
to  the  requirements  for  the  building  type  as  regulated 
by  Table  602  and  780  CMR  14. 

1510.5  Mansards    and    other    sloping    roofs: 

Mansards  and  other  sloping  roofs  shall  comply  with 
780  CMR  1510.5.1  and  1510.5.2. 

1510.5.1  High-slope  roofs  Every  mansard  roof 
or  other  sloping  roof  having  a  pitch  of  more  than 


60  degrees  (1.05  rad)  to  the  horizontal  hereafter 
erected  on  any  building  or  structure  of  other  than 
Type  5  construction  which  is  more  than  three 
stories  or  40  feet  (12192  mm)  in  height,  shall  be 
constructed  of  noncombustible  materials  with  a 
fireresistance  rating  of  not  less  than  one  hour. 
Where  the  building  is  more  than  seven  stories  or 
85  feet  (25908  mm)  in  height,  such  roofs  shall 
afford  the  same  fireresistance  rating  required  for 
the  exterior  walls  of  the  building,  but  are  not 
required  to  exceed  a  1 '/2-hour  fireresistance  rating. 

1510.5.2  Low-slope  roofs:  Where  the  pitch  is  60 
degrees  (1.05  rad)  or  less  to  the  horizontal,  the 
mansard  or  other  sloping  roof  located  on  any 
building  shall  be  constructed  of  not  less  than  the 
same  materials  as  required  for  the  roof  of  the 
building. 

1510.6  Dormers:  The  sides  and  roofs  of  dormers 
shall  be  of  the  same  type  of  construction  as  the  main 
roof,  except  that  where  a  side  of  the  dormer  is  a 
vertical  extension  of  an  exterior  wall,  that  side  of  the 
dormer  shall  be  subject  to  the  same  fireresistance 
rating  requirements  as  apply  to  the  wall  of  the 
building.  The  roofs  of  dormers  shall  be  protected 
with  approved  roof  coverings  complying  with 
780  CMR  1506.0.  The  sides  of  dormers  shall  be 
protected  with  approved  roof  coverings  or  with 
material  permitted  for  covering  the  exterior  walls  cf 
the  building. 

1510.7  Water  tanks:  Water  tanks  shall  be 
constructed  and  installed  in  accordance  with 
780  CMR  1510.7.1  through  1510.7.5. 

1510.7.1  Supports:  Water  tanks  having  a  capacity 
of  more  than  500  gallons  (1.90  m3)  placed  in  or  on  a 
building  shall  be  supported  on  masonry,  reinforced 
concrete,  steel  or  other  approved  noncombustible 
framing  or  on  timber  conforming  to  Type  4 
construction;  provided  that,  where  such  supports  are 
located  in  the  building  above  the  lowest  story,  the 
support  shall  be  fireresistance  rated  as  required  for 
Type  1 A  construction. 

1510.7.2  Emergency  discharge:  A  pipe  or  outlet 
shall  be  located  in  the  bottom  or  in  the  side  close 
to  the  bottom,  or  the  tank  shall  be  fitted  with  a 
quick-opening  valve,  to  enable  the  contents  to  be 
discharged  in  an  emergency  to  a  suitable  drain 
that  complies  with  the  248  CMR  2.00:  the 
Massachusetts  State  Plumbing  Code  listed  in 
Appendix  A. 

1510.7.3  Location:  A  tank  shall  not  be  located 
over  or  near  a  stairway  or  elevator  shaft  unless  a 
solid  roof  or  floor  deck  is  constructed  underneath 
the  tank 

1510.7.4  Tank  cover:  All  roof  tanks  exposed  to 
the  weather  shall  have  approved  covers  sloping 
towards  the  outer  edges 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


255 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1510.7.5  Hoop  and  strap  protection:  Where 
metal  hoops  are  utilized  in  the  construction  of 
wood  tanks,  such  hoops  shall  be  protected  with 
approved  corrosion-resistant  coatings  or 
manufactured  from  approved  corrosion-resistant 
alloys. 

1510.8  Cooling  towers:  Cooling  towers  erected  on 
the  roofs  of  buildings  where  the  base  of  the  tower  is 
more  than  55  feet  (16764  mm)  above  grade  plane 
shall  be  constructed  of  approved  noncombustible 
material  or  fireretardant-treated  wood  except  that 
drip  bars  are  not  required  to  be  of  noncombustible 
material  or  fireretardant-treated  wood 

1510.9  Miscellaneous  roof  structures:  Except  as 
here  in  specifically  provided  for,  all  towers,  spires, 
dormers  or  cupolas  shall  be  erected  of  the  type  of 
construction  and  fireresistance  rating  required  for 
the  building  to  which  such  structures  are  accessory 
as  regulated  by  Tables  503  and  602.  Where  the 
height  of  such  appurtenant  structures  exceeds  85 
feet  (25908  mm)  above  grade  plane  or  where  the 
area  at  any  horizontal  section  of  the  tower,  spire, 
dormer  or  cupola  exceeds  200  square  feet  ( 1 9  m2),  or 
where  utilized  for  any  purpose  other  than  as  a  belfry 
or  architectural  embellishment,  the  structure  and  the 
associated  supports  shall  be  of  Type  1  or  2 
construction,  or  of  fireretardant-treated  wood 
complying  with  780  CMR  2310.0.  Radio  and 
television  towers  and  antennas  shall  be  constructed 
to  comply  with  780  CMR  3 108.0  and  3109.0. 

780  CMR  1511.0  ROOFTOP  HELIPORTS 

1511.1  General:  780  CMR  1511.0  governs  the 
design  and  construction  of  rooftop  facilities  intended 
to  accommodate  the  landing  of  helicopters.  The 
utilization  of  a  roof  for  landing  shall  be  subject  to 
the  approval  of  the  Federal  Aviation  Administration. 

1511.2  Structural  loads:  The  roof  and  all  pertinent 
building  components  shall  be  designed  for  the  dead 
loads,  live  loads,  impact  loads  and  vibrations 
imparted  to  the  structure  due  to  helicopter  landing, 
including  the  single-skid  point  landing. 

1511.3  Referenced  standard:  All  rooftop  heliports 
shall  comply  with  NFiPA  418  listed  in  Appendix  A. 

780  CMR  1512.0  REROOFTNG 
1512.1     General:     Materials    and     methods     of 
application  used  for  recovering  or  replacing  an 


existing  roof  covering  shall  comply  with  the 
requirements  of  780  CMR  1505.0  or  1507.0.  The 
repair  of  existing  roofs  and  roof  coverings  shall 
comply  with  the  provisions  of  780  CMR  34,  but 
more  than  25%  of  the  roof  covering  of  any  building 
shall  not  be  removed  and  replaced  within  any  12- 
month  period  unless  the  entire  roof  covering  is  made 
to  conform  to  the  requirements  for  new  roofing. 

1512.2  Structural  and  construction  loads:  The 

structural  roof  components  shall  be  capable  of 
supporting  the  roof  covering  system  and  the  material 
and  equipment  loads  that  will  be  encountered  during 
installation  of  the  roof  covering  system. 

1512.3  Recovering  vs.  replacement:  New  roof 
coverings  shall  not  be  installed  without  first 
removing  existing  roof  coverings  where  any  of  the 
following  conditions  occur: 

1 .  Where  the  existing  roof  or  roof  covering  is 
water  soaked  or  has  deteriorated  to  the  point  that 
the  existing  roof  or  roof  covering  is  not  adequate 
as  a  base  for  additional  roofing. 

2.  Where  the  existing  roof  covering  is  wood 
shake,  slate,  clay,  cement  or  asbestos-cement  tile. 

3.  Where  the  existing  roof  has  two  or  more 
applications  of  any  type  of  roof  covering. 

Exception:  Complete  and  separate  roofing 
systems,  such  as  standing-seam  metal  roof 
systems,  which  are  designed  to  transmit  all 
roof  loads  directly  to  the  building's  structural 
system  and  which  do  not  rely  on  existing  roofs 
and  roof  coverings  for  support,  shall  not 
require  the  removal  of  existing  roof  coverings. 

1512.4  Reinstallation  of  materials:  Existing  slate, 
clay  or  cement  tile  shall  be  permitted  for 
reinstallation,  except  that  damaged,  cracked  or 
broken  slate  or  tile  shall  not  be  reinstalled.  Existing 
vent  flashings,  metal  edgings,  drain  outlets,  collars 
and  metal  counterflashings  shall  not  be  reinstalled 
where  rusted,  damaged  or  deteriorated.  Aggregate 
surfacing  materials  shall  not  be  reinstalled. 

1512.5  Flashings:  Flashings  shall  be  reconstructed 
in  accordance  with  approved  manufacturer's 
installation  instructions.  Metal  flashings  to  which 
bituminous  materials  are  to  be  adhered  shall  be 
primed  prior  to  installation. 


256 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  16 


STRUCTURAL  LOADS 

(This  Chapter  is  entire'v  unique  to  Massachusetts) 


780  CMR  1601.0  GENERAL 
1601.1  Scope:  The  provisions  of  780  CMR  16  shall 

control  the  structural  design  of  all  buildings  and 
structures,  or  portions  thereof,  hereafter  erected. 

780  CMR  1602.0  DEFINITIONS 
1602.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  16  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Load  Forces  or  other  actions  that  arise  on  structural 
systems  from  the  weight  of  all  permanent 
construction,  occupants  and  their  possessions, 
environmental  effects,  differential  settlement  and 
restrained  dimensional  changes. 
Dead  load:  The  weight  of  all  permanent  structural 
and  nonstructural  components  of  a  building,  such 
as  walls,  floors,  roofs,  ceilings,  stairways  and 
fixed  service  equipment. 

Duration  of  load:  The  period  of  continuous 
application  of  a  given  load,  or  the  aggregate  of 
periods  of  intermittent  applications  of  the  same 
load. 

Earthquake  load:  The  assumed  lateral  load  acting 
in  any  horizontal  direction  on  the  structural  frame 
due  to  the  dynamic  action  of  earthquakes. 
Impact  load:  The  load  resulting  from  moving 
machinery,  elevators,  craneways,  vehicles  and 
other  similar  forces  and  kinetic  loads. 
Internal  load:  The  forces  resulting  from  the 
restraint  of  movement  of  construction  materials  or 
differential  movement  of  a  combination  of 
materials  caused  by  the  effects  of  expansion  or 
contraction  due  to  temperature  changes, 
shrinkage,  moisture  changes,  creep,  differential 
settlement  or  combinations  thereof. 
Lateral  soil  load:  The  lateral  pressure  in  pounds 
per  square  foot  (psf)  (kilograms  per  square  meter 
[kg/m2])  due  to  the  weight  of  the  adjacent  soil, 
including  due  allowance  for  hydrostatic  pressure 
and  possible  surcharge  from  fixed  or  moving 
loads. 

Live  load:  Those  loads  produced  by  the 
occupancy  of  the  building,  not  including 
environmental  loads  such  as  wind  loads,  snow 
loads,  earthquake  loads  or  dead  loads. 
Wind  load  The  lateral  pressure  on  the  building  or 
structure  in  pounds  per  square  foot  (psf) 
(kilograms  per  square  meter  [kg/m2])  due  to  wind 
blowing  in  any  direction. 


Panel  (part  of  a  structure):  The  section  of  a  floor 
or  wall  comprised  between  the  supporting  frame 
of  two  adjacent  rows  of  columns  and  girders  or 
column  bands  of  floor  construction. 

Wall 

Loadbearing  wall:  A  wall  supporting  any  vertical 
load  in  addition  to  its  own  weight. 
Nonloadbearing  wall:  A  wall  which  does  not 
support  vertical  loads  other  than  its  own  weight. 

780  CMR  1603.0  CONSTRUCTION 
DOCUMENTS 

1603.1  General:  Construction  documents  shall  show 
the  size,  and  relative  locations  of  all  structural 
members  with  foundation,  floor  and  roof  levels, 
column  centers  and  all  offsets  dimensioned.  The 
design  loads  and  other  information  pertinent  to  the 
structural  design  required  by  780  CMR  1603.2 
through  1603.7  shall  be  clearly  indicated  on  the 
construction  documents  for  all  parts  of  the  building 
or  structure. 

1603.2  Floor  live  load:  The  uniformly  distributed 
floor  live  load  utilized  in  the  design  shall  be 
indicated  for  all  floor  areas  (780  CMR1606.0).  Live 
load  reduction  (780  CMR  1608.0),  if  utilized,  shall 
be  indicated. 

1603.3  Roof  live  load:  The  roof  live  load  utilized  in 
the  design  shall  be  indicated  for  all  roof  areas 
(780  CMR  1609.0). 

1603.4  Roof  snow  load:  The  basic  snow  load  shall 
be  indicated. 

1603.5  Wind  load:  The  following  information 
related  to  wind  loads  shall  be  indicated,  regardless  of 
whether  wind  loads  govern  the  lateral  design  of  the 
building: 

1.  Wind  Load  Zone.  If  more  than  one  wind 
direction  is  exposed,  the  applicable  wind  direction 
shall  be  indicated 

2.  Wind  pressure,  P. 

3 .  Special  exposures 

1603.6  Earthquake  design  data:  Where  earthquake 
loads   are    applicable,    the    following    earthquake 
design  data  shall  be  indicated  on  the  construction 
documents: 

1.  The  Seismic  Hazard  Exposure  Group  in 
accordance  with  780  CMR  1612.2.5; 

2.  The  Seismic  Performance  Category  in 
accordance  with  780  CMR  1612.2.7; 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


257 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3.  The  soil-profile  type  in  accordance  with  Table 
1612.4.1; 

4.  The  basic  structural  system  and  seismic- 
resisting  system  in  accordance  with  Table 
1612.4.4; 

5.  The  response  modification  factor  (R)  and  the 
deflection  amplification  factor  (Cd)  in  accordance 
with  Table  1612.4.4;  and 

6.  The  analysis  procedure  utilized  in  accordance 
with  780  CMR  1612.5  or  1612.6  as  applicable. 

1603.7  Other  loads:  Concentrated  loads  (780  CMR 
1613.0),  impact  loads  (780  CMR  1614.0)  and 
special  loads  (780  CMR  1615.0)  which  are 
applicable  to  the  design  of  the  building  or  structure 
shall  he  indicated. 

780  CMR  1604.0  DESIGN  SAFE  LOAD 

1604.1  Safe  support  required:  Buildings  or  other 
structures,  and  all  parts  thereof,  shall  be  designed 
and  constructed  to  support  safely  all  loads,  including 
dead  loads,  without  exceeding  the  allowable  stresses 
(or  specified  strengths  when  appropriate  load  factors 
are  applied)  for  the  materials  of  construction  in  the 
structural  members  and  connections. 

1604.2  Progressive  collapse:  Buildings  and 
structural  systems  shall  provide  such  structural 
integrity  that  the  hazards  associated  with  progressive 
collapse  are  reduced  to  a  level  consistent  with  good 
engineering  practice.  Structures  shall  be  able  to 
sustain  local  damage  or  failure,  with  the  structure  as 
a  whole  remaining  stable.  Compliance  with  the 
applicable  provisions  of  ASCE  7  listed  in 
Appendix  A  shall  be  deemed  to  meet  the 
requirements  of  780  CMR  1604.0. 

1604.3  In-situ  load  tests:  The  code  official  is 
authorized  to  require  an  engineering  analysis  or  a 
load  test,  or  both,  of  any  construction  whenever 
there  is  reason  to  question  the  safety  of  the 
construction  for  the  intended  occupancy. 
Engineering  analysis  and  load  tests  shall  be 
conducted  in  accordance  with  780  CMR  1707.0  or 
1709.0. 

780  CMR  1605.0  DESIGN  DEAD  LOAD 

1605.1  Weights  of  materials  and  construction:  In 

estimating  dead  loads  for  the  purposes  of  structural 
design,  the  actual  weights  of  materials  and 
constructions  shall  be  utilized,  but  not  less  than  the 
unit  dead  loads  prescribed  in  ASCE  7  listed  in 
Appendix  A.  In  the  absence  of  definite  information, 
any  values  assumed  by  the  designers  shall  be  subject 
to  the  approval  of  the  code  official. 

1605.2  Weight  of  fixed   service  equipment:   In 

estimating  dead  loads  for  the  purposes  of  design,  the 
weight  of  fixed  service  equipment  such  as  plumbing 
stacks    and    risers,     electrical     feeders,     heating. 


ventilating,  air  conditioning  and  fire  protection 
systems,  shall  be  included. 

1605.3  Partition  load:  In  offices  and  other  buildings 
in  which  subdividing  partitions  are  subsequently 
erected,  rearranged  or  relocated,  provisions  shall  be 
made  to  support  the  actual  weight  of  such  partitions 
where  the  partitions  occur,  or  for  an  equivalent 
uniform  load,  which  shall  be  assumed  to  be  not  less 
than  20  psf  (97.64  kg/nr)  of  floor  area  in  addition  to 
the  specified  uniformly  distributed  live  load. 
Provisions  for  partition  weight  shall  be  made 
whether  or  not  partitions  are  shown  on  the 
construction  documents,  unless  the  specified  live 
load  exceeds  80  psf  (390.56  kg/nr). 

780  CMR  1606.0  UMFORMLY 
DISTRIBUTED  LIVE  LOADS 

1606.1  Uniform  live  load:  The  minimum  uniformly 
distributed  live  load  in  pounds  per  square  foot  shall 
be  as  provided  for  in  Table  1606.1,  and  for  all 
concentrated  loads  wherever  such  loads  occur  as 
provided  for  in  780  CMR  1613.0.  The  live  loads  in 
Table  1606. 1  are  the  minimum  loads  to  be  used  for 
the  occupancies  listed.  Where  the  building  will  be 
subjected  to  greater  live  loads,  such  loads  shall  be 
utilized  for  design. 

1606.1.1  Trucks  and  buses:  Minimum  live  loads 
for  garages  having  trucks  or  buses  shall  be  in 
accordance  with  lane  loads  of  AASHTO  HB-  15 
listed  in  Appendix  A,  but  shall  not  be  less  than  50 
psf  (244  kg/nr). 

1606.1.2  Residential  attics:  All  live  load  shall  be 
applied  to  joists  or  to  bottom  chords  of  trusses  or 
trussed  rafters  only  in  those  portions  of  attic  space 
having  a  clear  height  of  42  inches  (1067  mm)  or 
more  between  joist  and  rafter  in  conventional 
rafter  construction;  and  between  bottom  chord  and 
any  other  member  in  trusses  or  trussed  rafter 
construction.  However,  joists  or  the  bottom 
chords  of  trusses  or  trussed  rafters  shall  be 
designed  to  sustain  the  imposed  dead  load  or  ten 
psf  (49  kg/nr),  whichever  is  greater,  uniformly 
distributed  over  the  entire  span. 

A  further  ceiling  dead-load  reduction  to  a 
minimum  of  five  psf  (24  kg/nr)  or  the  actual  dead 
load,  whichever  is  greater,  applied  to  joists  in 
conventional  rafter  construction  or  to  the  bottom 
chords  of  trusses  or  trussed  rafters  is  permitted 
under  either  or  both  of  the  following  conditions: 

1.  Where  the  clear  height  is  not  over  30 
inches  (762  mm)  between  joist  and  rafter  in 
conventional  construction  and  between  the 
bottom  chord  and  any  other  member  for  trusses 
or  trussed  rafter  construction. 

2.  Where  a  clear  height  of  greater  than  30 
inches  (762  mm),  as  denned  in  780  CMR 
1606.1  item  1,  does  not  exist  for  a  horizontal 
distance  of  more  than  12  inches  (305  mm) 
alonu  the  member 


258 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


Table  1606.1 
MINIMUM  UNIFORMLY  DISTRIBUTED 
LIVE  LOADS  


Occupcncy 


Live  load 

(psf)a 


Occupcncy 


Live  load 
(psf)3 


Apartments  (see  Residential) 

Armories  and  drill  rooms  1 50 

Assembly  areas  &  theatres: 

Fixed  seats  60 

Movable  seats  1 00 

Platforms  (assembly)  100 

Stage  floors  150 

Balcony,  decks  (exterior)  1 00 

One-and  two-family  dwellings  only  60 

Bowling  centers,  poolrooms  and  billiard  rooms  75 

Cornices  75 

Corridors,  except  as  otherwise  indicated  1 00 

Dwellings  (see  Residential) 

Fire  escapes  1 00 

Single-family  residential  buildings  only  40 

Garages: 

Passenger  cars  50 

Trucks  and  buses  -  see  also  780  CMR  1 606. 1.1  50 

Grandstands  (see  Reviewing  stands) 

Gvmnasiums,  main  fllors  and  balconies  100 

Hospitals 

Operating  Rooms  Laboratories  100 

Private  Rooms  40 

Wards  40 

Corridors  above  first  flloor  80 
Hotels  (see  Residential) 
Institutional  -  residential  care  (see  Residential) 
Libraries: 

Reading  Rooms  60 

Stack  rooms  (books  and  shelves  @  40  pcf  but  1 50 
not  less  than) 
Manufacturing 

Light  125 

Heavy  150 
Marquees  75 

Office  buildings: 
Offices  50 

Lobbies  '  100 

Corridors,  above  first  floor  80 

File  and  computer  rooms  require  heavier 
loads  based  upon  anticipated  occupancy 
Penal  Institutions: 

Cell  Blocks  40 

Corridors  100 

Residential: 

Attics  -  see  780  CMR  1 606. 1,2  20 

Multiple  -  family  dwellings: 

Dwelling  units  40 

Public  rooms  100 

Corridors  80 

One-and  two-family  dwellings  (areas  other  than  40 

sleeping  rooms) 

Sleeping  rooms  30 

Decks,  balconies,  etc.  60 

Hotels: 

Guestrooms  40 

Public  rooms  100 

Corridors  serving  public  rooms  1 00 

Corridors  80 


Reviewing  stands,  grandstands  and  bleachers  -  see 

780  CMR  1614.5  100 

Schools 

Classrooms  50 

Corridors  80 

Flexible  open  plan  areas  100 

Sidewalks,  vehicular  driveways,  subject  to  250 
trucking 

Skating  rinks  100 

Stairs  and  exits  1 00 

Storage  areas: 

Light  125 

Heavy  250 

Stores: 

Retail- 1st  floor  100 

Retail  -  upper  flloors  75 

Wholesale  100 

Yards  and  terraces,  pedestrians 100 

Note  a.  1  psf  =  4.882  fcg/nr. 

780  CMR  1607.0  DESIGN  LIVE  LOAD 

1607.1  Required  live  load:  The  live  loads  to  be 
assumed  in  the  design  of  buildings  and  structures 
shall  be  the  greatest  load  produced  by  the  intended 
occupancy,  but  not  less  than  the  minimum  uniformly 
distributed  unit  loads  required  in  780  CMR  1606.0 
for  specific  use  groups. 

1607.2  Loads  not  specified:  The  code  official  shall 
approve  the  required  live  load  for  any  occupancy  not 
specifically  provided  for  in  Table  1606.1. 

1607.3  Partial  loading:  The  full  intensity  of  the 
appropriately  reduced  live  load  applied  only  to  a 
portion  of  the  length  of  a  structure  or  member  shall 
be  considered  if  such  applied  load  produces  a  more 
unfavorable  effect  than  the  same  intensity  applied 
over  the  full  length  of  the  structure  or  member. 

780  CMR  1608.0  LIVE  LOAD  REDUCTION 
1608.1  General:  The  design  live  loads  specified  in 
780  CMR  1607.0  may  be  reduced  as  permitted  and 
specified  herein,  except  that  the  design  live  load 
shall  not  be  reduced  on  the  following  types  of 
structural  members: 

1 .  One-way  precast  or  cast-in-place  solid,  ribbed 
and  hollow  core  concrete  slabs. 

Exception:  Ribs  of  ribbed  or  hollow  core 
slabs  may  be  treated  as  individual  beams,  and 
live  load  may  be  reduced  on  the  ribs  the  same 
as  for  beams. 

2.  Two-way  concrete  flat  slabs  and  grid  slabs, 
with  or  without  capitals  or  drop  panels. 

Exception:  live  load  may  be  reducted  on  slab 
panels  if  there  are  beams  on  all  sides  of  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


259 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


panels,  and  load  is  transferred  to  the  columns 
from  these  beams  entirely  by  "beam  shear". 

3 .    Hangers 

1608.2  Design  live  loads  of  100  psf  or  less:  Except 
for  places  of  public  assembly  (as  defined  in 
780  CMR  210.)  garages,  and  open  parking 
structures,  a  structural  member  having  a  tributary 
area  AT  that  is  greater  than  A3  may  be  designed  for 
a  reduced  live  load  determined  by  the  following 
formulas: 

L  =NL0 

N  =  the  largest  of  the  following: 

1.  1  -  0.0008  (AT  -  AB) 

2.  0.75  -  0.20  (D/L0) 

3.  0.50  for  members  supporting  load  from 
more  than  one  floor,  or  0.60  for  members 
supporting  load  from  one  floor  only,  in  which: 

L  =  reduced  design  live  load  for  the  member 

L0  =  basic  design  live  load 

D0  =  dead  load  on  the  member 

AT  =  loaded  area  tributary  to  the  member,  square 

feet 

AB  =  basic  tributary  area,  square  feet,  defined  as 

follows: 

AB  =  100  square  feet  for  members  supporting 

load  from  more  than  one  floor 

AB  =  250  square  feet  for  members  supporting 

load  from  one  floor  only 

1608.3  Design  live  loads  greater  than  100  psf  and 
design  live  loads  for  garages  and  open  parking 
structures:  Structrual  members  supporting  load  from 
more  than  one  floor  may  be  designed  for  a  reduced 
live  load  equal  to  80%  of  the  design  live  load. 

1608.4  For  determination  of  the  number  of  floors 
supported  by  a  member  in  780  CMR  1608. 1,  1608.2 
and  1608.3  a  roof  may  be  considered  to  be  a  floor  if 
the  design  live  load  of  the  roof  is  equal  to  or  greater 
than  the  design  live  load  of  the  floor  below. 

780  CMR  1609.0  ROOF  LOADS 

1609.1  General:  The  structural  supports  of  roofs  and 
marquees  shall  be  designed  to  resist  wind  (see 
780  CMR  1611.0)  and,  where  applicable,  snow  (see 
780  CMR  1610.0)  and  earthquake  loads  (see 
780  CMR  1612.0)  in  addition  to  the  dead  load  of 
construction  and  the  appropriate  live  loads  as 
prescribed  in  780  CMR  1609.0,  or  in  Tablel606.1 

1609.2  Definitions  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  1609.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Fabric  awning:  A  fabric  awning  is  an  architectural 
projection  that  provides  weather  protection, 
identity  or  decoration  and  is  wholly  supported  by 
the  building  to  which  it  is  attached.  An  awning  is 


comprised  of  a  lightweight,  rigid  or  retractable 
skeleton  structure  over  which  a  fabric  cover  is 
attached. 

Fabric  canopy:  A  fabric  canopy  is  an  architectural 
projection  that  provides  weather  protection, 
identity  or  decoration  and  is  ground  supported  in 
addition  to  being  supported  by  the  building  to 
which  the  canopy  is  attached.  A  canopy  is 
comprised  of  a  lightweight  skeleton  structure  over 
which  a  fabric  cover  is  attached.  A  fabric  canopy 
is  not  a  primary  structure  or  a  roof. 

1609.3  Minimum  roof  loads:  Ordinary  roofs,  either 
flat,  pitched  or  curved,  shall  be  designed  for  the  live 
loads  as  specified  in  Table  1609.3  or  the  snow  load, 
whichever  is  greater. 

1609.4  Overhanging  eaves:  In  other  than 
occupancies  in  Use  Group  R-3,  and  except  where  the 
overhang  framing  is  a  continuation  of  the  roof 
framing,  overhanging  eaves,  cornices  and  other  roof 
projections  shall  be  designed  for  a  minimum 
uniformly  distributed  live  load  of  60  psf  (292.92 
kg/m2). 

Table  1609.3 
MINIMUM  ROOF  LIVE  LOADS3 


Roof  slope 

Tributary  loaded  area  in 

square  feet 
for  anv  structural  member 

0  to  200 

201  to  600 

Over  600 

Flat,  or  rise  less  than  4 
inches  per  foot  (1 :3) 

Arch  or  dome  with  rise  less 
than  V4  of  span 

20 

16 

12 

Rise  4  inches  per  foot  (1 :3) 
toless  than  1 2  inches  per 
foot  (1:1) 

16 

14 

12 

Rise  12  inches  per  foot 
(1:1)  and  greater 

Arch  or  dome  with  rise  % 
of  span  or  greater 

12 

12 

12 

Note  a:  loads  are  expressed  in  pounds  per  square  foot  of 

horizontal  projection 

Note  b:  1  square  foot  =  0.093  m2l  psf  =  4.882  kg/m2 

1609.5  Ponding:  Roofs  shall  be  designed  for  the 
maximum  possible  depth  of  water  that  would  pond 
thereon  as  determined  by  the  relative  levels  of  roof 
deck  and  overflow  weirs,  scuppers,  edges  or 
serviceable  drains  in  combination  with  the  deflected 
structural  elements.  In  determining  the  maximum 
possible  depth  of  water,  all  primary  roof  drainage 
means  shall  be  assumed  to  be  blocked. 

1609.6  Special  purpose  roofs:  Where  occupied  for 
incidental  promenade  purposes,  roofs  shall  be 
designed  for  a  minimum  live  load  of  60  psf  (292.92 
kg/m2);  and  100  psf  (488.20  kg/m2)  where  designed 
for  roof  gardens  or  assembly  or  educational 
occupancies. 


260 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


1609.6.1  Landscaped  roofs:  Where  roofs  are  to 
be  landscaped,  the  uniform  design  live  load'm  the 
landscaped  area  shall  be  20  psf  (97.64  kg/m2).  The 
weight  of  the  landscaping  materials  shall  be 
considered  as  dead  load  and  shall  be  computed  on 
the  basis  of  saturation  of  the  soil. 

1609.6.2  Fabric  awnings  and  canopies:  Where 
awnings  and  canopies  are  covered  with  a.  fabric 
material,  such  awnings  and  canopies  shall  be 
designed  for  a  uniform  live  load  of  5  psf  (24.4 
kg/nr)  as  well  as  for  snow  loads  and  wind  loads 
as  specified  in  780  CMR  1610.0  and  1611.0. 

1609.6.3  Special  purpose  roofs:  Roofs  to  be 
utilized  for  other  special  purposes  shall  be 
designed  for  appropriate  loads,  or  as  otherwise 
approved. 

780  CMR  1610.0  SNOW  LOADS 

1610.1  General:  Design  snow  loads  shall  be 
determined  in  accordance  with  780  CMR  1610.0  and 
shall  be  applied  to  the  roof  and  open  decks  of  all 
buildings  and  other  structures. 

1610.1.1  Application  of  loads:  Buildings  and 
other  structures  shall  be  designed  for  the  greater 
of  the  effects  from  either  a  uniform  snow  load 


over  the  whole  roof  or  open  deck  (balanced  snow 
load)  or  an  unbalanced  snow  load  on  the  roof  or 
open  deck  (partial  snow  load).  Buildings  and 
other  structures  shall  also  be  designed  for  the 
additional  effects  of  drifting  snow  at  changes  in 
roof  elevation  and  at  roof  projections,  and  for  the 
additional  effects  of  sliding  snow.  Snow  loads 
acting  on  a  sloping  surface  shall  be  considered  to 
act  on  the  horizontal  projection  of  that  surface. 
When  establishing  unbalanced  snow  loads  or 
drifting  snow  loads,  the  effects  of  wind  from  any 
direction  shall  be  considered. 

1610.2  Basic  snow  load:  Figures  1610. 1A, 
1610.  IB,  1610.1C,  and  1610.  ID  define  four  snow 
load  zones  in  the  state.  The  basic  snow  load  for  each 
zone  shall  be  a  uniformly  distributed  load,  P,,  in 
pounds  per  square  foot  of  horizontal  projection,  as 
follows: 


Snow  Load  Zone 

P/ 

1 

25  psf 

2 

30  psf 

3 

35  psf 

4 

40  psf 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


261 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Figure  1610.1A 
SNOW  LOAD  MAP  -  ZONE  1 


H^j-lTLlCK^T-^"^ 


List  of  Towns  in  Minimum  Uniform 
Snow  Load  Zones  Zone  1 


Barnstable 

Gav  Head 

Sandwich 

Bourne 

Gosnold 

Brewster 

Tisbury 

Harwich 

Truro 

Chatham 

Chjlmark 

Mashpee 

Vineyard  Haven 

Dennis 

Nantucket 

Wellfleet 

West  Tisbury 

Easlham 

Oak  Bluffs 

Edgartown 

Orleans 

Yarmouth 

Falmouth 

Provincetown 

262 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/Q7) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


Figure  1610.1B 
SNOW  LOAD  MAP  -  ZONE  2 


List  of  Towns  in  Minimum  Uniform 


Cambridge 

Freetown 

Snow  Load  Zones  . 

Zone  2 

Randolph 

Abington 

Lawrence 

Milton 

Taunton 

Acushnet 

Carlisle 

Lexington 

Ray  n  ham 

Tewksbury 

Amesbury 

Carver 

Georgetown              Lowell 

Nahant 

Reading 

Topsfield 

Andover 

Chemlsford 

Gloucester 

Lvnn 

New  Bedford 

Rehoboth 

Tyngsborough 

Arlington 

Chelsea 

Groveland 

Lynn  field 

Newburv 

Revere 

Attleboro 

Cohasset 

Newburyport 

Rochester 

Wakefield 

Halifax 

Newton 

Rockland 

Waltham 

Bedford 

Danvers 

Hamilton 

Maiden 

N.  Andover 

Rockport 

Wareham 

Belmont 

Dartmouth 

Hanover 

Manchester 

N.  Attleboro 

Rowley 

Watertown 

Berkley 

Dighton 

Hanson 

Mansfield 

N.  Reading 

Wenham 

Beverly 

Dracut 

Haverhill 

Marblehead 

Norton 

Salem 

W.  Bridgeware 

Billcrica 

Duxbury 

Hingham 

Marion 

Norwell 

Salisbury 

W.  Newbury 

Boston 

Hoi  brook 

Marshfield 

Saugus 

Wcstport 

B  oxtbrd 

E.  Bridgewatcr 

Hull 

Mattapoisett 

Peabody 

Scituate 

Wevmouth 

Braintrce 

Easton 

Med  ford 

Pembroke 

Seekonk 

Whitman 

Bridgcwatcr 

Essex 

Ipswich 

Melrose 

Plvmouth 

Somerset 

Wilmington 

Brockton 

Everett 

Merrimac 

Plympton 

Somerville 

Winchester 

Brookline 

Kingston 

Methuen 

Stoncham 

Winthrop 

Burlington 

Fairhaven 

Middlcborough 

Quiricy 

Swampscott 

Woburn 

Fall  River 

Lakcvillc 

Middleton 

Swansea 

2/7/97   .(Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Figure  1610.1C 
SNOW  LOAD  MAP  -  ZONE  3 


P*^t 


.  fecgTi^agSTOM 


=C3X.££P«3UG^  ""'* 

■2$^- —  f=>L-Ck.r-ns/|  |_L& 

List  of  Towns  in  Minimu 

m  Uniform 

Snow  Load  Zones  Zone  3 

Acton 

Chicopee 

Greenfield 

Lunenburg 

Oakham 

Sunderland 

Wendell 

Agawam 

Clinton 

Groton 

Orange 

Suttton 

West  Boylston 

Amherst 

Concord 

Marlborough 

Oxford 

Sharon 

West  Brookfield 

Ashbumham 

Hadley 

Maynard 

Sherbom 

W.  Springfield 

Ashbv 

Dedham 

Hampden 

Medfield 

Palmer 

Shirley 

Westborough 

Ashland 

Deerfield 

Hardwick 

Millbury 

Paxton 

Shrewsbury 

Westfield 

Athol 

Douglas 

Harvard 

Millville 

Pelham 

Shutesbury 

Westford 

Aubum 

Dover 

Hatfield 

Medway 

Pepperell 

S.  Hadlev 

Westminster 

Avon 

Dudley 

Holland 

Mendon 

Petersham 

Southampton 

Weston 

Aver 

Dunstable 

Holliston 

Milford 

Phillipston 

Southborough 

Westwood 

Holden 

Millis 

Plainville 

Wilbraham 

Barre 

E.  Brooktield 

Holyoke 

Monson 

Princeton 

Tcmpleton 

Winchendon 

Belchertown 

Easthampton 

Hopedale 

Montague 

Townsend 

Whately 

Bellingham 

E.  Longmeadow 

Hopkinlon 

Rovalston 

Worcester 

Berlin 

Erving 

Hubbardston 

Natick 

Rutland 

Upton 

Wrentham 

Bemardston 

Hudson 

Needham 

Uxbridge 

Blackstone 

Fitchburg 

New  Braintree 

Southbridge 

Bolton 

Foxborough 

Lancaster 

New  Salem 

Southwick 

Wales 

Boylston 

Framingham 

Leicester 

Norfolk 

Spencer 

Walpole 

Boxborough 

Franklin 

Leominster 

North  Brookfield 

Springfield 

Ware 

Brimfield 

Leverett 

Northampton 

Sterling 

Warren 

Brooktield 

Gardner 

Lincoln 

Northborough 

Stoughton 

Warwick 

Gill 

Littleton 

Northbridge 

Stow 

Wavland 

Canton 

Grafton 

Longmeadow 

Northiield 

Sturbridge 

Webster 

Charlton 

Granby 

Ludlow 

Norwood 

Sudburv 

Welleslev 

264 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


Figure  1610.1D 
SNOW  LOAD  MAP  -  ZONE  4 


zorisf 


&*■+& 


Adams 
Alford 
Ashfield 

Becket 
Blandford 
Buck]  and 

Charlemont 

Cheshire 

Chester 

Chesterfield 

Clarksburg 


Colrarn 
Conway 
Cummington 

Dalton 

Egremont 

Flonda 

Goshen 
Granville 
Great  Bamngton 


List  of  Towns  in  Minimum  Uniform 

Snow  Load  Zones  Zone  4 
Hancock 
Hawley 
Heath 
Hinsdale 
Huntington 


Monterey 
Montgomery 
Mount  Washington 

New  Ashford 
New  Marlborough 


Lanesborough 
Lee 
Lenox 
Leyden 

Middlefield 
Monroe 


1610.3  Symbols  and  notations  The  following 
symbols  and  notations  apply  to  the  provisions  of 
780  CMR  1610.0. 

roof  slope  expressed  in  degrees 
coefficient  for  amount  of  sliding  snow 
crossectional    area    of    drift    surcharge, 
expressed  in  square  feet 
slope  factor  (See  780  CMR  1610.5) 
density  of  snow,  expressed  in  pounds  per 
cubic  foot  (pcf) 
hfr       =height  of  uniform  snow  load  on  lower  roof 
or  deck,  expressed  in  feet 

hj       =maximum    height    of    drift    surcharge, 
expressed  in  feet 


Peru 
Pittsfield 


'<*■- 


Richmond 

Rowe 

Russell 

Sandisfield 

Savoy 

Sheffield 

Shelboume 

Stockbndge 


reduced     height 
expressed  in  feet 


Tolland 
Tyringham 

Washington 

W.  Stockbridge 

Westhampton 

Williamsburgh 

Wilhamstown 

Windsor 

Worthington 


of     drift     surchargfe, 


H. 


a  = 

A  = 

Cs  = 

D  = 


,1  -  potential  height  of  drift  surcharge  from 
snow  blown  from  lower  roof,  expressed  in 
feet 
//^r=reduced  height  of  drift  surcharge  from  snow 
blown  from  lower  roof,  expressed  in  feet 


Hfa  =potential  height  of  drift  surcharge  from 

snow  blown  from  upper  roof,  expressed  in 

feet 
//^ur=reduced  height  of  drift  surcharge  from  snow 

blown  from  upper  roof,  expressed  in  feet 
hf  =    difference  in  height  between  the  upper  and 

lower  roof  or  deck,  expressed  in  feet 


2/7/97    (Effective  2/28/97) 


780  CMR.  -  Sixth  Edition 


265 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


LT  =the  dimension  of  an  upper  roof  or 
projecting  element  perpendicular  to  the  wind  flow 
(perpendicular  to  (W  bu  and  W  bl),  expressed  in 
feet 


T 


basic   uniform   snow   load,    expressed   in 


pounds  per  square  foot  (psf) 
Ps  =    intensity    of    sloped    roof    snow    load, 

expressed  in  pounds  per  square  foot  (psf) 
Pfa  =  maximum  intensity  of  surcharge  load  from 

sliding   snow,    expressed   in   pounds   per 

square  foot  (psf) 
S  =    horizontal    separation    between    adjacent 

structures,    expressed  in  feet  (See  Figure 

1610.7) 
W  =  horizontal   dimension,   in   feet,    of  upper 

sloping  roof  (  See  Figure  1610.10) 
Wfru  =horizontal  dimension,  in  feet,  of  upper  roof 

normal  to  the  line  of  change  in  roof  level 

(See  Figure  1610.4) 
Wfri  =horizontal  dimension,  in  feet,  of  lower  roof 
normal  to  the  line  of  change  in  roof  level  (See 
Figure  1610.4) 
Wd=  width  of  snow  drift,  expressed  in  feet  (See 

Figure  1610.4) 
Ws  =  width  of  sliding  snow  drift,  expressed  in 

feet  (See  Figure  1610.10) 

1610.4  Uniform  Snow  Loads 

1610.4.1  Uniform  snow  load  for  flat  and  low- 
sloped  roofs  with  planar  panels  the  snow  load 
on  a  flat  roof  or  on  a  roof  with  planar  panels 
which  have  a  slope  less  than  30  degrees  shall  be 
equal  to  the  basic  snow  load,  P, 

1610.4.2  Uniform  snow  load  for  sloped  roofs 
with  planar  panels:  The  sloped  roof  snow  load 
on  roofs  having  a  slope  greater  than  30  degress 
shall  be  calculated  using  the  following  formula: 


P    =  CPf 

S  S     J 


(Equation  I) 


where    "Cs"    is    determined   by   the   following 
formula: 


=  1  _   (q  -  30) 


40 


(Equation  2) 


and  "a"  is  the  slope  of  the  roof  expressed  in 
degrees. 

1610.4.3  Uniform  snow  load  for  convex  curved 
roofs:  Where  the  tangents  to  the  surface  of  a 
convex  curbed  roof  have  slopes  greater  than  70 
degrees,  the  point  at  which  the  slope  of  the 
tangent  exceeds  70  degrees  shall  be  considered 
the  effective  eave.  The  surface  of  a  convex 
curved  roof  below  the  effective  eave  shall  be 
considered  free  of  snow.    The  snow  load  on    a 


convex  curved  roof  shall  be  determined  by 
Equation  1.  with  "a"  equal  to  the  effective  roof 
slope  in  degrees.  The  effective  roof  slope  is 
equal  to  the  slope  of  a  chord  from  the  eave  or 
effective  eave  to  the  crown  of  the  roof 

1610.4.4  Uniform  snow  load  for  concave 
curved  roofs:  The  effective  loaded  area  of  a 
concave  curved  roof  shall  be  that  area  of  the 
surface  of  the  roof  where  the  tangents  to  the 
surface  have  a  slope  of  50  degrees  or  less.  The 
total  load  on  a  concave  curved  roof  shall  be  the 
basic  snow  load.  Py.  multiplied  by  the  total 
horizontal  projected  area  of  the  roof  This  total 
load  shall  be  applied  uniformly  over  the  effective 
loaded  area  of  the  roof 

1610.4.5  Uniform  Snow  Loads  for  multiple 
roofs  For  multiple  folded-plate,  sawtooth,  and 
barrel  vault  roofs,  the  snow  load  shall  be  equal  to 
the  basic  snow  load.  P/.  regardless  of  the  slope  of 
the  roof 

1610.5  Unbalanced  Snow  loads  Except  as 
otherwise  specifically  provided  in  780  CMR 
1610.5.1  through  780  CMR  1610.5.3.  unbalanced 
snow  loads  shall  be  applied  in  patterns  of  100%  of 
the  uniform  snow  load  alternating  with  50%  of  the 
uniform  snow  load  The  location  and  extent  of  the 
loadings  in  the  patterns  shall  be  such  as  to  maximize 
the  various  structural  effects. 

1610.5.1  Unbalanced  snow  load  for  hip  and 
gable  roofs:  For  hip  and  gable  roofs  with  siopes 
between  1 5  degrees  and  70  degrees,  the  structure 
shall  be  designed  to  sustain  an  unbalanced 
uniform  snow  ioad  on  the  leeward  side  of  the  roof 
equal  to  1  5PS,  where  Ps  is  determined  in  accord- 
ance with  780  CMR  1610.4.2.  The  windward  side 
of  the  roof  shall  be  considered  free  from  snow 

1610.5.2  Unbalanced  snow  load  for  convex 
curved  roofs.  For  convex  curved  roofs  with 
effective  roof  slopes  between  ten  degrees  and  60 
degrees,  determined  in  accordance  with  780  CMR 
161 0.4.3.  unbalanced  snow  loads  shall  be 
determined  in  accordance  with  the  loading 
diagrams  of  Figure  1610.2.  In  all  cases,  the 
windward  side  shall  be  considered  free  of  snow, 
and  any  portion  of  the  leeward  side  of  the  roof 
where  the  slope  of  the  tangent  to  the  roof  surface 
is  greater  than  70  degrees  shall  also  be  considered 
free  from  snow  If  the  ground  or  another  roof 
abuts  a  Case-II  or  Case-Ill  (see  Figure  1610.2) 
convex  curved  roof  structure  at.  or  within  three 
feet  of  its  eave.  the  snow  load  distribution  shall  be 
in  accordance  with  the  dashed  lines  on  Figure 
1610.2. 


266 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 

Figure  1610.2 
UNBALANCED  LOADING  CONDITIONS  FOR  CONVEX  CURVED  ROOFS 

Case  1  -    Slope  of  tangent 
At  eave  <30° 

C>Wind 


Eave 


Crown 


Eave 


Casell-  Slope  of  tangent 
At eave  30°  to70° 


Lt>  Wind 


Eave 


Crown 


*d& 


"2Pe     1     - 


X-30 
40 


30°    Eave     Where  x  =  slope  of 
point  tangent  at  eave 


Case  in  -  Slope  of  tangent 
At  eave  >  70° 

C>Wind 


30°       70° 
Point     Point 


Eave 


Crown 
'Distribution  of  snow  load  where  the  ground  or  another  roof  abuts  at  or  less  than  3'-0  from  eave 


1610.5.3  Unbalanced  snow  load  for  multiple 
roofs:  For  multiple  folded-plate,  sawtooth,  and 
barrel  vault  roofs,  the  unbalanced  snow  load  shall  be 
as  shown  on  Figure  1610  3.  In  the  figures,  P,  is  the 
basic  snow  load  intensity.  The  snow  depth  above 
the  valleys  need  not  exceed  the  level  of  the  snow 


above  the  ndges,  and  the  maximum  snow  load 
intensity  in  the  valleys  may  be  reduced  accordingly. 
Snow  depth  and  reduced  snow  loads  shall  be 
determined  from  the  assumed  density  of  snow,  D,  of 
20  pcf. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


267 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Figure  1610.3 
BALANCED  AND  UNBALANCED  LOADS  ON  A  SAWTOOTH  ROOF 


BALANCED 
LOAD  © 


UNBALANCED 
LOAD 


1610.6  Snow  Drift  loads  at  changes  in  roof 
elevation  and  at  roof  projections:  Multi-level 
roofs,  lower  roofs  and  decks  of  adjacent  structures, 
and  roofs  adjacent  to  projections  shall  be  designed  in 
accordance  with  780  CMR  1610.6.1  through 
1610.6.6 

1610.6.1  Design  loads  at  changes  in  roof 
elevation:  The  drift  load  on  lower  roofs  or  decks 
at  changes  in  roof  or  deck  elevation  shall  be  taken 
as  the  triangular  loading  surcharge  superimposed 
on  the  uniform  roof  snow  load,  Py  as  shown  in 
Figure  1610.4 

Two  types  of  drifts  shall  be  considered: 

1 .  from  wind  blowing  snow  from  the  upper 
roof 

2.  from  wind  in  the  opposite  direction  blowing 
snow  from  the  lower  roof 


The  drift  causing  the  more  severe  structural  effect 
shall  be  used  for  design 

The  density  of  snow,  D  in  a  snowdrift  and  in 
the  uniform  layer  of  snow  underlying  the  drift 
shall  be  not  less  than: 


D  =  IQpcf 


(Equation  3) 


The   height,    hj,   ,   of  the  uniform   snow  layer 
underlying  the  drift  shall  be: 


D 


(Equation  4) 


The  intensity  of  snow  load  at  any  point  shall  be 
the  total  depth,  at  that  point,  of  the  snowdrift  and 
the  underlying  uniform  layer  of  snow,  times  the 
density,  D 


Figure   1610.4 

DRTFTING  SNOW  ON  LOWER  ROOFS  AND 

DECKS  AT  CHANGES  EN  ROOF  OR  DECK 

ELEVATIONS 

Wbl 


1610.6.1.1  Drifting  of  snow  from  upper  roof: 

The  height  of  drift,  hd,  and  the  width  of  drift, 

Wd,    both   in   feet   shall   be   determined   as 

follows: 

a.     Compute  the  potential  drift  height  Hdu,  in 

feet,  and  the  cross-sectional  areas  of  drift,  Ad, 

in  square  feet,  as: 


Hda  =   1.15(WJ°"  -   1.5      (Equations) 

(Alternately,  H^  may  be  determined  from 
Figure  1610.5) 

A    _   (HJ(AHJ  2 

Ad  -   =  ltidu     (Equation  6) 


268 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


b:     \i{H^u  +  h fo)  is  less  than  or  equal  to  the 
difference  in  roof  elevations,  hr  ,  then: 


WJ 


(Equation  7) 


-  4(Hju)  (Equation  8) 

c:    If(Hdu  +  hb)  is  greater  than  hj.: 
\ 


W, 


h    -  K 


(Equation  10) 


Wj  need  not  exceed  10  (hr  -  h^ 

1610.6.1.2  Drifting  of  snow  from  lower  roof: 

The  height  of  drift,  hd  ,  and  the  width  of  drift, 
Wj  ,  both  in  feet  shall  be  determined  as  follows: 

a.  Compute  the  potential  drift  height,  FLj| ,  in 
feet,  as: 

Hdl  =  0.5[1.15(Wbl)033   -    1.5]   (Equation  11) 

(Alternatively,  Hd,  may  be  determined  from 
Figure  1610.5) 

b.  If  (Hdl  +  hb)  is  less  than  or  equal  to  h  r  , 
then: 

hd  =  Hjj  (Equation  12) 

c.  If  (  Hdj  +  hb)  is  greater  than  hr ,  then: 

hd  =  h    -  h.  (Equation  13) 


Wd  =  8(A .) 


(Equation  14) 


Figure  1610.5 

HEIGHT  OF  DRIFT  AT  CHANGE  IN 

ROOF  ELEVATION 


—  O     ICO     2CO     SCD  -«=>     tOO   GOO    TOO    OOO   -CO    lOOO 

WIDTH  OF  UPPER  ROOF,  Wbll,  OR  LOWER  ROOF,  Wb, 

PERPENDICULAR  TO  ROOF  SEPARATION 


1610.6.1.3  Multiple  level  roofs:  For  multiple 
stepped  roofs  similar  to  that  shown  in  Figure 
1610.6a,  the  sum  of  all  the  roof  lengths  upwind 
above  the  drift  under  consideration  shall  be 
considered  as  the  length  of  upper  roof  for  that 
drift  (as  shown,  for  example,  in  Figure 
1610.6a). 

For  multiple  level  roofs  similar  to  that  shown 

in  Figure  1610.6b,  if  the  total  calculated  height 

of  a  drift  and  the  underlying  uniform  snow 

layer  on  the  upwind  side  of  a  higher  roof  (  h'd 

+  hb)  is  equal  to  or  greater  than  0.7hp  then  the 

length,  Wbu  *,  as  shown  in  Figure  1610.6b, 

shall  be  used  in  place  of  Wbu  in  Equation  5. 

1610.6.2     Drift    loads    fln    adjacent    lower 

structures:   A  drift  surcharge  shall  be  applied  to 

roofs    of   lower    adjacent    structures    if  these 

structures  are  located  within  a  distance  of  Wd  ,  but 

not  greater  than  20  feet,  of  the  higher  structure  as 

depicted  in  Figure  1610.7.   The  height  of  drift  hd 

and  the  width  of  drift  Wd  shall  be  computed  for 

wind   in    either   direction,    in   accordance   with 

780     CMR     1610.6.1,     assuming,     for    these 

computations  only  that  there  is  no  space  between 

the  higher  and  lower  structures.      The  actual 

triangular  drift  surcharge  on  the  roof  of  the  lower 

structure  shall  be  as  shown  in  Figure  1610.7. 

Figure  1610.6 
DRIFTING  SNOW  AT  MULTIPLE 
CHANGES  IN  ROOF  ELEVATION 

Figure  1610.6a 


WIND 

wbu 


yc 


Figure  1610.6b 

WIND      J^- 

wbu* 


NOTE:  Use  Wbu*  when  h'd  +  hb  ^  7h'r. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


269 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figure  1610.7 

DRIFTING  SNOW  ON  TO  ADJACENT  LOW 

STRUCTURES 


NOTE:  Drift  surcharge  required  only  when  S  < 
Wd  and  S  <  20  Ft. 

Figure  1610.8 
SNOW  DRIFTING  AT  ROOF  PROJECTIONS 


whl 

wbu 

IT) 

-DRIFT 
SURCHARGE 

(WTNDFR< 

JMLEFT) 

(WTNTTFROM 

RIG 

ROOF . 

PROJECTION 

DRIFT <_ 

SURCHARGE^ 

\          > 

__£ 

>£* 

iC< 

{A 

'■••.                        s    .-..'• 

--•   .'     ■'.'  -"^ 

hh      ' 

1      L                  L 
hb        /                   / 

P 

Figure  1610.9 
INTERSECTING  SNOW  DRIFTS 


Figure  1610.10 

ADDITIONAL  SURCHARGE  DUE  TO 

SLIDING  SNOW 


,  =  15"  SMOOTH  SURFACES 
(METAL  OR  SLATE) 

,  =25*  OTHER  SURFACES 


1610.6.3  Very  high  roof  separations  When  the 
ratio  h/LT  is  greater  than  1.0,  where  Lp  is  the  di- 
mension in  feet  of  the  upper  roof  perpendicular  to 
the  wind  flow  (perpendicular  to  Wbu  and  Wb|),  the 
drift  surcharge  load  on  the  lower  roof  due  to 
drifting  of  snow  from  the  upper  roof  may  be 
reduced.  The  reduced  height  of  the  drift 
surcharge,  Hdur,  shall  be  not  less  than: 


ff*r   =  HJ2    -   f) 


(Equation  15) 


except  that  when  h/L^  is  greater  than  2.0,  Hdur 
shall  be  equal  to  zero. 

1610.6.4  Limited  extent  of  upper  roof:  When 
Lp,  the  dimension  in  feet  of  an  upper  roof  or 
projecting  element  perpendicular  to  the  wind 
flow,  (perpendicular  to  Wbu  and  Wb|)  is  less  than 
20  feet,  the  potential  height  of  drift  may  be 
reduced  and  shall  not  be  less  than: 


Hdur    ~    ^H^ 


(Equation  16) 


Hdlr  =   ^H^ 


(Equation  17) 


1610.6.5  Parapets  and  other  roof  projections: 

Design  drift  loads  for  roofs  adjacent  to  parapets 
and  other  roof  projections,  as  shown  in  Figure 
1610.8,  shall  be  determined  in  accordance  with 
780  CMR  1610.6.1  and  1610.6.4.  Drifts  due  to 
snow  from  the  top  of  a  roof  projection  need  only 
be  considered  when  Wbu  is  ten  feet  or  greater. 


270 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


1610.6.6  Intersecting  drifts  When  one  snow 
drift  intersects  another  at  an  angle  as  shown  in 
Figure  1610.9,  the  unit  snow  load  at  any  point 
shall  be  not  less  than  the  greater  of  the  unit  loads 
from  the  two  individual  drifts,  plus  the  unit  load 
of  the  underlying  uniform  snow  layer. 

1610.7    Sliding  snow  from  sloped  upper  roofs 

Two  cases  of  drift  loading  shall  be  considered  for 
roofs  which  are  located  below  upper  sloped  roofs,  as 
shown  in  Figure  1610.10  and  as  follows: 

(a)  Case  I  Drift  loading  due  to  snow  from  the 
upper  roof  computed  in  accordance  with 
780  CMR  1610.6. 1,  but  without  load  from  sliding 
snow  (Wbu  is  the  full  width  of  the  upper  roof  as 
shown  in  Figure  1610.10.) 

(b)  Case  II  Drift  loading  due  to  snow  from  the 
lower  roof  computed  in  accordance  with 
780  CMR  1610.6. 1  and  a  sliding  snow  surcharge 
load  as  specified  below  and  as  shown  in  Figure 
1610.10. 

The  maximum  intensity  of  the  sliding  snow  load, 
PHc ,  shall  be: 


AW. 

~W 


'<Pf) 


(Equation  18) 


where  Wa  and  Ws  are  defined  in  Figure  1610.10  and 
the  coefficient  A  is  defined  as  follows: 

(a)  For  roof  surfaces  of  metal  and  slate,  and  for 
other  roof  surfaces  smoother  than  mineral 
surfaced  roofing:  If  the  angle  of  slope  of  the  upper 
roof,  "a'\  as  shown  in  Figure  1610  10  is  equal  to 
or  greater  than  15  degrees  (slope  3.2  in  12).  A  = 
1.6;  if  "a"  is  less  than  15  degrees.  A  =  0  (no 
sliding  snow  load). 

(b)  For  roof  surfaces  of  mineral  surfaced  roofing 
or  rougher  surfaces: 

If  "a"  is  equal  to  or  greater  than  25  degrees 
(slope  5.6  in  12),  A  =  1.0, 
if  "a,r  is  less  than  25  degrees,  A  =  0. 
The  value  of  Ws  ,  the  width  of  the  sliding  snow 
surcharge,  shall  be  computed  as  follows: 

(a)    For  "a"  less  than  or  equal  to  45  degrees. 


W   =  h 


W 


4 


(Equation  19) 


(Equation  20) 


whichever  is  greater. 

(b)    For  "a"  greater  than  or  equal  to  45° 
W    +  h  (cot  a)  (Equation  21) 


W 


W 


(Equation  22) 


whichever  is  greater 

1610.7.1  Snow  guards:  Sliding  snow  from  an 
adjacent  sloping  high  roof  need  not  be  considered 
on  the  low  roof  if  proper  snow  guards  are 
provided  on  the  high  roof  In  this  case,  the 
sloping  roof  with  snow  guards  shall  be  designed 
for  the  unit  snow  loads  required  for  a  flat  roof 

1610.8  Snow  pockets  or  wells  Account  shall  be 
taken  of  the  load  effects  of  potentially  excessive 
snow  accumulation  in  pockets  or  wells  of  roofs  or 
decks. 

1610.9  Snow    storage    and    collection    areas: 

Consideration  of  potentially  excessive  snow 
accumulation  shall  be  given  to  portions  of  structures 
which  mav  be  designed  or  used  as  snow  collection 
or  storage  areas  during  and  after  snow  removal 
operations 

780  CMR  1611.0  WIND  LOAD 

1611.1  Wind  load  zones  The  locations  of  Mind 
load  zones  are  shown  in  the  Figures  1 6 1 1 . 1  A. 
1611  IB,  161 1.1C  maps  Zone  1  consists  of  the 
Counties  of  Berkshire,  Franklin.  Hampshire  and 
Hampden;  Zone  2  consists  of  the  County  of 
Worcester;  and  Zone  3  consists  of  the  Counties  of 
Essex,  Middlesex,  Suffolk.  Norfolk,  Plymouth. 
Bristol  Barnstable,  Dukes  and  Nantucket. 

1611.2  Exposures:  Exposure  is  defined  as  a 
measure  of  terrain  roughness  and  is  classfied  as 
follows 

Exposure  A:  centers  of  large  cities  and  very 
rough,  hilly  terrain.  Exposure  A  applies  for 
downtown  areas  only  when  the  terrain  for  at  least 
one  half  mile  upwind  of  the  structure  is  heavily 
built  up,  with  at  least  50%  of  the  buildings  being 
in  excess  of  four  stones,  and  when  Exposure  B 
prevails  beyond  this  boundary. 

Exercise  caution  in  using  these  reduced  wind 
pressures  for  buildings  and  structures  on  high 
ground  in  the  midst  of  cities  or  rough  terrain. 

Exposure  B  suburban  areas,  towns,  city 
outskirts,  wooded  areas,  and  rolling  terrain 
Exposure  B  applies  only  when  the  terrain  for  at 
least  one  half  mile  upwind  is  a  continuous  urban 
development,  forest,  wooded  area,  or  rolling 
terrain 

Exposure    C        open   level    terrain  with   only 

scattered      buildings,       structures,  trees      or 

miscellaneous  obstructions,  open  water,  or 
shorelines. 

1611.2.1  Special  exposures:  Consideration  shall 
be  given  to  the  application  of  a  more  severe 
exposure  (e.g.,  Exposure  C  instead  of  Exposures 
B  or  A)  when  the  ground  slope  near  the  site  of  a 
structure  changes  abruptly,  in  order  to  account  for 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


271 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


the  resulting  higher  wind  speeds  near  ground 
level. 

1611.3  Reference  wind  velocities:  The  reference 
wind  velocity  for  each  wind  load  zone  is  the 
"fastest-mile'-  wind  velocity,  in  miles  per  hour,  at  30 
feet  about  the  ground  (  V30)  for  Exposure  C,  as 
shown  in  Table  1611.3: 


Table  1611.3 


Zone 

V30  (mph) 

1 

70 

2 

80 

3 

90 

Figure  161 1.1  A 
WIND  LOAD  MAP  -  ZONE  1 


"^^S 


W>LL|A*-fS-p=Tf 


•ng>LjT-iT 


List  of  Towns:  Wind  Load  Zones 


Zone  1 

Adams 

Chicopee 

Granville 

Lenox 

North  Adams 

Sheffield 

Wendell 

Agawam 

Clarksburg 

Great  Bamngton 

Leverett 

Northampton 

Shelboume 

W.  Springfield 

Alford 

Colrain 

Greenfield 

Levden 

Northfield 

Shutesbury 

W.  Stockbndge 

Amherst 

Conway 

Hadley 

Longmeadow 

Orange 

S.  Hadlev 

Westfield 

Ashfield 

Cummington 

Hampden 

Ludlow 

Otis 

Southampton 

Westhampton 

Becket 

Dalton 

Hancock 

Middlefield 

Palmer 

South  wick 

Whatelv 

Belchertown 

Deerfield 

Hatfield 

Monroe 

Pelham 

Springfield 

Wilbraham 

Bemardston 

E.  Longmeadow 

Hawlev 

Monson 

Peru 

Stockbndge 

Williamsburgh 

Blandford 

Easthampton 

Heath 

Montague 

Pittsfield 

Sunderland 

Wiliamstown 

Bnmfield 

Egremont 

Hinsdale 

Monterey 

Plainfield 

Tolland 

Wmdsor 

Buckland 

Erving 

Holland 

Montgomery 

Richmond 

Tyrmgham 

Worthington 

Charlemont 

Florida 

Holvoke 

Mount  Washington 

Rowe 

Wales 

Cheshire 

Gill 

Huntington 

New  Ashford 

Russell 

Ware 

Chester 

Goshen 

Lanesborough 

New  Marlborough 

Sandisfield 

Warwick 

Chesterfield 

Granby 

Lee 

New  Salem 

Savoy 

Washington 

272 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


FIGURE  1611.1b 
WIND  LOAD  MAP  -  ZONE  2 


"P*^ 


PlTd-|f£=UC2& 


Asburnham 

Athol 

Auburn 

Barre 

Berlin 

Blackstone 

Bolton 

Boylston 

Brookfield 

Charlton 

Clinton 

Douglas 

Dudley 

E.  Brookfield 

Fitchburg 

Gardner 

Grafton 

Harvard 

Hardwick 

Holden 


List  of  Towns:  Wind  Load  Zones 
Zone  2 

Hopedale  Royalston 

Hubbardston  Rutland 

Lancaster  Shrewsbury 

Leicester  Southborough 

Leominster  Southbridge 

Lundenburg  Spencer 

Mendon  Sterling 

Milford  Sturbridge 

Millbury  Sutton 

Millville  Templeton 

New  Braintree  Upton 

N.  Brookfield  Uxbridge 

Northborough  Warren 

Northbridge  Webster 

Oakham  W.  Boylston 

Oxford  W.  Brookfield 

Paxton  Westborough 

Petersham  Westminster 

Phillipston  Winchedon 

Princeton  Worcester 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


273 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDliNG  CODE 

FIGURE  I61I.1C 
WIND  LOAD  MAP  -  ZONE  3 


£»C 

72* 

o 

^ 

List  o 

f  Towns:  Wind  Load  Zones 

Zone  3 

Abington 

Boston 

Cohasset 

Fall  River 

Hingham 

Mansfield 

Nahant 

Acton 

Boxborough 

Concord 

Falmouth 

Holbrook 

Marblehead 

Nantucket 

Accushnet 

Boxford 

Danvers 

Foxborough 

Holliston 

Marion 

Natick 

Amesburv 

Bourne 

Dartmouth 

Framingham 

Hopkinton 

Marlborough 

Needham 

Andover 

Braintree 

Dedham 

Franklin 

Hudson 

Marshfield 

New  Bedford 

Arlington 

Brewster 

Dennis 

Freetown 

Hull 

Mashpee 

Newbury 

Ashby 

Bridgewater 

Dighlon 

Gay  Head 

Ipswich 

Mattapoisett 

Newburyport 

Ashland 

Brockton 

Dover 

Georgetown 

Kingston 

Maynard 

Newton 

Attleboro 

Brookline 

Dracut 

Gloucester 

Lakeville 

Medfield 

Norfolk 

Avon 

Burlington 

Dunstable 

Gosnold 

Lawrence 

Medford 

N.  Andover 

Ayer 

Cambridge 

Duxburv 

Groton 

Lexi  tgton 

Medway 

N  Attleboro 

Barnstable 

Canton 

E.  Bridgewater 

Groveland 

Lincoln 

Melrose 

N.  Reading 

Bedford 

Carlisle 

Eastham 

Halifax 

Littleton 

Merrimac 

Norton 

Bellingham 

Carver 

Easton 

Hamilton 

Lowell 

Methuen 

Norwell 

Belmont 

Chatham 

Edgartown 

Hanover 

Lvnn 

Middleborough 

Norwood 

Berkley 

Chemlsford 

Essex 

Hanson 

l.vnnlield 

Middleton 

Oak  Bluffs 

Beverly 

Chelsea 

Everett 

Harwich 

Maiden 

Millis 

Orleans 

Billerica 

Chilmark 

Fairhaven 

Haverhill 

Manchester 

Milton 

Peabodv 

274 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


Pembroke 

Rehoboth 

Scituate 

Stow 

Truro 

Wellesley 

Westwood 

Pepperell 

Revere 

Seekonk 

Sudburv 

Tyngsborough 

Wellfleet 

Wevmouth 

Plainville 

Rochester 

Sharon 

Swampscott 

Vineyard  Haven 

Wenham 

Whitman 

Plymouth 

Rockland 

Sherbom 

Swansea 

Wakefield 

W.  Bridgewater 

Wilmington 

Plympton 

Rockport 

Shirley 

Taunton 

Walpole 

Westford 

Winchester 

Provmcetown 

Rowley 

Somerset 

Tewksbury 

Waltham 

W.  Newbury 

Winthrop 

Quincy 

Salem 

Somerville 

Tisburv 

Wareham 

Weston 

Woburn 

Randolph 

Salisbury 

Stoneham 

Topsfield 

Watertown 

Westport 

Wrentham 

Ravnham 

Sandwich 

Stoughton 

Townsend 

Wavland 

W.  Tisburv 

Yarmouth 

Reading 

Saugus 

1611.4  Reference  wind  pressures:  Reference  wind 
pressures  for  the  various  exposures  and  wind  zones 
are  given  in  the  following  Table  1611.4.  The 
tabulated  pressures  are  combined  windward  and 
leeward  pressures  representing  the  overall  effect  of 
the  wind  on  essentially  rectangular  structures,  and 
account  for  typical  gust  effects  as  found  in  ordinary 
buildings.  These  pressures  do  not  account  for 
buffeting  or  channeling  caused  by  positions  of 
nearby  structures,  vortex  shedding,  or  wind  sensitive 
dynamic  properties  of  a  particular  structure. 

1611.5  Wind  loads  on  structures  as  a  whole:   All 

buildings  and  enclosed  or  partially  enclosed 
structures  shall  be  designed  to  withstand  a  total  wind 
load  acting  on  the  structure  as  a  whole  determined 
by  applying  the  appropriate  reference  wind  pressures 
given  in  Table  1611.4  or  1611.4a,  to  the  vertical 
projected  area,  normal  to  the  wind  direction  of  the 
vertical  surfaces  of  the  structure,  plus  the 
appropriate  wind  forces  on  the  roof  as  specified  in 
780  CMR  161 1.8.  Consideration  shall  be  given  to 
wind  acting  in  all  directions. 

1611.5.1  Simultaneous  wind  forces  on 
orthogonal  sides:  For  structures  which  are 
essentially  rectangular  in  plan,  or  whose  plan 
shape  is  made  up  of  rectangular  parts,  only  wind 
directions  normal  to  the  sides  of  the  structure  need 
be  considered,  provided  that  0.7  times  the  effects 


of  the  wind  acting  simultaneously  normal  to 
adjacent  orthogonal  sides  shall  also  be  considered 
when  it  produces  more  severe  effects  in  the 
structural  support  system.  Factors  other  than  0.7 
may  be  used  if  substantiated  by  appropriate  wind 
tunnel  tests. 

1611.5.2  Wind  force  distribution:  The  total 
wind  force  on  the  vertical  surfaces  of  a  structure 
prescribed  in  780  CMR  1611.5  shall  be 
distributed  6/10  to  the  windward  surfaces  (as  a 
positive  pressure)  and  4/10  to  the  leeward  surfaces 
(as  a  suction).  Other  distributions  may  be  used  if 
substantiated  by  appropriate  wind  tunnel  tests. 

1611.6  Vertical  parts  of  structures:  Vertical  parts 
of  structures  that  are  subjected  directly  to  the  wind, 
and  their  local  supporting  elements,  shall  be 
designed  to  resist  the  pressures  listed  in  Table 
1611.6,  normal  to  the  surface,  inward  or  outward. 
The  pressures  listed  in  the  table  represent  the 
combined  internal  and  external  pressures.  A  local 
supporting  element  of  a  vertical  part  subjected 
directly  to  the  wind  shall  be  defined  as  a  wall 
assembly,  a  stud,  a  mullion,  a  girt,  or  a  similar  item 
which  distributes  the  wind  load  from  the  vertical 
part  to  the  principal  structural  system  of  the 
structure. 


TABLE  1611.4 
REFERENCE  WIND  PRESSURE  (POUNDS  PER  SQUARE  FOOT) 

Height 

Zone  1 

Zone  2 

Zone  3 

above  grade 

Exposure 

Exposure 

Exposure 

1 1  (feet) 

A 

B 

C 

A 

B 

C 

A 

B 

C 

0-50 

11 

12 

12 

11 

17 

17 

14 

21 

21 

50-  100 

11 

12 

18 

11 

17 

24 

14 

21 

31 

100-  150 

11 

16 

22 

14 

21 

29 

18 

26 

37 

150-200 

13 

18 

25 

17 

24 

33 

22 

30 

41 

200  -  250 

15 

20 

27 

20 

27 

36 

25 

34 

45 

250  -  300 

17 

22 

29 

22 

30 

39 

28 

37 

48 

300  -  400 

19 

25 

31 

25 

33 

42 

32 

41 

52 

400  -  500 

22 

28 

34 

29 

37 

46 

36 

46 

57 

500  -  600 

24 

30 

37 

33 

41 

49 

41 

51 

61 

600  -  700 

27 

33 

39 

36 

44 

52 

45 

55 

65 

700  -  800 

29 

35 

41 

39 

47 

55 

48 

58 

68 

800  -  900 

31 

37 

43 

41 

49 

57 

52 

62 

72 

900-  1000 

33 

39 

45 

44 

52 

59 

55 

65 

74 

Sec  tabic  161  1.1a  for  empirical  wind  pressure  formulas 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


275 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE   1611.4a 
EMPIRICAL  WEND  PRESSURE  FORMULAS' 


Zone  1 

Zone  2 

Zone  3 

Exposure 

Exposure 

Exposure 

A 

B 

C 

A 

B 

C 

A 

B 

C 

p  =  30_ 

fh/SOO)0'35 

p  =  36 
0  45 
fh/800) 

p  =  42 
(h/800-)0,35 

p  =  40 
(h/800)0'53 

p  =  48 
0  45 
(h/800) 

p  =  56 
(h/800)035 

p  =  50_ 
(W800)0:>5 

p  =  60 
0  45 
(h/800) 

p  =  70 
(h/800)035 

Note  a:  Empuical  wind  pressure  formulas  may  be  used  in  lieu  of  the  reference  wind  pressures  in  table  1611.1 

TABLE   1611.6 

WEND  PRESSURES  ON  PARTS  OF  STRUCTURES 

AND  LOCAL  SUPPORTING  ELEMENTS 


Tributary  wind  load  area  of  part 
or  local  supporting  element 

Required  Design  Pressures 

Location  of  applied 
wind  pressure 

Reference  pressure  of 

780  CMR  1611.4 

multiplied  bv 

But  not  less 
than 

But  need  not  be 
greater  than 

Within  salient  comer  area" 

Anv 

1.7 

20psf 

70psf 

Bevond  salient  comer  area 

Less  than  or  equal  to  200  sf 

1.2 

20psf 

50psf 

Bevond  salient  comer  area 

Greater  than  200  sf 

0.8 

15psf 

50psf 

Note  1:  For  partially  enclosed  structures,  where  any  side  is  more  than  35%  open,  add  a  factor  of  0.3  to  the  coefficients 
of  this  column  of  the  table 

Note  2:  The  salient  corner  shall  be  defined  as  the  vertical  surface  located  within  a  distance  of  1/10  the  least  width  of 
the  structure,  but  not  more  than  ten  feet,  from  a  prominent  (salient)  corner. 

TABLE  1611.8 
EXTERNAL  WIND  PRESSURES  ON  ROOFS 


External  Wind  Pressure  -  flat,  gable,  shed  roofs  (wind  perpendicular  to  ndge) 

Roof  pitch                                             Multiples  of  reference  wind  pressure  of  780  CMR  161 1.4 

Degrees 

Rise/run 

Windward  slope 

Leeward  slope 

Positive  pressure 

Suction 

Suction 

0-20 

Flat  to  4/1 2 

... 

0.6 

0.5 

20-30 

4/12  to  7/12 

0.2 

0.5 

0.5 

30-40 

7/12  to  10/12 

0.3 

0.4 

0.5 

40-50 

10/12  to  14/12 

0.4 

0.3 

0.5 

50-90 

14/12  to  vertical 

0.6 

0.5 

External  Wind  Pressure  -  arch  shaped  roofs  (wind  perpendicular  to  ridge) 

Multiples  of  reference  wind  pressure  of  780  CMR  161 1 .4 

Rise  to  span  ratio 

Windward  quarter 

Center  half 

Leeward  quarter 

Positive  pressure 

Suction 

Suction 

Suction 

Less  than  2/10 

0.2 

0.7 

0.7 

0.4 

2/10  to  3/10 

0.3 

0.8 

0.4 

3/10  to  6/10 

0.6 



1.0 

0.4 

External  wind  pressure  -  flat,  gable,  shed  or  arched  shaped  roofs  (wind  parallel  to  ridge) 

All                                   Suction  of  0.6  multiplied  bv  the  reference  wind  pressure  of  780  CMR  161 1.4 

1611.7  Wind  loads  on  roofs:  Roofs  and  their 
supporting  structure  shall  be  designed  to  resist  the 
combined  effects  of  the  external  and  internal  wind 
pressures  specified  in  780  CMR  1611.8  through 
1611.11.  All  pressures  specified  shall  be  considered 
to  act  normal  to  the  roof  surface.  When  applying  the 
reference  wind  pressures  of  780  CMR  161 1.4  to  the 
provisions  of  780  CMR  1611.8  through  1611.11, 
the  reference  wind  pressures  shall  be  for  a  height 
equal  to  the  average  height  of  the  roof  eave  above 
grade. 

1611.8  External  wind  pressures  on  roofs  of 
enclosed  structures:  Except  as  specified  otherwise 
in  780  CMR  1611.11,  external  wind  pressures  shall 


be  specified  in  Table  1611.8,  or  780  CMR  1611.8. 
Where  both  positive  pressure  and  suction  are 
specified,  the  effects  of  each  shall  be  evaluated. 

1611.8.1  Roof  shapes  not  specified:  For  roof 
shapes  not  specified  herein,  external  wind 
pressures  shall  be  determined  as  specified  in 
780  CMR  1611.13  but  the  minimum  suction 
effect  shall  be  equal  to  0.6  times  the  reference 
wind  pressure  of  780  CMR  1611.4. 

1611.9  Internal  wind  pressures  on  roofs  of 
enclosed  structures:  Except  as  specified  otherwise 
in  780  CMR  161 1.10,  internal  wind  pressures  shall 
be  0.2  times  the  reference  wind  pressure  given  in 
780  CMR  1611  4     The  internal  pressure  shall  be 


276 


780  CMR -Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


applied  as  a  positive  pressure  or  a  suction, 
whichever  gives  the  greater  structural  effect  when 
added  to  the  external  pressure,  for  the  design  of  each 
structural  component. 

1611.10  Wind  pressures  on  roofs  over 
nonenclosed    or    partially    enclosed    structures: 

Except  as  specified  otherwise  in  780  CMR  1611.11, 
wind  pressures  for  roofs  of  partially  enclosed  or 
nonenclosed  structures  shall  be  as  follows: 

1.  When  a  structure  is  partially  enclosed,  with 
each  side  not  more  than  35%  open,  the  wind 
pressure  shall  be  the  same  as  for  an  enclosed 
structure. 

2.  When  a  structure  is  partially  enclosed,  with 
openings  essentially  all  on  one  side,  and  when 
that  side  is  more  than  35%  open,  external  wind 
pressure  shall  be  as  specified  in  Table  1611.4  or 
Table  1611.4a  and  internal  wind  pressures  shall 
be  as  specified  in  780  CMR  161 1.9  except  that  the 
value  of  internal  wind  pressure  shall  be  equal  to 
0.5  times  the  reference  wind  pressure  given  in 
Table  1611.3. 

3.  For  all  other  cases  of  partially  enclosed 
structures,  or  for  nonenclosed  structures,  the 
combined  effect  of  the  wind  pressures  above  and 
below  roofs  shall  be  equal  to  1 .25  times  the  values 
specified  in  Table  1611.8  for  the  corresponding 
roof  shapes  and  wind  directions. 

1611.11  Wind  pressures  for  parts  of  roofs:  Parts 
of  roofs  that  are  subject  directly  to  the  wind,  and 
their  local  supporting  elements,  shall  be  designed  to 
resist  the  following  pressures  in  an  outward 
direction: 

1.  Where  parts  of  roofs  subjected  directly  to  the 
wind  are  located  within  a  distance  of  1/10  the  least 
width  of  a  structure,  but  not  more  than  ten  feet, 
from  the  ridge,  eave,  or  cornice,  they  shall  resist 
a  pressure  1.7  times  the  reference  wind  pressure 
given  in  Table  161 1.4  (representing  the  combined 
internal  and  external  pressures). 

2.  Where  parts  of  roofs  subjected  directly  to  the 
wind  are  located  outside  the  zones  specified  in 
780  CMR  1611.11.1  they  shall  resist  pressures  as 
specified  in  780  CMR  1611.8  through  1611.10 
and  Table  1611.8. 

A  local  supporting  element  of  a  part  of  a  roof  shall 
be  defined  as  a  roof  deck  element,  purlin,  rafter,  or 
similar  item  which  distributes  the  wind  load  from  the 
roof  part  to  the  principal  structural  system  of  the 
structure. 

1611.12  Wind  load  on  signs,  towers,  exposed 
framing,  tanks,  stacks  and  chimneys:  Signs, 
towers,  exposed  framing,  tanks,  stacks,  chimneys, 
and  similar  structures,  or  parts  thereof,  shall  be 
designed  for  wind  forces  determined  by  applying 
coefficients  given  for  the  applicable  structure  in 
Tables  12  through  16  of  ASCE-7  for  the  applicable 


reference  wind  pressures  given  in  Table  1611.4, 
multiplied  by  0.75. 

1611.12.1  Shielding:  Shielding  effect  of  one 
element  by  another  shall  not  be  considered  when 
the  distance  between  them  exceeds  four  times  the 
projected  smallest  dimensions  of  the  windward 
element. 

1611.12.2  Signs:  For  open  or  solid  outdoor  signs 
with  ratios  of  dimensions  with  the  limits  stated 
below,  a  wind  load  applied  uniformly  over  the 
area  of  the  sign  and  determined  by  the  lesser  of 
1.2P  on  the  projected  gross  area  within  the  outside 
dimensions  of  the  sign,  or  1.6P  on  the  net 
projected  area  of  the  sign;  whichever  is  less,  may 
be  used  in  lieu  of  the  loads  given  in  ASCETr 
where  "P"  is  the  reference  wind  pressure  given  in 
Table  1611.4  for  a  height  equal  to  the  average 
height  of  the  sign  above  the  ground. 

1 .  Ground  supported  signs  (whose  bottom  is 
0.25  times  the  vertical  height  from  the  ground 
to  the  top  of  the  sign):  height  to  width  ratio  less 
than  ten. 

2.  Above  ground  signs:  largest  to  smallest 
dimension  ratio  less  than  20. 

1611.13  Wind  forces  and  pressures  using  wind 
tunnel  tests:  Design  wind  forces  and  pressures  may 
be  determined  by  appropriate  wind  tunnel  tests  on 
specific  structures  as  stipulated  by  the  responsible 
design  engineer  and  approved  by  the  building 
official.  The  wind  tunnel  test  program  shall 
adequately  represent  the  relevant  properties  of  the 
structure  and  its  surroundings  and  the  oncoming 
wind  flow.  The  wind  tunnel  tests  may  be  combined 
with  a  detailed  statistical  study  of  meteorological 
records,  including  high  level  wind  velocity  and 
direction,  from  stations  near  the  proposed  structure. 
The  wind  effects  used  for  design  of  the  structure 
shall  be  not  less  than  those  corresponding  to  an 
event  having  an  annual  probability  of  occurrence  of 
0.01.  In  lieu  of  a  detailed  statistical  study  of 
meteorological  records,  the  appropriate  reference 
wind  velocity  stipulated  in  780  CMR  1611.3  may  be 
used. 

The  wind  forces  and  pressures  so  determined,  plus 
an  appropriate  allowance  for  stack  effects  and 
internal  pressures  may  be  used  for  the  design  of  the 
structure  as  a  whole,  and  its  individual  parts. 
However,  these  values  of  forces  and  pressures  shall 
not  be  less  than  .8  of  the  values  required  by 
780  CMR  1611.5,  1611.7  and  1611.12,  as 
applicable,  for  reference  wind  pressures  for 
Exposure  A  and  the  appropriate  wind  zone  specified 
in  Table  1611.4. 

1611.14  Uplift,  overturning  and  sliding: 

1611.14.1  Anchorage,  roofs  and  walls:       All 

parts  of  a  structure  subjected  directly  to  the  wind 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


277 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


shall  be  anchored  to  the  supporting  structure,  to 
resist  specified  wind  loads  inwardly  or  outwardly. 

1611.14.2    Anchorage,  structural  system:  The 

design  of  the  structural  system  and  its  elements 
for  uplift,  overturning  moment,  or  horizontal 
shear,  or  their  combination,  shall  provide 
anchorage  resistance  required  by  the  load 
combinations  specified  in  780  CMR  1616.0 

1611.15       Eccentricity       of       wind        forces: 

Consideration  shall  be  given  to  the  effects  of 
specified  wind  forces  being  applied  eccentrically  to 
the  center  of  rigidity  of  a  structure. 

780  CMR  1612.0  EARTHQUAKE  LOADS 

1612.1  Purpose:  780  CMR  1612.0  presents  criteria 
for  the  design  and  construction  of  buildings,  and 
structures  subject  to  earthquake  ground  motions. 
The  purposes  of  780  CMR  1612.0  is  to  minimize  the 
hazard  to  life  to  occupants  of  all  buildings  and  non 
building  structures,  to  increase  the  expected 
performance  of  higher  occupancy  structures  as 
compared  to  ordinary  structures,  and  to  improve  the 
capability  of  essential  facilities  to  function  during 
and  after  an  earthquake.  Because  of  the  complexity 
of  and  the  great  number  of  variables  involved  in 
seismic  design  (e.g.  the  variability  in  ground  motion, 
soil  types,  dynamic  characteristics  of  the  structure, 
material  strength  properties  and  construction 
practices),  780  CMR  1612.0  presents  only  minimum 
criteria  in  general  terms.  These  minimum  criteria 
are  considered  to  be  prudent  and  economically 
justified  for  the  protection  of  life  safety  in  buildings 
subject  to  earthquakes.  It  must  be  emphasized  that 
absolute  safety  and  prevention  of  damage,  even  in  an 
earthquake  event  with  a  reasonable  probability  of 
occurrence,  cannot  be  achieved  economically  for 
most  buildings. 

The  "design  earthquake"  ground  motion  levels 
specified  herein  may  result  in  both  structural  and 
non  structural  damage.  For  most  structures  designed 
and  constructed  according  to  780  CMR  1612.0,  it  is 
expected  that  structural  damage  from  a  major 
earthquake  may  be  repairable  but  the  repair  may  not 
be  economical.  For  ground  motions  larger  than  the 
design  levels,  the  intent  of  780  CMR  1612.0  is  that 
there  be  a  low  likelihood  of  building  collapse. 

1612.2  General:  Every  building  and  structure  shall 
be  designed  and  constructed  to  resist  the  effects  of 
earthquake  motions  determined  in  accordance  with 
this  section.  Additions  and  changes  of  occupancy  to 


existing  buildings  and  structures  shall  be  designed 
and  constructed  to  resist  the  effects  of  earthquake 
motions  determined  in  accordance  with  this  section. 
Special  structures,  including  but  not  limited  to 
vehicular  bridges,  transmission  towers,  industrial 
towers  and  equipment,  piers  and  wharves,  and 
hydraulic  structures  shall  be  designed  for  earthquake 
loads  utilizing  an  approved,  substantiated  analysis. 

Exceptions: 

1 .  Detached  one-  and  two-family  dwellings  are 
exempt  from  the  requirements  of  780  CMR 
1612.2. 

2.  Agricultural  storage  buildings  which  are 
intended  only  for  incidental  human  occupancy  are 
exempt  from  the  requirements  of  780  CMR 
1612.2 

1612.2.1  Additions  to  existing  buildings:  An 

addition  to  an  existing  building  shall  be  designed 
and  constructed  in  accordance  with  the 
requirements  of  780  CMR  34. 

1612.2.2  Change  of  occupancy:  Where  a  change 
of  occupancy  occurs  in  an  existing  building,  the 
building  shall  conform  to  the  provisions  of 
780  CMR  34. 

1612.2.3  Seismic  ground  acceleration  maps: 

The  effective  peak  velocity-related  acceleration 
(Av)  and  the  effective  peak  acceleration  (Aa)  shall 
each  be  taken  as  0. 12g  throughout  Massachusetts 
for  the  purposes  of  seismic  design  in  accordance 
with  780  CMR. 

1612.2.4  Site-specific  response  spectra:  Where 
site-specific  response  spectra  are  required  for 
buildings  assigned  to  Seismic  Performance 
Category  D  in  accordance  with  Table  1612.4.6.2. 
the  site-specific  response  spectra  shall  be 
developed  based  on  ground  motions  which  have 
a  90%  probability  of  not  being  exceeded  in  50 
years. 

1612.2.5  Seismic  Hazard  Exposure  Groups:  All 

buildings  shall  be  assigned  to  one  of  the  Seismic 
Hazard  Exposure  Groups  in  accordance  with 
Table  1612.2.5. 

1612.2.5.1  Multiple  occupancies:  Where  a 
building  is  occupied  for  two  or  more 
occupancies  not  included  in  the  same  Seismic 
Hazard  Exposure  Group,  the  building  shall  be 
assigned  the  classification  of  the  highest 
Seismic  Hazard  Exposure  Group  occupancy. 


278 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


Table  1612.2.5 
SEISMIC  HAZARD  EXPOSURE  GROUP 


Seismic  Hazard 

Exposure  Group  type 

Nature  of  occupancy 

and  description 

Group  I 

All  occupancies  except  those  listed 

below 

Group  II 

1. 

Use  Group  A  in  which  more  than 

Seismic  Hazard  Expos- 

300 people  congregate  in  one  area. 

ure  Group  II  buildings 

2. 

Use  Group  E  with  an  occupant 

are  those  which  have  a 

load  greater  than  250. 

substantial  public  haz- 

3. 

Use  Group  B  used  for  college  or 

ard  due  to  occupancy  or 

adult  education  with  an  occupant 

use,,  including  build- 

load grater  than  500. 

ings  containing  anv  one 

4 

Use  Group  1-2  with  an  occupant 

or  more  of  the  indicated 

load  greater  than  50,  not  having 

occupancies 

surgery  or  emergency  treatment 
facilities. 

5 

Use  Group  1-3 

6 

Power  generating  stations  and 
other  public  utility  facilities  not 
included  in  Seismic  Hazard 
Exposure  Group  III 

7 

Any  other  occupancy  with  an 
occupancy  load  greater  than  5.000 

Group  III 

1 

Fire,  rescue  and  police  stations 

Seismic  Hazard 

2. 

Use  Group  1-2  having  surgery  or 

Exposure  Group  III 

emergency  treatment  facilities. 

buildings  are  those  hav- 

3. 

Emergency  preparedness  centers 

ing  essential  facilities 

4, 

Post-earthquake  recovery  vehicle 

which  are  required  for 

garages. 

5 

Power-generating  stations  and 

recovery,  including 

other  utilities  required  as 

buildings  containing 

emergency  backup  facilities. 

any  one  ore  more  of  the 

6. 

Primary  communcation  facilities. 

indicated  occupancies. 

7 

High  toxic  materials  as  defined  by 
7S0  CMR  307.0  where  the 
quantify  of  the  material  exceeds 
the  exempt  amounts  of  780  CMR 

307.8 

1612.2.6  Group  ITJ  building  protected  access. 

Where  operational  access  to  a  Seismic  Hazard 
Exposure  Group  III  building  is  required  through 
an  adjacent  building,  the  adjacent  building  shall 
conform  to  the  requirements  for  Group  III 
buildings.  Where  operational  access  is  less  than 
ten  feet  (30.48  m)  from  the  interior  lot  line  or 
another  building  on  the  same  lot,  protection  from 
potential  falling  debris  from  adjacent  property 
shall  be  provided  by  the  owner  of  the  Seismic 
Hazard  Exposure  Group  III  building. 

1612.2.7  Seismic  Performance  Category:  All 

buildings  shall  be  assigned  a  Seismic  Performance 
Category  as  follows; 


Seismic  Hazard  Exposure  Group 
(from  Table  1612.2.5) 

Seismic  Performance 
Category 

I 

C 

II 

C 

III 

D 

1612.3  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  1612.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 


Acceleration: 

Effective  peak:  Coefficient  Aa,  in  accordance 
with  780  CMR  1612.2.3,  for  determining  the 
prescribed  seismic  forces. 

Effective  peak  velocity-related:  Coefficient  Av, 
in  accordance  with  780  CMR  1612.2.3,  for 
determining  the  prescribed  seismic  forces. 

Base:  The  level  at  which  the  horizontal  seismic 
ground  motions  are  considered  to  be  imparted  to 
the  building. 

Base  shear:  Total  design  lateral  force  or  shear  at  the 
base  of  the  building. 

Bay  (part  of  a  structure):  The  space  between  two 
adjacent  piers  or  mullions  or  between  two 
adjacent  lines  of  columns. 

Design  earthquake:  The  earthquake  that  produces 
ground  motions  at  the  site  under  consideration 
which  has  a  90%  probability  of  not  being 
exceeded  in  50  years. 

Designated  seismic  systems:  The  seismic-resisting 
system  and  those  architectural,  electrical  and 
mechanical  systems  and  their  components  that 
require  special  performance  characteristics. 

Diaphragm:  A  horizontal,  or  nearly  horizontal, 
portion  of  the  seismic-resisting  system,  which  is 
designed  to  transmit  seismic  forces  to  the  vertical 
elements  of  the  seismic-resisting  system. 

Frame: 

Braced:  An  essentially  vertical  truss,  or  its 
equivalent,  of  the  concentric  or  eccentric  type  that 
is  provided  in  a  loadbearing  wall,  building  frame 
or  dual  system  to  resist  seismic  forces. 
Concentrically  braced  frame  (CBF):  A  braced 
frame  in  which  the  members  are  subjected 
primarily  to  axial  forces. 

Eccentrically  braced  frame  (EBF):  A  diagonally 
braced  steel  frame  in  which  at  least  one  end  of 
each  brace  frames  into  a  beam  a  short  distance 
from  a  beam-column  joint  or  from  another 
diagonal  brace.  These  short  beam  segments  are 
called  link  beams.  The  following  EBF  definitions 
apply: 

Diagonal  brace:  A  member  of  an  EBF  placed 

diagonally  in  the  bay  of  the  frame. 

Lateral      support      members:      Secondary 

members  designed  to  transmit  seismic-resisting 

system. 

Link  beam:  The  horizontal  beam  in  an  EBF 

which    has    a   length   of  the    clear   distance 

between  the  diagonal  braces  or  between  the 

diagonal  brace  and  the  column  face. 

Link  beam  end  web  stiffeners:  Vertical  web 

stiffeners  placed  on  the  sides  of  the  web  at  the 

diagonal  brace  end(s)  of  the  link  beam. 

Link    beam    intermediate    web    stiffener: 

Vertical  web  stiffeners  placed  within  the  link 

beam. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


279 


780  CMR:    STATE  BOARD  OF  BUTLDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Link  beam  rotation  angle:  The  angle  between 

the  beam  outside  of  the  link  beam  and  the  link 

beam  occurring  at  a  total  story  drift  of  the 

deflection  amplification  factor  (C^)  times  the 

elastic  drift  at  the  prescribed  design  forces.  The 

rotation  angle  is  permitted  to  be  computed 

assuming  the  EBF  bay  is  deformed  as  a  rigid, 

ideally  plastic  mechanism. 

Intermediate  moment  frame:  A  frame  in  which 

members  and  joints  are  capable  of  resisting  forces 

by  flexure  as  well   as   along  the  axis  of  the 

members.     Intermediate     moment     frames     of 

reinforced  concrete  shall  conform  to  780  CMR 

1903.3.2. 

Ordinary  moment  frame:  A  frame  in  which 
members  and  joints  are  capable  of  resisting  forces 
by  flexure  as  well  as  along  the  axis  of  the 
members. 

Space  frame:  A  structural  system  composed  of 
interconnected  members,  other  than  loadbearing 
walls,  that  is  capable  of  supporting)  vertical  loads 
and,  if  so  designed,  resist  the  seismic  forces. 
Special  moment  frame:  A  frame  in  which 
members  and  joints  are  capable  of  resisting  forces 
by  flexure  as  well  as  along /the  axis  of  the 
members.  Special  moment  frames  shall  conform 
to  the  applicable  requirements  of  780  CMR 
1903.0  or  2204.0. 

Frame  system: 

Building:  A  structural  system  with  an  essentially 
complete  space  frame  providing  support  for 
vertical  loads.  Seismic  force  resistance  is 
provided  by  shear  walls  or  braced  frames. 
Dual:  A  structural  system  with  an  essentially 
complete  space  frame  providing  support  for 
vertical  loads.  A  moment-resisting  frame  shall  be 
provided  which  shall  be  capable  of  resisting  at 
least  25%  of  the  prescribed  seismic  forces.  The 
total  seismic  force  resistance  is  provided  by  the 
combination  of  the  moment-resisting  frame 
together  with  shear  walls  or  braced  frames  in 
proportion  to  their  relative  rigidities. 
Moment  resisting:  A  structural  system  with  an 
essentially  complete  space  frame  providing 
support  for  vertical  loads.  Seismic  force 
resistance  is  provided  by  special,  intermediate  or 
ordinary  moment  frames  capable  of  resisting  the 
total  prescribed  forces. 

High-temperature  energy  source:  A  fluid,  gas  or 
vapor  whose  temperature  exceeds  220°F  (104°C). 

Inverted  pendulum-type  structures:  Structures  that 
have  a  large  portion  of  their  mass  concentrated 
near  the  top  and  thus  have  essentially  one  degree 
of  freedom  in  horizontal  translation.  The 
structures  are  usually  T-shaped  with  a  single 
column  supporting  the  beams  or  slab  at  the  top. 

Light-framed  wall  with  shear  panels:  Wood  or 
steel  stud  walls  with  finishes  other  than  masonry 
veneer.     Loadbearing  wall  system:  A  structural 


system  with  loadbearing  walls  providing  support 
for  all,  or  major  portions  of,  the  vertical  loads. 
Shear  walls  or  braced  frames  provide  seismic 
force  resistance. 

P-Delta  effect:  The  secondary  effect  on  shears  and 
moments  of  frame  members  due  to  the  action  of 
the  vertical  loads  induced  by  displacement  of  the 
building  frame  resulting  from  lateral  forces. 

Resilient  stable-mounting  system:  A  system 
incorporating  helical  springs,  air  cushions,  rubber- 
in-shear  mounts,  fiber-in-shear  mounts,  or  other 
comparable  approved  systems.  The  force 
displacement  ratios  are  equal  in  the  horizontal  and 
vertical  directions 

Restraining  device:  A  device  used  to  limit  the 
vertical  or  horizontal  movement  of  the  mounting 
system  due  to  earthquake  motions. 
Elastic:  A  fixed  restraining  device  that 
incorporates  an  elastic  element  to  reduce  the 
seismic  forces  transmitted  to  the  structure  due  to 
impact  from  the  resilient  mounting  system. 
Fixed:  A  nonyielding  or  rigid  type  of  restraining 
device. 

Seismic  activated:  An  interactive  restraining 
device  that  is  activated  by  earthquake  motion. 

Seismic-resisting  system:  That  part  of  the  structural 
system  that  has  been  considered  in  the  design  to 
provide  the  required  resistance  to  the  seismic 
forces  prescribed  herein. 

Shear  wall:  A  wall,  loadbearing  or  nonloadbearing, 
designed  to  resist  seismic  forces,  from  other  than 
its  own  mass,  acting  in  the  plane  of  the  wall. 

Story  drift  ratio:  The  story  drift  divided  by  the 
story  height. 

Story  shear:  The  summation  of  design  lateral  forces 
at  levels  above  the  story  under  consideration. 

1612.4  Structural  design  requirements: 

1612.4.1  Design  Basis:  The  seismic  analysis  and 
design  procedures  utilized  in  the  design  of 
buildings  and  their  structural  components  shall  be 
in  accordance  with  the  requirements  of  780  CMR 
1612.4.  The  design  seismic  forces  and  their 
distribution  over  the  height  of  the  building  shall 
be  in  accordance  with  the  procedures  in  780  CMR 
1612.5  or  1612.6.  The  corresponding  internal 
forces  in  the  structural  components  of  the  building 
shall  be  determined  using  a  linearly  elastic  model. 
An  alternate  procedure  using  structural 
concepts  other  than  as  specified  in  this  section 
may  be  used,  if  approved  by  the  building  offical, 
to  establish  the  design  forces  and  their 
distribution.  Such  an  alternate  procedure  may  be 
permitted  where  evidence  is  submitted  to  the 
building  official  showing  that  equivalent  ductility 
and  energy  dissipation  are  provided,  and  the 
corresponding  internal  forces  and  deformations  in 


280 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


the  structural  components  are  determined  using  a 
model  consistent  with  the  approved  procedure. 

Individual  structural  members  shall  be 
designed  for  the  shear  forces,  axial  forces  and 
moments  determined  in  accordance  with 
780  CMR  1612.4.  Connections  shall  be  designed 
to  develop  the  strength  of  the  connected  members 
or  the  analysis  force,  whichever  is  less.  The 
design  story  drift  of  the  building,  calculated  as 
specified  herein,  shall  not  exceed  the  allowable 
story  drift  of  780  CMR  1612.4.8,  when  the 
building  is  subjected  to  the  design  seismic  forces. 

A  continuous  load  path,  or  paths,  with  adequate 
strength  and  stiffness  shall  be  provided  to  transfer 
all  forces  from  the  point  of  application  to  the  final 
point  of  resistance.  The  foundation  shall  be 
designed  to  resist  the  forces  developed  and  shall 
accomodate  the  movements  imparted  to  the 
building  by  the  design  ground  motions.  The 
foundation  design  criteria  shall  account  for  the 
dynamic  nature  of  the  seismic  forces,  the  design 
ground  motions  and  the  design  basis  for  strength 
and  ductility  of  the  structure. 

Consideration  shall  be  given  to  the  manner  in 
which  the  earthquake  lateral  force,  computed  in 
accordance  with  780  CMR  1612.5  or  1612.6  will 
be  transmitted  from  the  soil  or  rock  to  the 
structure.  Transmission  of  the  lateral  force  will 
occur  through  one  or  more  of  the  following 
foundation  elements: 

a.      Lateral  soil  pressure  against  foundation 

walls,  footings,  grade  beams  and  pile  caps; 


b.  Lateral  soil  pressure  against  piles,  piers  or 
caissons; 

c.  Side  or  bottom  friction  on  walls,  footings  or 
mats  or; 

d.  Batter  piles. 

Bottom  friction  under  pile  caps  shall  be  assumed 
to  be  ineffective  in  transmitting  horizontal  forces. 
The  horizontal  force  shall  be  distributed  among 
the  various  elements  in  the  foundation  in 
proportion  to  their  estimated  rigidities.  Any 
element  which  will  participate  in  the  transfer  of 
horizontal  forces  from  the  soil  to  the  structure 
shall  be  designed  to  resist  forces  in  such  a  way 
that  its  ability  to  sustain  static  load  will  not  be 
impaired. 

1612.4.2  Site  coefficient:  The  value  of  the  site 
coefficient  (S)  shall  be  determined  from  Table 
1612.4.1.  In  locations  where  the  soil  properties 
are  not  known  in  sufficient  detail  to  determine 
the  soil-profile  type  or  where  the  soil  profile  does 
not  fit  any  of  the  four  types  indicated  in  Table 
1612.4.1,  a  site  coefficient  (S)  of  1.5  shall  be 
used.  For  determination  of  Site  Coefficient,  all 
soil  and  rock  below  the  final  ground  surface  shall 
be  considered. 

When  a  structure  is  located  on  soil  deposits 
meeting  the  criteria  for  two  or  more  site 
coefficient  values,  the  largest  applicable  value 
shall  be  used. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


281 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1612.4.1 
SITE  COEFFICIENT 


Soil- 
profile 
type 


Description 


Site 

Coefficient 

S 


A  profile  consisting  of: 
Rock  of  Material  Classes  1  through  4,  or. 
Rock  of  any  characteristic,  either  shale- 
like or  crystalline  in  nature,  which  has  a 
shear  wave  velocity  greater  than  2,500 
feet  per  second,  or; 

Stiff  soil  conditions  where  the  soil  depth 
is  less  than  200  feet  and  the  soil  types 
overlying  rock  are  stable  deposits  of 
weathered  bedrock  of  Material  Class  5; 

S,       dense  to  very  dense  till,  gravel  or  sand  1.0 

and  gravel  of  Materials  Classes  6  and  7; 
dense  to  very  dense  sand  of  Material 
Classes  8  and  9;  dense  inorganic  silt  of 
Material  Class  9;  stiff  to  hard  clay  of 
Material  Class  10  with  undrained  shear 
strength  of  2,000  pounds  per  square  foot 
or  greater,  or;  compacted  granular  fills 
provided  that  the  fill  soils  are  compacted 
throughout   as  required  in  780   CMR 

1804.1 

A  soil  profile  meeting  the  requirements 
for  S,  except  the  soil  depth  exceeds  200 
feet;  or  a  soil  profile  which  contains  up 
to  40  feet  of  medium  stiff  clay  (Material 
Class  10),  with  undrained  shear  strength 

„  of  1,000  pounds  per  square  foot  or 
2  greater,  or  a  soil  profile  which  contains 
up  to  40  feet  of  medium  dense  gravel, 
sand  and/or  silt  (Material  Classes  7 
through  10),  that  is  not  susceptible  to 
liquefaction       in       accordance       with 

7S0  CMR  1802.2 

A  soil  profile  containing  40  to  100  feet 
in  thickness  of  medium  stiff  clay 
(Material  Class  10)  with  undrained  shear 
strength  of  1,000  pounds  per  square  foot 
or  greater,  with  or  without  intervening 
layers  of  granular  soils;  or  up  to  40  feet 
of  soft  clay  (Material  Class    10)  with 

53  undrained  shear  strength  of  less  than         1.5 
1 ,000  pounds  per  square  foot;  or  up  to  40 

feet  of  very  loose  to  loose  gravel,  sand  or 
silt  (Material  Classes  7  through  9);  or  up 
to  20  feet  of  organic  soil  (Material  Class 
1 1)  or  loose  or  soft  fill  which  was  not 
placed  in  accordance  with  780  CMR 
1804.1 

54  A  soil  profile  containing  more  than  1 00  2.0 
feet  of  medium  stiff  clay  (Material  Class 

10)  with  undrained  shear  strength  of 
1 ,000  pounds  per  square  foot  or  greater, 
with  or  without  intervening  layers  of 
granular  soils;  or  more  than  40  feet  of 
soft  clay  (Material  Class  10)  with 
undrained  shear  strength  of  less  than 
1 ,000  pounds  per  square  foot;  or  more 
than  40  feet  of  very  loose  to  loose  sand 
or  silt  (Material  Classes  8  and  9);  or 
more  than  20  feet  of  organic  soil 
(Material  Class  II);  or  more  than  20 
feet  of  loose  or  soft  fill  which  was  not 
placed  in  accordance  with  780  CMR 
1 804 , 1 ;  or  more  than  20  feet  of  soils  of 
any  type  having  a  shear  wave  velocity  of 
500  feet  per  second  or  less. 


Notes: 

a)  1  foot  =  304.8  mm 

b)  See  appendix  G  for  guidance  in  selecting  Material 
Classes 

1612.4.3  Soil-structure  interaction:  The  design 
base  shear,  story  shears,  overturning  moments  and 
deflections  determined  by  the  requirements  of 
780  CMR  1612.5  or  1612.6  are  permitted  to  be 
modified  in  accordance  with  approved  procedures 
which  account  for  the  effects  of  soil-structure 
interaction. 

1612.4.4  Structural  framing  systems:  The  basic 
structural  framing  systems  to  be  utilized  are 
indicated  in  Table  1612.4.4.  Each  type  is 
subdivided  by  the  types  of  vertical  structural 
elements  that  will  resist  the  design  lateral  forces. 
The  structural  system  utilized  shall  be  in 
accordance  with  the  seismic  performance  category 
and  height  limitations  indicated  in  Table  1612.4.4. 
The  appropriate  response  modification  factor  (R) 
and  the  deflection  amplification  factor  (Cd) 
indicated  in  Table  1612.4.4  shall  be  utilized  in 
determining  the  base  shear  and  the  design  story 
drift.  Structural  framing  and  seismic-resisting 
systems  which  are  not  contained  in  Table 
1612.4.4  shall  be  permitted  if  analysis  and  test 
data  are  submitted  that  establish  the  dynamic 
characteristics  and  demonstrate  the  lateral  force 
resistance  and  energy  dissipation  capacity  to  be 
equivalent  to  the  structural  systems  listed  in  Table 
1612.4.4  for  equivalent  response  modification 
factor  (R)  values. 

1612.4.4.1  Dual  system:  For  a  dual  system,  the 
moment  frame  shall  be  capable  of  resisting  at 
least  25%  of  the  design  seismic  forces.  The 
total  seismic  force  resistance  is  to  be  provided 
by  the  combination  of  the  moment  frame  and 
the  seismic-resisting  elements  in  proportion  to 
their  rigidities. 

1612.4.4.2  Combinations  of  framing 
systems:  Different  structural  framing  systems 
are  permitted  along  the  two  orthogonal  axes  of 
the  building.  Combinations  of  framing  systems 
shall  comply  with  the  requirements  of 
780  CMR  1612.4.4.2.1  and  1612.4.4.2.2 
1612.4.4.2.1  Combination  framing  factor 
(R):  The  response  modification  factor  (R)  in 
the  direction  under  consideration  at  any  story 
shall  not  exceed  the  lowest  response 
modification  factor  (R)  obtained  from  Table 
1612.4.4  or  the  seismic-resisting  system  in  the 
same  direction  considered  above  that  story. 
Exception:  Supported  structural  systems  with 
weight  equal  to  or  less  than  10%  of  the  weight 
of  the  building  are  not  required  to  comply  with 
780  CMR  1612.4.4.2.1. 


282 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


1612.4.4.2.2  Combination  framing  detailing 
requirements:  The  detailing  requirements  of 
780  CMR  1612.4.7  required  by  the  higher 
response  modification  factor  (R)  shall  apply  to 
structural  components  common  to  systems 
having  different  response  modification  factors. 

1612.4.4.3  Seismic  Performance  Category  C 
The  structural  framing  system  for  buildings 
assigned  to  Seismic  Performance  Category  C 
shall  comply  with  the  building  height  and 
structural  system  limitations  in  Table  1612.4.4. 

1612.4.4.4  Seismic  Performance  Category  D 
The  structural  framing  system  for  buildings 
assigned  to  Seismic  Performance  Category  D 
shalicomply  with  780  CMR  1612.4.4.3  and  the 
additional  provisions  of  780  CMR  1612.4.4 

1612.4.4.4.1  Limited  building  height 
Buildings  having  a  structural  system  of  steei 
or  cast-in-place  concrete-braced  frames  or 
shear  walls  are  limited  to  a  height  of  240  feet 
(73 .15  m)  where  there  are  braced  frames  or 
shear  walls  so  arranged  that  braced  frames  or 
shear  walls  in  one  plane  resist  not  more  than 


the  following  proportion  of  the  seismic 
design  force  in  each  direction,  including 
torsional  effects: 

1 .  60%  where  the  braced  frame  or  shear 
walls  are  arranged  only  on  the  perimeter; 

2.  40%  where  some  of  the  braced  frames 
or  shear  walls  are  arranged  on  the 
perimeter,  or 

3.  30%  for  other  arrangements 
1612.4.4.4.2  Interaction  effects  Moment- 
resisting  frames  that  are  enclosed  or 
adjoined  by  more  rigid  elements  not 
considered  to  be  pan  of  the  seismic-resisting 
system  shall  be  designed  so  that  the  action 
or  failure  of  the  enclosing  or  adjoining 
elements  will  not  impair  the  vertical  load 
and  seismic  force-resisting  capability  of  the 
frame.  The  design  shall  provide  for  the 
effect  of  these  rigid  elements  on  the 
structural  system  at  building  deformations 
corresponding  to  the  design  story  drift 
(delta)  as  determined  in  780  CMR  1612.5.5 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


283 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  1612.4.41  ' 
Structural  Systems 

Basic  Structural  system 

Response 
Modification 
Factor  (R) 

Deflection 
Amplification 
Factor  (Cd) 

Structural  system  limitations 
and  building  height  (feet) 
limitations  (see  Note  b) 

Seismic  Performace  Category 

Seismic  Resisting  System 

C 

D 

1  -  Loadbearing  wall  system 

Light-framed  walls  with  shear  panels 

654 

4 

Not  limited 

160 

Reinforced  concrete  shear  walls 

4  54 

4 

Not  limited 

160 

Reinforced  masonry  shear  walls 

354 

3 

Not  limited 

160 

Concentrically  braced  frames 

y/z 

354 

Not  limited 

160 

Unreinforced  masonry  shear  walls 

VA 

VA 

Not  permitted 

Not  permitted 

Plain  concrete  shear  walls 

154 

VA 

Not  permitted 

Not  permitted 

2.  Building  Frame  System 

Eccentrically  braced  frames,  moment  resisting  connections  at 
columns  awav  from  link  beam 

8 

4 

Not  limited 

160 

Eccentrically  braced  frames  nonmoment-resi sting  connections 
at  columns  away  from  link  beam 

7 

4 

Not  limited 

160 

Light-framed  walls  with  shear  panels 

7 

454 

Not  limited 

160 

Concentrically  braced  frames 

5 

454 

Not  limited 

160 

Reinforced  concrete  shear  walls 

\554 

5 

Not  limited 

160 

Reinforced  masonry  shear  walls 

454 

4 

Not  limited 

160 

Unreinforced  masonrv  shear  walls 

114 

154 

Not  permitted 

Not  permitted 

Plain  concrete  shear  walls 

2 

2 

Not  permitted 

Not  permitted 

3 .  Moment-resisting  frame  svstem 

Special  moment  frames  of  steel 

8 

5'/= 

Not  limted 

Not  limited 

Special  moment  frames  of  reinforced  concrete 

8 

554 

Not  limited 

Not  limited 

Intermediate  moment  frames  of  reinforced  concrete 

5 

454 

Not  limited 

Not  permitted 

Ordinary  moment  frames  of  steel 

454 

4 

Not  limited 

160 

Ordinary  moment  frame  of  reinforced  concrete 

3 

254 

Not  permitted 

Not  permitted 

4.  Dual  system  with  a  special  moment  frame  capable  of  resisting 
at  least  25%  of  the  prescribed  seismic  forces  Eccentrically 
braced  frames,  moment-resisting  connections  at  columns 
awav  from  link  beam 

8 

4 

Not  limited 

Not  limited 

Eccentrically  braced  frames,  nonmoment-resisting 
connections  at  columns  awav  from  link  beam 

7 

4 

Not  limited 

Not  limited 

Concentrically  braced  frames 

6 

5 

Not  limited 

Not  limited 

Reinforced  concrete  shear  walls 

8 

654 

Not  limited 

Not  limited 

Reinforced  masonry  shear  walls 

654 

554 

Not  limited 

Not  limited 

Wood-sheathed  shear  walls 

8 

5 

Not  limited 

Not  limited 

5.  Dual  system  with  an  intermediate  moment  frame  of  reinforced 
concrete  or  an  ordinary  moment  frame  of  steel  capable  of 
resisting  at  least  25%  of  the  prescribed  seismic  forces 

Concentrically  braced  frames 

5 

454 

Not  limited 

160 

Reinforced  concrete  shear  walls 

6 

5 

Not  limited 

160 

Reinforced  masonry  shear  walls 

5 

414 

Not  limited 

160 

Wood-sheathed  shear  walls 

7 

454 

Not  limited 

160 

6.  Inverted  Pendulum  structures  Special  moment  frames  of 
structural  steel 

254 

214 

Not  limited 

Not  limited 

Special  moment  frames  of  reinforced  concrete 

254 

214 

Not  limited 

Not  united 

Ordinary  moment  frames  of  structural  steel 

VA 

VA 

Not  limited 

Not  permitted 

Note  a.  Response  modification  factor(R)  for  application  of  780  CMR  1612.5  and  1612.6:  Deflection  amplificaton  factor 

(Cd)  for  application  of  780  CMR  1612.5  and  1612.6. 

Note  b.   The  building  height  shall  not  exceed  the  general  height  limitation  of  780  CMR  503.0  and  502.0  based  on  the 

type  of  construction 

Note  c.  See  780  CMR  1612.4  4.4.  lfor  description  of  building  systems  which  are  limited  to  buildings  with  a  height  of 

240  feet  or  less. 

Note  d.  See  780  CMR  1612.4.4.5  for  description  of  building  systems  which  are  limited  to  buildings  with  a  height  of 

160  feet  or  less 


284 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


1612.4.4.3.3  Deformational  compatibility: 

Every  structural  component  not  included  in 
the  seismic  force-resisting  system  in  the 
direction  under  consideration  shall  be 
designed  to  be  adequate  for  the  vertical 
load-bearing  capacity  and  the  induced 
moments  resulting  from  the  design  story 
drift  (a)  as  determined  in  accordance  with 
780  CMR  1612.5.5  (see  also  780  CMR 
1612.4.8) 

1612.4.4.4.4  Special  moment  frames:  A 

special  moment  frame  that  is  utilized  but  not 
required  by  Table  1612.4.4  is  permitted  to 
be  discontinuous  and  supported  by  a  more 
rigid  system  with  a  lower  response 
modification  factor  (R)  provided  that  the 
requirements  of  780  CMR  1612.4.7.2.4  and 
1612.4.7.4.2  are  met.  Where  a  special 
moment  frame  is  required  by  Table 
1612.4.4,  the  frame  shall  be  continuous  to 
the  foundation. 

1612.4.5  Building  configuration:  Buildings  shall 
be  classified  as  regular  or  irregular  based  on  the 
plan  and  vertical  configuration. 

1612.4.5.1  Plan  irregularity:  Buildings 
having  one  or  more  of  the  features  listed  in 
Table  1612.4.5.1  shall  be  designated  as  having 
plan  irregularity  and  shall  comply  with  the 
requirements  in  the  referenced  code  sections  of 
Table  1612.4.5.1. 

1612.4.5.2  Vertical  irregularity:  Buildings 
having  one  or  more  of  the  features  listed  in 
Table  1612.4.5.2  shall  be  designated  as  having 
vertical  irregularity  and  shall  comply  with  the 
requirements  in  the  referenced  code  sections  of 
Table  1612.4.5.2. 

Exceptions: 

1.  Structural  irregularities  of  Type  1  or  2  in 
Table  1612.4.5.2  do  not  apply  where  the 
building  story  drift  ratio  is  less  than  130%  of 
the  story  drift  ratio  of  the  next  story  above. 
Torsional  effects  are  not  required  to  be 
considered  in  the  calculation  of  story  drifts. 
The  story  drift  ratio  relationship  for  the  top 
two  stories  of  the  building  is  not  required  to 
be  evaluated. 

2.  Irregularity  Types  1  and  2  of  Table 
1612.4.5.2  are  not  required  to  be  considered 
for  one-  and  two-story  buildings. 


Table  1612.4.5.1 
PLAN  STRUCTURAL  IRREGULARITIES 


Irregularity  type  and  description 

Referenced 
Section 

Seismic 
Performance 

Category 
Application 

1  Torsional  irregularity  —  to  be 
considered  where  diaphragms 
are   rigid   in   relation   to   the 
vertical     structural    elements 
which  resist  the  lateral  seismic 
forces. 

Torsional  irregularity  shall  be 
considered  to  exist  where  the 
maxixmum   story   drift   com- 
puted,    including     accidental 
torsion,    at    one    end   of  the 

■ 

780  CMR 
1612.4.7.4.2 

780  CMR 
1612.5.3.1 

D 
CandD 

structure  transverse  to  an  axis 
is  more  than    1.2   times  the 
average  of  the  story  drifts  at 
the  two  ends  of  the  structure. 

2  Re-entrant  comers 

Plan     configurations     of     a 
structure  and  its  lateral  force- 
resisting    system   contain    re- 
entrant  comers,   where    both 
projections    of   the    structure 
beyond  a  re-entrant  comer  are 
greater  than  15%  of  the  plan 
dimension  of  the  structure  in 
the  given  direction. 

780  CMR 
1612.4.7.4.2 

D 

3  Diaphragm  discontinuity 

Diaphragms       with       abrupt 
discontinuities  or  variations  in 
stifness,       including       those 
having  cutout  or  open  areas 
greater  than  50%  of  the  gross 
enclosed  area  of  diaphragm,  or 
changes     in     effective     dia- 
phragm stiffness  of  more  than 
50%  from  one  story  to  the 
next. 

780  CMR 
1612.4.7.4.2 

D 

4  Out-of-plane  vertical  element 
offsets 

Discontinuities    in    a    lateral 
force-resistance  path,  such  as 
out-of-plane    offsets    of    the 
vertical  elements  which  resist 
the  lateral  seismic  forces. 

780  CMR 
1612.4.7.4.2 

D 

5  Nonparallel  systems 

The     vertical     lateral     force- 
resisting  elements  are  not  par- 
allel to,  or  are  not  symmetric 
about,   the  major   orthogonal 
axes    of    the    lateral    force- 
resisting  svstem. 

780  CMR 
1612.4.7.3.1 

CandD 

2/7'97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


285 


780  CMR:    STATE  BOARD  OF  BUILDING  P  EGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1612.4.5.2 

VERTICAL  STRUCTURAL 

IRREGULARITIES 


Irregularity  type  and  description 

Referenced 
Section 

Seismic 
Performance 

Category 
Application 

1  Stiffness    irregularity   —    soft 
story. 

A  soft  story  is  one  in  which 
the  lateral  stiffness  is  less  than 
70%  of  that  in  the  story  above 
or    less    than    80%    of    the 
average  stiffness  of  the  three 
stories  above. 

780  CMR 
1612.4.6.2 

D 

2  Weight  (mass)  irregularity 

Mass     irregularity     shall     be 
considered  to  exist  where  the 
effective  masss  of  any  story  is 
more     than     150%     of    the 
effective  mass  of  an  adjacent 
story.     A  roof  that  is  lighter 
than  the  floor  below  is  not 
required  to  be  considered. 

780  CMR 
1612.4.6.2 

D 

3  Vertical  geometric  irregularity 

Vertical  geometric  irregularity 
shall   be   considered   to   exist 
where  the  horizontal  dimen- 
sion    of    the     lateral     force- 
resisting  system  in  any  story  is 
more  than  130%  of  that  in  an 
adjacent  storv. 

780  CMR 
1612.4.6.2 

D 

4  In-plane  discontinuity  in  ver- 
tical lateral  force-resisting  ele- 
ments. 

An    in-plane    offset    of    the 
lateral  force-resisting  elements 
greater  than  the  length  of  those 
elements. 

780  CMR 
1612.4.7.4.2 

D 

5  Discontinuity   in   capacity   — 
weak  story 

A  weak  story  is  one  in  which 
the  story  lateral  strength  is  less 
than  80%  of  that  in  the  story 
above.     The  story  strength  is 
the  total  strength  of  all  seismic 
resisting  elements  sharing  the 
story  shear  for  the   direction 
under  consideration. 

780  CMR 
1612.4.7.2.4 

CandD 

1612.4.6  Analysis  procedures:  A  structural 
analysis  shall  be  made  for  all  buildings  in 
accordance  with  the  requirements  of  780  CMR 
1612.4.6.  An  alternative  generally  accepted 
procedure,  including  utilization  of  a  site-specific 
response  spectrum,  is  permitted,  where  approved 
by  the  code  official.  The  limitations  on  the  base 
shear  in  780  CMR  1612.6  apply  to  dynamic 
modal  analysis.  When  this  alternative  is  used,  the 
site  specific  response  spectrum  shall  be 
considered  in  the  required  peer  review. 

1612.4.6.1  Seismic  Performance  Category  C: 
Regular   or   irregular   buildings   assigned   to 


Category  C  shall  be  analyzed  in  accordance 
with  the  procedures  in  780  CMR  1612.5. 
1612.4.6.2  Seismic  Performance  Category  D: 

Buildings  assigned  to  Seismic  Performance 
Category  D  shall  be  analyzed  in  accordance 
with  the  referenced  sections  in  Table 
1612.4.6.2. 

Table  1612.4.6.2 

ANALYSIS  PROCEDURES  FOR  SEISMIC 

PERFORMANCE  CATEGORY  D 


Building  Description 

Referenced 
Section  and 
Procedures 

1  Buildings  designated  as  regular  which 
do  not  exceed  240  feet  in  height. 

780  CMR  1612.5 

2  Buildings  that  have  only  vertical 
irregularities  of  Type  1 ,  2  or  3  in  table 
1612.4.5.2  and  have  a  height  exceeding 
five  stories  or  65  feet,  and  all  buildings 
exceeding  240  feet  in  height. 

780  CMR  1612.6 

3  All  other  buildings  designated  as 
having  plan  or  vertical  irregularities  in 
accordance  with  tables  1612.4.5.1  and 
1612.4.5.2 

780  CMR  1612.5 

or 
780  CMR  1612.6 

1612.4.7  Design,  detailing  requirements  and 
structural  component  load  effects:  The  design 
and  detailing  of  structural  components  of  the 
seismic-resisting  system  shall  comply  with  the 
requirements  of  780  CMR  1612.4.  Foundation 
design  shall  conform  to  the  applicable 
requirements  of  780  CMR  18. 

1612.4.7.1  Seismic  Performance  Category  A: 
The  design  and  detailing  of  buildings  assigned 
to  Seismic  Performance  Category  A  shall 
comply  with  the  requirements  of  780  CMR 
1612.4.7.1. 

1612.4.7.1.1  Ties  and  continuity:  Except 
for  connections  exempted  by  780  CMR 
1612.7,  all  parts  of  the  building  that  transmit 
seismic  force  shall  be  interconnected  to  form 
a  continuous  path  to  the  building's  seismic- 
resisting  system.  Any  smaller  portion  of  the 
building  shall  be  tied  to  the  remainder  of  the 
building  with  elements  having  a  strength 
capable  of  transmitting  the  seismic  force 
(F_)  determined  in  accordance  with 
780  CMR  1612.7,  but  not  less  than  one-third 
of  the  effective  peak  velocity-related 
acceleration  (Av)  times  the  weight  of  the 
smaller  portion  (Wc)  or  5%  of  the  portion's 
weight,  whichever  is  greater.  For  a  building 
which  is  exempt  from  a  full  seismic  analysis 
by  780  CMR  1612.2  and  is  only  required  to 
comply  with  780  CMR  1612.4.7.1,  the 
building's  main  windforce-resisting  system 
in  accordance  with  780  CMR  1611.0  shall 
be  deemed  to  be  the  seismic-resisting 
system.  A  positive  connection  for  resisting 
a  horizontal  force  acting  parallel  to  the 
member  shall  be  provided  for  each  beam. 


286 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


girder  or  truss  to  its  support.  The  connection 
shall  have  a  minimum  strength  of  5%  of  the 
dead  plus  live  load  reaction. 
1612.4.7.1.2  Concrete  or  masonry  wall 
anchorage:  Concrete  and  masonry  walls 
shall  be  anchored  to  the  roof  and  all  floors 
that  provide  lateral  support  for  the  wall.  The 
anchorage  shall  provide  a  direct  connection 
between  the  walls  and  the  roof  or  floor 
construction.  Toe  nailing  or  nails  subject  to 
withdrawal  forces  is  not  permitted.  Wood 
ledgers  shall  not  be  subjected  to  cross-grain 
bending  or  cross-grain  tension.  The 
connections  shall  be  capable  of  resisting  a 
lateral  seismic  force  (F  )  in  accordance  with 
either  780  CMR  1612.4.7.2.8  or  780  CMR 
1612.7,  for  loadbearing  and  nonloadbearing 
walls  respectively,  but  not  less  than  1,000 
times  the  effective  peak  velocity-related 
acceleration  (A^)  (pounds)  per  lineal  foot  of 
wall.  Walls  shall  be  designed  to  resist 
bending  between  anchors  where  the  anchor 
spacing  exceeds  four  feet  (1.22  m). 
1612.4.7.2  Seismic  Performance  Category  B: 
Buildings  assigned  to  Category  B  shall 
conform  to  the  requirements  of  780  CMR 
1612.4.7.1  for  Category  A  and  the 
requirements  of  780  CMR  1612.4.7.2. 

1612.4.7.2.1  Component  Load  Effects: 
Seismic  load  effects  on  components  shall  be 
detemined  from  the  load  analysis  as  required 
by  780  CMR  1612.4.6,  by  other  portions  of 
780  CMR  1612.4.7.2,  and  by  780  CMR 
1616.  The  second  order  effects  shall  be 
included  where  applicable  Where  these 
seismic  load  effects  exceed  the  minimum 
load  path  connection  forces  given  in 
780  CMR  1612.4.7.1.1  and  1612.4.7.2.2, 
they  shall  govern. 

1612.4.7.2.2  Openings:  Where  openings 
occur  in  shear  walls,  diaphragms  or  other 
plate-type  elements,  the  edges  of  the 
openings  shall  be  designed  to  transfer  the 
stresses  into  the  structure.  The  edge 
reinforcement  shall  extend  into  the  body  of 
the  wall  or  diaphragm  a  distance  sufficient 
to  develop,  the  stress  of  the  edge 
reinforcement  member. 

1612.4.7.2.3  Orthogonal  effects  The 
design  seismic  forces  shall  be  applied 
separately,  and  independently,  in  each  of 
two  orthogonal  directions. 

1612.4.7.2.4  Discontinuities  in  vertical 
system:  Buildings  with  a  discontinuity  in 
lateral  capacity,  vertical  irregularity  Type  5 
as  defined  in  Table  1612.4.5.2,  shall  not  be 
more  than  two  stories  or  30  feet  (9. 14  m)  in 
height  where  the  "weak"  story  has  a 
calculated  strength  of  less  than  65%  of  the 
storey  above. 


Exception:  Where  the  "weak"  story  is 
capable  of  resisting  a  total  seismic  force 
equal  to  75%  of  the  deflection  application 
factor  (Cd)  times  the  design  force  prescribed 
in  780  CMR  1612.5. 

1612.4.7.2.5  Nonredundant  systems:  The 
building  design  shall  comply  with  780  CMR 
1604.2. 

1612.4.7.2.6  Collector  elements:  Collector 
elements  shall  be  provided  which  are 
capable  of  transferring  the  seismic  forces 
originating  in  other  portions  of  the  building 
to  the  element  providing  the  resistance  to 
those  forces. 

1612.4.7.2.7  Diaphragms:  The  deflection  in 
the  plane  of  the  diaphragm,  as  determined 
by  engineering  analysis,  shall  not  exceed  the 
allowable  deflection  of  the  attached 
elements.  Allowable  deflection  shall  be  that 
deflection  which  will  permit  the  attached 
element  to  maintain  its  structural  integrity 
under  the  individual  loading  and  continue  to 
support  the  prescribed  loads. 

Floor  and  roof  diaphragms  shall  be 
designed  to  resist  the  following  seismic 
forces:  a  minimum  force  equal  to  50%  the 
effective  peak  velocity-related  acceleration 
(A^.)  times  the  weight  of  the  diaphragm  and 
other  elements  of  the  building  attached 
thereto,  plus  the  portion  of  the  seismic  shear 
force  at  that  level  (Vx)  required  to  be 
transferred  to  the  components  of  the  vertical 
seismic-resisting  system  because  of  offsets 
or  changes  in  stiffness  of  the  vertical 
components  above  and  below  the 
diaphragm. 

Diaphragms  shall  provide  for  both  the 
shear  and  bending  stresses  resulting  from 
these  forces.  Diaphragms  shall  have  ties  or 
struts  to  distribute  the  wall  anchorage  forces 
into  the  diaphragm.  Connections  within 
diaphragms,  connections  of  diaphragms  to 
lateral  load  resisting  elements,  and 
connections  of  collectors  such  as  ties  and 
struts,  to  the  diaphragm  and  vertical 
elements,  shall  be  positive  connections, 
mechanical  or  welded. 

1612.4.7.2.8  Loadbearing  walls:  Exterior 
and  interior  loadbearing  walls  and  their 
anchorage  shall  be  designed  for  a  force  of 
the  effective  peak  velocity-related 
acceleration  (Av)  times  the  weight  of  wall, 
normal  to  the  surface,  with  a  minimum  force 
of  10%  of  the  weight  of  the  wall. 
Interconnection  of  wall  elements  and 
connections  to  supporting  framing  systems 
shall  have  sufficient  ductility,  rotational 
capacity  or  sufficient  strength  to  resist 
shrinkage,  thermal  changes  and  differential 
foundation  settlement  where  combined  with 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


>S7 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


seismic  forces.  The  connections  shall  also 
satisfy  780  CMR  1612.4.7. 1.2 

1612.4.7.2.9  Inverted  pendulum-type 
structures:  Supporting  columns  or  piers  of 
inverted  pendulum-type  structures  shall  be 
designed  for  the  bending  moment  calculated 
at  the  base  determined  by  the  procedures 
given  in  780  CMR  1612.5  and  shall  vary 
uniformly  to  a  moment  at  the  top  equal  to 
one-half  the  calculated  bending  moment  at 
the  base. 

1612.4.7.2.10  Anchorage  of 
Nonstructural  Systems:  When  required  by 
780  CMR  1612.7,  all  portions  or 
components  of  the  building  shall  be 
anchored  for  the  seismic  force  (Fp) 
prescribed  therein. 

1612.4.7.3  Seismic  Performance  Category  C: 
Buildings  assigned  to  Category  C  shall 
conform  to  the  requirements  of  780  CMR 

1612.4.7.2  for  Category  B  and  the 
requirements  of  780  CMR  1612.4.7.3. 

1612.4.7.3.1  Plan  irregularity:  Buildings 
that  have  plan  structural  irregularity  Type  5 
in  Table  1612.4.5.1  shall  be  analyzed  for  the 
critical  load  effect  due  to  direction  of 
application  of  seismic  forces.  Alternatively, 
the  building  shall  be  analyzed  in  any  two 
orthogonal  directions.  Structural  elements 
and  foundations  shall  be  designed  for  100% 
of  the  forces  for  one  direction  plus  a 
simultaneous  load  of  30%  of  the  forces  for 
the  perpendicular  direction,  except  where 
the  amplified  seismic  load  effects  of 
780  CMR  1616.4  are  used. 

1612.4.7.4  Seismic  Performance  Category  D: 
Buildings  assigned  to  Category  D  shall 
conform  to  the  requirements  of  780  CMR 

1612.4.7.3  for  Category  C  and  to  the 
requirements  of  780  CMR  1612.4.7.4. 

1612.4.7.4.1  Orthogonal  load  effects: 
Buildings  shall  be  designed  for  100%  of  the 
seismic  forces  for  one  direction  plus  a 
simultaneous  load  of  30%  of  the  seismic 
forces  for  the  perpendicular  direction.  The 
load  combination  requiring  the  maximum 
structural  component  strength  shall  be  used. 
Exception:  Where  amplified  seismic  load 
effects  of  780  CMR  1616.4  are  used,  the 
building  may  be  designed  for  the  load 
effects  based  on  analyses  in  any  two 
orthogonal  directions.  Diaphragms  and 
components  of  the  seismic-resisting  system 
utilized  in  only  one  of  the  two  orthogonal 
directions  are  not  required  to  be  designed  for 
the  combined  load  effects. 

1612.4.7.4.2  Plan  or  vertical  irregularities: 

For  buildings  having  a  plan  irregularity  of 
Type  1,  2,  3  or  4  in  Table  1612.4.5.1  or  a 


vertical  irregularity  of  Type  4  in  Table 
1612.4.5.2,  the  design  forces  determined 
from  780  CMR  1612.5  shall  be  increased 
25%  for  connections  of  diaphragms  to 
vertical  elements  and  to  collectors  and  for 
connections  of  collectors  to  the  vertical 
elements. 

1612.4.7.4.3  Vertical  seismic  loads:  The 
vertical  component  of  earthquake  ground 
motion  shall  be  accounted  for  in  the  design 
of  horizontal  cantilever  and  horizontal 
prestressed  components.  Horizontal 
prestressed  components  shall  be  designed 
for  load  combination  #8  of  780  CMR 
1616.3.1,  including  the  amplified  seismic 
effects  of  780  CMR  1616.4.  Horizontal 
cantilever  structural  components  shall  be 
designed  for  a  net  upward  force  of  0.2  times 
the  dead  load,  as  a  separate  loading  case,  in 
addition  to  the  applicable  load  combinations 
of  780  CMR  1616. 

1612.4.8  Deflection  and  drift  limits:  The  design 
story  drift  (a)  as  determined  in  780  CMR 
1612.5.5    or    1612.6.8,    shall   not    exceed    the 

allowable  story  drift  (Aa)  from  Table  1612.4.8  for 
any  story.  For  structures  with  significant  torsional 
deflections,  the  maximum  drift  shall  include 
torsional  effects.  The  total  deflection  of  a  building 
due  to  seismic  design  forces  shall  not  encroach  on 
an  interior  lot  line.  All  portions  of  the  building 
shall  be  designed  and  constructed  to  act  as  an 
integral  unit  in  resisting  seismic  forces  unless 
separated  structurally  by  a  distance  sufficient  to 
avoid  contact  causing  damage  to  the  structural 
system  of  the  building  under  total  deflection  (5X) 
as  determined  by  780  CMR  1612.5.5.1. 

1612.4.9  Foundation  walls  and  retaining  walls: 

Exterior  foundation  walls  and  retaining  walls  shall 
be  designed  to  resist  at  least  the  superimposed 
effects  of  the  total  static  lateral  soil  pressure, 
excluding  the  pressure  caused  by  any  temporary 
surcharge,  plus  and  earthquake  force  of 
0.045 Yt  H2  for  horizontal  backfill  surface.  Where 
Y,  is  the  total  unit  weight  of  the  soil  and  H  is  the 
height  of  the  wall  measured  as  the  difference  in 
elevation  of  finished  ground  surface  (or  floor)  in 
front  of  and  behind  the  wall.  Surcharges  which 
are  applied  over  extended  periods  of  time  shall  be 
included  in  the  total  static  lateral  soil  pressure  and 
their  earthqake  lateral  force  shall  be  computed 
and  added  to  the  force  of  0.045Yt  H2  .  The 
earthquake  force  from  the  backfill  shall  be 
distributed  as  an  inverse  triangle  over  the  height 
of  the  wall.  The  point  of  application  of  the  earth- 
quake force  from  an  extended  duration  surcharge 
shall  be  determined  on  an  individual  case  basis. 
If  the  backfill  consists  of  loose  saturated  granular 
soil,  consideration  shall  be  given  to  the  potential 
increase  in  lateral  pressure  due  to  liquefaction  of 


288 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


the  backfill  during  the  seismic  loading  in 
accordance  with  780  CMR  1805.2.  For  use  in 
wall  strength  design,  a  load  factor  of  1.43  times 
the  earthquake  force  calculated  above  shall  be 
applied. 

1612.5     Equivalent     lateral    force     procedure: 

780  CMR  1612.5  provides  requirements  for  the 
equivalent  lateral  force  procedure  of  seismic 
analysis  of  buildings.  For  purposes  of  analysis,  the 
building  is  considered  to  be  fixed  at  the  base.  See 
780  CMR  1612.4.6  for  limitations  on  the 
applicability  of  this  procedure. 

Table  1612.4.8 
ALLOWABLE  STORY  DRIFT  (a.)  a 


Building 

Seismic  Hazard  Exposure 
Group 

I                II               III 

One  story  buildings  without 
equipment  attached  to  the 
seismic-resisting   structural 
system    and    with    interior 
walls,    partitions,    ceilings 
and  exterior  wall   systems 
which  have  been  designed 
to    accomodate    the    story 
drifts. 

No  Limit  0.020  hsx  0.015  h^ 

Buildings      having       four 
stories  or  less  with  interior 
walls,    partitions,    ceilings 
and  exterior  wall   systems 
which  have  been  designed 
to    accomodate    the    story 
drifts. 

0.025  hsx  0.020  hsx  0.01 5  hsx 

All  other  buildings 

0.020  hsx  0.015  hsx  0.010  hsx 

Note  a:  hsx  is  the  story  height  below  level  x 

1612.5.1  Seismic  base  shear:  The  seismic  base 
shear  (V)  in  a  given  direction  shall  be  determined 
in  accordance  with  the  following  formula: 

V  =  cw 

where: 

Cs  =  The  seismic  design  coefficient  determined  in 

accordance  with  780  CMR  1612.5.1.1. 
W  =  The  total  dead  load  and  applicable  portions 
of  other  loads  listed  below: 
1        For  occupancies  in  Use  Group  S,  a 
minimum  of  25%  of  the  floor  live  load  shall 
be  applicable. 

Exception:  Floor  live  load  in  public 
garages  and  open  parking  structures  is 
not  applicable. 

2.  Where  partitions  will  be  present,  whether 
or  not  partitions  are  shown  on  the 
cotistruction  documents,  the  actual  partition 
weight  or  a  minimum  weight  of  10  psf  of 
floor  area,  whichever  is  greater,  shall  be 
applicable. 

3.  Total  operating  weight  of  permanent 
equipment. 


4.  Snow    load    reduction   of  50%    is 

permitted. 
1612.5.1.1  Calculation  of  seismic  coefficient 
(Cs):  The  seismic  design  coefficient  (Cs)  shall 
be     determined     in     accordance     with     the 
following  formulas: 

c  -  12AvS 

>     RT* 

where: 

Av  =  The  coefficient  representing  effective  peak 

velocity-related  acceleration  from  780  CMR 

1612.2.3. 

S=    The      coefficient      for      the      soil-profile 

characteristics  of  the  site  in  Table  1612.4.1. 

R  =   The  response  modification  factor  in  Table 

1612.4.3. 
T=  The  fundamental  period  of  the  building 
determined  in  780  CMR  1612.5.1.2. 
A  soil-structure  interaction  reduction  is 
permitted  where  determined  from  an  approved 
procedure.  Alternatively,  the  seismic  design 
coefficient  (Cs)  is  not  required  to  be  greater 
than  the  following  equation: 


c.  = 


2.5A 

a 

R 


where: 

Aa  =  Jhe  seismic  coefficient  representing  the 
effective  peak  acceleration  as  determined  in 
780  CMR  1612.2.3 

R=  The  response  modification  factor  in  Table 
1612.4.4 
1612.5.1.2  Period  determination:  The 
fundamental  period  (7),  in  seconds,  of  the 
building,  in  the  direction  under  consideration, 
shall  be  established  based  on  the  structural 
properties  and  deformational  characteristics  of 
the  resisting  elements  in  a  properly 
substantiated  analysis.  The  fundamental  period 
(7)  shall  not  exceed  the  product  of  the 
coefficient  for  the  upper  limit  on  calculated 
period  (Ca)  from  Table  1612.5.1.2,  and  the 
approximate  fundamental  period  (Ta). 

Alternatively,  the  fundamental  period  (T) 
shall  be  determined  from  780  CMR 
1612.5.1.2.1. 

Table  1612.5.1.2 

COEFFICIENT  FOR  UPPER  LIMIT  ON 

CALCULATED  PERIOD  (Ca) 

Av 
Coefficient  representing  effective                   Ca 
peak  velocity  related  acceleration 


1612.5.1.2.1    Approximate   fundamental 
period  (Ta).  The  approximate  fundamental 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


289 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


period  (Ta),  in  seconds,  shall  be  determined 
from  the  following  formula: 

Ta  =  CjH* 

where: 

hn  =  The  height  (in  feet)  from  the  base  to  the 

highest  level  of  the  building. 
CT=  0.035     For     moment-resisting     frame 
systems  of  steel  which  provide  100%  of 
the    required    lateral    force    resistance, 
where   the   frame   is   not    enclosed    or 
adjoined  by  more  rigid  components. 
Cr=  0.03  For  moment-resisting  frame  systems 
of  concrete  which  provide  100%  of  the 
required  lateral  force  resistance,  where 
the  frame  is  not  enclosed  or  adjoined  by 
more  rigid  components. 
CT  =  0.03  For  building  frame  systems  with  an 
eccentrically  braced  steel  frame  or  dual 
systems   with    an    eccentrically    braced 
frame. 
Cr  =  0.02  For  seismic-resisting  systems  with 
shear       walls,       shear       panels       or 
concentrically    braced    frames    and    all 
other  building  systems. 
Alternatively,  the  approximate  fundamental 
period  (Tg),  in  seconds,  shall  be  determined 
from  the  following  formula  for  buildings  in 
which    the    lateral    force-resisting    system 
consists    of  concrete    or    steel    moment- 
resisting  frames  capable  of  resisting  1 00% 
of  the  required  lateral  force  and  where  such 
frames  are  not  enclosed  or  adjoined  by  more 
rigid  components  tending  to  prevent  the 
frames  from  deflecting  when  subjected  to 
seismic   forces.    Such   buildings   shall   not 
exceed  12  stories  in  height  and  shall  have  a 
story  height  of  not  less  than  ten  feet  (3048 
mm). 

Ts  =  O.IN 

where: 

N=  Number  of  stories. 

1612.5.2  Vertical  distribution  of  seismic  forces: 

The  lateral  force  (F^)  induced  at  any  level  shall  be 
determined  from  the  following  formulas: 

F    =  C  V 

X  VX 

where: 

Cvx  =    Vertical  distribution  factor 

V      =   Total  design  lateral  force  or  shear  at  the 

base  of  the  building 
Wj  and  wx  =  the  portion  of  the  total  gravity  load  of 


the  building  (W)  located  or  assigned  to 
level  i  or  x 
hj  and  hx  =  the  height  (in  feet)  from  the  base  to 

level  i  or  x 
k  =    An  exponent  related  to  the  building  period 

as  follows; 

For  buildings  having  a  period  of  0.5  seconds 

or  less,  k=l. 

For  buildings  having  a  period  of  2.5  seconds 

or  more,  k=2 

For  buildings  having  a  period  between  0.5 

and  2.5  seconds,  k  shall  be  2  or  shall  be 

determined  by  linear  interoplation  between 

1  and  2. 

1612.5.3   Horizontal  shear  distribution:   The 

seismic  design  story  shear  in  any  story  (Vx)  shall 
be  determined  from  the  following  formula: 


r,  =  5>i 


where: 

Fj  =      the  portion  of  the  seismic  base  shear  (V) 

induced  at  level ;'. 
The  seismic  design  story  shear  (Vx)  shall  be 
distributed  to  the  various  vertical  elements  of  the 
seismic-resisting  system  in  the  story  under 
consideration  based  on  the  relative  lateral  stiffness 
of  the  vertical  resisting  elements  and  the 
diaphragm. 

1612.5.3.1  Torsion:  The  design  shall  include 
the  torsional  moment  (A/,)  resulting  from  the 
location  of  the  building  masses  plus  the 
accidental  torsional  moments  (Mla)  caused  by 
assumed  displacement  of  the  mass  each  way 
from  its  actual  location  by  a  distance  equal  to 
5%  of  the  dimension  of  the  building 
perpendicular  to  the  direction  of  the  applied 
forces. 

In  buildings  of  Seismic  Performance 
Categories  C,  D  and  E,  where  Type  1  torsional 
irregularity  exists  as  defined  in  Table 
1612.4.5.1,  the  effects  shall  be  accounted  for 
by  increasing  the  accidental  torsion  at  each 
level  by  a  torsional  amplification  factor  (Ax) 
determined  from  the  following  formula: 


A    = 


1.26 


where: 

6  mwt  =  the  maximum  displacment  at  level  x. 
5  mg  =  the  average  of  the  displacments  at  the 
extreme  points  of  the  structure  at  level  x. 

The  torsional  amplification  factor  (A^  is  not 

required  to  exceed  3.0. 

1612.5.4   Overturning:    The  building  shall  be 
designed  to  resist  overturning  effects  caused  by 


290 


780  CMR -Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


the  seismic  forces  determined  in  780  CMR 
1612.5.2.  At  any  story,  the  increment  of 
overturning  moment  in  the  story  under 
consideration  shall  be  distributed  to  the  various 
vertical  resisting  elements  in  the  same  proportion 
as  the  distribution  of  the  horizontal  shears  to  those 
elements 

The  overturning  moments  at  level  x  (M^.)  shall 
be  determined  from  the  following  formula: 


k  =  tLhk  -  K) 


where: 

Ft  =  The  portion  of  the  seismic  base    shear  (V) 

induced  at  level  i. 
hx  and  hx  =  The  height  (in  feet)  from  the  base  to 

level  /  or  x. 
T   =  1 .0  for  the  top  ten  stories, 

0.8  for  the  20th  story  from  the  top  and 

below;  and 

a  value  between  1.0  and  0.8  determined  by 

a    straight    line    interpolation    for    stones 

between  the  tenth  and  20th  stories  below  the 

top 
The  foundations  of  buildings,  except  inverted 
pendulum  structures,  shall  be  designed  for  the 
foundation  overturning  design  moment  (Mj)  at  the 
foundation-soil  interface  determined  by  the 
equation  for  the  overturning  moment  at  level  x 
(MJ  with  an  overturning  moment  reduction  factor 
(T)  of  0.75  for  all  building  heights. 

1612.5.5  Drift  determination  and  P-delta 
effects:  Stop,'  drifts  and,  where  required,  member 
forces  and  moments  due  to  P-delta  effects,  shall 
be  determined  in  accordance  with  780  CMR 
1612.5.5.1  and  1612.5.5.2. 

1612.5.5.1  Story  drift  determination:  The 
design  story  drift  (a)  shall  be  computed  as  the 
difference  of  the  deflections  at  the  top  and 
bottom  of  the  story  under  consideration.  The 
deflections  of  level  x  at  the  center  of  the  mass 
(8  )  shall  be  determined  in  accordance  with 
the  following  formula: 

8  =C,b 

x        a    xe 

where: 

Cd=       The   deflection   amplification   factor  in 

Table  1612.4.4. 
6xe  =      The  deflections  determined  by  an  elastic 
analysis. 
The  elastic  analysis  of  the  seismic-resisting 
system  shall  be  made  utilizing  the  required 
seismic  design  forces  of  780  CMR  1612.5.2. 

For  determining  compliance  with  the  story 
drift  limitation  of  780  CMR  1612.4.8,  the 
deflection  of  level  x  at  the  center  of  mass  (8X) 
shall  be  calculated  as  required  in  this  section. 
For  the  purposes  of  this  drift  analysis  only,  the 


computed  fundamental  period  (T)  of  the 
building  is  not  required  to  include  the  upper 
bond  limitation  specified  in  780  CMR 
1612.5.1.2  when  determining  drift  level 
seismic  design  forces. 

Where  applicable,  the  design  story  drift  (a) 
shall  be  increased  by  the  incremental  factor 
relating  to  the  P-delta  effects  as  determined  in 
780  CMR  1612.5.5.2. 

1612.5.5.2  P-delta  effects:  P-delta  effects  on 
story  shears  and  moments,  the  resulting 
member  forces  and  moments,  and  the  story 
drifts  induced  by  these  effects  are  not  required 
to  be  considered  where  the  stability  coefficient 
(6),  as  determined  by  the  following  formula,  is 
equal  to  or  less  than  0  10: 

Pa 


Vh   C\ 


where: 

Px  =       The  total  vertical  design  load  at  story 

level  x.  In  calculating  the  vertical  design 

load  for  the  purpose  of  determining  P- 

delta  effects,  individual  load  factors  are 

not  required  to  exceed  1.0. 
A  =         The     design     story      drift     occurring 

simultaneously  with  the  story  shear  (Vx) 
Vx  =       The  seismic  shear  force  between  levels  x 

and  x-1 
h^  =       The  story  height  below  level  x. 
Cd  =       The   deflection   amplification   factor  in 

Table   1612.4.4 
The  stability  coefficient  (6)  shall  not  exceed 
6„„.  determined  as  follows: 


0.5 


^0.25 


where: 

P  =  The  ratio  of  shear  demand  to  shear  capacity 
for  the  story  between  levels  x  and  x-1.  This 
ratio  is  permitted  to  be  considered  as  1.0. 
Where  the  stability  coefficient  (6)  is  greater 
than  0.10  but  less  than  or  equal  to  6max,  the 
incremental  factor  related  to  P-delta  effects 
shall  be  determined  by  rational  analysis.  To 
obtain  the  story  drift  for  including  the  P-delta 
effect,  the  design  story  drift  determined  in 
780  CMR  1612.5.5.1  shall  be  multiplied  by 
1.0/(1  -6) 

1612.6    Modal    analysis   procedure     780   CMR 

1612.6  provides  required  standards  for  the  modal 
analysis  procedure  of  seismic  analysis  of  buildings 
780  CMR  1612.4.6  specifies  the  limitations  on  the 
applicability  of  this  procedure. 

1612.6.1  General:  The  symbols  in  this  method  of 
analysis  have  the  same  meaning  as  those  for 
similar  terms  used  in  780  CMR  1612.5.  with  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


291 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


subscript  "m"  denoting  quantities  in  the  mth 
mode. 

1612.6.2  Modeling:  The  building  shall  be 
modeled  as  a  system  of  masses  lumped  at  the 
floor  levels  with  each  mass  having  one  degree  of 
freedom;  lateral  displacement  in  the  direction 
under  consideration. 

1612.6.3  Modes:  The  analysis  shall  include,  for 
each  of  two  mutually  perpendicular  axes,  at  least 
the  lowest  three  modes  of  vibration,  or  all  modes 
of  vibration  with  periods  greater  than  0  4  seconds, 
or  sufficient  modes  to  include  90%  of  the 
participating  mass  of  the  structure,  whichever  is 
greater.  The  number  of  modes  shall  equal  the 
number  of  stories  for  buildings  less  than  three 
stories  in  height. 

1612.6.4  Periods:  The  required  periods  and  mode 
shapes  of  the  building  in  the  direction  under 
consideration  shall  be  calculated  by  established 
methods  of  structural  analysis  for  the  fixed  base 
condition  utilizing  the  masses  and  elastic 
stiffnesses  of  the  seismic-resisting  system. 

1612.6.5  Modal  base  shear:  The  portion  of  the 
base  shear  contributed  by  the  m  mode  (V  )  shall 
be  determined  from  the  following  formula: 

V     =  C  W 

m  mm 

where: 

Csm=     The   modal    seismic   design   coefficient 

determined  by  the  following  formula. 
Wm  =     The     effective     modal     gravity     load 

determined  by  the  following  formula 


W     = 


E  wp. 


E  wp 


where. 


Wj  =       the  portion  of  the  total  gravity  load  of  the 

building  at  level  i. 
®im  =     ^he  displacement  amplitude  at  the  ith 

level  of  the  building  when  vibrating  in  its 

mth  mode. 
The  modal  seismic  design  coefficient  (Csm)  shall 
be  determined  in  accordance  with  the  following 
formula: 


C-m 


l.2AvS 
RTl' 


where: 
\  = 


Seismic     coefficient     representing    the 
effective  peak  velocity-related 

acceleration  as  determined  in  780  CMR 
1612.2.3. 


S  =        The    coefficient    for    the    soil-profile 
characteristics  of  the  site  as  determined 
by  Table  1612  4.1 
R  =        The      response      modification      factor 

determined  from  Table  1612.4.4. 
Tm  =  The  modal  period  of  vibration,  in 
seconds,  of  the  mth  mode  of  the  building 
The  modal  seismic  design  coefficient  (Csm)  is  not 
required  to  exceed  2Vi  times  the  seismic 
coefficient  representing  the  effective  peak 
acceleration  (Aa)  divided  by  the  response 
modification  factor  (R) 
Exceptions 

1 .  The  limiting  value  of  the  modal  seismic 
design  coefficient  (Csm)  is  not  applicable  to 
Category  D  and  E  buildings  with  a  period  of 
0.7  seconds  or  greater  located  on  type  S4  soils 

2  For  buildings  on  soil-profile  characteristics 
S3  or  S4,  the  modal  seismic  design  coefficient 
(Csm)  for  modes  other  than  the  fundamental 
mode  that  have  periods  less  than  0.3  seconds  is 
permitted  to  be  determined  by  the  following 
formula 

A  (1.0  +  5.or  ) 
R 

3  For  buildings  where  any  modal  period  of 
vibration  CTm)  exceeds  4.0  seconds,  the  modal 
seismic  design  coefficient  (Csm)  for  that  mode 
is  permitted  to  be  determined  by  the  following 
formula: 


c     = 


3AS 


RTl 


where: 


Aa  =       Seismic    coefficient     representing    the 
effective  peak  acceleration  as  determined 
in  780  CMR  1612.2.3. 
A,  =  Seismic  coefficient  representing  the 

effective  peak  velocity-related  acceleration 

as  determined  in  780  CMR  1612.2.3. 
R  =   The  response  modification  factor  determined 

from  Table  1612.4.4. 
Tm  =  The  modal  period  of  vibration,  in  seconds, 

of  the  mth  mode  of  the  building. 
S  =    The     coefficient     for     the     soil     profile 

characteristics  of  the  site  as  determined  by 

Table  1612.4.1. 

1612.6.6  Modal  forces,  deflections  and  drifts. 

The  modal  force  (F^)  at  each  level  shall  be 
determined  by  the  following  formulas: 

F     =  C  ■   V_ 


292 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


where: 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 

fi  determined  by  taking  the  square  root  of  the  sum  of 

„  i  jii  the  squares  of  each  of  the  modal  values  (SRSS 

«»  n  method)  or  by  using  the  Complete  Quadratic 

y^  WQ .  Combination  (CQC)  method.  When  the  periods  of 

,=i  ""  any  two  modes  used  in  this  analysis  differ  by  less 

than  25%  the  CQC  method  shall  be  used. 

The  base  shear  (V)  utilizing  the  equivalent 
lateral  force  procedure  in  780  CMR  1612.5  shall 
be  calculated  based  on  a  fundamental  period  of 
the  building  (T),  in  seconds,  of  1.2  times  the 
coefficient  for  the  upper  limit  on  the  calculated 
period  (Ca)  times  the  approximate  fundamental 
period  of  the  building  (Ta).  Where  the  design 
value  for  the  modal  base  shear  (Vt)  is  less  than  the 
calculated  base  shear  (V)  utilizing  the  equivalent 
lateral  force  procedure,  the  design  story  shears, 
moments,  drifts  and  floor  deflections  shall  be 
multiplied  by  the  following  modification  factor: 


mode. 
V     =     The  total  design  lateral  force  or  shear  at 
m  th 

the  base  in  the  m    mode. 

Wj  and  wx  =  The  portion  of  the  total  gravity  load 
of  the  building  (W)  located  or  assigned  to 
level  i  or  x. 
6  xm  =  The  displacement  amplitude  at  the  x' 
level  of  the  building  when  vibrating  in 
the  m    mode. 
Q-     =     The  displacement  amplitude  at  the  i 
level  of  the  building  when  vibrating  in 
the  m1   mode. 
The  modal  deflection  at  each  level  (o.^)  shall  be 
determined  by  the  following  formulas: 

6      =  C£__ 


g 

4u2 

nr  xm 

.      W*     . 

where: 

Cd  =       The     deflection     amplification     factor 

determined  from  Table  1612.4.4. 
8xem  =  The  deflection  of  level  x  in  the  m*  mode 

at  the  center  of  the  mass  at  level  x 

determined  by  an  elastic  analysis, 
g  =         The  acceleration  due  to  gravity  (feet  per 

second2). 
Tm  =      The    modal    period    of   vibration,    in 

seconds,  of  the  mth  mode  of  the  building. 
Fxm  =    The  portion  of  the  seismic  base  shear  in 

the  m"1  mode,  induced  at  level  x. 
wx  =      The  portion  of  the  total  gravity  load  of 

the  building  (W)  located  or  assigned  to 

level  x. 

The  modal  drift  in  a  story  (Am)  shall  be  computed 
as  the  difference  of  the  deflections  (o,^)  at  the 
top  and  bottom  of  the  story  under  consideration. 

1612.6.7  Modal  story  shears  and  moments:  The 

story  shears,  story  overturning  moments,  and  the 
shear  forces  and  overturning  moments  in  walls 
and  braced  frames  at  each  level,  due  to  the 
seismic  forces  determined  from  the  appropriate 
equation  in  780  CMR  1612.6.6,  shall  be  computed 
for  each  mode  by  linear  static  methods. 

1612.6.8  Design  values:  The  design  value  for  the 
modal  base  shear  (Vt),  each  of  the  story  shear, 
moment  and  drift  quantities,  and  the  deflection  at 
each  level  shall  be  determined  by  combining  their 
modal  values,  obtained  from  780  CMR  1612.6.6 
and      1612.6.7.     The     combination     shall     be 


where: 

V  =  The  equivalent  lateral  force  procedure  base 
shear,  calculated  in  accordance  with 
780  CMR  1612.6  and  780  CMR  1612.5. 

V,  =  The  modal  base  shear,  calculated  in 
accordance  with  780  CMR  1612.6 

The  model  base  shear  (Vt)  is  not  required  to 

exceed  the  base  shear  from  the  equivalent  lateral 

force  procedure  in  780  CMR  1612.5 

1612.6.9  Horizontal  shear  distribution:   The 

distribution  of  horizontal  shear  shall  be  in 
accordance  with  the  requirements  of  780  CMR 
1612.5.3. 

1612.6.10  Foundation      overturning:      The 

foundation  overturning  moment  at  the  foundation- 
soil  interface  shall  not  be  reduced  by  more  than 
10%. 

1612.6.11  P-delta  effects:  The  P-delta  effects 
shall  be  determined  in  accordance  with  780  CMR 
1612.5.5.2.  The  story  drifts  and  story  shears  shall 
be  determined  in  accordance  with  780  CMR 
1612.6.8. 

1612.7  Architectural,  mechanical  and  electrical 
components  and  systems:  All  components  and 
systems  in  buildings  shall  be  designed  and 
constructed  to  resist  seismic  forces  as  determined  in 
accordance  with  the  provisions  of  780  CMR  1612.7. 
Architectural,  mechanical  and  electrical  components 
and  systems  in  buildings  assigned  to  Seismic  Hazard 
Perfrmance  Category  C,  and  are  in  Seismic  Hazard 
Exposure  Group  I  and  have  a  Performance  Criteria 
Factor  of  0.5,  are  exempt  from  the  requirements  of 
780  CMR  1612.7. 

Exceptions: 

1.  Individual    electrical    and    mechanical 

components  which  weigh  more  than  2,000  pounds 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


293 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  are  located  more  than  15  feet  above  the  base 
shall  be  designed  in  accordance  with  780  CMR 
1612.7.4. 

2.  Elevator  components  and  systems  in  buildings 
assigned  to  Seismic  Hazard  Performance 
Category  C  and  are  in  Seismic  Hazard  Exposure 
Group  I  buildings  not  more  than  70  feet  in  height 
are  exempt  from  the  requirements  of  780  CMR 
1612.7. 

1612.7.1  Component   force  application:   The 

component  seismic  force  shall  be  applied  at  the 
center  of  gravity  of  the  component 
nonconcurrently  in  any  horizontal  direction. 
Mechanical  and  electrical  components  and 
systems  shall  be  designed  for  a  nonsimultaneous 
vertical  force  of  33%  of  the  horizontal  force. 

1612.7.2  Component        force        transfer: 

Components  shall  be  attached  such  that  the 
component  forces  are  transferred  to  the  structural 
system  of  the  building.  Component  seismic 
attachments  shall  be  positive  connections  without 
consideration  of  frictional  resistance. 

1612.7.3  Architectural    component    design: 

Architectural  components  and  their  attachments 
shall  be  designed  for  seismic  forces  (Fp) 
determined  in  accordance  with  the  following 
formula: 

F    = ACPW 

p  V     c  c 

where: 

Av  =  The  coefficient  representing  effective  peak 

velocity-related  acceleration  from  780  CMR 

1612.2.3. 
Cc  =  The    seismic    coefficient   for    architectural 

components  from  Table  1612.7.3. 
P  =   Performance    criteria    factor    from    Table 

1612.7.3. 
Wc  =  The  weight  of  the  architectural  component. 

1612.7.3.1  Exterior  wall  panel  connections: 

The  connections  of  exterior  wall  panels  to  the 
building  seismic-resisting  system  shall  be 
designed  for  the  design  story  drift  determined 
in  accordance  with  780  CMR  1612.5.5.1  or  in 
accordance  with  780  CMR  1612.6.6  and 
1612.6.8. 

1612.7.3.2  Architectural  component 
deformation:  Architectural  components  shall 
be  designed  for  the  design  story  drift  of  the 
structural  seismic-resisting  system  determined 
in  accordance  with  780  CMR  1612.5.5.1  or  in 
accordance  with  780  CMR  1612.6.6  and 
1612.6.8.  Architectural  components  shall  be 
designed  for  vertical  deflection  due  to  joint 
rotation  of  cantilever  structural  members. 

Exception:  Architectural  components 
having  a  performance  criteria  factor  of  0.5 
shall  be  designed  for  50%  of  the  design 
story  drift. 


1612.7.3.3  Ceilings:  Provision  shall  be  made 
for  the  lateral  support  and  interaction  of  other 
architectural,  mechanical  and  electrical 
systems  or  components  incorporated  into  the 
ceiling  which  impose  seismic  forces  into  the 
ceiling  system. 

Table  1612.7.3 

ARCHITECTURAL  COMPONENT  SEISMIC 

COEFFICIENT  (Cc)  AND  PERFORMANCE 

CRITERIA  FACTOR  (P)a 


Component 

Seismic 

Coefficient 

(Cc) 

Performance 
Criteria 
Factor  (P) 

Architectural  Component 

Seismic  Hazard 
Exposure 

Group 

I 

II 

III 

1    Exterior  nonloadbearing  walls 

0.9 

1.5 

1.5 

1  5 

2  Interior  nonloadbearing  walls  , 

Exit,  stair  and  elevator 

enclosures. 

Other  vertical  shaft  enclosures 

Other  nonloadbearing  walls 

1.5 
0.9 
0.9 

1.0 
1.0 
1.0 

1.0 
1.0 
1.0 

1.5 
1.5 
1.5 

3    Cantilever  elements,  parapets, 
chimneys  or  stacks 

3.0 

1.5 

1.5 

1.5 

4    Wall  attachments 

3.0 

1.5 

1.5 

1.5 

5    Veneer  connections 

3.0 

0.7 

1.0 

1.0 

6    Penthouses 

0.6 

0.7 

1.0 

1.0 

7    Membrane  fire  protection 

0.9 

1.0 

1.0 

1.5 

8    Ceilings 

Fireresistance  rated  membrane 
Nonfireresistance  rated  mem- 
brane 

0.9 
0.6 

1.0 
0.5 

1.0 
1.0 

1.5 
1.0 

9    Storage  racks,  contents  included 

1.5 

1.0 

1.0 

1  5 

10  Access  floor,  supported  equip- 
ment included 

2.0 

0.5 

1.0 

1.5 

1 1  Elevator  and  counterweight 
guardrails  and  supports 

1.25 

1.0 

1.0 

1.5 

Note  a:  See  780  CMR  1612.7  for  general  exceptions 
Note  b:  See  780  CMR  1612.4.7.2.8  for  exterior  and 
interior  loadbearing  wall  requirements 
Note  c:  The  design  seismic  force  for  a  penthouse  shall  be 
the  larger  of  the  force  determined  in  accordance  with 
780  CMR  1612.7.3,  this  table  and  the  force  determined  in 
accordance  with  780  CMR  1612.5  or  1612.6 

1612.7.4  Mechanical,  electrical  component  and 
system  design:  Mechanical,  electrical 
components  and  systems  and  their  attachments 
shall  be  designed  for  seismic  forces  (Fp) 
determined  in  accordance  with  the  following 
formula: 

F    =  ACPaWr 

p  V     c        c      c 

where: 

A^  =  The  coefficient  representing  effective  peak 
velocity-related  acceleration  from  780  CMR 
1612.2.3. 
Cc  =       The  seismic  coefficient  for  mechanical, 
electrical  components  and  systems  from 
Table  1612.7.4(1). 


294 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


P  =    Performance        criteria        factor        from 

1612.7.4(1). 
a     -      The    attachment    amplification    factor 
determined   in   accordance  with   Table 
1612.7  4(2). 
Wc  =  The  operating  weight  of  the  mechanical, 

electrical  component  or  system. 
Alternatively,   the  seismic  forces  (F  )   shall  be 
determined  by  a  properly  substantiated  dynamic 
analysis  subject  to  approval. 

Exception:  Bracing  of  fire  sprinkler  systems 
shall  be  permitted  to  be  in  accordance  with 
NFiPA  13  listed  in  Appendix  A. 

Table  1612.7.4(1) 

MECHANICAL,  ELECTRICAL 

COMPONENT  AND  SYSTEM  SEISMIC 

COEFFICIENT  (Cc)  AND  PERFORMANCE 

CRITERLA  FACTOR  (P)a 


Performance 

Criteria  Factor 

(P) 

Mechanical,  electrical  component 
or  system 

Component 

or  system 

seismic 

coefficient 

(Cc) 

Sesimic 

Hazard 

Exposure 

Group 

I 

II 

III 

1  Fire  protection  equipment  and 
svstems 

2.0 

1.5 

1.5 

1.5 

2  Emergency'  or  standby  electrical 
svstems 

2.0 

1.5 

1.5 

]  5 

3  Elevator  drive,  suspension  system 
and  controller  anchoraae 

1.25 

1.0 

1.0 

1.5 

4  General  equipment 

A.  Boilers,  furnaces,  incinerators, 
water  heaters  and  other  equip- 
ment utilizing  combustible 
energy  sources  or  high  temper- 
ature sources. 

B.  Communication  systems 

C.  Electrical  bus  ducts  and 
primary  cable  systems1'. 

D.  Electrical  motor  control  cen- 
ters, motor  control  devices, 
switchgear,  transformers  and 
unit  substations. 

E.  Reciprocating  or  rotating 
equipment 

F.  Tanks,  heat  exchangers  and 
pressure  vessels. 

2.0 

0.5 

1.0 

1.5 

5  Manufacturing  and  process 
machinery 

0.67 

0.5 

1.0 

1.5 

6  Pipe  systems 

Gas  and  high  hazard  piping 
Fire  suppression  piping 
Other  pipe  svstems 

2.0 
2.0 
0.67 

15 
1.5 
0.5 

5 
5 
0 

1 
1 
1 

5 
5 
5 

7  HVACductsd 

0.67 

0.5 

0 

1 

5 

8  Electrical  panel  board 

0.67 

0.5 

0 

1 

.5 

9  Lighting  fixtures 

0.67 

0.5 

0 

1 

5 

Note  a:  Sec  780  CMR  1612.7  for  general  exceptions 
Note   b:   Electrical  conduit  seismic  restraints   arc  not 
required  for  any  one  of  the  following  conditions 


1.  Conduit  suspended  by  individual  hangars  12 
inches  or  less  in  length  from  the  top  of  the  conduit  to 
the  supporting  structure 

2.  Conduit  which  has  less  than  2in  inches  inside 
diameter 

Note  c:  Seismic  restraints  are  not  required  for  any  one  of 
the  following  conditions  for  other  pipe  systems 

1.  Piping  suspended  by  individual  hangars  12  inches 
or  less  in  length  from  the  top  of  the  pipe  to  the 
supporting  structure 

2.  Piping  in  boiler  and  mechanical  rroms  which  has 
less  than  1  'A  inches  inside  diameter. 

3.  Piping  in  other  areas  which  has  less  than  2'/:  inches 
inside  diameter. 

Note  d:  Seismic  restraints  are  not  required  for  any  one  of 
the  following  conditions  for  HVAC  ducts: 

1.  Ducts  suspended  by  individual  hangars  12  inches 
or  less  in  length  from  the  top  of  the  duct  to  the 
supporting  structure 

2.  Ducts  which  have  a  cross-sectional  area  less  than 
6  square  feet. 

Note  e:  Pendulum  lighting  fixtures  sahll  be  designed 
based  on  a  component  seismic  coefficient  (CJ  of  1.5. 
The  vertical  supportshall  be  designed  with  a  factor  of 
safety  of  4.0 

Table  1612.7.4(2) 

ATTACHMENT  AMPLIFICATION 

FACTOR  (a,) 


Component  mounting  system 

Attachment 

amplification  factor  (a.,) 

Fixed  of  direct  connection 

1.0 

Resilient-mounting  system 

Seismic-activated  restraining 

1.0 

device 

Elastic  restraining  device  where: 

T                T 

— <0.6    or    —  >1.4" 

T                 T 

1.0 

T                 T 

—  2:0.6    or    — £l.4a 

T                 T 

2.0 

Note  a:  T  is  the  fundemental  period  of  the  building,  in 
seconds,  determined  by  780  CMR  1612.5.1.2  or 
780  CMR  1612.6.4.  Tc  is  the  fundemental  period,  in 
seconds,  of  the  component  and  its  attachement 
determined  by  780  CMR  1612.7.4.1 

1612.7.4.1       Component       period:       The 

fundamental  period  of  the  component  and  its 
attachments  (Tc),  in  seconds,  shall  be 
determined  by  the  following  formula: 


0.32 


W 

C 


where: 

Wc  =  Weight  of  the  component  (lbs). 
For  stable  resilient-mounting  attachments: 
K=   Spring  stiffness  constant  (lb. /in.). 
For  other  resilient-mounting  attachments: 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


295 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


K  =   Slope  of  the  load  vs  deflection  curve  (lb.  /in.) 

at  the  point  of  loading. 
Alternatively,    the   fundamental    period   of  the 
component  (TJ,  in  seconds,  shall  be  determined 
by   experimental   test   data   or   by   a   properly 
substantiated  analysis. 

1612.7.4.2  Component  attachment:  Systems, 
components  and  the  means  of  their  attachment 
shall  be  designed  to  accommodate  relative 
seismic  displacements  between  points  of 
support.  Displacements  at  points  of  support 
shall  be  determined  in  accordance  with 
780  CMR  1612.5.5  or  1612.6.8.  Relative 
lateral  displacements  at  points  of  support  shall 
be  determined  considering  the  difference  in 
elevation  between  the  supports  and  considering 
full  out-of-phase  displacements  across  portions 
of  the  building  that  are  capable  of  moving  in  a 
differential  manner  such  as  at  seismic  and 
expansion  joints.  Anchor  bolts  shall  be 
designed  for  combined  shear  and  tension. 
Restraining  devices  shall  be  provided  to  limit 
the  horizontal  and  vertical  motions,  to  prevent 
component  resonance  and  to  prevent 
overturning. 

1612.7.5  Elevator  design   requirements:   The 

design  and  construction  of  elevators  and  elevator 
components  in  buildings  assigned  to  Seismic 
Performance  Category  D  or  E,  in  accordance  with 
780  CMR  1612.2,  shall  comply  with  the 
requirements  in  Appendix  F  of  ASME  A17.1 
listed  in  Appendix  A. 

780  CMR  1613.0  CONCENTRATED  LOADS 

1613.1  General:  Floors  and  roofs  of  buildings  in  the 
locations  specified  in  Table  1613.1  shall  be  designed 
to  support  the  uniformly  distributed  live  loads 
prescribed  in  780  CMR  1606.0  or  the  minimum 
concentrated  loads  in  pounds  prescribed  in  Table 
1613.1,  whichever  produces  the  greater  stresses.  If 
the  anticipated  actual  loads  are  higher,  the  actual 
loads  shall  be  utilized.  Unless  otherwise  specified, 
the  indicated  concentration  shall  be  assumed  to 
occupy  an  area  of  2Vi  square  feet  and  shall  be  so 
located  as  to  produce  the  maximum  stress  conditions 
in  the  structural  members. 


Table  1613.1 
MINIMUM  CONCENTRATED  LOADS 


Location 


Load  (pounds) 


Elevator  machine  room  grating 

(on  area  of  4  square  inches)  300 
Finish  light  plate  floor  construction 

(on  area  of  4  square  inches)  200 
Garages                                                See  780  CMR  1613.2 

Greenhouse  roof  bars,  purlins  and  rafters  1 00 

Hospitals  and  ward  rooms  1 ,000 

Libraries  1,000 

Manufacturing  and  storage  buildings  2,000 
Mechanical  equipment                           See  780  CMR  1613.3 

Mercantile  areas  2,000 

Office  2,000 

Schools  1,000 
Scuttles,  skylight  ribs  and  accessible 

ceiling  ribs  and  hangers  (over  an  area  of  200 
one  suare  inch) 

Sidewalks  or  vehicular  driveways  subject  8,000 

to  trucking 

Stair  treads  (over  area  of  4  square  inches  at  300 

center  of  tread) 
Note  a:  1  pound  =  4.448  N;  1  square  inch=645.16  mm2 

1613.2  Garages:  Minimum  concentrated  loads  for 
garages  or  portions  of  buildings  occupied  for 
parking  motor  vehicles  shall  be: 

1.  For  passenger  cars  accommodating  not  more 
than  nine  passengers,  2,000  pounds  (8896  N) 
acting  on  an  area  of  20  square  inches  (12900 
mm2); 

2.  Mechanical  parking  structures  without  slab, 
passenger  cars  only,  1500  pounds  (6672  N)  per 
wheel;  and 

3.  For  trucks  or  buses,  on  slabs,  applicable  wheel 
loads  and  tire  contact  areas  specified  in  AASHTO 
Standard  Specification  for  Highway  Bridges  with 
interim  revisions  to  1995  {see  Appendix  A). 

1613.3  Mechanical  Equipment:  The  actual 
concentrated  loads  of  the  machinery,  shall  be  used 
for  buildings  containing  mechanical  material 
handling  equipment,  machines  or  other  heavy 
apparatus. 


296 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


780  CMR  1614.0  IMPACT  LOADS 

1614.1  General:  The  live  loads  specified  in 
780  CMR  1606.0  shall  be  assumed  to  include 
adequate  allowance  for  ordinary  impact  conditions. 
Provisions  shall  be  made  in  the  structural  design  for 
special  occupancies  and  loads  which  involve 
vibration  and  impact  forces.  Where  dynamic  effects 
such  as  resonance  and  fatigue  are  likely  to  be 
important  as  a  result  of  cyclical  loading,  a  dynamic 
analysis  shall  be  carried  out. 

1614.2  Elevators:  Structural  supports  for  elevators, 
dumbwaiters,  escalators  and  moving  walks  shall  be 
designed  for  the  loads  and  within  the  limits  of  the 
deflection  specified  in  the  Massachusetts  State 
Department  of  Public  Safety,  Board  Elevator 
Regulations  (524  CMR  1.0  through  34.0),  listed  in 
Appendix  A.  (In  accordance  with  the  Regulations, 
all  suspended  elevator  loads  shall  be  increased  100% 
for  impact. 

1614.3  Machinery:  For  the  purposes  of  design,  the 
weight  of  machinery  and  moving  loads  shall  be 
increased  as  follows  to  allow  for  impact: 

Elevator  machinery    100% 

Light  machinery,  shaft-  or  motor-driven  .  .    20% 

Reciprocating  machinery  or  power-driven 

units    50% 

These   percentages   shall  be   increased   where   so 

specified  by  the  manufacturer. 

1614.4  Hangers  for  floors  and  stairs:  Live  loads 
on  hangers  supporting  floors  or  stairs  shall  be 
multiplied  by  an  impact  factor  of  1 .33. 


780  CMR  1615.0  SPECIAL  LOADS 
1615.1  General:  Provisions  shall  be  made  for  all 
special  loads  herein  prescribed  and  all  other  special 
loads  to  which  the  building  or  structure  is  subjected. 


1615.2  Hydrostatic  uplift:  All  foundation  slabs  and 
other  footings  subjected  to  water  pressure  shall  be 
designed  to  resist  an  uplift  equal  to  the  full 
hydrostatic  pressure.  All  foundation  slabs,  footings 
and  walls  of  buildings  located  in  flood-hazard  zones 
(A  Zones)  and  high-hazard  zones  (V  Zones)  shall  be 
designed  to  resist  uplift  and  lateral  loads  associated 
with  hydrostatic  pressure  resulting  from  flooding  to 
the  base  flood  elevation.  Counteracting  weight  shall 
be  reduced  to  0.85  times  the  actual  weight. 

1615.3  Hydrodynamic  loads:  For  buildings  located 
in  flood-hazard  zones  (A  Zones)  or  high-hazard 
zones  (V  Zones),  all  structural  components  located 
below  the  base  flood  elevation  shall  be  designed  to 
resist  hydrodynamic  forces  resulting  from  velocity 
waters  during  flooding  to  the  base  flood  elevation. 

1615.4  Partitions  and  Interior  Finish:  Partitions, 
their  components  and  other  interior  finish  shall  have 
adequate  strength  to  resist  a  horizontal  load  of  not 
less  than  5  psf. 

1615.5  Guardrails  and  handrails:  All  required 
guardrails  and  handrails  shall  be  designed  and 
constructed  to  the  structural  loading  conditions  set 
forth  in  Table  1615.5.  without  exceeding  the 
allowable  design  working  stresses  of  the  materials, 
anchorage  and  connecting  devices  utilized.  The 
allowable  working  stresses  shall  be  as  defined  by  the 
appropriate  design  standard.  Each  load  shall  be 
applied  so  as  to  produce  the  maximum  stress  in  each 
of  the  respective  components. 

Each  load  shall  be  applied  in  the  direction 
indicated  in  the  table.  The  concentrated  load  and 
uniformly  distributed  loads  need  not  be  applied 
simultaneously.  The  loads  applied  to  in-fill  areas 
need  not  be  applied  simultaneously  with  the  loads 
applied  on  the  top  railing. 


TABLE  1615.5 
LOADS  ON  GUARDRAILS  AND  HANDRAILS 


Type  of  Occupancy 

Location  of  Load 

Type  of  load 

Direction  of  Load 

Magnitude  of  Load 

All 

Handrails 

Concentrated 

Any 

200  lb. 

All,  except  dwelling  units  in 
Use  Groups  R-2  and  R-3 

Handrails 

Uniformly  distributed 

Any 

50  lb/ft. 

All,  except  as  noted 
otherwise 

Guardrails,  top  railing 
members 

Concentrated 

Any 

2001b. 

All,  except  dwelling  units  in 
Use  Groups  R-2  and  R-3 
and  as  noted  otherwise 

Guardrails,  top  railing 
members 

Uniformly  distributed 

Vertical 

simultaneously  with 

horizontal 

100  lb/ft 
50  lb/ft. 

All 

Guardrails,  in-fill  areas 

Concentrated 

Any 

200  lb.  applied 
over  1  sf.  area 

Grandstands,  stadia,  arenas, 
and  similar  structures  used 
for  public  assembly 

Guardrails,  top  railing 
members 

Concentrated 

Any 

300  lb 

Grandstands,  stadia,  arenas, 
and  similar  structures  used 
for  public  assembly 

Guardrails,  top  railing 
members 

Uniformly  distributed 

Any 

100  lb/ft 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1615.6  Grandstands,  stadia  and  similar  structures 
shall  be  designed  to  resist,  in  combination  with 
design  wind  loads,  a  horizontal  swaying  load  applied 
parallel  to  the  row  of  seats  of  not  less  than  24 
pounds  per  lineal  foot  of  seats  per  row,  or  in 
combination  with  wind,  a  horizontal  swaying  load 
applied  transversely  of  not  less  than  ten  pounds  per 
lineal  foot  of  seats  per  row.  Foot  boards  and  seat 
boards  shall  be  designed  for  a  minimum  vertical  load 
of  120  lb.  per  lineal  foot. 

1615.7  Horizontal  crane  loads:  A  lateral  force 
shall  be  applied  perpendicular  (normal)  to  the  span 
of  runway  beams  and  a  lateral  force  shall  be  applied 
parallel  (longitudinal)  to  the  beam  span. 

(a)  The  lateral  force  acting  normal  to  the  runway 
shall  be  applied  at  the  top  of  the  rail,  and  shall  be 
20%  for  power-operated  crane  trolleys,  and  1 0% 
for  hand-operated  trolleys,  of  the  sum  of  the 
weights  of  the  maximum  lifted  load  and  of  the 
crane  trolley.  This  force  shall  be  distributed  to 
tributary  supporting  structural  members  based  on 
the  relative  lateral  stiffness  of  each  component 
structure  supporting  the  rails. 

(b)  The  longitudinal  force  acting  parallel  to  the 
runway  and  applied  at  the  top  of  the  rail  shall  be 
10%  of  the  maximum  wheel  loads  of  the  crane. 

(c)  Reductions  in  these  loads  may  be  permitted 
if  substantiating  technical  data  acceptable  to  the 
building  official  is  provided. 

(d)  These  loads  need  not  be  considered  in 
combination  with  wind  loads. 

1615.8  Temperature  loads:  Movements,  and 
forces  resulting  from  restraint  of  movements, 
produced  by  changes  in  temperature  shall  be 
considered  in  the  design  of  buildings  and  structures. 

780  CMR  1616.0  COMBINATION  OF  LOADS 

1616.1  General:  Combinations  of  structural  loads 
shall  be  considered  in  accordance  with  780  CMR 
1616.0.  Live  loads  may  be  reduced  as  appropriate  in 
accordance  with  780  CMR  1616.0.  In  addition  to 
the  load  combinations  listed,  the  following  shall  be 
considered  in  design:  structural  effects  of  loads  due 
to  fluids,  loads  due  to  the  weight  and  lateral  pressure 
of  soil  and  water  in  soil,  rain  loads  including 
ponding,  and  effects  arising  from  contraction  or 
expansion  resulting  from  temperature  changes, 
shrinkage,  moisture  changes,  creep  in  component 
materials,  and  movement  due  to  differential 
settlement. 

1616.1.1  Design  Methods:  As  permitted  by  the 
structural  design  standards  listed  in  Appendix  A, 
the  structural  designer  may  use  either  the 
allowable  stress  design  method  (also  called 
working  stress  design)  or  the  strength  design 
method  (also  called  limit  states  design,  load  and 
resistance   factor   design,    or   ultimate   strength 


design).  The  applicable  load  combinations  given 
in  780  CMR  1616.1  shall  govern  over  the  load 
combinations  given  in  the  design  standards  in 
Appendix  A. 

Exception:  Use  load  combinations  from  design 
standards  in  Appendix  A  which  do  not  include 
wind  or  seismic  loads,  if  those  combinations 
produce  a  more  unfavorable  effect  in  the 
structure  or  foundation. 

1616.2  Load   Combinations   Using  Allowable 
Stress  Design 

1616.2.1  Basic  Combinations.  All  loads  listed 
herein  shall  be  considered  to  act  in  the  following 
combinations,  whichever  produces  the  most 
unfavorable  effect  in  the  building,  foundation  or 
structural  member  being  considered.  The  most 
unfavorable  effect  may  occur  when  one  or  more 
of  the  contributing  loads  is  not  acting. 

1 .  Dead 

2.  Dead  +  floor  live  +  roof  live  (or  snow) 

3.  Dead  +  floor  live  +  0.5  roof  live  (or  0.5 
snow)  +  wind 

4.  Dead  +  floor  live  +  roof  live  (or  snow)  +  0.5 
wind 

5.  0.67  Dead  -  wind 

6.  0.67  Dead  -  0.8  seismic 

7.  Dead  +  0.9  floor  live  +  0.6  snow  +  0.8 
seismic 

1616.3  Load  Combinations  Using  Strength  Design 

1616.3.1  Basic  Combinations.  All  loads  listed 
herein  shall  be  considered  to  act  in  the  following 
factored  load  combinations,  whichever  produces 
the  most  unfavorable  effect  in  the  building, 
foundation  or  structural  member  being 
considered.  The  most  unfavorable  effect  may 
occur  when  one  or  more  of  the  contributing  loads 
is  not  acting. 

1.  1.4  Dead 

2.  1.3  Dead+  1.6  floor  live  +  0.5  roof  live  (or 
0.5  snow) 

3.  1.3  Dead  +  0.5  floor  live  +  1.6  roof  live  (or 
1.6  snow) 

4.  1.3  Dead  +  0.5  floor  live  +  0.5  roof  live  (or 
0.5  snow)  +  1.3  wind 

5.  1.3  Uead+  1.6  roof  live  (or  1.6  snow) +  0.8 
wind 

6.  0.9  Dead-  1.3  wind 

7.1.3  Dead  +1.0  floor  live  +  0.7  snow  +1.0 
seismic 

8.  (0.90  -  0.5  Av)  Dead  -  1.0  seismic 
Exception:  The  load  factor  on  floor  live 
load  in  combinations  3  and  4  shall  equal  1.0 
for  garages,  areas  occupied  as  places  of 
public  assembly,  and  all  areas  where  the 
floor  live  load  is  greater  than  100  pounds  per 
square  foot. 


298 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  LOADS 


1616.4  Amplification  of  seismic  load  effects  for 
special  conditions:  Seismic  load  effects  shall  be 
amplified  by  the  factor  2R/5,  where  2R/5  shall  be 
not  less  than  1.0,  in  allowable  stress  design 
780  CMR  1616.2. 1,  and  in  strength  design  780  CMR 
1616.3.1  for  the  following  conditions.  Note:  In 
allowable  stress  design  load  combinations  6  and  7, 
the  term  "0.8  seismic"  shall  be  replaced  by 
"0.8(2R/5)  seismic". 

1.  For  computing  the  design  forces  in  members 
such  as  columns,  girders  or  trusses  which  support 
discontinuous  lateral  force-resisting  elements 
when  using  Load  Combination  7  in  780  CMR 
1616.2.1  (Allowable  Stress  Design)  or  Load 
Combination  7  in  780  CMR  1616.3.1  (Strength 
Design).  However,  the  computed  forces  in  such 
members  need  not  exceed  the  capacity  of  other 
elements  of  the  structure  to  transfer  such  forces 
into  these  members.  The  capacity  of  the  other 
elements  to  transfer  such  forces  shall  not  be  less 
than  1.25  times  the  computed  design  strengths  of 
the  other  elements. 

2.  For  computing  the  design  forces  in  members 
and  connections  that  do  not  develop  the  full 
strength  of  the  weaker  member  connected  when 
using  Load  Combination  6  in  780  CMR  1616.2.1 
(Allowable  Stress  Design)  or  Load  Combination 
8  in  780  CMR  1616.3.1  (Strength  Design). 
However,  the  design  forces  need  not  exceed  the 
limit  determined  by  the  capacity  of  the  foundation 
to  resist  overturning  uplift. 

1616.5  Counteracting  Load:  Where  the  effects  of 
design  loads  counteract  one  another  in  a  structural 


member  or  joint,  the  design  shall  account  for  and 
shall  ensure  adequate  safety  for  possible  stress 
reversals. 

1616.6  Stress  Increases:  All  allowable  stresses  and 
soil  load-bearing  values  specified  in  780  CMR  for 
allowable  stress  design  are  permitted  to  be  increased 
one-third  where  wind  load  or  seismic  load 
combinations  are  utilized. 

1616.7  Crane  hook  loads  are  not  required  to  be 
combined  with  the  roof  live  load,  nor  with  seismic 
load,  nor  with  more  than  0.75  of  the  snow  load  or 
one-half  of  the  wind  load 

780  CMR  1617.0  EXISTING  BUILDINGS 

1617.1  General:  The  repair,  reconstruction, 
alteration,  addition  to  or  change  in  use  or  occupancy 
of  existing  buildings  shall  comply  with  780  CMR 
34. 

1617.2  Posted  live  load:  When  floor  live  loads 
required  by  the  Code  have  been  increased  from  those 
heretofore  approved  for  a  building  or  structure  in  a 
particular  use  group  and  there  is  no  change  to  a  new 
use  requiring  greater  floor  loads  than  those  currently 
required  for  the  original  use  group,  the  floors  so 
affected  may  be  posted  for  the  originally  approved 
live  loads,  provided  the  building  is  structurally  safe 
in  all  its  parts,  is  adequate  for  its  existing  use,  and 
the  public  safety  is  not  endangered  thereby. 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


299 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


300  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  17 


STRUCTURAL  TESTS  AND  INSPECTIONS 

(A  substantial  portion  of  this  Chapter  is  unique  to  Massachusetts) 


780  CMR  1701.0  GENERAL 

1701.1  Scope:  The  provisions  of  780  CMR  17  shall 

govern  the  quality,  workmanship  and  requirements 
for  all  materials  hereafter  used  in  the  construction  of 
buildings  and  structures.  All  materials  of 
construction  and  tests  shall  conform  to  the 
applicable  standards  listed  in  780  CMR. 

1701.2  New  materials:  All  new  building  materials, 
equipment,  appliances,  systems  or  methods  of 
construction  not  provided  for  in  780  CMR,  and  any 
material  of  questioned  suitability  proposed  for  use  in 
the  construction  of  a  building  or  structure,  shall  be 
subjected  to  the  tests  prescribed  in  780  CMR  17  and 
in  the  approved  rules  to  determine  character,  quality 
and  limitations  of  use. 

In  accordance  with  780  CMR  109.3.4,  the 
building  official  may  require  that  such  materials  be 
presented  before  the  Construction  Materials  Safety 
Board  for  approval. 

1701.3  Used  materials:  The  use  of  all  second-hand 
materials  which  meet  the  minimum  requirements  of 
this  code  for  new  materials  shall  be  permitted. 

780  CMR  1702.0  DEFINITIONS 
1702.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  1702.0  and  as 
used  elsewhere  in  780  CMR  have  the  meanings 
shown  herein. 

Approved  agency:  An  established  and  recognized 
agency  regularly  engaged  in  conducting  tests  or 
furnishing  inspection  services,  when  such  agency 
has  been  approved  (see  780  CMR  1704.0). 

Fabricated  item:  Structural,  loadbearing  or  lateral 
/oatf-resisting  assemblies  consisting  of  materials 
assembled  prior  to  installation  in  a  building  or 
structure,  or  subjected  to  operations  such  as  heat 
treatment,  thermal  cutting,  cold  working  or 
reforming  after  manufacture  and  prior  to 
installation  in  a  building  or  structure.  Materials 
produced  in  accordance  with  standard 
specifications  referenced  by  780  CMR,  such  as 
rolled  structural  steel  shapes,  steel-reinforcing 
bars,  masonry  units  and  plywood  sheets,  shall  not 
be  considered  "fabricated  items." 

Inspection,  structural  inspection  as  herein  required 
of  the  installation,  fabrication,  erection  or 
placement     of    components     and     connections 


requiring  special  expertise  to  ensure  adequacy 
(see  780  CMR  1 16.0  and  1705.0). 

Label:    A   plate,    tag   or   other   device   which   is 

permanently  and  prominently  affixed  to  a  product 

or  material  indicating  that  it  has  been  tested  and 

evaluated  by  an  approved  agency  (see  780  CMR 

1704.3). 

Structural    Engineer    of   Record    (SER)     The 

registered  professional  engineer  whose  professional 

seal  of  registration  and  signature  appears  on  the 

design    documents    submitted    with    the   building 

permit   application,   or  the  alternate   (SER)  who 

succeeds  the   (SER),   as   provided  in   780   CMR 

1705.3.3. 

780  CMR  1703.0  INFORMATION  REQUIRED 

1703.1  Material  performance:  Where  the  quality  of 
materials  is  essential  for  conformance  to  780  CMR 
specific  information  shall  be  given  to  establish  such 
quality;  and  780  CMR  shall  not  be  cited,  or  the  term 
"legal"  or  the  term's  equivalent  be  used  as  a 
substitute  for  specific  information.  This  information 
shall  consist  of  test  reports  conducted  by  an 
approved  testing  agency  in  accordance  with  the 
standards  referenced  in  Appendix  A  or  such  other 
information  as  necessary  for  the  code  official  to 
determine  that  the  material  meets  the  applicable 
code  requirements. 

1703.1.1  Labeling:  Where  materials  or 
assemblies  are  required  by  780  CMR  to  be 
labeled,  such  materials  and  assemblies  shall  be 
labeled  by  an  approved  agency  in  accordance 
with  780  CMR  1704.0. 

1703.2  Research  and  investigation:  Sufficient 
technical  data  shall  be  submitted  to  substantiate  the 
proposed  use  of  any  material  or  assembly.  If  it  is 
determined  that  the  evidence  submitted  is 
satisfactory  proof  of  performance  for  the  use 
intended,  the  code  official  shall  approve  the  use  of 
the  maternal  or  assembly  subject  to  the  requirements 
of  780  CMR.  The  cost  of  all  tests,  reports  and 
investigations  required  under  780  CMR  17  shall 

be  paid  by  the  permit  applicant. 

1703.2.1  Research  reports:  Supporting  data, 
where  necessary  to  assist  in  the  approval  of  all 
materials  or  assemblies  not  specifically  provided 
for  in  780  CMR,  shall  consist  of  valid  research 
reports  from  approved  sources. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1703.3  Evaluation  and  follow-up  inspection 
services:  Prior  to  the  approval  of  a  closed 
prefabricated  assembly,  the  permit  applicant  shall 
submit  an  evaluation  report  of  each  prefabricated 
assembly.  The  report  shall  indicate  the  complete 
details  of  the  assembly,  including  a  description  of 
the  assembly  and  the  assembly's  components,  the 
basis  upon  which  the  assembly  is  being  evaluated, 
test  results  and  similar  information,  and  other  data  as 
necessary  for  the  code  official  to  determine 
conformance  to  780  CMR. 

1703.3.1  Evaluation  service:  The  code  official 
shall  review  evaluation  reports  from  approved 
sources  for  adequacy  and  conformance  to 
780  CMR. 

1703.3.2  Follow-up  inspection:  The  owner  shall 
provide  for  structural  inspections  of  fabricated 
items  in  accordance  with  780  CMR  1705. 

1703.3.3  Test  and  inspection  records:  Copies  of 
all  necessary  test  and  inspection  records  shall  be 
filed  with  the  code  official. 

780  CMR  1704.0  APPROVALS 

1704.1  Written  approvals:  Where  approvals  by  the 
building  official  are  required  by  the  provisions  of 
780  CMR,  such  approvals  shall  be  given  in  writing 
within  a  reasonable  time  after  satisfactory 
completion  of  all  the  required  tests  and  submissions 
of  required  test  reports. 

1704.2  Approved  record:  For  any  material, 
appliance,  equipment,  system  or  method  of 
construction  that  has  been  approved,  a  record  of 
such  approval,  including  all  of  the  conditions  and 
limitations  of  the  approval,  shall  be  kept  on  file  in 
the  building  official's  office  and  shall  be  open  to 
public  inspection  at  all  appropriate  times. 

1704.3  Labeling:  Products  and  materials  required  to 
be  labeled  shall  be  labeled  in  accordance  with  the 
procedures  set  forth  in  780  CMR  1704.3.1  through 
1704.3.3. 

1704.3.1  Testing:  An  approved  agency  shall  test 
a  representative  sample  of  the  product  or  material 
being  labeled  to  the  relevant  standard  or 
standards.  The  approved  agency  shall  maintain  a 
record  of  all  of  the  tests  performed.  The  record 
shall  provide  sufficient  detail  to  verify  compliance 
with  the  test  standard. 

1704.3.2  Inspection    and    identification:    The 

approved  agency  shall  periodically  perform  an 
inspection,  which  shall  be  in-plant  if  necessary,  of 
the  product  or  material  that  is  to  be  labeled-  The 
inspection  shall  verify  that  the  labeled  product  or 
material  is  representative  of  the  product  or 
material  tested. 

1704.3.2.1   Independent:  The  agency  to  be 
approved  shall  be  objective  and  competent. 


The  agency  shall  also  disclose  all  possible 
conflicts  of  interest  so  that  objectivity  can  be 
confirmed. 

1704.3.2.2  Equipment:  An  approved  agency 
shall  have  adequate  equipment  to  perform  all 
required  tests.  The  equipment  shall  be 
periodically  calibrated. 

1704.3.2.3  Personnel:  An  approved  agency 
shall  employ  experienced  personnel  educated 
in  conducting,  supervising  and  evaluating 
tests. 

1704.3.3  Label  information:  The  label  shall 
contain  the  manufacturer's  or  distributor's 
identification,  model  number,  serial  number,  or 
definitive  information  describing  the  product  or 
material's  performance  characteristics  and 
approved  agency's  identification. 

1704.4  Heretofore-approved  materials:  The  use  of 

any  material  already  fabricated  or  of  any 
construction  already  erected,  which  conformed  to 
requirements  or  approvals  heretofore  in  effect,  shall 
be  permitted  to  continue,  if  not  detrimental  to  life, 
health  or  safety  of  the  public. 

780  CMR  1705.0  REQUIREMENTS  FOR 
STRUCTURAL  TESTS  AND  INSPECTIONS 

1705.1  General:  The  permit  applicant  shall  provide 
special  inspections  where  application  is  made  for 
construction  as  described  in  780  CMR  1705.0. 

Exceptions: 

1.  Structural  tests  and  inspections  are  not 
required  for  building  components  unless  the 
design  involves  the  practice  of  professional 
engineering  or  architecture  as  defined  by  M.  G.L. 
c  112  §60K and/or  M.G.L.  c  112  §  81D. 

2.  Structural  tests  and  inspections  are  not 
required  for  occupancies  in  Use  Group  R-3. 

1705.2  Purpose:  The  purpose  of  the  structural  tests 
and  inspections  specified  in  780  CMR  1 705  is  to 
provide  assurance  to  the  owner  and  the  building 
official  that  the  construction  complies  with  the 
requirements  of  the  structural  design  by  the  SER 
These  tests  and  inspections  are  for  quality 
asurance  audits  and  their  implementation  does  not 
relieve  the  contractor  or  sub-contractors  of  their 
responsibility  for  quality  control  of  the  work  and 
any  design  for  which  they  are  responsible. 

1705.3  Program  for  tests  and  inspections:  The 
SER  shall  establish  a  program  of  structural  tests 
and  inspections  which  meets  the  requiremnts  of 
780  CMR  17.  The  SER  shall  direct  the 
implementation  of  this  program  and  select  any 
structural  inspectors  required  to  undertake  the 
program.  All  fees  and  costs  related  to  the 
implementation  of  this  program  shall  be  borne  by 
the  owner 


302 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  TESTS  AND  INSPECTIONS 


1705.3.1  Building  permit  requirement:  The 
permit  applicant  shall  submit  the  program  of 
structural  tests  and  inspections  prepared  by  the 
SER  as  a  condition  for  permit  issuance.  This 
program  shall  include  a  complete  list  of 
materials  and  work  requiring  structural  tests  and 
inspections  by  780  CMR  1 705.  1,  the  inspections 
to  be  performed  and  a  list  of  the  individuals, 
approved  agencies  and  firms  intended  to  be 
retained  for  conducting  such  inspections. 

1705.3.2  Report  requirement  A  final  report 
stating  that  the  program  of  structural  tests  and 
inspections  has  been  satisfactorily  completed 
shall  be  submitted  to  the  owner  and  the  building 
official  by  the  SER  prior  to  the  issuance  of  the 
certificate  of  occupancy.  As  construction 
progresses,  inspection  reports  and  records  of 
tests  and  measurements  shall  be  maintained  by 
the  SER.  When  these  records  are  requested  by 
the  building  official,  they  shall  be  submitted 
promptly,  in  accordance  with  procedures 
established  by  the  building  official  prior  to  the 
start  of  construction.  When  deviations  from 
design  requirements  are  determined  during  tests 
or  inspections,  the  SER  shall  promptly  report 
such  to  the  contractor  for  correction.  If  the 
contractor  fails  to  correct  any  reported  deviation, 
it  shall  be  reported  to  the  building  official  by  the 
SER. 

1705.3.3  Alternate  SER:  If  the  SER  cannot 
continue  with  the  project,  the  owner  shall  retain 
an  alternate  qualified  registered  professional 
engineer  to  review  the  design  and  assume  the 
full  responsibilities  of  the  former  SER 

1705.3.4  Performance  speciflactions:  The  SER 
shall  identify,  in  the  program  of  structural  tests 
and  inspections  submitted  with  the  building 
permit  application,  any  structural  elements  or 
systems  that  the  SER  has  specified  to  be 
designed  by  another  registered  professional 
engineer.  The  SER  shall  review  the  design  of 
these  structural  elements  or  systems  and  shall 
include  them  in  the  program  of  structural  tests 
and  inspections. 

1705.3.5  Waiver  of  structural  inspection  by  the 
SER:  Where,  in  then  opinion  of  the  SER,  any 
portion  of  the  contractor's  quality  control 
program  meets  the  inspection  and  test 
requirements  of  780  CMR  1705,  the  SER  may- 
reduce  the  specified  quality  assurance  structural 
inspection  and  test  program  following  approval 
by  the  building  official  When  this  is  done  the 
final  inspection  report  shall  also  include 
reference  to  the  results  of  those  inspections 
performed  by  the  contractor.  As  construction 
progresses,  reports  of  inspections  ■  and 
measurements  shall  be  submitted  to  the  SER 
and,  if  requested  to  the  building  official 


1705.4  Inspection  of  fabricators:  Where  fabrication 
of  structural  loadbearing  members  and  assemblies  is 
being  performed  on  the  premises  of  a  fabricator's 
shop,  structural  inspection  of  the  fabricated  items 
shall  be  required.  The  fabricated  items  shall  be 
inspected  as  required  by  780  CMR  1705.0  and  as 
required  elsewhere  in  780  CMR. 

1705.4.1  Fabrication  procedures  The  special 
inspector  shall  verify  that  the  fabricator  maintains 
detailed  fabrication  and  quality  control  procedures 
which  provide  a  basis  for  inspection  control  of  the 
workmanship  and  the  fabricator's  ability  to 
conform  to  approved  drawings,  project 
specifications  and  referenced  standards.  The 
special  inspector  shall  review  the  procedures  for 
completeness  and  adequacy  relative  to  the  code 
requirements  for  the  fabricator's  scope  of  work. 

1705.4.2  Procedures  implementation  The 
structural  inspector  shall  verify  that  the  fabricator 
is  properly  implementing  the  fabrication  and 
quality  control  procedures  outlined  in  780  CMR 
1705.4.1. 

Exception  Structural  inspections  as  required 
by  780  CMR  1705.4  may  be  reduced  by  the 
SER  where  the  fabricator  maintains  an 
agreement  with  an  approved  independent 
inspection  or  quality  control  agency  to 
conduct  periodic  in-plant  inspections  at  the 
fabricator's  plant,  at  a  frequency  that  will 
assure  the  fabricator's  conformance  to  the 
requirements  of  the  inspection  agency's 
approved  quality  control  program. 

1705.5  Steel  construction:  The  structural 
inspections  for  steel  elements  of  buildings  and 
structures  shall  be  as  required  by  780  CMR  1705.5. 1 
through  1705.5.3 

1705.5.1  Inspection  of  steel  fabricators    The 

permit  applicant  shall  provide  structral 
inspection  of  steel  fabricated  items  in  accordance 
with  the  provisions  of  780  CMR  1705.2. 

Exception:  Structural  Inspection  of  the  steel 
fabrication  process  shall  not  be  required  where 
the  fabricator  does  not  perform  any  welding, 
thermal  cutting  or  heating  operation  of  any 
kind  as  part  of  the  fabrication  process.  In  such 
cases,  the  fabricator  shall  be  required  to  submit 
a  detailed  procedure  for  material  control  which 
demonstrates  the  fabricator's  ability  to  maintain 
suitable  records  and  procedures  such  that,  at 
any  time  during  the  fabrication  process,  the 
material  specification,  grade  and  mill  test 
reports  for  the  main  stress-carrying  elements 
and  bolts  are  capable  of  being  determined. 

1705.5.2  Material  receiving:  All  main  stress- 
carrying  elements,  welding  material  and  bolting 
material  shall  be  inspected  for  conformance  to 
Table  1705.5.2. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1705.5.2 
INSPECTION  FOR  STEEL  MATERIALS 


Material 

Inspection  requuired 

Reference  for 
criteria 

Bolts, 
nuts, 
washers 

1  -  Material  identification 
markings 

2.  Conformance  to  ASTM 
standards  specified  by 
the  design  engineer 
Manufacturer's  certifi- 
cate of  compliance  is 
required 

Applicable  ASTM 
material 

specifications;  AISC 
ASD,  Section  A3.4; 
AISC  LRFD, 
Section  A3. 3 

Structural 
steel 

1    Material  identification 

markings 
2.  Conformance  to  ASTM 

standards  specified  in 

the  approved  plans  and 

specifications 

ASTM  A6  or  ASTM 
A568 

Provide  certified  test 
reports  in  accord- 
ance with  ASTM  A6 
orASTMA568 

Weld  filter 
materials 

1  -  Conformance  to  AWS 
specifications  as  speci- 
fied in  the  approved 
plans  and  specifica- 
tions. 

Manufacturer's  certifi- 
cate of  compliance  is 
required 

AISC  ASD.  Section 
A3.6:  AISC  LRFD. 
Section  A3. 5 

Note  a.  The  specific  standards  referenced  are  those  listed 
in  Appendix  A. 

1705.5.3  Erection:  Structural  inspections  are 
required  for  bolts,  welding  and  details  as  specified 
in  780  CMR  1705.5.3.1  through  1705.5.3.3. 

1705.5.3.1  Installation  of  high-strength 
bolts:  Inspection  shall  be  as  specified  in 
Section  9  of  the  RCSC  Specification  for 
Structural  Joints  Using  A325  or  A490  Bolts 
listed  in  Appendix  A 

1705.5.3.2  Welding:  Weld  inspection  shall  be 
in  compliance  with  Section  6  of  AWS  D  i .  I 
listed  in  Appendix  A  Weld  inspectors  shall  be 
certified  in  accordance  with  AWS  D 1 . 1  listed 
in  Appendix  A 

1705.5.3.2.1  Welding  of  the  structural 
seismic-resisting  system:  Welding  of  the 
structural  seismic-resisting  system  of 
buildings,  shall  be  inspected  in  accordance 
with  780  CMR  1705.5.3.2.2  and 
1705.5.3.2.3.  Each  complete  penetration 
groove  weld  in  joints  and  splices  shall  be 
tested  for  the  full  length  of  the  weld  either 
by  ultrasonic  testing  or  by  other  approved 
methods,  for  special  moment  frames  and 
eccentrically  braced  frames 

Exception:  The  nondestructive  testing  rate 
for  welds  made  by  an  individual  welder  is 
permitted  to  be  reduced  to  25%  of  the  welds, 
with  the  approval  of  the  SER,  provided  the 
weld  inspection  reject  rate  is  5%  or  less. 

1705.5.3.2.2  Column  splice  welds:  Column 
splice  welds,  which  are  partial  penetration 
groove  welds,  shall  be  tested  by  ultrasonic 
testing  or  other  approved  methods  at  a 
percentage  rate  established  by  SER.   All 


partial    penetration    column    splice    welds 

designed  for  axial  or  flexural  tension  from 

seismic  forces  shall  be  tested. 

1705.5.3.2.3  Base  metal  testing  Base  metal 

having  a  thickness  more  than  1.5  inches  (38 

mm)  and  subject  to  through-thickness  weld 

shrinkage    strains    shall    be    ultrasonically 

tested     for    discontinuities     behind     and 

adjacent  to  the  welds  after  joint  welding 

Any     material     discontinuities     shall     be 

evaluated  based  on  the  criteria  established  in 

the  construction  documents  by  the  SER. 

1705.5.3.3  Details:  The  structural  inspector 

shall  perform  an  inspection  of  the  steel  frame 

to  verify  compliance  with  the  details  shown  on 

the  approved  construction  documents,  such  as 

bracing,    stiffening,    member    locations    and 

proper   application  of  joint  details  at   each 

connection. 

1705.6  Concrete  construction:  The  structural 
inspections  for  concrete  structures  and  concreting 
operations  shall  be  as  required  by  780  CMR 
1705.6.1  through  1705.6.6. 

Exception:  Structural  inspections  shall  not  be 

\  required  for: 

\  1.  Concrete  footings  of  buildings  three  stones 
^srless  in  height  which  are  fully  supported  on 
earth  or  rock 

2.  Nonstructural  concrete  slabs  supported 
directly  on  the  ground,  including  prestressed 
slabs  on  grade,  where  the  effective  prestress  in 
the  concrete  is  less  than  1 50  psi  (0.11  kg/mm2) 

3  Plain  concrete  foundation  walls  constructed 
in  accordance  with  Table  1812.3.2. 

4  Concrete  patios,  driveways  and  sidewalks, 
on  grade 

1705.6.1  Materials:  In  the  absence  of  sufficient 
data  or  documentation  providing  evidence  of 
conformance  to  quality  standards  for  materials  in 
Chapter  3  of  ACI  3 1 8  listed  in  Appendix  A  the 
code  official  shall  require  testing  of  materials  in 
accordance  with  the  appropriate  standards  and 
criteria  for  the  material  in  Chapter  3  of  ACI  3 1 8 
listed  in  Appendix  A.  Weldability  of 
reinforcement  that  conforms  to  ASTM  A706 
listed  in  Appendix  A  shall  be  determined  in 
accordance  with  the  requirements  of  780  CMR 
1906.5.2. 

1705.6.2  Installation  of  reinforcing  and 
prestressing  steel:  The  location  and  installation 
details  of  reinforcing  and  prestressing  steel  shall 
be  inspected  for  compliance  with  the  approved 
construction  documents  and  ACI  318  (such  as 
Sections  7.4,  7.5,  7.6  and  7.7)  listed  in 
Appendix  A.  Welding  of  reinforcing  of  the 
structural  seismic-resisting  system  shall  be 
inspected. 


304 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  TESTS  AND  INSPECTIONS 


1705.6.3  Concreting  operations:  During  placing 
and  curing  of  concrete,  the  special  inspections 
listed  in  Table  1705.6.3  shall  be  performed. 

Table  1705.6.3 

REQUIRED  INSPECTIONS  DURING 

CONCRETING  OPERATIONS 


Table  1705.7 
SPECIAL  INSPECTIONS  FOR 
MASONRY  CONSTRUCTION 


Required  inspection 


Evaluation  of  concrete 
strength,  except  as  exempted 
by  780  CMR1 908.3  1(3). 
Inspection  &r  use  of  proper 
mix  proportions  and  proper 
mix  techniques. 
Inspection  during  concrete 
placement,  for  proper 
application  techniques. 
Inspection  for  maintenance  of 
specified  curing  temperatures 
and  techniques. 


Reference  for  criteria 


ACI  31 8  Section  5.6 


AQ  31 8  Chapter  4, 

Sections  5.2,  5.3,  5.4  and 

5.8 

ACI  318  Sections  5.9  and 

5.10 

ACI  318  Sections  5.11, 
5.12and5.13 


Note  a   ACI  318  listed  in /l/?pe/i<ftx/l 

1705.6.4  Inspection     during     prestressing: 

Inspection  during  the  application  of  prestressing 
forces  shall  be  performed  to  determine 
compliance  with  Section  18.18  of  ACI  318  listed 
in  Appendix  A 

1705.6.4.1  Inspection  during  grouting 
Inspection  during  the  grouting  of  bonded 
prestressing  tendons  in  the  structural  seismic- 
resisting  system  shall  be  performed. 

1705.6.5  Manufacture  of  precast  concrete:  The 

manufacture  of  precast  concrete,  as  required  by 
780  CMR  1705.4,  shall  be  subject  to  a  quality 
control  program  administered  by  an  approved 
agency 

1705.6.6  Erection  of  precast  concrete:  Erection 
of  precast  concrete  shall  be  inspected  for 
compliance  with  the  approved  plans  and  erection 
drawings. 

1705.7  Masonry  construction:  The  structural 
inspections  listed  in  Table  1705.7  shall  be  required 
for  masonry  construction. 


Referenced   criteria 

ACI  530/ 

ACI  530.1 

Inspection  or  test 

ASCE5/ 

ASCE  6/ 

TMS402 

IMS  602 

i.  Material 

Sec.2.2 

2.  Masonry  strength 

Sec.  1.6 

3   Construction  operations: 

a.   Proportioning,  miximg 

Sec.  2.3.2.5 

consistency  of  mortar  and 

Sec  4.2.2 

grout 

b.   Application  of  mortar  grout 

Sec.  2.3.3.3 

and  masonry  units 

Sec.  4.3.3 

c.   Condition,  size,  location  and 

Chapters 

d    Protection  of  masonry 'during 

Sec.  2.3.2.2 

cold  weather  (temperature 

Sec  2.3.2.3 

below  40  °F)  or  hot  weather 

(temperature  above  100°F) 

e.  Anchorage 

Sec.  4.2 
Sec.  5.14 

4    Inspection  of  welding  of 

Noteb 

Note  b 

reinforcement,  grouting. 

consolidation  and  reconsolidation 

for  buildings  assigned  to  Seismic 

Performance  Category  Cor  D  in 

accordance  with  780  CMR 

1612.2.7 

Note  a.  The  specific  standards  referenced  are  those  listed 

in  Appendix  A. 

Note  b    Referenced  criteria  not  applicable. 

1705.8  Wood  construction  Structural  inspections 
of  the  fabrication  process  of  wood  structural 
elements  and  assemblies  shall  be  in  accordance  with 
780  CMR  1705.4.  Structural  inspection  is  required 
for  nailing,  bolting,  structural  gluing  or  other 
fastening  of  the  structural  seismic-resisting  system 

1705.9  Prepared  fill:  The  structural  inspections  for 
prepared  fill  shall  be  as  required  by  780  CMR 
1705.9. i  through  1705.9.3.  The  approved  report, 
required  by  780  CMR  1804.1,  shall  be  used  to 
determine  compliance. 

1705.9.1  Site  preparation:  Prior  to  placement  of 
the  prepared  fill,  the  structural  inspector  shall 
determine  that  the  site  has  been  prepared  in 
accordance  with  the  approved  report. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1705.9.2  During  fill  placement  During  the 
placement  and  compaction  of  the  fill  material,  the 
structural  inspector  shall  determine  that  the 
material  being  used  and  the  maximum  lift 
thicknesses  comply  with  the  approved  report. 

1705.9.3  Evaluation  of  in-place  density:  The 

structural  inspector  shall  determine,  at  the 
approved  frequency,  that  the  in-place  dry  density 
of  the  compacted  fill  complies  with  the  approved 
report. 

1705.10  Pile  foundations:  Structural  inspections  of 
pile  foundations  are  required  as  provided  for  in 
780  CMR  1816.13. 

1705.11  Pier  foundations:  Structural  inspection  is 
required  for  pier  foundations. 

1705.12  Wall  panels  and  veneers:  Structural 
inspection  is  required  for  exterior  wall  panels  and 
their  attachment  to  the  building  structure. 

1705.13  Light  gauge  metal  framing:  Structural 
inspection  is  required  for  light  gauge  metal 
framing  systems  for  roofs,  floors,  and  load  bearing 
walls  and  for  light  gauge  metal  framing  in  exterior 
curtain  walls  that  have  a  story  height  greater  than 
ten  feet 

1705.14  Special  cases:  Structural  inspections  shall 
be  required  for  proposed  work  which  is,  in  the 
opinion  of  the  code  official,  unusual  in  its  nature, 
such  as: 

1.  Construction  of  materials  and  systems  which 
are  alternatives  to  materials  and  systems 
prescribed  by  780  CMR. 

2.  Unusual  design  applications  of  materials 
described  in  780  CMR. 

3.  Materials  and  systems  required  to  be  installed 
in  accordance  with  additional  manufacturer's 
instructions  that  prescribe  requirements  not 
contained  in  780  CMR  or  in  standards  referenced 
by  780  CMR. 

780  CMR  1706.0  DESIGN  STRENGTHS 
OF  MATERIALS 

1706.1  Conformance  to  standards:  The  design 
strengths  and  permissible  stresses  of  any  structural 
material  that  is  identified  as  to  manufacture  and 
grade  by  mill  tests,  or  the  strength  and  stress  grade 
is  otherwise  confirmed  to  the  satisfaction  of  the  code 
official,  shall  conform  to  the  specifications  and 
methods  of  design  of  accepted  engineering  practice 
or  the  approved  rules  in  the  absence  of  applicable 
standards 

1706.2  New  materials:  For  materials  which  are  not 
specifically  provided  for  in  780  CMR,  the  design 
strengths     and     permissible     stresses     shall     be 


established  by  tests  as  provided  for  in  780  CMR 

1708.0  and  1709.9. 

780  CMR  1707.0  ALTERNATIVE  TEST 
PROCEDURE 

1707.1  General:  In  the  absence  of  approved  rules  or 
other  approved  standards,  the  code  official  shall 
make,  or  cause  to  be  made,  the  necessary  tests  and 
investigations;  or  the  code  official  shall  accept  duly 
authenticated  reports  from  approved  agencies  in 
respect  to  the  quality  and  manner  of  use  of  new 
materials  or  assemblies  as  provided  for  in  780  CMR 
106.0.  The  cost  of  all  tests  and  other  investigations 
required  under  the  provisions  of  780  CMR  shall  be 
borne  by  the  permit  applicant. 

780  CMR  1708.0  TEST  SAFE  LOAD 
1708.1  Where  required  Where  proposed 
construction  is  not  capable  of  being  designed  by 
approved  engineering  analysis,  or  where  proposed 
construction  design  method  does  not  comply  with 
the  applicable  material  design  standard  listed  in 
Appendix  A,  the  system  of  construction  or  the 
structural  unit  and  the  connections  shall  be  subjected 
to  the  tests  prescribed  in  780  CMR  1710.0.  The  code 
official  shall  accept  certified  reports  of  such  tests 
conducted  by  an  approved  testing  agency,  provided 
that  such  tests  meet  the  requirements  of  780  CMR 
and  approved  procedures. 

780  CMR  1709.0  EV-SrTU  LOAD  TESTS 

1709.1  General:  Whenever  there  is  a  reasonable 
doubt  as  to  the  stability  or  loadbearing  capacity  of  a 
completed  building,  structure  or  portion  thereof  for 
the  expected  loads,  an  engineering  assessment  shall 
be  required.  The  engineering  assessment  shall 
involve  either  a  structural  analysis  or  an  in-situ  load 
test,  or  both.  The  structural  analysis  shall  be  based 
upon  actual  material  properties  and  other  as-built 
conditions  which  affect  stability  or  loadbearing 
capacity,  and  shall  be  conducted  in  accordance  with 
the  applicable  design  standard  listed  in  Appendix  A. 
If  the  structural  assessment  determines  that  the 
loadbearing  capacity  is  less  than  that  required  by  the 
code,  load  tests  shall  be  conducted  in  accordance 
with  780  CMR  1709.2.  If  the  building,  structure  or 
portion  thereof  is  found  to  have  inadequate  stability 
or  loadbearing  capacity  for  the  expected  loads, 
modifications  to  insure  structural  adequacy  or  the 
removal  of  the  inadequate  construction  shall  be 
required. 

1709.2  Test  standards:  All  structural  components 
and  assemblies  shall  be  tested  in  accordance  with  the 
appropriate  material  standards  listed  in  Appendix  A 
In  the  absence  of  a  standard  listed  in  Appendix  A 
that  contains  an  applicable  load  test  procedure,  the 
test  procedure  shall  be  developed  by  a  registered 
professional  engineer  and  approved  The  test 
procedure  shall  simulate  the  loads  and  conditions  of 


306 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

STRUCTURAL  TESTS  AND  INSPECTIONS 


application  that  the  completed  structure  or  portion 
thereof  will  be  subjected  to  in  normal  use. 

1709.3  In-situ  load  tests:  All  in-situ  load  tests  shall 
be  conducted  in  accordance  with  780  CMR  1709.3. '; 
or  1709.3.2  and  shall  be  supervised  by  a  registered 
professional  engineer  The  test  shall  simulate  the 
applicable  loading  conditions  specified  in  780  CMR 
16  as  necessary  to  address  the  concerns  regarding 
structural  stability  of  the  building,  structure  or 
portion  thereof. 

1709.3.1  Load  test  procedure  specified:  Where 

a  standard  listed  in  Appendix  A  contains  an 
applicable  load  test  procedure  and  acceptance 
criteria,  the  test  procedure  and  acceptance  criteria 
in  the  standard  shall  apply.  In  the  absence  of 
specific  load  factors  or  acceptance  criteria,  the 
load  factors  and  acceptance  criteria  in  780  CMR 

1709.3.2  shall  apply. 

1709.3.2  Load  test  procedure  not  specified  In 

the  absence  of  applicable  load  test  procedures 
contained  within  a  standard  referenced  by  this 
code  or  acceptance  criteria  for  a  specific  materia! 
or  method  of  construction,  such  existing  structure 
shall  be  subjected  to  a  test  load  equal  to  two  times 
the  design  load  The  test  load  shall  be  left  in  place 
for  a  period  of  24  hours.  The  structure  shall  be 
considered  to  have  met  successfully  the  test 
requirements  if  all  of  the  following  criteria  are 
satisfied: 

1 .  Under  the  design  load,  the  deflection  shall 
not  exceed  the  limitations  specified  by  the 
SER 

2.  Within  24  hours  after  removal  of  the  test 
load,  the  structure  shall  have  recovered  not  less 
than  75%  of  the  maximum  deflection;  and 

3 .  During  and  immediately  after  the  test,  the 
structure  shall  not  show  evidence  of  failure. 

780  CMR  1710.0  PRECONSTRUCTION 
LOAD  TESTS 

1710.1  General:  In  evaluating  the  physical 
properties  of  materials  and  methods  of  construction 
which  are  not  capable  of  being  designed  by 
approved  engineering  analysis  or  which  do  not 
comply  with  the  applicable  material  design  standards 
listed  in  Appendix  A,  the  structural  adequacy  shall 
be  predetermined  based  on  the  load  test  criteria 
established  by  780  CMR  1710.2  through  1710.5 

1710.2  Load  test  procedures  specified:  Where 
specific  load  test  procedures,  load  factors  and 
acceptance  criteria  are  included  in  the  applicable 
design  standards  listed  in  Appendix  A,  such  test 
procedures,  load  factors  and  acceptance  criteria  shall 
apply  In  the  absence  of  specific  test  procedures, 
load  factors  or  acceptance  criteria,  the  corresponding 
provisions  in  780  CMR  1710.3  shall  apply 


1710.3  Load  test  procedures  not  specified  Where 
load  test  procedures  are  not  specified  in  the 
applicable  design  standards  listed  in  Appendix  A, 
the  loadbearing  capacity  of  structural  components 
and  assemblies  shall  be  determined  on  the  basis  of 
load  tests  conducted  in  accordance  with  780  CMR 
1710.3.1  and  1710.3.2.  Load  tests  shall  simulate  all 
of  the  applicable  loading  conditions  specified  in 
780  CMR  16. 

1710.3.1  Test  procedure  The  test  assembly  shall 
be  subjected  to  an  increasing  superimposed  load 
equal  to  not  less  than  two  times  the  superimposed 
design  load.  The  test  load  shall  be  left  in  place  for 
a  period  of  24  hours.  The  tested  assembly  shall  be 
considered  to  have  met  successfully  the  test 
requirements  if  the  assembly  recovers  not  less 
than  75%  of  the  maximum  deflection  within  24 
hours  after  the  removal  of  the  test  load  The  test 
assembly  shall  then  be  reloaded  and  subjected  to 
an  increasing  superimposed  load  until  either 
structural  failure  occurs  or  the  superimposed  load 
is  equal  to  2Vz  times  the  load  at  which  the 
deflection    limitations    specified    in    780    CMR 

1710.3.2  were  reached,  or  the  load  is  equal  to  2Vz 
times  the  superimposed  design  load.  In  the  case  of 
structural  components  and  assemblies  for  which 
deflection  limitations  are  not  specified  in 
780  CMR  1710.3.2,  the  test  specimen  shall  be 
subjected  to  an  increasing  superimposed  load  until 
structural  failure  occurs  or  the  load  is  equal  to  2Vi 
times  the  desired  superimposed  design  load  The 
allowable  superimposed  design  load  shall  be 
taken  as  the  lesser  of: 

1  The  load  at  the  deflection  limitation  given 
by  780  CMR  1709.3.2; 

2  The  failure  load  divided  by  2.5,  or 

3.    The  maximum  load  applied  divided  be  2.5. 

1710.3.2  Deflection:  The  deflection  of  structural 
members  under  the  design  load  shall  not  exceed 
the  limitations  in  780  CMR  1604.5 

1710.4  Wall       and       partition       assemblies 

Loadbearing  wall  and  partition  assemblies  shall 
sustain  the  test  load  both  with  and  without  window 
framing.  The  test  load  shall  include  all  design  load 
components. 

1710.5  Test  specimens:  All  test  specimens  and 
construction  shall  be  representative  of  the  materials, 
workmanship  and  details  normally  used  in  practice. 
The  properties  of  the  materials  used  to  construct  the 
test  assembly  shall  be  determined  on  the  basis  of 
tests  on  samples  taken  from  the  load  test  assembly  or 
on  representative  samples  of  the  materials  used  to 
construct  the  load  test  assembly.  All  required  tests 
shall  be  conducted  or  witnessed  by  an  approved 
agency  Wall  and  partition  assemblies  shall  be  tested 
both  with  and  without  door  and  window  framing 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


307 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


308  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  18 


FOUNDATIONS  AND  RETAINING  WALLS 

(This  Chapter  is  unique  to  Massachusetts) 


780  CMR  1801.0  GENERAL 

1801.1  Scope:  The  provisions  of  780  CMR  18  shall 

control  the  foundation  design  and  construction  of  all 
buildings  and  structures  hereafter  erected  to  insure 
adequate  strength  of  all  parts  thereof  for  the  safe 
support  of  all  superimposed  live  and  special  loads, 
in  addition  to  their  own  dead  load,  without 
exceeding  the  allowable  stresses  or  design 
capabilities. 

780  CMR  1802.0  FOUNDATION 
INVESTIGATIONS 

1802.1  Where  required:  Borings,  test  pits  or  other 
soil  investigations  shall  be  required  for  all  structures 
except  the  following,  unless  specifically  required  by 
the  code  official: 

1.  one-  and  two-family  dwellings  and  their 
accessory  buildings; 

2.  structures  less  than  35,000  cubic  feet  in  gross 
volume;  or 

3.  structures  used  for  agricultural  purposes. 

The  borings,  test  pits  or  other  soil  investigations 
shall  be  adequate  in  number  and  depth  and  so 
located  to  accurately  define  the  nature  of  the 
subsurface  materials  necessary  for  the  support  of  the 
structure.  When  it  is  proposed  to  support  the 
structure  directly  on  bedrock,  the  code  official  shall 
require  core  borings  to  be  made  into  the  rock;  or 
shall  require  other  satisfactory  evidence  to  prove  that 
the  structure  shall  be  adequately  founded  on 
bedrock. 

1802.1.1  Seismic  investigation:  Where  the 
foundation  investigation  indicates  subsoils  of 
Material  Classes  8  or  9,  as  defined  in  Table 
1804.3,  a  soil  investigation  report  which  evaluates 
the  potential  hazards  due  to  liquefaction  and  slope 
instability  during  an  earthquake  shall  be  submitted 
to  the  code  official.  The  liquefaction  evaluation 
shall  be  performed  in  accordance  with  780  CMR 
1805.3 

1802.2  Soil  samples  and  boring  reports:  Samples 
of  the  strata  penetrated  in  test  borings  or  test  pits, 
representing  the  natural  disposition  and  conditions  at 
the  site,  shall  be  available  for  examination  by  the 
code  official.  Wash  or  bucket  samples  shall  not  be 
accepted.  Duplicate  copies  of  the  results  obtained 
from  all  borings  and  of  all  test  results  or  other 
pertinent  soil  data  shall  be  filed  with  the  code 
official. 


780  CMR  1803.0  SOD1  BEARING  TESTS 

1803.1  General:  Whenever  the  allowable  bearing 
pressure  on  bearing  materials  is  in  doubt,  the  code 
official  may  require  soil  bearing  tests.  The  tests 
shall  be  performed  under  the  direction  of  a 
registered  design  professional.  A  complete  record 
of  the  test  results  together  with  a  soil  profile  shall  be 
filed  by  the  registered  design  professional  who  shall 
have  a  representative  on  the  site  during  all  boring 
and  test  operations. 

1803.2  Loaded  areas:  The  loaded  area  shall  be 
approximately  four  square  feet  for  all  bearing 
materials;  except  that  when  the  footing  overlies  wet 
clay  or  other  soft  materials,  the  test  load  shall  be 
applied  to  an  area  of  not  less  than  ten  square  feet. 
Bearing  tests  shall  be  applied  at  the  elevations  of  the 
proposed  bearing  surfaces  of  the  structure;  except 
that  the  load  may  be  applied  directly  on  the  surface 
of  compacted  granular  material.  The  excavation 
within  three  feet  (1  m)  surrounding  an  area  to  be 
tested  shall  be  made  not  deeper  than  one  foot  (0.3  m) 
above  the  plane  of  application  of  the  test.  The  test 
plate  shall  be  placed  with  uniform  bearing. 

1803.3  Loading  procedure:  The  application  of  the 
test  load  shall  be  in  steps  equal  to  not  more  than  Vi 
the  contemplated  design  bearing  pressure,  to  at  least 
twice  the  contemplated  design  bearing  pressure.  The 
unloading  shall  be  at  least  two  steps,  to  the  design 
pressure  and  then  to  zero  load.  The  contemplated 
design  pressure  and  twice  the  contemplated  design 
pressure  shall  be  maintained  constant  for  at  least  24 
hours  and  until  the  movement  does  not  exceed  two 
hundredths  of  an  inch  (0.5  mm)  during  a  24-hour 
period.  The  load  for  all  other  load  and  unload  steps 
including  the  zero  load  at  the  end  of  the  test  shall  be 
maintained  constant  for  a  period  of  not  less  than  four 
hours.  Sufficient  readings  for  each  load  step  shall  be 
made  to  define  properly  the  time-deflection  curve. 

1803.4  Accuracy  of  loading:  Test  loads  applied  by 
mechanical  devices  shall  be  automatically  controlled 
so  as  to  insure  not  more  than  a  5%  variation  in 
applied  load.  Such  devices  shall  be  calibrated  prior 
to  the  test. 

1803.5  Test  acceptance:  The  proposed  design  load 
shall  be  allowed  provided  that  the  requirements  of 
780  CMR  1805.5  are  fulfilled  and  the  settlements 
under  the  design  bearing  pressure  and  twice  the 
design  bearing  pressure  do  not  exceed  %  of  an  inch 
(10  mm)  and  one  inch  (25  mm),  respectively. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


309 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  18O4.0  LOAD  BEARING 
VALUE  OF  SOILS 

1804.1  Soils  report:  All  applications  for  permits  for 
the  construction  of  new  buildings  or  structures,  and 
for  the  alteration  of  permanent  structures  which 
require  changes  in  foundation  loads  and  distribution, 
shall  be  accompanied  by  a  report  describing  the  soil 
in  the  ultimate  loadbearing  strata,  including 
sufficient  data  to  establish  its  character,  nature  and 
loadbearing  capacity.  The  report  shall  be  prepared 
by  a  registered  design  professional. 

1804.2  Satisfactory      foundation      materials: 

Satisfactory  bearing  strata  to  provide  structural 
support  shall  be  considered  to  include  the  following: 
natural  strata  of  rock,  gravel,  sand,  inorganic  silt, 
inorganic  clay,  or  combination  of  these  materials 
provided  that  they  do  not  overlie  an  appreciable 
amount  of  peat,  organic  silt,  soft  clay  or  other 
objectionable  materials.  Compacted  fills,  when 
designed  and  monitored  by  a  registered  design 
professional,  may  be  accepted  by  the  code  official. 
Other  conditions  of  unsatisfactory  bearing  materials 
which  are  improved  in  accordance  with  the 
recommendations  of,  and  monitored  by,  a  registered 
design  professional  may  be  accepted  by  the  code 
official. 

1804.2.1  Loading  interaction:  Wherever  bearing 
strata  are  subject  to  interaction  from  other 
loadings  or  strata  reactions,  such  conditions  shall 
be  incorporated  in  the  evaluation  of  the  design 
bearing  capacity  of  the  support  strata. 

1804.2.2  Protection  of  bearing  strata.  Bearing 
strata  which  may  be  adversely  affected  by 
conditions  within  the  structure,  such  as 
evaporation  and  shrinkage  due  to  excess  heat  or 
cold,  shall  be  adequately  protected. 

1804.3  Presumptive  load   bearing  values:   The 

maximum  allowable  pressure  on  supporting  soils 
under  spread  footings  at  or  near  the  surface  shall  not 
exceed  the  values  specified  in  Table  1804.3  or  the 


maximum  allowable  pressure  shall  be  determined  by 
load  tests  conducted  in  the  field  or  as  otherwise 
provided  herein.  Presumptive  loadbearing  values 
shall  apply  to  all  materials  with  similar  physical 
characteristics.  Surface  values  shall  be  adjusted  for 
deep  footings  and  for  weaker  loadbearing  strata 
below  piles,  as  provided  for  in  780  CMR  1817.8. 
Higher  allowable  bearing  pressures  may  be  approved 
by  the  code  official  when  substantiated  by  the  results 
of  investigations,  analyses  or  testing  prepared  by  a 
registered  design  professional. 

1804.3.1  Classification  of  bearing  materials: 

The  terms  used  in  780  CMR  1804  shall  be 
interpreted  in  accordance  with  generally  accepted 
engineering  nomenclature.  Refer  to  commentary 
in  Appendix  D  for  guidelines  regarding  soil  and 
rock  classification  and  description. 

1804.3.2  Prepared  fill:  Materials  from  Classes  6 
through  8,  Table  1804.3,  or  dense  graded  crushed 
stone  or  slag,  which  contain  no  plastic  fines,  shall 
have  a  maximum  allowable  bearing  pressure  of  up 
to  five  tons  per  square  foot  when  compacted  to 
95%  or  greater  of  the  maximum  dry  density  as 
determined  by  ASTM  D1557  listed  in  Appendix 
A.  For  compacted  fills  which  do  not  meet  the 
above  criteria  or  materials  which  cannot  be  tested 
as  above,  &  registered  design  professional  shall  be 
engaged  to  provide  recommendations  for 
compaction  and  maximum  allowable  design 
bearing  pressures. 

1804.3.3  Field  Control:  The  code  official  will 
require  that  a  registered  design  professional  or  his 
representative  be  on  the  project  at  all  times  while 
fill  is  being  placed  and  compacted.  The 
representative  shall  make  an  accurate  record  of 
the  types  of  materials  used,  including  grain-size 
curves,  thickness  of  lifts,  densities,  percent 
compaction,  type  of  compacting  equipment  and 
number  of  coverages,  the  use  of  water  and  other 
pertinent  data. 


310 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 

Table  1804.3 

ALLOWABLE  BEARING  PRESSURES  FOR 

FOUNDATION  MATERIALS 


Material 
Class 


Descnptic 


Notes 


Consistency  in  Place 


Allowable  Net  Bearing 
Pressure  (tons/ft  ) 


Massive  bedrock: 

Granite,  diorite  gabbro,  basalt,  gneiss 

Quartzite,  well  cemented 

conglomerate 

Foliated  bedrock:  slate,  schist 

Sedimentary  bedrock;  cementation 
shale,  siltstone,  sandstone,  limestone, 
dolomite,  conglomerate 
Weaklv  cemented  sedimentary 
bedrock:  compaction  shale  or  other 
similar  rock  tn  sound  condition 
Weathered  bedrock:  any  of  the  above 
except  shale. 

Slightly  cemented  sand  and/or  gravel, 

glacial  till  ("basal  or  lodgement). 

hardpan 

Gravel,  widely  graded  sand  and 

gravel:  and  granular  ablation  till 


Sands  and  non-plastic  silty  sands  with 
little  or  no  gravel  (except  for  Class  9 
materials) 


Fine  sand,  silty  fine  sand,  and  non- 


3       Hard,  sound  rock,  minor 

jointing 
3       Hard,  sound  rock  moderate 

jointing 
3        Medium  hard  rock,  mmor 

jointing 
3.4     Soft  rock,  moderate  jointing 


11 


plastic  inorganic  silt 


Inorganic  sandy  or  silty  clay,  clayey 
sand,  clayey  silt,  clay,  or  varved  clay 
low  to  high  plasticity 


Organic  soils  peat,  organic  silt, 
organic  clav 


3,5 

Very  soft  rock,  weathered 
and/or  major  jointing  and 
fracturing 

8 

7,8 

Verv  dense 

10 

6,  7,  8 

Very  dense 
Dense 

Medium  dense 
Loose 
Very  loose 

8 
6 

4 

Note  1 1 

6.7,8. 

Dense 

4 

9 

Medium  dense 

Loose 
Verv  ioose 

Note  1 1 

6,7,9 

Dense 

3 

Medium  dense 

2 

Loose 

1 

Verv  loose 

Note  1 1 

5.6, 
10 

Hard 
Stiff 

-i 

Medium 
Soft 

1 
Note  1 1 

11 

Note  1 1 

Notes  for  Table  1804.3: 

1.  Refer  to  commentary  in  Appendix  D  regarding  typical  index  test  values  that  may  be  helpful  as  guides  for  evaluation 
of  consistency  in  place. 

2.  Refer  to  780  CMR  1807.0  for  determination  of  design  loads  and  for  special  cases. 

3.  The  allowable  bearing  pressures  may  be  increased  by  an  amount  equal  to  10%  for  each  foot  of  depth  below  the 
surface  of  sound  rock;  however,  the  increase  shall  not  exceed  two  times  the  value  given  in  the  table. 

4.  For  limestone  and  dolomite,  the  bearing  pressures  given  are  acceptable  only  if  an  exploration  program  performed 
under  the  direction  of  a  registered  design  professional  demonstrates  that  there  are  no  cavities  within  the  zone  of 
influence  of  the  foundations.  If  cavities  exist,  a  special  study  of  the  foundation  conditions  is  required. 

5.  Weathered  shale  and/or  weathered  compaction  shale  shall  be  included  in  Material  Class  10  Other  highly 
weathered  rocks  and/or  residual  soils  shall  be  treated  as  soil  under  the  appropriate  description  tn  Material  Classes 
6  to  10.  Where  the  transition  between  residual  soil  and  bedrock  is  gradual,  a  registered  design  professional  shall 
make  a  judgment  as  to  the  appropriate  bearing  pressure. 

6.  Settlement  analyses  in  accordance  with  780  CMR  1805.5  should  be  performed  if  the  ability  of  a  given  structure 
to  tolerate  settlements  is  in  question,  particularly  for.  but  not  limited  to.  soft  or  very  soft  clays  and  silts  and  loose 
granular  materials. 

7.  Allowable  bearing  pressures  may  be  increased  by  an  amount  equal  to  5%  for  each  foot  of  depth  of  the  bearing  area 
below  the  rrunimum  required  in  780  CMR  1806.0.  however,  the  bearing  pressure  shall  not  exceed  two  times  the 
value  given  in  the  table.  For  foundation  bearing  areas  having  a  least  lateral  dimension  smaller  than  three  feet,  the 
allowable  bearing  pressure  shall  be  Vb  of  the  tabulated  value  tunes  the  least  dimension  in  feet. 

8.  Refer  to  780  CMR1 804.3  when  these  materials  are  used  as  compacted  fills. 

9.  These  materials  are  subject  to  the  provisions  in  780  CMR  1 805.3  (Liquefaction). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


311 


780  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

10    Alternatively,  the  allowable  bearing  pressure  may  be  taken  as  1.5  times  the  peak  unconfined  compressive  strength 

of  undisturbed  samples  for  square  and  round  footings  or  1.25  times  that  strength  for  footings  with  length  to  width 

ratio  of  4  or  greater.  For  intermediate  cases,  interpolation  may  be  used. 
11.  A  registered  design  professional  shall  be  engaged  to  provide  recommendations  for  these  special  cases.    Direct 

bearing  on  organic  soils  is  not  permitted.   Organic  soils  are  allowed  under  foundations  for  those  cases  defined  in 

780  CMR  1804.4.2,  Preloaded  materials. 


1804.4  Lightweight  structures:  One-story 
structures  without  masonry  walls  and  not  exceeding 
800  square  feet  in  area  may  be  founded  on  a  layer  of 
satisfactory  bearing  material  not  less  than  three  feet 
(1  m)  thick,  which  is  underlain  by  highly 
compressible  material,  provided  that  the  stresses 
induced  in  the  unsatisfactory  material  by  the  live  and 
dead  loads  of  the  structure,  and  the  weight  of  any 
new  fill  within  or  adjacent  to  the  building  area,  will 
not  exceed  250  pounds  per  square  foot  (250  psf). 

1804.4.1  Bearing  capacity  for  lightweight 
structures:  Lightweight  structures  and  accessory 
structures,  such  as  garages  and  sheds,  may  be 
founded  on  normally  unacceptable  bearing  strata, 
providing  such  material  is  determined  by  a 
registered  design  professional  as  being 
satisfactory  for  the  intended  use. 

1804.4.2  Preloaded  materials:  The  code  official 
may  allow  the  use  of  certain  otherwise 
unsatisfactory  natural  soils  and  uncompacted  fills 
for  support  of  one-story  structures  after  these 
materials  have  been  preloaded  to  effective  stresses 
not  less  than  150%  of  the  effective  stresses  which 
will  be  induced  by  the  live  and  dead  loads  of  the 
structure. 

1804.4.3  Load  test:  The  code  official  may 
require  the  loading  and  unloading  of  a  sufficiently 
large  area,  conducted  under  the  direction  of  a 
registered  design  professional  approved  by  the 
code  official,  who  shall  submit  a  report  containing 
a  program  which  will  allow  sufficient  time  for 
adequate  consolidation  of  the  material  based  on 
an  analysis  of  the  preloaded  material  and  of  the 
probable  settlements  of  the  structure. 

780  CMR  1805.0  ALLOWABLE 
FOUNDATION  LOADS 

1805.1  General:  The  maximum  allowable  pressures 
on  foundation  materials  shall  be  in  accordance  with 
780  CMR  1804.0  and  as  modified  herein. 

1805.2  Soil  Capacity:  For  the  load  combinations, 
including  seismic  as  specified  in  780  CMR  1616.0, 
the  soil  loadbearing  strength  shall  be  sufficient  to 
resist  loads  at  acceptable  strain,  considering  both  the 
duration  of  the  loading  and  the  dynamic  properties 
of  the  soil.  For  foundations  supported  on  or  in 
Material  Classes  1  through  6,  as  defined  in  Table 
1804.3,  or  medium  dense  to  very  dense  soils  of 
Material  Classes  7  through  9,  or  stiff  to  hard  soil  of 
Materials  Class  10,  the  allowable  bearing  pressure  or 
pile  or  pier  capacity  may  be  increased  by  up  to  33% 


for  load  combinations  that  include  wind  or  seismic 
loading. 

1805.3    Liquefaction: 

1.  The  earthquake  liquefaction  potential  of 
saturated  clean  medium  to  fine  sands  shall  be 
evaluated  on  the  basis  of  Figure  1805.3  for  cases 
where  lateral  sliding  cannot  occur. 

Figure  1805.3 
LIQUEFACTION  SUSCEPTABILITY 

O  1©  20  SO 


1    DEPTH 
TO 
GROUND- 
WATER 
(FEET) 


STANDARD  PENETRATION 
RESISTANCE,  N  (BLOWS/FT.) 

If  the  standard  resistances,  N,  in  all  strata  of 
medium  to  fine  sand  lie  above  the  applicable 
curve  in  Figure  1805.3  the  sands  at  the  site  shall 
not  be  considered  subject  to  liquefaction. 
Liquefaction  below  a  depth  of  60  feet  (18  m)  from 
final  grade  need  not  be  considered  for  level 
ground.  For  pressure-injected  footings,  the  ten- 
foot  (3-m)  thickness  of  soil  immediately  below 
the  bottom  of  the  driven  shaft  shall  not  be 
considered  subject  to  liquefaction. 
2  Compacted  granular  fills  shall  not  be 
considered  subject  to  liquefaction  provided  they 
are  systematically  compacted  to  at  least  93%  of 
maximum  dry  density  as  determined  in 
accordance  with  ASTM  Standard  Method  D1557, 
listed  in  Appendix  A  or  to  a  relative  density  of  at 
least  60%  in  the  case  of  granular  soils  having  less 
than  10%  by  weight  material  passing  the  No.  200 
U.S.  Sieve. 

3.  For  sites  not  meeting  the  above  criteria, 
studies  by  a  registered  design  professional  shall 
be  made  to  determine  that  the  structural  loads  can 
be  safely  supported.  Such  studies  might  include 
the  following: 

•  Investigations  to  establish  that  the  soils  at 
the  site  are  not  subject  to  liquefaction  during 
the  design  earthquake  as  specified  in 
780  CMR  1612.0. 


312 


780  CMR  -  Sixth  Edition     corrected-  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


•  Design  of  foundations  that  will  not  fail 
either  by  loss  of  bearing  capacity  or 
excessive  settlement  if  liquefaction  occurs. 

•  Replacement  or  densification  of 
liquefaction-susceptible  soils  such  that 
liquefaction  will  not  occur. 

4.  For  sites  underlain  by  saturated  sands  where 
lateral  sliding  (slope  instability)  may  occur, 
studies  by  a  registered  design  professional  shall 
be  made  to  establish  the  safety  against  sliding 
during  an  earthquake  with  a  peak  acceleration  of 
0  12  g  and  a  frequency  content  similar  to  that 
implied  by  the  modal  seismic  design  coefficient 
set  forth  in  780  CMR  1612.5 

5.  For  sites  underlain  by  saturated  silty  sands  and 
inorganic  non-plastic  silts,  studies  shall  be  made 
by  a  registered  design  professional  to  determine 
the  susceptibility  to  liquefaction  of  these  soils. 

1805.4  Vertical  pressure  The  computed  vertical 
pressure  at  any  level  beneath  a  foundation  shall  not 
exceed  the  allowable  bearing  pressure  for  the 
material  at  that  level.  Computation  of  the  vertical 
pressure  in  the  bearing  materials  at  any  depth  below 
a  foundation  shall  be  made  on  the  assumption  that 
the  load  is  spread  uniformly  at  an  angle  of  30°  with 
the  vertical;  but  the  area  considered  as  supporting 
the  load  shall  not  extend  beyond  the  intersection  of 
30°  planes  of  adjacent  foundations 

1805.5  Settlement  analysis:  Whenever  a  structure 
is  to  be  supported  by  medium  or  soft  clay  (materials 
of  Class  10)  or  other  materials  which  may  be  subject 
to  settlement  or  consolidation,  the  settlements  of  the 
structure  and  of  neighboring  structures  due  to 
consolidation  shall  be  given  careful  consideration, 
particularly  if  the  subsurface  material  or  the  loading 
is  subject  to  significant  variation  The  code  official 
may  require  a  settlement  analysis  to  be  made  by  a 
registered  design  professional  when  the  live  and 
dead  loads  of  the  structure,  as  specified  in  this 
article,  minus  the  weight  of  the  excavated  material, 
induce  a  maximum  stress  greater  than  300  pounds 
per  square  foot  at  mid-depth  of  the  underlying  soft 
soil  layer. 

Settlement  analysis  will  be  based  on  a 
computation  of  the  new  increase  in  stress  that  will  be 
induced  by  the  structure  and  realistically  appraised 
live  loads,  after  deducting  the  weight  of  excavated 
material  under  which  the  soil  was  fully  consolidated. 
The  effects  of  fill  loads  within  the  building  area  or 
fill  and  other  loads  adjacent  to  the  building  shall  be 
included  in  the  settlement  analysis.  The  appraisal  of 
the  live  loads  may  be  based  on  surveys  of  actual  live 
loads  of  existing  buildings  with  similar  occupancy. 
The  soil  compressibility  shall  be  determined  by  a 
registered  design  professional. 

1805.6  Disturbance    of    bearing    materials: 

Whenever  the  bearing  materials  are  disturbed  from 
any  cause,  for  example,  by  the  inward  or  upward 


flow  of  water  and/or  by  construction  activities,  the 
extent  of  the  disturbance  shall  be  evaluated  by  a 
registered  design  professional  and  appropriate 
remedial  measures  satisfactory  to  the  code  official 
shall  be  taken. 

1805.7  Rock  foundations:  Where  subsurface 
explorations  at  the  project  site  indicate  variations  or 
doubtful  characteristics  in  the  structure  of  the  rock 
upon  which  it  is  proposed  to  construct  foundations, 
a  sufficient  number  of  borings  shall  be  made  to  a 
depth  of  not  less  than  ten  feet  below  the  level  of  the 
foundations  to  provide  assurance  of  the  soundness  of 
the  foundation  stratum  and  its  bearing  capacity. 
Refer  to  Table  1804.3  for  allowable  bearing 
pressures  and  special  conditions. 

The  maximum  presumptive  loadbearing  capacity 
of  Class  1  or  Class  2  rock  may  be  increased  where 
the  surface  is  leveled  or  benched,  provided  that  such 
increased  safe  capacity  is  determined  by  load  tests 
on  an  area  of  not  less  than  one  square  foot  (0.093 
nr)  in  accordance  with  the  provisions  of  780  CMR 
1803.0. 

780  CMR  1806.0  DEPTH  OF  FOOTINGS 

1806.1  Frost  protection:  All  permanent  supports  of 
buildings  and  structures  larger  than  1 00  square  feet 
(9.3  m2)  in  area  or  ten  feet  (3  m)  in  height  shall 
extend  to  a  minimum  of  four  feet  (1.2  m)  below- 
finished  grade  except  when  erected  upon  sound 
bedrock  or  when  protected  from  frost,  or  when  the 
foundation  grade  is  established  by  a  registered 
design  professional  and  as  approved  by  the  code 
official.  Spread  footings  of  adequate  size  shall  be 
provided  where  necessary  to  distribute  properly  the 
load  within  the  allowable  load  bearing  value  of  the 
soil.  Footings  shall  not  bear  on  frozen  soils. 

1806.2  Isolated  footings  Footings  on  granular  soil 
of  Classes  7,  8  and  9  of  Table  1804.3  and  compacted 
fill  shall  be  so  located  that  the  line  drawn  between 
the  lower  edges  of  adjoining  footings  shall  not  have 
a  steeper  slope  than  30°  (0.52  rad)  with  the 
horizontal  unless  the  material  supporting  the  higher 
footing  is  braced  or  retained  or  otherwise  laterally 
supported  in  an  approved  manner  or  a  greater  slope 
has  been  properly  established  by  a  registered  design 
professional. 

1806.3  Depth  of  spread  foundations:  The  bottom 
surface  of  any  footing  resting  on  material  of 
Classes  5  through  10  of  Table  1804.3,  shall  be  at 
least  1 8  inches  (460  mm)  below  the  lowest  ground 
surface  or  the  top  surface  of  a  floor  slab  bearing 
directly  on  the  soil  immediately  adjacent  to  the 
footing. 

780  CMR  1807.0  FOOTING  DESIGN 

1807.1  Design  loads:  The  loads  to  be  used  in 
computing  the  pressure  upon  bearing  materials 
directly  underlying  foundations  shall  be  the  live  and 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


J 13 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


dead  loads  of  the  structure,  as  specified  in  780  CMR 
1616  0  including  the  weight  of  the  foundations  and 
of  any  immediately  overlying  material,  but 
deducting  from  the  resulting  pressure  per  square  foot 
the  total  weight  of  a  one-foot-square  column  of  soil, 
including  the  water  in  its  voids,  which  extends  from 
the  lowest  immediately  adjacent  surface  of  the  soil 
to  the  bottom  of  the  footing,  pier  or  mat 
Foundations  shall  be  constructed  so  as  to  resist  the 
maximum  probable  hydrostatic  pressures. 

1807.2  Vibratory  loads:  Where  machinery 
operations  or  other  vibrations  are  transmitted 
through  the  foundation,  consideration  shall  be  given 
in  the  footing  design  to  prevent  detrimental 
disturbances  of  the  soil. 

1807.3  Varying  unit  pressures:  Footings  shall  be 
so  designed  that  the  unit  soil  pressure  under  the  dead 
load  shall  be  as  uniform  as  possible  under  all  parts 
of  the  building  structure.  When  necessary  for 
stability  in  the  structure  due  to  settlement  or  varying 
soil  conditions,  approved  variations  are  permitted  in 
the  unit  pressure  under  different  footings. 

1807.4  Eccentric  loads:  Eccentricity  of  loadings  in 
foundations  shall  be  fully  investigated,  and  the 
maximum  pressure  on  the  basis  of  straight-line 
distribution  shall  not  exceed  the  allowable  bearing 
pressures 

1807.5  Protection  of  footings:  Trenching  installed 
parallel  to  footings  shall  not  extend  below  the  line  of 
a  45°  (0.79  rad)  angle  downward  from  the 
loadbearing  plane  of  the  footing. 

780  CMR  1808.0  TIMBER  FOOTINGS 
AND  WOOD  FOUNDATIONS 

1808.1  Timber  footings:  Timber  footings  are 
permitted  for  buildings  of  Type  5  construction  and 
as  otherwise  approved.  Such  footings  shall  be 
treated  in  accordance  with  AWPA  C2  or  C3  listed  in 
Appendix  A.  Treated  timbers  are  not  required  where 
placed  entirely  below  permanent  water  level,  or 
where  used  as  capping  for  wood  piles  which  project 
above  the  water  level  over  submerged  or  marsh 
lands.  The  compressive  stresses  perpendicular  to 
grain  in  untreated  timber  footings  supported  upon 
piles  shall  not  exceed  70%  of  the  allowable  stresses 
for  the  species  and  grade  of  timber  as  specified  in 
NFoPA  NDS  listed  in  Appendix  A 

1808.2  Pole  buildings:  Pole-type  buildings  shall  be 
designed  and  erected  in  accordance  with  AWPI  Pole 
Building  Design  listed  in  Appendix  A.  The  poles 
shall  be  treated  in  accordance  with  AWPA  C2  or  C4 
listed  in  Appendix  A. 

1808.3  Wood  foundations:  Wood  foundation 
systems  shall  be  designed  and  installed  in 
accordance  with  NFoPA  TR7  listed  in  Appendix  A 


All  lumber  and  plywood  shall  be  treated  in 
accordance  with  AWPA  C22  listed  in  Appendix  A 
and  shall  be  identified  in  accordance  with  780  CMR 
2311.3.1. 

^80  CMR  1809.0  STEEL  GRHXAGES 
1809.1  General:  All  steel  grillage  beams  shall  be 
separated  with  approved  steel  spacers  and  shall  be 
entirely  encased  in  at  least  three  inches  (76  mm)  of 
concrete,  and  the  spaces  between  the  beams  shall  be 
completely  filled  with  concrete  or  cement  grout 
Where  used  on  yielding  soils,  steel  grillages  shall 
rest  on  approved  concrete  beds  not  less  than  six 
inches  (152  mm)  thick 


780  CMR  1810.0  CONCRETE  FOOTINGS 

1810.1  Concrete  strength:  Concrete  in  footings 
shall  have  a  specified  compressive  strength  of  not 
less  than  2.500  psi  (1.76  kg/mm2)  at  28  days. 

1810.2  Design:  Concrete  footings  shall  comply  with 
780  CMR  19  and  ACI  318  or  ACI  318.1  listed  in 
Appendix  A 

1810.2.1  Footing  seismic  ties:  Individual  spread 
footings,  located  on  soil  profile  type  S2,  S3  or  S4, 
in  accordance  with  780  CMR  1612.4.2,  and 
supporting  buildings  assigned  to  Seismic 
Performance  Category  D,  in  accordance  with 
780  CMR  1612.2.7.  shall  be  interconnected  by 
ties.  All  ties  shall  be  capable  of  resisting,  in 
tension  or  compression,  a  force  equal  to  1 0%  of 
the  larger  column  dead  plus  live  load.  Individual 
tie  beams  are  not  required  when  it  is  demonstrated 
that  equivalent  restraint  will  be  provided  by 
structural  members  within  slabs  on  grade  or 
reinforced  concrete  slabs  on  grade  or  confinement 
be  competent  rock,  hard  cohesive  soils,  very 
dense  granular  soils  or  other  approved  means. 

1810.3  Thickness:  The  thickness  of  concrete 
footings  shall  comply  with  780  CMR  1810.3.1  and 
1810.3.2. 

1810.3.1  Plain  concrete:  In  plain  concrete 
footings,  the  edge  thickness  shall  not  be  less  than 
eight  inches  (203  mm)  for  footings  on  soil;  except 
that  for  occupancies  of  Use  Group  R-3  and 
buildings  less  than  two  stories  in  height  of  Type  5 
construction,  the  required  edge  thickness  shall  be 
six  inches  (152  mm)  provided  that  the  footing 
does  not  extend  beyond  four  inches  (102  mm)  on 
either  side  of  the  supported  wall. 

1810.3.2  Reinforced  concrete:  In  reinforced 
concrete  footings,  the  thickness  above  the  bottom 
reinforcement  shall  not  be  less  than  six  inches 
(152  mm)  for  footings  on  soil.  The  clear  cover  on 
reinforcement  where  the  concrete  is  cast  against 
the  earth  shall  not  be  less  than  three  inches 
(76  mm)    Where  concrete  is  exposed  to  soil  after 


314 


780  CMR  -  Sixth  Edition     corrected-  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


it  has  been  cast,  the  clear  cover  shall  not  be  less 
than  1/4  inches  (38  mm)  for  reinforcement  of 
No.  5  bars  or  s/s-inch  (16  mm)  diameter  wire  or 
smaller,  nor  less  than  two  inches  (51  mm)  for 
larger  reinforcement. 

1810.4  Deposition:  Concrete  footings  shall  not  be 
placed  through  water  unless  otherwise  approved. 
Where  placed  under  or  in  the  presence  of  water,  the 
concrete  shall  be  deposited  by  approved  means  to 
insure  minimum  segregation  of  the  mix  and 
negligible  turbulence  of  the  water. 

1810.5  Protection  of  concrete:  Concrete  footings 
shall  be  protected  from  freezing  during  depositing 
and  for  a  period  of  not  less  than  five  days  thereafter. 
Water  shall  not  be  allowed  to  flow  through  the 
deposited  concrete. 

1810.6  Forming  of  concrete  Concrete  footings 
shall  not  be  cast  against  the  earth  where,  in  the 
opinion  of  the  code  official,  soil  conditions  warrant 
forming.  Where  forming  is  required,  forming  shall 
be  in  accordance  with  Chapter  6  of  ACI  318  listed  in 
Appendix  A 

780  CMR  1811.0  MASONRY-UNIT 
FOOTINGS 

1811.1  Dimensions:  Masonry-unit  footings  shall  be 
laid  in  Type  M  or  S  mortar  complying  with 
780  CMR  2105.7,  and  the  depth  shall  not  be  less 
than  twice  the  projection  beyond  the  wall,  pier  or 
column.  The  width  shall  not  be  less  than  eight 
inches  (203  mm)  wider  than  the  wall  supported 
thereon. 

1811.2  Offsets:  The  maximum  offset  of  each  course 
in  brick  foundation  walls  stepped  up  from  the 
footings  shall  be  1  'A  inches  (3"8  mm),  if  laid  in  single 
courses,  and  three  inches  (76  mm),  if  laid  in  double 
courses. 

780  CMR  1812.0  FOUNDATION  WALLS 

1812.1  Design:  Foundation  walls  shall  be  designed 
to  resist  frost  action  and  to  support  safely  all  vertical 
and  lateral  loads  as  provided  for  in  780  CMR  16. 
The  maximum  stresses  caused  by  combined  loads 
shall  be  within  the  values  specified  for  the  materials 
used  in  the  construction.  Unless  properly  reinforced, 
tensile  stresses  shall  not  exceed  those  permitted  in 
plain  masonry. 

1812.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  1812  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Foundation  wall:  A  wall  below  the  floor  nearest 
grade  which  serves  as  a  support  for  a  wall,  pier, 
column  or  other  structural  part  of  a  building. 


Retaining  wall:  A  wall  designed  to  resist  the  lateral 
displacement  of  soil  or  other  material. 

1812.3  Minimum  thickness  The  thickness  of 
foundation  walls  shall  not  be  less  than  the  thickness 
of  the  wall  supported,  and  the  minimum  thickness 
shall  be  limited  for  the  various  materials  of 
construction  as  herein  specified.  Eight-inch 
foundation  walls  shall  be  permitted  under  brick- 
veneered  frame  and  under  ten-inch  cavity  walls 
where  the  total  height  of  the  wall  supported, 
including  gables,  is  not  more  than  20  feet  (6  m). 

1812.3.1  Reinforced  concrete  Reinforced 
concrete  exterior  foundations  and  exterior  and 
interior  basement  walls  which  retain  or  support 
the  lateral  pressure  of  earth  or  water  shall  not  be 
less  than  71  .■;  inches  (191  mm)  thick. 

1812.3.2  Hollow  and  solid  masonry  and  plain 
concrete  The  thickness  of  masonry  foundation 
walls  shall  not  be  less  than  shown  in  Table 
1812.3.2  for  the  type  of  foundation  used  Where 
the  height  of  the  unbalanced  fill  (height  of 
finished  ground  level  above  the  basement  floor  or 
inside  ground  level)  exceeds  eight  feet  (2  4  m)  or 
where  the  equivalent  fluid  weight  of  the 
unbalanced  fill  exceeds  30  pounds  per  cubic  foot 
l  pcf)  ( 1 46  kg/m"1)  or  where  the  height  of  the 
foundation  wall  between  lateral  supports  exceeds 
eight  feet  (2.4  m),  the  foundation  wall  thickness 
shall  be  determined  by  structural  analysis  in 
accordance  with  ACI  530/ASCE  5/  TMS  402  or 
ACI  318  1  listed  in  Appendix  A 

Table  1812.3.2 
THICKNESS  OF  FOUNDATION  WALLS 

Maximum  depth  of 

unbalanced  fill 

(feet) 


Foundation  w 
consirucuc 


Thickness 
i  inches ) 


Masonn  of  hollow  units 
Ungrouted 

Masonry  of  hollow  units, 
reinforced  vertically  with 
#4  bars  and  grout  at  24" 
o.c.  Bars  located  not  less 
than  4'/i"  from  pressure 
sideofwali 

Masonn."  of  solid  units 


Plain  concrete  or 
masonn  of  hollow  or 
sobd  units,  fully  grouted 


Note  a.  Maximum  depths  of  unbalanced  fill  shall  be 
permitted  to  be  increased  with  the  approval  of  the  code 
official  where  soil  conditions  or  local  experience  warrant 
such  increase. 

Note  b.  The  actual  thickness  shall  not  be  more  than 
'/:  mch  less  than  the  required  nominal  thickness  specified 
in  the  table. 

Note  c.  Other  bar  sizes  and  spacings  shall  be 
permitted  as  determined  by  structural  analysis  as  required 
m  ACI  530/ASCE  5/TMS  402  listed  m  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


315 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Noted    1  inch  =  25.4  mm;  1  foot  =  304.8  ram. 

1812.3.3  Hollow-unit  walls:  Foundation  walls  of 
approved  hollow  masonry  units  shall  be  provided 
with  not  less  than  four  inches  (102  mm)  of  solid 
masonry  at  girder  supports,  or  shall  be 
strengthened  with  buttresses. 

1812.3.4  Rubble  stone:  Foundation  walls  of 
rough  or  random  rubble  stone  shall  not  be  less 
than  16  inches  (406  mm)  thick. 

1812.3.5  Bonding:  All  foundation  walls  shall  be 
bonded  as  required  for  superstructure  walls  in 
780  CMR  21 10.0. 

1812.4  Increased  thickness  with  depth:  Where  any 
foundation  wall,  other  than  a  wall  that  is  designed  as 
a  retaining  wall,  extends  more  than  12  feet  (3.7  m) 
below  the  top  of  the  first  floor  beams,  the  thickness 
of  the  wall  shall  be  increased  four  inches  (102  mm) 
for  each  additional  12  feet  (3.7  m)  or  fraction  thereof 
in  depth. 

1812.5  Corbels  on  eight-inch  walls:  Where  an 
eight-inch  (203  mm)  wall  is  corbelled,  the  top  corbel 
shall  be  a  full  course  of  headers  at  least  six  inches 
(152  mm)  in  length,  extending  not  higher  than  the 
bottom  of  the  floor  framing.  The  maximum 
projection  of  one  unit  shall  exceed  neither  Vi  of  the 
depth  of  the  unit  nor  Vb  of  its  width  at  right  angles  to 
the  face  which  is  offset. 

1812.6  Lateral  stability:  Foundation  walls  of 
buildings  and  structures  which  serve  as  retaining 
walls  shall  conform  to  the  applicable  requirements 
of  780  CMR  1825.0,  and  shall  be  strengthened  with 
buttresses  or  additional  wall  thickness  to  resist 
lateral  soil  and  hydrostatic  pressure  where  subjected 
thereto,  and  to  resist  seismic  loads  as  required  by 
780  CMR  1612.4  9. 

780  CMR  1813.0  WATERPROOFING 
AND  DAMPPROOFING 

1813.1  Where  required:  Walls  or  portions  thereof 
that  retain  earth  and  enclose  interior  spaces  and 
floors  below  grade  shall  be  waterproofed  and 
dampproofed  in  accordance  with  780  CMR  1813.0, 
with  the  exception  of  those  spaces  containing  use 
groups  other  than  residential  and  institutional  where 
such  omission  is  not  detrimental  to  the  building  or 
occupancy. 

1813.1.1  Story  above  grade:  Where  a  basement 
is  considered  a  story  above  grade  and  the  finished 
ground  level  adjacent  to  the  basement  wall  is 
below  the  basement  floor  elevation  for  25%  or 
more  of  the  perimeter,  the  floor  and  walls  shall  be 
dampproofed  in  accordance  with  780  CMR 
1813.3  and  a  foundation  drain  shall  be  installed  in 
accordance  with  780  CMR  1813.5.2.  The 
foundation  drain  shall  be  installed  around  the 
portion  of  the  perimeter  where  the  basement  floor 


is  below  ground  level.  The  provisions  of 
780  CMR  1813.2,  1813.4  and  1813.5.1  shall  not 
apply  in  this  case. 

1813.1.2  Underfloor  space  The  finished  ground 
level  of  an  underfloor  space  such  as  a  crawl  space 
shall  not  be  located  below  the  bottom  of  the 
footings  Where  there  is  evidence  that  the  ground 
water  table  rises  to  within  six  inches  (152  mm)  of 
the  ground  level  at  the  outside  building  perimeter 
or  where  there  is  evidence  that  the  surface  water 
does  not  readily  drain  from  the  building  site,  the 
ground  level  of  the  underfloor  space  shall  be  as 
high  as  the  outside  finished  ground  level,  unless 
an  approved  drainage  system  is  provided.  The 
provisions  of  780  CMR  1813.2,1813.3.  1813  4, 
1813  5  and  1813.6  shall  not  apply  in  this  case. 

1813.2  Ground  water  table  investigation:  The 

owner  or  applicant  shall  perform  a  subsurface  soil 
investigation  in  accordance  with  780  CMR  1802.0  to 
determine  the  possibility  of  the  ground  water  table 
rising  above  the  proposed  elevation  of  the  floor  or 
floors  below  grade 

Exception:  A  subsurface  soil  investigation  shall 

not  be  required  where: 

i     Waterproofing  is  to  be  provided; 

2  Satisfactory  data  from  adjacent  areas  are 
available  which  demonstrate  that  ground  water 
has  not  been  a  problem;  or 

3  Floodproofing  is  to  be  provided  in  accordance 
with  780  CMR  3107.0. 

1813.2.1  Ground  water  control:  Where  the 
ground  water  table  is  lowered  and  maintained  at 
an  elevation  not  less  than  six  inches  (152  mm) 
below  the  bottom  of  the  lowest  floor,  the  floor  and 
walls  shall  be  dampproofed  in  accordance  with 
780  CMR  1813.3.  The  design  of  the  system  to 
lower  the  ground  water  table  shall  be  based  upon 
accepted  principles  of  engineering  which  shall 
consider,  but  not  necessarily  be  limited  to: 
permeability  of  the  soil;  rate  at  which  water  enters 
the  drainage  system;  rated  capacity  of  pumps; 
head  against  which  pumps  are  to  pump;  and  the 
rated  capacity  of  the  disposal  area  of  the  system. 
The  design  shall  also  take  into  account  any 
adverse  impacts  on  utilities,  structures  or  other 
facilities  in  the  vicinity  which  would  result  from 
the  lowering  of  groundwater  levels. 

1813.3  Dampproofing  required:  Where  hydrostatic 
pressure  will  not  occur  as  determined  by  780  CMR 
1813.2,  floors  and  walls  for  other  than  wood 
foundation  systems  shall  be  dampproofed  in 
accordance  with  780  CMR  1813.0  Wood 
foundation  systems  shall  be  constructed  in 
accordance  with  NFoPA  TR7  listed  in  Appendix  A. 

1813.3.1  Floor  applications:  The  required 
dampproofing  materials  shall  be  installed  between 
the    floor   and    the   base    course   required    by 


316 


780  CMR  -  Sixth  Edition     corrected-  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUTLDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


780  CMR  1813.5.1,  except  where  a  separate  floor 

is  provided  above  a  concrete  slab 

1813.3.1.1  Floor  dampproofing  materials: 
Where  installed  beneath  the  slab, 
dampproofing  shall  consist  of  not  less  than 
6-mil  (.006  inch;  152  fxm)  polyethylene  with 
joints  lapped  not  less  than  six  inches 
(152  mm),  or  other  approved  methods  or 
materials.  Where  permitted  to  be  installed  on 
top  of  the  slab,  dampproofing  shall  consist  of 
mopped-on  bitumen,  not  less  than  4-mil 
(.004  inch;  102  fj.m)  polyethylene,  or  other 
approved  methods  or  materials.  Joints  in  the 
membrane  shall  be  lapped  and  sealed  in 
accordance  with  the  manufacturer's  installation 
instructions. 

1813.3.2  Walls:  Dampproofing  materials  shall  be 
installed  on  the  exterior  surface  of  walls  and  shall 
extend  from  the  top  of  the  footing  to  above 
ground  level 

1813.3.2.1  Surface  preparation  of  walls: 
Prior  to  application  of  dampproofing  materials 
on  concrete  walls,  all  holes  and  recesses 
resulting  from  the  removal  of  form  ties  shall  be 
sealed  with  a  bituminous  material  or  other 
approved  methods  or  materials.  Unit  masonry 
walls  shall  be  parged  on  the  exterior  surface 
below  ground  level  with  not  less  than  %  inch 
(10  mm)  of  portland  cement  mortar.  The 
parging  shall  be  coved  at  the  footing. 

Exception:  Parging  of  unit  masonry  walls  is 
not  required  where  a  material  is  approved 
for  direct  application  to  the  masonry. 

1813.3.2.2  Wall  dampproofing  materials: 
Dampproofing  shall  consist  of  a  bituminous 
material,  three  pounds  per  square  yard  of 
acrylic  modified  cement,  Vs-inch  coat  of 
surface-bonding  mortar  complying  with  ASTM 
C887  listed  in  Appendix  A,  any  of  the 
materials  permitted  for  waterproofing  by 
780  CMR  1813.4.2.2,  or  other  approved 
methods  or  materials. 

1813.4  Waterproofing  required:  Where  the  ground 
water  investigation  required  by  780  CMR  1813.2 
indicates  that  a  hydrostatic  pressure  condition  exists, 
walls  and  floors  shall  be  waterproofed  in  accordance 
with  780  CMR  1813.4. 

1813.4.1      Floors:     Floors     required     to     be 

waterproofed  shall  be  of  concrete,  designed  and 
constructed  to  withstand  the  hydrostatic  pressures 
to  which  the  floors  will  be  subjected. 

1813.4.1.1   Floor  waterproofing  materials 

Waterproofing  shall  be  accomplished  by 
placing  a  membrane  of  rubberized  asphalt, 
butyl  rubber,  neoprene,  or  not  less  than  6-mil 
(.006  inch;  152  ^m)  polyvinyl  chloride  or 
polyethylene  with  joints  lapped  not  less  than 
six    inches    (152    mm)    or    other    approved 


materials  under  the  slab  Joints  in  the 
membrane  shall  be  lapped  and  sealed  in 
accordance  with  the  manufacturer's  installation 
instructions. 

1813.4.2  Walls:  Walls  required  to  be 
waterproofed  shall  be  of  concrete  or  masonry  and 
shall  be  designed  and  constructed  to  withstand  the 
hydrostatic  pressures  and  other  lateral  loads  to 
which  the  walls  will  be  subjected. 

1813.4.2.1  Surface  preparation  of  walls: 
Prior  to  the  application  of  waterproofing 
materials  on  concrete  or  masonry  walls,  the 
walls  shall  be  prepared  in  accordance  with 
780  CMR  1813.3.2.1. 

1813.4.2.2  Wall  waterproofing  materials: 
Waterproofing  shall  be  applied  from  the 
bottom  of  the  wall  to  not  less  than  1 2  inches 
(305  mm)  above  the  maximum  elevation  of  the 
ground  water  table.  The  remainder  of  the  wall 
shall  be  dampproofed  in  accordance  with 
780  CMR  1813.3.2.2.  Waterproofing  shall 
consist  of  two-ply  hot-mopped  felts,  not  less 
than  6-mil  (.006-inch;  152-/^m)  polyvinyl 
chloride,  40-mil  (040-inch;  1  mm)  polymer- 
modified  asphalt,  6-mil  (006-inch;  152-fj.m) 
polyethylene  or  other  approved  methods  or 
materials  capable  of  bridging  nonstructural 
cracks.  Joints  in  the  membrane  shall  be  lapped 
and  sealed  in  accordance  with  the 
manufacturer's  installation  instructions. 

1813.4.3  Joints  and  penetrations:  Joints  in  walls 
and  floors,  joints  between  the  walls  and  floor,  and 
penetrations  of  the  wall  and  floor  shall  be  made 
water  tight  utilizing  approved  methods  and 
materials. 

1813.5  Subsoil  drainage  system:  Where  a 
hydrostatic  pressure  condition  does  not  exist, 
dampproofing  shall  be  provided  and  a  base  shall  be 
installed  under  the  floor  and  a  drain  installed  around 
the  foundation  perimeter  A  subsoil  drainage  system 
designed  and  constructed  in  accordance  with 
780  CMR  1813.2.1  shall  be  deemed  adequate  for 
lowering  the  groundwater  table. 

1813.5.1  Floor  base:  Floors  of  basements,  except 
as  provided  for  in  780  CMR  1813.1.1,  shall  be 
placed  over  a  base  course  not  less  than  four  inches 
(102  mm)  in  thickness  that  consists  of  gravel  or 
crushed  stone  containing  not  more  than  10%  of 
material  that  passes  through  a  No.  4  sieve. 

Exception:  Where  a  site  is  located  in  well- 
drained  gravel  or  sand/gravel  mixture  soils,  a 
floor  base  is  not  required 

1813.5.2  Foundation  drain:  A  drain  shall  be 
placed  around  the  perimeter  of  a  foundation  that 
consists  of  gravel  or  crushed  stone  containing  not 
more  than  10%  material  that  passes  through  a 
No.  4  sieve.  The  drain  shall  extend  a  minimum  of 


2/^/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


317 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


12  inches  (102  mm)  beyond  the  outside  edge  of 
the  footing.  The  thickness  shall  be  such  that  the 
bottom  of  the  drain  is  not  higher  than  the  bottom 
of  the  base  under  the  floor,  and  that  the  top  of  the 
drain  is  not  less  than  six  inches  ( 1 52  mm)  above 
the  top  of  the  footing.  The  top  of  the  drain  shall 
be  covered  with  an  approved  filter  membrane 
material  Where  a  drain  tile  or  perforated  pipe  is 
used,  the  invert  of  the  pipe  or  tile  shall  not  be 
higher  than  the  top  of  the  lowest  floor  elevation. 
The  top  of  joints  shall  be  protected  with  an 
approved  filter  membrane  material.  The  pipe  or 
tile  shall  be  placed  on  not  less  than  two  inches 
(5 1  mm)  of  gravel  or  crushed  stone  complying 
with  780  CMR  1813.5.1,  and  shall  be  covered 
with  not  less  than  six  inches  (152  mm)  of  the 
same  material. 

1813.5.3  Drainage  disposal  The  floor  base  and 
foundation  perimeter  drain  shall  discharge  by 
gravity  or  mechanical  means  into  an  approved 
drainage  system  that  complies  with  the  plumbing 
code  (248  CMR)  listed  in  Appendix  A. 

Exception:  Where  a  site  is  located  in  well- 
drained  gravel  or  sand/gravel  mixture  soils,  a 
dedicated  drainage  system  is  not  required. 

1813.6  Placement  of  backfill:  The  excavation 
outside  the  foundation  shall  be  backfilled  with  soil 
that  is  free  of  organic  material,  construction  debris 
and  large  rocks.  The  backfill  shall  be  placed  in  lifts 
and  compacted  in  a  manner  which  does  not  damage 
the  foundation,  the  waterproofing  or  the 
dampproofing  material. 

1813.7  Site  grading:  The  ground  immediately 
adjacent  to  the  foundation  shall  be  sloped  away  from 
the  building  at  a  slope  of  not  less  than  one  unit 
vertical  in  12  units  horizontal  (1:  12)  for  a  minimum 
distance  of  eight  feet  (2.4  m)  measured  perpendicu- 
lar to  the  face  of  the  wall  or  an  approved  alternate 
method  of  diverting  water  away  from  the  foundation 
shall  be  used.  The  procedure  utilized  to  establish  the 
final  ground  level  adjacent  to  the  foundation  shall 
account  for  all  additional  settlement  of  the  backfill 

1813.8  Erosion  protection:  Where  water  impacts 
the  ground  from  the  edge  of  the  roof,  downspout, 
scupper  or  other  rainwater  collection  or  diversion 
device,  provisions  shall  be  made  to  prevent  soil 
erosion  and  direct  the  water  away  from  the 
foundation. 

780  CMR  1814.0  MAT,  RAFT  AND 
FLOAT  FOUNDATIONS 

1814.1  General:  Mat,  raft  and  float  foundations 
shall  only  be  used  where  the  applied  loads  of  the 
building  or  structure  are  so  arranged  as  to  result  in 
practically  uniformly  balanced  loading,  and  the  soil 
immediately  below  the  mat  is  of  uniform 
loadbearing  capacity.  The  characteristics  of  the  soil 


under  the  mat  or  raft  shall  be  considered  in  the 
analysis  of  loading  on  mats  and  other  continuous 
footings,  and  due  allowance  shall  be  made  for 
possible  concentrated  soil  pressures  under  heavily 
loaded  columns. 

1814.2  Settlement  Analysis  The  design  of  floating 
foundations  shall  include  a  settlement  analysis  in 
accordance  with  the  provisions  on  780  CMR 
1805.5. 

780  CMR  1815.0  PEER  FOUNDATIONS 

1815.1  General:  A  foundation  pier  is  here  defined 
as  a  structural  member  which  extends  to  satisfactory 
bearing  materials  to  develop  support  by  end  bearing 
and/or  friction  in  those  materials.  The  pier  shall  be 
constructed  by  advancing  a  hole  to  the  required 
depth  using  non-displacement  methods  and  filling 
the  hole  with  reinforced  or  plain  concrete  780  CMR 
1815  0  includes  foundation  types  referred  to  as 
drilled  piers,  drilled  shafts  and  caissons,  including 
both  circular  and  non-circular  foundation  elements. 
Uncased  piles  installed  by  the  hollow  stem  auger 
method  are  included  in  780  CMR  1820.2.  Augered 
uncased  piles. 

The  minimum  dimension  of  the  pier  shall  be  no 
less  than  12  inches  (305  mm).  The  base  may  be 
enlarged  by  belling  to  increase  the  bearing  area. 

1815.1.1  Special  types  of  piers:  Types  of  piers 
not  specifically  covered  by  the  provisions  of 
780  CMR  1815.0  may  be  permitted,  subject  to  the 
approval  of  the  code  official,  upon  the  submission 
of  acceptable  test  data  and  design  and 
construction  information  prepared  by  a  registered 
design  professional  stating  that  the  pier 
installation  is  adequate  to  fulfill  the  design 
requirements. 

1815.2  Seismic  design 

1815.2.1  Foundation  ties:  Pier  foundations  shall 
be  interconnected  by  ties  capable  of  resisting,  in 
tension  or  compression,  a  force  equal  to  1 0%  of 
the  larger  column  dead  plus  live  load  Individual 
tie  beams  are  not  required  when  it  is  demonstrated 
that  equivalent  restraint  will  be  provided  by 
structural  members  within  slabs  on  grade  or 
reinforced  concrete  slabs  on  grade  or  confinement 
by  competent  rock,  hard  cohesive  soils,  dense 
granular  soils  or  other  approved  means. 

1815.2.2  Seismic  reinforcement:  Cast  in  place 
concrete  piers  shall  have  minimum  reinforcement 
of  0.25%  of  the  minimum  pier  design  cross- 
sectional  area  for  buildings  assigned  to  Seismic 
Performance  Category  C,  and  a  minimum 
reinforcement  of  0.50%  for  buildings  assigned  to 
Seismic  Performance  Category  D  in  accordance 
with  780  CMR  1612.2.7.  The  minimum  pier 
design  cross-sectional  area  is  that  area  determined 
in  accordance  with  780  CMR  1815.6.  (The  actual 


318 


780  CMR  -  Sixth  Edition     corrected-  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  -AND  RETAINING  WALLS 


constructed  cross-sectional  area  may  be  larger.) 
The  reinforcing  shall  be  placed  in  the  top  V%  of  the 
pier  length  or  extend  ten  feet  (3  m)  from  the  top  of 
the  pier,  whichever  is  the  longer  length. 

For  Seismic  Performance  Category  C 
buildings,  the  pier  reinforcing  shall  be  a  minimum 
of  four  longitudinal  bars  with  closed  ties,  or 
equivalent  spirals,  having  a  minimum  diameter  of 
Vt  inch.  The  ties  shall  be  provided  at  a  maximum 
spacing  of  16  times  the  longitudinal  reinforcing 
bar  diameter  and  shall  enclose  an  area  of  concrete 
sufficient  to  confine  the  minimum  design  cross- 
sectional  concrete  area.  The  maximum  tie 
spacing  in  the  top  two  feet  (0.6  m)  of  the  pier 
length  shall  be  four  inches  (102  mm).  Tie 
detailing  shall  be  in  accordance  with  780  CMR 
1903.4 

For  Seismic  Performance  Category  D 
buildings,  the  pier  reinforcing  shall  be  a  minimum 
of  four  longitudinal  bars  with  closed  ties,  or 
equivalent  spirals,  having  a  minimum  diameter  of 
%  inch,  for  piers  with  a  diameter  of  20  inches 
(508  mm)  or  less;  and  a  minimum  tie  diameter  of 
Vz  inch,  for  piers  with  a  diameter  more  than  20 
inches  (508  mm).  The  ties  shall  be  provided  at  a 
maximum  spacing  of  eight  times  the  longitudinal 
reinforcing  bar  diameter.  The  maximum  tie 
spacing  in  the  top  four  feet  (1.2  m)  of  the  pier 
length  shall  be  three  inches  (76  mm).  Tie 
detailing  shall  be  in  accordance  with  780  CMR 
1903.5. 

Exception:  Pier  ties  are  not  required  where 
spiral  welded  metal  casing  is  used,  provided 
the  casing  has  thickness  of  not  less  than  0  068 
inch  (1.7  mm),  and  is  adequately  protected 
from  corrosion  due  to  soil,  changing  water 
levels,  or  other  subgrade  conditions  indicated 
by  the  site  soil  investigation 

1815.2.3  Pier  cap  connection:  All  piers  shall  be 
connected  to  the  pier  cap  so  that  pier 
reinforcement  is  embedded  in  the  cap  for  a 
distance  equal  to  the  development  length  as 
specified  in  ACI  318  listed  in  Appendix  A.  Field- 
placed  dowels  anchored  in  the  concrete  piers  are 
acceptable.  The  development  length  to  be 
provided  is  the  full  development  length  of  the 
reinforcement  for  compression  without  reduction 
in  length  for  excess  area. 

1815.2.4  Alternative  detailing:  Alternative 
measures  for  laterally  confining  concrete  and 
maintaining  toughness  and  ductile-like  behavior 
at  the  top  of  the  pier  shall  be  permitted  provided 
consideration  is  given  to  forcing  the  hinge  to 
occur  in  the  confined  region. 

1815.3  Installation:  In  unstable  soils,  a  temporary 
casing  or  slurry  shall  be  used  to  stabilize  the 
excavation.  When  a  slurry  is  used  to  stabilize  the 
excavation,  the  level  and  quality  of  the  slurry  shall 


be  monitored  and  controlled  to  maintain  stability  of 
the  shaft  and  the  bearing  surface. 

1815.4  Enlarged  bases:  Bell-shaped  bases  shall 
have  a  minimum  edge  thickness  of  four  inches 
(102  mm)  The  bell  roof  shall  slope  not  "less  than 
60°  with  the  horizontal  unless  the  base  is  designed 
in  accordance  with  ACI  336  listed  in  Appendix  A 
(hereinafter  ACI  336). 

1815.5  Placement  of  concrete  Concrete  may  be 
dropped  into  the  pier  from  the  ground  surface 
provided  nc  more  than  three  inches  (76  mm)  of 
water  remains  in  the  bottom  and  the  concrete  will 
free-fall  vertically  without  obstruction.  The  concrete 
shall  be  placed  in  a  rapid,  continuous  operation  and 
controlled  such  that  the  concrete  does  not  segregate 

1815.5.1  No  piers  shall  be  installed  near  a 
concreted  pier  until  the  concrete  has  set 
sufficiently  to  avoid  damage  to  the  concreted  pier 

1815.5.2  For  piers  without  enlarged  bases, 
concrete  or  grout  may  be  placed  through  still 
water  or  slurry.  A  properly  operated  tremie  or 
pumping  method  shall  be  used.  Samples  of  the 
slurry  shall  be  tested  to  determine  the  properties 
prior  to  placing  concrete  in  each  pier.  The 
quality,  consistency,  and  density  of  the  slurry 
shall  be  controlled  to  ensure  that  there  will  be 
free-flow  of  concrete  from  the  tremie  pipe.  The 
concrete  must  be  placed  such  that  all  water,  slurry 
and  contaminated  concrete  below  design  cutoff 
level  is  displaced. 

1815.5.3  For  piers  with  enlarged  bases,  the 
concrete  may  be  placed  under  slurry,  based  upon 
the  recommendations  of  a  registered  design 
professional  and  with  the  approval  of  the  code 
official.  The  specific  soil  or  rock  conditions, 
equipment  and  procedures  used  shall  be  taken  into 
account. 

1815.5.4  A  suitable  method  shall  be  employed  to 
verify  that  the  entire  length  of  the  shaft  is 
completely  filled  with  concrete.  Such  means  shall 
include  the  ability  to  determine  the  incremental 
volumes  of  concrete  installed  in  relation  to 
calculated  shaft  volume. 

1815.6  Design  stresses.  Foundation  piers  may  be 
designed  as  concrete  columns  with  continuous 
lateral  support  below  the  soil  level.  The  unit 
compressive  stress  in  the  concrete  shall  not  exceed 
33%  of  the  28  day  strength  of  the  concrete  or 
1,600  psi,  whichever  is  less.  The  unit  compressive 
stress  in  the  steel  reinforcement  or  the  permanent 
steei  casing  shall  not  exceed  40%  of  the  yield 
strength  of  the  steel  or  24,000  psi,  whichever  is  less. 
Permanent  steel  casing  which  is  used  as  structural 
reinforcement  shall  be  protected  against  corrosion  in 
accordance  with  780  CMR  1816  4  1 


9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


319 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1815.7  Alignment:  When  the  center  of  the  cross 
section  of  a  foundation  pier  at  any  level  deviates 
from  the  resultant  of  all  forces  more  than  1/50  of  its 
height,  or  more  than  1/10  of  its  diameter,  it  shall  be 
reinforced  as  provided  in  ACI  336.  The  restraining 
effect  of  the  surrounding  soil  may  be  taken  into 
account. 

1815.8  Allowable  bearing  pressure:  The  allowable 
bearing  pressure  on  the  bottom  of  the  pier  shall  be  in 
accordance  with  780  CMR  1804.3  Additional  load 
may  be  carried  by  using  higher  bearing  pressures 
than  allowed  by  780  CMR  1804.3  and/or  by  friction 
on  the  sides  of  the  pier  embedded  in  suitable  bearing 
material  based  on  recommendations  by  a  registered 
design  professional  and  subject  to  the  approval  of 
the  code  official.  Such  recommendations  shall  be 
based  on  the  results  of  load  tests  or  other  suitable 
tests  or  analyses  carried  out  to  measure  side  friction 
and/or  end  bearing  of  piers  installed  in  the  same 
bearing  stratum. 

1815.9  Minimum  spacing:  The  minimum  center-to- 
center  spacing  between  adjacent  piers  designed  for 
friction  support  shall  be  not  less  than  two  times  the 
shaft  diameter. 

1815.10  Special  provisions:  For  piers  with  shaft 
diameter  less  than  24  inches  (610  mm),  the 
following  special  provisions  shall  apply: 

1815.10.1  For  piers  with  temporary  casing 
extending  to  the  bottom,  the  concrete  may  be 
poured  from  the  top  in  accordance  with  780  CMR 
1815.5. 

1815.10.2:  For  all  other  cases,  piers  shall  be  filled 
from  the  bottom  upward  through  a  tremie  or 
concrete  pump  tube  in  accordance  with  780  CMR 
1815.5.2 

1815.11  Records:  The  owner  shall  engage  a 
registered  design  professional  to  monitor  the 
installation  of  the  piers.  The  design  professional  or 
his  representative,  qualified  by  training  and 
experience,  shall  be  present  at  all  times  while 
foundation  piers  are  being  installed,  to  observe  and 
test  the  bearing  material  in  place,  to  verify  the  pier 
dimensions  and  to  observe  concrete  placement. 
When  direct  inspection  of  the  bearing  surface  is 
impossible,  a  suitable  method  shall  be  employed  to 
verify  the  condition  of  the  bearing  material  and  to 
make  the  measurements  and  tests.  Records  of  all 
observations,  tests  and  dimensions  shall  be  signed 
by  the  registered  design  professional  and  a  copy 
shall  be  filed  in  the  office  of  the  code  official. 

780  CMR  1816.0  PILE  FOUNDATIONS 
1816.1    Investigation:   Pile  foundations   shall  be 
designed  and  installed  on  the  basis  of  a  foundation 
investigation  and  report  conducted  in  accordance 
with  780  CMR  1802.0.     The  investigation  shall 


include  borings,  test  pits  or  other  subsurface 
explorations  at  locations  and  depths  sufficient  to 
determine  the  position,  thickness  and  adequacy  of 
the  loadbearing  soils  and  demonstrate  that  there  are 
no  compressible  soil  deposits  below  the  bearing 
stratum  which  would  adversely  affect  the  structure, 
except  where  sufficient  data  upon  which  to  base  the 
design  and  installation  are  available  from  other 
sources.  In  addition,  the  building  site  shall  be 
investigated  for  all  conditions  which  might  promote 
deterioration  of  pile  foundations,  in  order  to  satisfy 
the  requirements  of  780  CMR  1816  4  The 
investigation  and  report  shall  include,  but  not  be 
limited  to.  the  following: 

1.  Recommended  pile  types  and  installed 
capacities; 

2.  Driving  criteria; 

3.  Installation  and  field  inspection  procedures; 

4  Pile  load  test  requirements, 

5  Durability  of  pile  materials;  and 

6  Designation  of  loadbearing  stratum  or  strata. 

1816.2  Special  piles:  Types  of  piles  not  specifically 
covered  by  the  provisions  of  780  CMR  1816.0  may 
be  permitted,  subject  to  the  approval  of  the  code 
official,  upon  the  submission  of  acceptable  test  data 
and  design  and  construction  information  prepared  by 
a  registered  design  professional  stating  that  the  pile 
installation  is  adequate  to  fulfill  the  design 
requirements. 

1816.3  Pile  bending  seismic  design:  Piling  for 
buildings  assigned  to  Seismic  Performance 
Category  D,  in  accordance  with  780  CMR  1612.2.7, 
shall  be  designed  for  the  maximum  imposed 
curvatures  resulting  from  seismic  forces  on  free- 
standing piles  where  the  piles  are  located  in  loose 
granular  soils  or  in  soil-profile  type  S3  or  S4.  in 
accordance  with  780  CMR  1612.4.2.  The  piles  shall 
be  designed  and  detailed  in  accordance  with  the 
special  moment  frame  requirements  of  780  CMR 
1903.3.3  or  780. CMR  2203.2  for  a  length  equal  to 
120%  of  the  flexural  length  The  flexural  length 
shall  be  the  distance  from  the  point  of  fixity  to  the 
pile  cap. 

1816.4  Protection  of  pile  materials:  Where  boring 
records,  previous  experience,  or  site  conditions 
indicate  possible  deleterious  action  on  pile  materials 
because  of  soil  constituents,  changing  water  levels 
or  other  factors,  the  pile  materials  shall  be 
adequately  protected  by  approved  materials, 
methods  or  processes.  Protective  materials  shall  be 
applied  to  the  piles  so  as  not  to  be  rendered 
ineffective  by  driving. 

1816.4.1    Steel   and   steel-concrete   piles:    At 

locations  where  steel  and  steel-concrete  piles  will 
be  in  contact  with  any  material  which  is  corrosive 
to  the  steel,  one  of  the  following  procedures  shall 
be  used  for  protection,  or  any  other  method  which 
will  satisfy  the  requirements  of  the  code  official: 


320 


780  CMR  -  Sixth  Edition     corrected-  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


1  Remove  all  objectionable  material 

2  Effectively  protect  the  steel  surface  from 
pile  cutoff  grade  to  a  grade  15  feet  (4.6  m) 
below  the  bottom  of  the  objectionable  material 
by  means  of: 

a.     cathodic  protection  as  approved  by  the 

code  official; 

b     an  approved  encasement  of  not  less  than 

three  inches  (76  mm)  of  dense  concrete; 

c    an  effective  protective  coating  subject  to 

the  approval  of  the  code  official;  or 

d    providing  an  excess  steel  thickness  of  Ve 

inch  (3.2  mm)  beyond  design  requirements 

on  all  exposed  steel  surfaces. 

1816.4.2  Timber  piles:  The  preservative 
treatment  of  timber  piles  shall  comply  with  the 
provisions  of  780  CMR  1822.2. 

1816.5  Lateral  support:  Any  soil  shall  be  deemed 
to  afford  sufficient  lateral  support  to  permit  the 
design  of  any  type  of  pile  as  a  short  column  When 
piles  are  driven  through  soil  which  will  be  removed 
subsequent  to  the  completion  of  the  foundation,  the 
resistance  offered  by  such  material  shall  not  be 
considered  to  contribute  to  the  lateral  supporting 
capacity. 

1816.5.1  Column  action:  The  portion  of  a  pile 
that  is  not  laterally  supported  shall  be  designed  as 
a  column  in  accordance  with  780  CMR  19  taking 
into  consideration  the  conditions  of  end  fixity 

1816.6  Group  action:  In  cohesive  soils,  the 
compressive  load  capacity  of  a  group  of  friction 
piles  shall  be  analyzed  by  a  generally  accepted 
engineering  method,  and,  where  such  analysis 
indicates,  the  individual  allowable  pile  load  shall  be 
reduced  accordingly. 

1816.7  Stability 

1816.7.1  Wall  foundations:  All  piles  in  wall 
foundations  shall  be  staggered  about  the  center  of 
gravity  of  the  wall  load  at  a  minimum  distance  of 
Vz  the  pile  top  diameter  therefrom.  A  foundation 
wall  restrained  laterally  so  as  to  ensure  stability 
both  during  and  after  construction  may  be 
supported  by  a  single  row  of  piles. 

1816.7.2  Columns.  Individual  columns  supported 
on  piles  shall  be  designed  for  eccentricity  between 
the  column  and  the  centroid  of  the  supporting 
piles  equal  to  a  minimum  of  three  inches  (76  mm) 
or  the  actual  eccentricity,  whichever  is  greater. 
The  design  shall  account  for  such  eccentricity 
through  one  of  the  following  methods. 

a.  By  supporting  the  column  on  a  minimum  of 
three  piles  in  a  triangular  pattern. 

b.  By  designing  walls,  grade  beams  or 
structural  floors  to  resist  the  bending  moment 
induced  by  the  eccentricity. 


c.  By  designing  the  piles,  column  or  both  to 
resist  the  bending  moment  induced  by  the 
eccentricity  and  providing  adequate  lateral 
restraint  at  the  top  of  the  piles  to  resist  the 
lateral  thrust  due  to  the  bending  moment. 

1816.8  Structural  integrity  Piles  shall  be  installed 
in  such  a  manner  and  sequence  as  to  prevent 
distortion  or  damage  to  piles  being  installed  or 
already  in  place,  to  the  extent  that  such  distortion  or 
damage  affects  the  structural  integrity  of  the  piles. 

When  piles  have  been  damaged  in  driving,  or  have 
been  driven  in  locations  and  alignment  other  than 
those  indicated  on  the  plans,  or  have  capacities  less 
than  required  by  the  design,  the  affected  pile  groups 
and  pile  caps  shall  be  investigated,  and  if  necessary, 
the  pile  groups  or  pile  caps  shall  be  redesigned  or 
additional  piles  shall  be  driven  to  replace  the 
defective  piles. 

1816.9  Spacing:  The  minimum  center-to-center 
spacing  of  piles  shall  be  not  less  than  twice  the 
average  diameter  of  a  round  pile,  nor  less  than  1% 
times  the  diagonal  dimension  of  a  rectangular  pile. 
When  driven  to  or  penetrating  into  rock,  the  spacing 
shall  be  not  less  than  24  inches  (610  mm)  When 
receiving  principal  support  from  end-bearing  on 
materials  other  than  rock  or  through  frictional 
resistance,  the  spacing  shall  be  not  less  than  30 
inches  (762  mm)  or  as  provided  in  780  CMR 
1820.4  6  for  Pressure  Injected  Footings. 

1816.10  Splices:  Splices  shall  be  avoided  insomuch 
as  practicable.  When  used,  slices  shall  be 
constructed  so  as  to  provide  and  maintain  true 
alignment  and  position  of  the  component  parts  of  the 
pile  during  installation  and  subsequent  thereto,  and 
shall  be  of  adequate  strength  to  transmit  the  vertical 
and  lateral  loads  and  moments  occurring  at  the 
location  of  the  splice  during  driving  and  under 
service  loading.  Splices  shall  develop  not  less  than 
50%  of  the  capacity  of  the  pile  in  bending. 
Additionally,  all  pile  splices  occurring  in  the  upper 
ten  feet  (3  m)  of  the  embedded  portion  of  the  pile 
shall  be  capable  of  resisting  at  allowable  working 
stresses  the  moment  and  shear  that  results  from  an 
assumed  eccentricity  of  the  pile  load  of  three  inches 
(76  mm);  or  the  pile  shall  be  braced  in  accordance 
with  780  CMR  1816.7  to  other  piles  that  do  not  have 
splices  in  the  upper  ten  feet  (3  m)  of  embedment. 

1816.11  Pile  caps:  Pile  caps  shall  be  of  reinforced 
concrete.  The  soil  immediately  below  the  pile  cap 
shall  not  be  considered  as  carrying  any  vertical  load. 
The  tops  of  all  piles  shall  be  embedded  not  less  than 
three  inches  (76  mm)  into  pile  caps,  and  the  caps 
shall  extend  at  least  four  inches  (102  mm)  beyond 
the  edges  of  all  piles.  The  tops  of  all  piles  shall  be 
cut  back  to  sound  material  before  capping. 

1816.11.1    Pile   cap   seismic   connection:    All 

concrete  piles  shall  be  connected  to  the  pile  cap  so 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


321 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


accordance  with  780  CMR  1612.1.7.  so  that 
reinforcement  is  embedded  in  the  pile  cap  for  a 
distance  equal  to  the  development  length  as 
specified  in  ACI  318  listed  in  Appendix  A 

Field-placed  dowels  anchored  in  the  concrete 
piles  are  acceptable  The  development  length  to 
be  provided  is  the  full  development  length  for 
compression  without  reduction  in  length  for 
excess  area.  Where  seismic  confinement 
reinforcement  at  the  top  of  the  pile  is  required, 
alternative  measures  for  laterally  confining 
concrete  and  maintaining  toughness  and  ductile- 
like  behavior  at  the  top  of  the  pile  shall  be 
permitted  provided  consideration  is  given  to 
forcing  the  hinge  to  occur  in  the  confined  region. 

Where  a  minimum  length  for  reinforcement  or 
the  extent  of  closely  spaced  confinement 
reinforcement  is  specified  at  the  top  of  the  pile, 
provisions  shall  be  made  so  that  those  specified 
lengths  or  extents  are  maintained  after  pile 
cut-off 

1816.11.2  Pile  foundation  seismic  ties  Piles  or 
pile  caps  shall  be  interconnected  by  ties  capable 
of  resisting,  in  tension  or  compression,  a  force 
equal  to  10%  of  the  larger  column  dead  plus  live 
load  Individual  tie  beams  are  not  required  when 
it  is  demonstrated  that  equivalent  restraint  will  be 
provided  by  structural  members  within  slabs  on 
grade  or  reinforced  concrete  slabs  on  grade  or 
confinement  by  competent  rock,  cohesive  soils, 
very  dense  granular  soils  or  other  approved 
means. 

1816.12  Pre-excavation:  Jetting,  augering  and  other 
methods  of  pre-excavation  must  be  approved  by  the 
code  official  and  carried  out  in  the  same  manner  as 
used  for  piles  subject  to  load  test  and  in  a  manner 
which  will  not  impair  the  carrying  capacity  of  the 
piles  already  in  place  or  the  safety  of  existing 
adjacent  structures.  Pre-excavation  shall  be  of  the 
same  method  as  carried  out  on  piles  subject  to  load 
tests.  Immediately  after  completion  of  jetting  or 
augering,  the  pile  shall  be  advanced  to  the  maximum 
depth  of  pre-excavation  and  driven  below  this  depth 
to  the  required  load  resistance.  Where  load  tests  are 
required,  pre-excavation  of  test  piles  will  be  of  the 
same  manner  as  proposed  for  production  piles. 

1816.13  Inspection:  The  owner  shall  engage  a 
registered  design  professional  who  shall  submit  his 
qualifications  in  writing  to  the  code  official.  This 
design  professional,  or  his  representative,  who  must 
be  qualified  by  experience  and  training,  shall  be 
present  at  all  times  while  piles  are  being  driven  to 
observe  all  work  in  connection  with  the  piles  The 
design  professional  or  his  representative  shall  make 
an  accurate  record  of  the  material  and  the  principal 
dimensions  of  each  pile,  of  the  weight  and  fall  of  the 
ram,  the  type,  size  and  make  of  hammer,  cushion 
blocks,  the  number  of  blows  per  minute,  the  energy 
per  blow,  the  number  of  blows  per  inch  for  the  last 


six  inches  (150  mm)  of  driving,  together  with  the 
grades  at  point  and  cutoff  and  any  other  pertinent 
details.  A  copy  of  these  records  shall  be  signed  by 
the  registered  design  professional,  and  filed  in  the 
office  of  the  code  official. 

1816.14  Identification  All  pile  materials  shall  be 
identified  for  conformity  to  the  specified  grade  with 
this  identification  maintained  continuously  from  the 
point  of  manufacture  to  the  point  of  installation  or 
shall  be  tested  by  an  approved  agency  to  determine 
conformity  to  the  specified  grade  and  the  approved 
agency  shall  furnish  an  affidavit  of  compliance  to 
the  code  official  . 

1816.15  Pile  location  plan:  A  plan  showing  the 
location  and  designation  of  all  piles  by  an 
identification  system  shall  be  filed  with  the  code 
official  prior  to  installation  of  such  piles.  All 
detailed  records  for  individual  piles  shall  bear  an 
identification  corresponding  to  that  shown  on  the 
plan 

1816.16  Use  of  existing  piles:  Piles  left  in  place 
where  a  structure  has  been  demolished  shall  not  be 
used  for  the  support  of  new  construction  unless 
satisfactory  evidence  is  submitted  to  the  code 
official  which  indicates  that  the  piles  are  sound  and 
meet  all  of  the  requirements  of  780  CMR.  Such 
piles  shall  be  load  tested  or  redriven  to  verify  their 
capacities.  The  design  load  applied  to  such  piles 
shall  be  the  lowest  allowable  load  as  determined  by 
tests  or  redriving  data. 

1816.17  Pile  driveability:  Pile  cross  sections  shall 
be  of  sufficient  size  and  strength  to  withstand 
handling  and  driving  stresses  without  damage  to  the 
pile  and  to  provide  sufficient  stiffness  to  transmit  the 
required  driving  forces.  Driven  piles  of  uniform 
cross  section  or  tapered  piles  shall  have  a  minimum 
nominal  diameter  of  eight  inches  (200  mm)  except 
as  provided  in  780  CMR  1820.6.4  for  small  diameter 
grouted  piles,  780  CMR  1822.3.3  for  timber  piles 
and  780  CMR  1821.1  for  precast  concrete  piles 
Tapered  shoes  or  points  of  lesser  dimensions  may  be 
attached  to  the  pile  unit. 

1816.18  Pile  heave:  Adequate  provision  shall  be 
made  to  observe  pile  heave.  Accurate  reference 
points  shall  be  established  on  each  pile  immediately 
after  installation;  for  cast-in-place  piles  with  unfilled 
corrugated  shells,  the  reference  point  shall  be  at  the 
bottom  of  the  pile  If,  following  the  installation  of 
other  piles  in  the  vicinity,  heaving  of  XA  inch  (13 
mm)  or  more  occurs,  the  heaved  piles  shall  be  re- 
driven  to  develop  the  required  capacity  and 
penetration,  or  the  capacity  of  the  pile  may  be 
verified  by  load  tests  in  accordance  with 
780  CMR  1817.4. 


322 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


1816.19  Settlement  analysis:  The  settlement  of 
individual  piles  or  groups  of  piles  shall  be  estimated 
based  upon  approved  methods  of  analysis  and  in 
accordance  with  780  CMR  1805.2.2.  The  predicted 
settlement  shall  neither  cause  harmful  distortion  of 
or  instability  in  the  structure,  nor  cause  any  stresses 
to  exceed  allowable  values. 

1816.20  Use  of  vibratory  drivers:  Vibratory  drivers 
shall  only  be  used  to  install  piles  where  the  pile  load 
capacity  is  verified  by  load  tests  in  accordance  with 
780  CMR  1817.4.  The  installation  of  production 
piles  shall  be  controlled  according  to  power 
consumption,  rate  of  penetration  or  other  approved 
means  that  assure  pile  capacities  equal  to  or 
exceeding  those  of  the  test  piles. 

1816.21  Installation  sequence:  Piles  shall  be 
installed  in  such  sequence  as  to  avoid  compacting 
the  surrounding  soil  to  the  extent  that  other  piles 
cannot  be  installed  properly,  and  to  prevent  ground 
movements  that  could  damage  adjacent  structures. 

780  CMR  1817.0  ALLOWABLE  PILE  LOADS 

1817.1  General:  The  allowable  load  on  piles  shall 
be  determined  by  the  applicable  formulas  complying 
with  accepted  engineering  practice  or  load  tests  as 
stated  herein.  The  maximum  load  capacity  shall  be 
limited  by  the  supporting  capacity  as  obtained  from 
bearing  upon  or  embedment  in  bearing  materials  as 
defined  in  780  CMR  1804.0  and  1805.0,  but  the  load 
shall  not  exceed  the  capacity  of  the  pile  designed  in 
accordance  with  the  provisions  of  780  CMR  1817.0 
and  the  Code  provisions  for  the  construction 
materials  involved. 

The  allowable  load  on  a  pile  shall  not  be  limited 
to  load  obtained  by  multiplying  its  point  area  by  the 
allowable  bearing  pressure  given  in  780  CMR 
1804.3. 

1817.2  Piles  in  subsiding  areas:  Where  piles  are 
driven  through  subsiding  fills  or  other  subsiding 
strata  and  derive  support  from  underlying  firmer 
materials,  the  downward  friction  forces  which  are 
imposed  on  the  piles  by  the  subsiding  upper  strata 
shall  be  included  in  the  design. 

1817.3  Determination  of  allowable  load:  In  the 

absence  of  pile  load  tests  performed  in  accordance 
with  780  CMR  1817.4,  the  load  on  a  single  pile, 
except  for  the  pile  types  covered  in  780  CMR  1820.2 
(augered  uncased  piles),  780  CMR  1820.4  (pressure 
injected  footings)  and  780  CMR  1824.0  (steel-core 
caissons),  shall  not  exceed  the  higher  of  the  two 
values  determined  in  accordance  with  780  CMR 
1817.3.1  (driving  formula)  or  780  CMR  1817.3.2 
(friction  formula  in  clay).  Loads  on  jacked  piles 
shall  be  determined  in  accordance  with  1817.3.3. 

1817.3.1  Driving  formula: 


1.  Where  the  design  load  capacity  of  the  pile 
does  not  exceed  50  tons,  the  allowable  load 
may  be  computed  by  means  of  the  following 
driving  formula: 

s  +  c 

where— 

R  =    allowable  pile  load  in  pounds; 

E  =    energy  per  blow  in  foot-pounds; 

S  =     penetration  of  last  blow  or  average 

penetration  of  last  few  blows  expressed  in 

inches;  and 

C  =    constant  equal  to  1.0  for  drop  hammer 

and  0. 1  for  steam  or  air  hammer. 

2.  When  the  design  load  capacity  of  a  pile 
exceeds  50  tons,  the  required  driving  resistance 
shall  be  increased  above  that  required  by  the 
driving  formula  in  780  CMR  1817.3.1  based  on 
load  tests  or  past  experience  under  similar 
conditions. 

3.  The  value  of  S  must  be  determined  with  the 
hammer  operating  at  100%  of  the  rated  number 
of  blows  per  minute  for  which  the  hammer  is 
designed. 

4.  Any  driving  resistance  developed  in  strata 
overlying  the  bearing  material  shall  be 
discounted. 

5.  If  the  driving  of  the  pile  has  been 
interrupted  for  more  than  one  hour,  the  value 
of  S  shall  not  be  determined  until  the  pile  is 
driven  at  least  an  additional  12  inches 
(305  mm),  except  when  it  encounters  refusal 
on  or  is  in  a  material  of  Classes  1  through  6. 

6.  When  any  pile  is  driven  through  a  layer  of 
gravel,  sand  or  hard  clay  exceeding  five  feet  in 
thickness,  and  through  an  underlying  soft 
stratum  to  reach  the  bearing  stratum,  the 
bearing  capacity  shall  not  be  determined  in 
accordance  with  the  driving  formula,  unless 
jetting  is  used  during  the  entire  driving  of  the 
pile  through  the  layer  of  gravel,  sand  or  hard 
clay  or  unless  a  hole  is  pre-excavated  through 
said  layer  for  each  pile. 

1817.3.2  Friction  formula  in  clay:  Where  the 
design  load  does  not  exceed  22  tons,  the 
allowable  load  on  a  pile  stopped  in  soil  of 
Material  Class  10  (Table  1804.3)  of  medium  to 
hard  consistency  may  be  based  on  a  friction  value 
of  500  psf  of  embedded  pile  surface.  Higher 
design  loads  or  other  friction  values  shall  be 
determined  by  pile  load  tests  in  accordance  with 
780  CMR  1817.4  or  1817.7. 

The  embedded  length  shall  be  the  length  of  the 
pile  below  the  surface  of  the  Class  10  soil  or 
below  the  surface  of  immediately  overlying 
satisfactory  bearing  material.  The  area  of 
embedded  pile  surface  shall  be  computed  by 
multiplying  the  embedded  length  by  the  perimeter 
of  the  smallest  circle  or  polygon  that  can  be 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


323 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDrNG  CODE 


circumscribed  around  the  average  section  of  the 
embedded  length  of  the  pile.  The  method  of 
determining  the  allowable  load  described  in 
780  CMR  1817.3.2  shall  not  be  used  for  a  pile  in 
which  the  drive  pipe  is  withdrawn  or  for  piles 
which  are  driven  through  the  clay  to  or  into  firmer 
bearing  materials. 

In  case  these  piles  are  in  clusters,  the  allowable 
load  shall  be  computed  for  the  smaller  of  the 
following  two  areas:  the  sum  of  the  embedded 
pile  surfaces  of  individual  piles;  or  the  area 
obtained  by  multiplying  the  perimeter  of  the 
polygon  circumscribing  the  cluster  at  the  surface 
of  the  satisfactory  bearing  material  by  the  average 
embedded  length  of  the  piles. 

1817.3.3  Jacked  piles: 

1.  Not  less  than  10%  of  jacked  piles  shall  be 
load-tested  to  twice  the  design  load  (load  test 
piles).  All  other  jacked  piles  shall  be  founded 
in  the  same  bearing  stratum  as  the  load  test 
piles  and  shall  be  proof-loaded  to  125%  of 
design  load  (production  piles). 

2.  For  production  piles,  the  125%  of  design 
load  shall  be  maintained  for  at  least  30 
minutes.  Acceptability  criteria:  during  final 
15  minutes  of  load,  the  rate  is  not  progressive 
(plot  is  linear  or  decreasing  when  settlement  is 
plotted  against  logarithm  of  time);  and  the  rate 
of  settlement  is  equal  to  or  less  than  that 
observed  for  load  test  piles  during  the 
corresponding  time  period  under  125%  of 
design  load. 

3.  Settlement  readings  shall  be  plotted  after 
one,  two,  four,  eight,  and  15  minutes,  and  at 
15-minute  intervals  thereafter.  Load  shall  be 
maintained  on  production  piles  until 
acceptability  criteria  are  met. 

4.  For  load  test  piles,  the  load  shall  be  applied 
directly  to  125%  of  design  load  and  maintained 
for  not  less  than  30  minutes,  and  until  the 
settlement  rate  is  not  progressive  (as  defined 
above).  Load  shall  then  be  increased  to  twice 
the  design  load  and  maintained  constant  for  not 
less  than  four  hours.  Settlement  during  the 
four  hour  period  shall  not  exceed  0.050  inches 
(1.3  mm). 

In  the  event  that  settlement  exceeds  0.050 
inches  (1.3  mm)  in  four  hours,  the  pile  shall  be 
deemed  unacceptable  for  Vz  of  the  final  load. 
The  allowable  load  on  the  rejected  pile  may  be 
established  by  performing  an  additional  load 
test  at  the  lesser  design  load.  The  design  load 
shall  not  exceed  !4  the  load  maintained  for  a 
four  hour  period  during  which  time  settlement 
did  not  exceed  0.050  inches  (1.3  mm). 

1817.4  Compression  load  test:  Where  the  design 
load  for  any  pile  is  in  doubt  or  where  the  proposed 
design  load  for  any  pile,  including  pressure  injected 
footings,  exceeds  50  tons  or  exceeds  the  value 
determined  in  accordance  with  780  CMR  1817.3.2 


(friction  formula  in  clay),  one  or  more  pile  load  tests 
shall  be  performed  on  representative  piles  in 
accordance  with  780  CMR  1817.0. 

The  results  of  the  load  test  can  be  applied  to  other 
piles  within  the  area  of  substantially  similar  subsoil 
conditions  as  that  for  the  test  pile,  providing  the 
performance  of  the  test  pile  has  been  satisfactory  and 
the  remaining  piles  are  of  the  same  type,  shape  and 
size  as  the  test  pile  and  are  installed  using  the  same 
methods  and  equipment  and  are  driven  into  the  same 
bearing  strata  as  the  load-tested  pile  to  an  equal  or 
greater  penetration  resistance. 

For  design  loads  between  50  and  120  tons,  pile 
load  tests  may  be  waived  by  the  code  official,  where 
justified,  upon  submittal  of  substantiating  data 
prepared  by  a  registered  design  professional  which 
include  experience  and/or  performance  records  for 
the  proposed  pile  installation  under  similar  soil  and 
loading  conditions. 

1817.4.1  Required  test  load:  A  single  pile  shall 
be  load-tested  to  not  less  than  twice  the  allowable 
design  load.  When  two  or  more  piles  are  to  be 
tested  as  a  group,  the  total  load  shall  be  not  less 
than  IVi  times  the  allowable  design  load  for  the 
group. 

In  no  case  should  the  load  reaching  the  top  of 
the  bearing  stratum  under  maximum  test  load  for 
a  single  pile  or  pile  group  be  less  than  the 
following: 

Case  A-piles  designed  as  end-bearing  piles: 
100%  of  the  allowable  design  load. 
Case   B-piles   designed   as   friction   piles: 
150%  of  the  allowable  design  load. 
For  piles  designed  as  combination  end-bearing 
and  friction  piles,  Case  A  applies  if  the  pile  is 
designed  to  support  more  than  50%  of  its  design 
in  bearing;  otherwise,  Case  B  applies. 

1817.4.2  Internal  instrumentation:  The  test  pile 
shall  be  instrumented  in  accordance  with  the 
requirements  in  paragraph  4.4. 1  of  ASTM  Dl  143 
listed  in  Appendix  A  (hereinafter  ASTM  D 1 143) 
to  enable  measurement  or  computation  of  the  load 
in  the  pile  where  it  enters  the  bearing  stratum. 
For  piles  containing  concrete,  instrumentation 
shall  be  installed  in  the  test  pile  to  permit  direct 
measurement  of  the  elastic  modulus  of  the  pile. 

This  requirement  is  waived  for  the  following 
cases: 

1.  The  test  pile  is  installed  within  a  casing 
that  extends  to  within  ten  feet  above  the 
bearing  stratum. 

2.  The  pile  to  be  tested  has  been  functioning 
satisfactorily  under  load  for  a  period  of  one 
year  or  more. 

3.  The  pile  is  30  feet  long  or  less  and  no 
appreciable  load  will  be  supported  above  the 
bearing  stratum. 

1817.4.3  Loading  procedure:  Pile  load  tests  shall 
be  conducted  in  accordance  with  ASTM  Dl  143, 


324 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


Standard  Method  of  Testing  Piles  Under  Static 
Axial  Compressive  Load,  except  that  Section  5, 
Loading  Procedures,  shall  be  deleted  and  replaced 
by  the  following  provisions: 

1 .  Apply  25%  of  the  allowable  design  load 
every  lA  hour.  Longer  time  increments  may  be 
used,  but  each  time  increment  should  be  the 
same.  In  no  case  shall  a  load  be  changed  in  the 
rate  of  settlement  is  not  decreasing  with  time. 

2.  At  200%  of  the  allowable  design  load  (or 
150%  for  pile  groups),  maintain  the  load  for  a 
minimum  of  one  hour  and  until  the  settlement 
(measured  at  the  lowest  point  on  the  pile  at 
which  measurements  are  made)  over  a  one- 
hour  period  is  not  greater  than  0.01  in. 

3.  Remove  50%  of  the  design  load  every  15 
minutes  until  zero  load  is  reached.  Longer 
time  increments  may  be  used,  but  each  should 
be  the  same. 

4  Measure  rebound  at  zero  load  for  a 
minimum  of  one  hour. 

5.    For  each  load  increment  or  decrement,  take 

readings  at  the  top  of  the  pile  and  on  the 

internal  instrumentation  at  one,  two,  four,  eight 

and  15  minutes  and  at   15-minute  intervals 

thereafter. 

A  load  greater  than  200%  of  the  allowable  design 

load  (or  150%  of  the  allowable  design  load  for 

pile  groups)  may  be  applied  at  the  top  of  the  pile, 

using  the  above  loading  procedure,  to  ensure  that 

780  CMR  1817.4.1  is  fulfilled.    Other  optional 

methods  listed  in  ASTM  Dl  143  may  be  approved 

by  the  code  official  upon  submittal  in  advance  of 

satisfactory  justification  prepared  by  a  registered 

design  professional  who  is  qualified  in  this  field. 

1817.4.4  Selection  of  design  load:  Provided  that 
the  allowable  design  load  does  not  exceed  the 
load  allowed  in  780  CMR  1817.0  for  the  type  of 
pile  and  provided  that  the  allowable  design  load 
does  not  exceed  100%  of  the  load  supported  in  the 
bearing  stratum  (or  %  of  the  load  supported  in  the 
bearing  stratum  for  friction  piles  or  pile  groups) 
when  the  maximum  test  load  is  applied,  then  the 
allowable  design  load  shall  be  the  greater  of  the 
following: 

1 .  Allowable  design  load  based  on  settlement 
during  loading:  50%  of  the  applied  test  load 
which  causes  a  gross  settlement  at  the  pile 
cutoff  grade  equal  to  the  sum  of:  a)  the 
theoretical  elastic  compression  of  the  pile  in 
inches  assuming  all  the  load  on  the  butt  is 
transmitted  to  the  tip,  plus  b)  0.15  inch 
(3.8  mm),  plus  c)  1%  of  the  pile  tip  diameter  or 
pile  width  in  inches.  If  the  settlements  are  so 
small  that  the  load-settlement  curve  does  not 
intersect  the  failure  criterion,  the  allowable 
design  load  shall  be  50%  of  the  maximum  test 
load. 

2  Allowable  design  load  based  on  the  net 
settlement  after  rebound:  50%  of  the  applied 
test  load  which  results  in  a  net  settlement  at  the 


top  of  the  pile  of  Vz  inch  (13  mm)  after  rebound 
for  a  minimum  of  one  hour  at  zero  load 

1817.5  Use  of  higher  allowable  stresses:  Higher 
stresses  than  those  permitted  in  780  CMR  1817  for 
various  pile  materials  may  be  approved  by  the  code 
official  based  upon  the  submission  of  substantiating 
data  and  analyses  which  justify  such  higher  stresses. 
The  data  shall  be  presented  in  a  report  prepared  by 
a  registered  design  professional  experienced  in 
geotechnical  aspects  of  foundation  design  and  shall 
include,  as  applicable:  the  results  of  the  soil 
investigation,  dynamic  analyses  of  the  pile  behavior, 
pile  load  tests,  analyses  of  load  transfer  during 
testing  and  prediction  of  pile  performance  during 
long  term  service. 

1817.6  Lateral  load  tests:  The  allowable  load  on 
piles  subject  to  lateral  load  shall  be  verified  by  test 
unless  it  is  waived  by  the  code  official.  Pile  load 
tests  may  be  waived  by  the  code  official,  where 
justified,  upon  submittal  of  substantiating  data  which 
include  experience  and/or  performance  records  for 
pile  installations  under  similar  soil  and  loading 
conditions  prepared  by  a  registered  design 
professional  experienced  in  geotechnical  aspects  of 
foundation  design. 

1817.6.1  Required  test  load:  A  single  pile  shall 
be  load  tested  to  not  less  than  200%  of  the  design 
lateral  load. 

1817.6.2  Test  setup  and  loading  procedure:  The 

load  test  setup  instrumentation  and  loading 
procedure  shall  be  in  accordance  with  ASTM 
D3966  listed  in  Appendix  A 

1817.6.3  Selection  of  design  load:  The  design 
load  shall  be  selected  by  the  responsible 
registered  design  professional,  based  upon 
interpretation  of  the  load-deflection  data  from  the 
load  test. 

1817.7  Tension  load  tests:  The  allowable  load  on 
piles  in  tension  shall  be  verified  by  test  unless  it  is 
waived  by  the  code  official  Pile  load  test  may  be 
waived  by  the  code  official,  where  justified,  upon 
submittal  of  substantiating  data  which  includes 
experience  and/or  performance  records  for  pile 
installations  under  similar  soil  and  loading 
conditions  prepared  by  a  registered  design 
professional  experienced  in  the  geotechnical  aspects 
of  foundation  design. 

1817.7.1  Required  load  test:  A  single  pile  or  a 
pile  group  shall  be  load  tested  to  not  less  than 
200%  of  the  design  load  for  transient  loads  (i.e.: 
earthquake  and  wind)  and  250%  for  sustained 
loads. 

1817.7.2  Test  setup  and  loading  procedure:  The 

load  test  setup,  instrumentation  and  loading 
procedure  shall  be  in  accordance  with  ASTM 
D3689. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


325 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1817.7.3  Selection  of  design  load:  Provided  the 
allowable  design  load  does  not  exceed  the 
allowable  stresses  in  the  pile  materials,  the 
allowable  design  load  shall  be  the  lower  of  the 
following: 

1.  50%  (for  transient  loads)  or  40%  (for 
sustained  loads)  of  the  applied  test  load  which 
results  in  a  net  upward  movement  of  14  inch  at 
the  top  of  the  pile  after  removal  of  the 
maximum  test  load  (The  gross  upward 
movement  minus  the  rebound  movement). 

2.  50%  (for  transient  loads)  or  40%  (for 
sustained  loads)  of  the  applied  test  load  which 
results  in  continuous  upward  movement  with 
no  increase  in  load. 

1817.8  Bearing  capacity:  Individual  piles  and 
groups  of  piles  shall  develop  ultimate  load  capacities 
of  at  least  twice  the  design  working  loads  in  the 
designated  bearing  layers.  Where  weaker  materials 
underlie  the  load  bearing  material  into  which  the 
piles  are  driven,  the  allowable  pile  load  shall  be 
limited  by  the  provision  that  the  vertical  pressures  in 
such  underlying  materials  produced  by  the  loads  on 
all  piles  in  a  foundation  shall  not  exceed  the 
allowable  bearing  pressures  of  such  materials  as 
provided  in  Table  1804.3  or  as  established  by 
analysis,  applying  accepted  principles  of  soil 
mechanics.  Piles  or  pile  groups  shall  be  assumed  to 
transfer  their  loads  to  the  underlying  materials  by 
spreading  the  load  uniformly  at  an  angle  of  60°  with 
the  horizontal,  starting  at  a  polygon  circumscribing 
the  piles  at  the  top  of  the  satisfactory  bearing 
material  in  which  they  are  embedded;  but  the  area 
considered  as  supporting  the  load  shall  not  extend 
beyond  the  intersection  of  the  60°  planes  of  adjacent 
piles  or  pile  groups. 

1817.9  Bent  piles:  The  load  bearing  capacity  of 
piles  discovered  to  have  a  sharp  or  sweeping  bend 
shall  be  determined  by  an  approved  method  of 
analysis  or  by  load  testing  a  representative  pile. 

1817.10  Overloads  on  piles:  The  maximum 
compressive  load  on  any  pile  due  to  mislocation 
shall  not  exceed  1 10%  of  the  allowable  design  load. 

780  CMR  1818.0  STRUCTURAL 
STEEL  PILES 

1818.1  Materials:  Structural  steel  piles  and  fully 
welded  steel  piles  fabricated  from  plates  shall 
conform  to  ASTM  A36,  A252,  A283,  A572  or  A588 
listed  in  Appendix  A. 

1818.2  Allowable  stress:  The  allowable  design 
compressive  stress  shall  not  exceed  35%  of  the 
minimum  specified  yield  strength  of  the  steel  nor 
12,600  psi.  The  maximum  allowable  design  stress 
shall  be  limited  to  50%  of  the  minimum  specified 


yield  strength  of  the  steel  where  higher  stresses  are 
substantiated  by  780  CMR  1817  5. 

1818.3  Pile  cap  seismic  connection:  All  structural 
steel  piles  shall  be  connected  to  the  pile  cap  for 
buildings  assigned  to  Seismic  Performance 
Category  D,  in  accordance  with  780  CMR  1612.2  7. 
The  connection  between  the  pile  cap  and  the 
structural  steel  piles  shall  be  designed  for  a  tensile 
force  equal  to  10%  of  the  pile  compression  design 
load. 

1818.4  Dimensions  of  H-piles  Sections  of  H-piles 
shall  comply  with  the  criteria  of  780  CMR  1818  4.1 
through  1818.4.4. 

1818.4.1  Flanges  The  flange  projections  shall  not 
exceed  14  times  the  minimum  thickness  of  metal 
in  either  the  flange  or  the  web.  and  the  flange 
widths  shall  not  be  less  than  80%  of  the  depth  of 
the  section. 

1818.4.2  Depth:  The  nominal  depth  in  the 
direction  of  the  web  shall  not  be  less  than  eight 
inches 

1818.4.3  Thickness:  Flanges  and  webs  shall  have 
a  minimum  nominal  thickness  of  %  inch 
(9.5  mm). 

1818.4.4  Tip  reinforcement:  The  tips  of  all 
steei  H  piles  having  a  thickness  of  metal  less  than 
5/10  inches  (12.7  mm)  which  are  driven  to  end 
bearing  on  rock  of  Classes  1  through  3  by  an 
impact  hammer  shall  be  reinforced.  The 
installation  of  all  steel  H  piles  by  impact  hammer 
to  end  bearing  on  rock  of  Classes  1  through  3 
shall  be  conducted  so  as  to  terminate  driving 
when  the  pile  reaches  refusal  on  the  rock  surface. 

780  CMR  1819.0  CONCRETE-FILLED 
STEEL  PIPE  AND  TUBE  PI1 ES 

1819.1  Material:  Steel  pipe  and  tube  piles  shall 
conform  to  ASTM  A252  or  A283  listed  in 
Appendix  A    Concrete  shall  conform  to  780  CMR 

1820.1.1. 

1819.2  Allowable  stress 

1819.2.1  Top  driven  piles:  The  allowable  design 
compressive  stress  in  the  concrete  shall  not 
exceed  25%  of  the  28-day  compressive  strength  of 
the  concrete  or  1,100  pounds  per  square  inch 
whichever  is  smaller.  The  maximum  allowable 
compressive  stress  in  the  steel  shall  not  exceed 
9,000psi. 

1819.2.2  Mandrel  driven  piles:  For  piles 
installed  with  mandrels  which  transmit  driving 
stresses  to  the  bottom  of  the  steel  pipe,  the 
allowable  design  compressive  stress  in  the 
concrete  shall  not  exceed  33%  of  the  28-day 
specified  compressive  strength.  The  allowable 
design  compressive  stress  in  the  steel  shall  not 


326 


780  CMR  -  Sixth  Edition     corrected-  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


exceed  35%  of  the  minimum  specified  yield  strength 
of  the  steel.  The  maximum  allowable  design  stress 
shall  be  limited  to  50%  of  the  minimum  specified 
yield  strength  of  the  steel  where  higher  stresses  are 
substantiated  by  780  CMR  1817. 

1819.3  Reinforcement:  Reinforcement  steel  shall 
conform  to  780  CMR  1820. 1.2.  Reinforcement  shall 
not  be  placed  within  one  inch  (25  mm)  of  the  steel 
casing. 

1819.3.1      Pile  cap  seismic  connection:     All 

concrete-filled  steel  pipe  and  tube  piles  shall  have 
minimum  reinforcement  of  1%  of  the  pile 
cross-sectional  area.  The  longitudinal  reinforce- 
ment shall  be  provided  in  the  top  of  the  pile  with 
a  length  equal  to  two  times  the  required  cap 
embedment  anchorage  into  the  pile  cap. 

1819.4  Minimum  dimensions:  Piles  shall  have  a 
nominal  outside  diameter  of  not  less  than  eight 
inches  (203  mm)  and  a  minimum  wall  thickness  of 
1/10  inch  (2.5  mm),  except  that  for  piles  driven  open 
ended,  the  nominal  outside  diameter  shall  not  be  less 
than  ten  inches  (254  mm)  and  the  wall  thickness  not 
less  than  V*  inch  (6  4  mm)  for  diameters  less  than  14 
inches  (356  mm)  and  %  inch  (9.5  mm)  for  diameters 
greater  than  14  inches.  Pipe  of  lesser  wall  thickness 
may  be  used  if  a  suitable  cast  steel  cutting  shoe  is 
provided. 

1819.5  Placing  concrete:  The  placement  of  concrete 
shall  conform  to  780  CMR  1820.1.3  and  1820.5. 

780  CMR  1820.0  CAST-IN-PLACE 
CONCRETE  PILES 

1820.1  General:  780  CMR  1820.0  includes  augered 
uncased  piles,  pressure  injected  footings  (enlarged 
base  piles),  cased  poured  piles,  and  small  diameter 
grouted  piles  Unless  otherwise  noted,  the  materials, 
reinforcing  and  installation  shall  conform  to 
780  CMR."  1820.1.1  through  1820.1.3. 

1820.1.1  Material.  All  concrete  shall  have  a 
28-day  specified  compressive  strength  (/'J  of  not 
less  than  3,000  psi  (2. 1 1  kg/mm2).  The  maximum 
size  of  coarse  aggregate  for  all  concrete  shall  be  % 
inch  (19  mm),  and  the  concrete  shall  have  a  slump 
of  four  to  seven  inches  (102  mm  to  178  mm).  If 
concrete  is  to  be  pumped,  the  mix  design 
including  slump  shall  be  adjusted  to  produce  a 
pumpable  concrete. 

1820.1.2  Reinforcement:  Except  for  steel  dowels 
embedded  five  feet  (1.5  m)  or  less  in  the  pile  and 
as  provided  for  in  780  CMR  1820.2  and  1820.6. 
reinforcement,  where  required,  shall  be  assembled 
and  tied  together  and  shall  be  placed  in  the  pile  as 
a  unit  before  the  reinforced  portion  of  the  pile  is 
filled  with  concrete. 

1820.1.2.1      Seismic      reinforcement:      All 
cast-in-place     concrete     piles     shall     have 


minimum  reinforcement  of  0.25%  of  the  pile 
cross-sectional  area  for  buildings  assigned  to 
Seismic  Performance  Category  C,  and  a 
minimum  reinforcement  of  0.50%  for  buildings 
assigned  to  Seismic  Performance  Category:  D 
in  accordance  with  780  CMR  1612.2.7  The 
reinforcing  shall  be  placed  in  the  top  Vs  of  the 
pile  length  or  extend  ten  feet  (3  m)  from  the 
top  of  the  pile,  whichever  is  the  longer  length. 
For  Seismic  Performance  Category  C 
buildings,  the  pile  reinforcing  shall  be  a 
minimum  of  four  longitudinal  bars  with  closed 
ties,  or  equivalent  spirals,  having  a  minimum 
diameter  of  Vt  inch.  The  ties  shall  be  provided 
at  a  maximum  spacing  of  16  times  the 
longitudinal  reinforcing  bar  diameter.  The 
maximum  tie  spacing  in  the  top  two  feet 
(610  mm)  of  the  pile  length  shall  be  four  inches 
(102  mm).  Tie  detailing  shall  be  in  accordance 
with  780  CMR  1903.4 

For  Seismic  Performance  Category  D 
buildings,  the  pile  reinforcing  shall  be 
minimum  of  four  longitudinal  bars  with  closed 
ties,  or  equivalent  spirals,  having  a  minimum 
diameter  of  %  inch,  for  piles  with  a  diameter  of 
20  inches  (205  mm)  or  less,  and  a  minimum  tie 
diameter  of '/:  inch,  for  piles  with  a  diameter 
more  than  20  inches  (508  mm).  The  ties  shall 
be  provided  at  a  minimum  spacing  of  eight 
times  the  longitudinal  reinforcing  bar  diameter 
The  maximum  tie  spacing  in  the  top  four  feei 
(1.2  m)  of  the  pile  length  shall  be  three  inches 
(76  mm) 

Exception:  Pile  ties  are  not  required  where 
spiral  welded  metal  casing  is  used,  provided 
the  casing  has  thickness  as  follows:  for 
Seismic  Performance  Category  C  buildings, 
0.058  inch  (1.5  mm)  and  for  Category  D 
buildings,  0.070  inch  (1.8  mm).  The  steel 
casings  must  be  adequately  protected  from 
corrosion  due  to  soil,  changing  water  levels, 
or  other  subgrade  conditions  indicated  by 
the  site  soil  investigation. 

1820.1.3  Installation:  For  all  cased  piles,  the 
inside  of  the  pipe  or  casing  shall  be  thoroughly 
cleaned  to  the  bottom  and  visually  inspected  prior 
to  filling  with  concrete.  The  piles  shall  be  poured 
in  such  a  manner  as  to  exclude  all  foreign  matter 
and  to  assure  a  well-formed  unit  of  full  cross- 
section.  The  concreting  shall  be  subject  to  the 
following  limitations. 

1 .  The  diameter  shall  not  vary  more  than  20% 
from  the  specified  value. 

2.  Concrete  shall  not  be  placed  through  water 
except  where  tremie  methods  are  approved. 

3.  When  depositing  concrete  from  the  top  of 
the  pile,  the  concrete  flow  shall  be  rapid  and 
continuous,  and  centered  at  the  top  of  the  pile. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


327 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


4.  After  filling  with  concrete,  the  top  ten  feet 
(3  m)  shall  be  thoroughly  rodded. 

5.  No  pile  shall  be  installed  within  a  distance 
of  nine  feet  (2.7  m)  from  a  pile  which  has  been 
filled  with  concrete  for  less  than  12  hours, 
unless  approved. 

1820.2  Augered  uncased  piles: 

1820.2.1  Definition:  An  augered  uncased  pile  is 
defined  as  a  structural  member  installed  utilizing 
a  hollow-stem  auger  no  less  than  12  inches 
(305  mm)  in  outside  diameter  which  extends  to 
satisfactory  bearing  materials  to  develop  support 
by  end  bearing  and/or  friction  in  those  materials. 

1820.2.2  Pile  diameter:  The  design  pile 
diameter  shall  be  taken  as  the  outside  diameter  of 
the  hollow  stem  auger. 

1820.2.3  Allowable  design  stresses:  Except  as 
provided  in  780  CMR  1817.5,  the  design  stresses 
shall  not  exceed  the  following  values: 

1.  For  compression  loads:  The  maximum 
allowable  design  stress  on  the  cement  grout  or 
concrete  shall  be  33%  of  the  specified  28-  day 
unconfined  compressive  strength,  but  not 
exceeding  1,600  psi  The  maximum  allowable 
design  stress  on  the  steel  reinforcing,  including 
permanent  steel  casing,  shall  be  40%  of  the 
minimum  specified  yield  strength,  but  not 
exceeding  24,000  psi. 

2.  For  tension  loads:  The  maximum  allowable 
design  tensile  stress  on  the  steel  reinforcing 
shall  be  60%  of  the  minimum  specified  yield 
strength.  The  allowable  design  tensile  stress 
on  the  cement  grout  shall  be  zero. 

1820.2.4  Reinforcement:  Reinforcement  shall 
be  as  required  in  780  CMR  1820.1.,  except 
reinforcement  may  be  placed  after  withdrawal  of 
the  auger  where  approved  by  the  code  official. 

1820.2.4.1  Concrete  cover:  The  minimum 
concrete  cover  shall  be  2'/2  inches  (64  mm)  for 
uncased  shafts  and  one  inch  (25  mm)  for  cased 
shafts. 

1820.2.4.2  Corrosion  protection:  Corrosion 
protection  shall  be  as  detailed  in  780  CMR 
1820.6.6. 

1820.2.5  Minimum  spacing:  The  minimum 
center-to-center  spacing  between  adjacent  piles 
shall  not  be  less  than  30  inches  (760  mm)  or  two 
times  the  pile  diameter,  whichever  is  greater.  In 
addition,  for  groups  of  friction  piles,  the  overall 
circumference  of  a  pile  group  shall  exceed  the 
sum  of  the  circumferences  of  all  of  the  individual 
piles  within  the  group. 

1820.2.6  Installation:  Augered  uncased  piles 
shall  be  formed  by  advancing  a  closed-end 
continuous-flight  hollow-stem  auger  of  uniform 
diameter  through  unsuitable  material  and  into  a 
satisfactory  bearing  material  followed  by  removal 


of  the  tip  closure  and  pumping  cement  grout  or 
concrete  through  the  hollow-stem  while  the 
hollow-stem  auger  is  extracted.  During 
advancement,  the  hollow-stem  auger  shall  be 
rotated  rapidly  such  that  the  material  through 
which  the  auger  is  being  advanced  is  removed  by 
the  auger  flights  and  is  not  displaced  laterally  by 
the  auger  During  withdrawal,  if  the  hollow  stem 
auger  is  rotated,  it  shall  be  rotated  in  a  positive 
(advancing)  direction. 

1  The  grout  or  concrete  shall  be  pumped 
under  continuous  pressure  and  in  one 
continuous  operation.  Grout  or  concrete  pump 
pressures  shall  be  measured  and  maintained  at 
all  times  sufficiently  high  to  offset  hydrostatic 
and  lateral  earth  pressures  The  rate  of 
withdrawal  of  the  auger  shall  be  carefully 
controlled  to  exclude  all  foreign  matter  and 
ensure  that  the  augered  hole  is  completely 
filled  with  grout  or  concrete  as  the  auger  is 
withdrawn.  The  actual  volume  of  grout  or 
concrete  pumped  into  each  hole  shall  be  equal 
to,  or  greater  than  ,  the  theoretical  volume  of 
the  augered  hole. 

2.  If  the  grouting  or  concreting  process  of  any 
pile  is  interrupted,  or  a  loss  of  concreting 
pressure  occurs,  the  pile  shall  be  redrilled  to  its 
original  depth  plus  six  inches  ( 1 52  mm)  (unless 
bearing  on  rock)  and  filled  from  the  bottom. 

3.  Augered  uncased  piles  shall  not  be  installed 
within  six  pile  diameters  (center-to-center)  of 
a  pile  filled  with  grout  or  concrete  less  than  24- 
hours  old  except  where  approved  by  the  code 
official. 

1820.2.7  Records:  The  owner  shall  engage  a 
registered  design  professional  to  monitor  the 
installation  of  augered  uncased  piles  in 
accordance  with  780  CMR  1816.13.  The  design 
professional  or  his  representative  shall  make  an 
accurate  record  of  the  installation  equipment  used, 
pile  dimensions,  grout  or  concrete  volumes, 
reinforcement,  interruptions  or  delays  in  pile 
installation,  and  all  other  pertinent  installation 
data 

1820.2.8  Instrumentation:  The  continuous- 
flight  auger  rig  utilized  to  install  augered  uncased 
piles  shall  be  equipped  with  data  logging 
equipment  that  automatically  monitors  and 
produces  a  real-time  printout  of  depth,  grout  or 
concrete  pressure,  grout  or  concrete  flow,  and  rate 
of  auger  withdrawal.  The  automatic  monitoring 
equipment  shall  immediately  indicate  to  the 
equipment  operator,  and  record  on  the  printed 
record,  any  instance  during  the  withdrawal  of  the 
hollow-stem  auger  where  the  rate  of  auger 
withdrawal  times  the  theoretical  pile  cross- 
sectional  area  exceeds  the  rate  of  grout  or 
concrete  placement.  A  printed  instrumentation 
readout  for  each  pile  shall  be  provided  to  the 


328 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


design  professional's  representative  upon 
completion  of  each  pile. 

1820.3  Driven  uncased  pile:  No  provisions. 

1820.4  Pressure-injected  footings:  (Enlarged  base 
piles) 

1820.4.1  Materials:  Concrete  shall  satisfy  the 
provisions  of  780  CMR  1820.1.1.  Compacted 
concrete  shall  have  a  zero  slump.  Reinforcement 
shall  be  as  provided  in  780  CMR  1820. 1.2. 

1820.4.2  Allowable    design    stresses:        The 

maximum  allowable  design  stress  on  shaft 
concrete  shall  be  33%  of  the  28-day  strength,  but 
not  exceeding  1,600  psi.  The  maximum  allowable 
design  stress  on  permanent  steel  casing,  if  at  least 
1/10-inch  (2.5  mm)  thick,  and  on  steel  reinforcing 
shall  be  40%  of  the  minimum  specified  yield 
strength,  but  not  exceeding  24,000  psi. 

1820.4.3  Installation:  The  installation  of 
pressure-injected  footings  shall  fulfill  the 
following  requirements: 

1820.4.3.1  Base: 

1 .  The  enlarged  base  of  a  pressure-injected 
footing  shall  be  formed  on  or  in  bearing 
materials  of  Classes  1  to  9  inclusive.  The 
Class  9  material  (fine  sand)  shall  have  a 
maximum  of  1 5%  by  weight  finer  than  the 
No.  200  mesh  sieve  and  shall  be  non-plastic, 
unless  satisfactory  load  test  results  or  other 
substantiating  data  are  submitted  to,  and 
approved  by,  the  code  official. 

2.  The  compacted  concrete  placement  shall 
be  in  measured  batches,  to  establish  impact 
energy  required  per  unit  volume  of  concrete. 
A  minimum  of  one  Standard  Batch  Volume 
of  concrete,  as  defined  in  Table  1820.4, 
shall  be  injected  in' the  base,  after  expulsion 
of  the  concrete  plug  or  boot  used  to  close 
the  tube  during  the  driving  process. 

1820.4.3.2  Shaft  installation: 

1820.4.3.2.1  Uncased  compacted-concrete 
shaft: 

1.  Concrete  shall  be  placed  at  zero 
slump,  in  small  batches,  and  shall  be 
compacted  in  place  in  a  controlled 
manner  as  the  drive-tube  is  withdrawn. 

2.  Pressure  injected  footings  formed 
through  soils  of  Classes  10  and  11, 
located  less  than  nine  feet  or  within  the 
heave  range  from  an  uncased  shaft,  shall 
be  pre-drilled  through  such  soil. 

3.  An  uncased  compacted-concrete  shaft 
shall  not  be  formed  through  very  soft  to 
soft  soils  of  Classes  10  and  1 1.  The  code 
official  may  waive  this  requirement  based 
upon  satisfactory  evidence  prepared  by  a 
registered  design  professional  that  the 


soil  has  sufficient  strength  for  proper 
shaft  construction. 

4.  A  suitable  method  shall  be  employed 
by  the  contractor  and  the  design 
professional  to  verify  and  record  that  the 
entire  length  of  the  shaft  is  completely 
filled  with  concrete.  Such  means  shall 
include  the  ability  to  determine  the 
incremental  volume  of  concrete  installed 
in  relation  to  the  calculated  shaft  volume. 

1820.4.3.2.2Uncased  high-slump  concrete 

shaft: 

1.  Concrete  shall  be  placed  at  not  less 
than  eight-inch  slump,  except  that  slump 
as  low  as  four  inches  may  be  allowed  if 
adequate  vibration  is  applied  to  the  drive- 
tube  during  the  entire  withdrawal  process. 
During  withdrawal,  the  level  of  concrete 
within  the  tube  shall  have  a  positive 
differential  head  over  external  soil  and 
water  pressures  at  all  times. 

2.  The  shaft  shall  be  provided  with  full- 
length  reinforcing  steel  anchored  in  the 
enlarged  base.  At  a  minimum,  provide  a 
cage  with  four,  full  length,  number  five 
reinforcing  bars  evenly  spaced  near  the 
shaft  perimeter. 

3.  Pressure  injected  footings  located  less 
than  nine  feet  (2.7  m)  from  a  completed 
uncased  high-slump  shaft  shall  not  be 
installed  until  at  least  12  hours  after  shaft 
pour. 

4.  A  suitable  method  shall  be  employed 
by  the  contractor  and  the  design 
professional  to  verify  and  record  that  the 
entire  length  of  the  shaft  is  completely 
filled  with  concrete.  Such  means  shall 
include  the  ability  to  determine  the 
incremental  volume  of  concrete  installed 
in  relation  to  the  calculated  shaft  volume. 

1820.4.3.2.3  Cased  shaft: 

1.  The  permanent  metal  casing  shall  be 
fastened  to  the  enlarged  base  in  such  a 
manner  that  the  two  will  not  separate. 

2.  Concrete  shall  be  placed  in  the  same 
manner  as  for  cased  poured  concrete 
piles.  The  requirements  of  780  CMR 
1820.1.3  shall  apply. 

1820.4.4  Loadbearing  capacity: 

1 .  Pile  loadbearing  capacity  shall  be  verified 
by  load  tests  as  required  in  780  CMR  1817.4. 

2.  For  loads  up  to  120  tons,  the  allowable  load 
may  be  computed  by  the  following  formula: 

R-  BxEr% 


Where: 

R  =  allowable  load  in  pounds; 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


329 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


B  =average  number  of  blows  required  to 

inject  one  cubic  foot  of  concrete,  during 

injectio.i  of  the  last  batch; 

E  =Energy  per  blow  in  foot-pounds; 

C  =constant;  and 

V  =total  volume  of  base  concrete  in  cubic 

feet. 

The  values  of  R  E,  and  C  shall  conform  to 
Table  1820.4  unless  other  values  are 
determined  by  load  test,  in  which  case  the 
latter  values  shall  control.  Use  of  Table  1820.4 
is  limited  by  the  provisions  of  780  CMR 
1817.4. 

The  value  ofV  shall  include  an  allowance  of 
one  Standard  Batch  Volume  of  concrete,  if 
concrete  is  used  in  the  tube  during  the  driving 
process,  plus  the  additional  volume  of  concrete 
injected  during  formation  of  the  base. 
3.  During  injection  of  the  last  batch  of  concrete 
in  the  base,  the  height  of  concrete  within  the 
drive  tube  shall  not  be  more  than  Vb  of  the 
drive-tube  inside  diameter. 


TABLE  1820.4 

R 
(tons) 

Energy,  E 
(foot-pounds) 

C 

Standard  Batch 
Volume 
(cubic  feet) 

over  100 
51  to  100 

25  to  50 

140,000 
100,000 
60.000 

18 

:.  is 

30 

5 

:           5 

1820.4.5  Loading:  The  load  on  pressure-injected 
footings  shall  be  limited  by  the  provisions  of 
780  CMR  1817.8  except  that  the  circumscribing 
polygon  shall  start  at  the  junction  of  the  shaft  and 
the  enlarged  base,  and  the  bearing  area  shall  be 
taken  at  planes  six  feet  or  more  below  the 
junction,  or  at  the  top  of  weaker  material, 
whichever  is  higher. 

1820.4.6  Spacing:  The  center-to-center  spacing 
of  pressure-injected  footings  with  uncased  shafts 
shall  be  not  less  than  2'/2  times  the  outside 
diameter  of  the  drive  tube  and  not  less  than  VA 
feet.  The  center-to-center  spacing  of  pressure- 
injected  footings  with  cased  shafts  shall  be  not 
less  than  three  times  the  shaft  diameter. 

1820.5  Cased  poured  concrete  piles:  Steel-cased 
piles  shall  comply  with  the  requirements  of 
780  CMR  1820.5.1  through  1820.5.4. 

1820.5.1  Materials:  Concrete  shall  satisfy  the 
provisions  of  780  CMR  1 820. 1.1.  Pile  shells  or 
casings  shall  be  of  steel  and  shall  be  sufficiently 
strong  to  resist  collapse  and  sufficiently  water 
tight  to  exclude  any  foreign  materials  during  the 
placing  of  concrete.  The  shape  of  the  pile  may  be 
cylindrical,  or  conical,  or  a  combination  thereof, 
or  it  may  be  a  succession  of  cylinders  of  equal 
length,  with  the  change  in  diameter  of  adjoining 
cylinders  not  exceeding  one  inch. 


1820.5.2  Allowable  design  stresses:  The  load  on 
cased  poured  concrete  piles  shall  be  as  provided 
in  780  CMR  1817.0  and  shall  not  exceed  the  load 
computed  on  the  basis  of  33%  of  the  28-day 
strength  of  the  concrete,  nor  1,600  psi  when 
applied  to  the  cross-sectional  area  computed  on 
the  following  basis: 

1.  For  metal-cased  piles  driven  to  and  into 
materials  of  Classes  1  to  4  inclusive,  using  the 
diameter  measured  one  foot  (0.3  m)  above  the 
point,  except  that  when  the  rock  is  immediately 
overlain  by  a  bearing  stratum  consisting  of  one 
or  a  combination  of  bearing  materials  of 
Classes  5,  6,  and  7,  using  the  diameter  at  the 
surface  of  the  bearing  stratum. 

2.  For  metal-cased  piles,  driven  through 
compressible  materials  including  Classes  10 
and  1 1  and  into  a  bearing  stratum  consisting  of 
one  or  a  combination  of  bearing  materials  of 
Classes  5-9  inclusive,  using  the  diameter  at  the 
surface  of  the  bearing  stratum. 

1820.5.3  Installation:  Piles  shall  have  steel  shells 
or  casings  which  are  mandrel-driven  their  full 
length  in  contact  with  the  surrounding  soil,  left 
permanently  in  place  and  filled  with  concrete. 
The  requirements  of  780  CMR  1820.1.3  shall 
apply. 

1820.6  Small  diameter  grouted  piles: 

1820.6.1  General:  780  CMR  1820.6  covers 
grouted  cast-in-place  piles  which  are  less  than  12 
inches  (305  mm)  in  diameter  and  in  which  all  or 
a  portion  of  the  pile  is  cast  directly  against  the  soil 
without  permanent  casing. 

1820.6.2  Materials:  Concrete  or  sand-cement 
grout  shall  satisfy  the  provisions  of  780  CMR 
1820.1.1. 

1820.6.3  Allowable  load:  The  load  on  small 
diameter  grouted  piles  shall  not  exceed  the 
allowable  load  computed  on  the  basis  of  the 
allowable  stresses  given  in  780  CMR  1820.2.3 
and  the  requirements  of  780  CMR  1820.6.3. 1  and 
1820.6.3.2. 

1820.6.3.1  Minimum  reinforcing:  The  steel 
reinforcing  shall  be  designed  to  carry  the 
following  minimum  percentage  of  the  design 
compression  load: 

1.  For  a  pile  or  a  portion  of  a  pile  grouted 
inside  a  temporary  casing,  grouted  inside  a 
hole  drilled  into  rock,  or  grouted  with  a 
hollow-stem  auger,  the  reinforcing  steel 
shall  be  designed  to  carry  not  less  than  40% 
of  the  design  compression  load. 

2.  For  a  pile  or  a  portion  of  a  pile  grouteJ 
in  an  open  drill  hole  without  temporary  or 
permanent  casing  or  grouted  within 
materials  of  Classes  1  through  5,  the  pile 
shall  be  designed  to  carry  the  entire  design 


330 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


compression  load  on  the  reinforcing  steel. 
If  a  steel  pipe  section  is  used  for  reinforcing, 
any  portion  of  the  cement  grout  enclosed 
within  the  pipe  may  also  be  included  at  the 
allowable  stress  for  the  grout. 

1820.6.3.2  Load  test:  For  all  design  loads,  the 
allowable  load  shall  be  determined  by  load 
tests  in  accordance  with  780  CMR  1817.4. 
Load  tests  may  be  waived  by  the  code  official 
based  on  substantiating  data  and  analyses 
prepared  by  a  registered  design  professional 

1820.6.3.3  Alternative  load  test  procedure 
for  friction  piles:  For  piles  designed  as  friction 
piles,  the  friction  capacity  in  compression  may 
be  verified  by  load  testing  in  tension.  The 
tension  load  test  shall  be  performed  in 
accordance  with  780  CMR  1817.7,  with  the 
following  exceptions: 

1.  The  test  pile  must  be  cased  or  left 
ungrouted  down  to  the  top  of  the  bearing 
stratum  in  a  manner  which  will  ensure  that 
no  friction  resistance  is  developed  above 
the  bearing  stratum. 

2.  The  maximum  design  load  shall  be 
taken  as  50%  of  the  applied  test  load  which 
results  in  a  movement  under  load  of  Vi  inch 
(13  mm)  at  the  pile  tip.  The  movement  at 
the  pile  tip  shall  be  a.)  measured  directly  by 
a  tell-tale  or  b.)  computed  by  deducting  the 
theoretical  elastic  elongation  of  the  pile 
from  the  displacement  measured  at  the  top 
of  the  pile. 

1820.6.4  Installation:  The  pile  may  be  formed  in 
a  hole  advanced  by  rotary  or  rotary  percussive 
drilling  methods  (with  or  without  temporary- 
casing),  by  a  hollow-stem  auger,  or  by  driving  a 
temporary  casing.  The  pile  shall  be  grouted  with 
a  fluid  cement  grout.  The  grout  shall  be  pumped 
through  a  tremie  pipe  extending  to  the  bottom  of 
the  pile  until  grout  of  suitable  quality  returns  at 
the  top  of  the  pile. 

The  following  requirements  apply  to  specific 
installation  methods: 

1 .  Piles  grouted  with  temporary  casing:  For 
piles  grouted  inside  a  temporary  casing,  the 
reinforcing  steel  shall  be  inserted  prior  to 
withdrawal  of  the  casing.  The  casing  shall  be 
withdrawn  in  a  controlled  manner  with  the 
grout  level  maintained  at  the  top  of  the  pile,  to 
ensure  that  the  grout  completely  fills  the  drill 
hole.  During  withdrawal  of  the  casing,  the 
grout  level  inside  the  casing  shall  be  monitored 
to  check  that  the  flow  of  grout  inside  the  casing 
is  not  obstructed. 

2.  Piles  grouted  without  temporary  casing: 
For  a  pile  or  portion  of  a  pile  grouted  in  an 
open  drill  hole  in  soil  without  temporary 
casing,  the  minimum  design  diameter  of  the 
drill  hole  shall  be  verified  by  a  suitable  device 


immediately  prior  to  grouting.  The  reinforcing 
steel  shall  be  inserted  prior  to  grouting 

3.  Piles  grouted  with  hollow-stem  augers:  For 
piles  installed  with  a  hollow-stem  auger,  the 
grout  shall  be  pumped  under  continuous 
pressure,  and  the  rate  of  withdrawal  of  the 
auger  shall  be  carefully  controlled  to  ensure 
that  the  hole  is  completely  filled  with  grout  as 
the  auger  is  withdrawn.  The  actual  volume  of 
grout  pumped  for  each  one  foot  (0.3  m)  of 
withdrawal  of  the  auger  shall  be  recorded  and 
must  be  equal  to  or  greater  than  the  theoretical 
volume.  The  reinforcing  steel  shall  be  inserted 
prior  to  withdrawal  of  the  auger. 

4.  For  piles  designed  for  end  bearing,  a 
suitable  means  shall  be  employed  to  verify  that 
the  bearing  surface  is  properly  cleaned  prior  to 
grouting. 

5.  Subsequent  piles  shall  not  be  drilled  or 
driven  near  piles  that  have  been  grouted  until 
the  grout  has  had  sufficient  time  to  harden. 

1820.6.5  Pile  diameter:  The  design  pile  diameter 
shall  be  taken  as: 

1 .  The  outside  diameter  of  the  temporary 
casing;  or 

2.  The  diameter  of  a  full  circumferential  drill 
bit  attached  to  the  bottom  of  the  temporary 
casing;  or 

3.  The  outside  diameter  of  the  hollow-stem 
auger,  or 

4.  The  borehole  diameter  verified  by  suitable 
measurements  made  immediately  prior  to 
grouting. 

1820.6.6  Corrosion  protection: 

1.  Minimum  grout  cover:  Where  steel 
reinforcing  is  not  enclosed  inside  a  permanent 
casing,  centralizers  shall  be  provided  on  the 
reinforcing  to  ensure  a  minimum  grout  cover  of 
one  inch  (25  mm)  in  soil  and  !4  inch  (13  mm) 
in  rock.  Grout  cover  requirements  may  be 
reduced  when  the  reinforcing  steel  is  provided 
with  a  suitable  protective  coating. 

2.  Permanent  steel  casing  that  is  used  as 
structural  reinforcing  shall  be  protected  in 
accordance  with  the  provisions  of  780  CMR 
1816.4.2. 

3.  For  piles  subjected  to  sustained  tension 
loading  in  corrosive  environments,  the 
reinforcing  steel  shall  be  protected  by  a 
suitable  protective  coating  or  encapsulation 
method. 

1820.6.7  Records  The  owner  shall  engage  a 
registered  design  professional  to  observe  the 
installation  of  the  piles  in  accordance  with 
780  CMR  1816  13.  The  design  professional  or 
his  representative  shall  make  an  accurate  record 
of  the  installation  equipment  used,  pile 
dimensions,  grouting  volumes  and  procedures 
used  and  all  other  pertinent  installation  data. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


331 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  1821.0  PRECAST  CONCRETE 
PDJES 

1821.1  Design  and  manufacture:  All  piles  shall  be 
designed  and  manufactured  in  accordance  with 
accepted  engineering  practice  to  resist  all  stresses 
induced  by  handling,  driving  and  service  loads  The 
minimum  lateral  dimension  shall  be  ten  inches 
(254  mm).  All  corners  of  square  piles  shall  be 
chamfered  Longitudinal  steel  shall  be  arranged  in 
a  symmetrical  pattern  and  shall  be  laterally  tied  with 
steel  ties  or  wire  spiral  spaced  not  more  than  three 
inches  (76  mm)  apart,  center  to  center,  for  a  distance 
of  two  feet  (610  mm)  from  the  ends  of  the  pile;  and 
not  more  than  six  inches  (152  mm)  elsewhere  except 
that  at  the  ends  of  each  pile,  the  first  five  ties  or 
spirals  shall  be  spaced  one  inch  (25  mm)  center  to 
center  When  driven  to  or  into  bearing  materials  of 
Classes  1  to  6  inclusive,  or  through  materials 
containing  boulders,  piles  shall  have  metal  tips  of 
approved  design. 

1821.1.1  Installation:  All  piles  shall  be  handled 
and  driven  so  as  not  to  cause  injury  or 
overstressing  which  affects  durability  or  strength 

1821.2  Reinforced  piles:  Reinforced  precast 
concrete  piles  shall  conform  to  780  CMR  1821.2. 1 
through  1821.2.5. 

1821.2.1  Design:  The  minimum  amount  of 
longitudinal  reinforcement  shall  be  2%  of  the 
concrete  section  and  shall  consist  of  at  least  four 
bars. 

1821.2.2  Material:  All  concrete  shall  have  a 
28-day  specified  compressive  strength  (/'c)  of  not 
less  than  4,000  psi  (2.81  kg/mm2). 

1821.2.3  Allowable  stress:  The  allowable 
compressive  stress  in  the  concrete  shall  not 
exceed  33%  of  the  28-day  specified  compressive 
strength  (/'J  nor  1,600  psi  applied  to  the  gross 
cross-sectional  area  of  the  pile. 

1821.2.4  Concrete  cover:  All  pile  reinforcement 
shall  have  a  concrete  cover  of  not  less  than  two 
inches  (5 1  mm),  except  that  piles  exposed  to  sea 
water  shall  have  a  minimum  protective  concrete 
cover  of  three  inches  (76  mm). 

1821.2.5  Installation:  A  precast  concrete  pile 
shall  not  be  driven  before  the  concrete  has 
attained  a  compressive  strength  of  at  least  3,000 
psi  (2. 1 1  kg/mm2),  but  not  less  than  such  strength 
sufficient  to  withstand  handling  and  driving 
forces. 

1821.3  Prestressed  piles:  Prestressed  concrete  piles 
shall  conform  to  the  requirements  of  780  CMR 
1821.3.1  through  1821.3.6. 

1821.3.1  Design:  The  effective  prestress  in  the 
pile  shall  not  be  less  than  700  psi  (0.49  kg/mm2). 


1821.3.2  Material:  Prestressing  steel  shall 
conform  to  ASTM  A416  listed  in  Appendix  A. 
All  concrete  shall  have  a  28-day  specified 
compressive  strength  (/'J  of  not  less  than  5,000 
psi  (3.52  kg/mm2). 

1821.3.3  Allowable    stress:     The    maximum 

allowable  design  compressive  stress  (/c)  in 
concrete  shall  be  determined  as  follows: 

/c  =  0.33  /',  -  0.27  /^ 
where  f'c  is  the  28-day  compressive  strength  and 
/^  is  the  effective  prestress  on  the  gross  area  of 
the  pile  section,  however,   0.33  f\  shall  not 
exceed  1,600  psi 

1821.3.4  Installation:  A  prestressed  pile  shall  not 
be  driven  before  the  concrete  has  attained  a 
compressive  strength  of  at  least  4,000  psi  (2.81 
kg/mm2),  but  not  less  than  such  strength 
sufficient  to  withstand  handling  and  driving 
forces. 

1821.3.5  Pile      cap      seismic      connection: 

Prestressed  pile  connection  to  the  pile  cap  shall  be 
in  accordance  with  the  requirements  of  780  CMR 
1816.11  1  or  by  extension  of  the  pile  reinforcing 
strand  into  the  pile  cap  The  embedment  into  the 
pile  cap  shall  develop  the  strength  of  the 
reinforcing     strand  Prestressed     pile     cap 

connections  in  buildings  assigned  to  Seismic 
Performance  Category  D,  in  accordance  with 
780  CMR  1612.2.7,  shall  not  be  by  development 
of  exposed  strand. 

1821.3.6  Spiral  seismic  reinforcing:  The  upper 
two  feet  of  the  pile  immediately  below  the  pile 
cap  shall  have  No.  3  ties  minimum  at  not  over 
four-inch  spacing,  or  equivalent  spirals.  The 
spiral  reinforcement  in  prestressed  piles  for 
buildings  assigned  to  Seismic  Performance 
Category  D,  in  accordance  with  780  CMR 
1612.2.7,  shall  not  be  less  than  0.6%  for  the  full 
length  of  the  pile  where  subjected  to  vertical  loads 
only  or  where  the  design  bending  moment  does 
not  exceed  20%  of  the  unfactored  ultimate 
moment  capacity  at  balanced  strain  conditions 
computed  in  accordance  with  ACI  318  listed  in 
Appendix  A - 

780  CMR  1822.0  TIMBER  PRES 

1822.1  Materials:  Round  timber  piles  shall  conform 
to  ASTM  D25  listed  in  Appendix  A.  Round  timber 
piling  shall  be  new  longleaf,  shortleaf,  loblolly  or 
slash  species  of  Southern  pine,  oak,  Douglas  fir  or 
other  woods  of  similar  strength  and  physical 
characteristics. 

1822.2  Preservative  treatment:  Timber  piles  used 
to  support  permanent  structures  shall  be  pressure 
treated  in  accordance  with  AWPA  C3  listed  in 
Appendix  A  for  round  timber  piles.  Preservative- 
treated  timber  piles  shall  be  subject  to  a  quality 
control    program    administered    by    an    approved 


332 


780  CMR  -  Sixth  Edition     corrected-  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

FOUNDATIONS  AND  RETAINING  WALLS 


agency.  Pile  cutoffs  shall  be  treated  in  accordance 
with  AWPA  M4  listed  in  Appendix  A. 

1822.3  Allowable  load: 

1822.3.1  Allowable  stress:  The  allowable  stress 
in  the  timber  shall  not  exceed  1,000  psi  in 
compression  at  the  critical  cross-sectional  area 
taken  at  the  top  of  the  bearing  stratum  Piles 
designed  for  end  bearing  on  materials  of  Classes  1 
through  5  shall  be  designed  for  a  maximum  stress 
of  500  psi  in  compression  on  the  pile  cross- 
sectional  area  at  the  tip. 

1822.3.2  Maximum  Load:  The  load  on  timber 
piles  shall  not  exceed  the  allowable  load  specified 
in  780  CMR  1817.0  nor  35  tons,  whichever  is 
smaller 

1822.3.3  Minimum  dimensions  Timber  piles 
shall  be  sized  to  conform  to  the  minimum  tip  sizes 
as  specified  in  ASTM  D25  but  no  less  than  six 
inches  (152  mm)  in  diameter  at  the  tip. 

1822.4  Precautions  during  driving: 

1822.4.1  Hammer  energy  Pile  hammer  energy 
shall  be  selected  to  prevent  damage  to  the  pile,  but 
in  no  case  shall  the  maximum  hammer  energy,  as 
rated  by  the  manufacturer,  exceed  18,000  ft.  lbs. 
For  end  bearing  piles,  on  materials  of  Class  1 
through  5.  the  maximum  hammer  energy  shall  be 
reduced. 

1822.4.2  Driving  resistance:  Driving  shall  be 
stopped  immediately  when  abrupt  high  resistance 
to  penetration  is  encountered.  Any  sudden 
decrease  in  driving  resistance  of  an  end-supported 
timber  pile  shall  be  investigated  with  regard  to  the 
possibility  of  damage.  If  the  sudden  decrease  in 
driving  resistance  cannot  be  correlated  to 
loadbearing  data,  the  pile  shall  be  removed  for 
inspection  or  rejected. 

780  CMR  1823.0  COMPOSITE  PILES 

1823.1  Design:  Composite  piles  consisting  of  two  or 
more  approved  pile  types  shall  be  designed  to  meet 
the  conditions  of  installation. 

1823.2  Limitation  of  load:  The  maximum  allowable 
load  shall  be  limited  by  the  capacity  of  the  weakest 
section  incorporated  in  the  pile. 

1823.3  Splices:  Splices  between  concrete  and  steel 
or  wood  sections  shall  be  designed  to  prevent 
separation  both  before  and  after  the  concrete  portion 
has  set,  and  to  insure  the  alignment  and  transmission 
of  the  total  pile  load.  Splices  shall  be  designed  to 
resist  uplift  caused  by  upheaval  during  driving  of 
adjacent  piles,  and  shall  develop  the  fiill 
compressive  strength  and  not  less  than  50%  of  the 
tension  and  bending  strength  of  the  weaker  section. 


780  CMR  1824.0  CONCRETE-FILLED  PIPE 
WITH  STEEL  CORE  CAISSONS 

1824.1  Construction:  These  units  shall  consist  of  a 
shaft  section  of  concrete-filled  pipe  extended  to  and 
firmly  seated  in  bedrock  of  Classes  1  or  2  with  an 
uncased  socket  drilled  into  the  bedrock  which  is 
filled  with  cement  grout.  A  steel  core  shall  be 
centered  in  the  shaft  and  shall  extend  through  the 
cement  grout  to  the  bottom  of  the  socket 

1824.2  Rock  socket:  A  socket,  approximately  the 
inside  diameter  of  the  pipe,  shall  be  made  in  bedrock 
of  Classes  1  or  2  to  a  depth  that  will  assure  load 
transfer  when  computed  for  bearing  on  the  bottom 
surface  of  the  socket  in  accordance  with  780  CMR 
1803.0,  1807.0  and  1817.0  acting  together  with  a 
bond  stress  on  the  perimeter  surface  of  the  socket. 
The  socket  design  stress  shall  be  determined  by  a 
registered  design  professsional  based  upon 
foundation  investigation  study  in  accordance  with 
780  CMR  1816,  but  in  no  case  will  the  design  bond 
stress  on  the  perimeter  of  the  socket  exceed  200  psi. 
Load  tests,  in  accordance  with  780  CMR  1817.4, 
may  be  required  by  the  code  official  if  foundation 
investigation  data  are  judged  insufficient  to  verify 
the  selected  bond  stress.  The  minimum  socket  depth 
shall  be  at  least  equal  to  the  diameter  of  the  pipe. 
Before  placement  of  concrete,  the  socket  and  pipe 
shall  be  thoroughly  cleaned  and  the  rock  inspected 
by  a  registered  design  professional  or  his  qualified 
representative. 

1824.3  Seismic  reinforcement:  All  piles  designed 
under  780  CMR  1824.0  shall  have  seismic 
reinforcement  required  by  780  CMR  1820.1.2.1. 

1824.4  Material:  Pipe  and  steel  cores  shall  conform 
to  the  material  requirements  in  780  CMR  1818.0. 
Pipe  shall  have  a  minimum  diameter  of  18inches 
(457  mm)  and  a  minimum  wall  thickness  of  %  inch 
(9.5  mm)  and  shall  be  fitted  with  a  suitable  steel 
driving  shoe  welded  to  the  bottom  of  the  pipe.  All 
concrete  shall  have  a  28-day  specified  compressive 
strength  (/'^  of  not  less  than  4,000  psi  (2.81 
kg/mm  ).  The  concrete  mix  shall  be  designed  and 
proportioned  so  as  to  produce  a  cohesive  workable 
mix  with  a  slump  of  four  inches  (102  mm)  to  six 
inches  (152  mm). 

1824.5  Structural  core:  The  gross  cross-sectional 
area  of  the  structural  steel  core  shall  not  exceed  25% 
of  the  gross  area  of  the  caisson.  The  minimum 
clearance  between  the  structural  core  and  the  pipe 
shall  be  two  inches  (5 1  mm).  If  cores  are  to  be 
spliced,  the  ends  shall  be  milled  or  ground  to 
provide  full  contact  and  shall  be  full-depth  welded 

1824.6  Allowable  stress:  The  allowable  design 
compressive  stresses  shall  not  exceed  the  following: 
concrete,  0.33  /'  ;  steel  pipe,  0.35  /  ■  and  structural 
steel  core,  0.50  /_,. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1824.7  Installation:  The  rock  socket  and  pile  shall 
be  thoroughly  cleaned  of  all  foreign  materials  before 
filling  with  cement  grout  and  concrete.  Steel  cores 
shall  be  bedded  in  cement  grout  at  the  base  of  the 
rock  socket. 

1824.8  Spacing:  The  minimum  center-to-center 
spacing  shall  be  not  less  than  2Vz  times  the  outside 
diameter  of  the  steel  shell. 


overturning,  sliding,  excessive  foundation  pressure 
and  water  uplift.  Retaining  walls  shall  be  designed 
to  resist  seismic  loads  in  accordance  with  780  CMR 
1612.49. 

1825.3  Hydrostatic  pressure:  Unless  drainage  is 
provided,  the  hydrostatic  head  of  the  water  pressure 
shall  be  assumed  to  be  equal  to  the  height  of  the 
wall. 


780  CMR  1825.0  RETAINING  WALLS 

1825.1  General:  Walls  built  to  retain  or  support  the 
lateral  pressure  of  earth  or  water  or  other 
superimposed  loads  shall  be  designed  and- 
constructed  of  approved  masonry,  reinforced 
concrete,  steel  sheet  piling  or  other  approved 
materials  within  the  allowable  stresses  specified  in 
780  CMR  23 11 .7. 

1825.2  Design:  Retaining  walls  shall  be  designed  to 
resist  the  pressure  of  the  retained  material,  including 
both  dead  and  live  load  surcharges  to  which  such 
walls  are  subjected,  and  to  insure  stability  against 


1825.4  Coping:  All  masonry  retaining  walls,  other 
than  reinforced  concrete  walls,  shall  be  protected 
with  an  approved  coping. 

1825.5  Guards:  Where  retaining  walls  with 
differences  in  grade  level  on  either  side  of  the  wall 
in  excess  of  four  feet  (1.2  m)  are  located  closer  than 
two  feet  (0.6  m)  to  a  walk.  path,  parking  lot  or 
driveway  on  the  high  side,  such  retaining  walls  shall 
be  provided  with  guards  that  are  constructed  in 
accordance  with  780  CMR  1021.0  or  other  approved 
protective  measures. 


334 


780  CMR  -  Sixth  Edition     corrected-  9/19/97  (Effective  2/28/97) 


CHAPTER  19 


CONCRETE 


780  CMR  1901.0  CONCRETE  DESIGN 
STANDARDS 

1901.1  Reinforced    and    prestressed    concrete: 

Structural  members  of  reinforced  concrete,  including 
prestressed  concrete,  shall  be  designed  and 
constructed  in  accordance  with  the  provisions  of 
780  CMR19  and  ACI  318  listed  in  Appendix  A, 
hereafter  referred  to  in  780  CMR  19  as  ACI  318. 

1901.2  Plain  concrete:  Structural  members  of  plain 
concrete  shall  be  designed  and  constructed  in 
accordance  with  the  provisions  of  780  CMR  19  and 
ACI  318.1  listed  in  Appendix  A.  Concrete  that  is 
either  unreinforced  or  contains  less  reinforcement 
than  the  minimum  specified  for  reinforced  concrete 
by  ACI  318  shall  be  classified  as  plain  concrete. 
Plain  concrete  shall  not  be  used  for  structural 
members  where  special  design  considerations  are 
required  for  blast  forces,  unless  specifically 
approved. 

780  CMR  1902.0  DEFINITIONS 
1902.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  19  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Admixture:  Material  other  than  water,  aggregate  or 
hydraulic  cement,  used  as  an  ingredient  of 
concrete  and  added  to  concrete  before  or  during 
mixing  to  modify  the  properties  of  the  concrete. 

Cementitious  material:  A  material  specified  in 
780  CMR  1906.0  which  has  cementing  value 
when  used  in  concrete  either  by  itself,  such  as 
Portland  cement  or  blended  hydraulic  cements,  or 
when  used  in  combination  with  portland  cement 
or  blended  hydraulic  cement,  such  as  fly  ash,  raw 
or  calcined  natural  pozzolans  or  ground- 
granulated  blast-furnace  slag. 

Concrete:  A  mixture  of  portland  cement  or  any 
other  hydraulic  cement,  fine  and  course 
aggregates  and  water,  with  or  without  admixtures, 
of  such  proportions  and  manipulation  as  to  meet 
specific  requirements. 

Concrete,  reinforced:  Concrete  with  no  less 
reinforcement  than  required  by  780  CMR 
prestressed  or  nonprestressed,  and  designed  on  the 
assumption  that  the  two  materials  act  together  in 
resisting  forces  (see  780  CMR  1901.1). 

Member 

Primary.  Any  member  of  the  structural  frame  of 
a  building  or  structure  used   as  a  column  or 


grillage  beam,  or  to  support  masonry  walls  and 
partitions,  including  trusses,  isolated  lintels 
spanning  an  opening  of  eight  feet  (2438  mm)  or 
more,  and  any  other  member  required  to  brace  a 
column  or  a  truss. 

Secondary:  Any  member  of  the  structural 
framework  other  than  a  primary  member, 
including  fill-in  beams  of  floor  systems. 

780  CMR  1903.0  SEISMIC  REQUIREMENTS 
FOR  REINFORCED  CONCRETE 

1903.1  General:  The  design  and  construction  of 
reinforced  concrete  components  that  resist  seismic 
forces  shall  conform  to  the  requirements  of 
780  CMR  1903.0  and  ACI  318  except  as  modified 
by  780  CMR  1903.1.1. 

1903.1.1  Modifications  to  ACI  318:  The  sections  of 
ACI  318  shall  be  modified  as  indicated  in  780  CMR 
1903.1.1  items  1  through  13. 

1.  Modify  Section  8.1.2  to  read:  "except  where 
load  combinations  of  780  CMR  1616,  including 
seismic  forces,  are  used,  design  of  nonprestressed 
reinforced  concrete  members  using  Appendix  A, 
Alternate  Design  Method,  is  permitted." 

2.  Replace  ACI  318  Section  9.2.3  with  780  CMR 
1616. 

3 .  Add  the  following  definitions  to  Section  21.1 
of  ACI  318: 

"Confined  region:  That  portion  of  a  reinforced 
concrete  component  in  which  the  concrete  is 
confined  by  closely  spaced  special  transverse 
reinforcement  restraining  the  concrete  in 
directions  perpendicular  to  the  applied  stress." 

"Joint:  That  portion  of  a  column  bounded  by  the 
highest  and  lowest  surfaces  of  the  other 
members  framing  into  it." 

"Special  transverse  reinforcement:  Reinforcement 
composed  of  spirals,  closed  stirrups,  or  hoops 
and  supplementary  cross  ties  provided  to 
restrain  the  concrete  and  qualify  the  portion  of 
the  component,  where  used,  as  a  confined 
region." 

4.  Replace  ACI  318  Sections  21.2.1.3  and 
21.2.1.4  with  the  requirements  of  780  CMR 
1903.3  through  1903.6. 

5.  Modify  Section  21.2.1.5  to  read:  "A 
reinforced  concrete  structural  system  not 
satisfying  the  requirements  of  780  CMR  19, 
including  those  composed  of  precast  elements,  is 
allowed  if  it  is  demonstrated  by  experimental 
evidence  and  analysis  that  the  proposed  system 
will  have  strength  and  toughness  equal  to  or 
exceeding    that    provided    by    a    comparable 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


335 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


monolithic  reinforced  concrete  structure  satisfying 
780  CMR  19." 

6.  Add  the  following  to  the  end  of  Section 
21.2.5.1:  "Post-tensioning  tendons  are  allowed  in 
flexural  members  of  frames  provided  the  average 
prestress  (Jpc)  calculated  for  an  area  equal  to  the 
member's  shortest  cross-sectional  dimension 
multiplied  by  the  perpendicular  dimension,  does 
not  exceed  350  psi." 

7.  Add  a  new  Section  21.3.2.5  to  read:  "For 
members  in  which  prestressing  tendons  are  used 
together  with  ASTM  A706  or  A615  (Grades  40  or 
60)  reinforcement  to  resist  earthquake-induced 
forces,  prestressing  tendons  shall  not  provide 
more  than  one-quarter  of  the  strength  for  both 
positive  moments  and  negative  moments  at  the 
joint  face.  Anchorages  for  tendons  shall  be 
demonstrated  to  perform  satisfactorily  for  seismic 
loadings.  Anchorage  assemblies  shall  withstand, 
without  failure,  a  minimum  of  50  cycles  of 
loading  ranging  between  40  and  85%  of  the 
minimum  specified  strength  of  the  tendon. 
Tendons  shall  extend  through  exterior  joints  and 
be  anchored  at  the  exterior  face  of  the  joint  or 
beyond." 

8.  Modify  Section  21.3.3.4  to  read:  "Where 
hoops  are  not  required,  stirrups  with  135-degree 
or  greater  hooks  with  six  bar  diameter  but  not  less 
than  three-inch  extensions  shall  be  located 
throughout  the  length  of  the  member  and  spaced 
not  more  than  one-half  the  distance  from  the 
extreme  compression  fiber  to  the  centroid  of 
tension  reinforcement  (d)." 

9.  Add  a  new  Section  21.4.4.7  to  read:  "At  any 
section  where  the  nominal  strength  {§Pn)  of  the 
column  is  less  than  the  sum  of  the  shear  (Vc) 
computed  in  accordance  with  Section  21.4.5.1  for 
all  of  the  beams  framing  into  the  column  above 
the  level  under  consideration,  special  transverse 
reinforcement  shall  be  provided.  For  beams 
framing  into  opposite  sides  of  the  column,  the 
moment  components  are  allowed  to  be  assumed  to 
be  of  opposite  sign.  For  determination  of  the 
nominal  strength  (Pn)  of  the  column,  these 
moments  are  allowed  to  be  assumed  to  result  from 
the  deformation  of  the  frame  in  any  one  principal 
axis." 

10.  Add  to  the  end  of  Section  21.6.1:  "A  cast-in- 
place  topping  on  a  precast  floor  system  is  allowed 
to  serve  as  a  diaphragm  provided  that  the  cast-in- 
place  topping  is  proportioned  and  detailed  to 
resist  the  design  shear  forces.  Where  untopped 
precast  elements  are  used  as  diaphragms,  the 
strength  reduction  factor  (<£)  for  connections 
between  elements  shall  be  0.5  except  that  for 
connection  elements  that  form  a  continuous  tie 
across  and  through  the  untopped  element, 
extending  across  the  diaphragm,  the  strength 
reduction  factor  (<}))  shall  be  0.7." 

1 1.  Modify  Section  21.6.3  to  read:  "The  design 
shear  force  (Vu)  shall  be  obtained  from  the  lateral 


load  analysis  in  accordance  with  the  factored 
loads  and  combinations  of  loads  specified  in 
780  CMR  1616.0. 

12.  Renumber  existing  Sections  21.6.6  through 
21.6.8  to  Sections  21.6.7  through  21.6.9, 
respectively,  and  add  a  new  Section  21.6.6  to 
read: 

21.6.6  Coupling  beams:  A  coupling  beam  (beam 
which  interconnects  two  shear  walls  in  their  own 
plane)  with  clear-span-to-effective-depth  ratio 
(l„/d)  of  less  than  four  and  with  factored  shear 
force  (Vu)  exceeding  ^Jf'bjd  shall  be 
provided  with  shear  reinforcement  as  specified  in 
Sections  21.6.6.1  through  21.6.6.3. 

21.6.6.1  Factored  shear  force  (Vu)  shall  be 
resisted  by  two  intersecting  groups  of  symmetrical 
diagonally  placed  bars  extending  across  the  full 
length  of  the  member  and  adequately  anchored 
within  the  shear  walls.  Each  group  shall  consist 
of  a  minimum  of  four  bars  providing  an  area  (AVJ) 
not  less  than  that  calculated  by  the  following 
formula: 

Vu 

\d- 

2/   sin  a 

where:  a  is  the  angle  between  the  diagonal 
reinforcement  and  the  longitudinal  axis  of  the 
member. 

21.6.6.2  Contribution  of  the  diagonal 
reinforcement  to  nominal  flexural  strength  of  the 
coupling  beam    shall  be  included. 

21.6.6.3  Each  group  of  diagonally  placed  bars 
shall  be  enclosed  in  special  transverse 
reinforcement  conforming  to  Sections  21.4.4.1 
through  21.4.4.3.  For  the  purpose  of  computing 
A„  in  accordance  with  Equations  10-5  and  21-3, 
minimum  cover  as  specified  in  Section  7.7  shall 
be  assumed  over  each  group  of  diagonally  placed 
reinforcing  bars. " 

13.  Modify  the  title  of  Section  21.8  to  read: 
"Requirements  for  Intermediate  Moment  Frames" 

1903.2  Headed  bolts  and  headed  stud  anchors  in 
concrete:  Headed  bolts  and  headed  stud  anchors 
shall  be  solidly  cast  in  concrete.  The  factored  loads 
on  embedded  headed  bolts  and  headed  stud  anchors 
shall  not  exceed  the  design  strengths  determined  by 
780  CMR  1903.2.2. 

1903.2.1  Load  factor  multipliers:  In  addition  to 
theload  factors  in  780  CMR  1616.1,  a  multiplier 
of  2  shall  be  used  if  special  inspection  is  not 
provided,  or  a  multiplier  of  1.3  shall  be  used  if 
special  inspection  is  provided.  Where  anchors  are 
embedded  in  the  tension  zone  of  a  member,  the 
load  factors  in  780  CMR  1616.1  shall  have  a 
multiplier  of  3  if  special  inspection  is  not 
provided  or  of  2  if  it  is  provided. 


336 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


1903.2.2  Strength  of  anchors:  The  strength  of 
headed  bolts  and  headed  stud  anchors  solidly  cast 
in  concrete  shall  be  taken  as  the  average  of  ten 
tests  for  each  concrete  strength  and  anchor  size  or 
calculated  in  accordance  with  780  CMR 
1903.2.2.1  through  1903.2.2.3.  The  loadbearing 
area  of  headed  anchors  shall  be  at  least  1V2  times 
the  shank  area  for  anchors  of  not  more  than 
60,000  psi  yield  strength. 

1903.2.2.1  Strength  in  tension:  The  strength 
of  anchors  in  tension  shall  be  the  minimum  of 
P„  or  <t>  Pr  where: 


and 


where: 


P,  =  0.9A.f's 


=  chX  ^(2.8As  +  4At) 


Al  =  Area  (in  square  inches)  of  bolt  or  stud. 
Must  be  used  with  the  corresponding  steel 
properties  to  determine  the  weakest  part  of  the 
assembly  in  tension.  In  shear,  the  insert  leg  is 
not  required  to  be  checked. 
As  =  The  sloping  area  (in  square  inches)  of  an 
assumed  failure  surface.  For  a  single  anchor  or 
anchors  in  a  group  where  the  distance  between 
anchors  is  equal  to  or  greater  than  twice  their 
embedment  length,  the  surface  is  assumed  to 
be  that  of  a  truncated  cone  radiating  at  a  45- 
degree  slope  from  the  loadbearing  edge  of  the 
anchor  to  the  surface  (i.e.,  At  =  0). 

For  anchors  in  a  group  where  the  distance 
between  anchors  is  less  than  twice  their 
embedment  length,  the  failure  surface  is 
assumed  to  be  that  of  a  truncated  pyramid 
radiating  at  a  45-degree  slope  from  the 
loadbearing  edge  of  the  anchor  group  to  the 
surface.  Additionally;  for  thin  sections  with 
anchor  groups,  the  failure  surface  shall 
assumed  to  follow  the  extension  of  this  slope 
through  to  the  far  side  rather  than  truncate  as  in 
A, ,  (i.e.,  A,  =  0),  and  the  failure  mode  resulting 
in  the  lower  value  of  (J)  Pc  shall  control. 
At  =  The  area  (in  square  inches)  of  the  flat 
bottom  of  the  truncated  pyramid  of  an  assumed 
concrete  failure  surface.  Where  anchors  in  a 
group  are  closer  than  twice  their  embedment 
length,  the  failure  surface  pyramid  is  assumed 
to  truncate  at  the  anchor  loadbearing  edge 
rather  than  form  separate  cones. 
f'c  =  Specified  compressive  strength  of 
concrete  (psi),  which  shall  not  be  taken  greater 
than  6,000  psi. 

f's  =  Ultimate  tensile  strength  (in  psi)  of  the 
bolt,  stud  or  insert  leg  wires,  which  shall  not  be 
taken  greater  than  60,000  psi.  For  A307  bolts 
or  A108  studs,  f's  shall  be  permitted  to  be 
assumed  to  be  60,000  psi. 


P  =  Tensile  strength  required  due  to  factored 
loads  (pounds). 

Vu  =  Shear  strength  required  due  to  factored 
loads  (pounds). 

~K  =  One  for  normal-weight  concrete,  0.75  for 
all  lightweight  concrete,  and  0.85  for  sand- 
lightweight  concrete. 

<J)  =  Strength  reduction  factor  shall  be  taken  as 
0.65,  except  (J>  is  permitted  to  be  taken  as  0.85 
where  the  anchor  is  attached  to  or  hooked 
around  reinforcing  steel  or  otherwise 
terminated  so  as  to  transfer  effectively  forces 
to  reinforcing  steel  that  is  designed  to 
distribute  forces  and  avert  sudden  local  failure. 
Where  the  edge  distance  is  less  than 
embedment  length,  reduce  <}>  ?c 
proportionately.  For  multiple  edge  distances 
less  than  the  embedment  length,  use  multiple 
reductions. 

1903.2.2.2  Strength  in  shear:  The  strength  of 
anchors  in  shear  shall  be  the  minimum  of  Vs  or 
(J)  Vc  where: 

V.    =    0-7H   f's 

and  where  loaded  toward  an  edge  greater  than 
ten  diameters  away: 

<hFc  =  $800Ab  X  JTC 
or  where  loaded  toward  an  edge  less  than  ten 
diameters  away: 

,2 


$Vc  =  tyl-Kd]  X  ^Tc 


where: 

de  =  Edge  distance  from  the  anchor  axis  to  the 

free  edge. 

For  groups  of  anchors,  the  concrete  design 

shear  strength  shall  be  taken  as  the  smallest  of: 

1 .  The  strength  of  the  weakest  anchor  times 
the  number  of  anchors; 

2.  The  strength  of  the  row  of  anchors 
nearest  the  free  edge  in  the  direction  of  shear 
times  the  number  of  rows;  or 

3.  The  strength  of  the  row  farthest  from  the 
free  edge  in  the  direction  of  shear. 

For  shear  loading  toward  an  edge  less  than  ten 
diameters  away,  or  tension  or  shear  not  toward 
an  edge  less  than  four  diameters  away, 
reinforcing  sufficient  to  carry  the  load  shall  be 
provided  to  prevent  failure  of  the  concrete  in 
tension.  In  no  case  shall  the  edge  distance  be 
less  than  31/3  diameters  for  shear  toading 
toward  an  edge,  or  IV3  diameters  for  tension  or 
shear  not  toward  an  edge. 
1903.2.2.3  Combined  tension  and  shear: 
Where  tension  and  shear  act  simultaneously, 
both  of  the  following  shall  be  met: 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


337 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


/       \ 

2 

(      ,r     > 

2 

p 

vu 

u 

+ 

y 

V 

V     CJ 

\   °  > 

. 

and 


<,! 


si 


1903.2.3  Special  provisions  for  anchor  bolts  in 
tops  of  columns:  Anchor  bolts  at  the  tops  of 
columns  shall  be  enclosed  with  not  less  than  two 
#4  ties  located  within  four  inches  from  the  top  of 
the  column.  Bolts  in  the  tops  of  columns  shall  be 
embedded  not  less  than  nine  bolt  diameters. 

1903.3  Moment  frames:  Moment  frames  shall 
comply  with  780  CMR  1903.3.1,  or  1903.3.2. 

1903.3.1  Intermediate      moment      frames: 

Intermediate  moment  frames  shall  comply  with 
the  requirements  of  Section  21.8  of  ACI  318, 
except  as  follows: 

1903.3.1.1  Transverse  reinforcement  for  frame 
members  subjected  principally  to  bending, 
where  the  factored  axial  compressive  force  on 
the  members  do  not  exceed  (A  f'^lO),  shall 
comply  with  Section  21.3.3  of  ACI  318. 

1903.3.1.2  Transverse  reinforcement  for  frame 
members  subjected  to  bending  and  axial  load, 
where  the  factored  axial  compressive  force  on 
the  members  exceeds  (Al^/'JIO),  shall  comply 
with  Section  21.4.4  of  ACI  318. 

1903.3.1.3  Transverse  reinforcement  as 
specified  in  Section  21.4.4  of  ACI  318  shall  be 
provided  within  joints  of  frames,  for  the  full 
height  of  the  joints,  except  that  it  may  be 
omitted  over  the  depth  of  the  shallowest  beam 
where  beams  frame  into  all  four  sides  of 
columns. 

1903.3.1.4  Moment  frames  composed  of  two 
way  slabs  without  beams  shall  not  be  used  to 
resist  lateral  seismic  forces.  Delete  Section 
21.8.6  of  ACI  318. 

1903.3.2  Special  moment  frames:  Special 
moment  frames  shall  comply  with  the 
requirements  of  Sections  21.2  through  21.5  of 
ACI  3  1 8  as  modified  in  780  CMR  1 903 . 1 . 1 ,  and 
with  the  requirements  of  780  CMR  1903.3.1  for 
intermediate  moment  frames. 

1903.4  Seismic     Performance     Category     C: 

Buildings  assigned  to  Seismic  Performance 
Category  C  shall  conform  to  all  of  the  requirements 
of  ACI  3  18  as  listed  in  Appendix  A  and  to  780  CMR 
1903.4.1,  1903.4.2  and  1903.4.3. 

1903.4.1  Moment  frames  All  moment  frames 
that  are  part  of  the  seismic-resisting  system  shall 


be  intermediate  moment  frames  conforming  to 
780  CMR  1903.3.1,  or  special  moment  frames 
conforming  to  780  CMR  1903.3.2. 

1903.4.2  Discontinuous  members:  Columns 
supporting  reactions  from  discontinuous  stiff 
members,  such  as  walls,  shall  be  provided  with 
special  transverse  reinforcement  at  the  spacing 
(s0)  as  defined  in  Section  21.9.5.1  of  ACI  318 
over  their  full  height  beneath  the  level  at  which 
the  discontinuity  occurs.  This  special  transverse 
reinforcement  shall  be  extended  above  and  below 
the  column  as  required  by  Section  21.4.4.5  of  ACI 
318. 

1903.4.3  Shear  walls:  The  design  shear  strength 
of  shear  walls  shall  be  calculated  as  the  maximum 
shear  obtained  from  design  load  combinations 
which  include  twice  the  earthquake  effect 
calculated  in  accordance  with  the  provisions  of 
780  CMR. 

1903.4.4  Shear  walls  in  Dual  Systems:  Shear 
walls  acting  in  combination  with  a  moment  frame 
in  a  Dual  System  shall  conform  to  sections  21.2 
through  21.6  in  ACI  318  as  modified  by 
780  CMR  1903.1.1. 

1903.5     Seismic     Performance     Category     D: 

Buildings  assigned  to  Seismic  Performance 
Category  D  shall  conform  to  all  of  the  requirements 
for  Seismic  Performance  Category  C,  and  to  the 
requirements  of  780  CMR  1903.5.1  through 
1903.5.3. 

1903.5.1  Moment  frames:  All  moment  frames 
that  are  part  of  the  seismic-resisting  system, 
regardless  of  height,  shall  be  special  moment 
frames  conforming  to  780  CMR  1903.3.2. 

1903.5.2  Seismic-resisting  system:  All  materials 
and  components  in  the  seismic-resisting  system 
shall  conform  to  Sections  21.2  through  21.6  in 
ACI  3 1 8.  as  modified  by  780  CMR  1 903 . 1 . 1 . 

1903.5.3  Frame  members  not  proportioned  to 
resist  earthquake  forces:  All  frame  components 
which  are  not  part  of  the  seismic-resisting  system 
shall  conform  to  780  CMR  1612.4.4.3.3  and  to 
Section  21.7. 1.1  or  21.7.1.2,  and  Section  21.7.2 
of  ACI  318. 

780  CMR  1904.0  SEISMIC  REQUIREMENTS 
FOR  PLAIN  CONCRETE 

1904.1  General:  The  design  and  construction  of 
plain  concrete  components  that  resist  seismic  forces 
shall  conform  to  the  requirements  of  ACI  318.1 
listed  in  Appendix  A  except  as  modified  by 
780CMR1904.0. 

1904.2  Seismic     Performance     Category     C: 

Structural  members  of  plain  concrete  in  buildings 
assigned  to  Seismic  Performance  Category  C  shall 
conform  to  the  requirements  of  ACI  318  1  listed  in 


338 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 

CONCRETE 


Appendix  A  and  the  additional  provisions  and 
limitations  of  780  CMR  1904.0. 

1904.2.1  Footings:  Plain  concrete  footings 
supporting  walls  shall  be  provided  with  not  less 
than  two  continuous  longitudinal  reinforcing  bars 
Bars  shall  not  be  smaller  than  #4,  and  shall  have 
a  total  area  of  not  less  than  0.002  times  the  gross 
cross-sectional  area  of  the  footing.  Continuity  of 
reinforcement  shall  be  provided  at  corners  and 
intersections. 

1904.2.2  Pedestals:  Plain  concrete  pedestals  shall 
not  be  used  to  resist  lateral  forces  due  to 
earthquake. 

1904.2.3  Walls  Basement  and  foundation  walls 
shall  be  reinforced  as  specified  in  ACI  318.1 
listed  in  Appendix  A  Other  walls  shall  be 
reinforced  vertically  and  horizontallv  as  required 
by  780  CMR  1904.2  3.1  and  1904.2.3.2 

1904.2.3.1  Vertical  reinforcement  Vertical 
reinforcement  consisting  of  at  least  one  44  bar 
shall  be  provided  continuously  from  support  to 
support  at  each  corner,  at  each  side  of  each 
opening  and  at  ends  of  walls  or  panels. 

1904.2.3.2  Horizontal  reinforcement 
Horizontal  reinforcement  consisting  of  at  least 
one  44  bar  shall  be  provided  as  follows: 

1  At  the  top  and  bottom  of  each  wall 
opening,  extending  not  less  than  24  inches 
(610  mm)  beyond  the  sides  of  the  opening, 
and 

2.     Continuously  at  structurally  connected 

roofs  and  floors,  at  the  top  of  walls,  at  the 

bottom  of  the  wall  or  in  the  top  of  the 

foundation  where  the  foundation  is  doweled 

to  the  wall,   and  at  a  maximum  vertical 

spacing  often  feet  (3048  mm). 

Reinforcement  at  the  top  and  bottom  of  wall 

openings   shall  be  continuous  to  qualify  as 

reinforcement      required      by      780      CMR 

1904.2.3.2  item  2. 

1904.3      Seismic     Performance     Category     D 

Structural  members  of  plain  concrete  are  not 
permitted  in  buildings  assigned  to  Seismic 
Performance  Category  D. 

Exceptions: 

1 .  For  occupancies  in  Use  Group  R-3  in 
buildings  of  wood  frame  construction,  plain 
concrete  footings  without  longitudinal 
reinforcement  supporting  walls,  and  plain 
concrete  column  footings  are  permitted. 

2.  In  all  other  buildings,  plain  concrete  footings 
supporting  walls  shall  be  permitted  provided  that 
such  footings  are  reinforced  longitudinally  as 
specified  in  780  CMR  1904.2.1. 

3.  For  occupancies  in  Use  Group  R-3.  plain 
concrete  foundation  or  basement  walls  having  a 
thickness  of  not  less  than  IV2  inches  (191  mm) 


and  retaining  four  feet  (1219  mm)  or  less  of 
unbalanced  fill  shall  be  permitted 

780  CMR  1905.0  MINIMUM  SLAB 
THICKNESS 

1905.1  General.  The  thickness  of  concrete  floor 
slabs  supported  directly  on  the  ground  shall  not  be 
less  than  3J4  inches  (89  mm).  A  6-mil  (0.006  inch. 
152  urn)  polyethylene  vapor  retarder  with  joints 
lapped  not  less  than  six  inches  (152  mm)  shall  be 
placed  between  the  base  course  or  subgrade  and  the 
concrete  floor  slab,  or  other  approved  equivalent 
methods  or  materials  shall  be  used  to  retard  vapor 
transmission  through  the  floor  slab 

Exception:  A  vapor  retarder  is  not  required: 
1  For    detached    structures   accessory   to 

occupancies  in  Use  Group  R-3,  such  as  garages, 
utility  buildings  or  other  unheated  facilities; 

2.  For  unheated  storage  rooms  having  an  area  of 
less  than  70  square  feet  (6.5  m2)  and  carports 
attached  to  occupancies  in  Use  Group  R-3: 

3.  For  buildings  of  other  use  groups  where 
migration  of  moisture  through  the  slab  from 
below  will  not  be  detrimental  to  the  intended 
occupancy  of  the  building. 

4         For  driveways,   walks,   patios  and  other 

flatwork  which  will  not  be  enclosed  at  a  later 

date;  or 

5.         Where   approved   based   upon   local    site 

conditions. 

780  CMR  1906.0  MATERIALS 

1906.1  General:  Materials  used  to  produce  concrete 
and  admixtures  for  concrete  shall  comply  with  the 
requirements  of  780  CMR  1906  0  and  ACI  318. 

1906.2  Cements  Cement  shall  conform  to  ASTM 
CI 50  listed  in  Appendix  A.  or  to  such  other  cements 
as  listed  in  ACI  3  18 

1906.3  Aggregates:  Concrete  aggregates  shall 
conform  to  ASTM  C33  or  to  ASTM  C330  listed  in 
Appendix  A 

1906.3.1  Special  tests:  Aggregates  failing  to  meet 
the  specifications  listed  in  780  CMR  1906.3  shall 
not  be  used  unless  approved  and  shown  by  special 
test  or  actual  service  to  produce  concrete  of 
adequate  strength  and  durability 

1906.3.2  Nominal  size:  Nominal  maximum  size 
of  coarse  aggregate  shall  not  be  larger  than: 

1.  1/5  of  the  narrowest  dimension  between 
sides  of  forms; 

2.  V3  of  the  depth  of  slabs,  nor 

3.  3/4  of  the  minimum  clear  spacing  between 
individual  reinforcing  bars  or  wires,  bundles  of 
bars,  or  prestressing  tendons  or  ducts. 

Exception:  These  limitations  shall  not  apply 
where  information  is  submitted  by  the  engineer 
and  is  approved  showing  that  the  workability  and 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUTLDENG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


methods  of  consolidation  are  such  that  concrete 
will  be  placed  without  honeycomb  or  voids. 

1906.4  Water:  Water  used  in  mixing  concrete  shall 
be  clean  and  free  from  injurious  amounts  of  oils, 
acids,  alkalis,  salts,  organic  materials  or  other 
substances  that  are  deleterious  to  concrete  or 
reinforcement. 

1906.4.1  Chloride  ions:  Mixing  water  for 
prestressed  concrete  or  for  concrete  that  will 
contain  aluminum  embedments,  including  that 
portion  of  mixing  water  contributed  in  the  form  of 
free  moisture  on  aggregates,  shall  not  contain 
deleterious  amounts  of  chloride  ion  (see 
780  CMR  1907. 1.4). 

1906.4.2  Potability:  Nonpotable  water  shall  not 
be  used  in  concrete  unless  the  specific 
requirements  of  ACI  318  allowing  the  use  of 
nonpotable  water  are  satisfied. 

1906.5  Metal  reinforcement:  Reinforcement  and 
welding  of  reinforcement  to  be  placed  in  concrete 
construction  shall  conform  to  the  requirements  of 
780  CMR  1906.5 

1906.5.1  Reinforcement  Type:  Reinforcement 
shall  be  of  the  deformed  type,  except  for  plain 
reinforcement  used  for  spirals  or  tendons  and 
reinforcement  consisting  of  structural  steel,  stee! 
pipe  or  steel  tubing  as  specified  in  ACI  318 
Reinforcement  shall  conform  to  the  applicable 
ASTM  standards  listed  in  ACI  318. 

1906.5.2  Welding:  Reinforcing  bars  to  be  welded 
shall  be  indicated  on  the  drawings,  and  the 
welding  procedure  to  be  used  shall  be  specified. 
ASTM  reinforcing  bar  specifications,  except  for 
ASTM  A706  listed  in  Appendix  A,  shall  be 
supplemented  to  require  a  report  of  material 
properties  necessary  to  conform  to  welding 
procedures  specified  in  AWS  D1.4  listed  in 
Appendix  A. 

1906.5.3  Tests:  Where  unidentified  reinforcement 
is  approved  for  use,  not  less  than  three  tension  and 
three  bending  tests  shall  be  made  on 
representative  specimens  of  the  reinforcement 
from  each  shipment  and  grade  of  reinforcing  steel 
proposed  for  use  in  the  work. 

1906.6  Admixtures:  Admixtures  used  in  concrete 
shall  comply  with  780  CMR  1906.6.1  through 
1906.6.4. 

1906.6.1  Chloride:  Calcium  chloride  or 
admixtures  containing  chloride  from  other  than 


impurities  from  admixture  ingredients  shall  not  be 
used  in  prestressed  concrete,  in  concrete 
containing  embedded  aluminum,  in  concrete  cast 
against  stay-in-place  galvanized  metal  forms,  or 
in  concrete  to  be  exposed  to  severe  or  very  severe 
sulfate-containing  solutions  as  defined  in  ACI  3 1 8 
(see  780  CMR  1907  1.3  and  1907.1.4). 

1906.6.2  Standards  Air-entraining  admixtures 
shall  conform  to  ASTM  C260  listed  in 
Appendix  A  Water-reducing  admixtures, 
retarding  admixtures,  accelerating  admixtures, 
water-reducing  and  retarding  admixtures,  and 
water-reducing  and  accelerating  admixtures  shall 
conform  to  ASTM  C494  listed  in  Appendix  A 

1906.6.3  Pozzolans:  Fly  ash  or  other  pozzolans 
used  as  admixtures  shall  conform  to  ASTM  C6 1 8 
listed  in  Appendix  A. 

1906.6.4  Blast-furnace  slag:  Ground-granulated 
blast-furnace  slag  used  as  an  admixture  shall 
conform  to  ASTM  C989  listed  in  Appendix  A 

1906.7  Tests  of  materials  Tests  of  concrete  and  the 
materials  used  in  concrete  shall  be  in  accordance 
with  ACI  3 18 

780  CMR  1907.0  DURABILITY 
REQUIREMENTS 

1907.1  Durability  requirements  Where  concrete 
is  exposed  to  special  conditions  as  described  in 
780  CMR  1907.1.1  through  1907.1.5,  the 
requirements  set  forth  in  780  CMR  1907  1  1  through 
1907.1.5  shall  be  met. 

1907.1.1  Freezing  and  thawing  and  deicer 
chemicals:  Normal  weight  and  lightweight 
concrete  exposed  to  freezing  and  thawing  or 
deicer  chemicals  shall  be  air  entrained  with  the  air 
content  indicated  in  Table  1 907. 1.1.  Tolerance  on 
air  content  as  delivered  shall  be  ±  1.5%.  For  a 
specified  compressive  strength  (/  'c)  greater  than 
5,000  psi  (34475  kPa),  the  required  air  content 
indicated  in  Table  1907.1.1  shall  be  reduced  by 
1%.  Where  finely  divided  materials  of  fly  ash  or 
natural  pozzolans  are  used  as  mineral  admixtures 
(see  780  CMR  1906.6.3)  in  air-entrained  portland 
cement  concrete,  air  content  tests  shall  be  made  in 
accordance  with  ASTM  C23 1  listed  in 
Appendix  A,  to  assure  compliance  with  the  air 
content  requirements  of  Table  1907.1.1.  The 
frequency  of  air  content  tests  shall  be  the  same  as 
that  for  strength  tests  required  by  780  CMR 
1908.3.1. 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


Table  1907.1.1 
TOTAL  AER  CONTENT  FOR  FROST- 
RESISTANT  CONCRETE 


Nominal 

Air  content,  percent 

maximum   , 

aggregate  size 
(inches) 

severe   exposure 

Moderate 
e\posure 

% 

VA 

6 

!/2 

7 

5'/2 

3/4 

6 

5 

1 

6 

4/2 

l'/j 

y/i 

4'/2 

2C 

5 

4 

j 

4'/2 

3'/2 

Note  a.  The  severe  and  moderate  exposures 
referenced  in  this  table  are  not  based  upon  the  weathering 
regions  shown  in  figure  1907.1.2.  For  the  purposes  of 
780  CMR  1907.  severe  and  moderate  exposures  shall  be 
defined  as  follows: 

Severe  exposure  occurs  when  concrete  will  be  in 
almost  continuous  contact  with  moisture  prior  to  freezing, 
or  where  deicing  salts  are  used.  Examples  are  pavements, 
bridge  decks,  sidewalks,  parking  garages  and  water  tanks. 

Moderate  exposure  occurs  when  concrete  will  be  only 
occasionally  exposed  to  moisture  prior  to  freezing,  and 
where  deicing  salts  are  not  used.  Examples  arc  certain 
exterior  walls,  beams,  girders  and  slabs  not  in  direct 
contact  with  soil. 


Note  b.  See  ASTM  C33  listed  in  Appendix  A  for 
oversize  tolerances  for  various  nominal  maximum  size 
designations. 

Note  c.  These  air  contents  apply  to  total  mix,  as  for 
the  preceding  aggregate  sizes.  When  testing  these 
concretes,  however,  aggregate  larger  than  1/4  inches  is 
removed  by  handpicking  or  sieving  and  air  content  is 
determined  on  the  minus- l'/i-inch  fraction  of  mix. 
(Tolerance  on  air  content  as  delivered  applies  to  this 
value.)  Air  content  of  the  total  mix  is  computed  from  the 
value  determined  on  the  minus- 1  VS-inch  fraction. 

1907.1.2  Water-cementitious  material  ratio  and 
strength:  For  occupancies  and  appurtenances 
thereto  in  Use  Group  R-3,  and  occupancies  in  Use 
Group  R-2  that  are  in  buildings  less  than  four 
stories  in  height,  normal-weight  aggregate 
concrete  that  is  subject  to  weathering  (freezing 
and  thawing),  as  determined  from  Figure 
1907.1.2,  or  deicer  chemicals  shall  comply  with 
the  requirements  of  Table  1907.1.2(1).  In  all 
other  buildings,  concrete  that  is  intended  to  have 
a  low  permeability  to  water,  or  concrete  that  will 
be  subject  to  freezing  and  thawing  in  a  moist 
condition  or  that  will  be  exposed  to  deicing  salts, 
brackish  water,  sea  water  or  spray  from  these 
sources,  shall  conform  to  the  requirements  of 
Table  1907.1.2(2).  Additionally,  concrete  that 
will  be  exposed  to  deicing  chemicals  shall 
conform  to  the  limitations  of  780  CMR1 907. 1.2.2. 


Figure  1907.1.2 
Weathering  Probability  Map  for  Concrete 


Severe  -  (Over  500°)         t 
Moderate -(100  to  500°)  L 

Negligible  (Under  100°)  t 


Weathering  Regions  (Weathering  Index) 


Note  a.  Lines  defining  areas  are  approximate  only.  Local  conditions 
can  be  more  or  less  severe  than  indicated  by  the  region  classification. 

Note  b  Data  needed  to  detemiinc  the  weathering  index  for  any  locality 
can  be  found  or  estimated  from  the  Tables  of  Local  Climalological  Data. 
published  by  the  National  Oceanic  &  Atmospheric  Administration.  U.S. 
Department  of  Commerce. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


341 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  1907.1.2(1) 

MINIMUM  SPECIFIED  COMPRESSIVE 

STRENGTH  (/'  )c 


T\pe  of  location  of  concrete 
construction 


Basement  walls  and  founda- 
tions not  exposed  to  the 
weather 


Basement  slabs  and  interior 
slabs  on  grade,  except  garage 
floor  slabs 


Basement  walls,  foundation 
walls,  exterior  walls  and 
other  vertical  concrete 
surfaces  exposed  to  the 
weather 


Driveways,  curbs,  walks, 
patios,  porches,  carport 
slabs,  steps  and  other  flat- 
work  exposed  to  the  weather, 
and  Earaee  floor  slabs 


Minimum  specified 
compressive  strength 
(/'at  28  days,  psi) 


Negligible 
exposure 


Moderate 
exposure 


Severe 
exposure 


Note  a.  Concrete  tn  these  locations  which  can  be 
subjected  to  freezing  and  thawing  during  construction 
shall  be  of  air-entrained  concrete  in  accordance  with 
Table  1907.1.1. 

Note  b.  Concrete  shall  be  air  entrained  in  accordance 
with  Table  1907.1.1. 

Note  c.   1  psi  =  6.895  kPa. 

Table  1907.1.2(2) 

REQUIREMENTS  FOR  SPECIAL 

EXPOSURE  CONDITIONS 


Exposure  condition 

Maximum  water 

cementitious 

materials  ratio 

(by  weight), 

normal-weight 

aggregate 

concrete 

Minimum/' 
normal-weight 
and  lightweight 
aggregate  g 
concrete  (psi) 

Concrete  intended  to 
have  low  permeability 
when  exposed  to  water 

0.50 

4,000 

Concrete  exposed  to 
freezing  and  thawing  in 
a  moist  condition 

0.45 

4.500 

For  corrosion  protection 
for  reinforced  concrete 
exposed  to  deicing  salts, 
brackish  water,  sea- 
water  or  spray  from 
these  sources 

0.40 

5,000 

Note  a.   1  psi  =  6.895  kPa. 

1907.1.2.1  Calculation  of  water-cementitious 
material  ratio:  To  determine  compliance  with 
the  maximum  water-cementitious  material  ratio 
requirement  of  Table  1907.1.2(2),  the  weight 
of  cementitious  material  shall  include  weights 
of  any  of  the  following  if  contained  in  the 
concrete  mixture:  cement  conforming  to  the 
requirements  of  ASTMC150  orC595;  fly  ash 


or  other  pozzolan  conforming  to  the 
requirements  of  ASTM  C61S;  and  ground- 
granulated  blast-furnace  slag  conforming  to  the 
requirements  of  ASTM  C989  listed  in 
Appendix  A. 

1907.1.2.2  Limitations  on  use  of  certain 
cementitious  materials:  For  concrete  exposed 
to  deicing  chemicals,  the  maximum  weight  of 
fly  ash  or  other  pozzolan,  or  ground  granulated 
blast-furnace  slag  that  is  included  in  the 
calculation  of  water-cementitious  material 
ratio,  shall  not  exceed  the  percentages  of  the 
total  weight  of  cementitious  material  specified 
in  7S0  CMR  1907.1.2.2.1  through  1907.1.2 
2.3. 

1907.1.2.2.1  Concrete  containing  fly  ash 
or  pozzolan:  The  combined  weight  of  fly 
ash  and  other  pozzolan  conforming  to 
ASTM  C618  listed  in  Appendix  A.  shall  not 
exceed  25%  of  the  total  weight  of 
cementitious  materials.  Fly  ash  or  other 
pozzolan  used  to  manufacture  Type  IP  or 
IPM  blended  hydraulic  cement  conforming 
to  ASTM  C595  listed  in  Appendix  A  shall  be 
included  with  fly  ash  or  other  pozzolan 
added  as  an  admixture. 

1907.1.2.2.2  Concrete  containing  ground- 
granulated  blast-furnace  slag:  The  weight 
of  ground-granulated  blast-furnace  slag 
conforming  to  ASTM  C989  listed  in 
Appendix  A  shall  not  exceed  50%  of  the 
total  weight  of  cementitious  materials.  Slag 
used  to  manufacture  Type  IS  or  ISM 
blended  hydraulic  cement  conforming  to 
ASTM  C595  listed  in  Appendix  A  shall  be 
included  with  slag  added  as  an  admixture. 

1907.1.2.2.3  Concrete  containing  fly  ash 
or  pozzolan  and  slag:  If  fly  ash  or  other 
pozzolan  and  slag  are  used  in  concrete, 
Portland  cement  conforming  to  ASTM  CI 50 
listed  in  Appendix  A  shall  constitute  not  less 
than  50%  of  the  total  weight  of  cementitious 
materials.  Fly  ash  or  other  pozzolan  shall 
constitute  not  more  than  25%  of  the  total 
weight  of  cementitious  materials.  See 
780  CMR  1907.1.2.2.1. 

1907.1.3  Protection  from  sulfate:  Concrete  that 
will  be  exposed  to  sulfate-containing  solutions  or 
soils  shall  conform  to  the  requirements  for  such 
exposure  in  ACI  318. 

1907.1.4  Corrosion  resistance:  For  corrosion 
resistance,  the  maximum  water-soluble  chloride 
ion  concentrations  in  concrete  shall  not  exceed 
the  limitations  established  in  ACI  318. 

1907.1.5  Protection  from  salt:  Where  reinforced 
concrete  will  be  exposed  to  deicing  chemicals, 
salts,  brackish  water,  sea  water  or  spray  from 
these  sources,  the  requirements  of  Table 
1907.1.2(2)  for  the  water-cementitious  material 


342 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


ratio,  or  the  concrete  strength  and  minimum 
concrete  cover  requirements  of  780  CMR  1910.6, 
shall  be  satisfied. 

780  CMR  1908.0  CONCRETE  QUALITY, 
MIXING  AND  PLACING 

1908.1  General:  Concrete  shall  be  proportioned  to 
provide  an  average  compressive  strength  as 
prescribed  by  ACI  318,  and  to  satisfy  the  durability 
criteria  of  780  CMR  1907.0.  Concrete  shall  be 
produced  to  minimize  frequency  of  strengths  below 
f'c  as  prescribed  in  780  CMR  1908.3.2.  The 
specified  compressive  strength  (J'c  )  for  concrete 
designed  and  constructed  in  accordance  with  this 
chapter  shall  not  be  less  than  2,500  psi  ( 17238  kPa). 

Unless  otherwise  specified,  f'c  shall  be  based  on 
28-day  strength.  If  other  than  28  days  is  used  in  the 
design,  the  length  of  time  to  reach  f'c  shall  be 
indicated  on  the  construction  documents. 

1908.2  Selection  of  concrete  proportions:  Concrete 
proportions  shall  be  determined  in  accordance  with 
ACI  318  and  as  modified  in  780  CMR1908. 

1908.2.1  Proportioning  by  water-cementitious 
material  ratio:  If  data  based  on  field  experience 
or  trial  mixture  as  required  by  ACI  318  are  not 
available,  concrete  proportions  shall  be  based  on 
the  water-cementitious  material  ratio  limitations 
shown  in  Table  1908.2.1,  subject  to  approval. 
The  specified  compressive  strengths  in  Table 
1908.2.1  are  28-day  strengths  for  cements 
conforming  to  the  strength  limitations  of  ASTM 
C 1 50  listed  in  ACI  3 1 8,  Type  I.  I A  II  or  II A  and 
seven-day  strengths  for  Types  III  and  IIIA.  For 
strengths  above  3,500  psi  (24133  kPa),  concrete 
proportioned  by  the  water-cementitious  material 
ratio  shall  be  established  by  the  methods  listed  in 
ACI  318. 

Table  1908.2.1 

MAXIMUM  WATER-CEMENTITIOUS 

MATERIAL  RATIOS  AND  MINIMUM 

CEMENT  CONTENTS 


Minimum 
sacks  of 
cement 

per  cubic 
yard  of 
concrete 

Maximum  permissible  water- 
cementitious  material  ratios 

Specified 

Nonair-enlramed 
concrete 

Air-entrained 
concrete 

compressive 

strength 

(psi) 

Absolute 
ratio  by 
weight 

US 
gallon 
per  94 
pound 
bag  of 
cement 

Absolute 
ratio  by 
weight 

US 
gallon 
per  94 
pound 
bag  of 
cement 

2,500 
3  000 
3.500 

5 

5  'A 
6 

0.67 
0.58 
0.51 

7.6 
6.6 
5.8 

0.54 
0.46 
0  40 

6.1 
5.2 

4  5 

Note  a.    1  psi  -6.895  kPa; 
pound  =  0.454  kg. 


gallon  =  .00379  m~ 


1908.2.2  Limitation  on  use:  Table  1908.2.1  shall 
be   used   only   for   concrete   to   be   made  with 


cements  conforming  to  the  strength  requirements 
for  Type  I,  I  A,  II,  IIA,  III,  IIIA  or  V  of  ASTM  C 
150  listed  in  Appendix  A  or  Type  IS,  IS-A, 
IS(MS),  IS-A(MS),  I(SM),  I(SM)-A  IP,  IP -A, 
I(PM),  I(PM)-A  IPfMS),  IP-A(MS)  or  P  of 
ASTM  C595  listed  in  Appendix  A  and  shall  not 
be  applied  to  concrete  containing  lightweight 
aggregates  or  admixtures  other  than  those  for 
entraining  air. 

1908.2.3  Durability  requirements:  Concrete 
proportioned  by  the  water-cementitious  material 
ratio  limitations  prescribed  in  Table  1908.2.1  shall 
also  conform  to  the  durability  requirements  of 
780  CMR  1907.0  and  to  compressive  strength  test 
criteria  of  780  CMR1908.3. 

1908.3  Evaluation  for  acceptance  of  concrete:  For 

evaluation  and  acceptance  of  concrete,  the 
procedures  established  in  780  CMR  1908.3.1 
through  1908.3.4  shall  be  followed. 

1908.3.1  Frequency  of  testing:  Testing  shall  be 
conducted  as  required  by  the  following: 

1.  Samples  for  strength  tests  of  each  class  of 
concrete  placed  each  day  shall  be  taken  not  less 
than  once  a  day,  nor  less  than  once  for  each 
150  cubic  yards  (115  m  )  of  concrete,  nor  less 
than  once  for  each  5,000  square  feet  (465  m') 
of  surface  area  for  slabs  or  walls. 

2.  On  a  given  project,  if  the  total  volume  of 
concrete  is  such  that  the  frequency  of  testing 
required  by  780  CMR  1908.3.1,  item  1, 
provides  less  than  five  strength  tests  for  a  given 
class  of  concrete,  tests  shall  be  made  from  at 
least  five  randomly  selected  batches  or  from 
each  batch  if  fewer  than  five  batches  are  used. 

3 .  Where  total  quantity  of  a  given  class  of 
concrete  is  less  than  50  cubic  yards  (3S  m3), 
strength  tests  are  not  required  when  approved 
and  evidence  of  satisfactory  strength  is 
provided.  Satisfactory  evidence  shall  include, 
but  not  be  limited  to,  certification  from  the 
concrete  supplier  that  the  concrete  to  be 
provided  will  be  proportioned  to  achieve  the 
specified  compressive  strength  based  on  "field 
experience"  or  "trial  batches"  in  accordance 
with  ACI  318.  In  the  absence  of  satisfactory 
evidence,  concrete  shall  be  proportioned  in 
accordance  with  Table  1908.2.1. 

4.  A  strength  test  shall  be  the  average  of  the 
strengths  of  two  cylinders  made  from  the  same 
sample  of  concrete  and  tested  at  28  days  or  at 
the  test  age  designated  for  determination  of  /' 

1908.3.2  Laboratory-cured         specimens: 

Laboratory-cured  specimens  shall  conform  to  the 
following  criteria: 

1.  Samples  for  strength  tests  shall  be  taken  in 
accordance  with  ASTM  CI  72  listed  in 
Appendix  A 

2.  Cylinders  for  strength  tests  shall  be  molded 
and    laboratory    cured    in    accordance    with 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


ASTM  C3 1  listed  in  Appendix  A,  and  tested  in 
accordance  with  ASTM  C39  listed  in 
Appendix  A. 

3.  Strength  level  of  an  individual  class  of 
concrete  shall  be  considered  satisfactory  if  both 
of  the  following  requirements  are  met: 

3.1.  Average  of  all  sets  of  three  consecutive 
strength  tests  equals  or  exceeds  /'c;  and 

3.2.  All  individual  strength  tests  (average 
of  two  cylinders)  shall  not  fall  below  /'c  by 
more  than  500  psi  (3448  kPa). 

4.  If  either  of  the  requirements  of  780  CMR 
1908.3.2,  item  3,  is  not  met,  steps  shall  be 
taken  to  increase  the  average  of  subsequent 
strength  test  results.  The  requirements  of  780 

CMR  1908.3.4  shall  apply  if  the  requirement 
in  780  CMR  1908.3.2,  item  3.2,  is  not  met. 

1908.3.3  Field-cured  specimens:  Where  the  code 
official  requires  strength  tests  of  cylinders  cured 
under  field  conditions  to  check  adequacy  of 
curing  and  protection  of  concrete  in  the  structure, 
the  field-cured  specimens  shall  conform  to  the 
following  criteria: 

1.  Field-cured  cylinders  shall  be  cured  under 
field  conditions  in  accordance  with  ASTM  C3 1 
listed  in  Appendix  A. 

2.  Field-cured  test  cylinders  shall  be  molded 
at  the  same  time  and  from  the  same  samples  as 
laboratory-cured  test  cylinders. 

3.  Procedures  for  protecting  and  curing 
concrete  shall  be  improved  where  the  strength 
of  field-cured  cylinders  at  the  test  age 
designated  for  determination  of  f'c  is  less  than 
85%  of  that  of  companion  laboratory-cured 
cylinders.  The  85%  criterion  is  not  required 
where  the  field-cured  strength  exceeds  f'c  by 
more  than  500  psi  (3448  kPa). 

1908.3.4  Investigation  of  low-strength  test 
results:  If  the  investigation  of  concrete  indicates 
low-strength  conditions,  the  following  procedures 
shall  apply: 

1.  If  any  strength  test  (see  780  CMR  1908.3.1, 
item  4)  of  laboratory-cured  cylinders  falls 
below  the  specified  value  of  f'c  by  more  than 
500  psi  (3448  kPa)  (see  780  CMR  1908.3.2, 
item  3.2)  or  if  tests  of  field-cured  cylinders 
indicate  deficiencies  in  protection  and  curing 
(see  780  CMR  1908.3.3,  item  3),  steps  shall  be 
taken  to  assure  that  the  loadbearing  capacity  of 
the  structure  is  not  jeopardized. 

2.  If  the  likelihood  of  low-strength  concrete  is 
confirmed  and  computations  indicate  that  the 
loadbearing  capacity  will  be  significantly 
reduced,  tests  of  cores  drilled  from  the  area  in 
question  shall  be  made  in  accordance  with  ACI 
318. 

3.  Concrete  in  an  area  represented  by  core 
tests  shall  be  considered  structurally  adequate 
if  the  average  of  three  cores  is  not  less  than 
85%  of  f'c  and  if  a  single  core  is  not  less  than 


75%  of  f'c.  Where  necessary  to  check  testing 
accuracy,  locations  represented  by  erratic  core 
strengths  shall  be  retested. 
4.  If  the  criteria  of  780  CMR  1908.3.4,  item  3, 
are  not  met,  and  if  structural  adequacy  remains 
in  doubt,  load  tests  shall  be  ordered  at  the 
discretion  of  the  engineer  or  the  code  official 
as  outlined  in  Chapter  20  of  ACI  318  for  the 
questionable  portion  of  the  structure,  or  other 
appropriate  action  taken. 

1908.4  Preparation  of  equipment  and  place  of 
deposit:  Preparation  before  concrete  placement  shall 
include  the  following  criteria: 

1.  All  equipment  for  mixing  and  transporting 
concrete  shall  be  clean. 

2.  All  debris  and  ice  shall  be  removed  from 
spaces  to  be  occupied  by  concrete. 

3.  Forms  shall  be  properly  coated. 

4.  Masonry  filler  units  that  will  be  in  contact 
with  concrete  shall  be  well  drenched. 

5.  Reinforcement  shall  be  thoroughly  clean  of 
ice  or  other  deleterious  coating. 

6.  Water  shall  be  removed  from  the  place  of 
deposit  before  concrete  is  placed,  unless  a 
extreme  is  to  be  used  or  unless  otherwise 
approved  by  the  code  official. 

7.  All  laitance  and  other  unsound  material  shall 
be  removed  before  additional  concrete  is  placed 
against  hardened  concrete. 

1908.5  Mixing:  All  concrete  shall  be  mixed  until 
there  is  a  uniform  distribution  of  materials,  and  shall 
be  discharged  completely  before  the  mixer  is 
recharged. 

1908.5.1  Ready-mixed  concrete:  Ready-mixed 
concrete  shall  be  mixed  and  delivered  in 
accordance  with  ASTM  C94  or  ASTM  C685 
listed  in  Appendix  A. 

1908.5.2  Job-mixed  concrete:  Job-mixed 
concrete  shall  be  mixed  in  accordance  with  ACI 
318. 

1908.6  Conveying:  Concrete  shall  be  conveyed 
from  the  mixer  to  the  place  of  final  deposit  by 
methods  that  will  prevent  separation  or  loss  of 
materials.  Conveying  equipment  shall  be  capable  of 
providing  a  supply  of  concrete  at  the  site  of 
placement  without  separation  of  ingredients  and 
without  interruptions  sufficient  to  permit  loss  of 
plasticity  between  successive  increments. 

1908.7  Depositing:  Concrete  shall  be  deposited  as 
nearly  as  practicable  in  its  final  position  to  avoid 
segregation  caused  by  rehandling  or  flowing. 

1908.7.1  Placement  timing:  Concrete  placement 
shall  be  carried  on  at  such  a  rate  that  the  concrete 
is  at  all  times  plastic  and  flows  readily  into  spaces 
between  reinforcement. 


344 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


1908.7.2  Unacceptable  concrete:  Concrete  that 
has  partially  hardened  or  has  been  contaminated 
by  foreign  materials  shall  not  be  deposited  in  the 
structure. 

1908.7.3  Retempering:  Retempered  concrete  or 
concrete  that  has  been  remixed  after  initial  set 
shall  not  be  used  unless  approved  by  the 
registered  design  professional 

1908.7.4  Continuous  concreting:  Once  started, 
concreting  shall  be  carried  on  as  a  continuous 
operation  until  the  placement  of  a  panel  or 
section,  as  defined  by  panel  or  section  boundaries 
or  predetermined  joints,  is  completed  except  as 
provided  for  in  780  CMR  1909.4. 

1908.7.5  Placement  in  walls:  Top  surfaces  of 
vertically  formed  lifts  shall  be  generally  level. 

1908.7.6  Construction  joints:  Where 
construction  joints  are  required,  such  joints  shall 
be  made  in  accordance  with  780  CMR  1909.4. 

1908.7.7  Consolidation:  All  concrete  shall  be 
thoroughly  consolidated  by  suitable  means  during 
placement  and  shall  be  thoroughly  worked  around 
reinforcement  and  embedded  fixtures  and  into 
comers  of  forms 

1908.8  Curing:  Concrete  (other  than  high-early- 
strength)  shall  be  maintained  above  50°F  (10CC) 
and  in  a  moist  condition  for  at  least  the  first  seven 
days  after  placement,  except  when  cured  in 
accordance  with  780  CMR  1908.8.2. 

1908.8.1  High-early-strength  concrete:  High- 
early-strength  concrete  shall  be  maintained  above 
50°F  (10°C)  and  in  a  moist  condition  for  at  least 
the  first  three  days  after  placement,  except  when 
cured  in  accordance  with  780  CMR  1908.8.2. 

1908.8.2  Accelerated  curing  If  curing  is  to  be 
accelerated,  such  curing  shall  be  done  in 
accordance  with  ACI  318. 

1908.9  Cold-weather  requirements:  Adequate 
equipment  shall  be  provided  for  heating  concrete 
materials  and  protecting  concrete  during  freezing  or 
near-freezing  weather. 

1908.9.1  Frost:  All  concrete  materials  and  all 
reinforcement,  forms,  fillers  and  ground  with 
which  concrete  is  to  come  in  contact  shall  be  free 
from  frost. 

1908.9.2  Ice:  Frozen  materials  or  materials 
containing  ice  shall  not  be  used. 

1908.10  Hot-weather  requirements:  During  hot 
weather,  attention  shall  be  given  to  ingredients, 
production  methods,  handling,  placing,  protection 
and  curing  to  prevent  excessive  concrete 
temperatures  or  water  evaporation  that  would  impair 
required  strength  or  serviceability  of  the  member  or 
structure. 


780  CMR  1909.0  FORMWORK,  EMBEDDED 
PffES  AND  CONSTRUCTION  JOINTS 

1909.1  Design  of  formwork:  The  design, 
fabrication  and  erection  of  forms  shall  result  in  a 
final  structure  that  conforms  to  shapes,  lines  and 
dimensions  of  the  members  as  required  by  the 
construction  documents. 

1909.1.1  Form  strength  Forms  shall  be 
substantial  and  shall  be  sufficiently  tight  to 
prevent  leakage  of  concrete 

1909.1.2  Form  bracing:  Forms  shall  be  properly 
braced  or  tied  together  to  maintain  position  and 
shape 

1909.1.3  Form  placement  Forms  and  their 
supports  shall  be  designed  so  as  not  to  damage 
previously  placed  structures 

1909.2  Removal  of  forms  and  shores  Construction 
loads  shall  not  be  supported  on.  nor  any  shoring 
removed  from,  any  part  of  the  structure  under 
construction  except  where  that  portion  of  the 
structure,  in  combination  with  the  remaining 
forming  and  shoring  system,  has  sufficient  strength 
to  support  safely  its  weight  and  loads  placed 
thereon 

1909.2.1  Structural  analysis:  Sufficient  strength 
shall  be  demonstrated  by  structural  analysis 
considering  proposed  loads,  strength  of  the 
forming  and  shoring  system,  and  concrete  strength 
data.  Concrete  strength  data  shall  be  based  on 
tests  of  field-cured  cylinders  or.  where  approved, 
on  other  procedures  to  evaluate  concrete  strength. 
Structural  analysis  and  concrete-strength  test  data 
shall  be  furnished  to  the  code  official  when  so 
required. 

1909.2.2  Construction  loads:  Construction  loads 
exceeding  the  combination  of  superimposed  dead 
load  plus  specified  live  load  shall  not  be 
supported  on  any  unshored  portion  of  the 
structure  under  construction,  unless  analysis 
indicates  adequate  strength  to  support  such 
additional  loads. 

1909.2.3  Safety:  Forms  shall  be  removed  in  such 
a  manner  so  as  not  to  impair  safety  and 
serviceability  of  the  structure.  All  concrete  to  be 
exposed  by  form  removal  shall  have  sufficient 
strength  not  to  be  damaged  thereby. 

1909.2.4  Prestressed  members:  Form  supports 
for  prestressed  concrete  members  shall  not  be 
removed  unless  sufficient  prestressing  has  been 
applied  to  enable  prestressed  members  to  carry 
their  dead  load  and  anticipated  construction 
loads 

1909.3  Conduits  and  pipes  embedded  in  concrete: 

Where  conduits,  pipes  and  sleeves  of  any  material 
not  harmful  to  concrete  and  within  limitations  of 


9/1 9/97.  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


345 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  are  embedded  in  concrete  with  the 
approval  of  the  engineer,  such  embedments  shall  not 
be  considered  to  replace  structurally  the  displaced 
concrete,  except  as  provided  for  in  780  CMR 
1909.3.5. 

1909.3.1  Aluminum  conduit  and  pipe:  Conduits 
and  pipes  of  aluminum  shall  not  be  embedded  in 
structural  concrete  unless  effectively  coated  or 
covered  to  prevent  aluminum  concrete  reaction  or 
electrolytic  action  between  aluminum  and  steel. 

1909.3.2  Structural  effect:  Conduits,  pipes  and 
sleeves  passing  through  a  slab,  wall  or  beam  shall 
not  impair  significantly  the  strength  of  the 
construction. 

1909.3.3  Columns:  Conduits  and  pipes,  including 
fittings,  embedded  within  a  column,  shall  not 
displace  more  than  4%  of  the  area  of  the  cross 
section  on  which  strength  is  calculated  or  which 
is  required  for  fire  protection. 

1909.3.4  Slabs,  walls  or  beams:  Except  where 
construction  documents  for  conduits  and  pipes  are 
approved  by  the  registered  design  professional 
and  the  code  official,  conduits  and  pipes 
embedded  within  a  slab,  wall  or  beam  (other  than 
those  merely  passing  through)  shall: 

1 .  Not  be  larger  in  outside  dimension  than  Vz 
of  the  overall  thickness  of  the  slab,  wall  or 
beam  in  which  such  conduits  and  pipes  are 
embedded. 

2.  Not  be  spaced  closer  than  three  diameters 
or  widths  on  center. 

3.  Not  impair  significantly  the  strength  of  the 
construction. 

1909.3.5  Displaced  concrete  Conduits,  pipes  and 
sleeves  shall  not  be  considered  in  compression  as 
replacing  structurally  the  displaced  concrete 
unless  such  conduits,  pipes  and  sleeves: 

1.  Are  not  exposed  to  rusting  or  other 
deterioration. 

2.  Are  of  uncoated  or  galvanized  iron  or  steel 
not  thinner  than  standard  Schedule  40  steel 
pipe. 

3.  Have  a  nominal  inside  diameter  not  over 
two  inches  and  are  spaced  not  less  than  three 
diameters  on  center. 

1909.3.6  Additional  considerations:  In  addition 
to  the  other  requirements  of  780  CMR  1909.3, 
pipes  that  will  contain  liquid,  gas  or  vapor  which 
are  embedded  in  structural  concrete  shall  conform 
to  the  following  conditions: 

1  Pipes  and  fittings  shall  be  designed  to  resist 
effects  of  the  material,  pressure  and 
temperature  to  which  the  pipes  and  fittings  will 
be  subjected. 

2.  Liquid,  gas  or  vapor  except  water  not 
exceeding  90°F  (32°C)  or  50  psi  (345  kPa) 
pressure,  shall  not  be  placed  in  the  pipes  until 
the  concrete  has  attained  design  strength. 


3.  In  solid  slabs,  piping  that  is  not  used  for 
radiant  heating  or  snow  melting  shall  be  placed 
between  top  and  bottom  reinforcement 

4.  Concrete  cover  for  pipes,  conduit  and 
fittings  shall  not  be  less  than  VA  inches  (38 
mm)  for  concrete  exposed  to  earth  or  weather 
conditions  or  Vt  inch  (19  m)  for  concrete  not 
exposed  to  weather  conditions  or  in  contact 
with  ground. 

5.  Reinforcement  with  an  area  of  not  less  than 
0.002  times  the  area  of  the  concrete  section 
shall  be  provided  normal  to  piping. 

6.  Piping  and  conduit  shall  be  fabricated  and 
installed  so  that  cutting,  bending  or 
displacement  of  reinforcement  from  the  proper 
location  will  not  be  required. 

1909.4  Construction  joints:  Construction  joints 
shall  be  created  using  the  procedures  set  forth  in 
780  CMR  1909.4.1  through  1909.4.6. 

1909.4.1  Surface  cleaning:  Surface  of  concrete 
construction  joints  shall  be  cleaned  and  laitance 
removed. 

1909.4.2  Preparation  of  joint:  Immediately 
before  new  concrete  is  placed,  all  construction 
joints  shall  be  wetted  and  standing  water  shall  be 
removed. 

1909.4.3  Effect  on  strength:  Construction  joints 
shall  be  so  made  and  located  as  not  to  impair  the 
strength  of  the  structure.  Provisions  shall  be 
made  for  the  transfer  of  shear  and  other  forces 
through  construction  joints. 

1909.4.4  Location  of  joints  Construction  joints 
in  floors  shall  be  located  within  the  middle  third 
of  the  spans  of  slabs,  beams  and  girders.  loints  in 
girders  shall  be  offset  a  minimum  distance  of  two 
times  the  width  of  intersecting  beams. 

1909.4.5  Support  conditions  Beams,  girders  or 
slabs  supported  by  columns  or  walls  shall  not  be 
cast  or  erected  until  concrete  in  the  vertical 
support  members  is  not  in  a  plastic  state. 

1909.4.6  Monolithic  pours:  Beams,  girders, 
haunches,  drop  panels  and  capitals  shall  be  placed 
monolithically  as  part  of  a  slab  system,  unless 
otherwise  shown  on  the  construction  documents. 

780  CMR  1910.0  DETAILS  OF 
REINFORCEMENT 

1910.1  General:  Details  of  reinforcement  shall 
comply  with  the  requirements  of  780  CMR  1910.0 
and  ACI  318.  Where  unidentified  reinforcement  is 
approved  for  use,  such  reinforcement  shall  be  tested 
in  accordance  with  780  CMR  2208. 1 

1910.2  Bending  reinforcement:  All  reinforcement 
shall  be  bent  cold,  unless  otherwise  permitted  by  the 
registered  design  professional  and  approved. 
Reinforcement  partially  embedded  in  concrete  shall 


346 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


not  be  field  bent,  except  as  shown  on  the 
construction  documents  or  as  authorized  by  the 
registered  design  professional  and  approved. 

1910.3  Surface  conditions  of  reinforcement:  At 

the  time  concrete  is  placed,  metal  reinforcement 
shall  be  free  from  mud,  oil  or  other  nonmetallic 
coatings  that  adversely  affect  bonding  capability. 

1910.3.1  Rust  or  mill  scale:  Metal  reinforcement, 
except  prestressing  tendons,  with  rust  or  mill 
scale,  or  a  combination  of  both,  shall  be 
considered  satisfactory,  provided  that  the 
minimum  dimensions  (including  height  of 
deformations)  and  the  weight  of  a  hand-wire- 
brushed  test  specimen  are  not  less  than  the 
specification  requirements  of  the  applicable 
ASTM  standard  referenced  by  ACI  3  18. 

1910.3.2  Prestressing  tendons:  Prestressing 
tendons  shall  be  clean  and  free  of  oil,  dirt,  scale, 
pitting  and  excessive  rust.  A  light  oxide  is 
permissible. 

1910.4  Placing  reinforcement:  Reinforcement, 
prestressing  tendons  and  ducts  shall  be  accurately 
placed  and  supported  before  concrete  is  placed,  and 
shall  be  secured  against  displacement  within  the 
tolerances  permitted  in  780  CMR  1910.4.1  through 
1910.4.3. 

Exception:  Embedded  items  (such  as  dowels  or 
inserts)  of  precast  concrete  members  that  either 
protrude  from  concrete  or  remain  exposed  for 
inspection  shall  not  be  embedded  while  the 
concrete  is  in  a  plastic  state  unless  authorized  by 
the  registered  design  professional  and  the 
following  conditions  are  met: 

1.  Embedded  items  are  not  required  to  be 
hooked  or  tied  to  reinforcement. 

2.  Embedded  items  shall  be  maintained  in  the 
correct  position  while  concrete  remains  plastic. 

3.  Embedded  items  shall  be  properly  anchored 
to  develop  required  factored  loads. 

1910.4.1  Reinforcement,  prestressing  tendons 
and  pretressing  ducts:  Unless  otherwise 
specified  by  the  engineer,  reinforcement, 
prestressing  tendons  and  prestressing  ducts  shall 
be  placed  within  the  following  tolerances: 

1.  The  tolerance  for  depth  (d)  and  the 
minimum  concrete  cover  in  flexural  members, 
walls  and  compression  members  shall  be  as 
specified  in  Table  1910.4  1,  except  that  the 
tolerance  for  the  clear  distance  to  formed 
soffits  shall  be  minus  V*  inch  (6  mm)  and  the 
tolerance  for  cover  shall  not  exceed  minus  one- 
third  of  the  minimum  concrete  cover  required 
in  the  design  drawings  or  specifications. 

2.  The  tolerance  for  longitudinal  location  of 
bends  and  ends  of  reinforcement  shall  be  ±  2 
inches  (51  mm)  except  at  discontinuous  ends  of 


members  where  the  tolerance  shall  be  Vi  inch 
(13  mm). 

Table  1910.4.1 
TOLERANCES3 


Tolerance 

Depth  {d) 

Toleramce 
on  d 

on  d 
minimum 
concrete 

cover 

d  less  than  or  equal  to  8  inches 
d  greater  than  8  inches 

±3/8  inch 
±Vi  inch 

-3/a  inch 
-'/2  inch 

Note  a.   1  inch  =  25.4  mm 

1910.4.2  Welded  wire  fabric:  Where  welded 
wire  fabric  (with  wire  size  not  greater  than  W5  or 
D5)  used  in  slabs  not  exceeding  ten  feet  (3048 
mm)  in  span  is  curved  from  a  point  near  the  top  of 
slab  over  the  support  to  a  point  near  the  bottom  of 
slab  at  midspan,  such  reinforcement  shall  be 
either  continuous  over,  or  securely  anchored  at, 
the  support. 

1910.4.3  Welding:  Welding  of  crossing  bars  shall 
not  be  permitted  for  assembly  of  reinforcement 
unless  authorized  by  the  engineer. 

1910.5  Spacing  limitations  for  reinforcement:  The 

clear  distance  between  reinforcing  bars,  bundled 
bars,  prestressing  tendons  and  ducts  shall  be  in 
accordance  with  the  limitations  of  ACI  318. 

1910.6  Concrete  protection  for  reinforcement: 

Reinforcement  shall  be  provided  with  the  protection 
required  by  780  CMR  1910.6.1  through  1910.6.5. 

1910.6.1  Cast-in-place  concrete:  In  cast-in-place 
concrete  (nonprestressed),  the  minimum  concrete 
cover  for  reinforcement  shall  be  as  indicated  in 
Table  1910.6.1. 

Table  1910.6.1 
MINIMUM  COVER 


Structural  element  and  condition 

Minimum 
cover 

(inches) 

1 .  Concrete  cast  against  and  permanently 
exposed  to  earth 

3 

2.  Concrete  exposed  to  earth  or  weather: 
#6  through  #18  bars 
#5  bar,  W3 1  or  D3 1  wire  and  smaller 

2 
1 54 

3.  Concrete  not  exposed  to  weather  or  in 
contact  with  ground 
Slabs,  walls,  joists 

#14  and  #18  bars 

#1 1  bar  and  smaller 
Beams,  columns: 

Primary  reinforcement,  ties,  stirrups, 

spirals 
Shells,  folded  plate  members: 

#6  bar  and  larger 

#S  bar.  W3 1  or  D3 1  wire,  and  smaller 

i54 

3/< 

i54 

Va 

54 

Note  a.    1  inch  =  25.4  mm 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1910.6.2  Precast  concrete:  The  minimum  cover 
for  reinforcement  in  precast  concrete 
manufactured  under  plant  control  conditions  and 
for  prestressed  concrete  shall  be  in  accordance 
with  ACI318. 

1910.6.3  Corrosive  environments:  In  corrosive 
environments  or  other  severe  conditions,  the 
amount  of  concrete  protection  shall  be  suitably 
increased,  and  the  density  and  nonporosity  of 
protection  concrete  shall  be  considered,  or  other 
protection  shall  be  provided. 

1910.6.4  Future  extensions:  Exposed 
reinforcement,  inserts  and  plates  intended  for 
bonding  with  future  extensions  shall  be  protected 
from  corrosion. 

1910.6.5  Fire  protection:  Where  this  code 
requires  a  thickness  of  cover  for  fire  protection 
greater  than  the  minimum  concrete  cover 
specified  in  780  CMR  1910.6.1  or  ACI318,  such 
greater  thickness  shall  be  used. 

780  CMR  1911.0  SHOTCRETE 

1911.1  General:  Except  as  specified  in  780  CMR 
911.0,  shotcrete  shall  conform  to  the  requirements 
for  plain  concrete  or  reinforced  concrete.  Shotcrete 
is  mortar  or  concrete  which  is  pneumatically 
projected  at  a  high  velocity  onto  a  surface. 

1911.2  Proportioning:  Shotcrete  proportions  shall 
be  selected  that  allow  suitable  placement  procedures 
using  the  delivery  equipment  selected,  and  that 
results  in  in-place  hardened  shotcrete  conforming  to 
the  strength  requirements  of  780  CMR. 

1911.3  Aggregate:  Coarse  aggregate,  if  used,  shall 
not  exceed  V*  inch  (19  mm)  in  size. 

1911.4  Reinforcement:  Reinforcement  shall  comply 
with  780  CMR  1911.4.1  through  1911.4.3. 

1911.4.1  Size:  The  maximum  size  of 
reinforcement  shall  be  No.  5  bars.  The  code 
official  shall  approve  the  use  of  larger  bars  where 
it  is  demonstrated  that  adequate  encasement  of  the 
larger  bars  will  be  achieved. 

1911.4.2  Spacing:  The  minimum  clearance 
between  parallel  reinforcing  bars  shall  be  2'A 
inches  (64  mm).  Welded  wire  fabric  shall  have 
a  minimum  wire  spacing  of  two  inches  (5 1  mm) 
by  two  inches  (5 1  mm). 

1911.4.3  Splices:  Lap  splices  of  reinforcing  bars 
shall  be  by  the  noncontact  lap-splice  method  with 
at  least  two  inches  (5 1  mm)  of  clearance  between 
bars.  The  code  official  shall  permit  the  use  of 
contact  lap  splices  where  necessary  for  the 
support  of  the  reinforcing  and  provided  that  it  is 
demonstrated  that  adequate  encasement  of  the 
bars  at  the  splice  will  be  achieved. 


1911.5  Rebound:  Any  rebound  or  accumulated 
loose  aggregate  shall  be  removed  from  the  surfaces 
to  be  covered  prior  to  placing  the  initial  or  any 
succeeding  layers  of  shotcrete.  Rebound  shall  not  be 
reused  as  aggregate. 

1911.6  Joints:  Except  where  permitted  herein, 
unfinished  work  shall  not  be  allowed  to  stand  for 
more  than  30  minutes  unless  all  edges  are  sloped  to 
a  thin  edge.  For  structural  elements  which  will  be 
under  compression  and  for  construction  joints  shown 
on  the  approved  (construction  documents,  square 
joints  are  permitted.  Before  placing  additional 
material  adjacent  to  previously  applied  work, 
sloping  and  square  edges  shall  be  cleaned  and 
wetted. 

1911.7  Damage:  Shotcrete  that  exhibits  sags, 
sloughs,  segregation,  honeycombing,  sand  pockets 
or  other  obvious  defects,  shall  be  removed  and 
replaced. 

1911.8  Curing:  During  the  curing  periods  specified 
herein,  shotcrete  shall  be  maintained  above  40°F 
(4°C)  and  in  a  moist  condition. 

1911.8.1  Initial  curing:  Shotcrete  shall  be  kept 
continuously  moist  for  24  hours  after  shotcreting 
is  completed  or  shall  be  sealed  with  an  approved 
curing  compound. 

1911.8.2  Final  ruring:  Final  curing  shall  continue 
for  seven  days  after  shotcreting,  or  for  three  days 
if  high-early-strength  cement  is  used,  or  until  the 
specified  strength  is  obtained.  Final  curing  shall 
consist  of  the  initial  curing  process  or  the 
shotcrete  shall  be  covered  with  an  approved 
moisture-retaining  cover. 

1911.8.3  Natural  curing:  Natural  curing  shall  not 
be  used  in  lieu  of  that  specified  in  this  section 
unless  the  relative  humidity  remains  at  or  above 
85%,  and  is  authorized  by  the  registered  design 
professional,  and  approved  by  the  code  official. 

1911.9  Strength  test:  A  strength  test  of  shotcrete 
shall  be  made  in  accordance  with  the  quality 
assurance  provisions  of  ACI  506.2  listed  in 
Appendix  A. 

780  CMR  1912.0  CONCRETE-FELLED 
PIPE  COLUMNS 

1912.1  General:  Concrete-filled  pipe  columns  shall 
be  manufactured  from  standard,  extra-strong  or 
double-extra-strong  steel  pipe  or  tubing  which  is 
filled  with  concrete  so  placed  and  manipulated  as  to 
secure  maximum  density  and  to  insure  complete 
filling  of  the  pipe  without  voids. 

1912.2  Design:  The  safe  supporting  capacity  of 
concrete-filled  pipe  columns  shall  be  computed  in 


348 


780  CMR  -  Sixth  Edition 


2/27/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE 


accordance  with  the  approved  rules  or  as  determined 
by  a  test. 

1912.3  Connections:  All  caps,  base  plates  and 
connections  shall  be  of  approved  types  and  shall  be 
positively  attached  to  the  shell  and  anchored  to  the 
concrete  core.  Welding  of  brackets  without 
mechanical  anchorage  shall  be  prohibited.  Where 
the  pipe  is  slotted  to  accommodate  webs  of  brackets 
or  other  connections,  the  integrity  of  the  shell  shall 
be  restored  by  welding  to  insure  hooping  action  of 
the  composite  section. 

1912.4  Reinforcement:  To  increase  the  safe  load- 
supporting  capacity  of  concrete- filled  pipe  columns, 
the  steel  reinforcement  shall  be  in  the  form  of  rods, 
structural  shapes  or  pipe  embedded  in  the  concrete 
core  with  sufficient  clearance  to  insure  the 
composite  action  of  the  section,  but  not  nearer  than 
one  inch  (25  mm)  to  the  exterior  steel  shell.  All 
structural  shapes  used  as  reinforcement  shall  be 
milled  to  insure  bearing  on  cap  and  base  plates. 


1912.5  Fireresistance  rating  protection:  Pipe 
columns  shall  be  of  such  size  or  so  protected  as  to 
develop  the  required  fireresistance  ratings  specified 
in  Table  602.  Where  an  outer  steel  shell  is  used  to 
enclose  the  fireresistive  covering,  the  shell  shall  not 
be  included  in  the  calculations  for  strength  of  the 
column  section.  The  minimum  diameter  of  pipe 
columns  shall  be  four  inches  (102  mm)  except  that 
in  structures  of  Type  5  construction  not  exceeding 
three  stories  or  40  feet  (12192  mm)  in  height,  pipe 
columns  used  in  the  basement  and  as  secondary  steel 
members  shall  have  a  minimum  diameter  of  three 
inches  (76  mm). 

1912.6  Approvals:  All  details  of  column 
connections  and  splices  shall  be  shop  fabricated  by 
approved  methods  and  shall  be  approved  only  after 
tests  in  accordance  with  the  approved  rides.  Shop- 
fabricated  concrete-filled  pipe  columns  shall  be 
inspected  by  the  code  official  or  by  an  approved 
representative  of  the  manufacturer  at  the  plant. 


2/7/97,   (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


349 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


350  780  CMR  -  Sixth  Edition  2/27/97    (Effective  2/28/97) 


CHAPTER  20 

LIGHTWEIGHT  METALS 

780  CMR  2001.0  GENERAL  780  CMR  2002.0  MATERIALS 

2001.1  Scope:  The  provisions  of  780  CMR  20  shall  2002.1  General:  Aluminum  used  for  structural 
govern  the  materials,  design,  construction  and  purposes  in  buildings  and  structures  shall  comply 
quality  of  aluminum  and  other  lightweight  metal  with  AA  SAS  30  and  AA  ASM  35  listed  in 
alloys.  Appendix  A.    Other  lightweight  metal  alloys  used 

for  structural  purposes  in  buildings  and  structures 
shall  be  of  approved  materials. 


2/7/97  ■  (Effective  2/28/97)  780  CMR  -  Sixth  Edition  35 1 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


352  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  21 


MASONRY 


780  CMR  2101.0  GENERAL 

2101.1  Scope:  The  provisions  of  780  CMR  21  shall 

govern    the    materials,    design,    construction    and 
quality  of  masonry. 

2101.1.1    Engineered    masonry    design:    All 

masonry  shall  conform  to  the  engineered  masonry 
design  requirements  of  Chapters  1  through  8  of 
ACI~530/ASCE  5/TMS  402  listed  in  Appendix  A. 
Exception:  Where  permitted  by  780  CMR 
2104.3,  empirically  designed  masonry  shall 
conform  to  780  CMR  21  and  Chapters  1 
through  4  and  Chapter  9  of  ACI  530/ASCE 
5/TMS  402  listed  in  Appendix  A. 

2101.2  Seismic    requirements:    Masonry    shall 
comply  with  the  requirements  of  780  CMR  2104. 

780  CMR  2102.0  DEFINITIONS 
2102.1   General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  21  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Anchor:  Metal  rod,  wire  or  strap  that  secures 
masonry  to  its  structural  support. 

Architectural  terra  cotta:  Plain  or  ornamental  hard- 
bumed  plastic  clay  units,  larger  in  size  than  brick, 
with  glazed  or  unglazed  ceramic  finish. 

Area,  gross  cross-sectional:  The  areas  delineated  by 
the  out-to-out  dimensions  of  masonry  in  the  plane 
under  consideration. 

Bed  joint:  The  horizontal  layer  of  mortar  on  which 
a  masonry  unit  is  laid 

Brick 

Calcium  silicate  brick  (sand  lime  brick):  A 

building  unit  made  of  sand  and  lime. 

Clay  or  shale:  A  solid  masonry  unit  made  of  clay 

or  shale,  usually  formed  into  a  rectangular  prism 

while  in  the  plastic  state  and  burned  or  fired  in  a 

kiln. 

Concrete  brick:  A  solid  masonry  unit  having  the 

approximate  shape  of  a  rectangular  prism  and 

composed  of  inert  aggregate  particles  embedded 

in  a  hardened  cementitious  matrix. 

Hollow  brick:  A  masonry  unit  made  of  clay  or 

shale  whose  net  cross-sectional  area  in  any  plane 

parallel  to  the  loadbearing  surface  is  not  less  than 

75%  of  its  gross  cross-sectional  area  measured  in 

the  same  plane. 


Buttress:  A  projecting  part  of  a  masonry  wall  built 
integrally  therewith  to  furnish  lateral  stability 
which  is  supported  on  proper  foundations. 

Chimney:  A  primarily  vertical  enclosure  containing 
one  or  more  passageways. 

Chimney,  masonry:  A  field-constructed  chimney  of 
solid  masonry  units,  stones  or  reinforced  concrete 
(see  780  CMR  2114.0). 

Collar  joint:  Vertical  longitudinal  joint  between 
wythes  of  masonry  or  between  masonry  and  back- 
up construction  which  is  permitted  to  be  filled 
with  mortar  or  grout. 

Connector:  A  mechanical  device  for  securing  two  or 
more  pieces,  parts  or  members  together,  including 
anchors,  wall  ties  and  fasteners. 

Diaphragm:  A  roof  or  floor  system  designed  to 
transmit  lateral  forces  to  shear  walls  or  other 
vertical  resisting  elements. 

Dimensions,  nominal:  Equal  to  the  actual  dimension 
plus  the  width  of  the  mortar  joint.  Dimensions 
and  thicknesses  specified  in  this  chapter  are 
nominal  dimensions. 

Effective  height:  Clear  height  of  a  braced  member 
between  lateral  supports  and  used  for  calculating 
the  slenderness  ratio  of  a  member.  Effective 
height  for  unbraced  members  shall  be  calculated. 

Head  joint:  Vertical  mortar  joint  placed  between 
masonry  units  within  the  wythe  at  the  time  the 
masonry  units  are  laid. 

Header  (Bonder):  A  masonry  unit  that  connects  two 
or  more  adjacent  wythes  of  masonry. 

Height,  walls:  The  vertical  distance  from  the 
foundation  wall  or  other  immediate  support  of 
such  wall  to  the  top  of  the  wall. 

Masonry:  A  built-up  construction  or  combination  of 
building  units  or  materials  of  clay,  shale,  concrete, 
glass,  gypsum,  stone  or  other  approved  units 
bonded  together  with  mortar  or  monolithic 
concrete.  Reinforced  concrete  is  not  classified  as 
masonry. 

Ashlar  facing  masonry:  Facing  of  solid 
rectangular  units  larger  in  size  than  brick  and 
made  of  burned  clay  or  shale,  natural  or  cast 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


553 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


stone,  with  sawed,  dressed  and  squared  beds  and 
mortar  joints. 

Ashlar  masonry:  Masonry  composed  of  bonded, 
rectangular  units,  larger  in  size  than  brick,  with 
sawed,  dressed  or  squared  beds  and  mortar  joints. 
Solid  masonry:  Masonry  consisting  of  solid 
masonry  units  laid  contiguously  with  the  joints 
between  the  units  filled  with  mortar,  or  consisting 
of  plain  concrete. 

Masonry  unit 

Clay:  A  building  unit  larger  in  size  than  a  brick, 
composed  of  burned  clay,  shale,  fire  clay  or 
mixtures  thereof. 

Concrete:  A  building  unit  or  block  larger  in  size 
than  12  by  4  by  4  inches  (305  mm  by  102  mm  by 
102  mm)  made  of  cement  and  suitable  aggregates. 
Hollow:  A  masonry  unit  whose  net  cross- 
sectional  area  in  any  plane  parallel  to  the 
loadbearing  surface  is  less  than  75%  of  its  gross 
cross-sectional  area  measured  in  the  same  plane. 
Solid:  A  masonry  unit  whose  net  cross-sectional 
area  in  every  plane  parallel  to  the  loadbearing 
surface  is  75%  or  more  of  its  gross  cross-sectional 
area  measured  in  the  same  plane. 

Mortar:  A  plastic  mixture  of  approved  cementitious 
materials,  fine  aggregates  and  water  used  to  bond 
masonry  or  other  structural  units  (see  780  CMR 
2105.0). 

Mortar,  surface-bonding:  A  mixture  used  to  bond 
concrete  masonry  units  which  contains:  hydraulic 
cement;  glass  fiber  reinforcement  with  or  without 
inorganic  fillers  or  organic  modifiers;  and  water 
(see  780  CMR  2105.8). 

Rubble  masonry:  Masonry  composed  of  roughly 
shaped  stones. 

Coursed  rubble:  Masonry  composed  of  roughly 
shaped  stones  fitting  approximately  on  level  beds 
and  well  bonded.  Random  rubble:  Masonry 
composed  of  roughly  shaped  stones  laid  without 
regularity  of  coursing  but  well  bonded  and  fitted 
together  to  form  well-defined  joints. 
Rough  or  ordinary  rubble:  Masonry  composed 
of  unsquared  field  stones  laid  without  regularity 
of  coursing  but  well  bonded. 

Running  bond:  The  placement  of  masonry  units 
such  that  head  joints  in  successive  courses  are 
horizontally  offset  at  least  one-quarter  the  unit 
length. 

Stack  bond:  The  placement  of  masonry  units  in  a 
bond  pattern  is  such  that  head  joints  in  successive 
courses  are  vertically  aligned  For  the  purpose  of 
this  code,  requirements  for  stack  bond  shall  apply 
to  all  masonry  laid  in  other  than  running  bond. 


Stone  masonry:  Masonry  composed  of  field, 
quarried  or  caststone  units  bonded  by  mortar. 

1.  Stone  masonry,  ashlar:  Stone  masonry 
composed  of  rectangular  units  having  sawed, 
dressed  or  squared  bed  surfaces  and  bonded  by 
mortar. 

2.  Stone  masonry,  rubble:  Stone  masonry 
composed  of  irregular-shaped  units  bonded  by 
mortar. 

Tile,  wall:  Metal  connector  that  connects  wythes  of 
masonry  walls  together. 

Tile:  A  ceramic  surface  unit,  usually  relatively  thin 
in  relation  to  facial  area,  made  from  clay  or  a 
mixture  of  clay  and  other  ceramic  materials, 
called  the  body  of  the  tile,  having  either  a 
"glazed"  or  "unglazed"  face  and  fired  above  red 
heat  in  the  course  of  manufacture  to  a  temperature 
sufficiently  high  enough  to  produce  specific 
physical  properties  and  characteristics  (see 
780  CMR  2105.0). 

Tile,  structural  clay:  A  hollow  masonry  unit 
composed  of  burned  clay,  shale,  fire  clay  or 
mixtures  thereof,  and  having  parallel  cells  (see 
780  CMR  2105.0). 

Wall 

•  Cavity  wall:  A  wall  built  of  masonry  units  or  of 
plain  concrete,  or  a  combination  of  these 
materials,  arranged  to  provide  an  air  space  within 
the  wall,  and  in  which  the  inner  and  outer  parts  of 
the  wall  are  tied  together  with  metal  ties. 
Composite  wall:  A  wall  built  of  a  combination  of 
two  or  more  masonry  units  of  different  materials 
bonded  together,  one  forming  the  backup  and  the 
other  the  facing  elements. 

Dry-stacked,  surface-bonded  walls:  A  wall  built 
of  concrete  masonry  units  where  the  units  are 
stacked  dry,  without  mortar  on  the  bed  or  head 
joints,  and  where  both  sides  of  the  wall  are  coated 
with  a  surface-bonding  mortar  (see  780  CMR 
2106.3). 

Faced  wall:  A  wall  in  which  the  masonry  facing 
and  backing  are  so  bonded  as  to  exert  common 
action  under  load. 

Hollow  wall:  A  wall  built  of  masonry  units  so 
arranged  as  to  provide  an  air  space  within  the 
wall,  and  in  which  the  facing  and  backing  of  the 
wall  are  bonded  together  with  masonry  units. 
Parapet  wall:  That  part  of  any  wall  entirely 
above  the  roof  line. 

Wythe:  Each  continuous,  vertical  section  of  a  wall, 
one  masonry  unit  in  thickness. 


354 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


780  CMR  2103.0  CONSTRUCTION 
DOCUMENTS 

2103.1  Drawings:  The  drawings  and  details  shall 
show  all  the  items  required  to  be  shown  on  the 
drawings  by  780  CMR  including  the  following: 

1.  Specified  size,  grade,  type  and  location  of 
reinforcement,  anchors  and  wall  ties; 

2.  Reinforcing  bars  to  be  welded  and  welding 
procedure; 

3.  Size  and  location  of  all  structural  elements; 
and 

4.  Provision  for  dimensional  changes  resulting 
from  elastic  deformation,  creep,  shrinkage, 
temperature  and  moisture. 

2103.2  Fireplace  drawings:  The  construction 
documents  shall  describe  in  sufficient  detail  the 
location,  size  and  construction  of  all  masonry 
fireplaces.  The  thickness  and  characteristics  of  all 
material  and  the  clearances  from  walls,  partitions 
and  ceilings  shall  be  clearly  indicated. 

780  CMR  2104.0  SEISMIC  REQWREMENTS 

2104.1  Scope:  Seismic  design  requirements  apply  to 
the  design  of  masonry  and  the  construction  of 
masonry  building  elements,  except  masonry  veneers. 
Seismic  requirements  for  masonry  veneers  shall 
comply  with  Chapter  12  of  the  ACI  530/ASCE 
5/TMS  402  Masonry  Code  listed  in  Appendix  A. 
All  masonry  shall  be  designed  to  comply  with  the 
requirements  of  Chapter  7  of  the  ACI  530/ 
ASCE  5/TMS  402  Masonry  Code  listed  in 
Appendix  A,  except  as  otherwise  permitted  herein. 

2104.2  General:  Masonry  structures  and  masonry 
elements  shall  comply  with  the  requirements  of 
780  CMR  2104.3  through  2104.5.  In  addition, 
masonry  structures  and-  masonry  elements  shall 
comply  with  either  the  allowable  stress  design 
requirements  of  Section  5.1  of  the  ACI  530/ASCE 
5/TMS  402  Masonry  Code,  listed  in  Appendix  A  and 
with  780  CMR  2104.2.2  and  2104.2.3,  or  the 
strength  design  requirements  of  780  CMR  2104.2.1 
and  780  CMR  2104.2.3. 

2104.2.1  Strength  requirements:  For  masonry 
structures  that  are  not  designed  in  accordance 
with  Section  5.1  of  the  ACI  530/ASCE  5/TMS 
402  Masonry  Code  listed  in  Appendix  A,  the 
provisions  of  780  CMR  2104.0  shall  apply.  The 
design  strength  of  masonry  structures  and 
masonry  elements  shall  be  at  least  equal  to  the 
required  strength  determined  in  accordance  with 
this  section  except  for  masonry  elements  designed 
in  accordance  with  the  provisions  of  Chapter  9  of 
the  ACI  530/ASCE  5/TMS  402  Masonry  Code 
listed  in  Appendix  A. 

1.  Required  strength:  Required  strength,  U, 
to  resist  seismic  forces  in  such  combinations 
with  gravity  and  other  loads  including  load 
factors  shall  be  as  required  in  780  CMR  1616 


except  that  non-bearing  masonry  walls  shall  be 
designed  for  the  seismic  force  applied 
perpendicular  to  the  plane  of  the  wall  and 
uniformly  distributed  over  the  wall  area. 

2.  Nominal  strength:  The  nominal  strength 
of  masonry  shall  be  taken  as  2Vz  times  the 
allowable  stress  value.  The  allowable  stress 
value  shall  be  determined  in  accordance  with 
Chapter  7  of  the  ACI  530/ASCE  5/TMS  402 
Masonry  Code  listed  in  Appendix  A. 

3.  Design  strength:  The  design  strength  of 
masonry  provided  by  a  member,  its 
connections  to  other  members  and  its  cross 
sections  in  terms  of  flexure,  axial  load,  and 
shear  shall  be  taken  as  the  nominal  strength 
multiplied  by  a  strength  reduction  factor  0,  as 
follows; 

a.  Axial  load  and  flexure  except  for  flexural 
tension  in  unreinforced  masonry  <3>  =0.8. 

b.  Flexural  tension  in  unreinforced  masonry 
$  =0.4 

c.  Shear  0  =  0.6 

d.  Shear    and    tension    on    anchor   bolts 
embedded  in  masonry  $  =  0.6 

2104.2.2  Shear  Factor:  When  calculating  shear 
or  diagonal  tension  stresses  using  allowable  stress 
design,  shear  walls  and  beams  which  resist 
seismic  forces  shall  be  designed  to  resist  1.33 
times  the  seismic  shear  forces  obtained  from  an 
analysis  of  the  building. 

2104.2.3  Drift  limits:  The  design  story  drift  of 
masonry  structures  due  to  the  combination  of 
seismic  forces  and  gravity  loads  shall  not  exceed 
0.007  times  the  story  height.  The  drift  shall  be 
calculated  using  load  combinations  7  or  8  for 
strength  design  in  780  CMR  1616.3  1  with  the 
seismic  deflections  multiplied  by  the  seismic 
amplification  factor,  Cd,  given  in  Table  1612.4.4. 

2104.3  Design  of  elements  that  are  not  part  of 
lateral  force  resisting  system: 

2104.3.1  Masonry  elements  that  are  listed  in 
780  CMR  2104.3  and  isolated  from  the  structure 
so  that  vertical  and  lateral  forces  are  not  imparted 
to  these  elements  and  that  are  not  part  of  the 
lateral  force  resisting  system  shall  comply  with 
the  provisions  of  780  CMR  2104.3  and  may  be 
designed  in  accordance  with  the  provisions  of 
Chapter  9  of  the  ACI  530/ASCE  5/TMS  402 
Masonry  Code  listed  in  Appendix  A. 

2104.3.2  Load  bearing  frames  or  columns  that  are 
not  part  of  the  lateral  force  resisting  system  shall 
be  analyzed  as  to  their  effect  on  the  response  of 
the  system.  Such  frames  or  columns  shall  be 
adequate  for  vertical  load  carrying  capacity  and 
induced  moment  due  to  the  design  story  drift. 

2104.3.3    Anchorage    Of    Masonry    Walls 

Masonry  walls  shall  be  anchored  to  the  roof  and 
all  floors  that  provide  lateral  support  out  of  plane 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


555 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


for  the  wall.  The  anchorage  shall  provide  a  direct 
connection  between  the  walls  and  the  floor  or  roof 
construction.  The  connections  shall  be  capable  of 
resisting  the  greater  of  the  seismic  lateral  force 
induced  by  the  wall  or  120  pounds  per  lineal  foot 
of  wall  (allowable  stress  design),  or  200  pounds 
per  lineal  foot  of  wall  (strength  design). 

2104.3.4  Masonry  partition  walls  16  feet  or  less 
in  height,  masonry  screen  walls  and  other 
masonry  elements,  except  those  listed  in 
780  CMR  2104.3.6,  that  are  not  designed  to  resist 
vertical  or  lateral  loads,  other  than  those  induced 
by  their  own  mass,  shall  be  isolated  from  the 
structure  so  that  vertical  and  lateral  forces  are  not 
imparted  to  these  elements.  Isolation  joints  and 
connectors  between  these  elements  and  the 
structure  shill  be  designed  to  accommodate  the 
design  story  drift.  Masonry  elements  listed  in 
780  CMR  2104.3.4  shall  be  reinforced  in  either 
the  horizontal  or  vertical  direction  in  accordance 
with  the  following; 

1.  Horizontal  reinforcement:  Horizontal 
reinforcement  shall  consist  of  at  least  two 
longitudinal  W1.7  wires  spaced  not  more  than 
16  in.  (vertically)  for  walls  greater  than  four 
inches  in  width  and  at  least  one  longitudinal 
W1.7  wire  spaced  not  more  than  16  inches  for 
walls  not  exceeding  four  inches  in  width;  or  at 
least  one  No.  4  bar  spaced  not  more  than  48 
inches  Where  two  longitudinal  wires  of  joint 
reinforcement  are  used,  the  space  between 
these  wires  shall  be  the  widest  that  the  mortar 
joint  will  accommodate.  Horizontal 
reinforcement  shall  be  provided  within  16 
inches  of  the  top  and  bottom  of  these  masonry 
elements;  OR 

2.  Vertical  reinforcement:  Vertical 
reinforcement  shall  consist  of  at  least  one 
No.  4  bar  spaced  not  more  than  48  inches 
Vertical  reinforcement  shall  be  located  within 
16  inches  of  the  ends  of  masonry  walls. 

2104.3.5  Masonry  partition  walls,  greater  than  16 
feet  in  height,  masonry  screen  walls  and  other 
masonry  elements  except  those  listed  in  780  CMR 
2104.3.6,  that  are  not  designed  to  resist  vertical  or 
lateral  loads,  other  than  those  induced  by  their 
own  mass,  shall  be  isolated  from  the  structure  so 
that  the  vertical  and  lateral  forces  are  not  imparted 
to  these  elements.  Isolation  joints  and  connectors 
between  these  elements  and  the  structure  shall  be 
designed  to  accommodate  the  design  story  drift. 
Masonry  elements  listed  in  780  CMR  2104.3.5 
shall  be  reinforced  in  accordance  with  the 
following: 

1.  Vertical  reinforcement:  Vertical  re- 
inforcement of  at  least  0.2  square  inches  in 
cross-sectional  area  shall  be  provided  at 
corners,  within  16  inches  of  each  side  of 
openings,  within  eight  inches  of  each  side  of 
movement  joints,  within  eight  inches  of  the 


ends  of  walls,  and  at  a  maximum  spacing  of 
eight  feet. 

2.  Horizontal  reinforcement:  Horizontal 
reinforcement  shall  consist  of  at  least  two 
wires  of  W  1.7  spaced  not  more  than  16  inches. 
Horizontal  reinforcement  of  at  least  0.2  square 
inches  in  cross  sectional  areas  shall  also  be 
provided  at  the  bottom  and  top  of  wall 
openings  and  shall  extend  not  less  than  24 
inches  nor  less  than  40  bar  diameters  past  the 
opening;  continuously  at  structurally  connected 
roof  and  floor  levels;  within  16  inches  of  the 
top  of  walls;  and  at  a  maximum  spacing  of 
eight  feet. 

2104.3.6  Nonstructural  masonry  partition  walls 
that  are  isolated  from  the  structure  in  accordance 
with  780  CMR  2104.3.4,  and  2104.3.5,  which 
enclose  stairwells,  exit  discharges,  exits  and 
elevator  shafts  shall  be  designed  for  the  code 
required  lateral  loads  and  at  a  minimum  in 
accordance  with  the  following: 

1.  Vertical  reinforcement:  Vertical 
reinforcement  0.31  square  inches  in  cross 
sectional  area  shall  be  provided  at  corners, 
within  16  inches  of  each  side  of  openings, 
within  eitght  inches  of  each  side  of 
movements  joints,  and  within  eight  inches  of 
the  ends  of  walls  and  at  a  maximum  spacing  of 
six  feet. 

2.  Horizontal  reinforcement:  Horizontal 
reinforcement  shall  consist  of  at  least  two 
wires  of  W  1.7  spaced  not  more  that  16  inches 
Horizontal  reinforcement  of  at  least  0.20 
square  inches  in  cross-sectional  area  shall  also 
be  provided  at  the  bottom  and  top  of  wall 
openings  and  shall  extend  not  less  than  24 
inches  nor  less  than  40  bar  diameters  past  the 
opening;  continuously  at  structurally  connected 
roof  and  floor  levels;  and  within  16  inches  of 
the  top  of  walls;  or 

3.  Walls  spanning  horizontally:  Walls  which 
are  designed  to  span  horizontally,  shall  comply 
with  780  CMR  2104.3.6  and  the  following: 
horizontal  reinforcement  shall  consist  of  at 
least  two  wires  of  W.  1.7  spaced  not  more  than 
16  inches.  Horizontal  reinforcement  of  at  least 
0.3 1  square  inches  in  cross-sectional  area  shall 
also  be  provided  at  the  bottom  and  top  of  wall 
openings  and  shall  extend  not  less  than  24 
inches  nor  less  than  40  bar  diameters  past  the 
opening.  Horizontal  reinforcement  of  at  least 
0.31  square  inches  shall  be  provided 
continuously  at  structurally  connected  roof  and 
floor  levels,  within  16  inches  of  the  top  of 
walls  and  at  a  maximum  of  six  feet. 

2104.3.7  Masonry  walls  listed  in  780  CMR 
2104.3,  that  are  NOT  isolated  from  the  structure 
as  required  in  780  CMR  2104.3.4  and  2104.3.5, 
shall  be  designed  to  withstand  the  induced  forces. 


356 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


2104.4  Design  of  elements  which  are  part  of  the 
lateral  force  resisting  system,  bearing  walls,  exterior 
walls,  parapets  and  chimneys. 

2104.4.1  Connections  to  masonry  shear  walls: 

Connectors  shall  he  provided  to  transfer  forces 
between  horizontal  elements  and  masonry  walls  in 
accordance  with  the  requirements,  of  Section 
5. 1 1  of  the  ACI  530/ASCE  5/TMS  402  Masonry 
Code  listed  in  Appendix  A.  Connectors  shall  be 
designed  to  transfer  horizontal  design  forces 
acting  either  perpendicular  or  parallel  to  the  wall, 
but  not  less  than  200  pounds  per  lineal  foot  of 
wall  (allowable  stress  design)  or  335  pounds  per 
lineal  foot  of  wall  (strength  design).  The 
maximum  spacing  between  connectors  shall  be 
four  feet. 

2104.4.2  Connections   to   masonry   columns: 

Connectors  shall  be  provided  to  transfer  forces 
between  masonry  columns  and  horizontal 
elements  in  accordance  with  the  requirements  of 
Section  5.11  of  ACI  530/ASCE  5/TMS  402 
Masonry  Cede  listed  in  Appendix  A.  Where 
anchor  bolts  are  used  to  connect  horizontal 
elements  to  the  tops  of  columns,  anchor  bolts 
shall  be  placed  within  lateral  ties.  Lateral  tics 
shall  enclose  both  the  vertical  bars  in  the  column 
and  the  anchor  bolts.  There  shall  be  a  minimum  of 
two  No,  4  lateral  ties  provided  in  the  top  five 
inches  of  the  column. 

2104.4.3  Minimum  reinforcement 
requirements  for  bearing  walls,  exterior  walls, 
shear  walls,  parapets  and  chimneys:  These 
walls  shall  be  reinforced  in  both  the  vertical  and 
horizontal  direction.  The  sum  of  the  cross- 
sectional  area  of  horizontal  and  vertical 
reinforcement  shall  be  at  least  0.002  times  the 
gross  cross-sectional  area  of  the  wall,  and  the 
minimum  cross-sectional  area  in  each  direction 
shall  he  not  less  than  0.0007  times  the  gross  cross- 
sectional  area  of  the  wall.  Reinforcement  shall  be 
uniformly  distributed.  The  maximum  spacing  of 
reinforcement  shall  be  48  inches  The  maximum 
spacing  of  reinforcement  for  stack  bond  masonry 
shall  be  24". 

2104.4.4  Shear  wall  additional  reinforcing 
requirements  for  buildings  classified  in  Seismic 
Performance  Category  D:  The  maximum 
spacing  of  vertical  and  horizontal  reinforcement 
shall  be  the  smaller  of;  one-third  the  length  of  the 
shear  wall,  one-third  the  height  of  the  shear  wall, 
or  48  inches  The  minimum  cross-sectional  area  of 
vertical  reinforcement  per  horizontal  foot  of  shear 
wall  shall  be  one-third  of  the  required  shear 
reinforcement  per  vertical  foot  of  shear  wall. 
Shear  reinforcing  shall  be  anchored  around 
vertical  reinforcing  bars  with  a  standard  hook. 

2104.4.5  Minimum  reinforcement  for  masonry 
columns:  Lateral  ties  in  masonry  columns  shall 


be  spaced  not  more  than  eieht  inches  on  center 
and  shall  be  at  least  %  inches  diameter.  Lateral 
ties  shall  be  embedded  in  grout. 

2104.4.6  Material  requirement:  Neither  Type  N 
mortar  nor  masonry  cement  shall  be  used  as  part 
of  the  lateral  force  resisting  system. 

2104.4.7  Lateral  tie  anchorage:  Standard  hooks 
for  lateral  tie  anchorage  shall  be  either  a  135 
degree  standard  hook  or  a  180  degree  standard 
hook. 

2104.5  Inspection:  Masonry  shall  be  inspected  in 
accordance  with  780  CMR  1705.7. 

780  CMR  2105.0  MASONRY 
CONSTRUCTION  MATERIALS 

2105.1  Concrete  masonry  units:  Concrete  masonry 
units  shall  conform  to  the  following  standards  listed 
in  Appendix  A:  ASTM  C55  for  concrete  brick; 
ASTM  C73  for  calcium  silicate  face  brick;  ASTM 
C90  for  loadbearing  concrete  masonry  units;  or 
ASTM  C744  for  prefaced  concrete  and  calcium 
silicate  masonry  units. 

2105.2  Clay  or  shale  masonry  units:  Clay  or  shale 
masonry  units  shall  conform  to  the  following 
standards  listed  in  Appendix  A:  ASTM  C34  for 
structural  clay  loadbearing  wall  tile;  ASTM  C56  for 
structural  clay  nonloadbearing  wall  tile;  ASTM  C62 
for  building  brick  (solid  masonry  units  made  from 
clay  or  shale);  ASTM  CI 088  for  solid  units  of  thin 
veneer  brick;  ASTM  CI 26  for  ceramic-glazed 
structural  clay  facing  tile,  facing  brick  and  solid 
masonry  units;  ASTM  C212  for  structural  clay 
facing  tile;  ASTM  C216  for  facing  brick  (solid 
masonry  units  made  from  clay  or  shale);  and  ASTM 
C652  for  hollow  brick  (hollow  masonry  units  made 
from  clay  or  shale). 

Exception:  Structural  clay  tile  for  nonstructural 
use  in  fireproofing  of  structural  members  and  in 
wall  furring  shall  not  be  required  to  meet  the 
compressive  strength  specifications.  The 
fireresistance  rating  shall  be  determined  in 
accordance  with  ASTM  El  19  listed  in 
Appendix  A  and  shall  comply  with  the 
requirements  of  Table  602. 

2105.3  Stone  masonry  units:  Stone  masonry  units 
shall  conform  to  the  following  standards  listed  in 
Appendix  A:  ASTM  C503  for  marble  building  stone 
(exterior);  ASTM  C568  for  limestone  building  stone; 
ASTM  C615  for  granite  building  stone;  ASTM 
C616  for  sandstone  building  stone;  or  ASTM  C629 
for  slate  building  stone. 

2105.4  Ceramic  tile:  Ceramic  tile  shall  be  as 
defined  in  ANSI  A137. 1  listed  in  Appendix  A  and 
shall  conform  to  the  requirements  of  ANSI  A137.1 
listed  in  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


357 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2105.5  Glass  block:  Glass  block  shall  be  partially 
evacuated,  hollow  masonry  units  made  of  clear, 
colorless  glass  (with  or  without  a  highly  reflective 
oxide  surface  coating),  having  a  thickness  of  not  less 
than  31/8  inches  or  shall  be  solid  glass-block  units, 
having  a  thickness  of  not  less  than  three  inches. 

2105.6  Second-hand  units:  Second-hand  masonry 
units  shall  not  be  reused  unless  the  units  conform  to 
the  requirements  for  new  units.  The  units  shall  be  of 
whole,  sound  material  and  be  free  from  cracks  and 
other  defects  that  will  interfere  with  proper  laying  or 
use.  All  old  mortar  shall  be  cleaned  from  the  units 
before  reuse. 

2105.7  Mortar:  Mortar  for  masonry  construction 
shall  conform  to  ASTM  C270  listed  in  Appendix  A. 

2105.8  Surface-bonding  mortar:  Surface-bonding 
mortar  shall  comply  with  ASTM  C887  listed  in 
Appendix  A.  Surface  bonding  of  concrete  masonry 
units  shall  comply  with  ASTM  C946  listed  in 
Appendix  A. 

2105.9  Metal    reinforcement    and    accessories: 

Metal  reinforcement  and  accessories  shall  conform 
to  780  CMR  2105.9.1  through  2105.9.7.  Where 
unidentified  reinforcement  is  approved  for  use,  such 
reinforcement  shall  be  tested  in  accordance  with 
780  CMR  2208.1. 

2105.9.1  Deformed  reinforcing  bars:  Deformed 
reinforcing  bars  shall  conform  to  the  following 
standards  listed  in  Appendix  A :  ASTM  A6 1 5  for 
deformed  and  plain  billet-steel  bars  for  concrete 
reinforcement;  ASTM  A616  for  rail-steel 
deformed  and  plain  bars  for  concrete 
reinforcement;  ASTM  A617  for  axle-steel 
deformed  and  plain  bars  for  concrete 
reinforcement;  and  ASTM  A706  for  low-alloy- 
steel  deformed  bars  for  concrete  reinforcement. 

2105.9.2  Joint  reinforcement:  Joint  reinforcing 
wire  shall  conform  to  the  following  standards 
listed  in  Appendix  A:  ASTM  A82  for  steel  wire, 
plain,  for  concrete  reinforcement;  and  ASTM 
A167,  Type  304,  for  stainless  and  heat-resisting 
chromium-nickel  steel  plate,  sheet  and  strip. 

Longitudinal  wires  shall  be  deformed.  One  set 
of  two  deformations  shall  occur  around  the 
perimeter  of  the  wire  at  a  maximum  spacing  of 
0.7  times  the  diameter  of  the  wire  but  not  less 
than  eight  sets  per  one  inch  (25  mm)  of  length. 
The  overall  length  of  each  deformation  within  the 
set  shall  be  such  that  the  summation  of  gaps 
between  the  ends  of  the  deformations  shall  not 
exceed  33%  of  the  perimeter  of  the  wire.  The 
indentation  depth  of  the  deformations  shall  be 
0.006  inch  (0.15  mm)  plus  or  minus  0.003  inch 
(0.08  mm). 


2105.9.3  Deformed  reinforcing  wire:  Deformed 
reinforcing  wire  shall  conform  to  ASTM  A496 
listed  in  Appendix  A. 

2105.9.4  Wire  fabric:  Wire  fabric  shall  conform 
to  ASTM  A185  listed  in  Appendix  A  for  plain 
steel-welded  wire  fabric  for  concrete 
reinforcement  or  ASTM  A497  listed  in 
Appendix  A  for  welded  deformed  steel  wire  fabric 
for  concrete  reinforcement. 

2105.9.5  Anchors,     ties     and     accessories: 

Anchors,  ties  and  accessories  shall  conform  to  the 
following  standards  listed  in  Appendix  A:  ASTM 
A36  for  structural  steel;  ASTM  A82  for  plain 
steel  wire  for  concrete  reinforcement;  ASTM 
A 185  for  plain  steel-welded  wire  fabric  for 
concrete  reinforcement;  ASTM  A167,  Type  304, 
for  stainless  and  heat-resisting  chromium-nickel 
steel  plate,  sheet  and  strip;  and  ASTM  A366  for 
cold-rolled  carbon  steel  sheet,  commercial 
quality. 

2105.9.6  Corrosion  protection:  Joint 
reinforcement  anchors,  wall  ties  and  accessories, 
except  those  of  Type  304  stainless  steel 
complying  with  ASTM  A  167  listed  in 
Appendix  A,  shall  be  protected  from  corrosion  by 
galvanizing  as  follows. 

Metal  accessories  for  use  in  exterior  wall 
construction  shall  be  hot-dipped  galvanized  after 
fabrication  with  a  minimum  coating  of  1.5  ounces 
per  square  foot  (458  g/m2)  in  accordance  with 
ASTM  A153  listed  in  Appendix  A.  Metal 
accessories  for  use  in  interior  wall  construction 
shall  be  mill  galvanized  with  a  minimum  coating 
of  0.1  ounce  per  square  foot  (31  g/m2)  in 
accordance  with  the  standards  listed  in 
Appendix  A  as  follows:  ASTM  A64 1  for  joint 
reinforcement,  wire  anchors  and  ties;  and  ASTM 
A525,  Class  G-60,  for  sheet  metal  anchors  and 
ties. 

2105.9.7  Tests:  Where  unidentified  reinforcement 
is  approved  for  use,  not  less  than  three  tension  and 
three  bending  tests  shall  be  made  on 
representative  specimens  of  the  reinforcement 
from  each  shipment  and  grade  of  reinforcing  steel 
proposed  for  use  in  the  work. 

2105.10  Mortars  for  ceramic  wall  and  floor  tile: 

Portland  cement  mortars  for  installing  ceramic  wall 
and  floor  tile  shall  comply  with  ANSI  A 108. 1  listed 
in  Appendix  A  and  be  of  the  compositions  indicated 
in  Table  2105. 10. 

2105.10.1   Dry-set  portland  cement  mortars: 

Premixed  prepared  portland  cement  mortars, 
which  require  only  the  addition  of  water  and 
which  are  used  in  the  installation  of  ceramic  tile, 
shall  comply  with  ANSI  All 8.1  listed  in 
Appendix  A  The  shear  bond  strength  for  tile  set  in 
such  mortar  shall  be  as  required  in  accordance 
with  ANSI  Al  18.1  Wstsd'm  Appendix  A.  Tile  set 


358 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


in  dry-set  portland  cement  mortar  shall  be 
installed  in  accordance  with  ANSI  A108.5  listed 
in  Appendix  A. 

2105.10.2  Electrically  conductive  dry-set 
mortars:  Premixed  prepared  portland  cement 
mortars,  which  require  only  the  addition  of  water 
and  which  comply  with  ANSI  A118.2  listed  in 
Appendix  A,  shall  be  used  in  the  installation  of 
electrically  conductive  ceramic  tile.  Tile  set  in 
electrically  conductive  dry-set  mortar  shall  be 
installed  in  accordance  with  ANSI  A 108. 7  listed 
in  Appendix  A. 

Table  2105.10 
CERAMIC  TILE  MORTAR  COMPOSITIONS 


Walls 

Scratchcoat 

1  cement;  1  /5  hydrated  lime; 
4  dry  or  5  damp  sand 

Setting  bed  and 
leveling  coat 

1  cement.  14  hydrated  lime; 
5  damp  sand;  to  1  cement; 
1  hydrated  lime;  7  damp  sand 

Floors 

Setting  bed 

1  cement;  1/10  hydrated  lime. 
5  drv  or  6  damp  sand;  or  1 
cement,  5  dry  or  6  damp  sand 

Ceilings 

Scratchcoat  and 

sand  bed 

1  cement;'/;  hydrated  lime;  2V: 
drv  sand  or  3  damp  sand 

2105.10.3  Latex-modified  portland  cement 
mortars:  Latex -modified  portland  cement  thin- 
set  mortars-in  which  latex  is  added  to  dry-set 
mortar  as  a  replacement  for  all  or  part  of  the 
gauging  water-which  are  used  for  the  installation 
of  ceramic  tile  shall  comply  with  ANSI  A118.4 
listed  in  Appendix  A.  Tile  set  in  latex-modified 
portland  cement  shall  be  installed  in  accordance 
with  ANSI  A108.5  listed  in  Appendix  A 

2105.10.4  Epoxy  mortar:  Ceramic  tile  set  and 
grouted  with  chemical-resistant  epoxy  shall 
comply  with  ANSI  Al  18.3  listed  in  Appendix  A 
Tile  set  and  grouted  with  epoxy  shall  be  installed 
in  accordance  with  ANSI  A108  6  listed  in 
Appendix  A. 

2105.10.5  Furan  mortar  and  grout:  Chemical- 
resistant  furan  mortar  and  grout  which  are  used  to 
install  ceramic  tile  shall  comply  with  ANSI 
A118.5  listed  in  Appendix  A  Tile  set  and 
grouted  with  furan  shall  be  installed  in  accordance 
with  ANSI  Al  08.8  listed  in  Appendix  A 

2105.10.6  Modified  epoxy-emulsion  mortar  and 
grout:  Modified  epoxy-emulsion  mortar  and 
grout  which  are  used  to  install  ceramic  tile  shall 
comply  with  ANSI  Al  18 .8  listed  in  Appendix  A 
Tile  set  and  grouted  with  modified  epoxy- 
emulsion  mortar  and  grout  shall  be  installed  in 
accordance  with  ANSI  A108.9  listed  in 
Appendix  A. 

2105.10.7  Organic  adhesives:  Water-resistant 
organic  adhesives  used  for  the  installation  of 
ceramic  tile  shall  comply  with  ANSI  A136.1  listed 
in  Appendix  A.  The  shear  bond  strength  after  water 


immersion  shall  not  be  less  than  40  psi  (0.028 
kg/mm2)  for  Type  I  adhesive,  and  not  less  than  20 
psi  (0.014  kg/mnr)  for  Type  II  adhesive,  when 
tested  in  accordance  with  ANSI  A136.1  listed  in 
Appendix  A.  Tile  set  in  organic  adhesives  shall  be 
installed  in  accordance  with  ANSI  A108.4  listed  in 
Appendix  A. 

2105.10.8  Portland  cement  grouts  Portland 
cement  grouts  used  for  the  installation  of  ceramic 
tile  shall  comply  with  ANSI  A  118.6  listed  in 
Appendix  A  Portland  cement  grouts  for  tilework 
shall  be  installed  in  accordance  with  ANSI  A108.10 
listed  in  Appendix  A 

2105.11  Grout:  Grout  shall  conform  to  ASTM  C476 
listed  m  Appendix  A 

780  CMR  2106.0  LATERAL  STABDLTrV 

2106.1  Shear  walls:  Where  the  structure  depends 
upon  masonry  walls  for  lateral  stability,  shear  walls 
shall  be  provided  parallel  to  the  direction  of  the 
lateral  forces  resisted. 

2106.1.1  Shear  wall  thickness  Minimum 
nominal  thickness  of  masonry  shear  walls  shall  be 
eight  inches 

Exception:  Shear  walls  of  one-story  buildings 
are  permitted  to  be  a  minimum  nominal 
thickness  of  six  inches. 

2106.1.2  Cumulative  length  of  shear  walls    In 

each  direction  in  which  shear  walls  are  required 
for  lateral  stability,  the  minimum  cumulative 
length  of  shear  walls  provided  shall  be  0.4  times 
the  long  dimension  of  the  building.  Cumulative 
length  of  shear  walls  shall  not  include  openings. 

2106.1.3  Maximum  diaphragm  ratio  Masonry 
shear  walls  shall  be  provided  so  that  the  span-to- 
width  (or  depth)  ratio  of  floor  or  roof  diaphragms 
does  not  exceed  that  indicated  in  Table  2106.1 .3. 

Table  2106.1.3 

MAXIMUM  SPAN-TO-WIDTH  (DEPTH) 

RATIO  OF  FLOOR  AND  ROOF 

DIAPHRAGMS 


Floor  or  roof 
diaphragm  construction 


Maximum  span-to-width 
(depth)  ratio  of  Diaphragm 


Cast-in-place  concrete 

5:1 

Precast  concrete 

4.1 

Metal  deck  with  concrete 

3:1 

fill 

Metal  deck  -without  fill 

2:1 

Wood  diaphragm 

2:1 

2106.2  Roofs:  The  roof  construction  shall  be 
designed  so  as  not  to  impart  out-of-plane  lateral 
thrust  to  the  walls  under  roof  gravity  load. 

2106.3  Surface-bonded  walls  Dry-stacked, 
surface-bonded  concrete  masonry  walls  shall  comply 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


359 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


with  the  requirements  of  780  CMR  for  masonry  wall 
construction,  except  where  otherwise  noted  in 
780  CMR  2 106 

2106.3.1  Strength:  Dry-stacked,  surface-bonded 
concrete  masonry  walls  shall  be  of  adequate 
strength  and  proportions  to  support  all 
superimposed  loads  without  exceeding  the 
allowable  stresses  listed  in  Table  2106.3.1. 
Allowable  stresses  not  specified  in  Table  2106.3.1 
shall  comply  with  the  requirements  of  ACI 
530/ASCE  5/TMS  402  listed  in  Appendix  A. 

Table  2106.3.1 
ALLOWABLE  STRESS  GROSS  CROSS- 
SECTIONAL  AREA  FOR  DRY-STACKED, 
SURFACE-BONDED  CONCRETE 
MASONRY  WALLS 
Compression 
standard  block 


Shear 

Flexural  tension 
Vertical  span 
Horizontal  span 


45  psi 
lOpsi 


ISpsi 

30  psi 


2106.4  Construction:  Construction  of  dry-stacked, 
surface-bonded  masonry  walls,  including  stacking 
and  leveling  of  units,  mixing  and  application  of 
mortar,  and  curing  and  protection,  shall  comply  with 
ASTM  C946  listed  in  Appendix  A. 

780  CMR  2107.0  COMPRESSIVE  STRESS 
REQLTREMENTS 

2107.1  Vertical  dead  plus  live  loads:  Compressive 
stresses  in  masonry  due  to  vertical  dead  plus  live 
loads  (excluding  wind  or  seismic  loads)  shall  be 
determined  in  accordance  with  780  CMR  2107.2.1. 
Dead  and  live  loads  shall  be  in  accordance  with 
780  CMR  16,  with  such  live  load  reductions  as  are 
permitted  in  780  CMR  1608.0. 

2107.2  Maximum  values:  The  compressive  stresses 
in  masonry  shall  not  exceed  the  values  given  in 
Table  2107.2.  Stress  shall  be  calculated  based  on 
actual  rather  than  nominal  dimensions. 

2107.2.1  Calculated     compressive    stresses: 

Calculated  compressive  stresses  for  single-wythe 
walls  and  for  multiple-wythe  composite  masonry 
walls  shall  be  determined  by  dividing  the  design 
load  by  the  gross  cross-sectional  area  of  the 
member  The  area  of  openings,  chases  or  recesses 
in  walls  shall  not  be  included  in  the  gross  cross- 
sectional  area  of  the  wall. 

2107.2.2  Multiple-wythe  walls:  The  allowable 
stress  shall  be  as  given  in  Table  2107.2  for  the 
weakest  combination  of  the  units  and  mortar  used 
in  each  wythe. 


Table  2107.2 
ALLOWABLE  COMPRESSIVE  STRESSES 
FOR  EMPIRICAL  DESIGN  OF  MASONRY 


Construction,  compressive 

strength  of  unit,  gross 

area,  psi 

Allowable  compressive  stresses 
gross  cross-sectional  area,  psi 

Type  M  or  S 
mortar 

TypeN 
mortar 

Solid  masonry  of  brick 

and  other  solid  units  of 

clav  or  shale;  sand-lime  or 

concrete  brick: 

8,000  or  greater 

350 

300 

4,500 

225 

200 

2,500 

160 

140 

1,500 

115 

100 

Grouted  masonrv  of  clay 

or  shale,  sand-lime  or 

concrete: 

4,500  or  greater 
2,500 

225 
160 

200 
140 

1,500 

115 

100 

Solid  masonrv  of  solid 

concrete  masonry  units: 
3.000  or  greater 
2,000 

225 
160 

200 
140 

1.200 

115 

100 

Masonrv  of  hollow 

ioadbeanng  units: 

2,000  or  greater 

140 

120 

1,500 

115 

100 

1,000 

75 

70 

750 

60 

55 

Hollow  walls 

(noncomposite  masonry 
bonded"'', 

Solid  units: 

2,500  or  greater 
1,500 

160 
115 

140 
100 

Hollow  units 

75 

70 

Stone  ashlar  masonry: 
Granite 

720 

640 

Limestone  or  marble 

450 

400 

Sandstone  or  cast  stone 

360 

320 

Rubble  stone  masonrv 

Coursed,  rough  or 

random 

120 

100 

Note  a  .  Linear  interpolation  for  determining  allowable 
stresses  for  masonry  units  having  compressive  strengths 
which  are  intermediate  between  those  given  in  the  table 
is  permitted. 

Note  b.  Where  floor  and  roof  loads  are  carried  upon 
one  wythe,  the  gross  cross-sectional  area  is  that  of  the 
wythe  under  load:  if  both  wythes  are  loaded,  the  gross 
cross-sectional  area  is  that  of  the  wall  minus  the  area  of 
the  cavity  between  the  wythes.  Walls  bonded  with  metal 
ties  shall  be  considered  as  noncomposite  walls  unless 
collar  joints  are  filled  with  mortar  or  grout. 

780  CMR  2108.0  LATERAL  SUPPORT 
2108.1  General:  Masonry  walls  shall  be  laterally 
supported  in  either  the  horizontal  or  the  vertical 


360 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


direction  at  intervals  not  exceeding  those  given  in 
Table  2108.1. 

2108.1.1  Thickness:  Except  for  cavity  walls  and 
cantilever  walls,  the  thickness  of  a  wall  shall  be 
the  nominal  thickness  measured  perpendicular  to 
the  face  of  the  wall.  For  cavity  walls,  the 
thickness  shall  be  determined  as  the  sum  of  the 
nominal  thicknesses  of  the  individual  wythes.  For 
cantilever  walls,  except  for  parapets,  the  ratio  of 
height  to  nominal  thickness  shall  not  exceed  6:1 
for  solid  masonry  or  4: 1  for  hollow  masonry.  The 
thickness  and  height  of  parapets  shall  conform  to 
780  CMR  2109.2. 

2108.2  Lateral  support:  Lateral  support  shall  be 
provided  by  cross  walls,  pilasters,  buttresses  or 
structural  frame  members  where  the  limiting 
distance  is  taken  horizontally,  or  by  floors,  or  roofs 
acting  as  diaphragms  or  structural  frame  members 
where  the  limiting  distance  is  taken  vertically. 

Table  2108.1 

WALL  LATERAL  SUPPORT 

REQUIREMENTS 


Construction 

Maximum  ratio  of  wall  length 

to  thickness  or  wall  height  to 

thickness 

Loadbeanng  walls 

Sobd  or  solid  grouted 

Mother 
Nonloadbearing  walls 

Exterior 

interior 

20 
18 

18 
36 

780  CMR  2109.0  THICKNESS  OF  MASONRY 

2109.1  Thickness  of  walls:  The  nominal  thickness 
of  masonry  walls  shall  conform  to  the  requirements 
of  780  CMR  2109. 

2109.1.1  Minimum  thickness:  The  minimum 
thickness  of  masonry  loadbeanng  walls  more  than 
one  story  high  shall  be  eight  inches.  The 
minimum  thickness  of  masonry  loadbeanng  walls 
of  one-story  buildings  shall  not  be  less  than  six 
inches. 

2109.1.2  Rubble  stone  walls:  The  minimum 
thickness  of  rough  or  random  or  coursed  rubble 
stone  walls  shall  be  16  inches. 

2109.1.3  Change  in  thickness:  Where  a  wall  of 
masonry  of  hollow  units  or  a  masonry-bonded 
hollow  wall  is  decreased  in  thickness,  a  course  or 
courses  of  solid  masonry  shall  be  interposed 
between  the  wall  below  and  the  thinner  wall 
above,  or  special  units  or  construction  shall  be 
used  to  transmit  the  loads  from  face  shells  or 
wythes  above  to  those  below. 

2109.2  Parapet  walls:  Parapet  walls  shall  be  at  least 
eight  inches  thick,  and  the  height  shall  not  exceed 
three  times  the  thickness  Parapet  walls  shall  be 
reinforced  in  accordance  with  780  CMR  2104.4.3. 


780  CMR  2110.0  BOND 

2110.1  General:  The  facing  and  backing  of 
multiple-wythe  masonry  walls  shall  be  bonded  in 
accordance  with  780  CMR  2110.2,  2110.3  or 
2110.4. 

2110.2  Bonding  with  masonry  headers:  Bonding 
with  solid  or  hollow  masonry  headers  shall  comply 
with  780  CMR  21 10.2. 1  and  21 10.2.2. 

2110.2.1  Solid  units:  Where  the  facing  and 
backing  (adjacent  wythes)  of  solid  masonry 
construction  are  bonded  by  means  of  masonry 
headers,  not  less  than  4%  of  the  wall  surface  of 
each  face  shall  be  composed  of  headers  extending 
not  less  than  three  inches  (76  mm)  into  the 
backing.  The  distance  between  adjacent  full- 
length  headers  shall  not  exceed  24  inches  (610 
mm)  either  vertically  or  horizontally.  In  walls  in 
which  a  single  header  does  not  extend  through  the 
wall,  headers  from  the  opposite  sides  shall  overlap 
at  least  three  inches  (76  mm),  or  headers  from 
opposite  sides  shall  be  covered  with  another 
header  course  overlapping  the  header  below  at 
least  three  inches  (76  mm). 

2110.2.2  Hollow  units  Where  two  or  more 
hollow  units  are  used  to  make  up  the  thickness  of 
a  wall,  the  stretcher  courses  shall  be  bonded  at 
vertical  intervals  not  exceeding  34  inches  (864 
mm)  by  lapping  at  least  three  inches  (76  mm)  over 
the  unit  below,  or  by  lapping  at  vertical  intervals 
not  exceeding  17  inches  (432  mm)  with  units 
which  are  at  least  50%  greater  in  thickness  than 
the  units  below. 

2110.3  Bonding  with  wall  ties  or  joint 
reinforcement:  Bonding  with  wall  ties  or  joint 
reinforcement  shall  comply  with  780  CMR  21 10.3. 1 
through  21 10.3.2. 

2110.3.1  Bonding  with  wall  ties:  Except  as 
required  by  780  CMR  2110.3.1.1,  where  the 
facing  and  backing  (adjacent  wythes)  of  masonry 
walls  are  bonded  with  3/16-inch  diameter  wall  ties 
or  metal  wire  of  equivalent  stiffness  embedded  in 
the  horizontal  mortar  joints,  there  shall  be  at  least 
one  metal  tie  for  each  4V4  square  feet  (0.42  m2)  of 
wall  area.  Ties  in  alternate  courses  shall  be 
staggered.  The  maximum  vertical  distance 
between  ties  shall  not  exceed  24  inches  (610  mm), 
and  the  maximum  horizontal  distance  shall  not 
exceed  36  inches  (914  mm).  Rods  or  ties  bent  to 
rectangular  shape  shall  be  used  with  hollow 
masonry  units  laid  with  the  cells  vertical.  In  other 
walls,  the  ends  of  ties  shall  be  bent  to  90-degree 
(1.57  rad)  angles  to  provide  hooks  not  less  than 
two  inches  (51  mm)  long.  Additional  bonding  ties 
shall  be  provided  at  all  openings,  spaced  not  more 
than  three  feet  (914  mm)  apart  around  the 
perimeter  and  within  12  inches  (305  mm)  of  the 
opening. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2110.3.1.1  Bonding  with  adjustable  wall  ties 

Where  the  facing  and  backing  (adjacent 
wythes)  of  masonry  are  bonded  with  adjustable 
wall  ties,  there  shall  be  at  least  one  tie  for  each 
1 .77  square  feet  (0.16  m2)  of  wall  area.  Neither 
the  vertical  nor  horizontal  spacing  of  the 
adjustable  wall  ties  shall  exceed  16  inches  (406 
mm).  The  maximum  vertical  offset  of  bed 
joints  from  one  wythe  to  the  other  shall  be  IV* 
inches  (32  mm).  The  maximum  clearance 
between  connecting  parts  of  the  ties  shall  be 
1/16  inch  (1 .6  mm).  Where  pintle  legs  are  used, 
ties  shall  have  at  least  two  3/16-inch  (5  mm) 
diameter  legs 

2110.3.2  Bonding  with  prefabricated  joint 
reinforcement:  Where  the  facing  and  backing 
(adjacent  wythes)  of  masonry  are  bonded  with 
prefabricated  joint  reinforcement,  there  shall  be  at 
least  one  cross  wire  serving  as  a  tie  for  each  2% 
square  feet  (0.25  m2)  of  wall  area.  The  vertical 
spacing  of  the  joint  reinforcement  shall  not 
exceed  16  inches  (406  mm).  Cross  wires  on 
prefabricated  joint  reinforcement  shall  not  be 
smaller  than  No  9  gage.  The  longitudinal  wires 
shall  be  embedded  in  the  mortar 

2110.4  Bonding   with    natural   or   cast    stone 

Bonding  with  natural  or  cast  stone  shall  conform  to 
780  CMR  2110.4. 1  and  21 10.4.2. 

2110.4.1  Ashlar  masonry:  In  ashlar  masonry, 
uniformly  distributed  bonder  units  shall  be 
provided  to  the  extent  of  not  less  than  10%  of  the 
wall  area.  Such  bonder  units  shall  extend  not  less 
than  four  inches  (  102  mm  )  into  the  backing  wall. 

2110.4.2  Rubble  stone  masonry  Rubble  stone 
masonry  24  inches  or  less  in  thickness  shall  have 
bonder  units  with  a  maximum  spacing  of  3  feet 
(914  mm)  vertically  and  three  feet  (914  mm) 
horizontally  Rubble  stone  masonry  greater  than 
24  inches  in  thickness  shall  have  one  bonder  unit 
for  each  six  square  feet  (0.56  m2)  of  wall  surface 
on  both  sides. 

2110.5  Masonry  bonding  pattern:  Masonry  laid  in 
running  and  stack  bond  shall  conform  to  780  CMR 
2110.5.1  and  2110.5.2. 

2110.5.1  Masonry  laid  in  running  bond:  In  each 
wythe  of  masonry  laid  in  running  bond,  head 
joints  in  successive  courses  shall  be  offset  by  not 
less  than  one-fourth  the  unit  length,  or  the 
masonry  walls  shall  be  reinforced  longitudinally 
as  required  in  780  CMR  21 10.5.2. 

2110.5.2  Masonry  laid  in  stack  bond:  Where 
unit  masonry  is  laid  with  less  head  joint  offset 
than  in  780  CMR  2 1 1 0. 5 . 1 ,  the  minimum  area  of 
horizontal  reinforcement  placed  in  mortar  bed 
joints  or  in  bond  beams  spaced  not  more  than  48 


inches  (1219  mm)  apart  shall  be  0.0007  times  the 
vertical  cross-sectional  area  of  the  wall 

780  CMR  2111.0  ANCHORAGE 

2111.1  General:  Masonry  elements  shall  be 
anchored  in  accordance  with  780  CMR  2111.0. 

2111.2  Intersecting  walls:  Masonry  walls 
depending  upon  one  another  for  lateral  support  shall 
be  anchored  or  bonded  at  locations  where  the  walls 
meet  or  intersect  by  one  of  the  following  methods 
indicated  in  780  CMR  2111.2.1  through  2111 .2.5. 

2111.2.1  Bonding  pattern:  50%  of  the  units  at 
the  intersection  shall  be  laid  in  an  overlapping 
masonry  bonding  pattern,  with  alternate  units 
having  a  bearing  of  not  less  than  three  inches  (76 
mm)  on  the  unit  below. 

2111.2.2  Steel  connectors  Walls  shall  be 
anchored  by  steel  connectors  having  a  minimum 
cross  section  of  Vi-inch  by  I '/:  inches  with  ends 
bent  up  at  least  two  inches  (5 1  mm),  or  with  cross 
pins  to  form  anchorage  Such  anchors  shall  be  at 
least  24  inches  (610  mm)  long  and  the  maximum 
spacing  shall  be  four  feet  (1219  mm). 

2111.2.3  Joint  reinforcement  Walls  shall  be 
anchored  by  joint  reinforcement  spaced  at  a 
maximum  distance  of  eight  inches  (203  mm). 
Longitudinal  reinforcement  shall  be  at  least  No  9 
gage  and  shall  extend  at  least  30  inches  (762  mm) 
in  each  direction  at  the  intersection. 

2111.2.4  Interior      nonloadbearing      walls 

Interior  nonloadbearing  walls  shall  be  anchored  at 
the  intersection  of  the  walls  at  vertical  intervals  of 
not  more  than  16  inches  (406  mm)  with  joint 
reinforcement  or  Vi-inch  galvanized  mesh 
hardware  cloth. 

2111.2.5  Ties,  joint  reinforcement  and  anchors 

Other  metal  ties,  joint  reinforcement  or  anchors, 
if  used,  shall-be  spaced  to  provide  equivalent  area 
of  anchorage  to  that  required  by  780  CMR 
2111.0. 

2111.3  Floor  and  roof  anchorage  Floor  and  roof 
diaphragms  providing  lateral  support  to  masonry 
shall  comply  with  780  CMR  1612 .4.7.1.2  and  shall 
be  connected  to  the  masonry  by  one  of  the  methods 
specified  in  780  CMR  21 11.3.1  through  2111  3  3 

2111.3.1  Wood  floor  joists  Wood  floor  joists 
supported  by  masonry  walls  shall  be  anchored  to 
the  wall  at  intervals  not  to  exceed  six  feet  (1829 
mm)  by  metal  strap  anchors.  Joists  parallel  to  the 
wall  shall  be  anchored  with  metal  straps  spaced 
not  more  than  six  feet  (1829  mm)  on  centers 
extending  over  or  under  and  secured  to  at  least 
three  joists.  Blocking  shall  be  provided  between 
joists  at  each  strap  anchor. 


362 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


2111.3.2  Steel  floor  joists:  Steel  floor  joists  shall 
be  anchored  to  masonry  walls  with  %-inch  round 
bars,  or  their  equivalent,  spaced  not  more  than  six 
feet  (1829  mm)  on  center.  Where  joists  are 
parallel  to  the  wall,  anchors  shall  be  located  at 
joist  cross  bridging. 

2111.3.3  Roof  structures:  Roof  structures  shall 
be  anchored  to  masonry  walls  with  '/2-inch  bolts 
six  feet  (1829  mm)  on  center.  Bolts  shall  extend 
and  be  embedded  at  least  15  inches  (381  mm)  into 
the  masonry,  or  be  hooked  or  welded  to  not  less 
than  0.2  square  inches  (129  mm2)  of  bond  beam 
reinforcement  placed  not  less  than  six  inches  (152 
mm)  from  the  top  of  the  wall. 

2111.4  Walls  adjoining  structural  framing:  Walls 
that  are  dependent  upon  the  structural  frame  for 
lateral  support  shall  be  anchored  to  the  structural 
members  with  metal  anchors  or  otherwise  keyed  to 
the  structural  members.  Metal  anchors  shall  consist 
of  14-inch  bolts  spaced  at  four  feet  (1219  mm)  on 
center  embedded  four  inches  (102  mm)  into  the 
masonry,  or  of  other  bolts  of  equivalent  area. 

780  CMR  2112.0  MASONRY 
CONSTRUCTION 

2112.1  Masonry  construction:  Masonry 
construction  shall  comply  with  the  requirements  of 
780  CMR  21 12.1.1  through  2112.5. 

2112.1.1  Tolerances:  Masonry  shall  be 
constructed  within  the  tolerances  specified  in  ACI 
530.1/ASCE  6/TMS  602  listed  in  Appendix  A. 

2112.1.2  Placing  mortar  and  units:  Placement  of 
mortar  and  units  shall  comply  with  780  CMR 
2112.1.2.1  through  21 12. 1.2.4. 

2112.1.2.1  Bed  and  head  joints:  Unless 
otherwise  required  or  indicated  on  the  project 
drawings,  head  and  bed  joints  shall  be  %  inch 
(10  mm)  thick,  except  that  the  thickness  of  the 
bed  joint  of  the  starting  course  placed  over 
foundations  shall  not  be  less  than  %-inch  (6 
mm)  and  not  more  than  3/i-inch  (19  mm). 

2112.1.2.2  Hollow  units:  Hollow  units  shall  be 
placed  such  that  face  shells  of  bed  joints  are 
fully  mortared,  webs  are  fully  mortared  in  all 
courses  of  piers,  column  and  pilasters,  in  the 
starting  course  on  foundations,  where  adjacent 
cells  or  cavities  are  to  be  grouted  and  where 
otherwise  required,  and  head  joints  are 
mortared  a  minimum  distance  from  each  face 
equal  to  the  face  shell  thickness  of  the  unit. 

2112.1.2.3  Solid  units:  Unless  otherwise 
required  or  indicated  on  the  project  drawings, 
solid  units  shall  be  placed  in  fully  mortared  bed 
and  head  joints.  The  ends  of  the  units  shall  be 
completely  buttered.  Head  joints  shall  not  be 
filled  by  slushing  with  mortar  Head  joints 
shall  be  constructed  by  shoving  mortar  tight 


against  the  adjoining  unit.  Bed  joints  shall  not 
be  furrowed  deep  enough  to  produce  voids. 
2112.1.2.4  All  units:  Units  shall  be  placed 
while  the  mortar  is  soft  and  plastic.  Any  unit 
disturbed  to  the  extent  that  the  initial  bond  is 
broken  after  initial  positioning  shall  he 
removed  andrelaid  in  fresh  mortar. 

2112.1.3  Installation  of  wall  ties:  The  ends  of 
wall  ties  shall  be  embedded  in  mortar  joints.  Wall 
tie  ends  shall  engage  outer  face  shells  of  hollow 
units  by  at  least  '/2-inch  (13  mm).  Wire  wall  ties 
shall  be  embedded  at  least  VA  inches  (38  mm) 
into  the  mortar  bed  of  solid  masonry  units  or 
solid-grouted  hollow  units.  Wall  ties  shall  not  be 
bent  after  being  embedded  in  grout  or  mortar. 

2112.1.4  Chases:  Chases  shall  be  constructed  as 
masonry  units  are  laid. 

2112.1.5  Bracing  of  masonry:  Bracing  that  will 
assure  stability  of  masonry  during  construction 
shall  be  provided  and  installed. 

2112.1.6  Construction  loads:  Construction  loads 
shall  not  exceed  the  superimposed  loads  that  the 
masonry,  with  supplemental  supports,  is  capable 
of  supporting  safely. 

2112.1.7  Masonry    protection:    The    top    of 

unfinished  masonry  work  shall  be  covered  to 
protect  the  masonry  from  the  weather 

2112.2  Corbeled  masonry:  Solid  masonry  units 
shall  be  used  for  corbeling.  The  maximum  corbeled 
projection  beyond  the  face  of  the  wall  shall  not  be 
more  than  Vz  of  the  wall  thickness  nor  Vi  the  wythe 
thickness  for  hollow  walls.  The  maximum 
projection  of  one  unit  shall  neither  exceed  Vi  the 
height  of  the  unit  nor  Vs  the  thickness  at  right  angles 
to  the  wall. 

2112.2.1  Molded  cornices:  Unless  structural 
support  and  anchorage  are  provided  to  resist  the 
overturning  moment,  the  center  of  gravity  of  all 
projecting  masonry  or  molded  cornices  shall  lie 
within  the  middle  one-third  of  the  supporting 
wall.  Terra  cotta  and  metal  cornices  shall  be 
provided  with  a  structural  frame  of  approved 
noncombustible  material  anchored  in  an  approved 
manner. 

2112.3  Cold-weather  construction:  The  following 
cold-weather  procedures  shall  be  implemented  when 
either  the  ambient  temperature  falls  below  40°F 
(4°C)  or  the  temperature  of  masonry  units  is  below 
40°F(4°C): 

1.  Temperatures  of  masonry  units  shall  not  be 
less  than  20°F  (-7°C)  when  laid  in  the  masonry. 
Visible  ice  on  masonry  units  shall  be  removed 
before  the  unit  is  laid  in  the  masonry. 

2.  Mortar  sand  or  mixing  water  shall  be  heated  to 
produce  mortar  temperatures  between  40  °F  (4°C) 
and  120°F  (49°C)  at  the  time  of  mixing.  Mortar 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


363 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


shall  be  maintained  above  freezing  until  used  in 
masonry. 

3.  Heat  sources  shall  be  used  where  ambient 
temperatures  are  between  20°F  (-7°C)  and  25 °F 
(-4°C)  on  both  sides  of  the  masonry  under 
construction  and  wind  breaks  shall  be  installed 
when  wind  velocity  is  in  excess  of  15  mph  (6.7 
m/s). 

4.  Where  ambient  temperatures  are  below  20°F 
(-7°C),  an  enclosure  for  the  masonry  under 
construction  shall  be  provided  and  heat  sources 
shall  be  used  to  maintain  temperatures  above 
32 °F  (0°C)  within  the  enclosure. 

5.  Where  mean  daily  temperatures  are  between 
32°F  (0°C),  and  40°F  (4°C),  completed  masonry 
shall  be  protected  from  rain  or  snow  by  covering 
with  a  weather-resistant  membrane  for  24  hours 
after  construction. 

6.  Where  mean  daily  temperatures  are  between 
25°F  (-4°C)  and  32°F  (0°C),  completed  masonry 
shall  be  completely  covered  with  a  weather- 
resistant  membrane  for  24  hours  after 
construction. 

7.  Where  mean  daily  temperatures  are  between 
20°F  (-7°C)  and  25°F  (-4°C),  completed  masonry 
shall  be  completely  covered  with  insulating 
blankets  or  equal  protection  for  24  hours  after 
construction. 

8.  Where  mean  daily  temperatures  are  below 
20°F  (-7°C),  masonry  temperature  shall  be 
maintained  above  32°F  (0°C)  for  24  hours  after 
construction  by  enclosure  with  supplementary 
heat,  by  electric  heating  blankets,  by  infrared  heat 
lamps  or  by  other  approved  methods. 

2112.4  Hot-weather  construction:  The  following 
hot-weather  procedures  shall  be  implemented  when 
either  of  the  following  conditions  exist:  the  ambient 
temperature  equals  or  exceeds  100°F  (38°C)  or  the 
ambient  temperature  equals  or  exceeds  90°F  (32°C) 
with  a  wind  velocity  greater  than  eight  mph  (3.6 
m/s). 

1 .  Mortar  beds  shall  not  be  spread  more  than 
four  feet  (1219  mm)  ahead  of  masonry. 

2.  Masonry  units  shall  be  laid  within  one  minute 
after  mortar  placement. 

2112.5  Wetting  of  brick:  Brick  (clay  or  shale)  at  the 
time  of  laying  shall  require  wetting  if  the  unit's 
initial  rate  of  water  absorption  exceeds  30  grams  per 
30  square  inches  per  minute  (30  g/323  mm2)  or 
0.035  ounces  per  square  inch  (0.0015  g/mm2),  as 
determined  by  ASTM  C67  listed  in  Appendix  A 

780  CMR  21 13.0  MISCELLANEOUS 
REQUIREMENTS 

2113.1  Chases  and  recesses:  Masonry  directly 
above  chases  or  recesses  wider  than  12  inches  (305 
mm)  shall  be  supported  on  lintels. 


2113.2  Lintels:  The  design  for  lintels  shall  be  in 
accordance  with  the  engineered  masonry  design 
provisions  of  780  CMR  2101.1.1.  Minimum  length 
of  end  support  shall  be  four  inches  (102  mm). 

2113.3  Support  on  wood:  Masonry  shall  not  be 
supported  on  wood  girders  or  other  form  of  wood 
construction. 

Exception:  Glass-block  panels  complying  with 
780  CMR  21 15.0  are  permitted  to  be  supported  by 
wood  members. 

780  CMR  2114.0  FIREPLACES  AND 
CHIMNEYS 

2114.1  Scope:  The  provisions  of  780  CMR  2114.0 
shall  govern  the  design,  installation,  maintenance, 
repair  and  approval  of  all  masonry  fireplaces  and 
chimneys. 

2114.2  Mechanical  code:  All  masonry  fireplaces 
and  chimneys  shall  conform  to  the  applicable 
requirements  of  the  BOCA  national  mechanical  code 
listed  in  Appendix  A. 

2114.3  Dimensions:  The  firebox  of  a  masonry 
fireplace  shall  have  a  minimum  depth  of  20  inches 
(508  mm).  The  size  of  the  chimney  connection  shall 
have  a  minimum  cross-sectional  area  of  50  square 
inches  (32258  mm2).  The  minimum  cross-sectional 
area  of  the  fireplace  shall  equal  the  cross-sectional 
area  of  the  chimney  connection. 

2114.3.1  Rumford  fireplaces:  Rumford 
fireplaces  shall  be  permitted  provided  that  the 
depth  of  the  fireplace  is  at  least  12  inches  (305 
mm)  and  is  at  least  Vz  of  the  width  of  the  fireplace 
opening;  and  that  the  throat  is  at  least  12  inches 
(305  mm)  above  the  lintel,  and  is  at  least  l/20th  of 
the  cross-sectional  area  of  the  fireplace  opening. 

2114.4  Wall  construction:  Fireplace  walls  lined 
with  a  minimum  of  two  inches  (51  mm)  of  approved 
low-duty  refractory  brick  shall  have  a  minimum  total 
thickness  of  eight  inches  (203  mm)  of  solid 
masonry.  Approved  medium-duty  fire-clay  mortar 
or  an  equivalent  shall  be  utilized  with  the  low-duty 
refractory  brick.  Unlined  fireplace  walls  shall  be 
constructed  of  solid  masonry  having  a  minimum 
total  thickness  of  12  inches  (305  mm). 

2114.4.1  Extension  of  liners:  The  liner  of  the 
fireplace  walls  shall  extend  a  minimum  of  four 
inches  (102  mm)  into  the  throat  of  the  fireplace. 

2114.4.2  Throat  and  smoke  chamber:  The  walls 
of  the  throat  and  smoke  chamber  shall  be 
constructed  of  solid  masonry  having  a  minimum 
thickness  of  eight  inches  (203  mm).  The  throat 
and  smoke  chamber  walls  are  permitted  to  be 
reduced  in  thickness  to  four  inches  (102  mm)  of 
solid  masonry  provided  that  such  walls  are  lined 
with  at  least  one  inch  (25  mm)  of  insulating 


364 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MASONRY 


refractory  masonry  so  that  the  heat  transferred 
through  this  wall  is  not  more  than  the  heat 
transferred  through  eight  inches  (203  mm)  of  solid 
masonry. 

2114.4.3  Heat  exchanger:  Gravity-fed  heat 
exchangers  installed  in  the  walls  of  masonry 
fireplaces  shall  not  reduce  the  total  thickness  of 
solid  masonry. 

2114.5  Foundation  and  hearth:  The  foundation  of 
a  fireplace  shall  be  constructed  of  noncombustible 
materials  and  shall  conform  to  the  requirements  of 
780  CMR  18.  The  hearth  and  hearth  extension  shall 
be  constructed  of  solid  masonry  having  a  minimum 
thickness  of  four  inches  (102  mm). 

2114.5.1  Hearth  extension:  The  hearth  shall 
extend  a  minimum  of  16  inches  (406  mm)  beyond 
the  face  of  the  fireplace  opening  and  a  minimum 
of  eight  inches  (203  mm)  on  each  side  of  the 
fireplace  opening  for  fireplaces  having  an  opening 
of  less  than  six  square  feet  (0.56  nr).  The  hearth 
of  larger-sized  fireplaces  shall  extend  a  minimum 
of  20  inches  (508  mm)  beyond  the  face  of  the 
fireplace  opening  and  a  minimum  of  12  inches 
(305  mm)  on  each  side  of  the  fireplace  opening. 
Combustible  forms  used  during  construction  of 
the  hearth  and  hearth  extension  shall  be  removed. 

2114.6  Clearance  to  combustibles:  The  exterior 
surface  of  fireplace  walls  shall  have  a  minimum  of 
four  inches  (102  mm)  clearance  to  combustibles. 
Combustible  material,  including  framing  and 
sheathing,  shall  have  a  minimum  clearance  of  two 
inches  (51  mm)  from  the  exterior  surface  of  smoke 
chamber  walls.  Combustible  material  attached  to  a 
fireplace  face,  such  as  trim  and  mantels  shall  have  a 
minimum  clearance  of  six  inches  (152  mm)  from  a 
fireplace  opening.  Combustible  material  above  and 
projecting  more  than  V/z  inches  (38  mm)  from  a 
fireplace  face  shall  have  a  minimum  clearance  of  12 
inches  (305  mm)  above  a  fireplace  opening. 

2114.7  Opening  to  the  chimney:  Means  shall  be 
provided  to  shut  off  the  opening  to  the  chimney 
when  the  fireplace  is  not  in  operation. 

2114.7.1  Dampers:  Dampers  shall  be  constructed 
of  metal  having  a  minimum  thickness  of  No.  12 
Manufacturer's  Standard  Gage  (0.105  inch). 

2114.8  Chimneys  with  metal  hoods:  Metal  hoods 
shall  extend  a  minimum  of  six  inches  (152  mm) 
beyond  the  firebox.  The  hoods  shall  comply  with 
the  requirements  for  metal  chimneys. 

2114.9  Existing  masonry  chimneys:  Existing 
masonry  chimneys  are  permitted  to  vent  open 
fireplaces  only-even  if  the  existing  chimneys  lack 
the  clearances  to  combustibles  as  required  by  the 
BOCA  national  mechanical  code  listed  in 
Appendix    A    -    provided    that    such    chimneys 


otherwise  conform  to  the  requirements  of  the  BOCA 
national  mechanical  code  listed  in  Appendix  A  or  are 
made  to  conform  to  such  requirements  through 
repair  or  relining. 

780  CMR  2115.0  GLASS-BLOCK  WALLS 

2115.1  General:  Masonry  of  glass  blocks  used  in 
nonloadbearing  exterior  or  interior  walls  and  in 
window  openings,  either  isolated  or  in  continuous 
bands,  shall  have  a  minimum  thickness  of  three 
inches  at  the  mortar  joint  and  all  the  mortared 
surfaces  of  the  glass  block  shall  be  treated  for  mortar 
bonding.  Sizes  of  structural  members  supporting 
glass-block  panels  shall  be  determined  by  structural 
analysis  to  avoid  excessive  or  harmful  deflection. 
Maximum  deflection  of  such  members  shall  not 
exceed  1/600  of  the  span  of  the  supporting  members. 

Solid  or  hollow  approved  glass  blocks  shall  not  be 
used  in  fire  walls,  party  walls,  fire  separation 
assemblies  or  fire  partitions,  or  for  loadbearing 
construction.  Such  blocks  shall  be  erected  with 
mortar  and  reinforcement  in  metal-channel-type 
frames,  structural  frames,  masonry  or  concrete 
recesses  or  embedded  panel  anchors  as  provided  for 
both  exterior  and  interior  walls  or  other  approved 
joint  materials.  Wood  strip  framing  shall  not  be 
used  in  fire  separation  assemblies  that  are  required 
to  be  fireresistance  rated. 

Exceptions: 

1.  Glass-block  assemblies  having  a  fireresistance 
rating  of  not  less  than  3A  hour  shall  be  permitted 
as  opening  protectives  in  fire  separation 
assemblies  or  in  fire  partitions  which  have  a 
required  fireresistance  rating  of  1  hour  or  less  and 
do  not  enclose  exit  stairways  or  exit  passageways. 

2.  Glass-block  assemblies  as  permitted  in 
780  CMR  404.5,  Exception  2. 

2115.2  Size  of  panels:  The  maximum  dimensions  of 
all  hollow  glass-block  wall  panels  in  both  exterior 
and  interior  walls,  where  used  singly  or  in  multiples 
to  form  continuous  bands  of  glass  blocks  between 
structural  supports,  shall  be  25  feet  (7620  mm)  in 
length  and  20  feet  (6096  mm)  in  height  between 
structural  supports  and  expansion  joints;  and  the  area 
of  each  individual  panel  shall  not  be  more  than  144 
square  feet  (13.39  nr)  for  exterior  panels  and  250 
square  feet  (23.25  m2)  for  interior  panels. 
Intermediate  structural  supports  shall  be  provided  to 
support  the  dead  load  of  the  wall  and  all  other 
superimposed  loads.  Where  individual  panels  are 
more  than  the  maximum  area  permitted  for  those 
panels,  a  supplementary  structural  stiffener  shall  be 
provided  to  anchor  the  panels  to  the  structural 
supports. 

The  maximum  area  of  all  solid  glass-block  wall 
panels  in  both  exterior  and  interior  walls  shall  not  be 
more  than  100  square  feet  (9  3  nr). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


365 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


21 15.3  Joint  materials:  Glass  block  shall  be  laid  up 
in  Type  S  or  N  mortar.  Both  vertical  and  horizontal 
mortar  joints  shall  be  at  least  lA  inch  (6  mm)  and  not 
more  than  Vi  inch  (13  mm)  thick  and  shall  be 
completely  filled.  The  sills  of  glass-block  panels 
shall  be  coated  with  approved  water-based  asphaltic 
emulsion,  or  other  elastic  waterproofing  material, 
prior  to  laying  the  first  mortar  course.  All 
individually  framed  glass-block  panels  shall  be 
provided  with  3/s-inch-thick  (10  mm)  expansion 
joints  at  the  sides  and  top.  Expansion  joints  shall  be 
entirely  free  of  mortar  and  shall  be  caulked  to  a 
depth  of  not  less  than  V2  inch  (13  mm)  with 
nonhardening  caulking  compound  on  both  faces,  or 
other  approved  expansion  joints  shall  be  provided. 

2115.4  Reinforcement:  Glass-block  panels  shall 
have  joint  reinforcement  in  every  other  mortar  bed 
joint,  extending  the  entire  length  of  the  panel,  but 


not  across  expansion  joints.  Joint  reinforcement  is 
permitted  to  be  spliced  by  lapping  longitudinal  wires 
at  least  six  inches  (152  mm).  Joint  reinforcement 
shall  be  placed  in  the  bed  joint  immediately  below 
and  above  any  opening  in  the  panel.  Joint 
reinforcement  shall  be  hot-dipped  galvanized  after 
fabrication. 

2115.5  Wind  and  earthquake  loads:  Exterior  wall 
panels  shall  be  held  in  place  in  the  wall  opening  to 
resist  both  the  internal  and  external  pressures  due  to 
wind  and  earthquake  loads  as  specified  in  780  CMR 
1611.0  and  1612.0,  with  metal-channel-type  frames, 
structural  frames,  masonry  or  concrete  recesses  or 
embedded  panel  anchors  at  the  sides  and  top.  Where 
recess  type  of  framing  is  used,  glass  block  shall  be 
recessed  within  the  framing  not  less  than  one  inch 
(25  mm). 


366 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  22 


STEEL 


780  CMR  2201.0  GENERAL 

2201.1  Scope:  The  provisions  of  780  CMR  22  shall 
govern  the  materials,  design,  construction  and 
quality  of  structural  steel  members. 

780  CMR  2202.0  DEFINITIONS 
2202.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  22  and  as  used 
elsewhere  in  780  CMR  have  the  meanings  shown 
herein. 

Steel  construction,  cold-formed:  That  type  of 
construction  made  up  entirely,  or  in  part,  of  steel 
structural  members  cold  formed  to  shape  from 
sheet  or  strip  steel  such  as  roof  deck,  floor  and 
wall  panels,  studs,  floor  joists,  roof  joists  and 
other  structural  elements. 

Steel  joist:  Any  steel  structural  member  of  a 
building  or  structure  made  of  hot-rolled  or  cold- 
formed  solid  or  open-web  sections,  or  riveted  or 
welded  bars,  strip  or  sheet  steel  members,  or 
slotted  and  expanded,  or  otherwise  deformed 
rolled  sections 

Steel  member,  structural:  Any  steel  structural 
member  of  a  building  or  structure  consisting  of  a 
rolled  steel  structural  shape  other  than  cold- 
formed  steel,  light-gage  steel  or  steel  joist 
members. 

780  CMR  2203.0  STRUCTURAL  STEEL 
CONSTRUCTION 

2203.1  General:  Structural  steel  construction  used 
in  all  buildings  and  structures  shall  be  fabricated 
from  materials  of  uniform  quality  which  are  free 
from  defects  that  vitiate  the  strength  or  stability  of 
the  structure.  All  structural  steel  shall  be  designed 
and  constructed  in  accordance  with  either  the  AISC 
Specification  for  Structural  Steel  Buildings- 
Allowable  Stress  Design  and  Plastic  Design, 
hereafter  referred  to  AISC  ASD,  or  the  AISC  Load 
and  Resistance  Factor  Design  Specification  for 
Structural  Steel  Buildings,  hereafter  referred  to  as 
AISC  LRFD,  listed  in  Appendix  A,  except  as 
modified  by  the  provisions  of  780  CMR  2204.0. 

2203.2  Structural  steel  seismic  requirements:  The 

design  of  structural  steel  members  and  connections 
to  resist  seismic  forces  shall  be  in  accordance  with 
780  CMR  2203. 1  and  the  AISC  Seismic  Provisions 
for  Structural  Steel  Buildings,  listed  in  Appendix  A, 
except  as  modified  by  780  CMR  2203.2.1  and 
780  CMR  1616. 


2203.2.1  Modifications  to  AISC  seismic 
provisions:  The  AISC  Seis/?iic  Provisions  for 
Structural  Steel  Buildings  shall  be  modified  as 
indicated  in  items  1  through  8. 

1.  In  Part  1,  Section  2.1  of  the  AISC 
Provisions,  replace  the  entire  paragraph  with 
the  following:  "All  buildings  assigned  to 
Category  C  shall  be  designed  in  accordance 
with  these  provisions". 

2.  780  CMR  Table  1612  2.5  shall  be  used  in 
lieu  of  Table  2-1  in  Part  I  of  the  AISC 
Provisions. 

3.  In  Part  1,  Section  3.1,  of  the  AISC 
Provisions,  delete  the  entire  section,  except 
for  Load  Combinations  3-7  and  3-8  and 
replace  with  780  CMR  1616.3.  Replace  load 
combinations  3-  7  and  3-8  as  follows; 

1.3  Dead+1. 0  Floor  Live+0. 7  Snow 
+/-(2R/5)  Seismic  (3-7) 

(0. 9-0.5  AJDead  +/-  (2R/5)  Seismic(3-8) 

The  term  (2R/5)  shall  be  greater  than  or  equal 

to  1.0 

4.  In  Part  I,  Section  6. 1,  of  the  AISC 
Provisions,  replace  equation  6-1  with  the 
following: 

1.3  Dead+1. 0  Live+0.  7  Snow+(2R/5) 
Seismic  <  0cPn  (6-1) 

5.  In  Part  I,  Section  6.1,  of  the  AISC 
Provisions,  replace  equation  6-2  with  the 
following: 

(0.9-  0.5AJ  Dead  -  (2R/5)Seismic 

<  $,Pn  (6-2) 

6.  In  Part  1,  Sections  6. 2,  7.1,  8.1  and  9. 1  of 
the  AISC  Provisions,  replace  all  references  to 
Load  Combinations  3-1  through  3-6  with  the 
following;  "...Load  Combinations  1  through 
8  of  780  CMR  1616.3.1". 

7.  In  Part  1,  Sections  8.3a,  9.4a,  9.4b  and 
10.8,  and  in  Part  II,  Section  7.1  of  the  AISC 
Provisions,  replace  all  references  to  Load 
Combinations  3-5  and  3-6  with  the  following; 
"...Load  Combinations  7  and  8  of  780  CMR 
1616.3.1". 

8.  In  Part  1,  Sections  8. 7b  of  the  AISC 
Provisions  replace  the  reference  to  Load 
Combination  3-5  with  the  follmving;  "...  Load 
Combination  7  of  780  CMR  1616.3. 1 ". 

9.  Special  provisions  for  Welded  Steel 
Moment  Frames:  Recent  experience  has 
shown  that  prequalified,  welded  beam-to- 
column  moment  connections  used  for 
Moment  Resisting  Frames  are  much  more 
susceptible  to  damage  than  originally  thought 
when  the  AISC  Provisions  were  published 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


367 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


The  current  state  of  knowledge  indicates  that 
the  welded  beam-to-column  moment 
connections  depicted  in  the  AISC  Provisions, 
Commentary  Section  8,  do  not  provide  the 
level  of  ductility  required  by  the  Provisions 
for  buildings  that  will  be  subjected  to  repeated 
cycles  of  inelastic  deformation  during  an 
earthquake. 

Welded  beam-to-column  moment 
connections  for  Special  Moment  Resisting 
Frames,  Eccentrically  Braced  Frames  and 
Dual  Systems  with  Special  Moment  Resisting 
Frames  shall  be  designed  in  accordance  with 
780  CMR  2203.2.1,  Item  10. 

Welded  beam-to-column  moment 
connections  for  Ordinary  Moment  Resisting 
Frames  shall  be  designed  in  accordance  with 
780  CMR  2203.2.1,  Item  11. 
1 0.  Design  of  Special  Moment  Resisting 
Frames:  The  design  of  Special  Moment 
Resisting  Frames,  Eccentrically  Braced 
Frames  and  Dual  Systems  with  Special 
Moment  Resisting  Frames  shall  follow  the 
procedures  of  the  Interim  Guidelines: 
Evaluation,  Repair,  Modification  and  Design 
of  Welded  Steel  Moment  Frame  Structures 
(FEMA  267/August,  1995),  except  as  noted 
herein.  Chapter  7  of  this  document  offers 
guidance  for  the  design  of  new  buildings  with 
welded  moment  frames  and  Chapter  8 
addresses  metallurgy  and  welding.  The 
following  exceptions  and  clarifications  shall 
apply  to  FEMA  267/August,  1995. 

1.  All  buildings  with  welded  beam-to- 
column  moment  connections,  including 
light  single  story  buildings,  shall  be 
considered  to  be  susceptible  to  connection 
failure.  The  welded  beam-to-column 
connections  depicted  in  the  AISC  Seismic 
Provisions,  Section  8,  Commentary  shall 
be  prohibited  for  Special  Moment  Resisting 
Frames. 

Exceptions:  Buildings  that  will  remain 
elastic  when  subject  to  dead  and  live 
loads,  together  with  full  seismic  load, 
computed  with  R=l.  An  analysis  that 
demonstrates  that  all  components  of  the 
structure  and  its  connections  have 
adequate  strength  to  resist  these  loads 
shall  be  submitted  and  approved  In 
addition,  the  requirements  of  780  CMR 
2203.2.1,  Item  11,  shall  be  applicable. 

2.  Welded  steel  beam-to-column  moment 
connection  details  used  in  the  design  of 
buildings  with  Special  Moment  Resisting 
Frames  shall  be  sufficiently  verified  by 
tests  of  connections  with  similar  geometry 
and  member  size.  The  example  designs 
shown  in  Section  7.9  of  FEMA  267/August 
1995  shall  not  be  permitted  unless 
adequate      data      showing      acceptable 


performance  has  been  submitted  and 
approved 

3.     The  construction  documents  shall  set 

forth  the  connection  geometry  and  specific 

design  procedures  demonstrating  that  the 

connections  meet  the  design  intent  and 

comply  with  all  requirements  of  780  CMR 

11.     Design  of  Ordinary  Moment  Resisting 

Frames:  Welded  beam-to-column  connections 

depicted  in  the  AISC  Provisions,  Section  8 

Commentary  shall  be  allowed  for  Ordinary 

Moment    Resisting    Frames   provided    the 

following  provisions  are  met: 

1.  Filler  metal  used  in  critical  welds, 
including  all  full  penetration  welds,  in 
beam-to-column  connections  shall  have  a 
minimum  Charpy  V-Notch  value  of  20ft- 
Ibs  at  40  °F  for  fully  enclosed  and  heated 
buildings  and  20  ft-lbs  at  zero  degrees 
Fahrenheit  for  other  buildings  or 
structures. 

2.  Backer  bars  shall  be  removed  at  all 
bottom  flange  welds  made  in  the  down 
hand  position,  and  the  root  pass  shall  be 
back  gouged  and  re-welded  A  reinforcing 
fillet  weld  shall  be  added  at  the  top  and 
bottom  of  bottom  flange  full  penetration 
welds. 

3.  A  reinforcing  fillet  weld  shall  be  added 
at  the  top  of  top  flange  full  penetration 
welds. 

4.  The  construction  documents  shall  set 
forth,  in  sufficient  detail,  the  connection 
geometry  and  specific  design  procedures 
demonstrating  that  the  connections  meet 
the  design  intent  and  comply  with  all 
requirements  of  780  CMR 

2203.3  Temporary  and  special  stresses:  Provision 
shall  be  made  in  the  design  of  structural  steel 
construction  for  temporary  stresses  that  occur  during 
erection,  and  for  the  influence  of  special  loads 
producing  impact  or  vibrations  as  provided  for  in 
780  CMR  1614.0.  Stresses  caused  by  eccentric 
loading  shall  be  fully  provided  for  and  eccentric 
details  shall  be  shown  on  the  design  and  shop 
drawings. 

2203.4  Shop  drawings:  Complete  shop  drawings 
shall  be  prepared  in  compliance  with  the  best 
modem  practice  in  advance  of  the  actual  fabrication. 
Such  drawings  shall  clearly  distinguish  between 
shop  and  field  rivets,  bolts  and  welds  in  all 
connections  and  details. 

2203.5  Painting    and    special    protection:    All 

painting  shall  comply  with  the  requirements 
contained  in  AISC  ASD  or  AISC  LRFD  listed  in 
Appendix:  A.  Where  exposed  to  highly  corrosive 
fumes  or  vapors,  or  where  subject  to  destruction 
from  other  highly  hazardous  industrial  processes,  all 


780  CMR  -  Sixth  Edition 


2/7/97     (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


structural  steelwork  shall  be  protected  by  an 
approved  method. 

780  CMR  2204.0  SEISMIC  REQUIREMENTS 
FOR  STRUCTURAL  STEEL 

2204.1  General:  Steel  structural  elements  that  resist 
seismic  forces  shall  be  designed  in  accordance  with 
the   applicable   provisions   of  780   CMR  2203.0, 

2205.0,  2206.0  and  2207.0 

780  CMR  2205.0  OPEN-WEB  STEEL  JOIST 
CONSTRUCTION 

2205.1  General.  Steel  joists  and  joist  girders  used  as 
structural  members  in  floor  and  roof  construction 
shall  be  designed  and  constructed  in  accordance  with 
SJI  Standard  Specifications,  Load  Tables  and 
Weight  Tables  for  Steel  Joists  and  Joist  Girders 
listed  in  Appendix  A. 

2205.2  Partitions:  The  joists  shall  be  designed  to 
support  the  dead  load  of  partitions,  wherever  they 
occur,  in  addition  to  all  other  imposed  dead  and  live 
loads. 

2205.3  Protection:  Painting  of  steel  joists  shall  be  in 
accordance  with  the  requirements  of  780  CMR 

2206.4  for  formed  steel  construction. 

2205.4  Tests:  Where  not  subject  to  approved 
engineering   analysis   as   regulated  by   780   CMR 

2205.1,  the  assembly  shall  meet  the  load  test 
requirements  specified  in  780  CMR  1709.0  and 
1710.0. 

780  CMR  2206.0  FORMED  STEEL 
CONSTRUCTION 

2206.1  Design:  The  design  of  all  cold-formed 
carbon  and  low-alloy  steel  structural  members  and 
assembled  wall,  floor  and  roof  panels,  used  alone  or 
in  combination  with  other  structural  members,  or 
with  component  materials,  shall  be  in  accordance 
with  the  AISI  Specification  for  the  Design  of  Cold- 
Formed  Steel  Structural  Members,  allowable  stress 
design,  hereafter  referred  to  as  AISI  CFSD-ASD  or 
the  AISI  Load  and  Resistance  Factor  Design 
Specification  for  Cold  -Formed  Steel  Structural 
Members  hereafter  referred  to  as  AISI  CFSD-LRFD, 
listed  in  Appendix  A,  except  as  modified  by  the 
provisions  of  780  CMR  2206.0.  The  design  of  all 
cold-formed  stainless  steel  structural  members  and 
components  shall  be  based  on  a  load  and  resistance 
factor  design  method  or  an  allowable  stress  design 
method  and  maximum  deflections  in  accordance 
with  the  ASCE  Specification  for  the  Design  of  Cold 
Formed  Stainless  Steel  Structural  Members, 
hereafter  referred  to  as  ASCE  8-SSD-LRFD,  or 
ASCE  8-SSD-ASD  listed  in  Appendix  A,  except  as 
modified  by  the  provisions  of  780  CMR  2206.3  and 
2206.3.1. 


STEEL 

2206.1.1  Composite  slabs:  Composite  slabs  of 
concrete  on  steel  deck  shall  be  designed  and 
constructed  in  accordance  with  ASCE  3  listed  in 
Appendix  A. 

2206.2  Secondary  structural  systems:  Formed 
steel  floor,  wall  and  roof  systems  are  permitted  to 
be  designed  and  constructed  to  resist  all  vertical 
and  horizontal  moments  and  shears  resulting  from 
lateral  forces.  Such  members,  where  designed  to 
transmit  horizontal  shears  due  to  wind  or  other 
lateral  forces,  shall  be  connected  to  the  supporting 
structure  so  as  to  resist  adequately  all  primary  and 
secondary  stresses.  Where  concrete  topping  or 
other  approved  decking  is  installed  and  strength 
of  the  composite  member  is  included  in  the 
calculations,  the  concrete  topping  or  decking  shall 
be  installed  in  such  a  manner  as  to  insure 
composite  action  of  the  assembly 

2206.3  Cold-formed  steel  structural  member 
seismic  requirements:  The  AISI  CFSC-LRFD 
and  ASCE  8-SSD-LRFD  listed  in  Appendix  A  for 

the  design  based  on  the  load  and  resistance  factor 
design  method,  and  the  AISI  CFSD-ASD  and 
ASCE  8-SSD-ASD  listed  in  Appendix  A  for  the 
design  based  on  the  allowable  stress  design 
method,  shall  be  modified  as  indicated  in  this 
section.  The  references  to  sections  and  paragraph 
numbers  are  to  those  of  the  particular 
specification  modified. 

1     AISI  CFSD-ASD:  The  nominal  strength  of 

members     and     connections     shall     be     in 

accordance  with  AISI  CFSD-ASD,  except  that 

the    nominal    strength    for    shear    and    web 

crippling  shall  be  determined  by  multiplying 

the  allowable  strength  by  1.7.  Design  strengths 

shall  be  determined  by  multiplying  the  nominal 

strengths  by  the  following  resist  ance  factors: 

Shear  strength  for  h/t  >  (Ekv/Fy),^    ...  0.9 

Shear  strength  for  h/t  <  (Ekv/Fv)  2    ...  1.0 

Web  crippling  for  members  with  single 

unreinforced  webs 0.75 

Web  crippling  for  "I"  sections 0.80 

All  other  cases  ....  1.55/Factor  of  Safety 
The  notation  shall  have  the  same  meaning  as  in 
AISI  CFSD-ASD. 

2.  Load  factors:  Modify  Section  A5.1.4  in 
AISI  CFSD-LRFD  by  substituting  a  load  factor 
of  1.0,  in  place  of  1.5,  for  nominal  earthquake 
loads. 

3.  The  strength  of  stainless  steel  structural 
members  and  connections  subject  to  seismic 
forces  in  combination  with  other  prescribed 
loads  shall  be  determined  by  the  provisions  of 
ASCE  8-SSD-LRFD,  except  that  combinations 
of  load  effects  shall  comply  with  the 
requirements  of  780  CMR  1616.0. 

2206.3.1  Steel  deck  diaphragms:  Steel  deck 
diaphragms  shall  be  made  from  materials 
conforming  to  the  requirements  of  AISI  CFSD- 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


369 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


ASD,  AISI  CFSD-LRFD  or  ASCE  8-SSD-  ASD 
listed  in  Appendix  A.  Nominal  strengths  shall  be 
determined  in  accordance  with  approved  test 
procedures  developed  by  a  registered  design 
professional.  Design  strengths  shall  be  determined 
by  multiplying  the  nominal  strength  by  a 
resistance  factor  of  0.60. 

The  steel  deck  installation  for  the  building, 
including  fasteners,  shall  comply  with  the  test 
assembly  arrangement. 

2206.3.2  Light  gage  steel-framed  walls:  Cold- 
formed  steel  stud  walls  in  buildings  assigned  to 
Seismic  Performance  Category  D  in  accordance 
with  780  CMR  1612.2.7  shall  comply  with 
780  CMR  2206.0  and  the  following  requirements: 

2206.3.2.1  Boundary  members:  All  boundary 
members,  chords  and  collectors  shall  be 
designed  to  transmit  the  induced  axial  force. 

2206.3.2.2  Connections:  Connections  for 
diagonal  bracing  members,  top  chord  splices, 
boundary  members  and  collectors  shall  be 
designed  to  develop  the  tensile  strength  of  the 
member  or,  in  those  cases  where  (2R/5)  is 
equal  to  or  greater  than  1  .0,  (2R/5)  multiplied 
by  the  design  seismic  force,  where  R  is  the 
response  modification  factor  determined  from 
Table  1612.4.4.  The  pull-out  resistance  of 
screws  shall  not  be  used  to  resist  seismic 
forces. 

2206.3.2.3  Braced  bay  members:  Vertical  and 
diagonal  members  in  braced  bays  shall  be 
anchored  such  that  the  bottom  track  is  not 
required  to  resist  uplift  forces  by  bending  of 
the  track  web.  Both  flanges  of  studs  shall  be 
braced  to  prevent  lateral  torsional  buckling. 

2206.4  Protection:  Formed  steel  shall  be  protected 
in  accordance  with  780  CMR  2206.4.1  through 
2206.4.4. 

2206.4.1  Shop  coat:  All  individual  structural 
members  and  assembled  panels  of  light  gage  and 
formed  steel  construction,  except  where  fabricated 
of  approved  corrosion-resistant  metallic  steel  or  of 
steel  having  a  corrosion-resistant  or  other 
approved  coating,  shall  be  protected  against 
corrosion  with  an  approved  shop  coat  of  paint, 
enamel  or  other  approved  protection. 

2206.4.2  Field  coat:  After  erection  where  directly 
exposed  to  the  weather,  except  where  encased  in 
concrete  made  of  non-corrosive  aggregates,  or 
where  fabricated  of  approved  corrosion-resistant 
steel,  or  of  galvanized  or  otherwise  adequately 
protected  steel,  individual  structural  members  and 
assembled  panels  of  light  gage  and  formed  steel 
construction  shall  be  given  an  additional  coat  of 
approved  protection. 

2206.4.3  Siding:  Exposed  siding  or  sheathing 
shall  be  fabricated  of  approved  corrosion-resistant 
steel  or  otherwise  protected  at  the  ground  level  for 


sufficient  height  above  grade  as  determined  by  the 
depth  of  average  snowfall  in  the  locality,  but  not 
less  than  eight  inches  (203  mm). 

2206.4.4  Protection  at  exterior  walls:  Floor  or 
roof  construction  which  extends  into  an  exterior 
wall  shall  be  adequately  waterproofed  and 
protected  from  the  weather  to  prevent  corrosion. 

2206.5  Tests:  Where  not  capable  of  design  by 
approved  engineering  analysis,  the  code  official 
shall  require  tests  of  the  individual  or  assembled 
structural  units  and  the  connections  as  prescribed  in 
780  CMR  1709.0  and  17100.  At  least  three 
specimens  truly  representative  of  the  construction  to 
be  used  in  practice  shall  be  subjected  to  the 
prescribed  test  and  the  mean  of  the  results  shall 
determine  the  safe  working  value;  provided  that  any 
individual  test  varying  more  than  10%  from  the 
mean  value  shall  cause  rejection  of  the  series. 

2206.6  Identification:  Each  structural  member, 
siding  panel  and  roof  panel  of  a  metal  building 
system,  other  than  hardware  items  such  as  bolts. 
nuts,  washers,  shims  and  rivets,  shall  be  identified 
by  the  manufacturer.  The  identification  shall  include 
the  manufacturer's  name  or  logo,  and  the  part 
number  or  part  name  consistent  with  assembly 
instructions. 

780  CMR  2207.0  SPECIAL  STEEL  AND 
STEEL  CABLE  STRUCTURAL  SYSTEMS 

2207.1  Special  steels:  Alloy,  high-carbon  or  other 
special  high-strength  steels  not  covered  in  780  CMR 
22,  where  used  in  the  design  and  construction  of 
buildings  and  structures,  shall  conform  to  780  CMR 
1706.0. 

2207.2  Structural  steel  cable  systems:  The  design, 
fabrication  and  erection  of  steel  cables  used  as 
loadbearing  members  in  buildings  and  structures 
shall  be  in  accordance  with  the  AISI  Criteria  for 
Structural  Applications  of  Steel  Cables  for  Buildings 
listed  in  Appendix  A,  except  as  modified  by  the 
provisions  of  780  CMR  2207.2. 1 . 

2207.2.1  Steel  cable  seismic  requirements:  The 

AISI  Criteria  for  Structural  Applications  of  Steel 
Cables  for  Buildings  listed  in  Appendix  A  shall  be 
modified  as  indicated  in  780  CMR  2207.2.  The 
references  to  sections  are  those  of  the  AISI 
Criteria  for  Structural  Applications  of  Steel 
Cables  for  Buildings  listed  in  Appendix  A. 

1.  Load  combination  "d."  of  Section  5  shall  be 
modified  by  substituting  1.5T,  instead  of 
2.0T4,  where  T4  is  the  net  tension  in  the  cable 
due  to  dead  load,  prestress,  live  load  and 
seismic  load. 

2.  A  load  factor  of  1 . 1  shall  be  applied  to  the 
prestress  forces  to  be  added  to  the  load 
combination  in  Section  3  of  the  steel  cable 
specification. 


370 


780  CMR  -  Sixth  Edition 


2/7/97     (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


STEEL 


3.  The  effective  design  breaking  strength  in 
Section  6  shall  be  multiplied  by  the  following 
resistance  factors: 

Members,  connections  and  base  plates 
that  develop  the  strength  of  the  mem- 
bers of  structural  systems    0.90 

Connections  that  do  not  develop  the 
strength  of  the  member  or  structural 
system,  including  connections  to  base 
plates,  and  anchor  bolts 0.67 

780  CMR  2208.0  CAST-STEEL 
CONSTRUCTION 

2208.1  Materials:  Carbon  steel  casting  for  building 
construction  shall  be  cast  from  steel  conforming  to 
AISC  ASD  or  AISC  LRFD  listed  in  Appendix  A.  All 
castings  shall  be  free  from  injurious  blow  holes  or 
other  defects  which  will  impair  the  structural 
strength. 

2208.2  Higher  strength  cast  steel:  Higher  strength 
cast  steel  shall  not  be  used  unless  approved 

2208.3  Welding  cast  steel:  Cast  steel  designed  for 
use  in  welding  shall  be  of  weldable  grade. 

780  CMR  2209.0  CAST-IRON 
CONSTRUCTION 

2209.1  Materials:  Cast  iron  for  building 
construction  shall  be  a  good  foundry  mixture 
providing  clean,  tough,  gray  iron  that  is  free  from 
serious  blow  holes,  cinder  spots  and  cold  shuts,  and 
that  conforms  to  ASTM  A48  listed  in  Appendix  A 
for  medium  gray-iron  castings. 

2209.2  Limitations  of  use:  Cast-iron  columns  shall 
not  be  used  where  subject  to  eccentric  loads  that 
produce  a  net  tension  in  the  section,  nor  in  any  part 
of  a  structural  frame  that  is  required  to  resist  stress 
due  to  wind.  The  maximum  stresses  for  cast  iron 
shall  be  as  indicated  in  Table  2209.2 

Table  2209.2 
CAST-IRON  STRESSES 


Type  of  stress 

Maximum  stress 

(psi) 

Extreme  compression  (fiber  stress  m 

16,000 

bending) 

Extreme  tension  (fiber  stress  in 

3,000 

bending) 

Column  compression 

9,000  minus  40(//r) 

Shear 

3,000 

Tension 

3.000 

2209.3  Multistory  columns:  Cores  of  superimposed 
columns  shall  be  of  the  same  dimensions  above  and 
below  a  splice.  Where  a  column  of  smaller  diameter 
is  superimposed  over  one  of  larger  diameter,  the 
larger  column  shall  be  tapered  down  to  the  smaller 
diameter  over  a  length  of  not  less  than  six  inches 
(152  mm). 

2209.4  Thickness  of  metal  The  minimum  thickness 
of  cast  iron  shall  not  be  less  than  specified  in 
780  CMR  2209.4.1  through  2209.4.3. 

2209.4.1  Columns  In  columns,  the  metal  shall 
not  be  less  than  one-twelfth  of  the  smallest 
dimension  of  the  cross  section  and  not  less  than  % 
inch  (19  mm). 

2209.4.2  Bases  and  brackets  In  bases  and 
flanges,  the  metal  shall  not  be  less  than  one  inch 
(25  mm)  thick,  and  shall  be  reinforced  with  fillets 
and  brackets. 

2209.4.3  Lintels:  In  lintels,  the  metal  shall  not  be 
less  than  3A  inch  (19  mm)  thick,  and  shall  be 
limited  to  use  on  spans  of  not  more  than  six  feet 
(1829  mm). 

2209.5  Inspection:  A  cast-iron  column  shall  not  be 
erected  in  place  before  such  column  has  been 
inspected  and  approved.  The  use  of  any  cast-iron 
column  in  which  blow  holes  or  imperfections  reduce 
the  effective  area  of  the  cross  section  more  than  10% 
shall  be  prohibited  Where  required  by  the  code 
official,  3/s-inch  (10  mm)  round  inspection  holes 
shall  be  drilled  in  the  section  to  expose  the  thickness 
of  metal  for  inspection  purposes. 

780  CMR  2210.0  EXTERIOR  STEEL  FRAME 

CORROSION  PROTECTION  UNDER 

MASONRY 

2210.1  Required:  Exterior  steel  columns  and 
girders,  before  embedment  in  masonry  of  the 
required  fireresistance  rating  specified  in  Table  602, 
shall  be  protected  from  moisture  by  an  approved 
waterproofing  material,  a  parging  coat  of  cement 
mortar  or  by  a  minimum  of  eight  inches  of  weather- 
tight  masonry 


Ratio  li'r  not  to  exceed  70 


Note  a.  1  psi  =  6.895  kPa 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


371 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


372  780  CMR  -  Sixth  Edition  2/7/97     (Effective  2/28/97) 


CHAPTER  23 


WOOD 


780  CMR  2301.0  GENERAL 
2301.1  Scope:  The  provisions  of  780  CMR  23  shall 
govern    the   materials,    design,    construction    and 
quality  of  wood 

780  CMR  2302.0  DEFINITIONS 
2302.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Native  lumber:  Native  lumber  is  wood  processed  in 
the  Commonwealth  of  Massachusetts  by  a  mill 
registered  in  accordance  with  780  CMR  Such 
wood  may  be  ungraded  but  is  stamped  or 
certified  in  accordance  with  the  requirements  of 
780  CMR  R-4.  Native  lumber  shall  be  restricted 
to  use  in  one-  and  two-story  dwellings,  barns, 
sheds,  agricultural  and  accessory  buildings  and 
other  structures  when  permitted  by  780  CMR 
2303. 

Nominal  dimension  (lumber):  A  dimension  that 
varies  from  actual  dimensions  in  accordance  with 
DOC  PS  20  listed  in  Appendix  A 

Particleboard:  Particleboard  is  a  mat-formed  panel 
consisting  of  particles  of  wood  or  a  combination 
of  wood  particles  and  wood  fibers  bonded 
together  with  synthetic  resins  or  other  suitable 
bonding  systems  (see  780  CMR  2308.0). 

Preservative  treatment  (treated  material):  Unless 
otherwise  noted,  means  impregnation  under 
pressure  with  a  wood  preservative  A  wood 
preservative  is  any  suitable  substance  that  is  toxic 
to  fungi,  insects,  borers  and  other  living  wood- 
destroying  organisms. 

780  CMR  2303.0  PERFORMANCE 
REQUIREMENTS 

2303.1  Structural  design:  All  structural  wood 
members  and  connections  shall  be  of  sufficient  size 
or  capacity  to  carry  all  design  loads  as  required  by 
780  CMR  16  without  exceeding  the  allowable 
design  values  specified  in  AFPA  NDS  listed  in 
Appendix  A  Trusses  and  long-span  girders  shall  be 
designed  with  sufficient  camber,  or  other  provision 
shall  be  made  to  counteract  any  deflection  other  than 
that  permitted  in  780  CMR  1606.5  Design  values 
shall  be  adjusted  for  wood  that  is  pressure 
impregnated  with  fireretardant  chemicals  Such 
adjustment  shall  be  in  accordance  with  780  CMR 
2310.2.1. 


2303.1.1  Identification:  All  lumber  utilized  for 
/oer<i-supporting  purposes,  including  end-jointed 
or  edge-glued  lumber,  shall  be  identified  by  the 
grade  mark  of  an  approved  lumber  grading  or  an 
approved  inspection  agency.  Grading  practices 
and  identification  shall  be  in  accordance  with 
rules  published  by  an  approved  agency  In  lieu  of 
a  grade  mark  on  the  material,  a  certificate  of 
inspection  as  to  species  and  grade  which  is  issued 
by  an  approved  lumber  grading  or  an  approved 
inspection  agency  shall  be  accepted  for  precut, 
remanufactured  or  rough-sawn  lumber,  and  for 
sizes  larger  than  three  inches  nominal  in 
thickness.  Fireretardent-treated  wood  shall  be 
labeled m  accordance  with  780  CMR  2310.2.2 

2303.2  Native  lumber:  Native  lumber,  as  defined  in 
780  CMR  2302.1  shall  be  acceptable  for  use  in  one 
and  two  story  dwellings,  barns,  sheds,  agricultural 
and  accessory  structures.  Native  lumber  shall  also 
be  acceptable  for  use  in  other  one  and  two  story 
structures  as  columns  when  the  design  loads  are 
25%  greater  than  required  elsewhere  by  780  CMR; 
as  joists,  principal  beams,  and  girders  in  floor 
constructions  when  the  design  loads  are  15% 
greater  than  required  elsewhere  by  780  CMR;  and 
as  other  elements  when  the  design  loads  are  as 
required  elsewhere  by  780  CMR 

Each  piece  of  native  lumber  produced  shall  be 
stamped  with  the  name  and  registration  number  of 
the  producer  in  accordance  with  the  780  CMR  In 
addition,  all  native  lumber  shall  bear  an  approved 
mark  identifying  the  species  of  wood  In  lieu  of  the 
stamp  bearing  the  name  and  registration  number 
and  species  identification,  a  certification  bearing 
the  same  information  may  be  provided  by  the 
producer  for  precut  or  re-manufactured  lumber  in 
accordance  with  780  CMR  When  native  lumber  is 
used,  it  shall  be  subject  to  the  following 
requirements: 

1.  Sizing  criteria:  For  lumber,  sized  in 
accordance  with  the  DOC  PS-20-  70,  figures  for 
maximum  fiber  stress  and  modulus  of  elasticity 
for  framing  grade  No.  2  will  be  used  in 
establishing  span  and  spacing  characteristics  for 
all  structural  members. 

2.  Stress  criteria:  Lumber  which  is  sized  in 
excess  of  the  dimensions  established  by  the  DOC 
PS-20-70  for  the  given  nominal  size  referenced 
shall  be  allowed  to  have  a  maximum  fiber  stress 
increase  above  that  provided  in  780  CMR  2303.2 
item  1  in  proportion  to  the  increased  bearing 
capacity  of  the  cross  section  as  provided  in  Table 
2303.2  or  as  calculated 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


373 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  2303.2 
NATIVE  LUMBER  -  ALLOWABLE  STRESSES 


Actual  Lumber  Size 

Factor  to  be  added  to  multiplier 

Closest  size  which  does  not 

factor  for  lumber  oversized  in 

exceed  the  size  shown) 

Multiplier  factor 
based  on  lumber 

thickness 

Nominal  Size 

Actual  Size 

Thickness 

Thickness 

(thickness  x  width) 

width 

increase  of  %"  to 

Vi' 

increase  of  over 
Vi"  to  1" 

,'/i         '/z 

2,'x7 
2  2x8 

1.0  xFs 

3x8 

1  07 

+0.10 

+0.20 

1.14 

Vz         Vi 
2     x  9 

Vz     v. 

2,'x9 

2    x  10 

1.0 

3x  10 

1.05 

+0.10 

+0.20 

1.11 

3x  12 

2AxllA 

Vz      y. 

2   ,x  1 1 

2     xl2 

1.0 

1.04 

+0.10 

+0.20 

1.09 

3x  14 

2    xl3 
2   ,x  13 
2    xl4 

i  0 
1.04 

+0.10 

+0.20 

1.07 

Vz         Vz 

3     x  9 

Vz        % 

3,*x9 
3  2xl0 

1.0 

4x  10 

1.05 

+0.07 

+0.14 

1.11 

JA     ..Vz 
3    ,xll          ■ 

10 

4x  12 

1.04 

+0.07 

+0.14 

3  2xl2 

1.09 

4x  14 

3'/2xl3% 
3    ,xl3 

3  2x  14 

1.0 

1.04 

+0.07 

+0.14 

1.08 

2303..3  Fireresistance  All  wood  structural 
elements  shall  comply  with  Table  602. 

2303.4  Flameresistance  All  wood  surfaces  used  as 
interior  finishes  and  all  exposed  surfaces  as 
described  in  780  CMR  801.1  shall  conform  to  the 
requirements  of  780  CMR  803.0. 

2303.5  Combustibility:  Wood  used  as  structural 
elements  or  portions  thereof  shall  be  limited  to 
combustible  structural  elements  as  required  by 
780  CMR. 

Exceptions: 

1.      Fireretardant-treated  wood  as  permitted  by 

Table  602,  Note  d,  and  which  complies  with 

780  CMR  2310.0. 

2         As  specifically  permitted  by  780  CMR 

602.4.1. 

780  CMR  2304.0  HEAVY  TIMBER 
CONSTRUCTION 

2304.1  Material  grade  and  design:  All  structural 
wood  members,  sawn  or  glued-laminated,  which  are 
installed  in  buildings  and  structures  of  Type  4 
construction  shall  be  stress-grade  timbers  identified 
as  to  grade  and  strength  by  approved  manufacturing, 
testing  or  in  spection  agencies  or  bureaus.     All 


structural  timber  members  shall  have  the  minimum 
dimensions  specified  in  780  CMR  2304.3  through 
2304.6  for  buildings  and  structures  of  Type  4 
construction  and  shall  be  designed,  fabricated  and 
installed  in  accordance  with  AFPA  NDS  and  AITC 
108,  112.  117,  119  and  A190.1  listed  in  Appendix  A 

2304.2  Steel  or  concrete  Structural  steel  or 
reinforced  concrete  members  shall  not  be  substituted 
for  timber  in  any  part  of  the  structural  frame  unless 
protected  to  develop  the  required  fireresistance 
rating  specified  in  Table  602,  but  not  less  than  a  one- 
hour  fireresistance  rating  Structural  members  that 
support  walls  shall  be  protected  to  afford  the  same 
fireresistance  rating  as  the  wall  supported. 

2304.3  Columns:  Wood  columns  shall  be  sawn  or 
glued-laminated  and  shall  not  be  less  than  eight 
inches  nominal  in  any  dimension  where  supporting 
floor  loads;  not  less  than  six  inches  nominal  in 
width,  and  not  less  than  eight  inches  nominal  in 
depth  where  supporting  only  roof  and  ceiling  loads. 
Columns  shall  be  continuous  or  superimposed 
throughout  all  stories  by  means  of  reinforced 
concrete  or  metal  caps  with  brackets,  or  shall  be 
connected  by  properly  designed  steel  or  iron  caps, 
with  pintles  and  base  plates,  or  by  timber  splice 
plates  affixed  to  the  columns  by  means  of  metal 


374 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


connectors  housed  within  the  contact  faces,  or  by 
other  approved  methods.  Girders  or  trusses  which 
support  columns  shall  have  at  least  a  one-hour 
fireresistance  rating. 

2304.4  Floors:  Floors  shall  be  without  concealed 
spaces  and  shall  be  constructed  of  sawn,  glued- 
laminated,  splined  or  tongue-and-groove  planks  not 
less  than  three  inches  nominal  in  thickness  and 
covered  with  a  one-inch  nominal  dimension  tongue- 
and-groove  flooring,  laid  crosswise  or  diagonally,  or 
15/32-inch  wood  structural  panel  or  '/2-inch 
particle  board,  or  of  planks  not  less  than  four  inches 
nominal  in  width  that  are  set  on  edge  close  together 
and  securely  spiked,  and  covered  with  one-inch 
particleboard.  The  lumber  shall  be  laid  so  that  a 
continuous  line  of  joints  will  not  occur  except  at 
points  of  support  and  so  that  planks  are  not  spiked  to 
supporting  girders  that  are  parallel  to  the  lamination 
of  the  floor.  Floors  and  flooring  shall  not  extend 
closer  than  14-inch  (13  mm)  to  walls  so  as  to  provide 
an  expansion  joint.  Such  '/4-inch  (13  mm)  spaces 
shall  be  covered  by  a  molding  fastened  to  the  wall 
either  above  or  below  the  floor  and  arranged  such 
that  the  molding  will  not  obstruct  the  expansion  or 
contraction  movements  of  the  floor,  or,  as  an 
alternative,  corbeling  of  masonry  walls  under  floor 
shall  be  utilized  in  place  of  molding 

2304.4.1  Floor  joists,  beams  and  girders  Joists, 
beams  and  girders  of  wood  shall  be  constructed  of 
sawn  or  glued-laminated  timber  and  shall  not  be 
less  than  six  inches  nominal  in  width,  and  not  less 
than  ten  inches  nominal  in  depth.  Framed  sawn  or 
glued-laminated  timber  arches  that  spring  from 
the  floor  line  and  support  floor  loads  shall  not  be 
less  than  eight  inches  nominal  in  any  dimension. 
Framed  timber  trusses  supporting  floor  loads  shall 
have  members  of  not  less  than  eight  inches 
nominal  in  any  dimension' 

2304.5  Roofs  Roofs  shall  be  without  concealed 
spaces  and  roof  decks  shall  be  constructed  of:  sawn, 
glued-laminated,  splined  or  tongue-and-groove 
planks  not  less  than  two  inches  nominal  in  thickness; 
1  Vs-inch-thick  interior  wood  structural  panel 
(exterior  glue);  or  of  planks  not  less  than  three 
inches  nominal  in  width  that  are  set  on  edge  close 
together  and  laid  as  required  for  floors  in  780  CMR 
2304.4. 

2304.5.1  Arches:  Framed  or  glued-laminated 
arches  for  roof  construction  which  spring  from  the 
floor  line  or  from  grade  and  do  not  support  floor 
loads  shall  have  members  not  less  than  six  inches 
nominal  in  width,  not  less  than  eight  inches 
nominal  in  depth  for  the  lower  half  of  the  height 
and  not  less  than  six  inches  nominal  in  depth  for 
the  upper  half.  Framed  or  glued-laminated  arches 
for  roof  construction  which  spring  from  the  top  of 
walls  or  wall  abutments,  framed  timber  trusses 
and  other  roof  framing  which  does  not  support 


floor  loads  shall  have  members  not  less  than  four 
inches  nominal  in  width  and  not  less  than  six 
inches  nominal  in  depth.  Spaced  members  shall 
be  composed  of  two  or  more  pieces  not  less  than 
three  inches  nominal  in  thickness  where  blocked 
solidly  throughout  their  intervening  spaces  or 
where  such  spaces  are  tightly  closed  by  a 
continuous  wood  cover  plate  of  not  less  than  two 
inches  nominal  in  thickness,  secured  to  the 
underside  of  the  members.  Splice  plates  shall  not 
be  less  than  three  inches  nominal  in  thickness. 
Where  equipped  with  an  automatic  sprinkler 
system  installed  in  accordance  with  780  CMR 
906.2.1,  906.2.2  or  907.0  under  the  roof  deck, 
framing  members  shall  not  be  less  than  three 
inches  nominal  in  width. 

2304.6  Interior  wall  construction:  Walls  shall  be  of 
solid  wood  construction  formed  by  not  less  than  two 
layers  of  one-inch  matched  boards,  laminated 
construction  four  inches  in  thickness,  or  of  one-hour 
fireresistance  rated  construction. 

2304.7  Exterior  structural  members:  Wood 
columns  and  arches  conforming  to  heavy  timber 
sizes  shall  only  be  installed  externally  where  a.  fire 
separation  distance  of  20  feet  (6096  mm)  or  more  is 
provided  WTiere  a  fire  separation  distance  of  less 
than  20  feet  (6096  mm)  is  provided,  columns  and 
arches  shall  be  permitted  where  located  inside  an 
exterior  wall,  and  the  exterior  wall  has  a 
fireresistance  rating  not  less  than  required  by  Table 
602,  for  exterior  walls. 

2304.8  Beams  and  girders:  Beams  and  girder 
supports  and  connections  shall  comply  with 
780  CMR  2305.6.3  and  2305.6.4. 

2304.9  Column  connections:  Girders  and  beams 
shall  be  closely  fitted  around  columns  and  adjoining 
ends  shall  be  cross  tied  to  each  other,  or  inter-tied  by 
caps  or  ties,  to  transfer  horizontal  loads  across  the 
joint.  Wood  bolsters  shall  not  be  placed  on  tops  of 
columns  unless  the  columns  support  roof  loads  only. 

2304.10  Maintenance:  All  connections  in  the  joints 
of  timber  trusses  and  structural  frames  shall  be 
inspected  periodically.  Bolts  and  other  connectors 
shall  be  maintained  tight. 

2304.11  Framing  around  flues  and  chimneys: 

Clearances  for  combustible  framing  members  from 
all  flues,  chimneys  and  fireplaces  shall  be  in 
accordance  with  780  CMR  2305. 12. 

780  CMR  2305.0  WOOD  FRAME 
CONSTRUCTION 

2305.1  Design  and  construction  Exterior  walls, 
interior  partitions,  floors  and  roofs  of  wood 
construction  shall  be  designed  and  constructed  in 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


375 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


accordance  with  780  CMR  2305.0,  780  CMR  2303.0 
and  780  CMR  2307.0  through  23 12.0. 

2305.2  Fastening:  The  quantity  and  size  of  fasteners 
connecting  wood  frame  members  together  and 
sheathing  materials  to  wood  frame  members  shall 
not  be  less  than  that  specified  in  Table  2305.2. 

2305.3  Cutting  and  notching:  It  shall  be  unlawful 
to  notch,  cut  or  pierce  wood  beams,  joists,  rafters  or 
studs  in  excess  of  the  limitations  herein  specified, 
unless  proven  safe  by  structural  analysis  or  suitably 
reinforced  to  transmit  all  calculated  loads. 

2305.3.1  Notches:  Notches  in  joists,  rafters  and 
beams  shall  not  exceed  1/6  of  the  depth  of  the 
member,  shall  not  be  longer  than  Vs  of  the  depth 
of  the  member  and  shall  not  be  located  in  the 


middle  Vb  of  the  span.  Notch  depth  at  the  ends  of 
the  member  shall  not  exceed  Vi  of  the  depth  of  the 
member. 
Exceptions: 

1.  A  notch  over  the  support  is  permitted  to 
extend  the  full  width  of  the  support. 

2.  Notches  on  cantilevered  portions  of  the 
member  are  permitted  to  extend  the  full  length 
of  the  cantilever  if  the  strength  and  deflection 
of  the  cantilever  is  calculated  based  on  the 
reduced  member  section 

3.  The  tension  side  of  beams,  joists  and  rafters 
which  are  four  inches  or  greater  in  nominal 
thickness,  shall  not  be  notched,  except  at  ends 
of  members 


Table  2305.2 
FASTENING  SCHEDULE 


Building  element 


Nail  or  staple  size  and  type 


Number  and  location 


1 .  Floor  construction 

Built  up  to  girders  and  beams 

Bridging  to  joists 

Floor  joists  to  studs  (no  ceiling  joists) 

Floor  joists  to  studs  (with  ceiling  joists) 

Floor  joists  to  sill  or  girder 

Ledger  strip 

1 "  subflooring  (6"  or  less) 

1 "  subflooring  (8"  or  more) 

2"  subflooring 

Particleboard  underiayment  (Vi"  -  %") 
Particleboard  subflooring  (%  or  greater) 
Wood  structural  panel  subflooring 
(Vi"  or  less) 

(19/32"  -Va") 

(%"-r/e) 

(Vi"  or  less) 
(19/32",  s/8") 

2.  Wall  construction 

Smd  to  sole  plate 

Stud  to  cap  plate 

Double  studs 

Corner  studs 

Sole  plate  to  joist  or  blocking 

Interior-braced  wail  sole  plate  to  parallel 

joist 
Double  cap  plate 
Cap  plate  laps 
Ribbon  strip  6"  or  less 
Ribbon  strip  6"  or  more 
Diagonal  brace  (to  stud  and  plate) 


20d  common 
8d  common 
1  Od  common 
1  Od  common 
I  Od  common 
8d  common 
16d  common 
8d  common 
8d  common 
1 6d  common 
6d  annular  threaded 
8d  common 

6d  common  or  6d  annular  or  spiral 

thread 
8d  common  or  6d  annular  or  spiral 

thread 
1  Od  common  or  8d  ring  shank  or 

8d  annular  or  spiral  thread 
16  gage  galvanized  wire  staples 
%"  minimum  crown,  l5/s"  length 


8d  common 
16d  common 
1 6d  common 
lOd  common 
1 6d  common 
16d  common 

16d  common 
lOd  common 
lOd  common 
1  Od  common 
1  Od  common 
8d  common 


32"  o.c.  direct 

2  each  direct  end 
5  direct  or 

3  direct 
2direct 

3  toenail 

.3  each  direct  joist 

2each  direct  joist 

3  each  direct  joist 

2  each  direct  joist 

6"  o.c  direct  edges  and  12"  o.c.  intermediate 

6"  o.c  direct  edges  and  12"  o.c.  intermediate 

6"  o.c  direct  edges  and  12"  o.c.  intermediate 

6"  o.c  direct  edges  and  12"  o.c.  intermediate 

6"  o.c  direct  edges  and  6"  o.c.  intermediate 

4"  o.c.  edges  and  7"  o.c.intermediate 
2/4"  o.c.  edges  and  4"  o.c.  intermediate 


4  toe  nail  or 
2  direct  nail 
2  toe  nail  or  2  direct  nail 

12"  o.c.  direct 
24"  o.c.  direct 
16"  o.c. 

12"  O.c. 

16"  o.c.  direct  nail 

2  direct  nail 

2  each  direct  bearing 

3  each  direct  bearing 
2  each  direct  bearing 


376 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


Building  element 


Nail  or  staple  size  and  type 


Number  and  location 


Interior  -braced  wall  top  plate  to  Joist  or 

blocking 
Tail  beams  to  headers  (where  nailing  is 

permitted) 
Header  beams  to  trimmers  (where 

nailing  is  permitted) 
Continuous  header  to  stud 
Continuous  header,  two  pieces 

3.  Roof  and  ceiling  construction 

Ceiling  joists  to  piate 

Ceiling  joists  (laps  over  partition) 

Ceiling  joists  (parallel  torafler) 

Collar  beam 

Roof  rafter  to  plate 

Roof  rafter  to  ridge 

Jack  rafter  to  hip 

1"  roof  decking  (6"  or  less  in  width) 
1"  roof  decking  (over  6"  in  width) 

4.  Wall  and  roof  sheathing 

I"  wall  sheathing  (8"  or  less  in  width) 

1 "  wall  shfiarhing  (over  8*  in  width) 

Diagonal  wall  sheathing  (seismic 

bracing) 

W  fiberboard  sheathing 


25/32"  fiberboard  sheathing 


Gypsum  sheathing 

Gypsum  sheathing  (seismic  bracing) 

Parricleboard  roof  and  wall  sheathing 

(Vzn  or  less) 

(%"  or  greater} 
Wood  structural  panel  roof  and  wall 

sheathing 

(V2"  or  less) 

(19/32"  or  greater) 

(lA"  or  less) 


(19/32",  %") 
Shingles,  wood 
Weatherboarding 


lOd  common 

20d  common 

20d  common 
8d  common 
1 6d  common 


16d  common 
lOd  common 
Hid  common 
lOd  common 
8d  common 
1 6d  common 
K)d  common 
16d  common 
8d  common 
8d  common 


8d  common 
8d  common 
See  Table  2306.4.5 


12"o.c 

1  each  end  4  sq.  fl.  floor  area 

1  each  end  8  sq.  ft  floor  area 
4  toe  nail 
16"  o  c.  direct 


3  toenail 
3  direct  nail 
3  direct  nail 
3  direct 
3  toe  nail 

2  toe  nail  or  direct  nail 

3  toe  nail  or 
2  direct  nail 

2  each  direct  rafter 

3  each  direct  rafter 


2  each  direct  stud 

3  each  direct  stud 


1 V2"  galvanized  roofing  nail  or  6d      3"  o.c.  exterior  edge.  6"  o.c.  intermediate 

common  nail  or  16  gage  staple, 

1  W  long  with  minimum  crown 

of  7/1 6" 
l3A"  galvanized  roofing  nail  or  8d      3"  o.c.  exterior  edge,  6"  o.c.  intermediate 

common  nail  or  16  gage  staple, 

1  Vz  long  with  nunimum  crown 

of  7/1 6" 
12  gage  1%"  large  head  corrosion      4"  °c-  on  edge,  8"  o.c.  intermediate 

resistant 
1 1  gage  1 %"  long  7/16"  head  4"  oc  a11  beannS  Pomts 

diamond  point,  galvanized 


6d  common 
8d  common 


6d  common 
8d  common 

16  gage  galvanized  wire  staples, 
%"  rmnrnrum  crown;  length  of 
I*  phis  panel  thickness 

Same  as  immediately  above 

No.  14  B&S  Gage  corrosion 
resistant 

8d  corrosion  resistant 


6"  o.c.  direct  edges  and  1 2"  o.c.  intermediate 
6*  o.c.  direct  edges  and  12"  o.c.  intermediate 


6"  o.c.  direct  edges  and  12"  o.c.  intermediate 
6"  o.c.  direct  edges  and  12"  oc.  intermedite 

4"  o.c.  edges  and  8°  o.c.  intermediate 


2'/2"  o.c.  edges  and  5"  o.c.  intermediate 
2  each  bearing 
2  each  bearing 


Note  a    Single  nails  shall  penetrate  not  less 
as  otherwise  provided  for  in  780  CMR  1507 


than  V*  inch  into  nailing  strips,  sheathing  or  supporting  construction  except 
0 


2305.3.2  Holes:  Holes  bored  or  cut  into  joists, 
rafters  or  beams  shall  not  be  closer  than  two 
inches  (51  mm)  to  the  top  or  bottom  of  the  joist, 
or  to  any  other  hole  located  in  the  member. 
Where  the  member  is  notched,  the  hole  shall  not 
be  closer  than  two  inches  (5 1  mm)  to  the  notch. 


The  diameter  of  the  hole  in  joists  shall  not  exceed 
1/3  of  the  depth  of  the  member 

2305.3.3  Studs:  In  studs  of  loadbearing  walls  or 
partitions,  notches  or  bored  holes  shall  not  be  cut 
or  bored  more  than  Vs  of  the  depth  of  the  stud 
unless  reinforced  in  accordance  with  780  CMR 
2305.3.4. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


377 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2305.3.4  Reinforcement:  Where  the  stud  is  cut  or 
bored  in  excess  of  Vb  of  its  depth,  the  stud  shall  be 
reinforced  to  be  equal  in  loadbearing  capacity  to 
a  stud  that  is  notched  not  more  than  Vb  of  its 
depth. 

2305.4  Loadbearing  walls:  Posts  and  studs  in 
loadbearing  walls  and  partitions  shall  be  designed  as 
columns,  with  due  allowance  for  lateral  support 
furnished  by  sheathing,  intermediate  bracing, 
horizontal  bridging,  wall  coverings  and  the  floor  and 
roof  assemblies.  The  walls  shall  be  fabricated  in 
such  a  manner  as  to  provide  adequate  support  for  the 
materials  that  enclose  the  building  and  to  provide  for 
transfer  of  all  lateral  loads  to  the  foundation  in 
accordance  with  780  CMR  1710.4. 

2305.4.1  Wall  framing:  Studs  shall  be  placed 
with  the  wide  dimension  perpendicular  to  the 
wall.  Not  less  than  three  studs  shall  be  installed 
at  each  corner  of  an  exterior  wall 

Exception:  At  corners,  a  third  stud  is  not 
required  where  wood  spacers  or  backup  cleats 
of  3/8-inch-thick  wood  structural  panel,  3/e-inch 
Type  2-M  particleboard,  one-inch-thick 
lumber  or  other  approved  devices  which  serve 
as  an  adequate  backing  for  the  attachment  of 
facing  materials  are  used.  Where  fireresistance 
ratings  or  shear  loads  apply,  wood  spacers, 
backup  cleats  or  other  devices  shall  not  be 
installed  unless  specifically  approved. 

2305.4.2  Double  top  plates:  Stud  walls  shall  be 
capped  with  double  top  plates  installed  to  provide 
overlapping  corners  and  wall  intersections.  Top 
plate  joints  shall  be  offset  not  less  than  48  inches 
(1219  mm). 

Exception:  Detached  one-  and  two-family 
dwellings  and  agricultural  storage  buildings 
that  are  intended  only  for  incidental  human 
occupancy  are  permitted  to  have  a  single  top 
plate  provided  that  the  plate  is  adequately  tied 
at  joints,  corners  and  intersecting  walls  by  at 
least  the  equivalent  of  galvanized  steel  that  is 
three  inches  (76  mm)  by  six  inches  (152  mm) 
by  0. 036  inches  thick  and  nailed  to  each  wall 
or  segment  of  wall  by  three  8d  nails  or  the 
equivalent,  and  the  rafters,  joists  or  trusses 
are  centered  over  the  studs  with  a  tolerance  of 
not  more  than  one  inch  (25  mm). 

2305.4.3  Bottom  plates:  Studs  shall  have  full 
support  by  a  plate  or  sill.  The  sill  shall  have  not 
less  than  a  two-inch  nominal  thickness  and  a 
width  at  least  equal  to  the  width  of  the  studs. 

2305.5  Nonloadbearing  walls:  Studs  in 
nonloadbearing  walls  and  partitions  shall  not  be 
spaced  more  than  48  inches  (1219  mm)  o.c,  and  are 
permitted  to  be  erected  with  the  long  dimension 
parallel  to  the  wall,  unless  otherwise  approved  as  an 
integrated  assembly  by  testing.    A  single  top  plate 


shall  be  prohibited  except  where  such  plate  is 
installed  in  accordance  with  780  CMR  2305.4.2. 

2305.6  Support  and  anchorage:  Support  and 
anchorage  of  members  on  girders,  walls  and  beams 
shall  conform  to  780  CMR  2305.6.1  through 
2305.64. 

2305.6.1  Support  and  anchorage  on  girders:  All 

members  framing  into  girders  shall  be  anchored  or 
tied  to  secure  continuity.  The  ends  of  all  wood 
beams  that  rest  on  girders  shall  bear  not  less  than 
four  inches  (102  mm)  or  shall  be  supported  in 
approved  metal  stirrups,  hangers  or  on  wood  clips 
or  ribbon  strips.  Beams  framing  from  opposite 
sides  shall  either  lap  at  least  six  inches  (152  mm) 
and  be  bolted  or  spiked  together  or,  where  framed 
end-to-end,  the  beams  shall  be  secured  together 
by  approved  ties,  straps,  dogs,  plates  or  sheathing. 

2305.6.2  Support  and  anchorage  on  walls  or 
beams:  Except  where  supported  on  a  1  x  4  ribbon 
strip  and  nailed  to  the  adjoining  stud,  joists  shall 
bear  on  walls  or  beams  of  wood  or  steel  not  less 
than  l'/i  inches  (38  mm)  or  shall  be  supported  by 
metal  stirrups,  hangers  or  a  nominal  2-inch  wood 
ledger  strip.  The  minimum  bearing  on  concrete 
or  masonry  shall  be  three  inches  (76  mm).  Joists 
framing  over  beams  from  opposite  sides  shall 
either  lap  at  least  three  inches  (76  mm)  and  be 
securely  fastened  together  or,  where  framed  end- 
to-end,  the  joists  shall  be  secured  together  by 
approved  ties,  straps,  dogs,  plates  or  sheathing. 

2305.6.3  Girder  supports:  Wall  plate  boxes  of 
the  self-releasing  type,  or  approved  hangers,  shall 
be  provided  where  beams  and  girders  are 
supported  by  masonry.  An  air  space  of  Vz  inch 
(13  mm)  shall  be  provided  at  the  top,  end  and 
sides  of  the  member  unless  approved  naturally 
durable  or  preservative-treated  wood  in 
accordance  with  780  CMR  2311.0  is  installed. 
Wood  beams  and  girders  supported  by  walls 
required  to  have  a  fireresistance  rating  of  two 
hours  or  more  shall  have  not  less  than  four  inches 
(102  mm)  of  solid  masonry  between  their  ends 
and  the  outside  face  of  the  wall  and  between 
adjacent  beams. 

2305.6.4  Fire  cuts:  All  wood  and  other 
combustible  floor,  roof  and  other  structural 
members  framing  into  masonry  walls  shall  be  cut 
to  a  bevel  of  three  inches  (76  mm)  in  depth  and 
shall  project  not  more  than  four  inches  ( 1 02  mm) 
into  the  wall. 

2305.7  Wind  bracing  In  buildings  more  than  one 
story  in  height  and  where  necessary  for  strength  in 
one-story  buildings,  the  comer  posts  shall  be  the 
equivalent  of  not  less  than  two  pieces  of  two-inch  by 
four-inch  studs,  braced  by  not  less  than  one  piece  of 
one-inch  by  four-inch  continuous-diagonal  brace  let 
into  the  studs.      Bracing  is  not   required  where 


378 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BLTLDrNG  REGULATIONS  AND  STANDARDS 


WOOD 


diagonal  wood  sheathing,  wood  structural  panels  or 
particleboard  panels  are  installed,  or  where  other 
sheathing  as  specified  in  780  CMR  2305.13  is 
applied  vertically  in  panels  of  not  less  than  four  feet 
by  eight  feet  with  approved  fasteners  complying 
with  Table  2305.2.  Other  sheathing  materials  shall 
be  permitted  when  tested  in  accordance  with  ASTM 
E72  listed  in  Appendix  A. 

The  lateral  load  resistance  shall  be  established  by 
the  lesser  of:  the  values  determined  by  dividing  the 
maximum  load  reported  in  the  test  by  2.5;  or  the 
load  at  which  the  deflection  reported  in  the  test 
exceeds  /j/480,  where  h  is  the  height  of  the  test 
assembly. 

2305.8  Seismic  bracing:  Where  structural  analysis 
of  the  seismic  force-resisting  system  is  not  provided, 
buildings  shall  meet  the  provisions  of  780  CMR 
2305.0  and  shall  have  roof  and  exterior  wall  dead 
loads  less  than  or  equal  to  1 5  psf  (73  kg/m2)  and 
floor  dead  loads  less  than  or  equal  to  10  psf  (49 
kg/m2). 

Table  2305.8 

WALL  SPACING  AND  HEIGHT 

LIMITATIONS  FOR  WOOD  AND  FRAME 

CONTRUCTION 


Seismic  Performance 
Category 

Maximum  distance 

between  interior 
bracing  walls  (feet) 

Maximum  Stories 
(height)  permitted 

C 

25 

2  (30  feet) 

Da 

25 

1  (20  feet  i 

Note  a:  Applies  only  to  Seismic  Hazard  Exposure  Group 
I;  engineering  analysis  required  for  Seismic  Hazard 
Exposure  Group  II 

2305.8.1  Wall  bracing  required:  All  exterior 
walls  and  required  interior  bracing  walls  shall  be 
braced  by  one  of  the  types  of  sheathing  prescrided 
in  table  2305.8. 1  for  each  25  lineal  feet  (or  7.6  m) 
of  exterior  wall  or  required  interior  bracing  wall 
length.  The  required  length  of  sheathing  shall  be 
distributed  along  the  length  of  the  bracing  wall 
with  a  minimum  four  foot  panel  of  sheathing  at, 
or  within  four  feet  of,  each  end.  Construction  of 
bracing  walls  shall  comply  with  the  requirements 
of  780  CMR  2305.9 

Table  2305.8.1 

MINIMUM  SEISMIC  WALL  BRACING  PER 

25  LINEAL  FEET  OF  INTERIOR  AND 

EXTERIOR  WALL  LENGTH30 


Story  location 

Sheathing 

Av  =  0.12 

Top  or  only 
story 

GP 

W/GP 

7>-0" 

4'-0" 

First  of  two 
stories 

GP 

W/GP 

13'-0" 
7'-0" 

Note  a.    Interpolation  of  the  tabular  values  is  permitted 
where   the   length   of  wall   between   exterior  walls   or 
interior-braced  walls  is  less  than  25  feet. 
Note  b.  GP  =  Gypsum  or  particleboard  sheathing;  W/SP 
=  Diagonal  wood  boards  or  wood  structural  panels. 
Note  c.  One  foot  =  304.8  mm. 

2305.8.2  Double-sheathed  walls:  Where  braced 
walls  are  sheathed  on  both  sides  with  identical 
sheathing,  the  required  length  of  sheathing  in 
Table  2305.8. 1  is  permitted  to  be  taken  as  Vi  the 
tabular  length.  Where  different  sheathing 
materials  are  used  on  either  side  of  a  wall,  the 
required  length  of  sheathing  in  Table  2305.8.1  is 
permitted  to  be  taken  as  Vz  of  the  tabular  length 
for  the  material  requiring  the  greater  length. 
Double-sheathed  walls  shall  have  a  minimum 
length  of  four  feet  (1219  mm). 

2305.8.3  Stud  walls:  Stud  walls  that  are  less  than 
the  full  height  of  the  story  shall  be  braced  as 
required  for  exterior  walls  or  interior-braced 
walls  and  shall  be  considered  an  additional  story. 

2305.8.4  Sheathing  installation:  Sheathing  shall 
be  installed  in  accordance  with  the  provisions  of 
Table  2305.13  where  acting  as  wall  bracing.  To 
be  considered  effective  as  bracing,  the  sheathing 
shall  be  at  least  48  inches  in  width  covering  three 
16-inch  stud  spaces  or  two  24-inch  stud  spaces 
and  be  fastened  to  the  wall  studs  in  accordance 
with  Table  2305.2.  Sheathing  shall  be  fastened  to 
the  wall  studs,  sole  plate  and  top  plate  in 
accordance  with  Table  2305.2.  All  vertical  joints 
of  panel  sheathing  shall  occur  over  studs  and  all 
horizontal  joints  shall  occur  over  blocking  at  least 
equal  in  size  to  the  studs.  All  framing  in 
connection  with  sheathing  used  for  bracing  shall 
not  be  less  than  two  inches  nominal  in  thickness. 

2305.9  Braced  wall:  All  exterior  walls  and  interior- 
braced  walls  required  by  Table  2305.8,  shall  be 
constructed  to  transfer  forces  from  roofs  and  floors 
to  braced  walls  and  from  the  braced  walls  in  upper 
stories  to  the  braced  walls  in  the  story  below. 
Braced  wall  lines  from  the  story  above  to  the  story 
below  are  permitted  to  be  offset  a  maximum  of  24 
inches  (610  mm).  Blocking,  where  required  by 
780  CMR  2305.9,  need  only  be  provided  for  the 
length  of  the  wall  specified  in  Table  2305.8.1. 

2305.9.1  Roof  to  braced  wall  connections:  Roof 
to  interior-braced  wall  connections  for  buildings 
with  maximum  dimensions  not  over  50  feet 
(15240  mm)  are  permitted  to  be  made  at  the 
intersection  of  exterior  walls.  Double  top  plates 
shall  be  lapped  at  the  intersection  and  nailed  in 
accordance  with  Table  2305.2.  For  buildings  with 
maximum  dimensions  greater  than  50  feet  (15240 
mm),  the  interior-braced  walls  shall  be  fastened 
directly  to  the  ceiling  joist  in  accordance  with 
780  CMR  2305.9.2  or  2305.9.3. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


379 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2305.9.2  Parallel  floor  joist  and  braced  wall 
connections:  Where  the  floor  framing  is  parallel 
to  the  braced  wall  line,  joists  shall  be  doubled 
directly  beneath  the  braced  wall  line  and  nailed  in 
accordance  with  Table  2305.2. 

Where  the  upper  and  lower  braced  walls  are 
offset,  the  joist  spaces  between  the  offset  braced 
walls  shall  be  blocked  with  a  minimum  blocking 
size  of  two  inches  by  six  inches,  spaced  at  32 
inches  (813  mm)  on  center,  within  the  joist  cavity 
under  the  braced  wall,  and  positioned  in  the  upper 
portion  of  the  cavity.  The  upper  braced  wall  is 
permitted  to  be  nailed  to  the  blocking  with  two 
16d  nails  at  each  piece  of  blocking.  The  lower 
braced  wall  shall  be  toe  nailed,  in  accordance  with 
Table  2305.2,  to  a  joist  located  directly  above  the 
top  plates. 

2305.9.3  Perpendicular  floor  joist  and  braced 
wall  connections:  Where  the  floor  framing  is 
perpendicular  to  the  braced  wall  line,  solid 
blocking  for  the  full  depth  of  the  floor  joist  shall 
be  provided  for  the  length  of  bracing  required. 
The  interior-braced  wall  shall  be  nailed  to  the 
blocking  in  accordance  with  Table  2305.2. 

Where  the  upper  and  lower  braced  walls  are 
offset,  a  minimum  of  two-inch  by  six-inch 
blocking  shall  be  located  in  the  upper  portion  of 
the  joist  space,  directly  beneath  the  upper  braced 
wall  and  in  the  lower  portion  of  the  joist  space, 
directly  above  the  lower  braced  wall. 

2305.10  Multiple  stories:  Where  the  frame  is  more 
than  one  story  in  height  and  studs  and  posts  are  not 
continuous  from  sill  to  roof,  the  members  shall  be 
secured  together  with  approved  clips,  splices  or 
other  connections  to  insure  a  continuous,  well- 
integrated  structure.  Sheet  metal  clamps,  ties  or 
clips  shall  be  formed  of  galvanized  steel  or  other 
approved  corrosion-resistant  material  equivalent  to 
0.040-inch  nominal  thickness  steel  sheets  for  two- 
inch  framing  members  and  not  less  than  0.052-inch 
nominal  thickness  steel  sheets  for  three-inch 
structural  members.  For  four-inch  and  larger 
members,  column  splices  and  beam  and  girder 
supports  shall  comply  with  780  CMR  2304. 1 . 

2305.11  Framing  over  openings:  Headers,  double 
joists,  trusses  or  other  approved  assemblies  which 
are  of  adequate  size  to  transfer  all  superimposed 
loads  to  the  vertical  members  shall  be  provided  over 
all  window  and  door  openings  in  loadbearing  walls 
and  partitions. 

2305.12  Framing  around  flues  and  chimneys: 

Combustible  framing  shall  be  a  minimum  of  two 
inches  (51  mm),  but  shall  not  be  less  than  the 
distance  specified  in  780  CMR  2114.0  and  the 
mechanical  code  listed  in  Appendix  A,  from  all 
flues,  chimneys  and  fireplaces,  and  six  inches  (152 
mm)  away  from  flue  openings. 


2305.13  Wall  sheathing:  Except  as  provided  for  in 
780  CMR  1405.3  for  weatherboarding  or  where 
stucco  construction  that  complies  with  780  CMR 
2506.0  is  installed,  all  enclosed  buildings  shall  be 
sheathed  with  one  of  the  materials  of  the  nominal 
thickness  specified  in  Table  2305.13  or  any  other 
approved  material  of  equivalent  strength  and 
durability. 

Table  2305.13 

MINIMUM  THICKNESS  OF  WALL 

SHEATHING 


Sheathing  type 

Minimum 
thickness 

Maximum  shear 
wall  stud  spacing' 

Wood  boards 

%  inch 

24  inches  on  center 

Fiberboard 

7/16  inch 

1 6  inches  on  center 

Wood  structural  panel 

In  accordance  with  Table  2307.3.5 

2-M-lor2-M-W 
Particleboard 

In  accordance  with  Table  2308.5(2) 

Gypsum  sheathing 

Vi  inch 

1 6  inches  on  center 

Gypsum  wallboard 

Vi  inch 

24  inches  on  center 

Reinforced  cement 
mortar 

1  inch 

24  inches  on  center 

Note  a.  1  inch  =  25.4  mm. 

2305.13.1  Wood  structural  panel  wall  bracing: 

In  buildings  assigned  to  Seismic  Performance 
Category  D,  where  wood  structural  panel 
sheathing  is  installed  structurally  as  covering  on 
the  exterior  of  outside  walls,  such  sheathing  shall 
be  of  the  exterior  type.  Where  used  elsewhere 
structurally,  wood  structural  panel  sheathing  shall 
be  bonded  by  intermediate  or  exterior  glue. 

2305.13.2  Paper-backed   lath   sheathing:    In 

occupancies  in  Use  Group  R-3  and  one-story 
commercial  buildings  with  brick  or  similar 
veneers,  the  sheathing  shall  conform  to  780  CMR 
2305.13  or  shall  consist  of  a  layer  of  paper- 
backed lath  complying  with  780  CMR  2505.0  and 
a  one-inch  (25  mm)  intermediate  space  which 
shall  be  mortar  filled  as  each  course  of  veneering 
is  applied. 

2305.14  Flooring:  The  flooring  of  wood  frame 
construction  shall  be  of  adequate  strength  and 
stiffness  to  support  required  loads  and,  where 
necessary  for  strength  and  for  lateral  support  of  the 
building,  subflooring  shall  be  provided. 

2305.14.1  Floor  spans:  Design  stresses  of  floor 
joists  shall  be  determined  in  accordance  with 
AFPA  NDS  listed  in  Appendix  A.  Metal-plate- 
connected  floor  trusses  shall  be  designed  in 
accordance  with  TPI  Design  Specifications  for 
Metal  Plate  Connected  Parallel  Chord  Wood 
Trusses  and  AFPA  NDS  listed  in  Appendix  A. 


380 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


2305.14.2  Bridging:  In  all  floor,  attic  and  roof 
framing,  except  as  hereafter  noted,  there  shall  not 
be  less  than  one  line  of  bridging  for  each  eight 
feet  (  or  2450  mm)  of  span.  The  bridging  shall 
consist  of  not  less  than  one-inch  by  three-inch 
lumber,  double  nailed  at  each  end,  or  of 
equivalent  metal  bracing  of  equal  rigidity.  A  line 
of  bridging  shall  also  be  required  at  supports 
where  adequate  lateral  support  is  not  otherwise 
provided.  Midspan  bridging  is  not  required  for 
floor,  attic  or  roof  framing  in  occupancies  in  Use 
Groups  R-2  and  R-3,  except  where  the  joist  depth 
exceeds  12  inches  nominal  or  where  the  minimum 
uniformly  distributed  live  load  exceeds  40  psf 
(195  kg/m2). 

2305.15  Roof  spans:  Design  stresses  of  rafters  shall 
be  determined  in  accordance  with  AFPA  NDS  listed 
in  Appendix  A.  Metal-plate-connected  roof  trusses 
shall  be  designed  in  accordance  with  TPI  Design 
Specifications  for  Metal  Plate  Connected  Wood 
Trusses  and  AFPA  NDS  listed  in  Appendix  A,  and 
shall  be  braced  to  prevent  rotation  and  provide 
lateral  stability. 

2305.15.1  Roof  decking  and  sheathing:  Roof 
deck  sheathing  shall  consist  of  not  less  than  5/s- 
inch  boards,  wood  structural  panel  of  the 
thickness  specified  in  780  CMR  2307.3, 
particleboard  of 'the  grade  and  thickness  specified 
in  780  CMR  2308.4,  or  other  approved  materials 
of  equivalent  strength  and  rigidity.  Where  open 
deck  sheathing  is  used  on  pitched  roofs,  such 
sheathing  shall  consist  of  not  less  than  one-inch 
by  four-inch  roofers  spaced  not  more  than  six 
inches  (152  mm)  on  center,  or  of  material  of 
equivalent  strength  and  rigidity. 

2305.16  Foundation  anchorage:  Wall  sill  plates, 
minimum  of  two-inch  by  four-inch  members,  shall 
be  sized  and  anchored  to  foundation  walls  or  piers 
and  at  intermediate  intervals  as  required  to  resist 
wind  uplift.  Foundation  anchorage  shall  be  provided 
by  the  installation  of  anchor  bolts  or  other  approved 
anchoring  method.  Anchor  bolts  shall  be  of  a 
minimum  diameter  of  'A  inch.  The  bolts  shall  be 
embedded  in  foundations  to  a  depth  of  not  less  than 
eight  inches  (203  mm)  of  cast-in-place  concrete,  and 
not  less  than  15  inches  (381  mm)  in  grouted  unit 
masonry.  There  shall  be  a  minimum  of  two  anchor 
bolts  per  section  of  plate  and  anchor  bolts  shall  be 
placed  12  inches  (305  mm)  from  the  end  of  each 
section  of  plate,  with  intermediate  bolts  spaced  a 
maximum  of  six  feet  (1829  mm)  on  center  for  one- 
and  two-story  buildings  and  not  more  than  four  feet 
(12  1 9  mm )  on  center  for  buildings  over  two  stories 
in  height. 

Exception:  Agricultural  storage  buildings  which 
are  intended  only  for  incidental  human 
occupancy,   are  permitted  to  have  maximum 


intermediate  bolt  spacings  of  eight  feet  (or  2450 
mm). 

2305.17  Fire  cuts:  All  wood  structural  members 
which  frame  into  masonry  walls  shall  conform  to 
780  CMR  2305.6.4. 

780  CMR  2306.0  SEISMIC  REQUIREMENTS 
FOR  WOOD  AND  TIMBER 

2306.1  General:  All  buildings  for  which  a  seismic 
analysis  is  required,  in  accordance  with  780  CMR 
1612.2,  and  which  are  constructed  partially  or 
wholly  of  wood  or  wood-based  materials  shall  be 
designed  in  accordance  with  the  provisions  of 
780  CMR  2306.0  and  780  CMR  2305.0. 

2306.2  Definitions:  The  following  words  and  terms 
shall  apply  to  the  provisions  of  780  CMR  2306.0  and 
have  the  following  meanings: 

Blocked  diaphragm:  A  diaphragm  in  which  all 
sheathing  edges  not  occurring  on  a  framing 
member  are  supported  on  and  connected  to 
blocking. 

Diaphragm:  A  horizontal  or  nearly  horizontal 
system  designed  to  transmit  lateral  forces  to  the 
vertical  elements  of  the  seismic-resisting  system. 

Wood  shear  panel:  A  wood  floor,  roof  or  wall 
component  sheathed  to  act  as  a  shear  wall  or 
diaphragm. 

2306.3  Strength  of  members  and  connections:  The 

allowable  load  capacities  of  780  CMR  2306.0  are  to 
be  utilized  with  allowable  stress  design  load 
combinations. 

2306.4  Engineered  timber  construction:  Where 
seismic  analysis  is  required  in  accordance  with 
780  CMR  1612.2,  the  proportioning  and  design  of 
wood  systems,  members  and  connections  shall  be  in 
accordance  with  780  CMR  2306.4  and  AFPA  NDS 
listed  in  Appendix  A. 

2306.4.1  Column  framing  requirements:  All 

wood  columns  shall  be  provided  with  full  end 
support.  Columns  shall  be  provided  with 
adequate  support  to  maintain  stability.  Positive 
connections  shall  be  provided  to  resist  uplift  and 
lateral  displacement. 

2306.4.2  Wood  shear  panels:  Wood  shear  panels 
shall  comply  with  780  CMR  2306.4.2.1  through 
2306.4.2.6.  Diaphragm  construction  shall 
comply  with  780  CMR  2306.4.3.  Shear  wall 
construction  shall  comply  with  780  CMR 
2306.4.4.  The  construction  of  wood  shear  panels 
shall  comply  with  780  CMR  2306.4  5  for 
diagonally  sheathed  lumber  shear  panels, 
780  CMR  2306.4.6  for  wood  structural  panel 
sheathed  shear  panels,  780  CMR  2306.4.7  for 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


381 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


particleboard  sheathed  shear  panels,  or  780  CMR 
2306.4.8  for  other  shear  panel  sheathing. 

2306.4.2.1  Framing  members:  All  framing 
members  stalled  in  shear  panel  construction 
shall  be  at  least  two  inches  nominal  in 
thickness.  Boundary  members,  and  chords  in 
diaphragms  and  shear  walls  and  collectors 
transferring  forces  to  such  elements  shall  be 
designed  and  detailed  for  the  axial  forces. 
Boundary  members  shall  be  connected  at  all 
corners. 

2306.4.2.2  Opening  details:  Openings  in  shear 
panels  shall  be  designed  and  detailed  to 
transfer  the  shear  and  axial  forces  induced  by 
the  discontinuity  created  by  the  opening  and 
the  details  shall  be  shown  on  the  approved 
plans. 

2306.4.2.3  Connection  and  anchorage 
details:  Positive  connections  and  anchorages, 
capable  of  resisting  the  design  forces,  shall  be 
provided  between  the  shear  panel  and  the 
attached  components.  Concrete  or  masonry 
wall  anchorage  shall  not  be  accomplished  by 
installation  of  toe  nails,  or  nails  subject  to 
withdrawal  and  wood  ledgers  shall  not  be 
installed  in  cross-grain  bending  or  tension. 

2306.4.2.4  Torsion:  The  diaphragms  in 
buildings  having  torsional  irregularity,  where 
the  lateral  stiffness  ratio  of  the  structural 
members  is  greater  than  four  to  one,  or  in 
buildings  with  one  line  of  resistance  in  either 
orthogonal  direction,  shall  be  sheathed  with 
diagonal  boards  or  wood  structural  panels.  The 
length  of  the  diaphragm  normal  to  the  soft  side 
shall  not  exceed  25  feet  (or  7600  mm)  nor  shall 
the  diaphragm  length-to-width  ratio  exceed  1.0 
for  one-story  buildings  or  0.67  for  buildings 
over  one  story  in  height. 

Exception:  Where  calculations  demonstrate 
that  the  diaphragm  deflections  will  be 
tolerated,  the  length  limitation  of  25  feet  (or 
7600  mm)  does  not  apply  and  the  length-to- 
width  ratio  of  1.5  is  permitted  for 
diaphragms  sheathed  with  single  diagonal 
boards;  and  a  ratio  of  2.0  is  permitted  where 
sheathed  with  double  diagonal  boards  or 
wood  structural  panels. 

2306.4.2.5  Panel  height-to-width  ratio:  The 
width  of  a  shear  panel  in  a  diaphragm  or  shear 
wall  shall  not  be  less  than  two  feet  and  the  h/w 
ratio  of  a  shear  wall  shall  not  be  greater  than 
two,  where  h  is  the  height  of  a  shear  panel  or 
shear  wall  an  m>  is  the  width  of  a  shear  panel  or 
shear  wall. 

2306.4.3  Diaphragms:  Wood  diaphragms  shall 
not  be  installed  to  resist  torsional  forces  induced 
by  concrete  or  masonry  construction  in  buildings 
of  Seismic  Performance  Category  D  which  are 
more  than  two  stories  in  height. 


2306.4.3.1  Ties  and  splices:  Diaphragm 
sheathing  shall  not  be  installed  as  the  ties  and 
splices  required  by  780  CMR  1612.3.6.1.1  and 
780  CMR  1612.3.6.1.2. 

Exception:  Diaphragm  sheathing  in 
buildings  of  Seismic  Performance 
Category  C. 

2306.4.4  Shear  walls:  Shear  wall  construction 
shall  comply  with  the  requirements  of  780  CMR 
2306.4.4 

2306.4.4.1  Design  shear  increases:  The  design 
shear  capacity  is  permitted  to  be  doubled 
where  identical  materials  are  applied  to  both 
sides  of  the  wall.  Where  the  shear  capacities  of 
the  materials  are  not  equal,  the  allow  able  shear 
shall  be  considered  to  be  equal  to  either  the 
shear  for  the  side  with  the  higher  capacity  or 
twice  the  shear  for  the  side  with  the  lower 
capacity. 

2306.4.4.2  Material  limitations:  Shear  walls 
shall  be  sheathed  with  wood  structural  panels 
in  Seismic  Performance  Category  C  and  D 
buildings. 

Exceptions: 

1.  In  Seismic  Performance  Category  C 
buildings:  particleboard,  gypsum  sheathing, 
gypsum  wallboard,  fiberboard  and  wire  lath 
and  cement  plaster  shear  walls  are  permitted. 

2.  In  Seismic  Performance  Category  D 
buildings:  particleboard,  gypsum  sheathing, 
gypsum  wallboard  and  wire  lath  and  cement 
plaster  shear  walls  in  one-story  buildings 
and  the  top  story  of  buildings  two  stories  or 
more  in  height  are  permitted 

2306.4.5  Diagonally  sheathed  lumber  shear 
panels:  Diagonally  sheathed  lumber  shear  panels 
shall  be  nailed  in  accordance  with  Table  2306.4.5. 

Table  2306.4.5 

DIAGONALLY  SHEATHED  SHEAR  PANEL 

NAILING  SCHEDULE 


Sheathing 
nominal 

Nailing  to  intermediate 
and  end-supported  studs 

Nailing  at  the  shear 
panel  boundaries 

Number  of  nails  per  board  and  nail  size 

dimension 

Common 
nails 

Box  nails 

Common 
nails 

Box  nails 

1 "  x  6" 

(2)8d 

(3)8d 

(3)8d 

(5)8d 

l"x8" 

(3)8d 

(4)8d 

(4)8d 

(6)8d 

2"  x  6" 

(2)  16d 

(3)  16d 

(3)  16d 

(5)  16d 

2"  x  8" 

(3)  I6d 

(4)  I6d 

(4)  16d 

(6)  16d 

2306.4.5.1    Single    diagonal    construction: 

Single  diagonally  sheathed  lumber  shear  panels 
shall  be  constructed  of  minimum  one-inch- 
thick  nominal  sheathing  boards  laid  at  an 
angle  of  approximately  45  degrees  (0.78   rad) 


382 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


to  the  supports.  The  shear  capacity  for  single 
diagonally  sheathed  lumber  shear  panels  of 
Southern  pine  or  Douglas  fir-larch  shall  not 
exceed  200  pounds  per  lineal  foot  (298  kg/m) 
of  width.  The  shear  capacities  shall  be 
adjusted  by  a  reduction  factor  of  0.82  for 
species  with  a  specific  gravity  of  0.42  or 
greater  but  less  than  0.49  and  a  reduction  factor 
of  0.65  for  species  with  a  specific  gravity  of 
less  than  0.42,  as  contained  in  AFPA  NDS 
listed  in  Appendix  A. 

2306.4.5.1.1  End  joints:  Joints  in  adjacent 
boards  shall  be  separated  by  not  less  than 
one  stud  or  joist  space  and  there  shall  not  be 
less  than  two  boards  between  joints  on  the 
same  support. 

2306.4.5.1.2  Two-inch  nominal  lumber: 
Wood  shear  panels  made  up  of  two-inch- 
thick  diagonal  lumber  sheathing  fastened 
with  16d  nails  shall  be  designed  with  the 
same  shear  capacities  as  shear  panels  using 
one-inch  boards  fastened  with  8d  nails, 
provided  that  there  are  not  splices  in 
adjacent  boards  on  the  same  support  and  the 
supports  are  not  less  than  four  inches 
nominal  in  depth  or  three  inches  nominal  in 
thickness. 

2306.4.5.2  Double  diagonal  construction: 
Double  diagonally  sheathed  lumber  shear 
panels  shall  be  constructed  of  two  layers  of 
diagonal  sheathing  boards  laid  at  90  degrees 
(1.57  rad)  to  each  other  on  the  same  face  of  the 
supporting  members.  Each  chord  shall  be 
considered  as  a  beam  loaded  with  uniform  load 
per  foot  equal  to  50%  of  the  unit  shear  due  to 
diaphragm  action.  The  load  shall  be  assumed 
as  acting  normal  to  the  chord  in  the  plane  of 
the  diaphragm  in  either  direction.  The  span  of 
the  chord  or  portion  thereof  shall  be  the 
distance  between  framing  members  of  the 
diaphragm  such  as  the  joists,  studs  and 
blocking  that  serve  to  transfer  the  assumed 
load  to  the  sheathing.  The  shear  capacity  of 
double  diagonally  sheathed  diaphragms  of 
Southern  pine  or  Douglas  fir-larch,  shall  not 
exceed  600  pounds  per  lineal  foot  (893  kg/m) 
of  width.  The  shear  capacity  shall  be  adjusted 
by  a  reduction  factor  of  0.82  for  species  with  a 
specific  gravity  of  0.42  or  greater  but  less  than 
0.49  and  a  reduction  factor  of  0.65  for  species 
with  a  specific  gravity  of  less  than  0.42  as 
contained  in  AFPA  NDS  listed  in  Appendix  A. 

2306.4.6  Wood  structural  panel  shear  panels: 

The  design  and  shear  capacity  of  wood  structural 
panel  shear  panels  shall  be  in  accordance  with 
780  CMR  2306.4.6.1  for  diaphragms  and 
780  CMR  2306.4.6.2  for  shear  walls,  or  shall  be 
calculated  by  using  the  nail  strengths  in  AFPA 
NDS    and    the    wood    structural    panel    shear 


WOOD 

capacities    as   given    in    DOC    PS    1    listed    in 
Appendix  A. 

Shear  panels  shall  be  constructed  of  wood 
structural  panels  manufactured  with  exterior  glue 
not  less  than  four  feet  by  eight  feet,  except  at 
boundaries  and  changes  in  framing.  Wood 
structural  panels  shall  be  designed  to  resist  shear 
only,  and  chords,  collector  members  and 
boundary  members  shall  be  designed  to  transfer 
the  axial  forces.  Boundary  members  shall  be 
connected  at  all  comers.  Wood  structural  panels 
less  than  12  inches  (305  mm)  wide  shall  be 
blocked. 

2306.4.6.1  Wood  structural  panel  floor  and 
roof  diaphragm  construction:  The  nail  size 
and  spacing  at  diaphragm  boundaries  and  at  the 
edges  of  each  sheet  of  wood  structural  panel 
shall  be  provided  as  shown  in  Table  2306.4.6. 1 
and  Figure  2306.4.6.1,  and  by  the  provisions  of 
780  CMR  2306.4.6.1.1  through  2306.4.6.1.4. 
Nails  of  the  same  size  shall  be  placed  along  all 
intermediate  framing  members  at  12  inches 
(305  mm)  on  center. 

2306.4.6.1.1  Other  wood  species:  Shear 
capacities  for  fasteners  in  framing  members 
of  other  wood  species,  shall  be  calculated  by 
multiplying  the  shear  capacities  for 
Structural  I  panels  by  0.82  for  species  with 
a  specific  gravity  of  0.42  and  greater  but  less 
than  0.49  and  0.65  for  species  with  a 
specific  gravity  of  less  than  0.42.  as 
contained  in  AFPA  NDS  listed  in 
Appendix  A. 

2306.4.6.1.2  Framing  and  panel  layout: 
The  orientation  of  the  structural  framing  and 
wood  structural  panels  shall  comply  with 
Case  1,2,3,4,5  or  6  of  Table  2306.4.6. 1  and 
with  Figure  2306.4.6.1.  For  blocked 
diaphragms,  the  maximum  shear  for  Cases  3, 
4,  5  and  6  shall  not  exceed  1,200  pounds  per 
lineal  foot  (1787  kg/m). 

2306.4.6.1.3  Fastener  spacings  of  two  and 
2i4  inches:  Where  either  two-inch  (51  mm) 
or  2  Vi-inch  (64  mm)  fastener  spacings  are 
installed  with  two-inch-wide  framing 
members  in  accordance  with  Table 
2306.4.6.1,  the  framing  member  adjoining 
panel  edges  shall  be  three  inches  nominal  in 
width  and  nails  at  panel  edges  shall  be 
placed  in  two  lines. 

2306.4.6.1.4  Panels  V/e  inch  thick: 
Unblocked  lVe-inch  panels  with  tongue-and- 
groove  edges  are  permitted  to  use  the 
blocked  diaphragm  shear  capacities  for 
19/32-inch  minimum  nominal  panel 
thickness  values,  where  one-inch  by  %-inch 
crown  by  No.  16  gage  staples  are  driven 
through  the  tongue-and-groove  edges  %inch 
(10  mm)  from  the  panel  edge  so  as  to 
penetrate   the   tongue       Staples   shall    be 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


383 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


spaced  at  one-half  the  boundary  nail  spacing 
for  Cases  I  and  2  and  at  Va  the  boundary  nail 
spacing  for  Cases  3,  4,  5  and  6. 
2306.4.6.2  Wood  structural  panel  shear  wall 
construction:  The  nail  size  and  spacing  at  the 
edge  of  each  wood  structural  panel  shall  be 
provided  as  shown  in  Table  2306.4.6.2  and  by 
the  provisions  of  780  CMR  2306.4.6.2.1 
through  2306.4.6.2.3.  For  3/s-inch  and  7/16- 
inch  panels,  installed  on  studs  spaced  24  inches 


Table  2306.4.6.1 

HORIZONTAL  WOOD  STRUCTURAL  PANEL  DIAPHRAGM  ALLOWABLE  SHEAR 

WITH  FRAMING  MEMBERS  OF  DOUGLAS  FBI-LARCH  OR  SOUTHERN  PINE 


(610  mm)  on  center,  nails  shall  be  spaced  at  six 
inches  (152  mm)  on  center  along  intermediate 
framing  members.  For  all  other  thicknesses 
and  spacing  of  studs,  intermediate  framing 
members  shall  have  nails  of  the  same  size 
spaced  at  12  inches  (305  mm)  on  center.  All 
panel  edges  shall  be  backed  with  twc-inch  or 
wider  framing  members. 


Fastener 
type 

Fastner 
minimum 
penetration 
in  framing 

(inches) 

specified 
panel 

thickness 
(inch) 

Minimum 
nominal 
width  of 
framing 
member 
(inches) 

Lines  of 
fasteners 

Allowable  shear  (pounds  per  foot) 

Blocked  diaphragms 

Unblocked 
diaphragms 

Panel  grade 

Fastener  spacing  (inches)  at  diaphragm 

boundaries  (all  cases),  at  continuous 
panel  edges  parallel  to  load  (Cases  3  and 
4),  and  at  all  panel  edges  (Cases  5  and  6) 

Fastener 

spacing  at  6 

inches  at 

supported 

edges 

6    |         4                 214        |          2 

Case  1 

Cases 

Spacing  (inches)  per  line  at  other  panel 
edges  (cases  1,2,3  and  4) 

2.3, 
4,5 

6 

6 

4 

4 

3 

3 

2 

and  6 

6d  common 

l'/4 

5/16 

2 
3 

185 
210 

250 
280 

375 
420 

420 
475 

165 
185 

125 
140 

8d  common 

l'/2 

% 

2 

3 

270 
300 

360 
400 

530 
600 

600 
675 

240 
265 

180 
200 

Structural  1 

1  Od  common 

1% 

15/32 

2 
3 

320 
360 

425 
480 

640 
720 

730 
820 

285 
320 

215 

240 

lOd  common 

1% 

23/32 

3 
4 
4 

2 
2 
3 

650 
755 
940 

870 
980 

1.305 

940 
1.080 
1,375 

1,230 
1,410 
1.810 

14-gage 
staples 

2 

23/32 

3 
4 

2 
3 

600 
840 

600 
900 

840 
1,140 

900 
1.350 

1,040 
1,440 

1,200 
1.800 

6d  common 

l'/4 

5/16 

2 
3 

170 
109 

225 
250 

335 
380 

380 
430 

150 
170 

110 
125 

C-D,  C-C 

% 

2 

3 

185 
210 

250 
280 

375 
420 

420 
475 

165 
185 

125 
140 

and  other 
similar 

8d  common 

IV2 

% 

2 
3 

240 
270 

320 
360 

480 
540 

545 
610 

215 

240 

160 
180 

grades 

7/16 

2 

3 

255 
285 

340 
380 

505 
570 

575 
645 

230 

255 

170 

190 

15/32 

2 
3 

270 
300 

360 
400 

530 
600 

600 
675 

240 
265 

180 
200 

lOd  common 

1% 

15/32 

2 
3 

290 

325 

385 
430 

575 
650 

655 
735 

255 
290 

190 
215 

C-D,  C-C 

and  other 

similar 

grades 

19/32 

2 
3 

320 
360 

425 
480 

640 
720 

730 
820 

285 
320 

215 
240 

23/32 

3 
4 
4 

2 
2 

3 

645 
750 
935 

870 

980 

1.305 

935 
1,075 
1,390 

1,225 
1,395 
1,510 

14-gage 

staples 

2 

23/32 

3 
4 

2 
3 

600 

820 

600 

900 

820 
1,120 

900 
1,350 

1,020 
1 .400 

1.200 
1,510 

Note  a.  For  sheathing  and  framing  configuration  Cases  I  through  6,  see  Figure  2306.4.6. 1. 
Note  b.   1  inch  =  25.4  mm;  1  pound  per  foot  =  1.489  jg/m. 


384 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


Figure  2306.4.6.1 
SHEATHING  AND  FRAMING  CONFIGURATIONS 


WOOD 


SHEATHING 
FRAMING- 
LOAD      , 

HI 


\ 

LOAD    / 
11/ 

I 

\ 

III 

1 1 1 1 1 1 1 

W 

\ 

rn  ii]  i 

1 

III 

MM 

Ml 

1 

CASE  5 
CONTINUOUS 
PANEL  JOINTS 


\   lll/f 

\     = 

z"" 

CASE  I 

■  CONTINUOUS 
PANa  JOINTS 


Table  2306.4.6.2 
ALLOWABLE  SHEAR  FOR  WOOD  STRUCTURAL  PANEL  SHEAR  WALLS  WITH  FRAM- 
ING OF  DOUGLAS  FIR-LARCH  OR  SOUTHERN  PINE  FOR  WIND  OR  SEISMIC  LOADING 


Minimum 
nominal 

panel 
thickness 

(inch) 

Minimum 

nail 

penetration 

in  framing 

(inches) 

Panels  applied  direct  to  framing 

Panels  applied  over  Va-inch  or  %-inch 
gypsum  sheathing 

Panel  Grade 

Nail  Size 

(common  or 

galvanized 

box) 

Allowable  shear  (pounds  per  foot) 

based  on  nail  spacmg  at  panel 

edges  (inches) 

Nail  size 

(common  or 

galvanized 

box) 

Allowable  shear  (pounds 

per  foot)   based  on  nail 

spacing  at  panel  edges 

(inches) 

6 

4 

3 

2 

6 

4 

3 

2 

5/16 

1% 

6d 

200 

300 

390 

510 

8d 

200 

300 

390 

510 

% 

l'/2    . 

8d 

230 

360 

460 

610 

lOd 

280 

430 

550 

Structural  I 

7/16 

255 

395 

505 

670 

730 

15/32 

280 

430 

550 

730 

15/32 

1% 

lOd 

340 

510 

665 

870 

5/16 

1% 

6d 

180 

270 

350 

450 

8d 

180 

270 

350 

450 

% 

200 

300 

390 

510 

200 

300 

390 

510 

Sheathing, 

% 

l'/j 

8d 

220 

320 

410 

530 

lOd 

260 

380 

490 

Plywood 

7/16 

240 

350 

450 

585 

640 

siding. 

15/32 

260 

380 

490 

640 

15/32 

1% 

lOd 

310 

460 

600 

770 

- 

19/32 

340 

510 

665 

870 

Nail  size 

(galvanized 

casing) 

Nail  size 

(galvanized 

casing) 

Plywood 

5/16 

1% 

6d 

140 

210 

275 

360 

8d 

140 

210 

275 

360 

siding 

% 

l'/2 

8d 

160 

240 

310 

410 

lOd 

160 

240 

310 

410 

Note  a.   1  inch  =  25.4  mm;  1  pound  per  foot  =  1.489  kg/m. 

2306.4.6.2.1  Other  wood  species:  Shear 
capacities  for  fasteners  in  framing  members 
of  other  wood  species  shall  be  calculated  by 
multiplying  the  shear  capacities  for 
Structural  I  panels  by  0  82  for  species  with 
a  specific  gravity  of  0  42  or  greater  but  less 


than  0  49  and  0.65  for  species  with  a 
specific  gravity  of  less  than  0.42,  as 
contained  in  AFPA  NDS  listed  in 
Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


385 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2306.4.6.2.2  Three-inch  nominal  width 
framing:  Framing  shall  be  three  inches 
nominal  or  wider  and  the  nails  shall  be 
staggered  where  nails  are  spaced  two  inches 
(51  mm)  on  center  or  where  lOd  nails 
having  a  penetration  into  framing  of  more 
than  1%  inches  (41  mm)  are  used  with  a 
three-inch  (76  mm)  nail  spacing. 

2306.4.6.2.3  Panels  %  inch  and  7/16  inch 
thick:  The  shear  capacity  for  %-inch  and 
7/16-inch  panels  applied  direct  to  framing 
with  8d  nails  is  permitted  to  be  increased  to 
the  values  shown  for  15/32-inch  panels  with 
the  same  nailing  where  the  framing  studs  are 
spaced  a  maximum  of  16  inches  (406  mm) 
on  center  or  the  panels  are  applied  with  the 
long  dimension  across  the  studs. 

Shear  capacity  for  %-inch  and  7/16-inch 
panels  shall  be  as  indicated  in  Table 
2306.4.6.2. 

2306.4.7  Particleboard  shear  panels  The  design 
shear  capacity  of  particleboard  panels  shall  be  in 
accordance  with  780  CMR  2306.4.7.1  for 
diaphragms  and  780  CMR  2306.4.7.2  for  shear 
walls. 

Shear    panels    shall    be    constructed    with 
particleboard  sheets    not  less  than  four  feet  by 


eight  feet,  except  at  boundaries  and  changes  in 
framing,  particleboard  panels  shall  be  designed  to 
resist  shear  only,  and  chords,  collector  members 
and  boundary  members  shall  be  designed  to 
transfer  the  axial  forces.  Boundary  members  shall 
be  connected  at  all  corners.  Particleboard  panels 
less  than  12  inches  (305  mm)  wide  shall  be 
blocked 

2306.4.7.1  Particleboard  floor  and  roof 
diaphragm  construction:  The  nail  size  and 
spacing  at  diaphragm  boundaries  and  the  edges 
of  each  sheet  of  particleboard  shall  be  as 
shown  in  Figure  2306.4.6.1  and  Table 
2306.4.7.1  and  shall  be  designed  in  accordance 
with  the  provisions  of  this  section.  Nails  of  the 
same  size  shall  be  placed  along  all  intermediate 
framing  members  at  12  inches  (305  mm)  on 
center. 

2306.4.7.1.1  Other  wood  species:  Shear 
capacities  for  fasteners  in  framing  members 
of  other  wood  species  shall  be  calculated  by 
multiplying  the  shear  capacities  by  0.82  for 
species  with  a  specific  gravity  of  0.42  or 
greater  but  less  than  0.49,  and  by  0.65  for 
species  with  a  specific  gravity  of  less  than 
0.42,  as  contained  in  AFPA  NDS  listed  in 
Appendix  A . 


Table  2306.4.7.1 

ALLOWABLE  SHEAR  FOR  PARTICLEBOARD  DIAPHRAGMS  WITH  FRAMING  MEMBERS 

OF  DOUGLAS  FIR-LARCH  OR  SOUTHERN  PINE  FOR  SEISMIC  LOADING 


Common 
nail  size 

Minimum 

nail 

penetration 

in  framing 

(inches) 

Minimum 
nominal 

panel 
thickness 

(inch) 

Minimum 
nominal  width 
of  framing 
member 
(inches) 

Allowable  shear  (pounds  per  foot) 

Blocked  Diaphragms 

Unblocked 
diaphragms 

Panel 

Nail  spacing  (inches)  at  diaphragm 

boundaries  (all  cases),  at  continuous 

panel  edges  parallel  to  load  (Cases  3  & 

4),  and  all  panel  edges  (Cases  5  &  6) 

Nails  spaced  6  inches 

maximum  at 

supported  edges 

grade 

6 

4 

2'/2 

2 

Case  1  (No 
unblocked 
edges  or 
continuous 

joints 

parallel  to 

load) 

All  other 
configur- 
ations 
(Cases  2, 

Nail  spacing  (inches)  at  other  panel 
edges  (Cases  1,2,  3  &  4) 

6 

6 

4 

3 

3,4,  5  & 
6) 

6d 

1% 

5/16 

3 

170 
190 

225 
250 

335 
380 

380 
430 

150 
170 

110 
125 

Va 

2 
3 

185 
210 

250 

280 

375 

420 

420 

475 

165 
185 

125 
140 

8d 

l'/2 

% 

3 

240 
270 

320 
360 

480 
540 

545 
610 

215 

240 

160 
180 

2-M-W 

7/16 

2 
3 

255 
285 

340 
380 

505 
570 

575 
645 

230 
255 

170 
190 

Vi 

2 
3 

270 
300 

360 
400 

530 
600 

600 
675 

240 
265 

180 
200 

lOd 

1% 

'A 

2 
3 

290 
325 

385 

430 

575 
650 

655 
735 

255 
290 

190 
215 

% 

2 
3 

320 
360 

425 
480 

640 
720 

730 
820 

285 
320 

215 

240 

2-M-3 

lOd 

1% 

% 

2 
3 

320 

360 

425 

480 

640 

720 

730 
820 

285 
320 

215 

240 

Note  a.  For  sheathing  and  framing  configuration  Cases  1  through  6,  see  Figure  2306. 4.i 
Note  b.    1  inch  =  25.4  mm;  1  pound  per  foot  =  1.489  kg/m 


386 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


2306.4.7.1.2  Framing  and  panel  layout: 

The  orientation  of  the  structural  framing  and 
particleboard  panels  shall  comply  with 
Figure  2306.4.6. 1  and  Case  1,  2,  3,  4,5  or  6 
in  Table  2306.4.7.1. 

2306.4.7.1.3  Fastener  spacings  of  two  and 
2'/2  inches:  Where  either  two-inch  (51  mm) 
or  2 '/2-inch  (64  mm)  fastener  spacings  are 
installed  with  2-inch-wide  framing  members 
in  accordance  with  Table  2306.4.7.1,  the 
framing  member  adjoining  panel  edges  shall 
be  three  inches  nominal  in  width  and  nails  at 
panel  edges  shall  be  placed  in  two  lines. 

2306.4.7.1.4  Panel  edge  framing:  Framing 
at  adjoining  panel  edges  shall  be  three 
inches  nominal  or  wider  and  nails  shall  be 
staggered  where  lOd  nails  having 
penetration  into  framing  of  more  than  1% 
inches  (41  mm)  are  spaced  three  inches  (76 
mm)  or  less  on  center. 

2306.4.7.2  Particleboard  shear  wall 
construction:  The  required  nail  size  and 
spacing  in  Table  2306.4.7.2  apply  to  panel 
edges  only.  All  panel  edges  shall  be  backed 
with  two-inch  nominal  or  wider  framing. 
Sheets  are  permitted  to  be  installed  either 
horizontally  or  vertically.  For  %-inch 
particleboard  sheets  installed  with  the  long 
dimension  parallel  to  studs  spaced  24  inches 
(610  mm)  on  center,  nails  shall  be  spaced  at  six 
inches  (152  mm)  on  center  along  intermediate 
framing  members.  For  all  other  conditions, 
nails  of  the  same  size  shall  be  spaced  at  12 
inches  (305  mm)  on  center  along  intermediate 
framing  members. 

2306.4.7.2.1  Other  wood  species:  Shear 
capacities  for  fasteners  in  framing  members 
of  other  wood  species,  shall  be  calculated  by 
multiplying  the  shear  capacities  by  0.82  for 
species  with  a  specific  gravity  of  0.42  or 
greater  but  less  than  0.49  and  0.65  for 
species  with  a  specific  gravity  of  less  than 
0.42  as  contained  in  AFPA  NDS  listed  in 
Appendix  A. 


2306.4.7.2.2  Three-inch  nominal  width 
framing:  Framing  shall  be  three  inches 
nominal  or  wider  and  the  nails  shall  be 
staggered  where  nails  are  spaced  two  inches 
(51  mm)  on  center  or  where  lOd  nails 
having  a  penetration  into  framing  of  more 
than  1%  inches  (41  mm)  are  installed  with  a 
three-inch  (76  mm)  nail  spacing. 

2306.4.7.2.3  Particleboard  of  %  and  7/16 
inch  thicknesses:  The  shear  capacities  for 
%-inch  and  7/16-inch  particleboard  applied 
direct  to  framing  with  8d  nails,  are  permitted 
to  be  increased  to  the  '/2-inch  particleboard 
shear  capacities  of  Table  2306.4.7.2  where 
the  framing  studs  are  spaced  a  maximum  of 
16  inches  (406  mm)  on  center  or  the 
particleboard  is  applied  with  the  long 
dimension  perpendicular  to  the  studs. 

2306.4.7.2.4  Double-sided  wall:  Where 
particleboard  is  applied  to  both  faces  of  a 
wall  and  the  nail  spacing  is  less  than  six 
inches  (152  mm)  on  center  on  either  side, 
panel  joints  shall  be  offset  to  be  placed  on 
different  framing  members,  or  framing  shall 
be  three  inches  nominal  or  thicker  and  nails 
on  each  side  shall  be  staggered. 

2306.4.8  Shear  panels  sheathed  with  other 
materials:  Wood  stud  walls  sheathed  with  lath 
and  plaster,  gypsum  sheathing  board  or 
gypsum  wallboard,  constructed  in  accordance 
with  780  CMR  2502.0,  or  fiberboard  sheathing 
constructed  in  accordance  with  780  CMR 
2309.8,  shall  be  permitted  to  be  used  to  resist 
earthquake  forces  in  wood  frame  buildings. 
Nails  shall  be  spaced  at  least  %  inch  (10  mm) 
from  the  edges  and  ends  of  boards  and  panels. 
The  maximum  height-to-width  ratio  shall  be 
1.5.  The  shear  capacities  utilized  in  design 
shall  not  be  cumulative  with  the  shear 
capacities  of  other  materials  applied  to  the 
same  wall. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


387 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  2306.4.7.2 

ALLOWABLE  SHEAR  FOR  PARTICLEBOARD  SHEAR  WALLS  WITH  FRAMING  OF 

DOUGLAS  FIR-LARCH  OR  SOUTHERN  PINE  FOR  SEISMIC  LOADING 


Minimum 
nominal 

panel 
thickness 

(inch) 

Minimum  nail 

penetration  in 

framing 

(inches) 

Panels  applied  direct  to  framing 

Panels  applied  over  '/2-inch  gypsum  sheathing 

Panel 

grade 

Nail  size 

(common  or 

galvanized 

box) 

Allowable  shear  (pounds  per 

foot)3  nail  spacing  at  panel 

edges  (inches) 

Nail  size 

(common  or 

galvanized 

box) 

Allowable  shear  (pounds  per 

foot)   nail  spacing  at  panel 

edges  (inches) 

6 

4 

3 

2 

6 

4 

3 

2 

7,6 

l'/4 

6d 

180 

270 

350 

450 

8d 

180 

270 

350 

450 

% 

200 

300 

390 

510 

200 

300 

390 

510 

% 

VA 

8d 

220 

320 

410 

530 

lOd 

260 

380 

490 

2-M-W 

'A, 

240 

350 

450 

585 

640 

Vt 

260 

380 

490 

640 

Vi 

1% 

lOd 

310 

460 

600 

770 

NAb 

NAb 

NAb 

NAb 

NAb 

% 

340 

510 

665 

870 

Note  a.  1  inch  =  25.4  mm;  1  pound  per  foot  =  1.489kg/m. 
Note  b.  NA  =  Not  Applicable 

780  CMR  2307.0  WOOD  STRUCTURAL 
PANELS 

2307.1  Standards:  All  wood  structural  panels  that 
are  utilized  structurally  shall  comply  with  the 
requirements  of  DOC  PS  1,  DOC  PS  2,  HPMA  HP 
and  HPMA  HP-SG  listed  in  Appendix  A  for  the 
type,  grade  and  span  rating  or  species  group  of  wood 
structural  panels  involved,  and  shall  be  so  identified 
by  an  approved  agency. 

2307.2  Types:  Wood  structural  panels  for  interior 
installations  shall  be  of  the  interior  type,  moisture- 
resistant  type  or  exterior  type.  Wood  structural 
panels  for  exterior  installations  shall  be  of  the 
exterior- waterproof  type,  except  that  wood  structural 
panel  roof  sheathing  exposed  to  the  outdoors  on  the 
underside  is  permitted  to  be  of  the  interior  type  and 
bonded  with  exterior  glue.  Exterior  wood  structural 
panels  shall  not  be  applied  directly  to  the  framing  as 
a  siding  unless  the  wood  structural  panel  has  a 
minimum  nominal  thickness  of  %  inch.  Joints  shall 
occur  over  framing  members,  unless  wood  or  wood 
structural  panel  sheathing  is  used  or  joints  are  lapped 
horizontally  a  minimum  of  VA  inches  (38  mm)  or 
otherwise  made  waterproof  in  an  approved  manner. 
Where  a  wood  structural  panel  is  utilized  as  lapped 
siding  without  sheathing,  the  wall  framing  to  which 
such  wood  structural  panel  is  attached  shall  be 
diagonally  braced. 

23073  Spans:  The  maximum  spans  for  wood 
structural  panel  sheathing  shall  be  limited  by  the 
allowable  stresses  and  deflections  for  the  design  live 


load,  but  shall  not  be  greater  than  the  spans  specified 
in  Tables  2307.3.1(1),  2307.3.1(2),  2307.3.3  and 
2307.3.5.  The  spans  specified  in  these  tables  shall 
apply  to  wood  structural  panels  not  treated  with  fire 
retardant  chemicals.  The  design  criteria  for  fire 
retardant-treated  wood  structural  panels  shall  be 
provided  by  valid  research  reports  from  approved 
sources. 

2307.3.1  Floor  and  roof  sheathing:  Allowable 
spans  for  floor  and  roof  sheathing  shall  be  as 
specified  in  Tables  2307.3.1(1)  and  2307.3.1(2). 
The  values  in  Table  2307.3.1(1)  apply  to 
Structural  I,  C-D  and  C-C  sheathing  and  single 
floor  grades  only,  and  are  limited  to  the  spans 
shown  because  of  the  possible  effects  of 
concentrated  loads. 

2307.3.2  Floor  sheathing:  Edges  of  wood 
structural  panel  floor  sheathing  shall  have 
approved  tongue-and-groove  joints  or  shall  be 
supported  with  blocking,  unless  Vi-inch  minimum 
thickness  underlayment  or  VA  inches  (38  mm)  of 
approved  cellular  or  lightweight  concrete  is 
installed,  or  unless  the  finish  floor  is  of  %-inch 
wood  strip.  The  allowable  uniform  load  based  on 
a  deflection  of  1/360  of  the  span  is  100  pounds  per 
square  foot  (psf)  (488  kg/m2)  at  maximum  span. 

2307.3.3  Wood  structural  panel  combination 
subfloor  underlayment:  Allowable  spans  for 
combination  subfloor  underlayment  shall  be  as 
specified  in  Table  2307.3.3. 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


Table  2307.3.1(1) 

ALLOWABLE  SPANS  AND  LOADS  FOR  WOOD  STRUCTURAL  PANEL  SHEATHING 

GRADES  AND  SINGLE  FLOOR  GRADES  CONTINUOUS  OVER  TWO  OR  MORE  SPANS 

WITH  LONG  DIMENSION  PERPENDICULAR  TO  SUPPORTS^ 


Sheathing  grades 

Roof 

Floor 

Span  rating 

Panel  thickness 
(inch)' 

Maximum  span  (inches)" 

Load  (pounds  per  square  foot) 

Maximum  span 
(inches) 

Roof/floor  span 

With  edge 
support 

Without  edge 
support 

Total  load 

Live  load 

12/0 
16/0 
20/0 

24/0 
24/16 

32/16 
40/20 
48/24 

5'16 

5'16,% 

5'16,% 

%,7/i6,  Vz 

7'liM 

15'32,  Vz,  5/s 

23'32,s/a,  Va,  7/b 

23'32,3/4,  % 

12 
16 
20 

24 
24 

32 
40 
48 

i2 
16 
20 

20d 
24 

28 
32 
36 

40 
40 
40 

40 
50 

40 
40 
45 

30 
30 
30 

30 
40 

30 
30 
35 

0 
0 
0 

0 
16 

■6 

20 

24 

Single  floor  grades 

Roof 

Floor 

Span  rating 

Panel  thickness 
(inches) 

Maximum  span  (inches) 

Load  (pounds  per  square  foot) 

Maximum  span 
(inches) 

With  edge 
support0 

Without  edge 
support 

Total  load 

Live  load 

16  o.c. 
20  o.c. 

24  o.c. 
32  o.c. 

48  o.c. 

19'32,% 
"'32,  Ve,  % 

%,i 

1332.  l1/s 

24 
32 

48 
48 

60 

24 
32 

36 
40 

48 

50 
40 

35 
50 

50 

40 
30 

25 
40 

40 

>6 

20 

24 
32 

48 

Note  a.   The  allowable  loads  were  determined  based  on  a  dead  load  of  10  psf.   If  the  dead  load  exceeds  10  psf.  then 

the  live  load  shall  be  reduced  accordingly. 

Note  b.  For  limitations  on  the  applicability  of  this  table  to  wood  structural  panel  grade,  see  780  CMR  2307.3. 1 

Note  c    Tongue-and-groove  edges,  panel  edge  clips  (one  midway  between  each  support,  except  two  equally  spaced 

between  supports  48  inches  on  center),  lumber  blocking,  or  other.     Only  lumber  blocking  shall  satisfy  blocked 

diaphragm  requirements. 

Note  d.  24  inches  for  '/2-inch  panels. 

Note  e.    Maximum  framing  space  shall  be  24  inches  on  center  for  floors  where  1  Vi  inches  of  cellular  or  lightweight 

concrete  is  applied  over  the  panels. 

Note  f.    Maximum  frame  spacing  shall  be  24  inches  on  center  where  '/i-inch  wood  strip  flooring  is  installed  a  right 

angles  to  joist 

Note  g.  Shall  apply  only  to  panels  24  inches  or  wider. 

Note  h.  Span  rating  shall  appear  on  all  panels  in  the  construction  grades  listed  in  780  CMR  2307.3.1. 

Note  i.   1  inch  =  25.4 mm;  1  psf  =4.882  kg/m2 

Table  2307.3.1(2) 

ALLOWABLE  LOADS  FOR  WOOD  STRUCTURAL  PANEL  ROOF  SHEATHING 

CONTINUOUS  OVER  TWO  OR  MORE  SPANS  AND  LONG  DIMENSION  PARALLEL  TO 

SUPPORTS 
(Plywood  Structural  Panels  are  5  ply/5  layer  unless  otherwise  noted)  ' 


Panel  grade 

Thickness  (inch) 

Span  rating 

Maximum  span 
(inch) 

Load  at  maximum  span  (psf) 

Live 

Total 

7'16 

24/0,24/16 

24 

20 

30 

Structural i 
sheathing 

!5'32 
Vz 

32/16 
32/16 
40/20 

24 
24 
24 

40b 
70 

50 
80 

23'32,y« 

48/24 

24 

90 

100 

\ 

24/0,24/16 

16 

40 

50 

32/16 

24 

20 

25 

Sheathing 

$32 

24/0,32/16 

40/20 

24 
24 

25 
40b 

30 
50" 

s/s 

32/16,40/20 

24 

45b 

55b 

"'32,% 

40/20, 48/24 

24 

60b 

65b 

9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


389 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Note  a.  Uniform  load  deflection  limitations:  1/180  of  span  under  live  load  plus  dead  load,  1/240  under  live  load  only 
Edges  shall  be  blocked  with  lumber  or  other  approved  type  of  edge  supports. 
Note  b.  For  composite  and  4-ply  plywood  panels,  load  shall  be  reduced  by  15  psf 
Note  c.   1  inch  =  25.4  mm;  1  psf  =  4  882  kg/m 


Table  2307.3.3 

ALLOWABLE  SPANS  FOR  WOOD 

STRUCTURAL  PANEL  COMBINATION 

SUBFLOOR  UNDERLAYMENT"  PANELS 

CONTINUOUS  OVER  TWO  OR  MORE 

SPANS  AND  LONG  PANEL  DIMENSION 

PERPENDICULAR  TO  SUPPORT 

(THICKNESS  IN  INCHES)d 


Table  2307.3.5 
ALLOWABLE  STUD  SPACING  FOR  WOOD 
STRUCTURAL  PANEL  WALL  SHEATHING 


Identification 

Maximum  spacing  of  joists  (inches) 

Species 
groups 

16 

20 

24 

32 

48 

1 

2,3 
4 

14 

% 

3/4 

V* 

Va 

1 

- 

"  • 

Single  floor 
span  rating 

16  o.c. 

20  o.c. 

24  o.c. 

32  o.c. 

48  o.c. 

Note  a.  For  limitations  on  the  use  of  Table  2307.3.3  see 

780  CMR  2307.3.4. 

Note  b    Applicable  to  all  grades  of  sanded  exterior-type 

plywood. 

Note  c.     Applicable  to  underlayment  grade  and  C-C 

(plugged)  plywood  and  single-floor  grade  panels. 

Note  d.   1  inch  =  25.4  mm;  1  psf  =  4.882  kg/m2. 

2307.3.4  Limitations:  Table  2307.3.3  is 
applicable  to  under  layment  grade,  C-C  (plugged), 
single-floor  grade  and  all  grades  of  sanded 
exterior-type  plywood.  For  panels  with  a  span 
rating  of  other  than  48  inches  (1219  mm)  on 
center  (o.c),  the  allowable  uniform  load  based  on 
a  deflection  of  1/360  of  the  span  is  100  psf  (488 
kg/m  ).  Panels  with  a  span  rating  of  48  inches 
o.c.  are  limited  to  a  total  load  of  65  psf  (317 
kg/m  )  at  the  maximum  span.  Wood  structural 
panel  edges  shall  have  approved  tongue-and- 
groove  joints  or  shall  be  supported  with  blocking, 
unless  %-inch  minimum  thickness  underlayment 
or  l'/2  inches  (38  mm)  of  approved  cellular  or 
lightweight  concrete  is  installed,  or  unless  the 
finish  floor  is  of  %-inch  wood  strip.  If  wood 
strips  are  perpendicular  to  the  supports, 
thicknesses  or  span  ratings  shown  for  16-inch 
(406  mm)  and  20-inch  (508  mm)  spans  shall  be 
used  on  24-inch  (610  mm)  spans.  Spans  are 
limited  to  the  values  shown  in  Table  2307.3.3 
because  of  the  possible  effects  of  concentrated 
loads. 

2307.3.5  Vertical  maximum  stud  spacing:  Stud 
spacing  for  vertical  sheathing  shall  be  as  specified 
in  Table  2307.3.5. 


Panel  span  rating 

Panel 

thickness 

(inch)d  and 

construction 

Maximum  stud  spacing 

(inches) 

Exterior  coverings  nailed  to: 

Stud 

Sheathing 

12/0,  16/0,20/0 
or  wall  -  16  o.c. 

5/16.% 

16 

!6b 

24/0,24/16,32/16 
or  wall  -  24  o.c. 

%.7'16.  15'32. 

14 

24 

c 

24 

Note  a.     Blocking  of  horizontal  joints  shall  not  be 

required. 

Note  b.   Plywood  sheathing  %  inch  thick  or  less  shall  be 

applied  with  long  dimension  across  studs. 

Note  c.   Three-ply  plywood  panels  shall  be  applied  with 

long  dimension  across  studs 

Note  d    1  inch  =  25.4  mm. 

2307.4  Stressed  skin  panel:  For  use  in  stressed  skin 
or  other  prefabricated  construction,  wood  structural 
panel  design  shall  be  determined  by  approved 
engineering  analysis  or  by  the  tests  prescribed  in 
780  CMR  1710.0  for  prefabricated  assemblies. 

780  CMR  2308.0  PARTICLEBOARD 

2308.1  Standards  Particleboard  shall  conform  to 
ANSI  A208.1  listed  in  Appendix  A  Particleboard 
shall  be  identified  by  the  grade  mark  or  the 
certificate  of  inspection  issued  by  an  approved 
agency 

2308.2  Floor  underlayment:  Underlayment  shall 
conform  to  Type  1-M-l  or  sanded  Type  2-M-W  of 
ANSI  A208.1  listed  in  Appendix  A  Underlayment 
shall  not  be  less  than  V*  inch  in  thickness  and  shall 
be  installed  in  accordance  with  the  manufacturer's 
installation  instructions 

2308.3  Subfloor  or  combination  subfloor 
underlayment:  Allowable  spans  and  grades  for 
combination  subfloor  underlayment  shall  be  as 
specified  in  Table  2308.3  All  panels  shall  be 
continuous  over  two  or  more  spans  and  the  tongue- 
and-groove  panels  shall  be  installed  with  the  long 
dimension  perpendicular  to  the  supports.  Uniform 
deflection  limitation  shall  be  1/360  of  the  span  under 
a  minimum  load  of  100  psf.  Edges  shall  have 
tongue-and-groove  joints  or  shall  be  supported  with 
blocking  unless  %-inch  minimum  thickness 
underlayment  is  installed,  or  unless  the  finish  floor 
is  of  25/32-inch  wood  strip 


390 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


Table  2308.3 

ALLOWABLE  SPANS  FOR 

PARTICLEBOARD  SUBFLOOR  AND 

COMBINATION  SUBFLOOR 

UNDERLAYMENT  a 


Thickness 
(inches) 

Maximum  spacing   of  supports  (inches) 

Grade 

Subfloor 

Combination  subfloor 
underlavment 

2-M-W 

Vi 
s/e 

3A 

16 
20 

24 

16 
24 

2-M-3 

3A 

20 

20 

Note  a.    For  limitations  on  the  use  of  Table  2308.3,  see 

780  CMR  2308.3 

Note  b.  1  inch  =  25.4  mm. 

2308.4  Roof  sheathing:  Allowable  loads  for  roof 
sheathing  shall  be  in  accordance  with  the  spans  and 
grades  specified  in  Table  2308.4.  Panels  shall  be 
continuous  over  two  or  more  spans.  Uniform  load 
deflection  limitations  shall  be  1/180  of  the  span  under 
live  had  plus  dead  load  and  1/240  of  the  span  under 
live  load  only.  Edges  of  all  %-inch  panels  and  edges 
of  7/16-inch  panels  with  24  inches  (610  mm)  o.c. 
spacing  shall  be  supported  with  blocking  or  edge 
clips. 

Table  2308.4 

ALLOWABLE  LrVE  LOADS  FOR 

PARTICLEBOARD  ROOF  SHEATHINGab 


Grade 

Thickness 
(inches) 

Maximum  on- 
center  spacing 
of  supports 
(inches! 

Live  load 

(pounds 

per  square 

foot) 

Total  load 
(pounds  per 
square  foot) 

2-M-W 

% 

7/16 
7/16 
Vl 

</2 

16 

16 
24 
16 
24 

45 

105 
30 

110 
40 

65 

105 
40 

150 
55 

Note  a.  For  limitations  on  the  use  of  Table  2308.4,  see 
780  CMR  2308.4. 

Note  b.  1  inch  =  25.4  mm;  1  pound  per  square  foot  = 
4.882  kg/m2. 

2308.5  Siding  and  sheathing:  Allowable  spans  and 
grades  ofparticleboard  siding  and  sheathing  shall  be 
as  specified  in  Tables  2308.5(1)  and  2308.5(2). 

Table  2308.5(1) 

ALLOWABLE  SPANS  FOR  EXPOSED 

PARTICLEBOARD  PANEL  SIDING 


Stud 
spacing 
(inches) 

Minimum  thickness  (inches) 

Grade 

Siding 

Exterior  ceilings 
and  soffits 

Direct  to 
studs 

Continuous 
support 

Direct  to 
supports 

2-M-W 

16 
24 

3/s 

5/16 

5/16 

5/16 

% 

2-M-l  and 
2-M-2 

16 
24 

% 
% 

Table  2308.5(2) 

ALLOWABLE  SPANS  FOR 

PARTICLEBOARD  WALL  SHEATHING3 


Thickness 
(inches) 

Stud  spacing  (inches) 

Grade 

Siding  nailed 
to  studs 

Sheathing  under 

coverings  parallel  or 

perpendicular  to 

studs 

2-M-W 

5/16 
% 

7/16 

16 

24 
24 

16 

24 

2-M-l  and 

2-M-2 

3/a 

16 
16 

16 

Note  a.  Where  not  exposed  to  the  weather  and  where  the 
long  dimension  of  the  panel  is  parallel  or  perpendicular 
to  the  studs. 
Note  b.   1  inch  =  25.4  mm. 

780  CMR  2309.0  FIBERBOARD 

2309.1  Standards:  Insulating  boards  manufactured 
with  wood  or  other  vegetable  fibers  which  are  used 
as  building  boards  for  sheathing,  roof  decks,  interior 
wall  and  ceiling  finishes,  roof  insulation  or  sound 
deadening,  shall  be  vermin-proof,  resistant  to  rot- 
producing  fungi,  water-repellent  and  shall  conform 
to  the  strength  and  durability  tests  specified  in 
ASTM  C208~and  C532  and  AHA  A  194.1  listed  in 
Appendix  A.  Sheathing  that  is  utilized  structurally 
shall  be  so  identified  by  an  approved  agency.  Where 
required  under  the  provisions  of  780  CMR  7  or  8, 
the  boards  shall  be  protected  or  treated  to  develop 
the  required  fireresistance  rating  or  flameresistance 
as  determined  by  test. 

2309.2  Jointing:  To  insure  tight-fitting  assemblies, 
edges  shall  be  manufactured  with  square, 
shiplapped,  beveled,  tongue-and-groove  or  U-shaped 
joints. 

2309.3  Roof  insulation:  Where  used  as  roof 
insulation  in  all  types  of  construction,  fiberboards 
shall  be  protected  with  an  approved  roof  covering. 

2309.4  Wall  insulation:  Where  installed  and 
firestopped  to  comply  with  780  CMR  7,  fiberboards 
are  permitted  as  wall  insulation  in  all  types  of 
construction.  In  fire  wall  and  fire  separation  wall 
constructions,  unless  treated  to  comply  with 
780  CMR  803.2  for  Class  1  materials,  the  boards 
shall  be  cemented  directly  to  the  masonry  or  other 
noncombustible  base  and  shall  be  protected  with  an 
approved  noncombustible  veneer  anchored  to  the 
base  without  intervening  air  spaces. 

2309.5  Drywall  construction:  Where  fireresistance 
ratings  are  required,  provision  shall  be  made  for 
interlocking,  lapping  or  otherwise  protecting  the 
joints  between  adjacent  boards  to  insure  smoke  and 
flame  tightness. 


Note  a    1  inch  =  25  4  mm. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2309.6  Insulating  roof  deck:  Where  used  as  roof 
decking  in  open  beam  construction,  fiberboard 
insulating  roof  deck  shall  have  a  nominal  thickness 
of  not  less  than  one  inch. 

2309.7  Siding:  Hardboard  siding  shall  comply  with 
AHA  A135.6  listed  in  Appendix  A. 

2309.8  Shear  capacity:  Wood  stud  walls  sheathed 
with  fiberboard  sheathing  are  permitted  to  resist 
horizontal  loads  provided  that  such  walls  comply 
with  Table  2309.8.  Fiberboard  shear  walls  shall  not 
be  utilized  to  resist  horizontal  loads  from  concrete  or 
masonry  walls. 

Table  2309.8 

ALLOWABLE  SHEAR  CAPACITY  FOR 

WIND  OR  SEISMIC  LOADING  ON  SHEAR 

WALLS  OF  FIBERBOARD  SHEATHING 

BOARD 


Thickness  and 
grade 

Fastener  type 

Shear  capacity  for  3  - 

inch  nail  spacing 

around  perimeter  and 

6-inch  at  intermediate 

studs  (poundsper  foot 

of  wall) 

VS-inch  Regular 
density 

No.  1 1  ga.  galv. 

Roofing  nail  1  Vi" 

long  7/i6"head 

50 

'/;-inch 

Intennediate 

density 

No.  1 1  ga.  galv. 

Roofing  nail  1  !4" 

long7/l6"head 

60 

25/32-inch 
Regular  density 

No.  1 1  ga.  galv. 

Roofing  nail  1  Vi" 

long  7i6"head 

60 

Note  a.    Fiberboard  sheathing  is  permitted  to  be  stapled 

using  16-gage  galvanized  staples  \Va  inch  long  for  XA- 

inch  sheathing  and  1  Vi  inch  long  for  25/32-inch  sheathing. 

Staples  shall  have  a  minimum  crown  of  7/16  inch  and 

shall  be  spaced  three  inches  o.c.  at  edges  and  six  inches 

o.c.  at  studs. 

Note  b.    Where  studs  are  permitted  to  be  located  at  24 

inches  o.c,  the  shear  capacity  shall  not  be  greater  than  50 

pounds  per  linear  foot  (plf). 

Note  c.   1  inch  =  25.4  mm:  1  plf  =  1.489  kg/m. 

2309.8.1  Framing:  Four-foot  by  eight-foot 
fiberboard  sheathing  shall  be  applied  vertically  to 
wood  studs  not  less  than  two  inches  nominal  in 
thickness  spaced  16  inches  (406  mm)  on  center. 

Exception:  Studs  on  24-inch  centers  are 
permitted  for  '/;-inch  intermediate  density 
sheathing  and  25/32-inch  regular  density 
sheathing  in  accordance  with  Table  2309.8. 

2309.8.2  Nailing:  Nailing  shall  be  in  accordance 
with  Table  2309.8.  Nails  shall  be  spaced  not  less 
than  %  inch  (10  mm)  from  edges  and  ends  of 
sheathing. 


780  CMR  2310.0  FIRERETARDANT- 
TREATEDWOOD 

2310.1  Applications:  Fireretardant-treated  wood 
shall  comply  with  780  CMR  2310.0.  Where  Table 
602  permits  fireretardant-treated  wood  in  Types  1 
and  2  construction,  fireretardant-treated  wood  shall 
not  be  utilized  in  Ioadbearing  walls  or  in  assemblies 
with  a  required  fireresistance  rating  of  more  than  one 
hour. 

2310.2  General:  Fireretardant-treated  wood  shall  be 
any  wood  product  which,  when  impregnated  with 
chemicals  by  a  pressure  process  in  accordance  with 
AWPA  C20  or  AWPA  C27  listed  in  Appendix  A,  or 
other  means  during  manufacture,  shall  have,  when 
tested  in  accordance  with  ASTM  E84  listed  in 
Appendix  A,  a  flame  spread  rating  not  greater  than 
25  when  the  test  is  continued  for  a  period  of  30 
minutes,  without  evidence  of  significant  progressive 
combustion;  and  the  flame  front  shall  not  progress 
more  than  lO'/i  feet  (3048  mm)  beyond  the 
centerline  of  the  burner  at  any  time  during  the  test. 
Fireretardant-treated  wood  shall  be  dried  to  a 
moisture  content  of  19%  or  less  for  lumber  and  15% 
or  less  for  plywood  before  use. 

2310.2.1  Strength  modifications:  Design  values 
for  untreated  lumber,  as  specified  in  780  CMR 
2303.1,  shall  be  adjusted  for  lumber  that  is 
pressure  impregnated  with  fireretardant 
chemicals.  Adjustments  to  the  design  values 
shall  be  based  upon  an  approved  method  of 
investigation  which  takes  into  consideration  the 
effects  of  the  anticipated  temperature  and 
humidity  to  which  the  fireretardant-treated  wood 
will  be  subjected,  the  type  of  treatment  and 
redrying  procedures. 

2310.2.2  Labeling:  Fireretardant-treated  lumber 
and  plywood  shall  bear  the  label  of  approved 
agencies  in  accordance  with  780  CMR  1704.3.2. 
Such  labels  shall  indicate  compliance  with  the 
appropriate  treating  standard  in  accordance  with 
780  CMR  2310.2  and  indicate  compliance  with 
780  CMR  23  10.2.1. 

2310.3  Exposure  to  weather:  Where  fireretardant- 
treated  wood  is  to  be  exposed  to  the  weather,  the 
material  shall  be  further  identified  to  indicate  that 
there  is  not  an  increase  in  the  listed  flame  spread 
classification  after  being  weathered  in  accordance 
with  ASTM  D2898  listed  in  Appendix  A. 
Fireretardant-treated  wood  subjected  to  high- 
humidity  conditions  shall  be  identified  to  indicate 
that  the  treated  wood  has  a  moisture  content  of  not 
over  28%  when  tested  at  92%  relative  humidity  in 
accordance  with  ASTM  D3201  listed  in 
Appendix  A. 


392 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


WOOD 


780  CMR  2311.0  NATURALLY  DURABLE 
AND  PRESERVATIVE-TREATED  WOOD 

2311.1  Required:  Where  protection  of  wood 
members  is  required  because  of  exposure  to  soil  or 
weather,  protection  shall  be  provided  by  using 
naturally  durable  or  preservative-treated  wood  as 
required  by  780  CMR  2311.0. 

2311.2  Naturally  durable  wood:  The  term 
"naturally  durable  wood"  refers  to  the  heartwood  of 
the  following  species  with  the  exception  that  an 
occasional  piece  with  corner  sapwood  is  permitted  if 
90%  or  more  of  the  width  of  each  side  on  which  it 
occurs  is  heartwood 

Decay  resistant:      Redwood,  cedar,  black  locust 

and  black  walnut. 
Termite  resistant:  Redwood    and    Eastern    red 

cedar 

2311.3  Preservative-treated  wood:  The  term 
"preservative-treated  wood"  refers  to  wood 
(including  plywood)  pressure  treated  with 
preservatives,  that  conforms  to  retention,  penetration 
and  other  requirements  applicable  to  the  species, 
product,  treatment  and  conditions  of  use  in  AWPA 
C  1,  C2  and  C9  listed  in  Appendix  A.  Preservatives 
shall  conform  to  AWPA  P1/P13,  P2,  P5,  P8  and  P9 
listed  in  Appendix  A  Lumber  and  plywood  in  wood 
foundation  systems  shall  conform  to  780  CMR 
1808.3. 

2311.3.1  Identification  All  piles,  poles,  lumber 
and  plywood  which  are  required  to  be 
preservative-treated  shall  bear  the  quality  mark  of 
an  approved  agency  that  maintains  continuing 
supervision,  testing  and  inspection  over  the 
quality  of  the  product.  Quality-control  inspection 
agencies  for  preservative-treated  wood  shall  be 
certified  as  to  competency  and  performance  by  an 
approved  organization.  Said  mark  shall  include 
the  following  information  in  a  legible  format: 
identification  of  the  inspection  agency;  the 
standard  to  which  the  product  is  treated;  the 
identification  of  the  treating  plant;  and  the 
purpose  for  which  the  product  has  been  treated. 
The  mark  shall  be  permanently  affixed  to  each 
piece  unless  specifically  waived  by  the  code 
official. 

2311.3.2  Moisture  content:  Where  wood  that  is 
pressure  treated  with  a  water-borne  preservative 
is  used  in  enclosed  locations  where  drying  in 
service  cannot  readily  occur,  such  wood  shall  be 
at  a  moisture  content  of  19%  or  less  before  being 
covered  with  insulation,  interior  wall  finish,  floor 
covering  or  other  material. 

2311.3.3  Fasteners:  Fasteners  for  preservative- 
treated  wood  shall  be  of  hot-dipped,  zinc-coated, 
galvanized  stainless  steel,  silicon  bronze,  copper 
or  other  corrosion-resistant  materials.    Fasteners 


for  wood  foundations  shall  be  as  required  in 
AFPA  TR7  listed  in  Appendix  A. 

2311.4  Wood  used  above  ground:  Wood  installed 
above  ground  in  the  locations  specified  in  780  CMR 
2311.4.1  through  231 1.4.6  shall  be  naturally  durable 
wood  or  preservative-treated  wood  that  uses  water- 
borne  preservatives,  and  shall  be  treated  in 
accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  above-ground  use. 

2311.4.1  Joists  and  girders.  Where  wood  joists 
or  the  bottom  of  a  wood  structural  floor  without 
joists  are  closer  than  18  inches  (457  mm),  or 
wood  girders  are  closer  than  12  inches  (305  mm), 
to  the  exposed  ground  in  crawl  spaces  or  unex- 
cavated  areas  located  within  the  perimeter  of  the 
building  foundation,  the  floor  assembly  (including 
posts,  girders,  joists  and  subfloor)  shall  be  of 
approved  naturally  durable  or  preservative-treated 
wood. 

2311.4.2  Framing:  All  wood  framing  members, 
including  wood  sheathing,  which  rest  on  exterior 
foundation  walls  and  are  less  than  eight  inches 
(203  mm)  from  exposed  earth  shall  be  of 
approved  naturally  durable  or  preservative-treated 
wood. 

2311.4.3  Sleepers  and  sills:  Sleepers  and  sills  on 
a  concrete  or  masonry  slab  which  is  in  direct 
contact  with  earth  shall  be  of  approved  naturally 
durable  or  preservative-treated  wood. 

2311.4.4  Girder  ends:  The  ends  of  wood  girders 
entering  exterior  masonry  or  concrete  walls  shall 
be  provided  with  a  Vi-inch  (13  mm)  air  space  on 
top,  sides  and  end,  unless  approved  naturally 
durable  or  preservative-treated  wood  is  used. 

2311.4.5  Clearance:  Clearance  between  wood 
siding  and  earth  on  the  exterior  of  a  building  shall 
not  be  less  than  six  inches  (152  mm)  except  where 
siding,  sheathing  and  wall  framing  are  of 
approved  preservative-treated  wood. 

2311.4.6  Posts  or  columns:  Posts  or  columns 
supporting  permanent  structures  and  supported  by 
a  concrete  or  masonry  slab  or  footing  which  is  in 
direct  contact  with  the  earth  shall  be  of  approved 
naturally  durable  or  preservative-treated  wood 

Exceptions: 

1.  Posts  or  columns  which  are  either  exposed 
to  the  weather  or  located  in  basements  or 
cellars,  supported  by  concrete  piers  or  metal 
pedestals  projecting  at  least  one  inch  (25  mm) 
above  the  slab  or  deck  and  six  inches  (152  mm) 
above  exposed  earth,  and  are  separated 
therefrom  by  an  impervious  moisture  barrier. 

2.  Posts  or  columns  in  enclosed  crawl  spaces 
or  unexcavated  areas  located  within  the 
periphery  of  the  building,  supported  by  a 
concrete  pier  or  metal  pedestal  at  a  height 
greater    than   eight   inches   (203    mm)   from 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


393 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


exposed  ground,  and  are  separated  therefrom 
by  an  impervious  moisture  barrier. 

2311.5  Wood  in  contact  with  the  ground:  All 

wood  in  contact  with  the  ground  (exposed  earth) 
which  supports  permanent  structures  that  are 
intended  for  human  occupancy,  shall  be  of  approved 
naturally  durable  or  preservative-treated  wood  using 
water-borne  preservatives  and  shall  be  treated  in 
accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  ground  contact,  where  used  in  the 
locations  specified  in  7S0  CMR  2311.5.1  and 
2311.5.2. 

Exception:  Untreated  wood  is  permitted  where 
such  wood  is  entirely  below  the  ground  water 
level  or  where  continuously  submerged  in  fresh 
water. 

2311.5.1  Posts  or  columns:  Sawn  posts  and 
columns  supporting  permanent  structures  that  are 
intended  for  human  occupancy  and  which  are 
embedded  in  concrete  in  direct  contact  with  the 
earth  or  embedded  in  concrete  exposed  to  the 
weather,  or  in  direct  contact  with  the  earth,  shall 
be  of  approved  preservative-treated  wood. 

2311.5.2  Wood  structural  members:  Wood 
structural  members  that  support  moisture- 
permeable  floors  or  roofs  which  are  exposed  to 
the  weather  -  such  as  concrete  or  masonry  slabs  - 
shall  be  of  approved  naturally  durable  or 
preservative-treated  wood  unless  separated  from 
such  floors  or  roofs  by  an  impervious  moisture 
barrier. 

2311.6  Geographical  areas:  In  geographical  areas 
where  experience  has  demonstrated  a  specific  need, 
approved  naturally  durable  or  preservative-treated 
wood  shall  be  utilized  for  those  portions  of  wood 
members  which  form  the  structural  supports  of 
buildings,  balconies,  porches  or  similar  permanent 
building  appurtenances  where  such  members  are 
exposed  to  the  weather  without  adequate  protection 
from  a  roof,  eave,  overhang  or  other  covering  to 
prevent  moisture  or  water  accumulation  on  the 
surface  or  at  joints  between  members.  Depending 
on  local  experience,  such  members  include,  but  are 
not  limited  to,  the  following: 

1.  Horizontal  members  such  as  girders,  joists  and 
decking; 

2.  Vertical  members  such  as  posts,  poles  and 
columns;  or 

3.  Both  horizontal  and  vertical  members. 

2311.7  Wood  used  in  retaining  walls:  Wood 
installed  in  retaining  or  crib  walls  shall  be  of 
approved  preservative-treated  wood  treated  in 
accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  ground  contact,  except  as  indicated 
in  780  CMR  23  11.7.1  through  23  1  1.7.3. 


2311.7.1  Untreated  wood:  Where  the  wall  is  not 
more  than  two  feet  (610  mm)  in  height  and  is 
separated  from  the  lot  line  or  a  permanent 
building  by  a  minimum  distance  equal  to  the 
height  of  the  wall,  the  wall  is  permitted  to  be  of 
untreated  wood. 

2311.7.2  Naturally  durable  wood  on  the  lot 
line:  Where  a  retaining  wall  or  a  crib  wall  is  not 
more  than  two  feet  (610  mm)  in  height  and  is 
located  on  the  lot  line,  approved  naturally  durable 
wood  is  permitted. 

2311.7.3  Naturally  durable  wood  separated: 

Where  a  retaining  wall  or  a  crib  wall  is  not  more 
than  four  feet  (1219  mm)  in  height  and  is 
separated  from  the  lot  line  or  a  permanent 
building  by  a  minimum  distance  equal  to  the 
height  of  the  wall,  approved  naturally  durable 
wood  is  permitted. 

780  CMR  2312.0  JOIST  HANGERS 

2312.1  Test  standard:  The  vertical  loadbearing 
capacity,  torsional  moment  capacity,  and  deflection 
characteristics  of  joist  hangers  shall  be  determined 
in  accordance  with  ASTM  D1761  listed  in 
Appendix  A,  using  lumber  having  a  specific  gravity 
of  0.49  or  greater  but  not  greater  than  0.55  as 
determined  in  accordance  with  AFPA  NDS  listed  in 
Appendix  A  for  the  joist  and  headers. 

2312.2  Vertical  load  capacity:  The  vertical  load 
capacity  for  the  joist  hanger  shall  be  determined  by 
testing  three  joist  hanger  assemblies  as  specified  in 
ASTM  D 1 76 1  listed  in  Appendix  A.  If  the  ultimate 
vertical  load  for  any  one  of  the  tests  varies  more 
than  20%  from  the  average  ultimate  vertical  load,  at 
least  three  additional  tests  shall  be  conducted.  The 
allowable  vertical  load  for  a  normal  duration  of 
loading  of  the  joist  hanger  shall  be  the  lowest  value 
determined  from  the  following: 

1 .  The  lowest  ultimate  vertical  load  from  any 
test  divided  by  2.5  (where  three  tests  are 
conducted  and  each  ultimate  vertical  load  does 
not  vary  more  than  20%  from  the  average  ultimate 
vertical  load). 

2.  The  average  ultimate  vertical  load  for  all  tests 
divided  by  six  (where  six  tests  are  conducted). 

3.  The  vertical  load  at  which  the  vertical 
movement  of  the  joist  with  respect  to  the  header 
is  0. 125  inch  (3  mm)  in  any  test. 

4.  The  allowable  design  load  for  nails  or  other 
fasteners  utilized  to  secure  the  joist  hanger  to  the 
wood  members. 

5.  The  allowable  design  load  for  the  wood 
members  forming  the  connection. 

2312.3  Torsional  moment  capacity:  The  torsional 
moment  capacity  for  the  joist  hanger  shall  be 
determined  by  testing  at  least  three  joist  hanger 
assemblies  as  specified  in  ASTM  D1761  listed  in 
Appendix  A     The  allowable  torsional  moment  for 


394 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


normal  duration  of  loading  of  the  joist  hanger  shall 
be  the  average  torsional  moment  at  which  the  lateral 
movement  of  the  top  or  bottom  of  the  joist  with 
respect  to  the  original  position  of  the  joist  is  0.125 
inch. 

2312.4  Design  value  modifications:  Allowable 
design  values  for  joist  hangers  which  are  determined 
by  failure  of  the  metal-to-wood  connection  shall  be 
permitted  to  be  modified  by  the  appropriate  duration 
of  loading  factors  as  specified  in  AFPA  NDS  listed 
in  Appendix  A.  Allowable  design  values  determined 
by  failure  of  the  metal  joist  hanger  shall  not  be 
modified  by  duration  of  loading  factors. 

780  CMR  2313.0  PREFABRICATED 
COMPONENTS 

2313.1    Structural    glued-laminated    members: 

Buildings  and  structures  designed  and  erected  of 
glued-laminated  structural  members  or  of  composite 
members  of  dimension  lumber  and  wood  structural 
panels  shall  comply  with  780  CMR  2313.0. 

2313.1.1  Exposed  structural  glued-laminated 
timber:  Those  portions  of  glued-laminated 
timbers  which  form  the  structural  supports  of  a 
building  or  other  structure  and  are  exposed  to 
weather  and  not  properly  protected  by  a  roof,  eave 
overhang  or  similar  covering,  shall  be  treated  in 
accordance  with  AITC  109  listed  in  Appendix  A 
or  shall  be  manufactured  from  approved  naturally 
durable  woods. 

2313.1.2  Glued-laminated  members:  Design  and 
fabrication  of  built-up  beam  and  column  sections, 
which  consist  of  one  or  more  webs  with  glued- 
lumber  flanges  and  stiffeners,  shall  be  based  upon 
an  approved  method  which  takes  into 
consideration  the  conditipns  of  use  Glued- 
laminated  elements  shall  be  subject  to  a  quality 
control  program  administered  by  an  approved 
agency  and  shall  bear  a  label  in  accordance  with 
780  CMR  1704.3.  Such  label  shall  contain  the 
information  required  by  780  CMR  1704.3.3. 

2313.1.3  Gluing  surfaces:  In  glued-lumber 
constructions,  the  surfaces  to  be  glued  shall  be 
worked  to  a  smooth,  flat  surface  without  sanding 
and  shall  be  free  from  wax,  grease  or  oil  to  insure 
a  complete  glue  bond  over  the  entire  contact. 
Factory-sanded  wood  structural  panels  shall  be 
permitted. 

2313.2  Sandwich  panels:  Design  and  fabrication 
of  sandwich  panels  or  other  integrated  assemblies 


WOOD 

which  are  fabricated  of  dimension  lumber  with 
wood  stress  coverings  glued  thereto,  or  which 
consist  of  structural  units  of  metal-covered  or 
molded  wood  structural  panels  or  other  approved 
plastics  formed  and  molded  into  prefabricated 
loadbearing  members,  shall  be  based  upon  an 
approved  method  which  takes  into  consideration 
the  conditions  of  installation  or  meets  the  test 
requirements  of  780  CMR  1704.0,  1709.0  and 
1710.0.  Sandwich  panels  shall  be  subject  to  a 
quality  control  program  administered  by  an 
approved  agency  and  shall  bear  a  label  in 
accordance  with  780  CMR  1704.3.  Such  label 
shall  contain  the  information  required  by 
780  CMR  1704.3.3 

2313.2.1  Splices:  Splices  and  connections 
between  panels  shall  be  weather  tight  and  shall 
be  of  sufficient  strength  to  resist  two  and  one- 
half  times  the  design  live  load  to  which  such 
splices  will  be  subjected  in  normal  installation. 
The  fastening  of  coverings  to  structural  studs, 
ribs  or  joists  shall  provide  a  rigidity  equivalent 
to  approved  gluing.  Nailing  shall  not  be 
acceptable  for  that  purpose. 

2313.3  Prefabricated  trusses:  Prefabricated  trusses 
shall  be  designed  to  resist  all  superimposed  design 
loads. 

2313.3.1  Roof  trusses:  Metal-plate-connected 
roof  trusses  shall  be  designed  in  accordance  with 
TPI  Design  Specifications  for  Metal  Plate 
Connected  Wood  Trusses  and  AFPA  NDS  listed 
in  Appendix  A,  and  shall  be  braced  to  prevent 
rotation  and  provide  lateral  stability. 

2313.3.2  Floor  trusses:  Metal-plate-connected 
floor  trusses  shall  be  designed  in  accordance  with 
TPI  Design  Specif  cations  for  Metal  Plate 
Connected  Parallel  Chord  Wood  Trusses  and 
AFPA  NDS  listed  in  Appendix  A. 

2313.4  Special  inspection:  The  fabrication  process 
for  prefabricated  wood  components  shall  be  subject 
to  special  inspection  as  required  by  780  CMR 
1705.4. 

2313.5  Prefabricated  wood  I-joists:  Structural 
capacities  and  design  provisions  for  prefabricated 
wood  I  joists  shall  be  established  and  monitored  in 
accordance  with  ASTM  D5055  listed  in 
Appendix  A 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


395 


780  CMR:    STATE  BOARD  OF  BUTLDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


396  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  24 


GLASS  AND  GLAZING 


780  CMR  2401.0  GENERAL 
2401.1  Scope:  The  provisions  of  780  CMR  24  shall 
govern  the  materials,  design,  construction  and 
quality  of  glass  and  glazing  in  vertical  and  sloped 
applications.  For  the  definition  of  approved  light- 
transmitting  plastic,  see  780  CMR  2604. 1 .  Safety 
glazing  materials  shall  conform  to  the 
requirements  of  M.G.L.  c  143,  §§  3T,  3U,  and  3  V, 
as  amended  and  CPSC  16  CFR;  1201,  as 
applicable. 

780  CMR  2402.0  GENERAL 
REQUIREMENTS  FOR  GLASS 

2402.1  Marking:  Each  lite  shall  bear  the 
manufacturer's  mark  designating  the  type  and 
thickness  of  glass.  The  mark  shall  not  be  omitted 
unless  approved  and  an  affidavit  is  furnished  by  the 
glazing  contractor  certifying  that  each  lite  is  glazed 
in  accordance  with  approved  plans  and 
specifications  in  accordance  with  the  provisions  of 
780  CMR  24.  Safety  glazing  shall  be  marked  in 
accordance  with  780  CMR  2405.1.1  and  shall 
conform  to  the  requirements  of  M.G.L.  c  143, 
§§3T,  3U,  and3V,  as  amended.  The  mark  shall  not 
be  omitted  from  tempered  glass.  Each  unit  of 
tempered  glass  shall  be  permanently  identified  by 
the  manufacturer's  mark.  The  identifying  mark  shall 
be  etched  or  ceramic  fired  on  the  glass  and  shall  be 
visible  when  the  unit  is  glazed.  Tempered  spandrel 
glass  is  exempted  from  permanent  marking,  but  shall 
be  provided  with  a  removable  paper  marking  by  the 
manufacturer 

2402.2  Glass  supports:  Where  one  or  more  sides  of 
any  lite  of  glass  is  not  firmly  supported,  or  is 
subjected  to  unusual  load  conditions,  detailed 
construction  documents,  detailed  shop  drawings  and 
analysis  or  test  data  assuring  safe  performance  for 
the  specific  installation  shall  be  prepared  by  a 
registered  design  professional  and  approved. 
Analysis  shall  be  based  on  the  wind  loads  required 
by  780  CMR  1611.6.  The  elevation  of  the  glazed 
openings  shall  be  computed  by  adding  the  distances 
from  grade  to  the  head  and  sill,  respectively,  and 
dividing  the  sum  by  two. 

2402.3  Interior  glazed  areas:  Where  interior 
glazing  is  installed  adjacent  to  a  walking  surface,  the 
differential  deflection  of  two  adjacent  unsupported 
edges  shall  not  be  greater  than  the  thickness  of  the 
panels  when  a  force  of  50  pounds  per  linear  foot 
(730  N/m)  is  applied  horizontally  to  one  panel  at  any 
point  up  to  42  inches  (1067  mm)  above  the  walking 
surface. 


2402.4     Glass     dimensional     tolerance:     Glass 

thickness  tolerances  shall  comply  with  those 
established  in  Table  2402.4.  Where  the  thickness  is 
to  be  controlled,  nominal  values  are  stated  subject  to 
the  tolerances  shown  in  Table  2402.4. 

Table  2402.4 
MINIMUM  GLASS  THICKNESS 


Nominal  thickness 
(inches) 

Plate  glass 

minimum  thickness 

(inches) 

Sheet  glass 

minimum  thickness 

(inches) 

Single  strength  (SS) 

— 

0.085 

Double  strength  (DS) 

— 

0.115 

Ve 

0.094 

— 

3/16 

0.1  S6 

0.182 

13/64 

0.172 

— 

7/32 

— 

0.205 

Vt 

0.218 

0.236 

5/16 

0.281 
0.343 

0.357 

% 

0.468 

0.478 

0.562 
0.689 

— 

% 

7/a 

0.750 
0.875 

— 

1 

1% 

1.125 

— 

Note  a.  One  inch  =  25.4  mm. 

2402.5  Louvered  windows  or  jalousies:  Regular 
float,  wired  and  patterned  glass  in  louvered  windows 
and  jalousies  shall  not  be  thinner  than  nominal  3/16 
inch  and  not  longer  than  48  inches  (1219  mm). 
Where  other  glass  types  are  used,  design  shall  be 
submitted  to  the  code  official  for  approval.  Exposed 
glass  edges  shall  be  smooth.  Wired  glass  with  wire 
exposed  on  longitudinal  edges  shall  not  be  used  in 
jalousies  or  louvered  windows. 

780  CMR  2403.0  WIND,  SNOW  AND  DEAD 
LOADS  ON  GLASS 

2403.1  Vertical  glass:  All  glass  within  15  degrees 
(0.26  rad)  of  vertical  in  windows,  curtain  and 
window  walls,  doors  and  other  exterior  applications 
shall  be  designed  to  resist  the  wind  loads  in 
780  CMR  1611.6  for  components  and  cladding. 
Maximum  allowable  sizes  shall  be  based  on  Figure 
2403.1.  The  equivalent  load  for  use  in  the  figure 
shall  be  determined  by  dividing  the  design  wind  load 
by  the  applicable  factor  from  Table  2403  1  Figure 
2403  1  is  for  rectangular  glass  firmly  supported  on 
all  four  edges. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


397 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2403.2  Sloped  glass:  All  glass  sloped  more  than  15 
degrees  (0.26  rad)  from  vertical  in  skylights, 
sunspaces,  sloped  roofs  and  other  exterior 
applications  shall  be  designed  to  resist  the 
combination  of  wind  loads  in  780  CMR  161 1.6  for 
components  and  cladding,  the  snow  loads  in 
780  CMR  1610.0,  and  the  glass  dead  load. 
Maximum  allowable  sizes  shall  be  based  on  Figure 
2403.1.  Figure  2403.1  is  for  rectangular  glass  firmly 
supported  on  all  four  edges. 

The  combined  load  shall  be  calculated  as  follows. 
The  largest  of  1,  2  or  3  shall  be  used: 

1 .  Negative  wind  load;  -  F  x  dead  load 

2.  Positive  wind  load;  +  Fx  (dead  load  +  V:  wind 
load) 

3.  Fx  (snow  load  4  dead  load)  +  'A  positive  wind 
load 

where: 

F=  2.0  where  any  pane  or  ply  is  regular  glass. 
F  =  1.5  where  any  pane  or  ply  is  heat- 
strengthened  glass  and  the  remainder  are  fully 
tempered  glass. 

F    =1.2  where  all  panes  and  plies  are  fully 
tempered  glass. 
The  glass  dead  load  is  equal  to  the  cosine  of  the 

slope  from  horizontal  x  the  total  glass  thickness  in 

inches  x  13. 
The  equivalent  load  for  use  in  Figure  2403. 1  shall 

be  determined  by  dividing  the  combined  load  by  the 

applicable  factor  from  Table  2403.2. 

Table  2403.1 
FACTORS  FOR  VERTICAL  GLASS 


Glass  type 


Factor 

for  use  with  figure 

2403.1 


Single  Glass 
Regualr  (annealed) 
Heat  strengthened 
Fully  tempered 
Wired 
Pattemedd 
Sandblasted' 
Laminated,  regular  piles 
Laminated,  heat  strengthened  plies 
Laminated,  futry  tempered  plies  ' 

Insulating  Glass 
Regular,  (annealed) 
Heat  strengthened 
Fully  tempered 
Laminated,  regular  piles 
Laminated,  heat  strengthened  plies3* b 
Laminated,  fully  tempered  plies3 


1.0 

2.0 

4.0 

0.5 

1.0 

0.5 

0.75 

1.5 

3.0 

1.8 

3.6 

7.2 
1.4 
2.7 


Note  a.  For  laminated  glass,  use  the  line  in  Figure 
2403. 1  for  total  glass  thickness  (after  adjusting  wind  load 
by  the  factor  in  Table  2403. 1). 

Note  b.  For  laminated  glass,  values  are  based  on  two 
panes  of  identical  thickness  and  type. 

Note  c.  For  insulated  glass,  values  are  based  on  two 
panes  of  identical  thickness  and  type.  Utilize  thickness 
for  one  pane.  For  example,  tha  maximum  allowable  area 
for  an  insulating  glass  unit  consisting  of  two  plies  of  fully 
tempered  Vi-inch  glass  is  determined  using  the  line  for 
Vi-inch  glass. 


Note  d.  Values  for  patterned  glass  are  based  on  the 
thinnest  part  of  the  pattern.  Interpolation  between  lines 
in  the  figure  is  permitted. 

Note  e.  Value  for  sandblasting  glass  is  minimum  and 
depends  on  severity  and  depth  of  sandblast. 

Figure  2403.1 

MAXIMUM  ALLOWABLE  AREA  FOR 

VERTICAL  AND  SLOPED  GLASS 


60       80     100    150    200 


Equivalent  Load  Determined  from  780  CMR  2403. 1  and 
Table  2403.0  or  780  CMR  2403.2  and  2403.2  on  psf 


Table  2403.2 
FACTORS  FOR  SLOPED  GLASS 


Glass  type 


Factor 

for  use  with  figure 

2403.1 


Single  Glass 
Regualr  (annealed) 
Heat  strengthened 
fully  tempered 
Wired 

Laminated,  regular  piles 
Laminated,  heat  strengthened  plies  ' 
Laminated,  tempered  plies 

Insulating  Glass 
Regular,  (annealed) 
Heat  strengthened 
Fully  tempered 
Laminated,  regular  piles  ' 
Laminated,  heat  strengthened  plies  * 
Laminated,  fully  tempered  plies3' 


0.72 

1.7 

3.6 

0.36 

0.54 

1.3 

2.7 

1.3 
3.1 
6.6 
1.0 
2.3 


Note  a.  For  laminated  glass,  use  the  line  in  Figure 
2403. 1  for  total  glass  thickness  (after  adjusting  wind 
load  by  the  factor  in  Table  2403.2). 

Note  b.  For  laminated  glass,  values  are  based  on 
two  panes  of  identical  thickness  and  type. 

Note  c.  For  insulated  glass,  values  are  based  on 
two  panes  of  identical  thickness  and  type.  Utilize 
thickness  for  one  pane.  For  example,  tha  maximum 
allowable  area  for  an  insulating  glass  unit  consisting 
of  two  plies  of  fully  tempered  %-inch  glass  is 
determined  using  the  line  for  Vi-inch  glass. 


398 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

GLASS  AND  GLAZING 


780  CMR  2404.0  SLOPED  GLAZING  AND 
SKYLIGHTS 

2404.1  Sloped  glazing:  Any  installation  of  glass  or 
other  transparent,  translucent  or  opaque  glazing 
material  which  is  installed  at  a  slope  of  15  degrees 
(0.26  rad)  or  more  from  the  vertical  plane 
— including  skylights,  roofs  and  sloped  walls — shall 
comply  with  780  CMR2404.0. 

2404.2  Allowable  glazing  materials:  Sloped 
glazing  shall  be  any  of  the  following  materials, 
subject  to  the  limitations  specified  in  780  CMR 

2404.3  and  the  exceptions  specified  in  780  CMR 
2404.4: 

1.  For  monolithic  glazing  systems,  the  glazing 
material  of  the  single  light  or  layer  shall  be 
laminated  glass  with  a  minimum  30-mil  (762  (am) 
polyvinyl  butyral  interlayer,  wired  glass, 
approved  plastic  materials,  heat-strengthened 
glass  or  fully  tempered  glass. 

2.  For  multiple-layer  glazing  systems,  each  light 
or   layer   shall   consist   of  any   of  the   glazing 
materials  specified  in  780  CMR  2404.2  item  1. 
For  additional  requirements  for  plastic  skylights, 

see  780  CMR  2608.0.  Glass-block  construction  shall 
conform  to  the  requirements  of  780  CMR  21 15.0. 

2404.3  Limitations:  Where  used  in  monolithic 
glazing  systems,  heat-strengthened  glass  and  fully 
tempered  glass  shall  have  screens  installed  below  the 
glazing  material,  subject  to  the  exceptions  in 
780  CMR  2404.4,  to  protect  building  occupants 
from  falling  glass  should  breakage  occur.  The 
screens  shall  be  capable  of  supporting  the  weight  of 
the  glass  and  shall  be  substantially  supported  below 
and  installed  within  four  inches  (  102  mm)  of  the 
glass.  The  screens  shall  be  constructed  of  a 
noncombustible  material  not  thinner  than  No.  12 
B&S  Gage  (0.0808  inch)  with  a  mesh  not  larger  than 
one  inch  by  one  inch  (25  mm  by  25  mm).  In  a 
corrosive  atmosphere,  structurally  equivalent 
noncorrosive  atmosphere,  structurally  equivalent 
noncorrosive  screening  materials  shall  be  used. 
Where  used  in  multiple-layer  glazing  systems  as  the 
bottom  glass  layer  over  the  walking  surface,  heat- 
strengthened  glass,  fully  tempered  glass  and  wired 
glass  shall  be  equipped  with  screening  that  conforms 
to  the  requirements  specified  for  monolithic  glazing 
systems. 

2404.4  Exceptions:  In  monolithic  and  multiple-layer 
sloped  glazing  systems,  the  following  exceptions 
apply: 

1.  Fully  tempered  glass  installed  without 
protective  screens  where  glazed  between 
intervening  floors  at  a  slope  of  30  degrees  (0.52 
rad)  or  less  from  the  vertical  plane  shall  have  the 
highest  point  of  the  glass  ten  feet  (3048  mm)  or 
less  above  the  walking  surface. 

2.  Screens  are  not  required  below  any  glazing 
material,    including   annealed   glass,    where  the 


walking  surface  below  the  glazing  material  is 
permanently  protected  from  the  risk  of  falling 
glass  or  tho  area  below  the  glazing  material  is  not 
a  walking  surface. 

3.  Any  glazing  material,  including  annealed 
glass,  is  permitted  to  be  installed  without  screens 
in  the  sloped  glazing  systems  of  commercial  or 
detached  greenhouses  used  exclusively  for 
growing  plants  and  not  open  to  the  public, 
provided  that  the  height  of  the  greenhouse  at  the 
ridge  does  not  exceed  20  feet  (6096  mm)  above 
grade.  Greenhouse  frames  shall  be 
noncombustible  if  the  height  of  the  sloped  glazing 
exceeds  20  feet  (6096  mm)  above  grade. 

4.  Screens  shall  not  be  required  within  dwelling 
units  of  occupancies  in  Use  Groups  R-2  and  R-3 
where  fully  tempered  glass  or  laminated  glass 
with  a  15  mil  polyvinyl  butyral  interlayer  is  used 
as  single  glazing  or  as  both  panes  in  an  insulating 
glass  unit,  and  all  of  the  following  conditions  are 
met: 

4.1.  Each  pane  of  glass  is  16  square  feet  (1.5 
m2)  or  less  in  area; 

4.2.  The  highest  point  of  the  glass  is  12  feet 
(3658  mm)  or  less  above  any  walking  surface 
or  other  area  having  access  thereto;  and 

4.3.  The  glass  thickness  is  3/16  inch  (5  mm) 
or  less. 

2404.5  Framing:  In  Types  I  and  2  construction,  all 
sloped  glazing  and  skylight  frames  shall  be 
constructed  of  noncombustible  materials.  In 
buildings  where  acid  fumes  deleterious  to  metal  are 
incidental  to  the  occupancy  of  the  buildings, 
approved  pressure-treated  woods  or  other  approved 
noncorrosive  materials  shall  be  permitted  for  sash 
and  frames.  All  sloped  glazing  and  skylights  shall  be 
designed  to  meet  all  structural  requirements  for  roofs 
specified  in  780  CMR  16.  All  skylights  set  at  an 
angle  of  less  than  45  degrees  (0.79  rad)  from  the 
horizontal  plane  shall  be  mounted  at  least  four 
inches  (102  mm)  above  the  plane  of  the  roof  on  a 
curb  construction  as  required  for  the  frame. 
Skylights  shall  not  be  installed  in  the  plane  of  the 
roof  where  the  roof  pitch  is  less  than  45  degrees 
(0.79  rad)  from  the  horizontal. 

Exception:  Curbs  for  skylights  are  not  required 
on  roofs  with  a  minimum  slope  of  three  units 
vertical  in  12  units  horizontal  (3:12)  in 
occupancies  in  Use  Group  R-3. 

780  CMR  2405.0  SAFETY  GLAZING 
2405.1  Human  impact  loads:  Individual  glazed 
areas,  including  glass  mirrors,  in  hazardous  locations 
such  as  those  indicated  in  780  CMR  2405.2  shall 
pass  the  test  requirements  of  CPSC  16  CFR;  1201 
and  shall  conform  to  the  requirements  of  M.G.L. 
c.  143,  §§  3T,  3U  and  3  V,  as  applicable,  listed  in 
Appendix  A.  The  requirements  of  780  CMR  2405.1 
and  780  CMR  2405  2  and  2407.0  shall  apply  equally 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


399 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


to  replacement  glass  and  new  glass  installation. 
Additional  requirements  as  specified  in  780  CMR 
2407.2  are  to  be  satisfied  for  glass  used  in  locations 
where  the  hazard  is  of  a  continuous  nature,  such  as 
glass  enclosures  for  sporting  activities  as  identified 
in  780  CMR  2407.1. 

Exceptions: 

1.  Polished  wired  glass  used  in  required  fire 
resistance  rated  assemblies  or  polished  wire  glass 
used  in  hazardous  locations  such  as  those 
indicated  in  780  CMR  2405.2,  items  6,  7,  8  and 

9  shall  comply  with  ANSI  Z97.1  listed  in 
Appendix  A. 

2.  Plastic  glazing  shall  meet  the  weathering 
requirements  of  ANSI  Z97. 1  listed  in 
Appendix  A. 

3.  Glass-block  walls  shall  comply  with  780  CMR 
2115.0. 

2405.1.1  Marking:  Each  light  of  safety  glazing 
material  installed  in  hazardous  locations  as 
defined  in  780  CMR  2405.2  shall  bear  a 
permanent  identifying  mark  issued  by  an 
approved  agency  which  specifies  the  marking 
agency,  whether  manufacturer  or  installer,  and 
the  test  standard. 
Exceptions 

1.  Polished  wire  glass  is  exempt  from  a 
permanent  identifying  mark  provided  that 
the  distributor  or  the  installer  provides  an 
affidavit  certifying  that  the  polished  wire 
glass  complies  with  ANSI  Z9  7. 1  listed  in 
Appendix  A. 

2.  Laminated  glass  is  exempt  from  a 
permanent  identifying  mark  provided  that 
the  distributor  or  installer  provides  an 
affidavit  certifying  that  the  laminated  glass 
complies  with  CPSC 16  CFR 1201,  listed  in 
Appendix  A. 

2405.2  Specific  hazardous  locations:  The  following 
shall  be  considered  specific  hazardous  locations  for 
the  purposes  of  glazing: 

1 .  Glazing  in  ingress  and  means  of  egress  doors 
except  jalousies  (see  780  CMR  2402.5). 

2.  Glazing  in  fixed  and  sliding  panels  of  sliding 
(patio)  door  assemblies  and  panels  in  swinging 
doors. 

3.  Glazing  in  storm  doors. 

4.  Glazing  in  all  unframed  swinging  doors. 

5.  Glazing  in  doors  and  enclosures  for  hot  tubs, 
whirlpools,  saunas,  steam  rooms,  bathtubs  and 
showers.  Glazing  in  any  portion  of  a  building  wall 
enclosing  these  compartments  where  the  bottom 
exposed  edge  of  the  glazing  is  less  than  60  inches 
(1525  mm)  above  a  standing  surface. 

6.  Glazing  in  an  individual  fixed  or  operable 
panel  adjacent  to  a  door  where  the  nearest 
exposed  edge  of  the  glazing  is  within  a  24-inch 
(610  mm)  arc  of  either  vertical  edge  of  the  door  in 
a  closed  position  and  where  the  bottom  exposed 


edge  of  the  glazing  is  less  than  60  inches  (1525 
mm)  above  the  walking  surface. 

7.  Glazing  in  an  individual  fixed  or  operable 
panel,  other  than  in  those  locations  described  in 
preceding  items  5  and  6,  which  meets  all  of  the 
following  conditions: 

7.1.  Exposed  area  of  an  individual  pane 
greater  than  nine  square  feet  (0.84  m2); 

7.2.  Exposed  bottom  edge  less  than  18  inches 
(460  mm)  above  the  floor: 

7.3.  Exposed  top  edge  greater  than  36  inches 
(915  mm)  above  the  floor;  and 

7.4.  One  or  more  walking  surface(s)  within  36 
inches  (915  mm)  horizontally  of  the  plane  of 
the  glazing. 

8.  All  glazing  in  guards  and  railings  regardless  of 
area  or  height  above  a  walking  surface.  Included 
are  structural  baluster  panels  and  nonstructural  in- 
fill panels. 

9.  Glazing  in  walls  and  fences  enclosing  indoor 
and  outdoor  swimming  pools  where  the  bottom 
edge  of  the  glazing  on  the  pool  side  is  less  than  60 
inches  (1525  mm)  above  a  walking  surface  and 
within  36  inches  (914  mm)  horizontally  of  a 
walking  surface.  This  shall  apply  to  single  glazing 
and  all  panes  in  multiple  glazing. 

Exception:  The  following  products,  materials 
and  uses  shall  not  be  considered  specific 
hazardous  locations: 

1 .  Openings  in  doors  through  which  a  3-inch 
(76  mm)  sphere  is  unable  to  pass. 

2.  Assemblies  of  leaded  glass  or  faceted  glass 
and  items  of  carved  glass  used  for  decorative 
purposes  in  locations  described  in  780  CMR 
2405.2,  items  1,  6  or  7. 

3.  Glazing  materials  used  as  curved  glazed 
panels  in  revolving  doors. 

4.  Commercial  refrigerated  cabinet  glazed 
doors. 

5.  Glazing  as  described  in  780  CMR  2405.2, 
item  6,  where  there  is  an  intervening  wall  or 
some  other  permanent  barrier  that  will  prevent 
a  person  approaching  the  door  from 
accidentally  striking  the  glazing. 

6.  Glazing  as  described  in  780  CMR  2405.2, 
item  7,  where  a  protective  bar  is  installed  34 
inches  to  38  inches  (864  mm  to  965  mm)  above 
the  floor  on  the  side  of  the  glazing  having 
access  thereto.  The  bar  shall  be  capable  of 
withstanding  a  horizontal  load  of  50  pounds 
per  linear  foot  (730  N/m)  without  contacting 
the  glass  and  be  a  minimum  of  Wi  inches  (38 
mm)  in  height.  The  protective  bar  may  be  an 
applied  bar  or  an  integral  part  of  the  glazed 
framing  dividing  an  upper  lite  from  a  lower 
lite. 

7.  Outboard  panes  in  insulating  glass  units 
and  other  multiple-glazed  panels  as  described 
in  780  CMR  2405.2,  item  7,  where  the  bottom 
exposed  edge  of  the  glass  is  25  feet  (7620  mm) 
or  more  above  any  grade,  roof,  walking  surface 


400 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

GLASS  AND  GLAZING 


or  other  horizontal  or  sloped  (within  45 
degrees  of  horizontal)  surface  adjacent  to  the 
glass  exterior. 

8.  Louvered  windows  and  jalousies  complying 
with  the  requirements  of  780  CMR  2402.5. 

9.  Glazing  which  is  mounted  or  hung  on  a 
surface  that  provides  a  continuous  backing 
support. 

2405.3  Glass  in  fire-fighter  access  panels:  In  cases 
where  tempered  glass  is  required  in  fire-fighter 
access  panels,  both  panes  in  double  glazing  shall  be 
tempered  glass. 

780  CMR  2406.0  GLASS  IN  HANDRAILS  AND 
GUARDRARS 

2406.1  Materials:  Glass  used  as  structural 
balustrade  panels  in  railings  shall  be  constructed  of 
either  single  fully  tempered  glass,  laminated  fully 
tempered  glass  or  laminated  heat-strengthened  glass. 
Glazing  in  railing  in-fill  panels  shall  conform  to 
ANSI  Z97. 1  listed  in  Appendix  A  or  shall  be  of  an 
approved  safety  glazing  material  that  conforms  to 
the  provisions  of  780  CMR  2405.1.  For  all  glazing 
types,  the  minimum  nominal  thickness  shall  be  % 
inch.  Fully  tempered  glass  and  laminated  glass  shall 
comply  with  Category  II  of  CPSC  16  CFR  1201, 
listed  in  Appendix  A.  Wired  glass  shall  comply  with 
ANSI  Z97. 1  listed  in  Appendix  A. 

2406.1.1  Loads:  The  panels  and  their  support 
system  shall  be  designed  to  withstand  the  loads 
specified  in  780  CMR  1606.4.  A  safety  factor  of 
4  shall  be  used. 

2406.1.2  Support:  Each  handrail  or  guardrail 
section  shall  be  supported  by  a  minimum  of  three 
glass  balusters  or  shall  be  otherwise  supported  to 
remain  in  place  should  one  baluster  panel  fail. 
Glass  balusters  shall  not  be  installed  without  an 
attached  handrail  or  guardrail. 

2406.1.3  Parking  garages:  Glazing  materials 
shall  not  be  installed  in  railings  in  parking 
garages  except  for  pedestrian  areas  not  exposed 
to  impact  from  vehicles. 


780  CMR  2407.0  GLAZING  IN 
RACQUETBALL  AND  SQUASH  COURTS 

2407.1  Continuously  hazardous  locations:  The 

following  shall  be  considered  continuously 
hazardous  locations  for  the  purposes  of  glazing: 

1.  Glazing  in  squash  and  racquetball  courts 
which  forms  whole  or  partial  wall  sections. 

2.  Glazing  in  squash  and  racquetball  courts 
which  is  used  as  a  door  or  part  of  a  door. 

2407.2  Testing:  Test  methods  and  loads  for 
individually  glazed  areas  such  as  those  described  in 
780  CMR  2407.1  shall  conform  to  those  of  CPSC  16 
CFR;  1201,  listed  in  Appendix  A,  with  impacts 
being  applied  at  a  height  from  ground  level  of  59 
inches  (1499  mm)  to  an  actual  or  simulated  glass 
wall  installation  with  fixtures,  fittings  and  methods 
of  assembly  identical  to  those  used  in  practice. 

In  order  to  be  deemed  acceptable,  the  following 
conditions  shall  be  achieved  for  glass  walls: 

1 .  Any  glass  wall  in  a  squash  or  racquetball  court 
shall  remain  intact  following  a  test  impact. 

2.  The  deflection  of  such  walls  shall  not  be 
greater  than  VA  inches  (38  mm)  at  the  point  of 
impact. 

In  order  to  be  deemed  acceptable,  the  following 
conditions  shall  be  achieved  for  glass  doors: 

1.  Glass  doors  shall  remain  intact  following  a 
test  impact  at  the  prescribed  height  in  the  center 
of  the  door. 

2.  The  relative  deflection  between  the  edge  of  a 
glass  door  and  the  adjacent  wall  shall  not  exceed 
the  following  values  for  the  impact  test  bag-drop 
heights: 

2.1.  The  thickness  of  the  wall  plus  Vfe  inch  (3 
mm)  for  a  drop  height  of  24  inches  (610  mm). 

2.2.  The  thickness  of  the  wall  plus  V*  inch  (6 
mm)  for  a  drop  height  of  36  inches  (914  mm). 

2.3.  The  thickness  of  the  wall  plus  Vi  inch  (13 
mm)  for  a  drop  height  of  48  inches  (1219  mm). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


401 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


402  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  25 


GYPSUM  BOARD  AND  PLASTER 


780  CMR  2501.0  GENERAL 

2501.1  Scope:  The  provisions  of  780  CMR  25  shall 
govern  the  materials,  design,  construction  and 
quality  of  gypsum  and  plaster. 

780  CMR  2502.0  SHEAR  WALLS 
2502.1  General:  Wood  frame  shear  walls 
constructed  in  accordance  with  the  materials  and 
provisions  of  Table  2502.1  are  permitted  to  resist 
wind  and  seismic  forces.  Where  such  construction 
is  designed  to  resist  seismic  forces,  the  panel  size 


and  arrangement  provisions  of  780  CMR  2306.4.7 
shall  be  met  in  addition  to  780  CMR  2502.0. 

2502.1.1  Nailing:  All  studs,  top  and  bottom 
plates  and  blocking  shall  be  nailed  in 
accordance  with  Table  2502.1. 

2502.1.2  Limitations:  Shear  walls  shall  not  be 
used  to  resist  horizontal  loads  from  masonry  or 
concrete  walls. 


Table  2502.1 
SHEAR  CAPACITY  FOR  SHEAR  WALLS  OF  LATH  AND  PLASTER, 
GYPSUM  SHEATHING  BOARD,  AND  GYPSUM  WALLBOARD  WOOD  FRAME  ASSEMBLIES 


Type  of  material 

Thickness 

of  material 

(inch) 

Wall 
construction 

Nail  spacing 
maximum 
(inches) 

Allowable 

shear 
pounds  per 
foot  of  wall 

Fastener  size 

Woven  or  welded  wire  lath  and 
portland  cement  plaster 

Vs 

Unblocked 

6 

180 

No.  1 1  gage,  1  Vz  inches 
ling,  7/16-inch  head,  or 
No.  16  gage  staples 
having  Vs-inch-long  legs 

Gypsum  lath,  plain  or 
perforated 

%  lath  and 
Vi  plaster 

Unblocked 

5 

100 

No.  1 3  gage,  1  Vs  inches 
long,  1 9/64-  inch  head, 
plasterboard  blued  nail 

Gypsum 

2  feet  x  8  feet 

Vz 

Unblocked 

4 

75 

No  1 1  gage,  1  %  inches 

sheathing 

4  feet  x  8  feet 

Blocked 

4 

175 

long,  7/16-inch  head, 
diamond  point, 

board 

4  feet  x  8  feet 

Unblocked 

7 

100 

galvanized 

Vz 

Unblocked 

7 

100 

Unblocked 

4 

125 

Blocked 

7 

125 

Gypsum  wallboard 

Blocked 

4 

150 

% 

Blocked 

4 

175 

6d  cooler  nails 

Blocked 
two  plv 

Base  ply  9  inches 
Face  plv  7  inches 

250 

Base  ply  -  6d  cooler  nails 
Face  plv  -  8d  cooler  nails 

Note  a.  Shear  values  are  based  on  a  maximum  framing  spacing  of  16  inches  (406  mm)  on  center. 
Note  b.   1  inch  =  25.4  mm;  1  foot  =  304.8  mm;  1  pound  per  foot  =  1,489  kg/m. 


780  CMR  2503.0  GYPSUM  BOARD 
MATERIALS 

2503.1  General:  All  gypsum  board  materials  and 
accessories  shall  be  marked  to  indicate  the 
appropriate  standards  referenced  in  780  CMR  2503 
and  stored  so  as  to  protect  such  materials  from  the 
weather. 


2503.2  Standards:  All  gypsum  board  materials  shall 
conform  to  the  appropriate  standards  listed  in  Table 
2503.2  and  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


403 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  2503.2 

GYPSUM  BOARD  MATERIALS  AND 

ACCESSORIES 


Material 

Standard 

Gypsum  sheathing 
Gypsum  wallboard 

ASTM  C79 
ASTM  C36 

Joint  reinforcing  tape  and 

compound 
Nails  for  gypsum  boards 
Steel  screws 

ASTM  C474; 

ASTM  C5 14 
ASTM  C 1002 

C475 
,C9S4 

Steel  studs,  nonloadbearing 
Water-resistant  gypsum 
backing  board 

ASTM  C645 
ASTM  C630 

2503.3  Installation:  Installation  of  these  materials 
shall  conform  to  780  CMR  2504.0  and  Table  2503.3, 
except  as  otherwise  required  by  780  CMR. 

2503.4  Water-resistant  gypsum  backer  board:  In 

all  areas  subjected  to  repeated  damp  conditions  and 
moisture  accumulation  such  as  bathtub  and  shower 
compartments,  water-resistant  gypsum  backer  board 
complying  with  ASTM  C630  listed  in  Appendix  A 
shall  be  used  as  a  substratum  unless  protected  with 
a  moistureproof  and  vaporproof  covering. 


Table  2503.3 
MAXIMUM  SPACING  OF  GYPSUM  WALLBOARD  FASTNERS 


Thickness  of 

Plane  of 
framing 
surface 

Long  dimension 
of  gypsum 

wallboard  sheets 
in  relation  to 
direction  of 

framing  members 

Maximum 
spacing  of 

Maximum  spacing  of 

fasteners  (center-to-center 

in  inches) 

Nails  to  wood 

wallboard  (inch) 

(center-to-center 
in  inches) 

Nails 

Screws 

Horizontal 

Either  direction 

16 

7 

12 

No  1 3  gage,  1 3/s"  long 

Vz 

Horizontal 

Perpendicular 

24 

7 

12 

diameter,  1 V*  long, 

Vertical 

Either  direction 

24 

8 

12 

Annular  ringed,  5d  cooler 
nail 

Horizontal 

Either  direction 

16 

7 

12 

No.  1 3  gage,  1  %"  long, 

% 

Horizontal 

Perpendicular 

24 

7 

12 

diameter,  1  %"  long, 

Vertical 

Either  direction 

24 

8 

12 

Annular  ringed,  6d  cooler 
nail. 

Fastening  required  with  adhesive  application 

Vi 
or 

Horizontal 

Either  direction 

16 

16 

16 

As  required  for  Vi'  and 

Horizontal 

Perpendicular 

24 

12 

16 

s/a"  gypsum  wallboard, 

% 

Vertical 

Either  direction 

24 

16 

24 

2  layers  each 

Horizontal 

Perpendicular 

24 

16 

16 

Base  ply  nailed  as 
required  for  Vi   gypsum 
wallboard  and  face  ply 
placed  with  adhesive 

%"  (3/4  total) 

Vertical 

Either  direction 

24 

24 

24 

Note  a.  Where  the  metal  framing  has  a  clinching  design  formed  to  receive  the  nails  by  two  edges  of  metal,  the 
nails  shall  not  be  less  than  %  inch  longer  than  the  wallboard  thickness,  and  shall  have  ringed  shanks.  Where  the  metal 
framing  has  a  nailing  groove  formed  to  receive  the  nails,  the  nails  shall  have  barbed  shanks  or  be  5d  cooler  nails  (No 
W/i  gage,  1%  inches  long,  15/64-inch  head)  for  '/z-inch  gypsum  wallboard  (No.  13  gage,  l7/a  inches  long,  15/64-inch 
head)  for  %-inch  gypsum  wallboard. 

Note  b.  Two  nails  at  two  inches  to  2/2  inches  apart  are  permitted  to  be  used  if  the  pairs  are  spaced  12  inches 
center-to-center  except  around  perimeters. 

Note  c.  Screws  shall  be  No.  6  with  tapered  head  and  long  enough  to  penetrate  into  wood  framing  not  less  than 
5/a  inch  and  metal  framing  not  less  than  'A  inch. 

Note  d.  For  fireresistance  rated  construction  assemblies,  see  the  pertinent  fire  test  information. 

Note  e.   1  inch  =  25.4  mm. 


404 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

GYPSUM  BOARD  AND  PLASTER 


780  CMR  2504.0  GYPSUM 
CONSTRUCTION 

2504.1  General:  Gypsum  board  and  plaster 
construction  shall  be  of  the  materials  listed  in  Table 

2503.2  and  Table  2505.2.  These  materials  shall  be 
assembled  and  installed  in  compliance  with  the 
appropriate  standards  listed  in  Table  2504.1  and 
Appendix  A. 

Table  2504.1 

INSTALLATION  OF  GYPSUM 

CONSTRUCTION 


Gypsum  plaster 
Gypsum  veneer  base 

Gypsum  veneer  plaster 
Interior  lathing  and  furring 

Steel  framing  for  gypsum 
boards 


ASTM  C842 
ASTM  C844 


ASTM  C843 
ASTM  C841 


ASTMC754;C1007 


2504.2  Limitations:  Gypsum  construction  shall  not 
be  used  in  any  exterior  location  where  such  gypsum 
construction  will  be  exposed  directly  to  the  weather. 

2504.3  Inspection:  The  building  official  shall  be 
notified  not  less  than  24  hours  in  advance  of  all 
plastering  work  or  installation  of  any  gypsum  board 
except  gypsum  lath.  Plaster  shall  not  be  applied 
until  after  the  lathing  or  other  plaster  base  has  been 
inspected  and  approved. 

2504.4  Weather  protection:  When  plastering  work 
is  in  progress,  the  building  or  structure  shall  be 
enclosed  and  conditioned  to  provide  proper 
ventilation  and  temperatures  not  less  than  40°F 
(4°C)  nor  more  than  80°F  (27°C)  from  one  week 
prior  to  the  plastering  operation  and  until  one  week 
following  or  until  the  plaster  is  dry. 

780  CMR  2505.0  INTERIOR  LATHING 
AND  GYPSUM  PLASTERING 

2505.1  General:  All  interior  lathing  and  gypsum 
plastering  materials  and  accessories  shall  be  marked 
to  indicate  the  appropriate  standards  referenced  in 
780  CMR  2505.0  and  stored  in  such  a  manner  as  to 
protect  them  from  the  weather. 

2505.2  Standards:  All  interior  lathing  and  gypsum 
plastering  materials  shall  conform  to  the  standards 
listed  in  Table  2505.2  and  Appendix  A  and,  where 


required  for  fire  protection,  shall  also  conform  to  the 
provisions  of  780  CMR  7. 

Table  2505.2 

PLASTERING  MATERIALS  AND 

ACCESSORIES 


Material 

Standard 

Exterior  plaster  bonding  compounds 
Gypsum  base  for  veneer  plasters 
Gypsum  casting  and  molding  plaster 

ASTM  C932 
ASTM  C588 
ASTM  C59 

Gypsum  Keene's  cement 
Gypsum  lath 

ASTMC61 
ASTM  C37 

Gypsum  plaster 
Gypsum  veneer  plaster 
Interior  bonding  compounds 

,  gypsum 

ASTM  C28 
ASTM  C587 
ASTM  C63 1 

Lime  plasters 
Metal  lath 

ASTMC5;C206 
ASTMC847 

Plaster  aggregates 
Sand 
Perlite 
Vermiculite 

ASTM  C35;  C897 
ASTM  C35 
ASTMC35 

Portland  cement 
Steel  studs  and  track 

ASTM  CI 50 
ASTMC645;C955 

Steel  screws 
Welded  wire  lath 

ASTMC1002.C954 
ASTMC933 

2505.3  Installation:  Installation  of  interior  lathing 
and  gypsum  plastering  materials  shall  conform  to 
780  CMR  2504.0. 

780  CMR  2506.0  PORTLAND  CEMENT 
STUCCO  LATHING  AND  PLASTERING 

2506.1  General:  All  exterior  and  interior  portland 
cement  stucco  lathing  and  plastering  shall  be  done 
with  the  appropriate  materials  listed  in  Table  2505.2 
and  Appendix  A. 

2506.2  Weather  protection:  All  materials  shall  be 
stored  in  such  a  manner  as  to  protect  such  materials 
from  the  weather. 

2506.3  Installation:  Installation  of  these  materials 
shall  be  in  compliance  with  ASTM  C926  and  ASTM 
C  1063  listed  in  and  780  CMR  2506.4. 

2506.4  Protection  after  application:  At  all  times 
during  application  and  for  a  period  of  not  less  than 
48  hours  after  application  of  each  coat,  provisions 
shall  be  made  to  keep  stucco  work  above  40  °F 
(4°C). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


405 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


40(3  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  26 


PLASTIC 


780  CMR  2601.0  GENERAL 

2601.1  Scope:  The  provisions  of  780  CMR  26  shall 

govern  the  design,  construction  and  quality  of  light- 
transmitting  plastic  materials  and  foam  plastics. 
780  CMR  2601.0  shall  apply  to  all  light-transmitting 
plastic  materials  and  foam  plastics.  780  CMR 
2603.0  shall  only  apply  to  foam  plastics.   780  CMR 

2604.0  through  2608.0  shall  only  apply  to  light- 
transmitting  plastic  materials 

2601.2  Approved  materials:  The  use  of  all  plastics 
that  conform  to  the  strength,  durability,  sanitary  and 
fireresistive  requirements  of  this  code  and  ASTM 
D635,  D1929,  D2843  and  E84  listed  in  Appendix  A, 
shall  be  permitted  subject  to  the  limitations  of 
780  CMR  26. 

2601.3  Application  for  approval:  Applicants  for 
approval  of  a  plastic  material  shall  furnish,  in 
accordance  with  780  CMR  1704.0  all  necessary 
technical  data  required  by  the  code  official .  The 
data  shall  include,  if  necessary:  chemical 
composition;  applicable  physical,  mechanical  and 
thermal  properties,  such  as  fireresistance, 
flammability  and  flame  spread;  weather  resistance; 
electrical  properties;  products  of  combustion;  and 
coefficients  of  expansion. 

2601.4  Identification:  All  plastic  materials 
approved  for  use  under  780  CMR  shall  be  identified 
by  the  trade  formula  number  or  name  or  other 
acceptable  identification.  Each  unit  or  package  shall 
bear  the  approval  number  or  other  identification 
mark  of  the  approving  authority. 

2601.5  Interior  finish  and  trim  Light-transmitting 
plastic  materials  installed  as  interior  finish  or  trim 
shall  comply  with  780  CMR  803.0.  Foam  plastics 
shall  only  be  installed  as  interior  finish  in 
accordance  with  780  CMR  2603.8.  Foam  plastics 
installed  as  interior  trim  shall  comply  with  780  CMR 
2603.7. 

780  CMR  2602.0  DEFINITIONS 

2602.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  26  and  as  used 
elsewhere  in  780  CMR,  have  the  meanings  shown 
herein. 

Plastic 

Light-diffusing      system:  A      suspended 

construction  consisting  in  whole  or  in  part  of 
lenses,  panels,  grids  or  baffles  suspended  below 
independently  mounted  electrical  lighting  sources. 


Plastic  glazing:  Plastic  materials  which  are 
glazed  or  set  in  frame  or  sash  and  not  held  by 
mechanical  fasteners  which  pass  through  the 
glazing  material. 

Plastic  roof  panels:   Plastic  materials  which  are 
fastened  to  structural  members,  or  to  structural 
panels  or  sheathing,  and  which  are  used  as  light- 
transmitting  media  in  roofs. 
Plastic  wall  panels:   Plastic  materials  which  are 
fastened  to  structural  members,  or  to  structural 
panels  or  sheathing,  and  which  are  used  as  light- 
transmitting  media  in  exterior  walls. 
Reinforced     plastic,     glass     fiber:         Plastic 
reinforced  with  glass  fiber  having  not  less  than 
20%  of  glass  fibers  by  weight. 
Thermoplastic   material:      A  plastic   material 
which  is  capable  of  being  repeatedly  softened  by 
increase  of  temperature  and  hardened  by  decrease 
of  temperature. 

Thermosetting  material:  A  plastic  material 
which  is  capable  of  being  changed  into  a 
substantially  nonreformable  product  when  cured. 

780  CMR  2603.0  FOAM  PLASTIC 

2603.1  General:  The  provisions  of  780  CMR 
2603.0  shall  govern  the  requirements  and  uses  of 
foam  plastic  in  buildings  or  structures. 

2603.1.1  Urea  based foamed-in-place  insulation: 
Use  of  this  material  has  been  banned  by  the 
Massachusetts  Department  of  Public  Healtlu 

2603.2  Labeling:  Foam  plastics  or  their  packages  of 
foam  plastics,  and  containers  of  foam-in-place 
plastic  system  ingredients,  shall  be  labeled  in 
compliance  with  780  CMR  1704.3. 

2603.3  Surface-burning  characteristics:  Unless 
otherwise  indicated  in  780  CMR  2603.0,  all  foam 
plastic  and  foam  plastic  cores  of  manufactured 
assemblies  shall  have  a  flame  spread  rating  of  not 
more  than  75  and  a  smoke-developed  rating  of  not 
more  than  450  when  tested  in  the  maximum 
thickness  intended  for  use  in  accordance  with  ASTM 
E84  listed  in  Appendix  A. 

Exceptions: 

1.  Smoke-developed  ratings  for  interior  trim  as 
provided  for  in  780  CMR  2603.7.4. 

2.  Flame  spread  ratings  for  exterior  wall 
installations  as  provided  for  in  780  CMR  2603.6.3 
and  2603.6.8. 

3.  Flame  spread  and  smoke-developed  ratings  for 
roof  applications  as  provided  for  in  780  CMR 
2603.4.1.5. 

4.  Where  foam  plastic  is  tested  in  a  thickness  of 
four  inches  (102  mm)  and  is  used  in  a  thickness  of 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


greater  than  four  inches  (102  mm)  up  to  ten  inches 
(254  mm),  the  building  shall  be  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2. 1  and  the  foam 
plastic  shall  be  protected  by  a  thermal  barrier. 

2603.4  Thermal  barrier:  Except  as  provided  for  in 
7S0  CMR  603.4. 1,  all  foam  plastic  shall  be  separated 
from  the  interior  of  a  building  by  an  approved 
thermal  barrier  of  '/2-inch  gypsum  wallboard  or 
equivalent  thermal  barrier  material  which  will  limit 
the  average  temperature  rise  of  the  unexposed 
surface  to  not  more  than  250°F  (121  °C)  after  15 
minutes  of  fire  exposure,  complying  with  the 
standard  time-temperature  curve  of  ASTM  El  19 
listed  in  Appendix  A.  The  thermal  barrier  shall  be 
installed  such  that  said  thermal  barrier  will  stay  in 
place  for  a  minimum  of  15  minutes  under  the  same 
test  conditions. 

2603.4.1  Thermal  barrier  not  required:    The 

thermal  barrier  specified  in  780  CMR  2603.4  is 
not  required  under  the  conditions  set  forth  in  any 
one  of  780  CMR  2603.4. 1.1  through  2603.4.1.8. 

2603.4.1.1  Siding  backer  board:  Foam 
plastic  to  be  used  as  siding  backer  board,  or 
where  applied  as  insulation  with  re-siding  over 
existing  exterior  wall  construction,  shall  have 
a  maximum  thickness  of  Vi  inch  (13  mm)  and 
shall  be  separated  from  the  interior  of  the 
building  by  not  less  than  two  inches  (51  mm) 
of  mineral  fiber  insulation  or  other  approved 
materials. 

2603.4.1.2  Walk-in  coolers:  Where  foam 
plastic  is  used  in  a  maximum  thickness  of  four 
inches  (102  mm)  in  walk-in  coolers  or  in 
freezer  units  less  than  400  square  feet  (37.2  m2) 
in  floor  area,  the  foam  plastic  shall  be  covered 
by  a  metal  facing  of  not  less  than  0.032-inch- 
thick  aluminum  or  corrosion-resistant  steel 
having  a  minimum  base  metal  thickness  of 
0.016  inch. 

2603.4.1.3  Masonry  or  concrete 
construction:  Where  the  foam  plastic  is 
protected  by  a  one-inch  (25  mm)  minimum 
thickness  of  masonry  or  concrete,  a  thermal 
barrier  is  not  required. 

2603.4.1.4  Attics  and  crawl  spaces:  Within 
an  attic  or  crawl  space  where  entry  is  made 
only  for  service  of  utilities,  foam  plastic  shall 
be  protected  against  ignition  by  1  Vz  inch-thick 
(38  mm)  mineral  fiber  insulation,  Vi-inch-thick 
wood  structural  panel,  particleboard  or 
hardboard,  %-inch  gypsum  wallboard, 
corrosion-resistant  steel  having  a  base  metal 
thickness  of  0.016  inch,  or  other  approved 
material  installed  in  such  a  manner  that  the 
foam  plastic  is  not  exposed.  The  protective 
covering  shall  be  consistent  with  the 
requirements  for  the  type  of  construction. 


2603.4.1.5  Roofing:  Foam  plastic  used  in  a 
roof  covering  assembly  that  employs  a  wood 
roof  deck  without  the  thermal  barrier  shall 
have  the  foam  plastic  separated  from  the 
interior  of  the  building  by  wood  structural 
panel  sheathing  or  tongue-and-groove  wood 
plank  sheathing  not  less  than  15/32  inch  in 
thickness  or  other  approved  materials.  All 
wood  structural  panel  roof  sheathing  shall  be 
bonded  with  exterior  glue  with  edges  supported 
by  blocking,  tongue-and-groove  joints  or  other 
approved  type  of  edge  support. 

The  requirements  of  780  CMR  2603.3  and 
2603.4  are  not  applicable  to  foam  plastic  roof 
insulation  used  in  roof  deck  construction  that 
complies  as  an  assembly  with  FM  4450  or  UL 
1256  listed  in  Appendix  A. 

For  all  roof  applications,  the  smoke- 
developed  rating  shall  not  be  applicable. 

2603.4.1.6  Doors  not  required  to  have  a 
fireresistance  rating:  Where  doors  are 
permitted  without  a  fireresistance  rating  and 
foam  plastic  is  used  as  a  core  material,  the  door 
facing  shall  be  of  metal  having  a  minimum 
thickness  of  0.032-inch  aluminum  or  0.016- 
inch  steel. 

2603.4.1.7  Exterior  doors  in  buildings  of  Use 
Group  R-3:  In  buildings  of  Use  Group  R-3, 
foam-filled  exterior  entrance  doors  that  do  not 
require  a  fireresistance  rating  shall  be  faced 
with  wood  or  other  approved  materials. 

2603.4.1.8  Exterior  walls,  one-story 
buildings:  A  thermal  barrier  is  not  required  in 
the  exterior  wall  application  provided  for  in 
780  CMR  2603.6.8. 

2603.5  Exterior  applications:  Foam  plastic 
installed  in  or  on  the  exterior  side  of  walls  of 
buildings  shall  also  comply  with  the  applicable 
requirements  of  780  CMR  1405.0. 

2603.6  Exterior  walls:  Foam  plastic  installed  in  or 
on  the  exterior  side  of  exterior  walls  in  buildings  of 
Type  1,  2,  3  or  4  construction  shall  comply  with  the 
requirements  of  780  CMR  2603.6.1  through 
2603.6.7  or,  in  one-story  buildings,  shall  comply 
with  the  requirements  of  780  CMR  2603.6.8. 

2603.6.1  Fireresistance  rating:  Foam  plastic  is 
permitted  within  exterior  walls  provided  that  the 
wall  assembly  affords  the  required  fireresistance 
rating. 

2603.6.2  Thickness.  The  foam  plastic  shall  be 
limited  to  a  maximum  thickness  of  four  inches 
(102  mm). 

2603.6.3  Flame  spread:  The  foam  plastic  core, 
coatings  and  facings,  when  tested  individually, 
shall  each  have  a  flame  spread  rating  of  25  or  less 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


when  tested  in  accordance  with  ASTM  E84  listed 
in  Appendix  A. 

2603.6.4  Fastening:  Facing,  coating  and  core 
materials  shall  be  fastened  to  each  other,  and  the 
overall  assembly  shall  be  fastened  to  the  building 
frame  to  prohibit  failure  in  bond  due  to 
temperatures  that  occur  in  a  building  fire,  wind 
loads  or  other  conditions. 

2603.6.5  Full-scale  tests:  Results  of  full-scale 
fire  tests,  which  reflect  an  end-use  configuration 
and  which  demonstrate  that  the  assembly  in  its 
final  form  does  not  show  any  tendency  to 
propagate  flame  over  the  surface  or  through  the 
core  when  exposed  on  the  exterior  face  to  a  fire 
source,  shall  be  submitted  to  the  code  official. 
Such  testing  shall  be  performed  on  the  finished 
manufactured  foam  plastic  assemblies  and  on  the 
maximum  thickness  intended  for  installation. 

2603.6.6  Thermal  barrier:  Any  foam  plastic 
shall  be  separated  from  the  building  interior  by  a 
thermal  barrier  unless  specific  approval  is 
obtained  on  the  basis  of  780  CMR  2603.8. 

2603.6.7  Identification  The  edge  or  face  of  each 
piece  of  foam  plastic  insulation  shall  be  labeled  in 
accordance  with  780  CMR  1704.3. 

2603.6.8  Exterior  walls,  one-story  buildings: 

Foam  plastic  insulation  having  a  flame  spread 
rating  of  not  more  than  25  and  installed  without  a 
thermal  barrier  in  or  on  exterior  walls  of  one- 
story  buildings,  shall  have  a  thickness  of  not  more 
than  four  inches  (102  mm).  The  foam  plastic 
shall  be  covered  by  a  thickness  of  not  less  than 
0.032-inch  aluminum  or  corrosion-  resistant  steel 
having  a  base  metal  thickness  of  0.016  inch  and 
the  building  area  shall  be  equipped  throughout 
with  an  automatic  sprinkler  system  in  accordance 
with  780  CMR  906.2.1. 

2603.7  Interior  trim:  Foam  plastic  used  as  interior 
trim  shall  comply  with  780  CMR  2603.7.1  through 
2603.7.4. 

2603.7.1  Density:  The  minimum  density  of  the 
interior  trim  shall  be  20  pounds  per  cubic  foot 
(320  kg/m3). 

2603.7.2  Thickness:  The  maximum  thickness  of 
the  interior  trim  shall  be  V2  inch  (13  mm)  and  the 
maximum  width  shall  be  four  inches  (102  mm). 

2603.7.3  Area  limitation:  The  interior  trim  shall 
not  constitute  more  than  10%  of  the  aggregate 
wall  and  ceiling  area  of  any  room  or  space. 

2603.7.4  Flame  spread:  The  flame  spread  rating 
shall  not  exceed  75  when  tested  in  accordance 
with  ASTM  E84  listed  in  Appendix  A.  The 
smoke-developed  rating  shall  not  be  limited 

2603.8  Alternative  approval:  Foam  plastic  is  not 
required    to    comply    with    the    requirements    of 


PLASTIC 

780  CMR  2603.4  through  2603.7  when  specifically 
approved  based  on  tests  such  as  FM  Procedure  4880, 
UL  Subject  1040  or  UL  1715  listed  in  Appendix  A. 
Such  testing  shall  be  performed  on  the  finished 
manufactured  foam  plastic  assemblies  and  on  the 
maximum  thickness  intended  for  use.  Foam  plastics 
which  are  used  as  interior  finish  on  the  basis  of 
diversified  tests  shall  also  conform  to  the  flame 
spread  requirements  of  780  CMR  803.0.  All 
assemblies  tested  shall  include  seams,  joints  and 
other  typical  details  used  in  the  installation  of  the 
assembly  and  shall  be  tested  in  the  manner  intended 
for  use. 

780  CMR  2604.0  GENERAL 

REQUIREMENTS  FOR 

UGHT-TRANSMnTING  PLASTICS 

2604.1  Approved  light-transmitting  plastics:  An 

approved  light-transmitting  plastic  shall  be:  any 
thermoplastic,  thermosetting  or  reinforced 
thermosetting  plastic  material  which  has  a  self- 
ignition  temperature  of  650°F  (343°C)  or  greater 
when  tested  in  accordance  with  ASTM  D1929  listed 
in  Appendix  A;  a  smoke  density  rating  not  greater 
than  450  when  tested  in  the  manner  intended  for  use 
in  accordance  with  ASTM  E84  listed  in  Appendix  A, 
or  not  greater  than  75  when  tested  in  the  thickness 
intended  for  use  in  accordance  with  ASTM  D2843 
listed  in  Appendix  A;  and  which  conforms  to  one  of 
the  following  combustibility  classifications: 

Class  CI:  Plastic  materials  which  have  a  burning 
extent  of  one  inch  (25  mm)  or  less  when  tested  at 
a  nominal  thickness  of  .060  inch,  or  in  the 
thickness  intended  for  use,  in  accordance  with 
ASTM  D635  listed  in  Appendix  A,  or 
Class  C2:  Plastic  materials  which  have  a  burning 
rate  of  2.5  inches  per  minute  (1.06  mm/s)  or  less 
when  tested  at  a  nominal  thickness  of  .060  inch, 
or  in  the  thickness  intended  for  use,  in  accordance 
with  ASTM  D635  listed  in  Appendix  A. 

2604.2  Structural  requirements:  All  plastic 
materials  and  associated  assemblies  shall  be  of 
adequate  strength  and  durability  to  withstand  the 
loads  and  forces  specified  in  780  CMR  16  for  the 
approved  application. 

2604.3  Connections  and  supports:  All  fastenings, 
connections  and  supports  shall  be  proportioned  to 
transmit  safely  two  and  one-half  times  the  design 
live  load.  Adequate  allowance  shall  be  made  in  the 
fastenings  and  supports  for  differential  expansion 
and  contraction  of  the  connected  materials. 

2604.4  Other  applicable  requirements:  Light- 
transmitting  plastics  installed  as  exterior  wall  panels 
shall  conform  to  780  CMR  2605.0.  Light- 
transmitting  plastics  installed  in  glazing  of  un- 
protected openings  shall  conform  to  780  CMR 
2606  0.  Light-transmitting  plastics  installed  as  roof 
panels  shall  conform  to  780  CMR  2607.0.    Light- 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


transmitting  plastics  installed  in  skylight  assemblies 
shall  conform  to  780  CMR  2608.0. 

2604.5  Light-diffusing  systems:  Light-diffusing 
systems  shall  not  be  installed  in  occupancies  in  Use 
Group  1-2  or  1-3,  nor  in  exits,  unless  the  building  is 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1. 
Plastic  diffusers  shall  be  supported  directly  or 
indirectly  from  ceiling  or  roof  construction  by  use  of 
noncombustible  hangers.  Hangers  shall  be  at  least 
No.  12  steel-wire  gage  (0. 106  inch)  galvanized  wire 
or  equivalent. 

2604.5.1  Installation:  Approved  light- 
transmitting  plastic  diffusers  shall  comply  with 
780  CMR  803.0  unless  the  plastic  panels  will  fall 
from  the  mountings  before  igniting  and  at  an 
ambient  temperature  of  at  least  200  °F  (93  °C) 
below  the  ignition  temperature  of  the  panels.  The 
panels  shall  remain  in  place  at  an  ambient  room 
temperature  of  175°F  (79  °C)  for  a  period  of  not 
less  than  1 5  minutes 

2604.5.2  Size  limitations:  Individual  panels  or 
units  shall  not  exceed  ten  feet  (3048  mm)  in 
length  nor  30  square  feet  (2.79  m2)  in  area. 

2604.5.3  Fire  suppression  system:  In  buildings 
that  are  equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1,  plastic  light-diffusing  systems  shall  be 
protected  both  above  and  below  unless  the 
sprinkler  system  has  been  specifically  approved 
for  installation  only  above  the  light-diffusing 
system.  Areas  of  light-diffusing  systems  that  are 
protected  in  accordance  with  780  CMR  2604.0 
shall  not  be  limited. 

2604.5.4  Electrical  lighting  fixtures:  Plastic 
light-transmitting  panels  and  light  diffuser  panels 
which  are  installed  in  approved  electrical  lighting 
fixtures  shall  comply  with  the  requirements  of 
780  CMR  803.0  unless  the  plastic  panels  conform 
to  the  requirements  of  780  CMR  2604.5. 1 .  The 
area  of  approved  plastic  materials  that  are  used  in 
required  exits  or  corridors  shall  not  exceed  30% 
of  the  aggregate  area  of  the  ceiling  in  which  such 
panels  are  installed,  unless  the  building  is 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1. 

2604.6  Partitions:  Approved  light-transmitting 
plastics  used  in  or  as  partitions  shall  comply  with  the 
requirements  of  780  CMR  603.2  and  803.0. 

2604.7  Bathroom  accessories:  Approved  plastics 
shall  be  permitted  as  glazing  in  shower  stalls, 
shower  doors,  bathtub  enclosures  and  similar 
accessory  units  (see  780  CMR  2405.0). 

2604.8  Awnings  and  similar  structures:  Approved 
light-transmitting  plastics  used   on   awnings   and 


similar  structures  shall  comply  with  the  general 
performance  provisions  of  780  CMR. 

780  CMR  2605.0  UGHT-TRANSMnTING 
WALL  PANELS 

2605.1  General:  Approved  light-transmitting 
plastic  materials  shall  not  be  used  as  wall  panels  in 
exterior  walls  in  occupancies  in  Use  Groups  A-l,  A- 
2,  1-2  and  1-3.  In  all  other  use  groups  approved 
light-transmitting  plastic  materials  shall  be  permitted 
to  be  used  as  wall  panels  in  exterior  walls  provided 
that  the  walls  are  not  required  to  have  a 
fireresistance  rating  and  the  installation  conforms  to 
the  requirements  of  780  CMR  2605.0.  Such  panels 
shall  be  erected  and  anchored  on  a  foundation  coat, 
waterproofed  or  otherwise  protected  from  moisture 
absorption  and  sealed  with  a  coat  of  mastic  or  other 
approved  waterproof  coating.  Refer  to  780  CMR 
2604.0  for  requirements  for  approved  light- 
transmitting  plastics. 

2605.2  Installation:  Exterior  wall  panels  installed 
as  provided  for  herein  shall  not  alter  the  type  of 
construction  classification  of  the  building. 

2605.3  Height  limitation:  Light-transmitting 
plastics  shall  not  be  installed  more  than  70  feet 
(21336mm)  above  mean  grade,  except  as  allowed  by 
780  CMR  2605.7. 

2605.4  Area   limitation    and   separation:      The 

maximum  area  of  a  single  wall  panel  and  minimum 
vertical  and  horizontal  separation  requirements  for 
exterior  plastic  wall  panels  shall  be  as  provided  for 
in  Table  2605.4.  The  maximum  percentage  of  wall 
area  of  any  story  in  plastic  wall  panels  shall  not 
exceed  that  indicated  in  Table  2605.4  or  the 
percentage  of  unprotected  openings  permitted  by 
780  CMR  705.3,  whichever  is  smaller. 

Exception:  Veneers  of  approved  weather- 
resistant  plastics  used  as  exterior  siding  in 
buildings  of  Type  5  construction  in  compliance 
with  780  CMR  1405.2. 

2605.5  Spandrel  separation:  Vertical  spandrel  wall 
separation  shall  be  in  accordance  with  Table  2605.4. 
See  780  CMR  2604.1  for  the  definition  of  CI  and 
C2  light-transmitting  plastics. 

2605.6  Fire  canopies:  In  structures  which  are 
provided  on  any  floor  above  the  first  with 
continuous  architectural  projections  constituting  an 
effective  fire  canopy  extending  at  least  36  inches 
(914  mm)  from  the  surface  of  the  wall  in  which 
plastic  wall  panels  are  installed,  vertical  separation 
at  that  floor  is  not  required  except  as  provided  by  the 
vertical  thickness  of  the  projection. 

2605.7  Automatic  sprinkler  system:  Where  the 
building  is  equipped  throughout  with  an  automatic 
sprinkler  system   in   accordance  with   780   CMR 


410 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


PLASTIC 


906.2.1,  the  maximum  percentage  area  of  exterior 
wall  in  any  story  in  plastic  wall  panels  and  the 
maximum  square  footage  of  a  single  area  given  in 
Table  2605.4  shall  be  increased  100%,  but  the  area 
of  plastic  wall  panels  shall  not  exceed  50%  of  the 
wall  area  in  any  story,  or  the  area  permitted  by 
780  CMR  705.3.1  for  unprotected  openings, 
whichever  is  smaller.  These  installations  shall  be 
exempt  from  height  limitations. 

Table  2605.4 
AREA  LIMITATION  AND  SEPARATION 

REQUIREMENTS  FOR  LIGHT- 
TRANSMITTING  PLASTIC  WALL  PANELS3 


K.re 
separation 

Class 

of 
plastic 

Maximum 
percentage 
area  of 
exterior 
wall  in 
plastic 
panels 

Maximum 

single 

area 

(square 

feet) 

Minimum 
separation  of 
panels  (feet) 

distance 
(feet) 

Vertical 

Horizontal 

<6 

NPC 

NP 

- 

6  or  more 
but  less 
than  11 

CI 
C2 

10 

NP 

50 

NP 

8 

4 

1 1  or  more 
but  less 
than  30 

CI 
C2 

25 
15 

90 

70 

6 
8 

4 
4 

>30 

CI 
C2 

50 

50 

Not 

limited 

100 

3b 
6b 

0 
3 

Note  a.  For  combination  of  glazing  and  wall  panel 
areas  permitted,  see  780  CMR  2605.8. 

Note  b.  For  reductions  in  vertical  separation 
allowed,  see  780  CMR  2605.0. 

Note  c.  NP  =  Not  permitted. 

Note  d.   1  foot  =  304.8  mm;  1  square  foot  =  0.093 


such  glazing  is  installed  or  the  area  of  unprotected 
openings  permitted  by  780  CMR  705.3, 
whichever  is  smaller. 

Exception:  Where  the  building  is  equipped 
throughout  with  an  automatic  sprinkler  system 
in  accordance  with  780  CMR  906.2. 1,  the  area 
of  the  glazing  shall  not  exceed  50%  of  the  wall 
face  of  the  story  in  which  such  glazing  is 
located  or  the  area  of  unprotected  openings 
permitted  by  780  CMR  705.3.1,  whichever  is 
smaller. 

2606.2.2  Size:  The  area  of  a  unit  or  pane  of 
glazing  installed  above  the  first  story  shall  not 
exceed  16  square  feet  (1.49  m:)  and  the  vertical 
dimension  of  a  unit  or  pane  shall  not  exceed  four 
feet  (1219  mm).  There  shall  be  a  minimum  three- 
foot  (914  mm)  vertical  spandrel  wall  between 
stories. 

2606.2.3  Height:  Approved  plastic  glazing  shall 
not  be  installed  more  than  70  feet  (21336  mm) 
above  mean  grade. 

2606.3       Approved       thermoplastic       glazing: 

Approved  thermoplastic  materials  installed  in  areas 
up  to  50%  of  the  wall  area  of  each  story,  but  not 
exceeding  the  area  of  unprotected  openings 
permitted  by  780  CMR  705.3,  are  permitted  in 
structures  less  than  150  feet  (45720  mm)  in  height 
provided  that  each  floor  above  the  first  floor  is 
equipped  with  continuous  architectural  projections 
constituting  an  effective  fire  canopy  extending  at 
least  three  feet  (914  mm)  from  the  surface  of  the 
wall  in  which  the  glazing  is  installed.  The  size  and 
the  dimensions  of  individual  units  shall  not  be 
limited  in  such  installations  except  as  required  to 
meet  structural  loading  requirements. 


2605.8  Combinations  of  glazing  and  plastic  wall 
panels:  Combinations  of  plastic  glazing  and  plastic 
wall  panels  shall  be  subject  to  the  area,  height  and 
percentage  limitations  and  the  separation 
requirements  applicable  to  the  class  of  plastic 
asprescribed  for  plastic  wall  panel  installations. 

780  CMR  2606.0  UGHT-TRANSMITTING 

PLASTIC  GLAZING  OF  UNPROTECTED 

OPENINGS 

2606.1  Where  permitted:  Plastic  glazing  is 
permitted  in  doors,  sashes  and  framed  openings 
where  protected  openings  are  not  required  in 
accordance  with  780  CMR  705.0  and  the  installation 
conforms  to  the  requirements  of  780  CMR  2606.2  or 
780  CMR  2606.3. 

2606.2  Approved  plastic  glazing:  Approved 
plastic  glazing  shall  comply  with  780  CMR  2606.2. 1 
through  2606.2.3. 

2606.2.1  Area:   The  area  of  the  glazing  shall  not 
exceed  25%  of  the  wall  face  of  the  story  in  which 


780  CMR  2607.0  UGHT-TRANSMrTTING 
PLASTIC  ROOF  PANELS 

2607.1  General:  Approved  light-transmitting 
plastic  roof  panels  shall  not  be  installed  in 
occupancies  in  Use  Groups  H,  1-2  and  1-3.  In  all 
other  use  groups,  approved  light-transmitting  plastic 
roof  panels  shall  not  be  installed  unless  one  of  the 
following  conditions  applies: 

1 .  The  building  is  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906. 2.1; 

2.  The  roof  construction  is  not  required  to  have  a 
fireresistance  rating  by  Table  602;  or 

3.  The  roof  panels  meet  the  requirements  for  roof 
coverings. 

2607.2  Separations:  Individual  roof  panels  shall  be 
separated  from  each  other  by  a  distance  of  not  less 
than  four  feet  (1219  mm)  measured  in  a  horizontal 
plane,  except  that  the  separation  between  roof  panels 
is  not  required  in  a  building  equipped  throughout 
with  an  automatic  sprinkler  system  in  accordance 
with  780  CMR  906.2.1. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


411 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2607.3  Location:  Where  exterior  wall  openings  are 
required  to  be  protected  by  780  CMR  705.0,  a  roof 
panel  or  unit  shall  not  be  installed  within  six  feet 
(1829  mm)  of  such  exterior  wall. 

2607.4  Area  limitations:  Roof  panels  or  units  shall 
be  limited  in  area  and  the  aggregate  area  of  panels 
shall  be  limited  by  a  percentage  of  the  floor  area  of 
the  room  or  space  sheltered  in  accordance  with 
Table  2607.4. 

Exceptions: 

1.  The  area  limitations  of  Table  2607.4  shall  be 
increased  by  100%  in  buildings  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2. 1 . 

2.  Low-hazard  occupancy  buildings,  such  as 
swimming  pool  shelters  and  greenhouses,  are 
exempt  from  the  area  limitations  of  Table  2607.4 
provided  that  the  buildings  do  not  exceed  5,000 
square  feet  (465  m2)  in  area  and  have  a  minimum 

fire  separation  distance  of  four  feet  (1219  mm). 

3.  Roof  coverings  over  terraces  and  patios  in 
occupancies  in  Use  Group  R-3  are  exempt  from 
the  area  limitations  of  Table  2607.4  and  shall  be 
permitted  with  approved  plastics. 

Table  2607.4 
AREA  LIMITATIONS  FOR  ROOF  PANELS 

Maximum  area  Maximum 

Class  of  plastic        individual  unit  or         aggregate  area 
panel  (square  feet)        (%  of  floor  area) 


CI 
C2 


300 
100 


30 


Note  a.   1  square  foot  =  0.093  mJ 


780  CMR  2608.0  UGHT-TRAiNSMTITING 
SKYLIGHT  GLAZING 

2608.1    Light-transmitting    plastic   glazing   of 

skylight  assemblies:     Skylight  assemblies  glazed 

with  approved  light-transmitting  plastic  materials 

shall  conform  to  the  provisions  of  780  CMR  2608.0. 

Exceptions: 

1 .  780  CMR  2608. 1  shall  not  apply  to  a  skylight 
of  approved  light-transmitting  plastic  on  a 
building  which  is  not  more  than  one  story  in 
height,  has  afire  separation  distance  of  at  least  30 
feet  (9144  mm)  and  the  room  or  space  sheltered 
by  the  roof  is  not  classified  as  Use  Group  1-2  or  I- 
3  or  as  a  means  of  egress. 

2.  780  CMR  26.08.1  shall  not  apply  to  skylights 
in  which  the  approved  light-transmitting  plastic 
conforms  to  the  required  roof  covering  class  in 
accordance  with  780  CMR  1506.0. 

2608.2  Mounting:  The  plastic  shall  be  mounted 
above  the  plane  of  the  roof  on  a  curb  constructed  in 
accordance  with  the  requirements  for  the  type  of 
construction  classification,  but  at  least  four  inches 
(102  mm)  above  the  plane  of  the  roof.  Edges  of 
plastic  skylights  or  domes  shall  be  protected  by 
metal  or  other  approved  noncombustible  material,  or 


the  plastic  dome  or  skylight  shall  be  shown  to  be 
able  to  resist  ignition  when  exposed  at  the  edge  to  a 
flame  from  a  Class  B  brand  as  described  in  ASTM 
El  08  listed  in  Appendix  A. 
Exceptions: 

1 .  Curbs  are  not  required  for  skylights  used  on 
roofs  having  a  minimum  slope  of  three  units 
vertical  in  12  units  horizontal  (3:12)  in 
occupancies  in  Use  Group  R-3  and  on  buildings 
with  an  unclassified  roof  covering. 

2.  The  metal  or  noncombustible  edge  material  is 
not  required  where  unclassified  roof  coverings 
are  permitted. 

2608.3  Slope:  Flat  or  corrugated  plastic  skylights 
shall  slope  at  least  four  units  vertical  in  12  units 
horizontal  (4: 12).  Dome-shaped  skylights  shall  rise 
above  the  mounting  flange  a  minimum  distance 
equal  to  10%  of  the  maximum  span  of  the  dome,  but 
not  less  than  three  inches  (76  mm). 

Exception:  Skylights  that  pass  the  Class  B 
Burning  Brand  Test  specified  in  ASTM  El 08 
listed  in  Appendix  A. 

2608.4  Maximum  area  of  skylight  units:  Each 
skylight  unit  shall  have  a  maximum  area  within  the 
curb  of  100  square  feet  (9.30  m2)  except  that  the  area 
of  skylight  units  shall  not  be  limited  in  buildings 
equipped  throughout  with  an  automatic  sprinkler 
system  in  accordance  with  780  CMR  906.2.1. 

2608.5  Aggregate  area  of  skylights:  The  aggregate 
area  of  skylights  shall  not  exceed  33%  of  the  floor 
area  of  the  room  or  space  sheltered  by  the  roof  in 
which  such  skylights  are  installed  where  Class  CI 
materials  are  utilized,  and  25%  where  Class  C2 
materials  are  utilized. 

Exception:  The  aggregate  area  limitations  of 
approved  plastic  skylights  shall  be  increased 
100%  beyond  the  limitations  set  forth  in 
780  CMR  2608.0  where  the  building  is  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2.1 

2608.6  Separation:  Skylights  shall  be  separated 
from  each  other  by  a  distance  of  not  less  than  four 
feet  (1219  mm)  measured  in  a  horizontal  plane, 
except  that  the  separation  shall  not  be  required 
where  the  building  is  equipped  throughout  with  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1. 

2608.7  Location:  Where  exterior  wall  openings  are 
required  to  be  protected  by  780  CMR  705.0,  a 
skylight  shall  not  be  installed  within  six  feet  (1829 
mm)  of  such  exterior  wall. 

2608.8  Combinations  of  roof  panels  and  skylights: 

Combinations  of  plastic  roof  panels  and  skylights 
shall    be    subject    to    the    area    and    percentage 


412 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

PLASTIC 

limitations  and  separation  requirements  applicable  to 
roof  panel  installations. 


2/7/Q7    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  413 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


414  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  27 

ELECTRIC  WIRING,  EQUIPMENT  AND  SYSTEMS 

(780  CMR  27  is  Entirely  Unique  to  Massachusetts) 

2701.0:      M.G.L.  c.  143,  §  3L,  provides  that  all  Code  (527  CMR  12.00)  listed  in  Appendix  A  and 

installation,  repair  and  maintenance  of  wiring  and  promulgated  by  the  Board  of  Fire  Prevention 

electrical  fixtures  used  for  light,  heat  and  power  Regulations       of      the       Commonwealth       of 

purposes  in  buildings  and  structures  shall  be  in  Massachusetts,  Department  of  Public  Safety, 
conformance  with  the  Massachusetts  Electrical 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  415 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


416  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  28 


MECHANICAL  SYSTEMS 


780  CMR  2801.0 

2801.1  Scope:  The  provisions  of  780  CMR  28  shall 
control  the  construction,  inspection  and  maintenance 
of  all  mechanical  equipment  and  systems  with 
respect  to  structural  strength,  fire  safety  and 
operation. 

Note:  Also  see  780  CMR  9,  12  and  13. 

2801.2  Mechanical  code:  All  mechanical  equipment 
and  systems  shall  be  constructed,  installed  and 
maintained  in  accordance  with  the  BOCA  National 
Mechanical  Code  listed  in  Appendix  A. 

2801.2.1  Heating,  Pumping,  Process  Piping 
and  Refrigeration  Systems:  Heating,  pumping, 
process  piping  and  refrigeration  systems  shall  be 
installed  by  contractors  and  personnel 
appropriately  licensed  in  the  Commonwealth  of 
Massachusetts  (Installing  Contractor).  Engineered 
designs  and  specifications  prepared  by  Registered 
Professional  Engineers  shall  identify  systems 
requiring  compliance  with  appropriate  sections  of 
M.G.L.  c.  146  and  528  CMR.  Shop  drawings  and 
design  layout  prepared  by  licensed  installing 
contractors  shall  note  the  name(s),  license 
number(s)  and  license  expiration  date(s)  of  the 
contractor(s)  installing  the  heating,  pumping, 
process  piping  and  refrigeration  systems.  (See 
Installing  Contractor  Definition  780  CMR  202.0). 

780  CMR  2802.0  CONSTRUCTION 
DOCUMENTS 

2802.1  General:  The  construction  documents  for  the 
installation,  repair,  extension  or  removal  of  any 
mechanical  equipment  or  system  shall  be  submitted 
in  accordance  with  780  CMR  1 10.0  and  a  building 
permit  shall  be  secured  prior  to  the  commencement 
of  any  work. 

2802.2  Matter  covered:  The  construction 
documents  shall  show  in  sufficient  detail  all 
applicable  features  and  clearances  of  the  appliances 
and  systems,  including:  size  and  type  of  apparatus; 
construction  of  flue,  stack  or  chimney;  stack 
connections;  type  of  fuel;  method  of  operation;  and 
the  method  of  compliance  with  all  regulations  for  the 
class  and  type  of  equipment  installed. 

2802.3  Details:  An  application  for  a  building  permit 
for  mechanical  systems  shall  be  accompanied  by 
construction  documents  complying  with  the 
provisions  of  the  mechanical  code  listed  in 
Appendix  A  before  a  permit  shall  be  issued  for  the 
mechanical  equipment  or  system.  The  construction 


documents  shall  be  drawn  to  a  scale  of  not  less  than 
Vb  inch  to  the  foot  (1:100).  and  shall  show  the 
location  and  arrangement  of  all  equipment  and 
distribution  elements  including  safeties  and 
pressure-controlling  devices. 

Note:  Also  see  780  CMR  2803.1. 

780  CMR  2803.0  FEES 
2803.1  General:  Fees  for  mechanical  work,  shall  be 
included  in  the  building   permit  application   (see 
780  CMR  1 14.0). 

780  CMR  2804.0  INSPECTIONS  AND  TESTS 

2804.1  Inspection:  All  mechanical  equipment  and 
systems  requiring  a  permit  shall  be  inspected  in 
accordance  with  the  BOCA  National  Mechanical 
Code  listed  in  Appendix  A  and  shall  not  be  placed  in 
operation  until  having  been  tested  and  approved. 

2804.2  Concealment:  It  shall  be  unlawful  for 
owners,  contractors  or  workers  to  lath  over  or  in  any 
way  conceal  any  piping,  outlet  boxes  or  other  parts 
of  the  mechanical  equipment  or  system  requiring  a 
permit  until  an  inspection  has  been  made  thereof  and 
due  notice  has  been  given  that  the  work  has  been 
approved. 

2804.3  Defects  and  repairs:  Upon  inspection  or 
reinspection  of  a  mechanical  system,  any  defects  or 
deficiencies  which  require  repair  to  insure  safe 
operation  shall  be  rectified  before  the  system  is 
placed  in  service. 

2804.4  Power  to  deem  unsafe:  A  system  or  any  part 
thereof  that  is  found  to  be  unsafe  to  life  or  property, 
shall  be  deemed  unsafe  and  shall  not  be  restored  to 
service  until  such  system  has  been  made  safe  and 
approved. 

780  CMR  2805.0  PLENUMS 
2805.1  General:  The  term  "plenum"  shall  mean  an 
enclosed  portion  of  the  building  structure  which 
forms  part  of  an  air  distribution  system  and  is 
designed  to  allow  the  movement  of  air.  Supply, 
return,  exhaust,  relief  and  ventilation  air  plenums 
shall  be  limited  to  uninhabited  crawl  spaces,  areas 
above  a  ceiling  or  below  the  floor,  or  attic  spaces 
and  mechanical  equipment  rooms.  The  location  of 
supply  and  return  air  plenums  shall  also  comply  with 
780  CMR  1005.7.  Plenums  shall  be  limited  to  one 
fire  area.  Fuel-fired  equipment  shall  not  be  installed 
within  a  plenum.  In  buildings  of  Type  I  or  2 
construction,  all  plenums  shall  be  noncombustible 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  shall  comply  with  780  CMR  2805.2.  In 
buildings  of  Type  3,  4  or  5  construction, 
noncombustible  plenums  in  accordance  with 
780  CMR  2805.2,  combustible  plenums  in 
accordance  with  780  CMR  2805.3,  and  stud  and  joist 
space  plenums  in  accordance  with  780  CMR  2805.4, 
shall  be  permitted. 

2805.2  Noncombustible  plenums:  Plenums  shall  be 
constructed  with  noncombustible  material. 
Combustible  material  shall  not  be  exposed  within  a 
plenum  except  as  permitted  in  780  CMR  2805.2.1 
through  2805.2.6. 

2805.2.1  Pipe:  Pipe  shall  be  noncombustible 
except  that  plastic  fire  sprinkler  piping  in  wet  pipe 
systems  shall  be  permitted  where  the  piping  has  a 
peak  optical  density  not  greater  than  0.50,  an 
average  optical  density  not  greater  than  0. 1 5  and 
a  flame  spread  not  greater  than  5.0  feet  (1524 
mm)  when  tested  in  accordance  with  UL  1887 
listed  in  Appendix  A.  Piping  shall  bear  the  label 
of  an  approved  agency. 

2805.2.2  Ceiling  and  thermal  material:  Thermal 
and  acoustical  materials  and  pipe  insulation  shall 
have  a  flame  spread  of  25  or  less  and  a  smoke- 
developed  rating  of  50  or  less  when  tested  in 
accordance  with  ASTM  E84  listed  in  Appendix  A 

2805.2.3  Ducts:  Rigid  or  flexible  ducts  and 
connectors  shall  conform  to  the  mechanical  code 
listed  in  Appendix  A. 

2805.2.4  Duct  coverings:  Duct  coverings,  linings, 
tape  and  connectors  shall  conform  to  the  BOCA 
National  Mechanical  Code  listed  in  Appendix  A. 

2805.2.5  Wire:  Wire  shall  be  low-voltage  or 
power-limited  wire  or  cable.  Wire  shall  have  a 
peak  optical  density  not  greater  than  0.50,  an 
average  optical  density  not  greater  than  0. 1 5  and 
a  flame  spread  of  not  greater  than  five  feet  (1524 
mm)  when  tested  in  accordance  with  UL  910 
listed  in  Appendix  A.  Wire  shall  bear  the  label  of 
an  approved  agency  and  shall  be  marked  in 
accordance  with  527  CMR  12.00  listed  in 
Appendix  A. 

2805.2.6  Combustible     pneumatic     tubing: 

Combustible  pneumatic  tubing  shall  have  a  peak 
optical  density  not  greater  than  0.50,  an  average 
optical  density  not  greater  than  0.15  and  a  flame 
spread  of  not  greater  than  five  feet  (1524  mm) 
when  tested  in  accordance  with  UL  1820  listed  in 
Appendix  A,  and  shall  bear  the  label  of  an 
approved  agency. 

2805.3  Combustible  plenums:  The  plenum  shall  be 
constructed  with  approved  material.  Combustible 
material,  pipe  or  wire  exposed  within  the  plenum 
shall  be  permitted. 


2805.3.1  Size:  Combustible  plenums  shall  be 
draftstopped  every  3,000  square  feet  (279  m2)  in 
area. 

Exception:  Plenums  shall  be  limited  to  one  fire 
area  without  draftstopping  in  buildings 
equipped  throughout  with  an  automatic 
sprinkler  system  in  accordance  with  780  CMR 
906.2.1. 

2805.4  Stud  and  joist  spaces:  The  space  between 
studs  or  joists  shall  not  be  utilized  as  a  plenum  for 
supply  air.  The  space  between  studs  or  joists  utilized 
as  a  plenum  for  return  air  shall  not  be  part  of  a 
required  fireresistance  rated  assembly.  Air  shall  be 
removed  from  one  floor  level  only.  All  connections 
shall  be  firestopped  and  draftstopped. 

780  CMR  2806.0  DRYING  ROOMS 

2806.1  General:  A  drying  room  or  dry  kiln  installed 
within  a  building  shall  be  constructed  entirely  of 
approved  noncombustible  materials  or  assemblies  of 
such  materials  with  the  required  fireresistance  rating 
based  on  the  fire  hazard  of  the  contents  and  the 
process,  as  required  in  780  CMR  4. 

2806.2  Piping  clearance:  All  overhead  heating 
pipes  shall  have  a  clearance  of  not  less  than  two 
inches  (5 1  mm)  from  combustible  contents  of  the 
dryer. 

2806.3  Insulation:  Where  the  operating  temperature 
of  the  dryer  is  175°F  (79°C)  or  more,  metal 
enclosures  shall  be  insulated  from  adjacent 
combustible  materials  by  not  less  than  12  inches 
(305  mm)  of  air  space,  or  the  metal  walls  shall  be 
lined  with  Vi-inch  insulating  mill  board  or  other 
approved  equivalent  insulation. 

2806.4  Fire  protection:  Drying  rooms  designed  for 
high-hazard  materials  and  processes,  including 
special  occupancies  as  provided  for  in  780  CMR  4, 
shall  be  protected  by  an  approved  automatic  fire 
suppression  system  conforming  to  the  provisions  of 
780  CMR  9. 

780  CMR  2807.0  WASTE-  AND  LINEN- 
HANDLING  SYSTEMS 

2807.1  General:  Waste  (refuse)  and  linen  (laundry) 
systems  shall  be  installed  in  accordance  with 
780  CMR  2807.0  and  the  provisions  of  Chapters  3 
and  4  of  NFiPA  82  listed  in  Appendix  A. 

Exception:  Systems  serving  and  contained  within 
a  single  dwelling  unit. 

2807.2  Waste  and  linen  chute  enclosures:  A  shaft 
containing  a  refuse  or  linen  chute  shall  not  be  used 
for  any  other  purpose  and  shall  be  enclosed  in 
accordance  with  780  CMR  710.0.  All  openings  into 
the  shaft,  including  those  from  access  rooms  and 
termination  rooms,  shall  be  protected  with  approved 


418 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MECHANICAL  SYSTEMS 


fireresistance  rated  assemblies.  Such  opening 
protectives  shall  be  self-closing  or  automatic-closing 
upon  detection  of  smoke,  except  that  a  heat-activated 
device  for  closing  the  opening  protective  between 
the  shaft  and  the  termination  room  is  permitted. 

2807.3  Waste   and   linen   chute   access   rooms: 

Access  openings  for  waste  and  linen  chutes  shall  be 
located  in  rooms  or  compartments  which  are 
completely  enclosed  by  fire  separation  assemblies 
having  a  fireresistance  rating  of  not  less  than  one 
hour;  and  openings  into  the  access  rooms  shall  be 
protected  by  fire  doors  that  comply  with  780  CMR 
716.0.  Access  openings  to  waste  and  linen  chutes 
shall  not  be  located  in  exit  access  corridors  or  exit 
enclosures. 

2807.4  Termination  room:  Waste  and  linen  chutes 
shall  discharge  into  an  enclosed  room  that  is 
completely  separated  from  the  remainder  of  the 
building  by  fire  separation  assemblies  having  a 
fireresistance  rating  of  not  less  than  one  hour;  and 
openings  into  the  termination  room  shall  be 
protected  by  fire  doors  that  comply  with  780  CMR 
716.0.  Waste  chutes  shall  not  terminate  in  an 
incinerator  room. 

2807.5  Incinerator  room:  Where  located  within  a 
building,  incinerators  shall  be  enclosed  within  a 
room  that  is  separated  from  the  remainder  of  the 
building  by  fire  separation  assemblies  having  a 
fireresistance  rating  of  not  less  than  two  hours;  and 
openings  into  the  incinerator  room  shall  be  protected 
by  fire  doors  that  comply  with  780  CMR  716.0. 

2807.6  Automatic  fire  suppression:  An  approved 
automatic  fire  suppression  system  shall  be  installed 
at  the  top  and  at  alternate  floor  levels  in  a  waste  or 
linen  chute  and  in  the  termination  and  incinerator 


780  CMR  2808.0  REFUSE  VAULTS 

2808.1  Refuse  vault  enclosures:  A  vault  for 
receiving  combustible  refuse  from  an  exhaust  system 
shall  be  enclosed  with  fire  separation  assemblies 
having  not  less  than  a  three-hour  fireresistance 
rating. 

2808.2  Openings  to  boiler  rooms:  The  opening 
between  a  vault  and  a  boiler  room  shall  not  exceed 
nine  square  feet  (0.84  m2)  in  area  and  shall  be 
located  at  least  eight  feet  (2438  mm)  from  the  firing 
door  of  the  boiler,  and  the  bottom  of  the  opening 
shall  not  be  less  than  six  inches  (152  mm)  above  the 
boiler  room  floor.  All  openings  shall  be  equipped 
vAth  fire  doors  having  a  fire  protection  rating  of  not 
less  than  1  Vi  hours  and  complying  with  780  CMR 
716.0. 

2808.3  Location:  Where  located  within  a  building, 
a  refuse  vault  shall  extend  above  the  roof  or  shall  be 


directly  vented  to  the  outer  air  with  ducts  that 
comply  with  the  BOCA  National  Mechanical  Code 
listed  in  Appendix  A. 

2808.4  Fire  protection:  A  vault  for  combustible 
refuse  which  exceeds  360  cubic  feet  (10  m3)  in 
volume  shall  be  protected  by  an  approved  automatic 
fire  suppression  system  that  conforms  to  780  CMR 
9. 

780  CMR  2809.0  MEDICAL  GASES 

2809.1  Nonflammable         medical         gases: 

Nonflammable  medical  gas  systems  shall  be 
designed  and  installed  in  accordance  with  Chapter  4 
of  NFiPA  99  listed  in  Appendix  A. 

2809.2  Anesthetic  systems:  Inhalation  anesthetic 
systems  shall  be  designed  and  installed  in 
accordance  with  Chapters  3  and  4  of  NFiPA  99 
listed  in  Appendix  A. 

780  CMR  2810.0  OXYGEN  SYSTEMS 

2810.1  General:  Nonmedical  oxygen  systems  shall 
be  designed  and  installed  in  accordance  with  NFiPA 
50  and  NFiPA  5 1  listed  in  Appendix  A. 

780  CMR  2811.0  EXISTING  BUILDINGS 

2811.1  Unsafe  orders:  All  existing  mechanical 
equipment  and  systems  shall  be  maintained  and 
operated  in  accordance  with  the  requirements  of  this 
code  and  the  BOCA  National  Mechanical  Code 
listed  in  Appendix  A.  Any  such  equipment  which 
does  not  comply  with  the  requirements,  and  the 
operation  of  which  is  deemed  unsafe  to  the  building 
occupants,  shall  be  altered  as  ordered  by  the  code 
official  to  secure  adequate  safety. 

Note:  Also  see  780  CMR  3400.6. 

780  CMR  28110  POWER  VENTERS 
2812.1  Power  vented  systems  used  for  the  venting 
of  comfort  heating  and/or  comfort  cooling 
appliances:  Power  venters  are  a  portion  of  a 
venting  system  using  a  fan  or  other  mechanical 
means  to  cause  the  removal  of  flue  or  vent  gases 
under  positive  static  vent  pressure.  Power  venting 
of  comfort  heating  and/or  comfort  cooling 
appliances  may  be  accomplished  via  the  use  of 
power  venting  systems  that  are  separately  listed 
systems  or  are  an  integral  part  of  the  listed  heating 
or  cooling  appliances.  Such  listed  systems  are 
equipment  that  have  been  tested  for  intended 
design  conditions  by  established  and  recognized 
agencies  regularly  engaged  in  conducting  tests  or 
furnishing  testing/listing  services.  Such  listed 
equipment  will  typically  hear  a  plate,  label  or  other 
means  of  identification  indicating  the  listing 
agency,  conditions  of  operation  and  other  pertinent 
information. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


419 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


281 Z  1.1  Regulations  of  the  Specialized  Codes 
impacting  the  acceptable  design,  installation, 
operation  and  maintenance  of  power  vented 
equipment:  The  Specialized  Codes  (780  CMR 
101.5)  including  248  CMR:  BOARD  OF  STATE 
EXAMINERS  OF  PLUMBERS  AND  GAS 
FITTERS,  and  527  CMR:  BOARD  OF  FIRE 
PREVENTION  REGULATIONS,  and  not 
enforced  by  Building  Officials  but  rather 
enforced  by  Plumbing/Gas  Inspectors  and  Fire 
Service  Personnel,  respectively,  have  specific 
criteria  imposed  on  power  vented  appliances 
beyond  those  regulations  included  herein. 

2812.2  Automatic  safe  shutoff:  Power  venters 
shall  operate  in  such  a  manner  and  be  electrically 
connected  to  the  comfort  heating  and/or  comfort 
cooling  appliances  in  such  a  way  as  to  prevent  the 
operation  of  such  appliances  when  the  power 
venter  is  not  in  operation  or  is  not  providing 
sufficient  draft  for  the  appliance  being  vented. 

2812.3  Installation  of  power  vented  equipment- 
Power  vented  equipment  shall  be  installed  in 
accordance  with  the  manufacturer's  installation 
manual  and  instructions  (typically,  only  personnel 
trained  in  the  installation  of  such  equipment  are 
accepted  by  the  manufacturer  as   qualified  to 


install).  Power  venters  shall  be  selected  to  match 
the  venting  requirements  of  the  equipment  being 
vented  in  accordance  with  the  manufacturers' 
requirements. 

2812.4  Termination:  The  vent  system  shall 
terminate  so  that  proper  clearances  are  maintained 
in  accordance  with  the  requirements  of  248  CMR 
or  527  CMR  when  applicable  or  in  accordance  with 
the  manufacturer's  listed  requirements  when 
248  CMR  or  527  CMR  are  not  applicable. 

2812.5  Other  applications  of  power  exhausters: 
For  applications  of  power  exhausters  for  other 
than  the  venting  of  comfort  heating  appliances 
and/or  comfort  cooling  appliances,  the 
requirements  of  the  BOCA  Mechanical  Code,  listed 
in  Appendix  A,  shall  apply,  as  well  as  any 
additional  regulatory  criteria  set  forth  in  any  of  the 
Specialized  Codes. 

2813. 0  SOLID  FUEL-FIRED  APPLIANCES 

2813.1  Solid  fuel-fired  appliances,  general:  For 

requirements  addressing  solid  fuel-fired  appliances 
see  780  CMR  3610.6. 


420 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  29 

PLUMBING  SYSTEMS 

(780  CMR  29  is  Entirely  Unique  to  Massachusetts) 

2901.0  M.G.L.    c.   142,  §  13  provides  that  all  2901.1     Other    Laws    and    Regulations:    Fire 

construction,  alteration,  repair  and  inspection  of  protection,  heating,  pumping,  process  piping  and 

plumbing  and  gasfitting  shall  be  in  conformance  refrigeration  systems  arc  required  to  be  installed  by 

with   the  Massachusetts  State  Plumbing   Code  contractors  and  personnel  appropriately  licensed  in 

(248  CMR  2. 00)  and  the  Massachusetts  Fuel  Gas  the  Commonwealth  of  Massachusetts  (Installing 

Code  (248  CMR  3.00  through  8.00),  listed  in  Contractor).  (See  Installing  Contractor  Definition 

Appendix  A,  and  promulgated  by  the  Board  of  780  CMR,  202. 0). 
State  Examiners  of  Plumbers  and  Gasfitters. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  421 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


422  '80  CMR  -Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  30 

ELEVATORS 

(This  Chapter  is  Entirely  Unique  to  Massachusetts) 

780  CMR  3001.0  GENERAL  Elevator  Regulations  of  the    Commonwealth   of 

300  J.  1  M.G.L.  c.  143,  §  69  as  amended,  provides  Massachusetts,  Department  of  Public  Safety, 
that  elevators  and  similar  equipment  shall  conform 

to  the   Elevator  Regulations  524  CMR  as  listed  in  300L2  Shafi  construction  shall  be  in  accordance 

Appendix  A  and  promulgated  by  the  Board  of  ™th  the  applicable  provisions  of  780  CMR. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  423 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


424  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2828/97) 


CHAPTER  31 


SPECIAL  CONSTRUCTION 


780  CMR  3101.0  GENERAL 
3101.1  Scope:  In  addition  to  the  general 
requirements  of  780  CMR  governing  the  design  and 
construction  of  all  structures,  the  provisions  of 
780  CMR  3 1  shall  control  the  special  structures  and 
construction  features  as  herein  provided 

780  CMR  3102.0  SIGNS 

3102.1  General:  The  provisions  of  780  CMR  3 102.0 
shall  govern  the  construction,  alteration,  repair  and 
maintenance  of  all  signs  together  with  the  associated 
appurtenant  and  auxiliary  devices  in  respect  to 
structural  and  fire  safety. 

3102.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3102.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Sign:  Any  fabricated  sign  or  outdoor  display 
structure,  including  its  structure,  consisting  of  any 
letter,  figure,  character,  mark,  point,  plane, 
marquee  sign,  design,  poster,  pictorial,  picture, 
stroke,  stripe,  line,  trademark,  reading  matter  or 
illuminating  device,  which  is  constructed, 
attached,  erected,  fastened  or  manufactured  in  any 
manner  so  that  the  same  shall  be  used  for  the 
attraction  of  the  public  to  any  place,  subject, 
person,  firm,  corporation,  public  performance, 
article,  machine  or  merchandise,  and  displayed  in 
any  manner  out  of  doors  for  recognized 
advertising  purposes. 

Closed  sign:  A  sign  in  which  more  than  50%  of 
the  entire  area  is  solid  or  tightly  enclosed  or 
covered. 

Ground  sign:  A  sign  supported  by  uprights  or 
braces  in  or  upon  the  ground  surface. 
Marquee  sign:  A  57077  attached  to  or  hung  from  a 
marquee,  canopy  or  other  covered  structure, 
projecting  from  and  supported  by  the  building  and 
extending  beyond  the  building  wall,  building  line 
or  street  lot  line. 

Open  sign:  A  sign  in  which  at  least  50%  of  the 
enclosed  area  is  uncovered  or  open  to  the 
transmission  of  wind. 

Portable  sign:  A  s;g77,  usually  of  a  temporary 
nature,  not  securely  anchored  to  the  ground  or  to 
a  building  or  structure  and  which  obtains  some  or 
all  of  its  structural  stability  with  respect  to  wind 
or  other  normally  applied  forces  by  means  of  its 
geometry  or  character. 

Projecting  sign:  A  display  sign  which  is  attached 
directly  to  the  building  wall,  and  which  extends 


more  than  15  inches  (381  mm)  from  the  face  of 
the  wall. 

Roof  sign:  A  sign  which  is  erected,  constructed 
and  maintained  above  the  roof  of  the  building. 
Temporary  sign:  A  sign  constructed  of  cloth, 
fabric  or  other  lightweight  temporary  material 
with  or  without  a  structural  frame  intended  for  a 
limited  period  of  display,  including  decoration 
displays  for  holidays  or  public  demonstrations. 
Wall  sign:  A  sign  which  is  painted  on  or  attached 
directly  to  a  fence  or  on  the  surface  of  masonry, 
concrete,  frame  or  other  approved  building  walls, 
and  which  extends  not  more  than  15  inches  (381 
mm)  from  the  face  of  the  fence  or  wall. 

3102.3  Zoning  law:  Where  more  restrictive  in 
respect  to  location,  purpose,  size  or  height  of  signs, 
the  limitations  of  zoning  laws  that  affect  occupancy 
of  land  shall  take  precedence  over  the  regulations  of 
780  CMR. 

In  the  absence  of  approved  rules  governing 
details  of  construction,  the  provisions  of  the 
applicable  standards  listed  in  Appendix  A  shall  be 
deemed  to  conform  to  the  requirements  of 
780  CMR  unless  otherwise  specified  in  780  CMR 
31. 

Outdoor  advertising  subject  to  711  CMR  3.00: 
Control  and  Restriction  of  Billboards,  Signs  and 
Other  Advertising  Devices  (the  Outdoor 
Advertising  Board)  as  listed  in  Appendix  A,  and  in 
accordance  with  Massachusetts  General  Laws 
Annotated,  as  amended,  requires  approval  of  said 
Board  prior  to  the  issuance  of  a  permit 

3102.4  Permits    and    construction   documents: 

Permits  for  signs  shall  be  required  as  specified  in 
780  CMR  3 102.4. 1  and  3 102.4.2  except  as  provided 
for  in  780  CMR  3 102.4.3.  Construction  documents 
shall  be  prepared  and  filed  in  accordance  with 
780  CMR  3 102.4.4  and  3102.4.5. 

3102.4.1  New  signs:  A  new  sign  shall  not 
hereafter  be  erected,  constructed,  altered  or 
maintained  except  as  provided  for  herein,  and 
until  a  permit  has  been  issued  by  the  code  official 

3102.4.2  Alterations:  A  sign  shall  not  be 
enlarged  or  relocated  unless  such  sign  conforms 
to  the  provisions  of  780  CMR  3102.0  for  new 
signs,  or  until  a  proper  permit  has  been  secured 
The  changing  of  movable  parts  of  an  approved 
sign  that  is  designed  for  such  changes,  or  the 
repainting  or  reposting  of  display  matter,  shall  not 
be  deemed  an  alteration,  provided  that  the 
conditions  of  the  original  approval  and  the 
requirements  of  780  CMR  3 102  0  are  not  violated 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


425 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3102.4.3  Permit  exemptions:  A  permit  shall  not  be 
required  for  the  signs  specified  in  780  CMR 
3102.4.3.1  through  3102.4.3.5.  Such  exceptions, 
however,  shall  not  be  construed  to  relieve  the  owner 
of  the  sign  from  responsibility  for  the  sign's  erection 
and  maintenance  in  a  safe  manner. 

3102.4.3.1  Wall  signs:  A  permit  shall  not  be 
required  for  a  sign  painted  on  the  surface  of  a 
fence  or  approved  building  wall,  or  any 
nonilluminated  wall  sign  on  a  building  or 
structure  which  is  not  more  than  ten  square  feet 
(0.93  m2)  in  area. 

3102.4.3.2  Sale  or  rent:  A  permit  shall  not  be 
required  for  ground  signs  erected  to  announce 
the  sale  or  rent  of  property,  provided  that  such 

•     signs  are  not  more  than  25  square  feet  (2.33 
nr)  in  area. 

3102.4.3.3  Transit  directions:  A  permit  shall 
not  be  required  for  the  erection  or  maintenance 
of  a  ground  sign  designating  the  location  of  a 
transit  line,  a  railroad  station  or  other  public 
carrier  provided  that  such  signs  are  not  more 
than  three  square  feet  (0.28  m2)  in  area. 

3102.4.3.4  Street  signs:  A  permit  shall  not  be 
required  for  ground  signs  erected  by  a 
jurisdiction  for  street  direction. 

3102.4.3.5  Projecting  signs:  A  permit  shall 
not  be  required  for  a  projecting  sign  not 
exceeding  2Vi  square  feet  (0.23  m2)  of  display 
surface. 

3102.4.3.6  Government  building  signs:  Signs 
erected  on  a  municipal,  state  or  federal 
building  which  announce  the  name,  nature  of 
the  occupancy  and  information  as  to  use  of, 
or  admission  to  the  premises. 

3102.4.4  Construction  documents  and  owner's 
consent:  Before  any  permit  is  issued  for  the 
erection  of  a  sign,  construction  documents  shall 
be  filed  with  the  code  official  showing  the 
dimensions,  materials  and  required  details  of 
construction,  including  loads,  stresses  and 
anchorage.  The  applications  shall  be 
accompanied  by  the  written  consent  of  the  owner 
or  lessee  of  the  premises  upon  which  the  sign  is  to 
be  erected. 

3102.4.5  Identification  Every  sign  for  which  a 
permit  has  been  issued  and  which  is  hereafter 
erected,  constructed  or  maintained,  shall  be 
plainly  marked  with  the  name  of  the  person,  firm 
or  corporation  owning,  erecting,  maintaining  or 
operating  such  sign.  The  method  and  location  of 
this  identification  shall  appear  on  the  construction 
documents  filed  with  the  code  official. 

3102.5  Maintenance  and  inspection:  Sign 
maintenance  and  inspection  shall  comply  with 
780  CMR  3102.5. 1  through  3102.5.4. 


3102.5.1  Removal:  The  code  official  is 
authorized  to  order  the  removal  of  any  sign  that  is 
not  maintained  in  accordance  with  the  provisions 
of  780  CMR  3102.0. 

3102.5.2  Maintenance:  All  signs  for  which  a 
permit  is  required,  together  with  all  supports, 
braces,  guys  and  anchors,  shall  be  kept  in  repair  in 
accordance  with  the  provisions  of  780  CMR 
3102.0  and  780  CMR  1  Where  not  galvanized  or 
constructed  of  approved  corrosion-resistant 
noncombustible  materials,  signs  shall  be  painted. 

3102.5.3  Housekeeping:  The  owner  or  lessee  of 
every  sign  shall  maintain  the  immediate  premises 
occupied  by  the  sign  in  a  clean,  sanitary  and 
healthful  condition 

3102.5.4  Inspection:  Every  sign  shall  be  subject 
to  inspection  and  approval 

3102.6  General  requirements:  All  signs  shall  be 
designed  and  constructed  to  comply  with  the 
provisions  of  780  CMR  for  materials,  loads  and 
stresses,  and  with  the  requirements  of  780  CMR 
3102.6.1  through  3102.6  5 

3102.6.1  Wind  load:  All  signs  shall  be  designed 
and  constructed  to  withstand  wind  pressure  as 
provided  for  in  780  CMR  1611.12.2 

3102.6.2  Earthquake  load:  Signs  designed  to 
withstand  wind  pressures  shall  be  considered 
capable  of  withstanding  earthquake  loads,  except 
as  provided  for  in  780  CMR  1612.0  and  1616  0. 

3102.6.3  DIumination:  A  sign  shall  not  be 
illuminated  by  other  than  electrical  means,  and 
electrical  devices  and  wiring  shall  be  installed  in 
accordance  with  the  requirements  of  527  CMR 
12.00  listed  in  Appendix  A  Any  open  spark  or 
flame  shall  not  be  used  for  display  purposes 
unless  specifically  approved. 

3102.6.4  Use  of  combustibles:  The  requirements 
of  780  CMR  3102.6.4.1  and  3102.6.4.2  shall 
apply  to  combustible  material  for  signs. 

3102.6.4.1  Ornamental  features:  Wood  or 
approved  plastic  as  provided  for  in  780  CMR 
26,  or  other  materials  of  combustible 
characteristics  similar  to  wood,  used  for 
moldings,  cappings,  nailing  blocks,  letters  and 
latticing,  shall  comply  with  780  CMR  3102.7, 
and  shall  not  be  used  for  other  ornamental 
features  of  signs,  unless  approved. 

3102.6.4.2  Internally  illuminated  signs: 
Except  as  provided  for  malls  in  780  CMR 
402. 14,  where  internally  illuminated  signs  have 
sign  facings  of  wood  or  approved  combustible 
plastic,  the  area  of  such  facing  section  shall  not 
be  more  than  1 20  square  feet  (11.16  m2)  and 
the  wiring  for  electric  lighting  shall  be  entirely 
enclosed  in  the  sign  cabinet  with  a  clearance  of 
not  less  than  two  inches  (51  mm)  from  the 


426 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  CONSTRUCTION 


facing  material.  The  dimensional  limitation  of 
120  square  feet  (11.16  m2)  shall  not  apply  to 
sign  facing  sections  made  from  flameresistant- 
coated  fabric  (ordinarily  known  as  "flexible 
sign  face  plastic")  that  weighs  less  than  20 
ounces  per  square  yard  (678  g/m2)  and  which, 
when  tested  in  accordance  with  NFiPA  701 
listed  in  Appendix  A  meets  the  requirements  of 
both  the  small-scale  test  and  the  large-scale 
test,  or  which,  when  tested  in  accordance  with 
the  requirements  of  ASTM  D568  listed  in 
Appendix  A,  exhibits  an  average  burn  time  for 
ten  specimens  of  two  seconds  or  less  and  a 
burning  extent  of  1 5  centimeters  or  less. 

3102.6.5  Animated  devices:  Signs  that  contain 
moving  sections  or  ornaments  shall  have  fail- 
safe provisions  to  prevent  the  section  or 
ornament  from  releasing  and  falling  or  shifting 
its  center  of  gravity  more  than  15  inches  (381 
mm).  The  fail-safe  device  shall  be  in  addition 
to  the  mechanism  and  the  mechanism's  housing 
which  operate  the  movable  section  or 
ornament.  The  fail-safe  device  shall  be 
capable  of  supporting  the  full  dead  weight  of 
the  section  or  ornament  when  the  moving 
mechanism  releases. 

3102.7  Ground  signs:  The  structural  frame  of 
ground  signs  shall  not  be  erected  of  combustible 
materials  to  a  height  of  more  than  35  feet  (10668 
mm)  above  the  ground.  In  all  locations,  where 
constructed  entirely  of  noncombustible  material, 
ground  signs  shall  not  be  erected  to  a  height  of 
greater  than  100  feet  (30480  mm)  above  the  ground. 
Greater  heights  are  permitted  where  approved  and 
located  so  as  not  to  create  a  hazard  or  danger  to  the 
public. 

3102.8  Roof  signs:  Roof  signs  shall  comply  with 
780  CMR  3102.8.1  through  3102.8.4. 

3102.8.1  Materials:  All  roof  signs  shall  be 
constructed  entirely  of  metal  or  other  approved 
noncombustible  material  except  as  provided  for  in 
780  CMR  3 102.6.4.  Provisions  shall  be  made  for 
electric  grounding  of  all  metallic  parts.  Where 
combustible  materials  are  permitted  in  letters  or 
other  ornamental  features,  all  wiring  and  tubing 
shall  be  kept  free  and  insulated  therefrom. 

3102.8.2  Bottom  clearance:  There  shall  be  a 
clear  space  of  not  less  than  six  feet  (1829  mm) 
between  the  lowest  part  of  the  sign  and  the  roof 
level,  except  for  necessary  structural  supports. 

3102.8.3  Closed  signs:  A  closed  roof  sign  shall 
not  be  erected  to  a  height  greater  than  50  feet 
(15240  mm)  above  the  roof  of  buildings  of 
Types  1  and  2  construction,  nor  more  than  35  feet 
(1066S  mm)  above  the  roof  of  buildings  of 
Types  3,  4  and  5  construction. 


3102.8.4  Open  signs:  An  open  roof  sign  shall  not 
exceed  a  height  of  100  feet  (30480  mm)  above  the 
roof  of  buildings  of  Types  1  and  2  construction; 
and  not  more  than  60  feet  (18288  mm)  above  the 
roof  of  buildings  of  Types  3,  4  and  5  construction. 

3102.9  Wall  signs:  Wall  signs  shall  comply  with 
780  CMR  3  102.9.1  and  3  102.9.2. 

3102.9.1  Materials:  Wall  signs  which  have  an 
area  exceeding  40  square  feet  (3.72  nr)  shall  be 
constructed  of  metal  or  other  approved 
noncombustible  material,  except  for  nailing  rails 
and  as  provided  for  in  780  CMR  3 1 02.6.4. 

3102.9.2  Extension:  Wall  signs  shall  not  be 
erected  to  extend  above  the  top  of  the  wall,  nor  to 
extend  beyond  the  ends  of  the  wall  to  which  the 
signs  are  attached  unless  such  signs  conform  to  all 
of  the  requirements  for  roof  signs,  projecting 
signs  or  ground  signs. 

3102.10  Projecting  signs:  Projecting  signs  shall 
comply  with  780  CMR  3102.10.1  through 
3102.10.4. 

3102.10.1  Materials:  Projecting  signs  shall  be 
constructed  entirely  of  metal  or  other  approved 
noncombustible  material  except  as  provided  for  in 
780  CMR  3  102.6.4. 

3102.10.2  Maximum  projection:  A  projecting 
sign  shall  not  extend  beyond  a  vertical  plane  that 
is  two  feet  (610  mm)  inside  the  curb  line. 

3102.10.3  Clearance:  A  vertical  clearance  of  not 
less  than  eight  feet  (2438  mm)  shall  be  provided 
below  all  parts  of  projecting  signs. 

3102.10.4  Additional  loads:  Projecting  sign 
structures  which  will  be  used  to  support  an 
individual  on  a  ladder  or  other  servicing  device  - 
whether  or  not  specifically  designed  for  the 
servicing  device  -  shall  be  capable  of  supporting 
the  anticipated  additional  load,  but  not  less  than  a 
100-pound  (45.4  kg)  concentrated  horizontal  load 
and  a  300-pound  (136.2  kg)  concentrated  vertical 
load  applied  at  the  point  of  assumed  or  most 
eccentric  loading.  The  building  component  to 
which  the  projecting  sign  is  attached  shall  also  be 
designed  to  support  the  additional  loads. 

3102.11  Marquee  signs:  Marquee  signs  shall 
comply  with  780  CMR  3102.11.1  through 
3102.11.3. 

3102.11.1  Materials:  Marquee  signs  shall  be 
constructed  entirely  of  metal  or  other  approved 
noncombustible  material  except  as  provided  for  in 
780  CMR  3 102.6.4. 

3102.11.2  Attachment:  Marquee  signs  shall  be 
attached  to  approved  marquees  that  are 
constructed  in  accordance  with  780  CMR 
3203.11. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


427 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3102.11.3  Dimensions:  Marquee  signs  shall  not 
project  beyond  the  perimeter  of  the  marquee. 

3102.12  Temporary  signs:  Temporary  signs  shall 
comply  with  780  CMR  3102.12.1  through 
3102.12.4. 

3102.12.1  Banner  and  cloth  signs:  Temporary 
signs  and  banners  which  are  attached  to  or 
suspended  from  a  building,  and  which  are 
constructed  of  cloth  or  other  combustible 
material,  shall  be  constructed  in  an  approved 
manner  and  shall  be  securely  supported.  Such 
signs  and  banners  shall  be  removed  as  soon  as 
torn  or  damaged,  and  not  later  than  60  days  after 
erection.  Permits  for  temporary  signs  that  are 
suspended  from  or  attached  to  a  canopy  or 
marquee  shall  be  limited  to  a  period  often  days. 

3102.12.2  Maximum  size:  Temporary  signs  of 
combustible  construction  shall  not  be  more  than 
10  feet  (3048  mm)  in  one  dimension  nor  more 
than  500  square  feet  (46.5  m2)  in  area. 

3102.12.3  Supports:  Where  more  than  100  square 
feet  (9.3  m2)  in  area,  temporary  signs  and  banners 
shall  be  constructed  and  fastened  to  supports  that 
are  capable  of  withstanding  the  design  loads  listed 
in  780  CMR  1610.0. 

3102.12.4  Special  permits:  Temporary  signs  used 
for  holidays,  public  demonstrations  or  promotions 
of  civic  welfare  or  charitable  purposes,  which 
extend  across  streets  or  other  public  spaces  shall 
be  subject  to  special  approval  of  the  authority 
having  jurisdiction. 

3102.13  Illuminated  signs:  Illuminated  signs  shall 
comply  with  780  CMR  3102.13.1  through 
3102.13.3. 

3102.13.1  Certificates:  All  electrically 
illuminated  signs  shall  be  certified  as  to  electric 
wiring  and  devices  by  the  agency  having 
jurisdiction,  and  all  wiring  and  accessory 
electrical  equipment  shall  conform  to  the 
requirements  of  527  CMR  12.00  listed  in 
Appendix  A. 

3102.13.2  Additional  permits:  Electrical  permits 
shall  be  issued  for  the  erection  or  maintenance  of 
illuminated  signs. 

3102.13.3  Relettering  signs:  The  requirements  of 
780  CMR  3102.13  shall  not  apply  to  the 
relettering  of  illuminated  signs,  except  where  such 
relettering  requires  a  change  of  wiring  or  piping 
of  the  sign. 

3102.14  Portable  signs:  Portable  signs  shall 
conform  to  all  requirements  for  ground,  roof, 
projecting,  flat  and  temporary  signs  where  such 
signs  are  used  in  a  similar  capacity.  The 
requirements  of  780  CMR  3102.14  shall  not  be 


construed  to  require  portable  signs  to  have 
connections  to  surfaces,  tie-downs  or  foundations 
where  provisions  are  made  by  temporary  means  or 
configuration  of  the  structure  to  provide  stability  for 
the  expected  duration  of  the  installation. 

3102.14.1  Electrical:  Portable  signs  that  require 
electrical  service  shall  have  a  positive  connecting 
device  on  the  sign.  Electrical  service  lines  to  the 
sign  shall  be  protected  from  damage  from  all 
anticipated  traffic. 

780  CMR  3103.0  MEMBRANE  STRUCTURES 

3103.1  General:  The  provisions  of  780  CMR  3 103.0 
shall  apply  to  air-supported,  air-inflated,  membrane- 
covered  cable  and  membrane-covered  frame 
structures,  collectively  known  as  membrane 
structures,  erected  for  a  period  of  90  days  or  longer. 
Those  erected  for  a  shorter  period  of  time  shall 
comply  with  the  applicable  provisions  of  the  fire 
prevention  code,  527  CMR,  listed  in  Appendix  A 
and  780  CMR  3104.0.  Membrane  structures 
covering  water  storage  facilities,  water  clarifiers, 
water  treatment  plants,  sewage  treatment  plants  and 
similar  facilities  not  used  for  human  occupancy,  are 
required  to  meet  only  the  requirements  of  780  CMR 
3103.3.2  and  3103.6. 

3103.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3103.0  and  as 
used  elsewhere  in  780  CMR,  have  the  meanings 
shown  herein. 

Membrane:  As  it  pertains  to  membrane  structures,  a 
thin,  flexible,  impervious  material  capable  of 
being  supported  by  an  air  pressure  of  1.5  inches  of 
water  column  (373  P). 

Membrane  structures 

Air-inflated  structure:  A  building  where  the 
shape  of  the  structure  is  maintained  by  air 
pressurization  of  cells  or  tubes  to  form  a  barrel 
vault  over  the  usable  area.  Occupants  of  such  a 
structure  do  not  occupy  the  pressurized  area  used 
to  support  the  structure. 

Air-supported  structure:  A  building  wherein  the 
shape  of  the  structure  is  attained  by  air  pressure 
and  occupants  of  the  structure  are  within  the 
elevated  pressure  area.  Air-supported  structures 
are  of  two  basic  types: 

Double  skin:  Similar  to  a  single  skin,  but  with 
an  attached  liner  that  is  separated  from  the 
outer  skin  and  provides  an  air  space  which 
serves  for  insulation,  acoustic,  aesthetic  or 
similar  purposes. 

Single  skin:  Where  there  is  only  the  single 

outer  skin  and  the  air  pressure  is  directly 

against  that  skin. 

Cable-restrained,  air-supported  structure:  A 

structure  in  which  the  uplift  is  resisted  by  cables 

or    webbings    which    are    anchored    to    either 


428 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  CONSTRUCTION 


foundations  or  dead  men.  Reinforcing  cable  or 
webbing  is  attached  by  various  methods  to  the 
membrane  or  is  an  integral  part  of  the  membrane. 
This  is  not  a  cable-supported  structure. 
Membrane-covered  cable  structure:  A 
nonpressurized  structure  in  which  a  mast  and 
cable  system  provides  support  and  tension  to  the 
membrane  weather  barrier  and  the  membrane 
imparts  structural  stability  to  the  structure. 
Membrane-covered  frame  structure:  A 
nonpressurized  building  wherein  the  structure  is 
composed  of  a  rigid  framework  to  support 
tensioned  membrane  which  provides  the  weather 
barrier. 

Noncombustible  membrane  structure:  A 
membrane  structure  in  which  the  membrane  and 
all  component  parts  of  the  structure  are 
noncombustible. 

Tent:  Anv  structure,  enclosure  or  shelter  which  is 
constructed  of  canvas  or  pliable  material 
supported  in  any  manner  except  by  air  or  the 
contents  it  protects. 

3103.3  Construction  requirements  Construction 
of  membrane  structures  shall  comply  with  780  CMR 
3103.3.1  through  3103.3.5. 

3103.3.1  Type       of       construction        All 

noncombustible  membrane  structures  shall  be 
classified  as  Type  2C  Noncombustible  frame-  or 
cable-supported  structures  covered  by  an 
approved  membrane  in  accordance  with  780  CMR 

3103.3.2  shall  be  classified  as  Type  2C 
construction.  Heavy  timber  frame-supported 
structures  covered  by  an  approved  membrane  in 
accordance  with  780  CMR  3103.3.2  shall  be 
classified  as  Type  3B  construction.  A 
noncombustible  membrane  structure  that  is  used 
exclusively  as  a  roof  and  is  located  more  than  20 
feet  (6096  mm)  above  any  floor,  balcony  or 
gallery,  is  deemed  to  comply  with  the  roof 
construction  requirements  for  Type  1  and  Type  2 
construction,  provided  that  such  a  structure 
complies  with  the  requirements  of  780  CMR 
3103  All  other  membrane  structures  shall  be 
classified  as  Type  5B  construction. 

3103.3.2  Membrane  material:  Membranes  shall 
be  either  noncombustible  as  defined  by  780  CMR 
704.4,  or  flameresistant  as  determined  in 
accordance  with  both  the  small-scale  and  large- 
scale  tests  in  NFiPA  701  listed  in  Appendix  A 

Exception:  Plastic  less  than  20  mil  (500  um) 
in  thickness,  used  in  greenhouses  where 
occupancy  by  the  general  public  is  not 
permitted  and  for  aquaculture  pond  covers,  is 
not  required  to  be  flameresistant. 

3103.3.3  Applicability    of   other    provisions: 

Except  as  otherwise  specifically  required  by 
780  CMR  3103.3,  membrane  structures  shall  meet 
all   applicable  provisions  of  780   CMR.      The 


membrane  shall  meet  the  roof  covering 
requirements  of  780  CMR  1506.0. 

3103.3.4  Allowable  floor  areas:  The  area  of  a 
membrane  structure  shall  not  exceed  the 
limitations  set  forth  in  Table  503,  except  as 
provided  for  in  780  CMR  506.0. 

3103.3.5  Maximum  height:  Membrane  structures 
shall  not  exceed  one  story  nor  shall  such 
structures  exceed  the  height  limitations  in  feet  set 
forth  in  Table  503 

Exception:  Noncombustible  membrane 
structures  that  serve  as  roof  construction  only 

3103.4  Inflation  systems:  Air-supported  and  air- 
inflated  structures  shall  be  provided  with  primary 
and  auxiliary  inflation  systems  to  meet  the  minimum 
requirements  of  780  CMR  3103.4.1  and  3103.4.2. 

3103.4.1  Equipment  requirements:  The  inflation 
system  shall  consist  of  one  or  more  blowers  and 
shall  include  provisions  for  automatic  control  to 
maintain  the  required  inflation  pressures.  The 
system  shall  be  so  designed  as  to  prevent 
overpressurization  of  the  system. 

In  addition  to  the  primary  inflation  system,  in 
buildings  exceeding  1,500  square  feet  (140  m2)  in 
area,  an  auxiliary  inflation  system  shall  be 
provided  with  sufficient  capacity  to  maintain  the 
inflation  of  the  structure  in  case  of  primary  system 
failure.  The  auxiliary  inflation  system  shall 
operate  automatically  when  there  is  a  loss  of 
internal  pressure  and  when  the  primary  blower 
system  becomes  inoperative 

Blower  equipment  shall  meet  the  following 
requirements: 

1 .  Blowers  shall  be  powered  by  continuous- 
rated  motors  at  the  maximum  power  required 
for  any  flow  condition  as  required  by  the 
structural  design. 

2.  Blowers  shall  be  provided  with  inlet 
screens,  belt  guards  and  other  protective 
devices  as  required  by  the  code  official  to 
provide  protection  from  injury. 

3.  Blowers  shall  be  housed  within  a  weather- 
protecting  structure. 

4.  Blowers  shall  be  equipped  with  backdraft 
check  dampers  to  minimize  air  loss  when 
inoperative 

5.  Blower  inlets  shall  be  located  to  provide 
protection  from  air  contamination  The 
location  of  inlets  shall  be  approved. 

3103.4.2  Standby  power:  Wherever  an  auxiliary 
inflation  system  is  required,  an  approved  standby 
power-generating  system  shall  be  provided.  The 
system  shall  be  equipped  with  a  suitable  means 
for  automatically  starting  the  generator  set  upon 
failure  of  the  normal  electrical  service  and  for 
automatic  transfer  and  operation  of  all  of  the 
required  electrical  functions  at  full  power  within 
60   seconds  of  such  service  failure       Standby 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


429 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


power  shall  be  capable  of  operating  independently 
for  a  minimum  of  four  hours. 

3103.5  Support  provisions:  A  system  capable  of 
supporting  the  membrane  in  the  event  of  deflation 
shall  be  provided  for  in  all  air-supported  and  air- 
inflated  structures  having  an  occupant  load  of  more 
than  50  or  where  covering  a  swimming  pool 
regardless  of  occupant  load.  The  support  system 
shall  be  capable  of  maintaining  membrane  structures 
used  as  a  roof  for  Type  1  or  Type  2  construction  not 
less  than  20  feet  (6096  mm)  above  floor  or  seating 
areas.  The  support  system  shall  be  capable  of 
maintaining  all  other  membranes  at  least  seven  feet 
(2134  mm)  above  the  floor,  seating  area  or  surface 
of  the  water. 

3103.6  Engineering  design:  All  membrane 
structures  shall  be  structurally  designed  in 
accordance  with  approved  criteria  that  are  developed 
by  a  registered  design  professional. 

780  CMR  3104.0  TEMPORARY 
STRUCTURES 

3104.1  General:  The  provisions  of  780  CMR  3104.0 
shall  apply  to  tents,  membrane  structures  and  other 
structures  erected  for  a  period  of  less  than  180  days. 
Those  erected  for  a  longer  period  of  time  shall 
comply  with  780  CMR  3 103.0  or  with  all  applicable 
sections  of  780  CMR  where  780  CMR  3 103.0  is  not 
applicable. 

3104.1.1  Permit  required:  All  temporary 
structures  that  cover  an  area  in  excess  of  120 
square  feet  (11.16  m2),  including  all  connecting 
areas  or  spaces  with  a  common  means  of  egress 
or  entrance  which  are  used  or  intended  to  be  used 
for  the  gathering  together  often  or  more  persons, 
shall  not  be  erected,  operated  or  maintained  for 
any  purpose  without  obtaining  a  permit  from  the 
code  official.  Tents  used  exclusively  for 
recreational  camping  purposes  shall  be  exempt 
from  the  above  requirements.  Special  permits 
required  by  780  CMR  shall  be  secured  from  the 
code  official. 

3104.2  Construction  documents:  A  permit 
application  and  construction  documents  shall  be 
submitted  for  each  installation  of  a  temporary 
structure.  The  construction  documents  shall  include 
a  site  plan  indicating  the  location  of  the  temporary 
structure  and  information  delineating  the  means  of 
egress  and  the  occupant  load. 

3104.3  Location:  All  temporary  structures  shall  be 
located  in  accordance  with  the  requirements  of  Table 
705.2  based  on  the  fireresistance  rating  of  the 
exterior  walls  for  the  proposed  type  of  construction. 


3104.4  Construction:  Tents  and  air-supported 
structures  shall  be  constructed  as  required  by  this 
code  and  NFiPA  102  listed  in  Appendix  A 

3104.5  Membrane  material:  The  membrane 
material  for  all  tents  shall  be  of  approved 
noncombustible  material  as  defined  in  780  CMR 
704.4;  flameresistant  material  as  determined  in 
accordance  with  both  the  small-scale  and  large-scale 
tests  in  NfiPA  701  listed  in  Appendix  A:  or  material 
treated  in  an  approved  manner  to  render  the  material 
flameresistant. 

3104.6  Certification  An  affidavit  or  affirmation 
shall  be  submitted  to  the  code  official  and  a  copy 
retained  on  the  premises  on  which  the  tent  or  air- 
supported  structure  is  located  The  affidavit  shall 
attest  to  the  following  information  relative  to  the 
flameresistance  of  the  fabric: 

1 .  Names  and  addresses  of  the  owners  of  the  tent 
or  air-supported  structure. 

2.  Date  the  fabric  was  last  treated  with  flame- 
resistant solution 

3.  Trade  name  or  kind  of  chemical  used  in 
treatment 

4.  Name  of  person  or  firm  treating  the  material. 

5.  Name  of  testing  agency  and  test  standard  by 
which  the  fabric  was  tested. 

3104.7  Inflation  pressure:  Operating  pressure  shall 
be  maintained  at  the  design  pressure  specified  by  the 
manufacturer  to  assure  structural  stability  and  to 
avoid  excessive  distortion  during  high  wind  or  snow 
loads. 

3104.8  Door  operation:  In  high  winds  over  50  mph 
(80  45  km/h)  or  in  snow  conditions,  the  doors  in  air- 
supported  structures  shall  be  controlled  to  avoid 
excessive  air  loss.  Doors  shall  not  be  left  open 
under  any  conditions 

3104.9  Means  of  egress:  All  temporary  structures 
including  tents  and  membrane  structures  shall 
conform  to  the  means  of  egress  requirements  of 
780  CMR  10  and  shall  have  a  maximum  exit  access 
travel  distance  of  100  feet  (30480  mm). 

780  CMR  3105.0  CANOPIES  AND  AWNINGS 

3105.1  General:  Rigid  canopies  or  awnings 
supported  in  whole  or  in  part  by  members  resting  on 
the  ground  and  used  for  patio  covers,  car  ports, 
summer  houses  or  other  similar  uses  shall  comply 
with  the  requirements  of  780  CMR  3105.2  through 
3105.4  for  design  and  construction  Such  structures 
shall  be  braced  as  required  to  provide  rigidity 

3105.2  Design  and  construction:  Fixed  awnings, 
canopies  and  similar  structures  shall  be  designed  and 
constructed  to  withstand  wind  or  other  lateral  loads 
and  live  loads  as  required  by  780  CMR  1 6  with  due 
allowance  or  shape,  open  construction  and  similar 


430 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  CONSTRUCTION 


features  that  relieve  the  pressures  or  loads 
Structural  members  shall  be  protected  to  prevent 
deterioration. 

3105.3  Canopy  materials:  Canopies  shall  be 
constructed  of  a  metal  framework  with  an  approved 
covering,  that  is  flameresistant  as  determined  by 
both  the  small-scale  and  large-scale  tests  in 
accordance  with  NFiPA  701  listed  in  Appendix  A  or 
that  has  a  flame  spread  rating  not  greater  than  25 
when  tested  in  accordance  with  ASTM  E84  listed  in 
Appendix  A  Canopies  shall  be  attached  to  the 
building  at  the  inner  end  and  supported  at  the  outer 
end  by  not  less  than  two  stanchions,  with  braces 
anchored  in  an  approved  manner.  The  stanchions 
shall  be  placed  not  less  than  44  inches  (1118  mm) 
apart  The  horizontal  portion  of  the  framework  shall 
not  be  less  than  eight  feet  (2438  mm)  nor  more  than 
12  feet  (3658  mm)  above  the  walking  surface  and 
the  clearance  between  the  covering  or  valance  and 
the  walking  surface  shall  not  be  less  than  seven  feet 
(2134  mm). 

3105.4  Projections:  In  addition  to  780  CMR  3 105.0. 
awnings  and  canopies  that  are  constructed  in  the 
public  right-of-way  shall  conform  to  the 
requirements  of  780  CMR  32. 

780  CMR  3106.0  PEDESTRIAN  WALKWAYS 

3106.1  General:  An  exterior  elevated  pedestrian 
walkway  that  connects  buildings  shall  comply  with 
780  CMR  3106.0.  The  walkway  shall  not  contribute 
to  the  building  area  or  the  number  of  stories  or 
height  of  connected  buildings. 

3106.1.1  Separate  structures  Connected 
buildings  shall  be  considered  to  be  separate 
structures. 

Exception:    Buildings    on   the    same    lot    in 
accordance  with  780  CMR  503.1.3 

3106.2  Construction:  The  walkway  shall  be  of 
noncombustible  construction 

Exception:  Combustible  construction  shall  be 
permitted  where  all  connected  buildings  are  of 
combustible  construction. 

3106.3  Occupancy:  The  walkway  shall  not  be 
occupied  for  other  than  low  fire-hazard  uses  and 
only  approved  materials  and  decorations  shall  be 
located  in  the  space. 

3106.4  Separation  assemblies  between  walkways 
and  buildings:  Walkways  shall  be  separated  from 
the  interior  of  the  building  by  fire  separation  walls 
with  a  fireresistance  rating  of  not  less  than  two 
hours  This  protection  shall  extend  vertically  from 
a  point  ten  feet  (3048  mm)  above  the  walkway  roof 
surface  or  the  connected  building  roof  line, 
whichever  is  lower,  down  to  a  point  ten  feet  (3048 
mm)  below  the  walkway  and  horizontally  ten  feet 


(3048  mm)  from  each  side  of  the  walkway. 
Openings  within  the  ten-foot  (3048  mm)  horizontal 
extension  of  the  protected  walls  beyond  the 
walkway  shall  be  equipped  with  fixed  3/4-hour 
opening  protectives. 

Exception:  The  walls  separating  the  walkway 
from  a  connected  building  are  not  required  to 
have  a  fireresistance  rating  by  780  CMR  3106.4, 
given  compliance  with  one  of  the  following: 

1 .  Where  the  distance  between  the  connected 
buildings  is  more  than  ten  feet  (3048  mm),  the 
walkway  and  connected  buildings  are  equipped 
throughout  with  an  automatic  sprinkler  system  in 
accordance  with  780  CMR  906.2.1,  and  the  wall 
is  constructed  of  a  tempered,  wired  or  laminated 
glass  wall  and  doors  subject  to  the  following: 

1.1.  The  glass  shall  be  protected  by  an 
automatic  sprinkler  system  in  accordance  with 
780  CMR  906.2.1  and  the  sprinkler  system 
shall  completely  wet  the  entire  surface  of 
interior  sides  of  the  glass  wall  when  actuated 

1.2.  The  glass  shall  be  in  a  gasketed  frame 
and  installed  in  such  a  manner  that  the  framing 
system  will  deflect  without  breaking  (loading) 
the  glass  before  the  sprinkler  operates. 

1.3.  Obstructions  shall  not  be  installed 
between  the  sprinkler  heads  and  the  glass; 

2.  Where  the  distance  between  the  connected 
buildings  is  more  than  ten  feet  (3048  mm),  and 
both  sides  are  at  least  50%  open  with  the  open 
area  uniformly  distributed  to  prevent  the 
accumulation  of  smoke  and  toxic  gases; 

3  Buildings  on  the  same  lot,  in  accordance  with 
780  CMR  503. 1.3;  or 

4.  Where  exterior  walls  of  connected  buildings 
are  required  by  780  CMR  705.0  to  have  a 
fireresistance  rating  greater  than  two  hours,  the 
walkway  shall  be  equipped  throughout  with  an 
automatic  sprinkler  system  installed  in  accordance 
with  780  CMR  9. 

3106.5  Public  way:  The  installation  of  a  pedestrian 
walkway  over  a  public  way  shall  be  subject  to  the 
approval  of  local  authorities.  Construction  criteria 
for  approved  walkways  shall  meet  the  requirements 
of780CMR3106.0. 

3106.6  Egress:  Access  shall  be  provided  at  all  times 
to  a  pedestrian  walkway  that  serves  as  a  required 
exit 

3106.7  Width:  The  unobstructed  width  of  pedestrian 
walkways  shall  not  be  less  than  36  inches  (914  mm). 
The  total  width  shall  not  exceed  30  feet  (9144  mm). 

3106.8  Exit  access  travel:  The  length  of  exit  access 
travel  shall  not  exceed  200  feet  (60960  mm). 

Exceptions: 

1  Exit  access  travel  distance  on  a  walkway 
equipped  throughout  with  an  automatic  sprinkler 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


431 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


system  in  accordance  with  780  CMR  9  shall  not 
exceed  250  feet  (76200  mm)  in  length. 
2.      Exit  access  travel  distance  on  a  walkway 
constructed  with  both  sides  at  least  50%  open 
shall  not  exceed  300  feet  (91440  mm)  in  length. 

780  CMR  3107.0  FLOOD-RESISTANT 
CONSTRUCTION 

3107.1  General:  All  buildings  and  structures  erected 
in  areas  prone  to  flooding  shall  be  constructed  and 
elevated  as  required  by  the  provisions  of  780  CMR 

3107.0. 

3107.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3107,  and  as 
used  elsewhers  in  780  CMR,  have  the  meanings 
shown  herein: 

A-Zones:  Flood-hazard  zones-  all  areas  which 
have  been  determined  to  be  prone  to  flooding, 
but  not  subject  to  high-velocity  waters  or  wave 
action. 

Base  Flood  Elevation:  The  flood  having  a  1% 
chance  of  being  equalled  or  exceed  in  any  given 
year  and  shall  be  used  to  define  areas  prone  to 
flooding,  and  describe  at  a  minimum,  the  depth 
or  peak  elevation  of  flooding. 

Basement/cellar:  Any  area  of  the  building  having 
its  floor  subgrade  (Below  ground  level)  on  all 
sides 

Breakaway  Wall:  A  wall  that  is  not  part  of  the 
structural  support  of  the  building  and  intended, 
through  its  design  and  construction,  to  collapse 
under  specific  lateral  loading  forces,  without 
causing  damage  to  the  elevated  portion  of  the 
building  or  supporting  foundation  system. 

Elevation:  The  placement  of  a  structure  above 
flood  level  to  minimize  or  prevent  flood  damages. 

Flood  Hazard  Zones:  Areas  which  have  been 
determined  to  be  prone  to  flooding  but  not  to 
high  velocity  waters  or  wave  action.  (A  ZONES) 

Floodproofing:  Any  combination  of  structural  and 
non-structural  additions,  changes  or 
adjustments  to  structures  which  reduce  or 
eliminate  flood  damage  to  new  or  substantially 
improved  structures. 

F.EM.  A.:  Federal  Emergency  Management 
Agency. 

Flood  Insurance  Rate:  Flood  insurance  rate  map 
(FIRM)  means  an  official  map  of  a  community, 
which  delineates  both  the  special  hazard  areas 
and  the  risk  premium  zones  applcable  to  the 
community. 


Flood  Proofing:  Any  combination  of  structural 
and  nonstructural  additions,  changes,  or 
adjustments  to  structures  which  reduce  or 
eliminate  flood  damage  to  non-residential 
structures. 

High-hazard  Zones  (V  Zones)  Areas  of  tidal 
influence  which  have  been  determined  to  be 
subject  to  wave  run  heights  in  excess  of  three 
feet  or  subject  to  high-velocity  wave  run-up  or 
wave-induced  erosion  (V  Zones). 

Highest  Adjacent  Grade:  The  highest  natural 
elevation  of  the  ground  surface,  prior  to 
construction,  adjoining  the  proposed  foundation 
walls  of  a  structure 

Impact  Loads:  Loads  induced  by  the  collision  of 
solid  objects  on  a  structure  carried  by 
fioodwater. 

Lowest  Floor:  The  lowest  floor  of  the  lowest 
enclosed  area  (including  basement/cellar).  An 
unfinished  or  flood  resistant  enclosure,  usable 
solely  for  parking  of  vehicles,  building  access,  or 
incidental  storage  in  an  area  other  than  a 
basement/cellar  with  appropriate  hydrostatic 
openings  as  required  in  780  CMR  3107.5.3  is 
not  considered  a  building's  lowest  floor. 

Manufactured  Home:  See  DEFINITIONS, 
780  CMR  3502. 

Scouring:  The  erosion  or  washing  away  of  slopes 
or  soil  by  velocity  waters. 

Special  Hazard  Zones:  An  area  having  special 
flood,  and/or  flood-related  erosion  hazards  and 
shown  on  a  Flood  Hazard  Boundry  Map  or 
FIRM  as  Zone  A,  AO,  Al-30,  AE,  A99,  AH,  VO, 
Vl-30,  VE,  V. 

Start  of  Construction:  The  date  the  building  permit 
was  issued,  provided  the  actual  start  of 
construction,  repair,  reconstruction,  placement, 
or  other  improvement  was  within  180  days  of  the 
permit  date  The  actual  start  means  the  first 
placement  of  permanent  construction  of  a 
structure  on  a  site,  such  as  the  pouring  of  slab  or 
footings,  the  installation  of  piles,  the 
construction  of  columns,  or  any  work  beyond  the 
stage  of  excavation  or  the  placement  of  a 
manufactured  home  on  a  foundation. 

Structure:  A  walled  and  roofed  building,  including 
a  gas  or  liquid  storage  tank,  that  is  principally 
above  ground  and  affixed  to  a  permanent  site,  as 
well  as  a  manufactured  home. 


432 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  CONSTRUCTION 


Substantial       Improvements:  Substantial 

improvement  means  any  reconstruction, 
rehabilitation,  addition,  repair  or  improvement 
of  a  structure,  the  cost  of  which  equals  or 
exceeds  50%  of  the  market  value  of  the  structure 
before  the  "start  of  construction"  of  the 
improvement  This  term  includes  structures 
which  have  incurred  "Substantial  damage", 
regardless  of  the  actual  repair  work  performed 
Substantial  improvement  does  not,  however, 
include  either: 

1.  any  project  for  improvement  of  a  structure  to 
correct  existing  violations  of  state  or  local 
health,  sanitary,  or  safety  codes  which  have  been 
identified  by  the  local  code  enforcement  official 
and  which  are  the  minimum  necessary  to  assure 
safe  living  conditions  or 

2.  any  alteration  of  a  "Historic  structure", 
provided  that  the  alteration  will  not  preclude  the 
structure's  continued  designation  as  a  "historic 
structure. " 

Note  I:  The  following  items  can  be  excluded 
from  the  cost  of  improvement  or  repair:  plans, 
specifications,  survey,  permits,  and  other  items 
which  are  separate  from  or  incidental  to  the 
repair  of  the  damaged  or  improved  building.  Le. 
debris  removal/cartage. 

Note  2:  The  latest  Assessors' structure  value  may 
be  used,  provided  that  the  Assessors  certify  that 
said  value  is  based  on  100%  valuation,  less 
depreciation. 

V Zones:  Areas  of  tidal  influence  which  have  been 
detemmined  to  be  subject  to  wave  run  heights  in 
excess  of  three  feet  or  subject  to  high-velocity 
wave  run-up  or  wave-induced  erosion.  (V  Zones) 

Variance:  A  grant  of  relief  by  a  community  and 
the  Commonwealth,  Via  the  Boards  of  Appeal, 
from  the  terms  of  the  Floodplain  Management 
Regulations. 

Venting  A  system  designed  to  allow  flood  waters  to 
enter  an  enclosure,  usually  the  interior  of 
foundations  walls,  so  that  the  rising  water  does 
not  create  a  dangerous  differential  in  hydrostatic 
pressure;  usually  achieved  through  openings  in 
the  walls.  Vents  may  be  installed  in  garage  doors 
to  satisfy  this  requirement,  provided  such  vents 
are  installed  consistent  with  780  CMR  3107. 
The  necessity  of  human  intervention,  such  as 
opening  garage  doors,  does  not  satisfy  this 
requirement 

3107.3  Base  flood  elevation:  The  base  flood 
elevation  shall  be  used  to  define  areas  prone  to 
flooding,  and  shall  describe,  at  a  minimum,  the 
depth  or  peak  elevation  of  flooding  (including  wave 
height)  which  has  a  1%  (100-year  flood)  or  greater 
chance  of  occurring  in  any  given  year 


The  100-year  flood  elevation  shall  be  determined 
as  follows: 

/.  In  Al-30,  AH,  AE,  Vl-30  and  VE,  the  Base 
Flood  Elevation  is  provided  on  the  community's 
Flood  Insurance  Study  and  the  Flood  Insurance 
Rate  Map  (FIRM). 

2.  In  AO  zones,  add  the  depth  provided  on  the 
Flood  Insurance  Rate  Map  to  the  highest 
adjacent  grade  If  no  depth  is  provided  add  at 
least  two  feet  to  the  highest  adjacent  grade 

3.  In  A,  A99  and  V  zones,  the  building  official, 
design  professional,  or  surveyor  shall  obtain, 
review  and  reasonably  utilize  and  Base  Flood 
Elevation  Data  available  from  a  federal,  state  or 
other  reliable  sources. 

3107.4  Hazard  zones:  Areas  which  have  been 
determined  to  be  prone  to  flooding  shall  be  classified 
as  either  flood-hazard  zones  (A  Zones)  or  high- 
hazard  zones  (V  Zones)  in  accordance  with 
780  CMR  3107.5  and  3 107.6. 

3107.5  Flood-hazard  zones  (A  Zones):  All  areas 
which  have  been  determined  to  be  prone  to  flooding 
but  not  subject  to  high-velocity  waters  or  wave 
action  shall  be  designated  as  floodhazard  zones.  All 
buildings  and  structures  as  defined  in  780  CMR 
3107.2  erected  or  substantially  improved  in 
floodhazard  zones  shall  be  designed  and  constructed 
in  accordance  with  780  CMR  3107.5.1  through 
3107.5.4  Plans  for  such  construction  or 
improvements  shall  be  prepared  by  a  qualified 
registered  professional  engineer  or  architect  to 
ensure  the  compliance  with  780  CMR  3107.5. 

Exception:  a  proposed  addition  that  triggers  the 
substantial  improvement  requirements  shall  be 
constructed  according  to  the  provisions  of 
780  CMR  3107.5.  However,  the  existing 
structure  is  not  required  to  be  brought  into 
compliance  with  780  CMR  3107.5,  provided  that 
the  addition  IS  NOT  an  additional  story(s)  which 
relies  on  the  support  of  the  existing  structure. 

Should  the  construction  of  an  additional 
story(s)  meet  the  substantial  improvement 
definition,  the  existing  structure  shall  then  meet 
all  the  applicable  provisions  of  780  CMR  3107.5. 

3107.5.1  Elevation  All  buildings  or  structures 
erected  within  a  flood-hazard  zone  shall  be 
elevated  so  that  the  lowest  floor  is  located  at  or 
above  the  base  flood  elevation.  All  basement 
cellar  floor  surfaces  shall  be  located  at  or  above 
the  base  flood  elevations 
Exceptions: 

1.  Floors  of  occupancy  in  any  use  group, 
other  than  use  group  R,  below  the  base  flood 
elevation  shall  conform  to  780  CMR  3107.5.4. 

2.  Floors  of  occupancies  in  any  use  group 
which  are  utilized  solely  for  structure  means 
of  egress,  incidental  storage  garages  and 
parking,  and  which  are  located  below  the  base 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


flood  elevation,  shall  conform  to  780  CMR 
3107.5.3. 

3107.5.2  Anchorage:  The  structural  systems  of 
all  buildings  or  structures  shall  be  designed, 
connected  and  anchored  to  resist  flotation, 
collapse  or  permanent  lateral  movement  due  to 
structural  loads  and  stresses  from  flooding  equal 
to  the  base  flood  elevation  and  shall  be  designed 
in  accordance  with  780  CMR  1615.3  and  1615.4. 

31 07.5.3  Enclosures  below  base  flood  elevation 

Enclosed  spaces  below  the  base  flood  elevation 
shall  not  be  used  for  human  occupancy  with  the 
exception  of  structure  means  of  egress,  entrance 
foyers,  stairways  and  incidental  storage.  Fully 
(  enclosed  spaces  shall  be  designed  to  equalize 
automatically  hydrostatic  forces  on  exterior  walls 
by  allowing  for  the  entry  and  exit  of  floodwateis. 
Designs  for  meeting  this  requirement  shall  either 
be  certified  by  a  registered  design  professional  in 
accordance  with  780  CMR  3 107. 12  or  conform  to 
the  following  minimum  criterion:  a  minimum  of 
two  openings  having  a  total  net  area  of  not  less 
than  one  square  inch  (645  mm2)  for  every  one 
square  foot  (0. 1  m2)  of  enclosed  area  subject  to 
flooding  shall  be  provided.  The  bottom  of  all 
openings  shall  not  be  higher  than  12  inches  (305 
mm)  above  grade  immediately  adjacent  to  the 
location  of  the  opening.  Openings  shall  not  be 
equipped  with  screens,  louvers,  valves  or  other 
coverings  or  devices  unless  such  devices  permit 
the  automatic  entry  and  discharge  of  floodwaters. 

3107.5.4  Water-resistant        construction 

Occupancies  in  any  use  group  other  than  Use 
Group  R  shall,  in  lieu  of  meeting  the  elevation 
provisions  of  780  CMR  3107.5.1,  be  erected  with 
floors  usable  for  human  occupancy  below  the  base 
flood  elevation  provided  that  the  following 
conditions  are  met: 

1 .  All  space  below  the  base  flood  elevation 
shall  be  constructed  with  walls  and  floors  that 
are  substantially  impermeable  to  the  passage  of 
water. 

2.  All  structural  components  subject  to 
hydrostatic  and  hydrodynamic  loads  and 
stresses  during  the  occurrence  of  flooding  to 
the  base  flood  elevation  shall  be  capable  of 
resisting  such  forces,  including  the  effects  of 
buoyancy. 

3.  All  openings  below  the  base  flood 
elevation  shall  be  provided  with  water-tight 
closures  and  shall  have  adequate  structural 
capacity  to  support  all  flood  loads  acting  upon 
the  closure  surfaces 

4.  All  floor  and  wall  penetrations  for 
plumbing,  mechanical  and  electrical  systems 
shall  be  made  water  tight  to  prevent  floodwater 
seepage  through  spaces  between  the 
penetration  and  wall  construction  materials 
Sanitary  sewer  and  storm  drainage  systems  that 
have  openings  below  the  base  flood  elevation 


shall  be  provided  with  shutoff  valves  or  closure 
devices  to  prevent  backwater  flow  during 
conditions  of  flooding. 

3107.6  High-hazard  zones  (V  Zones):  Areas  of 
tidal  influence  which  have  been  determined  to  be 
subject  to  wave  heights  in  excess  of  three  feet  (914 
mm)  or  subject  to  high-velocity  wave  run-up  or 
wave-induced  erosion  shall  be  classified  as  high- 
hazard  zones.  All  buildings  or  structures  erected  in 
a  high-hazard  zone  shall  be  designed  and 
constructed  in  accordance  with  780  CMR  3 1 07.6. 1 
through  3 107.6.4.  Plans  for  such  construction  shall 
be  prepared  by  a  registered  professional  engineer 
or  architect  to  ensure  compliance  with  780  CMR 
3107.6 

Exception:  a  proposed  addition  that  triggers  the 
substantial  improvement  requirements  shall  be 
constructed  according  to  the  provisions  of 
780  CMR  3107.6.  However,  the  existing 
structure  is  not  required  to  be  brought  into 
compliance  with  780  CMR  3107. 6,  provided  that 
the  addition  IS  NOT  an  additional  story(s)  which 
relies  on  the  support  of  the  existing  structure 

Should  the  construction  of  an  additional 
story(s)  meet  the  substantial  improvement 
definition,  the  existing  structure  shall  then  meet 
all  the  applicable  provisions  of  780  CMR  3107.6. 

Note:  Areas  shown  as  V  Zones  on  the  most  recent 
Flood  Insurance  Rate  Map  published  by  the 
Federal  Emergency  Management  Agency  shall  be 
considered  in  establishing  high-hazard  zones. 

3107.6.1  Elevation:  All  buildings  or  structures 
erected  within  a  high-hazard  zone  shall  be 
elevated  so  that  the  lowest  portion  of  all  structural 
members  supporting  the  lowest  floor,  with  the 
exception  of  mat  or  raft  foundations,  piling,  pile 
caps,  columns,  grade  beams  and  bracing,  is 
located  at  or  above  the  base  flood  elevation. 

3107.6.2  Enclosures  below  base  flood  elevation 

All  spaces  below  the  base  flood  elevation  in  a 
high-hazard  zone  shall  not  be  used  for  human 
occupancy  and  shall  be  free  of  obstruction  except 
as  permitted  herein: 

1 .  Mat  or  raft  foundations,  piling,  pile  caps, 
bracing,  grade  beams  and  columns  which 
provide  structural  support  for  the  building. 

2.  Entrances  and  exits  which  are  necessary  for 
required  ingress  and  means  of  egress. 

3.  Incidental  storage  of  portable  or  mobile 
items  readily  moved  in  the  event  of  a  storm. 

4.  Walls  and  partitions  are  permitted  to 
enclose  all  or  part  of  the  space  below  the 
elevated  floor  provided  that  such  walls  and 
partitions  are  not  part  of  the  structural  support 
of  the  building  and  are  constructed  with  insect 
screening,  open  wood  lattice,  or  nonsupporting 
walls  designed  to  break  away  or  collapse 
without  causing  collapse,  displacement  or  other 


434 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SPECIAL  CONSTRUCTION 


structural  damage  to  the  elevated  portion  of  the 
building  or  supporting  foundation  system  due 
to  the  effect  of  wind  loads  as  specified  in 
780  CMR  1611.0  and  water  loads  as  specified 
in  780  CMR  1615.0  acting  simultaneously. 
Any  such  nonsupporting  solid  wall  shall  be 
certified  as  specified  in  780  CMR  3107.12.3. 

3107.6.3  Foundations:  All  buildings  or  structures 
erected  in  high-hazard  zones  shall  be  supported 
on  pilings  or  columns  and  shall  be  adequately 
anchored  to  such  pilings  or  columns.  The  piling 
shall  have  adequate  soil  penetrations  to  resist  the 
combined  wave  and  wind  loads  (lateral  and  uplift) 
to  which  such  piles  are  likely  to  be  subjected 
during  a  flood  to  the  base  flood  elevation.  Pile 
embedment  shall  include  consideration  of 
decreased  resistance  capacity  caused  by  scour  of 
soil  strata  surrounding  the  piling.  Pile  system 
design  and  installation  shall  also  be  made  in 
accordance  with  the  provisions  of  780  CMR 
1816.0  and  1817.0.  Mat  or  raft  foundations  which 
support  columns  shall  not  be  permitted  where  soil 
investigations  required  in  accordance  with 
780  CMR  1802.1  indicate  that  soil  material  under 
the  mat  or  raft  is  subject  to  scour  or  erosion  from 
wave-velocity  flow  conditions. 

3107.6.4  Repair  or  Replacement  of  Existing 
Foundations:  Existing  foundations  may  be 
repaired  without  further  compliance  with 
780  CMR  3107  unless  the  work  required  is 
determined  to  be  substantial  as  defined  herein. 

Exception:  Existing  foundation  systems 
which  are  replaced  in  total  or  which  are 
replaced  so  as  to  constitute  new  construction 
shall  meet  the  requirements  of  780  CMR 
3107.6  regardless  of  whether  the  work 
required  is  substantial 

3107.7  Protection  of  mechanical  and  electrical 
systems:  New  and  replacement  electrical  equipment 
and  heating,  ventilating,  air  conditioning  and  other 
service  equipment  shall  be  either  placed  above  the 
base  flood  elevation  or  protected  so  as  to  prevent 
water  from  entering  or  accumulating  within  the 
system  components  during  floods  up  to  the  base 
flood  elevation  in  accordance  with  the  mechanical 
code  listed  in  Appendix  A.  Installation  of  electrical 
wiring  and  outlets,  switches,  junction  boxes  and 
panels  below  the  base  flood  elevation  shall  conform 
to  the  provisions  of  527  CMR  12.00  listed  in 
Appendix  A  for  location  of  such  items  in  wet 
locations.  Duct  insulation  subject  to  water  damage 
shall  not  be  installed  below  the  base  flood  elevation. 

3107.8  Construction  materials,  methods  and 
practices:  All  buildings  or  structures  erected  in 
flood-hazard  zones  (A  Zones)  or  in  high-hazard 
zones  (V  Zones)  shall  be  constructed  with  materials 
resistant  to  flood  damage  and  be  constructed  by 
methods  and  practices  that  minimize  flood  damage 


Construction  materials  shall  be  resistant  to  water 
damage  in  accordance  with  the  provisions  of 
780  CMR  1808.0,  1810.2,1813.4,  2307.2,  2309.1, 
2311.4,  2311.6  and  2503.4. 

3107.9  Mobile  units:  New  or  replacement  mobile 
units  to  be  located  in  any  hazard  zone  shall  be 
placed  in  accordance  with  the  applicable  elevation 
requirements  of  780  CMR  3107.5.1  and  3107.6.1 
and  the  anchor  and  tie-down  requirements  of 
780  CMR  35. 

3107.10  Alterations,  renovations  and  repairs: 
Alterations,  renovations  and  repairs  to  existing 
buildings  located  in  any  hazard  zone  shall  comply 
with  all  applicable  provisions  of  780  CMR. 
Compliance  with  780  CMR  3107  is  not  required 
unless  such  alteration,  renovation  or  repairs 
constitute  substantial  improvements  as  defined  in 
780  CMR  3107.2. 

Exception:  Repair  or  replacement  of  existting 
foundations  shall  comply  with  780  CMR 
3107.6.4. 

3107.11  Increases  in  building  height  and  floor 
area:  See  780  CMR  3107.5  Exception  and 3107.6 
Exception. 

3107.12  Certifications:  Certifications  shall  be 
submitted  in  accordance  with  780  CMR  3107.12.1 
through  3107.12.3. 

3107.12.1  As-built  elevation  certifications:  A 

licensed  land  surveyor  or  registered  design 
professional  shall  certify  the  actual  elevation  (in 
relation  to  base  flood  elevation)  of  the  lowest 
structural  member  required  to  be  elevated  by  the 
provisions  of  780  CMR  12. 

3107.12.2  Waterresistant  construction:  Where 
buildings  or  structures  are  to  be  constructed  in 
accordance  with  780  CMR  3107.5.4,  the  code 
official  shall  require  that  a  registered  design 
professional  provide  construction  documents 
showing  proposed  details  of  floor,  wall  and 
foundation  support  components,  loading 
computations  and  other  essential  technical  data 
used  in  meeting  the  conditions  of  780  CMR 
3107.5.4.  The  construction  documents  shall  be 
accompanied  by  a  statement  bearing  the  signature 
of  the  registered  design  professional  indicating 
that  the  design  and  proposed  methods  of 
construction  are  in  accordance  with  all  applicable 
provisions  of  780  CMR  3107.5.4. 

3107.12.3  High-hazard  construction:  Where 
buildings  or  structures  are  to  be  constructed  in 
accordance  with  780  CMR  3107.6,  the  code 
official  shall  require  that  a  registered  design 
professional  provide  construction  documents 
showing  proposed  details  of  foundation  support 
and  connection  components  which  are  used  in 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


435 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


meeting  the  requirements  of  780  CMR  3107.6.3. 
Where  solid  walls  or  partitions  are  proposed 
below  the  base  flood  elevations,  wall,  framing  and 
connection  details  of  such  walls  shall  be  provided, 
including  loading  computations  for  the  wall  and 
foundation  system  used  in  meeting  the  conditions 
of  780  CMR  3107.6.2.  The  construction 
documents  shall  be  accompanied  by  a  statement 
bearing  the  signature  of  the  registered  design 
professional  indicating  that  the  design  and 
proposed  methods  of  construction  are  in 
accordance  with  all  applicable  provisions  of 
780  CMR  3107.6. 

780  CMR  3108.0  RADIO  AND  TELEVISION 
TOWERS 

3108.1  General:  Subject  to  the  structural  provisions 
of  780  CMR  1611.0  for  wind  loads  and  the 
requirements  of  780  CMR  1510.0  governing  the 
fireresistance  ratings  of  buildings  for  the  support  of 
roof  structures,  all  radio  and  television  towers  shall 
be  designed  and  constructed  as  herein  provided. 

3108.2  Location  and  access:  Towers  shall  be 
located  and  equipped  with  step  bolts  and  ladders  so 
as  to  provide  ready  access  for  inspection  purposes. 
Guy  wires  or  other  accessories  shall  not  cross  or 
encroach  upon  any  street  or  other  public  space,  or 
over  any  electric  power  lines,  or  encroach  upon  any 
other  privately  owned  property  without  written 
consent  of  the  owner. 

3108.3  Construction:  All  towers  shall  be 
constructed  of  approved  corrosion-resistant 
noncombustible  material.  The  minimum  type  of 
construction  of  isolated  radio  towers  not  more  than 
100  feet  (30480  mm)  in  height  shall  be  Type  4. 

3108.4  Loads:  Towers  shall  be  designed  to  resist 
wind  loads  in  accordance  with  EIA  222-E  listed  in 
Appendix  A.  Consideration  shall  be  given  to 
conditions  involving  wind  load  on  ice-covered 
sections  in  localities  subject  to  sustained  freezing 
temperatures. 

3108.4.1  Dead  load:  Towers  shall  be  designed  for 
the  dead  load  plus  the  ice  load  in  regions  where 
ice  formation  occurs. 

3108.4.2  Uplift:  Adequate  foundations  and 
anchorage  shall  be  provided  to  resist  two  times 
the  calculated  wind  uplift. 

3108.5  Grounding:  All  towers  shall  be  permanently 
and  effectively  grounded. 

780  CMR  3109.0  RADIO  AND  TELEVISION 

ANTENNAS 
3109.1  Permits  not  required:  A  building  permit  is 
not    required    for    roof   installation    of   antennal 
structures  not  more  than  12  feet  (3658  mm)  in  height 


for  private  radio  or  television  reception.  Such  a 
structure  shall  not  be  erected  so  as  to  injure  the  roof 
covering,  and  when  removed  from  the  roof,  the  roof 
covering  shall  be  repaired  to  maintain  weather  and 
water  tightness.  The  installation  of  any  antennal 
structure  mounted  on  the  roof  of  a  building  shall  not 
be  erected  nearer  to  the  lot  line  than  the  total  height 
of  the  antennal  structure  above  the  roof,  nor  shall 
such  structure  be  erected  near  electric  power  lines  or 
encroach  upon  any  street  or  other  public  space. 

3109.2  Permits  required:  Approval  shall  be  secured 
for  all  roof-mounted  antennal  structures  more  than 
12  feet  (3658  mm)  in  height  above  the  roof.  The 
application  shall  be  accompanied  by  detailed 
drawings  of  the  structure  and  methods  of  anchorage. 
All  connections  to  the  roof  structure  shall  be 
properly  flashed  to  maintain  water  tightness.  The 
design  and  materials  of  construction  shall  comply 
with  the  requirements  of  780  CMR  3108.3  for 
character,  quality  and  minimum  dimension. 

3109.3  Dish  antennas:  An  antenna  consisting  of  a 
radiation  element  which  transmits  or  receives 
radiation  signals  generated  as  electrical,  light  or 
sound  energy,  and  supported  by  a  structure  with  or 
without  a  reflective  component  to  the  radiating  dish, 
usually  in  a  circular  shape  with  a  parabolic  curve 
design  constructed  of  a  solid  or  open  mesh  surface, 
shall  be  known  as  a  dish  antenna. 

3109.3.1  Permits:  The  approval  of  the  code 
official  shall  be  secured  for  all  dish  antennal 
structures  more  than  two  feet  (610  mm)  in 
diameter  erected  on  the  roof  of  or  attached  to  any 
building  or  structure.  A  permit  is  not  required  for 
dish  antennas  not  more  than  two  feet  (610  mm)  in 
diameter  erected  and  maintained  on  the  roof  of 
any  building. 

3109.3.2  Structural  provisions:  Dish  antennas 
larger  than  two  feet  (6 1 0  mm)  in  diameter  shall  be 
subject  to  the  structural  provisions  of  780  CMR 
1610.0,1611.0  and  3108.4.  The  snow  load 
provisions  of  780  CMR  1610.0  shall  not  apply 
where  the  antenna  has  a  heater  to  melt  falling 
snow. 

780  CMR  3110.0  WINDOW-CLEANING 
SAFEGUARDS 

3110.1  General:  All  buildings  and  structures  over 
50  feet  (15240  mm)  or  four  stories  in  height,  in 
which  the  windows  are  cleaned  from  the  outside, 
shall  be  provided  with  anchors,  belt  terminals  or 
other  approved  safety  devices  for  all  window 
openings.  Such  devices  shall  be  of  an  approved 
design,  and  shall  be  constructed  of  corrosion- 
resistant  materials  securely  attached  to  the  window 
frames  or  anchored  in  the  enclosure  walls  of  the 
building.  Cast-iron  or  cast-bronze  anchors  shall  be 
prohibited. 


436 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  32 

CONSTRUCTION  IN  THE  PUBLIC  RIGHT-OF-WAY 


780  CMR  3201.0  GENERAL 

3201.1  Scope:  The  provisions  of  780  CMR  32  shall 
govern  encroachment  and  projection  of  structures 
into  the  public  right-of-way. 

780  CMR  3202.0  STREET 
ENCROACHMENTS 

3202.1  General:  Except  as  herein  provided,  a  part  of 
any  building  hereafter  erected  and  additions  to  an 
existing  building  heretofore  erected  shall  not  project 
beyond  the  lot  lines  or  beyond  the  building  line 
where  such  lines  are  established  by  the  zoning  law  or 
any  other  statute  controlling  building  construction. 

3202.2  Below  grade:  A  part  of  a  building  hereafter 
erected  below  grade  that  is  necessary  for  structural 
support  of  the  building  shall  not  project  beyond  the 
lot  lines,  except  that  the  footings  of  street  walls  or 
their  supports  which  are  located  at  least  eight  feet 
(2438  mm)  below  grade  shall  not  project  more  than 
12  inches  (305  mm)  beyond  the  street  lot  line. 

3202.3  Above  grade:  All  projections  hereafter 
permitted  beyond  the  street  lot  line  or  the  building 
line  above  grade  shall  be  so  constructed  as  to  be 
readily  removable  without  endangering  the  safety  of 
the  building. 

3202.4  Projections  necessary  for  safety:  In  any 

specific  application,  the  code  official  is  authorized  to 
designate  by  approved  rules  such  architectural 
features  and  accessories  which  are  deemed  desirable 
or  necessary  for  the  health  or  safety  of  the  public  as 
well  as  the  maximum  extent  to  which  such  features 
shall  project  beyond  the  street  lot  line  or  the  building 
line  where  established  by  statute,  subject  to  all 
provisions  and  restrictions  that  are  otherwise 
prescribed  by  law,  ordinance  or  rule  of  the 
authorities  having  jurisdiction  over  streets  or  public 
spaces. 

3202.5  Permit  revocable:  Any  permit  granted  or 
permission  expressed  or  implied  in  the  provisions  of 
this  code  to  construct  a  building  so  as  to  project 
beyond  the  street  lot  line  or  building  line  shall  be 
revocable  by  the  jurisdiction  at  will. 

3202.6  Existing  encroachments:  Parts  of  existing 
buildings  and  structures  which  already  project 
beyond  the  street  lot  line  or  building  line  are  not 
required  to  be  altered  until  their  removal  is  directed 
by  the  proper  authorities  of  the  jurisdiction. 


780  CMR  3203.0  PERMISSIBLE  STREET 
PROJECTIONS 

3203.1  General:  Subject  to  such  provisions  as  are 
otherwise  prescribed  by  law  or  ordinance,  or  by 
rules  of  the  authorities  having  jurisdiction  over 
streets,  highways  and  public  spaces,  the  projections 
described  in  780  CMR  3203.3  through  3203.12  1 
shall  be  permitted  beyond  the  street  lot  line  or  the 
building  line 

3203.2  Definitions:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  3203.0  and  as 
used  elsewhere  in  780  CMR  have  the  meanings 
shown  herein 

Areaway  (form  of  construction)  An  uncovered 
subsurface  space  adjacent  to  a  building  (see 
780  CMR  3203  12  1). 

Curb  level:  The  elevation  of  the  street  curb  as 
established  in  accordance  with  law 
Building  or  wall  height:  The  elevation  of  the 
street  grade  opposite  the  center  of  the  wall  nearest 
to  and  facing  the  street  lot  line 

Oriel  window  A  window  projected  beyond  and 
suspended  from  the  wall  of  the  building  or 
cantilevered  therefrom  (see  780  CMR  3203  7) 

3203.3  Cornices  and  eaves:  Main  cornices  or  roof 
eaves  located  at  least  12  feet  (3658  mm)  above  the 
curb  level  shall  not  project  more  than  three  feet  (914 
mm) 

3203.4  Architectural  decorations:  Belt  courses, 
lintels,  sills,  architraves,  pediments  and  similar 
architectural  decorations  shall  not  project  more  than 
four  inches  (102  mm)  where  less  than  ten  feet  (3048 
mm)  above  the  curb  level,  and  not  more  than  ten 
inches  (254  mm)  where  ten  feet  (3048  mm)  or  more 
above  the  curb  level. 

3203.5  Ornamental  columns:  Ornamental  columns 
or  pilasters,  including  the  bases  and  moldings  which 
emphasize  the  main  entrance  of  the  building,  shall 
not  project  more  than  12  inches  (305  mm). 

3203.6  Entrance  steps:  Entrance  steps  and  doors 
shall  not  project  more  than  12  inches  (305  mm)  and 
shall  be  guarded  by  check  pieces  not  less  than  three 
feet  (914  mm)  high,  or  shall  be  located  between 
ornamental  columns  or  pilasters 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


437 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3203.7  Oriel  windows:  Oriel  windows  with  the 
lowest  portion  at  least  ten  feet  (3048  mm)  above  the 
curb  level  shall  not  project  more  than  2Vi  feet  (762 
mm). 

3203.8  Balconies:  Balconies  located  at  least  ten  feet 
(3048  mm)  above  the  curb  level  shall  not  project 
more  than  three  feet  (914  mm),  except  that  where  the 
balcony  is  required  in  connection  with  a  fire  escape 
or  exterior  stairway  as  an  element  of  a  means  of 
egress,  the  projection  shall  not  exceed  four  feet 
(1219  mm). 

3203.9  Awnings:  Retractable  or  fixed  awnings  shall 
have  clearances  above  grade  and  shall  be  installed  in 
accordance  with  the  requirements  of  780  CMR 
3105.0  and  3205.0. 

3203.10  Awning  covers  or  boxes:  Awning  covers 
or  boxes  located  at  least  eight  feet  (2438  mm)  above 
the  curb  level  shall  not  project  more  than  three  feet 
(914  mm). 

3203.11  Marquees:  For  the  purposes  of  780  CMR 
3203.11,  a  marquee  shall  include  any  object  or 
decoration  attached  to,  or  part  of,  said  marquee. 

3203.11.1  Projection    and    clearance:     The 

horizontal  clearance  between  a  marquee  and  the 
curb  line  shall  not  be  less  than  two  feet  (610  mm). 
A  marquee  projecting  more  than  %  of  the  distance 
from  the  property  line  to  the  curb  line  shall  not  be 
less  than  ten  feet  (3048  mm)  above  the  ground  or 
pavement  below. 

3203.11.2  Thickness:  The  maximum  height  or 
thickness  of  a  marquee  measured  vertically  from 
its  lowest  to  its  highest  point  shall  not  exceed 
three  feet  (914  mm)  where  the  marquee  projects 
more  than  %  of  the  distance  from  the  property 
line  to  the  curb  line,  and  shall  not  exceed  nine  feet 
(2743  mm)  where  the  marquee  is  less  than  %  of 
the  distance  from  the  property  line  to  the  curb 
line. 

3203.11.3  Roof  construction:  Where  the  roof  or 
any  part  thereof  is  a  skylight,  the  materials  shall 
consist  of  approved  plastics  or  wired  glass  not 
less  than  %  inch  thick  with  a  single  pane  not  more 
than  18  inches  (457  mm)  wide.  Every  roof  and 
skylight  of  a  marquee  shall  be  sloped  to 
downspouts  that  shall  conduct  any  drainage  from 
the  marquee  in  such  a  manner  so  as  not  to  spill 
over  the  sidewalk. 

3203.11.4  Location  prohibited:  Every  marquee 
shall  be  so  located  as  not  to  interfere  with  the 
operation  of  any  exterior  standpipe,  and  such  that 
the  marquee  does  not  obstruct  the  clear  passage  of 
stairway  or  exit  discharge  from  the  building  or  the 
installation  or  maintenance  of  street  lighting. 

3203.11.5  Construction:  A  marquee  shall  be 
supported     entirely     from    the     building     and 


constructed  of  noncombustible  materials. 
Marquees  shall  be  designed  and  constructed  to 
withstand  wind  or  other  lateral  loads  and  live 
loads  as  required  in  780  CMR  16.  Structural 
members  shall  be  protected  to  prevent 
deterioration. 

3203.12  Vaults:  Vaults  below  the  sidewalk  level 
shall  not  extend  closer  than  three  feet  (914  mm)  to 
the  curb  line.  The  construction  and  utilization  of 
such  vaults  shall  be  subject  to  the  terms  and 
conditions  of  the  authority  or  legislative  body  having 
jurisdiction. 

3203.12.1  Areaways:  Areaways  shall  not  project 
beyond  the  street  lot  line  more  than  four  feet 
(1219  mm),  provided  that  every  such  areaway 
shall  be  covered  over  at  the  street  grade  by  an 
approved  grating  of  metal  or  other 
noncombustible  material. 

780  CMR  32O4.0  SPECIAL  AND 
TEMPORARY  PROJECTIONS 

3204.1  Alley  projections:  The  permissible 
projection  beyond  street  lot  lines  shall  apply  in 
general  to  building  projections  into  alleyways, 
except  as  modified  by  the  authority  having 
jurisdiction  or  by  special  deed  restriction. 

3204.2  Special  permits:  Where  authorized  by 
special  permit,  vestibules  and  storm  doors  shall  be 
erected  for  periods  of  time  not  exceeding  seven 
months  in  any  one  year,  and  shall  not  project  more 
than  three  feet  (914  mm)  nor  more  than  V*  of  the 
width  of  the  sidewalk  beyond  the  street  lot  line. 
Temporary  entrance  awnings  shall  be  erected  with  a 
minimum  clearance  of  seven  feet  (2134  mm)  to  the 
lowest  portion  of  the  hood  or  awning  where 
supported  on  removable  steel,  or  other  approved 
noncombustible  supports. 

780  CMR  3205.0  AWNINGS  AND  CANOPIES 

3205.1  Permit:  A  permit  shall  be  obtained  from  the 
code  official  for  the  erection,  repair  or  replacement 
of  any  fixed  awning,  canopy  or  hood,  except  as 
provided  for  in  780  CMR  3205.1.1,  and  for  any 
retractable  awning  located  at  the  first-story  level  and 
extending  over  the  public  street  or  over  any  portion 
of  a  court  or  yard  beside  a  building  serving  as  a 
passage  from  a  required  exit  or  exit  discharge  to  a 
public  street. 

3205.1.1  Exemption  from  permit:  A  permit  shall 
not  be  required,  for  the  erection,  repair  or 
replacement  of  fixed  or  retractable  awnings 
installed  on  occupancies  in  Use  Group  R-3  unless 
such  awnings  project  over  public  property;  for 
retractable  awnings  installed  above  the  first  story; 
or  where  the  awning  does  not  project  over  the 
public  street  or  over  any  court  or  yard  serving  as 
a  passage  from  a  required  exit  to  a  public  street. 


438 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:  STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONSTRUCTION  IN  THE  PUBLIC  RIGHT-OF-WAY 


3205.2  Retractable  awnings:  There  shall  be  a 
minimum  clearance  of  seven  feet  (2134  mm)  from 
the  sidewalk  to  the  lowest  part  of  the  framework 
or  any  fixed  portion  of  any  retractable  awning, 
except  that  the  bottom  of  the  valance  of  canvas 
awnings  shall  have  a  minimum  clearance  of  six 
feet  nine  inches  (2057  mm)  above  the  sidewalk. 
Retractable  awnings  shall  be  securely  fastened  to 
the  building  and  shall  not  extend  closer  than  12 
inches  (305  mm)  in  from  the  curb  line. 
Retractable  awnings  shall  be  equipped  with  a 
mechanism  or  device  for  raising  and  holding  the 
awning  in  a  retracted  or  closed  position  against 
the  face  of  the  building. 


3205.3  Fixed    or    permanent    awnings:    The 

clearance  from  the  sidewalk  to  the  lowest  part  of 
any  fixed  or  permanent  awning  shall  be  the  same 
as  required  in  780  CMR  3205.2  for  retractable 
awnings.  Fixed  or  permanent  awnings  installed 
above  the  first  story  shall  not  project  more  than 
four  feet  (1219  mm). 

3205.4  Canopies:  Stanchions  that  support 
canopies  shall  be  placed  not  less  than  two  feet 
(610  mm)  in  from  the  curb  line.  The  horizontal 
portion  of  the  canopy  framework  shall  not  be  less 
than  eight  feet  (2438  mm)  nor  more  than  12  feet 
(3658  mm)  above  the  sidewalk  and  the  clearance 
between  the  covering  or  valance  and  the  sidewalk 
shall  not  be  less  than  seven  feet  (2134  mm). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


439 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


440  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


CHAPTER  33 


SITE  WORK,  DEMOLITION  AND  CONSTRUCTION 


780  CMR  3301.0  GENERAL 

3301.1  Scope:  The  provisions  of  780  CMR  33  shall 

apply  to  all  construction  in  connection  with  work 
requiring  a  permit  for  structures  in  accordance  with 
780  CMR. 

3301.2  Other  laws:  Nothing  herein  contained  shall 
be  construed  to  nullify  any  rules,  regulations  or 
statutes  of  state  or  federal  agencies  governing  the 
protection  of  the  public  or  workers  from  health  or 
other  hazards. 

When  not  covered  by  the  provisions  of  780  CMR, 
454  CMR  10. 00:  Construction  Industry  Rules  and 
Regulations,  shall  apply. 

3301.3  Combustible  and  explosive  hazards:  The 

provisions  of  780  CMR  which  apply  to  the  storage, 
use  or  transportation  of  explosives,  highly  flammable 
and  combustible  substances,  gases  and  chemicals 
shall  be  construed  as  supplemental  to  the 
requirements  of  the  federal  laws,  the  regulations  of 
the  Department  of  Transportation  (DOTn)  and  527 
CMR  13. 00,  Keeping,  Storage,  Use,  Manufacture, 
Sale,  Handling,  and  Transportation  of  Explosives, 
as  listed  in  Appendix  A. 

780  CMR  3302.0  CONSTRUCTION 
DOCUMENTS  AND  SPECIAL  PERMITS 

3302.1  Temporary  construction:  Before  any 
construction  operation  is  started,  construction 
documents  shall  be  filed  with  the  code  official 
showing  the  design  and  construction  of  all  sidewalk 
sheds,  temporary  vehicular  passageways,  trestles, 
foot  bridges,  guard  fences  and  other  similar  devices 
required  in  the  operation.  Approval  shall  be  secured 
from  the  code  official  before  the  commencement  of 
any  work. 

3302.2  Special  permits:  All  special  licenses  and 
permits  for  the  storage  of  materials  on  sidewalks  and 
highways,  for  the  use  of  water  or  other  public 
facilities  and  for  the  storage  and  handling  of 
explosives,  shall  be  secured  from  the  administrative 
authorities  having  jurisdiction. 

3302.3  Temporary  encroachments:  Sidewalk 
sheds,  underpinning  and  other  temporary  protective 
guards  and  devices  shall  not  project  beyond  the 
interior  and  street  lot  lines  except  where  required  to 
insure  the  safety  of  the  adjoining  property  and  the 
public,  subject  to  approval.  Where  necessary,  the 
consent  of  the  adjoining  property  owner  shall  be 
obtained. 


780  CMR  3303.0  TESTS 
3303.1  Loading:  It  shall  be  unlawful  to  load  any 
structure,  temporary  support,  sidewalk  bridge  or 
sidewalk  shed  or  any  other  device  during  the 
construction  or  demolition  of  any  building  or 
structure  in  excess  of  its  safe  working  capacity  as 
provided  for  in  780  CMR  16  for  allowable  loads  and 
working  stresses. 

780  CMR  3304.0  PROTECTION  OF  PUBLIC 

3304.1  General.  Wherever  a  building  or  structure  is 
erected,  altered,  repaired,  removed  or  demolished, 
the  operation  shall  be  conducted  in  a  safe  manner 
and  suitable  protection  for  the  general  public  shall 
be  provided. 

3304.2  Fences:  Every  excavation  or  area  of 
construction  on  a  site  located  five  feet  (1524  mm)  or 
less  from  the  street  lot  line  shall  be  enclosed  with  a 
barrier  not  less  than  six  feet  (1829  mm)  high  to 
prevent  the  entry  of  unauthorized  persons.  Where 
located  more  than  five  feet  (1524  mm)  from  the 
street  lot  line,  a  barrier  shall  be  erected  where 
required  by  the  code  official.  All  barriers  shall  be  of 
adequate  strength  to  resist  wind  pressure  as  specified 
in  780  CMR  161 1.0. 

3304.3  Sidewalk  bridge:  Wherever  the  ground  is 
excavated  under  the  sidewalk,  a  sidewalk  bridge 
shall  be  constructed  at  least  four  feet  (1219  mm) 
wide,  or  a  protected  walkway  of  equal  width  shall  be 
erected  in  the  street,  provided  that  the  required 
permit  for  such  walkway  is  obtained  from  the 
administrative  authority. 

3304.4  Sidewalk  shed:  Sidewalk  sheds  shall  be  as 
provided  for  in  accordance  with  780  CMR  3304.4. 1 
through  3304.4.4  except  where  sidewalks  are  closed 
by  the  authority  having  jurisdiction 

3304.4.1  Within  ten  feet  of  street  lot  line:  Where 
any  building  or  part  thereof  which  is  located 
within  ten  feet  (3048  mm)  of  the  street  lot  line  is 
to  be  erected  or  raised  to  exceed  40  feet  (12192 
mm)  in  height,  or  wherever  a  building  which  is 
more  than  40  feet  (12192  mm)  in  height  and  is 
within  ten  feet  (3048  mm)  of  the  street  lot  line  is 
to  be  demolished,  a  sidewalk  shed  shall  be  erected 
and  maintained  for  the  full  length  of  the  building 
on  all  street  fronts  for  the  entire  time  that  work  is 
performed  on  the  exterior  of  the  building. 

3304.4.2  Within  20  feet  of  street  lot  line:  Where 
the  building  being  demolished  or  erected  is 
located  within  20  feet  (6096  m)  of  the  street  lot 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


line  and  is  more  than  40  feet  (12192  mm)  in 
height,  exterior  flare  fans  or  catch  platforms  shall 
be  erected  at  vertical  intervals  of  not  more  than 
two  stories. 

3304.4.3  Buildings   higher  than  six  stories: 

Where  the  building  being  demolished  or  erected 
is  more  than  six  stories  or  75  feet  (22860  mm)  in 
height,  unless  set  back  from  the  street  lot  line  a 
distance  of  more  than  Vi  of  the  height  of  the 
building,  a  sidewalk  shed  shall  be  provided. 

3304.4.4  Walkway:  An  adequately  lighted 
walkway  at  least  four  feet  (1219  mm)  wide  and 
eight  feet  (2438  mm)  high  in  the  clear  shall  be 
maintained  under  all  sidewalk  sheds  for 
pedestrians.  Where  ramps  are  required,  the  ramps 
shall  conform  to  the  provisions  of  780  CMR  33 
and  780  CMR  1016.0. 

3304.5  Thrust-out  platforms:  Thrust-out  platforms 
or  other  substitute  protection  in  lieu  of  sidewalk 
sheds  shall  not  be  used  unless  approved  and  deemed 
adequate  to  insure  the  public  safety.  Thrust-out 
platforms  shall  not  be  used  for  the  storage  of 
materials. 

3304.6  Watchman:  Wherever  a  building  is  being 
demolished,  erected  or  altered,  a  watchman  shall  be 
employed  to  warn  the  general  public  when 
intermittent  hazardous  operations  are  conducted 
across  the  sidewalk  or  walkway. 

780  CMR  3305.0  FIRE  HAZARDS 

3305.1  General:  The  provisions  of  780  CMR  and  of 
the  527  CMR:  the  Massachusetts  State  Board  of 
Fire  Prevention  Regulations,  listed  in  Appendix  A 

shall  be  strictly  observed  to  safeguard  against  all  fire 
hazards  attendant  upon  construction  operations. 

3305.2  Portable  fire  extinguishers:  All  buildings 
under  construction,  alteration  or  demolition  shall  be 
provided  with  at  least  one  portable  fire  extinguisher 
with  a  minimum  2-A:20-B:C  rating  at  each  exit  on 
all  floor  levels  where  combustible  materials  have 
accumulated.  A  portable  fire  extinguisher  with  a 
minimum  2-A:20-B:C  rating  shall  also  be  provided 
in  every  storage  and  construction  shed.  Additionally, 
at  least  one  portable  fire  extinguisher  shall  be 
provided  in  accordance  with  the  527  CMR:  the 
Massachusetts  State  Board  of  Fire  Prevention 
Regulations,  listed  in  Appendix  A  where  special 
hazards,  such  as  flammable  or  combustible  liquid 
storage,  exist. 

3305.2.1  Steam  boilers:  All  temporary  or 
permanent  high-pressure  steam  boilers  shall  be 
operated,  or  be  in  charge  of  an  individual  in 
possession  of  a  current  engineers  or  fire  mans 
license  in  accordance  with  the  provisions  of 
MG.Lc.  146  and  522  CMR  the  Board  of  Boiler 
Rules  as  listed  in  Appendix  A.      When  such 


boilers  are  located  within  a  building  or  within 
ten  feet  thereof,  all  such  boilers  shall  be 
enclosed  with  approved  noncombustible 
construction. 

3305.3  Standpipes  Standpipes  required  in  buildings 
by  780  CMR  914.0  shall  be  installed  when  the  work 
of  the  building  progresses  more  than  40  feet  (12192 
mm)  above  the  lowest  level  of  fire  department 
vehicle  access.  The  standpipes  shall  be  either 
temporary  or  permanent  in  nature,  and  with  or 
without  a  water  supply,  provided  that  such 
standpipes  conform  to  the  requirements  of  780  CMR 
914.0  as  to  number  of  risers,  capacity,  outlets  and 
materials.  Access  from  the  street  to  such  standpipes 
shall  be  maintained  at  all  times. 

3305.3.1  Height:  The  standpipe  system  shall  be 
carried  up  with  each  floor  and  shall  be  installed 
and  ready  for  use  as  each  floor  progresses. 
Standpipes  shall  be  extended  as  construction 
progresses  to  within  one  floor  of  the  highest  point 
of  construction  having  secured  decking  or 
flooring. 

3305.3.2  Outlets:  Hose  outlets  shall  be  provided 
with  caps  and  attachment  chains. 

3305.3.3  Fire  department  connections:  For  each 
temporary  or  permanent  standpipe  installation, 
there  shall  be  provided,  at  the  street  level,  one  or 
more  two-way  fire  department  inlet  connections. 
Access  shall  be  provided  to  fire  department  inlet 
connections  at  all  times,  and  such  connections 
shall  be  prominently  marked  (see  780  CMR 
915.8). 

3305.3.4  Buildings  under  demolition:  Where  a 
building  is  being  demolished  and  a  standpipe  is 
existing  within  such  a  building,  such  standpipe 
shall  be  maintained  in  an  operable  condition  so  as 
to  be  available  for  use  by  the  fire  department. 
Such  standpipe  shall  be  demolished  with  the 
building  but  shall  not  be  demolished  more  than 
one  floor  below  the  floor  being  demolished. 

780  CMR  3306.0  MAINTENANCE 
3306.1  General:  It  shall  be  unlawful  to  remove  or 
render  inoperative  any  structural,  fire  protection  or 
sanitary  safeguard  or  device  herein  required  except 
where  necessary  for  the  actual  installation  and 
prosecution  of  the  work. 

780  CMR  3307.0  HEALTH  HAZARDS 
3307.1  General:  Every  construction  or  maintenance 
operation  which  results  in  the  diffusion  of  dust, 
stone  and  other  small  particles,  toxic  gases  or  other 
harmful  substances  in  quantities  hazardous  to  health 
shall  be  safeguarded  by  means  of  local  ventilation  or 
other  protective  devices  to  insure  the  safety  of  the 
public  as  required  by  the  regulations  of  the 
administrative  authority. 


442 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

SITE  WORK,  DEMOLITION  AND  CONSTRUCTION 


3307.2  Removal  of  dust:  Dust,  sand  blasts  or  other 
harmful  agents  which  are  used  or  which  occur  in 
construction  operations  shall  be  disposed  of  at  or 
near  the  point  of  origin  to  prevent  diffusion  over 
adjoining  premises  or  streets. 

3307.3  Protective  equipment:  Facilities  shall  be 
provided  in  approved  closed  containers  for  housing 
the  necessary  vision,  respiratory  and  protective 
equipment  required  in  welding  operations,  and  in 
accordance  with  the  regulations  of  the  administrative 
authority. 

780  CMR  3308.0  PROTECTION  OF 
ADJOINING  PROPERTY 

3308.1  General:  Adjoining  property  shall  be 
completely  protected  from  any  damage  caused  by 
the  construction  of  a  structure  when  the  owner  of  the 
adjoining  property  permits  free  access  to  the 
structure  at  all  reasonable  times  to  provide  the 
necessary  safeguards  in  accordance  with  780  CMR 
3310.0. 

780  CMR  3309.0  EXISTING  BWLDEMGS 

3309.1  Protection:  All  adjoining  public  and  private 
property  shall  be  protected  from  damage  caused  by 
construction. 

3309.2  Chimney,  soil  and  vent  stacks:  Wherever  a 
new  building  or  structure  is  erected  to  greater  or 
lesser  heights  than  an  adjoining  building,  the 
construction  and  extension  of  new  or  existing 
chimneys  shall  conform  to  the  provisions  of  the 
mechanical  code  listed  in  Appendix  A,  and  the 
construction  and  extension  of  soil  and  vent  stacks 
and  the  location  of  window  openings  shall  comply 
with  the  provisions  of  780  CMR  2908.3. 

3309.3  Adjoining  walls:  The  owner  of  the  new  or 
altered  structure  shall  preserve  all  adjoining 
independent  and  party  walls  from  damage  as 
provided  for  herein.  The  owner  shall  underpin  where 
necessary  and  support  the  adjoining  building  or 
structure  by  proper  foundations  to  comply  with 
780  CMR  3310.0. 

3309.3.1  Maintenance:  In  case  an  existing  party 
wall  is  intended  to  be  used  by  the  person  who 
causes  an  excavation  to  be  made,  and  such  party 
wall  is  in  good  condition  and  sufficient  for  the  use 
of  both  the  ex;  sting  and  proposed  building,  such 
person  shall  preserve  the  party  wall  from  injury 
and  shall  support  the  party  wall  by  proper 
foundations  at  said  person's  own  expense,  so  that 
the  wall  is  and  remains  as  safe  and  useful  as  the 
party  wall  was  before  the  excavation  was 
commenced.  During  the  demolition,  the  party  wall 
shall  be  maintained  weatherproof  and  structurally 
safe  by  adequate  bracing  until  such  time  as  the 
permanent  structural  supports  have  been  provided. 


3309.3.2  Beam  holes:  Where  a  structure 
involving  a  party  wall  is  being  demolished,  the 
owner  of  the  demolished  structure  shall,  at  his  or 
her  own  expense,  bend  over  all  wall  anchors  at  the 
beam  ends  of  the  standing  wall  and  shall  brick  up 
all  open  beam  holes  and  otherwise  maintain  the 
safety  and  usefulness  of  the  wall. 

3309.3.3  Party  wall  exits:  A  party  wall  balcony 
or  horizontal  exit  shall  not  be  destroyed  unless 
and  until  a  substitute  means  of  egress  has  been 
provided  and  approved. 

3309.4  Adjoining  roofs:  Where  a  new  building  or 
demolition  of  an  existing  building  is  being 
conducted  at  a  greater  height,  the  roof,  roof  outlets 
and  roof  structures  of  adjoining  buildings  shall  be 
protected  against  damage  with  adequate  safeguards 
by  the  person  doing  the  work. 

780  CMR  3310.0  DEMOLITION  AND 
EXCAVATION 

3310.1  Notice  of  intent:  The  person  intending  to 
cause  a  demolition  or  an  excavation  shall  deliver 
written  notice  of  such  intent  to  the  owner  of  each 
potentially  affected  adjoining  lot,  building  or 
structure  at  least  one  week  prior  to  the 
commencement  of  work.  The  notice  shall  request 
license  to  enter  the  potentially  affected  lot,  building 
or  structure  prior  to  the  commencement  of  work  and 
at  reasonable  intervals  during  the  work  to  inspect 
and  preserve  the  lot,  building  or  structure  from 
damage. 

3310.2  Protection    of    adjoining    property:    If 

afforded  the  necessary  license  to  enter  the  adjoining 
lot,  building  or  structure,  the  person  causing  the 
demolition  or  excavation  to  be  made  shall  at  all 
times  and  at  his  or  her  own  expense  preserve  and 
protect  the  lot,  building  or  structure  from  damage  or 
injury.  If  the  necessary  license  is  not  afforded,  it 
shall  be  the  duty  of  the  owner  of  the  adjoining  lot, 
building  or  structure  to  make  safe  his  or  her  own 
property,  for  the  prosecution  of  which  said  owner 
shall  be  granted  the  necessary  license  to  enter  the 
premises  of  the  demolition  or  excavation. 

3310.2.1  Removal  of  debris:  All  waste  materials 
shall  be  removed  in  a  manner  which  prevents 
injury  or  damage  to  persons,  adjoining  properties 
and  public  rights-of-way. 

3310.3  Notice  to  the  code  official:  If  the  person 
causing  a  demolition  or  excavation  to  be  made  is  not 
afforded  license  to  enter  an  adjoining  structure,  that 
person  shall  immediately  notify  in  writing  both  the 
code  official  and  the  owner  of  the  adjoining  property 
that  the  responsibility  of  providing  support  to  the 
adjoining  lot  building  or  structure  has  become  the 
exclusive  responsibility  of  the  owner  of  the 
adjoining  property. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


443 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3310.4  Grading  of  lot:  Where  a  structure  has  been 
demolished  or  removed  and  a  building  permit  has 
not  been  approved,  the  vacant  lot  shall  be  filled, 
graded  and  maintained  in  conformity  to  the 
established  elevation  of  the  street  grade  at  curb  level 
nearest  to  the  point  of  demolition  or  excavation. 
Provision  shall  be  made  to  prevent  the  accumulation 
of  water  or  damage  to  any  foundations  on  the 
premises  or  the  adjoining  property. 

3310.5  Utility  connections:  All  service  utility 
connections  shall  be  discontinued  and  capped  in 
accordance  with  the  approved  rules  and  the 
requirements  of  the  authority  having  jurisdiction. 

780  CMR  3311.0  RETAINING  WALLS  AND 
PARTITION  FENCES 

3311.1  General:  Where  the  adjoining  grade  is  not 
higher  than  the  legal  level,  the  person  causing  an 
excavation  to  be  made  shall  erect,  where  necessary, 
a  retaining  wall  at  his  or  her  own  expense  and  on  his 
or  her  own  land.  Such  wall  shall  be  built  to  a  height 
sufficient  to  retain  the  adjoining  earth,  shall  be 
properly  coped  as  required  in  780  CMR  1825.0  and 
shall  be  provided  with  a  guardrail  or  fence  not  less 
than  42  inches  (1067  mm)  in  height. 

780  CMR  3312.0  STORAGE  OF  MATERIALS 
AND  CONSTRUCTION  EQUIPMENT 

3312.1  General:  The  term  "construction  equipment" 
shall  mean  the  machinery,  tools,  derricks,  hoists, 
scaffolds,  platforms,  runways,  ladders  and  all 
material-handling  equipment,  safeguards  and 
protective  devices  used  in  construction  operations. 
The  term  "runway"  shall  mean  an  aisle  or  walkway 
constructed  or  maintained  as  a  temporary 
passageway  for  pedestrians  or  vehicles.  All 
construction  materials  and  equipment  required  for 
the  permitted  construction  shall  be  stored  and  placed 
so  as  not  to  endanger  the  public,  the  workers  or 
adjoining  property. 

3312.2  Design  capacity:  Construction  materials  and 
equipment  stored  within  the  building,  or  on 
sidewalks  or  sheds,  shall  be  placed  so  as  not  to 
overload  any  part  of  the  construction  beyond  the 
design  capacity,  nor  interfere  with  the  safe 
prosecution  of  the  work. 


3312.3  Pedestrian  walkways:  Construction 
materials  and  equipment  shall  not  be  stored  on  the 
street  without  a  permit  issued  by  the  administrative 
authority  having  jurisdiction.  Where  so  stored,  such 
materials  or  equipment  shall  not  unduly  interfere 
with  vehicular  traffic  or  the  orderly  travel  of 
pedestrians  on  the  highway  or  street.  The  piles  shall 
be  arranged  to  maintain  a  safe  walkway  not  less  than 
four  feet  (1219  mm)  wide,  unobstructed  for  its  full 
length,  and  adequately  lighted  at  night  and  at  all 
necessary  times  for  the  use  of  the  Public. 

3312.4  Obstructions:  Construction  materials  and 
equipment  shall  not  be  placed  or  stored  so  as  to 
obstruct  access  to  fire  hydrants,  standpipes,  fire  or 
police  alarm  boxes,  utility  boxes,  catch  basins  or 
manholes,  nor  shall  such  material  and  equipment  be 
located  within  20  feet  (6096  mm)  of  a  street 
intersection,  or  placed  so  as  to  obstruct  normal 
observations  of  traffic  signals  or  to  hinder  the  use  of 
public  transit  loading  platforms. 

780  CMR  3313.0  REMOVAL  OF  WASTE 
MATERIAL 

3313.1  General:  Material  shall  not  be  dropped  by 
gravity  or  thrown  outside  the  exterior  walls  of  a 
building  during  demolition  or  erection.  Wood  or 
metal  chutes  shall  be  provided  for  the  removal  of 
such  materials.  Where  the  removal  of  any  material 
will  cause  an  excessive  amount  of  dust,  such 
material  shall  be  wet  down  to  prevent  the  creation  of 
a  nuisance. 

780  CMR  3314.0  STAIRWAYS 

3314.1  Temporary  stairways:  Where  a  building  has 
been  constructed  to  a  height  greater  than  50  feet 
(15240  mm)  or  four  stories,  or  where  an  existing 
building  exceeding  50  feet  (15240  mm)  in  height  is 
altered,  at  least  one  temporary  lighted  stairway  shall 
be  provided  unless  one  or  more  of  the  permanent 
stairways  are  erected  as  the  construction  progresses. 

780  CMR  3315.0  LIGHTING 
3315.1  General:  All  stairways  and  parts  of 
buildings  under  demolition,  erection  or  repair  shall 
be  adequately  lighted  while  persons  are  engaged  at 
work,  in  accordance  with  the  provisions  of 
780  CMR  1024.0  and  2702.2.5. 


444 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CHAPTER  34 


REPAIR,  ALTERATION,  ADDITION,  AND  CHANGE  OF  USE 
OF  EXISTING  BUILDINGS 

(780  CMR  34  is  entirely  unique  to  Massachusetts) 


780  CMR  3400.0  SCOPE 

3400.1  General:  The  provisions  of  780  CMR  34  are 
intended  to  maintain  or  increase  public  safety, 
health,  and  general  welfare  in  existing  buildings  by 
permitting  repair,  alteration,  addition,  and/or  change 
of  use  without  requiring  full  compliance  with  the 
code  for  new  construction  except  where  otherwise 
specified  in  780  CMR  34. 

3400.2  Compliance:  Repairs,  alterations,  additions, 
and  changes  of  use  shall  conform  to  the 
requirements  of  780  CMR  34.  Where  compliance 
with  the  provisions  of  this  code  for  new  construction 
is  required  by  780  CMR  34,  and  where  such 
compliance  is  impractical  because  of  construction 
difficulties  or  regulatory  conflicts,  compliance 
alternatives  as  described  in  780  CMR  3406.0  may 
be  accepted  by  the  building  official. 

Note:  Specialized  codes,  rules,  regulations,  and 
laws  pertaining  to  repair,  alteration,  addition,  or 
change  of  use  of  existing  buildings  promulgated 
by  various  authorized  agencies  may  impact  upon 
the  provisions  of  780  CMR  34.  Specialized  state 
codes,  rules,  regulations,  and  laws  include,  but  are 
not  limited  to  those  listed  in  Appendix  A. 

3400.3  Applicability:  The  provisions  of  780  CMR 
34  apply  to  repair,  alteration  addition  or  change  in 
use  to  existing  buildings  which  qualify  to  use 
780  CMR  34  (see  780  CMR  3400. 3 . 1 ),  based  on  the 
proposed  continuation  of,  or  change  in  use  group,  as 
follows: 

1 .  Continuation  of  the  same  use  group,  or  a 
change  in  use  group  which  results  in  a  change  in 
hazard  index  of  one  or  less  as  determined  by 
780  CMR  3403  shall  comply  with  780  CMR 
3404.0. 

2.  Change  in  use  group  to  a  use  group  with 
hazard  index  of  two  or  more  greater  than  the 
hazard  index  of  the  existing  use  shall  comply  with 
the  requirements  of  780  CMR  3405.0  and  the 
code  for  new  construction. 

3.  Part  change  in  use  (Mixed  Use):  Portions  of 
the  building  is  changed  to  a  new  use  group,  shall 
be  separated  from  the  remainder  of  the  building 
with  fire  separation  assemblies  complying  with 
780  CMR  313,  or  with  approved  compliance 
alternatives.  The  portion  of  the  building  changed 
shall  be  made  to  conform  with  the  applicable 
provisions  of  780  CMR  34. 

4.  Additions:  Additions  to  existing  buildings 
shall  comply  with  all  code  requirements  for  new 


construction,  except  as  otherwise  provided  in 
780  CMR  34.  The  combined  height  and  area  of 
the  existing  building  and  the  addition  shall  not 
exceed  that  allowed  by  780  CMR  503.0  and  Table 
503  as  modified  by  780  CMR  504  and  506. 
Where  afire  wall  complying  with  780  CMR  707.0 
and  708.0  is  provided,  the  addition  shall  be 
considered  as  a  separate  building. 

5.  Ordinary  repairs:  Ordinary  repairs  conforming 
to  780  CMR  1 10.3  (4),  780  CMR  2  and  780  CMR 
902  may  be  performed  without  a  building  permit. 

6.  Assembly  use  groups:  A  change  from  any 
other  use  group  to  an  assembly  use  group  (A)  or 
any  alteration  or  change  in  occupancy  within  an 
assembly  use  group  shall  comply  with  the 
requirements  of  the  code  for  new  construction, 
except  that  earthquake  requirements  need  only 
conform  to  780  CMR  3408. 

7.  Institutional  use  groups:  A  change  from  any 
other  use  group  to  an  institutional  use  group  (I)  or 
any  alteration  or  change  in  occupancy  within  an 
institutional  use  group  shall  comply  with  the 
requirements  of  the  code  for  new  construction, 
except  that  earthquake  requirements  need  only 
conform  to  780  CMR  3408. 

8.  Residential  use  groups:  A  change  from  any 
other  use  group  to  a  residential  use  group  (R)  or 
any  alteration  or  change  in  occupancy  within  an 
residential  use  group  shall  comply  with  the 
requirements  of  the  code  for  new  construction, 
except  that  earthquake  requirements  need  only 
conform  to  780  CMR  3408. 

9.  Historic  buildings:  Buildings  which  qualify 
as  totally  or  partially  preserved  historic  buildings 
in  accordance  with  780  CMR  3409  shall  meet  the 
provisions  of  780  CMR  3409. 

10.  Structural  requirements:  Structural 
requirements  for  additions,  and  for  existing 
buildings  subject  to  repair,  alteration,  and/or 
change  of  use,  shall  be  in  accordance  with 
780  CMR  3408. 

Exceptions:  Totally  Preserved  and  Partially 
Preserved  Historic  Buildings 

3400.3.1     Buildings    which     qualify:         The 

provisions  of  780  CMR  34  shall  apply  to  existing 
buildings  which  have  been  legally  occupied 
and/or  used  for  a  period  of  at  least  five  years. 
Any  building  for  which  there  exists  an 
outstanding  notice  of  violation  or  other  order  of 
the  building  official  shall  not  qualify  to  use 
780  CMR  34  unless  such  proposed  work  includes 
the  abatement  of  all  outstanding  violations  and 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


compliance  with  all  outstanding  orders  of  the 
building  official.  Buildings  which  do  not  qualify 
as  existing  buildings  for  the  purposes  of  780  CMR 
34  shall  comply  fully  with  the  applicable 
provisions  of  this  code  for  new  construction. 

Exceptions: 

(1)  Existing  buildings  or  portions  thereof 
which  are  changed  in  use  from  any  other  use 
group  to  day  care  centers  (1-2  or  E)  shall  not 
qualify  as  existing  buildings  for  the  purposes  of 
780  CMR  34,  but  shall  comply  with  the 
requirements  of  780  CMR  4,  as  applicable. 

(2)  Existing  buildings  or  portions  thereof, 
which  are  changed  in  use  from  any  use  to  a 
Group  Residence,  Limited  Group  Residence  or 
Group  Dwelling  Unit  shall  not  qualify  as 
existing  buildings  for  the  purposes  of  780 
CMR  34,  but  shall  comply  with  the  provisions 
of  780  CMR  4,  as  applicable. 

3400.4  Special  Provisions  for  Means  of  Egress: 

3400.4.1  Existing  Non  Conforming  Means  of 
Egress:  The  following  conditions,  when 
observed  by  the  building  official,  shall  be  cited,  in 
writing  as  a  violation.  Said  citation  shall  order 
the  abatement  of  the  non  conformance  and  shall 
include  such  a  time  element  as  the  building 
official  deems  necessary  for  the  protection  of  the 
occupants  thereof,  or  as  otherwise  provided  for  by 
statute. 

1.  Less  than  the  number  of  means  of  egress 
serving  every  space  and/or  story,  required  by 
780  CMR  1010.0  and  Table  1010.2,  or 
780  CMR  36  for  one  and  two  family  dwellings. 

2.  Any  required  means  of  egress  component 
which  is  not  of  sufficient  width  to  comply  with 
780  CMR  1009,  or  is  not  so  arranged  as  to 
provide  safe  and  adequate  means  of  egress, 
including  exit  signage  and  emergency  lighting. 

3400.5  Hazardous  Means  of  Egress: 

3400.5.1  Exit  Order/Hazardous  Means  of 
Egress:  In  any  existing  building  or  structure  not 
provided  with  exit  facilities  as  herein  prescribed 
for  new  buildings  and  in  which  the  exits  are 
deemed  hazardous  or  dangerous  to  life  and  limb, 
the  building  official  shall  declare  such  building 
dangerous  and  unsafe  in  accordance  with  the 
provisions  of  780  CMR  121.0. 

3400.5.2  Appeal  from  exit  order:  Any  person 
served  with  any  order  pursuant  to  780  CMR 
3400.5  shall  have  the  remedy  prescribed  in 
780  CMR  121. 

3400.6  Unsafe  Lighting  and/or  Unsafe 
Ventilation:  In  any  existing  building  ,  or  portion 
thereof,  in  which  (a)  the  light  or  ventilation  do  not 
meet  the  applicable  provisions  of  780  CMR  12.0  and 
(b)  which,  in  the  opinion  of  the  building  official,  are 


dangerous,  or  hazardous,  to  the  health  and  safety  of 
the  occupants,  the  building  official  shall  order  the 
abatement  of  such  conditions  to  render  the  building 
or  structure  livable  for  the  posted  use  and  occupant 
load. 

In  enforcing  the  provisions  of  780  CMR  3400.6 
the  building  official  may  require  or  accept 
engineering  or  other  evaluations  of  the  lighting 
and/or  ventilation  systems  in  order  to  evaluate 
possible  dangerous  or  hazardous  conditions  and 
acceptable  solutions. 

Where  full  compliance  with  780  CMR  for  new 
construction  is  not  practical  for  structural  and/or 
other  technical  reasons,  the  building  official  may 
accept  compliance  alternatives,  or  engineering  or 
other  evaluations  which  adequately  address  the 
building  or  structure  livability  for  the  posted  use  and 
occupant  load. 

780  CMR  3401.0  DEFINITIONS 
3401.1  General:  Definitions  shall,  for  the  purposes 
of  780  CMR  3401.0,   have  the  meaning  shown 
herein: 

Building  System:  Any  mechanical,  structural,  egress, 
electrical,  plumbing,  building  enclosure  and/or 
fire  protection  system,  or  fire  resistive 
construction  system,  or  portion  thereof. 

Building  System  Component:  A  part  or  portion  of  a 
building  system. 

Compliance  Alternative:  An  alternative  life-safety 
construction  feature  which  meets  or  exceeds  the 
requirements  or  intent  of  a  specific  provision  of 
780  CMR.  The  Building  Official  is  authorized  to 
approve  or  disapprove  compliance  alternatives. 
Compliance  alternatives  are  only  permitted  for 
existing  buildings. 

Existing  building  or  structure:  Any  building  or 
structure  qualifying  under  780  CMR  3400.3.1. 

Hazard  Index:  A  numerical  value,  between  1  and  8, 
which  is  assigned  to  a  specific  Use  Group  in  order 
to  determine  which  of  the  provisions  of  780  CMR 
34  apply  to  the  proposed  work  on  the  existing 
building.  The  Hazard  Index  is  a  relative  scale 
used  only  to  determine  applicable  provisions  of 
780  CMR  34.  Hazard  indices  are  listed  in  Table 
3403  and  Appendix  F. 

Historic  buildings:  (a)  Any  building  or  structure 
individually  listed  on  the  National  Register  of 
Historic  Places  or  (b)  any  building  or  structure 
evaluated  by  MHC  to  be  a  contributing  building 
within  a  National  Register  or  State  Register 
District  (c)  any  building  or  structure  which  has 
been  certified  by  the  Massachusetts  Historical 
Commission  to  meet  eligibility  requirements  for 
individual   listing  on  the  National   Register  of 


446 


780  CMR  -  Sixth  Edition 


2/10/97    (Effective  2/28/97) 


780  CMR;    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


Historic  Places.  Historic  building  shall  be  further 
defined  as  totally  or  partially  preserved  buildings 
All  entries  into  the  totally  preserved  building  list 
shall  be  certified  by  the  Massachusetts  Historical 
Commission.  The  Board  of  Building  Regulations 
and  Standards  shall  ratify  all  buildings  or 
structures  certified  by  the  Massachusetts 
Historical  Commission  to  qualify  for  totally- 
preserved  listing  (see  Appendix  H). 

Partially  preserved  buildings:  (a)  Any  building  or 
structure  individually  listed  on  the  National 
Register  of  Historic  Places  or  (b)  any  building 
or  structure  certified  as  a  historic  building  by 
the  Massachusetts  Historical  (Comrrussion/t 
and  not  designated  a  totally  preserved  building 
in  Appendix  H 

Restoration  Restoration  is  the  process  of 
accurately  reconstructing  or  repairing  the 
forms  and  details  of  a  building  or  structure  or 
portion  thereof  as  it  appeared  at  a  particular 
period  or  periods  of  time  by  means  of  removal 
of  later  work/or  the  replacement  of  missing 
original  work 

Totally  preserved  buildings:  A  totally  preserved 
building  is  an  historic  building  or  structure 
The  principal  use  of  such  a  building  or 
structure  must  be  as  an  exhibit  of  the  building 
or  the  structure  itself  which  is  open  to  the 
public  not  less  than  12  days  per  year,  although 
additional  uses,  original  and/  or  ancillary  to  the 
principal  use  shall  be  permitted  within  the 
same  building  up  to  maximum  of  40%  of  the 
gross  floor  area  Totally  preserved  buildings 
shall  be  those  listed  in  Appendix  H.  All  entries 
into  the  totally  preserved  building  list  shall  be 
certified  by  the  Massachusetts  Historical 
Commission.  The  Board  of  Building 
Regulations  and  Standards  shall  ratify  all 
buildings  or  structures  certified  by  the 
Massachusetts  Historical  Commission  to 
qualify  for  totally  preserved  listing  (See 
Appendix  H). 

Seismic  Hazard  Category:  A  numerical  value, 
between  1  and  3,  which  is  based  on  a  proposed 
change  in  use,  change  in  occupancy  and  cost  of 
alterations  in  order  to  determine  which  of  the 
provisions  of  780  CMR  3408  apply  to  the 
proposed  work  on  the  existing  building  The 
Seismic  Hazard  Category  is  a  relative  scale  used 
only  to  determine  applicable  provisions  of 
780  CMR  34.  Seismic  Hazard  Categories  are 
listed  in  Table  3408.1 

Substantial  Renovation,  or  Substantial  Alteration: 
The  terms  substantial  renovation  and  substantial 
alteration  are  defined  herein  for  the  specific 
purpose  of  determining  whether  fire  protective 
systems  are  required  in  existing  buildings,  when 
such  buildings  undergo  renovations  or  alterations. 


change  in  use  or  occupancy  or  additions.  As 
used  in  780  CMR  34,  substantial  renovation  or 
substantial  alteration  shall  have  the  following 
meanings;  Substantial  renovation  and  substantial 
alteration  is  work  which  is  major  in  scope  and 
expenditure  when  compared  to  the  work  and 
expenditure  required  for  the  installation  of  a  fire 
protection  system,  when  such  system  is  required 
by  780  CMR  9  for  a  particular  use  group  The 
building  official  shall  make  such  determination 
and  may  request  the  owner  or  applicant  to  provide 
such  supporting  information  as  is  necessary  to 
make  such  determination 

780  CMR  3402.0  IMPLEMENTATION 
3402.  {.  Building  Permit  Application 

Requirements  for  Existing  Buildings  A  building 
permit  shall  be  required  for  any  work  regulated  bv 
780  CMR  34. 

Exception:  Ordinary  repairs  may  be  performed 
without  a  building  permit 

3402.1.1  Investigation  and  evaluation:   For  any 

proposed  work  regulated  by  780  CMR  34.  which 
is  subject  to  780  CMR  1 16,  as  a  condition  of  the 
issuance  of  a  building  permit  the  building  owner 
shall  cause  the  existing  budding  (or  portion 
thereof)  to  be  investigated  and  evaluated  in 
accordance  with  the  provisions  of  780  CMR  34 
(see  Appendix  F). 

The  investigation  and  evaluation  shall  be  in 
sufficient  detail  to  ascertain  the  effects  of  the 
proposed  work  (if  any)  on  the  structural,  egress, 
fire  protection,  energy  conservation  systems  and 
light  and  ventilation  systems  of  the  space  under 
consideration  and,  where  necessary,  the  entire 
building  or  structure 

3402.1.2  Submittal:  The  results  of  the 
investigation  and  evaluation,  along  with  any 
proposed  compliance  alternatives,  shall  be 
submitted  to  the  building  official  in  written  report 
form. 

3402.1.3  Non  Conformities  and  Compliance 
Alternatives:  The  application  for  a  building 
permit  shall  identify  all  items  of  non  or  partial 
compliance  with  the  requirements  of  780  CMR 
34,  and  compliance  alternatives,  if  any  are 
proposed,  for  approval  by  the  building  official. 
The  building  official  shall  respond  to  the 
acceptability  of  any  proposed  compliance 
alternatives  within  30  days  of  the  filing  of  the 
building  permit  application.  Where  proposed 
compliance  alternatives  are.  in  the  opinion  of  the 
building  official,  unacceptable,  or  where  issues  of 
non-compliance  remain,  the  permit  applicant  shall 
have  the  remedies  prescribed  by  780  CMR  122.0. 

3402.1.5  Documentation  of  compliance 
alternatives  Whenever  action  is  taken  on  any 
building    permit    application    to    repair,    make 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


447 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


building  permit  application  to  repair,  make 
alterations  or  additions,  or  change  the  use  or 
occupancy  of  an  existing  building,  and  when  said 
application  proposes  the  use  of  compliance 
alternatives,  the  building  official  shall  ensure  that 
one  copy  of  the  proposed  compliance  alternatives, 
including  applicable  plans,  test  data,  or  other  data 
for  evaluation,  be  submitted  to  the  BBRS, 
together  with  a  copy  of  the  building  permit 
application  and  the  building  official's  decision 
regarding  the  proposed  compliance  alternatives. 

780  CMR  3403.0  HAZARD  INDEX 

3403.1  Hazard  Index  In  the  implementation  of  the 
provisions  of  780  CMR  34,  the  hazard  index 
associated  with  a  particular  use  group  shall  be  as 
identified  in  table  3403  and  Appendix  F.  In  order 
to  determine  the  applicable  provisions  of  780  CMR 
34  the  hazard  index  of  the  existing  use  group  shall 
be  subtracted  from  the  hazard  index  of  the  proposed 
use  The  algebraic  difference  shall  be  used  to 
determine  the  applicable  provisions  of  780  CMR  34 
Table  3403 
HAZARD  INDEX  


USE  (1) 

DESCRIPTION 

HAZARD 
INDEX 

NO.(2) 

A-] 

Theater  with  stage 

6 

A-2 

Night  Club 

7 

A-3 

Theater  without  stage 

5 

A-3 

Restaurant 

5 

A-3 

Lecture  halls,  recreations  centers, 
museums,  libraries,  similar 
assembly  buildings 

4 

A-4 

Churches 

4 

B 

Business 

2 

E 

Educational  (K  through  1 2) 

4 

F 

Factory  and  industrial 

3 

H 

High  hazard 

8 

1-1,1-3 

Institutional  restrained 

5 

1-2 

Institutional  incapacitated 

4 

M 

Mercantile 

3 

R-l 

Hotels,  motels 

2 

R-2 

Multi-family 

2 

R-3 

One  and  two  familv 

2 

S-l 

Storage,  moderate  hazard 

3 

S-2 

Storage,  low  hazard 

1 

Notes  to  Table  3404: 

(1)  See  780  CMR  3  and  4  and  Appendix  F. 

(2)  Hazard  Index  Modifier  for  selected  construction 
types  as  follows: 

(a)  When  a  building  is  classified  in  construction  Type 
1A,  IB,  2A,  or  2B,  subtract  one  from  the  Hazard  index 
shown  in  Table  3403  for  the  applicable  proposed  new 
use  group  only. 

(b)  When  a  building  is  classified  in  construction  Type 
2C  or  5B,  add  one  to  the  Hazard  index  shown  tn 
Table  3403  for  the  applicable  proposed  new  use  group 
only.  Exception:  Partially  Preserved  Historic 
Buildings  (780  CMR  3409). 


780  CMR  3404.0  REQUIREMENTS  FOR 

CONTINUATION  OF  THE  SAME  USE 

GROUP  OR  CHANGE  TO  A  USE  GROUP 

RESULTING  IN  A  CHANGE  IN  HAZARD 

INDEX  OF  ONE  OR  LESS 

3404.1  General:  The  requirements  of  780  CMR 
3404.0  and  applicable  provisions  of  780  CMR  3408 
shall  apply  to  all  repairs  and  alterations  to  existing 
buildings  having  a  continuation  of  the  same  use 
group  or  to  existing  buildings  changed  in  use  group 
of  one  or  less  hazard  index  (Table  3403) 

3404.2  Requirements  exceeding  those  required 
for  new  construction:  Existing  buildings  which,  in 
part  or  as  a  whole,  exceed  the  requirements  of 
780  CMR  may  be  altered^  in  the  course  of 
compliance  with  780  CMR  34,  so  as  to  reduce  or 
remove,  in  part  or  completely,  features  not  required 
by  this  code  for  new  construction. 

Exception:  Pursuant  to  M.G.L.  c.  148,  §  27 A 
fire  protection  devices,  shall  not  be  disconnected 
(temporarily  or  permanently),  obstructed, 
removed  or  shut  off  or  destroyed  without  first 
procuring  a  written  permit  from  the  head  of  the 
local  fire  department 

3404.3  New  building  systems:  Any  new  building 
system  or  portion  thereof  shall  conform  to  780  CMR 
for  new  construction  to  the  fullest  extent  practical. 
However,  individual  components  of  an  existing 
building  system  may  be  repaired  or  replaced  without 
requiring  that  system  to  comply  fully  with  the  code 
for  new  construction  unless  specifically  required  by 
780  CMR  3408 

3404.4  Alterations  and  repairs:  Alterations  or 
repairs  to  existing  buildings  which  maintain  or 
improve  the  performance  of  the  building  may  be 
made  with  the  same  or  like  materials,  unless 
required  otherwise  by  780  CMR  3408  Alterations 
or  repairs  which  have  the  effect  of  replacing  a 
building  system  as  a  whole  shall  comply  with 
780  CMR  3404.3 

3404.5  Number  of  Means  of  Egress  Every  floor  or 
story  of  any  existing  building  shall  provide  at  least 
the  number  of  means  of  egress  as  required  by 
780  CMR  3400.4  and  which  are  acceptable  to  the 
building  official. 

3404.6  Capacity  of  exits:  All  required  means  of 
egress  shall  comply  with  780  CMR  1009.0.  Existing 
means  of  egress  may  be  used  to  contribute  to  the 
total  egress  capacity  requirement  based  on  the  unit 
egress  widths  of  780  CMR  1009.0. 

3404.7  Exit  signs  and  lights:  Exit  signs  and 
lighting  shall  be  provided  in  accordance  with 
780  CMR  1023.0. 


448 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR,  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


3404.8  Means  of  egress  lighting:  Means  of  egress 
lighting  shall  be  provided  in  accordance  with 
780  CMR  1024.0. 

3404.9  Height  and  Area  limitations:  The  height 
and  area  requirements  of  780  CMR  5  shall  apply  to 
existing  buildings  when  such  existing  buildings  are 
modified  by  addition  and/or  change  in  use. 
Modifications  to  the  height  and  area  requirements  as 
provided  in  780  CMR  504.0  and  506.0  are 
permitted. 

3404.10  Existing  Fire  and  party  walls:  No  further 
compliance  is  required  with  780  CMR  707.0.  The 
height  above  the  roof  of  existing  fire,  party  and 
exterior  walls  need  not  comply  with  780  CMR 
3404.0 

3404.11  Fire  Protection  Systems:  Fire  Protection 
Systems:  Design,  installation  and  maintenance  of 
fire  protection  systems  shall  be  provided  in 
accordance  with  780  CMR  3404.3  and  780  CMR 
3404.12.1  as  applicable. 

3404.12  Fire  protection  systems  are  required  for 
the  following  cases: 

1 .  Additions  where  required  by  780  CMR  9.0  for 
the  specific  use  group. 

2.  For  existing  buildings  and  additions  to  existing 
buildings,  where  required  by  780  CMR  9  or 
where  required  by  780  CMR  506  to  satisfy  height 
and  area  requirements. 

3.  Existing  buildings,  or  portions  thereof  which 
are  substantially  altered  or  substantially 
renovated,  and  where  otherwise  required  by 
780  CMR  9.0  for  the  specific  use  group. 

Note:  Notwithstanding  the  provisions  of 
780  CMR  3404.10,  automatic  Fire  Suppression 
systems  are  required  in'municipalities  which  have 
adopted  the  provisions  of  MGL  cl48  §  26G,  H  or 
I  (See  Official  Interpretation  Number  45-96  listed 
in  Appendix  B). 

3404.13  Enclosure  of  stairways:  Open  stairways 
are  prohibited  except  in  one-  and  two-family 
dwellings  or  unless  otherwise  permitted  by 
780  CMR  10.  There  shall  be  no  minimum 
fireresistance  rating  required  for  an  existing 
enclosure  of  a  stairway.  Partitions  or  other  new 
construction  which  is  added  in  order  to  fully  and 
solidly  enclose  a  stairway  shall  provide  a  minimum 
fireresistance  rating  of  one  hour.  All  doors  in  the 
enclosure  shall  be  self-closing  and  tight-fitting  with 
approved  hardware.  All  doors  in  those  portions  of 
the  stairway  which  are  fireresistance  rated  shall 
comply  to  the  applicable  provisions  of  780  CMR  9. 

3404.14  Assembly  Use  Groups:  Notwithstanding 
the  provisions  of  780  CMR  3404,  Assembly  Use 
Groups  shall  comply  with  the  provisions  of 
780  CMR  3400.3,  item  6. 


3404.15  Institutional  Use  Groups:  Notwithstanding 
the  provisions  of  780  CMR  3404,  Institutional  Use 
Groups  shall  comply  with  the  provisions  of 
780  CMR  3400.3,  item  7. 

3404.16  Residential  Use  Groups:  Notwithstanding 
the  provisions  of  780  CMR  3404,  Residential  Use 
Groups  shall  comply  with  the  provisions  of 
780  CMR  3400.3,  item  8. 

3404.17  Fire  hazard  to  adjacent  buildings:    Any 

proposed  change  in  the  use  or  occupancy  of  an 
existing  building  which  has  the  effect  of  increasing 
the  fire  hazard  to  adjacent  buildings  shall  comply 
with  the  requirements  of  Table  705.2  for  exterior 
wall  fire  resistance  rating  requirements,  or  with 
approved  compliance  alternatives. 

3404.18  Accessibility  for  Persons  with 
Disabilities:  Accessibility  requirements  shall  be  in 
accordance  with  521  CMR  as  listed  in  Appendix  A. 

3404.19  Energy  Conservation:  Energy 
conservation  requirements  shall  be  in  accordance 
with  780  CMR  3407.0. 

780  CMR  3405.0  REQUIREMENT  FOR 
CHANGE  IN  USE  GROUP  TO  TWO  OR 
MORE  HAZARD  INDICES  GREATER 

3405.1  General:  When  the  existing  use  group  is 
changed  to  a  new  use  group  of  two  or  more  hazard 
indices  higher  (as  provided  in  Table  3403),  the 
existing  building  shall  conform  to  the  requirements 
of  the  code  for  new  construction,  except  as  provided 
in  780  CMR  3408. 

3405.2  Accessibility  for  Persons  with  Disabilities. 

Accessibility  requirements  shall  be  in  accordance 
with  521  CMR  as  listed  in  Appendix  A. 

780  CMR  3406.0  COMPLIANCE 
ALTERNATIVES 

3406.1  General:  Where  compliance  with  the 
provisions  of  the  code  for  new  construction,  required 
by  780  CMR  34,  is  impractical  because  of 
construction  difficulties  or  regulatory  conflicts, 
compliance  alternatives  may  be  accepted  by  the 
building  official. 

Examples  of  compliance  alternatives  which  have 
been  used  are  provided  in  Appendix  F.  The 
building  official  may  accept  these  compliance 
alternatives  or  others  proposed. 

3406.2  Documentation:  In  accordance  with 
780  CMR  3402.5.  the  building  official  shall  ensure 
that  the  BBRS  is  provided  with  information 
regarding  compliance  alternatives  accepted  or 
rejected  by  the  building  official. 


llim  .  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  3407.0  ENERGY  PROVISIONS 
FOR  EXISTING  BUILDINGS 

3407.1  General:  780  CMR  3407.0  establishes  the 
energy  provisions  for  existing  buildings  governed  by 
780  CMR  3404.0.  Existing  buildings  governed  by 
780  CMR  3404.0,  3405.0,  or  by  the  code  for  new 
construction  shall  comply  with  the  requirements  of 
780  CMR  13  for  new  construction. 

3407.2  Compliance:  Alterations  to  any  building 
component  affecting  energy  conservation 
performance  of  an  existing  building  shall  comply 
with: 

(a)  780  CMR  3407,  Table  3407  (COMPONENT 
VALUES  FOR  ALTERED  ELEMENTS)  and  all 
applicable  subsections  of  780  CMR  13.0,  or; 

(b)  780  CMR  1314.4  for  thermal  envelope 
requirements  and  all  other  applicable 
requirements  of  780  CMR  13.0,  or; 

(c)  780  CMR  1314.5  for  thermal  envelope 
requirements  and  all  other  applicable 
requirements  of  780  CMR  13.0,  or; 

(d)  780  CMR  13 15.0  in  its  entirety,  or; 

(e)  780  CMR  1315.0  as  supplemented  by 
780  CMR  1316.0 


3407.3  Exempt  buildings:     Refer  to  780  CMR 

1301.4  for    thermally     exempt     buildings     and 
780  CMR  1313.1.2  for  lighting  exemptions. 

3407.4  Compliance  exceptions 

3407.4.1  Fenestration:  When  alterations  to  a 
wall  assembly  include  only  altering  the 
fenestration  component,  the  areas  of  fenestration 
may  be  decreased  or  replaced  with  an  opaque  wall 
element  made  to  comply  with  the  thermal 
transmittance  value  of  the  existing  wall. 

3407.4.2  Ordinary  repairs:  Ordinary  repairs 
need  not  comply  with  the  energy  provisions. 

3407.4.3  Roofs:  Compliance  of  the  roof/ceiling 
assembly  is  not  required  unless  the  existing 
roofing  material  is  stripped  off  the  roof  deck. 
However,  if  a  structural  analysis  by  a  registered 
professional  engineer  shows  that  the  roof  will  not 
support  the  additional  live  loads  imposed  by 
compliance  of  the  roof/ceiling  assembly,  or,  if 
such  analysis  shows  that  addition  of  the  required 
amount  of  insulation  will  cause  ponding  of  water, 
then  compliance  of  the  roof/ceiling  assembly  is 
not  required. 


TABLE  3407 
COMPONENT  VALUES  FOR  ALTERED  ELEMENTS 


WALLS 

All  wall  construction  containing  heated  or  mechanically  cooled  space 

0.08 

6,8 

Foundation  Walls 
Including  Band 

Containing  heated  or  mechanically  cooled  space 
Containing  unheated  space 

0.08 
0.17 

4 

Roof/Ceiling  Assembly 

Wood  plank  and  beam  construction  containing  heated  or  mechanically 
cooled  space 

0.08 

1 

Roof/Ceiling  Assembly 

Construction  other  than  wood  plank  and  beam  containing  heated  or 
mechanically  cooled  space 

0.05 

Doors,  Skylights  and 
Windows 

All  construction  enclosing  heated  or  mechanically  cooled  space 

0.65 
0.65 

2,7 
5 
6 

Floors 

Floor  sections  over  area  exposed  to  outside  air  or  unheated  areas 
Unheated  slab  on  grade 
Heated  slab  on  grade 

0.08 
5.50  (R) 
7.75  (R) 

3 

Mechanical  Equipment 

Heating,  cooling,  sizing  and  efficiency 

780  CMR  1310.0, 
13 1 1.0 

9 

Equipment  Controls 

Humidistats,  thermostats  &  zoning 

780  CMR  1310.0 

9 

Duct  and  Pipe 
Insulation  and 
Construction 

Located  in  or  on  buildings 

7S0CMR  1310.0 
1310.0 

Electrical  Distribution. 

- 

780  CMR  1312.0 
1312.3 

Lighting 

Lighting 

780  CMR  1313.0 

Note  1.  Wood  plank  and  beam  assemblies  are  constructions  in  which  the  finished  interior  surface  is  the  underside  of 

the  roof  deck. 

Note  2.  Double  glazing  or  storm  windows  will  satisfy  the  required  U  Value  of  0.65. 

Note  3.  Insulation  may  be  omitted  from  floors  over  unheated  areas  when  foundation  walls  are  provided  with  a  U  value 

of  0.17. 

Note  4.  The  U  value  requirement  of  0. 1 7  for  foundation  walls  may  be  omitted  when  floors  over  unheated  spaces  are 

provided  with  a  U  value  of  0.08. 

Note  5.  Allowable  air  infiltration  values  for  windows  -  .50  cfm/lin.  ft.  of  operable  sash  crack;  residential  doors  - 

(sliding)  .50  cfm/sf,  (entrance)  1.25  cfm/sf.;  commercial  doors   1 1  cfm/lin. ft. 


450 


780  CMR-  Sixth  Edition 


2/10/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 

Note  6.  The  first  floor  exterior  envelope  of  business  and  mercantile  use  groups  shall  have  an  overall  thermal 

transmittance  value  not  greater  than  .65  in  lieu  of  individual  component  values  for  walls  and  fenestration. 

Note  7.  When  the  glass  area  is  increased,  the  glass  and  wall  components  which  are  altered  shall  comply  with  the 

component  values  in  Table  3407.  The  extent  of  wall  made  to  comply  shall  be  equivalent  to  the  decreased  opaque  wall 

area. 

Note  8.  When  any  alterations  to  the  exterior  wall  component  exposes  the  wall  cavity  or,  when  a  finished  system  is 

added  to  a  wall  having  no  cavity,  the  wall  must  comply  with  the  values  in  Table  3407. 

Note  9.  When  mechanical  system  compliance  is  required  on  an  existing  system,  only  the  portions  of  the  system  altered 

and  any  other  portions  which  can  reasonably  be  incorporated  need  comply. 


780  CMR  3408.0  STRUCTURAL 

REQUIREMENTS  FOR  EXISTING 

BUILDINGS 

3408.1  General  Requirements 

3408.1.1  Buildings  Constructed  on  or  after 
January  1,  1975:  The  structural  systems  of 
existing  buildings  which  were  constructed  under 
a  building  permit  issued  on  or  after  lanuary  1, 
1975  shall  conform  to  the  requirements  for  new 
construction  of  either  the  current  edition  of 
780  CMR  (the  Massachusetts  State  Building 
Code),  or  to  the  edition  in  effect  on  the  date  of  the 
permit  plus  applicable  provisions  of  780  CMR 
3408.0  of  the  current  edition  of  the  code. 
Provisions  of  780  CMR  3408.0  which  are  less 
stringent  than  the  code  in  effect  on  the  date  of  the 
permit  shall  not  apply. 

3408.1.2  Buildings  Constructed  prior  to 
January  1,  1975:  The  structural  systems  of 
existing  buildings  constructed  under  a  building 
permit  issued  prior  to  lanuary  1,  1975  shall 
conform  to  780  CMR  3408.0  and  the  building 
code  applicable  at  the  time  of  the  original  building 
permit.  In  the  event  of  conflict  between  the  prior 
code  and  780  CMR  3408.0,  the  provisions  of 
780  CMR  3408.0  shall  govern. 

3408.1.3  Structural  Engineering  Services:  For 

buildings  subject  to  construction  control,  as 
determined  in  780  CMR  116,  the  Owner  shall 
retain  a  registered  professional  engineer  qualified 
in  the  structural  design  of  buildings  (hereinafter 
called  the  structural  engineer)  to  perform  all 
structural  engineering  required  by  780  CMR.  For 
purposes  of  determining  applicability  of 
construction  control,  the  volume  of  enclosed 
space  shall  include  the  entire  existing  building 
and  all  proposed  additions.  (See  780  CMR  1 16. 1 
for  buildings  exempt  from  construction  control.) 

3408.2  Evaluation   of  Existing  Buildings:   The 

structural  engineer  shall  make  a  structural  evaluation 
of  the  existing  building  to  determine  the  adequacy  of 
all  structural  systems  that  are  affected  by  alteration, 
addition,  change  of  use,  or  damage  to  be  repaired. 
The  evaluation  shall  include  review  of  relevant 
available  documentation  about  the  building  design 
and  construction,  a  field  investigation  of  the  existing 
conditions,  and  a  structural  analysis.  When  deemed 
necessary  by  the  structural  engineer,  the  evaluation 
shall  also  include  detailed  field  surveys,  testing,  and 


laboratory  analysis.  Refer  to  780  CMR  F-104  in 
Appendix  F.  When  new  structural  elements  or 
strengthening  of  existing  elements  is  necessary,  the 
evaluation  shall  include  the  effects  of  such  new 
elements  and  strengthening.  A  report  on  the 
structural  evaluation  shall  be  submitted  to  the 
building  official  with  the  application  for  the  building 
permit. 

3408.2.1  Field  Investigation:  The  field 
investigation  of  an  existing  building  shall  be 
sufficient  to  determine  the  location,  size,  details, 
and  conditions  of  existing  structural  elements,  and 
to  verify  structural  information  on  the  drawings  of 
the  existing  building,  if  said  drawings  exist. 

3408.2.2  Structural  Analysis:  The  structural 
analysis  shall  include  analysis  of  all  structural 
systems  affected  by  the  proposed  alteration, 
addition,  change  in  use  or  repair,  or  for  which 
design  loads  are  specified  in  780  CMR  3408,  and 
shall  be  adequate  to  demonstrate  the  ability  of 
new  and  existing  systems  to  support  the  required 
loads. 

3408.2.3  Field  Observations  During 
Construction:  The  structural  engineer  shall  make 
periodic  field  visits  during  the  progress  of  the 
construction  work  on  the  existing  building  in 
order  to  observe  and  verify  the  assumed 
conditions  on  which  the  structural  design  was 
based,  and  shall  modify  the  design  should  the 
observed  conditions  differ  in  any  significant 
manner  from  those  on  which  the  structural  design 
was  based.  The  structural  engineer  shall  provide 
a  written  notification  to  the  building  official  of 
changes  to  the  contract  documents  as  shown  on 
the  permit  application. 

3408.2.4  Geotechnical  Explorations: 

Explorations  shall  be  performed  as  necessary  to 
determine  the  subsoils  and  the  type  and  condition 
of  existing  foundations  for  the  lateral  load 
analysis  of  foundations  required  in  780  CMR 
3408.3.4  and  for  the  liquefaction  evaluation 
required  in  780  CMR  3408.7. 

3408.3  General  Structural  Design  Requirements: 

The  provisions  of  780  CMR  3408.3  shall  apply  to 
the  structural  analysis  and  design  of  additions, 
alterations,  changes  in  use,  and  repairs  to  existing 
buildings.  Specific  requirements  for  additions,  and 
for  alterations  or  changes  of  use,  or  repairs  are 
prescribed    in    780    CMR    3408  4    and    3408.5 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


451 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


respectively.  Additional      requirements      for 

earthquake  analysis  and  design  are  prescribed  in 
780  CMR  3408.6. 

3408.3.1  New  Structural  Members  and 
Systems:  All  new  structural  elements  and 
systems,  whether  in  new  additions  or  in  existing 
construction,  shall  be  designed  and  constructed  in 
accordance  with  the  code  requirements  for  new 
construction  using  the  loads  and  criteria  specified 
in  780  CMR  3408.0. 

3408.3.2  Existing  Structural  Members  and 
Systems:  Strength  of  existing  systems,  elements, 
and  connections  shall  be  determined  in 
accordance  with  current  accepted  engineering 
practice,  using  the  actual  strength  and  other 
physical  properties  of  the  existing  materials. 
Alternatively,  except  for  earthquake  design, 
applicable  design  codes  at  the  time  of 
construction  may  be  used  to  determine  the 
strength  of  existing  systems,  elements  and 
connections,  provided  that  the  allowable  stresses 
specified  in  those  codes  are  not  exceeded,  and 
provided  the  applicable  provisions  of  those  codes 
have  not  since  been  found  to  endanger  public 
safety. 

3408.3.2.1  Strength  of  Existing  Materials: 
The  strength  of  existing  materials  shall  be 
determined  by  tests  or  from  generally  accepted 
historical  records. 

3408.3.2.2  Reuse  of  Existing  Structural 
Members:  Existing  structural  members  in 
sound  structural  condition  may  be  reused, 
providing  analysis  in  accordance  with 
780  CMR  3408.3.2  demonstrates  adequate 
capacity  to  support  the  loads  required  by 
780  CMR  3408.0. 

3408.3.3  Reinforcement  and  Repair  of  Existing 
Construction:  Repair  or  reinforcement  of 
existing  structural  elements  or  systems  shall  be 
designed  and  constructed  in  accordance  with  the 
code  requirements  for  new  construction,  using  the 
loads  and  criteria  specified  in  780  CMR  3408.0, 
and  in  the  case  of  existing  materials,  using  the 
actual  physical  properties  of  the  existing 
materials.  Alternatively,  for  other  than 
earthquake  design,  design  codes  applicable  at  the 
time  of  construction  of  the  existing  building  may 
be  used,  provided  that  the  allowable  stresses 
specified  in  those  codes  are  not  exceeded,  and 
provided  the  applicable  provisions  of  those  codes 
have  not  since  been  found  to  endanger  public 
safety. 

3408.3.4  Lateral  Load  Analysis:  Lateral  load 
analysis  of  a  building  required  by  the  provisions 
of  780  CMR  3408.0  shall: 

1.  Consider  all  walls,  frames,  diaphragms,  and 
other  structural  elements  that  may  contribute  to 
lateral  load  resistance. 


2.  Consider  eccentricity  of  center  of  applied 
wind  load  from  center  of  rigidity  of  the 
structure. 

3.  Consider  relative  stiffnesses  of  resisting 
elements. 

4.  Consider  flexibility  of  diaphragms  where 
appropriate. 

5.  Include  calculations  of  total  lateral 
earthquake  force  as  prescribed  in  780  CMR 
3408.6.1. 

6.  Include  calculations  of  distribution  of 
lateral  earthquake  force  as  in  780  CMR 
1612.5.2,  of  horizontal  torsional  moments  as  in 
780  CMR  1612.5.3,  of  overturning  as  in 
780  CMR  1612.5.4,  and  of  lateral  forces  on 
foundations  and  retaining  walls  as  in  780  CMR 
1612.4.9. 

3408.3.5  Existing    Lateral    Load    Capacity: 

Alterations  shall  not  be  made  to  elements  or 
systems  contributing  to  the  lateral  load  resistance 
of  a  building  which  would  reduce  their  capacity  to 
resist  lateral  loads,  unless  a  structural  analysis 
conforming  to  780  CMR  3408.3.4  shows: 

1.  That  the  lateral  load  resisting  system  of  the 
building  as  altered  conforms  to  780  CMR 
1611.0  and  1612.0  of  the  code  for  new 
construction,  or 

2.  That  the  lateral  load  resisting  system  as 
altered  conforms  to  all  applicable  minimum 
load  requirements  of  780  CMR  3408,  and  that 
there  is  no  reduction  in  the  lateral  load  capacity 
of  the  building  as  a  whole. 

Existing  elements  or  systems  may  be  reinforced  or 
replaced  with  new  elements  or  systems  of 
equivalent  strength  and  stiffness,  in  order  to  meet 
these  requirements. 

A  building  which  complies  with  780  CMR 
1611.0  and  1612.0  except  that  the  lateral  load 
resisting  system  does  not  conform  to  the  detailing 
requirements  of  780  CMR  19  through  23  for  the 
structural  materials  and  seismic  load  resisting 
system  employed,  may  be  considered  to  be  in 
compliance  with  780  CMR  3408.3.5  if  the  lateral 
load  resisting  system  can  safely  resist  a  lateral 
force  calculated  in  accordance  with  the  formulae 
in  780  CMR  1612.4,  but  with  lateral  force  factors 
(R)  and  force  modification  factors  as  stipulated  in 
Tables  3408.2  and  3408.3,  respectively. 

3408.3.6  Load  Combinations:  The  loads 
specified  in  780  CMR  3408.0  shall  be  combined 
in  accordance  with  780  CMR  1616.0. 

3408.3.7  Live  Load  Reduction:  Live  loads 
specified  in  780  CMR  3408.0  may  be  reduced  as 
permitted  in  780  CMR  1608.0. 

3408.3.8  Deficient  or  Damaged  Structural 
Members:  Existing  structural  members  that  are 
found  to  be  deficient  or  damaged,  either  prior  to 
or  during  an  alteration  or  addition,  shall  be 
repaired,  replaced,  or  reinforced  so  that  their  load 


452 


780  CMR  -  Sixth  Edition 


2/10/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR,  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


capacities  conform  to  the  requirements  of 
780  CMR  3408.5.  Existing  structural  members 
shall  be  considered  deteriorated  or  damaged  if 
their  capacity  is  less  than  85%  of  the  strength 
required  by  780  CMR  3408.1.1  or  3408.1.2,  as 
applicable. 

3408.4  Additions: 

3408.4.1  Live,  Dead,  Snow  and  Special  Loads: 

Additions  shall  be  designed  to  support  the  live 

load,  dead,  snow  and  special  loads  specified  in 

780  CMR  1605.0  through  1610.0  and  1613.0 

through  1615.0,  inclusive.    Where  additions  are 

supported  on  existing  construction,  the  existing 

structural    elements    shall    be    reinforced    or 

replaced,  if  necessary,  to  support  these  loads. 

3408.4.1.1  Snow  Drifts  and  Sliding  Snow: 

Where  the  geometry  of  an  addition  may  cause 

snow   drifting   or  sliding   snow  on   existing 

adjacent   construction,  the  affected  existing 

construction  shall  be  reinforced  so  that  it  will 

support  the  snow  loads  specified  in  780  CMR 

1610.0. 

3408.4.2  Wind  Loads: 

3408.4.2.1  Structure-As-A-Whole:  When  the 
aggregate  of  all  additions  made  to  a  building 
since  January  1,  1975  produce  effects  due  to 
the  wind  loads  specified  in  780  CMR  1611.0 
that  are  more  than  10%  of  the  capacity  of  the 
existing  lateral  load  resisting  system  of  the 
building,  a  lateral  load  resisting  system  shall  be 
provided  so  that  the  structure-as-a-whole  will 
resist  the  wind  loads  specified  in  780  CMR 
161 1.0.  When  such  effects  due  to  wind  are  less 
than  10%  of  the  capacity  of  the  existing  lateral 
load  resisting  system,  a  lateral  load  resisting 
system  shall  be  provided,  where  necessary,  so 
that  the  structure-as-whole  will  resist  the  wind 
loads  specified  for  Exposure  A  in  780  CMR 
1611.0.  Where  portions  of  a  building  are 
structurally  independent,  the  above 
requirement  shall  apply  to  each  structurally 
independent  portion. 

3408.4.2.2  Walls  and  Roofs:  New  parts  of 
enclosure  walls  and  roofs  that  are  subjected 
directly  to  the  wind,  and  their  local  supporting 
structural  elements,  shall  be  designed  to  resist 
the  wind  loads  specified  in  780  CMR  1611.0. 
Existing  local  supporting  structural  elements  of 
enclosure  walls  and  roofs  that  are  not  altered 
need  not  comply  with  780  CMR  161 1.0. 

3408.4.3  Earthquake  Loads:  All  new  materials 
and  portions  of  the  structure  shall  conform  to  all 
applicable  provisions  of  780  CMR  1612.0. 
Compliance  of  existing  portions  of  the  structure  to 
780  CMR  1612.0  is  not  required,  except  as 
stipulated  in  780  CMR  3408.4.3.1  and  3408.4.3.2. 


3408.4.3.1  Structurally  Separated  Additions: 

Additions  which  are  structurally  separated 
from  the  existing  portion  of  the  building  in 
accordance  with  780  CMR  1612.4.8  shall  be 
considered  as  separate  structures  for 
earthquake  design  purposes,  and  shall  conform 
to  all  provisions  of  780  CMR  1612.0.  Existing 
portions  of  the  structure  need  conform  only  to 
780  CMR  3408.5. 

3408.4.3.2  Additions  Not  Structurally 
Separated:  Existing  portions  of  buildings  with 
new  additions  which  are  not  structurally 
separated  from  the  existing  structure  shall  meet 
the  following  seismic  design  criteria: 

1 .  If  both  the  area  and  the  weight  of  the 
building  are  increased  by  less  than  10%, 
earthquake  resistance  of  the  existing  portion 
of  the  building  need  only  comply  with 
requirements  of  780  CMR  3408.3.5. 

2.  If  either  the  area  or  weight  of  the  building 
is  increased  by  10%  or  more,  but  neither  is 
increased  by  more  than  100%,  the  following 
seismic  design  criteria  shall  apply: 

a.  The  structure  shall  be  designed  to  resist 
a  percentage  of  the  base  earthquake  force, 
calculated  in  accordance  with  the 
requirements  of  780  CMR  3408.6. 1 .1,  not 
less  than  that  given  in  Figure  3408. 1 . 
b  Existing  structural  elements  not 
conforming  to  the  detailing  requirements  of 
780  CMR  19  through  23  may  be 
considered  effective  in  resisting  lateral 
seismic  loads,  providing  that  their  design 
seismic  force  is  calculated  in  accordance 
with  780  CMR  3408.6.1. 
c.  The  existing  building  shall  be 
investigated  for  the  presence  of  special 
earthquake  hazards  as  described  in 
780  CMR  3408.6.3,  and  all  such  hazards  as 
are  present  shall  be  corrected  in  accordance 
with  the  provisions  of  780  CMR  3408.6.3. 

3.  If  either  the  area  or  weight  of  the  building 
is  increased  by  more  than  100%,  the  structure 
as  a  whole  shall  comply  with  the  code  for 
new  construction.  Existing  elements  that  do 
not  conform  to  the  requirements  of  780  CMR 
19  through  23  shall  not  be  considered 
effective  in  resisting  lateral  seismic  loads. 

4.  For  the  purposes  of  780  CMR  3408.4.3.2, 
"area"  shall  mean  the  total  of  all  gross  floor 
and  roof  areas  supported  by  the  building 
structure,  and  "weight"  shall  have  the  same 
meaning  as  "W"  as  defined  in  780  CMR 
1612.5.1.  Percentage  changes  in  building 
area  and  weight  shall  be  calculated  by 
dividing  the  total  area  or  weight  of  the 
structure  after  the  proposed  addition  by  the 
total  area  and  weight  existing  five  years  prior 
to  the  date  of  the  current  building  permit 
application. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


453 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figure  3408.1 

MINIMUM  PERCENTAGE  OF  LATERAL 

EARTHQUAKE  LOAD 


Percent  Increase  in 
Weight  or  Area 

Percentage  of  Lateral 
Force  from  3408.6. 1 

10 

40 

20 

50 

30 

60 

40 

70 

50 

80 

60 

90 

70 

100 

80 

100 

90 

100 

100 

100 

3408.4.4  Change  in  Use:  If  an  addition  is 
accompanied  by  a  change  in  use,  the  more 
stringent  requirements  for  addition  or  change  in 
use  shall  apply 

FIGURE  3408.1 

MINIMUM  PERCENTAGE  OF  LATERAL 

EARTHQUAKE  LOAD 


~~~)f^~. 4 4 


Percent  Increase  n  WergH  or  Area 


3408.5  Alterations,  Repairs  and  Changes  of  Use: 

The  following  requirements  apply  to  existing 
buildings  which  are  altered  or  repaired,  or  for  which 
there  is  a  change  of  use. 

3408.5.1  Floor  Loads:  Except  as  provided  in 
780  CMR  3408.5.2,  the  load  capacity  of  all  floors 
affected  by  alterations,  repairs  or  changes  in  use 
shall  be  adequate  to  support  the  loads  required  by 
780  CMR  1605.0  through  1608.0,  1613.0  and 
1614.0,  inclusive,  or  the  floors  shall  be  reinforced 
or  replaced  with  new  structural  members. 

3408.5.2  Posted  Live  Load:  Except  for  Use 
Groups,  F,  I,  and  S,  any  existing  building  in 
which  a  new  use  requires  greater  live  loads  may 
be  posted  for  the  originally  approved  live  loads, 
provided  that  the  use  is  controlled  in  a  way 
acceptable  to  the  building  official,  and  so  that  the 
public  safety  is  not  endangered  thereby 

3408.53  Wind  Loads:  The  wind  load  capacity  of 
the  structure-as-whole  shall  not  be  less  than  that 
required  for  Exposure  A  in  780  CMR  1611.00. 
The  existing  lateral  load  resisting  system  shall  be 
reinforced  or  new  lateral  load  resisting  elements 
or  systems  shall  be  added,  as  necessary,  to  meet 
this  requirement. 

Exception:  The  building  official  may  waive 
this  requirement  if  the  alterations  are  minor 
and  if  there  is  not  change  in  use.  and  if  the 
structural  engineer  certifies  that  there  are  no 
alterations  to  structural  elements. 

3408.5.4  Earthquake  Loads: 

3408.5.4.1  Seismic  Hazard  Category  for 
Existing  Buildings:  The  Seismic  Hazard 
Category  for  existing  buildings  shall  be 
determined  from  Table  3408.1  on  the  basis  of 
the  proposed  change  in  use,  change  in 
occupancy  and  cost  of  alterations. 


Table  3408.1 
SEISMIC  HAZARD  CATEGORY 


CHANGE  IN  OCCUPANCY  OR  COST  OF  ALTERATIONS 

CHANGE  IN  USE  (1) 

Occupancy  increased  by  more  than  25%  and  to 

a  total  occupancy  of  100  or  more;  or  total  cost 

of  alterations  exceeds  50%  of  the  assessed 
(2) 

valuation  of  the  building. 

All  other  changes  in  occupancy,  and 
total  cost  of  alterations  less  than  or  equal 
to  50%  of  assessed  valuation  of  the 
building. 

Change  from  Use  Group  with  Hazard 
Index  less  than  4  to  Use  Group  with 
Hazard  Index  of  4  or  greater,  or 
Seismic  Hazard  Exposure  Group  III 
per  Table  1612.2.5. 

3 

2 

All  other  changes  in  Use  Group,  or  no 
change  in  Use  Group. 

2(3) 

,(3) 

Note  1.  Refer  to  Table  3403  and  Appendix  F,  Table  F-l  for  the  Hazard  Index  of  any  use  group.  Adjustments  to  the 
Hazard  Index  indicated  in  the  footnotes  to  Table  3403  shall  not  be  applied  for  determination  of  Seismic  Hazard 
Category. 


454 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 

Note  2.    Total  cost  of  alterations  shall  include  the  cost  of  alterations  proposed  under  the  current  building  permit 
application,  plus  the  cost  of  any  alterations  covered  by  building  permits  in  the  two-year  period  preceding  the  date  of 
the  current  permit  application.  The  assessed  valuation  shall  be  as  of  the  date  of  the  current  building  permit  application 
Note  3.  When  there  is  no  change  in  use,  the  following  costs  may  be  excluded  from  the  total  cost  of  alterations: 
a.    Costs  incurred  by  requirements  for  compliance  with  the  following: 

i.    Americans  With  Disabilities  Act 

ii.   Massachusetts  Architectural  Access  Board  Regulations,  52 1  CMR 

iii   M.G.L.  c.   148,  §  26AV4  requiring  sprinklers  in  existing  high-rise  structures. 
b.Costs  incurred  for  improvements  in: 

i.    Sprinklering 

ii.    Smoke  and  heat  detection 

iii.   Fire  alarm  systems 

iv.   Exit  enclosures 


3408.5.4.2  Partial    Change    of   Use:    For 

buildings  in  which  more  than  33%  of  the  totai 
floor  area  is  classified  as  Seismic  Hazard 
Category  2  or  3,  the  earthquake  design  of  the 
entire  building  shall  be  governed  by  the 
requirements  applying  to  that  higher  Seismic 
Hazard  Category. 

3408.5.4.3  For  Seismic  Hazard  Category  1: 

Earthquake  resistance  need  only  comply  with 
the  requirements  of  780  CMR  3408.3.5. 

3408.5.4.4  For  Seismic  Hazard  Category  2. 

Earthquake  resistance  shall  comply  with  the 
requirements  of  780  CMR  3408.3.5,  and  the 
existing  building  shall  be  investigated  for  the 
presence  of  special  earthquake  hazards  as 
described  in  780  CMR  3408.6.3,  and  all  such 
hazards  that  are  present  shall  be  corrected  in 
accordance  with  the  provisions  of  780  CMR 
3408.6.3. 

3408.5.4.5  For  Seismic  Hazard  Category  3: 
Full  compliance  with  780  CMR  1612.0  is 
required,  except  as  provided  in  780  CMR 

3408.5.4.6  and  3408.6.4,  and  except  that 
existing  structural  systems  not  conforming  to 
the  requirements  of  780  CMR  19  through  23 
may  be  considered  to  participate  in  resisting 
lateral  seismic  loads,  but  only  if  the  seismic 
design  force  is  calculated  in  accordance  with 
780  CMR  3408.6.1.1. 

3408.5.4.6  Maximum  Lateral  Earthquake 
Force:  When  the  provisions  of  780  CMR 
3408.5.4  require  compliance  with  the  code  for 
new  construction,  or  otherwise  require  design 
for  minimum  lateral  seismic  force,  and  the 
building  is  not  being  extended  in  area  or 
height,  the  design  lateral  seismic  force  need  not 
exceed  75%  of  the  base  earthquake  force 
calculated  in  accordance  with  780  CMR 
3408.6.1.1. 

3408.6: 

3408.6.1  R  Factors  and  Force  Modification 
Factors  for  Existing  Construction: 

3408.6.1.1  Base  Earthquake  Force:  Where 
the  provisions  of  780  CMR  require  calculation 
of   earthquake    design    forces    on    existing 


buildings,  a  base  earthquake  force  shall  be 
calculated  in  accordance  with  one  of  the 
following  methods: 
1  Where  the  lateral  load  resisting  system 
conforms  to  the  requirements  of  780  CMR 
1612.,  the  base  earthquake  force  shall  be 
calculated  using  780  CMR  1612.4  and  the 
appropriate  response  modification  factor  R 
from  Table  1612.4.4. 

2.  Where  the  lateral  load  resisting  system 
does  not  conform  to  the  requirements  of 
780  CMR  1612.0.  the  base  earthquake  force 
shall  be  calculated  in  accordance  with 
780  CMR  1612.4  except  that  the  appropriate 
response  modification  factor  R  from  Table 
3408.2  shall  be  used. 

3.  Where  the  "lateral  load  resisting  system 
does  not  conform  to  the  requirements  of 
780  CMR  1612.0,  and  is  not  adequately 
described  by  one  of  the  systems  identified  in 
Table  3408.2,  the  base  earthquake  force  shall 
be  determined  by  a  properly  substantiated 
analysis  which  takes  into  account  the 
dynamic  and  ductility  characteristics  of  the 
existing  structure,  and  ground  motion 
characteristics  consistent  with  the 
requirements  of  780  CMR  1612.0.  The 
ductility  characteristics  used  in  the  analysis 
shall  be  confirmed  by  physical  tests  If  the 
ductility  characteristics  of  the  existing 
structure  cannot  be  determined,  the  structure 
shall  be  analyzed  on  the  basis  of  an  R  factor 
of  1.25. 

3408.6.1.2  Earthquake  Design  Force:  The 
earthquake  design  force  for  the  existing  lateral 
load  resisting  system  shall  be  equal  to  the  base 
earthquake  force  calculated  in  accordance  with 
780  CMR  3408.6.1.1,  multiplied  by  the 
appropriate  reduction  factor  from  780  CMR 
34084.3.2  or  780  CMR  3408.5  4.6,  where 
applicable. 

3408.6.1.3  Earthquake  Force  on 
Components  of  Lateral  Resisting  System: 
The  earthquake  design  forces  for  components 
of  the  lateral  load  resisting  system  shall  be 
determined  from  the  lateral  load  analysis, 
based     on    the     earthquake    design     force 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


455 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


calculated    in    accordance   with    780    CMR 

3408.6.1.2. 
Exception:  When  the  design  earthquake 
force  is  derived  from  a  base  earthquake  force 
calculated  in  accordance  with  780  CMR 
3408.6.1.1,  Method  2,  design  forces  for 
components  of  structural  systems  which  are 
listed  in  Table  3408.3  shall  be  multiplied  by 
a  force  modification  factor  as  set  forth  in  that 
Table. 

3408.6.2  Existing  Rigid  Elements  in 
Earthquake  Analysis:  Existing  rigid  elements 
may  be  assumed  not  to  participate  in  the  lateral 
load  resisting  system,  provided  that  their  effect  on 
the  action  of  the  system  is  considered  and 
provided  for  in  analysis  and  design.  In  addition, 
the  effects  of  the  lateral  deflection  on  such  rigid 
elements  themselves  and  on  their  attachment  to 
the  building  structure  shall  be  considered.  Where 
the  existing  rigid  elements  are  load-bearing 
elements,  such  as  walls  or  braced  frames,  which 
do  not  conform  to  the  detailing  requirements  of 
780  CMR  1903,  2104,  2203  or  2306,  as 
applicable: 

1 .  The  value  of  R  used  in  design  shall  not  be 
greater  than  4,  and, 

2.  The  lateral  stiffness  of  the  building  in  any 
story,  based  on  the  elements  assumed  in  the 
design  to  resist  lateral  loads,  shall  not  be  less 
than  Vi  of  the  stiffness  that  would  pertain  if  all 

•  new  and  existing  elements  were  considered  to 

be  fully  effective  in  resisting  lateral  loads. 
780  CMR  3408.6.2  shall  not  apply  to  buildings 
where  the  required  lateral   load  resistance   is 
controlled  by  780  CMR  3408.3.5. 

3408.6.3  Reduction  of  Earthquake  Hazards: 

Where  the  provisions  of  780  CMR  3408.0.  require 
correction  of  special  earthquake  hazards,  the 
following  measures  shall  be  taken  to  reduce 
hazards  from  parapets,  masonry  walls,  and/or 
precast  concrete  structural  elements  which  do  not 
conform  to  the  requirements  of  780  CMR  1612.0: 

1.  Parapets:  All  parapets  not  meeting  the 
requirements  of  780  CMR  1612.0  shall  be 
removed,  or  braced  so  as  to  meet  the 
requirements  of  780  CMR  1612.7  and,  for 
unreinforced  masonry  parapets,  780  CMR 
3408.6.4. 

2.  Masonry  walls:  All  masonry  walls  shall  be 
connected  to  floor  or  roof  diaphragms,  or  other 
elements  providing  their  lateral  support,  so  as 
to  conform  to  the  requirements  of  780  CMR 
1612.7.  The  design  force  for  the  connection 
shall  not  be  less  than  100  pounds  per  linear 


foot  of  wall.    Connections  shall  not  produce 

cross-grain  bending  in  wood  members. 

3.      Precast  concrete  structural  elements: 

Interconnections  of  precast  concrete  structural 
elements  shall  be  investigated,  and  reinforced 
if  necessary.  Connections  shall  conform  to  the 
requirements  of  780  CMR  19. 

Table  3408.2 

RESPONSE  MODIFICATION  FACTOR  "R" 

FOR  EXISTING  BUILDINGS  (U) 


BUILDING  LATERAL  FORCE  RESISTING 
SYSTEM 

R 

cd 

Wood  Systems 

Light  Framed  Plywood  Shear  Walls  3  Stories  or  Less 
Other  Wood  Buildings 

6.5 
5 

4 
3 

Steel  Systems 

Steel  Moment  Frame 

Steel  Braced  Frame  without  Gravity  Loads  in  Braces 
Steel  Braced  Frame  with  Gravity  Loads  in  Braces 
Steel  Frame  with  Concrete  Shear  Walls 

4.5 

5 
4 
5.5 

4 

4.5 
3.5 

5 

Cast-in-Place  or  Precast  Concrete  Systems 

Concrete  Moment  Frame 

Concrete  Frame  with  Concrete  Shear  Walls 

Unreinforced  Concrete  Shear  Walls 

3 
4.5 

1.5 

2.5 
4 
1.5 

Unreinforced  Masonry  Systems 

Infill  Shear  Walls  in  Complete  Steel  or  Concrete 

Frame 
Shear  Wall  Systems  with  Partial  Steel  or  Concrete 

Frame 
Bearing  Wall  Systems 

1.5 
1.38 

1.25 

1.5 
1.38 

1.25 

Note  1.  See  Table  3408.3  for  Force  Modification  Factors 

applicable  to  Components  of  Lateral  Force  Resisting 

Systems. 

Note  2.    For  buildings  deriving  lateral  load  resistance 

from  a  combination  of  structural  systems: 

a.  For  vertical  combinations  with  a  regular  flexible 
upper  portion  above  a  rigid  lower  portion,  perform  a 
two-stage  analysis.  Evaluate  the  flexible  upper  portion 
as  a  separate  structure  supported  laterally  by  the  rigid 
base.  Evaluate  the  base  structure  as  a  separate 
structure,  adding  the  base  shear  and  overturning 
moment  from  the  upper  structures  as  lateral  forces 
applied  at  the  top  of  the  base  structure. 

b.  For  combinations  along  different  horizontal  axes, 
use  values  of  R  and  Cd  for  the  principal  system  in  the 
respective  directions,  except  in  buildings  deriving  a 
significant  portion  of  lateral  resistance  from  bearing 
walls.  For  these  buildings,  use  the  values  of  R  and  C^ 
associated  with  the  bearing  wall  system  for  all 
directions. 

c.  For  other  combinations,  use  the  lowest  value  of  R 
(and  corresponding  value  of  Cd)  of  all  systems 
participating  in  lateral  load  resistance. 

Note  3.  To  qualify  for  a  R  factor  of  1.50,  infill  walls 
must  bear  tightly  on  surrounding  frame  members  on  all 
four  sides.  In  all  other  cases,  use  a  R  factor  of  1.38. 


456 


780  CMR  -  Sixth  Edition 


2/10/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR,  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


Table  3408.3 

FORCE  MODIFICATION  FACTORS  FOR 

COMPONENTS  OF  LATERAL  LOAD 

RESISTING  SYSTEMS 


FORCE 

STRUCTURAL  COMPONENT 

MODIFICATION 

FACTOR  (1) 

Structural  Steel  Systems 

All  forces  in  bracing  connections  not 

0.4R 

conformingto  780  CMR  2204.3.1. 

All  forces  in  column  connections  using 

partial  penetration  welds  not  con- 

0.8R 

forming  to  relevant  portions  of  780 

CMR  2203.0. 

All  forces  in  members  and  connections 

0.8R 

of  open  web  steel  joists  resisting 

earthquake  loads. 

Cast-in-Place  and  Precast  Concrete 

Systems 

Moment  at  any  cross-section  of  a  fiex- 

0.8R 

ural  member  where  the  reinforcing 

ratio  is  less  than  200/fy,  or  where  the 

reinforcing  consists  of  less  than  two 

bars,  or  is  less  than  V*  of  the  amount 

of  reinforcing  in  the  opposite  face  of 

the  member. 

Moment  and  shear  in  any  beam  without 

0.4R 

closed  stirrups  at  a  maximum  spacing 

of  d/4  over  a  distance  of  1  '/id  from 

each  end  of  the  clear  span. 

Moment  and  shear  in  any  column 

0.8R 

without  ties  as  a  spacing  not  exceed- 

ing the  smaller  of  times  the  diam- 

eter of  the  smallest  enclosed  bar,  24 

tie  bar  diameters,  or  Vz  the  smallest 

dimension  of  the  member,  over  a  dis- 

tance from  each  end  of  the  member 

not  less  than  1 16  the  clear  height  of 

the  column,  the  largest  dimension  of 

the  member,  or  1 8  inches. 

Force  in  concrete  shear  wall  reinforcing 

0.8R 

with  splices  that  do  not  develop  the 

full  yield  stress  of  the  reinforcing  in 

tension. 

Shear  in  shear  walls  not  conforming  with 

0.4R 

minimum  wall  reinforcing 

requirements. 

Axial  force  in  any  column  supporting  a 

0.8R 

discontinuous  stiff  element,  such  as  a 

shear  wall,  resisting  axial  loads, 

unless  the  column  has  special  trans- 

verse reinforcement  over  its  full 

height. 

All  forces  in  precast  concrete  connec- 

0.8R 

tions  not  conforming  to  the  require- 

ments of  780  CMR  19 

All  Systems 

Shear  in  any  story  where  the  strength  of 

0.8R 

all  shear  resisting  elements  is  less 

than  65%  of  the  strength  of  all  shear 

resisting  elements  in  the  story  above. 

Note  1. 
1.0. 


Force  Modification  Factor  shall  not  be  less  than 


3405.6.4  Existing  Unreinforced  Masonry 
Walls:  Where  compliance  with  the  code  for  new 
construction  is  required  by  780  CMR  3408.0, 
existing  unreinforced  masonry  walls  in  sound 
condition  may  continue  in  service,  providing: 

1 .  They  are  adequately  tied  to  the  structural 
elements  providing  their  lateral  support;  and, 

2.  The  ratio  of  unbraced  height  or  length  to 
nominal  thickness  in  at  least  one  direction  does 
not  exceed  20  for  walls  spanning  laterally 
between  two  supports,  nor  4  for  cantilever 
walls  and  parapets;  and, 

3.  The  wall  is  of  sufficient  strength  to  resist 
the  required  earthquake  forces  from  780  CMR 
1612.7. 

Masonry  walls  allowed  to  be  unreinforced  by  the 
provisions  of  the  code  for  new  construction  and 
which  satisfy  all  provisions  of  the  code  for  new 
construction  need  not  satisfy  780  CMR  3408.6.4 
item  2.  Additional  bracing  or  structural  ties  may 
be  provided  to  meet  these  requirements. 
Unreinforced  walls  continuing  in  service  under 
780  CMR  3408.6.4  shall  not  be  considered 
effective  as  shear  walls  resisting  lateral 
earthquake  force  specified  in  780  CMR  16,  except 
where  the  provisions  of  780  CMR  3408.0 
specifically  permit  use  of  structural  systems  not 
conforming  to  780  CMR  2104. 

3408.6.5  Changes  in  Building  Mass:  A  reduction 
in  the  weight  of  a  building  shall  not  be  considered 
to  offset  a  reduction  in  lateral  load  capacity  of  the 
building,  in  evaluating  compliance  with  780  CMR 
3408.3.5,  except  that  the  weight  of  the  building  as 
altered  shall  be  used  in  evaluating  compliance 
with  780  CMR  1612.0.  An  increase  in  the  weight 
of  the  building  shall  be  considered  as  an  addition, 
for  purposes  of  determining  earthquake  resistance 
requirements  (see  780  CMR  3408.4). 

3408.7  Liquefaction  Evaluation  for  Existing 
Buildings:  The  subsoils  supporting  the  existing 
building  shall  be  evaluated  to  determine  the  potential 
for  liquefaction,  and  if  necessary  the  subsoils  and/or 
foundations  shall  be  improved  to  prevent  failure  in 
the  event  liquefaction  occurs,  as  required  below: 

1.  Existing  buildings  with  Seismic  Hazard 
Category  1  (see  780  CMR  3408.5.4  and  Table 
3408.1)  shall  not  require  evaluation  of 
liquefaction  potential  or  compliance  with 
780  CMR  1805.3. 

2.  Existing  buildings  with  Seismic  Hazard 
Category  2  or  3  (see  780  CMR  3408.5.4  and 
Table  3408.1)  shall  comply  with  the  requirements 
of  780  CMR  1805.3. 

3.  Existing  buildings  with  structurally  separate 
additions  shall  comply  with  3408.7  item  1  or  2, 
based  on  the  Seismic  Hazard  Category  of  the 
existing  building. 

4.  Existing  buildings  with  structurally  attached 
additions  which  meet  the  requirements  of 
780  CMR  3408.4.3.2,  item   1,  and  which  are 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


457 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


classified  as  Seismic  Hazard  Category  1  (see 
780  CMR  3408.5.4  and  Table  3408.1),  shall  not 
require  evaluation  of  liquefaction  potential  or 
compliance  with  780  CMR  1805.3. 

5.  Existing  buildings  with  structurally  attached 
additions  which  meet  the  requirements  of 
780  CMR  3408.4.3.2,  item  2,  and  which  are 
classified  as  Seismic  Hazard  Category  1  or  2, 
shall  comply  with  the  requirements  of  780  CMR 
1805.3,  except  that  the  blow  count  scale  in  Figure 
1805.3  may  be  multiplied  by  the  appropriate 
reduction  factor  from  Figure  3408. 1. 

6.  Existing  buildings  with  structurally  attached 
additions  which  meet  the  requirements  of 
780  CMR  3408.4.3.2,  item  3,  shall. comply  with 
the  requirements  of  780  CMR  1805.3. 

780  CMR  3409.0  HISTORIC  BUILDINGS 
3409.1  Scope:  The  provisions  of  780  CMR  3409.0 
shall  govern  all  buildings  and  structures  in  the 
Commonwealth  which  are  legally  designated  as 
historic  buildings.  780  CMR  3409.0  shall  preempt 
all  other  regulations  of  780  CMR  governing  the 
reconstruction  alterations  change  of  use  and 
occupancy,  repairs  maintenance  and  additions  for 
the  conformity  of  historic  buildings  and  structures  to 
780  CMR  with  the  exception  of  780  CMR  122.0  for 
appeals,  or  unless  otherwise  specified  (see 
Appendix  H).  There  is  no  obligation  for  owners  of 
historic  properties  to  apply  for  780  CMR  3409.0. 

3409.1.1  Key  Definitions:  The  following  five 
definitions  are  found  in  780  CMR  3401. 1,  but  are 
also  presented  here  as  such  definitions  form  a 
significant  portion  of  780  CMR  3409. 

Historic  buildings:  (a)  Any  building  or  structure 
individually  listed  on  the  National  Register  of 
Historic  Places  or  (b)  any  building  or  structure 
evaluated  by  MHC  to  be  a  contributing 
building  within  a  National  Register  or  State 
Register  District,  (c)  any  building  or  structure 
which  has  been  certified  by  the  Massachusetts 
Historical  Commission  to  meet  eligibility 
requirements  for  individual  listing  on  the 
National  Register  of  Historic  Places.  Historic 
building  shall  be  further  defined  as  totally  or 
partially  preserved  buildings.  All  entries  into 
the  totally  preserved  building  list  shall  be 
certified  by  the  Massachusetts  Historical 
Commission.  The  Board  of  Building 
Regulations  and  Standards  shall  ratify  all 
buildings  or  structures  certified  by  the 
Massachusetts  Historical  Commission  to 
qualify  for  totally  preserved  listing  (see 
Appendix  H). 

Partially  preserved  buildings:  (a)  Any  building 
or  structure  individually  listed  on  the 
National  Register  of  Historic  Places  or  (b) 
any  building  or  structure  certified  as  a 
historic    building    by    the    Massachusetts 


Historical  (Commission/t  and  not  designated 
a  totally  preserved  building  in  Appendix  H. 

Restoration:  Restoration  is  the  process  of 
accurately  reconstructing  or  repairing  the 
forms  and  details  of  a  building  or  structure  or 
portion  thereof  as  it  appeared  at  a  particular 
period  or  periods  of  time  by  means  of 
removal  of  later  work/or  the  replacement  of 
missing  original  work 

Totally  preserved  buildings:  A  totally 
preserved  building  is  an  historic  building  or 
structure.  The  principal  use  of  such  a 
building  or  structure  must  be  as  an  exhibit  of 
the  building  or  the  structure  itself  which  is 
open  to  the  public  not  less  than  12  days  per 
year,  although  additional  uses,  original  and/ 
or  ancillary  to  the  principal  use  shall  be 
permitted  within  the  same  building  up  to 
maximum  of  40%  of  the  gross  floor  area. 
Totally  preserved  buildings  shall  be  those 
listed  in  Appendix  H.  All  entries  into  the 
totally  preserved  building  list  shall  be 
certified  by  the  Massachusetts  Historical 
Commission.  The  Board  of  Building 
Regulations  and  Standards  shall  ratify  all 
buildings  or  structures  certified  by  the 
Massachusetts  Historical  Commission  to 
qualify  for  totally  preserved  listing  (See 
Appendix  H). 

3409.2  Totally  preserved  buildings: 

3409.2.1  State  Building   Code   exceptions:   A 

totally  preserved  building  shall  be  subject  to  the 
following  exceptions: 

1 .  Repairs,  maintenance  and  restoration  shall  be 
allowed  without  conformity  to  780  CMR 
generally,  if  the  provisions  of  780  CMR  3409.4 
have  been  met. 

2.  In  case  of  fire  or  other  casualty  to  a  totally 
preserved  building,  said  building  may  be  rebuilt, 
in  total  or  in  part,  using  such  techniques  and 
materials  as  are  necessary  to  restore  it  to  its 
original  condition  and  use  group. 

3.  If  a  historic  building  or  structure,  as  a  result 
of  proposed  work,  would  become  eligible  for 
certification  as  a  totally  preserved  building  and 
the  Massachusetts  Historical  Commission  so 
certifies  by  affidavit,  such  affidadit  is  submitted 
to  the  building  official  with  the  permit 
application,  and  the  building  official  shall  then 
allow  the  work  to  proceed  under  the  provisions 
of  780  CMR  3409.2. 

3409.2.2  Mandatory  safety  requirements:    All 

totally  preserved  buildings  shall  comply  to  the 

following  requirements: 

3409.2.2.1  Fire  protection  equipment:  Fire 
protection  equipment  shall  be  provided 
according  to  the  following  requirements. 


458 


780  CMR  -  Sixth  Edition 


2/10/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
REPAIR,  ALTERATION,  ADDITION  AND  CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


1.  Manual  fire  extinguishing  equipment:  All 
use  groups,  other  than  Residential  R-3  and  R- 
4,  shall  have  approved  manual  fire 
extinguishing  equipment,  as  determined  by  the 
head  of  the  local  fire  department. 

2.  Fire  Protective  Signaling  Systems  (Fire 
Alarm  Systems):  All  residential  buildings  in 
use  groups  R-l,  R-2  and  R-3  shall  conform  to 
the  applicable  requirements  of  780  CMR  918 
and  919  as  applicable.  All  other  use  groups 
shall  comply  with  780  CMR  3409.2.2.1  items 
2.(a)  and  (b): 

(a)  Locations:  Provide  smoke  detectors  in 
accordance  with  manufacturers  listing  and 
spacing  requirements,  but  not  less  than  one. 
for  every  1200  square  feet  of  floor  area  per 
level.  In  addition,  all  lobbies,  common 
corridors,  hallways  and  exitway  access  and 
discharge  routes  shall  be  provided  with 
approved  smoke  detectors  installed  in 
accordance  with  the  manufacturers  listing 
and  spacing  requirements  but  not  more  than 
30  feet  spacing  between  detectors.  All 
required  smoke  detectors  shall  have  an  alarm 
audible  throughout  the  structure  or  building. 

(b)  Single  station  and  multiple  station 
smoke  detection  devices:  Smoke  detectors 
of  single  station  and  multiple  station  types 
shall  meet  the  requirements  of  UL  217  and 
be  listed  or  approved  by  a  nationally- 
recognized  fire-testing  laboratory.  All  other 
smoke  detectors  shall  be  listed  in  accordance 
with  UL  268  as  listed  in  Appendix  A. 

3.  Manual  pull  stations:  A  manual  fire  alarm 
pull  station  shall  be  provided  in  the  natural 
path  of  egress  in  all  use  groups  except  R-3  and 
R-l.  Manual  pull  stations  shall  be  connected  to 
the  building  fire  warning  system  in 
conformance  with  NFPA  72  as  listed  in 
Appendix  A. 

3409.2.2.1.1  Supervision:  Fire  protective 
signaling  systems  required  by  780  CMR 
3409.2.2.1  shall  be  supervised  in  accordance 
with  the  requirements  of  780  CMR  923.2. 

Exception:  Residential  single  and  multiple 

station  smoke  detectors. 

3409.2.2.2  Exit  signs  and  emergency  lights: 
Approved  exit  signs  and  emergency  lighting, 
where  designated  by  the  local  building  official, 
shall  be  provided  in  compliance  with  780  CMR 
1023.0  and  780  CMR  1024.0. 

Exception:  All  totally  preserved  buildings 
need  not  comply  with  780  CMR  1023.0  and 
780  CMR  1024.0  if  not  occupied  after 
daylight  hours,  except  that  paths  of  egress 
shall  have  exit  signs. 

3409.2.2.3  Maximum  occupancy:  Occupancy 
shall  be  limited  by  the  actual  structural  floor  load 
capacity  as  certified  by  a  qualified  Massachusetts 
registered  professional  engineer  or  architect  or 


in  accordance  with  780  CMR  1008.0.  whichever 
is  less.  Said  floor  load  shall  be  posted  in 
accordance  with  the  procedures  set  forth  in 
780  CMR  120.0,  780  CMR  1003.3  and 
780  CMR  1617.2.  The  owner  shall  submit 
evidence  of  this  certification  and  related 
computations  to  the  building  official  upon 
request. 

3409.2.2.4  Limited  egress:  Where  one  or  more 
floors  of  a  totally  preserved  building  are  limited 
to  one  meats  of  egress,  the  occupancy  load  shall 
be  computed  as  follows: 

1  Floors  below  the  first  story  Not  more 
than  one  occupant  per  100  square  feet  of  gross 
floor  area  with  a  maximum  occupancy  of  49. 
2.  First  story:  Not  more  than  one  occupant 
per  50  square  feet  of  gross  floor  area. 
3'.  Second  story  and  above:  Not  more  than 
one  occupant  per  100  square  feet  of  gross  floor 
a  area,  or  30  occupants  per  unit  of  egress 
width,  whichever  condition  results  in  the  lesser 
occupancy  load. 

3409.2.2.5  Inspections:  The  building  official 
and  the  fire  official  shall  inspect  all  totally 
preserved  buildings  not  less  frequently  than  once 
every  year  in  order  to  determine  that  the  building 
or  structure  continues  to  conform  to  780  CMR 
3409. .3.  A  qualified  Massachusetts  registered 
professional  engineer  or  architect  shall  certify 
every  five  years  thereafter  as  to  the  exact  floor 
load  capacity  of  the  building  or  structure.  The 
building  official  shall  certify  all  totally  preserved 
buildings  not  less  frequently  than  once  every 
year.  Fees  shall  be  established  at  S25.00  per 
building  per  inspection. 

3409.2.2.6  Accessibility  for  Persons  with 
Disabilities:  Accessibility  requirements  shall  be 
in  accordance  with  521  CMR  as  listed  in 
Appendix  A. 

3409.2.2.7  Energy  Conservation:  Totally 
preserved  buildings  are  exempt  from  the 
requirements  of  780  CMR  13  and  the  energy 
conservation  rewuirements  of  780  CMR  36. 

3409.3     Partially  preserved  buildings: 

3409.3.1    State   Building    Code   provisions:    A 

partially  preserved  building  shall  be  subject  to  the 
following  provisions: 

1.  Existing  Systems  -  individual  components  of 
an  existing  building  system  may  be  repaired  or 
replaced  in  kind  without  requiring  that  system  to 
comply  fully  with  the  code  for  new  construction. 
(See  780  CMR  34,  780  CMR  3404.3:  New 
Systems) 

2.  Replacement  in  kind  -  when  the  repair  of 
historic  materials  including  patching,  splicing, 
piecing-in,  consolidating  or  reinforcing  is  not 
possible,  compatible  materials  may  be 
substituted  which  closely  convey  the  form  and 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


459 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


design  as  well  as  the  visual  appearance  of  the 
existing  feature. 

3409.3.2     State  Building  Code  exceptions:  A 

partially  preserved  building  shall  be  subject  to  the 
following  exceptions:  Repairs  or  in  kind 
replacement  of  the  following  features  will  be 
allowed  on  partially  preserved  buildings  so  as  not  to 
compromise  the  architectural  integrity  of  the 
historical  characteristics  and  qualities  which 
contributed  to  the  eligibility  for  listing  in  the 
National  Register  of  Historic  Places. 

1 .  Roofing  -  repair  or  in  kind  replacement  of  an 
existing  historic  roof  system  (i.e.,  slate,  wood, 
clay,  tile,  metal)  shall  be  permitted  without 
requiring  structural  compliance  for  equivalent 
new  construction  providing  that  dead  and  live 
loading  requirements  have  not  changed. 

2.  Windows  -  repair  or  in  kind  replacement  of 
existing  historic  windows  (i.e.,  frames,  sash, 
muntins,  glazing,  sills,  molding,  shutters)  shall 
be  permitted  without  requiring  energy  code 
compliance. 

3.  Entries/Porches  -  repair  or  in  kind 
replacement  of  existing  individual  decorative 
features  of  an  existing  system  (i.e.  columns, 
balustrades,  stairs,  pilasters,  doors,  sidelights) 
shall  be  permitted.  (See  780  CMR  3409.5.1;  1 
2). 

4.  Wood  Siding/Decorative  Elements  -  Repair 
or  in  kind  replacement  of  an  existing  system 
including  such  items  as  clapboards,  shingles, 
cornices,  brackets,  and  window  and  door 
surrounds  shall  be  permitted.  (See  780  CMR 
3409.5.1;  1  2) 

5.  Masonry  -  repair  or  in  kind  replacement  of 
masonry  units  as  part  of  an  existing  system  (i.e., 
brick,  stone,  terra  cotta,  concrete  and  stucco) 
shall  be  permitted.  (See  780  CMR  3409.1;  1  2) 

6.  Metals  -  repair  or  in  kind  replacement  of 
existing  architectural  metals  (i.e.  cast  and 
wrought  iron,  steel,  tin,  copper  and  copper 
alloys,  aluminum,  zinc)  shall  be  permitted.  (See 
780  CMR  3409. 1.1,  .2). 

7.  Interior  features  -  repair  or  in  kind 
replacement  of  non-structural  interior  features 
that  areimportant  in  defining  the  overall  historic 
character  of  a  building  (i.e.,  columns,  cornices, 
baseboards,  fireplace  mantels,  paneling,  window 
trim,  doors,  moldings,  railings,  flooring, 
plasterwork)  shall  be  permitted  (See  780  CMR 
3409.5.1.1,  .2) 


3409.3.3  Applicability:  780  CMR  3409.3  and 
780  CMR  34  shall  apply  to  all  partially  preserved 
Historic  buildings. 

34093.4  Continuation  of  use  and  occupancy:  The 

legal  use  and  occupancy  of  any  partially  preserved 
building  may  be  continued  without  change  or 
further  compliance  to  780  CMR.  The  provisions  of 
780  CMR  3409.6  shall  be  required  for  Historic 
buildings  accessible  to  the  public  on  more  than  50 
days  per  year. 

3409.3.5  Inspection  certification  and  fees: 
Partially  preserved  buildings  shall  not  require 
annual  inspection  unless  otherwise  stipulated  in 
780  CMR  106.5  and  Table  106. 

3409.3.6  Fire  damage:  If  a  building  or  structure  is 
damaged  from  fire  or  other  casualty  it  may  be 
restored  to  its  original  construction  or  it  shall  meet 
the  requirements  of  780  CMR  provided  these 
requirements  do  not  compromise  the  features  for 
which  the  building  was  considered  Historic  when 
listed  in  the  National  Register  of  Historic  Places. 

34093.7  Change  in  occupancy:  See  780  CMR  34. 

3409.3.8  New  systems.  See  780  CMR  34. 

3409.3.9  Lesser  and  equal  hazard:  See  780  CMR 

34.  A  partially  preserved  building  classified  under 
unprotected  construction  Type  3C  or  5B  shall  have 
waived  the  requirement  to  add  one  to  the  Hazard 
Index  number  (See  780  CMR  34,  Table  3403). 

3409.3.10  Greater  hazard:  See  780  CMR  34.  A 

partially  preserved  building  classified  under 
unprotected  construction  Type  3C  or  5B  shall  have 
waived  the  requirement  to  add  one  to  the  Hazard 
Index  number  (See  780  CMR  34,  Table  3403). 

3409.3.11  Energy  Conservation:  Partially 
preserved  buildings  are  exempt  from  the  energy 
requirements  of  780  CMR  13  and  the  energy 
requirements  of  780  CMR  36. 

Exception:  Additions  to  partially  preserved 
buildings  shall  comply  with  the  energy 
provisions  of  780  CMR  13  or  of  780  CMR  36, 
as  applicable. 

3409.3.12  Accessibility  for  Persons  with 
Disabilities:  Accessibility  requirements  shall  be  in 
accordance  with  521  CMR  as  listed  in  Appendix  A. 


460 


780  CMR  -  Sixth  Edition 


2/ 1 0/97    (Effective  2/28/97) 


CHAPTER  35 


MANUFACTURED  BUILDINGS,  MANUFACTURED  BUILDING  COMPONENTS 
AND  MANUFACTURED  HOUSING 

(This  Chapter  is  entirely  unique  to  Massachusetts) 


780  CMR  3501.0  GENERAL 

3501.1  Scope:  The  provisions  of  780  CMR  35  shall 
govern  the  materials,  design,  manufacture,  handling, 
storage,  transportation,  assembly,  construction 
and/or  installation  of  manufactured  buildings  and 
manufactured  building  components  intended  for 
installation  in  the  Commonwealth  of  Massachusetts. 
Manufactured  buildings  or  manufactured  building 
components  shall  not  be  installed  in  any  jurisdiction 
of  the  Commonwealth  of  Massachusetts  unless  such 
manufactured  buildings  or  manufactured  building 
components  have  been  approved  and  certified  in 
accordance  with  780  CMR  35,  applicable  provisions 
of  780  CMR,  and  the  Rules  and  Regulations  for 
Manufactured  Buildings,  Manufactured  Building 
Components  and  Manufactured  Housing,  780  CMR 
R3,  as  listed  in  Appendix  A. 

3501.2  Manufactured  housing:  When  constructed 
in  accordance  with  the  Code  of  Federal  Regulations 
(CFR)  Title  24,  Chapter  XX  -  Office  of  Assistant 
Secretary  for  Housing  -  Federal  Housing 
Commissioner,  Department  of  Housing  and  Urban 
Development,  Parts  3280,  Manufactured  home 
construction  and  safety  standards,  and  3282, 
Manufactured  home  procedural  and  enforcement 
regulations;  manufactured  housing  shall  be  exempt 
from  the  provisions  of  780  CMR  35. 

Exceptions: 

1.  Foundations  for  manufactured  housing  shall 
conform  to  780  CMR  1806.0; 

2.  Additions,  (when  not  a  manufactured  home  as 
defined  herein)  and  site  built  modifications  shall 
conform  to  780  CMR  in  its  entirety,  as  applicable. 

780  CMR  3502.0  DEFINITIONS 
3502.1  General:  The  following  words  and  terms 
shall,  for  the  purposes  of  780  CMR  35  and  as  used 
elsewhere  in  780  CMR  shall  have  the  meaning 
shown  herein. 

Approved:  Approval  by  the  State  Board  of  Building 
Regulations  and  Standards  (BBRS). 

Manufactured      Building      Component:      Any 

manufactured  subsystem,  manufactured  sub- 
assembly, or  other  manufactured  system  designed 
for  use  in  or  part  of  a  structure  having  concealed 
elements  such  as  electrical,  mechanical,  plumbing 
and  fire  protection  systems  and  other  systems 
affecting  health  and  safety,  including  variations 


which   are   submitted   as   part   of  the   building 
systems. 

Certification:  Any  manufactured  building, 
manufactured  building  component  or 
manufactured  housing  which  meets  the  provisions 
of  applicable  codes  and  780  CMR  R3  pursuant 
thereto,  as  listed  in  Appendix  A;  which  has  been 
labeled  accordingly. 

Code:  780  CMR  (The  Commonwealth  of 
Massachusetts  State  Building  Code)  or 
specialized  codes  as  defined  herein,  and  as  listed 
in  Appendix  A. 

Department  (DPS):  The  Department  of  Public 
Safety,  Division  of  Inspections. 

Inspection  Agency:  An  independent  agency, 
sometimes  referred  to  as  the  "third-party  agency", 
retained  by  the  manufacturer  and  approved  by  the 
BBRS  to  perform  inspections  and  evaluations  of 
manufactured  building  systems,  compliance 
assurance  programs,  manufactured  buildings  and 
manufactured  building  components. 

Installation:  The  process  of  affixing,  or  assembling 
and  affixing  a  manufactured  building, 
manufactured  building  component  or 
manufactured  housing  unit(s)  on  the  building  site, 
and  connecting  it  to  utilities,  and/or  to  an  existing 
building.  Installation  may  also  mean  the 
connecting  of  two  or  more  manufactured  housing 
units  designed  and  approved  to  be  so  connected 
for  use  as  a  dwelling. 

Installer  of  Manufactured  Building:  An  individual, 
who  on  the  basis  of  training  and  experience,  has 
been  certified  by  a  specific  manufacturer  of 
manufactured  building  as  competent  to  supervise 
the  placement  and  connection  required  to  install 
the  manufactured  homes  of  that  manufacturer. 
Said  certification  by  the  manufacturer  shall  be  in 
writing,  and  the  certified  installer  shall  be  issued 
picture  identification  by  the  manufacturer  in 
verification  of  his\her  certification. 

Label:  An  approved  device  or  seal  evidencing 
certification  in  accordance  with  the  applicable 
codes  and  rules  and  regulations  promulgated 
pursuant  thereto,  and  as  listed  in  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Local  Enforcement  Agency:  A  department  or 
agency  in  a  municipality  charged  with  the 
enforcement  of  780  CMR  and  appropriate 
specialized  codes  which  include,  but  are  not 
limited  to,  248  CMR  (the  State  Fuel  Gas  and 
Plumbing  Code)  and  527  CMR  12.00  (the  State 
Electrical  Code),  as  listed  in  Appendix  A. 

Manufactured  Building:  Any  manufactured 
building  which  has  concealed  elements,  such  as 
electrical,  mechanical,  plumbing,  fire  protection, 
insulation,  and  other  systems  affecting  health  and 
safety,  and  which  is  manufactured  or  assembled  in 
accordance  with  780  CMR  and  pertinent 
regulations,  in  manufacturing  facilities,  on  or  off 
the  building  site.  Also,  any  manufactured 
building  as  defined  above  which  does  not  have 
concealed  elements,  but  which  has  been  approved 
by  the  BBRS  at  the  request  of  the  manufacturer. 
"Manufactured  building"  does  not  mean 
"manufactured  home". 

Manufactured  Homes  (Housing):  As  defined  in  24 
CFR,  Part  3280.2;  a  structure,  transportable  in 
one  or  more  sections,  which  in  the  traveling 
mode,  is  eight  body  feet  or  more  in  width  or  forty 
body  feet  or  more  in  length,  or,  when  erected  on 
site,  is  320  or  more  square  feet,  and  which  is  built 
on  a  permanent  chassis  and  designed  to  be  used  as 
a  dwelling  with  or  without  a  permanent 
foundation  when  connected  to  the  required 
utilities,  and  includes  the  plumbing,  heating,  air- 
conditioning,  and  electrical  systems  contained 
therein.  Calculations  used  to  determine  the 
number  of  square  feet  in  a  structure  will  be  based 
on  the  structure's  exterior  dimensions  measured  at 
the  largest  horizontal  projections  when  erected  on 
site.  These  dimensions  will  include  all 
expandable  rooms,  cabinets,  and  other  projections 
containing  interior  space,  but  do  not  include  bay 
windows.  (See  24  CFR,  Part  3280.2  for  a  more 
detailed  description  of  manufactured  homes  as 
defined  by  the  Department  of  Housing  and  Urban 
Development.) 

Specialized  Code:  All  building  codes,  rules  or 
regulations  pertaining  to  building  construction, 
reconstruction,  alteration,  repair,  or  demolition 
promulgated  by  and  under  the  authority  of  the 
various  agencies  which  have  been  authorized 
from  time  to  time  by  the  General  Court  of  the 
Commonwealth     of     Massachusetts.  The 

specialized  codes  shall  include,  but  are  not  limited 
to,  248  CMR  (the  State  Fuel  Gas  and  Plumbing 
Code)  and  527  CMR  12.00  (the  Electrical  Code), 
as  listed  in  Appendix  A. 


780  CMR  3503.0  CONSTRUCTION 
DOCUMENTS 

3503.1  Building  System  Plans:  The  building 
system  plans  shall  show  in  sufficient  detail  the 
approved  system  to  which  the  manufactured 
building  or  building  component  was  produced; 
including  foundation  connection  details,  component 
connection  details,  emergency  escape  window 
locations  and  sizes,  structural  design  loads,  the 
manufacturer's  data  plate,  the  location  of  all  labels 
required  of  780  CMR  35  and  780  CMR  R3,  and 
other  details  as  may  be  required  by  the  Division  of 
Inspection.  The  building  system  plan  shall  bear 
evidence  of  the  approval  of  the  Division  of 
Inspection  and  evidence  of  third  party  engineering 
review. 

780  CMR  3504.0  APPROVAL 

3504.1  General:  The  Commonwealth  of 
Massachusetts,  Department  of  Public  Safety, 
Division  of  Inspection  (hereinafter  referred  to  as  the 
"Division  of  Inspection"  in  780  CMR  35)  shall 
evaluate  manufactured  buildings  and  building 
components  and  recommend  approval  to  the  BBRS 
of  those  which  it  determines  to  be  in  compliance 
with  applicable  sections  of  780  CMR  35,  other 
applicable  sections  of  780  CMR,  and  780  CMR  R3, 
as  listed  in  Appendix  A. 

All  approvals  of  plumbing,  electrical  or  gas 
systems  shall  be  made  by  the  appropriate  state 
agencies  having  jurisdiction,  as  specified  in 
780  CMR  R3,  as  listed  in  Appendix  A. 

3504.2  Approved  tests:  The  Division  of  Inspection 
may  utilize  the  results  of  approved  tests  to  determine 
whether  a  manufactured  building  or  manufactured 
building  component  meets  the  requirements  of 
780  CMR  35  and  the  780  CMR  R3  as  listed  in 
Appendix  A,  if  that  determination  cannot  be  made 
from  evaluation  of  plans,  specifications  and 
documentation  alone. 

3504.3  Approval  of  compliance  assurance 
programs:  The  Division  of  Inspection  shall  evaluate 
manufacturers'  compliance  assurance  programs  and 
make  recommendations  for  approval  to  the  BBRS 
of  those  which  it  determines  to  be  in  compliance 
with  780  CMR  35  and  780  CMR  R3,  listed  in 
Appendix  A. 

3504.4  Authorization  to  vary:  A  manufactured 
building,  manufactured  building  component  or  a 
compliance  assurance  program  heretofore  approved 
in  accordance  with  780  CMR  3503.3,  shall  not  be 
varied  in  any  way  without  prior  authorization  by  the 
BBRS  in  accordance  with  780  CMR  R3,  as  in 
Appendix  A. 


462 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


MANUFACTURED  BUILDINGS,  MANUFACTURED  COMPONENTS 
AND  MANUFACTURED  HOUSING 


780  CMR  3505.0  CERTIFICATION 
3505.1  Labeling:  Any  manufactured  building  or 
manufactured  building  component  heretofore 
approved,  in  accordance  with  780  CMR  3504.0, 
shall  have  an  approved  device  or  seal  affixed  as 
certification  of  such  approval. 

780  CMR  3506.0  RECIPROCITY 

3506.1  General:  If  the  BBRS  finds  that  the 
standards  for  manufacture  and  inspection  of 
manufactured  buildings  or  manufactured  building 
components  prescribed  by  the  statutes  or  the  rules 
and  regulations  of  another  state  or  other 
governmental  agency  meet  the  objectives  of 
780  CMR  35  and  780  CMR  R3,  listed  in 
Appendix  A,  and  such  standards  are  enforced 
satisfactorily  by  such  other  state  or  governmental 
agency  or  by  its  agents,  the  BBRS  may  grant 
approval  and  the  Division  of  Inspection  shall  accept 
all  manufactured  buildings  or  manufactured  building 
components  which  have  been  approved  in 
accordance  with  this  section  by  such  other  state  or 
governmental  agency  and  shall  insure  that  the 
product  is  properly  labeled. 

3506.1.1  Condition  of  reciprocity:  The  standards 
of  another  state  shall  not  be  deemed  to  be 
satisfactorily  enforced  unless  such  other  state 
provides  for  notification  to  the  BBRS  of 
suspensions  or  revocations  of  approvals  issued  by 
that  state,  in  a  manner  satisfactory  to  the  BBRS. 

3506.2  Suspension  of  reciprocal  approval:  Upon 
recommendation  from  the  Division  of  Inspection, 
the  BBRS  shall  suspend  or  cause  to  be  suspended 
reciprocal  approval  for  the  following  reasons: 

1.  Determination  that  the  standards  for  the 
manufacture  and  inspection  of  such  manufactured 
buildings  or  manufactured  building  components 
of  another  state  or  other  governmental  agency  do 
not  meet  the  objectives  of  780  CMR  35  and 
780  CMR  R3,  listed  in  Appendix  A,  or  that  the 
standards  are  not  being  enforced  to  the 
satisfaction  of  the  Division  of  Inspection  or 
BBRS;  and 

2.  if  anotheF  state  or  governmental  agency,  or  its 
agent,  suspends  or  revokes  said  approval,  the 
approval  granted  under  780  CMR  3506.2  shall  be 
suspended  or  revoked  accordingly. 

780  CMR  3507.0  ASSURANCE  INSPECTION 
3507.1  General:  Any  person  or  firm  producing 
manufactured  buildings  or  manufactured  building 
components  applying  for  certification  shall  agree  in 
writing  that  the  Division  of  Inspection  or  the  BBRS 
has  the  right  to  conduct  unannounced  inspections  at 
any  reasonable  time. 


3507.2  Responsibilities  of  Division  of  Inspection: 

The  Division  of  Inspection  shall  carry  out  the 
following  responsibilities: 

1.  Periodically  make,  or  cause  to  be  made, 
inspections  of  the  entire  process  of  the  production 
of  manufactured  buildings  or  manufactured 
building  components  in  order  to  verify  the 
reliability  of  the  compliance  assurance  program 
and  of  the  approved  inspection  agency. 

2.  In  addition  to  other  on-site  inspection 
provided  for  in  780  CMR  3507.2,  the  Division  of 
Inspection  shall  inspect,  or  cause  to  be  inspected, 
certified  manufactured  buildings  or  manufactured 
building  components  which  it  determines  to  have 
been  sufficiently  damaged  after  certification  to 
warrant  such  action  with  regard  to  such 
manufactured  buildings  or  manufactured  building 
components  as  is  authorized  hereof,  or  as  is 
otherwise  necessary  to  eliminate  dangerous 
conditions. 

Note:  An  inspection  entailing  disassembly, 
damage  to  or  destruction  of  certified 
manufactured  buildings  or  manufactured  building 
components  shall  not  be  conducted  except  to 
implement  the  provisions  of  780  CMR  35 

780  CMR  3508.0  RESPONSffilLITY  OF 
THE  LOCAL  ENFORCEMENT  AGENCIES 

3508.1  Issuance  of  building  permits:  Upon 
application  and  in  conformity  with  the  provisions  of 
780  CMR,  the  building  official  shall  issue  building 
permits  for  installation  of  certified  manufactured 
buildings,  manufactured  building  components  or 
manufactured  housing. 

3508.1.1  Licensed  Construction  Supervisors 
and  Certified  Installers:  A  construction 
supervisor,  duly  licensed  in  accordance  with 
780  CMR  R5,  shall,  in  accordance  with  780  CMR 
108.3.5,  act  as  the  agent  for  the  owner  for  the 
purpose  of  applying  for  and  obtaining  any  and  all 
building  permits  required  for  the  field  erection  of 
all  one  or  two  family  manufactured  dwellings 
subject  to  the  provisions  of  780  CMR  35  and 
applicable  780  CMR  R3. 

As  part  of  the  building  permit  application 
process,  the  licensed  construction  supervisor  shall 
submit  to  the  building  official,  in  writing,  the 
name  of  the  installer,  who  shall  be  duly  certified 
by  the  manufacturer  to  install  said  manufacturer's 
product  and  is  identified  as  a  certified  installer  of 
manufactured  buildings  (certified  installer)  by 
said  manufacturer.  The  certified  installer  shall  be 
responsible  for  the  safe  and  proper  placement  and 
connection  of  the  manufactured  home  units  in 
accordance  with  780  CMR  35,  780  CMR  R3  and 
specialized  codes  as  listed  in  Appendix  A. 

The  licensed  construction  supervisor  shall  be 
responsible  for  the  construction  of  the  foundation 
system,  and  all  pertinent  site  work,  in  accordance 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


463 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


with  780  CMR  35  and  780  CMR  R3  listed  in 
Appendix  A.  The  licensed  construction 
supervisor  shall  provide  at  least  48  hours  notice  to 
the  building  official  before  the  placement  and 
connection  of  such  units  shall  begin. 

3508.2  Inspection:  The  local  enforcement  agency 
shall  make  the  following  inspections: 

1.  The  site  preparation  work,  including 
foundations,  installation  of  any  certified 
manufactured  buildings  or  manufactured  building 
components  or  approved  homes;  and  for  all  utility 
service  connections,  including  plumbing, 
electrical,  gas,  water  and  sewer;  for  compliance 
with  the  applicable  codes. 

2.  Inspect  all  certified  manufactured  buildings  or 
manufactured  building  components  or  approved 
manufactured  homes  upon,  or  promptly  after, 
installation  at  the  building  sites  to  determine 
whether  all  applicable  instructions  or  conditions 
have  been  followed.  This  may  include  tests  for 
tightness  of  plumbing  and  mechanical  systems, 
for  malfunctions  in  the  electrical  system,  and  a 
visual  inspection  for  obvious  violations  of 
780  CMR  R3.  Destructive  disassembly  of 
certified  manufactured  buildings  or  manufactured 
building  components  or  approved  manufactured 
homes  shall  not  be  performed  in  order  to  conduct 
such  inspections.  Nondestructive  disassembly 
may  be  performed  only  in  accordance  with 
780  CMR  R3. 

Note:  Notification  to  the  BBRS.  When  any 
local  enforcement  agency  finds  a  violation  or 
suspects  a  violation  exists,  said  violation  or 


suspected  violation  shall  be  reported  to  the 
BBRS  in  accordance  with  780  CMR  R3.5.6. 

3508.3  Issuance  of  certificates  of  occupancy:  The 

building  official  shall  issue  a  certificate  of 
occupancy  for  all  certified  manufactured  buildings 
or  approved  manufactured  homes  that  have  been 
installed  and  inspected  and  that  meet  the 
requirements  of  780  CMR. 

780  CMR  3509.0  SUSPENSION  OR 
REVOCATION  OF  CERTIFICATION 

3509.1  General:  The  Board  shall  suspend  or  revoke 
the  approval  of  any  manufactured  building  or 
manufactured  building  component  which  does  not 
comply  with  the  provisions  of  780  CMR  or  with 
780  CMR  R3. 

3509.2  Labels  of  certification:  The  Division  of 
Inspection  shall  remove  or  cause  to  be  removed  the 
label  of  certification  from  any  such  manufactured 
building  or  building  component  not  in  compliance 
until  such  time  as  it  is  brought  into  compliance  with 
780  CMR  35  and  780  CMR  R3. 

3509.3  Notice  of  suspension  or  revocation:  Notice 
shall  be  submitted  in  writing  to  the  affected  parties 
stating  the  reason  for  the  suspension  or  revocation. 

3509.4  Appeals  Procedure:  All  appeals  from 
suspension  or  revocation  shall  be  heard  by  the  State 
Building  Code  Appeals  Board  as  specified  in  the 
pertinent  provisions  of  780  CMR  122.0. 


464 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  36 

ONE  AND  TWO  FAMILY  DWELLING  CODE 

(This  Section  is  unique  to  Massachusetts.) 

780  CMR  3601.0  GENERAL  780  CMR  3601 2  PURPOSE 

ADMINISTRATION  3601.2.1  Minimum  standards:  The  purpose  of 

3601.1  General:  The  provisions  of  780  CMR  36  780  CMR  36  is  to  provide  minimum  standards  for 

shall    be    known   as   the   One    and   Two   Family  the    protection    of  life,    limb,    health,    property, 

Dwelling  Code,  and  may  be  cited  as  such.  environment  and  for  the  safety  and  welfare  of  the 

consumer,   general   public,   and  the   owners   and 

3601.1.1  Application  of  other  laws:    Nothing  occupants   of  residential   buildings   regulated   by 

herein  contained  shall  be  deemed  to  nullify  any  780  CMR  36. 
provisions  of  the  zoning  by-laws  or  ordinance  of 

any    municipality    in    the    Commonwealth    of  3601.2.2  Scope:  780  CMR  1,  in  its  entirety,  shall 

Massachusetts  insofar  as  those  provisions  deal  serve    as    the    administrative    requirements    of 

exclusively   with   those    powers    of  regulating  780  CMR  36. 
zoning  granted  by  the  provisions  of  M.G.L.  C.40A 
and  41. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  465 


780  CMR:    STATE  BOARD  OF  BUTLDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


466  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3602 


BUILDING  DEFINITIONS 


780  CMR  3602.0  GENERAL 
3602.1  Scope:  Unless  otherwise  expressly  stated, 
the  following  words  and  terms  shall,  for  the 
purposes  of  780  CMR  36,  have  the  meaning  shown 
herein.  Words  used  in  the  singular  include  the 
plural,  and  the  plural  the  singular  Words  used  in  the 
masculine  gender  include  the  feminine,  and  the 
feminine  the  masculine. 

3602.1.1  Terms  defined  in  other  codes:  Where 
terms  are  not  defined  in  780  CMR  36,  but  are 
defined  in  the  plumbing,  fire  prevention,  or 
mechanical  codes,  or  other  elsewhere  in 
780  CMR,  or  its  reference  standards  as  listed  in 
Appendix  A,  such  terms  shall  have  the  meanings 
ascribed  to  them  in  those  codes. 

3602.1.2  Terms  not  defined:  Where  terms  are 
not  defined  through  the  methods  authorized  by 
780  CMR  3602.1.1,  such  terms  shall  have  the 
ordinarily  accepted  meanings  such  as  the 
context  implies. 

780  CMR  36022 
GENERAL  BUILDING  DEFINITIONS 

ACCESSORY  STRUCTURE:  A  building,  the  use 
of  which  is  incidental  to  that  of  the  main  building 
and  which  is  located  on  the  same  lot. 

ACCESSORY  USE:  A  use  incidental  to  the 
principal  use  of  a  building  as  defined  or  limited 
by  the  provisions  of  the  local  zoning  laws. 

APPROVED:  Approved  by  the  Board  of  Building 
Regulations  and  Standards  (BBRS),  the  building 
official,  or  by  reason  of  accepted  principles  or 
tests  by  nationally  recognized  organizations,  or  by 
accepted  engineering  practice. 

APPROVED  AGENCY:  An  established  and 
recognized  agency  regularly  engaged  in 
conducting  tests  or  furnishing  inspection  services, 
when  such  agency  has  been  approved  as  defined 
herein. 

BALCONY  (Exterior):  An  exterior  floor  system 
projecting  from  a  structure  and  supported  by  thai 
structure,  with  no  additional  independem 
supports 

BASEMENT:  That  portion  of  a  building  which  is 
partly  or  completely  below  grade  (see  "Story 
above  grade") 


BOARD  OF  BUILDING  REGULATIONS  AND 
STANDARDS  (BBRS):  In  accordance  with 
M.G.L.  c.  143.  §  94,  the  Board  responsible  for 
the  development  and  promulgation  of  780  CMR 
(the  Massachusetts  State  Building  Code).  See 
M.G.L  a  143,  §§  95  through  100  for  additional 
responsibilities  of  the  BBRS. 

BUILDING:  Building  shall  mean  any  one-  and  two- 
family  dwelling  or  portion  thereof,  which  is  used, 
or  designed  or  intended  to  be  used  for  human 
habitation,  for  living,  sleeping,  cooking  or  eating 
purposes,  or  any  combination  thereof,  and  shall 
include  structures  accessory  thereto. 

BUILDING,  EXISTING:  A  building  erected  prior 
to  the  adoption  of  this  code,  or  one  for  which  a 
legal  building  permit  has  been  issued. 

BUILDING  OFFICIAL:  See  building  code 
enforcement  official  780  CMR  2, 

CEILING  HEIGHT:  Ceiling  height  shall  be  the 
clear  vertical  distance  from  the  finished  floor  to 
the  finished  ceiling 

DECK:  An  exterior  floor  system  supported  on  at 
least  two  opposing  sides  by  an  adjoining  structure 
and/or  posts,  piers,  or  other  independent  supports. 

D WELLING,  ONE  FAMILY:  A  building 
containing  one  dwelling  unit  with  not  more  than 
five  lodgers  and  boarders. 

DWELLING.  TWO  FAMILY:  A  building 
containing  two  dtvelling  units  with  not  more 
than  five  lodgers  or  boarders  per  family. 

DWELLING  UNIT:  A  single  unit  providing 
complete  independent  living  facilities  for  one  or 
more  persons  including  permanent  provisions  for 
living,  sleeping,  eating,  cooking  and  sanitation 

FOUNDATION:  A  base  constructed  to  support 
any  building  or  structure  including  but  not 
limited  to  footings,  floating  foundation,  piles  and 


FOUNDATION  WALL:  A  wall  below  the  floor 
nearest  grade  serving  as  a  support  for  a  wall, 
pier,  column  or  other  structural  part  of  a 
building. 


9/19/97  (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


467 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


GRADE:  A  reference  plane  representing  the 
average  finished  ground  level  adjoining  the 
building  at  all  exterior  walls. 

GRADE  FLOOR  WINDOW:  A  window  located 
such  that  the  sill  height  of  the  window  is  not  more 
than  44  inches  (1118  mm)  above  or  below  the 
finished  grade  adjacent  to  the  window. 

GREENHOUSE:  An  enclosed  detached  accessory 
structure  consisting  primarily  of  light -transmitting 
materials  and  used  exclusively  for  growing  plants. 
In  accordance  with  St  1973,  c  672,  the 
provisions  of  the  780  CMR  shall  not  apply  to 
greenhouses  covered  exclusively  with  plastic 
film;  provided,  however,  that  the  provisions  of 
M.  G.L.  c  40A  shall  continue  to  apply. 

GUARDRAIL  SYSTEM:  A  system  of  building 
components  located  near  open  sides  of  elevated 
walking  surfaces. 

HABITABLE  ROOM  (SPACE):  Habitable  room 
shall  mean  any  room  meeting  the  requirements  of 
780  CMR  36  for  sleeping,  living,  cooking  or 
dining  purposes,  excluding  such  enclosed  places 
as  closets,  pantries,  bath  or  toilet  rooms,  hallways, 
laundries,  storage  spaces,  utility  rooms  and 
similar  spaces. 

HANDRAIL:  A  horizontal  or  sloping  rail  grasped 
for  guidance  or  support. 

KITCHEN:  Kitchen  shall  mean  an  area  used,  or 
designated  to  be  used  for  the  preparation  of  food. 

LISTED  and  LISTING:  Terms  referring  to 
equipment  which  is  shown  in  a  list  published  by 
an  approved  testing  agency  qualified  and 
equipped  for  experimental  testing  and  maintaining 
an  adequate  periodic  inspection  of  current 
productions  and  whose  listing  states  that  the 
equipment  complies  with  nationally  recognized 
standards,  when  installed  in  accordance  with  the 
manufacturer's  installation  instructions. 

LOADS,  LrVE  AND  DEAD:  See  780  CMR  2. 


MANUFACTURED  HOME: 

and  780  CMR-R3. 


See  780  CMR  35 


MUNICIPALITY:  Any  city  or  town  in  the 
Commonwealth  of  Massachusetts.  The  word 
"municipality"  shall  be  construed,  where  the 
context  requires,  as  though  followed  by  the 
words  "or  combination  of  municipalities". 

OCCUPIED  SPACE:  See  780  CMR  2. 

REPAIRS,  ORDINARY:  See  780  CMR  2. 

STORY:  Story  is  that  portion  of  a  building  included 
between  the  upper  surface  of  any  floor  and  the 
upper  surface  of  the  floor  next  above,  except  that 
the  topmost  story  shall  be  that  habitable  portion 
of  a  building  included  between  the  upper  surface 
of  the  topmost  floor  and  ceiling  or  roof  above. 

STORY  ABOVE  GRADE:  Any  story  having  its 
finished  floor  surface  entirely  above  grade  except 
that  a  basement  shall  be  considered  as  a  story 
above  grade  when  the  finished  surface  of  the  floor 
above  the  basement  is: 

1 .  More  than  six  feet  (1829  mm)  above  grade 
plane; 

2.  More  than  six  feet  (1829  mm)  above  the 
finished  ground  level  for  more  than  50  percent 
of  the  total  building  perimeter;  or 

3.  More  than  12  feet  (3658  mm)  above  the 
finished  ground  level  at  any  point. 

WALL:  See  780  CMR  2. 

WINDOW:  Window  shall  mean  a  glazed  opening, 
including  portions  of  glazed  doors. 

WOOD  STRUCTURAL  PANEL:  A  structural 
panel  product  composed  primarily  of  wood,  and 
meeting  the  requirements  of  DOC  PS  1  or  DOC 
PS  2.  Wood  structural  panels  include  all  veneer 
plywood,  composite  panels  containing  a 
combination  of  veneer  and  wood-based  material, 
and  mat-formed  panels  such  as  oriented  strand 
board  and  waferboard. 


468 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3603 


BUILDING  PLANNING 

(This  Section  is  unique  to  Massachusetts.) 


780  CMR  3603.1  STRUCTURAL  DESIGN 
CRITERIA 

3603.1.1  Design:  Buildings  and  structures,  and  all 
parts  thereof,  regulated  by  780  CMR  36,  shall  be 
constructed  to  support  safely  all  applied  dead,  live 
and  environmental  loads  specified  in  780  CMR 
3603.1. 

Exception:  One  and  Two  Family  Dwellings  are 
exempt  from  the  earthquake  load  requirements  of 
780  CMR  1612. 

3603.1.2  Dead  load:  The  actual  weights  of  materials 
and  construction  shall  be  used  for  determining  dead 
load  with  consideration  for  the  dead  load  of  fixed 
service  equipment. 

3603.1.3  Live  load:  The  minimum  uniformly 
distributed  live  load  shall  be  as  specified  in  Table 
3603. 1.3.  Elevated  garage  floors  shall  be  designed  to 
support  a  2,000  pound  (8.90  kN)  concentrated  load 
applied  over  a  20  square  inch  (0  0129  m")  area,  in 
addition  to  the  loads  specified  in  table  3603. 1.3. 

3603.1.4  Roof  Live  Load:  Roofs  shall  be  designed 
to  support  the  live  load  specified  in  Table  3603.1.4, 
or  the  snow  load  specified  in  780  CMR  3603.1.5, 
whichever  is  greater. 

3603.1.5  Basic  snow  load:  Figures  3603.1.5a, 
3603.1.5b,  3603.1.5c  and  3603. 1.5d  define  four 
snow  load  zones.  The  basic  snow  load  for  each  zone 
shall  be  applied  to  the  horizontal  projection  of 
sloped  or  flat  roofs  and  unenclosed  floor  areas,  as  a 
uniformly  distributed  load,  P ,,  in  pounds  per  square 
foot,  as  specified  in  Table  3603.1.5. 

3603.1.6  Deflection:  The  allowable  deflection  of 
any  structural  member  under  the  live  load  or  snow 
load  listed  in  780  CMR  3603.1.3,  3603.1.4  and 
3603.1.5  shall  not  exceed  the  values  in  Table 
3603.1.6. 


Table  3603.1.3 

MINIMUM  UND70RMLY  DISTRD3UTED 

LIVE  LOADS 

(POUNDS  PER  SQUARE  FOOT) 


USE 


Balconies  and  decks 


Garages  (passenger  cars  only) 


Attics  (roof  slope  not  steeper  than  3  in  1 2  -  no 
storage) 


Attics  (limited  storage) 


Living  Areas  (except  sleeping  rooms) 


Sleeping  Rooms 


Guardrails  and  Handrails  (single  concentrated 
load  at  anv  point  along  the  top) 


LIVE 
LOAD  (psf) 


^ 


200 


Notes: 

(1)  See  also  780  CMR  3603. 1.3 

(2)  In  addition  to  the  uniformly  distributed  live  load, 
individual  stair  treads  shall  be  designed  for  a  single 
concentrated  load  of  300  pounds  over  an  area  of  four 
square  inches. 

Table  3603.1.4 

MINIMUM  ROOF  LIVE  LOAD 

(POUNDS  PER  SQUARE  FOOT  OF 

HORIZONTAL  PROJECTION) 


ROOF  SLOPE 

TRIBUTARY  LOADED 

AREA  (square  feet)  for  any 

structural  member 

0  to  200 
sf 

201sfto600 
sf 

Over  600 
sf 

Flat,  or  rise  less  than  4 
inches  per  foot 

20 

16 

12 

Rise  4  inches  per  foot  to 
less  than  1 2  inches  per  foot 

16 

14 

12 

Rise  1 2  inches  per  foot  or 
greater 

12 

12 

12 

Table  3603.1.5 
BASIC  SNOW  LOAD,  Pf 

SNOW  LOAD  ZONE  l 

BASIC  SNOW  LOAD  Vf 

1 

25  psf 

: 

30  psf 

3 

35  psf 

4 

40  psf 

Notes: 

1.    See  figures  3603.1.5  c 

through 

d 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


469 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Figure  3603.1.5a 

MINIMUM  UNIFORM  SNOW  LOAD  MAP 

ZONE  1 


List  of  Towns  in  Minimum  Uniform 
Snow  Load  Zones  Zone  1 


Barnstable 

Boumc 

Brewster 

Gay  Head 
Gosnold 

Sandwich 

Ttsbury 

Harwich 

Truro 

Chatham 

Chilmark 

Mash  pee 

Vineyard  Haven 

Dennis 

Nantucket 

Wellfleet 
West  Tisbury 

Eastham 

Oak  Bluffs 

Edgartown 
Falmouth 

Orleans 
Provincetown 

Yarmouth 

470 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


Figure  3603.1.5b 

MINIMUM  UNIFORM  SNOW  LOAD  MAP 

ZONE  2 


pLYMCO'T-4 


List  of  Towns  in  Minimum  Uniform 


Snow  Load  Zones 

Zone  2 

Abington 

Cambridge 

Freetown 

Lawrence 

Milton 

Randolph 

Taunton 

Acushnet 

Carlisle 

Lexington 

Raynham 

Tewksbury 

Amesbury 

Carver 

Georgetown 

Lowell 

Nahant 

Reading 

Topsfield 

Andover 

Chemlsford 

Gloucester 

Lynn 

New  Bedford 

Rehoboth 

Tyngsborough 

Arlington 

Chelsea 

Grovel  and 

Lynnfieid 

Newbury 

Revere 

Attleboro 

Cohasset 

Newburyport 

Rochester 

Wakefield 

Halifax 

Newton 

Rockland 

Waltham 

Bedford 

Danvers 

Hamilton 

Maiden 

N.  Andover 

Rockport 

Wareham 

Belmont 

Dartmouth 

Hanover 

Manchester 

N.  Attleboro 

Rowley 

Watertown 

Berkley 

Dighton 

Hanson 

Mansfield 

N.  Reading 

Wenham 

Beverly 

Dracut 

Haverhill 

Marblehead 

Norton 

Salem 

W.  Bridgewater 

Billerica 

Duxbury 

Hingham 

Marion 

Norwell 

Salisbury 

W.  Newbury 

Boston 

Holbrook 

Marsh  field 

Saugus 

Westport 

B  oxford 

E.  Bridgewater 

Hull 

Mattapoisett 

Peabody 

Scituate 

Weymouth 

Braintree 

Easton 

Med  ford 

Pembroke 

Seckonk 

Whitman 

Bridgewater 

Essex 

Ipswich 

Melrose 

Plvmouth 

Somerset 

Wilmington 

Brockton 

Everett 

Merrimac 

Plympton 

Somerville 

Winchester 

Brookline 

Kingston 

Methuen 

Stoncham 

Winthrop 

Burlington 

Fairhaven 

Middleborough 

Quincy 

Swampscott 

Wo  bum 

Fall  River 

Lakcville 

Middleton 

Swansea 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Figure  3603.1.5c 

MINIMUM  UNIFORM  SNOW  LOAD  MAP 

ZONE  3 


,  EyggrlA.gS'STCT-l 


List  of  Towns  in  Minimum  Uniform 


low  Load  Zones  Zone  3 

Acton 

Chicopee 

Greenfield 

Lunenburg 

Oakham 

Sunderland 

Wendell 

Agawam 

Clinton 

Groton 

Orange 

Suttton 

West  Boylston 

Amherst 

Concord 

Marlborough 

Oxford 

Sharon 

West  Brookfield 

Ashbumham 

Hadley 

Maynard 

Sherborn 

W.  Springfield 

Ashby 

Dedham 

Hampden 

Medfield 

Palmer 

Shirley 

Westborough 

Ashland 

Deerfield 

Hardwick 

Millbury 

Paxton 

Shrewsbury 

Westfield 

Athol 

Douglas 

Harvard 

Millville 

Pelham 

Shutesbury 

Westford 

Auburn 

Dover 

Hatfield 

Medway 

Pepperell 

S.  Hadley 

Westminster 

Avon 

Dudley 

Holland 

Mendon 

Petersham 

Southampton 

Weston 

Ayer 

Dunstable 

Holliston 

Milford 

Phillipston 

Southborough 

Westwood 

Holden 

Millis 

Plainville 

Wilbraham 

Barre 

E.  Brookfield 

Holyoke 

Monson 

Princeton 

Temploton 

Winchendon 

Belchertown 

Easthampton 

Hopedale 

Montague 

Townsend 

Whately 

Bellingham 

E.  Longmeadow 

Hopkinton 

Royalston 

Worcester 

Berlin 

Erving 

Hubbardston 

Natick 

Rutland 

Upton 

Wrentham 

Bernardston 

Hudson 

Needham 

Uxbridge 

Blackstone 

Fitchburg 

New  Braintree 

Southbridge 

Bolton 

Foxborough 

Lancaster 

New  Salem 

Southwick 

Wales 

Boylston 

Framingham 

Leicester 

Norfolk 

Spencer 

Walpole 

Boxborough 

Franklin 

Leominster 

North  Brookfield 

Springfield 

Ware 

Brimfield 

Leverett 

Northampton 

Sterling 

Warren 

Brookfield 

Gardner 

Lincoln 

Northborough 

Stoughton 

Warwick 

Gill 

Littleton 

Northbridge 

Stow 

Wayland 

Canton 

Grafton 

Longmeadow 

Northfield 

Sturbridge 

Webster 

Charlton 

Granby 

Ludlow 

Norwood 

Sudbury 

Wellesley 

472 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 

Figure  3603.1.5d 

MINIMUM  UNIFORM  SNOW  LOAD  MAP 

ZONE  4 


Wi  LIJA.TSTP 


Cgr-NVA~Y 

SiEattvi  LLH- 


List  of  Towns  in  Minimum  Uniform 


Snow  Load  Zones  Zone  4 

Adams 

Colrain 

Hancock 

Monterey 

Plainfield 

Tolland 

Alford 

Conway 

Hawley 

Montgomery 

Tyringham 

Ashfield 

Cummin  gton 

Heath 

Mount  Washington 

Richmond 

Hinsdale 

Rowe 

Washington 

Becket 

Dalton 

Huntington 

New  Ashford 

Russell 

W.  Stockbridge 

Blandford 

New  Marlborough 

Westhampton 

Buck]  and 

Egremont 

Lanesborough 

Sandisfield 

Williamsburgh 

Lee 

North  Adams 

Savov 

Williamstown 

Charlemont 

Florida 

Lenox 

Sheffield 

Windsor 

Cheshire 

Leyden 

Otis 

Shelboume 

Worthmgton 

Chester 

Goshen 

Stockbridge 

Chesterfield 

Granville 

Middlefield 

Peru 

Clarksburg 

Great  Barrington 

Monroe 

Pittsfield 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


473 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  3603.1.6 

ALLOWABLE  LIVE  LOAD  DEFLECTION 

OF  STRUCTURAL  MEMBERS 


STRUCTURAL  MEMBER 

ALLOWABLE 

DEFLECTION 

Rafters  having  slopes  greater  than  3  in  1 2 
-no  finished  ceiling  attached  to  rafters 

L/180 

Interior  walls  and  partitions 

H/180 

Floors  and  veneer  plastered  ceilings 

L/360 

Gypsum  panel  ceilings  and  all  other 
structural  members 

L/240 

Notes: 

L  =  Span  length 
H  =  Span  height 

780  CMR  36032 

CONSTRUCTION  IN  AREAS  SUBJECT 

TO  FLOODING 

3603.2.1       Flood       Resistant       Construction: 

Construction  in  areas  designated  as  subject  to 
flooding  on  the  community  Flood  Insurance  Rate 
Map  (FIRM)  shall  be  designed  and  constructed  in 
accordance  with  the  applicable  provisions  of 
780  CMR  3107. 

780  CMR  3603 3  FIRERESISTANCE  RATING 
OF  EXTERIOR  WALLS 

3603.3.1  Exterior  walls:  Exterior  walls  located  less 
than  three  feet  (0.914m)  from  property  lines  shall 
have  a  minimum  of  one-hour  fire-resistive  rating. 
The  fire-resistive  rating  of  exterior  walls  located  less 
than  three  feet  (0.914  m)  from  a  property  line  shall 
be  rated  for  exposure  from  both  sides.  Projections 
beyond  the  exterior  wall  shall  not  extend  more  than 
12  inches  (0.305  m)  into  areas  where  openings  are 
prohibited. 

3603.3.2  Openings:  Openings  shall  not  be  permitted 
in  exterior  walls  of  dwellings  located  less  than  three 
feet  (914  mm)  from  the  property  line.  This  distance 
shall  be  measured  perpendicular  to  the  vertical  plane 
of  the  wall. 

780  CMR  3603.4  DWELLING  UNIT 
SEPARATION 

3603.4.1  Two-family  dwellings:  Dwelling  units  in 
two-family  dwellings  shall  be  separated  by  wall 
and/or  floor-ceiling  assemblies  of  not  less  than  one- 
hour  fire-resistive  rating  when  tested  in  accordance 
with  ASTM  E  119,  as  listed  in  Appendix  A.  Fire- 
resistive-rated  floor-ceiling  and  wall  assemblies 
shall  extend  to,  and  be  tight  against,  the  exterior 
wall.  Wall  assemblies  shall  extend  to  the  underside 
of  the  roof  sheathing. 

3603.4.2  Supporting  construction:  When  floor 
assemblies  are  required  to  be  fire-resistive  rated  by 
780 CMR  3603.4.1,  the  supporting  construction  of 
such  assemblies  shall  have  an  equal  or  greater  fire- 
resistive  rating. 


3603.4.3  Sound  transmission:  Wall  and  floor- 
ceiling  assemblies  separating  dwelling  units  shall 
provide  airborne  sound  insulation  for  walls  and  both 
airborne  and  impact  sound  insulation  for  floor- 
ceiling  assemblies. 

3603.4.3.1  Airborne  noise:  Airborne  sound 
insulation  for  wall  and  floor-ceiling  assemblies 
shall  meet  a  Sound  Transmission  Class  (STC)  of 
45  when  tested  in  accordance  with  ASTM  E  90. 

3603.4.3.2  Penetrations:  Penetrations  or 
openings  in  the  assembly  for  pipes,  ventilation  or 
exhaust  ducts  shall  be  sealed,  lined,  insulated  or 
otherwise  treated  to  maintain  the  required  ratings. 

3603.4.3.3  Structural-borne  noise:  Impact  sound 
insulation  for  floor-ceiling  assemblies  shall  meet 
an  Impact  Insulation  Class  (HC)  of  45  when  tested 
in  accordance  with  ASTM  E  492.  Floor  covering 
may  be  included  in  the  assembly  to  obtain  the 
required  rating. 

780  CMR  3603.5  GARAGE  SEPARATION 

3603.5.1  Opening  protection:  Openings  from  a 
private  garage  directly  into  a  room  used  for  sleeping 
purposes  shall  not  be  permitted.  Other  openings 
between  the  garage  and  dwelling  shall  be  equipped 
with  either  solid  wood  doors  not  less  than  1%  inch 
(45  mm)  in  thickness  or  20-minute  fire-rated  doors. 
Self  closing  devices  and  fire  resistive  rated  door 
frames  are  not  required. 

3603.5.2  Fire  Separation:  The  garage  shall  be 
separated  from  the  residence  and  its  attic  area  by 
means  of  minimum  %  inch  (16  mm)  type  X  gypsum 
board  applied  to  the  garage  side.  Wherever  the  attic 
area  is  continuous  between  the  garage  and  the 
dwelling  a  firestop  of  5/a  inch  (16  mm)  type  X 
gypsum  board  shall  be  used  to  form  a  barrier  to 
separate  the  garage  and  dwelling. 

3603.5.3  Floor  surface:  Garage  and  carport  floor 
surfaces  shall  be  constructed  of  concrete  or  other 
approved  noncombustible  material.  Slab  on  grade 
construction  shall  be  in  accordance  with  the 
provisions  of  780  CMR  3605.5.  The  minimum 
floor  thickness  shall  be  3  Vz  inches.  The  area  of  floor 
used  for  parking  of  automobiles  or  other  vehicles 
shall  be  sloped  to  facilitate  drainage  toward  the  main 
vehicle  entry/exit  doorway.  All  door  openings 
between  the  garage  and  the  dwelling  shall  be 
provided  with  a  raised  sill  with  a  minimum  height  of 
four  inches. 

780  CMR  3603.6  LIGHT,  VENTILATION  AND 
HEATING 

3603.6.1  Light  required:  Every  room  or  space 
intended  for  human  occupancy  shall  be  provided 
with  natural  or  artificial  light. 


474 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


Exception  1:    Every  bathroom  and  toilet  room 
shall,  as  a  minimum,  be  provided  with  artificial 
light. 

Exception  2:  All  interior  and  exterior  stairways 
shall  be  provided  with  artificial  light  providing 
direct  or  indirect  illumination  and  capable  of 
illuminating  the  entire  length  of  the  stairway  and 
associated  landings.  The  control  for  activation  of 
the  required  interior  stairway  lighting  shall  be 
accessible  at  the  top  and  bottom  of  each  stair 
without  traversing  any  step  of  the  stair  and  shall 
otherwise  be  installed  in  accordance  with  the 
requirements  of  527  CMR  12.00,  the 
Massachusetts  State  Electrical  Code,  as  listed  in 
Appendix  A  The  illumination  of  exterior  stairs 
shall  be  controlled  from  inside  the  dwelling  unit 
unless  continuously  illuminated  or  automatically 
activated. 

3603.6.2  Ventilation  required:  Every  room  or 
space  intended  for  human  occupancy  shall  be 
provided  with  natural  or  mechanical  ventilation. 

Exception:  Every  bathroom  and  toilet  room  shall 
be  equipped  with  a  mechanical  exhaust  fan  and 
associated  ductwork  with  the  fan  exhausting,  as  a 
minimum,  at  50  cfm  if  operated  intermittently  or 
20  cfm  if  continuously  operated.  Such  bathroom 
exhaust  shall  vent  directly  to  the  outside  and  no 
exhaust  vent  termination  to  attics  or  other  interior 
portions  of  the  building  are  allowed. 

3603.6.3  Heating  required:  One  and  two  family 
dwellings  shall  be  designed  with  heating  systems 
complying  with  the  requirements  of  780  CMR 
3603.21. 

3603.6.4  Natural  light 

3603.6.4.1  General:  Should  natural  lighting  be 
chosen  as  a  lighting  option,  in  the  application  of 
the  provisions  of  780  CMR  3603.0  for  habitable 
and  occupiable  rooms,  unless  otherwise 
specifically  required  by  the  provisions  of 
780  CMR  4  for  special  occupancies,  the 
requirements  of  780  CMR  3603.6.4.2  through 
780  CMR  3603.6.4.6  shall  apply. 

3603.6.4.2  Minimum  glazing  area:  Every  room 
or  space  intended  for  human  occupancy  shall  have 
an  exterior  glazing  area  of  not  less  than  8%  of  the 
floor  area.  Vz  of  the  required  area  of  glazing  shall 
be  openable.  Glazed  openings  shall  be  located 
such  that  they  open  directly  onto  a  street  or  public 
alley,  or  a  yard  or  court,  or  other  open  space 
located  on  the  same  lot  as  the  building  Glazed 
openings  are  permitted  to  face  into  a  roofed  porch 
where  the  porch  abuts  a  street,  yard  or  court,  or 
other  open  area  and  the  longer  side  of  the  porch  is 
at  least  65%  open  and  unobstructed  and  the 


ceiling  height  of  the  porch  is  not  less  than  seven 
feet  (2134  mm). 
Exceptions: 

1 .  Glazed  areas  need  not  be  openable  where 
the  opening  is  not  required  by  780  CMR 
3603.10.4  and  an  approved  mechanical 
ventilation  system  is  provided  which  is  capable 
of  producing  0.35  air  change  per  hour  in  the 
room  or  a  whole-house  mechanical  ventilation 
system  is  installed  capable  of  supplying 
outdoor  ventilation  air  of  15  cubic  feet  per 
minute  (cfm)  (7.08  L/s)  per  occupant  computed 
on  the  basis  of  two  occupants  for  the  first 
bedroom  and  one  occupant  for  each  additional 
bedroom. 

2.  The  glazed  areas  may  be  omitted  in  rooms 
where  the  opening  is  not  required  by  780  CMR 
3603.10.4  and  an  approved  mechanical 
ventilation  system  is  provided  capable  of 
producing  0.35  air  change  per  hour  in  the  room 
or  a  whole-house  mechanical  ventilation 
system  is  installed  capable  of  supplying 
outdoor  ventilation  air  of  15  cfm  (7.08  L/s)  per 
occupant  computed  on  the  basis  of  two 
occupants  for  the  first  bedroom  and  one 
occupant  for  each  additional  bedroom,  and 
artificial  light  is  provided  capable  of  producing 
an  average  illumination  of  six  foot-candles 
(6.46  Ix)  over  the  area  of  the  room  at  a  height 
of  30  inches  (762  mm)  above  the  floor  level. 

3603.6.4.3  Adjoining  spaces:  Where  natural  light 
for  rooms  or  spaces  without  exterior  glazing  areas 
is  provided  through  an  adjoining  room,  the 
unobstructed  opening  to  the  adjoining  room  shall 
be  at  least  8%  of  the  floor  area  of  the  interior 
room  or  space,  but  not  less  than  25  square  feet 
(2.33  rrf).  The  exterior  glazing  area  shall  be  based 
on  the  total  floor  area  being  served. 

3603.6.4.4  Stairways:  See  7S0  CMR  3603.6.1, 
Exception  2 

3603.6.4.5  Hallways:  Natural  light  shall  be 
capable  of  penetrating  the  full  length  of  the 
hallway. 

3603.6.4.6  Bathrooms  and  toilet  rooms:  See 

780  CMR  3603.6.1,  Exception  1. 

3603.6.5  Artificial  light 

3603.6.5.1  General:  Artificial  light  shall  be 
capable  of  providing  the  minimum  illumination 
considered  safe  for  the  specific  space  application 
(an  average  illumination  of  six  foot  candles  over 
the  area  of  a  room  at  a  height  of  30  inches  above 
the  floor  is  typically  considered  acceptable  except 
for  bathrooms  and  toilet  rooms  where  three  foot- 
candles,  so  measured  is  typically  considered 
acceptable) 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


475 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3603.6.6  Natural  ventilation 

3603.6.6.1  General:  Natural  ventilation  of  an 
occupied  space  shall  be  provided  by  means  of 
windows,  doors,  louvers  or  other  natural  openings 
to  the  outdoor  air. 

3603.6.6.2  Ventilation    area    required:    The 

minimum  openable  area  to  the  outdoors  shall  be 
4%  of  the  floor  area  being  ventilated. 

3603.6.6.2.1  Adjoining  spaces:  Where  rooms 
and  spaces  without  openings  to  the  outdoors 
are  ventilated  through  an  adjoining  room,  the 
unobstructed  opening  to  the  adjoining  room 
shall  be  at  least  8%  of  the  floor  area  of  the 
interior  room  or  space,  but  not  less  than  25 
square  feet  (2.33  m").  The  ventilation  openings 
to  the  outdoors  shall  be  based  on  the  total  floor 
area  being  ventilated. 

3603.6.6.2.2  Bathrooms  and  toilet  rooms: 
See  780  CMR  3603.6.2,  Exception. 

3603.6.6.2.3  Openings  below  grade: 
Openings  below  grade  shall  be  acceptable  for 
natural  ventilation  provided  that  the  outside 
horizontal  clear  space  measured  perpendicular 
to  the  opening  is  1  Vi  times  the  depth  below  the 
average  adjoining  grade. 

3603.6.6.3  Openings  onto  yards,  courts  or  open 
areas:  Natural  ventilation  shall  be  provided  by 
openings  onto  yards,  courts  or  other  open  space 
on  the  same  lot. 

3603.6.7  Mechanical  ventilation 

3603.6.7.1  General:  Mechanical  ventilation  shall 
conform  to  the  requirements  of  780  CMR  36.0 
and  otherwise  to  the  requirements  of  the  BOCA 
National  Mechanical  Code  listed  in  Appendix  A. 

3603.6.8  Ventilation  of  special  spaces 

3603.6.8.1  Roof  spaces:  Enclosed  attics  and 
enclosed  rafter  spaces  formed  where  ceilings  are 
applied  directly  to  the  underside  of  roof  rafters, 
shall  have  cross  ventilation  for  each  separate 
space  by  ventilation  openings  that  are  protected 
against  the  entrance  of  rain  and  snow.  The 
openings  shall  be  covered  with  corrosion-resistant 
mesh  not  less  than  V*  inch  (6  mm)  nor  more  than 
Vi  inch  (13  mm)  in  any  direction. 

3603.6.8.1.1  Ventilating  area:  The  minimum 
required  net  free  ventilating  area  for  such  roof 
spaces  shall  be  /150  of  the  area  of  the  space 
ventilated,  except  that  the  minimum  required 
area  shall  be  reduced  to  /300,  provided  that:  a 
vapor  retarder  having  a  permeance  not 
exceeding  one  perm  is  installed  on  the  warm 
side  of  the  ceiling;  or  at  least  50%  and  not 
more  than  80%,  of  the  required  ventilating  area 
is  provided  by  ventilators  located  in  the  upper 
portion  of  the  space  to  be  ventilated  at  least 


three  feet  (914  mm)  above  eave  or  cornice 
vents,  with  the  balance  of  the  required 
ventilation  provided  by  eave  or  cornice  vents. 

3603.6.8.2  Basements,  cellars  and  crawl 
spaces:  All  basements,  cellars  which  are  not 
used  as  habitable,  occupiable  space,  and  crawl 
spaces,  other  than  crawl  spaces  used  as  an 
underfloor  plenum,  shall  be  ventilated  by 
openings  in  exterior  foundation  walls,  by 
openable  windows  or  by  approved  mechanical 
means.  Openings  or  openable  windows  shall  be 
located  as  as  near  as  practical  to  provide  cross 
ventilation.  The  openings  shall  be  covered 
with  corrosion  resistant  mesh  not  less  than  Vi 
inch  (6  mm)  nor  more  than  Vz  inch  (13  mm)  in 
any  direction,  except  than  when  openable 
windows  are  used  for  basement  or  cellar 
ventilation,  standard  window  screens  may  be 
used  as  the  corrosion  resistant  mesh. 
Exception: 

1 .  Basements  or  cellars  used  as  habitable, 
occupiable  space  (Typically  basements  and 
cellars  are  not  classified  as  habitable, 
occupiable  space  -  see  Definitions, 
780  CMR  2  and  1202)  shall  satisfy  the 
ventilation  requirements  of  780  CMR 
3603.6.6  or  780  CMR  3603.6.7,  as 
applicable. 

2.  All  basements  and  cellars  containing 
solid  fuel  fired  or  fossil  fired  appliances 
shall  additionally  satisfy  combustion  air 
requirements  of  780  CMR  3611.1 

3603.6.8.2.1  Opening  size:  Openings  or 
openable  windows  shall  have  a  net  area  of 
not  less  than  one  square  foot  (0.093  m  )  for 
each  150  square  feet  (13.95  m )  of 
foundation  floor  area.  Where  an  approved 
vapor  retarder  is  installed  over  the  ground 
surface,  the  required  net  area  of  openings 
shall  be  reduced  to  0. 1  square  foot  (0.093 
m2)  for  each  150  square  feet  (13.95  m  )  and 
where  vents  are  provided,  they  shall  have 
manually  operable  louvers. 

Exception:  Basements  and  cellars  not 
used  as  habitable,  occupiable  space  shall 
be  provided  with  a  minimum  of  four 
sliding  type,  or  awning  type  basement 
windows  for  every  1500  square  feet  of 
floor  area,  or  multiples  thereof,  and  shall 
be  located,  as  near  as  practical,  to  provide 
cross  ventilation. 

3603.6.8.2.2  Alternative  mechanical 
ventilation:  Enclosed  attics,  rafter, 
basement,  cellar  and  crawl  spaces  which  are 
not  ventilated  as  herein  required  shall  be 
equipped  with  a  mechanical  ventilation 
system  conforming  to  the  requirements  of 
the  BOCA  National  Mechanical  Code  listed 
in  Appendix  A 


476 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


780  CMR  3603.7  ROOM  DIMENSIONS 
3603.7.1  Floor  area:  Every  dwelling  unit  shall  have 
at  least  one  room  which  shall  have  not  less  than  150 
square  feet  (13.95  m  )  of  floor  area.  Other  habitable 
rooms,  except  kitchens,  shall  have  an  area  of  not  less 
than  70  square  feet  (6.51  m  ).  Every  kitchen  shall 
have  not  less  than  50  square  feet  (4.64  m  )  Habitable 
rooms,  except  kitchens  shall  not  be  less  than  seven 
feet  (2134  mm)  in  any  horizontal  direction. 

780  CMR  3603.8  CEILING  HEIGHT 
REQUIREMENTS 

3603.8.1  Minimum  ceiling  height:  Habitable 
rooms,  except  kitchens,  shall  have  a  ceiling  height  of 
not  less  than  seven  feet  six  inches  (2286  mm)  for  at 
least  50%  of  their  required  areas.  Not  more  than 
50%  of  the  required  area  may  have  a  sloped  ceiling 
less  than  seven  feet  six  inches  (2286  mm)  in  height 
with  no  portion  of  the  required  areas  less  than  five 
feet  (1524  mm)  in  height  If  any  room  has  a.  furred 
ceiling,  the  prescribed  ceiling  height  is  required  for 
at  least  50%  of  the  area  thereof,  but  in  no  case  shall 
the  height  of  the  furred  ceiling  be  less  than  seven 
feet  (2134  mm) 

Exceptions: 

1 .  Beams  and  girders  spaced  not  less  than  four 
feet  (1219  mm)  on  center  may  project  not  more 
than  six  inches  (153  mm)  below  the  required 
ceiling  height. 

2.  All  other  rooms  including  kitchens,  bathrooms 
and  hallways  shall  have  a  minimum  ceiling  height 
of  seven  feet  (2134  mm)  measured  to  the  lowest 
projection  from  the  ceiling. 

3 .  Basements  not  used  for  habitable  spaces  shall 
have  a  minimum  clear  ceiling  height  of  six  feet 
eight  inches  (2032  mm)  except  for  under  beams, 
girders,  ducts  or  other  obstructions  where  the 
clear  height  shall  be  a  minimum  of  six  feet  four 
inches  (1931  mm). 

3603.8.2  Height  effect  on  room  area:  Portions  of 
a  room  with  a  sloping  ceiling  measuring  less  than 
five  feet  zero  inches  (1524  mm)  or  a.  furred  ceiling 
measuring  less  than  seven  feet  zero  inches  (2134 
mm)  from  the  finished  floor  to  the  finished  ceiling 
shall  not  be  considered  as  contributing  to  the 
minimum  required  habitable  area  for  that  room. 

3603.8.3  Stairway  ceiling  height:  Stairway 
headroom  clearances  shall  be  in  accordance  with  the 
provisions  of  780  CMR  3603.13.3. 

780  CMR  3603.9  ACCESS  TO  CRAWL 
SPACES  AND  ATTICS 

3603.9.1  Access  to  crawl  spaces:  Access  shall  be 
provided  to  crawl  spaces  by  an  opening  not  less  than 
18  inches  (457  mm)  by  24  inches  (610  mm). 


3603.9.2  Access  to  attics:  An  opening  not  less  than 
22  inches  by  30  inches  (559  mm  by  762  mm)  with 
ready  access  thereto  shall  be  provided  to  any  attic 
area  having  a  clear  height  of  over  30  inches  (762 
mm).  Where  doors  or  other  openings  are  installed  in 
the  draftstopping,  such  doors  shall  be  self-closing 
and  be  of  approved  materials  as  specified  in  this 
section,  and  the  construction  shall  be  tightly  fitted 
around  all  pipes,  ducts  or  other  assemblies  piercing 
the  draftstopping. 

780  CMR  3603.10  MEANS  OF  EGRESS 

3603.10.1  Means  of  egress:  Egress  from  all 
dwelling  units  shall  be  by  means  of  two  exit  doors, 
remote  as  possible  from  each  other  and  leading 
directly  to  grade.  Such  doors  shall  be  provided  at 
the  normal  level  of  entry/exit  In  addition,  all  other 
floors  within  a  dwelling  unit  shall  have  at  least  one 
means  by  which  a  continuous  and  unobstructed  path 
to  the  exit  doors,  by  means  of  stairways,  corridors, 
hallways  or  combinations  thereof  is  provided 

Exception:  In  split  level  and  raised  ranch  style 
layouts,  the  two  separate  exit  doors  required  by 
780  CMR  3603.10.1  are  permitted  to  be  located 
on  different  levels. 

3603.10.2  Exit  doors:  One  of  the  required  exit  doors 
required  by  780  CMR  3603.10  1  shall  be  a 
side-hinged  swinging  door.  The  second  exit  door 
may  be  provided  by  a  side-hinged  swinging  door  or 
sliding  type  doors.  Side  hinged  swinging  doors 
provided  to  meet  this  requirement  may  swing 
inward. 

3603.10.3  Door  hardware:  Double  cylinder  dead 
bolts  requiring  a  key  operation  on  both  sides  are 
prohibited  on  required  means  of  egress  doors  serving 
more  than  one  dwelling  unit. 

3603.10.4  Emergency  egress  from  sleeping  rooms: 

Sleeping  rooms  shall  have  at  least  one  openable 
window  or  exterior  door  approved  for  emergency 
egress  or  rescue  in  each  such  room.  The  units  shall 
be  operable  from  the  inside  to  a  full  clear  opening 
without  the  use  of  a  key  or  tool.  Emergency  escape 
windows,  under  780  CMR  3603.10.4,  shall  have  a 
sill  height  of  not  more  than  44  inches  (1118  mm) 
above  the  floor 

3603.10.4.1  Minimum  size.  All  emergency 
escape  windows  from  sleeping  rooms  shall  have 
a  net  clear  opening  of  5.7  square  feet  (0.530  m  ). 
The  minimum  net  clear  opening  height  shall  be 
22  inches  (559  mm).  The  minimum  net  clear 
opening  width  shall  be  20  inches  (508  mm). 

Exception: 

1 .    Grade  floor  windows  may  have  a  minimum 

net  clear  opening  of  five  square  feet  (320 

mnT). 

2       Windows  in  sleeping  rooms  of  existing 

dwellings    which    do    not    conform    to    the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


477 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


requirements  of  780  CMR  3603. 10.4. 1  may  be 
replaced  without  conforming  to  780  CMR 
3603.10.4.1,  provided  that  the  replacement 
windows  do  not  significantly  reduce  the 
existing  opening  size  and  further  providing  that 
the  minimum  opening  size  is  3  7  square  feet. 

3603.10.4.2  Bars,  grills  and  screens:  Bars,  grills, 
screens  or  other  obstructions  placed  over 
emergency  escape  windows  shall  be  releasable  or 
removable  from  the  inside  without  the  use  of  a 
key  or  tool. 

3603.10.5     Exirway     under     stair     protection 

Enclosed  accessible  space  under  stairs  shall  have 
walls  and  soffits  protected  on  the  enclosed  side  with 
''2-inch  (12.7  mm)  gypsum  board 

780  CMR  3603.11  DOORS  AND  HALLWAYS 

3603.11.1  Exit  doors:  The  minimum  nominal  width 
of  at  least  one  of  the  exit  doors  required  by 
780  CMR  3603.10.1  shall  be  36  inches  and  the 
minimum  nominal  height  shall  be  six  feet  eight 
inches.  All  other  exit  doors  and  doors  leading  to  or 
from  enclosed  stairways,  shall  not  be  less  than  32 
inches  in  nominal  width  nor  six  feet  eight  inches  in 
nominal  height. 

3603.11.2  Interior  Doors:  All  doors  providing 
access  to  habitable  rooms  shall  have  a  minimum 
nominal  width  of  30  inches  and  a  minimum  nominal 
height  of  six  feet  six  inches 

Exception:  Doors  providing  access  to  bathrooms 
are  permitted  to  be  28  inches  in  nominal  width 

780  CMR  3603.12  LANDINGS 
3603.12.1  General:  A  minimum  of  three  foot  by 
three  foot  (914  mm  by  914  mm)  landing  or  open 
floor  area  shall  be  provided  at  the  interior  side  of  all 
exit  doors  A  minimum  four  foot  by  four  foot 
landing  shall  be  provided  on  the  exterior  side  of  all 
exit  doors.  The  floor  area  or  landing  shall  not  be 
more  than  1  Vi  inches  (3  8  mm)  lower  than  the  top  of 
the  threshold  on  the  interior  side,  nor  more  than  8% 
inches  lower  than  the  threshold  on  the  exterior  side 

Exceptions. 

1 .  At  the  top  of  a  flight  of  interior  stairs,  on  the 
stairway  side,  provided  the  door  does  not  swing 
over  the  stairs. 

2.  Exterior  storm  and  screen  doors  are  exempt 
from  the  requirements  for  landings. 

780  CMR  3603.13  STAIRWAYS 
3603.13.1  Width:  Stairways  shall  not  be  less  than 
36  inches  (914  mm)  in  clear  width  at  all  points 
above  the  permitted  handrail  height  and  below  the 
required  headroom  height.  The  minimum  width  at 
and  below  the  handrail  height  shall  not  be  less  than 


32  inches  (813  mm)  where  a  handrail  is  installed  on 
one  side  and  28  inches  (711  mm)  where  handrails 
are  provided  on  both  sides. 

3603.13.2  Treads  and  risers:  The  maximum  riser 
height  shall  be  8%  inches  (210  mm)  and  the 
minimum  tread  depth  shall  be  nine  inches  (229  mm) 
The  riser  height  shall  be  measured  vertically 
between  leading  edges  of  the  adjacent  treads  The 
tread  depth  shall  be  measured  horizontally  between 
the  vertical  planes  of  the  foremost  projection  of 
adjacent  treads  and  at  a  right  angle  to  the  tread's 
leading  edge.  The  walking  surface  of  treads  and 
landings  of  a  stairway  shall  be  sloped  no  steeper 
than  one  unit  vertical  in  48  units  horizontal  (2% 
slope).  The  greatest  riser  height  within  any  flight  of 
stairs  shall  not  exceed  the  smallest  by  more  than  % 
inch  (9  5  mm)  and  any  two  successive  risers  shall 
not  deviate  by  more  than  /,6-inch  in  height  The 
greatest  tread  depth  within  any  flight  of  stairs  shall 
not  exceed  the  smallest  by  more  than  3/s  inch  (9.5 
mm)  and  any  two  successive  treads  shall  not  deviate 
in  depth  by  more  than   /16-inch 

3603.13.2.1  Nosing  Profile  The  radius  of 
curvature  at  the  leading  edge  of  the  tread  shall  be 
no  greater  than  /!6  inch  (14.3  mm).  A  nosing  not 
less  than  %  inch  (19  mm)  but  not  more  than  1  'A 
inches  (32  mm)  shall  be  provided  on  stairways 
with  solid  risers.  Beveling  of  nosing  shall  not 
exceed  XA  inch  (12  7  mm).  Risers  shall  be  vertical 
or  sloped  from  the  underside  of  the  leading  edge 
of  the  tread  above  at  an  angle  not  more  than  30 
degrees  from  the  vertical 

Exception  1:    A  nosing  is  not  required  where 

the  tread  depth  is  a  minimum  of  1 1  inches  (279 

mm). 

Exception    2:     Stairways    that    are    legally 

mandated    for  persons  with  disabilities  shall 

conform  to  the  requirements  of  521  CMR  as 

listed  in  Appendix  A 

3603.13.3  Headroom:  The  minimum  headroom  in 
all  parts  of  the  stairway  shall  not  be  less  than  six  feet 
eight  inches  (2032  mm)  measured  vertically  from 
the  sloped  plane  adjoining  the  tread  nosing  or  from 
the  floor  surface  of  the  landing  or  platform 

3603.13.4  Winders:  Winders  are  permitted, 
provided  that  the  width  of  the  tread  at  a  point  not 
more  than  12  inches  (305  mm)  from  the  side  where 
the  treads  are  narrower  is  not  less  than  ten  inches 
(254  mm)  and  the  minimum  width  of  any  tread  is  not 
less  than  six  inches  (153  mm).  The  continuous 
handrail  required  by  780  CMR  3603.14.1  shall  be 
located  on  the  side  where  the  tread  is  narrower 

3603.13.5  Spiral  stairs:  Spiral  stairways  are 
permitted,  provided  the  minimum  width  shall  be  26 
inches  (660  mm)  with  each  tread  having  a  VA-iach 


478 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


(190  mm)  minimum  tread  width  at  12  inches  (305 
mm)  from  the  narrow  edge.  All  treads  shall  be 
identical,  and  the  rise  shall  be  no  more  than  9!/2 
inches  (241  mm).  A  minimum  headroom  of  six  feet 
six  inches  (1982  mm)  shall  be  provided. 

3603.13.6  Circular  stairways:  Circular  stairways 
shall  have  a  minimum  tread  depth  and  a  maximum 
riser  height  in  accordance  with  780  CMR  3603. 13.2 
and  the  smaller  radius  shall  not  be  less  than  twice 
the  width  of  the  stairway  The  minimum  tread  depth 
of  ten  inches  (254  mm)  shall  be  measured  from  the 
narrower  end. 

3603.13.7  Illumination  All  stairways  shall  be 
provided  with  artificial  illumination  in  accordance 
with  780  CMR  3603.6.1  (exception  2). 

780  CMR  3603.14  HANDRAILS  AND 
GUARDRAILS 

3603.14.1  Handrails 

3603.14.1.1  Handrails:  Handrails  having 
minimum  and  maximum  heights  of  30  inches  and 
38  inches  (762  mm  and  965  mm),  respectively, 
measured  vertically  from  the  nosing  of  the  treads, 
shall  be  provided  on  at  least  one  side  of  stairways 
of  three  or  more  risers.  Spiral  stairways  shall  have 
the  required  handrail  located  on  the  outside 
radius.  All  required  handrails  shall  be  continuous 
the  full  length  of  the  stairs.  Ends  shall  be  returned 
or  shall  terminate  in  newel  posts  or  safety 
terminals.  Handrails  adjacent  to  a  wall  shall  have 
a  space  of  not  less  than  l'/2  inches  (38  mm) 
between  the  wall  and  the  handrail. 

Exceptions: 

1.         Handrails   shall   be   permitted   to   be 

interrupted  by  a  newel  post  at  a  turn. 

2       The  use  of  a  volute,  turnout  or  starting 

easing  shall  be  allowed  over  the  lowest  tread 

3603.14.1.2  Handrail  grip  size:  Handrails  shall 
have  either  a  circular  cross  section  with  a 
diameter  of  I  Va  inches  (32  mm)  to  two  inches  (5 1 
mm),  or  a  non-circular  cross  section  with  a 
perimeter  dimension  of  at  least  four  inches  (102 
mm)  but  not  more  than  6/4  inches  (159  mm)  and 
a  largest  cross-section  dimension  not  exceeding 
2%  inches  (28.6  mm).  Edges  shall  have  a 
minimum  radius  of  Ve  inch  (3.2  mm). 

3603.14.2  Guardrails 

3603.14.2.1  Guardrail  details:  Porches, 
balconies,  decks  or  raised  floor  surfaces  located 
more  than  30  inches  (762  mm)  above  the  floor  or 
grade  below  shall  have  guardrails  not  less  than  36 
inches  (914  mm)  in  height.  Open  sides  of  stairs 
with  a  total  rise  of  more  than  30  inches  (762  mm) 
above  the  floor  or  grade  below  shall  have 
guardrails,  which  may  also  serve  as  handrails,  not 


less  than  34  inches  (864  mm)  in  height  measured 
vertically  from  the  nosing  of  the  treads 

3603.14.2.2    Guardrail    opening    limitations: 

Required  guardrails  on  open  sides  of  stairways, 
balconies,  porches,  decks  and  raised  floor  areas. 
shall  have  intermediate  rails,  balusters  or 
ornamental  closures  which  prevent  the  passage  of 
an  object  four  inches  (102  mm)  or  more  in 
diameter. 

Exception:  Triangular  spaces  formed  by  the 
riser,  tread  and  bottom  rail  of  a  guard  at  the 
open  side  of  a  stairway  may  be  of  sized  to 
prevent  the  passage  of  a  sphere  six  inches  (153 
mm)in  diameter. 

780  CMR  3603.15  RAMPS 

3603.15.1  Maximum  slope  All  egress  ramps  shall 
have  a  maximum  slope  of  one  unit  vertical  in  eight 
units  horizontal  (12.5%  slope). 

Exception  1:  The  maximum  slope  of  ramps  for 
persons  with  disabilities  shall  be  one  unit  vertical 
in  12  units  horizontal. 

Exception  2:  Where  access  for  persons  with 
disabilities  is  legally  mandated,  ramps  shall  be 
constructed  in  accordance  with  the  requirements 
of  521  CMR  as  listed  in  Appendix  A. 

3603.15.2  Guardrails  and  handrails:  Guardrails 
shall  be  provided  on  both  sides  of  all  ramps  and  shall 
be  constructed  in  accordance  with  780  CMR 
3603.14.2.  Handrails  conforming  to  780  CMR 
3603  14. 1  shall  be  provided  on  at  least  one  side  of 
all  ramps  exceeding  a  siope  of  one  unit  vertical  in  12 
units  horizontal  (8%  slope). 

Exception  1:  For  persons  with  disabilities, 
handrails  shall  be  provided  on  both  sides  of  the 
ramp  when  the  vertical  rise  between  landings 
exceeds  six  inches. 

Exception  2:  Where  access  for  persons  with 
disabilities  is  required  by  statute,  ordinance  or 
bylaw,  guardrails  and  handrails  shall  be  provided 
in  accordance  with  the  requirements  of  521  CMR 
as  listed  in  Appendix  A. 

3603.15.3  Landing  required:  A  minimum  three- 
foot-by-three-foot  (914  mm  by  914  mm)  level 
landing  shall  be  provided  at  the  top  and  bottom  of 
ramps  where  doors  open  onto  the  ramp  and  where 
the  ramp  changes  direction 

Exception  1:  Ramps  required  for  persons  with 
disabilities  shall  not  have  a  vertical  rise  greater 
than  30  inches  between  landings. 
Exception  2:  Where  access  for  persons  with 
disabilities  is  legally  mandated,  landing 
requirements  shall  conform  to  the  requirements  of 
521  CMR  as  listed  in  Appendix  A. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


479 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  3603.16  FIRE  PROTECTION 
SYSTEMS 

3603.16.1  General:  All  one  and  two  family 
dwellings  hereafter  constructed  shall  be  equipped 
with  a  household  fire  warning  system,  in  accordance 
with  the  provisions  of  780  CMR  3603.16.  All 
devices  shall  be  installed  and  maintained  in 
accordance  with  the  requirements  of  780  CMR 
3603.16,  manufacturers  instructions  and  listing 
criteria  and  otherwise  shall  be  installed  and 
maintained  in  accordance  with  Chapter  2  of  NFPA 
72  and  527  CMR  12.00  as  listed  \n  Appendix  A. 

Exception:  In  addition  to  the  requirements  of 
780  CMR  3603.16.1,  two  family  dwellings  that 
contain  common  areas  such  as  basements, 
hallways  and/or  interior  stairways  that  serve  both 
dwelling  units,  but  are  not  within  the  dwelling 
units  shall  be  provided  with  multiple  station 
smoke  detectors  or  a  listed  control  unit  with 
automatic  smoke  detectors  and  occupant 
notification  appliances  in  the  following  locations. 

1 .  In  all  common  basements. 

2.  In  all  common  hallways. 

3.  In  all  common  stairways  on  each  level  out- 
side the  dwelling  unit  doorways. 

Each  detection  device  shall  cause  the  operation  of 
an  alarm  that  is  clearly  audible  in  all  bedrooms 
over  background  noise  levels  with  all  intervening 
doors  closed.  Such  devices  shall  be  installed  in 
accordance  with  NFPA  72  and  527  CMR  12.00  as 
listed  in  Appendix  A. 

3603.16.2  Compatibility:  All  devices  and/or 
combination  of  devices  and  equipment  shall  be 
approved  and  listed  for  the  purposes  for  which  such 
devices  are  to  be  utilized. 

3603.16.3  Smoke  detectors:  All  detached  one-  and 
two  family  buildings,  including  manufactured  homes 
in  accordance  with  780  CMR  35,  shall  contain 
listed  single  and  multiple  station  smoke  detectors  or 
other  household  fire  warning  systems  in  compliance 
with  ANSI/UL  217  and/or  ANSI/UL  268  (listed  in 
Appendix  A)  and  conforming  to  780  CMR  3603 .  16; 
such  household  fire  warning  systems  shall  be 
installed  and  maintained  in  accordance  with  the 
requirements  of  780  CMR  3603.16,  manufacturers 
instructions  and  listing  criteria  and  otherwise  shall 
be  installed  and  maintained  in  accordance  with 
Chapter  2  of  NFPA  72  and  527  CMR  12.00  as  listed 
in  Appendix  A. 

3603.16.4  Heat  detectors:  (Reserved). 

3603.16.5  Primary  electrical  power  for  single 
station  and  multiple  station  smoke  detectors: 

Power  for  single  and  multiple  station  smoke 
detectors  shall  be  supplied  from  a  permanently  wired 
connection  directly  to  an  AC  primary  source  of 
power.  All  power  for  AC  powered  smoke  detectors 


shall  be  taken  from  a  single  branch  circuit  which 
also  provides  other  electrical  service  to  habitable, 
occupiable  spaces.  The  power  source  shall  be  on  the 
supply  side,  ahead  of  any  switches. 

3603.16.6  Primary  electrical  power  for  other 
household  fire  warning  systems:  Low  voltage 
household  fire  warning  systems  that  include  a  listed 
control  unit  with  automatic  detectors  and  occupant 
notification  appliances  shall  be  powered  from  a 
permanently  wired  AC  primary  power  source.  Such 
AC  primary  power  shall  be  supplied  either  from  a 
dedicated  branch  circuit  or  the  unswitched  portion  of 
a  branch  circuit  also  used  for  power  and  lighting  of 
habitable,  occupiable  spaces,  in  accordance  with  the 
requirements  of  NFPA  72  and  527  CMR  12.00  as 
listed  in  Appendix  A. 

3603.16.7  Secondary  electrical  power:  In  addition 
to  required  primary  power  as  discussed  in  780  CMR 
3603.16.5  and  780  CMR  3603.16.6,  all  household 
fire  warning  systems  shall  have  secondary  (standby) 
power  supplied  from  monitored  batteries  in 
accordance  with  the  household  fire  warning 
equipment  requirements  of  NFPA-72  as  listed  in 
Appendix  A. 

3603.16.8  Required  alarm  notification  appliances: 

Where  more  than  one  smoke  or  heat  detector  is 
required  by  780  CMR  3603.16.10,  all  required 
detectors  shall  be  installed  so  that  the  activation  of 
any  detector  shall  cause  the  alarm  in  all  required 
smoke  detectors  in  the  dwelling  unit  to  sound. 

Detector  activation  in  a  dwelling  unit  shall  not 
activate  signals  in  any  other  dwelling  unit  or 
common  areas. 

3603.16.8.1  Non-required  alarm  notification 
appliances:  Non-required  smoke  or  heat  detectors 
shall  be  installed  so  that  the  actuation  of  any  non- 
required  detector  shall  cause  the  alarm  in  all 
required  and  non-required  detectors  in  the 
dwelling  unit  to  sound.  Detector  activation  in  a 
dwelling  unit  shall  not  activate  signals  in  any 
other  dwelling  unit  or  common  areas. 

3603.16.9  Alarm  signaling  intensity:  All  required 
alarm-sounding  appliances  shall  have  a  minimum 
rating  of  85  dB  A  at  ten  feet  in  accordance  with  the 
requirements  of  NFPA  72. 

Exception:  Sounding  appliances  directly  located 
in  bedrooms  shall  have  a  sound  pressure  level  as 
low  as  75  dBA  at  ten  feet  in  accordance  with  the 
requirements  of  NFPA  72. 

3603.16.10  Required  smoke  detector/heat 
detector  locations:  Smoke  detectors  shall  be 
installed  in  the  following  locations: 

1 .  In  the  immediate  vicinity  of  bedrooms; 

2.  In  all  bedrooms; 


480 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


3.  In  each  story  of  a  dwelling  unit,  including 
basements  and  cellars,  but  not  including  crawl 
spaces  and  uninhabitable  attics; 

4.  In  residential  units  of  1200  square  feet  or 
more,  automatic  fire  detectors,  in  the  form  of 
smoke  detectors  shall  be  provided  for  each  1200 
square  feet  of  area  or  part  thereof; 

5.  Fixed  temperature  heat  detectors  shall  be 
installed  in  accordance  with  the  requirements  of 
780  CMR  3603.16.4. 

Exceptions: 

1.  In  dwelling  units  with  one  or  more  split 
levels,  (i.e.,  adjacent  levels  with  less  than  one 
full  story  separation  between  levels)  a  smoke 
detector  installed  on  the  upper  level  shall 
suffice  for  the  adjacent  lower  level  unless 
there  is  an  intervening  door  between  one  level 
and  the  adjacent  lower  level  in  which  case 
smoke  detectors  shall  be  installed  on  both 
levels. 

2.  In  buildings  equipped  throughout  with  an 
automatic  sprinkler  system,  smoke  detectors 
are  not  required  in  bedrooms. 

3603.16.11  Photo  electric  smoke  detector 
requirements:  Any  smoke  detector  located  within 
20  feet  of  a  kitchen  or  within  20  feet  of  a  bathroom 
containing  a  tub  or  shower  shall  be  a  photo  electric 
type  smoke  detector  but  shall  satisfy  the 
compatibility  requirements  of  780  CMR  3603.16.2. 

3603.16.12  Maintenance  and  testing:  It  shall  be  the 
responsibility  of  the  owner  to  properly  maintain  the 
household  fire  warning  system  in  accordance  with 
the  requirements  of  NFPA  72  as  listed  in 
Appendix  A. 

3603.16.13  Additions,  alterations  and  repairs: 

When  one  or  more  sleeping  rooms  are  added  or 
created  in  existing  dwellings,  the  entire  building 
shall  be  provided  with  smoke  detectors  designed  and 
located  as  required  for  new  dwellings. 

For  other  alterations  or  repairs  that  would  require 
a  fire  protection  system  in  an  existing  building  be 
upgraded,  refer  to  780  CMR  3404  and/or  780  CMR 
3405,  as  applicable. 

780  CMR  3603.17  FOAM  PLASTIC 
3603.17.1  General:    The  provisions  of  this  section 
shall  govern  the  requirements  and  uses  of  foam 
plastic  insulation. 

3603.17.1.1   Surface  burning  characteristics: 

Except  where  otherwise  noted  in  780  CMR 
3603.17.2,  all  foam  plastic  or  foam  plastic  cores 
in  manufactured  assemblies  used  in  building 
construction  shall  have  a  flame-spread  rating  of 
not  more  than  75  and  shall  have  a  smoke- 
developed  rating  of  not  more  than  450  when 
tested  in  the  maximum  thickness  intended  for  use 
in  accordance  with  ASTM  E  84. 


3603.17.1.2  Thermal  barrier:  Foam  plastic, 
except  where  otherwise  noted,  shall  be  separated 
from  the  interior  of  a  building  by  minimum  '/•>- 
inch  (12.7  mm)  gypsum  wallboard.  The  gypsum 
board  shall  be  installed  using  a  mechanical 
fastening  system  in  accordance  with  780  CMR 
3607.2.3.5.  Reliance  on  adhesives  to  ensure  the 
gypsum  wallboard  will  remain  in  place  when 
exposed  to  fire  shall  be  prohibited. 

3603.17.2  Specific  requirements:  The  following 
requirements  shall  apply  to  all  uses  of  foam  plastic 
unless  specifically  approved  in  accordance  with 
780  CMR  3603.17.3  or  by  other  sections  of 
780  CMR. 

3603.17.2.1  Masonry  or  concrete  construction: 

Foam  plastics  may  be  used  without  the  thermal 
barrier  described  in  780  CMR  3603.17.1.2  when 
the  foam  plastic  is  protected  by  a  minimum  one- 
inch  (25  mm)  thickness  of  masonry  or  concrete. 

3603.17.2.2  Roofing:  Foam  plastic  may  be  used 
in  a  roof-covering  assembly  without  the  thermal 
barrier  when  the  foam  is  separated  from  the 
interior  of  the  building  by  plywood  or  wood 
structural  panel  sheathing  in  accordance  with 
780  CMR  3608.3,  not  less  than  15/32  inch  (12  mm) 
in  thickness  bonded  with  exterior  glue  and 
identified  as  Exposure  1 ,  with  edge  supported  by 
blocking  or  tongue-and-groove  joints.  The  smoke- 
developed  rating  shall  not  be  limited. 

3603.17.2.3  Attics:  Within  an  attic  accessible  by 
means  of  a  fixed  stairway,  foam  plastics  shall  be 
protected  against  ignition  by  1  '/--inch-thick  (38 
mm)  mineral  fiber  insulation,  '/t-inch-thick  (6.4 
mm)  wood  structural  panels,  3/s-inch  (9.5  mm) 
particleboard,  '/4-inch  (6.4  mm)  hardboard,  or  %- 
inch  (9.5  mm)  gypsum  wallboard,  corrosion- 
resistant  steel  having  a  base  metal  thickness  of 
0.016  inch  (0.406  mm). 

3603.17.2.4  Foam-filled  doors:  Foam-filled 
doors  are  exempt  from  the  requirements  of 
780  CMR  3603.17. 

3603.17.2.5  Siding  backer  board:  Foam  plastic 
board  of  not  more  than  Vi-inch  (12.7  mm) 
thickness  may  be  used  as  siding  backer  board 
when  separated  from  interior  spaces  by  not  less 
than  two  inches  (51  mm)  of  mineral  fiber 
insulation  or  '/2-inch  (12.7  mm)  gypsum 
wallboard  or  installed  over  existing  exterior  wall 
finish  in  conjunction  with  re-siding,  providing  the 
plastic  board  does  not  have  a  potential  heat  of 
more  than  2,000  Btu  per  square  foot  (22  720 
kJ/nr)  when  tested  in  accordance  with  NFiPA 
259. 

3603.17.2.6  Interior  trim:  Foam  plastic  trim 
defined  as  picture  molds,  chair  rails,  baseboards, 


2/7/97    (Effestive  2/28/97) 


780  CMR  -  Sixth  Edition 


481 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


handrails,  ceiling  beams,  door  trim  and  window 
trim  may  be  installed,  provided: 

1.  The  minimum  density  is  20  pounds  per 
cubic  foot  (3.14  kN/m3); 

2.  The  maximum  thickness  of  the  trim  is  Vi 
inch  (12.7  mm)  and  the  maximum  width  is  four 
inches  (102  mm); 

3.  The  trim  constitutes  no  more  than  10%  of 
the  area  of  any  wall  or  ceiling,  and 

4.  The  flame-spread  rating  does  not  exceed  75 
when  tested  per  ASTM  E  84.  The  smoke- 
developed  rating  is  not  limited. 

3603.17.3  Specific  approval:  Plastic  foam  not 
meeting  the  requirements  of  780  CMR  3603.17.1 
and  3603.17.2  may  be  specifically  approved  on  the 
basis  of  approved  tests  such  as,  but  not  limited  to,  a 
tunnel  test  in  accordance  with  ASTM  E  84,  FM 
4880,  UL  1040,  ASTM  E  152,  or  UL  1715,  or  fire 
tests  related  to  actual  end-use  configurations.  The 
specific  approval  may  be  based  on  the  end  use, 
quantity,  location  and  similar  considerations  where 
such  tests  would  not  be  applicable  or  practical. 

3603.17.4  Interior  finish:  Foam  plastics  which  are 
used  as  interior  finish  shall  also  meet  the  flame- 
spread  requirements  for  interior  finish. 

780  CMR  3603.18  INTERIOR  FINISH 

REQUIREMENTS/FLAME  SPREAD  AND 

SMOKE  DEVELOPED 

3603.18.1  Wall  and  ceiling:  Wall  and  ceiling 
finishes  shall  have  a  flame-spread  classification  of 
not  greater  than  200. 

Exception:  Flame-spread  requirements  for 
finishes  shall  not  apply  to  trim  defined  as  picture 
molds,  chair  rails,  baseboards  and  handrails;  to 
doors  and  windows  or  their  frames;  or  to  materials 
which  are  less  than  V28  inch  (0.907  mm)  in 
thickness  cemented  to  the  surface  of  walls  or 
ceilings  if  these  materials  have  a  flame-spread 
characteristic  no  greater  than  paper  of  this 
thickness  cemented  to  a  noncombustible  backing. 

3603.18.2  Smoke  density:  The  smoke  density  shall 
not  be  greater  than  450. 

3603.18.3  Testing.  Tests  shall  be  made  in 
accordance  with  ASTM  E  84. 

780  CMR  3603.19  INSULATION/FLAME 

SPREAD,  SMOKE  DEVELOPED/CRITICAL 

RADIANT  FLUX 

3603.19.1  Insulation:  All  exposed  insulation 
materials,  including  facings,  such  as  vapor  barriers 
or  breather  papers  installed  within  floor-ceiling 
assemblies,  roof-ceiling  assemblies,  wall  assemblies, 
crawl  spaces  and  attics  shall  have  a  flame-spread 
rating  not  to  exceed  25  with  an  accompanying 


smoke  developed  factor  not  to  exceed  450  when 
tested  in  accordance  with  ASTM  E  84. 

Exception:  When  such  materials  are  installed  in 
concealed  spaces,  the  flame-spread  and  smoke- 
development  limitations  do  not  apply  to  the 
facings,  provided  that  the  facing  is  installed  in 
substantial  contact  with  the  unexposed  surface  of 
the  ceiling,  floor  or  wall  finish. 

3603.19.2  Loose-fill  insulation:  Loose-fill 
insulation-materials  which  cannot  be  mounted  in  the 
ASTM  E  84  apparatus  without  a  screen  or  artificial 
supports  shall  have  a  flame-spread  rating  not  to 
exceed  25  with  an  accompanying  smoke-developed 
factor  not  to  exceed  450  when  tested  in  accordance 
withCAN4-S102.2-M83. 

3603.19.3  Exposed  attic  insulation:  All  exposed 
insulation  materials  installed  on  attic  floors  shall 
have  a  critical  radiant  flux  not  less  than  0. 12  watt  per 
square  centimeter. 

3603.19.4  Testing:  Tests  for  critical  radiant  flux 
shall  be  made  in  accordance  with  ASTM  E  970. 

780  CMR  3603  20  GLAZING 

3603.20.1  Scope:  The  provisions  of  780  CMR 
3603.20  and  780  CMR  24  shall  govern  the  materials, 
design,  construction  and  quality  of  glass  and  glazing 
in  vertical  and  sloped  applications.  For  the  definition 
of  approved  light-transmitting  plastic,  see  780  CMR 
2604. 1 .  Safety  glazing  materials  shall  conform  to 
the  requirements  ofM.G.L.  c  143,  §§  3T,  3  V,  and 
3V,  and  CPSC 16  CFR;  1201,  as  applicable 

3603.20.2  Marking:  Each  light  shall  bear  the 
manufacturer's  mark  designating  the  type  and 
thickness  of  glass.  Labels  may  be  omitted  from  other 
than  safety  glazing  materials  unless  specifically 
required  by  the  building  official.  Safety  glazing  shall 
be  marked  in  accordance  with  780  CMR  3603.20.1 
and  shall  conform  to  the  requirements  ofM.G.L. 
c.  143,  §§3T,  3U,  and3V.  The  mark  shall  not  be 
omitted  from  tempered  glass.  Each  unit  of  tempered 
glass  shall  be  permanently  identified  by  the 
manufacturer's  mark.  The  identifying  mark  shall  be 
etched  or  ceramic  fired  on  the  glass  and  shall  be 
visible  when  the  unit  is  glazed. 

3603.20.2.1  Identification:  To  qualify  as  glass 
with  special  performance  characteristics,  each  unit 
of  laminated,  heat-strengthened,  tempered  glass 
shall  be  permanently  identified  by  the 
manufacturer.  The  identification  of  tempered 
glass  shall  be  etched  or  ceramic  fired  on  the  glass 
and  be  visible  when  the  unit  is  glazed.  Heat- 
strengthened  and  tempered  spandrel  glasses  are 
exempted  from  permanent  labeling.  This  type  of 
glass  shall  be  labeled  with  a  removable  paper 
label  by  the  manufacturer. 


482 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


3603.20.3  Louvered     windows     or    jalousies: 

Regular,  float,  wired  or  patterned  glass  in  jalousies 
and  louvered  windows  shall  be  no  thinner  than 
nominal  3/16  inch  (4.76  mm)  and  no  longer  than  48 
inches  (1219  mm).  Exposed  glass  edges  shall  be 
smooth.  Wired  glass  with  wire  exposed  on 
longitudinal  edges  shall  not  be  used  in  jalousies  or 
louvered  windows. 

3603.20.4  Safety  glazing: 

3603.20.4.1  Human  impact  loads:  Individual 
glazed  areas,  including  glass  mirrors,  in  hazardous 
locations  such  as  those  indicated  in  780  CMR 
2405.2  shall  pass  the  test  requirements  of  CPSC 
16  CFR,  1201  and  shall  conform  to  the 
requirements  of  M.G.L.  c.  143,  §§  3T,  3U  and 
3V,  as  applicable,  listed  in  Appendix  A.  The 
requirements  of  this  section  and  780  CMR  2405.2 
and  2407.0  shall  apply  equally  to  replacement 
glass  and  new  glass  installation.  Additional 
requirements  as  specified  in  780  CMR  2407.2  are 
to  be  satisfied  for  glass  used  in  locations  where 
the  hazard  is  of  a  continuous  nature,  such  as  glass 
enclosures  for  sporting  activities  as  identified  in 
780  CMR. 
Exceptions: 

1.  Polished  wired  glass  used  in  required  fire 
resistance  rated  assemblies  or  polished  wire 
glass  used  in  hazardous  locations  such  as 
those  indicated  in  780  CMR  3603.20.4.2, 
items  6,7,8  and  9  shall  comply  with  ANSI 
Z97. 1 ,  listed  in  Appendix  A. 

2.  Plastic  glazing  shall  meet  the  weathering 
requirements  of  ANSI  Z97.1  listed  in 
Appendix  A. 

3.  Glass-block  walls  shall  comply  with 
780  CMR  2115.0. 

3603.20.4.1.1  Identification:  Each  light  of 
safety  glazing  material  installed  in  hazardous 
locations  as  defined  in  780  CMR  3603.20.4.2 
shall  bear  a  permanent  identifying  mark  issued 
by  an  approved  agency  which  specifies  the 
marking  agency,  whether  manufacturer  or 
installer,  and  the  test  standard. 
Exceptions: 

1.  Polished  wire  glass  is  exempt  from  a 
permanent  identifying  mark  provided  that 
the  distributor  or  the  installer  provides  an 
affidavit  certifying  that  the  polished  wire 
glass  complies  with  ANSI  Z9  7. 1  listed  in 
Appendix  A. 

2.  Laminated  glass  is  exempt  from  a 
permanent  identifying  mark  provided  that 
the  distributor  or  installer  provides  an 
affidavit  certifying  that  the  laminated  glass 
complies  with  CPSC  16  CFR  1201,  listed  in 
Appendix  A. 

3603.20.4.2    Specific    hazardous   locations: 

The   following   shall   be   considered   specific 


hazardous    locations    for    the    purposes    of 
glazing: 

1 .  Glazing  in  ingress  and  means  of  egress 
doors  except  jalousies  (see  780  CMR 
2402.5). 

2.  Glazing  in  fixed  and  sliding  panels  of 
sliding  (patio)  door  assemblies  and  panels  in 
swinging  doors. 

3.  Glazing  in  storm  doors. 

4.  Glazing  in  all  untrained  swinging  doors. 

5.  Glazing  in  doors  and  enclosures  for  hot 
tubs,  whirlpools,  saunas,  steam  rooms, 
bathtubs  and  showers.  Glazing  in  any 
portion  of  a  building  wall  enclosing  these 
compartments  where  the  bottom  exposed 
edge  of  the  glazing  is  less  than  60  inches 
(1525  mm)  above  a  standing  surface. 

6.  Glazing  in  an  individual  fixed  or 
operable  panel  adjacent  to  a  door  where  the 
nearest  exposed  edge  of  the  glazing  is  within 
a  24-inch  (610  mm)  arc  of  either  vertical 
edge  of  the  door  in  a  closed  position  and 
where  the  bottom  exposed  edge  of  the 
glazing  is  less  than  60  inches  (1525  mm) 
above  the  walking  surface. 

7.  Glazing  in  an  individual  fixed  or 
operable  panel,  other  than  in  those  locations 
described  in  780  CMR  3603.20.4.2  items  5. 
and  6.,  which  meets  all  of  the  following 
conditions: 

a.  Exposed  area  of  an  individual  pane 
greater  than  nine  square  feet  (0.84  m"); 

b.  Exposed  bottom  edge  less  than  18 
inches  (460  mm)  above  the  floor: 

c.  Exposed  top  edge  greater  than  36 
inches  (915  mm)  above  the  floor;  and 

d.  One  or  more  walking  surface(s)  within 
36  inches  (915  mm)  horizontally  of  the 
plane  of  the  glazing. 

8.  All  glazing  in  guards  and  railings 
regardless  of  area  or  height  above  a  walking 
surface.  Included  are  structural  baluster 
panels  and  nonstructural  in-fill  panels. 

9.  Glazing  in  walls  and  fences  enclosing 
indoor  and  outdoor  swimming  pools  where 
the  bottom  edge  of  the  glazing  on  the  pool 
side  is  less  than  60  inches  (1525  mm)  above 
a  walking  surface  and  within  36  inches  (914 
mm)  horizontally  of  a  walking  surface.  This 
shall  apply  to  single  glazing  and  all  panes  in 
multiple  glazing. 

Exception:  The  following  products, 
materials  and  uses  shall  not  be  considered 
specific  hazardous  locations: 

1.  Glazed  openings  in  doors  through 
which  a  three-inch  (76  mm)  sphere  is 
unable  to  pass. 

2.  Assemblies  of  leaded  glass  or  faceted 
glass  and  items  of  carved  glass  used  for 
decorative  purposes  in  locations  described 
in  780  CMR  3603  20  4.2,  items  1 .,  6.  or  7. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


48  j 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3.  Glazing  as  described  in  780  CMR 
3603.20.4.2,  item  6.,  where  there  is  an 
intervening  wall  or  some  other  permanent 
barrier  that  will  prevent  a  person 
approaching  the  door  from  accidentally 
striking  the  glazing. 

4.  Glazing  as  described  in  780  CMR 
3603.20.4.2,  item  7.,  where  a  protective 
bar  is  installed  34  inches  to  38  inches  (864 
mm  to  965  mm)  above  the  floor  on  the 
side  of  the  glazing  having  access  thereto. 
The  bar  shall  be  capable  of  withstanding  a 
horizontal  load  of  50  pounds  per  linear 
foot  (730  N/m)  without  contacting  the 
glass  and  be  a  minimum  of  1  Vz  inches  (38 
mm)  in  height.  The  protective  bar  may  be 
an  applied  bar  or  an  integral  part  of  the 
glazed  framing  dividing  an  upper  lite 
from  a  lower  lite. 

5.  Outboard  panes  in  insulating  glass 
units  and  other  multiple-glazed  panels  as 
described  in  780  CMR  3603.20.4.2,  item 
7.,  where  the  bottom  exposed  edge  of  the 
glass  is  25  feet  (7620  mm)  or  more  above 
any  grade,  roof,  walking  surface  or  other 
horizontal  or  sloped  (within  45  degrees  of 
horizontal)  surface  adjacent  to  the  glass 
exterior. 

6.  Louvered  windows  and  jalousies 
complying  with  the  requirements  of 
780  CMR  3603.20.3. 

7.  Glazing,  including  mirrors,  mounted 
or  hung  on  a  surface  that  provides  a 
continuous  backing  support. 

3603.20.5  Sloped  glazing  and  skylights 

3603.20.5.1  Sloped  glazing:  Any  installation  of 
glass  or  other  transparent,  translucent  or  opaque 
glazing  material  which  is  installed  at  a  slope  of  1 5 
degrees  (0.26  rad)  or  more  from  the  vertical  plane 
— including  skylights,  roofs  and  sloped 
walls— shall  comply  with  780  CMR  3603.20.5. 

3603.20.5.2  Allowable  glazing  materials:  Sloped 
glazing  shall  be  any  of  the  following  materials, 
subject  to  the  limitations  specified  in  780  CMR 

3603.20.5.3  and  the  exceptions  specified  in 
780  CMR  3603.20.5.4: 

1 .  For  monolithic  glazing  systems,  the  glazing 
material  of  the  single  light  or  layer  shall  be 
laminated  glass  with  a  minimum  30-mil  (762 
urn)  polyvinyl  butyral  interlayer,  wired  glass, 
approved  plastic  materials,  heat-strengthened 
glass  or  fully  tempered  glass. 

2.  For  multiple-layer  glazing  systems,  each 
light  or  layer  shall  consist  of  any  of  the  glazing 
materials  specified  in  780  CMR  3603.20.5.2, 
item  1. 

For  additional  requirements  for  plastic  skylights, 
see  780  CMR  2608.0. 


3603.20.5.3  Limitations:  Where  used  in 
monolithic  glazing  systems,  heat- strengthened 
glass  and  fully  tempered  glass  shall  have  screens 
installed  below  the  glazing  material,  subject  to  the 
exceptions  in  780  CMR  3603.20.5.4,  to  protect 
building  occupants  from  falling  glass  should 
breakage  occur.  The  screens  shall  be  capable  of 
supporting  the  weight  of  the  glass  and  shall  be 
substantially  supported  below  and  installed  within 
four  inches  (102  mm)  of  the  glass.  The  screens 
shall  be  constructed  of  a  noncombustible  material 
not  thinner  than  No.  12  B  &  S  Gage  (0.0808  inch) 
with  a  mesh  not  larger  than  one  inch  (25  mm  by 
25  mm).  In  a  corrosive  atmosphere,  structurally 
equivalent  non-corrosive  atmosphere,  structurally 
equivalent  non-corrosive  screening  materials  shall 
be  used.  Where  used  in  multiple-layer  glazing 
systems  as  the  bottom  glass  layer  over  the 
walking  surface,  heat-strengthened  glass,  fully 
tempered  glass  and  wired  glass  shall  be  equipped 
with  screening  that  conforms  to  the  requirements 
specified  for  monolithic  glazing  systems. 

3603.20.5.4  Exceptions:  In  monolithic  and 
multiple-layer  sloped  glazing  systems,  the 
following  exceptions  apply: 

1.  Fully  tempered  glass  installed  without 
protective  screens  where  glazed  between 
intervening  floors  at  a  slope  of  30  degrees 
(0.52  rad)  or  less  from  the  vertical  plane  shall 
have  the  highest  point  of  the  glass  one  feet 
(3048  mm)  or  less  above  the  walking  surface. 

2.  Screens  are  not  required  below  any  glazing 
material,  including  annealed  glass,  where  the 
walking  surface  below  the  glazing  material  is 
permanently  protected  from  the  risk  of  falling 
glass  or  the  area  below  the  glazing  material  is 
not  a  walking  surface. 

3.  Any  glazing  material,  including  annealed 
glass,  is  permitted  to  be  installed  without 
screens  in  the  sloped  glazing  systems  of 
detached  greenhouses,  provided  that  the  height 
of  the  greenhouse  at  the  ridge  does  not  exceed 
20  feet  (6096  mm)  above  grade.  Greenhouse 
frames  shall  be  noncombustible  if  the  height  of 
the  sloped  glazing  exceeds  20  feet  (6096  mm) 
above  grade. 

4.  Screens  shall  not  be  required  where  fully 
tempered  glass  or  laminated  glass  with  a  15 
mil  polyvinyl  butyral  interlayer  is  used  as 
single  glazing  or  as  both  panes  in  an  insulating 
glass  unit,  and  all  of  the  following  conditions 
are  met: 

a.  Each  pane  of  glass  is  16  square  feet  (1.5 
m  )  or  less  in  area; 

b.  The  highest  point  of  the  glass  is  12  feet 
(3658  mm)  or  less  above  any  walking 
surface  or  other  area  having  access  thereto; 
and 

c.  The  glass  thickness  is  3/,5  inch  (5  mm)  or 
less. 


484 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


3603.20.5.5    Curbs    for    skylights     All    unit 

skylights  installed  in  a  roof  with  a  pitch  flatter 
than  three  units  vertical  in  12  units  horizontal 
(25%  slope)  shall  be  mounted  on  a  curb  extending 
at  least  four  inches  (102  mm)  above  the  plane  of 
the  roof. 

780  CMR  360321  ENERGY  CONSERVATION 
REQUIREMENTS 

3603.21.1  General:  All  one  and  two  family 
detatched  buildings  shall  comply  with  the 
comprehensive  energy  requirements  set  forth  in 
780  CMR  Appendix  J. 

780  CMR  360322  PROTECTION  AGAINST 
DECAY  AND  TERMITES 

3603.22.1  Required  Protection:  Where  protection 
of  wood  members  is  required  by  780  CMR  3603.22. 
protection  shall  be  provided  against  decay  or  termite 
damage  by  the  use  of  naturally  durable  or 
preservative-treated  wood  as  required  by  780  CMR 
3603.22- 

3603.22.2  Naturally  durable  wood:  The  term 
"naturally  durable  wood"  refers  to  the  heartwood  of 
the  following  species  with  the  exception  that  an 
occasional  piece  with  corner  sapwood  is  permitted  if 
90%  or  more  of  the  width  of  each  side  on  which  it 
occurs  is  heartwood 

Decay  resistant:  Redwood,  cedar,  black  locust 

and  black  walnut. 

Termite  resistant:   Redwood  and  Eastern  red 

cedar 

3603.22.3  Preservative-treated  wood 

3603.22.3.1  Preservative-treated   wood:    The 

term  "preservative-treated  wood"  refers  to  wood 
(including  plywood)  '  pressure  treated  with 
preservatives,  that  conforms  to  retention, 
penetration  and  other  requirements  applicable  to 
the  species,  product,  treatment  and  conditions  of 
use  in  AWPA  CI,  C2,  C9,  CI 5,  CI 8,  C20,  C22, 
C23,  C24.  C27  and  C28  listed  in  Appendix  A. 
Preservatives  shall  conform  to  AWPA  P1/P13,  P2, 
P5,  P8  and  P9  listed  in  Appendix  A.  Lumber  and 
plywood  in  wood  foundation  systems  shall 
conform  to  780  CMR  1808.3 

3603.22.3.2  Identification:  All  piles,  poles, 
lumber  and  plywood  which  are  required  to  be 
preservative-treated  shall  bear  the  quality  mark  of 
an  approved  agency  that  maintains  continuing 
supervision,  testing  and  inspection  over  the 
quality  of  the  product  Quality-control  inspection 
agencies  for  preservative-treated  wood  shall  be 
certified  as  to  competency  and  performance  by  an 
approved  organization.  Said  mark  shall  include 
the  following  information  in  a  legible  format: 
identification    of  the    inspection    agency;    the 


standard  to  which  the  product  is  treated;  the 
identification  of  the  treating  plant;  and  the 
purpose  for  which  the  product  has  been  treated 
The  mark  shall  be  permanently  affixed  to  each 
piece  unless  specifically  waived  by  the  building 
official 

3603.22.3.3  Moisture  content:  Where  wood  that 
is  pressure  treated  with  a  water-borne 
preservative  is  used  in  enclosed  locations  where 
drying  in  service  cannot  readily  occur,  such  wood 
shall  be  at  a  moisture  content  of  19%  or  less 
before  being  covered  with  insulation,  interior  wall 
finish,  floor  covering  or  other  material. 

3603.22.3.4  Fasteners  Fasteners  for 
preservative-treated  wood  shall  be  of  hot-dipped, 
zinc-coated,  galvanized  stainless  steel,  silicon 
bronze,  copper  or  other  corrosion-resistant 
materials.  Fasteners  for  wood  foundations  shall 
be  as  required  in  AFPA  TR7  listed  in 
Appendix  A 

3603.22.4  Wood  used  above  ground:  Wood 
installed  above  ground  in  the  locations  specified  in 
780  CMR  3603.22.4.  1  through  3603  22.4  6  shall  be 
naturally  durable  wood  or  preservative-treated  wood 
treated  by  water-bome  preservatives,  and  shall  be 
treated  in  accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  above-ground  use. 

3603.22.4.1  Joists  and  girders:  Where  wood 
joists  or  the  bottom  of  a  wood  structural  floor 
without  joists  are  closer  than  18  inches  (457  mm), 
or  wood  girders  are  closer  than  12  inches  (305 
mm),  to  the  exposed  ground  in  crawl  spaces  or 
unexcavated  areas  located  within  the  perimeter  of 
the  building  foundation,  the  floor  assembly 
(including  posts,  girders,  joists  and  subfloor)  shall 
be  of  approved  naturally  durable  or  preservative- 
treated  wood 

3603.22.4.2  Framing:  All  wood  framing 
members,  including  wood  sheathing,  which  rest 
on  exterior  foundation  walls  and  are  less  than 
eight  inches  (203  mm)  from  exposed  earth  shall 
be  of  approved  naturally  durable  or  preservative- 
treated  wood 

3603.22.4.3  Sleepers  and  sills:  Sleepers  and  sills 
on  a  concrete  or  masonry  slab  which  is  in  direct 
contact  with  earth  shall  be  of  approved  naturally 
durable  or  preservative-treated  wood. 

3603.22.4.4  Girder  ends:  The  ends  of  wood 
girders  entering  exterior  masonry  or  concrete 
walls  shall  be  provided  with  a  '/4-inch  ( 1 3  mm)  air 
space  on  top,  sides  and  end,  unless  approved 
naturally  durable  or  preservative-treated  wood  is 
used. 

3603.22.4.5  Clearance:  Clearance  between  wood 
siding  and  earth  on  the  exterior  of  a  building  shall 
not  be  less  than  six  inches  (1 52  mm)  except  where 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


485 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


siding,  sheathing  and  wall  framing  are  of 
approved  preservative-treated  wood. 

3603.22.4.6  Posts  or  columns:  Posts  or  columns 
supporting  permanent  structures  and  supported  by 
a  concrete  or  masonry  slab  or  footing  which  is  in 
direct  contact  with  the  earth  shall  be  of  approved 
naturally  durable  or  preservative-treated  wood 

Exceptions: 

1 .  Posts  or  columns  which  are  either  exposed 
to  the  weather  or  located  in  basements  or 
cellars,  supported  by  concrete  piers  or  metal 
pedestals  projecting  at  least  one  inch  (25  mm) 
above  the  slab  or  deck  and  six  inches  (152  mm) 
above  exposed  earth,  and  are  separated 
therefrom  by  an  impervious  moisture  barrier. 

2.  Posts  or  columns  in  enclosed  crawl  spaces 
or  unexcavated  areas  located  within  the 
periphery  of  the  building,  supported  by  a 
concrete  pier  or  metal  pedestal  at  a  height 
greater  than  eight  inches  (203  mm)  from 
exposed  ground,  and  are  separated  therefrom 
by  an  impervious  moisture  barrier. 

3603.22.5  Wood  in  contact  with  the  ground:  All 

wood  in  contact  with  the  ground  (exposed  earth) 
which  supports  permanent  structures  that  are 
intended  for  human  occupancy,  shall  be  of  approved 
naturally  durable  or  preservative-treated  wood  using 
water-borne  preservatives  and  shall  be  treated  in 
accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  ground  contact,  where  used  in  the 
locations  specified  in  780  CMR  3603.22.5.1  and 
3603.22.5.2. 

Exception:  Untreated  wood  is  permitted  where 
such  wood  is  entirely  below  the  ground  water 
level  or  where  continuously  submerged  in  fresh 
water. 

3603.22.5.1  Posts  or  columns:  Sawn  posts  and 
columns  supporting  permanent  structures  that  are 
intended  for  human  occupancy  and  which  are 
embedded  in  concrete  in  direct  contact  with  the 
earth  or  embedded  in  concrete  exposed  to  the 
weather,  or  in  direct  contact  with  the  earth,  shall 
be  of  approved  preservative-treated  wood. 

3603.22.5.2  Wood  structural  members:  Wood 
structural  members  that  support  moisture- 
permeable  floors  or  roofs  which  are  exposed  to 
the  weather-such  as  concrete  or  masonry  slabs- 
shall  be  of  approved  naturally  durable  or  preserva 
tive-treated  wood  unless  separated  from  such 
floors  or  roofs  by  an  impervious  moisture  barrier. 

3603.22.6  Exposed  Structural  Members:  Wood 
members  which  form  the  structural  supports  of 
buildings,  balconies,  porches,  decks  or  similar 
permanent  building  appurtenances  where  such 
members  are  exposed  to  the  weather  without 
adequate  protection  from  a  roof,  eave,  overhang  or 
other    covering    to    prevent    moisture    or    water 


accumulation  on  the  surface  or  at  joints  between 
members  Depending  on  local  experience,  such 
members  include,  but  are  not  limited  to,  the 
following: 

1.  Horizontal  members  such  as  girders,  joists  and 
decking; 

2.  Vertical  members  such  as  posts,  poles  and 
columns;  or 

3.  Both  horizontal  and  vertical  members 

3603.22.7  Wood  used  in  retaining  walls  Wood 
installed  in  retaining  or  crib  walls  shall  be  of 
approved  preservative-treated  wood  treated  in 
accordance  with  AWPA  C2  or  C9  listed  in 
Appendix  A  for  ground  contact,  except  as  indicated 
in  780  CMR  3603.22.7.1  through  231  1.7.3. 

3603.22.7.1  Untreated  wood:  Where  the  wall  is 
not  more  than  two  feet  (610  mm)  in  height  and  is 
separated  from  the  lot  line  or  a  permanent 
building  by  a  minimum  distance  equal  to  the 
height  of  the  wall,  the  wall  is  permitted  to  be  of 
untreated  wood. 

3603.22.7.2  Naturally  durable  wood  on  the  lot 
line:  Where  a  retaining  wall  or  a  crib  wall  is  not 
more  than  two  feet  (610  mm)  in  height  and  is 
located  on  the  lot  line,  approved  naturally  durable 
wood  is  permitted. 

3603.22.7.3  Naturally  durable  wood  separated: 

Where  retaining  wall  or  a  crib  wall  is  not  more 
than  four  feet  (1219  mm)  in  height  and  is 
separated  from  the  lot  line  or  a  permanent 
building  by  a  minimum  distance  equal  to  the 
height  of  the  wall,  approved  naturally  durable 
wood  is  permitted. 

780  CMR  3603.23  MANUFACTURED 

BUILDINGS  AND  MANUFACTURED 

HOUSING 

3603.23.1  Scope:  The  design,  manufacture, 
handling,  storage,  transportation,  assembly, 
construction  and/or  installation  of  manufactured 
buildings  and  manufactured  building  components 
intended  for  installation  in  the  Commonwealth  of 
Massachusetts  shall  be  in  accordance  with  the 
provisions  of  780  CMR  35.  Manufactured 
buildings  or  manufactured  building  components 
shall  not  be  installed  in  any  jurisdiction  of  the 
Commonwealth  of  Massachusetts  unless  such 
manufactured  buildings  or  manufactured  building 
components  have  been  approved  and  certified  in 
accordance  with  780  CMR  35,  and  the  Rules  and 
Regulations  for  Manufactured  Buildings, 
Manufactured  Building  Components  and 
Manufactured  Housing,  780  CMR  R3,  as  listed  in 
Appendix  A. 

3603.23.2  Manufactured  housing:  When 
constructed  in  accordance  with  the  Code  of 
Federal  Regulations  (CFR)  Title  24,  Chapter  XX- 


486 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  BUILDING  PLANNING 


Office  of  Assistant  Secretary  for  Housing  -  Federal 
Housing  Commissioner,  Department  of  Housing 
and  Urban  Development,  Parts  3280, 
Manufactured  home  construction  and  safety 
standards,  and  3282,  Manufactured  home 
procedural  and  enforcement  regulations; 
manufactured  housing  shall  be  exempt  from  the 
provisions  of  780  CMR  3603.23. 

Exceptions: 

1.  Foundations  for  manufactured  housing  shall 
conform  to  780  CMR  1806. 0; 

2.  Additions,  (when  not  a  manufactured 
housing  unit  as  defined  herein)  and  site  built 
modifications  shall  conform  to  applicable 
provisions  of  780  CMR 

780  CMR  360324  SANITATION 
3603.24.1    Plumbing    and    Sanitary    Facilities: 

Every  dwelling  unit  shall  be  provided  with  plumbing 
and  sanitary  facilities  as  required  by  248  CMR  the 
Massachusetts  State  Plumbing  and  Fuel  Gas  Code, 
105  CMR  410.000,  the  State  Sanitary  Code,  listed  in 
Appendix  A.     Water  closets,  baths,  showers  and 


bidets  shall  be  located  in  rooms  which  provide 
privacy  to  the  occupant. 

3603.24.2  Water  supply  to  fixtures:  All  plumbing 
fixtures  shall  be  connected  to  an  approved  water 
supply,  in  accordance  with  248  CMR  as  listed  in 
Appendix  A. 

3603.24.3  Wastewater:  Provision  shall  be  made  for 
disposal  of  wastewater  in  accordance  with 
248  CMR,  as  listed  in  Appendix  A.  Wastewater  shall 
be  discharged  to  a  sanitary  sewer  or  to  an  approved 
private  sewage  disposal  system. 

780  CMR  360325  ELECTRICAL 
REQUIREMENTS 

3603.25.1  General:  Every  dwelling  unit  shall  be 
provided  with  electrical  facilities  in  accordance  with 
the  requirements  of  527  CMR  12.00,  the 
Massachusetts  State  Electrical  Code  as  listed  in 
Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 
NON-TEXT  PAGE 


488  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3604 


FOUNDATIONS 


780  CMR  3604.1  GENERAL 

3604.1.1  General:  The  provisions  of  780  CMR 
3604.0  shall  control  the  design  and  construction  of 
the  foundation  and  foundation  spaces  for  all 
buildings. 

3604.1.2  Requirements:  The  foundation  and  its 
structural  elements  shall  be  capable  of 
accommodating  all  superimposed  live,  dead  and 
other  loads  according  to  780  CMR  3603.0  and  all 
lateral  loads  in  accordance  with  the  provisions  of 
780  CMR  36.  Fills  which  support  footings  and 
foundations  shall  be  designed,  installed  and  tested  in 
accordance  with  accepted  engineering  practice. 
Gravel  fill  used  as  footings  for  wood  foundations 
shall  comply  with  780  CMR  3604.3. 

3604.1.3  Drainage:  Surface  drainage  shall  be 
diverted  to  a  storm  sewer  conveyance  or  other  point 
of  collection  away  from  the  foundation  system  to 
avoid  creating  a  hazard.  Finished  grades  shall  be 
arranged  to  direct  surface  water  away  from  all 
foundation  walls.  The  finished  grade  shall  slope  a 
minimum  of  A"  per  foot  for  a  distance  of  at  least 
six  feet  from  the  face  of  all  foundation  walls. 

Exception:  Where  lot  lines,  walls,  slopes  or  other 
physical  barriers  interfere  with  the  drainage 
requirements  of  780  CMR  3604.1.3,  drains  or 
swales  shall  be  provided  to  ensure  that  surface 
drainage  is  appropriately  diverted  away  from  the 
structure. 

3604.1.4  Geotechnical  evaluation:  The 
presumptive  load-bearing  values  defined  in  Table 

3604. 1 .4  shall  be  used  to  determine  soil  bearing 
capacity  for  all  foundation  systems  defined  herein. 

Exception:     Where    there    is    evidence    that 

expansive,  compressible,  shifting  or  other 
unstable  soil  characteristics  exist,  the  building 
official  shall  require  soil  tests  as  necessary  to 
determine  the  bearing  capacity  of  the  soil.  For 
the  purposes  of  this  section,  soils  test  shall  be 
conducted  in  accordance  with  780  CMR  1802. 0. 

3604.1.5  Expansive,  compressible  or  shifting  soil: 

When  top  or  subsoils  are  expansive,  compressible  or 
shifting,  such  soils  shall  be  removed  to  a  depth  and 
width  sufficient  to  assure  stable  moisture  content  in 
each  active  zone  and  shall  not  be  used  as  fill;  or 
stabilized  within  each  active  zone  by  chemical, 
dewatering  or  presaturation. 


TABLE  3604.1.4 

PRESUMPTIVE  LOAD-BEARING  VALUES 

OF  FOUNDATION  MATERIALS 


CLASS  OF  MATERIAL 


Crystalline  bedrock 
Sedimentary  rock 
Sandy  grave!  or  gravel 
Sand,  silty  sand,  clayey  sand, 

silty  gravel  and  clayey 

gravel 
Clay,  sandy  clay,  silty  clay, 

and  f.laywf  gilt 


LOAD  BEARING 

PRESSURE 

(pounds  per  square  foot) 


12,000 
6,000 
5,000 
3,000 


2,000 


780  CMR  3604.2  MATERIALS 
3604.2.1   Wood   foundations:   Wood  foundation 
systems    shall    be    designed    and    installed    in 
accordance  with  the  provisions  780  CMR  36. 

Exception:  The  provisions  of  780  CMR  3604.2 
for  wood  foundations  apply  only  in  the  following 
situations: 

1  Buildings  supported  by  wood  foundations 
shall  be  limited  to  no  more  than  two  floors  and 
a  roof. 

2.  No  dimension  in  a  basement  room  or  crawl 
space  area  shall  exceed  the  smaller  dimension 
of  either  the  building  width  or  building  length 

3604.2.1.1  Fasteners:  Fasteners  used  below  grade 
to  attach  plywood  to  the  exterior  side  of  exterior 
basement  or  crawlspace  wall  studs,  or  fasteners 
used  in  knee  wall  construction,  shall  be  of  Type 
304  or  316  stainless  steel.  Fasteners  used  above 
grade  to  attach  plywood,  and  all  lumber-to-lumber 
fasteners  except  those  used  in  knee  wall 
construction  shall  be  of  Type  304  or  3 16  stainless 
steel,  silicon  bronze,  copper,  hot-dipped 
galvanized  (zinc  coated)  steel  nails,  or  hot- 
tumbled  galvanized  (zinc  coated)  steel  nails 
Electrogalvanized  steel  nails  and  galvanized  (zinc 
coated)  steel  staples  shall  not  be  permitted 

3604.2.1.2  Wood  treatment:  All  lumber  and 
plywood  shall  be  treated  in  accordance  with 
AWPA  C22  as  listed  in  Appendix  A  and  shall  be 
identified  as  in  conformance  with  such  standard 
by  an  approved  inspection  agency.  Where  lumber 
and  plywood  is  cut  or  drilled  after  treatment,  the 
cut  surface  shall  be  field  treated  with  Ammoniacal 
Copper  Arsenate  (ACA),  Chromated  Copper 
Arsenate  (CCA),  or  Copper  Napthenate  by 
repeated  brushing,  dipping  or  soaking  until  the 
wood  absorbs  no  more  preservative.  Water-borne 
preservatives  ACA  and  CCA  Types  A  B  and  C 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


489 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


shall  have  a  minimum  concentration  of  3%  in 
solution.  Water-borne  preservatives  FCAP  and  ACC 
shall  be  permitted  for  field  treatment  of  material 
originally  treated  with  CCA  and  ACA  water-borne 
preservatives,  and  the  concentration  of  FCAP  or 
ACC  shall  be  a  minimum  of  5%  in  solution.  Copper 
Napthenate  shall  be  prepared  with  a  solvent 
conforming  to  AWPA  P5.  The  preservative 
concentration  shall  contain  a  minimum  of  2%  copper 
metal 

3604.2.2  Concrete:  Concrete  shall  have  a  minimum 
specified  compressive  strength  as  shown  in  Table 
3604.12  and  shall  be  air  entrained  when  subject  to 
freeing  and  thawing  during  construction.  Total 
air  content  (percent  by  volume  of  concrete)  shall 
not  be  less  than  5%  or  more  than  7%. 

Exception:  Concrete  mixtures  used  for  exterior 
porches,  carport  slabs,  and  steps  that  will  be 
exposed  to  freezing  and  thawing  in  the  presence 
of  deicing  chemicals  shall  consist  of  520  pounds 
(236  kg)  of  cement  per  cubic  yard  of  concrete 
which  meets  ASTM  C  150  or  C  595  as  listed  in 
Appendix  A. 

TABLE  3604.2.2 
MINIMUM  SPECIFIED  COMPRESSIVE 
STRENGTH  OF  CONCRETE     


TYPE  OR  LOCATION  OF 
CONCRETE  CONSTRUCTION 

mtnimum  specified 
compressive 

strength'c/'c) 

Basement  walls  and  foundations 
not  exposed  to  the  weather 

2,5002 

Basement  slabs  and  interior  slabs 
on  grade,  except  garage  floor  slabs 

2.5002 

Basement  walls,  foundation  walls, 
exterior  walls  and  other  vertical 
concrete  work  exposed  to  the 
weather 

3.0O03 

Porches,  carport  slabs  and  steps 
exposed  to  the  weather,  and 
garage  floor  slabs 

3.5003'4 

For  SI:  1  psi  =  6.895  kPa. 

1 .  At  28  days  psi. 

2.  Concrete  in  these  locations  which  may  be  subject  to 
freezing  and  thawing  during  construction  shall  be  air- 
entrained  concrete  in  accordance  with  Footnote  3. 

3.  Concrete  shall  be  air-entrained.  Total  air  content 
(percent  by  volume  of  concrete)  shall  not  be  less  than  5% 
or  more  than  7%. 

4.  See  780  CMR  3604.2.2.  for  minimum  cement 
content 


780  CMR  36043  FOOTINGS 

3604.3.1  General:  All  permanent  supports  of 
buildings  and  structures  larger  than  120  square 
feet  in  area  or  ten  feet  in  height  shall  extend  to 
minimum  of  four  feet  (1.2  m)  below  finished  grade 
except  when  erected  on  solid  rock  or  otherwise 
protected  from  frost,  or  when  the  foundation  grade 
is  established  by  a  registered  design  professional 
and  is  approved  by  the  building  code  official 
Minimum  sizes  for  concrete  or  masonry  footings 
shall  be  as  set  forth  in  Table  3604.3  1  and  Figure 
3604.3.1a 

3604.3.1.1  Slope:  The  top  surface  of  all  footings 
shall  be  level.  The  bottom  surface  of  footings  may 
have  a  slope  not  exceeding  one  unit  vertical  in  ten 
units  horizontal  (10%  slope)  Footings  shall  be 
stepped  where  it  is  necessary  to  change  the 
elevation  of  the  top  surface  of  the  footing,  or 
where  the  slope  of  the  bottom  surface  of  the 
footing  will  exceed  one  unit  vertical  in  ten  units 
horizontal  (10%  slope). 

3604.3.2  Footings  for  wood  foundations:  Footings 
for  wood  foundations  shall  comply  with  the 
applicable  provisions  of  780  CMR  3604.4,  and 
Figures  3604.3.1b  and  3604.3.1c  The  gravel  base 
depicted  in  Figures  3604.3.1b  and  3604.3.  lc  shall 
be  washed  and  well  graded  The  maximum  size 
stone  shall  not  exceed  %  inch  (19  mm).  Gravel  shall 
be  free  from  organic,  clayey  or  silty  soils.  Sand  shall 
be  coarse,  not  smaller  than  1/16-inch  (1.6  mm)  grains 
and  shall  be  free  from  organic,  clayey  or  silty  soils 
Crushed  stone  shall  have  a  maximum  size  of  V*  inch 
(12.7  mm). 

3604.3.3  Insulated  footings:  Footings  for  heated 
buildings  with  slab-on-ground  foundations  are  not 
required  to  extend  below  the  frost  line  when 
protected  from  frost  by  insulating  methods 
prescribed  by  Figure  3604.3.3a  and  Table  3604.3.3 
Materials  used  below  grade  for  the  purpose  of 
insulating  foundations  against  frost  shall  be  labeled 
as  complying  with  ASTM  C  578. 


490 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FOUNDATIONS 


FIGURE  3604.3.1a 

CONCRETE  AND  MASONRY 

FOUNDATION  DETAILS 

-  BEARING  WALL 
3  l.Z"  MIN.- 


GROUND  SLPPORT  SLAB  WITH  WASONRY     BASEMENT  OH  CRAM.  SPACE  WITH 


WALL  AND  SPREAD  FOOTING 


MASONRY  WALL  AND  SPREAD  FOOT*!  G 
EXTEPJOR 


BASEMENT  Cfl  CRAWl  SPACE 
WITH  CONCRETE  WALL  AND  SPREAD 
FOOTING 


BASEMENT  Cfl  CRAWL  SPACE  WITH 
FOUNCATION  WAa  BEARING 
DIRECTLY  ON  SOI 


NOTES 

1.  Exterior  footings  shall  extend  to  below  the  frost  line 
unless  otherwise  protected  against  frost  heave.  In  no  case 
shall  exterior  footings  be  less  than  12  inches  below  grade. 

2.  Footing  widths  (W)  shall  be  based  on  the  load-bearing 
value  of  the  soil  in  accordance  with  Table  3604.1.4  or 
shall  be  designed  in  accordance  with  accepted 
engineering  practice. 

3.  Spread  footings  shall  be  a  minimum  of  six  inches 
thick,  and  footing  projections  (P)  shall  be  a  minimum  two 
inches  and  shall  not  exceed  the  footing  thickness. 

4.  Footings  shall  be  supported  on  undisturbed  natural 
soil  or  engineered  fill. 

5.  The  sill  plate  or  floor  system  shall  be  anchored  to  the 
foundation  with  VS-inch-diameter  bolts  placed  six  feet  on 
center  and  not  more  than  12  inches  from  corners.  Bolts 
shall  extend  a  minimum  of  15  inches  into  masonry  or 
seven  inches  into  concrete.  Sill  plates  shall  be  protected 
against  decay  where  required  by  780  CMR  3603.22. 

6.  Pier  and  column  footing  sizes  shall  be  based  on  the 
tributary  load  and  allowable  soil  pressure  in  accordance 
with  Table  3605.2.3.3b. 


For  SI  1  inch  =  25.4  mm.  1  foot  =  304 .8  mm 


2/7/97    (-Effective  2/28/97) 


780  CMR  -  Six'h  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

FIGURE  3604.3.1b 
TYPICAL  DETAILS  FOR  WOOD  FOUNDATION  BASEMENT  WALL 


FIELD  APPLIED  2  BY  6  TOP  PLATE 


2  BY  6  TOP  PLATE 


2  BY  6  STUD  WALL  INSULATED  AS  APPROPRIATE 
AND  WARM  SIDE  VAPOR  BARRIER 


1 '  THICK  LUMBER  OR  PLYWOOD  STRIP 
PROTECTING  TOP  OF  POLYETHYLENE  FILM 


FINISH  GRADE  SLOPE  1/2"  PER  FOOT 
MINIMUM  6'  FROM  WALL 


PLYWOOD  (See  Table  3604.43.3 
6  MIL  POLYETHYLENE  FILM 


6  MIL  POLYETHYLENE  FILM  ON 
CRUSHED  STONE  OR  GRAVEL  BACKFILL 


3'  OR  4"  CONCRETE  SLAB  WITH  OPTIONAL 
1"  SCREED  BOARD  AND  VAPOR  BARRIER 


2  BY  6  BOTTOM  PLATE 
2  BY  8  FOOTING  PLATE 

4"  GRAVEL  OR  CRUSHED  STONE  FILL 


For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 


492 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FOUNDATIONS 


FIGURE  3604.3.1c 
TYPICAL  DETAILS  FOR  WOOD  FOUNDATION  CRAWL  SPACE  WALLS 


FLOOR  JOIST 

FIELD  APPLIED  2  BY  6  TOP  PLATE 
FLASHING 
2  BY  6  TOP  PLATE 


FINISH  GRADE  SLOPE  V2"  PER  FOOl 
MINIMUM  6'  FROM  WALL 


2  BY  6  STUD  WALL 

6  MIL  POLYETHYLENE  FILM 
PLYWOOD  (See  Table  3604.4.3.3 

2  BY  6  BOTTOM  PLATE 

2  BY  8  FOOTING  PLATE 

4"  GRAVEL  OR  CRUSHED  STONE 

BELOW  FROST  LINE 


For  SI:  !  inch  =  25.4  mm,  1  foot  =  304.8  mm. 

TABLE  3604.3.1 

MINIMUM  WIDTH  OF  CONCRETE  OR 

MASONRY  FOOTINGS  (inches) 


LOAD-BEARING  VALUE  OF  SOIL  (psf) 


TABLE  3604.3.3 

MINIMUM  INSULATION  REQUIREMENTS 

FOR  FROST-PROTECTED  FOOTINGS  IN 

HEATED  BUILDINGS 


1.500     2,000     2.500     3,000     3,500     4,000 


Conventional  Wood  Frame  Construction 


1 -story 

16 

12 

10 

8 

7 

6 

2-story 

19 

15 

12 

10 

8 

7 

3 -story 

22 

17 

14 

11 

10 

9 

VERTICAL 
INSULA- 
TION/?- 
VALUE14 

HORIZONTAL 

INSULATION  R- 

VALUEW 

HORIZONTAL 

INSULATION 

DIMENSIONS  PER 

FIGURE  3604.3.3 

(inches) 

along  walls 

at  corners 

A 

B 

C 

45 

NR 

NR 

NR 

NR 

NR 

4-inch  Brick  Veneer  over  Wood  Frame  or 
Hollow  Concrete  Masonry 

8-inch 

1 -story 

19 

15 

12 

10 

8 

7 

2-story 

25 

19 

15 

13 

11 

10 

3 -story 

31 

23 

19 

16 

13 

12 

8-inch  Solid  or  Fully  Grouted  Masonry 


1 -story 

22 

17 

13 

11 

10 

9 

2-story 

32 

23 

19 

16 

13 

12 

3-storv 

40 

30 

24 

20 

17 

15 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304  8  mm. 


For  SI:  1  inch  =  25.4  mm,  °F  =  1.8°C  +  32 

1.  Insulation  requirements  are  for  protection  against  frost 
damage  in  heated  buildings.  Greater  values  may  be 
required  to  meet  energy  conservation  standards. 
Interpolation  between  values  is  permissable. 

2.  Air  Freezing  Index  values  based  on  1,500  °F  days. 

3.  Insulation  materials  shall  provide  the  stated  minimum 
R-values  under  the  long  term  exposure  to  moist,  below- 
ground  conditions  in  freezing  climates.  The  following  R- 
values  shall  be  used  to  determine  insulation  thickness 
required  for  this  application:  Type  II  expanded  polystyrene  - 
2.4R  per  inch;  Type  IV  extruded  polystyrene  -  4.5R  per 
inch;  Type  VI  extruded  polystyrene  -  4  5R  per  inch;  Type 
IX  expanded  polystyrene  -  3.2R  per  inch;  Type  X  extruded 
polystyrene  -  4.5R  per  inch.  NR  indicates  that  insulation  is 
not  required. 

4.  Vertical  insulation  shall  be  expanded  polystyrene 
insulation  or  extruded  insulation. 

5.  Horizontal  insulation  shall  be  extruded  polystyrene 
insulation. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

FIGURE  3604.3.3a 

INSULATION  PLACEMENT  FOR  FROST-PROTECTED  FOOTINGS 

IN  HEATED  BUILDINGS 


INSULATION  DETAIL 


■  VERTICAL  WALL  INSULATION' 
-  HORIZONTAL  INSULATION' 
NOMINAL  4"  THICK  GRANULAR  BASE 


"4--  ■■■-^'<AH~,-->:y  "-,■■:■■   .--nirS^^M^i 


HORIZONTAL  INSULATION  PLAN 


For  SI:  1  inch  =  25.4  mm. 

1.      See  table  3604.3.3  for  required  dimensions  and  R- 

values  for  vertical  and  horizontal  insulation. 

780  CMR  3604.4  FOUNDATION  WALLS 
3604.4.1  Concrete  and  masonry  foundation  walls: 

Foundation  walls  shall  be  constructed  in  accordance 
with  the  provisions  of  780  CMR  3604.4  or  in 
accordance  with  ACI  318,  ACI  318.1,  NCMA 
TR68-A  or  ACI  530/ASCE  5/TMS  402  as  listed  in 
Appendix  A,  or  other  approved  structural  systems. 

3604.4.1.1  Masonry  and  concrete  wall 
construction:  Masonry  and  concrete  foundation 
walls  shall  be  constructed  as  in  accordance  with 
Table  3604.4.1.1a. 

Exception:  Where  unstable  soil  conditions 
exist  or  where  the  foundation  extends  to  or 
below  the  seasonal  high  groundwater  table, 


foundation    walls    shall    be    constructed    in 
accordance  with  Table  3604.4.1.1b. 

3604.4.1.2  Design:  Foundation  walls  subject  to 
more  pressure  than  would  be  exerted  by  backfill 
having  an  equivalent  fluid  weight  of  30  pounds 
per  cubic  foot  (141  kN/m3)  shall  be  designed  in 
accordance  with  accepted  engineering  practice  by 
a  registered  professional  engineer  or  registered 
architect. 

3604.4.1.3  Grade  Clearance:  Foundation  walls 
shall  extend  at  least  eight  inches  above  the 
finished  grade  adjacent  to  the  foundation  at  all 
points. 

Exception:  Where  masonry  veneer  is  used, 
foundation  walls  shall  extend  a  minimum  of  four 
inches  (102  mm)  above  the  finished  grade. 


494 


780  CMR  -  Sixth  Edition 


'7/97    (Effective  2/28/97) 


1,2 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FOUNDATIONS 

TABLE  3604.4.1.1a 

MINIMUM  THICKNESS  AND  ALLOWABLE 

DEPTH  OF  UNBALANCED  FILL  FOR 

UNRETNFORCED  MASONRY  AND, 
CONCRETE  FOUNDATION  WALLS 
WHERE  UNSTABLE  SOIL  OR 
GROUNDWATER  CONDITIONS  DO  NOT 
EXIST  ======^^ 

For  SI:  1  inch  =  25.4  mm:  1  foot  =  304.8  mm. 

1.  Unbalanced  fill  is  the  difference  in  height  of  the 
exterior  and  interior  finish  ground  levels.  Where  an 
interior  concrete  slab  is  provided,  the  unbalanced  fill 
shall  be  measured  from  the  exterior  finish  ground  level  to 
the  top  of  the  interior  concrete  slab. 

2.  The  height  between  lateral  supports  shall  not  exceed 
eight  feet. 

3.  The  actual  thickness  shall  not  be  more  than  V2  inch 
less  than  the  required  nominal  thickness  specified  in  the 
table. 

4.  Six-inch  plain  concrete  walls  shall  be  formed  on  both 
sides. 


FOUNDATION  WALL 
CONSTRUCTION 

NOMINAL, 

THICKNESS"' 

(inches') 

MAXIMUM 

DEPTH  OF 

UNBALANCED 

FILL1  (feel) 

Masonry  of  Hollow  Units. 
L'ngrouted 

S 
10 

12 

4 
5 
6 

Masonry  of  Solid  Units 

6 
S 
10 

12 

5 
6 

Masonry  of  Hollow  or  Solid 
Units,  Fully  Grouted 

S 
10 
12 

7 
8 
8 

Plain  Concrete 

6* 
8 
10 

6 

8 
8 

Rubble  Stone  Masonrv 

16 

8 

Masonry  of  hollow  units 
reinforced  vertically, 
with  No.  4  bars  and  grout 
at  24  inches  on  center. 
Bars  located  not  less 
than  41/;  inches  from 
pressure  side  of  wall. 

8 

7 

TABLE  3604.4.1.1  b 

REQUIREMENTS  FOR  MASONRY  OR  CONCRETE  FOUNDATION  WALLS  SUBJECTED  TO 

NO  MORE  PRESSURE  THAN  WOULD  BE  EXERTED  BY  BACKFILL  HAVING  AN 

EQUIVALENT  FLUID  WEIGHT  OF  30  POUNDS  PER  CUBIC  FOOT  OR  SUBJECTED  TO 

UNSTABLE  SOIL  CONDITIONS  


MATERIAL  TYPE 

HEIGHT  OF 
UNBALANCED 
FILL  IN  FEET 

LENGTH  OF 

WALL  BETWEEN 

SUPPORTING 

MASONRY  OR 

CONCRETE 
WALLS  IN  FEET 

MINIMUM" 

WALL 

THICKNESS  IN 

INCHES'' 

REQUIRED  REINFORCING 

Honzintal  Bar  in 

Upper  1 2  inches  of 

wall 

Size  and  Spacing  of 
Vertical  Bars 

Hollow  Masonry 

4  or  less 

unlimited 

S 

not  required 

not  required 

more  than  4 

design  required 

design  required 

design  required 

design  required 

4  or  less 

unlimited 

8 

noot  required 

not  required 

more  than  4 

less  lha  8 

8 

2-No  3 

No.  3  (a),  18"o.c. 

Masonry 

8  or  less 

8  to  10 

8 

2-No.  4 

No.  3@  18"oc. 

8  or  less 

10  to  12 

8 

2-No.  5 

No  3  @  18"  oc. 

more  than  8 

design  required 

design  required 

design  required 

design  required 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  pound  per  cubic  foot  (pcf)  =  0. 1572  kN/m" . 

1    Backfilling  shall  not  be  commenced  until  after  the  wall  is  anchored  to  the  floor  or  adequate  bracing  is  in  place. 

2.  Thickness  of  concrete  walls  may  be  six  inches,  provided  reinforcing  is  placed  not  less  than  one  inch  or  more  than 
two  inches  from  the  face  of  the  wall  not  against  the  earth. 

3.  The  actual  thickness  shall  not  be  more  than  Vi  inch  less  than  the  required  thickness  specified  in  the  table. 

4.  Solid  masonry  shall  include  solid  brick  or  concrete  units  and  hollow  masonry  units  with  all  cells  grouted. 


3604.4.1.3.1  Backfill  placement:  Backfill 
adjacent  to  the  wall  shall  not  be  placed  until 
the  wall  has  sufficient  strength  in  accordance 


with  780  CMR  3604.2.2  and  has  been  anchored 
to  the  floor,  or  has  been  sufficiently  braced  to 
prevent  damage  by  the  backfill. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Exception:  Such  bracing  is  not  required  for 
walls  retaining  less  than  three  feet  (914 
mm)  of  unbalanced  backfill. 

3604.4.2  Design  required:  Foundation  walls  subject 
to  more  lateral  pressure  than  would  be  exerted  by 
backfill  consisting  of  freely  draining  sands  and 
gravel  classified  as  Group  I  according  to  the  United 
States  Soil  Classification  System  or  soils  having  an 
equivalent  fluid  weight  of  greater  than  30  pounds  per 
cubic  foot  (4.72  kN/m3)  shall  be  designed  in 
accordance  with  accepted  engineering  practices  by 
a  registered  professional  engineer  or  registered 
architect. 


3604.4.3  Wood  foundation  walls:  Wood  foundation 
walls  shall  be  constructed  in  accordance  with  the 
provisions  of  780  CMR  3604.4.3.1  through 
3604.4.3.5  and  with  the  details  shown  in  Figures 
3604.3.1b  and  3604.3.1c 

3604.4.3.1  Wood  grade:  All  load-bearing  lumber 
and  plywood  shall  conform  to  applicable 
standards  or  grading  rules  and  be  identified  by  a 
grade  mark  or  certificate  of  inspection  issued  by 
an  approved  lumber  or  plywood  grading  or 
inspection  bureau  or  agency.  Lumber  shall 
conform  to  DOC  PS  20-70. 


TABLE  3604.4.3.3 

PLYWOOD  GRADE  AND  THICKNESS  FOR 

WOOD  FOUNDATION  CONSTRUCTION 

(30  pcf  equivalent-fluid  weight  soil  pressure) 


HEIGHT 

STUD 
SPACING 
(inches) 

FACE  GRAIN  ACROSS  STUDS 

FACE  GRAIN  PARALLEL  TO  STUDS 

OF  FILL 
(inches) 

Grade 

Minimum 
Thickness 

Identification 
Index 

Grade 

Minimum 
Thickness" 

Identification  Index 

12 

B 

15/32 

32/16 

A 

15/32 

32/16 

B 

15/323 

32/16 

16 

B 

15/32 

32/16 

A 

15/323 

32/16 

B 

19/323(4,5ply) 

40/20 

12 

B 

15/32 

32/16 

A 

15/32 

32/16 

B 

15/323(4,5ply) 

32/16 

36 

B 

1 9/323  (4,  5  ply) 

40/20 

16 

B 

15/323 

32/16 

A 

19/32 

40/20 

B 

23/32 

48/24 

12 

B 

15/32 

32/16 

A 

15/323 

32/16 

48 

B 

19/323(4,5ply) 

40/20 

16 

B 

19/32 

40/20 

A 

19/323 

40/20 

A 

23/32 

48/24 

For  SI:  1  inch  =  25.4  mm,  1  pound  per  cubic  foot  =  0. 1572  kN/m" . 

1.  Plywood  shall  be  of  the  following  minimum  grades  in  accordance  with  DOC  PS  1  or  DOC  PS2: 
(i)    DOC  PS  1  Plywood  grades  marked: 

a.  Structural  I  C-D  (Exposure  I) 

b.  C-D  (Exposure  I) 

(ii)    DOC  PS  2  Plywood  grades  marked: 

a.  Structural  I  Sheathing  (Exposure  I) 

b.  Sheathing  (Exposure  I) 

(iii)    Where  a  major  portion  of  the  wall  is  exposed  above  ground  and  a  better  appearance  is  desired,  the  following 
plywood  grades  marked  Exterior  are  suitable: 

a.  Structural  I A-C,  Structural  I  B-C  or  Structural  I  C-C  (Plugged)  in  accordance  with  DOC  PS  1 

b.  A-C  Group  1,  B-C  Group  1,  C-C  (Plugged)  Group  1  or  MDO  Group  1  in  accordance  with  DOC  PS  1 

c.  Single  Floor  in  accordance  with  DOC  PS  2 

2.  Minimum  thickness  15/32  inch,  except  crawl  space  sheathing  may  be  %  inch  for  face  grain  across  studs  16  inches 
on  center  and  maximum  two  foot  depth  of  unequal  fill. 

3.  For  this  fill  height,  thickness  and  grade  combination,  panels  which  are  continuous  over  less  stud  spacings  require 
blocking  16  inches  above  the  bottom  plate.  Offset  adjacent  blocks  and  fasten  through  corrosion-resistant  nails  at  each 
end. 


3604.4.3.2  Stud  size:  The  studs  used  in 
foundation  walls  shall  be  two  by  six  (51  by  153) 
members.  When  spaced  16  inches  on  center,  a 
wood  species  with  an  Fb  value  of  not  less  than 
1,250    psi    (8612    kPa)    as    listed    in    Table 


3605.2.3.1d  shall  be  used.  When  spaced  12  inches 
(305  mm)  on  center,  an  Fb  of  not  less  than  875 
(6029  kPa)  shall  be  required. 

3604.4.3.3  Height  of  backfill:  The  height  of 
backfill  against  a  foundation  wall  shall  not  exceed 


496 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FOUNDATIONS 


more  than  12  inches  (305  mm)  above  the  interior 
grade  of  a  crawl  space  or  floor  of  a  basement,  the 
thickness  of  the  plywood  sheathing  shall  meet  the 
requirements  of  Table  3604.4.3.3. 

3604.4.3.4  Backfilling:  Wood  foundation  walls 
shall  not  be  backfilled  until  the  basement  floor 
and  first  floor  have  been  constructed  or  the  walls 
have  been  braced.  For  crawl  space  construction, 
backfill  or  bracing  shall  be  installed  on  the 
interior  of  the  walls  prior  to  placing  backfill  on 
the  exterior. 

3604.4.3.5  Drainage  and  dampproofing:  Wood 
foundation  basements  shall  be  drained  and 
dampproofed  in  accordance  with  780  CMR 
3604.5  and  780  CMR  3604.6,  respectively. 

780  CMR  3604.5  FOUNDATION  DRAINAGE 
3604.5.1     Concrete    or    masonry    foundations: 

Drains  shall  be  provided  around  all  concrete  or 
masonry  foundations  enclosing  habitable  or  usable 
spaces  located  below  grade.  Drainage  tiles,  gravel  or 


crushed  stone  drains,  perforated  pipe  or  other 
approved  systems  or  materials  shall  be  installed  at  or 
below  the  area  to  be  protected  and  shall  discharge  by 
gravity  or  mechanical  means  into  an  approved 
drainage  system.  Gravel  or  crushed  stone  drains 
shall  extend  at  least  one  foot  (305  mm)  beyond  the 
outside  edge  of  the  footing  and  six  inches  (153  mm) 
above  the  top  of  the  footing  and  be  covered  with  an 
approved  filter  membrane  material.  The  top  of  open 
joints  of  drain  tiles  shall  be  protected  with  strips  of 
building  paper,  and  the  drainage  tiles  or  perforated 
pipe  shall  be  placed  on  a  minimum  of  two  inches  (5 1 
mm)  of  washed  gravel  or  crushed  rock  at  least  one 
sieve  size  larger  than  the  tile  joint  opening  or 
perforation  and  covered  with  not  less  than  six  inches 
(153  mm)  of  the  same  material. 

Exception:  A  drainage  system  is  not  required 
when  the  foundation  is  installed  on  well-drained 
ground  or  sand-gravel  mixture  soils  according  to 
the  Unified  Soil  Classification  System,  Group  I 
Soils,  as  detailed  Table  3604.5.1. 


TABLE  3604.5.1 

PROPERTIES  OF  SOILS  CLASSD7IED  ACCORDING  TO  THE  UNIFDZD 

SOIL  CLASSIFICATION  SYSTEM 


SOIL 
GROUP 

UNIFIED  SOIL 

CALSSIFICA- 

TION  SYSTEM 

SYMBOL 

SOIL  DESCRIPTION 

DRAINAGE 
CHARACTERISTICS 

FROST 

HEAVE 

POTENTIAL 

VOLUME 

CHANGE 

POTENTIAL 

EXPANSION 

GW 

Well-graded  gravels,  gravel  sand 
mixtures,  little  or  no  fines 

Good 

Low 

Low 

GP 

Poorly  graded  gravels  or  gravel  sand 
mixtures,  little  or  no  fines 

Good 

Low 

Low 

Group  I 

sw 

Well-graded  sands,  gravelly  sands, 
little  or  no  fines 

Good 

Low 

Low 

SP 

Poorly  graded  sands  or  gravelly 
sands,  little  or  no  fines 

Good 

Low 

Low 

GM 

Silty  gravels,  gravel-sand-silt 
mixtures 

Good 

Medium 

Low 

SM 

Siltv  sand,  sand-silt  mixtures 

Good 

Medium 

Low 

GC 

Clayey  gravels,  gravel-sand-clay 
mixtures 

Medium 

Medium 

Low 

SC 

Clayey  sands,  sand-clay  mixture 

Medium 

Medium 

Low 

Group  II 

ML 

Inorganic  silts  and  very  fine  sands, 
rock  flour,  silty  or  clayey  fine  sands 
or  clayey  silts  with  slight  plasticity. 

Medium 

High 

Low 

CL 

Inorganic  clays  of  low  to  medium 
plasticity,  gravelly  clays,  sandy 
clays,  silty  clays,  lean  clays 

Medium 

Medium 

Medium"  to 
Low 

Group 
III 

CH 

Inorganic  clays  or  high  plasticity,  fat 
clavs 

Poor 

Medium 

High2 

MH 

Inorganic  silts,  micaceous  or 
diatomaceous  fine  sandy  or  silty 
soils,  elastic  silts 

Poor 

High 

High 

Group 
IV 

OL 

Organic  silts  and  organic  silty  clays 
of  low  plasticity. 

Poor 

Medium 

Medium 

OH 

Organic  clays  of  medium  to  high 
plasticity,  organic  silts. 

Unsatisfactory 

Medium 

High 

Pt 

Peat  and  other  highlv  organic  soils. 

Unsatisfactory 

Medium 

Hieh 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

For  SI:  1  inch  =  25.4  mm. 

1    The  percolation  rate  for  good  drainage  is  over  four  inches  per  hour,  medium  drainage  is  two  to  four  inches 

per  hour,  and  poor  is  less  than  two  inches  per  hour. 

2.    Dangerous  expansion  might  occur  if  these  two  soil  types  are  dry  but  subject  to  future  wetting. 


3604.5.2  Wood  foundations:  Wood  foundations 
enclosing  habitable  or  usable  spaces  located  below 
grade  shall  be  adequately  drained  in  accordance  with 
780  CMR  3604.5.2.1  through  3604.5.2.3. 

3604.5.2.1  Base:  A  porous  layer  of  gravel, 
crushed  stone  or  coarse  sand  shall  be  placed  to  a 
minimum  thickness  of  four  inches  (102  mm) 
under  the  basement  floor.  Provision  shall  be  made 
for  automatic  draining  of  this  layer  and  the  gravel 
or  crushed  stone  wall  footings. 

3604.5.2.2  Moisture  barrier:  A  six-mil-thick 
(0.15  mm)  polyethylene  moisture  barrier  shall  be 
applied  over  the  porous  layer  with  the  basement 
floor  constructed  over  the  polyethylene. 

3604.5.2.3  Drainage  system:  In  other  than 
Group  I  soils,  a  sump  shall  be  provided  to  drain 
the  porous  layer  and  footings.  The  sump  shall  be 
at  least  24  inches  (610  mm)  in  diameter  or  20 
inches  square  (0.0129  m  ),  shall  extend  at  least  24 
inches  (610  mm)  below  the  bottom  of  the 
basement  floor  and  shall  be  capable  of  positive 
gravity  or  mechanical  drainage  to  remove  any 
accumulated  water.  The  drainage  system  shall 
discharge  into  an  approved  sewer  system  or  to 
daylight. 

780  CMR  3604.6  FOUNDATION 
WATERPROOFING  AND  DAMPPROOFING 

3604.6.1  Concrete  and  masonry  foundation 
dampproofing:  Except  where  required  to  be 
waterproofed  by  780  CMR  3604.6.2,  foundation 
walls  enclosing  habitable  or  storage  space  shall  be 
dampproofed  from  the  top  of  the  footing  to  the 
finished  grade.  Masonry  walls  shall  be  dampproofed 
by  applying  not  less  than  3/s  inch  (9.5  mm)  portland 
cement  parging  to  the  exterior  of  the  wall.  The 
parging  shall  be  covered  with  a  bituminous  coating, 
three  pounds  per  square  yard  (1.63  kg/m2)  of  acrylic 
modified  cement,  Vfc-inch  (3.2  mm)  coat  of  surface- 
bonding  mortar  complying  with  ASTM  C  887  or  any 
material  permitted  for  waterproofing  in  780  CMR 
3604.6.2.  Concrete  walls  shall  be  dampproofed  by 
applying  any  one  of  the  above  listed  dampproofing 
materials  or  any  one  of  the  waterproofing  materials 
listed  in  780  CMR  3604.6.2  to  the  exterior  of  the 
wall. 

3604.6.2  Concrete  and  masonry  foundation 
waterproofing:  In  areas  where  a  high  water  table  or 
other  severe  soil-water  conditions  are  known  to 
exist,  exterior  foundation  walls  enclosing  habitable 
or '  storage  space  shall  be  waterproofed  with  a 
membrane  extending  from  the  top  of  the  footing  to 
the  finished  grade.    The  membrane  shall  consist  of 


two-ply  hot-mopped  felts,  55  pound  (25  kg)  roll 
roofing,  6-mil  (0.  15  mm)  polyvinyl  chloride,  six-mil 
(0.15  mm)  polyethylene  or  40-mil  (1  mm)  polymer- 
modified  asphalt.  The  joints  in  the  membrane  shall 
be  lapped  and  sealed  with  an  adhesive  compatible 
with  the  waterproofing  membrane. 

3604.6.3  Dampproofing  for  wood  foundations: 

Wood  foundations  enclosing  habitable  or  usable 
spaces  located  below  grade  shall  be  dampproofed  in 
accordance  with  780  CMR  3604.6.3.1  through 
3604.6.3.5. 

3604.6.3.1  Panel  joint  sealed:  Plywood  panel 
joints  in  the  foundation  walls  shall  be  sealed  full 
length  with  a  caulking  compound  capable  of 
producing  a  moistureproof  seal  under  the 
conditions  of  temperature  and  moisture  content  at 
which  it  will  be  applied  and  used. 

3604.6.3.2  Below  grade  moisture  barrier:  A  six- 
mil-thick  (0.15  mm)  polyethylene  film  shall  be 
applied  over  the  below-grade  portion  of  exterior 
foundation  walls  prior  to  backfilling.  Joints  in  the 
polyethylene  film  shall  be  lapped  six  inches  (153 
mm)  and  sealed  with  adhesive.  The  top  edge  of 
the  polyethylene  film  shall  be  bonded  to  the 
sheathing  to  form  a  seal.  Film  areas  at  grade  level 
shall  be  protected  from  mechanical  damage  and 
exposure  by  a  pressure  preservatively  treated 
lumber  or  plywood  strip  attached  to  the  wall 
several  inches  above  finish  grade  level  and 
extending  approximately  nine  inches  (229  mm) 
below  grade.  The  joint  between  the  strip  and  the 
wall  shall  be  caulked  full  length  prior  to  fastening 
the  strip  to  the  wall.  Other  coverings  appropriate 
to  the  architectural  treatment  may  also  be  used. 
The  polyethylene  film  shall  extend  down  to  the 
bottom  of  the  wood  footing  plate  but  shall  not 
overlap  or  extend  into  the  gravel  or  crushed  stone 
footing. 

3604.6.3.3  Porous  fill:  The  space  between  the 
excavation  and  the  foundation  wall  shall  be 
backfilled  with  the  same  material  used  for 
footings,  up  to  a  height  of  one  foot  (305  mm) 
above  the  footing  for  well-drained  sites,  or  Vz  the 
total  backfill  height  for  poorly  drained  sites.  The 
porous  fill  shall  be  covered  with  strips  of  30- 
pound  (13.6  kg)  asphalt  paper  or  six-mil  (0.15 
mm)  polyethylene  to  permit  water  seepage  while 
avoiding  infiltration  of  fine  soils. 

3604.6.3.4  Backfill:  The  remainder  of  the 
excavated  area  shall  be  backfilled  with  the  same 
type  of  soil  as  was  removed  during  the 
excavation.  The  backfill  shall  be  placed  in  six-  to 


498 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FOUNDATIONS 


eight-inch   (153    mm   to   203    mm)   layers   and 
compacted  to  consolidate  the  fill. 

3604.6.3.5  Final  grading:  Finished  grades  shall 
conform  to  780  CMR  3604.1.3. 

780  CMR  3604.7  FOUNDATION 
INSULATION 

3604.7.1  Protection  of  exposed  foundation 
insulation:  Foundation  walls  and  the  edges  of  slab- 
on-ground  floors  with  exterior  applied  insulation 
shall  have  a  rigid,  opaque  and  weather-resistant 
protective  covering  to  prevent  the  degradation  of 
thermal  performance.  The  protective  covering  shall 
cover  the  exposed  insulation  and  extend  to  a 
minimum  of  six  inches  (153  mm)  below  grade. 

780  CMR  3604.8  COLUMNS 

3604.8.1  Wood  column  protection:  Wood  columns 
shall  be  protected  against  decay  as  set  forth  in 
780  CMR  3603.22. 

3604.3.2  Steel  column  protection:  All  surfaces 
(inside  and  outside)  of  steel  columns  shall  be  given 
a  shop  coat  of  rust-inhibitive  paint,  except  for 
corrosion-resistant  steel  and  steel  treated  with 
coatings  to  provide  corrosion  resistance. 

3608.3  Structural  requirements:  All  columns  shall 
be  restrained  to  prevent  lateral  displacement.  Wood 
columns  shall  not  be  less  in  nominal  size  than  four 
inches  by  four  inches  (102  mm  by  i  02  mm)  and 
steel  columns  shall  not  be  less  than  three-inch- 
diameter  (76  mm)  standard  pipe  or  approved 
equivalent. 

780  CMR  3604.9  CRAWL  SPACE 

3604.9.1  Ventilation:  The  space  between  the  bottom 
of  the  floor  joists  and  the  earth  under  any  building 
(except  such  space  as  is  occupied  by  a  basement  or 
cellar)  shall  be  provided  with  a  sufficient  number  of 
ventilation  openings  through  foundation  walls  or 
exterior  walls.  Such  ventilation  openings  shall  be 
covered  with  corrosion-resistant  wire  mesh,  the  least 
dimension  shall  not  exceed  Vs  inch  (3.2  mm).  The 
minimum  net  area  of  ventilation  openings  shall  not 
be  less  than  one  square  foot  for  each  150  square  feet 


(0.67  m"  for  each  100  nr)  of  crawl  space  area.  One 
such  ventilating  opening  shall  be  within  three  feet 
(914  mm)  of  each  corner  of  the  building,  and  the 
ventilation  openings  shall  be  positioned  to  provide 
cross  ventilation. 

Exceptions: 

1.  The  total  area  of  ventilation  openings  may  be 
reduced  to  1/1,500  of  the  under-floor  area  where 
the  ground  surface  is  treated  with  an  approved 
vapor  barrier  material  and  one  such  ventilation 
opening  is  within  three  feet  (914  mm)  of  each 
corner  of  said  buildings.  The  vents  may  have 
operable  louvers. 

2       If  design  conditions  warrants,  ventilation 
openings  may  be  omitted  on  one  side. 
3.      Under-floor  spaces  used  as  supply  plenums 
for  distribution  of  heated  and  cooled  air  shall 
comply  with  the  requirements  of  780  CMR  3621 
as  applicable. 
4.       Ventilation  openings  may  be  omitted  when 
continuously    operated    mechanical    ventilation    is 
provided  at  a  rate  of  1 .0  cfm  for  each  50  square  feet 
(1.02  L/s  for  each  10  m")  of  crawl  space  floor  area 
and  ground  surface  is  covered  with  an  approved 
vapor  barrier  material. 

3604.9.2  Access:  An  access  crawl  hole  18  inches  by 
24  inches  (457  mm  by  610  mm)  shall  be  provided  to 
the  under-floor  space. 

3604.3  Removal  of  debris:  The  under-floor  grade 
shall  be  cleaned  of  all  vegetation  and  organic 
material.  All  wood  forms  used  for  placing  concrete 
shall  be  removed  before  a  building  is  occupied  or 
used  for  any  purpose. 

3604.9.4  Finished  grade:  The  finished  grade  of 
under-floor  surface  may  be  located  at  the  bottom  of 
the  footings;  however,  where  there  is  evidence  that 
the  groundwater  table  can  rise  to  within  six  inches 
(153  mm)  of  the  finished  floor  at  the  building 
perimeter  or  where  there  is  evidence  that  the  surface 
water  does  not  readily  drain  from  the  building  site, 
the  grade  in  the  under-floor  space  shall  be  as  high  as 
the  outside  finished  grade,  unless  an  approved 
drainage  system  is  provided. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


499 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


500  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3605 


FLOORS 


780  CMR  3605.1  GENERAL 

3605.1.1  Application:  The  provisions  of  780  CMR 
3605.0  shall  control  the  design  and  construction  of 
the  floors  for  all  buildings.  The  use  of  materials  or 
methods  of  construction  not  specified  in  780  CMR 
3605.0  accomplishing  the  purposes  intended  by 
780  CMR  36  and  approved  by  the  building  official 
in  accordance  with  780  CMR  1 09  shall  be  accepted 
as  complying  with  780  CMR  36. 

3605.1.2  Requirements:  Floor  construction  shall  be 
capable  of  supporting  all  loads  imposed  according 
to  780  CMR  3603.1  and  transmitting  the  resulting 
loads  to  other  supporting  elements. 

780  CMR  3605.2  FLOOR  FRAMING 

3605.2.1  General:  Load-bearing  dimension  lumber 
for  joists,  beams  and  girders  shall  conform  to  DOC 
PS  20,  as  listed  in  Appendix  A,  and  to  other 
applicable  standards  or  grading  rules  and  shall  be  so 
identified  by  a  grade  mark  or  certificate  of 
inspection  issued  by  an  approved  agency  The  grade 
mark  or  certificate  shall  provide  adequate 
information  to  determine  Fb.  the  allowable  stress  in 
bending,  and  E,  the  modulus  of  elasticity. 

Exception:  Use  of  Native  Lumber  shall  be 
allowed  in  accordance  with  780  CMR  2303.0. 

3605.2.1.1  Preservative-treated       lumber: 

Preservative-treated  dimension  lumber  shall  also 
be  identified  by  the  quality  mark  of  an  approved 
agency. 

3605.2.1.2  Blocking  and  subflooring:  Blocking 
shall  be  a  minimum  of  Utility  grade  lumber. 
Subflooring  may  be  a  minimum  of  Utility  Grade 
lumber  or  No.  4  Common  grade  boards. 

3605.2.1.3  End  jointed  lumber:  Approved  end- 
jointed  lumber  may  be  used  interchangeably  with 
solid-sawn  members  of  the  same  species  and 
grade. 

3605.2.2  Design  and  construction:  Floors  of  wood 
construction  shall  be  designed  and  constructed  in 
accordance  with  the  provisions  of  780  CMR  3605.2 
and  Figure  3605.2.2. 

3605.2.3  Allowable  spans:  Joists,  girders  and  floor 
sheathing  shall  comply  with  780  CMR  3605.2.3.1 
through  3 605. 2. 3. 3  and  780  CMR  3605.3 

3605.2.3.1  Allowable  joist  spans:  The  clear  span 
of  floor  joists  shall  not  exceed  the  values  set  forth 
in  Tables  3605.2.3.1a,  3605.2.3.1b  and 
3605.2.3.1c  The  modulus  of  elasticity,  E,  and  the 


actual  stress  in  bending,  Fb,  shown  in  the  tables 
shall  not  exceed  the  values  specified  in  Tables 
3605.2.3. Id  and  3605.2.3.  le  listed  at  the  end  of 
780  CMR  3605.2.  The  values  for  Fb,  specified  as 
"repetitive  member  use"  may  be  used  when  floor 
joists  are  spaced  not  more  than  24  inches  (610 
mm)  on  center. 

3605.2.3.2  Joists    under   bearing    partitions: 

Joists  under  parallel  bearing  partitions  shall  be 
doubled  or  a  beam  of  adequate  size  to  support  the 
load  shall  be  provided.  Double  joists  which  are 
separated  to  permit  the  installation  of  piping  or 
vents  shall  be  provided  with  solid  blocking  spaced 
not  more  than  four  feet  (1219  mm)  on  center. 

3605.2.3.3  Allowable     girder     spans:     The 

allowable  spans  of  girders  shall  not  exceed  the 
values  set  forth  in  Tables  3605.2.3.3a  and 
3605.2.3.3b. 

3605.2.4  Bearing:  The  ends  of  all  joists,  beams  or 
girders  shall  have  not  less  than  114  inches  (38  mm) 
of  bearing  on  wood  or  metal  and  not  less  than  three 
inches  (76  mm)  on  masonry  except  where  supported 
on  a  one-inch-by-four-inch  (25  mm  by  102  mm) 
ribbon  strip  and  nailed  to  the  adjacent  stud  or  shall 
be  supported  by  the  use  of  approved  joist  hangers. 

3605.2.4.1  Floor  systems:  Joists  that  are  framed 
from  opposite  sides  and  extend  over  a  bearing 
support  shall  be  tied  together  by  lapping  the  ends 
of  each  joist  a  minimum  of  three  inches  (76  mm), 
or  with  a  wood  or  metal  splice  plate,  or  shall  be 
secured  by  overlapping  the  floor  sheathing  at 
least  three  inches  (76  mm)  beyond  the  end  of 
each  floor  joist,  or  by  other  approved  methods 

3605.2.4.2  Joist  framing  Joists  framing  into  the 
side  of  a  wood  girder  shall  be  supported  by 
approved  framing  anchors  or  on  ledger  strips 
measuring  not  less  than  nominal  two  inches  by 
two  inches  (5 1  mm  by  5 1  mm). 

3605.2.5  Lateral  restraint  at  supports:  Joists  shall 
be  supported  laterally  at  the  ends  by  full-depth  solid 
blocking  not  less  than  two  inch  (51  mm)  nominal 
thickness;  or  by  attachment  to  a  header,  band  or  rim 
joist,  or  to  an  adjoining  stud;  or  shall  be  otherwise 
provided  with  lateral  support  to  prevent  rotation. 
Such  lateral  support  is  not  required  over 
intermediate  supports  such  as  center  girders  or 
bearing  walls. 

3605.2.5.1  Bridging:  Joists  having  a  depth-to- 
thiclcness  ratio  exceeding  6:1  based  on  nominal 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


501 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


dimensions  shall  be  supported  laterally  by  solid 
blocking,  diagonal  bridging  (wood  or  metal),  or  a 
continuous  one-inch-by-three-inch  (25  mm  by  76 
mm)  strip  set  perpendicularly  across  the  bottom  of 
joists  and  appropriately  nailed.  Bridging  shall  be 
installed  at  intervals  not  exceeding  eight  feet  (2438 
mm). 

Exception:  Cantilevered  joists  shall  be  laterally 
braced  at  points  of  support 

3605.2.6  Cutting  and  notching:  It  shall  be  unlawful 
to  notch,  cut  or  pierce  wood  beams,  joists,  rafters  or 
studs  in  excess  of  the  limitations  specified  in 
780  CMR  3605.2.6,  unless  proven  safe  by  structural 
analysis  or  suitably  reinforced  to  transmit  all 
calculated  loads. 

3605.2.6.1  Drilling  and  notches:  Notches  in  the 
top  or  bottom  of  joists  shall  not  exceed  one-sixth 
of  the  depth  of  the  joist,  shall  not  be  longer  than 
one-third  the  depth  of  the  member  and  shall  not 
be  located  in  the  middle  third  of  the  span.  Notch 
depth  at  the  ends  of  the  member  shall  not  exceed 
one-fourth  the  joist  depth. 


Exceptions: 

1.  A  notch  over  the  support  is  permitted  to 
extend  the  full  width  of  the  support 

2.  Notches  on  cantilevered  portions  of  the 
member  are  permitted  to  extend  the  full 
length  of  the  cantilever  if  the  strength  and 
deflection  of  the  cantilever  is  calculated  based 
on  the  reduced  member  section. 

3.  The  tension  side  of  beams,  joists  and 
rafters  which  are  four  inches  or  greater  in 
nominal  thickness,  shall  not  be  notched, 
except  at  ends  of  members. 

3605.2.6.2  Holes:  Holes  drilled,  bored  or  cut  into 
joists  shall  not  be  closer  than  two  inches  (5 1  mm) 
to  the  top  or  bottom  of  the  joists,  or  to  any  other 
hole  located  in  the  joist  Where  the  joist  is 
notched,  the  hole  shall  not  be  closer  than  two 
inches  to  the  notch.  The  diameter  of  the  hole 
shall  not  exceed  one-third  the  depth  of  the  joist. 

3605.2.8  Fastening:  Floor  framing  shall  be  nailed  in 
accordance  with  Table  3606.2.3a.  Where  posts  and 
beam  or  girder  construction  is  used  to  support  floor 
framing,  positive  connections  shall  be  provided  to 
ensure  against  uplift  and  lateral  displacement. 


502 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


FIGURE  3605.2.2 
FLOOR  CONSTRUCTION 


-  SUBFLOOR  OR 
FLOOR  SHEATHING 
SEE  780  CMR  3605.3 


■  FOUNDATION 


OT 


-  BRIDGING 
BETWEEN  JOISTS 
_j      SEE  SECTION  3605.2.5.1 


DOUBLE  JOISTS  UNDER  BEARING 
PARTITIONS.  IF  JOISTS  ARE 
SEPARATED  FOR  PIPES.  BLOCK 
4'-0-  ON  CENTER  MAXIMUM 


o   O 


PROVISION  FOR  PIPES 
AND  VENTS 


For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


503 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1a 

ALLOWABLE  SPANS  FOR  FLOOR  JOISTS 

40  Lbs.  per  Sq.  Ft.  Live  Load 

(All  rooms  except  those  used  for  sleeping  areas  and  attic  floors.) 

DESIGN  CRITERIA: 

Strength-  Live  load  of  40  lbs.  per  sq.  ft.  plus  dead  load  of  10  lbs.  per  sq.  ft.  determines  the  fiber  stress  value 

shown. 
Deflection-For  40  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (upper  figure  in  each  square).  Determine  size  and 
spacing  (first  column)  based  on  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row) 
of  lumber  to  be  used. 


Joist  Size 
and  Spacing 

MODULUS  OF  ELASTICITY,  "E,"  IN  1,000.000  PSI 

inches!  inches!    0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0    1    1.1    1    1.2 

1.3 

1.4    1    1.5 

1.6 

1.7 

1.8 

1.9    I    2.0 

2.2 

2.4 

12.0 

6-9 
450 

7-3 
520 

7-9 
590 

8-2 
660 

8-6 

720 

8-10 
780 

9-2 
830 

9-6 
890 

3-9 
940 

10-0 
990 

10-3 
1,040 

10-6 
1,090 

10-9 
1,140 

10-11 
1.190 

11-2 
1,230 

11-4 

1,280 

11-7" 
1,320 

ii-n 

1,410 

12-3 
1,490 

2X6 

16.0 

6-2 
500 

6-7 
580 

7-0 
650 

7-5 
720 

7-9 
790 

8-0 
860 

8-4 
920 

8-7 
980 

8-10 
1,040 

9-1 
1,090 

9-4 
1,150 

9-6 

1,200 

9-9 

1,250 

9-11 
1,310 

10-2 
1,360 

10-4 
1,410 

10-6 
1,460 

10-10 
1,550 

11-2 
1,640 

24.0 

5-4 
570 

5-9 
660 

6-2 
750 

6-6 
830 

6-9 

900 

7-0 
980 

7-3' 
1.050 

7-6 
1,120 

7-9 
1.190 

7-11 
1,250 

8-2 
1,310 

8-4 
1,380 

8-6 

1,440 

8-8 
1,500 

8-10 
1,550 

9-0 
1,610 

>2 
1,670 

9-6 

1,780 

9-9 
1.880 

12.0 

8-11 
450 

9-7 
520 

10-2 
590 

10-9 
660 

11-3 

720 

11-8 
780 

12-1 
830 

12-6 
890 

12-10 
940 

13-2 
990 

13-6 

1,040 

13-10 
1,090 

14-2 
1,140 

14-5 
1,190 

14-8 
1,230 

15-0 
1,280 

15-3 

1,320 

15-9 
1,410 

16-2 
1,490 

2X8 

16.0 

8-1 
500 

8-9 
580 

9-3 

650 

9-9 

720 

10-2 
790 

10-7 
850 

11-0 
920 

11-4 

980 

11-8 
1,040 

12-0 
1,090 

12-3 
1,150 

12-7 
1,200 

12-10 
1,250 

13-1 
1,310 

13^1 
1,360 

13-7 
1,410 

13-10 
1,460 

14-3 
1,550 

14-8 
1,640 

24.0 

7-1 
570 

7-7 
660 

8-1 

750 

8-6 
830 

8-11 
900 

9-3 
980 

9-7 
1,050 

9-11 

1,120 

10-2 
1,190 

10-6 

1,250 

10-9 
1,310 

11-0 
1,380 

11-3 

1,440 

11-5 

1,500 

11-8 
1,550 

11-11 
1,610 

12-1 

1,670 

12-6 
1,780 

12-10 
1,880 

12,0 

11-4 
450 

12-3 
520 

13-0 
590 

13-8 
660 

14-4 
720 

14-11 
780 

15-5 
830 

15-11 
890 

16-5 
940 

16-10 
990 

17-3 
1,040 

17-8 
1,090 

18-0 
1,140 

18-5 
1,190 

18-9 
1,230 

19-1 
1,280 

19-5 

1320 

20-1 
1,410 

20-8 
1,490 

2X  10 

16.0 

10-4 
500 

11-1 
580 

U-1Q 
650 

12-5 
720 

13-0 
790 

13-6 
850 

14-0 
920 

14-6 
980 

14-11 
1,040 

15-3 
1,090 

15-8 
1,150 

16-0 
1,200 

16-5 
1,250 

16-9 
1310 

17-0 
1360 

17-4 
1,410 

17-8 
1,460 

18-3 
1,550 

18-9 
1,640 

24:0 

9-0 
570 

9-9 
660 

10-4 
750 

10-10 
830 

11-4 
900 

11-10 
980 

12-3 
1,050 

12-8 
1,120 

13-0 
1,190 

13-4 

1,250 

13-8 
1,310 

14-0 
1.380 

14-4 
1,440 

14-7 
t,500 

14-11 
1.550 

15-2 
1.610 

15-5 
1.670 

15-1! 
1,780 

16-5 
1,880 

12.0 

13-10 
450 

14-11 
520 

15-10 
590 

16-8 
660 

17-5 
720 

18-1 
780 

18-9 
830 

19-4 
890 

19-11 
940 

20-6 
990 

21-0 
1,040 

21-6 
1,090 

21-11 
1,140 

22-5 
1,190 

22-10 
1,230 

23-3 

1,280 

23-7 
1,320 

24-5 
1,410 

25-1 
1,490 

2X  12 

16.0 

12-7 
500 

13-6 

580 

14-4 
650 

15-2 
720 

15-10 
790 

16-5 
860 

17-0 
920 

17-7 
980 

18-1 
1.040 

18-7 
1,090 

17-11 
1,220 

18^t 
1,280 

18-9 
1,330 

19-2 
1,390 

19-6 

1,440 

19-10 
1,500 

20-2 
1,550 

20-10 
1,650 

21-6 
1,750 

24.0 

11-10 
570 

11-10 
660 

12-7 
750 

13-3 

830 

13-10 
900 

14^1 
980 

14-11 

1,050 

15^1 
1,120 

15-10 
1,190 

16-3 
1,250 

16-8 
1.310 

17-0 
1,380 

17-5 
1,440 

17-9 

1 ,500 

18-1 
1,550 

18-5 
1,610 

18-9 
1,670 

19-4 
1,780 

19-11 
1,880 

For  SI:   1  inch  =  25.4  mm,  1  pound  per  square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/nr. 
NOTE:  The  extreme  fiber  stress  in  bending,  "Fj,"  in  pounds  per  square  inch  is  shown  below  each  span. 


504 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 

TABLE  3605.2.3.1b 

ALLOWABLE  SPANS  FOR  FLOOR  JOISTS 

30  Lbs  per  Sq.  Ft.  Live  Load 

(All  rooms  used  for  sleeping  areas  and  attic  floors.) 
DESIGN  CRITERIA: 

Strength-  10  lbs.  per  sq.  ft.  dead  load  plus  30  lbs.  per  sq.  live  load  determines  fiber  stress  value  shown. 
Deflection-For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (Upper  figure  in  each  square).  Determine  size  and 
spacing(first  column)  based  on  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row) 
of  lumber  to  be  used. 


Joist  Size  and 
Spacing 

MODULUS  OF  ELASTICITY,  "E,"  IN  1,000,000  PSI 

inches 

inches 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

1.1 

1.2 

1.3 

1.4 

1.5 

1.6 

1.7 

1.8 

1.9 

2.0    I    2.2 

2.4 

1Z0 

7-5 
440 

8-0 
510 

8-6 

570 

8-11 
640 

94 
700 

9-9 

750 

10-1 
810 

10-5 
860 

10-9 
910 

ii-o 

960 

11-3 
1,010 

11-7 
1,060 

11-10 
1,100 

12-0 
1,150 

12-3 
1,200 

12-6 
1,240 

12-9 
1,280 

13-1 

1,370 

13-6 
1,450 

2X6 

16.0 

6-9 

480 

7-3 
560 

7-9 
630 

8-2 
700 

8-6 

770 

8-10 
830 

9-2 
890 

9-6 
950 

9-9 
1,000 

10-0 
1,060 

10-3 
1,110 

10-6 
LJ60 

10-9 
1,220 

10-11 
1,270 

11-2 
1320 

114 

1,360 

11-7 
1,410 

11-11 

1,500 

12-3 
1,590 

24.0 

5-11 

550 

6-4 

640 

6-9 
720 

7-1 
800 

7-5 
880 

7-9 
950 

8-0 
1,020 

8-3 
1,080 

8-6 
1,150 

8-9 
1,210 

8-11 

1,270 

9-2 
1,330 

94 
1,390 

9-7 
U450 

9-9 
1.510 

9-11 
1,560 

10-1 
1,620 

10-5 
1,720 

10-9 
1,820 

12.0 

9-10 
440 

10-7 
510 

11-3 

570 

11-10 
640 

124 
700 

12-10 
750 

134 
810 

13-9 
860 

14-2 
910 

14-6 
960 

14-11 
1,010 

15-3 
1,060 

15-7 
1,100 

15-10 
1,150 

16-2 
1,200 

16-6 
1,240 

16-9 
1,280 

174 
1,370 

17-10 
1,450 

2X8 

16.0 

8-11 
480 

9-7 
560 

10-2 
630 

10-9 

700 

11-3 
770 

11-8 
830 

12-1 

890 

12-6 
950 

12-10 

1,000 

13-2 
1,060 

13-6 
1,110 

13-10 
1,160 

14-2 
1,220 

14-5 
1,270 

14-8 
1,320 

15-0 

1,360 

15-3 
1,410 

15-9 
1,500 

16-2 
1,590 

24.0 

7-9 
550 

8-5 

640 

8-11 

720 

94 
800 

9-10 
880 

10-2 

950 

10-7 
1,020 

10-11 
1,080 

11-3 
1,150 

11-6 

1,210 

11-10 
1,270 

12-1 
1,330 

124 
1,390 

12-7 
1,450 

12-10 
1,510 

13-1 
1^560 

134 
1,620 

13-9 

1,720 

14-2 
U520 

12.0 

12-6 
440 

13-6 
510 

14-4 

570 

15-1 
640 

15-9 
700 

16-5 
750 

17-0 
810 

17-6 
860 

18-0 
910 

18-6 
960 

19-0 
1,010 

19-5 
1,060 

19-10 
1,100 

20-3 
1,150 

20-8 
1,200 

.21-0 
1,240 

21-5 
1,280 

22-1 

1,370 

22-9 
1,450 

2X10 

16.0 

11-4 
480 

12-3 
560 

13-0 
630 

13-8 
70O 

144 

770 

14-11 
830 

15-5 
890 

15-11 
950 

16-5 
1,000 

16-10 

1,060 

17-3 
1,1 10 

17-8 
1,160 

18-0 
1,220 

18-5 
1,270 

18-9 
1320 

19-1 
1,360 

19-5 
1,410 

20-1 
1,500 

20-8 
1,590 

24.0 

9-11 
550 

10-8 
640 

11-4 
720 

11-11 
800 

12-6 
880 

13-0 
950 

13-6 

1,020 

13-11 

1.080 

14-4 
1,150 

14-8 
1,210 

15-1 

1,270 

15-5 
1,330 

15-9 
1,390 

16-1 
1,450 

16-5 
1,510 

16-8 

1,560 

17-0 
1,620 

17-6 

U720 

18-0 
1,820 

12.0 

15-2 
440 

16-5 
510 

17-5 
570 

184 
640 

19-2 
700 

19-11 
750 

20-8 
810 

214 
860 

21-11 
910 

22-6 
960 

23-1 
1,010 

23-7 
1,060 

24-2 
1,100 

24-8 
1,150 

25-1 
1,200 

25-7 
1,240 

26-0 
1,280 

26-10 
1,370 

27-8 
1,450 

2X  12 

16.0 

13-10 
480 

14-11 
560 

15-10 
630 

16-8 
700 

17-5 
770 

18-1 
830 

18-9 
890 

194 
950 

19-11 
1,000 

20-6 
1,060 

21-0 
1,110 

21-6 
1,160 

21-11 
1,220 

22-5 
1,270 

22-10 
1,320 

23-3 
1,360 

23-7 
1,410 

24-5 
1,500 

25-1 
1,590 

24.0 

12-1 

550 

13-0 

640 

13-10 

720 

14-7 

800 

15-2 
880 

15-10 
950 

16-5 
1,020 

16-11 
1,080 

17-5 
1,150 

17-11 

1,210 

184 

1,270 

18-9 

1,330 

19-2 

1,390 

19-7 

1,450 

19-11 

1,510 

20-3 

1,560 

20-8 
1,620 

214 
1,720 

21-11 

1,820 

For  SI:   1  inch  =  25.4  mm,  1  pound  per  square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m 
NOTE:  The  extreme  fiber  stress  in  bending,  "Fb"  in  pounds  per  square  inch  is  shown  below  each  span. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


505 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1c 

ALLOWABLE  SPANS  FOR  FLOOR  JOISTS  IN  DECKS  AND  BALCONIES 

60  Lbs  per  square  foot  Live  Load 

DESIGN  CRITERIA: 

Strength  -  Live  load  of  60  psf  plus  dead  load  of  10  psf  determines  the  fiber  stress  value  shown. 
Deflection  -  Live  load  of  60  psf.  Limited  to  span  (in  inches)  divided  by  360. 

HOW  TO  USE  TABLES: 

Enter  table  with  span  of  joists  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column)  based 
on  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row)  of  lumber  to  be  used. 


Joist  S 

zeand 

.ing 

ties 

MODULUS  OF  ELASTICITY 

"E",  IN  1,000,000  PSI 

Spa 
inc 

0.8 

0.9 

1.0 

1.1 

1.2 

1.3 

1.4 

1.5 

1.6 

1.7 

1.8 

1.9 

2.0 

2.1 

2.2   2.3 

2.4 

12 

7-5 
767 

7-9 
830 

8-0 
890 

8-3 
949 

8-6 
1005 

8-9 
1061 

9-2 
1 167 

9-4 
1218 

9-7 
1268 

9-9 
1317 

9-11 
1366 

10-1 
1413 

10-3 
1460 

1114 

1506 

1551 

1596 

2x6 

16 

6-9 
844 

7-0 
913 

7-3 
980 

7-6 
1044 

7-9 
1107 

7-11 
U67 

8-2 
1226 

8-4 
1284 

8-6 

1341 

8-8 
1396 

8-10 
1450 

9-0 
1503 

9-2 
1556 

9-4 
1607 

9-6 
1658 

9-7 
1707 

9-9 
1757 

24 

5-11 
967 

6-2 

1046 

6-4 

1122 

6-7 
1195 

6-9 
1267 

6-11 
1336 

7-1 
1404 

7-3 
1470 

7-5 
1535 

7-7 
1598 

7-9 
1660 

7-10 
1721 

8-0 
1781 

8-2 
1848 

8-3 

1897 

8-5 
1995 

8-6 

2011 

12 

9-10 
767 

10-2 
830 

10-7 
890 

10-11 
949 

11-3 

1005 

11-6 
1061 

11-10 
1114 

12-1 
1167 

12-4 
1218 

12-7 
1268 

12-10 
1317 

13-1 
1366 

13-4 
1413 

13-6 
1460 

13-9 
1506 

13-11 
1551 

14-2 
1596 

2x8 

16 

8-11 
844 

9-3 
913 

9-7 
980 

9-11 

1044 

10-2 
1107 

10-6 
1167 

10-9 
1226 

11-0 
1284 

11-3 
1341 

11-5 
1396 

11-8 

1450 

11-11 
1503 

12-1 
1556 

12-3 
1607 

12-6 
1658 

12-8 
1707 

12-10 
1757 

24 

7-9 
967 

8-1 
1046 

8-5 

1122 

8-8 
1195 

8-11 
1267 

9-2 
1336 

9-4 
1404 

9-7 
1470 

9-10 
1535 

10-0 
1598 

10-2 
1660 

10-5 
1721 

10-7 
1781 

10-9 
1848 

10-11 
1897 

11-1 
1995 

11-3 
2011 

12 

12-6 
767 

13-0 
830 

13-6 

890 

13-11 
949 

14-4 

1005 

14-8 
1061 

15-1 
III4 

15-5 
1167 

15-9 
1218 

16-1 

1268 

16-5 
1317 

16-8 
1366 

17-0 
1413 

17-3 
1460 

17-6 
1506 

17-9 
1551 

18-0 
1596 

2x10 

16 

11-4 

844 

11-10 
913 

12-3 
980 

12-8 
1044 

13-0 
1107 

13-4 
1167 

13-8 
1226 

14-0 
1284 

14-4 
1341 

14-7 
1396 

14-11 
1450 

15-2 
1503 

15-5 
1556 

15-8 
1607 

15-11 

1658 

16-2 
1707 

16-5 
1757 

24 

9-11 
967 

10-4 
1046 

10-8 
1122 

II-O 
1195 

11-4 
1267 

1 1-8 
1336 

11-11 

:!404 

12-3 
1470 

12-6 
1535 

12-9 
1598 

13-0 
1660 

13-3 
1721 

13-6 
1781 

13-8 
1848 

13-11 
1897 

1 4-1 
1995 

14-4 
2011 

12 

15-2 
767 

15-10 
830 

16-5 

890 

16-11 
949 

17-5 
1005 

17-11 
1061 

18-4 
1114 

18-9 
1167 

19-2 
1218 

19-7 
1268 

19-11 
1317 

20-3 
1366 

20-8 
1413 

21-0 
1460 

21-4 

1506 

21-7 
1551 

21-11 
1596 

2x12 

16 

13-10 
844 

14-4 
913 

14-11 
980 

15-4 
1044 

15-10 
1107 

16-3 
1167 

16-8 
1226 

17-0 
1284 

17-5 
1341 

17-9 
1396 

18-1 
1450 

18-5 
1503 

18-9 
1556 

19-1 
1607 

19-4 
1658 

19-8 
1707 

19-11 
1757 

24 

12-1 
967 

12-7 
1046 

13-0 
1122 

13-5 
1195 

13-10 
1267 

14-2 
1336 

14-7 
1404 

14-11 
1470 

15-2 
1535 

15-6 
1598 

15-10 
1660 

16-1 
1721 

16-5 
1781 

16-8 
1848 

16-11 
1897 

17-2 
1995 

17-5 
2011 

For  SI:    1  inch  =  25.4  mm,  1  pound  per  square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2 
NOTE:  The  extreme  fiber  stress  in  bending,  "Fb  "  in  pounds  per  square  inch  is  shown  below  each  span. 


506 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3. Id 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 

These  "F"  values  are  for  use  where  three  or  more  repetitive  members  are  spaced  not  more  than  24  inches  apart.   For 
wider  spacing  or  for  single  or  double  member  headers  or  beams,  the  "Fb"  values  should  be  reduced  13%.    Values  for 


surfaced  drv  or  surfacec 

i  creen  lumber 

applv  at  19%  maximum  moisture 

content  tn  use. 

SPECIES  AND  GRADE 

SIZE 

NORMAL 

DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

ASPEN 

Select  Structural 

2"  x  4" 

1,510 

1,735 

1,885 

1,100,000 

Northeastern 

Lumber 

Manufacturers 

Association 

Northern 
Softwood 
Lumber 
Bureau 

Western 

Wood 

Products 

Association 

(See  Footnotes 
1  and  2) 

No:  1 

1.080 

1,240 

1.350 

1,100.000 

No.  2 

1,035 

1.190 

1,295 

1,000,000 

No.  3 

605 

695 

755 

900,000 

Stud 

600 

690 

750 

900,000 

Construction 

805 

"25 

1,005 

900,000 

Standard 

430 

495 

540 

900,000 

Utility 

200 

230 

250 

800.000 

Select  Structural 

2"x  6" 

1.310 

1,505 

1,635 

1,100.000 

No.  1 

935 

1,075 

1,170 

1,100.000 

No.  2 

895 

1,030 

1,120 

1 ,000,000 

No.  3 

525 

600 

655 

900,000 

Stud 

545 

630 

685 

900,000 

Select  Structural 

2"  x  8" 

1.210 

1.390 

1,510 

1,100,000 

No.  1 

865 

990 

1,080 

1,100,000 

No.  2 

830 

950 

1.035 

1 ,000.000 

No.  3 

485 

555 

605 

900.000 

Select  Structural 

2"x  10" 

1.105 

1,275 

1.385 

1.100,000 

No.  1 

790 

910 

990 

1,100,000 

No.  2 

760 

875 

950 

1,000,000 

No.  3 

445 

510 

555 

900,000 

Select  Structural 

2"x  12" 

1,005 

1.155 

1,260 

1,100,000 

No.  1 

720 

825 

900 

1,100.000 

No.  2 

690 

795 

865 

1,000,000 

No.  3 

405 

465 

505 

900,000 

BEECH 

-BiRCll-HICKC 

RY 

Select  Structural 

2"  x  4" 

2,500 

2.875 

3,125 

1 ,700,000 

Northeastern 

Lumber 
Manufacturers 
Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,810 

2,085 

2,265 

1 ,600,000 

No.  2 

1.725 

1.985 

2,155 

1,500,000 

No.  3 

990 

1,140 

1,240 

1,300,000 

Stud 

980 

1,125 

1,225 

1,300,000 

Construction 

1,325 

1,520 

1,655 

1 ,400,000 

Standard 

750 

860 

935 

1,300,000 

Utility 

345 

395 

430 

1 ,200,000 

Select  Structural 

2"x  6" 

2,170 

2,495 

2,710 

1,700,000 

No.  1 

1,570 

1,805 

1,960 

1,600,000 

No.  2 

1.495 

1,720 

1.870 

1,500,000 

No.  3 

860 

990 

1,075 

1,300,000 

Stud 

890 

1,025 

1,115 

1,300,000 

Select  Structural 

2"  x  8" 

2,000 

2,300 

2,500 

1 .700,000 

No.  1 

1,450 

1,665 

1,810 

1 ,600,000 

No.  2 

1,380 

1,585 

1,725 

1,500,000 

No.  3 

795 

915 

990 

1,300,000 

Select  Structural 

2"x  10" 

1,835 

2,110 

2,295 

1 ,700,000 

No.  1 

1,330 

1,525 

1,660 

1 ,600,000 

No.  2 

1.265 

1,455 

1,580 

1 ,500,000 

No.  3 

725 

835 

910 

1.300,000 

Select  Structural 

2"  x  1 2" 

1.670 

1,920 

2,085 

1.700,000 

No.  1 

1.210 

1,390 

1,510 

1 ,600,000 

No.  2 

1,150 

1,325 

1.440 

1 ,500,000 

No  3 

660 

760 

825 

1 ,300,000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


NORMAL 

DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading    7-Day  Loading 

COTTONWOOD 

Select  Structural 

2"  x  4" 

1,510 

1,735 

1,885 

1 ,200,000 

Northeastern 

Lumber 

Manufacturers 

Association 

Northern 

Softwood 
Lumber 
Bureau 

Western 

Wood 

Products 

Association 

(See  Footnotes 
land  2) 

No.  1 

1 .080 

1,240 

1,350 

1,200,000 

No.  2 

1,080 

1,240 

1,350 

1,100,000 

No.  3 

605 

695 

755 

1,100,000 

Stud 

oOO 

690 

750 

1 ,000,000 

Construction 

SO? 

925 

1,005 

1 ,000,000 

Standard 

400 

530 

575 

900,000 

Ulilitv 

200 

230 

250 

900,000 

Select  Structural 

2"x  6" 

1.310 

1,505 

1.635 

1,200,000 

No.  1 

935 

1.075 

1,170 

1,200,000 

No  2 

935 

1.075 

1,170 

1,100,000 

No.  3 

525 

ooo 

655 

1 ,000,000 

Stud 

545 

630 

685 

1 ,000.000 

Select  Structural 

2"  x  8" 

1.210 

1.390 

1.510 

1,200.000 

No.  1 

865 

990 

1,080 

1.200,000 

No.  2 

865 

990 

1.080 

1,100.000 

No.  3 

485 

555 

O05 

1 ,000.000 

Select  Structural 

2"x  10" 

1.105 

1.275 

1,385 

1.200.000 

No.  1 

790 

910 

910 

1 ,200,000 

No.  2 

790 

910 

990 

1,100.000 

No.  3 

445 

510 

555 

1,000,000 

Select  Structural 

2"xl2" 

1.005 

1.155 

1,260 

1 ,200.000 

No   1 

720 

825 

900 

1 ,200,000 

No.  2 

720 

825 

900 

1,100,000 

No.  3 

405 

465 

505 

1.000,000 

DOUGLAS  FIR  -  LARCH 

Select  Structural 

2"  x  4" 

2.500 

2,875 

3,125 

1,900.000 

West  Coast 
Lumber 

Inspection 
Bureau 

Western 

Wood 

Products 

Association 

(See  Footnotes 
1  and  2) 

No.  1  &  Btr 

1 .985 

2.2SO 

2,480 

1 ,800,000 

No   1 

1.725 

1.985 

2,155 

1 .700,000 

No.  2 

1.510 

1,735 

1,885 

1,600,000 

No  3 

865 

WOO 

1,080 

1,400,000 

Stud 

855 

980 

1,065 

1 ,400,000 

Construction 

1,150 

1.325 

1,440 

1,500.000 

Standard 

635 

725 

790 

1 ,400,000 

Utilitv 

315 

365 

395 

1,300,000 

Select  Structural 

2"x  6" 

2,170 

2,495 

2,710 

1,900,000 

No   1  &  Btr 

1.720 

1.975 

2,150 

1,800,000 

No.  1 

1,495 

1,720 

1.870 

1,700,000 

No.  2 

1,310 

1.505 

1,635 

1 ,600.000 

No.  3 

750 

860 

935 

1 ,400,000 

Stud 

775 

895 

970 

1,400,000 

Select  Structural 

2"  x  8" 

2.000 

2,300 

2,500 

1 ,900,000 

No.  &  Btr 

1,585 

1,825 

1,985 

1,800,000 

No.  1 

1.380 

1.585 

1,725 

1,700,000 

No.  2 

1.210 

1.390 

1.510 

1 ,600,000 

No.  3 

690 

795 

865 

1 ,400,000 

Select  Structural 

2"x  10" 

1.835 

2.110 

2,295 

1 ,900,000 

No   1  &  Btr 

1.455 

1.675 

1.820 

1,800,000 

No.  1 

1.265 

1.455 

1 ,580 

1 .700.000 

508 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3. Id  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

No.  2 

2"x  10" 

1.105 

1,275 

1,385 

1,600,000 

No.  3 

635 

725 

790 

1,400,000 

DOUGLAS  FIR  -  LARCH  (NORTH) 

Select  Structural 

2"  x  4" 

2,245 

2,580 

2.805 

1,900,000 

National 
Lumber 
Grades 
Authority 

(See  Footnotes 
1  and  2) 

No.  l/No.2 

1,425 

1,635 

1,780 

1 ,600,000 

No.  3 

820 

940 

1,025 

1,400,000 

Stud 

820 

945 

1,030 

1,400,000 

Construction 

1,095 

1,255 

1.365 

1,500,000 

Standard 

605 

695 

755 

1,400,000 

Utilitv 

290 

330 

360 

1,300,000 

Select  Structural 

2"x  6" 

1,945 

2,235 

2,430 

1 ,900,000 

No.  1/No.  2 

1,235 

1,420 

1,540 

1,600,000 

No.  3 

710 

815 

890 

1,400,000 

Stud 

750 

860 

935 

1,400,000 

Select  Structural 

2"  x  8" 

1,795 

2,065 

2,245 

1 ,900,000 

No.  1/No.  2 

1,140 

1,310 

1,425 

1,600,000 

No.  3 

655 

755 

820 

1,400,000 

Select  Structural 

2"x  10" 

1,645 

1,890 

2,055 

1 ,900,000 

No.  1/  No.  2 

1,045 

1,200 

1.305 

1 ,600,000 

No.  3 

600 

690 

750 

1 ,400,000 

Select  Structural 

2"x  12" 

1,495 

1,720 

1,870 

1,900,000 

No.  1/No.  2 

950 

1,090 

1,185 

1,600,000 

No.  3 

545 

630 

685 

1,400,000 

DOUGLAS  FIR  -  SOUTH 

Select  Structural 

2"x4" 

2,245 

2,580 

2,805 

1 ,400,000 

Western 

Wood 

Products 

Association 

(See  footnotes  1 
and  2) 

No.  1 

1,555 

1,785 

1,940 

1,300,000 

No.  2 

1.425 

1,635 

1,780 

1,200,000 

No.  3 

820 

940 

1.025 

1,100,000 

Stud 

820 

945 

1,030 

1,100,000 

Construction 

1,065 

1,225 

1,330 

1 ,200,000 

Standard 

605 

695 

755 

1,100,000 

Utility 

290 

330 

360 

1,000,000 

Select  Structural 

2"  x  6" 

1,945 

2,235 

2,430 

1,400,000 

No.  1 

1.345 

1,545 

1.680 

1,300,000 

No.  2 

1.235 

1,420 

1.540 

1 ,200,000 

No.  3 

710 

815 

890 

1,100,000 

Stud 

750 

860 

935 

1.100,000 

Select  Structural 

2"  x  8" 

1,795 

2.065 

2,245 

1 ,400,000 

No.  1 

1,240 

1,430 

1,555 

1,300,000 

No.  2 

1,140 

1.310 

1,425 

1,200,000 

No.  3 

655 

755 

820 

1,100,000 

EASTERN  SOFTWOODS 

Select  Structural 

2"  x  4" 

2.155 

2,480 

2,695 

1,200,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2 

No.  1 

1,335 

1,535 

1,670 

1.100,000 

No.  2 

990 

1,140 

1,240 

1,100,000 

No.  3 

605 

695 

755 

900.000 

Stud 

570 

655 

710 

900,000 

Construction 

775 

895 

970 

1.000,000 

Standard 

430 

495 

540 

900,000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


509 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3. Id  -  continued 
DESIGN  VALUES  FOR  DLMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "/T>" 

MODULUS 

OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Utility 

2"  x  4" 

200 

230 

250 

800,000 

Select  Structural 

2"x  6"' 

1.S70 

2,150 

2,335 

1,200,000 

Northeastern 

Lumber 

Manufacturers 

Association 

Northern 
Softwood 
Lumber 
Bureau 

(See  Footnotes 
1  and  2) 

No.  1 

1.160 

1,330 

1.450 

1,100.000 

No.  2 

860 

990 

1,075 

1,100.000 

No.  3 

525 

600 

655 

900,000 

Stud 

520 

595 

645 

900.000 

Select  Structural 

2"  x  8" 

1.725 

1,985 

2,155 

1,200.000 

No.  1 

1.070 

1,230 

1.335 

1,100.000 

No.  2 

795 

915 

990 

1,100,000 

No.  3 

485 

555 

605 

900,000 

Select  Structural 

2"x  10" 

1.580 

1.820 

1.975 

1,200.000 

No   1 

980 

1.125 

1.225 

1.100,000 

No.  2 

725 

835 

910 

1.100.000 

No.  3 

445 

510 

555 

900.000 

Select  Structural 

2"x  12" 

1,440 

1,655 

1.795 

1 .200,000 

No  1 

890 

1,025 

1,115 

1,100.000 

No.  2 

660 

760 

825 

1,100.000 

No.  3 

405 

465 

505 

900.000 

EASTERN  WHITE  PINE 

Select  Structural 

2"  x  4" 

2.155 

2.480 

2,695 

1.200.000 

Northeastern 

Lumber 
Manufacturers 
Association 

Northern 
Softwood 

Lumber 
Bureau 

(See  Footnotes 
1  and  2) 

No   ! 

1.335 

1.535 

1.670 

1.100.000 

No.  2 

990 

1,140 

1.240 

1.100.000 

No.  3 

605 

695 

755 

900.000 

Stud 

570 

655 

710 

900.000 

Construction 

775 

895 

970 

1.000.000 

Standard 

430 

495 

540 

900.000 

Utility 

200 

230 

250 

800.000 

Select  Structural 

2"  x  6" 

1.870 

2.150 

2,335 

1,200,000 

No.  1 

1.160 

1,330 

1.450 

1.100.000 

No.  2 

860 

990 

1.075 

1.100.000 

No  3 

525 

600 

655 

900.000 

Stud 

520 

595 

645 

900.000 

Select  Structural 

2"  x  8" 

1.725 

1.985 

2.155 

1,200.000 

No.  1 

1,070 

1.230 

1,335 

1.100,000 

No.  2 

795 

915 

990 

1,100.000 

No.  3 

485 

555 

605 

900.000 

Select  Structural 

2"x  10" 

1,580 

1.820 

1.975 

1.200.000 

No.  1 

980 

1.125 

1.225 

1,100.000 

No.  2 

725 

835 

910 

1,100.000 

No.  3 

445 

510 

555 

900.000 

Select  Structural 

2"xl2" 

1,440 

1.655 

1,795 

1.200.000 

No  1 

890 

1,025 

1,115 

1.100.000 

No.  2 

660 

760 

825 

1,100.000 

No.  3 

405 

465 

505 

900,000 

HEM  -  FTR 

Select  Structural 

2"  x  4" 

2,415 

2.775 

3,020 

1 ,600.000 

No.  1  &  Btr 

1,810 

2,085 

2,265 

1 .500.000 

No.  1 

1.640 

1,885 

2.050 

1 ,500,000 

No.  2 

1.465 

1,685 

1 .835 

1.300.000 

510 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Ft" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

No.  3 

2"  x  4" 

865 

990 

1,080 

1,200,000 

West  Coast 
Lumber 

Inspection 
Bureau 

Western 

Wood 

Products 

Association 

(See  Footnotes 
1  and  2) 

Stud 

855 

980 

1,065 

1,200,000 

Construction 

1,120 

1,290 

1,400 

1,300,000 

Standard 

635 

725 

790 

1,200.000 

Utility 

290 

330 

360 

1,100,000 

Select  Structural 

2"x  6" 

2,095 

2,405 

2,615 

1,600,000 

No.  1  &  Bo- 

1,570 

1,805 

1,960 

1,500,000 

No.  1 

1,420 

1,635 

1,775 

1,500,000 

No.  2 

1.270 

1,460 

1,590 

1,300,000 

No.  3 

750 

860 

935 

1,200,000 

Stud 

775 

895 

970 

1,200,000 

Select  Structural 

2"  x  8" 

1,930 

2,220 

2,415 

1,600,000 

No.  &  Bu- 

1,450 

1,665 

1,810 

1,500,000 

No.  1 

1,310 

1,510 

1,640 

1,500,000 

No.  2 

1,175 

1,350 

1,465 

1.300,000 

No.  3 

690 

795 

865 

1,200,000 

Select  Structural 

2"  x  10" 

1,770 

2,035 

2,215 

1,600,000 

No.  1  &  Btr 

1,330 

1,525 

1,660 

1,500,000 

No.  1 

1,200 

3,380 

1,500 

1,500,000 

No.  2 

1,075 

1,235 

1,345 

1,300,000 

No.  3 

635 

725 

790 

1,200,000 

Select  Structural 

2"xl2" 

1,610 

1,850 

2,015 

1,600,000 

No.  1  &  Btr 

1,210 

1,390 

1,510 

1,500,000 

No.  1 

1,095 

1,255 

1,365 

1,500,000 

No.  2 

980 

1,125 

1,220 

1,300,000 

No.  3 

575 

660 

720 

1,200,000 

HEJ 

A-Y!R  (NORTH) 

Select  Structural 

2"  x  4" 

2,245 

2,580 

2,805 

1,700,000 

National 
Lumber 
Grades 

Authority 

(See  Footnotes 
1  and  2) 

No.  l/No.2 

1,725 

1,985 

2,155 

1,600,000 

No.  3 

990 

1,140 

1,240 

1,400,000 

Stud 

980 

1,125 

1,225 

1,400,000 

Construction 

1,325 

1,520 

1,655 

1,500,000 

Standard 

720 

825 

900 

1,400,000 

Utility 

345 

395 

430 

1,300,000 

Select  Structural 

2"x  6" 

1,945 

2,235 

2,430 

1,700,000 

No.  1/No.  2 

1,495 

1,720 

1,870 

1,600,000 

No.  3 

860 

990 

1,075 

1,400,000 

Stud 

890 

1,025 

1,115 

1,400,000 

Select  Structural 

2"  x  8" 

1,795 

2,065 

2,245 

1,700,000 

No.  1/No.  2 

1,380 

1,585 

1,725 

1,600,000 

No.  3 

795 

915 

990 

1,400,000 

Select  Structural 

2"x  10" 

l',645 

1,890 

2,055 

1,700,000 

No.  1/  No.  2 

1,265 

1,455 

1,580 

1.600,000 

No.  3 

725 

835 

910 

1,400,000 

9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


511 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"xl2" 

1,495 

1,720 

1,870 

1,700,000 

No.  l/No.2 

1,150 

1,325 

1,440 

1 ,600,000 

No.  3 

660 

760 

825 

1,400,000 

MIXED  MAPLE 

Select  Structural 

2"  x  4" 

1,725 

1,985 

2,155 

1,300,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,250 

1,440 

1,565 

1,200,000 

No.  2 

1,210 

1,390 

1,510 

1,100,000 

No.  3 

690 

795 

865 

1,000,000 

Stud 

695 

800 

870 

1,000,000 

Construction 

920 

1,060 

1,150 

1,100,000 

Standard 

520 

595 

645 

1,000,000 

Utility- 

260 

300 

325 

900,000 

Select  Structural 

2"x  6" 

1,495 

1,720 

1,870 

1,300,000 

No.  1 

1,085 

1,245 

1,355 

1,200,000 

No.  2 

1,045 

1,205 

1,310 

1,100,000 

No.  3 

600 

690 

750 

1,000,000 

Stud 

635 

725 

790 

1,000,000 

Select  Structural 

2*'x8" 

1,380 

1,585 

1,725 

1,300,000 

No.  1 

1,000 

1,150 

1,250 

1,200,000 

No.  2 

965 

1,110 

1,210 

1,100,000 

No.  3 

550 

635 

690 

1,000,000 

Select  Structural 

2"x  10" 

1,265 

1,455 

1,580 

1,300,000 

No.  1 

915 

1,055 

1,145 

1,200,000 

No.  2 

885 

1,020 

1,105 

1,100,000 

No.  3 

505 

580 

635 

1,000,000 

Select  Structural 

2"xl2" 

1,150 

1,325 

1,440 

1,300,000 

No.  1 

835 

960 

1,040 

1,200,000 

No.  2 

805 

925 

1,005 

1,100,000 

No.  3 

460 

530 

575 

1,000,000 

MIXED  OAK 

Select  Structural 

2"  x  4" 

1,985 

2,280 

2,480 

1,100,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,425 

1,635 

1,780 

1,000,000 

No.  2 

1,380 

1,585 

1,725 

900,000 

No.  3 

820 

940 

1,025 

800,000 

Stud 

790 

910 

990 

800,000 

Construction 

1,065 

1,225 

1,330 

900,000 

Standard 

605 

695 

755 

800,000 

Utility' 

290 

330 

360 

800,000 

Select  Structural 

2"x  6" 

1,720 

1,975 

2,150 

1,100,000 

No.  1 

1,235 

1,420 

1,540 

1 ,000,000 

No.  2 

1,195 

1,375 

1,495 

900,000 

No.  3 

710 

815 

890 

800,000 

Stud 

720 

825 

900 

800,000 

Select  Structural 

2"  x  8" 

1,585 

1,825 

1,985 

1,100,000 

No.  1 

1,140 

1,310 

1,425 

1,000,000 

No.  2 

1,105 

1,270 

1,380 

900,000 

No.  3 

655 

755 

820 

800,000 

512 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "iT>" 

MODULUS 
OF  ELASTICITY 

»E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"x  10" 

1,455 

1,675 

1,820 

1,100,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,045 

1,200 

1,305 

1,000,000 

No.  2 

1,010 

1,165 

1,265 

900,000 

No.  3 

600 

690 

750 

800,000 

Select  Structural 

2"xl2" 

1,325 

1,520 

1,655 

1,100,000 

No.  1 

950 

1,090 

1,185 

1,000,000 

No.  2 

920 

1,060 

1,150 

900,000 

No.  3 

545 

630 

685 

800,000 

MIXED  SOUTHERN  PINE 

Select  Structural 

2"  x  4" 

2,360 

2,710 

2,945 

1 ,600,000 

Southern 

Pine 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,670 

1,920 

2,085 

1,500,000 

No.  2 

1,495 

1,720 

1,870 

1,400,000 

No.  3 

865 

990 

1,080 

1,200,000 

Stud 

890 

1,025 

1,115 

1,200,000 

Construction 

1,150 

1,325 

1,440 

1,300,000 

Standard 

635 

725 

790 

1,200,000 

Utility 

315 

365 

395 

1,100,000 

Select  Structural 

2"x  6" 

2,130 

2,445 

2,660 

1,600,000 

No.  1 

1,495 

1,720 

1,870 

1,500,000 

No.  2 

1,325 

1,520 

1,655 

1 .400,000 

No.  3 

775 

895 

970 

1,200,000 

Stud 

775 

895 

970 

1,200,000 

Select  Structural 

2"  x  8" 

2,015 

2,315 

2.515 

1,600,000 

No.  1 

1,380 

1,585 

1,725 

1.500,000 

No.  2 

1,210 

1,390 

1,510 

1 .400,000 

No.  3 

720 

825 

900 

1,200,000 

Select  Structural 

2"x  10" 

1,725 

1,985 

2,155 

1,600,000 

No.  1 

1,210 

1,390 

1,510 

1,500,000 

No.  2 

1,065 

1,225 

1,330 

1,400,000 

No.  3 

605 

695 

755 

1 ,200,000 

Select  Structural 

2"xl2" 

1,610 

1,850 

2,015 

1,600,000 

No.  1 

1,120 

1,290 

1,400 

1,500,000 

No.  2 

1,005 

1,155 

1,260 

1 ,400,000 

No.  3 

575 

660 

720 

1 ,200,000 

NORTHERNRED  OAK 

Select  Structural 

2"  x  4" 

2,415 

2,775 

3,020 

1 ,400,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,725 

1,985 

2,155 

1,400,000 

No.  2 

1,680 

1,935 

2,100 

1 .300,000 

No.  3 

950 

1,090 

1,185 

1,200,000 

Stud 

950 

1,090 

1,185 

1,200,000 

Construction 

1,265 

1,455 

1,580 

1,200,000 

Standard 

720 

825 

900 

1,100,000 

Utility 

345 

395 

430 

1,000,000 

Select  Structural 

2"x  6" 

2,095 

2.405 

2,615 

1,400,000 

No.  1 

1,495 

1,720 

1,870 

1 .400,000 

No.  2 

1,460 

1,675 

1,820 

1 .300,000 

No.  3 

820 

945 

1,030 

1,200,000 

Stud 

865 

990 

1,080 

1,200,000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


513 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3. Id  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  »Fb" 

MODULUS 
OF  ELASTICITY 

«E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"  x  8" 

1,930 

2,220 

2,415 

1,400,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,380 

1,585 

1,725 

1,400,000 

No.  2 

1,345 

1,545 

1,680 

1,300,000 

No.  3 

760 

875 

950 

1,200,000 

Select  Structural 

2"x  10" 

1,770 

2,035 

2,215 

1,400,000 

No.  1 

1,265 

1,455 

1,580 

1,400,000 

No.  2 

1,235 

1,420 

1,540 

1,300,000 

No.  3 

695 

800 

870 

1,200,000 

Select  Structural 

2"x  12" 

1,610 

1,850 

2,015 

1 ,400,000 

No.  1 

1,150 

1,325 

1,440 

1,400,000 

No.  2 

1,120 

1,290 

1,400 

1,300,000 

No.  3 

635 

725 

790 

1,200,000 

NORTHERN  SPECIES 

Select  Structural 

2"  x  4" 

1,640 

1,885 

2,050 

1,100,000 

National 
Lumber 
Grades 
Authority 

(See  Footnotes 
1  and  2) 

No.  l/No.2 

990 

1,140 

1,240 

1,100,000 

No.  3 

605 

695 

755 

1,000,000 

Stud 

570 

655 

710 

1 ,000,000 

Construction 

775 

895 

970 

1,000,000 

Standard 

430 

495 

540 

900,000 

Utility 

200 

230 

250 

900,000 

Select  Structural 

2"x  6" 

1,420 

1,635 

1,775 

1,100.000 

No.  1/No.  2 

860 

990 

1,075 

1,100,000 

No.  3 

525 

600 

655 

1,000,000 

Stud 

520 

595 

645 

1 ,000,000 

Select  Structural 

2"  x  8" 

1,310 

1,510 

1,640 

1,100,000 

No.  1/No.  2 

795 

915 

990 

1,100,000 

No.  3 

485 

555 

605 

1,000,000 

Select  Structural 

2"x  10" 

1,200 

1,380 

1,500 

1,100,000 

No.  1/  No.  2 

725 

835 

910 

1,100,000 

No.  3 

445 

510 

555 

1 ,000,000 

Select  Structural 

2"x  12" 

1,095 

1.255 

1,365 

1,100,000 

No.  1/No.  2 

660 

760 

825 

1,100,000 

No.  3 

405 

465 

505 

1 ,000,000 

NORTHERN  WHITE  CEDAR 

Select  Structural 

2"  x  4" 

1,335 

1,535 

1,670 

800,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

990 

1,140 

1,240 

700,000 

No.  2 

950 

1,090 

1,185 

700,000 

No.  3 

560 

645 

700 

600,000 

Stud 

540 

620 

670 

600,000 

Construction 

720 

825 

900 

700,000 

Standard 

405 

465 

505 

600,000 

Utility 

200 

230 

250 

600.000 

Select  Structural 

2"x  6" 

1.160 

1,330 

1,450 

800,000 

No   1 

860 

990 

1,075 

700,000 

No.  2 

820 

945 

1,030 

700,000 

No.  3 

485 

560 

605 

600,000 

Stud 

490 

560 

610 

600.000 

514 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"  x  8" 

1,070 

1,230 

1,335 

800,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

795 

915 

990 

700,000 

No.  2 

760 

875 

950 

700,000 

No  3 

450 

515 

560 

600,000 

Select  Structural 

2"x  10" 

980 

1,125 

1,225 

800,000 

No.  1 

725 

835 

910 

700,000 

No.  2 

695 

800 

870 

700,000 

No.  3 

410 

475 

515 

600,000 

Select  Structural 

2"xl2" 

890 

1,025 

1,115 

800,000 

No.  1 

660 

760 

825 

700,000 

No.  2 

635 

725 

790 

700,000 

No.  3 

375 

430 

465 

800,000 

RED  MAPLE 

Select  Structural 

2"  x  4" 

2,245 

2,580 

2,805 

1,700,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,595 

1,835 

1,995 

1,600,000 

No.  2 

1,555 

1,785 

1,940 

1,500,000 

No.  3 

905 

1.040 

1,130 

1,300,000 

Stud 

885 

1,020 

1,105 

1.300.000 

Construction 

1.210 

1,390 

1,510 

1 ,400.000 

Standard 

660 

760 

825 

1,300.000 

Utility 

315 

365 

395 

1,200,000 

Select  Structural 

2"x  6" 

1,945 

2,235 

2,430 

1,700.000 

No.  1 

1.385 

1,590 

1,730 

1,600,000 

No.  2 

1,345 

1,545 

1,680 

1,500,000 

No.  3 

785 

905 

980 

1,300,000 

Stud 

805 

925 

1,005 

1,300,000 

Select  Structural 

2"  x  8" 

1,795 

2,065 

2.245 

1,700,000 

No.  1 

1,275 

1,470 

1,595 

1,600,000 

No.  2 

1,240 

1,430 

1.555 

1,500,000 

No.  3 

725 

835 

905 

1 ,300,000 

Select  Structural 

2"x  10" 

1,645 

1,890 

2.055 

1,700,000 

No.  1 

1.170 

1,345 

1.465 

1,600,000 

No.  2 

1,140 

1,310 

1,425 

1,500,000 

No.  3 

665 

765 

830 

1,300.000 

Select  Structural 

2"x  12" 

1,495 

1,720 

1.870 

1,700,000 

No.  1 

1,065 

1,225 

1,330 

1,600,000 

No.  2 

1,035 

1,150 

1,295 

1,500.000 

No.  3 

605 

695 

755 

1,300,000 

RED  OAK 

Select  Structural 

2"  x  4" 

1,985 

2,280 

2.480 

1,400,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,425 

1,635 

1,780 

1,300,000 

No.  2 

1,380 

1,585 

1,725 

1,200,000 

No.  3 

820 

940 

1,025 

1.100,000 

Stud 

790 

910 

990 

1,100.000 

Construction 

1,065 

1,225 

1.330 

1 ,200,000 

Standard 

605 

695 

755 

1,100,000 

Utility 

290 

330 

360 

1.000,000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


515 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"x  6" 

1,720 

1,975 

2,150 

1,400,000 

Northeastern 

Lumber 

Manufacturers 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,235 

1,420 

1,540 

1,300,000 

No.  2 

1,195 

1,375 

1,495 

1,200,000 

No.  3 

710 

815 

890 

1,100,000 

Stud 

720 

825 

900 

1,100,000 

Select  Structural 

2"  x  8" 

1,585 

1,825 

1,985 

1 ,400,000 

No.  1 

1,140 

1,310 

1,425 

1,300,000 

No.  2 

1,105 

1,270 

1,380 

1,200,000 

No.  3 

655 

755 

820 

1.100,000 

Select  Structural 

2"x  10" 

1,455 

1.675 

1,820 

1,400,000 

No.  1 

1,045 

1.200 

1,305 

1,300,000 

No.  2 

1,010 

1,165 

1,265 

1 ,200,000 

No.  3 

600 

690 

750 

1,100,000 

Select  Structural 

2"xl2" 

1,325 

1,520 

1,655 

1 ,400,000 

No.  1 

950 

1,090 

1,185 

1 ,300,000 

No.  2 

920 

1,060 

1,150 

1,200,000 

No.  3 

545 

630 

685 

1,100,000 

REDWOOD 

Clear  Structural 

2"  x  4" 

3,020 

3,470 

3,775 

1 ,400,000 

Redwood 

Inspection 

Service 

(See  Footnotes  1 
and  2) 

Select  Structural 

2,330 

2,680 

2,910 

1,400,000 

Select  Structural,  open 
grain 

1,900 

2,180 

2,370 

1,100,000 

No.  1 

1,680 

1,935 

2,100 

1,300,000 

No.  1 ,  open  grain 

1,335 

1,535 

1,670 

1,100,000 

No.  2 

1,595 

1,835 

1,995 

1,200,000 

No.  2,  open  grain 

1,250 

1,440 

1,565 

1,000,000 

No.  3 

905 

1,040 

1,130 

1,100,000 

No.  3,  open  grain 

735 

845 

915 

900,000 

Stud 

725 

835 

910 

900,000 

Construction 

950 

1,090 

1,185 

900,000 

Standard 

520 

595 

645 

900,000 

Utilitv 

260 

300 

325 

800,000 

Clear  Structural 

2"x6" 

2,615 

3,010 

3,270 

1,400,000 

Select  Structural 

2,020 

2,320 

2,525 

1,400,000 

Select  Structural,  open 
grain 

1,645 

1,890 

2,055 

1,100,000 

No.  1 

1,460 

1.675 

1,820 

1,300,000 

No.  1 ,  open  grain 

1.160 

1.330 

1,450 

1,100,000 

No.  2 

1,385 

1,590 

1,730 

1,200,000 

No.  2,  open  grain 

1,085 

1,245 

1.355 

1,000,000 

No.  3 

785 

905 

980 

1,100,000 

No.  3,  open  grain 

635 

730 

795 

900,000 

Stud 

660 

760 

825 

900,000 

Clear  Structural 

2"  x  8" 

2,415 

2,775 

3,020 

1,400,000 

Select  Structural 

1,865 

2,140 

2.330 

1,400,000 

Select  Structural,  open 
grain 

1,520 

1,745 

1,900 

1,100,000 

No.  1 

1,345 

1,545 

1,680 

1,300,000 

No.  1 ,  open  grain 

1.070 

1,230 

1,335 

1,100.000 

No.  2 

1.275 

1,470 

1,595 

1.203,000 

516 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 

TABLE  3605.2.3.1d  -  continued 


DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 

SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

No.  2,  open  grain 

2"x  8" 

1,000 

1,150 

1,250 

1,000,000 

No.  3 

725 

835 

905 

1,100,000 

No.  3,  open  grain 

585 

675 

735 

900,000 

Clear  Structural 

2"x  10" 

2,215 

2,545 

2,765 

1 ,400,000 

Select  Structural 

1,710 

1,965 

2,135 

1,400,000 

Select  Structural,  open 
grain 

1,390 

1,600 

1,740 

1,100,000 

No.  1 

1,235 

1,420 

1,540 

1,300,000 

No.  1 ,  open  grain 

980 

1,125 

1,225 

1,100,000 

No.  2 

1.170 

1,345 

1,465 

1,200,000 

Redwood 

Inspection 

Service 

(See  Footnotes  1 
and  2) 

No.  2,  open  gram 

915 

1,055 

1,145 

1,000,000 

No.  3 

665 

765 

830 

1,100,000 

No.  3,  open  grain 

540 

620 

670 

900,000 

Clear  Structural 

2"xl2" 

2,015 

2,315 

2,515 

1,400,000 

Select  Structural 

1,555 

1,785 

1,940 

1,400,000 

Select  Structural,  open 
grain 

1,265 

1,455 

1,580 

1.100,000 

No.  1 

1,120 

1,290 

1,400 

1,300,000 

No.  1 ,  open  gram 

890 

1,025 

1,115 

1,100,000 

No.  2 

1,065 

1,225 

1,330 

1,200,000 

No.  2,  open  grain 

835 

960 

1,040 

1,000,000 

No.  3 

605 

695 

755 

1,100,000 

No.  3,  open  grain 

490 

560 

610 

900,000 

SOUTHERN.  PINE 

Dense  Select  Structural 

2"  x  4" 

3.510 

4,035 

4,385 

1,900,000 

Southern 

Pine 

Inspection 

Bureau 

(See  Footnotes 
1  and  2) 

Select  Strcrural 

3,280 

3,770 

4,095 

1,800,000 

Non  -  Dense  Select 
Structural 

3,050 

3,505 

3,810 

1,700,000 

No.  1  Dense 

2.300 

2,645 

2,875 

1,800,000 

No.  1 

2,130 

2,445 

2,660 

1 ,700,000 

No.  1  Non  -  Dense 

1,955 

2,250 

2,445 

1 ,600,000 

No.  2  Dense 

1,955 

2,250 

2,445 

1,700,000 

No.  2 

1,725 

1,985 

2,155 

1,600,000 

No.  2  Non  -  Dense 

1,555 

1,785 

1,940 

1,400,000 

No.  3 

980 

1,125 

1,220 

1 ,400,000 

Stud 

1,005 

1,155 

1,260 

1,400,000 

Constrction 

1,265 

1,455 

1,580 

1,500,000 

Standard 

720 

825 

900 

1 ,300,000 

Utility 

345 

395 

430 

1,300,000 

Dense  Select  Structural 

2"x  6" 

3,105 

3,570 

3,880 

1,900,000 

Select  Structural 

2.935 

3.370 

3,665 

1 ,800.000 

Non  -  Dense  Select 
Structural 

2,705 

3,110 

3,380 

1,700,000 

No.  1  Dense 

2,015 

2,315 

2,515 

1,800,000 

No.  1 

1,900 

2,180 

2,370 

1 ,700.000 

No.  1  Non  -  Dense 

1.725 

1,985 

2,155 

1 ,600,000 

No.  2  Dense 

1,670 

1,920 

2,085 

1 ,700,000 

No.  2 

1,440 

1,655 

1,795 

1 ,600,000 

No  2  Non  -  Dense 

1.325 

1,520 

1.655 

1 ,400.000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


517 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

No.  3 

2"  x  6" 

865 

990 

1,080 

1,400,000 

Southern 

Pine 

Inspection 

Bureau 

(See  Footnotes 
1  and  2) 

Stud 

890 

1,025 

1,115 

1,400,000 

Dense  Select  Structural 

2"  x  8" 

2,820 

3,240 

3,520 

1,900,000 

Select  Structural 

2,645 

3,040 

3,305 

1,800,000 

Non  -  Dense  Select 
Structural 

2,415 

2,775 

3,020 

1,700,000 

No.  1  Dense 

1,900 

2,180 

2,370 

1,800,000 

No.  1 

1,725 

1,985 

2,155 

1,700,000 

No.  1  Non  -  Dense 

1,555 

1,785 

1,940 

1,600,000 

No.  2  Dense 

1,610 

1,850 

2.015 

1,700,000 

No.  2 

1,380 

1,585 

1,725 

1,600,000 

No.  2  Non  -  Dense 

1,265 

1,455 

1,580 

1,400,000 

No.  3 

805 

925 

1,005 

1,400,000 

Dense  Select  Structural 

2"x  10" 

2.475 

2,845 

3,090 

1,900,000 

Select  Structural 

2,360 

2,710 

2.945 

1 .800,000 

Non  -  Dense  Select 
Structural 

2,130 

2,445 

2,660 

1,700,000 

No.  1  Dense 

1,670 

1,920 

2.085 

1,800,000 

No.  1 

1,495 

1,720 

1,870 

1,700,000 

No.  1  Non  -  Dense 

1,380 

1,585 

1,725 

1 ,600,000 

No.  2  Dense 

1,380 

1,585 

1,725 

1,700,000 

No.  2 

1,210 

1,390 

1,510 

1,600,000 

No.  2  Non  -  Dense 

1,095 

1.255 

1,365 

1,400,000 

No.  3 

690 

795 

865 

1,400,000 

Dense  Select  Structural 

2"xl2" 

2,360 

2,710 

2,945 

1,900,000 

Select  Structural 

2,185 

2,515 

2,730 

1,800,000 

Non  -  Dense  Select 
Structural 

2,015 

2,315 

2,515 

1,700,000 

No.  1  Dense 

1,555 

1,785 

1,940 

1,800,000 

No.  1 

1,440 

1,655 

1,795 

1 ,700,000 

No.  1  Non  -  Dense 

1,325 

1,520 

1,655 

1,600  000 

No.  2  Dense 

1,325 

1,520 

1,655 

1,700,000 

No.  2 

1,120 

1,290 

1,400 

1,600,000 

No.  2  Non  -  Dense 

1,035 

1,190 

1,295 

1,400,000 

No.  3 

660 

760 

825 

1,400,000 

SPRUCE -PINE -FIR 

Select  Structural 

2"  x  4" 

2,155 

2,480 

2,695 

1,500,000 

National 

Lumber 
Grades 
Authority 

(See  Footnotes 
1  and  2) 

No.  1/No.  2 

1,510 

1,735 

1,885 

1,400,000 

No.  3 

865 

990 

1,080 

1.200,000 

Stud 

855 

980 

1,065 

1.200,000 

Construction 

1,120 

1,290 

1,400 

1 ,300,000 

Standard 

635 

725 

790 

1,200,000 

Utility 

290 

330 

360 

1,100,000 

Select  Structural 

2"x  6" 

1,870 

2,150 

2.335 

1 ,500,000 

No.  1/No.  2 

1,310 

1,505 

1.635 

1 ,400,000 

No.  3 

750 

860 

935 

1 ,200,000 

Stud 

775 

895 

970 

1 ,200,000 

518 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  " Fb" 

MODULUS 

OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Select  Structural 

2"  x  8" 

1,725 

1,985 

2,155 

1,500,000 

National 
Lumber 
Grades 
Authority 

(See  Footnotes 
1  and  2) 

No.  1/No.  2 

1.210 

1,390 

1,510 

1 ,400,000 

No.  3 

690 

795 

865 

1 .200,000 

Select  Structural 

2"x  10" 

1,580 

1,820 

1.975 

1.500.000 

No.  1/  No.  2 

1,105 

1,275 

1.385 

1,400.000 

No.  3 

635 

725 

790 

1,200,000 

Select  Structural 

2"x  12" 

1,440 

1,655 

1,795 

1.500,000 

No.  1  /  No.  2 

1.005 

1,155 

1,260 

1,400,000 

No.  3 

575 

660 

720 

1,200,000 

No  3 .  open  grain 

540 

620 

670 

900,000 

SPRUCE  -  PINE  -  FIR  (SOUTH) 

Select  Structural 

2"  x  4" 

2,245 

2,580 

2,805 

1,300,000 

Northeastern 

Lumber 

Manufacturers 

Association 

Northern 
Softwood 
Lumber 
Bureau 

West  Coast 
Lumber 

Inspection 
Bureau 

Western 

Woods 

Products 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,465 

1,685 

1,835 

1 .200,000 

No.  2 

1,295 

1,400 

1,615 

1,100,000 

No.  3 

735 

845 

915 

1 ,000.000 

Stud 

725 

835 

910 

1 ,000,000 

Construction 

980 

1,125 

1.220 

1 ,000,000 

Standard 

545 

630 

685 

900,000 

Utility 

260 

300 

335 

900,000 

Select  Structural 

2"x  6" 

1,045 

2,235 

2,430 

1,300,000 

No.  1 

1,270 

1,460 

1,590 

1.200,000 

No.  2 

1,120 

1.290 

1.400 

1,100,000 

No.  3 

635 

730 

795    . 

1 ,000,000 

Stud 

660 

760 

825 

1,000,000 

Select  Structural 

2"  x  8" 

1,795 

2,065 

2,245 

1 .300.000 

No.  1 

1.175 

1,350 

1,465 

1,200.000 

No.  2 

1,035 

1,190 

1.295 

1,100,000 

No.  3 

585 

675 

735 

1.000,000 

Select  Structural 

2"x  10" 

1.645 

1,890 

2.055 

1,300,000 

No.  1 

1,075 

1.235 

1.345 

1 ,200,000 

No  2 

950 

1,090 

1.185 

1,100.000 

No.  3 

540 

620 

670 

1 ,000,000 

Select  Structural 

2"x  12" 

1,495 

1,720 

1,870 

1,300,000 

No.  1 

980 

1.125 

1,220 

1.200,000 

No.  2 

865 

990 

1,080 

1.100,000 

No.  3 

490 

560 

610 

1.000.000 

WESTERN  CEDARS 

Select  Structural 

2"  x  4" 

1 ,725 

1,985 

2.155 

1,100,000 

West  Coast 
Lumber 

Inspection 
Bureau 

Western 

Woods 

Products 

Association 

(See  Footnotes 
1  and  2) 

No   1 

1,250 

1,440 

1,565 

1,000.000 

No.  2 

1,210 

1,390 

1,510 

1 ,000,000 

No.  3 

690 

795 

865 

900,000 

Stud 

695 

800 

870 

900,000 

Construction 

920 

1,060 

1,150 

900,000 

Standard 

520 

595 

645 

800.000 

Utility 

260 

300 

325 

800,000 

Select  Structural 

2"x  6" 

1,495 

1.720 

1,870 

1,100,000 

No.  1 

1,085 

1.245 

1,355 

1 ,000,000 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


519 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "Fb" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

No.  2 

2"  x  6" 

1,045 

1,205 

1,310 

1 ,000.000 

West  Coast 

Lumber 

Inspection 

Bureau 

Western 

Woods 

Products 

Association 

(See  Footnotes 
1  and  2) 

No.  3 

600 

690 

750 

900,000 

Stud 

635 

725 

790 

900,000 

Select  Structural 

2"  x  8" 

1,380 

1,585 

1,725 

1,100,000 

No.  1 

1,000 

1,150 

1.250 

1 ,000,000 

No.  2 

965 

1,110 

1,210 

1,000.000 

No.  3 

550 

635 

690 

900,000 

Select  Structural 

2"x  10" 

1,265 

1,455 

1,580 

1,100.000 

No.  1 

915 

1,055 

1,145 

1 ,000,000 

No.  2 

885 

1,020 

1,105 

1 .000.000 

No.  3 

505 

580 

635 

900,000 

Select  Structural 

2"x  12" 

1,150 

1,325 

■1 ,440 

1,100,000 

No.  1 

835 

960 

1,040 

1 ,000,000 

No.  2 

805 

925 

1,005 

1 ,000,000 

No.  3 

460 

530 

575 

900,000 

WESTERN  WOODS 

Select  Structural 

2"  x  4" 

1,150 

1,735 

1,885 

1 ,200,000 

West  Coast 

Lumber 

Inspection 

Bureau 

Western 

Woods 

Products 

Association 

(See  Footnotes 
1  and  2) 

No.  1 

1,120 

1,290 

1,400 

1,100,000 

No.  2 

1.120 

1,290 

1,400 

1 ,000,000 

No.  3 

645 

745 

810 

900,000 

Stud 

635 

725 

790 

900.000 

Construction 

835 

960 

1,040 

1 ,000.000 

Standard 

460 

530 

575 

900,000 

Utility 

230 

265 

290 

800,000 

Select  Structural 

2"x  6" 

1.310 

1.505 

1,635 

1 ,200.000 

No.  1 

970 

1,120 

1,215 

1,100,000 

No.  2 

970 

1.120 

1,215 

1 ,000,000 

No.  3 

560 

645 

700 

900,000 

Stud 

575 

660 

720 

900,000 

Select  Structural 

2"  x  8" 

1,210 

1.390 

1,510 

1,200,000 

No.  1 

895 

1,030 

1.120 

1,100.000 

No  2 

895 

1,030 

1.120 

1 ,000,000 

No.  3 

520 

595 

645 

900,000 

Select  Structural 

2"x  10" 

1.105 

1,275 

1.385 

1 ,200,000 

No.  1 

820 

945 

1,030 

1,100,000 

No.  2 

820 

945 

1.030 

1 ,000,000 

No.  3 

475 

545 

595 

900,000 

Select  Structural 

2"x  12" 

1,005 

1.155 

1,260 

1,200.000 

No.  1 

750 

860 

935 

1.100.000 

No.  2 

750 

860 

935 

1 .000.000 

No  3 

430 

495 

540 

900.000 

WHITE  OAK 

Select  Structural 

2"  x  4" 

2,070 

2.380 

2,590 

1,100,000 

West  Coast 
Lumber 
Inspection 
Bureau 
Western 
Woods 
Products 
Association 

No.  1 

1,510 

1,735 

1,885 

1,000,000 

No.  2 

1,465 

1.685 

1,835 

900,000 

No.  3 

820 

940 

1,025 

800,000 

Stud 

820 

945 

1,030 

800.000 

Construction 

1 .095 

1,255 

1,365 

900,000 

520 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1d  -  continued 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  VISUAL  GRADING 


SPECIES  AND  GRADE 

SIZE 

NORMAL 
DURATION 

DESIGN  VALUE 
IN  BENDING  "FZ>" 

MODULUS 
OF  ELASTICITY 

"E" 

GRADING 

RULES 
AGENCY 

Snow  Loading 

7-Day  Loading 

Standard 

2"  x  4" 

605 

695 

755 

800,000 

West  Coast 

Lumber 

Inspection 

Bureau 

Western 

Woods 

Products 

Association 

(See  Footnotes 
1  and  2) 

Utility 

290 

330 

360 

800.000 

Select  Structural 

2"x  6" 

1,795 

2,065 

2,245 

1,100,000 

No.  1 

1,310 

1,505 

1,635 

1,000,000 

No.  2 

1,270 

1,460 

1.590 

900,000 

No.  3 

710 

815 

890 

800,000 

Stud 

750 

860 

935 

800,000 

Select  Structural 

2"  x  8" 

1,655 

1,905 

2,070 

1,100,000 

No.  1 

1,210 

1,390 

1,510 

1,000.000 

No.  2 

1,175 

1.350 

1.465 

900,000 

No.  3 

655 

755 

820 

800,000 

Select  Structural 

2"x  10" 

1,520 

1,745 

1.900 

1,100,000 

No.  1 

1,105 

1,275 

1.385 

1,000,000 

No.  2 

1,075 

1,235 

1,345 

900,000 

No.  3 

600 

690 

750 

800.000 

Select  Structural 

2"x  12" 

1.380 

1.585 

1,725 

1.100.000 

No.  1 

1.005 

1,155 

1,260 

1.000.000 

No.  2 

980 

1,125 

1,220 

900.000 

No  3 

545 

630 

685 

800,000 

YELLOW  POPLAR 

Select  Structural 

2"  x  4" 

1725 

1.985 

2,155 

1 ,500,000 

Northern 
Softwood 
Lumber 
Bureau 
(See  Footnotes 
1  and  2) 

No.  1 

1.250 

1.440 

1,565 

1 ,400,000 

No.  2 

1,210 

i.390 

1.510 

1,300,000 

No.  3 

690 

795 

865 

1 .200,000 

Stud 

695 

800 

870 

1,200,000 

Construction 

920 

1,060 

1,150 

1,300,000 

Standard 

520 

595 

645 

1,100,000 

Utility 

230 

265 

290 

1,100,000 

Select  Structural 

2"x  6" 

1,495 

!,720 

1,870 

1,500,000 

No.  1 

1.085 

1.245 

1,355 

1 ,400,000 

No.  2 

1.045 

1,205 

1,310 

1 ,300,000 

No.  3 

600 

690 

750 

1.200,000 

Stud 

635 

725 

790 

1,200,000 

Select  Structural 

2"xS" 

1,380 

1.585 

1,725 

1 ,500,000 

No.  1 

1,000 

1,150 

1,250 

1,400,000 

No.  2 

965 

1,110 

1,210 

1,300.000 

No.  3 

550 

635 

690 

1,200,000 

Select  Structural 

2"x  10" 

1.265 

1.455 

1.580 

1,500,000 

No.  1 

915 

1,055 

1,145 

1.400,000 

No.  2 

885 

1,020 

1,105 

1,300,000 

No.  3 

505 

580 

635 

1 ,200,000 

Select  Structural 

2"x  12'" 

1,150 

1,325 

1,440 

1,500,000 

No.  1 

835 

960 

1,040 

1.400.000 

No.  2 

805 

925 

1,005 

1.300,000 

No  .3 

460 

530 

575 

1,200,000 

For  SI:   1  inch  =  25.4  mm,  1  psi  =  6.895  kPa. 

1       When  dimension  lumber  is  used  where  moisture  content  will  exceed  19%  for  an  extended  tune  period,  Fb  shall  be 

multiplied  by  0  85  if  Fb  exceeds  1,150  psi,  andfshall  be  multiplied  by  0.9. 

2.     Following  is  a  list  of  agencies  certified  by  the  American  Lumber  Standards  Committee   Board  of  Review  (as  of 

1 99 1 )  for  inspection  and  grading  of  untreated  lumber  under  the  rules  indicated. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


521 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Rules  in  Writing  Agencies 

National  Lumber  Grades  Authority  (NLGA) 

260-1055  W.  Hastings  Street 

Vancouver,  BC  V6E  2E9 

Canada 
Northeastern  Lumber  Manufacturers  Association  (NELMA) 

272  Turtle  Road,  P.O.  Box  87A 

Cumberland  Center,  Maine  0402 1 
Northern  Softwood  Lumber  Bureau  (NSLB) 

272  Tuttle  Road,  P.O  Box  87A 

Cumberland  Center,  Maine  04021 
Redwood  Inspection  Service  (RIS) 

405  Enfrente  Drive,  Suite  200, 

Novato,  California  94949 

Southern  Pine  Inspection  Bureau  (SPIB) 

4709  Scenic  Highway, 

Pensacola,  Florida  32504 
West  Coast  Lumber  Inspection  Bureau  (WCLIB) 

6980  SW  Vames  Road,  P.O  Box  23 145 

Portland,  Oregon  97223 
Western  Wood  Products  Association  (WWPA) 
522  S.W.  5th  Avenue 
Yeon  Building,  Portland,  OR  97204 

Non-Rules  Writing  Agencies 

California  Lumber  Inspection  Services 

Pacific  Lumber  Inspection  Bureau,  Inc. 

Timber  Products  Inspection 

Alberta  Forest  Products  Association 

Canadian  Lumbermen's  Association 

Cariboo  Lumber  Manufacturers  Association 

Central  Forest  Products  Association 

Council  of  Forest  Industries  of  British  Columbia 

Interior  Lumber  Manufacturers  Association 

Macdonald  Inspection 

Maritime  Lumber  Bureau 

Ontario  Lumber  Manufacturers  Association 

Pacific  Lumber  Inspection  Bureau 

Quebec  Lumber  Manufacturers  Association 


Rules  for  which  grading  is  authorized 

NLGA 


NELMA  NLGA, 
WCLIB.  WWPA,  NLGA 

WSLB,  WCLIB. 
WWPA  NLGA 

RIS.WCLIB. 
WWPA 


SPIB.  NELMA, 
WCLIB,  WWPA  NLGA 


WCLIB.  RIS. 
WWPA  NLGA  SPIB 


WWPA  WCLIB. 
NLGA  RIS.  SPIB 


RIS,  WCLIB.  WWPA  NLGA  SPIB 

RIS.WCLIB.WWPA  NLGA 

RIS.  SPIB,  WCLIS.  WWPA 

NLGA 

NLGA  NELMA 

NLGA 

NLGA 

NLGA 

NLGA 

NLGAS 

NLGA  NELMA 

NLGA  NELMA 

NLGA 

NLGA  NELMA 


522 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.2.3.1e 
DESIGN  VALUES  FOR  DIMENSION  LUMBER  -  MACHINE  STRESS  RATED 


These  "Fb"  values  are  for  use  where  repetitive  members  are  spaced  not  more  than  24  inches     For  wider 
spacing,  the  "Fh"  values  should  be  reduced  13%.  Values  apply  at  19%  maximum  moisture  content  in  use. 

GRADE 
DESIGNATION 

GRADING  RULES 

AGENCY 

(See  Footnotes 

1.2,3.4) 

SIZE 
CLASSIFICATION 

DESIGN  VALUE  IN  BENDING  "Fb" 

MODULUS  OF 

ELASTICITY 

"E" 

Normal  Duration 

Snow 
Loading 

7-Day 
Loading 

900f.l.0£ 

3,4 

Machine 
rated 

lumber 
2X4 
and 
wider 

1,050 

1,210 

1,310 

1 ,000,000 

1200f.l.2£ 

1,2,3,4 

1,400 

1,610 

1,750 

1,200,000 

1350f.l.3£ 

2,4 

1,550 

1,780 

1,940 

1 .300,000 

I450f.l.3£ 

1,3,4 

1,650 

i,900 

2,060 

1.300,000 

1500f.l.3£ 

2 

1,750 

2,010 

2,190 

1.300,000 

1500f.l.4£ 

1,2,3,4 

1,750 

2,010 

2,190 

1 ,400,000 

1650f.l.4£ 

2 

1,900 

2,190 

2,370 

1,400,000 

I650f.l.6£ 

1,2,3.4 

1,900 

2,180 

2,380 

1,500,000 

I800f.l.6£ 

1,2,3,4 

2,050 

2,360 

2,560 

1 ,600,000 

1950f.l.5£ 

2 

2,250 

2,590 

2,810 

1 ,500,000 

1950f.I.7£ 

1,2,4 

2,250 

2,590 

2,810 

1700,000 

2100f.l.8£ 

1,2,3.4 

2,400 

2,760 

3,000 

1X00,1)00 

2250f.l.6£ 

2 

2,600 

2,990 

3,250 

1 ,600,000 

2250f.l.9£ 

1,2,4 

2,600 

2.990 

3,250 

1 ,900,000 

2400f.l.7£ 

2 

2,750 

3,160 

3,440 

1 ,700,000 

2400f.2.0  £ 

1,2,3,4 

2,750 

3,160 

3,440 

2,000,000 

2550f.2.1£ 

1,2,4 

2,950 

3,390 

3,690 

2,100,000 

2700f.2.2  £ 

1,2,3,4 

3,100 

3,570 

3,880 

2,200,000 

2850f.  2.3  £ 

2 

3,300 

3,800 

4,130 

2,300,000 

3000f.2.4  £ 

1,2 

3,450 

3,970 

4,310 

2,400,000 

3150f.2.5£ 

2 

3,600 

4,140 

4,500 

2,500,000 

3300f.  2.6  £ 

2 

3,800 

4,370 

4,750 

2,600,000 

900f.l.0£ 

1,2,3 

See 
Footnotes 

1,050 

1,210 

1,310 

1,000.000 

900f.l.2£ 

1,2,3 

1,050 

1,210 

1,310 

1,200,000 

1200f.l.5£ 

1,2,3 

1,400 

1,610 

1.750 

1,500,000 

1350f.l.8£ 

1,2 

1,550 

1780 

1,940 

1,800,000 

1500f.l.8£ 

3 

1,750 

2,010 

2,190 

"1,800,000 

1800f.2.1£ 

1,2,3 

2,050 

2,360 

2,560 

2,100,000 

For  SI:  1  inch  =  25.4  mm,l  psi  =  6.895kPa. 

Table  3605.2.3.  Id  footnotes  applicable  to  machine  stress  rated  joists  and  rafters 

1.  National  Lumber  Grades  Authority  (see  Footnote  2,  Table  3605.2.3.  lc);  Machine  Rated  Lumber,  2X4 
and  wider. 

2.  Southern  Pine  Inspection  Bureau;  Machine  Rated  Lumber,  2X4  and  wider 

3.  West  Coast  Lumber  Inspection  Bureau;  Machine  Rated  Lumber,  2X4  and  wider;  Machine  Rated  Joists, 
2X6  and  wider. 

4.  Western  Wood  Products  Association;  Machine  Rated  Lumber,  2X4  and  wider. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


523 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3605.2.3.3a 
ALLOWABLE  SPAN  FOR  GIRDERS  SUPPORTING  ONE  FLOOR  ONLY 

SIZE  OF  WOOD 
GIRDER2 

FLOOR  LIVE  LOAD 
(psf) 

SPACING  BETWEEN  GIRDERS  OR  BETWEEN  GIRDERS  AND  LOAD 
BEARING  WALLS3 

4  feet 

6  feet 

8  feet 

10  feet 

16  feet 

4x4 

30 

5'6" 

4'6" 

3'6" 

3'0" 

2'6" 

40 

S'O" 

4'0" 

3'6" 

3'0" 

2'6" 

4x6 

30 

8'0" 

6'6" 

5'6" 

5'0" 

4'6" 

40 

7'6" 

6'0" 

S'6" 

4'6" 

4'0" 

4x8 

6x6 

30 

W0" 

9'0" 

8'0" 

7'0" 

5'6" 

40 

lO'O" 

8'6r 

7'6" 

6'6" 

5'0" 

4x10 

6x8 

30 

14'0" 

11 '6" 

lO'O" 

8'6" 

6'0" 

40 

13'0" 

10'6" 

9'6" 

8'6" 

5'6" 

4x12 

6x10 

30 

16'6" 

14'0" 

1  ro- 

ll'O" 

9'0" 

40 

16'0" 

12'6" 

ll '0" 

lO'O" 

8'0" 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  pound  per  square  foot  =  0.0479  kN/m2. 

1.  Allowable  spans  may  be  interpolated  between  tributary  loads  shown  in  table.    Spans  and  girder  sizes  may  be 
computed  independently  of  the  above  table  in  accordance  with  accepted  engineering  practice. 

2.  Spans  are  based  on  No.  2  lumber. 

3.  The  spacing  is  the  tributary  load  to  the  girder.   It  is  found  by  adding  the  spans  of  the  floor  structure  on  each  side 
which  are  supported  by  the  girder  and  dividing  by  2. 

TABLE  3605.2.3.3b 

ALLOWABLE  SPANS  FOR  BUILT-UP  WOOD  CENTER  GIRDERS 

AND  FOOTING  SIZES  FOR  GIRDER  SUPPORT  COLUMNS 


WIDTH  OF 

STRUCTURE 

(feet) 

GIRDER 

SIZE 
(inches) 

ONE  STORY 

TWO  STORY 

THREE  STORY 

Maximum  Span 
(feet-inches) 

Footing  Size 
(inches) 

Maximum  Span 
(feet-inches) 

Footing  Size 
(inches) 

Maximum  Span 
(feet-inches) 

Footing  Size 
(inches) 

24 

3-2x8 

6-7 

17x17* 

4-11 

20x20 

4-1 

22x22 

4-2x8 

7-8 

19x19* 

5-8 

21x21 

4-9 

24x24 

3-2x10 

8-5 

20x20* 

6-3 

23x23 

5-3 

25x25 

4-2x10 

9-9 

21x21 

7-3 

24x24 

6-1 

27x27 

3-2x12 

10-3 

22x22 

7-8 

25x25 

6-4 

27x27 

4-2x12 

11-10 

23x23 

8-10 

27x27 

7-4 

29x29 

26 

3-2x8 

6-4 

17x17* 

4-9 

20x20 

3-11 

22x22 

4-2x8 

7-4 

18x18* 

5-6 

22x22 

4-7 

24x24 

3-2x10 

8-1 

19x19 

6-1 

23x23 

5-0 

25x25 

4-2x10 

9-4 

21x21 

7-0 

24x24 

5-10 

27x27 

3-2x12 

9-10 

21x21 

7-4 

25x25 

6-1 

28x28 

4-2x12 

11-5 

23x23 

8-6 

27x27 

7-1 

30x30 

28 

3-2x8 

6-2 

17x17* 

4-7 

21x21 

3-10 

23x23 

4-2x8 

7-1 

18x18* 

5-3 

22x22 

4-5 

24x24 

3-2x10 

7-10 

19x19 

5-10 

23x23 

4-10 

26x26 

4-2x10 

9-0 

20x20 

6-9 

25x25 

5-7 

28x28 

3-2x12 

9-6 

21x21 

7-1 

26*26 

5-11 

28x28 

4-2x12 

11-0 

22x22 

8-2 

28x28 

6-10 

30x30 

32 

3-2x8 

5-9 

16x16* 

4-3 

21x21 

3-7 

24x24 

4-2x8 

6-7 

17x17 

4-11 

23x23 

4-1 

25x25 

3-2x10 

7-4 

18x18 

5-5 

24x24 

4-6 

27x27 

4-2x10 

8-5 

20x20 

6-3 

26x26 

5-3 

28x28 

3-2x12 

8-11 

20x20 

6-8 

27x27 

5-6 

29x29 

4-2x12 

10-3 

22x22 

7-8 

29x29 

6-4 

31x31 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  psf  =  0.0479  kN/m2,  1  psi  =  6.895  kPa. 

1.  Values  shown  are  for  a  clear-span  trussed  roof,  a  load  bearing  center  wall  on  the  first  floor  in  a  two-story 
construction,  and  a  load-bearing  center  wall  on  the  first  and  second  floors  in  three-story  construction. 

2.  Spans  based  on  allowable  stress  in  bending  Fb  -  1,000  pounds  per  square  inch  (psi)  for  repetitive  members.   See 
Table  3605.2.3.  Id 

3.  Footing  size  based  on  2,000  psf  soil-bearing  capacity;  footing  thickness  shall  be  one-half  (minimim)  the  width  of 
the  footing,  or  ten  inches,  whichever  is  greater. 

4.  4x4  posts  may  be  used  at  these  (*)  locations,  6x6  posts,  or  4x4  posts  or  three-inch  diameter  steel  columns  with 
bearing  plates  or  equivalent  area,  are  acceptable  in  all  locations. 


524 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


3605.2.9  Framing  of  openings:  Openings  in  floor 
framing  shall  be  framed  with  header  and  trimmer 
joists.  When  the  header  joist  span  does  not  exceed 
four  feet  (1219  mm),  the  header  joist  may  be  a  single 
member  the  same  size  as  the  floor  joist.  Single 
trimmer  joists  may  be  used  to  carry  a  single  header 
joist  that  is  located  within  three  feet  (914  mm)  of  the 
trimmer  joist  bearing.  When  the  header  joist  span 
exceeds  four  feet  (1219  mm),  the  trimmer  joists  and 
the  header  joist  shall  be  doubled  and  of  sufficient 
cross  section  to  support  the  floor  joists  framing  into 
the  header.  Approved  hangers  shall  be  used  for  the 
header-joist  to  trimmer  joist  connections  when  the 
header  joist  span  exceeds  six  feet  (1829  mm). 

3605.2.10  Floor  trusses:  Wood  floor  trusses  shall  be 
designed  in  accordance  with  approved  engineering 
practice.  The  design  of  metal  plate  connected  wood 
trusses  shall  comply  with  TPI  QST,  TPI  PCT  and 
TPI-1  "Design  Specification  for  Metal  Plate 
Connected  Wood  Trusses,  as  listed  in  Appendix  A." 
Trusses  shall  be  braced  and  installed  in  accordance 
with  their  appropriate  engineered  design.  In  the 
absence  of  specific  bracing  requirements,  trusses 
shall  be  braced  in  accordance  with  TPI  BWT,  as 
listed  in  Appendix  A.  Truss  members  shall  not  be 
drilled,  cut,  notched  or  altered  in  any  manner  unless 
so  designed. 

3605.2.11  Draftstopping  required:  When  there  is 
usable  space  above  and  below  the  concealed  space 
of  a  floor/ceiling  assembly,  draftstops  shall  be 
installed  so  that  the  area  of  the  concealed  space  does 
not  exceed  1,000  square  feet  (93  m2).  Draftstopping 
shall  divide  the  concealed  space  into  approximately 
equal  areas.  Draftstopping  shall  be  provided  in 
floor/ceiling  assemblies  under  the  following  certain 
circumstances: 

1.  Ceiling  is  suspended. under  the  floor  framing; 
or 

2.  Floor  framing  is  constructed  of  truss-type 
open-web  or  perforated  members. 

3 .  The  assembly  is  enclosed  by  a  floor  membrane 
above  and  a  ceiling  membrane  below. 

3605.2.11.1  Materials:  Draftstopping  materials 
shall  not  be  less  than  '/2-inch  (12.7  mm)  gypsum 
hoard,  %-inch  (9  5  mm)  wood  structural  panels, 
%-inch  (9.5  mm)  Type  2-M-W  particleboard  or 
other  approved  materials  adequately  supported. 
Draftstopping  shall  be  installed  parallel  to  the 
floor  framing  members  unless  otherwise  approved 
by  the  building  official.  The  integrity  of  all 
draftstops  shall  be  maintained. 

780  CMR  3605 3  FLOOR  SHEATHING 
3605.3.1  Lumber  sheathing:  Maximum  allowable 
spans  for  lumber  used  as  floor  sheathing  shall 
conform  to  Tables  3605.3.1,  3605.3.2.1.1a  and 
3605.3.2.1.1b. 


3605.3.1.1  End  joints.  Lumber  used  as 
subflooring  shall  be  installed  with  end  joints  over 
supports  unless  end-matched  lumber  is  used,  in 
which  case  each  piece  shall  bear  on  at  least  two 
joists.  Subflooring  may  be  omitted  when  joist 
spacing  does  not  exceed  16  inches  (406  mm)  and 
a  one-inch  (25  mm)  nominal  tongue-and-groove 
wood  strip  flooring  is  applied  perpendicular  to  the 
joists 

TABLE  3605.3.1  MINIMUM  THICKNESS  OF 
LUMBER  FLOOR  SHEATHING 


JOIST  OR  BEAM 

SPACING 

(inches) 

MTNTMUM  NET  THICKNESS 

Perpendicular  to  Joist 

Diagonal  to  Joist 

24 

11/16 

% 

16 

% 

% 

48' 

l'/iT&G 

542 

N/A 

603 

For  SI:  1  inch  =  25.4  mm,  1  psi  =  6.895  kPa. 

1 .  Minimum  840  Fb  1,000,000  E. 

2.  Minimum  950  Fb  1,300,000  E. 

3     Minimum  1,060  Fb  1,600,000  E. 

3605.3.2  Plywood  sheathing: 

3605.3.2.1  Identification  and  grade:  Plywood 
used  for  structural  purposes  shall  conform  to  DOC 
PS  1,  DOC  PS  2  and  HPMA  (ANSI)  HP,  as  listed 
in  Appendix  A,  and  wood  structural  panels  shall 
conform  to  DOC  PS  2,  as  listed  in  Appendix  A. 
All  panels  shall  be  identified  by  a  grade  mark  of 
certificate  of  inspection  issued  by  an  approved 
agency. 

36053.2.1.1  Subfloor  and  combined  subfloor 
underlayment:  Where  used  as  subflooring  or 
combination  subfloor  underlayment,  wood 
structural  panels  shall  be  of  one  of  the  grades 
specified  in  Table  3605.3.2.1.1a.  When  sanded 
plywood  is  used  as  a  combination  subfloor 
underlayment,  the  grade  shall  be  as  specified  in 
Table  3605.3.2.1.1b 

3605.3.2.1.2  Wood  structural  panels:  Wood 
structural-use  panels  conforming  to  DOC  PS  2 
includes  performance-rated  plywood,  oriented 
strand-board  and  composite  panels.  Oriented 
strand-board  structural-use         panels 

manufactured  in  Canada  shall  conform  to  CSA 
0437,  as  listed  in  Appendix  A. 

3605.3.2.2  Allowable  spans:  The  maximum 
allowable  span  for  wood  structural  panels  used  as 
subfloor  or  combination  subfloor  underlayment 
shall  be  as  set  forth  in  Table  3605.3.2.1.1a.  The 
maximum  span  for  sanded  plywood  combination 
subfloor  underlayment  shall  be  set  forth  in  Table 
3605.3.2.1.1b. 

3605.3.2.3  Installation:  Plywood  and  wood 
structural  panels  used  as  subfloor  or  combination 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


525 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


subfloor  underlayment  shall  be  attached  to 
framing  in  accordance  with  Table  3606.2.3a. 

3605.3.3  Particleboard: 

3605.3.3.1  Identification  and  grade: 
Particleboard  shall  conform  to  ANSI  A208.1,  as 
listed  in  Appendix  A,  and  shall  be  so  identified  by 
a  grade  mark  or  certificate  of  inspection  issued  by 
an  approved  agency. 


3605.3.3.2  Floor  underlayment:  Particleboard 
floor  underlayment  shall  conform  to  Type  PBU, 
as  listed  in  Appendix  A,  and  shall  not  be  less  than 
Vi-inch  (6.4  mm)  in  thickness. 

3605.3.3.3  Installation:  Particleboard 
underlayment  shall  be  installed  in  accordance 
with  the  recommendations  of  the  manufacturer 
and  attached  to  framing  in  accordance  with  Table 
3606.2.3a 


TABLE  3605.3.2.1.1a 

ALLOWABLE  SPANS  AND  LOADS  FOR  PLYWOOD  AND  WOOD  STRUCTURAL  PANELS 

FOR  ROOF  AND  SUBFLOOR  SHEATHING  AND  COMBINATION  SUBFLOOR 

UNDERLAYMENTS  *~ 


NOMINAL 

PANEL 

THICKNESS 

(inch) 

MINIMUM  SPAN  (inches) 

LOAD  (pounds  per  square 
foot,  at  maximum  span) 

MAXIMUM  SPAN 

With  Edge 
Support 

Without  Edge 
Support 

Total  Load 

Live  Load 

(inches) 

C-D,  C-C,  SHEATHING5 

ROOF6 

SUBFLOOR6 

12/0 

\e 

12 

12 

40 

30 

0 

16/0 

5A,.% 

16 

16 

40 

30 

0 

20/0 

5/16,% 

20 

20 

40 

30 

0 

24/0 

%,7/,6>'/2 

24 

207 

40 

30 

0 

24/1-6 

V* 

24 

24 

50 

40 

16 

32/16 

'V/2,% 

32 

28 

40 

30 

16s 

40/20 

%>Va,3/4,7/8 

40 

32 

40 

30 

208'* 

48/24 

%,%,% 

48 

36 

45 

35 

24 

UNDERLAYMENT,  C-C 
PLUGGED  SINGLE  FLOOR 

ROOF6 

COMBINATION 

SUBFLOOR 

UNDERLAYMENT 

16o.c. 

%.% 

24 

24 

50 

40 

166 

20  o.c. 

%,%,% 

32 

32 

40 

30 

208'y 

24  o.c. 

^.^ 

48 

36 

35 

25 

24 

32  o.c. 

%,  1 

48 

40 

50 

40 

32 

48  o.c. 

l\,V/e 

60 

48 

50 

40 

48 

For  SI:  1  inch  =  25.4  mm,  1  psf  =  0.0479kNnT 

1.  The  allowable  loads  were  determined  using  a  dead  load  of  10  psf    If  the  dead  load  exceeds  10  psf,  then  the  live 
load  shall  be  reduced  accordingly. 

2.  Panels  continuous  over  two  or  more  spans  with  long  dimension  perpendicular  to  supports.  Spans  shall  be  limited 
to  values  shown  because  of  possible  effect  of  concentrated  loads. 

3.  Applies  to  panels  24  inches  or  wider. 

4.  Lumber  blocking,  panel  edge  clips  (one  midway  between  each  support,  except  two  equally  spaced  between  supports 
when  span  is  48  inches),  tongue-and-groove  panel  edges,  or  other  approved  type  of  edge  support. 


rades. 


Includes  Structural  1  panels  in  these  era 
6.    Uniform  load  deflection  limitation;   /180  of  span  under  live  load  plus  dead  load,  '/240  of  span  under  live  load  only. 

7  Maximum  span  24  inches  for  VS-inch  panels. 

8  Maximum  span  24  inches  where  3/4-inch  wood  finish  flooring  is  installed  at  right  angles  to  joists. 

9.  Maximum  span  24  inches  where  1  !4  inches  of  lightweight  concrete  or  approved  cellular  concrete  is  placed  over 
the  subfloor. 

10  Unsupported  edges  shall  have  tongue-and-groove  joints  or  shall  be  supported  with  blocking  unless  nominal  Vi-inch 
thick  underlayment  or  1  Vi  inches  of  light-weight  concrete  or  approved  cellular  concrete  is  placed  over  the  subfloor. 
or  3/4-inch  wood  finish  is  used.  Allowable  uniform  live  load  at  maximum  span,  based  on  deflection  of  V360  of  span, 
is  100  psf. 

11.  Unsupported  edges  shall  have  tongue-and-groove  joints  or  shall  be  supported  with  blocking  unless  nominal  Vi- 
inch  thick  underlayment  or  3/4-inch  wood  finish  flooring  is  used.  Allowable  uniform  live  load  at  maximum  span,  based 
on  deflection  of  /360  of  span,  is  100  psf,  except  panels  with  a  Span  Rating  of  48  o.c.  are  limited  to  65  psf  total  uniform 
load  at  maximum  span. 


526 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  FLOORS 


TABLE  3605.3.2.1.1b 

ALLOWABLE  SPANS  FOR  PLYWOOD 

COMBINATION  SUBFLOOR 

UNDERLAYMENT1 


IDENTIFICATION 

SPACING  OF  JOISTS 

16 

20 

24 

Species  Group" 
1 
2,3 
4 

% 

5/8 

3/4 
7/8 

3/4 

Vb 

i 

For  SI:  1  inch  =  25.4  mm,  lpsf  =  0.0479  kNnT 

1.  Plywood  continuous  over  two  or  more  spans  and  face 
grain  perpendicular  to  supports.  Unsupported  edges  shall 
be  tongue-and-groove  or  blocked  except  where  nominal 
Vi-inch-thick  underlayment  or  3/4-inch  wood  finish  floor 
is  used.  Allowable  uniform  live  load  at  maximum  span 
based  on  deflection  of  V360  of  span  is  100  psf. 

2.  Applicable  to  all  grades  of  sanded  Exterior-type 
plywood. 

780  CMR  3605.4  TREATED-WOOD  FLOORS 
(ON  GROUND) 

3605.4.1  General:  Treated-wood  basement  floors 
and  floors  on  ground  shall  be  designed  to  withstand 
axial  forces  and  bending  moments  resulting  from 
lateral  soil  pressures  at  the  base  of  the  exterior  walls 
and  floor  live  and  dead  loads.  Floor  framing  shall  be 
designed  to  meet  joist  deflection  requirements  in 
accordance  with  780  CMR  3603.1. 

3605.4.1.1  Unbalanced  soil  loads:  Unless  special 
provision  is  made  to  resist  sliding  caused  by 
unbalanced  lateral  soil  loads,  wood  basement 
floors  shall  be  limited  to  applications  where  the 
differential  depth  of  fill  on  opposite  exterior 
foundation  walls  is  two  feet  (610  mm)  or  less. 

3605.4.1.2  Construction:  Joists  in  wood 
basement  floors  shall  bear  tightly  against  the 
narrow  face  of  studs  in  the  foundation  wall  or 
directly  against  a  band  joist  which  bears  on  the 
studs.  Plywood  subfloor  shall  be  continuous  over 
lapped  joists  or  over  butt  joints  between  in-line 
joists.  Sufficient  blocking  shall  be  provided 
between  joists  to  transfer  lateral  forces  at  the  base 
of  the  end  walls  into  the  floor  system. 

3605.4.1.3  Uplift  and  buckling:  Where  required, 
resistance  to  uplift  or  restraint  against  buckling 
shall  be  provided  by  interior  bearing  walls  or 
properly  designed  stub  walls  anchored  in  the 
supporting  soil  below. 

3605.4.2  Site  preparation:  The  area  within  the 
foundation  walls  shall  have  all  vegetation,  topsoil 
and  foreign  material  removed,  and  any  fill  material 
which  is  added  shall  be  free  of  vegetation  and 
foreign  material.  The  fill  shall  be  compacted  to 
assure  uniform  support  of  the  treated-wood  floor 
sleepers. 


3605.4.2.1  Base:  A  minimum  four-inch-thick 
(102  mm)  granular  base  of  gravel  having  a 
maximum  size  of  V*  inch  (19  mm)  or  crushed 
stone  having  a  maximum  size  of  Vi  inch  (12.7 
mm)  shall  be  placed  over  the  compacted  sub- 
grade. 

3605.4.2.2  Moisture  barrier:  Polyethylene 
sheeting  of  minimum  six-mil  (0.15  mm)  thickness 
shall  be  placed  over  the  granular  base.  Joints  shall 
be  lapped  six  inches  (153  mm)  and  left  unsealed. 
The  polyethylene  membrane  shall  be  placed  over 
the  treated-wood  sleepers  and  shall  not  extend 
beneath  the  footing  plates  of  the  exterior  walls. 

3605.4.3  Materials:  All  framing  materials, 
including  sleepers,  joists,  blocking  and  plywood 
subflooring,  shall  be  pressure  preservatively  treated 
and  dried  after  treatment  in  accordance  with  AWPA 
C22,  as  listed  in  Appendix  A. 

780  CMR  3605.5  CONCRETE  FLOORS 
(ON  GRADE) 

3605.5.1  General:  Concrete  slab-on-grade  floors 
shall  be  constructed  in  accordance  with  Figure 
3604.3.1a.  The  specified  compressive  strength  of 
concrete  at  28  days  shall  not  be  less  than  2,500 
pounds  per  square  inch  (17,225  kPa),  except  where 
weather  exposure  requires  greater  strength  and  air- 
entrained  concrete,  as  set  forth  in  Table  3604.2.2 
and  780  CMR  3604.2.2. 

Slabs  shall  be  constructed  with  control  joints 
having  a  depth  of  at  least  'A  the  slab  thickness  but 
not  less  than  one  inch,  and  joints  shall  be  spaced  at 
intervals  not  more  than  30  feet  in  each  direction 
and  slabs  not  rectangular  in  shape  shall  have 
control  joints  across  the  slab  at  points  of  offset,  if 
offset  exceeds  ten  feet. 

Exception:  Control  joints  are  not  required  or 
may  exceed  30  foot  intervals  where  welded  wire 
fabric  or  equivalent  is  provided  in  accordance 
with  Table  3605.  S.  1.  The  welded  wire  fabric  or 
equivalent  material  shall  be  placed  at  mid-depth 
of  the  slab  or  two  inches  from  the  top  surface  for 
slabs  more  than  four  inches  in  thickness. 

Table  3605.5.1 

CRACK  CONTROL  REINFORCEMENT 

FOR  SLABS 


MAXIMUM  DIMENSION 

OF  SLAB  OR  DISTANCE 

BETWEEN  CONTROL 

JOINTS  (Feet)1 

ww 

WTRE 
SPACING 
(inches) 

WWF"  WIRE 

SIZE 

DESIGNATION 

SLAB  THICKNESS  (inches) 

3.5 

40 

45 

5  0 

55 

60 

42 
59 

86 

36 
52 

75 

32 
46 

67 

29 
42 
60 

26 
38 

55 

24 
35 

50 

6x6 
6x6 
6x6 

W1.4xW1.4 
W2.0xW2.0 
W2.9xW2.9 

1.  Values  in  table  are  based  on  reinforcement  with  a 
yield  strength  of  65,000  psi.  If  reinforcement  with  a 
different  yield  strength  is  used,  the  slab  dimension  shown 


2/7/97    (Effective  2/28/97) 


7S0  CMR  -  Sixth  Edition 


527 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


in  the  table  shall  be  adjusted  by  multiplying  by  the  yield 
strength  of  the  steel  to  be  used  and  dividing  by  65,000. 
2.    Welded  wire  fabric. 

3605.5.2  Site  preparation:  The  area  within  the 
foundation  walls  shall  be  cleaned  of  all  vegetation 
and  organic  and  foreign  material  and  top  soil. 

3605.5.2.1  Fill:  Fill  material  shall  be  free  of 
vegetation  and  foreign  material.  The  fill  shall  be 
compacted  to  assure  uniform  support  of  the  slab, 
and  except  where  approved,  the  fill  depths  shall 
not  exceed  24  inches  (610  mm)  for  clean  sand  or 
gravel. 

3605.5.2.2  Base:  A  four-inch-thick:  (102  mm) 
base  course  consisting  of  clean  graded  sand, 
gravel,  crushed  stone  or  crushed  blast-furnace 
slag  passing  a  two-inch  (51  mm)  sieve  shall  be 
placed  on  the  prepared  subgrade  when  the  slab  is 
below  grade. 

Exceptions:  A  base  course  is  not  required 
when  the  concrete  slab  is  installed  on  well- 
drained  or  sand-gravel  mixture  soils  according 
to  the  United  Soil  Classification  System, 
Group  I  Soils. 


3605.5.2.3  Vapor  barrier:  An  approved  vapor 
barrier  with  joints  lapped  not  less  than  six  inches 
(153  mm)  shall  be  placed  between  the  concrete 
floor  slab  and  the  base  course  or  the  prepared 
subgrade  where  no  base  course  exists. 

Exception:  The  vapor  barrier  may  be  omitted: 

1.  From  detached  garages,  utility  buildings 
and  other  unheated  accessory  structures; 

2.  From  driveways,  walks,  patios  and  other 
flatwork  not  likely  to  be  enclosed  and  heated  at 
a  later  date;  or 

3.  Where  approved  by  the  building  official, 
based  on  local  site  conditions. 

780  CMR  3605.6  METAL 
3605.6.1  General:  Steel  and  aluminum  elements 
shall  be  constructed  of  materials  and  designed  in 
accordance  with  the  AISC  "Specification  for  the 
Design,  Fabrication  and  Erection  of  Structural 
Steel  Buildings"  and  AA  SAS30,  respectively,  as 
listed  in  Appendix  A.  Steel  elements  may  be  hot- 
rolled  or  cold-formed  structural  steeL  Members 
shall  be  straight  and  free  of  any  defects  which  would 
significantly  affect  their  structural  performance. 


528 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3606 


WALL  CONSTRUCTION 


780  CMR  3606.1  GENERAL 

3606.1.1  Application:  The  provisions  of  780  CMR 
3606. 1  shall  control  the  design  and  construction  of 
all  walls  and  partitions  for  all  buildings.  The  use  of 
materials  or  methods  of  construction  not  specified  in 
this  chapter  accomplishing  the  purposes  intended  by 
780  CMR  36  and  approved  by  the  building  official 
in  accordance  with  780  CMR  109.0  shall  be 
accepted  as  complying  with  780  CMR  36. 

3606.1.2  Requirements:  The  wall  construction  shall 
be  capable  of  accommodating  all  loads  imposed 
according  to  780  CMR  3603.1  and  transmitting  the 
resulting  loads  to  supporting  structural  elements. 

3606.1.2.1  Floor-covering  materials:  Interior 
and  exterior  bearing  and  non-loadbearing  walls 
shall  be  placed  directly  on  floor  sheathing, 
underlayment  or  a  structural  framing  member, 
fastened  in  accordance  with  Table  3606.2.3a. 
Compressible  floor-covering  materials  that 
compress  more  than  /32  inch  (0.794  mm)  when 
subjected  to  50  pounds  (23  kg)  applied  over  one 
square  inch  (645  mm)  of  material  and  are  greater 
than  Vfe  inch  (3.2  mm)  in  thickness  in  the 
uncompressed  state  shall  not  extend  beneath 
walls,  partitions  or  columns  which  are  fastened  to 
the  floor. 

780  CMR  36062  WALL  FRAMING 

3606.2.1  Identification:  Load-bearing  dimension 
lumber  used  for  studs,  plates  and  headers  shall 
conform  to  DOC  PS  20,  as  listed  in  Appendix  A, 
and  to  other  applicable  standards  and  grading  rules 
and  shall  be  identified  by  a  grade  mark,  or  certificate 
of  inspection  issued  by  an  approved  agency.  The 
grade  mark  or  certificate  shall  provide  adequate 
information  to  determine  the  "F^"  the  allowable 
stress  in  bending,  and  "E,"  the  modulus  of  elasticity. 
Approved  end-jointed  lumber  may  be  used 
interchangeably  with  solid-sawn  members  of  the 
same  species  and  grade. 

Exception:  Native  Lumber  as  identified  in 
780  CMR  2303. 2  and  780  CMR  R4. 

3606.2.2  Grade:  Studs  shall  be  a  minimum  No.  3, 
Standard  or  Stud  grade  lumber. 

Exception:  Bearing  studs  not  supporting  floors 
and  nonhealing  studs  may  be  Utility  grade 
lumber,  provided  the  studs  are  spaced  in 
accordance  with  Table  3606.2.3d. 

3606.2.3  Exterior  Walls:  Exterior  walls  of  wood- 
frame  construction  shall  be  designed  and  constructed 


in  accordance  with  the  provisions  of  780  CMR 
36062  and  Figures  3606.2.3a  and  3606.2.3b. 
Components  of  exterior  walls  shall  be  fastened  in 
accordance  with  Tables  3606.2.3a  through 
3606.2.3d 

3606.2.3.1  Special  provisions  for  high  wind 
loads:  Exterior  walls  subject  to  wind  pressures  of 
30  pounds  per  square  foot  (1.44  kN/m2)  or 
greater,  as  established  by  wind  load  maps, 
780  CMR  1611.1a,  h  and  c,  shall  be  designed  in 
accordance  with  accepted  engineering  practice. 

3606.2.3.2  Stud  spacing:  In  bearing  walls,  studs 
which  are  not  more  than  ten  feet  (3048  mm)  in 
length  shall  be  spaced  not  more  than  is  specified 
in  Table  3606.2.3d  for  the  corresponding  stud 
size. 

3606.23.3  Top  plate:  Exterior  wall  studs  shall  be 
capped  with  a  double  top  plate  installed  to  provide 
overlapping  at  comers  and  intersections  with 
bearing  partitions.  End  joints  in  top  plates  shall 
be  offset  at  least  48  inches  (1219  mm). 

Exception:  A  single  top  plate  may  be  installed 
in  bearing  and  exterior  walls,  provided  the 
plate  is  adequately  tied  at  joints,  corners  and 
intersecting  walls  with  three-inch-by-six-inch 
by  a  0.036-inch-thick  (76  mm  by  153  mm  by 
0.914  mm)  galvanized  steel  plate  that  is  nailed 
to  each  wall  or  segment  of  wall  by  three  8d 
nails,  provided  the  rafters  or  joists  are  centered 
over  the  studs  with  a  tolerance  of  no  more  than 
one  inch  (25  mm).  The  top  plate  may  be 
omitted  over  lintels  which  are  adequately  tied 
to  adjacent  wall  sections  with  steel  plates  or 
equivalent  as  previously  described. 

3606.2.3.4  Bearing  studs:  Where  floor  or  roof 
framing  members  are  spaced  more  than  1 6  inches 
(406  mm)  on  center  and  the  bearing  studs  are 
spaced  24  inches  (610  mm)  on  center,  such 
members  shall  bear  within  five  inches  (127  mm) 
of  the  bearing  studs. 
Exceptions: 

1 .  The  top  plates  are  two  two-inch-by-six- 
inch  (5 1  mm  by  153  mm)  or  two  three-inch-by- 
four-inch  (76  mm  by  102  mm)  members. 

2.  A  third  top  plate  is  installed. 

3.  Solid  blocking  equal  in  size  to  the  studs  is 
installed  to  reinforce  the  double  top  plate. 

3606.2.4  Interior  load-bearing  partitions:  Interior 
load-bearing  partitions  shall  be  constructed,  framed 
and  firestopped  as  specified  for  exterior  walls. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


529 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3606.2.4.1     Interior    nonbearing    partitions: 

Interior  nonbearing  partitions  may  be  constructed 
with  two-inch-by-three-inch  (51  mm  by  76  mm) 
studs  spaced  24  inches  (610  mm)  on  center  or 
two-inch-by-four-inch  (51  mm  by  102  mm)  flat 
studs  spaced  16  inches  (406  mm)  on  center. 
Interior  nonbearing  partitions  may  be  capped  with 
a  single  top  plate. 

3606.2.5  Drilling  and  notching-studs:  Any  stud  in 
an  exterior  wall  or  bearing  partition  may  be  cut  or 
notched  to  a  depth  not  exceeding  25%  of  its  width 
Studs  in  nonbearing  partitions  may  be  notched  to  a 


depth  not  to  exceed  40%  of  a  single  stud  width.  Any 
stud  may  be  bored  or  drilled,  provided  that  the 
diameter  of  the  resulting  hole  is  no  greater  than  40% 
of  the  stud  width,  the  edge  of  the  hole  is  no  closer 
than  %  inch  (15.9  mm)  to  the  edge  of  the  stud,  and 
the  hole  is  not  located  in  the  same  section  as  a  cut  or 
notch. 

Exception:  A  stud  may  be  bored  to  a  diameter  not 
exceeding  60%  of  its  width,  provided  that  such 
studs  when  located  in  exterior  walls  or  bearing 
partitions  are  doubled  and  that  not  more  than  two 
successive  studs  are  bored. 


TABLE  3606.2.3a 

FASTENER  SCHEDULE  FOR 

STRUCTURAL  MEMBERS 


DESCRIPTION  OF  BUILDING  ELEMENTS 

NUMBER  AND 

TYPEO?2,3  4 
FASTENERS     •' 

SPACING  OF  FASTENERS 

Jcist  to  sill  or  girder,  toe  nail 

3-8d 

1 "  x  6"  subfloor  or  less  to  each  joist,  face  nail 

2-8d 
2  staples,  1  Va " 

2"  subfloor  to  joist  to  girder,  blind  and  face  nail 

Sole  plate  to  joist  or  blocking,  face  nail 

Top  or  sole  plate  to  stud,  end  nail 

Stud  to  sole  plate,  toe  nail 

Double  studs,  face  nail 

Double  top  plates,  face  nail 

Double  top  plates,  minimum  48-inch  offset  of  end  to  joints,  face 

nail  in  lapped  area 
Top  plates,  laps  at  corners  and  intersections,  face  nail 

2-16d 
16d 

2-16d 
3-8dor2-16d 

lOd 

lOd 
4-1  Od 

2-10d 

16d"  o.c. 

24"  o.c. 
24"  o.c. 

Built-up  header,  two  pieces  with  Vi "  spacer 

16d 

16"  o.c.  along  each  edge 

Continued  header,  two  pieces 

16d 

16"  o.c.  along  each  edge 

Ceiling  joists  to  plate,  toe  plate 
Continuous  header  to  stud,  toe  nail 
Ceiling  joist,  laps  over  partitions,  face  nail 
Ceiling  joist  to  parallel  rafters,  face  nail 
Rafter  to  plate,  toe  nail 

3-8d 
4-8d 
3-I0d 
3-10d 
2-16d 

- 

1 "  brace  to  each  stud  and  plate,  face  nail 

2-8d 
2  staples,  1 V* " 

1 "  x  6"  sheathing  to  each  bearing,  face  nail 

2-8d 
2  staples,  1  % " 

- 

1"  x  8"  sheathing  to  each  bearing,  face  nail 

3-8d 
3  staples,  \Va" 

- 

Wider  than  1 "  x  8"  sheathing  to  each  bearing,  face  nail 

3-8d 
4  staples,  I  Vt " 

Built  up  comer  studs 

lOd 

24"  o.c. 

Built-up  girders  and  beams,  2-uich  lumber  layers 

lOd 

Nail  each  layer  as  follows:  32:  o.c. 
at  top  and  bottom  and  staggered. 
Two  nails  at  ends  and  at  each  splice. 

2"  planks 

2-16d 

At  each  bearing 

Roof  Rafters  to  ridge,  valley  or  hip  rafters: 
toenail 
face  nail 

4-16d 
3-16d 

Rafter  ties  to  rafters,  face 

3/8d 

DESCRIPTION  OF 
BUILDING 
MATERIALS 

DESCRIPTIQNQF 
FASTENER  *  ' 

SPACING  OF  FASTENERS 

Edges  (inches)           Intermediate  Supports  '    (inches) 

Plywood  and  wood  structural  panels,  subfloor,  roof  and  wall  sheathing  to  framing,  and  particleboard  wall  sheathing  to  framing 

V-'/2" 

6d  common  nail  (subfloor,  wall) 
8d  common  nail  (roof) 

6 

127 

-  %-r 

8d  common  nail 

6 

127 

l1/a"-l'/4 

1  Od  common  nail  or  8d  deformed  nail 

6 

12 

530 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


DESCRIPTION  OF 
BUILDING 
MATERIALS 

DESCRIPTIQNOP 
FASTENER  A  ^ 

SPACING  OF  FASTENERS 

Edges  (inches)           Intermediate  Supports  '   (inches) 

Other  wall  sheathing 

Vi"  gypsum  sheathing 

1  !4"  galvanized  roofing  nail; 

6d  common  nail;  staple  galvanized, 

1  lA"  long;  1 Va"  screws,  Type  W  or  S 

4 

8 

%"  gypsum  sheathing 

VA"  galvanized  roofing  nail;  8d 
common  nail;  Staple  galvanized,  1%" 
long,  ls/e"  screws,  Type  W  or  S 

4 

8 

Plywood  and  wood  structural  panels,  conbination  subfloor  underlayment  to  framing 

3/i"  and  less 

6d  deformed  nail,  or  8d  common  nail 

6 

12 

%"-l" 

8d  common  nail  or  8d  deformed  nail 

6 

12 

IW-VA" 

lOd  common  nail  or  8d  deformed  nail 

6 

12 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  mph  =  1.609  km/h. 

1.  All  nails  are  smooth-common,  box  or  deformed  shanks  except  where  otherwise  stated 

2.  Staples  are  16  gauge  wire  and  have  a  minimum  /16-inch  O.D.  crown  width. 

3.  Nails  shall  be  spaced  not  more  than  six  inches  ox.  at  all  supports  where  spans  are  48  inches  or  greater. 

4.  Four-foot  by  eight-foot  or  four-foot-by-nine-foot  panels  shall  be  applied  vertically. 

5.  Spacing  of  fasteners  not  included  in  this  table  shall  be  based  on  Table  3606.2. 3a(l). 

6.  For  regions  having  basic  wind  speed  of  90  mph  or  greater,  8d  deformed  nails  shall  be  used  for  attaching  plywood 
and  wood  structural  panel  roof  sheathing  to  framing  within  minimum  48-inch  distance  from  gable  end  walls,  if  mean 
roof  height  is  more  than  24  feet,  up  to  35  feet  maximum 

7.  For  regions  having  basic  wind  speed  of  80  mph  or  less,  nails  for  attaching  plywood  and  wood  structural  panel  roof 
sheathing  to  gable  end  wall  framing  shall  be  spaced  six  inches  o.c  When  basic  wind  speed  is  greater  than  80  mph,  nails 
for  attaching  panel  roof  sheathing  to  intermediate  supports  shall  be  spaced  six  inches  o.c  for  minimum  48-inch  distance 
from  ridges,  eaves  and  gable  end  walls;  and  four  inches  o.c  to  gable  end  wall  framing. 

8.  Gypsum  sheathing  shall-conform  to  ASTM  C  79  and  shall  be  installed  m  accordance  with  GA  253.  Fiberboard 
sheathing  shall  conform  to  either  AHA  194. 1  or  ASTM  C  208. 

TABLE  3606.2.3a(l) 
ALTERNATE  ATTACHMENTS 


NOMINAL  MATERIAL 
THICKNESS 

DESCRD7TION1,2  OF  FASTENER  AND 
LENGTH 

SPACING3  OF  FASTENERS 

Edges  (inches) 

Intermediate 
Supports  (inches) 

Plywood  and  wood  structural  panels  subfloor,  roof  and  wall  sheathing  to  framing  and  particleboard  wall  sheathing  to  framing 

V 

0.097  -0.099  Nail  VA" 
Staple  15  ga  l3/s" 

6 

12 

%" 

Staple  15  ga  1%" 

6 

12 

0.097 -0.099  Nail  VA" 

4 

10 

%"  and  !4" 

Staple  15  ga  VA" 

6 

12 

0.097 -0.099  Nail  1%" 

3 

6 

'VandVa" 

0.113  Nail  1%" 

Staple  15  and  16  ga.  1%" 

6 

12 

0.097  -0.099  Nail  VA" 

3 

6 

"VandW 

Staple  14  ga.  VA" 

6 

12 

Staple  15ga.  VA" 

5 

10 

0.097  -0.099  Naill%" 

3 

6 

1" 

Staple  14  ga.  2" 

5 

10 

0.113  Nail-2V&* 

Staple  15  ga.  2" 

4 

8 

0.097  -0.099  Nad  2Vi" 

3 

6 

Floor  underlayment;  plywcod-hardboard-particleboard 

Edges  (inches) 

Body  of  Panel 

Plywood 

Va"  and  5/16. 

1  Va"  ring  or  screw  shank  nail  -  minimum 
12'/2  ga.  (0.099")  shank  diameter 

6 

8 

'V.  and  %,",5/32"  and  Vi" 

1  Va  "  ring  or  screw  shank  nail  -  minimum 
12'/2  ga.  (0.099")  shank  diameter 

6 

85 

I9/32",  and  %",  23/32"  and  Va" 

1 Vi"  ring  or  screw  shank  nail  -  minimum 
I2V2  ga.  (0.099")  shank  diameter 

6 

12 

9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


531 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


NOMINAL  MATERIAL 
THICKNESS 

DESCRIPTION1,2  OF  FASTENER  AND 
LENGTH 

SPACING3  OF  FASTENERS 

Edges  (inches) 

Body  of  Panel 

Hardboard 
0.200" 

1  Vi"  long  ring-grooved  underlayment  nail 

6 

6 

4d  cement-coated  sinker  nail 

6 

6 

Staple  18  ga.  7/e"  long  (plastic  coated) 

3 

6 

Particleboard 

4d  ring-grooved  underlayment  nail 

3 

6 

Staple  18  ga.  Vs"  long  3/16"  crown 

3 

6 

%" 

6d  ring-grooved  underlayment  nail 

6 

10 

Staple  16  ga.  IVb"  long%"  crown 

3 

6 

14"  -  %" 

6d  ring-grooved  underlayment  nail 

6 

10 

Staple  16  ga.  1%"  long%"  crown 

3 

6 

For  SI:  1  inch  =  25.4  mm. 

1.  Nail  is  a  general  description  and  may  be  T-head,  modified  round  head,  or  round  head. 

2.  Staples  shall  have  a  minimum  crown  width  of  /I6-inch  o.d.  except  as  noted. 

3.  Nails  or  staples  shall  be  spaced  at  not  more  than  six  inches  o.c  at  all  supports  where  spans  are  48  inches  or  greater. 
Nails  or  staples  shall  be  spaced  at  not  more  than  ten  inches  o.c.  at  intermediate  supports  for  floors. 

4.  Fasteners  shall  be  placed  in  a  grid  partem  throughout  the  body  of  the  panel. 

5.  For  5-ply  panels,  intermediate  nails  shall  be  spaced  not  more  than  12  inches  o.c.  each  way. 


TABLE  3606.2.3b 
ALLOWABLE  STUD  SPACING  FOR  WOOD  STRUCTURAL  PANEL  WALL  SHEATHING 

PANEL  SPAN  RATING 

PANEL  NOMINAL  THICKNESS 

(inch) 

MAXIMUM  STUD  SPACING  (inches) 

Siding  Nailed  to: 

Stud 

Sheathing 

12/0  16/0, 20/0,  or  Wall  - 16  o.c. 

5/16,% 

16 

162 

24/0, 24/16,  32/16  or  Wall  -  24  o.c. 

%,7/„%'/2 

24 

243 

For  SI:  1  inch  =  25.4  mm. 

1    Blocking  of  horizontal  joints  shall  not  be  required. 

2.  Plywood  sheathing  %-inch  thick  or  less  shall  be  applied  with  long  dimension  across  studs. 

3.  Three-ply  plywood  panels  shall  be  applied  with  long  dimension  across  studs. 

TABLE  3606.2.3c 
ALLOWABLE  SPANS  FOR  PARTICLEBOARD  WALL  SHEATHING1 


THICKNESS  (inches) 

GRADE 

STUD  SPACING  (inches) 

When  Siding  is  nailed  to 
Studs 

When  Siding  is  Nailed  to 

Sheathing 

% 

M-l  Exterior  Glue 

16 

- 

Vi 

M-2  Exterior  Glue 

16 

16 

For  SI:   1  inch  =  25.4  mm. 

1 .  Wall  sheathing  not  exposed  to  the  weather.  If  the  panels  are  applied  horizontally,  the  end  joints  of  the  panels  shall 
be  offset  so  that  four  panels  corners  will  not  meet.  All  panel  edges  must  be  supported.  Leave  a  /16-inch  gap  between 
panels  and  nail  to  no  closer  than  %  inch  from  panel  edges. 


TABLE  3606.2.3d 
MAXIMUM  STUD  SPACING  (inches) 

STUD  SIZE 

SUPPORTING  ROOF 
AND  CEILING  ONLY 

SUPPORTING  ONE 

FLOOR  ROOF  AND 

CEILING 

SUPPORTING  TWO 

FLOORS ROOF AND 

CEILING 

SUPPORTING  ONE 
FLOOR  ONLY 

2x4 

241 

16 

- 

241 

3x4 

241 

24 

16 

24 

2x5 

24 

24 

- 

24 

2x6 

24 

24 

16 

24 

For  SI:  1  inch  =  25.4  mm. 

1    Shall  be  reduced  to  16  inches  if  Utility  grade  studs  are  used. 


3606.2.5.1    Drilling   and   notching-top   plate: 

When  piping  or  ductwork  is  placed  in  or  partly  in 
an  exterior  wall  or  interior  load-bearing  wall, 
necessitating  a  cutting  of  the  top  plate  by  more 


than  50%  of  its  width,  the  plate  shall  be  reinforced 
to  provide  equivalent  strength. 

3606.2.6  Headers:  The  allowable  spans  for  nominal 
four-inch  thick  (102  mm)  single  headers  and  two- 


532 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


inch  thick  (5 1  mm)  double  headers  in  bearing  walls 
shall  not  exceed  the  spans  set  forth  in  Table 
3606.2.6.  The  table  shall  not  be  used  where 
concentrated  loads  are  supported  by  the  headers. 

3606.2.6.1  Single  headers:  Nominal  two-inch 
thick  (5 1  mm)  single  headers  shall  not  be  used  in 

load-bearing  walls. 

3606.2.6.2  Plywood  box  headers:  Plywood  box 
headers  shall  be  constructed  in  accordance  with 
Figure  3606.2.6.2  and  Table  3606.2.6.2. 


3606.2.6.3  Non-bearing  walls:  Load-bearing 
headers  are  not  required  in  interior  or  exterior 
nonhealing  walls.  A  single  flat  two-inch-by-four- 
inch  (51  mm  by  102  mm)  member  may  be  used  as 
a  header  in  interior  or  exterior  nonhealing  walls 
for  openings  up  to  eight  feet  (2438  mm)  in  width 
if  the  vertical  distance  to  the  parallel  nailing 
surface  above  is  not  more  than  24  inches  (610 
mm).  Cripple  spacing  shall  be  the  same  as 
spacing  of  studs. 


FIGURE  3606.2.3a 
TYPICAL  WALL,  FLOOR  AND  ROOF  FRAMING 


t^sfv 


BOTTOM 
^PLATE 


RAFTERS  AND 
CEILING  JOISTS 
OR  APPROVED 
ROOF  TRUSS 


SECOND  STORY 


FLOOR  JOIST- 
SEE  DRILLING 
AND  NOTCHING 
PROVISIONS 
780  CMR  3605.2.6.1 
and  3605.2.6.2         ^ 


TOP  PLATE—  • 
SEE  DRILLING 
AND  NOTCHING 
PROVISIONS 
780  CMR  3606.2.5.1 


WALL  STUD- 
SEE  DRILLING  AND 

NOTCHING  PROVISIONS 
780  CMR  3606.2.5 

JOIST  MAY  BE  CUT 

OR  NOTCHED  BETWEEN 

THESE  LIMITS  , 


FOR  BLOCKING  AND 
BRIDGING.  SEE 
780  CMR  3605.2.5 


LAP  JOISTS  3"  MIN 
OR  SPLICE— SEE 
780  CMR  3605.2.4 


NT 


1  BY  4  RIBBON 
CUT  INTO  STUD- 
SEE  780  CMR  3606.2.7 
FOR  FIRESTOPPING 


CRAWL  SPACE 
OR  BASEMENT 
FOUNDATION 


INTERMEDIATE 
BEARING  WALL 


PLATFORM  FRAMING 


MONOLITHIC 

SLAB-ON-GRADE 

FOUNDATION 


BALLOON  FRAMING 


NOTE:  See  Figure  3604.3.  la  for  other  foundation  types 


For  SI:  1  inch  =  25.4  mm. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


533 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


FIGURE  3606.2.3b 
FRAMING  DETAILS 


CUT  PLATE  TIED 
WITH  25  GAGE 
STEET  ANGLE  OR 
EQUIVALENT 

SINGLE  OR 

DOUBLE  TOP 

PLATE 


STAGGER  JOINTS  4"  OR 
USE  SPUCE  PLATES 
SEE  780  CMR  3606.2.3.3 


FOUNDATION 
-^RIPPLE 
WALL  SEE      ' 
780  CME 
3606.2.8 


ANCHOR  BOLTS  EMBEDDED 
IN  FOUNDATION  6'0"  O.C. 
MAXIMUM 


CORNER  AND  PARTITION  POSTS 


1"  BY  4"  DIAGONAL 
BRACELET  INTO  STUDS 


3"TO"£ 


Apply  approved  sheathmg  or  brace  exterior  walls  with  1" 
by  4"  braces  let  into  studs  and  plates  and  extending  from 
bottom  plate  to  top  plate. 
See  780  CMR  3606.2.9. 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  204.8  mm. 


NOTE:  A  third  stud  and/or  anchor  partition 
intersection  backing  studs  may  be  omitted  through 
the  use  of  wood  backup  cleats,  metal  dry  wall  clips 
or  other  approved  devices  that  will  serve  as  an 
adequate  backing  for  the  facing  materials 


TABLE  3606.2.6 
MINIMUM  SPANS  FOR  HEADERS  LOCATED  OVER  OPENINGS  IN  WALLS 


SIZE  OF  HEADER1,2 

HEADERS  IN  BEARING  WALLS2 

HEADERS  EM 

WALLS  NOT 

SUPPORTING 

FLOORS  OR  ROOFS 

Supporting  Roof  Only 

One  Story  Above 

Two  Stories  Above 

2x4 
2x6 
2x8 
2x  10 
2x  12 

4 
6 
8 
10 
12 

4 
6 
8 
10 

6 
8 

10 
12 
16 

For  SI:  1  inch  =  25.4  mm,  1  foot  304.8  mm. 

1.  Nominal  four-inch  thick  single  headers  may  be  substituted  for  double  members. 

2.  Spans  are  based  on  No.  2  Grade  Lumber  with  ten-foot  tributary  floor  and  roof  loads. 


534 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


FIGURE  3606.2.6.2 
TYPICAL  PLYWOOD  BOX  HEADER  CONSTRUCTION 


For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 
1    The  top  plate  shall  be  continuous  over  header. 

2.  Jack  studs  shall  be  used  for  spans  over  four  feet. 

3.  Cripple  spacing  shall  be  the  same  as  for  studs. 

4.  Plywood  faces  shall  be  single  pieces  of  :  /32-inch-thick  C-D  (exterior  glue)  or  better,  installed  on  the  interior  or 
exterior  or  both  sides  of  the  header. 

5.  Plywood  faces  shall  be  nailed  to  framing  and  cripples  with  8d  common  nails  spaced  three  inches  o.c.  staggering 
alternate  nails  'A  inch 


TABLE  3606.2.6.2 

MAXIMUM  SPANS  FOR  PLYWOOD  BOX 

HEADERS  (feet)1 


HEADER 

coNSTRUcnopr 

HEADER 
DEPTH 

(inches) 

HOUSE  DEPTH  (feet)  1 

24 

26 

28 

30 

32 

Plywood  One  Side 

9      . 

15 

4 
5 

4 
5 

3 

4 

3 
3 

3 

Plywood  Both  Sides 

9 
15 

7 
8 

5 

8 

5 

7 

4 

6 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 

1.  Spans  are  based  on  single  story  with  clear-span 
trussed  roof  or  two  story  with  floor  and  roof  supported  by 
interior-bearing  walls. 

2.  See  Figure  3606.2.6.2  for  construction  details. 

3606.2.7  Firestopping:  Firestopping  shall  be 
provided  to  cut  off  all  concealed  draft  openings 
(both  vertical  and  horizontal)  and  to  form  an 
effective  fire  barrier  between  stories,  and  between  a 
top  story  and  the  roof  space.  Firestopping  shall  be 
provided  in  wood-frame  construction  in  the 
following  locations. 

1.  In  concealed  spaces  of  stud  walls  and 
partitions,  including  furred  spaces,  at  the  ceiling 
and  floor  level; 

2.  At  all  interconnections  between  concealed 
vertical  and  horizontal  spaces  such  as  occur  at 
soffits,  drop  ceilings,  cove  ceilings,  etc.; 


3.  In  concealed  spaces  between  stair  stringers  at 
the  top  and  bottom  of  the  run; 

4.  At  openings  around  vents,  pipes,  ducts, 
chimneys  and  fireplaces  at  ceiling  and  floor  level, 
with  noncombustible  materials. 

3606.2.7.1  Materials:  Except  as  provided  in 
780  CMR  3606.2.7  item  4,  fire-stopping  shall 
consist  of  two-inch  (51  mm)  nominal  lumber,  or 
two  thicknesses  of  one-inch  (25  mm)  nominal 
lumber  with  broken  lap  joints,  or  one  thickness  of 
/32-inch  (18  mm)  wood  structural  panels  with 
joints  backed  by  /32-inch  (18  mm)  wood 
structural  panels  or  one  thickness  of  %-inch  (19 
mm)  particleboard  with  joints  backed  by  %-inch 
(19  mm)  particleboard,  '/i-inch  (12.7  mm) 
gypsum  board,  or  /4-inch  (6.4  mm)  cement-based 
mill-board 

3606.2.7.1.1  Unfaced  fiberglass:  Unfaced 
fiberglass  bat  insulation  used  as  firestopping 
shall  fill  the  entire  cross  section  of  the  wall 
cavity  to  a  minimum  height  of  1 6  inches  (406 
mm)  measured  vertically.  When  piping, 
conduit  or  similar  obstructions  are 
encountered,  the  insulation  shall  be  packed 
tightly  around  the  obstruction. 

3606.2.7.1.2  Firestopping  integrity:  The 
integrity  of  all  firestops  shall  be  maintained. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


535 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3606.2.8  Cripple  walls:  Foundation  cripple  walls 
shall  be  framed  of  studs  not  less  in  size  than  the 
studs  supported.  When  exceeding  four  feet  (1219 
mm)  in  height,  such  walls  shall  be  framed  of  studs 
having  the  size  required  for  an  additional  story. 

3606.2.8.1  Bracing:  Such  walls  having  a  stud 
height  exceeding  14  inches  (356  mm)  shall  be 
considered  to  be  first  story  walls  for  the  purpose 
of  determining  the  bracing  required  by  780  CMR 
3606.2.9.  Stud  walls  less  than  14  inches  (356 
mm)  in  height  shall  be  sheathed  with  plywood  or 
wood  structural  panels  attached  to  both  the  top 
and  bottom  plates  in  accordance  with  Table 
3606.2.3a,  or  the  walls  shall  be  constructed  of 
solid  blocking. 

3606.2.9  Wall  bracing:  Exterior  and  foundation 
wall  panels  of  frame  construction  shall  be  braced 
with  one-inch-by-four-inch  (25  mm  by  102  mm)  let- 
in  braces,  or  approved  metal  strap  devices  installed 
in  accordance  with  the  manufacturer's  specifications; 
wood  structural  panels  in  accordance  with  Table 
3606.2.3b,  particleboard  in  accordance  with  Table 
3606.2.3c,  gypsum  sheathing,  wallboard  or  veneer 
base  applied  vertically  or  horizontally  to  studs 
spaced  not  more  than  24  inches  (610  mm)  on  center 
and  fastened  in  accordance  with  Table  3606.2.3a, 
fiberboard  sheathing  applied  vertically  to  studs 
spaced  not  more  than  16  inches  (406  mm)  on  center 
and  fastened  in  accordance  with  Table  3606.2.3a, 
Portland  cement  plaster  applied  over  metal  lath 
attached  to  studs  spaced  not  more  than  16  inches 
(406  mm)  on  center  in  accordance  with  780  CMR 
3607.3.6,  or  other  approved  material.  If  let-in 
bracing  is  used,  it  shall  be  let  into  the  top  and  bottom 
plates  and  the  intervening  studs,  placed  at  not  more 
than  60  degrees  or  less  than  45  degrees  from  the 
horizontal  and  attached  to  the  framing  in 
conformance  with  Table  3606.2.3a.  Structural 
sheathing  and  one-inch-by-four-inch  (25  mm  by  102 
mm)  let-in  braces  shall  be  installed  in  accordance 
with  Table  3606.2.9  and  fastened  in  accordance 
with  Table  3606.2.3a. 

Exception:  The  minimum  48-inch  (1219  mm) 
braced  wall  panel  width  required  by  Table 
3606.2.9  may  be  replaced  by  an  alternate  braced 
wall  panel  constructed  in  accordance  with  the 
following: 

1.  In  one-story  buildings,  each  panel  shall 
have  a  width  of  not  less  than  32  inches  (813 
mm)  and  a  height  of  not  more  than  ten  feet 
(3048  mm).   Each  panel  shall  be  sheathed  on 


one  face  with  %-inch  (9.5  mm)  minimum 
thickness  wood  structural  panel  sheathing 
nailed  with  8d  common  or  galvanized  box  nails 
in  accordance  with  Table  3606.2.3a  and 
blocked  at  all  edges.  Two  anchor  bolts 
installed  in  accordance  with  Figure  3604.3.1a 
or  approved  equivalent  shear  connectors  shall 
be  provided  in  each  panel.  Each  panel  end  stud 
shall  have  a  tie-down  device  fastened  to  the 
foundation,  capable  of  providing  an  approved 
uplift  capacity  of  not  less  than  1,800  pounds 
(816  kg).  The  tie-down  device  shall  be 
installed  in  accordance  with  the  manufacturer's 
recommendations.  The  panels  shall  be 
supported  directly  on  a  foundation  or  on  floor 
framing  supported  directly  on  a  foundation. 
This  foundation  or  footing  shall  be  continuous 
across  the  entire  length  of  the  braced  wall  line 
and  shall  be  reinforced  with  not  less  than  two 
No.  4  bars. 

2.  In  the  first  story  of  two-story  buildings, 
each  braced  wall  panel  shall  be  constructed  in 
accordance  with  780  CMR  3606.2.9  Exception 
item  1 ,  except  that  the  wood  structural  panel 
sheathing  shall  be  applied  to  both  faces,  three 
anchor  bolts  or  approved  equivalent  shear 
connectors  shall  be  provided,  and  tie-down 
device  uplift  capacity  shall  not  be  less  than 
3,000  pounds  (1361  kg). 

780  CMR  36063  METAL 
3606.3.1  General:  Metal  structural  elements  in 
walls  and  partitions  may  be  either  hot-rolled 
structural  shapes  or  bar  sections  or  members  cold 
formed  to  shape  from  sheet,  strip  or  plate,  or  a 
fabricated  combination  thereof.  Members  shall  be 
straight  and  free  of  any  defects  which  would 
significantly  affect  their  structural  performance 
Structural  elements  in  walls  and  partitions  shall 
be  constructed  of  materials  and  designed  in 
accordance  with  AA  SAA30,  the  AISI 
"Specification  for  the  Design,  Fabrication  and 
Erection  of  Structural  Steel  for  Buildings  ",  as 
listed  in  Appendix  A. 

780  CMR  3606.4  GENERAL  MASONRY 
CONSTRUCTION 

3606.4.1  General:  Masonry  construction  shall  be 
designed  and  constructed  in  accordance  with  the 
provisions  of  780  CMR  3606.4  or  in  accordance 
with  the  provisions  of  ACI  530/ASCE  5/TMS  402, 
as  listed  in  Appendix  A. 


536 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


TABLE  3606.2.9 
WALL  BRACING 


CONDITION1 

TYPE  OF  BRACE 

AMOUNT  OF  BRACING2-3 

One  story 

Top  of  two  story  or  three  story. 
First  story  of  two  story. 
Second  Story. 

One-inch-by-four-inch  let  in 
bracing  or  structural  sheathing. 

Located  at  each  end  and  at  least 
every  25  feet  of  wall  length 

First  story  of  three  story 

Structural  sheathing 

Miminum  48-inch-wide  panels. 
Located  as  required  for  let-in 
bracing. 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 

1     Foundation  wall  panels  braced  same  as  story  above. 

2.  Where  structural  sheathing  is  used,  each  braced  panel  must  be  at  least  48  inches  in  width. 

3.  Structural  sheathing  and  let-in  bracing  shall  be  located  at  each  end  or  as  near  thereto  as  possible. 


3606.4.2  Thickness  of  masonry:  The  nominal 
thickness  of  masonry  walls  shall  conform  to  the 
requirements  of  780  CMR  3606.4.2.1  through 
3606.4.2.4 

3606.4.2.1  Minimum  thickness:  The  minimum 
thickness  of  masonry  bearing  walls  more  than  one 
story  in  height  shall  be  eight  inches  (203  mm). 
Solid  masonry  walls  of  one  story  dwellings  and 
garages  shall  not  be  less  than  six  inches  (153  mm) 
in  thickness  when  not  greater  than  nine  feet  (2743 
mm)  in  height,  provided  that  when  gable 
construction  is  used,  an  additional  six  feet  (1829 
mm)  is  permitted  to  the  peak  of  the  gable. 
Masonry  walls  shall  be  laterally  supported  in 
either  the  horizontal  or  vertical  direction  at 
intervals  as  required  by  780  CMR  3606.4.8. 

3606.4.2.2  Rubble  stone  masonry  wall:  The 

minimum  thickness  of  rough,  random  or  coursed 
rubble  stone  masonry  walls  shall  be  16  inches 
(406  mm). 

3606.4.2.3  Change  in  thickness:  Masonry  walls 
comprised  of  hollow  units  or  of  masonry  bonded 
hollow  units  that  decrease  in  thickness  shall  be 
constructed  with  a  course  of  solid  masonry 
between  the  wall  below  and  the  thinner  wall 
above,  or  shall  be  constructed  with  special  units 
or  construction  that  shall  transmit  the  loads 
from  face  shells  or  wythes  above  to  those  below. 

3606.4.2.4  Parapet  walls:  Unreinforced  solid 
masonry  parapet  walls  shall  not  be  less  than  eight 
inches  (203  mm)  in  thickness  and  the  height  of  the 
parapet  shall  not  exceed  four  times  its  thickness. 
Unreinforced  hollow  unit  masonry  parapet  walls 
shall  not  be  less  than  eight  inches  (203  mm)  in 
thickness,  and  the  height  of  the  parapet  shall  not 
exceed  three  times  its  thickness. 

3606.4.3  Corbeled  masonry:  Solid  masonry  units 
shall  be  used  for  corbeling.  The  maximum  corbeled 
projection  beyond  the  face  of  the  wall  shall  not  be 
more  than  Vz  of  the  wall  thickness  or  Vz  the  wythe 
thickness  for  hollow  walls;  the  maximum  projection 
of  one  unit  shall  not  exceed  Vithe  height  of  the  unit 
or  V3  the  thickness  at  right  angles  to  the  wall.  The 
top  course  of  corbels  shall  be  a  header  course  when 


the  corbeled  masonry  is  used  to  support  floor  or 
roof-framing  members 

3606.4.3.1  Support  conditions:  Cavity  wall  or 
masonry  veneer  construction  may  be  supported  on 
an  eight-inch  (203  mm)  foundation  wall,  provided 
the  eight-inch  (203  mm)  wall  is  corbeled  with 
solid  masonry  to  the  width  of  the  wall  system 
above.  The  total  horizontal  projection  of  the 
corbel  shall  not  exceed  two  inches  (5 1  mm)  with 
individual  corbels  projecting  not  more  than  Vs  the 
thickness  of  the  unit  or  Vz  the  height  of  the  unit. 
The  top  course  of  all  corbels  shall  be  a  header 
course. 

3606.4.4  Allowable  stresses:  Allowable 
compressive  stresses  in  masonry  shall  not  exceed  the 
values  prescribed  in  Table  3606.4.4  In  determining 
the  stresses  in  masonry,  the  effects  of  all  loads  and 
conditions  of  loading  and  the  influence  of  all  forces 
affecting  the  design  and  strength  of  the  several  parts 
shall  be  taken  into  account. 

3606.4.4.1  Combined  units:  In  walls  or  other 
structural  members  composed  of  different  kinds 
or  grades  of  units,  materials  or  mortars,  the 
maximum  stress  shall  not  exceed  the  allowable 
stress  for  the  weakest  of  the  combination  of  units, 
materials  and  mortars  of  which  the  member  is 
composed.  The  net  thickness  of  any  facing  unit 
which  is  used  to  resist  stress  shall  not  be  less  than 
IV2  inches  (38  mm). 

3606.4.5  Piers:  The  unsupported  height  of  masonry 
piers  shall  not  exceed  ten  times  the  least  dimension 
of  the  pier.  When  structural  clay  tile  or  hollow 
concrete  masonry  units  are  used  for  isolated  piers  to 
support  beams  and  girders,  the  cellular  spaces  shall 
be  filled  solidly  with  concrete  or  Type  M  or  S 
mortar.  When  hollow  masonry  units  are  solidly 
filled  with  concrete  or  Type  M  S  or  N  mortar,  the 
allowable  compressive  stress  may  be  increased  as 
provided  in  Table  3606.4  4. 

Exception:  Unfilled  hollow  piers  may  be  used  if 
the  unsupported  height  of  the  pier  is  not  more 
than  four  times  its  least  dimension. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


537 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3606.4.5.1  Pier  cap:  Hollow  piers  shall  be  capped 
with  four  inches  (102  mm)  of  solid  masonry  or 
concrete  or  the  cavities  of  the  top  course  shall  be 
filled  with  concrete  or  grout  or  other  methods 
approved  by  the  building  official. 

TABLE  3606.4.4 

ALLOWABLE  COMPRESSIVE  STRESSES 

FOR  EMPIRICAL  DESIGN  OF  MASONRY 


ALLOWABLE 

COMPRESSIVE 

STRESSES1 

GROSS 

CONSTRUCTION; 

CROSc 

COMPRESSIVE  STRENGTH 

sectio 

NAL 

OF  UNIT,  GROSS  AREA 

AREA 

Type  M  or 

TypeN 

S  Mortar 

Mortar 

Solid  masonry  of  brick  and  other 

solid  units  of  clay  or  shale;  sand 

lime  or  concrete  brick: 

8,000 +  psi 

350 

300 

4,500  psi 

225 

200 

2,500  psi 

160 

140 

1,500  psi 

115 

100 

Grouted3  masonry,  of  clay  or  shale; 

sand-lime  or  concrete: 

4,500  psi 

225 

200 

2,500  psi 

160 

140 

1,500  psi 

115 

100 

Solid  masonry  of  solid  concrete 

masonry  units: 

3,000  psi 

225 

200 

2,000  psi 

160 

140 

1,200  psi 

115 

100 

Masonry  of  hollow  load  bearing 

units: 

2,000  psi 

140 

120 

1,500  psi 

115 

100 

1,000  psi 

75 

70 

700  psi 

60 

55 

Hollow  walls  (cavity  or  masonry 

bounded  )  solid  units: 

2,500  psi 

160 

140 

1,500  psi 

115 

100 

Hollow  units 

75 

70 

Stone  ashlar  masonry: 

Granits 

720 

640 

Limestone  or  marble 

450 

400 

Sandstone  or  cast  stone 

360 

320 

Rubble  Stone  Masonry: 

Coarse,  rough  or  random 

120 

100      | 

For  SI:  1  psi  =  6.895  kPa. 

1.  Linear  interpolation  shall  be  used  for  detennining 
allowable  stresses  for  masonry  units  having 
comprehensive  strengths  which  are  intermediate  between 
those  given  in  this  table. 

2.  Gross  cross-sectional  area  shall  be  calculated  on  the 
actual  rather  than  nominal  dimensions. 

3.  See  780  CMR  3606.7  Grouted  Masonry. 


4.  Where  floor  and  roof  loads  are  carried  upon  one 
wythe,  the  gross  cross-sectional  area  is  that  of  the  wythe 
under  load;  if  both  wythes  are  loaded,  the  gross  cross- 
sectional  area  is  that  of  the  wall  minus  the  area  of  cavity 
between  the  wythes.  Walls  bonded  with  metal  ties  shall 
be  considered  as  cavity  walls  unless  the  collar  joints  are 
filled  with  mortar  or  grout 

3606.4.6  Chases:  Chases  and  recesses  in  masonry 
walls  shall  not  be  deeper  than  Va  the  wall  thickness, 
and  the  maximum  length  of  a  horizontal  chase  or 
horizontal  projection  shall  not  exceed  four  feet 
(1219  mm),  and  shall  have  at  least  eight  inches  (203 
mm)  of  masonry  in  back  of  the  chases  and  recesses 
and  between  adjacent  chases  or  recesses  and  the 
jambs  of  openings.  Chases  and  recesses  in  masonry 
walls  shall  be  designed  and  constructed  so  as  not  to 
reduce  the  required  strength  or  required  fire 
resistance  of  the  wall  and  in  no  case  shall  a  chase  or 
recess  be  permitted  within  the  required  area  of  a 
pier.  Masonry  directly  above  chases  or  recesses 
wider  than  12  inches  (305  mm)  shall  be  supported 
on  noncombustible  lintels. 

3606.4.7  Stack  bond:  In  unreinforced  masonry 
construction  where  units  are  laid  in  stack  bond, 
longitudinal  reinforcement  consisting  of  not  less 
than  two  continuous  wires  each  with  a  minimum 
aggregate  cross-sectional  area  of  0.017  square  inches 
(1 1  mm2)  shall  be  provided  in  horizontal  bed  joints 
spaced  not  more  than  16  inches  (406  mm)  on  center 
vertically. 

3606.4.8  Lateral  support:  Masonry  walls  shall  be 
laterally  supported  in  either  the  horizontal  or  the 
vertical  direction.  The  maximum  spacing  between 
lateral  supports  shall  not  exceed  the  distances 
allowed  in  Table  3606.4.8.  Lateral  support  shall  be 
provided  by  cross  walls,  pilasters,  buttresses,  or 
structural  frame  members  when  the  limiting  distance 
is  taken  horizontally,  or  by  floors  or  roofs  when  the 
limiting  distance  is  taken  vertically. 

3606.4.8.1  Horizontal  lateral  support:  Lateral 
support  in  the  horizontal  direction  provided  by 
intersecting  masonry  walls  shall  be  provided  by 
one  of  the  methods  defined  in  780  CMR 
3606.4.8.1.1  or  3606.4.8.1.2. 

3606.4.8.1.1  Bonding  pattern:  50%  of  the 
units  at  the  intersection  shall  be  laid  in  an 
overlapping  masonry  bonding  pattern,  with 
alternate  units  having  a  bearing  of  not  less  than 
three  inches  (76  mm)  on  the  unit  below. 


538 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


TABLE  3606.4.8 

SPACING  OF  LATERAL  SUPPORT  FOR 

MASONRY  WALLS 


CONSTRUCTION 

MAXIMUM  WALL 

LENGTH  TO  THICKNESS 

OR  WALL  HEIGHT  TO 

THICKNESS1'2 

Bearing  Walls 

Solid  or  solid  grouted 
All  others 

20 
18 

Nonbeanng  walls 
Exterior 
Exterior 

18 
36 

For  SI:  1  foot  =  304.8  mm. 

1.  Except  for  cavity  walls  and  cantilevered  walls,  the 
thickness  of  a  wall  shall  be  its  nominal  thickness 
measured  perpendicular  to  the  face  of  the  wall.  For 
ca'vity  walls,  the  thickness  shall  be  determined  as  the  sum 
of  the  nominal  thicknesses  of  the  individual  wythes.  For 
cantilever  walls,  except  for  parapets,  the  ratio  of  the 
height  to  nominal  thickness  shall  not  exceed  six  for  solid 
masonry,  or  four  for  hollow  masonry.  For  parapets,  see 
780  CMR  3606.4.2.4. 

2.  An  additional  unsupported  height  of  six  feet  is 
permitted  for  gable  end  walls. 

3606.4.8.1.2  Metal  reinforcement:  Interior 
nonload-bearing  walls  shall  be  anchored  at 
their  intersections,  at  vertical  intervals  of  not 
more  than  16  inches  (406  mm)  with  joint 
reinforcement  of  at  least  9  gage,  or  V*  inch  (6.4 
mm)  galvanized  mesh  hardware  cloth. 
Intersecting  masonry  walls,  other  than  interior 
nonloadbearing  walls,  shall  be  anchored  at 
vertical  intervals  of  not  more  than  eight  inches 
(203  mm)  with  joint  reinforcement  of  at  least  9 
gage  and  shall  extend  at  least  30  inches  (762 
mm)  in  each  direction  at  the  intersection. 
Other  metal  ties,  joint  reinforcement  or 
anchors,  if  used,  shall  be  spaced  to  provide 
equivalent  area  of  anchorage  to  that  required 
by  780  CMR  3606.4.8. 

3606.4.8.2  Vertical  lateral  support:  Vertical 
lateral  support  of  masonry  walls  shall  be  provided 
in  accordance  with  one  of  the  methods  in 
780  CMR  3606.4.8.2. 1  or  3606.4.8.2.2. 

3606.4.8.2.1  Roof  structures:  Masonry  walls 
shall  be  anchored  to  roof  structures  with  metal 
strap  anchors,  /4-inch  (12.7  mm)  bolts,  or  other 
approved  anchors  spaced  not  more  than  six  feet 
(1829  mm)  on  center.  Anchors  shall  be 
embedded  at  least  16  inches  (406  mm)  into  the 
masonry,  or  be  hooked  or  welded  to  bond  beam 
reinforcement  placed  not  less  than  six  inches 
(153  mm)  from  the  top  of  the  wall. 

3606.4.8.2.2  Floor  diaphragms:  Masonry 
walls  shall  be  anchored  to  floor  diaphragms  at 
intervals  not  to  exceed  six  feet  (1829  mm). 
Support  shall  be  provided  by  metal  strap 
anchors  or  '/i-inch-diameter  (12.7  mm)  bolts 
installed  as  shown  in  Figure  3606.4.10a,  or  by 
other  approved  methods. 


3606.4.9  Lintels:  Masonry  over  openings  shall  be 
supported  by  steel  lintels,  reinforced  concrete  or 
masonry  lintels  or  masonry  arches,  designed  to 
support  load  imposed. 

3606.4.10  Anchorage.  Masonry  walls  shall  be 
anchored  to  floor  and  roof  systems  in  accordance 
with  the  details  shown  in  Figure  3606.4.10a, 
3606.4.10b  or  3606.4.10c.  Footings  may  be 
considered  as  points  of  lateral  support. 

3606.4.11  Reinforcement:  Masonry  walls  subject  to 
wind  loads  of  30  pounds  per  square  foot  (1.44 
kN/m2)  or  greater,  shall  be  constructed  in  accordance 
with  the  requirements  of  780  CMR  3606.4.11  and 
Figures  3606.4.10b  and  3606.4.10c  In  addition,  the 
minimum  area  of  reinforcement  shall  not  be  less 
than  0.002  times  the  gross  cross-sectional  area  of  the 
wall,  not  more  than  %  of  which  may  be  used  in 
either  direction.  No  required  vertical  reinforcement 
shall  be  less  than  %  inch  (9.5  mm)  in  diameter. 
Principal  wall  reinforcement  shall  have  a  maximum 
spacing  of  four  feet  (1219  mm)  on  center. 

3606.4.12  Protection  for  reinforcement:  All  bars 
shall  be  completely  embedded  in  mortar  or  grout, 
loint  reinforcement  embedded  in  horizontal  mortar 
joints  shall  not  have  less  than  5/s-inch  (15.9  mm) 
mortar  coverage  from  the  exposed  face.  All  other 
reinforcement  shall  have  a  minimum  coverage  of 
one  bar  diameter  over  all  bars,  but  not  less  than  % 
inch  (19  mm).  Where  exposed  to  weather  or  soil, 
the  minimum  coverage  shall  be  two  inches  (5 1  mm). 

3606.4.13  Beam  supports:  Beams,  girders  or  other 
concentrated  loads  supported  by  a  wall  or  column 
shall  have  a  bearing  of  at  least  three  inches  (76  mm) 
in  length  measured  parallel  to  the  beam  upon  solid 
masonry  not  less  than  four  inches  (102  mm)  in 
thickness,  or  upon  a  meta!  bearing  plate  of  adequate 
design  and  dimensions  to  distribute  the  load  safely, 
or  upon  a  continuous  reinforced  masonry  member 
projecting  not  less  than  four  inches  (102  mm)  from 
the  face  of  the  wall. 

3606.4.13.1  Joist  bearing:  loists  shall  have  a 
bearing  of  not  less  than  lVi  inches  (38  mm), 
except  as  provided  in  780  CMR  3606.4.13,  and 
shall  be  supported  in  accordance  with  Figures 
3606.4.10b  and  3606.4.10c. 

3606.4.14  Metal  accessories:  loint  reinforcement, 
anchors,  ties  and  wire  fabric  shall  conform  to  the 
following  reference  standards  as  listed  in 
Appendix  A:  ASTM  A  82  for  joint  reinforcement, 
wire  anchors  and  ties;  ASTM  A  36  for  plate,  headed 
and  bent-bar  anchors;  ASTM  A  510  for  corrugated 
sheet  metal  anchors  and  ties;  ASTM  B  227  for 
copper-clad  steel  wire  ties  or  ASTM  A  167  for 
stainless  steel  hardware. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


539 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3606.4.14.1  Corrosion  protection:  Minimum 
corrosion  protection  of  joint  reinforcement, 
anchor  ties  and  wire  fabric  for  use  in  masonry 
wall  construction  shall  conform  to  Table 
3606.4.14.1. 

TABLE  3606.4.14.1 
MINIMUM  CORROSION  PROTECTION 


MASONRY  METAL 
ACCESSORY 

STANDARD 

Joint  reinforcement,  interior 
walls 

ASTMA641,Classl 

Wire  ties  or  anchors  in  exterior 
walls  completely  embedded  in 
mortor  or  grout 

ASTMA641,Class3 

Wire  ties  or  anchors  in  exterior 
walls  not  completely  embedded 
in  mortor  or  grout 

ASTMA153,ClassB-2 

Joint  reinforcement  in  exterior 
walls  or  interior  walls  exposed  to 
moist  environment 

ASTMA153,ClassB-2 

Sheet  metal  ties  or  anchors 
exposed  to  weather 

ASTMA  153,  Class  B-2 

Sheet  metal  ties  or  anchors 
completely  embedded  in  mortar 
or  grout 

ASTM  A  525,  Class  G-60 

Stainless  steel  hardware  for  any 
exposure 

ASTMA  167,  Type  304 

540 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 

FIGURE  3606.4.10a 
ANCHORAGE  REQUIREMENTS  FOR  MASONRY  WALLS 


SHEATHfC  NALED  N  ACCORDANCE 
WITH  TABLE  3606.2.3a 


BOLT  EMBEDDED  4" 


JOIST  SPAN 

BOLT  SIZE  AND  SPACING 

Roof 

Floor 

Iff 

7/g<a>3'-6- 

>l2@Z4T 
7/8@2"-9~ 

|        I0'-I5' 

»/2  @  l'-9" 

l/2 @  l'-4" 

'/scar-o- 

1 

is'-ar 

V2@  l'-3' 

'/8@y-o" 

i/2  @  r-rr 
7/8@  r-fi" 

SHEATHNG  NAILED  N  ACCORDANCE  " 
WITH  TABLE  3606.2.3* 


JOISTS 

PERPENDCULAR 

TO  WALL 


SEE  TABLE  ABOVE 
FOR  BOLT  AND  SIZE 
OFSPACUG 


WHERE  BOLTS  ARE  LOCATED  IN  HOLLOW  MASONRY,  THE  CELLS  IN  THE  COURSES 
RECEIVING  THE  BOLTS  SHALL  BE  GROUTED  SOLID 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  psf =  0^0479  kN/rn2 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


541 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

FIGURE  3606.4.10b 

REQUIREMENTS  FOR  REINFORCED  GROUTED  MASONRY  CONSTRUCTION 

WHERE  WIND  LOADS  ARE  30  PSF  OR  GREATER 


NOTE:  CONTWLOUS  BONO  BEAU 
REOU1REDAT  EACH  FLOOR  OR 
CELNQ  LEVEL  OTHER  EQUIVALENT 
METHODS  OF  ANCHDRNG  THE  ROOF 
RUMMQ  MEMBERS  TO  THE  WALL 
MAYBE  APPROVED. 


WHERE  NTERIOR  STUD 
PAHTmON  MEETS  WALL. 
BOLT  END  STUD  WITH 
1/8"  I  BOLTS  J-O-O.C 


-UIN.W  GROUT 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  1  psf  =  0.0479  kN.rn^ 


542 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 

FIGURE  3606.4.10c 

REQUIREMENTS  FOR  REINFORCED  HOLLOW-UNIT  MASONRY  CONSTRUCTION 

WHERE  WEVD  LOADS  ARE  30  PSF  OR  GREATER 


NOTE  CONTMJOUS  BOND 
REOUIREDATEACH  FLOOR  OR  BEAM 
CEUN3  LEVEL  OTHER  EQUIVALENT 
METHOOS  OF  ANCHORING  THE  HOOF 

TO  THE  WALL 
UAY  BE  APPROVED. 


WSPSmON  OPENNG  NOT 
REQUIRED  IF  rSPECTED 
ATTHE  COURSE 


A  FULL  BED  JOINT  MUST  BE  PROVIDED.  ALL 
CELLS  CONTANINQ  VERTICAL  BARS  ARE  TO 
BE  FIXED  TO  TOP  OF  WALL  PROVIDE 
INSPECTION  OPENWG  AS  SHOWN  ON  DETAIL 
■A".  HORIZONTAL  BARS  ARE  TO  BE  LAID  AS 
SHOWN  ON  DETAL  "B".  UNTEL  BARS  ARE 
TO  BE  LAID  AS  SHOWN  ON  SECTION  "C". 


For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm.  1  psf  =  0.0479  kN/m2 


9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


543 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  3606.5  UNIT  MASONRY 

3606.5.1  Placing  mortar  and  masonry  units: 

3606.5.1.1  Bed  and  head  joints:  Unless 
otherwise  required  or  indicated  on  the  project 
drawings,  head  and  bed  joints  shall  be  %  inch 
(9.5  mm)  thick,  except  that  the  thickness  of  the 
bed  joint  of  the  starting  course  placed  over 
foundations  shall  not  be  less  than  Vt  inch  (6.4 
mm)  and  not  more  than  %  inch  (19  mm). 

3606.5.1.1.1  Mortar  joint  thickness 
tolerance:  Mortar  joint  thickness  shall  be 
within  the  following  tolerances  from  the 
specified  dimensions: 

bed  joint ±Vs  inch  (3.2  mm) 

head  joint -V*  inch  (6.4  mm),  +%  inch  (9.5  mm) 

collar  joints  ...  -V*  inch  (6.4  mm),  +%  inch  (9.5  mm) 
Exception:  Nonload-bearing  masonry 
elements  and  masonry  veneers  designed  and 
constructed  in  accordance  with  780  CMR 
3607.3.7  are  not  required  to  meet  these 
tolerances 

3606.5.1.2  Masonry  unit  placement:  The  mortar 
shall  be  sufficiently  plastic  and  units  shall  be 
placed  with  sufficient  pressure  to  extrude  mortar 
from  the  joint  and  produce  a  tight  joint.  Deep 
furrowing  of  bed  joints  which  produces  voids 
shall  not  be  permitted  Any  units  disturbed  to  the 
extent  that  the  initial  bond  is  broken  after  initial 
placement  shall  be  removed  and  relaid  in  fresh 
mortar.  Surfaces  to  be  in  contact  with  mortar 
shall  be  clean  and  free  of  deleterious  materials. 

3606.5.1.2.1  Solid  masonry:  All  solid 
masonry  units  shall  be  laid  with  full  head  and 
bed  joints  and  all  interior  vertical  joints  that  are 
designed  to  receive  mortar  shall  be  filled  solid. 

3606.5.1.2.2  Hollow  masonry:  All  head  and 
bed  joints  of  hollow  masonry  units  shall  be 
filled  solidly  with  mortar.  The  mortar  shall 
extend  a  distance  from  the  face  of  the 
masonry  unit  that  shall  measure  not  less  than 
the  thickness  of  the  face  shell 

3606.5.2  Installation  of  wall  ties:  The  installation 
of  wall  ties  shall  be  as  follows: 

1 .  The  ends  of  wall  ties  shall  be  embedded  in 
mortar  joints.  Wall  tie  ends  shall  engage  outer 
face  shells  of  hollow  units  by  at  least  lA  inch 
(12.7  mm).  Wire  wall  ties  shall  be  embedded  at 
least  ll/2  inches  (38  mm)  into  the  mortar  bed  of 
solid  masonry  units  or  solid  grouted  hollow  units. 

2.  Wall  ties  shall  not  be  bent  after  being 
embedded  in  grout  or  mortar. 

780  CMR  3606.6  MULTIPLE  WYTHE 
MASONRY 

3606.6.1    General:    The   facing   and   backing   of 
multiple  wythe  masonry  walls  shall  be  bonded  in 


accordance  with  780  CMR 3606.6.1.1,  3606.6.1.2  or 
3606.6.1.3.  In  cavity  walls,  neither  the  facing  nor 
the  backing  shall  be  less  than  three  inches  (76  mm) 
nominal  in  thickness  and  the  cavity  shall  not  be 
more  than  four  inches  (102  mm)  nominal  in  width. 
The  backing  shall  be  at  least  as  thick  as  the  facing. 

Exception:  Cavities  may  exceed  the  four-inch 
(102  mm)  nominal  dimension  provided  tie  size 
and  tie  spacing  have  been  established  by 
calculation. 

3606.6.1.1  Bonding  with   masonry   headers: 

Bonding  with  solid  or  hollow  masonry  headers 
shall  comply  with  780  CMR  3606.6.1.1.1  and 
3606.6.1.1.2. 

3606.6.1.1.1  Solid  units:  Where  the  facing  and 
backing  (adjacent  wythes)  of  solid  masonry 
construction  are  bonded  by  means  of  masonry 
headers,  no  less  than  4%  of  the  wall  surface  of 
each  face  shall  be  composed  of  headers 
extending  not  less  than  three  inches  (76  mm) 
into  the  backing.  The  distance  between 
adjacent  full-length  headers  shall  not  exceed  24 
inches  (610  mm)  either  vertically  or 
horizontally.  In  walls  in  which  a  single  header 
does  not  extend  through  the  wall,  headers  from 
the  opposite  sides  shall  overlap  at  least  three 
inches  (76  mm),  or  headers  from  opposite  sides 
shall  be  covered  with  another  header  course 
overlapping  the  header  below  at  least  three 
inches  (76  mm). 

3606.6.1.1.2  Hollow  units:  Where  two  or  more 
hollow  units  are  used  to  make  up  the  thickness 
of  a  wall,  the  stretcher  courses  shall  be  bonded 
at  vertical  intervals  not  exceeding  34  inches 
(864  mm)  by  lapping  at  least  three  inches  (76 
mm)  over  the  unit  below,  or  by  lapping  at 
vertical  intervals  not  exceeding  17  inches  (432 
mm)  with  units  which  are  at  least  50%  greater 
in  thickness  than  the  units  below. 

3606.6.1.2  Bonding  with  wall  ties  or  joint 
reinforcement:  Bonding  with  wall  ties  or  joist 
reinforcement  shall  comply  with  780  CMR 
3606.6.1.2.1  through  3606. 6.1.2.3 

3606.6.1.2.1  Bonding  with  wall  ties:  Bonding 
with  wall  ties,  except  as  required  by  780  CMR 
3606.6.1.2.2,  where  the  facing  and  backing 
(adjacent  wythes)  of  masonry  walls  are  bonded 
with  /I6-inch-diameter  (4.8  mm)  wall  ties 
embedded  in  the  horizontal  mortar  joints,  there 
shall  be  at  least  one  metal  tie  for  each  4'/2 
square  feet  (0  418  m  )  of  wall  area.  Ties  in 
alternate  courses  shall  be  staggered.  The 
maximum  vertical  distance  between  ties  shall 
not  exceed  24  inches  (610  mm),  and  the 
maximum  horizontal  distance  shall  not  exceed 
36  inches  (914  mm).  Rods  or  ties  bent  to 
rectangular  shape  shall  be  used  with  hollow 
masonry  units  laid  with  the  cells  vertically.  In 
other  walls,  the  ends  of  ties  shall  be  bent  to  90- 


544 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


degree  angles  to  provide  hooks  no  less  than 
two  inches  (51  mm)  long  Additional  bonding 
ties  shall  be  provided  at  all  openings,  spaced 
not  more  than  three  feet  (914  mm)  apart  around 
the  perimeter  and  within  12  inches  (305  mm) 
of  the  opening. 

3606.6.1.2.2  Bonding  with  adjustable  wall 
ties:  Where  the  facing  and  backing  (adjacent 
wythes)  of  masonry  are  bonded  with  adjustable 
wall  ties,  there  shall  be  at  least  one  tie  for  each 
2%  square  feet  (0.248  m2)  of  wall  area. 
Neither  the  vertical  nor  horizontal  spacing  of 
the  adjustable  wall  ties  shall  exceed  24  inches 
(610  mm).  The  maximum  vertical  offset  of 
bed  joints  from  one  wythe  to  the  other  shall  be 
1  l/i  inches  (32  mm).  The  maximum  clearance 
between  connecting  parts  of  the  ties  shall  be 
V16  inch  (1.6  mm).  When  pintle  legs  are  used, 
ties  shall  have  at  least  two  /16-inch-diameter 
(4.8  mm)  legs. 

3606.6.1.2.3  Bonding  with  prefabricated 
joint  reinforcement:  Where  the  facing  and 
backing  (adjacent  wythes)  of  masonry  are 
bonded  with  prefabricated  joint  reinforcement, 
there  shall  be  at  least  one  cross  wire  serving  as 
a  tie  for  each  2%  square  feet  (0.248  m  )  of 
wall  area.  The  vertical  spacing  of  the  joint 
reinforcement  shall  not  exceed  16  inches  (406 
mm).  Cross  wires  on  prefabricated  joint 
reinforcement  shall  not  be  smaller  than  No.  9 
gage.  The  longitudinal  wires  shall  be 
embedded  in  the  mortar. 

3606.6.1.3  Bonding  with  natural  or  cast  stone: 

Bonding  with  natural  and  cast  stone  shall  conform 
to  780  CMR  3606.6.1.3.1  and  3606.6.1 3.2 

3606.6.1.3.1  Ashlar  masonry:  Bonder  units  in 
ashlar  masonry  that  are  uniformly  distributed, 
shall  be  provided  to  the  extent  of  not  less  than 
10%  of  the  wall  area.  Such  bonder  units  shall 
extend  not  less  than  four  inches  (102  mm)  into 
the  backing  wall. 

3606.6.1.3.2  Rubble  stone  masonry:  Rubble 
stone  masonry  24  inches  (610  mm)  or  less  in 
thickness    shall    have    bonder   units   with    a 


maximum  spacing  of  three  feet  (914  mm) 
vertically  and  three  feet  (9 1 4  mm)  horizontally, 
and  if  the  masonry  is  of  greater  thickness  than 
24  inches  (610  mm),  shall  have  one  bonder  unit 
for  each  six  square  feet  (0.557  nr)  of  wall 
surface  on  both  sides 

3606.6.2  Masonry  bonding  pattern:  Masonry  laid 
in  running  and  stack  bond  shall  conform  to 
780  CMR  3606.6.2.1  and  3606.6.2.2. 

3606.6.2.1  Masonry  laid  in  running  bond:  In 

each  wythe  of  masonry  laid  in  running  bond,  head 
joints  in  successive  courses  shall  be  offset  by  not 
less  than  one-fourth  the  unit  length,  or  the 
masonry  walls  shall  be  reinforced  longitudinally 
as  required  in  780  CMR  3606.6.2.2. 

3606.6.2.2  Masonry  laid  in  stack  bond:  Where 
unit  masonry  is  laid  with  less  head  joint  offset 
than  in  780  CMR  3606.6.2.1,  the  minimum  area 
of  horizontal  reinforcement  placed  in  mortar  bed 
joints  or  in  bond  beams  spaced  not  more  than  48 
inches  (1219  mm)  apart,  shall  be  0.0007  times  the 
vertical  cross-sectional  area  of  the  wall 

780  CMR  3606.7  GROUTED  MASONRY 
3606.7.1  General:  Grouted  multiple- wythe  masonry 
is  a  form  of  construction  in  which  the  space  between 
the  wythes  is  solidly  filled  with  grout.  It  is  not 
necessary  for  the  cores  of  masonry  units  to  be  filled 
with  grout.  Grouted  hollow  unit  masonry  is  a  form 
of  construction  in  which  certain  cells  of  hollow  units 
are  continuously  filled  with  grout. 

3606.7.1.1  Mortar  and  grout:  Only  Type  M  or 
Type  S  mortar  mix  consisting  of  portland  cement, 
hydrated  lime  and  sand  in  accordance  with  ASTM 
C  270.  listed  in  Appendix  A,  and  the  proportion 
specifications  of  Table  3606.7.1.1a  shall  be  used 
to  construct  masonry  wythes.  Grout  shall  consist 
of  cementitious  material  and  aggregate  in 
accordance  with  ASTM  C  476,  listed  in 
Appendix  A,  and  the  proportion  specifications  of 
Table  3606. 7.1.1b  Type  M  or  Type  S  mortar  to 
which  sufficient  water  has  been  added  to  produce 
pouring  consistency  can  be  used  as  grout 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


545 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3606.7.1.1a 
MORTAR  PROPORTIONS1 


PROPORTIONS  BY  VOLUME  (Cementitious  Materials) 

Mortar 

Type 

Protland  Cement 
or  Blended  Cement 

Masonry  Cement 

Hydrated  Lime  or 
Lime  Putty 

Aggregate  Ratio 

(Measured  in  Damp, 

Loose  Conditions) 

MSN 

Cement-lime 

M 
S 
N 
0 

1 
1 
1 
1 

over  V*  to  V4 
over  54  to  1  Vi 
over  lVi  to  254 

Not  less  than  2%  and  not 
more  than  three  times  the 
sum  of  separate  volumes  of 
lime,  if  used,  and  cement 

Masonry 
cement 

M 
M 
S 

s 

N 
0 

1 

54 

1 
1 

! 
1 

! 

For  SI:  1  cubic  foot  =  0.0283  m\  1  pound  =  0.454  kg. 

1 .  For  the  purpose  of  these  specifications,  the  weight  of  one  cubic  foot  of  the  respective  materials  shall  be  considered  to  be  as 
follows:  Portland  Cement94  lb. 

Masonry  cementWeight  printed  on  bag 

Hydrated  lime40  lb. 

Lime  putty(quicklune)80  lb. 

Sand,  damp  and  loose80  lb.  of  dry  sand 

2.  Two  air-entraining  materials  shall  not  be  combined  in  mortar. 

TABLE  3606.7.1.1b 
GROUT  PROPORTIONS  BY  VOLUME  FOR  MASONRY  CONSTRUCTION 


TYPE 

PORTLAND  CEMENT 

OR  BLENDED  CEMENT 

SLAG  CEMENT 

HYDRATED  LIME 
OR  LIME  PUTTY 

AGGREGATE  MEASURED  IN  A  DAMP,  LOOSE 
CONDITION 

Fine 

Coarse 

Fine 

1 

0  to  '/,„ 

2%  to  three  times  the  sum  of  the 
volume  of  the  cementitious 
materials 

Coarse 

1 

0  to  710 

2lA  to  three  times  the  sum  of  the 
volume  of  the  cementitious 
materials 

One  to  two  times  the  sum 
of  the  volumes  of  the 
cementitious  materials 

3606.7.1.2  Grouting  requirements:  Maximum 
pour  heights  and  the  rninimum  dimensions  of 
spaces  provided  for  grout  placement  shall 
conform  to  Table  3606. 7.1.2.  If  the  work  is 
stopped  for  one  hour  or  longer,  the  horizontal 
construction  joints  shall  be  formed  by  stopping  all 
tiers  at  the  same  elevation  and  with  the  grout  one 
inch  (25  mm)  below  the  top. 

TABLE  3606.7.1.2 

GROUT  SPACE  DIMENSIONS  AND 

POUR  HEIGHTS 


GROUT 
TYPE 

GROUT 

POUR 

MAXIMUM 

HEIGHT 

(feet) 

MINIMUM 

WIDTH  OF 

GROUT 

SPACES ' 
(inches) 

MINIMUM 
GROUT2^  SPACE 

DIMENSIONS 
FOR  GROUTING 

CELLS  OF 
HOLLOW  UNITS 
(inches  =  43  inches) 

Fine 

1 

V, 

1'/2X2 

5 

2 

2x3 

12 

2'A 

21/2x3 

24 

3 

3x3 

Coarse 

1 

154 

154x3 

5 

2 

2'/2x3 

12 

2XA 

3x3 

24 

3 

3x4 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 

1    For  grouting  between  masonry  wythes. 

2.        Grout  space  dimension  is  the  clear  dimension 

between  any  masonry  protrusion  and  shall  be  increased 

by  the  horizontal  projection  of  the  diameters  of  the 

horizontal  bars  within  the  cross  section  of  the  grout 

space. 

3     Area  of  vertical  reinforcement  shall  not  exceed  6%  of 

the  area  of  the  grout  space. 

3606.7.1.3  Grout  space  (cleaning):  Provision 
shall  be  made  for  cleaning  grout  space.  Mortar 
projections  which  project  more  than  Vz  inch  (12.7 
mm)  into  grout  space  and  any  other  foreign  matter 
shall  be  removed  from  grout  space  prior  to 
inspection  and  grouting 

3606.7.1.4  Grout  placement:  Grout  shall  be  a 
plastic  mix  suitable  for  pumping  without 
segregation  of  the  constituents  and  shall  be  mixed 
thoroughly.  Grout  shall  be  placed  by  pumping  or 
by  an  approved  alternate  method  and  shall  be 


546 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  CONSTRUCTION 


placed  before  any  initial  set  occurs  and  in  no  case 
more  than  IV2  hours  after  water  has  been  added. 
Grouting  shall  be  done  in  a  continuous  pour,  in  lifts 
not  exceeding  four  feet  (1219  mm)  It  shall  be 
consolidated  by  puddling  or  mechanical  vibrating 
during  placing  and  reconsolidated  after  excess 
moisture  has  been  absorbed  but  before  plasticity  is 
lost. 

3606.7.1.4.1  Grout  pumped  through 
aluminum  pipes:  Grout  shall  not  be  pumped 
through  aluminum  pipes 

3606.7.1.5  Cleanouts:  Where  required  by  the 
building  official,  cleanouts  shall  be  provided  as 
specified  in  780  CMR  3606.7.1.5.  The  cleanouts 
shall  be  sealed  before  grouting  and  after 
inspection. 

3606.7.1.5.1  Grouted  multiple-wythe 
masonry:  Cleanouts  shall  be  provided  at  the 
bottom  course  of  the  exterior  wythe  at  each 
pour  of  grout  where  such  pour  exceeds  five 
feet  (1524  mm)  in  height. 

3606.7.1.5.2  Grouted  hollow  unit  masonry: 
Cleanouts  shall  be  provided  at  the  bottom 
course  of  each  cell  to  be  grouted  at  each  pour 
of  grout,  where  such  pour  exceeds  four  feet 
(1219  mm)  in  height. 

3606.7.1.6  Inspection:  Special  inspection  during 
grouting  shall  be  provided  where  required  by  the 
building  official. 

3606.7.2     Grouted     multiple-wythe     masonry: 

Grouted  multiple-wythe  masonry  shall  conform  to 
all  the  requirements  specified  in  780  CMR  3606.  7.1 
and  the  requirements  of  780  CMR  3606.7.2. 

3606.7.2.1  Bonding  of  backup  wythe:  Where  all 
interior  vertical  spaces  are  filled  with  grout  in 
multiple-wythe  construction,  masonry  headers 
shall  not  be  permitted  Metal  wall  ties  shall  be 
used  in  accordance  with  780  CMR  3606.6.1.2  to 
prevent  spreading  of  the  wythes  and  to  maintain 
the  vertical  alignment  of  the  wall.  Wall  ties  shall 
be  installed  in  accordance  with  780  CMR 
3606.6.1.2,  when  the  backup  wythe  in  multiple- 
wythe  construction  is  fully  grouted. 

3606.7.2.2  Grout  spaces:  Fine  grout  shall  be  used 
when  interior  vertical  space  to  receive  grout  does 
not  exceed  two  inches  (51  mm)  in  thickness. 
Interior  vertical  spaces  exceeding  two  inches  (5 1 
mm)  in  thickness  shall  use  course  or  fine  grout. 

3606.7.2.3  Grout  barriers:  Vertical  grout 
barriers  or  dams  shall  be  built  of  solid  masonry 
across  the  grout  space  the  entire  height  of  the  wall 
to  control  the  flow  of  the  grout  horizontally. 
Grout  barriers  shall  not  be  more  than  25  feet 
(7620  mm)  apart.  The  grouting  of  any  section  of 
a  wall  between  control  barriers  shall  be  completed 
in  one  day  with  no  interruptions  greater  than  one 
hour. 


3606.7.3  Reinforced  grouted  muitiple-wythe 
masonry:  Reinforced  grouted  multiple-wythe 
masonry  shall  conform  to  all  the  requirements 
specified  in  780  CMR  3606. 7.1  and  3606. 7.2  and  the 
requirements  of  780  CMR  3606.7.3 

3606.7.3.1  Construction:  The  thickness  of  grout 
or  mortar  between  masonry  units  and 
reinforcement  shall  not  be  less  than  Vi  inch  (6  4 
mm),  except  that  '/4-inch  (6  4  mm)  bars  may  be 
laid  in  horizontal  mortar  joints  at  least  V4  inch 
(12.7  mm)  thick,  and  steel  wire  reinforcement 
may  be  laid  in  horizontal  mortar  joints  at  least 
twice  the  thickness  of  the  wire  diameter 

3606.7.4  Reinforced     hollow     unit     masonry: 

Reinforced  hollow  unit  masonry  shall  conform  to  all 
the  requirements  of  780  CMR  3606.7.1  and  the 
requirements  of  780  CMR  3606.7.4. 

3606.7.4.1     Construction:     Requirements    for 

construction  shall  be  as  follows: 

1.  All  reinforced  hollow-unit  masonry  shall 
be  built  to  preserve  the  unobstructed  vertical 
continuity  of  the  cells  to  be  filled.  Walls  and 
cross  webs  forming  such  cells  to  be  filled  shall 
be  full-bedded  in  mortar  to  prevent  leakage  of 
grout.  All  head  and  end  joints  shall  be  solidly 
filled  with  mortar  for  a  distance  in  from  the 
face  of  the  wall  or  unit  not  less  than  the 
thickness  of  the  longitudinal  face  shells.  Bond 
shall  be  provided  by  lapping  units  in 
successive  vertical  courses. 
2  Cells  to  be  filled  shall  have  vertical 
alignment  sufficient  to  maintain  a  clear, 
unobstructed  continuous  vertical  cell  of 
dimensions  prescribed  in  Table  3606.  7.1.2 

3.  Vertical  reinforcement  shall  be  held  in 
position  at  top  and  bottom  and  at  intervals  not 
exceeding  200  diameters  of  the  reinforcement. 

4.  All  cells  containing  reinforcement  shall  be 
filled  solidly  with  grout.  Grout  shall  be  poured 
in  lifts  of  eight-foot  (2438  mm)  maximum 
height.  When  total  grout  pour  exceeds  eight 
feet  (2438  mm)  in  height,  the  grout  shall  be 
placed  in  lifts  not  exceeding  four  feet  (1219 
mm)  and  special  inspection  during  grouting 
shall  be  required 

5.  Horizontal  steel  shall  be  fully  embedded  by 
grout  in  an  uninterrupted  pour. 

780  CMR  3606.8  WINDOWS 
3606.8.1  Testing  and  certification:  Windows  shall 
be  tested  and  certified  to  indicate  compliance  with 
the  requirements  of  the  following  specifications: 

Aluminum:  AAMA  (ANSI)  101 

Wood:  ANSI/NWWDA  IS.  2 

Polyvinyl  Chloride:  ASTM  D  4099,  each  as  listed 

in  Appendix  A. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


547 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3606.S.2  Air  infiltration:  Regardless  of  the  type  or 

requirements  of  the  windows  set  forth  in  the 
aforementioned  specifications,  no  window  may  be 
selected  whose  air  infiltration  exceeds  0.50  cubic 
feet  per  minute  per  linear  foot  (0.236  L/s  per  mm)  of 
crack  when  tested  in  accordance  with  ASTM  E  283, 
as  listed  in  Appendix  A,  at  a  pressure  differential  of 
1.56  psf  (0.075  kN/m2). 

780  CMR  3606.9  SLIDING  GLASS  DOORS 

3606.9.1  Testing  and  certification:  Sliding  glass 
doors  shall  be  tested  and  certified  to  indicate 
compliance  with  the  requirements  of  the  following 
specifications: 

Aluminum:  AAMA  (ANSI)  101 

Wood:  ANSI/NWWDA  I.  S3,  each  as  listed  in 

Appendix  A. 

3606.9.2  Air  infiltration  Regardless  of  the  type  or 
requirements  of  the  sliding  glass  doors  set  forth  in 
the  aforementioned  specifications,  no  sliding  glass 
door  may  be  selected  whose  air  infiltration  exceeds 
0.50  cubic  feet  per  minute  per  square  foot  (0.236  L/s 
per  mm2)  of  door  area  when  tested  in  accordance 
with  ASTM  E  283,  as  listed  in  Appendix  A,  at  a 
pressure  differential  of  1.56  pounds  per  square  foot 
(0.075kN/m2). 


780  CMR  3606.10  PLYWOOD  AND  WOOD 
STRUCTURAL  PANELS 

3606.10.1  Identification  and  grade:  Plywood  shall 
conform  to  DOC  PS  1,  DOC  PS  2  or  HPMA  (ANSI) 
HP,  as  listed  in  Appendix  A.  Wood  structural 
panels  shall  conform  to  DOC  PS  2,  as  listed  in 
Appendix  A.  All  panels  shall  be  identified  by  a 
grade  mark  or  certificate  of  inspection  issued  by  an 
approved  agency.  Wood  structural  panels  shall 
comply  with  the  grades  specified  in  Table  3606.2.3b. 

3606.10.2  Allowable  spans:  The  maximum 
allowable  spans  for  wood  structural  panel  wall 
sheathing  shall  not  exceed  the  values  set  forth  in 
Table  3606.2.3b 

3606.10.3  Installation:  Wood  structural  panel  wall 
sheathing  shall  be  attached  to  framing  in  accordance 
with  Table  3606.2.3a.  Wood  structural  panels 
marked  Exposure  1  or  Exterior  are  considered  water- 
repellent  sheathing  under  780  CMR. 

780  CMR3606.il  PARTICLEBOARD 
3606.11.1  Identification  and  grade:  Particleboard 
shall  conform  to  ANSI  A208.1,  as  listed  in 
Appendix  A,  and  shall  be  so  identified  by  a  grade 
mark  or  certificate  of  inspection  issued  by  an 
approved  agency.  Particleboard  shall  comply  with 
the  grades  specified  in  Table  3606.2.3c. 


548 


780  CMR  -  Sixth  Edition   corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR  3607 


WALL  COVERING 


780  CMR  3607.1  -  GENERAL 
3607.1.1  Application:  The  provisions  of  780  CMR 
3607.1  shall  control  the  design  and  construction  of 
the  interior  and  exterior  wall  covering  for  all 
buildings  The  use  of  materials  or  methods  of 
construction  not  specified  in  780  CMR  3607.1 
accomplishing  the  purposes  intended  by  780  CMR 
36  and  approved  by  the  building  of  in  accordance 
with  780  CMR  109  shall  be  accepted  as  complying 
with  780  CMR  36. 

3607.1.2  Installation:  Products  sensitive  to 
adverse  weather  shall  not  be  installed  until 
adequate  weather  protection  for  the  installation  is 
provided.  Exterior  sheathing  shall  be  dry  before 
applying  exterior  cover. 

780  CMR  36072  INTERIOR  COVERING 

3607.2.1  General:  Interior  coverings  shall  be 
installed  in  accordance  with  this  section  and  Tables 
3607.2.1a,  3607.2.1b,  3607.2.1c  and  3607.2.3.4. 
Interior  finishes  and  materials  shall  conform  to  the 
flame  spread  and  smoke-density  requirements  of 
780  CMR  3603 

3607.2.2  Interior  plaster:  Gypsum  plaster  or 
Portland  cement  plastering  materials  shall  conform 
to  ASTM  C  5,  C  28,  C  35,  C  37,  C  59,  C  61,  C  587. 
C  588,  C  631,  C847,  C  897,  C  933,  C  1032  and  C 
1047,  and  shall  be  installed  or  applied  in 
conformance  with  ASTM  C  843,  C  844  and  C  1063. 
each  as  listed  in  Appendix  A.  Plaster  shall  not  be 
less  than  three  coats  when  applied  over  metal  lath 
and  not  less  than  two  coats  when  applied  over  other 
bases  permitted  by  780  CMR  3607.2,  except  that 
veneer  plaster  may  be  applied  in  one  coat  not  to 
exceed  /16  inch  (4.76  mm)  thickness,  provided  the 
total  thickness  is  as  set  forth  in  Table  3607.2.1a. 

3607.2.2.1  Support:  Support  spacing,  spacing  of 
fasteners  and  size  of  fasteners  for  gypsum  and 
metal  lath  shall  conform  with  Table  3607.2.3.4 
Gypsum  lath  shall  be  installed  at  right  angles  to 
support  framing  with  end  joints  staggered. 

3607.2.3  Gypsum  wallboard: 

3607.2.3.1  Materials:  All  gypsum  wallboard 
materials  and  accessories  shall  conform  to  ASTM 
C  36,  C  475,  C  514,  C  960,  C  1002  and  C  1047  as 
listed  in  Appendix  A,  and  shall  be  installed  in 
accordance  with  the  provisions  of  780  CMR 
3607.2.  Adhesives  for  the  installation  of  gypsum 
wallboard  shall  conform  to  ASTM  C  557  as  listed 
in  Appendix  A. 


3607.2.3.2  Wood  framing:  Wood  framing 
supporting  gypsum  wallboard  shall  not  be  less 
than  two  inches  (5 1  mm)  nominal  thickness  in  the 
least  dimension  except  that  wood  furring  strips 
not  less  than  one-inch-by-two  inch  (25  mm  by  5 1 
mm)  nominal  dimension  may  be  used  over  solid 
backing  or  framing  spaced  not  more  than  24 
inches  (6 1 0  mm)  on  center. 

3607.2.3.3  Steel  framing:  Steel  framing  shall  not 
be  less  than  1  %  inches  (32  mm)  wide  in  the  least 
dimension.  Light-gage  nonload-bearing  steel 
framing  shall  comply  with  ASTM  C  645  as  listed 
in  Appendix  A.  Load-bearing  steel  framing  and 
steel  framing  from  0.033  inch  to  0.1 12  inch  (0.838 
mm  to  2  84  mm)  thick  shall  comply  with  ASTM 
C  955  05  listed  in  Appendix  A. 

3607.2.3.4  Application:  Support  spacing  and 
size  and  spacing  of  fasteners  shall  comply  with 
Table  3607.2.3.4  Gypsum  wallboard  may  be 
applied  at  right  angles  or  parallel  to  framing 
members.  All  edges  and  ends  of  gypsum 
wallboard  shall  occur  on  the  framing  members, 
except  those  edges  and  ends  which  are 
perpendicular  to  the  framing  members.  Interior 
gypsum  wallboard  shall  not  be  installed  where  it 
is  exposed  to  the  weather  construction. 

3607.2.3.5  Fastening:  Screws  for  attaching 
gypsum  wallboard  to  wood  shall  be  Type  W  in 
accordance  with  ASTM  C  1002  as  listed  in 
Appendix  A  and  shall  penetrate  the  wood  not  less 
than  5/s  inch  (15.9  mm).  Screws  for  attaching 
gypsum  wallboard  to  light-gage  steel  shall  be 
Type  S  in  accordance  with  ASTM  C  1002  as 
listed  in  Appendix  A  and  shall  penetrate  the  steel 
not  less  than  V4  inch  (6.4  mm).  Screws  for 
attaching  gypsum  wallboard  to  steel  0.033  inch  to 
0.112  inch  (0.838  mm  to  2.84  mm)  thick  shall 
comply  with  ASTM  C  954  as  listed  in 
Appendix  A. 

3607.2.4  Bathtub  and  shower  spaces:  Bathtub  and 
shower  floors  and  walls  shall  be  finished  with  a 
smooth,  hard  and  nonabsorbent  surface.  Ceramic  tile 
surfaces  shall  be  installed  in  accordance  with  ANSI 
A  108.1,  A108.4,  A108.5,  A108.6,  A108.ll, 
A118.1,  A  118.3,  A  136.1  and  A  137.1  as  listed  in 
Appendix  A.  Such  wall  surfaces  shall  extend  to  a 
height  of  not  less  than  six  feet  (1829  mm)  above  the 
floor. 

3607.2.4.1  Ceramic  tile:  Gypsum  board  utilized 
as  the  base  or  backer  board  for  adhesive 
application  of  ceramic  tile  or  other  nonabsorbent 


9/19/97  (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


549 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


finish  material  shall  conform  with  ASTM  C  630 
as  listed  in  Appendix  A  Water-resistant  gypsum 
backing  board  shall  be  permitted  to  be  used  on 
ceilings  where  framing  spacing  does  not  exceed 
12  inches  (305  mm)  on  center.  All  cut  or  exposed 
edges,  including  those  at  wall  intersections,  shall 
be  sealed  as  recommended  by  the  manufacturer. 

3607.2.5  Other  finishes:  Wood  veneer  or 
hardboard  paneling  not  less  than  '/t-inch  (6.4  mm) 
nominal  thickness  [13/64-inch  (5.2  mm)  actual]  shall 
conform  to  HPMA  (ANSI)  HP  and  stud  spacing  may 
not  exceed  1 6  inches  on  center. 

3607.2.6  Wood  shakes  and  shingles:  Wood  shakes 
and  shingles  shall  conform  to  CSSB  "Grading  Rules 
for  Wood  Shakes  and  Shingles"  as  listed  in 
Appendix  A  and  shall  be  permitted  to  be  installed 
directly  to  the  studs  with  maximum  24  inches  (610 
mm)  on  center  spacing;  wood  veneer  harboard 
paneling  less  than  '/4-inch  (6.4  mm)  nominal 
thickness  must  not  have  less  than  3/s-inch  (9.5  mm) 
gypsum  board  backer. 

TABLE  3607.2.1a 
THICKNESS  OF  PLASTER 


PLASTER  BASE 

FINISHED  THICKNESS  OF 

PLASTER  FROM  FACE  TO 

LATH,  MASONRY,  CONCRETE 

Gypsum  Plaster 

Portland  Cement 
Mortar 

Expanded  metal  lath 

s/s"  minimum 

%"  minimum 

Wire  lath 

5/e"  minimum 

3/i"  minimum 
(interior) 

%"  minimum 
(exterior)' 

Gypsum  lath 

Vz"  minimum 

Masonry  walls 

Vi"  minimum 

Vi"  minimum 

Monolithiaconcrete 
walls 

s/s"  maximum 

Vs"  maximum 

Monolithic  concrete 
ceilings 

3/ »                       5 
va   maximum 

Vi"  maximum 

Gypsum  veneer 
base 

l,    „     ■  ■         1 
/16   minimum 

lath,  exclusive  of  ribs,  or  self  -furring  lath,  plaster 
thickness  shall  be  Va  inch  minimum. 

2.  When  measured  from  face  of  support  or  backing. 

3.  Because  masonry  and  concrete  surfaces  may  vary  in 
plane,  thickness  of  plaster  need  not  be  uniform. 

4.  When  applied  over  a  liquid  bonding  agent  finish  coat 
may  be  applied  directly  to  concrete  surface. 

5.  Approved  acoustical  plaster  may  be  applied  directly 
to  concrete  or  over  base  coat  plaster,  beyond  the 
maximum  plaster  thickness  shown. 

6  Attachment  shall  be  in  accordance  with  Table 
3607.2.3.4. 

TABLE  3607.2.1b 
GYPSUM  PLASTER  PROPORTIONS 


NUMBER 

COAT 

PLASTER 

BASE  OR 

LATH 

MAXIMUM 
VOLUME 
AGGREGATE  PER 
100  POUNDS  NEAT 
PLASTER2 
(cubic  feet) 

Damp 
Loose 
Sand 

Perlite  or 
Vermiculite 

Two-coat 

3ase  coat 

Gypsum  lath 

2Vz 

2 

work 

3ase  coat 

Masonry 

3 

3 

Three-coat 

•irst  coat 

Lath 

24 

2 

work 

Second  coat 

Lath 

34 

5 

-irst  and 

second 

;oats 

Masonry 

3 

3 

1               Wr 

For  SI:  1  inch  =  25.4  mm 

1.     When  measured  from  back  plane  of  expanded  metal 


For  SI:  1  inch  =  25.4  mm,  1  cubic  foot  =  0.0283  mJ, 
1  pound  =  0.454  kg. 

1 .  Wood-fibered  gypsum  plaster  may  be  mixed  in 
the  proportions  of  100  pounds  of  gypsum  to  not 
more  than  one  cubic  foot  of  sand  where  applied  on 
masonry  or  concrete. 

2.  When  determining  the  amount  of  aggregate  in  set 
plaster,  a  tolerance  of  10%  shall  be  allowed. 

3.  Combinations  of  sand  and  lightweight  aggregate 
may  be  used,  provided  the  volume  and  weight 
relationship  of  the  combined  aggregate  to  gypsum 
plaster  is  maintained. 

4.  If  used  for  both  first  and  second  coats,  the 
volume  of  aggregate  may  be  2V2  cubic  feet. 

5.  Where  plaster  is  one  inch  or  more  in  total 
thickness,  the  proportions  for  the  second  coat  may 
be  increased  to  three  cubic  feet. 


TABLE  3607.2.1c 
PORTLAND  CEMENT  PLASTER 


MAXIMUM  VOLUME  AGGREGATE  PER  VOLUME  CEMENTTTIOUS  MATERIAL1 

MINIMUM 
PERIOD 
MOIST 
COATS 

Portland  Cement 
Plaster  Maximum 
Volume  Aggregate 
per  Volume  Cement 

3 
Portland  Cement-lime  Plaster 

Approximate 

4 
Minimum  Thickness 

Curing 

MINIMUM 

COAT 

Maximum  Volume 

Lime  per  Volume 

Cement 

Maximum  Volume 
Sand  per  Volume 
Cement  and  Lime 

BETWEEN 

First 

4 

Va 

4 

3/a5 

48   Hours 

487  Hours 

Second 

5 

Va 

5 

First  and  Second  coats 

48  Hours 

7  Days8 

Finished 

39 

39 

Ve 

8 

For  SI:  1  inch  =  25.4  mm,  1  pound  =  0.454  kg. 


550 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -WALL  COVERING 

1 .  When  determining  the  amount  of  aggregate  in  set  plaster,  a  tolerance  of  1 0%  may  be  allowed. 

2.  From  ten  to  20  pounds  of  dry  hydrated  lime  (or  an  equivalent  amount  of  lime  putty)  may  be  added  as  a  plasticizing 
agent  to  each  sack  of  Type  I  and  Type  II  standard  portland  cement  in  base  coat  plaster. 

3.  No  additions  of  plasticizing  agents  shall  be  made. 

4.  See  Table  3607.2.1a 

5 .  Measured  from  face  of  support  or  backing  to  crest  of  scored  plaster. 

6.  24  hour  minimum  period  for  moist  curing  of  interior  portland  cement  plaster. 

7.  24  hour  minimum  interval  between  coats  of  interior  portland  cement  plaster. 

8.  Finish  coat  plaster  may  be  applied  to  interior  portland  cement  base  coat  after  a  48-hour  period. 

9.  For  finish  coat,  plaster  up  to  an  equal  part  of  dry  hydrated  lime  by  weight  (or  an  equivalent  volume  of  lime  putty) 
may  be  added  to  Type  I,  Type  II  and  Type  HI  standard  portland  cement. 

TABLE  3607.2.3.4 
APPLICATION  AND  MINIMUM  THICKNESS  OF  GYPSUM  WALLBOARD 


THICKNESS 
OF  GYPSUM 
WALLBOARD 

(inch) 


PLANE  OF 
FRAMING 

SURFACE 


LONG 
DIMENSION  OF 

GYPSUM 
WALLBOARD 

SHEETS  IN 

RELATION  TO 

DIRECTION  OF 

FRAMING 

MEMBERS 


MAXIMUM 

SPACING  OF 

FRAMING 

MEMBERS 

[center-to-center 
in  inches) 


MAXIMUM  SPACING 
OF  FASTENERS 

(center-to-center,  in 
inches) 


NAILS 
TO  WOOD 


Fastening  required  without  adhesive  application. 


% 

Horizontal 

Perpendicular 

16 

7 

12 

No.  13  gage  1  Vi"  long.  I9/M" 

Vertical 

Either  direction 

16 

8 

12 

annular-ringed;  4d  cooler  nail 

Horizontal 

Either  direction 

16 

7 

12 

No.  13  gage  We"  long.  "/M" 

Vi 

Horizontal5 

Perpendicular 

24 

7 

12 

head,  0.098"diameter,  1  Vi"  long, 

Vertical 

Either  direction 

24 

8 

12 

annular-ringed;  5d  cooler  nail 

Horizontal 

Either  direction 

16 

7 

12 

No.  13  gage  ls/a"  long,  1S7M" 

% 

Horizontal 

Perpendicular 

24 

7 

12 

head;  0.098"  diameter,  l3/a"  long, 

Vertical 

Either  direction 

24 

8 

12 

annular-nnged;  6d  cooler  nail 

With  adhesive  application. 


% 

Horizontal 

Perpendicular 

16 

16 

16 

Same  as  above  for  %" 

Vertical 

Either  direction 

16 

16 

24 

Horizontal 

Either  direction3 

16 

16 

16 

ViorVs 

Perpendicular 

24 

12 

16 

As  required  for  14    and  % ' 
gypsum  wallboard,  see  above 

Vertical 

Either  direction 

24 

24 

24 

2%  layers 

Horizontal 

Perpendicular 

24 

16 

16 

Base  ply  nailed  as  required  for 
14    gypsum  wallboard  and  face 
plv  placed  with  adhesive 

Vertical 

Either  direction 

24 

24 

24 

For  SI:  1  inch  =  25.4  mm 

1 .  Where  the  metal  framing  has  a  clinching  design  formed  to  receive  the  nails  by  two  edges  of  metal,  the  nails  shall 
not  be  less  than  5/s  inch  longer  than  the  wallboard  thickness  and  shall  have  ringed  shanks.  Where  the  metal  framing 
has  a  nailing  groove  formed  to  receive  the  nails,  the  nails  shall  have  barbed  shanks  or  be  5d,  13'/2  gage,  1%  inches 
long,  /64-inch  head  for  '/4-inch  gypsum  wallboard;  6d,  13  gage,  l7/e  inches  long,  /M  -inch  head  for  %-inch  gypsum 
wallboard. 

2.  Two  nails  spaced  not  less  than  two  inches  apart,  or  more  than  2V2  inches  apart  may  be  used  where  the  pairs  are 
spaced  12  inches  on  center  except  around  the  perimeter  of  the  boards. 

3.  %-inch  single-ply  gypsum  board  shall  not  be  installed  if  water-based  textured  finish  is  applied  or  to  support 
insulation  above  a  ceiling.  On  horizontal  applications  to  receive  a  water-based  texture  material,  either  hand  or  spray 
applied,  gypsum  board  shall  be  applied  perpendicular  to  framing  and  board  thickness  increased  from  %  inch  to  !4  inch 
for  16-inch  o.c.  framing,  and  from  Vi  inch  to  %  inch  for  24-inch  o.c.  framing. 

4.  Horizontal  refers  to  applications  such  as  ceilings.  Vertical  refers  to  applications  such  as  walls. 


3607.2.6.1  Attachment:  Nails,  staples  or  glue  are 
permitted  for  use  in  attaching  shakes  or  shingles 
to  the  wall,  and  the  shakes  or  shingles  shall  be 
permitted  to  be  attached  directly  to  the  surface 
provided  the  fasteners  are  appropriate  for  the  type 
of  wall  surface  material.  When  nails  or  staples  are 


used,  two  fasteners  shall  be  provided  and  shall  be 
placed  so  that  they  are  covered  by  the  course 
above. 

3607.2.6.2  Furring  strips:  Where  furring  strips 
are  used,  they  shall  be  one  inch  by  two  inches  or 
one  inch  by  three  inches  (25  mm  by  51  mm  or  25 


9/19/97  (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


551 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


mm  by  76  mm),  spaced  a  distance  on  center  equal 
to  the  shake  or  shingle  exposure,  and  shall  be 
attached  to  the  wall  by  nailing  through  the  base 
wall  material  into  the  studs  of  the  interior  spaces. 

3607.2.6.3  Bottom  course:  The  bottom  course 
shall  be  doubled. 

780  CMR  3607.3  EXTERIOR  COVERING 

3607.3.1  General:  All  exterior  walls  shall  be 
covered  with  approved  materials  designed  and 
installed  to  provide  a  barrier  against  the  weather  and 
insects  to  enable  environmental  control  of  the 
interior  spaces  The  exterior  coverings  in  780  CMR 
3607.0  shall  be  installed  in  the  specified  manner 
unless  otherwise  approved. 

3607.3.2  Weather-resistant    sheathing    paper: 

Asphalt-saturated  felt,  free  from  holes  and  breaks 
and  weighing  not  less  than  14  pounds  per  100  square 
feet  (0.683  kg/m2)  or  other  approved  weather- 
resistant  material  shall  be  applied  over  studs  or 
sheathing  of  all  exterior  walls  as  required  by  Table 
3607.3.4  Such  felt  or  material  shall  be  applied 
horizontally,  with  the  upper  layer  lapped  over  the 
lower  layer  not  less  than  two  inches  (51  mm). 
Where  joints  occur,  felt  shall  be  lapped  not  less  than 
six  inches  (153  mm). 

3607.3.2.1  Felt  or  material:  Such  felt  or  material 
may  be  omitted. 

1.  In  detached  accessory  buildings. 

2.  Under  panel  siding  with  shiplap  joints  or 
battens. 

3.  Under  exterior  wall  finish  materials  as 
permitted  in  Table  3607.3.4. 

4.  Under  paperbacked  stucco  lath. 

5.  Over  water-repellent  sheathing  materials. 

3607.3.3  Wood,  plywood  and  wood  structural 
panel  siding:  Joints  in  wood,  plywood  or  wood 
structural  panel  siding  shall  be  made  as  follows 
unless  otherwise  approved.  Vertical  joints  in  panel 
siding  shall  occur  over  framing  members,  unless 
wood  or  wood  structural  panel  sheathing  is  used,  and 
shall  be  shiplapped  or  covered  with  a  batten. 
Horizontal  joints  in  panel  siding  shall  be  lapped  a 
minimum  of  one  inch  (25  mm)  or  shall  be  flashed 
with  Z-flashing. 

3607.3.3.1  Horizontal  siding:  Horizontal  siding 
shall  be  lapped  a  minimum  of  one  inch  (25  mm), 
or  Vz  inch  (12.7  mm)  if  rabbeted,  and  shall  have 
the  ends  caulked,  covered  with  a  batten,  or  sealed 
and  installed  over  a  strip  of  flashing. 

3607.3.4  Attachments:  Unless  specified  otherwise, 
all  wall  coverings  shall  be  securely  fastened  in 
accordance  with  Table  3607.3.4  or  with  other 
approved  aluminum,  stainless  steel,  zinc-coated,  or 
other  approved  corrosion-resistive  fasteners. 


3607.3.5  Wood  shakes  and  shingles:  Wood  shakes 
and  shingles  shall  conform  to  CSSB  "Grading  Rules 
for  Wood  Shakes  and  Shingles." 

3607.3.5.1  Application:  Wood  shakes  or  shingles 
shall  be  applied  either  single-course  or  double- 
course  over  nominal  '/i-inch  (12.7  mm)  wood- 
based  sheathing  or  to  furring  strips  over  Vi-inch 
(12.7  mm)  nominal  non-wood  sheathing.  A 
weather-resistant  permeable  membrane  shall  be 
provided  over  the  sheathing,  with  horizontal 
overlaps  in  the  membrane  of  not  less  than  two 
inches  (5 1  mm)  and  vertical  overlaps  of  not  less 
than  six  inches  (153  mm).  Where  furring  strips  are 
used,  they  shall  be  one  inch  by  three  inches  or  one 
inch  by  four  inches  (25  mm  by  76  mm  or  25  mm 
by  102  mm)  and  shall  be  fastened  horizontally  to 
the  studs  with  7d  or  8d  box  nails  and  shall  be 
spaced  a  distance  on  center  equal  to  the  actual 
weather  exposure  of  the  shakes  or  shingles,  not  to 
exceed  the  maximum  exposure  specified  in  Table 

3607.3.5.2  The  spacing  between  adjacent 
shingles  to  allow  for  expansion  shall  not  exceed 
Vi  inch  (6.4  mm),  and  between  adjacent  shakes, 
shall  not  exceed  Vi  inch  (12.7  mm).  The  offset 
spacing  between  joints  in  adjacent  courses  a 
minimum  of  1  Vi  inches  (38  mm). 

3607.3.5.2  Weather  exposure:  The  maximum 
weather  exposure  for  shakes  and  shingles  shall 
not  exceed  that  specified  in  Table  3607.3.5.2. 

3607.3.5.3  Attachment:  Each  shake  or  shingle 
shall  be  held  in  place  by  two  hot-dipped  zinc- 
coated,  stainless  steel,  or  aluminum  nails  or 
staples.  The  fasteners  shall  be  long  enough  to 
penetrate  the  sheathing  or  furring  strips  by  a 
minimum  of  x/z  inch  (12.7  mm)  and  shall  not  be 
overdriven. 

3607.3.5.3.1  Staple  attachment:  Staples  shall 
not  be  less  than  16  gage  and  shall  have  a  crown 
width  of  not  less  than  7/16  inch  (11  mm),  and 
the  crown  of  the  staples  shall  be  parallel  with 
the  butt  of  the  shake  or  shingle.  In  single- 
course  application,  the  fasteners  shall  be 
concealed  by  the  course  above  and  shall  be 
driven  approximately  one  inch  (25  mm)  above 
the  butt  line  of  the  succeeding  course  and  % 
inch  (19  mm)  from  the  edge.  In  double-course 
applications,  the  exposed  shake  or  shingle  shall 
be  face-nailed  with  two  casing  nails,  driven 
approximately  two  inches  (5 1  mm)  above  the 
butt  line  and  %  inch  (19  mm)  from  each  edge. 
Staples  shall  not  be  permitted  for  face-nailing 
With  shingles  wider  than  eight  inches  (203 
mm),  two  additional  nails  shall  be  required  and 
shall  be  nailed  approximately  one  inch  (25 
mm)  apart  near  the  center  of  the  shingle. 

3607.3.6    Exterior    lath:        All    lath    and    lath 
attachments  shall  be  of  corrosion-resistant  materials. 


552 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  COVERING 


Expanded  metal  or  woven  wire  lath  shall  be  attached 
with  1V2  inch  (38  mm)  long,  1 1  gage  nails  having  a 
/is-inch  (1 1  mm)  head,  or  7/s  inch  (22  mm)  long,  16 
gage  staples,  spaced  at  no  more  than  six  inches  (153 
mm),  or  as  otherwise  approved. 

3607.3.7  Masonry  veneer,  general:  All  masonry 
veneer  shall  be  installed  in  accordance  with 
780  CMR  3607.3.7,  Table  3607.3.4  and  Figure 
3607.3.7.  Exterior  masonry  veneer  shall  not  be 
laterally  supported  by  wood  frame  at  any  point  more 
than  35  feet  (7620  mm)  above  the  adjacent  ground 
elevation. 
Exceptions: 

1.  Veneers  used  as  interior  wall  finishes  may  be 
supported  on  wood  floors  which  are  designed  to 
support  the  loads  imposed. 

2.  Exterior  masonry  veneers  with  an  installed 
weight  of  40  pounds  per  square  foot  (195  kg/m  ) 
or  less  may  be  supported  on  wood  construction. 
When  the  masonry  veneer  is  supported  by  wood 
construction  that  adjoins  the  masonry  veneer 
supported  by  the  foundation,  there  shall  be  a 
movement  joint  between  the  veneer  supported  by 
the  wood  construction  and  the  foundation.  The 
wood  construction  supporting  the  masonry  veneer 
shall  be  designed  to  limit  deflection  to   /600  of  the 


span  for  the  supporting  members. 

3607.3.7.1  Lintels:  Masonry  veneer  shall  not 
support  any  vertical  load  other  than  the  dead  load 
of  the  veneer  above.  Veneer  above  openings  shall 
be  supported  on  lintels  of  noncombustible 
materials  and  the  allowable  span  shall  not  exceed 
the  values  set  forth  in  Table  3607.3.7.1.  The 
lintels  shall  have  a  length  of  bearing  of  not  less 
than  four  inches  (102  mm). 

3607.3.7.2  Attachment:  Masonry  veneer  shall  be 
attached  to  the  supporting  wall  with  corrosion- 
resistant  metal  ties. 

3607.3.7.2.1  Size  and  spacing:  Veneer  ties,  if 
strand  wire,  shall  not  be  less  in  thickness  than 
No.  9  U.S.  gage  wire  and  shall  have  a  hood 
embedded  in  the  mortar  joint,  or  if  sheet  metal, 
not  less  than  No.  22  U.S.  gage  by  Ve  inch  (22 
mm)  corrugated.  Each  tie  shall  be  spaced  not 
more  than  24  inches  (610  mm)  on  center 
horizontally  and  shall  support  not  more  than 
3%  square  feet  (0.302  m2)  of  wall  area. 

Exception:  In  wind  areas  of  more  than  30 
pounds  per  square  foot  (1.44  kN/irr),  each 
tie  shall  support  not  more  than  two  square 
feet  (0.186  m2)  of  wall  area. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


553 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3607.3.4 
WEATHER-RESISTANT  SIDING  ATTACHMENT  AND  MINIMUM  THICKNESS 


NOMINAL 

rmcNEss 

(inches) 

JOINT 
TREATMENT 

SHEATHING 

PAPER 
REQUIRED 

TYPE  OF  SUPPORTS  FOR  THE  SIDING  MATERIAL  AND 
FASTENERS^ 

SIDING 
MATERIAL 

Wood,  or 
Wood 

structural 
Panel 

Sheathing 

Fiberboard 

Sheathing  into 

Stud 

Gypsum 
Sheathing 
into  Stud 

Direct  to 
Studs 

Number  or 
Spacing  of 
Fasteners 

Without 
insulation 

0.0196 

Lap 

No 

0.120  nail 
1  'A"  long 

0.120  nail 
2"  long 

0.120  nail 
2"  long 

Not  allowed 

Horizontal 
aluminum 

0.024 

Lap 

No 

0.120  nail 
1  V2"  long 

0.120  nail 
2"  long 

0.120  nail 
2"  long 

Not  allowed 

Same  as  stud 
spacing 

With 
insulation 

0.019 

Lap 

No 

0.120  nail 
l'/z"  long 

0.120  nail 
2"  long 

0.120  nail 
2V2"  long 

0120  nail 
IV2"  long 

Brick  veneer 

Concrete  masonry 

veneer 

2 

780  CMR 
3607.3 

Yes  (13) 

See  780  CMR  3607 .3.78 

Hard  board 
Board  and  batten- 
vertical 

\e 

(7) 

(7) 

0.099  nail 
2"  long 

0.099  nail 
2Vi"  long 

0.099  nail 
2"  long 

0.099  nail 
\Va"  long 

6"  panel  edges 
8"  inter,  sup. 

Hardboard 
Lap-siding-horizontal 

''|6 

(7) 

(7) 

0.099  nail 
2"  long 

0.099  nail 
2'/j"  long 

0.099  nail 
2Va"  long 

0.099  nail  2" 
long 

Same  as  stud 

spacing  2  per 

bearing 

Steel9 

29  ga. 

Lap 

No 

0.113nail  l3/i" 

Staple  1%" 

0.113nail23/4" 
Staple  2'/2" 

0.113  nail 
2'A"  Staple 

l'A" 

Not  allowed 

Same  as  stud 
spacing 

Stone  veneer 

2 

780  CMR 
3607.3 

Yes 

See  780  CMR  3607.3  and  Figure  3607.3.7 

Particalboard  panels 

3/a-'/2 

(7) 

O) 

6d  box  nail 

6d  box  nail 

6d  box  nail 

6d  box  nail, 
%  not 
allowed 

6"  panel  edges 

% 

O) 

(7) 

6d  box  nail 

8d  box  nail 

8d  box  nail 

6d  box  nail 

Plywood  panel 
(exterior  grade) 

3/a 

0) 

(7) 

0.099  nail  2" 
Staple  1%" 

0.113  nail  2'A" 
Staple  2'A" 

0.099  nail  2" 
Staple  2" 

0.099  nail  2° 
Staple  l3/e" 

6"  on  edges  12" 
inter,  sup. 

14 
Vinyl  Siding 

0.035 

Lap 

No 

0.120  nail  1 14" 
Staple  l3/<" 

0.120  nal  2" 
Staple  2'A" 

0.120  nail  2" 
Staple  2I/2" 

Not  allowed 

Same  as  stud 
spacing 

Wood" 

Rustic  drop 

Shiplap 

Bevel 
Butt  tip 

3/a  Minimum 
/32  Average 

;;„ 

Lap 

Lap 
Lap 

No 

No 
No 

Fastener  penetration  into  stud  -  1 " 

0.1 13  nail 
2'A"  Staple 

Face  nailig  up  to 
6"  widths,  1  nail 
per  bearing:  8" 
widrhs  and  over, 
2  nails  per 
bearing 

For  SI:  1  inch  =  25.4  mm. 

1.  Based  on  stud  spacing  of  16  inches  o.c.  Where  studs  are  spaces  24  inches,  siding  may  be  applied  to  sheathing 
approved  for  that  spacing. 

2.  Nail  is  a  general  description  and  may  be  T-head,  modified  round  head,  or  round  head  with  smooth  or  deformed 
shanks. 

3.  Staples  shall  have  a  minimum  crown  width  of  7/16-inch  O.D.  and  be  manufactured  of  minimum  No.  16  gage  wire. 

4.  Nails  or  staples  must  be  aluminum,  galvanized,  or  rust-preventive  coated  and  shall  be  driven  into  the  studs  for 
fiberboard  or  gypsum  backing. 

5.  Aluminum  nails  shall  be  used  to  attach  aluminum  siding. 

6  Aluminum  (0.019  inch)  may  be  unbacked  only  when  the  maximum  panel  width  is  ten  inches  and  the  maximum  flat 
area  is  eight  inches.  The  tolerance  for  aluminum  siding  shall  be  ±0.002  inch  of  the  nominal  dimension. 

7.  If  boards  are  applied  over  sheathing  or  weather  resistant  membrane,  joints  need  not  be  treated.  Otherwise,  vertical 
joints  must  occur  at  studs  and  be  covered  with  battens  or  be  lapped. 

8.  All  attachments  shall  be  coated  with  a  corrosion-resistive  coating. 

9.  Shall  be  of  approved  type. 

10.  %-inch  plywood  may  be  applied  directly  to  studs  spaced  16  inches  on  center.  '/2-inch  plywood  may  be  applied 
directly  to  studs  spaced  at  24  inches  on  center. 

11.  Woodboard  sidings  applied  vertically  shall  be  nailed  to  horizontal  nailing  strips  or  blocking  set  24  inches  o.c. 
Nails  shall  penetrate  1  'A  inches  into  studs,  studs  and  wood  sheathing  combined,  or  blocking.  A  weather-resistant 
membrane  shall  be  installed  weatherboard  fashion  under  the  vertical  siding  unless  the  siding  boards  are  lapped  or 
battens  are  used. 

12.  Hardboard  siding  shall  comply  with  AHA  A135.6 

13.  For  masonry  veneer,  a  weather-resistant  membrane  or  building  paper  is  not  required  over  water-repellent  sheathing 
materials  when  a  one-inch  air  space  is  provided  between  the  veneer  and  the  sheathing.    When  the  one-inch  space  is 


554 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  WALL  COVERING 

filled  with  mortar,  a  weather-resistant  membrane  or  building  paper  is  required  over  studs  or  sheathing 
14.    Vinyl  siding  shall  comply  with  ASTM  D  3679. 


TABLE  3607.3.5.2 

MAXIMUM  WEATHER  EXPOSURE  FOR 

WOOD  SHAKES  AND  SHINGLES  ON 

EXTERIOR  WALLS 

(Dimensions  are  in 


LENGTH 

EXPOSURE  FOR 
SINGLE  COURSE 

EXPOSURE  FOR 
DOUBLE  COURSE 

SHINGLES1 
'  16 

18 
24 

VA 

12' 
14 

16 

SHAKES1 
18 

,      24 

8'/2 

IVA 

14 
18 

For  SI:  1  mch  =  25.4  mm 

1 .  Dimensions  given  are  for  No.  1  Grade. 

2.  A  maximum  ten-inch  exposure  is  permitted  for  No  2 
Grade. 

3.  A  maximum  1 1-inch  exposure  is  permitted  for  No.  2 
Grade. 

3607.3.7.2.2  Paper  backing  required:  When 
applied  over  stud  construction,  the  studs  shall 
be  spaced  a  maximum  of  24  inches  (610  mm) 
on  center  and  approved  paper  shall  first  be 
applied  over  the  sheathing  or  wires  between 
the  studs,  except  as  otherwise  provided  in 
780  CMR  3607.3.2  and  mortar  shall  be  slushed 
into  the  one-inch  (25  mm)  space  between 
facing  and  paper. 

Exception:  As  an  alternate,  an  air  space  of 
at  least  one  inch  (25  mm)  may  be  maintained 
between  the  backing  and  the  veneer,  in 
which  case  a  weather-resistant  membrane  or 
felt  sheathing  paper  or  approved  water- 
repellent  sheathing  shall  be  applied  over  the 
studs. 

3607.3.7.2.3  Veneer  grouting:  In  lieu  of  such 
wire  ties,  an  approved  method  of  grouting  the 


veneer     to     a     paperbacked     reinforcement 
attached  directly  to  the  studs  may  be  used. 

3607.3.7.3  Flashing:  Flashing  shall  be  located 
beneath  the  first  course  of  masonry  above  finished 
ground  level  above  the  foundation  wall  or  slab, 
and  at  other  points  of  support,  including 
structural  floors,  shelf  angles  and  lintels  when 
masonry  veneers  are  designed  in  accordance  with 
780  CMR  3607.3. 7.  See  780  CMR  3607.3.8  for 
additional  requirements. 

3607.3.7.4  Weepholes  Weepholes  shall  be 
provided  in  the  outside  of  masonry  walls  at  a 
maximum  spacing  of  33  inches  (838  mm)  on 
center  Weepholes  shall  not  be  less  than  3/16  inch 
(4.8  mm)  in  diameter  Weepholes  shall  be  located 
immediately  above  the  flashing. 

3607.3.8  Flashing:  Approved  corrosion-resistive 
flashing  shall  be  provided  at  top  and  sides  of  all 
exterior  window  and  door  openings  in  such  a 
manner  as  to  be  leak-proof,  except  that  self-flashing 
windows  having  a  continuous  lap  of  not  less  than 
1%  inches  (28  mm)  over  the  sheathing  material 
around  the  perimeter  of  the  opening,  including 
corners,  do  not  require  additional  flashing,  jamb 
flashing  may  also  be  omitted  when  specifically 
approved  by  the  building  official.  Similar  flashings 
shall  be  installed  at  the  intersection  of  chimneys  or 
other  masonry  construction  with  frame  or  stucco 
walls,  with  projecting  lips  on  both  sides  under  stucco 
copings:  under  and  at  the  ends  of  masonry,  wood  or 
metal  copings  and  sills;  continuously  above  all 
projecting  wood  trim:  where  exterior  porches,  decks 
or  stairs  attach  to  a  wall  or  floor  assembly  of  wood- 
frame  construction;  at  wall  and  roof  intersections. 


9/19/97  (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


555 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

FIGURE  3607 3.1 
MASONRY  VENEERED  WALL  DETAIL 


3       E 


\  i. 4- 4- 4---.  I 


BUS_DiNG  PAPER 
OR  APPROVED 
WATER  REPELLENT 
SHEATHNSOVER 
STUD  AS  DESCRIBED 
IN  780  CMR  3607.3.2 


APPROVED  TIES 
REOURED  M  SBSMC 
ZONES  3  AND  4 


1-  AIR  SPACE  OP. 
1- MORTARED  SPACE 
AS  DESCRIBED  N 
7S0CME3S07J.4 


MASONRY  VENEER  WALL  SUPPORT  ON 
FOOTING  FOUNDATION  WALL  OR  AS 
OESCRBED  IN  7g0  CMR  3607J.7 


FLASHUG  AMD  WEEP  HOLES1 


For  SI:  1  inch  =  25.4  mm. 

1.    Location  of  flashing  and  weepholes  as  described  in  780  CMR  3607.3.7.3  and  3607 .3.7.4. 


TABLE  3607.3.7.1 
ALLOWABLE  SPANS  FOR  LINTELS  SUPPORTING  MASONRY  VENEER 

size  of  steel 
angle" 

NO  STORY  ABOVE 

ONE  STORY  ABOVE 

TWO  STORIES  ABOVE 

NO  OF  Vz"  OR 

EQUIVALENT 

REINFORCING 

BARS 

3  x  3  x  % 

6-0" 

3'-6" 

3'-0" 

1 

4  x  3  x  V, 

8'  -  0" 

5'-0" 

3-0" 

1 

6x3'/2x'/4 

14' -0" 

8'-0" 

3'-6" 

2 

2-6x31/2X% 

20'  -  0" 

ll'-O" 

5'-0" 

4 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm. 

1     Long  leg  of  the  angle  shall  be  placed  in  a  vertical  position. 

2.  Depth  of  reinforced  lintels  shall  not  be  less  than  eight  inches  and  all  cells  of  hollow  masonry  lintels  shall  be  grouted 
and  solid.  Reinforcing  bars  shall  extend  not  less  than  eight  mches  into  the  support. 

3.  Steel  members  indicated  are  adequate  typical  examples;  other  steel  members  meeting  structural  design  requirements 
may  be  used 


556 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3608 


ROOF-CEILING  CONSTRUCTION 


3608.1  GENERAL 

3608.1.1  Application:  The  provisions  of  780  CMR 
3608.1  shall  control  the  design  and  construction  of 
the  roof-ceiling  system  for  all  buildings.  The  use  of 
materials  or  methods  of  construction  not  specified  in 
780  CMR  3608.1  accomplishing  the  purposes 
intended  with  780  CMR  36  and  approved  by  the 
building  official  in  accordance  with  780  CMR  36 
and  approved  by  the  building  official  in  accordance 
with  780  CMR  109  shall  be  accepted  as  complying 
with  780  CMR  36. 

3608.1.2  Requirements:  Roof-ceiling  construction 
shall  be  capable  of  supporting  all  loads  imposed 
according  to  780  CMR  3603.1  and  shall  transmit  the 
resulting  loads  to  supporting  structural  elements. 

3608.1.3  Roof  drainage:  In  areas  where  expansive 
or  collapsible  soils  are  known  to  exist  or  where 
required  by  city  or  town  ordinance  or  by-law,  all 

dwellings  shall  have  a  controlled  method  of  water 
disposal  from  roofs  that  will  collect  and  discharge 
all  roof  drainage  to  the  ground  surface  at  least  five 
feet  (1524  mm)  from  foundation  walls  or  to  an 
approved  drainage  system. 

780  CMR  360&2  ROOF  FRAMING 
3608.2.1  Identification  and  grade:  Load-bearing 
dimension  lumber  for  rafters,  trusses  and  ceiling 
joists  shall  conform  to  DOC  PS  20  and  to  other 
applicable  standards  or  grading  rules,  as  listed  in 
Appendix  A,  and  be  identified  by  a  grade  mark  or 
certificate  of  inspection-  issued  by  an  approved 
agency.  The  grade  mark  or  certificate  shall  provide 
adequate  information  to  determine  Fb,  the  allowable 
stress  in  bending,  and  E,  the  modulus  of  elasticity. 
Approved  end  jointed  lumber  may  be  used 
interchangeably  with  solid-sawn  members  of  the 
same  species  and  grade.  Blocking  shall  be  a 
minimum  of  utility  grade  lumber. 

Exception:  Use  of  Native  Lumber  shall  be 
allowed  in  accordance  with  780  CMR  2303. 0. 

3608.2.1.1  Fire-retardant-treated  lumber:  The 

allowable  unit  stresses  for  fire-retardant-treated 
lumber,  including  fastener  values,  shall  be 
developed  from  an  approved  method  of 
investigation  which  considers  the  effects  of 
anticipated  temperature  and  humidity  to  which  the 
fire-retardant  lumber  will  be  subjected,  the  type  of 
treatment  and  redrying  process.  The  fire-retardant 
treated  lumber  shall  be  graded  by  an  approved 
agency. 


3608.2.2  Design  and  construction:  Roof-ceilings 
of  wood  construction  shall  be  designed  and 
constructed  in  accordance  with  the  provisions  of 
780  CMR  3608.2  or  with  the  AFPA  NDS-1991 
"National  Design  Specification  for  Wood 
Construction,"  the  CWC-1987  "Canadian  Dimension 
Lumber  Data  Book,"  the  WWPA-  1992  "Western 
Lumber  Span  Tables  for  Floor  and  Ceiling  Joists  and 
Roof  Rafters,"  or  the  "Southern  Pine  Maximum 
Spans  for  Joists  and  Rafters,"  each  as  listed  in 
Appendix  A.  Roof-ceilings  shall  be  constructed  in 
accordance  with  Figures  3606.4.10a,  3606.4.10b, 
3606.4.10c  and  3608.2.4.1  and  nailed  in  accordance 
with  Table  3606.2.3a 

3608.2.2.1  Cathedral  ceilings:  When  ceiling 
joists  and  rafter  ties  are  omitted  and  the  rafters  are 
used  to  create  a  cathedral  ceiling,  rafter  ends  shall 
be  supported  on  bearing  walls,  headers  or  ridge 
beams.  Rafters  shall  be  attached  to  supporting 
members  in  accordance  with  Table  3606.2.3a. 
Ridge  beams  shall  be  capable  of  carrying  the 
imposed  roof  loads  and  shall  be  supported  by 
structural  elements  which  transmit  the  loads  to  the 
foundation. 

3608.2.3  Framing  details:  Rafters  shall  be  nailed  to 
ceiling  joists  to  form  a  continuous  tie  between 
exterior  walls  where  joists  are  parallel  to  the  rafters. 
Where  not  parallel,  rafters  shall  be  tied  with  a  rafter 
tie,  located  as  near  the  plate  as  practical.  Rafter  ties 
shall  be  spaced  not  more  than  four  feet  (1219  mm) 
on  center.  Rafters  shall  be  framed  to  ridge  board  or 
to  each  other  with  gusset  plate  as  a  tie.  Ridge  board 
shall  be  at  least  one-inch  (25  mm)  nominal  thickness 
and  not  less  in  depth  than  the  cut  end  of  the  rafter. 
At  all  valleys  and  hips  there  shall  be  a  valley  or  hip 
rafter  not  less  than  two-inch  (51  mm)  nominal 
thickness  and  not  less  in  depth  than  the  cut  end  of 
the  rafter.  Hip  and  valley  rafters  shall  be  supported 
at  the  ridge  by  a  brace  to  a  bearing  partition  or  be 
designed  to  carry  and  distribute  the  specific  load  at 
that  point. 

3608.23.1  Ceiling  joists  lapped:  Ends  of  ceiling 
joists  shall  be  lapped  a  minimum  of  three  inches 
(76  mm)  or  butted  over  bearing  partitions  or  beam 
and  toenailed  to  the  bearing  member  When 
ceiling  joists  are  used  to  provide  resistance  to 
rafter  thrust,  lapped  joists  shall  be  nailed  together 
and  butted  joists  shall  be  tied  together  in  a  manner 
to  resist  such  thrust. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


557 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3608.2.4  Allowable  spans:  The  unsupported  spans 
for  ceiling  joists  shall  not  exceed  the  values  set  forth 
in  Tables  3608.2.4aa  through  3608.2.4M  The 
unsupported  spans  for  rafters  shall  not  exceed  the 
values  set  forth  in  Tables  3608.2.4a  through 
3608.2.4x.  When  the  roof  pitch  is  less  than  three 
units  vertical  in  12  units  horizontal  (25%  slope), 
members  supporting  rafters  and  ceiling  joists,  such 
as  ridge  beams,  hips  and  valleys,  shall  be  designed 
as  beams.  Selection  of  rafters  shall  be  based  on 
lumber  properties,  snow  load  zone  and  deflection 
due  to  live  load  based  on  ceiling  finish  (see  table 
3603.1.6 


3608.2.4.1  Purlins:  Purlins  may  be  installed  to 
reduce  the  span  of  rafters  as  shown  in  Figure 
3608.2.4.1.  Purlins  shall  be  sized  no  less  than  the 
required  size  of  the  rafters  that  they  support 
Purlins  shall  be  continuous  and  shall  be  supported 
by  two  by  four  (51  by  102)  struts  installed  to 
bearing  walls  at  a  slope  not  less  than  45  degrees 
from  the  horizontal.  The  struts  shall  be  spaced  not 
more  than  four  feet  (1219  mm)  on  center,  and  the 
unbraced  length  of  struts  shall  not  exceed  eight 
feet  (2438  mm). 


FIGURE  3608.2.4.1 
BRACED  RAFTER  CONSTRUCTION 


RAFTER  SPAN 
SEE  TABLES 

3608.2.4a  throu. 


RIDGE  BOARD 


7 

CEILING  JOIST 
SEE  TABLES 

3608.2.4aa  through 
3608.2.4dd 


\ 


■  FOUNDATION 


Nr 


-BEARING  WALL 


For  SI:  one  inch  =  25.4  mm,  one  foot  =  304.8  mm. 

NOTE:  Where  ceiling  joists  run  perpendicular  to  the  rafters,  rafter  ties  shall  be  nailed  to  the  rafters  near  the 

plate  line  and  spaced  not  more  than  four  feet  on  center 


3608.2.5  Bearing:  The  ends  of  each  rafter  or  ceiling 
joist  shall  have  not  less  than  VA  inches  (38  mm)  of 
bearing  on  wood  or  metal  and  not  less  than  three 
inches  (76  mm)  on  masonry. 

3608.2.6  Cutting  and  notching:  It  shall  be  unlawful 
to  notch,  cut  or  pierce  wood  beams,  joists  or  rafters 
in  excess  of  the  limitations  herein  specified,  unless 
proven  safe  by  structural  analysis  or  suitably 
reinforced  to  transmit  all  calculated  loads.  Notches 
in  the  top  or  bottom  of  rafter  shall  not  exceed  V16  of 
the  depth  of  the  rafter,  shall  not  be  longer  than  16 
the  depth  of  the  member  and  shall  not  be  located  in 
the  middle  third  of  the  span.  Notch  depth  at  the  ends 
of  the  member  shall  not  exceed  V*  the  rafter  depth 


Exceptions: 

1.  A  notch  over  the  support  is  permitted  to 
extend  the  full  width  of  the  support 

2.  Notches  on  cantilevered  portions  of  the 
member  are  permitted  to  extend  the  full  length  of 
the  cantilever  if  the  strength  and  deflection  of 
the  cantilever  is  calculated  based  on  the  reduced 
member  section. 

3.  The  tension  side  of  rafters  which  are  four 
inches  or  greater  in  nominal  thickness,  shall  not 
be  notched,  except  at  ends  of  members. 

3608.2.7  Holes:  Holes  drilled,  bored  or  cut  into 
rafters  shall  not  be  closer  than  two  inches  (5 1  mm) 
to  the  top  or  bottom  of  the  rafters,  or  to  any  other 
hole  located  in  the  rafter.  Where  the  rafter  is 
notched,  the  hole  shall  not  be  closer  than  two 


558 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


inches  to  the  notch.  The  diameter  of  the  hole  shall 
not  exceed  V3  the  depth  of  the  rafter. 

3608.2.8  Lateral  support:  Rafters  and  ceiling  joists 
having  a  depth-to-thickness  ratio  exceeding  five  to 
one  based  on  nominal  dimensions  shall  be  provided 
with  lateral  support  at  points  of  bearing  to  prevent 
rotation 

3608.2.8.1  Bridging:  Rafters  and  ceiling  joists 
having  a  depth-to-thickness  ratio  exceeding  six  to 
one  based  on  nominal  dimensions  shall  be 
supported  laterally  by  solid  blocking,  diagonal 
bridging  (wood  or  metal)  or  a  continuous  one- 
inch-by-three-inch  (25  mm  by  76  mm)  wood  strip 
nailed  across  the  rafters  or  ceiling  joists  at 
intervals  not  exceeding  ten  feet  (3048  mm). 

3608.2.9  Framing  of  openings:  Openings  in  roof 
and  ceiling  framing  shall  be  framed  with  headers 
between  ceiling  joists  or  rafters.  When  the  header 
span  does  not  exceed  four  feet  (1219  mm),  the 
header  may  be  a  single  member  the  same  size  as  the 
ceiling  joist  or  rafter.  When  the  header  span  exceeds 
four  feet  (1219  mm),  the  header  and  the  joists  or 
rafters  that  support  the  header  shall  be  doubled,  and 
approved  hangers  shall  be  used  to  connect  the 
header  to  the  joists  or  rafters. 

3608.2.10  Headers:  Roof-ceiling  framing  around 
openings  shall  be  provided  with  headers.  The 
allowable  spans  for  headers  in  bearing  walls  shall 
not  exceed  the  values  set  for  in  Table  3608.2.6.2. 

3608.2.11  Trusses:  Wood  trusses  shall  be  designed 
in  accordance  with  approved  engineering  practice. 
Truss  components  may  be  joined  by  nails,  glue, 
timber  connectors  or  other  approved  fastening 
devices.  The  design  of  metal  plate  connected  wood 
trusses  shall  comply  with'  TFT  QST,  TPI  PCT  and 
TPI-1985  "Design  Specification  for  Metal  Plate 
Connected  Wood  Trusses",  each  as  listed  in 
Appendix  A.  Trusses  shall  be  braced  according  to 
their  appropriate  engineered  design  In  the  absence 
of  specific  bracing  requirements,  trusses  shall  be 
braced  in  accordance  with  TPI  BWT,  as  listed  in 
Appendix  A.  Truss  members  shall  not  be  cut  or 
altered  unless  so  designed. 

3608.2.12  Roof  tie-down:  Roof  assemblies  subject 
to  wind  uplift  pressures  of  20  pounds  per  square  foot 
(0.958  kN/m2)  or  greater,  shall  have  rafter  or  truss 
ties  provided  in  accordance  with  Table  3608.2.12. 


The  resulting  uplift  forces  from  the  rafter  or  truss 
ties  shall  be  transmitted  to  the  foundation. 

780  CMR  3608 3  ROOF  SHEATHING 

3608.3.1  Lumber  sheathing:  Allowable  spans  for 
lumber  used  as  roof  sheathing  shall  conform  to 
Table  3608.3.1  Spaced  lumber  sheathing  for  wood 
shingle  and  shake  roofing  shall  conform  to  the 
requirements  of  780  CMR  3609. 8  and  3609. 9 

3608.3.2  Plywood  sheathing 

3608.3.2.1  Identification  and  grade:  Plywood 
and  wood  structural  panels  shall  conform  to  DOC 
PS  1  or  DOC  PS  2  as  listed  in  Appendix  A,  and 
shall  be  identified  by  grade  mark  or  certificate  of 
inspection  issued  by  an  approved  agency. 
Plywood  and  wood  structural  panels  shall  comply 
with  the  grades  specified  in  Table  3605. 3.2.1. la 

3608.3.2.1.1  Type:  All  plywood,  when 
designed  to  be  exposed  in  outdoor  applications, 
shall  be  of  an  exterior  type.  Plywood  or  wood 
structural  panel  roof  sheathing  exposed  to  the 
underside  may  be  of  interior  type  bonded  with 
exterior  glue,  identified  as  Exposure  1 . 

3608.3.2.1.2  Fire-retardant-treated  plywood: 
The  allowable  unit  stresses  for  fire-retardant- 
treated  plywood,  including  fastener  values, 
shall  be  developed  from  an  approved  method 
of  investigation  which  considers  the  effects  of 
anticipated  temperature  and  humidity  to  which 
the  fire-retardant  plywood  will  be  subjected, 
the  type  of  treatment  and  redrying  process. 
The  fire-retardant-treated  plywood  shall  be 
graded  by  an  approved  agency. 

3608.3.2.1.3  Wood  structural  panels:  Wood 
structural-use  panels  conforming  to  DOC  PS  2, 
as  listed  in  Appendix  A,  includes  performance- 
rated  plywood,  oriented  strandboard  and 
composite  panels.  Oriented  strandboard 
structural-use  panels  manufactured  in  Canada 
shall  conform  to  CSA  0437  as  listed  in 
Appendix  A. 

3608.3.2.2  Allowable  spans:  The  maximum 
allowable  spans  for  plywood  and  wood  structural 
panel  roof  sheathing  shall  not  exceed  the  values 
set  forth  in  Table  3605.3.2.1.1a 

3608.3.2.3  Installation:  Plywood  and  wood 
structural  panel  roof  sheathing  shall  be  installed 
with  joints  staggered  or  nonstaggered  in 
accordance  with  Tables  3605.3.2.1.1a  and 
3606.2.3a,  or  APA  E  30  as  listed  in  Appendix  A. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


559 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3608.2.12 
WIND  UPLIFT  FORCES  ON  ROOF 

TRUSSES  AND  RAFTERS1 2  3  4 
(Pounds  Per  Tie-Down  Connection) 


WIND  UPLIFT 

PRESSURE  ON 

ROOF  (psl) 

TOTAL  BUILDING  WIDTH  ROOF 
INCLUDING  OVERHANG  (feet) 

24 

28 

32 

36 

40 

20 

192 

224 

256 

288 

320 

30 

432 

504 

576 

648 

720 

40 

672 

784 

895 

1,008 

1,120 

50 

912 

1,064 

1,216 

1,368 

1,520 

60 

1,152 

1,344 

1,536 

1,728 

1,920 

70 

1,392 

1,624 

1,856 

2,088 

2,320 

80 

1,632 

1,904 

2,176 

2,448 

2,720 

90 

1,872 

2,184 

2,496 

2,808 

3,120 

For  SI:  1  inch  =  25.4  mm,  1  foot  =  304.8  mm,  psf  = 
0.0479  kNnr 

1.  A  continuous  load  path  capable  of  resisting  the 
tributary  forces  shall  be  provided  from  tie-down 
connections  to  the  foundation 

2.  Wind  uplift  forces  are  based  on  24-inch  spacing  of 
roof  trusses  or  rafters.  For  spacing  other  than  24  inches, 
forces  shall  be  adjusted  accordingly. 

3.  Interpolation  is  permitted  for  intermediate  values  of 
wind  uplift  pressures  and  building  widths. 

4.  The  rated  capacity  of  approved  tie-down  devices  is 
permitted  to  include  a  V3  increase  for  wind  effects. 

5.  Tie-down  connections  shall  be  provided  at  bearing 
walls  for  roof  trusses  or  rafters  to  resist  wind  uplift 
forces. 

3608.3.3  Particleboard  sheathing: 

3608.3.3.1       Identification      and      grade: 

Particleboard  roof  sheathing  shall  conform  to 
Type  2-M-W  as  set  forth  in  ANSI  A208.1  as 
listed  in  Appendix  A  and  shall  be  so  identified  by 
a  grade  mark  or  certificate  of  inspection  issued  by 
an  approved  agency. 

3608.33.2  Allowable  spans:  The  allowable  loads 
and  spans  for  particleboard  roof  sheathing  shall 
not  exceed  the  values  set  forth  in  Table 
3608.3.3.2 

3608.3.3.3  Installation:  Particleboard  roof 
sheathing  shall  be  installed  in  accordance  with 
Tables  3606.2.3a  and  3608.3.3.2  Where  walls  are 
subject  to  wind  pressures  of  30  pounds  per  square 
foot  (1.44  kN/m  )  or  greater,  particleboard  roof 
sheathing  shall  be  attached  to  the  gable  end  with 
8d  common  nails  spaced  at  no  more  than  four 
inches  on  center  (102  mm),  or  equivalent 
fasteners. 


TABLE  3608.3.1 
MINIMUM  THICKNESS  LUMBER  ROOF 
SHEATHING    


RAFTER  OR  BEAM 
SPACING  (inches) 

MINIMUM  NET 
THICKNESS  (inches) 

24 

% 

48* 

60 

1V4T&G 

72^ 

For  SI:  1  inch  =  25.4  mm,  1  psi=  6.895  kPa. 

1.  Minimum  270  Fb,  340,000  E. 

2.  Minimum  420  Fb,  660,000  E. 

3.  Minimum  600  Fb,  1,150,000  E. 

TABLE  3803.3.2 

ALLOWABLE  LOADS  FOR 

PARTICLEBOARD  ROOF  SHEATHING' 2  3 


GRADE 

THICKNESS 
(inches) 

MAXIMUM 
ON- 
CENTER 
SPACING 

LIVE 
LOAD 

(pounds  per 
square  foot) 

TOTAL 
LOAD 

(pounds  per 
square  foot) 

3/S4 

16 

45 

65 

V 

16 

105 

105 

2-M-W 

V 

24 

30 

40 

v2 

16 

110 

150 

Vi 

24 

40 

55 

For  SI:  1  inch  =  25.4  mm,  1  psi  =  6895  kPa. 

1     Panels  are  continuous  over  two  or  more  spans. 

2.  Uniform  load  deflection  limitations:  Vl80  of  the  span 
under  live  load  plus  dead  load  and  V240  of  the  span  under 
live  load  only. 

3.  The  panels  may  be  applied  parallel  or  perpendicular 
to  the  span  of  the  rafters  or  joists  and  shall  be  continuous 
over  two  or  more  spans.  If  the  panels  are  applied 
perpendicular  to  roof  supports,  the  end  joints  of  the 
panels  shall  be  offset  so  that  four  panel  comers  will  not 
meet.  Cutouts  for  items  such  as  plumbing  and  electrical 
shall  be  oversized  to  avoid  a  forced  fit  A  '/2-inch  gap 
must  be  provided  between  the  panel  and  concrete 
masonry  walls.  Leave  a  V,6-inch  gap  between  panels  and 
nail  no  closer  than  %  inch  from  panel  edge. 

4.  Edges  shall  be  tongue  and  groove  or  supported  with 
blocking  or  edge  clips 

780  CMR  3608.4  METAL 
3608.4.1  General:    Elements  shall  be  straight  and 
free  of  any  defects  which  would  significantly  affect 
their  structural  performance. 


560 


CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


3608. 4.2  Steel  Elements:  Steel  structural  elements 
in  roof-ceiling  construction  may  be  either  hot- 
rolled  structural  steel  shapes  or  members  cold 
formed  to  shape  from  steel  strip  or  plate  or  a 
fabricated  combination  thereof.  Steel  structural 
members  in  roof-ceiling  construction  shall  be 
designed  in  accordance  with  the  AISC 
"Specification  for  the  Design",  "Fabrication  and 
Erection  of  Structural  Steel  for  Buildings"  as  listed 
in  Appendix ,  i. 

3608.4.3  Aluminum  Elements:  Aluminum 
structural  elements  in  roof-ceiling  systems  shall,  be 
constructed  of  materials  and  designed  in 
accordance  with  AA  SAS  30  as  listed  in 
Appendix  A. 

780  CMR  3608.5  CEILING  FINISHES 
3608.5.1   Ceiling  installation:     Ceilings  shall  be 
installed  in  accordance  with  the  requirements  for 
interior  wall  finishes,   as  provided  in   780  CMR 
360Z2. 

780  CMR  3608.6  ROOF  VENTILATION 

3608.6.1  Ventilation  required:  Enclosed  attics  and 
enclosed  rafter  spaces  formed  where  ceilings  are 
applied  directly  to  the  underside  of  roof  rafters  shall 
have  cross  ventilation  for  each  separate  space  by 
ventilating  openings  protected  against  the  entrance 
of  rain  or  snow.     Ventilating  openings  shall  be 


provided  with  corrosion-resistant  wire  mesh,  with 
the  least  dimension  being  Ve  inch  (3.2  mm). 

3608.6.2  Minimum  area:  The  total  net  free 
ventilating  area  shall  not  be  less  than  one  to  150  of 
the  area  of  the  space  ventilated  except  that  the  total 
area  is  permitted  to  be  reduced  to  one  to  300, 
provided  at  least  50%  and  not  more  than  80%  of  the 
required  ventilating  area  is  provided  by  ventilators 
located  in  the  upper  portion  of  the  space  to  be 
ventilated  at  least  three  feet  (914  mm)  above  eave  or 
cornice  vents  with  the  balance  of  the  required 
ventilation  provided  by  eave  or  cornice  vents.  As  an 
alternative,  the  net  free  cross-ventilation  area  may  be 
reduced  to  one  to  300  when  a  vapor  barrier  having  a 
transmission  rate  not  exceeding  one  perm  (57.4 
ng/s-nr-Pa)  is  installed  on  the  warm  side  of  the 
ceiling. 

3608.6.3  Vent  clearance:  Where  eave  or  cornice 
vents  are  installed,  insulation  shall  not  block  the  free 
flow  of  air.  A  minimum  of  one-inch  (25  mm)  space 
shall  be  provided  between  the  insulation  and  the  roof 
sheathing  at  the  location  of  the  vent. 

780  CMR  3608.7  ATTIC  ACCESS 

3608.7.1  Accessible  attic  access:  A  readily 
accessible  attic  access  framed  opening  not  less  than 
22  inches  by  30  inches  (559  mm  by  762  mm)  shall 
be  provided  to  any  attic  area  having  a  clear  height  of 
over  30  inches  (762  mm). 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


561 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4aa 

ALLOWABLE  SPANS  FOR  CEILING  JOISTS 

20  Lbs.  per  Sq.  Ft.  Live  Load 

(Limited  attic  storage  where  development  of  future  rooms  is  not  possible) 

(Veneer  Plaster  Ceiling) 

DESIGN  CRITERIA:  Deflection — For  20  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

Strength — Live  load  of  20  lbs.  per  sq.  ft.  plus  dead  load  of  10  lbs.  per  sq.  ft.  determines  fiber  stress  value  shown. 

HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (upper  figure  in  each  square).  Determine  size  and  spacing 


(first  column 

)  based  stress  grade  (1 

ower  figu 

re  in  each 

square) 

ind  modu 

Ius  of  ela 

sticity  (to 

p  row)  ot 

lumber  tc 

)  be  used. 

JOIST  SIZE  AND 
SPACING 

MODULUS  OF  ELASTICITY,  "£,' 

EM  1,000,000  PSi 

(inches) 

(inches) 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

1.1 

1.2 

1.3 

2x4 

12.0 

5-5 
430 

5-10 
500 

6-2 
560 

6-6 
630 

6-10 
680 

7-1 
740 

7-4 
790 

7-7 
850 

7-10 
900 

8-0 

950 

16.0 

4-11 
470 

5-4 
550 

5-8 
620 

5-11 
690 

6-2 
750 

6-5 
810 

6-0 
870 

6-11 
930 

7-1 
990 

7-3 
1,040 

24.0 

4-4 
540 

4-8 

630 

4-11 
710 

5-2 
790 

5-5 
860 

5-8 
930 

5-10 
1,000 

6-0 
1,070 

6-2 
1,130 

6-4 
1,190 

2x6 

120 

8-6 

430 

9-2 
500 

99 
560 

10-3 
630 

10-9 
680 

11-2 
740 

11-7 
790 

11-11 
850 

12-3 
900 

12-7 
950 

16.0 

7-9 
470 

8-4 

550 

8-10 
620 

9-4 
690 

99 

750 

10-2 
810 

10-6 
870 

10-10 
930 

11-2 
990 

11-5 
1,040 

24  0 

6-9 
540 

7-3 
630 

7-9 
710 

8-2 
790 

8-6 
860 

8-10 
930 

9-2 
1,000 

9-6 
1,070 

9-9 
1,130 

10-0 
1.190 

2x8 

120 

11-3 
430 

12-1 

500 

12-10 
560 

13-6 
630 

14-2 
680 

14-8 
740 

15-3 
790 

15-9 
850 

16-2 
900 

16-7 
950 

16.0 

10-2 
470 

11-0 
550 

11-8 
620 

12-3 
690 

12-10 
750 

13-4 
810 

13-10 
870 

14-3 
930 

14-8 
990 

15-1 
1,040 

24.0 

8-11 

540 

9-7 
630 

10-2 
710 

10-9 
790 

11-3 
860 

11-8 
930 

12-1 
1,000 

12-6 
1,070 

12-10 
1,130 

13-2 
1,190 

2x10 

12.0 

14-4 
430 

15-5 
500 

16-5 
560 

17-3 
630 

18-0 
680 

18-9 
740 

19-5 
790 

20-  1 
850 

20-8 
900 

21  -2 
950 

16.0 

13-0 

470 

14-0 
550 

14-11 
620 

15-8 
690 

16-5 
750 

17-0 
810 

17-8 
870 

18-3 
930 

18-9 
990 

19-3 

1,040 

24.0 

11-4 
540 

12-3 
630 

13-0 
710 

13-8 
790 

14-4 
860 

14-11 
930 

15-5 
1,000 

15-11 
1,070 

16-5 
1,130 

16-10 
1,190 

(inches) 

(inches) 

1.4 

1.5 

1.6 

1.7 

1.8 

1.9 

2.0 

2.2 

2.4 

2x4 

12.0 

8-3 
990 

8-5 
1,040 

8-7 
1,090 

8-9 
1,130 

8-11 
1,170 

9-1 

1,220 

9-3 
1,260 

9-7 
1,340 

9-10 
1,420 

16.0 

7-6 
1,090 

7-8 
1,140 

7-10 
1.200 

8-0 

1,240 

8-1 
1,290 

8-3 
1,340 

8-5 
1,390 

8-8 
1,480 

8-11     I 
1,570    i 

24.0 

6-6 
1,250 

6-8 
1,310 

6-10 
1,370 

7-0 
1,420 

7-1 
1,480 

7-3 
1,530 

7-4 
1,590 

7-7 
I  690 

7-10 
1,790 

2x6 

12.0 

12-11 
990 

13-3 
1,040 

13-6 
1,090 

13-9 
1,130 

14-1 
1,170 

14-4 
1,220 

14-7 
1,260 

15  0 

1  340 

15-6 
1,420 

16.0 

11-9 
1,090 

12-0 
1,140 

12-3 
1,200 

12-6 
1,240 

12-9 
1,290 

13-0 
1,340 

13-3 
1,390 

13-8 
1,480 

14-1 
1,570 

24.0 

10-3 
1,250 

10-6 
1,310 

10-9 
1,370 

10-11 
1,420 

11-2 

1,480 

11-4 
1,530 

11-7 
1,590 

11.11 

1,690 

12-3 
1,790 

2x8 

12.0 

17-0 
990 

17-5 
1,040 

17-10 
1,090 

18-2 
1,130 

18-6 
1,170 

18-10 
1,220 

19-2 
1,260 

19-10 
1,340 

20-5 
1,420 

16.0 

15-6 
1,090 

15-10 
1,140 

16-2 

1,200 

16-6 

1,240 

16-10 
1,290 

17-2 
1,340 

17-5 
1,390 

18-0 
1,480 

18-6 

1,570 

24.0 

13-6 
1,250 

13-10 
1,310 

14-2 
1,370 

14-5 
1,420 

14-8 
1,480 

15-0 
1,530 

15-3 
1,590 

15-9 
1,690 

16-2 

1,790 

2x  10 

12.0 

21-9 
990 

22-3 
1,040 

22-9 
1,090 

23-2 
1,130 

23-8 
1,170 

24-1 
1,220 

24-6 
1,260 

25-3 
1,340 

26-0 
1,420 

16.0 

19-9 
1,090 

20-2 
1,140 

20-8 
1,200 

21-1 
1,240 

21-6 
1.290 

21-10 
1,340 

22-3 
1,390 

22-11 
1,480 

23-8 
1,570 

24.0 

17-3 
1,250 

17-8 
1,310 

18-0 
1,370 

18-5 
1,420 

18-9 

1,480 

19-1 
1,530 

19-5 
1,590 

20-1 
1,690 

20-8 
1,790 

For  SI:  I  inch  =  25.4  mm 
NOTE:  The  extreme  fiber 


1  pound  per  square 
stress  in  bending.  " 


inch  =  6.895  kPa.l 
Fb. "  in  pounds  per 


I  pound  per  square  foot  =  0 
square  inch  is  shown  below 


0479  kN/m2. 
each  span. 


562 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4bb 
ALLOWABLE  SPANS  FOR  CEILING  JOISTS 
20  Lbs.  per  Sq.  Ft.  Live  Load 
(Limited  attic  storage  where  development  of  future  rooms  is  not  possible) 
(Gypsum  Ceiling) 
DESIGN  CRITERIA:  Deflection — For  20  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 
Strength — Live  load  of  20  lbs  per  sq.  ft.  plus  dead  load  of  10  lbs.  per  sq.  ft.  determines  fiber  stress  value. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (upper  figure  in  each  square).  Determine  size  and 
(first  column)  based  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row)  of  lumber  to 


spacing 
be  used. 


JOIST  SIZE  AND 
SPACING 

MODULUS  OF  ELASTICITY,  ••£,"  IN  1,000,000  PSI 

(inches) 

(inches) 

0.4 

0.5 

0.6 

0.7 

0.8 

OS 

1.0 

1.1 

1.2 

1  J 

2x4 

12.0 

6-2 

560 

6-8 
660 

7-1 
740 

7-6 
820 

7-10 
900 

8-1 
970 

8-5 
1,040 

8-8 

1,110 

8-11 
1,170 

9-2 
1,240 

16.0 

5-8 
620 

6-1 

720 

6-5 
810 

6-9 
900 

7-1 
990 

7-5 
1,070 

7-8 

1,140 

7-11 
1,220 

8-1 
1,290 

8-4 
1,360 

240 

4-11 
710 

5-4 
830 

5-8 
930 

5-11 
1,030 

6-2 
1,130 

6-5 

1,220 

6-8 

1,310 

6-11 
1.400 

7-1 
1,480 

7-3 
1.560 

2x6 

12.0 

9-9 
560 

10-6 
660 

11-2 

740 

i  1-9 

820 

12-3 
900 

12-9 
970 

13-3 
1,040 

13-8 
1.110 

14-1 
1,170 

14-5 
1.240 

16.0 

8-10 
620 

9-6 

720 

10-2 
810 

10-8 
900 

11-2 

990 

11-7 
1,070 

12-0 
1,140 

12-5 
1,220 

12-9 
1,290 

13-1 
1.360 

24.0 

7-9 

710 

8-4 
830 

8-10 
930 

9-4 
i,030 

9-9 
1,130 

10-2 
1,220 

10-6 
1,310 

10-10 
1,400 

11-2 
i  ,480 

11  -5 
1.560 

2x8 

12.0 

12-10 
560 

13-10 
660 

14-8 
740 

15-6 
820 

16-2 
900 

16-10 
970 

17-5 
1,040 

18-0 
1,110 

18-6 
1,170 

19-0 
1,240 

16.0 

11  -8 
620 

12-7 
720 

13-4 
810 

14-1 
900 

14-8 
990 

15-3 
1,070 

15-10 

1.140 

164 
1,220 

16-10 
1,290 

17-3 
1,360 

24.0 

10-2 
710 

11-0 
830 

11-8 
930 

12-3 
1,030 

12-10 
1,130 

13-4 

1,220 

13-10 

1,310 

14-3 
1,400 

14-8 
1,480 

15-1 
1,560 

2x10 

12.0 

16-5 
560 

17-8 
660 

18-9 
740 

19-9 
820 

20-S 
900 

21  -6 
970 

22-3 
1,040 

22-11 
1,110 

23-8 
1,170 

24-3 
i,240 

16.0 

14-11 
620 

16-0 
720 

17-0 
810 

17-11 
900 

18-9 
990 

19-6 
1,070 

20-2 
1,140 

20-10 
1,220 

21-6 
1,290 

22-1 
1,360 

24.0 

13-0 
710 

14-0 
830 

14-11 
930 

15-8 
1,030 

16-5 
1,130 

17-0 
1,220 

17-8 
1,310 

18-3 
1,400 

189 
1,480 

19-3 
1,560 

{inches) 

(inches) 

1.4 

1.5 

L6 

1.7 

1.8 

1.9 

2.0 

2.2 

2.4 

2x4 

12.0 

9-5 
1,300 

9-8 
1,360 

9-10 
1,420 

10-0 
1,480 

10-3 
1,540 

10-5 
1,600 

10-7 
1.650 

10-11 
1.760 

11-3 
1.860 

16.0 

8-7 
1,430 

8-9 
1,500 

8-11 
1,570 

9-1 
1,630 

9-4 
1,690 

9-6 
1,760 

9-8 

1.820 

9-  11 
1,940 

10-3 
2.050 

24.0 

7-6 
1,640 

7-8 
1,720 

7-10 
1,790 

8-0 
1,870 

8-1 
1,940 

8-3 
2,010 

8-5 
2,080 

8-8 
2,220 

8-11 
2,350 

2x6 

12.0 

14-9 
1,300 

15-2 
1,360 

15-6 
1,420 

15-9 
1,480 

16-1 

1,540 

16-4 
1,600 

16-8 
1,650 

17-2 
1,760 

17-8 
1,860 

16.0 

13-5 
1,430 

13-9 
1,500 

14-1 
1,570 

14-4 
1,630 

14-7 
1,690 

14-11 
1,760 

15-2 
1,820 

15-7 
1,940 

16-1 
2,050 

24.0 

11-9 
1,640 

12-0 
1,720 

12-3 
1,790 

12-6 
1,870 

12-9 
1,940 

13-0 
2,010 

13-3 
2,080 

13-8 
2,220 

14-1 
2,350 

2x8 

12.0 

19-6 
1,300 

19-11 
1,360 

20-5 
1,420 

20-10 
1,480 

21-2 
1,540 

21-7 
1,600 

21-11 
1,650 

22-8 
1,760 

23-4 
1,860 

16.0 

17-9 
1,430 

18-2 
1,500 

18-6 

1,570 

18-11 
1,630 

19-3 
1,690 

19-7 
1,760 

19-11 
1,820 

20-7 
1,940 

21-2 
2,050 

24.0 

15-6 
1,640 

15-10 
1,720 

16-2 
1,790 

16-6 
1,870 

16-10 
1,940 

17-2 
2,010 

17-5 
2,080 

18-0 
2,220 

18-6 
2,350 

2x10 

12.0 

24-10 
1,300 

25-5 
1,360 

26-0 
1,420 

26-6 
1,480 

27-1 
1,540 

27-6 
1,600 

28-0 
1,650 

28-11 
1,760 

29-9 
1,860 

16.0 

22-7 
1,430 

23-2 
1,500 

23-8 
1,570 

24-1 
1,630 

24-7 
1,690 

25-0 
1,760 

25-5 
1,820 

26-3 
1,940 

27-  1 
2,050 

24.0 

19-9 
1,640 

20-2 
1,720 

20-8 
1,790 

21-1 
1,870 

21-6 
1,940 

21-10 
2,010 

22-3 
2,080 

22-11 
2,220 

23-8 
2,350 

For  SI:  I  inch  =  25.4  mm,  I  pound  per  square 
NOTE:  The  extreme  fiber  stress  in  bending, 


inch  =  6.895  kPa,  I  pound 
'Fb,  "in  pounds  per  square 


per  square  foot  =  0.0479  kN/m2 
inch  is  shown  below  each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


563 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4cc 

ALLOWABLE  SPANS  FOR  CEILING  JOISTS 

10  Lbs.  per  Sq.  Ft.  Live  Load 

(No  attic  storage  and  roof  slope  not  steeper  than  3  in  1  2) 

(Veneer  Plaster  Ceiling) 

DESIGN  CRITERIA:  Deflection-For  10  lbs.  per  sq.  Ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

Strength-Live  load  of  10  lbs.  per  sq.  Ft.  plus  dead  load  of  5  lbs  per  sq  ft.  determines  fiber  stress  value 

HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (upper  figure  in  each  square)  Determine  size  and 

spacing  (first  column)  based  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row) 

of  lumber  to  be  used. 


JOIST  SIZE  AND 
SPACING 

MODULUS  OF  ELASTICITY,  "E" 

IN  1,000,000  PSI 

(inches) 

(inches) 

0.4 

0.5 

0.6 

0.7 

0.8 

03 

1.0 

1.1 

1.2 

L3 

2x4 

120 

6-10 
340 

7-4 
400 

7-10 
450 

8-3 
500 

8-7 
540 

8-11 
590 

9-3 
630 

9-7 
670 

9-10 
710 

10-1 
750 

16.0 

6-2 
380 

6-8 

440 

7-1 
490 

7-6 
550 

7-10 
600 

8-1 
650 

690 

740 

780 

830 

24.0 

5-5 
430 

5-10 
500 

6-2 
560 

6-6 
630 

6-10 
680 

7-1 
740 

7-4 
790 

7-7 
850 

7-10 
900 

8-0 
950 

2x6 

12.0 

10-9 
340 

11-7 
400 

12-3 
450 

12-11 
500 

13-6 
540 

14-1 
590 

14-7 
630 

15-0 
670 

15-6 
710 

15-11 

750 

16.0 

9-9 
380 

10-6 
440 

11-2 
490 

11-9 
550 

12-3 
600 

12-9 
650 

13-3 
690 

13-8 

740 

14.1 
780 

14-5 
830 

24.0 

8-6 

430 

9-2 

500 

9-9 
560 

10-3 
630 

10-9 
680 

11-2 
740 

11-7 
790 

11-11 
850 

12-3 
900 

12-7 
950 

2x8 

12.0 

14-2 

340 

15-3 
400 

16-2 
450 

17-0 
500 

17-10 
540 

18-6 
590 

19-2 
630 

19-10 
670 

20-5 
710 

20-11 
750 

16.0 

12-10 
380 

13-10 
440 

14-8 
490 

15-6 

550 

16-2 
600 

16-10 
650 

17-5 
690 

i8-0 

740 

18-6 
780 

19-0 
830 

24.0 

11-3 
430 

12-1 
500 

12-10 
560 

13-6 
630 

14-2 
680 

14-8 
740 

15-3 
790 

15-9 
850 

16-2 
900 

16-7 
950 

2x10 

12.0 

18-0 
340 

19-5 

400 

20-8 
450 

21-9 
500 

22-9 
540 

23-8 
590 

24-6 
630 

25-3 
670 

26-0 
710 

26-9 
750 

16.0 

16-5 
380 

17-8 
440 

18-9 
490 

19-9 
550 

20-8 
600 

21  -6 
650 

22-3 
690 

22-  11 
740 

23-8 
780 

24-3 
830 

24.0 

14-4 
430 

15-5 
500 

16-5 
560 

17-3 
630 

18-0 
680 

18-9 

740 

19-5 

790 

20-1 
850 

20-8 
900 

21-2 
950 

(inches) 

(inches) 

1.4 

1.5 

1.6 

1.7 

1.8 

1.9 

2.0 

Z2 

2.4 

2x4 

12.0 

10-4 
790 

10-7 
830 

10-10 
860 

900 

1 1-3 

930 

11-6 
970 

11-8 
1,000 

12-1 

i.070 

12-5 
1,130 

16.0 

9-5 

870 

9-8 
910 

9-10 
950 

10-0 
990 

10-3 
1,030 

10-5 
1,060 

10-7 
1,100 

10  li 
1,170 

11-3 
1,240 

24.0 

8-3 
990 

8-5 
1,040 

8-7 
1,090 

8-9 
1,130 

8-11 
i.170 

9-1 
1,220 

9-3 
1,260 

9-7 
1.340 

9-10 

1,420 

2x6 

12.0 

16-3 
790 

16-8 
830 

17-0 
860 

17-4 
900 

17-8 

930 

18-0 
970 

18-4 
1,000 

18-11 
1,070 

19-6 
1.130 

16.0 

14-9 
870 

15-2 
910 

15-6 
950 

15-9 
990 

i6-l 
1,030 

16-4 
1,060 

16-8 
1,100 

17-2 
1.170 

17-8 
1,240 

24.0 

12-11 
990 

13-3 
1,040 

13-6 
1,090 

13-9 
1.130 

14-1 
1,170 

14-4 
1,220 

14-7 
1.260 

15-0 
1,340 

15-6 
1,420 

2x8 

12.0 

21  -5 
790 

21-11 
830 

22-5 
860 

22-  11 
900 

23-4 
930 

23-9 
970 

24-2 
1.000 

24-  1 1 
1,070 

25-8 
1,130 

16.0 

19-6 
870 

19-11 
910 

20-5 
950 

20-10 
990 

21-2 
1,030 

21-7 
1,060 

21-11 
1,100 

22-8 
1.170 

23-4 
1,240 

24.0 

17-0 
990 

17-5 
1,040 

17-10 
1,090 

18-2 
1.130 

18-6 
1,170 

18-10 
1,220 

19-2 
1,260 

19-10 
1,340 

20-5 
1.420 

2x10 

12.0 

27-5 
790 

28-0 
830 

28-7 
860 

29-2 
900 

29-9 
930 

30-4 
970 

30-  10 
1,000 

31  -  10 
1,070 

32-9 
1,130 

16.0 

24-10 
870 

25-5 
910 

26-0 
950 

26-6 
990 

27-1 
1,030 

27-6 
1,060 

28-0 
1,100 

28-11 
1,170 

29-9 
1,240 

24.0 

21  -9 
990 

22-3 
1,040 

22-9 
1,090 

23-2 
1,130 

23-8 
1,170 

24- i 

1,220 

24-6 
1,260 

25-3 
1,340 

26-0 
1,420 

For  SI:  1  inch  =  25.4  mm 
NOTE:  The  extreme  fiber 


1  pound 
stress  in 


per  square  inch  = 
bending,  "Fb. "  in 


6.895  kPa. 
pounds  per 


1  pound  per  square  foot  =  0 
square  inch  is  shown  below 


0479  kN/m2. 
each  span. 


564 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4dd 
ALLOWABLE  SPANS  FOR  CEILING  JOISTS 

10  Lbs  per  Sq.  Ft  Live  Load 
(No  attic  storage  and  roof  slope  not  steeper  than  3  in  12) 
(Gypsum  Ceiling) 
DESIGN  CRITERIA:  Deflection — For  10  lbs.  per  sq.  ft  live  load.  Limited  to  span  in  inches  divided  by  240 
Strength — Live  load  of  10  lbs.  per  sq.  Ft.  plus  dead  load  of  5  lbs.  per  sq.  ft.  determines  fiber  stress  value. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  joists  (upper  figure  in  each  square)  Determine  size  and 
(first  column)  based  stress  grade  (lower  figure  in  each  square)  and  modulus  of  elasticity  (top  row)  of  lumber  to 


spacing 
be  used. 


JOIST  SIZE  AND 
SPACING 

MODULUS  OF  ELASTICITY,  "E,"  IN  1,000,000  PSI 

(inches) 

(inches) 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

1.1 

1.2 

L3 

2x4 

12.0 

7-10 
450 

8-5 
520 

8-11 
590 

9-5 
650 

9-10 
710 

10-3 

770 

10-7 
830 

10-11 
880 

11-3 
930 

11-7 
980 

16.0 

7-1 

490 

7-8 
570 

8-1 
650 

8-7 
720 

8-11 
780 

9-4 
850 

9-8 
910 

9-11 
970 

10-3 
1,030 

10-6 
1,080 

24.0 

6-2 
560 

6-8 
660 

7-1 

740 

7-6 

820 

7-10 
900 

8-1 

970 

8-5 
1,040 

8-8 
1,110 

8-11 
1,170 

9-2 

1,240 

2x6 

12.0 

12-3 

450 

13-3 
520 

14-1 
590 

14-9 
650 

15-6 
710 

16-1 

770 

16-8 
830 

17-2 
880 

17-8 
930 

18-2 
980 

16.0 

11-2 

490 

12-0 
570 

12-9 
650 

13-5 
720 

14-1 
780 

14-7 
850 

15-2 
910 

15-7 
970 

16-i 
1,030 

16-6 
1,080 

24.0 

9-9 
560 

10-6 
660 

11-2 
740 

11-9 
820 

12-3 
900 

12-9 
970 

13-3 
1,040 

13-8 
1,110 

14-1 

1,170 

14-5 
1,240 

2x8 

12.0 

16-2 
450 

17-5 
520 

18-6 
590 

19-6 
650 

20-5 
710 

21-2 
770 

21-11 
830 

22-8 
880 

23-4 
930 

24-0 
980 

16.0 

14-8 
490 

15-10 

570 

16-10 
650 

17-9 
720 

18-6 
780 

19-3 
850 

19-11 
910 

20-7 
970 

21-2 
1,030 

21-9 
1,080 

24.0 

12-10 
560 

13-10 
660 

14-8 
740 

15-6 
820 

16-2 
900 

16-10 
970 

17-5 
1,040 

18-0 
1,110 

18-6 
1,170 

19-0 
1,240 

2x10 

12.0 

20-8 
450 

22-3 
520 

23-8 
590 

24-10 
650 

26-0 
710 

27-1 
770 

28-0 
830 

28-  11 
880 

29-9 
930 

30-7 
980 

16.0 

18-9 
490 

20-2 
570 

21  -6 
650 

22-7 
720 

23-8 
780 

24-7 
850 

25-5 
910 

26-3 
970 

27-  i 
1,030 

27-9 
1,080 

24.0 

16-5 
560 

17-8 
660 

18-9 
740 

19-9 
820 

20-8 
900 

21-6 
970 

22-3 
1,040 

22-11 
1,110 

23-8 
1,170 

24-3 
1,240 

(inches) 

(inches) 

1.4 

IS 

1.6 

1.7 

1.8 

1.9 

2.0 

2.2 

2.4 

2x4 

12.0 

11-10 
1,030 

12-2 
1.080 

12-5 
1.130 

12-8 
1,180 

12-11 
1,220 

13-2 
1,270 

13-4 
1,310 

13-9 
1,400 

14-2 
1,480 

16.0 

10-9 
1,140 

11-0 
1,190 

11  -3 
1,240 

11  -6 
1,290 

11-9 
1,340 

11-11 
1,390 

12-2 
1,440 

12-6 
1,540 

12-  11 
1,630 

24,0 

9-5 
1,300 

9-8 
1,360 

9-10 
1,420 

10-0 
1,480 

10-3 
1,540 

10-5 
1,600 

10-7 
1,650 

10-11 
1,760 

11-3 
1,860 

2x6 

12.0 

18-8 
1,030 

19-1 
1,080 

19-6 
1,130 

19-11 
1,180 

20-3 
1,220 

20-8 
1,270 

21-0 
1,310 

21-8 
1,400 

22-4 
1,480 

16.0 

16-11 
1,140 

17-4 
1,190 

17-8 
1,240 

18-1 
1,290 

18-5 
1,340 

18-9 
1,390 

19-1 
1,440 

19-8 
1,540 

20-3 
1,630 

240 

14-9 
1,300 

15-2 
1,360 

15-6 
1,420 

15-9 
1,480 

16-1 
1,540 

16-4 
1,600 

16-8 
1,650 

17-2 
1,760 

17-8 
i,860 

2x8 

12.0 

24-7 
1,030 

25-2 
1,080 

25-8 
1,130 

26-2 
1,180 

26-9 
1,220 

27-2 
1,270 

27-8 
1,310 

28-7 
1,400 

29-5 
1,480 

16.0 

22-4 
1,140 

22-10 
1,190 

23-4 
1,240 

23-10 
1,290 

24-3 
1,340 

24-8 
1,390 

25-2 
1,440 

25-11 
1,540 

26-9 
1,630 

24.0 

19-6 
1,300 

19-11 
1,360 

20-5 
1,420 

20-10 
1,480 

21-2 
1,540 

21-7 
1,600 

21-11 
1,650 

22-8 
1,760 

23-4 
1,860 

2x10 

12.0 

31-4 
1,030 

32-1 
1,080 

32-9 
1,130 

33-5 
1,180 

34-1 
1,220 

34-8 
1,270 

35-4 
1,310 

36-5 
"1,400 

37-6 
1,480 

160 

28-6 
1,140 

29-2 
1,190 

29-9 
1,240 

30-5 
1,290 

31  -0 
1,340 

31  -6 
1,390 

32-1 
1,440 

33-  1 
1,540 

34-  1 
1,630 

24.0 

24-10 
1,300 

25-5 
1,360 

26-0 

1,420 

26-6 
1,480 

27-1 
1,540 

27-6 
1,600 

28-0 
1,650 

28-11 
1,760 

29-9 
1,860 

For  SI:  1  inch  =  25.4  mm, 
NOTE:  The  extreme  fiber 


1  pound 
stress  in 


per  square  inch  = 
bending,  "Fb, "in 


6.895  kPa, 
pounds  per 


1  pound  per  square  foot  =  0. 
square  inch  is  shown  below 


0479  kN/m2. 
each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


565 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4a 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft.  Live  Load 

For  Use  in  Snow  Load  Zone  1 

DESIGN  CRITERIA:  Strength  25  lbs.  per  sq.  ft.  live  load  plus  1 0  lbs.  peT  sq  .ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  180. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 


based  on  stress  grade  (top  row)  and  modulus  of  e 

.asticitv  (1 

jwerfigur 

i  in  each  square)  of  i 

umber  to  1 

e  u.sed 

RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING.  "Ft 

"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-7 

.12 

7-7 
18 

8-6 
.25 

9-4 
.33 

10-0 
41 

10-9 
.50 

11-5 
.60 

12-0 
.70 

12-7 
.81 

13-2 
.92 

16.0 

5-8 
.10 

6-7 
.15 

7-4 
.21 

8-1 
.28 

8-8 
.36 

9-4 
.43 

9-10 

.52 

10-5 
.61 

10-1! 
.70 

il-5 
.80 

24.0 

4-8 
.08 

5-4 
.13 

6-0 
.18 

6-7 
.23 

7-1 
.29 

7-7 
.35 

8-1 
.42 

8-6 
.50 

8-11 
.57 

9-4 
.65 

2x8 

12.0 

8-8 

.12 

10-0 
.18 

11-2 
.25 

12-3 
.33 

13-3 
.41 

14-2 
.50 

15-0 
.60 

15-10 
.70 

16-7 
.81 

17-4 
.92 

16.0 

7-6 
.10 

8-8 
.15 

9-8 
.21 

10-7 
.28 

11-6 
.36 

12-3 
.43 

13-0 
.52 

13-8 
61 

"|4-4 
.70 

15-0 
.80 

24.0 

6-2 

.08 

7-1 
13 

7-11 
.18 

8-8 

9-4 
.29 

10-0 
.35 

10-7 

42 

11-2 
.50 

11-9 

.57 

12-3 
.65 

2x10 

12.0 

11-1 

.12 

12-9 
.18 

14-3 
.25 

15.8 

.33 

16-11 
.41 

18-1 
.50 

19-2 
.60 

20-2 
.70 

21-2 
.81 

.92 

16.0 

9-7 
.10 

11-1 
15 

12-4 
.21 

13-6 
.28 

14-8 
.36 

15-8 
.43 

16-7 

.52 

17-6 
.6! 

18-4 

.70 

19-2 
.80 

24.0 

7-10 
.08 

9-0 
.13 

10-1 
.18 

11-1 

11-11 
.29 

12-9 

35 

13-6 
.42 

14-3 
.50 

15-0 

57 

15-8 
.65 

2x12 

12.0 

13-6 

0.12 

15-6 
0.18 

17-4 
0.25 

19-0 
0.33 

20-7 
0.41 

22-0 
0.50 

23-4 
0.60 

24-7 
0  70 

25-9 
0.81 

26-11 
0.92 

16.0 

11-8 

0.10 

13-5 

0.15 

15-0 
0.21 

16-6 
0.28 

17-9 
0.36 

19-0 

0.43 

20-2 
0.52 

21-3 
0.61 

22-3 
0.70 

0.92 

24.0 

9-6 
0.08 

11-0 

0.13 

12-3 
0.18 

13-5 

0.23 

14-6 

0.29 

15-6 
0.35 

16-6 

0.42 

17-4 
0.50 

18-3 
0.57 

19-0 
0.65 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

13-8 
1.04 

14-2 
1.16 

14-8 
1.29 

15-2 
1.42 

15-8 
1.55 

16-1 
1.69 

16-7 
1.84 

17-0 
1.98 

17-5 
2.13 

17-10 
2.29 

16.0 

11-10 
.90 

12-4 
1.01 

12-9 
1.12 

13-2 
1.23 

13-7 
1.35 

13-11 
1.47 

14-4 
1.59 

14-8 
1.72 

15-1 
1.85 

15-5 
1.98 

24.0 

9-8 

.74 

10-0 
.82 

10-5 
.91 

10-9 
1.00 

U-i 
1.10 

11-5 

1.20 

11-8 
1.30 

12-0 
1.40 

12-4 

:  5! 

12-7 
1.62 

2x8 

12.0 

18-0 

1.04 

18-9 
1.16 

19-5 
1.29 

20-0 
1.42 

20-8 
1.55 

21-3 
1.69 

21-10 
1.84 

22-4 
1.98 

22-11 
2.13 

23-6 
2.29 

16.0 

15-7 
.90 

16-3 
1.01 

16-9 
1.12 

17-4 
1.23 

17-10 
1.35 

18-5 
1.47 

18-1! 

1.59 

19-5 
1.72 

19-10 
1.85 

20-4 
1.98 

24.0 

12-9 

.74 

13-3 
.82 

13-8 
.9"! 

14-2 
1.00 

14-7 
1.10 

15-0 
1.20 

15-5 
1.30 

15-10 
1.40 

16-3 
1 .51 

16-7 
1.62 

2x  10 

12.0 

23-0 
1.04 

23-11 
1.16 

24-9 
1.29 

25-6 
1.42 

26-4 
1.55 

27-1 
1.69 

27-10 
1.84 

28-7 
1.98 

28-3 
2.13 

30-0 
2.29 

16.0 

19-11 
.90 

20-8 
1.01 

21-5 
1.12 

22-1 
1.23 

22-10 
1.35 

23-5 
1.47 

24-1 
1.59 

24-9 
1.72 

25-4 
1.85 

25-11 
1.98 

24.0 

16-3 

.74 

16-11 
.82 

17-6 
.91 

18-1 
1.00 

18-7 
1.10 

19-2 
1.20 

19-8 
1.30 

20-2 
1  40 

20-8 
1.51 

21-2 
1.62 

2x  12 

12.0 

28-0 
1.04 

29-1 
1.16 

30-1 
1.29 

31-1 
1.42 

32-0 
1.56 

33-0 
1.70 

33-10 
1.84 

34-9 
1.98 

35-8 
2.13 

36-5 
2.29 

16.0 

24-3 
0.90 

25.2 
1.01 

26-0 
1.12 

26-10 
1.23 

27-9 
1.35 

28-6 
1.47 

29-2 
1.59 

30-0 
1.72 

30-9 
1.85 

31-6 
1.98 

24  0 

19-10 
0.74 

20-7 
0.82 

21-3 
0.91 

22-0 
1.01 

22-8 
1.10 

23-4 
1.20 

23-11 
1.30 

24-7 
1.4! 

25-2 

1.51 

25-9 
1.62 

For  SI:  1  inch  =  25,4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E,1 


square  mch  =  6.895  kPa.  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


566 


780  CMR  -  Sixth  Edition    corrected  -  9/ 19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4b 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Gypsum  Wallboard  Ceiling) 
For  Use  in  Snow  Load  Zone  1 
DESIGN  CRITERIA:  Strength — 25  lbs.  per  sq.ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Ft 

."  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-7 
.15 

7-7 
.24 

8-6 
.33 

9-4 

.43 

10-0 
.55 

10-9 
.67 

11-5 
.80 

12-0 

.94 

12-7 
1.03 

13-2 
1.23 

16.0 

5-8 

.13 

6-7 
.20 

7-4 
.29 

8-1 

38 

8-8 

.47 

9-4 
58 

9-10 
.69 

10-5 
.81 

10-11 
93 

11-5 
1.06 

24.0 

4-8 
.11 

5-4 

.17 

6-0 
.23 

6-7 
.31 

7-1 
.39 

7-7 
.47 

8-1 
.56 

8-6 
.66 

8-11 
.76 

9-4 

.87 

2x8 

12.0 

8-8 

.15 

10-0 
.24 

11-2 

.33 

12-3 
.43 

13-3 

.55 

14-2 
.67 

15-0 

.80 

15-10 
.94 

16-7 
1.08 

17-4 
1  23 

16.0 

7-6 
.13 

8-8 

.20 

9-8 
.29 

i0-7 
.38 

11-6 

.47 

12-3 
.58 

13-0 

.69 

13-8 
.81 

14-4 
.93 

15-0 
1.06 

24.0 

6-2 

.11 

7-1 
.17 

7-11 
.23 

8-8 

.31 

9-4 
.39 

10-0 

.47 

10-7 
.56 

11-2 
.66 

11-9 

76 

12-3 
.87 

2x  10 

12.0 

11-1 
.15 

12-9 

.24 

14-3 
.33 

15-8 
.43 

16-11 
.55 

18-1 

.67 

19-2 
.80 

20-2 
.94 

21-2 
1.08 

22-1 
1.23 

16.0 

9-7 
.13 

11-1 
.20 

12-4 
.29 

13-6 
.38 

14-8 

47 

15-8 
.58 

16-7 
69 

17-6 
.81 

18-4 
.93 

19-2 
1.06 

24.0 

7-10 
.11 

9-0 

.17 

10-1 

.23 

11-1 
.31 

11-11 
39 

12-9 
.47 

13-6 

.56 

14-3 
.66 

15-0 
.76 

15-8 
.87 

2x  12 

12.0 

13-5 
.15 

15-6 
.24 

17-4 
.33 

19-0 
.43 

20-6 
.55 

21-11 
.67 

.80 

24-7 
.94 

25-9 
1.08 

26-11 
1.23 

16.0 

11-8 

13 

13-5 

20 

15-0 
.29 

16-6 
.38 

17-9 
47 

19-0 
.58 

20-2 
69 

21-3 
.81 

22-4 
.93 

1.06 

24.0 

9-6 

.11 

11-0 

.17 

12-3 

23 

13-5 
.31 

14-6 

.39 

15-6 

.47 

16-6 
.56 

17-4 
.66 

18-2 
.76 

19-0 
.87 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

13-8 

1.39 

14-2 
1.55 

14-8 

1.72 

15-2 
1.89 

15-8 
2.07 

16-1 
2.26 

16-7 
2.45 

17-0 
2.65 

17-5 
2.85 

17-10 
3.06 

16.0 

11-10 
1.20 

12-4 
1.34 

12-9 
1.49 

13-2 
1.64 

13-7 
1.80 

13-11 
1.96 

14-4 
2.12 

14-8 
2.29 

15-1 
2.46 

15-5 
2.64 

24.0 

9-8 
.98 

10-0 
1.10 

lo-5 

1.21 

10-9 
1.34 

11-1 
1.47 

11-5 
1.60 

11-8 
1.73 

12-0 
1.87 

12-4 
2.01 

12-7 
2.16 

2x8 

12.0 

18-0 
1.39 

18-9 
1.55 

19-5 
1.72 

20-0 
1.89 

20-8 
2.07 

21-3 
2.26 

21-10 
2.45 

22-5 
2.65 

22-11 
2.85 

23-6 
3.06 

16.0 

15-7 

1.20 

16-3 
1.34 

16-9 
1.49 

17-4 
1.64 

17-10 
1.80 

18-5 

1.96 

18-11 
2.12 

19-5 
2.29 

19-10 
2.46 

20-4 
2.64 

24.0 

12-9 
.98 

13-3 
1.10 

13-8 
1.21 

14-2 
1.34 

14-7 
1.47 

15-0 
1.60 

15-5 
1.73 

15-10 
1.87 

16-3 
2.01 

16-7 
2.16 

2x  10 

12.0 

23-0 
1.39 

23-11 
1.55 

24-9 
1.72 

25-6 
1.89 

26-4 
2.07 

27-2 
2.26 

27-10 
2.45 

28-7 
2.65 

29-3 
2.85 

29-11 
3.06 

16.0 

19-11 
1.20 

20-8 
1.34 

21-5 
1.49 

22-1 
1.64 

22-10 
1.80 

23-5 
1.96 

24-1 
2.12 

24-9 
2.29 

25-4 
2.46 

25-11 
2.64 

24.0 

16-3 
.98 

16-11 
1.10 

17-6 
1.21 

18-1 

1.34 

18-7 

1.47 

19-2 
1.60 

19-8 
1.73 

20-2 
1.87 

20-8 
2.01 

21-2 
2.16 

2x  12 

12.0 

28-0 
1.39 

29-1 
1.55 

30-1 
1.72 

31-1 
1.89 

32-0 
2.07 

32-11 
2.26 

33-9 
2.45 

34-9 
2.65 

35-7 
2.85 

36-6 
3.06 

16.0 

24-3 
1.20 

25-2 
1.34 

26-0 
1.49 

26-10 
1.64 

27-9 
1.80 

28-6 
1.96 

29-4 
2.12 

30-1 
2.29 

30-9 
2.46 

31-6 
2.64 

24.0 

19-10 
.98 

20-6 
1.10 

21-3 
1.21 

21-11 
1.34 

22-8 
1.47 

23-3 
1.60 

23-11 
1.73 

24-7 
1.87 

25-2 
2.01 

25-9 
2.16 

For  SI:  1  inch  =  25.4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity.  "E." 


square  inch  =  6.895 
in  1 .000.000  pound* 


kPa,  1  pound  per  square  foot  =  0  0479 
per  square  inch  is  shown  below  each  s 


kN/m2. 
pan. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4c 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 
For  Use  in  Snow  Load  Zone  1 

DESIGN  CRITERIA:  Strength-25  lbs.  per  sq.ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spar.s  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  eaui  square)  Determine  size  and  spacing  (first  column) 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fb,' 

(psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-7 
.23 

7-7 
.35 

8-6 
.50 

9-4 
.65 

10-0 
.82 

10-9 
1.00 

11-5 
1.20 

12-0 
1.40 

12-7 
1.62 

13-2 
1.84 

16.0 

5-8 

.20 

6-7 
.31 

7-4 
.43 

8-1 
.56 

8-8 

.71 

9-4 

.87 

9-10 
1.04 

10-5 
1.21 

10-11 
1.40 

11-5 
1.60 

24.0 

4-8 
.16 

5-4 
.25 

6-0 
.35 

6-7 
.46 

7-1 

.58 

7-7 
.71 

8-1 
.85 

8-6 
.99 

8-11 
1.14 

9-4 
1.30 

2x8 

12.0 

8-8 

.23 

10-0 
.35 

11-2 
.50 

12-3 
.65 

13-3 
.82 

14-2 
1.00 

15-0 
1.20 

15-10 
1.40 

16-7 
1.62 

17-4 
1.84 

16.0 

7-6 
.20 

8-8 
.31 

9-8 
.43 

10-7 
.56 

11-6 

.71 

12-3 

.87 

13-0 
1.04 

13-8 

1.21 

14-4 
1.40 

15-0 
1.60 

24.0 

6-2 
.16 

7-1 

.25 

7-11 
.35 

8-8 
.46 

9-4 
.58 

10-0 
.71 

10-7 
.85 

11-2 
99 

11-9 
1.14 

12-3 
1.30 

2x  10 

12.0 

11-1 
.23 

12-9 
.35 

14-3 
.50 

15.8 
.65 

16-11 
.82 

18-1 
1.00 

19-2 
1.20 

20-2 
1.40 

21-2 
1.62 

22-1 
1.84 

16.0 

9-7 
.20 

11-1 
.31 

12-4 
.43 

13-6 
.56 

14-8 
.71 

15-8 
.87 

16-7 
1.04 

17-6 
1.21 

18-4 
1.40 

19-2 
1.60 

24.0 

7-10 
.16 

9-0 
.25 

10-1 
.35 

11-1 
.46 

11-11 
.58 

12-9 
.71 

13-6 
.85 

14-3 
.99 

15-0 
1.14 

15-8 
1.30 

2x12 

12.0 

13-5 
.23 

15-6 
.35 

17-4 
.50 

19-0 
.65 

20-6 
.82 

21-11 
1.00 

23-3 
1.20 

24-7 
1.40 

25-9 
1.62 

26-11 
1.84 

16.0 

11-8 
.20 

13-5 
.31 

15-0 
.43 

16-6 
.56 

17-9 
.71 

19-0 
.87 

20-2 
1.04 

21-3 
1.21 

22-4 
1.40 

23-3 
1.60 

24.0 

9-6 
.16 

11-0 
.25 

12-3 
.35 

13-5 
.46 

14-6 
.58 

15-6 
.71 

16-6 
.85 

17-4 
.99 

18-2 
1.14 

19-0 
1.30 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

13-8 
2.08 

14-2 
2.32 

14-8 
2.58 

15-2 
2.84 

15-8 
3.11 

16-1 
3.39 

16-6 
3.68 

17-0 
3.97 

17-5 
4.28 

17-10 
4.58 

16.0 

11-10 
1.80 

12-4 
2.01 

12-9 
2.23 

13-2 
2.46 

13-7 
2.69 

13-11 
2.93 

14-4 
3.18 

14-8 
3.44 

15-1 
3.70 

15-5 
3.96 

24.0 

9-8 
1.47 

10-0 
1.64 

10-5 
1.82 

10-9 
2.01 

11-1 
2.20 

11-5 
2.40 

11-8 
2.60 

12-0 
2.81 

12-4 
3.02 

12-7 
3.24 

2x8 

12.0 

18-0 
2.08 

18-9 
2.32 

19-5 
2.58 

20-0 
2.84 

20-8 
3.11 

21-3 
3.39 

21-10 
3.68 

22-5 
3.97 

22-11 
4.28 

23-6 
4.59 

16.0 

15-7 
1.80 

16-3 
2.01 

16-9 
2.23 

17-4 
2.46 

17-10 
2.69 

18-4 
2.93 

18-10 
3.18 

19-4 
3.44 

19-10 
3.70 

20-4 
3.97 

24.0 

12-9 
1.47 

13-3 
1.64 

13-8 
1.82 

14-2 
2.01 

14-7 
2.20 

15-0 
2.40 

15-5 
2.60 

15-10 
2.81 

16-3 
3.02 

16-7 
3.24 

2x  10 

12.0 

23-0 
2.08 

23-11 
2.32 

24-9 
2.58 

25-7 
2.84 

26-4 
3.11 

27-2 
3.39 

27-10 
3.68 

28-7 
4.28 

29-3 
4.59 

29-11 
4.90 

16.0 

19-11 
1.80 

20-8 
2.01 

21-5 
2.23 

22-1 
2.46 

22-9 
2.69 

23-5 
2.93 

24-1 
3.18 

24-9 
3.44 

25-4 
3.70 

25-11 
3.97 

24.0 

16-3 
1.47 

16-11 

1.64 

17-6 
1.82 

18-1 
2.01 

18-7 
2.10 

19-2 
2.40 

19-8 
2.60 

20-2 
2.81 

20-8 
3.02 

21-2 
3.24 

2x  12 

12.0 

28-0 
2.08 

29-1 
2.33 

30-2 
2.58 

31-1 

2.84 

32-0 
3.11 

32-11 
3.39 

33-11 
3.68 

34-9 
3.97 

35-7 
4.28 

36-5 
4.59 

16.0 

24-3 
1.80 

25-2 
2.01 

26-0 
2.23 

26-11 
2.46 

27-9 
2.69 

28-6 
2.93 

29-4 
3.18 

30-1 

3.44 

30-10 
3.70 

31-6 
3.97 

24.0 

19-10 
1.47 

20-6 
1.64 

21-3 
1.82 

21-11 
2.01 

22-8 
2.20 

23-3 
2.40 

23-11 
2.60 

24-7 
2.81 

25-2 
3.02 

25-9 
3.24 

For  SI:  1  inch  =  25,4 
NOTE:  The  modulus 


mm,  1  pound 
of  elasticity, ' 


per  square  inch  = 
E,"  in  1 .000,000 


■■  6.895  kPa, 
pounds  per 


1  pound  per  square  foot  =  0.0479  kN/m2. 
square  inch  is  shown  below  each  span. 


568 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4d 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft  Live  Load 

For  Use  in  Snow  Load  Zone  1 
DESIGN  CRITERIA:  Strength — 25  lbs.  per  sq.  ft.live  load  plus  15  lbs.  per  sq.ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  180. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Ft 

."  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-2 
0.09 

7-1 

0.15 

7-11 
0.20 

8-8 

0.27 

9-5 
0.34 

10-0 
0.41 

10-8 
0.49 

11-3 
0.57 

11-9 

0.66 

12-4 

0.75 

16.0 

5-4 
.08 

6-2 

.13 

6-10 
.18 

7-6 

.23 

8-2 
.29 

8-8 
.36 

9-3 

.42 

9-9 

.50 

10-2 

57 

10-8 
.65 

24.0 

4-4 
07 

5-0 
10 

5-7 
.14 

6-2 
.19 

6-8 
.24 

7-1 
.29 

7-6 
.35 

7-11 
.41 

8-4 

.47 

8-8 

.53 

2x8 

12.0 

8-1 

.09 

9-4 
.15 

10-6 
.20 

11-6 

27 

12-5 
.34 

13-3 
.41 

14-0 
.49 

14-10 
.57 

15-6 
.66 

16-3 
.75 

16.0 

7-0 
.08 

8-1 

.13 

9-1 
.18 

9-11 

.23 

10-9 
.29 

11-6 
.36 

12-2 

.42 

12-10 
.50 

13-5 
.57 

14-0 
.65 

24.0 

5-9 

.07 

6-7 

.10 

7-5 
.14 

8-1 
.19 

8-9 
.24 

9-4 
.29 

9-11 
.35 

10-6 

.41 

11-0 
.47 

11-6 
.53 

2\  10 

12.0 

10-4 
.09 

11-11 
.15 

13-4 
.20 

14-8 
.27 

15-10 

.34 

16-11 
.41 

17-11 
.49 

18-11 
.57 

19-10 
.66 

20-8 
.75 

160 

8-11 
.08 

10-4 
.13 

11-7 
.18 

12-8 
23 

13-8 
.29 

14-8 
.36 

15-6 

.42 

16-4 
.50 

17-2 
.57 

17-11 
.65 

24.0 

7-4 
.07 

8-5 
.10 

9-5 
.14 

10-4 
19 

11-2 

.24 

11-11 
.29 

12-8 

.35 

13-4 
.41 

14-0 
.47 

14-8 
.53 

2x  12 

12.0 

12-7 
.09 

14-6 

.15 

16-3 
.20 

17-9 
.27 

19-3 
.34 

20-6 
.41 

21-9 
.49 

23-0 

.57 

24-1 
.66 

25-2 
.75 

16.0 

10-11 
.08 

12-7 
.13 

14-1 
.18 

15-5 

.23 

16-8 
.29 

17-9 
.36 

18-10 
.42 

19-11 
.50 

20-10 
.57 

21-9 
.65 

24.0 

8-11 
.07 

10-3 
.10 

11-6 

.14 

12-7 
.19 

13-7 
.24 

14-6 
.29 

15-5 
.35 

16-3 
.41 

17-0 

.47 

17-9 
.53 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-10 
.85 

13-3 
.95 

13-9 
1.05 

14-2 
1.16 

14-8 
1.27 

15-1 
1.39 

15-6 
1.50 

15-11 
1.62 

16-3 
1.75 

16-8 
1.87 

16.0 

11-1 

.74 

11-6 
.82 

11-11 
91 

12-4 
1.01 

12-8 
1.10 

13-1 
1.20 

13-5 
1.30 

13-9 
1.41 

14-1 
1.51 

14-5 
1.63 

240 

9-1 
.60 

9-5 

.67 

9-9 
.75 

10-0 
.82 

10-4 
.90 

10-8 
.98 

10-11 
1.06 

11-3 
1.15 

11-6 
1.24 

11-9 
1.32 

2x8 

12.0 

16-10 

85 

17-6 
.95 

18-1 
1.05 

18-9 
1.16 

19-4 
1.27 

19-10 
1.39 

20-5 
1.50 

20-11 
1.62 

21-11 
1.75 

21-11 
1.87 

16.0 

14-7 

.74 

15-2 
.82 

15-8 
.91 

16-3 
1.01 

16-9 
1.10 

17-2 
1.20 

17-8 
1.30 

18-1 
1.41 

18-7 
1.51 

19-0 
1.63 

24.0 

ll-ll 

60 

12-5 
.67 

12-10 
.75 

13-3. 
.82 

13-8 
.90 

14-0 
.98 

14-5 
1.06 

14-10 
1.15 

15-2 
1.24 

15-6 
1.32 

2x  10 

12.0 

21-6 
.85 

22-4 
.95 

23-1 
1.05 

23-11 
1.16 

24-7 
1.27 

25-4 
1.39 

26-0 
1.50 

26-8 
1.62 

27-4 
1.75 

28-0 
1.87 

16.0 

18-8 
.74 

19-4 
.82 

20-0 
.91 

20-8 
1.01 

21-4 
1.10 

21-11 
1.20 

22-6 
1.30 

23-1 
1.41 

23-8 
1.75 

24-3 
1.63 

24.0 

1 5-3 
.60 

15-10 
.67 

16-4 
.75 

16-11 
.82 

17-5 
.90 

17-11 
.98 

18-5 
1.06 

18-11 
1.15 

19-4 
1.24 

19-9 
1.32 

2x  12 

12.0 

26-2 
0.85 

27-2 
0.95 

28-2 
1.05 

29-1 
1.16 

29-11 
1.27 

30-10 
1.39 

31-8 
1.50 

32-6 
1.62 

33-3 
1.75 

34-1 
1.87 

160 

22-8 
0.74 

23-6 
0.83 

24-4 
0.92 

25-2 
1.01 

25-11 
1.10 

26-8 
1.20 

27-5 
1.30 

28-2 
1.41 

28-10 
1.51 

29-6 
1.63 

240 

1 8-6 
0  60 

19-2 
0.67 

19-10 
0.75 

20-6 
0X2 

21-2 
0.90 

21-9 
0.98 

22-4 
1.06 

22-11 
1  15 

23-6 
1.24 

24-1 

1.32 

For  SI:  I  inch  =  25.4  mm.  I  pound  per 
NOTE:  The  modulus  of  clasticitv,  "E," 


square  inch  =  6.895  kPa.  1  pound  per  square  foot  = 
in  1 ,000,000  pounds  per  square  inch  is  shown  bclo 


0.0479 
v  each  s 


kN/m2 
pan. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


569 


780  CiMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3608.2.4e 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Gypsum  Wallboard  Ceiling) 
For  Use  in  Snow  Load  Zone  1 
DESIGN  CRITERIA:  Strength-25  lbs.  per  sq.  ft.  live  load  plus  15  lbs.  per  sq.ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  .n  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-2 
.13 

7-1 
.19 

7-11 

.27 

8-8 
.36 

9-5 

.45 

10-0 
.55 

10-8 
.65 

11-3 
.77 

11-9 
.88 

12-4 
1.01 

16.0 

5-4 
.11 

6-2 

.17 

6-10 
23 

7-6 
.31 

8-2 
.39 

8-8 

.47 

9-3 
.57 

9-9 
.66 

10-2 
.76 

10-8 
.87 

24.0 

4-4 
.09 

5-0 

.14 

5-7 
•19 

6-2 
.25 

6-8 

.32 

7-1 
.39 

7-6 
.46 

7-11 

.54 

8-4 

.62 

8-8 

.71 

2x8 

12.0 

8-1 
.13 

9-4 
.19 

10-6 
.27 

11-6 
.36 

12-5 
.45 

13-3 
.55 

14-0 
.65 

14-10 
.77 

15-6 
.88 

16-3 
1.01 

16.0 

7-0 
.11 

8-1 
.17 

9-1 

.23 

9-11 
.31 

10-9 
.39 

11-6 
.47 

12-2 
.57 

12-10 
.66 

13-5 
.76 

14-0 
.87 

24.0 

5-9 

.09 

6-7 
.14 

7-5 
.19 

8-1 

.25 

8-9 
.32 

9-4 
.39 

9-11 
.46 

10-6 
.54 

11-0 
.62 

11-6 
.71 

2x  10 

12.0 

10-4 
.13 

11-11 
.19 

13-4 
.27 

14-8 
.36 

15-10 
.45 

16-11 
.55 

17-11 
.65 

18-11 
.77 

19-10 
.88 

20-8 
1.01 

16.0 

8-11 
.11 

10-4 

.17 

11-7 
.23 

12-8 
.31 

13-8 
.39 

14-8 
.47 

15-6 
.57 

16-4 
.66 

17-2 
.76 

17-11 
.87 

24.0 

7-4 
.09 

8-5 

.14 

9-5 
.19 

10-4 
.25 

11-2 
.32 

11-11 
.39 

12-8 
.46 

13-4 
.54 

14-0 
.62 

14-8 
.71 

2x12 

12.0 

12-7 
.13 

14-6 
.19 

16-3 
.23 

17-9 
.36 

19-3 
.45 

20-6 
.55 

21-9 
.65 

23-0 
.77 

24-1 
88 

25-2 
1.01 

16.0 

10-11 
.11 

12-7 
.17 

14-1 
.23 

15-5 
.31 

16-8 
.39 

17-9 
.47 

18-10 
.57 

19-11 
66 

20-10 
.76 

21-9 
.87 

24.0 

8-11 
.09 

10-3 
.14 

11-6 
.19 

12-7 
.25 

13-7 
.32 

14-6 
.39 

15-5 
.46 

16-3 
.54 

17-0 
.62 

17-9 
.71 

(Inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-10 
1.13 

13-3 
1.27 

13-9 
1.41 

14-2 
1.55 

14-8 
1.70 

15-1 
1.85 

15-6 
2.00 

15-11 
2.17 

16-3 
2.33 

16-8 
2.5 

16.0 

11-1 
0.98 

11-6 
1.10 

11-11 
1.22 

12-4 
1.34 

12-8 
1.47 

13-1 
1.60 

13-5 
1.74 

13-9 
1.88 

14-1 
2.02 

14-5 
2.17 

24.0 

9-1 

0.80 

9-5 
0.90 

9-9 
0.99 

10-0 
1.10 

10-4 
1.20 

10-8 
1.31 

10-11 
1.42 

11-3 

1.53 

11-6 
1.65 

11-9 
1.77 

2x8 

12.0 

16-10 
1.13 

17-6 
1.27 

18-1 
1.41 

18-9 
1.55 

19-4 
1.70 

19-10 
1.85 

20-5 
2.00 

20-11 
2.17 

21-6 
2.33 

21-11 
2.50 

16.0 

14-7 
0.98 

15-2 
1.10 

15-8 
1.22 

16-3 
1.34 

16-9 
1.47 

17-2 
1.60 

17-8 
1.74 

18-1 
1.88 

18-7 
2.02 

19-0 
2.17 

24.0 

11-11 
0.80 

12-5 
0.90 

12-10 
0.99 

13-3 
1.10 

13-8 
1.20 

14-0 
1.31 

14-5 
1.42 

14-10 
1.53 

15-2 
1.65 

15-5 
1.77 

2x  10 

12.0 

21-6 
1.13 

22-4 
1.27 

23-1 
1.41 

23-11 
1.55 

24-7 
1.70 

25-4 
1.85 

26-0 
2.00 

26-9 
2.17 

27-4 
2.33 

28-0 
2.50 

16.0 

18-8 
0.98 

19-4 
1.10 

20-0 
1.22 

20-8 
1  34 

21-4 
1.47 

21-11 
1.60 

22-6 
1.74 

23-1 
1.88 

23-8 
2.02 

24-3 
2.17 

24.0 

15-3 
0.80 

15-10 
0.90 

16-4 
0.99 

16-11 
1.10 

17-5 
1.20 

17-11 
1.31 

18-5 
1.42 

18-11 
1.53 

19-4 
1.65 

19-10 
1.77 

2x12 

12.0 

26-2 
1.13 

27-2 
1.27 

28-2 
1.41 

29-1 
1.55 

29-11 
1.70 

30-10 
1.85 

31-8 
2.00 

32-6 
2.17 

33-3 
2.33 

34-1 
2.50 

16.0 

22-8 
0.98 

23-6 
1.10 

24-4 
1.22 

25-2 
1.34 

25-11 
1.47 

26-8 
1.60 

27-5 
1.74 

28-1 
1.88 

28-10 
2.02 

29-6 
2.17 

24.0 

18-6 
080 

19-3 
.90 

19-11 
.99 

20-6 
1.10 

21-2 
1.20 

21-9 
1.31 

22-5 
1.42 

23-0 
1.53 

23-6 
1.65 

24-1 
1.77 

For  SI:  1  inch  =  25,4  mm,  I  pound  per 
NOTE:  The  modulus  of  elasticity ,  "E,' 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


570 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4f 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

25  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 
For  Use  in  Snow  Load  Zone  1 

DESIGN  CRITERIA:  Strength-25  lbs.  per  sq.  ft.  live  load  plus  15  lbs.  per  sq.ft.  dead  load  determines  fiber  stress. 
Deflection — For  25  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

6-2 
.19 

7-1 
.29 

7-11 
.41 

8-8 
.53 

9-5 
.67 

10-0 
.82 

10-8 
.98 

11-3 
1.15 

11-9 
1.32 

12-4 
1.51 

16.0 

5-4 
.16 

6-2 
.25 

6-10 
.35 

7-6 
.46 

8-2 
.58 

8-8 

.71 

9-3 
.85 

9-9 
.99 

10-2 
1.15 

10-8 
1.31 

24.0 

4-4 
.13 

5-0 
.21 

5-7 
.29 

6-2 
.38 

6-8 
.48 

7-1 
.58 

7-6 
.69 

7-11 
.81 

8-4 
.94 

8-8 
1.07 

2x8 

12.0 

8-1 
.19 

9-4 
.29 

10-6 
.41 

11-6 
.53 

12-5 
.67 

13-3 
.82 

14-0 
.98 

14-10 
1.15 

15-6 
1.32 

16-3 
1.51 

16.0 

7-0 
.16 

8-1 
.25 

9-1 

.35 

9-11 
.46 

10-9 
.58 

11-6 
.71 

12-2 
.85 

12-10 
.99 

13-5 
1.15 

14-0 
1.31 

24.0 

5-9 
.13 

6-7 
.21 

7-5 
.29 

8-1 
.38 

8-9 
.48 

9-4 
.58 

9-11 
.69 

10-6 
.81 

11-0 
.94 

11-6 
1.07 

2x10 

12.0 

10-4 
.19 

11-11 
.29 

13-4 
.41 

14-8 
.53 

15-10 
.67 

16-11 
.82 

17-11 

.98 

18-11 
1.15 

19-10 
1.32 

20-8 
1.51 

16.0 

8-11 
.16 

10-4 
.25 

11-7 
.35 

12-8 
.46 

13-8 
58 

14-8 
.71 

15-6 
.85 

16-4 
.99 

17-2 
1.15 

17-11 
1.31 

24.0 

7-4 
.13 

.5-5 
.21 

9-5 

.29 

10-4 
.38 

11-2 
.48 

11-11 
.58 

12-8 
.69 

13-4 
.81 

14-0 
.94 

14-8 
1.07 

2x12 

12.0 

12-7 
.19 

14-6 
.29 

16-3 
.41 

17-9 
.53 

19-3 

.67 

20-6 
.82 

21-9 
.98 

23-0 
1.15 

24-1 
1.32 

25-2 
1.51 

16.0 

10-11 
.16 

12-7 
.25 

14-1 
.35 

15-5 
.46 

16-8 
.58 

17-9 
.71 

18-10 
.85 

19-11 
.99 

20-10 
1.15 

21-9 
1.31 

24.0 

8-11 
.13 

10-3 
.21 

11-6 
.29 

12-7 
.38 

13-7 
.48 

14-6 
.58 

15-5 
.69 

16-3 
.81 

17-0 
.94 

17-9 
1.07 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-10 
1.70 

13-3 
1.90 

13-9 
2.11 

14-2 
2.32 

14-8 
2.55 

15-1 

2.77 

15-6 
3.01 

15-10 
3.25 

16-3 
3.49 

16-8 
3.75 

16.0 

11-1 
1.47 

.46 
1.65 

11-11 
1.83 

12-4 
2.01 

12-8 
2.20 

13-1 
2.40 

13-5 
2.61 

13-9 
2.82 

14-1 
3.03 

14-5 
3.25 

24.0 

9-1 

1.20 

9-5 
1.34 

9-9 
1.49 

10-0 
1.64 

10-4 
1.80 

10-8 
1.96 

10-11 
2.13 

11-3 
2.30 

11-6 
2.47 

11-9 
2.65 

2x8 

12.0 

16-10 
1.70 

17-6 
1.90 

18-1 
2.11 

18-9 
2.32 

19-4 
2.55 

19-10 

2.77 

20-5 
3.01 

20-11 
3.25 

21-5 
3.49 

21-11 
3.75 

16.0 

14-7 
1.47 

15-2 
1.65 

15-8 
183 

16-3 
2.01 

16-9 
2.20 

17-2 
2.40 

17-8 
2.61 

18-2 
2.82 

18-7 
3.03 

19-0 
3.25 

24.0 

11-11 
1.20 

12-5 
1.34 

12-10 
1.49 

13-3 
1.64 

13-8 
1.80 

14-0 
1.96 

14-5 
2.13 

14-10 
2.30 

15-2 
2.47 

15-6 
2.65 

2x  10 

12.0 

21-6 
1.70 

22-4 
1.90 

23-1 
2.11 

23-11 
2.32 

24-7 
2.55 

25-4 
2.77 

26-0 
3.01 

26-9 
3.25 

27-4 
3.49 

28-0 
3.75 

16.0 

18-8 

1.47 

19-4 
1.65 

20-0 
1.83 

20-8 
2.01 

21-4 
2.20 

21-11 
2.40 

22-6 
2.61 

23-2 
2.82 

23-9 
3.03 

24-3 
3.25 

24.0 

15-3 
1.20 

15-10 
1.34 

16-4 
1.49 

16-11 
1.64 

17-5 
1.80 

17-11 
1.96 

18-5 
2.13 

18-11 
2.30 

19-4 

2.47 

19-10 
2.65 

2x  12 

12.0 

26-2 
1.70 

27-2 
1.90 

28-2 
2.11 

29-1 
2.32 

29-11 
2.55 

30-10 
2.77 

31-8 
3.01 

32-6 
3.25 

33-3 
3.49 

34-1 

3.75 

16.0 

22-8 
1.47 

23-6 
1.65 

24-4 
1.83 

25-2 
2.01 

25-11 
220 

26-8 
2.40 

27-5 
2.61 

28-2 
2.82 

28-10 
3.03 

29-6 
3.25 

24.0 

18-6 
1.20 

19-3 
1.34 

19-11 
1.49 

20-6 
1.64 

21-2 
1  SO 

21-9 
1.96 

22-5 
2.13 

23-0 
2.30 

23-6 
2.47 

24-1 
2.65 

For  SI:  1  inch  =  25,4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6  895  kPa,  1  pound  per  square  foot  =  0 
in  1 ,000,000  pounds  per  square  inch  is  shown  below 


0479 
:ach  s 


kN/m2. 
pan. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


571 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4g 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft  Live  Load 
For  Use  in  Snow  Load  Zone  2 

DESIGN  CRITERIA:  Strength — 10  lbs.  per  sq.  fl.  dead  load  plus  30  lbs.  per  sq.  ft.  live  load  determines  fiber  stress. 
Deflection — For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  180. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (last  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  flower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING 

,  "Fb,"  (p 

si) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

6-2 
0.11 

7-1 

0.17 

7-11 
0.24 

8-8 
0.32 

9-4 

0.40 

10-0 
0.49 

10-8 
0.59 

11-3 
0.69 

11-9 
0.80 

12-4 
0.91 

12-9 
1.02 

16.0 

5-4 
0.10 

6-2 
0.15 

6-10 
0.21 

7-6 
0.28 

8-2 
0.35 

8-8 

0.43 

9-3 

0.51 

9-9 
0.60 

10-2 
0.69 

10-8 
0.78 

11-1 
0.88 

■  24.0 

4-4 
0.08 

5-0 
0.12 

5-8 
0.17 

6-2 
0.23 

6-8 
0.29 

7-1 
0.35 

7-6 
0.42 

7-11 
0.49 

8-4 
0.56 

8.8 
0.64 

9-1 

0.72 

2x8 

12.0 

8-1 

0.11 

9-4 
0.17 

10-6 
0.24 

11-6 
0.32 

12-4 
0.40 

13-3 
0.49 

14-1 
0.59 

14-10 
0.69 

15-6 
0.80 

16-3 
0.91 

16-10 
1.02 

16.0 

7-0 
0.10 

8-1 
0.15 

9-1 
0.21 

9-11 
0.28 

10-9 
0.35 

11-6 

0.43 

12-2 
0.51 

12-10 
0.60 

13-6 
0.69 

14-1 
0.78 

14-8 
0.88 

24.0 

5-9 
0.08 

6-8 
0.12 

7-5 
0.17 

8-1 

0.23 

8-9 
0.29 

9-4 
0.35 

9-11 
0.42 

10-6 
0.49 

11-0 
0.56 

11-6 
0.64 

11-11 
0.72 

2x10 

12.0 

10-4 
0.11 

11-11 
0.17 

13-4 
0.24 

14-8 
0.32 

15-10 
0.40 

16-11 
0.49 

17-11 
0.59 

18-11 
0.69 

19-11 
0.80 

20-8 
0.91 

21-6 
1.02 

16.0 

8-11 
0.10 

10-4 
0.15 

11-7 
0.21 

12-8 

0.28 

13-8 
0.35 

14-8 

0.43 

15-6 
0.51 

16-4 
0.60 

17-2 
0.69 

17-11 
0.78 

18-8 

0.88 

24.0 

7-4 
0.08 

8.5 
0.12 

9-5 
0.17 

10-4 
0.23 

11-2 
0.29 

11-11 
0.35 

12-8 
0.42 

13-4 

0.49 

14-0 
0.56 

14-8 
0.64 

15-3 
0.72 

2x  12 

12.0 

12-7 
0.11 

14-6 
0.17 

16-3 
0.24 

17-9 
0.32 

19-3 
0.40 

20-6 
0.49 

21-10 
0.59 

22-11 
0.69 

24-1 
0.80 

25-2 
0.91 

26-2 
1.02 

16.0 

10-11 
0.10 

12-7 
0.15 

14-1 

0.21 

15-5 
0.28 

16-8 
0.35 

17-10 
0.43 

18-10 
0.51 

19-11 
0.60 

20-10 
0.69 

21-10 
0.78 

22-8 
0.88 

24.0 

8-10 
0.08 

10-3 
0.12 

11-6 

0.17 

12-7 
0.23 

13-7 
0.29 

14-6 
0.35 

15-5 
0.42 

16-3 
0.49 

17-0 
0.56 

17-9 
0.64 

18-6 
0.72 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

2x6 

12.0 

13-3 
1.14 

13-9 
1.27 

14-3 
1.40 

14-8 
1.53 

15-1 
1.67 

15-6 
1.81 

15-10 
1.95 

16-3 
2.10 

16-8 

2.25 

17-0 
2.41 

17-5 
2.57 

16.0 

11-6 
0.99 

11-11 
1.10 

12-4 
1.21 

12-8 
1.32 

13-1 

1.44 

13-5 
1.56 

13-9 
1.69 

14-1 
1  82 

14-6 
1.95 

14-9 
2.08 

15-1 
2.22 

24.0 

9-5 

0.81 

9-9 

0.89 

10-0 
0.99 

10-4 
1.08 

10-8 
1.18 

10-11 
1.27 

11-3 
1.38 

11-6 
1.48 

11.9 
1.59 

12-0 
1.70 

12-3 
1.81 

2x8 

12.0 

17-6 
1.14 

18-2 
1.27 

18-9 
1.40 

19-4 
1.53 

19-10 
1.67 

20-5 
1.81 

20-11 
1.95 

21-6 
2.10 

21-11 

2.25 

22-6 
2.41 

22-11 
2.57 

16.0 

15-2 
0.99 

15-7 
1.10 

16-3 
1.21 

16-9 
1.32 

17-2 
1.44 

17-8 
1.56 

18-2 
1.69 

18-7 
1.82 

19-0 
1.95 

19-5 
2.08 

19-10 

2.22 

24.0 

12-4 
0.81 

12-10 
0.89 

13-3 
0.99 

13-8 
1.08 

14-0 
1.18 

14-5 

1.27 

14-9 
1.38 

15-2 
1.48 

15-6 
1.59 

15-10 
1.70 

16-3 
1.81 

2x  10 

12.0 

22-4 
1.14 

23-2 
1.27 

23-11 
1.40 

24-8 
1.53 

25-4 
1.67 

26-0 
1.81 

26-9 
1.95 

27-5 
2.10 

28-0 
2.25 

28-8 
2.41 

29-3 
2.57 

16.0 

19-4 
0.99 

20-0 
1.10 

20-8 
1.21 

21-4 
1.32 

21-11 
1.44 

22-7 
1.56 

32-2 
1.69 

23-9 
1.82 

24-3 
1.95 

24-10 
2.08 

25-4 
2.22 

24.0 

15-9 
0.81 

16-4 
0.89 

16-10 
0.99 

17-5 
1.08 

19-11 
1.18 

18-5 

1.27 

18-10 
1.38 

19-4 

1.48 

19-9 
1.59 

20-3 
1.70 

20-8 
1.81 

2x  12 

12.0 

27-2 
1.14 

28-1 
1.27 

29-1 
1.40 

29-11 
1.53 

30-10 
1.67 

31-8 
1.81 

32-6 
1.95 

33-3 
2.10 

34-1 
2.25 

34-10 
2.41 

35-7 
2.57 

16.0 

23-6 
0.99 

24-4 
1.10 

25-2 
1.21 

25-11 
1.32 

26-8 
1.44 

27-5 
1.56 

28-2 
1.69 

28-10 
1.82 

29-6 
1.95 

30-2 
2.08 

30-10 
2.22 

24.0 

19-3 
0.81 

19-10 
0.89 

20-6 
0.99 

21-2 
1  Oh 

21-9 
1.18 

22-4 
1.27 

22-11 
1.38 

23-6 
1.48 

24-1 
1.59 

24-9 
1.70 

25-2 
1.81 

For  SI: 
NOTE: 


1  inch  =  25.4  mm,  1  pound  per 
The  modulus  of  elasticity,  "E 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  IcN/mZ. 
in  1 .000,000  pounds  per  square  inch  is  shown  below  each  span. 


572 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4h 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Gypsum  Ceiling) 

For  Use  in  Snow  Load  Zone  2 

DESIGN  CRITERIA:  Strength— 10  lbs.  per  sq.  ft  dead  load  plus  30  lbs.  per  sq.  ft.  live  load  determines  fiber  stress. 
Deflection — For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (last  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Ft,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

6-2 
0.15 

7-1 
0.23 

7-11 
0  32 

8-8 
0.43 

9-5 
0.54 

10-0 
0.66 

10-8 
0.78 

11-3 
0.92 

11-9 
1.06 

124 
1.21 

12-10 
1.36 

16.0 

5-4 
0.13 

6-2 
0.20 

6-11 
0.28 

7-6 
0.37 

8-2 
0.47 

8-8 

0.57 

9-3 
0.68 

9-9 
0.80 

10-2 
0.92 

10-8 
1.05 

11-1 
1.18 

24.0 

4-4 
0.11 

5-0 
0.16 

5-7 
0.23 

6-2 
0.30 

6-8 

7-1 

7-6 

7-11 

8-4 

8-8 

9-1 

0.38 

0.46 

0.55 

0.65 

0.75 

0.85 

0.96 

2x8 

12.0 

8-1 
0.15 

9^1 
0.23 

10-6 
0.32 

11-6 
0.43 

12-5 
0.54 

13-3 
0.66 

14-0 
0.78 

14-10 
0.92 

15-6 
1.06 

16-3 
1.21 

16-10 
1.36 

16.0 

7-0 
0.13 

8-1 

0.20 

9-1 

0.28 

9-11 
0.37 

10-9 

0.47 

11-6 
0.57 

12-2 
0.68 

12-10 
0.80 

13-5 
0.92 

14-0 
1.05 

14-7 
1.18 

24.0 

5-9 
0.11 

6-7 
0.16 

7-5 
0.23 

8-1 
0.30 

8-9 
0.38 

9-4 
0.46 

9-11 

0.55 

10-6 
0.65 

11-0 
0.75 

11-6 
0.85 

11-11 
0.96 

2x10 

12.0 

10-4 
0.15 

11-11 
0.23 

13^1 
0.32 

14-8 
0.43 

15-10 
0.54 

16-11 
0.66 

17-11 
0.78 

18-11 
0.92 

19-10 
1.06 

20-8 
1.21 

21-6 
1.36 

16.0 

8-11 
0.13 

10-4 
0.20 

11-7 
0.28 

12-8 
0.37 

13-8 
0.47 

14-8 
0.57 

15-6 
0.68 

16-4 
0.80 

17-2 
0.92 

17-11 
1.05 

18-8 
1.18 

24.0 

7-4 
0.11 

8-5 
0.16 

9-5 

0.23 

10^1 
0.30 

11-2 
0.38 

11-11 
0.46 

12-8 
0.55 

134 
0.65 

14-0 
0.75 

14-8 
0.85 

15-3 
0.96 

2x12 

12.0 

12-7 
0.15 

14-6 
0.23 

16-3 
0.32 

17-9 
0.43 

.  19-3 
0.54 

20-6 
0.66 

21-9 
0.78 

23-0 
0.92 

24-1 
1.06 

25-2 
1.21 

26-2 
1.36 

16.0 

10-11 
0.13 

12-7 
0.20 

14-1 
0.28 

15-5 
0.37 

16-8 
0.47 

17-9 
0.57 

18-10 
0.68 

19-11 
0.80 

20-10 
0.92 

21-9 
1.05 

22-8 
1.18 

24.0 

8-11 
0.11 

10-3 
0.16 

11-6 
0.23 

12-7 
0.30 

13-7 
0.38 

14-6 
0.46 

15-5 

0.55 

16-3 
0.65 

17-0 
0.75 

17-9 
0.85 

18-6 
0.96 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2O00 

2100 

2200 

2400 

2x6 

12.0 

13-3 
1.52 

13-9 
1  69 

14-2 
1.86 

14-8 
2.04 

15-1 
2.22 

15-6 
2.41 

15-11 
2.60 

16-3 
2.80 

16-8 
3.00 

17-5 
3.42 

16.0 

11-6 
1.32 

11-11 
1.46 

12-4 
1.61 

12-8 
1.76 

13-1 

1.92 

13-5 
2.08 

13-9 
2.25 

14-1 
2.42 

14-5 
2.60 

15-1 

2.96 

24.0 

9-5 
1.08 

99 
1.19 

10-0 
1.31 

10-4 
1.44 

10-8 
1.57 

10-11 
1.70 

11-3 
1.84 

11-6 
1.98 

11-9 
2.12 

12-4 
2.41 

2x8 

12.0 

17-6 
1.52 

182 
1.69 

18-9 
1.86 

19-4 
2.04 

19-10 
2.22 

20-5 
2.41 

20-11 
2.60 

21-5 
2.80 

21-11 
3.00 

22-11 
3.42 

16.0 

15-2 
1.32 

15-8 
1.46 

16-3 
1.61 

16-9 
1.76 

17-2 
1.92 

17-8 
2.08 

18-2 

2.25 

18-7 
2.42 

19-0 
2.60 

19-10 
2.96 

24.0 

12-5 
1.08 

12-10 
1.19 

13-3 
1.31 

13-8 
1.44 

14-0 
1.57 

14-5 
1.70 

14-10 
1.84 

15-2 
1.98 

15-6 
2.12 

16-3 
2.41 

2x10 

12.0 

22-4 
1.52 

23-2 
1.69 

23-11 
1.86 

24-7 
2.04 

25-4 
2.22 

26-0 
2.41 

26-8 
2.60 

27-4 
2.80 

28-0 
3.00 

29-3 
3.42 

16.0 

19-4 
1.32 

20-0 
1.46 

20-8 
1.61 

21-4 
1.76 

21-11 
1.92 

22-6 
2.08 

23-2 
2.25 

23-8 
2.42 

24-3 
2.60 

25-4 
2.96 

24.0 

15-10 
1.08 

16-4 
1.19 

16-11 
1.31 

17-5 
1.44 

17-11 
1.57 

18-5 
1.70 

18-11 
1.84 

19-4 
1.98 

19-10 
2.12 

20-8 
2.41 

2x12 

12.0 

27-2 
1.52 

28-2 
1.69 

29-  1 
1.86 

29-11 
2.04 

30-  10 
2.22 

31  -8 
2.41 

32-6 
2.60 

33-3 
2.80 

34-1 
3.00 

35-7 
3.42 

16.0 

23-6 
1.32 

24-4 
1.46 

25-2 
1.61 

25-11 
1.76 

26-8 
1.92 

27-5 
2.08 

28-2 
2.25 

28-10 
2.42 

29-6 
2.60 

30-10 
2.96 

24.0 

19-3 
1.08 

19-11 
1.19 

20-6 
1.31 

21-2 
1.44 

21-9 
1.57 

22-5 
1.70 

23-0 
1.84 

23-6 
1.98 

24-1 
2.12 

25-2 
2.41 

For  SI: 
NOTE: 


1  inch  =  25.4  mm,  1  pound  per 
The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/mZ 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


573 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4i 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 

For  Use  in  Snow  Load  Zone  2 
DESIGN  CRITERIA:     Strength — 10  lbs.  per  sq.  fl.  dead  load  plus  30  lbs.  per  sq.  ft.  live  load  determines  fiber  stress. 
Deflection — For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (last  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING 

,  "FA,"  (f 

si) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

12.0 

6-2 

7-1 

7-11 

8-8 

9-5 

10-0 

10-8 

11-3 

11-9 

12-3 

12-10 

2x6 

0.23 

0.35 

0.49 

0.64 

0.81 

0.99 

1.18 

1.38 

1.59 

1.81 

2.04 

16.0 

5-4 

6-2 

6-10 

7-6 

8-2 

8-8 

9-3 

9-9 

10-2 

10-8 

11-1 

0.20 

0.30 

0.42 

0.55 

0.70 

0.85 

1.02 

1.19 

1.38 

1.57 

1.77 

24.0 

4-4 

5-0 

5-7 

6-2 

6-8 

7-1 

7-6 

7-11 

8-4 

8-8 

9-1 

016 

0.25 

0.34 

0.45 

0.57 

0.70 

0.83 

0.97 

1.12 

1.28 

1  44 

12.0 

8-1 

9-4 

10-6 

11-5 

12-4 

13-3 

14-1 

14-10 

15-6 

16-3 

16-10 

2x8 

0.23 

0.35 

0.49 

0.64 

0.81 

0.99 

1.18 

1.38 

1.59 

1.81 

2.04 

16.0 

7-0 

8-1 

9-1 

9-11 

10-9 

11-6 

12-2 

12-10 

13-5 

14-0 

14-8 

0.20 

0.30 

0.42 

0.55 

0.70 

0.85 

1.02 

1.19 

1.38 

1.57 

1.77 

24.0 

5-9 

6-7 

7-5 

8-1 

8-9 

9-4 

9-11 

10-6 

11-0 

11-6 

11-11 

0.16 

0.25 

0.34 

0.45 

0.57 

0.70 

0.83 

0.97 

1.12 

1.28 

1.44 

12.0 

10-4 

11-11 

13-4 

14-8 

15-10 

16-11 

17-11 

18-11 

19-11 

20-8 

21-6 

2x10 

0.23 

0.35 

0.49 

0.64 

0.81 

0.99 

1.18 

1.38 

1.59 

1.81 

2.04 

16.0 

8-11 

10-4 

11-7 

12-8 

13-8 

14-7 

15-6 

16-4 

17-2 

17-11 

18-8 

0.20 

0.30 

0.42 

0.55 

0.70 

0.85 

1.02 

1.19 

1  38 

1.57 

1.77 

24.0 

7-4 

8-5 

9-5 

10-4 

11-2 

11-11 

12-8 

13-4 

14-0 

14-8 

15-3 

0.16 

0.25 

0.34 

0.45 

0.57 

0.70 

0.83 

0.97 

1.12 

1.28 

1.44 

12.0 

12-7 

14-6 

16-3 

17-10 

19-3 

20-6 

21-9 

23-0 

24-1 

25-2 

26-2 

2x  12 

0.23 

0.35 

0.49 

0.64 

0.81 

0.99 

1.18 

1.38 

1.59 

1.81 

2.04 

16.0 

10-1! 

12-7 

14-1 

15-5 

16-8 

17-9 

18-10 

19-11 

20-10 

21-9 

22-8 

0.20 

0.30 

0.42 

0.55 

0.70 

0.85 

1.02 

1.19 

1.38 

1.57 

1.77 

24.0 

8-11 

10-3 

11-6 

12-7 

13-7 

14-6 

15-5 

16-3 

17-0 

17-9 

18-6 

0.16 

0.25 

0.34 

0.45 

0.57 

0.70 

0.83 

0.97 

1.12 

1.28 

1.44 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

12.0 

13-3 

13-9 

14-3 

14-8 

15-1 

15-6 

15-10 

16-3 

16-8 

17-0 

17-5 

2x6 

2.29 

2.53 

2.79 

3.06 

3.33 

3.61 

3.90 

4.20 

4.50 

4.81 

5.13 

16.0 

11-6 

11-11 

12^» 

12-8 

13-0 

13-5 

13-9 

14-1 

14-5 

14-9 

15-1 

1.98 

2.19 

2.42 

2.65 

2.88 

3.13 

3.38 

3.63 

3.89 

4.16 

4.44 

24.0 

9-4 

9-9 

10-0 

10-4 

10-8 

10-11 

11-3 

11-6 

11-9 

12-0 

12-3 

1.61 

1.79 

1.97 

2.16 

2.35 

2.55 

2.75 

2.96 

3.18 

3.39 

3.62 

12.0 

17-6 

18-1 

18-9 

19-3 

19-10 

20-5 

20-11 

21-5 

21-11 

22-5 

22-11 

2.29 

2.53 

2.79 

3.06 

3.33 

3.61 

3.90 

4.20 

4.50 

4.81 

5.13 

15-2 

15-8 

16-3 

16-9 

17-3 

17-8 

18-1 

18-7 

19-0 

19-5 

19-10 

1.98 

2.19 

2.42 

2.65 

2.88 

3.13 

3.38 

3.63 

3.89 

4.16 

4.44 

24.0 

12-4 

12-10 

13-3 

13-8 

14-0 

14-5 

14-9 

15-2 

15-6 

15-10 

16-3 

1.61 

1.79 

1.97 

2.16 

2.35 

2.55 

2.75 

2.96 

3.18 

3.39 

3.62 

22-4 

23-1 

23-10 

24-7 

25-4 

26-0 

26-9 

27-4 

28-0 

28-8 

29-3 

2x10 

2.29 

2.53 

2.79 

3.06 

3.33 

3.61 

3.90 

4.20 

4.50 

4.81 

5.13 

16.0 

19-4 

20-0 

20-8 

21-4 

21-11 

22-7 

23-2 

23-9 

24-3 

24-10 

25-4 

1.98 

2.19 

2.42 

2.65 

2.88 

3.13 

3.38 

3.63 

3.89 

4.16 

4.44 

15-9 

16-4 

16-10 

17-5 

19-11 

18-5 

18-10 

19-4 

19-10 

20-3 

20-8 

1.61 

1.79 

1.97 

2.16 

2.35 

2.55 

2.75 

2.96 

3.18 

3.39 

3.62 

27-2 

28-1 

29-1 

29-11 

30-10 

31-8 

32-6 

33-3 

34-1 

34-10 

35-7 

2.29 

2.53 

2.79 

3.06 

3.33 

3.61 

3.90 

4.20 

4.50 

4.81 

5.13 

23-6 

24-4 

25-2 

25-11 

26-8 

27-5 

28-2 

28-10 

29-6 

30-2 

30-10 

1.98 

2.19 

2.42 

2.65 

2.88 

3.13 

3.38 

3.63 

3.89 

4.16 

4.44 

24.0 

19-2 
1.61 

19-10 
1.79 

20-6 
1.97 

21-2 
2.16 

21-9 
2.35 

22-4 
2.55 

22-11 

2.75 

23-6 
2  96 

24-1 
3.18 

24-7 
3.39 

25-2 
3  62 

For  Si: 
NOTE: 


1  inch  =  25.4  mm,  1  pound  per 
The  modulus  of  elasticity,  "E," 


square  mch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/mZ. 
in  1,000,000  pounds  per  square  mch  is  shown  below  each  span. 


574 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4J 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft.  Live  Load 

For  Use  in  Snow  Load  Zone  2 

DESIGN  CRITERIA:  Strength — 15  lbs.  per  sq.  ft.  dead  load  plus  30  lbs.  per  sq.  ft  live  load  determines  fiber  stress 
Deflection — For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  180. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacmg  (last  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  flower  figure  m  each  square)  of  lumber  to  be  used. 


RAFTER  SPACING 
AND  SIZE 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING, 

'Fb,"  (psi) 

(inches) 

(inches) 

200 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x4 

12.0 

3-0 
0.05 

3-8 
0.09 

4-3 
0.15 

4-9 
0.20 

5-3 

0.27 

5-8 
0.34 

6-0 
0.41 

6-5 
0.49 

6-9 
0.58 

7-1 
0.67 

7-5 
0.76 

7-8 
0.86 

16.0 

2-7 
0.04 

3-2 
0.08 

3-8 
0.13 

4-1 
0.18 

4-6 
0.23 

4-11 
0.29 

5-3 
0.36 

5-6 
0.43 

5-10 
0.50 

6-1 
0.58 

6-5 
0.66 

6-8 
0.74 

24.0 

2-2 
0.04 

2-7 
0.07 

3-0 
0.10 

3-4 
0.14 

3-8 

0.19 

4-0 
0.24 

4-3 
0.29 

4-6 
0.35 

4-9 
0.41 

5-0 

0.47 

5-3 
0.54 

5-5 
0.61 

2x6 

12.0 

4-9 
0.05 

5-10 
0.09 

6-8 
0.15 

7-6 
0.20 

8-2 
0.27 

8-10 
0.34 

9-6 
0.41 

10-0 
0.49 

10-7 
0.58 

11-1 
0.67 

11-7 
0.76 

12-1 
086 

160 

4-1 
0.04 

5-0 
0.08 

5-10 
0.13 

6-6 
0.18 

7-1 
0.23 

7-8 
0.29 

8-2 
0.36 

8-8 
0.43 

9-2 
0.50 

9-7 
0.58 

10-0 
0.66 

10-5 
0.74 

240 

3-4 
0.04 

4-1 
0.07 

4-9 
0.10 

5-4 
0.14 

5-10 
0.19 

6-3 
0.24 

6-8 

0.29 

7-1 
0.35 

7-6 
0.41 

7-10 
0.47 

8-2 
0.54 

8-6 
0.61 

2x8 

12.0 

6-3 
005 

7-8 
0.09 

8-10 
0.15 

9-10 
0.20 

10-10 
0.27 

11-8 
0.34 

12-6 
0.41 

13-3 
0.49 

13-11 
0.58 

14-8 
0.67 

15-3 
0.76 

15-11 
0.86 

16.0 

5-5 
0.04 

6-7 

0.08 

7-8 
0.13 

8-7 
0.18 

9-4 
0.23 

10-1 
0.29 

10-10 
0.36 

11-6 
0.43 

12-1 

0.50 

12-8 
0.58 

13-3 
0.66 

13-9 
074 

24.0 

4-5 
0.04 

5-5 

0.07 

6-3 
0.10 

7-0 
0.14 

7-8 
0.19 

8-3 

0.24 

8-10 
0.29 

9-4 
0.35 

9-10 
0.41 

10-4 
047 

10-10 
0.54 

11-3 
0.61 

2x10 

120 

8-0 
0.05 

9-9 
0.09 

11-3 
0.15 

12-7 
0.20 

13-9 
0.27 

14-11 
0.34 

15-11 
0.41 

16-11 
0.49 

17-10 
0.58 

18-8 
067 

19-6 
0.76 

20-4 
086 

160 

6-11 
0.04 

8-5 
0.08 

9-9 
0.13 

10-11 
0.18 

11-11 
0.23 

12-il 
0.29 

13-9 
0.36 

14-8 
0.43 

15-5 
0.50 

16-2 
0.58 

16-11 
0.66 

17-7 
074 

24.0 

5-8 

0.04 

6-11 

0.07 

8-0 
0.10 

8-11 

0.14 

9-9 

0.19 

10-6 
0.24 

11-3 
0.29 

11-11 
0.35 

12-7 
0.41 

13-2 
0.47 

13-9 

0.54 

14-4 
061 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2  100 

2200 

2400 

2700 

3000 

2x4 

12.0 

8-0 
0.96 

8-3 
1.06 

8-6 
1.17 

8-9 
1.28 

9-0 
1.39 

9-3 
1.51 

9-6 
1.63 

9-9 
1.76 

10-0 
1.88 

10-5 
2.15 

11-1 

2.56 

16.0 

6-11 
0.83 

7-2 
0.92 

7-5 
1.01 

7-7 
1.11 

7-  10 
1.21 

8-0 
1.31 

8-3 
1.41 

8-5 
1.52 

8-8 
1.63 

9-0 
1.86 

9-7 

2.22 

10-  1 
260 

24.0 

5-8 
0.68 

5-10 
0.75 

6-0 
0.83 

6-3 

0.90 

6-5 
0.99 

6-7 
1.07 

6-9 
1.15 

6-11 
1.24 

7-1 
1.33 

7-5 
1.52 

7-10 
1.81 

8-3 
2  12 

2x6 

12.0 

12-6 
0.96 

13-0 
1.06 

13-5 
1.17 

13-10 
1.28 

14-2 
1.39 

14-7 
1.51 

15-0 
1.63 

15-4 
1.76 

15-8 
1.88 

16-5 
2.15 

17-5 
2.56 

16.0 

10-10 
0.83 

11-3 
0.92 

11-7 
1.01 

11-11 
1.11 

12-4 
1.21 

12-8 
1.31 

13-0 
1.41 

13-3 
1.52 

13-7 
1.63 

14-2 
1.86 

15-1 

2.22 

15-11 
2.60 

24.0 

8-10 
0.68 

9-2 

0.75 

9-6 
0.83 

9-9 

0.90 

10-0 
0.99 

10-4 
1.07 

10-7 
1.15 

10-10 
1.24 

11-1 
1.33 

11-7 
1.52 

12-4 
1.81 

13-0 
2.12 

2x8 

12.0 

16-6 
0.96 

17-1 
1.06 

17-8 
1.17 

18-2 
1.28 

18-9 
1.39 

19-3 
1.51 

19-9 
1.63 

20-3 
1.76 

20-8 
1.88 

21-7 
2.15 

22-11 
2.56 

16.0 

14-4 
0.83 

14-10 
0.92 

15-3 
1.01 

15-9 
1.11 

16-3 
1.21 

16-8 
1.31 

17-1 
1.41 

17-6 
1.52 

17-11 
1.63 

18-9 
1.86 

19-10 
2.22 

20-11 
2.60 

24.0 

11-8 
0.68 

12-1 

0.75 

12-6 
0.83 

12-10 
0.90 

13-3 
0.99 

13-7 
1.07 

13-11 
1.15 

14-4 
1.24 

14-8 
1.33 

15-3 
1.52 

16-3 
1.81 

17-1 
2.12 

2x10 

12.0 

21-1 
0.96 

21-10 
1.06 

22-6 
1.17 

23-3 
1.28 

23-1  i 
1.39 

24-6 
1.51 

25-2 
1.63 

25-10 
1.76 

26-5 
1.88 

27-7 
2.15 

29-3 
2.56 

16.0 

18-3 
0.83 

18-11 
0.92 

19-6 
1.01 

20-1 
1.11 

20-8 
1.21 

21-3 
1.31 

21-10 
1.41 

22-4 
1.52 

22-10 
1.63 

23-11 
1.86 

25-4 
2.22 

26-8 
2.60 

24.0 

14-11 
0.68 

15-5 
0.75 

15-11 
0.83 

16-5 
0.90 

16-11 
0.99 

17-4 
1.07 

17-10 
1.15 

18-3 
1.24 

18-8 
1.33 

19-6 
1.52 

20-8 
1.81 

21-10 
2.12 

For  SI:  1  inch  =  25.4 
NOTE:  The  modulus 


mm,  1  pound  per 
of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  peT  square  inch  is  shown  below  each  span. 


9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


575 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3608.2.4k 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Gypsum  Ceiling) 

For  Use  in  Snow  Load  Zone  2 
DESIGN  CRITERIA:     Strength — 15  lbs.  per  sq.  fl.  dead  load  plus  30  lbs.  per  sq.  ft.  live  load  determines  fiber  stress. 
Deflection — For  30  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (last  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING 

,"F6,"(p 

si) 

( i  nchcs) 

(i  nches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

5-10 
0.13 

6-8 

0  19 

7-6 
0.27 

8-2 
0.36 

8-10 
0.45 

9-6 

0.55 

10-0 
0.66 

10-7 
0.77 

11-1 

0.89 

11-7 
1.01 

12-1 
1.14 

16.0 

5-0 

0.11 

5-10 
0.17 

6-6 
0.24 

7-1 
0.31 

7-8 
0.39 

8-2 
0.48 

8-8 
0.57 

9-2 
0.67 

9-7 
0.77 

10-0 
0.88 

10-5 
0.99 

24.0 

4-1 
0.09 

4-9 

0.14 

5-4 
0.19 

5-10 
0.25 

6-3 

0.32 

6-8 

0.39 

7-1 
0.46 

7-6 
0.54 

7-10 
0.63 

8-2 

0.72 

8-6" 
0.81 

2x8 

12.0 

7-8 
0.13 

8-10 
0.19 

9-10 
0.27 

10-10 
0.36. 

11-8 
0.45 

12-6 
0.55 

13-3 

0.66 

13-11 

0.77 

14-8 
0.89 

15-3 
1.01 

15-11 
1.14 

16.0 

6-7 
0.11 

7-8 
0.17 

8-7 
0.24 

9-4 
0.31 

10-1 
0.39 

10-10 
0.48 

11-6 
0.57 

12-1 
0.67 

12-8 
0.77 

13-3 
0.88 

13-9 
0.99 

24.0 

5-5 
0.09 

6-3 
0.14 

7-0 

0.19 

7-8 
0.25 

8-3 

0.32 

8-10 
0.39 

9-4 
0.46 

9-10 
0.54 

10-4 
0.63 

10-10 
0.72 

11-3 
0.81 

2x10 

12.0 

99 
0.13 

11-3 
0.19 

12-7 
0.27 

13-9 
0.36 

14-11 
0.45 

15-11 

0.55 

16-11 
0.66 

17-10 
0.77 

18-8 
0.89 

19-6 
1.01 

20-4 
1.14 

16.0 

8-5 
0.11 

99 
0.17 

10-11 
0.24 

11-11 
0.31 

12-11 
0.39 

13-9 
0.48 

14-8 
0.57 

15-5 
0.67 

16-2 
0.77 

16-11 
0.88 

17-7 
0.99 

24.0 

6-11 
0.09 

8-0 
0.14 

8-11 
0.19 

99 
0.25 

10-6 
0.32 

11-3 
0.39 

11-11 
0.46 

12-7 
0.54 

13-2 
0.63 

13-9 
0.72 

14-4 
0.81 

2x12" 

12.0 

11-10 
0.13 

13-8 
0.19 

154 
0.27 

16-9 
0.36 

18-1 
0.45 

194 
0.55 

20-6 
0.66 

21-8 
0.77 

22-8 
0.89 

23-9 
1.01 

24-8 
1.14 

16.0 

10-3 
0.11 

11-10 
0.17 

13-3 
0.24 

14-6 
0.31 

15-8 
0.39 

16-9 
0.48 

17-9 
0.57 

18-9 
0.67 

19-8 
0.77 

20-6 
0.88 

21-5 
0.99 

24.0 

8-5 
0.09 

9-8 
0.14 

10-10 
0.19 

11-10 
0.25 

12-10 
0.32 

13-8 
0.39 

14-6 
0.46 

15-4 
0.54 

16-1 
0.63 

16-9 
0.72 

17-5 
0.81 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2400 

2x6 

12.0 

12-6 
1.28 

13-0 
1.41 

13-5 
1.56 

13-10 
1.71 

14-2 
1.86 

14-7 
2.02 

15-0 
2.18 

15-4 

2.34 

15-8 
2.51 

16-5 
2.86 

16.0 

10-10 
1.10 

11-3 
1.22 

11-7 
1.35 

11-11 
1  48 

12-4 
1.61 

12-8 
1.75 

13-0 
1.89 

13-3 
2.03 

13-7 
2.18 

14-2 
2.48 

24.0 

8-10 
0.90 

9-2 
1.00 

9-6 
1.10 

99 
1.21 

10-0 
1.31 

10-4 
1.43 

10-7 
1.54 

10-10 
1.66 

11-1 
1.78 

11-7 
2.02 

2x8 

120 

16-6 
1.28 

17-1 
1.41 

17-8 
1.56 

18-2 
1.71 

18-9 
1.86 

19-3 
2.02 

19-9 
2.18 

20-3 
2.34 

20-8 
2.51 

21-7 
2.86 

16.0 

14-4 
1.10 

14-10 
1.22 

15-3 
1  35 

15-9 
1.48 

16-3 
1.61 

16-8 
1.75 

17-1 
1.89 

17-6 
2.03 

17-11 
2.18 

18-9 
2.48 

24.0 

11-8 
0.90 

12-1 
1.00 

12-6 
1.10 

12-10 
1.21 

13-3 

1.31 

13-7 
1.43 

13-11 
1.54 

14-4 
1.66 

14-8 
1.78 

15-3 

2.02 

2x10 

120 

21-1 
1.28 

21-10 
1.41 

22-6 
1.56 

23-3 
1.71 

23-11 
1.86 

24-6 
2.02 

25-2 
2.18 

25-10 
2.34 

26-5 
2.51 

27-7 
2.86 

16.0 

18-3 
1.10 

18-11 
1.22 

19-6 
1.35 

20-1 
1.48 

20-8 
1.61 

21-3 
1.75 

21-10 
1.89 

22-4 
2.03 

22-10 
2.18 

23-11 
2.48 

24.0 

14-11 
0.90 

15-5 
1.00 

15-11 
1.10 

16-5 
1.21 

16-11 
1.31 

17-4 
1.43 

17-10 
1.54 

18-3 
1.66 

18-8 
1.78 

19-6 
2.02 

2x12 

120 

25-7 
1.28 

26-6 
1.41 

27-5 
1.56 

28-3 
1.71 

29-1 
1.86 

29-10 
2.02 

30-7 
2.18 

31-4 
2.34 

32-1 
2.51 

33-6 
2.86 

16.0 

22-2 
1.10 

23-0 
1.22 

23-9 
1.35 

24-5 
1.48 

25-2 
1.61 

25-10 
1.75 

26-6 
1.89 

27-2 
2.03 

27-10 
2.18 

29-1 
2.48 

24.0 

18-1 
0.90 

18-9 
1.00 

19-4 
1.10 

20-0 
1.21 

20-6 
1.31 

-21-1 
1.43 

21-8 
1.54 

22-2 
1.66 

22-8 
1.78 

23-9 
202 

For  SI:  1  inch  =  25.4  mm,  1  pound 
NOTE:  The  modulus  of  elasticity 


per  square  inch  = 
E,"in  1,000,000 


:  6.895  kPa 
pounds  per 


1  pound  per  square  foot  =  0.0479  kN/m2. 
square  inch  is  shown  oelow  each  span. 


576 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.41 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

30  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Plaster  Ceiling) 

For  Use  in  Snow  Load  Zone  2 

DESIGN  CRITERIA:  Strength — 15  lbs.  per  sq  ft.  dead  load  plus  30  lbs.  per  sq.ft.  live  load  determines  fiber  stress. 

Deflection — For  30  lbs.  per  sq.  ft.  live  load  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  m  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Ft 

."  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

5-10 
0.19 

6-8 
0.29 

7-6 
0.41 

8-2 
0.54 

8-10 
0.68 

9-6 
0.83 

10-0 
0.99 

10-7 
1.15 

11-1 
1.33 

11-7 

1.52 

16.0 

5-0 
0.16 

5-10 

0.25 

6-6 

0.35 

7-1 
0.46 

7-8 
0.59 

8-2 

0.72 

8-8 

0.85 

9-2 
1.00 

9-7 
1.15 

10-0 
1.31 

24.0 

4-1 
0.13 

4-9 
0.21 

5-4 
0.29 

5-10 
0.38 

6-3 

0.48 

6-8 
0.5S 

7-1 
0.70 

7-6 
0.82 

7-10 
0.94 

8-2 
1.07 

2x8 

12.0 

7-8 
0.19 

8-10 
0.29 

9-10 
0.41 

10-10 
0.54 

11-8 
0.68 

12-6 
0.83 

13-3 
0.99 

13-11 
1.15 

14-8 
1.33 

15-3 
1.52 

16.0 

6-7 
0.16 

7-8 
0.25 

8-7 
0.35 

9-4 
0.46 

10-1 
0.59 

10-10 
0.72 

11-6 
0.85 

12-1 
1.00 

12-8 
1.15 

13-3 
1.31 

24.0 

5-5 
0.13 

6-3 
0.21 

7-0 
0.29 

7-8 
0.38 

8-3 

0.48 

8-10 
0.58 

9-4 

0.70 

9-10 
0.82 

10-4 
0.94 

10-10 
1.07 

2x  10 

12.0 

9-9 
0.19 

11-3 
0.29 

12-7 
0.41 

13-9 
0.54 

14-11 
0.68 

15-11 
0.83 

16-11 
0.99 

17-10 
1.15 

18-8 
1.33 

19-6 
1.52 

16.0 

8-5 
0.16 

9-9 
0.25 

10-11 
0.35 

11-11 

046 

12-11 
0.59 

13-9 
0.72 

14-8 
0.85 

15-5 
1.00 

16-2 
1.15 

16-11 
1.31 

24.0 

6-11 
013 

8-0 
0.21 

8-11 
0.29 

99 

0.38 

10-6 
0.48 

11-3 
0.58 

11-11 
0.70 

12-7 
0.82 

13-2 
0.94 

13-9 
1.07 

2x12 

12.0 

11-10 
0.19 

13-8 
0.29 

15-4 
0.41 

16-9 
0.54 

18-i 

0.68 

19-4 
0.83 

20-6 
0.99 

21-8 
1.15 

22-8 
1.33 

23-9 
1.52 

16.0 

10-3 
0.16 

11-10 
0.25 

13-3 
0.35 

14-6 
0.46 

15-8 
0.59 

16-9 
0.72 

17-9 
0.85 

18-9 
1.00 

19-8 
1.15 

20-6 
1.31 

24.0 

8-5 
0.13 

9-8 
0.21 

10-10 
0.29 

11-10 
0.38 

12-10 
0.48 

13-8 
0.58 

14-6 
0.70 

15-4 
0.82 

16-1 
0.94 

16-9 
1.07 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-1 
1.71 

12-6 
1.91 

13-0 
2.12 

13-5 
2.34 

13-10 
2.56 

14-1 
2.79 

14-6 
3.02 

15-0 
3.27 

15-4 
3.51 

15-8 
3.77 

16.0 

10-5 
1.48 

10-10 
1.66 

11-3 
1.84 

11-7 
2.02 

11-11 
2.22 

12-4 
2.41 

12-8 
2.62 

12-11 
2.82 

13-3 
3.04 

13-11 
3.26 

24.0 

8-6 
1.21 

8-10 
1.35 

9-2 
1.50 

9-6 
1.65 

9-9 
1.81 

10-0 
1.97 

10-4 
2.14 

10-7 
2.31 

10-10 
2.48 

11-1 
2.66 

2x8 

12.0 

15-11 
1.71 

16-6 
1.91 

17-1 
2  12 

17-8 
2  34 

18-2 
2.56 

18-8 
2.79 

19-3 
3.02 

19-9 
3.27 

20-3 
3.51 

20-8 
3.77 

16.0 

13-9 
1.48 

14-4 
1.66 

14-10 
1.84 

15-3 
2.02 

15-9 
2.22 

16-3 
2.41 

16-8 
2.62 

17-1 
2.83 

17-6 
3.04 

17-11 
3.26 

24.0 

11-3 
1.21 

11-8 
1.35 

12-1 
1.50 

12-6 
165 

12-10 
1.81 

13-3 
1.97 

13-7 
2.14 

13-11 
2.31 

14-4 
2.48 

14-7 
2.66 

2x10 

12.0 

20-4 
1.71 

21-1 
1.91 

21-10 
2.12 

22-6 
2.34 

23-3 
2.56 

23-10 
2.79 

24-6 
3.02 

25-2 
3.27 

25-10 
3.51 

26-5 
3.77 

16.0 

17-7 
1.48 

18-3 
1.66 

18-11 
1.84 

19-6 
2.02 

20-1 
2.22 

20-8 
2.41 

21-3 
2.62 

21-9 
2.83 

22-4 
3.04 

22-10 
3.26 

24.0 

14-4 
1.21 

14-11 
1.35 

15-5 
1.50 

15-11 
1.65 

16-5 

1.81 

16-11 
1.97 

17-4 
2.14 

17-10 
2.3! 

18-3 
2.48 

18-8 
2.66 

2x12 

12.0 

24-8 
1.71 

25-7 
1.91 

26-6 
2.12 

27-5 
2.34 

28-3 
2.56 

29-1 
2.79 

29-10 
3.02 

30-7 
3.27 

21-4 
3.51 

32-1 
3.77 

16.0 

21-5 
1.48 

22-2 
1.66 

23-0 
1.84 

23-9 
2.02 

24-5 
2.22 

25-2 
2.41 

25-10 
2.62 

26-6 
2.83 

27-2 
3.04 

27-10 
3.26 

24.0 

17-5 
1.21 

18-1 
1.35 

18-9 
1.50 

19-4 
1.65 

20-0 
1.81 

20-6 
1.97 

21-1 
2.14 

21-8 
2.31 

22-2 
2.48 

22-8 
2.66 

For  SI:  1  inch  =  25,4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


577 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4m 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft.  Live  Load 
For  Use  in  Snow  Load  Zone  3 

DESIGN  CRITERIA:  Strength-35  lbs.  per  sq.  ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  1 80. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fl 

"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

5-10 
.11 

6-8 
.17 

7-6 

.24 

8-2 
.31 

8-10 
.39 

9-6 
.48 

10-0 
.58 

10-7 
.67 

11-1 
.78 

11-7 
.89 

16.0 

5-0 
.10 

5-10 
.15 

6-6 
.21 

7-1 

.27 

7-8 
.34 

8-2 

42 

8-8 

.50 

9-2 
.58 

9-7 
.67 

10-0 

.77 

24.0 

4-1 
.08 

4-9 
.12 

5-4 

.17 

5-10 
.22 

6-3 
.28 

6-8 

.34 

7-1 
.41 

7-6 
.48 

7-10 
.55 

8-2 
.63 

2x8 

12.0 

7-8 
11 

8-10 
.17 

9-10 
.24 

10-10 
.31 

11-8 
.39 

12-6 
.48 

13-3 
.58 

13-11 

.67 

14-8 

.78 

15-3 
.89 

16.0 

6-7 

.10 

7-8 
.15 

8-7 
.21 

9-4 
.27 

10-1 

.34 

10-10 
.42 

11-6 
.50 

12-1 
58 

12-8 

.67 

13-3 

.77 

24.0 

5-5 
.08 

6-3 
.12 

7-0 

17 

7-8 
.22 

8-3 
.28 

8-10 
.34 

9-4 

.41 

9-10 
.48 

10-4 
.55 

10-10 
.63 

2x10 

12.0 

9-9 
.11 

11-3 

.17 

12-7 
.24 

13-9 

.31 

14-11 
.39 

15-11 
.48 

16-11 
.58 

17-10 
.67 

18-8 
.78 

19-6 
.89 

16.0 

8-5 

.10 

9-9 

15 

10-11 
.21 

11-11 
.27 

12-11 
.34 

13-9 
.42 

14-8 
.50 

15-5 
.58 

16-2 

.67 

16-11 
.77 

24.0 

6-11 
.08 

8-0 
.12 

8-11 
.17 

9-9 

.22 

10-6 
.28 

11-3 
.34 

11-11 

41 

12-7 
.48 

13-2 
.55 

13-9 
.63 

2x  12 

12.0 

11-10 
0.11 

13-8 
0.17 

15-4 
0.24 

16-9 
0.31 

18-1 
0.39 

19-4 
0.48 

20-6 
0.58 

21-8 
0.67 

22-9 
0.78 

23-9 
0.89 

16.0 

10-3 
0.10 

11-10 
0.15 

13-3 
0.21 

14-6 
0.27 

15-8 
0.34 

16-9 

0.42 

17-8 
0.58 

18-9 
0.58 

19-8 

0.67 

20-6 
0.77 

24.0 

8-4 
0.08 

9-8 
0.12 

10-10 
0.17 

11.10 
0.22 

12-10 
0.28 

13-8 

0.34 

14-6 
0.41 

15-4 
0  48 

16-1 
0.55 

16-9 
0.63 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-1 
1.00 

12-6 
1.12 

13-0 
1.24 

13-5 
1.36 

13-10 
1.49 

14-2 
1.63 

14-7 
1.76 

15-0 
1.91 

15-4 
2.05 

15-9 

2.2 

16.0 

10-5 
.86 

10-10 
.97 

11-3 
1.07 

11-7 
1.18 

11-11 
1.29 

12-4 
1  41 

12-8 
1.53 

13-0 
1.65 

13-3 
1.78 

13-7 
1.90 

24.0 

8-6 

.71 

8-10 
.79 

9-2 
.88 

9-6 
.96 

9-9 
1.06 

10-0 
1.15 

10-4 
1.25 

10-7 
1.35 

10-10 
1.45 

11-1 
1.55 

2x8 

12.0 

15-11 
1.00 

16-6 

1.12 

17-1 
1.24 

17-8 
1.36 

18-2 
1.49 

18-9 
1.63 

19-3 
1.76 

19-9 
1.91 

20-3 
2.05 

20-8 
2.20 

16.0 

13-9 
.86 

14-4 
.97 

14-10 
1.07 

15-3 
1.18 

15-9 
1.29 

16-3 
1.41 

16-8 
1.53 

17-1 
1.65 

17-6 
1.78 

17-11 
1.90 

24.0 

11-3 
.71 

11-8 
.79 

12-1 
.88 

12-6 
.96 

12-10 
1.06 

13-3 
1.15 

13-7 
1.25 

13-11 
1.35 

14-4 
1.45 

14-8 
1.55 

2x10 

12.0 

20-4 
1.00 

21-1 
1.12 

21-10 
1.24 

22-6 
1.36 

23-3 
1.49 

23-11 
1.63    . 

24-6 
1.76 

25-2 
1.91 

25-10 
2.05 

26-5 
2.20 

160 

17-7 
.86 

18-3 
.97 

18-11 
1.07 

19-6 
1.18 

20-1 
1.29 

20-8 
1.41 

21-3 
1.53 

21-10 
1.65 

22-4 
1.78 

22-10 
1.90 

24.0 

14-4 
.71 

14-11 
79 

15-5 
.88 

15-11 
.96 

16-5 
1.06 

16-11 

1.15 

17-4 
1.25 

17-10 
1.35 

18-3 
1.45 

18-8 
1.55 

2x12 

12.0 

24-8 
1.00 

25-7 
22-2 

26-6 
1.24 

27-4 
1.36 

28-3 
1.49 

29-1 
1.63 

29-10 
1.76 

30-7 
1.91 

31-4 
2.05 

21-1 
2.20 

16.0 

21-4 
0.86 

0.97 
18-1 

22-11 
1.07 

23-9 
1.18 

24-5 
1.29 

25-2 
1.41 

25-10 
1.53 

26-6 
1.65 

27-2 
1.78 

27-10 
1.90 

24.0 

17-5 
0.71 

0.79 
0.79 

18-9 

0.87 

19-4 
0.96 

19-11 
1.06 

20-6 
1.15 

21-2 
1.25 

21-8 
1.35 

22.2 
1.45 

22-9 
1.55 

For  SI:  1  inch  =  25,4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


578 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  36082.4n 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Gypsum  Wallboard  Ceiling) 
For  Use  in  Snow  Load  Zone  3 

DESIGN  CRITERIA:  Strength-35  lbs.  per  sq.  ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACLNG 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fl 

."  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

5-10 
0.15 

6-8 

0.23 

7-6 
.32 

8-2 
.42 

8-10 

53 

9-6 
.64 

10-0 

.77 

10-7 
.90 

11-1 
1.04 

11-7 
1.18 

16.0 

5-0 

.13 

5-10 
.20 

6-6 
.27 

7-1 
.36 

7-8 
.46 

8-2 

.56 

8-8 

.66 

9-2 

.78 

9-7 
.90 

10-0 
1.02 

24.0 

4-1 

.10 

4-9 
.16 

5-4 

5-10 
.30 

6-3 
.37 

6-8 

.45 

7-1 
.54 

7-6 
64 

7-10 
.73 

8-2 
.83 

2x8 

12.0 

7-8 
15 

8-10 

9-10 

.32 

10-10 
.42 

11-8 

.53 

12-6 
.64 

13-3 

77 

13-11 

.90 

14-8 
1.04 

15-3 
1.18 

16.0 

6-7 
.13 

7-8 
.20 

8-7 
.27 

9-4 

36 

10-1 
.46 

10-10 
.56 

11-6 
.66 

12-1 
78 

12-8 
.90 

13-3 
1.02 

24.0 

5-5 
.10 

6-3 
.16 

7-0 

7-8 
30 

8-3 

8-10 

45 

9-4 

.54 

9-10 
.64 

10-4 

.73 

10-10 
.83 

2x  10 

12.0 

9-9 

.15 

11-3 

.23 

12-7 

.32 

13-9 
.42 

14-11 
.53 

15-11 
.64 

16-11 

.77 

17-10 
.90 

18-8 
1.04 

19-6 
1.18 

16.0 

8-5 

.13 

9-9 

.20 

10-11 

.27 

11-11 
.36 

12-11 
.46 

13-9 
.56 

14-8 
.66 

15-5 
.78 

16-2 
.90 

16-11 
1.02 

24.0 

6-11 
.10 

8-0 
.16 

8-11 

9-9 
.20 

10-6 

11-3 
.45 

11-11 
.54 

12-7 
.64 

13-2 

.73 

13-9 
.83 

2x  12 

12.0 

11-10 

.15 

13-8 

.23 

15-4 
.32 

16-9 
.42 

18-1 

.53 

19-4 
.64 

20-6 

77 

21-8 
.90 

22-8 
1.04 

23-9 
1.18 

16.0 

10-3 
.13 

11-10 

20 

13-3 

.27 

14-6 
.36 

15-8 
.46 

16-9 

.56 

17-9 
.66 

18-9 
.78 

19-8 

.9" 

20-6 
1.02 

24.0 

8-5 
.10 

9-8 

16 

10-10 

.22 

11-10 

30 

12-10 
.37 

13-8 

.45 

14-6 
.54 

15-4 
.64 

16-1 

73 

16-9 
.83 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-1 
1.33 

12-6 
1  49 

13-0 
1.65 

13-5 

1.82 

13-10 
1.99 

14-2 

2.17 

14-7 
2.35 

15-0 

2.54 

15-4 
2^4 

15-8 
2.93 

16.0 

10-5 

r.  is 

10-10 
1.29 

11-3 

1.43 

11-7 
1.57 

11-11 

1.72 

12-4 
1.88 

12-8 

2.04 

13-0 
2.20 

13-3 

2.37 

13-7 
2.54 

24.0 

8-6 

.94 

8-10 
1  05 

9-2 

1.17 

9-6 
1.29 

9-9 
1.41 

10-0 
1.53 

10-4 
1.66 

10-7 
1.80 

10-10 
1.93 

11-1 
2.07 

2x8 

12.0 

15-11 
1.33 

16-6 

1.49 

17-1 
1.65 

17-8 
1.82 

18-2 
1.99 

18-9 

2.17 

19-3 
2.35 

19-9 
2.54 

20-3 
2.74 

20-8 
2.93 

16.0 

13-9 
1.15 

14-4 
1.29 

14-10 

1.43 

15-3 
1.57 

15-9 
172 

16-3 
1.88 

16-8 
2.04 

17-1 
2.20 

17-6 
2.37 

17-11 
2.54 

24.0 

11-3 
.94 

11-8 
1.05 

12-1 
1.17 

12-6 
1.29 

12-10 
1.41 

13-3 
1.53 

13-7 
1.66 

13-11 
1.80 

14-4 
1.93 

14-7 

2.07 

2x  10 

12.0 

20-4 
1.33 

21-1 
1.49 

21-10 
1.65 

22-6 
1.82 

23-3 
1.99 

23-11 
2.17 

24-6 
2.35 

25-2 
2.54 

25-10 
2.74 

26-5 
2.93 

16.0 

17-7 
1.15 

18-3 
1.29 

18-11 

1.43 

19-6 
1.57 

20-1 

172 

20-8 
1.88 

21-3 
2.04 

21-10 
2.20 

22-4 
2.37 

22-10 
2.54 

24.0 

14-4 
.94 

14-11 
1.05 

15-5 
1.17 

15-11 
1.29 

16-5 
1.41 

16-11 
1.53 

17-4 
1.66 

17-10 
1.80 

18-3 
1.93 

18-8 
2.07 

2x  12 

12.0 

24-8 
1.33 

25-7 
1.49 

26-6 
1.65 

27-4 
1.82 

28-3 
1.99 

29-0 
2.17 

29-10 
2.35 

30-7 
2.54 

31-4 
2.74 

32-1 
2.93 

16.0 

21-5 
1.15 

22-2 
1.29 

23-0 
1.43 

23-9 
1.57 

24-5 
1  72 

25-2 
1.88 

25-10 
2.04 

26-5 
2.20 

27-2 
2.37 

27-10 
2.54 

24.0 

17-5 
94 

18-1 
1.05 

18-9 
1.17 

19-4 
1.29 

20-0 
1.41 

20-6 
1.53 

21-1 
1.66 

21-8 
1.80 

22-2 
1.93 

22-8 
2.07 

For  SI:  1  inch  =  25.4  mm.  I  pound  per 
NOTE:  The  modulus  of  elasticity.  "E." 


square  inch  =  6.895  kPa.  1  pound  per 
in  1 .000,000  pounds  per  square  inch  i; 


;quare  foe 
shown  bi 


t  =  0.0479 
:low  each  s 


kN/m2. 
pan. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


579 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4o 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 
For  Use  in  Snow  Load  Zone  3 

DESIGN  CRITERIA:  Strength-35  lbs.  per  sq.  ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fl 

."  (P»0 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

UOO 

1200 

2x6 

12.0 

5-10 
.22 

6-8 
.34 

7-6 
.48 

8-2 
.63 

8-10 
.79 

9-6 
.96 

10-0 
1.15 

10-7 
1.35 

11-1 
1.55 

11-7 
1.77 

16.0 

5-0 
.19 

5-10 
.30 

6-6 
.41 

7-1 
.54 

7-8 
.68 

8-2 
.83 

8-8 
1.00 

9-2 
1.17 

9-7 
1.35 

10-0 
1.53 

24.0 

4-1 
.16 

4-9 
.24 

5-4 
.34 

5-10 
.44 

6-3 
.56 

6-8 
.68 

7-1 
.81 

7-6 
.95 

7-10 
1.10 

8-2 
1.25 

2x8 

12.0 

7-8 
.22 

8-10 
.34 

9-10 
.48 

10-10 
.63 

11-8 
.79 

12-6 
.96 

13-3 
1.15 

13-11 
1.35 

14-8 
1.55 

15-3 

1.77 

16.0 

6-7 
.19 

7-8 
.30 

8-7 
.41 

9-4 
.54 

10-1 
.68 

10-10 
.83 

11-6 

1.00 

12-1 
1.17 

12-8 
1.35 

13-3 
1.53 

24.0 

5-5 
.16 

6-3 

.24 

7-0 
.34 

7-8 

.44 

8-3 
.56 

8-10 
.68 

9-4 
.81 

9-10 
.95 

10-4 
1.10 

10-10 
1.25 

2x10 

12.0 

9-9 

.22 

11-3 

.34 

12-7 
.48 

13-9 
.63 

14-11 
.79 

15-11 
.96 

16-11 
1.15 

17-10 
1.35 

18-8 
1.55 

19-6 

1.77 

16.0 

8-5 
.19 

9-9 
.30 

10-11 
.41 

11-11 
.54 

12-11 
.68 

13-9 
.83 

14-8 
1.00 

15-5 
1.17 

16-2 
1.35 

16-11 
1.53 

24.0 

6-11 
.16 

8-0 
.24 

8-11 
.34 

9-9 
.44 

10-6 
.56 

11-3 
.68 

11-11 
.81 

12-7 
.95 

13-2 
1.10 

13-9 
1.25 

2x12 

12.0 

11-10 
.22 

13-8 

.34 

15-4 
.48 

16-9 
.63 

18-1 

.79 

19-4 
.96 

20-6 
1.15 

21-8 
1.35 

22-8 
1.55 

23-9 

1.77 

16.0 

10-3 
.19 

11-10 
.30 

13-3 
.41 

14-6 
.54 

15-8 
.68 

16-9 

.83 

17-9 
1.00 

18-9 
1.17 

19-8 
1.35 

20-6 
1.53 

24.0 

8-5 
.16 

9-8 

.24 

10-10 
.34 

11-10 
.44 

12-10 
.56 

13-8 
.68 

14-6 
.81 

15-4 
.95 

16-1 
1.10 

16-9 
1.25 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

12-1 
2.00 

12-6 
2.23 

13-0 
2.47 

13-4 
2.73 

13-10 
2.99 

14-2 
3.26 

14-7 
3.53 

14-11 
3.81 

15-4 
4.10 

15-8 
4.40 

16.0 

10-5 
1.73 

10-10 
1.93 

11-3 

2.14 

11-7 
2.36 

11-11 
2.59 

12-4 

2.82 

12-7 
3.06 

12-11 
3.30 

13-3 
3.55 

13-7 
3.81 

24.0 

8-6 
1.41 

8-10 
1.58 

9-2 
1.75 

9-6 
1.93 

9-9 
2.11 

10-0 
2.30 

10-4 
2.49 

10-7 
2.69 

10-10 
2.90 

11-1 
3.11 

2x8 

12.0 

15-11 
2.00 

16-6 
2.23 

17-1 

2.47 

17-8 
2.73 

18-2 
2.99 

18-9 
3.26 

19-3 
3.53 

19-9 
3.81 

20-3 
4.10 

20-8 
4.40 

16.0 

13-9 

1.73 

14-4 
1.93 

14-10 
2.14 

15-3 
2.36 

15-9 
2.59 

16-3 
2.82 

16-8 
3.06 

17-1 
3.30 

17-6 
3.55 

17-11 
3.81 

24.0 

11-3 
1.41 

11-8 
1.58 

12-1 
1.75 

12-6 
1.93 

12-10 
2.11 

13-3 
2.30 

13-7 
2.49 

13-11 
2.69 

14-4 
2.90 

14-8 
3.11 

2x  10 

12.0 

20-4 
2.00 

21-1 
2.23 

21-10 
2.47 

22-6 
2.73 

23-3 
2.99 

23-10 
3.26 

24-6 
3.53 

2S-2 
3.81 

25-9 
4.10 

26-5 
4.40 

16.0 

17-7 
1.73 

18-3 
1.93 

18-11 
2.14 

19-6 
2.36 

20-1 
2.59 

20-8 
2.82 

21-3 
3.06 

21-9 
3.30 

22-4 
3.55 

22-10 
3.81 

24.0 

14-4 
1.41 

14-11 
1.58 

15-5 

1.75 

15-11 
1.93 

16-5 
2.11 

16-11 
2.30 

17-4 
2.49 

17-9 
2.69 

18-3 
2.90 

18-8 
3.11 

2x  12 

12.0 

24-8 
2.00 

25-7 
2.23 

26-6 
2.47 

27-4 
2.73 

28-3 
2.99 

29-0 
3.26 

29-10 
3.53 

30-7 
3.81 

31-4 
4.10 

21-1 
4.40 

16.0 

21-5 
1.73 

22-2 
1.93 

23-0 
2.14 

23-9 
2.36 

24-5 
2.59 

25-2 
2.82 

25-10 
3.06 

26-6 
3.30 

27-2 
3.55 

27-10 
3.81 

24.0 

17-5 
1  41 

18-1 
1.58 

18-9 
1.75 

19-4 
193 

20-0 
2.11 

20-6 
2.30 

21-1 
2.49 

21-8 
269 

22-2 
2.90 

22-9 
3.11 

For  SI:  1  inch  =  25.4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


580 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  36082.4p 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft.  Live  Load 

For  Use  in  Snow  Load  Zone  3 
DESIGN  CRITERIA:  Strength-35  lbs.  per  sq.  ft.  live  load  plus  15  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  180. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  ("top  row )  and  modulus  of  elasticity  i  lower  figure  in  each  square)  of  lumber  to  be  used 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Ft 

."  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

5-6 
.09 

6-4 

.15 

7-1 
.20 

7-9 
.27 

8-5 
.34 

9-0 
.41 

9-6 

.49 

10-0 
.58 

10-6 
.66 

11-0 

.76 

16.0 

4-9 
.08 

5-6 
.13 

6-2 
.18 

6-9 

7-3 
.29 

7-9 

.36 

8-3 
.43 

8-8 

.50 

9-1 

.57 

9-6 

.65 

24.0 

3-11 
.07 

4-6 
.10 

5-0 
.14 

5-6 
.19 

5-11 
.24 

6-4 
.29 

6-9 

.35 

7-1 

.41 

7-5    " 
.47 

_  7^9~~ 
.53 

2x8 

12.0 

7-3 
.09 

8-4 
.15 

9-4 
.20 

10-3 
.27 

11-1 
.34 

11-10 
.41 

12-7 
.49 

13-3 
.58 

13-11 
.66 

14-6 
.76 

16.0 

6-3 
.08 

7-3 
.13 

8-1 
.18 

8-11 
.23 

9-7 
.29 

10-3 
.36 

10-10 

.43 

11-6 
.50 

12-0 
.57 

12-7 
.65 

24.0 

5-2 
07 

5-11 
.10 

6-7 
.14 

7-3 
.19 

7-10 
.24 

8-4 

.29 

8-1 
.35 

9-4 

.41 

9-10 

.47 

10-3 
.53 

2x  10 

12.0 

9-3 
.09 

10-8 
.15 

11-11 
.20 

13-1 

.27 

14-2 
.34 

15-1 
.41 

16-0 
.49 

16-11 
.58 

17-9 
.66 

18-6 

.76 

16.0 

8-0 
.08 

9-3 

.13 

10-4 
.18 

11-4 

.23 

12-3 
.29 

13-1 
36 

13-10 
.43 

14-8 
.50 

15-4 

57 

16-0 
.65 

24.0 

6-6 
.07 

7-7 
.10 

8-5 
.14 

9-3 
.19 

10-0 
.24 

10-8 
.29 

11-4 
.35 

11-11 

.41 

12-6 

.47 

13-1 
.53 

2x  12 

12.0 

11-3 
0.09 

13-0 
0.15 

14-6 
0.20 

15-11 
0.27 

17-2 
0.34 

18-4 
0.41 

19-6 
0.49 

20.6 
0.58 

21-6 
0.66 

22-6 
0.76 

16.0 

9-9 
0.08 

11-3 
0.13 

12-7 
0.18 

13-9 
0.23 

14-10 
0.29 

15-11 
0.36 

16-10 
0.43 

17-9 
0.50 

18-8 
0.57 

19-6 
0.65 

24.0 

8-0 
0.07 

9-2 
0.10 

10-3 
0.14 

11-3 
0.19 

12-2 
0.24 

13-0 
0.29 

13-8 
0.35 

14-6 
0.41 

15-3 
0.47 

15-11 
0.53 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

11-5 
.85 

11-11 

.95 

12-4 
1.06 

12-8 
1.16 

13-1 
1.27 

13-6 
1.39 

13-10 
1.51 

14-2 
1.63 

14-7 
1.75 

14-10 
1.88 

16.0 

9-11 
'74 

10-3 
.83 

10-8 
.91 

11-0 
1.01 

11-4 
1.10 

11-8 
1.20 

12-0 
1.30 

12-4 
1.41 

12-7 
1.52 

12-10 
1.62 

24  0 

8-1 
.60 

8-5 

.67 

8-8 

.75 

9-0 
.82 

9-3 
.90 

9-6 
.98 

9-9 
1.07 

10-0 
1.15 

10-3 
1.24 

10-6 
1.33 

2x8 

12.0 

15-1 
.85 

15-8 
.95 

16-3 
1.06 

16-9 
1.16 

17-3 
1.27 

17-9 
1.39 

18-3 
1.51 

18-9 
1.63 

19-2 
1.75 

19-7 
1.88 

16.0 

13-1 

.74 

13-7 
83 

14-0 
.91 

14-6 
1.01 

14-11 
1.10 

15-5 
1.20 

15-10 
1.30 

16-3 

1.41 

16-7 
1.52 

17-0 
1.62 

24.0 

10-8 
.60 

11-1 
.67 

11-6 

.75 

11-10 
.82 

12-2 
.90 

12-7 
.98 

12-11 
1.07 

13-3 
1.15 

13-7 
1.24 

13-10 
1.33 

2x  10 

12.0 

19-3 
.85 

20-0 
.95 

20-8 
1.06 

21-4 
1.16 

22-0 
1.27 

22-8 
1.39 

23-3 
1.51 

23-11 
1.63 

24-6 
1.75 

25-0 
1.88 

16.0 

16-8 

.74 

17-4 
.83 

17-11 
.91 

18-6 
1.01 

19-1 
1.10 

19-7 
1.20 

20-2 
1.30 

20-8 
1.41 

21-2 
1.52 

21-8 
1.62 

24.0 

13-7 
.60 

14-2 
.67 

14-8 
.75 

15-1 
.82 

15-7 
.90 

16-0 
.98 

16-6 
1.07 

16-11 
1.15 

17-4 
1.24 

17-9 
1.33 

2x  12 

12.0 

23-5 
0.85 

24-3 
0.95 

25-2 
1.06 

21-4 
1.16 

26-9 
1.27 

27-6 
1.39 

28-4 
1.51 

29-0 
1.63 

29-9 
1.75 

30-5 
1.88 

16.0 

20-3 
0.74 

21-0 
0.82 

21-9 
0.91 

22-6 
1.01 

23-2 
1.10 

23-10 
1.20 

24-6 
1.30 

25-2 
1.41 

25-9 
1.51 

26-4 
1.62 

24.0 

16-6 
0.60 

17-2 
0.67 

17-9 
0.75 

18-4 
0.82 

18-11 
0.90 

19-6 
0.98 

20-0 
1.07 

20-6 
1.15 

21-0 

1.24 

21-7 
1.33 

For  SI:  1  inch 
NOTE:  The  n 

=  25,4  mm,  1 
odulusof  clas 

pound  per 
ticity,  "E.' 

square  in 
in  1 ,000.( 

:h  =  6.895 
)00  pound 

kPa,  1  po 
s  per  squa 

und  per  sc 
e  inch  is  s 

uare  foot  = 
nown  beli 

=  0.0479  1 
w  each  sr 

N/m2. 
an. 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


581 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3608.2.4q 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Gypsum  Wallboard  Ceiling) 
For  Use  in  Snow  Load  Zone  3 
DESIGN  CRITERIA:  Strength-35  lbs.  per  sq.ft.  live  load  plus  1 5  lbs.  per  sq.ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

12.0 

5-6 

6-4 

7-1 

7-9 

8-5 

9-0 

9-6 

10-0 

10-6 

11-0 

2x6 

.13 

.19 

.27 

.36 

.45 

.55 

.65 

.77 

.88 

1.01 

16.0 

4-9 

5-6 

6-2 

6-9 

7-3 

7-9 

8-3 

8-8 

9-1 

9-6 

.11 

.17 

.23 

.31 

.39 

.48 

.57 

.66 

.77 

.87 

24.0 

3-11 

4-6 

5-0 

5-6 

5-11 

6-4 

6-9 

7-1 

7-5 

7-9 

.09 

.14 

.19 

.25 

.32 

.39 

.46 

.54 

.63 

.71 

12.0 

7-3 

8-4 

9-4 

10-3 

11-1 

11-10 

12-7 

13-3 

13-11 

14-6 

2x8 

.13 

.19 

.27 

.36 

.45 

.55 

.65 

.77 

.88 

1.01 

16.0 

6-3 

7-3 

8-1 

8-11 

9-7 

10-3 

10-10 

11-6 

12-0 

12-7 

.11 

.17 

.23 

.31 

.39 

.48 

.57 

.66 

.77 

.87 

24.0 

5-2 

5-11 

6-7 

7-3 

7-10 

8-4 

8-11 

9-4 

9-10 

10-3 

.09 

.14 

.19 

.25 

.32 

.39 

.46 

.54 

.63 

.71 

12.0 

9-3 

10-8 

11-11 

13-1 

14-2 

15-1 

16-0 

16-11 

17-9 

18-6 

2x10 

.13 

.19 

.27 

.36 

.45 

.55 

.65 

.77 

.88 

1.01 

16.0 

8-0 

9-3 

10-4 

11-4 

12-3 

13-1 

13-10 

14-8 

15-4 

16-0 

.11 

.17 

.23 

.31 

.39 

.48 

.57 

.66 

.77 

.87 

24.0 

6-6 

7-7 

8-5 

9-3 

10-0 

10-8 

11-4 

11-11 

12-6 

13-1 

.09 

.14 

.19 

.25 

.32 

.39 

.46 

.54 

.63 

.71 

12.0 

11-3 

13-0 

14-6 

15-11 

17-2 

18-4 

19-6 

20-6 

21-7 

22-6 

2x12 

.13 

.19 

.23 

.36 

.45 

.55 

.65 

.77 

.88 

1.01 

16.0 

9-9 

11-3 

12-7 

13-9 

14-11 

15-11 

16-10 

17-9 

18-8 

19-6 

.11 

.17 

.23 

.31 

.39 

.48 

.57 

.66 

.77 

.87 

24.0 

7-11 

9-2 

10-3 

11-3 

12-2 

13-0 

13-9 

14-6 

15-3 

15-11 

.09 

.14 

.19 

.25 

.32 

.39 

.46 

.54 

.63 

.71 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

12.0 

11-5 

11-11 

12-4 

12-8 

13-1 

13-6 

13-10 

14-2 

14-7 

14-10 

2x6 

1.14 

1.27 

1.41 

1.55 

1.70 

1.85 

2.01 

2.17 

2.33 

2.50 

16.0 

9-11 
.98 

10-3 
1.10 

10-8 

1.22 

11-0 
1.34 

11-4 
1.47 

11-8 
1.60 

12-0 
1.74 

12-4 
1.88 

12-7 
2.02 

12-10 
2.16 

24.0 

8-1 

8-5 

8-8 

9-0 

9-3 

9-6 

9-9 

10-0 

10-3 

10-6 

.80 

.90 

1.00 

1.10 

1.20 

1.31 

1.42 

1.53 

1.65 

1.77 

12.0 

15-1 

15-8 

16-3 

16-9 

17-3 

17-9 

18-3 

18-9 

19-2 

19-7 

2x8 

1.14 

1.27 

1.41 

1.55 

1.70 

1.85 

2.01 

2.17 

2.33 

2.50 

16.0 

13-1 
.98 

13-7 
1.10 

14-0 
1.22 

14-6 
1.34 

14-11 
1.47 

15-5 
1.60 

15-10 
1.74 

16-3 
1.88 

16-7 
2.02 

17-0 
2.17 

10-8 

11-1 

11-6 

11-10 

12-2 

12-7 

12-11 

13-3 

13-7 

13-10 

.80 

.90 

1.00 

1.10 

1.20 

1.31 

1.42 

1.53 

1.65 

1.77 

19-3 

20-0 

20-8 

21-4 

22-8 

22-8 

23-3 

23-11 

24-6 

25-0 

2x  10 

1.14 

1.27 

1.41 

1.55 

1.70 

1.85 

2.01 

2.17 

2.33 

2.50 

16-8 

17-4 

17-11 

18-6 

19-1 

19-7 

20-2 

20-8 

21-2 

21-8 

.98 

1.10 

1.22 

1.34 

1.47 

1.60 

1.74 

1.88 

2.02 

2.16 

13-7 

14-2 

14-8 

15-1 

15-7 

16-0 

16-6 

16-11 

17-4 

17-9 

.80 

.90 

1.00 

1.10 

1.20 

1.31 

1.42 

1.53 

1.65 

1.77 

23-5 

24-4 

25-2 

26-0 

26-9 

27-6 

28-4 

29-0 

29-9 

30-5 

2x  12 

1.14 

1.27 

1.41 

1.55 

1.70 

1.85 

2.01 

2.17 

2.33 

2.50 

20-3 

21-1 

21-9 

22-6 

23-2 

23-10 

24-6 

25-2 

25-9 

26-4 

.98 

1.10 

1.22 

1.34 

1.47 

1.60 

1.74 

1.88 

2.02 

2.16 

24.0 

16-7 

17-2 

17-9 

18-4 

18-11 

19-6 

20-0 

20-6 

21-1 

21-6 

.80 

.90 

1.00 

1.10 

1.20 

1.31 

1.42 

1.53 

1.65 

1.77 

For  SI:  I  inch  =  25,4  mm,  I  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


582 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4r 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

35  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 
For  Use  in  Snow  Load  Zone  3 

DESIGN  CRITERIA:  Strength-35  lbs.  per  sq  ft.  live  load  plus  1 5  lbs  per  sq.  ft.dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  ( li: 


projection. 

st  column"! 


based  on  sires 

s  crade  (top  row)  and  modulus  of  e 

asticitv  (1 

ower  figur 

:  in  each  square)  of  lumber  to  be  used. 

R\FTER  SIZE 
AND  SPACLNG 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  SENDING,  "Ft 

,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

2x6 

12.0 

5-6 
19 

6-4 
29 

7-1 
.41 

7-9 

S-5 

67 

9-0 

82 

9-0 
98 

10-0 
1  15 

.0-6 
1  33 

11-0 
1.51 

16.0 

4-9 
16 

5-6 

6-2 

6-9 
.46 

.58 

7-9 

8-3 

S5 

8-8 
1  00 

9-1 
1  15 

9-6 
1  31 

24.0 

3-11 
13 

4-6 
.21 

5-0 
.29 

5-6 
78 

5-11 
48 

0-4 
.58 

6-9 
69 

7-1 
.81 

7-5 
94 

7-9 
1.07 

2x-8 

12.0 

7-3 
.19 

8-4 
29 

9-4 

41 

10-3 

11-1 
67 

11-10 
82 

12-7 
.98 

13-3 
115 

13-11 
1.33 

14-6 

16.0 

6-3 
.16 

i5 

8-1 

8-11 
.46 

.58 

10-3 
.71 

10-10 

S5 

11-6 
1.00 

12-U 

1.15 

12-7 
1.31 

24.0 

5-2 
.13 

5-11 
21 

6-7 
29 

7-3 
.38 

7-10 
48 

8-4 
58 

8-11 

69 

9-4 
.81 

9-10 
.94 

10-3 
1.07 

2x  10 

12.0 

9-3 

19 

10-8 
.29 

11-11 
.41 

13-1 
.53 

14-2 

.67 

15-1 

82 

16-0 
.98 

16-1! 
1.15 

17-9 

1S-6 

151 

16.0 

8-0 
.16 

9-3 

10-4 

11-4 

46 

12-3 

13-1 

71 

13-10 
85 

14-8 
1.00 

115 

16-0 
131 

24.0 

6-6 
.13 

.21 

8-5 
29 

9-3 
.38 

10-0 
4S 

10-8 

.58 

11-4 
.69 

11-11 
.81 

12-6 
.94 

13-1 

2x  12 

120 

11-7 
.19 

13-0 
.29 

14-6 

.41 

15-11 

17-2 
.67 

18-4 

19-6 
.98 

20-6 

1.15 

21-7 
1.33 

22-6 

1  51 

16  0 

9-9 

.16 

11-3 
25 

12-7 
.35 

13-9 

46 

14-11 
58 

15-11 
.71 

16-10 
.85 

17-9 
1.00 

18-8 

1.15 

19-6 

1  31 

240 

7-11 
13 

9-2 
21 

10-3 
.29 

11-3 

.38 

12-2 
48 

13-0 
58 

13-9 

.69 

14-6 
81 

15-3 
94 

15-11 
1  07 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12  0 

11-5 
1.70 

11-11 

1.91 

12-4 
2.11 

12-8 
2.33 

13-1 
2.55 

13-6 

2.7S 

13-10 
3.01 

14-2 
3.25 

14-6 
3.50 

14-10 

3.75 

16.0 

9-1.1, 

1.48 

10-3 
1  65 

10-8 
1.83 

11-0 

2.02 

11-4 

2.21 

11-8 
2.41 

12-0 
261 

12-3 
2.81 

12-7 
3.03 

12-10 
3.25 

24.0 

S-l 
1.21 

8-5 
1.35 

8-8 
1.49 

9-0 

1.65 

9-3 
1.80 

9-6 
1.96 

9-9 
2.13 

10-0 
2.30 

10-3 
248 

10-6 
2  65 

2x8 

12.0 

15-1 
1.70 

15-8 
1.91 

16-3 
2.11 

16-9 
2.33 

17-3 

2.55 

17-9 

2.78 

18-3 

3.01 

18-9 

3.25 

19-2 
3.50 

19-7 

16.0 

13-1 
1.48 

13-7 
1  65 

14-0 
1.83 

14-6 
2.02 

14-11 
221 

15-5 

2.41 

15-9 
2.61 

16-2 
2.81 

16-7 
303 

17-0 
3.25 

24.0 

10-8 
1.21 

1  1-1 
1.35 

11-6 
1.49 

11-10 
1.65 

12-2 
1.80 

12-7 
1.96 

12-11 
2.13 

13-3 

2.30 

13-7 
2.48 

13-10 

2.65 

2x  10 

12.0 

19-3 
1.70 

20-0 
1.91 

20-8 
2.11 

21-4 
2.33 

22-0 
2.55 

22.8 
2.78 

23-3 
301 

23-10 
3.25 

24-6 
3.50 

25-0 
3.50 

16.0 

16-8 
1.48 

17-4 
1.65 

17-11 
1.83 

18-6 
2.02 

19-1 

2.21 

19-7 
2.41 

20-2 
2.61 

20-8 
2.81 

21-2 
3.03 

21-8 

24.0 

13-7 
1.21 

14-2 
1.35 

14-8 
1.49 

15-1 
1.65 

15-7 
1.80 

16-0 
1.96 

16-6 

2.13 

16-11 
2.30 

17-4 
2.48 

17-9 
2.65 

2x  12 

12.0 

23-5 
1.70 

24-4 
1.91 

25-2 
2.11 

26-0 

2.33 

26-9 

2.55 

27-6 
2.78 

28-3 
3.01 

29-0 
3.25 

20-9 

3.50 

30-5 

375 

160 

20-3 
1  48 

21-1 
1.65 

21-9 
1  83 

22-6 
2.02 

23-2 

2.21 

23-10 
241 

24-6 
2.61 

25-2 
281 

25-9 
3.03 

26-4 
3.25 

24  0 

16-7 
1  21 

17-2 
135 

17-9 
1  49 

18-4 
1.65 

18-11 
1.80 

19-6 
1.96 

20-0 

2  13 

20-6 
2  30 

21-1 
2.48 

21-o 

For  SI:  1  inch  =  2i,4  mm. 
NOTE:  The  modulus  of  el 


1  pound  pc 
isticitv,  "E, 


r  square  inch  =  6.895 
"  in  1 .000,000  pounds 


kPa,  1  pound  per 
per  square  inch  i; 


iquare  toot 
shown  bcli 


=  0.0479 
w  each  < 


N/m2 

pan 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


583 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3608.2.4s 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft  Live  Load 
For  Use  in  Snow  Load  Zone  4 

DESIGN  CRITERIA:  Strength-40  lbs.  per  sq.  ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 

Deflection — For  40  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  1 80. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 

HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING 

,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

5-6 
0.11 

6-4 
0.17 

7-1 

0.23 

7-9 
0.30 

8-5 

0.38 

9-0 
0.47 

9-6 

0.56 

10-0 
0.66 

10-6 
0.76 

11-0 
0.86 

11-5 
0.97 

16.0 

4-9 
0.09 

5-6 
0.14 

6-2 
0.20 

6-9 

0.26 

7-3 
0.33 

7-9 
0.41 

8-3 

0.48 

8-8 

0.57 

9-1 

0.66 

9-6 

0.75 

9-11 
0.84 

24.0 

3-10 
0.08 

4-6 
0.12 

5-0 
0.16 

5-6 
0.22 

5-11 

0.27 

6-4 
0.33 

6-9 
0.40 

7-1 

0.47 

7-5 
0.54 

7-9 
0.61 

8-1 
0.69 

2x8 

12.0 

7-3 
0.11 

8-4 
0.17 

9-4 
0.23 

10-3 
0.30 

11-1 

0.38 

11-10 
0.47 

12-6 
0.56 

13-3 
0.66 

13-10 
0.76 

14-6 
0.86 

15-1 
0.97 

16.0 

6-3 

0.09 

7-3 
0.14 

8-1 

0.20 

8-10 
0.26 

9-7 
0.33 

10-3 
0.41 

10-10 
0.48 

11-5 
0.57 

12-0 
0.66 

12-7 
0.75 

13-1 
0.84 

24.0 

5-1 
0.08 

5-11 
0.12 

6-7 
0.16 

7-3 
0.22 

7-10 
0.27 

8-4 
0.33 

8-10 
0.40 

9-4 
0.47 

9-9 
0.54 

10-3 
0.61 

10-8 
0.69 

2x10 

12.0 

9-3 
0.11 

10-8 
0.17 

11-11 
0.23 

13-1 
0.30 

14-1 
0.38 

15-1 

0.47 

16-0 
0.56 

16-10 
0.66 

17-8 
0.76 

18-6 
0.86 

19-3 
0.97 

16.0 

8-0 
0.09 

9-3 

0.14 

10-4 
0.20 

11-4 

0.26 

12-3 
0.33 

13-1 
0.41 

13-10 
0.48 

14-7 
0.57 

15-4 
0.66 

16-0 
0.75 

16-8 
0.84 

24.0 

6-6 

0.08 

7-6 
0.12 

8-5 
0.16 

9-3 
0.22 

10-0 
0.27 

10-8 
0.33 

11-4 
0.40 

11-11 
0.47 

12-6 
0.54 

13-1 
0.61 

13-7 
0.69 

2x12 

12.0 

11-3 
0.11 

13-0 
0.17 

14-6 
0.23 

15-11 
0.30 

17-2 
0.38 

18-4 
0.47 

19-6 
0.56 

20-6 
0.66 

21-6 
0.76 

22-6 
0.86 

23-5 
0.97 

16.0 

9-9 
0.09 

11-3 
0.14 

12-7 
0.20 

13-9 

n.26 

14-10 
0.33 

15-11 
0.41 

16-10 
0.48 

17-9 
0.57 

18-8 
0.66 

19-6 

0.75 

20-3 
0.84 

24.0 

8-0 
0.08 

9-2 
0.12 

10-3 
0.16 

11-3 

0.22 

12-1 

0.27 

13-0 
0.33 

13-9 
0.40 

14-6 
0.47 

15-3 
0.54 

15-11 
0.61 

16-6 
0.69 

(inches) 

(i  nches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

2x6 

120 

11-10 
1.09 

12-3 
1.20 

12-8 
1.33 

13-1 
1.45 

13-6 
1.58 

13-10 
1.72 

14-2 
1.85 

14-6 
2.00 

14-10 
2.14 

15-3 
2.29 

15-7 
2.44 

16.0 

10-3 
0.94 

10-8 
1.04 

11-0 
1.15 

11-4 

1.26 

11-8 
1.37 

12-0 
1.49 

12-3 
1.61 

12-7 
1.73 

12-11 
1.85 

13-2 
1.98 

13-5 
2.11 

24.0 

8-5 

0.77 

8-8 
0.85 

9-0 
0.94 

9-3 
1.03 

9-6 

1.12 

9-9 

1.22 

10-0 
1.32 

10-3 
1.42 

10-6 
1.52 

10-9 
1.62 

11-0 
1.73 

2x8 

12.0 

15-8 
1.09 

16-2 
1.20 

16-9 
1.33 

17-3 
1.45 

17-9 
1.58 

18-3 
1.72 

18-9 
1.85 

19-2 
2.00 

19-8 

2.14 

20-1 
2.29 

20-6 
2.44 

16.0 

13-7 
0.94 

14-0 
1.04 

14-6 
1.15 

14-11 
1.26 

15-4 
1.37 

15-9 
1.49 

16-2 
1.61 

16-7 
1.73 

17-0 
1  85 

17-4 
1.98 

17-9 
2.11 

24.0 

11-1 

0.77 

11-5 
0.85 

11-10 
0.94 

12-3 
1.03 

12-6 
1.12 

12-11 
1.22 

13-3 
1.32 

13-7 
1.42 

13-10 
1.52 

14-2 
1.62 

14-6 
1.73 

2x10 

12.0 

20-0 
1.09 

20-8 
1.20 

21-4 
1.33 

22-0 
1.45 

22-8 
1.58 

23-3 
1.72 

23-10 
1  85 

24-6 
2.00 

25-0 
2.14 

25-7 
2.29 

26-2 
2.44 

16.0 

17-3 
0.94 

17-11 
1.04 

18-6 
1.15 

19-1 
1.26 

19-8 
1.37 

20-2 
1.49 

20-8 
1.61 

21-2 
1.73 

21-8 
1.85 

22-2 
1.98 

22-8 
2.11 

24.0 

14-1 
0.77 

14-8 
0.85 

15-1 
0.94 

15-7 
1.03 

16-0 
1.12 

16-6 
1.22 

16-10 
1.32 

17-4 
1.42 

17-9 
1.52 

18-1 
1.62 

18-6 
1.73 

2x  12 

120 

24-3 
1.09 

25-2 
1.20 

26-0 
1.33 

26-9 
1.45 

27-7 
1.58 

28-3 
1.72 

29-0 
1.85 

29-9 
2.00 

30-5 
2.14 

31-1 
2.29 

31-10 
2.44 

16.0 

21-0 
0.94 

21-9 
1.04 

22-6 
1.15 

23-2 
1.26 

23-10 
1.37 

24-6 
1.49 

25-2 
1.61 

25-9 
1.73 

26-4 
1.85 

27-0 
1.98 

27-7 
2.11 

24.0 

17-2 
0.77 

17-9 
0.85 

18-4 
0.94 

18-11 
1.03 

19-6 
1.12 

20-0 
1.22 

20-6 
1.32 

21-1 
1.42 

21-7 
1.52 

22-0 
1.62 

22-6 
1.73 

For  SI:  1  inch  =  25.4 
NOTE:  The  modulus 


mm,  I  pound  per 
of  elasticity,  "E," 


square  inch  = 
in  1,000,000 


6  895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
pounds  per  square  inch  is  shown  below  each  span. 


584 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4t 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft.  Live  Load  (Supporting  Gypsum  Ceiling) 
For  Use  in  Snow  Load  Zone  4 
DESIGN  CRITERIA:   Strength-40  lbs.  per  sq.  ft.  live  load  plus  1 0  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  40  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  bv  240 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square)  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  I  top  row )  and  modulus  of  elasticity  { lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING 

"Fft,"  (p 

si) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12  0 

5-6 
0.14 

6-4 
022 

7-1 

0  31 

7-9 
041 

8-5 

0.51 

9-0 
0.63 

9-6 
075 

1 0-0 
0.88 

10-6 
1.0! 

11-0 
1.15 

11-5 
1.30 

16.0 

4-9 
0.12 

5-6 

0.19 

6-2 
0.27 

6-9 
0.35 

7-3 
0.44 

7-9 

0  54 

8-3 
0.65 

8-8 

0.76 

9-  1 
0.88 

9-6 
1.00 

9-  li 
1  12 

24.0 

3-11 
0.10 

4-6 
0.16 

5-0 
0.22 

5-6 

0.29 

5- 11 
0.36 

6-4 
0.44 

6-9 
0.53 

7-1 
0.62 

7-5 
0.71 

7-9 
0.81 

8-1 
0.92 

2x8 

120 

7-3 
0.14 

8-4 

0.22 

9-4 

0.31 

10-3 
0.41 

11-) 
0.51 

11-10 
063 

12-7 
0.75 

13-3 

088 

13-11 
1.01 

14-6 
1.15 

15-1 
1  30 

16.0 

6-3 

0  12 

7-3 
0.19 

8-1 

0.27 

8-11 
0.35 

9-7 

0.44 

10-3 
0.54 

10-11 
0.65 

11-6 

0.76 

12-0 
0.88 

12-7 
1.00 

1 3-  i 
1.12 

24.0 

0  10 

5-11 
0.16 

6-7 
0.22 

7-3 
0  29 

7-10 
0.36 

8-4 

0  4. 

8-11 

0.53 

9-4 
0.62 

9-10 
0.75 

10-3 
0.81 

10-8 

0.92 

2x  10 

12.0 

9-3 
0.14 

10-8 
0.22 

11-1 
C.31 

12-1 
0.41 

14-2 
0.51 

15-! 
0  63 

16-0 

0.75 

16-11 
088 

17-9 
1.01 

18-6 
1.15 

19-3 
1.30 

16.0 

8-0 
0  12 

9-3 
0.19 

10-4 
0.27 

11-4 
0.35 

0.44 

13-1 
0.54 

13-11 
0.65 

14-8 
0.76 

15-4 
0.88 

16-0 
1.00 

16-8 
1.12 

24.0 

6-6 
0  10 

0.16 

8-5 
0.22 

9-3 
0.29 

10-0 
0.36 

10-8 

0  44 

11-4 
053 

11-11 

0.62 

12-6 
0.71 

13-1 
081 

13-7 
0.92 

2x  12 

12.0 

11-3 
0  14 

13-0 

0.22 

14-6 
0.31 

15-11 
0.41 

17-2 
0.51 

18-4 
0.63 

19-6 

0  75 

20-6 
0.88 

21-7 
l.Oi 

22-6 
1.15 

23-5 
1.30 

16.0 

9-9 
0.12 

11-3 
0.19 

12-7 
0.27 

13-9 
0.35 

ii-l  i 

0.44 

15-11 
0.54 

i6-ll 
0.65 

17-9 
0.76 

18-8 
0.88 

19-6 
i.00 

20-3 
1.12 

24.0 

7-1! 
0  10 

9-2 
0.16 

10-3 
0.22 

11-3 
0.29 

12-1 
0.36 

13-0 

0.44 

13-9 

0.53 

14-6 
0.62 

15-3 
0.71 

15-11 
0.81 

16-7 
092 

[Inches)1 

(Inches) 

1400 

1500 

1600 

1700 

1600 

1900 

2000 

2100 

2200 

2300 

2400 

2x6 

120 

11-11 
1.45 

12-4 
1.61 

12-8 
1.77 

13-1 
1.94 

13-6 
2.12 

13-10 
2.3C 

14-2 
2.48 

14-6 
2.66 

14-10 

2.85 

15-3 
3.05 

15-7 
3.25 

16.0 

10-3 
1.26 

10-8 
1.39- 

11-0 
1.54 

1 1-4 

1  68 

ii-S 
1.83 

12-0 
1.99 

12-4 
2.15 

12-7 

2  31 

12-1! 
2  48 

13-2 
2.64 

13-5 

2.82 

240 

8-5 
1.03 

8-8 
1.14 

9-0 
1.25 

9-3 
1.37 

9-6 
1.50 

9-9 
1.62 

10-0 
1.75 

10-3 
1.89 

10-6 
2.02 

10-9 
2.16 

11-0 
2.30 

2x8 

12  0 

15-8 
1.45 

16-3 
1  6! 

16-9 

1.77 

17-3 
1.94 

17-9 

2.12 

18-3 
2.30 

18-9 
2.48 

19-2 
2.66 

19-7 
2.85 

20-1 
3.05 

20-6 
3.25 

16.0 

13-7 
1.26 

14-0 

1.39 

14-6 
1.54 

14-11 
1.68 

15-5 
1.83 

15-10 
1.99 

16-3 
2.15 

16-7 
2.31 

17-0 
2.48 

17-4 
2.64 

17-9 
2.82 

24.0 

11-1 
1.03 

11-6 
1.14 

11-10 
1.25 

12-2 
1.37 

12-7 
1.50 

12-11 
1.62 

13-3 

1.75 

13-7 
1.89 

13-11 

2.02 

14-2 
2.16 

14-6 
2.30 

2x  10 

120 

20-0 
1.45 

20-8 
1.61 

21-4 
1.77 

22-0 
1.94 

22-8 
2.12 

23-3 
2.30 

23-11 
2  48 

24-6 
2.66 

25-0 
2.85 

25-7 
3.05 

26-2 
3.25 

160 

17-4 
1.26 

17-11 
1.39 

18-6 
1  54 

19-1 
1.68 

19-7 
1.83 

20-2 
1.99 

20-8 
2.15 

21-2 
231 

21-8 
2  48 

22-2 
2.64 

22-8 

2.82 

24.0 

14-2 
1.03 

14-8 
1.14 

15-1 
1.25 

15-7 
1.37 

16-0 
1.50 

16-6 
1.62 

16-11 

1.75 

17-4 
i.89 

17-9 
2.02 

18-1 
2.16 

18-6 

2.30 

2x  12 

12.0 

24-4 
1.45 

25-2 
1.61 

26-0 
1.77 

26-9 
1  94 

27-7 
2.12 

28-a 
2.30 

29-1 
2.48 

29-9 
2.66 

30-5 
2.85 

31-2 
3.05 

31-9 
3.25 

16.0 

21-1 
1.26 

21-9 
1.39 

22-6 
1.54 

23-2 
1.68 

23-10 
1.83 

24-6 
1.99 

25-2 
2.15 

25-9 
2.31 

26-5 
2.48 

27-0 
2.64 

27-7 
2.82 

24.0 

i7-2 
1.03 

1 7-9 
1.14 

18-4 
1.25 

18-11 

1.37 

19-6 

1.50 

20-0 
1.62 

20-6 
1.75 

21-1 
1.89 

21-7 
2.02 

22-0 
2.16 

22-6 
2.30 

For  SI:  1  inch  =  2 
NOTE:  Themodul 


4  mm,  1  pound  per 
us  of  elasticity.  "E," 


square  inch  =  6 

in  1 .000.000  pounds 


kPa,  1  pound  per  square  foot  =  0.0479  kN/m 
peT  square  inch  is  shown  below  each  span 


9/1 9/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


585 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4u 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 
For  Use  in  Snow  Load  Zone  4 

DESIGN  CRITERIA:  Strength-40  lbs.  per  sq.  ft.  live  load  plus  10  lbs.  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  40  lbs.  per  sq.  ft.  live  load.  Limited  to  span  m  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

5-6 
0.22 

6-4 
033 

7-1 

0.46 

7-9 
0.61 

8-5 

0.77 

9-0 
0.94 

9-6 
1.12 

10-0 
1.31 

10-6 
1.51 

11-0 
1.72 

11-5 
1.94 

16.0 

4-9 
0.19 

5-6 

0.29 

6-2 

0.40 

6-9 
0.53 

7-3 
0.67 

7-9 
0.81 

8-3 
0.97 

8-8 

1.14 

9-1 
1.31 

9-6 
149 

9-11 
1.68 

24.0 

3-11 
0.15 

4-6 
0.24 

5-0 
0.33 

5-6 
0.43 

5-11 
0.54 

6-4 
0.67 

6-9 

0  79 

7-1 
0.93 

7-5 
1.07 

7-9 

1.22 

8-1 

1.38 

2x8 

12.0 

7-3 
0.22 

8-4 
0.33 

9-4 
0.46 

10-3 
0.61 

11-1 

0.77 

11-10 
0.94 

12-6 
1  12 

13-3 
1.31 

13-10 
1.51 

14-6 
1.72 

15-1 
1.94 

16.0 

6-3 

0.19 

7-3 
0.29 

8-1 

0.40 

8-10 
0.53 

9-7 
0.67 

10-3 
0.81 

10-10 
0.97 

11-5 
1.14 

12-0 
1.31 

12-6 
1.49 

13-1 
1.68 

24.0 

5-1 
0.15 

5-11 
0.24 

6-7 
0.33 

7-3 
0.43 

7-10 
0.54 

8-4 
0.67 

8-10 
0.79 

9-4 
0.93 

9-9 
1.07 

10-3 
1.22 

10-8 
1.38 

2x10 

12.0 

9-3 

0.22 

10-8 
0.33 

11-11 
0.46 

13-1 
0.61 

14-1 
0.77 

15-1 
0.94 

16-0 
1.12 

16-10 
1.31 

17-9 
1.51 

18-6 

1.72 

19-3 
1.94 

16.0 

8-0 
0.19 

9-3 

0.29 

10-4 
040 

11-4 

0.53 

12-3 
0.67 

13-1 
0.81 

13-10 
0.97 

14-7 
1.14 

15-4 
1.31 

16-0 
1.49 

16-8 
1.68 

24.0 

6-6 
0.15 

7-6 
0.24 

8-6 
0.33 

9-3 

0.43 

10-0 
0.54 

10-8 
0.67 

11-4 
079 

11-11 

0.93 

12-6 
1.07 

13-1 
1.22 

13-7 
1.38 

2x12 

12.0 

11-3 
0.22 

13-0 
0.33 

14-6 
0.46 

15-11 
0.61 

17-2 
0.77 

18-4 
0.94 

19-6 
1  12 

20-6 
1.31 

21-6 
1.51 

22-6 
1.72 

23-5 
1.94 

16.0 

9-9 
0.19 

11-3 
0.29 

12-7 
0.40 

13-9 
0.53 

14-10 
0.67 

15-11 
0.81 

16-10 
0.97 

17-9 
1.14 

18-8 
1.31 

19-6 
1.49 

20-3 
1  68 

24.0 

8-0 
0.15 

9-2 
0.24 

10-3 
0.33 

11-3 

0.43 

12-2 
0.54 

13-0 
0.67 

13-9 
0  79 

14-6 
0.93 

15-3 
1.07 

15-11 
1.22 

16-7 
1.38 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

2x6 

120 

11-10 
2.17 

12-3 
2.41 

12-8 
2.65 

13-1 
2.91 

13-6 
3.17 

13-10 
3.43 

14-2 
3.71 

14-6 
3.99 

14-10 
4.28 

15-3 
4.57 

15-7 
4.88 

16.0 

10-3 
1.88 

10-8 
2.09 

11-0 
2.30 

11-4 

2.52 

11-8 
2.74 

12-0 
2.97 

12-3 
3.21 

12-7 
3.46 

12-11 
3.71 

13-2 
3.96 

13-6 
4.22 

24.0 

8-5 
1.54 

8-9 
1.71 

9-0 
1  88 

9-3 
2.06 

9-6 

2.25 

9-9 

2.44 

10-0 
2.63 

10-3 
2.83 

10-6 
3.04 

10-9 
3.24 

11-0 
3.46 

2x8 

12.0 

15-8 
2.17 

16-2 
2.41 

16-9 
2.65 

17-3 
2.91 

17-9 
3.17 

18-3 
3.43 

18-9 
3.71 

19-2 
3.99 

19-7 
4.28 

20-1 

4.57 

20-6 
488 

16.0 

13-7 
1.88 

14-0 
2.09 

14-6 
2.30 

14-11 

2.52 

15-4 
2.74 

15-9 
2.97 

16-2 
3.21 

16-7 
3.46 

17-0 
3.71 

17-4 
3.96 

17-9 
4.22 

24.0 

11-1 

1.54 

11-6 
1.71 

11-10 
1  88 

12-3 
2.06 

12-6 

2.25 

12-11 
2.44 

13-3 
2.63 

13-7 
2.83 

13-11 
3.04 

14-2 
3.24 

14-6 
3.46 

2x10 

12.0 

20-0 
2.17 

20-8 
2.41 

21-4 
2.65 

22-0 
2.91 

22-8 
3.17 

23-3 
3.43 

23-10 
3.71 

24-6 
3.99 

25-0 
4.28 

25-7 
4.57 

26-2 
4.88 

16.0 

17-3 
1.88 

17-11 
2.09 

18-6 
2.30 

19-1 
2.52 

19-7 
2.74 

20-2 
2.97 

20-8 
3.21 

21-2 
3.46 

21-8 
3.71 

22-2 
3.96 

22-8 
4.22 

24.0 

14-1 
1.54 

14-7 
1.71 

15-1 
1.88 

15-7 
2.06 

16-0 
2.25 

16-6 
2.44 

16-10 
2.63 

17-4 
2.83 

17-9 
3.04 

18-1 
3.24 

18-6 
3.46 

2x  12 

12  0 

24-3 
2.17 

25-2 
2.41 

26-0 
2.65 

26-9 
2.91 

27-7 
3.17 

28-3 
3.43 

29-0 
3.71 

29-9 
3.99 

30-5 
4.28 

31-2 
4.57 

31-10 
4.88 

16.0 

21-0 
1.88 

21-9 
209 

22-6 
2.30 

23-2 
2.52 

23-10 
2.74 

24-6 
2.97 

25-2 
3.21 

25-9 
3.46 

26-4 
3.71 

27-0 
3.96 

27-7 
4.22 

24.0 

17-2 
1.54 

17-9 
1.71 

18-4 
1.88 

18-11 
2.06 

19-6 
2.25 

20-0 
2.44 

20-6 
2.63 

21-1 

2.83 

21-7 

3.04 

22-0 
3.24 

22-6 
3  46 

For  SI:  1  inch  =  25.4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "£," 


square  inch  = 
in  1,000,000 


;  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
pounds  per  square  inch  is  shown  below  each  span. 


586 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 


TABLE  3608.2.4v 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft  live  Load 
For  Use  in  Snow  Load  Zone  4 

DESIGN  CRITERIA:  Strength-40  lbs.  per  sq.  ft.  live  load  plus  i  5  lbs  per  sq.  ft.  dead  load  determines  fiber  stress. 
Deflection — For  35  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  1 80. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FTBER  STRESS  IN  BENDING,  "Fb,"  (psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

2x6 

12.0 

5-3 
0.09 

6-1 

0.14 

6-9 
0.20 

7-5 
0.26 

8-0 
0.33 

8-7 

0.41 

9-1 
0.49 

9-7 

0.57 

10-0 
0.66 

10-6 
0.75 

10-1! 
0.84 

16.0 

4-6 
0.08 

5-3 
0.12 

5-  10 
0.17 

6-5 

0.23 

6-  11 
0.29 

7-5 
0.35 

7-10 

0.42 

8-3 
0.49 

8-8 
0.57 

9-  1 

0.65 

9-5 
0.73 

24.0 

3-8 
0.07 

4-3 
0.10 

4-9 
0.14 

5-3 
0.19 

5-8 

0.24 

6-1 

0.29 

6-5 

0.34 

6-9 

0.40 

7-1 
0.46 

7-5 
0.53 

7-9 
0.60 

2x8 

12.0 

6-11 
0.09 

8-0 
0.14 

8-11 
0.20 

9-9 

0.26 

10-7 
0.33 

11-3 
0.41 

12-0 
0.49 

12-7 
0.57 

13-3 
0.66 

13-10 
0.75 

14-5 
0.84 

16.0 

6-0 
0.08 

6-11 
0.12 

7-9 
0.17 

8-6 

0.23 

9-2 
0.29 

9-9 
0.35 

10-4 
0.42 

10-11 
0.49 

11-6 

0.57 

12-0 
0.65 

12-6 
0.73 

24.0 

4-11 
0.07 

5-8 
0.10 

6-4 
0.14 

6-11 
0.19 

7-6 
0.24 

8-0 
0.29 

8-6 

0.34 

8-11 
0.40 

9-4 
0.46 

9-9 
0.53 

10-2 
0.60 

2x  10 

12.0 

8-10 
0.09 

10-2 
0.14 

11-5 
0.20 

12-6 
0.26 

13-6 
0.33 

14-5 
0.41 

15-3 
0.49 

16-1 

0.57 

16-11 
0.66 

17-8 

0.75 

18-4 
0.84 

16.0 

7-8 
0.08 

8-10 
0.12 

9-10 
0.17 

10-10 
0.23 

11-8 
0.29 

12-6 
0.35 

13-3 
0.42 

13-1  1 
0.49 

14-8 
0.57 

15-3 
0.65 

15-11 
0.73 

24.0 

6-3 

0.07 

7-2 
0.10 

8-1 
0.14 

8-10 
0.19 

9-6 

0.24 

10-2 
0.29 

10-10 
0.34 

11-5 
0.40 

11-11 
0.46 

12-6 
0.53 

13-0 
0.60 

2x12 

12.0 

10-9 
0.09 

12-4 
0.14 

13-10 
0.20 

15-2 
0.26 

16-4 
0.33 

17-6 
0.4! 

18-7 
0.49 

19-7 
0.57 

20-7 
0.66 

21-6 
0.75 

22-4 
0.84 

16.0 

9-3 

0.08 

10-9 
0.12 

12-0 
0.17 

13-1 
0.23 

14-2 
0.29 

15-2 
0.35 

16-1 
0.42 

17-0 
0.49 

17-9 
0.57 

18-7 
0.65 

19-4 
0.73 

24.0 

7-7 
0.07 

8-9 

0.10 

9-9 
0.14 

10-9 
0.19 

11-7 
0.24 

12-4 
0.29 

13-1 
0.34 

13-10 
0.40 

14-6 
0.46 

15-2 
0.53 

15-9 
0.60 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

2x6 

120 

11-4 
0.94 

11-9 
1.05 

12-1 
1.15 

12-6 
1.26 

12-10 
1.38 

13-2 
i.49 

13-6 
1.61 

13-10 
1.73 

14-2 
1.86 

14-6 
1  99 

14-10 
2.12 

16.0 

9-10 
0.82 

10-2 
0.91 

10-6 
1.00 

10-10 
1.09 

11-1 
1.19 

U-5 
1.29 

11-9 
1.40 

12-0 
1.50 

i2-4 
1.61 

12-7 
1.72 

12-10 
1.83 

24.0 

8-0 
0.67 

8-3 
0.74 

8-7 
0.82 

8-10 
0.89 

9-1 

0.97 

9-4 
1.06 

9-7 
1.14 

9-10 
1.23 

10-0 
1.31 

10-3 
1.41 

10-6 
1.50 

2x8 

12.0 

14-11 
0.94 

15-5 
1.05 

16-0 
1.15 

16-5 
1.26 

16-11 
1.38 

17-5 
1.49 

17-10 
1.61 

18-3 
1.73 

18-9 
1.86 

19-2 
1.99 

19-7 
2.12 

16.0 

12-11 
0.82 

13-5 
0.91 

13-10 
1.00 

14-3 
1.09 

14-8 
1.19 

15-1 

1.29 

15-5 
1.40 

15-10 
1.50 

16-3 
1.61 

16-7 
1.72 

16-11 
1.83 

24.0 

10-7 
0.67 

10-11 
0.74 

11-3 
0.82 

11-8 
0.89 

12-0 
0.97 

12-4 
1.06 

12-7 
1.14 

12-11 

1.23 

13-3 

1.31 

13-6 
1.41 

13-10 
1.50 

2x10 

12.0 

19-1 
0.94 

19-9 
1.05 

20-4 
1.15 

21-0 
1.26 

21-7 
1.38 

22-2 
i.49 

22-9 
1.61 

23-4 
1.73 

23-  11 
1.86 

24-5 
1.99 

24-11 
2.12 

16.0 

16-6 
0.82 

17-1 
0.91 

17-8 
1.00 

18-2 
1.09 

18-9 
1.19 

19-3 
1.29 

19-9 
1.40 

20-2 
1.50 

20-8 
1.61 

21-2 
1.72 

21-7 
1.83 

24.0 

13-6 
0.67 

13-11 
0.74 

14-5 
0.82 

14-10 
0.89 

15-3 
0.97 

15-8 
1.06 

16-1 
1.14 

16-6 
1.23 

16-11 

1.31 

17-3 
1.41 

17-8 
1.50 

2x12 

120 

23-2 
0.94 

24-0 
1.05 

24-9 
1.15 

25-6 
1.26 

26-3 
1.38 

27-0 
1.49 

27-8 
1.61 

28-4 
1.73 

29-1 
1.86 

29-9 
1.99 

30-4 
2.12 

16.0 

20-1 
0.82 

20-9 
0.91 

21-5 
1.00 

22-1 
1.09 

22-9 
1.19 

23-4 
1.29 

24-0 
1.40 

24-7 
1.50 

25-2 
1.61 

25-9 
1.72 

26-3 
1.83 

24.0 

16-4 
0.67 

17-0 
0.74 

17-6 
0.82 

18-1 
0.89 

18-7 
0.97 

19-1 

1.06 

19-7 
1.14 

20-1 
i.23 

20-6 
1.31 

21-0 
1.41 

21-5 
1.50 

For  SI:  1  inch  =  25.4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E,' 


square  inch  = 
in  1,000,000 


■-  6.895  kPa,  1  pound  per  square  foot  =  0  0479  kN/m2 
pounds  per  square  inch  is  shown  below  each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


587 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3608.2.4w 
ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Gypsum  Ceiling) 
For  Use  in  Snow  Load  Zone  4 

DESIGN  CRITERIA:  Strength — 15  lbs.  per  sq.  ft.  dead  load  plus  40  lbs.  per  sq.  ft.  live  load  determines  fiber  stress. 
Deflection — For  40  lbs.  per  sq.  ft.  live  load.  Limited  to  span  in  inches  divided  by  240. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  m  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  in  each  square)  of  lumber  to  be  used. 


RAFTER  SIZE 
AND  SPACING 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING, 

Fb, "  (ps 

) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

800 

900 

1000 

1100 

1200 

1300 

12.0 

5-3 

6-1 

6-9 

7-5 

8-0 

8-7 

9-1 

9-7 

10-0 

10-6 

10-11 

0.12 

0.19 

0.27 

0.35 

0.44 

0.54 

0.65 

0.76 

0.88 

1.00 

1.13 

4-6 

5-3 

5-10 

6-5 

6-1! 

7-5 

7-10 

8-3 

8-8 

9-1 

9-5 

0.11 

0.17 

0.23 

0.3! 

0.39 

0.47 

0.56 

0.66 

0.76 

L  0.86 

098 

3-8 

4-3 

4-9 

5-3 

5-8 

6-1 

6-5 

6-9 

7-1 

7-5 

7-9 

0.09 

0.14 

0.19 

0.25 

0.31 

0.38 

0.46 

0.54 

0.62 

0.71 

0.80 

12.0 

6-11 

8-0 

8-11 

9-9 

10-7 

1 1-3 

12-0 

12-7 

13-3 

13-10 

14-5 

0.12 

0.19 

0.27 

0.35 

0.44 

0.54 

0.65 

0.76 

0.88 

1.00 

1  13 

16.0 

6-0 

6-  11 

7-9 

8-6 

9-2 

9-9 

10-4 

10-  11 

11  -6 

12-0 

12-6 

0.11 

0.17 

0.23 

0.31 

0.39 

0.47 

0.56 

0.66 

0.76 

0.86 

098 

24.0 

4-11 

5-8 

6-4 

6-11 

7-6 

8-0 

8-6 

8-11 

9-4 

9-9 

10-2 

0.09 

0.14 

0.19 

0.25 

0.31 

0.38 

0.46 

0.54 

0.62 

0.71 

0.80 

12.0 

8-10 

10-2 

11-5 

12-6 

13-6 

14-5 

15-3 

16-1 

16-11 

17-8 

18-4 

2x10 

0.12 

019 

0.27 

0.35 

0.44 

0.54 

0.65 

0.76 

0.88 

1.00 

1.13 

16.0 

7-8 

8-10 

9-10 

10-10 

11-8 

12-6 

13-3 

13-11 

14-8 

15-3 

15-11 

0.11 

0.17 

0.23 

0.31 

0.39 

0.47 

0.56 

0.66 

0.76 

0.86 

0.98 

24.0 

6-3 

7-2 

8-1 

8-10 

9-6 

10-2 

10-10 

11-5 

11-11 

12-6 

13-0 

0.09 

0.14 

0.19 

0.25 

0.31 

0.38 

0.46 

0.54 

0.62 

0.71 

0.80 

12.0 

10-9 

12-5 

13-  10 

15-2 

16-5 

17-6 

18-7 

19-7 

20-6 

21  -5 

22-4 

2x12 

0.12 

0.19 

0.27 

0.35 

0.44 

0.54 

0.65 

0.76 

0.88 

1.00 

1.13 

9-3 

10-9 

12-0 

13-2 

14-2 

15-2 

16-1 

17-0 

17-9 

18-7 

19-4 

160 

0.11 

0.17 

0.23 

0.31 

0.39 

0.47 

0.56 

0.66 

076 

086 

0.98 

24.0 

7-7 

8-9 

9-10 

10-9 

11-7 

12-5 

!3-2 

13-10 

14-6 

15-2 

15-9 

0.09 

0  14 

0.19 

0.25 

0.31 

0.38 

0.46 

0.54 

0.62 

0.71 

0.80 

(inches) 

(inches) 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2300 

2400 

120 

11-4 

11-9 

12-1 

12-6 

12-10 

13-2 

13-6 

13-10 

14-2 

14-6 

14-10 

2x6 

1.26 

1.40 

1.54 

1.68 

1.83 

1.99 

2.15 

2.31 

2.48 

2.65 

2.82 

16.0 

9-10 

10-2 

10-6 

10-10 

11-1 

11-5 

11-9 

12-0 

12-4 

12-7 

12-10 

1.09 

1.21 

1.33 

1.46 

i.59 

1.72 

1.86 

2.00 

2.15 

2.29 

2.45 

24.0 

8-0 

8-3 

8-7 

8-  10 

9-1 

9-4 

9-7 

9-  10 

10-0 

10-3 

10-6 

0.89 

0.99 

1.09 

1.19 

1.30 

!.41 

1.52 

1.63 

1.75 

1.87 

2.00 

120 

14-11 

15-5 

16-0 

16-5 

16-11 

17-5 

17-10 

18-3 

18-9 

19-2 

19-7 

1.26 

1.40 

1.54 

1.68 

1.83 

1.99 

2.15 

2.31 

2.48 

2  65 

2.82 

16.0 

12-11 

13-5 

13-10 

14-3 

14-8 

15-1 

15-5 

15-10 

16-3 

16-7 

16-11 

2x8 

1.09 

1.21 

1.33 

1.46 

1.59 

1.72 

1.86 

2.00 

2.15 

2.29 

2.45 

24.0 

10-7 

10-11 

11-3 

11-8 

12-0 

12-4 

12-7 

12-11 

13-3 

13-6 

13-10 

0.89 

0.99 

1.09 

1.19 

1.30 

1.41 

1.52 

1.63 

1.75 

1.87 

2.00 

12.0 

19-1 

19-9 

20-4 

21  -0 

21  -7 

22-2 

22-9 

23-4 

23-11 

24-5 

25-0 

2x10 

1.26 

1.40 

1.54 

1.68 

1.83 

1.99 

2.15 

2.31 

2.48 

2.65 

2.82 

16.0 

16-6 

17-1 

17-8 

18-2 

18-9 

19-3 

19-9 

20-2 

20-8 

21-2 

21-7 

1.09 

1.21 

1.33 

1  46 

1.59 

1.72 

1.86 

2.00 

2.15 

2.29 

2.45 

24.0 

13-6 
0.89 

13-11 
0.99 

14-5 
1.09 

14-10 
1.19 

15-3 
1.30 

15-8 
1.41 

16-1 
1.52 

16-6 
1.63 

16-11 

1  75 

17-3 
1.87 

17-8 
2.00 

12.0 

23-2 

24-0 

24-9 

25-6 

26-3 

27-0 

27-8 

28-5 

29-  1 

29-9 

30-4 

2x12 

1.26 

1.40 

1.54 

1.68 

1.83 

1.99 

2.15 

2.31 

2.48 

2.65 

2.00 

16.0 

20-  1 

20-9 

21  -5 

22-1 

22-9 

23-5 

24-0 

24-7 

25-2 

25-9 

26-3 

1.09 

1.21 

1.33 

1.46 

1.59 

1.72 

1.86 

2.00 

2.15 

2.29 

2.45 

24.0 

16-5 

17-0 

17-6 

18-1 

18-7 

19-1 

19-7 

20-1 

20-6 

21-0 

21  -5 

0.89 

0.99 

1.09 

1.19 

1.30 

1.4! 

1.52 

1.63 

1.75 

1.87 

2.00 

For  SI:  1  inch  =  25.4 
NOTE:  The  modulus 


mm,  1  pound  per  square  inch  =  6.895  kPa, 
of  elasticity.  "E,"  in  1.000,000  pounds  per 


1  pound  per  square  foot  =  0  0479  kN/m2. 
square  inch  is  shown  below  each  span. 


588 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF-CEILING  CONSTRUCTION 

TABLE  3608.2.4x 

ALLOWABLE  SPANS  FOR  LOW  OR  HIGH  SLOPE  RAFTERS 

40  Lbs.  per  Sq.  Ft  Live  Load  (Supporting  Veneer  Plaster  Ceiling) 

For  Use  in  Snow  Load  Zone  4 

DESIGN  CRITERIA:  Strength— 15  lbs.  per  sq.  ft  dead  load  plus  40  lbs.  per  sq.  fl.  live  load  determines  fiber  stress. 
Deflection — For  40  lbs.  per  sq.  fl.  live  load.  Limited  to  span  in  inches  divided  by  360. 

RAFTERS:  Spans  are  measured  along  the  horizontal  projection  and  loads  are  considered  as  applied  on  the  horizontal  projection. 
HOW  TO  USE  TABLES:  Enter  table  with  span  of  rafters  (upper  figure  in  each  square).  Determine  size  and  spacing  (first  column) 
based  on  stress  grade  (top  row)  and  modulus  of  elasticity  (lower  figure  m  each  square)  of  lumber  to  be  used 


RAFTER  SPACING 
AND  SIZE 

ALLOWABLE  EXTREME  FIBER  STRESS  IN  BENDING,  "F6,' 

(psi) 

(inches) 

(inches) 

300 

400 

500 

600 

700 

300 

900 

1000 

1100 

1200 

2x6 

12.0 

5-3 
0.19 

6-1 

0.29 

6-9 
0.40 

7-5 
0.53 

8-0 
0.67 

8-7 
0.82 

9-1 

0.97 

9-7 
1  14 

10-0 
1  31 

10-6 
1  50 

160 

4-6 
0.16 

5-3 
025 

5-10 
035 

6-5 

046 

6-1  1 
058 

7-5 
071 

7-10 
084 

8-3 

099 

8-8 
1  14 

9-1 

130 

24.0 

3-8 
0.13 

4-3 
0.20 

4-9 
0.28 

5-3 
0.37 

5-8 

0.47 

6-1 
0.58 

6-5 

6-9 

7-1 

7-5 

0.69 

0.81 

0.93 

1.06 

2x8 

12.0 

6-11 
0.19 

8-0 
0.29 

8-11 
0.40 

9-9 
0.53 

iO-7 
0.67 

11-3 
0.82 

12-0 
0.97 

12-7 
1.14 

13-3 
1.31 

13-10 
1.50 

16.0 

6-0 
0.16 

6-11 
0.25 

7-9 
0.35 

8-6 
0.46 

9-2 
0.58 

9-9 

0.71 

10-4 
0.84 

10-11 
0.99 

11-6 
1.14 

12-0 
1.30 

24.0 

4-11 
0.13 

5-8 
0.20 

6-4 
0.28 

6-11 
0.37 

7-6 

0.47 

8-0 
0.58 

8-6 
0.69 

8-11 

0.81 

9-4 
.093 

9-9 
1.06 

2x10 

12.0 

8-10 
0.19 

10-2 
0.29 

11-5 
040 

12-6 
053 

13-6 
067 

14-5 
082 

15-3 
097 

16-1 
1  14 

16-11 
1  31 

17-8 
150 

16.0 

7-8 
0.16 

8-10 
0.25 

9-10 
0.35 

10-10 
0.46 

11-8 
0.58 

12-6 
0.71 

13-3 
084 

13-1  1 
0.99 

14-8 
1  14 

15-3 
1.30 

24.0 

6-3 

0.1  3 

7-2 
0.20 

8-1 
0.28 

8-10 
0.37 

9-6 

0.47 

10-2 
0.58 

10-10 
0.69 

11-5 
0.8  1 

11-11 
0.93 

12-6 
1.06 

2x12 

12.0 

10-9 
0.19 

12-5 
0.29 

13-10 
0.40 

15-2 
0.53 

16-5 
0.67 

17-6 
0.82 

18-7 
0.97 

19-7 
1.14 

20-6 
1.31 

21-5 
1.50 

16.0 

9-3 
0.16 

10-9 
0.25 

12-0 
0.35 

13-2 
0.46 

14-2 
0.58 

15-2 
0.71 

16-1 
0.84 

17-0 
0.99 

17-9 
1.14 

18-7 
1  30 

24  0 

7-7 
0.13 

8-9 
0.20 

9-10 
0.28 

10-9 
0.37 

!  1-7 
0.47 

12-5 
0.58 

13-2 

0.69 

13-10 
0.81 

14-6 
0.93 

15-2 
1.06 

(inches) 

(inches) 

1300 

1400 

1500 

1600 

1700 

1800 

1900 

2000 

2100 

2200 

2x6 

12.0 

10-11 
1.69 

11-4 
1.89 

11-9 
2.09 

12-1 

2.31 

12-6 
2.53 

12-10 
2.75 

13-2 
2.98 

13-6 
3.22 

13-10 
3.47 

14-2 
3.72 

16.0 

9-5 
1.46 

9-10 
1.63 

10-2 
1.81 

10-6 
2.00 

10-10 
2.19 

11-1 
2.38 

11-5 
2.58 

11-9 

2.79 

12-0 
3.00 

12-3 

3.22 

24.0 

7-9 
1.19 

8-0 
1.33 

8-3 
1.48 

8-7 
1.63 

8-10 
1.79 

9-1 
1.95 

9-4 
2.11 

9-7 
2.28 

9-10 

2.45 

10-0 
2.63 

2x8 

12.0 

14-5 
1.69 

14-11 
1.89 

15-5 
2.09 

16-0 
2.31 

16-5 
2.53 

16-11 
2.75 

17-5 
2.98 

17-10 
3.22 

18-4 
3.47 

18-9 
3.72 

16.0 

12-6 
1.46 

12-11 
1.63 

13-5 
1.81 

13-10 
2.00 

14-3 
2.19 

14-8 
2.38 

15-1 
2.58 

15-6 
2.79 

15-10 
3.00 

16-2 
3.22 

24.0 

10-2 
1.19 

10-7 
1.33 

10-11 
1.48 

11-3 
1.63 

11-8 
1.79 

12-0 
1.95 

12-4 
2.11 

12-7 
2.28 

12-11 
2.45 

13-3 
2.63 

2x10 

12.0 

18-4 
1.69 

19-1 
1.89 

19-9 
2.09 

20-4 
2.31 

21-0 
2.53 

21-7 
2.75 

22-2 
2.98 

22-9 

3.22 

23-4 
3.47 

23-10 
3.72 

16.0 

15-11 
1.46 

16-6 
1.63 

17-1 
1.81 

17-8 
2.00 

18-2 
2.19 

18-9 

2.38 

19-3 
2.58 

19-9 

2.79 

20-2 
3.00 

20-8 
3.22 

24.0 

13-0 
1.19 

13-6 
1.33 

13-11 
1.48 

14-5 
1.63 

14-10 
1.79 

15-3 
1.95 

15-8 
2.11 

16-1 
2.28 

16-6 
2.45 

16-10 
2.63 

2x12 

120 

22-4 
1.69 

23-2 
1.89 

24-0 
2.09 

24-9 
2.31 

25-6 
2.53 

26-3 
2.75 

27-0 
2.98 

27-9 
3.22 

28-4 
3.47 

29-1 
3.72 

16.0 

19-4 
1.46 

20-1 
1.63 

20-9 
1.81 

21-5 
2.00 

22-1 
2.19 

22-9 
2.38 

23-5 
2.58 

24-0 
2.79 

24-7 
3.00 

25-2 
3.22 

24.0 

15-9 
1.19 

16-5 
1.33 

17-0 
1.48 

17-6 
1.63 

18-1 
1.79 

18-7 
1  95 

19-1 
2.11 

19-7 
2.28 

20-1 
2.45 

20-6 
2.63 

For  SI:  1  inch  =  25.4  mm,  1  pound  per 
NOTE:  The  modulus  of  elasticity,  "E," 


square  inch  =  6.895  kPa,  1  pound  per  square  foot  =  0.0479  kN/m2. 
in  1 ,000,000  pounds  per  square  inch  is  shown  below  each  span. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


589 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 
NON-TEXT  PAGE 


590  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3609 


ROOF  COVERINGS 


3609.1  GENERAL 

3609.1.1  Application:  The  provisions  of  780  CMR 
3609.1  shall  control  the  design  and  construction  of 
roof  coverings  for  all  buildings.  Roof  coverings 
shall  be  listed  for  their  intended  use.  Materials  for 
which  listing  is  not  available  shall  be  required  to  be 
approved  by  the  State  Board  of  Building 
Regulations  and  Standards  in  accordance  with 
780  CMR  109.3.4. 

3609.1.2  Requirements:  The  roof  covering  shall  be 
capable  of  accommodating  the  loads  indicated  in 
780  CMR  3603.1  and  provide  a  barrier  against  the 
weather  to  protect  supporting  elements  and  the 
structure  beneath. 

3609.1.3  Roofing  covering  materials:  Roofs  shall 
be  covered  with  materials  as  set  forth  in  780  CMR 
3609.3  through  3609.9.  Classified  roofing  shall 
conform  to  UL  790,  as  listed  in  Appendix  A,  and 
shall  be  installed  when  the  edge  of  the  roof  is  less 
than  three  feet  (914  mm)  from  a  property  line  or  as 
required  by  city  or  town  ordinance  or  bylaw.  The 
roofing  materials  set  forth  in  780  CMR  3609.4 
through  3609. 6  and  concrete  slabs  may  be  accepted 
as  Class  A  roofing. 

780  CMR  3609.2  DECK  PREPARATION 

3609.2.1  Supporting  construction:  Roofing  shall 
be  applied  only  when  the  supporting  roof 
construction  is  clean  and  dry. 

3609.2.2  Single  layer  underlayment:  When  a 
single  ply  of  underlayment  is  required,  it  shall  be 
laid  parallel  to  the  eaves  with  a  two-inch  (5 1  mm) 
top  lap  and  four-inch  (102  mm)  end  lap  nailed 
sufficiently  to  hold  in  place. 

3609.23  Multiple  layer  underlayment:  When  two 
layers  of  underlayment  are  required,  they  shall  be 
laid  shingle  fashion  parallel  to  the  eaves  with  19- 
inch  (483  mm)  top  lap  and  12-inch  (305  mm)  end 
lap,  with  end  laps  located  at  least  six  feet  (1829  mm) 
from  end  laps  in  the  preceding  course,  and  blind 
nailed  sufficiently  to  hold  in  place. 


780  CMR  36093  ASPHALT  SHINGLES 

3609.3.1  General:  Asphalt  shingles  shall  be  applied 
only  to  solidly  sheathed  roofs  Asphalt  shingles  shall 
be  applied  according  to  the  manufacturer's  printed 
instructions  and  780  CMR  36. 

3609.3.2  Slopes  of  four  units  vertical  in  12  units 
horizontal  (33%  slope)  or  greater:  Asphalt 
shingle  roofs  shall  have  an  underlayment  of  not  less 
than  one  ply  of  No.  15  felt,  applied  as  required  in 
780  CMR  3609.2  and  Table  3609.3.4 

3609.3.3  Slopes  less  than  four  units  vertical  in  12 
units  horizontal  (33%  slope)  but  not  less  than  two 
units  vertical  in  12  units  horizontal  (17%  slope): 

Nominally  double-coverage  asphalt  shingles  may  be 
installed  on  slopes  as  low  as  two  units  vertical  in  12 
units  horizontal  ( 1 7%  slope),  provided  the  shingles 
are  approved  self-sealing  shingles  or  are  hand  sealed 
and  are  installed  with  an  underlayment  consisting  of 
two  layers  of  No.  1 5  felt,  applied  as  required  in 
780  CMR  3609.2  and  Table  3609.3.4.  The  two 
layers  of  felt  shall  be  cemented  together,  in  addition 
to  the  required  nailing,  from  the  eaves  up  the  roof  to 
overlie  a  point  24  inches  (610  mm)  inside  the 
interior  wall  line  of  the  building.  Asphalt  shingles 
shall  not  be  used  on  roofs  with  slopes  less  than  two 
units  vertical  in  12  units  horizontal  (17%  slope). 

3609.3.4  Fasteners:  Asphalt  shingles  shall  be 
fastened  according  to  the  manufacturer's  printed 
instructions  and  Table  3609.3.4. 

3609.3.5  Valley  flashing:  Roof  valleys  shall  be 
flashed  by  one  of  the  methods  listed  in  780  CMR 
3609.3.5.1  through  3609.3.5.3  Asphalt  shingles 
shall  be  applied  according  to  the  manufacturer's 
printed  instructions. 

3609.3.5.1  Sheet  metal:  Open  roof  valleys  may 
be  provided  of  not  less  than  No.  28  gage 
galvanized  corrosion-resistant  sheet  metal  and 
shall  extend  at  least  eight  inches  (203  mm)  from 
the  center  line  each  way.  Sections  of  flashing 
shall  be  jointed  to  provide  an  adequate  water  lock. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


591 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

TABLE  3609.3.4 
ASPHALT  SHINGLE  APPLICATION 


ROOF  OF  SLOPE 

NOT  PERMITTED  BELOW  2:12 

2:12  to  less  than  4:12                                                   4:12  and  over 

DECK  REQUIREMENT 

Asphalt  shingles  shall  be  fastened  to  solidly  sheathed  roofs.  Sheathing  shall  conform  to  Tables 
3605.3.2.1.1a  and  3608.3.3.2 

UNDERLAYMENT 
Temperate  climate 

Asphalt  strip  shingles  may  be  installed  on  slopes  as 
low  as  two  inches  in  twelve  inches,  provided  the 
shingles  are  approved  self-sealing  or  are  hand 
sealed  and  are  installed  with  an  underlayment 
consisting  of  two  layers  of  nonperforated  Type  1 5 
felt  applied  shingle  fashion.  Starting  with  an  1 8- 
inch-wide  sheet  and  a  36-inch-wide  sheet  over  the 
eaves,  each  subsequent  sheet  shall  be  lapped  1 9 
inches  horizontally. 

One  layer  nonperforated  Type  1 5  felt  lapped 
two  inches  horizontally  and  four  inches 
vertically  to  shed  water. 

Severe  climate: 

In  areas  subject  to  wind- 
driven  snow  or  roof  ice 
buildup. 

Same  as  for  temperate  climate,  and  additionally  the 
two  layers  shall  be  solid  cemented  together  with 
approved  cementing  material  between  the  plies 
extending  from  the  eave  up  the  roof  to  a  line  24 
inches  inside  the  exterior  wall  line  of  the  building. 

One  layer  nonperforated  Type  1 5  felt  lapped 
two  inches  horizontally  and  four  inches 
vertically  to  shed  water. 

ATTACHMENT 
Type  of  fasteners 

Corrosion-resistant  nails,  minimum  1 2-gage  %-inch  head,  or  approved  corrosion-resistant 
staples,  minimum  16-gage  1!/16-inch-crown  width. 

Fasteners  shall  be  long  enough  to  penetrate  into  the  sheathing  %  inch  or  through  the  thickness  of 
the  sheathing,  whichever  is  less. 

No.  of  fasteners1 

four  per  36-40  inch  strip 
two  per  nine- 1 8-inch  strip 

Exposure 

Field  of  roof 

Per  manufacturer's  instructions  included  with  packages  of  shingles. 

Hips  and  ridges 

Hip  and  ridge  weather  exposures  shall  not  exceed  those  permitted  for  the  field  of  the  roof 

Method 

Per  manufacturer's  instructions  included  with  packages  of  shingles. 

FLASHINGS 
Valleys 
Other  buildings 

Per  780  CMR  3609.3.5 

Per  780  CMR  3609.3.6  and  3609.3.7 

For  SI".  1  inch  =  25  4  mm. 

1.    Figures  shown  are  for  normal  application.  For  special  conditions  such  as  mansard  application  and  where  roofs  are 

in  special  wind  regions,  shingles  shall  be  attached  per  manufacturer's  instructions. 


3609.3.5.2  Roll  roofing:  Woven  or  closed 
valleys  may  be  constructed  by  centering  36-inch- 
wide  (914  mm)  roll  roofing  material  not  less  than 
Type  50  in  the  valley  over  the  underlayment. 

3609.3.5.3  Multiple  layer  flashing:  Roof  valley 
flashing  may  be  of  laced  composition  shingles, 
applied  in  an  approved  manner,  with  an  underlay 
not  less  than  30-pound  (14  kg)  felt  extending  ten 
inches  (254  mm)  from  the  center  line  each  way,  or 
shall  be  of  two  layers  of  90-pound  (41  kg) 
mineral-surfaced  cap  sheet  cemented  together 
with  the  bottom  layer  not  less  than  12  inches  (305 
mm)  wide  laid  face  down  and  the  top  layer  not 
less  than  24  inches  (610  mm)  wide  laid  face  up. 

3609.3.6  Side  wall  flashing:  Flashing  against  a 
vertical  sidewall  shall  be  by  the  step-flashing 
method. 

Exception:  Other  methods  shall  be  permitted 
when  installed  in  accordance  with  the  shingle 
manufacturer's  printed  instructions. 

3609.3.7  Other  flashing:  Flashings  against  vertical 
front  wall,  as  well  as  soil  stack,  vent  pipe  and 
chimney  flashing,  shall  be  applied  according  to 
asphalt  shingle  manufacturer's  printed  instructions. 


3609.3.8  Hips  and  ridges:  Hip  and  ridge  shingles 
shall  be  fastened  according  to  the  manufacturer's 
printed  instructions  and  Table  3609.3.4. 

780  CMR  3609.4  SLATE  SHINGLES 

3609.4.1  General:  Slate  shingles  shall  be  applied  in 
an  approved  manner  and  securely  fastened  with 
corrosion-resistant  nails  or  corrosion-resistant  nails 
and  wire. 

3609.4.2  Slate  shingles:  Slate  shingles  shall 
conform  to  ASTM  C406  as  listed  in  Appendix  A. 
Slate  shingles  shall  not  be  installed  on  roof  slopes 
below  two  units  vertical  in  12  units  horizontal 
(2:12).  Double-layer  No.  15  felt  underlayment  shall 
be  required  on  roof  slopes  below  four  units  vertical 
in  12  units  horizontal  (4:12).  Single-layer  No.  IS 
felt  underlayment  shall  be  required  on  all  other 
roof  slopes.  Slate  shingles  shall  be  secured  to  the 
roof  with  two  fasteners  per  slate  The  minimum 
slate  headlap  shall  be  three  inches  (76  mm). 

3609.4.3  Valleys:  Roof  valley  flashing  shall  be 
provided  of  not  less  than  No.  28  gage  galvanized 
corrosion-resistant  sheet  metal  and  shall  extend  at 
least  1 1  inches  (279  mm)  from  the  center  line  each 


592 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF  COVERING 


way  and  shall  have  a  splash  diverter  rib  not  less  than 
one  inch  (25  mm)  high  at  the  flow  line  formed  as 
part  of  the  flashing.  Sections  of  flashing  shall  have 
an  end  lap  of  not  less  than  six  inches  (153  mm)  and 
shall  be  provided  with  an  adequate  water  lock. 

780  CMR  3609.5  METAL 

3609.5.1  General:  Flat  sheets  or  shingles  shall  be 
applied  only  to  solid  sheathed  roofs.  Metal  roofing 
shall  be  applied  in  an  approved  manner  consistent 
with  the  manufacturer's  recommendations. 

3609.5.2  Materials:  Metal  roofing  shall  conform  to 
AA  ASM  35,  or  ASTM  A  361  or  B  209,  cs  listed  in 
Appendix  A. 

3609.5.3  Metal  shingles:  Metal  shingles  shall  not 
be  installed  on  roof  slopes  below  four  units  vertical 
in  12  units  horizontal  (4:12).  Single-layer 
underlayment  of  No.  30  felt  is  required  for  all 
metal  shingles  other  than  flat  metal  shingles  on  all 
roof  slopes. 

780  CMR  3609.6  TILE,  CLAY  OR 
CONCRETE  SHINGLES 

3609.6.1  Attachment:  All  roof  tile  shall  be  securely 
fastened  with  corrosion-resistant  nails  or  corrosion- 
resistant  nails  and  wire,  or  other  approved  means. 

3609.6.2  Interlocking  clay  or  cement  tile: 
Interlocking  clay  or  cement  tile  shall  be  installed 
only  over  solid  sheathing  or  spaced  structural 
sheathing  boards.  Interlocking  clay  or  cement  tile 
shall  not  be  installed  on  roof  slopes  below  four 
units  vertical  in  12  units  horizontal  (4:12). 
Horizontal  battens  shall  be  required  on  roof  slopes 
over  seven  units  vertical  in  12  units  horizontal 
(7:12).  Single-layer  underlayment  is  required  over 
solid  sheathing  on  all  roof  slopes.  Reinforced 
underlayment  shall  be  required  where  spaced 
sheathing  is  installed  Regardless  of  roof  slope,  the 
first  three  tile  courses  and  all  tile  within  three  feet 
(914  mm)  of  roof  edges,  changes  in  roof  slope  or 
changes  in  slope  direction,  shall  be  fastened  to  the 
roof.  For  the  field  of  the  roof,  fastening  is  not 
required  on  roof  slopes  below  five  units  vertical  in 
12  units  horizontal  (5:12);  every  tile  course  shall  be 
fastened  on  roof  slopes  five  units  vertical  in  12 
units  horizontal  (5:12)  to  less  than  12  units  vertical 
in  12  units  horizontal  (12:12);  and  every  tile  shall 
be  fastened  on  roof  slopes  12  units  vertical  in  12 
units  horizontal  (12:12)  and  over.  Tile  overlap 
shall  be  in  accordance  with  approved 
manufacturer's  installation  instructions. 

3609.6.3  Noninterlocking  clay  or  cement  tile: 
Noninterlocking  clay  or  cement  tile  shall  not  be 
installed  on  roof  slopes  below  2'A  units  vertical  in 
12  units  horizontal  (2'A:12).  Double-layer 
underlayment  is  required  on  roof  slopes  below 
three  units  vertical  in  12  units  horizontal  (3:12). 


Single-layer  underlayment  is  required  on  all  other 
roof  slopes.  Noninterlocking  clay  or  cement  tile 
shall  be  secured  to  the  roof  with  two  fasteners  per 
tile.  The  minimum  tile  overlap  shall  be  three 
inches  (76  mm). 

3609.6.4  Tile  lugs:  Tile  with  projection  anchor  lugs 
at  the  bottom  of  the  tile  shall  be  held  in  position  by 
means  of  one-inch-by-two-inch  wood  (25  mm  by  51 
mm)  stripping,  treated  to  resist  moisture 
deterioration,  nailed  to  the  roof  sheathing  over  the 
underlayment  or  other  approved  means. 

3609.6.5  Nailing  and  flashing:  Nailing  and  valley 
flashing  shall  be  the  same  as  required  for  slate 
shingles. 

780  CMR  3609.7  BUnVT-UP  ROOFING 

3609.7.1  Decking:  Built-Up  roofing  shall  be 
applied  only  to  solid  surface  roof  decks. 

3609.7.2  Materials:  Built-Up  roofing  shall  conform 
to  UL  55  A  as  listed  in  Appendix  A. 

3609.7.3  Underlayment:  An  underlayment  of  one 
layer  sheathing  paper  is  required  under  built-up 
roofing  assemblies  when  the  roof  deck  is  constructed 
of  sheathing  boards  Underlayment  is  to  be  applied  as 
specified  in  780  CMR  3609.2 

3609.7.4  Base  ply:  On  nailable  decks,  a  base  ply  is 
to  be  fastened  to  the  deck  in  accordance  with  the 
manufacturer's  published  specifications  and  Table 
3609.3.4 

3609.7.4.1  Nonnailabie  decks:  On  nonnailable 
decks,  cast-in-place  concrete  or  precast  concrete, 
a  base  ply  required  by  manufacturer's 
specification  shall  be  cemented  or  spot  mopped  to 
a  primed  deck  as  required  by  the  type  of  deck 
material,  using  not  less  than  20  pounds  (9.1  kg) 
per  square  of  hot  asphalt  for  solid  mopping,  or  not 
less  than  ten  pounds  (4.5  kg)  per  square  for  spot 
mopping,  or  not  less  than  1  Vi  gallons  (5.7  L)  per 
square  of  cold  bituminous  compound,  or  25 
pounds  (11  kg)  per  square  of  coal-tar  pitch,  in 
accordance  with  the  manufacturer's  published 
specifications.  If  a  base  ply  is  not  used,  a 
minimum  of  three  roofing  plies  applied  shingle 
fashion  shall  be  solidly  cemented  to  the  primed 
deck  and  cemented  together,  using  no  less 
cementing  material  than  that  specified  for  a 
solidly  cemented  base  ply. 

3609.7.4.2  Insulated  decks:  On  insulated  decks, 
a  vapor  retarder  shall  be  installed  between  the 
deck  and  the  insulation.  Insulation  shall  be  of  a 
rigid  type  suitable  for  application  of  a  roof 
covering.  The  insulation  must  be  properly 
attached  using  mechanical  fasteners  Type  II  or 
Type  HI  asphalt  in  accordance  with  ASTM  D  3 12, 
as   listed   in   Appendix  A,    and    installed    in 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


593 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


accordance  with  the  manufacturer 's  published  ply 
specifications.  The  insulation  may  be  taped  if 
required.  A  base  ply  required  by  the 
manufacturer's  specification  shall  be  solidly 
cemented  to  the  insulation,  using  no  less 
cementing  material  than  that  specified  for  a 
solidly  cemented  base  ply  to  a  primed  nonnailable 
deck.  If  a  base  ply  is  not  used,  a  minimum  of 
three  roofing  plies  applied  shingle  fashion  shall  be 
solidly  cemented  to  the  insulation  and  cemented 
together,  using  no  less  cementing  material  than 
that  specified  for  a  solidly  cemented  base  ply. 

3609.7.5  Membrane  over  base  ply:  A  minimum  of 
two  successive  layers  of  roofing  plies  shall  be 
solidly  cemented  shingle  fashion  to  the  base  ply, 
using  no  less  cementing  material  than  that  specified 
for  a  solidly  cemented  base  ply. 

3609.7.6  Surfacing:  The  built-up  roofing  assembly 
shall  be  surfaced  by  one  of  the  methods  described  in 
780  CMR  3609. 7.6.1  and 3609. 7.6.2. 

3609.7.6.1  Mineral  aggregate  roofs:  Mineral 
aggregate  surfaced  roofs  shall  be  surfaced  with 
not  less  than  60  pounds  (27  kg)  of  hot  asphalt  or 
75  pounds  (34  kg)  of  coal-tar  pitch  in  which  is 
embedded  not  less  than  400  pounds  (181  kg)  of 
gravel  or  300  pounds  (136  kg)  of  crushed  slag  per 
roofing  square. 

3609.7.6.2  Mineral-surfaced  cap  roofs:  Mineral- 
surfaced  cap  sheets  shall  be  cemented  to  the 
roofing  plies  using  no  less  cementing  material 
than  specified  for  between  the  plies. 

780  CMR  3609.8  WOOD  SHINGLES 

3609.8.1  Sheathing  requirements:  Wood  shingles 
shall  be  applied  to  roofs  with  solid  or  spaced 
sheathing.  Spaced  sheathing  boards  shall  not  be  less 
than  one  inch  by  four  inch  (25  mm  by  102  mm) 
nominal  dimensions  and  shall  be  spaced  on  centers 
a  distance  equal  to  the  actual  weather  exposure  of 
the  shingles,  not  to  exceed  the  dimensions  set  forth 
in  Table  3609.8  3.3. 

3609.8.2  Materials:  Wood  shingle  roofing  shall 
conform  to  CSSB  "Grading  and  Packing  Rules  for 
Centigrade  Red  Cedar  Shingles,"  as  listed  in 
Appendix  A. 

3609.8.3  Installation:  Wood  shingles  shall  be  laid 
with  a  side  lap  of  not  less  than  154  inches  (38  mm). 
Joints  in  adjacent  courses  shall  be  offset  a  minimum 
of  l!4  inches  (38  mm)  and  no  two  joints  in  alternate 
courses  shall  be  in  direct  alignment.  Spacing 
between  shingles  shall  not  be  less  than  lA  inch  (6.4 
mm)  or  more  than  %  inch  (9.5  mm).  Wood  shingles 
shall  be  fastened  to  the  sheathing  in  accordance  with 
Table  3609.8.3. 


3609.8.3.1  Roof  slope:  Shingles  shall  not  be 
installed  on  a  roof  having  a  slope  less  than  three 
units  vertical  in  12  units  horizontal  (25%  slope) 
On  roofs  having  slopes  of  three  units  vertical  in 
12  units  horizontal  (25%  slope)  and  seven  inches 
(178  mm)  from  the  center  line  each  way  for  slopes 
of  12  inches  (305  mm)  to  less  than  four  units 
vertical  in  12  units  horizontal  (33%  slope), 
shingles  shall  be  installed  with  reduced  exposures 
or  they  shall  be  installed  over  an  underlayment  of 
not  less  than  one  ply  of  No.  1 5  felt,  applied  as 
required  in  780  CMR  3609.2 

3609.8.3.2  Valley  flashing:  Roof  valley  flashing 
shall  not  be  less  than  No.  28  gage  corrosion- 
resistant  sheet  metal  and  shall  extend  ten  inches 
(254  mm)  from  the  center  line  each  way  for  roofs 
having  slopes  less  than  12  units  vertical  in  12 
units  horizontal  (100%  slope)  and  greater. 
Sections  of  flashing  shall  have  an  end  lap  of  not 
less  than  four  inches  (102  mm). 

3609.8.3.3  Weather  exposure:  Weather 
exposures  shall  not  exceed  those  set  forth  in  Table 
3609.8.3.3.  Hip  and  ridge  weather  exposures 
shall  not  exceed  those  permitted  for  the  field  of 
the  roof  Wood  shingle  hip  and  ridge  units  shall 
conform  to  CSSB  "Grading  Rules  for  Shake  Hip 
and  Ridge  based  on  the  Standards  of  the  Cedar 
Shake  and  Shingle  Bureau,"  as  listed  in 
Appendix  A.  Nails  used  to  fasten  hip  and  ridge 
units  shall  be  longer  than  those  used  in  the  field  of 
the  roof  in  order  to  penetrate  the  sheathing  Va- 
inch  (19  mm)  minimum. 

3609.8.3.4  Label  required:  Each  bundle  of 
shingles  shall  be  identified  by  a  label  of  an 
approved  grading  or  inspection  bureau  or  agency. 

780  CMR  3609.9  WOOD  SHAKES 

3609.9.1  Sheathing  requirements:  Wood  shakes 
shall  be  applied  to  roofs  with  solid  or  spaced 
sheathing.  Spaced  sheathing  boards  shall  not  be  less 
than  one-inch-by-by-inch  (25  mm  by  102  mm) 
nominal  dimensions  for  shakes  installed  at 
maximum  7/4-inch  (190  mm)  exposures  and  shall  be 
spaced  on  centers  a  distance  equal  to  the  actual 
weather  exposure  of  the  shakes,  not  to  exceed  the 
dimensions  set  forth  in  Table  3609.8.3.3.  For  24- 
inch  (610  mm)  shakes  used  in  ten-inch  (254  mm) 
exposure,  the  spaced  sheathing  shall  be  either  one- 
inch-by-four-inch  (25  mm  by  102  mm)  nominal 
dimension  board  spaced  on  centers  a  distance  equal 
to  the  weather  exposure  with  an  additional  one-inch- 
by-four-inch  (25  mm  by  102  mm)  board  placed 
between  these  boards,  or  one-inch-by-six-inch  (25 
mm  by  153  mm)  nominal  dimension  boards  spaced 
on  centers  a  distance  equal  to  the  weather  exposure 
The  shakes  shall  be  applied  over  an  underlayment  as 
required  in  Table  3609.8.3. 


594 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF  COVERING 


TABLE  3609.8.3 
WOOD  SHINGLE  OR  SHAKE  APPLICATION 


ROOF  SLOPE 

WOOD  SHINGLES 

Not  permitted  below  3:12 
See  Table  3609.8.3.3 

WOOD  SHAKES 

Not  permitted  below  4:12 
See  Table  3609.8.3.3 

DECK  REQUIREMENT 

Wood  shingles  shall  be  applied  to  roofs 
having  solid  or  spaced  sheathing  in 
accordance  with  780  CMR  3609.8. 1 

Wood  shakes  shall  be  applied  to  roofs  having  solid  or 
spaced  sheathing  in  accordance  with  780  CMR 
3609  9.1 

UNDERLAYMENT 
Temperate  climate 

No  Requirements 

One  18-inch-wide  interlayment  of  Type  30  felt 
shingled  between  each  course  in  such  a  manner  that 
no  felt  is  exposed  to  the  weather  below  the  shake 
butts. 

Severe  climate: 

In  areas  subject  to 
roof  ice  buildup 

Two  lavers  of  nonperforated  Type  15  felt 
applied  shingle  fashion  shall  be  installed  and 
solid  cemented  together  with  approved 
cementing  materia!  between  the  plies 
extending  from  the  eaves  to  a  line  36  inches 
inside  the  exterior  wall  line  of  the  building 

Sheathing  shall  be  solid  and  the  shakes  shall  be 
applied  over  a  layer  of  nonperforated  Type  1 5  felt 
applied  shingle  fashion.  Two  layers  of  nonperforated 
Type  1 5  felt  applied  shingle  fashion  shall  be  installed 
and  solid  cemented  together  with  approved  cementing 
material  between  the  plies  extending  from  the  eaves 
up  the  roof  to  a  lme  36  mches  mside  the  exterior  wall 
line  of  the  buiiding 

ATTACHMENT 
Type  of  fasteners 

Corrosion-resistant  nails,  minimum  No.  14 
Vi-gage,   /3;-inch  head,  or  corrosion-resistant 
staples  when  approved  by  the  building 
official. 

Corrosion-resistant  nails,  minimum  No.  13-gage.  73;- 
uich  head,  or  corrosion-resistant  staples  when 
approved  by  the  building  official 

Fasteners  shall  be  long  enough  to  penetrate  into  the  sheathing  %  inch  or  through  the  thickness  of  the 
sheathing,  whichever  is  less 

No.  of  fasteners 

two  per  shingle                                                  |rwo  per  shake 

Exposure 

Field  of  roof 
Hips  and  ridges 

Weather  exposures  shall  not  exceed  those  set  forth  in  Table  3609.8  3.3 

Hip  and  ndge  weather  exposures  shall  not  exceed  those  permitted  for  the  field  of  the  roof. 

Method 

Shingles  shall  be  laid  with  a  side  lap  of  not 
less  than  1  Vi  inches  between  joints  in 
adjacent  courses,  and  not  in  direct  alignment 
in  alternate  courses.  Spacing  between 
shingles  shall  be  approximately  V*  inch. 
Each  shingle  shall  be  fastened  with  two  nails 
only,  positioned  approximately  V*  inch  from 
each  edge  and  approximately  one  mch  above 
the  exposure  line    Starter  course  at  the  eaves 
shall  be  doubled. 

Shakes  shall  be  laid  with  a  side  lap  of  not  less  than 
1  Vi  mches  between  joints  in  adjacent  courses. 
Spacing  between  shakes  shall  not  be  less  than  Vs  mch 
or  more  than  %  inch  except  for  preservative-treated 
wood  shakes  which  shall  have  a  spacing  not  less  than 
'/« inch  or  more  than  %  mch.  Shakes  shall  be  fastened 
to  the  sheathing  with  two  nails  only,  positioned 
approximately  one  mch  from  each  edge  and 
approximately  two  mches  above  the  exposure  line. 
The  starter  course  at  the  eaves  shall  be  doubled    The 
bottom  or  first  layer  may  be  either  shakes  or  shingles. 
1 5-inch  or  1 8-inch  shakes  may  be  used  for  the  starter 
course  at  the  eaves  and  final  course  at  the  ndge 

FLASHINGS 
Valleys 
Other  flashings 

Per  780  CMR  3609.8.3.2  and  3609.9.3 .3 
Per  accepted  practice. 

For  SI:  1  inch  =  25.4  mm. 

1     When  approved  by  the  building  official  wood  shakes  may  be  installed  on  a  slope  of  not  less  than  three  units  vertical 

in  12  units  horizontal  (25%  slope)  when  underlayment  of  not  less  than  nonperforated  Type  15  felt  is  installed 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


595 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3609.8.3.3 

WOOD  SHINGLE  AND  SHAKE  MAXIMUM 

WEATHER  EXPOSURES 


GRADE 

LENGTH 

(inches) 

LESS  THAN  4"  IN 

12"  (inches) 
(Minimum  3"  in  12" 

Permitted) 

4" IN  12" 

AND 
STEEPER 

(inches) 

WOOD  SHINGLES 

No.  1 

16 

3% 

5 

No.21 

16 

3V4 

4 

No.  31 

16 

3 

314 

No.  1 

18 

4% 

514 

No.21 

18 

4 

414 

No.  31 

18 

314 

4 

No.  1 

24 

5V. 

714 

No.21 

24 

5'/2 

614 

No.  31 

24 

5 

514 

WOOD  SHAKES2 

No.  1 

18 

714 

VA 

No.2 

183 

Not  Permitted 

514 

No.  1 

24 

10 

10 

No.2 

24j 

Not  Permitted 

714 

For  SI:  1  inch  =  25.4  mm. 

1.  To  be  used  only  when  specifically  permitted  by  the 
building  official. 

2.  Exposure  of  24-inch  resawn  handsplit  shakes  shall 
not  exceed  714  inches  regardless  of  the  roof  slope. 

3.  No.  2  grade  wood  shakes  pertain  to  Taper-sawn 
shakes  only. 

3609.9.2  Materials:  Wood  shake  shall  conform  to 
CSSB  "Grading  and  Packing  Rules  for  Certi-Split 
Red  Cedar  Shakes"  or  "Grading  Rules  for  Certi- 
Sawn  Taper-Sawn  Cedar  Shakes,"  each  as  listed  in 
Appendix  A. 

3609.9.3  Installation:  Preservative  treated  wood 
shakes  shall  conform  to  CSSB  "Wood  Shakes 
(Preservative  Treated)  based  on  Grading  and 
Packing  Rules  for  Treated  Southern  Pine  Taper 
Sawn  Shakes  of  the  Cedar  Shake  and  Shingle 
Bureau,"  as  listed  in  Appendix  A-  Wood  shakes 
shall  be  fastened  to  the  sheathing  in  accordance  with 
Table  36  09. 8.3. 

3609.9.3.1  Shake  and  shingle  placement:   The 

starter  course  at  the  eaves  shall  be  doubled  and 
the  bottom  layer  shall  be  either  15-,  1 8-  or  24-inch 
(381,  457  or  610  mm)  wood  shakes  or  wood 
shingles.  Fifteen-inch  (381  mm)  or  18-inch  (457 
mm)  wood  shakes  may  be  used  for  the  final 
course  at  the  ridge.  Shakes  shall  be  interlaid  with 
18-inch-wide  (451  mm)  strips  of  not  less  than  No. 
30  felt  shingled  between  each  course  in  such  a 
manner  that  no  felt  is  exposed  to  the  weather  by 
positioning  the  lower  edge  of  each  felt  strip  above 
the  butt  end  of  the  shake  it  covers  a  distance  equal 
to  twice  the  weather  exposure. 


3609.9.3.2  Roof  slope:  Shakes  shall  not  be 
installed  on  a  roof  having  a  slope  less  than  four 
units  vertical  in  12  units  horizontal  (33%  slope) 
unless  they  are  installed  over  an  underlayment  of 
not  less  than  No.  15  felt,  applied  as  required  in 
780  CMR  3  609. 2. 

3609.9.3.3  Valley  flashing:  Roof  valley  flashing 
shall  not  be  less  than  No  28  gage  corrosion- 
resistant  sheet  metal  and  shall  extend  at  least  1 1 
inches  (279  mm)  from  the  center  line  each  way. 
Sections  of  flashing  shall  have  an  end  lap  of  not 
less  than  four  inches  (102  mm). 

3609.9.3.4  Weather  exposure:  Weather 
exposures  shall  not  exceed  those  set  forth  in  Table 
3609.8.3.3.  Hip  and  ridge  weather  exposures  shall 
not  exceed  those  permitted  for  the  field  of  the 
roof  Wood  shake  hip  and  ridge  units  shall 
conform  to  CSSB  "Grading  Rules  for  Shake  Hip 
and  Ridge  based  on  the  Standards  of  the  Cedar 
Shake  and  Shingle  Bureau,"  as  listed  in 
Appendix  A.  Nails  used  to  fasten  hip  and  ridge 
units  shall  be  longer  than  those  used  in  the  field  of 
the  roof  in  order  to  penetrate  the  sheathing  %  inch 
(19  mm)  minimum. 

3609.9.3.5  Label  Required:  Each  bundle  of 
shakes  shall  be  identified  by  a  label  of  an 
approved  grading  or  inspection  bureau  or  agency. 

780  CMR  3609.10  REROOFING 

3609.10.1  General:  Materials  and  methods  used  for 
repair,  replacement  or  recovering  an  existing  roof 
shall  comply  with  780  CMR  3601. 1 7  and  3609.1.1. 

When  the  repair  replacement  or  recovering  within 
any  12-month  period  exceeds  25%  of  the  roof 
covering  of  the  building,  the  entire  roof  covering 
shall  comply  with  the  requirements  for  new  roofing. 

3609.10.2  Structural  and  construction  loads:  The 

existing  roof  system  shall  be  capable  of  supporting 
all  equipment  loads  encountered  during  installation 
as  well  as  the  loads  resulting  from  the  new  roofing 
materials. 

3609.10.3  Recovering  vs.  replacement:  New  roof 
covering  shall  not  be  installed  without  first  removing 
existing  roof  coverings  when  any  of  the  following 
conditions  occur: 

1.  When  the  existing  roof  or  roof  covering  is 
water  soaked  or  deteriorated  to  the  point  of  being 
unacceptable  as  a  base  for  additional  roofing. 

2.  When  the  existing  roof  covering  is  wood 
shake,  slate,  clay  or  cement  tile;  except  when  the 
new  roof  covering  is  installed  in  accordance  with 
approved  industry  standards. 

3.  When  the  existing  roof  has  three  or  more 
layers  of  any  type  of  roofing. 

Exception:  The  removal  of  existing  roof 
coverings  shall  not  be  required  where  complete 


596 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  ROOF  COVERING 

and  separate  roofing  systems  are  provided  which       3609.10.4    Reinstallation    of    materials:        The 

transmit  all  roof  loads  directly  to  the  structural       reinstallation  of  existing  roof  covering  materials 
system  of  the  building  and  which  do  not  bear       which  have  been  removed  is  not  permitted, 
upon  the  existing  roof 

3609.10.5      Flashings:  Flashings      shall      be 

reconstructed     in     accordance     with     approved 
manufacturer's  instruction. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  597 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


NON-TEXT  PAGE 


598  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3610 


CHIMNEYS,  FIREPLACES  AND  SOLID  FUEL-FIRED  APPLIANCES 


3610.1  GENERAL 
3610.1.1  Scope:  The  provisions  of  780  CMR  3610 
shall  control  the  design,  construction,  listing  and/or 
installation  of  chimneys,  fireplaces  and  solid  fuel- 
fired  appliances  in  one-  and  two-family  buildings 

3610.2  Masonry  chimneys,  general:  Masonry 
chimneys  shall  be  constructed,  anchored,  supported 
and  reinforced  as  required  in  780  CMR  36 10  and  the 
applicable  provisions  of  780  CMR  3603,  3604  and 
3606.  Chimneys  shall  be  structurally  sound,  durable, 
smoke  tight  and  capable  of  conveying  flue  gases  to 
the  exterior  safely. 

Chimneys  in  wood-frame  buildings,  shall,  at  a 
minimum,  be  anchored  laterally  at  the  ceiling  lines 
and  at  each  floor  line  which  is  more  than  six  feet 
above  grade  except  when  entirely  within  the 
framework  of  the  building.  Anchors,  bolts,  and 
straps  so  utilized  shall  be  listed  for  such  use  and 
utilized  in  accordance  with  their  listing. 

3610.2.1  Support:  Masonry  chimneys  shall  be 
supported  on  foundations  of  solid  masonry  or 
concrete  at  least  12  inches  (305  mm)  thick  and  at 
least  six  inches  (153  mm)  beyond  each  side  of  the 
exterior  dimensions  of  the  chimney.  Footings 
shall  be  founded  on  natural  undisturbed  earth 
below  frostline.  In  areas  not  subject  to  freezing, 
footings  shall  be  located  a  minimum  of  12  inches 
(305  mm)  below  finished  grade. 

3610.2.2  Corbeling:  Masonry  chimneys  shall  not 
be  corbeled  more  than  six  inches  (153  mm)  from 
a  wall  or  foundation,  nor  shall  a  chimney  be 
corbeled  from  a  wall  or  foundation  which  is  less 
than  12  inches  (305  mm)  in  thickness  unless  it 
projects  equally  on  each  side  of  the  wall,  except 
that  on  the  second  story  of  a  two-story  dwelling, 
corbeling  of  chimneys  on  the  exterior  of  the 
enclosing  walls  may  equal  the  wall  thickness.  The 
projection  of  a  single  course  shall  not  exceed  one- 
half  the  unit  height  or  one  third  of  the  unit  bed 
depth,  whichever  is  less. 

3610.2.3  Changes  in  dimension:  The  chimney 
wall  or  chimney  flue  lining  shall  not  change  in 
size  or  shape  w-.thin  six  inches  (153  mm)  above  or 
below  where  the  chimney  passes  through  floor 
components,  ceiling  components  or  roof 
components. 

3610.2.4  Additional  load:  Chimneys  shall  not 
support  loads  other  than  their  own  weight  unless 
they  are  designed  and  constructed  to  support  the 
additional  load. 


3610.2.5  Termination  Chimneys  shall  extend  at 
least  two  feet  (610  mm)  higher  than  any  portion  of 
the  building  within  ten  feet  (3048  mm),  but  shall 
not  be  less  than  three  feet  (914  mm)  above  the 
point  where  the  chimnev  passes  through  the  roof 

3610.2.6  Wall  thickness.  Masonry  chimney  walls 
shall  be  constructed  of  solid  masonry  units  with 
not  less  than  four  inches  (102  mm)  nominal 
thickness. 

3610.2.7  Flue  lining  (material)  All  masonry 
chimneys  shall  be  lined  with  fireclay  flue  liners 
not  less  than  s/s  inch  (15  9  mm)  in  thickness  or 
with  other  approved  liner  of  material  that  will 
resist,  without  cracking  or  softening,  a 
temperature  of  1.800  *F  (9S2CC). 

Note  Lined  masonry  chimneys  may  require 
additional  metai  liners  when  such  chimneys 
convey  the  exhaust  products  of  gas-fired  or  oil- 
fired  appliances  -  refer  also  to  248  CMR  or 
527  CMR  as  applicable. 

3610.2.8  Flue  lining  (installation):  Fiue  liners 
shall  extend  from  a  point  not  less  than  eight 
inches  (203  mm)  below  the  lowest  inlet  or  as 
otherwise  required  by  248  CMR  or  527  CMR  if 
applicable,  or,  in  the  case  of  fireplaces,  from  the 
top  of  the  smoke  chamber,  to  a  point  above  the 
enclosing  walls.  Fireclay  flue  liners  shall  be  laid 
with  tight  mortar  joints  left  smooth  on  the  inside 
and  installed  to  maintain  a  '^-inch-wide  (12  7 
mm)  air  space  separating  the  flue  liners  from  the 
interior  face  of  the  chimney  masonry  walls.  Flue 
lining  shall  be  supported  on  all  sides 

3610.2.9  Multiple  flues:  When  two  or  more  flues 
are  located  in  the  same  chimney,  masonry  wythes 
shall  be  built  between  adjacent  flue  linings  The 
masonry  wythes  shall  be  at  least  four  inches  (102 
mm)  thick  and  bonded  into  the  walls  of  the 
chimney. 

Exception:  When  venting  only  one  appliance, 
two  flues  may  adjoin  each  other  in  the  same 
chimney  with  only  the  flue  lining  separation 
between  them  The  joints  of  the  adjacent  flue 
linings  shall  be  staggered  at  least  seven  inches 
(178  mm). 

3610.2.10  Flue  area  (appliance):  Chimney  flues 
shall  not  be  smaller  in  area  than  that  of  the  area  of 
the  connector  from  the  appliance  The  sizing  and 
installation  of  a  chimney  flue  to  which  multiple- 
appliance  venting  systems  are  connected  shall  be 
in  accordance  with  780  CMR  3621. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


599 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figure  3610.2.11 
FLUE  SIZES  FOR  MASONRY  CHIMNEYS1 


20  x  20 

16  x  20 

16  x  16 
12  x  16 

12  x  12 
8  xl6 

8  x  12 
8x8 

^ 

—  3000 

y. 

2800 

2600 

^^ 

^"' 

2400 

^^~ 

224 

2000 

1800 

^ 

MOO 

140 



. 

110 

1000 

■ 

S3 

■ 

J . 

200 

I             1 

1 

>2- 
IS2 

_1U1 

<  t! 
Zw-^ 

2i 

3         1 

4          1 

S          1 

6          1 

HE 
C 

7          1 

K3HT.I 

>FCCW 

1 

a       1 

4EASU 

busti 

DP  OF 

9         2 
REDFf 

wca 

FLUE 

■0         2 

W3MFL 

\MBER 
FT) 

1          22         23        24          »„,      J 
DOR                                            q!z« 

< 

For  SI:  1  inch  =  25.4  mm.  1  foot  =  304.8  mm,  1  square 
inch  =  645.16  mm". 

1.  When  using  figure  3610.2.11.  select  the  smaller  flue 
size  when  the  opening  and  height  selected  for  the 
fireplace  and  chimney,  respectively,  intersect  between 
standard  flue  sizes. 


3610.2.11  Flue  area  (masonry  fireplace):  The 

cross-sectional  area  of  the  chimney  flue  shall  be 
determined  in  accordance  with  Figure  3610.2. 1 1 . 
For  square  or  rectangular  flues,  the  nominal  flue 
size  shown  or  a  size  providing  equivalent  cross- 
sectional  area  shall  be  used  For  round  flues,  the 
size  selected  shall  be  at  least  equal  to  the  effective 
flue  area  determined  in  accordance  with  Figure 
3610.2.11.  The  height  of  the  chimney  shall  be 
measured  from  the  firebox  floor  to  the  top  of  the 
last  chimney  flue  tile.  Individual  flue  tiles  shall 
not  have  a  cross-sectional  area  less  than  50  square 
inches  (0.032  m")  for  round  flues  or  64  square 
inches  (0.041  m  )  for  square  or  rectangular  flues. 
Unlined  chimneys  shall  have  a  minimum  cross- 
sectional  area  of  100  square  inches  (0.064  m2). 

3610.2.12  Inlet:  Inlets  to  masonry  chimneys  shall 
enter  from  the  side.  Inlets  shall  have  a  thimble  of 


fireclay,  rigid  refractory  material  or  metal  that 
will  prevent  the  connector  from  pulling  out  of  the 
inlet  or  from  extending  beyond  the  wall  of  the 
liner 

3610.2.13  Masonry  chimney  cleanout  openings: 

Cleanout  openings  shall  be  provided  within  six 
inches  (153  mm)  of  the  base  of  every  masonry 
chimney 

Exception:  Chimneys  serving  masonry  fireplaces. 

3610.2.14  Chimney  clearances:  A  portion  of  a 
masonry  chimney  located  in  the  interior  of  the 
building  or  within  the  exterior  wall  of  the  building 
shall  have  a  minimum  air  space  clearance  to 
combustibles  of  two  inches  (51  mm).  Chimneys 
located  entirely  outside  the  exterior  walls  of  the 
building,  are  permitted  to  have  combustible 
matenai  m  contact  with  the  chimney  exterior 
surfaces.  Masonry  chimneys  equipped  with  a 
chimney  lining  system  listed  and  labeled  for  use 
in  chimneys  in  contact  with  combustibles  in 
accordance  with  UL  1777,  and  installed  in 
accordance  with  the  manufacturer's  installation 
instructions,  are  permitted  to  have  combustible 
material  in  contact  with  their  exterior  surfaces. 


600 


780  CMR  -  Sixth  Edition  corrected-  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  CHIMNEYS,  FIREPLACES  AND 

SOLID  FUEL-FIRED  APPLIANCES 


The  requirements  of  780  CMR  3610.2.14  shall 
not  eliminate  the  requirement  for  noncombustible 
firestopping  in  accordance  with  780  CMR 
3610.2.15. 

3610.2.15  Chimney  firestopping:  See  780  CMR 

3606.2.7. 

3610.2.16  Chimney  crickets  Chimney  shall  be 
provided  with  crickets  when  the  dimension 
parallel  to  the  ridgeline  is  greater  than  30  inches 
(762  mm)  and  does  not  intersect  the  ridgeline. 
The  intersection  of  the  cricket  and  the  chimney 
shall  be  flashed  and  counterflashed  in  the  same 
manner  as  normal  roof-chimney  intersections 
Crickets  shall  be  constructed  in  conformity  with 
Figure  3610.2.16  and  Table  3610  2.16. 


3610.4  Masonry  fireplaces,  general:  Masonry 
fireplaces  shall  conform  to  the  requirements  of 
780  CMR  3610.4.1  through  3610.4.7. 

Note:  Masonry  fireplaces  may  be  prescriptively 
constructed  or  may  be  of  the  "Rumford"  type  or 
may  be  of  contemporary  design;  refer, 
additionally  to  the  BOCA  National  Mechanical 
Code.  Brick  Institute  of  America,  Technical  Notes 
and  NFPA  21 1  as  listed  in  Appendix  A  -  also  see 
Figures  3610.4.1a,  lb,  lc,  Id,,  le,  If  and  lg. 

3610.4.1  Fireplace  support:  Fireplace 
foundations  and  supporting  walls  shall  be 
anchored,  supported  and  reinforced  as  required  in 
780  CMR  3610.4.1  through  3610.4.7,  Table 
3610.4.1,  Figure  3610.4.1a  and  the  applicable 
provisions  of  780  CMR  3603  and  3604. 


Figure  3610.2.16 
CHIMNEY  CRICKET 


Table  3610.2.16 
CRICKET  DIMENSIONS 


ROOF  SLOPE 

H 

12-  12 

1/2  of  W 

8-  12 

1/3   of  W 

6-  12 

1/4  of  W 

4-  12 

1/6  of  W 

3  -  12 

1/8  of  W 

3610.3  Factory-built  chimneys,  general:  Factory- 
built  chimneys  shall  be  tested  and  listed  to  UL-103 
or  CAN/ULC-S629-M87  as  found  in  Appendix  A 

and  shall  be  installed,  operated  and  maintained  in 
accordance  with  the  conditions  of  their  listing  and 
the  manufacturer's  requirements.  Factory-built 
chimneys  that  are  listed  as  part  of  an  assembly  with 
factory-built  fireplaces  shall  conform  to  780  CMR 
3610.5.1. 


Exception:  Masonry  fireplaces  other  than 
those  that  are  prescriptively  constructed  shall 
comply  with  the  requirements  of  780  CMR 
3610.4.1  through  3610.4.7  but  may  be  of  a 
design  other  than  shown  in  Figure  3610.4.1a- 
also  see  Figures  3610.4.1b,  lc,  Id,,  le,  If  and 

lg- 

Foundations  for  masonry  fireplaces  and 
their  chimneys  shall  be  constructed  of  concrete 
or  solid  masonry  at  least  12  inches  (305  mm) 
thick  and  extend  at  least  six  inches  (153  mm) 
beyond  the  face  of  the  fireplace  or  supporting 
wall  on  all  sides.  Footings  shall  be  founded  on 
natural  undisturbed  earth  or  engineered  fill 
below  frost  depth.  In  areas  not  subjected  to 
freezing,  footings  shall  be  at  least  12  inches 
(305  mm)  below  finished  grade. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


601 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Table  3610.6.4.1 
REQUIREMENTS  FOR  MASONRY  FIREPLACES  AND  CHIMNEYS 

ITEM 

LETTER 

REQUIREMENTS 

Hearth  slab  thickness 

A 

4"" 

Hearth  extension 
(each  side  of  opening) 

B 

8"  fireplace  opening  <  6  sq.  ft. 
12"  fireplace  opening  >  6  sq  ft 

Hearth  extension 
(front  of  opening) 

C 

1 6"  fireplace  opening  <  6  sq.  ft 
20"  fireplace  opening  >  6  sq.  ft 

Hearth  slab  reinforcing 

D 

Reinforced  as  necessary  to  cam'  its  own  weight 
and  all  imposed  loads 

Thickness  of  wall  of  firebox 

E 

10"  solid  brick  or  8"  where  a  firebrick  lining  is 
used  Joints  in  firebrick  1/4"  max 

Distance  from  top  of  opening  to  throat 

F 

S" 

Smoke  chamber  edge  of  shelf 
Rear  wall  -  thickness 
Front  wall  -  thickness 

G 

6" 
8" 

Chimney 
Vertical  reinforcing 

Seismic  load  reinforcement  not  required  in 
Massachusetts 

Horizontal  reinforcing 

Seismic  load  reinforcement  not  iequired  m 
Massachusetts 

Bond  beams 

K 

No  specified  requirements 

Fireplace  lintel 

L 

Noncombustible  material 

Walls  with  flue  lining 

M 

Refer  to  780  CMR  3610.2.8 

Walls  with  unlined  flue 

N 

Unlined  chimneys  are  not  allowed  to  be 
constructed  in  Massachusetts 

Distances  between  adjacent  flues 

Refer  to  780  CMR  3610.2.9 

Effective  flue  area 
(based  on  area  of  fireplace  opening) 

P 

Refer  to  7S0  CMR  3610  2. 10  and  3610.2. 1 1 

Clearances 
Wood  frame  and 
combustible  material 

Above  roof 

R 

Refer  to  780  CMR  3610.2.14  and  3610.4.7 
2"  at   10'  (780  CMR  3610.2.5) 

Anchorage 

Seismic  load  reinforcement  not  required  in 
Massachusetts  but  also  refer  to  780  CMR  3610.2 

Footing 
Thickness 

Width 

T 

12"  mm. 

6"  each  side  of  fireplace  wall 

For  SI:   1  inch  =  304.8  mm 

I.    The  letters  m  this  column  refer  to  Figure  3610.4. 


602 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  CHIMNEYS,  FIREPLACES  AND 

SOLID  FUEL-FIRED  APPLIANCES 

Figure  3610.4.1a 
FIREPLACE  AND  CHIMNEY  DETAILS 


UASONRY  CAP 


— u© 


=i^i 


W3 


.     7WCX 
MASONRY  UWTS 
/T?,  VERTICAL   RON  FORCING 
^25"    L>P   tf   SPutOl 
TO  FOOTlNC  OOWELS 

-ossaabT1 — 

KyxFOOTWC  W10TH  9" 
1^S53DS5TREE 

STAHONC  fwepuce 

W\\X—  NA1URAI. 

CONCRCTE 
FOCTTTMC 


8RICK   FIREBOX  AND   CHIMNEY- 
SECTIONAL  SIDE  VIEW  ON  WOOD  FLOOR 


BRICK  FIREBOX  AND   BLOCK  CHIMNEY- 
SECTIONAL  SIDE  VIEW  ON  CONCRETE  SUB 


2/7/97    Effective  (2/28/97) 


780  CMR  -  Sixth  Edition 


603 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figures  3610.4.1b  through  3610.4.1g 
TYPICAL  FIREPLACE  DETAILS 


Figure  3 10.4.  Id 
RUMFORD  REQUIREMENTS 


604 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


ONE  AND  TWO  FAMILY  DWELLINGS  -  CHIMNEYS,  FIREPLACES  AND 

SOLID  FUEL-FIRED  APPLIANCES 


3610.4.2  Seismic  reinforcing:  Not  applicable  in 
Massachusetts. 

3610.4.2.1  Seismic  anchorage:  Not  applicable 
in  Massachusetts. 

3610.4.3  Fireplace  walls:  Masonry  fireplaces 
shall  be  constructed  of  solid  masonry  units,  stone 
or  reinforced  concrete  in  accordance  with  Figure 
3610.4.  la.  When  a  lining  of  firebrick  at  least  two 
inches  (5 1  mm)  in  thickness  is  provided,  the  total 
thickness  of  back  and  sides,  including  the  lining, 
shall  not  be  less  than  eight  inches  (203  mm). 
When  no  lining  is  provided,  the  thickness  of  back 
and  sides  shall  not  be  less  than  ten  inches  (254 
mm). 

3610.4.3.1  Walls,  steel  fireplace  units:  Steel 
fireplace  units  shall  be  listed  in  accordance 
with  UL  127  as  found  in  Appendix  A  and  shall 
be  installed,  operated  and  maintained 
according  to  their  listing,  the  manufacturer's 
requirements  and  any  applicable  requirements 
of  780  CMR.  Such  fireplaces  incorporating  a 
fire  box  liner  of  not  less  than  V*  inch  (6.4  mm) 
in  thickness  and  an  air  chamber,  may  be 
installed  with  masonry  to  provide  a  total 
thickness  at  the  back  and  sides  of  not  less  than 
eight  inches  (203  mm),  of  which  not  less  than 
four  inches  (102  mm)  shall  be  of  solid 
masonry.  Warm-air  ducts  employed  with  steel 
fireplace  units  of  the  circulating  air  type  shall 
be  constructed  of  metal  or  masonry. 

3610.4.4  Lintel:  Masonry  over  a  fireplace 
opening  shall  be  supported  by  a  lintel  of 
noncombustible  material.  The  minimum  required 
bearing  length  on  each  end  of  the  fireplace 
opening  shall  be  four  inches  (102  mm). 

3610.4.5  Hearth  extension  material:  Hearth 
extensions  shall  be  of  masonry  or  concrete  at  least 


two  inches  (51  mm)  thick  and  supported  by 
noncombustible  materials  and  reinforced  to  carry 
its  own  weight  and  all  imposed  loads.  The  hearth 
extension  shall  be  readily  distinguishable  from  the 
surrounding  floor.  Combustible  forms  and  centers 
used  during  the  construction  of  the  hearth 
extension  shall  be  removed  after  the  construction 
is  complete. 

Exception:  When  the  bottom  of  the  firebox 
opening  is  raised  at  least  eight  inches  (203 
mm)  above  the  top  of  the  hearth  extension,  a 
hearth  extension  of  not  less  than  %  inch-thick 
(9.51  mm)  brick,  concrete,  stone,  tile  or  other 
approved  noncombustible  material  may  be 
used. 

3610.4.6  Hearth  extension:  The  hearth  and  the 
hearth  extension  shall  extend  a  minimum  of  36 
inches  (914  mm)  from  the  back  of  the  firebox  to 
the  end  of  the  hearth  extension.  Hearth 
extensions  shall  extend  at  least  16  inches  (406 
mm)  in  front  of,  and  at  least  eight  inches  (203 
mm)  beyond,  each  side  of  the  fireplace  opening. 
Where  the  fireplace  opening  is  six  square  feet 
(0.557  m2)  or  larger,  the  hearth  extension  shall 
extend  at  least  20  inches  (508  mm)  in  front  of,  and 
at  least  12  inches  (305  mm)  beyond,  each  side  of 
the  fireplace  opening. 

3610.4.7  Fireplace  clearance:  Wood  or 
combustible  framing  shall  not  be  placed  within 
two  inches  (51  mm)  of  the  outside  face  of  a 
masonry  fireplace  and  not  less  than  six  inches 
(153  mm)  from  the  inside  surface  of  the  nearest 
flue  lining.  Wood  framing  and  other  combustible 
material  shall  not  be  placed  within  two  inches  (5 1 
mm)  of  the  back  surface  of  a  masonry  fireplace. 
See  Figures  3610.4.7a  and  7b. 


2/7/97    Effective  (2/28/97) 


780  CMR  -  Sixth  Edition 


605 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figure  3610.4.7a 

CONSTRUCTION  REQUIREMENTS  FOR  A  TYPICAL  MASONRY  FIREPLACE 

IN  A  WOOD  FRAME  WALL 


UIN.    CLEARANCE    FROM   COUBUST18LES 


HEARTH    EXTENSION 


Figure  3610.4.7b 
REQUIRED  CLEARANCES  FROM  AMSONRY  FIREPLACE  TO  COMBUSTIBLES 


SUOKE   CHAMBER 


C0UBUST19LE  MATERIAL 
PROJECTING   WORE 
THAN    I     1/2' 


FIREPLACE  WALL 


3610.5  Factory-built  fireplaces,  general:  Factory- 
built  fireplaces  shall  conform  to  the  requirements  of 
780  CMR  3610.5.1  through  3610.5.4. 

3610.5.1  Installation:  Factory-built  fireplaces 
that  consist  of  a  fire  chamber  assembly,  one  or 
more  chimney  sections,  a  roof  assembly  and  other 
parts  shall  be  tested  and  listed  to  UL-127  as  found 
in  Appendix  A.  Such  fireplaces  may  be  installed 
when  complying  with  all  the  following 
provisions: 

1.  The  fire  chamber  assembly  is  installed  to 
provide  clear  clearance  to  combustible 
materials  not  less  than  set  forth  in  the  listing. 

2.  The  chimney  sections  are  installed  to 
provide  clearance  to  combustible  material  not 
less  than  specified  in  the  listing  and  if  the 
fireplace  chimney  extends  through  floors  and 


ceilings,  factory-furnished  firestops  or  firestop 
spacers  shall  be  installed.  Portions  of  chimneys 
which  extend  through  rooms  or  closets  are  to 
be  enclosed  to  avoid  personal  contact,  contact 
of  combustible  material,  and  damage  to  the 
chimney. 

3.  Hearth  extensions  shall  not  be  less  than  %- 
inch-thick  (9.5  mm)  millboard,  hollow  metal, 
stone,  tile  or  other  approved  noncombustible 
material.  Such  hearth  extensions  may  be 
placed  on  combustible  subflooring  or  finish 
flooring.  The  hearth  extension  shall  be  readily 
distinguished  from  the  surrounding  floor. 

Note:  Where  floor  protection  underneath,  to 
the  sides,  back  or  in  front  of  factory-built 
fireplaces  is  required  via  testing/listing 
and/or  manufacturer's  requirments,  refer  to 


606 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


ONE  AND  TWO  FAMILY  DWELLINGS  -  CHIMNEYS,  FIREPLACES  AND 

SOLID  FUEL-FIRED  APPLIANCES 


floor  protector  requirements  of  780  CMR 
3610.6.7.1  and  3610.6,7,1,1. 

4.  Hearth  extensions  shall  extend  not  less  than 
16  inches  (406  mm)  in  front  of  and  at  least 
eight  inches  (203  mm)  beyond  both  sides  of  the 
fireplace  opening. 

Exception:  Where  tested/listed  extensions 
are  identified,  such  hearth  extension  shall  be 
allowed  and  required. 

5.  Factory-built  fireplaces  shall  be  installed  in 
accordance  with  their  listing  and  the 
manufacturer's  installation  instructions. 

6.  The  supporting  structure  for  a  hearth 
extension  shall  be  at  the  same  level  as  the 
supporting  structure  for  the  fire  place  unit 
unless  otherwise  authorized  by  the  listing. 

3610.6 

3610.6.1  Solid  fuel-fired  appliances,  general: 

Solid  fuel-fired  appliances  employed  for  comfort 
heating  include,  but  are  not  limited  to,  room 
heaters  and  stoves,  fireplace  inserts,  furnaces  and 
boilers;  additionally,  the  fuel  for  such  appliances 
includes,  but  is  not  limited  to:  wood  and  wood 
pellets,  coal  and  various  other  solid  fuels  such  as 
nut  shells  and  corn,  etc.  Solid  fuel-burning 
appliances  shall  be  tested  and  listed  by  approved 
agencies  and  installed,  operated  and  maintained  in 
accordance  with  such  listing,  the  manufacturers' 
requirements  and  otherwise  conform  to  the 
requirements  of  780  CMR  3610.6. 

Note  1:  No  solid  fuel-burning  appliance  shall 
be  installed  in  Massachusetts  unless  such 
appliance  conforms  to  all  applicable 
requirements  of  780  CMR  3610.6,  including 
the  testing  and  listing  of  all  clearances  to 
combustibles  and  identification  of  required 
floor  protection. 

Note  2:  In  the  absence  of  explicit  requirements 
of  780  CMR  3610.6,  the  applicable 
requirements  of  NFPA  21 1  and/or  the  BOCA 
National  Mechanical  Code,  as  listed  in 
Appendix.  A,  shall  apply. 

3610.6.1.1  Listing  standards,  Room  heaters, 
stoves  and  fireplace  inserts:  Room  heaters, 
stoves  and  fireplace  stoves  (inserts),  employed 
for  comfort  heating  shall  be  listed  and  tested  to 
UL  1482  and/or  ANSIAJL  737  as  found  in 
Appendix  A  and  as  applicable;  all  such 
appliances  shall  bear  labeling  as  required  in 
780  CMR  3610.6.2  or  3610.6.3  as  applicable. 

3610.6.1.2  Listing  standards,  all  pellet  fueled 
solid  fuel-burning  appliances:  All  pellet 
solid  fuel-burning  appliances  sold  for  use  in 
Massachusetts  shall  conform  to  780  CMR 
3610.6.1.1  and  additionally  comply  with  the 
certification  program  set  forth  by  the  State 
Board  of  Building  Regulations  and  Standards 


(for  pellet  appliance  certification  information, 
contact  the  State  Board  of  Building 
Regulations  and  Standards). 

Note:  Commencing  January  1,  1998,  all 
pellet  solid  fuel-burning  appliances  shall  be 
tested  and  listed  to  ASTM  E  1509  as  found 
in  Appendix  A  and  shall  bear  such  labeling 
as  required  in  780  CMR  3610.6.2 

3610.6.2  Solid  fuel-burning  appliance  labeling 
(not  central  heating  appliances):  Every  solid 
fuel-burning  appliance  utilized  for  comfort 
heating  shall  bear  a  permanent  and  legible 
factory-applied  label  supplied  to  the  manufacturer 
and  controlled  by  an  approved  testing  agency; 
such  label  shall  contain  the  following  information: 

1.  Manufacturer's  name  and  trademark; 

2.  Model  and/or  identification  number  of  the 
appliance; 

3.  Type(s)  of  fuel(s)  approved; 

4.  Testing  laboratory's  name  or  trademark 
and  location; 

5.  Date  tested; 

6.  Clearances  to  combustibles 

(a)  Above  top 

(b)  From  front 

(c)  From  back 

(d)  From  sides 

7.  Floor  protection 

8.  National  test  standard(s) 

9.  Label  serial  number 

3610.6.3  Solid  fuel-burning  central  heating 
appliance  labeling:  Every  solid  fuel-burning 
boiler  or  warm  air  furnace  shall  bear  a  permanent 
and  legible  factory-applied  label  supplied  to  the 
manufacturer  and  controlled  by  an  approved 
testing  agency;  such  label  shall  contain  the 
following  information: 

1.  Manufacturer's  name  and  trademark; 

2.  Model  and/or  identification  number  of  the 
appliance; 

3.  Type(s)  of  fuel(s)  approved; 

4.  Testing  laboratory's  name  or  trademark 
and  location; 

5.  Date  tested; 

6.  Clearances  to  combustibles 

(a)  Above  top 

(b)  From  front 

(c)  From  back 

(d)  From  sides 

7.  Floor  protection  if  applicable 

8.  National  test  standard(s) 

9.  Label  serial  number 

10.  Type  of  appliance  (boiler  or  warm  air 
furnace) 

1 1 .  Every  boiler,  pressure  vessel,  or  pressure 
relief  device  must  be  stamped  in  accordance 
with  the  requirements  of  the  ASME  Boiler  and 
Pressure  Vessel  Code.  ASME  stamping  shall 
also  be  required  for  boilers,  pressure  vessels 


2/7/97    Effective  (2/28/97) 


780  CMR  -  Sixth  Edition 


607 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  pressure  relief  devices  produced  outside 
the  United  State  of  America.  Where  required 
by  the  ASME  Boiler  and  Pressure  Vessel 
Code,  ASME  stamping  may  be  affixed  directly 
to  the  appliance  in  lieu  of  on  the  data  plate. 

3610.6.3  Hazardous  locations:  Solid  fuel- 
burning  appliances  shall  not  be  installed  in 
hazardous  locations  (any  location  considered  to  be 
a  fire  hazard  for  flammable  vapors,  dust, 
combustible  fibers  or  other  highly  combustible 
substances). 

Exception:  solid  fuel-fired  appliances  listed 
for  such  locations. 

3610.6.4  Air  for  combustion  and  ventilation: 

Solid  fuel-burning  appliances  shall  be  installed  in 
a  location  and  manner  to  assure  satisfactory 
combustion  of  fuel,  proper  chimney  draft  and 
maintenance  of  safe  operating  temperatures. 
Combustion  air  may  be  obtained  from  interior 
spaces  when  the  interior  space  containing  the 
appliance  has  a  volume,  in  cubic  feet  equal  to 
one-twentieth  (1/20)  of  the  output  Btu  rating  of 
all  fuel-burning  appliances  in  the  space.  When 


buildings  are  so  tight  as  to  preclude  adequate 
infiltration,  provisions  shall  be  made  to  introduce 
outside  air  for  combustion  and  ventilation. 

3610. 6.. 5  Chimney  connection:  All  solid  fuel- 
burning  appliances  shall  be  connected  to 
chimneys  in  accordance  with  their  listing,  the 
manufacturer's  requirements  and  the  requirements 
of780CMR36. 

Exception:  Solid  fuel-burning  appliances  listed 
for  exhaust  vent  termination  other  than  through 
a  chimney. 

3610.6.5.1  Chimney  connector  clearance  to 
combustibles:  See  780  CMR  Table  3610.6.5. 1 . 

3610.6.5.2  Chimney  flue  size:  For  solid  fuel- 
burning  comfort  heating  appliances  for  one- 
and  two  family  use,  the  cross-sectional  area  of 
the  flue  shall  not  be  less  than  the  cross- 
sectional  area  of  the  appliance  flue  collar.  The 
cross-sectional  area  of  the  flue  shall  not  be 
more  than  three  times  the  cross-sectional  area 
of  the  flue  collar  of  the  appliance. 


,1,2 


Table  3610..6.5.1 
CHIMNEY  AND/OR  VENT  CONNECTOR  CLEARANCES  TO 
COMBUSTIBLE  MATERIALS/SOLID  FUEL-BURNING  APPLIANCES  ONLY 


Description  of  Appliance 

Connector  Type 

Minimum 

Clearance 

(in) 

Minimum 

Clearance 

(mm) 

Residential-Type  Appliances 

Single-wall  Metal  Pipe 
Connector 

18 

457 

Residential-Type  Appliances 

Type  L  Vent  Piping 
Connector 

9 

229 

Low-heat  Appliances 

Boilers,  Furnaces,  Water  Heaters 

Single-wall  Metal  Pipe 
Connector 

18 

457 

Medium-Heat  Appliances 

Single-wall  Metal  Pipe 
Connector 

36 

914 

High-Heat  Appliances 

Masonry  or  Metal 
Connector 

Note  3 

Note  3 

1.  For  greater  detail  and  guidance,  refer  to  NFPA  211,  Section  6-5. 

2.  For  Chimney  Connectors  tested  and  listed  for  other  clearances  to  combustibles,  such  tested,  listed 
clearances  shall  apply. 

3.  Clearances  shall  be  based  on  engineering  calculations  and,  good  engineering  practice  -  Refer  to  NFPA 
211,  Section  6-5 


608 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  CHIMNEYS,  FIREPLACES  AND 

SOLID  FUEL-FIRED  APPLIANCES 


3610.6.6  Connection  to  masonry  fireplaces:  A 

solid  fuel-burning  appliance  such  as  a  stove  or 
fireplace  insert  shall  be  permitted  to  use  a 
masonry  fireplace  flue  where  the  following 
conditions  are  met: 

1 .  There  is  a  connector  that  extends  from  the 
appliance  to  the  flue  liner; 

2.  The  cross-sectional  area  of  the  flue  is  no 
more  than  three  times  the  cross-sectional  area 
of  the  flue  collar  of  the  appliance  but  never  less 
than  the  appliance  exhaust  collar  cross- 
sectional  area; 

3.  If  the  appliance  vents  directly  through  the 
chimney  wall  above  the  smoke  chamber  of  the 
fireplace,  there  shall  be  a  noncombustible  seal 
below  the  entry  point  of  the  connector,  sealing 
the  fireplace  from  the  appliance; 

4.  The  installation  shall  be  such  that  the 
chimney  system  can  be  inspected  and  cleaned; 

5.  Means  shall  be  provided  to  prevent  dilution 
of  combustion  products  in  the  chimney  flue 
with  air  from  the  habitable  space. 

3610.6.7  Mounting  (placing)  of  residential  solid 
fuel-burning  appliances:  Residential  type  solid 
fuel-burning  appliances  shall  be  tested  and  listed 
by  approved  agencies  and  such  appliances,  when 
mounted  (placed)  on  combustible  or 
noncombustible  materials,  shall  be  installed  in 
accordance  with  their  listing  and  the 
manufacturer's  requirements. 

Exceptions:  SeeNFPA211,  Section  9-5.1.1.1 
(all  such  exceptions  pertain  to  placing  of  such 
appliances  on  well  supported  concrete  bases, 
concrete  slabs,  properly  stabilized, 
noncombustible  soils  or  on  approved, 
noncombustible  assemblies  of  two  hour  fire 
resistance  with  floors  constructed  of 
noncombustible  materials). 

3610.6.7.1  Floor  protection:  Floor  protection 
shall  satisfy  all  listing  requirements. 

3610.6.7.1.1  Floor  protectors  -  definition: 

Floor  protectors  are  noncombustible 
surfacing  applied  to  the  combustible  or 
noncombustible  floor  area  underneath  and 
extending  in  front,  to  the  sides  and  to  the 
rear  of  a  heat  producing  appliance.  For 
purposes  of  780  CMR  3610.6.7,  floor 
protectors  must  be  noncombustible  and 
have  the  necessary  thermal  conductivity  to 
satisfy  the  appliance  tested/listing  floor 
protection  requirements. 

Note  1:  Refer  to  Appendix  K  for 
information  on  floor  protector  thermal 
conductivity  calculations 
Note  2:  Various  "hearth  rugs",  "mats", 
"tile  board",  "hearth  board"  and  similar 
products,  sold  as  floor  protectors  may  be 
noncombustible    but    may    not    satisfy 


thermal    conductivity    requirements    to 
comply  with  780  CMR  3610.6.7. 1. 

3610.6.8  Appliance  clearances:  Solid  fuel- 
burning  appliances  shall  be  installed  in 
accordance  with  the  manufacturer's  tested,  listed 
clearances  (also  see  780  CMR  3610.6. 11.1  for 
used  solid  fuel-burning  appliance  clearance 
requirements). 

3610.6.8.1  Clearance  reductions:  Tested, 
listed  clearances  to  combustibles  shall  only  be 
permitted  to  be  reduced  in  accordance  with  the 
requirements  of  NFPA  21 1,  Section  9-6.1  and 
9-6.2. 

Note  that  an  engineered  protection  system  is 
required  to  achieve  a  reduced  clearance 
installation  except  when  appliances  are 
installed  in  rooms  that  are  large  in 
comparison  to  the  size  of  the  appliance  -  see 
NFPA  211,  Section  9-6.1. 

3610.6.9  Supply  ducts:  When  a  solid  fuel- 
burning  appliance  utilizes  supply  ducts  such  ducts 
conveying  heated  air  shall  be  fabricated  of 
noncombustible  materials. 

Exception:  Combustible  ducts  specifically 
tested  and  listed  for  such  purpose. 
3610.6.9.1  Supply  duct  clearance  to 
combustibles:  Supply  ducts  conveying  heated 
air  shall  have  a  clearance  to  combustibles  of 
not  less  than  1 2  inches  for  the  first  ten  feet  of 
distance  from  the  appliance  plenum/bonnet. 

Exception:   ducts  specifically  tested  and 

listed  for  such  purpose. 

3610.6.10  Multiple  flue  connections:  A  solid 
fuel-burning  appliance  and  a  fossil  fuel-burning 
appliance  shall  not  be  vented  into  a  common  flue 
of  a  masonry  chimney  unless  such  common 
connection  is  allowed  by  248  CMR  or  527  CMR 
as  applicable.  If  allowed,  the  common  flue  shall 
be  of  such  size  to  serve  all  appliances  connected 
if  such  appliances  were  operated  simultaneously. 

Note  that  248  CMR  and  527  CMR  are 
enforced  by  Gas  Inspectors  and  the  Heads  of 
Fire  Departments,  respectively. 

3610.6.10.1  Multiple  flue  connections  not 
allowed:  A  solid  fuel-burning  appliance  shall 
not  share  a  common  flue  with  a  working 
fireplace  nor  with  another  solid  fuel-burning 
appliance  (also  see  780  CMR  3610.6.10 
above). 

Exception:  780  CMR  3610.6.6. 

3610.6.11  Used  solid  fuel-burning  appliances  - 
installation  inspection:  Used  solid  fuel-burning 
appliances  that  predate  the  listing  requirements  set 
forth  in  780  CMR  3610  may  be  utilized  but  the 
installation  of  such  appliances  shall  otherwise 
conform  to  the  requirements  of  780  CMR  3610 


2/7/97    Effective  (2/28/97) 


780  CMR  -  Sixth  Edition 


609 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  such  installations  shall  be  inspected  by  the 
Building  Official  (or  Fire  Official  in  such  towns 
that  utilize  the  Fire  Official  for  such  inspection 
purposes). 

3610.6.11.1  Used  solid  fuel-burning 
appliance  clearances  to  combustibles:  In  the 
absence  of  tested,  listed  clearances  and  floor 
protection  requirements,  used  solid  fuel- 
burning  appliances  shall  be  required  to  be 
installed  in  accordance  with  the  clearances  of 
Table  3610.6.1 1.  Floor  protection  requirements 
shall  be  evaluated  by  engineering  methods  or 
otherwise  four  inches  of  %  inch  millboard 
having  a  thermal  conductivity  of : 
k  =  0.84  (Btu)  (inch)  /  (foot2)  (hour)  (°F) 
or  an  equivalent  noncombustible  floor 
protector  of  the  same  overall  thermal 
conductivity  shall  be  required  (also  see 
780  CMR  3610.6.7.1.1). 

Exception  1:    If  tested,  listed  clearances 
and/or  floor  protection  requirements  are 


documentable  for  the  specific  used 
appliance  being  installed,  then  such 
clearances  and/or  floor  protection  may  be 
utilized. 

Exception  2:  If  known  tested,  listed 
clearances  are  greater  than  those  of  Table 
3610.6.11,  then  such  clearances  must  be 
maintained. 

Exception  3:  If  existing  floor  protection 
can  be  demonstrated  to  have  been  adequate 
for  previous  installations  of  said  used  solid 
fuel-burning  appliances  then  such 
previously  utilized  floor  protection  shall  be 
allowed.  If  calculations  demonstrate  that 
the  existing  floor  protection  has  a  thermal 
conductivity  lower  than  that  set  by 
780  CMR  3610.6.11.1  and  adequacy  has 
otherwise  been  demonstrated,  then  the 
existing  floor  protection  must  be 
maintained. 


Table  3610.6.111,2'3 

STANDARD  CLEARANCES  TO  COMBUSTIBLES  FOR  SOLID  FUEL-BURNING 

APPLIANCES 


Appliance  Type 

Clearance 

Above  Top  of 

Appliance 

(inches) 

Clearance  from 

Front  of 

Appliance 

(inches) 

Clearance  from 

Back  of 

Appliance 

(inches) 

Clearance  from 

Sides  of 

Appliance 

(inches) 

Room  Heaters; 
Fireplace  Stoves; 
Combination 

36 

36 

36 

36 

1.  For  reduced  clearance  requirements,  see  780  CMR  3610.  6.8. 1 

2.  Adequate  clearance  for  maintenance  and  cleaning  shall  be  provided. 

3.  Provisions  for  solid  fuel  storage  -  solid  fuel  shall  not  be  stored  any  closer  than  36  inches  from  the  sides, 
front  or  back  of  the  solid  fuel-burning  appliance. 


610 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3611 


MECHANICAL  ADMINISTRATION 
(This  Section  is  Entirely  Unique  to  Massachusetts) 


3611.1   GENERAL 
3611.1.1  Scope.  The  provisions  of  780  CMR  3611 
shall  establish  the  general  scope  of  the  mechanical 
system  and  equipment  requirements  of  780  CMR. 


3611.1.2     Definitions:     General 
provided  in  780  CMR  3612.1 


definitions    are 


3611.1.3  Application:  In  addition  to  the  general 
administration  requirements  of  780  CMR  1,  the 
provisions  of  780  CMR  361 1  -  780  CMR  3622  snail 
apply;  additionally,  in  the  absence  of  specific 
criteria  set  forth  in  such  sections,  the  International 
Mechanical  Code,  as  listed  in  Appendix  A  shall 
apply. 

Note:  This  supplementing  of  the  administrative 
provisions  is  necessary,  in  part,  as  the  regulatory 
requirements  of  other  State  Agencies  legally 
impact  the  design,  installation  and  maintenance  of 
fossil  fuel-fired  appliances;  i.e.,  527  CMR  for  oil- 
fired  appliances  and  248  CMR  for  gas-fired 
appliances  and  specifically  527  CMR  12  as  the 
Massachusetts  Electrical  Code. 


3611.1.4  Conformity;  Conformity  with  the 
applicable  Code  of  Massachusetts  Regulations 
(527  CMR  and  248  CMR)  or  otherwise  with  the 
applicable  provisions  of  780  CMR  361 1  -  780  CMR 
3622  is  required. 

780  CMR  361 1.2  -  EXISTING  MECHANICAL 

SYSTEMS 
3611.2.1  Additions,  alterations,  repairs  or 
replacement:  Additions,  alterations,  repairs  or 
replacement  shall  be  made  to  existing  mechanical 
systems  in  accordance  with  the  requirements  of  the 
applicable  CMR  (527  CMR  or  248  CMR  )  except 
that  in  the  absence  of  other  CMR  regulatory  control, 
in  an  existing  one-  or  two-family  detached  home, 
any  new  mechanical  system  shall  conform  to 
780  CMR  for  new  construction  to  the  fullest  extent 
practical.  However,  individual  components  of  an 
existing  mechanical  system  may  be  repaired  or 
replaced  without  requiring  that  system  to  comply 
with  7S0  CMR  for  new  construction,  provided  such 
component  repair  or  replacement  shall  not  cause  an 
existing  system  to  become  unsafe,  unsanitary  or 
overloaded. 


2/7/97    (Effective  2/2S/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


612  780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3612 


MECHANICAL  DEFINITIONS 


3612.1  GENERAL 

3612.1.1  Scope:  Unless  otherwise  expressly  stated, 
the  following  terms  shall,  for  the  purpose  of 
780  CMR,  have  the  meanings  indicated  in 
780  CMR  3612.1.  Words  used  in  the  present  tense 
include  the  future;  the  singular  number  includes  the 
plural  and  the  plural  the  singular.  Where  terms  are 
not  defined  in  780  CMR  3612.1  and  are  defined  in 
780  CMR  2  they  shall  have  the  meanings  ascribed 
to  them  in  780  CMR  2.  Where  terms  are  not 
defined  in  780  CMR  2  or  780  CMR  3612.1,  they 
shall  have  their  ordinarily  accepted  meanings. 

Note:  Such  definitional  terms  are  provided  to 
establish  a  uniform  technical  language 
consistent  with  definitional  terms  of  527  CMR, 
248  CMR,  NFPA-31,  NFPA-54  and  the 
International  Mechanical  Code,  as  applicable. 

780  CMR  3612.2.1  -  GENERAL 
MECHANICAL  DEFINITIONS 

ACCESSIBLE:  Signifies  access  that  requires  the 
removal  of  an  access  panel  or  similar  removable 
obstruction. 

ACCESSIBLE,  READILY:  Signifies  access 
without  the  necessity  for  removing  a  panel  or 
similar  obstruction. 

AIR  CIRCULATION,  FORCED  A  means  of 
providing  space  conditioning  utilizing  movement 
of  air  through  ducts  or  plenums  by  mechanical 
means 

AER-CONDITIONING  SYSTEM:  An  air- 
conditioning  system  consists  of  heat  exchangers, 
blowers,  filters,  supply,  exhaust  and  return-air 
systems  and  shall  include  any  apparatus  installed 
in  connection  therewith 

ALTERATION:  A  change  in  an  air-conditioning, 
heating,  ventilating  or  refrigeration  system  that 
involves  an  extension,  addition  or  change  to  the 
arrangement,  type  or  purpose  of  the  original 
installation. 

APPLIANCE:  A  device  which  utilizes  fuel  or  other 
forms  of  energy  to  produce  light,  heat,  power, 
refrigeration  or  air-conditioning.  This  definition 
shall  also  include  a  vented  decorative  gas 
appliance  and  decorative  gas  appliances  for 
installation  in  vented  solid-fuel-burning 
fireplaces  Unlisted  gas-fired  log  lighters  shall  not 
be  considered  appliances 


BOILER,  HOT  WATER  HEATING:  A  self- 
contained  appliance  from  which  hot  water  is 
circulated  for  heating  purposes  and  then  returned 
to  the  boiler,  and  which  operates  at  water 
pressures  not  exceeding  160  pounds  per  square 
inch  gage  (psig)  (1 102  kPa  gage)  and  at  water 
temperatures  not  exceeding  250°F  (121  °C)  near 
the  boiler  outlet. 

BRAZED  JOINTS:  A  joint  obtained  by  the  joining 
of  metal  parts  with  metals  or  alloys  that  melt  at  a 
temperature  above  1,000°F  (538°C)  but  lower  than 
the  melting  temperature  of  the  parts  to  be  joined. 

Btu/h:  The  listed  maximum  capacity  of  any 
appliance,  absorption  unit  or  burner  expressed  in 
British  thermal  units  input  per  hour. 

CHIMNEY:  (See  also  "Vent")  One  or  more 
passageways,  vertical  or  nearly  so,  for  conveying 
flue  gases  to  the  outside  atmosphere. 

CHIMNEY  CONNECTOR:  A  pipe  that  connects 
a  fuel-burning  appliance  to  a  chimney. 

CLOSET:  A  small  room  or  chamber  used  for 
storage. 

COMBUSTIBLE  MATERIAL:  Any  material  not 
defined  as  noncombustible. 

COMBUSTION  AER:  The  air  provided  to  fuel- 
burning  equipment  including  air  for  fuel 
combustion,  draft  hood  dilution  and  ventilation  of 
the  equipment  enclosure. 

CONCEALED  GAS  PIPING:  Piping  that  is 
enclosed  in  the  building  construction  without 
means  of  access. 

CONDENSATE:  The  liquid  which  separates  from 
a  gas  due  to  a  reduction  in  temperature,  e.g.,  water 
that  condenses  from  flue  gases  and  water  that 
condenses  from  air  circulating  through  the  cooling 
coil  in  air-conditioning  equipment. 

CONDENSING  APPLIANCE:  An  appliance  that 
condenses  water  generated  by  the  burning  of 
fuels. 

CONDITIONED  AIR:  Air  treated  to  control  its 
temperature,  relative  humidity  or  quality. 

CONDITIONED  SPACE:  The  space  contained 
within  a  building  which  is  conditioned  directly  or 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


613 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


indirectly  by  heating  the  operation  of  a  cooling 
appliance. 

CONFINED  SPACE:  A  room  or  space  having  a 
volume  less  than  50  cubic  feet  per  1,000  Btu/h 
(4X3  LAV)  of  the  aggregate  input  rating  of  all 
fuel-burning  appliances  installed  in  that  space. 

CONTROL,  LIMIT:  An  automatic  control 
responsive  to  changes  in  liquid  flow  or  level, 
pressure,  or  temperature  for  limiting  the  operation 
of  an  appliance. 

CONTROL,  PRIMARY  SAFETY:  A  safety 
control  responsive  directly  to  flame  properties  that 
*  senses  the  presence  or  absence  of  flame  and,  in 
event  of  ignition  failure  or  unintentional  flame 
extinguishment,  automatically  causes  shutdown  of 
mechanical  equipment. 

CONVECTOR:  A  system  incorporating  heating 
element  in  an  enclosure  in  which  air  enters  an 
opening  below  the  heating  element,  is  heated  and 
leaves  the  enclosure  through  an  opening  located 
above  the  heating  element. 

CONVENIENCE  OUTLET, GAS:  A  permanently 
mounted  hand-operated  device  for  connecting  and 
disconnecting  an  appliance  to  the  gas  supply 
piping  conforming  to  AGA  Requirement  7-90. 
The  device  includes  an  integral,  manually 
operated  gas  valve  so  that  the  appliances  can  be 
disconnected  only  when  the  valve  is  in  the  closed 
position. 

DAMPER,  VOLUME:  A  device  that  will  restrict, 
retard  or  direct  the  flow  of  air  in  any  duct,  or  the 
products  of  combustion  of  heat-producing 
equipment,  vent  connector,  vent  or  chimney. 

DECORATIVE  GAS  APPLIANCE,  VENTED:  A 

vented  appliance  installed  for  the  aesthetic  effect 
of  the  flames  rather  than  functional  effects. 

DECORATIVE  GAS  APPLIANCES  FOR 
INSTALLATION  IN  VENTED  SOLID-FUEL- 
BURNING  FIREPLACES:  A  self-contained, 
freestanding,  fuel-gas-burning  appliance  designed 
for  installation  only  in  a  vented  solid-fuel-burning 
fireplace  and  whose  primary  function  lies  in  the 
aesthetic  effect  of  the  flame. 

DILUTION  AIR:  Air  that  enters  a  draft  hood  or 
draft  regulator  and  mixes  with  flue  gases. 

DIRECT-VENT  APPLIANCE:  A  fuel-burning 
appliance  with  a  sealed  combustion  system  that 
draws  all  air  for  combustion  from  the  outside 
atmosphere  and  discharges  all  flue  gases  to  the 
outside  atmosphere. 


DRAFT:  The  flow  of  gases  or  air  through  chimney, 
flue  or  equipment  caused  by  pressure  differences. 
Mechanical  or  induced:  The  draft  developed  by 
fan,  air,  steam  jet  or  other  mechanical  means. 
Natural:  The  draft  developed  by  the  difference  in 
temperature  of  hot  gases  and  outside  atmosphere. 

DRAFT  HOOD:  A  device  built  into  an  appliance,  or 
a  part  of  the  vent  connector  from  an  appliance, 
which  is  designed  to  (1)  provide  for  the  ready 
escape  of  the  flue  gases  from  the  appliance  in  the 
event  of  no  draft,  backdraft  or  stoppage  beyond 
the  draft  hood,  (2)  prevent  a  backdraft  from 
entering  the  appliance,  and  (3)  neutralize  the 
effect  of  stack  action  of  the  chimney  or  gas  vent 
on  the  operation  of  the  appliance. 

DRAFT  REGULATOR:  A  device  which  functions 
to  maintain  a  desired  draft  in  the  appliance  by 
automatically  reducing  the  draft  to  the  desired 
value. 

DUCT  SYSTEM:  A  duct  system  is  a  continuous 
passageway  for  the  transmission  of  air  which,  in 
addition  to  ducts,  may  include  duct  fittings, 
dampers,  plenums,  fans  and  accessory  airhandling 
equipment. 

EQUIPMENT:  A  general  term  including  materials, 
fittings,  devices,  appliances  and  apparatus  used  as 
part  of  or  in  connection  with  installations 
regulated  by  780  CMR  36. 

EVAPORATIVE  COOLER:  A  device  used  for 
reducing  air  temperature  by  the  process  of 
evaporating  water  into  an  airstream. 

EXCESS  AIR:  Air  which  passes  through  the 
combustion  chamber  and  the  appliance  flue  in 
excess  of  that  which  is  theoretically  required  for 
complete  combustion. 

EXHAUST  HOOD,  FULL  OPENING:  An  exhaust 
hood  with  an  opening  at  least  equal  to  the 
diameter  of  the  connecting  vent. 

FACTORY-BUILT  CHIMNEY:  A  chimney 
composed  of  listed  and  labeled  factory-built 
components  assembled  in  accordance  with  the 
manufacturer's  installation  instructions  to  form  the 
completed  chimney. 

FIREPLACE:  A  listed  and  labeled  factory-built  or 
site-built  hearth  and  fire  chamber  constructed  of 
noncombustible  material  for  use  with  solid  fuels 
and  provided  with  a  chimney. 

FIREPLACE  STOVE:  A  freestanding,  chimney- 
connected  solid-fuel-burning  heater  with  or  without 
doors  connected  to  the  chimney. 


614 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/2S/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  MECHANICAL  DEFINITIONS 


FLAME-SPREAD  INDEX:  A  numerical  index 
indicating  the  relative  surface-burning  behavior  of 
a  material  tested  in  accordance  with  ASTM  E  84. 

FLOOR  FURNACE:  A  self-contained  furnace 
suspended  from  the  floor  of  the  space  being 
heated,  taking  air  for  combustion  from  outside 
such  space,  and  with  means  for  lighting  the 
appliance  from  such  space. 

FLUE:  See  "Vent." 

FLUE,  APPLIANCE:  The  passages  within  an 
appliance  through  which  combustion  products 
pass  from  the  combustion  chamber  to  the  flue 
-collar. 

FLUE  COLLAR:  The  portion  of  a  fuel-burning 
appliance  designed  for  the  attachment  of  a  draft 
hood,  vent  connector  or  venting  system. 

FLUE  GASES:  Products  of  combustion  plus  excess 
air  in  appliance  flues  or  heat  exchangers. 

FUEL-PIPING  SYSTEM:  All  piping,  tubing, 
valves  and.  fittings  used  to  connect  fuel  utilization 
equipment  to  the  point  of  fuel  delivery. 

FURNACE,  WARM-AIR:  A  vented  heating 
appliance  designed  or  arranged  to  discharge 
heated  air  into  a  conditioned  space. 

GAS:  Fuel  gas,  such  as  natural  gas,  manufactured 
gas,  undiluted  liquefied  petroleum  gas  (vapor 
phase  only),  liquefied  petroleum  gas-air  mixture 
or  mixtures  of  these  gases. 


GAS        PRESSURE 

"Regulator  " 


REGULATOR 


See 


HEAT  PUMP:  An  appliance  having  heating  or 
heating/cooling  capability  and  which  uses 
refrigerants  to  extract  heat  from  air,  liquid  or 
other  sources. 

HIGH-TEMPERATURE  (H.T.)  CHIMNEY:  A 

high  temperature  chimney  complying  with  the 
requirements  of  UL  103.  A  Type  H.T.  chimney  is 
identifiable  by  the  markings  "Type  H.T."  on  each 
chimney  pipe  section. 

LABELED:  Devices,  equipment  or  materials  to 
which  have  been  affixed  a  label,  seal,  symbol  or 
other  identifying  mark  of  a  testing  laboratory, 
inspection  agency  or  other  organization  concerned 
with  product  evaluation  that  maintains  periodic 
inspection  of  the  production  of  the  above  labeled 
items  which  attests  to  compliance  with  a  specific 
standard 


LISTED  and  LISTING:  Terms  referring  to 
equipment  which  is  shown  in  a  list  published  by 
an  approved  testing  agency  qualified  and 
equipped  for  experimental  testing  and  maintaining 
an  adequate  periodic  inspection  of  current 
productions  and  whose  listing  states  that  the 
equipment  complies  with  nationally  recognized 
standards  when  installed  in  accordance  with  the 
manufacturer's  installation  instructions. 

LOG  LIGHTER,  GAS-FIRED:  An  unlisted 
manually  operated  gas-fired  solid-fuel  ignition 
device  for  installation  in  a  vented  solid-fuel- 
burning  fireplace. 

LOW-PRESSURE  GAS  SUPPLY  SYSTEM:  A 

gas  supply  system  with  gas  pressure  at  or  below 
0.5  psig  (3.44  kPa  gage). 

LP  GAS:  Liquefied  petroleum  gas  composed 
predominately  of  propane,  propylene,  butanes  or 
butylenes,  or  mixtures  thereof  which  are  gaseous 
under  normal  atmospheric  conditions,  but  can  be 
liquefied  under  moderate  pressure  at  normal 
temperatures. 

MANUFACTURER'S  INSTALLATION 

INSTRUCTIONS:  Printed  instructions  included 
with  equipment  as  part  of  the  conditions  of  listing 
and  labeling. 

MASONRY  CHIMNEY:  A  field-constructed 
chimney  of  masonry  units,  bricks,  stones,  labeled 
masonry  chimney  units,  or  reinforced  portland 
cement  concrete,  lined  with  suitable  chimney  flue 
liners. 

MECHANICAL         EXHAUST         SYSTEM 

Equipment  installed  in  a  venting  system  to 
provide  an  induced  draft. 

MEDIUM-PRESSURE  GAS  SUPPLY 

SYSTEMS:  A  gas  supply  system  with  gas  pressure 
exceeding  0.5  psig  (3.44  kPa  gage)  but  not 
exceeding  5  psig  (34  kPa  gage). 

NONCOMBUSTIBLE  MATERIAL  Materials 
that  pass  the  test  procedure  for  defining 
noncombustibility  of  elementary  materials  set  forth 
in  ASTM  E  136. 

NONCONDITIONED  SPACE  A  space  that  is 
isolated  from  conditioned  space  by  insulated  walls, 
floors  or  ceilings. 

PLENUM:  A  chamber  which  forms  part  of  an  air- 
circulation  system  other  than  the  occupied  space 
being  conditioned. 

PURGE:  To  clear  of  air,  gas  or  other  foreign 
substances 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


615 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


QUICK-DISCONNECT  DEVICE:  A  hand- 
operated  device  that  provides  a  means  for 
connecting  and  disconnecting  an  applianceto  a  gas 
supply  and  that  is  equipped  with  an  automatic 
means  to  shut  off  the  gas  supply  when  the  device 
is  disconnected. 

REFRIGERANT:  A  substance  used  to  produce 
refrigeration  by  its  expansion  or  evaporation. 

REFRIGERANT  COMPRESSOR:  A  specific 
machine,  with  or  without  accessories,  for 
compressing  a  given  refrigerant  vapor. 

REFRIGERATING  SYSTEM:  A  combination  of 
interconnected  refrigerant-containing  parts 
constituting  one  closed  refrigerant  circuit  in  which 
a  refrigerant  is  circulated  for  the  purpose  of 
extracting  heat.  In  a  direct  cooling  system,  the 
refrigeration  is  circulated  through  a  heat 
exchanger  located  in  an  air  passage.  In  an  indirect 
cooling  system,  a  secondary  working  fluid  is 
cooled  by  the  refrigerating  system  and  circulated 
through  a  heat  exchanger  located  in  an  air 
passage. 

REGULATOR:  A  device  for  reducing,  controlling 
and  maintaining  the  pressure  in  a  portion  of  a 
piping  system  downstream  of  the  device. 

REGULATOR  VENT:  The  opening  in  the 
atmospheric  side  of  the  regulator  housing 
permitting  the  movement  of  air  to  compensate  for 
the  movement  of  the  regulator  diaphragm. 

RETURN  AER:  Air  removed  from  a  conditioned 
space  through  openings,  ducts,  plenums  or 
concealed  spaces  to  the  heat  exchanger  of  a 
heating,  cooling  or  ventilating  system. 

ROOM  HEATER:  A  freestanding  heating 
appliance  installed  in  the  space  being  heated  and 
not  connected  to  ducts. 

SERVICE  PIPING:  The  piping  and  equipment 
between  the  street  gas  main  and  the  gas-piping 
system  inlet,  which  is  installed  by  and  is  under  the 
control  and  maintenance  of  the  serving  gas 
supplier. 

SMOKE-DEVELOPED  RATING:  A  numerical 
index  indicating  the  relative  density  of  smoke 
produced  by  burning  assigned  to  a  material  tested 
in  accordance  with  ASTM  E  84. 

SUPPLY  AIR:  Air  delivered  to  a  conditioned  space 
through  ducts  or  plenums  from  the  heat  exchanger 
of  a  heating,  cooling  or  ventilating  system. 

TYPE  B  VENT:  A  listed  and  labeled  vent 
conforming  to  UL  44 1  for  venting  gas  appliances 


with  draft  hoods  and  other  gas  appliances  listed 
for  use  with  Type  B  vents. 

TYPE  BW  VENT:  A  listed  and  labeled  vent 
conforming  to  UL  1  441  for  venting  gas-fired 
vented  wall  furnaces  listed  for  use  with  Type  BW 
vents. 

TYPE  L  VENT:  A  listed  and  labeled  vent 
conforming  to  UL  641  for  venting  oil-burning 
appliances  listed  for  use  with  Type  L  vents  or 
with  listed  gas  appliances. 

UNUSUALLY      TIGHT      CONSTRUCTION: 

Construction  in  which: 

1 .  Walls  and  ceilings  exposed  to  the  outside 
atmosphere  have  a  continuous  water  vapor 
retarder  with  a  rating  of  one  perm  [57.4  ng/(s- 
m2  Pa)]  or  less  with  openings  gasketed  or 
sealed,  and 

2.  Weatherstripping  has  been  added  on 
openable  windows  and  doors,  and 

3.  Caulking  or  sealants  are  applied  to  areas 
such  as  joints  around  window  and  door  frames 
between  sole  plates  and  floors,  between  wall- 
ceiling  joints,  between  wall  panels,  at 
penetrations  for  plumbing,  electrical  and  gas 
lines,  and  at  other  openings. 

VENT:  A  passageway  for  conveying  flue  gases  from 
fuel-fired  appliances,  or  their  vent  connectors,  to 
the  outside  atmosphere. 

VENT  COLLAR:  see  "flue  collar." 

VENT  CONNECTOR:  That  portion  of  a  venting 
system  which  connects  the  flue  collar  or  draft 
hood  of  an  appliance  to  a  vent. 

VENT  DAMPER  DEVICE,  AUTOMATIC:  A 

device  intended  for  installation  in  the  venting 
system,  in  the  outlet  of  or  downstream  of  the 
appliance  draft  hood,  of  an  individual, 
automatically  operated  fuel-burning  appliance  and 
which  is  designed  to  automatically  open  the 
venting  system  when  the  appliance  is  in  operation 
and  to  automatically  close  off  the  venting  system 
when  the  appliance  is  in  a  standby  or  shutdown 
condition. 

VENT  GASES:  Products  of  combustion  from  fuel- 
burning  appliances,  plus  excess  air  and  dilution 
air,  in  the  venting  system  above  the  draft  hood  or 
draft  regulator. 

VENTED  GAS  APPLIANCE  CATEGORIES 

The  following  categories  are  used  to  differentiate 
gas  utilization  equipment  according  to  vent 
pressure  and  flue  gas  temperature. 

Category  I.  An  appliance  that  operates  with  a 
nonpositive  vent  connector  pressure  and  with 


616 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  MECHANICAL  DEFINITIONS 

a  flue  gas  temperature  at  least  140°F  (60°C)  VENTILATION:    The   process   of  supplying   or 

above  its  dewpoint.  removing  conditioned  or  unconditioned  air  by 

Category  n.  An  appliance  that  operates  with  natural  or  mechanical  means  to  or  from  any  space, 
a  nonpositive  vent  connector  pressure  and  with 

a  flue  gas  temperature  less  than  140°F  (60  °C)  VENTING:  Removal  of  combustion  products  to  the 

above  its  dewpoint.  outdoors. 
Category  III.  An  appliance  that  operates  with 

a  positive  vent  pressure  and  with  a  flue  gas  WATER  HEATER:  A  closed  vessel  in  which  water 

temperature  at  least  140°F  (60  °C)  above  its  is  heated  by  the  combustion  of  fuels,  electricity  or 

dewpoint.  other   energy   source   and   withdrawn   for   use 

Category  TV.  An  appliance  that  operates  with  external  to  the  vessel  at  pressures  not  exceeding 

a  positive  vent  pressure  and  with  a  flue  gas  160  psig  (1102  kPa  gage),  including  the  apparatus 

temperature  less  than  140°F  (60°C)  above  its  by  which  heat  is  generated  and  all  controls  and 

dewpoint.  devices  necessary  to  prevent  water  temperatures 

from  exceeding  210°F  (99°C). 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  6 1 7 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


61 8  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3613 


GENERAL  MECHANICAL  SYSTEM  REQUIREMENTS 

(This  Section  is  Entirely  Unique  to  Massachusetts) 


3613.1  GENERAL 

3613.1.1  Scope:  The  provisions  of  780  CMR  3613.0 
shall  govern  the  installation  of  mechanical  systems 
not  specifically  addressed  elsewhere  in  780  CMR 
36. 

780  CMR  3613.2  APPROVAL 
3613.2.1  Heating  and  cooling  appliances:  Fossil- 
fueled  heating  and  cooling  appliances  shaii  be  listed 
and  bear  the  label  of  an  approved  agency  in 
accordance  with  the  requirements  of  527  CMR  or 
248  CMR  as  applicable,  other  heating  and  cooling 
appliances  not  under  the  jurisdictional  control  of 
527  CMR  or  248  CMR  shall  be  provided  with  listing 
labeling  information  as  set  forth  in  780  CMR 
3613.3.1,  3613.3.2,  or  3613.3.3'as  applicable  or 
otherwise  be  approved  by  the  BBRS  when  such 
approval  is  necessary. 

Note:    for    solid    fuel-burning    appliances,    see 
780  CMR  3610. 

780  CMR  36133  LABELING  OF 

EQUIPMENT  NOT  UNDER  THE  CONTROL 

OF  527  CMR  OR  248  CMR 

3613.3.1  General:  All  appliances  shall  bear  a 
permanent  and  legible  factory-applied  label  which 
shall  include  the  following  information: 

1.  Name  or  trademark  of  the  manufacturer 

2.  The  model  and  serial  number. 

3.  Identity  of  the  agency  certifying  compliance 
of  equipment  with  approved  standards. 

4.  Clearances  from  combustible  construction  for 
heat-producing  appliances. 

3613.3.2  Fuel-burning  appliances:  The  listing  and 
label  for  fuel-burning  appliances,  except  wood 
stoves  and  fireplaces  (for  solid  fuel-burning 
appliances  and  fireplaces  see  780  CMR  3610.1), 
shall  also  indicate: 

1.  The  type  of  fuel  approved  for  use  with  the 
appliance. 

2.  The  input  or  output  ratings. 

3.  Instructions  for  the  lighting  operation  and  shut 
off  of  the  appliance. 

3613.3.3  Other  than    fuel-burning   appliances: 

When  the  design,  installation  and  maintanence  of 
other  than  fuel-burning  appliances  falls  under  the 
jurisdiction  of  780  CMR,  the  listing  and  label  for 
such  appliances  shall  also  indicate: 
1     The  output  rating  in  Btu/h  or  kw. 


2.  The  electrical  rating  in  volts,  amperes  (or 
watts)  and,  for  other  than  single  phase,  the 
number  of  phases. 

3.  The  electrical  rating  in  volts,  amperes  or  watts 
of  each  field-replaceable  electrical  component. 

4.  Amount  and  type  of  refrigerant,  and  factory 
test  pressures  or  pressures  applied  for  heat  pumps 
and  refrigeration  cooling  equipment. 

780  CMR  3613.4  TYPE  OF  FUEL 

3613.4.1  Appliances:  Each  appliance  shall  be 
designed  for  use  with  the  type  of  fuel  to  which  it  is 
to  be  connected.  Appliances  shall  not  be  converted 
from  fuel  specified  on  the  rating  plate  for  use  with  a 
different  fuel  without  conforming  to  the  applicable 
requirements  of  527  CMR  or  248  CMR  for  oil  or 
gaseous  fuels  respectivley  or  otherwise  securing 
approval  from  the  BBRS  for  other  types  of 
appliances. 

780  CMR  3613.5  APPLIANCE  ACCESS 

1305.1  Appliance  access  for  inspection  service, 
repair  and  replacement:  Fossil  fueled  appliances 
shall  conform  to  the  access  requirements  set  fort  in 
527  CMR  or  248  CMR  as  applicable;  additionally, 
all  appliances  shall  be  accessible  for  inspection, 
service,  repair  and  replacement  without  removing 
permanent  construction.  In  the  absence  of 
manufacturer's  listing/installation  requirements, 
thirty  inches  (762  mm)  of  working  space  and 
platform  shall  be  provided  in  front  of  the  control 
side  to  service  an  appliance  not  otherwise  under  the 
jurisdictional  control  of  527  CMR  or  248  CMR  . 

Note:  solid-fuel  burning  appliances  shall  comply 
with  the  applicable  requirements  of  780  CMR 
3610. 

780  CMR  3613.6  CLEARANCES  FROM 
COMBUSTIBLE  CONSTRUCTION 

3613.6.1  Appliance  clearance  Appliances  shall 
comply  with  the  clearance  requirements  of 
527  CMR  or  248  CMR  as  applicable  or:  if  not  under 
the  jurisdictional  control  of  527  CMR  or  248  CMR 
shall  have  clearances  from  combustible  materials  in 
accordance  the  manufacturer's  listing  requirements 
or  in  the  absence  of  such  information,  in  accordance 
with  Figure  3613.6.1  and  Tables  3613.6.1a  and 
3613.6.1b  as  applicable.  Forms  of  protection  with 
ventilated  air  space  shall  conform  to  the  following 
requirements: 


2/7/97  .  (Effective  2/28/97) 


780  CMR -Sixth  Edition 


619 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


1.  Not  less  than  one-inch  (25  mm)  air  space  shall 
be  provided  between  the  protection  and 
combustible  wall  surface. 

2.  Air  circulation  shall  be  provided  by  having 
edges  of  the  wall  protection  open  at  least  one  inch 
(25  mm). 

3.  If  the  wall  protection  is  mounted  on  a  single 
flat  wall  away  from  corners,  air  circulation  shall 
be  provided  by  having  the  bottom  and  top  edges, 
or  the  side  and  top  edges  open  at  least  one  inch 
(25  mm). 

4.  Wall  protection  covering  two  walls  in  a  corner 
shall  be  open  at  the  bottom  and  top  edges  at  least 
one  inch  (25  mm). 


780  CMR  3613.7  APPLIANCE 
ENSTALLATION 

3613.7.1  General:  Fossil  fuel-fired  appliances  shall 
be  installed  in  accordance  with  the  applicable 
requirements  of  527  CMR  or  248  CMR.  The 
installation  of  appliances  not  under  the  jurisdictional 
control  of  527  CMR  or  248  CMR  shall  conform  to 
the  conditions  of  the  manufacturer's  listing/ 
installaion  requirements.  The  manufacturer's 
operating  instructions  shall  remain  attached  to  the 
appliance  or  otherwise  be  provided  to  the  installer 
and  end-user  of  such  appliances. 


FIGURE  3613.6.1  -  REDUCED  CLEARANCE  DIAGRAM 


CONSTRUCTION  USING  COMBUSTIBLE 
MATERIAL  PLASTERED  OR  UNPLASTERED 


SHEET  METAL 
OR  OTHER 
PROTECTION 


Note: 


"A"  equals  the  required  clearance  with  no  protection,  specified  in  Table  3613.6.  la.  "B"  equals  the  reduced 
clearance  permitted  with  Table  3613.6.1b.  The  protection  applied  to  the  construction  using  combustible 
material  shall  extend  far  enough  in  each  direction  to  make  "C"  equal  to  "A". 


620 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
ONE  AND  TWO  FAMILY  DWELLINGS  -  GENERAL  MECHANICAL  SYSTEM  REQUIREMENTS 


TABLE  3613.6.1a 
STANDARD  INSTALLATION  CLEARANCES  FOR  HEATING  APPLIANCE 


CLEARANCE  (inches) 

Above  Top 

From  Front 

From  Back 

From  Sides 

Boilers  and  Water  Heaters: 

Automatic  oil  or  combination  gas  and  oil- 

6 

24 

6 

6 

Automatic  gas- 

6 

18 

6 

6 

Solid- 

6 

48 

6 

6 

Electnc- 

6 

18 

6 

6 

Ccntral  Furnaces: 

Automatic  oil  or  combination  gas  and  oil- 

6 

24 

6 

6 

Automaf.c  gas- 

6 

IS 

6 

6 

Solid- 

18 

48 

18 

18 

Electric- 

6 

18 

6 

6 

Floor  Furnaces 

Automatic  oil  or  combination  gas  and  oil- 

36 

12 

12 

12 

Automatic  eas- 

36 

12 

12 

12 

Room  Heaters: 

Circulating  tvpe: 

Oil  or  solid  fuel- 

36 

24 

12 

12 

Gas- 

36 

24 

12 

12 

Radiant  or  other  type: 

Oil  or  solid  fuel- 

36 

36 

36 

36 

Gas- 

36 

36 

18 

18 

Gas  with  double  metal  or  ceramic  back- 

36 

36 

12 

18 

Fireplace  stove: 

Solid  fuel- 

48 

54 

48 

48 

For  SI:  1  inch  =  25.4  mm. 

1.  Reductions  in  the  required  clearance  shall  be  permitted  in  accordance  with  Table  3613.6.1b. 

2.  Same  clearances  required  from  top  and  sides  of  warm  air  bonnet  or  plenum  of  central  furnaces. 

3.  Room  heaters  shall  be  installed  on  noncombustible  floors. 


TABLE  1306.1b 
REDUCED  CLEARANCES  WITH  SPECIFIED  FORMS  OF  PROTECTION  (inches) 


WHERE  REQUIRED  CLEARANCE  WITH  NO  PROTECTION  IS 

TYPE  OF  PROTECTION 

36                              19                            12 

r> 

CLEARANCE  MAY  BE  REDUCED  TO 

'/z-inch  noncombustible  insulation  board  over  one- 

Wall 

Ceiling 

WaU 

Ceiling 

Wall 

Ceiling 

Wall 

Ceiling 

inch  giass  fiber  or  mineral  wood  butts  with  no  air 
space 

18 

24 

9 

12 

6 

8 

3 

4 

Vj-inch-thick  noncomnustible  insulation  board  with 
ventilated  air  space 

12 

18 

6 

9 

4 

6 

2 

3 

24-gage  sheet  metal  with  ventilated  air  space 

12 

18 

6 

9 

4 

6 

2 

3 

3 'A- inch  thick  masonry  wall  with  air  space 

12 

- 

6 

4 

- 

2 

- 

For  SI:  =  1  inch  =  25.4  mm.  1  pound  per  cubic  foot  =  0.1572  kN/m",  °F  =  1.8°C  +  32,  1  (Btu-inch)/(square  foot  hour- 

°F)=  1.721  W/(m-K). 

Notes: 

1.  Required  clearances  shall  be  measured  as  shown  in  Figure  3613.6.1. 

2.  The  clearance  between  the  appliance  and  the  face  of  the  protection  shall  not  be  reduced  below  that  shown  in  the 
table.  Required  clearances  between  those  shown  in  the  table  may  be  interpolated. 

3.  With  all  clearance  reduction  svstems  using  ventilated  are  space,  air  circulation  shall  be  provided  as  described  in 
780  CMR  3613.6.1. 

4.  Spacers  and  ties  shall  be  noncombustible  and  shall  not  be  used  directly  behind  an  appliance  or  a  connector. 

5.  Mineral  wood  butts  shall  have  a  minimum  density  of  eight  pounds  per  cubic  foot  and  a  minimum  melting  point  of 
L500°F. 

6.  Insulation  material  shall  have  a  thermal  conductivity  of  1 .0  (Btu-in.)/(sq.  ft.-hr°F)  or  less. 

7.  A  single  wall  connector  passing  through  the  masonry  wall  shall  have  at  least  Yi  inch  of  open  ventilated  air  space 
between  the  connector  and  the  masonrv. 


3613.7.1.1  Additional  installation 

requirements/appliances   located   in   garages: 

The  requirements  of  527  CMR  or  248  CMR  shall 
be  met  when  fossil  fueled  heating  and/or  cooling 
appliances    are    to    be    located    in    a    garage; 


additionally,  all  appliances  shall  be  protected 
from  impact  by  automobiles.  Appliances  that 
generate  a  glow,  spark  or  flame  capable  of 
igniting  gasoline  vapors  and  located  in  a  garage 
shall    be  installed  with  burners,  burner  ienition 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


621 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

devices,  or  heating  elements  and  switches  at  least  780  CMR  3613.8  CONTROL  DEVICES 

18  inches  (457  mm)  above  the  floor  level  or  as  3618.8.1  Oil-fired  and  gas-fired  appliances:  See 

further  required  by  527  CMR  or  248  CMR  when  527  CMR  or  248  CMR  as  applicable, 
applicable.  When  such  appliances  are  enclosed  in 

a  separate  compartment  having  access  only  from  36138.2    Electric    duct    heaters:    Electric    duct 

outside  of  the  garage,  such    appliances  may  be  heatgrs  sha],  be  equipped  with  an  automatic  reset  air 

installed  at  floor  level,  provided  that  the  required  QUt|et  temperature-limit  control  that  will  limit  the 

combustion  air  is  taken  from  and  discharged  to  oudet   aif  temPerature   to   no   more  than  200°F 

the  exterior  of  the  garage.  (93  °  C).  The  electric  elements  of  the  heater  shall  be 

equipped   with    fusible   links   or   a    manual    reset 

3613.7.2     Electrical        appliances:        Electrical  temperature-limit    control    that    will    prevent    air 

appliances   shall  be  installed  in  accordance  with  ternperature  ;n  the  immediate  vicinity  of  the  heating 

527  CMR  12.  elements  from  exceeding  25°F  (121  °C). 


622  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3614 


HEATING  AND  COOLING  EQUIPMENT 

(This  Section  is  Entirely  Unique  to  Massachusetts) 


3614.1  GENERAL 

3614.1.1  General:  All  heating  and  cooling 
appliances  that  are  fossil-fuel  fired  shall  conform  to 
the  requirements  of  780  CMR  3614.0. 

Note  1:  Solid  fuel  burning  appliances  shall 
conform  to  the  requirements  of  780  CMR  3610. 

Note  2:  Boilers  and  water  heaters  shall 
additionally  comply  with  the  requirements  of 
248  CMR  and  527  CMR,  as  applicable. 

3614.1.2  Installation:  Heating  and  cooling 
equipment  installation  shall  be  in  accordance  with 
the  specific  requirements  of  527  CMR  for  oil  fired 
equipment  and  248  CMR  for  gas-fired  equipment  or 
otherwise  in  accordance  with  the  general 
requirements  of  780  CMR  36  when  such  equipment 
is  not  under  the  jurisdictional  control  of  527  CMR  or 
248  CMR. 

Note  1:  When  explicit  requirements  of  527  CMR 
and/or  248  CMR  apply,  enforcement  of  such 
explicit  requirements  lies  with  the  Head  of  the 
Fire  Department  of  the  jurisdiction  (or  his 
designee)  for  matters  controlled  under  527  CMR 
and  with  the  Gas  Inspector  of  the  jurisdiction  for 
matters  controlled  under  248  CMR. 

Note  2:  248  CMR  explicitly  regulates  the  size, 
type,  listing  and  installation  criteria  for  gas-fired 
appliances,  associated  connector,  equipment 
venting,  including  chimney  flue  size  and  liner 
criteria  and  combustion  air  and  appliance  venting 
criteria. 

Note  3:  527  CMR  explicitly  regulates  the  size, 
type,  listing  and  installation  criteria  for  oil-fired 
appliances,  associated  connector  piping, 
combustion  air  and  appliance  ventilation  criteria 
and  certain  aspects  of  equipment  venting  criteria 
but  otherwise  defaults  to  780  CMR  for  chimney 
flue  size  and  liner  criteria. 

Note  4:  Where  flue  liner  size  and/or  material  is 
otherwise  not  controlled  by  527  CMR  or 
248  CMR,  flue  size  and  material  type  shall 
conform  to  the  requirements  of  780  CMR  and  the 
appliance  manufacturer's  listing/installation 
requirements. 

3614.1.3  Ventilation  requirements:  See  780  CMR 
3617.1 

3614.1.4  Exhaust   system    requirements:       See 

780  CMR  3618.1. 


3614.1.5  Duct  construction   requirements:   See 

780  CMR  3619.1. 

3614.1.6  Combustion    air    requirements:    See 

780  CMR  3620.1. 

3614.1.7  Chimney  and  vent  requirements:  See 

780  CMR  3  62 1 . 1  and  780  CMR  3610,  generally. 

3614.1.8  Access:  Heating  and  cooling  equipment 
shall  be  located  relative  to  building  construction  and 
other  equipment  in  such  manner  as  to  permit 
maintenance,  servicing  and  replacement.  Refer  to 
the  specific  requirements  of  527  CMR  or  248  CMR 
as  applicable;  otherwise  such  equipment  access  shall 
comply  to  applicable  requirements  of  780  CMR  36 
and  the  manufacturer's  specific  listing/installation 
requirements. 

3614.1.9  Sizing:  Comfort  heating  and  cooling 
equipment  shall  be  sized  according  780  CMR 
3603.21. 

3614.1.10  Heating  and  cooling  equipment  room 
installations:  Refer  to  the  specific  requirements  of 
527  CMR  or  248  CMR  as  applicable  or  otherwise 
such  installations  shall  comply  to  applicable 
requirements  of  780  CMR  36  and  the  manufacturer's 
specific  listing/installation  requirements. 

3614.1.10.1  Additional  installation 

requirements/attic  installations:  Refer  to  the 
specific  requirements  of  527  CMR  or  248  CMR 
as  applicable;  otherwise  such  installations  shall 
comply  to  applicable  requirements  of  780  CMR 
36  and  the  manufacturer's  specific  listing/ 
installation  requirements. 

Note  that  attic  installation  of  heating 
equipment  and  associated  duct/piping  requires 
care  that  heating  system  heat  loss  to  the  attic 
space  does  not  lead  to  roof  winter  ice 
damming.  Materials  acceptable  to  the  building 
official  shall  be  presented  to  demonstrate  that 
heating  system  heat  loss  to  the  attic  space  will 
not  result  in  heat  loss  to  the  space  sufficient  to 
promote  roof  ice  damming.  To  reduce  heat 
loss  to  the  attic  space,  if  the  attic  heating 
system  is  insulated  or  placed  in  an  isolated, 
insulated  space,  such  approach  shall  in  no  way 
violate  manufacturer's  listing  requirements  of 
the  heating  equipment  nor  preclude  proper 
combustion  air,  ventilation  or  exhaust  of  such 
equipment  and/or  space. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


623 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3614.1.10.1.1  Electricity  required:  For  attic 
installations,  a  permanent  electric  outlet  and 
lighting  fixture  shall  be  provided  near  the 
equipment  which  shall  be  controlled  by  a 
switch  and  installed  in  accordance  with 
527  CMR  12.00. 

3614.1.10.2  Additional  installation 
requirements/crawl  space  installations:  Refer  to 
527  CMR  or  248  CMR  as  applicable  or  in  the 
absence  of  such  jurisdictional  guidance, 
equipment  supported  from  the  ground  shall  be 
level  and  firmly  supported  on  frost-protected 
construction  extending  not  less  than  three  inches 
(76  mm)  above  the  adjoining  ground.  Equipment 
suspended  from  the  floor  shall  have  a  clearance  of 
not  less  than  six  inches  (153  mm)  from  the 
ground. 

3614.1.10.2.1  Electricity  required:  A 
permanent  electric  outlet  and  lighting  fixture 
shall  be  provided  near  the  equipment 
controlled  by  a  switch  and  installed  in 
accordance  with  527  CMR  12. 

3614.1.10.3  Additional  installation 
requirements/exterior  installations:  Refer  to  the 
specific  requirements  of  527  CMR  or  248  CMR 
as  applicable,  or  in  the  absence  of  such 
jurisdictional  guidance  such  supports  and 
foundations  shall  prevent  excessive  vibration, 
settlement,  or  movement  of  the  equipment. 
Supports  and  foundations  shall  be  level  and 
conform  to  the  manufacturer's  installation 
instructions  and  be  frost-protected. 


780  CMR  3614.1.11 
boilers: 


Fossil  fired  furnaces  and 


3614.1.11.1  General:  All  fossil-fired  furnaces 
and  boilers  shall  conform  to  the  requirements  of 
527  CMR  or  248  CMR  as  applicable.  Such 
furnaces  and  boilers  shall  not  be  installed  in  a 
room  designed  to  be  used  as  a  storage  closet 
unless  allowed  by  both  the  manufacturer  and  by 
either  527  CMR  or  248  CMR  as  applicable. 
Furnaces  and  boilers  located  in  a  bedroom  or 


bathroom  shall  be  installed  in  a  sealed  enclosure 
such  that  combustion  air  will  not  be  taken  from 
the  living  space  unless  such  furnaces  or  boilers 
are  of  a  direct  vent  type. 

Exception:  Unless  required  by  527  CMR  or 
248  CMR,  direct  vent  furnaces  are  not  required 
to  be  installed  within  an  enclosure. 

3614.1.11.1.1  Clearances:  Refer  to  the 
specific  requirements  of  527  CMR  or 
248  CMR  as  applicable,  or  otherwise 
clearances  to  combustibles  shall  comply  with 
applicable  requirements  of  780  CMR  36  and 
the  manufacturer's  specific  listing/installation 
requirements. 

3614.1.12  Electric  furnaces:  Electric  furnaces  shall 
be  constructed  in  accordance  with  UL  1096.  Electric 
furnaces  shall  be  installed  in  compliance  with 
780  CMR  36,  their  listing,  the  manufacturer's 
installation  instructions  and  527  CMR  12.00. 

780  CMR  3614.2  HEAT  PUMP  EQUIPMENT 
3614.2.1  Heating  elements:  Heat  pump  equipment 
utilizing  supplemental  electric  heating  elements  shall 
have  such  elements  constructed  in  accordance  with 
UL  559  and  installed  in  accordance  with  527  CMR 
12.00. 
3614.2.1  Foundations  and  supports:  Supports 
and  foundations  for  the  outdoor  unit  of  a  heat 
pump  shall  be  raised  at  least  three  inches  (76  mm) 
above  the  ground  to  permit  free  drainage  of 
defrost  water,  shall  conform  to  the  manufacturer's 
installation  instructions  and  be  frost-protected. 

780  CMR  3614-3  REFRIGERATION 
COOLING  EQWPMENT 

3614.3.1  Compliance:  When  applicable, 
refrigeration  cooling  equipment  and  its 
installation  shall  comply  with  M.G.L.  c.  146, 
§§42  through  45 A,  81  and  528  CMR  11. 


624 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  3615 


ELECTRIC  RESISTANCE  HEATING 


780  CMR  3615.1  GENERAL 

3615.1.1  General:  Electric  baseboard  convectors 
shall  be  listed  and  labeled  and  shall  be  installed  in 
accordance  with  the  manufacturer's  installation 
instructions  and  527  CMR  12.00. 

780  CMR  3615.2  RADIANT  HEATING 
SYSTEMS 

3615.2.1  General:  Radiant  heating  systems  shall  be 
listed  and  labeled  and  shall  be  installed  in 
accordance  with  the  manufacturer's  installation 
instructions  and  527  CMR  12.00. 

3615.2.2  Clearances:  Clearances  for  radiant  heating 
panels  or  elements  to  any  wiring,  outlet  boxes,  and 
junction  boxes  used  for  installing  electrical  devices 
or  mounting  lighting  fixtures  shall  comply  with 
manufacturer's  listing  requirements  and  527  CMR 
12.00. 

3615.2.3  Installation  of  radiant  panels  on  wood 
framing:  Radiant  panels  installed  on  wood  framing 
shall  only  be  so  installed  if  so  listed  by  the 
manufacturer  and  additionally  shall  conform  to  the 
following  requirements: 

1.  Heating  panels  shall  be  installed  parallel  to 
framing  members  and  secured  to  the  surface  of 
framing  members  or  mounted  between  framing 
members. 

2.  Panels  shall  be  nailed  or  stapled  only  though 
the  unheated  portions  provided  for  this  purpose 
and  shall  not  be  fastened  at  any  point  closer  than 
Vt  inch  (6.4  mm)  from  an  element. 

3.  Unless  listed  and  labeled  for  field  cutting, 
heating  panels  shall  be  installed  as  complete  units. 

3615.2.4  Installation  of  radiant  panels  in  concrete 
or  masonry:  Radiant  heating  systems  installed  in 
concrete  or  masonry  shall  only  installed  if  so  listed 
by  the  manufacturer  and  additionally  conform  to  the 
following  requirements: 

1.  Radiant  heating  systems  shall  be  identified  as 
being  suitable  for  the  installation  and  shall  be 
secured  in  place  as  specified  in  the  manufacturer's 
installation  instructions. 

2.  Radiant  heating  panels  or  radiant  heating 
panel  sets  shall  not  be  installed  where  they  bridge 


expansion  joints  unless  protected  from  expansion 
and  contraction. 

3615.2.5  Installation  of  radiant  panels  in  gypsum 
assemblies:  Radiant  heating  systems  shall  only  be 
used  in  gypsum  assemblies  when  so  listed  by  the 
manufacturer  and  such  panel  operating  temperatures 
shall  not  exceed  125°F  (52°C). 

3615.2.6  Finish  surfaces:  Finish  materials  installed 
over  radiant  heating  panels  or  systems  shall  be 
installed  in  accordance  with  the  manufacturer's 
installation  instructions.  Surfaces  shall  be  secured  so 
that  nails  or  other  fastenings  do  not  pierce  the 
radiant  heating  elements. 

780  CMR  36153  DUCT  HEATERS 

3615.3.1  General:  Electric  duct  heaters  shall  be 
listed  and  labeled  and  shall  be  installed  in 
accordance  with  the  manufacturer's  installation 
instructions  and  527  CMR  12. 

3615.3.2  Installation:  Electric  duct  heaters  shall  be 
installed  so  that  they  will  not  create  a  fire  hazard. 
Class  I  ducts,  duct  coverings  and  linings  shall  be 
interrupted  at  each  heater  to  provide  the  clearances 
specified  in  the  manufacturer's  installation 
instructions.  Such  interruptions  are  not  required  for 
duct  heaters  listed  and  labeled  for  zero  clearance 
from  combustible  materials.  Insulation  installed  in 
the  immediate  area  of  each  heater  shall  be  classified 
for  the  maximum  temperature  produced  on  the  duct 
surface. 

3615.3.3  Installation  with  heat  pumps  and  air 
conditioners:  Duct  heaters  located  within  four  feet 
(1219  mm)  of  a  heat  pump  or  air  conditioner  shall  be 
listed  and  labeled  for  such  installations.  The  heat 
pump  or  air  conditioner  shall  additionally  be  listed 
and  labeled  for  such  duct  heater  installations. 

3615.3.4  Access:  Duct  heaters  shall  be  accessible  for 
servicing,  and  clearance  shall  be  maintained  to 
permit  adjustment,  servicing,  and  replacement  of 
controls  and  heating  elements  in  accordance  with  the 
manufacturer's  listing/installation  requirements  and 
otherwise  in  accordance  with  any  applicable 
requirements  of  780  CMR  36. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


625 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


626  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3616 


VENTED  FLOOR,  WALL  AND  ROOM  HEATERS 


780  CMR  3616.1  GENERAL 

3616.1.1  General:  Vented  floor  furnaces,  vented 
wall  furnaces  and  room  heaters  shall  conform  to  the 
listing,  design,  installation  and  maintenance 
requirements  of  527  CMR  or  248  CMR  and 
otherwise  shall  be  installed  in  accordance  with 
applicable  requirements  of  780  CMR  36  and  the 
manufacturer's  listing/installation  instructions. 

>  Exception:   Solid  fuel  burning  appliances  shall 
conform  to  the  requirements  of  780  CMR  3610. 

3616.1.2  Clearances:  Vented  floor  furnaces,  vented 
wall  furnaces  and  room  heaters  shall  be  installed  in 
accordance  with  clearance  installation  requirements 
of  527  CMR  or  248  CMR  and  otherwise  installed  in 
accordance  with  the  applicable  requirements  of 
780  CMR  36  and  the  manufacturer's  listing 
/installation  requirements. 

3616.1.3  Location:  Location  of  vented  floor 
furnaces,  vented  wall  furnaces  and  room  heaters 
shall  conform  to  the  requirements  of  527  CMR  or 
248  CMR  and  otherwise  be  installed  in  accordance 
with  the  applicable  requirements  of  780  CMR  36 
and  the  manufacturer's  listing/installation 
requirements. 

3616.1.4  Access:  Access  to  vented  floor  furnaces, 
vented  wall  furnaces  and  room  heaters  shall  be  in 
accordance  with  the  requirements  of  527  CMR  or 
248  CMR  and  otherwise  shall  be  provided  in 
accordance  with  the  applicable  requirements  of 
780  CMR  36  and  the  manufacturer's  listing 
/installation  requirements. 

3616.1.5  Installation:  Vented  floor  furnace,  vented 
wall  furnace  and  room  heater  installations  shall 
conform  to  the  requirements  of  527  CMR  or 
248  CMR  and  otherwise  conform  with  the 
applicable  requirements  of  780  CMR  36  and  the 
manufacturer's  listing/installation  requirements 


780  CMR  3616.2  VENTED  WALL 
FURNACES/ADDITIONAL  REQUIREMENTS 

3616.2.1  Location:  The  location  of  vented  wall 
furnaces  falling  under  the  jurisdiction  of  780  CMR 
3616.1.6  shall  conform  to  the  following 
requirements: 

1.  Vented  wall  furnaces  shall  be  located  not  less 
than  six  inches  (153  mm)  from  adjoining  walls  at 
inside  corners. 

2.  Vented  wall  furnaces  shall  not  be  located 
where  a  door  can  swing  within  12  inches  (305 
mm)  of  the  furnace  air  inlet  or  outlet  and  shall  not 
be  installed  less  than  18  inches  (457  mm)  below 
overhead  projections. 

3616.2.2  Installation:  Vented  wall  furnace 
installations  shall  conform  to  the  following 
requirements: 

1.  Required  wall  thicknesses  shall  be  in 
accordance  with  the  manufacturer's  installation 
instructions. 

2.  Ducts  shall  not  be  attached  to  a  wall  furnace. 
Casing  extensions  or  boots  shall  only  be  installed 
when  listed  as  part  of  a  listed  and  labeled 
appliance. 

780  CMR  3616.3  VENTED  ROOM 
HEATERS/ADDITIONAL  REQLTREMENTS 

3616.3.1  Location:  A  room  heater  shall  be  placed  so 
as  not  to  cause  a  hazard  to  walls,  floors,  curtains  and 
drapes,  or  to  the  free  movement  of  persons. 

3616.3.2  Installation:  Room  heaters  shall  be 
installed  on  noncombustible  floors  or  on  approved 
floor  protectors  for  combustible  floors  (see 
780  CMR  3610).  Such  floor  protectors  shall  be 
constructed  of  noncombustible  materials.  The 
noncombustible  floor  or  floor  protector  shall  extend 
at  least  16"  beyond  the  appliance  on  all  sides  unless 
the  room  heater  manufacturer  has  listing/installation 
requirements  that  allow  for  less  than  an  18" 
extension. 


3616.3.3  Solid-fuel-burning  heaters  See  780  CMR 
3616.10. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


627 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


628  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3617 

VENTILATION  AIR  SUPPLY 

3617.1.1  Ventilation  required:  General  building  a  building  space,   in  which  case  the  ventilation 

ventilation  shall  be  in  accordance  with  780  CMR  criteria,  as  dictated  by  appliance  requirements  shall 

3603.6     unless     specific     appliance     ventilation  apply, 
requirements  impose  greater  ventilation  criteria  on 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  629 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


630  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3618 


EXHAUST  SYSTEMS 


780  CMR3618.1  CLOTHES  DRYER 
EXHAUST 

3618.1.1  General:  Dryer  vent  systems  shall  be 
independent  of  all  other  systems  and  shall  convey 
the  moisture  to  the  outdoors  -  no  dryer  vent  shall 
terminate  in  the  interior  space  of  a  building  unless 
such  dryer  system  is  listed  for  such  application  and 
has  been  approved  by  the  BBRS  if  necessary; 
additionally,  the  following  criteria  shall  be  satisfied: 

1 .  Gas  fired  clothes  dryers  shall  be  installed  in 
accordance  with  the  requirements  of  248  CMR, 
and  such  exhaust  vent  systems  shall  also  have  a 
backdraft  damper  located  on  the  building  interior 
side  of  the  vent  termination  unless  otherwise 
prohibited  by  listing  or  by  248  CMR; 

2.  For  clothes  dryers  generally,  vents  shall  not  be 
connected  with  sheet-metal  screws  or  fastening 
means  which  extend  into  the  vent.  Exhaust  vents 
shall  be  equipped  with  a  backdraft  damper.  Vents 
shall  be  constructed  of  minimum  0.016-inch-thick 
(0.406  mm)  rigid  metal  ducts,  having  smooth 
interior  surfaces  with  joints  running  in  the 
direction  of  air  flow,  except  that; 

3.  Approved  flexible  duct  connectors  may  be 
used  in  connection  with  domestic  dryer  exhausts 
unless  otherwise  prohibited  by  equipment  listing 
or  248  CMR.  Flexible  duct  connectors  shall  not 
be  concealed  within  construction. 

3618.1.2  Exhaust  vent  size:  The  minimum  diameter 
of  the  exhaust  vent  shall  be  in  accordance  with 
780  CMR  3618.1.3,  but  shall  be  at  least  the  diameter 
of  the  appliance  outlet. 

3618.1.3  Length  limitation:  The  maximum  length 
of  a  four-inch  (102  mm)  diameter  exhaust  vent  shall 
not  exceed  25  feet  (7620  mm)  from  the  dryer 
location  to  wall  or  roof  termination,  and  shall 
terminate  with  a  full  opening  exhaust  hood.  A 
reduction  in  maximum  length  of  2.5  feet  (762  mm) 
for  each  45-degree  bend  and  five  feet  (1524  mm)  for 
each  90-degree  bend  shall  apply.  Installations  when 
this  length  is  exceeded  shall  be  installed  in 
accordance  with  the  manufacturer's  installation 
instructions. 


780  CMR  3618.2  RANGE  HOODS 
3618.2.1  General:  Gas-fired  appliances  shall 
conform  to  the  requirements  of  248  CMR  and 
otherwise  all  range  hoods  shall  be  vented  to  the 
outdoors  by  a  single-wall  duct  constructed  of 
galvanized  steel,  stainless  steel  or  copper.  The  duct 
serving  the  hood  shall  have  a  smooth  interior 
surface,  be  substantially  air  tight  and  shall  be 
equipped  with  a  backdraft  damper.  Vents  serving 
range  hoods  shall  not  terminate  in  an  attic  or  crawl 
space  or  areas  inside  the  building  but  shall  vent 
directly  to  the  building  exterior. 

Exception:  Listed  labeled  unvented  range  hoods 
shall  be  allowed  and  shall  be  installed  in 
accordance  with  the  terms  of  their  listing. 

780  CMR  36183  ENSTALLATION  OF 
MICROWAVE  OVENS 

3618.3.1  Installation  of  microwave  oven  over  a 
cooking  appliance:  The  installation  of  a  listed  and 
labeled  cooking  appliance  or  microwave  oven  over 
a  listed  and  labeled  cooking  appliance  shall  conform 
to  the  terms  of  the  upper  appliance's  listing  and  label 
and  the  manufacturer's  installation  instructions. 

780  CMR  3618.4  OVERHEAD 
VENTOATING  HOODS 

3618.4.1  General:  Gas-fired  appliances  shall 
conform  to  the  requirements  of  248  CMR  and 
otherwise  domestic  open-top  broiler  units  shall  be 
provided  with  a  metal  ventilating  hood,  not  less  than 
28  gage,  with  a  clearance  of  not  less  than  'A  inch  (6.4 
mm)  between  the  hood  and  the  underside  of 
combustible  material  or  cabinets.  A  clearance  of  at 
least  24  inches  (610  mm)  shall  be  maintained 
between  the  cooking  surface  and  the  combustible 
material  or  cabinet.  The  hood  shall  be  at  least  as 
wide  as  the  broiler  unit  and  shall  extend  over  the 
.  entire  unit. 

Exception:  Broiler  units  incorporating  an  integral 
exhaust  system,  and  listed  and  labeled  for  use 
without  a  ventilating  hood,  need  not  be  provided 
with  a  ventilating  hood. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


632  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3619 


DUCT  SYSTEMS 


780  CMR  3619.1  DUCT  CONSTRUCTION 

3619.1.1  Materials  -  duct  construction:  Ducts  and 
duct  materials  used  for  a  duct  serving  heating  and 
cooling  equipment  shall  be  fabricated  in  accordance 
with  the  provisions  of  780  CMR  3619.1. 

3619.1.1.1  Above  ground  duct  systems:  Above 
ground  duct  systems  shall  conform  to  the 
following: 

1.  Equipment  connected  to  duct  systems  shall 
have  a  250°F  (121  °C)  temperature  limit 
control. 

2.  Factory-made  air  ducts  shall  be  constructed 
of  Class  1  or  Class  2  materials  as  designated  in 
Table  3619.1.1a.  Class  2  materials  shall  not  be 
used  for  ducts  located  within  the  first  three  feet 
(914  mm)  of  the  bonnet,  plenum  or  casing  of 
the  heating  unit. 

3.  Minimum  thicknesses  of  metal  duct 
material  shall  be  listed  in  Table  3619.1.1b. 
Galvanized  steel  shall  conform  to  ASTM  A 
525. 

4.  Gypsum  products  may  be  used  as  ducts  or 
plenums,  provided  that  the  air  temperature 
does  not  exceed  125°F  (52°C)  and  exposed 
surfaces  are  not  subject  to  condensation. 

5.  Return  ducts,  except  those  portions  directly 
above  the  heating  surface  or  closer  than  two 
feet  (610  mm)  to  the  heating  unit  casing,  shall 
be  constructed  of  materials  having  a  flame- 
spread  rating  not  greater  than  200. 

6.  Structural  areas  between  studs  or  partitions 
to  be  used  as  return  ducts  shall  be  isolated  from 
unused  spaces  with  tight-fitting  stops  of  sheet 
metal,  or  with  wood  not  less  than  2-inch  (5 1 
mm)  nominal  thickness. 

3619.1.1.2  Underground       duct      systems. 

Underground  duct  systems  shall  be  constructed  of 
approved  concrete,  clay,  metal  or  plastic.  The 
maximum  duct  temperature  for  plastic  ducts  shall 
not  be  greater  than  150°F(66°C).  Plastic  pipe  and 
fittings  shall  conform  to  cell  classification  12454- 
B  of  ASTM  D  1248  or  ASTM  D  1784,  and 
external  loading  properties  of  ASTM  D  2412. 

3619.1.2  Factory-made  ducts:  Factory-made  air 
ducts  or  duct  material  shall  be  approved  for  the  use 
intended,  and  shall  be  installed  in  accordance  with 
the  manufacturer's  installation  instructions.  Each 
portion  of  a  factory-made  air  duct  system  shall  bear 


a  listing  and  label  indicating  compliance  with  UL 
181  andUL  181A. 

3619.1.2.1  Duct  insulation  materials:  Duct 
insulation  materials  shall  conform  to  the 
following  requirements: 

1.  Duct  insulation  shall  comply  with  the 
energy  conservation  requirements  of  780  CMR 
3603.21.; 

2.  Duct  coverings  and  linings  shall  have  a 
flame-spread  rating  not  greater  than  25,  and  a 
smoke-developed  rating  not  greater  than  50. 

3.  Duct  coverings  and  duct  linings  shall 
withstand  a  test  temperature  of  250°F  (121  °C) 
minimum. 

4.  Blanket  insulation  and  factory-insulated 
flexible  duct  shall  be  labeled  with  the  R-value, 
flame-spread  rating,  and  smoke-developed 
rating. 

3619.1.2.2  Vibration  isolators:  Vibration 
isolators  installed  between  mechanical  equipment 
and  metal  ducts  shall  be  fabricated  from  approved 
materials  and  shall  not  exceed  ten  inches  (254 
mm)  in  length. 

3619.1.3  Installation:  Duct  installation  shall 
comply  with  780  CMR  3619.1.3.1  through 
3619.1.3.8. 

3619.1.3.1  Duct  sizing:  Supply  and  return  ducts 
shall  be  sized  according  to  ACCA  Manual  D  or 
SMACNA  Installation  Standards  for  Residential 
Heating  and  Air  Conditioning  Systems  or  other 
approved  methods. 

3619.1.3.2  Joints  and  seams.  Joints  of  duct 
systems  shall  be  made  substantially  air  tight  by 
means  of  tapes,  mastics  or  gasketing.  Crimp  joints 
for  round  ducts  shall  have  a  contact  lap  of  at  least 
l'/2  inches  (38  mm)  and  shall  be  mechanically 
fastened  by  means  of  at  least  three  sheet  metal 
screws  equally  spaced  around  the  joint. 

TABLE  3619.1.1a 

CLASSIFICATION  OF  FACTORY-MADE 

Am  DUCTS 


DUCT  CLASS 

MAXIMUM  FLAME 
SPREAD  RATING 

0 
1 

0 
25 

50 

2/7/97    (2/28/97) 


780  CMR  -  Sixth  Edition 


632 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  3619  Lib 
GAGES  OF  METAL  DUCTS  AND  PLENUMS  USED  FOR  HEATING  OR  COOLING 


TYPE  OF  DUCT 

SIZE  (INCHES) 

NOMINAL 

THICKNESS  (inches) 

EQUIVALENT 
GALVANIZED 
SHEET  GAGE 

APPROXIMATE 

ALUMINUM  B.  &  S. 

GAGE 

Round  ducts  and  enclosed 
reccaneular  ducts 

14  or  less 
over  14 

0.016 
0  019 

30 
28 

26 

24 

Exposed  rectangular  ducts 

14  or  less 
over  14 

0.019 
0.022 

28 

26 

24 

For  SI:  1  inch  =  25.4  mm. 


3619.1.3.3  Support:  Metal  ducts  shall  be 
supported  by  one-inch  (2mm)  by  lS-gage  metal 
straps,  12-gage  galvanized  wire  at  intervals  not 
exceeding  ten  feet  (304S  mm).  Nonmetallic  ducts 
shall  be  supported  in  accordance  with  the 
manufacturer's  installation  instructions. 

3619.1.3.4  Firestopping:  Duct  installations  shall 
be  firestopped  in  accordance  with  780  CMR 
3606.2.7. 

3619.1.3.5  Duct  insulation:  Duct  insulation  shall 
be  installed  in  accordance  with  the  following 
requirements: 

1.  .All  ductwork  shall  be  insulated  in 
accordance  with  780  CMR  3603.21. 

2.  Vapor  retarders  with  a  maximum 
permeance  of  0.05  perm  [(2.87  ng/(s  m2  Pa)], 
or  aluminum  foil  with  a  minimum  thickness  of 
two  mils  (0.051  mm),  shall  be  installed  on 
cooling  supply  ducts  that  pass  through 
nonconditioned  spaces  conducive  to 
condensation. 

3.  Exterior  ducts  shall  be  protected  with 
weatherproof  covering  capable  of  ultraviolet 
(UV)  protection. 

4.  Duct  coverings  shall  not  penetrate  a 
firestopped  wall  or  floor. 

3619.1.3.6  Ducts  in  slabs:  Ducts  shall  be  listed 
and  labeled  for  underground  installation.  Metallic 
ducts  not  having  an  approved  protective  coating 
shall  be  completely  encased  in  a  minimum  of  two 
inches  (51  mm)  of  concrete.  Metallic  ducts  having 
an  approved  protective  coating  and  nonmetallic 
ducts  shall  be  installed  in  accordance  with  the 
manufacturer's  installation  instructions. 

3619.1.3.7  Factory-made  air  ducts:  Factory- 
made  air  ducts  shall  not  be  installed  in  or  on  the 
ground,  in  tile  or  metal  pipe,  or  within  masonry  or 
concrete. 

3619.1.3.8  Metal  duct  separation:  Metal  ducts 
shall  be  installed  with  at  least  four  inches  (102 
mm)  separation  from  earth. 

3619.1.4  Under-floor  plenums:  An  under-floor 
space  used  as  a  supply  plenum  shall  conform  to  the 
requirements  of  780  CMR  3619.1.4.  Fuel  gas  lines 
and  plumbing  waste  cleanouts  shall  not  be  located 
within  the  space. 


3619.1.4.1  General:  The  space  shall  be  cleaned  of 
loose  combustible  materials  and  scrap,  and  shall 
be  tightly  enclosed.  The  ground  surface  of  the 
space  shall  be  covered  with  a  moisture  barrier 
having  a  minimum  thickness  of  four  mils  (0,102 
mm). 

3619.1.4.2  Materials:  The  under-floor  space, 
including  the  sidewall  insulation,  shall  be  formed 
by  materials  having  flamespread  ratings  not 
greater  than  200. 

3619.1.4.3  Furnace  connections:  A  duct  shall 
extend  from  the  furnace  supply  outlet  to  not  less 
than  sixinches  (153  mm)  below  the  combustible 
framing.  This  duct  shall  comply  with  the 
provisions  of  780  CMR  3616.2.1.  A 
noncombustible  receptacle  shall  be  installed 
below  the  floor  opening  into  the  plenum  in 
accordance  with  the  following  requirements: 

1.  The  receptacle  shall  be  securely  suspended 
from  the  floor  members  and  shall  not  be  more 
than  18  inches  (457  mm)  below  the  floor 
opening. 

2.  The  area  of  the  receptacle  shall  extend 
three  inches  (76  mm)  beyond  the  opening  on 
all  sides. 

3.  The  perimeter  of  the  receptacle  shall  have 
a  vertical  lip  at  least  one  inch  (25  mm)  high  at 
the  open  sides. 

3619.1.4.4  Access:  Access  to  an  under-floor 
plenum  shall  be  provided  through  an  opening  in 
the  floor  with  minimum  dimensions  of  18  inches 
by  24  inches  (457  mm  by  610  mm). 

3619.1.4.5  Furnace  controls:  Furnace  controls 
shall  conform  to  the  applicable  requirements,  of 
527  CMR  or  248  CMR 

Exception:  For  solid  fuel  burning  appliances 
see  780  CMR  3610. 

780  CMR  3619.2  RETURN  AIR 
3619.2.1  Return  air:  Return  air  shall  be  taken  from 
inside  the  dwelling,  but  may  be  diluted  with  outdoor 


3619.2.2  Required  area:  The  total  unobstructed 
area  of  return  ducts  or  openings  to  a  warm-air 
furnace  shall  be  in  accordance  with  the 
manufacturer's  installation  instructions,  but  not  less 
than  two  square  inches  (1290  mm')  for  each  1,000 


634 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/2S/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  DUCT  SYSTEMS 


Btu/h  (293  W)  input  rating  of  the  furnace.  The 
minimum  unobstructed  total  area  of  the  return  air 
ducts  or  openings  to  a  central  air-conditioning  unit 
and/or  heat  pump  shall  be  in  accordance  with  the 
manufacturer's  installation  instructions,  but  shall  not 
be  less  than  six  square  inches  (3870  mm")  for  each 
1.000  Btu/h  (293  W)  nominal  cooling  output  rating. 

3619.2.3  Prohibited  sources:  Return  air  for  a  warm- 
air  furnace  shall  not  be  taken  from  bathrooms, 
kitchens,  garages  or  other  dwelling  units.  Outdoor 
air  shall  not  be  taken  from  within  ten  feet  (3048  mm) 
of  an  appliance  or  plumbing  vent  outlet  that  is 
located  less  than  three  feet  (914  mm)  above  the  air 
inlet. 

3619.2.4  Inlet  opening  protection:  Outdoor  air 
inlets  shall  be  covered  with  screen  having  no  less 


than  Vi-inch  (6.4  mm)  openings  and  no  greater  than 
'/2-inch  (12.7  mm)  openings. 

780  CIVDR  3619.3  -  SUPPLY  AIR 

3619.3.1  General:  The  minimum  unobstructed  total 
area  of  supply  ducts  from  a  warm-air  furnace  shall 
be  in  accordance  with  the  manufacturer's  installation 
instructions,  but  shall  not  be  less  than  two  square 
inches  (1290  mm2)  for  each  1,000  Btu/h  (293  W) 
input  rating  of  the  furnace.  The  minimum 
unobstructed  total  area  of  the  supply  air  ducts  from 
a  central  air-conditioning  unit  and/or  heat  pump 
shall  be  in  accordance  with  the  manufacturer's 
installation  instructions,  but  shall  not  be  less  than  six 
square  inches  (3870  mm")  for  each  1,000  Btu/h 
(293  W)  nominal  cooling  output  rating.  Dampers, 
grilles  or  registers  installed  for  the  purpose  of 
controlling  the  supply  airflow  shall  not  be 
considered  as  obstructions. 


2/7/97    (2/28/97) 


780  CMR  -  Sixth  Edition 


635 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


636  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  3620 


COMBUSTION  AIR 


3620.1  General:  Combustion  air  requirements  of 
780  CMR  3620  are  intended  to  apply  only  when  the 
requirements  of  248  CMR  or  527  CMR,  as 
applicable,  do  not  apply. 

3620.1.1  Air  supply:  Fuel-burning  equipment 
shall  be  provided  with  a  supply  of  air  for  fuel 
combustion,  draft  hood  dilution  and  ventilation  of 
the  space  in  which  the  equipment  is  installed.  The 
methods  of  providing  combustion  air  in  this 
chapter  do  not  apply  to  direct  vent  appliances, 
listed  cooking  appliances,  refrigerators  and 
domestic  clothes  dryers. 

3620.1.1.1  Buildings  of  unusually  tight 
construction:  In  buildings  of  unusually  tight 
construction,  combustion  air  shall  be  obtained 
from  outside  the  sealed  thermal  envelope.  In 
buildings  of  ordinary  tightness  insofar  as 
infiltration  is  concerned,  all  or  a  portion  of  the 
combustion  air  for  fuel-burning  appliances  may 
be  obtained  from  infiltration  when  the  room  or 
space  has  a  volume  of  50  cubic  feet  per  1,000 
Btu/h  (4.83  LAV)  input. 

3620.1.2  Exhaust  and  ventilation  system:  Air 

requirements  for  operation  of  exhaust  fans, 
kitchen  ventilation  systems,  clothes  dryers,  and 
fireplaces  shall  be  considered  in  determining  the 
adequacy  of  a  space  to  provide  combustion  air. 

3620.1.3  Volume  dampers  prohibited:  Volume 
dampers  shall  not  be  installed  in  combustion  air 
openings. 

3620.1.4  Prohibited  sources:  Combustion  air 
ducts  and  openings  shall  not  connect  appliance 
enclosures  with  space  in  which  the  operation  of  a 
fan  may  adversely  affect  the  flow  of  combustion 
air.  Combustion  air  shall  not  be  obtained  from  an 
area  in  which  flammable  vapors  present  a  hazard. 

3620.1.5  Opening  area:  The  free  area  of  each 
opening  shall  be  used  for  determining  combustion 
air.  Unless  otherwise  specified  by  the 
manufacturer  or  determined  by  actual 
measurement,  the  free  area  shall  be  considered 
75%  of  the  gross  area  for  metal  louvers  and  25% 
of  the  gross  area  for  wood  louvers. 

3620.2  All  air  from  inside  the  building,  general: 

The  requirements  of  780  CMR  3620.2.1  through 
3620.2.3  shall  apply  when  all  combustion  air  is 
taken  from  inside  the  building. 

Note:  also  see  780  CMR  3610,  generally,  for 
fireplaces  and  solid  fuel-burning  appliances. 


3620.2.1  Required  volume:  If  the  volume  of  the 
space  in  which  fuel-burning  appliances  are 
installed  is  greater  than  50  cubic  feet  per  1  ,000 
Btu/h  (4.83  LAV)  of  aggregate  input  rating  in 
buildings  of  ordinary  tightness  insofar  as 
infiltration  is  concerned,  normal  infiltration  shall 
be  regarded  as  adequate  to  provide  combustion 
air.  Rooms  communicating  directly  with  the  space 
in  which  the  appliances  are  installed  through 
openings  not  furnished  with  doors  shall  be 
considered  part  of  the  required  volume. 

3620.2.2  Confined  space:  Where  the  space  in 
which  the  appliance  is  located  does  not  meet  the 
criterion  specified  in  780  CMR  3620.2.1,  two 
permanent  openings  to  adjacent  spaces  shall  be 
provided  so  that  the  combined  volume  of  all 
spaces  meets  the  criterion.  One  opening  shall  be 
within  12  inches  (305  mm)  of  the  top  and  one 
within  12  inches  (305  mm)  of  the  bottom  of  the 
space,  as  illustrated  in  Figure  3620.2.2.  Each 
opening  shall  have  free  area  equal  to  a  minimum 
of  one  square  inch  per  1,000  Btu/h  (2.20  mm2AV) 
input  rating  of  all  appliances  installed  within  the 
space,  but  not  less  than  100  square  inches  (0.064 
m2). 

3620.2.3  Unusually  tight  construction:  If  the 

space  is  of  adequate  volume  in  accordance  with 
780  CMR  3620.2.1  or  3620.2.2,  but  is  within  a 
building  sealed  so  tightly  that  infiltration  air  is  not 
adequate  for  combustion,  combustion  air  shall  be 
obtained  from  outdoors  or  from  spaces  freely 
communicating  with  the  outdoors  in  accordance 
with  780  CMR  3620.3  or  3620.4. 

3620.3  AH  combustion  air  from  outside  the 
building,  general:  The  requirements  of  780  CMR 
3620.3.1  through  3620.3.5  shall  apply  when  all 
combustion  air  is  taken  from  outside  the  building. 

3620.3.1  Outdoor  air:  When  the  space  in  which 
fuel-burning  appliances  are  located  does  not  meet 
the  criterion  for  indoor  air  specified  in  780  CMR 
3620.2,  outside  combustion  Jr  shall  be  supplied 
through  openings  or  ducts,  as  illustrated  in 
Figures  3620.3.1,  3620.3.3a,  3620.3.3b  and 
3620.4.  One  opening  shall  be  within  12  inches 
(305  mm)  of  the  top  of  the  enclosure,  and  one 
within  12  inches  (305  mm)  of  the  bottom  of  the 
enclosure.  Openings  are  permitted  to  connect  to 
spaces  directly  communicating  with  the  outdoors, 
such  as  ventilated  crawl  spaces  or  ventilated  attic 
spaces.  The  same  duct  or  opening  shall  not  serve 
both  combustion  air  openings.  The  duct  serving 
the  upper  opening  shall  be  level  or  extend  upward 
from  the  appliance  space 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


637 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


3620.3.2  Size  of  opening:  When  communicating 
with  the  outdoors  by  means  of  vertical  ducts,  each 
opening  shall  have  a  free  area  of  at  least  one 
square  inch  per  4,000  Btu/h  (0.550  rrurr/W)  of 
total  input  rating  of  all  appliances  in  the  space.  If 
horizontal  ducts  are  used,  each  opening  shall  have 
a  free  area  of  at  least  one  square  inch  per  2,000 
Btu/h  (1.10  mnr/W)  of  total  input  of  all 
appliances  in  the  space.  Ducts  shall  be  of  the 
same  minimum  cross-sectional  area  as  the 
required  free  area  of  the  openings  to  which  they 
connect.  The  minimum  cross-sectional  dimension 
of  rectangular  air  ducts  shall  be  three  inches  (76 
mm). 

3620.3.3  Attic  combustion  air:  Combustion  air 
obtained  from  an  attic  area,  as  illustrated  in  Figure 
3620.3.3a,  shall  be  in  accordance  with  the 
following: 

1.  The  attic  ventilation  shall  be  sufficient  to 
provide  the  required  volume  of  combustion  air. 

2.  The  combustion  air  opening  shall  be 
provided  with  a  metal  sleeve  extending  from 
the  appliance  enclosure  to  at  least  six  inches 
(153  mm)  above  the  top  of  the  ceiling  joists 
and  ceiling  insulation. 

3.  An  inlet  air  duct  within  an  outlet  air  duct 
shall  be  an  acceptable  means  of  supplying  attic 
combustion  air  to  an  appliance  room  provided 
that  the  inlet  duct  extends  at  least  12  inches 
(305  mm)  above  the  top  of  the  outlet  duct  in 
the  attic  space,  as  illustrated  in  Figure 
3620.3.3b. 

4.  The  end  of  ducts  that  terminate  in  an  attic 
shall  not  be  screened. 

3620.3.4  Under-floor       combustion       air: 

Combustion  air  obtained  from  under-floor  areas, 
as  illustrated  in  Figure  3620.3.4,  shall  have  a  free 


opening  area  to  the  outside  equivalent  to  not  less 
than  twice  the  required  combustion  air  opening. 

3620.3.5  Opening  requirements:  Outside 
combustion  air  openings  shall  be  covered  with 
corrosion-resistant  screen  or  equivalent  protection 
having  no  less  than  Vi-inch  (6.4  mm)  openings, 
and  not  greater  than  VS-inch  (12.7  mm)  openings. 

3620.4  Combined  use  of  indoor  and  outdoor  air 
for  combustion,  general:  The  requirements  of  780 
CMR  3620.4.1  through  3620.4.2  shall  apply  when 
required  combustion  air  consists  of  both  indoor  and 
outdoor  air. 

3620.4.1  Supply  method:  When  the  space  in 
which  fuel-burning  appliances  are  located  does 
not  meet  the  criterion  for  indoor  air  specified  in 
780  CMR  3620.2,  combustion  air  supplied  by  a 
combined  use  of  indoor  and  outdoor  air  shall  be 
supplied  through  openings  and  ducts  extending  to 
the  appliance  room  or  to  the  vicinity  of  the 
appliance. 

3620.4.2  Openings   and   supply   ducts:    Two 

openings  for  ventilation  shall  be  located  and  sized 
in  accordance  with  7S0  CMR  3620.2.2.  In 
addition,  there  shall  be  one  opening  directly 
communicating  with  the  outdoors  or  to  such 
spaces  (crawl  space  or  attic)  that  freely 
communicates  with  the  outdoors.  This  opening 
shall  have  free  area  of  at  least  one  square  inch  per 
5,000  Btu/h  (0.440  mm2/W)  of  total  input  of  all 
appliances  in  the  space.  Ducts  shall  be  of  the 
same  minimum  cross-sectional  area  as  the 
required  free  area  of  the  opening.  Ducts 
admitting  outdoor  air  may  be  connected  to  the 
return  air  side  of  the  heating  system. 


638 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  COMBUSTION  AIR 


Figure  3620.2.2 

EQUIPMENT  LOCATED  IN  CONFINED  SPACES  - 

ALL  AIR  FROM  ADJACENT  SPACES  WITHIN  THE  BUILDING 


CHIMNEY  OR  GAS  VENT 


For  SI:    1  square  inch  =  645. 16  mm2,  1  Btu/h  =  0.293 1  W. 

NOTE:  Each  opening  shall  have  a  free  area  of  not  less  than  one  square  inch  per  1,000  Btu/h  of  the  total  input 

rating  of  all  equipment  in  the  enclosure,  but  not  less  than  100  square  inches. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Figure  3620.3.1 

EQUIPMENT  LOCATED  IN  CONFINED  SPACES  - 

ALL  AIR  TAKEN  FROM  OUTDOORS 

J—  CHIMNEY  OR  GAS  VENT 


O 


INLET  AIR  DUCT 


I  I 


i  i       ~r 


For  SI:  1  Btu/h  =  0.2931  W. 

NOTES:  Each  air  duct  opening  shall  have  a  free  area  of  not  less  than  one  square  inch  per  2,000  Btu/h  of  the 

total  input  rating  of  all  equipment  in  the  enclosure. 

FIGURE  3620.3.3a 

EQUIPMENT  LOCATED  IN  CONFINED  SPACES  - 

ALL  AIR  FROM  OUTDOORS  THROUGH  VENTILATED  ATTIC 


VENTILATION  LOUVERS 
(EACH  END  OF  ATTIC) 


INLET  AIR  DUCT 

(ENDS  1  FOOT  ABOVE  FLOOR) 


For  SI:     1  inch  =  25.4  mm,  1  square  inch  =  645. 16  mm",  1  Btu/h  =  0.293 1  W. 

NOTE:  The  inlet  and  outlet  air  openings  shall  each  have  a  free  area  of  not  less  than  one  square  inch  per  4,000 

Btu/h  of  the  total  input  rating  of  all  equipment  in  the  enclosure. 


640 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  COMBUSTION  AIR 

Figure  3620.3.3b 

EQUIPMENT  LOCATED  IN  CONFINES  SPACES  - 

ALL  AIR  FROM  OUTDOORS  THROUGH  VENTILATED  ATTIC 

(Alternative  Method) 


VENTILATION  LOUVERS 
(EACH  END  OF  ATTIC) 


INLET  AIR  OUCT 

(ENDS  WITHIN  1  FOOT  OF  THE  FLOOR) 


For  SI:    1  inch  =  25.4  mm,  1  square  inch  =  645.16  mm2,  1  Btu/h  =  0.2931  W. 

NOTE:  The  inlet  and  outlet  air  openings  shall  each  have  a  free  area  of  not  less  than  one  square  inch  per  4,000 

Btu/h  of  the  total  input  of  all  equipment  in  the  enclosure. 

Figure  3620.4 

EQUIPMENT  LOCATED  IN  CONFINED  SPACES  - 

INLET  AHl  FROM  VENTILATED  CRAWL  SPACE  AND  OUTLET  AIR 

TO  VENTILATED  ATTIC 


CHIMNEY  OR  GAS  VENT 


VENTILATION  LOUVERS 
(EACH  END  OF  ATTIC) 


VENTILATION  LOUVERS  FOR  UNHEATED  CRAWL  SPACE 


For  SI:    1  square  inch  =  645. 16  mm2,  1  Btu/h  =  0.293 1  W. 

NOTE:  The  inlet  and  outlet  air  openings  shall  each  have  a  free  area  of  not  less  than  one  square  inch  per  4,000 

Btu/h  of  the  total  input  of  all  equipment  in  the  enclosure. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


641 


780  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


642  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/07) 


780  CMR  3621 


CHIMNEYS  AND  VENTS 


3621.1  GENERAL 
NOTE  The  requirements  of  780  CMR  3621  are 
to  be  recognized  in  conjunction  with  applicable 
requirements  of  248  CMR  and/or  527  CMR  for 
gas-fired  and  oil-fired  appliances  respectively; 
also  note  that  24S  CMR  is  enforced  by  Gas 
Inspectors  and  527  CMR  is  enforced  by  the  Heads 
of  Fire  Departments 

3621.1.1  Vent  required:  Fuel-burning  appliances 
shall  be  vented  to  the  outside  in  accordance  with 
their  listing  and  label  and  manufacturer's  installation 
instructions.  Venting  systems  shall  consist  of 
approved  chimneys  or  vents,  or  venting  assemblies 
which  are  integral  parts  of  labeled  appliances. 

3621.1.2  Draft  requirements  A  venting  system 
shall  satisfy  the  draft  requirement  of  the  equipment 
in  accordance  with  the  manufacturer's  installation 
instructions  and  shall  be  constructed  and  installed  to 
develop  a  positive  flow  to  convey  combustion 
products  to  the  outside  atmosphere. 

3621.1.3  Inspection  of  chimneys  Before 
connecting  a  vent  connector  to  a  chimney,  the 
chimney  passageway  shall  be  cleaned  and  free  of 
obstructions.  When  inspection  reveals  that  an 
existing  chimney  is  not  safe  for  the  intended 
application,  it  shall  be  rebuilt  to  conform  to 
780  CMR  3610.2  if  the  chimney  is  a  masonry 
chimney  (or  applicable  requirements  of  248  CMR  or 
527  CMR),  lined  or  relined  with  an  approved  liner, 
or  replaced  with  an  approved  vent  or  chimney. 

3621.1.4  Mechanical  draft  systems:  A  mechanical 
draft  system  shall  be  used  only  with  equipment  listed 
and  labeled  for  such  use.  Provision  shall  be  made  to 
prevent  the  flow  of  fuel  to  the  equipment  when  the 
draft  system  is  not  operating.  Forced  draft  systems 
and  all  portions  of  induced  draft  systems  under 
positive  pressure  during  operation  shall  be  designed 
and  installed  so  as  to  prevent  leakage  of  flue  gases 
into  a  building. 

3621.1.5  Direct  vent  appliances:  Direct  vent 
appliances  shall  be  listed  and  labeled  and  shall  be 
installed  in  accordance  with  the  manufacturer's 
installation  instructions 

3621.1.6  Support  Venting  systems  shall  be 
adequately  supported  for  the  weight  of  the  material 
used. 


3621.1.7  Duct  penetrations  Vents  or  vent 
connectors  shall  not  extend  into  or  through  supply 
and  return  air  ducts  or  plenums. 

3621.1.8  Firestopping  Vent  and  chimney 
installations  shall  be  firestopped  in  accordance  with 
780  CMR  3606.2. 7 

3621.1.9  Unused  openings:  Unused  openings  in  any 
venting  system  shall  be  closed  or  capped. 

780  CMR  3621.2  -  VENT  COMPONENTS 

3621.2.1  Draft  hoods:  Unless  otherwise  allowed  by 
24S  CMR  or  527  CMR  as  applicable,  draft  hoods 
shall  be  located  in  the  same  room  or  space  as  the 
combustion  air  openings  for  the  appliances. 

3621.2.2  Vent  dampers:  Vent  dampers  shall  comply 
with  7S0  CMR  3621.2  2.1  and  3621.2  2.2. 

3621.2.2.1  Manually  operated:  Unless 
otherwise  allowed  by  24S  CMR  or  527  CMR  as 
applicable,  manually  operated  dampers  shall  not 
be  installed  except  in  connectors  or  chimneys  of 
solid  fuel-burning  appliances. 

3621.2.2.2  Automatically  operated: 

Automatically  operated  dampers  shall  be  installed 
in  accordance  with  the  requirements  of  24S  CMR 
or  527  CMR  if  applicable  and  otherwise  in 
accordance  with  the  terms  of  their  listing  and 
labtl  and  the  manufacturer's  requirements  and 
shall  be  installed  to  prevent  firing  of  the  burner 
unless  the  damper  is  opened  to  a  safe  position. 
Automatic  dampers  shall  conform  to  ANSI 
Z21.66. 

3621.2.3  Draft  regulators:  For  oil-fired  appliances 
required  to  be  connected  to  a  chimnev,  draft 
regulators  shall  be  provided  as  required  bv 
527  CMR.  Draft  regulators  provided  for  solid-fuel- 
burning  appliances  to  reduce  draft  intensity  shall  be 
installed  and  set  in  accordance  with  the 
manufacturer's  installation  and  operation 
requirements. 

3621.2.3.1  Location:  When  required  by 
248  CMR  or  527  CMR  or  the  manufacturer's 
installation/operation  requirements,  draft 
regulators  shall  be  installed  in  the  same  room  or 
enclosure  as  the  appliance  such  that  no  difference 
in  pressure  between  the  air  at  the  regulator  and  the 
combustion  air  supply  will  exist. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


643 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780CMR362L3  CHIMNEY  AND  VENT 
CONNECTORS 

3621.3.1  Chimney      and      vent      connectors: 

Connectors  shall  be  used  to  connect  fuel-burning 
appliances  to  a  vertical  chimney  or  vent  unless  the 
chimney  or  vent  is  attached  directly  to  the  appliance. 

3621.3.2  Connectors  for  gas  appliances:      See 

248  CMR 

3621.3.3  Connectors  for  oil  and  solid  fuel 
appliances:  For  connector  requirements  for  oil- 
fired  appliances,  see  527  CMR.  For  solid  fuel- 
burning  appliances,  connectors  compatible  with  the 
listed  appliance  shall  be  utilized  and  may  include, 
but  not  be  limited  to  factory-built  chimney  material. 
Type  L  vent  material.  Type  PL  vent  material  or 
single-wall  metal  pipe  having  resistance  to  corrosion 
and  heat,  and  thickness  not  less  than  that  of 
galvanized  steel  as  specified  in  Table  3621.3.3. 

Table  3621.3.3 

THICKNESS  FOR  SLNGLE-WALL 

METAL  PIPE  CONNECTORS 


Diameter  of 
Connector  (in) 

Sheet  Metal 
Gage  Number 

Less  than  6 

26 

6  to  10 

24 

For  SI:  1  inch  =  =25.4  mm 

3621.3.4  Installation  Unless  otherwise  permitted 
by  248  CMR  or  527  CMR  if  applicable,  the 
following  requirements  shall  be  met:  vent  and 
chimney  connectors  shall  be  installed  in  accordance 
with  the  appliance  manufacturer's  installation 
instructions  and  within  the  space  that  the  appliance 
is  located.  Appliances  shall  be  located  as  close  as 
practical  to  the  vent  or  chimney.  Connectors  shall  be 
as  short  and  straight  as  possible  and  installed  with  a 
rise  of  not  less  than  'A  inch  (6.4  mm)  to  the  foot  run. 
Connectors  shall  be  securely  supported  and  joints 
shall  be  fastened  with  sheet  metal  screws  and  rivets. 
Devices  that  obstruct  the  flow  of  flue  gases  shall  not 
be  installed  in  a  connector  unless  listed  and  labeled 
or  approved  for  such  installations. 

3621.3.4.1  Location.  When  the  connector  serving 
a  gas  appliance  with  a  draft  hood  is  located  in 
nonconditioned  space,  that  portion  of  the 
connector  shall  conform  to  the  requirements  of 
248  CMR. 

3621.3.4.2  Floors  ceiling  and  wall  penetrations: 

A  chimney  connector  or  vent  connector  shall  not 
pass  through  any  floor,  ceiling,  wall,  or  partition 
unless  the  connector  is  listed  and  labeled  for  wall 
pass-through,  or  is  routed  through  a  device  listed 
and  labeled  for  wall  pass-through  and  is  installed 
in  accordance  with  the  conditions  of  its  listing  and 
label.  Connectors  for  listed  and  labeled  gas 
appliances    with    draft     hoods,     and    oil-fired 


appliances  listed  and  labeled  for  Type  L  vents, 
passing  through  walls  or  partitions  shall  be  in 
accordance  with  the  following: 

1 .  Type  B  or  Type  L  vent  material  for  gas 
appliances  and  Type  L  vent  material  for  oil 
appliances  shall  be  installed  with  not  less  than 
listed  and  labeled  clearances  to  combustible 
material. 

2.  Single-wall  metal  pipe  shall  be  guarded  by 
a  ventilated  metal  thimble  not  less  than  four 
inches  (102  mm)  larger  in  diameter  than  the 
vent  connector. 

3621.3.4.3  Length:  Unless  otherwise  permitted 
by  248  CMR  or  527  CMR  if  applicable,  the 
horizontal  run  of  an  uninsulated  connector  to  a 
natural  draft  chimney  shall  not  exceed  75%  of  the 
height  of  the  vertical  portion  of  the  chimney 
above  the  connector.  The  horizontal  run  of  a  listed 
connector  to  a  natural  draft  chimney  shall  not 
exceed  100%  of  the  height  of  the  vertical  portion 
of  the  chimney  above  the  connector. 

3621.3.4.4  Size:  A  connector  shall  not  be  smaller 
than  the  flue  collar  of  the  appliance. 

Exception:  When  the  appliance  is  otherwise 
listed  for  such  connector  application  and  the 
respective  requirements  of  248  CMR  or 
527  CMR  if  applicable,  so  allow. 

3621.3.4.5  Clearance:  Connectors  shall  be 
installed  with  clearance  to  combustibles  as  set 
forth  in  NFPA  211,  Section  6-5.1.  Reduced 
clearances  to  combustible  material  shall  be  in 
accordance  with  NFPA  21 1,  Section  6-5.1.2. 

3621.3.4.6  Access:  The  entire  length  of  a 
connector  shall  be  accessible  for  inspection, 
cleaning  and  replacement. 

3621.3.4.7  Fireplace  connection:  An  appliance 
shall  not  be  connected  to  a  chimney  flue  serving 
a  fireplace  unless  the  fireplace  opening  is  sealed 
or  the  chimney  flue  which  vents  the  fireplace  is 
permanently  sealed  below  the  connection.  (Also 
see  780  CMR  3610.6.5.2). 

780  3621.4  VENTS 

3621.4.1  Type  of  vent  required:  Gas-fired  and  oil- 
fired  appliances  shall  be  vented  in  accordance  with 
248  CMR  or  527  CMR  as  applicable.  Solid  fuel- 
burning  appliances  shall  be  vented  in  accordance 
with  the  requirements  of  780  CMR  3610.6.5.2  and 
3610.6.6  and  additionally  in  accordance  with  their 
listing  and  manufacturer's  requirements,  as 
applicable. 

3621.4.2  Termination:  Vent  termination  shall 
comply  with  780  CMR  3621.4.2. 1  and  3621.4.2.6. 

3621.4.2.1  Through  the  roof:  Vents  passing 
through  a  roof  shall  extend  through  flashing  and 
terminate  in  accordance  with  the  manufacturer's 
installation  requirements 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ONE  AND  TWO  FAMILY  DWELLINGS  -  DUCT  SYSTEMS 


3621.4.2.2  Natural  draft  appliances:  Vents  for 
natural  draft  fossil  fuel-fired  appliances  shall 
terminate  at  heights  above  the  highest  connected 
appliance  in  accordance  with  the  requirements  of 
248  CMR  or  527  CMR  as  applicable,  otherwise 
such  vents  shall  terminate  at  least  five  feet  (1524 
mm)  above  the  highest  connected  appliance 
outlet,  and  natural  draft  gas  vents  serving  wall 
furnaces  shall  terminate  at  an  elevation  at  least  12 
feet  (3658  mm)  above  the  bottom  of  the  furnace. 
Also  see  780  CMR  3610  generally. 

3621.4.2.3  Type  B  or  BW  vent:   See  248  CMR. 

3621.4.2.4  Type  L  vent:  For  oil-fired  appliances, 
see  527  CMR  (in  the  absence  of  guidance  from 
527  CMR  such  vents  shall  terminate  not  less  than 
2  feet  (610  mm)  above  any  portion  of  the  building 
within  ten  feet  (3048  mm)). 

3621.4.2.5  Direct    vent     appliances:         See 

248  CMR  or  527  CMR  if  applicable,  otherwise, 
the  vent  terminal  of  a  direct  vent  appliance  with 
an  input  of  50,000  Btu/h  (14  655  W)  or  less  shall 
be  located  not  less  than  nine  inches  (229  mm) 
from  any  opening  through  which  vent  gases  could 
enter  a  building.  The  vent  terminal  of  a  direct 
vent  appliance  having  an  input  exceeding  50,000 
Btu/h  (14  655  W)  shall  be  located  not  less  than  12 
inches  (305  mm)  from  the  opening.  The  bottom 
of  a  vent  terminal  and  an  air  intake  shall  be 
located  at  least  12  inches  (305  mm)  above  grade 
and  in  all  cases  shall  comply  to  manufacturer's 
installation  requirements  when  such  requirements 
exceed  the  criteria  of  780  CMR  3621.4.2.5. 

3621.4.2.6  Mechanical       draft       systems 

Mechanical  draft  systems  other  than  direct  vent 
systems  shall  be  installed  in  accordance  with 
248  CMR  or  527  CMR  if  applicable,  otherwise 
such  svstems  shall  be  installed  in  accordance  with 
their  listing  and  the  manufacturer's  installation 
requirements. 

3621.4.3  Installation:  Type  B,  Type  BW  and 
Type  L  vents  shall  be  installed  in  accordance  with 
the  applicable  requirements  of  248  CMR  or 
527  CMR  and  otherwise  in  accordance  with  the 
terms  of  their  listing  and  label  and  the 
manufacturer's  installation  instructions.  For  venting 
systems  for  listed  and  labeled  Category  II,  111  and 
IV  gas  appliances,  see  248  CMR  and  the 
manufacturer's  installation  instructions. 

3621.4.3.1  Size  of  single  appliance  venting 
systems:  Except  as  otherwise  allowed  by 
248  CMR  or  527  CMR  as  applicable,  an 
individual  vent  for  a  single  appliance  shall  have  a 
cross-sectional  area  equal  to  or  greater  than  the 
area  of  the  connector  to  the  appliance,  but  not  less 
than  seven  square  inches  (45  15  mnr)  except 
where  the  vent  is  an  integral  part  of  a  listed  and 


labeled  appliance.  Also  see  780  CMR  3610 
generally. 

3621.4.3.2  Size  of  multiple-appliance  venting 
systems.  For  gas-fired  and  oil-fired  appliances, 
see  248  CMR  or  527  CMR  as  applicable.  For 
other  appliances  see  780  CMR  3610  generally. 

Note  1:  Connectors  serving  appliances 
operating  under  natural  draft  shall  not  be 
connected  into  any  portion  of  a  mechanical 
draft  system  operating  under  positive  pressure. 
Note  2:  Solid  fuel-burning  appliances  shall 
not  be  connected  to  a  vent  serving  another 
appliance  burning  other  fuels  except  as  noted 
in  780  CMR  3610.6. 10. 

3621.4.3.3  Size    of      solid    fuel    vents:    See 

780  CMR  3610.6.5.2. 

3621.5  MASONRY  AND  FACTORY-BUILT 
CHIMNEYS 

3621.5.1  Masonry  and  factory-built  chimneys  - 
general:  Masonry  and  factory-built  chimneys  shall 
be  built  and  installed  in  accordance  with  780  CMR 
3610. 

3621.5.2  Installation  of  factory-built  chimneys 

Factory-built  chimneys  and  chimney  units  shall  be 
installed  in  accordance  with  the  manufacturer's 
installation  instructions  such  that  flue  gas 
temperatures  in  the  chimney  shall  not  exceed  the 
limits  specified  in  their  listing  and  label.  Factory- 
built  chimneys  for  use  with  wood-burning 
appliances  shall  be  Type  HT  -  Also  see  780  CMR 
3610.3. 

3621.5.3  Masonry  chimney  connection:  Unless 
otherwise  allowed  by  248  CMR  or  527  CMR,  if 
applicable:  a  chimney  connector  shall  enter  a 
masonry  chimney  not  less  than  six  inches  (153  mm) 
above  the  bottom  of  the  chimney,  except  that  if  six 
inches  (153  mm)  are  not  available,  a  cleanout  shall 
be  provided  by  installing  a  capped  tee  in  the 
connector  next  to  the  chimney.  A  connector 
entering  a  masonry  chimney  shall  extend  through, 
but  not  beyond  the  wall  and  shall  be  flush  with  the 
inner  face  of  the  liner.  Connectors,  or  thimbles, 
when  used,  shall  be  firmly  cemented  into  the 
masonry. 

3621.5.4  Size  of  masonry  chimneys:  The  effective 
area  of  a  natural  draft  chimney  flue  for  one 
appliance  shall  not  be  less  than  the  area  of  the 
connector  to  the  appliance.  Chimneys  connected  to 
more  than  one  appliance  shall  not  be  less  than  the 
area  of  the  largest  connector  plus  50%  of  the  areas  of 
additional  vent  connectors  -  also  see  780  CMR 
3610.2.10  and  3610.2.11. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

3621.5.4.1    Size    of   chimney    for    single    gas  3621.5.4.2  Size  of  chimney  for  multiple  gas 

appliance:  See  248  CMR  appliance.  See  248  CMR. 


646  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/2S/97) 


780  CMR  3622 


SOLAR  SYSTEMS 


3622.1  Solar  systems,  general:  780  CMR  3622 
provides  for  construction,  installation,  alteration,  and 
repair  of  equipment  and  systems  utilizing  solar 
energy  to  provide  space  heating  or  cooling,  hot 
water  heating,  and  swimming  pool  heating. 

NOTE  1:  Also  see  energy  conservation 
provisions,  780  CMR  3603. 

NOTE  2:  Solar  systems  shall  conform  to  all 
applicable  requirements  of  248  CMR. 

3622.2  Installation:  Installation  of  solar  energy 
systems  shall  comply  with  780  CMR  3622.2.1 
through  3622.2.7. 

3622.2.1  Access:  Solar  energy  collectors, 
controls,  dampers,  fans,  blowers,  and  pumps  shall 
be  accessible  for  inspection,  maintenance,  repair, 
and  replacement. 

3622.2.2  Roof-mounted  collectors:  The  roof 
shall  be  constructed  to  support  the  loads  imposed 
by  roof-mounted  solar  collectors  .  Roof-mounted 
solar  collectors  that  serve  as  a  roof  covering  shall 
conform  to  the  requirements  for  roof  coverings  in 
780  CMR  3609.  When  mounted  on  or  above  the 
roof  coverings,  the  collectors  and  supporting 
structure  shall  be  constructed  of  noncombustible 
materials  or  fire-retardant-treated  wood  equivalent 
to  that  required  for  the  roof  construction  and  such 
mounting  shall  be  engineered  to  ensure  proper 
structural  support,  unless  the  collector  and 
mounting  design  satisfies  the  criteria  set  forth  in 
Table  3622.2,  including  all  Table  notes. 

3622.2.3  Pressure    and    temperature    relief: 

System  components  containing  fluids  shall  be 
protected  with  pressure-  and  temperature-relief 
valves.  Relief  devices  shall  be  installed  in 
sections  of  the  system  such  that  a  section  cannot 
be  valved  offor  isolated  from  a  relief  device. 
Such  pressure  and. or  pressure-temperature  relief 
devices  shall  conform  to  all  pertinent 
requirements  of  248  CMR  or  ASME  Boiler  and 
Pressure  Vessel  Rules  as  applicable. 


3622.2.4  Vacuum  relief:  System  components  that 
may  be  subjected  to  pressure  drops  below 
atmospheric  pressure  during  operation  or 
shutdown  shall  be  protected  by  a  vacuum-relief 
valve. 

3622.2.5  Protection  from  freezing:  System 
components  shall  be  protected  from  damage  by 
freezing  of  heat-transfer  liquids  at  the  lowest 
ambient  temperatures  during  operation. 

3622.2.6  Expansion  tanks:  Expansion  tanks  in 
solar  energy  systems  shall  be  installed  in 
accordance  with  248  CMR  and  possess  ASME 
Boiler  and  Pressure  Vessel  stamps  if  applicable. 

3622.2.7  Roof  penetrations:  Roof  penetrations 
shall  be  flashed  and  waterproofed  in  accordance 
with  780  CMR  3609. 

3622.3  Labeling:  Labeling  shall  comply  with 
780  CMR  3622.3.1  and  3622.3.2. 

Exception:  Collectors  and/or  thermal  storage 
units  that  are  site-built  except  such  labeling  that 
would  otherwise  be  required  by  state  and/or 
federal  agencies  having  jurisdiction. 

3622.3.1  Collectors:  Collectors  shall  be  listed  and 
labeled  to  show  the  manufacturer's  name,  model, 
serial  number,  collector  weight,  maximum 
allowable  temperatures  and  pressures,  and  the 
type  of  heat  transfer  fluids  allowed 

3622.3.2  Thermal  storage  units:  Pressurized 
thermal  storage  units  shall  be  listed  and  labeled  to 
show  the  manufacturer's  name,  model,  serial 
number,  maximum  and  minimum  allowable 
operating  temperatures  and  pressures,  and  the 
type  of  heat  transfer  fluids  allowed 

3622.4  Prohibited  heat  transfer  fluids:  Flammable 
gases  and  liquids  shall  not  be  used  as  heat  transfer 
fluids. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


647 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  3622.2 

ALLOWABLE  SPANS  FOR  ROOF  RAFTERS 

SUPPORTING  CERTAIN  SOLAR  COLLECTORS 


50LAR                     y/\ol'^ 
COLLECTOR-^/     \       >" 

SOLAR 
COLLECTOR. 1 

Ik      A\oftcr 
//  I        twam 

II     \         3'"Q" 

%0^ 

Cj^jL 

CONDITION  A 

CONDITION  B 

Member 

800  psi  (spruce 

1200  psi  (hemfir  or 

SOOpsi  (spruce  or 

1299  psi  (hemfir  or 

or  better 

better) 

better 

better) 

MAX  SPAN 

MAX  SPAN 

MAX  SPAN 

MAX  SPAN 

LRC 

HRC 

LRC 

HRC 

LRC 

HRC 

LRC 

HRC 

2x6 

12"  o.c. 

9-1 

8-8 

11-3 

10-8 

7-0 

6-9 

8-10 

8-6 

16"  o.c. 

7-11 

7-5   . 

9-9 

9-3 

6-0 

5-10 

7-6 

7-3 

24"  o.c 

6-8 

6-0 

7-11 

7-5 

4-10 

4-9 

6-0 

5-10 

2x8 

12"  o.c. 

12-2 

11-7 

15-1 

14-4 

9-7 

9-3 

12-0 

11-7 

16"  o.c. 

10-6 

10-0 

13-0 

12-4 

8-2 

7-11 

10-3 

9-11 

24"  o.c. 

8-6 

8-1 

10-6 

10-0 

6-5 

6-3 

8-2 

7-11 

2x  10 

12"  o  c. 

15-9 

14-11 

19-6 

18-5 

12-7 

12-1 

15-9 

15-2 

16"  o.c. 

13-6 

12-10 

16-9 

15-10 

10-9 

10-4 

13-5 

12-11 

24"  o.c. 

10-11 

10-5 

13-6 

12-10 

8-6 

8-3 

10-8 

10-4 

2x  12 
12"  o.c. 

19-4 

18-4 

23-11 

22-7 

15-8 

15-0 

19-7 

18-10 

16"  o.c. 

16-8 

15-9 

20-6 

19-5 

13-4 

12-10 

16-9 

16-1 

24"  o.c. 

13-5 

12-9 

16-7 

15-9 

10-8 

10-3 

13-4 

12-10 

CRITICAL  NOTES  TO  TABLE  3622.2 

ALLOWABLE  SPANS  FOR  ROOF  RAFTERS 

SUPPORTING  SOLAR  COLLECTORS 

HOW  TO  USE  TABLE  3622.2: 

1.  Check  to  determine  that  none  of  the  maximum 
conditions  listed  below  are  exceeded  (see  all  Notes) 

a.  maximum  pitch  of  collectors  -  20:12  (60°) 

b.  maximum  collector  weight  -  seven  lbs.  per  sq. 
ft. 

c.  maximum  length  of  collector  -  nine  ft. 

2.  Determine  whether  Condition  A  or  Condition  B 
applies. 

3.  Inspect  roof  rafters  and  determine  their  size, 
spacing  &  type  of  wood.  (Most  are  hemfir  or  better). 

4.  Determine  whether  light  roof  construction  (LRC- 
asphalt,  wood  shingles,  etc.)  or  heavy  roof 
construction  (HRC-slate,  tile  shingles,  etc.)  applies. 
5  Read  allowable  span  from  tables.  Rafter  spans 
are  measured  along  the  horizontal  projection  and 
loads  are  considered  as  applied  on  the  horizontal 
projection. 


ADDITIONAL  CONSTRUCTION  CRITERIA 

Provide  solid  blocking  between  each  panel 
connection  to  roof.  Lag  bolt  or  through  bolt  panel 
connection  to  rafters  or  blocking. 

For  situations  exceeding  any  maximum  condition 
listed  above  or  not  shown  in  Condition  A  or  B,  the 
structure  shall  be  approved  by  a  licensed 
professional  engineer  or  registered  architect 

DESIGN  CRITERIA  (Table  3622.2) 
Strength:  ten  lbs  per  sq.  ft.  (Light  roof  construction- 
LRC)  or  15  lbs.  per  sq.  ft.  (heavy  roof  construction- 
HRC)  as  noted  plus  30  lbs.  per  sq.  ft.  live  load  plus 
load  of  drifting  snow  plus  loads  of  solar  collectors 
determine  fiber  stress. 

Deflection:  For  30  lbs.  per  sq.  ft.  live  load, 
deflection  shall  be  limited  to  span  in  inches  divided 
by  180. 


648 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


APPENDIX  A 


Parti 


REFERENCED  STANDARDS 


The  following  is  a  listing  of  the  standards  referenced  in  780  CMR,  the  effective  date  of  the  standard,  the 
promulgating  agency  of  the  standard  and  the  section(s)  of  780  CMR  that  refer  to  the  standard. 


AA 


Aluminum  Association 
900  19th  Street,  N.W. 
Suite  300 
Washington,  D.C.  20006 


Standard  reference                                                                     _.  . 

Title 
number 

Referenced  in 

780  CMR  Section 

number 

ASM  35-80           Specification  for  Aluminum  Sheet  Metal  Work  in  Building  Construction 
SAS  30-94            Specification  for  Aluminum  Structures 

2002.1,3609.5.2 
..  ..  2002.1,3608.4.3 

AAMA 


American  Architectural  Manufactures  Association 

Suite  310 

1540  Dundee  Road 

Palatine,  IL  60067 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


1402-86 
101-88 


Standard  Specifications  for  Aluminum  Siding,  Soffit  and  Fascia   

Volentary  Specification  for  Aluminum  Prime  Windows  and  Glass  Doors 


1405.3.4 

3606.8.1,  3606.9.1 


AASHTO 


Standard  reference 
number 


American  Association  of  State  Highway  and  Transportation  Officials 

444  North  Capitol  Street,  N.W. 

Suite  225 

Washington,  D.C.  20001 


Referenced  in 

780  CMR  Section 

number 


HB-15-92 


Standard  Specifications  for  Highway  Bridges    1606.1.1 


ACI 


American  Concrete  Institute 
P.O.  Box  19150 
Detroit,  Michigan  48219 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


Building  Code  Requirements  for  Structural  Concrete  . 


Concrete  Code 


1705.4.1,  1705.4.2,  1705.4.3, 
Table  1705.4.4,  1705.4.5, 
1810.2,1821.3.6,1901.1, 

1901.2,  1903.1,  1903.4, 

1903.5.2,  1903.6.2,  1903.6.3, 
1906.1,1906.2,1906.4.2, 

1906.5.1,  1906.6.1,  1906.7, 

1907.1.3,1907.1.4,1908.1, 

1908.2,1908.2.1,  1908.3.1, 

1908.3.4,  1908.5.2,  1908.8.2, 

1910.1,  1910.3.1,  1910.5, 

1910.6.2,  1910.6.5,3604.4.1 

1815.4,  1815.7 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


649 


7S0  CMR     STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Standard  reference 
number 


Title 


Referenced  in 

780  CMR  Section 

number 


318.1-89  Building  Code  Requirements  for  Structural  Plain  Concrcie-with  1992  Revisions.    18i0.2.  1812.3.2, 

1901.2.  1904.1. 

1904  2.1904.3.3. 

360 4  J.  I 

506  2-90  Specification  for  Materials.  Proportioning,  and  Application  of  Shortcrete 191  1.9 


ACI  530/ASCE     Building  Code  Requirements  for  Masonry  Structures 
5  TMS402-95 


ACI  530  1.  Specifications  for  Masonrv  Structures 

ASCE6/TMS 

602-95 


707.3  1705  5,  Table  1705.5. 

1812.3.2.  Table  1812.3.2. 

2101.1.1.2101.1  2.2104.2. 

2104.2.1.2104.3.2104.4. 

2106.3.1,  3604.4. 1,  3606.4. 1 

Table  1705  5. 

2112.1  1 


AFP  A 


American  Forest  and  Paper  Association 
1111  19™  Street,  N\V,  Suite  800 
Washington,  D.C.  20036 


Standard  reference 
number 


Till. 


Referenced  in 

780  CMR  Section 
number 


NDS-91 


(National  Design)  Specification  for  Wood  Construction  Design  Val 
for  Wood  Construction 


AHA 


American  Hardboard  Association 
520  N.  Hicks  Road 
Palatine.  Illinois  60067 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


A135.4-95  Basic  Hardboard   . 

A  135.6-90  Hardboard  Siding  . 


Cellulosic  Fiber  Board 


1405.3.1 

.  1405.3.2.2309.7. 
Table  3607.3.4 

2309  1. 

Table  3606.2  3(a) 


A  ISC 


American  Institute  of  Stee!  Construction,  Inc. 

Suite  3100 

One  East  VVacker  Drive 

Chicago,  Illinois  60601-2001 


Standard 

Referenced  in 

reference 

Title 

"SO  CMR  Section 

number 

number 

ASD-89          Specification  for  Structural  Steel  Buildings  -  Allowable  Stress  Design  and 
Plastic  Design  


LFRD-93        Load   and  Resistance   Factor   Design   Specifications   for  Structural   Steel 
Buildings 

AISC-92         Seismic  Provisions  for  Structural  Steel  Buildings    


Table  1705.3.2.  2203.1. 
2203.5.2208.1 

Table  1705.3.2.2203.1. 

2203.5.2208.1 

2203.2.2203.2.1 


650 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 


AISI 


American  Iron  and  Steel  Institute 
Suite  1300 

1010  17th  Street,  N.W. 
Washington,  D.C.  20036-4700 


Standard  reference 
number 


_. .  Referenced  in 

780  CMR  Section  number 

Criteria  for  Structural  Applications  of  Steel  Cables  for  Buildings 2207.2 

Specification  for  Design  of  Cold-  Formed  Steel  Structural  Members  - 

with  1989  Addendum  2206.1,2206.3  2206.3.1 

Load  and  Resistance  Factor  Design  Specification  for  Cold-Formed 

Steel  Structural  Members  2206.1.  2206.3.  2206.3.1 


AISI-73 

CFSD-ASD-86 


CFSD-LRFD-91 


AITC 


American  Institute  of  Timber  Construction 

Suite  407 

1818  S.E.  Mill  Plain  Blvd. 

Vancouver,  Washington  98684 


Standard  reference 
number 


Referenced  in 
Title  780  CMR  Section 

number 

Standard  for  Heavy  Timber  Construction 2304. 1 

Standard  for  Preservative  treatment  of  Structural  Glued  Laminated  Timber 2313.1.1 

Standard  for  Tongue  and  Groove  Heavy  Timber  Roof  Decking    2304.1 

Standard  Specifications  for  Structural  Glued  Laminated  Timber  of  Softwood 

Species  (Design)  2304. 1 

Standard  Specifications  for  Hardwood  Glued  Laminated  Timber  2304. 1 

Structural  Glued  Laminated  Timber 2304. 1 


108-93 
109-90 
112-93 
117-93 

119-96 
A190.1-92 


ANSI 


American  National  Standards  Institute 

11  West  42nd  Street 

New  York,  New  York  10036 


Standard  reference 
number 


Referenced  in 
Title  780  CMR  Section 

number 

Specifications  for  the  installation  of  Ceramic   Tile  with  Portland  Cement 

Mortar 2105.10, 3607.2 

Installation  of  Ceramic  Tile  with  Organic  Adhesives  or  Water  Cleanable  Tile 

Setting  Epoxy  Adhesive  2105.10.7,  3607.2 

Installation  of  Ceramic  Tile  with  Dry-Set  Portland  Cement  Mortar  or  Latex- 
Portland  Cement  Mortar 2105. 10.1,  2105.10.. 

3607.2 
Installation  of  Ceramic  Tile  with  Chemical  Resistant.  Water  Cleanable  Tile 

Setting  and  Grouting  Epoxy 2105.10.4  3607.2 

Specifications    for    Electrically    Conductive    Ceramic    Tile    Installed   with 

Conductive  Dry-Set  Portland  Cement  Mortar   2105.10., 

Installation  of  Ceramic  Tile  with  Chemical  Resistant  Furan  Mortar  and  Grout 2 105. 10 

Installation  of  Ceramic  Tile  with  Modified  Epoxy  Emulsion  Mortar/Grout 2105.10 

Installation  of  Grout  in  Tilework 2105.10 

Installation  of  Interior  Ccmentitious  Backer  Units 3607.2 

Specifications  for  Dry-Set  Portland  Cement  Mortar 2 105. 10 

Specifications  for  Conductive  Dry-Set  Portland  Cement  Mortar 2105. 10.2.  3607.2. 

Specifications   for  Chemical  Resistant  Water  Cleanable  Tile  Setting  and 

Grouting  Epoxy  and  Water  Cleanable  Tile  Setting  Epoxy  Adhesive    2105.10.4,  3607.2 

Specifications  for  Latex-Portland  Cement  Mortar  2105.10 

Specifications  for  Chemical  Resistant  Furan ■ 2105.10. 

Specifications  for  Ceramic  Tile  Grouts 2105. 10. 

Specifications  for  Modified  Epoxy  Emulsion  Mortar/Grout   2105.10. 

Specification  for  Organic  Adhesives  for  Installation  of  Ceramic  Tile,  Types 

I  and  II   2105.10.7,3607.2. 

Specifications  for  Ceramic  Tile 2105.4.  3607.2. 


A108.1-92 
A108.4-92 
A108.5-92 

A108.6-92 

A  108.7-92 

A108.8-92 
A  108.9-92 
A 108. 10-92 
A 108. 11-90 
Al  18.1-92 
A  118.2-92 
Al  18.3-92 

A 1 18.4-92 
A  118.5-92 
A  118.6-92 
A  118.8-92 
A 136. 1-92 

A137.1-88 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


651 


7S0  CMR:    STATE  BOARD  OF  BUILD[NG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

_      .     .     ,  Referenced  in 

Standard  relerence  _.,,  ->onox/r.c-     . 

.  Title  780  CMR  Section 

number  , 

number 

A208.1-93  Wood  Particleboard 2308. 1.  2308  2, 

3605.3.3.1, 

3606.11.1,3608.3.3.1 

Z97. 1-84  Safety  Performance  Specifications  and  Methods  of  Test  for  Safety  Glazing 

Materials  Used  in  Buildings  2405. 1,  3603.8.3 

Z2 1.66-85  Electrically  Operated  Automatic  Vent  Damper  Devices  for  Use  with  Gas-fired 

Appliances    3621.2.2.2 

NWWDA  Industry  Standard  for  Wood  Window  Units 3606.8. 1 

I.S.2-87 

NWWDA  Industry  Standard  for  Wood  Sliding  Doors 3606.9.1 

I. S. 3-88 


APA 


American  Plywood  Association 
P.O.Box  11700 
Tacoma,  WA  9841 1 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


E30-90 


Design  and  Construction  Guide:  Residential  and  Commercial 3608.3.2.3 


ASCE  American  Society  of  Civil  Engineers 

345  East  47th  Street 
New  York,  NY  10017 

_       .     .     ,,  Referenced  in 

Standard  reference  _...  -ion™«T>c    .- 

,  Title  780  CMR  Section 

number  , 

number 

ASCE  3-84  Specifications  for  the  Design  and  Construction  of  Composite  Slabs 2206.1.1 

ASCE  5/ACI  Building  Code  Requirements  for  Masonry  Structures   707.3,  1705.5, 

530/TMS  402-95  Table  1705.5,  1812.3.2 

Table  1812.3.2, 

2101.1.1,  2101.1.2, 

2104.2,2104.3.2104.4, 

2106.3.1 

ASCE  6/ACI  Specifications  for  Masonry  Structures   2112.1.1 

530. 1/TMS  602-95 

ASCE  7-95  Minimum  Design  Loads  for  Buildings  and  Other  Structures 1604.2,  1605.1 

1611.1.1,  1611.12, 
1611.12.2,  3603.1.2(b) 
ASCE  8-SSD-           Specifications  for  Design  of  Cold-Formed  Stainless  Steel  Structural 
LRFD/ASD-90  Members  2206.1.  2206.3.  2206.3.1 


ASHRAE  American  Society  of  Heating, 

Refrigerating  and  Air  Conditioning  Engineers 
1791  Tullie  Circle,  N.E. 
Atlanta,  Georgia  30329-2305 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


90  1-1989  Energy  Codefor  Commercial  and  High  Rise  Residential  Buildings 1314.5.2 


652 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 

ASME  American  Society  of  Mechanical  Engineers 

345  East  47th  Street 
New  York,  New  York  10017 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


1-81(85)        Scheme  for  Identification  of  Piping  Systems    416.15.3 

.3-93 Chemical  Plant  and  Petroleum  Refinery  Piping   416.15 


ASTM  American  Society  for  Testing  Materials 

1916  Race  Street 
Philadelphia,  Pennsylvania  19103 


Standard  _  , 

_.  ,  Referenced  m 

reterenCe  Tltle  780  CMR  Section  number 


number 


A6-95c         Specification  for  General  Requirements  for  Rolled  Steel  Plates,  Shapes,  Sheet 

Piling,  and  Bars  for  Structural  Use Table  1705.3.2 

A36-94         Specification  for  Structural  Steel 1818.1,  2105.9.5, 

3606.4.14 

A82-95  Specification  for  Steel  Wire,  Plain,  for  Concrete  Reinforcement 2105.9.2  2105.9.5, 

3606.4.14 

A153-95        Specification  for  Zinc  Coating  (Hot  Dip)  on  Iron  and  Steel  Hardware   2105.9.6, 

Table  3606. 14.1 
A167-94a     Specification  for  Stainless  and  Heat-Resisting  Chromium-Nickel  steel  Plate, 

Sheet,  and  Strip 2105.9.2,  2105.9.5, 

2105.9.6,  3604..  14, 
Table  3606. 14.1 
A 185 -94       Specification  for  Steel  Welded  Wire  Fabric,  Plain,  for  Concrete  Reinforcement 

2105.9.4, 2105.9.5 

{Note:  ASTMA256  -  82  has  been  discontinued  and  not  replaced  by  ASTM) 

A252-93       Specification  for  Welded  and  Seamless  Steel  Pipe  Piles    1818.1,  1819.1 

A283-93a     Specification  for  Low  and  Intermediate  Tensile  Strength  Carbon  Steel  Plates 1818.1,  1819.1 

A361-94       Specification  for  Steel  Sheet.  Zinc-Coated  (Galvanized)  by  Hot-Dip  Process  for 

Roofing  and  Siding .' 1507.3.7,  3609.5.2 

A366-91       Specification  for  Steel,  Sheet,  Carbon.  Cold-Rolled  Commercial  Quality 2105.9.5 

A4 16-94a     Specification  for  Steel  Strand,  Uncoated  Seven  Wire  for  Prestressed  Concrete 1821.3.2 

A496-95       Specification  for  Steel  Wire,  Deformed,  for  Concrete  Reinforcement  2105.9.3 

A  497-95      Specification    for    Steel    Welded    Wire    Fabric,    Deformed,    for    Concrete 

Reinforcement 2105.9.4 

A5 10-82       Specification  for  Wire  Rods  and  Course  Round  Wire,  Carbon  Steel 3606.4. 14 

A  525-9 lb    Specification    for    General    Requirements    for    Steel    Sheet,   Zinc    -    Coated 

(Galvanized)  by  the  Hot  -  Dip  Process 2105.9.6, 

Table  3606.14.1, 
3619.1.1.1.3 
A  568-95      Specification  for  Steel  Sheet.  Carbon  and  High  -  Strength,  Low  -  Alloy,  Hot  - 

Rolled  and  Cold  -  Rolled,  General  Requirements  for Table  1705.3.2 

A  572  -94c   Specification  for  High  -  Strength  Low  Alloy  Columbium  -  Vanadium  Steels  of 

Structural  Quality  1818.1 

A  588  -94     Specification  for  High  -  Strength  Low  Alloy  Structural  Steel  with  50  ksi  (345 

Mpa)  Minimum  Yield  Point  to  4  in.  (100  mm)  Thick  1818.1 

A  615  -95c  Specification    for    Deformed    and    Plain    Billet    -    Steel    Bars    for    Concrete 

Reinforcement 2105.9.1 

A  616 -95b  Specification    for    Rail    -    Steel    Deformed    and    Plain    Bars    for    Concrete 

Reinforcement 2105.9. 1 

A  617 -95b   Specification    for   Axle    -    Steel    Deformed    and    Plain    Bars    for   Concrete 

Reinforcement  2105.9.1 

A  641  -92     Specification  for  Zinc-Coated  (Galvanized)  Carbon  Steel  Wire    2105.9.6, 

Table  3606.4.14.1 
A  706  -95b  Specification  for  Low  -  Alloy  Steel  Deformed  Bars  for  Concrete  Reinforcement.  .  .  .    1906.5.2,  2105.9. 1 
A  755  -95     Specification  for  Steel  Sheet,  Metallic  -  Coated  by  the  Hot  -  Dip  Process  and 
Prepaintcd  by  the  Coil  -  Coating  Process  for  Exterior  Exposed  Building 

Products 1507.3.7 

B 10 1-92        Specification  for  Lead  -  Coated  Copper  Sheets 1507.3.7 

2/7/97  (Effective  2/28/97)  780  CMR  -  Sixth  Edition  653 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Standard 
reference 
number 


— . .  Referenced  in 

780  CMR  Section  number 

Specification  for  Aluminum  and  Aluminum-Alloy  Seet  and  Plate 3609.5.2 

Specifiation  for  Hard-Drawn  Copper-Clad  Steel  Wire 3606.4. 14 

Specification  for  Quicklime  for  Structural  Purposes  (Re-approved  1992)    Table  2505.2.  3607.2.2 

Specifications  for  Gypsum  Plasters Table  2505.2,  3607.2.2 

Practice  for  Making  and  Curing  Concrete  Test  Specimens  in  the  Field 1908.3.2 

Specifications  for  Concrete  Aggregates   1906.3,  Table  1907.1.1 

Specifications  for  Structural  Clay  Load-Bearing  Wall  Tile  2105.2, 

Table  3603. 1.2(a) 

Specifications  for  Inorganic  Aggregates  for  Use  in  Gypsum  Plaster Table  2505.2,  3607.2.2 

Specifications  for  Gypsum  Wallboard   Table  2503.2, 

3607.2.3.1 

Specifications  for  Gypsum  Lath  Table  2505.2,  3607.2.2 

Test  Method  for  Compressive  Strength  of  Cylindrical  Concrete  Specimens 1908.3.2 

Specification  for  Concrete  Building  Brick    2105.1.  3602.2 

Specification  for  Structural  Clay  Non-Load-Bearing  Tile   2104.7.3,  2105.2 

Specifications  for  Gypsum  Casting  and  Molding  Plaster Table  2505.2,  3607.2.2 

Specifications  for  Gypsum  Keene's  Cement Table  2505.2,  3607.2.2 

Specifications  for  Building  Brick  (Solid  Masonry  Units  made  from  from  Clay  or 

Shale) 2105.2.  3602.2 

Test  Methods  of  Sampling  and  Testing  Brick  and  Structural  Clay  Tile 21 12.5 

Specifications  for  Calcium  Silicate  Face  Bnck  (Sand  Lime  Brick)   2105.1,  3602.2 

Specifications  for  Gypsum  Sheathing  Board    Table  2503.2, 

Table  3606.2.3(a) 

Hollow  Load-Bearing  Concrete  Masonry  Units  3602.2 

Specifications  for  Ready-Mix  Concrete   1908.5. 1 

Specifications  for  Ceramic  Glazed  Structural  Clay  Facing  Tile,  Facing  Bnck  and 

Solid  Masonry  Units 2105.2 

Nonioad-Beanng  Concrete  Masonry  Units 3602.2 

Solid  Load-Bearing  Concrete  Masonry  Unit 3602.2 

Specification  for  Portland  Cement    1906.2,  1907.1.2.1. 

1907.1.2.2.3,  1908.2.1, 

1908.2.2.  Table  2505.2, 

3604.2.2 

Practice  for  Sampling  Freshly  Mixed  Concrete    1908.3.2 

Specification  for  Finishing  Hydrated  Lime Table  2505.2 

Specification  for  Cellulosic  Fiber  Insulating  Board  2309.1, 

Table  3606.2.3(a) 

Specification  for  Structural  Clay  Facing  Tile 2105.2 

Specification  for  Facing  Brick  (Solid  Masonry  Units  Made  from  Clay  or  Shale) 2105.2.  3602.2 

Test  Method  for  Air  Content  of  Freshly  Mixed  Concrete  by  the  Pressure  Method 1907.1.1 

Specification  for  Air-Entraining  Admixtures  for  Concrete 1906.6  2 

Specification  for  Mortar  for  Unit   2105.7,  3606.7.1.1 

Specification  for  Lightweight  Aggregates  for  Structural  Concrete 1906.3 

Specification  for  Roofing  Slate 1507.2.7,  3609.4.2 

Test  Methods  for  Joint  Treatment  Materials  for  Gypsum  Board  Construction   Table  2503.2 

Specification  for  Joint  Compound  and  Joint  Tape  for  Finishing  Gypsum  Board Table  2503  2, 

3607.2.3.1 

Specification  for  Grout  for  Masonry 2105.11,3606.7.1.1 

Specification  for  Chemical  Admixtures  for  Concrete 1906.6.2 

Specification  for  Marbie  Dimension  Stone  (Exterior)   2105.3 

Specification  for  Nails  for  the  Application  of  Gypsum  Wallboard   Table  2503.2, 

3607.2.3.1 

Specification  for  Structural  Insulating  Formboard  (Cellulosic  Fiber)   2309. 1 

Specification  for  Adhesives  for  Fastening  Gypsum  Wallboard  to  Wood  Framing 3607.2.3. 1 

Specification  for  Limestone  Dimension  Stone   2105.3 

Specification  for  Preformed  Cellular  Polytyrenc  Thermal  Insulation 3604.3.3 

Specification  for  Gypsum  Veneer  Plaster Table  2505.2, 

3607.2.2 

Specification  for  Gypsum  Base  for  Veneer  Plasters Table  2505.2, 

3607.2.2 

Specification  for  Blended  Hydraulic  Cements    1907. 1.2. 1, 

1907.1.2.2.1, 

1907.1.2.2.2.  1908.2.2, 

3604.2.2 


B  209-89 
B  227-80 
C  5  -79, 
C  28-92 
C  31-95 
C  33-93 
C  34-93 

C  35-95 
C  36-92 

C  37-92 
C  39-94 
C  55-95 
t  56-93 
C  59-91 
C  61-95 
C  62-95a 

C  67-94 
C  73-95 
C  79-95 

C  90-85 
C  94-95 
C  126-95 

C129-85 
C 145-85 
C 150-95 


C  172-90 
C  206-84 
C  208-95 

C  212-93 
C216-95a 
C231-91b 
C  260-95 
C  270-95 
C  330-89 
C  406-89 
C  474-94 
C  475-94 

C476-95 
C494-92 
C503-89 
C5 14-94 

C532-88 
C  557-93 
C  568-89 
C  578-87 
C  587-91 

C  588-95 

C  595-95a 


654 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 


Standard 
reference 
number 


j-  ,  Referenced  in 

780  CMR  Section  number 

Specification  for  Granite  Dimension  Stone 2105.3 

Specification  Quartz-  Based  Dimension  Stone 2105.3 

Specification  for  Fly  Ash  and  Raw  or  Calcined  Natural  Pozzolan  for  Use  as  a 

Mineral  Admixture  in  Portland  Cement  Concrete  1502.6.3,  1906.6.3, 

1907.1.2.1 

Specification  for  Slate  Dimension  Stone 2105.3 

Specification  for  Water  -  Resistant  Gypsum  Backing  Board Table  2503.2, 

Table  2505.2, 
3607.2.4.1 

Specification  for  Bonding  Compounds  for  Interior  Plastering Table  2505.2,  3607.2.2 

Specification  for  Non-Load  (Axis)  Bearing  Steel  Studs,  Runners  (Track),  and 

Rigid  Furring  Channels  for  Screw  Application  of  Gypsum  Board   Table  2503.2, 

Table  2505.2. 
3607.2.3.3 
Specification  for  Hollow  Brick  (Hollow  Masonry  Units  Made  from  Clay  or 

Shale) 2105.2,  3602.2 

Specification   for   Concrete   Made  by  Volumetric   Batching   and   Continuous 

Mixing 1908.5. 1 

Specification  for  Prefaced  Concrete  and  Calcium  Silicate  Masonry  Units 2105.1 

Specification  for  Installation  of  Steel  Framing  Members  to  Receive  Screw- 
Attached  Gypsum  Board Table  2504. 1 

Specification  for  High-  Solids  Content,  Cold  Liquid-  Applied  Elastometric 

Waterproofing  Membrane  for  Use  With  Separate  Wearing  Course   1507.3.6 

Specification  for  Installation  of  Interior  Lathing  and  Furring Table  2504. 1 

Specification  for  Application  of  Interior  Gypsum  Plaster   Table  2504. 1 

Specification  for  Application  of  Gypsum  Veneer  Plaster Table  2504.1,  3607.2.2 

Specification  for  Application  of  Gypsum  Base  to  Receive  Gypsum  Veneer 

Plaster  Table  2504. 1,  3607.2.2 

Specification  for  Metal  Lath  (Re-approved  1992)  Table  2505.2,  3607.2.2 

Specification  for   Packaged,   Dry,   Combined  Materials   for  Surface  Bonding 

Mortar ' 1813.3.2.2,  2105.8, 

3604.6.1 
Specification  for  Aggregate  for  Job-Mixed  Portland  Cement-Based  Plasters   ....  Table  2505.2,  3607.2.2 

Specification  for  Application  of  Portland  Cement  Based-Plaster 2506.3 

Specification  for  Surface-Applied  Bonding  Agents  for  Exterior  Plastering Table  2505.2 

Specification  for  Welded  Wire  Lath  (Re-approved  1990)  Table  2505.2,  3607.2.2 

Practice  for  Construction  of  Dry-stacked.  Surface-Bonded  Walls 2105.8,  2106.4 

Specification  for  Steel  Drill  Screws  for  the  Application  of  Gypsum  Board  or 

Metal  Plaster  Bases  to  Steel  Studs  from  0.033  in.  (0.84  mm)  to  0.1 12  in.  (2.84 

mm)  in  Thickness   Table  2503.2,  2505.2, 

3607.2.3.5 
Specification  for  Load  Bearing  (Transverse  and  Axial)  Steel  Studs,  Runners 

(Track),  and  Bracing  or  Bridging  for  Screw  Application  of  Gypsum  and  Metal 

Plaster  Bases Table  2505.2, 

3607.2.3.3 
Specification  for  High-  Solids  Content,  Cold  Liquid-  Applied  Elastometric 

Waterproofing  Membrane  with  Integral  Wearing  Surface 1507.3.6 

Specification  for  Ground  Granulated  Blast  -  Furnace  Slag  for  Use  in  Concrete 

and  Mortars 1906.6.4,  1907.1.2.1, 

1907.1.2.2.2.3607.2.3.1 

Specifications  for  Predecorated  Gypsum  Board 

Specification  for  Drill  Screws  for  the  Application  of  Gypsum  Board  or  Metal 

Plaster  Bases Table  2503.2. 

Table  2505.2, 
3607.2.3.1,3607.2.3.5 
Specification  for  Installation  of  Load  Bearing  (Transverse  and  Axial)  Steel  Studs 

Accessories  and  Related  Accessories   Table  2504. 1 

Specification    for    Spray    -    Applied    Rigid    Cellular    Polyurethane    Thermal 

Insulation 1507.3.5 

Specification  for  Woven  Wire  Plaster  Base  (Re-approvcd  1990)   3607.2.2 

Specification  for  Accessories  for  Gypsum  Wallboard  and  Gypsum  Veneer  Base 

(Re-approved  1990) 3607.2.2,  3607.2.3  1 

Specification  for  Installation  of  Lathing  and  Furring  for  Portland  Cement  -  Based 

Plaster  2506.3.  3607.2.2 


C  615-92 
C  616-95 
C  618-95 


C  629-89 
C  630-95 


C  631 -95a 
C  645-95a 


C  652-95c 

C  685-95 

C  744-95a 
C  754-95a 

C  836-89a 

C  841-90 
C  842-85 
C  843-94 
C844-85 

C847-93 
C887-95 


C897-95a 

C926-95 

C932-85 

C933-85 

C946-91 

C954-93 


C955-95b 


C957-93 
C  989-95 


C960-91 
CI  002-93 


C 1007-83 
CI  029-90 


C1032-86 
C 1047-85 


C 1063-  95a 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


655 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Standard  n  e  .  ■ 

_...  Referenced  in 

refer!nce  Tltle  780  CMR  Sect.on  number 

number 

C1088-94     Specification  for  Thin  Veneer  Brick  Units  Made  from  Clay  or  Shale  2105.2 

D1586 

D25-91  Specification  for  Round  Timber  Piles 1822.1 

D56-93         Test  Method  for  Flash  Point  by  Tag  Closed  Tester  307.2 

D93-94         Test  Methods  for  Flash  Point  by  Pensky-Martens  Closed  Tester Table  307.2 

D224-89       Specification  for  Smooth-  Surfaced  Asphalt  Roll  Roofing  (Organic  Felt) 1507.2.2 

D225-95       Specification   for  Asphalt  Shingles   (Organic  Felt)   Surfaced  With  Mineral 

Granules    '.  1507.2.3 

D226-95       Specification    for   Asphalt-    Saturated    Organic   Felt   Used   in   Roofing    and 

Waterproofing Table  1507.3.1 

D227-95       Specification   for   Coal-Tar    Saturated   Organic   Felt   Used    in   Roofing   and 

Waterproofing Table  1507.3.1 

D2487  

D2488  

D249-89       Specification  for  Asphalt  Roll  Roofing    (Organic  Felt)  Surfaced  with  Mineral 

Granules 1507.2.2 

D2938 

D3 12-95        Specification  for  Asphalt  Used  in  Roofing Table  1507.3. 1, 

3609.7.4.2 

D323-94       Test  Method  for  Vapor  Pressure  of  Petroleum  Products  (Reid  Method) 307.2 

D368  Tension  Load  Test 1801 

D371-89       Specification  for  Asphalt  Roll  Roofing  (Organic  Felt)  Surfaced  with  Mineral 

Granules;  Wide-  Selvage 1507.2.2 

D450-91       Specification    for    Coal-Tar    Pitch    Used    in    Roofing,    Dampproofing,    and 

Waterproofing Table  1507.3. 1 

(Note  568-77  has  been  discontinued  and  not  replaced  by  ASTM) 
D635-91       Test  Method  for  Rate  of  Burning  and/or  Extent  and  Time  of  Burning  of  Self- 

Supporting  Plastics  in  a  Horizontal  Position  2601.2,  2604.1 

Dl  143-81     Test  Method  for  Piles  under  Static  Axial  Compressive  Load 1817.4.2 

D1227-87     Specification  for  Emulsified  Asphalt  Used  as  a  Protective  Coating  for  Roofing 1507.3.6 

D1248-84     Specification  for  Polystyrene  Plastics  Molding  and  Extrusion  Materials 3619.1.1.2 

(1989) 

D1557  Test  methods  for  Moisture-Density  Relations  of  Soils  and  Soil  Aggregate 

Mixtures  Using  10-lb.  (4.54-kg)  Rammer  and  18-in.  (457-mm)  Drop 1804.3.2,  1805.3 

D  1586-84    Method  for  Penetration  Test  and  Split  Barrel  Sampling  of  Soils 1805.3 

D1761-88     Test  Methods  for  Mechanical  Fasteners  in  Wood 2312.1,2312.2,2312.3 

D 1 784-90     Specification  for  Rigid  Poly  (Vinyl  Chloride)  (PFC)  Compounds  and  Chlorinated 

Poly  (Vinyl  Chloride)  (CPVC)  Compounds 3619.1.1.2 

D1863-  86    Specification  for  Mineral  Aggregate  Used  on  Built-Up  Roofs Table  1507.3.1 

D  1929-93     Test  Method  for  Ignition  Properties  of  Plastics   2601.2, 2604.2 

D2 178-89     Specification  for  Asphalt  Glass  Felt  Used  in  Roofing  and  Waterproofing   Table  1507.3.1 

D24 12-87    Test  Method  for  Determination  of  External  Loading  Characteristics  of  Plastic 

Pipe  by  Parallel-Plate  Loading 3619.1.1.2 

D2487  Classification  of  Soils  for  Engineering  Purposes  (Unified  Soil  Classification 

System)  

D2488  Practice  for  description  and  Identification  of  Soils  (Visual-Manual  Procedure)  

D2626-95     Specification  for  Asphalt-Saturated  and  Coated  Organic  Felt  Base  Sheet  Used  in 

Roofing  Table  1507.3.1 

(Note:  D2277-87  has  been  discontinued  and  not  replaced  by  ASTM) 
D2843-93     Test  Method  for  Density  of  Smoke  from  the  Burning  or  Decomposition  of 

Plastics 2601.2, 2604.1 

D2898-94     Methods  for  Accelerated  Weathering  of  Fire-Retardant  Tested  Wood  for  Fire 

Testing 1506.2,  2310.3 

D2938  

D3 161-8 1      Test  Method  for  Wind  Resistance  of  Asphalt  Shingles   1505.2.3 

D3462-93a  Specification  for  Asphalt  Shingles  Made  from  Glass  Felt  and  Surfaced  with 

Mineral  Granules 1507.2.3 

D3468-90     Specification  for  Liquid-  Applied  Neoprene  and  Chlorosulfonated  Polyethylene 

Used  in  Roofing  and  Waterproofing 1507.3.6 

D3672-86     Specification  for  Venting  Asphalt  -  Saturated  and  Coated  Inorganic  Felt  Base 

Sheet  Used  in  Roofing Table  1507.3. 1 

D3679-88     Rigid  Poly  (Vinyl  Chloride)  (PVC)  Siding Table  3607.3.4 

D3689-90     Test  Method  Individual  Piles  under  Static  Axial  Tensile  Load   1817.7 

D3746-85     Test  Method  for  Impact  Resistance  of  Bituminous  Roofing  Systems  1505.3.2 


656 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 

Standard 

c  _..,  Referenced  m 

reference  Title  ^onr-xmc     .  u 

,  7sU  CMK  Section  number 

number 

D3909-95a  Specification  for  Asphalt  Roll  Roofing  (Glass  Felt)  Surfaced  with  Mineral 

Granules    1507.2.2, 

Table  1507.3.1 

D3966-90     Test  Method  for  Piles  Under  Lateral  Loads   1817.6.2 

D4099-89     Specification  for  Poly  (Vinyl  Chloride)  (PVC)  Prime  Wndows ' 3606.8. 1 

D4272-90a    Test  Method  for  Total  Energy  Impact  of  Plastic  Films  by  Dart  Drop  1505.3.2 

D4434-87     Specification  for  Poly  (Vinyl  Chloride)  Sheet  Roofing 1507.3.3 

D4601-95      Specification  for  Asphalt  Coated  Glass  Fiber  Base  Sheet  Used  in  Roofing    Table  1507.3.1 

D4637-87     Specification  for  Vulcanized  Rubber  Sheet  Used  in  Single-Ply  Roof  Membrane 1507.3.2 

D5055-95a  Specification    for    Establishing    and    Monitoring    Structural    Capacities    of 

Prefabricated  Wood  I-Joists  23 13.5 

E72-95  Methods  of  Conducting  Strength  Tests  of  Panels  for  Building  Construction 2305.7 

E84-95b       Test  Method  for  Surface  Burning  Characteristics  of  Building  Materials 412.3.6.3,  704.4.1.2, 

722.2,  722.3,  80T.2, 

803.3.2,2310.2, 

2601.2,2603.3, 

2603.6.3,  2603.7.4, 

2604.1,2805.2.2, 

3603.17.1.1, 

3603.17.2.6,3603.17.3, 

3603.18.3,3603.19.1, 

3603.19.2 

E90-90         Test  Method  for  Laboratory  Measurement  of  Airborne  Sound  Transmission  Loss 

of  Building  Partitions   1214.2,  3603.4.3.1 

E96-90  Standard  Test  for  Water  Vapor  Transmission  of  Materials 

E108-95        Test  Methods  for  Fire  Tests  of  Roof  Coverings 1506.1,  1506.2, 

2608.2,  2608.3 

El  19-95a     Test  Methods  for  Fire  Tests  of  Building  Construction  and  Materials 412.3.6.2,  704.1.1, 

705.4,707.7.2,707.7.3, 

707.8.1.2,709.6.1, 

709.6.2,  709.6.4, 

709.7.1.2,713.4.2, 

2105.2,2603.4, 

3603.4.1 

E136-95        Test  Method  for  Behavior  of  Materials  in  Vertical  Tube  Furnace  at  750°C 704.4.1.1,3612.2 

E152-81a      Methods  of  Fire  Tests  of  Door  Assemblies 716.1,716.1.1, 

3603.17.3 

E163-84        Methods  of  Fire  Tests  of  Window  Assemblies 718.1,719.1 

E283-9 1        Test  Method  for  Rate  of  Air  Leakage  Through  Exterior  Windows,  Curtain  Walls, 

and  Doors  Under  Specified  PressureDifferences  Across  the  Specimen 3606.8.2,  3606.9.2 

E492-90       Test   Method   for  Laboratory   Measurement  of  Impact   Sound  Transmission 

Through  Floor-Ceiling  Assemblies  Using  the  Tapping  Machine    1214.3,  3603.4.3.3 

E648-95        Test  Method  for  Critical  Radiant  Flux  of  Floor-Covering  Systems  Using  a 

Radiant  Heat  Energy  Source  805.2 

E814-94b      Test  Method  for  Fire  Tests  of  Through-Penetration  Fire  Stops 707.7.2,  707.7.3, 

709.6.1,709.6.2, 
713.4.1 
E838-81        Practice  for  Performing  Accelerated  Outdoor  Weathering  Using  Concentrated 

Natural  Sunlight   1505.3.1 

E970-89       Test  Method  for  Critical  Rdiant  Flax  of  Exposed  Attic  Floor  Insulation  Using  a 

Radiant  Heat  Energy  Sources 3603. 19.4 

E1509-  Specification  for  Room  Heaters,  Pellet  Fuel-Burning  Type 3610.1.2.1,3610.6.13 

G23-95  Practice  for  Operating  Light-  Exposure  Apparatus  (Carbon-  Arc  Type)  With  and 

Without  Water  for  Exposure  of  Nonmetallic  Materials 1505.3. 1 

G26-95         Practice  for  Operating  Light-  Exposure  Apparatus  (Xenon-  Arc  Type)  With  and 

Without  Water  for  Exposure  of  Nonmetallic  Materials 1505.3. 1 

G53-95         Practice  for  Operating  Light-  and  Water-  Exposure  Apparatus  (Fluorescent  UV  - 

Condensation  Type)  for  Exposure  of  Nonmetallic  Materials 1505.3. 1 


2/7/97  (Effective  2/28/97)  780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


AWPA 


American  Wood  Preservers  Association 

P.O.  Box  286 

Woodstock,  Maryland  21163-02S6 


Standard  _. .  Referenced  in 

reference  number  780  CMR  Section  number 

Cl-95  All  Timber  Products  -Preservative  Treatment  by  Pressure  Processes   1506.3,  23 1 1.3, 

3603.22.3.1 
C2-95  Lumber,  Timber,  Bridge  Ties  and  Mine  Ties  -Preservative  Treatment  by 

Pressure  Processes 1808.1,  1808.2,  2311.3, 

2311.4,2311.5,2311.7, 
3603.22.3.1 

C3-95  Piles  -  Preservative  Treatment  by  Pressure  Processes    1808.1,  1822.2, 

3603.22.3.1 

C4-95  Poles  -  Preservative  Treatment  by  Pressure  Processes 1808.2,  3603.22.3.1 

C9-95  Plywood- Preservative  Treatment  by  Pressure  Processes 2311.3,2311.4,2311.5, 

2311.7,3603.22.3.1 
C 15-90  Wood  for  Commercial-Residential  Constrruction  Preservative  Treatment 

by  Pressure  Process 3603.22.3. 1 

CI 8-90  Standard  for  Pressure-treated  Material  in  Marine  Construction 3603.22.3.1 

C20-93  Structural  Lumber  -  Fire- Retardant  Treatment  Pressure  Processes 2310.2,3603.22.3.1 

C22-93  Lumber  and  Plywood  for  Permanent  Wood  Foundations  -    Preservative 

Treatment  by  Pressure  Processes  1808.3,  3603.22.3.1, 

3604.2.1.2,3605.4.3 
C23-84  Round   Poles   and  Posts  Used   in  Building  Construction,  Preservative 

Treatment  by  Pressure  Process 3603.22.3. 1 

C24-86  Sawn  Timber  Piles  Used  for  Residential  Commerce  Building 3603.22.3. 1 

C27-93  Plywood-  Fire-Retardant  Treatment  by  Pressure  Process 23 10.2,  3603.22.3.1 

C28-90  Standard    for    Preservative   Treatment   of   Structural    Glues-Laminated 

Members  and  Laminations  Before  Cluing  of  Southern  Pine,  Pacific 

Coast  Douglas  Fir,  Hem-fir  and  Western  Hemlock  by  Pressure  Process 

M4-95  Standard  for  the  Care  of  Preservative-  Treated  Wood  Products 1822.2 

Pl/P  13-95  Standard  for  Coal  Tar  Creosote  for  Land  and  Fresh  Water  and  Marine 

(Coastal  Water)  Use  2311.3,  3603.22.3.1 

P2-95  Standard  for  Creosote  Solutions  2311.3,3603.22.3.1 

P3-89  Standard  for  Creosote  -  Petroleum  Oill  Solution   3603.22.3.1 

P5-95  Standards  for  Waterborne  Preservatives 2311.3,  3603.22.3.1, 

3604.2.1.2 

P8-95  Standards  for  Oil-  Borne  Preservatives 231 1.3,  3603.22.3.1 

P9-92 Standards  for  Solvents  and  Formulations  for  Oiganic  Preservative  Systems 23 1 1.3 


AWS 


American  Welding  Society 
550  N.W.  LejeuneRoad 
P.O.  Box  351040 
Miami,  Florida  33135 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


Dl.1-92 
D  1.4-92 


Structural  Welding  Code-  Steel 

Structural  Welding  Code-  Reinforced  Steel 


1705.3.3.2 
.    1906.5.2 


658 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 


BOCA 


Building  Officials  and  Code  Administrators  International 

4051  West  Flossmoor  Road 

Country  Club  Hills,  Illinois  60477-5795 


Standard  reference 
number 


Title 


Referenced  m 
7S0  CMR  Section  number 


BNFOC-93 


BNMC-93 


BNPC-9? 


BOCA  National  Fire  Prevention  Code 


BOCA  National  Mechanical  Code 


BOCA  National  Plumbing  Code 


307.5.  307.8.  Table  307.8(1).  Table  307.8(2).  408.6 

415.L  417.1.  417.2.1. 417.3.  417.5. 417.5.1 

417.5.2,417.5.3.417.5  5.  417.6.  417.6.1.  417.6.3 

418.1.  418.2.  418.2.1. 418.3,  418.3.1. 41S.3.2 

418.3.3.  418.4.  418.5.  419.2.3.  705.2.1.  707.1.1 

901.2,3103 
.  .  201.3.  307.8.  408.4. 1.  408.5.  41 1.3.  416.9.  417.1 
417.3.  418.3.1.4.418.3.2.  418.3  2.3.  41S.3.3 

418.3.4.  419.2.  419.2.1.  602.4.2.  602.4.3.  717.2 
722.2.913.1.  1203.1,  1208.3.  1209.1.  1210.3. 

21 14.2.  21 14.9.  2305. 12.  2801.2.  2802.1.  2802.3 
2804.1.  2805.2.3.  2805.2.4.  2808.3.  281 1.1,  3  107.6 

3309.2.3603.6.7 
..  201.3.  408.4.  418.3.4.  602.4.3.  1212.7.  1813.5 


CGSB 


Canadian  General  Standards  Board 
Technical  Information  Unit 
PCI,  Phase  III,  Place  Du  Portage 
Hull,  Ottawa,  Canada  K1A  IG6 


Standard  reference 
number 


Referenced  in 
7S0  CMR  Section 

number 


37-GP-52M-84      Roofing  and  Waterproofing  Membrane.  Sheet  Applied.  Elastometric 1505.3.2,  1507.3.2 

37-GP-54M-79     Roofing   and  Waterproofing   Membrane,   Sheet  Applied.   Flexible.   Polyvinyl 

Chloride '...'. 1507.3.3 

37GP-56M-80      Membrane.  Modified.  Bituminous.  Prefabricated,  and  Reinforced  for  Roofing  - 

with  Dec.  1985  revision   1507.3.4 


CPSC 


Consumer  Product  Safety  Commission 
Office  of  the  Secretary 
Washington,  D.C.  20207 


Standard  reference 
number 


Referenced  in 

7S0  CMR  Section 

number 


Safety  Standard  for  Architectural  Glazing   2405.1,  2406.1, 

2407.2.3603.20.4.1 
Interim  Safetv  Standard  for  Cellulose  Insulation   722.4 


16CFR 
Part  1201-77 
16CFR 
Part  1209-86 

I6CFR  Part  1404-86      Cellulose  Insulation 722.4 

16CFR  Part  1500-84      Hazardous  Substances  and  Articles,  Administration  and  Enforcement 

Regulations  307.2 

16CFR.  Part  1630  Standard  for  die  Surface  Flammabihty  of  Carpets  and  Rugs 805.3,  805.5 

(DOCFF-D-70  


CSA 


Canadian  Standards  Association 

178  Rex  Dale  Boulevard 

Rex  Dale,  Ontario.  Canada  M9W1R3 


Standard  reference 
number 


Title 


Referenced  in 
780  CMR  Section  number 


CSA  0437-M92 


OSB  and  Wafcrboard 


3605.2.1.2.  3608.2  1  3 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


Standard 

Title 

Referenced  in 

reference  number 

780  CMR  Section 
number 

7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

CSSB  Cedar  Shake  and  Shingle  Bureau 

515  116™  Avenue,  NE,  Suite  275 
Bellevue,  WA  98004 

CSSB-84  Grading  and  Packing  Rules  for  Certigrade  Red  Cedar  Shingles  (Revised 

February  1,  1984)   3609.8.2 

CSSB-85  Grading  and  Packing   Rules   for  Cert-Split  Red  Cedar  Shakes   (Revised 

October  1,  1985) 3609.9.2 

CSSB-90  Grading  Rules  for  Shake  Hip  and  Ridge  based  on  the  Standards  of  the  Cedar 

Shake  and  Shingle  Bureau 3609.8.3.3,  3609.9.3.4 

CSSB-90  Grading  Rules  for  Certi-Sawn  Taper-Sawn  Cedar   Shakes  (Revised  May  30, 3609.9.2 

1990) 
CSSB-90  Wood  Shakes  (Preservative  Treated)  based  on  Grading  and  Packing  Rules  for 

Treated  Southern  Pine  Taper-Sawn  Shakes  of  the  Cedar  Shake  and  Shingle 

Bureau 3609.9.3 

CSSB-93  Grading  Rules  for  Wood  Shakes  and  Shingles 3607.2.6,  3607.3.5 

Exterior  and  Interior  Walls  -  Design  and  Application  Manual  for,  1989 

New  Roof  Coverings  -  Red  Cedar  Shingle  and  Shake  Design  and 

Application  Manual  for,  1989 

Red  Cedar  Shingles  -  Grading  Rules  for  Certi-Grade,  1984 

Wood  Shakes  - 

Grading  Rules  for  Certi-Sawn  Taper  Sawn  Red  Cedar  Shakes,  198 1 
Grading  Rules  for  Certi-Split  Red  Cedar  Shakes,  1985 
Wood  Shingles  - 
Grading  Rules  for  Certi-Grade  Shingles.  1984 


cwc 


Canadian  Wood  Council 

1730  St.  Laurent  Boulevard  -  Suite  350 

Ottawa,  Ontario,  Canada  K1G  5L1 


Standard  reference 
number 


Title 


Referenced  in 

780  CMR  Section 

number 


CWC-87 


Canadian  Dimension  Lumber  Data  Book 3608.2.2 


DOC  United  States  Department  of  Commerce 

National  Institute  of  Standards  and  Technology 
Gaithersburg,  MD  20899 

Standard  reference  Referenced  in 
number 780  CMR  Section  number 

PS  1-95  Construction  and  Industrial  Plywood   2306.4.6, 2307.1,  3606.10.1, 

3608.3.2.1,  Table  3604.4.3.3 

PS  2-95  Performance  Standard  for  Wood-  Based  Structural-  Use  Panels 2307. 1,  3604.4.3.3, 

3605.3.2.1,3605.3.2.1.2, 
3606.10.13608.3.2.1 

PS  20-94  American  Softwood  Lumber  Standard  -with  1991  Amendments 2302.1,  3604.4.3.1, 

3605.2.1,3606.2,3608.2.1 

FF-1(CPSC  16  CFR,   Standard  for  the  Surface  Flammabilitv  of  Carpet  and  Rugs 805.3,  805.5 

Part  1630) -70  

DO  I  n  U.S.  Department  of  Transportation 

c/o  Superintendent  of  Documents 
U.S.  Government  Printing  Office 
Washington,  D.C.  20402-9325 

Referenced  in 
Standard  reference  number  Title  780  CMR  Section 

number 

49  CFR.  Part  100-178  Specification  for  Transportation  of  Explosive  and  Other  Dangerous  Articles, 

&  179-199 -88  Shipping  Containers 307  2 

660  7S0  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 

EIA  Electronics  Industries  Association 

2001  Pennsylvania  Avenue,  NW 
Washington,  D.C.  20006 

„       ,     .     c  Referenced  in 

Standard  reference  _.  ,  _,„„ 

,  Title  780  CMR  Section 

number 

number 

222-E-91             Structural    Standards    for    Steel    Antenna    Towers    and    Antenna    Supporting 
Structures 3  108.4 

F\I  Factory  Mutual  Engineering  Corporation 

Standards  Laboratories  Department 
1151  Boston  Providence  Turnpike 
Norwood,  Massachusetts  02062 

,     .     ,  Referenced  in 

Standard  reference  .„„„,.„(.      . 

Title  780  CMR  Section 

number  . 

number 

4450-90  Approval  Standard  for  Class  I  Insulated  Steel  Deck  Roofs  -with  Supplement 

(July  1992)   1505.2.2,  2603.4.1.5 

4470-86  Approval  Standard  for  Class  1  Roof  Coverings  -with  Supplement  3  (August 

1992) 1505.2.2,  1505.3.2 

4880-94 Test  Procedure  for  Building  Corner  Fire  Test 2603.8,3605.17.3 


GA 


Gypsum  Association 

103  Orrington  Avenue,  Suite  1210 

Evanston.  IL  60201 


Standard  reference 
number 


Title 


Referenced  in 

780  CMR  Section 

number 


GA  253-93 


Recommended  Specification  for  the  Application  of  Gypsum  Seathing  Table  3606.2.3(a) 


HP  MA 


Hardwood  Plywood  Manufactures  Association 
1825  Michael  Faraday  Drive,  P.O.  Box  2789 
Reston,  Virginia  22090-2789 


Standard  reference 
number 


Referenced  in 
780  CMR  Section  number 


HP-83 
HP-SG- 


Hardwood  and  Decorative  Plywood   

Structural  Design  Guide  for  Hardwood  Plywood  Wall  Panels 


.  ..  2307.1,3607.2.5 

2307.1,3605.3.2.1, 

3606.10.1 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


661 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

MASSACHUSETTS,  COMMONWEALTH  OF 
CODE  OF  MASSACHUSETTS  REGULATIONS  (CMR) 

Specific  numbers  have  been  established  by  the  Massachusetts  Office  of  the  Secretary  of  State  to  identify  for  reference 
purposes  all  rules  and  regulations  promulgated  by  agencies  of  the  Commonwealth  of  Massachusetts.  These  numbers 
are  designated  as  "Code  of  Massachusetts  Regulations"  (CMR's). 

Board  of  State  Examiners  of  Plumbers  and  Gas  Fitters 
100  Cambridge  Street 
Boston,  MA  02202 


248  CMR  2.00 

248  CMR  4.00 -7.00 


Massachusetts  State  Plumbing  Code 
Massachusetts  Fuel  Gas  Code 


711  CMR  3.00 


Outdoor  AdvertisingBoard 
100  Cambridge  Street,  Floor  20 
Boston,  MA  02002 

Control  and  Restriction  of  Billboards,  Signs  and  Other  Advertising  Devices 


105  CMR  130.000 
105  CMR  140.000 


105  CMR  151.000 
105  CMR 

105  CMR  400.000 

105CMR410.000 

105  CMR  420.000 

105  CMR  430.000 

105  CMR  435. 000 
105  CMR  440.000 

105  CMR  590:000 


Department  of  Public  Health 
150  Tremont 
Boston,  MA  02111 

Hospital  Licensure 

Licensure  of  Clinics 

Designer's    Guide   (Bureau   of  Planning   and   Construction)    Dispensaries    and   Clinics, 

December  21,  1966- 

General  Standards  of  Construction  for  Long  Term  Care  Facilities  in  Massachusetts 
Intensive  Care  Unit  Amendment,  October  1,  1972 

State  Sanitary  Code  Chapter  I:  General  Administrative  Procedures 

Minimum  Standards  of  Fitness  for  Human  Habitation  (State  Sanitary  Code:  Chapter  II: 

Housing  and  Sanitation  Standards  for  Farm  Labor  Camps  (State  Sanitary  Code:  Chapter  III) 

Minimum  Sanitation  and  Safety  Standards  for  Recreational  Camps  for  Children  (State 
Sanitary  Code:  Chapter  IV) 

Minimum  Standards  for  Swimming  Pools  (State  Sanitary  Code:  Chapter  V) 

Minimum  Standards  for  Developed  Family  Type  Campgrounds  (State  Sanitary  Code: 
Chapter  VI) 

State  Sanitary  Code  Chapter  X  -  Minimum  Sanitation  Standards  for  Food  Establishments 


454  CMR  2.00 
454  CMR  10.00 
454  CMR  11.00 
454  CMR  12.00 
454  CMR  16.00 

454  CMR  19  00: 


Division  of  Industrial  Safety 

100  Cambridge  Street,  11th  Floor 

Boston,  MA  02202 

Toilets  in  Industrial  Establishments 
Industrial  Bulletin  No.  4 

Construction  Industry  Rules  and  Regulations 
Industrial  Bulletin  No.  12 

Structural  Painting  Safety  Code 
Industrial  Bulletin  No.  13 

Requirements  for  the  Care  of  Employees  Injured  or  Taken  111  in  Industrial  Establishments 
Industrial  Bulletin  No.  14 

Lighting  Code   for  Factories,   Workshops,   Manufacturing,   Mechanical   and   Mercantile 

Establishments 

Industrial  Bulletin  No.  IS 

Window  Cleaning 
Industrial  Bulletin  No.  21 


662 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 

APPENDIX  A 

Architectural  Access  Board 
Department  of  Public  Safety 
One  Ashburton  Place,  13  th  Floor 
Boston,  MA  02108 

521  CMR  1.00  -  47.00       Architectural  Access  Board  Regulations 


522  CMR  2.00 
522  CMR  3.00 

522  CMR  4.00 
522  CMR  5.00 
522  CMR  6.00 
522  CMR  7.00 
522  CMR  8.00 
522  CMR  9.00 
522  CMR  10.00 
522  CMR  11.00 
522  CMR  12.00 


Board  of  Boiler  Rules 
Department  of  Public  Safety 
One  Ashburton  Place,  Roon  1301 
Boston,  MA  02108 

Construction  of  Power  Boilers 

Power  Boilers.  Power  Reactor  Vessels  and  Piping  and  Unfired  Pressure  Vessels  as  Used  i 
Atomic  Energy  Installations 

Steam  and  Hot  Water  Boilers  and  Heat  Storage  Sources 

Heating  Boilers 

Low  Pressure  Heating  Boilers 

Air  Tanks 

Air  Tanks 

Refrigeration  and  Air  Conditioning  Systems 

Material  Specifications 

Welding  Specifications 

Fiberglass-reinforced  Plastic  Pressure  Vessels 


Board  of  Elevator  Regulations 
One  Ashburton  Place,  Roon  1301 
Boston,  MA  02108 

524  CMR  2.00  -  1 1 .00      Elevator  and  Escalator  Regulations 

524  CMR  15.00-34.00      Elevator.  Dumbwaiter,  Escalator,  and  Moving  Walk  Regulations 


527  CMR  3.00 

527  CMR  4.00 
527  CMR  5.00 

527  CMR  6.00 
527  CMR  7.00 
527  CMR  9.00 
527  CMR  10.00 
527  CMR  12.00 
527  CMR  14.00 
527CMR21.00 


Board  of  Fire  Prevention  and  Regulation 
1010  Commonwealth  Avenue 
Boston,  MA  02215 

Dry  Cleaning  and  Dry  Dyeing  and  the  Keeping.  Storage  and  Use  of  Cleaning  and  Dyeing 
Fluids 

Oil  Burning  Equipment 

Operation  and  Maintenance  of  Buildings  or  Other  Structures  Used  as  Garages,  Service 
Stations  and  the  Related  Storage,  Keeping  and  Use  of  Gasoline  or  Other  Motor  Fuel 

Liquefied  Petroleum  Gas  Containers  and  Systems 

Manufacture  and  Handling  of  Plastics 

Tanks  and  Containers 

Prevention  of  Fire  in  Buildings  and  in  or  on  Ships 

1993  National  Electrical  Code  (Amendments) 

Flammable  and  Combustible  Liquids,  Flammible  Solids  or  Flammable  Gases 

Decorations,  Curtains.  Draperies,  Blinds  and  Other  Window  Treatments 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


663 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NCMA  National  Concrete  Masonry  Association 

2302  Horse  Pen  Road,  P.O.  Box  781 
Herndon,  VA  22070 

Standard  reference  _. .  Referenced  in 

number       780  CMR  Section  number 

NCMA  Design  and   Construction  of  Plain   and  Reinforced  Concrete  Masonry 

TR68-A-75  Basement  and  Foundation  Walls 3604.4.1 


NFPA  National  Fire  Protection  Association 

Batterymarch  Park 
Quincy,  Massachusetts  02269 


Standard  reference  _. .  Referenced  in 

number  780  CMR  Section  number 

10-94  Portable  Fire  Extinguishers 920.2 

1 1-94  Low  Expansion  Foam  And  Combined  Agent  Systems 91 1.1,  91 1.5 

1 1A-94  Medium  and  High  Expansion  Foam  Systems 91 1. 1,  91 1.5 

12-93  Carbon  Dioxide  Extinguishing  Systems 909.1,  909.5 

12A-92  Halon  1301  Fire  Extinguishing  Systems 912.1,  912.5 

12B-90  Halon  121 1  Fire  Extinguishing  Systems 912.1,  912.5 

13-96  Installation  of  Sprinkler  Svstems 412.7, 416.4,  706.2, 

906.2.1,906.9.1,907.2.1, 
917.7.3 
1 3D-96  Installation  of  Spri:ikler  Systems  in  One-  and  Two-  Family  Dwellings  and 

Mobile  Homes .' 906.2.3 

13  R-94  Installation  of  Sprinkler  Svstems  in  Residential  Occupancies  Up  to  Four 

Stories  in  Height  . .  . .  * 906.2.2,  923. 1 

14-95  Standpipe  and  Hose  Systems 914.1,  914.5,  914.12.1 

15-96  Water  Spray  Fixed  Systems  for  Fire  Protection  908. 1,  908.4 

16-95  Deluge  Foam- Water  Sprinkler  and  Spray  Systems   911.1,911.5 

17-94  Dry  Chemical  Extinguishing  System 910.1,  910.5 

17A-94  Wet  Chemical  Extinguishing  Systems    913.1,913.5 

20-96  Installation  of  Centrifugal  Fire  Pumps   924.1 

22-96  Standard  for  Water  Tanks  for  Private  Fire  Protection   

24-95  Installation  of  Private  Fire  Service  Mains 417.6.3.  906.9.1,  914.6.1 

25-95  Inspection.  Testing,  and  Maintenance  of  Water-Based  Fire  Protection 

Systems 901.4 

30-96  Flammable  and  Combustible  Liquids  Code   307.8,  416.14,  418.3.2. 

419.2.3 

30A-96  Automotive  and  Marine  Service  Station  Code   408.6,  417.6.6 

32-96  Dry  Cleaning  Plants 418.3.4 

33-95  Spray  Application  Using  Flammable  and  Combustible  Materials 307.8,  419.1 

34-95  Dipping  and  Coating  Processes  Using  Flammable  or  Combustible  Liquids 307.8,  419.1 

40-94  Cellulose  Nitrate  Motion  Picture  Film    411.1 

50-96  Bulk  Oxygen  Systems  at  Consumer  Sites 28 10. 1 

5 1-92  Oxygen-Fuel  Gas  Systems  for  Welding,  Cutting  and  Allied  Processes  2810.1 

61-95  Prevention  of  Fire  and  Dust  Explosions  in  Agricultural  Food  Products 

Facilities    418.3.1 

65-93  Processing  and  Finishing  of  Aluminum    418.3.1 

69-92  Explosion  Prevention  Systems   417.5.1.2 

70-96  National  Electrical  Code  416.11,416.14.6, 

416.15.2,602.4.4, 
1405.4.3,3102.6.3. 
3102.13.1,  3107.6 

72-96  National  Fire  Alarm  Code 403.6,  417.5.3,  917.1, 

917.6,917.7,917.8.1. 

917.9,917.10,918.1, 

918.8,919.1,919.6, 

921.4,923.1 

80-95  Fire  Doors  and  Windows 716  2.  716.5. 

1017.4.4 

80A-96  Protection  of  Buildings  from  Exterior  Fire  Exposures 

82-94  Incinerators.  Waste  and  Linen  Handling  Systems  and  Equipment 2807  1 

90A-96  Installation  of  Air  Conditioning  and  Ventilation  Systems   

90B-96  Installation  of  Warm  Air  Heating  and  Air  Conditioning  Systems   

664  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 


Standard  reference 
number 


_. .  Referenced  in 

780  CMR  Section  number 

Smoke  Control  Systems 

Smoke  Management  System  in  Malls.  Atria  and  Alrge  Areas  

Ventilation    Control    and    Fire    Protection    of   Commercial    Cooking 

Operations  

Health  Care  Facilities    2809.1,  2809.2 

Life  Safety  Code   

Assembly  Seating.  Tents  and  Membrane  Structures 3 104.4 

Coal  Preparation  Plants 418.3.1 

Standard  for  Fixed  Guidevvay  Systems 

General  Storage 426.0 

Rack  Storage  of  Materials 507.1,  Table  922.2 

Storage  of  Rubber  Tires    426.0 

Safeguarding  Construction.  Alteration  and  Demolition  Operations 915.1,  914.7.2, 

903.1.5 

Standard  Test  Method  for  Potential  Heat  of  Building  Materials 3603.17.2.5 

Aircraft  Hangers   

Construction  and  Protection  of  Airport  Terminal  Buildings 

Roof-top  Heliport  Construction  and  Protection   15 1 1.3 

Storage  of  Liquid  and  Solid  Oxidizers   

Explosive  Material  Code 417.5.1 

Access  Highways,  Tunnels.  Bridges,  Air  Right  Structures 

Manufacture  of  Aluminum  or  Magnesium  Powder 418.3.1 

Prevention   of      Fire,    and   Dust   Explosions   in   the   Chemical,    Dye, 

Pharmaceutical,  and  Plastics  Industries   418.3.1 

Prevention  of  Sulfur  Fires  and  Explosions   418.3.1 

Prevention    of    Fires     and    Explosions    in    Wood    Processing    and 

Woodworking  Facilities    418.3.1 

Standard  Methods  of  Fire  Tests  for  Flame  Resistant  Textiles  and  Films 807.2,  807.2.2, 

3102.6.4.2,3103.3.2, 
3104.5 

Identification  of  the  Fire  Hazards  of  Materials 416.2,416.15.1 

Installation  of  Water  Mist  Fire  Protection  Systems    

Pulverized  Fuel  Systems   418.3.1 


92A-96 
92B-95 
96-96 

99-96 

104-94 

102-95 

120-94 

130-95 

231-95 

231C-95 

231D-94 

241-96 

259-87 
409-95 
416-93 
418-95 
430-95 
495-96 
502-96 
651-93 
654-94 

655-93 
664-93 


704-96 
750-96 
850-96 


NFoPA 

(AFPA) 


American  Forest  and  Paper  Association* 
1250  Connecticut  Avenue,  N.W./  Suite  200 
Washington,  D.C.  20036 


Standard  reference 
number 


Title 


Referenced  in 
7S0  CMR  Section  number 


NDS-91  National  Design  Specification  for  Wood  Construction  -with  1991 

Supplement:  Design  Values  for  Wood  Construction 2303. 1,  2304. 1, 

2305. 14. 1,  2306.4,  2306.4.5. 1, 

2306.4.5.2,2306.4.6, 

2306.4.6.1.1,2306.4.6.2.1, 

2306.4.7.1.1,2306.4.7.2.1, 

2312.1,2312.4,2313.3.1, 

2313.3.2 

TR7-87  Basic  Requirements  for  Permanent  Wood  Foundation  Svstem    1808.3.1813.3.2311.3.3 

"The  National  Forest  Products  .Association  (NFoPA)  has  changed  their  name  to  the  American  Forest  and  Paper 
.Association  (AFPA).   The  referenced  standard  in  this  code  are  identified  with  the  designation  NFoPA. 


2/7/97  (Effective  2/28/97) 


"SO  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STAND ARDS 
THE  MASSACHUSETTS  STATE  BUILD[NG  CODE 


RCSC 


Research  Council  On  Structural  Connections 

c/o  American  Institute  of  Steel  Construction,  Inc. 

Suite  3100 

One  East  Wacker  Drive 

Chicago,  IL  60601-2001 


Standard  reference 
number 


Referenced  in 

7S0  CMR  Section 

number 


RCSC-85 
RCSC-88 


Specifications  for  Structural  Joints  Using  A325  or  A490  Bolts 
Specification  for  Load  and  Resistance  Design   


1705.3.3.1 


RMA  Rubber  Manufacturers  Association 

1200  K  Street,  N.W. 
Washington,  D.C.  20005 

Referenced  in 
Title  780  CMR  Section 

number 

RP-1-  90  Minimum  Requirements  for  Non-  Reinforced  Black  EPDM  Rubber  Sheets  1507.3.2 

RP-2-90  Minimum  Requirements  for  Fabric-  Reinforced  Black  EPDM  Rubber  Sheets 1507.3.2 

RP-3-85  Minimum  Requirements  for  Fabric-  Reinforced  Black  Polychlorprene  Rubber 

Sheets      1507.3.2 


Standard  reference 
number 


SJI 


Steel  Joist  Institute 

1205  48th  Avenue  North 

Suite  A 

Myrtle  Beach.  South  Carolina  29577 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


Standard  Specifications.  Load  Tables  and  Weight  Tables  for  Steel  Joists  and  Joist 
Girders 


SMACNA  Sheet  Metal  and  Air  Conditioning  Contractors 

National  Association,  Inc. 

4201  Lafayette  Center  Drive 
Chantilly,  VA  22021 


Standard  reference 
number 


Title 


Referenced  in 

7S0  CMR  Section 

number 


SMACN'A-88       Installation  Standards  for  Residential  Heating  and  Air  Conditioning  Systems 


TFS 


Texas  Forest  Service 
Forest  Products  Laboratory 
P.O.  Box  310 
Lufkin,  Texas  75902-0310 


Standard 
reference 
number 


Referenced  in 

780  CMR 
Section  number 


TFS-90 


Grading  Rules  for  Preservative  Treated  Southern  Yellow  Pine  Tapersawn  Shakes 1507_19 


666 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  A 


TMS 


The  Masonry  Council 
Suite  B 

2619  Spruce  Street 
Boulder,  CO  80302-3808 


Standard  reference 
number 


Title 


Referenced  in 
780  CMR  Section  number 


TMS  402/ACI  530/     Building  Code  Requirements  for  Masonrv  Structures 
ASCE  5-95 


707.3,  1705.5,  Table  1705.5,  1812.3.2, 
Table  18 12.3.2,  210 1. 1 . 1,  21 01. 1 .2, 

2104.2,2104.3,  2104.4.2106.3.1 


TMS602/ACI  Specifications  for  Masonrv  Structures    Table  1705.5,2104.2.2112.1.1 

530. 1/ASCE  6-95 


TPI 


Truss  Plate  Institute  Inc. 
Suite  200 

583  D'Onofrio  Drive 
Madison,  Wisconsin  53719 


Standard  reference 
number 


_. .  Referenced  in 

780  CMR  Section  number 

Design  Specification  for  Metal  Plate  Connected  Parallel  Chord  Wood 

Trusses    2305.14.1,2313.3.2, 

3605.2.10,3608.2.11 

National   Design  Standard  for  Metal   Plate  Connected  Wood  Truss  2305.15,  2313.3.1, 

Construction   3605.2. 10,  3608.2. 1 1 

Bracing  Wood  Trusses:  Commentary  and  Recommendations   3605.2. 10,  3608.2. 1 1 

Quality  Standard  for  Metal  Plate  Connected  Wood  Trusses    3605.2. 10.  3608.2. 1 1 


PCT- 


TPI  1-95 


TPI  BWT-76 
TPI  QST-89 


UL 


Underwriters  Laboratories,  Inc. 
333  Pfingsten  Road 
Northbrook,  Illinois  60062 


Standard  reference 
number 


Referenced  in 
Title  780  CMR  Section 

number 

Standard  for  Safety  Tin-  Clad  Fire  -with  Revisions  through  May  1985 716.2 

Standard  for  Safety  Sliding  Hardware  for  Standard.  Horizontally  Mounted  Tin- 
Clad  Fire  Doors  -with  Revisions  through  October  1984 716.2 

Standard  for  Safety  Swinging  Hardware  for  Standard  Tin-Clad  Fire  Doors 

Mounted  Singly  and  in  Pairs  -with  Revisions  through  October  1984 716.2 

Material  for  Built-up  Roof  Covenngs  (Revised  1989) 3609.7.2 

Standard  for  Safety  Chimneys,  Factory  Built,  Residential  Type  and  Building 

Heating  Appliance  -with  Revisions  through  February  1989  720.6.4,  3612.2 

Standard  for  Safety  Factory-Built  Fireplaces  -with  Revisions  through  June,  1992 720.6.4 

Factory-Made  Air  Ducts  and  Air  Connectors  (Revised  November,  1990)    3619.1.2 

Closure  System  for  Use  with  Rigid  Air  Ducts  and  Connectors 3619. 1.2 

Standard    for   Safety   Single   and   Multiple    Station   Smoke    Detectors    -with 

Revisions  through  February  1989 409.5. 1 

Standard  for  Safety  Smoke  Detectors  for  Fire  Protective  Signaling  Systems  -with 

Revisions  through  May  1989  409.5. 1 

Gas  Vents 3612.2 

Fire  Dampers 

Heat  Pumps  (Revised  December,  1987) 3614.3.1 

Standard  for  Safety  Tests  for  Uplift  Resistance  of  Roof  Assemblies  -with 

Revisions  through  December  1989 1505.2.2 

Low-Temperature  Venting  Systems,  Type  L   36 12.2 

Tests  for  Fire  Resistance  of  Roof  Covering  Material  (Revised,  1989)   3609.1.3 

Standard  for  Safety  Test  for  Flame  Propagation  and  Smoke-Density  Values  for 
Electrical     and     Optical-Fiber     Cables     used     in     Spaces     Transporting 

Environmental  Air 2805  2.5 

Standard  for  Safety  Wind  Resistance  of  Prepared  Roof  Covering  Materials  -with 

Revisions  through  July,  1981   1505.2.3 


10A-93 
14B-93 

14C-93 

55A-83 
103-94 

127-88 
181-90 
181A-90 
217-93 

268-89 

441-86 
555-95 
559-85 
580-94 

641-86 
790-83 
910-95 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


667 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Standard  reference 
number 


Referenced  in 
Title  780  CMR  Section 

number 

Outline  of  Investigation  for  Insulated  Wall  Construction 3603. 17.3 

Electric  Central  Air  Heating  Equipment  (Revised  January,  1988) 3614.1.12 

Standard  for  Safety  Fire  Test  of  Roof  Deck  Constructions   2603.4. 1.5 

Fire  Test  of  Interior  Finish  Material  -with  Revisions  through  March  1991 2603.8,  3603.17.3 

Chimney  Liners  (Revised  November,  1989) 3610.1.14 

Standard   for   Safety   Fire   Test   Pneumatic   Tubing   for   Flame   and    Smoke 

Characteristics  -with  Revisions  through  April  1991    2805.2.6 

Fire  Tests  of  Plastic  Sprinkler  Pipe  for  Flame  and  Smoke  Characteristics 2805.2.1 

Outline  of  Proposed  Investigation  for  Insulated  Wall  Construction 2603.8 


1040-71 
1096-86 
1256,-85 
1715-94 
1777-88 
1820-94 

1887-95 
1040-89 


use 


United  States  Code 
c/o  Superintendent  of  Documents 
U.S.  Government  Printing  Office 
Washington,  D.C.  20402-9325 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


Title  18;  Importation,  Manufacture,  Distribution  and  Storage  of  Explosive  Materials   307.2 

Chapter  40-70 


WWPA 


Western  Lumber 


Standard  reference 
number 


Referenced  in 

780  CMR  Section 

number 


WWPA-92 


Western  Lumber  Span  Tables  for  Floor  and  Ceiling  Joists  and  Roof  Rafters 3608.2.2 


668 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  Appendix  B 

Appendix  B  contains  the  following  information  and  documentation; 

Appendix  B-l 

A)  Sample  Uniform  Building  Permit  Application  Form  for  One  and  Two  Family  Dwellings  and  Accessory 
Buildings.  This  application  form  is  not  mandated  by  780  CMR,  however,  the  information  requested  on  the 
form  is  the  minimum  information  required  to  satisfy  780  CMR  1 10  4 

B)  Sample  Uniform  Building  Permit  Application  Form  for  Any  Building  Other  than  One  and  Two  Family 
Dwellings  and  Accessory  Buildings  This  application  form  is  not  mandated  by  780  CMR  however,  the 
information  requested  on  the  form  is  the  minimum  information  required  to  satisfy  the  requirements  of 
780  CMR  110.4. 

Appendix  B-2 

Application  Forms  required  to  file  an  appeal  with  the  State  Building  Code  Appeals  Board  in  accordance 
with  780  CMR  122.0. 

Appendix  B-3 

Official  Interpretations  of  the  Building  Code  issued  by  the  BBRS  under  authority  of  M.G.L.  c  143,  §  94(e). 
These  interpretations  have  been  made  over  the  period  since  the  promulgation  of  the  first  Edition  of 
780  CMR  on  January  1,  1975.  Interpretations  are  identified  by  number,  in  order  of  interpretation,  followed 
by  the  year  of  the  interpretation.  The  edition  of  780  under  which  the  interpretation  was  made  is  indicated 
for  each  Official  Interpretation 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  669 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

APPENDIX  B-l 

SAMPLE  BUILDING  PERMIT  APPLICATION  FORMS 

The  following  sample  building  permit  application  forms  have  been  developed  to  simplify  the  building  permit 
application  process  for  the  applicant  and  provide  the  building  department  with  sufficient  detail,  in  a 
standardized  and  concise  form.  Wherever  possible  the  forms  utilize  a  check  off  process  for  ease  of  use 

The  sample  application  forms  also  reference  certain  Massachusetts  General  Laws  which  impact  the  issuance 
of  the  building  permit. 

The  primary  objective  in  the  development  of  these  application  forms  is  to  promote  standardization  throughout 
the  Commonwealth.  Standardization  will  benefit  both  the  building  permit  applicant  and  the  building 
department. 

The  sample  application  forms  are  not  mandatory,  but  their  use  is  strongly  suggested.  The  information 
contained  on  the  sample  application  forms,  however,  is  the  minimum  required  to  be  contained  on  a  building 
permit  application  consistent  with  780  CMR  1 10.4 

Application  forms  have  been  developed  for; 

•  One  and  two  family  dwellings  and  accessory  buildings  thereto  and; 

•  All  other  buildings  and  structures. 


670  780  CMR  -  Sixth  Edition    corrected  -  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 


The  Commonwealth  of  Massachusetts 

State  Board  of  Building  Regulations  and 

Standards 

Massachusetts  State  Building  Code 

780  CMR 


FOR  MUNICIPALITY  USE 


APPLICATION  TO  CONSTRUCT.  REPAIR.  RENOVATE  OR  DEMOLISH  A  ONE  OR  TWO  FAMILY  DWELLING 


This  Section  For  Official  Use  Only 


Building  Permit  Number: 


Date  Issued: 


Signature: 


Building  Commissioner/Inspector  of  Buildings 


SECTION  1  -  SITE  INFORMATION 


1.1  Property  Address: 


1.2   Assessors  Map  &  Parcel  Number: 


Map  Number 


Parcel  Number 


1.3   Zoning  Information 


1.4  Property  Dimensions: 


Zoning  District 


1.5  Building  Setbacks  (ft) 


Front  Yard 


Required 


Required 


Required 


Provided  i 


/ 


1.6  Water  Supply  (M.G.L.  c.  40,  §  54)      1.7  Flood  Zone  Information:  1.8  Sewage  Disposal  System: 

Public     D  Private     D  Zone: Outside  Flood  Zone      □  Municipal    c    On  site  disposal  system 


SECTION  2  -  PROPERTY  OWNERSHIP/ AUTHORIZED  AGENT 


2. 1  Owner  of  Record: 


Address  for  Service: 


Signature 


Telepho 


2.2  Authorized  Agent: 


Address  for  Service: 


Telepho 


SECTION  3  -  CONSTRUCTION  SERVICES 


3. 1  Licensed  Construction  Supervisor: 


Licensed  Construction  Supervisor: 


Signature 


Not  Applicable    D 


Expiration  Date 


3.2   Registered  Home  Improvement  Contractor: 


Not  Applicable    C 


Company  Name 


Registration   Number 


Expiration  Date 


Signature 


Telephone 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


671 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


SECTION  4  -  WORKERS*  COMPENSATION  INSURANCE  AFFIDAVIT  {M.G.L.  c.  152,  §  25C(6)) 


Workers  Compensation  Insurance  affidavit  must  be  completed  and  submitted  with  this  application.  Failure  to  provide  this 
affidavit  will  result  in  the  denial  of  the  issuance  of  the  building  permit 


Signed  Affidavit  Attached  Yes o 


SECTION  S  -  DESCRIPTION  OF  PROPOSED  WORK  {check  all  applicable) 


New  Construction 


Existing  Building 


Repair(s) 


O     Alteration(s) 


Accessory  Bldg. 


Demolition 


Other  D    Specify: 


Brief  Description  of  Proposed  Work: 


SECTION  6  -  ESTIMATED  CONSTRUCTION  COSTS 


Estimated  Cost  (Dollars)  to  be 
completed  by  permit  applicant 


Official  Use  Only 


1.   Building 


(a)  Building  Permit  Fee 
Multiplier 


2.   Electrical 


(b)  Estimated  Total  Cost  of 
Construction  from  (6) 


3.   Plumbing 


4.   Mechanical  (HVAC) 


5.  Fire  Protection 


Building  Permit  Fee 
(a)  x  (b) 


6.   Total  =  (1+2  +  3  +  4  +  5) 


Check  Number 


SECTION  7a  -  OWNER  AUTHORIZATION  -  TO  BE  COMPLETED  WHEN 
OWNERS  AGENT  OR  CONTRACTOR  APPLIES  FOR  BUILDING  PERMIT 


hereby  authorize  

my  behalf,  in  all  matters  relative  to  work  authorized  by  this  building  permit  application. 


_.  as  Owner  of  the  subject  property 
to  act  on 


Signature  of  Owner 


SECTION  7b  -  OWNER/AUTHORIZED  AGENT  DECLARATION 


I. . .  as  Owner/ Authorized  Agent 

hereby  declare  that  the  statements  and  information  on  the  foregoing  application  are  true  and  accurate,  to  the  best  of  my 
knowledge  and  belief. 

Signed  under  the  pains  and  penalties  of  perjury. 


Signature  of  Owner/Agent 


672 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 


The  Commonwealth  of  Massachusetts 

State  Board  of  Building  Regulations  and 

Standards 

Massachusetts  State  Building  Code 

780  CMR 


FOR  MUNICIPALITY  USE 


APPLICATION  TO  CONSTRUCT.  REPAIR,  RENOVATE,  CHANGE  THE  USE  OR  OCCUPANCY  OF,   OR  DEMOLISH  ANY 
BUILDING  OTHER  THAN  A  ONE  OR  TWO  FAMILY  DWELLING 


This  Section  For  Official  Use  Only 


Building  Permit  Number: 


Date  Issued: 


Signature: 


Building  Commissioner/Inspector  of  Buildings 


SECTION  1  -  SITE  INFORMATION 


1. 1  Property  Address: 


1.2   Assessors  Map  &  Parcel  Number: 


Map  Number 


Parcel  Number 


1.3   Zoning  Information: 


1.4  Property  Dimensions: 


Zoning  District 


Proposed  Us 


ontage  (ft) 


1.5  Building  Setbacks  (ft) 


Front  Yard 


Required 


Required 


Required 


/ 


1.6  Water  Supply  (M.G.L.  c.  40.  §  541        1.7  Flood  Zone  Information:  1.8  Sewage  Disposal  System: 

Public   D  Private  n  Zone: Outside  Flood  Zone   c       Municipal   □  On  site  disposal  system 


SECTION  2  -  PROPERTY  OWNERSHIP/AUTHORIZED  AGENT 


2.1  Owner  of  Record: 


Signature 


2.2  Authorized  Agent: 


Telephone 


SECTION  3  -  CONSTRUCTION  SERVICES  FOR  PROJECTS  LESS  THAN  35,000  CUBIC  FEET  OF  ENCLOSED  SPACE 


3. 1  Licensed  Construction  Supervisor: 


Licensed  ConstrucUon  Supervls 


Signature 


Telepho 


Not  Applicable  a 


License  Number 


Expiration  Date 


3.2    Registered  Home  Improvement  Contractor: 


Not  Applicable   □ 


Company  Name 


Registration    Numbe 


Expiration  Date 


Telephon 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


673 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


SECTION  4  -WORKERS'  COMPENSATION  INSURANCE  AFFIDAVIT  (M.G.L.  c.  152  g  25C(6)) 

Workers  Compensation  Insurance  affidavit  must  be  completed  and  submitted  with  this  application.  Failure  to  provide  this 
affidavit  will  result  in  the  denial  of  the  issuance  of  the  building  permit. 

Signed  Affidavit  Attached  Yes □                       No □ 

SECTION  5-  PROFESSIONAL  DESIGN  AND  CONSTRUCTION  SERVICES  -  FOR  BUILDINGS  AND  STRUCTURES  SUBJECT 
TO  CONSTRUCTION  CONTROL  PURSUANT  TO  780  CMR  116  [CONTAINING  MORE  THAN  35.0O0  C.F.  OF  ENCLOSED 
SPACE) 

5.1  Registered  Architect: 

Not  Applicable  a 

Name  (Registrant): 

Registration  Number 

Address 

Expiration  Date 

Signature                                                                                                        Telephone 

5.2  Registered  Professional  Engineer(s): 

Name 

Area  of  Responsibility 

Address 

Registration  Number 

Signature                                                                                                         Telephone 

Expiration  Date 

Name 

Area  of  Responsibility 

Address 

Registration  Number 

Signature                                                                                                         Telephone 

Expiration  Date 

Name 

Area  of  Responsibility 

Address 

Registration   Number 

Signature                                                                                                         Telephone 

Expiration  Date 

Name 

Area  of  Responsibility 

Address 

Registration   Number 

Signature                                                                                                        Telephone 

Expiration  Date 

5.3  General  Contractor 

Not  Applicable   a 

Company  Name: 

Responsible  In  Charge  of  Construction 

Address 

Signature                                                                                                         Telephone 

674 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  : 


SECTION  6  -  DESCRIPTION  OF  PROPOSED  WORK  (check  all  applicable 


New  Construction   □ 


Existing  Building 


Repalrtsl 


AHeration(s)   □ 


Accessory  Bldg.    D 


Demolition   D 


Other  □     Specify: 


Brief  Description  of  Proposed  Work: 


SECTION  7  -  USE  GROUP  AND  CONSTRUCTION  TYPE 


USE  GROUP  (Check  as  applicable) 


CONSTRUCTION  TYPE 


A  Assembly 


A-l 
A- 4 


E    Educational 


H  High  Hazard 


I   Institutional 


R    Residential 


Specify: 


M    Mixed  Use 


Specify. 


S   Special  Use 


Specify: 


COMPLETE  THIS  SECTION  IF  EXISTING  BUILDING  UNDERGOING  RENOVATIONS.  ADDHIONS  AND/OR  CHANGE  IN  USE 


Existing  Use  Gr 


Existing  Hazard  Index  780  CMR  34): 


Proposed  Use  Group: 


Proposed  Hazard  index  780  CMR  34) 


SECTION  8  BUILDING  HEIGHT  AND  AREA 


BUILDING  AREA 


Existing  (if  applicable) 


Proposed 


Number  of  Floors  or  stories  include 
basement  levels 


Floor  Area  per  Floor  (sf) 


Total  Area  (sf) 


Total  Height  (ft) 


SECTION  9-  STRUCTURAL  PEER  REVIEW  (780  CMR  110.1 1) 


Independent  Structural  Engineering  Structural  Peer  Review  Required 


SECTION  10a  -  OWNER  AUTHORIZATION  -  TO  BE  COMPLETED  WHEN 
OWNERS  AGENT  OR  CONTRACTOR  APPLIES  FOR  BUILDING  PERMIT 


hereby  authorize 

my  behalf.  In  all  matters  relative  to  work  authorized  by  this  building  permit  application. 


as  Owner  of  the  subject  property 
to  act  on 


Signature  of  Owner 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


675 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


SECTION  10b  -  OWNER/AUTHORIZED  AGENT  DECLARATION 

I                                                                                                                                                                      ,  as  Owner/ Authorized  Agent 

hereby  declare  that  the  statements  and  Information  on  the  foregoing  application  are  true  and  accurate,  to  the  best  of  my 

knowledge  and  belief. 

Signed  under  the  pains  and  penalties  of  perjury. 

Print  Name 

Signature  of  Owner/ Agent                                                                                                                            Date 

SECTION  11  -  ESTIMATED  CONSTRUCTION  COSTS 

Item 

Estimated  Cost  (Dollars)  to  be 
completed  by  permit  applicant 

Official  Use  Only 

1.   Building 

(a)  Building  Permit  Fee 
Multiplier 

2.   Electrical 

(b)  Estimated  Total  Costof 
Construction  from  (6) 

3.   Plumbing 

Building  Permit  Fee    (a)  z  (b) 

4.   Mechanical  (HVAC) 

5.   Fire  Protection 

6.  Total  =  (1  +  2  +  3  +  4+  5) 

Check  Number 

676 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 
Appendix  B-2 

State  Building  Code  Appeals  Board  Filing  Instructions  and  Application  Forms 


2/7/07    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  677 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

(execcc/use,  (17uUc&  of  crctAuo  Cfafetu, 

istlbloaxmacjL  Sria£e>  Guice,  Z$tu/t£ina, 

W,LU<£LWELD                                     @a^,  Jfa^zcAu^      02408  """ST" 

KATHLEEN  M.  OTOOLE  THOMAS  L.  ROGERS 

S~™c<7                                                            TEL:  (617)  727-3200  FAX:  (617)  227-1754  A*nmb.tor 


STATE  BUILDING  CODE  APPEALS  BOARD  -  FILING  INSTRUCTIONS 

Note:  Appeals  are  held  pursuant  to  801  CMR  1.02  Informal/Fair  Hearing  Rules 


The  procedure  outlined  below  must  be  followed  when  filing  a  Building  Code  Appeal: 

1.  The  appellant  must  be  in  receipt  of  a  letter  of  denial  from  the  local  Building  Official  as  required  under 
780  CMR  111.1  of  the  State  Building  Code.  An  appeal  must  be  filed  within  45  days  of  the  date  of  the  letter 
of  denial.  An  appeal  may  be  filed  either  with  the  local  Building  Code  Appeals  Board,  if  one  has  been 
established,  or  directly  with  the  State  Building  Code  Appeals  Board. 

2.  Two  documents  are  required  to  be  completed  by  the  appellant  or  his/her  representative  -  the  Appeal 
Application  Form  (2  pages)  and  the  Service  Notice  (1  page). 

The  Service  Notice,  which  gives  notice  to  the  building  official  that  an  appeal  is  being  filed,  should  include 
the  date  appearing  on  the  appeal  form  and  the  name  and  address  of  the  Building  Official  under  the  section 
"PERSON/ AGENCY  SERVED". The  Method  of  Service  should  list  one  of  the  following  procedures  as 
set  forth  in  Section  121.2.1  of  the  State  Building  Code. 

A.    Personally;  or 

B     Registered  or  Certified  Mail,  return  receipt  requested;  or 

C.    By  any  person  authorized  to  serve  civil  process. 

The  Date  of  Service  is  the  date  when  a  copy  of  the  appeal  is  delivered  or  mailed  to  the  Building  Official 
or  other  party  entitled. 

The  Service  Notice  must  be  signed  by  the  appellant  or  his/her  representative  and  the  signature  must  be 
notarized. 

The  Appeal  Application  Form  (2  pages)  must  be  completed  in  total.  The  application  will  be  reviewed 
for  completeness  prior  to  a  hearing  being  scheduled.  Applications  determined  to  be  incomplete  will  be 
returned  to  the  applicant  for  correction.  Questions  relating  to  completing  the  application  should  be 
directed  to  your  local  building  department  or  this  office. 

3.  One  complete  copy  of  the  appeal  filing,  including  the  original  of  the  Service  Notice,  must  be  delivered 
to  the  Building  Official  or  the  official  entitled.  Four  complete  copies  of  the  appeal  filing,  including  the 
original  plus  three  copies  of  the  Appeal  Application  form,  four  copies  of  the  Service  Notice  and  four  copies 
of  the  letter  of  denial,  together  with  a  check  for  $150.00  (filing  fee)payable  to  the  Commonwealth  of 
Massachusetts  must  be  filed  with  this  office,  if  the  appeal  is  made  directly  to  the  State  Building  Code 
Appeals  Board.  (Filing  fee  requirements  for  filings  before  a  local  Building  Code  Appeals  Board  may  differ 
from  the  fees  prescribed  for  submission  to  the  State  Building  Code  Appeals  Board). 

ALL  CASES  WTT.I.  BF  HEARD  ON  THE  SCHEDULED  DATE 
POSTPONEMENTS  WILL  NOT  BE  GRANTED. 


678  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  ] 

(oxecu&ue'  €yj&ce>  of  cruJdio  Jafetu< 

S/ia/e-  ZOacLfd  a£3otu/ckna,  dneau/aManA.  and-  .TtasiclajLcL, 

&ne.  srfJdujUan,  &tace,    -    £%aorn,-/301 
W,LLc"LWELD  ®o^,  JL^cAuAeO.      02108  KNTAjOTHrrsuM. 

KATHLEEN  M.  OTOOLE 

s^uy  TEL:  (817)  727J200  FAX:  (6171  227-1754 


STATE  USE  ONLY 

Fee  Received: 

Check  No.:    

'Received  By: 


STATE  BUILDING  CODE  APPEALS  BOARD 
APPEAL  APPLICATION  FORM 


DOCKET  NUMBER: DATE: 

(State  Use  Only) 
The  undersigned  hereby  appeals  to  the  State  Board  of  Building  Regulations  and  Standarus  from  the  decision 
of  the: 

Building  Official  from  the  City/Town  of: 

Board  of  Appeals  from  the  City/Town  of: 

Other  Municipal  Agency/Official  entitled: 

State  Agency/Official  entitled: 

OTHER: . 

Dated: 19 ,  having  been  aggrieved  by  such  (check  as  appropriate) 

Interpretation     o  Order     o       Requirement      o  Direction        o 

Failure  to  Act     o  Other     o        Explain_ 


All  appropriate  code  sections  must  be  identified.  All  written  supporting  documentation  must  be 
submitted  with  this  application.  Parties  may  present  written  material  at  the  hearing.  However,  the 
Board  reserves  the  right  to  continue  the  proceeding  if  such  material  warrants  extensive  review. 

State  Briefly  desired  relief: 


APPELLANT: 


ADDRESS  FOR  SERVICE: 


Telephone  No. 


ADDRESS  OF  SUBIECT  PROPERTY: 


APPELLANT'S  CONNECTION  TO  SUBJECT  PROPERTY: 


SIGNATURE  OF  APPELLANT/REPRESENTATIVE  (NAME  -  PLEASE  PR[NT) 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  679 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


DESCRIPTION  OF  BUILDING  OR  STRUCTURE  RELATIVE  TO  THE  MASSACHUSETTS 
STATE  BUILDING  CODE  (780  CMR  6th  EDITION)     (Check  as  appropriate) 


Check  Here  if  Building  is  a  One  or  Two  Family  Dwelling  □  Proceed  to  section  entitled  "Brief  Description 
of  the  Proposed  Work!'  -  Do  not  complete  the  tables  below 


DESCRIPTION  OF  PROPOSED  WORK  (check  all  applicable) 


New  Construction]     Existing  Building  D     Repaiits) 


a    Alteration(s)  □  I  Addition 


Accessory  Bldg.   a 


Demolition 


Other  □    Specify: 


Brief  Description  of  Proposed  Work: 


USE  GROUP  AND  CONSTRUCTION  TYPE 


USE  GROUP  (Check  as  applicable) 


CONSTRUCTION  TYPE 


A  Assembly 


A-l 
A-4 


A-2 
A-5 


E  Educational 


F  Factory 


H  High  Hazard 


I  Institutional 


M   Mercantile 


R  Residential 


S  Storage 


U  Utility 


Specify:  . 


M   Mixed  Use 


Specify: 


S  Special  Use 


Specify:_ 


COMPLETE  THIS  SECTION  IF  EXISTING  BUILDING  UNDERGOING  RENOVATIONS,  ADDITIONS 
AND  /OR  CHANGE  IN  USE 


Existing  Use  Group: 

Existing  Hazard  Index  (780  CMR  34): 


Proposed  Use  Group: 

Proposed  Hazard  Index  (780  CMR  34): 


BUILDING  HEIGHT  AND  AREA 

BUILDING  AREA 

Existing  (if  applicable) 

Proposed 

Number  of  Floors  or  stories  include 
basement  levels 

Floor  Area  per  Floor  (sf) 

Total  Area  (sf) 

Total  Height  (ft) 

Brief  Description  of  the  Proposed  Work: 


680 


7S0  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 


SflcUe-  &ooj^  o£ cStu/ckfiO'  Soj&judatLaiu,  and Crtasit/axck' 

isncttojunacJi  Snd/e-  £//pce<  ZGiu/dings 

@ne,  S&ALis/osv  &lace.    -    !$oosrv/S01 

SSaUdrv,  ^JtaiAacAuAe&K      0& '-/OS 

TEL:  (817)  727J200  FAX:  (617)  227-1754 


WILLIAM  F  WELD 


KATHLEEN  M.  OTOOLE 


STATE  BUILDING  CODE  APPEALS  BOARD  -  SERVICE  NOTICE 


for  the 


Appellant/Petitioner 


in  an  appeal  filed  with  the 


State  Building  Code  Appeals  Board  on 


19 


HEREBY  SWEAR  UNDER  THE  PAINS  AND  PENALTIES  OF  PERJURY  THAT  IN  ACCORDANCE 
WITH  THE  PROCEDURES  ADOPTED  BY  THE  STATE  BOARD  OF  BUILDING  REGULATIONS  AND 
STANDARDS  AND  SECTION  122.3.1  OF  THE  STATE  BUILDING  CODE,  I  SERVED  OR  CAUSED  TO 
BE  SERVED,  A  COPY  OF  THIS  APPEAL  APPLICATION  ON  THE  FOLLOWING  PERSON(S)  IN  THE 
FOLLOWING  MANNER: 


NAME  AND  ADDRESS  OF 
PERSON/AGENCY  SERVED 


METHOD  OF  SERVICE 


DATE  OF  SERVICE 


Signature:  APPELLANT/PETITIONER 


On  the 


Day  of 


PERSONALLY  APPEARED 


BEFORE  ME  THE  ABOVE  NAMED 


(Type  or  Print  the  Name  of  the  Appellant) 
AND  ACKNOWLEDGED  AND  SWORE  THE  ABOVE  STATEMENTS  TO  BE  TRUE. 


NOTARY  PUBLIC 


MY  COMMISSION  EXPIRES 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


681 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Appendix  B-3 

Official  Interpretations  of  the  State  Building  Code  Pursuant  to  M.G.L.  c.  143,  §  94(e) 


682  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Official  Interpretation  No.  1-85 

DATE:  October  30,  1985 

SUBJECT:         State  Building  Code  Section  108.5.1 

Question  1:  Section  108.5.1  requires  the  periodic  inspection  of  certain  buildings,  and  the  issuance  of 
Certificates  of  Inspection  for  these  buildings  on  a  regular  basis.  The  standard  form  Certificate 
of  Inspection  which  was  developed  by  the  Commonwealth  states  that  "The  means  of  egress 
are  sufficient  for  the  following  number  of  persons"  and  provides  space  for  the  listing  of 
permitted  occupancy  load  by  story  and  by  place  of  assembly  Is  it  the  intent  of  the  Code  to 
require  a  complete  periodic  reinspection  of  the  entire  building  or  is  such  an  inspection  limited 
to  the  building's  egress  system? 

Answer  1:  No.    Section  108.5.1  states  in  part  "A  Certificate  of  Inspection  as  herein  specified  shall  not  be 

issued  until  an  inspection  is  made  certifying  that  the  building  or  structure  or  parts  thereof 
complies  with  ALL  the  applicable  requirements  of  this  Code  ..."  (emphasis  supplied)  The 
periodic  reinspection  is  not  necessarily  limited  to  the  building's  egress  system  but  may  extend 
throughout  to  the  entire  building,  or  parts  thereof  requiring  certification  The  Certificate  of 
Inspection  serves  as  a  spot  check  to  ensure  that  other  Code  mandated  procedures  have  been 
followed  (e.g.  permits  obtained  for  alterations)  and  that  the  building  has  been  maintained  in 
a  safe  condition.  The  building  has  been  maintained  in  a  safe  condition  The  building  official 
is  free  to  use  his  judgment  in  determining  how  extensive  a  periodic  inspection  need  be. 

Question  2:  Do  Code  requirements  for  periodic  reinspection  include  a  requirement  to  reinspect  by  wiring, 
plumbing,  gas  fitting  and  elevator  inspectors  for  compliance  with  the  various  applicable 
specialized  codes9 

Answer  2:  No.     The  Massachusetts  State  Building  Code  does  not  include  a  requirement  for  periodic 

reinspection  by  plumbing,  wiring,  gas  fitting  or  other  various  specialized  code  enforcement 
officials.  However,  periodic  inspections  conducted  by  the  building  official  may  reveal 
conditions  that  would  require  further  attention  by  local  wiring,  plumbing,  gas  or  elevator 
inspectors. 

Question  3:        May  a  professional  consultant  assume  or  be  granted  the  powers  and  duties  of  the  Building 

Official  to  issue  permits  and  certificates  or  may  he  merely  submit  a  report  for  the  Building 
Official's  review  and  acceptance? 

Answer  3  Section  114.1  states  in  part,  "The  Building  Commissioner  or  Inspector  of  Buildings  shall 

examine  or  cause  to  be  examined  all  applications  for  permits  and  amendments  thereto  within 
30  days  after  filing.  ...  If  he  is  satisfied  that  the  proposed  work  conforms  to  the  requirements 
of  this  Code  and  all  pertinent  law  applicable  thereto,  he  shall  issue  a  permit."  Only  a  Building 
Official,  appointed  in  accordance  with  Section  107  to  enforce  the  building  code  may  issue 
building  permits  and/or  related  certificates.  A  professional  consultant  may  submit  a  report  for 
the  Building  Official's  review,  but  the  issuance  or  denial  of  the  permit  or  certificate  is 
ultimately  the  Building  Official's  responsibility 

Question  4:        May  such  a  professional  consultant  be  hired  by  a  municipality  to  perform  inspections  in  the 

absence  of  any  "unusual  technical  issues"  as  described  in  Section  108.5,  or  should  the 
consultant  more  properly  be  engaged  by  the  building  owner  in  the  absence  of  unusual  technical 
issues? 

Answer  4:  A  professional  consultant  or  expert  retained  by  a  municipality  in  the  absence  of  any  "unusual 

technical  issues"  to  perform  inspections  would  be  required  to  meet  the  criteria  and 
qualifications  outlined  in  M.G.L.  c.  143,  §  3,  and  would  be  deemed  a  local  inspector,  and 
subject  to  all  pertinent  requirements  of  Code  and  law  However,  a  Building  Official  may 
review  and/or  accept  reports  from  other  qualified  personnel,  per  Section  111.21  (see  Question 
3). 


9/19/97  (Effective  2/28/97)  -  correction  780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Ouestion  5:        What,  if  any,  liability  under  the  Code  would  a  municipality  assume  in  utilizing  a  professional 
consultant  for  the  various  functions  described  above? 

Answer  5:  Opinions  relative  to  broad  legal  questions  of  liability  are  beyond  the  purpose  and  scope  of  the 

Board  of  Building  Regulations  and  Standards  Therefore,  we  must  decline  to  answer  this 
question,  and  would  direct  the  municipality  to  its  legal  advisor(s)  for  such  and  opinion. 

Official  Interpretation  No.  2-85 

DATE:  October  30,  1985 

SUBJECT:         State  Building  Code  Section  1 19.3 

Ouestion  J:        Do  All  existing  buildings  have  a  legal  use  group  classification  ,  whether  in  use  or  not? 

Answer  J:  Yes.    Section  202.1  states  "All  buildings  and  structures  shall  be  classified  with  respect  to  use 

in  one  (1)  of  the  use  groups  listed ...".  The  use  group  classification  is  based  on  the  purpose  for 
which  a  building  or  structure  is  designed,  used  or  intended  to  be  used  A  use  group 
classification  is  required  to  be  assigned  to  a  building  or  structure  whether  in  actual  use  or  not. 

Question  2:        On  what  is  the  legal  use  based7 

Answer  2:  The  Massachusetts  State  Building  Code  defines  use  as  "The  purpose  for  which  the  building 

or  structure  is  designed,  used  or  intended  to  be  used."  The  lawful  use  and/or  use  group 
classification  of  an  existing  building  may  be  based  upon  the  Building  Official's  records 
pertaining  to  the  particular  structure.  In  the  case  of  a  vacant  structure,  the  last  legal  use  of 
record  would  apply 

Question  3.         Does  the  legal  use  change  or  cease  to  exist  when  ownership  changes? 

Answer  3 :  No.  A  change  in  ownership  of  a  building  would  not  change  the  use  group  classification  of  the 

building  or  cause  the  use  to  cease.  A  change  of  use  and/or  occupancy  may  take  place 
regardless  of  ownership  when  done  in  accordance  with  a  permit  issued  by  the  Building 
Official. 

Does  the  use  have  any  relationship  with  ownership7 

The  use  and  ownership  are  only  related  in  that  the  owner,  as  defined  by  Code,  is  responsible 
to  comply  with  the  applicable  sections  of  the  Code  as  regard  to  use,  and  must  obtain  a  permit 
to  change  the  use  of  a  building 

Ouestion  4:        Is  there  ever  any  such  thing  as  "abandonment"  of  a  use  group  classification,  so  that  an  existing 
building  has  no  use  group9 

Answer  4.  No    All  buildings  are  required  to  be  classified  with  respect  to  their  use.  The  discontinuance 

or  "abandonment"  of  the  actual  using  of  a  building  or  structure  would  not  change  the  use  group 
classification  For  example,  a  vacant  office  building  (formerly  legally  occupied)  would 
remain  in  use  group  "B"  (Business  Buildings),  the  last  lawful  use  of  the  building,  until  a  permit 
was  obtained  to  change  that  use. 

Ouestion  5:        Upon  request  by  an  owner  for  a  certificate  of  use  and  occupancy,  is  the  Building  Official 
obligated  to  cite  in  writing  any  violation  of  law  or  orders  pending? 

Answer  5:  Yes.   If  there  are  violations  of  law  or  orders  pending,  the  provisions  of  Section  121.0  would 

apply  Section  121.2.1  states  that  every  notice  or  order  authorized  by  this  Code  shall  be  in 
writing  and  shall  be  served  on  the  person  responsible. 

Ouestion  6:        Can  the  use  of  a  building  or  portion  of  a  building,  subsequent  to  January  1,  1975,  legally 
change  without  the  issuance  of  a  building  permit  and  a  certificate  of  use  and  occupancy7 

Answer  6:  No.   Section  113.0  and  Section  1 13.1  state  that  a  permit  is  required  "...to  change  the  use  or 

occupancy  of  a  building  or  structure...". 


684 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Section  1 19.0  and  Section  119.2  state  "  A  building  or  structure,  in  whole  or  in  part,  altered  to 
change  from  one  use  group  to  another:  to  a  different  use  within  the  same  use  group... shall  not 
be  occupied  or  used  until  the  certificate  shall  have  been  issued  certifying  that  the  work  has 
been  completed  in  accordance  with  the  provisions  of  the  approved  permits...". 

The  Massachusetts  State  Building  Code  became  effective  on  lanuary  1,  1975.  All  changes  of 
use  or  occupancy  subsequent  to  lanuary  1,  1975  would  be  subject  to  the  provisions  of  the 
Code. 

Official  Interpretation  No.  3-85 

DATE:  October  30,  1985 

SUBJECT:         State  Building  Code  Section  609 .3 

Massachusetts  State  Building  Code  Section  609.2  requires  not  less  than  two  approved 
independent  exitways  serving  every  building  except  as  modified  in  Section  609.3. 

Massachusetts  State  Building  Code  Section  609.3  also  allows  one  exitway  in  a  building  of  the 
use  group  and  characteristics  as  specified  in  Table  609. 

Massachusetts  State  Building  Code  Section  609.3  also  allows  one  exitway  from  the  first  story 
of  a  building  when  the  first  story  is  2,000  square  feet  or  less  in  area  and  with  an  occupancy 
load  not  exceeding  50  persons.  Egress  from  other  stories  shall  comply  with  Article  6. 

Massachusetts  State  Building  Code  Section  609.2  also  specifies  not  less  than  two  approved 
independent  exitways  serving  every  story,  except  in  one  and  two  family  dwellings  and  as 
modified  in  Section  609.3. 

It  is  our  interpretation  that  Section  609.3  deals  with  two  distinct  and  separate  building  design 
configurations.  In  its  first  essence,  Section  609.3  provides  for  certain  buildings  (those 
complying  with  Table  609)which  are  required  to  have  only  one  exitway.  The  remaining 
sentences  in  Section  609.3  describe  conditions  (less  than  50  occupants  and  less  than  2,000 
square  feet  in  area)  in  which  the  first  story  only  of  any  building  is  required  to  have  only  one 
exitway.  Table  609  does  not  relate  to  the  latter  case. 

Official  Interpretation  No.  4-85 

DATE:  October  30,   1985 

SUBJECT:         State  Building  Code  Table  214  and  Section  217.4 

An  existing  three  story  building  is  proposed  to  be  of  type  3-C  constriction.  The  exterior  walls  have  a  fire 
separation  of  30  feet  or  more  and  the  walls  themselves  are  non-bearing.  The  loads  are  carried  by  a 
structural  steel  frame  and  there  are  structural  beams  and  columns  within  the  exterior  wall  which  are  part 
of  the  load  bearing  system.  Therefore,  the  steel  frame  is  load  bearing.  The  walls  themselves  are 
essentially  curtain  walls. 

Question:  Are  the  beams  and  columns  which  are  on  the  exterior  part  of  the  building,  required  as  load 

bearing  members,  to  have  a  two  hour  fire  rating? 

Answer:  No.   Table  214,  line  8  of  the  State  Building  Code  establishes  the  fire  resistance  rating  required 

for  the  columns  and  framing(beams)  and  does  not  require  a  fire  resistance  rating  for  columns 
or  beams  for  the  proposed  condition.  However,  it  should  be  noted  that,  per  Section  91 1.6, 
beams  which  support  walls  required  to  be  fire  resistance  rated  must  be  protected  to  afford  not 
less  than  the  fire  resistance  rating  of  the  wall  supported  and,  when  supporting  masonry  walls, 
must  carry  a  minimum  fire  resistance  of  one  hour.  Further,  it  should  be  noted  that,  if  the 
framing  supports  a  required  fire  separation  wall  such  as  an  exitway  enclosure,  Section  909.4 
would  require  this  framing  to  be  protected  to  afford  a  fire  resistance  rating  equal  to  the  wall 
supported. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  685 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Answer:  No.    The  exit  stairway  requirements  described  in  Sections  616  and  2101  of  the  Code  are 

intended  to  provide  a  stairway  of  certain  minimum  exit  capacity,  with  the  full  width  being 
available  for  occupant  egress,  at  an  incline  that  results  in  motion  familiar  to  the  occupants. 
Alternate  tread  stairways  are  intended  for  use  where  floor  space  is  limited  and  therefore  a 
steeper  than  usual  incline  is  required.  The  steeper  incline,  when  descending  the  stairway, 
requires  an  unfamiliar  foot  motion  more  downward  and  less  outward  than  that  typically 
required.  Imposing  such  an  unfamiliar  motion  on  occupants  exiting  the  building  during  a  life 
threatening  situation  is  unwarranted. 

The  Lapeyre  Alternating  Tread  Stair  exceeds  the  maximum  incline  permitted  by  Sections  616 
and  2101  and  will,  therefore,  require  an  unfamiliar  motion  by  the  occupants. 

In  addition,  the  overall  width  of  these  stairs  does  not  meet  the  minimum  width  requirement  of 
Sections  616  and  2101,  nor  would  the  exit  capacity  be  equal  to  that  of  a  full  stairway  if  the 
minimum  width  were  satisfied  since  these  stairs  do  not  permit  parallel  egress  of  individuals. 

The  Lapeyre  Alternating  Tread  Stair  is,  therefore,  not  permitted  as  an  element  of  a  required 
means  of  egress. 

Official  Interpretation  No.  13-88 
DATE:  October  25,  1988 

SUBJECT:         State  Building  Code  Section  2108 

Question:  A  single  family  dwelling  is  to  be  constructed  with  a  fuel-fired  water  heater  in  the  basement  and 

a  fireplace  lined  with  a  2  inch  thick  refractory  brick  on  the  first  floor.  What  construction  is 
required  to  separate  the  water  heater  flue  from  the  firebox  and  smoke  chamber  of  the  fireplace 
at  the  first  floor?  What  separation  is  required  within  the  chimney? 

Answer:  Section  2108.7.2  requires  that  the  firebox  of  a  fireplace  constructed  of  solid  masonry  and  lined 

with  refractory  brick  have  back  and  side  walls  of  at  least  8  inches  total  thickness. 

Section  2108.7.4.5  requires  that  the  walls  of  the  smoke  chamber  be  a  minimum  of  eight  inches 
thick.  Thus  a  minimum  of  eight  inches  of  solid  masonry  is  required  in  these  locations.  Once 
the  elevation  of  the  fireplace  flue  is  reached,  Section  2108.3.2.4  allows  two  adjoining  flues  to 
be  contained  in  the  same  chimney,  so  long  as  the  flue  liner  joints  are  staggered  at  least  seven 
inches.  If  this  staggering  of  flue  liner  joints  is  not  provided,  or  if  more  than  two  flues  are 
present,  Section  2108.3.2.5  requires  that  masonry  flue  partitions  of  at  least  four  inch  thickness, 
bonded  into  the  chimney  walls,  be  constructed  to  separate  the  flues. 

Official  Interpretation  No.  14-89 

DATE:  March  28,  1989 

SUBJECT:  State  Building  Code  Section  437  and  616.8 

Question  1:  Section  437.1.3.2  provides  that  "At  least  one  required  exitway  shall  be  accessible  without 
passage  through  an  atrium."  Section  437.2.2,  which  speaks  to  the  enclosure  of  atriums, 
contains  an  exception  which  provides  that  "The  adjacent  spaces  of  any  three  (3)  floors  of  the 
atrium  shall  not  be  required  to  be  separated  from  the  atrium;  however,  these  spaces  shall  be 
included  in  the  atrium  volume  according  to  Section  437.2."  Is  it  the  intent  of  Section  437.1.3.2 
to  require  at  least  one  required  exitway  to  be  accessible  without  passage  through  an  atrium  on 
those  floors  exempted  by  Section  437.2.2  from  the  requirement  for  separation  from  the  atrium? 

Answer  1:  No.   The  exception  in  Section  437.2.2  allows  the  designer  to  eliminate  atrium  separations  on 

any  three  floors  so  long  as  the  additional  spaces  on  these  floors  are  added  to  the  atrium  volume 
for  purposes  of  sizing  the  smoke  control  requirements  of  the  atrium.  What  this  allowance 
essentially  does  is  to  add  these  adjacent  spaces  to  the  atrium.  It  is  impossible  to  provide  an  exit 
which  is  accessible  without  passage  through  an  atrium  for  spaces  within  that  atrium.  The 
provisions  of  Section  437.1.3.2  are  intended  to  ensure  that  spaces  outside  the  atrium  need  not 
depend  on  the  viability  of  the  atrium  in  order  to  gain  access  to  an  exitway.  Therefore,  these 
provisions  are  not  applicable  for  any  spaces  which  are  already  included  in  the  atrium  space, 
including  those  spaces  added  when  the  exception  in  Section  437.2.2  is  applied. 


688 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Question  2:        Is  it  the  intent  of  the  Code  that  stairways  conforming  to  Section  616.8  and  escalators 
conforming  to  Article  16  be  subject  to  the  requirements  of  Section  437.3. 1? 

Answer  2:  Not  necessarily.    It  is  intended  that  unenclosed  supplemental  stairways  be  prohibited  from 

connections  with  (required)  exit  stairways  and  exitway  access  corridors,  and  that  these 
unenclosed  supplemental  stairways  be  equipped  with  a  draft  stop  conforming  to  Section 
437.3.1.  While  there  are  no  provisions  in  the  Code  text  to  require  that  escalators  be  classified 
and  protected  as  floor  openings,  it  is  possible  that  escalators  can  be  so  classified.  However, 
escalators  may  also  be  enclosed  in  fire  resistance  rated  construction,  or  may  be  located  within 
an  atrium.  A  supplemental  stairway  may  also  be  enclosed  in  fire  resistance  rated  construction, 
or  may  be  located  in  an  atrium,  and  may  therefore  not  be  classified  as  a  floor  opening. 

Sequential  Gap  -  Official  Interpretation  Number  15 

Official  Interpretation  No.  16-89 

DATE:  August  29,  1989 

SUBJECT:         State  Building  Code  Ssections  616 

Question:  Does  the  installation  of  a  handicapped  stair  lift  in  a  required  exit  stairway  constitute  an 

obstruction  to  the  means  of  egress? 

Answer:  Yes.  Section  616  of  the  State  Building  Code  makes  the  following  provisions: 

"Stairways  shall  not  reduce  in  width  in  the  direction  of  exit  travel.  Projections  into  a  stairway 
are  prohibited  except  for  handrails  as  indicated  in  Section  616.5.1  and  for  stairway  stringers 
which  may  project  not  more  than  one  and  one-half  inches."  (616.2.3) 

"The  least  dimension  of  landings  and  platforms  shall  be  not  less  than  the  required  width  of 
stairway."  (616.3.1) 

"Stairways  shall  have  continuous  guards  and  handrails  on  both  sides..."  (616.5) 

"An  exitway  enclosure  shall  not  be  used  for  any  purpose  other  than  means  of  egress."  (616.9.2) 

Moreover,  Section  605  states  that  "It  shall  be  unlawful  to  obstruct,  or  reduce  in  any  manner, 
the  clear  widths  of  any  doorway,  hallway,  passageway  or  any  other  exitway  required  by  the 
provisions  of  this  code."  Section  605  also  requires  that  "All  required  means  of  egress 
components  shall  at  all  times  be  maintained  in  a  safe  usable  condition." 

Handicapped  stair  lifts  installed  in  required  egress  stairs  can  conceivably  violate  all  of  the 
above  sections.  When  in  use,  such  lifts  render  at  least  a  portion  of  a  stairway  unusable.  Even 
when  not  in  use,  the  lift  equipment  projects  into  the  required  width,  interferes  with  the  use  of 
handrails,  and  presents  a  potential  tripping  hazard  to  persons  using  the  stair.  Also,  the 
introduction  of  this  equipment  into  a  stair  enclosure  does,  in  a  sense  utilize  an  exitway 
enclosure  as  an  elevator  shaft,  and  there  is  the  possibility  that  the  equipment,  motor,  and  wiring 
can  catch  fire,  thereby  rendering  the  exitway  unusable.  There  is  also  reason  to  expect  that  loss 
of  primary  electrical  power  in  an  emergency  situation  could  disable  the  lift  in  a  position  where 
it  would  present  a  greater  obstruction  than  when  not  in  use.  For  these  reasons,  we  conclude 
that  the  installation  of  inclined  stairway  chairlifts  in  required  exitway  stairways  is  potentially 
hazardous,  and  is  therefore  not  permitted.  However,  the  building  official  may  allow  the 
installation  of  such  lifts  in  stairways  which  are  not  a  component  of  the  required  means  of 
egress,  so  long  as  the  building  official  determines  that  the  particular  installation  is  not 
hazardous.  It  is  the  policy  of  the  Department  of  Public  Safety,  Division  of  Inspection,  Elevator 
Section  to  require  a  letter  of  approval  from  the  building  official  before  granting  a  permit  for 
an  inclined  stairway  chairlift. 

Official  Interpretation  No.  17-89 

DATE:  October  24,  1989 

SUBJECT:         State  Building  Code  Section  1216 

Question:  Under  the  new  (ASME/ANSI  A  17  1)  elevator  code,  smoke  detectors  are  required  in  the 

elevator  lobby  for  elevator  control  Are  these  same  smoke  detectors  required  to  be  tied  into 
the  fire  alarm  system? 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


689 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Answer:  Yes.  NfiPA  72 A,  the  applicable  fire  protection  standard  referenced  in  Section  1216. 1,  requires 

that  these  detectors  be  tied  into  the  fire  alarm  system. 

Official  Interpretation  No.  18-90 
DATE:  February  27,  1990 

SUBJECT:       State  Building  Cods  Section  1QQ6.2 

Question:  Is  the  "direct  venting"  (through-the-sidewall  combustion  product  exhaust  venting)  of  "listed" 

comfort  heating  and  comfort  cooling  appliances  allowed  in  lieu  of  venting  to  a  masonry 
chimney  as  required  in  Section  1004  of  the  State  Building  Code? 

Answer:  Yes,    Section  1006  of  the  State  Building  Code  (the  Code)  defines  "listed  appliances"  and 

Section  1006.2  addressing  appliances  to  be  vented  states: 

-  "Appliances  shall  be  connected  to  a  listed  venting  system  or  provided  with  other  means 
for  exhausting  the  flue  gasses  to  the  outside  atmosphere  in  accordance  with  the  venting 
system  selection  chart  contained  in  the  mechanical  code  listed  in  Appendix  B." 

In  Section  1001.2,  the  Code  recognizes  that  appliances  required  to  be  vented  "shall  be 
connected  to  a  vent  or  chimney..."  and  in  Section  1002  addresses  the  performance  test  and 
acceptance  criteria  to  insure  safe  and  proper  performance  of  the  venting  system. 

Direct  venting  systems  that  are  "listed"  or  are  part  of  a  listed  appliance  conform  to  the 
requirements  of  the  Code. 

Official  Interpretation  No.  19-90 

DATE:  December  11,  1990 

SUBJECTS:       of  Section  602.1  of  the  Fifth  Edition  of  the  State  Building  Code  and.  BBRS  Approval  of  the 
Use  of  Power  Venters 

In  order  to  immediately  correct  an  inadvertent  oversight  in  Section  602. 1  of  the  Fifth  Edition  of  the  State 
Building  Code,  at  is  meeting  of  November  20,  1990,  the  Board  unanimously  voted  that  it  should  reflect 
the  provisions  of  M.G.L.  c.  148,  §§  26A  and  26A'/i  and,  therefore,  should  read  - 

602.1  Applicability:  the  provisions  of  this  section  shall  apply  to  all  buildings  more  than  70  feet 
above  mean  grade,  except  that  the  provisions  of  this  section  shall  not  apply  to  airport  traffic 
control  towers  conforming  to  the  requirements  of  Section  616.0. 

By  way  of  clarification,  Section  602.1,  as  cited  in  the  Fifth  Edition,  is  in  conflict  with  statutory 
requirements  of  2  counts: 

1 .  It  ties  high  rise  provisions  to  floors  used  for  human  occupancy  and  located  more  than  70 
feet  above  the  lowest  level  of  fire  department  vehicle  access;  whereas,  the  governing  statues 
identify  high  rise  buildings  as  all  buildings  of  more  than  70  feet  in  height  above  the  mean 
grade;  and 

2.  The  cited  section  in  the  Fifth  Edition  measures  from  the  lowest  level  of  fire  department 
vehicle  access;  whereas,  the  statutes  measure  from  mean  grade. 

As  you  know,  statutory  requirements  govern  and  in  this  case  also  reference  the  high  rise 
provisions  of  the  State  Building  Code. 

POWER  VENTERS 

Power  Venters,  as  contained  in  Section  2513  of  the  Fifth  Edition,  are  ONLY  allowed  for  use 
WITH  GAS  OR  OIL  FERED  comfort  heating  and/or  cooling  appliances.  Approval  from  the 
BBRS  is  required  for  use  with  solid  fuel  burning  appliances. 


690  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Official  Interpretation  No.  21-91 

DATE:  July  30,  1991 

SUBJECT:  Section  908  1  of  the  Fifth  Edition  of  the  State  Building  Code  as  related  to  attached  dwelling 

units  (Use  Group  R-3).  in  which  the  units  are  separated  bv  interior  lot  lines. 

Question:  a)     When  side  by  side  attached  single  family  dwelling  units  (Use  Group  R-3)  are  constructed 

such  that  the  exterior  wall  of  each  is  located  at  the  lot  line  which  divides  them,  will  two  one- 
hour  rated  wood  stud  walls  comply  with  Section  908.1  (Fire  Walls  and  Party  Walls)  of  the  5th 
Edition  of  the  Code? 

b)  Could  the  two  walls  referred  to  in  question  a)  above  be  supported  on  a  single  foundation 
wall. 

A/mver:  a)     For  multiple  attached  single  family  dwelling  units,  (Use  Group  R-3),  which  are  separated 

by  interior  lot  lines,  the  intent  of  section  908.1  is  satisfied  by  the  construction  of  a  single  fire 
separation  wall  having  a  fireresistance  rating  of  one-hour.  Such  fire  separation  walls  may  be 
used  between  attached  dwelling  units  providing  that  the  wall  construction  meets  the 
requirements  of  Section  910  and  the  sound  transmission  ratings  of  Section  714.  and  that  the 
allowable  area  limitations  between  fire  walls  of  Table  501  are  not  exceeded.  Fire  walls, 
constructed  in  accordance  with  Section  908,  are  required  when  the  allowable  area  limitations 
of  table  501  are  reached,  (e.g.  4800  sf  per  floor  for  multiple  attached  single  family  dwelling 
units,  Use  Group  R-3). 

b)  The  wall  referenced  in  answer  a)  above  may  be  supported  one  a  single  concrete  or  masonry 
foundation  wall  of  equivalent  or  greater  fire  resistance  rating. 

Discussion:         Section  908. 1  of  the  Code  requires  party  walls  to  be  constructed  as  fire  walls  if  an  interior  lot 
line  is  present.      Furthermore,  the  fire  walls      "....shall  be  constructed  of  any  approved 
noncombustible  materials  providing  the  required  strength  and  fireresistance  rating  specified 
in  Table  401  for  the  type  of  construction,  but  not  less  than  the  fire  grading  of  the  use  group 
specified  in  Table  902.   Strength ". 

The  argument  can  be  made  that  such  party  walls  can  be  considered  to  be  exterior  walls,  thus 
causing  the  requirements  of  section  908.1  to  be  in  conflict  with  the  exterior  wall  fireresistance 
requirements  of  Table  906.2  (for  fire  separations  of  five  feet  or  less). 

Table  906.2  requires  an  exterior  wall  fireresistance  rating  of  one  hour  for  a  fire  separation 
distance  of  zero  feet.  If  two  dwelling  units  were  constructed  on  adjacent  lots  and  each  were 
constructed  on  the  common  lot  line,  such  that  the  fire  separation  distance  of  each  unit  was  zero, 
Table  906.2  would  require  each  exterior  wall  to  have  a  fireresistance  rating  of  one  hour. 
However,  Code  requirements  for  multiple  single  family  attached  dwelling  units  when  interior 
lot  lines  are  not  present,  table  401  would  simply  require  the  construction  of  dwelling  unit 
separation  walls  with  a  fireresistance  rating  of  one  hour,  between  dwelling  units.  It  would 
appear  to  be  inconsistent  to  require  the  same  R-3  structure  to  have  a  greater  degree  of  fire 
safety  due  simply  to  the  separation  of  the  dwelling  units  by  an  imaginary  lot  line. 

Official  Interpretation  No.  22-91 

DATE:  September  24,  1991 

SUBJECT:         Section  2102. 4(\)  of  the  Fifth  Edition  of  the  State  Building  Code  as  it  relates  to  reconstruction 
in  Coastal  High  Hazard  Areas  following  Storm  Damage. 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Tuesday  24,  September 
1991,  the  Board  approved  the  following  interpretation  of  Section  2102.4(1)  of  the  5th  Edition  of  the 
Massachusetts  State  Building  Code,  effective  immediately. 

Question:  When  a  structure  is  located  in  a  Coastal  High  Hazard  Area  ("V"  zone)  and  is  swept  from  its 

foundations  during  a  storm,  and  the  building  remains  intact  but  the  foundation  system  is 
completely  destroyed,  does  the  code  require  that  the  structure  be  constructed  on  an  elevated 
pile  foundation,  in  accordance  with  Section  2102.4  ? 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


691 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Answer:  Yes.   The  structure,  as  described  would  be  considered  to  be  substantially  damaged  and  as  such 

would  be  required  to  be  provided  with  a  new  foundation  system.  Section  3203.3,  the 
foundation  system  would  constitute  a  "new  system",  as  defined  in  Section  3201  and  therefore 
would  be  required  to  be  constructed  to  meet  the  requirements  for  new  construction.  Since  the 
structure  is  located  within  a  "V"  zone,  Section  2102.4(1)  would  require  the  structure  to  be 
elevated  on  piles. 

Question:  When  a  structure  is  located  in  a  Coastal  High  Hazard  Area  ("V"  zone)  and  is  swept  from  its 

foundations  during  a  storm,  and  both  the  building  and  foundation  system  remain  intact  and  if 
the  costs  associated  in  relocating  the  building  onto  its  existing  foundation  system  are  less  than 
50%  of  the  market  value  of  the  structure  prior  to  the  damage,  does  the  code  require  that  the 
structure  be  constructed  on  a  raised  pile  foundation,  in  accordance  with  Section  2102.4  ? 

Answer:  No.  If  both  the  foundation  system  and  structure  are  intact  and  the  cost  associated  in  relocating 

the  structure  to  its  pre-damaged  condition,  then  the  structure  is  permitted  to  be  relocated  on  the 
existing  foundation  unless,  in  the  opinion  of  the  building  official,  under  Section  101.3— the- 
proposed  reconstruction  would  constitute  an  unsafe  structural  condition,  in  which  case  the 
structure  should  be  elevated  in  accordance  with  Section  2102.4(1). 

Official  Interpretation  No.  23-91 

DATE:  September  30,  1991 

SUBJECT:         Section  816  of  the  Fifth  Edition  of  the  State  Building  Code  as  It  Relates  to  Requirements  for 
Stairways 

Date  of  Interpretation: 

The  State  Board  of  Building  Regulations  and  Standards,  at  it's  regular  monthly  meeting  of  September  24, 
1991,  affirmed  the  following  requirements: 

Question:  To  what  extent  are  the  provisions  of  Massachusetts  State  Building  Code,  Section  816, 

applicable  to  a  stairway  providing  access  to  an  attic  area  in  a  business  establishment;  said  attic 
area  used  for  the  storage  of  stock  used  in  conjunction  with  that  business? 

Answer:  Section  816,  INTERIOR  STAIRWAYS,  (in  conjunction  with  Section  819,  EXTERIOR 

STAIRWAYS),  of  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  requires  that  all 
stairways,  whether  interior  or  exterior,  required  or  supplemental,  must  be  so  constructed  to 
satisfy  the  applicable  requirements  imposed  for  interior  exit  stairways. 

This  means  that  for  interior  or  exterior,  required  or  supplemental  stairways,  the  width, 
headroom,  stairway  allowed  width  restrictions,  the  allowed  dimensions  of  platforms  and 
landings,  the  acceptable  vertical  rise  between  landings  and  platforms,  riser  height  and  tread 
depth  and  the  dimensional  uniformity  required  between  adjacent  risers  and  treads  and  the 
requirements  for  stairway  guards  and  handrails  are  controlled  by  the  requirements  of  Section 
816. 

Note  1:  If  classified  as  a  mezzanine,  then  the  subject  attic  area  would  fall  under  the  requirements  of 

Section  605  of  the  State  Building  Code;  otherwise  such  area  would  be  treated  as  an  additional 
story  of  the  building,  with  the  resulting  classification  determining  what  applicable  State 
Building  Code  requirements  apply. 

Note  2:  Only  fixed,   interior   or   exterior,    required   or   supplemental   stairways   (dimensions   and 

handrail/guardrail  requirements)  are  controlled  by  Section  816  -  ladder  type  stairs  and  "pull- 
down", non-fixed  stair  systems  are  not  explicitly  regulated  by  the  Building  Code. 

Note  3:  Article  34,  Section  3401,  still  controls  dimensions  and  handrail/guardrail  requirements  for 

fixed  stairways  in  one  and  two  family  detached  dwellings. 


692 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Official  Interpretation  No.  24-92 

DATE:  January  28,  1992 

SUBJECT:         Section  1205  of  the  Fifth  Edition  of  the  State  Building  Code  as  it  relates  to  Frost  Protection  for 
Fence  Posts 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Tuesday  28,  January, 
1992,  the  Board  approved  the  following  interpretation  of  Section  1205  of  the  5th  Edition  of  the 
Massachusetts  Slate  Building  Code,  effective  immediately. 

Question:  Is  it  the  intent  of  the  Code  to  require  a  four  foot  deep  concrete  footing  to  the  posts  of  a  fence 

up  to  six  feet  in  height  ? 

Answer:  No.  The  requirement  of  section  1205,  which  requires  protection  against  frost  for  footings  for 

permanent  structures  is  not  applicable  to  minor  fences  such  as  described  in  the  above  question. 

In  certain  fence  applications,  post  embedment  depths  of  four  feet  or  more  may  indeed  be 
required  for  fences  of  unusual  size,  or  fences  which  are  subjected  to  unusual  loading  conditions 
(such  as  a  prison  security  fence,  for  instance  which,  in  addition  to  wind  loads,  may  also  be 
subjected  to  vehicle  impact  loads).  However,  it  is  not  the  intent  of  the  Code  to  require  frost 
protection  for  fences  which  are  only  four  feet  in  height. 

As  an  example  consider  the  construction  of  a  four  foot  high  chain  link  fence,  erected  as  a 
property  line  demarkation.  The  required  post  embedment  depth  is  determined  by  a  number  of 
factors  including;  the  height  of  the  fence;  the  applied  horizontal  loads;  the  nature  of  the  soil 
and;  the  intended  function  of  the  fence.  Specific  reference  related  to  post  embedment  depths 
can  be  found  in  ASTM  F  567-84  "  Standard  Practice  for  Installation  of  Chain  Link  Fence", 
and  although  not  specifically  referenced  in  the  Code,  is  a  recognized  national  standard  of 
practice.  Sections  4.1  and  4.8  of  ASTM  F  567-84  specify  minimum  post  embedment  depths 
of  24  inches  and  36  inches,  for  concrete  encased  and  driven  posts,  respectively,  when  used  in 
the  construction  of  a  four  foot  high  chain  link  fence.  For  this  particular  type  of  fence,  it  is 
unlikely  that  movement  due  to  frost  heave  would  result  in  a  life  safety  hazard  or  cause  serious 
damage.  However,  it  is  incumbent  upon  the  designer  to  make  this  determination  on  a  site 
specific  basis  (and  to  submit  his  determination  to  the  local  building  official  for  approval)  and 
prepare  the  design  accordingly. 

In  summary,  the  intent  of  the  Code  relating  to  these  issues  is  expressed  in  Section  3 1 1 .0,  USE 
GROUP  U,  UTILITY  AND  MISCELLANEOUS  USES,  which  states  ..."  Buildings  and 

Structures  of  an  accessory  character. shall  be  constructed  equipped  and  maintained  to 

meet  the  requirements  of  this  code  commensurate  with  the  fire  and  life  hazard  incidental  to 
their  use,  [emphasis  added]  Utility  and  miscellaneous  uses  shall  include  fences  over  6  feet 
high,  tanks,  cooling  towers,  retaining  walls  and  buildings  such  as  private  garages,  carports, 
sheds  and  agricultural  buildings".  The  phrase  "commensurate  with  the  fire  and  life  hazard 
incidental  to  their  use"  is  the  key  phrase  to  consider,  as  it  provides  the  necessary  guidance  to 
the  designer  and  building  code  official  to  avoid  the  "blanket"  literal  interpretation  of  the 
requirements  of  Section  1205  and  other  inappropriate  sections  of  the  Code. 

Official  Interpretation  No.  25-92 

DATE:  January  28,  1992 

SUBJECT:  Section  921.6  2  of  the  Fifth  Edition  of  the  State  Building  Code  as  it  relates  to  Firestopping 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Tuesday  28  January, 
1992,  the  Board  approved  the  following  interpretation  of  Section  921.6.2  of  the  5th  Edition  of  the 
Massachusetts  State  Building  Code,  effective  immediately. 

Question:  In  a  building  which  has  suspended  ceilings  and  vertical  partitions  extending  to  the  underside 

or  suspended  horizontal  membrane  of  the  ceiling,  is  it  the  intent  of  Section  921.6.2  to  require 
firestopping  at  the  top  of  the  partitions  to  eliminate  the  open  connection  between  the  vertical 
wall  openings  and  the  horizontal  ceiling  space  ? 

If  firestopping  is  required,  is  the  requirement  applicable  to  combustible  and  noncombustible 
construction  ? 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


693 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Answer:  If  the  vertical  partition  does  not  penetrate  the  ceiling  membrane,  (i.e.  if  the  partition  terminates 

at  the  underside  of  the  plane  of  the  ceiling)  there  is  effectively  no  connection  between  the 
horizontal  space  above  the  ceiling  and  the  vertical  space  within  the  partition,  therefore 
firestopping  is  not  required.  If,  however,  the  vertical  partition  penetrated  the  plane  of  the 
ceiling,  firestopping  would  be  required  at  the  interface  of  the  ceiling  and  partition.  For  this 
situation,  the  firestopping  would  be  required  whether  the  partition  and  ceiling  materials  were 
combustible  or  noncombustible. 

Official  Interpretation  No.  26-92 

DATE:  January  28,  1992 

SUBJECT:         Sections  706.1  and  707.1  of  the  Fifth  Edition  of  the  State  Building  Code  as  related  to 
Mechanical  Ventilation  of  Non  Public  Bathrooms 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Tuesday  28,  January, 
1992,  the  Board  approved  the  following  interpretation  of  Section  706.1  and  707.1  of  the  5th  Edition  of 
the  Massachusetts  State  Building  Code,  effective  immediately. 

Question:  Can  a  bathroom  exhaust  fan  exhaust  into  an  enclosed  ventilated  attic  space  which  has  soffit 

vents  in  conjunction  with  continuous  ridge  vents  or  eaves  vents. 

Answer:  No.      Section  707.1  requires  that  "  Mechanical  ventilation,  when  provided,  shall  conform  to 

the  requirements  of  the  BOCA  National  Mechanical  Code  listed  in  Appendix  A,  unless 
expressly  defined  within  this  Code,  and  may  be  substituted  for  the  requirements  for  natural 
ventilation." 

Article  16  of  the  BOCA  National  Mechanical  Code  (1987)  lists  the  required  mechanical 
ventilation  air  in  Table  1602.2. 

Section  M-1604.1  (Mechanical  Exhaust)  of  the  BOCA  National  Mechanical  Code  (1987) 
states,  in  part,  that  "....  The  exhaust  shall  discharge  directly  to  an  approved  location  on  the 
exterior  of  the  building". 

Warm,  moist  air  exhausted  from  bathroom  spaces  would  condense  in  the  cooler  attic  space, 
even  if  the  attic  space  were  adequately  ventilated.  Moisture  from  condensation  will  eventually 
cause  damage  to  wood  framing  members  (or  sheathing),  insulation  and  ceiling  materials  and 
may  pose  a  threat  of  fire  if  electrical  circuitry  is  contacted. 

Sequential  Gap  27  and  28 


Official  Interpretation  No.  29-92 

DATE:  January  12,  1993 

SUBJECT:         Articles  6.  8  and  9 


Smoke  Protection  in  Egress  Corridors  of  Fully  Suppressed  Buildings 


Question  1:  In  a  fully  sprinklered  building,  is  it  the  intent  of  Section  810.4.1  of  the  Fifth  Edition  of  the 
Massachusetts  State  Building  Code  (the  Code)  that  egress  corridors  be  constructed  so  as  to 
serve  as  an  effective  barrier  to  limit  the  transfer  of  smoke? 

Answer  1:  Yes,  for  USE  GROUPS  where  "sleeping  uses"  are  involved. 

The  BOCA  National  Building  Code/1987  Commentary,  for  Section  810.4.1  (the  Massachusetts 
Code,  utilizes  the  BOCA  Building  Code  language  for  this  Section)  states  that  Section  810.4.1 
"...acknowledges  that  an  automatic  fire  suppression  system  can  serve  to  control  or  eliminate 
fire  development  which  could  threaten  the  exit  access  corridor.  The  nonsleeping  occupancies 
are  permitted  to  have  nonrated  corridors  if  the  suppression  system  is  installed  throughout  the 
area  served  by  the  corridor  as  well  as  the  corridor  itself.  "In  the  sleeping  uses  ...the  corridor 
fireresistance  is  reduced  to  one-half  hour.  The  purpose  of  the  fireresistance  rated  corridor  is 
not  only  to  provide  a  fire  endurance  capability,  but  mainly  to  provide  a  quality  of  construction 
that  would  ensure  such  walls  would  serve  effectively  as  barriers  to  smoke.  The  dwelling  unit 
(sleeping  uses)  separation  walls,  while  reduced  to  one-half  hour,  are  to  be  constructed  tight  to 
the  ceiling  above  (tight  to  the  underside  of  the  floor/roof  deck  above  or  tight  to  the  lated 
floor/ceiling  assembly  above),  to  complete  the  barrier  to  smoke  function." 


694 


780  CMR-  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

The  interpretation  provided  above  is  no!  meant  to  imply  that  Section  8 10.4  requires  satisfying 
Section  911  -  "SMOKE  BARRIERS",  as  "SMOKE  BARRIERS"  are  unique  to  certain 
"defend-in-place"  concepts,  specifically  associated  with  Section  610.5,  1-2  USE. 

Note  that  Section  810.4.1  does  allow  that  when  an  approved  fire  suppression  system  is 
installed  and  supervised  in  accordance  with  Section  1020.1,  parts  1,  2  or  3,  and  has  its  water 
flow  alarm  device  connected  to  an  approved  central  station  system,  proprietary  system  or 
remote  station  system  of  the  jurisdiction,  a  fire  resistance  rating  for  exit  access  corridors,  and 
tenant  separation  walls  which  are  also  corridor  walls,  is  not  required  in  USE  GROUPS  A  B, 
E,  F,  M  and  S. 

Question  2:  In  a  fully  sprinklered  building  of  USE  GROUP  1-2,  is  it  the  intent  of  Section  610.4  of  the  Fifth 
Edition  of  the  Massachusetts  State  Building  Code  (the  Code)  that  egress  corridors  be 
constructed  so  as  to  serve  as  an  effective  barrier  to  limit  the  transfer  of  smoke? 

Answer  2:  Yes  -  Section  610.4  clearly  states  that  "...in  buildings  equipped  throughout  with  an  approved 

automatic  fire  suppression  system,  the  corridor  wall  fireresistance  rating  is  not  required 
provided  the  corridor  walls  form  a  barrier  to  limit  the  transfer  of  smoke." 

The  BOCA  National  Building  Code/1987  Commentary,  for  Section  610.4  (the  Massachusetts 
Code,  utilizes  the  BOCA  Building  Code  language  for  this  Section)  states  that  "...if  the  building 
is  protected  throughout  with  an  automatic  fire  suppression  system,  thereby  reducing  the 
possibility  that  a  fire  will  develop  which  is  life-threatening  to  persons  outside  the  room  of 
origin,  the  corridor  walls  need  only  be  able  to  resist  the  passage  of  smoke." 
"...when  the  building  is  protected  with  an  automatic  fire  suppression  system,  the  primary 
concern  is  to  contain  the  smoke  since  the  suppression  system  is  expected  to  suppress  and 
thereby  contain  the  fire." 

The  interpretation  provided  above  is  noj  meant  to  imply  that  Section  610.4  requires  satisfying 
Section  911  -  "SMOKE  BARRIERS",  unless  a  wall  of  the  exit  access  corridor  is  intended  to 
be  a  "SMOKE  BARRIER"  wall.  "SMOKE  BARRIERS"  are  unique  to  certain  "defend-in- 
place"  concepts,  specifically  associated  with  Section  610.5, 1-2  USE. 

Question  3:  In  fully  sprinklered  buildings  of  USE  GROUPS  R-l,  R-2  and  1-2,  is  it  the  intent  of  the  Code 
that  smoke  dampers  be  provided  at  duct  penetrations  through  the  unrated  corridor  walls? 

Answer  3:  No,  provided  in  the  case  of  the  1-2  USE,  the  corridor  wall  is  not  a  portion  of  a  "SMOKE 

BARRIER"  (Section  911.5  would  require  a  smoke  damper  in  a  "SMOKE  BARRIER"/I-2 
USE). 

Note  that  the  Code  is  effectively  silent  on  the  use  of  "smoke  dampers",  but  does  provide 
guidance  in  Section  918,  on  the  use  of  "fire  dampers".  Section  918.2  states  that  "fire  dampers" 
shall  be  provided  at  locations  where  air  distribution  systems  penetrate  assemblies  required  to 
have  a  fireresistance  rating",  thus  the  R- 1  and  R-2  USES,  having  a  one-half  hour  rating  would 
require  "fire  dampers"  but  not  smoke  dampers"  -  the  1-2  USE  corridor  walls,  if  not  a  portion 
of  a  "SMOKE  BARRIER"  -  Section  91 1  -  would  not  be  rated  and  would  not  require  a  "fire 
damper". 

Exceptions  to  Section  918.2  "fire  damper"  requirements  include  exception  no.  3  to  Section 
918.2,  where: 

Exception  3  states  that  a  fire  damper  is  not  required  "...at  penetrations  of  tenant  separation  and 
corridor  walls  in  buildings  equipped  throughout  with  an  approved  automatic  fire  suppression 
system."  Here,  the  1987  Commentary  states  that  "since  an  automatic  fire  suppression  system 
reduces  the  potential  for  duct  collapse,  fire  dampers  are  not  required  to  protect  penetrations  of 
tenant  separation  and  corridor  walls  in  buildings  protected  throughout  with  an  approved 
automatic  suppression  system." 

Utilizing  this  same  reasoning,  a  smoke  damper  would  not  be  required  as  it  is  not  expected  that 
a  fire  can  develop  sufficiently  in  R-l  and  R-2  or  1-2  buildings  that  are  fully  suppressed,  thus 
the  level  of  "passive  defense"  required  in  corridor  construction  (where  such  corridor  walls  are 
not  part  of  a  "SMOKE  BARRIER" A-2  USE),  is  limited  to  the  corridor  walls  being  constructed 
tight  to  the  ceiling  above  (tight  to  the  underside  of  the  floor/roof  deck  above  or  tight  to  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


695 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

rated  floor/ceiling  assembly  above),  to  complete  the  barrier  to  smoke  function  and  thus  limit 
the  transfer  of  smoke  in  the  exit  corridors  of  these  "sleeping  occupancies. 

Question  4:  In  fully  sprinkJered  buildings  of  USE  GROUP  1-2,  is  it  the  intent  of  the  Code  to  allow  the  use 
of  flexible  duct  (designed,  listed  and  installed  per  the  requirements  of  Section  M-303  of  the 
BOCA  National  Mechanical  Code/ 1987)? 

Answer  4:  Yes.  As  is  noted  in  answers  #1,  #2,  and  #3  above,  the  Code  now  places  great  emphasis  on 

"active  defense"  in  the  form  of  full  suppression  and  would  allow  the  use  of  flexible  duct  when 
designed,  listed  and  installed  per  the  BOCA  National  Mechanical  Code/1987  and  additionally 
satisfies  the  requirements  of  NFiPA-90A  in  the  case  of  the  1-2  USE. 

Official  Interpretation  No.  30-93 

DATE:  March  9,  1993 

SUBJECT:         of  Table  401.  Item  12  of  the  Fifth  Edition  of  the  State  Building  Code  as  it  relates  to  the  Use 
of  Skylights  in  Fire  resistance  Rated  Roof  Construction 

Question:  Is  it  the  intent  of  the  Code  to  allow  the  use  of  unrated  skylights  in  roof  construction  that  is 

required  to  have  a  fire  resistance  rating  under  the  provisions  of  item  12  of  table  401,  by  virtue 
of  the  type  of  construction  and  height  from  the  floor  to  the  lowest  structural  member  ? 

Answer:  Yes.  The  intent  of  the  fire  resistance  rating  requirements  of  table  401  are  (in  protected 

construction)  to  offer  a  degree  of  protection  to  the  structural  members  of  the  roof  system  in 
order  to  prevent  premature  structural  collapse  of  the  roof. 

For  a  particular  type  of  construction,  the  degree  of  fire  resistance  required  by  table  401  to  be 
provided  for  the  roof  construction  is  consistent  with  the  protection  required  for  the  remainder 
of  the  structural  elements  of  the  building.  Damage  caused  to  a  skylight  during  a  fire  event  will 
not  promote  premature  structural  collapse  of  a  rated  roof  system. 

Question:  Is  it  the  intent  of  the  code  to  allow  a  roof  assembly,  which  is  required  to  be  rated  under  table 

401  (item  12),  to  be  constructed  wholly  of  non  rated  skylights. 

Answer:  Yes.  Provided  that  the  following  conditions  exist: 

a.  the  structural  members  of  the  roof  system  are  protected  in  accordance  with  the 
requirements  of  table  401; 

b.  the  subject  building  does  not  require  the  roof  to  be  rated  under  the  provisions  of  section 
906.5.  If  the  roof  system  is  required  to  be  rated  due  to  vertical  protection  issues  of  section 
906.5,  unrated  skylights  are  prohibited  from  being  located  within  fifteen  feet  of  the  adjacent 
building. 

Question:  Are  opening  protectees  required,  in  accordance  with  Section  906.5,  for  exterior  wall  openings 

which  are  located  less  than  fifteen  feet  vertically  above  the  roof  of  an  adjacent  lower  building, 
if  the  adjacent  lower  building  has  a  roof  assembly  fire  resistance  rating  of  one  hour  or  greater 
and  the  roof  assembly  contains  unrated  glass  skylights  ? 

Answer:  Yes.    Section  906.5  requires  opening  protectives  for  exterior  wall  openings  in  an  adjacent 

higher  building  if  the  openings  are  located  less  than  fifteen  feet  vertically  above  the  lower  roof 
and  the  adjacent  buildings  are  separated  horizontally  by  a  distance  less  than  fifteen  feet,  unless, 
the  roof  construction  of  the  lower  roof  has  a  fire  resistance  rating  of  one  hour  or  greater.  Fire 
in  the  lower  building  may  be  a  source  of  exposure  to  openings  in  an  adjacent  higher  building 
if  the  fire  were  to  breech  the  roof  construction.  If  the  roof  of  the  lower  building  has  a  fire 
resistance  rating  which  affords  the  degree  of  safety  against  collapse  of  the  roof,  the  potential 
for  spread  of  fire  to  the  adjacent  (and  taller)  building  would  exist  if  fire  penetrated  the  skylights 
and  if  the  skylights  were  located  within  fifteen  feet  vertically  and  fifteen  feet  horizontally  of 
the  skylight.  Section  906.5  does  not  require  exterior  wall  opening  protectives,  even  if  the 
lower  adjacent  roof  assembly  is  unrated  provided  that  the  buildings  are  separated  horizontally 
by  a  fire  separation  distance  of  over  fifteen  feet. 

Therefore  skylights  would  be  permitted  in  rated  roof  construction  of  the  lower  roof  without  the 
need  for  exterior  wall  opening  protectives  if  either  the  buildings  were  separated  horizontally 


696 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

fifteen  feet  greater,  if  the  skylights  were  a  distance  of  fifteen  feet  or  more  from  the  adjacent 
exterior  wall,  or  if  the  adjacent  exterior  wall  openings  were  greater  than  fifteen  feet  above  the 
lower  roof  level. 

Official  Interpretation  No.  31-93 

DATE:  April  13,1993 

SUBJECT:         of  Section  1133  and  Section  201.0  Definitions  fownerl  of  the  Fifth  Edition  of  the  State 
Building  Code  as  it  relates  to  the  definition  of  owner. 


Question  1: 


Answer  1: 


If  a  contractor  is  hired  by  an  owner,  is  the  contractor  considered  an  agent  under  the 
definition  of  owner  (Section  201.0)  ? 

Yes 


Question  2:        What  information  would  be  necessary  to  qualify  that  the  contractor  was  an  agent  ? 

Answer  2:  The  contractor  would  need  to  produce  (1)  a  letter  stating  that  he/she  has  been  granted  the 

authority  to  act  as  an  agent  or  (2)  a  copy  of  a  written  contract  signed  by  the  owner  and  the 
contractor  as  specified. 

Question  3:  Can  a  city  or  town  refuse  to  issue  a  permit  to  a  contractor  with  (1)  a  letter  stating  that  they 
may  act  as  an  agent  or  (2)  with  a  signed  contract  between  the  two  parties  to  remodel  or 
construct  a  structure  simply  because  he/she  is  not  the  owner  of  the  structure  or  property  ? 

Answer  3:  No.    The  definition  of  owner  (Section  201.0  owner)  states  "  Every  person  who  alone  or 

jointly  or  severally  with  others 

(b)  has  care,  charge  or  control  of  any  building  or  structure  in  any  capacity  ".  The 

contractor  is  considered  to  have  control,  care  or  charge  of  the  building  during  the  time  of 
construction  as  ling  as  the  contractor  has  a  letter  stating  that  he/she  is  authorized  to  take  out 
a  permit  (  act  as  an  agent  of  the  owner)  or  the  contractor  has  a  signed  contract  with  the 
owner. 

Official  Interpretation  No.  32-93 

DATE:  May  14,  1993 

SUBJECT:  of  Section  827.1  of  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  as  it  relates 
to  when  guardrails  are  required. 

Question  I:  Is  the  30  inch  elevation  intended  to  be  the  limit  above  which  guardrails  are  required  to  be 
installed  in  accordance  with  Section  827.1  ? 

Answer  1:  Yes.  It  is  generally  established  in  the  BOCA  National  Building  Code  (1987)  that  when  the 

height  difference  between  the  walking  surface  and  the  adjacent  lower  walking  surface  or 
grade  is  30  inches  or  greater,  guardrails  are  required  to  be  provided. 

Question  2:  Is  the  30  inch  difference  in  elevation  intended  to  be  the  point  at  which  guardrails  are  required 
for  ramps  in  addition  to  stairs  or  walking  surfaces  ? 

Answer:  No.    Ramps  are  required  to  be  provided  with  guardrails  (if  the  ramp  has  an  open  side) 

irrespective  of  the  difference  in  elevation  between  the  ramp  and  the  adjacent  walking 
surface. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


697 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Official  Interpretation  No.  33-93 
DATE:  May  14,  1993 

SUBJECT:  Section  1 14  3  of  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  as  it  relates 

building  permit  extensions 

Question:  May  a  building  official,  if  work  has  not  begun  as  required  under  a  building  permit,  within 

the  six  month  period  after  the  issuance  of  such  permit,  issue  an  extension  of  time  for  a  period 
of  more  than  six  months. 

Answer:  No.  Section  1 14.3  states  that  the  building  permit  shall  be  considered  abandoned  unless  the 

work  authorized  by  it  shall  have  commenced  within  six  months  after  its  issuance.  Section 
1 14.3  permits  the  building  commissioner  or  inspector  of  buildings,  for  cause,  to  grant  one 
or  more  extensions  of  time,  for  periods  not  exceeding  six  months,    {emphasis  added}. 

Building  permit  extensions  may  be  granted  for  periods  of  greater  than  six  months  by 
variance  from  a  local  or  State  Building  Code  Appeals  Board  pursuant  to  sections  126  of  the 
Building  Code. 

Official  Interpretation  No.  34-93 

DATE:  September  28,  1993 

SUBJECT:         Requirements  of  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  for  "Permanent 

Foundations".  "Frost-Protected  Foundations"  and  the  Building  Inspector's  Responsibilities 

Under  "Doubtful  U-.e  Classification" 

Question  1:  Do  Sections  1205.1  or  3402.3.4  of  the  Massachusetts  State  Building  Code  (the  Code) 
mandate  that  all  buildings  and  structures  that  are  constructed,  be  placed  on  "permanent", 
frost-protected  foundation  systems? 

Answer  1:  No.  Neither  Section  1205. 1,  nor  3402.3.4  mandate  permanent  supports  for  all  buildings  and 

structures,  but  rather  state  that  where  permanent  supports  exist,  they  shall  be  frost-protected 
in  a  certain  way  (in  order  for  supports  to  be  considered  "permanent",  they  must  satisfy  the 
requirements  of  either  Section  1205.1  or  3402.3.4  of  the  Code). 

Question  2:  Does  the  State  Building  Code  allow  for  other  than  frost-protected  foundation  systems  or 
permanent  foundation  systems  for  new  construction  building  and  structures? 

Answer  2:  Yes. 

(The  issue  of  when  such  non-permanent  foundation  systems  should  be  allowed,  often  arises 
when  the  Building  Official  is  confronted  with  a  "Doubtful  Use"  or  "Utility  Use"  building  - 
typically,  storage  sheds,  carports,  landscape  type  structures  such  as  detached  gazebos,  etc.). 

Question  3:  As  the  Code  does  allow  for  other  than  frost-protected  or  permanent  foundation  systems  in 
buildings  and  structures,  what  Code  guidance  is  provided  to  assess  whether  or  not  frost- 
protected/permanent  foundation  systems  are  required  for  new  construction  buildings  and 
structures? 

Answer  3:  Article  3  of  the  Code,  Sections  301  through  313,  address  USE  classification,  and  review  of 

same  will  lead  the  reader  to  Sections  311.1  and  312.1  of  the  Code. 

Section  311.1,  in  part,  states:  "Buildings  and  structures  of  an  accessory  character  and 
miscellaneous  structures  not  classified  in  any  specific  use  group  shall  be  constructed, 
equipped  and  maintained  to  meet  the  requirements  of  this  code  commensurate  with  the  fire 
and  life  hazard  incidental  to  their  use.  Utility  and  miscellaneous  uses  shall  include...  carports, 
sheds  and  agricultural  buildings."  (note  underlining  emphasis  added). 

Section  312.1,  in  part,  states:  "When  a  building  or  structure  is  proposed  for  a  use  not 
specifically  provided  for  in  this  code,  or  the  classification  of  which  is  doubtful,  such  building 
or  structure  siiall  be  included  in  the  use  group  which  it  most  nearly  resembles  in  respect  to 
the  existing  or  proposed  life  and  fire  hazard,  and  it  shall  be  so  classified  by  the  building 
official."  (note  underlining  emphasis  added). 


698 


780  CMR-  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Review  of  these.  Article  3  subsections,  reveals  that  use  classification,  under  utility  or 
doubtful  use,  allows  -  in  fact,  mandates  -  that  the  Building  Official  make  a  judgement  call 
and  that  the  classification  of  use  be  commensurate  with  the  fire  and  life  hazard  incidental  to 
the  use  of  the  structure.  On  this  basis,  if,  in  the  judgement  of  the  Building  Official  (which 
is  required  to  be  made  under  Section  312.1),  a  utility  type  structure,  such  as  a  shed,  would 
have  a  low  fire  and  life  hazard,  the  Building  Official  could  allow  a  non-frost-protected,  non- 
permanent  foundation  system. 

Official  Interpretation  No.  35-94 

DATE:  April  12,  1994 

SUBJECT:         Referenced  Standards  adopted  as  listed  in  Appendix  A. 

Question:  Some  of  the  reference  standards,  as  listed  in  Appendix  A,  give  the  local  authority  having 

jurisdiction  the  power  to  amend  or  vary  the  requirements  of  certain  provisions  contained 
within  the  standard.  Does  this  mean  that  a  building  official  may,  (or  the  fire  official,  when 
reviewing  plans  pursuant  to  article  10)  when  requested,  or  on  his  or  her  own  initiative,  waive 
or  vary  said  requirements. 

Answer:  No.  The  Board  adopts  the  technical  content  of  the  reference  standards,  as  written,  but  retains 

jurisdiction  to  adjudicate  all  variance  requests  pursuant  to  M.G.L.  c.  143,  §  100.  The 
variance  must  be  pursued  through  the  appeals  process  pursuant  to  Section  126  of  the 
Building  Code  and  must  be  heard  at  the  State  level  or  by  local  or  regional  Building  Code 
Appeals  Board  if  local  or  regional  boards  exist  within  your  jurisdiction. 


Official  Interpretation  No.  36-94 

DATE:  April  12,  1994 

SUBJECT:         Design  of  Connections  in  Structural  Steel  Braced  Frames 
1113.5  72 


Sections  1113  5  2  2(a)  and 


Question:  What  design  force  should  be  considered  for  the  members  of  a  braced  frame  constructed  of 

structural  steel  9 

Answer:  The  connection  of  members  in  a  structural  steel  braced  frame  shall  be  designed  for  not  less 

than  the  lesser  of  the  following  forces; 

a.  1 .25  (one  point  twenty  five)  times  the  force  determined  in  accordance  with  Section 
1113.4.1,  without  the  allowable  Vfe  (one  third)  stress  increase  or; 

b.  The  full  axial  capacity  of  the  member,  based  on  0.6  (zero  point  six)  Fy  multiplied  by  the 
member  gross  cross  sectional  area. 

This  is  a  minimum  requirement  and  may  be  followed  in  lieu  of  Section  1 1 13.5.7.2. 


DATE:  April  12,  1994 

SUBJECT:         Formal  Interpretation  Number  36-94 

The  seismic  advisory  committee,  at  its  meeting  of  April  7,  1994,  voted  to  approve  the  attached  formal 
interpretation  number  36-94  relating  to  the  design  of  connections  in  structural  steel  frames.  Vie 
request  for  the  interpretation  was  submitted  by  Weidlinger  Associates,  Inc.  on  December  6,  1993. 

Advisory  Ruling  No.  1-94 

DATE:  April  14,  1994 

SUBJECT:         Section  1 19.1  of  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  as  it  relates  to 
the  Issuance  of  the  Certificate  of  Occupancy 


Question: 


If  a  conflict  occurs  between  a  building  official  and  other  local  agencies  as  to  whether  or  not 
a  certificate  of  use  and  occupancy  (c/o)  is  to  issue  for  a  building  or  structure,  what  action 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


699 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

should  the  building  official  take  pursuant  to  Section  119.1  of  the  Fifth  Edition  of  the 
Massachusetts  State  Building  Code? 

Answer:  The  building  official  has  the  authority  to  issue  a  c/o  pursuant  to  Section  1 19.1.  If  a  conflict 

is  created  with  other  local  agencies  as  a  result  of  the  issuance  of  the  c/o,  the  aggrieved 
party/parties  may,  in  accordance  with  M.G.L.  c.  143,  §100,  appeal  to  the  State  Building  Code 
Appeals  Board  Any  person  aggrieved  by  a  decision  of  the  State  Building  Code  Appeals 
Board  may  appeal  to  a  court  of  law  or  equity  in  conformance  with  M.G.L.  C.30A  §14. 

Official  Interpretation  No.  38-94 

DATE:  August,  16,  1994 

SUBJECT:  Use  of  a  Registered  Professional  Engineers  Seal  as  Required  under  Section  s  1 13.5.2  and 
127 

Discussion:  Section  1 13.5  2  requires  the  seal  of  a  qualified  registered  professional  engineer  or  architect 
be  contained  on  all  plans  and  specifications  for  buildings  and  structures  containing  over 
35,000  cubic  feet  of  enclosed  space.  Additionally  section  127.2.1  requires  that  all  plans 
computations  and  specifications  involving  new  construction,  alterations  repairs,  expansions 

or  additions  shall  be  prepared  by a  registered  professional  architect  or  engineer  and 

shall  bear  his  signature  and  seal 

The  Board  of  Registration  of  Professional  Engineers  and  Land  Surveyors  (the  Board  of 
Registration)  is  the  Board  having  statutory  authority  to  register  professional  engineers  in  the 
Commonwealth  of  Massachusetts.  The  Board  of  Registration  registers  engineers  by 
discipline,  perhaps  the  those  most  related  to  the  construction  of  buildings  and  structures 
being  civil,  mechanical,  HVAC,  structural,  sanitary,  electrical  and  fire  protection. 

Question  I:  Consider  the  situation  where  a  set  of  plans  and  specifications  are  filed  with  the  building 
official  at  the  permit  application  stage  for  an  automatic  fire  suppression  (sprinkler)  system. 
The  plans  and  specifications  bear  the  seal  and  signature  of  a  Massachusetts  Registered 
Professional  Structural  (or  any  other  discipline)  Engineer.  Do  the  plans,  as  filed  comply 
with  section  1113.5.2  and  127.2.1  ?  Additionally,  is  it  required  that  the  discipline  of  the 
engineer  to  be  shown  on  the  plans  ? 

Answer  1:  The  plans  and  specifications  may  be  sealed  by  an  engineer  of  any  discipline  with  the 

following  conditions;. 

The  Board  of  Registration's  regulations  250  CMR  are  the  rules  and  regulations  relating  to 
the  practice  of  engineering  and  land  surveying. 

The  Board  of  Registration  initially  registers  an  engineer  in  one  branch  of  engineering  only, 
following  a  determination  that  the  engineer  has  been  found  competent  by  education, 
experience  and  specific  examination  passed  by  the  registrant.  The  branch  of  engineering  in 
which  the  engineer  is  registered  shall  either  be  included  as  part  of  the  seal,  or  shall  be 
handwritten  above  the  registrant's  signature  (250  CMR  3.05(2). 

The  Board  of  Registration's  regulations  250  CMR  3.05(7)  requires  the  engineer  to  limit 
professional  practice  to  areas  of  professional  competence  as  demonstrated  to  and  approved 
by  (emphasis  added}  the  Board  of  Registration. 

The  Board  of  Registration  does  not  limit  the  engineer  to  the  discipline  in  which  he/she  is 
registered  but  allows  the  registrant  to  practice  in  branches  of  engineering  outside  that 
indicated  on  his/her  seal  provided  that  he  he/she  has  demonstrated  competence  to  the  Board 
of  Registration.  (250  CMR  3.05(6)  A  registrant  who  wishes  to  practice  engineering  in  an 
area  of  competence  other  than  that  in  which  registered  may  request  a  determination  of 
competence  by  submitting  such  evidence  as  may  be  required  by  the  Board  of  Registration). 
The  Board  of  Registrations  regulations  mandate  that  the  burden  of  proof  of  competence  rests 
with  the  registrant  should  a  question  be  raised  as  to  that  competence.  The  Board  of 
Registration  is  the  only  authority  empowered  to  determine  competency  and  will  do  so  if 
requested  by  the  registrant  or  any  person  or  entity.  The  entity  could  be  a  city  or  town  and 
an  individual  could  be  the  building  official  acting  in  his  official  capacity  or  acting  as  a 
private  citizen. 


700 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Question  2:  Under  the  requirements  of  construction  control  (section  127),  does  the  building  official  (or 
the  fire  official  when  reviewing  plans  pursuant  to  Article  10)  have  to  accept  the  seal  of  any 
Massachusetts  registered  professional  engineer  even  if  the  discipline  noted  on  said  seal  is 
not  the  discipline  associated  with  the  reports,  design,  plans  or  specifications  under  the 
building  permit  review  ? 

Answer  2:  No,  the  building  official  (or  the  fire  official  when  reviewing  plans  pursuant  to  Article  10) 

does  not  have  to  accept  the  seal.  In  the  case  where  the  seal  is  a  different  discipline  than  the 
work  contained  in  the  report,  design,  plans  or  specifications,  or  where  the  reviewing  official 
believes  there  is  a  question  of  competency,  the  building  official,  may  require  that  the 
registered  professional  engineer  demonstrate  competence,  in  accordance  with  the  Board  of 
Registration's  regulations  (250  CMR  3.05(6)  or  (7)).  When  the  registrant's  competency  is 
questioned,  it  is  incumbent  upon  the  registrant  to  apply  to  the  Board  of  Registration  for  a 
determination  of  competency.  It  is  not  the  responsibility  of  the  building  (or  fire)  official  to 
make  a  determination  relative  to  competency,  but  it  is  perfectly  permissible  for  a  building 
(or  fire)  official  to  request  that  the  registrant  prove 


Official  Interpretation  No.  39-94 

DATE:  July  12,  1994 


SUBJECT: 


The  Impact  on  the  State  Building  Code  Due  to  the  May  17.  1994  Emergency  Updating  of 
Reference  Standards  in  Appendix  A  fNFiPA  Reference  Standards') 


Question  J:  At  its  May  17,  1994  Public  Hearing,  the  Board,  via  emergency  adoption,  updated  numerous 
NFiPA  reference  standards  in  Appendix  A  of  the  Code  -  did  the  Board,  by  this  action,  intend 
to  cause  substantive  changes  to  the  explicit  regulatory  requirements  of  the  Code  proper? 

Answer  J:  No.  The  Board  was  simply  updating  Appendix  A  reference  standards  to  reflect  currently 

available  NFiPA  reference  standards;  there  was  no  intention  to  change  explicit  requirements 
of  the  Code  proper. 

Question  2:  As  NFiPA  72-1993,  the  "NATIONAL  FIRE  ALARM  CODE"  is  one  of  the  reference 
standards  that  was  updated  at  the  May  17,  1994  Public  hearing  and  as  Section  2-2.1.1.1  of 
NFiPA  72-93  requires  that  in  new  residential  construction,  there  be  smoke  detectors  installed 
in  each  sleeping  room,  would  this  requirement  supersede  smoke  detector  requirements 
historically  mandated  by  the  Code? 

Answer  2:  No.  As  indicated  in  the  response  to  the  first  question,  above,  there  was  no  intention  on  the 

part  of  the  Board  to  cause  substantive  changes  to  the  explicit  requirements  of  the  Code  when 
Appendix  A  reference  standards  were  updated  in  May  of  1994. 

Also,  Section  101.4  of  Article  1  of  the  Code  states  that:  "Where  differences  occur  between 
provisions  of  this  Code  and  referenced  standards,  the  provisions  of  this  Code  shall  apply." 

In  the  case  of  smoke  detector  requirements  for  residential  occupancies.  Section  1018  of  the 
Code  is  explicitly  prescriptive  relative  to  the  required  location  for  smoke  detectors  and 
therefore  supersedes  the  installation  requirements  of  NFiPA  72-93. 

Official  Interpretation  No.  41-94 
DATE:  August  15,  1994 

SUBJECT:  Section  109. 1.1.1  -  The  Use  of  Municipal  Construction  Supervisor  Licenses  in 
Municipalities  Where  Such  Licensing  was  Established  Prior  to  January  1.  1975 

Background'Discussion: 

Section  109.1.1.1  does  not  prohibit  a  municipality  from  requiring  a  license  for  individuals 
engaged  in  directly  supervising  persons  engaged  in  construction,  reconstruction, 
alteration. ..in  those  categories  of  buildings  and  structures  for  which  the  BBRS  is  not 
requiring  a  license. 

Section  109  1.1.1  goes  on  to  say;  provided  that  those  municipalities  which  have  established 
licensing  requirements  for  construction  supervisors  prior  to  January  1,  1975  may  maintain 
their  existing  licensing  requirements. 


2/7/97    (Effective  2/28/97) 


780  CMR -Sixth  Edition 


701 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

As  a  result  of  a  Building  Code  Appeal,  a  BBRS  Appeals  Board,  on  March  18,  1992, 
unanimously  agreed  that  no  municipality  can  implement  building  licensing  regulations  that 
conflict  with  those  promulgated  by  the  Commonwealth.  The  City  of  Boston  was  ordered:  (1) 
"to  immediately  issue  appropriate  building  permits  to  the  appellants,  provided  such  work 
falls  within  the  scope  of  their  State  Construction  Supervisor's  Licenses";  (2)  "to  immediately 
cease  the  illegal  activity  of  denying  building  permits  to  holders  of  valid  State  Construction 
Supervisor's  Licenses,  provided  such  work  falls  within  the  scope  of  such  State  Construction 
Supervisor's  Licenses";  and  (3)  to  immediately  cease  the  illegal  activity  of  issuing  building 
permits  to  holders  of  Boston  Builders  Licenses,  but  who  do  not  hold  a  valid  State 
Construction  Supervisor's  License,  where  such  work  falls  within  the  scope  of  the  State 
Construction  Supervisor's  License  program." 

Question:  Considering   the   current    practice   of  many   Building   Departments   requiring   a   State 

Construction  Supervisor's  License  (CSL)  or  a  Municipal  Construction  License  (of  that 
Municipality,  only)  and  where  such  Municipal  License  was  established  prior  to  January  1, 
1975,  is  the  Board,  via  the  Board  of  Appeal  ruling  of  March  18,  1992,  ruling  that  all  building 
permits  awarded  to  holders  of  such  Municipal  Licenses  are  invalid  and  illegal? 

Also,  is  it  the  Board's  intent  to  propose  a  Code  Change  to  Section  109.1.1.1  eliminating 
Construction  Licensing  by  Municipalities  when  such  Municipal  Licensing  was  established 
prior  to  January  1,  1975? 

Answer:  The  Board  decision  of  March  18,  1992  was  tied  to  the  City  of  Boston  refusing  to  issue 

building  permits  to  holders  of  State  CSL's  and  was  based  on  the  language  of  St.  1972,  c.  802, 
§  75,  which  states  "All  by-laws  and  ordinances  of  cities  and  towns  in  conflict  with  the  state 
building  code  shall  cease  to  be  effective  on  January  1,  1975." 

The  Board  is  charged  with  promulgating  a  single  uniform  building  code  for  the 
Commonwealth  and  Section  109.1.1.1  of  the  Code  is  an  explicit  portion  of  said  Code  and 
may  be  formally  interpreted  by  the  Board.  To  this  end,  it  is  the  Board's  position  that  Section 
109. 1.1.1,  for  Municipalities  that  had  appropriate  construction  supervisor  licensing  programs 
in  effect  prior  to  January  1,  1975,  such  Municipalities  may  maintain  their  existing  practices 
of  accepting  either  their  local  Municipal  construction  supervisor  license  or  the  State  CSL  - 
Note  that  a  building  permit  may  not  be  denied  to  holders  of  valid  State  CSLs  (provided  such 
work  falls  within  the  scope  of  the  State  CSL)  even  though  such  holders  of  the  State  CSL  do 
not  have  the  Municipal  construction  supervisor's  license,  also  note  that  the  holder  of  a  local 
Municipal  construction  supervisor  license  may  not  utilize  that  license  in  another 
Municipality  but  must  possess  the  State  CSL  when  performing  building  permittable  work 
within  the  scope  of  the  State  CSL  in  a  community  without  a  valid,  local  Municipal 
construction  supervisor  license  program. 

Official  Interpretation  No.  42-94 

DATE:  September  13,  1994 

SUBJECT:         Section  1011.2-  Acceptable  Discharge  Testing  of  Wet  Chemical  Range  Hood  Extinguishing 
Systems 

Background/Discussion: 

Section  1011.2,  "TESTS",  in  part,  states  that:  "a  completed  system  shall  be  tested  by  a 
discharge  of  wet  chemical  in  sufficient  amounts  to  verify  that  the  system  is  properly  installed 
and  functional." 

In  reality,  that  portion  of  the  sprinkler  installation  industry  installing  specialized  commercial 
kitchen  suppression  tests  the  various  pre-engineered  wet  chemical  systems,  not  by 
discharging  wet  chemical,  but  rather  by  utilizing  pressurized  gas  -  this  industry  approach 
allows  for  determination  that  piping  to  spray  nozzle  integrity  exists  and  that  nozzles  are  not 
blocked,  but  does  not  create  a  clean-up  problem  nor  does  such  testing  wet  up  the  internals 
of  the  piping  /nozzle  system. 

NfiPA  17A,  "STANDARD  ON  WET  CHEMICAL  EXTINGUISHING  SYSTEMS" 

and  which  is  referenced  in  Section  1011  defines  pre-engineered  wet  chemical  extinguishing 
systems  as  those  having  predetermined  flow  rates,  nozzle  pressures,  and  quantities  of  liquid 


702 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

agent.  Such  systems  may  have  specific  pipe  sizes,  maximum  and  minimum  pipe  lengths, 
flexible  hose  specifications,  number  of  fittings,  and  number  and  types  of  nozzles  prescribed 
by  a  testing  laboratory.  The  hazards  protected  by  these  pre-engineered  systems  are 
specifically  limited  as  to  type  and  size  by  a  testing  laboratory.  Limitations  on  hazards  that 
can  be  protected  and  piping  and  nozzle  configurations  are  contained  in  the  manufacturer's 
listed  installation  and  maintenance  manual  which  is  part  of  the  listing. 


Question: 


Answer: 


NfiPA  17A  also  notes  that  where  required  by  the  authority  having  jurisdiction,  the  approval 
tests  shall  include  a  discharge  of  wet  chemical  (such  a  test  is  not  mandated,  however,  by 
NFiPA  17 A)  -  the  Standard  further  notes  that  the  method  of  verification  shall  be  acceptable 
to  the  authority  having  jurisdiction. 

Discussions  with  a  major  manufacturer  of  pre-engineered  wet  chemical  range  hood 
extinguishing  systems  indicates  that  since  the  basic  system  is  a  pre-engineered  listed 
product,  acceptance  testing  of  the  entire  wet  chemical/piping/nozzle  system  need  only 
consist  of  ensuring  piping  integrity  and  further  ensuring  that  the  installed  nozzles  are  not 
blocked  and  a  full,  wet  chemical  discharge  for  acceptance  testing  of  a  pre-engineered  system 
is  not  necessary  and  a  simplified  gas  discharge  test  would  suffice. 

For  pre-engineered  wet  chemical  range  hood  extinguishing  systems  as  discussed  in  Section 
1011  of  the  Code,  is  it  acceptable  to  substitute  a  pressurized  gas  discharge  test  for  the  full 
wet  chemical  discharge  test  as  required  by  Section  101 1.2? 

YES,  for  pre-engineered  systems,  since  such  systems  are  tested,  listed  systems,  it  is 
sufficient  for  acceptance  testing  that  a  simple  gas  discharge  test  that  ensures  down  stream 
piping  integrity  and  further  ensures  that  spray  nozzles  are  not  blocked,  would  be  an 
acceptable  test  approach  since  the  intent  of  the  Code  is  to  ensure  that  the  installed  range 
hood  extinguishing  system  is  functioning. 

Note  that  it  would  also  be  acceptable  to  test  in  accordance  with  the  pre-engineered  system 
manufacturer's  recommendations. 


Official  Interpretation  No.  43-95 

DATE:  May  9,  1995 

SUBJECT:         Section  600  3  -  Impact  of  Section  600.3  on  Egress  Requirements  of  Sections  63 


638 


636  and 


Background  Discussion: 

Section  600.3  is  language  excerpted  directly  from  the  1987  BOCA  National  Building  Code 
and  directly  adopted  into  the  Fifth  Edition  of  the  Massachusetts  State  Building  Code  -  it's 
noted  that  the  requirements  of  Section  600.3  of  the  1987  BOCA  National  Building  Code 
were  dropped  in  the  1990  version  of  the  BOCA  National  Building  Code  and  additionally, 
such  requirements  are  also  absent  in  the  latest,  1993  BOCA  National  Building  Code. 

In  the  current  Massachusetts  State  Building  Code,  Section  600.3  ,  "MEANS  OF  EGRESS" 
states:  "The  means  of  egress  for  buildings  of  special  uses  and  occupancies  shall  conform  to 
the  requirements  of  Article  8,  except  as  is  modified  by  more  restrictive  provisions  of  this 
article  for  specific  uses." 

This  language  is  sufficiently  broad  so  that  one  current  interpretation  of  this  Section  is  to 
require  in  Section  631,  636  and  638  residences  EXIT  SIGNS  and  LIGHTS  in  accordance 
with  Section  823  of  Article  8  and  MEANS  OF  EGRESS  LIGHTING  in  accordance  with 
Section  824  of  the  Code. 

Section  631,  "GROUP  RESIDENCE";  Section  636,  "LIMITED  GROUP  RESIDENCE", 
and  Section  638,  "GROUP  DWELLING  UNITS"  are  sections  of  the  Code  that  were 
developed  on  a  consensus  basis  in  conjunction  with  DMR/DMH/OFC**  input  and  the 
specific  requirements  contained  within  these  sections  are  intended  to  stand  alone  as  express 
life-safety  requirements  for  these  special  uses  . 

The  adoption  of  Section  600.3  of  the  1987  BOCA  National  Building  Code  was  nol  intended 
to  impose  additional  signage  and  lighting  requirements  in  these  dwelling  units  although 
should  certain  of  these  dwelling  units  be  located,  for  example,  in  an  R-2  USE  apartment 
building,  the  common  egress  areas  of  the  apartment  building  would  be  required  by  Code  to 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


703 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

possess  exit  signage  and  lighting  appropriate  to  the  building  but  exit  signage  and/or  lighting 
for  the  dwelling  unit  proper  and  not  expressly  required  by  Section  63 1  or  636  or  638  would 
not  be  required  in  the  dwelling  unit. 

**  Department  of  Mental  Retardation  (DMR);  Department  of  Mental  Health  (DMH); 
Office  for  Children  (OFC) 

Question:  Does  Section  600.3,  "MEANS  OF  EGRESS"  of  the  Code  require  that  the  requirements  of 

Section  823,  "EXIT  SIGNS  AND  LIGHTS"  and/or  Section  824,  "MEANS  OF  EGRESS 
LIGHTING"  automatically  be  imposed  on  dwelling  units  falling  under  Sections  631,  636 
and  638  respectively? 

Answer:  No.  Numerous  dwelling  units  with  respect  to  Sections  63 1,  636  or  638  are  found  in  one-  or 

two-family  buildings  of  R-4  or  R-3  USE  and  it  is  not  the  intention  of  the  Code  to  require  exit 
signage  or  means  of  egress  lighting  in  such  dwelling  units  unless  expressly  required  by  the 
special  Section.  For  example,  the  specific  requirements  of  Section  636.3.3.10  requires 
MEANS  OF  EGRESS  LIGHTING  in  accordance  with  Section  824,  but  nowhere  in  Section 
636  is  there  a  requirement  for  EXIT  SIGNS  and  EXIT  LIGHTS. 

Residences  licensed  under  Sections  631,  636  and  638  are  defined  as  RESIDENTIAL  USES 
and  are  noj  classified  as  INSTITUTIONAL  USE;  therefore  only  the  Iighting/signage 
requirements  of  63 1,  636  and  638  proper  are  to  be  imposed  on  the  dwelling  units  of  these 
residences  -  note  the  deliberate  term  "dwelling  unit"  as  opposed  to  the  term  "building".  A 
Section  638  "GROUP  DWELLING  UNIT"  ,  for  example,  could  be  found  in  an  R-2  USE 
apartment  building,  and  by  Code,  the  common  egress  areas  of  the  R-2  building  would 
require  exit  signage,  lights  and  means  of  egress  lighting,  but  the  Section  638  dwelling  unit 
proper  would  not  require  such  signage  and  lighting  unless  expressly  required  by  Section  638 
and  /or  other  sections  of  Code  expressly  referenced  in  Section  638. 

Official  Interpretation  No.  44-95 

DATE:  lune  13,  1995 

SUBJECT:         Use  Group  Classification  -  Warehouse-Mercantile  Buildings  and  Structures. 

Discussion:  Recent  trends  in  retail  marketing  and  sales  have  seen  an  upsurge  in  the  numbers  of  the 
"warehouse-mercantile"  type  stores.  These  kinds  of  facilities  utilize  bulk  storage  on  the 
actual  sales  floor  area  in  racks.  Commodities  stored  and  sold  range  from  hardware  and 
household  items  through  floorcoverings,  cabinetry,  lumber  paint,  adhesives  and  other 
building  materials,  flammables,  aerosols,  pool  chemicals  and  fertilizers.  The  building 
typically  functions  as  both  a  warehouse  and  a  retail  establishment,  and  the  amounts  of  each 
type  of  product  stored  is  typically  orders  of  magnitude  greater  than  a  typical  mercantile 
establishment.  Furthermore,  there  is  usually  no  dedicated  storage  area  separate  from  gross 
sales  area.  Aisles  are  used  for  staging  product  prior  to  storage  in  the  high  rack  storage 
system,  in  addition  to  merchandizing.  Typically,  mercantile  stores  which  utilize  separated 
storage  and  sales  areas  are  designed  as  mixed  use  buildings,  and  conform  to  the  separated 
or  non  separated  requirements  of  the  code.  The  increasingly  popular  trend  of  the  warehouse- 
mercantile  occupancies  has  raised  a  question  as  to  which  use  group  is  most  appropriate  for 
such  occupancies.  Depending  upon  the  amounts  and  types  of  product  stored,  it  is  possible 
that  the  building  could  consist  of  a  variety  of  uses  such  as;  Mercantile  (M),  Low  Hazard 
Storage  (S-2),  Moderate  Hazard  Storage  (S-J)  and  High  Hazard  (H)  and/or  other  uses. 

Question:  Since  the  State  Building  Code  does  not  specifically  address  warehouse  retail  (retail 

warehouse)  type  occupancies  or  use  groups  (occupancies  consisting  of  open  type  floor  plan 
utilizing  rack  storage  type  structures  consisting  of  any  combination  of  horizontal,  vertical 
or  diagonal  members  that  support  stored  material  or  displayed  material  generally  exceeding 
12  feet  in  height),  is  it  the  intent  of  the  code  to  classify  such  uses  as  Mercantile,  Use  Group 
M,  based  on  the  stock  of  goods  for  sale  and  accessibility  to  the  public? 

Answer:  No.  Due  to  the  life  and  fire  hazard  as  noted  in  Section  312,  Doubtful  Use  Classification,  this 

type  of  occupancy  should  be  classified  Doubtful  Use  Group  until  sufficient  information  is 
provided  to  the  satisfaction  of  the  Building  Official  in  order  that  the  Building  Official  can 


704 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

determine  the  appropriate  use  (or  uses)  which  it  most  resembles  in  terms  of  life  and  fire 
hazard  in  accordance  with  section  3 12. 

Regardless  of  the  Use  Group  classifications  determined  by  the  Building  Official,  it  is  the 
responsibility  of  the  permit  applicant  in  accordance  with  section  1 1 3  {Application  for 
Permit),  to  provide  sufficient  information  to  show  the  nature  and  character  of  the  work.  As 
part  of  this  section,  the  Building  Official  shall  forward  the  available  information  to  the  Head 
of  the  Fire  Department  for  review  and  approval  of  the  applicable  sections  of  Article  6, 
Special  Use  and  Occupancy  Requirements  and  Article  10,  Fire  Protection  Systems. 

As  addressed  in  Article  10,  Section  1001.2,  the  information  presented  must  be  "...  of 
sufficient  detail  to  evaluate  the  hazard  and  the  effectiveness  of  the  system.  The  details  of  the 
hazards  shall  include  materials  involved,  the  location  and  arrangement,  and  the  exposure  to 
the  hazard." 

To  properly  address  the  particular  issues  and  acquire  the  required  information  for  such  a 
review  as  identified  in  Section  1001.2,  any  plans,  documents  and  reports  which  are 
submitted  to  the  Building  Official  in  accordance  with  sections  113  and  127  must  bear  the 
seal  of  a  qualified  professional  engineer  or  architect  when  required  by  the  building  code  or 
statute.  Since  Section  1001.2  addresses  special  fire  protection  features,  it  shall  be  noted  that 
the  Building  Official  and  the  Head  of  the  Fire  Department  should  refer  to  the  official 
interpretation  No.  38-94  Relating  to  the  Use  of  Registered  Professional  Engineers  Seal  as 
required  under  Section  1 13.5.2  and  127,  to  determine  whether  the  information  submitted  is 
sufficient  and  properly  documented  and  sealed  by  engineers  qualified  in  fire  protection 
concerns,  (see  Official  Interpretation  No.  38-94) 

Unless  the  necessary  information  and  documentation  is  properly  submitted  in  sufficient 
detail  per  Section  1001.2,  the  Head  of  the  Fire  Department  will  not  be  capable  of  proper 
evaluation  and  analysis  of  the  hazards  and  exposures  to  property  and  life  and  any  associated 
fire  and  life  safety  systems  provided  and  therefore  can  not  approve  the  plans.  In  order  for  the 
Head  of  the  Fire  Department  to  approve  plans  and  specifications  per  Section  1 13. 5(  Plans 
and  Specifications). 

Sufficient  details  and  supporting  documentation  should  be  included  to  address,  as  a 
minimum,  the  following; 

Material  storage/display  arrangement 

Segregation/separation  of  incompatible/hazardous  materials 

Emergency  evacuation  plans  (number  and  location  of  exits) 

Warehousing  operations  (open  and  closed) 

Employee  training  and  drills 

Management  participation  (housekeeping) 

Fire  initiation  and  development 

Spread  of  smoke  and  toxic  products 

Smoke  exhaust  venting 

Fire  Suppression  Systems 

Standpipe  systems  (21'2"  vs.  I"2  outlets) 

Requirements  for  rack  sprinklers  (NFiPA  23 1C) 

Adequacy  of  water  supplies 

Egress  relative  to  rack  aisles  (blockage/obstructions) 

Occupant  evacuation  time 

Fire  alarm  systems  (automatic  and  manual) 

Fire  Department  notification  (master  box/central  station  service) 

Occupant  notification 

Fire  Department  site  and  building  entry  access 

Seasonal   changes   in   merchandising   (introduction   of  additional   flammable   and 

hazardous  material) 

Access  to  floor/merchandising  plan  (periodic  review) 

Review  of  other  agency  requirements  (CMR  527,  Fire  Prevention  Regulations) 

Review  of  other  nationally  recognized  engineering  standards  relative  to  fire  hazards 

and  life  safety 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


705 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

If  sufficient  client  information  is  not  provided  to  the  Head  of  the  Fire  Department  as 
identified  above,  then  the  Building  Official  shall  classify  the  building  as  Doubtful  Use  Group 
per  Section  3 12,  Doubtful  Use  Classification,  and  the  structure  shall  be  included  in  the  use 
group  it  most  nearly  resembles,  (such  as  a  Use  Group  H,  High  Hazard  Uses,  Section  306  or 
as  described  in  Section  308,  Mercantile  Uses,  Use  Group  M,  or  as  the  Building  Official  so 
deems  until  adequate  information  is  provided  as  per  Section  1001.2,  to  determine  otherwise. 

If  sufficient  information  is  submitted  in  detail  satisfactory  to  the  Building  Official  and  the 
Head  of  the  Fire  Department  to  achieve  the  desired  level  of  life  safety  and  fire  hazard 
protection,  then  the  building  could  be  classified  Use  Group  M  or  other  as  determined  by  the 
Building  Official  in  cooperation  with  the  Head  of  the  Fire  Department. 

Official  Interpretation  No.  45-96 

DATE:  June  27,  1996 

SUBJECT:         Impacts  of  M.G.L.  c.  148,  §§  26G,  26H  and  261 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Thursday  27,  June 
1996,  the  Board  approved  the  following  interpretation  of  the  application  of  M.G.L.  c.  148,  §  26G,  26H 
and  261  as  they  impact  the  building  permit  process. 

Discussion:  M.G.L.  c.  148,  §§  26G,  26H  and  261  are  "local  option  statutes".  These  are  state  laws  which 
are  not  applicable  in  a  municipality  until  a  municipality  elects  to  adopt  them,  at  which  time 
they  become  law  in  that  municipality.  The  statutes  are  "Fire  Safety  Statutes",  and  require 
the  installation  of  automatic  sprinkler  systems  in  specific  buildings  identified  in  the  statutes. 
Once  adopted,  they  are  enforced  by  the  Head  of  the  Local  Fire  Department  (the  Fire  Chief). 

In  summary,  the  statutes  require  the  following 


Statute  fivf.G.L.)(a) 

Requirements 

Appeal  Provision 

c.  148,  §260™ 

Automatic  Sprinkler  System  in: 

1)  New  buildings  over  7,500  sf 

2)  Additions  to  existing  buildings 
(addition  only)  over  7,500  sf 

3)  Major  alterations  to  existing 
buildings  over  7,500  sf 

Automatic  Sprinkler 
Appeals  Board 

c.  148,  §  26H 

Automatic  Sprinkler  System  in  lodging 
and  boarding  houses 

Automatic  Sprinkler 
Appeals  Board 

c.  148,  §  261 

Sprinkler  system  installation  in; 

1)  New  multiple  family  dwellings 
containing  four  or  more  dwelling 
units. 

2)  Substantially  rehabilitated  buildings 
in  multi  family  dwellings  containing 
four  or  more  dwelling  units. 

State  Fire  Marshal 

Notes: 

(a)  Refer  to  statute  for  exact  wording 

(b)  Residential  uses  exempted 


In  some  municipalities,  the  adoption  of  these  statutes  has  created  an  apparent  regulatory 
conflict  and  has,  in  extreme  cases  resulted  in  omission  of  sprinkler  systems  at  the  outset  of 
construction  resulting  in  lawsuits  and  court  judgments  requiring  the  installation  of  the 
sprinkler  systems  after  occupancy.  Needless  to  say,  such  cases  have  proved  to  be  extremely 
costly. 


706 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  B 

Question:  How  do  these  particular  statutes  affect  the  responsibilities  of  the  Building  Official  in  the 

enforcement  of  the  State  Building  Code''  In  particular,  what  action  does  the  Building 
Official  take  at  the  building  permit  application  stage9 

Answer:  In  accordance  with  the  provisions  of  M.G.L.  c.  1 43,  §  3,  the  Building  Official  is  empowered 

to  enforce  the  provisions  of  the  State  Building  Code  and  the  Architectural  Access  Board 
Regulations  (521  CMR).  The  Fire  Chief  is  empowered  to  enforce  the  provisions  of  M.G.L. 
c.  148,  §§  26G.  26Hcmd26I. 

The  statutes  link  the  requirement  to  install  the  automatic  sprinkler  to  the  building  code  by 
requiring  the  installation  to  be  "....in  accordance  with  the  provisions  of  the  state  building 
code"  .  This  language  shall  be  properly  interpreted  as  "...An  accordance  with  standards 
referenced  for  the  installation  of  an  automatic  sprinkler  system",  e.g.  NFiPA  13,  13R  or 
13D,  etc.  Such  interpretation  would  also  extend  to  the  permitting  requirements  of  Article  1. 

The  Building  Official's  approach  in  municipalities  which  have  adopted  said  statutes  shall 
be. 

The  Building  Official  should  become  generally  aware  of  the  requirements  of  M.G.L.  c.  148, 
§§26G.26Hand26I. 

If  a  building  permit  application  is  made  which  may  trigger  the  enforcement  of  the  statutes, 
the  determination  is  (by  law)  made  by  the  Fire  Chief  It  is  clear  in  the  subject  statutes  that 
the  Fire  Chief  is  the  sole  authority  to  determine  whether  or  not  a  particular  construction 
activity  is  subject  to  said  statutes  and  the  municipality  and  its  agents,  including  the  Building 
Official  are  bound  by  this  determination.  The  permit  applicant  is  provided  avenues  of 
administrative  appeal  from  the  Fire  Chiefs  determination,  by  way  of  the  State  Fire  Marshal 
or  the  Automatic  Sprinkler  Appeals  Board.  Once  a  determination  has  been  made  by  the  Fire 
Chief  that  the  statute  is  applicable,  the  Building  Official  must  ensure,  at  the  building  permit 
application  stage,  that  provision  has  been  made  for  the  design  and  installation  of  the 
automatic  sprinkler  system.  If  plans  submitted  at  the  building  permit  application  stage  do 
not  include  the  sprinkler  system,  the  application  shall  be  denied  based  on  non  compliance 
with  Section  113  of  the  Massachusetts  State  Building  Code,  i.e.  incomplete  plans  and/or 
application  materials. 

If  an  appeal  is  taken,  the  Building  Official,  pending  the  outcome  of  the  appeal,  may  issue  a 
permit  in  part  and  shall,  in  writing,  concurrently  notify  the  Fire  Chief  and  the  permit 
applicant.   Said  notification  must  clearly  identify  the  limits  placed  on  the  construction. 

In  communities  which  have  adopted  the  provisions  of  M.G.L.  c.  148,  §  26H,  a  certificate  of 
inspection,  as  required  by  Table  108  for  a  lodging  or  boarding  house,  shall  not  be  issued  if 
an  automatic  sprinkler  system  has  not  been  installed  within  the  time  provided  for  by  said 
statute,  providing  that  the  Building  Official  has  been  notified  by  the  Fire  Chief  of  the  date 
of  the  adoption  of  said  statute.  If  an  appeal  is  pending  a  temporary  certificate  of  inspection 
may  be  issued  and  renewed,  each  for  periods  not  exceeding  30  days,  pending  the  outcome 
of  the  appeal. 

This  interpretation  is  made  to  foster  cooperation  between  building  and  fire  officials  in  this 
particular  area  of  law  which  has  caused  some  confusion  in  the  past. 

Official  Interpretation  No.  46-96 

DATE:  June  27,  1996 

SUBJECT:         Handrails  and  Guardrails  in  One  and  Two  Family  Dwellings 

Section  3401 . 1 1  of  the  Fifth  Edition  of  the  State  Building  Code 

At  a  regular  meeting  of  the  Board  of  Building  Regulations  and  Standards  held  on  Thursday  27,  June  1996, 
the  Board  approved  the  following  interpretation  of  the  application  of  Section  3401. 1 1  of  the  Fifth  Edition 
of  the  Stale  Building  Code. 

Section  3401  1 1  states  that  ".  .  .  Handrails  having  [a]  minimum  and  maximum  height  of 
thirty  (30)  inches  and  thirty-four  (34)  inches,  respectively,  measured  vertically  from  the 
nosing  of  the  treads  shall  be  provided  on  at  least  one  (1)  side  of  stairways  of  three  (3)  or 
more  risers.   Open  sides  of  all  stairs  shall  be  similarly  protected  by  guards.  .  . 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


707 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Question  1:        Is  it  the  intent  of  Section  3401.1 1  to  require  both  handrails  and  guardrails  set  at  different 
heights  on  the  open  sides  of  stairs  in  a  one  or  two  family  dwelling? 

Answer  1:  No.  It  is  the  opinion  of  the  Board  that  the  word  similarly  refers  to  the  handrail  description, 

which  means  that  the  open  side  of  the  stair  must  be  protected  with  a  guardrail  that  also  acts 
as  a  handrail.  It  is  not  necessary  to  provide  a  guardrail  set  at  36  inches  in  height  with  a 
handrail  set  between  30  and  34  inches. 

Question  2:        At  what  height  should  the  guardrail  be  set? 

Answer  2:  The  guardrail  may  be  set  between  30  and  34  inches  in  height  measured  vertically  from  the 

nosing  of  the  tread.  If  a  handrail  is  provided  on  the  opposite  side  of  the  stair,  it  shall  be  set 
at  the  same  height.. 


708 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


APPENDIX  C 


RECOMMENDED  FASTENING  SCHEDULE 


Building  element 

Nail  size  and  type 

Number  and  location 

Stud  to  sole  plate 

8d  common 
1 6d  common 

4  toe-nail  or  2  direct-nail 

Stud  to  cap  plate 

16d  common 

2  toe-nail  or  2  direct-nail 

Double  studs 

1  Od  common 

1 2"  o.c.  direct 

Corner  studs 

16d  common 

24"  o.c.  direct 

Sole  plate  to  joist  or  blocking 

1 6d  common 

16"  o.c. 

Double  cap  plate 

lOd  common 

1 6"  o.c.  direct 

Cap  plate  laps 

lOd  common 

2  direct-nail 

Ribbon  strip,  6"  or  less 

1  Od  common 

2  each  direct  bearing 

Ribbon  strip,  6"  or  more 

lOd  common 

3  each  direct  bearing 

Roof  rafter  to  plate 

8d  common 

3  toe-nail 

Roof  rafter  to  ridge 

1 6d  common 

2  toe-nail  or  direct  nail 

Jack  rafter  to  hip 

1  Od  common 
1 6d  common 

3  toe-nail  or  2  direct-nail 

Floor  joists  to  studs 
(No  ceiling  joists) 

1  Od  common 
1  Od  common 

5  direct  or  3  direct 

Floor  joists  to  studs 
(With  ceiling  joists) 

1  Od  common 

2  direct 

Floor  joists  to  sill  or  girder 

3d  common 

3  toe-nail 

Ledger  strip 

16d  common 

3  each  direct 

Ceiling  joists  to  plate 

1 6d  common 

3  toe-nail 

Ceiling  joists  (laps  over  partition) 

lOd  common 

3  direct-nail 

Ceiling  joists  (parallel  to  rafter) 

I  Od  common 

3  direct 

Collar  beam 

1  Od  common 

3  direct 

Bridging  to  joists 

8d  common 

2  each  direct  end 

Diagonal  brace  (to  stud  &  plate) 

8d  common 

2  each  direct  bearing 

Tail  beams  to  headers 
(When  nailing  permitted) 

20d  common 

1  each  end  4  sq.  ft.  floor  area 

Header  beams  to  trimmers 

20d  common 

1  each  end  8  sq.  ft.  floor  area 

1"  roof  decking 
(over  6"  in  width) 

8d  common 
8d  common 

2  ea.  direct  rafter 

3  each  direct  rafter 

1  "  subfloonng  (6"  or  less) 

8d  common 

2  each  direct  joist 

1 "  subfloonng  (8"  or  more) 

8d  common 

3  each  direct  joist 

2" subfloonng 

1 6d  common 

2  each  direct  joist 

1 "  wall  sheathing  (8"  or  less  in  width) 

8d  common 

2  each  direct  stud 

1 "  wall  sheathing    (over  8"  in  width) 

8d  common 

3  each  direct  stud 

Plywood  roof  &  wall  sheathing 
('/z"  or  less) 
(%"  or  greater) 
(5/16",  %",or  '/=") 

6d  common 
8d  common 

1 6  gauge  galvanized  wire  staples,  %" 

minimum  crown;  length  of  1 "  plus 

plywood  thickness 

Same  as  immediately  above 

6"  o.c.  direct  edges  &  12"  o.c  intermediate 
6"  o.c.  direct  edges  &  12"  o.c.  intermediate 

4"  o.c.  edges  &  8"  o.c.  intermediate 
2'A"  o.c.  edges  &  5"  o.c.  intermediate 

Plywood  subflooring: 

CO 

(%",%") 

(1",  1V4") 

('//) 

6d  common  or  6d  annular  or  spiral  thread 
8d  common  or  8d  annular  or  spiral  thread 
lOd  common  or  8d  ring  shank  or  8d 
annular  or  spiral  thread 
1 6d  galvanized  wire  staples 
%"  minimum  crown.  1  %"  length 

6"  o.c.  direct  edges  &  10"  o.c.  intermediate 
6"  o.c.  direct  edges  &  10"  o.c.  intermediate 
6"  o.c.  direct  edges  &  6"  o.c.  intermediate 

4"  o.c.  edges  &  7"  o.c.  intermediate 
2'/i"  o.c.  edge  4"  o.c.  intermediate 

Built-up  girders  and  beams 

20d  common 

32"  o.c.  direct 

Continuous  header  to  stud 

8d  common 

4  toe  nail 

Continuous  header,  two  pieces 

16d  common 

16"  o.c.  direct 

'/;"  liber  board  sheathing 

114"  galvanized  roofing  nail  or  16  gauge 
staple.  1  'A"  long  with  min.  crown  of  7/16" 

3"  o.c.  exterior  edge  6"  o.c  intermediate 

2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


709 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Building  element 

Nail  size  and  type 

Number  and  location 

25/32"  fiber  board  sheathing 

lJ/<"  galvanized  rooting  nail  or  8d  common 
nail  or  1 6  gauge  staple,  1 14"  long  with 
nun.  crown  of  7/16" 

3"  o.c.  exterior  edge  6"  ox.  intermediate 

Gypsum  sheathing 

12  gauge  l3/«"  large  head  corrosion- 
resistant 

4"  o.c.  on  edge  8"  o.c.  intermediate 

Particle  board  underlayment  ('/«"-%") 

6d  annular  threaded 

6"  o.c.  direct  edges  10"  o.c.  intermediate 

Panicle  board  roof  and  wall  sheathing 
14"  or  less 

6d  common 

6"  o.c.  direct  edges  12"  o.c.  intermediate 

%"  or  greater 

8d  common 

6"  o.c.  direct  edges  12"  o.c.  intermediate 

Particle  board  subflooring 
(%"  or  greater) 

8d  common 

6"  o.c.  direct  edges  12"  o.c.  intermediate 

Shingles,  wood" 

No.  1 4  B&S  Gage  corrosion  resistive 

2  each  bearing 

Weather  boarding 

8d  corrosion 

2  each  bearing 

Note  a:  Shingle  nails  shall  penetrate  not  less  than  3/i"  into  nailing  strips,  sheathing  or  supporting  construction  except 
as  otherwise  provided  in  780  CMR  1225.4.4. 

Table  C-l 

Maximum  Spacing  of  Gypsum  Wallboard  Fasteners 

(For  nonfireresistance  rated  construction  assemblies) 


Thickness  of 

gypsum 

wallboard 

(inch) 

Plane  of 
framing 
surface 

Long  dimension  of 
gypsum  wall-board 
sheets  in  relation  to 
direction  of  framing 
members 

Maximum 

spacing  of 

framing  members 

(ccnter-to-centcr 

in  inches) 

Maximum  spacing 

of  fasteners 

(center-to-  center 

in  inches) 

Nails           Screws 

Nails  to  wood 

!4 

Horizontal 

Horizontal 

Vertical 

Either  direction 

16 

24 
24 

7                     12 

No.  13  gage,  1%" 
long,  19/54"  head 
No.  098  gage,  W." 
long.  Annular  ringed 
5d  cooler  nail 

Perpendicular 

7                     12 

Either  direction 

8                     12 

% 

Horizontal 

Horizontal 

Vertical 

Either  direction 

16 

24 
24 

7                     12 

No.  13  gage,  1%" 
long,  19/64"  head 
No  .098  gage,  1%" 
long,  Annual  ringed  6d 
cooler  nail 

Perpendicular 

7                     12 

Either  direction 

8                    12 

Fastening  required  with  adhesive  a 

pplication 

14 

Horizontal 

Either  direction 

16 

16 

16 

As  required  for  !4" 

or 

Perpendicular 

24 

12 

16 

and  %"  gypsum 

% 

Vertical 

Either  direction 

24 

wallboard,  see 
above 

2  layers 

Horizontal 

Perpendicular 

24 

16 

16 

Base  ply  nailed  as 

each  %" 

required  for  14" 

(V«"  total) 

Vertical 

Either  direction 

24 

24 

24 

gypsum  wallboard 
and  face  ply  placed 
with  adhesive 

Notes  to  Table  C-l: 

Note  a.   Where  the  metal  framing  has  a  clinching  design  formed  to  receive  the  nails  by  two  edges  of  metal,  the  nails 

shall  be  not  less  than  5/a  inch  longer  than  the  wallboard  thickness,  and  shall  have  ringed  shanks.    Where  the  metal 

framing  has  a  nailing  groove  formed  to  receive  the  nails,  the  nails  shall  have  barbed  shanks  or  be  5d  cooler  nail  (No. 

13  14  gage,  1%  inches  long,  15/64  inch  head)  for  'A  inch  gypsum  wallboard;  6d  cooler  (No.  13  gage,  17/b  inches  long, 

15/64  head)  for  s/s-inch  gypsum  wallboard. 

Note  b.  Two  nails  at  2  inches  to  2'A  inches  apart  may  be  used  if  the  pairs  are  spaced  12  inches  center-to-center  except 

around  perimeters. 

Note  c.  Screws  shall  be  No.  6  with  tapered  head  and  long  enough  to  penetrate  into  wood  framing  not  less  than  5/a  inch 

and  metal  framing  not  less  than  'A  inch 

Note  d.  All  nails  shall  meet  ASTM  C5 14  or  Federal  Specification  FF-N- 1 05C. 

Note  e.  For  fireresistance  rated  construction,  see  the  pertinent  fire  test  information. 

Notef.   1  inch  =  25  4  mm. 


710 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  C 

Table  C-2 

Allowable  Shear  for  Wind  or  Seismic  Forces  in  Pounds  Per  Foot 

For  Vertical  Diaphragms  of  Lath  and  Plaster  or  Gypsum  Board  Frame  Wall  Assemblies 


Type  of  material 

Thickness  of 
Material 

Wall 
Construction 

Nail  spacing 
maximum 
(in  inches) 

Shear 
value 

Minimum  nail  size 

Gypsum  lath,  plain  or  perforated 

%"  Lath  and 
V-i  Plaster 

Unblocked 

5 

100 

No.  13  gage,  lVs"  long,  19/64"  head, 
plasterboard  blued  nail. 

'A"  x  2'x  8' 

Unblocked 

4 

75 

No.  1 1  gage,  1  '/<"  long,  7/64"  head, 

Gypsum  sheathing  board 

'/2"x4' 
!4"x4' 

Blocked 
Unblocked 

7 

diamond  point,  galvanized. 

7 

175 
100 

5d  Cooler  nails 

1/2" 

Unblocked 

4 

Blocked 

7 
4 
4 

100 

Gypsum  Wallboard 

125 

OY  Veneer  base 

5/8" 

Blocked 
Two  ply 

Base  ply  9 
Face  ply  7 

150 
175 
250 

6d  cooler  nails 

Base  ply-6d  cooler  nails 

Face  plv-8d  cooler  nails 

Note  a.    These  vertical  diaphragms  shall  not  be  used  to  resist  loads  imposed  by  masonry  or  concrete  construction. 

Values  are  for  short  time  loading  due  to  wind  or  earthquake  and  must  be  reduced  25%  for  normal  loading 

Note  b.  Applies  to  nailing  at  all  studs,  top  and  bottom  plates  and  blocking. 

Note  c.  Values  shown  are  for  gypsum  board  applied  to  one  side  only.  The  shear  values  may  be  doubled  when  identical 

materials  are  applied  to  both  sides  of  wall 

Note  d.   1  inch=25.4  mm. 


2/7/97  (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


711 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


712  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  D 

GUIDANCE  FOR  SELECTION  OF  FOUNDATION  MATERIAL  CLASSES 
IN  TABLE  1804.3 


D-101.0  Purpose:  The  purpose  of  Appendix  D  is  to 
provide  guidance  for  the  selection  of  the  material 
class  and  consistency  in  place  when  using  Table 
1804.3. 

D-102.0  Application:  Appendix  D  is  provided  only 
as  a  general  guide  to  engineering  judgment.  All 
available  data  should  be  evaluated  and  professional 
engineering  judgment  exercised  in  selection  of  the 
appropriate  material  classification  for  use  with  Table 
1804.3  The  references  on  soil  and  rock 
classification  and  typical  ranges  of  index  properties 
provided  in  this  appendix  should  not  be  considered 
to  be  code  requirements. 

D-103.0  Classification  of  Soil:  Guidelines  for 
generally    accepted    engineering    practice    in    the 


description  and  classification  of  soils  are  provided  in 
ASTM  D2488-84  Description  and  identification  of 
Soils  (Visual-Manual  Procedure)  and  ASTM  D2487- 
85  Classification  of  Soils  for  Engineering  Purposes 

D-104.0  Classification  of  Rock  Guidelines  for 
generally  accepted  engineering  practice  in  the 
description  and  classification  of  rocks  are  provided 
in  Chapter  1  of  Design  Manual  7  1  -  Soil  Mechanics, 
Naval  Facilities  Engineering  Command,  May  1982 
(NAVFACDM-7  1) 

D-105.0  Typical  Index  Properties:  Typical  ranges 
of  index  properties  for  the  Material  Classes  listed  in 
Table  1804.3  are  provided  in  Table  D-l 


TABLE  D-l 
TYPICAL  RANGE  OF  INDEX  PROPERTIES 


Material 
Class 

Description 

Consistency 
in  Place 

Rock  Quality 

Designation 

(RQD%) 

Unconfined 

Compressive 

Strength 

(PSF) 

Standard 
Penetration 
Resistance 

(Blows/Foot) 

la 
lb 

Massive  bedrock  -  granite,  diorite,  gabbro. 

nasalt,  gneiss, 

quartzite,  well-cemented  conglomerate 

Hard  rock,  minor 

lointing 

Hard  sound  rock, 

moderate  jointing 

>75 
50  to  75 

>8000 

2 

Folliated  bedrock 

Medium  hard  rock  minor 
lointing 

>50 

>8000 

3 

Sedimentary  bedrock-cementation  shale,  silt- 
stone,  sandstone,  limestone,  dolomite, 
conglomerate 

Soft  rock,  moderate 
jointing 

>50 

4 

Weakly  cemented  sedimentary  bedrock  - 
compaction  shale  or  other  similar  rock  in 
sound  condition 

Very  soft  rock 

<50 

5 

Weathered  bedrock  -  any  of  the  above  except 
shale 

Very  soft  rock, 
weathered  and/or  major 
lointing  and  fracturing 

<50 

6 

Slightly  cemented  sand  and/or  gravel,  glacial 
till  (basal  or  lodgement),  haropan 

Very  dense 

>50 

7 

Gravel,  widely  graded  sand  and  gravel,  and 
granular  abiauon  till 

Very  dense 
Dense 

Medium  dense 
Loose 
Very  loose 

>50 
41-50 
16-40 
8-15 
<8 

8 

Sands  and  non-plastic  silty  sands  with  little 
or  no  gravel  (except  for  Class  9  materials 

Dense 

Medium  dense 
Loose 
Verv  loose 

>30 

11-30 

6-10 

<6 

9 

Fine  sand,  silty  sand  and  non-plastic 
inorganic  silt 

Dense 

Medium  dense 
ioose 
Very  loose 

>30 
11-30 
6-10 
<6 

10 

Inorganic  sandy  or  silty  clay,  clayey  sand, 
clayey  slit,  clay  or  varved  clay  low  to  high 
plasticity 

Hard 
Stiff 
Medium 
Soft 

>20 
9-20 
4-8 

<4 

9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


713 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

ll      1 1        [Organic  soils  -  peat  organic  silt,  organic  clav    I  -  I  I  I  || 

Notes  to  table  D-l 

Note  1:   For  discussion  of  ROD  values  see  Deere,  D.U.,  Rock  Mechanics  in  Engineering  Practice  (Chapter  1).  Stagg 

and  Zinkiewicz,  Eds.,  1968.  John  Wiley  and  Sons.  Inc. 

Note  2:  For  determination  of  Unconfined  Compressive  Strength  see  ASTM  D2938. 

Note  3:For  determination  of  Standard  Penetration  Resistance  N-value  see  ASTM  D1586     The  presence  of  large 

particles  (coarse  gravel,  cobbies,  boulders)  may  cause  N-values  to  be  unrealistically  high    Such  values  should  not  be 

used   Also  standard  penetration  resistance  should  not  be  used  over  depths  less  than  five  feet. 


714  780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


APPENDIX  E 


PROCEDURE  FOR  ACCOUNTING  FOR  SERIES 
AND  PARALLEL  HEAT  FLOW  PATHS 


El:  For  envelope  assemblies  containing  metal 
framing:  The  Ui  shall  be  determined  by  using  one 
of  the  following  methods: 

1.  Results  from  laboratory  or  field  test 
measurements.  One  of  the  procedures  specified  in 
780  CMR  3  10S.2  shall  be  used. 

2.  The  thermal  resistance  of  those  roof  and  wall 
assemblies  listed  in  Tables  E-l  and  E-2  shall  be 

.corrected  using  the  following  procedures: 

The  total  resistance  of  the  heat  flow  path  (Rt) 
is  determined  from  the  Equation  E-l: 

Rt  =  Rj  -  Re 
Where: 
R    =   1/U 
Rt  =  the    total    resistance   of  the    envelope 

assembly. 
Ri  for:    i  =  1  to  n.  is  the  resistance  of  the  series 
elements. 

Re  is  the  equivalent  resistance  of  the  element 
containing  the  parallel  path,  and  the  value  of 
Re  is: 

Re  =  R  value  of  insulation  x  Fc 
(where  Fc  is  the  parallel  path  correction  factor) 

The  Parallel  Path  correction  Factors  (Fc)  may  be 
obtained  from  tests  conducted  using  procedures 
listing  in  780  CMR  3 108.2.  Parallel  Path  Correction 
Factors  for  some  envelope  assemblies  are  listed  in 
Tables  E-l  and  E-2. 

Table  E-l 

ROOFS:    PARALLEL  PATH 

CORRECTION  FACTORS' 


Table  E-2 

WALL  SECTIONS  WITH  METAL  STUDS: 

PARALLEL  PATH  CORRECTION  FACTORS 


Bndeed 

R-vIlue     °       "        10        15       -°       25       30       40 

45 

50 

tion          1.0  0.96  0.92    0.88    0.85    0.79    0.76    0.73 

0.71 

0.69 

Factor 

Size  of 

Gauge  of 

Spacing  of 

.Members 

Stud 

Framing 

:n4 

18-  16 

16"  ox. 

2  \  4 

18-  16 

24"  o.c. 

2x6 

18-  16 

16"o.c. 

2x6 

IS-  16 

24"  o.c. 

Cavity 
Insulation 
R-Value 

R-ll 
R-ll 
R-ll 
R-ll 


Corrcctio 
n  Factor 

0.50 
060 
0.40 
0.45 


Table  E-3 
CALCULATION  PROCEDURES  FOR 

EVALUATING  ALL  SERIES 
AND  PARALLEL  HEAT  FLOW  PATHS 


Metal 

BRIDGE  TYPE 

Metal 

Non-Metal 

Type  of  Material 

to  uhuch  bridge 

is  attached 

Thermal 
Bridges  in 
Sheet  Metal 
Construction 

Method 

Parallel  Path 

Non-Metal 

Zone  Method 

Parallel  Path 

Note  1.  Table  E-l  values  are  based  upon:  Metal  trusses 
with  4-ft.  spacing  that  penetrate  the  insulation,  and  0.66 
inch  diameter  crossmembers  e\  erv  one  ft. 


3.  For  elements  with  internal  metallic  structures 
bonded  on  one  or  both  sides  to  a  metal  skin  or 
covering,  the  "Thermal  Bridges  in  Sheet  Metal 
Construction,"  the  calculation  procedure  as 
specified  in  "Thermal  Bridges  in  Sheet  Metal 
Construction."  Studies  in  Building  Physics 
(Johannesson.  Gudni.  1981.  Division  of  Building 
Technology,  Lund  Institute  of  Technology,  Lund, 
Sweden.  Report  of  TVBH-3007)  shall  be  used. 

4.  For  elements  other  than  those  covered  above, 
.     the  zone  method  described  in  Chapter  23  of  the 

ASHRAE  Handbook,  1985  Fundamentals  Volume 
shall  be  used.  The  formulas  on  pages  23.13-14 
shall  be  used  for  calculation. 

E2:  For  envelope  assemblies  containing  Non- 
metal  Framing,  the  Ui  shall  be  determined  from 
results  from  one  of  the  laboratory  or  field  test 
measurements  specified  in  780  CMR  3  108.2  or  from 
the  ASHRAE  series  parallel  method.  Formulas  in 
Chapter  23,  page  23.2  of  the  ASHRAE  Handbook, 
1985  Fundamentals  Volume  shall  be  used  for  these 
calculations. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


715 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


716  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  F 


REFERENCE  DATA  FOR  REPAIR,  ALTERATION,  ADDITION  AND 
CHANGE  OF  USE  OF  EXISTING  BUILDINGS 


PART  ONE-  GUIDELINES 
APPLICATION 


FOR 


F-101  PURPOSE 
F-101.1  Intent  of  780  CMR  34  The  purpose  of 
Appendix  F  is  to  provide  guidance  to  users  of 
780  CMR  (the  Massachusetts  State  Building  Code) 
as  to  techniques  of  acceptable  practice  which  can  be 
used  to  assess  the  acceptability  of  various  methods 
of  meeting  the  intent  of  code  provisions  of  780  CMR 
34  on  a  case-by-case  basis.  The  purpose  of  the 
provisions  in  780  CMR  34  and  Appendix  F  is  to 
allow  the  repair,  alteration  addition,  and  change  of 
use  of  existing  buildings  without  requiring  the  entire 
building  to  be  brought  up  to  new  construction 
requirements,  while  still  providing  for  the  public 
health,  safety  and  general  welfare.  The  provisions  of 
780  CMR  34  and  Appendix  F  recognize  that  the 
provisions  of  780  CMR  for  new  construction  reflect 
the  latest  improvements  in  materials,  construction 
techniques,  standards  of  living  and  safety  and, 
therefor,  may  preclude  the  repair,  alteration, 
addition,  or  change  of  use  of  existing  buildings  that 
have  demonstrated  their  usefulness  and  safety. 

F-102.0  SCOPE 

F-102.1  Techniques:  Appendix  F  is  intended  to 
demonstrate  techniques  of  analysis  and  compliance 
with  780  CMR  34  in  the  repair,  alteration,  addition, 
and  change  of  use  of  existing  buildings. 

F-103.0 
F-103.1  General  conditions:  Conceptually,  it  is 
the  intent  of  780  CMR  34  and  Appendix  F  to  allow 
repair,  alteration,  addition,  or  change  of  use  of 
existing  buildings  without  meeting  all  new 
construction  requirements  under  the  following 
general  conditions: 

1 .  all  hazardous  conditions  must  be  corrected; 

2.  the  existing  building  becomes  the  minimum 
performance  standard;  and 

3.  the  degree  of  compliance  of  the  building  after 
changes  must  not  be  below  that  existing  before 
the  changes,  except  that  nothing  in  780  CMR  34 
will  require  compliance  with  requirements  more 
stringent  than  that  required  for  new  construction. 

F-1O4.0  IMPLEMENTATION 

F-104.1  Framework:  Implementation  of  the  above 
concept  requires  that  a  framework  be  established  for 
evaluating  the  condition  of  the  building;  determining 


the  potential  for  modification;  and  establishing  the 
acceptability  of  proposed  changes. 

F-104.2      Evaluation      of     existing      building: 

Evaluation  of  existing  conditions  in  a  structure  is 
required  to  determine  the  existence  of  any  hazardous 
conditions,  which  must  be  corrected;  and  to  provide 
a  basis  for  evaluating  the  impact  of  the  proposed 
changes  on  the  performance  of  the  building. 

The  following  list  of  evaluation  tools  described  in 
Appendix  F- 1 04. 1 . 1  through  F- 1 04.2. 7  can  be  used 
for  determining  the  condition  of  the  structure. 
However,  this  list  is  not  necessarily  complete  and 
the  use  of  other  methods  should  not  be  precluded. 

F-104.2.1  Available  documentation  of  existing 
building:  Prime  sources  of  design  information  for 
existing  buildings  are  the  architectural  and 
engineering  drawings  and  specifications  used  in 
the  construction  of  the  building.  Although  the 
passing  of  time  often  obscures  depositaries  of 
such  documents,  the  following  are  likely 
prospects  in  attempting  to  locate  such 
information: 

1.  If  the  building  is  currently  in  use,  an 
individual  or  office  responsible  for  its 
management  may  have  retained  drawings  and 
specifications  to  facilitate  maintenance.  A 
building  manager,  resident  engineer, 
superintendent,  custodian,  stationary  engineer 
or  plant  engineer  may  be  the  most  direct 
contact  at  the  building  site. 

2.  Other  potential  sources  (especially  if  the 
building  is  not  in  use)  include  the  original 
designer-architect  or  engineer. 

3.  The  building  department  which  issued  the 
permit  for  construction  may  have 
documentation. 

4.  Documentation  may  have  been  retained  by 
the  general  contractor  or  numerous 
subcontractors;  i.e.:  the  mason,  carpenter, 
plumber,  electrician,  HVAC  installer,  steel 
erector,  etc.,  as  well  as  manufacturers  of 
component  parts,  as  potential  sources  of 
documentation. 

5.  In  the  case  of  large  corporations  or 
government  agencies,  a  separate  contracting 
officer  may  have  developed  a  technical  file  on 
the  erection  of  a  building. 

6.  In  some  cases,  individual  consultants  are 
contracted  to  serve  as  "clerk-of-the-works"  and 
pursue  the  inspection  of  a  building  project 


2/7/97    (Effective  2/28/07) 


780  CMR  -  Sixth  Edition 


717 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


from  start  to  finish  with  the  keeping  of  a  file 
likely. 

7.  Insurance  companies  sometimes  maintain 
drawings  or  records  of  their  insured  buildings. 

8.  Historical  or  archaeological  societies  may 
have  considered  a  building  to  be  important 
enough  to  develop  a  file  of  documentation. 

F- 104.2.2  Field  surveys:  Having  drawn  upon 
available  documentation  to  help  evaluate  a 
building's  condition,  such  documentation  may  be 
augmented  by  on-site  data  acquired  through  field 
survey.  The  most  obvious  approach  is  to  make 
use  of  detailed  visual  examination  to  confirm 
and/or  alter  any  previously  available  information 
pertaining  to  the  building. 

F- 104.2.3  Testing:  Testing  is  a  tool  that  may  be 
used  in  evaluating  the  condition  of  a  building  or 
structure  or  parts  thereof  when  other  methods  of 
evaluation  will  not  suffice.  Testing  may  be 
initiated  voluntarily  on  the  part  of  the  permit 
applicant  or  may  be  required  by  the  building 
official  in  the  absence  of  approved  rules  as 
indicated  in  780  CMR  109.0,  1 16.0,  and  34.  The 
costs  of  all  such  tests  are  to  be  borne  by  the 
permit  applicant  and  should,  therefore,  be 
required  by  the  building  official  only  when  other 
methods  of  evaluation  prove  inadequate  or 
insufficient.  Such  testing  should  be  conducted  by 
an  approved  testing  agency  under  the  supervision 
of  a  registered  architect  or  engineer.  The  report  of 
the  tests  shall  be  submitted  to  the  building  official 
and  shall  include  the  details  of  test  procedures, 
references  to  any  accepted  test  standards  used,  the 
results  of  the  tests  and  any  conclusions  drawn 
from  the  test  results. 

F-104.2.4  Nondestructive  testing:  This  includes 
techniques  where  the  structural  integrity  of  the 
building  is  not  affected,  such  as  the  following: 

1.  analyzing  various  portions  of  the  building 
to  determine  dimensions,  types  and  condition 
of  materials,  etc.; 

2.  portable  apparatus  for  impact  testing; 

3.  load  application  short  of  failure  to 
determine  capacity  of  materials  and 
components; 

4.  magnetic  methods  for  detecting  flaws  in 
ferrous  metal; 

5.  proximity  magnetometers  (locating  rebars 
in  concrete,  concealed  ferrous  fasteners,  etc.), 

6.  electronic  means  for  measuring  the  sonic 
modulus  of  elasticity  of  concrete  and  masonry 
in  assessing  its  soundness; 

7.  ultrasonic  transmission  or  reflective 
methods  in  detecting  flaws  in  various 
materials;  and 

8.  x-ray  or  infrared-ray  photographic 
techniques  used  to  evaluate  portions  of 
elements  whose  integrity  is  questionable. 


F-104.2.6  Destructive  testing:  In  destructive 
testing  a  sample  of  the  building  could  be  removed 
and  tested  (e.g.,  concrete  core),  or  components  of 
the  building  could  be  reconstructed  and  tested  in 
the  laboratory. 

F-104.2.7  Laboratory  analysis:  In  some  cases, 
tests  can  be  performed  in  the  laboratory.  Such 
tests  might  include  the  following: 

1 .  chemical  or  metallurgical  test; 

2.  optical  or  electronic  microscopic  examin- 
ation which  can  help  identify  and  evaluate  the 
soundness  of  materials  where  decay  or  other 
molecular  degradation  is  involved; 

3.  conventional  laboratory  tests  for  deter- 
mining physical  properties  (strength,  ductility, 
absorption,  solubility,  permeability,  stiffness, 
etc.;  and/or 

4.  testing  of  a  scale  model  of  the  building 
(computer  model,  wind  tunnel  model,  etc.). 

F-104.3  Evaluation  of  change  in  performance 
level:  It  is  necessary  to  determine  if  the  level  of 
performance  of  the  building  after  alteration  is  below 
that  which  existed  before  the  change.  The  hazard 
level  could  be  increased  for  certain  attributes  (such 
as  fire  safety)  while  decreased  for  other  attributes 
(such  as  floor  loads)  for  a  given  alteration.  The 
evaluation  of  the  change  in  hazard  levels  of  each 
attribute  can  be  accomplished  using  various  tools 
singly  or  in  combination  as  described  below  in 
Appendix  F  - 1 04. 3 . 1  through  F-l 04.3.5. 

F-104.3.1  Data  on  archaic  systems:  Performance 
data  on  architectural  and  structural  systems 
encountered  are  tabulated  in  Appendix  F,  Part 
Four.  This  data  can  be  compared  to  the  proposed 
altered  systems  to  determine  if  the  performance  is 
adversely  affected. 

F-104.3.2  Compliance  alternatives'.  Alternate 
solutions  tabulated  in  Appendix  F,  Part  Two  were 
developed  from  appeal  data  and  from  accepted 
practice.  The  list  is  not  all-inclusive  and  should 
not  preclude  consideration  of  other  alternatives. 

F-104.3.3  Analysis  methods:  Analytical  methods 
based  on  good  engineering  practice  may  be  used 
to  determine  changes  in  performance  levels. 

F-104.3.4  Test  methods:  Test  procedures  as 
discussed  in  Appendix  F-104.2.3  through  F- 
104.2.6  can  be  used  to  evaluate  the  performance 
of  existing  construction. 

F-104.3. 5  Professional  judgement:  Professional 
judgement  based  on  previous  experience  with 
similar  buildings  should  be  used  to  the  fullest 
extent  possible. 


718 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


PART  TWO-  SUGGESTED       COMPLIANCE 
ALTERNATIVES 

F-201.0  PURPOSE  AND  SCOPE 

F-201.1  Purpose:  The  purpose  of  Appendix  F-201.0 
is  to  assist  the  building  official  and  those  regulated 
by  780  CMR  in  judging  the  acceptability  of 
compliance  alternatives  to  specific  provisions 
required  by  780  CMR. 

F-201.2  Application:  Appendix  F-201.0  contains 
generally  acceptable  compliance  alternatives  and 
examples.  The  examples  are  solely  for  the  purpose 
of  illustrating  principles  which  can  be  applied  to  the 
solution  of  code  compliance  problems  and  are  not 
necessarily  acceptable  under  all  circumstances.  It  is 
recognized  that  all  building  systems  interact  with 
each  other.  Therefore,  any  consideration  of 
compliance  alternatives  must  take  into  account  all 
existing  and  proposed  conditions  to  determine  their 
acceptability.  The  principles  applied  can  be  used  for 
the  solution  of  similar  compliance  problems  in  other 
buildings  and  occupancy  groups.  Commentaries  are 
provided  where  the  philosophy  in  establishing  the 
alternatives  is  not  obvious.  The  examples  were 
developed  from  appeal  data  and  accepted  practice. 
They  are  not  all-inclusive  and  should  not  preclude 
consideration  of  other  alternatives. 

Note:  It  is  anticipated  that  additional  compliance 
alternatives  will  be  added  to  Appendix  F-201.0 
through  the  mechanism  of  appeal  decisions  and 
from  results  of  research  being  conducted  by 
various  organizations  in  the  field  of  relative 
permanence  of  life  safety  systems. 

F-202.0  COMPLIANCE  ALTERNATIVES 
FOR  EGRESS  REQUIREMENTS 

F-202.1  Number  of  exits: 

F-202.1.1  General  compliance  alternatives: 

1.  Provide  connecting  fire  balconies. 

2.  Provide  alternate  egress  facilities  (windows, 
etc.). 

3.  Provide  a  fire  escape. 

4.  Provide  fire-rated  areas  of  refuge. 

F-202.1.2  Examples: 

Example  1  involves  a  five-story  Building  of  Use 
Group  B  without  a  fire  suppression  system  and 
with  only  one  means  of  egress. 

Solution  A.  Add  one  or  more  fire  escapes  as 
may  be  necessary  to  provide  all  tenants  with 
reasonable  access  to  two  means  of  egress  in 
separate  directions.  Access  to  a  street,  public 
way  or  area  of  refuge  shall  be  provided  at  the 
termination  of  the  fire  escape. 
Solution  B.  Add  connecting  fire  balconies 
across  fire  walls  if  the  above  solution  is 
impractical  due  to  construction  difficulties. 
Example  2  involves  a  building  of  Use  Group  R-2 
occupancy  with  an  apartment  in  the  basement 


There  is  only  one  means  of  egress  from  the 

basement. 

Solution  A.  Provide  egress  windows  in  each 
apartment  that  comply  with  780  CMR  10. 

F-202.2  Travel  Distance: 

F-202.2.1  General  Compliance  Alternatives: 

1.  Add  detection  system. 

2.  Add  a  partial  fire  suppression  system. 

3.  Add  smoke  doors. 

4.  Increase  fireresistance  rating  of  corridor 
walls  and  doors. 

F-202.2.2  Example:  This  example  involves  a  four 
story  building  of  Use  Group  R-2  without  a  fire 
suppression  system.  The  length  of  exitway  access 
travel  is  150  feet. 

Solution  A.     Add  a  partial  fire  suppression 
system    off  the    domestic   water   supply   (if 
adequate)  in  the  exit  access  corridor. 
Solution  B.  Subdivide  corridor  into  segments, 
if  less  than  100  feet,  with  smoke  doors. 
Solution  C.   If  not  required  by  other  sections 
of  780  CMR,  install  smoke  and  fire  detectors 
with  audible  alarms  in  the  corridor. 
Solution  D.    Increase  the  fireresistance  rating 
of  the  exit  access  corridor  from  one  hour  to 
two  hours  and  provide  "B"  label  self-closing  or 
automatic  closing  fire  doors  in  all  openings 
into  the  corridor. 

F-202.3  Enclosure  of  exitways: 

F-202.3.I  General  Compliance  alternatives: 

1.  Improve  enclosure  of  exitway. 

2.  Add  a  partial  fire  suppression  system. 

3.  Add  a  detection  system. 

F-202.3. 2  Examples:  This  example  involves  a 
four  story  row  building  of  Use  Group  R-2  with 
connecting  fire  balconies  and  an  interior  stair. 
The  stair  is  enclosed  with  lath  and  plaster,  wood 
stud  partitions  and  paneled  doors. 

Solution  A.  Cover  partitions  on  the  apartment 
side  with  5/s"  Type  X  gypsum  wallboard  or  its 
equivalent.  Replace  or  build  up  panel  doors 
until  minimum  solid  portion  is  1%"  and  install 
self-closers. 

Solution  B.  Provide  a  heat  and  smoke 
detection  system  in  the  stairwell  with  an  alarm 
audible  to  all  tenants.  Provide  self-closers  on 
all  stairwell  doors. 

Solution  C.  Provide  a  partial  fire  suppression 
system  in  the  stairwell  off  the  domestic  water 
supply  (if  adequate).  Provide  self-closers  on 
all  stairwell  doors. 

F-202.3.3  Commentary:  The  above  example, 
while  pertaining  to  a  four  story,  Use  Group  R-2 
building,  can  also  be  applied  to  other  buildings  of 
occupancies  and  floor  levels.  The  principle  that 
the  degree  of  code  compliance  may  not  be 
reduced  should  be  remembered     If  the  existing 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


719 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


enclosure  is  of  fireresi stive  construction,  it  must 
be  maintained  The  primary  principle  to 
remember,  in  the  required  enclosure  of  exitway,  is 
that  an  enclosure  must  be  provided,  whether 
fireresistive  or  not,  so  as  to  provide  a  smoke 
■  barrier.  The  purpose  of  providing  a  smoke  barrier 
is  to  prevent  the  passage  of  smoke  from  a  fire  on 
one  floor  to  the  exitways  and  exit  access  corridors 
of  other  floors  and  thus  render  them  unusable  for 
egress.  This  principle  is  illustrated  by  solutions 
A  B,  and  C  in  the  above  example. 

F-203.0  COMPLIANCE  ALTERNATIVES 
FOR  FIRE  HAZARDS 

F-203.1  Fire  separations  and  partitions; 

F-203.1.1  General  compliance  alternatives: 

1.  Improve  fire  separation. 

2.  Add  a  fire  suppression  system. 

3.  Add  a  detection  system. 

F-203.1.2  Examples:  Example  1  involves  a 
three  story  building  of  Type  3  A  construction, 
containing  a  Mercantile  (M)  Use  Group,  on  the 
first  floor  and  occupancy  Business  (B)  Use  on  the 
second  and  third  floors.  The  required  separation 
is  three  hours. 

Solution  A.   Add  a  fire  suppression  system  to 
the  first  and  second  floors. 
Solution  B.     Add  %  inch  Type  X  gypsum 
wallboard  or  its  equivalent  to  the  underside  of 
the  second  floor  and  install  a  system  of  smoke 
and  heat  detectors  with  audible  alarms  on  the 
first  and  second  floors. 
Example  2  involves  the  separation  between  two 
tenants  of  wood  lath  and  plaster  on  a  wood  studs 
partition.  The  required  separation  is  one  hour. 
Solution  A.     Add  %  inch  Type  X  gypsum 
wallboard  or  its  equivalent  to  either  side  of  the 
existing  partition. 
Example  3  involves  a  building  of  Use  Group  B 
with  unrated  exit  access  corridors. 

Solution  A.  Install  a  partial  fire  suppression 
system  in  the  exit  access  corridors. 
Solution  B.  Add  %  inch  Type  X  gypsum 
wallboard  or  its  equivalent  to  either  side  of  the 
corridor  partition  and  install  self-closers  on  all 
corridor  doors. 


Solution  C.  Install  a  smoke  and  heat  detection 
system  in  the  corridor  with  and  alarm  audible 
to  all  tenants  on  the  floor  and  install  self- 
closers  on  all  corridor  doors. 

F-203.2  Openings  and  exterior  wall  protection: 

F-203.2.1  General  compliance  alternatives: 

1 .  Add  fire  suppression  system. 

2.  Improve  fireresistance. 

3.  Remove  or  improve  openings. 

F-203.2.2  Examples:  Example  1  involves  a  two 
story  of  Type  5B  construction  building,  with  Use 
Group  M,  on  the  first  floor  the  basement  and 
upper  floors.  The  distance  between  the  building 
and  the  side  lot  line  is  five  feet  and-  ten— feet 
between  it  and  the  adjacent  building.  The 
adjacent  building  is  of  Type  5B  construction  and 
Use  Group  R-2.  The  former  occupant  was  a 
grocery  store;  the  new  occupant  is  a  hardware 
store. 

Solution  A.   Install  a  deluge  sprinkler  system 

along  the  interior  side  of  the  wall  affected. 

Solution  B.     Add  %  inch  Type  X  gypsum 

wallboard  to  interior  side  of  the  wall  affected. 
Example  2  is  the  same  as  example  1  but  with 
double-hung  wood  windows  in  affected  wall. 

Solution  A.      Remove  windows  and  close 

opening      with      one      hour      fireresistive 

construction. 

Solution  B.  Remove  windows  and  install  fire 

windows. 

Solution  C.   Install  a  deluge  sprinkler  system 

as  in  solution  A  to  example  1. 

PART  THREE-  DETAILED  CLASSIFICATION 
OF  OCCUPANCY  BY  HAZARD 
INDEX  NUMBER  AND  USE 
GROUP 

Appendix  F,  Part  Three  provides  a  more  detailed 
guide  for  users  of  780  CMR  to  determine  hazard 
index  numbers  and  use  groups  for  various  types  of 
occupancies.  It  supplements  780  CMR  3  and  Table 
34  contained  in  780  CMR  3404. 


720 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


TABLE  F-l 
HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 


Use  of  Structure 


Hazard  Index  No. 


Advertising  Displays  Manufacture  including  billboards 

Airport  or  other  aircraft  landing  or  service  facility  (see  also:  Helicopter 

rooftop  landing  facility 
Amusement  park,  indoor 
Animal 

Crematorium 

Hospital,  kennel,  pound 
Apartment  (see  Residences) 
Appliances 

Manufacture 

Sales 
Arenas 
Asphalt 

Processing  and  products  manufacture 
Athletic  equipment 

Manufacture 

Sales 
Auditoriums 


Automobile  and  other  motor  vehicles 

Gasoline  service  station 

Rental  agency  within  a  building 

Repair 
Repair  incidental  to  auto  sales  with  limitation 

Sales  within  a  building 

Wrecking 

Washing 
Awning  manufacturer 
Baked  goods  shop 
Bakeries 
Banks 

Banquet  halls 
Barber  shops 
Beauty  shops 
Beverages 

Bottling 

Manufacture 
Alcoholic 

Less  than  0.5%  alcohol  r§>  60° 
Bicycle 

Manufacture 

Rental  or  repair  conducted  within  a  building 

Sales 
Billiard  Parlor 
Blacksmith  shops 
Blueprinting,  etc.  establishments 
Boarding  house 
Boats  or  ships 

Building  or  repair  of  boats 
Bone  distillation 
Bowling  alleys 
Broom  or  brush  manufacture 
Building  materials 

Wholesale  business  in  roofed  structures 
Bus  terminals  or  stations 
Business  schools  or  colleges 


F 
A-3 


F-2 
B 


F-l 
M 
A-3 


3 

F-l 

3 

M 

6 

A-l  with  stage 

3 

A- 1  without  stage 

4 

A-3 

3 

M 

2 

B 

3 

S-l 

3 

S-l 

3 

M 

3 

F 

3 

S-l 

3 

F-l 

3 

M 

3 

F-l 

2 

B 

5 

A-3 

2 

B 

2 

B 

2 

Camera  and  other  photo  equipment 
Manufacture  except  film  sales 
Sales 


8 
3 

H 
F-l 

3 
3 
3 

F-l 
S-l 
M 

4 

A-3 

3 

F-l 

3 

F-l 

2 

R-l  orR-2 

3 

F-l 

3 

F-l 

4 

A-3 

3 

F-l 

3 

M  or  S-l 

4 

A-3 

4,2  or  other 

A-4,  B  or  dependent 
upon  use 

3 
3 

M 
M 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


721 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  F-l  (continued) 
HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 


Use  of  Structur 


Hazard  Index  No. 


Canvas  or  canvas  products 

Manufacture  or  repair 
Carpet  and  rug 

Cleaning  establishments 

Manufacture  or  repair 
Catering  for  outside  consumption 
Cemeteries 

Crematory  in  cemetery 

Mausoleum,  crypt,  columbarium 

Mortuary  chapel  in  cemetery 
Ceramics  products  manufacture,  including  pottery,  small  glazed  tile  and 

similar  items 
Charcoal,  fuel,  briquettes,  or  lampblack  manufacture 
Chemicals 

Packaging 

Manufacture 

Churches  or  other  places  of  worship 

Circuses,  temporary 

Cleaning  (see  Drycleaning  &  dying;  Laundries;  Automobiles,  washing) 

Clothing 

Manufacture 

Rental  establishment 

Retail  sales 

Tailoring,  custom  manufacture  or  repair  (see  also  Feathers;  Felt;  Fur; 

Leather) 
Clubs 

Private 

Nightclubs  (see  Eating  &  drinking  establishments) 
Coal,  coke  or  tar  products 

Manufacture 
Colleges  and  Universities 

Classroom  buildings 

Dormitories 

Fraternities  or  sororities 
Community  centers 

Convalescent  homes  (see  Nursing  homes) 
Convents 

Cosmetics  or  toiletries  manufacture 
Cotton  ginning 

Cotton  wadding  or  linters  manufacture 
Courthouses 
Crematoriums 

Ani  nal 

Human 
Dance  halls 
Day  care  agencies 
Day  nurseries 

Dental  offices  (see  Medical  &  dental) 
Department  stores 
Dormitories 

Dressmaking  shops,  custom 

Drinking  places  (see  Eating  &  drinking  establishments) 
Drive-in  restaurants 
Drug  stores 
Dry  cleaning  and  dying  establishments 

Dwellings  (see  Residences) 


8  or  3 

H.F-1 

3 

F-l 

3 

F-l 

3 

F-2 

1 

S-2 

4 

A-4 

3 

F-2 

8 

H 

H  or  F- 1  depending  on 

8  or  3 

nature  of  material 

H  or  F- 1  depending  on 

8  or  3 

nature  of  material 

4 

A-4 

4 

A-3 

H  or  F- 1  depending  on 

8  or  3 

nature  of  material 

3 

M 

3 

M 

3 

M 

4 

A-3  without  residence 

8 

H 

4 

A-3 

2 

R-2 

2 

R-2 

4  or  2 

A-3,  or B 

2 

R-2 

8 

H 

8 

H 

8 

H 

2  or  4 

B  or  A-3 

3 

F-2 

3 

F-2 

7 

A-2 

4 

1-2  or E 

4 

1-2 

3 

M 

2 

R-l  or R-2 

8 

H 

5 

A-3 

3 

M 

H  or  F- 1  depending  on 

8  or  3 

solvents  used 

722 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


TABLE  F-l  (continued) 
HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 


Use  of  Structure 


Hazard  Indi 

:x  No. 

Use  Grc 

5 

A-3 

4 

A-3 

7 

A-2 

3 

F-l 

3 

F-l 

3 

F-l 

3 

M 

Eating  or  drinking  establishments 

Lunchrooms,  restaurants,  cafeterias,  etc.,  primarily  enclosed 

Dnve-m 

With  entertainment  or  dancing 
Electric 

Power  or  steam  generating  plants 

Substation 
Electrical  appliances,  bulbs,  wiring,  supplies,  etc. 

Manufacture 

Sales 
Electronic  components  &  supplies 

Manufacture  or  repair 
Feathers 

Curing,  dyeing,  washing  or  bulk  processing 

Manufacturing  exclusive  of  above 
F'elt 

Curing,  dyeing,  washing  or  bulk  processing 

Products  manufacture,  exclusive  of  above 
Fertilizer  manufacture 
Film,  photographic,  manufacture 

Storage  and  studios 
Fire  stations 
Fish  processing 
Florida  shops 
Food 

Product  processing  except  meat  &  fish 

Retail  sales 
Fraternities  or  sororities 
Funeral  establishments 
Fur 

Curing,  dyeing,  finishing,  tanning 

Products  manufacture  exclusive  of  above 
Garage  (see  Parking  garage) 
Garbage  incineration  or  reduction 
Gas 

Manufacture 

Public  utility  stations  for  metering  or  regulating 

Storage 

2500  cu.  ft.  or  less 
more  than  2500  cu.  ft. 
Gasoline  service  station  (see  Automobiles) 
Gelatin  manufacture 
Generating  plants,  electric  or  steam 
Gift  shops 

Glass  products  from  previously  manufactured 
Glue  manufacture 
Golf 

Indoor  courses  or  driving  ranges 
Gymnasiums 
Grain  storage 
Hair 

Curing,  dyeing,  washing,  bulk  processing 

Product  manufacture  exclusive  of  above 
Hardware 

Manufacture 

Retail  sales 
Hat  bodies  manufacture 
Helicopter  landing  facility,  rooftop 
Home  occupations 
Homes  for  the  aged 
Hosiery  manufacture 


8 

H 

8 

H 

3 

F-l 

3 

F-l 

8 

H 

3  or  8 

F-l  orH 

3  or  8 

F-l  orH 

2 

B 

3 

F-l 

3 

M 

3 

F-l 

3 

M 

2 

R- 1  or  R-: 

4 

A-3 

8 

H 

3 

F-l 

M 
F-2 

F-l 

A-3 
A-3 
H 

F-l 
F-l 

F-l 
M 

F-l 

S-l 
B 
1-2 

F-l 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


723 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  F-l  (continued) 
HAZARD  INDEX  AM)  USE  GROUP  CLASSIFICATION 


Use  of  Structure 


Hazard  Index  No. 


Use  Group 


Hospitals 

Including  convalescent,  nursing,  or  rest  homes  and  sanitariums,  provided 
custodial  care  is  not  provided  for  drug  addicts,  alcoholics,  mentally  ill 
or  mentally  deficient 

For  care  of  drug  addicts,  mentally  ill,  or  mentally  deficient 

Research  or  teaching  laboratories 
(see  also  Animal  hospitals) 
Hotels 

Ice  manufacturing  (dry  or  natural) 
Ice  skating  rinks 

Incineration  or  reduction  of  garbage,  offal,  or  dead  animals 
Industry  uses  (see  specific  items) 

Without  resulting  noise,  vibration,  special  danger,  hazard,  dust,  smoke, 
fumes,  etc. 

Other  than  above 
Ink  or  inked  ribbon  manufacture 
Jewelry 

Kennels  (see  Animal) 
Laboratories 

Research  laboratory  not  accessory  to  school  or  hospital 

Scientific  research  or  teaching  laboratory,  non-profit,  accessory  to  school, 
or  hospital,  subject  to  limitations 
Laundries 

Hand  laundry 

Self  service;  pick-up  and  delivery  station  of  laundry  or  dry  cleaner 
Steam  laundries  without  limitations 
Leather 

Curing,  dyeing,  finishing  or  tanning 

Product  manufacture  exclusive  of  above 
Libraries 

Linoleum  or  oilcloth  manufacture 
Liquor  sales,  package 
Luggage  manufacture 
Lumber  (see  Wood) 
Manufacturing 
Matches  manufacture 
Mattress  manufacture  and  renovation 
Meat  Markets 

Slaughtering  or  packaging 
Medical  &  dental  offices 

(see  also  Laboratories;  Orthopedic  &  medical  appliances;  Hospitals) 

Meeting  hall 
Metals,  manufacture 

Reduction,  refining  or  smelting 
Monasteries 
Motels 

Motor  freight  stations  (see  trucking  terminals) 
Museums 

Musical  instruments  manufacture 
Newspaper  publishing 
Newsstands 

Novelty  products  manufacture 
Nursing  Homes 
Offices 

Oilcloth  manufacture 

Optical  equipment  or  similar  precision  instruments  manufacture 
Orphanages 

Orthopedic  or  medical  appliance  manufacture 
Paint,  turpentine  or  vamish 

Manufacture 

Spraying  booths 


4 

1-2 

5 

1-3 

2 

B 

2 

R-l 

3 

F-2 

4 

A-3 

3 

F-l 

3 

F-2 

3  or  8 

F-l  orH 

3 

F-l 

3 

F-l 

2 

B 

2 

B 

2 

B 

3 

F-l 

3 

F-l 

3 

F-l 

4 

A-3 

3 

F-l 

3 

M 

3 

F-l 

3  or  8 

F-lorH 

8 

H 

3 

F-l 

3 

M 

3 

F-l 

2 

B 

4 

A-3 

3 

F-2 

8 

H 

2 

R2 

2 

R-l 

3 

F-l 

3 

F-l 

3 

M 

3 

F-l 

4 

1-2 

2 

B 

3 

F-l 

3 

F-l 

3 

1-2 

3 

F-l 

8 

H 

8 

II 

724 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


TABLE  F-l  (continued) 

HAZARD  INDEX  AND  USE  GROUP  CIASSEFICATION 

Use  of  Structure 

Hazard  Index  No. 

Use  Group 

Paper  products  manufacture 

3 

F-l 

Parish  houses 

4 

A-3 

Parking  garages 

Group  1 

3 

S-l 

Group  2 

1 

S-2 

Petroleum  or  petroleum  products 

Refining 

8 

H 

Storage 

3 

S-l 

Pharmaceutical  products  manufacture 

3 

F-l 

Photography  studio 

2 

B 

Plastics 

Product  manufacture 

8 

H 

Raw,  manufacture 

8 

H 

Police  stations 

2 

B 

Pool  rooms 

4 

A-3 

Post  offices 

2 

B 

Printing 

Plant 

3 

F-l 

Printing  or  newspaper  publishing 

3 

F-l 

Prisons  &  other  correctional  or  detention  institutions 

5 

1-3 

Pumping  station  or  substation,  water  or  sewage 

3 

F-2 

Radio 

3 

Sales 

5 

M 

Studios  with  audience 

2 

A-l-B 

Studios  without  audience 

B 

Railroad 

Freight  terminal 

4 

A-3 

Passenger  station 

3 

S-l 

Recreation 

Center,  indoor 

4 

A-3 

Community  center  building 

4 

A-3 

Rectories 

2 

R-2 

Residences 

One-family 

2 

R-3,orR-4 

Two-family 

2 

R-3,orR-4 

Apartment 

2 

R-2 

Temporary  duelling  structure 

2 

R-3 

Boarding  or  lodging  house 

2 

R-l  or  R-2 

Dormitory 

2 

R-l  or R-2 

Fraternity  or  sorority 

2 

R-l  or R-2 

Hotel,  motel  apartment  with  accessory  services 

2 

R-l 

Convents,  monasteries,  rectories 

2 

R-2 

Research  laboratories  (  see  Laboratories) 

Restaurant,  lunch  room,  cafeteria  or  other  establishments  primarily  for  eating 

5 

A-3 

Retail  business 

3 

M 

Stores  with  combustible  or  flammable  goods  constructing  a  high  hazard 

8 

H 

Rubber 

Manufacture  (natural  or  synthetic),  including  tires,  tubes,  or  similar 

products 

8 

H 

Products  (exclusive  or  processing)  including  washers,  gloves,  footwear 

bathing  caps  and  the  like 

3 

F-l 

Sanatariums 

Not  providing  custodial  care  for  drug  addicts,  alcoholics,  mentally  ill,  or 

mentally  deficient 

4 

1-2 

Providing  care  for  the  above 

5 

1-3 

Schools 

4 

E 

Seminaries 

4  or  2 

A-4&R-1 

Settlement  houses  (depending  on  nature  of  activities) 

4  or  2 

A-3  or  B 

Sewage 

Disposal  plant 

3 

F-l 

Pumping  station 

3 

F-l  or F-2 

Shoddy  manufacture 

8 

H 

2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


725 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  F-l  (continued) 
HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 

Use  of  Structure 

Hazard  Index  No. 

Use  Group 

Hospitals 

Including  convalescent,  nursing,  or  rest  homes  and  sanitariums,  provided 

custodial  care  is  not  provided  for  drug  addicts,  alcoholics,  mentally  ill 

or  mentally  deficient 
For  care  of  drug  addicts,  mentally  ill,  or  mentally  deficient 
Research  or  teaching  laboratories 

(see  also  Animal  hospitals) 

4 
5 
2 

1-2 
1-3 
B 

Hotels 

2 

R-l 

Ice  manufacturing  (dry  or  natural) 

Ice  skating  rinks 

Incineration  or  reduction  of  garbage,  offal,  or  dead  animals 

3 
4 
3 

F-2 
A-3 
F-l 

Industry  uses  (see  specific  items) 

Without  resulting  noise,  vibration,  special  danger,  hazard,  dust,  smoke, 

fumes,  etc. 
Other  than  above 

3 
3  or  8 

F-2 
F-IorH 

Ink  or  inked  ribbon  manufacture 

3 

F-l 

Jewelry 

3 

F-l 

Kennels  (see  Animal) 

Laboratories 

Research  laboratory  not  accessory  to  school  or  hospital 
Scientific  research  or  teaching  laboratory,  non-profit,  accessory  to  school, 
or  hospital,  subject  to  limitations 

2 
2 

B 
B 

Laundries 

Hand  laundry 

Self  service,  pick-up  and  delivery  station  of  laundry  or  dry  cleaner 

2 

B 

Steam  laundries  without  limitations 

3 

F-l 

Leather 

Curing,  dyeing,  finishing  or  tanning 
Product  manufacture  exclusive  of  above 

3 
3 

F-l 
F-l 

Libraries 

4 

A-3 

Linoleum  or  oilcloth  manufacture 

3 

F-l 

Liquor  sales,  package 
Luggage  manufacture 

3 

3 

M 
F-l 

Lumber  (see  Wood) 

Manufacturing 

3  or  8 

F-l  or H 

Matches  manufacture 

8 

H 

Mattress  manufacture  and  renovation 

3 

F-l 

Meat  Markets 

Slaughtering  or  packaging 
Medical  &  dental  offices 

(see  also  Laboratories',  Orthopedic  &  medical  appliances;  Hospitals) 

3 
3 

2 

M 
F-l 

B 

Meeting  hall 

4 

A-3 

Metals,  manufacture 

Reduction,  refining  or  smelting 
Monasteries 

3 

8 
2 

F-2 
H 
R2 

Motels 

2 

R-l 

Motor  freight  stations  (see  trucking  terminals) 

Museums 

Musical  instruments  manufacture 

3 

F-l 

Newspaper  publishing 
Newsstands 

3 
3 

F-l 
M 

Novelty  products  manufacture 

3 

F-l 

Nursing  Homes 

4 

1-2 

Offices 

2 

B 

Oilcloth  manufacture 

3 

F-l 

Optical  equipment  or  similar  precision  instruments  manufacture 

3 

F-l 

Orphanages 

3 

1-2 

Orthopedic  or  medical  appliance  manufacture 

3 

F-l 

Paint,  turpentine  or  varnish 
Manufacture 
Spraying  booths 

8 
8 

H 
H 

724 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


TABLE  F-l  (continued) 

HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 

Use  of  Structure 

Hazard  Index  No. 

Use  Group 

Paper  products  manufacture 

3 

F-l 

Parish  houses 

4 

A-3 

Parking  garages 

Group  1 

3 

S-l 

Group  2 

1 

S-2 

Petroleum  or  petroleum  products 

Refining 

8 

H 

Storage 

3 

S-l 

Pharmaceutical  products  manufacture 

3 

F-I 

Photography  studio 

2 

B 

Plastics 

Product  manufacture 

8 

H 

Raw,  manufacture 

8 

H 

Police  stations 

2 

_B_ 

Pool  rooms 

4 

A-3 

Post  offices 

2 

B 

Printing 

Plant 

3 

F-l 

Printing  or  newspaper  publishing 

3 

F-l 

Prisons  &  other  correctional  or  detention  institutions 

5 

1-3 

Pumping  station  or  substation,  water  or  sewage 

3 

F-2 

Radio 

3 

Sales 

5 

M 

Studios  with  audience 

2 

A-l-B 

Studios  without  audience 

B 

Railroad 

Freight  terminal 

4 

A-3 

Passenger  station 

3 

S-l 

Recreation 

Center,  indoor 

4 

A-3 

Community  center  building 

4 

A-3 

Rectories 

2 

R-2 

Residences 

One-family 

2 

R-3,orR-4 

Two-family 

2 

R-3,orR-4 

Apartment 

2 

R-2 

Temporary  dwelling  structure 

2 

R-3 

Boarding  or  lodging  house 

2 

R-l  or R-2 

Dormitory 

2 

R-l  or R-2 

Fraternity  or  sorority 

2 

R-l  or R-2 

Hotel,  motel  apartment  with  accessory  services 

2 

R-l 

Convents,  monasteries,  rectories 

2 

R-2 

Research  laboratories  (  see  Laboratories) 

Restaurant,  lunch  room,  cafeteria  or  other  establishments  primarily  for  eating 

5 

A-3 

Retail  business 

3 

M 

Stores  with  combustible  or  flammable  goods  constructing 

;  a  high  hazard 

8 

H 

Rubber 

Manufacture  (natural  or  synthetic),  including  tires,  tubes, 

or  similar 

products 

8 

H 

Products  (exclusive  or  processing)  including  washers,  gloves,  footwear 

bathing  caps  and  the  like 

3 

F-l 

Sanatariums 

Not  providing  custodial  care  for  drug  addicts,  alcoholics, 

mentally  ill,  or 

mentally  deficient 

4 

1-2 

Providing  care  for  the  above 

5 

1-3 

Schools 

4 

E 

Seminaries 

4  or  2 

A-4&R-1 

Settlement  houses  (depending  on  nature  of  activities) 

4  or  2 

A-3  or  B 

Sewage 

Disposal  plant 

3 

F-l 

Pumping  station 

3 

F-l  or  F-2 

Shoddy  manufacture 

8 

H 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


725 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


TABLE  F-l  (continued) 
HAZARD  INDEX  AND  USE  GROUP  CLASSIFICATION 


Use  of  Structure 


Hazard  Index  No. 

Use  Group 

3 
2 

F-l 
B 

3 

F-l 

3 

A-3 

4 

A-3 

8 
3 

H 
F-l 

8 

H 

3 
3 

F-l 
M 

3 

S-l 

4 

A-5 

3  or  1 

S-lorS-2 

depending  on  nature  of 

materials 

Shoes 

Manufacture 

Repair  shop 
Silverware  manufacture,  plate  or  sterling 
Size  manufacture 
Skating  rinks 
Soap  and  detergents 

Manufacturing,  including  fat  rendering 

Packaging 
Solvent  extracting 
Sporting  or  athletic  goods 

Manufacture 

Stores 
Stables 
Stadiums 
Wholesale  business,  including  accessory  storage  other  than  flammable  liquids, 

gases  and  explosives,  in  roofed  structures 

Stores  (see  Retail  stores;  or  specific  items) 
Tailor  shops,  custom 
Tanning  (see  leather,  Fur) 
Taxidermist  shops 
Telephone  exchanges 

Automatic 

Non-automatic 
Television 

Sales 

Studios 


Textiles 

Manufacture,  including  knit  &  yard  goods,  thread  or  cordage,  spinning, 
weaving,  dyeing  &  printing,  shoddy  manufacture 
Theaters 


Tires,  manufacture 

Tobacco  products  manufacture  including  curing 

Tools  &  hardware 

Manufacture 

Sales 
Toys 

Manufacture 
Trailer  park  (see  Mobile  homes) 
Truck 

Repairs 

Sales 
Trucking  terminals 
Turpentine  manufacture 
Warehouses 

Waterpumping  stations 
Wax  products  manufacture 


B 
B 

M 

M 

A- 1  with  scenery 

A- 1  np  scenery 

B  no  audience 


F-l 

A- 1  with  scenery 

A-l  no  scenery,  motion 

picture 

H 

F-l 

F-l 
M 


S-l 
M 
S-l 
H 
H,  S-l,  or  S-2  depending 
on  nature  of  materials 
F-2 
H 


726 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


PART  FOUR-  ARCHAIC  CONSTRUCTION 
SYSTEMS 

F-401.0  PURPOSE  AND  SCOPE 

F-401.1  Purpose:  The  purpose  of  of  Appendix  F, 
Part  Four  is  to  assist  the  building  official  and  those 
regulated  by780  CMR  in  evaluating  the  properties 
of  archaic  construction  systems. 

F-401.2  Scope:  Appendix  F,  Part  Four  contains  data 
on  construction  systems  no  longer  in  general  use  but 
which  may  be  encountered  in  older  existing 
buildings.  It  is  meant  to  be  used  for  assessing 
existing  conditions  when  evaluating  how  proposed 
changes  will  impact  upon  the  performance  of  the 
building. 

F-401.3  Application:  In  any  given  problem,  all 
available  data  should  be  collected  and  professional 
judgement  exercised  in  arriving  at  decisions. 
Evaluative  judgment  should  be  used  when  test  data 
does  not  exist  or  when  applying  the  data  contained 
in  this  standard. 

F-402.0  ARCHAIC  FIRERESISTIVE 
SYSTEMS 

F-402.1  General:  Appendix  F,  Part  Four  contains  a 
list  of  fireresistive  materials  and  construction  which 
are  not  necessarily  currently  in  common  use.  Some 
of  the  hourly  ratings  contained  in  the  listing  predate 
ASTM  E-119  that  is  in  current  use.  The  hourly 
ratings  may  be  higher  or  lower  if  tested  according  to 
ASTM  E  119.  In  addition  to  the  data  contained 
herein,  see  Report  BMS92,  Building  Materials  and 
Structures,  dated  October  7,  1942,  National  Bureau 
of  Standards.  The  data  listed  below  is  extracted 
from  the  Boston  Building  Code,  circa  1943. 

F-402.2  Fireresistive  materials  and  construction: 

F-402.2.1  Minimum  qualities:  Materials,  to  be 
given  the  fireresistive  ratings  specified  in  this 
part,  shall  have  the  following  minimum  qualities 
set  forth  in  Appendix  F  F-402.2.2  through  F- 
402.2.19. 

F-402.2.2  Class  1  concrete:  Concrete  of  Class  1 
shall  be  so  proportioned  as  to  have  a  strength  of  at 
least  1500  pounds  per  square  inch  (psi)  and  the 
coarse  aggregate  shall  consist  of  limestone,  trap 
rock,  blast  furnace  slag,  cinders  containing  not 
more  that  20%  of  combustive  material,  burned 
clay  or  shale. 

F-402.2.3  Class  2  concrete:  Concrete  of  Class  2 
shall  be  so  proportioned  as  to  have  a  strength  of  at 
least  1500  pounds  psi,  the  coarse  aggregate 
consisting  of  sandstone,  granite,  quartzite, 
siliceous  gravel  or  other  similar  material  not  over 
one  inch  in  size. 


F-402.2.4  Masonry:  Masonry  shall  be  laid  in 
lime-cement  or  cement  mortar,  or  approved 
masonry  cement  mortar,  except  that  masonry  of 
gypsum  tile  shall,  and  masonry  of  structural  clay 
tile  may,  be  laid  in  gypsum  mortar.  Masonry  shall 
be  thoroughly  bonded  by  breaking  joints  in 
successive  courses  or  by  the  use  of  metal  ties. 

F-402.2. 5  Brick:  Brick  shall  be  burned  clay  or 
shale,  concrete  or  sand-lime  brick  of  Grade  C  or 
better. 

F-402.2.6  Stone:  Stone  shall  be  limestone, 
marble,  slate  or  equally  fireresistive  natural  stone. 
Sandstone,  granite  or  other  stone  which,  because 
of  its  crystalline  structure  or  for  other  reason,  is 
less  fireresistive,  shall  not  be  considered  fire 
protection  for  structural  metal,  but  may  be  used  in 
a  masonry  wall  not  less  that  12  inches  thick 
required  to  have  fireresistance.  Stone  masonry 
shall  have  the  same  fireresistive  rating  as  brick 
masonry. 

F-402.2.7  Cast  stone:  Cast  stone  masonry  shall 
have  the  same  fireresistive  rating  as  brick 
masonry. 

F-402.2.8  Concrete  blocks:  Concrete  blocks, 
whether  solid  or  hollow,  shall  have  as  coarse 
aggregate  limestone,  trap  rock,  blast  furnace  slag, 
cinders  containing  not  more  than  20%  of 
combustible  material,  burned  clay  or  shale. 

F-402.2.9  Structural  ciay  tile:  Structural  clay  tile 
shall  conform  to  the  specifications  for  load- 
bearing  tile,  floor  tile  or  partition  tile.  Where 
partition  tile  is  specified  load-bearing  tile  may  be 
used. 

F-402.2.10  Gypsum.  Gypsum  tile  or  pre-cast 
gypsum  concrete,  whether  solid  or  hollow,  shall 
conform  to  Standard  Specifications  for  Gypsum 
Partition  Tile  or  Block  of  the  American  Society 
for  Testing  Materials  and  shall  not  contain  more 
than  3%  by  weight  of  wood  or  other  combustible 
binder  or  filler. 

F-402.2.1 1  Gypsum  concrete:  Gypsum  concrete 
shall  not  contain  more  than  12/4  by  weight  of 
wood  or  other  combustive  binder  or  filler  and 
shall  have  a  compressive  strength  of  at  least  500 
psi.  It  shall  not  be  used  where  exposed  to  the 
elements. 

F-402.2. 12  Lath:  Expanded  metal  or  wire  lath  as 
a  base  or  reinforcement  for  plastering  shall  weigh 
not  less  that  2.2  pounds  per  square  yard  and  shall 
have  not  less  than  2Vi  meshes  per  inch. 

F-402.2. 13  Metal  mesh  for  masonry:  Metal 
mesh  reinforcement  specified  for  masonry  fire 
protection  of  structural  metal  shall  consist  of  wire 
lath  strips  the  full  thickness  of  the  masonry,  laid 
in  the  beds  thereof,  or  its  approved  equivalent. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


F-402.14  Metal  mesh  for  concrete:  Metal  mesh 
reinforcement  specified  for  concrete  fire 
protection  of  structural  metal  shall  consist  of  wire 
mesh  weighing  not  less  than  IV2  pounds  per 
square  yard  with  wire  spaced  not  over  four  inches, 
or  not  less  than  No.  1 1  gauge  steel  wire  spaced 
not  over  four  inches  apart,  or  its  approved 
equivalent. 

F-402.2.15  Cement  plaster:  Cement  plaster 
shall  be  proportioned  of  one  part  Portland  cement, 
and  not  more  than  two  parts  of  sand  measured  by 
volume  dry  and  loose  to  which  may  be  added  lime 
putty  or  hydrated  lime  not  exceeding  1 5%  of  the 
cement. 

F-402.2.16  Gypsum  plaster:  Gypsum  plaster, 
except  where  otherwise  specified,  may  contain 
sand,  not  in  excess  of  three  times  the  weight  of 
the  gypsum. 

F-402.2.17  Lime  plaster:  Lime  plaster  shall 
consist  of  a  mixture  of  one  part  lime,  not  over 
three  parts  sand,  and  water. 

F-402.2.18  Pneumatically  projected  mortar: 

Pneumatically  projected  mortar  made  of  Portland 
cement,  sand  nd  water  shall  be  rated  for  fire 
protection  the  same  as  Class  1  concrete. 

F-402.2.19  Concrete  fill:  Concrete  fill,  where 
specified  in  this  appendix  in  connection  with 
hollow  masonry  units  shall  consist  of  Class  1  or 
Class  2  concrete  poured  in  the  hollow  spaces  of 
the  units  as  they  are  laid. 

F-402.2.20  Reinforced  concrete:  Portland 
cement  concrete  or  gypsum  concrete  poured  in 
place  as  fire  protection  for  beams,  trusses  and 
other  horizontal  or  inclined  members  of  structural 
steel  and  pneumatically  projected  mortar  applied 
to  structural  steel  as  fire  protection  shall  be 
reinforced  with  metal  mesh  reinforcement. 
Concrete  protection  for  vertical  columns  of 
structural  metal  shall  have  reinforcing  consisting 
of  No.  5  wire  spaced  not  over  eight  inches  apart 
or  its  equivalent.  Reinforcement  shall  be  wrapped 
around  the  structural  member  and  so  arranged  as 
to  be  completely  embedded  in  the  fire  protection 
material  and  to  ensure  its  integrity. 

F-402.2.21  Reinforced  plaster:  Plaster  used  as 
fire  protection  or  to  resist  the  spread  of  fire  shall 
be  reinforced  with  metal  lath,  except  plaster  less 
than  one  inch  thick  or  masonry  or  concrete. 

F-402.2.22   Replacement     material:     In    the 

protection  of  structural  metal  including 
reinforcement,  Vi  inch  of  cement  or  gypsum 
plaster  may  replace  an  equal  thickness  of  poured 
concrete  or  pneumatically  projected  mortar  as 
protective  material;  and  one  inch  of  cement  or 
gypsum  plaster  reinforced  with  metal  lath  may 
replace  an  equal  thickness  of  poured  concrete, 


pneumatically  projected  mortar  or  masonry 
protection. 

F-402.2.23  Plaster:  Where  plaster  is  required 
without  other  specification,  it  shall  consist  of  Vz 
inch  of  cement  or  gypsum  plaster,  except  that  only 
gypsum  plaster  shall  be  used  on  gypsum  masonry. 

F-402.2.24  Thickness:  In  this  appendix,  except 
where  otherwise  specifically  stated,  the  thickness 
given  in  a  list  of  materials  applies  to  the  next 
following  item  only,  and  not  to  the  total  thickness 
where  additional  materials  are  specified. 

F-402.2.25  Embedding  limitations:  Pipes,  wires, 
conduits  and  ducts  shall  not  be  embedded  in  or 
placed  behind  the  fire-protective  materials 
required  for  the  protection  of  struetwal-steel  or 
iron  except  as  otherwise  provided  in  this 
paragraph.  Above  fire-protective  hung  ceilings 
and  within  the  enclosed  space  in  building  of 
Type  1  and  Type  2  construction  within  which, 
other  than  the  enclosure,  fire  protection  of  steel  is 
not  required,  pipes,  wires,  conduits  and  ducts  may 
be  placed,  provided  they  are  so  arranged  and  so 
secured  that  they  will  not,  either  by  expanding  in 
the  event  of  fire,  or  otherwise  impair,  the 
effectiveness  of  the  enclosing  protective 
materials.  Electric  conduits  and  wires  and  gas 
pipes  may  be  embedded  in  concrete  or  masonry 
fire  protection  of  structural  steel  where  the 
protective  material  is  reinforced  with  wire  mesh, 
provided  they  shall  have  protective  covering 
except  over  the  tops  of  beams  and  girders,  at  least 
as  thick  as  required  for  the  steel. 

F-402.2.26  Damage  protection:  In  factories, 
garages,  warehouses  and  other  buildings  in  which 
the  fire-protective  covering  required  for  steel  or 
iron  columns  may  be  damaged  by  the  movement 
of  vehicles,  materials  or  equipment,  such  covering 
shall  be  protected  by  metal  or  other  material  in  a 
manner  satisfactory  to  the  building  official. 

F-402.2.27  Firestopping:  Firestopping  shall 
mean  the  stopping  off  or  enclosure  at  the  ends  and 
wherever  else  specified  of  the  spaced  between 
studs  of  partitions,  joists  of  floors  and  roofs  and 
other  similar  spaces  to  prevent  drafts  of  air  and 
the  communication  of  fire  from  one  such  space  to 
another.  Fire-stopping  shall  consist  of  wood  not 
less  than  1 V2  inches  thick,  of  sheet  metal  not  less 
than  No.  24  gauge  or  of  masonry,  or  a 
combination  of  such  materials.  Firestopping  shall 
be  tightly  fitted  in  the  space  to  be  filled,  about 
pipes,  wires  and  ducts  and,  if  cut  or  disturbed  in 
the  placement  of  pipes,  wires  and  ducts,  shall  be 
repaired. 

F-402.3  Fire  protection  of  steel  columns: 

F-402.3.1  Protective  thickness:  Structural  steel 
columns  required  to  have  fire  protection  of  a 
given  rating  shall  be  covered  on  all  sides  with 


728 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


protective  material  having  not  less  than  the 
thickness  necessary  for  the  required  rating. 
Except  where  "no  fill"  is  specified,  re-entrant  and 
other  accessible  spaces  behind  the  specified  outer 
protection  shall  be  filled  with  concrete  or  brick 
masonry  or  the  material  of  the  outer  protection. 

F-402.3.2  Fireresistance  rating:  Materials  shall 
be  assumed  to  afford  to  steel  columns  fire 
protection  of  the  rating  indicated  in  the  following 
Appendix  F-402.3.3  through  F-402.3.6: 

F-402.3.3  Four  hour  rating: 

1 .  Two  inches  Class  1  concrete. 

2.  Three  inches  Class  2  concrete,  metal  mesh 
reinforcement. 

3 .  3  Vi  inches  brick  masonry. 

4.  Two  layers  two  inch  structural  clay 
partition  tile  masonry,  metal  mesh  in  beds. 

5.  Two  inches  structural  clay  partition  tile 
masonry,  concrete  fill,  metal  mesh  in  beds,  % 
inch  gypsum  plaster. 

6.  Four  inches  structural  clay  partition  tile 
masonry,  concrete  fill,  metal  mesh  in  beds,  5/s 
inch  lime  plaster. 

7.  Four  inches  structural  clay  partition  tile  or 
concrete  block  masonry,  concrete  fill,  plaster. 

8.  Three  inches  hollow  gypsum  tile  masonry 
and  plaster. 

9.  Two  inches  gypsum  concrete,  metal  mesh 
reinforcement. 

10.  Two  inches  solid  gypsum  tile  masonry 
and  plaster. 

11.  Three  inches  solid  cinder  concrete  block 
masonry  and  plaster. 

12.  Four  inches  hollow  cinder  concrete  block 
masonry  and  plaster 

F-402.3.4  Three  hour  rating: 

1.  1%  inches  Class  1  concrete. 

2.  Two  inches  Class  2  concrete,  metal  mesh 
reinforcement. 

3.  Two  inches  gypsum  concrete. 

4.  Two  inches  solid  cinder  concrete  block 
masonry  and  plaster. 

5.  Two  inches  structural  clay  partition  tile 
masonry,  concrete  fill. 

6.  Four  inches  structural  clay  partition  tile 
masonry,  concrete  fill,  metal  mesh  in  beds,  5/s 
inch  lime  plaster. 

F-402.3.5  Two  hour  rating: 

1 .  \Vi  inches  Class  1  concrete. 

2.  Two  inches  Class  2  concrete,  metal  mesh 
reinforcement. 

3.  One  inch  Class  1  or  Class  2  concrete 
encased  in  standard  weight  steel  or  wrought 
iron  pipe 

4.  Two  inches  structural  clay  partition  tile 
masonry  and  plaster. 


5.  Two  layers  plaster,  each  on  metal  lath,  with 
%  inch  air  space  between,  two  inches  total 
thickness. 

6.  Two  inches  gypsum  concrete. 

7.  Two  inches  solid  or  three  inches  hollow 
gypsum  tile  masonry. 

F-402.3.6  One  hour  rating: 

1 .  One  inch  Class  1  concrete. 

2.  lYi  inches  Class  2  concrete  with  metal 
mesh  reinforcement. 

3.  2%  inches  brick  masonry. 

4.  Two  inches  structural  clay  partition  tile  or 
concrete  block  masonry. 

5.  One  inch  cement  or  gypsum  plaster  on 
metal  lath. 

F-402.3.7  Thickness:  The  thickness  of  protection 
on  the  outer  edges  of  lugs  or  brackets  need  not 
exceed  one  inch. 

F-402.4  Fire  protection  of  cast  iron  columns: 

F-402.4.1  Protective  thickness:  Cast  iron 
columns  required  to  have  fire  protection  of  a 
given  rating  shall  be  covered  on  all  sides  with 
protective  materials  having  not  less  than  the 
thickness  necessary  for  the  required  rating.  Re- 
entrant spaces,  if  any  on  the  exterior  of  cast  iron 
columns,  and  other  accessible  spaces  behind  the 
specified  protection,  shall  be  filled  with  Class  1 
concrete  or  brick  masonry  or  the  material  of  the 
outer  protection. 

F-402.4.2  Fireresistance  rating:  Materials  shall 
be  assumed  to  afford  to  cast  iron  columns  fire 
protection  of  the  rating  indicating  in  the  following 
Appendix  F-402.4.3  through  F-402.4.5: 

F-402.4.3  Four  hour  rating:  Cast  iron  columns 
shall  not  be  used  where  the  protection  of  a  four 
hour  rating  is  required. 

F-402.4.4  Three  hour  rating: 

1.  Two  inches  Class  2  concrete. 

2.  Three  inches  Class  2  Concrete,  metal  mesh 
reinforcement. 

3 .  Two  inches  structural  clay  partition  tile  or 
concrete  block  masonry  concrete  fill. 

4.  1  Vi  inches  cement  or  gypsum  plaster  on 
metal  lath  and  metal  furring  to  form  Vi  inch  air 
space. 

5.  l'/i  inches  Class  1  concrete. 

6.  Two  inches  Class  2  concrete  with  metal 
mesh  reinforcement. 

F-402.4.5  One  hour  rating: 

1 .  One  inch  Class  1  concrete. 

2.  1V2  inches  Class  2  concrete  with  metal 
mesh  reinforcement. 

3.  One  inch  cement  or  gypsum  plaster  on 
metal  lath. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


F-402.5   Fire  protection   of  steel   in   reinforced 
concrete  columns: 

F-402.5.1  Protection  thickness:  The  main  steel 
reinforcement,  including  spiral  reinforcement  and 
-  ties  larger  than  Vi  inch,  in  reinforced  concrete 
columns  required  to  have  fire  protection  of  a 
given  rating  shall  be  covered  with  concrete  having 
not  less  than  the  thickness  listed  in  Appendix  F- 
402.5  for  the  rating  indicating  in  the  following 
Appendix  F-402.5. 2  through  F-402.5. 6. 

F-402.5.2  Four  hour  rating: 

1 .  1/4  inches  Class  1  concrete. 

2.  Two  inches  Class  2  concrete. 

F-402.5.3  Three  hour  rating:  1 XA  inches  Class  1 
or  Class  2  concrete. 

F-402.5.4  Two  hour  rating: 

1 .  One  inch  Class  1  concrete. 

2.  1  Vz  inches  Class  2  concrete. 

F-402.5. 5  One  hour  rating:  One  inch  Class  1  or 
Class  2  concrete. 

F-402.5. 6  Ties  less  than  Vi  inch:  The  thickness 
of  protection  on  column  ties  not  larger  than  Vz 
inch  may  be  Vz  inch  may  be  Vz  inch  thinner  than 
that  listed  above. 

F-402.6  Fire  protection  of  steel  beams,  girders, 
and  trusses: 

F-402.6. 2  Protective  thickness:  Steel  beams, 
girders  and  trusses  or  the  members  of  trusses, 
required  to  have  fire  protection  of  a  given  rating, 
shall  be  covered  on  all  sides  with  material  having 
not  less  than  the  thickness  necessary  for  the 
required  rating. 

F-402.6.3  Four  hour  rating: 

1 .  Two  inches  Class  1  concrete. 

2.  Three  inches  Class  2  concrete. 

3.  Three  inches  structural  clay  partition  tile  or 
concrete  block  masonry  and  plaster. 

4.  Three  inches  hollow  gypsum  tile  masonry 
and  plaster. 

5.  Two  inches  gypsum  concrete. 

6.  Two  inches  solid  gypsum  tile  masonry  and 
plaster. 

F-402.6.4  Three  hour  rating: 

1     1%  inches  Class  1  concrete. 

2.  2Vz  inches  Class  2  concrete. 

3.  Two  inches  gypsum  concrete. 

4.  Two  inches  structural  clay  partition  tile,  or 
concrete  block  masonry  and  plaster. 

5.  Two  inches  solid,  or  three  inches  hollow 
gypsum  tile  masonry. 

F-402.6. 5  Two  (2)  hour  rating: 

1 .  1 Vz  inches  of  Class  2  concrete 

2.  Two  inches  gypsum  concrete. 


F-402.6. 6  One  hour  rating: 

1      One  inch  Class  1  concrete. 

2.  1 Vz  inches  Class  2  concrete. 

3.  Va  inch  or  cement  or  gypsum  plaster  on 
metal  lath. 

F-402.7   Fire  protection  of  steel   in   reinforced 
concrete  beams: 

F-402.7. 1  Protective  thickness:  The  main  steel 
reinforcement,  including  stirrups  larger  than  Vz 
inch,  in  reinforced  concrete  beams,  girders  and 
trusses,  including  the  ribs  of  reinforced  concrete 
ribbed  floors  or  roofs  where  one  or  both  sides  of 
the  ribs,  in  addition  to  the  soffit,  are  exposed  to 
fire,  required  to  have  fire  protection  of  a  given 
rating,  shall  be  covered  on  all  sides  with  concrete 
having  not  less  than  the  thickness  listed  in 
Appendix  F-402.7  for  the  required  rating.  Where 
a  reinforced  concrete  floor  or  roof  has  a  flush 
ceiling  formed  with  approved  permanent  masonry 
filler  between  ribs,  the  reinforcement  shall  have 
the  protection  required  for  reinforcing  steel  of 
floors  and  roofs  in  Appendix  F-402.8. 

F-402.7.2  Four  hour  rating: 

1 .  1 Vz  inches  Class  1  concrete. 

2.  Two  inches  Class  2  concrete. 

F-402.7.3  Three  hour  rating:  1V2  inches  Class  1 
or  Class  2  concrete. 

F-402.7.4  Two  hour  rating: 

1.  One  inch  Class  1  concrete. 

2.  1 Vz  inches  Class  2  concrete. 

F-402.7. 5  One  hour  rating:  One  inch  Class  1  or 
Class  2  concrete. 

F-402.7.6    Stirrups    less    than    Vi    inch:    The 

thickness  of  protection  on  stirrups  not  larger  than 
Vz  inch  may  be  less  than  that  listed  by  not  more 
than  Vi  inch. 

F-402.8  Fire  protection  of  steel  reinforcing  in 
floors  and  roofs: 

F-402.8. 1  Protection  thickness:  The  steel 
reinforcement  in  reinforced  concrete  floors  and 
roofs  with  flush  or  plane  ceiling,  such  that  the 
exposure  to  fire  is  on  the  soffit  only,  required  to 
have  fire  protection  of  a  given  rating,  shall  be 
covered  with  concrete  having  not  less  than  the 
thickness  listed  in  Appenfix  F-402.8  for  the 
required  rating.  In  floors  or  roofs  having 
reinforced  concrete  ribs  where  the  concrete 
surrounding  the  steel  reinforcement  is  exposed  to 
fire  on  one  or  both  sides  in  addition  to  the  soffit, 
such  reinforcement  shall  have  the  protection 
specified  in  Appendix  F-402.7  for  steel  in 
reinforced  concrete  beams. 

F-402.8.2  Four  hour  rating: 

1.    One  inch  Class  1  concrete. 


730 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


2.    1  'A  inches  Class  2  concrete. 

F-402.8.3  Three  hour  rating:  One  inch  Class  1 
or  Class  2  concrete. 
F-402.8.4  Two  hour  rating: 

1.  V»  inch  Class  1  concrete. 

2.  One  inch  Class  2  concrete. 

F-402.8.5  One  hour  rating:  3A  inch  Class  1  or 

Class  2  concrete. 

F-402.9  Fireresistive  floor  and  roof  construction: 

F-402.9.1  Protective  thickness:  Floors  and  roofs 
required  to  have  resistance  of  a  given  rating  to  the 
spread  of  fire  shall  have  such  thickness  of  the 
materials  of  which  it  is  constructed,  as  shall  be 
'necessary  for  the  required  rating,  and  structural 
metal  forming  a  part  of  such  floors  or  roofs  shall 
have  protection  against  fire  of  such  required 
rating.  Floors  and  roofs  required  to  have  two  hour 
or  longer  resistance  to  fire  be  constructed  of 
noncombustible  materials.  Granolithic,  burned 
clay  tile,  ceramic  tile  or  other  similar 
incombustible  floor  finish  of  a  given  thickness 
may  be  substituted  for  an  equal  thickness,  and 
sand,  cinder  or  other  incombustible  filling 
material,  with  or  without  embedded  wooden 
screeds,  may  be  substituted  for  %  its  thickness,  of 
the  floor  or  roof  construction  material  specified  in 
Appendix  F-402.9,  provided  that  such  floors  and 
roofs  shall  have  adequate  thickness  for  structural 
purposes. 

F-402.9. 2  Fireresistance  rating:  Floor  or  roof 
construction  shall  be  assumed  to  afford  resistance 
to  the  spread  of  fire  of  the  rating  indicated  in  the 
following  Appendix  F-402.9. 3  through  F-4029.6: 

F-402.9.3  Four  hour  rating: 

1.  Four  inches  solid  slab  of  reinforced 
Portland  cement  concrete  or  reinforced  precast 
gypsum  concrete. 

2.  Four  inches  solid  masonry  arched  or  slabs 

3.  Four  inches  structural  clay  floor  tile 
masonry  arches  or  slabs  with  top  covering  of 
not  less  than  two  inches  of  solid  masonry  or 
reinforced  concrete. 

4.  Five  inches  combination  reinforced 
Portland  cement  concrete  slab  consisting  of 
permanent  fillers  of  concrete  block,  gypsum  or 
structural  clay  tile  and  1  Vi  inches  of  concrete 
topping;  but  if  structural  clay  partition  tiles  are 
used  for  fillers,  they  shall  be  plastered  on  the 
soffit. 

F-402.9.4  Three  hour  rating 

1.  Three  inches  solid  slab  of  reinforced 
Portland  cement  concrete  or  reinforced  precast 
gypsum  concrete. 

2.  Three  inches  solid  masonry  arches  or  slabs. 

3.  Four  inches  structural  clay  floor  tile 
masonry,  arches  or  slabs  with  top  covering  of 


not  less  than  1  Vz  inches  of  solid  masonry  or 
reinforced  concrete. 

4.  Four    inches    combination    reinforced 

Portland  cement  concrete  slab  consisting  of 
permanent  fillers  of  concrete  block,  gypsum  or 
structural  clay  tile  and  one  inch  concrete 
topping;  but  if  structural  clay  partition  tiles  are 
used  for  fillers,  they  shall  be  plastered  on  the 
soffit. 

F-402.9.5  Two  hour  rating: 

1.  2V2  inches  solid  slab  of  reinforced  Portland 
cement  concrete  or  reinforced  precast  gypsum 
concrete. 

2.  2/4  inches  solid  masonry  arches  or  slabs. 

3.  Three  inches  structural  clay  floor  tile 
masonry,  arches  or  slabs  with  top  covering  of 
not  less  than  one  inch  of  solid  masonry  or 
reinforced  concrete. 

F-402.9. 6  One  hour  rating: 

1.  Three  inches  structural  clay  floor  tile 
masonry,  arches  or  slabs  with  all  joints 
thoroughly  filled  with  cement  or  gypsum 
mortar. 

2.  Wood  floor  or  roof  construction  with  joists 
not  less  than  l5/s  inches  in  least  dimension, 
firestopped,  double  board  floor,  approved 
asbestos  felt  between  lay  of  boards,  and  with  a 
ceiling  of  at  least  Vt  inch  cement  or  gypsum 
plaster  on  metal  lath. 

3.  Steel  beams  or  steel  joists  not  more  than  36 
inches  apart  on  centers  with  noncombustible 
floor  and  a  ceiling  of  at  least  %  inch  cement  or 
gypsum  plaster  on  metal  lath  furring. 

F-402.10  Fireresistive  ceiling  construction: 

F-402.10.1  Protective  thickness:  Ceilings 
required  to  afford  fire  protection  of  a  given  rating 
to  the  floor  or  roof  framing  under  which  it  is 
supported  shall  be  of  fireresistive  materials  of  at 
least  the  thickness  necessary  for  the  given  rating. 
A  fireresistive  ceiling  and  all  hangers  and 
fastenings  necessary  for  its  support  to  the 
protected  framing  shall  be  of  noncombustible 
materials.  It  shall  be  capable  of  sustaining  its  own 
weight  without  exceeding  allowable  stresses. 
Metal  reinforcement  in  such  a  ceiling  shall  be 
protected  from  fire  as  specified  in  Appendix  F- 
402.8  for  reinforcing  in  a  floor. 

F-402.10.2  Fireresistance  rating:  Ceiling 
construction  shall  be  assumed  to  afford  to  floor  or 
roof  framing  fire  protection  of  the  rating  indicated 
in  the  following  Appendix  F-402. 10.3  through  F- 
402.10.6. 

F-402. 10.3  Four  hour  rating: 

1 .  2V2  inches  solid  slab  of  reinforced  Portland 
cement  concrete  or  reinforced  precast  gypsum 
concrete. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


731 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


2.  Two  inches  precast  reinforced  gypsum 
concrete,  plastered. 

F-402.10.4    Three  hour  rating: 

1.  Two  inches  solid  slab  of  reinforced 
Portland  cement  concrete  or  reinforced  precast 
gypsum  concrete. 

2.  Two  inches  precast  reinforced  gypsum 
concrete,  lapped  or  rabbeted  joints. 

F-402.10.5  Two  hour  rating:  \Vz  inches  solid 
slab  of  reinforced  Portland  cement  concrete  or 
reinforced  precast  gypsum  concrete. 

F-402.10.6  One  hour  rating:  %  inch  cement  or 
gypsum  plaster  on  metal  lath. 

F-402.11      Fireresistive      bearing      walls      and 
partitions: 

F-402.11. 1  Protective  thickness:  Bearing  walls 
and  partitions  required  to  have  resistance  to  fire  or 
the  spread  of  fire  of  a  given  rating  shall  be 
constructed  of  fireresistive  materials  and  shall 
have  at  least  the  thickness  necessary  for  the 
required  rating.  Walls  required  to  have  two  hour 
or  longer  rating  shall  be  of  noncombustible 
materials.  Steel  reinforcement  in  reinforced 
concrete  walls  shall  have  the  same  protection  for 
the  given  rating  as  is  required  in  Appendix  F- 
402.9  for  floors. 

F-402.11.2  Fireresistance  rating:  Bearing  walls 
and  partitions  shall  be  assumed  to  have  resistance 
to  fire  and  the  spread  of  fire  of  the  rating  indicated 
in  the  following  Appendix  F-402. 1 1 .3  through  F- 
40211.6: 

F-402.11.3  Four  hour  rating: 

1 .  Eight  inches  solid  brick  masonry. 

2.  12  inches  hollow  wall  of  brick  masonry, 
minimum  eight  inch  masonry  thickness. 

3.  12  inches  structural  clay  load-bearing  tile 
masonry  with  two  units  and  not  less  than  three 
cells  in  the  thickness  of  the  wall. 

4.  Eight  inches  structural  clay  load-bearing 
tile  masonry  with  one  unit  and  not  less  than 
two  cells  in  the  thickness  of  the  wall,  plastered 
both  sides. 

5.  12  inches  concrete  block  masonry  with  one 
unit  and  not  less  than  two  cells  in  the  thickness 
of  the  wall. 

6.  Eight  inches  one  piece  concrete  block 
masonry  with  shells  and  webs  at  least  P/2 
inches  thick,  plastered  both  sides. 

7.  12  inches  total  thickness  of  brick  masonry 
facing  bonded  to  structural  clay  load-bearing 
tile  masonry  backing. 

8.  Eight  inches  solid  concrete. 

9.  Six  inches  solid  reinforced  concrete. 

10.  A  steel  or  reinforced  concrete  frame 
bearing  wall  in  which  the  steel  has  fire 
protection   of  four  hour  rating,   with   panel 


filling  as  specified  in  Appendix  F-402. 12  for  a 
nonbearing  wall  of  four  hour  rating. 

F-402.11. 4  Three  hour  rating: 

1.  Eight  inches  structural  clay  load-bearing 
tile  masonry  with  two  units  and  not  less  than 
four  cells  in  the  thickness  of  the  wall. 

2.  12  inches  structural  clay  load-bearing  tile 
masonry  with  one  unit  and  not  less  than  three 
cells  in  the  thickness  if  the  wall. 

3.  Eight  inches  one  piece  concrete  block 
masonry  with  shells  and  webs  not  less  than  1  Vz 
inches  thick,  plastered  both  sides. 

4.  Eight  inches  one  piece  concrete  block 
masonry  with  shells  and  webs  not  less  than  two 
inches  thick. 

5.  Five  inches  solid  reinforced  concrete. 

6.  A  steel  or  reinforced  concrete  frame 
bearing  wall  in  which  the  steel  has  fire 
protection  of  three  hour  rating,  with  panel 
filling  as  specified  in  Appemdix  F-402. 12  for 
a  nonbearing  wall  of  three  hour  rating. 

F-402.11.5  Two  hour  rating: 

1.  Eight  inches  structural  clay  load-bearing 
tile  masonry  with  not  less  than  three  cells  in 
the  thickness  of  the  wall. 

2.  Eight  inches  concrete  block  masonry  with 
shells  and  webs  not  less  than  1  Vz  inches  thick. 

3.  A  steel  or  reinforced  concrete  frame 
bearing  wall  in  which  the  steel  has  fire 
protection  of  two  hour  rating,  with  panel  filling 
as  specified  in  Appendix  F-402. 12  for  a 
nonbearing  wall  of  two  hour  rating. 

F-402.11.6  One  hour  rating: 

1.  A  steel  or  wooden  stud  bearing  wall 
covered  on  both  sides  with  one  inch  cement  or 
gypsum  plaster  on  metal  lath,  firestopped  if  of 
wood. 

2.  A  steel  or  reinforced  concrete  frame 
bearing  wall  in  which  the  steel  has  fire 
protection  of  one  hour  rating,  with  panel  filling 
as  specified  in  Appendix  F-402. 12  for  a 
nonbearing  wall  of  one  hour  rating. 

F-402. 12    Fireresistive    nonbearing    walls    and 
partitions: 

F-402. 12.1  Protective  thickness:  Nonbearing 
walls  and  partitions  required  to  have  resistance  to 
fire  and  the  spread  of  fire  of  a  given  rating  shall 
be  constructed  of  fireresistive  materials  and  shall 
have  at  least  the  thickness  necessary  for  the 
required  rating.  Walls  required  to  have  two  hour 
or  longer  rating  shall  be  of  incombustible 
materials.  Steel  reinforcement  in  reinforced 
concrete  walls  shall  have  the  same  protection  for 
the  given  rating  as  is  required  in  Appendix  F- 
402.8. 


732 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


F-402.12.2  Fireresistance  rating  Nonhealing 
walls  and  partitions  shall  be  assumed  to  have 
resistance  to  fire  and  the  spread  of  fire  of  the 
rating  indicated  in  the  following  Appendix  F- 
402.12.3  through  F-402. 12. 6. 

F-402.12.3  Four  hour  rating: 

1 .  Eight  inches  solid  brick  masonry. 

2.  3'/2  inches  solid  brick  masonry,  plastered 
goth  sides. 

3.  Six  inches  structural  clay  load-bearing  tile, 
plastered  both  sides. 

4.  Six  inches  solid  concrete. 

5.  Four  inches  solid  reinforced  concrete. 

6.  Any  wall  which,  as  a  bearing  wall,  has  a 
three  hour  or  four  hour  rating  in  Appendix  F- 
402.1 1,  except  the  steel  or  reinforced  concrete 
frame  bearing  wall. 

F-402. 12.4  Three  hour  rating: 

1.  3  Vi  inches  solid  brick  masonry. 

2.  Four  inches  structural  clay  load-bearing 
tile,  plastered  both  sides. 

3.  Four  inches  solid  concrete. 

4.  Three  inches  reinforced  concrete. 

5.  Any  wall  which,  as  a  bearing  wall,  has  a 
two  hour  rating  in  Appendix  F-402. 1 1  except 
the  steel  or  reinforced  concrete  frame  bearing 
wall. 

F-402.12.5  Two  hour  rating: 

1.  Three    inches    gypsum    tile    masonry 

plastered  both  sides  except  in  exterior  walls. 

2.  Eight  inches  structural  clay  partition  tile 
masonry,  plastered  both  sides. 

3 .  Eight  inches  structural  clay  load-bearing  tile, 
with  three  cells  in  the  thickness  of  the  wall. 

4.  2'/2  inches  solid  cement  or  sanded  gypsum 
plaster  on  metal  lath  and  noncombustible 
studding. 

5.  Three  inches  total  thickness  of  hollow  wall,  % 
inch  cement  or  gypsum  plaster  on  metal  lath  and 
noncombustible  studding. 

6.  Three  inches  total  thickness  of  hollow  wall,  3A 
inch  cement  or  gypsum  plaster  on  metal  lath  and 
wooden  studding,  firestopped. 

F-402. 13  Fireresistive  doors: 

F-402.13.1  General:  Doors  which  are  required  to 
be  fire  doors,  fireresistive  doors,  or  of  fireresistive 
construction  shall  conform  to  the  requirements  of 
Appendix  F-402. 13  and  Appendix  F-402. 14 

F-402. 13.2  Classification:  Fire  doors  shall  be 
classified  for  the  proposes  of  this  code  as  Class  A, 
Class  B,  and  Class  C. 

F-402.13.3  Class  A  fire  doors:  Class  A  fire  doors 
shall  be  doors  of  the  following  construction  and  as 
specified  in  Appendix  F-402. 14: 

1      Tin-clad,  three  ply  wood  core,  sliding. 


2.  Tin-clad,  three  ply  wood  core,  swinging 
single  leaf,  doorway  not  over  six  feet  wide. 

3.  Tin-clad,  three  ply  wood  core,  swinging  in 
pairs,  doorway  not  over  feet  wide. 

4.  Hollow  metal,  swinging  single  leaf, 
doorway  not  over  four  feet  wide. 

5.  Hollow  metal,  swinging  in  pairs,  doorway 
not  over  eight  feet  wide. 

6.  Sheet  metal,  sliding,  single,  doorway  not 
over  ten  feet  wide. 

7.  Sheet  metal,  sliding  in  pairs,  doorway  not 
over  12  feet  wide. 

8.  Sheet  metal,  swinging  single  leaf,  doorway 
not  over  feet  wide. 

9.  Sheet  metal,  swinging  in  pairs,  doorway 
not  over  ten  feet  wide. 

10.  Steel  rolling  doorway  not  over  12  feet 
wide. 

1 1 .  Steel  plate,  doorway  not  over  four  feet 
wide. 

12.  Any  other  construction  equal  or  superior 
to  a  tin-clad  three  ply  wood  core  door  in  a 
standard  fire  test,  for  resistance  to  fire,  the 
spread  of  fire  and  smoke,  and  transmission  of 
heat. 

F-402.13.4  Class  B  fire  doors:  Class  B  fire  doors 
shall  be  doors  of  the  following  construction  and  as 
specified  in  Appendix  F-402. 14: 

1 .  Tin-clad,  three  ply  wood  core. 

2.  Tin-clad,  two  ply  wood  core,  sliding, 
doorway  not  over  ten  feet  wide. 

3.  Tin-clad,  two  ply  wood  core,  swinging 
single  leaf,  doorway  not  over  six  feet  wide. 

4.  Tin-clad,  two  ply  wood  core,  swinging  in 
pairs,  doorway  not  over  ten  feet  wide. 

5.  Hollow  metal,  sliding,  doorway  not  over 
eight  feet  wide. 

6.  Metal-clad,  paneled,  swinging  single  leaf, 
doorway  not  over  three  feet  wide. 

7.  Metal-clad,  paneled,  swinging  in  pairs, 
doorway  not  over  six  feet  wide. 

8.  Any  other  construction  equal  or  superior  to 
a  tin-clad  two  ply  wood  core  door  in  a  standard 
fire  test,  for  resistance  to  fire,  the  spread  of  fire 
and  smoke,  and  transmission  of  heat. 

F-402. 13.5  Class  C  fire  doors:  Class  C  Fire 
doors  shall  be  doors  of  the  following  construction 
and  as  specified  in  Appendix  F-402. 14: 

1.  Metal-clad,  paneled,  swinging  single  leaf, 
doorway  not  over  four  feet  wide. 

2.  Metal-clad,  paneled,  swinging  in  pairs, 
doorway  not  over  eight  feet  wide. 

F-402. 13.6  Substitution:  A  Class  A  door  may  be 
used  where  Class  b  or  Class  C  is  specified;  a 
Class  B  door  may  be  used  where  Class  C  is 
specified.  Two  Class  B  or  Class  C  doors  on 
opposite  sides  of  the  wall  may  be  used  where  a 
single  Class  A  or  Class  B  door  is  specified. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


733 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


F-402.13.7  Overlap:  Fireresistive  doors,  when 
closed,  shall  completely  cover  the  doorways  in  the 
walls  and  partitions  or  the  openings  in  the  floors 
or  roofs  to  which  they  ar  fitted.  A  swinging  fire 
door  shall  either  overlap  both  jambs  and  the  head 
of  the  opening  not  less  than  four  inches  or  be 
fitted  to  a  fireresistive  frame  with  a  rabbet  the  full 
thickness  of  the  door  and  with  not  less  than  Vi 
inch  overlap  on  the  door.  A  sliding  fire  door, 
except  in  enclosures  about  passenger  elevators, 
shall  overlap  both  jambs  and  the  head  of  the 
opening  not  less  than  four  inches.  A  sliding  fire 
door  in  an  enclosure  about  a  passenger  elevator 
shall  overlap  jambs,  head  and  adjoining  panels  not 
less  than  'A  inch.  Fire  doors  shall  fit  closely  at  the 
floor  with  clearance  of  not  over  V*  inch. 

'F-402.13.8  Thresholds:  In  buildings  with 
combustible  floors,  doorways  required  to  have 
fire  doors  shall  have  noncombustible  thresholds 
the  full  thickness  of  the  wall,  extending  at  least 
four  inches  from  the  face  of  the  wall  where  a  door 
is  hung  and  extending  laterally  at  least  six  inches 
behind  each  jamb  of  the  doorway.  Thresholds 
may  be  flush  with  the  floor. 

F-402.13.9  Rabbeted  frame:  The  rabbeted  frame 
of  a  swinging  fire  door  shall  be  constructed  of 
structural  steel  built  into  the  concrete,  masonry  or 
other  fireresistive  material  of  the  wall  about  the 
opening  and  secured  thereto,  except  that  the 
rabbeted  frame  of  a  Class  B  or  C  door  may  be  of 
wood,  covered  with  sheet  metal  not  less  than  No. 
26  gauge  in  thickness,  secured  to  the  wall  in  the 
opening. 

F-402.13.10  Fit:  Fire  doors  when  closed  shall  fit 
tightly  against  the  wall  or  frame  so  as  to  provide 
an  effective  stop  for  fire  and  smoke.  Except  for 
the  metal-covered  wooden  frame  specified  in 
Appendix  F-402. 10,  combustible  material  shall 
not  intervene  between  the  door  and  the 
fireresistive  material  of  the  wall,  floor  or  roof  to 
which  it  is  fitted. 

F-402.13.11  Hardware:  Hinge  hardware  for  fire 
doors  shall  be  of  malleable  iron  or  rolled 
structural  steel  not  less  than  %  inch  thick  except 
that  tubular  steel  track  for  sliding  doors  may  be 
not  less  than  Va  inch  thick.  Equivalent  thickness 
of  solid  bronze  or  brass  may  be  used.  Fire  doors 
shall  not  depend  upon  cords,  cables  or  chains  to 
support  them  in  closed  position  except  in  elevator 
shafts. 

F-402.13.12  Tracks:  Tracks  for  sliding  fire  doors 
shall  be  so  supported  that  a  track  hanger  comes  at 
each  door  hanger  when  the  door  is  closed.  Track 
hangers  shall  be  secured  to  wood  stud  walls  by 
through  bolts  and  to  concrete  walls  by  through 
bolts  or  approved  built-in  inserts.  Expansion 
shields  shall  not  be  used  to  support  fire  doors. 


F-402. 13.13  Hinges:  Hinges  for  swinging  fire 
doors,  except  in  wooden  stud  walls,  shall  be 
riveted  or  through-bolted  to  the  structural  steel 
frame  of  the  opening,  through-bolted  to  the  wall 
if  of  masonry  or  concrete  or  secured  by  approved 
inserts  in  the  concrete  or  built  into  masonry  in  an 
approved  manner 

F-402.13.14  Strap  hinges:  Strap  hinges  and 
sliding  door  hangers  shall  be  secured  to  fire  doors 
by  through-bolting,  riveting  or  welding. 
Swinging  fire  doors  in  rabbeted  frames,  except 
tin-clad,  wood  core  doors,  may  be  hung  on  butts. 
Other  swinging  fire  doors  shall  have  strap  hinges. 

F-402. 13.15  Straps,  locks  and  latches:  Sliding 
fire  doors  shall  have  adequate  stops  for  the  closed 
position.  Swinging  Class  A  fire  doors  shall  have 
surface  lathes  or  unit  locks.  Class  B  and  C  doors 
shall  have  surface  latches,  unit  or  mortise  locks. 
The  latch  bolts  of  unit  or  mortise  locks  on  fire 
doors  shall  have  a  throw  of  Vt  inch.  When 
mounted  in  pairs,  fire  doors  shall  be  rabbeted  by 
means  of  an  astragal  or  otherwise  where  they 
come  together.  One  of  a  pair  of  swinging  fire 
doors  shall  have  push  bolts  at  top  and  bottom  with 
a  throw  of  %  inch  and  the  other  shall  be  held  by 
latch  to  the  first. 

F-402.13.16  Opening  hardware:  Except  in 
detention  buildings,  fire  doors  hung  in  required 
exits  shall  be  so  fitted  with  hardware  that  they  can 
be  opened  from  inside  without  use  of  a  key  when 
the  building  is  occupied. 

F-402. 14  Fire  door  construction: 

F-402. 14.1  Fastening:  In  the  construction  of  fire 
doors,  solder  shall  not  be  used  except  for  filling 
joints.  Sheet  metal  shall  be  fastened  to  wood  by 
nailing  and  to  metal  frame  by  bolting,  riveting  or 
welding. 

F-402. 14.2  Glass:  Class  A  doors  shall  not  have 
glass  panels.  Class  B  doors  may  have  glass 
panels  not  larger  than  100  square  inches  in 
exposed  area  nor  more  than  12  inches  in  width  or 
height.  Class  C  doors  amy  have  glass  panels  not 
larger  than  2,016  square  inches  in  total  exposed 
area,  and  any  single  light  shall  not  have  an 
exposed  area  exceeding  1,296  square  inches. 
Glass  in  fire  doors  shall  be  wire  glass  not  less  than 
lA  inch  thick  and  shall  be  set  5/s  inch  in  grooves 
%  of  an  inch  deep. 

F-402.14.3:  Deleted 

F-402. 14.4  Tin-clay,  two  ply:  In-clad,  two  ply 
wood  core  doors  shall  be  shall  be  constructed  in 
accordance  with  the  specifications  of  the  National 
Board  of  Fire  Underwriters  for  such  doors  in 
Class  B  openings  and  shall  bear  the  label  of  the 
Underwriters'  Laboratories  to  this  effect. 


734 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  F 


F-402.14.5  Hollow  metals:  Hollow  metal  doors 
shall  have  substantial  stiles  and  rails  of  heavy 
pressed  steel,  reinforced  for  hinges  and  other 
hardware.  Panels  shall  be  of  sheet  filled  with 
asbestos  board  or  other  approved  insulating 
materials.  The  door  shall  be  assembled  by 
welding  or  riveting. 

F-402.14.6  Sheet  metals:  Sheet  metal  doors 
shall  be  constructed  with  a  rolled  steel  rigid  frame 
covered  both  sides  with  V16  inch  asbestos  board 
and  No.  26  gauge  corrugated  steel  metal,  with 
corrugations  vertical  on  one  side  and  horizontal 
on  the  other,  bound  on  the  edges  with  rolled  steel 
or  pressed  steel  shapes. 

F-402.14.7  Steel  rolling:  A  steel  rolling  fire  door 
shall  be  constructed  of  sheet  steel  interlocking 
slats,  sliding  in  grooves,  counterweighted  by 
springs,  with  the  roller  and  mechanism  enclosed 
in  heavy  sheet  metal. 

F-402.14.8  Steel  plate:  A  steel  plate  fire  door 
shall  be  constructed  of  not  less  than  No.  12  gauge 
steel  plate  mounted  on  a  rolled  steel  frame, 
assembled  by  welding  or  riveting. 

F-402.14.9  Metal  clad:  A  metal  clad,  paneled 
fire  door  shall  have  a  wood  core  with  stiles  and 
rails  not  less  than  1%  inches  thick  covered  with 
No.  26  gauge  sheet  steel;  panels  %  inch  thick 
covered  with  No.  26  gauge  sheet  steel,  set  %  inch 
in  grooves;  joints  of  metal  lapped  and  well  nailed. 

F-402.14.10  Class  A  label:  A  door  properly 
bearing  the  Underwriters'  label  certifying  that  it  is 
suitable  for  the  protection  of  a  Class  A  opening 
shall  be  acceptable  as  a  Class  A  door. 

F-402.14.11  Class  B  label:  A  door  properly 
bearing  the  Underwriters'  label  certifying  that  it  is 
suitable  for  the  protection  of  a  Class  B  opening 
shall  be  acceptable  as  a  Class  B  door,  except  that 
metal  clad  doors  wider  than  three  feet  shall  not  be 
accepted  as  Class  B  doors. 

F-402. 14.12  Class  C  label:  A  door  properly 
bearing  the  Underwriters'  label  certifying  that  it  is 
suitable  for  the  protection  of  a  Class  C  opening 
shall  be  acceptable  as  a  Class  C  door. 

F-402. 15  Fireresistive  shutters:  Shutters  required 
to  be  fire  shutters  or  fireresistive  shutters  shall  be 
constructed  and  hung  as  specified  for  Class  B 
fireresistive  doors  in  Appendix  F-402. 13  and  F- 
402.14. 

F-402.16  Fireresistive  windows: 

F-402. 16.1  General:  Windows  which  are 
required  to  be  fire  windows,  fireresistive 
windows,  or  of  fireresistive  construction  shall 
conform  to  the  requirements  of  Appendix  F- 
402.16 


F-402. 16.2  Moveable:  Firereisistive  windows 
may  be  fixed  or  arranged  to  open  and  close. 
Fixed  fireresistive  windows  shall  be  so  secured  in 
the  walls  in  which  they  are  placed  that  they  may 
expand  in  case  of  fire  without  buckling. 
Moveable  firereisitive  windows  shall  be  opened 
or  closed  in  one  of  the  following  manners: 

1.  One  or  more  sashes  may  slide  horizontally 
in  a  fireresistive  frame. 

2.  One  or  more  sashes  may  slide  vertically 
with  counterweights  or  with  tow  sashes 
counterbalanced  and  hung  on  chains.  If  a  sash 
is  closed  in  raised  position,  it  shall  have  a 
fastening. 

3.  A  sash  may  be  hinged  at  top,  bottom,  or 
either  side. 

4.  A  sash  may  be  pivoted  at  top  and  bottom  or 
at  the  sides. 

5.  A  sash  may  be  arranged  to  open  and  close 
in  any  other  approved  manner,  with  approved 
hardware. 

F-402. 16.3  Sash:  Moveable  sashes  in 
fireresistive  windows  shall  be  furred  to 
fireresistive  frames  of  the  same  or  similar 
construction.  Both  sashes  and  frames,  and  metal 
mullions  between  window  units,  shall  be  so  fitted 
in  the  walls  in  which  they  are  placed  as  to  be 
continuous  with  the  fireresistive  material  of  the 
wall  and  so  secured  that  they  may  expand  in  case 
of  fire  without  buckling. 

F-402. 16.4  Glass:  Glass  in  firereisistive 
windows  shall  be  wired  glass  not  less  than  Va 
inch  thick  and  the  area  of  a  single  light  shall  not 
exceed  720  square  inches.  Glass  shall  be  set  % 
inch  grooves  at  least  Vz  inch  deep.  Glass  shall  be 
secured  by  glazing  angles  or  molding  screwed  to 
the  sash  and  forming  continuous  grooves  for  the 
glass. 

F-402.16. 5  Construction:  Fireresistive  windows 
shall  be  of  the  following  construction: 

1.  Hollow  sheet  metal  sashes  and  frames 
fabricated  by  pressing,  welding,  riveting  or 
crimping  without  the  use  of  solder  or  other 
fusible  alloy,  except  for  filling  joints,  and 
bearing  the  label  of  Underwriters'  Laboratories. 

2.  Rolled  steel  or  pressed  steel  sashes 
fabricated  by  pressing,  welding,  riveting  or 
crimping,  of  a  make  and  style  approved  by  the 
commissioner. 

3.  Any  other  approved  constructions  as 
fireresistive  as  that  specified  in  Appendix  F- 
402.16.5  item. 

F-402. 16.6  Hollow  sheet  metal:  Fired 
fireresistive  windows  of  hollow  sheet  metal 
construction  shall  not  exceed  seven  feet  in  width 
not  ten  feet  in  height.  Fireresistive  windows  of 
hollow  sheet  metal  construction  with  moveable 
sashes  shall  not  exceed  six  feet  in  width  nor  ten 
feet  in  heitjht 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


735 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


F-402.16.7  Rolled  steel:  Fireresistive  windows 
of  rolled  steel  construction  shall  not  exceed  84 
square  feet  in  area  not  12  feet  in  either  height  or 
width. 

F-402. 16.8  Wind  pressure:  Fireresistive 
windows  and  their  fastenings  shall  be  capable  of 
resisting  the  wind  pressure  on  the  wall  of  the 
building  applied  either  on  he  inside  or  the  outside 
of  the  window  exceeding  allowable  stresses. 

F-402.16.9  Substitution:  Where  fireresistive 
windows  are  required,  wooden  windows  and  plain 
glass  may  be  substituted  provided  the  openings 
are  protection  by  fireresistive  doors  or  shutters, 
or,  in  buildings  of  approved  occupancy  and 
construction,  by  an  approved  system  of  open 
sprinklers. 

F-402.17  Fireresistive  roof  covering: 

F-402.I7.1  Classification:  Roof  covering  allowed 
under  this  code  shall  be  classified  as  fire-retardant 
or  ordinary,  according  to  resistance  to  fire  outside, 
as  provided  in  Appendix  F-402. 17.  Fire-retardant 
roof  covering  is  the  more  firereisistive  and  may  be 
used  where  fire-retardant  roofing  is  specified. 
Roof  covering  less  fireresistive  than  ordinary  roof 
covering  shall  not  be  used  on  any  building. 

F-402.17.2  Fire-retardant  roofing:  Fire- 
retardant  roofing  shall  be  any  roof  covering  than 
meets  the  requirements  of  Class  A  or  Class  B 
roofing  under  the  specifications  of  the 
Underwriters'  Laboratories,  Inc.  The  following 
roof  covering  shall  be  assumed  to  meet  the 
requirements  for  fire-retardant  roofing: 

1.  Built-up  roofing  consisting  of  successive 
layers  of  roofing  felt  impregnated  with  asphalt; 
a  final  layer  of  asphalt  in  which,  while  molten, 
is  embedded  a  continuous  layer  of  roofing 
gravel  or  slag. 

2.  Built-up  roofing  consisting  of  successive 
layers  of  roofing  felt  impregnated  with  coal  tar; 
a  final  layer  of  tar  in  which,  while  molten,  is 
embedded  a  continuous  layer  of  roofing  gravel 
or  slag. 

3.  Built-up  roofing  consisting  of  successive 
layers  of  roofing  felt  impregnated  with  asphalt; 
a  final  layer  of  asbestos  roofing  felt 
impregnated  with  asphalt  weighing  not  less 
than  14  pounds  per  100  square  feet,  or  a  final 
layer  of  asphalt-saturated  prepared  roofing 
coated  with  granulated  slate  or  other  similar 
material. 

4.  Built-up  roofing  consisting  of  successive 
layers  of  roofing  felt  impregnated  with  tar  or 


asphalt  and  a  finish  of  burned  clay  floor  tile, 
stone  flagging,  cement  concrete  or  other 
similar  material. 

5.  Sheet  metal  with  locked  and  soldered  joints 
not  less  than  No.  26  gauge  in  thickness. 

6.  Shingles  of  natural  slate. 

7.  Shingles  of  burned  clay  tile. 

8.  Shingles  of  sheet  metal  not  less  than  No.  26 
gauge  in  thickness. 

9.  Shingles  of  asbestos  board  not  less  than  Vs 
inch  thick. 

10.  Shingles  of  asphalt  saturated  felt  surfaced 
with  granulated  slate  or  other  similar  material 
and  carrying  the  Underwriters  Class  "C"  label. 

1 1.  Corrugated  sheet  metal  with  lapped  joints 
not  less  than  No.  26  gauge  in  thickness. 

12.  Corrugated  asbestos  board  not  less  than 
3/I6)  inch  thick. 

F-402. 17.3  Ordinary  roofing:  Ordinary  roofing 
shall  be  of  any  roof  covering  which  meets  the 
requirements  of  Class  C  roofing  under  the 
specifications  of  the  Underwriters'  Laboratories, 
Inc.  The  following  roof  covering  shall  be 
assumed  to  meet  the  requirements  for  ordinary 
roofing: 

1 .  Built-up  roofing  consisting  of  successive 
layers  of  roofing  felt  impregnated  with  asphalt, 
coal  tar  or  other  approved  material,  not  equal 
in  fireresistance  to  a  fire-retardant  roofing. 

2.  Prepared  roofing  consisting  of  felt  or  fabric 
impregnated  or  coated,  or  both,  with  asphalt, 
tar  or  other  approved  material  or  shingles  of 
such  prepared  roofing,  not  equal  in 
fireresistance  to  fire-retardant  roofing. 

3.  Canvas  stretched  tightly  and  coated  with 
paint. 

F-402. 17.4  Means  of  securing:  Built  up  roofing 
shall  be  secured  to  the  roof  deck  in  the  following 
manner: 

1 .  Over  masonry  slab,  the  first  layer  shall  be 
laid  in  molted  asphalt  or  tar  mopped  on  the 
roof  deck,  after  the  deck  is  properly  primed,  or 
by  nailing  a  layer  of  building  paper  to  nailing 
inserts  other  than  wood  placed  in  the  deck. 

2.  Over  wood  decks,  the  built-up  roofing  shall 
be  secured  by  nailing  a  layer  of  building  paper 
to  the  roof  deck  over  which  the  prepared 
roofing  is  to  be  laid  with  the  first  layer  laid  in 
molten  asphalt  or  tar. 

3.  Roofings  other  than  built-up  roofings,  such 
as  shingles,  slates,  and  tile  roll  roofing  shall  be 
well  secured  to  the  deck  by  nailing,  bolting, 
wiring,  or  other  approved  methods. 


736 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


APPENDIX  G 


UNIT  DEAD  LOADS  FOR  DESIGN  PURPOSES 


The  intent  of  780  CMR  Appendix  G  is  to  assist  the  designer  and  building  official  in  establishing  the 
minimum  weights  for  materials  commonly  used  in  building  construction.  Some  material  assemblies  have 
a  range  in  weight.  A  typical  figure  is  indicated,  but  when  there  is  reason  to  suspect  a  considerable 
deviation,  the  actual  weight  should  be  determined. 

Note  on  use  of  780  CMR  Appendix  G  tables:  When  making  calculations  based  on  the  tables  in  780  CMR 
Appendix  G,  the  weights  of  masonry  include  mortar  but  not  plaster.  For  plaster,  add  5  psf  for  each  face 
plastered.  Values  given  represent  averages.  In  some  cases  there  is  a  considerable  range  of  weight  for  the 
same  construction.  For  metric  conversion,  1  psf  equals  4.882  kg/m3. 


Table  G-l 
UNIT  DESIGN  DEAD  LOADS  FOR  CONCRETE  SLABS 


Concrete  slabs 

Pounds  per  square  foot 

Concrete,  reinforced  stone,  per  inch  of  thickness 
Concrete,  reinforced  lightweight  sand,  per  inch  of  thickness 
Concrete,  reinforced,  lightweight,  per  inch  of  thickness 
Concrete,  plain  stone,  per  inch  of  thickness 
Concrete,  plain,  lightweight,  per  inch  of  thickness 

12'/2 

9'/2 

9 
12 
8/2 

Table  G-2 
UNIT  DESIGN  DEAD  LOADS  FOR  RIBBED  SLABS 


Pounds  per  square  foot 

Ribbed  slabs 

Width  of  rib,  in  inches 

Depth  in  inches 

(rib  depth  plus  slab 

thickness)* 

4 

5 

6 

7 

8 

9 

12-inch  clay  tile  fillers 

(normal 

weight  concrete) 

4  plus  2 

49 

51 

52 

54 

- 

- 

6  plus  2 

60 

63 

65 

67 

- 

- 

8  plus  2'/2 

79 

82 

85 

87 

- 

- 

10  plus  3 

96 

100 

103 

106 

- 

. 

12  plus  3 

108 

112 

116 

120 

- 

- 

20-inch  wide 

forms: 

45 

48 

50 

50 

. 

. 

6  plus  2'/2 

51 

54 

57 

60 

- 

. 

8  plus  2'/2 

57 

60 

64 

68 

. 

- 

10plus2'/2 

63 

67 

72 

76 

- 

- 

12  plus  2'/2 

- 

74 

79 

84 

- 

- 

14  plus  2/2 

- 

- 

88 

93 

98 

- 

16  plus  2/2 

- 

- 

- 

111 

118 

- 

20  plus  2/2 

- 

Make  appropriate  allowances  for  tapered  ends. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


737 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  G-2  (continued) 
UNIT  DESIGN  DEAD  LOADS  FOR  RIBBED  SLABS 


Ribbed  slabs 
Depth,,  in  inches 
(rib  depth  plus  slab 
thickness)* 

Pounds  Per  square  foot 
Width  of  rib,  in  inches 

4 

5 

6 

7 

8 

9 

30-inch  wide 
forms: 
6  plus  2'/2 
8  plus  2'/2 
10plus2'/2 
12  plus  2  Vi 
14  plus  2'/2 
16  plus  2  Vi 
20  plus  2Vz 

41 
45 
49 
53 

43 
47 
52 
57 
62 

45 
50 
55 
60 
66 
72 

47 
53 
58 
64 
70 
76 
90 

80 
95 

101 

Two-way  clay  tile  fillers 
(12x12): 
4  plus  2 
6  plus  2 
8  plus  2/2 
10  plus  3 
12  plus  3 

61 
87 
100 
121 
136 

62 
89 
103 
126 
141 

64 
90 
107 
131 
146 

- 

- 

- 

Table  G-3 
UNIT  DESIGN  DEAD  LOADS  FOR  WAFFLE  SLABS 


Waffle  slabs 

Depth,  in  inches 

(Rib  depth  plus  slab  thickness) 

Pounds  per  square  foot 

19x19,  5@24 
6  plus  2Vi 
8  plus  2'/2 
10  plus  2V2 
12  plus  2 1/2 

30x30,  6@36 
8  plus  3 
10  plus  3 
12  plus  3 
14  plus  3 
16  plus  3 
20  plus  3 

66 
78 
84 
101 

73 
83 
95 
106 
114 
135 

738 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  G 

Table  G-4 
UNIT  DESIGN  DEAD  LOADS  FOR  FLOOR  FINISH 


Floor  finish 

Pounds  per  square  foot 

Double  Vs-inch  wood  on  sleepers,  light  concrete  fill 

19 

Double  Vs-inch  wood  on  sleepers,  stone  concrete  fill 

28 

Single  Vs-inch  wood  on  sleepers,  light  concrete  fill 

16 

Single  Vs-inch  wood  on  sleepers,  light  concrete  fill 

25 

3 -inch  wood  block  on  mastic,  no  fill 

10 

1-inch  cement  finish  on  stone  concrete  fill 

32 

1-inch  terrazzo  on  stone  concrete  fill 

32 

Marble  and  mortar  on  stone  concrete  fill 

33 

Linoleum  on  stone  concrete  fill 

32 

Linoleum  on  light  concrete  fill 

22 

l'/i-inch  asphalt  mastic  flooring 

IS 

3-inch  wood  block  on  !/;-inch  mortar  base 

16 

Solid  flat  tile  on  1-inch  mortar  base 

23 

2-inch  asphalt  block,  !4-  mortar 

30 

1-inch  terrazzo,  2-inch  stone  concrete 

32 

Floor  finish  tile  per  inch  depth 

12 

Cement  finish  per  inch  depth 

12 

Gypsum  slabs  per  inch  depth 

4 

Precast  concrete  plank  per  inch 

(as  determined  by  test) 

Hardwood  flooring  per  inch  depth 

4 

Underflooring  per  inch  depth 

3 

Linoleum 

2 

Asphalt  tile 

2 

Brick  pavers  per  inch  thickness 

10 

Table  G-5 
UNIT  DESIGN  DEAD  LOADS  FOR  WATERPROOFLNG 


Waterproofina 

Pounds  per  square  foot 

Five-plv  membrane 

5 

Table  G-6 
UNIT  DESIGN  DEAD  LOADS  FOR  FLOOR  FILL 


Floor  Fill 

Pounds  per  square  foot 

Cinder  fill,  per  inch 

Cinder  concrete  per  inch 

Lightweight  concrete,  per  inch 

Sand,  per  inch 

Stone,  concrete,  per  inch 

5 
9 
7 
8 

12 

Table  G-7 
UNIT  DESIGN  DEAD  LOADS  FOR  WOOD  JOIST  FLOORS 


Wood  joist  floors  (no  plaster) 
-  double  wood  floor  joist  sizes  in  inches 

Pounds  per  square  foot 
12-inch                               16-inch 
spacing                               spacing 

2x6 

6 

5 

2x8 

6 

6 

2x  10 

7 

6 

2x  12 

8 

7 

3x6 

7 

6 

3x8 

8 

7 

3x  10 

9 

8 

3x  12 

11 

9 

3x  14 

12 

10 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


739 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  G-8 
UNIT  DESIGN  DEAD  LOADS  FOR  MATERIALS 

Materials  Pounds  per  cubic  foot 


Cast-stone  masonry  (cement,  stone,  sand)   144 

Cinder  fill 57 

Concrete,  plain: 

Cinder 108 

Expanded  slag  aggregate 100 

Haydite  (burned  clay  aggregate)    90 

Slag 132 

Stone  (including  gravel) 144 

Vermiculite  and  perlite  aggregate, 

nonloadbearing   25-50 

Other  light  aggregate,  loadbearing ,  .  ,  .  .  ■ ,  70-105 

Concrete,  reinforced: 

Cinder Ill 

Slag 138 

Stone  (including  gravel) 150 

Earth  (dry) 96 

Earth  (damp) 108 

Earth  (wet)   120 

Cork  15 

Masonry,  ashler: 

Granite    168 

Limestone,  crystalline    168 

Limestone,  oolitic   135 

Marble 173 

Sandstone  144 

Masonry,  rubble  mortar: 

Granite   153 

Limestone,  crystalline    147 

Limestone,  oolitic   138 

Marble 156 

Sandstone  137 

Rubble  stone  masonry 156 

Terra  cotta,  architectural: 

Voids  filled   120 

Voids  unfilled    72 

Timber,  seasoned: 

Ash,  commercial  white 41 

Cypress,  southern    32 

Fir,  Douglas,  Coast  region 34 

Oak,  commercial  reds  and  whites 45 

Redwood 28 

Spruce,  red,  white,  and  Sitka 28 

Southern  pine,  short  leaf 39 

Southern  pine,  long  leaf 48 

Timber,  hemlock 30 


740  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  G 


Table  G-9 
UNIT  DESIGN  DEAD  LOADS  FOR  ROOF  AND  WALL  COVERINGS 


Roof  and  wall  coverings 

Pounds  per  square  foot 

Asphalt  shingles 

2 

Cement  asbestos  shingles 

4 

Cement  tile 

16 

Clay  tile  (for  mortar  add  10  lb): 

2-inch  book  tile 

12 

3-inch  book  tile 

20 

Roman 

12 

Ludowici 

19 

Composition: 

10 

Three-ply  ready  roofing 

Four-ply  felt  and  gravel 

1 

Five-ply  felt  and  gravel 

5'/2 

Copper  or  tin 

6 

Corrugated  asbestos  cement  roofing 

1 

Fiber  board,  Vi  inch 

1-3 

Formed  sheet  steel 

(see  manufacturer) 

Formed  steel  decking 

2 

Gypsum  sheathing,  '/;  inch 

3/4 

Rigid  insulation,  Vi  inch 

3 

Sheet  lead 

8 

Skylight,  metal  frame,  %-inch  wired  glass 

7 

Slate  3/16-inch 

10 

Slate  Vi  inch 

20 

Spanish  tile 

3 

Wood  sheathing,  per  inch  thickness 

3 

Wood  shinales 

Table  G-10 
UNIT  DESIGN  DEAD  LOADS  FOR  SUSPENDED  CEILINGS 


Suspended  ceilings 

Pounds  per  square  foot 

Cement  on  wood  lath 

12 

Cement  on  metal  lath 

15 

Gypsum  on  wood  or  metal  lath 

10 

Plaster  on  tile  or  concrete 

5 

Suspended  metal  lath  and  gypsum  plaster 

10 

Suspended  metal  lath  and  cement  plaster 

15 

Plaster  on  wood  lath 

8 

2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  G-ll 
UNIT  DESIGN  DEAD  LOADS  FOR  UNPLASTERED  WALLS  AND  PARTITIONS 

Walls  and  partitions  (unplastered)  Pounds  per  square  foot 


inch  clay  brick,  high  absorption 34 

inch  clay  brick,  medium  absorption   39 

inch  clay  brick,  low  absorption    46 

inch  sand/lime  brick 38 

•inch  concrete  brick,  heavy  aggregate 46 

4  -inch  concrete,  light  aggregate   33 

8  7inch  clay  brick,  high  absorption 69 

8  -inch  clay  brick,  medium  absorption   79 

8  -inch  clay  brick,  low  absorption    89 

8  -inch  sand/lime  brick 74 

8  -inch  concrete  brick,  heavy  aggregate 89 

8  -inch  concrete  brick,  light  aggregate 68 

12  -inch  common  brick 120 

12  -inch  pressed  brick 130 

12  -inch  sand/lime  brick   105 

12'/2  -  inch  concrete  brick,  heavy  aggregate 130 

12'/i  -  inch  concrete  brick,  light  aggregate 98 


17 
17 
17 
17 
17 
17 
22 
22 
22 -i 
22  -: 
22- 
22  - 
4-i 
4 


nch  clay  brick,  high  absorption 134 

nch  clay  brick,  medium  absorption 155 

nch  clay  brick,  low  absorption 173 

nch  sand/lime  brick   138 

nch  concrete  brick,  heavy  aggregate    174 

nch  concrete  brick,  light  aggregate 130 

nch  clay  brick,  high  absorption 168 

nch  clay  brick,  medium  absorption 194 

nch  clay  brick,  low  absorption 216 

nch  sand/lime  brick   173 

nch  concrete  brick,  heavy  aggregate    216 

nch  concrete  brick,  light  aggregate 160 

nch  brick,  4  inch  load  bearing  structural  clay  -  tile  backing  60 

nch  brick,  8  inch  loadbearing  structural  clay  -  tile  backing   75 

8  -inch  brick,  4  inch  loadbearing  structural  clay  -  tile  backing   102 

8  -inch  combination  brick  and  concrete  block 72 

12  -inch  combination  brick  and  concrete  block •. 90 

8  -inch  loadbearing  structural  clay  tile   42 

12  -inch  loadbearing  structural  clay  tile 58 

8  -inch  concrete  block,  heavy  aggregate 55 

12  -inch  concrete  block,  heavy  aggregate  85 

8  -inch  concrete  block,  light  aggregate 38 

1 2  -inch  concrete  block,  light  aggregate   55 

2  -inch  furring  tile,  one  side  of  masonry  wall,  -  add  to  above  figures 12 

4  -inch  hollow  concrete  block  -  stone  aggregate 30 

-lightweight 20 

6  -inch  hollow  concrete  block  -  stone  aggregate 42 

-lightweight 30 

8  -inch  hollow  concrete  block   55 

-lightweight 38 

10  -inch  hollow  concrete  block  -  stone  aggregate  62 

-lightweight    46 

12  -inch  hollow  concrete  block  -  stone  aggregate  85 

-lightweight 55 

4  -inch  solid  concrete  block  -  stone  aggregate  45 

-lightweight 34 

6  -solid  concrete  block  -  stone  aggregate 50 

-lightweight 37 


742  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  G 

Table  G-ll  (continued) 
UNIT  DESIGN  DEAD  LOADS  FOR  UNPLASTERED  WALLS  AND  PARTITIONS 

Walls  and  partitions  (unplastered)  Pounds  per  square  foot 


8  -inch  solid  concrete  block  -  stone  aggregate 67 

-lightweight 48 

10  -inch  solid  concrete  block  -  stone  aggregate 84 

-lightweight 52 

12  -inch  concrete  block  -  stone  aggregate 108 

-lightweight 72 

4  -inch  loadbearing  clay  tile 24 

6  -inch  loadbearing  clay  tile 36 

2  -inch  nonloadbearing  clay  tile   1 ! 

3  -inch  nonloadbearing  clay  tile  18 

4  -inch  nonloadbearing  clay  tile  20 

'  6  -inch  nonloadbearing  clay  tile  30 

8  -inch  nonloadbearing  clay  tile   36 

10  -inch  nonloadbearing  clay  tile 40 

4  -inch  nonloadbearing  hollow  concrete  block 20 

6  -inch  nonloadbearing  hollow  concrete  block 30 

8  -inch  nonloadbearing  hollow  concrete  block  40 

T.C.  1  Vi-inch  split  terra  cotta  furring 8 

2  -inch  split  terra  cotta  furring 10 

3  -inch  split  terra  cotta  furring 12 

2  -inch  hollow  gypsum  block 9.5 

3  -inch  hollow  gypsum  block 10 

4  -inch  hollow  gypsum  block 15 

5  -inch  hollow  gypsum  block 18 

6  -inch  hollow  gypsum  block 24 

2  -inch  solid  gypsum  block 12 

3  -inch  solid  gypsum  block 18 

4  -inch  solid  gypsum  block 24 

2  -inch  facing  tile 15 

4  -inch  facing  tile 25 

6  -inch  facing  tile 38 

2  -inch  solid  plaster 20 

4  -inch  solid  plaster 32 

4  -inch  hollow  plaster    22 

Wood  studs  2x4,  unplastered 4 

Wood  studs  2x4,  plastered  one  side 12 

Wood  studs  2x4,  plastered  two  sides 20 

4  -inch  glass  block 18 


Table  G-12 
UNIT  DESIGN  DEAD  LOADS  FOR  LATH  AND  PLASTER  PARTITIONS 

Lath  and  plaster  partitions  Pounds  per  square  foot 


nch  solid  cement  on  metal  lath 25 

nch  solid  gypsum  on  metal  lath    18 

nch  solid  gypsum  on  gypsum  lath 18 

nch  metal  studs,  gypsum  and  metal  lath  both  sides 18 

nch  metal  studs,  gypsum  and  metal  lath  both  sides 19 

nch  metal  studs,  gypsum  and  metal  lath  both  sides 20 

nch  wood  studs,  plaster  and  wood  lath  both  sides    18 

nch  wood  studs,  plaster  and  metal  lath  both  sides 18 

nch  wood  studs,  plaster  and  plaster  boards  both  sides    18 

nch  wood  studs,  unplastered  gypsum  board  both  sides  (dry  wall) 10 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  743 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Table  G-13 
UNIT  DESIGN  DEAD  LOADS  FOR  PLASTER  WORK 

Plaster  Work  Pounds  per  square  foot 


Gypsum  (one  side)  5 

Cement  (one  side) 10 

Gypsum  on  wood  lath 8 

Gypsum  on  metal  lath 8 

Gypsum  on  plaster  board  or  fiber  board   8 

Cement  on  wood  lath 10 

Cement  on  metal  lath   10 


744  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  H 

HISTORIC  STRUCTURES 

Historic  structures  eligible  for  individual  listing  in  the  National  Register  of  Historic  Places,  qualifying  as 
totally  preserved  buildings  (see  780  CMR  3409.0). 

Acton  Faulkner  Homestead,  High  Street 

Agawam      Capt.  Charles  Leonard  House,  Main  Street 

Amesbury    Rocky  Hill  Meetinghouse,  Portsmouth  Road 

Arlington     Fowle-Reed-Wyman  House,  64  Old  Mystic  Street 
Jason  Russell,  7  Jason  Street 
Old  Schwamb  Mill,  17  Mill  Lane 

Barre  Barre  Historical  Society,  Common  Street 

Barnstable    Barnstable  Custom  House,  Route  6A 

Bedford       Job  Lane  House,  295  North  Road 

Beverly        John  Balch  House,  448  Cabot  Street 

Capt.  John  Cabot  House,  1 17  Cabot  Street 
Rev.  John  Hale  House,  39  Hale  Street 

Boston  Gleason  House,  Beacon  Street 

James  Blake  House,  E.  Cottage  Street  (Dor.) 
Clapp  Houses,  105  Boston  Street  (Dor.) 
Loring-Greenough  House,  12  South  Street  (JP) 
Old  State  House,  15  State  Street 
Pierce  House,  24  Oakten  Avenue  (Dor.) 
South  End  Historical  Soc,  532  Mass.  Avenue 
Isabella  Stewart  Gardner  Museum,  280  The  Fenway 

Boxford       Holyoke-French  House,  Elm  Street 

Sylvanius-Thayer  Birthplace,  786  Washington  St 

Brookline     Edward  Devotion  House,  347  Harvard  Street 

Burlington   Francis  Wyman  House,  Francis  Wyman  Road 

Cambridge        Cooper-Frost- Austin  House,  21  Linnaean  St. 

Charlton       Ryder  Tavern,  Stafford  Street 

Chelmsford       Old  Chelmsford  Garrison  House,  105  Garrison  Road 

Chelsea  Gov.  Bellingham-Cary  House,  34  Parker  Street 

Cohasset      Caleb  Lothrop  House,  14  Summer  Street 

Danvers       Fowler  House,  1 66  High  Street 
Rebecca  Nurse  House 
Glen  Magna  House 

Dennis  Josiah  Dennis  Manse,  Nobscuset  Road 

West  Schoolhouse 

2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  745 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Duxbury      Gershom  Bradford  House,  93 1  Tremont  Street 
King  Caesar  House,  King  Caesar  Road 

Gloucester  Beauport,  Eastern  Pt.  Blvd. 

Hammond  Castle,  80  Hesperus  Avenue 

Hadley         Hadley  Farm  Museum,  Russell  Street 

Porter  Phelps  Huntinghouse,  130  River  Drive 

Haverhill  The  Whittier  House,  305  Whittier  Road 

Holyoke  Wisteriahurst,  238  Cabot  Street 

Ipswich  Castle  Hill,  Argilla  Road 

Lee  Merrell  Tavern,  Route  1 02 

Lexington    Buckman  Tavern,  1  Bedford  Street 

Sanderson  House,  3 14  Massachusetts  Ave. 
Monroe  Tavern,  1332  Massachusetts  Ave. 

Lincoln  The  Grange,  Codman  Road 

Lowell  Whistler  House,  Worthen  Street 

Lynnfield  Meetinghouse 

Medford  Peak  House,  347  Main  Street 

Milton         Dr.  Amos  Holbrook  House,  203  Adams  Street 
Daniel  Vose  House,  1370  Canton  Avenue 

Nantucket    Whaling  Museum,  Broad  Street 

Fire  Hose  Cart  House,  8  Gardner  Street 
Greater  Light,  8  Howard  Court 
Old  Gaol,  15  Vestal  Street 
1800  House,  4  Mill  Street 
Old  Mill,  50  Prospect  Street 
Hawden  House,  96  Main  Street 
Nathaniel  Macy  House,  12  Liberty  Street 
Thomas  Macy  Warehouse,  10  Straight  Wharf 
Fair  Street  Museum,  7  Fair  Street 
Quaker  Meeting  House,  7  Fair  Street 

New  Bedford  Benjamin  Rodman  House,  50  North  Second  Street 

New  Salem  Whitaker-Clary  House,  Elm  Street 

Newbury     Tristram  Coffin  House,  1 6  High  Road 

Spencer-Pierce-Little  House,  Little  Lane 

Newton       Jackson  Homestead,  527  Washington  Street 

No.  Andover    Parson  Barnard  House,  Osgood  Street 

No.  Easton  Old  Colony  Railroad  Station,  Oliver  Street 

Norwood     Fred  Holland  Day,  93  Bay  Street 

Orleans  French  Cable  Station,  Cove  Road 

746  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  H 

Oxford  Clara  Barton  Homestead,  Clara  Barton  Road 

Peabody       Gen.  Gideon  Foster  House,  35  Washington  Street 

Pittsfield      Herman  melville  House,  78  Holmes  Road 

Plymouth     Plymouth  Antiquarian  Society,  126  Water  Street 
Harlow  Old  Ft.  House,  19  Sandwich  Street 
Pilgrim  Hall,  75  Court  Street 
Richard  Sparrow  House,  42  Summer  Street 

Quincy  Adams  Academy,  8  Adams 

Quincy  Homestead,  34  Butler  Street 
Josiah  Quincy  House,  20  Muirhead  Street 

Randolph     Johnathan  Belcher  House,  360  N.  Main 

Reading       Parker  Tavern,  103  Washington  Street 

Rockport     Old  Castle,  Castle  Lane 

Salem  House  of  7  Gables,  46-54  Turner  Street 

Essex  Institute,  Essex  Street 
The  Norbone  House 
Witch  Museum 

Crowningshield  Bently,  Essex  Street 
Gardner-Pingree  House,  128  Essex  Street 
Gedney  House,  21  High  Street 
Cox  House,  19  High  Street 

Sandwich  Hoxie  House,  18  Water  Street 
Eldred  House,  4  Water  Street 
Wing  Fort  House,  Spring  Hill  Road 

Sheffield      Col.  John  Ashley  House,  Cooper  Hill  Road 

Shrewsbury      Gen.  Artemas  Ward  Homestead,  Main  Street 

Springfield  Alexander  House,  State  Street 

George  Walter  Vincent  Smith  Art  Museum 

Stockbridge     Naumkeag,  Prospect  Hill 

Swansea      The  Luther  Store,  160  Old  Warren  Road 
The  Martin  House,  22  Stoney  Hill  Road 

Taunton       Old  Colony  Historical  Society,  66  Church  Green 
Parson  Capen  House 

Watertown  Edmund  Fowle  House,  26  Marshall  Street 

Wenham      Claflin-Richard  House,  132  Main 

West  Springfield      Josiah  Day  House,  70  Park  Street 

Weston  Gold  Ball  Tavern,  Old  Post  Road 

Woburn        Loammi  Baldwin  Mansion,  2  Alfred  Street 

Wilmington      Harden  Tavern,  436  Salem  Street 

2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  747 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

Worcester    Timothy  Paine  House,  140  Lincoln  Street 
National  Historic  Landmarks 

Amesbury  John  Greenleaf  Whittier  Home,  86  Friend  Street 

Boston  African  Meeting  House,  8  Smith  Court 

Nichols  House,  55  Mt.  Vernon  Street 
Brook  Farm,  678  Baker  Street  (Rox.) 
Christ  Church,  191  Salem  Street 
Faneuil  Hall,  Dock  Square 
1st  Harrison  Gray  Otis  House,  141  Beacon  Street 
Paul  Revere  House,  19  North  Street 

Concord  Ralph  Waldo  Emerson  House,  28  Cambridge  Tpk. 

The  Old  Manse 
Orchard  House,  299  Lexington  Road 

Dedham  Fairbanks  House 

Deerfield  Old  Deerfield  Village  Historic  District 

Hancock  Hancock  Shaker  Village 

Harvard  Fruitlands,  Prospect  Street 

Hingham  Old  Ship  Meetinghouse,  Main  Street 

Ipswich  John  Whipple  House,  53  S.  Main  Street 

Lexington  Hancock  Clarke  House,  35  Hancock  Street 

Marblehead  Jeremiah  Lee  House,  Washington  Street 

King  Hooper  Mansion,  Hooper  Street 

Marshfield  Daniel  Webster  Law  Office,  Webster  Street 

Medford  Peter  Tufts  House,  350  Riverside  Drive 

Isaac  Royal  House,  1 5  George  Street 

Milton  Capt.  R.  B.  Forbes  House,  215  Adams 

Nantucket  Nantucket  Historic  District 

Jethro  Coffin  House,  Sunset  Hill 

New  Bedford       New  Bedford  Historic  District 

Newburyport        Caleb  Cushing  House,  98  High  Street 

Quincy  John  Adams  Birthplace,  133  Franklin  Street 

John  Quincy  Adams  Birthplace,  141  Franklin  Street 

Salem  Peabody  Museum 

The  Custom  House,  178  Derby  Street 

Saugus  Scotch  Boardman  House,  117  Howard  Street 

Stockbridge  Chesterwood,  Williamsville  Road 

The  Mission  House,  Main  Street 

Waltham  The  Vale,  Lyman  Street 

780  CMR  -  Sixth  Edition 


748 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

APPENDIX  H 

Gore  Place,  52  Gore  Street 

Woburn  Count  Rumford  Birthplace,  90  Elm  Street 

Worcester  American  Antiquarian  Society,  185  Salisbury  Street 


Historic  structures  determined  eligible  for  listing  in  the  National  Register  of  Historic  Places  not  qualifying 
as  totally  preserved  buildings  (see  Partially  preserved  buildings,  780  CMR  3409.0).  Refer  to: 

1 .  National  Register  of  Historic  Places, 

U.S.  Federal  Register,  February  1,  1978,  Part  II. 

2.  National  Register  of  Historic  Place  (additions).  Contact  the  Massachusetts  Historical 
Commission  at  the  Massachusetts  Archives  Building,  220  Morrissey  Boulevard,  Boston,  MA 
02125. 

Historic  districts  listed  in  the  National  Register  of  Historic  Places.  Refer  to: 

1.  National  Register  of  Historic  Places,  U.S.  Federal  Register,  February  1,  1979,  Part  II. 

2.  National  Register  of  Historic  Place  (additions).  Contact  the  Massachusetts  Historical 
Commission  at  the  Massachusetts  Archives  Building,  220  Morrissey  Boulevard,  Boston,  MA 
02125. 

Structures  proposed  for  certification  as  partially  preserved  not  listed  in  the  national  register  of  historic  places. 
Refer  to  Massachusetts  Historical  Commission  Inventory  Forms. 

Contact  the  Massachusetts  Flistorical  Commission  at  the  Massachusetts  Archives  Building,  220 
Morrissey  Boulevard,  Boston,  MA  02125. 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  749 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


750  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  I 


INDEPENDENT  STRUCTURAL  ENGINEER  REVIEW 


1-1  Primary  structure:  For  the  purposes  of  the 
independent  structural  engineering  review,  the 
primary  structure  shall  be  defined  as  the  structural 
frame,  the  load  supporting  parts  of  floors,  roofs,  and 
walls,  and  the  foundations.  Cladding,  cladding 
framing,  stairs,  equipment  supports,  ceiling  supports, 
non-load  bearing  partitions,  and  railings  are 
excluded  from  this  definition  of  primary  structure. 

1-2  Reviewing  engineer:  The  reviewing  engineer 
shall  be  engaged  by  the  owner. 

1-2.1  Qualifications:  The  reviewing  engineer 
shall  be  a  registered  professional  engineer, 
registered  in  Massachusetts,  qualified  by 
experience  and  training  and  who  shall  have  had 
structural  design  experience  with  buildings  or 
structures  similar  to  that  covered  by  the 
application  for  the  building  permit.  The  reviewing 
engineer  shall  be  impartial,  and  shall  be 
independent  of  the  architect  of  record,  structural 
engineer  of  record,  and  contractors  and  suppliers 
who  will  be  involved  in  the  construction  of  the 
structure. 

1-3  Criteria  for  review:  The  reviewing  engineer 
shall  review  the  plans  and  specifications  submitted 
with  the  application  for  the  building  permit  for 
compliance  with  the  structural  and  foundation  design 
provisions  of  the  Code.  The  reviewing  engineer  shall 
perform  the  following  tasks: 

1 .  Check  to  assure  that  the  design  loads  conform 
with  780  CMR; 

2.  Check  that  other  design  criteria,  and  design 
assumptions,  conform  to  780  CMR  and  are  in 
accordance  with  accepted  engineering  practice; 

3.  Review  geotechnical  and  other  engineering 
investigations  that  are  related  to  the  structural 
design  to  determine  if  the  design  properly 
incorporates  the  results  and  recommendations  of 
the  investigations; 

4.  Check  that  the  organization  of  the  structure  is 
conceptually  correct ;  and 

5.  Make  independent  calculations  for  a 
representative  fraction  of  systems,  members,  and 
details  to  check  their  adequacy  The  number  of 
representative  systems,  members,  and  details  shall 
be  sufficient  to  form  a  basis  for  the  reviewer's 
conclusions. 

1-3.1  Structural  Calculations:  The  structural 
calculations  prepared  by  the  structural  engineer  of 
record  shall  be  submitted  to  the  reviewing 
engineer,  upon  the  reviewing  engineer's  request, 
for  his  or  her  reference  only.  The  reviewing 
engineer  shall  not  be  obligated  to  review  or  check 


these  calculations.  If  the  design  criteria  and 
design  assumptions  are  not  shown  on  the 
drawings  or  in  the  computations,  the  structural 
engineer  of  record  shall  provide  a  statement  of 
these  criteria  and  assumptions  for  the  review. 

1-4  Structural  engineer  of  record:  The  structural 
engineer  of  record  shall  retain  sole  responsibility  for 
the  structural  design,  and  the  activities  and  reports  of 
the  reviewing  engineer  shall  not  relieve  the 
structural  engineer  of  record  of  this  responsibility. 

1-5  Report  and  follow-up: 

1.  The  reviewing  engineer  shall  prepare  a  report 
to  the  building  official  stating  whether  or  not  the 
structural  design  shown  on  the  drawings  and  the 
specifications  conform  with  the  structural  and 
foundation  requirements  of  780  CMR.  Said 
report  shall  be  based  on  the  review  as  prescribed 
in  this  appendix  and  shall  include  a  summary  of 
all  deficiencies,  if  any,  which  cannot  be  resolved 
with  the  structural  engineer  of  record. 

2.  The  structural  engineer  of  record  shall  review 
the  report  of  the  reviewing  engineer,  and  notify 
the  building  official  in  writing,  whether  or  not  he 
agrees  with  or  disputes  the  conclusions  and 
recommendations  of  the  reviewing  engineer. 

3.  Unresolved  disputes  between  the  structural 
engineer  of  record  and  the  reviewing  engineer 
shall  be  submitted  by  the  building  official,  the 
owner,  the  structural  engineer  of  record  or  the 
reviewing  engineer  to  the  Structural  Peer  Review 
Advisory  Board  for  resolution. 

4.  Any  changes  to  the  structural  design 
subsequent  to  the  original  submission  of  the  plans 
and  specifications  shall  be  shown  on  revised 
drawings  and  specifications,  submitted  with  an 
amendment  to  the  application  for  permit.  The 
reviewing  engineer  shall  review  the  changes  on 
the  revised  drawings  and  specifications,  and,  if 
the  original  report  does  not  account  for  the 
changes  in  said  drawings  and  specifications,  a 
supplementary  report  relating  to  the  changes  and 
prepared  by  the  reviewing  engineer  shall  be  made 
to  the  building  official. 

1-6  Foundation  permits:  When  the  plans  and 
specifications  are  partially  complete  and  an 
application  is  made  for  a  foundation  permit,  the 
reviewing  engineer  may  review  the  foundation  plans 
and  specifications  on  a  conditional  basis,  provided 
that  the  reviewing  engineer  is  given  sufficient 
documentation  so  that  he  can  perform  Appendix  1-3 
Tasks  1,  2,  3,  and  4  for  the  whole  structure,  and  so 
that  he  can  perform  Appendix  1-3  Task  5  for  that 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


751 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDrNG  CODE 

part  of  the  foundation  covered  by  the  application  for  specifications  as  prescribed  in  Appendix  1-3,  the 

foundation  permit.     The  reviewing  engineer  shall  reviewing  engineer  shall  reperform  Tasks  1,  2,  3, 

prepare  a  report  on  that  part  of  the  foundation  and  4,  as  necessary,  to  include  all  the  revisions  to  the 

covered  by  the  application  for  foundation  permit,  as  design    subsequent    to    the    application    for    the 

prescribed  in  Appendix  1-5,  stating  all  conditions  foundation  permit, 
upon  which  the  report  is  based.  When  the  reviewing 
engineer     reviews     the     completed     plans     and 


752  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  J 


ENERGY  PROVISIONS 

(This  Appendix  is  entirely  unique  to  Massachusetts) 


J1.0  GENERAL 

J1.0  Scope:  Appendix  J  sets  forth  requirements  for 
the  effective  use  of  energy  in  structures. 

Jl.l  Compliance:  Buildings  shall  be  deemed  to  be 
in  compliance  with  Appendix  J  when  built  to  the 
provisions  of  the  following: 

1.  component  design  (Appendix  J8.0,  J9.0  and 
780  CMR  1310  through  1312);  or 

2.  buildings  utilizing  nondepletable  energy 
sources  (780  CMR  13 16.0). 

J1.2  Other  regulations:  Appendix  J  is  not  intended 
to  abridge  any  safety  or  health  provisions  required 
under  any  other  applicable  codes  or  ordinances. 

J1.3  Existing  buildings:  Nothing  in  Appendix  J 
shall  require  the  removal,  alteration,  or 
abandonment,  or  prevent  the  continuance  of  the  use 
and  occupancy  of,  a  lawfully  existing  building, 
unless  provided  otherwise  specifically  by 
Appendix  J. 

J1.4  Exempt  buildings:  The  following  buildings  are 
exempt  from  the  provisions  of  Appendix  J,  with  the 
exception  of  780  CMR  1313.0  dealing  with  lighting 
requirements: 

1.  Buildings  and  structures  or  portions  thereof 
whose  peak  design  rate  of  energy  usage  is  less 
than  one  watt  per  square  foot  or  3.4  Btu/h  per 
square  foot  of  floor  area  for  all  purposes; 

2.  Buildings  which  are  neither  heated  nor  cooled; 

3.  Greenhouses  that  are  free-standing,  or  attached 
to  a  building  and  separated  by  a  wall  having  the 
same  thermal  value  as  an  exterior  wall,  and 
provided  with  a  separate  temperature  control 
system; 

4.  Buildings  with  less  than  100  square  feet  of 
gross  floor  area. 

J2.0  EXISTING  BUILDINGS 

J2.1  Additions  to  existing  buildings:  Additions  to 
existing  buildings  or  structures  shall  be  made 
without  making  the  entire  building  or  structure 
comply.  The  new  construction  shall  conform  to  the 
provisions  of  Appendix  J  as  they  relate  to  the 
addition  only. 

J2.2    Alterations    to    existing    buildings:     See 

780  CMR  34. 


J3.0  PLANS  AND  SPECIFICATIONS 

J3.1  Scope:  780  CMR  J3.0  applies  to  all  buildings. 

J3.2  General:  Plans,  specifications  and  necessary 
computations  shall  be  submitted  to  indicate 
conformance  with  780  CMR  J3.0  and  other 
applicable  sections  of  780  CMR. 

J3.3  Details:  The  data  submitted  shall  show  all 
pertinent  information  and  features  to  be  incorporated 
into  the  building,  including  but  not  limited  to:  the 
exterior  envelope  component  materials;  the  R  values 
of  the  respective  elements;  the  U  values  of  the 
overall  assembly;  calculations  of  overall  Uo  of  the 
walls,  roof/ceiling,  and  floors;  the  size  and  type  of 
apparatus  and  equipment;  controls;  lighting 
requirements;  and  other  pertinent  data  to  indicate 
conformance  to  Appendix  J.  Where  required  by  the 
Board  of  Building  Regulations  and  Standards  or  the 
local  enforcement  official,  such  data  shall  be 
submitted  on  forms  specified. 

J3.4  Calculation  procedures:  Calculation 
procedures  shall  be  in  accordance  with  data  in  the 
ASHRAE  Handbook,  1993  Fundamentals  Volume. 

J4.0  MATERIALS  AND  EQUIPMENT 

J4.1  Identification  Where  practicable,  all  materials 
and  equipment  referenced  in  780  CMR  J3.2  shall  be 
marked  in  order  to  show  compliance  with 
Appendix  J. 

J4.2  Maintenance  information:  Service  systems 
which  require  preventive  maintenance  to  maintain 
efficient  operation  shall  be  furnished  with  complete 
necessary  maintenance  information.  Required 
routine  maintenance  actions,  as  specified  by  the 
manufacturer,  shall  be  stated  clearly  and 
incorporated  on  a  readily  accessible  label  on  the 
equipment.  Such  label  may  be  limited  to  identifying, 
by  title  or  publication  number,  the  operation  and 
maintenance  manual  for  that  particular  model  and 
type  of  product. 

J5.0  DESIGN  CONDITIONS 
J5.1  Scope:  780  CMR  J5.0  applies  to  all  buildings. 

J5.2  General:  The  criteria  of  780  CMR  J5.0 
establish  the  minimum  requirements  for  the  thermal 
design  of  the  exterior  envelope  of  buildings  and  for 
HVAC  systems  and  equipment. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


753 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


J5.3  Thermal  performance:  A  building  that  is 
designed  to  be  both  heated  and  cooled  shall  meet  the 
more  stringent  of  the  heating  or  cooling 
requirements  as  provided  in  Appendix  J  when 
requirements  differ. 

J5.4  Design  parameters:  The  design  parameters 
listed  in  Tables  J5.1  and  J5.2  shall  be  used  for 
calculations  required  under  Appendix  J. 

J5.4.1  Indoor  design  temperature:  Indoor 
design  temperature  shall  be  72  °F  for  heating  and 
78  °F  for  cooling. 


J5.4.2  Design  humidity:  Indoor  design  relative 
humidity  for  heating  shall  not  exceed  30%.  For 
cooling,  the  actual  design  relative  humidity  within 
the  comfort  envelope  as  defined  in  ASHRAE 
Standard  55-92  listed  in  Appendix  A  shall  be 
selected  for  minimum  total  HVAC  system  energy 
use  in  accordance  with  accepted  practice. 

J5.5  Ventilation:  Ventilation  air  shall  conform  to 
the  requirements  specified  in  the  mechanical  code 
listed  in  Appendix  A. 


Table  J5.1 

DESIGN  TEMPERATURES 

HEATING  DEGREE  DAYS  BASE  65 

HDD65 


Outside  Ambient 

Heating  Degrees 

Cooling  Degrees 

Cooling  Degrees 

Heating  Degree 

(°F) 

(°F) 

(°F) 

Days 

Location 

Dry  Bulb 

Wet  Bulb 

Winter 

Summer 

Summer 

Base  65 

Boston 

9 

88 

74 

5634 

Clinton 

2 

87 

73 

6517 

Fall  River 

9 

84 

73 

5774 

Frammgham 

6 

86 

73 

6144 

Gloucester 

5 

86 

74 

- 

Greenfield 

-2 

85 

73 

- 

Lawrence 

0 

87 

74 

6195 

Lowell 

1 

88 

74 

6056 

New  Bedford 

9 

82 

73 

5395 

Pittsfield 

-3 

84 

72 

7578 

Springfield 

0 

87 

73 

5844 

Taunton 

9 

86 

74 

6184 

Worcester 

4 

84 

72 

6989 

Table  J6 
INSULATION  MATERIALS  STANDARDS 


Material 

Standard 

Mineral  Fiber 
blanketfoatt 
loose-fill 

ASTMC665-91 
ASTM  C-764-94 

Mineral  Cellular 
perlite 
vermiculite 
perlite  board 
cellular  glass  block 

ASTMC549-81/R1986 
ASTM  0516-80,011990 
ASTMC728-91 
ASTMC552-91 

Organic  Fiber 

cellulose  fiber  board 
cellulose  loose  fill 

ASTM  C208-94 
16  CFR  Part  1209 

Organic  Cellular 
polystyrene  board 
urethane  board 
flexible  unicellular 

polyurethane  or  polyisocyanurate  with  foil  face 
polvurcthane  or  polvisocvanurate  with  felt  face 

ASTM  C578-92 

ASTMC591-85 

ASTM  C534-94 

F.S.  HH-1-1972-1  (ASTM  C1289) 

F.S.  HH-1-1972-2  (ASTM  C1289) 

754 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  PROVISIONS 


J6.0  BUILDING  INSULATION 
SPECIFICATIONS 

J6.1  General:  Insulating  materials  must  conform  to 
the  Federal  Specifications  (F.S.),  the  American 
Society  for  Testing  Materials  (ASTM)  Test 
Standards,  or  the  Code  of  Federal  Regulations  (CFR) 
as  listed  in  Table  J6. 

J6.2  Moisture  control:  The  design  of  buildings  for 
energy  conservation  shall  not  create  conditions  of 
accelerated  deterioration  from  moisture 
condensation  (additionally,  see  780  CMR  12  for 
attic  and  under-floor  space  ventilation). 

J6.3  Installation: 

J6.3.1  Recessed  light  fixtures:  Only  IC  labeled 
recessed  lights  allowing  direct  contact  with 
insulating  materials  shall  be  used  in  areas 
separating  conditioned  and  unconditioned  spaces. 

Exception:    Wattage    levels    for    which    IC 

fixtures  are  not  available. 

J6.3.2  High  heat  sources:  A  clearance  of  three 
inches  from  any  high  heat  source,  including  but 
not  limited  to  chimneys,  flues  and  vents,  shall  be 
maintained  for  combustible  insulating  materials. 

J6.3.3.0  Foam  plastics: 

J6.3.3.1    General:    Except  where  specifically 

exempted  by  780  CMR  2603  foam  plastics 

shall  have  a  flame  spread  rating  of  not  more 

than  75  and  shall  have  a  smoke  developed 

rating  of  not  more  than  450  when  tested  in 

accordance  with  approved  standards  in  the 

thickness  intended  for  use. 

J6.3.3.2   Urea   formaldehyde   foams:   Urea 

formaldehyde  foams  shall  not  be  used  in  any 

building. 

J6.3.3.3    Liquid  foams:    Liquid  foams  must 

meet  minimum  standards  set  forth  in  HUD 

"Use  of  Materials"  Bulletin  No.  74. 

J6.3.3.4        Specific    requirements:        The 

following  requirements  shall  apply  to  all  uses 

of  foam  plastics  in  or  on  the  walls,  ceilings,  or 

in  attics,  roof  or  floors,  crawl  spaces  or  similar 

areas,    and   may  be  used   in   the   following 

locations: 

1.  Within  the  cavity  of  a  masonry  or 
concrete  wall. 

2.  On  the  room  side  surface  of  walls  or 
ceilings  or  other  surfaces  provided  the  foam 
plastic  is  fully  protected  from  the  interior  of 
the  building  by  a  thermal  barrier  of  Vi  inch 
gypsum  wallboard  having  a  finish  rating  of 
not  less  than  1 5  minutes  or  other  approved 
material  having  an  equivalent  finish  rating. 
Thermal  barriers  shall  be  installed  in  a 
manner  that  they  will  remain  in  place  for  a 
minimum  of  15  minutes  under  the  same  test 
conditions. 


3.  Foam  plastic  trim  covering  not  more 
than  10%  of  the  wall  or  ceiling  area  may  be 
used  provided  such  trim: 

(a)  has  a  density  of  not  less  than  20 
pounds  per  cubic  foot; 

(b)  has  a  maximum  thickness  of  Vi  inch 
and  a  maximum  width  of  four  inches;  and 

(c)  has  a  flame  spread  rating  no  greater 
than  75. 

J6.3.4  Walls:  Batt/blanket  insulation  with  a 
vapor  barrier  attached  shall  be  stapled  to  the  sides 
or  faces  of  wall  studs  at  intervals  of  eight  inches 
on  center  vertically.  Where  batt/blanket 
insulation  is  of  a  "friction  fit"  design  and  a  poly 
vapor  barrier  is  employed,  the  vapor  barrier  shall 
be  affixed  to  the  interior  face  of  the  wall  studs  in 
accordance  with  the  insulation  manufacturer's 
recommendations. 

J6.3.5  Cavities:  All  cavities  between  rough 
framing  and  door  and  window  heads,  jambs,  and 
sills  shall  be  filled  with  insulation  and  covered 
with  a  vapor  barrier  meeting  the  criteria  of 
780  CMR  J7. 

J6.3.6.1  Perimeter  insulation:  Perimeter 
insulation  for  slab  on  grade  construction  in 
buildings  of  Use  Group  R  of  three  stories  or 
less  shall  be  installed  so  that  the  concrete  to 
concrete  contact  between  the  foundation  wall 
and  the  floor  slab  is  broken  and  the  insulation 
extends  downward  the  thickness  of  the  slab 
and  then  extends  four  feet  vertically  down 
from,  or  four  feet  horizontally  beneath,  the 
floor  slab.  Perimeter  insulation  may  be 
installed  in  alternative  locations  if  installed  in 
a  manner  to  thermally  isolate  the  floor  from  the 
exterior. 

J6.3.7  Foundation  wall  insulation: 

1 .  For  interior  foundation  wall  insulation,  the 
entire  gross  wall  area  extending  from  the  top  of 
the  band  joist  to  the  floor  shall  be  insulated  in 
accordance  with  Table  J9. 1 . 

2.  For  exterior  foundation  wall  insulation,  the 
insulation  shall  extend  from  the  top  of  the 
foundation  to  a  minimum  of  eight  feet  below 
grade  or  to  foundation  footing,  whichever  is 
less.  All  exterior  basement  and  foundation  wall 
insulation  shall  be  suitably  protected  so  as  to 
prevent  deterioration  caused  by  ultra-violet 
light  or  insect  damage  in  accordance  with 
manufacturer's  instructions 

J 6.4   Fire  safety   relating   to   insulation:      See 
780  CMR  722  and  2603. 

J6.5:  Labeling 

J6.5.1    Batt   and    blanket   and    rigid    board 

Insulation  of  this  type  shall  be  labeled  according 
to  type,  manufacturer  or  distributor,  R  value  of  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


755 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


insulation  at  the  labeled  thickness,  and  material 
specification  as  listed  in  Table  J6. 

J6.5.2  Blown,  poured,  or  sprayed  on  types: 

Insulation  of  these  types  shall  be  labeled 
according  to  type,  manufacturer,  recommended 
insulation  density,  thickness  and  R  value,  fire 
safety  requirements  and  material  specifications  as 
listed  in  Table  J6. 

J7.0  AIR  INFILTRATION  AND  MOISTURE 
CONTROL 

J7.1  Vapor  barriers:  A  vapor  barrier  of  1.0  perm  or 
less  shall  be  installed  on  the  winter  warm  side  of 
walls,  ceilings  and  floors  enclosing  a  conditioned 
space. 

Exception:  Vapor  barriers  may  be  eliminated 
with  adequate  ventilation  as  defined  in  780  CMR 
12  (See  780  CMR  1210). 

J7.2  Taping:  All  tears  in  the  vapor  barrier  shall  be 
taped  or  sealed. 

J7.3  Air  leakage  for  low-rise  residential 
buildings: 

1 .  The  requirements  of  this  section  shall  apply 
to  those  locations  separating  outdoor  ambient 
conditions  from  interior  spaces  that  are  heated  or 
mechanically  cooled  and  are  not  applicable  to  the 
separation  of  interior  conditioned  spaces  from 
each  other. 

2.  The  following  openings  in  the  exterior 
building  envelope  shall  be  caulked,  gasketed, 
weatherstripped,  foamed  or  otherwise  sealed  to 
limit  infiltration: 

a.  Around  window  and  door  frames,  between 
the  unit  and  the  rough  framing; 

b.  Between  all  exterior  wall  soleplates  and  the 
structural  floor,  using  two  rows  of  caulking  or 
alternate  approved  procedure; 

c.  Over  all  framing  joints  where  floors  over 
conditioned  spaces  intersect  exterior  walls, 
using  a  water  vapor  permeable  infiltration 
barrier  or  alternate  approved  technique; 

d.  Around  openings  for  plumbing,  electricity, 
telephone  and  gas  lines  inwalls,  ceilings  and 
floors; 

e.  At  openings  in  the  ceiling,  such  as  where 
the  ceiling  panels  meet  interior  and  exterior 
walls,  at  exposed  beam  and  masonry  fireplaces; 

f.  At  the  mudsill,  in  addition  to  normal  sill 
sealer  in  conditioned  basements  and 
conditioned  crawispaces;  and, 

g.  At  all  other  openings  in  the  exterior 
building  envelope. 

h.  See  additional  requirements  for  attic  and 
crawl  space  access,  780  CMR  1211. 

3.  Electrical  outlet  plate  gaskets  shall  be 
installed  on  all  receptacle,  switch,  or  other 
electrical  boxes  in  walls  separating  conditioned 
from  unconditioned  space. 


4.  Heating  ducts  shall  be  sealed  at  all  joints  and 
corners  as  specified  in  13 10. 9. 

5.  Interior  openings  between  conditioned  and 
non-conditioned  space  shall  be  sealed  using 
sealant,  closed-cell  gasket  material,  permanent 
tape,  or  another  method  that  limits  infiltration. 

J7.4  Air  leakage  requirements  for  fenestration 
and  doors: 

J7.4.1  Windows  shall  have  an  air  leakage  rate 
of  0.34  cfm  per  foot  of  operable  sash  crack  in 
accordance  with  the  following  standards  as 
applicable: 

ANSI/AANA      101-88,      Aluminum     Prime 
Windows, 

ASTM    D    4099-89,        Specifications    for 
Polyvinylchloride  (PCV)  Prime  Windows, 
ANSI/NWWDA  I.S.   2-87,  Wood  Window 
Units  (Improved  Performance  Rating  Only). 
AAMA  101 V- 1986,  Polyvinyl  Chloride  (PVC) 
Prime  Windows  and  Sliding  Glass  Doors, 
AAMA    1701.2-1985   Prime   Windows    and 
Sliding  Glass  Doors/Manufactured  Housing, 
each  as  listed  in  Appendix  A. 

J7.4.2  Sliding  Doors  shall  meet  one  of  the 
following  standards  for  air  leakage: 

ANSI/AANA  101-88,  Aluminum  Sliding  Glass 

Doors,  or 

ANSI/NWWDA  I.S.  3-88,  Wood  Sliding  Patio 

Doors. 

AAMA  101V-1986,  Polyvinyl  Chloride  (PVC) 

Prime  Windows  and  Sliding  Glass  Doors, 

AAMA    1701.2-1985    Prime   Windows    and 

Sliding  Glass  Doors/Manufactured  Housing, 

each  as  listed  in  Appendix  A. 

J7.4.3  Commercial  entrance  swinging  or 
revolving  doors  shall  limit  air  leakage  to  a  rate  not 
to  exceed  1 .2  cfm  per  square  foot  of  door  area,  at 
standard  test  conditions. 

J7.4.4  Residential  swinging  doors  shall  limit  air 
leakage  to  a  rate  not  to  exceed  0.5  cfm  per  square 
foot  of  door  area,  at  standard  test  conditions. 

J7.4.5  Spaces  that  have  regular  high  volume 
traffic  through  the  building  envelopes  such  as 
retail  store  entrances  and  loading  bays,  shall  be 
designed  accounting  for  the  steady  state  air 
transfer  between  conditioned  and  unconditioned 
or  exterior  space. 

J7.5  VENTILATION 

J7.5.1  Attic  ventilation:  Enclosed  attics,  and 
enclosed  rafter  spaces  formed  where  ceilings  are 
applied  direct  to  the  underside  of  roof  rafters,  shall 
have  cross-ventilation  for  each  separate  space  by 
ventilating  openings  protected  against  the  entrance 


756 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  PROVISIONS 


of  rain  and  snow,  sized  by  the  criteria  in  780  CMR 
1210. 

J7.5.1.1  With  a  ceiling  vapor  barrier  installed: 

Attics  with  a  ceiling  vapor  barrier  must  be 
ventilated  with  screened  openings  of  at  least  one 
square  foot  of  free  vent  area  for  each  300  square 
feet  of  ceiling  area. 

J7.5.1.2  Without  a  ceiling  vapor  barrier 
installed:  Attics  without  a  ceiling  vapor  barrier 
installed  shall  be  ventilated  with  screened 
openings  of  at  least  one  square  foot  of  free  vent 
area  for  each  150  square  feet  of  ceiling  area. 

J7.5.1.3  Eave  vents:  When  eave  vents  are 
installed,  adequate  baffling  shall  be  provided  to 
deflect  the  incoming  air  above  the  surface  of  the 
insulation.  Baffles  shall  be  installed  prior  to 
insulation,  and  shall  be  installed  over  the  exterior 
wall  at  an  angle  to  provide  a  two  inch  minimum 
clearance  under  the  roof  deck  for  upward  flow  of 
ventilation  air  to  the  fixed  vents  in  the  upper 
portion  of  the  attic. 

J7.5.1.4  Ridge  or  gable  vent:  When  eave  vents 
are  installed,  the  ridge  or  gable  vent  must  be  at 
least  three  feet  above  the  level  of  the  eave  vents. 

J7.5.2  Underfloor  space  ventilation: 

J7.5.2.1        With    a    ground    vapor    barrier: 

Underfloor  spaces  with  an  approved  vapor  barrier 
installed  on  the  ground  surface  shall  be  ventilated 
with  screened  openings  of  one  square  foot  of  vent 
area  for  each  1,500  square  feet  of  crawl  space. 
Vents  shall  be  positioned  to  provide  cross 
ventilation.  See  780  CMR  1210. 

J8.0  COMPONENT  DESIGN 
J8.1  Scope:  All  low  rise  residential  buildings  that 
are  heated  or  mechanically  cooled  shall  be 
constructed  so  as  to  provide  the  required  thermal 
performance  of  the  various  components  listed  in 
780  CMR  J8.0,  J9.0  and  780  CMR  1310  through 
1312,  and  to  provide  the  lighting  switching 
requirements  of  780  CMR  1313.2.2.1. 

J8.2  Thermal  Performance:  Information  on 
thermal  properties,  performance  of  building 
envelope  sections  and  components,  and  heat  transfer 
shall  be  obtained  from  laboratory  or  field  test 
measurements,  or  when  information  is  not  available 
from  these  sources,  then  such  information  may  be 
obtained  from  the  ASHRAE  Handbook,  1993  of 
Fundamentals  as  listed  in  Appendix  A. 

When  laboratory  or  field  test  measurements  are 
used,  they  shall  be  conducted  in  accordance  with 
ASTM  standards: 

1.  C-177-85/R1993,  Standard  Test  Method  for 
Steady-State  Thermal  Transmission  Properties  by 
Means  of  the  Guarded  Hot  Plate, 

2.  C-5 1 8-9 1 ,  Steady-State  Thermal  Transmission 
Properties  by  Means  of  the  Heat  Flow  Meter, 


3.  C-236-89/R1993,  Standard  Test  Method  for 
Steady-State  Thermal  Performance  of  Building 
Assemblies  by  Means  of  a  Guarded  Hot  Box,  or 

4.  C-976-90,  Thermal  Performance  of  Building 
Assemblies  by  Means  of  a  Calibrated  Hot  Box, 
each  as  listed  in  Appendix  A. 

To  determine  thermal  conductance  through  window 
assemblies  the  following  ASTM  or  American 
Architectural  Manufacturers  Association  (AAMA) 
standards  shall  be  used. 

1.  AAMA  1503.1-1988,  Test  Method  of  Thermal 
Transmittance  of  Windows,  Doors  and  Glazed 
Wall  Sections, 

2.  ASTM  C-236-89/R1993,  Standard  Test 
Method  for  Steady-State  Thermal  Performance  of 
Building  Assemblies  by  Means  of  Guarded  Hot 
Box,  or 

3.  ASTM  C-976-90,  Thermal  Performance  of 
Building  Assemblies  by  Means  of  a  Calibrated 
Hot  Box,  each  as  listed  in  Appendix  A. 

When  using  any  of  the  three  test  procedures  above, 
a  15  mile  per  hour  wind  shall  be  applied 
perpendicular  to  the  glazing. 

J8.3  Gross  wall  area:  For  the  purposes  of 
Appendix  J,  the  gross  area  of  exterior  walls  consists 
of  all  opaque  wall  areas,  including  foundation  walls, 
areas  between  floor  spandrels,  peripheral  edges  of 
floors,  window  areas  including  sash,  and  door  areas, 
where  such  surfaces  enclose  a  heated  or 
mechanically  cooled  space  including  interstitial 
areas  between  two  such  spaces,  but  excluding  vents, 
grills  and  pipes. 

J8.4  Roof  assembly:  For  the  purpose  of  Appendix  J, 
a  roof  assembly  shall  be  considered  as  all 
components  of  the  roof/ceiling  envelope  through 
which  heat  flows,  thereby  creating  a  building 
transmission  heat  loss  or  gain,  where  such  assembly 
encloses  a  heated  or  mechanically  cooled  space. 

J8.4.1  Gross  roof  area:  The  gross  area  of  a  roof 
assembly  consists  of  the  total  interior  surface  of 
such  assembly,  including  skylights,  exposed  to  the 
heated  or  mechanically  cooled  space. 

J8.4.2  Ceiling  plenums:  Where  air  ceiling 
plenums  are  employed,  the  roof/ceiling  assembly 
shall: 

1.  for  thermal  transmittance  purposes  not 
include  the  ceiling  proper  nor  the  plenum  space 
as  part  of  the  assembly;  and 

2.  for  gross  area  purposes  be  based  upon  the 
interior  face  of  the  upper  plenum  surface. 

J8.5  Swimming  pools:  All  pool  enclosures  shall  be 
designed  in  accordance  with  the  1993  edition  of  the 
ASHRAE  Applications  Handbook,  as  listed  in 
Appendix  A. 

Such   pool   enclosures  shall   have  a  maximum 
overall  (roof/gables/sidewalls)  U  value  of  0.25. 


2/7/97    (Effective  2/28/97) 


780  CMR -Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDrNG  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDrNG  CODE 


J9.0  EXTERIOR  ENVELOPE 

REQUIREMENTS  FOR  LOW  RISE 

RESroENTIAL  BUILDINGS 

J9.1  Criteria  for  low  rise  residential  buildings: 

The  following  requirements  shall  apply  to  all 
buildings  and  structures  or  portions  thereof  in  use 
groups  R-l,  R-2,  R-3,  and  R-4  (hotels,  muiti-family, 
and  one-  and  two-family)  that  are  heated  or 
mechanically  cooled  and  not  more  than  three  stories 
high. 

1.  All  buildings  in  these  use  groups  shall 
conform  to  the  thermal  transmittance  values  in 
Table  J9.1  or  shall  be  designed  to  satisfy  the 
requirements    of  780    CMR   J9.3    or   shall   be 


designed  to  satisfy  the  requirements  of  780  CMR 
1315. 

2.  An  overall  (Jo  value  of  0.167  for  structures 
heated  by  oil,  gas  or  heat  pumps,  or  an  overall  Uo 
of  0.105  for  structures  heated  by  electric 
resistance  may  be  used  for  the  combination  of 
walls,  doors  and  windows  containing  heated  space 
in  lieu  of  the  separate  U  values  listed  for  walls, 
doors  and  windows.  The  overall  Uo  of  0.167  or 
0.105  shall  be  used  when  the  windows  exceed 
15%  of  the  gross  exterior  wall  area. 

3.  For  purposes  of  780  CMR  J9.0  only,  framing 
members  shall  not  be  included  in  the  calculations 
of  R  and  U  values. 


TABLE  J9.1 

MAXIMUM  U  VALUES  AND  MINIMUM  R  VALUES  OF  WALLS, 

ROOF/CEILING,  AND  FLOORS 

FOR  RESIDENTIAL  BUILDINGS  OF  J9.1 


ELEMENT 

DESCRIPTION 

U VALUE 

TOTAL 
R 

VALUE 

NOTES 

Walls 

All  wall  construction  containing 
heated  or  mechanically  cooled  space 

0.08 

12.5 

1 

Electric  resis'.mce  heating 

0.05 

20.0 

1 

Foundation  Walls 
Including  Band  Joist 

Containing  heated  or  mechanically 
cooled  space 

0.08 

12.5 

- 

Containing  unheated  space 

0.08 

12.5 

4 

Roof/Ceiling 
Assembly 

All  roof  construction  containing 
heated  or  mechanically  cooled  space 

0.033 

30.0 

Windows 

All  construction  enclosing  heated  or 
mechanically  cooled  space 

0.65 

1.54 

2 

Electric  resistance  heating 

0.40 

2.50 

6.7 

Doors 

All  construction  enclosing  heated  or 
mechanically  cooled  space 

0.40 

2.50 

- 

Floors 

Floor  sections  over  areas  exposed  to 
outside  air  or  unheated  space 

0.05 

20.0 

3 

Slab  on  grade  beneath  conditioned 
space 

10.0 

5 

Note  1:     These  values  may  be  used  when  the  doors  and  windows  do  not  exceed  15%  of  the  gross  exterior  wall  area. 

When  doors  and  windows  exceed  15%  of  the  gross  wall  area,  see  780  CMR  J9.1,  item  2. 

Note  2:      Double  glazed  primary  windows  or  single  glaze  primary  windows  with  storm  windows  will  satisfy  the 

required  U  value  of  0.65. 

Note  3:     Insulation  may  be  omitted  from  floors  over  unheated  areas  when  foundation  walls  are  provided  with  a  U 

value  of  0.08. 

Note  4:     The  U  value  requirement  of  zero  point  zero  eight  for  foundation  walls  may  be  omitted  when  floors  over 

unheated  spaces  are  provided  with  a  U  value  of  0.05. 

Note  5:    R  value  for  perimeter  insulation  (see  780  CMR  J6.4.6). 

Note  6:    When  doors  and  windows  do  not  exceed  15%  of  the  gross  exterior  wall  area,  this  value  may  be  used.  When 

doors  and  windows  do  not  exceed  10%  of  the  gross  exterior  wall  area,  windows  having  a  U  value  of  0.65  (R  value  of 

1.54)  may  be  used.  When  windows  and  doors  exceed  15%  of  the  gross  exterior  wall  area,  see  780  CMR  J9.1,  item  2. 

Note  7:     Double  glazed  primary  windows  with  storm  windows  or  most  triple  glazed  primary  windows  or  double 

glazed  low  emissivity  primary  windows  will  satisfy  the  required  U  value  of  0.40. 


758 


780  CMR-  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

ENERGY  PROVISIONS 


J9.2  Calculation  of  Uo:  Separate  overall  thermal 
transmittance  values  shall  be  calculated  for  wall 
assemblies,  roof/ceiling  assemblies,  and  floors- 
Equation  1  is  provided  as  an  example  of  the  Uo 
calculation  for  walls. 


Equation  1: 

Overall  wall  Uo  =  Uw  Aw  ±  Ug  Ag  - 


UdAd 


Where: 
Uo  = 


Aw  = 

Uw  = 


Aw  = 
Ug  = 


Ag  = 
Ud: 


Ad: 


average  or  combined  transmittance  of  the 

gross  exterior  wall;  (Btu/hr-ft"-cF). 

gross  exterior  wall  area,  (ft  ). 

thermal  transmittance  of  the  components 

of  the  opaque  wall;  (Btu/hr-ft*-°F). 

opaque  wall  area,  (ft') 

thermal  transmittance  of  the  windows, 

(Btu/hr-ft2-°F). 

window  area;  (ft  ). 

thermal  transmittance  of  the  door  or 

similar  opening;  (Btu/hr-fT-°F). 

door  area;  (ft  ). 


NOTE  Where  Ug  is  determined  by  test,  it  shall 
be  calculated  using  the  procedure  contained  in 
780  CMR  1314.3.2.2  including  calculation  for 
framing,  sash,  edge  effects,  and  all  other  factors 
pertinent  to  the  complete  window  assembly. 


J9.3  Alternates:  The  stated  Uo  (or  U)  value  of  any- 
one assembly,  such  as  roof/ceiling,  wall,  or  floor, 
may  be  increased  and  the  Uo  (or  U)  value  for  other 
components  decreased  provided  that  the  overall  heat 
gain  or  loss  for  the  entire  building  envelope  does  not 
exceed  the  total  resulting  from  conformance  to  the 
stated  Uo  (or  U)  values. 

J10.0  HEATING,  VENTILATING  AND  AIR 
CONDITIONING  (HVAQ  SYSTEMS 

(See  780  CMR  1310.0.) 

J11.0  HEATING,  VENTILATION  AND  ABR 
CONDITIONING  EQUD7MENT 

(See  780  CMR  1311.0.) 

J12.0  ELECTRIC  POWER  DISTRIBUTION 

(See  780  CMR  1312.0.) 

J13.0  LIGHTING  SYSTEMS 

(See  780  CMR  1313.0.) 

J14.0  BUILDING  UTILIZING  SOLAR, 

GEOTHERMIC,  WIND,  OR  OTHER 

NONDEPLETABLE  ENERGY  SOURCES  AS 

ALTERNATIVE  DESIGNS 

(See  780  CMR  1316.0.) 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


759 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


760  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


APPENDIX  K 


FLOOR  PROTECTOR  THERMAL  CONDUCTIVITY  CALCULATIONS 

(Reference  780  CMR  3610.7.1  and  3610.6.7.1.1) 


OVERVIEW 

Floor  protection  requirements  for  heat  producing 
appliances  are  typically  included  as  part  of  the 
tested/listed  installation  criteria  for  such  appliances. 

Such  floor  protection,  listed  as  a  thermal 
conductivity  factor  is  often  developed  utilizing 
NFPA  SUBJECT  1618,  "OUTLINE  OF 
INVESTIGATION  FOR  WALL  PROTECTORS, 
FLOOR  PROTECTORS,  AND  HEARTH 
EXTENSIONS".  (Note  that  an  NFPA  SUBJECT  is 
not  treated  nor  maintained  in  the  same  manner  as  an 
NFPA  STANDARD). 

When  floor  protection  is  developed  utilizing  NFPA 
1618,  the  SUBJECT  methodology  establishes  floor 
protection  relative  to  %  inch  millboard  having  a 
baseline  thermal  conductivity  of: 

k  =  0.84  (Btu)  (inch)  /  (foot2)  (hour)  (°F) 
The  minimum  necessary,  required  thermal 
conductivity  of  an  appliance  is  identified  in  the 
test/listing  report  and  the  required  floor  protection 
thermal  conductivity  may  necessarily  be  lower  than 
k  =  0.S4;  i.e.,  require  more  than  one  or  more  layers 
of  3/8  inch  millboard  or  other  noncombustible 
material  having  a  thermal  conductivity  of  less  than 
k=0.84. 

Note  that  the  lower  the  algebraic  value  of  "k",  the 
lower  the  thermal  conductivity  and  the  less  heat  per 
given  time  that  is  transferred  across  the  floor 
protector. 

Note  that  in  the  following  discussions  it  is  necessary 
to  maintain  consistent  dimensions  -  i.e.;  in  dealing 
with  the  thickness  of  materials,  do  not  mix  feet  with 
inches,  but  rather  keep  all  dimensions  in  inches. 

COMPLIANCE 

If  the  manufacturer  of  the  appliance  specifies  an 
acceptable  material  and  thickness  for  floor 
protection  it  is  necessary,  utilizing  that  specific 
material  with  specific  thermal  conductivity,  k,  to 
meet  or  exceed  the  thickness  specified  in  order  to 
assure  compliance  with  the  listed  floor  protection 
requirements  of  the  appliance. 

ESTABLISHING  EQUIVALENCY 

If  it  is  determined  that  another  material  of  different 
thermal  conductivity  is  desired  to  be  utilized  for 
floor  protection  (i.e.,  perhaps  for  aesthetic  reasons  or 
in  order  to  minimize  the  thickness  of  the  floor 
protector)  and  noting  that  the  thermal  conductivity, 


k,  is  linear  as  a  function  of  thickness  (for  a  given 
single  material)  then: 

k,/t,  =  k2/t2, 

where: 

k  =  thermal  conductivity  in 

(Btu)  (inch)  /  (foot2)  (hour)  (°F)  and 
t  =  thickness  in  inches 

and  therefore  knowing  any  three  of  the  variables  of 
k  and  t  allows  one  to  solve  for  the  remaining 
variable;  i.e.,  : 

Knowing  kT,  t,  and  t2,  one  can  solve  for  k2: 
k2  =(k,)(t2)/(t,) 

Knowing  kb  tj  and  k2,  one  can  solve  for  t2: 
t2  =  (k2)(t,)/(k,) 

COMPOSITE  FLOOR  PROTECTOR 
ASSEMBLIES 

When  an  assembly  consists  of  more  than  one 
material,  the  assembly  is  defined  as  a  composite 
"material". 

When  a  floor  protector  is  constructed  of  more  than 
one  material,  i.e.,  some  form  of  backer  board  with 
decorative  tile  over,  it  is  helpful  to  first  establish  the 
thermal  resistance,  r,  of  each  material  as  thermal 
resistances  may  be  directly  added  together  and  then 
convert  the  resulting  total  R  to  an  equivalent 
thermal  conductivity. 

r  =  (foot2)  (hour)  (°F)/(Btu)  (inch)  and; 

R  =  (r)  (t) 

where  r  is  for  a  particular  material  in  the  composite 
and  t  is  the  thickness  of  that  particular  material. 

Thus  for  the  two-material  example  of  backer  board 
plus  decorative  tile, 

**•  total  —  **■  backer  Board        "•  decorative  tile 

and; 

"■  backer  board    —  V  r    backer  board/  V  '  backer  board/ 

and; 

R1,le=(r„1e)(t.ile) 

RELATIONSHIP  BETWEEN  k  AND  R 

By  definition: 

R  =  (  1/k)  (  t  )  for  each  distinct  material 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


NON-TEXT  PAGE 


762  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  Rl 


CONCRETE  TESTING  LABORATORIES  LICENSING 


780CMRR1.1  ADMINISTRATION 

Rl.1.1  Title  As  authorized  by  St.  1972,  c.  802,  and 
in  accordance  with  780  CMR  123.0,  establishing  the 
Construction  Materials  Safety  Board,780  CMR  Rl 
is  adopted  for  Licensing  of  Concrete  Testing 
Laboratories. 

Rl.1.2  Definitions  Unless  otherwise  expressly 
stated  in  780  CMR,  the  following  terms  shall,  for  the 
purpose  of  780  CMR  Rl,  have  the  meaning 
indicated  in780  CMR  R1.2: 

Accredited  Laboratory:  A  laboratory  which  has 
been  licensed  in  accordance  with  780  CMR  Rl 
bytheBBRS. 

BBRS:  State  Board  of  Building  Regulations  and 
Standards 

Board:  Construction  Materials  Safety  Board 
(CMSB). 

Branch  Laboratories:  A  branch  of  a  Testing 
Laboratory  physically  removed  from  the 
location  of  the  headquarters  or  main  testing 
facility  of  the  Testing  laboratory. 

Laboratories:  Testing  laboratory,  branch 
laboratory,  and  project  laboratory. 

Person:  Individual,  partnership,  corporation, 
trust,  joint  venture,  etc. 

Pre-Qualifying  Agency.  Construction  Materials 
Safety  Board  (CMSB). 

Project  Laboratory:  A  temporary  on-site 
facility  providing  concrete  testing  services  for 
a  specific  project  under  the  direction  of  a 
testing  or  branch  laboratory  licensed  by  the 
Commonwealth  of  Massachusetts. 

Testing  Agency:  National  Bureau  of  Standards 
Cement  and  Concrete  Reference  Laboratory 
(CCRL),  the  Army  Corps  of  Engineers,  or 
other  agency  designated  by  the  BBRS. 

Testing      Laboratory:  A     proprietorship, 

corporation,  partnership  or  agency  which 
conforms  to  the  requirements  of  ASTM  E  329- 
72  as  modified  in  780  CMR  Rl. 

Rl.1.3  Licensing  All  laboratories  defined  by 
780  CMR  Rl.1.2  as  Testing  Laboratories,  Branch 
Laboratories  and  Project  Laboratories  which  are 
engaged  in  the  testing  of  concrete  and  concrete 
materials  for  use  in  buildings  and  structures  subject 
to  control  according  to  the  provisions  of  780  CMR 
116  will  be  licensed  by  the  BBRS  in  accordance 
with  780  CMR  Rl. 


Rl.1.4  Application  for  Licensing  Each  laboratory 
desiring  to  obtain  such  license  shall  make 
application  to  the  BBRS  upon  such  form  and  in  such 
manner  as  the  BBRS  shall  prescribe  and  shall 
furnish  evidence  satisfactory  to  the  BBRS  that  the 
laboratory  equipment  meets  the  requirements  of 
780  CMR  R1.2  and  its  management  personnel  are 
qualified  in  accordance  with  780  CMR  R1.4  and  .5. 
Such  application  shall  also  include  payment  of  the 
licensing  fee  set  forth  in  780  CMR  Rl.  1.8. 

Rl.1.5  Pre-qualifying  Agency  The  BBRS  hereby 
designates  the  Construction  Materials  Safety  Board 
as  its  Pre-Qualifying  Agency,  provided,  however, 
that  the  BBRS  may  revoke  such  designation  at  any 
time,  and  may  designate  any  other  agency  or 
agencies  which  it  deems  qualified,  from  time  to 
time,  to  act  as  its  Pre-Qualifying  Agency.  The  Pre- 
Qualifying  Agency  shall  examine,  or  cause  to  be 
examined,  the  evaluation  performed  by  the  Testing 
Agency  and  the  personnel  on  each  Concrete  Testing 
Laboratory  application  and  make  its 
recommendation  to  the  BBRS  regarding  such 
license. 

Rl.1.6  Testing  Agency  The  BBRS  hereby 
designates  the  Cement  and  Concrete  Reference 
Laboratory  of  the  National  Bureau  of  Standards  and 
the  Army  Corps  of  Engineers  as  the  agencies  to 
examine  and  evaluate  all  laboratories  desiring  to  be 
licensed  in  the  practice  of  concrete  testing,  provided, 
however,  that  the  BBRS  may  revoke  such 
designation  at  any  time,  and  may  designate  any  other 
agency  or  agencies  which  it  deems  qualified,  from 
time  to  time,  to  act  as  its  Testing  Agency. 

Rl.1.7  Notification  of  Testing  and  Testing 
Results  The  Testing  Agency  shall  notify  the 
applicant  of  the  date  for  evaluation.  The  BBRS  shall 
be  informed  by  the  Testing  Agency/Pre-Qualifying 
Agency  of  the  evaluation  results  and 
recommendations. 

Rl.1.8  Licensing  Fee  The  fee  for  licensing  shall  be 
$150.00  per  annum  or  in  accordance  with  the  fee 
schedule  established  by  the  BBRS  from  time  to  time. 

Rl.1.9  Number  and  Classification  Each 
laboratory  so  licensed  by  the  BBRS  shall  be  issued 
a  number  and  classification. 

Rl.1.10  Renewals  Commencing  January  1,  1978, 
all  licenses  issued  shall  expire  on  December  31  of 
the  year  issued.  Within  30  days  before  the 
expiration     date     of     any     such     license,     the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Administrator  of  the  BBRS  shall  forward  to  each 
laboratory  so  licensed  an  application  form  for 
renewal.  Said  renewals  shall  be  returned  to  the 
BBRS  by  December  31.  The  said  Executive 
Director,  upon  receipt  of  the  completed  form  and 
fee,  shall  renew  the  license  for  a  period  of  one  year 
or  notify  such  applicant  of  the  BBRS's  refusal  with 
reasons  thereof. 

Rl.1.11  Penalties  Any  such  person  and/or 
laboratory  who  fails  to  comply  with  the 
requirements  of  780  CMR  Rl .  1  or  who  files  a  false 
report  shall  be  subject  to  the  penalties  and  actions  as 
prescribed  in  780  CMR  118. 

780  CMR  R1.2  LABORATORY  LICENSING 

REQUIREMENTS 
Rl.2.1  ASTM  Testing  Requirements  Except  as 
modified  in  780  CMR  Rl,  all  testing  laboratories 
including  branch  laboratories  shall  conform  to 
Sections  5  and  6  of  the  ASTM  E  329-72  standard 
requirements  for  testing  of  concrete  and  its 
constituent  materials. 

Exception:  The  following  sections  of  ASTM  E 
329-72  shall  not  apply: 

Sections  2.2;  2.3;  2.7;  3.2.7;  3.3;  3.4  C360  of 

6.2;  7;  8;  9  and  10. 

Rl.2.2  ASTM  Equipment  and  Personnel 
Requirements:  All  laboratories  subject  to 
780  CMR  R1.0  shall  be  approved  and  licensed  in 
accordance  with  the  ASTM  E  329-72  standard  for 
the  performance  of  those  functions  recommended  in 
standard  ASTM  E  329-72,  for  equipment  and 
personnel,  as  modified  in  780  CMR  Rl . 

780CMRRL3  PRE-QUALJFICATION 
REQUIREMENTS  FOR  LABORATORIES 

Rl.3.1   Evaluation: 

a.  Testing  and  branch  laboratories  subject  to 
780  CMR  Rl  shall  be  examined  and  evaluated, 
upon  notification  from  the  BBRS,  by  a  testing 
agency  designated  by  the  BBRS.  The  interval 
between  such  examination  and  evaluation  shall 
not  exceed  three  years. 

b.  Project  laboratory  equipment  which  is  used  in 
the  testing  of  concrete  materials  for  use  in 
buildings  and  structures  subject  to  the  provisions 
of  780  CMR  shall  conform  to  the  requirements  of 
ASTM  E  329  as  modified  by  780  CMR  Rl  .2. 

c.  Reports  of  evaluations  by  the  testing  agency 
shall  be  filed  with  the  BBRS  within  ten  days  of 
receipt  of  the  report  by  the  laboratory,  unless  a 
waiver  is  granted  by  the  laboratory  to  have  the 
report  sent  directly  to  the  BBRS  by  the  testing 
agency. 

d.  Laboratory  deficiencies  cited  in  the  report  of 
the  testing  agency  shall  be  corrected  within  30 
days  of  the  date  of  issue  of  the  report  and  shall  be 


so  certified  by  an  affidavit  submitted  by  the 
laboratory  on  a  form  supplied  by  the  BBRS. 

Rl.3.2  Review  of  Deficiencies:  Laboratories  which 
fail  to  meet  the  requirements  of  780  CMR  Rl.3.1 
items  c.  and  d.  shall  be  subject  to  review  and 
revocation  of  their  license  by  the  BBRS. 

RI.3.3  Testing  Machines:  Compression  testing 
machines  used  for  testing  materials  subject  to 
780  CMR  Rl  shall  be  calibrated  and  verified,  with 
equipment  traceable  to  the  National  Bureau  of 
Standards,  at  least  annually  or  as  required  by  the 
BBRS,  and  the  results  submitted  to  the  BBRS. 

780CMRR1.4  PERSONNEL 

The  management  and  supervision  of  each  laboratory 
subject  to  780  CMR  R1.4  shall  be  in  accordance 
with  the  following  requirements: 

Rl.4.1  Required:  Each  accredited  licensed 
Concrete  Testing  Laboratory  must  have  an 
individual  approved  by  the  BBRS  in  each  of  three 
distinctly  different  categories:  Director  of  Testing 
Services,  Supervisory  Laboratory  Technician  and 
Supervisory  Field  Technician.  An  individual  may 
fill  more  than  one  position  at  the  particular 
laboratory  if  he  meets  all  the  qualifications  for  each 
position,  but  he  may  not  fill  positions  concurrently 
at  a  separate  (branch  or  project)  laboratory.  The 
project  laboratory  must  have  a  full-time  resident 
supervisory  laboratory  technician  qualified  in 
accordance  with  780  CMR  Rl  .4. 

Rl.4.2  Filing  of  Qualifications:  Each  individual 
being  certified  for  a  position  must  submit  their 
credentials  and  qualifications  under  penalty  of 
perjury  with  their  signature  notarized.  Individuals 
applying  for  certification  in  more  than  one  category 
must  file  separate  applications  for  each  position  as 
described  in  780  CMR  R1.5.  Application  for 
certification  shall  be  filed  within  30  days  of 
employment  for  such  duties.  It  is  the  responsibility 
of  the  Director  of  Testing  Services  to  notify  the 
BBRS  within  seven  days  of  any  vacancy  of  any 
position.  Any  vacant  position  shall  be  filled  within 
30  days. 

780CMRRL5  QUALIFICATIONS 
Rl.5.1  Qualifications  for  Director  of  Testing 
Services:  The  testing  services  of  each  laboratory 
(main,  branch  or  project)  shall  be  under  the  direction 
of  a  Director  of  Testing  Services  who  shall  be  a  full- 
time  resident  employee  of  that  laboratory  and  shall 
be  qualified  in  accordance  with  any  one  of  the 
following  three  sets  of  requirements: 

a.  He  or  she  shall  be  a  Professional  Engineer, 
registered  in  the  Commonwealth  of  Massachusetts 
with  a  least  five  years  of  experience  in  responsible 
charge  of  work  related  to  Structural  Engineering, 
Construction      Engineering      or      Construction 


764 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONCRETE  TESTING  LABORATORIES  LICENSING  RULES  AND  REGULATIONS 


Materials  Testing.  He  shall  be  subject  to 
demonstrate  his  ability  to  interpret  the  results  of 
tests  of  concrete  and  concrete  aggregates  as  stated 
in  ASTM  E  329-72;  or, 

b.  He  or  she  shall  have  a  Bachelor's  Degree  in 
Engineering  from  an  accredited  institution  and  an 
additional  total  of  three  years'  experience 
performing  tests  on  concrete  and  concrete 
materials  which  shall  include  two  years  as  a 
laboratory  technician  or  supervisor.  He  shall  be 
subject  to  demonstrate  his  ability  to  interpret  the 
results  of  tests  of  concrete  and  concrete 
aggregates  as  stated  in  ASTM  E  329-72;  or 

c.  He  or  she  shall  have  at  least  eight  years' 
experience  including  five  years'  experience  as  a 
laboratory  technician  or  supervisor  and  shall  be 
subject  to  demonstrate  his  ability  to  interpret  the 
results  of  tests  of  concrete  and  concrete 
aggregates  as  stated  in  ASTM  E  329-72. 

Rl.5.2  Qualifications      for      Supervisory 

Laboratory  Technician:  A  Supervisory  Laboratory 
Technician  shall  have  at  least  five  years'  experience 
performing  tests  on  construction  materials  including 
concrete  and  concrete  aggregates.  He  or  she  shall  be 
subject  to  demonstrate  his  ability  to  perform 
correctly  tests  of  concrete  and  aggregates  as  stated  in 
ASTM  E  329-72.  "Class  A"  accreditation  by  the 
Pre-Qualifying  Agency  shall  be  required  as 
qualification  for  concrete  only.  (See  780  CMR  R2 
Concrete  Testing  Personnel  Licensing  Rules  and 
Regulations.) 

Rl.5.3  Qualifications  for  Supervisory  Field 
Technician:  A  Supervisory  Field  Technician  shall 
have  at  least  five  years'  experience  performing  tests 
on  construction  materials  including  concrete.  He  or 
she  shall  be  subject  to  demonstrate  either  by  oral  or 
written  examination,  or  both,  his  ability  to  perform 
correctly  the  tests  of  concrete  as  stated  in  ASTM  E 
329-72.  "Class  A"  accreditation  by  the  Pre- 
Qualifying  Agency  shall  be  required  as  qualification 
for  concrete  only.  (See  780  CMR  R2  Concrete 
Testing  Personnel  Licensing  Rules  and  Regulations.) 

780CMRR1.6  PRO JECT  AFFIDAVIT 

In  accordance  with  780  CMR  110.12,  those 
structures  subject  to  control  as  required  in  780  CMR 
1 16,  affidavits  must  be  submitted  with  the  building 
permit  application  that  the  individuals  and  testing 
laboratories  responsible  for  carrying  out  the  duties  of 
780  CMR  1 16  have  been  licensed  and  registered  by 
the  BBRS. 

Rl.6.1  Affidavit:  Form  Number  BBRS-L-303-76, 
as  furnished  by  the  licensed  laboratory  (sample 
submitted  to  each  laboratory)  shall  be  used  by  the 
licensed  laboratory  for  each  building  project. 

Rl.6.2  Notice  of  Termination:  The  building 
official   shall   receive   written   notification   of  the 


termination  of  laboratory  functions  certifying  that 
the  owner  has  also  been  so  notified.  Such 
termination  shall  be  effective  no  earlier  than  three 
working  days  from  the  notification  received  by  the 
building  official. 

Rl.6.3  Successor  Laboratory:  If  concrete  testing 
is  to  be  continued  for  the  said  project  by  a  successor 
laboratory,  such  notice  shall  be  given  to  the  building 
official  and  a  new  project  affidavit  shall  be  filed 
with  the  building  official. 

780CMRR1.7  REVOCATION  AND 
SUSPENSION  PROCEDURES 

Rl.7.1  Revocation  and  Suspension:  The  BBRS  on 
its  own  initiative  or  upon  the  recommendation  of  the 
Construction  Materials  Safety  Board  may  suspend  or 
revoke  the  license  of  any  Testing  Laboratory  or 
Project  Laboratory  found  to  be  in  noncompliance 
with  780  CMR  Rl,  780  CMR,  or  the  Standards  of 
good  practice.  Notice  of  suspension  or  revocation  of 
such  license  shall  be  in  writing  with  the  reasons  for 
suspension  or  revocation  clearly  set  forth  therein, 
and  served  in  accordance  with  780  CMR  1 18.6. 

Rl.7.2  Notice  and  Conference:  Prior  to 
suspension,  revocation,  or  refusal  to  renew  the 
license  of  an  accredited  laboratory,  written  notice  of 
such  intent  shall  be  served  by  the  Construction 
Materials  Safety  Board  of  BBRS  in  accordance  with 
780  CMR  1 18.6.  Within  ten  calendar  days  of  receipt 
of  such  notice,  the  affected  accredited  laboratory 
may  request  a  conference  before  a  three  member 
panel  designated  by  the  Chairman  of  the 
Construction  Materials  Safety  Board,  who  will  hear 
facts  and  make  their  recommendations  to  the 
Construction  Materials  Safety  Board. 

Rl.7.3  Effect  of:  Upon  suspension  or  revocation  of 
the  license,  the  accredited  laboratory  shall 
immediately  cease  engaging  in  the  testing  of 
concrete  and  concrete  materials  for  use  in  buildings 
and  structures  which  are  subject  to  the  provision  of 
780  CMR  and  no  action  brought  before  the  Board  of 
Appeals  as  specified  in  780  CMR  R  1.8.1  or  in  any 
court  of  competent  jurisdiction  shall  stay  the  said 
suspension  or  revocation  unless  said  Board  of 
Appeals  or  court  shall  issue  an  order  for  a  stay  of  the 
BBRS's  suspension  or  revocation. 

780CMRR1.8  APPEALS 

Rl.8.1      Building  Code  Appeals  Board:      Any 

laboratory  or  individual  aggrieved  by  the  suspension 
or  revocation  of  their  license  or  by  an  interpretation, 
order,  requirement,  direction  or  failure  to  act  under 
780  CMR  Rl  may  appeal  to  the  State  Building  Code 
Appeals  Board  as  provided  in  780  CMR  122; 
however,  entry  of  an  appeal  from  the  BBRS's  order 
of  revocation  or  suspension  shall  not  stay  such 
revocation  or  suspension  unless  so  ordered  by  the 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


765 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

State  Building  Code  Appeals  Board  in  a  preliminary       122.3.2    dealing   with    procedure   required    for 
hearing  conducted  expressly  for  the  purpose  of  a       hearing  on  such  stay, 
stay  in  accordance  with  that  part  of  780  CMR 


766  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  R2 


CONCRETE  TESTING  PERSONNEL  LICENSING 


780  OVER  R2.1  ADMINISTRATION 

R2.1.1  Title:  As  authorized  by  St.  1972,  c.  802, 
and  in  accordance  with  780  CMR  123.0  establishing 
the  Construction  Materials  Safety  Board,  780  CMR 
R2  is  adopted  for  Concrete  Testing  Personnel. 

R2.1.2  Definitions:  Unless  otherwise  expressly 
stated  in  780  CMR  the  following  terms,  for  the 
purpose  of  780  CMR  R2,  shall  have  the  meaning 
indicated  in  780  CMR  R2. 1 .2. 

BBRS:  State  Board  of  Building  Regulations  and 
Standards 

Board:  Construction  Materials  Safety  Board 
(CMSB) 

Concrete  Testing  Personnel:  A  person  issued  a 
Class  "A"  license  by  the  BBRS  authorizing 
such  person  to  test/inspect  concrete. 

Field  Concrete  Technician:  A  person  issued  a 
Class  "A"  license  by  the  BBRS  to  test  concrete 
in  the  field. 

Pre-Qualifying  Agency:  Construction  Materials 
Safety  Board  (CMSB) 

Testing  Agency:  Massachusetts  Construction 
Industry  Board  (MCIB) 

R2.1.3  Licensing:  All  Concrete  Personnel  engaged 
in  the  testing/inspection  of  concrete  for  use  in 
buildings  and  structures  subject  to  control  according 
to  the  provisions  of  780  CMR  116.0  shall  be 
licensed  by  the  BBRS  in  accordance  with  780  CMR 
R2. 

R2.1.4  Application  for  Licensing:  Each  person 
desiring  to  obtain  such  license  shall  make 
application  to  the  BBRS  upon  such  form  and  in  such 
manner  as  the  BBRS  shall  prescribe  and  shall 
furnish  evidence  satisfactory  to  the  BBRS  that  he  is 
qualified  to  be  licensed  in  accordance  with 
780  CMR  R2. 

R2.1.5  Pre-qualifying  Agency  The  BBRS  hereby 
designates  the  Construction  Materials  Safety  Board 
as  its  Pre-Qualifying  Agency,  provided  however, 
that  the  BBRS  may  revoke  such  designation  at  any 
time  and  may  designate  any  other  agency  or 
agencies  which  it  deems  qualified,  from  time  to 
time,  to  act  as  its  Pre-Qualifying  Agency.  The  Pre- 
Qualification  Agency  shall  examine,  or  cause  to  be 
examined,  the  examination  results  and  evaluation 
performed  by  the  Testing  Agency  on  each  Concrete 
Testing    Personnel     Application     and     make    its 


recommendation  to  the  BBRS  regarding  such 
license. 

R2.1.6      Testing   Agency:      The  BBRS   hereby 

designates  the  Massachusetts  Construction  Industry 
Board  (MCIB)  as  the  agency  to  examine  and 
evaluate  all  persons  desiring  to  be  licensed  in  the 
practice  of  concrete  testing,  provided,  however,  that 
the  BBRS  may  revoke  such  designation  at  any  time, 
and  may  designate  any  other  agency  or  agencies 
which  it  deems  qualified,  from  time  to  time,  to  act  as 
its  Testing  Agency.  The  Testing  Agency  shall 
submit  all  examination  results  and  evaluation  on 
each  Concrete  Testing  Application  and  make  its 
recommendations  to  the  Pre-Qualification  Agency 
regarding  such  license. 

R2.1.7  Examination:  Accompanied  by  the 
application,  there  shall  be  paid  to  the  Testing 
Agency  an  initial  examination  fee  to  cover  the  cost 
of  such  testing.  The  Testing  Agency  may  also  assess 
fees  for  partial  or  complete  retesting.  The  Testing 
Agency  is  authorized  to  require  the  applicant  to 
provide  all  required  test  equipment. 

R2.1.8  Notification  of  Examination  and 
Examination  Results:  The  Testing  Agency  shall 
notify  the  applicant  of  the  time  and  place  for  the 
examination.  The  BBRS  shall  be  informed  by  the 
Testing  Agency/Pre-Qualifying  Agency  of  the 
examination  results,  evaluation  and 

recommendations.  Within  14  days  therefrom,  the 
BBRS  shall  notify  the  applicant  of  its  decision.  If 
the  applicant  fails  fully  or  partially,  he  may  request 
of  the  Testing  Agency  a  retesting.  If  the  applicant  is 
notified  by  the  BBRS  that  he  has  met  all  the 
requirements  herein  established,  he  shall  submit  to 
the  said  BBRS,  the  license  fee  in  accordance  with 
780  CMR  2.1.9,  and  his  1%"  x  1V4",  full  face,  black 
and  white  or  color  photograph. 

R2.1.9  Licensing  Fee:  The  fee  for  licensing  shall 
be  $50  in  accordance  with  the  fee  schedule 
established  by  the  BBRS  Concrete  Testing 
Personnel  employed  for  that  purpose  by  a 
municipality  or  county  or  the  federal  government,  or 
the  Commonwealth  or  any  department,  commission, 
agency  or  authority  of,  or  created  by,  the 
Commonwealth,  shall  be  exempt  from  this  fee. 

R2.1.10  Number  and  Classification:  Each  person 
so  licensed  by  the  BBRS  shall  be  issued  a  number 
and  classification. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


R2.1.11  Renewals:  Licenses  shall  be  valid  for  two 
years  and  the  license  renewal  fee  shall  be  $50 
dollars.  Within  30  days  before  the  expiration  date  of 
any  such  license,  the  Administrator  of  the  BBRS 
shall  forward  to  each  person  so  licensed  an 
application     form     for     renewal.  The     said 

Administrator,  upon  receipt  of  the  completed  form 
and  fee,  shall  renew  the  license  for  a  period  of  two 
years  or  notify  such  applicant  of  the  BBRS's  refusal 
with  the  reasons  thereof.  An  applicant  shall  submit 
a  renewal  application  with  fees  within  one  year  of 
the  expiration  date  of  the  license.  Failure  to  submit 
a  renewal  application  within  this  time  period  shall  be 
cause  for  examination  or  re-examination.  Upon 
successful  completion  of  a  Class  A  Technician's 
examination  said  applicant  is  eligible  to  be  licensed 
upon  submittal  of  an  application  and  fee.  Said 
application  and  fee  shall  be  submitted  within  one 
year  of  the  date  of  the  examination.  Failure  to 
acquire  a  license  within  this  time  period  shall  be 
cause  for  examination  or  re-examination. 

780CMRR2.2  PRE-QUALIFICATION 

REQUIREMENTS  FOR  PERSONS 

DESIROUS  OF  BEING  LICENSED  FOR 

CONCRETE  TESTING 

R2.2.1  Evaluation:  Field  Concrete  Technicians, 
subject  to  780  CMR  R2,  shall  be  examined  and 
evaluated  by  the  Massachusetts  Construction 
Industry  Board  to  determine  the  applicant's 
knowledge  and  ability  to  perform  the  following 
ASTM  Standard  Test  Procedures: 

a.  ASTMC172:  Sampling  Fresh  Concrete 

b.  ASTM  CHS:  Test  for  Slump 

c.  ASTM  C3 1 :     Making     and     Curing     Test 

Specimens  in  the  Field 

d.  ASTMC231:  Test  for  Air  Content  -  Pressure 

Method 

e.  ASTM  CI 73:  Test     for     Air     Content     - 

Volumetric  Method 

f.  ASTM  CI 38:   Test  for  Weight  per  Cubic  Foot 

(Density) 

g.  ASTM  CI 92:  Storage  and  Transportation  of 

Test  Cylinders 
The  applicant's  performance  of  these  tests  is  to  be 
observed  and  evaluated  by  two  qualified  jurors 
designated  by  the  Testing  Agency  (MCEB),  using 
detailed  data  sheets.  The  said  jurors'  evaluations  are 
appraised  by  the  Certification  Committee  of  the 
Testing  Agency  and  reappraised  by  the  Board  of 
Trustees  of  the  said  Testing  Agency.  Three 
categories  of  performance  are  to  be  used  in  the  final 
evaluation  process  as  follows: 

1.  PASS:  The  applicant  has  satisfactorily 

completed  the  examination. 

2.  PARTIAL:  The  applicant  has  failed  one  of 

the  five  performance  tests  and 
must  take  a  partial  re-test. 

3.  FAIL:  The  applicant  has  failed  two  or 

more   of  the   five   performance 


tests  and  must  take  a  complete  re- 
test. 

780CMRR2-3  REVOCATION  AND 
SUSPENSION  PROCEDURES 

R2.3.1  Revocation  and  Suspension:  The  BBRS  on 
its  own  initiative  or  upon  the  recommendation  of  the 
Construction  Materials  Safety  Board  or  the 
Massachusetts  Construction  Industry  Board,  may 
suspend  or  revoke  the  licenses  of  any  one  so 
engaged  in  the  practice  of  Concrete  Testing  found  to 
be  in  noncompliance  with  780  CMR  R2,  780  CMR 
or  the  standards  of  good  practice.  Notice  of 
suspension  or  revocation  of  such  license  shall  be  in 
writing  with  the  reasons  for  suspension  or  revocation 
clearly  set  forth  therein,  and  served  in  accordance 
with  780  CMR  118.6. 

R2.3.2  Notice  of  Conference.  Prior  to  suspension, 
revocation  or  refusal  to  renew  such  license,  written 
notice  of  such  intent  shall  be  served  by  the  Pre- 
Qualifying  Agency  or  BBRS  in  accordance  with 
780  CMR  1 18.6.  Within  ten  calendar  days  of  receipt 
of  such  notice,  the  affected  licensee  may  request  a 
hearing  before  a  three  member  panel  designated  by 
the  chairman  of  the  said  agency,  who  will  hear  facts 
and  make  recommendations  to  the  Pre-Qualifying 
Agency. 

R2.3.3  Effect  of  Suspension  or  Revocation  of 
License:  Upon  suspension  or  revocation  of  the 
license,  the  licensee  shall  immediately  cease 
engaging  in  the  testing  of  concrete  and  concrete 
materials  for  use  in  buildings  and  structures  which 
are  subject  to  the  provision  of  780  CMR  and  no 
action  brought  before  the  State  Building  Code 
Appeals  Board  as  specified  in  780  CMR  R2.4. 1  or  in 
any  court  of  competent  jurisdiction  shall  stay  the 
said  suspension  or  revocation  unless  said  Appeals 
Board  or  court  shall  issue  an  order  for  a  stay  of  the 
BBRS's  suspension  or  revocation. 

780CMRR2.4  APPEALS 
R2.4.1  Massachusetts  State  Building  Code 
Appeals  Board  Any  one  engaged  in  the  practice  of 
Concrete  Testing  aggrieved  by  the  suspension  or 
revocation  of  their  license  or  by  an  interpretation, 
order,  requirement,  direction  or  failure  to  act  under 
780  CMR  R2  may  appeal  to  the  State  Building  Code 
Appeals  Board  as  provided  in  780  CMR  122.0; 
however,  entry  of  an  appeal  from  the  BBRS's  order 
of  revocation  or  suspension  shall  not  stay  such 
revocation  or  suspension  unless  so  ordered  by  the 
said  Appeals  Board  in  a  preliminary  hearing 
conducted  expressly  for  the  purpose  of  a  stay  in 
accordance  with  that  part  of  780  CMR  122.3.2 
dealing  with  the  procedure  required  for  a  hearing  on 
such  stay. 


768 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  R3 


MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS 
AND  MOBILE  HOMES 


PART  I  GENERAL 


780  CMR  R3.1  ADMINISTRATION 

R3.1.1Title:  The  BBRS,  Massachusetts  Board  of 
Fire  Prevention  Regulations  (Massachusetts  Board 
of  State  Examiners  of  Electricians),  and  the 
Massachusetts  Board  of  State  Examiners  of 
Plumbers  and  Gas  Fitters  herewith  adopt  the  Rules 
and  Regulations  for  Manufactured  Buildings, 
Manufactured  Building  Components  and 
Manufactured  Homes. 

R3.1.2  Definitions  Unless  otherwise  expressly 
stated  in  780  CMR,  the  following  terms  shall,  for  the 
purpose  of  780  CMR  R3,  have  the  meaning 
indicated  in  780  CMR  R3. 1.2: 

Approval:  Approval  by  the  State  Board  of  Building 
Regulations  and  Standards  (BBRS) 

Building  System:  Plans,  specifications  and 
documentation  for  a  system  of  manufactured 
buildings  or  for  a  type  or  a  system  of 
manufactured  building  components,  which  may 
include  structural,  electrical,  mechanical, 
plumbing  and  fire  protection  systems  and  other 
systems  affecting  health  and  safety,  including 
variations  which  are  submitted  as  part  of  the 
building  system. 

Certification:  Any     manufactured     building, 

manufactured  building  component  or 
manufactured  home  which  meets  the  provisions 
of  the  applicable  Codes  and  Rules  and 
Regulations  pursuant  thereto;  and  which  has  been 
labeled  accordingly. 

Code:  780  CMR  or  Specialized  Codes  as  defined 
herein. 

Department  -  DPS:  The  Department  of  Public 
Safety,  Division  of  Inspections. 

Inspection      Agency:  Independent      agency, 

sometimes  referred  to  as  "third-party  agency", 
retained  by  the  manufacturer  and  approved  by 
BBRS  to  perform  inspections  and  evaluations  of 
building  systems,  compliance  assurance 
programs,  manufactured  buildings,  and 
manufactured  building  components. 

Installation:  The  process  of  affixing,  or  assembling 
and       affixing       a       manufactured       building. 


manufactured  building  component  or 
manufactured  home  on  the  building  site,  and 
connecting  it  to  utilities,  and/or  to  an  existing 
building.  Installation  may  also  mean  the 
connecting  of  two  or  more  manufactured  housing 
units  designed  and  approved  to  be  so  connected 
for  use  as  a  dwelling. 

Installer  of  Manufactured  Building:  An  individual, 
who  on  the  basis  of  training  and  experience,  has 
been  certified  by  a  specific  manufacturer  of 
manufactured  building  as  competent  to  supervise 
the  placement  and  connection  required  to  install 
the  manufactured  homes  of  that  manufacturer. 
Said  certification  by  the  manufacturer  shall  be  in 
writing,  and  the  certified  installer  shall  be  issued 
picture  identification  by  the  manufacturer  in 
verification  of  his\her  certification. 

Label:  An  approved  device  or  seal  evidencing 
certification  in  accordance  with  the  applicable 
Codes  and  Rules  and  Regulations  promulgated 
pursuant  thereto. 

Local  Enforcement  Agency:     A  department  or 

agency  in  a  municipality  charged  with  the 
enforcement  of  780  CMR  and  appropriate 
specialized  codes  which  include,  but  are  not 
limited  to,  248  CMR  (the  State  Plumbing  and  Gas 
Fitting  code)  and  527  CMR  12.00  (the  State 
Electrical  Code)  as  listed  in  Appendix  A. 

Manufactured  Building:  Any  manufactured 
building  which  has  concealed  elements,  such  as 
electrical,  mechanical,  plumbing,  fire  protection, 
insulation,  and  other  systems  affecting  health  and 
safety,  and  which  is  manufactured  or  assembled  in 
accordance  with  780  CMR  and  pertinent 
regulations,  in  manufacturing  facilities,  on  or  off 
the  building  site.  Also,  any  manufactured 
building  as  defined  above  which  does  not  have 
concealed  elements,  but  which  has  been  approved 
by  the  BBRS  at  the  request  of  the  manufacturer. 
"Manufactured  building"  does  not  mean 
"manufactured  home". 

Manufactured      Building      Component:      Any 

manufactured  subsystem,  manufactured 

subassembly,  or  other  system  designed  for  use  in 
or  as  part  of  a  structure  having  concealed 
elements  such  as  electrical,  mechanical,  plumbing 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


769 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


and  fire  protection  systems  and  other  systems 
affecting  health  and  safety. 

Manufactured  Homes  (Housing):  As  defined  in  24 
CFR,  Part  3280.2,  a  structure,  transportable  in 
Qne  or  more  sections,  which  in  the  traveling 
mode,  is  eight  body  feet  or  more  in  width  or  forty 
body  feet  or  more  in  length,  or,  when  erected  on 
site,  is  320  or  more  square  feet,  and  which  is  built 
on  a  permanent  chassis  and  designed  to  be  used  as 
a  dwelling  with  or  without  a  permanent 
foundation  when  connected  to  the  required 
utilities,  and  includes  the  plumbing,  heating,  air- 
conditioning,  and  electrical  systems  contained 
therein.  Calculations  used  to  determine  the 
number  of  square  feet  in  a  structure  will  be  based 
on  the  structure's  exterior  dimensions  measured  at 
the  largest  horizontal  projections  when  erected  on 
site.  These  dimensions  will  include  all 
expandable  rooms,  cabinets,  and  other  projections 
containing  interior  space,  but  do  not  include  bay 
windows.  (See  24  CFR,  Part  3280.2  for  a  more 
detailed  description  of  manufactured  homes  as 
defined  by  the  Department  of  Housing  and  Urban 
Development.) 

Specialized  Code:  All  building  codes,  rules  or 
regulations  pertaining  to  building  construction, 
reconstruction,  alteration,  repair  or  demolition 
promulgated  by  and  under  the  authority  of  the 
various  agencies  which  have  been  authorized 
from  time  to  time  by  the  General  Court  of  the 
Commonwealth      of     Massachusetts.  The 

specialized  codes  shall  include,  but  not  be  limited 
to.  248  CMR  (the  State  Plumbing  and  Gas  Fitting 
Code  )and  527  CMR  12.00  (the  Electrical  Code) 
as  listed  in  Appendix  A. 

State      Administrative      Agencies:  Boards, 

commissions,  departments  or  agencies  authorized 
to  promulgate,  adopt  and  amend  codes  and  rules 
and  regulations  relating  to  buildings  and 
structures  and  parts  thereof  and  limited  to  the 
BBRS,  Massachusetts  Board  of  Fire  Prevention 
Regulations,  Massachusetts  State  Examiners  of 
Electricians,  and  the  Massachusetts  Board  of  State 
Examiners  of  Plumbers  and  Gas  Fitters. 

State       Enforcement       Agencies:  Boards, 

commissions,  departments  or  agencies  authorized 
to  enforce  the  provisions  of  the  codes  and  rules 
and  regulations  which  have  been  promulgated, 
adopted  and  amended  and  which  relate  to 
buildings  or  structures  and  parts  thereof  and 
limited  to  the  Department  of  Public  Safety, 
Massachusetts  Board  of  State  Examiners  of 
Plumbers  and  Gas  Fitters,  and  the  Massachusetts 
State  Examiners  of  Electricians. 


R1.3  Scope: 

1.  780  CMR  R3  shall  govern  the  design, 
manufacture,  handling,  storage,  transportation  and 
installation  of  manufactured  buildings,  and 
manufactured  building  components  intended  for 
installation  in  this  State  and/or  manufactured  in 
this  State  for  shipment  to  any  other  state  in  which 
such  building,  building  components,  or 
manufactured  homes  and  the  labels  thereon  are 
accepted. 

2.  The  Federal  Manufactured  Home 
Construction  and  Safety  Standards  promulgated 
by  the  Department  of  Housing  and  Urban 
Development  govern  the  design,  manufacture, 
handling,  storage  and  transportation  of 
manufactured  homes  for  installation  in  this  state. 

3.  Subject  to  local  zoning  ordinances  and  by- 
laws, manufactured  buildings,  manufactured 
building  components  or  manufactured  homes  may 
be  sold  for,  delivered  to,  or  installed  on,  building 
sites  located  in  any  jurisdiction  of  this  State  if 
such  buildings,  building  components  or 
manufactured  homes  have  been  approved  and 
certified  pursuant  to  the  applicable  Codes  and 
780  CMR  R3. 

R3.1.4  Administration  and  Enforcement:     The 

BBRS  and  the  State  Enforcement  Agencies  shall 
enforce  all  provisions  of  780  CMR  R3.  The  State 
Enforcement  Agencies  shall  have  the  responsibility 
for  evaluating  and  recommending  approval  to  the 
BBRS  of  building  systems,  and  for  inspecting  and 
recommending  certification  of  manufactured 
buildings  and  manufactured  building  components  for 
compliance  with  780  CMR  R3  and  the  applicable 
codes.  The  State  Enforcement  Agencies  and  the 
local  enforcement  agencies  shall  accept 
manufactured  buildings,  manufactured  building 
components,  building  systems  and  compliance 
assurance  programs  labeled  and  certified  by 
inspection  agencies  approved  by  the  BBRS  and 
those  manufactured  homes  certified  as  in 
conformance  with  the  Federal  standards  by  the 
application  of  the  applicable  required  HUD  label. 

R3.1.5  Authorization  of  Third  Party  Inspections: 

Upon  recommendation  of  the  State  Enforcement 
Agencies,  the  BBRS  may  authorize  inspection 
agencies,  sometimes  referred  to  as  third  party 
inspection  agencies,  to  perform  all  or  part  of  the 
inspection  and  certification  of  manufactured 
buildings  and  manufactured  building  components, 
building  systems  and  compliance  assurance 
programs,  including  either  or  both  the  issuance  and 
the  attachment  of  labels  thereto.  The  BBRS  may 
suspend  or  revoke  and  such  authorization  for  cause. 

R3.1.6  Approvals  and  Compliance:  Upon  the 
recommendation  of  the  State  Enforcement  Agencies, 
the  BBRS  may  approve  building  systems  and 
compliance  assurance  programs  which  compiy  with 


770 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AjND  STANDARDS 

MANUFACTURED  BUILDINGS.  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


the  codes,  standards,  specifications  and  requirements 
and  780  CMR  R3. 

R3.1.7  Time  of  Manufacture:  For  purposes  of 
780  CMR  R3,  a  manufactured  building, 
manufactured  building  component  or  manufactured 
home  is  deemed  to  be  manufactured  at  such  time  as 
the  label  is  attached  to  it  in  accordance  with  the 
approved  compliance  assurance  program. 

R3.1.8  Retroactive  Changes:  No  changes  in  the 
codes,  standards,  specifications  and  requirements  of 
780  CMR  R3  shall  apply  retroactively. 

R3.I.9  Amendments:  The  State  Administrative 
Agencies  shall  notify  the  BBRS,  and  the  BBRS  shall 
notify  all  interested  parties  including  State 
Enforcement  Agencies,  inspection  agencies, 
manufacturers  with  approved  building  systems,  and 
local  governmental  jurisdictions  of  all  amendments 
to  780  CMR  R3,  and  each  manufacturer  shall  have 
no  more  than  180  days  following  the  sending  of 
notification  to  submit,  to  the  BBRS  compliance 
assurance  program  revisions  in  order  to  comply  with 
such  amendments.  Where  imminent  danger  to  life 
safety  is  involved,  the  State  Administrative  Agencies 
may  require  that  immediate  effect  be  given  such 
amendments  to  the  codes,  standards,  specifications 
and  requirements  so  adopted. 

780  CMR  R3.2  COMPLIANCE  ASSURANCE 
PROGRAMS 

RR3.2.1  Approval:  In  order  to  obtain  approval  for 
manufactured  buildings  or  manufactured  building 
components  a  manufacturer  shall  submit  a  building 
system  for  evaluation  to  the  BBRS  for  approvals  in 
accordance  with  780  CMR  R3. 

R3.2.2  Suitability:  Prior  to  a  full  evaluation,  the 
State  Enforcement  Agencies  shall  determine  that 
building  systems  and/or  the  application  for  approval 
of  the  compliance  assurance  program  submitted  to  it 
are  suitable  for  processing.  In  the  event  that  the 
application  is  found  to  be  unsuitable  for  processing, 
the  applicant  shall  be  notified  in  writing  of  such 
unsuitability  and  the  basis  thereof,  within  30  days  of 
the  date  the  application  is  received  by  the  BBRS.  In 
such  event,  all  but  $25  of  the  fee  will  be  returned 
and  the  findings  of  unsuitability  will  be  without 
prejudice.  Any  subsequent  submission  shall  be 
treated  as  a  new  application. 

R3.2.3  Requisites:  The  State  Enforcement 
Agencies  may  require  tests  to  determine  whether  a 
compliance  assurance  program  meets  the  codes, 
standards  and  requirements  of  the  evaluation  of 
plans,  specifications  and  documentation.  The 
procedures  used  shall  be  reviewed  and  evaluated  by 
the  BBRS  in  accordance  with  780  CMR  R3.  The 
costs  of  such  tests  shall  be  borne  by  the  applicant. 


R3.2.4  Notification  of  Disapproval:  In  the  event  a 
compliance  assurance  program  is  disapproved  by  the 
BBRS,  the  BBRS  shall  notify  the  applicant  with  a 
written  explanation  of  the  reasons  for  such 
disapproval  thereto. 

R3.2.5  Approval  -  Evidence:  Approval  of  a 
compliance  assurance  program  shall  be  evidenced  by 
a  letter  of  certification  issued  by  the  BBRS. 

R3.2.6  Approval  -  Report:  The  State  Enforcement 
Agencies  shall  prepare  and  the  BBRS  shall  issue  to 
the  applicant  a  building  system  approval  report 
which  shall  include  therein  any  conditions  imposed 
for  its  use. 

R2.7  Approval  -  Variations.  A  building  system 
and  compliance  assurance  program  or  any 
amendment  there  to  which  has  been  approved,  shall 
not  be  varied  in  any  way  without  prior  written 
authorization  by  the  BBRS.  All  amendments  shall 
be  in  writing  and  shall  be  made  a  part  of  the  written 
record  of  the  approval. 

R2.8  Amendments  -  Proposed:  Amendments  to 
compliance  assurance  programs  may  be  proposed  by 
submitting  to  the  BBRS  for  its  approval,  appropriate 
plans,  specifications,  or  documentation  showing  the 
effect  of  the  proposed  amendment  on  each  building 
system  and  the  required  fee. 

R3.2.9    Compliance   Assurance    Program:       A 

manufacturer  shall  obtain  approval  from  the  BBRS 
of  a  compliance  assurance  program  for  his  building 
system.  Buildings  or  building  components  shall  be 
manufactured  in  accordance  with  an  approved 
program  in  order  to  be  certified.  Compliance 
assurance  programs  shall  be  submitted  to  the  BBRS 
for  its  approval  in  accordance  with  780  CMR  R3. 

780  CMR  R3 _3  CERTIFICATION 

Manufactured  buildings  or  manufactured  building 
components  or  manufactured  homes,  accepted  by  the 
State  Enforcement  Agencies  and  an  inspection 
agency  as  having  been  manufactured  according  to  an 
approved  building  system  and  an  approved 
compliance  assurance  program,  shall  be  certified  by 
the  BBRS  upon  the  recommendation  of  the  State 
Enforcement  Agencies  as  complying  with  the 
requirements  of  the  applicable  codes  and  780  CMR 
R3.  Certification  shall  be  evidenced  by  the 
attachment  of  a  label  to  each  certified  manufactured 
building  or  manufactured  building  component  (or 
groups  of  components). 

R3.3.1  Manufacturer's  Data  Plate: 

R3.3.1.1  Contents:  The  following  information 
shall  be  placed  directly  or  by  reference  on  one  or 
more  permanent  manufacturer's  data  plates  in  the 
vicinity  of  the  electrical  distribution  panel  or  in 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


771 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


some  other  designated  location  acceptable  to  the 
State  Enforcement  Agencies,  on  the  manufactured 
building  or  manufactured  building  component 
where  it  will  be  readily  accessible  for  inspection: 

a.  Manufacturer's  name  and  address; 

b.  Serial  number  of  the  unit; 

c.  Label  serial  number; 

d.  Name  and  date  of  applicable  building, 
plumbing,  gas  and  electrical  codes  and  issue  of 
their  accumulative  supplements  complied  with; 

e.  Model  designation  and  name  of 
manufacturer  of  major  factory-installed 
appliances; 

f    Identification  of  permissible  type  of  gas  for 

appliance  and  directions  for  water  and  drain 

connection; 

g.    Snow,  wind,  seismic  and  other  live  loads; 

h.        Electrical    ratings    -    instructions    and 

warnings  on  voltage; 

i.     Special  conditions  or  limitations  on  use  of 

the  units,  including  unsuitability  for  areas  in 

which     specified     environmental     conditions 

prevail; 

j.      Methods  of  assembly  or  joining  multiple 

units; 

k.    Type  of  construction,  including  fire  rating, 

occupancy    class,    and    interior   finish   flame 

spread  class; 

1.    Building  height  and  story  limitation; 

m.    Floor  area;  and 

n.      Minimum  side  yard  requirements  for  fire 

rating 
If,  in  the  opinion  of  the  State  Administrative 
Agencies,  the  shape  or  size  of  a  building 
component  is  such  that  this  information  cannot  be 
attached  to  it  permanently,  the  information  may 
be  placed  in  a  manual  crated  with  the  component 
or  on  a  tag  attached  to  the  crate  in  which  the 
component  is  shipped,  if  the  information  is  not 
such  that  the  future  occupant  of  the  building 
should  know  it.  If  the  occupant  will  need  to  know 
the  information,  it  shall  be  contained  in  a  manual 
which  shall  be  presented  to  the  occupant  upon 
transfer  of  possession.  If  life  safety  is  involved, 
the  item  in  question  shall  be  plainly  labeled. 

R3.3.2  Labels:  Each  manufactured  building  or 
manufactured  building  component  which  is  certified 
pursuant  to  the  applicable  codes  and  780  CMR  R3, 
shall  have  permanently  attached  thereto,  in  a  visible 
location  as  shown  on  the  approved  building  system, 
an  approved  label  which  cannot  be  removed 
therefrom  without  destroying  such  label. 

R3.3.2.1  Contents:   An  approved  label  shall  bear 

the  following  information: 

a.  "This  label  certifies  that  this  building  (or 
building  component)  has  been  manufactured  in 
accordance  with  an  approved  building  system 
and  compliance  assurance  program  approved 
by  the  Commonwealth  of  Massachusetts  Board 


of  Building  Regulations  and  Standards  and 
inspected  by ."; 

b.  Label  serial  number; 

c.  Building  system  approval  number; 

d.  Manufacturer's  serial  number; 

e.  The  words  "See  data  plate  located  on 
.";  and 

f.  Date  of  manufacture. 

At  the  direction  of  the  BBRS  labels  and  data 
plates  may  be  limited  in  size  and  content  for 
components  whose  shape  and  size  does  not  permit 
the  full  information  to  be  placed  thereon. 

R3.3.2.2  Issuance:  The  approved  label  shall  be 
issued  by  the  BBRS  or  its  agents  in  accordance 
with  the  following: 

a.  If  the  BBRS  delegated  the  issuance  of 
labels  to  an  inspection  agency,  the  agency  shall 
be  required  to  obtain  approval  from  the  BBRS 
for  the  manner  in  which  they  are  handled; 

b.  Labels  must  be  serially  numbered; 

c.  A  manufacturer's  compliance  assurance 
program  submitted  in  accordance  with 
780  CMR  R3  shall  include  requirements  for 
issuance,  possession  of,  attachment  of  and 
accounting  for  all  labels  to  assure  that  labels 
are  attached  only  to  manufactured  buildings, 
manufactured  building  components,  or 
manufactured  homes  manufactured  pursuant  to 
an  approved  building  system  and  inspected 
pursuant  to  an  approved  compliance  assurance 
program;  and 

d.  Upon  request  of  the  inspection  agency,  the 
BBRS  may  determine  that  the  manufacturer's 
record  of  compliance  is  such  that  the 
inspection  agency  need  not  maintain  an 
inspector  in  a  given  plant  at  all  times, 
inspection  agency  may  entrust  labels  to  the 
custody  of  one  or  more  employees  of  the 
manufacturer,  who  shall  be  charged  with 
controlling  the  use  of  the  such  labels.  Such 
employees  shall  not  be  given  custody  of  more 
labels  than  are  necessary.  If  the  conditions  of 
custody  are  violated,  the  BBRS  or  an 
inspection  agency  shall  immediately  regain 
possession  of  all  labels  that  have  not  been 
applied  to  the  manufactured  buildings  or 
manufactured  building  components  and  shall 
take  such  further  action  with  respect  to  future 
labeling,  as  it  may  deem  necessary  to  assure 
compliance  with  the  applicable  codes  and 
780  CMR  R3. 

R3.3.3  Records  of  Labels:  Permanent  records  shall 
be  kept  of  the  handling  of  all  labels,  indicating  at 
least  how  may  labels  have  been  applied  to 
manufactured  buildings  or  manufactured  building 
components  (or  groups  of  components),  which  labels 
have  been  applied  to  which  buildings  or  building 
components,  the  disposition  of  any  damaged  or 
rejected  labels,  and  the  location  and  custody  of  all 
unused  labels.    Such  records  shall  be  maintained  by 


772 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUTLD[NG  REGULATIONS  AND  STANDARDS 

MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


the  manufacturer  or  by  the  inspection  agency.  A 
copy  of  such  records  covering  attachment  of  each 
label  shall  be  sent  to  the  BBRS  on  the  tenth  of  each 
month  and  the  BBRS  shall  forward  all  such  records 
to  the  State  Enforcement  Agencies. 

R3.3.4  Attachment  of  Labels:  The  inspection 
agency  shall  attach  in  consecutive  numerical 
sequence  labels  to  manufactured  buildings  or 
manufactured  building  components  manufactured  in 
accordance  with  an  approved  building  system  and 
meeting  the  requirements  of  an  approved  compliance 
assurance  program. 

Manufacturers  shall  attach  labels  in  the  same 
manner  to  manufactured  buildings  or  building 
components  manufactured  in  accordance  with  an 
approved  building  system  and  meeting  the 
requirements  of  an  approved  compliance  assurance 
program. 

Manufacturers  shall  attach  labels  in  the  same 
manner  to  manufactured  buildings  or  building 
components  manufactured  in  accordance  with  a 
approved  compliance  assurance  program,  if  custody 
of  the  labels  has  been  entrusted  to  them  in 
accordance  with  780  CMR  R3.3.3.4. 

R3.3.5  Suspension  and  Revocation:    The  BBRS 

may  suspend  or  revoke,  or  cause  to  be  suspended  or 

revoked,    the    certification    of  any    manufactured 

building  or  manufactured  building  component  which 

the  State  Enforcement  Agencies  or  an  inspection 

agency  finds  not  to  comply  with  the  applicable  codes 

or  780  CMR  R3,  or  which  has  been  manufactured 

pursuant  to   a  building   system  or  a  compliance 

assurance  program  for  which  approval  has  been 

suspended   or  revoked,   or  which   has  not  been 

manufactured   in   accordance   with   the   approved 

compliance     assurance     program.         The     State 

Enforcement  Agencies  or  an  inspection  agency  shall 

remove  or  cause  to  be  removed,  labels  from  any 

such  manufactured  building,  manufactured  building 

component  or  manufactured  home  until  it  is  brought 

into   compliance  with  the   applicable   codes   and 

780  CMR  R3.  Notice  of  suspension  or  revocation  of 

certification  shall  be  in  writing  with  the  reasons  for 

suspension  or  revocation  clearly  set  forth  therein. 

a.    Upon  suspension  or  revocation  of  the  approval 

of  any  building  system  or  compliance  assurance 

program,  no  further  labels  shall  be  attached  to  any 

manufactured  buildings  or  manufactured  building 

components     manufactured     pursuant     to     the 

buiiding  system  or  compliance  assurance  program 

with  respect  to  which  the  approval  was  suspended 

or  revoked.  Upon  termination  of  such  suspension 

or  revocation,  labels  may  again  be  attached  to  the 

manufactured  building  or  manufactured  building 

components  manufactured  after  the  date  approval 

was  reinstated.    Should  any  building  or  building 

component  have  been  manufactured  during  the 

period  of  suspension  or  revocation,  it  shall  not  be 

labeled  unless  the  State  Enforcement  Agencies  or 


inspection  agency  have  inspected  such  building  or 
building  component  and  is  satisfied  that  all 
requirements  for  certification  have  been  met.  If 
the  State  Enforcement  Agency  acts  under 
780  CMR  R3.3.5,  it  must  notify  the  inspection 
agency. 

b.  The  manufacturer  shall  return  all  labels 
allocated  for  a  manufactured  building  or 
manufactured  building  component  to  the  BBRS 
no  later  than  30  days  from  the  effective  date  of 
any  suspension  or  revocation  of  the  State 
Enforcement  Agencies  or  inspection  agency,  of 
the  building  system  or  compliance  assurance 
program  pursuant  to  which  the  manufactured 
building  or  manufactured  building  component  is 
being  manufactured.  The  manufacturer  shall  also 
return  to  the  BBRS  all  labels  which  it  determines 
for  any  reason  are  no  longer  needed. 

R3.6  Variations  of  Certified  Units:  Manufactured 
buildings,  manufactured  building  components  or 
manufactured  homes  certified  and  labeled  pursuant 
to  the  applicable  codes  and  780  CMR  R3  shall  not 
be  varied  in  any  way  prior  to  the  issuance  of  a 
certificate  of  occupancy  without  resubmission  to  the 
BBRS  for  its  approval  of  the  variation  and  of  the 
unit  which  includes  the  variation.  The  State 
Enforcement  Agencies  or  an  inspection  agency  shall 
inspect  the  manufactured  building,  manufactured 
building  component  or  manufactured  home  wherever 
it  is  located  and  such  inspection  may  include  such 
tests  or  destructive  or  nondestructive  disassembly  as 
the  State  Enforcement  Agencies  or  an  inspection 
agency  deems  necessary  to  assure  compliance  with 
the  applicable  Codes  and  780  CMR  R3.  Local 
Enforcement  Agencies  may  be  designated  by  the 
BBRS  or  State  Enforcement  Agencies  as  inspection 
agencies  for  such  purposes. 

780  CMR  R3.4  INSPECTION  BY  THE  STATE 

ENFORCEMENT  AGENCIES  OR  THEIR 

AGENTS 

The  State  Enforcement  Agencies  shall  make,  or 
cause  to  be  made,  such  inspections  of  the  entire 
processing  of  manufacturing,  certifying,  handling, 
storing  and  transporting  of  manufactured  buildings 
or  manufactured  building  components  produced 
pursuant  to  approved  building  systems  as  they  deem 
necessary. 

R3.4.1  Inspection  of  Facilities:  As  part  of  the 
process  of  evaluating  building  systems  and 
compliance  assurance  programs,  the  State 
Enforcement  Agencies  shall  inspect,  or  cause  to  be 
inspected,  the  manufacturing  facilities  in  which  the 
buildings  or  building  components  are  to  be 
manufactured. 

R3.4.2  Inspection  According  to  Compliance 
Assurance  Programs:  The  State  Enforcement 
Agencies  or  an  inspection  agency  shall  make  such 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


773 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


inspections  as  may  be  required  by  an  approved 
compliance  assurance  program,  or  as  may  be 
deemed  necessary  by  the  State  Enforcement 
Agencies. 

R3.4.3  Inspection  of  Damaged  Components:  Prior 
to-  the  issuance  of  a  certificate  of  occupancy,  the 
State  Enforcement  Agencies  or  an  inspection  agency 
shall  inspect,  or  cause  to  be  inspected,  certified 
manufactured  buildings  or  manufactured  building 
components  which  it  determines  to  have  been 
sufficiently  damaged  after  certification  to  warrant 
such  inspection  and  to  take  such  action  with  regard 
to  such  buildings  or  building  components  as  is 
authorized  hereof,  or  as  is  otherwise  necessary  to 
eliminate  dangerous  conditions.  The  local 
enforcement  agencies  may  be  designated  by  the 
BBRS  or  the  State  Enforcement  Agencies  as  the 
inspection  agency. 

R3.4.3.1    Repairing    Damaged    Components: 

The  State  Enforcement  Agencies  or  an  inspection 
agency  shall  require  manufactured  buildings  or 
manufactured  building  components  which  are  so 
damaged  as  to  no  longer  comply  with  the 
applicable  Codes  and  780  CMR  R3,  to  be  repaired 
and  made  to  comply  within  a  reasonable  time;  or 
if  they  are  so  damaged  that  they  cannot  be 
brought  into  compliance,  the  State  Enforcement 
Agencies  or  inspection  agency  shall  order  that  the 
labels  be  removed  from  such  buildings,  building 
components  or  manufactured  homes.  A  report 
under  this  section  shall  be  filed  with  the 
inspection  agency,  BBRS  and  State  Enforcement 
Agency. 

R3.4.3.2  Irreparably  Damaged  Components: 

Irreparably  damaged  buildings  or  building 
components  shall  be  disposed  of  by  the 
manufacturer. 

R3.4.4  Monitoring  Inspection  Agency:  The  State 
Enforcement  Agencies  or  their  designated  agents 
shall  examine  each  approved  inspection  agency,  at 
any  reasonable  time,  and  without  prior 
announcement,  in  order  to  monitor  the  reliability  of 
each  agency  and  of  its  monitoring  of  each 
compliance  assurance  program,.  Each  such 
examination  shall  investigate  the  adequacy  of  all 
procedures  used  by  the  agency  in  monitoring 
compliance  assurance  programs  including 
inspection,  tests,  production  methods,  process 
controls,  operator  performance,  materials,  receipts, 
storage  and  handling,  workmanship  standards, 
records  and  all  other  activities  which  implement  the 
compliance  assurance  program  in  the  manufacturing 
facility,  during  transport,  on-site,  and  at  critical 
subcontractors'  facilities.  The  results  of  such 
examinations  shall  be  filed  with  the  office  of  the 
BBRS.  Copies  of  such  reports  shall  be  sent  to  the 
inspection  agency  and  the  State  Enforcement 
Agencies.    Inspection  agencies  shall  be  specifically 


notified  by  the  BBRS  of  any  deficiencies  and  of  the 
manner  and  time  by  which  such  deficiencies  must  be 
eliminated.  If  deemed  necessary  by  the  State 
Enforcement  Agencies  an  inspection  agency's 
approval  may  be  suspended  or  revoked  by  the  BBRS 
as  provided  herein. 

R3.4.4.1  Prior  to  Approval:  Such  examinations 
may  also  be  conducted  before  approving  an 
inspection  agency. 

R3..5  Inspection  by  Disassembly:  No  inspection 
entailing  disassembly,  damage  to  or  destruction  of 
certified  manufactured  buildings,  manufactured 
building  components  or  manufactured  homes  shall 
be  conducted  except  to  implement  780  CMR  R3. 

780  CMR  R3.5  LOCAL  ENFORCEMENT 
AGENCY  PROCEDURES  AND  INSPECTIONS 

R3.5.1  Issuance  of  building  permits:  Upon 
application  and  in  conformity  with  the  provisions  of 
780  CMR,  the  building  official  shall  issue  building 
permits  for  installation  of  certified  manufactured 
buildings,  manufactured  building  components  or 
manufactured  housing. 

R3.5.1.1  Licensed  Construction  Supervisors 
and  Certified  Installers:  A  construction 
supervisor,  duly  licensed  in  accordance  with 
780  CMR  R5,  shall,  in  accordance  with  780  CMR 
108.3.5,  act  as  the  agent  for  the  owner  for  the 
purpose  of  applying  for  and  obtaining  any  and  all 
building  permits  required  for  the  field  erection  of 
all  one  or  two  family  manufactured  dwellings 
subject  to  the  provisions  of  780  CMR  35  and 
applicable  780  CMR  R3. 

As  part  of  the  building  permit  application 
process,  the  licensed  construction  supervisor  shall 
submit  to  the  building  official,  in  writing,  the 
name  of  the  installer,  who  shall  be  duly  certified 
by  the  manufacturer  to  install  said  manufacturer's 
product,  and  is  identified  as  a  certified  installer  of 
manufactured  buildings  (certified  installer)  by 
said  manufacturer.  The  certified  installer  shall  be 
responsible  for  the  safe  and  proper  placement  and 
connection  of  the  manufactured  home  units  in 
accordance  with  780  CMR  35,  780  CMR  R3  and 
specialized  codes  as  listed  in  Appendix  A 

The  licensed  construction  supervisor  shall  be 
responsible  for  the  construction  of  the  foundation 
system,  and  all  pertinent  site  work,  in  accordance 
with  780  CMR  35  and  780  CMR  R3  listed  in 
Appendix    A  The     licensed     construction 

supervisor  shall  provide  at  least  48  hours  notice  to 
the  building  official  before  the  placement  and 
connection  of  such  units  shall  begin  An 
application  to  local  enforcement  agencies  for  an 
appropriate  permit  shall,  when  requested,  in 
addition  to  any  other  requirements  contain: 

R3.5.1.2  Permit  Application  -  Statement  of 
Content:      A  statement  that   the  work  to  be 


774 


780  CMR -Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


performed  under  such  permit  is  to  include  the 
installation  of  a  certified  manufactured  building, 
manufactured  building  component  or 
manufactured  home  in  accordance  with  the 
provisions  of  the  applicable  codes,  the  statement 
to  be  signed  by  the  applicant  or  his  agent,  with  the 
appropriate  address. 

R3.5.13  Permit  Application  -  Building  System: 

A  true  copy  of  the  approved  building  system  with 
respect  to  which  the  manufactured  building  or 
manufactured  building  component  was 
manufactured  or  is  to  be  manufactured,  where  one 
has  not  previously  been  furnished  to  that  local 
enforcement  agency. 

R3.  5.1.4  Permit  Application  -  Building  System 
Approval:  A  copy  of  the  Building  System  Report, 
as  approved  by  the  BBRS,  where  it  has  not 
previously  been  furnished  to  the  Local 
Enforcement  Agency. 

R3.  5.2  Inspection  of  Site  Preparation  and  Service 
Connections:  Appropriate  local  enforcement 
agencies  shall  inspect  site  preparation  work 
including  foundations,  not  within  the  scope  of  the 
approval  and  certification,  and  the  structural, 
mechanical,  plumbing  and  electrical  connections 
among  units,  for  compliance  with  applicable  law, 
rules  and  regulations. 

R3.53  Compliance  with  Instructions:  Appropriate 
local  enforcement  agencies  shall  inspect  all 
manufactured  buildings,  manufactured  building 
components  or  manufactured  homes  upon,  or 
promptly  after,  installation  at  the  building  site  to 
determine  whether  all  instructions  in  the  Building 
System  Approval  Report  or  conditions  listed  on  the 
manufacturer's  data  plate  have  been  followed. 

This  may  include  tests  for  tightness  of  plumbing 
and  mechanical  systems,  and  for  malfunctions  in  the 
electrical  system  and  a  visual  inspection  for  obvious 
nonconformity  with  the  approved  building  system. 

R3.5.3.1  Disassembly  Prohibited:  Unauthorized 
destructive  disassembly  of  certified  buildings  and 
building  components  and  mobile  homes  shall  not 
be  performed  in  order  to  conduct  such  tests  or 
inspections,  except  as  provided  in  780  CMR 
R3.3.4.3,  nor  shall  there  be  imposed  standards  or 
test  criteria  different  from  those  adopted  by  the 
State  Enforcement  Agencies  or  specified  in  the 
Building  System  Approval  Report,  or  the 
"HUD's"  Manufactured  Home  Construction  and 
Safety  Standards. 

R3.5.3.2  Opening  Panels:  Nondestructive 
disassembly  may  be  performed  only  to  the  extent 
of  opening  access  panels  and  cover  plates. 

R3.5.4  Noncomplying  New  Units:  Local 
enforcement  agencies  shall  report  to  the  BBRS  in 
accordance      with      780      CMR      R3.5.6      any 


noncomplying  manufactured  buildings  and  building 
components. 

R3.5.5  Certificates  of  Occupancy:  Appropriate 
local  inspectors  shall  issue  certificates  of  occupancy 
for  certified  manufactured  buildings  and 
manufactured  homes  containing  certified  building 
components  which  otherwise  comply  with  all  the 
applicable  codes,  after  they  have  been  installed  and 
inspected  pursuant  to  the  applicable  codes  and 
780  CMR  R3,  provided  that  any  manufactured 
building  or  manufactured  building  component  found 
not  to  comply  with  the  Building  System  Approval 
Report  or  any  manufactured  home  found  not  to 
comply  with  "Hud's"  Manufactured  Home 
Construction  and  Safety  Standards  shall  be  brought 
into  compliance  before  such  certificate  of  occupancy 
shall  be  issued. 

R3.5.6  Reporting  of  Violations  to  Department  of 
Public  Safety:  When  any  local  enforcement  agency 
is  making  an  inspection  and  finds  violations  or 
suspected  violations,  it  shall  report  the  details  of  the 
violations  in  writing  to  the  BBRS.  Where  violations 
are  hazardous  to  occupants,  a  certificate  of 
occupancy  shall  not  be  issued  and  the  building  shall 
not  be  occupied  before  such  hazards  are  corrected. 
If  the  violations  are  not  hazardous,  a  temporary 
certificate  of  occupancy  may  be  issued. 

780  CMR  R3.6  FEES 
R3.6.1  Deposit  for  Application  to  the  BBRS:    A 

deposit  shall  be  required  upon  application  to  the 
BBRS  to  perform  any  of  the  functions  in  780  CMR 
R3. 

R3.6.2  Establishment  of  Fees:  Fees  charged  by  the 
BBRS  for  functions  performed  shall  be  in 
accordance  with  the  fee  schedule  established  by  the 
State  Administrative  Agencies  as  specified  in 
780  CMR  R3. 18. 

780  CMR  R3.7  NOTIFICATION  OF 

CHANGES  IN  NAME,  ADDRESS, 

OWNERSHIP  OR  LOCATION 

R3.7.1       Notification       by       Manufacturers: 

Manufacturers  shall  notify  the  BBRS  in  writing 
within  ten  days  of  any  of  the  following  occurrences: 

a.  The  corporate  name  is  changed; 

b.  The  main  address  of  the  company  is  changed; 

c.  There  is  a  change  in  25%  or  more  of  the 
ownership  interest  of  the  company  within  a  1 2 
month  period; 

d.  The  location  of  any  manufacturing  facility  is 
changed; 

e.  A  new  manufacturing  facility  is  established;  or 

f.  There  are  changes  in  principal  officers  of  the 
firm. 

The  BBRS  shall  notify  the  State  Administrative 
Agencies  of  such  occurrences. 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


775 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


R3.7.2    Notification    by    Inspection    Agencies: 

Inspection  agencies  shall  notify  the  BBRS  in  writing 
within  ten  days  of  any  of  the  following  occurrences: 

a.    The  company  name  is  changed; 

b     The  main  address  of  the  company  is  changed; 

,c.      There  is  a  change  in  25%  or  more  of  the 

ownership  interest  or  control  of  the  company 

within  a  12  month  period; 

d.  The  location  of  any  testing  facility  is  changed; 

e.  A  new  testing  facility  is  established;  or 

f.  There  are  changes  in  principal  officers  and  key 
supervisory  and  responsible  personnel  of  the  firm. 

The  BBRS  shall  notify  the  State  Administrative 
Agencies  of  such  occurrences. 

780  CMR  R3.8  PROPRIETARY 
INFORMATION 

All  information  relating  to  building  systems  and 
compliance  assurance  programs  which  the 
manufacturer  or  other  party  considers  proprietary 
shall  be  so  designated  by  him  at  the  time  of  its 
submission,  and  shall  be  so  held  by  the  State 
Enforcement  Agencies  and  State  Administrative 
Agencies,  except  as  the  State  Administrative 
Agencies  determine  in  each  case,  that  disclosure  is 
necessary  to  carry  out  the  purposes  of  the  applicable 
codes  and  780  CMR  R3. 

PARTE   REQUIREMENTS  FOR 

SUBMISSION  OF  BUILDING 
SYSTEMS  AND  COMPLIANCE 
ASSURANCE  PROGRAMS 

780  CMR  R3.9  BUILDING  SYSTEMS 

Building  systems  shall  meet  the  requirements  set 
forth  below  to  be  evaluated  for  compliance  with  the 
standards,  specifications  and  requirements  adopted 
by  the  State  Administrative  Agencies. 

R3.9.1  General  Requirements: 

R3.9.1.1  Plans,  Specifications  and 
Documentation:  Building  systems,  including  all 
plans,  specifications  and  other  documentation, 
shall  be  submitted  in  quadruplicate  to  the  BBRS 
who  shall  act  as  the  depository  and  disburser  of 
all  such  items.  The  BBRS  shall  forward  to  the 
appropriate  State  Enforcement  Agencies  plans, 
specifications  and  documentation  for  their 
recommendations. 

R3.9.1.2  Form  and  Fees:  Building  systems  shall 
be  submitted  in  the  form  prescribed  by  the  BBRS 
and  shall  be  accompanied  by  all  required  fees. 

R3.9.1.3     Identification:  All     documents 

submitted  with  the  application  shall  be  identified 
to  indicate  the  manufacturer's  name,  office 
address  and  address  of  the  manufacturing  facility. 


R3.9.1.4  Plans  Showing  Elements:  Plans  shall 
be  submitted  showing  all  elements  relating  to 
specific  systems  on  properly  identifiable  sheets. 

R3.9.1.5  Application  -  Approved  Architect  or 
Engineer:  Each  building  system  application  shall 
bear  the  signature  and  seal  of  an  approved 
registered  architect  or  registered  professional 
engineer  certifying  that  the  building  system 
complies  with  the  applicable  codes  and  standards 
promulgated  herein. 

R3.9.1.6  On-site  Work  Identified:  All  work  to 
be  performed  on-site,  including  connection  of  all 
systems,  equipment  and  appliances,  shall  be 
identified  and  distinguished  from  work  to  be 
performed  in  the  manufacturing  facility. 

R3.9.1.7  Space  for  State  Administrative 
Agencies  Approval  Stamp:  A  3"  x  4"  blank 
rectangular  space  shall  be  provided  on  all  sheets 
of  plans  near  the  title  box  for  the  BBRS's  stamp  of 
approval. 

R3.9.1.8  Material  Grade  and  Quality:  Grade, 
quality  and  identification  of  all  material  shall  be 
specified. 

R3.9.1.9  Calculations  and  Test  Reports:  Design 
calculations  and  test  reports  shall  be  specified. 
R3.9. 1.9.1  Drawings  to  Scale:  Drawings  shall 
be  drawn  to  scale  and  be  legible. 
R3.9. 1.9.2  Label  and  Data  Plate  Location: 
Drawings  shall  indicate  the  location  of  the 
approved  label  and  data  plate. 
R3.9.1.9.3  Drawings  Dated  and  Identified: 
Drawings  shall  be  dated  and  identified.    The 
number  of  sheets  in  each  set  shall  be  indicated. 

R3.9.2  Required  Construction  Details:  Building 
systems  for  manufactured  buildings  shall  provide  or 
show,  but  not  be  limited  to,  the  details  listed  below 
including  the  method  of  their  testing  or  evaluation, 
or  both.  These  requirements  shall  apply  to  the 
building  systems  for  building  components  only  to 
the  extent  deemed  necessary  by  the  State 
Enforcement  Agencies  to  permit  a  proper  evaluation 
of  the  building  component 

R3.9.2.1  General: 

a.  Details  and  methods  of  installation  of 
manufactured  buildings  or  manufactured 
building  components  on  foundations  and/or  to 
each  other. 

b.  All  exterior  elevations. 

c.  Cross  sections  as  necessary  to  identify 
major  building  components. 

d.  Details  of  flashing,  such  as  at  openings  and 
at  penetrations  through  roofs  and 
subcomponent  connections.  Indicate  flashing 
material  and  gauge  to  be  used 

e     Attic  access  and  attic  ventilation. 

f.      Exterior  wall,  roof  and  soffit  material  as 

well  as  finish. 


776 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


g.    Interior  wall  and  ceiling  finish  material. 

h.    Fire  separation  walls. 

i.         Sizes,    locations   and   types   of  doors, 

windows  and  fire/smoke  detectors. 

j.    Recommended  foundation  plans,  vents  and 

underfloor  access. 

R3.9.2.2  Building  Classification: 

a.  Occupancy  or  use. 

b.  Area,  height,  and  number  of  stories. 

c.  Type  of  construction. 

d.  Fireresistance  ratings. 

R3.9.2.3  Space  and  Fire  Safety: 

a.  Details  of  fire  resistance  rated  assemblies 
for  all  stairway  enclosures,  doors,  walls,  floors, 
ceilings,  partitions,  columns,  roof  and  shaft 
enclosures. 

b.  Detail  of  Fire  Protection  Systems. 

c.  Details  as  to  width  of  all  aisles,  exits, 
corridors,  passageways  and  stairway 
enclosures. 

d.  Toxicity  and  flame  spread  classification  of 
finished  materials. 

R3.9.2.4  Structural  Detail  Requirements: 

a.  Engineer's  calculations  of  structural 
members,  where  appropriate. 

b.  Structural  and  framing  details  of  all  floors, 
roof  and  walls. 

c.  Details  and  stress  diagrams  of  roof  trusses. 

d.  Details  of  reinforcing  steel. 

e.  Complete  loading  schedule. 

f    Column  loads  and  column  schedule 

g.    Lintel  schedule. 

h.      Size,  spacing  and  details  of  all  structural 

elements. 

i.     Grade  or  quality  of  all  structural  elements 

(lumber,  steel,  etc.). 

j.      Elevation  of  structural  elements,  walls  or 

sections    thereof,     providing    resistance    to 

vertical  loads  or  lateral  forces. 

k.  Complete    details    of   all    structural 

connections. 

R3.9.2.5  Mechanical  Detail  Requirements: 

a.  Location  of  all  equipment  and  appliances. 
Indicate  equipment  and  appliances  listed  or 
labeled  by  approved  agencies. 

b.  Heat  loss  and  heat  gain  calculations. 

c.  Manufacturer's  name,  make,  model, 
number,  BTU,  input  and  output  rating  of  all 
equipment  and  appliances,  as  appropriate,  or 
the  equal  thereof. 

d.  Duct  and  register  locations,  sizes,  and 
materials. 

e.  Clearances  from  combustible  material  or 
surfaces  for  all  ducts,  flues  and  chimneys. 


f.  Method  of  providing  required  combustion 
air  and  return  air. 

g.  Location  of  flues,  vents  and  chimneys  and 
clearances  from  air  intakes  and  other  vents  and 
flues. 

h.         Details    regarding   dampers   in    ducts 

penetrating  fire  separations. 

i.    Complete  drawings  of  fire  sprinkler  system, 

standpipe  system  or  smoke/fire  alarm  system 

as  required. 

j.       Detail  of  elevator  or  escalator  system, 

including  method  of  emergency  operation. 

k.    Duct  and  piping  insulation  thickness. 

1.    Ventilation  air  calculations. 

R3.9.2.6  Plumbing  Detail  Requirements: 

a.  Plan  or  schematic  drawing  of  the  plumbing 
layout,  including  but  not  limited  to,  size  of 
piping,  fitting,  traps  and  vents,  cleanouts  and 
valves,  gas,  water,  and  drainage  system. 

b.  Plumbing  materials,  and  location  of  all 
equipment  and  appliances  to  be  used.  Indicate 
fixture  unit  capacity  of  system(s)  and  the  make, 
model,  and  rating/capacity  of  equipment  and 
appliances.  Indicate  equipment  and  appliances 
listed  or  labeled  by  approved  agencies. 

c.  Make  and  model  of  safety  controls  (such  as 
for  water  heaters),  their  location,  and  whether 
listed  or  labeled  by  approved  agencies. 

d.  How  piping  is  to  be  supported  and  intervals 
of  support. 

e.  Location  of  vents  above  roofs  and  required 
clearances,  including  but  not  limited  to 
clearances  from  air  intakes,  other  vents  and 
flues. 

f.  Methods  of  testing. 

R3.9.2.7  Electrical  Detail  Requirements: 

a.  Plan  of  service  equipment,  including 
service  entrance,  conductors,  service  raceway 
and  clearances  above  ground  and  above 
structures. 

b.  Method  and  detail  for  grounding  service 
equipment. 

c.  Single  line  diagram  of  the  entire  electrical 
installation. 

d.  Load  calculations  for  service  and  feeders. 

e.  Sizes  of  all  feeders  and  branch  circuits. 

f.  Size,  rating  and  location  of  main 
disconnect/overcurrent  protective  devices. 

g.  Method  of  interconnection  between 
manufactured  buildings  or  manufactured 
building  components  and  location  of 
connections. 

h.    Location  of  all  outlets  and  junction  boxes. 

i.      Method  of  mounting  fixtures  and  wiring 

installations. 

j.    Lighting  power  calculations. 


2/7/97    (Effective  2/28/Q7) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  R3.10  COMPLIANCE  ASSURANCE 

PROGRAMS  FOR  MANUFACTURED 

BUILDINGS  AND  MANUFACTURED 

BUILDING  COMPONENTS 

Compliance  assurance  programs  shall  be 
approved  if  they  meet  the  requirements  set  forth  in 
780  CMR  R3.3.10.  It  is  the  manufacturer's 
responsibility  to  execute  every  aspect  of  this 
program.  The  manufacturer  shall  continue  to  be 
responsible  for  all  corrective  actions  required  and 
the-  contractual  relationship  between  the 
manufacturer  and  the  inspection  agency  shall  not 
diminish  such  responsibility.  The  manufacturer 
shall  cooperate  with  the  inspection  agency  by 
providing  the  inspection  agency  with  all  necessary 
reports,  information,  documents,  records,  facilities, 
equipment,  samples  and  other  assistance  for  assuring 
compliance. 

The  manufacturer's  compliance  assurance 
program  shall  be  submitted  to  the  BBRS  in  the  form 
of  a  compliance  assurance  manual  which  shall 
contain  complete  documentation  of  all  compliance 
assurance  activities  of  both  the  manufacturer  and  the 
inspection  agency.  The  manual  shall  be 
comprehensively  indexed,  and  shall  treat  the 
material  listed  here  in  detail,  as  follows: 

R3.10.1  Organization  Requirements: 

a.  A  procedure  for  periodic  revision  of  the 
manual; 

b.  An  organizational  structure  for  implementing 
and  maintaining  the  compliance  assurance 
program  and  its  functional  relationship  to  other 
elements  of  the  organization  structure  of  the 
manufacturer,  which  structure  shall  provide  for 
independence  from  the  production  department; 
Company  officers  and  employees  in  charge  of  the 
compliance  assurances  program  must  be 
identified,  and  their  training  and  qualifications 
specified; 

c.  A  uniform  system  of  audit  (in-depth  analysis 
of  program  effectiveness  and  means  to  identify 
deficiencies)  to  monitor  program  performance 
periodically; 

d.  Complete  and  reliable  records  of 
manufacturing  and  site  operations,  if  any  (suitable 
means  of  storage,  preservation  and  accessibility  of 
copies  of  forms  to  be  utilized  shall  be  included); 

e.  A  system  to  control  changes  in  production  or 
inspection  procedures; 

f    A  system  to  assure  that  working  drawings  and 

specifications,  working  instructions  and  standards, 

procurement   documents,    etc.    conform  to   the 

approved  building  system; 

g.        A  serial  number  system  for  buildings  or 

building  components;  and 

h.       The  method  of  safekeeping,  handling  and 

attaching    labels    and    identification    of   those 

employees  responsible  therefor. 


R3.10.2  Materials  Control 

a.  Procedure  to  assure  effective  control  over 
procurement  sources  to  ensure  that  materials, 
supplies  and  other  items  used  in  production  and 
site  operations,  if  any,  conform  to  the  approved 
plans,  specifications  and  quality  requirements; 

b.  Procedures  for  inspection  of  materials, 
supplies  and  other  items  at  the  point  of  receipt; 

c.  Method  of  protection  of  materials,  supplies 
and  other  items  against  deterioration  prior  to  their 
incorporation  in  the  certified  buildings  or  building 
component;  and 

d.  Provision  for  disposal  of  rejected  materials, 
supplies  and  other  items. 

R3.10.3  Production  Control: 

a.  Procedures  for  timely  remedial  and  preventive 
measures  to  assure  product  quality; 

b.  Provision,  maintenance  and  use  of  testing  and 
inspection; 

c.  Provision  for  frequency  of  sampling 
inspections; 

d.  Provision  of  necessary  authority  to  reject 
defective  work  and  carry  out  compliance 
assurance  functions,  notwithstanding  any  conflict 
with  production  department  goals  and  needs; 

e.  A  schematic  of  the  manufacturing  operation 
showing  the  location  of  inspection  stations,  and 
"hold"  points  for  mandatory  inspection 
characteristics; 

f.  Inspection  and  test  procedures,  including 
accept/reject  criteria  and  mandatory  inspection 
characteristics; 

g.  Standards  of  workmanship;  and 
h.    Provision  of  disposal  of  rejects. 

R3.10.4  Finished  Product  Control: 

a.  Procedure  for  final  inspection  of  all 
manufactured  buildings  or  manufactured  building 
components  before  shipment  to  the  site  or  storage 
point,  including  identification  and  labeling; 

b.  Procedures  for  handling  and  storing  all 
finished  manufactured  buildings  or  manufactured 
building  components,  both  at  the  manufacturing 
plant  or  other  storage  point  and  after  delivery  to 
the  building  site; 

c.  Procedures  for  packing,  packaging  and 
shipping  operations  and  related  inspections;  and 

d.  Procedures  for  transportation,  including  all 
measures  to  protect  against  damage  while  in 
transit,  and  setting  forth  the  modes  of 
transportation  to  be  utilized  and  the  carrying 
equipment  and  procedures. 

R3.10.5  Installation  Control: 

a.  Installation  procedures  including  component 
placement,  equipment  and  procedures,  field 
erection  and  finishing  work,  utility  connection 
instructions  and  all  appropriate  on-site  inspection 
criteria  and  test  descriptions;  and 


778 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


b.  Organizational  provisions  for  field  repair  and 
disposal  of  rejects. 

R3.10.6     Permission     for     Inspection:  The 

manufacturer  shall  provide  the  BBRS  with  written 
permission,  signed  and  notarized,  for  the  State 
Enforcement  Agencies  to  inspect  his  manufacturing 
facilities,  his  products,  and  building  sites  under  his 
control  at  any  reasonable  time  without  prior 
announcement. 

R3.10.7  Inspections  by  the  State  Enforcement 
Agencies:  The  Compliance  Assurance  Manual  shall 
contain  detailed  plans  for  inspections  by  the  State 
Enforcement  Agencies  or  inspection  agency. 

PART  IH   APPROVAL      OF      INSPECTION 
AGENCIES 

780  CMR  R3.ll  REQUIREMENTS  FOR 
SUBMISSION 

An  inspection  agency  seeking  approval  shall 
submit  a  quadruplicate  application  to  the  BBRS 
which  shall  include  the  items  listed  in  780  CMR 
3.11. 

R3.11.1  Articles  of  Incorporation:  The  original 
Articles  of  Incorporation  of  the  agency  and  all 
subsequent  amendments  thereto,  as  filed  in  the  State 
of  Incorporation. 

R3.11.2  By-laws:  The  by-laws  of  the  organization, 
if  any. 

R3.11.3  Business  Affiliations  of  Members:    The 

names,  addresses  and  business  affiliations  of  all 
members  of  the  Board  of  Directors  and  of  top 
management  personnel. 

R3.11.4  Stock  :  Individual  interests  representing 
more  than  10%  of  the  outstanding  ownership 
reflecting  the  financial  interest  of  the  agency's 
Board  of  Directors  and  top  management  personnel. 

R3.1 1.5  Certifications:  Certification  by  the  agency 
that: 

a.  Its  Board  of  Directors,  as  a  body,  and  its 
technical  personnel,  as  individuals,  can  exercise 
independence  of  judgment;  and 

b.  Its  activities  pursuant  hereto  will  result  in  no 
financial  benefit  to  the  agency  via  stock 
ownership,  or  other  financial  interests  in  any 
producer,  supplier  or  vendor  of  products  involved, 
other  than  through  standard  published  fees  for 
services  rendered. 

R3.1 1.6  Experience  of  Directors:  Names,  years  of 
experience,  state  in  which  professionally  registered 
and  other  qualifications  of  the  directors  of  inspection 
or  evaluation  programs. 


R3.11.7  Experience  of  Employees:  Names  and 
years  of  experience  of  employees  practicing  in  the 
following  disciplines:  architecture,  structural 
engineering,  mechanical  engineering,  electrical 
engineering,  fire  protection  and  other  branches  of 
engineering;  the  state  in  which  each  is  registered  and 
the  service  each  performs. 

R3.11.8  Organization  Chart:  An  organization 
chart  showing  management  and  supervisory  persons 
including  the  number  of  graduate  engineers  and 
architects,  and  the  names  of  all  consulting  engineers 
or  architects,  designating  which  are  full-time  and 
which  are  part-time  employees. 

R3.11.9   Number   and    Location    of  Personnel: 

Number  and  location  of  factory  inspectors, 
supervisors,  and  other  technicians,  including 
evaluators  of  factory  inspectors  and  the 
qualifications  of  each  specialized  group,  including 
records  of  work  experience,  licenses  held  and  other 
pertinent  qualifications;  description  of  types  of  work 
each  group  and  each  technician  is  expected  to 
perform  and  the  qualifications  of  each  group  and 
each  technician  to  perform  the  work  assigned. 

R3. 11.10    Employees    Training    Programs:    An 

outline  of  the  training  program,  if  any,  of  the  agency 
to  assure  that  all  inspectors,  evaluators  and  other 
technicians  are  properly  trained  to  do  each  job 
assigned  to  them. 

R3.ll.ll  Employee  Supervision:  An  outline  of  the 
general  procedures  for  supervision  of  inspectors  and 
evaluators,  including  checking  and  evaluation  of 
their  work. 

R3. 11.12    Non-employees    Relationships:        All 

engineers,  technicians  and  other  personnel  who  will 
perform  services  for  the  organization  but  who  are 
not  employees  of  the  organization,  and  the 
supervisory  and  other  relationships  which  each  will 
have  to  the  agency. 

R3.ll.13  Products  Evaluated: 

Type  of  products,  components,  equipment,  structures 
and  other  items  which  the  organization  has 
evaluated,  tested  or  inspected  and  the  number  of 
years  of  experience  the  organization  has  had  with 
each,  and  the  type  of  codes,  standards,  specifications 
and  requirements  with  respect  to  which  the 
organization  has  had  experience  in  providing 
evaluation,  inspection  or  testing  services,  and  the 
number  of  years  experience  with  each. 

R3. 11.14  Frequency  Capability:  Description  of 
the  frequency  with  which  the  agency  is  capable  of 
performing  inspections  or  evaluations. 

R3. 11.15  State  Approved  in:  List  of  the  states  in 
which  the  agency  is  now  approved  to  inspect  or 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


evaluate  manufactured  buildings  or  manufactured 
building  components  or  parts  thereof  for  compliance 
with  approved  building  systems. 

780  CMR  R3. 12  PROCEDURES  FOR 
APPROVING  INSPECTION  AGENCIES 

R3.12.1  Qualifications:  Upon  the  recommendation 
of  the  State  Enforcement  Agencies,  the  BBRS  may 
approve  inspection  agencies  which  meet  the 
requirements  of  the  applicable  codes  and  780  CMR 
3.0  and  which  the  State  Administrative  Agencies 
find  otherwise  qualified  to  perform  the  functions 
proposed  to  be  delegated  to  them. 

R3.I2.2  Suitability  of  Application:  Prior  to  a  full 
evaluation  of  an  application  for  approval,  the  BBRS 
shall  determine  whether  such  application  is 
unsuitable  for  processing.  In  the  event  the 
application  is  found  to  be  suitable  for  processing,  the 
applicant  shall  be  notified  in  writing  of  such 
unsuitability  and  the  basis  thereof  within  30  days  of 
the  date  of  the  application  is  received  by  the  BBRS. 
In  such  event,  all  but  $25.00  of  the  fee  will  be 
returned,  and  the  rulings  of  unsuitability  shall  be 
without  prejudice.  Any  subsequent  submission  shall 
be  treated  as  a  new  application. 

R3.12.3  Approvals:  In  the  event  of  approval  of  the 
BBRS,  an  inspection  agency  shall  be  notified  by  a 
letter  from  the  BBRS  indicating  such  approval  and 
stating  specifically  the  functions  which  the  applicant 
has  been  approved  to  perform.  Such  approval  shall 
not  constitute  the  actual  delegation  of  such 
functions. 

780  CMR  R3. 13  SUSPENSION  AND 
REVOCATION 

R3.13.1  Grounds.  The  BBRS  may  suspend  or 
revoke  its  approval  of  any  inspection  agency  if  the 
approval  was  issued  in  error;  was  issued  on  the  basis 
of  incorrect  information;  was  issued  in  violation  of 
any  of  the  applicable  Codes  or  780  CMR  R3;  if  the 
inspection  agency  violates  any  of  the  applicable 
Codes  or  780  CMR  R3;  if  examination  discloses  that 
the  agency  failed  to  perform  properly;  or  for  such 
other  cause  as  may  be  deemed  sufficient  by  the  State 
Enforcement  Agencies  to  warrant  such  action. 

R3.13.2  Procedures: 

R3. 13.2.1  General:  If  the  BBRS  suspends  or 
revokes  the  approval  of  an  inspection  agency,  the 
inspection  agency  shall  be  given  notice  in  writing 
from  the  BBRS  of  the  suspension  or  revocation 
with  the  reasons  therefore  set  forth  therein. 
Manufacturers  being  evaluated  or  inspected  by 
such  agencies,  all  local  enforcement  agencies 
within  this  State,  and  the  State  Enforcement 
Agencies  shall  also  be  notified  in  writing  of  such 
suspension  or  revocation.      Such  notices  shall 


contain  instructions  to  the  manufacturer  and  to  the 
local  enforcement  agency  as  to  the  procedures  to 
be  followed  regarding  manufactured  buildings  or 
manufactured  building  components  previously 
certified  by  an  agency  whose  approval  has  been 
suspended  or  revoked. 

R3. 13.2.2  Records:  An  inspection  agency  whose 
approval  has  been  suspended  or  revoked  shall 
within  90  days  of  the  suspension  or  revocation 
deliver  to  the  custody  of  the  BBRS  the  originals 
of  all  records  required  to  be  maintained  during  the 
course  of  the  inspection  agency's  operations 
pursuant  to  the  applicable  codes  and  780  CMR 
R3.0 

R3. 13.2.3  Labels:  An  inspection  agency  for 
which  approval  has  been  suspended  or  revoked 
shall  within  90  days  of  the  suspension  or 
revocation  deliver  to  the  custody  of  the  BBRS  all 
labels  in  the  agency's  possession,  under  its 
control,  or  for  which  it  is  responsible  pursuant  to 
the  applicable  codes  and  780  CMR  3.0. 

PART  IV   RECIPROCITY 

If  the  BBRS  finds  that  the  standards  for  the 
manufacture  and  inspection  of  manufactured 
buildings  or  manufactured  building  components 
prescribed  by  statute  or  rules  and  regulations  of 
another  state,  governmental  agency  or  private 
agency  meet  the  objectives  of  the  applicable  codes 
and  780  CMR  3.0,  and  are  enforced  satisfactorily  by 
such  other  state  or  other  agency,  or  by  their  agents, 
the  State  Enforcement  Agencies  shall  accept 
manufactured  buildings  or  manufactured  building 
components  which  have  been  certified  by  such  other 
state  or  other  agency,  and  the  BBRS  shall  assure  or 
be  assured  that  the  appropriate  label  is  attached 
thereto.  The  standards  of  another  state  or  agency 
shall  not  be  deemed  to  adequately  be  enforced  unless 
such  other  state  or  agency  provides  for  notification 
to  the  Department  of  suspensions  or  revocations  of 
approvals  issued  by  that  other  state  or  agency  in  a 
manner  satisfactory  to  the  BBRS  and  State 
Enforcement  Agencies  and  so  notify  the  BBRS.  The 
BBRS  shall  notify  the  State  Enforcement  Agencies 
of  any  action  taken  under  780  CMR  R3.3. 13. 

780  CMR  R3.14  PROCEDURES  FOR 

GRANTING  OR  REFUSING  RECffROCTTY 

TO  ANOTHER  JURISDICTION 

R3.14.1  Evaluation:  The  State  Enforcement 
Agencies  may  evaluate  the  statute,  codes,  rules  and 
regulations  of  another  state  or  other  state  or  other 
agency  at  any  time. 

R3.14.2  Methods  of  Extending  Reciprocity:  If  the 

BBRS  find  that  the  standards  prescribed  by  the 
statute  or  rules  and  regulations  of  another  state  or 
another  agency  meet  the  objectives  of  the 
appropriate   codes   and   that   780   CMR   3.0   are 


780 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

MANUFACTURED  BUILDINGS,  BUILDING  COMPONENTS  AND  MOBILE  HOMES 


satisfactorily  enforced,  it  may  upon  the 
recommendation  of  the  State  Enforcement  Agencies, 
as  provided  in  780  CMR  3.2. 1,  extend  reciprocity  to 
that  jurisdiction  by: 

a.  Giving  notice  to  any  requesting  manufacturer; 

b.  Giving  notice  to  the  Administrative  Agency  of 
the  other  jurisdiction; 

c.  Giving  notice  to  the  State  Enforcement 
Agencies  and  all  local  enforcement  agencies  in 
this  state. 

R3.14.3  Rejections:  If  the  standards  of  the  other 
state  or  other  agency  do  not  meet  the  objectives  of 
the  appropriate  codes  or  are  inadequately  enforced, 
or  both,  reciprocity  shall  not  be  extended.  In  that 
event,  the  BBRS  shall  notify  any  requesting 
manufacturer  and  the  Administrative  Agency  of  the 
other  state  or  other  agency  of  the  refusal  and  the 
reasons  therefore. 

780  CMR  R3.15  PROCEDURES  FOR 

RECIPROCITY  CERTIFYING 

MANUFACTURED  BUILDINGS  OR 

BUILDING  COMPONENTS 

A  manufacturer  from  a  jurisdiction  to  which 
reciprocity  has  been  extended  shall  submit  to  the 
BBRS  evidence  that  his  building  system  and 
compliance  assurance  program  have  been  approved 
by  such  state  or  other  agency.  The  BBRS  shall 
verify  the  approval  and  shall  notify  the  State 
Enforcement  Agencies,  local  enforcement  agencies 
and  the  manufacturer  in  writing  of  such  verification 
and  that  properly  labeled  buildings  or  building 
components  of  his  manufacture  will  be  accepted. 

780  CMR  R3.16  SUSPENSION  AND 
REVOCATION 

The  BBRS  shall  suspend  or  revoke,  or  cause  to  be 
suspended  or  revoked,  the  acceptance  or  certification 
or  both  of  such  reciprocally  certified  manufactured 
buildings  or  manufactured  building  components  if 
the  State  Enforcement  Agencies  determine  that  the 
standards  for  the  manufacture  and  inspection  of 
which  manufactured  buildings  or  manufactured 
building  components  of  such  other  state  or  other 
agency  do  not  meet  the  objectives  of  the  appropriate 
codes  and  780  CMR  R3.0,  or  that  such  standards  are 
not  being  enforced  to  the  satisfaction  of  the  State 
Enforcement  Agencies.  If  such  other  state  or  other 
agency  or  its  agents  should  suspend  or  revoke  its 
approval  and  certification,  the  acceptance  of 
certification  or  both  granted  under  780  CMR  3.16 
shall  be  revoked  or  suspended  accordingly.  Notice 
to  the  State  Enforcement  Agencies,  local 
enforcement  agencies,  manufacturer  and  to  the 
Administrative  Agency  of  such  other  state  or  agency 
of  such  suspension  or  revocation  shall  be  in  writing 
with  the  reasons  for  such  suspension  or  revocations 
set  forth  therein.  Appeals  from  such  suspension  or 
revocations  shall  receive  timely  review. 


PART  V  APPEALS 

780  CMR  R3.17  HEARINGS 

All  hearings  shall  comply  with  the  applicable 
sections  of  the  applicable  codes  and  the  Rules  and 
Regulations  thereof  established  for  the  purpose  of 
appeal. 

PART  VI    SCHEDULE  OF  FEES 

780  CMR  R3.18  ESTABLISHMENT 

The  following  is  the  SCHEDULE  OF  FEES 
established  by  the  BBRS  for  certifying  manufactured 
buildings  or  manufactured  building  components. 
Fees  shall  be  made  payable  to  the  "Commonwealth 
of  Massachusetts  Board  of  Building  Regulations  and 
Standards"  and  shall  accompany  all  applications  for 
certification. 

R3.18.1  Compliance  Assurance  Programs  and 
Building  Systems:  An  initial  fee  of  $500.00  shall  be 
charged  each  manufacturer  for  its  certified 
compliance  assurance  program  for  each  plant 
desiring  certification.  There  shall  be  an  additional 
charge  of  $500.00  for  the  certified  building  system 
except  that  there  shall  be  no  such  additional  charge 
per  building  component.  The  maximum  fee  charged 
under  780  CMR  3.18  shall  be  $1,000.00  for  each 
manufacturing  plant. 

R3.18.2  Third  Party  Inspection  Agencies:     An 

initial  fee  of  $500.00  shall  be  charged  to  each  third 
party  inspection  agency. 

R3.18.3  Annual  Renewal  Fees: 

a  One  year  from  the  date  of  certification  of  the 
manufacturer  and  every  year  thereafter 
certification  is  in  effect,  there  shall  be  paid  an 
annual  renewal  fee  of  $500.00  for  each  such 
certification. 

b.  One  year  from  the  date  of  certification  of  the 
Third  Party  Inspection  Agency,  and  every  year 
thereafter  certification  is  in  effect,  there  shall  be 
paid  an  annual  renewal  fee  of  $250.00. 

R3.18.4  Labels 

a.  A  fee  of  $12.50  per  unit  of  a  manufactured 
building  shall  be  charged  for  each  label  issued  by 
the  BBRS. 

Note:  A  "unit"  as  used  in  780  CMR  3.18  shall 
mean  any  building  or  proportion  thereof  which 
is  towed  or  shipped  separately  to  be  somehow 
tied  together  at  the  site. 

b.  A  fee  of  $1.00  per  building  component  shall 
be  charged  for  each  label  issued  by  the  BBRS  for 
building  components. 

Note:  Manufacturers  of  building  components 
shall  be  permitted  to  use  any  labels  as 
approved  by  the  BBRS      If  such  labels  are 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

supplied  by  any  source  other  than  the  BBRS,  d.    Upon  satisfactory  proof  to  theBBRS  of  lost  or 

there  shall  be  no  charge  for  such  labels.  stolen  labels,  not  the  result  of  negligence,  labels 

c.    Mutilated  labels  may  be  replaced  at  the  option  maY  be  replaced  at  a  cost  of  $2.00  each. 

of  the  BBRS  at  a  cost  of  $2.00  each.  e-    Labels  sha11  be  Purchased  from  the  BBRS  by 

the  inspection  agency  or  manufacturer. 


782  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


780  CMR  R4 


USE  OF  NATIVE  LUMBER 


780CMRR4.1  ADMINISTRATION 
R4.1.1  Title:  As  authorized  by  St.  1972,  802, 


and 


in  accordance  with  780  CMR  123  establishing  the 
Construction  Materials  Safety  Board,  780  CMR  R4 
is  ■  adopted  for  Controlling  the  Use  of  Native 
Lumber. 

R4.1.2  Definitions  Unless  otherwise  expressly 
stated  in  780  CMR  the  following  terms  shall,  for  the 
purpose  of  780  CMR  R4,  have  the  meaning 
indicated  in  780  CMR  R4. 1 .2. 

BBRS:  State  Board  of  Building  Regulations  and 
Standards 

Board:   Construction  Materials  Safety  Board 

Native  Lumber:  Native  lumber  is  wood 
processed  in  the  Commonwealth  of 
Massachusetts  by  a  mill  registered  in 
accordance  with  the  regulations  of  the  BBRS. 
Such  wood  is  ungraded  but  is  stamped  or 
certified  in  accordance  with  the  requirements 
of  780  CMR  2303.1.1.  For  the  purpose  this 
definition,  native  lumber  shall  be  restricted  to 
use  in  one-and  two-story  dwellings,  barns, 
sheds,  agricultural  and  accessary  buildings  and 
structures  and  other  uses  as  permitted  by 
780  CMR  23. 

Person:  Individual,  partnership,  corporation, 
trust,  joint  venture,  etc. 

Wood  Producers:  Persons  or  corporations  in  the 
business  of  milling  wood  into  native  lumber 
within  the  Commonwealth  of  Massachusetts. 

R4.1.3  Registrants:  No  person  shall  engage  in  the 
producing  of  native  lumber  for  use  in  buildings  or 
structures  within  the  Commonwealth  of 
Massachusetts  unless  registered  by  the  BBRS. 

R4.1.4  Application  for  Registration:  Each  person 
desiring  to  obtain  registration  as  a  wood  producer  of 
native  lumber  shall  make  application  to  the  BBRS 
upon  such  form  and  in  such  manner  as  the  BBRS 
shall  prescribe  and  shall  furnish  evidence 
satisfactory  to  the  BBRS  that  he  is  qualified  to  be 
registered  in  accordance  with  780  CMR  R4. 

R4.1.5  Application  Fee:  Applications  shall  be 
accompanied  by  a  registration  fee  of  $25.00  This 
initial  registration  fee  shall  be  for  two  years. 
Registration  shall  be  reviewed  every  two  years  in 
accordance  780  CMR  R4  The  fee  thereafter  for  a 
year  renewal  shall  be  $10.00. 


R4.1.6  Renewals:  Registration  shall  be  valid  for 
two  years  and  shall  be  renewed  biennially.  Within 
30  days  before  the  expiration  date  of  any  such 
registration,  the  Administrator  of  the  BBRS  shall 
forward  to  each  person  so  registered  an  application 
form  for  renewal.  The  said  Executive  Director,  upon 
receipt  of  the  completed  form  and  fee,  shall  renew 
the  registration  for  a  period  of  two  years  or  notify 
such  applicant  of  his  refusal  with  reasons  thereof. 
Any  application  for  renewal  of  registration  which 
has  expired  shall  require  the  payment  of  a  new 
registration  fee. 

R4.1.7  Pre-qualifying  Agency:  The  BBRS  hereby 
designates  the  Massachusetts  Wood  Producers' 
Association  as  its  pre-qualifying  agency,  providing, 
however,  that  the  BBRS  may  revoke  such 
designation  at  any  time  and  may  designate  any  other 
agency  or  agencies  which  it  deems  qualified,  from 
time  to  time,  to  act  as  its  pre-qualifying  agency  for 
pre-examination  registration. 

R4.1.8  Penalties:  Any  such  person  who  fails  to 
comply  with  the  requirements  of  780  CMR  4  or 
who  files  a  false  report  shall  be  subject  to  the 
penalties  and  actions  as  prescribed  in  780  CMR  1 18. 

780  CMR  4.  2  REGISTRATION 

4.2.1  Stamp:  Each  person  registered  by  the  BBRS 
shall  be  issued  a  name  and  number  for  use  in 
stamping  or  certifying  the  native  lumber  which  he 
produces. 

4.2.2  Stamp  Contents:  Each  stamp  filed  with  the 
BBRS  shall  be  a  minimum  of  two  inches  by  four 
inches  with  a  minimum  of  36  pt.  letters  and  shall 
contain  the  following  information: 

a.  Name  of  native  lumber  producer; 

b.  Registration  number;  and 

c.  Species  of  wood. 

4.2.3  Stamp  Use:  Each  piece  of  native  lumber 
produced  shall  bear  the  stamp  so  registered  with  the 
BBRS. 

4.2.4  Stamp  -  Unlawful  Use:  Each  registered  mill 
shall  be  assigned  an  individual  number.  It  shall  be 
unlawful  to  use  such  registration  number  in  any  mill 
other  than  the  mill  so  registered. 

R4.2.5  Stamp  -  Manufacture:  Each  producer  shall 
be  responsible  for  the  manufacture  and  use  of  his 
stamp  in  accordance  with  the  requirements  of  the 
BBRS  and  7S0  CMR  R4. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


783 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  R43  REVOCATION  AND 
SUSPENSION  PROCEDURES 
R4.3.1  Revocation  and  Suspension:  The  BBRS  on 
its  own  initiative  or  upon  the  recommendation  of  the 
Construction  Materials  Safety  Board  may  suspend  or 
revbke  the  registration  of  any  such  mill  registered  in 
accordance  with  780  CMR  R4,  780  CMR  or  the 
standards  of  good  practice.  Notice  of  suspension  or 
revocation  of  such  registration  shall  be  in  writing 
with  the  reasons  for  suspension  or  revocation  clearly 
set  forth  therein,  and  served  in  accordance  with 
780  CMR  118.6. 

R4.3.2  Notice  and  Conference:  Prior  to 
suspension  or  revocation  of  the  registration  of  any 
such  mill  so  registered,  written  notice  of  such  intent 
shall  be  served  by  the  Construction  Materials  Safety 
Board  in  accordance  with  780  CMR  118.6.  Within 
ten  calendar  days  of  receipt  of  such  notice,  the 
affected  mill  may  request  a  conference  before  a  three 
member  panel  designated  by  the  Chairman  of  the 
Construction  Materials  Safety  Board,  who  will  hear 
facts  and  make  their  recommendations  to  the 
Construction  Materials  Safety  Board. 

R4.3.3  Effect  of:  Upon  suspension  or  revocation  of 
the  registration  of  any  such  mill  so  registered,  such 


mill  shall  immediately  cease  engaging  in  the 
stamping  or  certifying  of  native  lumber.  The  filing 
of  an  appeal  with  the  State  Building  Code  Appeals 
Board  shall  stay  such  suspension  or  revocation 
subject  to  780  CMR  122.3.2. 

780CMRR4.4  APPEALS 
R4.4.1  Building  Code  Appeals  Board:  Anyone 
aggrieved  by  the  decision  of  the  BBRS,  the 
Construction  Materials  Safety  Board,  the 
Massachusetts  Wood  Producers'  Association  or 
others  may  appeal  to  the  State  Building  Code 
Appeals  Board  in  accordance  with  780  CMR  122. 

780  CMR  R4.5  QUALIFICATION 
R4.5.1  Evaluation:  Evaluation  by  the  pre- 
qualifying  agency  shall  be  required  prior  to 
registration  of  a  mill  subject  to  780  CMR  R4.  The 
agency  shall  examine  and  evaluate  the  application  of 
all  mills  and  make  its  recommendations  to  the 
Construction  Materials  Safety  Board.  The 
Construction  Materials  Safety  Board  shall  make  its 
recommendations  to  the  BBRS  who  shall  act  on  the 
application  of  the  mill  so  requesting  registration. 


784 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR  R5 


CONSTRUCTION  SUPERVISORS 


780  CMR  R5  covers  the  licensing  rules  and  regulations  for  construction  supervisors  as  defined  in  780  CMR 
109.11. 


780  CMR  R5.1  GENERAL 
R5.1.1  Title:     As  authorized  by  M.G.L. 


143. 


§  94(i).  the  BBRS  herewith  establishes  the  Rules  and 
Regulations  for  Licensing  Construction  Supervisors. 

R5.1.2  Definitions:  Unless  otherwise  expressly 
stated  in  780  CMR  the  following  terms  shall,  for  the 
purpose  of  780  CMR  R5.  have  the  meaning 
indicated  in  780  CMR  R5. 1 .2: 

BBRS:  State  Board  of  Building  Regulations  and 
Standards 

Construction  Supervisor:  Any  individual  directly 
supervising  persons  engaged  in  construction, 
reconstruction,  alteration,  repair,  removal  or 
demolition  involving  any  activity  regulated  by 
any  provision  of  780  CMR.  Such  term  shall  also 
apply  to  persons  supervising  themselves. 

A  licensed  construction  supervisor  shall  be 
required  for  the  installation  of  all  manufactured 
one  and  two  family  homes  as  required  by 
780  CMR  3508.1.1. 

Licensed  Designee:  Any  individual  designated  by 
the  license  holder  to  be  present,  in  the  absence  of 
said  license  holder,  during  any  of  the  periods 
stated  in  780  CMR  R5.2. 12  Such  designee  shall 
also  hold  a  Construction  Supervisor's  License,  but 
his  name  or  license  number  need  not  be  contained 
on  the  building  permit  application. 

License  Review  Committee  (Committee):     The 

Committee(s)  established  by  the  Chairman  of  the 
BBRS  to  carry  out  the  disposition  of  complaints 
against  licensed  constructon  supervisors. 

Recognition:  The  approval  by  the  BBRS  of  an 
application  and  related  documents  by  one  desirous 
of  being  licensed  as  a  construction  supervisor. 

R5.1.3  Scope: 

1.  780  CMR  R5  shall  govern  the  testing  and 
licensing  of  individuals  who  are  found  to  possess 
the  requisite  qualifications  to  be  licensed  as 
qualified  to  have  charge  or  control  of 
construction,  reconstruction,  alteration,  repair, 
removal  or  demolition  of  buildings  or  structures. 


2  Except  for  those  structures  governed  by 
Construction  Control  as  regulated  by  780  CMR 
116.0,  any  individual  directly  supervising  persons 
engaged  in  construction,  reconstruction, 
alteration,  repair,  removal  or  demolition  involving 
the  structural  elements  of  buildings  and  structures 
shall  be  licensed  according  to  780  CMR  R5. 

R5.1.4    Administration  and  Enforcement     The 

BBRS  shall  administer  and  enforce  the  provisions  of 
780  CMR  R5.  The  BBRS  or  those  designated  by  it, 
shall  administer  examinations,  under  780  CMR  R5. 
of  persons  desirous  of  being  registered  as  qualified 
to  receive  a  license  as  a  construction  supervisor 

R5.1.5        License    Review    Committee         The 

Chairman  of  the  BBRS  shall  appoint  a  License 
Review  Committee,  hereafter  referred  to  as  the 
"Committee",  which  shall  consist  of  any  three 
members  of  the  BBRS  who  shall  serve  for  one  year 
or  until  their  successors  are  appointed,  whichever  is 
later  The  said  Chairman  shall  appoint  a  Chairman 
of  the  Committee  who  shall  serve  until  his  successor 
is  appointed  The  Chairman  of  the  BBRS  may 
establish  and  abolish  as  many  Committees  as  he/she 
feels  appropriate  from  time  to  time. 

R5.1.6  Meetings:  The  Committee  shall  meet  at 
such  times  as  the  Chairman  deems  it  necessary  to 
carry  out  its  function  established  herein  by  the 
BBRS 

R5.1.7  Cities  and  Towns: 

5.1.7.1  Existing  Licensed  Construction 
Supervisors:  (Historical  Note)  All  individuals 
directly  supervising  persons  engaged  in 
construction,  reconstruction,  alteration,  repair, 
removal  or  demolition  involving  structural 
elements  of  buildings  or  structures  who  are  duly 
licensed  and  qualified  on  January  1,  1981  within 
any  city  or  town  shall  be  allowed  to  continue  in 
such  capacity  under  the  Rules  and  Regulations 
established  by  such  jurisdiction  until 
December  31.  1981.  Such  duly  licensed  person 
shall  only  be  allowed  to  engage  in  such  practice 
only  within  the  city  or  town  granting  such 
licensing. 


9/19/97    (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


785 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  R52  REGISTRATION  AND 
LICENSING 

R5.2.1  Experience:  (Historical  Note)  Each 
applicant  for  license  must  prove  to  the  Board  that  he 
has  had  at  least  three  years  of  experience  in  building 
construction  or  design  in  the  field  in  which  he 
desires  to  be  licensed,  together  with  any  technical 
knowledge  the  Board  may  require  him  to  possess. 

R5.2.1.1  Other  Requisites:  Any  person  who 
met  one  of  the  following  requisites  shall  be 
licensed  by  the  Board  without  testing  until  July  1, 
1982. 

1 .  Filed  with  the  BBRS  prior  to  July  1,  1982 
an  application  and  applicable  documents 
including  an  affidavit  on  a  form  provided  by 
the  BBRS  attesting  to  his  meeting  the 
following  qualifications: 

a.  A  registered  professional  architect  or 
engineer;  or 

b.  A  four-year  undergraduate  degree  in  a 
field  related  to  building  construction  or 
design  and  at  least  one  year,  out  of  the 
previous  ten  years,  of  experience  in  the 
supervision  of  building  construction  or 
design;  or 

c.  At  least  three  years,  out  of  the  previous 
ten  years,  of  experience  in  the  supervision  of 
building  construction  or  design  and  a 
general  knowledge  of  the  quality  and 
strength  of  building  materials;  a  general 
knowledge  of  the  accepted  requirements  for 
building  construction,  fire  prevention,  light, 
ventilation  and  safe  exits;  and  a  general 
knowledge  of  other  equipment  and  materials 
essential  for  safety,  comfort  and 
convenience  of  the  occupants  of  a  building 
or  structure. 

R5.2.2  Examinations:  Examinations  shall  be  held 
only  by  appointment.  All  applications  must  be  filed 
in  accordance  with  the  Massachusetts  Constructon 
Supervisor  (MACS)  Candidate  bulletin  of 
Information. 

R5.2.3  License  Approval:  A  majority  vote  of  the 
members  of  the  Board  shall  be  required  to  grant  a 
license. 

R5.2.4  Expiration:  Licenses  issued  pursuant  to 
these  rules  and  regulations  shall  expire  three  years 
from  the  date  of  issuance  which  shall  be  noted  on 
said  license  and  may  be  renewed. 

A  renewal  of  an  original  license  shall  be  for 
periods  of  two  years  and  a  renewal  license  shall 
expire  two  years  from  the  date  of  issuance  which 
shall  be  noted  on  said  license  and  may  be  renewed. 

A  renewal  license  shall  not  be  issued  unless 
application  therefore  is  made  within  one  year  of  the 
date  of  expiration  of  the  most  recently  issued 
license.  Failure  to  submit  a  renewal  application  and 


to  acquire  a  license  within  this  time  period  shall  be 
cause  for  examination  or  re-examination 

R5.2.5  Fees:  Any  and  all  fees  charged  for 
examination,  for  license  fees,  or  for  licensed  renewal 
fees  shall  be  determined  by  the  Commonwealth  and 
enforced  by  the  BBRS  Examination  fees  are  to  be 
established  from  time  to  as  necessary. 

R5.2.5.1  Building  Official  Fees:  The  BBRS  shall 
grant  a  license  at  no  fee  to  any  building  official 
who,  as  a  condition  of  his  employment  requires 
such  license;  provided  that  such  person  meets  the 
necessary  qualifications  for  licensure  and 
provided  further,  that  such  license  shall  be 
authorized  for  use  only  during  the  course  of 
employment  and  shall  be  appropriately  stamped  to 
indicate  as  such. 

R5.2.6  Procedure  for  Obtaining  a  License: 

R5.2.6.1  Application:  Applications  shall  be 
submitted  on  forms  supplied  by  the  BBRS  or  its 
authorized  agent. 

R5.2.6.2  Forms:  The  applicable  forms  may  be 
mailed  to  the  appropriate  testing  agency  as 
detailed  in  the  Massachusetts  Candidates  Bulletin 
(MACS).  It  shall  be  the  responsibility  of  the 
applicant  to  assure  that  the  required  forms  are 
received  by  the  testing  agency.  All  forms  shall  be 
accompanied  by  the  required  license  fee 

R5.2.6.3  Records:  The  BBRS  shall  keep  a  copy 
of  the  application  and  a  computer  file  listing  all 
licensed  construction  supen'isors. 

R5.2.6.4  Notification   of  Examination   Date: 

Upon  receipt  of  a  fully  completed  application,  an 
examination  date  shall  be  set  and  the  applicant  so 
notified. 

R5.2.7  False  Statements:  Any  false  statement  on 
the  application  or  references  shall  be  sufficient 
reason  to  refuse  to  issue  a  license,  or  to  suspend  or 
revoke  a  license  if  issued 

R5.2.8  Cause  for  Suspension  or  Revocation:  Any 

false  statement  on  the  application  for  license,  or  in 
answer  to  any  subsequent  request  for  information, 
shall  be  cause  for  suspension  or  revocation  of 
license.  Any  violation  of  a  provision  of  780  CMR 
shall  be  cause  for  suspension  or  revocation  of  a 
license  as  the  committee  sees  fit,  or  any  false 
statement  as  identified  in  780  CMR  R5.2.7,  or  work 
performed  without  a  building  permit  as  identified  in 
780CMRR5.2.9.1.1 


R5.2.9     Procedure     for     Suspension     And/or 
Revocation  of  License: 

R5.2.9.1  Complaints:   Upon  receipt  of  a  written 
complaint    from   a   building    official,    or   upon 


786 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONSTRUCTION  SUPERVISORS  RULES  AND  REGULATIONS 


written  complaint  from  other  persons,  or  upon 
complaint  of  the  Board  itself,  the  License  Review 
Committee  in  its  discretion,  shall  determine 
whether  or  not  a  hearing  shall  be  held  It  shall  not 
be  considered  as  a  complaint  if  such  work  was 
performed  prior  to  his/her  being  licensed  or  prior 
to  January  1,  1982,  whichever  is  later. 

R5.2.9.1.1  Basis  of  Complaint:  Only  work 
related  to  a  specific  building  permit  shall  be  the 
basis  of  such  complaint-  Any  work  requiring  a 
building  permit  which  is  performed  without 
such  permit  shall  be  considered  cause  for 
suspension  or  revocation. 

R5.2.9.2    Hearings    on    Complaints:      If  the 

Committee  shall  so  determine  that  a  hearing  shall 
>be  held,  it  shall  give  at  least  seven  days  notice  to 
the  complainant  and  license  holder  in  accordance 
with  780  CMR  118  6  The  sending  of  notice  to 
the  address  recorded  on  the  records  of  the  BBRS 
shall  be  deemed  sufficient  notice  to  the  license 
holder 

R5.2.9.3  Notice  of  Hearing:  The  notice  of 
hearing  shall  contain: 

1 .  The  name  of  the  complainant. 

2.  A  copy  of  the  complaint. 

3.  The  date,  time  and  place  of  said  hearing. 
The  complete  file  of  complaint  is  available  for 

inspection  at  the  Office  of  the  BBRS  during  its 
regular  hours 

The  license  holder  may  present  oral  and  written 
evidence  to  refute  or  mitigate  any  charge 
contained  in  the  complaint  and  present  witnesses 
in  his  behalf. 

Anyone  may  be  represented  by  legal  counsel. 

All  license  holders  shall  have  his/her  license  in 
his  possession  at  the  time  of  the  hearing 

R5.2.9.4    Continuation    of    Hearings:       The 

Committee  in  its  discretion  may  continue  the  date 
for  hearing  upon  request  by  the  license  holder  or 
complainant  or  the  Committee  itself. 

R5.2.9.5  Timing  of  Decision:  The  Committee 
shall  make  a  decision  within  ten  days  after  the 
hearing.  A  written  decision  shall  be  issued  within 
30  days  of  the  hearing  date. 

R5.2.9.6  Vote  of  License  Review  Committee:  A 

vote  of  at  least  two  members  of  the  Committee  is 
required  to  make  a  decision  pursuant  to  780  CMR 
R5.2.3. 

R5.2.9.6.1  Decisions:  This  decision  shall  be 
final  and  binding  upon  the  license  holder  and 
the  complainant.  If  the  Committee  votes  to 
revoke  or  suspend  the  license  of  a  construction 
supen'isor  at  the  time  of  the  hearing,  the  holder 
shall  immediately  surrender  said  license  to  the 
Committee. 


R5.2.9.7  Suspension,  Revocation  or 
Continuance:  If,  after  notice  has  been  duly 
given,  a  licensee  shall  not  attend  a  hearing,  the 
Committee  may  in  its  discretion  immediately 
suspend/revoke  said  license  or  proceed  with  the 
hearing  so  scheduled  and  make  decision  on  the 
evidence  so  presented,  or  continue  the  hearing  to 
another  date. 

R5.2.9.8  Notice  of  Suspension  or  Revocation: 

In  the  event  that  the  Committee  votes  to  suspend 
or  revoke  said  license  pursuant  to  this  hearing,  the 
license  holder  upon  notice  of  the  decision  shall 
immediately  comply  with  the  said  orders.  A 
refusal  to  comply  shall  automatically  revoke  the 
licensee's  right  to  supervise  construction 

R5.2.9.8.1  Terms  of  Suspension:  Suspension 
bv  the  Committee  shall  be  for  a  definite  term. 
R5.2.9.8.2  Reapplication:  Any  licensee 
whose  license  has  been  revoked  by  the 
Committee  may  reapply  for  a  license  in 
accordance  with  these  Rules  and  Regulations 
only  after  seeking  and  receiving  approval  to 
reapply  from  the  Committee. 

R5.2.10  Appeal:  Any  person  aggrieved  by  a 
decision  of  the  Committee  may  appeal  such  decision 
to  a  court  of  law  or  equity  in  conformance  with 
M.G.L  c.  30A  §  14. 

R5.2.11  Change  of  Address  The  license  holder 
shall  have  the  responsibility  of  reporting  any  change 
of  address  and/or  change  of  circumstance  to  the 
BBRS  The  information  on  file  at  the  BBRS  shall  be 
deemed  accurate  unless  changed  by  the  license 
holder. 

R5.2.12    On-site   Presence    of  Supervisor:      A 

licensed  individual  or  a  licensed  designee  shall  be 
present    on  the   site   at   some   point   to   approve 
construction,  reconstruction,  alterations,  removal  or 
demolition  involving  the  following  work. 
! .    Excavation 

2.  Foundation  (pouring  or  other) 

3 .  Decking 

4.  Rough  framing 

5.  Finished  framing 

6.  Chimneys 

a.  Excavation/foundation. 

b.  At  the  top  of  the  smoke  chamber  and  support 
of  the  flue  liner. 

c.  When  erection  of  the  chimney  is  completed. 

Exception  A  licensed  construction  supervisor 
shall  be  required  for  installation  of  manufactured 
one  and  two  family  homes  as  required  by 
780  CMR  3508. 1.1. 

R5.2.13  Lost/stolen  Licenses:  License  holders  are 
required  to  keep  the  license  in  their  possession  at  all 
times  during  the  course  of  construction  at  any  and  all 


9/19/97    (Effective  2/28/97)  -  corrected  780  CMR  -  Sixth  Edition 


787 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


building  sites.  If  said  license  is  lost,  stolen  or 
mutilated,  it  shall  be  the  responsibility  of  the  license 
holder  to  notify  the  BBRS. 

R5.2.14     Requirement  to   Show  License:   Any 

building  official  may  require  the  license  holder  to 
produce  the  license  at  any  time  on  a  job  site 
R5.2.15  Responsibility  of  Each  License  Holder: 

R5.2.15.1  Responsibility  for  Work:  The  license 
holder  shall  be  fully  and  completely  responsible 
for  all  work  for  which  he  is  supervising.  He  shall 
be  responsible  for  seeing  that  all  work  is  done 
pursuant  to  780  CMR  and  the  drawings  as 
approved  by  the  Building  Official. 

R5.2.15.2   Responsibility  to  Supervise  Work: 

The  license  holder  shall  be  responsible  to 
supervise  the  construction,  reconstruction, 
alteration,  repair,  removal  or  demolition  involving 
any  activity  regulated  by  any  provision  of 
780  CMR  only  pursuant  to  780  CMR  and  all  other 
applicable  Laws  of  the  Commonwealth  even 
though  he,  the  license  holder,  is  not  the  permit 
holder  but  only  a  subcontractor  or  contractor  to 
the  permit  holder. 

R5.2.15.3   Notification    of  Violations:      The 

license  holder  shall  immediately  notify  the 
building  official  in  writing  of  the  discovery  of  any 
violations  which  are  covered  by  the  building 
permit. 

R5.2.15.4  Willful  Violation:  Any  licensee  who 
shall  willfully  violate  780  CMR  R5.2.15.1. 
5.2.15.2  or  52.15.3  or  any  other  Sections  of 
780  CMR  R5  and  any  procedures,  as  amended, 
shall  be  subject  to  revocation  or  suspension  of 
license  by  the  Committee. 

R5.2.16  Permit  Applications:  All  building  permit 
applications  shall  contain  the  name,  signature  and 


license  number  of  the  construction  supervisor  who 
is  to  supervise  those  persons  engaged  in 
construction,  reconstruction,  alteration,  repair, 
removal  or  demolition  as  regulated  by  780  CMR 
108.3.5  and  780  CMR  R5  in  the  event  that  such 
licensee  is  no  longer  supervising  said  persons,  the 
work  shall  immediately  cease  until  a  successor 
license  holder  is  substituted  on  the  records  of  the 
building  department. 

R5.2.17  GENDER  OF  TERMS:  The  term  "he"  as 
used  in  780  CMR  R5  shall  include  the  pronoun  "he" 

and/or  "she." 

780  CMR  R5 3  ADMINISTRATION 
R5.3.1  Identification:  The  BBRS  shall  issue  a  card 
or  a  certificate  or  other  form  of  identification. 

R5.3.2    Records  of  Licensees:  The  BBRS  shall 

maintain  a  computer  listing  which  will  be  available 
to  the  public  at  the  office  of  the  BBRS  containing  all 
licenses  issued  by  the  BBRS. 

R5.3.3  Examination:  The  Board  shall  determine 
whether  an  examination  shall  be  required,  or  shall  be 
oral  or  written  and  shall  determine  the  content  of  the 
examination,  if  applicable. 

R5.3.4  Subject  to  Rules,  Regulations  and 
Procedures:  All  persons  licensed  shall  be  subject  to 
these  regulations  as  well  as  other  rules,  regulations, 
and  procedures  promulgated  by  this  BBRS. 

R5.3.5  Fees:  Any  and  all  fees  charged  for  license 
fees,  examination  fees,  renewal  fees,  and  registration 
fees  shall  be  determined  by  the  Commonwealth  and 
enforced  by  the  BBRS.  Examination  fees  shall  be 
established  from  time  to  time  as  necessary. 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780CMR  R6 


REGISTRATION  AND  ENFORCEMENT  OF 
HOME  IMPROVEMENT  CONTRACTOR  PROGRAM 


FORWARD 

780  CMR  R6  covers  the  registration  of  home  improvement  contractors  and  subcontractors  and  enforcement  of  the 
requirements  of  M.G.L.  c  142A  as  they  pertain  to  home  improvement  contractors  and  subcontractors.  Other 
regulations  applicable  to  the  Home  Improvement  Contractor  program  include: 

201  CMR  14.00     Operation  of  the  home  improvement  arbitration  program  authorized  by  M.G.L.  c.    142A, 
promulgated  by  the  secretary  of  the  Executive  Office  of  Consumer  Affairs  and  Business  Regulations. 

201  CMR  15.00  Operation  of  the  home  improvement  guaranty  fund,  promulgated  by  the  secretary  of  the  Executive 
Office  of  Consumer  Affairs  and  Business  Regulations. 


780  CMR  R6.1  General  Provisions 

R6.1.1    Title 

R6.1.2    Definitions 

R6.1.3    Scope 

R6. 1 .4    Administration  and  Enforcement 

R6. 1 .4. 1    Director  responsibility 

R6. 1.4.2    Advisory  board 
R6. 1 .5    Persons  Who  Must  Register 

R6- 1.5.1    Filing  of  application 

R6. 1.5.2    Designated  individual 

R6. 1.5.3    Liability 
R6. 1 .6    Persons  Exempt  From  Registration 


780  CMR 

R6.2.1 

R6.2. 
R6.2 
R6.2 
R6.2 
R6.2 
R6.2 
R6.2.2 
R6.2 
R6.2 
R6.2 
R6.2 
R6.2.3 
R6.2.4 

R6.2 
R6.2 

R6.2.5 
R6.2 
R6.2 
R6.2 


R6.2  Registration  Procedure 

Applicant  Actions 

1.1  Application 

1.2  Supporting  documentation 

1.3  Mailing  address 

1.4  Certified  check/money  order 

1.5  Lost/destroyed  certificate 

1.6  Licensee  liability 
Director's  Action  on  Application 

2.1  Issuance  of  certificate 

2.2  Grounds  for  refusal  to  register 

2.3  Application  refused 

2.4  Record  retention 
Duration  of  Registration 

Fees  to  be  Paid  Upon  Registration  or 
Renewal 

4.1  Registration  and  renewal  fee 

4.2  Contribution  to  guaranty  fund  - 

initial  registration 
Responsibilities  of  Each  Registrant 

5.1  Changes  in  status 

5.2  Display  of  certificate  number 

5.3  Return  of  certificate 


780  CMR  R6.3  Enforcement  Procedure 

R6.3.1    Notification  of  Violation 
R6.3.2    Consideration  of  Factors 
R6.3.3    Letter  of  Reprimand 
R6.3.4     Suspension,  Revocation,  Administrative 
Penalties 
R6.3.4. 1    Hearing  procedure 


R6.3.5    Injunction,  Restitution 
R6.3.6    Fines  and  Criminal  Penalties 

780  CMR  R6.4  Enforcement  Actions 

R6.4. 1    Administrative  Penalties 

R6.4. 1 . 1    Allowable  actions 

R6.4.1.2    Pendency  of  claims 
R6.4.2    Fine",  and  Criminal  Penalties 

R6.4.2. 1    Sought  by  attorney  general  or 
district  attorney 

R6.4.2.2    Operating  without  certificate 

R6.4.2.3    Other  violations 
R6.4.3    Injunction,  Restitution 

R6.4.3.1    Order  from  superior  court 

R6.4.3.2    Director  bond  not  required 
R6.4.4    Permit  Requirements,  Prohibited  Acts 
and  Penalties 

R6.4.4.1    Permit  requirements 

R6.4.4.2    Prohibited  acts 

R6.4.4.3    Penalties 

R6.4.4.4    Deceptive  act 

780  CMR  R6.5  Contracts 

R6. 5 . 1    Contract  in  Writing 
R6.5.2    Contents  of  Contract 

R6.5.2. 1    Documents  and  information 

R6.5.2.2    Permit  notice 

R6.5.2.3    Acceleration  of  payment 

R6. 5 . 2 . 4    Copy  to  owner 

R6.5.2.5    Alternative  dispute  resolution 
R6.5.3    Dispute  Resolution 

R6.5.3.1    Court  action 

R6.5.3.2    Owner  right  to  arbitration 

R6  5.3.3    Contractor  right  to  arbitration 
R6.5.4    Validity  of  contract 

780  CMR  R6.6  Supplementary  Identification 
Cards 

R6.6  1    Definitions 

R.6.6.2    Certificates  of  registrants 

R.6.6.2.2    Non-Individual  Registrants 
R6.6.3    Fees 
R6  6.4    Expiration 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


789 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


780  CMR  R6.1  GENERAL  PROVISIONS 
R6.1.1     Title:     780  CMR  R6  is  authorized  and 
promulgated  by  the  administrator  of  the  State  Board 
of  Building  Regulations  and  Standards  under  the 
authority  of  M.G.L.  c.  142A. 

R6.1.2  Definitions: 

Application:  The  form  provided  by  the  director 
which,  along  with  other  documentation  and  fee(s) 
that  may  be  required,  must  be  duly  filed  to 
become  a  registered  home  improvement 
contractor  or  subcontractor. 

Advertisement:  Any  commercial  message  in  any 
newspaper,  magazine,  leaflet,  flyer,  catalog, 
display  space  in  the  telephone  book,  on  radio, 
television,  public  address  system,  or  made  in 
person,  by  letter  or  other  printed  material,  or  any 
interior  or  exterior  sign  or  display,  including  on  a 
vehicle,  which  is  delivered  or  made  available  to 
an  owner  by  a  registrant  in  any  manner 
whatsoever. 

Applicant:  Any  person  who  files  an  application  to 
become  registered  as  a  home  improvement 
contractor  or  subcontractor. 

BBRS:  The  State  Board  of  Building  Regulations  and 
Standards 

Certificate:  The  document  provided  to  the  registrant 
which  lists  the  certificate  number  and  other 
information  required  by  the  director. 

Certificate  number:  See  registration  number. 

Clear  and  Conspicuous:  The  material 
representation  being  disclosed  is  often  point  type 
and  is  so  presented  as  to  be  readily  noticed  and 
understood  by  a  reasonable  person.  Language  in 
the  body  of  a  contract  is  "conspicuous"  if  it  is  in 
larger  or  contrasting  type  or  color,  or  underscored. 

Contract:  Unless  specifically  noted  otherwise  in 
the  text,  a  written  agreement  between  a  home 
improvement  contractor  and  an  owner  contained 
in  one  or  more  documents  for  the  performance  of 
certain  residential  contracting  work,  including  all 
labor,  material,  goods  and  services  set  forth  under 
said  agreement  for  a  total  amount  exceeding 
$1,000.00. 

Contractor:  Any  person  who,  through  himself  or 
others,  undertakes,  offers  to  undertake,  purports  to 
have  the  capacity  to  undertake,  or  submits  a  bid 
for  construction  work.  (See  "home  improvement 
contractor") 


Director:  The  administrator  of  the  State  Board  of 
Building  Regulations  and  Standards,  an  agency 
within  the  executive  office  of  public  safety, 
established  by  M.G.L.  c.  6A,  §  19. 

Employee:  For  the  purposes  of  780  CMR  6  in 
determining  the  number  of  employees  of  an 
applicant  for  registration,  any  individual  engaged 
in  construction  related  activities  who,  in  the 
weekly  pay  period  prior  to  the  date  of  registration 
worked  20  or  more  hours  for  the  registrant  and  for 
whom,  the  registrant  withheld  or  was  required  to 
withhold  federal  or  state  income  taxes  and  who, 
during  the  same  pay  period,  was  not  otherwise 
paid  or  had  such  taxes  withheld  by  any  other 
registrant.  Included  would  be  all  construction 
workers,  supervisors,  sales  personnel,  designers, 
estimators,  active  partners  and  officers  of 
corporations. 

Fund:  The  residential  contractor's  guaranty  fund. 
See  "guaranty  fund". 

Fund  administrator:  the  administrator  of  the 
residential  contractor's  guaranty  fund,  appointed 
by  the  secretary  of  the  Executive  Office  of 
Consumer  Affairs  and  Business  Regulation. 

Guaranty  fund:  The  residential  contractor's 
guaranty  fund.  A  fund  out  of  which  an  owner,  as 
defined  herein,  aggrieved  by  a  registrant(s)  may 
be  paid  part  or  all  of  their  damages  under  rules 
and  regulations  promulgated  by  the  secretary  of 
the  Executive  Office  of  Consumer  Affairs  and 
Business  Regulation. 

Home  improvement  contractor:  Any  person  who 
owns  or  operates  a  contracting  business  who, 
through  himself  or  others,  undertakes,  purports  to 
have  the  capacity  to  undertake,  offers  to 
undertake,  or  submits  a  bid  for  residential 
contracting  work  to  an  owner,  as  such  work  is 
defined  in  780  CMR  6  and  M.G.L.  c.  142 A,  and 
such  work  for  each  project  is  in  a  total  amount  in 
excess  of  $1,000,  and  is  registered  or  required  to 
be  registered  in  accordance  with  M.G.L.  c.  142A 
and  780  CMR  6. 

Homeowner:   See  "owner". 

Local  consumer  group:  A  local  or  regional  agency 
which  deals  with  the  resolution  of  consumer 
problems  and  who  is  determined  eligible  by  the 
attorney  general  under  standards  set  by  the 
attorney  general  in  accordance  with  M.G.L.  c.  12, 
§11G. 

Mortgage  broker:  Any  person,  who,  for 
compensation  or  gain,  or  in  the  expectation  of 
compensation    or   gain,    directly    or    indirectly 


790 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


7S0  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONTRACTOR  REGISTRATION  AND  ENFORCEMENT  OF  HOME  IMPROVEMENT 

CONTRACTOR  PROGRAM 


negotiates,  places,  assists  in  placement,  finds  or 
offers  to  negotiate,  place,  assist  in  placement  of 
mortgage  loans  on  residential  property  for  others, 
or  as  otherwise  defined  in  M.G.L.  c.  255E. 

Mortgage  lender:  Any  person  engaged  in  the 
business  of  making  mortgage  loans,  or  issuing 
commitments  to  fund  mortgage  loans,  or 
accepting  applications  or  fees  associated  with  the 
making  of  mortgage  loans  which  are  secured  by  a 
mortgage  on  residential  property,  or  as  otherwise 
defined  in  M.G.L.  c.  25 5E. 

Mortgage  loan:  A  loan  to  any  person  made 
primarily  for  personal,  family,  or  household 
purposes,  secured  wholly  or  partially  by  a 
mortgage  on  a  residential  property,  or  as 
otherwise  defined  by  M.G.L  c.  255E. 

Owner:  Any  homeowner  of  a  building  which  is  an 
existing  building  at  the  time  of  a  contract  that  is 
owner  occupied,  containing  at  least  one  but  not 
more  than  four  dwelling  units,  or  a  tenant 
authorized  by  the  homeowner  thereof,  who  orders, 
contracts  for,  or  purchases  the  services  of  a 
contractor  or  subcontractor.  An  owner  occupying 
a  condominium  unit  in  a  building  containing  no 
more  than  four  dwelling  units  qualifies  as  an 
owner  under  this  definition,  provided  the  owner 
owns  a  total  of  not  more  than  four  condominium 
units.  A  condominium  association  does  not 
qualify  as  an  owner. 

Owner-occupied  The  residential  building  of  at  least 
one  but  not  more  than  four  dwelling  units  and 
occupied  by  the  owner  as  a  primary  residence. 

Permit:  For  the  purposes  of  7S0  CMR  R6,  any 

construction-related  permit,  excluding  any 
permits  required  by  the  owner  which  are  not 
considered  construction-related,  such  as  zoning, 
environmental,  historical  commission,  and  the 
like. 

Person:  Any  individual,  partnership,  corporation, 
society,  trust,  association,  or  any  other  legal 
entity. 

Registrant:  Any  duly  registered  home  improvement 
contractor  or  subcontractor. 

Registration  number:  The  number  assigned  to  the 
applicant  after  he  has  been  approved  for 
registration  by  the  director  and  the  Board  of 
Building  Regulations  and  Standards. 

Residential  contracting:  The  reconstruction, 
alteration,  renovation,  repair,  modernization, 
conversion,  improvement,  removal  or  demolition 
or  the  construction  of  an  addition  to  any  pre- 


existing owner-occupied  building  containing  at 
least  one  but  not  more  than  four  dwelling  units, 
which  building  or  portion  thereof  is  used  or 
designed  to  be  used  as  a  residence  or  dwelling 
unit,  or  to  structures  which  are  adjacent  and 
accessory  to  such  residence  or  building,  including 
but  not  necessarily  limited  to:  garages,  sheds, 
cabanas,  poolhouses,  gazebos. 

Salesperson:  any  person,  other  than  a  supplier  of 
materials  or  a  laborer,  who  solicits,  offers, 
negotiates,  executes,  or  otherwise  endeavors  to 
procure  by  any  means  whatsoever,  directly  or 
indirectly,  a  contract  for  residential  contracting 
services  from  an  owner  on  behalf  of  a  home 
improvement  contractor  or  subcontractor. 

Secretary:  The  secretary  of  the  Executive  Office  of 
Consumer  Affairs  and  Business  Regulations. 

Subcontract:  A  contract,  written  or  verbal,  in  any 
amount,  between  a  home  improvement  contractor 
and  a  subcontractor  or  between  two 
subcontractors  for  the  performance  of  any  part  of 
the  home  improvement  contractor's  or 
subcontractor's  contract. 

Subcontractor:  Any  person,  other  than  a  supplier 
of  only  materials,  who  enters  into  a  contract, 
written  or  verbal,  with  a  home  improvement 
contractor  for  the  performance  of  any  part  of  a 
home  improvement  contractor's  contract  with  an 
owner  for  residential  contracting,  or  who  enters 
into  a  contract  with  any  other  subcontractor  for 
the  performance  of  any  part  of  the  subcontractor's 
contract. 

R6.1.3   Scope 

R6. 1.3.1     M.G.L.  c.   142A  and  780  CMR  R6 

require  the  registration  of  persons  who  engage  in 
residential  contracting  work  as  defined  in 
780  CMR  R6  and  M.G.L.  c.  142A  after  July  1, 
1992,  and  define  the  requirements  of  M.G.L. 
c.  142 A  and  enforcement  of  these  requirements, 
as  they  pertain  to  home  improvement  contractors 
and  subcontractors. 

R6. 1.3.2  Except  for  those  persons  who  are 
specifically  exempt  from  the  provisions  of 
7S0  CMR  R6  and  M.G.L.  c.  142A  all  contractors 
and  subcontractors  who  engage  in  residential 
contracting  as  defined  in  780  CMR  R6  and 
M.G.L.  c.  142A  shall  be  subject  to  and  shall 
comply  with  780  CMR  R6  and  M.G.L.  c.  142A. 

R6.1.4  Administration  and  Enforcement: 

R6. 1.4.1  Director  responsibility:  The  director 
shall  promulgate  and  enforce  the  provisions  of 
780  CMR  R6  and  M.G.L.  c.  142A  as  to  all  home 


2/7/97    (Effective  2/28/97) 


780  CMR-  Sixth  Edition 


791 


780  CMR.    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


improvement  contractors  and  subcontractors  who 
are  registered  or  required  to  register. 

R6. 1.4.2  Advisory  board:  The  director  may 
appoint  an  advisory  board  which  may  review 
proposed  suspensions,  revocations,  and 
administrative  penalties  against  any  registrants, 
and  shall  make  recommendations  to  the  director 
relative  thereto.  The  advisory  board  shall  include 
six  members,  any  four  of  whom  will  constitute  a 
quorum;  the  fund  administrator,  a  representative 
of  the  attorney  general,  a  representative  of  a 
consumer  group  appointed  by  the  secretary,  a 
representative  of  the  Massachusetts  Homebuilders 
Association  who  is  a  registered  home 
improvement  contractor  or  subcontractor,  a 
Representative  of  the  National  Association  of  the 
Remodeling  Industry,  and  a  BBRS  staff  member. 

R6.1.5  Persons  Who  Must  Register: 

R6. 1.5.1  General:  All  home  improvement 
contractors  and  subcontractors,  as  defined  in 
7S0  CMR  R6,  except  those  exempt  in  780  CMR 
R6.1.6,  shall  register  with  the  director  by  filing  an 
application  prescribed  by  the  director. 

R6.1.5.2  Designated  individual:  In  the  case  of 
registration  by  a  corporation  or  partnership,  an 
individual  shall  be  designated  to  be  responsible 
for  the  corporation's  or  partnership's  residential 
contracting  work. 

R6.1.5.3  Liability:  The  corporation  or 
partnership  and  its  designee  shall  be  jointly  and 
severally  liable  for  the  payment  of  the  registration 
fee,  the  payment  to  the  guaranty  fund,  and  for 
violations  of  any  provisions  of  780  CMR  R6, 
including  actions  by  the  registrant's  employees, 
subcontractors  or  salespersons. 

R6.1.6  Persons  Exempt  From  Registration  or 
Renewal:  Any  person  exempt  from  registration 
under  780  CMR  R6.1.6,  and  does  not  voluntarily 
register,  is  not  subject  to  any  of  the  provisions  of 
780  CMR  R6  or  M.G.L.  c.  I42A.  Persons  exempt 
from  registration  are: 

1.  the  Commonwealth  or  its  political 
subdivisions; 

2.  any  school,  public  or  private,  offering  as  part 
of  a  vocational  education  program  courses  and 
training  in  any  aspects  of  home  construction  or 
home  improvements; 

3.  electricians,  plumbers,  architects  or  any  other 
persons  who  are  required  by  law  to  attain 
standards  of  competency  or  experience  as  a 
prerequisite  to  licensure  for  and  engaging  in  such 
trade  or  profession  and  who  are  acting  exclusively 
within  the  scope  of  the  profession  for  which  they 
are  currently  licensed  pursuant  to  such  law, 
construction  supervisors  excepted. 


4.  persons  dealing  in  the  sale  of  goods  or 
materials  who  neither  arrange  to  perform  nor 
perform  directly  or  indirectly  any  work  or  labor  in 
connection  with  the  installation  of  or  application 
of  the  goods  or  materials; 

5.  any  owner  personally  doing  residential 
contracting  work  on  his/her  own  home; 

6.  any  individual  who  performs  construction 
related  labor  or  services  for  a  home  improvement 
contractor  or  subcontractor,  for  wages  or  salary 
and  who  does  not  act  in  the  capacity  of  a  home 
improvement  contractor  or  subcontractor; 

7.  any  contractor  or  subcontractor  who  works  on 
one  residential  contracting  undertaking  or  project 
by  one  or  more  contracts  where  the  aggregate 
contract  price  to  the  owner  is  less  than  S1,000; 
provided,  however,  that  the  contract  is  not  in  an 
amount  of  less  than  $1,000  for  the  purpose  of 
evading  780  CMR  R6  or  M.G.L.  c.  142A. 

8.  any  person  who  engages  in  the  business  of  a 
home  improvement  contractor  or  subcontractor  on 
other  than  a  full-time  basis,  and  who  has  earned  in 
gross  revenues  from  residential  contracting  work, 
less  than  S5,000  in  the  previous  12-month  period; 

9.  any  person  acting  as  a  home  improvement 
contractor  or  subcontractor  who  was  enrolled  as  a 
full-time  student  in  a  secondary  school  or  college 
with  degree  granting  authority  from  the 
government  of  the  state  in  which  the  school  is 
located,  for  the  immediately  preceding  academic 
semester  and  is  also  enrolled  as  a  full-time  student 
for  the  next  academic  semester,  in  the  same  or  a 
similar  degree  granting  secondary  school  or 
college  provided  that  at  least  %  of  the  number  of 
employees  of  the  contractor  or  subcontractor  are 
similarly  enrolled  in  secondary  schools  or 
colleges  and  that  the  home  improvement 
contractor  or  subcontractor  does  not  reasonably 
expect  to  earn  or  does  not  in  fact  earn,  in  gross 
revenues,  more  than  $5,000  from  residential 
contracting  work; 

10.  persons  who  install  any  or  all  of  the 
following: 

•  central  heating, 

•  air-conditioning  systems, 

•  energy-conservation  devices,  or 

•  provides  conservation  services  conducted  by 
or  on  behalf  of  a  public  utility  under  a 
program  approved  by  the  department  of  public 
utilities; 

1 1 .  any  contractor  or  subcontractor  who  works 
exclusively  in  any  of  the  following  home 
improvement  areas: 

•  landscaping; 

•  interior  painting  or  wall  covering; 

•  finished  floor  covering,  including,  but  not 
limited  to,  carpeting,  vinyl,  tile,  non-structural 
hardwood; 

•  fencing  or  freestanding  masonry  walls; 

•  above-ground  swimming  pools; 


792 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


CONTRACTOR  REGISTRATION  AND  ENFORCEMENT  OF  HOME  IMPROVEMENT 

CONTRACTOR  PROGRAM 


•  shutter  or  awning  installation; 

•  ground  level  patios;  includes  flagstone, 
concrete,  block,  and  wood  set  directly  onto  the 
ground;  excludes  decks  which  are  supported 
above  ground. 

•  asphalt  and  driveway  installation  and 
maintenance. 

780  CMR  R6.2  REGISTRATION 
PROCEDURE 

R6.2.1   Applicant  Actions: 

R6.2.1.1  Application:  Each  applicant  for 
registration  as  a  home  improvement  contractor  or 
subcontractor  shall  submit  a  completed  copy  of  an 
application  form  supplied  by  the  director  and 
necessary  supporting  documents  to  the  director, 
along  with  such  fees  as  required  by  the  provisions 
of  780  CMR  R6.2.4,  and  M.G.L.  c.  142A. 

R6.2.1.2  Supporting       documentation: 

Supporting  documentation  shall  include,  as 
applicable: 

1.  For  corporations:  an  official  document 
which  lists  the  names  and  addresses  of  officers, 
directors,  and  major  stockholders  such  as:  a 
copy  of  the  articles  of  incorporation,  a  current 
annual  report  as  filed  with  the  Secretary  of 
State,  a  copy  of  the  registration  as  a  foreign 
corporation  filed  with  the  Secretary  of  State,  or 
any  other  documentation  which  lists  the  names 
and  addresses  of  officers,  directors,  and  major 
stockholders,  will  be  accepted  in  lieu  of  listing 
these  names  on  the  application. 

2.  For  partnerships:  either  a  copy  of  the 
current  partnership  agreement  containing  the 
requested  information,  or  listing  of  the  names 
and  addresses  of  all  partners  on  the  application 
form. 

3  For  all  non-corporate  applicants:  a  copy 
of  the  business  registration  certificate  filed 
with  a  city  or  town  pursuant  to  M.G.L.  c.  110, 
§  5,  if  applicable. 

R6.2.1.3  Mailing  address:  The  application, 
supporting  documentation  and  fees  may  be  mailed 
or  delivered  as  follows: 

Director 

Home  Improvement  Contractor  Registration 

One  Ashburton  Place,  Room  1301 

Boston,  MA  02108 

It  shall  be  the  responsibility  of  the  applicant  to 
assure  that  the  required  registration  material  is 
received  by  the  director. 

R6.2.1.4     Certified  check/money  order:     All 

applications  shall  be  accompanied  by  the 
registration  fee  or  by  evidence  of  exemption,  and 
by  the  fee  for  the  guaranty  fund.  Fees  shall  be  in 
the  form  of  a  money  order  or  certified  check. 
Two  money  orders  or  certified  checks  shall  be 


included  -  one  for  the  registration  fee,  if  required, 
and  one  for  the  guaranty  fund.  Make  checks  or 
money  orders  payable  to  the  Commonwealth  of 
Massachusetts. 

As  noted  in  780  CMR  R6.2.4.1.2,  licensed 
individual  construction  supervisors  and  individual 
motor  vehicle  repair  shops  who  desire  to  register 
are  exempt  from  the  registration  fee  only;  there 
are  no  exemptions  to  the  requirement  for  a 
contribution  to  the  guaranty  find. 

R6.2.1.5  Lost/destroyed      certificate      of 

registration:  Upon  receipt  of  a  nominal  fee  as 
established  by  the  Commonwealth,  and  a 
completed  affidavit  provided  by  the  director,  that 
a  certificate  of  registration  has  been  lost  or 
destroyed,  a  replacement  certificate  clearly 
identified  as  such,  shall  be  issued  by  the  director. 

R6.2.1.6  Licensee  liabilities:  The  provisions  of 
780  CMR  R6  and  those  of  M.G.L.  c.  142A  shall 
not  be  construed  to  relieve  or  lessen  the 
responsibility  of  any  person  registered  under 
780  CMR  R6  and  M.G.L.  c.  142A  or  licensed 
under  M.G.L.  c.  143,  §  94(i),  nor  shall  the 
Commonwealth  be  deemed  to  have  assumed  any 
such  liability  by  reason  of  the  issuance  of 
registration  or  licensure. 

R6.2.2  Director's  Action  on  Application: 

R6.2.2.1  Issuance  of  certificate:  Upon  receipt  of 
a  completed  application  form,  supporting 
documentation,  and  the  proper  fee(s)  therefor,  the 
director  shall: 

•  ascertain  whether  such  applicant  meets  all  of 
the  registration  requirements  and  there  are  no 
grounds  for  rejection  as  specified  in  780  CMR 
R6.2.2.2; 

•  if  all  requirements  are  met,  the  Director, 
within  30  days  of  receipt  of  the  application 
shall  assign  a  registration  number,  with  the 
approval  of  the  BBRS; 

•  prepare  and  send  by  first  class  mail  to  such 
applicant,  at  the  address  stated  on  the 
registration  form,  a  certificate  indicating  the 
applicant's  registration  number,  name,  address, 
name  of  the  entity  of  the  applicant,  and  such 
other  information  as  is  deemed  necessary  by 
the  director.  The  registration  certificate  is  not 
transferable  to  any  other  person. 

R6.2.2.2  Grounds  for  refusal  to  register  or 
renew:  No  application  for  registration  or  renewal 
conforming  to  780  CMR  R6  and  M.G.L.  c.  142A 
may  be  denied  except  for  a  finding  by  the  director 
that  the  applicant  has  done  one  or  more  of  the 
following  acts  which  are  grounds  for  denial  after 
the  effective  date  of  780  CMR  R6: 

1.  made    material    omissions    or    mis- 

representations    of     fact     on     the     home 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


780  CMR;    STATE  BOARD  OF  BUILDING  REGULATIONS  .AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


improvement  contractor  or  subcontractor 
application  for  registration  or  renewal  and 
supporting  documentation  or  on  an  application 
for  licensure  or  renewal  under  M.G.L.  c.  143, 
§  94(i).  (construction  supervisor  license); 

2.  failed  to  pay  either  the  registration  fee  or  the 
payment  to  the  fund  as  required  under 
780  CMR  R6.2.4. 

3.  failed  consistently  to  perform  contracts  or 
has  performed  said  contracts  in  an 
unworkmanlike  manner  or  has  failed  to 
complete  said  contracts  with  no  good  cause  or 
has  engaged  in  fraud  or  bad  faith  with  respect 
to  said  contracts; 

4.  failed  to  meet  or  has  violated  any  of  the 
requirements  for  registered  home  improvement 
contractors  or  subcontractors  as  defined  in 
780  CMR  R6,  or  has  performed  or  is 
attempting  to  perform  any  act  prohibited  by 
780  CMR  R6  and  M.G.L.  c.  142A. 

5.  is  under  suspension  or  revocation  of 
registration  as  a  home  improvement  contractor 
or  subcontractor; 

6.  has  failed  to  repay  the  guaranty  fund  for 
any  payments  made  by  the  fund  on  the 
registrant's  account. 

R6.2.2.3  Application  refused:  If  the  application 

is  refused,  the  director  shall,  within  thirty  days  of 

the  application,  notify  the  applicant  in  writing  by 

first  class  mail  of  the  reasons  for  the  rejection. 

R6.2.2.3.1:     If  applicable,  the  applicant  may 

correct    the    deficiencies    in    the    application 

material  and  return  the  corrected  data  to  the 

director  within  ten  days  of  the  date  of  mailing 

of  the  director's  notice  of  refusal,  who  will  then 

assign    a    registration    number    and    issue    a 

certificate. 

R6. 2.2.3. 2:  If  the  grounds  for  rejection  are 
based  upon  substantive  grounds  for  refusal  of 
780  CMR  R6.2.2.2,  and  M.G.L.  142A,  the 
applicant  may  request  that  the  director 
reconsider  the  application  as  submitted  by 
stating  his/her  reasons  therefore,  in  writing, 
within  ten  days  of  the  date  of  mailing  of  the 
notice  of  the  director's  rejection  of  the 
application. 

R6.2.2.4  Record  retention:  The  director  shall 
keep  a  record  of  the  date  the  application  and  all 
pertinent  documents  are  received.  In  addition,  the 
director  shall  keep  on  file,  in  convenient  form  and 
open  to  public  inspection,  all  applications  for 
registration,  copies  of  certificates  issued,  and  the 
names  of  all  home  improvement  contractors  or 
subcontractors  whose  registration  has  been 
revoked,  suspended  or  surrendered 


R6.2.3   Duration  of  Registration 

R6. 2.3.1  Initial  registration:  Each  such 
registration  shall  be  in  effect  for  two  years  from 
the  date  of  issuance,  unless  suspended  or  revoked 
prior  to  that  time,  as  provided  in  780  CMR  R6 
and  M.G.L.  c.  142A. 

R6. 2.3.2  Renewal  of  registration:  Not  less  than 
90  days  before  the  date  of  the  expiration  of  such 
registration,  the  director  shall  send  or  cause  to  be 
sent.  to  each  registered  contractor  or 
subcontractor,  at  the  address  on  record,  a  notice 
for  renewal  of  the  registration  and  a  copy  of  all 
forms  necessary  for  such  renewal,  by  first  class 
mail,  along  with  a  schedule  of  such  fees  as  are 
necessary  for  said  renewal.  Renewals  will  remain 
in  effect  for  two  years  from  date  of  renewal  if  not 
suspended  or  revoked  prior  to  that  time.  The 
responsibility  for  timely  renewal  of  registration 
remains  with  the  registrant,  notwithstanding  this 
notice  An  applicant  shall  submit  a  renewal 
application  with  fees  within  one  year  of  the 
expiration  date  of  the  registration.  Failure  to 
submit  a  renewal  application  within  this  time 
period  shall  subject  the  applicant  to  a  fee  equal  to 
the  amount  for  initial  registration. 

R6.2.4     Fees  to  be  Paid  Upon  Registration  or 
Renewal: 

R6.2.4.1  Registration  and  renewal  fee:     All 

home  improvement  contractors  and 
subcontractors,  except  those  that  are  exempt  from 
the  registration  or  renewal  fee  in  780  CMR 
R6  2  4  1.2,  shall,  at  the  time  of  registration  or 
renewal,  pay  to  the  Commonwealth,  a  fee  in  the 
amount  of  the  fee  then  being  charged  for  the 
construction  supervisor's  license  under  M.G.L. 
c.  143,  §94(i). 

R6.2.4.1.2     Exemptions  from   registration 

and  renewal  fee: 

1.  Every  individual  construction  supervisor 
licensed  by  the  BBRS  in  accordance  with 
M.G.L.  c.  143,  §  94(i),  and  every  individual 
motor  vehicle  repair  shop  registered  in 
accordance  with  M.G.L.  c.  100A,  §  2,  who 
desires  to  be  registered  or  renew  their 
registration  as  a  home  improvement 
contractor  or  subcontractor,  and  whose 
license  or  registration  fee  has  been  paid  and 
is  current,  shall  be  deemed  to  have  paid  the 
registration  fee  required  by  780  CMR 
R6.2.4.1. 

2.  If  the  applicant  is  a  corporation  or 
partnership  and  the  named  individual 
responsible  for  home  improvement 
contracting  work  is  a  licensed  construction 
supervisor  and  a  substantial  owner  (10%  or 
more  of  ownership),  the  applicant  entity  is 
exempt  from  the  registration  and  renewal  fee. 


794 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/2S/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONTRACTOR  REGISTRATION  AND  ENFORCEMENT  OF  HOME  IMPROVEMENT 

CONTRACTOR  PROGRAM 


R6.2.4.2  Contribution  to  guaranty  fund  -  initial 
registration:  At  the  time  of  initial  registration, 
contractors  and  subcontractors  shall  also  pay  to 
the  Commonwealth,  in  a  separate  certified  check 
or  money  order  from  the  above  stated  registration 
fee,  if  any,  a  fee  payable  to  the  guaranty  fund. 

R6.2.4.2.1  The  fee  paid  by  contractors  and 
subcontractors  to  the  guaranty  fund  shall  be 
determined  based  on  the  number  of  employees 
(active  construction-related  personnel)  of  the 
home  improvement  contractor  or 
subcontractor,  as  defined  in  780  CMR  R6. 1.2, 
on  the  date  of  initial  registration,  as  follows: 

1 .  Zero  to  3  employees  $  1 00.00 

2.  4  employees  up  to  and  including  10  $200.00 

3.  1 1  employees  up  to  and  including  30  $300.00 

4.  More  than  30  employees  $500.00 

R6.2.4.2.2:  The  fee  to  the  guaranty  fund  shall 
be  paid  by  every  registered  home  improvement 
contractor  and  subcontractor  regardless  of 
whether  such  registrant  is  exempt  from  paying 
the  registration  fee  because  of  the  home 
improvement  contractor  or  subcontractor's 
status  as  a  licensed  construction  supervisor  or 
registered  motor  vehicle  repair  shop  owner. 

R6. 2. 4.2.3:  Any  registrant  who  fails  to 
accurately  determine  the  number  of  employees 
and  pay  the  correct  fee  therefor  shall  be 
deemed  to  have  failed  to  pay  the  fees  required 
for  registration  and  shall  be  subject  to 
enforcement  action  by  the  director,  in 
accordance  with  780  CMR  R6.2.2.2,  4.1  and 
4.3. 

R6.2.4.2.4:  No  home  improvement  contractor 
or  subcontractor  shall  be  required  to  pay  the 
contribution  to  the  guaranty  fund  more  than 
once  unless  the  fund  administrator  determines 
that  the  amount  of  the  fund  is  insufficient  to 
maintain  it  at  a  level  commensurate  with 
claims  made  against  the  fund.  If  such  a 
determination  is  so  made,  after  conducting  a 
public  hearing,  the  director,  in  consultation 
with  the  fund  administrator,  may  assess  each 
registered  home  improvement  contractor  or 
subcontractor  an  appropriate  fee,  the  amount  to 
be  determined  by  the  commissioner  of 
administration  and  finance,  which  shall  not 
exceed  the  amount  of  the  original  assessment; 
provided,  however,  that  the  director  shall  not 
assess  any  registrant  more  than  once  in  any  12 
month  period. 

R6.2.5    Responsibilities  of  Each  Registrant: 

R6.2.5.1  Changes  in  status:  Each  registrant 
shall  be  responsible  for  reporting,  in  writing, 
within  thirty  days,  changes  in  trade  name  or 
address  or  additions  of  business  name(s),  and  any 


other  pertinent  changes  in  circumstances  to  the 
director. 

R6.2.5.2  Display  of  certificate  number:  Every 
contract,  building  permit  and  advertisement  for 
residential  contracting  as  defined  in  780  CMR  R6 
shall  display  the  home  improvement  contractor's 
or  subcontractor's  certificate  of  registration 
number. 

R6.2.5.3  Return  of  certificate:  Upon  the 
expiration,  termination  or  voluntary  surrender  of 
a  registration,  the  registrant  shall  deliver  the 
certificate  to  the  director  who  shall  cancel  the 
registration  and  endorse  the  date  of  expiration, 
termination  or  surrender.  In  such  case,  no  further 
residential  contracting  work  will  be  engaged  in  by 
the  contractor  or  subcontractor. 

780  CMR  R6_5  ENFORCEMENT 
PROCEDURES 

R6.3.1  Notification  of  Violation:  The  fund 
administrator  shall  notify  the  director  if  a  registrant 
fails  to  repay  the  fund  for  any  payment  made  from 
the  fund  to  an  owner  because  of  the  conduct  of  said 
registrant.  In  addition,  the  secretary,  attorney 
general,  district  attorney,  or  local  consumer  groups 
as  defined  in  780  CMR  R6.1.2,  shall  advise  the 
director  of  orders  resulting  from  arbitration  or  court 
action,  cr  other  significant  complaint  activity  against 
individual  registrants,  accompanied  by  a 
recommendation  for  enforcement  action  against  a 
registrant.  Significant  complaint  activity  shall 
include  but  not  necessarily  be  limited  to: 

1.  repeated  acts  prohibited  under  780  CMR 
R6.4.4; 

2.  a  flagrant  complaint  or  complaints  involving 
substantial  harm  to  an  owner  or  owners. 

Nothing  in  780  CMR  R6.3.1  shall  preclude  the 
director  from  initiating  enforcement  action  on  his 
own  initiative. 

R6.3.2  Consideration  of  Factors:  The  director, 
upon  receipt  of  the  notification  under  780  CMR 
R6.3.1  shall  consider  the  pertinent  factors  in  the 
particular  situation,  and  decide  what  enforcement 
action  in  accordance  with  780  CMR  R6.4,  if  any, 
shall  be  taken  against  the  registrant  considering, 
among  any  other  pertinent  factors,  the 
recommendations  of  the  secretary,  attorney  general, 
district  attorney,  and/or  the  local  consumer  group(s), 
the  severity  of  the  violation(s),  the  frequency  of 
repetitive  violations,  the  harm  to  the  complainant  or 
the  general  public,  and  the  impact  upon  the 
registrant 

R6.3.3  Letter  of  Reprimand:  The  director,  on  his 
own  initiative,  may  send  a  letter  of  reprimand  to  the 
registrant  containing  the  facts  of  the  situation,  which 
may  include  that  the  incident  has  been  noted  on  the 
registrant's  official  records,  and  the  possibility  of 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


795 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


more  severe  disciplinary  action  in  the  event  of 
repetitive  violations. 

R6.3.4  Suspension,  Revocation,  Administrative 
Penalty:  The  director  may  institute  a  suspension  or 
revocation  of  registrant's  certificate  of  registration, 
or  administrative  penalty  against  a  registrant,  subject 
to  the  following  hearing  provisions: 

R6.3.4.1  Hearing  procedure: 
R6.3.4.1.1  Notice  of  hearing: 

1.  The  director  shall  give  at  least  14  days 
notice  of  a  scheduled  hearing  to  the 
registrant,  and  all  parties  to  the  hearing  i.e., 
the  secretary,  the  attorney  general,  the 
district  attorney,  and/or  the  local  consumer 
group  from  whom  the  recommendation  for 
enforcement  action  was  received.  Notice  to 
the  registrant  will  be  deemed  sufficient  if  it  is 
mailed  to  the  most  recent  address  of  record  in 
the  director's  file. 

2.  The  notice  of  hearing  shall  contain,  at 
minimum: 

a.  The  nature  of  the  violation; 

b.  A  statement  of  the  enforcement  action 
recommendation; 

c.  The  date,  time  and  place  for  the 
hearing; 

d.  Notice  that  the  registrant  may  be 
represented  by  legal  counsel; 

e.  Advise  that  the  complete  investigation 
file  is  available  for  review  at  the  office  of 
the  director  during  regular  business  hours; 

f.  Notice  that  the  registrant  may  present 
written  and  oral  testimony  and  evidence  to 
mitigate  any  planned  enforcement  action. 

3.  The  hearing  will  be  conducted  by  the 
director  or  a  hearings  officer  appointed  by 
the  director. 

R6.3.4.1.2   Rescheduling  of  hearing:   The 

director,  at  his  discretion,  may  delay  and 
reschedule  the  date  for  such  hearing  upon 
written  request  of  the  registrant,  the  secretary, 
the  attorney  general,  a  district  attorney,  or  the 
involved  local  consumer  group,  provided  the 
request  is  received  not  less  than  seven  days 
prior  to  such  hearing. 

R6.3.4.1.3  Decision:  Following  the  close  of 
the  hearing,  the  director  shall  issue  a  written 
decision  on  the  violation  within  14  working 
days.  A  copy  of  the  decision  shall  be  sent  to 
the  registrant,  the  secretary,  the  attorney 
general,  the  involved  district  attorney  and  local 
consumer  group. 

R6.3.4.1.4  Appeal:  Any  party  to  the  hearing 
who  is  aggrieved  by  the  decision  may  appeal 
under  the  applicable  provisions  of  the 
Massachusetts  Administrative  Procedures  Act, 
M.G.L.  c.  30A. 


R6.3.5.  Injunctions,  Restitution:  The  director,  on 
his  own  initiative,  may  institute  court  action  in 
accordance  with  780  CMR  R6.4.3,  to  obtain  a 
permanent  or  temporary  injunction  or  an  order 
requiring  restitution  or  completion  of  a  home 
improvement  contractor's  contract  with  an  owner. 

R6.3.6  Fines  and  Criminal  Penalties:  The  attorney 
general  or  a  district  attorney  may  initiate  court 
action  on  his  own  initiative  in  accordance  with 
780  CMR  R6.4.2. 

780  CMR  R6.4  ENFORCEMENT  ACTIONS 
R6.4.1  Administrative  Penalties:  If  the  director 
determines  that  any  registrant  is  liable  for  a  violation 
of  any  of  the  provisions  of  780  CMR  R6  or  M.G.L. 
c.  142 A,  the  director  may  institute  one  or  more  of 
the  following  actions: 

R6.4.1.1  Allowable  actions: 

1.  suspend  the  registrant's  certificate  of 
registration  for  such  period  of  time  as  shall  be 
determined  by  the  director; 

2.  revoke  the  registrant's  certificate  of 
registration; 

3.  send  a  letter  of  reprimand  to  the  registrant; 

4.  assess  an  administrative  penalty  not  to 
exceed  $2,000,  payable  within  30  days  of  the 
date  of  the  order  of  assessment,  for  each 
violation  of  any  provisions  of  780  CMR  R6 
and  M.G.L.  c.  142A  committed  by  the  home 
improvement  contractor(s)  or  subcontractors) 
who  are  registered  or  required  to  be  registered 
under  780  CMR  R6.  This  penalty  shall  be 
deposited  to  the  fund. 

R6.4.1.2  Pendency  of  a  claim:  The  pendency  of 
a  claim  against  the  fund  shall  not  limit  the  director 
from  taking  enforcement  action  against  any 
registrant  pursuant  to  780  CMR  R6  or  M.G.L 
c.  142  A. 

R6.4.2  Fines  and  Criminal  Penalties: 

R6.4.2.1  Sought  by  attorney  general  or  district 
attorney:  Fines  and  imprisonment  specified  in 
780  CMR  R6  and  M.G.L.  c.  142A  may  be  sought 
by  the  attorney  general  or  a  district  attorney,  and 
such  fines  and  imprisonment  shall  be  in  addition 
to  any  administrative  penalty  otherwise  applicable 
thereto. 

R6.4.2.2  Operating  without  a  certificate:  Any 

home  improvement  contractor  or  subcontractor 
who  shall  knowingly,  willfully,  or  negligently 
operate  without  obtaining  a  certificate  of 
registration  as  required  by  780  CMR  R6  and 
M.G.L.  c.  142A  and  who  is  not  otherwise  exempt 
from  the  registration  requirements  or  any  home 
improvement  contractor  or  subcontractor  who 
continues  to  operate  after  revocation  of  or  during 
suspension  of,  or  who  had  failed  to  renew  his 


796 


780  CMR  -  Sixth  Edition 


2/7/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


CONTRACTOR  REGISTRATION  AND  ENFORCEMENT  OF  HOME  IMPROVEMENT 

CONTRACTOR  PROGRAM 


certificate  of  registration,  shall  be  punished  by  a  fine 
not  exceeding  $5,000  or  imprisonment  not 
exceeding  two  years  or  both. 

R6. 4.2.3  Other  violations:  Any  person  who 
knowingly  and  willfully  violates  any  of  the 
provisions  of  780  CMR  R6  or  M.G.L.  c.  142A, 
with  respect  to  which  a  greater  penalty  is  not 
otherwise  provided  by  the  provisions  of  780  CMR 
R6  or  M.G.L.  c.  142 A  or  by  any  other  law  may  be 
punished  by  a  fine  of  not  more  than  52,000  or  by 
imprisonment  for  not  more  than  one  year  or  both. 

R6.4.3  Injunctions,  Restitution: 

R6. 4.3.1     Order  from  superior  court:  If  the 

director  concludes  that  the  continuing  conduct  of 
any  person  alleged  to  be  in  violation  of  780  CMR 
R6  and  M.G.L.  c.  142 A  may  result  in  substantial 
or  irreparable  harm  to  any  citizen  of  the 
Commonwealth,  the  director  may  seek: 

1  a  permanent  or  temporary  injunction  with 
respect  to  the  conduct  from  the  superior  court 
of  any  county  in  which  the  alleged  violation  is 
occurring,  or  in  which  the  violator  has  its 
principal  place  of  business;  or 
2.  an  order  requiring  restitution  or  satisfactory 
completion  of  the  home  improvement 
contractor's  contract  with  an  owner. 

R6.4.3.2  Bond  not  required:  The  director  shall 
not  be  required  to  file  a  bond  or  to  show  a  lack  of 
an  adequate  remedy  at  law  when  seeking  an 
injunction  under  M.G.L.  c.  142A  against  any 
person,  association,  partnership,  or  corporation 
not  registered  under  780  CMR  R6  and  M.G.L. 
c.  142A. 

R6.4.4  Permit  Requirements,  Prohibited  Acts 
and  Penalties: 

R6.4.4.1  Permit  requirements:  All  building 
permits  for  residential  contracting  work  covered 
by  780  CMR  R6  and  M.G.L.  c.  142A  shall: 

1 .  clearly  state  that  persons  contracting  with 
unregistered  contractors  do  not  have  access  to 
the  guaranty  fund, 

2.  contain  the  registered  home  improvement 
contractor's  or  subcontractor's  certificate 
number. 

R6.4.4.2  Prohibited  acts:  The  following  acts 
are  prohibited  by  registered  home  improvement 
contractors  or  subcontractors,  and  those  required 
to  register  under  the  provisions  of  780  CMR  R6 
and  M.G.L.  c.  142A: 

1.  operating  without  a  certificate  of 
registration  issued  by  the  director; 

2.  abandoning  or  failing  to  perform,  without 
justification,  any  contract  or  project  engaged  in 
or  undertaken,  or  deviating  from  or 
disregarding  plans  or  specifications  in  any 
material  way  without  the  consent  of  the  owner. 


except  for  changes  in  plans,  specifications,  or 
construction  techniques  required  by  building 
regulations; 

3.  failing  to  credit  the  owner  any  payment 
they  have  made  to  the  contractor  or  his 
salesperson  in  connection  with  a  residential 
contracting  transaction; 

4.  making  any  material  misrepresentation  in 
the  procurement  of  a  contract  or  making  any 
false  promise  of  a  character  likely  to  influence, 
persuade  or  induce  the  procurement  of 
contract; 

5.  acting  directly,  regardless  of  the  receipt  or 
expectation  of  receipt  of  compensation  or  gain 
from  the  mortgage  lender,  in  connection  with 
a  residential  contracting  transaction  by 
preparing,  offering  or  negotiating  or  attempting 
to  or  agreeing  to  prepare,  arrange,  offer  or 
negotiate  a  mortgage  loan  on  behalf  of  a 
mortgage  lender; 

6  acting  as  a  mortgage  broker  or  agent  for 
any  mortgage  lender; 

7.  publishing,  directly  or  indirectly,  any 
advertisement  relating  to  residential 
contracting  which  does  not  contain  the  home 
improvement  contractor's  or  subcontractor's 
certificate  of  registration  number  or  which  does 
contain  an  assertion,  representation  or 
statement  of  fact  which  is  false,  deceptive,  or 
misleading; 

8.  advertising  in  any  manner  that  a  registrant 
is  registered  under  780  CMR  R6  unless  the 
advertisement  includes  an  accurate  reference  to 
the  home  improvement  contractor's  or 
subcontractor's  certificate  of  registration; 

9.  violating  any  of  the  building  laws  of  the 
Commonwealth  or  of  any  political  subdivision 
thereof; 

10.  misrepresenting  a  material  fact  by  an 
applicant  in  obtaining  a  certificate  of 
registration; 

1 1 .  failing  to  notify  the  director  of  any  change 
of  trade  name  or  address  as  required  by 
780  CMR  R6. 2.5.1; 

12.  conducting  a  residential  contracting 
business  in  any  name  other  than  the  one  in 
which  the  home  improvement  contractor  or 
subcontractor  is  registered; 

13.  failing  to  pay  for  materials  or  services 
rendered  in  connection  with  his/her  operating 
as  a  home  improvement  contractor  or 
subcontractor  where  he/she  has  received 
sufficient  funds  as  payment  for  the  particular 
construction  work,  project  or  operation  for 
which  the  services  or  materials  were  rendered 
or  purchased, 

14.  failing  to  comply  with  any  order,  demand 
or  requirement  lawfully  made  by  the  director 
or  fund  administrator  under  and  within  the 
authority  of  780  CMR  R6  and  M.G.L.  c.  142A; 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


797 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


15.  demanding  or  receiving  payment  in 
violation  of  780  CMR  R6.5.2.  item  5,  6,  or 
5.2.2; 

16.  violating  any  other  provisions  of 
780  CMR  R6  and  M.G.L.  c.  142A. 

17.  failing  to  pay  to  the  guaranty  fund  in  full, 
including  interest,  any  amount  paid  from  said 
fund  because  of  the  conduct  of  the  registrant 

18.  any  of  the  grounds  for  refusal  to  register 
or  renew  in  780  CMR  R6.2.2.2  are  also 
considered  prohibited  acts. 

19.  failing,  within  21  days,  to  comply  with,  or 
advise  the  owner  of  intent  to  comply  with,  or 
appeal  the  decision  of,  an  arbitrator  as  provided 
for  in  M.G.L.  c.  I42A  and  201  CMR  14:00. 

20.  failing  to  display  the  registration  number 
on  every  contract,  building  permit  and 
advertisement  as  required  by  780  CMR 
R6.5.2. 1  item  2,  R6.4.4. 1  item  2,  R6.4.4.2  item 
7,  andR6.4.4.2item8. 

R6.4.4.3  Penalties:  Violations  of  780  CMR  R6 
or  M.G.L.  c.  142A  shall  subject  the  violator  to  the 
administrative  sanctions  of  780  CMR  R6.4. 1  and 
to  criminal  prosecution  or  other  court  action  as 
prescribed  in  780  CMR  R6.4.2  and  4.3. 

R6.4.4.4  Deceptive  act:  Violations  of  any  of  the 
provisions  of  780  CMR  R6  and  M.G.L.  c.  142A 
shall  constitute  an  unfair  or  deceptive  act  under 
the  provisions  of  M.G.L.  c.  93  A. 

780  CMR  R6.5  CONTRACTS 
R6.5.1     Contract  in  Writing:     Every  agreement 
between  a  home  improvement  contractor  and  an 
owner  to  perform  residential  contracting  services  in 
an  amount  in  excess  of  SI, 000  shall  be  in  writing. 

R6.5.2  Contents  of  Contract: 

R6. 5.2.1  Documents  and  information:  Every 
agreement  to  perform  residential  contracting 
services  in  excess  of  $1,000  shall  include,  but  not 
be  limited  to,  the  following  documents  and 
information: 

1 .  the  complete  agreement  between  the  owner 
and  the  contractor  and  a  clear  description  of 
any  other  documents  which  are  or  shall  be 
incorporated  into  said  agreement; 

2.  the  full  names,  federal  ID  number,  if 
applicable,  addresses  (exclusive  of  post  office 
box  addresses),  registration  number  of  the 
home  improvement  contractor,  the  name(s)  of 
the  salesperson(s),  if  any,  who  solicited  or 
negotiated  the  contract  and  the  date  when  said 
contract  was  executed  by  the  parties; 

3.  the  date  on  which  the  work  under  the 
contract  is  scheduled  to  begin  and  the  date  on 
which  said  work  is  scheduled  to  be 
substantially  completed; 


4.  a  detailed  description  of  the  work  to  be 
done  and  the  materials  to  be  used; 

5.  the  total  amount  agreed  to  be  paid  for  the 
work  to  be  performed  under  the  contract; 

6.  a  time  schedule  of  payments  to  be  made 
under  said  contract  and  the  amount  of  each 
payment  stated  in  dollars,  including  all  finance 
charges,  if  any.  Any  deposit  required  under  the 
contract  to  be  paid  in  advance  of  the 
commencement  of  work  under  said  contract 
shall  not  exceed  the  greater  of  Vb  of  the  total 
contract  price  or  the  actual  cost  of  any  material 
or  equipment  of  a  special  order  or  custom 
made  nature,  which  must  be  ordered  in 
advance  of  the  commencement  of  the  work,  in 
order  to  assure  that  the  project  will  proceed  on 
schedule.  No  final  payment  shall  be  demanded 
until  the  contract  is  completed  to  the 
satisfaction  of  the  parties  thereto; 

7.  the  signature  of  all  parties  shall  be  affixed 
to  the  contract; 

8.  there  shall  be  a  clear  and  conspicuous 
notice  appearing  in  the  contract  stating: 

a.  that  all  home  improvement  contractors 
and  subcontractors  shall  be  registered  by  the 
director  and  that  any  inquiries  about  a 
contractor  or  subcontractor  relating  to  a 
registration  should  be  directed  to: 

Director 

Home  Improvement  Contractor  Registration 

One  Ashburton  Place,  Room  1301 

Boston,  MA  02108 

(617)727-8598 

b.  the  registration  number  of  the  home 
improvement  contractor  on  the  first  page  of 
the  contract. 

■  c.  the  owner's  three-day  cancellation  rights 
under  M.G.L.  c.  93,  §  48;  M.G.L.  c.  HOD, 
§  10  or  M.G.L.  c.  255D,  §  14,  as  may  be 
applicable. 

d.  all  warranties  and  the  owner's  rights  under 
the  provisions  of  780  CMR  R6  and  M.G.L. 

c.  142  A; 

e.  in  ten  point  bold  type  or  larger,  directly 
above  the  space  provided  for  the  signature, 
the  following  statement: 

DO  NOT  SIGN  THIS  CONTRACT  IF  THERE 
ARE  ANY  BLANK  SPACES 
f   whether  any  lien  or  security  interest  is  on 
the    residence    as    a    consequence    of  the 
contract; 

(9)  an  enumeration  of  such  other  matters  upon 
which  the  owner  and  the  contractor  may 
lawfully  agree,  provided,  however  that  no  such 
agreement  may  waive  any  rights  conveyed  to 
the  owner  under  the  provisions  of  780  CMR 
R6  and  M.G.L.  c.  142A; 

(10)  any  other  provision  otherwise  required 
by  the  applicable  laws  of  the  Commonwealth. 


798 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CONTRACTOR  REGISTRATION  AND  ENFORCEMENT  OF  HOME  IMPROVEMENT 

CONTRACTOR  PROGRAM 


R6.5.2.2  Permit  notice:  Any  contract  entered 
into  between  a  home  improvement  contractor  and 
an  owner  shall  contain  a  clause  informing  the 
owner  of  the  following: 

1 .  any  and  all  necessary  construction-related 
permits; 

2.  that  it  shall  be  the  obligation  of  the  home 
improvement  contractor  to  obtain  such  permits 
as  the  owner's  agent; 

3.  that  owners  who  secure  their  own 
construction-related  permits  or  deal  with 
unregistered  contractors  will  be  excluded  from 
the  guaranty  fond  provisions  of  MG.L. 
c.  142  A; 

R6.5.2.3  Acceleration  of  payment:  No  contract 
shall  contain  an  acceleration  clause  under  which 
any  part  or  all  of  the  balance  not  yet  due  may  be 
declared  due  and  payable  because  the  holder 
deems  himself  to  be  insecure  However,  where  the 
contractor  deems  himself  to  be  insecure  he/she 
may  require  as  a  prerequisite  to  continuing  said 
work  that  the  balance  of  funds  due  under  the 
contract,  which  are  in  the  possession  of  the  owner, 
shall  be  placed  in  a  joint  escrow  account  requiring 
the  signatures  of  the  home  improvement 
contractor  and  owner  for  withdrawal. 

R6.5.2.4  Copy  to  owner:  At  the  time  of  signing, 
the  owner  shall  be  furnished  with  a  copy  of  the 
contract  signed  by  both  the  home  improvement 
contractor  and  the  owner.  No  work  shall  begin 
prior  to  the  signing  of  the  contract  and  transmittal 
to  the  owner  of  a  copy  of  such  contract. 

R6.5.2.5  Arbitration:  Any  contract  entered  into 
between  a  home  improvement  contractor  and 
owner  may  provide  that  the  home  improvement 
contractor  may  initiate  alternative  dispute 
resolution  through  any  private  arbitration  services 
approved  by  the  secretary,  as  provided  in  M.G.L. 
c.  142A;  provided,  that  said  alternative  dispute 
resolution  provision  is  clearly  and  conspicuously 
disclosed  in  the  contract,  in  language  designated 
by  the  secretary,  and  that  each  party  separately 
signs  and  dates  the  provision,  thereby  assenting  to 
the  procedure.  The  following  language  and  format 
is  acceptable: 

THE  CONTRACTOR  AND  THE 
HOMEOWNER  HEREBY  MUTUALLY 
AGREE  IN  ADVANCE  THAT  IN  THE 
EVENT  THE  CONTRACTOR  HAS  A 
DISPUTE  CONCERNING  THIS 

CONTRACT,  THE  CONTRACTOR  MAY 
SUBMIT  SUCH  DISPUTE  TO  A  PRIVATE 
ARBITRATION  SERVICE  WHICH  HAS 
BEEN  APPROVED  BY  THE  SECRETARY 
OF  THE  EXECUTIVE  OFFICE  OF 
CONSUMER  AFFAIRS  AND  BUSINESS 
REGULATIONS  AND  THE  CONSUMER 
SHALL  BE  REQUIRED  TO  SUBMIT  TO 


SUCH  .ARBITRATION  AS  PROVIDED  IN 

M.G.L.  C.142A. 


Contractor 


Owner 

NOTICE:  THE  SIGNATURES  OF  THE 
PARTIES  ABOVE  APPLY  ONLY  TO  THE 
AGREEMENT  OF  THE  PARTIES  TO 
ALTERNATIVE  DISPUTE  SETTLEMENT 
INITIATED  BY  THE  CONTRACTOR  THE 
OWNER  MAY  INITIATE  ALTERNATIVE 
DISPUTE  RESOLUTION  EVEN  WHERE  THIS 
SECTION  IS  NOT  SEPARATELY  SIGNED  BY 
THE  PARTIES 

R6.5.3  Dispute  Resolution 

R6.5.3.I  Court  action:  Any  party  may  bring  an 
action  to  enforce  any  provisions  of  780  CMR  R6 
and  M.G.L.  c.  142A  in  superior  court,  the  district 
court,  or  the  small  claims  division  of  the  district 
court. 

R6.5.3.2  Owner  right  to  arbitration:  In  the 

alternative,  an  owner  may  request  that  a  dispute 
resulting  from  and  relating  to  residential 
contracting  be  decided  under  the  terms  of  a 
private  arbitration  service  approved  by  the 
secretary. 

R6.5.3.3  Contractor  right  to  arbitration:  The 

home  improvement  contractor  may  initiate  dispute 
resolution  through  private  arbitration  services 
approved  by  the  secretary,  provided:  that  the 
contract  between  the  owner  and  the  home 
improvement  contractor  contains  such  a  clause  as 
provided  in  780  CMRR6.5.2.5. 

R6.5.4  Validity  of  contract:  Contracts  which  fail 
to  comply  with  the  requirements  of  780  CMR  R6 
and  M.G.L.  c.  142A  shall  not  be  invalid  solely 
because  of  noncompliance. 

780  CMR  R6.6  SUPPLEMENTARY 
roENTEFlCATION  CARDS 

R6.6.1  Definitions 

Certificate  of  registration:  The  document  issued  by 
the  Director  showing  the  registrant's  certificate 
number  and  other  data  as  required  by  the  director. 

Identification  card:  The  document  issued  to  the 
responsible  individual  or  to  one  or  more 
individuals  in  the  employ  of  the 
applicant/registrant. 

R6.6.2  Certificates  of  registrants:  For  applicants 
registering     as     individuals,     the     certificate     of 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


799 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


registration  and  identification  card  will  be  issued  in 
the  name  of  the  registrant.  Only  one  identification 
card  will  be  issued  to  individual  registrants. 

R6.6.2.2  Non-Individual  Registrants: 

R6.6.2.2.1  If  the  Applicant  is  a  corporation, 
partnership,  proprietorship  with  a  fictitious 
name,  or  other  non-individual  entity,  the 
certificate  of  registration  and  the  initial 
identification  card  will  bear  the  name  of  the 
registrant  entity  and  the  individual  responsible 
for  the  home  improvement  residential 
contracting  activities  of  the  registrant. 
R6.6.2.2.2  Supplementary  identification  cards 
may  be  issued,  upon  request  of  the  registrant, 
to  named  officers,  partners,  of  key  individuals 
in  the  employ  of  the  registrant  under  the 
certificate  of  registration  number  of  the 
applicant    entity,    upon    submission    of   the 


appropriate  request  form  and  fee.  The 
applicant  is  responsible  for  the  prompt  return 
of  individual  identification  cards  if  there  is  a 
change  in  status  of  individuals  holding  such 
supplementary  cards. 

R6.6.3  Fees:  For  each  additional  identification  card 
request  in  accordance  with  780  CMR  R6.2.2.1,  an 
additional  fee  per  card  in  an  amount  of  $10  00  must 
accompany  the  request  for  additional  cards. 

R6.6.4  Expiration:  Supplementary  cards  will 
expire  on  the  same  date  as  the  expiration  date  of  the 
registrant  entity,  and  must  be  renewed  along  with  the 
renewal  of  the  registrant  entity's  registration  by 
submission  of  the  required  application  and  fee  of 
$10.00  per  card  requested. 


800 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR  R7 

CERTIFICATION  OF  INSPECTORS  OF  BUILDINGS,  BUILDING 
COMMISSIONERS  AND  LOCAL  INSPECTORS 

FORWARD 

Contained  herein  are  the  RULES  and  REGULATIONS  for  the  certification  of  all  inspectors  of  buildings, 
building  commissioners  and  local  inspectors  (collectively  referred  to  as  building  code  enforcement  officials) 
of  the  Board  of  Building  Regulations  and  Standards  (BBRS).  In  accordance  with  M.G.L.  c.  143  §§3  and  94, 
the  BBRS  is  authorized  to  adopt  rules  and  regulations  which  govern  the  administration  of  such  program. 

780  CMR  R7  covers  the  certification  rules  and  regulations  for  inspector  of  buildings,  building 
commissioners  and  local  inspectors  as  defined  in  M.G.L.  c.  143,  §  3,  and  780  CMR  105. 

General  Provisions 

R7.1.1  Title 

R7.1.2  Definitions 

R7.1.3  Scope,  intent 

R7. 1  4  Powers  and  duties 

R7.1.5  Inspector  Certification  Advisory  Committee  (Building  Official  Certification  Committee) 

R7  1  6  Categories  of  certification 

R7. 1  7  Certifications  required 

Requirements  for  Initial  Certification 

R7.2.1    Application 

R7.2.2    Building  Code  Enforcement  Officials  in  office  as  of  November  12,  1992 

R7.2.3    After  November  12,  1992 

R7.2.4    Requirements  for  certification  as  a  local  inspector 

R7.2.5    Requirements  for  certification  as  an  inspector  of  buildings/building  commissioner 

Requirements  for  Maintenance  of  Certification 

R7. 3 . 1    Continuing  education 
R7.3.2    Renewal  of  certification 

Procedures  for  Complaints 

R7.4.1    Complaints 

R7.4.2    Revocation  of  certificates  and  alternate  sanctions 

R7.4.3    Violations  and  penalties 

780  CMR  R7.1  GENERAL  PROVISIONS  R7.1.3  Scope,  intent:  780  CMR  R7  shall  control  all 

R7.1.1  Title  780  CMR  R7  entitled  "Certification  of  matters  relatin§  to  qualifications  and  certification  of 

Inspectors  of  Buildings,  Building  Commissioners  ^  buMmS  code  enforcement  officials  engaged  in  or 

and    Local    Inspectors"    (hereinafter    collectively  to  be  engaged  m  the  admimstration  and  enforcement 

referred  to  as  Building  Code  Enforcement  Officials)  of  780  CMR-  categories  of  certified  building  code 

is  authorized  and  promulgated  by  the  State  Board  of  enforcement  officials;  procedures  for  application, 

Buildina    Regulations    and    Standards    under   the  'ssuance,  denial  and  revocation  of  certifications; 

authority  of  M.G.L.  c.  143,  §§  3  and  94.  approval  of  training  and/or  educational  programs 

offered  to  meet  the  requirements  for  certification; 

R7.1.2   Definitions:   Any  terms  not  herein  defined  maintenance   of  certification   through   continuing 

shall  assume  the  definition  of  the  term  as  used  in  the  education;   application  fees  for  cert.fication;   and 

Massachusetts  State  Building  Code  (780  CMR).  enforcement  of  780  CMR  R7. 

It  is  the  purpose  of  780  CMR  R7  to  establish 

BBRS:   State  Board  of  Building  Regulations  and  standards  and  procedures  for  certification,  and  to 

Standards  require  all  persons  performing  duties  with  respect  to 

Registrant:    Any  individual  registered  with  the  the   insPection   of  building   construction  for  any 

Board  of  Buildina  Regulations  and  Standards  Pohtlcal  subdivision  within  the  Commonwealth  to  be 

(BBRS)    as    a    building    code    enforcement  certified  as  provided  in  780  CMR  R7 
official   in  the  capacity   of  an  inspector  of 

buildings/building     commissioner     or     local       R714  Powers  and  Duties:    The  BBRS'  worklnS 
i  tor  through  the  Administrator  and  the  Board  staff,  shall 


2/7/97    (Effective  2/28/97)  780  CMR  -  Sixth  Edition  801 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


have  the  following  responsibilities  in  addition  to  all 
others  provided  in  780  CMR  R7. 

R7.1.4.1  Upon  recommendations  from  the 
Building  Official  Certification  Committee, 
established  under  780  CMR  R7.1.5,  to  issue 
certifications  to  individuals  deemed  qualified  as 
provided  for  herein. 

R7. 1.4.2  To  maintain  accurate  records  of  all 
applications  for  certification  and  any  official 
action  thereon  and  to  make  such  records  available 
for  inspection  by  the  public  at  all  reasonable 
times. 

R7.1.4.3  To  suspend  or  revoke  a  certification 
provided  for  herein  upon  the  establishment  of 
good  cause. 

R7.1.4.4  Any  person  aggrieved  by  any  notice. 
action,  ruling  or  order  of  the  Board,  or  the 
Building  Official  Certification  Committee  with 
respect  to  780  CMR  R7,  may  have  a  right  to  a 
hearing  as  provided  for  by  law. 

R7.1.5  Inspector     Certification     Advisory 

Committee     (Building     Official     Certification 
Committee): 

R7.1.5.1:  There  is  hereby  established  in  the 
BBRS  the  Inspector  Certification  Advisory 
Committee  hereafter  known  as  the  Building 
Official  Certification  Committee  This  Committee 
shall  be  supported  by  such  staff  of  the  BBRS  as 
may  be  required  for  the  effective  operation  of 
780  CMR  R7. 

R7.1.5.2  Powers  and  Duties:  The  Building 
Official  Certification  Committee  shall  have  the 
responsibility  to  advise  and  to  recommend  to  the 
BBRS  on  all  items  relating  to  the  certification  of 
building  code  enforcement  officials,  including, 
but  not  limited  to: 

a.    issuance  of  certificates 

b     review  of  credentials  of  applicants 

c.  maintenance  of  applicant  records 

d.  hearing  of  complaints  and  appeals  pertain- 
ing to  inspector  certification 

e.  review  and  approval  of  all  courses  of  study, 
seminars,  and  other  educational  programs  as 
deemed  necessary,  for  credit  toward  continuing 
education  requirements 

£  monitoring  all  appointments  to  assure  com- 
pliance with  780  CMR  R7. 
g.  reciprocity  may  be  considered  upon  petition 
of  the  Building  Official  Certification 
Committee  on  forms  provided  for  such 
purpose. 

R7. 1.5.3     Make-up  of  the  Committee:     The 

Building  Official  Certification  Committee  shall 
consist  of  nine  members  appointed  by  the  BBRS 
as  follows  (Terms  of  committee  members  are  as 
established  by  lot  at  the  March  31,  1993  meeting.) 


a        One  member  of  the  BBRS  or  his/her 

designee 

b        Six  members  who  are  active  building 

officials  consisting  of: 

-  One    member    from    each    of  the    three 
Municipal  Building  Official's  Associations 

(Southeastern  Building  Officials 
Association,  Building  Officials  of  Western 
Massachusetts.  Massachusetts  Building 
Commissioners  and  Inspectors 

Association) 

-  Three  members  at  large  to  be  appointed  by 
the  BBRS 

c  One  member  from  academia  who  is  an 
educator  of  construction  at  the  college  level 
(e.g.  architectural,  civil,  structural)  to  be 
appointed  by  the  BBRS 
d.  One  member  of  the  Massachusetts 
Municipal  Association. 

R7.1.6  Categories  of  Certification: 

R7.1.6.1  Categories  of  certification  for  building 
code  enforcement  officials  are  as  follows 
R7. 1.6. 1.1  Inspector  of  Buildings  or 
Building  Commissioner  An  individual 
certified  as  an  inspector  of  buildings  building 
commissioner  shall  perform  the  duties  as 
defined  in  780  CMR  105.3  and  M.G.L  c.  143 
R7. 1.6. 1.2  Local  Inspector:  An  individual 
certified  as  a  local  inspector  shall  perform  the 
duties  as  defined  in  780  CMR  1 05  4  and 
M.G.L.  c.  143 

R7. 1.6.1.3  Conditional  appointment  of  a 
building  code  enforcement  official  A 
conditional  appointee  shall  meet  the 
requirements  of  780  CMR  R7.1.7.4  through 
1.7.6.3. 

R7.1. 6.1.4  Alternate  inspectors  of  buildings/ 
building  commissioners  An  alternate 
inspector  of  buildings/building  commissioner 
shall  be  certified  prior  to  appointment. 

R7.1.7  Certifications  required: 

R7.1.7.1:  After  November  12,  1992,  no 
individual  shall  be  permanently  appointed  to  the 
position  of  inspector  of  buildings,  building 
commissioner  or  local  inspector  in  a  local 
enforcing  agency  for  which  a  certification 
requirement  has  been  established  by  780  CMR 
R7,  unless  that  individual  has  been  deemed 
qualified  and  certified  in  that  category  by  the 
Building  Official  Certification  Committee 

R7.1. 7.1.1  Conditional     appointments 

Conditional  appointments  may  be  made 
pursuant  to  780  CMR  R7.1  7.4,  1.7.5  and  1.7.6 

R7.1.7.2  Reporting  by  appointing  authorities 

Immediately  upon  the  appointment  of  an  inspector 


802 


780  CMR  -  Sixth  Edition  corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


CERTIFICATION  OF  INSPECTORS  OF  BUILDINGS,  BUILDING  COMMISSIONERS 

AND  LOCAL  INSPECTORS 


of  buildings,  building  commissioner  or  local 
inspector,  the  appointing  authority  shall  notify  the 
BBRS  in  writing  on  forms  provided  for  such 
purpose  of  the  name  of  the  appointee,  the 
appointed  position  and  the  date  of  appointment. 

R7. 1.7.3:  Any  individual  employed  as  inspector 
of  buildings,  building  commissioner  or  local 
inspector  and  who  was  in  office  on  November  1 2, 
1992  and  who  was  qualified  (in  accordance  with 
M.G.L.  c.  143,  §  3)  to  be  in  office  at  time  of  hire, 
and  who  has  presented  acceptable  evidence  of 
these  facts  to  the  BBRS,  shall  be  deemed  certified 
in  the  category  held  on  said  date,  and  shall  be 
provided  with  a  certificate  by  the  BBRS. 

R7. 1.7.4  Conditional  Appointments:  After 
November  12,  1992,  individuals  who  meet  or 
exceed  the  experience  requirements  pursuant  to 
M.G.L.  c.  143,  §  3  and  780  CMR  but  who  are  not 
certified  under  the  provisions  of  780  CMR  R7 
may  be  appointed  on  a  conditional  basis  only. 

R7. 1.7.5  Regulations  for  the  Conditional 
Appointment  of  Building  Code  Enforcement 
Officials. 

R7.1.7.5.1:  Any  individual  conditionally 
appointed  as  a  building  code  enforcement 
official,  on  or  after  November  12,  1992  who  is 
not  certified  in  the  appropriate  category  of 
certification  at  the  time  of  the  conditional 
appointment;  shall  comply  with  the  following: 

a.  Immediately  upon  appointment,  the 
appointing  authority  shall  report  the 
conditional  appointment  to  the  BBRS  in 
accordance  with  780  CMR  R7.1 .7.2. 

b.  Within  the  first  six  months  of 
employment  the  conditional  appointee  shall 
make  application  to  take  the  examination(s) 
required  for  the  appropriate  category  of 
certification  as  identified  in  780  CMR 
R7.2.0. 

c.  Within  one  year  following  the  first  six 
months  of  employment  the  conditional 
appointee  shall  attain  a  passing  score  on  all 
of  the  examinations  required  for  the 
category  of  certification  of  the  conditional 
appointment. 

d.  In  accordance  with  780  CMR  R7. 1.7.6, 
a  conditional  appointee  may  petition  the 
Building  Official  Certification  Committee  in 
writing  for  an  extension  of  time  to  comply 
with  the  examination  schedule  of  780  CMR 
R7.  Upon  establishment  of  cause,  the 
Building  Official  Certification  Committee 
may  grant  such  extensions  of  time  as  it  may 
consider  appropriate. 

R7. 1.7.5.2:  Conditional  appointees  shall 
notify  the  BBRS  of  any  change  in  the  status 
of  their  employment,  within  one  month  of 
such  change. 


R7.1.7.6  Requests  for  Extensions  of  Time  to 
Comply  with  Examination  Schedules: 

R7.1. 7.6.1:  Any  conditional  appointee  unable 
to  comply  with  the  examination  schedule  as 
cited  in  780  CMR  R7. 1.7.5  may,  for  cause,  be 
granted  an  extension  of  time  in  order  to 
comply,  upon  written  petition  to  the  Building 
Official  Certification  Committee.  Petitions 
shall  be  forwarded  to  the  clerk  of  said 
committee,  and  addressed  to  the  office  of  the 
BBRS  (current  address  listed  at  the  front  of  the 
building  code).  The  conditional  appointee  shall 
state  all  reasons  to  substantiate  the  request  for 
an  extension  of  time. 

R7.1.7.6.2:  The  Building  Official  Certification 
Committee  shall,  within  ten  days  of  any  action 
taken  by  the  committee  pursuant  to  780  CMR 
R7,  notify  the  appointing  authority  in  writing 
of  such  action. 

780  CMR  R72  REQUIREMENTS  FOR 
INITIAL  CERTIFICATION 

R7.2.1  Application:  Any  candidate  for 
certification  in  any  category  of  building  code 
enforcement  official  issued  pursuant  to  780  CMR  R7 
shall  submit  an  application  to  the  BBRS, 
accompanied  by  the  required  application  fee  as 
prescribed,  on  forms  provided  for  this  purpose  by 
the  BBRS.  The  application  shall  include  such 
information  and  documentation  as  the  BBRS  may 
require  pursuant  to  780  CMR  R7. 

R7.2.2  Building  Code  Enforcement  Officials  in 
Office  as  of  November  12,  1992:  Upon  receipt  of 
acceptable  evidence  as  established  by  the  BBRS, 
signed  by  the  city  or  town  clerk  and  the  appointing 
authority  in  attestation  that  the  applicant  for 
certification  was  employed  in  the  position  of 
inspector  of  buildings,  building  commissioner  or 
local  inspector  and  met  the  qualificational 
requirements  of  said  position  pursuant  to  M.G.L. 
c.  143,  §  3  and  780  CMR  as  of  the  date  of  hire,  the 
applicant  shall  be  deemed  certified  in  the  applicable 
category  and  shall  be  issued  a  certificate.  The 
certificate  shall  indicate  the  name  of  the  individual 
and  the  category  of  certification  and  other 
information  as  may  be  deemed  necessary  by  the 
BBRS. 

R7.2.3  After  November  12,  1992,  applicants  for 
certification  as  a  Building  Code  Enforcement 
Official  shall  meet  the  following  requirements: 

R7.2.4  Requirements  for  certification  as  a  Local 
Inspector: 

R7.2.4.1:  All  candidates  shall  meet  or  exceed  the 
qualifications  for  the  position  of  local  inspector 
pursuant  to  M.G.L.  c.  143,  §  3  and  780  CMR. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


S03 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


R7.2.4.2:  All  candidates  shall  attain  a  passing 
score  in  all  examinations  required  for  certification 
as  either  a  Building  Plans  Examiner  or  a 
Building  Inspector  under  the  Construction  Code 
Inspector  Certification  Program  of  the  Building 
Officials  and  Code  Administrators  International 
(BOCA). 

R7.2.5     Requirements  for  Certification  as  an 
Inspector  of  Buildings/Building  Commissioner: 

R7.2.5.1:  All  candidates  shall  meet  or  exceed  the 
qualifications  for  the  position  of  inspector  of 
buildings  or  building  commissioner  pursuant  to 
M.G.L.  c.  143,  §  3  and  780  CMR. 

R7.2.5.2:  All  candidates  shall  meet  the 
examination  requirements  for  certification  as  a 
local  inspector  pursuant  to  780  CMR  R7.2.4.2 
herein,  or  hold  a  certification  as  a  local  inspector 
pursuant  to  780  CMR  R7. 

R7.2.5.3:  All  candidates  shall  attain  passing 
scores  in  all  examinations  required  for 
certification  as  a  Certified  Building  Official 
under  the  Certified  Building  Official  Program  of 
the  Council  of  American  Building  Officials 
(CABO). 

780  CMR  73  REQUIREMENTS  FOR 
MAINTENANCE  OF  CERTIFICATION 

R7.3.1   Continuing  education: 

R7.3.1.1:  Within  each  three  year  period 
following  initial  certification,  the  registrant  shall 
complete  45  hours  of  continuing  education  credit 
acceptable  to  the  Building  Official  Certification 
Committee. 

R7.3.1.2:  The  Committee  may  publish  a  list  of 
acceptable  educational  programs,  courses, 
seminars,  and  the  like.  The  Committee  may  also 
accept  educational  activities  in  which  registrants 
have  participated  after  the  fact,  upon  application 
and  review  of  the  course  information.  The 
Committee  shall  assign  credits  to  each 
educational/training  event. 

R7.3.2  Renewal  of  certificate: 

R7.3.2.1  Term  of  certificate:  Each  certified 
individual  shall  maintain  a  record  of  his/her 
continuing  education  credits  and  forward  such 
information  to  the  office  of  the  BBRS  in  care  of 
the  Building  Official  Certification  Committee 
(address  is  listed  at  the  front  of  the  building  code) 
as  it  is  accumulated.  The  BBRS  shall  maintain  a 
record  of  each  inspector's  progress. 

At  the  end  of  each  three  year  period,  each 
inspector  who  has  successfully  maintained  his/her 
continuing  education  credit  shall  be  duly  notified 
by  the  BBRS. 


R7.3.3:  In  accordance  with  M.G.L.  c.  143,  §  99,  no 
building  code  enforcement  official  attending  BBRS 
required  educational  programs,  shall  lose  any  rights 
relative  to  compensation  or  vacation. 

780CMRR7.4  PROCEDURES  FOR 
COMPLAINTS 

R7.4.1   Complaints: 

R7.4.1.1  Cause  for  complaint:  Any  individual 
who  has  been  alleged  to  have  violated  the 
provisions  of  780  CMR  R7  or  780  CMR  may  be 
entitled  to  a  hearing  in  accordance  with  M.G.L.  c. 
30A  before  the  Building  Official  Certification 
Committee  or  subcommittee  thereof.  A  complaint 
shall  be  made  in  writing  to  the  BBRS,  attention; 
Building  Official  Certification  Committee. 

R7.4.1.2  Hearings  on  complaints:  If  a  hearing  is 
to  convene,  the  committee  shall  give  at  least  ten 
days  notice  to  all  those  party  to  the  complaint. 
The  sending  of  notice  to  the  address  recorded  on 
the  records  of  the  BBRS  shall  be  deemed 
sufficient  notice. 

R7.4.1.3  Notice  of  hearings:  The  notice  shall 
contain: 

a.  The  name  of  the  complainant 

b.  A  copy  of  the  complaint 

c.  The  date,  time  and  place  of  said  hearing. 
The  complete  file  of  complaint  shall  be  available 
for  inspection  at  the  office  of  the  BBRS  during 
regular  business  hours.  Parties  may  present 
written  or  oral  evidence  to  refute  or  mitigate  any 
charge  contained  in  the  complaint  and  present 
witnesses  in  his/her  behalf.  In  the  event  that  the 
committee  votes  to  take  action  against  said 
certification  pursuant  to  this  hearing,  the  building 
code  enforcement  official,  upon  notice  of  the 
decision,  shall  immediately  comply  with  said 
orders. 

R7.4.1.4     Continuation     of     hearings:     the 

committee,  in  its  discretion,  may  continue  the  date 
for  hearing  upon  request  by  building  official,  the 
complainant  or  the  committee  itself. 

R7.4.1.5  Timing  of  decisions:  The  committee 
shall  make  a  decision  within  15  days  of  the 
hearing.  A  written  decision  shall  be  issued  within 
30  days  of  the  hearing  date. 

R7.4.1.6  Decisions:  The  decision  shall  be  final 
and  binding  upon  the  building  code  enforcement 
official  and  the  complainant. 

R7.4.1.7  Notice  of  action:  In  the  event  that  the 
committee  votes  to  take  action  against  said 
certification  pursuant  to  this  hearing,  the  building 
code  enforcement  official,  upon  notice  of  the 
decision,  shall  immediately  comply  with  said 
orders. 


804 


780  CMR  -  Sixth  Edition 


2/7/97    (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 

CERTIFICATION  OF  INSPECTORS  OF  BUILDINGS,  BUTLDING  COMMISSIONERS 

AND  LOCAL  INSPECTORS 


R7.4.1.8  Appeal:  Any  person  aggrieved  by  a 
decision  of  the  committee  may  appeal  such 
decision  to  a  court  of  law  or  equity  in 
conformance  with  M.G.L.  c.  30A,  §  14. 

R7.4.2  Revocation  of  certificates  and  alternative 
sanctions: 

R7.4.2.1:  The  BBRS,  upon  recommendation  of 
the  Committee,  and  subject  to  the  requirements  of 
the  Administrative  Practices  in  accordance  with 
M.G.L.  c.  30A,  may  suspend  or  revoke  a 
certification,  or  assess  any  other  penalties  as 
provided  for  by  law,  if  it  is  determined  that  the 
registrant:  (The  following  is  not  an  exhaustive 
list.) 

a.  Has  obtained  a  certification  by  fraud  or 
misrepresentation,  or  the  person  named  in  the 
certificate  has  obtained  it  by  fraud  or 
misrepresentation; 

b.  Has  aided  or  abetted  in  practice  as  a 
certified  building  code  enforcement  official 
any  person  not  authorized  to  practice  as  a 
certified  building  code  enforcement  official 
under  the  provisions  of  780  CMR  R7; 

c.  Has  fraudulently  or  deceitfully  practiced  as 
a  certified  building  code  enforcement  official, 

d.  Has  been  grossly  negligent  or  has  engaged 
in  misconduct  in  the  performance  of  any  of  his 
duties; 

e.  Has  failed,  over  a  period  of  time,  to 
maintain  continuing  education  requirements  as 
specified  in  780  CMR  R7; 

f.  Has  been  found  to  have  failed  to  report  an 
offer,  or  bribe,  or  other  favor  in  a  proceeding 


under  780  CMR  R7  or  other  appropriate  law  of 

this  or  any  other  state  or  jurisdiction; 

g.    Has  made  a  false  or  misleading  statement, 

or   has    made    a   material    omission    in   any 

submission  to  the  BBRS; 

h.      Has  failed  to  enforce  the  provisions  of 

780  CMR  as  prescribed  by  M.G.L.  c.  143,  §  3. 

R7.4.3  Violations  and  Penalties: 

R7.4.3.1:  It  shall  be  a  violation  of  780  CMR  R7 
on  or  after  November  12,  1992,  for  any  individual 
to  represent  himself/herself  to  be  qualified  for  a 
position  that  the  individual  does  not  currently 
hold,  or  to  use  a  title  or  otherwise  represent 
himself/herself  to  be  qualified  for  a  position  that 
the  individual  does  not  currently  hold,  or  to  use  a 
title  or  otherwise  represent  himself/herself  as 
certified  or  authorized  to  act  under  the  780  CMR 
if  that  individual  does  not  possess  a  certificate, 
unless  such  person  is  appointed  subject  to  the 
provisions  of  780  CMR  R7  1.6.1.3.  In  addition  to 
any  other  remedy  available  under  law,  such 
representation  shall  be  deemed  a  violation  of 
780  CMR  R7  and  any  other  penalties  as  provided 
for  by  law. 

R7.4.3.2:  It  shall  be  a  violation  of  780  CMR  R7 
on  and  after  November  12,  1992,  for  any  local 
enforcing  agency  to  offer  employment,  to  retain 
for  employment  or  to  permanently  appoint  any 
individual  who  is  not  certified  in  accordance  with 
780  CMR  R7,  except  on  a  conditional  basis  in 
accordance  with  780  CMR  R7.1.6.1 .3. 


2/7/97    (Effective  2/28/97) 


780  CMR  -  Sixth  Edition 


805 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 

NON-TEXT  PAGE 


806  780  CMR  -  Sixth  Edition  2/7/97    (Effective  2/28/97) 


INDEX 

Bv  section  number 


A.  use  group.  assembly.  303.0 
Access 

Attics,  1211.2 

Courts.  1212.4 

Crawl  spaces.  1211.1 

Roofs.  1027.0 
Accessibility-.  780  CMR  1 1 
Accessor.-  structures 

Definition.  202.0.  3602.2 
.  Use  Group  U.  utility'  and  miscellaneous.  3 12.0 
Adjoining  property 

Demolition  and  excavation.  3310  0 

Existing  buildings.  3309.0 

Fences.  331 1.0 

Grade  control.  33 10.4 

Notice  to  owners.  33 10.  i 

Protection  of.  3308.0 

Storage  of  materials.  33 12.0 
Adjoining  spaces 

Natural  light.  1206.0 

Natural  ventilation.  1208.0 
Administrative 

Administration.  Chapter  1.  3601.0 

Alternate  materials  and  methods.  109.3 

Application  for  permits.  106.2 

Board  of  appeals.  122.0 

Building  classified  by  code  official.  302. 1 

Certificate  of  occupancy.  120.0 

Code  official  approves  plans,  109.0 

Code  official,  definition,  202.0 

Conditions  of  permit,  111.0.  113.0 

Drawings  and  specifications  required.  110  8 

Existing  structures,  102.5 

Foundation  permits.  108.7.  Hi  13 

Inspections  required.  1 15.0 

Inspectors  appointed,  105.1 

Liability,  105.7 

Maintenance  of  buildings,  103.1.  3401.2 

Organization  of  building  department  105.0 

Permit  fees.  114.0 

Permits  required,  110.1.  110.2 

Powers  and  duties  of  code  official,  105.0 

Records  of  department,  105.8 

Requirements  not  in  code,  102.2,  102.3 

Restrictions  on  employees.  105  6 

Revocation  of  permits,  111.12 

Scope  of  code.  101.2 

Stop  work  orders.  1 19.0 

Tests  and  test  reports,  1708.0 

Unsafe  structures,  121.0 

Validity  of  code,  104.0 

Violations  and  penalties.  118  0 
Aged,  homes  for 

Use  Group  I,  institutional.  308.0 
Aggregates 


Concrete.  1906.3 

Masonry,  mortar  and  grout.  2105.0 

Special  tests.  1906  3.1 
Air  ducts  (see  Ducts) 
Air  intakes 

Combustion.  3620.0 

Courts,  1212.5 

From  attic  areas.  3620.3.  3620.3.3 

From  under  floor  areas.  3620.3.  3620.3.4 

Return.  3619.2 

Supply.  3619.3 
Air  plenum  (see  Plenums) 
Airplane  hangars  (see  Garages) 
Airport  traffic  control  towers.  414.0 
Air-supported  structures 

Membrane  structures,  general.  3  1 03  0 

Temporary.  3104.0 
Aisles 

Assembh .  Use  Group  A.  1011   3.  i  012  0 

Exit  access,  other  use  groups.  10.1 1.0 

Illumination.  1024  0 
Alarm  systems  (see  Fire  protection  systems) 
Allowable  areas  and  heights  of  buildings  (also  see  Areas. 

building) 

Existing  buildings.  3400.3 

General.  503.0.  Tabie  503 

Unlimited  areas.  507.0 
Allowable  spans 

Floor  joists.  3605  2.3  1 

Headers.  3606.2.6 

Rafters  and  ceiling  joists.  3608.2.4 
Alloys 

Aluminum.  2002.1 

Specni  steei.  2207.1 
Alterations 

Additions.  3404.2.  3408.2.3  .  3408.4 

Area  and  height  limitations.  3404.9 

Certificate  of  occupancy .  1 20  0 

Definition,  202.0 

Existing  buildings.  3400.  3404.0 

Inspections.  115.0 

Light  and  ventilation  in  existing  buildings,  3400.6 

Minor  changes.  3404. 1 

Nonstructural  alterations  and  repairs.  340 1 .2 

Permit  fees.  1 14.0 

Permit  required.  111.0 

Signs,  3102.4.2 

Structural  alterations  and  repairs.  3404.0 
Alternative  materials  and  construction 

Approved  by  code  official,  109.0,  3601 

Board  of  appeals.  122.0 

Suitability  of,  1707.1 
Aluminum  alloys.  2002.0 
Amendments  to  plans.  110.12.  110  13 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


807 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Anchorage,  anchors 

Flood-resistant  construction,  3 107.5.2 

Framing  into  girders,  2305.6. 1 

Intersecting  masonry  walls,  2111.2 

Masonry,  general,  21 10.0, 21 1 1.0 
.  Masonry,  veneer,  1405.5 

Metal  veneers,  1405.4.1 

Projecting  masonry,  21 12.0 

Wood,  sill,  2305.16 
Antennas,  radio  and  television,  3 109.0 
Apartment  house  (see  Multiple  dwellings) 
Appeals,  board  of,  122.0 
Application  for  permit 

Action  by  code  official  on  application.  111.1 

Application  form,  1 10.4 

Awnings,  3205.0, 

Conditions  of  permit,  113.0 

Drawings  required.  110  8 

For  demolition  of  buildings.  112.0 

Foundation  permits,  108.7,  111.13 

Moving  buildings,  3407. 1 

Permit  fees,  114.0 

Plot  diagram  required,  107.6 

Records  to  be  kept,  105.8 

Registered  architect  or  engineer,  107.3 

Signs,  3102.4 

Swimming  pools,  421.3 

Temporary  structures,  3104.0 

What  required,  1 10.0,  1 1 1.0 

When  required,  1 10.0,  1 1 1.0 
Appointment  of  code  official,  105.1 
Approval 

Alternative  materials  and  methods  of  construction, 
109.3 

Certificate  of  occupancy,  120.0 

For  use  of  plastic  material.  2601.3 

General,  106.0 

Inspections,  1 15.0 

Materials,  1704.0 

Modifications,  106.2 

Moving  buildings,  3407.0 

Of  plans  for  permit,  108.5 

Used  materials,  109.2 
Approved,  definition,  202.0,  3602.2 
Approved  agency 

Criteria,  1704.3.1 

Definition,  202.0 
Architect 

Report,  permits  issued,  1 16.4 

Drawings  and  specifications,  by,  1 10.8 

Special  professional  services,  1 16.2 
Architectural  trim  (see  Exterior  trim  restrictions) 
Areas,  building 

Allowable  areas  for  buildings  (also  see  Allowable 

areas  and  heights  of  buildings),  503.0.  Table  503, 

3408.6.2 

Allowable,  required  reductions  of,  506.4,  Table  506  4 

Definition,  202.0 

Existing  buildings,  3404. 1 

Floor  area,  definition,  202.0 

General  area  limitations,  503.0 

Increase  for  street  frontage,  506.2 

Increase  for  suppression.  506.3 

Mezzanines,  505.2 

Modifications.  506.0, 506.4 


Open  parking  structures,  406.4 

Separate  buildings,  3 1 3. 1 .3,  503  1 ,  402. 1 6 

Special  industrial  uses,  503. 1. 1 

Unlimited  areas,  507.0 

Waiting  rooms.  409.2  . 1 
Areaways,  3203.12.1 
Artificial  light,  1207.0,  1024.1 
Asphalt  roof  shingles.  1507.2.3.  3609.3 
Assembly  buildings 

Aisles.  1  012.0 

Area  allowed,  503  0 

Classification  of.  303  0 

Determining  capacity  of  means  of  egress,  1009.0 

Fire  suppression  requirements.  904.0,  914.0 

Occupancy  load  requirements,  1008.0 

Stages  and  platforms,  412.0 

Use  Group  A,  303.0 
Atnums.  404.0 
Attic 

Access,  1211.2 

Combustion  air,  3620.3.3 

Definition.  202.0 

Draftstopping,  720.7.2 

Furnaces,  insulation  in, 

Insulation,  exposed.  722.2 

Ventilation  of,  1210.1 
Auditoriums 

Foyers  and  waiting  spaces,  1006.2.4 

Means  of  egress,  1006.2.2 

Use  Group  A-l.  assembly.  303.2 

Use  Group  A-3.  assembly,  303.4 
Automatic  fire  detection  systems  (see  Detection  systems, 

automatic  fire) 
Automatic  fire  suppression  systems  (also  see  Sprinklers) 

Atnums,  404.2 

Carbon  dioxide  systems.  909.0 

Covered  mall  buildings,  402. 10 

Dry-chemical  systems,  9 10.0 

Foam  systems.  91 1.0 

General,  901.0 

Halogenated  systems.  912.0 

High-nse  buildings,  403.2, 403.3 

Limited  area  systems,  907  0 

Plans   and  specifications   (construction   documents). 
903.1 

System  selection,  905.0 

Water  sprinkler  systems,  906.0 

Where  required.  904. 1 
Automobiles,  parking 

Open  parking  structures.  313.2, 406.0 

Private  garages,  202.0, 407.0 

Public  garages,  202.0,  402.16.  408.0 
Awnings 

Clearance,  3205.0 

Covers  and  boxes,  3203. 10 

Fixed,  3205.3 

Loads,  1609.0 

Moveable,  3205.2 

Over  public  property,  3203.9, 3205. 1 

Permit  for,  3205. 1 

Plastic,  2604.8 

Retractable.  3205.2 


808 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


B 


B.  use  group,  business,  304.0 
Balcony 

Exits,  1006.2.2 

Exterior  balconies,  3203.8 

Exterior  construction  of,  1406.4 

Live  loads.  1606.0 

Over  public  property,  3203.8 

Permissible  street  projections,  3203.8 

Railings.  1012.8.  1021.4.  1615.5 

Steps.  1012.0 
Banner  and  cloth  signs.  3 1 02. 12. 1 
Barricades 

Construction,  where  required,  maintenance.  3304.2, 

3310.1 
Bars,  reinforcing 

Clear  cover  in  concrete  footings.  1810.3.2 

Details  of  reinforcement,  1910  0.  1911 .4 

Reinforcing  steel.  2208.0 
Basement 

Dampproofing,  1813.0 

Definition,  202.0 

Enclosure  of  stairways.  1014. 1 1 

Fire  suppression  system  required,  904.10 

Floors  above,  protection  of.  1 006  3 . 1 

Ratproofing.  1215.0 

Required  exits,  1010.2 

Stairway  construction  1014 

Underground  structures,  405.0 

Waterproofing.  1813.0 
Bathrooms 

Light  and  ventilation.  1205.0 

Mechanical  ventilation  allowed,  1205.2 

Window  area  required  for,  1208  2 
Bay  window  (also  see  Windows,  bay) 

Construction  of,  1406.5 

Over  public  property,  projection.  3203.7 
Beams 

Bottom  flange  protection.  715.6 

Fireresistance.  rating  of.  Table  602,  715.0 

Fireresistance.  reinforced  concrete.  Table  602 

Reinforced  concrete  1901. 

Steel,  formed.  2206.0 

Steel,  structural.  2203.0 

Structural,  glued-laminated.  2307.1 

Supports.  3605.2.4 

Wood,  2303.0,  2305.0 

Wood  in  heavy  timber  construction.  2304.0 
Bearing  (Loadbeanng) 

For  wood  beams  and  girders.  2305.6.1.  2305.6.3 

On  hollow  masonry  units  1812.3.3.  2112.1 .2.2 
Bearing  partitions  (see  Walls) 
Bearing,  soil  capacity.  1804.0 
Bearing  walls  (see  Walls) 
Bleachers,  1013.0 

Blocks  concrete  masonry  units  (see  Masonry) 
Board  and  care  facilities  (see  1.  use  group,  institutional) 
Board  of  appeals,  121.0 
Boarding  houses  (see  Residential  buildings) 


Bond,  masonry 

Foundation  walls,  1812  3.5 
Masonry  veneers,  1405.5 
Masonry  walls,  21 10.0. 21 1 1.0 

Bonngs  and  tests  of  soils.  1802.0,  1803.0.  1804  0 
Bracing 

Adjoining  existing  buildings.  3309.3 

Exterior  stud  walls.  2305.7 

For  stud  walls  and  partitions,  bearing.  2305  4.2 

Masonry  walls,  lateral.  2108.0 

Seismic.    1903.0.    19040.  2104.0.   2204.0,  2305.: 
2306.0 
Bnck  (see  Masonry) 
Bridges 

Over  sidewalks  (wrecking).  3304.3 

Pedestrian  walkways.  3 106  0 
Bridging,  wood  floors.  2305. 14.2 
Building 

Allowable  areas  and  heights.  503.0.  Table  503 

Alterations  of  existing  buildings.  3400.0.  3404.0 

Ceiling  height  3603.8 

Certificate  of  use  and  occupancy .  120.0 

Change  m  use.  3400.3 

Classified  by  type  of  construction.  602. 1 

Classified  by  use  or  occupancy.  302. 1 

Construction  precautions.  Chapter  33 

Definition,  202.0 

Design  criteria.  3603. 1 

Doors.  3603.11 

Exits.  3603.10 

Flood  resistant,  3107.0 

Garages,  3603.5 

General  limitations.  Chapter  5 

Glazing.  3603.20 

Height,  definition.  202.0 

Height  modifications.  504.0 

Heights,  allowable.  503.0,  Table  503,  504.0,  507. 1 

High-rise.  403.0 

Historic.  3409.0 

Maintenance.  103.0 

Permissible  street  projections.  3203.0 

Room  dimensions.  3603.7 

Stairways.  3603.13 

Temporary,  1 10.2 

Two  or  more  on  same  lot,  503  1.3.  1201.2 

Unlimited  area,  507.0 

Unsafe,  121.0 
Building  department 

Annual  report  105.5. 1 

General.  1  05.0 

Records.  106.7 
Building  official  (see  Code  official).  202.0 
Building  paper.  1405.3  6 
Building  permits  (see  Permits) 
Business  buildings.  Use  Group  B.  304.0 


Caisson  piles.  1824.0 
Calculations  required.  110  8 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


809 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Canopies 

Construction.  3 105.0.  3205.4 

Loads,  1609.6.2 

On  exterior  walls.  3205.4 

Over  public  property.  3205. 1 
Carbon  dioxide  extinguishing  system  (see  Automatic  fire 

suppression  systems) 
Cast  iron,  2209.0 

Cast  stone 

Bonding,  2110.0 

General  requirements,  2105.3 
Cavity  walls 

Definition  (see  Walls).  202.0.  3606.6 
Ceilings 

Finishes,  3608.5 

Fireresistance  rated  assemblies,  713.0 
•Height  1204.0,  3603.8 

Panels,  713.1.1 

Plenums,  2805.0 
Cellar  (see  Basement) 
Cement 

Concrete,  materials,  mixes.  1906.0 

Stucco,  2506.0 

Water-cement  ratio.  1908.2 
Central-station  system 

Definition,  202.0 

Fire  suppression  system  supervision,  923. 1 
Ceramic  tile 

Mortar,  types  and  mix,  2105.10 

Veneers,  1405.5 
Certificate  of  occupancy 

Definition,  202.0 

Existing  buildings.  120.2.  120.3.  120.4 

General,  120.1 

Temporary  occupancy,  120.3 
Change  of  use,  202.0, 3400.0,  3405.0 
Changes  in  plans,  1 10. 1 
Changes  to  buildings 

Alterations,  3400.1,  3404.0 

Existing,  3400. 1 

Rehabilitation,  3400.1,  3404.0 
Chases  (see  Masonry) 
Chemicals 

High-hazard  use  group,  307.0 
Child  day  care  center 

Use  Group  E,  305.0 

Use  Group  1-2,308.3.1 

Use  Group  R,  310.5.1 
Chimneys 

Chimneys  and  fireplaces,  3610.0 

Clearance,  3610.2.14 

Crickets,  3610.2.16 

Design,  3610.0 

Factory  Built,  3610.3 

Firestopping,  3610.2.15 

Flue  lining,  3610.2.7,  3610.2.8 

Load,  3610.2.4 

Masonry, 

Multiple  flue,  3610.2.9 

Support,  3610.2.1 

Termination,  3610.2.5 

Wall  thickness,  3610.2.6 


Churches 

Use  Group  A-4,  assembly,  303.0 
Chutes 

Linen  and  refuse,  2807.0 
Classification 

Of  buildings,  by  code  official,  302. 1 

Of  buildings,  by  occupancy,  302.0 

Of  buildings,  by  types  of  construction,  602.0 

Of  types  of  construction.  603.0.  604  0.  605.0.  606  0 
Clay  tile 

General,  21050 

Veneer,  1405.0 
Clearances 

Around  concrete  reinforcing,  18 10.3.2 

Around  fireplaces,  21 14.6 

Around  timber  in  masonry,  2305.6.3 

Awnings,  movable.  3203.9.  3203. 10.  3205  2 

Marquee  awnings,  3203. 1 1 

Minimum  ceiling  heights,  1204  0 

Of  balconies  above  grade,  3203.8 

Of  wood  above  grade,  231 1.4.2 

Projection  over  sidewalks.  3203  0 

Under  first  floor  joists,  1210.2 
Coal  pockets.  418.3.1.6 
Code  official 

Appoints  inspectors,  105.1 

Charge  of  building  department  (duties  and  powers), 
106.1 

Classifies  building,  302. 1 

Definition,  202.0 

Deputies.  1 04  4 

Duties  and  powers  of.  105.0,  106.0.  1 10  0 

Inspections  by,  106.4,  1 15.0 

Issues  permits,  105.0,  106.2.  108.0 

Liability,  105.7 

Record  of  permits  required,  105.8 

Records,  official,  105.8 

Reports,  105.5 

Rule-making  authority.  108.1 

Columns 

Cast-iron  construction,  2209.4. 1 

Concrete-filled  pipe.  1912.0 

Fireresistance  and  protection  of.  Table  602,  715.0 

Fireresistance  tests,  704.0 

Heavy  timber  construction,  605.1,  2304.0 

Live  load  reduction,  1608  0 

Working  stresses,  cast  iron,  Table  2210.2 
Combustibility  tests,  704.7 
Combustible 

Dusts,  grain  processing  and  storage,  307  4. 418.3  1 

Fibers,  307.5 

Liquids,  307.4. 418.3.2 
Combustible  materials 

Decorative  material  restrictions.  807  0 

Definition.  202.0 

Exterior  trim  restrictions.  1406.0 

Flameresistance  tests,  807.2 

Insulation.  707.4.  722.0 

Interior  trim.  803.5 

Permitted    in    noncombustible    construction,    602.4. 
806.0 

Compliance  with  permit,  1 13.3 
Computations,  required.  107.7 


810 


780  CMR  -  Sixth  Edition    corrected  -  9/1 9/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Concealed  spaces,  605. 1.  720.6. 1,  720.7.2,  722.3 

Concentrated  loads,  1613.0 

Concrete 

Aggregates,  1906.3 

Caissons,  1824.0 

Cementitious  material,  limitations,  1907.1.2.2 

Columns,  concrete-filled  pipe,  1912.0 

Definition,  202.0 

Ducts,  3619.1 

Floors  (on  grade),  3605.5 

Footings,  1810.0 

Minimum  dimensions,  1905.0 

Piles,  1818.0,  1819.0,  1820.0,  1821.0 

Pipes  in,  1909  3 

Plain  concrete,  1901.2,  1904.0 

Reinforced  (also  see  Reinforced  concrete).   1901.1, 
1910.0 

Shingles.  3609.6 

Shotcrete,  1911.0 

Units  (also  see  Masonry),  2 105. 1 

Weathering,  3604.2.2 
Concrete,  masonry  blocks  (see  Blocks,  concrete  masonry 

units) 
Condensation,  1210.0,  1405.3.10 
Condition  of  permits,  113.0 
Construction 

Approval  of  materials,  etc..  109.0,  1704.0 

Basement  walls,  3604.4 

Cavity  wall  masonry,  3606.6 

Classification  of  construction  materials,  1707.0 

Concrete,  1908.0 

Covered  by  code,  102.0 

Fences,  3304.2 

Footings,  3604.3 

Foundations,  3604.0 

General  requirements,  602  0,  1701.0 

Grouted  masonry,  3606.7 

Inspection,  1 15.0,  1705.0 

Masonry,  21 12.0,  3606.4 

Metal,  3608.4 

Reinforced  hollow  masonry,  3606.7.4 

Roof-ceiling,  3608.0 

Stage,  413.2 

Steel,  2203.0, 2205.0,  2206.0,  2207.0, 2209.0,  2210.0 

Types  of  construction,  603.0,  604.0, 605.0,  606.0 

Wall,  3606.0 

Wood,  2305.0 
Construction  operations 

Demolition,  33 10.0 

Excavation,  3310.0 

Existing  buildings,  3309.0 

Fire  hazards,  3305.0 

General,  3301.0 

Lighting,  33 15.0 

Retaining  walls,  33 1 1.0 

Storage,  materials,  33 12.0 
Conveyors,  3010.0 
Cooling  towers  1510. 
Coping 

Flashing,  1405.3.10 

On  retaining  walls,  1825.4 
Corbeling 

Foundation  walls,  1812.5 

Masonry,  2112.2 


Cornices 

Masonry,  2112.2.1 

Projections,  3203.3 

Type  of  construction.  1406  0 
Corridors 

Arrangements,  1006.2.  1011.1 

Capacity  of  egress  width,  1009.0 

Deadends.  1011.2 

Definition.  202.0 

Fireresistance  ratings.  Table  602 

Height,  1204.1 

Obstructions,  1011.1 

Prohibited  use,  1005.0 

Widths,  1009.2.  1011.3 
Courts 

Definition.  1202.0 

General,  1212.1 

Obstructions.  1213.0 

Permissible  encroachments.  1213  2 
Covered  mall  buildings 

Definition.  402.2 

General.  402.0 

Smoke  control  systems,  92 1  1 
Coverings 

For  exterior  stairs,  1014.12 

For  exteriors,  weather  protection.  1405.2. 1 .  3607.3 

Interior  finishes.  803  0,  3607.2 

Roofs,  Chapter  15.  3609.0 

Wali,  3607  0 
Crawl  spaces 

Foam  plastics,  2603 .4.1.4 

Plenums,  2805.1 

Ventilation,  1210.2,3604  9 

Waterproofing,  1813.1.2,  3604.9.1 
Curtain  boards,  922.3 
Curtain  wall 

Ratproofing,  1215.0 
Curtains  (also  see  Decorations) 

Amum  separations,  sprinkler  obstructions.  404.5 

Decorative  material  restrictions.  404  3,  807  1 

Proscenium,  412.3  6 


D 


Dampers 

Fire,  accessibility,  717.3 

Fire,  approved  type,  717. 1 

Fire,  definition,  202.0 

Where  required,  717.2 
Dampproofing  1813.0 
Dance  halls 

Use  Group  A-2,  assembly.  303.2 
Dangerous  structures.  121.0 
Day  care  facilities  (see  Child  day  care  center) 
Dead  loads 

Decay,  3603.22 

Definition  (see  Load),  202.0 

Design,  1605.0 
Decisions  of  board  of  appeals.  122.4 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


811 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Decorations  (also  see  Interior  finish  and  trim) 

Atriums,  404.3 

Curtains,  404.5, 412.3.6,  807.1 

Flameresistance  tests,  807.2 

Restrictions,  807. 1 

Stages,  412.3.5.1 
Decorative  features 

Projections.  3203.4 
Definitions.  202.0 

Deflection  criteria,  604.5. 1,  709.3.2, 2308.2.6 
Demolition 

General,  112.0 

Permit,  when  required,  1 12. 1 

Standpipes  maintained,  3305.3.4 

Unsafe  buildings,  121.0,  121.5 
Depth  of  footings 

Governed  by  frost  Ime,  1 806. 1 

Governed  by  loading,  1805.0 
Design 

Approved  by  code  official,  1 704. 1 

Cast-in-place  concrete  piles,  1820.0 

Composite  piles,  1823.1 

Dead  load,  1605.0 

Fire    protective    requirements    (see    Fire    protection 
systems) 

Formed  steel  construction.  2206. 1 

Foundation  walls,  1812.1 

General  1601.0 

Glass,  glazing,  2402.0,  2403.0 

Live  loads,  1606.0,  1607.0 

Lumber  and  timber  construction.  2303  1 

Masonry  wall  construction,  21010 

Plain  concrete,  1901.2 

Plastics,  2603.0 

Precast  concrete  piles  1 82 1  1 

Proscenium  curtains.  412.3.6 

Reinforced  concrete,  190.1 

Retaining  walls,  1825.2 

Safe  load,  1604.0 

Seismic  (earthquake),  1612.3 

Signs,  general  requirements,  3102.6 

Special  steels,  2207. 1 

Steel  pipe  and  tapered  tubular  piles,  1819.0 

Wind  loads,161 1.0 
Detection  systems,  automatic  fire  (also  see  Fire  protection 

systems) 

Airport  traffic  control  towers,  414.3 

Approval,  918.3 

Atriums,  404.6 

Definition,  202.0 

General  requirements,  918.0 

High-rise  buildings,  403.4 

HPM  facilities,  416.9.2 

Plans  and  specifications,  918.2 

Sprinklered  buildings  exception,  918.5 

Use  Group  1-2,409.5.1 

Where  required,  918.4 

Zones,  918.6 
Deviations 

From  code,  109.3 
Devices  for  window  cleaning,  3 1 10.0 


Display  of  permit,  111.14 
Doors 

Air-supported  structures.  3 104.8 

Approved  type,  fire,  716.1,716.2 

Arrangement,  1006.2,  1017.2.3 

Automatic-closing  devices  for,  716.5 

Bolts,  surface,  1017.4.1.1 

Corridors  409.3.1,  1011.1.3.  1011.4.2 

Egress,  means  of,  1017.0 

Exterior  walls,  706.4 

Fire  (see  Fire  doors) 

Fire  partitions,  711.0 

Fire  separation  assemblies,  709.0 

Fire  walls.  707  0 

In  horizontal  exits.  1019.2 

Location  of.  1006.0,  1017.4 

Panic  hardware.  1017.4.2 

Power  operated,  1 0 1 7.4.3 

Rated  fire  door  assemblies,  7 1 6. 1 

Required  to  open  out  1014.8.2.  1017  4 

Revolving,  1018.0 

Stairways,  exterior,  1014.12 

Stairways,  interior,  1014.8,  1014.11 

Security  grilles,  1017.5 

Signs,  1017.4.1.  1017.4.1.2 

Smokeproof  enclosures.  1015.4.1,  1015.5.1    1015.5.2. 
1015.6.1 

Stages,  412.3.4 

Use  Group  1-2,409.3.1 

Use  Group  1-3,410.3,410.4 

Width  of,  1017.3 

Wired  glass  in,  719.2 
Dormers,  1510.6 
Dormitories 

Definition  (see  Dwellings).  202.0 

Use  Group  R-l,  residential,  3 10.0 
Doubtful  use  classification,  302. 1 
Downspout 

For  roofs,  3203. 11.3 

Materials,  1406.0 
Draftstopping 

Definition,  202.0 

General,  720.0 
Drainage 

Foundation  systems.  1813.5 

Marquees,  3203.11.3 
Dressing  rooms  (see  Theaters) 
Dry  cleaning  plants 

General,  418.3.4 

Use  group  classification,  306.0 
Drying  rooms,  2806.0 
Drywall  (see  Gypsum  board) 
Ducts 

Fire  dampers  required  in,  717.0 

Firestopping  openings,  720.6  4 
Dumbwaiter 

Definition,  202.0 
Dusts,  combustible,  307.2,  418.3.1 


812 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Duties 

Of  board  of  appeals,  122.0 
Of  code  official,  106.0 

Dwellings 

Area  and  height  limitations,  general,  503.0,  Table  503 

Ceiling  height,  1204.1 

Definition,  202.0 

Fire  partitions  in,  310.5,  711.4 

Floor  area,  minimum,  1204.2 

Use  Group  R,  residential,  3 10.0 


E 


E,  use  group,  educational,  305.0 
Earthquake  (seismic)  design 

Concrete,1903.0,1904.0 

Foundations,  1810.2.1,  1815.2.1,  1816.3,  1816.7.1, 
1816.11.1,  1818.3  1819.3,  1820.1.2,  1820.5.4. 
1821.3.5,  1821.3.6,  1824.3 

Inspection  related  to  1705.3.3.2,  1705.4.5,  1705.9, 
1705.10,  1705  II 

Loads,  1612.0 

Masonry,  2101.2, 2104.0 

Soils,  1 802. 1.1.1 805.2, 1 805.3 

Steel,  2203.2,  2203.2.1,  2204.0,  2206.3,  2207.2.1 

Wood,  2305.8,  2305.9,  2306.0 
Eaves 

Construction,  1406.0 

Draftstopping,  720.7.2 

Projection,  3203.0 
Educational  buildings.  Use  Group  E,  305.0 
Egress  (see  Means  of  egress) 
Electrical  equipment  and  systems,  Chapter  27 
Elevated  walkways,  3 106.0 
Elevators,  3000  0 
Emergency 

Controls,  proscenium  curtains,  412.3.6.4 

Escape,  1010.4 

Lighting,  1024.0 

Signs  for  exits,  1023.0 

Emergency  electrical  systems  (also  see  Standby  power 

systems) 

High-rise  buildings,  403.9.3 
Emergency  measures 

Closing  streets,  121.5 

Cost  of  emergency  repairs,  121.5 
Emergency  repairs,  121.2, 121.4 

Temporary  safeguards,  121.3 

Vacating  structures,  120.1 
Employees,  restrictions  on,  105.6 
Enclosure 

For  elevators,  3007.1.1 

For  interior  stairs,  1 0 14. 1 1 

For  motion  picture  projection  rooms,  41 1.2 

Of  exterior  stairways,  10 14. 12 

Ramps,  1016.0 

Shafts,  710.0 


Enclosure  walls  (see  Walls) 


Encroachments 

Awnings  and  canopies,  3203.9 

Court,  1213.0 

Existing,  3202.6 

General.  3201.0 

Special  and  temporary,  3204.0 

Street,  3202.0 

Yard,  1213.0 
Energy  conservation 

Alternative  systems,  1316.0 

Exceptions,  1301.4 

Exterior  envelope  requirements.  1309  0.  1314.0 

General,  1300.0 

In  electrical  distribution  systems,  13 12.0 

In  mechanical  systems,  1310.0,  1311.0 

In  water  heating  systems,  RESERVED 

Plans  and  specifications,  1303.0 
Enforcement  of  code,  106.0 
Engineering  calculations,  107.7,  110.8 
Engineering  practice,  116  0 
Escalators.  1006.6.3001.0 
Excavations 

Protection  of,  3310.0 

Protection  of  adjoining  property.  3308.0 

Walkways  over,  3304.3 
Exhaust  systems 

Contaminants  to  outdoor  air,  1208.3 

Spray  spaces.  419.2 
Existing  buildings 

Additions,  alterations,  repairs.  Chapter  34 

Areas,  allowable,  Table  503,  3404  9 

Certificate  of  occupancy,  120.0 

Change  in  existing  use,  3405.0 

Change  of  occupancy1,  3405.0 

Condemnation  of,  119  1 

Continuation  of,  102.2 

Definition  (see  Building),  202.0 

Demolition,  112.0 

General  requirements,  3400. 1 

Inspection  of,  106.4,  106.5,  115.0 

Moving,  102.5.6,  3407.0 

Nonstructural  alterations  and  repairs,  3404.4 

Protection  during  construction  operations,  3304.0 

Roof  coverings,  1512.0 

Unsafe,  121.0 
Existing  electrical  installations,  2708.0 
Existing  signs,  340 1  0 
Exit  lights,  1023.0,  1024.0 
Exit  signs,  1023.0 

Exits  (see  Means  of  egress),  3603. 10 
Expiration  of  permit  1 1 1.7 
Explosion  hazards,  307.3, 417.5.1 
Exterior  envelope 

Definition,  202.0 

Requirements,  1301.0,1305.0,  1309.0.  1314.0 
Exterior  opening,  protection  required.  706.0 
Exterior  stairways,  1014.12 
Exterior  trim  restrictions,  1406  0,  705. 1.2 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


813 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Exterior  walls 

Fireresistance  ratings,  507.2,  Table  602,  705.0 

General,  Chapter  14 
Extinguishers,  fire,  920.0 


F,  use  group,  factory  and  industrial,  306.0 
Faced  (veneered)  walls  (see  Walls) 
Factory  buildings 

Use  Group  F,  factory  and  industrial.  306  0 

Use  Group  H,  high-hazard.  307.0 
Fasteners 

Roof  construction,  1505.2,  1507.0 

Schedule,  Table  2305.2 

Weather  coverings,  1405.3.7 

Wood  construction,  2305.2 
Fees 

For  demolition,  1 12.2 

For  moving  of  buildings,  1 12.2 

For  new  construction  and  alterations,  1 14.3 

For  signs,  112.2 

General,  114.0 

Payment  of.  113.1 

Refunds,  112.5 

Schedule,  114.3.1 

Special,  114.2 
Fences 

Excavations,  33 10.0 

For  construction  purposes,  3304.2 

General  requirements,  3311.0 

Use  Group  U,  3 12.0 
Film 

Projection  rooms,  411.0 

Storage  and  use  of  flammable  film,  4 1 1  1 
Finish,  interior  (see  Interior  finish  and  tnm) 
Fire 

Alarm  system  (see  Fire  protection  system) 

Area,  definition,  202.0 

Dampers,  717.0 

Firestopping,  202.0,  720.0 

Hydrants,  916.0 

Sprinklers  and  standpipes,  904.0,  906.0,  914.0,  915.1 
Fire  department 

Central  control  station  for,  923.0 

Connections,  915.0,  915.2 
Fire  detection  systems,  918.0 

Fire  doors 

Closing  devices,  716.5 
Corridors,  1011.4.2 
Definition  (see  Doors),  202.0 
Dressing  rooms,  412.5.2 
Exterior  walls,  706.0 
Fire  partitions.  71 1.3 
Fire  separation  walls.  709.3 
Firewalls,  708.3 
General,  704.3,716.0 
Horizontal  exits,  1019.2.1 
Proscenium  walls,  412.3.5 
Shafts,  710.3.1 
Smoke  barriers,  712.3 
Siage  enclosures,  412.3.4 


Stairways.  1014.9 
Wired  glass,  716.4,  719  0 

Fire  escapes 

General,  1025.0 

Maintenance  of.  1028.0 
Fire  extinguishers,  920.0 
Fire  protection  systems 

Area  increased  by.  506.3 

Automatic  fire  detection  systems,  918.0 

Automatic  fire  detection,  where  required.  918.4 

Carbon  dioxide  extinguishing  system.  909  0 

Design.  903.1.3 

Dry-chemical  extinguishing  system.  910  0 

Fire  department  connection.  915.0 

Foam-extinguishing  system,  91 1.0 

General  requirements.  901.0 

Halogenated  fire-extinguishing  system,  912.0 

Height  increased  by,  504.2 

Limited  area  sprinkler  system.  907.0 

Manual  fire  alarm  system.  917.0 

Manual  fire  alarm  system,  where  required.  917.4 

Nonrequired  systems,  901 .3 

Outside  sprinklers.  706.2 

Plans  and  specifications,  903  0 

Smoke  control  systems.  921.0 

Standpipes,  where  required.  914.2 

Supervision,  923.0 

Suppression  system  selection,  905  0 

Temporary  standpipe  requirements,  3305.3 

Water-spray  fixed  systems,  908  0 

Water  sprinkler  system,  906.0 

Where  required,  904  1 

Yard  hydrants  916.0 
Fire  pumps,  power  source,  403.9. 1 .3 
Fire  separation  distance.  202.0,  507. 1.  Table  602.  705.0 
Fire  shutters.  718  0 
Fire  suppression  system  (see  Automatic  fire  suppression 

systems) 
Fire  towers  (see  Smokeproof  enclosure),  1015.0 
Fire  walls',  707.0 
Fire  windows,  718.0 
Fireplaces.  21 14.0,  3610.0 
Fireresistance  ratings 

Assemblies,  Table  602,  704.0 

Definition,  202.0 

Exterior  opening  protectives.  706.0 

Exterior  walls,  705.0 

Fire  dampers,  717.0 

Fire  doors,  716.0 

Fire  partitions,  7110 

Fire  separation  walls.  709.0 

Fire  wall  openings,  708.0 

Firewalls,  707.0 

Fire  windows,  718.0 

Floor  construction,  709.0,  713  0 

General,  701.0 

Plans  and  specifications,  703. 1 

Roof  construction,  714.0 

Shafts,  710.0 

Smoke  barriers,  712.0 

Special  requirements,  504.6.  504.7 

Structural  members,  715.0 

Tests,  704.0 


814 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Fireresistance  ratings  of  structure  elements.  Table  602 
Fireretardant-treated  wood 

Labeling,  2310.2.2 

Strength  modifications,  23 10.2. 1 

Tests,  2310.2 

Use  limitations,  23 10. 1 
Fires  topping 

Architectural  trim,  720.6.5.1406.2.4 

Between  wood  sleepers,  806.2 

Definition,  202.0 

Floor/roof  ceiling  assemblies.  720.0,  720.7.1,  3606.2.7 

General  requirements,  720.0,  720.1 

Of  attic  spaces,  720.0.  720.7.2 
Flagpoles,  1510.1 
Flameresistance 

General,  807.2 

Interior  floor  finishes,  805.0 

Interior  hangings  and  decorations.  807.0 

Interior  trim.  803.5 

Interior  wall  and  ceiling  finishes.  803.4 

Tests.  807.2.2 

Textile  wall  coverings,  803.6 
Flammable  liquids,  307.0.  417.0,  418.0 
Flashing.  1405.3.10 
Floodproofing.  3107  0 
Floor 

Area,  503.0,  Table  503,  506.0.  507.0 

Assemblies,  construction.  713.0 
Dmbustible  materials  permitted  in  Types   1   and  2 
construction.  602.4,  806.0 

Concrete,  3605.5 

Metal.  3605.6 

Treated-Wood,  3605.4 

Wood,  3605.2 
Floor 

Area,  definition,  202.0 

Level  of  exit  discharge  protection.  1006.3. 1 

Loads,  1606.0 

Public  garages,  408.3.3 

Ratproofing,  1215.0 

Theater  stages,  412.3.1 

Wood  panel  sheathing.  2307  3. 1 
Floor  openings 

Atriums,  404.0 

Public  garages,  408.3  3 

Shaft  enclosure  exceptions,  713.3 
Floor  surface  at  doors.  1017.1.1 
Foam-extinguishing  systems,  91 1.0 
Foam  plastics 

Diversified  tests,  2603.8 

Exterior  walls,  2603.4.1.8 

General,  2603.1 

Insulation,  722.0,  2603.4.1.5 

Interior  finish  and  trim,  804.3.1,  2603.7 

Labeling.  2603.2 

Prescriptive  installations,  2603.4.1 
Footings 

Allowable  loads.  1804.0,  1805.0 

Concrete,  design.  1810.0,  3605.2 

Depth,  1806  0 

Design,  1807.0 

Forming,  1810.6 

Frost  Protection  1806  1 

Masonry,  1811.0 


Prepared  fill,  1705.7 

Reinforced  concrete.  1810.3.2 

Soils  report.  1804.1 

Steel  grillage,  1809.0 

Timber.  1808.0 
Formed  steel  construction.  2206.0 
Foundation  systems 

Allowable  loads.  1805.0 

Caissons.  1824.0 

Cnpple  walls.  3606.2.8 

Design.  1812.1 

Footings  (see  Footings) 

For  neighboring  building.  33 10.2 

May  project  beyond  property  line.  3202.4 

Minimum  depth.  1806.0 

Minimum  thickness.  1812.3 

Piers,  1815.0 

Piles,  1816.0  through  1824.0 

Ratproofing,  1215.1 

Steel  grillage.  1809.0 

Walls  1812.0 

Wood  and  timber.  1808.0 
Frame  construction,  wood 

General  requirements.  2303.0.  2305.0.  2306.0 
Frost  protection 

Depth  of  footings.  1806.2 


Garages 

Beneath  a  dwelling,  407.3 

Construction  of  public  garages.  408  3 

Definition,  202.0 

Fire  doors,  407.6 

Open  Parking  structures.  4060 

Private.  407.0 

Public.  408.0 

Separations,  407.3.  407.4.  407.7 

Storage  of  flammables.  408.4.  408.5 

Ventilation.  408.5 
Garages,  private 

Connected  to  dwelling.  407.3.  407.4.  407.7,  3603.. 

Definition.  202.0 

Use  Group  U,  utility  and  miscellaneous,  3 12  0 
Garages,  public 

Construction  limited,  408 .3 

Definition.  202.0 

Fire  suppression  system  required.  408.3. 1 

Use  Group  S-l.  storage.  31 1.0 

Ventilation  required.  408.5 
Gardens,  roof,  1008.3 
Gas 

Hazardous,  307.0,  417.0.418  1 
Glass  and  glazing 

Area  required  for  natural  light.  1206  2.  1208.2 

Atrium  enclosure.  404.5 

Biock  reinforcement.  2115  4 

Block  walls.  2105.5.  21 15.0 

Dimensional  tolerances.  2402.4 

Doors.  2405.2 

Fire  windows.  718.0 

Greenhouses,  2404.4 

Guards.  2406.0 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


815 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Handrails,  2406.0 

Impact  loads,  2405.1 

In  fire  doors,  718.0,  719.2 

Jalousies,  2402.5 

Labeling,  2402. 1 

Plastic  (see  Light-transmitting  plastics) 
.  Protected  openings,  718.0,  719.0 

Racquetball  and  squash  courts,  2407.0 

Safety,  2405.0,  3603.20.4 

Skylights,  2404.0 

Sloped,  2404.0 

Supports,  2402.2 

Unsupported  edges,  2402.3 

Veneer,  structural,  1405.7 

Wind  loads,  1611.0,2403.1 

Wired  glass,  719.0 
Glazed  masonry  units,  2105.2 
Glazing  (see  Glass  and  glazing) 
Glued-laminated  lumber  construction,  23 13. 1 
Grade 

Definition,  202.0 

Depth  of  footings  and  foundations  below,    1806  0, 
1808.0,  1810.0,  1812.0 
Grading  a  lot,  33 10.4 
Grain  processing  and  storage,  418.3.1 
Grandstands,  1002.1,  1013.0 
Greenhouses 

Glazing,  2404.4 

Membrane  structure  materials.  3 103.3.2 
Grounding 

Metal  veneer,  1405.4.3 

Radio  and  television  antennas,  3 109.3 

Radio  and  television  towers.  3 108.5 
Group  homes 

Use  Group  1-1,  institutional,  308.0 
Grout  (also  see  Mortar),  2105.0 
Guards 

Balconies,  1005.5 

General,  1021.0,  3603.14.2 

Glass  in,  2406.0 

Open  parking  structures,  406.5 

Retaining  walls.  1 825.5 

Stairways,  1014.7 

Structural  design,  1615.5,  1615.8 

Wheel  406.6, 408.3.2 
Gutters 

For  roof,  3203. 11.3 

Materials.  1406.0 
Gypsum 

Construction,  2504.0 
Gypsum  board 

Installation,  2503.3 

Materials,  2503.0 

Standards.  2503.2,  3607.2.3 


H 

H,  use  group,  high-hazard,  307.0 
Habitable  space 
Definition.  202.0 


Halogenated  extinguishing  systems.  912.0 
Handicapped  and  aged,  requirements  for,  Chapter  II, 

3006.3 
Handrails 

Details,  1022.2 

General,  1022.0,3603.14 

Grandstands  and  bleachers,  1022.0 

Ramped  aisles,  1012.5 

Ramps,  1016.5,  1022.2 

Retaining  walls,  1825.5 

Stairways,  1014.7.  1022.2 

Structural  design.  1615.5 

Hardware  on  exit  doors,  1017.4 

Hazardous  uses 

General,  416.0, 417.0.  418.0 

High-hazard,  307.0 

Low-hazard.  311.1 

Moderate-hazard.  3 1 1.2 

Production  materials  (HPM).  416.0 

Prohibited  locations,  3 13.2 

Storage  segregation.  417.0 
Headroom 

Ceiling  heights,  1204.1 

Ramps,  1016.2.2 

Stairways,  1014.4 
Hearth  for  fireplace,  21 14.5, 3610.4.5,  3610.5.1 
Heated  space,  definition,  202.0 
Heating  systems 

Fireplaces.  21 14.0 

Gas-fired  equipment  2801.2 

General  requirements,  280 1  0 
Heavy  timber  construction,  605.0,  2306. 1 
Height 

Awnings,  3203.9,  3203.10 

Buildings  (see  Height,  buildings) 

Ceiling,  1204.1,3603.8 

Guards,  1021.2 

Handrails,  1022.2.2 

Marquees.  3203.11.1 

Masonry  veneers.  1405.5.1 

Parapet  walls,  705.6 

Permissible  street  projections.  3203.0 

Stairway,  maximum  vertical  nse,  1014.5 

Towers,  spires,  cupolas,  aerial  supports,  poles,  etc., 
1510.0 
Height,  buildings 

Airport  traffic  control  towers,  414.0 

Allowable,  503.0,  Table  503 

Alterations  for  existing  buildings,  3403.1,  3404.4 

Covered  mall  buildings,  402. 1,  402.7 

Day  care  centers,  504.4 

Definition,  202.0 

High-rise,  403. 1,403.3.3.1 

HPM  facilities,  416.3 

Membrane  structures,  3103.3.5 

Modifications,  504.0 

Open  parking  structures,  406.4 

Restrictions,  503.3,  507.1 

Special  industrial  uses,  503.1.1 

Unlimited  area  buildings.  507.0 


816 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


High-hazard 

Accessory  areas  to,  302. 1.2. 1 

Application  of  flammable  finishes,  419.0 

Classification,  302.1.2.1 

Control  areas,  307.8,  417.2 

Definition,  307.2 

Exceptions,  307.8 

Exempt    quantities,    307.8,    Table    307.8(1).    Table 
307.8(2) 

Explosion  control.  417.5. 1 

Flammable  and  combustible  liquids.  418.3.2 

Hazardous  materials,  417.0 

Liquefied  petroleum  gas  distribution  facilities,  418  3.3 

Multiple  hazards,  307.7 

Outside  storage,  dispensing  and  utilization,  417.6 

Unlimited  area  structures.  507.1,  507.1.2 

Use  group  requirements,  417.0,  418.0 

Use  group  structure  height  exemption.  504.5 

Use  groups.  307.0 
High-rise  buildings 

Alarm  and  communication  systems.  403.5. 403.6 

Applicability,  403.1 

Automatic  sprinkler  system,  403.2, 403.3 

Central  control  station,  403.7 

Elevators.  403.8 

Emergency  systems,  403.9 

Exits  in,  403.10 

Maintenance  and  inspection,  901.4 

Seismic  consideration  in,  1612  6 

Smoke  detection  systems,  403.4 
Historic  buildings  and  districts.  3409  0 
Homes  for  aged 

Use  Group  1-1,  institutional,  308  2 
Horizontal  exits 

Definition  (See  Means  of  egress),  202.0 

General  requirements.  1019.0 
Hospitals 

Use  Group  1-2,  institutional.  308.3 
Hotels 

Definition  (see  Dwellings),  202.0 

Use  Group  R-l.  residential.  3 10.3 
House,  lodging 

Use  Group  R,  residential,  310.0 
HPM  use  facilities,  416.0 
Hydrants,  fire  yard  systems,  916.1 


I 


Insane  asylums 

Use  Group  1-3.  institutional,  308.0 
Inspection 

By  code  official,  105  4,  106  4.  115  0 

Final.  115.5 

Of  electrical  wiring,  2704.0 

Of  existing  buildings,  106  4 

Of  heatmg  systems,  2804  0 

Of  prefabricated  construction.  113  2.2 

Of  signs,  3102.5.4 

Of  unsafe  buildings.  121  0 

Required  preliminary,  1 15.1,  1 15.2 

Special.  202.0,  1705.0 
Insulation 

Fiberboards  for  roof,  2309.3 

Fiberboards  for  wall.  2309  4 

Foam  plastics.  803.3.1.  2603  0 

Thermal  insulating  materials,  requirements.  722  0 
Interior  environmental  requirements.  Chapter  12 
Interior  finish  and  tnm 

Application  of,  804  0 

Classification  of  materials.  803.2.  803.4 

Decorative  material  restrictions.  807  1 

Flame  spread  of.  803.2,  803.4 

Flameresistance  tests,  807.2 

Floor  finishes,  805. 1,  805.2 

Foam  plastics,  803.3.1.2603.0 

General  requirements,  803  0 

Lath.  3607.2.2 

Plaster,  3607.2.2 

Restrictions  in  Types  1  and  2  buildings,  806.0 

Special  amusement  buildings,  413.6 

Textile  wall  coverings,  803.7 

Use  group  requirements,  803.4.  Table  803.4 
interior  iot  lines 

Definition  (See  Lot),  202.0 


Jails 

Use  Group  1-3.  institutional,  308  4 
Jalousies 

Windows  and  doors.  2402.5 
Jurisdiction 

Adopting  this  code,  101.1 


I.  use  group,  institutional,  308.0 
Identification  for  plastics,  260 1 .4 
Identification  for  signs,  3 102.4.5 
Illuminated  signs.  3102.13 
Industrial 

Use  Group  F,  factory  and  industrial,  306  0 
Industrial  heating  appliances,  classification.  2801  2. 
Infirmaries 

Use  Group  1-2.  institutional,  308.3 
Inner  court 

Definition  (see  Courts),  202.0 


Label,  definition,  202.0 

Labeling.  1703.1.1,  1704.3 

Landing  of  stairs,1014.3.2.  1014.5 

Landings  of  ramps,  1016.4 

Lathing  and  plastering,  2505.0.  2506  0 

Liability,  code  official,  105.7 

Licenses 

Fees  for,  1 14.0 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


817 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Light,  illumination 

Artificial,  1207.0,3603.6.5 

Court  requirements  for,  1212.0 

For  existing  buildings,  3401  0 

For  exit  signs,  1023.0 

General,  1201.0 
-  Natural.  1206.0 

Required,  1205.0 

Window  requirements,  1206  2 
Light-transmitting  plastics 

Approved  types,  2604. 1 

Bathroom  accessories,  2604.7 

Connections,  2604.3 

Definition  (see  Plastics),  202.0 

Glazing  of  unprotected  openings.  2606  0 

Light-diffusing  systems,  2604.5 

Partitions,  2604.6 

>Roof  panels.  2607.0 

Skylights.  2608.0 
Lmen  chutes,  2807.0 

Lintel 

Fire  protection,  715.2 

Masonry  support,  1405.5.2 

Over  openings,  frame  construction,  2305. 1 1 

Liquids 

Flammable  and  combustible,  307.4,  417.3, 418.3.2 
Liquefied  petroleum  gases,  307  4,  418.3.3 
Load  design,  1604  0.  1605.0.  1607.0.  1708.0 
Load  earthquake  (see  Earthquake  design) 

Load,  glass 

Impact  loads.  2405.1 

Jalousies,  2402.5 

Wind  loads,  2403.1 
Load,  impact 

Assembly  structures,  1614.5 

Craneways,  1614.4 

Definition.  202.0 

Elevators,  1614.2 

General.  1614.1 

Machinery,  1614.3 
Load  (live,  dead,  floor) 

Combination  of,  1616.0 

Concentrated,  1613.0 

Craneways,  1614.4 

Definition,  202.0 

Deflections  allowable,  1604.5 

Documentation  of.  1603.0 

Earthquake,  1612.0 

Floor  loads,  occupancy,  1606.1,  Table  1606  1 

Footings  and  foundations,  1805.0,  1807.0 

For  concrete  footings,  1807.0,  1810.0 

For  retaining  wall  design,  1615.2 

Glass  (see  Load,  glass) 

Guards,  1615.8 

Impact  (see  Load,  impact) 

Interior  finish,  803.7 

Piles,  allowable,  1817.0 

Railings.  1615.5 

Reductions  allowed,  1608.0 

Roof,  1609.0,  1611.0 

Snow,  1610.0,  3603.1  5 

Soil,  bearing  capacity.  1804  0 

Special,  1615.0 

Tests,  1604.3 

Uniform,  1606.0 


Wind  (see  Load,  wind) 
Load,  wind 

Chimneys,  1611.12 

Exterior  walls.  1611.0 

General  requirements.  161 1  0 

Glass,  2403.1 

Roofs.  1609.0.1611.10.  1611  11 

Signs.  1611.12.2 
Lobbies  and  passageways  as  exits.  1020.0 
Lodging  houses 

Definition  (see  Dwellings).  202.0 

Use  Group  R  residential,  310  0 

Lot 

Definition,  202.0 

Interior  lot  line,  definition  (see  Lot  line),  202.0 

Line  fences,  331 1.1 

Regulations  for.  33 10.4.  33 10.5 
Lumber  (also  see  Wood  construction) 

Grade  of.  2301. 1.3606.2.2 


M 


M,  use  group,  mercantile,  309.0 
Maintenance 

Of  exit  facilities.  1028.2 

Of  fire  protection  systems.  901  4 

Of  signs.  3102.5.2 
Malls,  covered,  402.0 
Manlifts.  3000.1 

Manual  fire  alarm  systems.  917.5. 1 
Marquees  and  canopies 

Construction  requirements.  3105.0.  3203.11.5.  3205.3 

Definition  (see  Signs),  202.0 

Drainage  of  water.  3203.1 1.3 

Signs.  3102.11.  3203  II 

Masonry 

Anchorage.  21 1 1.0,  3606.4. 10 

Attachment,  3607.3.7.2 

Bonding.2110.0.211i.2.i 

Brick.  2105.0 

Cavity  wall,  3606.6 

Chases  and  recesses,  2113.1 

Concrete  units,  2105.1 

Construction  requirements,  21 12.0 

Corbeled  and  protected,  21 12.2 

Cornices,  2112.2.1 

Definition,  202.0 

Design,  2101. 1.1,  2101. 1.2 

Fireplaces,  21 14.0 

Footings,  1811  0 

Foundations,  1812.3.2 

Freezing  protection.  21 12.3 

General,  3606.4. 1 

Glass  block,  21 15.0 

Glazed  units,  2105.2 

Grouted,  3606.7 

Hollow,  definition  of,  202.0 

Hollow  units.  2105.1,3606.5.1.2.2.  3606.7 

Lateral  bracing,  2106.0. 2108.0 

Lintels,  21 13  2 

Minimum  thickness,  2 1 09  1 . 1 

Mortar,  2105.7 

Reinforced,  2101.1.1,  3606.7.3 


818 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Reuse  of.  2105  6 

Solid,  definition  of.  202  0 

Solid  units.  2105.1.  2105.2 

Stone,  cast.  2105.3 

Stone,  natural.  2105.3 

Support  on  wood,  2113.3 

Tests,  general.  1701.0 

Tile,  structural,  2105.2 

Veneers.  1405.5.3 
Matches 

Use  Group  H.  high-hazard.  307.0 
Materials 

Alternative.  1701.2 

Approvals.  1704  0 

Used.  1701.3 
Matters  not  pro\  ided  for.  102.3 
Means  of  egress 

Aisles  and  aisle  accessways.  1012.0 

Arrangement.  1006.2 

Buildings  with  one  exit.  1010  3.  Table  1010.3 

Capacity.  1009.0 

Corridors.  1011.0 

Corridors    and    passageuass.    required    width    for. 
1011.3.  1012.0 

Definition.  202.0 

Doors,  revolving.  1018.0 

Doorways.  1011.4.2.  1014.8.  1017.0.  1018.0.  1019  2.  i 

Elevator  and  escalator  restrictions.  1006.6 

Exit  signs.  1023  0 

Exterior  exit  stairways.  1014.12 

Fire  escapes,  1025.0 

From  places  of  assembly.  1 006.2.2 

General  provisions.  1001.0 

Hardware.  1017  4 

Hazards  to.  1005.0 

Horizontal  exits,  1019  0 

Interior  exit  stairways.  1014.0 

Length  of  travei.  1006.5 

Level   of  exit   discharge   passagewavs   and   lobbies. 
1020.0 

Lighting,  1024.0 

Location  and  type  of.  1006  0 

Maintenance  of  exits,  1028.0 

Number  of  exits  required,  1010  0 

Occupant  load.  1008.0 

Opening  protectives.  1011.4 

Passageways  and  corridors   1011.0 

Prohibited  use,  1005.0 

Ramps.  1016.0 

Slidescapes.  1026.0 

Smokeproof  enclosure.  1015  0 

Spiral  stairways.  1014.6.4 

Stairway,  construction.  1014.9 

Through  adjoining  spaces.  1006.2.1 

To  roof.  1027.0 

Mechanical  ventilation  (see  Ventilation) 
Membrane  structures 

Definition.  202.0 

General.  3103.1 
Metal  siding 

Corrosion  protection,  1405.3.8 

Thickness.  1403.3 


Mezzanines 

Definition.  202.0 

General.  505.0 
Miscellaneous  buildings 

Use  Group  U.  utility  and  miscellaneous.  5 12.0 
Miscellaneous  signs.  3 102.0 
Mixed  uses.  313.0 
Mobile  units,  requirements.  420  0 
Modification  of  code  provisions 

By  board  of  appeals.  122.0 

Of  area.  506.0 

Of  height.  504.0 

Variations,  105.6.  106.2.  1064 

Written.  106.2.1 

Mortar.  2105  7.2112.0 
Motion  picture  film  storage.  4 1  1  i 
Motion  picture  projection  and  screening  rooms.  4 1  1 
Motion  picture  screening  rooms.  41  i. 6 
Motion  picture  studios.  4117 
Moved  structures.  3407  0 
Multiple  dwelling 

Definition  (see  Dwellings).  202.0 

Use  Group  R-2.  residential.  3 10.0 


Nails 

Fastening  schedule.  2305.2.  Table  2305  2 
New  materials  or  methods  of  construction 

Alternative   materials   and   methods   of  construction. 
106.4.  1701.0 

Board  of  adjustments  and  appeals.  121.1 
Noncombustible  construction 

Definition.  202.0 

General  603.0 
Noncombustible     material     (see     Definitions).     202.0. 

704.4  1  j 

Notices 

Board  of  appeals  meeting.  i2i.3 

Of  violations.  1 16  1 

Of  work  starting.  108  9 

Posting  occupancy  load.  1003.2.  1003.3 

Postmg  permits.  108  8 

Stop  work  order.  1 17.0 

Unsafe  buildinas.l  19.3.1 19.4.120. 1 


o 

Occupancy 

Certificate  of.  120.0 

Change  m  occupancy.  3405.0 

Covered  by  code.  102.0 

Definition,  202.0 
Occupant  load 

Allowances,  1008.0,  Table  10( 

Definition.  202.0 

Maximum,  1008.1  5 

Posted.  1003.3 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


819 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Occupiable  room,  definition,  202.0 
Office  buildings 

Use  Group  B,  business,  304.0 
Oil  storage,  2801.2 
Open  parking  structures 

Height  and  area,  406.4 

Protective  railings.  406.5 

Type  of  construction  permitted,  406.2 

Use  Group  S-2,  storage,  low-hazard.  31 1.0 

Wheel  guards  required,  406.6 

Openings 

Exterior  opening  protectives,  706.0 

Horizontal  protection,  705.3 

In  fire  partitions.  7110 

In  floors,  713.3 

In  shaft  enclosure  walls.  710.3.1 

On  or  near  exterior  stairways,  1014. 12.2 

Protected  with  fire  doors  or  windows.  704.3 

Vertical  protection.  705.5 
Ordinary  repairs.  3401.2 
Oriel  window 

Definition,  202.0 

Materials.  3203.2 
Owner 

Definition,  202.0 

Responsibility,  1401.2 


Paint 

Of  formed  steel,  2206.4 
Of  structural  steel,  2203.5 
Spraying  and  spray  booths,  419.0 
Storage,  419.2.3 

Panel  walls 

Glass  block,  21 15.0 

Thickness.  1404.6 
Panels 

Stressed  skin,  2313.2 
Panic  hardware,  on  exit  doors,  1017.4 
Parapet  wall,  705.6,  707.5 

Parking  structure,  open  (see  Open  parking  structures) 
Particleboard 

Definition,  202.0 

Requirements,  2308.0,  3606.1 1 
Party  walls 

Affected  by  excavations,  33 10.0 

Construction  of,  707.0 

Continuity,  707.5 

Definition  (see  Walls),  202.0 

Parapets  required,  707.5 

Size  and  construction  of  openings,  708.2 
Passageways 

Corridors,  1011.0 

Horizontal  exits,  1019.0 

Lobbies  as  exits,  1020.3 

Obstructions  prohibited,  1028.1 
Pedestrian  walkways,  3 106.0 
Penalties  and  violations,  provided  by  code,  1 18.0 


Penthouse 

Definition.  202.0 

General  requirements,  1510.3 

Permits 

Action  on  applications,  111.1 

Amendments  to,  110  14 

Application  for,  110.4.  110.13.  110.14 

Approval  in  part,  1 10.2.2 

Awnings,  3205.1 

Conditions  of,  111.0 

Definition,  202.0 

Electrical,  Chapter  27 

Examination  of  drawings,  108.5 

Expiration,  110.14 

Fees,  114.0 

For  awnings  and  canopies.  3205. 1 

Issued  upon  affidavits.  1 10. 12 

Posting  of.  111.14 

Records  to  be  kept  106.6,  106  7 

Required,  107  1 

Revoked,  111  12 

Signs,  3102.4 

Suspension  of.  108.2 

Temporary,  110.2.1 

Time  limitation,  1 10. 14 

To  demolish  buildings  1 12.0 

To  move  buildings.  3407  0 

Validity.  103.0 

Valuations,  112.0 
Petroleum  storage 

Flammable  and  combustible  liquids,  417.0.  418.0 

Liquefied  petroleum  gases,  418.3.3 

Piers 

Isolated  masonry,  2 1 10.0 

Piles 

Cast-in-place  concrete,  1820.0 
Composite,  1823.0 
Foundations,  1816.0 
Loads  allowable,  1817  0 
Precast  concrete.  1821.0 
Special.  1824.0 
Steel  pipe  and  tubular.  1819.0 
Structural  steel.  1818.0 
Timber.  1822.0 

Pipe 

Columns,  concrete-filled,  19 12.0 

Piles,  1819  0 
Plans  and  specifications 

Approval  of,  108.5 

Changes  in,  107.1 

Required,  107.5,  107.6 
Plastering  and  lathing 

Application,  interior,  2505.1 

Exterior,  3607.3.6 

Fireresistance  requirements,  721.0 

General  requirements,  2505  0.  2506.0 

Gypsum  plaster,  2505.0 

Interior    lathing    and    gypsum    plastering,    2505.0, 
3607.2.2 

Materials.  2505.0 

Portland  cement  stucco,  2506.0 


820 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Plastics 

Approval  for  use,  2601.3 

Approved.  2601.2 

Bathroom  accessories,  2604 .7 

Definition,  202.0 

Design  and  installation.  2604.0 

Fastenings.  2604.0 

Foam,  803  3.1.2603.0 

Glazing  of  unprotected  openings.  2606.0 

Interior  finish  and  trim.  803  0 

Light-diffusing  systems.  2604.5 

Of  signs,  3102.64  2 

Partitions,  2604.6 

Roof  panels.  2607.0 

Scope  and  use.  260 1  1 

Skylights.  2608.0 

Structural  requirements.  2604.2 

Thermoplastics,  definition.  202.0,  2604. 1 

Thermosetting,  definition.  202.0.  2604.1 

Veneer.  2605.1 

Wall  panels  exterior.  2605. 1 
Platforms 

Construction  of.  412  4 

Fire  suppression,  4 12.6 
Plenums,  1005  7,  2805.0 
Plot  plan,  required.  110.10 
Plumbing 

Certificate  of  approval.  2904.3 

Existing,  2908.0 

Permits,  2904.0 

Plans  and  specifications,  2902.0,  2904. 1.  2904.2 

Sewer  and  water  supply  data,  3404.0 

Violations.  2904.5 

Water  supply  systems.  2905.0 
Plywood.  2307.0.  3607.3.3.  3606.10 
Portable  signs.  3102.14 
Positive  heat  supply,  definition.  202.0 
Posting 

Occupant  load.  1003.3 

Permits.  111.14 

Unsafe  building.  121.0 
Projecting  signs.  3  1 02. 10 
Projection  rooms 

Construction  of.  4 1 1 .2 

General  requirements,  41 1.0 

Ventilation  of,  411.3 
Projections  from  buildings 

Awnings  and  canopies.  3203  9.  3205.0 
Projections 

Balconies  and  stairs.  3203  8 

Bay  windows,  3203.7 

Below  sidewalk,  3202  2 

Belt  courses,  3203.4 

Cornices  and  eaves,  3203.3 

General.  3201.1 

In  alleys.  3204.0 

Marquees,  3203.11 

Signs,  119.0.3102.11.3202  10 

Special  and  temporary.  3204.0 

Street  encroachments.  3202.0 

Street  projections,  permissible,  3203.0 

Yard  and  court.  1213.0 


Protected  construction 

Definition,  202.0 
Protection  against  corrosion 

Formed  steel,  2206.4 

Structural  steel,  2203.5 
Protection  against  dampness 

Of  crawl  spaces.  1210.2 

Of  foundation  walls,  1813.0 
Protection  against  decay  and  termites,  23 1 1  0.  3603.22 
Protection  during  construction 

During  wrecking.  3304.0 

Of  adjoining  property,  3308  0 

Of  excavation.  33  10.0 
Protection  of  exterior  openings 

Of  exterior  wall.  706.0.  718.0 

Of  fire  wall  opening.  708.0 
Public  assembly 

Use  Group  A.  assembly,  303  0 
Public  way,  definition.  202.0 


Q 


Qualifications 

Of  board  of  appeals,  121.2.1 


R 


R.  use  group,  residential.  3 10.0 

Radio  antennas  and  towers,  3 108.0.  3 109  0 

Rafters 

Grade  of  lumber.  3608.2 

Railings  (see  Handrails) 

Ramps.  1016  0 

Ratproofing.  1215.0 

Recesses  (see  Masonry  and  Walls) 

Records 

Of  decisions,  121.6 

Of  departments,  104.7 

Recreation  buildings 

Use  Group  A.  assembly.  303.0 
Reductions,  live  load.  1608.0 
Refineries 

Use  Group  H.  high-hazard.  307  0 
Reformatories 

Use  Group  1-3,  institutional.  308  0 

Refuse,  chutes,  2807.0 
Refuse  vaults.  2808.0 
Reinforced 

Definition,  concrete,  202.0 

Foundation  walls,  concrete,  1812.3.1 

Grouted  masonry.  3606.7.3 

Gypsum  concrete.  2504  0 

Hollow-unit  masonry.  3606  5  1.2.2.  3606.7.4 

Masonry,  foundation  wails.  1812  3.2 

Walls.  1812.0 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


821 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Reinforced  concrete  (also  see  Concrete) 

Definition  (see  Concrete),  202.0 

Design,  1901  1 

Footings,  181 10 

Gypsum,  2504.0 

Pipes  in,  1909.3 
Removal 

Of  buildings  and  structures,  121.3 

Of  waste  during  construction,  3313.0 
Repair 

Of  existing  buildings,  107.1.1,3401.2,3404.0 

Of  unsafe  buildings  or  structures.  121.0 

Permit  not  required,  107.1.1 

To  roofs  of  existing  buildings,  15 12.0 
Repair  shops,  motor  vehicle 

Definition  (see  Garage,  public),  202.0 

Public  garages,  408.0 

Use  Group  S-l.  storage,  moderate-hazard.  31 1.0 
Residential  buildings 

Sound  transmission  control,  1214  0 

Use  Group  R  310.0 
Restaurants 

Use  group  A-3,  assembly,  303.0 
Restrictions 

Area,  503.2 

Height,  503.3 

On  employees,  104.5 

Special  occupancy.  401.0 
Retail  stores 

Use  Group  M.  mercantile,  309.0 
Retaining  wall 

Definition  (see  Walls),  202.0 

Design,  1825.2 

General,  1825.1 

Guardrails  for,  1825.5 
Reviewing  stands ,  1013.0 
Revocation  of  permit,  111.12 
Revolving  doors.  1018.0 
Right  of  entry,  113.4 
Risers  for  stairways  (see  Stairwavs) 
Roof  construction 

As  required  by  type  of  construction,  603.0.  604.0. 
605.0,606.0 

Builtup,  3609.7 

Cooling  towers.  1510.8 

Covering,  1503.0,  3609.0 

Definition  of  roof  structure.  202  0 

Drainage,  3608. 1.3 

Fireresistance  requirements.  Table  602 

Flashing,  3607.3.8 

Loads,  1609.0,  1611.0 

Mansard  or  ordinary  construction,  510.5 

Of  approved  plastics,  2604.1,  2607.0 

Parapets  above,  705.6,  707.5 

Ponding  1609.5 

Stadiums,  714.2 

Wind  loads,  1611.0 

Wood  construction,  2305. 15 
Roof  covering 

Classified,  1506.0 

General.  Chapter  15 
Roof  signs,  3102.8 


Roof  structures.  1510.0 

Roofing  repairs  on  existing  buildings.  15 12.0 

Room  size,  3603.7 

Rooming  houses 

Use  Group  R  residential,  3 10.0 
Rubbish  chutes.  2807  0 
Rubble  stone  foundation  walls.  1812.3.4 
Rule-making  authority 

Promulgated  by  code  official,  108.0 
Rust  protection 

For  formed  steel,  2206.4 

For  structural  steel.  2203.5 


S,  use  group,  storage.  3110 

Safe  loads  on  soil.  1804  0 

Safeguards  during  construction,  3301.0 

Safety  devices  for  window  cleaning,  3 1 10.0 

Sanitariums 

Use  Group  i-2.  institutional.  308  0 
Scale  of  plans,  107.5 
Schools 

Use  Group  E.  educational.  305.0 
Scope  of  code 

General  101.0 
Screening  rooms,  motion  picture,  411.0 
Screens  for  skylights,  2404.3 
Scuttle 

Scuttle  size  and  construction.  15 10.2 
Seating 

Aisles  and,  1012.0 

Folding  and  telescopic,  1013.0 
Seismic  (earthquake)  design 

Concrete.  1903.0.  1904.0 

Foundations.  1810.2.1.  1815.2,  1816.3,  1816.11.1. 
1818.3.  1819.3.1.  1820.1.2.1.  1820.5.4,  1821.3.5. 
1821.3.6.  1824.3 

Inspection  related  to,  1705.3.3.2,  1705.4.5.  1705.9. 
1705.10.  1705.11 

Loads.  1612.0 

Masonry,  2101.2.  2104.0 

Soils,  1802.1.1,  1805.2,1805.3 

Steel,  2203.2.  2203.2.1,  2204.0,  2206.3, 2207.2.1 

Wood,  2305.8, 2305.9,  2306.0 
Shaft 

Definition,  202.0 

General,  710.0 
Shall,  definition,  202.0 
Sheathing 

Floor.  2307.3. 1.2307.3.2 

General  requirements  for.  2307.0.  2308.0,  2309.0 

Roof,  2305. 15. 1,  2307.3. 1,  2308.4 

Subfloor,  2307.3.3 

Wall,  2305.13 
Shed 

Sidewalk,  3304.4 


822 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


Shingles  and  shakes 

Asphalt  shingles,  3609 .3 

Materials.  1507.0 

Metal,  3609.5 

Slate,  3609.4 

Tile,  clay,  or  concrete,  3609.6 

Wood  shakes,  3609.9 
Shutters 

Shutters  on  exterior  wall  openings,  718  0 
Sidewalks 

Bridge,  3304.3 

Elevated  pedestrian  walkways,  3 1 06.0 
Siding,  3607.3.2 

Minimum  material  requirements.  1403.3 
Signs 

Alley,  119.2.4 

Alterations  to,  119.0 

Banner  and  cloth.  3102.12.1 

Definition.  202.0 

Design  loads,  3 102.6,  3 102. 10  4 

Doors,  1017  4.1,  1017.4.1.2 

Exemptions,  31024.3 

Existing,  102.2 

Extending  over  curb  prohibited,  3 102. 10.2 

For  exits.  1023.0 

General  requirements.  3 102.6 

Ground.  3 102.7 

Identification.  3102.83 

Illuminated,  3 1 02.6.3, 3 1 02. 1 3 

Inspection  of.  3102.5.4 

Maintenance,  3 102.5.2 

Marquee.  3102.11 

Miscellaneous^  102. 12 

Permits  for,  3102.4 

Plans  and  specifications,  3102.4 

Plastics  for,  3102.6.4.2.  2601.2 

Pole,  3102.7 

Projecting,  3102.2 

Roof,  3102.8 

Temporary,  3102.12 

Unsafe,  unlawful,  119  0 

Wall,  3102.9 

Windloads,1611.0,3102.6.1 
Skylights 

General,  2404.0, 3603.20.5 

Plastic,  2601.2, 2608.1 
Slidescapes,  202.0,1026  0 
Smoke  detection,  3603.16.3 
Smokeproof  enclosure,  202.0.  1015.0 
Snow  load  1610.0,3603.1.5 
Soil 

Bearing,  allowable,  1804.0,  1805.0 

Bearing  capacity,  1804.0,1  805.0 

Prepared  fill,  1705.9,  1804.3.2 

Soils  report,  1804.1,  1804.1.1 

Tests,  1802.0.  1803.0 
Sound  stages,  motion  picture,  411.0 
Sound  transmission  control  in  residential  buildings 

Air-borne  noise,  1214.2 

Scope,  1214.1 

Structure-bome  sound,  1214.3 


Spans 

Allowable,  3605.2.3,  3608.2.4 
Special  fireresistance  requirements 

For  grade  floor  protection,  1 006. 3  1 

For  residential  buildings.  313.3 
Spray  painting 

Booths,  419.2  1 

Construction  requirements  for  booths,  419.2. 1 

Fire  protection,  419.3 

Rooms  419.2.2 
Sprinklers  (also  see  Automatic  fire  suppression  systems) 

Area  increase  permitted.  506.3 

Capacity  of  means  of  egress,  width  permitted  1009  0. 
Table  1009.2 

General  requirements.  901.0.  906.0 

Length  of  travel,  increase  permitted.  1006.5 

Outside.  706.2 

Where  required,  904. 1 
Stadiums 

Roof  construction.  714.2 

Use  Group  A-5,  assembly.  303.6 
Stages 

Construction,  412.3 

Curtain,  proscenium.  412  3.6 

Definition.  412.2 

Fire  suppression,  4 12.6 

Proscenium  wall.  412.3.5 

Rooms,  accessory.  412.5 

Standpipes,  412.7 

Ventilation  of.  412  3  8 
Stairways 

Access  to  roof.  1027.0 

Circular.  3603  13.6 

Definition,  202.0 

Door  to  stairway.  1014.8 

Enclosures,  exterior.  1014.12.2 

Enclosures,  interior.  1014.1 1 

Exterior.  1014.12 

Fire  escapes,  1025.0 

Guardrails.  1014.7,  1021.0 

Handrails.  1014.7.  1022.0 

Headroom  clearance.  10144.3  60313. 3 

Illumination,  3603  13.7 

Landings,  width.  1014.3.2.1014.5 

Means  of  egress,  1010.2.1014.0 

Means  of  egress  lighting.  1024.0 

Rise  between  landings.  1014.5 

Slidescapes,  1026.0 

Spiral,  1014.6.4.  3603.13  5 

Treads  and  risers.  1014.1.1.1014.6,3603.13.2 

Width,  1014.3,  3603. 13.  i 

Wmders.  1014  6.3.  3603.13.4 
Standards,  referenced,  which  governs,  101.6,  102.4 
Standby  power  systems.  2707.0 

Standpipes 

Definition,  202.0 

During  construction.  3305.3 

Water  supply.  914.0 

Where  required.  9 14.0 
Starting  work 

Notice  to  building  official,  108  9 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


823 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Steel,  construction 

Cast-iron  construction,  2209.0 

Cast-steel  construction,  2208.0 

Definition,  202.0 

Fire  escapes,  1025.0 

Grillages  in  footings,  1809.0 

Joists,  open-web  construction,  2205.0 

Light  gage  and  formed  steel  construction,  2206.0 

Painting,  2203.5 

Reinforcing,  2105.9.3,  2105.9.4,  2208.0 

Special  steel,  2207.0 

Structural,  2203.0 
Steel  pipes 

Concrete-filled.  1819.1,  1819.5 
Stone 

Cast,  2105.3 

Foundation  walls,  1812.3.4 

Natural,  2105.3 

Veneer,  1405.5.6 
Stop  work  orders,  1 19.0 
Storage 

Of  combustible  dusts,  grain  processing  and  storage. 

418.3.1 

Of  flammable  liquids.  418.3.2 

Of  liquefied  petroleum  gas,  418.3.3 

Use  Group  S,  storage,  311.0 
Stor%'  above  grade,  definition.  202.0 
Street 

Definition.  202.0 

Encroachments.  3202.0 

Permissible  projections,  3203.0 
Structural  clay  tile,  2105.2 
Structural  glass  block.  2115.1 
Structural  panels,  wood.  Chapter  23 
Structural  requirements  for  plastics.  2604.2 
Structural  steel  (see  Steel,  construction) 
Structure 

Definition,  202.0 

Unsafe,  121.0 
Stucco,  2506.0 
Swimming  pools 

Definition,  421.2 

Design  and  construction,  421.5 

Hot  tub,  421.2,  421.10 

Permit  and  plans,  421.3 

Safety  precaution,  42 1 .9, 42 1 . 1 0 

Spa,  421.2,  421.10 

Water  supply  treatment  and  drainage  system,  42 1 .6 


Tanks 

Storage  of  flammable  liquids,  418.3.2 
Storage  of  liquefied  petroleum  gas.  418.3.3 

Telescopic  seating,  1013.0 


Television  antennas  and  towers,  3 108.0,  3 109.0 
Temporary 

Buildings  or  structures,  1 10.2,  3 104.0 
Electrical  use,  2705.0 
Occupancy,  120.3 
Permits.  111.0 
Safeguards,  120.1 
Signs,  3102.12 
Stairs,  3314.1 

Termination   of  approval   for   temporary   buildings, 
110.2.3 
Tents,  air-supported  structures,  requirements,  3 104.0 
Termite  protection 

Approved  pressure  preservative  treatment  of  wood, 
2311.0 
Tests 

Fireresistance.  704  1  1 
Flameresistance,  802.0 
General,  Chapter  1 7 
New  materials  and  devices.  1701.2 
Of  construction  equipment,  3303.0 
Of  fire  protection  systems.  Chapter  9 
Pile  capacity,  1817.0 
Prefabricated  construction,  1703  3 
Procedure  for  soil.  1 803 .3 
Soil  bearing  values.  1804.0 
Structural  steel  unit.  2203.0 
Ties  veneer,  3607.3.7.2.1 
Theaters 

Aisles.  1012.0 

Use  Group  A-l,  assembly,  303.2 
Thermal  insulating  materials,  722.0 
Thermoplastics,  accepted,  2604.0,  2606.3 
Thermosetting  plastics,  accepted.  2604.0 
Towers 

Cooling,  1510.8 

Radio  and  television,  requirements.  3 108.0 
Wind,  loads.  1611.0,3108  4 
Travel,  'length  of,  to  exits,  1006  5 
Treads,  stairs.  3402.2 
Trim,  exterior,  1406.0 
Trim,  interior  (see  Interior  finish  and  trim) 
Trusses 

Individual  encasement,  714.1 
Roof  slabs  and  arches,  714.4 
Roofs,  20  feet  or  higher,  7 14.3 
Wood   construction,   2305.14,   2305.15,   3605.2.10, 
3608.2.11 
Tunnel  flame  spread  test,  1 702  4. 1 
Types  of  construction 

Type  1,  noncombustible,  603.0 

Type  2,  noncombustible,  603.0 

Type  3,  noncombustible/combustible,  604.0 

Type  4,  heavy  timber,  605.0 

Type  5,  combustible.  606.0 


824 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97) 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 


INDEX 


U 


U.  use  group,  utility  and  miscellaneous,  312  0 

Underground  structures,  405.0 

Underpinning,  3309.3 

Unfixed  pressure  vessels,  2801.2 

Unlimited  area,  buildings.  507.0 

Unsafe  structures,  121.0 

Unusable  space.  713.1.2 

Use  Group 

Doubtful  classification,  302. 1 

Classification,  302.0 

Mixed  use  classification.  313.0 
Utilities  public,  discontinuance  of 

In  demolition  of  structures.  112.0 


Validity 

Of  code,  104.0 
Vapor  retarder.  722.3.1,  1403.3 
Vaults,  refuse,  2808.0 
Veneers 

Height  of,  for  frame  buildings,  1405.5. 1 

Masonry,  1405.5,  1405.6,  3607.3.7 

Metal.  1405.4 

Plastic.  1404.6 

Stone  and  tile,  1405.5.6 

Structural  glass,  1405.7 

Wall  facings  and.  1403.3 

Weather  resistance,  1403.3,3607.3.2 
Ventilation 

Attics.  1210.1 

Court  requirements  for,  1212.0 

Crawl  space,  1210.2 

Definition,  202.0 

For  existing  buildings,  3400.6 

Garages.  408.5 

General  requirements.  1201.0 

Mechanical,  1209.0 

Motion  picture  projection  rooms,  411.3 

Natural.  1208.0 

Roof,  3608.6 

Windows.  1208.2 
Vertical  openings 

Conveyor  openings,  3009. 1 

Enclosures,  710.4,  710.5 
Violations  and  penalties 

Abatements,  118.5 

Notice  of,  118.6 

Penalties.  118.4 

Stop  work,  119.0 

Unsafe  building  121.0 


w 

Walkways,  pedestrian,  3 1 06.0 
Wall  signs,  3102.9 


Wallboard  (also  see  Sheathing) 

Fiberboard,  2309.0 

For  frame  construction.  2305. 1 3 

Gypsum.  2503  0.  3607.2.3 

Hardboard.  1403.3 

Particleboard.  2308.0 

Wood  structural  panel,  2307.0 
Walls  (also  see  Masonry) 

Basement,  3604.4 

Bearing,  chases  and  recesses  in.  21 13  1 

Bearing,  lateral  bracing  of,  2108  2 

Bearing,  wood  frame  construction.  2305.4 

Bonding  of,  21 10.0,  21 11.0 

Bracing.  3606.2.9 

Concrete  masonry  units.  2 105  1 

Construction.  3606.2.3 

Corbeled  and  projecting  masonry.  2 1 12.2 

Definition.  202.0 

Deflection,  3607.3 

Design  for  wind  on  vertical  surfaces,  1611.0 

Ducts  in  fireresistance  rated  walls.  717.0 

Enclosures  for  theater  stages,  412.2 

Exterior  protection.  3607.3 

Fire  and  party.  707.0 

Fire  partitions,  71 1.0 

Fire  separation,  709.0 

Fire  wall  openings.  708  0 

Fireplace,  3610.4.3 

Foundation  walls,  1812  0 

Glass  block,  2115.0 

Hollow.  2105. 1,2105  2 

Hollow  panels,  thickness  of,  1404  6 

Masonry  wall  construction,  2113.1 

Panel.  1404.6 

Parapet.  705.6,  707.5 

Penthouse,  1510.3 

Plain  concrete,  1901.2 

Proscenium.  412.3.5 

Protection  of  exterior  openings  in.  706.0 

Reinforced  concrete,  1901. 1,1910.0 

Reinforced  concrete  walls,  1812.3.1 

Retaining,  1825.0 

Roof  structure,  1510.0 

Shaft  enclosure,  710.3.1 

Smoke  barriers,  712.0 

Stone  foundation,  1 8 12.3.4 

Thickness  of  panel.  1404.6 

Veneers,  glass,  1405.7 

Veneers,  metal,  1405.4 

Veneers,  plastic,  2605.0 

Veneers  thickness  of,  1403.3 

Veneers  thin  and  tile,  1405.5  6 
Warehouse 

Use  Group  S,  storage,  31 1.0 
Waste  chutes.  2807.0 
Waste  to  be  removed,  33 13.0 
Water 

Supply,  definition,  202.0 

Supply  for  plumbing,  2905.0 

Tanks,  1510.7 
Waterproofing  of  exterior  structural  elements,  1813.0 
Waterproofing  of  foundation  walls,  1813  4.2,  3604.6 


9/19/97  (Effective  2/28/97)  -  corrected    780  CMR  -  Sixth  Edition 


825 


780  CMR:    STATE  BOARD  OF  BUILDING  REGULATIONS  AND  STANDARDS 
THE  MASSACHUSETTS  STATE  BUILDING  CODE 


Welding 

Inspection,  1705.3.3.2 
Width 

Aisles,  1012.0 

Lobbies  used  as  an  exit  element.  1020.3 

Means  of  egress  doors,  1017.3 

Stair  exit  doors,  1014.8.1 
Units  of  exit  width,  1009. 1 
Wind  load  design  Zoning 

Buildings.  1611.0 

Definition,  202.0,  see  Load 

Glass,  2403.1 

Radio  and  television  towers.  3108.4 

Signs,  1611.12,  3102.6.1 

Winders,  1014.6.3 
Windows 
'Bay,  1406.5 

Cleaning  safeguards,  3 1 10.0 

Dormer,  1 5 10.6 

Fire,  718.0 

Fireresistive  design,  718.1 

Glass  area  required.  1206.2,1208.2 

Required  for  light  and  ventilation,  1205.0 
Wired  glass 

In  fireresistive  doors  and  windows,  719.0 
Wood  construction 

Bearing  walls,  2305.4 

Bracing,  2305.7 

Bridging,  2305.14.2 

Cambering,  2301.1 

Cornices,  1406.2.2 

Cutting  and  notching,  2305.3 

Designated  type  of.  606. 1 

Fiberboards,  2309.0 

Fireretardant-treated,  707.5.2, 2310.0 

Flashing,  1405  3.10 

Floor  sheathing,  2307.3. 1 

Floors,  3605.2 

Foundation  anchorage,  2305. 16 

Foundation,  general,  1812.0.  3604.4.3,  3604.5.2 

Framing  around  flues  and  chimneys.  2304  1 1 

Heavy  timber  construction,  2304.0 


Nailing,  1405.3  7,2305.2 

Nonhealing  walls,  2305.5 

Piles.  1822.0 

Plywood,  2307.0 

Prefabricated  1-joists,  23 13.5 

Protection  near  grade,  23 11.4 

Roof-ceiling,  3608.2 

Roof  sheathing.  2305. 15. 1.  2307.3. 1 

Shear  walls.  2502.0 

Sheathing  lath,  2305.13.2 

Shingles   and   shakes.    1506.3,    1507.2.8,    1507.2.9. 
3609.8.3609.9 

Spans  for  plywood  sheathing.  2307.3 

Stressed  skin  panels,  23 13.2 

Structural  glued-larmnated  timber.  23 13.1 

Structural  members,  2303  0 

Structural  panels.  2307.0 

Stud  spacing,  2307.3.5 

Subfloors.  2307.3  3 

Trusses.  3605.2.10.  3608.2. 1 1 

Veneer,  height  of.  1405.5.1 

Veneer,  masonry,  1405  5 

Veneer,  metal,  1405  4 

Wall  sheathing.  2305. 13.  3606.2 

Weatherboarduig,  exterior,  1403.3 
Work 

Stan.  111.15 

Stop  order.  119  0 
Workmanship.  117.0 
Written  notice 

Definition,  202.0 


Yard 

Definition,  202.0 

Obstruction  of,  1213  0 

Permissible  encroachments.  1213.2 
Yard  svstem  fire  mains.  916  0 


826 


780  CMR  -  Sixth  Edition    corrected  -  9/19/97  (Effective  2/28/97)