Ml
; i
:/
California Cbcle of ReguldtiQiis
Title 24, Part 2, \tolume 2 of 2
California Building Standards Commission; :
Based on the 2009 International Building God^® ■
2010 California Historical Building Codev Title 24, Pa^^
2010 California Existi% Building CbdeJTitle 24, R^t
\:
INTERNATIONAL--
CODE COUNCIL'
.vM^
/'. . '.A \
Xi>
,^ : : : Effective Date: January IJ, 2011
(For Errata ariySupplemfents, see History. Note: Afiipendix)
2010 California Existing Building Code
California Code of Regulations, Title 24, Part 10
First Printing: June 2010
ISBN 978-1-58001-974-3
Copyright © 2010
Held by
California Building Standards Commission
2525 Natomas Park Drive, Suite 130
Sacramento, CA 95833-2936
ALL RIGHTS RESERVED. This 2010 California Existing Building Code contains substantial copyrighted material from the 2009
International Existing Building Code, which is a copyrighted work owned by the International Code Council, Inc. Without advance
written permission from the copyright owner, no part of this book may be reproduced, distributed or transmitted in any form or by
any means, including, without limitation, electronic, optical or mechanical means (by way of example and not limitation, photo-
copying, or recording by or in an information storage retrieval system). For information on permission to copy material ^^^^^diiM^^
fair use, please contact: Publications, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFi^r
(422-7233).
Trademarks: "International Code Council," the "International Code Council" logo and the "International Existing Building Code"
are trademarks of the International Code Council, Inc.
PRINTED IN THE U.S.A.
PREFACE
This document is Part 2 of 12 parts of the official triennial compilation and publication of the adoptions, amendments
and repeal of administrative regulations to California Code of Regulations, Title 24, also referred to as the California
Building Standards Code. This Part is known as the California Building Code.
The California Building Standards Code is published in its entirety every three years by order of the California legisla-
ture, with supplements published in intervening years. The California legislature delegated authority to various state
agencies, boards, commissions and departments to create building regulations to implement the State's statutes. These
building regulations or standards, have the same force of law, and take effect 1 80 days after their publication unless oth-
erwise stipulated. The California Building Standards Code applies to occupancies in the State of California as anno-
tated.
A city, county or city and county may establish more restrictive building standards reasonably necessary because of
local climatic, geological or topographical conditions. Findings of the local condition(s) and the adopted local building
standard(s) must be filed with the California Building Standards Commission to become effective and may not be effec-
tive sooner than the effective date of this edition of California Building Standards Code. Local building standards that
were adopted and applicable to previous editions of the California Building Standards Code do not apply to this edition
without appropriate adoption and the required filing.
Should you find publication (e.g., typographical) errors or inconsistencies in this code or wish to offer conmients
toward improving its format, please address your comments to:
California Building Standards Commission
2525 Natomas Park Drive, Suite 130
Sacramento, CA 95833-2936
Phone: (916) 263-0916
Fax: (916) 263-0959
Web Page: www.bsc.ca.gov
ACKNOWLEDGMENTS
The 2010 California Building Standards Code (Code) was developed through the outstanding collaborative efforts of the Depart-
ment of Housing and Community Development, the Division of State Architect, the Office of the State Fire Marshal, the Office of
Statewide Health Planning and Development, the California Energy Commission, and the Building Standards Commission (Com-
mission).
This collaborative effort included the assistance of the Conimission's Code Advisory Committees and many other volunteers that
worked tirelessly to assist the Commission in the production of this Code.
Governor Arnold Schwarzenegger
Members of the Building Standards Commission
Acting Secretary Tom Sheehy - Chair
Isam Hasenin - Vice-Chair Christina Jamison
James Barthman Stephen Jensen
Craig Dailey Michael Paravagna
Susan Dowty Richard Sawhill
Tony Hoffman Steven Winkel
David Walls - Executive Director
Thomas Morrison - Deputy Executive Director
For questions on California state agency amendments; please refer to the contact list on the following page.
2010 CALIFORNIA BUILDING CODE III
California Code of Regulations, Title 24
California Agency Information Contact List
California Energy Commission
Energy Hotline (800) 772-3300
or (916) 654-5106
Building Efficiency Standards
Appliance Efficiency Standards
Compliance Manual/Forms
California State Lands Commission
Marine Oil Terminals (562) 499-6317
California State Library
Resources and Information (916) 654-0261
Government Publication Section (916) 654-0069
Corrections Standards Authority
Local Adult Jail Standards (916) 324-1914
LocalJuvenile Facility Standards (916) 324-1914
Department of Consumer Affairs — Acupuncture Board
Office Standards (916) 445-3021
Department of Consumer Affairs — Board of Pharmacy
Pharmacy Standards (916) 574-7900
Department of Consumer Affairs — Bureau of Bartering
and Cosmetolog y
Barber and Beauty Shop and (916) 574-7570
College Standards (800) 952-5210
Department of Consumer Affairs — Bureau of Home
Furnishings and Thermal Insulation
Insulation Testing Standards (916) 574-2041
Department of Consumer Affairs — Structural Pest
Control Board
Structural Standards (800) 737-8188
(916) 561-8708
Department of Consumer Affairs — Veterinary
Medical Board
Veterinary Hospital Standards (916) 263-2610
Department of Food and Agriculture
Meat & Poultry Packing Plant Standards . . . (916) 654-1447
Dairy Standards (916) 654-1447
Department of Public Health
Organized Camps Standards (916) 449-5661
Public Swimming Pools Standards (916) 449-5693
Asbestos Standards (510) 620-2874
Department of Housing and Community Development
Residential — Hotels, Motels, Apartments
Single-Family Dwellings (916) 445-9471
Permanent Structures in Mobilehome
and Special Occupancy Parks (916) 445-9471
Factory-Built Housing, Manufactured
Housing and Commercial Modular (916) 445-3338
Mobilehomes — Permits & Inspections
Northern Region (916) 255-2501
Southern Region (951) 782-4420
Employee Housing Standards (916) 445-9471
Department of Water Resources
Gray Water Installations Standards (916) 651-9667
Division of the State Architect — Access Compliance
Access Compliance Standards (916) 445-8100
Division of the State Architect — Structural Safety
Public Schools Standards (916) 445-8100
Essential Services Building Standards (916) 445-8100
Community College Standards (916) 445-8100
Division of the State Architect — State Historical
Building Safety Board
Alternative Building Standards (916) 445-8100
Office of Statewide Health Planning and Development
Hospital Standards (916) 440-8409
Skilled Nursing Facility Standards (916) 440-8409
Clinic Standards (916) 440-8409
Permits (916) 440-8409
Office of the State Fire Marshal
Code Development and Analysis (916) 445-8200
Fire Safety Standards (916) 445-8200
Fireplace Standards (916) 445-8200
Day-Care Centers Standards (916) 445-8200
Exit Standards (916) 445-8200
IV
2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
Distilling the code review process down to a methodical, sequential list of considerations is generally problematic. In many cases,
related provisions from various chapters of the code must be considered simultaneously, or reconsidered later in the process to
arrive at the correct classification or determination. Any number of acceptable alternatives may exist for construction of the building
and its specific features. Each choice provided by the code must be evaluated for its specific impact on other aspects of the build-
ing's analysis. With a basic understanding of the interrelationship of the various chapters, the practiced code user will make an initial
assessment of the building as a first step of the code review process. The following outUne may be helpful as a guide for the effective
use of the IBC, with the understanding that final resolution of each step is often dependant on subsequent steps.
The following process begins with a brief discussion of the key administrative areas of the code. The process addressing techni-
cal provisions is divided into two distinct areas of analysis, the nonstructural provisions of the IBC and the structural provisions.
Although reference is not made to all provisions set forth in the IBC, the process is intended to be representative of an approach to
using the IBC in an effective manner.
Administrative Provisions
Prior to any analysis based on the technical provisions of the IBC, it is important that the fundamental administrative aspects of the
code be reviewed. It is critical that the basis of technical decisions be consistent with the approach established in IBC Chapter 1,
including:
• Scope of the IBC
• Intent of the IBC
• Applicability of the IBC
• Duties and powers of the building official
• Alternate materials, designs and methods of construction
Nonstructural Provisions
1. Classify the building for occupancy and construction type. The first step in analyzing a building for code compliance is its
proper classification based on anticipated use(s) and construction features.
Identify the distinct and varied uses of the building. The uses that will occur within the building must be identified, evaluated and
classified into one or more of the distinct occupancy classifications estabhshed in the IBC. Some buildings will be classified as sin-
gle-occupancy, where there is only one applicable occupancy classification. Others will be considered as mixed-occupancy due to
the presence of two or more uses that are classified into different occupancy groups.
Sec. 302.1 Classify the building into one or more occupancy groups. Although there are 10 general occupancy groups,
many of the groups are subdivided into sub-groups to allow for a more exacting analysis of the building under consideration.
Sec. 303 Group A
Sec. 304
Group B
Sec. 305
Group E
Sec. 306
Group F
Sec. 307
Group H
Sec. 308
Group I
Sec. 309
Group M
Sec. 310
Group R
Sec. 311
Group S
Sec. 312
Group U
Identify the building's type of construction based on the materials of construction and degree of fire-resistance for the
building's major elements. The primary structural frame, exterior walls, interior walls, floor construction and roof construc-
tion, as applicable, must be evaluated in regard to their degree of fire-resistance and materials of construction in order to classify
the building based upon type of construction.
2010 CALIFORNIA BUILDING CODE v
EFFECTIVE USE OF THE IBC/CBC
Sec. 602.1 Classify the building into a single type of construction. Five general types of construction have been established
and further subdivided into nine specific construction types. The classification of construction type is based on a combination of
the degree of fire-resistance and the type of materials of the key building elements.
Sec. 602 Type of construction based on materials of construction
Table 601 Type of construction based on fire rating of the building elements
Sec. 603 Combustible materials in Type I and II buildings
Sec. 1505 Verify classification of roof covering. Roof coverings are typically required to provide protection against moderate
or light fire exposures from the exterior. Their minimum required classification is based upon the type of construction of the
building.
2. Determine if the building is to be fully sprinklered. Many of the code provisions vary based upon the presence of an automatic
sprinkler system throughout, or in specific portions of, the building.
Sec. 903.2 Determine if the building requires a fire sprinkler system. Many of the mandates for the installation of a sprin-
kler system are based upon the occupancy or occupancies that occur within the building. The provisions will often require some
degree of occupant load and fire area determination. Other conditions may also trigger a required sprinkler installation, such as
building height or the lack of exterior openings. Table 903.2.13 should also be consulted.
If a sprinkler system is not required, review for potential code modifications if a sprinkler system is installed. There are a
significant number of benefits provided by the code if a sprinkler system is installed. An initial analysis of the building will typi-
cally allow for an early determination of the value of such sprinkler benefits, including:
Sec. 504.2 Story and height increase (reduced type of construction)
Sec. 506.3 Allowable area increase (reduced type of construction)
Sec. 507.3 Unlimited area building (reduced type of construction)
Sec. 1018.1 Elimination of corridor fire-resistance rating
3. Locate the building on the site. The location of the building(s) on the lot is fundamental to the degree of fire exposure to and
from adjoining buildings and lots. In addition, the building's location influences the amount of fire department access that can be
provided from the exterior of the building.
Sec. 503.1.2 Determine the number of buUdings on the site. Where two or more buildings are located on the same lot, they can
be evaluated as a single building or multiple buildings. The type of construction requirements may differ based upon which of
the two methods is utilized.
Sec. 602.1 Determine minimum required fire rating of exterior v^alls. The fire separation distance is the measurement used
in evaluating the necessary fire rating for exterior walls. It is measured from the building to the lot line, to the center line of a pub-
lic way, or to an imaginary assumed line between two buildings on the same lot. Projections and parapets, if applicable, are also
regulated.
Sec. 704.8 Determine exterior opening protection requirements. Openings in exterior walls are regulated by the fire separa-
tion distance and the rating of the exterior wall in which they are located.
Sec. 506.2 Determine frontage increase for allowable area purposes. Utilized primarily for fire department access, open
space adjacent to a building's perimeter provides for an increase in the allowable area.
4. Verify building's construction type by determining the allowable building size. The permitted types of construction are pri-
marily based upon the occupancy classifications involved, the building's height and the building's floor area. Other conditions may
also affect the appropriate construction types, including the building's location on the lot and the intended materials of construction.
In buildings with mixed-occupancy conditions, the methods of addressing the relationship between the multiple occupancies indi-
rectly affect construction type.
Sec. 202 and 502 Calculate actual height of building in both *feet' and 'stories above grade plane'. The code specifically
describes the method for assigning a building height, measure both in the number of feet and the number of stories above grade
plane. The actual height must be compared with the allowable height to determine if the building's type of construction is accept-
able.
Sec. 504 Determine allowable height permitted for 'feet' and 'stories'
Sec. 505 Determine if mezzanine provisions are applicable
Sec. 504.3 Determine if any rooftop structures are in compliance
Sec. 502 Calculate actual floor area of each story of building. The building area is typically the entire floor area that occurs
within the surrounding exterior walls. The building area for each individual story must be calculated, as well as for the building
as a whole.
vi 2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
Sec. 507 Determine if building qualifies as an unlimited area building
Sec. 506 Determine allowable area permitted for each story and building as a whole if:
Sec. 506 Single-occupancy building
Sec. 508.2 Multi-occupancy w/accessory occupancies
Sec. 508.3 Multi-occupancy building w/nonseparated occupancies
Sec. 508.4 Multi-occupancy building w/separated occupancies
Sec. 706. 1 Use of fire walls
Sec. 509 Determine if special provisions are to be applied for height and/or area. The general requirements for allowable
height and area may be modified under limited conditions, typically where a parking garage is located in a building with other
occupancies.
5. Identify extent of any special detailed occupancy requirements. Special types of buildings, special uses that occur within
buildings, and special elements of a building are further regulated through specific requirements found in Chapter 4. Since these
provisions are specific in nature, they apply in lieu of the general requirements found elsewhere in the code.
Chapter 4. Determine special detailed requirements based on occupancy. A number of the special provisions are applicable to
a specific occupancy or group of similar occupancies.
Sec. 402 Covered mall buildings
Sec. 403 High-rise buildings
Sec. 404 Atriums
Sec. 405 Underground buildings
Sec. 406 Motor- vehicle-related occupancies
Sec. 407 Group 1-2 occupancies
Sec. 408 Group 1-3 occupancies
Sec. 411 Special amusement buildings
Sec. 412 Aircraft-related occupancies
Sec. 415 Group H occupancies
Sec. 419 Live/work units
Sec. 420 Groups I- 1 , R- 1 , R-2 and R-3
Sec. 422 Ambulatory health care facilities
Table 508.2.5 Determine if building contains any incidental accessory occupancies. The uses identified in Table 508.5.2 are
considered as a portion of the occupancy in which they are located, but special conditions required that they be addressed in a
more specific manner.
Sec, 508.2.5 Provide fire separation and/or fire-extinguishing system
6.1dentify and evaluate fire and smoke protective elements. Where fire-resistance-rated construction and/or smoke protection is
mandated by other provisions of the code, the provisions of Chapter 7 identify the appropriate methods for gaining compliance.
Chapter 7. Verify compliance w/details of fire and smoke resistance. The various elements of fire-resistance-rated and
smoke-resistant construction are detailed, including walls, horizontal assemblies, shaft enclosures, including openings such as
doors and windows, as well as the penetration of such elements by conduit, ducts, piping and other items.
Sec. 704
Structural members
Sec. 707
Fire barriers
Sec. 709
Fire partitions
Sec. 710
Smoke barriers
Sec. 711
Smoke partitions
Sec. 712
Horizontal assemblies
Sec. 708
Shaft enclosures
Sec. 713
Penetrations
Sec. 714
Joint systems
Sec. 715
Opening protectives
Sec. 716
Ducts and air transfer openings
2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
7. Identify additional fire protection systems that may be required. In addition to automatic sprinkler systems, there are several
other types of fire protection systems that may be required in a building.
Sec. 907.2. Determine compliance with fire alarm provisions. Fire alarm systems are typically mandated based upon the
occupancy classification and the number of occupants.
Sec. 905.3. Determine if standpipe system is required. A standpipe system is required in buildings once a specified height is
reached to provide for a more effective means of fighting a fire within the building.
Sec. 905.4.6. Verify location of standpipe hose connections.
8. Identify and evaluate materials utilized as interior floor, wall and ceiling finishes. Finish materials within the building are
primarily regulated for flame spread and smoke development characteristics.
Sec. 803.9. Verify compliance of wall and ceiling finishes. Interior wall and ceiling finishes are regulated based upon the occu-
pancy classification of the space and their location within the means of egress system. The classification may typically be
reduced where sprinkler protection is provided.
Sec. 804.4. Verify compliance of floor finishes. While regulated differently than wall and ceiling finishes, floor finishes com-
prised of fibers are also controlled based upon their use in the egress system, the occupancy classification, and the presence of a
sprinkler system.
9. Evaluate means of egress system based on anticipated occupant loads. The expected occupant load is the basis for the design
of the means of egress system. The egress elements must provide for a direct, continuous, obvious, undiminished and unobstructed
path of travel from any occupiable point in the building to the public way.
Sec. 1004. Determine the design occupant load. Although the primary use of an occupant load is in the design of the building ' s
means of egress system, occupant load is also occasionally an important factor in occupancy classification, sprinkler system and
fire alarm system requirements, and plumbing fixture counts.
Chapter 10. Verify compliance with means of egress provisions. The means of egress system is intended to provide the primary
occupant protection from fire and other hazards. The system consists of two major components, egress components and egress
design.
Sec. 1005.1 Egress width and distribution
Sec. 1006.3 Emergency lighting
Sec. 1007 Accessible means of egress
Sec. 1008.1.2 Door swing
Sec. 1008. L9 Door operations
Sec. 1008. l.lOPanic hardware
Sec. 1009.1 Stairway width
Sec. 1009.4 Stairway treads and risers
Sec. 1011 Exit signs
Sec. 1012 Stairway and ramp handrails
Sec. 1013 Guards
Sec. 1014.2 Egress through intervening spaces
Sec. 1014.3 Common path of egress travel
Sec. 1015.1 Number of exit or exit access doorways
Sec. 1015.2 Egress separation
Sec. 1016.1 Travel distance
Sec. 1018.1 Corridor construction
Sec. 1021 Number of exits
Sec. 1022 Vertical exit enclosures
Sec. 1023 Exit passageways
Sec. 1025 Horizontal exits
Sec. 1026 Exterior exit stairways
Sec. 1027 Exit discharge
Sec. 1028 Egress firom assembly occupancies
viii 201 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
10. Identify any special use features of the building. The activities that occur within the building pose varying risks to the occu-
pants. Special conditions are applicable when such activities are anticipated.
Chapter 4. Verify compliance with special detailed requirements. These provisions are often an extension of the general
requirements found elsewhere in the code.
Sec. 410 Stages and platforms
Sec. 413 Combustible storage
Sec. 414 Hazardous materials
Sec. 416 Application of flammable finishes
11. Determine areas of building and site required to be accessible. In general, access to persons with disabilities is required for
all buildings.
Chapter llA and/or IIB. Verify compliance with accessibility provisions. In order to be considered as accessible, buildings and
their individual elements must comply with the applicable technical provisions of Chapters 1 lA and/or 1 IB.
12. Determine extent of other miscellaneous provisions. Additional provisions may be applicable based upon each individual
building and its characteristics.
Sec. 2406.3. Verify safety glazing provided in hazardous locations. Safety glazing must be appropriately identified to ensure
the proper glazing material is installed in areas considered as subject to human impact.
Chapter 12. Interior environment. Provisions regulating ventilation, temperature control, lighting, sound transmission, room
dimensions and surrounding materials associated with interior spaces.
Chapter 14 Exterior walls. Requirements for installation of wall coverings and the permissible use of combustible materials on the
exterior side of exterior walls.
Chapter 24. Glass and glazing. General provisions for the installation of glazing materials and skylights.
Chapter 30. Elevators. Elevator hoistway provisions, including enclosure of hoistways, emergency operations and hoistway vent-
ing.
Chapter 31. Special construction. A variety of special conditions are addressed, including membrane structures, temporary struc-
tures, pedestrian walkways and tunnels, awnings and canopies, marquees, signs and swimming pool enclosures.
Structural Provisions
General Requirements
1. Design Loads.
The 2009 IBC references the national load standard. Minimum Design Loads for Buildings and Other Structures (ASCE/SEI
7 — 05) with Supplement Number 2.
Determine the applicable design loads that the building structure is expected to be subjected to. Code prescribed loads are given in
Chapter 16 and the referenced standard, ASCE/SEI 7. The code prescribed minimum Hve loads are given in IBC Table 1607.1.
The various code prescribed loads are probabilistic in nature. Environmental loads, such as flood, rain, snow, seismic and wind
vary based on the location of the building site. The following table gives the IBC section and ASCE/SEI 7 chapter for various types
of load.
REFERENCED IBC SECTIONS AND ASCE/SEI 7 CHAPTERS FOR LOADS
TYPE OF LOAD
IBC SECTION
ASCE/SEI 7 CHAPTER
Dead loads
Section 1606
Chapter 3
Live loads
Section 1607, Table 1607.1
Chapter 4
Snow loads
Section 1608
Chapter 7
Wind loads
Section 1609
Chapter 6
Soil lateral loads
Section 1610
Chapter 3
Rain loads
Section 1611
Chapter 8
Flood loads
Section 1612
Chapter 51
Earthquake loads
Section 1613
Chapter 11-22
1. Section 1612 references ASCE 24 which references Chapter 5 of ASCE/SEI 7
2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
2. Structural Materials.
The structural design begins with the selection of the type of structural materials to be used to support the building. Structural fram-
ing systems are constructed of concrete, masonry, steel or wood. Some miscellaneous or specialty structures and components, such
as awnings, canopies and cladding, are often constructed of aluminum.
The design of various structural materials is covered in specific material chapters in the code which in turn reference design stan-
dards for the type of material involved. The referenced standards in the 2009 IBC for the structural materials are shown in the
following table:
STRUCTURAL DESIGN STANDARDS FOR STRUCTURAL MATERIALS^
MATERIAL
IBC/CBC CHAPTER
REFERENCED STANDARD
Concrete
19
ACI318— 08
Building Code Requirements for Structural Concrete
Aluminum
20
ADM 1—05
Aluminum Design Manual
Masonry
21
TMS 402-08/ACI 530-08/ASCE 5-08
Building Code Requirements and Specification for Masonry Structures (MSJC Code)
Steel
22
AISC 360—05
Specification for Structural Steel Buildings
AISC 341— 05
Seismic Provisions for Structural Steel Buildings,
including Supplement No. 1 dated 2006
AISIS 100— 2007
North American Specification for the Design of Cold-Formed Steel Structural Members
Wood
23
AF&PA NDS— 05
National Design Specification (NDS) for Wood Construction with 2005 Supplement
AF&PA SDPWS— 08
Special Design Provisions for Wind and Seismic
1. The above table shows the main structural design standards for these structural materials. For a complete list of referenced standards, see IBC Chapter 35.
3. Structural Analysis, Design and Detailing.
Once the applicable loads are determined, the structural system of the building must be analyzed to determine the effects of the gov-
erning gravity and lateral loads that act on the structure. The structural system of a typical building consists of the roof and floor sys-
tems, walls, beams and columns, and the foundation. From the structural analysis, the next step is to design the structural members,
elements and systems to provide the minimum level of resistance in accordance with the various load combinations prescribed in
Section 1605,
Once the structural elements and systems are designed, the next step is to detail the load transfer connections to provide a com-
plete load path from the point of origin to the resisting element. In general, the ultimate resisting element of buildings and structures
is the foundation and supporting ground. The final step is to prepare a complete set of construction documents as required by Sec-
tions 107 and 1603. Construction documents are defined in Section 202 as "Written, graphic and pictorial documents prepared or
assembled for describing the design, location and physical characteristics of the elements of a project necessary for obtaining a
building permit." In general, construction documents consist of plans, specifications and calculations.
Section 1603.1 requires construction documents to show the size, section and relative locations of structural members with floor
levels, column centers and offsets dimensioned. Design loads required by Sections 1603. 1 . 1 through 1603. 1 .9 must be indicated on
the construction documents. If complete construction documents consisting of plans, specifications and calculations are provided,
the items Usted in Sections 1603. 1.1 through 1603.9 are generally included.
2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
The exception permits construction documents for buildings constructed in accordance with the conventional light-frame con-
struction provisions of Section 2308 need only indicate the following:
Roor and roof live loads
Ground snow load, P^.
Basic (3-second gust) wind speed (mph) and wind exposure category.
Seismic design category and site class.
Flood design data where sited in flood hazard areas
Design load-bearing values of soils.
General Requirements
1. Occupancy Category (IBC/CBC Table 1604.5).
Determine the occupancy category of the building based on Table 1604.5.
Where a structure is occupied by two or more occupancies that are not the same occupancy category, the building must be classi-
fied in the highest occupancy category corresponding to the various occupancies.
Where structures have two or more portions that are structurally separated, each separate portion should be separately classified.
Where a separated portion of a structure provides required access or egress from another portion of the building with a higher
occupancy category, both portions of the building must be assigned the higher occupancy category.
Where a separated portion of a structure shares life safety components with another portion of the building with a higher occu-
pancy category, both portions of the building must be assigned the higher occupancy category.
2. Floor and roof live loads (IBC/CBC Table 1607.1).
Determine uniformly distributed and concentrated floor live load for the floor areas of the building in accordance with Section
1603.1.1 and Table 1607.1.
Floor live load reduction in accordance with Section 1607.9 should be indicated for each type of live load that is reduced.
Determine the roof live load for roof areas in accordance with Section 1607.1 1.
Roof live load reduction in accordance with Section 1607.1 1.2 should be indicated for roof live loads that are reduced.
3. Snow load (IBC/CBC Section 1608, ASCE/SEI 7 Section 7).
Determine the ground snow load, P^, based on the location of the building site in accordance with Figure 1608.2 for the contigu-
ous United States and Table 1608.2 for Alaska.
In areas where the ground snow load, P^, exceeds 10 psf, the following information should be determined:
1. Flat-roof snow load, Pf.
2. Snow exposure factor, Q.
3. Snow load importance factor, /.
4. Thermal factor, C,.
4. Wind speed and wind exposure category.
Determine the following information related to wind loads in accordance with Section 1603.1.4:
1. Basic 3-second gust wind speed (mph).
2. Wind importance factor, /.
3. Wind exposure category (B, C, D). If more than one wind exposure is used, the wind exposure for each wind direction
should be determined.
4. The applicable internal pressure coefficient.
5. The design wind pressure (psf) used for the design of exterior component and cladding materials not specifically designed
by the registered design professional should be indicated.
2010 CALIFORNIA BUILDING CODE xl
EFFECTIVE USE OF THE IBC/CBC
5. Earthquake design requirements.
Determine the following information related to seismic loads regardless of whether seismic loads govern the design of the lat-
eral-force-resisting system of the building:
1 . Seismic importance factor, /, based on occupancy category.
2. Mapped spectral response accelerations, S^ and 5^.
3. Site class.
4. Design spectral response coefficients, S^s and Sfy^.
5. Seismic design category.
6. Basic seismic-force-resisting system(s).
7. Design base shear.
8. Seismic response coefficient(s), C5.
9. Response modification factor(s), R,
10. Analysis procedure used.
6. Geotechnieal information.
The design load bearing values of soils shall be shown on the construction documents in accordance with Section 1603.1.6.
7. Special loads.
Determine any special loads that are applicable to the design of the building, structure or portions thereof along with the specific
section of the code that addresses the special loading condition in accordance with Section 1603.1.8.
8. Load combinations.
Buildings and other structures and portions thereof are required to be designed to resist the load combinations specified in Sec-
tion 1605.2 or 1605.3 and Chapters 18 through 23, and the special seismic load combinations with overstrength as required by
Section 1605.1 and ASCE/SEI 7.
9. Wind and seismic detaUing.
Lateral-force-resisting systems are required to conform to the seismic detailing requirements of the code and ASCE/SEI 7 (exclud-
ing Chapter 14 and Appendix 1 1 A) even when wind load effects are greater than seismic load effects. See Section 1604.10.
10. Serviceability.
Structural systems and members shall be designed to have adequate stiffness to limit deflections and lateral drift. The deflection
of structural members shall not exceed the more restrictive of the limitations of Sections 1604.3.2 through 1604.3.6 or that per-
mitted by Table 1604.3. Structural systems shall be designed to have adequate stiffness to limit deformation and lateral drift due
to earthquake loading in accordance with Section 12.12.1 of ASCE/SEI 7.
11. Foundation.
A foundation system must be designed that provides adequate support for gravity and lateral loads. Walls of buildings of conven-
tional light frame construction, as defined in Section 202, are permitted to be supported by footings constructed in accordance
with Table 1 809.7. Otherwise, the foundation system must be designed in accordance with other provisions of Chapter 1 8. The
following table gives a summary of applicable sections for foundation systems.
FOUNDATION REQUIREMENTS
SUBJECT
IBC SECTION
Presumptive load-bearing values of soils
1806, Table 1806.2
Foundation walls, retaining walls and embedded posts & poles
1807
General requirements for foundations
1808
Minimum concrete specified concrete strength
Table 1808.8.1
Minimum concrete cover
Table 1808.8.2
Shallow foundations (footings)
1809
Prescriptive footings for light frame walls
Table 1809.7
Deep foundations
1810
xii
2010 CALIFORNIA BUILDING CODE
EFFECTIVE USE OF THE IBC/CBC
A geotechnical investigation is required where required by Section 1803.2 unless the building official determines that a soils
investigation is not required in accordance with the exception. A geotechnical investigation is required for buildings assigned to
Seismic Design Categories C, D, E and F in accordance with Sections 1803.5.11 and 1803.5.12.
12. Excavation, grading and fill
Requirements for excavation, grading and fill related to foundation construction are covered in Section 1804. General require-
ments for site grading are covered in Appendix J.
13. Flood design data.
Where required by Section 1612.5, buildings located in flood hazard areas as established in Section 1612.3 are required to pro-
vide documentation that includes the following information regardless of whether flood loads govern the design of the building :
1. In flood hazard areas not subject to high- velocity wave action, the elevation of the proposed lowest floor, including the
basement; and the elevation to which any nonresidential building will be dry flood proofed.
2. In flood hazard areas not subject to high- velocity wave action, the elevation to which any nonresidential building will be dry
floodproofed.
3. In flood hazard areas subject to high- velocity wave action, the proposed elevation of the bottom of the lowest horizontal
structural member of the lowest floor, including the basement.
14. Special inspection.
Where special inspection, special inspection for seismic resistance, or structural testing for seismic resistance is required by Sec-
tion 1704, 1707 or 1708, the registered design professional in responsible charge is required to prepare a statement of special
inspections in accordance with Section 1705. The statement of special inspections must be submitted by the permit applicant as a
condition of permit issuance in accordance with Section 106.1.
A statement of special inspections is not required for structures designed and constructed in accordance with the conventional
construction provisions of Section 2308 unless specific components in the structure require special inspection.
The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for con-
struction not designed by a registered design professional.
SPECIAL INSPECTION REQUIREMENTS
TYPE OF SPECIAL INSPECTION
APPLICABLE SECTION
REQUIRED VERIFICATION AND INSPECTION
Steel construction
1704.3
Table 1704.3
Concrete construction
1704.4
Table 1704.4
Masonry construction
Level 1
Level 2
1704.5
Table 1704.5.1
Table 1704.5.3
Wood construction
1704.6
Soils
1704.7
Table 1704.7
Driven deep foundations
1704.8
Table 1704.8
Cast in place deep foundations
1704.9
Table 1704.9
Helical pile foundations
1704.10
Vertical masonry foundations
1704.11
1704.5
—
Sprayed fire resistant materials
1704.12
Mastic and intumescent fire resistive coatings
1704.13
_
Exterior insulation and finish (EIFS) systems
1704.14
Special cases
1704.15
Smoke control systems
1704.16
—
Where required by the provisions of Section 1709.2 or 1709.3, the owner shall employ a registered design professional to perform structural observations as
defined in Section 1702. At the conclusion of the work included in the permit, the structural obserxer shall submit a written statement to the building official
that identifies any reported deficiencies that have not been resolved.
2010 CALIFORNIA BUILDING CODE
xlli
EFFECTIVE USE OF THE IBC/CBC
15. Special inspection for wind and seismic resistance.
Section 1706.1 requires special inspections for wind requirements based on wind speed and exposure category as prescribed in
Sections 1706,2 through 1706.4, unless exempted by the exceptions to Section 1704.1.
Section 1707.1 requires special inspections for seismic resistance based on seismic design category as prescribed in Sections
1707.2 through 1707.9, unless exempted by the exceptions of Section 1704.1 or 1705.3.
16. Structural testing for seismic resistance.
Section 1708.1 requires specific testing and qualification for seismic resistance as prescribed in Sections 1708.2 through 1708.5,
unless exempted from special inspections by the exceptions of Section 1704;1 and 1705.3.
17. Structural observation.
Where required by the provisions of Section 17 10.2 or 17 10.3 the owner is required to employ a registered design professional to
perform structural observations as defined in Section 1702. Section 1710.2 requires structural observations for seismic resis-
tance for certain structures assigned to Seismic Design Category D, E or F; Section 1710.3 requires structural observations for
wind requirements for certain structures sited where the wind speed exceeds 110 mph.
At the conclusion of the work included in the permit, the structural observer is required to submit a written statement to the
building official that identifies any reported deficiencies that have not been resolved.
Prior to the commencement of observations, the structural observer is required to submit a written statement to the building
official identifying the structural observations.
At the conclusion of the work included in the permit, the structural observer is required to submit a written statement to the
building official indicating what site visits have been made, identifies any deficiencies that have not been resolved.
18. Contractor responsibility.
Section 1709 requires each contractor responsible for the construction of a main wind- or seismic-force-resisting system, desig-
nated seismic system or a wind- or seismic-resisting component listed in the statement of special inspections is required to sub-
mit a written statement of responsibility to the building official and the owner prior to the commencement of work on the system
or component. (The term "designated seismic system" is defined in Section 1702 and Section 1 1 .2 of ASCE/SEI 7). The contrac-
tor's statement of responsibility is required to acknowledge awareness of the special requirements contained in the statement of
special inspections.
19. Phased approvals.
Construction of foundations or other part of a building is permitted before the construction documents for the whole building or
structure have been submitted, provided adequate information has been filed. The holder of such permit for the foundation or
other part of a building proceeds at their own risk and without assurance that a permit for the entire structure will be granted.
20. Amended construction documents.
Work must be constructed in accordance with the approved construction documents and any changes made during construction
that are not in compliance with the approved construction documents must be resubmitted for approval as amended construction
documents.
21. Deferred submittals.
Deferred submittals are items that are not submitted at the time of permit application and must have the prior approval of the
building official in accordance with Section 107.3.4.2. The registered design professional in responsible charge is required to hst
the deferred submittals on the construction documents for review by the building official. Documents for deferred submittal
items must be reviewed by the registered design professional in responsible charge who will forward them to the building official
with a notation indicating that they have been reviewed and are in general conformance with the design of the building.
xiv 201 CALIFORNIA BUILDING CODE
How to Distinguish Between Model Code Language
and
California Amendments
To distinguish between model code language and the incorporated California amendments, including exclusive California stan-
dards, California amendments will appear in italics,
[BSC] This symbol within a section identifies which State agency(s), by its "acronym," has amended a section of the model code.
Legend of Acronyms of Adopting State Agencies
BSC California Building Standards Commission
SFM Ofp.ce of the State Fire Marshal
HCD Department of Housing and Community Development
DSA-AC Division of the State Architect-Access Compliance
DSA-SS Division of the State Architect- Structural Safety
DSA-SS/CC Division of the State Architect-Structural Safety/Community Colleges
OSHPD Office of Statewide Health Planning and Development
CSA Corrections Standards Authority
DPH Department of Public Health
AGR Department of Food and Agriculture
CEC California Energy Commission
CA Department of Consumer Affairs:
Board ofBarbering and Cosmetology
Board of Examiners in Veterinary Medicine
Board of Pharmacy
Acupuncture Board
Bureau of Home Furnishings
Structural Pest Control Board
SL State Librarian
SLC State Lands Commission
DWR Department of Water Resources
Symbols in the margins indicate the status of code changes as follows:
This symbol indicates that a change has been made to a California amendment.
> This symbol indicates California deletion of California language.
2010 CALIFORNIA BUILDING CODE
xvi 2010 CALIFORNIA BUILDING CODE
California Matrix Adoption Tables
Format of the California IVIatrix Adoption Tables
The matrix adoption tables, which follow, show the user which state agencies have adopted and/or amended given sections of the
model code. The building application determines which state agency's adoptions apply. See Section's 102 through 1 14 for building
applications and enforcement responsibilities.
Agencies are grouped together, based on either local or state enforcement responsibilities. For example, regulations from SFM
are enforced both at the state and local levels; therefore, SFM is listed twice in each adoption table indicating state enforcement
responsibilities and local enforcement responsibilities.
The side headings identify the scope of state agencies' adoption as follows:
Adopt the entire IBC chapter without state amendments.
If there is an "X" under a particular state agency's acronym on this row; this means that particular state agency has adopted the entire
model code chapter without any state amendments.
Example:
CHAPTER 2 - DEFINITIONS AND ABBREVIATIONS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as amended
(amended sections listed below)
S
A
M
P
L
E
Adopt only those sections that
are listed below
Chapter/Section
Adopt the entire IBC chapter as amended, state-amended sections are listed below:
If there is an "X" under a particular state agency's acronym on this row, it means that particular state agency has adopted the entire
model code chapter; with state amendments.
Each state-amended section that the agency has added to that particular chapter is listed. There will be an "X" in the column, by
that particular section, under the agency's acronym, as well as an "X" by each section that the agency has adopted.
Example:
CHAPTER 2 - DEFINITIONS AND ABBREVIATIONS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire chapter as amended
(amended sections listed below)
X
Adopt only those sections that
are listed below
S
A
M
P
L
E
Chapter/Section
202
X
2010 CALIFORNIA BUILDING CODE
xvii
Adopt only those sections that are listed below:
If there is an "X" under a particular state agency's acronym on this row, it means that particular state agency is adopting only specific
model code or state-amended sections within this chapter. There will be an "X" in the column under the agency's acronym, as well
as an "X" by each section that the agency has adopted.
Example:
CHAPTER 2
- DEFINITIONS AND ABBREVIATIONS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections
that are listed below
X
X
S
A
M
P
L
E
Chapter 1
202
X
X
s
A
M
P
L
E
202
X
X
C
N
T.
203
X
X
203
X
X
xvlll
2010 CALIFORNIA BUILDING CODE
ORDINANCE
The International Codes are designed and promulgated to be adopted by reference by ordinance. Jurisdictions wishing to adopt the
2010 California Building Code as an enforceable regulation governing structures and premises should ensure that certain factual
information is included in the adopting ordinance at the time adoption is being considered by the appropriate governmental body.
The following sample adoption ordinance addresses several key elements of a code adoption ordinance, including the information
required for insertion into the code text.
SAMPLE ORDINANCE FOR ADOPTION OF
THE CALIFORNIA BUILDING CODE
ORDINANCE NO.
An ordinance of the [JURISDICTION] adopting the 2010 edition of the California Building Code, regulating and governing the condi-
tions and maintenance of all property, buildings and structures; by providing the standards for supplied utilities and facilities and
other physical things and conditions essential to ensure that structures are safe, sanitary and fit for occupation and use; and the con-
demnation of buildings and structures unfit for human occupancy and use and the demolition of such structures in the [JURISDIC-
TION]; providing for the issuance of permits and collection of fees therefor; repealing Ordinance No. of the [JURISDICTION]
and all other ordinances and parts of the ordinances in conflict therewith.
The [GOVERNING BODY] of the [JURISDICTION] does ordain as follows:
Section 1. That a certain document, three (3) copies of which are on file in the office of the [TITLE OF JURISDICTION'S KEEPER OF
RECORDS] of [NAME OF JURISDICTION], being marked and designated as the California Building Code, 2010 edition, including
Appendix Chapters [FILL IN THE APPENDIX CHAPTERS BEING ADOPTED] (see California Building Code Section 101 .2. 1, 2010 edi-
tion), as published by the International Code Council, be and is hereby adopted as the Building Code of the [JURISDICTION], in the
State of California for regulating and governing the conditions and maintenance of all property, buildings and structures; by provid-
ing the standards for supplied utilities and facilities and other physical things and conditions essential to ensure that structures are
safe, sanitary and fit for occupation and use; and the condemnation of buildings and structures unfit for human occupancy and use
and the demolition of such structures as herein provided; providing for the issuance of permits and collection of fees therefor; and
each and all of the regulations, provisions, penalties, conditions and terms of said Building Code on file in the office of the [JURIS-
DICTION] are hereby referred to, adopted, and made a part hereof, as if fully set out in this ordinance, with the additions, insertions,
deletions and changes, if any, prescribed in Section 2 of this ordinance.
Section 2. The following sections are hereby revised:
Section 101.1. Insert: [NAME OF JURISDICTION]
Section 1612.3. Insert: [NAME OF JURISDICTION]
Section 1612.3. Insert: [DATE OF ISSUANCE]
Section 3412.2. Insert: [DATE IN ONE LOCATION]
Section 3. That Ordinance No. of [JURISDICTION] entitled [FILL IN HERE THE COMPLETE TITLE OF THE ORDINANCE OR
ORDINANCES IN EFFECT AT THE PRESENT TIME SO THAT THEY WILL BE REPEALED BY DEFINITE MENTION] and all other ordinances
or parts of ordinances in conflict herewith are hereby repealed.
Section 4, That if any section, subsection, sentence, clause or phrase of this ordinance is, for any reason, held to be unconstitutional,
such decision shall not affect the validity of the remaining portions of this ordinance. The [GOVERNING BODY] hereby declares that it
would have passed this ordinance, and each section, subsection, clause or phrase thereof, irrespective of the fact that any one or more
sections, subsections, sentences, clauses and phrases be declared unconstitutional.
Section 5. That nothing in this ordinance or in the Building Code hereby adopted shall be construed to affect any suit or proceeding
impending in any court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or existing, under any
act or ordinance hereby repealed as cited in Section 3 of this ordinance; nor shall any just or legal right or remedy of any character be
lost, impaired or affected by this ordinance.
Section 6. That the [JURISDICTION'S KEEPER OF RECORDS] is hereby ordered and directed to cause this ordinance to be pubUshed.
(An additional provision may be required to direct the number of times the ordinance is to be published and to specify that it is to be
in a newspaper in general circulation. Posting may also be required.)
Section 7. That this ordinance and the rules, regulations, provisions, requirements, orders and matters established and adopted
hereby shall take effect and be in full force and effect [TIME PERIOD] from and after the date of its final passage and adoption.
201 CALIFORNIA BUILDING CODE xix
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
VOLUME 1
CHAPTER 1 SCOPE AND ADMINISTRATION. ... 3
DIVISION I CALIFORNIA ADMINISTRATION 3
Section
1 . 1 General 3
1.2 Building Standards Commission 5
1.3 Corrections Standards Authority 6
1.4 Department of Consumer Affairs 6
1.5 Reserved 7
1.6 Department of Food and Agriculture 7
1.7 California Department of Public Health 7
1 .8 Department of Housing and
Community Development 7
1.8.2 Authority and Abbreviations 7
1.8.3 Local Enforcing Agency 8
1.8.4 Permits, Fees, Applications and Inspections. ... 9
1.8.5 Right-of-Entry for Enforcement 10
1.8.6 Local Modification by
Ordinance or Regulation 10
1.8.7 Alternate Materials, Designs, Tests and
Methods of Construction 10
1.8.8 Appeals Board 11
1.8.9 Unsafe Buildings or Structures 12
1.8.10 Other Building Regulations 12
1.9 Division of the State Architect 12
1.10 Office of Statewide Health Planning and
Development 15
1.11 Office of the State Fire Marshal 16
1.12 State Librarian 20
1.13 Reserved 20
1.14 California State Lands Commission 20
DIVISION II SCOPE AND ADMINISTRATION. ... 21
101 General 21
102 Applicability 21
103 Department of Building Safety 22
104 Duties and Powers of Building Officials 22
105 Permits 23
106 Floor and Roof Design Loads 25
107 Submittal Documents 25
108 Temporary Structures and Uses 27
109 Fees 27
2010 CALIFORNIA BUILDING CODE
1 10 Inspections 27
111 Certificate of Occupancy 28
1 12 Service Utilities 29
113 Board of Appeals 29
1 14 Violations 29
115 Stop Work Order 29
116 Unsafe Structures and Equipment 29
CHAPTER 2 DEFINITIONS 39
Section
201 General 39
202 Definitions 39
CHAPTER 3 USE AND OCCUPANCY
CLASSIFICATION 59
Section
301 General 59
302 Classification 59
303 Assembly Group A 59
304 Business Group B 60
305 Educational Group E 60
306 Factory Group F 61
307 High-Hazard Group H 61
308 Institutional Group 1 70
309 Mercantile Group M 71
310 Residential Group R 71
311 Storage Group S 74
312 Utility and Miscellaneous Group U 75
313 Laboratories Group L [SFM] 75
CHAPTER 4 SPECIAL DETAILED
REQUIREMENTS BASED ON
USE AND OCCUPANCY 81
Section
401 Scope 81
402 Covered Mall and Open Mall Buildings 81
403 High-Rise Buildings and Group 1-2
Occupancies Having Occupied Floors
Located more than 75 Feet Above the Lowest
Level of Fire Department Vehicle Access 84
404 Atriums 88
405 Underground Buildings 88
406 Motor- Vehicle-Related Occupancies 89
407 Group 1-2 93
xxl
TABLE OF CONTENTS
408 Group 1-3. 96
409 Motion Picture Projection Rooms 99
410 Stages and Platforms 100
411 Special Amusement Buildings 102
412 Aircraft-Related Occupancies 102
413 Combustible Storage 105
414 Hazardous Materials 105
415 Groups H-l,H-2,H-3,H-4 and H-5 109
416 Application of Flammable Finishes 122
417 Drying Rooms 122
418 Organic Coatings 122
419 LiveAVork Units 123
420 Groups R-1, R-2, R-2.1, R-3,
R-3.1andR-4 123
421 Hydrogen Cutoff Rooms 124
422 Ambulatory Health Care Facilities 125
423 Storm Shelters 125
424 Special Provisions for Residential Hotels
[HCD 1 & HCD 1-AC] 125
425 Special Provisions for Licensed
24-Hour Care Facilities in a
Group R-2.1, R-3.1, R-4 [SFM] 125
426 Group 1-4 [SFM] 128
427 Reserved 129
428 Reserved 129
429 Reserved 129
430 Horse Racing Stables [SFM] 129
431 Pet Kennels [SFM] 129
432 Combustion Engines and
Gas Turbines [SFM] 129
433 Fixed Guideway Transit Systems [SFM] 130
434 Explosives [SFM] 133
435 Reserved 136
436 Winery Caves [SFM] 136
437 Reserved 137
438 Reserved 137
439 Public Libraries [SL AND SFM] 137
440 Group C [SFM] 138
441 Reserved 140
442 Group E [SFM] 140
443 Group L [SFM] 141
444 Reserved 144
445 Large Family Day-Care Homes [SFM] 144
CHAPTER 5 GENERAL BUILDING
HEIGHTS AND AREAS 149
Section
501 General 149
502 Definitions 149
503 General Building Height and
Area Limitations 149
504 Building Height 149
505 Mezzanines 151
506 Building Area Modifications 152
507 Unlimited Area Buildings 153
508 Mixed Use and Occupancy 154
509 Special Provisions 156
CHAPTER 6 TYPES OF CONSTRUCTION 163
Section
601 General 163
602 Construction Classification 163
603 Combustible Material in
Type I and II Construction 165
CHAPTER? FIRE AND SMOKE
PROTECTION FEATURES 169
Section
701 General 169
702 Definitions 169
703 Fire-Resistance Ratings and Fire Tests 170
704 Fire-Resistance Rating of
Structural Members 171
705 Exterior Walls 173
706 Fire Walls 177
707 Fire Barriers 179
708 Shaft Enclosures 180
709 Fire Parfitions 184
710 Smoke Barriers 185
711 Smoke Partitions 185
712 Horizontal Assemblies 186
713 Penetrations 187
714 Fire-Resistant Joint Systems 189
715 Opening Protectives 190
716 Ducts and Air Transfer Openings 194
717 Concealed Spaces 199
718 Fire-Resistance Requirements for Plaster. ... 201
719 Thermal- and Sound-Insulating Materials ...201
720 Prescripfive Fire Resistance 202
721 Calculated Fire Resistance 224
xxii
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
CHAPTER 7A MATERIALS AND CONSTRUCTION
METHODS FOR EXTERIOR
WILDFIRE EXPOSURE 255
Section
701 A Scope, Purpose and Application 255
702A Definitions 256
703A Standards of Quality 256
704A Ignition-Resistant Construction 257
705A Roofing 258
706A Vents 258
707A Exterior Covering 258
708 A Exterior Windows and Doors 260
709A Decking 260
710A Accessory Structures 261
CHAPTER 8 INTERIOR FINISHES 265
Section
801 General 265
802 Definitions 265
803 Wall and Ceiling Finishes 265
804 Interior Floor Finish 268
805 Combustible Materials in Type I
and II Construction 268
806 Decorative Materials and Trim 269
807 Insulation 269
808 Acoustical Ceiling Systems , 269
CHAPTER 9 FIRE PROTECTION SYSTEMS ... 277
Section
901 General 277
902 Definitions 277
903 Automatic Sprinkler Systems 280
904 Alternative Automatic
Fire-Extinguishing Systems 287
905 Standpipe Systems 289
906 Portable Fire Extinguishers 292
907 Fire Alarm and Detection Systems 294
908 Emergency Alarm Systems 308
909 Smoke Control Systems 308
910 Smoke and Heat Vents 315
911 Fire Command Center 317
912 Fire Department Connections 318
913 Fire Pumps 318
914 Emergency Responder Safety Features 319
915 Emergency Responder Radio Coverage 319
201 CALIFORNIA BUILDING CODE
CHAPTER 10 MEANS OF EGRESS 325
Section
1001 Administration 325
1002 Definitions 325
1003 General Means of Egress 326
1004 Occupant Load 329
1005 Egress Width 330
1006 Means of Egress Illumination 330
1007 Accessible Means of Egress 331
1008 Doors, Gates and Turnstiles 334
1009 Stairways 340
1010 Ramps 343
101 1 Exit Signs 344
1012 Handrails 346
1013 Guards .347
1014 Exit Access 348
1015 Exit and Exit Access Doorways 349
1016 Exit Access Travel Distance 351
1017 Aisles 352
1018 Corridors 352
1019 Egress Balconies 354
1020 Exits 354
1021 Number of Exits and Continuity 354
1022 Exit Enclosures 355
1023 Exit Passageways 357
1024 Luminous Egress Path Markings 357
1025 Horizontal Exits 359
1026 Exterior Exit Ramps and Stairways 360
1027 Exit Discharge 360
1028 Assembly 361
1029 Emergency Escape and Rescue 366
CHAPTER 11 RESERVED 369
CHAPTER llA HOUSING ACCESSIBILITY . . . • 373
Section
1 101 A Application 373
1 102A Building Accessibility 373
1 103 A Design and Construction 374
1104A Covered Multifamily Dwellings 374
1105A Garages, Carports and Parking Facilities . . . , 375
1106A Site and Building Characteristics 375
1107A Definitions 375
1 108 A General Requirements for Accessible Parking
and Exterior Routes of Travel 378
TABLE OF CONTENTS
1109A
lllOA
llllA
1112A
1113A
1114A
1115A
1116A
1117A
1118A
1119A
11 20 A
1121A
11 22 A
11 23 A
11 24 A
1125A
11 26 A
11 27 A
1128A
11 29 A
1130A
1131A
1132A
1133A
11 34 A
1135A
11 36 A
11 37 A
1138A
1139A
1140A
1141A
11 42 A
1143A
1144A
1145A
11 46 A
xxiv
Parking Facilities 378
Exterior Routes of Travel 380
Changes in Level on Accessible Routes 380
Curb Ramps on Accessible Routes 381
Walks and Sidewalks on an
Accessible Route 381
Exterior Ramps and Landings on
Accessible Routes 382
Exterior Stairways 383
Hazards on Accessible Routes 384
General Requirements for Accessible
Entrances, Exits, Interior Routes of
Travel and Facility Accessibility 385
Egress and Areas of Refuge 385
Interior Routes of Travel 385
Interior Accessible Routes 385
Changes in Level on Accessible Routes 386
Interior Ramps and Landings on
Accessible Routes 386
Interior Stairways 387
Elevators and Platform
(Wheelchair) Lifts 388
Hazards on Accessible Routes 390
Doors 390
Common Use Facilities 391
Covered Dwelling Units 398
Reserved 398
Accessible Route Within Covered
Multifamily Dwelling Units 398
Changes in Level on Accessible Routes 398
Doors 398
Kitchens 400
Bathing and Toilet Facilities 400
Laundry Rooms 403
Electrical Receptacle,
Switch and Control Heights 403
Other Features and Facilities 405
Reserved 405
Accessible Drinking Fountains 405
Accessible Telephones 405
Accessible Swimming Pools 406
Electrical Receptacle, Switch and
Control Heights 407
Signage 407
Reserved 408
Reserved 408
Reserved 408
1 147A Reserved 408
1148A Reserved 408
1 149A Reserved 408
1 150 A Site Impracticality Tests 409
CHAPTER IIB ACCESSIBILITY TO PUBLIC
BUILDINGS, PUBLIC
ACCOMODATIONS,
COMMERICAL BUILDINGS
AND PUBLICLY FUNDED
HOUSING 465
Section
IIOIB Scope 465
1102B Definitions 465
1 103B Building Accessibility 468
1 104B Accessibility for Group A Occupancies 469
1 105B Accessibility for Group B Occupancies 472
1 106B Accessibility for Group E Occupancies 473
1 107B Factories and Warehouses 474
1108B Accessibility for Group H Occupancies 474
1109B Accessibility for Group I Occupancies 475
I I lOB Accessibility for Group M Occupancies 475
I I I IB Accessibility for Group R Occupancies 477
1112B Reserved 479
1113B Reserved 479
11 14B Facility Accessibility 479
1 1 15B Bathing and Toilet Facilities
(Sanitary Facilities) 480
1 1 16B Elevators and Special Access
(Wheelchair) Lifts 486
1 1 17B Other Building Components 489
1 1 18B Space Allowance and Reach Ranges 497
1 1 19B Special Standards of Accessibility for
Buildings with Historical Significance .... 497
1120B Floor and Levels 497
1121B Transportation Facilities 498
1 122B Fixed or Built-in Seating,
Tables and Counters 501
1123B Access to Employee Areas 502
1 124B Ground and Floor Surfaces 502
1125B Storage 502
1126B Vending Machines and Other Equipment .... 502
1 127B Exterior Routes of Travel 503
1 128B Pedestrian Grade Separations
(Overpasses and Underpasses) 504
1 129B Accessible Parking Required 504
1 130B Parking Structures 506
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
113 IB Passenger Drop-off and Loading Zones 506
1132B Outdoor Occupancies 506
11 33B General Accessibility for
Entrances, Exits and Paths of Travel 508
1134B Accessibility for Existing Buildings 515
1 1 35B Historic Preservation— Special Standards
of Accessibility for Buildings with
Historical Significance 516
CHAPTER lie STANDARDS FOR CARD
READERS AT GASOLINE
FUELDISPENSING
FACILITIES 587
Section
1 lOlC Card-Reader Devices at
Fuel-Dispensing Equipment 587
1102C Application 587
1 103C Number of Accessible
Card-Reading Devices Required 587
1 104C Required Features 587
CHAPTER 12 INTERIOR ENVIRONMENT 593
Section
1201 General 593
1202 Definitions 593
1203 Ventilation 593
1204 Temperature Control 594
1205 Lighting 595
1206 Yards or Courts 595
1207 Sound Transmission 596
1208 Interior Space Dimensions 598
1209 Access to Unoccupied Spaces 599
1210 Surrounding Materials 599
121 1 Garage Door Springs 599
1212 Reserved 600
1213 Reserved 600
1214 Reserved 600
1215 Reserved 600
1216 Reserved 600
1217 Reserved 600
1218 Reserved 600
1219 Reserved 600
1220 Reserved 600
1221 Reserved 600
1222 Reserved 600
1223 Reserved 600
1224 Hospitals 600
2010 CALIFORNIA BUILDING CODE
1225 Skilled Nursing and
Intermediate-Care Facilities 628
1226 Clinics 633
1227 Correctional Treatment Centers 636
1228 Reserved 641
1229 Reserved 641
1230 Minimum Standards for
Juvenile Facilities 641
1231 Local Detention 645
1232 Reserved 651
1233 Reserved 651
1234 Reserved 651
1235 Sanitary Control of Shellfish
(Plants and Operations) 651
1236 Laboratory Animal Quarters 651
1237 Wild Animal Quarantine Facilities 652
1238 Reserved 652
1239 Reserved 652
1240 Meat and Poultry Processing Plants 652
1241 Collection Centers and Facilities 654
1242 Renderers 654
1243 Horsemeat and Pet Food Establishments .... 654
1244 Reserved 655
1245 Reserved 655
1246 Reserved 655
1247 Reserved 655
1248 Reserved 655
1249 Reserved 655
1250 Pharmacies 655
1251 Veterinary Facilities 655
1252 Barber Colleges and Shops 656
1253 Schools of Cosmetology,
Cosmetological Establishments and
Satellite Classrooms 656
1254 Acupuncture Offices 657
CHAPTER 13 ENERGY EFFICIENCY 659
CHAPTER 14 EXTERIOR WALLS 663
Section
1401 General 663
1402 Definitions 633
1403 Performance Requirements 663
1404 Materials 664
1405 Installation of Wall Coverings 665
XXV
TABLE OF CONTENTS
1406 Combustible Materials on the
Exterior Side of Exterior Walls 669
1407 Metal Composite Materials (MCM) 670
1408 Exterior Insulation and
Finish Systems (EIFS) 671
1409 [DSA-SS and DSA-SS/CC, OSHPD 1,2 & 4]
Additional Requirements for Anchored and
Adhered Veneer 671
CHAPTER 15 ROOF ASSEMBLIES AND
ROOFTOP STRUCTURES 675
Section
1501 General 675
1502 Definitions 675
1503 Weather Protection 675
1504 Performance Requirements 676
1505 Fire Classification 677
1506 Materials 678
1507 Requirements for Roof Coverings 678
1508 Roof Insulation 687
1509 Rooftop Structures 688
1510 Reroofmg 689
1511 [DSA-SS and OSHPD 1, 2 & 4] Seismic
Anchorage of Slate Shingle, Clay and
Concrete Tile Roof Coverings 690
INDEX 691
HISTORY NOTE 731
VOLUME 2
CHAPTER 16 STRUCTURAL DESIGN 5
Section
1601 General 5
1602 Definitions and Notations 5
1603 Construction Documents 6
1604 General Design Requirements 7
1605 Load Combinations 10
1606 Dead Loads .11
1607 Live Loads 11
1608 Snow Loads 17
1609 Wind Loads 20
1610 Soil Lateral Loads 33
161 1 Rain Loads 34
1612 Flood Loads 40
1613 Earthquake Loads 42
1614 Structural Integrity 48
1615 Additional Requirements [DSA-SS/CC] 69
CHAPTER 16A STRUCTURAL DESIGN 79
Section
1601A General 79
1602 A Definitions and Notations 79
1603 A Construction Documents 81
1604A General Design Requirements 82
1605A Load Combinations 84
1606A Dead Loads 86
1607A Live Loads 86
1608A Snow Loads 91
1609A Wind Loads 94
1610A Soil Lateral Loads 104
1611A Rain Loads 104
1612A Flood Loads 1 10
1613A Earthquake Loads 112
1614A Structural Integrity 117
1615A Modifications to ASCE 7 119
CHAPTER 17 STRUCTURAL TESTS AND
SPECIAL INSPECTIONS 129
Section
1701 General 129
1702 Definitions 129
1703 Approvals 129
1704 Special Inspections 130
1705 Statement of Special Inspections 141
1706 Special Inspections for Wind Requirements . . 143
1707 Special Inspections for Seismic Resistance . . 143
1708 Structural Testing for Seismic Resistance. ... 144
1709 Contractor Responsibility 145
1710 Structural Observations 145
1711 Design Strengths of Materials 145
1712 Alternative Test Procedure 145
1713 Test Safe Load 146
1714 In-Situ Load Tests 146
1715 Preconstruction Load Tests 146
1716 Material and Test Standards 147
CHAPTER 17A STRUCTURAL TESTS AND
SPECIAL INSPECTIONS 151
Section
1701A General 151
1702A Definitions 151
1703A Approvals 152
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
1704A Special Inspections 153
1705 A Statement of Special Inspections 165
1706 A Special Inspections for Wind Requirements . . 167
1707 A Special Inspections for Seismic Resistance . . 167
1708A Structural Testing for Seismic Resistance 168
1709 A Contractor Responsibility 169
1710A Structural Observations 169
1711 A Design Strengths of Materials 169
1712A Alternative Test Procedure 170
1713A Test Safe Load 170
1714A In-Situ Load Tests 170
1715A Preconstruction Load Tests 170
1716A Material and Test Standards 171
CHAPTER 18 SOILS AND FOUNDATIONS 175
Section
1801 General 175
1802 Definitions 175
1803 Geotechnical Investigations 175
1804 Excavation, Grading and Fill 178
1805 Dampproofing and Waterproofing 179
1806 Presumptive Load-Bearing Values of Soils. . . 180
1807 Foundation Walls, Retaining Walls and
Embedded Posts and Poles 181
1808 Foundations 187
1809 Shallow Foundations 189
1810 Deep Foundations 192
CHAPTER 18A SOILS AND FOUNDATIONS .... 207
Section
1801A General 207
1802A Definitions 207
1803 A Geotechnical Investigations 208
1804 A Excavation, Grading and Fill 211
1805 A Dampproofing and Waterproofing 211
1806 A Presumptive Load-Bearing Values of Soils. . . 213
1807 A Foundation Walls, Retaining Walls
and Embedded Posts and Poles 213
1808A Foundations 215
1809A Shallow Foundations 218
1810A Deep Foundations 219
1 8 11 A Prestressed Rock and S oil
Foundation Anchors 231
CHAPTER 19 CONCRETE 235
Section
1901 General 235
1902 Definitions 235
1903 Specifications for Tests and Materials 235
1904 Durability Requirements 236
1905 Concrete Quality, Mixing and Placing 236
1906 Formwork, Embedded Pipes and
Construction Joints 238
1907 Details of Reinforcement 238
1908 Modifications to ACI 318 239
1909 Structural Plain Concrete 241
1910 Minimum Slab Provisions 242
1911 Anchorage to Concrete — Allowable
Stress Design 242
1912 Anchorage to Concrete — Strength Design . . . 243
1913 Shotcrete 244
1914 Reinforced Gypsum Concrete 245
1915 Concrete-Filled Pipe Columns 245
1916 Additional Requirements [DSA-SS/CC] 246
CHAPTER 19A CONCRETE 253
Section
1902A General 253
1902A Definitions 253
1903 A Specifications for Tests and Materials 255
1904A Durability Requirements 255
1905 A Concrete Quality, Mixing and Placing 256
1906 A Formwork, Embedded Pipes and
Construction Joints 257
1907 A Details of Reinforcement 257
1908A Modifications to ACI 318 258
1909 A Structural Plain Concrete Not Permitted
by OSHPD and DSA-SS 262
1910A Minimum Slab Provisions 262
1 9 1 1 A Anchorage to Concrete —
Allowable Stress Design 263
1 9 1 2 A Anchorage to Concrete —
Strength Design 263
1913A Shotcrete 264
1914A Reinforced Gypsum Concrete 265
1915A Concrete-Filled Pipe Columns 265
1 9 1 6A Concrete, Reinforcement and
Anchor Testing 266
1917A Existing Concrete Structures 267
2010 CALIFORNIA BUILDING CODE
xxvil
TABLE OF CONTENTS
CHAPTER 20 ALUMINUM 271
Section
2001 General 271
2002 Materials 271
2003 Inspection 271
CHAPTER 21 MASONRY 275
Section
2101 General 275
2102 Definitions and Notations 275
2103 Masonry Construction Materials 278
2104 Construction 280
2105 Quality Assurance 280
2106 Seismic Design 281
2107 Allowable Stress Design 282
2108 Strength Design of Masonry 282
2109 Empirical Design of Masonry 282
2110 Glass Unit Masonry 284
2111 Masonry Fireplaces 284
2112 Masonry Heaters 287
2113 Masonry Chimneys 287
2114 Additional Requirements [DSA-SS/CC] 291
CHAPTER 21A MASONRY 297
Section
2101A General .297
2102A Definitions and Notations 298
2 103 A Masonry Construction Materials 301
2104A Construction 302
2105A Quality Assurance 305
2106A Seismic Design 306
2 107 A Allowable Stress Design 307
2 108 A Strength Design of Masonry 308
2 109 A Empirical Design of Masonry Not Permitted
by OSHPD and DSA-SS 309
21 lOA Glass Unit Masonry 309
21 11 A Masonry Fireplaces 309
2112A Masonry Heaters 311
21 13A Masonry Chimneys 312
21 14A Nonbearing Walls 316
21 15A Masonry Screen Walls 316
CHAPTER 22 STEEL 319
Section
2201 General 319
2202 Definitions 319
2203 Identification and Protection of Steel
for Structural Purposes 319
2204 Connections 319
2205 Structural Steel 320
2206 Steel Joists 320
2207 Steel Cable Structures 321
2208 Steel Storage Racks 321
2209 Cold-Formed Steel 321
22 1 Cold-Formed Steel Light-Frame
Construction 321
221 1 Additional Requirements [DSA-SS/CC] 322
CHAPTER 22A STEEL 327
Section
2201A General 327
2202A Definitions 327
2203A Identification and Protection of
Steel for Structural Purposes 327
2204A Connections 327
2205A Structural Steel 328
2206A Steel Joists 330
2207A Steel Cable Structures 331
2208A Steel Storage Racks 331
2209A Cold-Formed Steel 331
22 1 A Cold-Formed Steel
Light-Frame Construction 331
221 lA Light Modular Steel Moment
Frames for Public Elementary and
Secondary Schools, and
Community Colleges 332
2212A Testing 333
CHAPTER 23 WOOD 337
Section
2301 General 337
2302 Definitions 337
2303 Minimum Standards and Quality 339
2304 General Construction Requirements 343
2305 General Design Requirements for
Lateral-Force-Resisting Systems 354
2306 Allowable Stress Design 357
xxviii
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
2307 Load and Resistance Factor Design 358
2308 Conventional Light-Frame Construction 358
CHAPTER 24 GLASS AND GLAZING 411
Section
2401 General 411
2402 Definitions 411
2403 General Requirements for Glass 411
2404 Wind, Snow, Seismic and
Dead Loads on Glass 411
2405 Sloped Glazing and Skylights 413
2406 Safety Glazing 415
2407 Glass in Handrails and Guards 417
2408 Glazing in Athletic Facilities 417
2409 Glass in Elevator Hoistways and
Elevator Cars 417
CHAPTER 25 GYPSUM BOARD
AND PLASTER 421
Section
2501 General 421
2502 Definitions 421
2503 Inspection 421
2504 Vertical and Horizontal Assemblies 421
2505 Shear Wall Construction 422
2506 Gypsum Board Materials 422
2507 Lathing and Plastering 422
2508 Gypsum Construction 423
2509 Gypsum Board in Showers and
Water Closets 424
2510 Lathing and Furring for Cement
Plaster (Stucco) 424
2511 Interior Plaster 425
2512 Exterior Plaster 425
2513 Exposed Aggregate Plaster 426
CHAPTER 26 PLASTIC 431
Section
2601 General 431
2602 Definitions 431
2603 Foam Plastic Insulation 43 1
2604 Interior Finish and Trim 434
2605 Plastic Veneer 435
2606 Light-Transmitting Plastics 435
2607 Light-Transmitting Plastic Wall Panels 436
2608 Light-Transmitting Plastic Glazing 437
2010 CALIFORNIA BUILDING CODE
2609 Light-Transmitting Plastic Roof Panels 437
2610 Light-Transmitting Plastic Skylight Glazing . . 438
261 1 Light-Transmitting Plastic Interior Signs .... 439
2612 Fiber Reinforced Polymer and
Fiberglass-Reinforced Polymer 439
2613 Reflective Plastic Core Insulation 440
CHAPTER 27 ELECTRICAL 443
Section
2701 General 443
2702 Emergency and Standby Power Systems 443
CHAPTER 28 MECHANICAL SYSTEMS 447
Section
2801 General 447
CHAPTER 29 PLUMBING SYSTEMS 449
Section
2901 General 449
CHAPTER 30 ELEVATORS AND
CONVEYING SYSTEMS 455
Section
3001 General 455
3002 Hoistway Enclosures 455
3003 Emergency Operations 456
3004 Hoistway Venting 457
3005 Conveying Systems 457
3006 Machine Rooms 458
3007 Fire Service Access Elevator 458
3008 Occupant Evacuation Elevators 459
3009 Special Requirements for Elevators
in Hospitals 460
CHAPTER 31 SPECIAL CONSTRUCTION 465
Section
3101 General 465
3102 Membrane Structures 465
3103 Temporary Structures 466
3104 Pedestrian Walkways and Tunnels 466
3105 Av^^nings and Canopies 467
3106 Marquees 468
3107 Signs 468
3108 Telecommunication and Broadcast Towers. . . 468
3109 Swimming Pool Enclosures and
Safety Devices 468
3110 Automatic Vehicular Gates 472
xxix
TABLE OF CONTENTS
CHAPTER 31A RESERVED 473
CHAPTER 31B PUBLIC SWIMMING POOLS ... 477
Section
3101B Scope 477
3102B Definitions 477
3103B Special Pool Classifications 478
3104B Accessibility to the Physically
Handicapped Person 478
3105B Alternate Equipment, Materials and
Methods of Construction 478
3106B Pool Construction 478
3107B Additional Requirements for a
Temporary Training Pool 479
3108B Pool Geometry 479
3109B Permanent Markings 479
3110B Steps, Recessed Steps, Ladders and
Recessed Stairs (Treads) 482
3111B Handholds 483
3112B Diving Boards 483
3113B Pool Decks 483
3114B Pool Lighting 483
3115B Bathhouse Dressing,
Shower and Toilet Facilities 484
31 16B Drinking Fountains 484
3117B Hose Bibbs 484
31 18B Enclosure of Pool Area 484
3119B Signs 485
3120B Indoor Pool Ventilation 487
3121B Foundations For Pool Equipment 487
3122B Gas Chlorination Equipment Room 487
3123B General Requirements 487
3124B Turnover Time 487
3 125B Recirculation Piping System and
Components 487
3126B Recirculation Pump Capacity 488
3127B Water Supply Inlets 488
3128B Filters (All Types) 488
3129B Rapid Sand Pressure Filters 488
3 DOB Diatomaceous Earth Filters 489
3131B High-Rate Sand Filters 489
3132B Chemical Feeders 489
3133B Disinfectant Feeders 489
3134B Pool Fittings 490
3135B Spa Pool Special Requirements 491
3136B Cleaning Systems 491
XXX
3137B Waste Water Disposal 491
3138B Reserved 491
3139B Reserved 491
3140B Reserved 491
3141B Reserved 491
3142B Reserved 491
3143B Reserved 491
3144B Reserved . 491
3145B Reserved 491
3146B Reserved 492
3147B Reserved 492
3148B Reserved 492
3149B Reserved 492
3150B Reserved 492
3151B Reserved 492
3152B Reserved 492
3153B Reserved 492
3154B Reserved 492
3155B Reserved 492
3156B Reserved 492
3157B Reserved 492
3158B Reserved 492
3159B Reserved 492
3160B 492
3161B 492
3162B Anti-Entrapment Devices and Systems 493
CHAPTER 31C RADIATION 499
Section
3101C Scope 499
3102C Radiation Shielding Barriers 499
3103C Medical Radiographic and ^..^
Photofluorographic Installations 499 AB
3104C Medical Therapeutic X-Ray Installations 499 ^^
CHAPTER 31D FOOD ESTABLISHMENTS 503
Section
3101D Scope 503
3102D Definitions 503
3103B Building and Structures 503
CHAPTER 31E RESERVED 505
CHAPTER 31F MARINE OIL TERMINALS 509
Section
3101F Introduction 509
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
3102F Audit and Inspection 510
3103F Structural Loading Criteria 521
3104F Seismic Analysis and
Structural Performance 536
3105F Mooring and Berthing
Analysis and Design 543
3106F Geotechnical Hazards and Foundations 548
3107F Structural Analysis and
Design of Components 552
3108F Fire Prevention, Detection and Suppression . . 566
3109F Piping and Pipelines 570
3110F Mechanical and Electrical Equipment 573
31 1 IF Electrical Systems 576
CHAPTER 32 ENCROACHMENTS INTO THE
PUBLIC RIGHT-OF-WAY 581
Section
3201 General 581
3202 Encroachments 581
CHAPTER 33 SAFEGUARDS DURING
CONSTRUCTION 585
Section
3301 General 585
3302 Construction Safeguards 585
3303 Demolition 585
3304 Site Work 585
3305 Sanitary 585
3306 Protection of Pedestrians 586
3307 Protection of Adjoining Property 587
3308 Temporary Use of Streets, Alleys and
Public Property 587
3309 Fire Extinguishers 587
3310 Means of Egress 588
3311 Standpipes 588
3312 Automatic Sprinkler System 588
CHAPTER 34 EXISTING STRUCTURES 591
Section
3401 General 591
3402 Definitions 592
3403 Additions 593
3404 Alterations 593
3405 Repairs. . 594
3406 Fire Escapes 596
3407 Glass Replacement 596
3408 Change of Occupancy 596
2010 CALIFORNIA BUILDING CODE
3409 Historic Buildings 597
3410 Moved Structures 597
3411 Accessibility for Existing Buildings 597
3412 Compliance Alternatives 599
3413 Existing Group R-1 and Group R-2
Occupancies [SFM] 608
3414 Existing High-Rise Buildings [SFM] 611
3415 Existing Group I Occupancies [SFM] 613
3416 Existing Group L Occupancies [SFM] 614
3417 Earthquake Evaluation and Design for
Retrofit of Existing Buildings 614
3418 Definitions 617
3419 Seismic Criteria Selection for
Existing Buildings 618
3420 Method A 621
3421 Method B 621
3422 Peer Review Requirements 622
3423 Additional Requirements for Public
Schools and Community Colleges 623
CHAPTER 34A EXISTING STRUCTURES 627
Section
3401A General 627
3402A Definitions 627
3403A Additions 628
3404A Alterations 629
3405A Repairs 630
3406A Fire Escapes 63 1
3407A Glass Replacement 631
3408A Change of Occupancy 631
3409A Historic Buildings 632
3410A Moved Structures 632
341 1 A Additions, Alterations, Repairs and
Seismic Retrofit to Existing Buildings
or Structures Designed in Accordance
v^ith Pre- 1973 Building Code 632
3412A Compliance Alternatives for Additions,
Alterations, Repairs and Seismic
Retrofit to Existing Structures 632
3413A Modifications to ASCE 41 634
3414A Peer Review Requirements 636
341 5 A Earthquake Monitoring Instruments
for Existing Buildings 637
xxxi
TABLE OF CONTENTS
CHAPTER 35 REFERENCED STANDARDS 641
APPENDIX A EMPLOYEE
QUALIFICATIONS 671
Section
A 101 Building Official Qualifications 671
A102 Referenced Standards 671
APPENDIX B BOARD OF APPEALS 675
Section
BlOl General 675
APPENDIX C GROUP U— AGRICULTURAL
BUILDINGS 679
Section
ClOl General 679
C102 Allowable Height and Area 679
C103 Mixed Occupancies 679
C104 Exits 679
APPENDIX D FIRE DISTRICTS 683
Section
DlOl General 683
D102 Building Restrictions 683
D103 Changes to Buildings 684
D104 Buildings Located Partially in the
Fire District 684
D105 Exceptions to Restrictions in Fire District . . . 684
D106 Referenced Standards 685
APPENDIX E RESERVED 689
APPENDIX F RODENTPROOFING 693
Section
FlOl General 693
APPENDIX G FLOOD-RESISTANT
CONSTRUCTION 697
Section
GlOl Administration 697
G102 Applicability 697
G103 Powers and Duties 697
G104 Permits 698
G105 Variances 698
G201 Definitions 699
G301 Subdivisions 700
G401 Site Improvement 700
xxxii
G501 Manufactured Homes 700
G601 Recreational Vehicles 700
G701 Tanks 701
G801 Other Building Work 701
G901 Temporary Structures and
Temporary Storage 701
GlOOl Utility and Miscellaneous Group U 701
GllOl Referenced Standards 702
APPENDIX H SIGNS 705
Section
HlOl General 705
H102 Definitions 705
H103 Location 705
H104 Identification 705
H105 Design and Construction 706
H106 Electrical 706
H107 Combustible Materials 706
H108 Animated Devices 706
H109 Ground Signs 706
HllO Roof Signs 707
Hill Wall Signs 707
HI 12 Projecting Signs 707
HI 13 Marquee Signs 708
HI 14 Portable Signs 708
HI 15 Referenced Standards 708
APPENDIX I PATIO COVERS 711
Section
1101 General 711
1102 Definitions 711
1103 Exterior Openings 711
1104 Structural Provisions 711
APPENDIX J GRADING 715
Section
JlOl General 715
J102 Definitions 715
J103 Permits Required 715
J 104 Permit Application and Submittals 715
J105 Inspections 716
J106 Excavations 716
J107 Fills 719
J108 Setbacks 721
J109 Drainage and Terracing 721
2010 CALIFORNIA BUILDING CODE
TABLE OF CONTENTS
Jl 10 Erosion Control 721
Jill Referenced Standards 721
APPENDIX K GROUP R-3 AND GROUP R-3.1
OCCUPANCIES PROTECTED
BY THE FACILITIES OF THE
CENTRAL VALLEY FLOOD
PROTECTION PLAN 723
Section
KlOl Scope 723
K102 Definitions 723
K103 Structural Stability 724
K104 Evacuation Locations 724
K105 Space within the Building 724
K106 Decks and Balconies that are
Evacuation Locations 724
K107 Rooftop Evacuation Locations 727
K108 Attics that are Evacuation Locations 727
K109 Alternate Means of Protection 727
INDEX 729
HISTORY NOTE 769
2010 CALIFORNIA BUILDING CODE xxxiii
xxxiv 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 16 - STRUCTURAL DESIGN
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
Adopt only those sections that
are listed below
X
X
X
Chapter/Section
1601.1.1
X
1601.1.2
X
1601.1.3
X
1601.1.4
X
1601.2
X
X
1601.3
X
X
1602.1
X
1603.1
X
1607.1, Table 1607.1
X
1607.7
X
X
X
1607.7.2
X
X
X
X
1612.3
X
1613.1
X
1613.1.1
X
1613.1.2
X
1613.3.1 ^
X
1613.5.1
X
1613.5.6
X
1613.5.6.1
X
1613.5.6.2
X
1613.6.3
X
1613.6.9
X
1615.1.1
X
1615.1.2
X
1615.1.3
X
1615.2.1.1
X
1615.2.1.2
X
1615.2.1.3
X
1615.3.1
X
1615.4
X
1615.5.1.1
X
1615.5.1.2
X
1615.5.1.3
X
1615.5.1.4
X
1615.5.1.5
X
1615.5.1.6
X
(continued)
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 16 - STRUCTURAL DESIGN— continued
Adopting agency
BSD
SFM
HOD
DSA
OSHPD
ORA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
Adopt only those sections that
are listed below
X
X
X
Chapter/Section
1615.5.2
X
1615.6
X
1615.7.1
X
1615.7.2
X
1615.8
X
1615.9.1
X
1615.9.2 - Active Earthquake
Fault
X
1615.9.2 -Base
X
1615.9.2 - Distance for an
Active Earthquake Fault
X
1615.9.2 - Irregular Structure
X
1615.9.2 - Next Generation
Attenuation (NGA)
X
1615.9.2 - Structural Elements
X
1615.9.3
X
1615.9.4
X
1615.9.4.1
X
1615.9.4.2
X
1615.9.5
X
1615.9.6
X
1615.10
X
1615.10.1
X
1615.10.2
X
1615.10.3
X
1615.10.4
X
1615.10.5
X
1615.10.6
X
1615.10.7
X
1615.10.8
X
1615.10.9
X
1615.10.10
X
1615.10.11
X
1615.10.12
X
1615.10.13
X
1615.10.14
X
1615.10.15
X
(continued)
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 16 - STRUCTURAL DESIGN— continued
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
Adopt only those sections that
are listed below
X
X
X
Chapter/Section
1615.10.16
X
1615.10.17
X
1615.10.18
X
1615.10.19
X
1615.10.20
X
1615.10.21
X
1615.10.22
X
1615.10.23
X
1615.10.24
X
1615.10.25
X
1615.10.26
X
2010 CALIFORNIA BUILDING CODE
2010 CALIFORNIA BUILDING CODE
CHAPTER 16
STRUCTURAL DESIGN
n
SECTION 1601
GENERAL
1601.1 Scope. The provisions of this chapter shall govern the
structural design of buildings, structures and portions thereof
regulated by this code.
1601.1.1 Application, [DSA-SS/CC] The scope of applica-
tion of Chapter 16 is as follows:
Community college buildings regulated by the Division
of the State Architect-Structural Safety/Community Col-
leges (DSA-SS/CC), as listed in Section 1.9.2,2,
1601.1.2 Identification of amendments, [DSA-SS/CC]
Division of the State Architect-Structural Safety/Commu-
nity Colleges (DSA-SS/CC) amendments appear in this
chapter preceded with the appropriate acronym, as follows:
Division of the State Architect-Structural Safety/Com-
munity Colleges: [DSA-SS/CC] - For community college
buildings listed in Section 1.9.2,2,
1601.1.3 Reference to other chapters. [DSA-SS/CC]
Where reference within this chapter is made to sections in
Chapters 17 and 18, the provisions in Chapters 17 A and
18A respectively shall apply instead.
1601.1.4 Amendments. [DSA-SS/CC] See Section 161 5 for
additional requirements.
1601.2 References, [DSA-SS/CC, OSHPD 2] All referenced
codes and standards listed in Chapter 35 shall include all the
modifications contained in this code to referenced standards.
In the event of any discrepancy between this code and a refer-
enced standard, refer to Section 1.1.7.
1601.3 Enforcement agency approval, [DSA-SS/CC,
OSHPD 2] In addition to requirements ofCCR Title 24, Parts 1
Sl 2, any aspect of project design, construction, quality assur-
ance or quality control programs for which this code requires
approval by the design professional are also subject to
approval by the enforcement agency.
SECTION 1602
DEFINITIONS AND NOTATIONS
1602.1 Definitions. The following words and terms shall, for
the purposes of this chapter, have the meanings shown herein.
ALLOWABLE STRESS DESIGN. A method of proportion-
ing structural members, such that elastically computed stresses
produced in the members by nominal loads do not exceed spec-
ified allowable stresses (also called "working stress design").
DEAD LOADS. The weight of materials of construction
incorporated into the building, including but not limited to
walls, floors, roofs, ceilings, stairways, built-in partitions, fin-
ishes, cladding and other similarly incorporated architectural
and structural items, and the weight of fixed service equipment,
such as cranes, plumbing stacks and risers, electrical feeders,
heating, ventilating and air-conditioning systems and
automatic sprinkler systems. ,
DESIGN STRENGTH. The product of the nominal strength
and a resistance factor (or strength reduction factor).
DIAPHRAGM. A horizontal or sloped system acting to trans-
mit lateral forces to the vertical-resisting elements. When the
term "diaphragm" is used, it shall include horizontal bracing
systems.
Diaphragm, blocked. In light-frame construction, a dia-
phragm in which all sheathing edges not occurring on a
framing member are supported on and fastened to blocking.
Diaphragm boundary. In light- frame construction, a loca-
tion where shear is transferred into or out of the diaphragm
sheathing. Transfer is either to a boundary element or to
another force-resisting element.
Diaphragm chord. A diaphragm boundary element per-
pendicular to the applied load that is assumed to take axial
stresses due to the diaphragm moment.
Diaphragm flexible. A diaphragm is flexible for the pur-
pose of distribution of story shear and torsional moment
where so indicated in Section 12.3. 1 of ASCE 7, as modified
in Section 1613.6.1.
Diaphragm, rigid. A diaphragm is rigid for the purpose of
distribution of story shear and torsional moment when the
lateral deformation of the diaphragm is less than or equal to
two times the average story drift.
DURATION OF LOAD. The period of continuous applica-
tion of a given load, or the aggregate of periods of intermittent
applications of the same load.
ENFORCEMENT AGENT. [OSHPD 2] That individual
within the agency or organization charged with responsibility
for agency or organization compliance with the requirements
of this code. Used interchangeably with "Building Official" or
"Code Official."
ESSENTIAL FACILITIES. Buildings and other structures
that are intended to remain operational in the event of extreme
environmental loading from flood, wind, snow or earthquakes.
FABRIC PARTITION. A partition consisting of a finished
surface made of fabric, without a continuous rigid backing, that
is directly attached to a framing system in which the vertical
framing members are spaced greater than 4 feet (1219 mm) on
center.
FACTORED LOAD. The product of a nominal load and a load
factor.
GUARD. See Section 1002.1.
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
IMPACT LOAD. The load resulting from moving machinery,
elevators, craneways, vehicles and other similar forces and
kinetic loads, pressure and possible surcharge from fixed or
moving loads.
LIMIT STATE. A condition beyond which a structure or
member becomes unfit for service and is j udged to be no longer
useful for its intended function (serviceability limit state) or to
be unsafe (strength limit state).
LIVE LOADS. Those loads produced by the use and occu-
pancy of the building or other structure and do not include con-
struction or environmental loads such as wind load, snow load,
rain load, earthquake load, flood load or dead load.
LIVE LOADS (ROOF). Those loads produced (1) during
maintenance by workers, equipment and materials; and (2)
during the life of the structure by movable objects such as
planters and by people.
LOAD AND RESISTANCE FACTOR DESIGN (LRFD). A
method of proportioning structural members and their connec-
tions using load and resistance factors such that no applicable
limit state is reached when the structure is subjected to appro-
priate load combinations. The term "LRFD" is used in the
design of steel and wood structures.
LOAD EFFECTS. Forces and deformations produced in
structural members by the applied loads.
LOAD FACTOR. A factor that accounts for deviations of the
actual load from the nominal load, for uncertainties in the analy-
sis that transforms the load into a load effect, and for the proba-
bihty that more than one extreme load will occur simultaneously.
LOADS. Forces or other actions that result from the weight of
building materials, occupants and their possessions, environ-
mental effects, differential movement and restrained dimen-
sional changes. Permanent loads are those loads in which
variations over time are rare or of small magnitude, such as
dead loads. All other loads are variable loads (see also ''Nomi-
nal loads").
NOMINAL LOADS. The magnitudes of the loads specified in
this chapter (dead, live, soil, wind, snow, rain, flood and earth-
quake).
OCCUPANCY CATEGORY. A category used to determine
structural requirements based on occupancy.
OTHER STRUCTURES. Structures, other than buildings,
for which loads are specified in this chapter.
PANEL (PART OF A STRUCTURE). The section of a floor,
wall or roof comprised between the supporting frame of two
adjacent rows of columns and girders or column bands of floor
or roof construction.
RESISTANCE FACTOR. A factor that accounts for devia-
tions of the actual strength from the nominal strength and the
manner and consequences of failure (also called "strength
reduction factor").
STRENGTH, NOMINAL. The capacity of a structure or
member to resist the effects of loads, as determined by compu-
tations using specified material strengths and dimensions and
equations derived from accepted principles of structural
mechanics or by field tests or laboratory tests of scaled models.
allowing for modeling effects and differences between labora-
tory and field conditions.
STRENGTH, REQUIRED. Strength of a member, cross sec-
tion or connection required to resist factored loads or related
internal moments and forces in such combinations as stipulated
by these provisions.
STRENGTH DESIGN. A method of proportioning structural
members such that the computed forces produced in the mem-
bers by factored loads do not exceed the member design
strengtii [also called "load and resistance factor design''
(LRFD)]. The term "strength design" is used in the design of
concrete and masonry structural elements.
VEHICLE BARRIER SYSTEM. A system of building com-
ponents near open sides of a garage floor or ramp or building
walls that act as restraints for vehicles.
NOTATIONS.
D = Dead load.
E = Combined effect of horizontal and vertical
earthquake induced forces as defined in Section
12.4.2ofASCE7.
F = Load due to fluids with well-defined pressures and
maximum heights.
F^ = Flood load in accordance with Chapter 5 of ASCE 7. I
H = Load due to lateral earth pressures, ground water
pressure or pressure of bulk materials.
L = Live load, except roof live load, including any per-
mitted live load reduction.
L^ = Roof live load including any permitted live load
reduction.
R = Rain load.
S = Snow load.
T = Self-straining force arising from contraction or
expansion resulting from temperature change,
shrinkage, moisture change, creep in component
materials, movement due to differential settlement
or combinations thereof.
W = Load due to wind pressure.
SECTION 1603
CONSTRUCTION DOCUMENTS
1603.1 General. Construction documents shall show the size,
section and relative locations of structural members with floor
levels, column centers and offsets dimensioned. The design
loads and other information pertinent to the structural design
required by Sections 1603.1.1 through 1603. L9 shall be indi-
cated on the construction documents.
Exception: Construction documents for buildings con-
structed in accordance with the conventional light-frame
construction provisions of Section 2308 shall indicate the
following structural design information:
1. Floor and roof live loads.
2. Ground snow load, P„.
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
3. Basic wind speed (3-second gust), miles per hour
(mph) (km/hr) and wind exposure.
4. Seismic design category and site class.
5. Flood design data, if located in flood hazard areas
established in Section 1612.3.
6. Design load-bearing values of soils.
[OSHPD 2] Additional requirements are included in Sections
7-115 and 7-125 of the California Administrative Code (Part 1,
Title 24, C.C.R).
1603.1.1 Floor live load. The uniformly distributed, con-
centrated and impact floor live load used in the design shall
be indicated for floor areas. Use of live load reduction in
accordance with Section 1607.9 shall be indicated for each
type of live load used in the design.
1603.1.2 Roof live load. The roof live load used in the
design shall be indicated for roof areas (Section 1607.1 1).
1603.1.3 Roof snow load. The ground snow load, Pg, shall be
indicated. In areas where the ground snow load, P^, exceeds
10 pounds per square foot (psf) (0.479 kN/m^), the following
additional information shall also be provided, regardless of
whether snow loads govern the design of the roof:
1. Flat-roof snow load, P^
2. Snow exposure factor, C^.
3. Snow load importance factor, /.
4. Thermal factor, Q.
1603.1.4 Wind design data. The following information
related to wind loads shall be shown, regardless of whether
wind loads govern the design of the lateral-force-resisting
system of the building:
1. Basic wind speed (3-second gust), miles per hour
(km/hr).
2. Wind importance factor, /, and occupancy category.
3. Wind exposure. Where more than one wind exposure
is utilized, the wind exposure and applicable wind
direction shall be indicated.
4. The applicable internal pressure coefficient.
5. Components and cladding. The design wind pres-
sures in terms of psf (kN/m^) to be used for the design
of exterior component and cladding materials not spe-
cifically designed by the registered design profes-
sional.
1603.1.5 Earthquake design data. The following informa-
tion related to seismic loads shall be shown, regardless of
whether seismic loads govern the design of the lateral-
force-resisting system of the building:
1. Seismic importance factor, /, and occupancy cate-
gory.
2. Mapped spectral response accelerations, Ss and 5;.
3. Site class,
4. Spectral response coefficients, ^£,5 and S^^j.
5. Seismic design category.
6. Basic seismic-force-resisting system(s).
7. Design base shear.
8. Seismic response coefficient(s), Q.
9. Response modification factor(s), R.
10. Analysis procedure used.
1603.1.6 Geotechnical information. The design load-
bearing values of soils shall be shown on the construction
documents.
1603.1.7 Flood design data. For buildings located in whole
or in part in flood hazard areas as established in Section
1612.3, the documentation pertaining to design, if required
in Section 1612.5, shall be included and the following infor-
mation, referenced to the datum on the conmiunity's Flood
Insurance Rate Map (FIRM), shall be shown, regardless of
whether flood loads govern the design of the building:
1 . In flood hazard areas not subject to high-velocity
wave action, the elevation of the proposed lowest
floor, including the basement.
2. In flood hazard areas not subject to high-velocity
wave action, the elevation to which any nonresiden-
tial building will be dry floodproofed.
3. In flood hazard areas subject to high- velocity wave
action, the proposed elevation of the bottom of the
lowest horizontal structural member of the lowest
floor, including the basement.
1603.1.8 Special loads. Special loads that are applicable to
the design of the building, structure or portions thereof shall
be indicated along with the specified section of this code
that addresses the special loading condition.
1603.1.9 Systems and components requiring special
inspections for seismic resistance. Construction docu-
ments or specifications shall be prepared for those systems
and components requiring special inspection for seismic
resistance as specified in Section 1707.1 by the registered
design professional responsible for their design and shall be
submitted for approval in accordance with Section 107.1,
Chapter 7, Division 11. Reference to seismic standards in
lieu of detailed drawings is acceptable.
SECTION 1604
GENERAL DESIGN REQUIREMENTS
1604.1 General. Building, structures and parts thereof shall be
designed and constructed in accordance with strength design,
load and resistance factor design, allowable stress design,
empirical design or conventional construction methods, as per-
mitted by the applicable material chapters.
1604.2 Strength. Buildings and other structures, and parts
thereof, shall be designed and constructed to support safely the
factored loads in load combinations defined in this code with-
out exceeding the appropriate strength limit states for the mate-
rials of construction. Alternatively, buildings and other
structures, and parts thereof, shall be designed and constructed
to support safely the nominal loads in load combinations
defined in this code without exceeding the appropriate speci-
fied allowable stresses for the materials of construction.
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
Loads and forces for occupancies or uses not covered in this
chapter shall be subject to the approval of the building official.
1604.3 Serviceability. Structural systems and members
thereof shall be designed to have adequate stiffness to limit
deflections and lateral drift. See Section 12, 12. 1 of ASCE 7 for
drift limits applicable to earthquake loading.
1604.3.1 Deflections. The deflections of structural mem-
bers shall not exceed the more restrictive of the limitations
of Sections 1604.3.2 through 1604.3.5 or that permitted by
Table 1604.3.
TABLE 1604.3
DEFLECTION LIMITS^' '''*=' "^^ '
CONSTRUCTION
L
Soriy'
D+U"'^
Roof members:^
Supporting plaster ceiling
Supporting nonplaster ceiling
Not supporting ceiling
1/360
//240
//1 80
//360
//240
//1 80
1/240
//ISO
//1 20
Roor members
//360
—
//240
Exterior walls and interior partitions:
With brittle finishes
With flexible finishes
—
//240
//1 20
—
Farm buildings
—
—
//1 80
Greenhouses
-^
—
//120
For SI: 1 foot = 304.8 mm.
a. For structural roofing and siding made of formed metal sheets, the total load
deflection shall not exceed //60. For secondary roof structural members sup-
porting formed metal roofing, the live load deflection shall not exceed //1 50,
For secondary wall members supporting formed metal siding, the design
wind load deflection shall not exceed 1/90. For roofs, this exception only
applies when the metal sheets have no roof covering.
b. Interior partitions not exceeding 6 feet in height and flexible, folding and
portable partitions are not governed by the provisions of this section. The
deflection criterion for interior partitions is based on the horizontal load
defined in Section 1607.13.
c. See Section 2403 for glass supports.
d. For wood strucmral members having a moisture content of less than 1 6 per-
cent at time of installation and used under dry conditions, the deflection
resulting from L + 0.5D is permitted to be substituted for the deflection
resulting from L + D.
e. The above deflections do not ensure against ponding. Roofs that do not have
sufficient slope or camber to assure adequate drainage shall be investigated
for ponding. See Section 1611 for rain and ponding requirements and Sec-
tion 1503.4 for roof drainage requirements.
f. The wind load is permitted to be taken as 0.7 times the "component and clad-
ding" loads for the purpose of determining deflection limits herein.
g. For steel structural members, the dead load shall be taken as zero.
h. For aluminum structural members or aluminum panels used in skylights and
sloped glazing framing, roofs or walls of sunroom additions or patio covers,
not supporting edge of glass or aluminum sandwich panels, the total load
deflection shall not exceed //60. For continuous aluminum structural members
supporting edge of glass, the total load deflection shall not exceed 1/115 for
each glass lite or //60 for the entire length of the member, whichever is more
stringent. For aluminum sandwich panels used in roofs or walls of sunroom
additions or patio covers, the total load deflection shall not exceed //120.
i. For cantilever members, / shall be taken as twice the length of the cantilever.
1604.3.2 Reinforced concrete. The deflection of rein-
forced concrete structural members shall not exceed that
permitted by ACI 318.
1604.3.3 Steel. The deflection of steel structural members
shall not exceed that permitted by AISC 360, AISI SlOO,
ASCE 3, ASCE 8, SJI CJ-1.0, SJI JG-1.1, SJI K-1.1 or SJI
LH/DLH-1.1, as applicable.
1604.3.4 Masonry. The deflection of masonry structural
members shall not exceed that permitted by TMS 402/ACI
530/ASCE 5.
1604.3.5 Aluminum. The deflection of aluminum struc-
tural members shall not exceed that permitted by AA
ADMl.
1604.3.6 Limits. Deflection of structural members over
span, /, shall not exceed that permitted by Table 1604.3.
1604.4 Analysis. Load effects on structural members and their
connections shall be determined by methods of structural anal-
ysis that take into account equilibrium, general stability, geo-
metric compatibility and both short- and long-term material
properties.
Members that tend to accumulate residual deformations
under repeated service loads shall have included in their analy-
sis the added eccentricities expected to occur during their ser-
vice life.
Any system or method of construction to be used shall be
based on a rational analysis in accordance with well-estabHshed
principles of mechanics. Such analysis shall result in a system
that provides a complete load path capable of transferring loads
from their point of origin to the load-resisting elements.
The total lateral force shall be distributed to the various verti-
cal elements of the lateral-force-resisting system in proportion
to their rigidities, considering the rigidity of the horizontal
bracing system or diaphragm. Rigid elements assumed not to
be a part of the lateral-force-resisting system are permitted to
be incorporated into buildings provided their effect on the
action of the system is considered and provided for in the
design. Except where diaphragms are flexible, or are permitted
to be analyzed as flexible, provisions shall be made for the
increased forces induced on resisting elements of the structural
system resulting from torsion due to eccentricity between the
center of application of the lateral forces and the center of rigid-
ity of the lateral-force-resisting system.
Every structure shall be designed to resist the overturning
effects caused by the lateral forces specified in this chapter. See
Section 1609 for wind loads, Section 1610 for lateral soil loads
and Section 1613 for earthquake loads.
1604.5 Occupancy category. Each building and structure
shall be assigned an occupancy category in accordance with
Table 1604.5.
1604.5.1 Multiple occupancies. Where a building or struc-
ture is occupied by two or more occupancies not included in
the same occupancy category, it shall be assigned the classifi-
cation of the highest occupancy category corresponding to
the various occupancies. Where buildings or structures have
two or more portions that are structurally separated, each por-
tion shall be separately classified. Where a separated portion
of a building or structure provides required access to,
required egress from or shares life safety components with
another portion having a higher occupancy category, both
portions shall be assigned to the higher occupancy category.
1604.6 In-situ load tests. The building official is authorized to
require an engineering analysis or a load test, or both, of any
construction whenever there is reason to question the safety of
2010 CALIFORNIA BUILDING CODE
the construction for the intended occupancy. Engineering anal-
ysis and load tests shall be conducted in accordance with Sec-
tion 1714.
1604.7 Preconstniction load tests. Materials and methods of
construction that are not capable of being designed by
approved engineering analysis or that do not comply with the
applicable material design standards listed in Chapter 35, or
alternative test procedures in accordance with Section 1712,
shall be load tested in accordance with Section 1715.
1604.8 Anchorage.
1604.8.1 General. Anchorage of the roof to walls and col-
umns, and of walls and columns to foundations, shall be
provided to resist the uplift and sliding forces that result
from the application of the prescribed loads.
1604.8.2 Walls. Walls shall be anchored to floors, roofs and
other structural elements that provide lateral support for the
STRUCTURAL DESIGN
wall. Such anchorage shall provide a positive direct connec-
tion capable of resisting the horizontal forces specified in
this chapter but not less than the minimum strength design
horizontal force specified in Section 1 1 .7.3 of ASCE 7, sub-
stituted for "£" in the load combinations of Section 1605.2
or 1605.3. Concrete and masonry walls shall be designed to
resist bending between anchors where the anchor spacing
exceeds 4 feet (1219 mm). Required anchors in masonry
walls of hollow units or cavity walls shall be embedded in a
reinforced grouted structural element of the wall. See Sec-
tions 1 609 for wind design requirements and 1 6 1 3 for earth-
quake design requirements.
1604.8.3 Decks. Where supported by attachment to an exte-
rior wall, decks shall be positively anchored to the primary
structure and designed for both vertical and lateral loads as
applicable. Such attachment shall not be accomplished by
the use of toenails or hails subject to withdrawal. Where
TABLE 1604.5
OCCUPANCY CATEGORY OF BUILDINGS AND OTHER STRUCTURES
OCCUPANCY
CATEGORY
NATURE OF OCCUPANCY
I
Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to:
• Agricultural facilities.
• Certain temporary facilities.
• Minor storage facihties.
II
Buildings and other structures except those listed in Occupancy Categories I, III and IV
m
Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not
limited to:
• Buildings and other structures whose primary occupancy is public assembly with an occupant load greater than 300.
• Buildings and other structures containing elementary school, secondary school or day care facilities with an occupant
load greater than 250.
• Buildings and other structures containing adult education facilities, such as colleges and universities, with an occupant
load greater than 500.
• Group 1-2 occupancies with an occupant load of 50 or more resident patients but not having surgery or emergency
treatment facilities.
• Group 1-3 occupancies,
• Any other occupancy with an occupant load greater than 5,000^.
• Power-generating stations, water treatment facilities for potable water, waste water treatment facilities and other pub-
lic utility facihties not included in Occupancy Category IV.
• Buildings and other structures not included in Occupancy Category IV containing sufficient quantities of toxic or ex-
plosive substances to be dangerous to the public if released.
IV
Buildings and other structures designated as essential facihties, including but not limited to:
• Group 1-2 occupancies having surgery or emergency treatment facilities. [OSHPD 3] For OSHPD 3 facilities, see Sec-
tion 308.3,2.
• Fire, rescue, ambulance and pohce stations and emergency vehicle garages.
• Designated earthquake, hurricane or other emergency shelters.
• Designated emergency preparedness, communications and operations centers and other facilities required for emer-
gency response.
• Power-generating stations and other pubhc utility facilities required as emergency backup facilities for Occupancy
Category IV structures.
• Structures containing highly toxic materials as defined by Section 307 where the quantity of the material exceeds the
maximum allowable quantities of Table 307. 1 (2).
• Aviation control towers, air traffic control centers and emergency aircraft hangars.
• Buildings and other structures having critical national defense functions.
• Water storage facihties and pump structures required to maintain water pressure for fire suppression.
a. For purposes of occupant load calculation, occupancies required by Table 1004. 1. 1 to use gross floor area calculations shall be permitted to use net floor areas to
determine the total occupant load.
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
positive connection to the primary building structure cannot
be verified during inspection, decks shall be self-support-
ing. Connections of decks with cantilevered framing mem-
bers to exterior walls or other framing members shall be
designed for both of the following:
1. The reactions resulting from the dead load and live
load specified in Table 1607. 1, or the snow load spec-
ified in Section 1608, in accordance with Section
1605, acting on all portions of the deck.
2, The reactions resulting from the dead load and live
load specified in Table 1607.1, or the snow load spec-
ified in Section 1608, in accordance with Section
1605, acting on the cantilevered portion of the deck,
and no live load or snow load on the remaining por-
tion of the deck.
1604.9 Counteracting structural actions. Structural mem-
bers, systems, components and cladding shall be designed to
resist forces due to earthquake and wind, with consideration of
overturning, sliding and uplift. Continuous load paths shall be
provided for transmitting these forces to the foundation. Where
sliding is used to isolate the elements, the effects of friction
between sliding elements shall be included as a force.
1604.10 Wind and seismic detailing. Lateral-force-resisting
systems shall meet seismic detailing requirements and limita-
tions prescribed in this code and ASCE 7, excluding Chapter
14 and Appendix 1 1 A, even when wind load effects are greater
than seismic load effects.
SECTION 1605
LOAD COMBINATIONS
1605.1 General. Buildings and other structures and portions
thereof shall be designed to resist:
1. The load combinations specified in Section 1605,2,
1605.3.1 or 1605.3.2,
2. The load combinations specified in Chapters 18 through
23, and
3. The load combinations with overstrength factor speci-
fied in Section 12.4.3.2 of ASCE 7 where required by
Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With
the simplified procedure of ASCE 7 Section 12.14, the
load combinations with overstrength factor of Section
12.14.3.2 of ASCE 7 shall be used.
Applicable loads shall be considered, including both earth-
quake and wind, in accordance with the specified load combi-
nations. Each load combination shall also be investigated with
one or more of the variable loads set to zero.
Where the load combinations with overstrength factor in Sec-
tion 12.4.3.2 of ASCE 7 apply, they shall be used as follows:
1. The basic combinations for strength design with
overstrength factor in Heu of Equations 16-5 and 16-7 in
Section 1605.2.1.
2. The basic combinations for allowable stress design with
overstrength factor in lieu of Equations 16-12, 16-13 and
16-15 in Section 1605.3.1.
3. The basic combinations for allowable stress design with
overstrength factor in lieu of Equations 16-20 and 16-21
in Section 1605.3.2.
1605.1.1 Stability. Regardless of which load combinations
are used to design for strength, where overall structure sta-
bility (such as stability against overturning, sliding, or buoy-
ancy) is being verified, use of the load combinations
specified in Section 1605.2 or 1605.3 shall be permitted.
Where the load combinations specified in Section 1605.2
are used, strength reduction factors applicable to soil resis-
tance shall be provided by a registered design professional.
The stability of retaining walls shall be verified in accor-
dance with Section 1807.2.3.
1605.2 Load combinations using strength design or load
and resistance factor design.
1605.2.1 Basic load combinations. Where strength design
or load and resistance factor design is used, structures and
portions thereof shall resist the most critical effects from the
following combinations of factored loads:
1.4(D+F)
(Equation 16-1)
L2(Z) + F+r) + L6(L + /f) +
0.5(4 or 5 or/?)
(Equation 16-2)
1 .2D + 1 .6(L, or 5 or /?) + (/IL or 0.8 W) (Equation 16-3)
L2D+ 1.6W+/iL + 0.5(L,or5or/?) (Equation 16-4)
1 .2D + 1 .OE +f^L +f^S (Equation 16-5)
0.9D+ 1.6W+ 1.6^ (Equation 16-6)
0.9D + 1 .OE + 1 .67/ (Equation 16-7)
where:
/i = 1 for floors in places of public assembly, for live loads
in excess of 100 pounds per square foot (4.79 kN/m^),
and for parking garage live load, and
= 0.5 for other live loads.
/2 = 0.7 for roof configurations (such as saw tooth) that do
not shed snow off the structure, and
= 0.2 for other roof configurations.
Exception: Where other factored load combinations are
specifically required by the provisions of this code, such
combinations shall take precedence.
1605.2.2 Flood loads. Where flood loads, F^, are to be con-
sidered in the design, the load combinations of Section 2.3.3
of ASCE 7 shall be used.
1605.3 Load combinations using allowable stress design.
1605.3.1 Basic load combinations. Where allowable stress
design (working stress design), as permitted by this code, is
used, structures and portions thereof shall resist the most
critical effects resulting from the following combinations of
loads:
D + F
D-^H+F+L + T
D+//+F+(L,or5or/?)
(Equation 16-8)
(Equation 16-9)
(Equation 16-10)
10
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
D + /f + F + 0.75(L + r) +
0.75(L,or5ori?)
Z)+//+F+(Wor0.7£)
D + ^ + F + 0J5(W or 0.1 E) +
0,75L + 0.75(L,or5ori?)
0.6D + W+//
0.6D + 0.7F+//
(Equation 16-11)
(Equation 16-12)
(Equation 16-13)
(Equation 16-14)
(Equation 16-15)
0.9D + E/1.4
Exceptions:
(Equation 16-21)
Exceptions:
1 . Crane hook loads need not be combined with roof
Hve load or with more than three-fourths of the
snow load or one-half of the wind load.
2, Rat roof snow loads of 30 psf (1 .44 kN/m^) or less
and roof live loads of 30 psf or less need not be
combined with seismic loads. Where flat roof
snow loads exceed 30 psf ( 1 .44 kN/m^), 20 percent
shall be combined with seismic loads.
1605.3.1.1 Stress increases. Increases in allowable
stresses specified in the appropriate material chapter or
the referenced standards shall not be used with the load
combinations of Section 1605.3.1, except that increases
shall be permitted in accordance with Chapter 23.
1605.3.1.2 Flood loads. Where flood loads, F^, are to be
considered in design, the load combinations of Section
2.4.2 of ASCE 7 shall be used.
1605.3.2 Alternative basic load combinations. In lieu of the
basic load combinations specified in Section 1605.3.1, struc-
tures and portions thereof shall be permitted to be designed for
the most critical effects resulting from the following combina-
tions. When using these alternative basic load combinations
that include wind or seismic loads, allowable stresses are per-
mitted to be increased or load combinations reduced where
permitted by the material chapter of this code or the referenced
standards. For load combinations that include the counteract-
ing effects of dead and wind loads, only two-thirds of the mini-
mum dead load likely to be in place during a design wind event
shall be used. Where wind loads are calculated in accordance
with Chapter 6 of ASCE 7, the coefficient co in the following
equations shall be taken as 1 .3. For other wind loads, CO shall be
taken as 1. When using these alternative load combinations to
evaluate sliding, overturning and soil bearing at the soil-struc-
ture interface, the reduction of foundation overturning from
Section 12. 13.4 in ASCE 7 shall not be used. When using these
alternative basic load combinations for proportioning founda-
tions for loadings, which include seismic loads, the vertical
seismic load effect, E^, in Equation 12.4-4 of ASCE 7 is permit-
ted to be taken equal to zero.
D-\-L+(L,otSoxR)
D + L + (a)W)
D+L + coW+5/2
D-HL + 5 + C0W2
D+L + 5 + E/1.4
(Equation 16-16)
(Equation 16-17)
(Equation 16-18)
(Equation 16-19)
(Equation 16-20)
1 . Crane hook loads need not be combined with roof hve
loads or with more than three-fourths of the snow load
or one-half of the wind load.
2. Flat roof snow loads of 30 psf ( 1 .44 kN/m^) or less and
roof live loads of 30 psf or less need not be combined
with seismic loads. Where flat roof snow loads
exceed 30 psf (1 .44 kN/m^), 20 percent shall be com-
bined with seismic loads.
1605.3.2.1 Other loads. Where F,HotT are to be con-
sidered in the design, each applicable load shall be added
to the combinations specified in Section 1605.3.2.
1605.4 Heliports and helistops. HeUport and helistop landing
areas shall be designed for the following loads, combined in
accordance with Section 1605:
1 . Dead load, D, plus the gross weight of the helicopter, D^,,
plus snow load, 5.
2. Dead load, Z), plus two single concentrated impact loads,
L, approximately 8 feet (2438 mm) apart applied any-
where on the touchdown pad (representing each of the
helicopter's two main landing gear, whether skid type or
wheeled type), having a magnitude of 0.75 times the
gross weight of the helicopter. Both loads acting together
total 1.5 times the gross weight of the helicopter.
3. Dead load, D, plus a uniform live load, L, of 100 psf (4.79
kN/m2).
Exception: Landing areas designed for helicopters with
gross weights not exceeding 3,000 pounds (13.34 kN) in
accordance with Items 1 and 2 shall be permitted to be
designed using a 40 psf (1.92 kN/m^) uniform live load in
Item 3, provided the landing area is identified with a 3,000-
pound (13.34 kN) weight limitation. This 40 psf (1.92
kN/m^) uniform live load shall not be reduced. The landing
area weight Hmitation shall be indicated by the numeral "3"
(kips) located in the bottom right comer of the landing area
as viewed from the primary approach path. The indication
for the landing area weight limitation shall be a minimum 5
feet (1524 mm) in height.
SECTION 1606
DEAD LOADS
1606.1 General. Dead loads are those loads defined in Section
1602.1. Dead loads shall be considered permanent loads.
1606.2 Design dead load. For purposes of design, the actual
weights of materials of construction and fixed service equip-
ment shall be used. In the absence of definite information, val-
ues used shall be subject to the approval of the building official.
SECTION 1607
LIVE LOADS
1607.1 General. Live loads are those loads defined in Section
1602.1.
2010 CALIFORNIA BUILDING CODE
11
STRUCTURAL DESIGN
TABLE 1607.1
I MINIMUM UNIFORMLY DISTRIBUTED
MINIMUM CONCENTRATED
LIVE LOADS, L^ AND
LIVE L0ADS9
TABLE 1607.1— continued
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L^, AND I
MINIMUM CONCENTRATED LIVE LOADS^
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
1 . Apartments (see residential)
2. Access floor systems
Office use
Computer use
50
100
2,000
2,000
3. Armories and drill rooms
150
—
4. Assembly areas and theaters
Fixed seats (fastened to floor)
Follow spot, projections and control
rooms
Lobbies
Movable seats
Stages and platforms
Other assembly areas
60
50
100
100
125
100
—
5. Balconies (exterior) and decks'^
Same as
occupancy
served
—
6. Bowling alleys
75
—
7. Catwalks
40
300
8. Cornices
60
—
9. Corridors, except as otherwise indicated
100
—
10. Dance halls and ballrooms
100
—
1 1 . Dining rooms and restaurants
100
—
12. Dwellings (see residential)
—
—
13. Elevator machine room grating
(on area of 4 in^)
—
300
14. Finish light floor plate construction
(on area of 1 in-^)
~
200
15. Fire escapes
On single-family dwellings only
100
40
—
16. Garages (passenger vehicles only)
Trucks and buses
40 ' Note a
See Section 1607.6
17. Grandstands
(see stadium and arena bleachers)
—
18. Gymnasiums, main floors and balconies
100
19. Handrails, guards and grab bars
See Section 1607.7
20. Hospitals
Corridors above first floor
Operating rooms, laboratories
Patient rooms
80
60
40
21. Hotels (see residential)
—
22. Libraries
Corridors above first floor
Reading rooms
Stack rooms
80
60
ISO''
23. Manufacturing
Heavy
Light
250
125
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
24. Marquees
75
25. Office buildings-
Corridors above first floor
File and computer rooms shall be
designed for heavier loads based
on anticipated occupancy
Lobbies and first-floor corridors
Offices
80
100
50
2,000
2,000
2,000
26. Penal institutions
Cell blocks
Corridors
40
100
—
27. Residential
One- and two-family dwellings
Uninhabitable attics without storage'
Uninhabitable attics with limited
storage'' J'*^
Habitable attics and sleeping areas
All other areas
Hotels and multifamily dwellings
Private rooms and corridors
serving them
Public rooms and corridors serving
them
10
20
30
40
40
100
—
28. Reviewing stands, grandstands and
bleachers
Notec
29. Roofs
All roof surfaces subject to maintenance
workers
Awnings and canopies
Fabric construction supported by a
lightweight rigid skeleton structure
All other construction
Ordinary flat, pitched, and curved roofs
Primary roof members, exposed to a
work floor
Single panel point of lower chord of
roof trusses or any point along
primary structural members
supporting roofs:
Over manufacturing, storage ware-
houses, and repair garages
All other occupancies
Roofs used for other special purposes
Roofs used for promenade purposes
Roofs used for roof gardens or
assembly purposes
5
nonreducible
20
20
Notel
60
100
30. Schools •
Classrooms
Corridors above first floor
First-floor corridors
40
80
100
31. Scuttles, skylight ribs and accessible
ceilings
—
32. Sidewalks, vehicular driveways and
yards, subject to trucking
250^
33. Skating rinks
100
34. Stadiums and arenas
Bleachers
Fixed seats (fastened to floor)
100^
60^
continued
continued
12
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 1607.1— continued
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L^
MINIMUM CONCENTRATED LIVE LOADS^
AND
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
35. Stairs and exits
One- and two-family dwellings
All other
40
100
Notef
36. Storage warehouses
(shall be designed for heavier loads if
required for anticipated storage)
Heavy
Light
250
125
37. Stores
Retail
First floor
Upper floors
Wholesale, all floors
100
75
125
1,000
1,000
1,000
38. Vehicle barrier systems
See Section 1607.7.3
39. Walkways and elevated platforms
(other than exitways)
60
—
40. Yards and terraces, pedestrians
100
—
41. [OSHPD 2] Storage racks andwall-hung
cabinets
Total
loads^
—
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mnf ,
1 square foot = 0.0929 m\
1 pound per square foot = 0.0479 kN/m', 1 pound = 0.004448 kN,
1 pound per cubic foot - 16 kgAn^
a. Floors in garages or portions of buildings used for the storage of motor vehicles shall be
designed for the uniformly distributed live loads of Table 1607.1 or the following con-
centrated loads: (1) for garages restricted to passenger vehicles accommodating not
more than nine passengers, 3,000 pounds acting on an area of 4.5 inches by 4.5 inches;
(2) for mechanical parking structures without slab or deck which are used for storing
passenger vehicles only, 2,250 pounds per wheel.
b. The loading applies to stack room floors that support nonmobile, double-faced library
bookstacks, subject to the following limitations:
1 . The nominal bookstack unit height shall not exceed 90 inches;
2. The nominal shelf depth shall not exceed 12 inches for each face; and
3. Parallel rows of double-faced bookstacks shall be separated by aisles not less
than 36 inches wide.
c. Design in accordance with ICC 300.
d. Other uniform loads in accordance with an approved method which contains provisions
for truck loadings shall also be considered where appropriate.
e. The concentrated wheel load shall be applied on an area of 4.5 inches by 4.5 inches.
f . Minimum concentrated load on stair treads (on area of 4 square inches) is 300 pounds.
g. Where snow loads occur that are in excess of the design conditions, the structure shall
be designed to support the loads due to the increased loads caused by drift buildup or a
greater snow design determined by the building official (see Section 1608). For spe-
cial-purpose roofs, see Section 1607.11.2.2.
h. See Section 1604.8.3 for decks attached to exterior walls.
i. Attics without storage are those where the maximum clear height between the joist and
rafter is less than 42 inches, or where there are not two or more adjacent trusses with the
same web configuration capable of containing a rectangle 42 inches high by 2 feet
wide, or greater, located within the plane of the truss. For attics without storage, this live
load need not be assumed to act concurrently with any other live load requirements,
j. For attics with limited storage and constructed with trusses, this live load need only be
applied to those portions of the bottom chord where there are two or more adjacent
trusses with the same web configuration capable of containing a rectangle 42 inches
high by 2 feet wide or greater, located within the plane of the truss. The rectangle shall
fit between the top of the bottom chord and the bottom of any other truss member, pro-
vided that each of the following criteria is met:
i. The attic area is accessible by a pull-down stairway or framed opening in accor-
dance with Section 1209.2, and
ii. The truss shall have a bottom chord pitch less than 2: 12,
iii. Bottom chords of trusses shall be designed for the greater of actual imposed dead
load or 10 psf, uniformly distributed over the entire span,
k. Attic spaces served by a fixed stair shall be designed to support the minimum live load
specified for habitable attics and sleeping rooms.
1, Roofs used for other special purposes shall be designed for appropriate loads as
approved by the building official.
m. [OSHPD 2] The minimum vertical design live load shall be as follows:
Paper media:
12-inch-deep (305 mm) shelf 33 pounds per lineal foot (482 N/m)
15-inch-deep (381 mm) shelf 41 pounds per lineal foot (598 N/m), or
33 pounds per cubic foot (5183 NM) per total volume of the rack or cabinet,
whichever is less.
Film media:
18- inch-deep (457 mm) shelf 100 pounds per lineal foot (1459 N/m), or
50 pounds per cubic foot (7853 N/m^) per total volume of the rack or cabinet, which-
ever is less.
Other media:
20 pounds per cubic foot (311 N/n^) or 20 pounds per square foot (958 Pa),
whichever is less, but not less than actual loads.
1607.2. Loads not specified. For occupancies or uses not des-
ignated in Table 1607.1, the live load shall be determined in
accordance with a method approved by the building official.
1607.3 Uniform live loads. The live loads used in the design of
buildings and other structures shall be the maximum loads
expected by the intended use or occupancy but shall in no case
be less than the minimum uniformly distributed unit loads
required by Table 1607.1.
1607.4 Concentrated loads. Floors and other similar surfaces
shall be designed to. support the uniformly distributed live
loads prescribed in Section 1607.3 or the concentrated load, in
pounds (kilonewtons), given in Table 1607.1, whichever pro-
duces the greater load effects. Unless otherwise specified, the
indicated concentration shall be assumed to be uniformly dis-
tributed over an area 2V2 feet by 2V2 feet [6V4 square feet (0.58
m^)] and shall be located so as to produce the maximum load
effects in the structural members.
1607.5 Partition loads. In office buildings and in other build-
ings where partition locations are subject to change, provisions
for partition weight shall be made, whether or not partitions are
shown on the construction documents, unless the specified live
load exceeds 80 psf (3.83 kN/m^). The partition load shall not be
less than a uniformly distributed live load of 15 psf (0.74 kN/m^).
1607.6 Truck and bus garages. Minimum live loads for
garages having trucks or buses shall be as specified in Table
1607.6, but shall not be less than 50 psf (2.40 kN/m^), unless
other loads are specifically justified and approvedhy the build-
ing official. Actual loads shall be used where they are greater
than the loads specified in the table.
1607.6.1 Truck and bus garage live load application. The
concentrated load and uniform load shall be uniformly dis-
tributed over a 10-foot (3048 mm) width on a line normal to
the centerline of the lane placed within a 12-foot- wide
(3658 mm) lane. The loads shall be placed within their indi-
vidual lanes so as to produce the maximum stress in each
structural member. Single spans shall be designed for the
uniform load in Table 1607.6 and one simultaneous concen-
trated load positioned to produce the maximum effect. Mul-
tiple spans shall be designed for the uniform load in Table
1607.6 on the spans and two simultaneous concentrated
loads in two spans positioned to produce the maximum neg-
ative moment effect. Multiple span design loads, for other
effects, shall be the same as for single spans.
2010 CALIFORNIA BUILDING CODE
13
STRUCTURAL DESIGN
TABLE 1607.6
UNIFORM AND CONCENTRATED LOADS
LOADING
CLASS^
UNIFORM LOAD
(pounds/linear
foot of lane)
CONCENTRATED LOAD
(pounds)^
For moment
design
For shear
design
H20-44 and HS20-44
640
18,000
26,000
H15-44andHS15-44
480
13,500
19,500
For SI: 1 pound per linear foot = 0.01459 kN/m, 1 pound = 0.004448 kN,
1 ton = 8.90 kN.
a. An H loading class designates a two-axle truck with a semitrailer. An HS
loading class designates a tractor truck with a semitrailer. The numbers fol-
lowing the letter classification indicate the gross weight in tons of the stan-
dard truck and the year the loadings were instituted.
b. See Section 1607.6.1 for the loading of multiple spans.
1607.7 Loads on handrails, guards, grab bars, shower seats,
dressing room bench seats and vehicle barrier systems.
Handrails, guards, grab bars, accessible seats, accessible
benches and vehicle barrier systems shall be designed and con-
structed to the structural loading conditions set forth in this sec-
tion.
1607.7.1 Handrails and guards. Handrails and guards
shall be designed to resist a load of 50 pounds per linear foot
(plf) (0.73 kN/m) applied in any direction at the top and to
transfer this load through the supports to the structure. Glass
handrail assemblies and guards shall also comply with Sec-
tion 2407.
Exceptions:
1 . For one- and two-family dwellings, only the single
concentrated load required by Section 1607.7.1.1
shall be apphed.
2. In Group 1-3, F, H and S occupancies, for areas that
are not accessible to the general public and that
have an occupant load less than 50, the minimum
load shall be 20 pounds per foot (0.29 kN/m).
1607.7.1.1 Concentrated load. Handrails and guards
shall be able to resist a single concentrated load of 200
pounds (0.89 kN), applied in any direction at any point
along the top, and to transfer this load through the sup-
ports to the structure. This load need not be assumed to
act concurrently with the loads specified in Section
1607.7.1.
1607.7.1.2 Components. Intermediate rails (all those
except the handrail), balusters and panel fillers shall be
designed to withstand a horizontally applied normal load
of 50 pounds (0.22 kN) on an area equal to 1 square foot
(0.093 m^), including openings and space between rails.
Reactions due to this loading are not required to be super-
imposed with tiiose of Section 1607.7.1 or 1607.7.1.1.
1607.7.2 Grab bars, shower seats and dressing room
bench seats. Grab bars, shower seats and dressing room
bench seat systems shall be designed to resist a single con-
centrated load of 250 pounds (1.11 kN) apphed in any direc-
tion at any point. [DSA-AC & HCD l-AC] See Chapter 1 lA,
Section 1127A.4, and Chapter IIB, Sections 115B.7.2 and
I117B.8, for grab bars, shower seats and dressing room
bench seats, as applicable.
1607.7.3 Vehicle barrier systems. Vehicle barrier systems
for passenger vehicles shall be designed to resist a single
load of 6,000 pounds (26.70 kN) apphed horizontally in any
direction to the barrier system and shall have anchorage or
attachment capable of transmitting this load to the structure.
For design of the system, two loading conditions shall be
analyzed. The first condition shall apply the load at a height
of 1 foot, 6 inches (457 mm) above the floor or ramp surface.
The second loading condition shall apply the load at 2 feet, 3
inches (686 mm) above the floor or ramp surface. The more
severe load condition shall govern the design of the barrier
restraint system. The load shall be assumed to act on an area
not to exceed 1 square foot (0.0929 m^), and is not required
to be assumed to act concurrently with any handrail or guard
loadings specified in Section 1607.7.1. Garages accommo-
dating trucks and buses shall be designed in accordance
with an approved method that contains provisions for traffic
railings.
1607.8 Impact loads. The hve loads specified in Section
1607.3 include allowance for impact conditions. Provisions
shall be made in the structural design for uses and loads that
involve unusual vibration and impact forces.
1607.8.1 Elevators. Elevator loads shall be increased by
100 percent for impact and the structural supports shall be
designed within the limits of deflection prescribed by
ASMEA17.1.
1607.8.2 Machinery. For the purpose of design, the weight
of machinery and moving loads shall be increased as fol-
lows to allow for impact: (1) elevator machinery, 100 per-
cent; (2) light machinery, shaft- or motor-driven, 20 percent;
(3) reciprocating machinery or power-driven units, 50 per-
cent; (4) hangers for floors or balconies, 33 percent. Per-
centages shall be increased where specified by the
manufacturer.
1607.9 Reduction in live loads. Except for uniform live loads
at roofs, all other minimum uniformly distributed live loads,
L^, in Table 1607. 1 are permitted to be reduced in accordance
with Section 1607.9.1 or 1607.9.2. Roof uniform live loads,
other than special purpose roofs of Section 1607.11.2.2, are
permitted to be reduced in accordance with Section
1607.1 1.2. Roof uniform live loads of special purpose roofs
are permitted to be reduced in accordance with Section
1607.9.1 or 1607.9.2.
1607.9.1 General. Subject to the limitations of Sections
1607.9.1.1 through 1607.9.1.4, members for which a value
of ^^Ay-is 400 square feet (37. 16 m^) or more are permitted
to be designed for a reduced live load in accordance with the
following equation:
r \
15
L^L
0.25 +
V^^
(Equation 16-22)
T )
(
For SI: L ^ L^
where:
0.25 +
4.57
L = Reduced design live load per square foot (meter) of
area supported by the member.
14
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
L^ = Unreduced design live load per square foot (meter) of
area supported by the member (see Table 1607.1).
Ki^i^ Live load element factor (see Table 1607.9.1).
Aj = Tributary area, in square feet (square meters).
L shall not be less than O.SOL^ for members supporting one
floor and L shall not be less than 0.40L^ for members sup-
porting two or more floors.
TABLE 1607.9.1
LIVE LOAD ELEMENT FACTOR, K^l
ELEMENT
Kll
Interior columns
Exterior columns without cantilever slabs
4
4
Edge columns with cantilever slabs
3
Comer columns with cantilever slabs
Edge beams without cantilever slabs
Interior beams
2
2
2
All other members not identified above including:
Edge beams with cantilever slabs
Cantilever beams
One-way slabs
Two-way slabs
Members without provisions for continuous shear
transfer normal to their span
1
1607.9.1.1 One-way slabs. The tributary area, A-p, for
use in Equation 16-22 for one-way slabs shall not exceed
an area defined by the slab span times a width normal to
the span of 1.5 times the slab sp£in.
1607.9.1.2 Heavy live loads. Live loads that exceed 100
psf (4.79 kN/m^) shall not be reduced.
Exceptions:
1. The live loads for members supporting two or
more floors are permitted to be reduced by a
maximum of 20 percent, but the live load shall
not be less than L as calculated in Section
1607.9.1.
2. For uses other than storage, where approved,
additional live load reductions shall be permit-
ted where shown by the registered design pro-
fessional that a rational approach has been used
and that such reductions are warranted.
1607.9.1.3 Passenger vehicle garages. The live loads
shall not be reduced in passenger vehicle garages.
Exception: The live loads for members supporting
two or more floors are permitted to be reduced by a
maximum of 20 percent, but the live load shall not be
less than L as calculated in Section 1607.9.1.
1607.9.1.4 Group A occupancies. Live loads of 100 psf
(4.79 kN/m^) and at areas where fixed seats are located
shall not be reduced in Group A occupancies.
1607.9.1.5 Roof members. Live loads of 100 psf (4.79
kN/m^) or less shall not be reduced for roof members
except as specified in Section 1607.11.2.
1607.9.2 Alternate floor live load reduction. As an alter-
native to Section 1607.9.1, floor live loads are permitted to
be reduced in accordance with the following provisions.
Such reductions shall apply to slab systems, beams, girders,
colunms, piers, walls and foundations.
1. A reduction shall not be permitted in Group A occu-
pancies.
2. A reduction shall not be permitted where the live load
exceeds 100 psf (4.79 kN/m^) except that the design
live load for members supporting two or more floors
is permitted to be reduced by 20 percent.
Exception: For uses other than storage, where
approved, additional live load reductions shall be
permitted where shown by the registered design
professional that a rational approach has been used
and that such reductions are warranted.
3. A reduction shall not be permitted in passenger vehi-
cle parking garages except that the live loads for
members supporting two or more floors are permitted
to be reduced by a maximum of 20 percent.
4. For live loads not exceeding 1 00 psf (4.79 kN/m^), the
design hve load for any structural member supporting
150 square feet (13.94 m^) or more is permitted to be
reduced in accordance with Equation 16-23.
5. For one-way slabs, the area. A, for use in Equation
16-23 shall not exceed the product of the slab span
and a width normal to the span of 0.5 times the slab
span.
/? = 0.08(A-150)
(Equation 16-23)
For SI: /? = 0.861(A- 13.94)
Such reduction shall not exceed the smallest of:
1. 40 percent for horizontal members;
2. 60 percent for vertical members; or
3. R as determined by the following equation.
/? = 23. 1(1 +D/4) (Equation 16-24)
where:
A
D
Lo
R
= Area of floor supported by the member,
square feet (m^).
= Dead load per square foot (m^) of area sup-
ported.
= Unreduced live load per square foot (m^) of
area supported.
= Reduction in percent.
1607.10 Distribution of floor loads. Where uniform floor
live loads are involved in the design of structural members
arranged so as to create continuity, the minimum applied
loads shall be the full dead loads on all spans in combination
with the floor live loads on spans selected to produce the
greatest effect at each location under consideration. It shall be
permitted to reduce floor live loads in accordance with Sec-
tion 1607.9.
2010 CALIFORNIA BUILDING CODE
15
STRUCTURAL DESIGN
1607.11 Roof loads. The structural supports of roofs and mar-
quees shall be designed to resist wind and, where applicable,
snow and earthquake loads, in addition to the dead load of con-
struction and the appropriate live loads as prescribed in this
section, or as set forth in Table 1607. 1 . The live loads acting on
a sloping surface shall be assumed to act vertically on the hori-
zontal projection of that surface.
1607.11.1 Distribution of roof loads. Where uniform roof
live loads are reduced to less than 20 psf (0.96 kN/m^) in
accordance with Section 1607.1 1.2.1 and are applied to the
design of structural members arranged so as to create conti-
nuity, the reduced roof live load shall be applied to adjacent
spans or to alternate spans, whichever produces the most
unfavorable load effect. See Section 1607.11.2 for reduc-
tions in minimum roof live loads and Section 7.5 of ASCE 7
for partial snow loading.
1607.11.2 Reduction in roof live loads. The minimum uni-
formly distributed live loads of roofs and marquees, L^, in
Table 1 607. 1 are permitted to be reduced in accordance with
Section 1607.11.2.1 or 1607.11.2.2.
1607.11.2.1 Flat, pitched and curved roofs. Ordinary
flat, pitched and curved roofs, and awnings and canopies
other than of fabric construction supported by light-
weight rigid skeleton structures, are permitted to be
designed for a reduced roof live load as specified in the
following equations or other controlling combinations of
loads in Section 1605, whichever produces the greater
load. In structures such as greenhouses, where special
scaffolding is used as a work surface for workers and
materials during maintenance and repair operations, a
lower roof load than specified in the following equations
shall not be used unless approved by the building official.
Such structures shall be designed for a minimum roof
live load of 12 psf (0.58 kN/m^).
(Equation 16-25)
L, = L^RjR2
where: 12<L,<20
For SI: L, = L^;i?2
where: 0.58 <4< 0.96
L, = Reduced live load per square foot (m2) of horizon-
tal projection in pounds per square foot (kN/mj).
The reduction factors Rj and R2 shall be determined as
follows:
Rj = 1 for A, < 200 square feet
(18.58 m^)
(Equation 16-26)
Rj^ 1.2- O.OOIA, for 200 square
feet <Ai< 600 square feet (Equation 16-27)
For SI: 1.2-0,011A, for 18.58 square meters<A,<55.74
square meters
Rj = 0.6 for At > 600 square feet
(55.74 m2) (Equation 16-28)
where:
Af = Tributary area (span length multiplied by effective
width) in square feet (m^) supported by any struc-
tural member, and
7?2 ^ 1 f or F < 4 (Equation 16-29)
/?2= 1.2-0.05Ffor4<F< 12 (Equation 16-30)
R2 = 0,6forF> 12 (Equation 16-31)
where:
F = For a sloped roof, the number of inches of rise per
foot (for SI: F = 0. 1 2 X slope, with slope expressed
as a percentage), or for an arch or dome, the
rise-to-span ratio multiplied by 32.
1607.11.2.2 Special-purpose roofs. Roofs used for
promenade purposes, roof gardens, assembly purposes
or other special purposes, and marquees, shall be
designed for a minimum live load, L^, as specified in
Table 1607. 1 . Such live loads are permitted to be reduced
in accordance with Section 1607.9. Live loads of 100 psf
(4.79 kN/m^) or more at areas of roofs classified as
Group A occupancies shall not be reduced.
1607.11.3 Landscaped roofs. Where roofs are to be land-
scaped, the uniform design live load in the landscaped area
shall be 20 psf (0.958 kN/m^). The weight of the landscap-
ing materials shall be considered as dead load and shall be
computed on the basis of saturation of the soil.
1607.11.4 Awnings and canopies. Awnings and canopies
shall be designed for uniform live loads as required in Table
1607. 1 as well as for snow loads and wind loads as specified
in Sections 1608 and 1609.
1607.12 Crane loads. The crane live load shall be the rated
capacity of the crane. Design loads for the runway beams,
including connections and support brackets, of moving bridge
cranes and monorail cranes shall include the maximum wheel
loads of the crane and the vertical impact, lateral and longitudi-
nal forces induced by the moving crane.
1607.12.1 Maximum wheel load. The maximum wheel
loads shall be the wheel loads produced by the weight of the
bridge, as applicable, plus the sum of the rated capacity and
the weight of the trolley with the trolley positioned on its
runway at the location where the resulting load effect is
maximum.
1607.12.2 Vertical impact force. The maximum wheel
loads of the crane shall be increased by the percentages
shown below to determine the induced vertical impact or
vibration force:
Monorail cranes (powered) 25 percent
Cab-operated or remotely operated
bridge cranes (powered) 25 percent
Pendant-operated bridge cranes
(powered) lOpercent
Bridge cranes or monorail cranes with
hand-geared bridge, trolley and hoist percent
1607.12.3 Lateral force. The lateral force on crane runway
beams with electrically powered trolleys shall be calculated
16
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
as 20 percent of the sum of the rated capacity of the crane
and the weight of the hoist and trolley. The lateral force shall
be assumed to act horizontally at the traction surface of a
runway beam, in either direction perpendicular to the beam,
and shall be distributed according to the lateral stiffness of
the runway beam and supporting structure.
1607.12.4 Longitudinal force. The longitudinal force on
crane runway beams, except for bridge cranes with
hand-geared bridges, shall be calculated as 10 percent of the
maximum wheel loads of the crane. The longitudinal force
shall be assumed to act horizontally at the traction surface of
a runway beam, in either direction parallel to the beam.
1607.13 Interior walls and partitions. Interior walls and par-
titions that exceed 6 feet (1829 mm) in height, including their
finish materials, shall have adequate strength to resist the loads
to which they are subjected but not less than a horizontal load of
5 psf (0.240 kN/m^).
Exception: Fabric partitions complying with Section
1607.13.1 shall not be required to resist the minimum hori-
zontal load of 5 psf (0.24 kN/m^).
1607.13.1 Fabric partitions. Fabric partitions that exceed 6
feet (1829 mm) in height, including their finish materials,
shall have adequate strength to resist the following load con-
ditions:
1. A horizontal distributed load of 5 psf (0.24 kN/m^)
applied to the partition framing. The total area used to
determine the distributed load shall be the area of the
fabric face between the framing members to which
the fabric is attached. The total distributed load shall
be uniformly applied to such framing members in
proportion to the length of each member.
2. A concentrated load of 40 pounds (0. 176 kN) appUed
to an 8-inch diameter (203 mm) area [50.3 square
inches (32 452 mm^)] of the fabric face at a height of
54 inches (1372 mm) above the floor.
SECTION 1608
SNOW LOADS
1608.1 General. Design snow loads shall be determined in
accordance with Chapter 7 of ASCE 7, but the design roof load
shall not be less than that determined by Section 1607.
1608.2 Ground snow loads. The ground snow loads to be used
in determining the design snow loads for roofs shall be deter-
mined in accordance with ASCE 7 or Figure 1608.2 for the
contiguous United States and Table 1608.2 for Alaska.
Site-specific case studies shall be made in areas designated
"CS" in Figure 1608.2. Ground snow loads for sites at eleva-
tions above the limits indicated in Figure 1608.2 and for all
sites within the CS areas shall be approved. Ground snow load
determination for such sites shall be based on an extreme value
statistical analysis of data available in the vicinity of the site
using a value with a 2-percent annual probability of being
exceeded (50-year mean recurrence interval). Snow loads are
zero for Hawaii, except in mountainous regions as approvedby
the building official.
TABLE 1608.2
GROUND SNOW LOADS, p^ , FOR ALASKAN LOCATIONS
LOCATION
POUNDS PER
SQUARE FOOT
LOCATION
POUNDS PER
SQUARE FOOT
LOCATION
POUNDS PER
SQUARE FOOT
Adak
30
Galena
60
Petersburg
150
Anchorage
50
Gulkana
70
St. Paul Islands
40
Angoon
70
Homer
40
Seward
50
Barrow
25
Juneau
60
Shemya
25
Barter Island
35
Kenai
70
Sitka
50
Bethel
40
Kodiak
30
Talkeetna
120
Big Delta
50
Kotzebue
60
Unalakleet
50
Cold Bay
25
McGrath
70
Valdez
160
Cordova
100
Nenana
80
Whittier
300
Fairbanks
60
Nome
70
Wrangell
60
Fort Yukon
60
Palmer
50
Yakutat
150
For SI: 1 pound per square foot = 0.0479 kN/ml
2010 CALIFORNIA BUILDING CODE
17
STRUCTURAL DESIGN
In CS areas, site-specific Case Studies are required to
establish ground snow loads. Extreme local variations in
ground snow loads in these areas preclude mapping at
this scale.
Numbers in parentheses represent the upper elevation
limits in feet for the ground snow load values presented
below. Site -specific case studies are required to estab-
lish ground snow loads at elevations not covered.
To convert Ib/sq ft to kNm", multiply by 0.0479.
To convert feet to meters, multiply by 0.3048.
J
100
200
300 miles
FIGURE 1608.2
GROUND SNOW LOADS, Pg, FOR THE UNITED STATES (psf)
18
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
(500)
Wo'
(900)
FIGURE 1608.2"Continued
GROUND SNOW LOADS, Pg, FOR THE UNITED STATES (psf)
2010 CALIFORNIA BUILDING CODE
19
STRUCTURAL DESIGN
>
SECTION 1609
WIND LOADS
1609.1 Applications. Buildings, structures and parts thereof
shall be designed to withstand the minimum wind loads pre-
scribed herein. Decreases in wind loads shall not be made for
the effect of shielding by other structures.
1609,1.1 Determination of wind loads. Wind loads on
every building or structure shall be determined in accor-
dance with Chapter 6 of ASCE 7 or provisions of the alter-
nate all-heights method in Section 1609.6. The type of
opening protection required, the basic wind speed and the
exposure category for a site is permitted to be determined in
accordance with Section 1609 or ASCE 7. Wind shall be
assumed to come from any horizontal direction and wind
pressures shall be assumed to act normal to the surface con-
sidered.
Exceptions:
1. Subject to the limitations of Section 1609.1.1.1,
the provisions of ICC 600 shall be permitted for
applicable Group R-2 and R-3 buildings.
2. Subject to the limitations of Section 1609.1.1.1,
residential structures using the provisions of the
AF&PA WFCM.
3. Subject to the limitations of Section 1609.1.1.1,
residential structures using the provisions of AISI
S230.
4. Designs using NAAMM FP 1001.
5. Designs using TIA-222 for antenna-supporting
structures and antennas.
6. Wind tunnel tests in accordance with Section 6.6
of ASCE 7, subject to the limitations in Section
1609.1.1.2.
1609.1.1.1 Applicability. The provisions of ICC 600 are
applicable only to buildings located within Exposure B
or C as defined in Section 1609.4. The provisions of ICC
600, AF&PA WFCM and AISI S230 shall not apply to
buildings sited on the upper half of an isolated hill, ridge
or escarpment meeting the following conditions:
1. The hill, ridge or escarpment is 60 feet (18 288
nmi) or higher if located in Exposure B or 30 feet
(9144 mm) or higher if located in Exposure C;
2. The maximum average slope of the hill exceeds 10
percent; and
3. The hill, ridge or escarpment is unobstructed
upwind by other such topographic features for a dis-
tance from the high point of 50 times the height of
the hill or 1 mile (1.61 km), whichever is greater.
1609.1.1.2 Wind tunnel test limitations. The lower
limit on pressures for main wind-force-resisting systems
and components and cladding shall be in accordance
with Sections 1609.1.1.2.1 and 1609.1.1.2.2.
1609.1.1.2.1 Lower limits on main wind- force-
resisting system. Base overturning moments deter-
mined from wind tunnel testing shall be limited to not
less than 80 percent of the design base overturning
moments determined in accordance with Section 6.5 of
ASCE 7, unless specific testing is performed that dem-
onstrates it is the aerodynamic coefficient of the build-
ing, rather than shielding from other structures, that is
responsible for the lower values. The 80-percent limit
shall be permitted to be adjusted by the ratio of the
frame load at critical wind directions as determined
from wind tunnel testing without specific adjacent
buildings, but including appropriate upwind rough-
ness, to that determined in Section 6.5 of ASCE 7.
1609.1.1.2.2 Lower limits on components and clad-
ding. The design pressures for components and clad-
ding on walls or roofs shall be selected as the greater
of the wind tunnel test results or 80 percent of the
pressure obtained for Zone 4 for walls and Zone 1 for
roofs as determined in Section 6.5 of ASCE 7, unless
specific testing is performed that demonstrates it is
the aerodynamic coefficient of the building, rather
than shielding from nearby structures, that is respon-
sible for the lower values. Alternatively, limited tests
at a few wind directions without specific adjacent
buildings, but in the presence of an appropriate
upwind roughness, shall be permitted to be used to
demonstrate that the lower pressures are due to the
shape of the building and not to shielding.
1609.1.2 Protection of openings. In wind-borne debris
regions, glazing in buildings shall be impact resistant or pro-
tected with an impact-resistant covering meeting the require-
ments of an approved impact-resistant standard or ASTM E
1996 and ASTM E 1886 referenced herein as follows:
1 . Glazed openings located within 30 feet (9 144 mm) of
grade shall meet the requirements of the large missile
test of ASTM El 996.
2. Glazed openings located more than 30 feet (9144
mm) above grade shall meet the provisions of the
small missile test of ASTM E 1996.
Exceptions:
1 . Wood structural panels with a minimum thickness
of ^/i5 inch (11.1 mm) and maximum panel span of
8 feet (2438 mm) shall be permitted for opening
protection in one- and two-story buildings classi-
fied as Group R-3 or R-4 occupancy. Panels shall
be precut so that they shall be attached to the fram-
ing surrounding the opening containing the prod-
uct with the glazed opening. Panels shall be
predrilled as required for the anchorage method
and shall be secured with the attachment hardware
provided. Attachments shall be designed to resist
the components and cladding loads determined in
accordance with the provisions of ASCE 7, with
corrosion-resistant attachment hardware provided
and anchors permanently installed on the building.
Attachment in accordance with Table 1609.1.2
with corrosion-resistant attachment hardware pro-
vided and anchors permanently installed on the
building is permitted for buildings with a mean
roof height of 45 feet (13 716 mm) or less where
wind speeds do not exceed 140 mph (63 m/s).
20
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
2. Glazing in Occupancy Category I buildings as
defined in Section 1604.5, including greenhouses
that are occupied for growing plants on a produc-
tion or research basis, without public access shall
be permitted to be unprotected.
3. Glazing in Occupancy Category n, III or IV build-
ings located over 60 feet (18 288 mm) above the
ground and over 30 feet (9144 mm) above aggre-
gate surface roofs located within 1 ,500 feet (458 m)
of the building shall be permitted to be unprotected.
1609.1.2.1 Louvers. Louvers protecting intake and
exhaust ventilation ducts not assumed to be open that are
located within 30 feet (9144 mm) of grade shall meet
requirements of an approved impact-resisting standard
or the large missile test of ASTM E 1996.
1609.1.2.2 Garage doors. Garage door glazed opening
protection for wind-borne debris shall meet the require-
ments of an approved impact-resisting standard or
ANSI/DASMA115.
1609.2 Definitions. The following words and terms shall, for
the purposes of Section 1 609, have the meanings shown herein.
TABLE 1609.1.2
WIND-BORNE DEBRIS PROTECTION FASTENING
SCHEDULE FOR WOOD STRUCTURAL PANELS^- *»' «^' ^
FASTENER
TYPE
FASTENER SPACING (inches)
Panel
Span
<4feet
4feet<
Panel Span
< 6 feet
6feet<
Panel Span
<8feet
No. 8 wood-screw-based anchor
with 2-inch embedment length
16
10
8
No. 10 wood- screw-based
anchor with 2-inch embedment
length
16
12
9
V4-inch diameter lag-screw-
based anchor with 2-inch
embedment length
16
16
16
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N,
1 mile per hour = 0.447 m/s.
a. This table is based on 1 40 mph wind speeds and a 45-foot mean roof height.
b. Fasteners shall be installed at opposing ends of the wood structural panel.
Fasteners shall be located a minimum of 1 inch from the edge of the panel.
c. Anchors shall penetrate through the exterior wall covering with an
embedment length of 2 inches minimum into the building frame. Fasteners
shall be located a minimum of 2 V2 inches from the edge of concrete block or
concrete.
d. Where panels are attached to masonry or masonry/stucco, they shall be
attached using vibration-resistant anchors having a minimum ultimate with-
drawal capacity of 1,500 pounds.
HURRICANE-PRONE REGIONS. Areas vulnerable to
hurricanes defined as:
1. The U. S. Atlantic Ocean and Gulf of Mexico coasts
where the basic wind speed is greater than 90 mph (40
m/s) and
2. Hawaii, Puerto Rico, Guam, Virgin Islands and Ameri-
can Samoa.
WIND-BORNE DEBRIS REGION. Portions of hurri-
cane-prone regions that are within 1 mile (1.61 km) of the
coastal mean high water line where the basic wind speed is 1 10
mph (48 m/s) or greater; or portions of hurricane -prone
regions where the basic wind speed is 120 mph (53 m/s) or
greater; or Hawaii.
1609.3 Basic wind speed. The basic wind speed, in mph, for
the determination of the wind loads shall be determined by Fig-
ure 1609. Basic wind speed for the special wind regions indi-
cated, near mountainous terrain and near gorges shall be in
accordance with local jurisdiction requirements. Basic wind
speeds determined by the local jurisdiction shall be in accor-
dance with Section 6.5.4 of ASCE 7.
In nonhurricane-prone regions, when the basic wind speed is
estimated from regional climatic data, the basic wind speed
shall be not less than the wind speed associated with an annual
probability of 0.02 (50-year mean recurrence interval), and the
estimate shall be adjusted for equivalence to a 3 -second gust
wind speed at 33 feet (10 m) above ground in Exposure Cate-
gory C. The data analysis shall be performed in accordance
with Section 6.5.4.2 of ASCE 7.
1609.3.1 Wind speed conversion. When required, the
3-second gust basic wind speeds of Figure 1609 shall be
converted to fastest-mile wind speeds, V^, using Table
1609.3.1 or Equation 16-32.
Vfin =
(V35-IO.5)
1.05
(Equation 16-32)
where:
V^s = 3-second gust basic wind speed from Figure 1609.
1609.4 Exposure category. For each wind direction consid-
ered, an exposure category that adequately reflects the charac-
teristics of ground surface irregularities shall be determined for
the site at which the building or structure is to be constructed.
Account shall be taken of variations in ground surface rough-
ness that arise from natural topography and vegetation as well
as from constructed features.
TABLE 1609.3.1
EQUIVALENT BASIC WIND SPEEDS^'''
c
^35
85
90
100
105
110
120
125
130
140
145
150
160
170
Vm
71
76
85
90
95
104
109
114
123
128
133
142
152
For SI: 1 mile per hour = 0.44 m/s.
a. Linear interpolation is permitted.
b. Vjs is the 3-second gust wind speed (mph).
c. V^ is the fastest mile wind speed (mph).
2010 CALIFORNIA BUILDING CODE
21
STRUCTURAL DESIGN
-146 -"^^2
FIGURE 1609
BASIC WIND SPEED (3-SECOND GUST)
22
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
90(40)
100(45)
130(58)
140(63)
130(58)
140(63)
150(67)
90(40)
100(45)
130(58)
110(49) 120(54)
Location
HawaH
Puerto Rico
Guam
Virgin Islands
American Samoa
V mph (m/s)
105 (47)
145
170
145
125
(65)
(76)
(65)
(56)
Notes:
1. Values are nominal design 3-second gust wind speeds in miles per hour (m/s)
at 33 ft (10 m) above ground for Exposure C category.
2. Linear Interpolation between wind contours is permitted.
3. Islands and coastal areas outside the last contour shall use the last wind
speed contour of the coastal area.
4. Mountainous terrain, gorges, ocean promontories, and special wind regions
shall be examined for unusual wind conditions.
FIGURE 1609— continued
BASIC WIND SPEED (3-SECOND GUST)
2010 CALIFORNIA BUILDING CODE
23
STRUCTURAL DESIGN
Illlll Special Wind Region
100(45) / j 130(58)
110(49)120(54)
Notes:
1. Values are nominal design 3-second gust wind
speeds In mites per iiour (m/s) at 33 ft (10 m)
above ground for Exposure C category.
2. Linear Interpolation between wind contours is
permitted.
3. islands and coastal areas outside the last
contour shall use the last wind speed contour
of the coastal area.
4. l\/lountainous terrain, gorges, ocean
promontoriesi and special wind regions shall
be examined for unusual wind conditions.
FIGURE 1609-continued
BASIC WIND SPEED (3-SECOND GUST)
WESTERN GULF OF MEXICO HURRICANE COASTLINE
24
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
90(40)
100(4!^
110(49)
120(54)
130(58)
,130(58)
140(63)
Speciaf Wind Region
Notes:
1. Values are nominal design 3-second gust wind
speeds in miles per hour (m/s) at 33 ft (10 m)
above ground for Exposure C category.
2. Linear Interpolation between wind contours Is
permitted.
3. Islands and coastal areas outside the last
contour shall use the last wind speed contour
of the coastal area.
4. Mountainous terrain, gorges, ocean
promontories, and special wind regions shall
be examined for unusual wind conditions.
150(67)
FIGURE 1609-contlnued
BASIC WIND SPEED (3-SECOND GUST)
EASTERN GULF OF MEXICO AND SOUTHEASTERN U.S. HURRICANE COASTLINE
2010 CALIFORNIA BUILDING CODE
25
STRUCTURAL DESIGN
.S^120(S4)
Special Wind Region
Notes:
1. Vaiues are nominal design 3-second gust wind
speeds in miies per iiour (m/s) at 33 ft (10 m)
above ground for Exposure C category.
Linear interpolation between wind contours Is
permitted.
Islands and coastal areas outside the last
contour siiall use the last wind speed contour
of the coastal area.
4. Mountainous terrain, gorges, ocean
promontories, and special wind regions shall
be examined for unusual wind conditions.
FIGURE 1609-continued
BASIC WIND SPEED (3-SECOND GUST)
MID AND NORTHERN ATLANTIC HURRICANE COASTLINE
26
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1609.4.1 Wind directions and sectors. For each selected
wind direction at which the wind loads are to be evaluated,
the exposure of the building or structure shall be determined
for the two upwind sectors extending 45 degrees (0.79 rad)
either side of the selected wind direction. The exposures in
these two sectors shall be determined in accordance with
Sections 1609.4.2 and 1609,4.3 and the exposure resulting
in the highest wind loads shall be used to represent winds
from that direction.
1609.4.2 Surface roughness categories. A ground surface
roughness within each 45 -degree (0.79 rad) sector shall be
determined for a distance upwind of the site as defined in
Section 1609.4.3 from the categories defined below, for the
purpose of assigning an exposure category as defined in
Section 1609.4.3.
Surface Roughness B. Urban and suburban areas,
wooded areas or other terrain with numerous closely
spaced obstructions having the size of single-family
dwellings or larger.
Surface Roughness C. Open terrain with scattered
obstructions having heights generally less than 30 feet
(9144 mm). This category includes flat open country,
grasslands, and all water surfaces in hurricane -prone
regions.
Surface Roughness D. Flat, unobstructed areas and
water surfaces outside hurricane-prone regions. This
category includes smooth mud flats, salt flats and unbro-
ken ice.
1609.4.3 Exposure categories. An exposure category shall
be determined in accordance with the following:
Exposure B. Exposure B shall apply where the ground
surface roughness condition, as defined by Surface
Roughness B, prevails in the upwind direction for a dis-
tance of at least 2,600 feet (792 m) or 20 times the height
of the building, whichever is greater.
Exception: For buildings whose mean roof height is
less than or equal to 30 feet (9 144 mm), the upwind dis-
tance is permitted to be reduced to 1 ,500 feet (457 m).
Exposure C. Exposure C shall apply for all cases where
Exposures B or D do not apply.
Exposure D. Exposure D shall apply where the ground
surface roughness, as defined by Surface Roughness D,
prevails in the upwind direction for a distance of at least
5,000 feet (1524 m) or 20 times the height of the build-
ing, whichever is greater. Exposure D shall extend inland
from the shorehne for a distance of 600 feet ( 1 83 m) or 20
times the height of the building, whichever is greater.
1609.5 Roof systems.
1609.5.1 Roof deck. The roof deck shall be designed to
withstand the wind pressures determined in accordance
with ASCE 7.
1609.5.2 Roof coverings.
with Section 1609.5.1.
Roof coverings shall comply
tion 1609.5. 1 are permitted to be designed in accordance
with Section 1609.5.3,
Asphalt shingles installed over a roof deck complying
with Section 1609.5.1 shall comply with the wind-resis-
tance requirements of Section 1507.2.7.1.
1609.5.3 Rigid tile. Wind loads on rigid tile roof coverings
shall be determined in accordance with the following equa-
tion:
M, = ^,QZ?LLJ1.0-GC,]
(Equation 16-33)
For SI: M, =
q,C,bLL^[lO-GC^]
1,000
where:
b
Exception: Rigid tile roof coverings that are air perme-
able and installed over a roof deck complying with Sec-
Exposed width, feet (mm) of the roof tile.
Lift coefficient. The lift coefficient for concrete and
clay tile shall be 0.2 or shall be determined by test in
accordance with Section 1716.2.
GCp~ Roof pressure coefficient for each applicable roof
zone determined from Chapter 6 of ASCE 7. Roof
coefficients shall not be adjusted for internal pres-
sure.
L = Length, feet (mm) of the roof tile.
L^ = Moment arm, feet (mm) from the axis of rotation to
the point of uplift on the roof tile. The point of uplift
shall be taken at 0.76L from the head of the tile and
the middle of the exposed width. For roof tiles with
nails or screws (with or without a tail clip), the axis
of rotation shall be taken as the head of the tile for
direct deck application or as the top edge of the bat-
ten for battened applications. For roof tiles fastened
only by a nail or screw along the side of the tile, the
axis of rotation shall be determined by testing. For
roof tiles installed with battens and fastened only by
a clip near the tail of the tile, the moment arm shall
be determined about the top edge of the batten with
consideration given for the point of rotation of the
tiles based on straight bond or broken bond and the
tile profile.
M^ = Aerodynamic uplift moment, feet-pounds (N-mm)
acting to raise the tail of the tile.
q^ = Wind velocity pressure, psf (kN/m^) determined
from Section 6.5.10 of ASCE 7.
Concrete and clay roof tiles complying with the following
limitations shall be designed to withstand the aerodynamic
uplift moment as determined by this section.
1. The roof tiles shall be either loose laid on battens,
mechanically fastened, mortar set or adhesive set.
2. The roof tiles shall be installed on solid sheathing
which has been designed as components and clad-
ding,
3. An underlay ment shall be installed in accordance
with Chapter 15.
2010 CALIFORNIA BUILDING CODE
27
STRUCTURAL DESIGN
4. The tile shall be single lapped interlocking with a
minimum head lap of not less than 2 inches (5 1 mm).
5. The length of the tile shall be between 1.0 and 1.75
feet (305 mm and 533 mm).
6. The exposed width of the tile shall be between 0.67
and 1.25 feet (204 mm and 381 mm).
7 . The maximum thickness of the tail of the tile shall not
exceed 1.3 inches (33 mm).
8. Roof tiles using mortar set or adhesive set systems
shall have at least two-thirds of the tile' s area free of
mortar or adhesive contact.
1609.6 Alternate all-heights method. The alternate wind
design provisions in this section are simplifications of the
ASCE 7 Method 2— Analytical Procedure.
1609.6.1 Scope. As an alternative to ASCE 7 Section 6.5,
the following provisions are permitted to be used to deter-
mine the wind effects on regularly shaped buildings, or
other structures that are regularly shaped, which meet all of
the following conditions:
1 . The building or other structure is less than or equal to
75 feet (22 860 mm) in height with a height-to-least-
width ratio of 4 or less, or the building or other struc-
ture has a fundamental frequency greater than or
equal to 1 hertz.
2. The building or other structure is not sensitive to
dynamic effects.
3. The building or other structure is not located on a site
for which channeling effects or buffeting in the wake
of upwind obstructions warrant special consideration.
4. The building shall meet the requirements of a simple
diaphragm building as defined in ASCE 7 Section
6.2, where wind loads are only transmitted to the main
wind-force-resisting system (MWFRS) at the dia-
phragms.
5. For open buildings, multispan gable roofs, stepped
roofs, sawtooth roofs, domed roofs, roofs with slopes
greater than 45 degrees (0.79 rad), sohd free-standing
walls and sohd signs, and rooftop equipment, apply
ASCE 7 provisions.
1609.6.1.1 Modifications. The following modifications
shall be made to certain subsections in ASCE 7: in Sec-
tion 1609.6.2, symbols and notations that are specific to
this section are used in conjunction with the symbols and
notations in ASCE 7 Section 6.3.
1609.6.2 Symbols and notations. Coefficients and vari-
ables used in the alternative all-heights method equations
are as follows:
C„^^ = Net-pressure coefficient based on K^ [(G) (C^ -
(GCp^)], in accordance with Table 1609.6.2(2),
G = Gust effect factor for rigid structures in accordance
with ASCE 7 Section 6.5.8.1.
K^ ~ Wind directionality factor in accordance with
ASCE 7 Table 6-4,
P„^, = Design wind pressure to be used in determination
of wind loads on buildings or other structures or
their components and cladding, in psf (kN/m^).
q^ = Wind stagnation pressure in psf (kN/m^) in accor-
dance with Table 1609.6.2(1).
1609.6.3 Design equations. When using the alternative
all-heights method, the MWFRS, and components and clad-
ding of every structure shall be designed to resist the effects
of wind pressures on the building envelope in accordance
with Equation 16-34.
Pnet-^s^z^netU^zti
(Equation 16-34)
Design wind forces for the MWFRS shall not be less than
10 psf (0.48 kN/m^) multiplied by the area of the structure
projected on a plane normal to the assumed wind direction
(see ASCE 7 Section 6.1.4 for criteria). Design net wind
pressure for components and cladding shall not be less than
10 psf (0.48 kN/m^) acting in either direction normal to the
surface.
1609.6.4 Design procedure. The MWFRS and the compo-
nents and cladding of every building or other structure shall
be designed for the pressures calculated using Equation
16-34.
1609.6.4.1 Main wind-force-resisting systems. The
MWFRS shall be investigated for the torsional effects
identified in ASCE 7 Figure 6-9.
1609.6.4.2 Determination ofK^ and K^^. Velocity pres-
sure exposure coefficient, K^, shall be determined in
accordance with ASCE 7 Section 6.5.6.6 and the topo-
graphic factor, K^i, shall be determined in accordance
with ASCE 7 Section 6.5.7.
1. For the windward side of a structure, K^ and K^
shall be based on height z.
2. For leeward and sidewalls, and for windward and
leeward roofs, K^^ and K^ shall be based on mean
roof height h.
TABLE 1609.6.2(1)
WIND VELOCITY PRESSURE {q^) AT STANDARD HEIGHT OF 33 FEET^
BASIC WIND SPEED (mph)
85
90
100
105
110
120
125
130
140
150
160
170
PRESSURE, Q^ (psf)
18.5
20.7
25.6
28.2
31.0
36.9
40.0
43.3
50.2
57.6
65.5
74.0
For SI: 1 foot = 304.8 mm, 1 mph = 0.44 m/s, 1 psf = 47.88 I^.
a. For basic wind speeds not shown, use q^ = 0.00256 V^.
28
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 1609.6.2(2)
NET PRESSURE COEFFICIENTS
Cnet^''
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e, FACTOR
1 . Main wind-
force-resisting
frames and systems
Walls:
Enclosed
Partially enclosed
+ Internal
pressure
- Internal
pressure
+ Internal
pressure
- Internal
pressure
Windward wall
0.43
0.73
0.11
1.05
Leeward wall
-0.51
-0.21
-0.83
0.11
Sidewall
-0.66
-0.35
-0.97
-0.04
Parapet wall
Windward
1.28
1.28
Leeward
-0.85
-0.85
Roofs:
Enclosed
Partially enclosed
Wind perpendicular to ridge
+ Internal
pressure
- Internal
pressure
+ Internal
pressure
- Internal
pressure
Leeward roof or flat roof
-0.66
-0.35
-0.97
-0.04
Windward roof slopes:
Slope < 2:12 (10°)
Condition 1
-1.09
-0.79
-1.41
-0.47
Condition 2
-0.28
0.02
-0.60
0.34
Slope = 4:12 (18°)
Condition 1
-0.73
-0.42
-1.04
-0.11
Condition 2
-0.05
0.25
-0.37
0.57
Slope = 5: 12 (23°)
Condition 1
......
-0.58
-0.28
-0.90
0.04
Condition 2
0.03
0.34
-0.29
0.65
Slope = 6:12 (27°)
Condition 1
-0.47
-0.16
-0.78
0.15
Condition 2
0.06
0.37
-0.25
0.68
Slope = 7:12 (30°)
Condition 1
-0.37
-0.06
-0.68
0.25
Condition 2
0.07
0.37
-0.25
0.69
Slope 9:12 (37°)
Condition 1
-0.27
0.04
-0.58
0.35
Condition 2
0.14
0.44
-0.18
0.76
Slope 12:12 (45°)
0.14
0.44
-0.18
0.76
Wind parallel to ridge and flat roofs
-1.09
-0.79
-1.41
-0.47
Nonbuilding Structures: Chimneys, Tanks and Similar Structures:
h/D
1
7
25
Square (Wind normal to face)
0.99
1.07
1.53
Square (Wind on diagonal)
0.77
0.84
1.15
Hexagonal or Octagonal
0.81
0.97
1.13
Round
0.65
0.81
0.97
Open signs and lattice frameworks
Ratio of solid to gross area
<0.1
0.1 to 0.29
0.3 to 0.7
Flat
1.45
1.30
1.16
Round
0.87
0.94
1.08
(continued)
2010 CALIFORNIA BUILDING CODE
29
STRUCTURAL DESIGN
TABLE 1609.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C„^?^ ^
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e, FACTOR
2. Components and
cladding not in
areas of disconti-
nuity — roofs and
overhangs
Roof elements and slopes
Enclosed
Partially enclosed
Gable or hipped configurations (Zone 1)
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-1 IC Zone 1
Positive
10 square feet or less
0.58
0.89
1(X) square feet or more
0.41
0.72
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.92
-1.23
Overhang: Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-1 IB Zone 1
Negative
10 square feet or less
-1.45
100 square feet or more
-1.36
500 square feet or more
-0.94
6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 6-llD Zone 1
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.83
-1.15
Monosloped configurations (Zone 1)
Enclosed
Partially enclosed
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 6-14B Zone 1
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.26
-1.57
100 square feet or more
-1.09
-1.40
Tall flat-topped roofs h > 60'
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 1) See ASCE 7 Figure 6-17 Zone 1
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.92
-1.23
(continued)
30
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 1609.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C,
a,b
let
STRUCTURE OR
PART THEREOF
DESCRIPTION
^net FACTOR
3, Components and clad-
ding in areas of dis-
continuities — roofs
and overhangs
Roof elements and slopes
Enclosed
Partially enclosed
Gable or hipped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-llC Zone 2
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
10.72
Negative
10 square feet or less
-1.68
-2.00
100 square feet or more
-1.17
-1.49
Overhang for Slope Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-llC Zone 2
Negative
10 square feet or less
-1.87
100 square feet or more
-1.87
6:12 (27°) < Slope < 12:12 (45°) Figure 6-llD
Enclosed
Partially enclosed
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12: 12 (45°) See ASCE 7 Figure 6-1 ID Zone 2
Negative
10 square feet or less
-1.70
500 square feet or more
-1.53
Monosloped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 7: 1 2 (30°) See ASCE 7 Figure 6- 14B Zone 2
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.51
-1.83
100 square feet or more
-1.43
-1.74
Tall flat topped roofs h > 60'
Enclosed
Partiaily enclosed
Flat < Slope < 2:12 (10°) (Zone 2) See ASCE 7 Figure 6-17 Zone 2
Negative
10 square feet or less
-2.11
-2.42
500 square feet or more
-1.51
-1.83
Gable or hipped configurations at comers (Zone 3) See ASCE 7 Figure 6-1 IC Zone 3
Flat < Slope < 6:12 (27°)
Enclosed
Partially enclosed
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.53
-2.85
100 square feet or more
-1.85
-2.17
(continued)
2010 CALIFORNIA BUILDING CODE
31
STRUCTURAL DESIGN
TABLE 1609.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C^^?^^
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„^t FACTOR
3. Components and cladding in
areas of discontinuity — roofs
and overhangs
(continued)
Overhang for Slope Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-1 IC Zone 3
Negative
10 square feet or less
-3.15
100 square feet or more
-2.13
6:12 {IT) < 12:12 (45°) See ASCE 7 Figure 6-llD Zone 3
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12:12 (45°)
Enclosed
Partially enclosed
Negative
10 square feet or less
-1.70
100 square feet or more
-1.53
Monosloped Configurations at comers (Zone 3) See ASCE 7 Figure 6-14B Zone 3
Flat < Slope < 7:12 (30°)
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.62
-2.93
100 square feet or more
-1.85
-2.17
Tall flat topped roofs h > 60'
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 3) See ASCE 7 Figure 6-17 Zone 3
Negative
10 square feet or less
-2.87
-3.19
500 square feet or more
-2.11
-2.42
4. Components and cladding not
in areas of discontinuity — walls
and parapets
Wall Elements: h = 60' (Zone 4) Figure 6-1 1 A
Enclosed
Partially enclosed
Positive
10 square feetor less
1.00
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.09
-1.40
500 square feet or more
-0.83
-1.15
Wail Elements: h > 60' (Zone 4) See ASCE 7 Figure 6-17 Zone 4
Positive
20 square feet or less
0.92
1.23
500 square feet or more
0.66
0.98
Negative
20 square feet or less
-0.92
-1.23
500 square feet or more
-0.75
-1.06
Parapet Walls
Positive
2,87
3.19
Negative
-1.68
-2.00
32
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 1609.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C,
a,b
let
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„^, FACTOR
5. Components and cladding
in areas of discontinuity —
walls and parapets
Wall elements:
h < 60' (Zone 5) Figure 6-1 1 A
Enclosed
Partially enclosed
Positive
10 square feet or less
1.00
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.83
-1.15
Wall elements:
h > 60' (Zone 5) See ASCE 7 Figure 6-17 Zone 4
Positive
20 square feet or less
0.92
1.23
500 square feet or more
0,66
0.98
Negative
20 square feet or less
-1.68
-2.00
500 square feet or more
-LOO
-1.32
Parapet walls
Positive
3.64
3.95
Negative
-2.45
-2.76
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m^, 1 degree = 0.0175 rad.
a. Linear interpolation between values in the table is permitted.
b. Some C„^, values have been grouped together. Less conservative results may be obtained by applying ASCE 7 provisions.
1609.6.4.3 Determination of net pressure coefficients,
C„e,. For the design of the MWFRS and for components
and cladding, the sum of the internal and external net
pressure shall be based on the net pressure coefficient,
C
1. The pressure coefficient, Q^^, for walls and roofs
shall be determined from Table 1609.6.2(2).
2. Where C„^, has more than one value, the more
severe wind load condition shall be used for
design.
1609.6.4.4 Application of wind pressures. When using
the alternative all-heights method, wind pressures shall
be applied simultaneously on, and in a direction normal
to, all building envelope wall and roof surfaces.
1609.6.4.4.1 Components and cladding. Wind pres-
sure for each component or cladding element is
applied as follows using Q^^ values based on the
effective wind area, A, contained within the zones in
areas of discontinuity of width and/or length "a," "2a"
or "4a" at: comers of roofs and walls; edge strips for
ridges, rakes and eaves; or field areas on walls or roofs
as indicated in figures in tables in ASCE 7 as refer-
enced in Table 1609.6.2(2) in accordance with the fol-
lowing:
1. Calculated pressures at local discontinuities
acting over specific edge strips or corner
boundary areas.
2. Include "field" (Zone 1, 2 or 4, as applicable)
pressures applied to areas beyond the bound-
aries of the areas of discontinuity.
3. Where applicable, the calculated pressures at
discontinuities (Zones 2 or 3) shall be com-
bined with design pressures that apply specifi-
cally on rakes or eave overhangs.
SECTION 1610
SOIL LATERAL LOADS
1610.1 GeneraL Foundation walls and retaining walls shall be
designed to resist lateral soil loads. Soil loads specified in Table
1610.1 shall be used as the minimum design lateral soil loads
unless determined otherwise by a geotechnical investigation in
accordance with Section 1803. Foundation walls and other
walls in which horizontal movement is restricted at the top shall
be designed for at-rest pressure. Retaining walls free to move
and rotate at the top shall be permitted to be designed for active
pressure. Design lateral pressure from surcharge loads shall be
added to the lateral earth pressure load. Design lateral pressure
shall be increased if soils at the site are expansive. Foundation
walls shall be designed to support the weight of the full hydro-
static pressure of undrained backfill unless a drainage system is
installed in accordance with Sections 1805.4.2 and 1805.4.3.
Exception: Foundation walls extending not more than 8
feet (2438 mm) below grade and laterally supported at the
top by flexible diaphragms shall be permitted to be designed
for active pressure.
2010 CALIFORNIA BUILDING CODE
33
STRUCTURAL DESIGN
TABLE 1610.1
LATERAL SOIL LOAD
DESCRIPTION OF BACKFILL MATERIAL'^
UNIFIED SOIL
CLASSIFICATION
DESIGN LATERAL SOIL LOAD^
(pound per square foot per foot of depth)
Active pressure
At-rest pressure
Well-graded, clean gravels; gravel-sand mixes
GW
30
60
Poorly graded clean gravels; gravel-sand mixes
GP
30
60
Silty gravels, poorly graded gravel-sand mixes
GM
40
60
Clayey gravels, poorly graded gravel-and-clay mixes
GC
45
60
Well-graded, clean sands; gravelly sand mixes
sw
30
60
Poorly graded clean sands; sand-gravel mixes
SP
30
60
Silty sands, poorly graded sand-silt mixes
SM
45
60
Sand-silt clay mix with plastic fines
SM-SC
45
100
Clayey sands, poorly graded sand-clay mixes
SC
60
100
Inorganic silts and clayey silts
ML
45
100
Mixture of inorganic silt and clay
ML-CL
60
100
Inorganic clays of low to medium plasticity
CL
60
100
Organic silts and silt clays, low plasticity
OL
Noteb
Noteb
Inorganic clayey silts, elastic silts
MH
Note b
Noteb
Inorganic clays of high plasticity
CH
Noteb
Noteb
Organic clays and silty clays
OH
Noteb
Noteb
For SI: 1 pound per square foot per foot of depth = 0. 157 kPa/m, 1 foot = 304.8 mm.
a. Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or satu-
rated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads.
b. Unsuitable as backfill material.
c. The definition and classification of soil materials shall be in accordance with ASTM D 2487.
SECTION 1611
RAIN LOADS
1611.1 Design rain loads. Each portion of a roof shall be
designed to sustain the load of rainwater that will accumulate
on it if the primary drainage system for that portion is blocked
plus the uniform load caused by water that rises above the inlet
of the secondary drainage system at its design flow. The design
rainfall shall be based on the 100-year hourly rainfall rate indi-
cated in Figure 1611.1 or on other rainfall rates determined
from approved local weather data.
For SI: R = 0.0098(^, + d^)
where:
(Equation 16-35)
= Additional depth of water on the undeflected roof
above the inlet of secondary drainage system at its
design flow (i.e., the hydraulic head), in inches (mm).
= Depth of water on the undeflected roof up to the inlet of
secondary drainage system when the primary drainage
system is blocked (i.e., the static head), in inches (mm).
R - Rain load on the undeflected roof, in psf (kN/mj).
When the phrase "undeflected roof is used, deflec-
tions from loads (including dead loads) shall not be
considered when determining the amount of rain on the
roof.
1611.2 Ponding instability. For roofs with a slope less than V4
inch per foot [1.19 degrees (0.0208 rad)], the design calcula-
tions shall include verification of adequate stiffness to preclude
progressive deflection in accordance with Section 8.4 of ASCE
7.
1611.3 Controlled drainage. Roofs equipped with hardware
to control the rate of drainage shall be equipped with a second-
ary drainage system at a higher elevation that limits accumula-
tion of water on the roof above that elevation. Such roofs shall
be designed to sustain the load of rainwater that will accumu-
late on them to the elevation of the secondary drainage system
plus the uniform load caused by water that rises above the inlet
of the secondary drainage system at its design flow determined
from Section 1611.1. Such roofs shall also be checked for
ponding instability in accordance with Section 1611.2.
34
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
4.28^"
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
35
STRUCTURAL DESIGN
[P] FIGURE 1611.1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
36
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1 .1 >1 1^
i^ /Kg^"
2
.^
Li ^
rk\^
^s^
;^
.5 . -^M^r^.^4~lCp~M ^.^HV^
^J^"^
L ^
ivTl >f n
^
^^J^l
■A
5>^j^L„a^
J
f^
- V
V
L
y^
y«^
Jrfl
1.5'^^^OrAk^^
fcr-
^^^
~T
2Zisd/;\^^
^^^
=w^
-J-
/
/
ix-^ r\ 1
xh/j
^
\
V-J*^
i
■^^1! — k^
/ :3 y^/
w
W
flf
itx
F^-
■•■■^-- , W-^
/ f/l
1^
iv\t
W
1.5 1.5 i.r^
> / /
2
as 3^ —
^
L^
2
/
2.5
[P] FIGURE 1611.1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
37
STRUCTURAL DESIGN
170° 175» 180° 175° 170" 166=' 160° 165° 150° 146° 1W° 135° 130
[P] FIGURE 1611.1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA
For SI; 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
38
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
IS
E^^?^^
0.
'V^
i*
■^
<
X
Z
f*)?^"-^^^^^ IV
^>^^
*^x
N<^
/^
[P] FIGURE 1611.1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
39
STRUCTURAL DESIGN
SECTION 1612
FLOOD LOADS
1612.1 GeneraL Within flood hazard areas as established in
Section 1612.3, all new construction of buildings, structures
and portions of buildings and structures, including substantial
improvement and restoration of substantial damage to build-
ings and structures, shall be designed and constructed to resist
the effects of flood hazards and flood loads. For buildings that
are located in more than one flood hazard area, the provisions
associated with the most restrictive flood hazard area shall
apply.
1612.2 Definitions. The following words and terms shall, for
the purposes of this section, have the meanings shown herein.
BASE FLOOD. The flood having a 1 -percent chance of being
equaled or exceeded in any given year.
BASE FLOOD ELEVATION. The elevation of the base
flood, including wave height, relative to the National Geodetic
Vertical Datum (NGVD), North American Vertical Datum
(NAVD) or other datum specified on the Flood Insurance Rate
Map (FIRM).
BASEMENT. The portion of a building having its floor
subgrade (below ground level) on all sides.
This definition of "Basement" is limited in application to the
provisions of Section 1612 (see "Basement" in Section 502. 1).
DESIGN FLOOD. The flood associated with the greater of
the following two areas:
1. Area with a flood plain subject to a 1 -percent or greater
chance of flooding in any year; or
2. Area designated as a flood hazard area on a commu-
nity's flood hazard map, or otherwise legally designated.
DESIGN FLOOD ELEVATION. The elevation of the
"design floods including wave height, relative to the datum
specified on the community's legally designated flood hazard
map. In areas designated as Zone AG, the design flood eleva-
tion shall be the elevation of the highest existing grade of the
building's perimeter plus the depth number (in feet) specified
on the flood hazard map. In areas designated as Zone AO where
a depth number is not specified on the map, the depth number
shall be taken as being equal to 2 feet (610 mm).
DRY FLOODPROOFING. A combination of design modifi-
cations that results in a building or structure, including the
attendant utility and sanitary facihties, being water tight with
walls substantially impermeable to the passage of water and
with structural components having the capacity to resist loads
as identified in ASCE 7.
EXISTING CONSTRUCTION. Any buildings and struc-
tures for which the "start of construction" commenced before
the effective date of the community's first flood plain manage-
ment code, ordinance or standard. "Existing construction" is
also referred to as "existing structures."
EXISTING STRUCTURE. See "Existing construction."
FLOOD or FLOODING. A general and temporary condition
of partial or complete inundation of normally dry land from:
1. The overflow of inland or tidal waters.
2. The unusual and rapid accumulation or runoff of surface
waters from any source.
FLOOD DAMAGE-RESISTANT MATERL\LS. Any con-
struction material capable of withstanding direct and pro-
longed contact with floodwaters without sustaining any
damage that requires more than cosmetic repair.
FLOOD HAZARD AREA. The greater of the following two
areas:
1. The area within a flood plain subject to a 1 -percent or
greater chance of flooding in any year.
2. The area designated as 2l flood hazard area on a commu-
nity' s flood hazard map, or otherwise legally designated.
FLOOD HAZARD AREA SUBJECT TO HIGH-VELOC-
ITY WAVE ACTION. Area within the flood hazard area that
is subject to high- velocity wave action, and shown on a Flood
Insurance Rate Map (FIRM) or other flood hazard map as Zone
V,VO,VEorVl-30.
FLOOD INSURANCE RATE MAP (FIRM). An official
map of a community on which the Federal Emergency Man-
agement Agency (FEMA) has delineated both the special flood
hazard areas and the risk premium zones applicable to the com-
munity.
FLOOD INSURANCE STUDY. The official report provided
by the Federal Emergency Management Agency containing the
Flood Insurance Rate Map (FIRM), the Rood Boundary and
Floodway Map (FBFM), the water surface elevation of the
base flood and supporting technical data.
FLOODWAY. The channel of the river, creek or other water-
course and the adjacent land areas that must be reserved in
order to discharge the base flood v^iihovX cumulatively increas-
ing the water surface elevation more than a designated height.
LOWEST FLOOR. The floor of the lowest enclosed area,
including basement, but excluding any unfinished or
flood-resistant enclosure, usable solely for vehicle parking,
building access or limited storage provided that such enclosure
is not built so as to render the structure in violation of this sec-
tion.
SPECIAL FLOOD HAZARD AREA. The land area subject
to flood hazards and shown on a Rood Insurance Rate Map or
other flood hazard map as Zone A, AE, Al-30, A99, AR, AG,
AH,V,VO,VEorVl-30.
START OF CONSTRUCTION. The date of issuance for new
construction and substantial improvements to existing struc-
tures, provided the actual start of construction, repair, recon-
struction, rehabilitation, addition, placement or other
improvement is within 180 days after the date of issuance. The
actual start of construction means the first placement of perma-
nent construction of a building (including a manufactured
40
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
home) on a site, such as the pouring of a slab or footings, instal-
lation of pilings or construction of columns.
Permanent construction does not include land preparation
(such as clearing, excavation, grading or filling), the installa-
tion of streets or walkways, excavation for a basement, foot-
ings, piers or foundations, the erection of temporary forms or
the installation of accessory buildings such as garages or sheds
not occupied as dwelling units or not part of the main building.
For a substantial improvement, the actual "start of construc-
tion" means the first alteration of any wall, ceiling, floor or
other structural part of a building, whether or not that alteration
affects the external dimensions of the building.
SUBSTANTIAL DAMAGE. Damage of any origin sustained
by a structure whereby the cost of restoring the structure to its
before-damaged condition would equal or exceed 50 percent of
the market value of the structure before the damage occurred,
SUBSTANTIAL IMPROVEMENT. Any repair, reconstruc-
tion, rehabilitation, addition or improvement of a building or
structure, the cost of which equals or exceeds 50 percent of the
market value of the structure before the improvement or repair
is started. If the structure has sustained substantial damage, any
repairs are considered substantial improvement regardless of
the actual repair work performed. The term does not, however,
include either:
1 . Any project for improvement of a building required to
correct existing health, sanitary or safety code violations
identified by the building official and that are the mini-
mum necessary to assure safe living conditions.
2. Any alteration of a historic structure provided that the
alteration will not preclude the structure's continued
designation as a historic structure.
1612.3 Establishment of flood hazard areas. To establish
flood hazard areas, the applicable governing authority shall
adopt a flood hazard map and supporting data. The flood haz-
ard map shall include, at a minimum, areas of special flood haz-
ard as identified by the Federal Emergency Management
Agency in an engineering report entitled "The Flood Insurance
Study for [INSERT NAME OF JURISDICTION]," dated [INSERT
DATE OF ISSUANCE], as amended or revised with the accompa-
nying Flood Insurance Rate Map (FIRM) and Rood Boundary
and Flood way Map (FBFM) and related supporting data along
with any revisions thereto. The adopted flood hazard map and
supporting data are hereby adopted by reference and declared
to be part of this section.
Exception: [OSHPD 2] The flood hazard map shall
include, at a minimum, areas of special flood hazard as
identified by the Federal Emergency Management Agency's
Flood Insurance Study (FIS) adopted by the local authority
having jurisdiction where the project is located.
1612.3.1 Design flood elevations. Where design flood ele-
vations are not included in the flood hazard areas estab-
lished in Section 1612.3, or where floodways are not
designated, the building official is authorized to require the
applicant to:
1 . Obtain and reasonably utilize any design flood eleva-
tion and floodway data available from a federal, state
or other source; or
2. Determine the design flood elevation and/or
floodway in accordance with accepted hydrologic
and hydraulic engineering practices used to define
special flood hazard areas. Determinations shall be
undertaken by a registered design professional who
shall document that the technical methods used
reflect currently accepted engineering practice.
1612.3.2 Determination of impacts. In nvo^nnt flood haz-
ard areas where design flood elevations are specified but
floodways have not been designated, the applicant shall pro-
vide a floodway analysis that demonstrates that the pro-
posed work will not increase the design flood elevation
more than 1 foot (305 mm) at any point within the jurisdic-
tion of the applicable governing authority.
1612.4 Design and construction. The design and construction
of buildings and structures located in flood hazard areas,
including flood hazard areas subject to high-velocity wave
action, shall be in accordance with Chapter 5 of ASCE 7 and
with ASCE 24.
1612.5 Flood hazard documentation. The following docu-
mentation shall be prepared and sealed by a registered design
professional and submitted to the building official:
1. For construction in flood hazard areas not subject to
high- velocity wave action:
1.1. The elevation of the lowest floor, including the
basement, as required by the lowest floor eleva-
tion inspection in Section 110.3.3, Chapter 1,
Division II.
1.2. For fully enclosed areas below the design flood
elevation where provisions to allow for the auto-
matic entry and exit of floodwaters do not meet
the minimum requirements in Section 2.6.2.1 of
ASCE 24, construction documents shall include
a statement that the design will provide for equal-
ization of hydrostatic flood forces in accordance
with Section 2.6.2.2 of ASCE 24.
1.3. For dry floodproofed nonresidential buildings,
construction documents shall include a statement
that the dry floodproofing is designed in accor-
dance with ASCE 24.
2. For construction in flood hazard areas subject to
high- velocity wave action:
2.1. The elevation of the bottom of the lowest hori-
zontal structural member as required by the low-
est floor elevation inspection in Section 110.3.3,
Chapter 1, Division II.
2.2. Construction documents shall include a state-
ment that the building is designed in accordance
with ASCE 24, including that the pile or column
foundation and building or structure to be
attached thereto is designed to be anchored to
resist flotation, collapse and lateral movement
due to the effects of wind and flood loads acting
simultaneously on all building components, and
other load requirements of Chapter 16.
2010 CALIFORNIA BUILDING CODE
41
STRUCTURAL DESIGN
2.3. For breakaway walls designed to resist a nominal
load of less than 10 psf (0.48 kN/m^) or more than
20 psf (0.96 kN/m^), construction documents
shall include a statement that the breakaway wall
is designed in accordance with ASCE 24.
SECTION 1613
EARTHQUAKE LOADS
1613.1 Scope. Every structure, and portion thereof, including
nonstructural components that are permanently attached to
structures and their supports and attachments, shall be
designed and constructed to resist the effects of earthquake
motions in accordance with ASCE 7, excluding Chapter 14 and
Appendix 1 1 A. The seismic design category for a structure is
permitted to be determined in accordance with Section 1613 or
ASCE 7.
Exceptions:
1 . Detached one- and two- family dwellings, assigned to
Seismic Design Category A, B or C, or located where
the mapped short-period spectral response accelera-
tion, Ss, is less than 0.4 g.
2. The seismic-force-resisting system of wood-frame
buildings that conform to the provisions of Section
2308 are not required to be analyzed as specified in
this section. [OSHPD 2] Not permitted by OSHPD,
see Section 2308.
3. Agricultural storage structures intended only for inci-
dental human occupancy.
4. Structures that require special consideration of their
response characteristics and environment that are not
addressed by this code or ASCE 7 and for which other
regulations provide seismic criteria, such as vehicular
bridges, electrical transmission towers, hydraulic
structures, buried utility lines and their appurtenances
and nuclear reactors.
5. [OSHPD 2] Seismic Design Category shall be in
accordance with exception to Section 1613.5.6.
1613.1.1 Scope. [SL] For applications listed in Section 1.12
regulated by the State Librarian, only the provisions of
ASCE 7 Table 13.5-1 and Table 1607.1 ^ as amended^ of this
code shall apply.
1613.1.2 State-owned buildings. State-owned buildings,
including those of the University of California, CSU and
Judicial Council, shall not be constructed where any por-
tion of the foundation would be within a mapped area of
earthquake -induced liquefaction oflandsliding or within 50
feet of a mapped fault rupture hazard as established by Sec-
tion 1802.7.
1613.2 Definitions. The following words and terms shall, for
the purposes of this section, have the meanings shown herein.
DESIGN EARTHQUAKE GROUND MOTION. The earth-
quake ground motion that buildings and structures are specifi-
cally proportioned to resist in Section 1613.
MAXIMUM CONSIDERED EARTHQUAKE GROUND
MOTION. The most severe earthquake effects considered by
this code.
MECHANICAL SYSTEMS. For the purposes of determin-
ing seismic loads in ASCE 7, mechanical systems shall include
plumbing systems as specified therein.
ORTHOGONAL. To be in two horizontal directions, at 90
degrees (1.57 rad) to each other.
SEISMIC DESIGN CATEGORY. A classification assigned
to a structure based on its occupancy category and the severity
of the design earthquake ground motion at the site.
SEISMIC-FORCE-RESISTING SYSTEM. That part of the
structural system that has been considered in the design to pro-
vide the required resistance to the prescribed seismic forces.
SITE CLASS. A classification assigned to a site based on the
types of soils present and their engineering properties as
defined in Section 1613.5.2.
SITE COEFFICIENTS, The values of F^ and F, indicated in
Tables 1613.5.3(1) and 1613.5.3(2), respectively.
1613.3 Existing buildings. Additions, alterations, repairs or
change of occupancy of existing buildings shall be in accor-
dance with Chapter 34.
1613.3.1 Existing state buildings. Additions, alterations,
repairs or change of occupancy category of existing build-
ings shall be in accordance with Chapter 34.
1613.4 Special inspections. Where required by Sections
1705.3 through 1705.3.5, the statement of special inspections
shall include the special inspections required by Section
1705.3.6.
1613.5 Seismic ground motion values. Seismic ground
motion values shall be determined in accordance with this sec-
tion.
1613.5.1 Mapped acceleration parameters. The parame-
ters S^ and S^ shall be determined from the 0.2 and 1 -second
spectral response accelerations shown on Figures 1613.5(1)
through 1613.5(14). Where S^ is less than or equal to 0.04
and S^ is less than or equal to 0. 15, the structure is permitted
to be assigned to Seismic Design Category A.
Exception: [OSHPD 2] Seismic Design Category shall
be in accordance with exception to Section 1613.5.6.
1613.5.2 Site class definitions. Based on the site soil prop-
erties, the site shall be classified as either Site Class A, B, C,
D, E or F in accordance with Table 1613.5.2. When the soil
properties are not known in sufficient detail to determine the
site class. Site Class D shall be used unless the building offi-
cial or geotechnical data determines that Site Class E or F
soil is likely to be present at the site.
II
42
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 1613.5.2
SITE CLASS DEFINITIONS
SITE
CLASS
SOIL PROFILE
NAME
AVERAGE PROPERTIES IN TOP 100 feet, SEE SECTION 1613.5.5
Soil shear wave velocity, v^, (ft/s)
Standard penetration resistance,
N
Soil undrained shear strength, s„ , (psf)
A
Hard rock
V, > 5,000
N/A
N/A
B
Rock
2,500 < V, < 5,000
N/A
N/A
C
Very dense soil and soft rock
1,200 <v^ < 2,500
N>50
5„ > 2,000
D
Stiff soil profile
600 <v, < 1,200
15<iV<50
1,000 <5„< 2,000
E
Soft soil profile
V, < 600
N<15
5„< 1,000
E
—
Any profile with more than 10 feet of soil having the following characteristics:
1. Plasticity index P/> 20,
2. Moisture content w > 40%, and
3. Undrained shear strength ^„< 500 psf
F
—
Any profile containing soils having one or more of the following characteristics:
1 . Soils vulnerable to potential failure or collapse under seismic loading such as hquefiable
soils, quick and highly sensitive clays, collapsible weakly cemented soils.
2. Peats and/or highly organic clays (i^> 10 feet of peat and/or highly organic clay where
H - thickness of soil)
3. Very high plasticity clays {H > 25 feet with plasticity index PI>15)
4. Very thick soft/medium stiff clays (H > 120 feet)
TABLE 1613.5.3(1)
VALUES OF SITE COEFFICIENT F^ '
SITE
CLASS
IVIAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD
Ss < 0.25
S^ = 0.50
S^ = 0.75
S5=1.00
S3 > 1.25
A
0.8
0.8
0.8
0.8
0.8
B
1.0
1.0
1.0
1.0
1.0
C
1.2
1.2
1.1
1.0
1.0
D
1.6
1.4
1.2
1.1
1.0
E
2.5
1.7
1.2
0.9
0.9
F
Noteb
Noteb
Noteb
Noteb
Noteb
a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at short period, S^.
b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
TABLE 1613.5.3(2)
VALUES OF SITE COEFFICIENT Fy^
SITE
CLASS
MAPPED SPECTRAL RESPONSE ACCELERATION AT 1 -SECOND PERIOD
Si < 0.1
i?i = 0.2
Si = 0.3
S, = 0.4
Si > 0.5
A
0.8
0.8
0.8
0.8
0.8
B
1.0
1.0
1.0
1.0
1.0
C
1.7
1.6
1.5
1.4
L3
D
2.4
2.0
1.8
1.6
1.5
E
3.5
3.2
2.8
2.4
2.4
F
Noteb
Noteb
Noteb
Noteb
Noteb
a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at 1 -second period, 5,.
b. Values shall be determined in accordance with Section 1 1.4.7 of ASCE 7.
2010 CALIFORNIA BUILDING CODE
43
STRUCTURAL DESIGN
1613.5.3 Site coefficients and adjusted maximum con-
sidered earthquake spectral response acceleration
parameters. The maximum considered earthquake spectral
response acceleration for short periods, 5^5, and at 1 -second
period, S^^i, adjusted for site class effects shall be deter-
mined by Equations 16-36 and 16-37, respectively:
^MS ~ ^a^s
(Equation 16-36)
(Equation 16-37)
where:
F^ = Site coefficient defined in Table 1613.5.3(1).
= Site coefficient defined in Table 1613.5.3(2).
Ss
= The mapped spectral accelerations for short periods
as determined in Section 1613.5.1.
Si = The mapped spectral accelerations for a 1 -second
period as determined in Section 1613.5.1.
1613.5,4 Design spectral response acceleration parame-
ters. Five-percent damped design spectral response acceler-
ation at short periods, 5*^5, and at 1 -second period, 5^^, shall
be determined from Equations 16-38 and 16-39, respec-
tively:
^DS— ^^MS
^D\ — r.^Ml
(Equation 16-38)
(Equation 16-39)
where:
Sj^s - The maximum considered earthquake spectral
response accelerations for short period as deter-
mined in Section 1613.5.3.
Sj^i = The maximum considered earthquake spectral
response accelerations for 1 -second period as
determined in Section 1613.5.3.
1613.5.5 Site classification for seismic design. Site classi-
fication for Site Class C, D or E shall be determined from
Table 1613.5.5.
The notations presented below apply to the upper 100 feet
(30 480 mm) of the site profile. Profiles containing dis-
tinctly different soil and/or rock layers shall be subdivided
into those layers designated by a number that ranges from 1
to n at the bottom where there is a total of n distinct layers in
the upper 100 feet (30 480 mm). The symbol / then refers to
any one of the layers between 1 and n,
where:
v^, = The shear wave velocity in feet per second (m/s).
di = The thickness of any layer between and 100 feet
(30 480 mm).
where:
Vs =-
1=1
^ di
(Equation 16-40)
^ di = 100 feet (30 480 mm)
A^, is the Standard Penetration Resistance (ASTM D 1586)
not to exceed 100 blows/foot (328 blows/m) as directly
measured in the field without corrections. When refusal is
met for a rock layer, A^, shall be taken as 100 blows/foot (328
blows/m).
Ik
(Equation 16-41)
where A^, and d^ in Equation 16-41 are for cohesionless soil,
cohesive soil and rock layers.
Nch =-
d.
(Equation 16-42)
where:
m
1 = 1
Use di and A^, for cohesionless soil layers only in Equation
16-42.
ds = The total thickness of cohesionless soil layers in the
top 100 feet (30 480 mm).
m = The number of cohesionless soil layers in the top 100
feet (30 480 mm).
TABLE 1613.5.5
SITECLAS3IFICATI0N«
SITE CLASS
_
Vs
NotN,,
®u
E
< 600 ft/s
<15
< 1,000 psf
D
600 to 1,200 ft/s
15 to 50
1,000 to 2,000 psf
C
1,200 to 2,500 ft/s
>50
> 2,000
For SI: 1 foot per second = 304.8 mm per second, 1 pound per square foot = (i.0479kN/m^.
a. If the 5^^ method is used and the N^^and 5„ criteria differ, select the category w ith the softer soils (for example, use Site Class E instead of D).
44
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
5„, = The undrained shear strength in psf (kPa), not to
exceed 5,000 psf (240 kPa), ASTM D 2166 or D
2850.
Su =
if
(Equation 16-43)
where:
d^ = The total thickness of cohesive soil layers in the top
100 feet (30 480 mm).
k = The number of cohesive soil layers in the top 100 feet
(30 480 mm).
PI = The plasticity index, ASTM D 4318.
w = The moisture content in percent, ASTM D 2216.
Where a site does not qualify under the criteria for Site
Class F and there is a total thickness of soft clay greater than
1 feet (3048 mm) where a soft clay layer is defined hy:s^<
500 psf (24 kPa), w > 40 percent, and PI > 20, it shall be clas-
sified as Site Class E.
The shear wave velocity for rock, Site Class B, shall be
either measured on site or estimated by a geotechnical engi-
neer or engineering geologist/seismologist for competent
rock with moderate fracturing and weathering. Softer and
more highly fractured and weathered rock shall either be
measured on site for shear wave velocity or classified as Site
Class C.
The hard rock category. Site Class A, shall be supported
by shear wave velocity measurements either on site or on
profiles of the same rock type in the same formation with an
equal or greater degree of weathering and fracturing. Where
hard rock conditions are known to be continuous to a depth
of 100 feet (30 480 mm), surficial shear wave velocity mea-
surements are permitted to be extrapolated to assess v^ .
The rock categories. Site Classes A and B, shall not be
used if there is more than 10 feet (3048 mm) of soil between
the rock surface and the bottom of the spread footing or mat
foundation.
1613.5.5.1 Steps for classifying a site.
1. Check for the four categories of Site Class F
requiring site-specific evaluation. If the site corre-
sponds to any of these categories, classify the site
as Site Class F and conduct a site- specific evalua-
tion.
2. Check for the existence of a total thickness of soft
clay > 10 feet (3048 nmi) where a soft clay layer is
defined by: 5„< 500 psf (24 kPa), w > 40 percent
and PI > 20. If these criteria are satisfied, classify
the site as Site Class E.
3 . Categorize the site using one of the following three
methods with v^, N, and s^and computed in all
cases as specified.
3.1. v^ for the top 100 feet (30 480 mm)
(v^ method).
3.2.iV_for the top 100 feet (30 480 mm)
(A^method).
3.3. N^f, for cohesionless soil layers (PI < 20)
in the top 100 feet (30 480 mm) and aver-
age, s^ for cohesive soil layers (P/> 20) in
the top 100 feet (30 480 mm) ( s^ method).
1613.5.6 Determination of seismic design category.
Structures classified as Occupancy Category I, II or III that
are located where the mapped spectral response accelera-
tion parameter at 1 -second period, 5*;, is greater than or
equal to 0.75 shall be assigned to Seismic Design Category
E. Structures classified as Occupancy Category IV that are
located where the mapped spectral response acceleration
parameter at 1 -second period, Sj, is greater than or equal to
0.75 shall be assigned to Seismic Design Category F. All
other structures shall be assigned to a seismic design cate-
gory based on their occupancy category and the design
spectral response acceleration coefficients, Sj^s ^^^ ^di^
determined in accordance with Section 1613.5.4 or the site-
specific procedures of ASCE 7. Each building and structure
shall be assigned to the more severe seismic design category
in accordance with Table 1613.5.6(1) or 1613.5.6(2), irre-
spective of the fundamental period of vibration of the struc-
ture, r.
TABLE 1613.5.6(1)
SEISMIC DESIGN CATEGORY BASED ON
SHORT-PERIOD RESPONSE ACCELERATIONS
VALUE OF Sos
OCCUPANCY CATEGORY
lor II
111
IV
5^5<0.167g
A
A
A
ai67g<5^5<0.33g
B
B
C
0.33g<5^5<0.50g
C
C
D
0.50g<5^5
D
D
D
TABLE 1613.5.6(2)
SEISMIC DESIGN CATEGORY BASED ON
1 -SECOND PERIOD RESPONSE ACCELERATION
VALUE OF Soi
OCCUPANCY CATEGORY
lor II
III
IV
Soi < 0.067g
A
A
A
0.067g<5^;<0.133g
B
B
C
0.133g<5^;<0.20g
C
C
D
0.20g< Soi
D
D
D
Exception: [OSHPD 2] Structures not assigned to seis-
mic design category E or F above shall be assigned to
seismic design category D.
1613.5.6.1 Alternative seismic design category deter-
mination. Where 5; is less than 0.75, the seismic design
2010 CALIFORNIA BUILDING CODE
45
STRUCTURAL DESIGN
category is permitted to be determined from Table
1613.5.6(1) alone when all of the following apply:
1. In each of the two orthogonal directions, the
approximate fundamental period of the structure,
Ta, in each of the two orthogonal directions deter-
mined in accordance with Section 12.8.2.1 of
ASCE 7, is less than 0.8 T^ determined in accor-
dance with Section 11.4.5 of ASCE 7.
2. In each of the two orthogonal directions, the fun-
damental period of the structure used to calculate
the story drift is less than T,.
3. Equation 12.8-2 of ASCE 7 is used to determine
the seismic response coefficient, Q.
4. The diaphragms are rigid as defined in Section
1 2 . 3 . 1 of ASCE 7 or , for diaphragms that are flexi-
ble, the distances between vertical elements of the
seismic-force-resisting system do not exceed 40
feet (12 192 mm).
Exception: [OSHPD 2] Seismic design category
I I shall be determined in accordance with exception to
Section 1613.5 A
1613.5.6.2 Simplified design procedure. Where the
alternate simplified design procedure of ASCE 7 is used,
the seismic design category shall be determined in accor-
dance with ASCE 7.
Exception: [OSHPD 2] Seismic design category
I I shall be determined in accordance with exception to
Section 1613.5,6,
1613.6 Alternatives to ASCE 7. The provisions of Section
1613.6 shall be permitted as alternatives to the relevant provi-
sions of ASCE 7.
1613.6.1 Assumption of flexible diaphragm. Add the fol-
lowing text at the end of Section 12.3. 1. 1 of ASCE 7.
Diaphragms constructed of wood structural panels or
untopped steel decking shall also be permitted to be ideal-
ized as flexible, provided all of the following conditions are
met:
1. Toppings of concrete or similar materials are not
placed over wood structural panel diaphragms except
for nonstructural toppings no greater than 1 Vj inches
(38 mm) thick.
2. Each line of vertical elements of the seis-
mic-force-resisting system complies with the allow-
able story drift of Table 12.12-1.
3. Vertical elements of the seismic-force-resisting sys-
tem are light-frame walls sheathed with wood struc-
tural panels rated for shear resistance or steel sheets.
4. Portions of wood structural panel diaphragms that
cantilever beyond the vertical elements of the lat-
eral-force-resisting system are designed in accor-
dance with Section 4.2.5.2 of AF&PA SDPWS.
1613.6.2 Additional seismic-force-resisting systems for
seismically isolated structures. Add the following excep-
tion to the end of Section 17.5.4.2 of ASCE 7:
Exception: For isolated structures designed in accor-
dance with this standard, the Structural System Limita-
tions and the Building Height Limitations in Table
12.2-1 for ordinary steel concentrically braced frames
(OCBFs) as defined in Chapter 1 1 and ordinary moment
frames (OMFs) as defined in Chapter 1 1 are permitted to
be taken as 160 feet (48 768 mm) for structures assigned
to Seismic Design Category D, E or F, provided that the
following conditions are satisfied:
1 . The value ofRi as defined in Chapter 17 is taken as
1.
2. For OMFs and OCBFs, design is in accordance
with AISC 341.
1613.6.3 Automatic sprinkler systems. Automatic sprin-
kler systems designed and installed in accordance with
NFPA 13 shall be deemed to meet the requirements of Sec-
tion 13.6.8 of ASCE 7.
1613.6.4 Autoclaved aerated concrete (AAC) masonry
shear wall design coefficients and system limitations.
Add thefollowing text at the end of Section 12.2.1 of ASCE
7:
For ordinary reinforced AAC masonry shear walls used
in the seismic-force-resisting system of structures, the
response modification factor, /?, shall be permitted to be
taken as 2, the deflection amplification factor, C^, shall be
permitted to be taken as 2 and the system overstrength fac-
tor, Q„, shall be permitted to be taken as 2V2. Ordinary rein-
forced AAC masonry shear walls shall not be limited in
height for buildings assigned to Seismic Design Category B,
shall be limited in height to 35 feet (10 668 mm) for build-
ings assigned to Seismic Design Category C and are not per-
mitted for buildings assigned to Seismic Design Categories
D, E and F.
For ordinary plain (unreinforced) AAC masonry shear
walls used in the seismic-force-resisting system of struc-
tures, the response modification factor, /?, shall be permitted
to be taken as 1 V2, the deflection amplification factor, C^,
shall be permitted to be taken as IV2 and the system
overstrength factor, Q^, shall be permitted to be taken as 2 Vj.
Ordinary plain (unreinforced) AAC masonry shear walls
shall not be limited in height for buildings assigned to Seis-
mic Design Category B and are not permitted for buildings
assigned to Seismic Design Categories C, D, E and R
1613.6.5 Seismic controls for elevators. Seismic switches
in accordance with Section 8.4.10 of ASME A17.1 shall be
deemed to comply with Section 13.6.10.3 of ASCE 7.
1613.6.6 Steel plate shear wall height limits. Modify Sec-
tion 12.2.5.4 of ASCE 7 to read as follows:
12.2.5.4 Increased building height limit for steel-
braced frames, special steel plate shear walls and spe-
cial reinforced concrete shear walls. The height limits
in Table 12.2-1 are permitted to be increased from 160
feet (48 768 mm) to 240 feet (75 152 mm) for structures
assigned to Seismic Design Category D or E and from
100 feet (30 480 mm) to 160 feet (48 768 nmi) for struc-
tures assigned to Seismic Design Category F that have
46
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
steel-braced frames, special steel plate shear walls or
special reinforced concrete cast-in-place shear walls and
that meet both of the following requirements:
1 . The structure shall not have an extreme torsional
irregularity as defined in Table 12.2-1 (horizontal
structural irregularity Type lb).
2. The braced frames or shear walls in any one plane
shall resist no more than 60 percent of the total
seismic forces in each direction, neglecting acci-
dental torsional effects.
1613.6.7 Minimum distance for building separation. All
buildings and structures shall be separated from adjoining
structures. Separations shall allow for the maximum inelas-
tic response displacement (5^^). 5^^ shall be determined at
critical locations with consideration for both translational
and torsional displacements of the structure using Equation
16-44.
O Ayr
(Equation 16-44)
where:
Cj = Deflection amphfication factor in Table 12.2-1 of
ASCE 7.
5^^ = Maximum displacement defined in Section 12.8.4.3
of ASCE 7.
/ = Importance factor in accordance with Section 1 1.5.1
of ASCE 7.
Adjacent buildings on the same property shall be sepa-
rated by a distance not less than bj^j, determined by Equa-
tion 16-45.
^MT^ii^Mlf -^i^MlY
(Equation 16-45)
where:
^Af/j ^M2 = The maximum inelastic response displace-
ments of the adjacent buildings in accordance
with Equation 16-44.
Where a structure adjoins a property line not common to a
public way, the structure shall also be set back from the
property line by not less than the maximum inelastic
response displacement, 5^^, of that structure.
Exceptions:
1 . Smaller separations or property line setbacks shall
be permitted when justified by rational analyses.
2. Buildings and structures assigned to Seismic
Design Category A, B or C.
1613.6.8 HVAC ductwork with Ip = 1.5. Seismic supports
are not required for HVAC ductwork with /p = 1.5 if either of
the following conditions is met for the full length of each
duct run:
1. HVAC ducts are suspended from hangers 12 inches
(305 mm) or less in length with hangers detailed to
avoid significant bending of the hangers and their
attachments, or
2. HVAC ducts have a cross-sectional area of less than 6
square feet (0.557 m^).
1613.6.9 Exceptions for nonstructural components,
[BSC] Replace ASCE 7 Section 13.13 by the following
items:
Exemptions: The following nonstructural components
are exempt from the requirements of this section:
1. Furniture (except storage cabinets as noted in
Table 13.5-1.
2. Temporary or moveable equipment.
3. Architectural components in Seismic Design Cate-
gory B other than parapets supported by bearing
walls or shear walls, provided that the component
importance factor I p, is equal to 1.0.
4. Mechanical and electrical components in Seismic
Design Category B,
5. Mechanical and electrical components in Seismic
Design Category C, provided that the component
importance factor, Ip, is equal to 1.0.
6. Mechanical and electrical components in Seismic
Design Category D, E or F where all of the follow-
ing apply:
a. The component importance factor, Ip, is
equal to 1.0;
b. The component is positively attached to the
structure;
c. Flexible connections are provided between
the component and associated ductwork,
piping and conduit; and either:
i. The component weighs 400 lb (1780
N) or less and has a center of mass
located 4 ft (1.22 m) or less above the
adjacent floor level; or
a. The component weighs 20 lb (89 N) or
less, or, in the case of a distributed
system, 5 lb/ft (73 N/m) or less.
1613.6.10 Exceptions for nonstructural components,
[BSC] Replace Items 4 and 5 of ASCE 7 Section 13.1.4 with
the following items.
4, Mechanical and electrical components in Seismic
Design Category D, EorF where all of the following
apply:
a. The component importance factor, Ip, is equal
to 1.0;
b. The component is positively attached to the
structure;
c. Flexible connections are provided between the
component and associated ductwork, piping
and conduit; and either:
i. The component weights 400 lb (1 780 N)
or less and has a center of mass located 4
ft (1,22 m) or less above adjacent floor
level.
2010 CALIFORNIA BUILDING CODE
47
STRUCTURAL DESIGN
a. The component weights 20 lb (89 N) or
less, or, in the case of a distributed sys-
tem, 5 lb/ft (73N/m) or less.
1613.7 ASCE 7, Section 11.7.5. Modify ASCE 7, Section
1 1.7,5 to read as follows:
11.7.5 Anchorage of walls. Walls shall be anchored to the
roof and all floors and members that provide lateral support
for the wall or that are supported by the wall. The anchorage
shall provide a direct connection between the walls and the
roof or floor construction. The connections shall be capable
of resisting the forces specified in Section 11.7.3 applied
horizontally, substituted for E in load combinations of Sec-
tion 2.3 or 2.4.
SECTION 1614
STRUCTURAL INTEGRITY
1614.1 General. Buildings classified as high-rise buildings in
accordance with Section 403 and assigned to Occupancy Cate-
gory in or IV shall comply with the requirements of this sec-
tion. Frame structures shall comply with the requirements of
Section 1614.3. Bearing wall structures shall comply with the
requirements of Section 1614.4.
1614.2 Definitions. The following words and terms shall, for
the purposes of Section 1614, have the meanings shown herein.
BEARING WALL STRUCTURE. A building or other struc-
ture in which vertical loads from floors and roofs are primarily
supported by walls.
FRAME STRUCTURE. A building or other structure in
which vertical loads from floors and roofs are primarily sup-
ported by columns.
1614.3 Frame structures. Frame structures shall comply with
the requirements of this section.
1614.3.1 Concrete frame structures. Frame structures
constructed primarily of reinforced or prestressed concrete,
either cast-in-place or precast, or a combination of these,
shall conform to the requirements of ACI 318 Sections 7.13,
13.3.8.5, 13.3.8.6, 16.5, 18.12.6, 18.12.7 and 18.12.8 as
applicable. Where ACI 318 requires that nonprestressed
reinforcing or prestressing steel pass through the region
bounded by the longitudinal column reinforcement, that
reinforcing or prestressing steel shall have a minimum nom-
inal tensile strength equal to two-thirds of the required
one-way vertical strength of the connection of the floor or
roof system to the column in each direction of beam or slab
reinforcement passing through the column.
Exception: Where concrete slabs with continuous rein-
forcing having an area not less than 0.001 5 times the con-
crete area in each of two orthogonal directions are
present and are either monolithic with or equivalently
bonded to beams, girders or colunms, the longitudinal
reinforcing or prestressing steel passing through the col-
umn reinforcement shall have a nominal tensile strength
of one-third of the required one-way vertical strength of
the connection of the floor or roof system to the column
in each direction of beam or slab reinforcement passing
through the colunm.
1614.3.2 Structural steel, open web steel joist or joist
girder, or composite steel and concrete frame structures.
Frame structures constructed with a structural steel frame or
a frame composed of open web steeljoists, joist girders with
or without other structural steel elements or a frame com-
posed of composite steel or composite steeljoists and rein-
forced concrete elements shall conform to the requirements
of this section.
1614.3.2.1 Columns. Each column splice shall have the
minimum design strength in tension to transfer the
design dead and live load tributary to the column
between the splice and the splice or base immediately
below.
1614.3.2.2 Beams. End connections of all beams and
girders shall have a minimum nominal axial tensile
strength equal to the required vertical shear strength for
allowable stress design (ASD) or two-thirds of the
required shear strength for load and resistance factor
design (LRfTD) but not less than 10 kips (45 kN). For the
purpose of this section, the shear force and the axial ten-
sile force need not be considered to act simultaneously.
Exception: Where beams, girders, open web joist and
joist girders support a concrete slab or concrete slab
on metal deck that is attached to the beam or girder
with not less than Vg-inch-diameter (9.5 mm) headed
shear studs, at a spacing of not more than 12 inches
(305 nrni) on center, averaged over the length of the
member, or other attachment having equivalent shear
strength, and the slab contains continuous distributed
reinforcement in each of two orthogonal directions
with an area not less than 0.0015 times the concrete
area, the nominal axial tension strength of the end
connection shall be permitted to be taken as half the
required vertical shear strength for ASD or one-third
of the required shear strength for LRFD, but not less
than 10 kips (45 kN).
1614.4 Bearing wall structures. Bearing wall structures shall
have vertical ties in all load-bearing walls and longitudinal ties,
transverse ties and perimeter ties at each floor level in accor-
dance with this section and as shown in Figure 1614.4.
1614.4.1 Concrete wall structures. Precast bearing wall
structures constructed solely of reinforced or prestressed
concrete, or combinations of these shall conform to the
requirements of Sections 7.13, 13.3.8.5 and 16.5 of ACI
318.
1614.4.2 Other bearing wall structures. Ties in bearing
wall structures other than those covered in Section 1614.4. 1
shall conform to this section.
1614.4.2.1 Longitudinal ties. Longitudinal ties shall
consist of continuous reinforcement in slabs; continuous
or spliced decks or sheathing; continuous or spliced
members framing to, within or across walls; or connec-
tions of continuous framing members to walls. Longitu-
dinal ties shall extend across interior load-bearing walls
and shall connect to exterior load-bearing walls and shall
be spaced at not greater than 10 feet (3038 mm) on cen-
ter. Ties shall have a minimum nominal tensile strength,
48
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
Tj, given by Equation 16-46. For ASD the minimum
nominal tensile strength shall be permitted to be taken as
1.5 times the allowable tensile stress times the area of the
tie.
Tt=wLS <ajS
where:
(Equation 16-46)
w
a.
= The span of the horizontal element in the direction
of the tie, between bearing walls, feet (m).
= The weight per unit area of the floor or roof in the
span being tied to or across the wall, psf (N/m^).
= The spacing between ties, feet (m).
= A coefficient with a value of 1 ,500 pounds per foot
(2.25 kN/m) for masonry bearing wall structures
and a value of 375 pounds per foot (0.6 kN/m) for
structures with bearing walls of cold-formed steel
light-frame construction.
1614.4.2.2 Transverse ties. Transverse ties shall consist
of continuous reinforcement in slabs; continuous or
spliced decks or sheathing; continuous or spliced mem-
bers framing to, within or across walls; or connections of
continuous framing members to walls. Transverse ties
shall be placed no farther apart than the spacing of load-
bearing walls. Transverse ties shall have minimum nomi-
nal tensile strength Tj^ given by Equation 16-46. For
ASD the minimum nominal tensile strength shall be per-
mitted to be taken as 1 .5 times the allowable tensile stress
times the area of the tie.
1614.4.2.3 Perimeter ties. Perimeter ties shall consist of
continuous reinforcement in slabs; continuous or spliced
decks or sheathing; continuous or spliced members
framing to, within or across walls; or connections of con-
tinuous framing members to walls. Ties around the per-
imeter of each floor and roof shall be located within 4
feet (1219 mm) of the edge and shall provide a nominal
strength in tension not less than T^, given by Equation
16-47. For ASD the minimum nominal tensile strength
shall be permitted to be taken as 1.5 times the allowable
tensile stress times the area of the tie.
r^=200w<|Jr
For SI:
r, = 90.7vy<P,
(Equation 16-47)
where:
w =
As defined in Section 1614.4.2.1.
A coefficient with a value of 16,000 pounds
(7200 kN) for structures with masonry bearing
walls and a value of 4,000 pounds (1300 kN) for
structures with bearing walls of cold-formed
steel light-frame construction.
1614.4.2.4 Vertical ties. Vertical ties shall consist of
continuous or spliced reinforcing, continuous or spliced
members, wall sheathing or other engineered systems.
Vertical tension ties shall be provided in bearing walls
and shall be continuous over the height of the building.
The minimum nominal tensile strength for vertical ties
within a bearing wall shall be equal to the weight of the
wall within that story plus the weight of the diaphragm
tributary to the wall in the story below. No fewer than two
ties shall be provided for each wall. The strength of each
tie need not exceed 3,000 pounds per foot (450 kN/m) of
wall tributary to the tie for walls of masonry construction
or 750 pounds per foot (140 kN/m) of wall tributary to
the tie for walls of cold-formed steel light-frame con-
struction.
2010 CALIFORNIA BUILDING CODE
49
STRUCTURAL DESIGN
FIGURE 1613.5(1)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
50
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
FIGURE 1613.5(1)— continued
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
2010 CALIFORNIA BUILDING CODE
51
STRUCTURAL DESIGN
vtasionsofthisinapaiidotheis. Documentation, giidded
values, and Aic/M'O coverages used to mafce the maps
are also available.
The Califtnnia portion of the map was produced jointly
with the Calilbmia Geological Survey.
Map pnepared by U.S. Geological Survey.
- Region 1 is shown enlai^ged in figure 1 61 3.5(4)
- Region 2 is strawn enlarged in figure 1 61 3.5(6)
- Region 3 is shown enlarged in figure 1 61 3.5(3)
- Re^on 4 is shown enlaiged in figure 1 61 3.5(9)
FIGURE 1613.5(2)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES
OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
52
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1 00 100 200 300 400 500 6 00 KILOMETERS
M M M 1 I I 1 I ZU
FIGURE 1613.5(2)— continued
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES
OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
2010 CALIFORNIA BUILDING CODE
53
en
•1^
ro
o
o
O
>
O
33
Z
>
w
c
l-
g
z
Q
O
O
O
m
H
u
c
o
33
>
r-
D
m
CO
O
FIGURE 1613.5(3)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
o
o
O
>
O
D
Z
>
01
c
o
o
o
o
m
ConUmr intervals, % g
Note ccaaiouis are iiregdarfy spaced
Areas with a constant spectral
respcw6eacceteiad(HiofI50% g
Point vsim of specteil Ji^ponse
acceleratic "
of^vity.
Contouis of spectra] respcsise
acceleration ex|»essed as a jaeicera
of gravity. Hactmres point in
direction of ttecneasing values.
Locations of feults (see DISCUSSION).
Tte number on the fault is to
median spectral lesponse acceleration
times 1 .5, expaessed as a perc«it of
DISCUSSION
A One shown as a fault location is the piBJection to the earth's
sujfeie of the edge of the fault rapture aiea iocalfid closest to
die earth's surface. OnlytfiepotticHioftheiaultusedin
stetertiBning design values is shown. Ihsmrnifeei-onthefaultisthe
detendnistic median s^tral response acceleration times 1 ,5, The
vai ues on the fault portion shown may be used for inteipolation
ptuposes.
Selected contotiis Dsax feults have been deleted for clarity, in
these i«stancffi, interpolation amy bft done usiag feult values and the
nearest adjacent contour.
Refer to the nmj of ?Haxinium Considered EaidiquakB Qiound
MsMionfortheContermiiwus United States of (12 .">ec Spectral
Response Acceleration (R^ire 1 61 3.^1 )) foradc£tional discussion
and references.
FIGURE 1613.5(3)— continued
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
CO
H
3)
C
o
H
C
>
r
o
m
CO
o
o
o
>
O
Z
>
CD
C
21
c
o
H
C
>
r-
o
m
CO
o
o
o
O
D
m
FIGURE 1613.5(4)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
• •
o
O
\ \l\ A
Contour intervals, % g
Note contDtus arc inegulady spaced
Aieas nith a cotBtanl spectral
icsponse acceleration of 60% g
Ftoint value of spectral response
acceleration exptesscd as a peicei
of gravity
Contoius of spectral response
acceleration ejqnessed as a peiceid
of gravity. Hachmes point in
diiectiaa of decieasing values.
Locations of faults (see DISCUSSION).
The number on the fault is tte
median spectral [espouse acceleration
timas 1 .5, expressed as a peucentof
gravity.
DISCUSSION
A line shown as a fault location is the projection to ^ earth's
surface of the edge of tfie &ult nqituie area located closest to
the earth' ssufiice. Only the portion ofthe fault used in
deteimining design values is sbown The number on tls fault is the
deterministic median spectral response acceleration times 1.5, The
values on the &ult portion shown may be used for inteipolation
Selected contouisnearfaults have been deleted for clarity. In
these instances, interpolation may be done using feult values and the
nearest adjacent contour.
Refer 10 the map of Maximum Considefed Earthquake Gfotmd
Motion for the Comemiinous United States of 1 ,0 sec Spectral
Response Acceleration (Rgure 1 61 3.5(2)) f ' ' " ' '
and lefciences,
H
c
o
FIGURE 1613.5(4)— continued
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
33
>
|-
O
m
CO
o
lO
o
o
O
>
O
3)
Z
>
C
I I I I :
Eiqplanation
Contour intervals, % g
55
C
o
>
a
m
CO
z
Nole contoiKS are inegulariy spaced
+
R)U]t value of spectral nesponse
acceleration ex;«Essed as a pcicent
of gravity
Contoins of spectral response
acceleiation e^aessed as a peicrait
of gravity. Hachunss point in
direction of decreasing values.
Refer to the map of Maximum Considered Earthquake Ground
Motion for the Contemiinous United States of a2 sec Spectral
Response Acceleration (Hguie 1 61 3.5(1 )) for discission and
100 KILOMETERS
Index map showing location of study atea
o
o
o
a
m
FIGURE 1613.5(5)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 2 OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
o
O
>
■n
O
z
>
CD
C
o
o
o
a
m
100
I I
100 KILOMETERS
Explanation
Contour intervals, % g
Note contouis are iiiegulariy spaced
Point value of spectra] lesponse
acceleration expressed as a percent
of gravity
Contouis of spectra] response
acceleration expressed as a percent
of gravity, Hachures point in
diiecdon of decreasing values.
Refer to the map of Maximum Considered Earthquake Ground
Motion for the Qinternunous United States of 1 .0 sec Spectral
Response Acceleration (Rguie 1 61 3.5(2)) for discussion and
Index map showing location of study aiea
CJI
FIGURE 1613.5(6)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 2 OF
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
C/>
H
c
c
>
r-
a
m
(n
Q
Z
o
o
O
>
O
33
Z
>
m
a
z
o
o
o
D
m
100 KILOMETERS
CtHitotir into-vals, % g
Note contDinsaieinegulariy spaced
Aieas \Mth a constant spectral
iBsponse acceleiatbn of 1 S0% g
PouA value of spectral response
acceleration exjnessed as a percent
of gravity
ConlDuis of spectral response
acceleration expessed as a percent
ofgiavi^. Hactnnes point in
diKction of decicasing values.
Refer to the map of Maximuni Consideied Eaitfaquake Gmund
Motion for the Contemdiious United States of 0l2 sec Spectral
Response Acceleration (Rgme 1 61 3.5(1 )) for discussion and
Index map showing location of study area
FIGURE 1613.5(7)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 3 OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% PERCENT OF CRITICAL DAMPING), SITE CLASS B
53
3)
C
o
H
C
D
>
r-
a
m
o
lO
o
o
O
>
O
Z
>
00
o
o
o
a
m
H I ^31
100 KILOMETCRS
Contour intervals, % g
aie inegulaily spaced
I Areas with a ctmstaitt spectral
Paint value of spectral lesponse
acceleration eJquressed as a peicent
of gravity
Contoius of spectral response
acceleration expressed as aperct
of gravity. Haouires point in
diiection of ctecieasing values.
Refer to the map of Maximum Considered Earthquake Giound
Motion for tiie Conterminous United States of 1 .0 sec Spectral
Response Acceleration (Figure 1 61 3.5(2)) for discussion and
Pl^iinp 1 fti Q Rffl\ Index map showing location of study area
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 3 OF
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
H
3J
C
o
H
C
J)
>
I"
o
m
CO
o
STRUCTURAL DESIGN
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
+
6.2
Explanation
Point value of spectral response
acceleration expressed as a peicent
of gravity
Contoms of spectral lesponse
acceleration expiessed as a peicent
of gravity, Hachuies point in
diiecdon of decreasing values.
DISCUSSION
Refer to the maps of Maximum ConsideiedEaithqualQe Ground
Motion for the Q>ntenninous United States of Q2 and 1 .0 sec
Spectral Response Acceleratian (Hgures 1 61 3.5(1 ) and 1 61 3.5(2))
for discussion and refeiences.
100 KILOMETERS
Index map showing location of study aiea
FIGURE 1613.5(9)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 4 OF
0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
62
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
Contoiir intervals, % g
-200-
-175-
-150-
-125-
-100-
-90-
-80-
-70-
-60-
-50-
-40-
-35-
-30-
-25-
-20-
-15-
-10-
Note contousaie
ineculailv scaced
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
160°
Contour intervals, % g
150
125
100-
90-
75-
60-
50-
-25-
-20-
-15-
-10-
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
^ Paict value of spectral nsponse
f-j acceleration expiessed as a percent
'^^ of gravity
ContDuis of spectral iBspcmse
acceleration expitcssed as a percent
of gravity. Hachuies point in
diiection of decnsasing values.
DISCUSSION
The accderation values c»n!Duied on this tnap aie for the random hcnizontal
component of acceleratioa Fardesignpmposes, the lefeience site conditicm
for lie map is to be taken as Site Class B.
The two aieas shown as zone boundaries aie the projection to the eaitli's
sutface of horizontal niptuiejdanes at 9 km depth. Spectral accelerations
aieconstantwithtnthe boundaries of the zones. The number on the boundary
and inside the zone is the median spectral response acceleration times 1 .5.
Leyendecker, Rrankel, and Rukstates (2001 , 2004) have prepaied a CI>-ROM
that contains software to allow detemtination of Site Class B map values by
Mtude-longitude, The softwaie on the CD contains site coefficients that
allow the userto adjust mapvaluesfbrdifierentSiteClasses. Additional
maps at different scales aie also included on the CD. The CD was piepored
using tlie same data as (hat used to prepare the Maximum Considered Eaithquake
GfDund Motion maps.
TTie National Seismic Hazard Mappng Pnsject Web Site,
http //eqhazmapB. usgs.gov, contains electronic veraions of this map
andotheis. Documentation, gridded values, and Aic/INTO coverages used
to make the maps are also av^lahle.
Map prepBied by U.S. Gedogtcal Survey.
Areas with a constant spectra]
response acceleration of 1 50% g
m
(se
The number on the boundaiy and
inside the zone is the median
spectral response acceleration
times l.S, expressed as a
percent of gravity.
Areas with a constant spectral
response acceleration of 60% g
m
Localioiis of detemtinistic zone
boundaries (see DISCUSSION>
The number on the boundaiy and
inside the zone is the median
spectral RspfflBe acceleration
times 1 .5, expressed as a
petcent of gravity.
200 KILOMETERS
Building Seismic Safety Council 200*, NEHRP Reconnnended Provisions for Seismic
RegulatioiB for New Buildings and other Structures, E^ 1 - Provisions, FEMA 450l
Building Seismic Safety Council 2004, NEHRP Reconrnended Provisions for Seismic
Regulations for New Buildings and other Structures, Part 2 - Cwnnientaiy, FEMA 45Q
Klein, P., Frankel, A., Muellei; C, Wesson, R and Okubo, P., 2001 , Seismic hazaid
in Hawaii high rate of lai«e earthcnskes and piobabilistic gtound-motion maps.
Bull Seism Soc. Am, v. M, j^ 479^98.
Klein, F., Frankel, A., MueUei; C. Wesson, R and Okubo. R, 1 99S, Seismic-Hazard Maps
fe Hawaii, Sheet 2 -2% PtobahilityofExceedance in 50 Yeare for Rak Horizontal
Acceleration and Horizontal Spectral Response Acceleration for a2, 0.3, and 1 .0 Second
ftriods U.S. Geological Survey Geologic Investi^an Series 1-2724, scale 1 :2,000l,00a
Leyendecker, E, Frankel, A., and Rukstales, K., 2001 , Seismic Design Ruameteis, US.
Geological Survey Open-File Report 01 -437.
Leyendecker, E., Firankel, A., aixl Rukstales, K., 2004, Seismic Design Puameleis, U.S.
u:
[Seismic mzard Majqnng Project Web Site, http /ABqhazinap6.u5gs.gov,
L Geological Survey.
FIGURE 1613.5(10)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR HAWAII OF
0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
2010 CALIFORNIA BUILDING CODE
63
lO
o
O
>
-n
O
X
z
>
w
c
I-
o
£3
3}
C
o
H
C
>
r-
o
m
(0
O
z
Building Seismic Safety Council 2004, NHIRP Recoiimieiided PtovisicHis for Seismic
' s for New Buildings and other StmctuEs, I^ 1 -nDvisions,FEMA450L
g Seismic Safety Council 2004, NEHRP ReconunEaded Provisions for Seismic
Regulations for New Building and other Structuns, F^ 2 - Commenlaiy, FEMA 45Q
LeyendeekEr, E, Rankel, A., and Rukstales, K., 20Q1 , Seismic Etesign ftiamcteis, U.S.
Geological Survey Open-file Report 01 -437,
Leyendecker, E, Ranfcel, A., and Rukstales, K., 2004, Seismic Design Ptouneteis, U.S.
Geological Survey Opcn-Rle Report (in piogiessX
National Seismic Hazard Mapping Roject Web Site, http/^et^iazmaps. usgs.gov,
U. S. Geological Survey.
Wesson, R., Frankel, A., Mueller, C, and Hannsen. S., 1 999, Prohahilistic Seismic Hazard
Maps of Alaska, U.S Geoloacal Survey Open-Hie Rgiott 99-36
Wesson. R, Frankel, A, Mueller, C, and Hannsen, S., 1 998, Seismic-Hazaid Maps for
Alaska and die Aleutian Islands, Sheet 2 -2% Probability ofExceedarKc in 50 Years
for Peak Horizontal Acceleration and Horizontal Spectral Response Acceleration for 0l2,
a 3, and 1 .0 Second Periods US. Gcolopcal Survey Geologic Investigalion Series 1-2679,
scale l:7,50a00Q
L
750 KILOMETERS
o
o
o
a
m
FIGURE 1613.5(11)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR ALASKA OF
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
to
o
O
>
O
13
Z
>
C
f-
D
Z
o
o
o
a
m
Bmlding Seismic Safety Council 2004, NEHRP RecommeiKted Provisions for Seismic
Regulations for New Buildings and other Stnictiires, ftit 1 - Provisions, FEMA 450L
Building Seismic Safety Council 2004, NEHRP Recommended Provisions for Seismic
Regulations for New Buildings and other Stnicturcs, Part 2 - Commentaiy, FEMA 45Q
Leyendecker, E, Frankel, A., and Rukstales, K., 2001 , Seismic Design Rarameteis, US.
Geological Survey Open-File Report 01 -437,
Ley^ndaker, E, I^uikel, A., and Rukstales, K,, 2004, Seismic Design Parameters, U.S.
Geological Survey Open-File Report (in progress).
National Seismic Hazard Mapping ftoject Web Site, httpc//eqhazmaps.i]sgs.gov,
U. S. Geological Survey.
Wesson, R, Frankel, A, Muellei; C, and Haraisen, S., 1 999, Probabilistic Seismic Hazard
Maps of Alaska, U.S. Geological Survey Open-Hie Repmt 99-36.
Wesson, R, Franlffil, A., Mueller, Q, and Haimsen, S., 1 998, Seismic-lfezanl Maps for
Alaska and the Aleutian Islands, Sheet 2 - 2% Probability of Exceedance in 50 Yeais
for Peak Horizontal Acceleration and Horizontal Spectml Response Acceleration for 0.2,
03, and 1.0 Second Psriods U.S. Geological Survey Geologic Investigation Series 1-2679,
scale 1:7,500,000
^,
750 KILOMETERS
CJI
FIGURE 1613.5(12)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR ALASKA OF
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
CO
H
JJ
C
o
H
C
J}
>
r-
a
m
CO
O
STRUCTURAL DESIGN
0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
C<Hitour intervals, % g
150
125
100
90
60
40
30
20
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
+
6.2
10
10
Paint value of spectral response
acceleration expiessed as a peicent
ofgjavity
Contouis of spectral response
acceleration expressed as a percent
of gravity. Hachures point in
direction of decreasing values.
DISCUSSION
The acceleration values contoured on this map are for the random horizontal
ccHiqxinent of acceleration. Por design purposes, the reference site condition
for the niap is to be taken as Site Class B.
Leyendeckei; Franfcel, and Rukstales (2001 , 2004) have prepared a CD-ROM
that contains software to allow detemiination of Site Class B map values by
latitiide'longitiid& The software on the CD contains site coefficients that
allow die user to adjust map values for different Site Qasses. Additional maps
at different scales are also included on the CD. lite CD was prepared using die
sane data as diatused to prepare the Maximum Considered Eardiquake Ground
Motion maps.
The National Seismic Hazard Mappbg Ptoject Web Site,
tdtp//eqhazmaps.usgs.gov, caotains electtonic veisioiis of this map
andothets. Documentadon, ^dded values, and Arc/INFO coverages used
to make the maps are also available.
Map prepared by U.S. Geological Survey.
KILOMETERS
Building Seismic Safety Council 2004, NEHRP Recommended Provisions for Seismic
Regulations for New Buildings and other Structures, I^ 1 - Provisions, FEMA 45Q
Building Seismic Safety Council 2004, NEHRP Recommended Provisions for Seismic
Regulations for New Building? and other Structures, ftit 2 - Commentary, FEMA 450i
Leymdeclcer, E, Frankel, A, and Rukstales, K., 2001 , Seismic Design I^iaraeteis, U.S.
Geological Survey Open-File Report 01 -437.
Leyendecker, E, Piankel, A, and Rukstales, K., 2004, Seismic Design Ratameteis, U.S.
Geological Survey Opm-Rle Report (in progress).
Mueller; C, Rankel, A., I^teisea M, and Leyendeckiei; E, 2003, Documentation for
2003 uses Seismic Hazard Maps for Puerto Rico and the U.S. Virgin Islands, US.
Geolo^cal Survey Open-Rle Report 03-379.
Muellei; C, Franfcel, A.. Pcteisen, M, and Leyendecker, E, 2004, Seismic-Hazaid Maps
for Pierto Rico and the US. Vii^ Island, Sheet 2 - 2% Plobability of
Exoeedance in 50 Years for Fsak Horizontal Acceleration and Honzontal Spectral
Response Acceleration for 0l2, Q3, and 1 .0 Second ftriods U.S. Geological Survey
Geologic Investigadon Series (in progress).
National Seismic Hazard Mappng Pttjject Web SitCj htqx /Aeqhazmapa.usgs. gov,
U.S. Geologicai Survey.
FIGURE 1613.5(13)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR PUERTO RICO, CULEBRA, VIEQUES, ST. THOMAS,
ST. JOHN AND ST. CROIX OF 0,2 AND 1,0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
66
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
150% g
GUAM
(UNITED STATES)
r\
..^^
DISCUSSION
LeyeiKieck»;Bank£!, and Rukstales (2001, 2094) have pcep^a€1>-R0M (hat contains
software to allow detominatinn of Site Class B de^ values by either Mtwte-longitiKte or
»pcoda The softwanj cm the CT)cotaaim site coeffidcmsffiat allow the user to ad^
map values for diffieiBntSiteCaasses,
Nfap ptepaiBd by US. Geologjcal Survey.
100% g
/' TUTUILA
/ , (UNITED STATES)
a2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
^cg
/"\
x;y
J::^
GUAM
(UNITED STATES)
REFERE^^iCES
Building Seismic Safety Council ^)04, NBKRP Recommeodbd IVtn^^ons forSmcmc Kegulatioas
for New Buildin£^ and other Structtaes,!^] -Plovtsioie,FEMA45Q.
Building Seismic Safety Council 2004, NEHRPaecommencbd Ptovjsions fw Seismic ReguktkMU
for New BiuJdu^ and otherSmxmjnes, F^ 2 - GommndBiy, FEMA 4S(X
Leyendecker, E, mnkel, A. and Rakstales, K., 20tM , Seisone Design I^ratnetws, US. Geolo©cal
SurweyC^«n-Eile Report 01 -437.
Leyendecker. E, Bunkel, A. and Rulst^es, K, :KXM, SeisiiHC Des^ Ruani«e«s, MS. Geological
Survey O^it-Rle Reprat (in [xogjssssjL
National Seismic Hazanl Mailing Ptoject Wd» Site, httpi//eqha2mapfiLiB^gt3rv,
US. Geotogjcal Sorwy.
•'o%
/ TUTUILA
./ (UNITED STATES)
144P45' K5*0(yE ITt'Off 11
10 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING)
25 KItOMETERS
FIGURE 1613.5(14)
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR GUAM ANDTUTUILLA OF
0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
2010 CALIFORNIA BUILDING CODE
67
STRUCTURAL DESIGN
T = Transverse
L = Longitudinal
V = Vertical
P = Perimeter
FIGURE 1614.4
LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES
68
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
^
SECTION 1615
ADDITIONAL REQUIREMENTS [DSA-SS/CC]
161 5 J Construction documents,
1615 A A Additional requirements for construction docu-
ments are included in Sections 4-210 and 4-317 of the
Building Standards Administrative Code (Part 7, Title 24,
C.CR).
1615.1.2 Connections, Connections that resist design seis-
mic forces shall be designed and detailed on the design
drawings.
1615.1.3 Construction procedures. Where unusual erec-
tion or construction procedures are considered essential by
the project structural engineer or architect in order to
accomplish the intent of the design or influence the design,
such procedure shall be indicated on the plans or in the
specifications.
1615.2 General design requirements,
1615,2,1 Lateral load deflections,
1615.2.1.1 Horizontal diaphragms. The maximum
span-width ratio for any roof or floor diaphragm shall
not exceed those given in Table 2305.2 or Table 4.2,4 of
AF 6c PA SDPWS for wood sheathed diaphragms. For
other diaphragms, test data and design calculations
acceptable to the enforcement agency shall be submitted
and approved for span-width ratios.
1615.2.1.2 Veneers. The deflection shall not exceed the
limits in Section 1405.10 for veneered walls, anchored
veneers and adhered veneers over 1 inch (25 mm) thick,
including the mortar backing.
1615.2.1.3 Occupancy Category of buildings and other
structures. Occupancy Category IV includes structures
as defined in C.CR, Title 24, Part 1, Section 4-207 and
all structures required for their continuous operation or
access/egress.
1615.3 Load combinations,
1615.3.1 Stability, When checking stability under the provi-
sions of Section 1605.1.1 using allowable stress design, the
factor of safety for soil bearing values shall not be less than
the overstrength factor of the structures supported.
1615.4 Roof dead loads. The design dead load shall provide
for the weight of at least one additional roof covering in addi-
tion to other applicable loadings if the new roof covering is
permitted to be applied over the original roofing without its
removal, in accordance with Section 1510.
1615.5 Live loads.
1615.5.1 Modifications to Table 1607,1.
1615.5.1,1 Item 4. Assembly areas and theaters. The
following minimum loads for stage accessories apply:
1. Gridirons and fly galleries: 75 pounds per square
foot uniform live load.
2. Loft block wells: 250 pounds per lineal foot verti-
cal load and lateral load.
3. Head block wells and sheave beams: 250 pounds
per lineal foot vertical load and lateral load. Head
block wells and sheave beams shall be designed
for all tributary loft block well loads. Sheave
blocks shall be designed with a safety factor of five.
4. Scenery beams where there is no gridiron: 300
pounds per lineal foot vertical load and lateral
load.
5. Ceiling framing over stages shall be designed for a
uniform live load of 20 pounds per square foot.
For members supporting a tributary area of 200
square feet or more, this additional load may be
reduced to 15 pounds per square foot (0.72
kN/m^).
The minimum uniform live load for a press box floor or
accessible roof with railing is 100 psf
1615.5.1.2 Item 22. Libraries. The minimum vertical
design live load shall be as follows:
Paper media:
12-inch-deep (305 mm) shelf- 33 pounds per lin-
eal foot (482 N/m)
15 -inch-deep (381 mm) shelf- 41 pounds per lin-
eal foot (598 N/m), or
33 pounds per cubic foot (51 83 N/m ) per total vol-
ume of the rack or cabinet, whichever is less.
Film media:
18-inch-deep (457 mm) shelf- 100 pounds per lin-
eal foot (1459 N/m), or
50 pounds per cubic foot (7853 N/rn) per total vol-
ume of the rack or cabinet, whichever is less.
Other media:
20 pounds per cubic foot (311 N/m^) or 20 pounds
per square foot (958 Pa), whichever is less, but not
less than actual loads.
1615.5.1.3 Item 25. Office buildings. The minimum ver-
tical design live load shall conform to Section
1615.5.1.2.
1615.5.1.4 Item 28, Reviewing stands, grandstands and
bleachers. The minimum uniform live load for a press
box floor or accessible roof with railing is 100 psf.
1615.5.1.5 Item 40. Yards and terraces, pedestrians.
Item 40 applies to pedestrian bridges and walkways that
are not subjected to uncontrolled vehicle access.
1615.5.1.6 Item 41. Storage racks and wall-hung cabi-
nets. The minimum vertical design live load shall con-
form to Section 1615.5.1.2.
1615.5.2 Uncovered open-frame roof structures. Uncov-
ered open-frame roof structures shall be designed for a ver-
tical live load of not less than 10 pounds per square foot
(0.48 kN/rn^) of the total area encompassed by the frame-
work.
2010 CALIFORNIA BUILDING CODE
69
STRUCTURAL DESIGN
1615.6 Determination of snow loads. The ground snow load or
the design snow load for roofs shall conform with the adopted
ordinance of the city^ county, or city and county in which the
project site is located, and shall be approved by DSA.
1615.7 Wind loads,
1615.7.1 Special wind regions. The basic wind speed for
projects located in special wind regions as defined in Figure
1609 shall conform with the adopted ordinance of the city,
county, or city and county in which the project site is
located, and shall be approved by DSA-SS/CC.
1615.7.2 Story drift for wind loads. The calculated story
drift due to wind pressures shall not exceed 0.005 times the
story height for buildings less than 65 feet (19 812 mm) in
height or 0,004 times the story height for buildings 65 feet
(19 812 mm) or greater in height,
1615.8 Establishment of flood hazard areas. Flood hazard
maps shall include, at a minimum, areas of special flood haz-
ard as identified by the Federal Emergency Management
Agency 's Flood Insurance Study (FIS) adopted by the local
authority having jurisdiction where the project is located, as
amended or revised with the accompanying Flood Insurance
Rate Map (FIRM) and Flood Boundary and Floodway Map
(FBFM) and related supporting data along with any revisions
thereto,
1615.9 Earthquake loads,
1615.9.1 Seismic design category. The seismic design cate-
gory for a structure shall be determined in accordance with
Section 1613,
1615.9.2 Definitions, In addition to the definitions in Sec-
tion 1613.2, the following words and terms shall, for the
purposes of this section, have the meanings shown herein.
ACTIVE EARTHQUAKE FAULT, A fault that has been the
source of earthquakes or is recognized as a potential source
of earthquakes, including those that have exhibited surface
displacement within Holocene time (about 11,000 years) as
determined by California Geological Survey (CGS) under
the Alquist-Priolo Earthquake Fault Zoning Act, those
included as type A or type B faults for the U.S. Geological
Survey (USGS) National Seismic Hazard Maps, and faults
considered to have been active in Holocene time by an
authoritative source, federal, state or local governmental
agency,
BASE, The level at which the horizontal seismic ground
motions are considered to be imparted to the structure or the
level at which the structure as a dynamic vibrator is sup-
ported. This level does not necessarily coincide with the
ground level.
DISTANCE FROM AN ACTIVE EARTHQUAKE
FAULT, Distance measured from the nearest point of the
building to the closest edge ofan Alquist-Priolo Earthquake
fault zone for an active fault, if such a map exists, or to the
closest mapped splay of the fault,
IRREGULAR STRUCTURE. A structure designed as hav-
ing one or more plan or vertical irregularities per ASCE 7
Section 12.3.
NEXT GENERATION ATTENUATION (NGA). Attenua-
tion relations used for the 2008 United States Geological
Survey (USGS) seismic hazards maps (for the Western
United States) or their equivalent as determined by the
enforcement agency.
STRUCTURAL ELEMENTS, Floor or roof diaphragms,
decking, joists, slabs, beams, or girders, columns, bearing
walls, retaining walls, masonry or concrete nonbearing
walls exceeding one story in height, foundations, shear
walls or other lateral-force-resisting members, and any
other elements necessary to the vertical and lateral strength
or stability of either the building as a whole or any of its
parts, including connection between such elements.
1615.9.3 Mapped acceleration parameters. Seismic
Design Category shall be determined in accordance with
Section 1613,5.6.
1615.9.4 Determination of seismic design category. Struc-
tures not assigned to Seismic Design Category E or F in
accordance with Section 1613.5 shall be assigned to Seis-
mic Design Category D.
1615.9.4.1 Alternative seismic design category determi-
nation. The alternative Seismic Design Category deter-
mination procedure of Section 1613,5.6.1 is not
permitted by DSA-SS/CC.
1615.9.4.2 Simplified design procedure. The simplified
design procedure of Section 1613,5.6.2 is not permitted
by DSA-SS/CC
1615.9.5 Automatic sprinkler systems. The allowable val-
ues for design of anchors, hangers and bracing elements
shall be determined in accordance with material chapters of
this code in lieu of those in NFPA 13.
1615.9.6 Anchorage of walls. The modification of ASCE 7,
Section 11.7.5 in Section 1613,7 not adopted by DSA-SS/
CC
1615,10 Modifications to ASCE 7, The text of ASCE 7 shall be
modified as indicated in Sections 1615,10.1 through
1615,10.26.
1615.10.1 ASCE 7, Section 11,1, Modify ASCE 7 Section
11,1 by adding Section 11.1.5 as follows :
11,1,5 Structural design criteria. Where design reviews
are required in ASCE 7, Chapters 16, 17 or 18, the
ground motion, analysis and design methods, material
assumptions and acceptance criteria proposed by the
engineer shall be submitted to the enforcement agency in
the form of structural design criteria for approval.
1615.10.2 ASCE 7, Section 11,4,7, Modify ASCE 7 Section
11.4.7 as follows:
11,4,7 Site-specific ground motion procedures. The
site-specific ground motion procedure set forth in ASCE
7 Chapter 21 as modified in Section 1803 A. 6 of this code
is permitted to be used to determine ground motion for
any structure.
Unless otherwise approved, the site-specific proce-
dure per ASCE 7 Chapter 21 as modified by Section
70
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
I803A.6 of this code shall be used where any of the fol-
lowing conditions apply:
1) A site response analysis shall be performed per
Section 21,1 and a ground motion hazard analysis
shall be performed in accordance with Section
21.2 for the following structures:
a) Structure located in Type E soils and
mapped MCE spectral acceleration at short
periods (SJ exceeds 2.0g.
b) Structures located in Type F soils.
Exception:
1) Where S^ is less than 0.20g, use of
Type E soil profile shall be permitted.
2) Where exception to Section 20.3.1 is
applicable except for base isolated
buildings.
2) A ground motion hazard analysis shall be per-
formed in accordance with Section 21.2 when:
a) A time history response analysis of the
building is performed as part of the design.
b) The building site is located in an area identi-
fied in Section 4-3 17(e) of the California
Administrative Code (Part 7, Title 24,
C.C.R).
c) For seismically isolated structures and for
structures with damping systems.
1615 JO J ASCE 7, Table 12.2 -1, Modify ASCE 7 Table
12.2-1 as follows:
A. BEARING WALL SYSTEMS
14. Light-framed walls with shear panels of all other
materials - Not permitted by DSA-SS/CC.
B, BUILDING FRAME SYSTEMS
24. Light-framed walls with shear panels of all other
materials - Not permitted by DSA-SS/CC.
Exception:
1) Systems listed in this section can be used as an
alternative system when pre-approved by the
enforcement agency.
2) Rooftop or other supported structures not
exceeding two stories in height and 10 percent
of the total structure weight can use the systems
in this section when designed as components
per ASCE 7 Chapter 13.
3) Systems listed in this section can be used for
seismically isolated buildings when permitted
by Section 1613.6.2.
1615.10.4 ASCE 7, Section 12.2.3.L Modify ASCE 7 Sec-
tion 12.2.3.1 by adding the following additional require-
ments for a two stage equivalent lateral force procedure or
modal response spectrum procedure:
e. Where design of elements of the upper portion is gov-
erned by special seismic load combinations, the spe-
cial loads shall be considered in the design of the
lower portions.
1615.10.5 ASCE 7, Section 12.3.3. Modify ASCE 7 Section
12.3.3.1 as follows:
12.3.3.1 Prohibited horizontal and vertical irregulari-
ties for Seismic Design Categories D through E Struc-
tures assigned to Seismic Design Category EorF having
horizontal structural irregularity Type lb of Table 12.3-1
or vertical structural irregularities Type lb, 5a or 5b of
Table 12.3-2 shall not be permitted. Structures assigned
to Seismic Design Category D having vertical irregular-
ity Type lb or 5b of Table 12.3-2 shall not be permitted.
1615.10.6 ASCE 7, Section 12.7.2. Modify ASCE 7 Section
12.7.2 by adding Item 5 to read as follows:
5. Where buildings provide lateral support for walls
retaining earth, and the exterior grades on opposite
sides of the building differ by more than 6 feet (1829
mm), the load combination of the seismic increment of
earth pressure due to earthquake acting on the higher
side, as determined by a Geotechnical engineer quali-
fied in soils engineering, plus the difference in earth
pressures shall be added to the lateral forces pro-
vided in this section.
1615.10.7 ASCE 7, Section 12.8.7. Modify ASCE 7 Section
12.8.7 by replacing Equation 12.8-16 as follows:
d=-
VhC,
(12.8-16)
1615.10.8 ASCE 7, Section 12.9.4. Replace ASCE 7 Sec-
tion 12.9.4 as follows:
12.9.4 Scaling design values of combined response.
Modal base shear shall not be less than the base shear
calculated using the equivalent lateral force procedure
of Section 12.8.
1615.10.9 ASCE 7, Section 12.13.1. Modify ASCE 7 Sec-
tion 12.13.1 by adding Section 12.13.1.1 as follows:
12.13.1.1 Foundations and superstructure-to-founda-
tion connections. The foundation shall be capable of
transmitting the design base shear and the overturning
forces from the structure into the supporting soil. Stabil-
ity against overturning and sliding shall be in accor-
dance with Section 1605.1.1.
In addition, the foundation and the connection of the
superstructure elements to the foundation shall have the
strength to resist, in addition to gravity loads, the lesser
of the following seismic loads:
1. The strength of the superstructure elements
2010 CALIFORNIA BUILDING CODE
71
STRUCTURAL DESIGN
2. The maximum forces that would occur in the fully
yielded structural system
3. Forces from the Load Combinations with
overstrength factor in accordance with ASCE 7
Section 12.43.2
Exceptions:
1. Where referenced standards specify the
use of higher design loads.
2. When it can be demonstrated that inelas-
tic deformation of the foundation and
superstructure-to-foundation connection
will not result in a weak story or cause
collapse of the structure.
3. Where basic structural system consists of
light-framed walls with shear panels.
Where the computation of the seismic overturning
moment is by the equivalent lateral-force method or the
modal analysis method, reduction in overturning moment
permitted by Section 12.13.4 of ASCE 7 may be used.
Where moment resistance is assumed at the base of the
superstructure elements, the rotation andflexural defor-
mation of the foundation as well as deformation of the
superstructure-to-foundation connection shall be consid-
ered in the drift and deformation compatibility analyses.
1615.10.10 ASCE 7, Section 13.1.4. Replace ASCE 7 Sec-
tion 13.1.4 by the following:
1 3. L4 Exemptions. The following nonstructural compo-
nents are exempt from the requirements of this section:
1. Furniture (except storage cabinets as noted in
Table 13.5-1),
2. Temporary or moveable equipment.
Exceptions:
1) Equipment shall be anchored if it is perma-
nently attached to the building utility ser-
vices such as electricity, gas, or water. For
the purposes of this requirement, "perma-
nently attached'' shall include all electrical
connections except three-prong plugs for
duplex receptacles.
2) The enforcement agency shall be permitted
to require temporary attachments for mov-
able equipment which is usually stationed in
one place and heavier than 400 pounds,
when they are not in use for a period longer
than 8 hours at a time,
3. Mechanical and electrical components in Seismic
Design Categories D, E or F where all of the fol-
lowing apply:
a. The component is positively attached to the
structure;
b. Flexible connections are provided between
the component and associated ductwork,
piping and conduit; and either:
i. The component weighs 400 lb (1780
N) or less and has a center of mass
located 4 ft (1.22 m) or less above the
adjacent floor or roof level;
Exception: Special Certification
Requirements for Designated Seis-
mic Systems in accordance with
Section 13,2.2 shall apply.
or
a. The component weighs 20 lb (89 N) or
less or, in the case of a distributed sys-
tem, 5 lb/ft (73 N/m) or less.
Exception: The enforcement
agency shall be permitted to
require attachments for equipment
with hazardous contents to be
shown on construction documents
irrespective of weight.
1615.10.11 ASCE 7, Section 13.3.2. Modify ASCE 7 Sec-
tion 13.3.2 by adding the following:
The seismic relative displacements to be used in design
of displacement sensitive nonstructural components is
Dp 1 instead of Dp, where Dp is given by Equations 13.3-5
to 13,3-8 and 1 is the building importance factor given in
Section 11,5.
1615.10.12 ASCE 7, Section 13.4.5. Replace ASCE 7 Sec-
tion 13.4.5 by the following:
13.4.5 Power actuated fasteners. Power actuated fasten-
ers in concrete shall not be used for gravity tension loads
exceeding 100 lb (445 N) in Seismic Design Categories
D, E or F unless approved for seismic loading. Power
actuated fasteners in steel are permitted in Seismic
Design Category D,EorF if the gravity tension load on
any fastener does not exceed 250 lbs (1123 N) unless
approved for seismic loading. Power actuated fasteners
in masonry are not permitted unless approved for seismic
loading.
1615.10.13 ASCE 7, Section 13.5.6. Replace ASCE 7, Sec-
tion 13.5.6 by the following:
13.5.6 Suspended ceilings. Suspended ceilings shall be
in accordance with this section.
13.5.6.1 Seismic forces. The weight of the ceiling, Wp,
shall include the ceiling grid; ceiling tiles or panels;
light fixtures if attached to, clipped to, or laterally sup-
ported by the ceiling grid; and other components that are
laterally supported by the ceiling. Wp shall be taken as
not less than 4psf(19 N/m^).
The seismic force, Fp, shall be transmitted through the
ceiling attachments to the building structural elements
or the ceiling- structure boundary,
13.5.6.2 Industry standard construction for acoustical
tile or lay-in panel ceilings. Unless designed in accor-
dance with ASTM E 580 Section 5,2.8.8, or seismically
qualified in accordance with Sections 13,2.5 or 13.2.6,
72
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
acoustical tile or lay-in panel ceilings shall be designed
and constructed in accordance with this section.
13.5.6.2.1 Seismic Design Categories D through F.
Acoustical tile or lay-in panel ceilings in Seismic Design
Categories A E and F shall be designed and installed in
accordance with ASTM C 635, ASTM C 636, andASTM
E 580, Section 5 - Seismic Design Categories D, E and F
as modified by this section.
13.5.6.2.2 Modification to ASTM E 580. Modify ASTM
E 580 by the following:
1. Exitways. Lay -in ceiling assemblies in exitways of
hospitals and essential services buildings shall be
installed with a main runner or cross runner sur-
rounding all sides of each piece of tile, board or
panel and each light fixture or grille. A cross run-
ner that supports another cross runner shall be
considered as a main runner for the purpose of
structural classification. Splices or intersections
of such runners shall be attached with through
connectors such as pop rivets, screws, pins, plates
with end tabs or other approved connectors.
2. Corridors and lobbies. Expansion joints shall be
provided in the ceiling at intersections of corridors
and at junctions of corridors and lobbies or other
similar areas.
3. Lay-in panels. Metal panels and panels weighing
more than V2 pounds per square foot (24 N/m^)
other than acoustical tiles shall be positively
attached to the ceiling suspension runners.
4. Lateral force bracing. Lateral force bracing is
required for all ceiling areas except that they shall
be permitted to be omitted in rooms with fioor
areas up to 144 square feet when perimeter sup-
port in accordance with ASTM E 580 Sections
5.2.2 and 5,23 are provided and perimeter walls
are designed to carry the ceiling lateral forces.
5. Ceiling fixtures. Fixtures installed in acoustical tile
or lay-in panel ceilings shall be mounted in a man-
ner that will not compromise ceiling performance.
All recessed or drop-in light fixtures and grilles
shall be supported directly from the fixture housing
to the structure above with a minimum of two
12-gage wires located at diagonally opposite cor-
ners. Leveling and positioning of fixtures may be
provided by the ceiling grid. Fixture support wires
may be slightly loose to allow the fixture to seat in
the grid system. Fixtures shall not be supported
from main runners or cross runners if the weight of
the fixtures causes the total dead load to exceed the
deflection capability of the ceiling suspension sys-
tem.
Fixtures shall not be installed so that the main
runners or cross runners will be eccentrically
loaded.
Surface-mounted fixtures shall be attached to
the main runner with at least two positive clamp-
ing devices made of material with a minimum of 14
gage. Rotational spring catches do not comply. A
12-gage suspension wire shall be attached to each
clamping device and to the structure above.
6. Partitions. Where the suspended ceiling system is
required to provide lateral support for the perma-
nent or relocatable partitions, the connection of the
partition to the ceiling system, the ceiling system
members and their connections, and the lateral
force bracing shall be designed to support the reac-
tion force of the partition from prescribed loads
applied perpendicular to the face of the partition.
Partition connectors, the suspended ceiling system
and the lateral-force bracing shall all be engi-
neered to suit the individual partition application
and shall be shown or defined in the drawings or
specifications.
1615.10.14 ASCE 7, Section 13.6.5. Modify ASCE 7, Sec-
tion 13.6.5 by deleting Item ^6 in Section 13.6.5.5 and add-
ing Section 13.6.5.6 as follows:
13.6.5.6 Conduit, cable tray, and other electrical distri-
bution systems (raceways). Raceways shall be designed
for seismic forces and seismic relative displacements as
required in Section 13.3. Conduit greater than 2.5 inches
(64 mm) trade size and attached to panels, cabinets or
other equipment subject to seismic relative displace-
ment. Dp, shall be provided with flexible connections or
designed for seismic forces and seismic relative dis-
placements as required in Section 13.3.
Exceptions:
1. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for raceways where either:
a. Trapeze assemblies are used to support
raceways and the total weight of the race-
way supported by trapeze assemblies is
less than 10 lb/ft (146 N/m), or
b. The raceway is supported by hangers and
each hanger in the raceway run is 12 in.
(305 mm) or less in length from the race-
way support point to the supporting
structure. Where rod hangers are used,
they shall be equipped with swivels to
prevent inelastic bending in the rod.
2. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for conduit, regardless of the value of
Ip, where the conduit is less than 2.5 in. (64
mm) trade size.
1615.10.15 ASCE 7, Section 13.6.7. Replace ASCE 7, Sec-
tion 13.6.7 by the following:
13.6.7 Ductwork. HVAC and other ductwork shall be
designed for seismic forces and seismic relative dis-
placements as required in Section 13.3. Ductwork
designed to carry toxic, highly toxic or explosive gases,
2010 CALIFORNIA BUILDING CODE
73
STRUCTURAL DESIGN
or used for smoke control shall be designed and braced
without considering the exceptions noted below.
Exceptions:
1, Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for ductwork where either:
a. Trapeze assemblies are used to support
ductwork and the total weight of the
ductwork supported by trapeze assem-
blies is less than 10 lb/ft (146 N/m); or
b. The ductwork is supported by hangers
and each hanger in the duct run is 12 in.
(305 mm) or less in length from the duct
support point to the supporting structure.
Where rod hangers are used, they shall
be equipped with swivels to prevent
inelastic bending in the rod.
2. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required where provisions are made to avoid
impact with larger ducts or mechanical compo-
nents or to protect the ducts in the event of such
impact; and HVAC ducts have a cross- sec-
tional area of6ft^ (0.557 m^) or less, or weigh
10 lb/ft (146 N/m) or less.
HVAC duct systems fabricated and installed in accor-
dance with standards approved by the authority having
jurisdiction shall be deemed to meet the lateral bracing
requirements of this section.
Components that are installed in-line with the duct
system and have an operating weight greater than 75 lb
(334 N)y such as fans y heat exchangers and humidifiers,
shall be supported and laterally braced independent of
the duct system, and such braces shall meet the force
requirements of Section 13.3.1. Appurtenances such as
dampers, louvers and diffuse rs shall be positively
attached with mechanical fasteners. Unbraced piping
attached to in-line equipment shall be provided with ade-
quate flexibility to accommodate the seismic relative dis-
placements.
1615:10.16 ASCE 7, Section 13,6.8. Replace ASCE 7, Sec-
tion 13.6.8 by the following:
13.6.8 Piping systems. Unless otherwise noted in this
section, piping systems shall be designed for the seismic
forces and seismic relative displacements of Section
13.3. ASME pressure piping systems shall satisfy the
requirements of Section 13.6.8.1. Fire protection sprin-
kler piping shall satisfy the requirements of Section
13.68.2. Elevator system piping shall satisfy the require-
ments of Section 13.6.10.
Where other applicable material standards or recog-
nized design bases are not used, piping design including
consideration of service loads shall be based on the fol-
lowing allowable stresses:
a. For piping constructed with ductile materials
(e.g., steel, aluminum or copper), 90 percent of the
minimum specified yield strength.
b. For threaded connections in piping constructed
with ductile materials, 70 percent of the minimum
specified yield strength.
c. For piping constructed with nonductile materials
(e.g., cast iron or ceramics), 10 percent of the
material minimum specified tensile strength.
d. For threaded connections in piping constructed
with nonductile materials, 8 percent of the mate-
rial minimum specified tensile strength.
Piping not detailed to accommodate the seismic rela-
tive displacements at connections to other components
shall be provided with connections having sufficient flex-
ibility to avoid failure of the connection between the
components.
13.6.8.1 ASME Pressure piping systems. Pressure piping
systems, including their supports, designed and constructed
in accordance with ASME B 31 shall be deemed to meet the
force, displacement and other requirements of this section.
In lieu of specific force and displacement requirements pro-
vided in ASME B 31, the force and displacement require-
ments of Section 13.3 shall be used.
13.6.8.2 Fire protection sprinkler piping systems. Fire pro-
tection sprinkler piping designed and constructed in accor-
dance with NFPA 13 shall be deemed to meet the force and
displacement requirements of this section. The exceptions of
Section 13.6.8.3 shall not apply.
Exception: Pipe hangers, bracing and anchor capacities
shall be determined in accordance with material chap-
ters of the California Building Code, in lieu of using
those in NFPA 13. The force and displacement require-
ments of Section 13.3 or those in the NFPA 13 may be
used for design.
13.6.8.3 Exceptions. Design of piping systems and attach-
ments for the seismic forces and relative displacements of
Section 13.3 shall not be required where one of the follow-
ing conditions apply:
1. Trapeze assemblies are used to support piping
whereby no single pipe exceeds the limits set forth in
3a. or b. below and the total weight of the piping sup-
ported by the trapeze assemblies is less than 10 lb/ft
(146 N/m).
2. The piping is supported by hangers and each hanger
in the pipingrun is 12 in. (305 mm) or less in length
from the top of the pipe to the supporting structure.
Where pipes are supported on a trapeze, the trapeze
shall be supported by hangers having a length of 12
in. (305 mm) or less. Where rod hangers are used,
they shall be equipped with swivels, eye nuts or other
devices to prevent bending in the rod.
74
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
3. Piping having an Rp in Table 13.6-1 of 4.5 or greater
is used and provisions are made to avoid impact with
other structural or nonstructural components or to
protect the piping in the event of such impact and
where the following size requirements are satisfied:
a. For Seismic Design Categories D, E or F and
values oflp greater than one, the nominal pipe
size shall be 1 inch (25 mm) or less,
b. For Seismic Design Categories D,EorF where
Ip = 1.0 the nominal pipe size shall be 3 inches
(80 mm) or less.
The exceptions above shall not apply to elevator piping.
13,6,8.4 Other piping systems. Piping not designed and
constructed in accordance with ASME B 31 or NFPA 13
shall comply with the requirements of Section 13.6.11.
1615.10.17 ASCE 7, Section 13,6,10.1, Modify ASCE 7
Section 13.6.10.1 by adding Section 13. 6.10.1.1 as follows :
13.6.10.1,1 Elevators guide rail support. The design of
guide rail support bracket fastenings and the support-
ing structural framing shall use the weight of the coun-
terweight or maximum weight of the car plus not more
than 40 percent of its rated load. The seismic forces
shall be assumed to be distributed one-third to the top
guiding members and two-thirds to the bottom guiding
members of cars and counterweights, unless other sub-
stantiating data are provided. In addition to the
requirements of ASCE 7 Section 13.6.10.1, the mini-
mum seismic forces shall be 0.5 g acting in any horizon-
tal direction.
1615.10.18 ASCE 7, Section 13,6.10,4, Replace ASCE 7
Section 13.6.10.4 as follows :
13,6,10,4 Retainer plates. Retainer plates are required at
the top and bottom of the car and counterweight, except
where safety devices acceptable to the enforcement
agency are provided which meet all requirements of the
retainer plates, including full engagement of the machined
portion of the rail The design of the car, cab stabilizers,
counterweight guide rails and counterweight frames for
seismic forces shall be based on the following require-
ments:
L The seismic force shall be computed per the
requirements of ASCE 7 Section 13.6.10.1. The
minimum horizontal acceleration shall be 0.5gfor
all buildings.
2. Wp shall equal the weight of the counterweight or
the maximum weight of the car plus not less than
40 percent of its rated load.
3. With the car or counterweight located in the most
adverse position, the stress in the rail shall not
exceed the limitations specified in these regula-
tions, nor shall the deflection of the rail relative to
its supports exceed the deflection listed below:
BAIL SIZE
(weight per foot
of length,
pounds)
WIDTH OF
MACHINED
SURFACE
(inches)
ALLOWABLE
RAIL
DEFLECTION
(inches)
8
l'/4
0.20
11
1^/2
0.30
12
1%
0.40
15
l''/32
0.50
18^/2
l'%2
0.50
22^/,
2
0.50
30
2%
0.50
For Sf: 1 inch - 25 mm, 1 foot = 305 mm, J pound = 0.454 kg
Note: Deflection limitations are given to maintain a consistent factor of safety
against disengagement of retainer plates from the guide rails during an
earthquake.
4. Where guide rails are continuous over supports
and rail joints are within 2 feet (610 mm) of their
supporting brackets, a simple span may be
assumed.
5. The use of spreader brackets is allowed.
6. Cab stabilizers and counterweight frames shall be
designed to withstand computed lateral load with
a minimum horizontal acceleration of 0.5 g.
1615.10.19 ASCE 7, Section 16,1.3.2. Modify ASCE 7 Sec-
tion 16.1.3.2 by the following:
Where next generation attenuation relations are used in
accordance with CBC Section 1802A.6.2, each pair of
motion shall be scaled such that for each period between
0.2T and 1.5T, the average of the SRSS spectra from all
horizontal component pairs does not fall below the cor-
responding ordinate of the maximum considered earth-
quake (MCE) response spectrum determined using NGA
relations.
At sites within 5 km of an active fault that controls the
hazard, each pair of components shall be rotated to the
fault-normal and fault-parallel direction of the causative
fault, and shall be scaled so that average of the fault-nor-
mal components is not be less than the MCE response
spectrum for each period between 0.2T and 1.5T.
1615.10.20 ASCE 7, SecHon 16.1.4. Modify ASCE 7 Sec-
tion 16.1.4 by the following:
For each ground motion analyzed, the individual
response parameters shall be multiplied by the following
scalar quantities:
a. Force response parameters shall be multiplied by
I/R, where I is the importance factor determined in
2010 CALIFORNIA BUILDING CODE
75
STRUCTURAL DESIGN
accordance with Section 11.5.1, and R is the
Response Modification Coefficient selected in
accordance with Section 12,2.1.
b. Drift quantities shall be multiplied by C^/R, where
Q is the deflection amplification factor specified
in Table 12.2-1.
The distribution of horizontal shear shall be in accor-
dance with Section 12.8.4.
1615.10.21 ASCE 7, Section 16.2,4. Modify ASCE 7 Sec-
tion 16.2.4 by the following:
a) Where site is located within 3.1 miles (5 km) of an
active fault at least seven ground motions shall be
analyzed and response parameters shall be based on
larger of the average of the maximum response with
ground motions applied as follows:
1. Each of the ground motions shall have their
maximum component at the fundamental
period aligned in one direction.
2. Each of the ground motion's maximum compo-
nent shall be rotated orthogonal to the previous
analysis direction.
b) Where site is located more than 3.1 miles (5 km) from
an active fault at least 10 ground motions shall be
analyzed. The ground motions shall be applied such
that one-half shall have their maximum component
aligned in one direction and the other half aligned in
the orthogonal direction. The average of the maxi-
mum response of all the analyses shall be used for
design.
1615.10.22 ASCE 7, Section 17.2.1. Modify ASCE 7 Sec-
tion 17.2.1 by adding the following:
The importance factor, Ip, for parts and portions of a seis-
mically isolated building shall be the same as that required
for a fixed-base building of the same occupancy category.
1615.10.23 ASCE 7 Section 17.2.4.7. Modify ASCE 7 Sec-
tion 17.2.4.7 by adding the following:
The effects of uplift and/or rocking shall be explicitly
accounted for in the analysis and in the testing of the isola-
tor units.
1615.10.24 ASCE 7, Section 17.2.5.2. Modify ASCE 7, Sec-
tion 17.2.5.2 by adding the following:
The separation requirements for the building above the
isolation system and adjacent buildings shall be the sum
of the factored displacements for each building. The fac-
tors to be used in determining separations shall be:
1. For seismically isolated buildings, the deforma-
tion resulting from the analyses using the maxi-
mum considered earthquake unmodified by Rj.
2. For fixed based buildings, C^ times the elastic
deformations resulting from an equivalent static
analysis using the seismic base shear computed
via ASCE 7 Section 12.8.
1615.10.25 ASCE 7, Section 17.3.2. Modify ASCE 7, Sec-
tion 17.3.2 by adding the following:
Where next generation attenuation relations are used in
accordance with Section 1803A.6.2, each pair of motion
shall be scaled such that for each period between 0.5T^
and 1.25Ti^ (Where T^ and T^ are defined in Section
17.5.3), the average of the SRSS spectra from all hori-
zontal component pairs does not fall below the corre-
sponding ordinate of the maximum considered
earthquake (MCE) response spectrum determined using
NGA relations.
At sites within 5 km of an active fault that controls the
hazard, each pair of components shall be rotated to the
fault-normal and fault-parallel direction of the causative
fault, and shall be scaled so that average of the fault-nor-
mal components is not be less than the MCE response
spectrum for each period between 0.5Tf^ and 1.25Tj^.
1615.10.26 ASCE 7, Section 21.4. Replace ASCE 7, Sec-
tion 21.4 by the following:
21.4 Design Acceleration Parameters. Where the
site-specific procedure is used to determine the design
ground motion in accordance with Section 21.3, the
parameter Sps shall be taken as the spectral acceleration,
Sa, obtained from the site-specific spectra at a period of
0.2 sec, except that it shall not be taken less than 90 per-
cent of the peak spectral acceleration, S^, at any period
larger than 0.2 second. The parameter Sq] shall be taken
as the greater of the spectral acceleration, S^ at a period
of 1 sec or two times the spectral acceleration, S^, at a
period of 2 sec.
For use with the Equivalent Lateral Force Procedure,
the site specific spectral acceleration, S^ at T shall be
permitted to replace Sj^j/T in Equation 12.8-3 and
SdiT[/P in Equation 12.8-4. The parameter Sqs calcu-
lated per this section shall be permitted to be used in
Equations 12.8-2 and 12.8-5. The mapped value of Sj
shall be used in Equation 12.8-6. The parameters S^^
and S^i shall be taken as 1.5 times S^s (^^d S^^, respec-
tively. The values so obtained shall not be less than 80
percent of the values determined in accordance with Sec-
tion 11.4. 3 for S^s ^^d Sf^j and Section 11.4. 4 for Sps cind
Sdi-
76
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 16A - STRUCTURAL DESIGN
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SB
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
X
Chapter/Section
1607A.7.2
X
2010 CALIFORNIA BUILDING CODE
77
78 201 CALIFORNIA BUILDING CODE
CHAPTER 164
STRUCTURAL DESIGN
SECTION 16014
GENERAL
1601A.1 Scope, The provisions of this chapter shall govern the
structural design of buildings, structures and portions thereof
regulated by this code.
1601 A, 1,1 Application, The scope of application of Chap-
ter 16A is as follows:
1. Applications listed in Section 1.9,2,1, regulated by
the Division of the State Architect-Structural Safety
(DSA-SS). These applications include public elemen-
tary and secondary schools, community colleges and
state-owned or state-leased essential services build-
ings.
II 2. Applications listed in Sections 1,10.1 and 1.10.4, reg-
ulated by the Office of Statewide Health Planning and
Development (OSHPD). These applications include
hospitals, skilled nursing facilities, intermediate care
facilities, and correctional treatment centers.
Exception: [OSHPD 2] Single-story Type V
skilled nursing or intermediate care facilities uti-
lizing wood-frame or light- steel-frame construc-
tion as defined in Health and Safety Code Section
129725, which shall comply with Chapter 16 and
any applicable amendments therein.
1601 A, 1.2 Amendments in this chapter, DSA-SS and
OSHPD adopt this chapter and all amendments.
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1, Division of the State Architect-Structural Safety:
[DSA-SS] - For applications listed in Section
I I 1.9.2.1.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD 1] - For applications listed in Section
I I 1,10,1.
[OSHPD 4] - For applications listed in Section
I I 1,10,4.
1601 A,2 References, All referenced codes and standards
listed in Chapter 35 shall include all the modifications con-
tained in this code to referenced standards. In the event of
any discrepancy between this code and a referenced stan-
I I dard, refer to Section 1.1.7.
1601A.3 Enforcement agency approval In addition to the
requirements of California Code of Regulations (C.CR.)
Title 24, Parts 1 and 2, any aspect of project design, construc-
tion, quality assurance or quality control programs for which
this code requires approval by the design professional are
also subject to approval by the enforcement agency.
SECTION 16024
DEFINITIONS AND NOTATIONS
1602A. 1 Definitions. The following words and terms shall, for
the purposes of this chapter, have the meanings shown herein.
ALLOWABLE STRESS DESIGN. A method of proportion-
ing structural members, such that elastically computed stresses
produced in the members by nominal loads do not exceed spec-
ified allowable stresses (also called "working stress design"). ^
ALTERNATIVE SYSTEM. [OSHPD 1 & 4] Alternative mate-
rials, design and methods of construction in accordance with
Section 104.11, Section 11.1.4 ofASCE 7 or structural design <
criteria as approved by the enforcement agency,
DEAD LOADS. The weight of materials of construction
incorporated into the building, including but not limited to
walls, floors, roofs, ceihngs, stairways, built-in partitions, fin-
ishes, cladding and other similarly incorporated architectural
and structural items, and the weight of fixed service equipment,
such as cranes, plumbing stacks and risers, electrical feeders,
heating, ventilating and air-conditioning systems and
automatic sprinkler systems. ^
DESIGN STRENGTH. The product of the nominal strength
and a resistance factor (or strength reduction factor).
DIAPHRAGM. A horizontal or sloped system acting to trans-
mit lateral forces to the vertical-resisting elements. When the
term "diaphragm" is used, it shall include horizontal bracing
systems.
Diaphragm, blocked. In light-frame construction, a dia-
phragm in which all sheathing edges not occurring on a
framing member are supported on and fastened to blocking.
Diaphragm boundary. In light- frame construction, a loca-
tion where shear is transferred into or out of the diaphragm
sheathing. Transfer is either to a boundary element or to
another force-resisting element.
Diaphragm chord. A diaphragm boundary element per-
pendicular to the applied load that is assumed to take axial
stresses due to the diaphragm moment.
Diaphragm flexible. A diaphragm is flexible for the pur-
pose of distribution of story shear and torsional moment
where so indicated in Section 12.3. 1 ofASCE 7, as modified
in Section 1613A.6.1.
Diaphragm, rigid. A diaphragm is rigid for the purpose of
distribution of story shear and torsional moment when the
lateral deformation of the diaphragm is less than or equal to
two times the average story drift.
DURATION OF LOAD. The period of continuous applica-
tion of a given load, or the aggregate of periods of intermittent
applications of the same load.
ENFORCEMENT AGENT, That individual within the agency
or organization charged with responsibility for agency or
organization compliance with the requirements of this code.
2010 CALIFORNIA BUILDING CODE
79
STRUCTURAL DESIGN
Used interchangeably with ''Building Official" and ''Code
Official:'
ESSENTIAL FACILITIES. Buildings and other structures
that are intended to remain operational in the event of extreme
environmental loading from flood, wind, snow or earthquakes.
FABRIC PARTITION. A partition consisting of a finished sur-
face made of fabric, without a continuous rigid backing, that is
directly attached to a framing system in which the vertical fram-
ing members are spaced greater than 4 feet (1219 mm) on center.
FACTORED LOAD. The product of a nominal load and a load
factor,
GUARD. See Section 1002.1.
HOSPITAL BUILDING. Any building defined in Section
129725, Health and Safety Code,
IMPACT LOAD. The load resulting from moving machinery,
elevators, crane ways, vehicles and other similar forces and
kinetic loads, pressure and possible surcharge from fixed or
moving loads.
LIMIT STATE. A condition beyond which a structure or
member becomes unfit for service and is judged to be no longer
useful for its intended function (serviceability limit state) or to
be unsafe (strength limit state).
LIVE LOADS. Those loads produced by the use and occu-
pancy of the building or other structure and do not include con-
struction or environmental loads such as wind load, snow load,
rain load, earthquake load, flood load or dead load.
LIVE LOADS (ROOF). Those loads produced (1) during
maintenance by workers, equipment and materials; and (2)
during the life of the structure by movable objects such as
planters and by people.
LOAD AND RESISTANCE FACTOR DESIGN (LRFD). A
method of proportioning structural members and their connec-
tions using load and resistance factors such that no applicable
limit state is reached when the structure is subjected to appro-
priate load combinations. The term "LRFD" is used in the
design of steel and wood structures.
LOAD EFFECTS. Forces and deformations produced in
structural members by the appUed loads.
LOAD FACTOR. A factor that accounts for deviations of the
actual load from the nominal load, for uncertainties in the analy-
sis that transforms the load into a load effect, and for the proba-
bility that more than one extreme load will occur simultaneously.
LOADS. Forces or other actions that result from the weight of
building materials, occupants and their possessions, environ-
mental effects, differential movement and restrained dimen-
sional changes. Permanent loads are those loads in which
variations over time are rare or of small magnitude, such as
dead loads. All other loads are variable loads (see also '''Nomi-
nal loads'').
NOMINAL LOADS. The magnitudes of the loads specified in
this chapter (dead, live, soil, wind, snow, rain, flood and earth-
quake).
OCCUPANCY CATEGORY. A category used to determine
structural requirements based on occupancy.
OTHER STRUCTURES. Structures, other than buildings,
for which loads are specified in this chapter.
PANEL (PART OF A STRUCTURE). The section of a floor,
wall or roof comprised between the supporting frame of two
adjacent rows of columns and girders or column bands of floor
or roof construction.
RESISTANCE FACTOR. A factor that accounts for devia-
tions of the actual strength from the nominal strength and the
manner and consequences of failure (also called "strength
reduction factor").
STRENGTH, NOMINAL. The capacity of a structure or
member to resist the effects of loads, as determined by compu-
tations using specified material strengths and dimensions and
equations derived from accepted principles of structural
mechanics or by field tests or laboratory tests of scaled models,
allowing for modeling effects and differences between labora-
tory and field conditions.
STRENGTH, REQUIRED. Strength of a member, cross sec-
tion or connection required to resist factored loads or related
internal moments and forces in such combinations as stipulated
by these provisions.
STRENGTH DESIGN. A method of proportioning structural
members such that the computed forces produced in the mem-
bers by factored loads do not exceed the member design
strength [also called '''load and resistance factor design''
(LRFD)]. The term "strength design" is used in the design of
concrete and masonry structural elements.
VEHICLE BARRIER SYSTEM. A system of building com-
ponents near open sides of a garage floor or ramp or building
walls that act as restraints for vehicles.
NOTATIONS.
D = Dead load.
E = Combined effect of horizontal and vertical
earthquake induced forces as defined in Section
12.4.2ofASCE7.
F = Load due to fluids with well-defined pressures and
maximum heights.
F^ = Flood load in accordance with Chapter 5 of ASCE 7.
H = Load due to lateral earth pressures, ground water
pressure or pressure of bulk materials.
L = Live load, except roof live load, including any per-
mitted live load reduction.
L^ = Roof live load including any permitted live load
reduction.
R = Rain load.
S = Snow load.
T = Self- straining force arising from contraction or
expansion resulting from temperature change,
shrinkage, moisture change, creep in component
materials, movement due to differential settlement
or combinations thereof.
W = Load due to wind pressure.
80
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
SECTION 1603>»
CONSTRUCTION DOCUMENTS
1603A.1 General. Construction documents shall show the
size, section and relative locations of structural members with
floor levels, column centers and offsets dimensioned. The
design loads and other information pertinent to the structural
design required by Sections 1603A.1.1 through 1603A.1.9
shall be indicated on the construction documents.
Exception: Construction documents for buildings con-
structed in accordance with the conventional light-frame
construction provisions of Section 2308 shall indicate the
following structural design information:
1 . Floor and roof live loads.
2. Ground snow load, P^.
3. Basic wind speed (3 -second gust), miles per hour
(mph) (km/hr) and wind exposure.
4. Seismic design category and site class.
5. Rood design data, if located in flood hazard areas
established in Section 1612A.3.
6. Design load-bearing values of soils.
[DSA-SS] Additional requirements are included in Section
4-2 10 and 4-31 7 of the California Administrative Code (Part 7,
Title 24, C.CM
[OSHPD 1] Additional requirements are included in Section
7-115 and 7-125 of the California Administrative Code (Part 7,
Title 24, C.CR).
1603A.1.1 Floor live load. The uniformly distributed, con-
centrated and impact floor live load used in the design shall be
indicated for floor areas. Use of live load reduction in accor-
dance with Section 1607A.9 shall be indicated for each type
of live load used in the design.
1603A.1.2 Roof live load. The roof live load used in the
design shall be indicated for roof areas (Section 1607 A. 11).
1603A.1.3 Roof snow load. The ground snow load, P^, shall
be indicated. In areas where the ground snow load, P^, exceeds
10 pounds per square foot (psf) (0.479 kN/m^), the following
additional information shall also be provided, regardless of
whether snow loads govern the design of the roof:
1 . Flat-roof snow load, Pf.
2. Snow exposure factor, Q.
3. Snow load importance factor, 7.
4. Thermal factor, Q.
1603A.1.4 Wind design data. The following information
related to wind loads shall be shown, regardless of whether
wind loads govern the design of the lateral-force-resisting
system of the building:
1. Basic wind speed (3-second gust), miles per hour
(km/hr).
2. Wind importance factor, 7, and occupancy category.
3. Wind exposure. Where more than one wind exposure
is utilized, the wind exposure and applicable wind
direction shall be indicated.
4. The applicable internal pressure coefficient.
5. Components and cladding. The design wind pres-
sures in terms of psf (kN/m^) to be used for the design
of exterior component and cladding materials not spe-
cifically designed by the registered design profes-
sional.
1603A.1.5 Earthquake design data. The following infor-
mation related to seismic loads shall be shown, regardless of
whether seismic loads govern the design of the lat-
eral-force-resisting system of the building:
1 . Seismic importance factor, 7, and occupancy cate-
gory.
2. Mapped spectral response accelerations, S^ and Si.
3. Site class,
4. Spectral response coefficients, S^s ^^^ ^di-
5. Seismic design category.
6. Basic seismic-force-resisting system(s),
7. Design base shear.
8. Seismic response coefficient(s), Q.
9. Response modification factor(s), 7?.
10. Analysis procedure used.
77. Applicable horizontal structural irregularities.
12. Applicable vertical structural irregularities.
1603AA,5A Connections, Connections that resist
design seismic forces shall be designed and detailed on
the design drawings.
1603A.1.6 Geotechnical information. The design load-
bearing values of soils shall be shown on the construction
documents.
1603A. 1.7 Flood design data. For buildings located in whole
or in part in flood hazard areas as established in Section
1 6 1 2A. 3 , the documentation pertaining to design, if required in
Section 1612A.5, shall be included and the following informa-
tion, referenced to the datum on the conmiunity's Rood Insur-
ance Rate Map (FIRM), shall be shown, regardless of whether
flood loads govern the design of the building:
1. In flood hazard areas not subject to high- velocity
wave action, the elevation of the proposed lowest
floor, including the basement.
2. In flood hazard areas not subject to high-velocity
wave action, the elevation to which any nonresiden-
tial building will be dry floodproofed.
3. In flood hazard areas subject to high-velocity wave
action, the proposed elevation of the bottom of the
lowest horizontal structural member of the lowest
floor, including the basement.
1603A.1.8 Special loads. Special loads that are appUcable
to the design of the building, structure or portions thereof
shall be indicated along with the specified section of this
code that addresses the special loading condition.
1603A.1.9 Systems and components requiring special
inspections for seismic resistance. Construction docu-
2010 CALIFORNIA BUILDING CODE
81
STRUCTURAL DESIGN
11
ments or specifications shall be prepared for those systems
and components requiring special inspection for seismic
resistance as specified in Section 1707.1 by the registered
design professional responsible for their design and shall be
submitted for approval in accordance with Section 107.1.
Reference to seismic standards in lieu of detailed drawings
is acceptable.
1603A.U0 Construction procedures. Where unusual
erection or construction procedures are considered essen-
tial by the project structural engineer or architect in order to
accomplish the intent of the design or influence the design,
such procedure shall be indicated on the construction docu-
ments.
SECTION 1604>!l
GENERAL DESIGN REQUIREMENTS
1604A.1 General. Building, structures and parts thereof shall
be designed and constructed in accordance with strength
design, load and resistance factor design, allowable stress
design, empirical design or conventional construction meth-
ods, as permitted by the applicable material chapters.
1604A.2 Strength. Buildings and other structures, and parts
thereof, shall be designed and constructed to support safely the
factored loads in load combinations defined in this code with-
out exceeding the appropriate strength limit states for the mate-
rials of construction. Alternatively, buildings and other
structures, and parts thereof, shall be designed and constructed
to support safely the nominal loads in load combinations
defined in this code without exceeding the appropriate speci-
fied allowable stresses for the materials of construction.
Loads and forces for occupancies or uses not covered in this
chapter shall be subject to the approval of the building official.
1604A.3 Serviceability. Structural systems and members
thereof shall be designed to have adequate stiffness to limit
deflections and lateral drift. See Section 12.12.1 of ASCE 7 for
drift limits applicable to earthquake loading.
1604A.3.1 Deflections. The deflections of structural mem-
bers shall not exceed the more restrictive of the Umitations
I I of Sections 1604A.3.2 through 1604A.3.6 or that permitted
by Table 1604A.3.
1604A.3.2 Reinforced concrete. The deflection of rein-
forced concrete structural members shall not exceed that
permitted by ACI 318.
1604A.3.3 Steel. The deflection of steel structural members
shall not exceed that permitted by AISC 360, AISI SlOO,
ASCE 3, ASCE 8, SJI CJ-l.O, SJI JG-1.1, SJI K-1.1 or SJI
LH/DLH-1.1, as applicable.
1604A.3.4 Masonry. The deflection of masonry structural
members shall not exceed that permitted by TMS 402/ACI
530/ASCE 5.
1604A.3.5 Aluminum. The deflection of aluminum struc-
tural members shall not exceed that permitted by AA
ADMl.
1604A.3.6 Limits. Deflection of structural members over
span, /, shall not exceed that permitted by Table 1604A.3.
1604A,3.7 Horizontal diaphragms. The maximum span-
width ratio for any roof or floor diaphragm shall not exceed
those given in Table 4.2.4 ofAF & PA SDPWS or ICC-ES
AC 43 unless test data and design calculations acceptable
to the enforcement agency are submitted and approved for
the use of other span-width ratios. Concrete diaphragm
shall not exceed span-width ratios for equivalent composite
floor diaphragm in ICC-ES AC 43,
1604 A3, 8 Deflections* Deflection criteria for materials not
specified shall be developed by the project architect or struc-
tural engineer in a manner consistent with the provisions of
this section and approved by the enforcement agency.
TABLE 16044.3
DEFLECTION LIMITS^' ^^ ^' ^^ '
II
CONSTRUCTION
L
SorW^
D+L^'9
Roof members:^
Supporting plaster ceiling
Supporting nonplaster ceiling
Not supporting ceiling
1/360
1/240
//ISO
1/360
1/240
//ISO
1/240
//ISO
//120
Floor members
//360
—
1/240
Exterior walls and interior partitions:
With brittle finishes
With flexible finishes
Veneered walls, anchored veneers and
adhered veneers over 1 inch (25 mm)
thick, including the mortar backing
—
1/240
1/120
Section
1405.10
~
Farm buildings
—
—
//ISO
Greenhouses
—
//1 20
For SI: 1 foot = 304.8 mm.
a. For structural roofing and siding made of formed metal sheets, the total load
deflection shall not exceed //60. For secondary roof structural members sup-
porting formed metal roofing, the live load deflection shall not exceed //1 50.
For secondary wall members supporting formed metal siding, the design
wind load deflection shall not exceed //90. For roofs, this exception only
applies when the metal sheets have no roof covering.
b. Interior partitions not exceeding 6 feet in height and flexible, folding and
portable partitions are not governed by the provisions of this section. The
deflection criterion for interior partitions is based on the horizontal load
defined in Section 1607A.13.
c. See Section 2403 for glass supports.
d. For wood structural members having a moisture content of less than 16 per-
cent at time of installation and used under dry conditions, the deflection
resulting from L + 0.5Z) is permitted to be substituted for the deflection
resulting from L + D.
e. The above deflections do not ensure against ponding. Roofs that do not have
sufficient slope or camber to assure adequate drainage shall be investigated
for ponding. See Section 161 1 A for rain and ponding requirements and Sec-
tion 1503.4 for roof drainage requirements.
f. The wind load is permitted to be taken as 0.7 times the "component and clad-
ding" loads for the purpose of determining deflection limits herein.
g. For steel structural members, the dead load shall be talsen as zero.
h. For aluminum structural members or aluminum panels used in skylights and
sloped glazing framing, roofs or walls of sunroom additions or patio covers,
not supporting edge of glass or aluminum sandwich panels, the total load
deflection shall not exceed //60. For continuous aluminum structural mem-
bers supporting edge of glass, the total load deflecfion shall not exceed //1 75
for each glass lite or //60 for the entire length of the member, whichever is
more stringent. For aluminum sandwich panels used in roofs or walls of sun-
room additions or patio covers, the total load deflection shall not exceed
//1 20.
i. For cantilever members, / shall be taken as twice the length of the cantilever.
82
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1604A.4 Analysis* Load effects on structural members and
their connections shall be determined by methods of structural
analysis that take into account equilibrium, general stability,
geometric compatibility and both short- and long-term mate-
rial properties.
Members that tend to accumulate residual deformations
under repeated service loads shall have included in their analy-
sis the added eccentricities expected to occur during their ser-
vice life.
Any system or method of construction to be used shall be
based on a rational analysis in accordance with well-estab-
lished principles of mechanics. Such analysis shall result in a
system that provides a complete load path capable of transfer-
ring loads from their point of origin to the load-resisting ele-
ments.
The total lateral force shall be distributed to the various verti-
cal elements of the lateral-force-resisting system in proportion
to their rigidities, considering the rigidity of the horizontal
bracing system or diaphragm. Rigid elements assumed not to
be a part of the lateral-force-resisting system are permitted to
be incorporated into buildings provided their effect on the
action of the system is considered and provided for in the
design. Except where diaphragms are flexible, or are permitted
to be analyzed as flexible, provisions shall be made for the
increased forces induced on resisting elements of the structural
system resulting from torsion due to eccentricity between the
center of application of the lateral forces and the center of rigid-
ity of the lateral-force-resisting system.
Every structure shall be designed to resist the overturning
effects caused by the lateral forces specified in this chapter. See
Section 1609 A for wind loads, Section 161 OA for lateral soil
loads and Section 1613 A for earthquake loads.
1604A.5 Occupancy category. Each building and structure
shall be assigned an occupancy category in accordance with
Table 1604A.5.
1604A.5.1 Multiple occupancies. Where a building or
structure is occupied by two or more occupancies not
included in the same occupancy category, it shall be
assigned the classification of the highest occupancy cate-
gory corresponding to the various occupancies. Where
buildings or structures have two or more portions that are
structurally separated, each portion shall be separately clas-
sified. Where a separated portion of a building or structure
provides required access to, required egress from or shares
life safety components with another portion having a higher
occupancy category, both portions shall be assigned to the
higher occupancy category.
1604A.6 In-situ load tests. The building official is authorized
to require an engineering analysis or a load test, or both, of any
construction whenever there is reason to question the safety of
the construction for the intended occupancy. Engineering anal-
ysis and load tests shall be conducted in accordance with Sec-
tion 1714.
1604A.7 Preconstruction load tests. Materials and methods
of construction that are not capable of being designed by
approved engineering analysis or that do not comply with the
applicable material design standards listed in Chapter 35, or
alternative test procedures in accordance with Section 1712A,
shall be load tested in accordance with Section 1715A.
1604A.8 Anchorage.
1604A.8.1 General. Anchorage of the roof to walls and col-
umns, and of walls and columns to foundations, shall be
provided to resist the uplift and sliding forces that result
from the application of the prescribed loads.
1604A.8.2 Walls. Walls shall be anchored to floors, roofs
and other structural elements that provide lateral support for
the wall. Such anchorage shall provide a positive direct con-
nection capable of resisting the horizontal forces specified
in this chapter but not less than the minimum strength
design horizontal force specified in Section 1 1.7.3 of ASCE
7, substituted for "£7* in the load combinations of Section
1605 A. 2 or 1605 A. 3. Concrete and masonry walls shall be
designed to resist bending between anchors where the
anchor spacing exceeds 4 feet (1219 mm). Required
anchors in masonry walls of hollow units or cavity walls
shall be embedded in a reinforced grouted structural ele-
ment of the wall. See Sections 1609 A for wind design
requirements and 161 3 A for earthquake design require-
ments,
1604A.8.3 Decks. Where supported by attachment to an
exterior wall, decks shall be positively anchored to the pri-
mary structure and designed for both vertical and lateral
loads as applicable. Such attachment shall not be accom-
plished by the use of toenails or nails subject to withdrawal.
Where positive connection to the primary building structure
cannot be verified during inspection, decks shall be
self-supporting. Connections of decks with cantilevered
framing members to exterior walls or other framing mem-
bers shall be designed for both of the following:
1. The reactions resulting from the dead load and live
load specified in Table 1607A.1, or the snow load
specified in Section 1608 A, in accordance with Sec-
tion 1605 A, acting on all portions of the deck.
2. The reactions resulting from the dead load and live
load specified in Table 1607A.1, or the snow load
specified in Section 1608 A, in accordance with Sec-
tion 1605 A, acting on the cantilevered portion of the
deck, and no live load or snow load on the remaining
portion of the deck.
1604A.9 Counteracting structural actions. Structural mem-
bers, systems, components and cladding shall be designed to
resist forces due to earthquake and wind, with consideration of
overturning, sliding and uplift. Continuous load paths shall be
provided for transmitting these forces to the foundation. Where
sliding is used to isolate the elements, the effects of friction
between sliding elements shall be included as a force.
1604A.10 Wind and seismic detailing. Lateral-force-resist-
ing systems shall meet seismic detailing requirements and limi-
tations prescribed in this code and ASCE 7, excluding Chapter
14 and Appendix 1 1 A, even when wind load effects are greater
than seismic load effects.
2010 CALIFORNIA BUILDING CODE
83
STRUCTURAL DESIGN
TABLE 16044.5
OCCUPANCY CATEGORY OF BUILDINGS AND OTHER STRUCTURES
>
II
II
OCCUPANCY
CATEGORY
NATURE OF OCCUPANCY
I
Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to:
• Agricultural facilities.
• Certain temporary facilities.
• Minor storage facilities.
n
Buildings and other structures except those listed in Occupancy Categories I, III and IV
in
Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not
hmited to:
• Buildings and other structures whose primary occupancy is public assembly with an occupant load greater than 300.
• Buildings and other structures containing elementary school, secondary school or day care facilities with an occupant
load greater than 250.
• Buildings and other structures containing adult education facilities, such as colleges and universities with an occupant
load greater than 500.
• Group 1-3 occupancies.
• Any other occupancy with an occupant load greater than 5,000^.
• Power-generating stations, water treatment facihties for potable water, waste water treatment facihties and other pub-
lic utility facilities not included in Occupancy Category IV.
• Buildings and other structures not included in Occupancy Category IV containing sufficient quantities of toxic or ex-
plosive substances to be dangerous to the public if released.
IV
Buildings and other structures designated as essential facilities, including but not limited to:
• [OSHPD 1&4] Hospital Buildings as defined in C. CR. Title 24, Part 1, Section 7-111 and all structures required for
their continuous operation or access/egress,
• Fire, rescue, ambulance and police stations and emergency vehicle garages.
• Designated earthquake, hurricane or other emergency shelters.
• Designated emergency preparedness, communications and operations centers and other facilities required for emer-
gency response [DSA-SS] as defined in C. C.R. Title 24, Part 1, Section 4-207 and all structures required for their con-
tinuous operation or access/egress.
• Power-generating stations and other public utility facilities required as emergency backup facihties for Occupancy
Category IV structures.
• Structures containing highly toxic materials as defined by Section 307 where the quantity of the material exceeds the
maximum allowable quantities of Table 307.1(2).
• Aviation control towers, air traffic control centers and emergency aircraft hangars.
• Buildings and other structures having critical national defense functions.
• Water storage facilities and pump structures required to maintain water pressure for fire suppression.
a. For purposes of occupant load calculation, occupancies required by Table 1004. 1 . 1 to use gross floor area calculations shall be permitted to use net floor areas to
determine the total occupant load.
SECTION 16054
LOAD COMBINATIONS
1605A.1 General. Buildings and other structures and portions
thereof shall be designed to resist:
1. The load combinations specified in Section 1605A.2,
1605A3.1orl605A3.2,
2. The load combinations specified in Chapters 18 through
23, and
3. The load combinations with overs trength factor speci-
fied in Section 12.4.3.2 of ASCE 7 where required by
Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With
the simplified procedure of ASCE 7 Section 12.14, the
load combinations with overstrength factor of Section
12.14.3.2 of ASCE 7 shall be used.
Applicable loads shall be considered, including both earth-
quake and wind, in accordance with the specified load combi-
nations. Each load combination shall also be investigated with
one or more of the variable loads set to zero.
Where the load combinations with overstrength factor in
Section 12.4.3.2 of ASCE 7 apply, they shall be used as fol-
lows:
1. The basic combinations for strength design with
overstrength factor in lieu of Equations 16A-5 and 16A-7
in Section 1605A.2.1.
2. The basic combinations for allowable stress design with
overstrength factor in lieu of Equations 16A-12, 16A-13
and 16A-15 in Section 1605A.3.1.
3. The basic combinations for allowable stress design with
overstrength factor in lieu of Equations 16A-20 and
16A-21 in Section 1605A.3.2.
1605A.1.1 Stability. Regardless of which load combina-
tions are used to design for strength, where overall structure
84
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
Stability (such as stability against overturning, sliding, or
buoyancy) is being verified, use of the load combinations
specified in Section 1605A.2 or 1605A.3 shall be permitted.
Where the load combinations specified in Section 1605A.2
are used, strength reduction factors applicable to soil resis-
tance shall be provided by a registered design professional.
The stability of retaining walls shall be verified in accor-
dance with Section 1807A.2.3. When using allowable stress
design, factor of safety for soil bearing values shall not be
less than the overstrength factor of the structures supported.
1605A.2 Load combinations using strength design or load
and resistance factor design.
1605A.2.1 Basic load combinations. Where strength
design or load and resistance factor design is used, struc-
tures and portions thereof shall resist the most critical
effects from the following combinations of factored loads:
1.4(D + F)
1.2(D + F+D+1.6(L + iiO +
Q.5{L,orSorR)
(Equation 16A-1)
(Equation 16A -2)
(Equation 16A -3)
(Equation 16A -4)
(Equation 16A-5)
(Equation 16A-6)
(Equation 16A-7)
L2D + 1 .6(4 or 5 or 7?) + {f,L or 0.8 W)
1.2D+1.6W+/iL+0.5(L,or5ori?)
1.2D+1.0^+/iL+/25
0.9Z)+1.6W+1.6//
0.9D+\.0E+\.m
where:
/i = 1 for floors in places of pubhc assembly, for live loads
in excess of 100 pounds per square foot (4.79 kN/m^),
and for parking garage live load, and
= 0.5 for other Hve loads.
f^ = 0.7 for roof configurations (such as saw tooth) that do
not shed snow off the structure, and
= 0.2 for other roof configurations.
Exception: Where other factored load combinations are
specifically required by the provisions of this code, such
combinations shall take precedence.
1605A.2.2 Flood loads. Where flood loads, F^, are to be
considered in the design, the load combinations of Section
2.3.3 of ASCE 7 shall be used.
1605A.3 Load combinations using allowable stress design.
1605A.3.1 Basic load combinations. Where allowable
stress design (working stress design), as permitted by this
code, is used, structures and portions thereof shall resist the
most critical effects resulting from the following combina-
tions of loads:
D+H+F-^L-s-T
D + H+F+{L,ovSorR)
D + // + F + 0.75(L + D +
0.75(L,or5ori?)
(Equation 16A-8)
(Equation 16A-9)
(Equation 16A-10)
(Equation 16A-11)
D + H+F+{WoxQ.lE)
D + H + F + 0.75( W or 0.1 E) +
0.75L + 0.75(L,or^or/?)
0.6D + W+/f
0.6D + 0.7F+//
Exceptions:
(Equation 16A-12)
(Equation 16A-13)
(Equation 16A-14)
(Equation 16A-15)
1 . Crane hook loads need not be combined with roof
Hve load or with more than three-fourths of the
snow load or one-half of the wind load.
2. Flat roof snow loads of 30 psf ( 1 .44 kN/m^) or less
and roof live loads of 30 psf or less need not be
combined with seismic loads. Where flat roof
snow loads exceed 30 psf (1 .44 kN/m^), 20 percent
shall be combined with seismic loads.
1605A.3.1.1 Stress increases. Increases in allowable
stresses specified in the appropriate material chapter or
the referenced standards shall not be used with the load
combinations of Section 1605A.3.1, except that
increases shall be permitted in accordance with Chapter
23.
1605A.3.1.2 Flood loads. Where flood loads, F^, are to
be considered in design, the load combinations of Sec-
tion 2.4.2 of ASCE 7 shall be used.
1605A.3.2 Alternative basic load combinations. In lieu of the
basic load combinations specified in Section 1605A.3.1, struc-
tures and portions thereof shall be permitted to be designed for
the most critical effects resulting from the following combina-
tions. When using these alternative basic load combinations
that include wind or seismic loads, allowable stresses are per-
mitted to be increased or load combinations reduced where
permitted by the material chapter of this code or the referenced
standards. For load combinations that include the counteract-
ing effects of dead and wind loads, only two-thirds of the mini-
mum dead load likely to be in place during a design wind event
shall be used. Where wind loads are calculated in accordance
with Chapter 6 of ASCE 7, the coefficient (O in the following
equations shall be taken as 1 .3. For other wind loads, co shall be
taken as 1. When using these alternative load combinations to
evaluate sliding, overturning and soil bearing at the soil- struc-
ture interface, the reduction of foundation overturning from
Section 12. 13.4 in ASCE 7 shall not be used. When using these
alternative basic load combinations for proportioning founda-
tions for loadings, which include seismic loads, the vertical
seismic load effect, E^, m Equation 12.4-4 of ASCE 7 is permit-
ted to be taken equal to zero.
D + L-\-iL,ovS or R)
D+L + (coW)
D+L^(oW+S/2
Z)+L-H5-hC0W2
z)-hl+5-^£:/L4
(Equation 16A- 16)
(Equation 16A-17)
(Equation 16A-18)
(Equation 16A-19)
(Equation 16A-20)
2010 CALIFORNIA BUILDING CODE
85
STRUCTURAL DESIGN
0.9D + E/L4
(Equation 16A-21)
TABLE 16074.1
Exceptions:
1 . Crane hook loads need not be combined with roof live
loads or with more than three-fourths of the snow load
or one-half of the wind load.
2. Flat roof snow loads of 30 psf ( 1 .44 kN/m^) or less and
roof live loads of 30 psf or less need not be combined
with seismic loads. Where flat roof snow loads
exceed 30 psf (1 .44 kN/m^), 20 percent shall be com-
bined with seismic loads.
1605A. 3.2.1 Other loads. Where F, // or Tare to be con-
sidered in the design, each appUcable load shall be added
to the combinations specified in Section 1605A.3.2.
1605 A A Heliports and helistops. Heliport and helistop land-
ing areas shall be designed for the following loads, combined
in accordance with Section 1605 A:
1. Dead load, D, plus the gross weight of the helicopter, Df^,
plus snow load, 5.
2. Dead load, D, plus two single concentrated impact loads,
L, approximately 8 feet (2438 mm) apart applied any-
where on the touchdown pad (representing each of the
helicopter's two main landing gear, whether skid type or
wheeled type), having a magnitude of 0.75 times the
gross weight of the helicopter. Both loads acting together
total 1.5 times the gross weight of the helicopter.
3. Deadload, A plus auniform live load, L, of 100 psf (4.79
kN/m2).
SECTION 16064
DEAD LOADS
1606A.1 General. Dead loads are those loads defined in Sec-
tion 1 602A. 1 . Dead loads shall be considered permanent loads.
1606A.2 Design dead load. For purposes of design, the actual
weights of materials of construction and fixed service equip-
ment shall be used. In the absence of definite information, val-
ues used shall be subject to the approval of the building official.
1606A3 Roof dead loads. The design dead load shall provide
for the weight of at least one additional roof covering in addi-
tion to other applicable loadings if the new roof covering is
permitted to be applied over the original roofing without its
removal, in accordance with Section 1510,
SECTION 16074
LIVE LOADS
1607A.1 General. Live loads are those loads defined in Sec-
tion 1602A.1.
1607A.2 Loads not specified. For occupancies or uses not des-
ignated in Table 1607A. 1, the live load shall be determined in
accordance with a method approved by the building official.
1607A.3 Uniform live loads. The live loads used in the design
of buildings and other structures shall be the maximum loads
expected by the intended use or occupancy but shall in no case
be less than the minimum uniformly distributed unit loads
required by Table 1607A. 1.
MINIMUM CONCENTRATED LIVE L0ADS9
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
1. Apartments (see residential)
—
—
2. Access floor systems
Office use
Computer use
50
100
2,000
2,000
3. Armories and drill rooms
150
—
4. Assembly areas and theaters'*'^
Fixed seats (fastened to floor)
Follow spot, projections and control
rooms
Lobbies
Movable seats
Stages and platforms
Other assembly areas
60
50
100
100
125
100
—
5. Balconies (exterior) and decks^
Same as
occupancy
served
—
6. Bowling alleys
75
—
7. Catwalks
40
300
8. Cornices
60
—
9. Corridors, except as otherwise indicated
100
—
10. Dance halls and ballrooms
100
—
11. Dining rooms and restaurants
100
—
12. Dwellings (see residential)
—
—
13. Elevator machine room grating
(on area of 4 in^)
300
14. Finish light floor plate construction
(on area of 1 in^)
—
200
15. Fire escapes
On single-family dweUings only
100
40
—
16. Garages (passenger vehicles only)
Trucks and buses
40 Note a
See Section 1607A.6
17. Grandstands
(see stadium and arena bleachers)
—
—
18. Gynmasiums,^ main floors and balconies
100
—
19. Handrails, guards and grab bars
See Section 1607A.7
20. Hospitals
Corridors above first floor
Operating rooms, laboratories
Patient rooms
Mechanical and electrical equipment
areas including open areas around
equipment
Storage
Light
Heavy
Dining Area (not used for assembly)
Kitchen and serving areas
100
60
40
50
125
250
100
50
1,000
1,000
1,000
1,000
1,000
(continued)
86
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 16074.1— continued
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L^,
MINIMUM CONCENTRATED LIVE LOADS^
AND
TABLE 1607A.1— continued
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L^ AND I
MINIMUM CONCENTRATED LIVE LOADS^
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
21. Hotels (see residential)
22. Libraries'"
Corridors above first floor
Reading rooms
Stack rooms
80
60
ISO''
1,000
1,000
1,000
23. Manufacturing
Heavy
Light
250
125
3,000
2,000
24. Marquees
75
—
25. Office buildings'"
Corridors above first floor
File and computer rooms shall be
designed for heavier loads based
on anticipated occupancy
Lobbies and first-floor corridors
Offices
80
100
50
2,000
2,000
2,000
26. Penal institutions
. Cell blocks
Corridors
40
100
—
27. Residential
One- and two-family dwellings
Uninhabitable attics without storage^
Uninhabitable attics with limited
storage^'-''''
Habitable attics and sleeping areas
All other areas
Hotels and multifamily dwellings
Private rooms and corridors
serving them
Public rooms and corridors serving
them
10
20
30
40
40
100
—
28. Reviewing stands, grandstands and
bleachers^
Note c
29. Roofs
All roof surfaces subject to maintenance
workers
Awnings and canopies
Fabric construction supported by a
lightweight rigid skeleton structure
All other construction
Ordinary flat, pitched, and curved roofs
Primary roof members, exposed to a
work floor
Single panel point of lower chord of
roof trusses or any point along
primary structural members
supporting roofs:
Over manufacturing, storage
warehouses, and repair
garages
All other occupancies
Roofs used for other special purposes
Roofs used for promenade purposes
Roofs used for roof gardens or
assembly purposes
5
nonreducible
20
20
Notel
60
100
300
2,000
300
Notel
30. Schools'"
Classrooms
Corridors above first floor
First-floor corridors
40^
80
100
1,000
1,000
1,000
OCCUPANCY OR USE
UNIFORM
(psf)
CONCENTRATED
(lbs.)
31. Scuttles, skylight ribs and accessible
ceilings
200
32. Sidewalks, vehicular driveways and
yards, subject to trucking
250^
8,000^
33. Skating rinks
100
—
34. Stadiums and arenas
Bleachers^
Fixed seats (fastened to floor)
100^=
60^
—
35. Stairs and exits
One- and two-family dwellings
All other
40
100
Notef
36. Storage warehouses
(shall be designed for heavier loads if
required for anticipated storage)
Heavy
Light
250
125
37. Stores
Retail
First floor
Upper floors
Wholesale, all floors
100
75
125
1,000
1,000
1,000
38. Vehicle barrier systems
See Section 1607A.7.3
39. Walkways and elevated platforms
(other than exitways)
60
—
40. Yards and terraces, pedestrians^
100
—
41. Storage racks and wall-hung cabinets.
Total
loads""
—
continued
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm^,
1 square foot = 0.0929 m',
1 pound per square foot = 0.0479 kN/m', 1 pound = 0.004448 kN,
1 pound per cubic foot = 16 kgAn^
a. Floors in garages or portions of buildings used for the storage of motor vehicles shall be
designed for the uniformly distributed live loads of Table 1607A. 1 or the following con-
centrated loads: (1) for garages restricted to passenger vehicles accommodating not
more than nine passengers, 3,000 pounds acting on an area of 4.5 inches by 4.5 inches;
(2) for mechanical parking structures without slab or deck which are used for storing
passenger vehicles only, 2,250 pounds per wheel.
b. The loading applies to stack room floors that support nonmobile, double-faced library
bookstacks, subject to the following limitations:
1. The nominal bookstack unit height shall not exceed 90 inches;
2. The nominal shelf depth shall not exceed 12 inches for each face; and
3. Parallel rows of double-faced bookstacks shall be separated by aisles not less
than 36 inches wide.
c. Design in accordance with ICC 300.
d. Other uniform loads in accordance with an approved method which contains provisions
for truck loadings shall also be considered where appropriate.
e. The concentrated wheel load shall be applied on an area of 4.5 inches by 4.5 inches.
f . Minimum concentrated load on stair treads (on area of 4 square inches) is 300 pounds.
g. Where snow loads occur that are in excess of the design conditions, the structure shall
be designed to support the loads due to the increased loads caused by drift buildup or a
greater snow design determined by the building official (see Section 1608 A). For spe-
cial-purpose roofs, see Section 1607A.1 1 .2.2.
h. See Section 1604A.8.3 for decks attached to exterior walls.
i. Attics without storage are those where the maximum clear height between the joist and
rafter is less than 42 inches, or where there are not two or more adjacent trusses with the
same web configuration capable of containing a rectangle 42 inches high by 2 feet
wide, or greater, located within the plane of the truss. For attics without storage, this live
load need not be assumed to act concurrently with any other live load requirements.
j. For attics with limited storage and constructed with trusses, this five load need only be
applied to those portions of the bottom chord where there are two or more adjacent
trusses with the same web configuration capable of containing a rectangle 42 inches
high by 2 feet wide or greater, located within the plane of the truss. The rectangle shall
fit between the top of the bottom chord and the bottom of any other truss member, pro-
vided that each of the following criteria is met:
2010 CALIFORNIA BUILDING CODE
87
STRUCTURAL DESIGN
i. The attic area is accessible by a pull-down stairway or framed opening in accor-
dance with Section 1209.2, and
ii. The truss shall have a bottom chord pitch less than 2: 12.
iii. Bottom chords of trusses shall be designed for the greater of actual imposed dead
load or 10 psf, uniformly distributed over the entire span,
k. Attic spaces served by a fixed stair shall be designed to support the minimum live load
specified for habitable attics and sleeping rooms.
1. Roofs used for other special purposes shall be designed for appropriate loads as
approved by the building official.
m. The minimum vertical design live load shall be as follows:
Paper media:
12~inch-deep shelf 33 pounds per lineal foot
} 5-inch-deep shelf 41 pounds per lineal foot, or
3 3 pounds per cubic foot per total volume of the rack or cabinet, whichever is less.
Film media:
18-inch-deep shelf 100 pounds per lineal foot, or
50 pounds per cubic foot per total volume of the rack or cabinet, whichever is less.
Other media:
20 pounds per cubicfoot or 20 pounds per square foot, whichever is less, but not less
than actual loads,
n. [DSA-SSJ The following minimum loads for stage accessories apply:
1. Gridirons and fly galleries: 75 pounds per square foot uniform live load.
2. Loft block wells: 250 pounds per lineal foot vertical load and lateral load.
3. Head block wells and sheave beams: 250 pounds per lineal foot vertical loadand
lateral load. Head block wells and sheave beams shall be designed for all tribu-
tary loft block well loads. Sheave blocks shall be designed with a safety factor of
five.
4. Scenery beams where there is no gridiron: 300 pounds per lineal foot vertical
load and lateral load.
5. Ceiling framing over stages shall be designed for a uniform live load of 20
pounds per square foot. For members supporting a tributary area of 200 square
feet or more, this additional loadmay be reduced to 15 pounds per square foot.
o. [DSA-SSl The minimum uniform live load for classroom occupancies is 50 psf
p. [DSA-SS] The minimum uniform live load for a press box floor or accessible roof with
railing is 100 psf
q. [DSA -SS] Item 40 applies to pedestrian bridges and walkways that are not subjected to
uncontrolled vehicle access.
1607A.4 Concentrated loads. Floors and other similar sur-
faces shall be designed to support the uniformly distributed live
loads prescribed in Section 1607A.3 or the concentrated load,
in pounds (kilonewtons), given in Table 1607A.1, whichever
produces the greater load effects. Unless otherwise specified,
the indicated concentration shall be assumed to be uniformly
distributed over an area 2V2 feet by 2V2 feet [6V4 square feet
(0.58 m^)] and shall be located so as to produce the maximum
load effects in the structural members.
1607A.5 Partition loads. In office buildings and in other
buildings where partition locations are subject to change, pro-
visions for partition weight shall be made, whether or not parti-
tions are shown on the construction documents, unless the
specified live load exceeds 80 psf (3.83 kN/m^). The partition
load shall not be less than a uniformly distributed live load of
15psf(0.74kN/m^).
1607A.6 Truck and bus garages. Minimum live loads for
garages having trucks or buses shall be as specified in Table
1607 A.6, but shall not be less than 50 psf (2.40 kN/m^), unless
other loads are specifically justified and approved by the build-
if^g official. Actual loads shall be used where they are greater
than the loads specified in the table.
1607A.6.1 Truck and bus garage live load application.
The concentrated load and uniform load shall be uniformly
distributed over a 10-foot (3048 mm) width on a line normal
to the centerline of the lane placed within a 12-foot- wide
(3658 mm) lane. The loads shall be placed within their indi-
vidual lanes so as to produce the maximum stress in each
structural member. Single spans shall be designed for the
uniform load in Table 1607 A. 6 and one simultaneous con-
centrated load positioned to produce the maximum effect.
Multiple spans shall be designed for the uniform load in
Table 1607 A.6 on the spans and two simultaneous concen-
trated loads in two spans positioned to produce the maxi-
mum negative moment effect. Multiple span design loads,
for other effects, shall be the same as for single spans.
TABLE 1607A.6
UNIFORM AND CONCENTRATED LOADS
LOADING
CLASS^
UNIFORM LOAD
(pounds/linear
foot of lane)
CONCENTRATED LOAD
(pounds)''
For moment
design
For shear
design
H20-44 and HS20-44
640
18,000
26,000
H15-44andHSI5-44
480
13,500
19,500
For SI: 1 pound per linear foot = 0.01459 kN/m, 1 pound = 0.004448 kN,
1 ton = 8.90 kN.
a. An H loading class designates a two-axle truck with a semitrailer. An HS
loading class designates a tractor truck with a semitrailer. The numbers fol-
lowing the letter classification indicate the gross weight in tons of the stan-
dard truck and the year the loadings were instituted.
b. See Section 1607 A.6. 1 for the loading of multiple spans.
1607A,7 Loads on handrails, guards, grab bars, shower
seats^ dressing room bench seats and vehicle barrier
systems. Handrails, guards, grab bars, accessible seats, accessi-
ble benches and vehicle barrier systems shall be designed and
constructed to the structural loading conditions set forth in this
section.
1607A.7.1 Handrails and guards. Handrails and guards
shall be designed to resist a load of 50 pounds per linear foot
(plf) (0.73 kN/m) applied in any direction at the top and to
transfer this load through the supports to the structure. Glass
handrail assemblies and guards shall also comply with Sec-
tion 2407.
Exceptions:
1 . For one- and two-family dwellings, only the single
concentrated load required by Section
1607A.7.L1 shall be applied.
2. In Group 1-3, F, H and S occupancies, for areas that
are not accessible to the general public and that
have an occupant load less than 50, the minimum
load shall be 20 pounds per foot (0.29 kN/m).
1607A.7,1.1 Concentrated load. Handrails and guards
shall be able to resist a single concentrated load of 200
pounds (0.89 kN), applied in any direction at any point
along the top, and to transfer this load through the supports
to the structure. This load need not be assumed to act con-
currently with the loads specified in Section 1607A.7.1.
1607A.7.1.2 Components. Intermediate rails (all those
except the handrail), balusters and panel fillers shall be
designed to withstand a horizontally applied normal load
of 50 pounds (0.22 kN) on an area equal to 1 square foot
(0.093 m^), including openings and space between rails.
Reactions due to this loading are not required to be super-
imposed with those of Section 1607A.7.1 or 1607A.7.1.1.
1607A.7.2 Grab bars, shower seats and dressing room
bench seats. Grab bars, shower seats and dressing room
bench seat systems shall be designed to resist a single concen-
trated load of 250 pounds (1.11 kN) applied in any direction
*•
88
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
at any point. [DSA-AC] See Chapter 11 A, Section 1127 AA,
and Chapter IIB, Sections 1115BJ.2 and 11 17B, 8, for grab
bars, shower seats and dressing room bench seatSy as appli-
cable.
1607A.7.3 Vehicle barrier systems. Vehicle barrier systems
for passenger vehicles shall be designed to resist a single load
of 6,000 pounds (26.70 kN) applied horizontally in any direc-
tion to the barrier system and shall have anchorage or attach-
ment capable of transmitting this load to the structure. For
design of the system, two loading conditions shall be ana-
lyzed. The first condition shall apply the load at a height of 1
foot, 6 inches (457 mm) above the floor or ramp surface. The
second loading condition shall apply the load at 2 feet, 3
inches (686 mm) above the floor or ramp surface. The more
severe load condition shall govern the design of the barrier
restraint system. The load shall be assumed to act on an area
not to exceed 1 square foot (0.0929 m^), and is not required to
be assumed to act concurrently with any handrail or guard
loadings specified in Section 1 607 A.7.1. Garages accommo-
dating trucks and buses shall be designed in accordance with
an approved method that contains provisions for traffic rail-
ings.
1607A.8 Impact loads. The live loads specified in Section
1607A.3 include allowance for impact conditions. Provisions
shall be made in the structural design for uses and loads that
involve unusual vibration and impact forces.
1607A.8.1 Elevators. Elevator loads shall be increased by
100 percent for impact and the structural supports shall be
designed within the limits of deflection prescribed by
ASMEA17.1.
1607A.8.2 Machinery. For the purpose of design, the weight
of machinery and moving loads shall be increased as follows
to allow for impact: (1) elevator machinery, 100 percent; (2)
light machinery, shaft- or motor-driven, 20 percent; (3) recip-
rocating machinery or power-driven units, 50 percent; (4)
hangers for floors or balconies, 33 percent. Percentages shall
be increased where specified by the manufacturer.
1607A.9 Reduction in live loads. Except for uniform live
loads at roofs, all other minimum uniformly distributed live
loads, L^, in Table 1607A.1 are permitted to be reduced in
accordance with Section 1607A.9.1 or 1607A.9.2. Roof uni-
form live loads, other than special purpose roofs of Section
1607A. 11.2.2, are permitted to be reduced in accordance with
Section 1607A.11.2. Roof uniform live loads of special pur-
pose roofs are permitted to be reduced in accordance with Sec-
tion 1607A.9.1 or 1607A.9.2.
1607A.9.1 General. Subject to the limitations of Sections
1607A.9.1.1 through 1607A,9.1.4, members for which a
value of Ki^A-j- is 400 square feet (37. 1 6 m^) or more are per-
mitted to be designed for a reduced live load in accordance
with the following equation:
/
L = L
0.25 -h
15
V
V^^
r J
(Equation 16A-22)
For SI: L = L I 0.25-H
4.57
^|K^
T )
where:
L - Reduced design live load per square foot (meter) of
area supported by the member.
L^ = Unreduced design live load per square foot (meter) of
area supported by the member (see Table 1607A.1).
Kjjj=^ Live load element factor (see Table 1607A.9.1).
Aj - Tributary area, in square feet (square meters).
L shall not be less than 0,50L^ for members supporting one
floor and L shall not be less than 0.40L^ for members sup-
porting two or more floors.
TABLE 1607y\.9.1
LIVE LOAD ELEMENT FACTOR, Ki_^
ELEMENT
/c,,
Interior columns
Exterior columns without cantilever slabs
4
4
Edge columns with cantilever slabs
3
Comer columns with cantilever slabs
Edge beams without cantilever slabs
Interior beams
2
2
2
All other members not identified above including:
Edge beams with cantilever slabs
Cantilever beams
One-way slabs
Two-way slabs
Members without provisions for continuous shear
transfer normal to their span
1
1607A.9.1.1 One-way slabs. The tributary area, A^, for
use in Equation 16A-22 for one-way slabs shall not
exceed an area defined by the slab span times a width
normal to the span of 1.5 times the slab span.
1607A.9.1.2 Heavy live loads. Live loads that exceed
100 psf (4.79 kN/m^) shall not be reduced.
Exceptions:
1. The live loads for members supporting two or
more floors are permitted to be reduced by a max-
imum of 20 percent, but the Hve load shall not be
less than L as calculated in Section 1607A.9.1.
2. For uses other than storage, where approved,
additional live load reductions shall be permit-
ted where shown by the registered design pro-
fessional that a rational approach has been used
and that such reductions are warranted.
1607A.9.1.3 Passenger vehicle garages. The live loads
shall not be reduced in passenger vehicle garages.
Exception: The live loads for members supporting
two or more floors are permitted to be reduced by a
maximum of 20 percent, but the Hve load shall not be
less than L as calculated in Section 1607A.9.1.
1607A.9.1.4 Group A occupancies. Live loads of 100
psf (4.79 kN/m^) and at areas where fixed seats are
located shall not be reduced in Group A occupancies.
1607A. 9.1.5 Roof members. Live loads of 100 psf (4.79
kN/m^) or less shall not be reduced for roof members
except as specified in Section 1607A. 1 1.2.
2010 CALIFORNIA BUILDING CODE
89
STRUCTURAL DESIGN
1607A. 9.2 Alternate floor live load reduction. As an alter-
native to Section 1 607A.9. 1 , floor live loads are permitted to
be reduced in accordance with the following provisions.
Such reductions shall apply to slab systems, beams, girders,
colunms, piers, walls and foundations.
1 . A reduction shall not be permitted in Group A occu-
pancies.
2. A reduction shall not be permitted where the live load
exceeds 100 psf (4.79 kN/m^) except that the design
live load for members supporting two or more floors
is permitted to be reduced by 20 percent.
Exception: For uses other than storage, where
approved, additional live load reductions shall be
permitted where shown by the registered design
professional that a rational approach has been used
and that such reductions are warranted.
3. A reduction shall not be permitted in passenger vehi-
cle parking garages except that the live loads for
members supporting two or more floors are permitted
to be reduced by a maximum of 20 percent.
4. For live loads not exceeding 100 psf (4.79 kN/m^), the
design live load for any structural member supporting
150 square feet (13.94 m^) or more is permitted to be
reduced in accordance with Equation 16A-23.
5. For one-way slabs, the area, A, for use in Equation
16A-23 shall not exceed the product of the slab span and
a width normal to the span of 0.5 times the slab span.
i? = 0.08(A-150)
(Equation 16A-23)
For SI: i? = 0.861(A- 13.94)
Such reduction shall not exceed the smallest of:
1 . 40 percent for horizontal members;
2. 60 percent for vertical members; or
3. /? as determined by the following equation.
/? = 23.1(l+D/4)
where:
(Equation 16A-24)
A = Area of floor supported by the member,
square feet (m^).
D = Dead load per square foot (m^) of area sup-
ported.
L^ = Unreduced live load per square foot (m^) of
area supported.
R = Reduction in percent.
1607A. 10 Distribution of floor loads. Where uniform floor
live loads are involved in the design of structural members
arranged so as to create continuity, the minimum applied loads
shall be the full dead loads on all spans in combination with the
floor live loads on spans selected to produce the greatest effect
at each location under consideration. It shall be permitted to
reduce floor live loads in accordance with Section 1607A.9.
1607A.11 Roof loads. The structural supports of roofs and
marquees shall be designed to resist wind and, where applica-
ble, snow and earthquake loads, in addition to the dead load of
construction and the appropriate live loads as prescribed in this
section, or as set forth in Table 1607A. 1. The live loads acting
on a sloping surface shall be assumed to act vertically on the
horizontal projection of that surface.
1607A.11.1 Distribution of roof loads. Where uniform
roof live loads are reduced to less than 20 psf (0.96 kN/m^)
in accordance with Section 1607A. 1 1 .2. 1 and are applied to
the design of structural members arranged so as to create
continuity, the reduced roof live load shall be applied to
adjacent spans or to alternate spans, whichever produces the
most unfavorable load effect. See Section 1607A.11.2 for
reductions in minimum roof live loads and Section 7.5 of
ASCE 7 for partial snow loading.
1607A.11.2 Reduction in roof live loads. The minimum
uniformly distributed live loads of roofs and marquees, L^,
in Table 1607A. 1 are permitted to be reduced in accordance
with Section 1607A. 11.2.1 or 1607A, 11.2.2.
1607A. 11.2.1 Flat, pitched and curved roofs. Ordinary
flat, pitched and curved roofs, and awnings and canopies
other than of fabric construction supported by hghtweight
rigid skeleton structures, are permitted to be designed for a
reduced roof live load as specified in the following equa-
tions or other controlling combinations of loads in Section
1605 A, whichever produces the greater load.
In structures such as greenhouses, where special scaf-
folding is used as a work surface for workers and materi-
als during maintenance and repair operations, a lower
roof load than specified in the following equations shall
not be used unless approved by the building official.
Such structures shall be designed for a minimum roof
live load of 12 psf (0.58 kN/m^).
L^ = L^RjR2
(Equation 16A-25)
where: 12 < L, < 20
For SI: L, = LJljRz
where: 0.58 <L,< 0.96
L^ = Reduced live load per square foot (mj) of horizon-
tal projection in pounds per square foot (kN/m2).
The reduction factors Rj and R2 shall be determined as
follows:
Rj ^ 1 for A, < 200 square feet
(18.58 m2) (Equation 16A-26)
Rj = l2~ O.OOIA, for 200 square
feet <Af< 600 square feet (Equation 16A -27)
For SI: 1. 2 - 0.0 1 lA, for 18.58 square meters < A, < 55. 74
square meters
Rj = 0.6 for A, > 600 square feet
(55.74 m^) (Equation 16A-28)
where:
A^ = Tributary area (span length multiplied by effective
width) in square feet (m^) supported by any struc-
tural member, and
/?2= 1 forF<4 (Equation 16A-29)
/?3=1.2-0.05Ffor4<F<12 (Equation 16A -30)
90
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
R2 = 0.6 for F > 1 2 (Equation 16A-31)
where:
F = For a sloped roof, the number of inches of rise per
foot (for SI: F= 0.12 X slope, with slope expressed
as a percentage), or for an arch or dome, the
rise-to-span ratio multiplied by 32.
1607A. 11.2.2 Special-purpose roofs. Roofs used for
promenade purposes, roof gardens, assembly purposes
or other special purposes, and marquees, shall be
designed for a minimum live load, L^, as specified in
Table 1607A.1. Such live loads are permitted to be
reduced in accordance with Section 1607A.9. Live loads
of 100 psf (4.79 kN/m^) or more at areas of roofs classi-
fied as Group A occupancies shall not be reduced.
1607A. 11,3 Landscaped roofs. Where roofs are to be land-
scaped, the uniform design live load in the landscaped area
shall be 20 psf (0.958 kN/m^). The weight of the landscap-
ing materials shall be considered as dead load and shall be
computed on the basis of saturation of the soil.
1607A.11.4 Awnings and canopies. Awnings and canopies
shall be designed for uniform live loads as required in Table
1607A. 1 as well as for snow loads and wind loads as speci-
fied in Sections 1608A and 1609A.
I I 1607A.11.5 Uncovered open-frame roof structures.
Uncovered open-frame roof structures shall be designed for
a vertical live load of not less than 10 pounds per square
foot (0.48 kN/m^) of the total area encompassed by the
framework.
1607A.12 Crane loads. The crane live load shall be the rated
capacity of the crane. Design loads for the runway beams,
including connections and support brackets, of moving bridge
cranes and monorail cranes shall include the maximum wheel
loads of the crane and the vertical impact, lateral and longitudi-
nal forces induced by the moving crane.
1607A.12.1 Maximum wheel load. The maximum wheel
loads shall be the wheel loads produced by the weight of the
bridge, as applicable, plus the sum of the rated capacity and the
weight of the trolley with the trolley positioned on its runway at
the location where the resulting load effect is maximum.
1607A.12.2 Vertical impact force. The maximum wheel
loads of the crane shall be increased by the percentages
shown below to determine the induced vertical impact or
vibration force:
Monorail cranes (powered) • • • 25 percent
Cab-operated or remotely operated
bridge cranes (powered) 25 percent
Pendant-operated bridge cranes
(powered) lOpercent
Bridge cranes or monorail cranes with
hand-geared bridge, trolley and hoist percent
1607A.12.3 Lateral force. The lateral force on crane run-
way beams with electrically powered trolleys shall be calcu-
lated as 20 percent of the sum of the rated capacity of the
crane and the weight of the hoist and trolley. The lateral
force shall be assumed to act horizontally at the traction sur-
face of a runway beam, in either direction perpendicular to
the beam, and shall be distributed according to the lateral
stiffness of the runway beam and supporting structure.
1607A.12.4 Longitudinal force. The longitudinal force on
crane runway beams, except for bridge cranes with
hand-geared bridges, shall be calculated as 10 percent of the
maximum wheel loads of the crane. The longitudinal force
shall be assumed to act horizontally at the traction surface of
a runway beam, in either direction parallel to the beam.
1607A.13 Interior walls and partitions. Interior walls and
partitions that exceed 6 feet (1829 mm) in height, including
their finish materials, shall have adequate strength to resist the
loads to which they are subjected but not less than a horizontal
load of 5 psf (0.240 kN/m^). The 5 psf (0.24 kN/m') load need
not be applied simultaneously with wind or seismic loads. The
deflection of such walls under a load of 5 psf (0.24 kN/m^) shall
not exceed the limits in Table 1604A.3.
Exception: Fabric partitions complying with Section
1607A. 13.1 shall not be required to resist the minimum hor-
izontal load of 5 psf (0.24 kN/m^).
1607A.13.1 Fabric partitions. Fabric partitions that
exceed 6 feet (1829 mm) in height, including their finish
materials, shall have adequate strength to resist the follow-
ing load conditions:
1. A horizontal distributed load of 5 psf (0.24 kN/m^)
applied to the partition framing. The total area used to
determine the distributed load shall be the area of the
fabric face between the framing members to which
the fabric is attached. The total distributed load shall
be uniformly applied to such framing members in
proportion to the length of each member.
2. A concentrated load of 40 pounds (0. 176 kN) applied
to an 8-inch diameter (203 mm) area [50.3 square
inches (32 452 mm^)] of the fabric face at a height of
54 inches (1372 mm) above the floor.
SECTION 1608/4
SNOW LOADS
1608A.1 General. Design snow loads shall be determined in
accordance with Chapter 7 of ASCE 7, but the design roof load
shall not be less than that determined by Section 1607A.
1608A,2 Ground snow loads. The ground snow loads to be
used in determining the design snow loads for roofs shall be
determined in accordance with ASCE 7 or Figure 1608A.2 for
the contiguous United States. Site-specific case studies shall be
made in areas designated "CS" in Figure 1608A.2. Ground snow
loads for sites at elevations above the limits indicated in Figure
1608A.2 and for all sites within the CS areas shall be approved.
Ground snow load determination for such sites shall be based on
an extreme value statistical analysis of data available in the
vicinity of the site using a value with a 2-percent annual proba-
bihty of being exceeded (50-year mean recurrence interval).
1608A,3 Determination of snow loads. [DSA-SS] The
ground snow load or the design snow load for roofs shall con-
form with the adopted ordinance of the city, county, or city
and county in which the project site is located, and shall be
approved by DSA.
II
2010 CALIFORNIA BUILDING CODE
91
STRUCTURAL DESIGN
(100)
(400)
10
(300)
In CS areas, site-specific Case Studies are required to
establish ground snow loads. Extreme local variations in
ground snow loads in tliese areas preclude mapping at
this scale.
Numbers in parentheses represent the upper elevation
limits in feet for the ground snow load values presented
below. Site -specific case studies are required to estab-
lish ground snow loads at elevations not covered.
To convert Ib/sq ft to kNm^ multiply by 0.0479.
To convert feet to meters, multiply by 0.3048.
J I I L.
J
100
200
300 miles
FIGURE 16084.2
GROUND SNOW LOADS, Pg, FOR THE UNITED STATES (psf)
92
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
FIGURE 1608A2-contmued
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf)
2010 CALIFORNIA BUILDING CODE
93
STRUCTURAL DESIGN
SECTION 160M
WIND LOADS
1609A.1 Applications. Buildings, structures and parts thereof
shall be designed to withstand the minimum wind loads pre-
scribed herein. Decreases in wind loads shall not be made for
the effect of shielding by other structures.
1609A.1.1 Determination of wind loads. Wind loads on
every building or structure shall be determined in accor-
dance with Chapter 6 of ASCE 7 or provisions of the alter-
nate all-heights method in Section 1609A.6. The type of
opening protection required, the basic wind speed and the
exposure category for a site is permitted to be determined in
accordance with Section 1609A or ASCE 7. Wind shall be
assumed to come from any horizontal direction and wind
pressures shall be assumed to act normal to the surface con-
sidered.
Exceptions:
1 . Subject to the limitations of Section 1609A. 1.1.1,
the provisions of ICC 600 shall be permitted for
apphcable Group R-2 and R-3 buildings.
2. Subject to the limitations of Section 1 609A. 1.1.1,
residential structures using the provisions of the
AF&PA WFCM.
3. Subject to the limitations of Section 1609A. 1.1.1,
residential structures using the provisions of AISI
S230.
4. Designs using NAAMM FP 1001.
5. Designs using TIA-222 for antenna-supporting
structures and antennas.
6. Wind tunnel tests in accordance with Section 6.6
of ASCE 7, subject to the limitations in Section
1609A. 1,1.2.
1609A. 1.1.1 Applicability. The provisions of ICC 600
are applicable only to buildings located within Exposure
B or C as defined in Section 1609A.4. The provisions of
ICC 600, AFcfePA WFCM and AISI S230 shall not apply
to buildings sited on the upper half of an isolated hill,
ridge or escarpment meeting the following conditions:
L The hill, ridge or escarpment is 60 feet (18 288
mm) or higher if located in Exposure B or 30 feet
(9144 mm) or higher if located in Exposure C;
2. The maximum average slope of the hill exceeds 10
percent; and
3. The hill, ridge or escarpment is unobstructed
upwind by other such topographic features for a
distance from the high point of 50 times the height
of the hill or 1 mile (1.61 km), whichever is
greater.
1609A. 1.1.2 Wind tunnel test limitations. The lower
limit on pressures for main wind-force-resisting systems
and components and cladding shall be in accordance
with Sections 1609A. 1.1.2.1 and 1609A. 1.1.2.2.
1609A. 1.1.2.1 Lower limits on main wind-
force-resisting system. Base overturning moments
determined from wind tunnel testing shall be limited
to not less than 80 percent of the design base overturn-
ing moments determined in accordance with Section
6.5 of ASCE 7, unless specific testing is performed
that demonstrates it is the aerodynamic coefficient of
the building, rather than shielding from other struc-
tures, that is responsible for the lower values. The
80-percent limit shall be permitted to be adjusted by
the ratio of the frame load at critical wind directions as
determined from wind tunnel testing without specific
adjacent buildings, but including appropriate upwind
roughness, to that determined in Section 6.5 of ASCE
7.
1609A. 1.1.2.2 Lower limits on components and
cladding. The design pressures for components and
cladding on walls or roofs shall be selected as the
greater of the wind tunnel test results or 80 percent of
the pressure obtained for Zone 4 for walls and Zone 1
for roofs as determined in Section 6.5 of ASCE 7,
unless specific testing is performed that demonstrates
it is the aerodynamic coefficient of the building,
rather than shielding from nearby structures, that is
responsible for the lower values. Alternatively, lim-
ited tests at a few wind directions without specific
adjacent buildings, but in the presence of an appropri-
ate upwind roughness, shall be permitted to be used to
demonstrate that the lower pressures are due to the
shape of the building and not to shielding.
1609AAJ,3 Special wind regions. [DSA-SS] The basic
wind speed for projects located in special wind regions
as defined in Figure 1609A shall conform with the
adopted ordinance of the city, county or city and county
in which the project site is located, and shall be approved
by DSA'SS,
1609A.1.2 Protection of openings. In wind-borne debris
regions, glazing in buildings shall be impact resistant or pro-
tected with an impact-resistant covering meeting the
requirements of an approved impact-resistant standard or
ASTM E 1996 and ASTM E 1886 referenced herein as fol-
lows:
1 . Glazed openings located within 30 feet (9144 mm) of
grade shall meet the requirements of the large missile
test of ASTM E 1996.
2. Glazed openings located more than 30 feet (9144
mm) above grade shall meet the provisions of the
small missile test of ASTM E 1996.
Exceptions:
1 . Wood structural panels with a minimum thickness
of Vi6 inch (11.1 mm) and maximum panel span of
8 feet (2438 mm) shall be permitted for opening
protection in one- and two-story buildings classi-
fied as Group R-3 or R-4 occupancy. Panels shall
be precut so that they shall be attached to the fram-
ing surrounding the opening containing the prod-
uct with the glazed opening. Panels shall be
predrilled as required for the anchorage method
and shall be secured with the attachment hardware
provided. Attachments shall be designed to resist
94
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
the components and cladding loads determined in
accordance with the provisions of ASCE 7, with
corrosion-resistant attachment hardware provided
and anchors permanently installed on the building.
Attachment in accordance with Table 1609A.1.2
with corrosion-resistant attachment hardware pro-
vided and anchors permanently installed on the
building is permitted for buildings with a mean
roof height of 45 feet (13 716 mm) or less where
wind speeds do not exceed 140 mph (63 m/s).
2. Glazing in Occupancy Category I buildings as
defined in Section 1604A.5, including green-
houses that are occupied for growing plants on a
production or research basis, without public access
shall be permitted to be unprotected.
3. Glazing in Occupancy Category II, III or IV build-
ings located over 60 feet (18 288 mm) above the
ground and over 30 feet (9144 mm) above aggre-
gate surface roofs located within 1,500 feet (458
m) of the building shall be permitted to be unpro-
tected.
1609A. 1.2.1 Louvers. Louvers protecting intake and
exhaust ventilation ducts not assumed to be open that are
located within 30 feet (9144 mm) of grade shall meet
requirements of an approved impact-resisting standard
or the large missile test of ASTM E 1996.
1609A. 1.2,2 Garage doors. Garage door glazed open-
ing protection for wind-borne debris shall meet the
requirements of an approved impact-resisting standard
orANSI/DASMA115,
1609 AJ3 Story drift for wind loads. The calculated story
drift due to wind pressures shall not exceed 0.005 times the
story height for buildings less than 65 feet (19 812 mm) in
height or 0.004 times the story height for buildings 65 feet
(19 812 mm) or greater in height.
1609A.2 Definitions. The following words and terms shall, for
the purposes of Section 1609 A, have the meanings shown
herein.
TABLE1609A1.2
WIND-BORNE DEBRIS PROTECTION FASTENING
SCHEDULE FOR WOOD STRUCTURAL PANELS^' '''*^'*^
FASTENER
TYPE
FASTENER SPACING (inches)
Panel Span
<4feet
4feet<
Panel Span <
6 feet
6feet<
Panel Span <
8 feet
No. 8 wood-screw-based
anchor with 2-inch
embedment length
16
10
8
No. 10 wood-screw-based
anchor with 2-inch
embedment length
16
12
9
V4-inch diameter
lag-screw-based anchor
with 2-inch embedment
length
16
16
16
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N,
1 mile per hour = 0.447 m/s.
a. This table is based on 140 mph wind speeds and a 45-foot mean roof height.
b. Fasteners shall be installed at opposing ends of the wood structural panel.
Fasteners shall be located a minimum of 1 inch from the edge of the panel.
c. Anchors shall penetrate through the exterior wall covering with an
embedment length of 2 inches minimum into the building frame. Fasteners
shall be located a minimum of 2 V2 inches from the edge of concrete block or
concrete.
d. Where panels are attached to masonry or masonry/stucco, they shall be
attached using vibration-resistant anchors having a minimum ultimate with-
drawal capacity of 1,500 pounds.
HURRICANE-PRONE REGIONS.
hurricanes defined as:
Areas vulnerable to
1. The U. S. Atlantic Ocean and Gulf of Mexico coasts
where the basic wind speed is greater than 90 mph (40
m/s) and
2. Hawaii, Puerto Rico, Guam, Virgin Islands and Ameri-
can Samoa.
WIND-BORNE DEBRIS REGION. Portions of hurri-
cane-prone regions that are within 1 mile (1.61 km) of the
coastal mean high water line where the basic wind speed is 1 10
mph (48 m/s) or greater; or portions of hurricane -prone
regions where the basic wind speed is 120 mph (53 m/s) or
greater; or Hawaii.
TABLE 1 609 A3.1
EQUIVALENT BASIC WIND SPEEDS^'''
c
V^s
85
90
100
105
110
120
125
130
140
145
150
160
170
Vj^
71
76
85
90
95
104
109
114
123
128
133
142
152
For SI: 1 mile per hour = 0.44 m/s.
a. Linear interpolation is permitted.
b. V35 is the 3-second gust wind speed (mph).
c. Vj^ is the fastest mile wind speed (mph).
2010 CALIFORNIA BUILDING CODE
95
STRUCTURAL DESIGN
Notes:
1. Values are nominal design 3-second gust wind speeds in miles per hour (m/s) at 33 ft (10 m) abcve ground for Exposure C category.
2. Linear interpolation between wind contours is permitted.
3. Islands and coastal areas outside the last contour shall use the last wind speed contour of the coastal area.
4. Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
FIGURE 1609yt
BASIC WIND SPEED (3-SECOND GUST)
96
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1609A.3 Basic wind speed. The basic wind speed, in mph, for
the determination of the wind loads shall be determined by Fig-
ure 1609A. Basic wind speed for the special wind regions indi-
cated, near mountainous terrain and near gorges shall be in
accordance with local jurisdiction requirements. Basic wind
speeds determined by the local jurisdiction shall be in accor-
dance with Section 6.5.4 of ASCE 7.
In nonhurricane-prone regions, when the basic wind speed is
estimated from regional climatic data, the basic wind speed
shall be not less than the wind speed associated with an annual
probability of 0.02 (50-year mean recurrence interval), and the
estimate shall be adjusted for equivalence to a 3-second gust
wind speed at 33 feet (10 m) above ground in Exposure Cate-
gory C. The data analysis shall be performed in accordance
with Section 6.5.4.2 of ASCE 7.
1609A.3.1 Wind speed conversion. When required, the
3-second gust basic wind speeds of Figure 1609 A shall be
converted to fastest-mile wind speeds, V^, using Table
1609A.3.1 or Equation 16A-32.
Vfin =
(^3,-10.5)
1.05
(Equation 16A-32)
where:
V35 = 3-second gust basic wind speed from Figure 1609A.
1609A.4 Exposure category. For each wind direction consid-
ered, an exposure category that adequately reflects the charac-
teristics of ground surface irregularities shall be determined for
the site at which the building or structure is to be constructed.
Account shall be taken of variations in ground surface rough-
ness that arise from natural topography and vegetation as well
as from constructed features.
1609A.4.1 Wind directions and sectors. For each selected
wind direction at which the wind loads are to be evaluated,
the exposure of the building or structure shall be determined
for the two upwind sectors extending 45 degrees (0.79 rad)
either side of the selected wind direction. The exposures in
these two sectors shall be determined in accordance with
Sections 1609A.4.2 and 1609A.4.3 and the exposure result-
ing in the highest wind loads shall be used to represent
winds from that direction.
1609A.4.2 Surface rougliness categories. A ground sur-
face roughness within each 45-degree (0.79 rad) sector shall
be determined for a distance upwind of the site as defined in
Section 1609A.4.3 from the categories defined below, for
the purpose of assigning an exposure category as defined in
Section 1609A.4.3.
Surface Roughness B. Urban and suburban areas,
wooded areas or other terrain with numerous closely
spaced obstructions having the size of single-family
dwellings or larger.
Surface Roughness C. Open terrain with scattered
obstructions having heights generally less than 30 feet
(9144 mm). This category includes flat open country,
grasslands, and all water surfaces in hurricane-prone
regions.
Surface Roughness D. Flat, unobstructed areas and
water surfaces outside hurricane-prone regions. This
category includes smooth mud flats, salt flats and unbro-
ken ice.
1609A.4.3 Exposure categories. An exposure category
shall be determined in accordance with the following:
Exposure B. Exposure B shall apply where the ground
surface roughness condition, as defined by Surface
Roughness B, prevails in the upwind direction for a dis-
tance of at least 2,600 feet (792 m) or 20 times the height
of the building, whichever is greater.
Exception: For buildings whose mean roof height is
less than or equal to 30 feet (9 1 44 mm), the upwind dis-
tance is permitted to be reduced to 1 ,500 feet (457 m).
Exposure C. Exposure C shall apply for all cases where
Exposures B or D do not apply.
Exposure D. Exposure D shall apply where the ground
surface roughness, as defined by Surface Roughness D,
prevails in the upwind direction for a distance of at least
5,000 feet (1524 m) or 20 times the height of the build-
ing, whichever is greater. Exposure D shall extend inland
from the shorehne for a distance of 600 feet (183 m) or 20
times the height of the building, whichever is greater.
1609A.5 Roof systems.
1609A.5.1 Roof deck. The roof deck shall be designed to
withstand the wind pressures determined in accordance
with ASCE 7.
1609A.5.2 Roof coverings. Roof coverings shall comply
with Section 1609A.5.1.
Exception: Rigid tile roof coverings that are air perme-
able and installed over a roof deck complying with Sec-
tion 1609A.5.1 are permitted to be designed in
accordance with Section 1609A.5.3.
Asphalt shingles installed over a roof deck complying
with Section 1609A.5.1 shall comply with the wind-resis-
tance requirements of Section 1507.2.7.1.
1609A.5.3 Rigid tile. Wind loads on rigid tile roof cover-
ings shall be determined in accordance with the following
equation:
M^ = q,C,bLL^[\.0-GC^]
(Equation 16A-33)
For SI: M^ =
1,000
where:
b
Exposed width, feet (mm) of the roof tile.
Lift coefficient. The lift coefficient for concrete and
clay tile shall be 0.2 or shall be determined by test in
accordance with Section 1716.2.
GCp= Roof pressure coefficient for each applicable roof
zone determined from Chapter 6 of ASCE 7. Roof
coefficients shall not be adjusted for internal pres-
sure.
2010 CALIFORNIA BUILDING CODE
97
STRUCTURAL DESIGN
L = Length, feet (mm) of the roof tile.
L^ = Moment arm, feet (mm) from the axis of rotation to
the point of uplift on the roof tile. The point of uplift
shall be taken at 0.76L from the head of the tile and
the middle of the exposed width. For roof tiles with
nails or screws (with or without a tail clip), the axis
of rotation shall be taken as the head of the tile for
direct deck application or as the top edge of the bat-
ten for battened applications. For roof tiles fastened
only by a nail or screw along the side of the tile, the
axis of rotation shall be determined by testing. For
roof tiles installed with battens and fastened only by
a clip near the tail of the tile, the moment arm shall
be determined about the top edge of the batten with
consideration given for the point of rotation of the
tiles based on straight bond or broken bond and the
tile profile.
M^ = Aerodynamic uplift moment, feet-pounds (N-mm)
acting to raise the tail of the tile.
qf^ = Wind velocity pressure, psf (kN/m^) determined
from Section 6.5.10 of ASCE 7.
Concrete and clay roof tiles complying with the following
limitations shall be designed to withstand the aerodynamic
uplift moment as determined by this section.
1. The roof tiles shall be either loose laid on battens,
mechanically fastened, mortar set or adhesive set.
2. The roof tiles shall be installed on solid sheathing
which has been designed as components and clad-
ding.
3. An underlayment shall be installed in accordance
with Chapter 15.
4. The tile shall be single lapped interlocking with a
minimum head lap of not less than 2 inches (5 1 mm).
5. The length of the tile shall be between 1.0 and 1.75
feet (305 mm and 533 mm).
6. The exposed width of the tile shall be between 0.67
and 1.25 feet (204 mm and 381 mm).
7. The maximum thickness of the tail of the tile shall not
exceed 1.3 inches (33 mm).
8. Roof tiles using mortar set or adhesive set systems
shall have at least two-thirds of the tile's area free of
mortar or adhesive contact.
1609A.6 Alternate all-heights method. The alternate wind
design provisions in this section are simplifications of the
ASCE 7 Method 2— Analytical Procedure.
1609A.6.1 Scope. As an alternative to ASCE 7 Section 6.5,
the following provisions are permitted to be used to deter-
mine the wind effects on regularly shaped buildings, or
other structures that are regularly shaped, which meet all of
the following conditions:
1 . The building or other structure is less than or equal to
75 feet (22 860 mm) in height with a height-to-least-
width ratio of 4 or less, or the building or other struc-
ture has a fundamental frequency greater than or
equal to 1 hertz.
2. The building or other structure is not sensitive to
dynamic effects.
3. The building or other structure is not located on a site
for which channeling effects or buffeting in the wake
of upwind obstructions warrant special consideration.
4. The building shall meet the requirements of a simple
diaphragm building as defined in ASCE 7 Section
6.2, where wind loads are only transmitted to the main
wind-force-resisting system (MWFRS) at the dia-
phragms.
5. For open buildings, multispan gable roofs, stepped
roofs, sawtooth roofs, domed roofs, roofs with slopes
greater than 45 degrees (0.79 rad), soHd free-standing
walls and solid signs, and rooftop equipment, apply
ASCE 7 provisions.
1609A.6.1.1 Modifications. The following modifica-
tions shall be made to certain subsections in ASCE 7: in
Section 1609A.6.2, symbols and notations that are spe-
cific to this section are used in conjunction with the sym-
bols and notations in ASCE 7 Section 6.3.
1609A.6.2 Symbols and notations. Coefficients and vari-
ables used in the alternative all-heights method equations
are as follows:
C„g, = Net-pressure coefficient based on K^ [(G) (Cp) -
{GCpi)], in accordance with Table 1609A.6.2(2).
G = Gust effect factor for rigid structures in accordance
with ASCE 7 Section 6.5.8.1.
/ = Importance Factor in accordance with ASCE 7
Section 6.5.5
K^ = Wind directionality factor in accordance with
ASCE 7 Table 6-4.
P„g^ = Design wind pressure to be used in determination
of wind loads on buildings or other structures or
their components and cladding, in psf (kN/m^).
q^ = Wind stagnation pressure in psf (kN/m^) in accor-
dance with Table 1609A.6.2(1).
TABLE 16094.6.2(1)
WIND VELOCITY PRESSURE (q^) AT STANDARD HEIGHT OF 33 FEEr
BASIC WIND SPEED (mph)
85
90
100
105
110
120
125
130
140
150
160
170
PRESSURE, q^ (psf)
18.5
20.7
25.6
28.2
31.0
36.9
40.0
43.3
50.2
57.6
65.5
74.0
For SI: 1 foot = 304.8 mm, 1 mph = 0.44 m/s, 1 psf = 47.88 Fa.
a. For basic wind speeds not shown, use q^ = 0.00256 V^.
98
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 16094.6.2(2)
NET PRESSURE COEFFICIENTS
f> a,b
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e, FACTOR
1 . Main wind-
force-resisting
frames and systems
Walls:
Enclosed
Partially enclosed
+ Internal
pressure
- Internal
pressure
+ internal
pressure
- Internal
pressure
Windward wall
0.43
0.73
0.11
1.05
Leeward wall
-0.51
-0.21
-0.83
0.11
Sidewail
-0.66
-0.35
-0.97
-0.04
Parapet wall
Windward
1.28
1.28
Leeward
-0.85
-0.85
Roofs:
Enclosed
Partially enclosed
Wind perpendicular to ridge
+ Internal
pressure
- Internal
pressure
+ Internal
pressure
- Internal
pressure
Leeward roof or flat roof
-0.66
-0.35
-0.97
-0.04
Windward roof slopes:
Slope < 2:12 (10°)
Condition 1
-1.09
-0.79
-1.41
-0.47
Condition 2
-0.28
0.02
-0.60
0.34
Slope = 4:12 (18°)
Condition 1
-0.73
-0.42
-1.04
-0.11
Condition 2
-0.05
0.25
-0.37
0.57
Slope = 5:12 (23°)
Condition 1
-0.58
-0.28
-0.90
0.04
Condition 2
0.03
0.34
-0.29
0.65
Slope = 6:12 (27°)
Condition 1
-0.47
-0.16
-0.78
0.15
Condition 2
0.06
0.37
-0.25
0.68
Slope = 7:12 (30°)
Condition 1
-0.37
-0.06
-0.68
0.25
Condition 2
0.07
0.37
-0.25
0.69
Slope 9:12 (37°)
Condition 1
-0.27
0.04
-0.58
0.35
Condition 2
0.14
0.44
-0.18
0.76
Slope 12:12 (45°)
0.14
0.44
-0.18
0.76
Wind parallel to ridge and flat roofs
-1.09
-0.79
-1.41
-0.47
Nonbuilding Structures: Chimneys, Tanks and Similar Structures:
h/D
1
7
25
Square (Wind normal to face)
0.99
1.07
1.53
Square (Wind on diagonal)
0.77
0.84
1.15
Hexagonal or Octagonal
0.81
0.97
1.13
Round
0.65
0.81
0.97
Open signs and lattice frameworks
Ratio of solid to gross area
<0.1
0.1 to 0.29
0.3 to 0.7
Rat
1.45
1.30
1.16
Round
0.87
0.94
1.08
(continued)
2010 CALIFORNIA BUILDING CODE
99
STRUCTURAL DESIGN
TABLE 16094.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C^et"'^
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e^ FACTOR
2. Components and
cladding not in
areas of disconti-
nuity — roofs and
overhangs
Roof elements and slopes
Enclosed
Partially enclosed
Gable of hipped configurations (Zone 1)
Hat < Slope < 6: 1 2 {IT) See ASCE 7 Figure 6- 11 C Zone 1
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.92
-1.23
Overhang: Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-1 IB Zone 1
Negative
10 square feet or less
-1.45
100 square feet or more
-1.36
500 square feet or more
-0.94
6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 6-llD Zone 1
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.83
-1.15
Monosloped configurations (Zone 1)
Enclosed
Partially enclosed
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 6-14B Zone 1
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.26
-1.57
100 square feet or more
-1.09
-1.40
Tall flat-topped roofs h > 60'
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 1) See ASCE 7 Figure 6-17 Zone 1
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.92
-1.23
•
(continued)
100
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 16094.6.2(2)— continuec
NET PRESSURE COEFFICIENTS, C,
1
let
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e, FACTOR
3. Components and clad-
ding in areas of dis-
continuities — ^roofs
and overhangs
Roof elements and slopes
Enclosed
Partially enclosed
Gable or hipped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-llC Zone 2
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
10.72
Negative
10 square feet or less
-1,68
-2.00
100 square feet or more
-1.17
-1.49
Overhang for Slope Flat < Slope < 6: 12 (27°) See ASCE 7 Figure 6-1 IC Zone 2
Negative
10 square feet or less
-1.87
100 square feet or more
-1.87
6:12 (27°) < Slope < 12:12 (45°) Figure 6-1 ID
Enclosed
Partially enclosed
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
L15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 6-1 ID Zone 2
Negative
10 square feet or less
-1.70
500 square feet or more
-1.53
Monosloped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 6-14B Zone 2
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.51
-1.83
100 square feet or more
-1.43
-L74
Tall flat topped roofs h > 60'
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 2) See ASCE 7 Figure 6-17 Zone 2
Negative
10 square feet or less
-2.11
-2.42
500 square feet or more
-1.51
-1.83
Gable or hipped configurations at comers (Zone 3) See ASCE 7 Figure 6-1 IC Zone 3
Flat < Slope < 6:12 (27°)
Enclosed
Partially enclosed
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.53
-2.85
100 square feet or more
-1.85
-2.17
(continued)
2010 CALIFORNIA BUILDING CODE
101
STRUCTURAL DESIGN
TABLE 16094.6.2(2)— continued
NET PRESSURE COEFFICIENTS, C„^t^'^
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„ef FACTOR
3. Components and cladding in
areas of discontinuity — roofs
and overhangs
(continued)
Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-1 IC Zone 3
Negative
10 square feet or less
-3.15
100 square feet or more
-2.13
6:12 (27°) < 12:12 (45°) See ASCE 7 Figure 6-1 ID Zone 3
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12:12 (45°)
Enclosed
Partially enclosed
Negative
10 square feet or less
-1.70
100 square feet or more
-1.53
Monosloped Configurations at comers (Zone 3) See ASCE 7 Figure 6-14B Zone 3
Flat < Slope < 7:12 (30°)
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.62
-2.93
100 square feet or more
-1.85
-2.17
Tall flat topped roofs h > 60'
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 3) See ASCE 7 Figure 6-17 Zone 3
Negative
10 square feet or less
-2.87
-3.19
500 square feet or more
-2.11
-2.42
4, Components and cladding not
in areas of discontinuity — walls
and parapets
Wall Elements: h = 60' (Zone 4) Figure 6-11 A
Enclosed
Partially enclosed
Positive
10 square feetor less
LOO
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.09
-1.40
500 square feet or more
-0.83
-1.15
Wall Elements: h > 60' (Zone 4) See ASCE 7 Figure 6-17 Zone 4
Positive
20 square feet or less
0.92
1.23
500 square feet or more
0.66
0.98
Negative
20 square feet or less
-0.92
-1.23
500 square feet or more
-0.75
-1.06
Parapet Walls
Positive
2.87
3.19
Negative
-1.68
-2.00
(continued)
102
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
TABLE 16094.6.2(2)--continued
NET PRESSURE COEFFICIENTS, C^^^^^^
STRUCTURE OR
PART THEREOF
DESCRIPTION
C„e, FACTOR
5. Components and cladding
in areas of discontinuity —
walls and parapets
Wall elements:
h < 60' (Zone 5) Figure 6-1 1 A
Enclosed
Partially enclosed
Positive
10 square feet or less
1.00
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.83
-1.15
Wall elements:
h > 60' (Zone 5) See ASCE 7 Figure 6-17 Zone 4
Positive
20 square feet or less
0.92
1.23
500 square feet or more
0.66
0.98
Negative
20 square feet or less
-1.68
-2.00
500 square feet or more
-1.00
-1.32
Parapet walls
Positive
3.64
3.95
Negative
-2.45
-2.76
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m^ 1 degree = 0.0175 rad.
a. Linear interpolation between values in the table is permitted.
b. Some C„^^ values have been grouped together. Less conservative results may be obtained by applying ASCE 7 provisions.
1609A.6.3 Design equations. When using the alternative
all-heights method, the MWFRS, and components and clad-
ding of every structure shall be designed to resist the effects
of wind pressures on the building envelope in accordance
with Equation 16A-34.
Pnet-^sKzC„^tUKzt\
(Equation 16A-34)
ponents and cladding, the sum of the internal and exter-
nal net pressure shall be based on the net pressure coeffi-
cient, C„,,.
1 . The pressure coefficient, C„^^, for walls and roofs
shall be determined from Table 1609A.6.2(2).
2. Where Q^^ has more than one value, the more
Design wind forces for the MWFRS shall not be less than
10 psf (0.48 kN/m^) multiplied by the area of the structure
projected on a plane normal to the assumed wind direction
(see ASCE 7 Section 6.1.4 for criteria). Design net wind
pressure for components and cladding shall not be less than
10 psf (0.48 kN/m^) acting in either direction normal to the
surface.
1609A.6.4 Design procedure. The MWFRS and the com-
ponents and cladding of every building or other structure
shall be designed for the pressures calculated using Equa-
tion 16A-34.
1609A. 6.4.1 Main wind-force-resisting systems. The
MWFRS shall be investigated for the torsional effects
identified in ASCE 7 Figure 6-9.
1609A.6.4.2 Determination of K^ and K^^ Velocity
pressure exposure coefficient, K^, shall be determined in
accordance with ASCE 7 Section 6.5.6.6 and the topo-
graphic factor, K^f, shall be determined in accordance
with ASCE 7 Section 6.5.7.
1. For the windward side of a structure, K^^ and K^
shall be based on height z.
2. For leeward and side walls, and for windward and
leeward roofs, K^^ and K^ shall be based on mean
roof height h.
1609A. 6.4.3 Determination of net pressure coeffi-
cients, C„^f. For the design of the MWFRS and for corn-
severe wind load condition
design.
shall be used for
1609A. 6.4.4 Application of vt^ind pressures. When
using the alternative all-heights method, wind pressures
shall be applied simultaneously on, and in a direction
normal to, all building envelope wall and roof surfaces.
1609A. 6.4.4.1 Components and cladding. Wind
pressure for each component or cladding element is
applied as follows using C^^^ values based on the
effective wind area. A, contained within the zones in
areas of discontinuity of width and/or length "a," "2a"
or *'4a" at: corners of roofs and walls; edge strips for
ridges, rakes and eaves; or field areas on walls or roofs
as indicated in figures in tables in ASCE 7 as refer-
enced in Table 1609A. 6.2(2) in accordance with the
following:
1. Calculated pressures at local discontinuities
acting over specific edge strips or corner
boundary areas.
2. Include "field" (Zone 1, 2 or 4, as applicable)
pressures applied to areas beyond the bound-
aries of the areas of discontinuity.
3. Where applicable, the calculated pressures at
discontinuities (Zones 2 or 3) shall be com-
bined with design pressures that apply specifi-
cally on rakes or eave overhangs.
2010 CALIFORNIA BUILDING CODE
103
STRUCTURAL DESIGN
TABLE 1 61 0A1
LATERAL SOIL LOAD
DESCRIPTION OF BACKFILL MATERIAL"^
UNIFIED SOIL
CLASSIFICATION
DESIGN LATERAL SOIL LOAD^
(pound per square foot per foot of depth)
Active pressure
At-rest pressure
Well-graded, clean gravels; gravel-sand mixes
GW
30
60
Poorly graded clean gravels; gravel-sand mixes
GP
30
60
Silty gravels, poorly graded gravel-sand mixes
GM
40
60
Clayey gravels, poorly graded gravel-and-clay mixes
GC
45
60
Well-graded, clean sands; gravelly sand mixes
SW
30
60
Poorly graded clean sands; sand-gravel mixes
SP
30
60
Silty sands, poorly graded sand- silt mixes
SM
45
60
Sand-silt clay mix with plastic fines
SM-SC
45
100
Clayey sands, poorly graded sand-clay mixes
SC
60
100
Inorganic silts and clayey silts
ML
45
100
Mixture of inorganic silt and clay
ML-CL
60
100
Inorganic clays of low to medium plasticity
CL
60
100
Organic silts and silt clays, low plasticity
OL
Noteb
Noteb
Inorganic clayey silts, elastic silts
MH
Noteb
Noteb
Inorganic clays of high plasticity
CH
Noteb
Noteb
Organic clays and silty clays
OH
Noteb
Noteb
For SI: 1 pound per square foot per foot of depth = 0. 157 kPa/m, 1 foot = 304.8 mm.
a. Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or satu-
rated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads.
b. Unsuitable as backfill material.
c. The definition and classification of soil materials shall be in accordance with ASTM D 2487.
SECTION 16104
SOIL LATERAL LOADS
161QA. 1 GeneraL Foundation walls and retaining walls shall
be designed to resist lateral soil loads. Soil loads specified in
Table 1610A. 1 shall be used as the minimum design lateral soil
loads unless determined otherwise by a geotechnical investiga-
tion in accordance with Section 1803A. Foundation walls and
other walls in which horizontal movement is restricted at the
top shall be designed for at-rest pressure. Retaining walls free
to move and rotate at the top shall be permitted to be designed
for active pressure. Design lateral pressure from surcharge
loads shall be added to the lateral earth pressure load. Design
lateral pressure shall be increased if soils at the site are expan-
sive. Foundation walls shall be designed to support the weight
of the full hydrostatic pressure of undrained backfdl unless a
drainage system is installed in accordance with Sections
1805A.4.2andl805A.4.3.
Exception: Foundation walls extending not more than 8
feet (2438 mm) below grade and laterally supported at the
top by flexible diaphragms shall be permitted to be designed
for active pressure.
SECTION 16114
RAIN LOADS
161L4.1 Design rain loads. Each portion of a roof shall be
designed to sustain the load of rainwater that will accumulate
on it if the primary drainage system for that portion is blocked
plus the uniform load caused by water that rises above the inlet
of the secondary drainage system at its design flow. The design
rainfall shall be based on the 100-year hourly rainfall rate indi-
cated in Figure 161 1 A. 1 or on other rainfall rates determined
from approved local weather data.
For SI: R = 0.0098( J, + d^,)
where:
(Equation 16A-35)
df^ = Additional depth of water on the undeflected roof
above the inlet of secondary drainage system at its
design flow (i.e., the hydraulic head), in inches (mm).
d^ = Depth of water on the undeflected roof up to the inlet of
secondary drainage system when the primary drainage
system is blocked (i.e., the static head), in inches (mm).
R = Rain load on the undeflected roof, in psf (kN/m2).
When the phrase "undeflected roof is used, deflec-
tions from loads (including dead loads) shall not be
considered when determining the amount of rain on the
roof.
104
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
4.28-^'
[P] FIGURE 161 1A1
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
105
STRUCTURAL DESIGN
[P] FIGURE 1611A1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
106
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
*— ". ?
[P] FIGURE 1611 A1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
107
STRUCTURAL DESIGN
[P] FIGURE 1 61 1A1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
108
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
Ijx^
o;
•^^
- i'
xs
3
<
X
M/^^j^^^ I\
^;?^^
"-^Os
/
[P] FIGURE 1611 A1— continued
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
2010 CALIFORNIA BUILDING CODE
109
STRUCTURAL DESIGN
161 L4. 2 Ponding instability. For roofs with a slope less than
V4 inch per foot [1.19 degrees (0.0208 rad)] , the design calcula-
tions shall include verification of adequate stiffness to preclude
progressive deflection in accordance with Section 8.4 of ASCE
7.
161 L4. 3 Controlled drainage. Roofs equipped with hardware
to control the rate of drainage shall be equipped with a second-
ary drainage system at a higher elevation that limits accumula-
tion of water on the roof above that elevation. Such roofs shall
be designed to sustain the load of rainwater that will accumu-
late on them to the elevation of the secondary drainage system
plus the uniform load caused by water that rises above the inlet
of the secondary drainage system at its design flow determined
from Section 1611A.L Such roofs shall also be checked for
ponding instability in accordance with Section 1611A,2.
SECTION 16124
FLOOD LOADS
1612A.1 GeneraL Within flood hazard areas as established in
Section 1612A.3, all new construction of buildings, structures
and portions of buildings and structures, including substantial
improvement and restoration of substantial damage to build-
ings and structures, shall be designed and constructed to resist
the effects of flood hazards and flood loads. For buildings that
are located in more than one flood hazard area, the provisions
associated with the most restrictive flood hazard area shall
apply.
1612A. 2 Definitions. The following words and terms shall, for
the purposes of this section, have the meanings shown herein.
BASE FLOOD. The flood having a 1 -percent chance of being
equaled or exceeded in any given year.
BASE FLOOD ELEVATION. The elevation of the base
flood, including wave height, relative to the National Geodetic
Vertical Datum (NGVD), North American Vertical Datum
(NAVD) or other datum specified on the Flood Insurance Rate
Map (FIRM).
BASEMENT. The portion of a building having its floor
subgrade (below ground level) on all sides.
This definition of "Basement" is limited in appHcation to the
provisions of Section 1612A (see "Basement" in Section
502.1).
DESIGN FLOOD. The flood associated with the greater of
the following two areas:
1. Area with a flood plain subject to a 1 -percent or greater
chance of flooding in any year; or
2. Area designated as a flood hazard area on a commu-
nity' s flood hazard map, or otherwise legally designated.
DESIGN FLOOD ELEVATION. The elevation of the
'''design flood'' including wave height, relative to the datum
specified on the community's legally designated flood hazard
map. In areas designated as Zone AG, the design flood eleva-
tion shall be the elevation of the highest existing grade of the
building's perimeter plus the depth number (in feet) specified
on the flood hazard map. In areas designated as Zone AG where
a depth number is not specified on the map, the depth number
shall be taken as being equal to 2 feet (610 mm).
DRY FLOODPROOFING. A combination of design modifi-
cations that results in a building or structure, including the
attendant utility and sanitary facilities, being water tight with
walls substantially impermeable to the passage of water and
with structural components having the capacity to resist loads
as identified in ASCE 7.
EXISTING CONSTRUCTION. Any buildings and struc-
tures for which the "start of construction" commenced before
the effective date of the community's first flood plain manage-
ment code, ordinance or standard. "Existing construction" is
also referred to as "existing structures."
EXISTING STRUCTURE. See "Existing construction."
FLOOD or FLOODING. A general and temporary condition
of partial or complete inundation of normally dry land from:
1 . The overflow of inland or tidal waters.
2. The unusual and rapid accumulation or runoff of surface
waters from any source.
FLOOD DAMAGE-RESISTANT MATERIALS. Any con-
struction material capable of withstanding direct and pro-
longed contact with floodwaters without sustaining any
damage that requires more than cosmetic repair.
FLOOD HAZARD AREA. The greater of the following two
areas:
1. The area within a flood plain subject to a 1 -percent or
greater chance of flooding in any year.
2. The area designated as a flood hazard area on a commu-
nity's flood hazard map, or otherwise legally designated.
FLOOD HAZARD AREA SUBJECT TO HIGH- VELOC-
ITY WAVE ACTION. Area within the flood hazard area that
is subject to high-velocity wave action, and shown on a Flood
Insurance Rate Map (FIRM) or other flood hazard map as Zone
V,VG,VEorVl-30.
FLOOD INSURANCE RATE MAP (FIRM). An official
map of a community on which the Federal Emergency Man-
agement Agency (FEMA) has delineated both the special flood
hazard areas and the risk premium zones applicable to the com-
munity.
FLOOD INSURANCE STUDY. The official report provided
by the Federal Emergency Management Agency containing the
Flood Insurance Rate Map (FIRM), the Flood Boundary and
Floodway Map (FBFM), the water surface elevation of the
base flood and supporting technical data.
FLOODWAY. The channel of the river, creek or other water-
course and the adjacent land areas that must be reserved in
order to discharge the base flood without cumulatively increas-
ing the water surface elevation more than a designated height.
LOWEST FLOOR. The floor of the lowest enclosed area,
including basement, but excluding any unfinished or
flood-resistant enclosure, usable solely for vehicle parking,
building access or limited storage provided that such enclosure
is not built so as to render the structure in violation of this sec-
tion.
110
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
SPECIAL FLOOD HAZARD AREA. The land area subject
to flood hazards and shown on a Flood Insurance Rate Map or
other flood hazard map as Zone A, AE, Al-30, A99, AR, AG,
AH, V, VO, VE or Vl-30.
START OF CONSTRUCTION. The date of issuance for new
construction and substantial improvements to existing struc-
tures, provided the actual start of construction, repair, recon-
struction, rehabilitation, addition, placement or other
improvement is within 180 days after the date of issuance. The
actual start of construction means the first placement of perma-
nent construction of a building (including a manufactured
home) on a site, such as the pouring of a slab or footings, instal-
lation of piUngs or construction of columns.
Permanent construction does not include land preparation
(such as clearing, excavation, grading or filling), the installa-
tion of streets or walkways, excavation for a basement, foot-
ings, piers or foundations, the erection of temporary forms or
the installation of accessory buildings such as garages or sheds
not occupied as dwelling units or not part of the main building.
For a substantial improvement, the actual "start of construc-
tion" means the first alteration of any wall, ceiling, floor or
other structural part of a building, whether or not that alteration
affects the external dimensions of the building.
SUBSTANTIAL DAMAGE. Damage of any origin sus-
tained by a structure whereby the cost of restoring the struc-
ture to its before-damaged condition would equal or exceed
50 percent of the market value of the structure before the dam-
age occurred.
SUBSTANTIAL IMPROVEMENT. Any repair, reconstruc-
tion, rehabilitation, addition or improvement of a building or
structure, the cost of which equals or exceeds 50 percent of the
market value of the structure before the improvement or repair
is started. If the structure has sustained substantial damage, any
repairs are considered substantial improvement regardless of
the actual repair work performed. The term does not, however,
include either:
1. Any project for improvement of a building required to
correct existing health, sanitary or safety code violations
identified by the building official and that are the mini-
mum necessary to assure safe living conditions.
2. Any alteration of a historic structure provided that the
alteration will not preclude the structure's continued
designation as a historic structure.
1612A.3 Establishment of flood hazard areas. To establish
flood hazard areas, the applicable governing authority shall
adopt a flood hazard map and supporting data. The flood haz-
ard map shall include, at a minimum, areas of special flood haz-
ard as identified by the Federal Emergency Management
Agency 's Flood Insurance Study (FIS) adopted by the local
authority having jurisdiction where the project is located, as
amended or revised with the accompanying Flood Insurance
Rate Map (FIRM) and Flood Boundary and Floodway Map
(FBFM) and related supporting data along with any revisions
thereto. The adopted flood hazard map and supporting data are
hereby adopted by reference and declared to be part of this sec-
tion.
1612A.3.1 Design flood elevations. Where design flood
elevations are not included in the flood hazard areas estab-
lished in Section 1612A.3, or where floodway s are not des-
ignated, the building official is authorized to require the
applicant to:
1 . Obtain and reasonably utilize any design flood eleva-
tion and floodway data available from a federal, state
or other source; or
2. Determine the design flood elevation and/or
floodway in accordance with accepted hydrologic
and hydrauUc engineering practices used to define
special flood hazard areas. Determinations shall be
undertaken by a registered design professional who
shall document that the technical methods used
reflect currently accepted engineering practice.
1612A.3.2 Determination of impacts. In riverine flood
hazard areas where design flood elevations are specified
but floodways have not been designated, the applicant shall
provide a floodway analysis that demonstrates that the pro-
posed work will not increase the design flood elevation
more than 1 foot (305 mm) at any point within the jurisdic-
tion of the applicable governing authority.
1612A.4 Design and construction. The design and construc-
tion of buildings and structures located in flood hazard areas,
including flood hazard areas subject to high- velocity wave
action, shall be in accordance with Chapter 5 of ASCE 7 and
with ASCE 24.
1612A.5 Flood hazard documentation. The following docu-
mentation shall be prepared and sealed by a registered design
professional and submitted to the building official:
1. For construction in flood hazard areas not subject to
high-velocity wave action:
1.1. The elevation of the lowest floor, including the
basement, as required by the lowest floor eleva-
tion inspection in Section 110.3.3.
1.2. For fully enclosed areas below the design flood
elevation where provisions to allow for the auto-
matic entry and exit of floodwaters do not meet
the minimum requirements in Section 2.6.2.1 of
ASCE 24, construction documents shall include
a statement that the design will provide for equal-
ization of hydrostatic flood forces in accordance
with Section 2.6,2.2 of ASCE 24.
1.3. For dry floodproofed nonresidential buildings,
construction documents shall include a statement
that the dry floodproofing is designed in accor-
dance with ASCE 24.
2. For construction in flood hazard areas subject to
high- velocity wave action:
2.1. The elevation of the bottom of the lowest hori-
zontal structural member as required by the low-
est floor elevation inspection in Section 1 10.3.3.
2.2. Construction documents shall include a state-
ment that the building is designed in accordance
with ASCE 24, including that the pile or column
foundation and building or structure to be
2010 CALIFORNIA BUILDING CODE
111
STRUCTURAL DESIGN
>
>|
attached thereto is designed to be anchored to
resist flotation, collapse and lateral movement
due to the effects of wind and flood loads acting
simultaneously on all building components, and
other load requirements of Chapter 16A,
2.3. For breakaway walls designed to resist a nominal
load of less than 1 psf (0.48 kN/m^) or more than
20 psf (0.96 kN/m^), construction documents
shall include a statement that the breakaway wall
is designed in accordance with ASCE 24.
SECTION 1613/1
EARTHQUAKE LOADS
1613A.1 Scope. Every structure, and portion thereof, including
nonstructural components that are permanently attached to
structures and their supports and attachments, shall be
designed and constructed to resist the effects of earthquake
motions in accordance with ASCE 7 with all the modifications
incorporated herein, excluding Chapter 14 and Appendix 1 lA.
The seismic design category for a structure shall be determined
in accordance with Section 161 3 A.
Exception: Structures that require special consideration of
their response characteristics and environment that are not
addressed by this code or ASCE 7 and for which other regu-
lations provide seismic criteria, such as vehicular bridges,
electrical transmission towers, hydraulic structures, buried
utility lines and their appurtenances and nuclear reactors.
1613A.2 Definitions. The following words and terms shall, for
the purposes of this section, have the meanings shown herein.
Definition provided in Section 3402 A. 1 and ASCE 7 Section
11.2 shall apply when appropriate in addition to terms defined
in this section.
ACTIVE EARTHQUAKE FAULT A fault that has been the
source of earthquakes or is recognized as a potential source of
earthquakes, including those that have exhibited surface dis-
placement within Holocene time (about 11 ,000 years) as deter-
mined by California Geological Survey (CGS) under the
Alquist-Priolo Earthquake Fault Zoning Act, those included as
type A or type B faults for the U.S. Geological Survey (USGS)
National Seismic Hazard Maps, and faults considered to have
been active in Holocene time by an authoritative source, fed-
eral, state or local governmental agency.
BASE, The level at which the horizontal seismic ground
motions are considered to be imparted to the structure or the
level at which the structure as a dynamic vibrator is supported.
This level does not necessarily coincide with the ground level
DESIGN EARTHQUAKE GROUND MOTION. The earth-
quake ground motion that buildings and structures are specifi-
cally proportioned to resist in Section 1613A.
DISTANCE FROM AN ACTIVE EARTHQUAKE FAULT
Distance measured from the nearest point of the building to the
closest edge of an Alquist-Priolo Earthquake Fault Zone for an
active fault, if such a map exists, or to the closest mapped splay
of the fault.
HOSPITAL BUILDINGS. Hospital buildings and all other
medical facilities as defined in Section 1250, Health and Safety
Code.
IRREGULAR STRUCTURE. A structure designed as having
one or more plan or vertical irregularities per ASCE 7 Section
12.3.
MAXIMUM CONSIDERED EARTHQUAKE GROUND
MOTION. The most severe earthquake effects considered by
this code.
MECHANICAL SYSTEMS. For the purposes of determin-
ing seismic loads in ASCE 7, mechanical systems shall include
plumbing systems as specified therein.
NEXT GENERATION ATTENUATION (NGA). Attenuation
relations used for the 2008 United States Geological Survey
(USGS) seismic hazards maps (for the Western United States)
or their equivalent as determined by the enforcement agency.
ORTHOGONAL. To be in two horizontal directions, at 90
degrees (1.57 rad) to each other.
SEISMIC DESIGN CATEGORY. A classification assigned
to a structure based on its occupancy category and the severity
of the design earthquake ground motion at the site.
SEISMIC-FORCE-RESISTING SYSTEM. That part of the
structural system that has been considered in the design to pro-
vide the required resistance to the prescribed seismic forces.
SITE CLASS. A classification assigned to a site based on the
types of soils present and their engineering properties as
defined in Section 1613A.5.2.
SITE COEFFICIENTS. The values of F^ and F, indicated in
Tables 1613A.5.3(1) and 1613A.5.3(2), respectively.
STRUCTURAL ELEMENTS, Floor or roof diaphragms,
decking, joists, slabs, beams or girders, columns, bearing
walls, retaining walls, masonry or concrete nonbearing walls
exceeding one story in height, foundations, shear walls or
other lateral-force-resisting members and any other elements
necessary to the vertical and lateral strength or stability of
either the building as a whole or any of its parts, including con-
nection between such elements.
1613A.3 Existing buildings. [OSHPD 1 & 4] Additions, alter-
ations, repairs or change of occupancy of existing buildings
shall be in accordance with Chapter 34A,
1613A.4 Special inspections. Where required by Sections
1705A.3 through 1705A.3.5, the statement of special inspec-
tions shall include the special inspections required by Section
1705A.3.6.
112
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
#
1613A.5 Seismic ground motion values. Seismic ground
motion values shall be determined in accordance with this sec-
tion.
1613A.5.1 Mapped acceleration parameters. The param-
eters S^ and S^ shall be determined from the 0.2 and 1 -second
spectral response accelerations shovi^n on Figures 1613.5(1)
through 1613.5(14).
1613A.5.2 Site class definitions. Based on the site soil
properties, the site shall be classified as either Site Class A,
B, C, D, E or F in accordance with Table 1613A.5.2. When
the soil properties are not known in sufficient detail to deter-
mine the site class, Site Class D shall be used unless the
building official or geotechnical data determines that Site
Class E or F soil is likely to be present at the site.
1613A.5.3 Site coefficients and adjusted maximum con-
sidered earthquake spectral response acceleration
parameters. The maximum considered earthquake spectral
response acceleration for short periods, 5^^, and at 1 -second
period, Si^i, adjusted for site class effects shall be deter-
mined by Equations 16A-36 and 16A-37, respectively:
(Equation 16A-36)
(Equation 16A -37)
Sm\ — ^vS\
where:
F, = Site coefficient defined in Table 1613A.5.3(1).
Fy = Site coefficient defined in Table 161 3A. 5. 3(2).
Ss = The mapped spectral accelerations for short periods
as determined in Section 1613A.5.L
5i = The mapped spectral accelerations for a 1 -second
period as determined in Section 1613A.5.1.
1613A.5.4 Design spectral response acceleration param-
eters. Five-percent damped design spectral response accel-
eration at short periods, 5^,5, and at 1 -second period, Sj^ji,
shall be determined from Equations 16A-38 and 16A-39,
respectively:
^DS-^ r.^MS
^D\ — ry^Ml
(Equation 16A -38)
(Equation 16A-39)
where:
Sj^s = The maximum considered earthquake spectral
response accelerations for short period as deter-
mined in Section 1613A.53.
5^1 = The maximum considered earthquake spectral
response accelerations for 1 -second period as
determined in Section 1613A.5.3.
TABLE1613A5.2
SITE CLASS DEFINITIONS
SITE
CLASS
SOIL PROFILE
NAME
AVERAGE PROPERTIES IN TOP 100 feet, SEE SECTION 1613A.5.5
Soil shear wave velocity, v^, (ft/s)
Standard penetration resistance,
N
Soil undrained shear strength, s„ , (psf)
A
Hard rock
V, > 5,000
N/A
N/A
B
Rock
2,500 < v^ < 5,000
N/A
N/A
C
Very dense soil and soft rock
1,200 <v, < 2,500
N>50
5„ > 2,000
D
Stiff soil profile
600 <v, < 1,200
15<iV<50
1,000 <^„< 2,000
E
Soft soil profile
v^ < 600
N<15
s^ < 1,000
E
—
Any profile with more than 10 feet of soil having the following characteristics:
1 . Plasticity index PI > 20,
2. Moisture content w > 40%, and
3. Undrained shear strength 5„< 500 psf
F
—
Any profile containing soils having one or more of the following characteristics:
1. Soils vulnerable to potential failure or collapse under seismic loading such as hquefiable
soils, quick and highly sensitive clays, collapsible weakly cemented soils.
2. Peats and/or highly organic clays {/f > 10 feet of peat and/or highly organic clay where
H = thickness of soil)
3. Very high plasticity clays {H > 25 feet with plasticity index PI > 75)
4. Very thick soft/medium stiff clays {H > 120 feet)
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m^, 1 pound per square foot = 0.0479 kPa. N/A = Not applicable
2010 CALIFORNIA BUILDING CODE
113
STRUCTURAL DESIGN
TABLE 16134.5.3(1)
VALUES OF SITE COEFFICIENT F^ ^
SITE
CLASS
MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD
Ss < 0.25
S^ = 0.50
Sg = 0.75
Ss = 1.00
S^> 1.25
A
0.8
0.8
0.8
0.8
0.8
B
1.0
1.0
1.0
1.0
1.0
C
1.2
1.2
1.1
1.0
1.0
D
1.6
1.4
1.2
1.1
1.0
E
2.5
1.7
1.2
0.9
0.9
F
Noteb
Noteb
Noteb
Noteb
Noteb
a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at short period, S^.
b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
TABLE 16134.5.3(2)
VALUES OF SITE COEFFICIENT Fy^
SITE
CLASS
MAPPED SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD
Si < 0.1
S, = 0.2
S, = 0.3
Si = 0.4
Si > 0.5
A
0.8
0.8
0.8
0.8
0.8
B
1.0
1.0
1.0
1.0
1.0
C
1.7
1.6
1.5
1.4
1.3
D
2.4
2.0
1.8
1.6
1.5
E
3.5
3.2
2.8
2.4
2.4
F
Noteb
Noteb
Noteb
Noteb
Noteb
a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at 1 -second period, 5,.
b. Values shall be determined in accordance with Section 11. 4.7 of ASCE 7.
1613A.5.5 Site classification for seismic design. Site clas-
sification for Site Class C, D or E shall be determined from
Table 1613A.5.5.
The notations presented below apply to the upper 100 feet
(30 480 mm) of the site profile. Profiles containing dis-
tinctly different soil and/or rock layers shall be subdivided
into those layers designated by a number that ranges from 1
to n at the bottom where there is a total of n distinct layers in
the upper 100 feet (30 480 mm). The symbol / then refers to
any one of the layers between 1 and n.
where:
v,^ = The shear wave velocity in feet per second (m/s).
di = The thickness of any layer between and 100 feet
(30 480 mm).
where:
Xdi
^ J/ = 100 feet (30 480 mm)
(Equation 16A-40)
A^, is the Standard Penetration Resistance (ASTM D 1586)
not to exceed 100 blows/foot (328 blows/m) as directly
measured in the field without corrections. When refusal is
met for a rock layer, A^, shall be taken as 1 00 blows/foot (328
blows/m).
(Equation 16A-41)
where A^^ and di in Equation 16A-41 are for cohesionless
soil, cohesive soil and rock layers.
Nc
"" d
(Equation 16A-42)
A^;
where:
m
Use di and A^, for cohesionless soil layers only in Equation
16A-42.
d^ = The total thickness of cohesionless soil layers in the
top 100 feet (30 480 mm).
114
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
m = The number of cohesionless soil layers in the top 100
feet (30 480 mm).
s^,i = The undrained shear strength in psf (kPa), not to
exceed 5,000 psf (240 kPa), ASTM D 2166 or D
2850.
(Equation 16A-43)
Su =—
where:
dc = The total thickness of cohesive soil layers in the top
100 feet (30 480 mm).
k - The number of cohesive soil layers in the top 100 feet
(30 480 mm).
PI = The plasticity index, ASTM D 4318.
w = The moisture content in percent, ASTM D 2216.
Where a site does not qualify under the criteria for Site
Class F and there is a total thickness of soft clay greater than
10 feet (3048 mm) where a soft clay layer is defined by: s^ <
500 psf (24 kPa), w > 40 percent, and PI > 20, it shall be clas-
sified as Site Class E.
The shear wave velocity for rock, Site Class B, shall be
either measured on site or estimated by a geotechnical engi-
neer or engineering geologist/seismologist for competent
rock with moderate fracturing and weathering. Softer and
more highly fractured and weathered rock shall either be
measured on site for shear wave velocity or classified dis Site
Class C.
The hard rock category. Site Class A, shall be supported
by shear wave velocity measurements either on site or on
profiles of the same rock type in the same formation with an
equal or greater degree of weathering and fracturing. Where
hard rock conditions are known to be continuous to a depth
of 100 feet (30 480 mm), surficial shear wave velocity mea-
surements are permitted to be extrapolated to assess v^ .
The rock categories, Site Classes A and B, shall not be
used if there is more than 10 feet (3048 mm) of soil between
the rock surface and the bottom of the spread footing or mat
foundation.
1613A.5.5.1 Steps for classifying a site.
1. Check for the four categories of Site Class F
requiring site-specific evaluation. If the site corre-
sponds to any of these categories, classify the site
as Site Class F and conduct a site-specific evalua-
tion.
2. Check for the existence of a total thickness of soft
clay > 10 feet (3048 mm) where a soft clay layer is
defined by: s^< 500 psf (24 kPa), w > 40 percent
and PI > 20. If these criteria are satisfied, classify
the site as Site Class E,
3 . Categorize the site using one of the following three
methods with v^ , N, and s^ and computed in all
cases as specified.
3.1. V, for the top 100 feet (30 480 mm)
(v^ method).
3.2. TV^for the top 100 feet (30 480 mm)
(A^method).
3.3. N^f, for cohesionless soil layers (PI < 20)
in the top 100 feet (30 480 mm) and aver-
age, 5„ for cohesive soil layers (PI > 20) in
the top 100 feet (30 480 mm) ( s^ method).
1613A.5.6 Determination of seismic design category.
Structures classified as Occupancy Category I, n or III that
are located where the mapped spectral response accelera-
tion parameter at 1-second period, Sj, is greater than or
equal to 0.75 shall be assigned to Seismic Design Category
E. Structures classified as Occupancy Category IV that are
located where the mapped spectral response acceleration
parameter at 1-second period, 5y, is greater than or equal to
0.75 shall be assigned to Seismic Design Category F. All
other structures shall be assigned to a seismic design Cate-
gory D.
1613A. 5.6.1 Alternative seismic design category
determination. Not permitted by DSA-SS & OSHPD.
1613A. 5.6.2 Simplified design procedure. Not permitted
by DSA-SS & OSHPD.
1613A.6 Alternatives to ASCE 7. The provisions of Section
1 6 1 3A. 6 shall be permitted as alternatives to the relevant pro vi-
sions of ASCE 7.
<
TABLE 1613A5.5
SITE CLASSIFICATION^
SITE CLASS
Vb
NotN^
s„
E
< 600 ft/s
<15
< 1,000 psf
D
600 to 1,200 ft/s
15 to 50
1,000 to 2,000 psf
C
1,200 to 2,500 ft/s
>50
> 2,000
For SI: 1 foot per second = 304.8 mm per second, 1 pound per square foot = 0.0479 kN/m^.
a. If the 5„method is used and the N^^and 5„ criteria differ, select the category with the softer soils (for example, use Site Class E instead of D).
2010 CALIFORNIA BUILDING CODE
115
STRUCTURAL DESIGN
>l
1613A.6.1 Assumption of flexible diaphragm. Add the
following text at the end of Section 12.3.1.1 of ASCE 7.
Diaphragms constructed of wood structural panels or
untopped steel decking shall also be permitted to be idealized
as flexible, provided all of the following conditions are met:
1. Toppings of concrete or similar materials are not
placed over wood structural panel diaphragms except
for nonstructural toppings no greater than 1 Vj inches
(38 mm) thick.
2. Each line of vertical elements of the seismic-
force-resisting system complies with the allowable
story drift of Table 12.12-1.
3. Vertical elements of the seismic-force-resisting sys-
tem are light-frame walls sheathed with wood struc-
tural panels rated for shear resistance or steel sheets.
4. Portions of wood structural panel diaphragms that
cantilever beyond the vertical elements of the lat-
eral-force-resisting system are designed in accor-
dance with Section 4.2.5.2 of AF&PA SDPWS.
1613A.6.2 Additional seismic-force-resisting systems for
seismically isolated structures. Add the following excep-
tion to the end of Section 17.5.4.2 of ASCE 7:
Exception: For isolated structures designed in accor-
dance with this standard, the Structural System Limita-
tions and the Building Height Limitations in Table
12.2-1 for ordinary steel concentrically braced frames
(OCBFs) as defined in Chapter 11 and intermediate
moment frames (IMFs) as defined in Chapter 1 1 are per-
mitted to be taken as 160 feet (48 768 mm) for structures
assigned to Seismic Design Category D, E or F, provided
that the following conditions are satisfied:
1 . The value oiR^ as defined in Chapter 17 is taken as
1.
2. For OCBFs, design is in accordance with AISC
341.
3. For IMFs, design is in accordance with AISC 34 L
In addition, requirements of Section 9.3 of AISC
341 shall be satisfied,
1613A.6.3 Automatic sprinkler sysitvas. Automatic sprin-
kler systems designed and installed in accordance with
NFPA 13 shall be deemed to meet the requirements of Sec-
tion 13.6.8 of ASCE 7.
Exception: The allowable values for design ofanchorSy
hangers and bracings shall be determined in accordance
with material chapters of this code in lieu of those in
NFPA 13.
1613A.6.4 Autoclaved aerated concrete (A AC) masonry.
Not permitted by DSA-SS & OSHPD.
1613A.6.5 Seismic controls for elevators. Seismic switches
in accordance with Section 8.4.10 of ASME A17.1 shall be
deemed to comply with Section 13.6.10.3 of ASCE 7.
1613A.6.6 Steel plate shear wall height limits. Modify
Section 12.2.5.4 of ASCE 7 to read as follows:
12.2.5.4 Increased building height limit for steel-
braced frames, special steel plate shear walls and spe-
cial reinforced concrete shear walls. The height limits
in Table 12.2-1 are permitted to be increased from 160
feet (48 768 mm) to 240 feet (75 152 mm) for structures
assigned to Seismic Design Category D or E and from
100 feet (30 480 mm) to 160 feet (48 768 mm) for struc-
tures assigned to Seismic Design Category F that have
steel-braced frames, special steel plate shear walls or
special reinforced concrete cast-in-place shear walls and
that meet both of the following requirements:
1 . The structure shall not have an extreme torsional
irregularity as defined in Table 12.2-1 (horizontal
structural irregularity Type lb).
2. The braced frames or shear walls in any one plane
shall resist no more than 60 percent of the total
seismic forces in each direction, neglecting acci-
dental torsional effects.
1613A.6.7 Minimum distance for building separation.
All buildings and structures shall be separated from adjoin-
ing structures. Separations shall allow for the maximum
inelastic response displacement (8^^). h^ shall be determined
at critical locations with consideration for both translational
and torsional displacements of the structure using Equation
16A-44 for DSA-SS and 16A-44B for OSHPD.
Ofuf —
-c,d„
(Equation 16A-44A)
(Equation 16A-44B)
where:
Q - Deflection ampHfication factor in Table 12.2-1 of
ASCE 7.
5^^ = Maximum displacement defined in Section 12.8.4.3
of ASCE 7.
/ = Importance factor in accordance with Section 11.5.1
of ASCE 7.
Adjacent buildings on the same property shall be sepa-
rated by a distance not less than ?>mt^ determined by Equa-
tion 16A-45.
^MT^^i^Mx)" ^{^Mlf
(Equation 16A-45)
where:
^Mh ^M2 - The maximum inelastic response displace-
ments of the adjacent buildings in accordance
with Equations 16A-44A or 16A-44B for
OSHPD.
Where a structure adjoins a property line not common to a
public way, the structure shall also be set back from the
property line by not less than the maximum inelastic
response displacement, d^^, of that structure.
Exception: Smaller separations or property hne set-
backs shall be permitted when justified by rational analy-
ses.
116
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
SECTION 16144
STRUCTURAL INTEGRITY
1614A.1 General. Buildings classified as high-rise buildings
in accordance with Section 403 and assigned to Occupancy
Category III or IV shall comply with the requirements of this
section. Frame structures shall comply with the requirements
of Section 1614A.3. Bearing wall structures shall comply with
the requirements of Section 1614A.4.
1614A.2 Definitions. The following words and terms shall, for
the purposes of Section 1614A, have the meanings shown
herein.
BEARING WALL STRUCTURE. A building or other struc-
ture in which vertical loads from floors and roofs are primarily
supported by walls.
FRAME STRUCTURE. A building or other structure in
which vertical loads from floors and roofs are primarily sup-
ported by columns.
1614A.3 Frame structures. Frame structures shall comply
with the requirements of this section.
1614A.3.1 Concrete frame structures. Frame structures
constructed primarily of reinforced or prestressed concrete,
either cast-in-place or precast, or a combination of these,
shall conform to the requirements of ACI 318 Sections 7.13,
13.3.8.5, 13.3,8.6, 16.5, 18.12.6, 18.12.7 and 18.12.8 as
applicable. Where ACI 318 requires that nonprestressed
reinforcing or prestressing steel pass through the region
bounded by the longitudinal column reinforcement, that
reinforcing or prestressing steel shall have a minimum nom-
inal tensile strength equal to two-thirds of the required
one-way vertical strength of the connection of the floor or
roof system to the column in each direction of beam or slab
reinforcement passing through the column.
Exception: Where concrete slabs with continuous rein-
forcing having an area not less than 0.0015 times the con-
crete area in each of two orthogonal directions are
present and are either monolithic with or equivalently
bonded to beams, girders or columns, the longitudinal
reinforcing or prestressing steel passing through the col-
umn reinforcement shall have a nominal tensile strength
of one-third of the required one-way vertical strength of
the connection of the floor or roof system to the column
in each direction of beam or slab reinforcement passing
through the column.
1614A.3.2 Structural steel, open web steel joist or joist
girder, or composite steel and concrete frame structures.
Frame structures constructed with a structural steel frame or
a frame composed of open web steel joists, joist girders with
or without other structural steel elements or a frame com-
posed of composite steel or composite steel joists and rein-
forced concrete elements shall conform to the requirements
of this section.
1614A. 3.2.1 Columns. Each column splice shall have
the minimum design strength in tension to transfer the
design dead and live load tributary to the column
between the spHce and the splice or base immediately
below.
1614A.3.2.2 Beams. End connections of all beams and
girders shall have a minimum nominal axial tensile
strength equal to the required vertical shear strength for
allowable stress design (ASD) or two-thirds of the
required shear strength for load and resistance factor
design (LRFD) but not less than 10 kips (45 kN). For the
purpose of this section, the shear force and the axial ten-
sile force need not be considered to act simultaneously.
Exception: Where beams, girders, open web joist and
joist girders support a concrete slab or concrete slab
on metal deck that is attached to the beam or girder
with not less than Vg-inch-diameter (9.5 nun) headed
shear studs, at a spacing of not more than 12 inches
(305 mm) on center, averaged over the length of the
member, or other attachment having equivalent shear
strength, and the slab contains continuous distributed
reinforcement in each of two orthogonal directions
with an area not less than 0.0015 times the concrete
area, the nominal axial tension strength of the end
connection shall be permitted to be taken as half the
required vertical shear strength for ASD or one-third
of the required shear strength for LRFD, but not less
than 10 kips (45 kN).
1614A.4 Bearing wall structures. Bearing wall structures
shall have vertical ties in all load-bearing walls and longitudi-
nal ties, transverse ties and perimeter ties at each floor level in
accordance with this section and as shown in Figure 1614A.4.
1614A.4.1 Concrete wall structures. Precast bearing wall
structures constructed solely of reinforced or prestressed
concrete, or combinations of these shall conform to the
requirements of Sections 7.13, 13.3.8.5 and 16.5 of ACI
318.
1614A.4.2 Other bearing wall structures. Ties in bearing
wall structures other than those covered in Section
1614A.4.1 shall conform to this section.
1614A. 4.2.1 Longitudinal ties. Longitudinal ties shall
consist of continuous reinforcement in slabs; continuous
or spliced decks or sheathing; continuous or spliced
members framing to, within or across walls; or connec-
tions of continuous framing members to walls. Longitu-
dinal ties shall extend across interior load-bearing walls
and shall connect to exterior load-bearing walls and shall
be spaced at not greater than 10 feet (3038 mm) on cen-
ter. Ties shall have a minimum nominal tensile strength,
Tj, given by Equation 16A-46. For ASD the minimum
nominal tensile strength shall be permitted to be taken as
1 .5 times the allowable tensile stress times the area of the
tie.
(Equation 16A-46)
Tj^~wLS<0LtS
where:
L = The span of the horizontal element in the direc-
tion of the tie, between bearing walls, feet (m).
w = The weight per unit area of the floor or roof in the
span being tied to or across the wall, psf (N/m^).
S = The spacing between ties, feet (m).
2010 CALIFORNIA BUILDING CODE
117
STRUCTURAL DESIGN
a^^ = A coefficient with a value of 1,500 pounds per
foot (2.25 kN/m) for masonry bearing wall struc-
tures and a value of 375 pounds per foot (0.6
kN/m) for structures with bearing walls of
cold-formed steel light-frame construction.
1614A. 4.2.2 Transverse ties. Transverse ties shall con-
sist of continuous reinforcement in slabs; continuous or
spliced decks or sheathing; continuous or spliced mem-
bers framing to, within or across walls; or connections of
continuous framing members to walls. Transverse ties
shall be placed no farther apart than the spacing of load-
bearing walls. Transverse ties shall have minimum nomi-
nal tensile strength Tj^ given by Equation 16A-46. For
ASD the minimum nominal tensile strength shall be per-
mitted to be taken as 1 .5 times the allowable tensile stress
times the area of the tie.
1614A.4.2.3 Perimeter ties. Perimeter ties shall consist
of continuous reinforcement in slabs; continuous or
spliced decks or sheathing; continuous or spliced mem-
bers framing to, within or across walls; or connections of
continuous framing members to walls. Ties around the
perimeter of each floor and roof shall be located within 4
feet (1219 mm) of the edge and shall provide a nominal
strength in tension not less than Tp, given by Equation
16A-47. For ASD the minimum nominal tensile strength
shall be permitted to be taken as 1.5 times the allowable
tensile stress times the area of the tie.
7; = 200w<p7^
For SI:
Tp = 90.7w < ^r
(Equation 16A-47)
where:
w =
As defined in Section 1614A.4.2.1.
A coefficient with a value of 16,000 pounds
(7200 kN) for structures with masonry bearing
walls and a value of 4,000 pounds (1300 kN) for
structures with bearing walls of cold-formed
steel light-frame construction.
1614A.4.2.4 Vertical ties. Vertical ties shall consist of
continuous or spliced reinforcing, continuous or spliced
members, wall sheathing or other engineered systems.
Vertical tension ties shall be provided in bearing walls
and shall be continuous over the height of the building.
The minimum nominal tensile strength for vertical ties
within a bearing wall shall be equal to the weight of the
wall within that story plus the weight of the diaphragm
tributary to the wall in the story below. No fewer than two
ties shall be provided for each wall. The strength of each
tie need not exceed 3,000 pounds per foot (450 kN/m) of
wall tributary to the tie for walls of masonry construction
or 750 pounds per foot (140 kN/m) of wall tributary to
the tie for walls of cold-formed steel light-frame con-
struction.
T = Transverse
L = Longitudinal
V = Vertical
P = Perimeter
FIGURE 1 61 4A4
LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES
118
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
SECTION 16154
MODIFICATIONS TO ASCE 7
1615 AA General The textof ASCE 7 shall be modified as indi-
cated in Sections 1615A.1.1 through 1615A.L38.
1615A.1J ASCE 7, Section ILL Modify ASCE 7 Section
1 LI by the adding Section 11.1.5 as fo Hows:
11.1.5 Structural design criteria. Where design reviews
are required in ASCE 7, Chapters 16, 17 or 18, the
ground motion, analysis, and design methods, material
assumptions and acceptance criteria proposed by the
engineer shall be submitted to the enforcement agency in
the form of structural design criteria for approval.
[OSHPD 1 & 41 Peer review requirements in Section
341 4 A shall apply to design reviews required by ASCE 7
Chapters 17 and 18.
1615A.L2A [DSA-SS] ASCE 7, Section 11,4 J. Modify
ASCE 7 Section 11.4. 7 as follows:
11,4.7 Site-specific ground motion procedures. The
site-specific ground motion procedure set forth in ASCE
7 Section 21 as modified in Section 1803 A. 6 of this code
is permitted to be used to determine ground motion for
any structure.
Unless otherwise approved, the site-specific proce-
dure per ASCE 7 Section 21 as modified by Section
1803A.6 of this code shall be used where any of the fol-
lowing conditions apply:
1) A site response analysis shall be performed per
Section 2 LI, and a ground motion hazard analysis
shall be performed in accordance with Section
21.2 for the following structures:
a) Structure located in Type E soils and
mapped MCE spectral acceleration at short
periods (SJ exceeds 2.0g.
b) Structures located in Type F soils.
Exceptions:
1) Where S^ is less than 0.20g, use of
Type E soil profile shall be permit-
ted.
2) Where exception to Section 20.3.1
is applicable except for base iso-
lated buildings.
2) A ground motion hazard analysis shall be per-
formed in accordance with Section 21.2 when:
a) A time history response analysis of the
building is performed as part of the design.
b) The building site is located in an area identi-
fied in Section 4-3 17(e) of the California
Administrative Code (Part 1, Title 24,
C.C.R).
c) For seismically isolated structures and for
structures with damping systems.
I615A,1,2B, [OSHPD 1 & 4] Modify ASCE 7
Section 11.4. 7 by adding the following:
For buildings assigned to Seismic Design
Category F, or when required by the building
official, a ground motion hazard analysis
shall be performed in accordance with
ASCE 7 Chapter 21 as modified by Section
1803A.6.
16I5A,1,3 ASCE 7, Table 12,2-L Modify ASCE 7 Table
12.2-1 as follows:
A, BEARING WALL SYSTEMS
5. Intermediate Precast Shear Walls^Not per-
mitted by OSHPD.
14. Light-framed walls with shear panels of all
other materials — Not permitted by OSHPD and
DSA-SS.
B, BUILDING FRAME SYSTEMS
2. Steel eccentrically braced frames, non-
moment-resisting connections at columns away
from links — Not permitted by OSHPD.
4. Ordinary steel concentrically braced frames —
Not permitted by OSHPD.
9. Intermediate Precast Shear Walls — Not per-
mitted by OSHPD.
24. Light-framed walls with shear panels of all
other materials — Not permitted by OSHPD and
DSA-SS.
25. Buckling-restrained braced frames, non-
moment-resisting beam-column connections
—Not permitted by OSHPD.
27. Special steel plate shear wall — Not permitted
by OSHPD.
C, MOMENT-RESISTING FRAME SYSTEMS
2. Special steel truss moment frames — Not permit-
ted by OSHPD.
3. Intermediate steel moment frames — Not permit-
ted by OSHPD.
4. Ordinary steel moment frames — Not permitted
by OSHPD.
Exceptions:
1. Systems listed in this section can be used as an
alternative system when preapproved by the
enforcement agency.
2. Rooftop or other supported structures not exceed-
ing two stories in height and 10 percent of the total
structure weight can use the systems in this section
when designed as components per ASCE 7 Chap-
ter 13.
2010 CALIFORNIA BUILDING CODE
119
STRUCTURAL DESIGN
3. Systems listed in this section can be used for seis-
mically isolated buildings when permitted by Sec-
tion 1613A,6.2.
1615A.L4ASCE 7, Section 1223,1, Modify ASCE 7 Sec^
tion 12.2.3.1 by adding the following additional require-
ments for a two stage equivalent lateral force procedure or
modal response spectrum procedure:
e. Where design of elements of the upper portion is gov-
emed by special seismic load combinations, the spe-
cial loads shall be considered in the design of the
lower portion.
1615AJ,5ASCE 7, Section 12.3.3, Modify first sentence of
ASCE 7 Section 12.3.3.1 as follows :
12.3.3.1 Prohibited horizontal and vertical irregulari-
ties for Seismic Design Categories D through F. Struc-
tures assigned to Seismic Design Category D, E or F
having horizontal structural irregularity Type lb of
Table 12.3-1 or vertical structural irregularities Type
lb, 5a or 5b of Table 12.3-2 shall not be permitted.
1615AJ.6ASCE 7, Section 12.7.2. Modify ASCE 7 Section
12.7.2 by adding Item 5 to read as follows:
5. Where buildings provide lateral support for walls
retaining earth, and the exterior grades on opposite
sides of the building differ by more than 6 feet (1829
mm), the load combination of the seismic increment of
earth pressure due to earthquake acting on the higher
side, as determined by a geotechnical engineer quali-
fied in soils engineering plus the difference in earth
pressures shall be added to the lateral forces pro-
vided in this section.
1615A.1.7 ASCE 7, Section 12.8.7. Modify ASCE 7 Section
12.8.7 by replacing Equation 12.8-16 as follows:
6 =
V.hC,
(12,8-16)
1615A.1.8 ASCE 7, Section 12.9.4. Replace ASCE 7 Sec-
tion 12.9.4 as follows:
12.9.4 Scaling design values of combined response.
Modal base shear shall not be less than the base shear
calculated using the equivalent lateral force procedure
of Section 12.8.
1615A.1.9ASCE 7, Section 12.10.2.1. Modify ASCE 7 Sec-
tion 12.10.2.1 by adding the following:
The value of HqQe ^^^^ "^ ^^^^ combinations with
overstrength factors in ASCE 7-05 Section 12.4.3.2 for
design of collector elements, splices and their connections
to resisting elements may be taken as the largest of the fol-
lowing:
1) Q^oF, (where F, is given by ASCE 7-05 Eq.12.8-11)
2) Q,^^^ (where F^, is given by ASCE 7-05 Eq. 12.10-1
ignoring the O.iS^slWp^ minimum)
3) 0.2SjyslWp^ (Minimum value from Section 12.10.1.1)
1615A.1.10ASCE 7, Section 12.13.1. Modify ASCE 7 Sec-
tion 12.13.1 by adding Section 12.13.1.1 as follows:
12.13.1.1 Foundations and superstructure-to-founda-
tion connections. The foundation shall be capable of
transmitting the design base shear and the overturning
forces from the structure into the supporting soil. Stabil-
ity against overturning and sliding shall be in accor-
dance with Section 160 5 A. LI.
In addition, the foundation and the connection of the
superstructure elements to the foundation shall have the
strength to resist, in addition to gravity loads, the lesser
of the following seismic loads:
1. The strength of the superstructure elements.
2. The maximum forces that would occur in the fully
yielded structural system.
3. Forces from the Load Combinations with
overstrength factor in accordance with ASCE 7
Section 12.4.3.2.
Exceptions:
1. Where referenced standards specify the use of
higher design loads.
2. When it can be demonstrated that inelastic
deformation of the foundation and superstruc-
ture-to-foundation connection will not result in
a weak story or cause collapse of the structure.
3. Where basic structural system consists of light
framed walls with shear panels.
Where the computation of the seismic over-
turning moment is by the equivalent lat-
eral-force method or the modal analysis method,
reduction in overturning moment permitted by
section 12.13.4 of ASCE 7 may be used.
Where moment resistance is assumed at the
base of the superstructure elements, the rotation
andflexural deformation of the foundation as
well as deformation of the superstruc-
ture-to-foundation connection shall be consid-
ered in the drift and deformation compatibility
analyses.
1615A.1.11 ASCE 7, Section 13.1.3. [OSHPD 1&4] Mod-
ify ASCE 7 Section 13.1.3 by the following:
For position retention, the design of supports and attach-
ments for all nonstructural components shall have a compo-
nent importance factor, Ip, equal to 1.5.
1615A.1.12 ASCE 7, Section 13.1.4. Replace ASCE 7 Sec-
tion 13.1.4 with the following:
13.1.4 Exemptions. The following nonstructural compo-
nents are exempt from the requirements of this section:
1. Furniture (except storage cabinets as noted in
Table 13.5-1).
2. Temporary or moveable equipment
Exceptions:
a) Equipment shall be anchored if it is per-
manently attached to the building utility
services such as electricity, gas or water.
120
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
d
For the purposes of this requirement,
*' permanently attached" shall include all
electrical connections except three-
prong plugs for duplex receptacles.
b) The enforcement agency shall be permit-
ted to require temporary attachments for
movable equipment which is usually sta-
tioned in one place and heavier than 400
pounds, when they are not in use for a
period longer than 8 hours at a time.
3. Architectural, mechanical and electrical compo-
nents in Seismic Design Categories D, E or F
where all of the following apply:
a. The component is positively attached to the
structure;
b. Flexible connections are provided between
the component and associated ductwork,
piping and conduit; and either:
i. The component weighs 400 pounds
(1780 N) or less and has a center of
mass located 4 feet (1.22 m) or less
above the adjacent floor or roof level
that directly support the component;
Exception: Special Certification
Requirements for Designated Seis-
mic Systems in accordance with
Section 13.2.2 shall apply.
or
a. The component weighs 20 pounds (89
N) or less or, in the case of a distrib-
uted system, 5 lb/ft (73 N/m) or less.
Exception: The enforcement
agency shall be permitted to
require attachments for equipment
with hazardous contents to be
shown on construction documents
irrespective of weight.
1615AJJ3 ASCE 7, Section 13.3,2. Modify ASCE 7 Sec-
tion 13.3.2 by adding the following:
The seismic relative displacements to be used in design of
displacement sensitive nonstructural components is Dp 1
instead of Dp, where Dp is given by Equations 13.3-5 to 13.3-8
and I is the building importance factor given in Section 11.5.
1615A.1J4 ASCE 7, Section 13.4 Replace ASCE 7 Sec-
tions 13.4.1 and 13.4.2 with the following:
13.4.1 Design force in the attachment. The force in the
attachment shall be determined based on the prescribed
forces and displacements for the component as deter-
mined in Sections 13.3,1 and 13.3.2 except that Rp shall
not be taken as larger than 6.
13.4.2 Anchors in concrete or masonry.
13.4.2.1 Anchors in concrete. Anchors in concrete
used for component anchorage shall be designed in
accordance with Appendix D ofACI 318.
13.4.2.2 Anchors in masonry. Anchors in masonry
used for component anchorage shall be designed in
accordance with ACI 530. Anchors shall be designed
to be governed by the tensile or shear strength of a
ductile steel element.
Exception: Anchors shall be permitted to be
designed so that the attachment that the anchor is
connecting to the structure undergoes ductile
yielding at a load level corresponding to anchor
forces not greater than their design strength, or the
minimum design strength of the anchors shall be at
least 2.5 times the factored forces transmitted by
the attachment.
13.4.2.3 Postinstalled anchors in concrete and
masonry. Postinstalled anchors shall fulfill the
requirements of Section 13.4.2.1 or 13.4.2.2.
Postinstalled anchors in concrete used for component
anchorage shall be pre- qualified for seismic applica-
tions in accordance with ACI 355.2, ICC-ES AC193
or ICC-ES AC308. Postinstalled anchors in masonry
used for component anchorage shall be prequalified
for seismic applications in accordance with ICC-ES
AC01,AC58orAC106.
Exceptions:
1) Adhesive anchors shall not be permitted in
overhead applications or application with
sustained (continuous) tension load that can
lead to creep.
2) Anchors pre-qualified for seismic applica-
tions need not be governed by the steel
strength of a ductile steel element.
1615A.L15 ASCE 7, Section 13.4.5. Replace ASCE 7 Sec-
tion 13.4.5 with the following:
13.4.5 Power actuated fasteners. Power actuated fasten-
ers in concrete or steel shall not be used for sustained
tension loads or for brace applications in Seismic
Design Categories D, E, or F unless approved for seis-
mic loading. Power actuated fasteners in masonry shall
not be permitted unless approved for seismic loading.
Exception: Power actuated fasteners in concrete
used for support of acoustical tile or lay-in panel sus-
pended ceiling applications and distributed systems
where the service load on any individual fastener
does not exceed 90 lb (400 N). Power actuated fasten-
ers in steel where the service load on any individual
fastener does not exceed 250 lb (1,112 N).
1615A.1.16 ASCE 7, Section 13.5.6. Replace ASCE 7, Sec-
tion 13.5.6 with the following:
13.5.6 Suspended ceilings. Suspended ceilings shall be
in accordance with this section.
13.5.6.1 Seismic forces. The weight of the ceiling,
Wp, shall include the ceiling grid; ceiling tiles or pan-
els; light fixtures if attached to, clipped to, or laterally
supported by the ceiling grid; and other components
that are laterally supported by the ceiling. Wp shall be
taken as not less than 4 psf(19 N/rr?).
2010 CALIFORNIA BUILDING CODE
121
STRUCTURAL DESIGN
The seismic force^ Fp, shall be transmitted through
the ceiling attachments to the building structural ele-
ments or the ceiling-structure boundary.
13.5,6,2 Seismic design requirements. Suspended
acoustical tile or lay-in panel ceilings shall be
designed in accordance with ASTM E 580 Section
5,2.8.8 and the requirements of Sections } 3.5.6.2.1
and 13.5.6.2.2, or be designed in accordance with
Section 13.2.1.1, or be seismically qualified in accor-
dance with Sections 13.2.5 or 13.2.6.
13.5.6.2.1 Industry standard construction for
acoustical tile or lay-in panel ceilings. Acoustical
tile or lay -in panel ceilings in Seismic Design Cat-
egories D, E, and F shall be designed and installed
in accordance with ASTM C 635, ASTM C 636,
and ASTM E 580, Section 5 - Seismic Design Cate-
gories D, Ey and F as modified by Section
13.5.6.2.2.
13.5.6.2.2 Modification to ASTM E 580. Modify
ASTM E 580 by the following:
1. Exitways. Lay -in ceiling assemblies in
exitways of hospitals and essential services
buildings shall be installed with a main run-
ner or cross runner surrounding all sides of
each piece of tile, board or panel and each
light fixture or grille. A cross runner that
supports another cross runner shall be con-
sidered as a main runner for the purpose of
structural classification. Splices or intersec-
tions of such runners shall be attached with
through connectors such as pop rivets,
screws, pins, plates with end tabs or other
approved connectors.
2. Corridors and Lobbies. Expansion joints
shall be provided in the ceiling at intersec-
tions of corridors and at junctions of corri-
dors and lobbies or other similar areas.
3. Lay-in panels. Metal panels and panels
weighing more than V2 pounds per square
foot (24 N/m^) other than acoustical tiles
shall be positively attached to the ceiling
suspension runners.
4. Lateral force bracing. Lateral force brac-
ing is required for all ceiling areas except
that they shall be permitted to be omitted in
rooms with floor areas up to 144 square feet
when perimeter support in accordance with
ASTM E 580 Sections 5.2.2 and 5.2.3 are
provided and perimeter walls are designed
to carry the ceiling lateral forces.
5. Ceiling fixtures. Fixtures installed in acous-
tical tile or lay -in panel ceilings shall be
mounted in a manner that will not compro-
mise ceiling performance.
All recessed or drop-in light fixtures and
grilles shall be supported directly from the
fixture housing to the structure above with a
minimum of two 12 gage wires located at
diagonally opposite comers. Leveling and
positioning of fixtures may be provided by
the ceiling grid. Fixture support wires may
be slightly loose to allow the fixture to seat in
the grid system. Fixtures shall not be sup-
ported from main runners or cross runners if
the weight of the fixtures causes the total
dead load to exceed the deflection capability
of the ceiling suspension system.
Fixtures shall not be installed so that the
main runners or cross runners will be eccen-
trically loaded.
Surface-mounted fixtures shall be
attached to the main runner with at least two
positive clamping devices made of material
with a minimum of 14 gage. Rotational
spring catches do not comply. A 12 gage sus-
pension wire shall be attached to each
clamping device and to the structure above.
6. Partitions, Where the suspended ceiling sys-
tem is required to provide lateral support for
the permanent or relocatable partitions, the
connection of the partition to the ceiling sys-
tem, the ceiling system members and their
connections, and the lateral force bracing
shall be designed to support the reaction
force of the partition from prescribed loads
applied perpendicular to the face of the par-
tition. Partition connectors, the suspended
ceiling system and the lateral-force bracing
shall all be engineered to suit the individual
partition application and shall be shown or
defined in the drawings or specifications.
1615A.1,17 ASCE 7, Section 13,5.7, [OSHPD 1 & 4] Mod-
ify ASCE 7 Section 13.5.7 by the following:
All access floors shall be special access floors in accor-
dance with Section 13.5.7.2.
1615A.1.18 Reserved.
1615A,1.19 Reserved.
1615A,L20 ASCE 7, Section 13.6.5. Modify ASCE 7, Sec-
tion 13.6.5 by deleting Item 6 in Section 13. 6.5.5 and adding
Section 13.6.5.6 as follows:
13,6.5.6 Conduit, Cable Tray, and Other Electrical Dis-
tribution Systems (Raceways). Raceways shall be
designed for seismic forces and seismic relative dis-
placements as required in Section 13.3. Conduit greater
than 2.5 inches (64 mm) trade size and attached to pan-
els, cabinets or other equipment subject to seismic rela-
tive displacement of Section 13.3.2 shall be provided
with flexible connections or designed for seismic forces
p
122
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
and seismic relative displacements as required in Section
133,
Exceptions:
1. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for raceways where either:
a. Trapeze assemblies are used to support
raceways and the total weight of the race-
way supported by trapeze assemblies is
less than 10 lb/ft (146 N/m), or
b. The raceway is supported by hangers and
each hanger in the raceway run is 12 in.
(305 mm) or less in length from the race-
way support point to the supporting
structure. Where rod hangers are used
with a diameter greater than % inch, they
shall be equipped with swivels to prevent
inelastic bending in the rod.
2. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for conduit, regardless of the value of
Ip, where the conduit is less than 2.5 in. (64 mm)
trade size.
1615A,L21 ASCE 7, Section 13.6.7. Replace ASCE 7, Sec-
tion 13.6.7 with the following :
13,6.7 Ductwork. HVAC and other ductwork shall be
designed for seismic forces and seismic relative dis-
placements as required in Section 13.3. Ductwork
designed to carry toxic, highly toxic, or explosive gases,
or used for smoke control shall be designed and braced
without considering the Exceptions noted below.
Exceptions:
The following exceptions pertain to ductwork not
designed to carry toxic, highly toxic, or flammable
gases or used for smoke control:
1. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required for ductwork where either:
a. Trapeze assemblies are used to support
ductwork and the total weight of the
ductwork supported by trapeze assem-
blies is less than 10 lb/ft (146 N/m); or
b. The ductwork is supported by hangers
and each hanger in the duct run is 12 in.
(305 mm) or less in length from the duct
support point to the supporting structure.
Where rod hangers are used with a diam-
eter greater than % inch, they shall be
equipped with swivels to prevent inelastic
bending in the rod.
2. Design for the seismic forces and relative dis-
placements of Section 13.3 shall not be
required where provisions are made to avoid
impact with larger ducts or mechanical compo-
nents or to protect the ducts in the event of such
impact; and HVAC ducts have a cross- sec-
tional area of6ft^ (0.557 m^) or less, or weigh
10 lb/ft (146 N/m) or less.
HVAC duct systems fabricated and installed in accor-
dance with standards approved by the authority having
jurisdiction shall be deemed to meet the lateral bracing
requirements of this section.
Components that are installed in-line with the duct
system and have an operating weight greater than 75 lb
(334 N), such as fans, heat exchangers and humidifiers,
shall be supported and laterally braced independent of
the duct system and such braces shall meet the force
requirements of Section 13.3.L Appurtenances such as
dampers, louvers and diffusers shall be positively
attached with mechanical fasteners. Unbraced piping
attached to in-line equipment shall be provided with ade-
quate flexibility to accommodate the seismic relative dis-
placements of Section 13.3.2.
1615A.L22 ASCE 7, Section 13.6.8. Replace ASCE 7, Sec-
tion 13.6.8 with the following:
13.6.8 Piping Systems. Unless otherwise noted in this
section, piping systems shall be designed for the seismic
forces and seismic relative displacements of Section
13.3. ASME pressure piping systems shall satisfy the
requirements of Section 13.6.8.1. Fire protection sprin-
kler piping shall satisfy the requirements of Section
13.6.8.2. Elevator system piping shall satisfy the require-
ments of Section 13.6.10.
Where other applicable material standards or recog-
nized design bases are not used, piping design including
consideration of service loads shall be based on the fol-
lowing allowable stresses:
a. For piping constructed with ductile materials
(e.g., steel, aluminum, or copper), 90 percent of
the minimum specified yield strength.
b. For threaded connections in piping constructed
with ductile materials, 70 percent of the minimum
specified yield strength.
c. For piping constructed with nonductile materials
(e.g., cast iron, or ceramics), 10 percent of the
material minimum specified tensile strength.
d. For threaded connections in piping constructed
with nonductile materials, 8 percent of the mate-
rial minimum specified tensile strength.
Piping not detailed to accommodate the seismic rela-
tive displacements at connections to other components
shall be provided with connections having sufficient flex-
ibility to avoid failure of the connection between the
components.
13.6.8.1 ASME Pressure Piping Systems. Pressure
piping systems, including their supports, designed
and constructed in accordance with ASME B 31 shall
be deemed to meet the force, displacement, and other
requirements of this section. In lieu of specific force
and displacement requirements provided in ASME B
2010 CALIFORNIA BUILDING CODE
123
STRUCTURAL DESIGN
31, the force and displacement requirements of Sec-
tions 13.3 shall be used.
13.6.8.2 Fire protection sprinkler piping systems.
Fire protection sprinkler piping designed and con-
structed in accordance with NFPA 13 shall be deemed
to meet the force and displacement requirements of
this section. The exceptions of Section 13.6.8.3 shall
not apply.
Exception: Pipe hangers, bracing, and anchor
capacities shall be determined in accordance with
material chapters of the California Building Code,
in lieu of using those in NFPA 13. The force and
displacement requirements of Section 13.3 or
those in the NFPA 13 may be used for design.
13.6.8.3 Exceptions. Design of piping systems and
attachments for the seismic forces and relative dis-
placements of Section 13.3 shall not be required
where one of the following conditions apply:
1. Trapeze assemblies are used to support piping
whereby no single pipe exceeds the limits set
forth in 3a. or b. below and the total weight of
the piping supported by the trapeze assemblies
is less than 10 lb/ft (146 N/m).
2. The piping is supported by hangers and each
hanger in the piping run is 12 in. (305 mm) or
less in length from the top of the pipe to the sup-
porting structure. Where pipes are supported
on a trapeze, the trapeze shall be supported by
hangers having a length of 12 in. (305 mm) or
less. Where rod hangers are used with a diame-
ter greater than % inch, they shall be equipped
with swivels, eye nuts or other devices to pre-
vent bending in the rod.
3. Piping having an Rp in Table 13.6-1 of 4.5 or
greater is used and provisions are made to
avoid impact with other structural or
nonstructural components or to protect the pip-
ing in the event of such impact and where the
following size requirements are satisfied:
a. For Seismic Design Categories D,EorF
and values of Ip greater than one, the
nominal pipe size shall be 1 inch (25 mm)
or less.
b. For Seismic Design Categories D, E or F,
where lp = l.Othe nominal pipe size shall
be 3 inches (80 mm) or less.
The exceptions above shall not apply to elevator
piping.
13.6.8.4 Other Piping Systems. Piping not designed
and constructed in accordance with ASME B 31 or
NFPA 13 shall comply with the requirements of Sec-
tion 13.6.11.
1615A.1.23 ASCE 7, Section 13.6.10.1. Modify ASCE 7
Section 13.6.10.1 by adding Section 13.6.10.1.1 as follows:
13.6.10.1.1 Elevators guide rail support. The design of
guide rail support-bracket fastenings and the supporting
structural framing shall use the weight of the counter-
weight or maximum weight of the car plus not less than
40 percent of its rated load. The seismic forces shall be
assumed to be distributed one third to the top guiding
members and two thirds to the bottom guiding members
of cars and counterweights, unless other substantiating
data are provided. In addition to the requirements of
ASCE 7 Section 13.6.10.1, the minimum seismic forces
shall be 0.5 g acting in any horizontal direction.
1615A.1.24 ASCE 7, Section 13.6.10.4. Replace ASCE 7
Section 13.6.10.4 as follows:
13.6.10.4 Retainer plates. Retainer plates are required at
the top and bottom of the car and counterweight, except
where safety devices acceptable to the enforcement
agency are provided which meet all requirements of the
retainer plates, including full engagement of the
machined portion of the rail. The design of the car, cab
stabilizers, counterweight guide rails and counterweight
frames for seismic forces shall be based on the following
requirements:
1. The seismic force shall be computed per the
requirements of ASCE 7 Section 13.6.10.1. The
minimum horizontal acceleration shall be 0.5 g for
all buildings.
2. Wp shall equal the weight of the counterweight or
the maximum weight of the car plus not less than
40 percent of its rated load.
3. With the car or counterweight located in the most
adverse position, the stress in the rail shall not
exceed the limitations specified in these regula-
tions, nor shall the deflection of the rail relative to
its supports exceed the deflection listed below:
RAIL SIZE
(weight per foot
of length,
pounds)
WIDTH OF
MACHINED
SURFACE
(Inches)
ALLOWABLE
RAIL
DEFLECTION
(Inches)
8
1%
0.20
11
1%
0.30
12
1%
0.40
15
l'%2
0.50
18^/2
l'%2
0.50
22%
2
0.50
30
2%
0.50
For SI: 1 inch = 25 mm, I foot = 305 mm, 1 pound = 0.454 kg.
Note: Deflection limitations are given to maintain a consistent factor of safety
against disengagement of retainer plates from the guide rails during an
earthquake.
4. Where guide rails are continuous over supports and
rail joints are within 2 feet (610 mm) of their sup-
porting brackets^ a simple span may be assumed.
5. The use of spreader brackets is allowed.
6. Cab stabilizers and counterweight frames shall be
designed to withstand computed lateral load with
a minimum horizontal acceleration of 0.5 g.
124
2010 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
1615A,L25ASCE 7, Section 16,1,3,2, Modify ASCE 7 Sec-
tion 16.1.3.2 by the following:
Where next generation attenuation relations are used in
accordance with Section 1803A.6.2, each pair of motions
shall be scaled such that in the period range from 0.2T to
L5Ty the average of the SRSS spectra from all horizontal
component pairs does not fall below the corresponding
ordinate of the design response spectrum determined using
NGA relations.
At sites within 3.1 miles (5 km) of an active fault that con-
trols the hazard, each pair of components shall be rotated to
the fault-normal and fault-parallel direction of the causative
fault, and shall be scaled so that average of the fault-normal
components is not less than the Maximum Considered Earth-
quake (MCE) response spectrum determined using NGA
relations for each period range from 0.2Tto L5T.
1615A,L26 ASCE 7, Section 16.1,4, Modify ASCE 7 Sec-
tion 16.1.4 by the following:
For each ground motion analyzed, the individual
response parameters shall be multiplied by the following
scalar quantities:
a. Force response parameters shall be multiplied by 1/R,
where I is the importance factor determined in accor-
dance with Section 1L5.1, and R is the response mod-
ification coefficient selected in accordance with
Section 12.2.1.
b. Drift quantities shall be multiplied by CJR, where Q
is the deflection amplification factor specified in
Table 12.2-1.
The distribution of horizontal shear shall be in accor-
dance with Section 12.8.4.
1615A,1,27 ASCE 7, Section 16,2,4, Modify ASCE 7 Sec-
tion 16.2.4 by the following:
a) Where site is located within 3. 1 miles (5 km) of an
active fault at least seven ground motions shall be
analyzed and response parameters shall be based on
larger of the average of the maximum response with
ground motions applied as follows:
1. Each of the ground motions shall have their
maximum component at the fundamental
period aligned in one direction.
2. Each of the ground motion 's maximum compo-
nent shall be rotated orthogonal to the previous
analysis direction.
b) Where site is located more than 3.1 miles (5 km) from
an active fault at least 10 ground motions shall be ana-
lyzed. The ground motions shall be applied such that
one-half shall have their maximum component aligned
in one direction and the other half aligned in the
orthogonal direction. The average of the maximum
response of all the analyses shall be used for design.
16I5AJ,28 ASCE 7, Section 16,2.4.2 [OSHPD 1 & 4]
Modify ASCE 7 Section 16.2.4.2 by the following:
Acceptance criteria for elements subjected to deformation
beyond their linear range of response shall be based on ASCE
41 for Immediate Occupancy (10) at Design Earthquake (DE)
and Life Safety (LS) at Maximum Considered Earthquake
(MCE). For LS acceptance criteria at MCE, primary compo-
nents shall be within the acceptance criteria for primary com-
ponents and secondary components shall be within the
acceptance criteria for secondary components.
1615A.L29 ASCE 7, Section 17,2.1, Modify ASCE 7 Sec-
tion 17.2.1 by adding the following:
The importance factor, I^, for parts and portions of a seis-
mically isolated building shall be the same as that required
for a fixed-base building of the same occupancy category.
1615A.1,30ASCE 7, Section 17,2,4,7, Modify ASCE 7 Sec-
tion 17.2.4.7 by adding the following:
The effects of uplift and/or rocking shall be explicitly
accounted for in the analysis and in the testing of the isola-
tor units.
1615A.i,31 ASCE 7, Section 17,2,5,2, Modify ASCE 7,
Section 17.2.5.2 by adding the following:
The separation requirements for the building above the
isolation system and adjacent buildings shall be the sum of
the factored displacements for each building. The factors to
be used in determining separations shall be:
1. For seismically isolated buildings, the deformation <C
resulting from the analyses using the maximum con- <
sidered earthquake unmodified by Rf.
2. For fixed based buildings, Q times the elastic defor-
mations resulting from an equivalent static analysis
using the seismic base shear computed via ASCE 7
Section 12.8.
1615A,1,32 ASCE 7, Section 17,3,2, Replace ASCE 7, Sec-
tion 17.3.2 with the following:
17,3,2 Ground Motion Histories, Where response his-
tory procedures are used, ground motions shall consist of
pairs of appropriate horizontal ground motion accelera-
tion components developed in accordance with Section
16.1.3.2 except that 0.2T and 1.5T shall be replaced by
0.5 Td and 1.25Tj^, respectively, where Tp and T^ are
defined in Section 17.5.3.
1615A,1,33 ASCE 7, Section 17,4, Modify ASCE 7, Section
17.4 by adding the following:
17.4.2.3 Linear procedures. Linear procedures shall be
limited to structures located at sites with Sj less than
0.6g.
1615A,1,34 ASCE 7, Section 17.6 Modify ASCE 7, Section
17.6 by the following:
17,6,1,1 Minimum seismic force. For the response spec-
trum and linear response history procedures, V^ and V^,
shall not be taken less than those calculated in accor-
dance with Equations 17.5-7 and 17.5-8.
1615A,1,35 ASCE 7, Section 18,3,L Modify ASCE 7, Sec-
tion 18.3.1 by replacing the third paragraph with the follow-
ing:
If the calculated force in an element of the seismic force
resisting system does not exceed 1.5 times its nominal
2010 CALIFORNIA BUILDING CODE
125
STRUCTURAL DESIGN
strength for the Maximum Considered Earthquake (MCE)
nor its nominal strength for the design earthquake (DE), the
element is permitted to be modeled as linear
1615AJJ6ASCE 7, Section 2L4, Replace ASCE 7, Sec-
tion 21.4 with the following:
21,4 Design Acceleration Parameters, Where the
site-specific procedure is used to determine the design
ground motion in accordance with Section 21.3, the
parameter S^^ shall be taken as the spectral acceleration,
So, obtained from the site-specific spectra at a period of
0.2 sec, except that it shall not be taken less than 90 per-
cent of the peak spectral acceleration, Sa, at any period
larger than 0.2 second. The parameter Spj shall be taken
as the greater of the spectral acceleration, S^, at a period
of 1 sec or two times the spectral acceleration, S^, at a
period of 2 sec.
For use with the equivalent lateral force procedure, the
site specific spectral acceleration, S^ at T shall be permit-
ted to replace S^j/T in Equation 12.8-3 and Sj^jT/P in
Equation 12.8-4. The parameter S^^s calculated per this
section shall be permitted to be used in Equations 12,8-2
and 12.8-5. The mapped value of Si shall be used in
Equation 12.8-6. The parameters 5^^ anJ Sj^j shall be
taken as 1.5 times Sj^s ^^^ ^d]> respectively. The values so
obtained shall not be less than 80 percent of the values
determined in accordance with Section 11.43 for Sj^s
and Sj^j and Section 11.4.4 for Sj^s ^^^ ^oi-
161 5 A, 1,37. Earthquake Motion Measuring Instrumenta-
tion and Monitoring, [OSHPD 1 & 4] Modify ASCE 7 by
the following:
Scope: For buildings with a seismic isolation system, a
damping system or a lateral force resisting system
(LFRS) not listed in ASCE 7 Table 12.2-1, earthquake
motion measuring instrumentation and monitoring shall
be required.
Instrumentation: There shall be a sufficient number of
instruments to characterize the response of the building
during an earthquake and shall include at least one
tri-axial free field instrument or equivalent. A proposal
for instrumentation and equipment specifications shall
be forwarded to the enforcement agency for review and
approval. The owner of the building shall be responsible
for the implementation of the instrumentation program.
Maintenance of the instrumentation and removal/
processing of the records shall be the responsibility of the
enforcement agency.
Monitoring: After every significant seismic events,
where the ground shaking acceleration at the site
exceeds 0.3 g, or the acceleration at any monitored build-
ing level exceeds 0.8 g, as measured by the seismic moni-
toring system in the building, the owner shall retain a
structural engineer to make an inspection of the struc-
tural system. The inspection shall include viewing the
performance of the building, reviewing the strong motion
records, and a visual examination of the isolators, damp-
ers and connections for deterioration, offset or physical
damage. A report for each inspection, including conclu-
sions on the continuing adequacy of the structural sys-
tem, shall be submitted to the enforcement agency.
1615A,1,38 Operational Nonstructural Performance
Level Requirements, [OSHPD 1 & 4] New buildings
designed and constructed to this code shall be deemed to
satisfy operational nonstructural performance level when:
L The facility has on-site supplies of water and holding
tanks for wastewater, sufficient for 72 hours of emer-
gency operations, which are integrated into the build-
ing plumbing systems. As an alternative, hook-ups to
allow for the use of transportable sources of water
and sanitary waste water disposal shall be permitted.
2, An on-site emergency system as defined within Part 3,
Title 24 is incorporated into the building electrical
system for critical care areas. Additionally, the sys-
tem shall provide for radiological service and an
onsitefuel supply for 72 hours of acute care opera-
tion.
126
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
1702 - Approved Agency
X
X
1704.1
X
X
1704.1.1
X
X
1704.6.2
X
1711.1
X
2010 CALIFORNIA BUILDING CODE
127
1 28 201 CALIFORNIA BUILDING CODE
CHAPTER 17
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
SECTION 1701
GENERAL
1701.1 Scope. The provisions of this chapter shall govern the
quality, workmanship and requirements for materials covered.
Materials of construction and tests shall conform to the appli-
cable standards listed in this code,
1701.2 New materials. New building materials, equipment,
appliances, systems or methods of construction not provided
for in this code, and any material of questioned suitability pro-
posed for use in the construction of a building or structure, shall
be subjected to the tests prescribed in this chapter and in the
approved rules to determine character, quality and limitations
of use.
1701.3 Used materials. The use of second-hand materials that
meet the minimum requirements of this code for new materials
shall be permitted.
SECTION 1702
DEFINITIONS
1702.1 General. The following words and terms shall, for the
purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
APPROVED AGENCY. An established and recognized
agency regularly engaged in conducting tests or furnishing
inspection services, when such agency has been approved.
[HCD 1 & HCD 2] "Approved agency " shall mean "Listing
agency" and "Testing agency" (See Chapter 2 definitions).
APPROVED FABRICATOR. An established and qualified
person, firm or corporation approved by the building official
pursuant to Chapter 17 of this code.
CERTIFICATE OF COMPLIANCE. A certificate stating
that materials and products meet specified standards or that
work was done in compliance with approved construction doc-
uments.
DESIGNATED SEISMIC SYSTEM. Those architectural,
electrical and mechanical systems and their components that
require design in accordance with Chapter 13 of ASCE 7 and
for which the component importance factor, 7^, is greater than 1
in accordance with Section 13.1.3 of ASCE 7.
FABRICATED ITEM. Structural, load-bearing or lateral
load-resisting assemblies consisting of materials assembled
prior to installation in a building or structure, or subjected to
operations such as heat treatment, thermal cutting, cold work-
ing or reforming after manufacture and prior to installation in a
building or structure. Materials produced in accordance with
standard specifications referenced by this code, such as rolled
structural steel shapes, steel-reinforcing bars, masonry units,
and wood structural panels or in accordance with a standard,
listed in Chapter 35, which provides requirements for quality
control done under the supervision of a third-party quality con-
trol agency shall not be considered "fabricated items."
INSPECTION CERTIFICATE. An identification applied on
a product by an approved agency containing the name of the
manufacturer, the function and performance characteristics,
and the name and identification of an approved agency that
indicates that the product or material has been inspected and
evaluated by an approved agency (see Section 1703.5 and
''Label,'' "Manufacturer's designation" and ''Mark''),
INTUMESCENT FIRE-RESISTANT COATINGS. Thin
film liquid mixture applied to substrates by brush, roller, spray
or trowel which expands into a protective foamed layer to pro-
vide fire-resistant protection of the substrates when exposed to
flame or intense heat.
MAIN WINDFORCE-RESISTING SYSTEM. An assem-
blage of structural elements assigned to provide support and
stability for the overall structure. The system generally
receives wind loading from more than one surface.
MASTIC FIRE-RESISTANT COATINGS. Liquid mixture
applied to a substrate by brush, roller, spray or trowel that pro-
vides fire-resistant protection of a substrate when exposed to
flame or intense heat.
SPECIAL INSPECTION. Inspection as herein required of
the materials, installation, fabrication, erection or placement of
components and connections requiring special expertise to
ensure compliance with approved construction documents and
referenced standards (see Section 1704).
SPECIAL INSPECTION, CONTINUOUS. The full-time
observation of work requiring special inspection by an
approved special inspector who is present in the area where the
work is being performed.
SPECIAL INSPECTION, PERIODIC. The part-time or
intermittent observation of work requiring special inspection
by an approved special inspector who is present in the area
where the work has been or is being performed and at the com-
pletion of the work,
SPRAYED FIRE-RESISTANT MATERIALS. Cementitious
or fibrous materials that are sprayed to provide fire-resistant pro-
tection of the substrates.
STRUCTURAL OBSERVATION. The visual observadon of
the structural system by a registered design professional for
general conformance to the approved construction documents.
Structural observation does not include or waive the responsi-
bility for the inspection required by Section 1 10, 1704 or other
sections of this code.
SECTION 1703
APPROVALS
1703.1 Approved agency. An approved agency shall provide
all information as necessary for the building official to deter-
mine that the agency meets the applicable requirements.
1703.1.1 Independence. An approved agency shall be
objective, competent and independent from the contractor
2010 CALIFORNIA BUILDING CODE
129
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
responsible for the work being inspected. The agency shall
also disclose possible conflicts of interest so that objectivity
can be confirmed.
1703.1.2 Equipment. An approved agency shall have ade-
quate equipment to perform required tests. The equipment
shall be periodically calibrated.
1703.1.3 PersonneL An approved agency shall employ
experienced personnel educated in conducting, supervising
and evaluating tests and/or inspections.
1703.2 Written approval. Any material, appliance, equip-
ment, system or method of construction meeting the require-
ments of this code shall be approved in writing after
satisfactory completion of the required tests and submission of
required test reports.
1703.3 Approved record. For any material, appliance, equip-
ment, system or method of construction that has been
approved, a record of such approval, including the conditions
and limitations of the approval, shall be kept on file in the build-
ing official's office and shall be open to public inspection at
appropriate times.
1703.4 Performance. Specific information consisting of test
reports conducted by an approved testing agency in accordance
with standards referenced in Chapter 35, or other such informa-
tion as necessary, shall be provided for the building official to
determine that the material meets the applicable code require-
ments.
1703.4.1 Research and investigation. Sufficient technical
data shall be submitted to the building official to substanti-
ate the proposed use of any material or assembly. If it is
determined that the evidence submitted is satisfactory proof
of performance for the use intended, the building official
shall approve the use of the material or assembly subject to
the requirements of this code. The costs, reports and investi-
gations required under these provisions shall be paid by the
apphcant.
1703.4.2 Research reports. Supporting data, where neces-
sary to assist in the approval of materials or assemblies not
specifically provided for in this code, shall consist of valid
research reports from approved sources.
1703.5 Labeling. Where materials or assemblies are required
by this code to be labeled, such materials and assemblies shall
be labeled by an approved agency in accordance with Section
1703. Products and materials required to be labeled shall be
labeled in accordance with the procedures set forth in Sections
1703.5.1 through 1703.5.3.
1703.5.1 Testing. An approved agency shall test a represen-
tative sample of the product or material being labeled to the
relevant standard or standards. The approved agency shall
maintain a record of the tests performed. The record shall
provide sufficient detail to verify compliance with the test
standard.
1703.5.2 Inspection and identification. The approved
agency shall periodically perform an inspection, which
shall be in-plant if necessary, of the product or material that
is to be labeled. The inspection shall verify that the labeled
product or material is representative of the product or mate-
rial tested.
1703.5.3 Label information. The label shall contain the
manufacturer's or distributor's identification, model num-
ber, serial number or definitive information describing the
product or material's performance characteristics and
approved agency's identification.
1703.6 Evaluation and foUow-up inspection services. Where
structural components or other items regulated by this code are
not visible for inspection after completion of a prefabricated
assembly, the applicant shall submit a report of each prefabri-
cated assembly. The report shall indicate the complete details of
the assembly, including a description of the assembly and its
components, the basis upon which the assembly is being evalu-
ated, test results and similar information and other data as neces-
sary for the building official to determine conformance to this
code. Such a report shall be approved by the building official
1703.6.1 Follow-up inspection. The applicant shall pro-
vide for special inspections of fabricated items in accor-
dance with Section 1704.2.
1703.6.2 Test and inspection records. Copies of necessary
test and inspection records shall be filed with the building
official.
SECTION 1704
SPECIAL INSPECTIONS
1704.1 General. Where application is made for construction as
described in this section, the owner or the registered design
professional in responsible charge acting as the owner's agent
shall employ one or more approved agencies to perform
inspections during construction on the types of work listed
under Section 1704. These inspections are in addition to the
inspections identified in Section 110.
The special inspector shall be a qualified person who shall
demonstrate competence, to the satisfaction of the building
official, for the inspection of the particular type of construction
or operation requiring special inspection. The registered
design professional in responsible charge and engineers of
record involved in the design of the project are permitted to act
as the approved agency and their personnel are permitted to act
as the special inspector for the work designed by them, pro-
vided those personnel meet the qualification requirements of
this section to the satisfaction of the building official. The spe-
cial inspector shall provide written documentation to the build-
ing official demonstrating his or her competence and relevant
experience or training. Experience or training shall be consid-
ered relevant when the documented experience or training is
related in complexity to the same type of special inspection
activities for projects of similar complexity and material quali-
ties. These qualifications are in addition to quaUfications speci-
fied in other sections of this code.
Exceptions:
1. Special inspections are not required for work of a
minor nature or as warranted by conditions in the
jurisdiction as approved by tiie building official.
130
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
2. Special inspections are not required for building com-
ponents unless the design involves the practice of pro-
fessional engineering or architecture as defined by
applicable state statutes and regulations governing
the professional registration and certification of engi-
neers or architects.
3. Unless otherwise required by the building official,
special inspections are not required for Group U
occupancies that are accessory to a residential occu-
pancy including, but not limited to, those listed in
Section 312.1.
4. [HCD 1] The provisions of Health and Safety Code
Division 13, Part 6 and the California Code of Regu-
lations, Title 25, Division 1, Chapter 3, commencing
with Section 3000, shall apply to the construction and
inspection of factory-built housing as defined in
Health and Safety Code Section 19971.
1704.1.1 Statement of special inspections. The applicant
shall submit a statement of special inspections prepared by
the registered design professional in responsible charge in
I I accordance with Section 107.1 Chapter 1, Division II, as a
condition for issuance. This statement shall be in accor-
dance with Section 1705.
Exceptions:
1. A statement of special inspections is not required
for structures designed and constructed in accor-
dance with the conventional construction provi-
sions of Section 2308. [OSHPD 2] Not permitted
by OSHPD.
2. The statement of special inspections is permitted
to be prepared by a qualified person approved by
the building official for construction not designed
by a registered design professional.
1704.1.2 Report requirement. Special inspectors shall
keep records of inspections. The special inspector shall fur-
nish inspection reports to the building official, and to the
registered design professional in responsible charge.
Reports shall indicate that work inspected was or was not
completed in conformance to approved construction docu-
ments. Discrepancies shall be brought to the immediate
attention of the contractor for correction. If they are not cor-
rected, the discrepancies shall be brought to the attention of
the building official and to the registered design profes-
sional in responsible charge prior to the completion of that
phase of the work. A final report documenting required spe-
cial inspections and correction of any discrepancies noted in
the inspections shall be submitted at a point in time agreed
upon prior to the start of work by the applicant and the
building official.
1704.2 Inspection of fabricators. Where fabrication of struc-
tural load-bearing members and assemblies is being performed
on the premises of a fabricator's shop, special inspection of the
fabricated items shall be required by this section and as
required elsewhere in this code.
1704.2.1 Fabrication and implementation procedures.
The special inspector shall verify that the fabricator main-
tains detailed fabrication and quahty control procedures that
provide a basis for inspection control of the workmanship
and the fabricator's ability to conform to approved con-
struction documents and referenced standards. The special
inspector shall review the procedures for completeness and
adequacy relative to the code requirements for the fabrica-
tor's scope of work.
Exception: Special inspections as required by Section
1704.2 shall not be required where the fabricator is
approved in accordance with Section 1704.2.2.
1704.2.2 Fabricator approval. Special inspections
required by Section 1704 are not required where the work is
done on the premises of a fabricator registered and approved
to perform such work without special inspection. Approval
shall be based upon review of the fabricator's written proce-
dural and quality control manuals and periodic auditing of
fabrication practices by an approved special inspection
agency. At completion of fabrication, the approved fabrica-
tor shall submit a certificate of compliance to the building
official stating that the work was performed in accordance
with the approved construction documents.
1704.3 Steel construction. The special inspections for steel
elements of buildings and structures shall be as required by
Section 1704.3 and Table 1704.3.
Exceptions:
1. Special inspection of the steel fabrication process
shall not be required where the fabricator does not
perform any welding, thermal cutting or heating oper-
ation of any kind as part of the fabrication process. In
such cases, the fabricator shall be required to submit a
detailed procedure for material control that demon-
strates the fabricator's ability to maintain suitable
records and procedures such that, at any time during
the fabrication process, the material specification,
grade and mill test reports for the main stress-carrying
elements are capable of being determined.
2. The special inspector need not be continuously pres-
ent during welding of the following items, provided
the materials, welding procedures and qualifications
of welders are verified prior to the start of the work;
periodic inspections are made of the work in progress
and a visual inspection of all welds is made prior to
completion or prior to shipment of shop welding.
2. 1 . Single-pass fillet welds not exceeding Vjg inch
(7.9 mm) in size.
2.2. Roor and roof deck welding.
2.3. Welded studs when used for structural dia-
phragm.
2.4. Welded sheet steel for cold-formed steel
members.
2.5. Welding of stairs and railing systems.
1704.3.1 Welding. Welding inspection and welding inspec-
tor qualification shall be in accordance with this section.
1704.3.1.1 Structural steel. Welding inspection and
welding inspector qualification for structural steel shall
be in accordance with AWS DLL
2010 CALIFORNIA BUILDING CODE
131
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704.3
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
IBC REFERENCE
1 . Material verification of high-strength bolts, nuts and
washers:
a. Identification markings to conform to ASTM
standards specified in the approved
construction documents.
—
X
AISC 360,
Section A3. 3 and
applicable ASTM
material standards
b. Manufacturer's certificate of compliance
required.
—
X
—
—
2. Inspection of high-strength bolting:
a. Snug-tight joints.
—
X
AISC 360,
Section M2.5
1704.3.3
b.Pretensioned and slip-critical joints using
tum-of-nut with matchmarking, twist-off bolt or
direct tension indicator methods of installation.
—
X
c.Pretensioned and slip-critical joints using
tum-of-nut without matchmarking or calibrated
wrench methods of installation.
X
—
3. Material verification of structural steel and
cold-formed steel deck:
a. For structural steel, identification markings to
conform to AISC 360.
—
X
AISC 360,
Section M5.5
b. For other steel, identification markings to conform
to ASTM standards specified in the approved
construction documents.
—
X
Applicable ASTM
material standards
c. Manufacturer's certified test reports.
—
X
4. Material verification of weld filler materials:
a. Identification markings to conform to AWS
specification in the approved construction
documents.
—
X
AISC 360,
Section A3. 5 and
applicable AWS
A5 documents
b.Manufacturer's certificate of comphance required.
—
X
—
—
5. Inspection of welding:
a. Structural steel and cold-formed steel deck:
1) Complete and partial joint penetration groove
welds.
X
—
AWSDl.l
1704.3.1
2) Multipass fillet welds.
X
—
3) Single-pass fillet welds > Vjg"
X
—
4) Plug and slot welds.
X
—
5) Single-pass fillet welds < V^^"
—
X
6) Floor and roof deck welds.
—
X
AWSD1.3
(continued)
132
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704.3— continued
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
IBC
REFERENCE
b. Reinforcing steel:
~
1) Verification of weldability of reinforcing steel
other than ASTM A 706.
X
AWS D1.4 ACI 318: Section 3.5.2
2) Reinforcing steel resisting flexural and axial
forces in intermediate and special moment
frames, and boundary elements of special
structural walls of concrete and shear
reinforcement.
X
—
3) Shear reinforcement.
X
—
4) Other reinforcing steel.
—
X
6. Inspection of steel frame joint details for compliance:
a. Details such as bracing and stiffening.
—
X
—
1704.3.2
b. Member locations.
—
X
c. Application of joint details at each connection.
—
X
For SI: 1 inch = 25.4 mm.
a. Where applicable, see also Section 1707.1, Special inspection for seismic resistance.
1704.3.1.2 Cold-formed steel. Welding inspection and
welding inspector qualification for cold-formed steel
floor and roof decks shall be in accordance with AWS
D1.3.
1704.3.1.3 Reinforcing steel. Welding inspection and
welding inspector qualification for reinforcing steel shall
be in accordance with AWS D1.4 and ACI 318.
1704.3.2 Details. The special inspector shall perform an
inspection of the steel frame to verify comphance with the
details shown on the approved construction documents,
such as bracing, stiffening, member locations and proper
application of joint details at each connection.
1704.3.3 High-strength bolts. Installation of high-strength
bolts shall be inspected in accordance with AISC 360.
1704.3.3.1 General. While the work is in progress, the
special inspector shall determine that the requirements
for bolts, nuts, washers and paint; bolted parts and instal-
lation and tightening in such standards are met. For bolts
requiring pretensioning, the special inspector shall
observe the preinstallation testing and calibration proce-
dures when such procedures are required by the installa-
tion method or by project plans or specifications;
determine that all plies of connected materials have been
drawn together and properly snugged and monitor the
installation of bolts to verify that the selected procedure
for installation is properly used to tighten bolts. For
joints required to be tightened only to the snug-tight con-
dition, the special inspector need only verify that the con-
nected materials have been drawn together and properly
snugged.
1704.3.3.2 Periodic monitoring. Monitoring of bolt
installation for pretensioning is permitted to be per-
formed on a periodic basis when using the tum-of-nut
method with matchmarking techniques, the direct ten-
sion indicator method or the alternate design fastener
(twist-off bolt) method. Joints designated as snug tight
need be inspected only on a periodic basis.
1704.3.3.3 Continuous monitoring. Monitoring of bolt
installation for pretensioning using the calibrated
wrench method or the turn-of-nut method without
matchmarking shall be performed on a continuous basis.
1704.3.4 Cold-formed steel trusses spanning 60 feet or
greater. Where a cold-formed steel truss clear span is 60
feet (18 288 nun) or greater, the special inspector shall ver-
ify that the temporary installation restraint/bracing and the
permanent individual truss member restraint/bracing are
installed in accordance with the approved truss submittal
package.
1704.4 Concrete construction. The special inspections and
verifications for concrete construction shall be as required by
this section and Table 1704.4.
Exception: Special inspections shall not be required for:
L Isolated spread concrete footings of buildings three
stories or less above grade plane that are fully sup-
ported on earth or rock.
2010 CALIFORNIA BUILDING CODE
133
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
2. Continuous concrete footings supporting walls of
buildings three stories or less above grade plane that
are fully supported on earth or rock where:
2.1. The footings support walls of light-frame con-
struction;
2.2. The footings are designed in accordance with
Table 1809.7; or
2.3. The structural design of the footing is based
on a specified compressive strength, / \, no
greater than 2,500 pounds per square inch
(psi) (17.2 MPa), regardless of the compres-
sive strength specified in the construction
documents or used in the footing construction.
3. Nonstructural concrete slabs supported directly on
the ground, including prestressed slabs on grade,
where the effective prestress in the concrete is less
than 150 psi (1.03 MPa).
4. Concrete foundation walls constructed in accordance
with Table 1807.1.6.2.
5. Concrete patios, driveways and sidewalks, on grade.
TABLE 1704.4
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
IBC REFERENCE
1. Inspection of reinforcing steel, including
prestressing tendons, and placement.
—
X
ACI 318: 3.5, 7.1-7.7
1913.4
2. Inspection of reinforcing steel welding in
accordance with Table 1704.3, Item 5b.
—
—
AWSD1.4
ACI 318: 3.5.2
—
3. Inspection of bolts to be installed in concrete
prior to and during placement of concrete where
allowable loads have been increased or where
strength design is used.
X
—
ACI 318:
8.1.3,21.2.8
1911.5,
1912.1
4. Inspection of anchors installed in hardened
concrete.
—
X
ACI 318:
3.8.6,8.1.3,21.2.8
1912.1
5. Verifying use of required design mix.
—
X
ACI 318: Ch. 4, 5.2-5.4
1904.2.2, 1913.2,
1913.3
6. At the time fresh concrete is sampled to fabricate
specimens for strength tests, perform slump and
air content tests, and determine the temperature
of the concrete.
X
—
ASTMC172
ASTMC31
ACI 318: 5.6, 5.8
1913.10
7. Inspection of concrete and shotcrete placement
for proper application techniques.
X
—
ACI 318: 5.9, 5.10
1913.6, 1913.7, 1913.8
8. Inspection for maintenance of specified curing
temperature and techniques.
—
X
ACI 318: 5.11-5.13
1913.9
9. Inspection of prestressed concrete:
a. Application of prestressing forces.
b. Grouting of bonded prestressing tendons in
the seismic-force-resisting system.
X
X
—
ACI 318: 18.20
ACI 318: 18.18.4
—
10. Erection of precast concrete members.
—
X
ACI 318: Ch. 16
—
11. Verification of in-situ concrete strength, prior to
stressing of tendons in posttensioned concrete
and prior to removal of shores and forms from
beams and structural slabs.
—
X
ACI 318: 6.2
—
12. Inspect formwork for shape, location and
dimensions of the concrete member being
formed.
—
X
ACI 318: 6.1.1
—
For SI: 1 inch = 25.4 mm.
a. Where applicable, see also Section 1707.1, Special inspection for seismic resistance.
134
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
1704.4.1 Materials. In the absence of sufficient data or doc-
umentation providing evidence of conformance to quality
standards for materials in Chapter 3 of ACI 318, the build-
ing official shall require testing of materials in accordance
with the appropriate standards and criteria for the material
in Chapter 3 of ACI 318. Weldability of reinforcement,
except that which conforms to ASTM A 706, shall be
determined in accordance with the requirements of Section
3.5.2 of ACI 318.
1704.5 Masonry construction. Masonry construction shall be
inspected and verified in accordance with the requirements of
Sections 1704.5.1 through 1704.5.3, depending on the occu-
pancy category of the building or structure.
Exception: Special inspections shall not be required for:
1. Empirically designed masonry, glass unit masonry or
masonry veneer designed by Section 2109, 2110 or
Chapter 14, respectively, or by Chapter 5, 6 or 7 of
TMS 402/ACI 530/ASCE 5, respectively, when they
are part of structures classified as Occupancy Cate-
gory I, II or in in accordance with Section 1604.5.
2. Masonry foundation walls constructed in accordance
with Table 1807.1.6.3(1), 1807.1.6.3(2),
1807.1.6.3(3) or 1807.1.6.3(4).
3. Masonry fireplaces, masonry heaters or masonry
chimneys installed or constructed in accordance with
Section 2111, 2112 or 2113, respectively.
1704.5.1 Empirically designed masonry, glass unit
masonry and masonry veneer in Occupancy Category
IV. The minimum special inspection program for empirically
designed masonry, glass unit masonry or masonry veneer
designed by Section 2109, 21 10 or Chapter 14, respectively,
or by Chapter 5, 6 or 7 of TMS 402/ACI 530/ASCE 5, respec-
tively, in structures classified as Occupancy Category IV, in
accordance with Section 1604.5, shall comply with Table
1704.5.1.
1704.5.2 Engineered masonry in Occupancy Category I,
n or III. The minimum special inspection program for
masonry designed by Section 2107 or 2108 or by chapters
other than Chapter 5, 6 or 7 of TMS 402/ACI 530/ASCE 5 in
structures classified as Occupancy Category I, II or III, in
accordance with Section 1604.5, shall comply with Table
1704.5.1.
1704.5.3 Engineered masonry in Occupancy Category
IV. The minimum special inspection program for masonry
designed by Section 2107 or 2108 or by chapters other than
Chapter 5, 6 or 7 of TMS 402/ACI 530/ASCE 5 in structures
classified as Occupancy Category IV, in accordance with
Section 1604.5, shall comply with Table 1704.5.3.
1704.6 Wood construction. Special inspections of the fabrica-
tion process of prefabricated wood structural elements and
assemblies shall be in accordance with Section 1704.2. Special
inspections of site-built assemblies shall be in accordance with
this section.
1704.6.1 High-load diaphragms. High-load diaphragms
designed in accordance with Table 2306.2.1(2) shall be
installed with special inspections as indicated in Section
1704.1. The special inspector shall inspect the wood struc-
tural panel sheathing to ascertain whetiier it is of the grade
and thickness shown on the approved building plans. Addi-
tionally, the special inspector must verify the nominal size
of framing members at adjoining panel edges, the nail or sta-
ple diameter and length, the number of fastener lines and
that the spacing between fasteners in each line and at edge
margins agrees with the approved building plans.
1704.6.2 Metal-plate-connected wood trusses spanning
60 feet or greater. Where a truss clear span is 60 feet (18
288 nmi) or greater, the special inspector shall verify that the
temporary installation restraint/bracing and the permanent
individual truss member restraint/bracing are installed in
accordance with the approved truss submittal package.
1704.6.2 Manufactured trusses and assemblies. [OSHPD
2] The fabrication of trusses and other assemblages con-
structed using wood and metal members, or using light
metal plate connectors, shall be continuously inspected by a
qualified inspector approved by the enforcement agency.
The inspector shall furnish the architect, structural engi-
neer and the enforcement agency with a report that the lum-
ber species, grades and moisture content; type of glue,
temperature and gluing procedure; type of metal members
and metal plate connectors; and the workmanship conform
in every material respect with the duly approved plans and
specifications. Each inspected truss shall be stamped by the
inspector with an identifying mark.
1704.7 Soils. Special inspections for existing site soil condi-
tions, fill placement and load-bearing requirements shall be as
required by this section and Table 1704.7. The approved
geotechnical report, and the construction documents prepared
by the registered design professionals shall be used to deter-
mine compliance. During fill placement, the special inspector
shall determine that proper materials and procedures are used
in accordance with the provisions of the approved geotechnical
report.
Exception: Where Section 1803 does not require reporting
of materials and procedures for fill placement, the special
inspector shall verify that the in-place dry density of the
compacted fill is not less than 90 percent of the maximum
dry density at optimum moisture content determined in
accordance with ASTM D 1557.
1704.8 Driven deep foundations. Special inspections shall be
performed during installation and testing of driven deep foun-
dation elements as required by Table 1704.8. The approved
geotechnical report, and the construction documents prepared
by the registered design professionals, shall be used to deter-
mine compliance.
1704.9 Cast-in-place deep foundations. Special inspections
shall be performed during installation and testing of
cast-in-place deep foundation elements as required by Table
1704.9. The approved geotechnical report, and the construc-
tion documents prepared by the registered design profession-
als, shall be used to determine compliance.
2010 CALIFORNIA BUILDING CODE
135
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704.5.1
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
VERIFICATION AND INSPECTION
FREQUENCY OF INSPECTION
REFERENCE FOR CRITERIA
CONTINUOUS
PERIODIC
IBC SECTION
TMS 402/ACI
530/ASCE 5«
TMS 602/ACI
530.1/ASCE 6^
1. Compliance with required inspection pro-
visions of the construction documents and
the approved submittals shall be verified.
X
—
—
Art. 1.5
2. Verification of/^ saidf^^ prior to con-
struction except where specifically
exempted by this code.
-~
X
—
—
Art. 1.4B
3. Verification of slump flow and VSI as
delivered to the site for self-consolidating
grout.
X
~
—
—
Art. 1.5B.l.b.3
4. As masonry construction begins, the following shall be verified to ensure compliance:
a. Proportions of site-prepared mortar.
—
X
—
—
Art. 2.6A
b. Construction of mortar joints.
—
X
—
—
Art. 3.3B
c. Location of reinforcement,
connectors, prestressing tendons
and anchorages.
—
X
—
—
Art. 3.4, 3.6A
d. Prestressing technique.
—
X
—
—
Art. 3.6B
e. Grade and size of prestressing
tendons and anchorages.
—
X
-~
—
Art. 2.4B, 2.4H
5. During construction the inspection program shall verify:
a. Size and location of structural
elements.
—
X
—
—
Art. 3.3F
b. Type, size and location of anchors,
including other details of anchorage
of masonry to structural members,
frames or other construction.
—
X
—
Sec. 1.2.2(e),
1.16.1
—
c. Specified size, grade and type of
reinforcement, anchor bolts,
prestressing tendons and
anchorages.
—
X
—
Sec. 1.15
Art. 2.4, 3.4
d. Welding of reinforcing bars.
X
—
—
Sec. 2.1.9.7.2,
3.3.3.4(b)
—
e. Preparation, construction and
protection of masonry during cold
weather (temperature below 40°F)
or hot weather (temperature above
90°F).
—
X
Sec. 2104.3,
2104.4
Art. 1.8C,
1.8D
f. Application and measurement of
prestressing force.
X
—
—
~
Art. 3.6B
(continued)
136
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
•^
TABLE 1704.5.1— continued
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
VERIFICATION AND INSPECTION
FREQUENCY OF INSPECTION
REFERENCE FOR CRITERIA
CONTINUOUS
PERIODIC
IBC SECTION
TMS 402/ACI
530/ASCE 5^
TMS 602/ACI
530.1/ASCE 6^
6. Prior to grouting, the following shall be verified to ensure compliance:
a. Grout space is clean.
—
X
—
—
Art. 3.2D
b. Placement of reinforcement and
connectors, and prestressing
tendons and anchorages.
—
X
—
Sec. 1.13
Art. 3.4
c. Proportions of site-prepared grout
and prestressing grout for bonded
tendons.
—
X
—
—
Art. 2.6B
d. Construction of mortar joints.
—
X
—
—
Art. 3.3B
7. Grout placement shall be verified to
ensure compliance:
X
—
—
—
Art. 3.5
a. Grouting of prestressing bonded
tendons.
X
—
—
—
Art. 3.6C
8. Preparation of any required grout speci-
mens, mortar specimens and/or prisms
shall be observed.
—
X
Sec. 2105.2.2,
2105.3
—
Art. 1.4
For SI: °C = [fF) - 32]/1.8.
a. The specific standards referenced are those listed in Chapter 35.
2010 CALIFORNIA BUILDING CODE
137
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704.5.3
LEVEL 2 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCE FOR CRITERIA
IBC SECTION
TMS 402/ACI
530/ASCE 5^
TMS 602/ACI
530.1 /ASCE 6^
1 . Compliance with required inspection provi-
sions of the construction documents and the
approved submittals.
—
X
—
—
Art. 1.5
2. Verification of /^ and/^^ prior to construc-
tion and for every 5,000 square feet during
construction.
—
X
—
—
Art. 1.4B
3. Verification of proportions of materials in
premixed or preblended mortar and grout as
delivered to the site.
—
X
—
—
Art. 1.5B
4. Verification of slump flow and VSI as deliv-
ered to the site for self-consolidating grout.
X
—
—
—
Art. 1.5B.l.b.3
5. The following shall be verified to ensure compliance:
a. Proportions of site-prepared mortar,
grout and prestressing grout for bonded
tendons.
—
X
—
—
Art. 2.6A
b. Placement of masonry units and
construction of mortar joints.
—
X
—
Art. 3.3B
c. Placement of reinforcement, connectors
and prestressing tendons and
anchorages.
—
X
Sec. 1.15
Art. 3.4, 3.6A
d. Grout space prior to grout.
X
—
—
—
Art. 3.2D
e. Placement of grout.
X
—
—
—
Art. 3.5
f. Placement of prestressing grout.
X
—
—
—
Art. 3.6C
g. Size and location of structural elements.
—
X
—
—
Art. 3.3F
h. Type, size and location of anchors,
including other details of anchorage of
masonry to structural members, frames
or other construction.
X
—
—
Sec. 1.2.2(e),
1.16.1
—
i. Specified size, grade and type of
reinforcement, anchor bolts,
prestressing tendons and anchorages.
X
—
Sec. 1.15
Art. 2.4,^3.4
j. Welding of reinforcing bars.
X
—
— .
Sec. 2.1.9.7.2,
3.3.3.4(b)
/ —
k. Preparation, construction and protection
of masonry during cold weather
(temperature below 40°F) or hot
weather (temperature above 90°F).
—
X
Sec. 2104.3,
2104.4
/
Art. 1.8C, 1.8D
1. Application and measurement of
prestressing force.
X
—
—
— ;
Art. 3.6B
6. Preparation of any required grout specimens
and/or prisms shall be observed.
X
—
Sec. 2105.2.2,
2105.3
—
Art. 1.4
For SI: °C = [(°F) - 32]/l .8, 1 square foot = 0.0929 ml
a. The specific standards referenced are those listed in Chapter 35.
138
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704.7
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1. Verify materials below shallow foundations are adequate to
achieve the design bearing capacity.
—
X
2. Verify excavations are extended to proper depth and have
reached proper material.
—
X
3. Perform classification and testing of compacted fill
materials.
—
X
4. Verify use of proper materials, densities and lift thicknesses
during placement and compaction of compacted fill.
X
—
5 . Prior to placement of compacted fill, observe subgrade and
verify that site has been prepared properly.
—
X
TABLE 1704.8
REQUIRED VERIFICATION AND INSPECTION OF DRIVEN DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1 . Verify element materials, sizes and lengths comply with the
requirements.
X
—
2. Determine capacities of test elements and conduct additional
load tests, as required.
X
—
3. Observe driving operations and maintain complete and
accurate records for each element.
X
—
4. Verify placement locations and plumbness, confirm type and
size of hammer, record number of blows per foot of
penetration, determine required penetrations to achieve design
capacity, record tip and butt elevations and document
any damage to foundation element.
X
—
5. For steel elements, perform additional inspections in
accordance with Section 1704.3.
—
—
6. For concrete elements and concrete-filled elements, perform
additional inspections in accordance with Section 1704.4.
—
—
7. For specialty elements, perform additional inspections as
determined by the registered design professional in
responsible charge.
—
—
TABLE 1704.9
REQUIRED VERIFICATION AND INSPECTION OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1. Observe drilling operations and maintain complete and
accurate records for each element.
X
—
2. Verify placement locations and plumbness, confirm element
diameters, bell diameters (if applicable), lengths, embedment
into bedrock (if applicable) and adequate end-bearing strata
capacity. Record concrete or grout volumes.
X
—
3. For concrete elements, perform additional inspections in
accordance with Section 1704.4.
~
—
2010 CALIFORNIA BUILDING CODE
139
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
1704.10 Helical pile foundations. Special inspections shall be
performed continuously during installation of helical pile
foundations. The information recorded shall include installa-
tion equipment used, pile dimensions, tip elevations, final
depth, final installation torque and other pertinent installation
data as required by the registered design professional in
responsible charge. The approved geotechnical report and the
construction documents prepared by the registered design pro-
fessional shall be used to determine compliance.
1704.11 Vertical masonry foundation elements. Special
inspection shall be performed in accordance with Section
1704.5 for vertical masonry foundation elements.
1704.12 Sprayed fire-resistant materials. Special inspec-
tions for sprayed fire-resistant materials applied to floor, roof
and wall assemblies and structural members shall be in accor-
dance with Sections 1704.12.1 through 1704.12.6. Special
inspections shall be based on the fire-resistance design as des-
ignated in the approved construction documents. The tests set
forth in this section shall be based on samplings from specific
floor, roof and wall assemblies and structural members. Spe-
cial inspections shall be performed after the rough installation
of electrical, automatic sprinkler, mechanical and plumbing
systems and suspension systems for ceilings, where applicable.
1704.12.1 Physical and visual tests. The special inspec-
tions shall include the following tests and observations to
demonstrate compliance with the listing and the fire-resis-
tance rating:
1. Condition of substrates.
2. Thickness of application.
3. Density in pounds per cubic foot (kg/m^),
4. Bond strength adhesion/cohesion.
5. Condition of finished application.
1704.12.2 Structural member surface conditions. The
surfaces shall be prepared in accordance with the approved
fire-resistance design and the written instructions of
approved manufacturers. The prepared surface of structural
members to be sprayed shall be inspected before the appli-
cation of the sprayed fire-resistant material.
1704.12.3 Application. The substrate shall have a mini-
mum ambient temperature before and after application as
specified in the written instructions of approved manufac-
turers. The area for application shall be ventilated during
and after application as required by the written instructions
of approved manufacturers.
1704.12.4 Thickness. No more than 10 percent of the thick-
ness measurements of the sprayed fire-resistant materials
applied to floor, roof and wall assemblies and structural
members shall be less than the thickness required by the
approved fire-resistance design, but in no case less than the
minimum allowable thickness required by Section
1704.12.4,1.
1704.12.4.1 Minimum allowable thickness. For design
thicknesses 1 inch (25 mm) or greater, the minimum
allowable individual thickness shall be the design thick-
ness minus V4 inch (6.4 nun). For design thicknesses less
than 1 inch (25 mm), the minimum allowable individual
thickness shall be the design thickness minus 25 percent.
Thickness shall be determined in accordance with
ASTM E 605. Samples of the sprayed fire-resistant
materials shall be selected in accordance with Sections
1704.12.4.2 and 1704.12.4.3.
1704.12.4.2 Floor, roof and wall assemblies. The thick-
ness of the sprayed fire-resistant material applied to
floor, roof and wall assemblies shall be determined in
accordance with ASTM E 605, making not less than four
measurements for each 1,000 square feet (93 m^) of the
sprayed area in each story or portion thereof.
1704.12.4.2.1 Cellular decks. Thickness measure-
ments shall be selected from a square area, 12 inches
by 12 inches (305 mm by 305 mm) in size. A mini-
mum of four measurements shall be made, located
symmetrically within the square area.
1704.12.4.2.2 Fluted decks. Thickness measure-
ments shall be selected from a square area, 12 inches
by 12 inches (305 mm by 305 mm) in size. A mini-
mum of four measurements shall be made, located
symmetrically within the square area, including one
each of the following: valley, crest and sides. The
average of the measurements shall be reported.
1704.12.4.3 Structural members. The thickness of the
sprayed fire-resistant material applied to structural mem-
bers shall be determined in accordance with ASTM E
605. Thickness testing shall be performed on not less
than 25 percent of the structural members on each floor.
1704.12.4.3.1 Beams and girders. At beams and
girders thickness measurements shall be made at nine
locations around the beam or girder at each end of a
12-inch (305 mm) length.
1704.12.4.3.2 Joists and trusses. At joists and
trusses, thickness measurements shall be made at
seven locations around the joist or truss at each end of
a 12-inch (305 mm) length.
1704.12.4.3.3 Wide-flanged columns. At wide-
flanged columns, thickness measurements shall be
made at 12 locations around the colunm at each end of
a 12-inch (305 mm) length.
1704.12.4.3.4 Hollow structural section and pipe
columns. At hollow structural section and pipe col-
umns, thickness measurements shall be made at a
minimum of four locations around the column at each
end of a 12-inch (305 mm) length.
1704.12.5 Density. The density of the sprayed fire-resistant
material shall not be less than the density specified in the
approved fire-resistance design. Density of the sprayed
fire-resistant material shall be determined in accordance
with ASTM E 605. The test samples for determining the
density of the sprayed fire-resistant materials shall be
selected as follows:
1 . From each floor, roof and wall assembly at the rate of
not less than one sample for every 2,500 square feet
(232 m^) or portion thereof of the sprayed area in each
story.
140
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
2. From beams, girders, trusses and columns at the rate
of not less than one sample for each type of structural
member for each 2,500 square feet (232 m^) of floor
area or portion thereof in each story.
1704.12.6 Bond strength. The cohesive/adhesive bond
strength of the cured sprayed fire-resistant material applied
to floor, roof and wall assemblies and structural members
shall not be less than 150 pounds per square foot (psf) (7.18
kN/m^). The cohesive/adhesive bond strength shall be deter-
mined in accordance with the field test specified in ASTM E
736 by testing in-place samples of the sprayed fire-resistant
material selected in accordance with Sections 1704.12.6.1
through 1704.12.6.3.
1704.12.6.1 Floor, roof and wall assemblies. The test
samples for determining the cohesive/adhesive bond
strength of the sprayed fire-resistant materials shall be
selected from each floor, roof and wall assembly at the
rate of not less than one sample for every 2,500 square
feet (232 m^) of the sprayed area in each story or portion
thereof.
1704.12.6.2 Structural members. The test samples for
determining the cohesive/adhesive bond strength of the
sprayed fire-resistant materials shall be selected from
beams, girders, trusses, columns and other structural
members at the rate of not less than one sample for each
type of structural member for each 2,500 square feet
(232 m^) of floor area or portion thereof in each story,
1704.12.6.3 Primer, paint and eneapsulant bond tests.
Bond tests to qualify a primer, paint or eneapsulant shall
be conducted when the sprayed fire-resistant material is
applied to a primed, painted or encapsulated surface for
which acceptable bond-strength performance between
these coatings and the fire-resistant material has not been
determined. A bonding agent approved by the SFRM
manufacturer shall be applied to a primed, painted or
encapsulated surface where the bond strengths are found
to be less than required values.
1704.13 Mastic and intumescent fire-resistant coatings.
Special inspections for mastic and intumescent fire-resistant
coatings applied to structural elements and decks shall be in
accordance with AWCI 12-B. Special inspections shall be
based on the fire-resistance design as designated in the
approved construction documents.
1704.14 Exterior insulation and finish systems (EIFS). Spe~
cial inspections shall be required for all EIFS applications.
Exceptions:
1. Special inspections shall not be required for EIFS
applications installed over a water-resistive harrier
with a means of draining moisture to the exterior.
2. Special inspections shall not be required for EIFS
applications installed over masonry or concrete walls.
1704.14.1 Water-resistive barrier coating. A water-resis-
tive barrier cosd-ing complying with ASTM E 2570 requires
special inspection of the water-resistive barrier coating
when installed over a sheathing substrate.
1704.15 Special cases. Special inspections shall be required
for proposed work that is, in the opinion of the building official,
unusual in its nature, such as, but not limited to, the following
examples:
1 . Construction materials and systems that are alternatives
to materials and systems prescribed by this code.
2. Unusual design applications of materials described in
this code.
3. Materials and systems required to be installed in accor-
dance with additional manufacturer's instructions that
prescribe requirements not contained in this code or in
standards referenced by this code.
[F] 1704.16 Special inspection for smoke control. Smoke
control systems shall be tested by a special inspector.
[F] 1704.16.1 Testing scope. The test scope shall be as fol-
lows:
1 . During erection of ductwork and prior to concealment
for the purposes of leakage testing and recording of
device location.
2. Prior to occupancy and after sufficient completion for
the purposes of pressure difference testing, flow mea-
surements and detection and control verification.
[F] 1704.16.2 Qualifications. Special inspection agencies
for smoke control shall have expertise in fire protection
engineering, mechanical engineering and certification as air
balancers.
SECTION 1705
STATEMENT OF SPECIAL INSPECTIONS
1705.1 General. Where special inspection or testing is
required by Section 1704, 1707 or 1708, the registered design
professional in responsible charge shall prepare a statement of
special inspections in accordance with Section 1705 for
submittal by the applicant (see Section 1704.1.1).
1705.2 Content of statement of special inspections. The
statement of special inspections shall identify the following:
1. The materials, systems, components and work required
to have special inspection or testing by the building offi-
cial or by the registered design professional responsible
for each portion of the work.
2. The type and extent of each special inspection.
3. The type and extent of each test.
4. Additional requirements for special inspection or testing
for seismic or wind resistance as specified in Section
1705.3, 1705.4, 1707 or 1708.
5. For each type of special inspection, identification as to
whether it will be continuous special inspection or peri-
odic special inspection.
1705.3 Seismic resistance. The statement of special inspec-
tions shall include seismic requirements for cases covered in
Sections 1705.3.1 through 1705.3.5.
Exception: Seismic requirements are permitted to be
excluded from the statement of special inspections for struc-
2010 CALIFORNIA BUILDING CODE
141
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
tures designed and constructed in accordance with the fol-
lowing:
1 . The structure consists of light-frame construction; the
design spectral response acceleration at short periods,
5^,5, as determined in Section 1613.5.4, does not
exceed 0.5g; and the height of the structure does not
exceed 35 feet (10 668 mm) above grade plane; or
2. The structure is constructed using a reinforced
masonry structural system or reinforced concrete
structural system; the design spectral response accel-
eration at short periods, Sj^s, as determined in Section
1613.5.4, does not exceed 0.5g, and the height of the
structure does not exceed 25 feet (7620 mm) above
grade plane; or
3 . Detached one- or two-family dwellings not exceeding
two stories above grade plane, provided the structure
does not have any of the following plan or vertical
irregularities in accordance with Section 12.3.2 of
ASCE 7:
3.1. Torsional irregularity.
3.2. Nonparallel systems.
3.3. Stiffness irregularity — extreme soft story and
soft story.
3.4. Discontinuity in capacity — weak story.
1705.3.1 Seismic-force-resisting systems. The seismic-
force-resisting systems in structures assigned to Seismic
Design Category C, D, E or F, in accordance with Section
1613.
Exception: Requirements for the seismic-force-resist-
ing system are permitted to be excluded from the state-
ment of special inspections for steel systems in structures
assigned to Seismic Design Category C that are not spe-
cifically detailed for seismic resistance, with a response
modification coefficient, R, of 3 or less, excluding canti-
lever colunm systems.
1705.3.2 Designated seismic systems. Designated seismic
systems in structures assigned to Seismic Design Category
D, E or F.
1705.3.3 Seismic Design Category C. The following addi-
tional systems and components in structures assigned to
Seismic Design Category C:
1. Heating, ventilating and air-conditioning (HVAC)
ductwork containing hazardous materials and
anchorage of such ductwork.
2. Piping systems and mechanical units containing
flammable, combustible or highly toxic materials.
3. Anchorage of electrical equipment used for emer-
gency or standby power systems.
1705.3.4 Seismic Design Category D. The following addi-
tional systems and components in structures assigned to
Seismic Design Category D:
1. Systems required for Seismic Design Category C.
2. Exterior wall panels and their anchorage.
3. Suspended ceiling systems and their anchorage.
4. Access floors and their anchorage.
5. Steel storage racks and their anchorage, where the
importance factor is equal to 1.5 in accordance with
Section 15.5.3 of ASCE 7.
1705.3.5 Seismic Design Category E or F. The following
additional systems and components in structures assigned
to Seismic Design Category E or F:
1. Systems required for Seismic Design Categories C
andD.
2. Electrical equipment.
1705.3.6 Seismic requirements in the statement of spe-
cial inspections. When Sections 1705.3 through 1705.3.5
specify that seismic requirements be included, the statement
of special inspections shall identify the following:
1. The designated seismic systems and seismic-
force-resisting systems that are subject to special
inspections in accordance with Sections 1705.3
through 1705.3.5.
2. The additional special inspections and testing to be
provided as required by Sections 1707 and 1708 and
other applicable sections of this code, including the
applicable standards referenced by this code.
1705.4 Wind resistance. The statement of special inspections
shall include wind requirements for structures constructed in
the following areas:
1. In wind Exposure Category B, where the 3-second-gust
basic wind speed is 120 miles per hour (mph) (52.8 m/s) or
greater.
2. In wind Exposure Category C or D, where the 3-second-
gust basic wind speed is 1 10 mph (49 m/s) or greater.
1705.4.1 Wind requirements in the statement of special
inspections. When Section 1705.4 specifies that wind
requirements be included, the statement of special inspec-
tions shall identify the main wind-force-resisting systems
and wind-resisting components subject to special inspec-
tions as specified in Section 1705.4.2.
1705.4.2 Detailed requirements. The statement of special
inspections shall include at least the following systems and
components:
1 . Roof cladding and roof framing connections.
2. Wall connections to roof and floor diaphragms and
framing.
3. Roof and floor diaphragm systems, including collec-
tors, drag struts and boundary elements.
4. Vertical wind-force-resisting systems, including
braced frames, moment frames and shear walls.
5. Wind-force-resisting system connections to the foun-
dation.
142
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
6. Fabrication and installation of systems or compo-
nents required to meet the impact-resistance require-
ments of Section 1609.1.2.
or
Exception: Fabrication of manufactured systems ui
components that have a label indicating compliance with
the wind-load and impact-resistance requirements of this
code.
SECTION 1706
SPECIAL INSPECTIONS FOR
WIND REQUIREMENTS
1706.1 Special inspections for wind requirements. Special
inspections itemized in Sections 1706,2 through 1706.4, unless
exempted by the exceptions to Section 1704. 1, are required for
buildings and structures constructed in the following areas:
1. In wind Exposure Category B, where the 3-second-gust
basic wind speed is 120 miles per hour (52.8 m/sec) or
greater.
2. In wind Exposure Categories C or D, where the 3-sec-
ond-gust basic wind speed is 110 mph (49 m/sec) or
greater.
1706.2 Structural wood. Continuous special inspection is
required during field gluing operations of elements of the main
windforce-resisting system. Periodic special inspection is
required for nailing, bolting, anchoring and other fastening of
components within the main windforce-resisting system,
including wood shear walls, wood diaphragms, drag struts,
braces and hold-downs.
Exception: Special inspection is not required for wood
shear walls, shear panels and diaphragms, including nailing,
bolting, anchoring and other fastening to other components
of the main windforce-resisting system, where the fastener
spacing of the sheathing is more than 4 inches (102 mm) on
center.
1706.3 Cold-formed steel light-frame construction. Peri-
odic special inspection is required during welding operations
of elements of the main windforce-resisting system. Periodic
special inspection is required for screw attachment, bolting,
anchoring and other fastening of components within the main
windforce-resisting system, including shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs.
Exception: Special inspection is not required for
cold-formed steel light-frame shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs where
either of the following apply:
1 . The sheathing is gypsum board or fiberboard.
2. The sheathing is wood structural panel or steel sheets
on only one side of the shear wall, shear panel or dia-
phragm assembly and the fastener spacing of the
sheathing is more than 4 inches (102 mm) on center
(o.c).
1706.4 Wind-resisting components. Periodic special inspec-
tion is required for the following systems and components:
1. Roof cladding.
2. Wall cladding.
SECTION 1707
SPECIAL INSPECTIONS FOR
SEISMIC RESISTANCE
1707.1 Special inspections for seismic resistance. Special
inspections itemized in Sections 1707.2 through 1707.9, unless
exempted by the exceptions of Section 1704.1, 1705.3, or
1705.3.1, are required for the following:
1. The seismic-force-resisting systems in structures
assigned to Seismic Design Category C, D, E or F, as
determined in Section 1613.
2. Designated seismic systems in structures assigned to
Seismic Design Category D, E or F.
3. Architectural, mechanical and electrical components in
structures assigned to Seismic Design Category C, D, E
or F that are required in Sections 1707.6 and 1707.7.
1707.2 Structural steel. Special inspection for structural steel
shall be in accordance with the quality assurance plan require-
ments of AISC 341.
Exceptions:
1. Special inspections of structural steel in structures
assigned to Seismic Design Category C that are not
specifically detailed for seismic resistance, with a
response modification coefficient, R, of 3 or less,
excluding cantilever column systems.
2. For ordinary moment frames, ultrasonic and mag-
netic particle testing of complete joint penetration
groove welds are only required for demand critical
welds.
1707.3 Structural wood. Continuous special inspection is
required during field gluing operations of elements of the seis-
mic-force-resisting system. Periodic special inspection is
required for naiUng, bolting, anchoring and other fastening of
components within the seismic-force-resisting system, includ-
ing wood shear walls, wood diaphragms, drag struts, braces,
shear panels and hold-downs.
Exception: Special inspection is not required for wood
shear walls, shear panels and diaphragms, including nailing,
bolting, anchoring and other fastening to other components
of the seismic-force-resisting system, where the fastener
spacing of the sheathing is more than 4 inches (102 mm) on
center (o.c).
1707.4 Cold-formed steel light-frame construction. Peri-
odic special inspection is required during welding operations
of elements of the seismic-force-resisting system. Periodic
special inspection is required for screw attachment, bolting,
anchoring and other fastening of components within the seis-
2010 CALIFORNIA BUILDING CODE
143
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
mic-force-resisting system, including shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs.
Exception: Special inspection is not required for
cold-formed steel light-frame shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs where
either of the following apply:
1. The sheathing is gypsum board or fiberboard.
2. The sheathing is wood structural panel or steel sheets
on only one side of the shear wall, shear panel or dia-
phragm assembly and the fastener spacing of the
sheathing is more than 4 inches (102 mm) o.c.
1707.5 Storage racks and access floors. Periodic special
inspection is required during the anchorage of access floors
and storage racks 8 feet (2438 mm) or greater in height in struc-
tures assigned to Seismic Design Category D, E or F.
1707.6 Architectural components. Periodic special inspec-
tion during the erection and fastening of exterior cladding, inte-
rior and exterior nonbearing walls and interior and exterior
veneer in structures assigned to Seismic Design Category D, E
or K
Exceptions:
1. Special inspection is not required for exterior clad-
ding, interior and exterior nonbearing walls and inte-
rior and exterior veneer 30 feet (9144 mm) or less in
height above grade or walking surface.
2. Special inspection is not required for exterior clad-
ding and interior and exterior veneer weighing 5 psf
(24.5 N/m^) or less.
3. Special inspection is not required for interior
nonbearing walls weighing 15 psf (73.5 N/m^) or less.
1707.7 Mechanical and electrical components. Special
inspection for mechanical and electrical equipment shall be as
follows:
1 . Periodic special inspection is required during the anchor-
age of electrical equipment for emergency or standby
power systems in structures assigned to Seismic Design
Category C, D, E or F;
2. Periodic special inspection is required during the instal-
lation of anchorage of other electrical equipment in
structures assigned to Seismic Design Category E or F;
3 . Periodic special inspection is required during installation
of piping systems intended to carry flammable, combus-
tible or highly toxic contents and their associated
mechanical units in structures assigned to Seismic
Design Category C, D, E or F;
4. Periodic special inspection is required during the instal-
lation of HVAC ductwork that will contain hazardous
materials in structures assigned to Seismic Design Cate-
gory C, D, E or F; and
5. Periodic special inspection is required during the instal-
lation of vibration isolation systems in structures
assigned to Seismic Design Category C, D, E or F where
the construction documents require a nominal clearance
of V4 inch (6.4 mm) or less between the equipment sup-
port frame and restraint.
1707.8 Designated seismic system verifications. The special
inspector shall examine designated seismic systems requiring
seismic qualification in accordance with Section 1708.4 and
verify that the label, anchorage or mounting conforms to the
certificate of compliance.
1707.9 Seismic isolation system. Periodic special inspection
is required during the fabrication and installation of isolator
units and energy dissipation devices that are part of the seismic
isolation system.
SECTION 1708
STRUCTURAL TESTING FOR
SEISMIC RESISTANCE
1708.1 Testing and qualification for seismic resistance. The
testing and quahfication specified in Sections 1708.2 through
1708.5, unless exempted from special inspections by the
exceptions of Section 1704.1, 1705.3 or 1705.3.1 are required
as follows:
1. The seismic-force-resisting systems in structures
assigned to Seismic Design Category C, D, E or F, as
determined in Section 1613 shall meet the requirements
of Sections 1708.2 and 1708.3, as applicable.
2. Designated seismic systems in structures assigned to
Seismic Design Category C, D, E or F subject to the spe-
cial certification requirements of ASCE 7 Section 13.2.2
are required to be tested in accordance with Section
1708.4.
3. Architectural, mechanical and electrical components in
structures assigned to Seismic Design Category C, D, E
or F with an /^ = 1 .0 are required to be tested in accor-
dance with Section 1708.4 where the general design
requirements of ASCE 7 Section 13.2.1, Item 2 for man-
ufacturer's certification are satisfied by testing.
4. The seismic isolation system in seismically isolated
structures shall meet the testing requirements of Section
1708.5.
1708.2 Concrete reinforcement. Where reinforcement com-
plying with ASTM A 615 is used to resist earthquake-induced
flexural and axial forces in special moment frames, special
structural walls and coupling beams connecting special struc-
tural walls, in structures assigned to Seismic Design Category
B, C, D, E or F as determined in Section 1613, the reinforce-
ment shall comply with Section 21.1.5.2 of ACI 318. Certified
mill test reports shall be provided for each shipment of such
reinforcement. Where reinforcement complying with ASTM
A 615 is to be welded, chemical tests shall be performed to
determine weldabihty in accordance with Section 3.5.2 of ACI
318.
1708.3 Structural steel. Testing for structural steel shall be in
accordance with the quality assurance plan requirements of
AISC341.
Exceptions:
1. Testing for structural steel in structures assigned to
Seismic Design Category C that are not specifically
detailed for seismic resistance, with a response modi-
144
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
fication coefficient, R, of 3 or less, excluding cantile-
ver column systems.
2. For ordinary moment frames, ultrasonic and mag-
netic particle testing of complete joint penetration
groove welds are only required for demand critical
welds.
1708.4 Seismic certification of nonstructural components.
The registered design professional shall state the applicable
seismic certification requirements for nonstructural compo-
nents and designated seismic systems on the construction doc-
uments.
1. The manufacturer of each designated seismic system
components subject to the provisions of ASCE 7 Section
13.2.2 shall test or analyze the component and its mount-
ing system or anchorage and submit a certificate of com-
pliance for review and acceptance by the registered
design professional responsible for the design of the des-
ignated seismic system and for approval by the building
official. Certification shall be based on an actual test on a
shake table, by three-dimensional shock tests, by an ana-
lytical method using dynamic characteristics and forces,
by the use of experience data (i.e., historical data demon-
strating acceptable seismic performance) or by more rig-
orous analysis providing for equivalent safety.
2. Manufacturer's certification of compliance for the gen-
eral design requirements of ASCE 7 Section 13.2. 1 shall
be based on analysis, testing or experience data.
1708.5 Seismically isolated structures. For required system
tests, see Section 17.8 of ASCE 7.
SECTION 1709
CONTRACTOR RESPONSIBILITY
1709,1 Contractor responsibility. Each contractor responsi-
ble for the construction of a main wind- or seismic-force-resist-
ing system, designated seismic system or a v^ind- or
seismic-resisting component listed in the statement of special
inspections shall submit a written statement of responsibility to
the building official and the owner prior to the commencement
of work on the system or component. The contractor's state-
ment of responsibility shall contain acknowledgement of
awareness of the special requirements contained in the state-
ment of special inspection.
SECTION 1710
STRUCTURAL OBSERVATIONS
1710.1 General. Where required by the provisions of Section
1710.2 or 1710.3, the owner shall employ a registered design
professional to perform structural observations as defined in
Section 1702.
Prior to the commencement of observations, the structural
observer shall submit to the building official a written state-
ment identifying the frequency and extent of structural obser-
vations.
At the conclusion of the work included in the permit, the
structural observer shall submit to the building official a written
statement that the site visits have been made and identify any
reported deficiencies which, to the best of the structural
observer's knowledge, have not been resolved.
1710.2 Structural observations for seismic resistance.
Structural observations shall be provided for those structures
assigned to Seismic Design Category D, E or F, as determined
in Section 1613, where one or more of the following conditions
exist:
1 . The structure is classified as Occupancy Category III or
IV in accordance with Table 1604.5.
2. The height of the structure is greater than 75 feet (22 860
mm) above the base.
3. The structure is assigned to Seismic Design Category E,
is classified as Occupancy Category I or II in accordance
with Table 1604.5, and is greater than two stories above
grade plane.
4. When so designated by the registered design profes-
sional responsible for the structural design.
5. When such observation is specifically required by the
building official.
1710.3 Structural observations for wind requirements.
Structural observations shall be provided for those structures
sited where the basic wind speed exceeds 110 mph (49 m/sec)
determined from Figure 1609, where one or more of the fol-
lowing conditions exist:
1. The structure is classified as Occupancy Category III or
IV in accordance with Table 1604.5.
2. The building height of the structure is greater than 75 feet
(22 860 mm).
3. When so designated by the registered design profes-
sional responsible for the structural design.
4. When such observation is specifically required by the
building official.
SECTION 1711
DESIGN STRENGTHS OF MATERIALS
1711.1 Conformance to standards. The design strengths and
permissible stresses of any structural material that are identi-
fied by a manufacturer's designation as to manufacture and
grade by mill tests, or the strength and stress grade is otherwise
confirmed to the satisfaction of the building official, shall con-
form to the specifications and methods of design of accepted
engineering practice or the approved rules in the absence of
applicable standards.
1711.2 New materials. For materials that are not specifically
provided for in this code, the design strengths and permissible
stresses shall be established by tests as provided for in Section
1712.
SECTION 1712
ALTERNATIVE TEST PROCEDURE
1712.1 General. In the absence of approved rules or other
approved standards, the building official shall make, or cause to
2010 CALIFORNIA BUILDING CODE
145
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
be made, the necessary tests and investigations; or the building
official shall accept duly authenticated reports from approved
agencies in respect to the quality and manner of use of new
materials or assemblies as provided for in Section 104.11,
Chapter 1, Division 11. The cost of all tests and other investiga-
tions required under the provisions of this code shall be borne
by the applicant.
[BSC] In the absence of approved rules or other approved
standards, the building official shall make, or cause to be
made, the necessary tests and investigations; or the building
official shall accept duly authenticated reports from
approved agencies in respect to the quality and manner of
use of new materials or assemblies as provided for in Sec-
tion 1,2.2, Chapter 1, Division L The cost of all tests and
other investigations required under the provisions of this
code shall be borne by the applicant.
SECTION 1713
TEST SAFE LOAD
1713.1 Where required. Where proposed construction is not
capable of being designed by approved engineering analysis,
or where proposed construction design method does not com-
ply with tiie applicable material design standard, the system of
construction or the structural unit and the connections shall be
subjected to the tests prescribed in Section 1715. The building
official shall accept certified reports of such tests conducted by
an approved testing agency, provided that such tests meet the
requirements of this code and approved procedures.
SECTION 1714
IN-SITU LOAD TESTS
1714.1 GeneraL Whenever there is a reasonable doubt as to the
stability or load-bearing capacity of a completed building,
structure or portion thereof for the expected loads, an engineer-
ing assessment shall be required. The engineering assessment
shall involve either a structural analysis or an in-situ load test,
or both. The structural analysis shall be based on actual mate-
rial properties and other as-built conditions that affect stability
or load-bearing capacity, and shall be conducted in accordance
with the appHcable design standard. If the structural assess-
ment determines that the load-bearing capacity is less than that
required by the code, load tests shall be conducted in accor-
dance with Section 1714.2. If the building, structure or portion
thereof is found to have inadequate stability or load-bearing
capacity for the expected loads, modifications to ensure struc-
tural adequacy or the removal of the inadequate construction
shall be required.
1714.2 Test standards. Structural components and assemblies
shall be tested in accordance with the appropriate material stan-
dards listed in Chapter 35. In the absence of a standard that con-
tains an applicable load test procedure, the test procedure shall
be developed by a registered design professional and approved.
The test procedure shall simulate loads and conditions of appli-
cation that the completed structure or portion thereof will be
subjected to in normal use.
1714.3 In-situ load tests. In-situ load tests shall be conducted
in accordance with Section 1714.3.1 or 1714. 3. 2 and shall be
supervised by a registered design professional. The test shall
simulate the applicable loading conditions specified in Chapter
16 as necessary to address the concerns regarding structural
stability of the building, structure or portion thereof.
1714.3.1 Load test procedure specified. Where a standard
listed in Chapter 35 contains an applicable load test proce-
dure and acceptance criteria, the test procedure and accep-
tance criteria in the standard shall apply. In the absence of
specific load factors or acceptance criteria, the load factors
and acceptance criteria in Section 1714.3.2 shall apply.
1714.3.2 Load test procedure not specified. In the absence
of applicable load test procedures contained within a stan-
dard referenced by this code or acceptance criteria for a spe-
cific material or method of construction, such existing
structure shall be subjected to a test procedure developed by
a registered design professional that simulates applicable
loading and deformation conditions. For components that
are not a part of the seismic-load-resisting system, the test
load shall be equal to two times the unfactored design loads.
The test load shall be left in place for a period of 24 hours.
The structure shall be considered to have successfully met
the test requirements where the following criteria are satis-
fied:
1 . Under the design load, the deflection shall not exceed
the limitations specified in Section 1604.3.
2. Within 24 hours after removal of the test load, the
structure shall have recovered not less than 75 percent
of the maximum deflection.
3. During and immediately after the test, the structure
shall not show evidence of failure.
SECTION 1715
PRECONSTRUCTION LOAD TESTS
1715.1 General. In evaluating the physical properties of mate-
rials and methods of construction that are not capable of being
designed by approved engineering analysis or do not comply
with applicable material design standards listed in Chapter 35,
the structural adequacy shall be predetermined based on the
load test criteria established in this section.
1715.2 Load test procedures specified. Where specific load
test procedures, load factors and acceptance criteria are
included in the applicable design standards listed in Chapter
35, such test procedures, load factors and acceptance criteria
shall apply. In the absence of specific test procedures, load fac-
tors or acceptance criteria, the corresponding provisions in
Section 1715.3 shall apply.
1715.3 Load test procedures not specified. Where load test
procedures are not specified in the applicable design standards
listed in Chapter 35, the load-bearing and deformation capacity
of structural components and assembUes shall be determined
on the basis of a test procedure developed by a registered
design professional that simulates appHcable loading and
deformation conditions. For components and assemblies that
are not a part of the seismic-force-resisting system, the test
shall be as specified in Section 1715.3.1. Load tests shall simu-
late the applicable loading conditions specified in Chapter 16.
146
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
1715.3.1 Test procedure. The test assembly shall be sub-
jected to an increasing superimposed load equal to not less
than two times the superimposed design load. The test load
shall be left in place for a period of 24 hours. The tested
assembly shall be considered to have successfully met the
test requirements if the assembly recovers not less than 75
percent of the maximum deflection within 24 hours after the
removal of the test load. The test assembly shall then be
reloaded and subjected to an increasing superimposed load
until either structural failure occurs or the superimposed
load is equal to two and one-half times the load at which the
deflection limitations specified in Section 1715.3.2 were
reached, or the load is equal to two and one-half times the
superimposed design load. In the case of structural compo-
nents and assemblies for which deflection limitations are
not specified in Section 17 15.3.2, the test specimen shall be
subjected to an increasing superimposed load until struc-
tural failure occurs or the load is equal to two and one-half
times the desired superimposed design load. The allowable
superimposed design load shall be taken as the lesser of:
1. The load at the deflection limitation given in Section
1715.3.2.
2. The failure load divided by 2.5.
3. The maximum load applied divided by 2.5.
1715.3.2 Deflection. The deflection of structural members
under the design load shall not exceed the limitations in Sec-
tion 1604.3.
1715.4 Wall and partition assemblies. Load-bearing wall
and partition assemblies shall sustain the test load both with
and without window framing. The test load shall include all
design load components. Wall and partition assemblies shall be
tested both with and without door and window framing.
1715.5 Exterior window and door assemblies. The design
pressure rating of exterior windows and doors in buildings
shall be determined in accordance with Section 1715.5.1 or
1715.5.2.
Exception: Structural wind load design pressures for win-
dow units smaller than the size tested in accordance with
Section 1715.5.1 or 1715.5.2 shall be permitted to be higher
than the design value of the tested unit provided such higher
pressures are determined by accepted engineering analysis.
All components of the small unit shall be the same as the
tested unit. Where such calculated design pressures are
used, they shall be validated by an additional test of the win-
dow unit having the highest allowable design pressure.
1715.5.1 Exterior windows and doors. Exterior windows
and sliding doors shall be tested and labeled as conforming
to AAMAAVDMA/CSA101/I.S.2/A440. The label shall
state the name of the manufacturer, the approved labeling
agency and the product designation as specified in AAMA/
WDMA/CSA101/I.S.2/A440. Exterior side-hinged doors
shall be tested and labeled as conforming to
AAMAAVDMA/CSA101/I.S.2/A440 or comply with Sec-
tion 1715.5.2. Products tested and labeled as conforming to
AAMAAVDMA/CSA 101/I.S.2/A440 shall not be subject
to the requirements of Sections 2403.2 and 2403.3.
1715.5.2 Exterior windows and door assemblies not pro-
vided for in Section 1715.5.1, Exterior window and door
assemblies shall be tested in accordance with ASTM E 330.
Structural performance of garage doors shall be determined
in accordance with either ASTM E 330 or ANSI/DASMA
108, and shall meet the acceptance criteria of ANSI/
DASMA 108. Exterior window and door assemblies con-
taining glass shall comply with Section 2403. The design
pressure for testing shall be calculated in accordance with
Chapter 16. Each assembly shall be tested for 10 seconds at
a load equal to 1.5 times the design pressure.
1715.6 Test specimens. Test specimens and construction shall
be representative of the materials, workmanship and details
normally used in practice. The properties of the materials used
to construct the test assembly shall be determined on the basis
of tests on samples taken from the load assembly or on repre-
sentative samples of the materials used to construct the load test
assembly. Required tests shall be conducted or witnessed by an
approved agency.
SECTION 1716
MATERIAL AND TEST STANDARDS
1716.1 Test standards for joist hangers and connectors.
1716.1.1 Test standards for joist hangers. The vertical
load-bearing capacity, torsional moment capacity and
deflection characteristics of joist hangers shall be deter-
mined in accordance with ASTM D 1761 using lumber hav-
ing a specific gravity of 0.49 or greater, but not greater than
0.55, as determined in accordance with AF&PA NDS for
the joist and headers.
Exception: The joist length shall not be required to
exceed 24 inches (610 mm).
1716.1.2 Vertical load capacity for joist hangers. The ver-
tical load capacity for the joist hanger shall be determined
by testing a minimum of three joist hanger assemblies as
specified in ASTM D 1761 . If the ultimate vertical load for
any one of the tests varies more than 20 percent from the
average ultimate vertical load, at least three additional tests
shall be conducted. The allowable vertical load of the joist
hanger shall be the lowest value determined from the fol-
lowing:
1 . The lowest ultimate vertical load for a single hanger
from any test divided by three (where three tests are
conducted and each ultimate vertical load does not
vary more than 20 percent from the average ultimate
vertical load).
2. The average ultimate vertical load for a single hanger
from all tests divided by three (where six or more tests
are conducted).
3. The average from all tests of the vertical loads that
produce a vertical movement of the joist with respect
to the header of Vg inch (3.2 mm).
2010 CALIFORNIA BUILDING CODE
147
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
4. The sum of the allowable design loads for nails or
other fasteners utilized to secure the joist hanger to the
wood members and allowable bearing loads that con-
tribute to the capacity of the hanger.
5. The allowable design load for the wood members
forming the connection.
1716.1.3 Torsional moment capacity for joist hangers.
The torsional moment capacity for the joist hanger shall be
determined by testing at least three joist hanger assemblies
as specified in ASTM D 1761. The allowable torsional
moment of the joist hanger shall be the average torsional
moment at which the lateral movement of the top or bottom
of the joist with respect to the original position of the joist is
Vg inch (3.2 mm).
1716.1.4 Design value modifications for joist hangers.
Allowable design values for joist hangers that are deter-
mined by Item 4 or 5 in Section 1716.1.2 shall be permitted
to be modified by the appropriate duration of loading factors
as specified in AF&PA NDS but shall not exceed the direct
loads as determined by Item 1, 2 or 3 in Section 1716.1.2.
Allowable design values determined by Item 1, 2 or 3 in
Section 1716.1.2 shall not be modified by duration of load-
ing factors.
1716.2 Concrete and clay roof tiles.
1716.2.1 Overturning resistance. Concrete and clay roof
tiles shall be tested to determine their resistance to overturn-
ing due to wind in accordance with SBCCI SSTD 1 1 and
Chapter 15.
1716.2.2 Wind tunnel testing. When roof tiles do not sat-
isfy the limitations in Chapter 1 6 for rigid tile, a wind tunnel
test shall be used to determine the wind characteristics of the
concrete or clay tile roof covering in accordance with
SBCCI SSTD 1 1 and Chapter 15.
148
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 17A - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
149
150 2010 CALIFORNIA BUILDING CODE
CHAPTER 174
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
SECTION 17014
GENERAL
170M.1 Scope. The provisions of this chapter shall govern the
quality, workmanship and requirements for materials covered.
Materials of construction and tests shall conform to the appli-
cable standards listed in this code.
17 01 A, LI Application, The scope of application of Chap-
ter 17 A is as follows:
L Structures regulated by the Division of the State
Architect — Structural Safety, which include those
applications listed in Sections 1.9.2 A (DSA-SS), and
1.9.2.2 (DSA-SS/CC). These applications include
public elementary and secondary schools, community
colleges and state-owned or state-leased essential
services buildings
2. Structures regulated by the Office of Statewide
Health Planning and Development (OSHPD), which
include those applications listed in Sections 1.10.1
and 1.10.4. These applications include hospitals,
skilled nursing facilities, intermediate care facilities
and correctional treatment centers.
Exception: [OSHPD 2] Single-story Type V skilled nurs-
ing or intermediate care facilities utilizing wood-frame
or light-steel-frame construction as defined in Health
and Safety Code Section 129725, which shall comply
with Chapter 17 and any applicable amendments
therein.
170IAJ,2 Amendments in this chapter. DSA-SS and
OSHPD adopt this chapter and all amendments.
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1 . Division of the State Architect - Structural Safety:
[DSA-SS] For applications listed in Section
L9.2.L
[DSA-SS/CC] For applications listed in Section
1.9.2.2.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD 1] For applications listed in Section
1.10.1.
[OSHPD 4] For applications listed in Section
1.10.4.
1701 AA. 3 Reference to other chapters.
1701 A JJ J [DSA-SS/CC] Where reference within this
chapter is made to sections in Chapters 16 A, 19 A, 21 A,
22A and 34A, the provisions in Chapters 16, 19, 21, 22
and 34 respectively shall apply instead.
1701A.2 New materials. New building materials, equipment,
appliances, systems or methods of construction not provided
for in this code, and any material of questioned suitability pro-
posed for use in the construction of a building or structure, shall
be subjected to the tests prescribed in this chapter and in the
approved rules to determine character, quality and limitations
of use.
170M.3 Used materials. The use of second-hand materials
that meet the minimum requirements of this code for new mate-
rials shall be permitted.
I701A,4 Special inspectors. [OSHPD 1 and 4] In addition to
the inspector(s) of record required by Title 24, Part 1, Section
7-144, the owner shall employ one or more special inspectors
who shall provide inspections during construction on the types
ofwork listed under Chapters 17A, 18A, 19A, 20, 21 A, 22A, 23,
25, 34A, and noted in the test, inspection and observation
(TIO) program required by Sections 7-141, 7-145 and 7-149 of
Title 24, Part 1, of the California Administrative Code. Test,
inspection and observation (TIO) program shall satisfy
requirements of Section 1704A.1.L
1701 A.5 Special inspectors. [DSA-SS & DSA-SS/CC] In
addition to the project inspector required by Title 24, Part 1,
Section 4-333, the owner shall employ one or more special
inspectors who shall provide inspections during construction
on the types ofwork listed under Chapters 17 A, ISA, 19 A, 20,
21 A, 22 A, 23, 25, 34 and noted in the special test, inspection
and observation plan required by Section 4-335 of Title 24,
Part 1, of the California Administrative Code.
SECTION 1702 A
DEFINITIONS
1702A.1 General. The following words and terms shall, for the
purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
APPROVED AGENCY. An established and recognized
agency regularly engaged in conducting tests or furnishing
inspection services, when such agency has been approved.
APPROVED FABRICATOR. An established and qualified
person, firm or corporation approved by the building official
pursuant to Chapter 17 of this code.
CERTIFICATE OF COMPLIANCE. A certificate stating
that materials and products meet specified standards or that
work was done in compliance with approved construction doc-
uments.
DESIGNATED SEISMIC SYSTEM. Those architectural,
electrical and mechanical systems and their components that
require design in accordance with Chapter 13 of ASCE 7 and
for which the component importance factor, 7^, is greater than 1
in accordance with Section 13.1.3 of ASCE 7.
2010 CALIFORNIA BUILDING CODE
151
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
FABRICATED ITEM. Structural, load-bearing or lateral
load-resisting assemblies consisting of materials assembled
prior to installation in a building or structure, or subjected to
operations such as heat treatment, thermal cutting, cold work-
ing or reforming after manufacture and prior to installation in a
building or structure. Materials produced in accordance with
standard specifications referenced by this code, such as rolled
structural steel shapes, steel-reinforcing bars, masonry units,
and wood structural panels or in accordance with a standard,
listed in Chapter 35, which provides requirements for quality
control done under the supervision of a third-party quality con-
trol agency shall not be considered "fabricated items."
INSPECTION CERTIFICATE. An identification apphed on
a product by an approved agency containing the name of the
manufacturer, the function and performance characteristics,
and the name and identification of an approved agency that
indicates that the product or material has been inspected and
evaluated by an approved agency (see Section 1703 A. 5 and
''Label,'' "Manufacturer's designation" and ''Mark").
INTUMESCENT FIRE-RESISTANT COATINGS. Thin
film hquid mixture applied to substrates by brush, roller, spray
or trowel which expands into a protective foamed layer to pro-
vide fire-resistant protection of the substrates when exposed to
flame or intense heat.
MAIN WINDFORCE-RESISTING SYSTEM. An assem-
blage of structural elements assigned to provide support and
stability for the overall structure. The system generally
receives wind loading from more than one surface.
MASTIC FIRE-RESISTANT COATINGS. Liquid mixture
applied to a substrate by brush, roller, spray or trowel that pro-
vides fire-resistant protection of a substrate when exposed to
flame or intense heat.
PROJECT INSPECTOR [DSA-SS & DSA-SS/CC] The per-
son approved to provide inspection in accordance with Title 24,
Partly California Administrative Code, Section 4-3 3 3(b), The
term "project inspector" is synonymous with "inspector
of record,''
SPECIAL INSPECTION. Inspection as herein required of
the materials, installation, fabrication, erection or placement of
components and connections requiring special expertise to
ensure compliance with approved construction documents and
referenced standards (see Section 1704A).
SPECIAL INSPECTION, CONTINUOUS. The full-time
observation of work requiring special inspection by an
approved special inspector who is present in the area where the
work is being performed.
SPECIAL INSPECTION, PERIODIC. The part-time or
intermittent observation of work requiring special inspection
by an approved special inspector who is present in the area
where the work has been or is being performed and at the com-
pletion of the work.
SPRAYED FIRE-RESISTANT MATERLVLS. Cementitious
or fibrous materials that are sprayed to provide fire-resistant pro-
tection of the substrates.
STRUCTURAL OBSERVATION. The visual observation of
the structural system by a registered design professional for
general conformance to the approved construction documents.
Structural observation does not include or waive the responsi-
bihty for the inspection required by Section 110, 1704 A or
other sections of this code.
SECTION 17034
APPROVALS
1703A.1 Approved agency. An approved agency shall provide
all information as necessary for the building official to deter-
mine that the agency meets the applicable requirements.
1703A.1.1 Independence. An approved agency shall be
objective, competent and independent from the contractor
responsible for the work being inspected. The- agency shall
also disclose possible conflicts of interest so that objectivity
can be confirmed.
1703A.1.2 Equipment. An approved agency shall have
adequate equipment to perform required tests. The equip-
ment shall be periodically calibrated.
1703A.1.3 PersonneL An approved agency shall employ
experienced personnel educated in conducting, supervising
and evaluating tests and/or inspections.
1703A.2 Written appro vaL Any material, appliance, equip-
ment, system or method of construction meeting the require-
ments of this code shall be approved in writing after
satisfactory completion of the required tests and submission of
required test reports.
1703A.3 Approved record. For any material, appliance,
equipment, system or method of construction that has been
approved, a record of such approval, including the conditions
and limitations of the approval, shall be kept on file in the build-
ing officiaVs office and shall be open to public inspection at
appropriate times.
1703A.4 Performance. Specific information consisting of test
reports conducted by an approved testing agency in accordance
with standards referenced in Chapter 35, or other such informa-
tion as necessary, shall be provided for the building official to
determine that the material meets the appUcable code require-
ments.
1703A.4.1 Research and investigation. Sufficient technical
data shall be submitted to the building official to substantiate
the proposed use of any material or assembly. If it is deter-
mined that the evidence submitted is satisfactory proof of
performance for the use intended, the building official shall
approve the use of the material or assembly subject to the
requirements of this code. The costs, reports and investiga-
tions required under these provisions shall be paid by the
applicant.
1703A.4.2 Research reports. Supporting data, where nec-
essary to assist in the approval of materials or assemblies not
specifically provided for in this code, shall consist of valid
research reports from approved sources.
1703A.5 Labeling. Where materials or assemblies are required
by this code to be labeled, such materials and assemblies shall
be labeled by an approved agency in accordance with Section
1703 A. Products and materials required to be labeled shall be
152
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
m
labeled in accordance with the procedures set forth in Sections
1703A.5.1 through 1703A.5.3.
1703A.5.1 Testing. An approved agency shall test a repre-
sentative sample of the product or material being labeled to
the relevant standard or standards. The approved agency
shall maintain a record of the tests performed. The record
shall provide sufficient detail to verify compliance with the
test standard,
1703A.5.2 Inspection and identification. The approved
agency shall periodically perform an inspection, which
shall be in-plant if necessary, of the product or material that
is to be labeled. The inspection shall verify that the labeled
product or material is representative of the product or mate-
rial tested,
1703A.5.3 Label information. The label shall contain the
manufacturer's or distributor's identification, model num-
ber, serial number or definitive information describing the
product or material's performance characteristics and
approved agency's identification.
1703A.6 Evaluation and follow-up inspection services.
Where structural components or other items regulated by this
code are not visible for inspection after completion of a prefab-
ricated assembly, the applicant shall submit a report of each
prefabricated assembly. The report shall indicate the complete
details of the assembly, including a description of the assembly
and its components, the basis upon which the assembly is being
evaluated, test results and similar information and other data as
necessary for the building official to determine conformance to
this code. Such a report shall be approved by the building offi-
cial,
1703A.6.1 Follow-up inspection. The applicant shall pro-
vide for special inspections of fabricated items in accor-
dance with Section 1704A.2.
1703A.6.2 Test and inspection records. Copies of neces-
sary test and inspection records shall be filed with the build-
ing official.
SECTION 17044
SPECIAL INSPECTIONS
1704A.1 General. Where application is made for construction
as described in this section, the owner shall employ one or more
approved agencies to perform inspections during construction
on the types of work listed under Section 1704 A. These inspec-
tions are in addition to the inspections identified in Section 110.
The special inspector shall be a qualified person who shall
demonstrate competence, to the satisfaction of the building
official, for the inspection of the particular type of construction
or operation requiring special inspection. The registered
design professional in responsible charge and engineers of
record involved in the design of the project are permitted to act
as the approved agency and their personnel are permitted to act
as the special inspector for the work designed by them, pro-
vided those personnel meet the qualification requirements of
this section to the satisfaction of the building official. The spe-
cial inspector shall provide written documentation to the build-
ing official demonstrating his or her competence and relevant
experience or training. Experience or training shall be consid-
ered relevant when the documented experience or training is
related in complexity to the same type of special inspection
activities for projects of similar complexity and material quali-
ties. These qualifications are in addition to qualifications speci-
fied in other sections of this code.
Exceptions:
1. Special inspections are not required for work of a
minor nature or as warranted by conditions in the
jurisdiction as approved by the building official.
2. Special inspections are not required for building com-
ponents unless the design involves the practice of pro-
fessional engineering or architecture as defined by
applicable state statutes and regulations governing
the professional registration and certification of engi-
neers or architects.
3. Unless otherwise required by the building official,
special inspections are not required for Group U
occupancies that are accessory to a residential occu-
pancy including, but not limited to, those listed in
Section 312.L
1704A.1.1 Statement of special inspections. The applicant
shall submit a statement of special inspections prepared by
the registered design professional in responsible charge in
accordance with Section 107.1 as a condition for issuance.
This statement shall be in accordance with Section 1705 A.
Exception: The statement of special inspections is per- <
mitted to be prepared by a qualified person approved by
the building official for construction not designed by a
registered design professional.
1704A.1.2 Report requirement. The inspector of record
and special inspectors shall keep records of inspections.
The inspector of record and special inspector shall furnish
inspection reports to the building official, and to the regis-
tered design professional in responsible charge as required
by Title 24, Part 1. Reports shall indicate that work
inspected was or was not completed in conformance to
approved construction documents as required by Title 24,
Parts 1 and 2. Discrepancies shall be brought to the immedi-
ate attention of the contractor for correction. If they are not
corrected, the discrepancies shall be brought to the attention
of the building official and to the registered design profes-
sional in responsible charge prior to the completion of that
phase of the work. A final report documenting required spe-
cial inspections and correction of any discrepancies noted in
the inspections shall be submitted at a point in time agreed
upon prior to the start of work by the applicant and the build-
ing official.
1704A.2 Inspection of fabricators. Where fabrication of
structural load-bearing members and assemblies is being per-
formed on the premises of a fabricator's shop, special inspec-
tion of the fabricated items shall be required by this section and
as required elsewhere in this code.
2010 CALIFORNIA BUILDING CODE
153
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
1704A.2.1 Fabrication and implementation procedures.
The special inspector shall verify that the fabricator main-
tains detailed fabrication and quality control procedures that
provide a basis for inspection control of the workmanship
and the fabricator's ability to conform to approved con-
struction documents and referenced standards. The special
inspector shall review the procedures for completeness and
adequacy relative to the code requirements for the fabrica-
tor's scope of work.
1704A.3 Steel construction. The special inspections for steel
elements of buildings and structures shall be as required by
Section 1704A.3 and Table 1704A.3.
Exceptions:
1. Special inspection of the steel fabrication process
shall not be required where the fabricator does not
perform any welding, thermal cutting or heating oper-
ation of any kind as part of the fabrication process. In
such cases, the fabricator shall be required to submit a
detailed procedure for material control that demon-
strates the fabricator's ability to maintain suitable
records and procedures such that, at any time during
the fabrication process, the material specification,
grade and mill test reports for the main stress-carrying
elements are capable of being determined.
2. The special inspector need not be continuously pres-
ent during welding of the following items, provided
the materials, welding procedures and qualifications
of welders are verified prior to the start of the work;
periodic inspections are made of the work in progress
and a visual inspection of all welds is made prior to
completion or prior to shipment of shop welding.
2.1. Single-pass fillet welds not exceeding V^ 6 inch
(7.9 mm) in size.
2.2. Floor and roof deck welding.
2.3. Welded studs when used for structural dia-
phragm.
2.4. Welded sheet steel for cold-formed steel
members.
2.5. Welding of stairs and railing systems.
1704A.3.1 Welding. Welding inspection and welding
inspector qualification shall be in accordance with this sec-
tion.
1704A.3.1.1 Structural steel. Welding inspection and
welding inspector quaHfication for structural steel shall
be in accordance with AWS DLL
1704A.3.1.2 Cold-formed steel. Welding inspection
and welding inspector qualification for cold-formed
steel floor and roof decks shall be in accordance with
AWSD1.3.
1704A.3.1.3 Reinforcing steel. Welding inspection and
welding inspector qualification for reinforcing steel shall
be in accordance with AWS DL4 and ACI 318.
1704A.3.1,4 Inspection of Structural Welding. Inspec-
tion of all shop and field welding operations shall be
made by a qualified welding inspector approved by the
enforcement agency. The minimum requirements for a
qualified welding inspector shall be as those for an AWS
certified welding inspector (CWI), as defined in the pro-
visions of the AWS QCl. All welding inspectors shall be
as approved by the enforcement agency.
The welding inspector shall make a systematic daily
record of all welds. This record shall include in addition
to other required records:
1. Identification marks of welders.
2. List of defective welds.
3. Manner of correction of defects.
The welding inspector shall check the material, details
of construction and procedure, as well as workmanship
of the welds. The inspector shall verify that the installa-
tion of end-welded stud shear connectors is in accor-
dance with the requirements of AWS Dl.l and the
approved plans and specifications. The inspector shall
furnish the architect, structural engineer and the
enforcement agency with a verified report that the weld-
ing is proper and has been done in conformity with AWS
Dl.l, D1.8 and the approved construction documents.
1704A.3.2 Details. The special inspector shall perform an
inspection of the steel frame to verify compliance with the
details shown on the approved construction documents,
such as bracing, stiffening, member locations and proper
application of joint details at each connection.
I704A.3.2,I Steel joist and joist girder inspection. Spe-
cial inspection is required during the manufacture and
welding of steel joists or joist girders. The special inspec-
tor shall verify that proper quality control procedures
and tests have been employed for all materials and the
manufacturing process, and shall perform visual inspec-
tion of the finished product. The special inspector shall
place a distinguishing mark, and/or tag with this distin-
guishing mark, on each inspected joist or joist girder.
This mark or tag shall remain on the joist or joist girder
throughout the job-site receiving and erection process.
1704A3,2,2 Light-jramed steel truss inspection. The
manufacture of cold-formed light-framed steel trusses
shall be continuously inspected by a qualified special
inspector approved by the enforcement agency. The spe-
cial inspector shall verify conformance of materials and
manufacture with approved plans and specifications. The
special inspector shall place a distinguishing mark,
and/or tag with this distinguishing mark, on each
inspected truss. This mark or tag shall remain on the truss
throughout the job-site receiving and erection process.
<
<
154
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704A3
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
CBC REFERENCE
1 . Material verification of high-strength bolts, nuts and
washers:
a. Identification markings to conform to ASTM
standards specified in the approved
construction documents.
—
X
AISC 360,
Section A3.3 and
applicable ASTM
material standards
—
b. Manufacturer's certificate of compliance
required.
—
X
—
—
2. Inspection of high-strength bolting:
a. Snug-tight joints.
—
X
AISC 360,
Section M2.5
1704A.3.3
b.Pretensioned and slip-critical joints using
tum-of-nut with matchmarking, twist-off bolt or
direct tension indicator methods of installation.
—
X
c.Pretensioned and slip-critical joints using
tum-of-nut without matchmarking or calibrated
wrench methods of installation.
X
—
3. Material verification of structural steel and
cold-formed steel deck:
a. For structural steel, identification markings to
conform to AISC 360.
—
X
AISC 360,
Section M5.5
b. For other steel, identification markings to conform
to ASTM standards specified in the approved
construction documents.
—
X
Applicable ASTM
material standards
c. Manufacturer's certified test reports.
—
X
4. Material verification of weld filler materials:
a. Identification markings to conform to AWS
specification in the approved construction
documents.
—
X
AISC 360,
Section A3. 5 and
applicable AWS
A5 documents
—
b.Manufacturer's certificate of compliance required.
—
X
—
—
5 . Inspection of welding :
a. Structural steel and cold-formed steel deck:
1) Complete and partial joint penetration groove
welds.
X
—
AWSDl.l
1704A.3.1
2) Multipass fillet welds.
X
—
3) Single-pass fillet welds > Vj^"
X
—
4) Plug and slot welds.
X
—
5) Single-pass fillet welds < Vj^"
—
X
6) Floor and roof deck welds.
—
X
AWS D 1.3
(continued)
2010 CALIFORNIA BUILDING CODE
155
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704^1.3— continued
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
VERIRCATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
CBC
REFERENCE
b. Reinforcing steel:
—
1) Verification of weldability of reinforcing steel
otlier than ASTM A 706.
—
X
AWS D1.4 ACI 318: Section 3.5.2
2) Reinforcing steel resisting flexural and axial
forces in intermediate and special moment
frames, and boundary elements of special
structural walls of concrete and shear
reinforcement.
X
—
3) Shear reinforcement.
X ,
—
4) Other reinforcing steel.
—
X
6. Inspection of steel frame joint details for compliance:
a. Details such as bracing and stiffening.
—
X
—
1704A.3.2
b. Member locations.
—
X
c. Apphcation of joint details at each connection.
—
X
For SI: 1 inch = 25.4 mm.
a. Where applicable, see also Section 1707A.1, Special inspection for seismic resistance.
1704A.3.3 High-strength bolts. Installation of high-
strength bolts shall be inspected in accordance with AISC
360.
1704A .3.3.1 General. While the work is in progress, the
special inspector shall determine that the requirements
for bolts, nuts, washers and paint; bolted parts and instal-
lation and tightening in such standards are met. For bolts
requiring pretensioning, the special inspector shall
observe the preinstallation testing and calibration proce-
dures when such procedures are required by the installa-
tion method or by project plans or specifications;
determine that all plies of connected materials have been
drawn together and properly snugged and monitor the
installation of bolts to verify that the selected procedure
for installation is properly used to tighten bolts. For
joints required to be tightened only to the snug-tight con-
dition, the special inspector need only verify that the con-
nected materials have been drawn together and properly
snugged.
1704A .3.3.2 Periodic monitoring. Monitoring of bolt
installation for pretensioning is permitted to be per-
formed on a periodic basis when using the tum-of-nut
method with matchmarking techniques, the direct ten-
sion indicator method or the alternate design fastener
(twist-off bolt) method. Joints designated as snug tight
need be inspected only on a periodic basis.
1704A .3.3.3 Continuous monitoring. Monitoring of
bolt installation for pretensioning using the calibrated
wrench method or the turn-of-nut method without
matchmarking shall be performed on a continuous basis.
1704A.3.4 Cold-formed steel trusses spanning 60 feet or
greater. Where a cold-formed steel truss clear span is 60
feet (18 288 mm) or greater, the special inspector shall ver-
ify that the temporary installation restraint/bracing and the
permanent individual truss member restraint/bracing are
installed in accordance with the approved truss submittal
package.
1704A.4 Concrete construction. The special inspections and
verifications for concrete construction shall be as required by
this section and Table 1704A.4.
Exceptions: [DSA-SS & DSA-SS/CC] Special inspections
shall not be required for:
1, Nonstructural concrete slabs supported directly on
the ground, including prestressed slabs on grade,
where the effective prestress in the concrete is less
than 150 psi(L03MPa).
2. Concrete patios, driveways and sidewalks, on grade.
1704A.4.1 Materials. In the absence of sufficient data or
documentation providing evidence of conformance to qual-
ity standards for materials in Chapter 3 of ACI 318, the
building official shall require testing of materials in accor-
dance with the appropriate standards and criteria for the
material in Chapter 3 of ACI 318. Weldability of reinforce-
ment, except that which conforms to ASTM A 706, shall be
determined in accordance with the requirements of Section
3.5.2 of ACI 318.
1704A.4,2 Batch plant inspection. Except as provided
under Section 1 704A.4,3, the quality and quantity of materi-
als used in transit-mixed concrete and in batched
aggregates shall be continuously inspected at the location
156
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
where materials are measured by an approved special
inspector.
1704A,4,3 Waiver of continuous batch plant inspection.
Continuous batch plant inspection may be waived by the
registered design professional in responsible charge, sub-
ject to approval by the enforcement agency, under either of
the following conditions:
1. The concrete plant complies fully with the require-
ments ofASTM C 94, Sections 8 and 9, and has a cur-
rent certificate from the National Ready Mixed
Concrete Association or another agency acceptable
to the enforcement agency. The certification shall
indicate that the plant has automatic batching and
recording capabilities,
2. For single-story light framed buildings and isolated
foundations supporting equipment only, where the
specified compressive strength f \ of the concrete
delivered to thejobsite is 3,500 psi (24.13 MP a) and
where thef\ used in design is not greater than 3,000
psi (20,68 MPa).
When continuous batch plant inspection is waived, the
following requirements shall apply and shall be described
in the construction documents:
1. Qualified technician of the testing laboratory shall
check the first batch at the start of the day.
TABLE 1704A4
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCED
STANDARD^
CBC REFERENCE
1. Inspection of reinforcing steel, including
prestressing tendons, and placement.
—
X
ACI 318: 3.5, 7.1-7.7
1913A.4
2. Inspection of reinforcing steel welding in
accordance with Table 1704A.3, Item 5b.
—
—
AWSD1.4
ACI 318: 3.5.2
—
3. Inspection of bolts to be installed in concrete
prior to and during placement of concrete where
allowable loads have been increased or where
strength design is used.
X
—
ACI 318:
8.1.3,21.2.8
1911A.5,
1912A,1
4. Inspection of anchors installed in hardened
concrete.
—
X
ACI 318:
3.8.6,8.1.3,21.2.8
1912A.1
5. Verifying use of requked design mix.
—
X
ACI 318: Ch. 4, 5.2-5.4
1904A.2.2, 1913A.2,
1913A.3
6. At the time fresh concrete is sampled to fabricate
specimens for strength tests, perform slump and
air content tests, and determine the temperamre
of the concrete.
X
—
ASTM C 172
ASTMC31
ACI 318: 5.6, 5.8
1913A.10
7. Inspection of concrete and shotcrete placement
for proper application techniques.
X
—
ACI 318: 5.9, 5.10
1913A.6, 1913A.7,
1913A.8
8. Inspection for maintenance of specified curing
temperature and techniques.
—
X
ACI 318: 5.11-5.13
1913A.9
9. Inspection of prestressed concrete:
a. Application of prestressing forces.
b. Grouting of bonded prestressing tendons in
the seismic-force-resisting system.
X
X
—
ACI 318: 18.20
ACI 318: 18.18.4
—
10. Erection of precast concrete members.
—
X
ACI 318: Ch. 16
—
11. Verification of in-situ concrete strength, prior to
stressing of tendons in posttensioned concrete
and prior to removal of shores and forms from
beams and structural slabs.
—
X
ACI 318: 6.2
—
12. Inspect formwork for shape, location and
dimensions of the concrete member being
formed.
—
X
ACI 318: 6.1.1
—
For SI: 1 inch = 25.4 mm.
a. Where applicable, see also Section 1707A.1, Special inspection for seismic resistance.
2010 CALIFORNIA BUILDING CODE
157
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
2. Licensed weighmaster to positively identify materials
as to quantity and certify to each load by a batch
ticket.
3. Batch tickets, including actual material quantities
and weights shall accompany the load and shall be
transmitted to the inspector of record by a truck
driver with load identified thereon. The load shall not
be placed without a batch ticket identifying the mix.
The inspector will keep a daily record of placements,
identifying each truck, its load, time of receipt and
approximate location of deposit in the structure and
will transmit a copy of the daily record to the enforce-
ment agency.
1704A.4.4 Inspection of prestressed concrete.
i. In addition to the general inspection required for con-
crete work, all plant fabrication of prestressed con-
crete members or tensioning of posttensioned
members constructed at the site shall be continuously
inspected by an inspector specially approved for this
purpose by the enforcement agency.
2. The prestressed concrete plant fabrication inspector
shall check the materials, equipment, tensioning pro-
cedure and construction of the prestressed members
and prepare daily written reports. The inspector shall
make a verified report identifying the members by
mark and shall include such pertinent data as lot
numbers of tendons used, tendon jacking forces, age
and strength of concrete at time of tendon release and
such other information that may be required.
3. The inspector of prestressed members posttensioned
at the site shall check the condition oftheprestressing
tendons, anchorage assemblies and concrete in the
area of the anchorage, the tensioning equipment and
the tensioning procedure, and prepare daily written
reports. The inspector shall make a verified report of
the prestressing operation identifying the members or
tendons by mark and including such pertinent data as
the initial cable slack, net elongation of tendons, jack-
ing force developed, and such other information as
may be required.
4. The verified reports of construction shall show that of
the inspector's own personal knowledge, the work
covered by the report has been performed and materi-
als used and installed in every material respect in
compliance with the duly approved plans and specifi-
cations for plant fabrication inspection. The verified
report shall be accompanied by test reports required
for materials used. For site posttensioning inspec-
tions the verified report shall be accompanied by cop-
ies of calibration charts, certified by an approved
testing laboratory, showing the relationship between
gage readings and force applied by the jacks used in
the prestressing procedure
1704A,4,5 Concrete preplacement inspection. Concrete
shall not be placed until the forms and reinforcement have
been inspected, all preparations for the placement have
been completed, and the preparations have been checked by
the inspector of record.
1 704A,4, 6 Placing record, A record shall be kept on the site
of the time and date of placing the concrete in each portion
of the structure. Such record shall be kept until the comple-
tion of the structure and shall be open to the inspection of
the enforcement agency.
1704A.5 Masonry construction. Masonry construction shall
be inspected and verified in accordance with the requirements
of Sections 1704A.5.1 through 1704A.5.3, depending on the
occupancy category of the building or structure.
1704A.5.1 Glass unit masonry and masonry veneer in
Occupancy Category IV. The minimum special inspection
program for glass unit masonry or masonry veneer designed
by Chapter 21A or 14, or by Chapter 6 of TMS 402/ACI
530/ASCE 5, in structures classified as Occupancy Category
IV, in accordance with Section 1604A.5, shall comply with
Table 1704A.5.1.
1704A.5.2 Engineered masonry in Occupancy Category
I. The minimum special inspection program for masonry
designed by Section 2107A or 2108A or by chapters other
than Chapter 5, 6 or 7 of TMS 402/ACI 530/ASCE 5 in
structures classified as Occupancy Category I, in accor-
dance with Section 1604A.5, shall comply with Table
1704A.5.1.
1704A.5.3 Engineered masonry in Occupancy Category
//, /// or IV. The minimum special inspection program for
masonry designed by Section 2107A or 2108A or by chap-
ters other than Chapter 6 of TMS 402/ACI 530/ASCE 5 in
structures classified as Occupancy Category 11, III, or IV, in
accordance with Section 1604A.5, shall comply with Table
1704A.5.3.
1704A.6 Wood construction. Special inspections of the fabri-
cation process of prefabricated wood structural elements and
assemblies shall be in accordance with Section 1704A.2. Spe-
cial inspections of site-built assemblies shall be in accordance
with this section.
1704A.6.1 Higli-load diaphragms. High-load diaphragms
designed in accordance with Table 2306.2.1(2) shall be
installed with special inspections as indicated in Section
1704A. 1 . The special inspector shall inspect the wood struc-
tural panel sheathing to ascertain whether it is of the grade
and thickness shown on the approvedhmlding plans. Addi-
tionally, the special inspector must verify the nominal size
of framing members at adjoining panel edges, the nail or sta-
ple diameter and length, the number of fastener lines and
that the spacing between fasteners in each line and at edge
margins agrees with the approved building plans.
1704A.6.2 Metal-plate-connected wood trusses span-
ning 60 feet or greater. Where a truss clear span is 60 feet
(18 288 mm) or greater, the special inspector shall verify
that the temporary installation restraint/bracing and the per-
manent individual truss member restraint/bracing are
installed in accordance with the approved truss submittal
package.
m
<
<
<
<
<
158
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTBONS
1704A,6.3 Wood structural elements and assemblies. Spe-
cial inspection of wood structural elements and assemblies
is required, as specified in this section, to ensure confor-
mance with approved drawings and specifications and
applicable standards.
The special inspector shall furnish a verified report to the
design professional in general responsible charge of con-
struction observation, the structural engineer and the
enforcement agency, in accordance with Title 24, Part 1 and
this chapter The verified report shall list all inspected mem-
bers or trusses, and shall indicate whether or not the
inspected members or trusses conform with applicable
standards and the approved drawings and specifications.
Any nonconforming items shall be indicated on the verified
report.
1704A.6.3,1 Structural glued-laminated timber. Manu-
facture of all structural glued-laminated timber shall be
continuously inspected by a qualified special inspector
approved by the enforcement agency.
The special inspector shall verify that proper quality
control procedures and tests have been employed for all
materials and the manufacturing process, and shall per-
form visual inspection of the finished product. Each
inspected member shall be stamped by the special
inspector with an identification mark.
Exception: Special inspection is not required for
noncustom members ofS^/g inch (130 mm) maximum
width and 18 inch (457 mm) maximum depth, and
with a maximum clear span of 32 feet (9754 mm),
manufactured and marked in accordance with
ANSl/AITC A 190.1 Section 6.1.1 for noncustom
members.
1704A.6,3,2 Manufactured open web trusses. The man-
ufacture of open web trusses shall be continuously
inspected by a qualified special inspector approved by
the enforcement agency.
The special inspector shall verify that proper quality
control procedures and tests have been employed for all
materials and the manufacturing process, and shall per-
form visual inspection of the finished product. Each
inspected truss shall be stamped with an identification
mark by the special inspector
1704A.6.4 Timber connectors. The installation of all split
ring and shear plate timber connectors, and timber rivets
shall be continuously inspected by a qualified inspector
approved by the enforcement agency. The inspector shall
furnish the architect, structural engineer and the enforce-
ment agency with a report duly verified by him that the mate-
rials, timber connectors and workmanship conform to the
approved plans and specifications.
1704A.7 Soils. Special inspections for existing site soil condi-
tions, fill placement and load-bearing requirements shall be as
required by this section and Table 1704A.7. The approved
geotechnical report, and the construction documents prepared
by the registered design professionals shall be used to deter-
mine compliance. During fill placement, the special inspector
shall determine that proper materials and procedures are used
in accordance with the provisions of the approved geotechnical
report.
Exception: Where Section 1803 does not require reporting
of materials and procedures for fill placement, the special
inspector shall verify that the in-place dry density of the
compacted fill is not less than 90 percent of the maximum
dry density at optimum moisture content determined in
accordance with ASTM D 1557.
1704 AJ.l Soil fill. All fills used to support the foundations
of any building or structure shall be continuously inspected
by the geotechnical engineer or his or her qualified repre-
sentative. It shall be the responsibility of the geotechnical
engineer to verify that fills meet the requirements of the
specifications and to coordinate all fill inspection and test-
ing during the construction involving such fills.
The duties of the geotechnical engineer or his or her qual-
ified representative shall include, but need not be limited to,
the observation of cleared areas and benches prepared to
receive fill; observation of the removal of all unsuitable
soils and other materials; the approval of soils to be used as
fill material; the inspection of placement and compaction of
fill materials; the testing of the fills; and the inspection or <
review of geotechnical drainage devices where required by
the soils investigation, buttress fills or other similar protec-
tive measures.
A verified report shall be submitted to the enforcement
agency by the geotechnical engineer The report shall indi-
cate that all the tests required by the construction docu-
ments were completed and that the tested materials were in
compliance with the construction documents.
1704A.8 Driven deep foundations. Special inspections shall
be performed during installation and testing of driven deep
foundation elements as required by Table 1704A.8. The
approved geotechnical report, and the construction documents
prepared by the registered design professionals, shall be used
to determine compliance.
1704A.8.1 Driven deep foundations observation. The
installation of driven deep foundations shall be continu-
ously observed by a qualified representative of the
geotechnical engineer responsible for that portion of the
project. <
The representative of the geotechnical engineer shall
make a report of the deep foundation -driving operation giv-
ing such pertinent data as the physical characteristics of the
deep foundation-driving equipment, identifying marks for
each deep foundation, the total depth of embedment for each
deep foundation; and when the allowable deep foundation
loads are determined by a dynamic load formula, the design
formula used, and the permanent penetration under the last
10 blows. One copy of the report shall be sent to the enforce-
ment agency.
1704A.9 Cast-in-piace deep foundations. Special inspec-
tions shall be performed during installation and testing of
cast-in-place deep foundation elements as required by Table
1704A.9. The approved gtoitohwicdX report, and the construc-
tion documents prepared by the registered design profession-
als, shall be used to determine compliance.
2010 CALIFORNIA BUILDING CODE
159
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704A.5.1
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
VERIFICATION AND INSPECTION
FREQUENCY OF INSPECTION
REFERENCE FOR CRITERIA
CONTINUOUS
PERIODIC
CBC SECTION
TMS 402/ACI
530/ASCE 5^
TMS 602/ACI
530.1/ASCE 6«
1 . Compliance with required inspection pro-
visions of the construction documents and
the approved submittals shall be verified.
— .
X
—
—
Art. 1.5
2. Verification of /^ and/^^ prior to con-
struction except where specifically
exempted by this code.
—
X
—
—
Art. 1.4B
3. Verification of slump flow and VSI as
delivered to the site for self-consolidating
grout.
X
—
—
—
Art. L5B.l.b.3
4, As masonry construction begins, the following shall be verified to ensure compliance:
a. Proportions of site-prepared mortar.
—
X
—
—
Art. 2.6A
b. Construction of mortar joints.
—
X
—
—
Art. 3.3B
c. Location of reinforcement,
connectors, prestressing tendons
and anchorages.
—
X
—
—
Art. 3.4, 3.6A
d. Prestressing technique.
—
X
—
—
Art. 3.6B
e. Grade and size of prestressing
tendons and anchorages.
~
X
—
—
Art. 2.4B, 2.4H
5. During construction the inspection program shall verify:
a. Size and location of structural
elements.
~~
X
~
—
Art. 3.3F
b. Type, size and location of anchors,
including other details of anchorage
of masonry to structural members,
frames or other construction.
—
X
—
Sec. 1.2.2(e),
1.16.1
—
c. Specified size, grade and type of
reinforcement, anchor bolts,
prestressing tendons and
anchorages.
—
X
—
Sec. 1.15
Art. 2.4, 3.4
d. Welding of reinforcing bars.
X
— .
—
Sec. 2.1.9.7.2,
3.3.3.4(b)
—
e. Preparation, construction and
protection of masonry during cold
weather (temperature below 40°F)
or hot weather (temperature above
90^F).
—
X
Sec. 2104A.3,
2104A.4
—
Art. 1.8C,
1.8D
f . Application and measurement of
prestressing force.
X
—
—
—
Art. 3.6B
(continued)
160
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704A.5.1— continued
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF M>»SONRY CONSTRUCTION
VERIFICATION AND INSPECTION
FREQUENCY OF INSPECTION
REFERENCE FOR CRITERIA
CONTINUOUS
PERIODIC
CSC SECTION
TMS 402/ACI
530/ASCE 5"
TMS 602/ACI
530.1/ASCE 6=
6. Prior to grouting, the following shall be verified to ensure compliance:
a. Grout space is clean.
—
X
—
—
Art. 3.2D
b. Placement of reinforcement and
connectors, and prestressing
tendons and anchorages.
—
X
—
Sec. 1.13
Art. 3.4
c. Proportions of site-prepared grout
and prestressing grout for bonded
tendons.
—
X
—
—
Art. 2.6B
d. Construction of mortar joints.
—
X
—
—
Art. 3.3B
7. Grout placement shall be verified to
ensure compliance:
X
—
—
—
Art. 3.5
a. Grouting of prestressing bonded
tendons.
X
—
—
—
Art. 3.6C
8. Preparation of any required grout speci-
mens, mortar specimens and/or prisms
shall be observed.
—
X
Sec. 2105A.2.2,
2105A.3
—
Art. 1.4
For SI: °C = [(°F) - 32J/1.8.
a. The specific standards referenced are those listed in Chapter 35.
2010 CALIFORNIA BUILDING CODE
161
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 1704A5.3
LEVEL 2 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
VERIFiCATION AND INSPECTION
CONTINUOUS
PERIODIC
REFERENCE FOR CRITERIA
CHC SECTION
TMS 402/ACI
530/ASCE 5^
TMS 602/ACI
530.1/ASCE 6^
1. Compliance with required inspection provi-
sions of the construction documents and the
approved submittals.
—
X
—
—
Art. 1.5
2. Verification of /^ and/^^ prior to construc-
tion and for every 5,000 square feet during
construction.
—
X
—
—
Art. 1.4B
3. Verification of proportions of materials in
premixed or preblended mortar and grout as
delivered to the site.
—
X
—
—
Art. 1.5B
4. Verification of slump flow and VSI as deliv-
ered to the site for self-consohdating grout.
X
—
—
—
Art. l,5B.l.b.3
5. The following shall be verified to ensure comj
)liance:
a. Proportions of site-prepared mortar,
grout and prestressing grout for bonded
tendons.
—
X
—
—
Art. 2.6A
b. Placement of masonry units and
construction of mortar joints.
—
X
—
—
Art. 3.3B
c. Placement of reinforcement, connectors
and prestressing tendons and
anchorages.
—
X
—
Sec. 1.15
Art. 3.4, 3.6A
d. Grout space prior to grout.
X
—
—
—
Art. 3.2D
e. Placement of grout.
X
—
—
—
Art. 3.5
f . Placement of prestressing grout.
X
—
—
—
Art. 3.6C
g. Size and location of structural elements.
—
X
—
—
Art. 3.3F
h. Type, size and location of anchors,
including other details of anchorage of
masonry to structural members, frames
or other construction.
X
—
—
Sec. 1.2.2(e),
1.16.1
—
i. Specified size, grade and type of
reinforcement, anchor bolts,
prestressing tendons and anchorages.
—
X
—
Sec. 1.15
Art. 2.4, 3.4
j. Welding of reinforcing bars.
X
—
~
Sec. 2.1.9.7.2,
3.3.3.4 (b)
—
k. Preparation, construction and protection
of masonry during cold weather
(temperature below 40°F) or hot
weather (temperature above 90°F).
—
X
Sec. 2104A.3, 2104A.4
Art. 1.8C, 1.8D
1. Application and measurement of
prestressing force.
X
—
—
—
Art. 3.6B
6. Preparation of any required grout specimens
and/or prisms shall be observed.
X
—
Sec. 2105A.2.2, 2105A.3
Art. 1.4
7. Post-Installed anchors
X
—
1615A.L14[DSA-SS&
OSHPD]
1615.1.12 [DSA'SS/CC]
—
—
For SI: °C = [(°F) - 32]/1.8, 1 square foot = 0.0929 ml
a. The specific standards referenced are those listed in Chapter 35.
162
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
TABLE 17044.7
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1. Verify materials below shallow foundations are adequate to
achieve the design bearing capacity.
—
X
2. Verify excavations are extended to proper depth and have
reached proper material.
—
X
3. Perform classification and testing of compacted fill
materials.
—
X
4. Verify use of proper materials, densities and lift thicknesses
during placement and compaction of compacted fill.
X
—
5. Prior to placement of compacted fill, observe subgrade and
verify that site has been prepared properly.
—
X
TABLE 1704A8
REQUIRED VERIFICATION AND INSPECTION OF DRIVEN DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1. Verify element materials, sizes and lengths comply with the
requirements.
X
—
2. Determine capacities of test elements and conduct additional
load tests, as required.
X
—
3. Observe driving operations and maintain complete and
accurate records for each element.
X
—
4. Verify placement locations and plumbness, confirm type and
size of hammer, record number of blows per foot of
penetration, determine required penetrations to achieve design
capacity, record tip and butt elevations and document
any damage to foundation element.
X
—
5. For steel elements, perform additional inspections in
accordance with Section 1704 A. 3.
—
—
6. For concrete elements and concrete-filled elements, perform
additional inspections in accordance with Section 1704A.4.
—
—
7. For specialty elements, perform additional inspections as
determined by the registered design professional in
responsible charge.
—
—
TABLE 1704A9
REQUIRED VERIFICATION AND INSPECTION OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK
CONTINUOUS DURING TASK LISTED
PERIODICALLY DURING TASK LISTED
1 . Observe driUing operations and maintain complete and
accurate records for each element.
X
—
2. Verify placement locations and plumbness, confirm element
diameters, bell diameters (if applicable), lengths, embedment
into bedrock (if applicable) and adequate end-bearing strata
capacity. Record concrete or grout volumes.
X
—
3. For concrete elements, perform additional inspections in
accordance with Section 1704A.4.
—
—
2010 CALIFORNIA BUILDING CODE
163
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
1704A.10 Helical pile foundations. Special inspections shall
be performed continuously during installation of helical pile
foundations. The information recorded shall include installa-
tion equipment used, pile dimensions, tip elevations, final
depth, final installation torque and other pertinent installation
data as required by the registered design professional in
responsible charge. The approved geotechnical report and the
construction documents prepared by the registered design pro-
fessional shall be used to determine compliance.
1704A.11 Vertical masonry foundation elements. Special
inspection shall be performed in accordance with Section
1704A.5 for vertical masonry foundation elements.
1704A.12 Sprayed fire-resistant materials. Special inspec-
tions for sprayed fire-resistant materials applied to floor, roof
and wall assemblies and structural members shall be in accor-
dance with Sections 1704A.12.1 through 1704A.12.6. Special
inspections shall be based on the fire-resistance design as des-
ignated in the approved construction documents. The tests set
forth in this section shall be based on samplings from specific
floor, roof and wall assemblies and structural members. Spe-
cial inspections shall be performed after the rough installation
of electrical, automatic sprinkler, mechanical and plumbing
systems and suspension systems for ceilings, where applicable.
1704A.12.1 Physical and visual tests. The special inspec-
tions shall include the following tests and observations to
demonstrate compliance with the listing and the fire-resis-
tance rating:
1. Condition of substrates.
2. Thickness of application.
3. Density in pounds per cubic foot (kg/m^).
4. Bond strength adhesion/cohesion.
5. Condition of finished application.
1704A.12.2 Structural member surface conditions. The
surfaces shall be prepared in accordance with the approved
fire-resistance design and the written instructions of
approved manufacturers. The prepared surface of structural
members to be sprayed shall be inspected before the appli-
cation of the sprayed fire-resistant material.
1704A.12,3 Application. The substrate shall have a mini-
mum ambient temperature before and after apphcation as
specified in the written instructions of approved manufac-
turers. The area for application shall be ventilated during
and after application as required by the written instructions
of approved manufacturers.
1704A.12.4 Thickness. No more than 10 percent of the
thickness measurements of the sprayed fire-resistant mate-
rials applied to floor, roof and wall assemblies and structural
members shall be less than the thickness required by the
approved fire-resistance design, but in no case less than the
minimum allowable thickness required by Section
1704A.12.4.1.
1704A. 12.4.1 Minimum allowable thickness. For
design thicknesses 1 inch (25 mm) or greater, the mini-
mum allowable individual thickness shall be the design
thickness minus V4 inch (6.4 mm). For design thick-
nesses less than 1 inch (25 mm), the minimum allowable
individual thickness shall be the design thickness minus
25 percent. Thickness shall be determined in accordance
with ASTM E 605. Samples of the sprayed fire-resistant
materials shall be selected in accordance with Sections
1704A. 12.4.2 and 1704A. 12.4.3.
1704A. 12.4.2 Floor, roof and wall assemblies. The
thickness of the sprayed fire-resistant material applied to
floor, roof and wall assemblies shall be determined in
accordance with ASTM E 605, making not less than four
measurements for each 1,000 square feet (93 m^) of the
sprayed area in each story or portion thereof
1704A.12.4.2.1 Cellular decks. Thickness measure-
ments shall be selected from a square area, 12 inches
by 12 inches (305 mm by 305 mm) in size. A mini-
mum of four measurements shall be made, located
symmetrically within the square area.
1704A. 12.4.2.2 Fluted decks. Thickness measure-
ments shall be selected from a square area, 12 inches
by 12 inches (305 mm by 305 mm) in size. A mini-
mum of four measurements shall be made, located
symmetrically within the square area, including one
each of the following: valley, crest and sides. The
average of the measurements shall be reported.
1704A.12.4.3 Structural members. The thickness of
the sprayed fire-resistant material applied to structural
members shall be determined in accordance with ASTM
E 605. Thickness tesfing shall be performed on not less
than 25 percent of the structural members on each floor.
1704A. 12.4.3.1 Beams and girders. At beams and
girders thickness measurements shall be made at nine
locations around the beam or girder at each end of a
12-inch (305 mm) length.
1704A. 12.4.3.2 Joists and trusses. At joists and
trusses, thickness measurements shall be made at
seven locations around the joist or truss at each end of
a 12-inch (305 mm) length.
1704A.12.4.3.3 Wide-flanged columns. At wide-
flanged columns, thickness measurements shall be
made at 1 2 locations around the colunm at each end of
a 12-inch (305 mm) length.
1704A.12.4.3.4 Hollow structural section and pipe
columns. At hollow structural section and pipe col-
umns, thickness measurements shall be made at a
minimum of four locations around the column at each
end of a 12-inch (305 mm) length.
1704A.12,5 Density. The density of the sprayed fire-resis-
tant material shall not be less than the density specified in
the approved fire-resistance design. Density of the sprayed
fire-resistant material shall be determined in accordance
with ASTM E 605. The test samples for determining the
density of the sprayed fire-resistant materials shall be
selected as follows:
1 . From each floor, roof and wall assembly at the rate of
not less than one sample for every 2,500 square feet
(232 m^) or portion thereof of the sprayed area in each
story.
164
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
2. From beams, girders, trusses and columns at the rate
of not less than one sample for each type of structural
member for each 2,500 square feet (232 m^) of floor
area or portion thereof in each story.
1704A.12.6 Bond strength. The cohesive/adhesive bond
strength of the cured sprayed fire-resistant material applied
to floor, roof and wall assemblies and structural members
shall not be less than 150 pounds per square foot (psf) (7.18
kN/m^). The cohesive/adhesive bond strength shall be deter-
mined in accordance with the field test specified in ASTM E
736 by testing in-place samples of the sprayed fire-resistant
material selected in accordance with Sections 1704.12,6.1
through 1704.12.6.3.
1704A.12.6.1 Floor, roof and wall assemblies. The test
samples for determining the cohesive/adhesive bond
strength of the sprayed fire-resistant materials shall be
selected from each floor, roof and wall assembly at the rate
of not less than one sample for every 2,500 square feet
(232 m^) of the sprayed area in each story or portion
thereof.
1704A .12.6.2 Structural members. The test samples
for determining the cohesive/adhesive bond strength of
the sprayed fire-resistant materials shall be selected from
beams, girders, trusses, columns and other structural
members at the rate of not less than one sample for each
type of structural member for each 2,500 square feet
(232 m^) of floor area or portion thereof in each story.
1704A.12.6.3 Primer, paint and encapsulant bond
tests. Bond tests to quahfy a primer, paint or encapsulant
shall be conducted when the sprayed fire-resistant mate-
rial is applied to a primed, painted or encapsulated sur-
face for which acceptable bond-strength performance
between these coatings and the fire-resistant material has
not been determined. A bonding agent approved by the
SFRM manufacturer shall be applied to a primed,
painted or encapsulated surface where the bond strengths
are found to be less than required values.
1704A.13 Mastic and intumescent fire-resistant coatings.
Special inspections for mastic and intumescent fire-resistant
coatings applied to structural elements and decks shall be in
accordance with AWCI 12-B. Special inspections shall be
based on the fire-resistance design as designated in the
approved construction documents.
1704A.14 Exterior insulation and finish systems (EIFS).
Special inspections shall be required for all EIFS applications.
Exceptions:
1. Special inspections shall not be required for EIFS
applications installed over a water-resistive barrier
with a means of draining moisture to the exterior.
2. Special inspections shall not be required for EIFS
applications installed over masonry or concrete walls.
1704A.14.1 Water-resistive barrier coating. A water-
resistive barrier coating complying with ASTM E 2570
requires special inspection of the water-resistive barrier
coating when installed over a sheathing substrate.
1704A.15 Special cases. Special inspections shall be required
for proposed work that is, in the opinion of the building official,
unusual in its nature, such as, but not limited to, the following
examples:
1. Construction materials and systems that are alternatives
to materials and systems prescribed by this code.
2. Unusual design applications of materials described in
this code.
3. Materials and systems required to be installed in accor-
dance with additional manufacturer's instructions that
prescribe requirements not contained in this code or in
standards referenced by this code.
[F] 1704A.16 Special inspection for smoke control. Smoke
control systems shall be tested by a special inspector,
[F] 1704A.16.1 Testing scope. The test scope shall be as
follows:
1 . During erection of ductwork and prior to concealment
for the purposes of leakage testing and recording of
device location.
2. Prior to occupancy and after sufficient completion for
the purposes of pressure difference testing, flow mea-
surements and detection and control verification.
[F] 1704A.16.2 Qualifications. Special inspection agen-
cies for smoke control shall have expertise in fire protection
engineering, mechanical engineering and certification as air
balancers.
1704A,17 Shotcrete, All shotcrete work shall be continuously
inspected by an inspector specially approved for that purpose
by the enforcement agency. The special shotcrete inspector
shall check the materials, placing equipment, details of con-
struction and construction procedure. The inspector shall fur-
nish a verified report that of his or her own personal knowledge
the work covered by the report has been performed and materi-
als used and installed in every material respect in compliance
with the duly approved plans and specifications.
1704AJ7J Visual examination for structural soundness
of in-place shotcrete. Completed shotcrete work shall be
checked visually for reinforcing bar embedment, voids, rock
pockets, sand streaks and similar deficiencies by examining
a minimum of three 3 -inch (76 mm) cores taken from three
areas chosen by the design engineer which represent the
worst congestion of reinforcing bars occurring in the pro-
ject. Extra reinforcing bars may be added to noncongested
areas and cores may be taken from these areas. The cores
shall be examined by the special inspector and a report sub-
mitted to the enforcement agency prior to final approval of
the shotcrete.
Exception: Shotcrete work fully supported on earth,
minor repairs and when, in the opinion of the enforce-
ment agency, no special hazard exists.
SECTION 17054
STATEMENT OF SPECIAL INSPECTIONS
1705A.1 General. Where special inspection or testing is
required by Section 1704A, 1707A or 1708A, the registered
2010 CALIFORNIA BUILDING CODE
165
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
>
design professional in responsible charge shall prepare a state-
ment of special inspections in accordance with Section 1705A
for submittal by the applicant (see Section 1704A.1.1).
1705A.2 Content of statement of special inspections. The
statement of special inspections shall identify the following:
1. The materials, systems, components and work required
to have special inspection or testing by the building offi-
cial or by the registered design professional responsible
for each portion of the work.
2. The type and extent of each special inspection.
3. The type and extent of each test.
4. Additional requirements for special inspection or testing
for seismic or wind resistance as specified in Section
1705A.3, 1705A.4, 1707A or 1708A.
5. For each type of special inspection, identification as to
whether it will be continuous special inspection or peri-
odic special inspection.
1705A.3 Seismic resistance. The statement of special inspec-
tions shall include seismic requirements for cases covered in
Sections 1705A.3.1 through 1705A.3.5.
1705A.3.1 Seismic-force-resisting systems. The seismic-
force-resisting systems in structures assigned to Seismic
Design Category C, D, E or F, in accordance with Section
1613.
Exception: Requirements for the seismic-force-resist-
ing system are permitted to be excluded from the state-
ment of special inspections for steel systems in structures
assigned to Seismic Design Category C that are not spe-
cifically detailed for seismic resistance, with a response
modification coefficient, /?, of 3 or less, excluding canti-
lever column systems.
1705A.3.2 Designated seismic systems. Designated seis-
mic systems in structures assigned to Seismic Design Cate-
gory D, E or F.
1705A.3.3 Seismic Design Category C. The following
additional systems and components in structures assigned
to Seismic Design Category C:
1. Heating, ventilating and air-conditioning (HVAC)
ductwork containing hazardous materials and
anchorage of such ductwork.
2. Piping systems and mechanical units containing
flammable, combustible or highly toxic materials,
3. Anchorage of electrical equipment used for emer-
gency or standby power systems.
1705A.3.4 Seismic Design Category D. The following
additional systems and components in structures assigned
to Seismic Design Category D:
1. Systems required for Seismic Design Category C.
2. Exterior wall panels and their anchorage.
3. Suspended ceiling systems and their anchorage.
4. Access floors and their anchorage.
5. Steel storage racks and their anchorage, where the
importance factor is equal to 1.5 in accordance with
Section 15.5.3 of ASCE 7.
1705A.3.5 Seismic Design Category E or F. The following
additional systems and components in structures assigned
to Seismic Design Category E or F:
1, Systems required for Seismic Design Categories C
and D.
2. Electrical equipment.
1705A.3.6 Seismic requirements in the statement of special
inspections. When Sections 1705A.3 through 1705A.3.5 spec-
ify that seismic requirements be included, the statement of spe-
cial inspections shall identify the following:
1. The designated seismic systems and seismic-force-
resisting systems that are subject to special inspec-
tions in accordance with Sections 1705 A. 3 through
1705A.3.5.
2. The additional special inspections and testing to be
provided as required by Sections 1707A and 1708A
and other applicable sections of this code, including
the applicable standards referenced by this code.
1705A.4 Wind resistance. The statement of special inspec-
tions shall include wind requirements for structures con-
structed in the following areas:
1. In wind Exposure Category B, where the 3-second-gust
basic wind speed is 120 miles per hour (mph) (52.8 m/s) or
greater.
2. In wind Exposure Category C or D, where the 3-second-
gust basic wind speed is 1 10 mph (49 m/s) or greater.
1705A.4.1 Wind requirements in the statement of special
inspections. When Section 1705 A. 4 specifies that wind
requirements be included, the statement of special inspec-
tions shall identify the main wind-force-resisting systems
and wind-resisting components subject to special inspec-
tions as specified in Section 1705A.4.2.
1705A.4.2 Detailed requirements. The statement of spe-
cial inspections shall include at least the following systems
and components:
1 . Roof cladding and roof framing connections.
2. Wall connections to roof and floor diaphragms and
framing.
3. Roof and floor diaphragm systems, including collec-
tors, drag struts and boundary elements.
4. Vertical wind-force-resisting systems, including
braced frames, moment frames and shear walls.
5 . Wind-force-resisting system connections to the foun-
dation.
6. Fabrication and installation of systems or compo-
nents required to meet the impact-resistance require-
ments of Section 1609.1.2.
Exception: Fabrication of manufactured systems or com-
ponents that have a label indicating compliance with the
wind-load and impact-resistance requirements of this
code.
166
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
SECTION 1706 A
SPECIAL INSPECTIONS FOR
WIND REQUIREMENTS
1706A.1 Special inspections for wind requirements. Special
inspections itemized in Sections 1706A.2 through 1706A.4,
unless exempted by the exceptions to Section 1704A.1, are
required for buildings and structures constructed in the follow-
ing areas:
1. In wind Exposure Category B, where the 3 -second-gust
basic wind speed is 120 miles per hour (52.8 m/sec) or
greater.
2. In wind Exposure Categories C or D, where the 3-sec-
ond-gust basic wind speed is 110 mph (49 m/sec) or
greater.
1706A,2 Structural wood. Continuous special inspection is
required during field gluing operations of elements of the main
windforce-resisting system. Periodic special inspection is
required for nailing, bolting, anchoring and other fastening of
components within the main windforce-resisting system,
including wood shear walls, wood diaphragms, drag struts,
braces and hold-downs.
Exception: Special inspection is not required for wood
shear walls, shear panels and diaphragms, including nailing,
bolting, anchoring and other fastening to other components
of the main windforce-resisting system, where the fastener
spacing of the sheathing is more than 4 inches (102 mm) on
center.
1706A.3 Cold-formed steel light-frame construction. Peri-
odic special inspection is required during welding operations
of elements of die main windforce-resisting system. Periodic
special inspection is required for screw attachment, bolting,
anchoring and other fastening of components within the main
windforce-resisting system, including shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs.
Exception: Special inspection is not required for
cold-formed steel hght-frame shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs where
either of the following apply:
1. The sheathing is gypsum board or fiberboard.
2. The sheathing is wood structural panel or steel sheets
on only one side of the shear wall, shear panel or dia-
phragm assembly and the fastener spacing of the
sheathing is more than 4 inches (102 mm) on center
(o.c).
1706A.4 Wind-resisting components. Periodic special
inspection is required for the following systems and compo-
nents:
1. Roof cladding.
2. Wall cladding.
SECTION 1707A
SPECIAL INSPECTIONS FOR
SEISMIC RESISTANCE
1707A.1 Special inspections for seismic resistance. Special
inspections itemized in Sections 1707A.2 through 1707A.9,
unless exempted by the exceptions of Section 1704A.1,
1705A.3, or 1705A.3.1, are required for the following:
1. The seismic-force-resisting systems in structures
assigned to Seismic Design Category C, D, E or F, as
determined in Section 1613.
2. Designated seismic systems in structures assigned to
Seismic Design Category D, E or F.
3. Architectural, mechanical and electrical components in
structures assigned to Seismic Design Category C, D, E
or F that are required in Sections 1707A.6 and 1707A.7.
1707/1.2 Structural steel. Special inspection for structural
steel shall be in accordance with the quality assurance plan
requirements of AISC 341.
Exceptions:
1. Special inspections of structural steel in structures
assigned to Seismic Design Category C that are not
specifically detailed for seismic resistance, with a
response modification coefficient, R, of 3 or less,
excluding cantilever column systems.
2. For ordinary moment frames, ultrasonic and mag-
netic particle testing of complete joint penetration
groove welds are only required for demand critical
welds.
1707A.3 Structural wood. Continuous special inspection is
required during field gluing operations of elements of the seis-
mic-force-resisting system. Periodic special inspection is
required for nailing, bolting, anchoring and other fastening of
components within the seismic-force-resisting system, includ-
ing wood shear walls, wood diaphragms, drag struts, braces,
shear panels and hold-downs.
Exception: Special inspection is not required for wood
shearwalls, shear panels and diaphragms, including nailing,
bolting, anchoring and other fastening to other components
of the seismic-force-resisting system, where the fastener
spacing of the sheathing is more than 4 inches (102 mm) on
center (o.c.)
1707A.4 Cold-formed steel light-frame construction. Peri-
odic special inspection is required during welding operations
of elements of the seismic-force-resisting system. Periodic
special inspection is required for screw attachment, bolting,
anchoring and other fastening of components within the seis-
mic-force-resisting system, including shear walls, braces, dia-
phragms, collectors (drag struts) and hold-downs.
1707A.5 Storage racks and access floors. Periodic special
inspection is required during the anchorage of access floors
and storage racks 8 feet (2438 mm) or greater in height in struc-
tures assigned to Seismic Design Category D, E or F.
1707A.6 Architectural components. Periodic special inspec-
tion during the erection and fastening of exterior cladding, inte-
rior and exterior nonbearing walls and interior and exterior
2010 CALIFORNIA BUILDING CODE
167
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
veneer in structures assigned to Seismic Design Category D, E
orF.
Exception: [DSA-SS & DSA-SS/CC] Special inspection is
not required for interior nonbearing walls weighing 15 psf
(73.5 N/m^) or less.
1707A.7 Mechanical and electrical components. Special
inspection for mechanical and electrical equipment shall be as
follows:
1 . Periodic special inspection is required during the anchor-
age of electrical equipment for emergency or standby
power systems in structures assigned to Seismic Design
Category C, D, E or F;
2. Periodic special inspection is required during the instal-
lation of anchorage of other electrical equipment in
structures assigned to Seismic Design Category E or F;
3 . Periodic special inspection is required during installation
of piping systems intended to carry flammable, combus-
tible or highly toxic contents and their associated
mechanical units in structures assigned to Seismic
Design Category C, D, E or F;
4. Periodic special inspection is required during the instal-
lation of HVAC ductwork that will contain hazardous
materials in structures assigned to Seismic Design Cate-
gory C, D, E or F; and
5. Periodic special inspection is required during the instal-
lation of vibration isolation systems in structures
assigned to Seismic Design Category C, D, E or F where
the construction documents require a nominal clearance
of V4 inch (6.4 mm) or less between the equipment sup-
port frame and restraint.
1707A.8 Designated seismic system verifications. The spe-
cial inspector shall examine designated seismic systems requir-
ing seismic qualification in accordance with Section 1708A.4
and verify that the label, anchorage or mounting conforms to
the certificate of compliance,
1707 A,9 Seismic isolation and damping systems. Periodic
special inspection is required during the fabrication and instal-
lation of isolator units and damping devices. Continuous spe-
cial inspection is required for prototype and production testing
of isolator units and damping devices.
SECTION 17084
STRUCTURAL TESTING FOR
SEISMIC RESISTANCE
1708A.1 Testing and qualification for seismic resistance.
The testing and qualification specified in Sections 1708A.2
through 1708A.5, unless exempted from special inspections by
the exceptions of Section 1704A.1, 1705A.3 or 1705A.3.1 are
required as follows:
1. The seismic-force-resisting systems in structures
assigned to Seismic Design Category D, E or F, as deter-
mined in Section 161 3A shall meet the requirements of
Sections 1708A.2 and 1708A.3, as applicable.
2. Designated seismic systems in structures assigned to
Seismic Design Category D, E or F subject to the special
certification requirements of ASCE 7 Section 13.2.2 are
required to be tested in accordance with Section
1708A.4.
3. Architectural, mechanical and electrical components in
structures assigned to Seismic Design Category D, E or F
are required to be tested in accordance with Section
1708A.4 where the general design requirements of
ASCE 7 Section 13.2. 1, Item 2 for manufacturer's certif-
ication are satisfied by testing.
4. The seismic isolation system in seismically isolated
structures and damping devices shall meet the testing
requirements of Section 1708A.5.
1708A.2 Concrete reinforcement. Where reinforcement
complying with ASTM A 615 is used to resist earth-
quake-induced flexural and axial forces in special moment
frames, special structural walls and coupling beams connecting
special structural walls, in structures assigned to Seismic
Design Category B, C, D, E or F as determined in Section 1613,
the reinforcement shall comply with Section 21.1.5.2 of ACI
318. Certified mill test reports shall be provided for each ship-
ment of such reinforcement. Where reinforcement complying
with ASTM A 615 is to be welded, chemical tests shall be per-
formed to determine weldability in accordance with Section
3.5.2 of ACI 318.
1708A.3 Structural steel. Testing for structural steel shall be
in accordance with the quality assurance plan requirements of
AISC341.
Exception: For ordinary moment frames, ultrasonic and
magnetic particle testing of complete joint penetration
groove welds are only required for demand critical welds.
1708A.4 Seismic certification of nonstructural compo-
nents. The registered design professional shall state the appli-
cable seismic certification requirements for nonstructural
components and designated seismic systems on the construc-
tion documents.
1 . The manufacturer of each designated seismic system
components subject to the provisions of ASCE 7 Section
13.2.2 shall test or analyze the component and its mount-
ing system or anchorage and submit a certificate of com-
pliance for review and acceptance by the registered
design professional responsible for the design of the des-
ignated seismic system and for approval by the building
official. Certification shall be based on an actual test on a
shake table, by three-dimensional shock tests, by an ana-
lytical method using dynamic characteristics and forces,
by the use of experience data (i.e., historical data demon-
strating acceptable seismic performance) or by more rig-
orous analysis providing for equivalent safety.
[OSHPD 1 & 4] Active or energized components shall
be certified exclusively on the basis of approved shake
table testing in accordance with ASCE 7 Section 13.2.5
or experience data in accordance with ASCE 7 Section
13,2,6 unless it can be shown that the component is
inherently rugged by comparison with similar seismi-
cally certified components.
Unless specified otherwise in the test standard, a mini-
mum of two tests are required. Where a range of products
168
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
are tested, the two tests can be on different size products
as required by design changes in the internal structures.
Exception: When a single product (and not a product
line with more than one product with variations) is
certified and manufacturing process is ISO 9001 cer-
tified, one dynamic test shall be permitted.
For a multicomponent system, where active or ener-
gized components are certified by tests or experience
data, connecting elements, attachments and supports
can be justified by supporting analysis.
Special seismic certification in accordance withASCE
7 Section 13.2.2 shall be required for the following sys-
tems, equipment, and components, unless specified oth-
erwise by the enforcement agency:
1. Emergency and standby power systems includ-
ing generators, turbines, fuel tanks and auto-
matic transfer switches
2. Elevator equipment (excluding elevator cabs)
3. Components with hazardous contents (excluding
pipes, ducts, and underground tanks)
4. Smoke control fans
5. Exhaust fans
6. Switchgear
7. Motor control centers
8. X-Ray machines in fluoroscopy rooms
9. CT (computerized tomography) Scanners
10. Air conditioning units
11. Air handling un its
12. Chillers
13. Cooling towers (excluding cooling towers
designed as nonbuilding structures)
14. Transformers
15. Electrical substations
16. UPS (Inverters) and associated batteries
17. Distribution panels including electrical panel
boards
18. Control panels including fire alarm, fire sup-
pression, preaction, and auxiliary or remote
power supplies
Exceptions:
1. Equipment and components installed in
nonconforming buildings, unless the equip-
ment or component provides a service/system
or utility to conforming buildings, or building is
designated as SPC 3 or higher.
2. Equipment and components weighing not more
than 20 lbs supported directly on structures
(and not mounted on other equipment or com-
ponents) with supports and attachments in
accordance with ASCE 7 Chapter 13 as modi-
fied by Section 161 5 A.
2. Manufacturer's certification of compliance for the gen- <
eral design requirements of ASCE 7 Section 13.2.1 shall
be based on analysis, testing or experience data.
1708A.5 Seismically isolated structures and structures with
damping devices. For required system tests, see Sections 17.8
and 18.9 oi ASCEl .
Prototype and production testing and associated acceptance
criteria for isolator units and damping devices shall be subject
to preapproval by the building official. Testing exemption for
similar units shall require approval by the building official
SECTION 17094
CONTRACTOR RESPONSIBILITY
1709A.1 Contractor responsibility. Each contractor respon-
sible for the construction of a main wind- or seis-
mic-force-resisting system, designated seismic system or a
wind- or seismic-resisting component listed in the statement of
special inspections shall submit a written statement of respon-
sibility to the building official and the owner prior to the com-
mencement of work on the system or component. The
contractor's statement of responsibility shall contain acknowl-
edgement of awareness of the special requirements contained
in the statement of special inspection.
SECTION 17104
STRUCTURAL OBSERVATIONS
1710A.1 General. Where required by the provisions of Section
1710A.2 or 1710A.3, the owner shall employ a registered
design professional to perform structural observations as
defined in Section 1702A.
Prior to the commencement of observations, the structural
observer shall submit to the building official a written state-
ment identifying the frequency and extent of structural obser-
vations.
At the conclusion of the work included in the permit, the
structural observer shall submit to the building official a written
statement that the site visits have been made and identify any
reported deficiencies which, to the best of the structural
observer's knowledge, have not been resolved.
1710A.2 Structural observations for seismic resistance.
Observation of the construction shall be provided by the archi-
tect or engineer in responsible charge as set forth in Title 24,
Parti.
1710A.3 Structural observations for wind requirements.
Observation of the construction shall be provided by the archi-
tect or engineer in responsible charge as set forth in Title 24,
Part 1.
SECTION 17114
DESIGN STRENGTHS OF MATERIALS
1711A.1 Conformance to standards. The design strengths
and permissible stresses of any structural material that are iden-
tified by a manufacturer's designation as to manufacture and
grade by mill tests, or the strength and stress grade is otherwise
confirmed to the satisfaction of the building official, shall con-
form to the specifications and methods of design of accepted
<
<
2010 CALIFORNIA BUILDING CODE
169
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
engineering practice or the approved rules in the absence of
applicable standards.
171 lA .2 New materials. For materials that are not specifically
provided for in this code, the design strengths and permissible
stresses shall be established by tests as provided for in Section
1712A.
SECTION 17124
ALTERNATIVE TEST PROCEDURE
1712A.1 General. In the absence of approved rules or other
approved standards, the building official shall make, or cause to
be made, the necessary tests and investigations; or the building
official shall accept duly authenticated reports from approved
agencies in respect to the quality and manner of use of new
materials or assemblies as provided for in Section 104. 1 1. The
cost of all tests and other investigations required under the pro-
visions of this code shall be borne by the applicant.
SECTION 17134
TEST SAFE LOAD
1713A.1 Where required. Where proposed construction is not
capable of being designed by approved engineering analysis,
or where proposed construction design method does not com-
ply with the applicable material design standard, the system of
construction or the structural unit and the connections shall be
subjected to the tests prescribed in Section 1715A. The build-
ing official shall accept certified reports of such tests conducted
by an approved testing agency, provided that such tests meet
the requirements of this code and approved procedures.
SECTION 17144
IN-SITU LOAD TESTS
1714A.1 GeneraL Whenever there is a reasonable doubt as to
the stability or load-bearing capacity of a completed building,
structure or portion thereof for the expected loads, an engineer-
ing assessment shall be required. The engineering assessment
shall involve either a structural analysis or an in-situ load test,
or both. The structural analysis shall be based on actual mate-
rial properties and other as-built conditions that affect stability
or load-bearing capacity, and shall be conducted in accordance
with the applicable design standard. If the structural assess-
ment determines that the load-bearing capacity is less than that
required by the code, load tests shall be conducted in accor-
dance with Section 1714A.2. If the building, structure or por-
tion thereof is found to have inadequate stability or
load-bearing capacity for the expected loads, modifications to
ensure structural adequacy or the removal of the inadequate
construction shall be required.
1714A.2 Test standards. Structural components and assem-
blies shall be tested in accordance with the appropriate material
standards listed in Chapter 35. In the absence of a standard that
contains an applicable load test procedure, the test procedure
shall be developed by a registered design professional and
approved. The test procedure shall simulate loads and condi-
tions of application that the completed structure or portion
thereof will be subjected to in normal use.
1714A.3 In-situ load tests. In-situ load tests shall be con-
ducted in accordance with Section 1714A.3.1 or 1714A.3.2and
shall be supervised by a registered design professional The test
shall simulate the applicable loading conditions specified in
Chapter 16 as necessary to address the concerns regarding
structural stability of the building, structure or portion thereof.
1714A.3.1 Load test procedure specified. Where a stan-
dard listed in Chapter 35 contains an applicable load test
procedure and acceptance criteria, the test procedure and
acceptance criteria in the standard shall apply. In the
absence of specific load factors or acceptance criteria, the
load factors and acceptance criteria in Section 1714A.3.2
shall apply.
17144.3.2 Load test procedure not specified. In the
absence of applicable load test procedures contained within
a standard referenced by this code or acceptance criteria for
a specific material or method of construction, such existing
structure shall be subjected to a test procedure developed by
a registered design professional that simulates applicable
loading and deformation conditions. For components that
are not a part of the seismic-load-resisting system, the test
load shall be equal to two times the unfactored design loads.
The test load shall be left in place for a period of 24 hours.
The structure shall be considered to have successfully met
the test requirements where the following criteria are satis-
fied:
1 . Under the design load, the deflection shall not exceed
the limitations specified in Section 1604.3.
2. Within 24 hours after removal of the test load, the
structure shall have recovered not less than 75 percent
of the maximum deflection,
3. During and immediately after the test, the structure
shall not show evidence of failure.
SECTION 17154
PRECONSTRUCTION LOAD TESTS
1715A.1 General. In evaluating the physical properties of
materials and methods of construction that are not capable of
being designed by approved engineering analysis or do not
comply with applicable material design standards Usted in
Chapter 35, the structural adequacy shall be predetermined
based on the load test criteria established in this section.
1715A.2 Load test procedures specified. Where specific load
test procedures, load factors and acceptance criteria are
included in the applicable design standards listed in Chapter
35, such test procedures, load factors and acceptance criteria
shall apply. In the absence of specific test procedures, load fac-
tors or acceptance criteria, the corresponding provisions in
Section 1715A.3 shall apply.
1715A.3 Load test procedures not specified. Where load test
procedures are not specified in the applicable design standards
listed in Chapter 35, the load-bearing and deformation capacity
of structural components and assemblies shall be determined
on the basis of a test procedure developed by a registered
design professional that simulates applicable loading and
deformation conditions. For components and assemblies that
170
2010 CALIFORNIA BUILDING CODE
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
are not a part of the seismic-force-resisting system, the test
shall be as specified in Section 17 15A.3 . 1 . Load tests shall sim-
ulate the applicable loading conditions specified in Chapter 16.
1715A.3.1 Test procedure. The test assembly shall be sub-
jected to an increasing superimposed load equal to not less
than two times the superimposed design load. The test load
shall be left in place for a period of 24 hours. The tested
assembly shall be considered to have successfully met the
test requirements if the assembly recovers not less than 75
percent of the maximum deflection within 24 hours after the
removal of the test load. The test assembly shall then be
reloaded and subjected to an increasing superimposed load
until either structural failure occurs or the superimposed
load is equal to two and one-half times the load at which the
deflection limitations specified in Section 1715A.3.2 were
reached, or the load is equal to two and one-half times the
superimposed design load. In the case of structural compo-
nents and assemblies for which deflection limitations are
not specified in Section 1715A.3.2, the test specimen shall
be subjected to an increasing superimposed load until struc-
tural failure occurs or the load is equal to two and one-half
times the desired superimposed design load. The allowable
superimposed design load shall be taken as the lesser of:
1. The load at the deflection limitation given in Section
1715A.3.2.
2. The failure load divided by 2.5.
3. The maximum load applied divided by 2.5.
17 ISA .3.2 Deflection. The deflection of structural mem-
bers under the design load shall not exceed the limitations in
Section 1604.3.
1715A.4 Wall and partition assemblies. Load-bearing wall
and partition assemblies shall sustain the test load both with
and without window framing. The test load shall include all
design load components. Wall and partition assemblies shall be
tested both with and without door and window framing.
1715A.5 Exterior window and door assemblies. The design
pressure rating of exterior windows and doors in buildings
shall be determined in accordance with Section 1715A.5.1 or
1715A.5.2.
Exception: Structural wind load design pressures for win-
dow units smaller than the size tested in accordance with
Section 1715A.5.1 or 1715A.5.2 shall be permitted to be
higher than the design value of the tested unit provided such
higher pressures are determined by accepted engineering
analysis. All components of the small unit shall be the same
as the tested unit. Where such calculated design pressures
are used, they shall be validated by an additional test of the
window unit having the highest allowable design pressure.
1715A.5.1 Exterior windows and doors. Exterior windows
and sliding doors shall be tested and labeled as conforming to
AAMAAVDMA/CSA101/I.S.2/A440. The label shall state
the name of the manufacturer, the approved labeling agency
and the product designation as specified in AAMA/
WDMA/CSA101/I.S.2/A440. Exterior side-hinged doors
shall be tested and labeled as conforming to AAMA/
WDMA/CSA101/I.S.2/A440 or comply with Section
1715A.5.2. Products tested and labeled as conforming to
AAMA/WDMA/CSA 101/I.S.2/A440 shall not be subject to
the requirements of Sections 2403.2 and 2403.3.
1715A.5.2 Exterior windows and door assemblies not
provided for in Section 1715A.5.1. Exterior window and
door assemblies shall be tested in accordance with ASTM E
330. Structural performance of garage doors shall be deter-
mined in accordance with either ASTM E 330 or
ANSI/DASMA 108, and shall meet the acceptance criteria
of ANSI/DASMA 108. Exterior window and door assem-
blies containing glass shall comply with Section 2403. The
design pressure for testing shall be calculated in accordance
with Chapter 16. Each assembly shall be tested for 10 sec-
onds at a load equal to 1.5 times the design pressure.
1715A.6 Test specimens. Test specimens and construction
shall be representative of the materials, workmanship and
details normally used in practice. The properties of the materi-
als used to construct the test assembly shall be determined on
the basis of tests on samples taken from the load assembly or on
representative samples of the materials used to construct the
load test assembly. Required tests shall be conducted or wit-
nessed by an approved agency.
SECTION 17164
MATERIAL AND TEST STANDARDS
1716A.1 Test standards for joist hangers and connectors.
1716A.1.1 Test standards for joist hangers. The vertical
load-bearing capacity, torsional moment capacity and
deflection characteristics of joist hangers shall be deter-
mined in accordance with ASTM D 1761 using lumber hav-
ing a specific gravity of 0.49 or greater, but not greater than
0.55, as determined in accordance with AF&PA NDS for
the joist and headers.
Exception: The joist length shall not be required to
exceed 24 inches (610 mm).
1716A.1.2 Vertical load capacity for joist hangers. The
vertical load capacity for the joist hanger shall be deter-
mined by testing a minimum of three joist hanger assem-
blies as specified in ASTM D 1761. If the ultimate vertical
load for any one of the tests varies more than 20 percent
from the average ultimate vertical load, at least three addi-
tional tests shall be conducted. The allowable vertical load
of the joist hanger shall be the lowest value determined from
the following:
1 . The lowest ultimate vertical load for a single hanger
from any test divided by three (where three tests are
conducted and each ultimate vertical load does not
vary more than 20 percent from the average ultimate
vertical load).
2. The average ultimate vertical load for a single hanger
from all tests divided by three (where six or more tests
are conducted).
3. The average from all tests of the vertical loads that
produce a vertical movement of the joist with respect
to the header of Vg inch (3.2 mm).
2010 CALIFORNIA BUILDING CODE
171
STRUCTURAL TESTS AND SPECIAL INSPECTIONS
4. The sum of the allowable design loads for nails or
other fasteners utilized to secure the joist hanger to the
wood members and allowable bearing loads that con-
tribute to the capacity of the hanger.
5. The allowable design load for the wood members
forming the connection.
1716A.1.3 Torsional moment capacity for joist hangers.
The torsional moment capacity for the joist hanger shall be
determined by testing at least three joist hanger assemblies
as specified in ASTM D 1761. The allowable torsional
moment of the joist hanger shall be the average torsional
moment at which the lateral movement of the top or bottom
of the joist with respect to the original position of the joist is
Vg inch (3.2 mm).
1716A.1.4 Design value modifications for joist hangers.
Allowable design values for joist hangers that are deter-
mined by Item 4 or 5 in Section 1716A.1.2 shall be permit-
ted to be modified by the appropriate duration of loading
factors as specified in AF&PA NDS but shall not exceed the
direct loads as determined by Item 1, 2 or 3 in Section
1716A.1.2. Allowable design values determined by Item 1,
2 or 3 in Section 1716A.1.2 shall not be modified by dura-
tion of loading factors.
1716A.2 Concrete and clay roof tiles.
1716A.2.1 Overturning resistance. Concrete and clay roof
tiles shall be tested to determine their resistance to overturn-
ing due to wind in accordance with SBCCI SSTD 11 and
Chapter 15.
1716A.2.2 Wind tunnel testing. When roof tiles do not sat-
isfy the limitations in Chapter 16 for rigid tile, a wind tunnel
test shall be used to determine the wind characteristics of the
concrete or clay tile roof covering in accordance with
SBCCI SSTD 11 and Chapter 15.
172
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 18 - SOILS AND FOUNDATIONS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire cliapter
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
1801.2
X
X
1803.1.1 -1803.1.1.3
X
X
1803.2
X
1803.6
X
1803.7
X
1810.3.1.5.1
X
1810.3.10.4.1
X
2010 CALIFORNIA BUILDING CODE
173
174 2010 CALIFORNIA BUILDING CODE
CHAPTER 18
SOILS AND FOUNDATIONS
This chapter has been revised in its entirety; there will be no marginal markings.
SECTION 1801
GENERAL
1801.1 Scope. The provisions of this chapter shall apply to
building and foundation systems.
1801.2 Design basis. Allowable bearing pressures, allowable
stresses and design formulas provided in this chapter shall be
used with the allowable stress design load combinations speci-
fied in Section 1605.3. The quality and design of materials used
structurally in excavations and foundations shall comply with
the requirements specified in Chapters 16, 19, 21, 22 and 23 of
this code. Excavations and fills shall also comply with Chapter
33.
[HCD 1] For limited-density owner-built rural dwellings,
pier foundations, stone masonry footings and foundations,
pressure-treated lumber, poles or equivalent foundation mate-
rials or designs may be used, provided that the bearing is suffi-
cient for the purpose intended.
SECTION 1802
DEFINITIONS
1802.1 Definitions. The following words and terms shall, for
the purposes of this chapter, have the meanings shown herein.
DEEP FOUNDATION. A deep foundation is a foundation
element that does not satisfy the definition of a shallow founda-
tion.
DRILLED SHAFT. A drilled shaft is a cast-in-place deep
foundation element constructed by drilling a hole (with or
without permanent casing) into soil or rock and filling it with
fluid concrete.
Socketed drilled shaft. A socketed drilled shaft is a drilled
shaft with a permanent pipe or tube casing that extends
down to bedrock and an uncased socket drilled into the bed-
rock.
HELICAL PILE. Manufactured steel deep foundation ele-
ment consisting of a central shaft and one or more helical bear-
ing plates. A helical pile is installed by rotating it into the
ground. Each helical bearing plate is formed into a screw thread
with a uniform defined pitch.
MICROPILE. A micropile is a bored, grouted-in-place deep
foundation element that develops its load-carrying capacity by
means of a bond zone in soil, bedrock or a combination of soil
and bedrock.
SHALLOW FOUNDATION. A shallow foundation is an
individual or strip footing, a mat foundation, a slab-on-grade
foundation or a similar foundation element.
SECTION 1803
GEOTECHNICAL INVESTIGATIONS
1803.1 General. Geotechnical investigations shall be con-
ducted in accordance with Section 1803.2 and reported in
accordance with Section 1803.6. Where required by the build-
ing official or where geotechnical investigations involve in-situ
testing, laboratory testing or engineering calculations, such
investigations shall be conducted by a registered design profes-
sional,
1803,1,1 General and where required for applications
listed in Section 1.8.2,1,1 regulated by the Department of
Housing and Community Development, [HCD 1] Founda-
tion and soils investigations shall be conducted in confer-
ence with Health and Safety Code Sections 17953 through
17955 as summarized below.
1803.1.1.1 Preliminary soil report. Each city, county, or
city and county shall enact an ordinance which requires
a preliminary soil report, prepared by a civil engineer
who is registered by the state. The report shall be based
upon adequate test borings or excavations, of every sub-
division, where a tentative and final map is required pur-
suant to Section 66426 of the Government Code,
The preliminary soil report may be waived if the build-
ing department of the city, county or city and county, or
other enforcement agency charged with the administra-
tion and enforcement of the provisions of this part, shall
determine that, due to the knowledge such department
has as to the soil qualities of the soil of the subdivision or
lot, no preliminary analysis is necessary,
1803.1.1.2 Soil investigation by lot, necessity, prepara-
tion^ and recommendations. If the preliminary soil
report indicates the presence of critically expansive soils
or other soil problems which, if not corrected, would lead
to structural defects, such ordinance shall require a soil
investigation of each lot in the subdivision.
The soil investigation shall be prepared by a civil engi-
neer who is registered in this state. It shall recommend
corrective action which is likely to prevent structural
damage to each dwelling proposed to be constructed on
the expansive soil.
1803.1.1.3 Approval, building permit conditions,
appeal The building department of each city, county or
city and county, or other enforcement agency charged
with the administration and enforcement of the provi-
sions of this part, shall approve the soil investigation if it
determines that the recommended action is likely to pre-
vent structural damage to each dwelling to be con-
structed. As a condition to the building permit, the
ordinance shall require that the approved recommended
2010 CALIFORNIA BUILDING CODE
175
SOILS AND FOUNDATIONS
action be incorporated in the construction of each dwell-
ing. Appeal from such determination shall be to the local
appeals board.
1803.2 Investigations required. Geotechnical investigations
shall be conducted in accordance with Sections 1 803.3 through
1803.5.
Exception: The building official shall be permitted to waive
the requirement for a geotechnical investigation where sat-
isfactory data from adjacent areas is available that demon-
strates an investigation is not necessary for any of the
conditions in Sections 1803.5.1 through 1803.5.6 and Sec-
tions 1803.5.10 and 1803.5.11.
[OSHPD 2] Geotechnical reports are not required for
one-story, wood-frame and light-steel-frame buildings
of Type V construction and 4,000 square feet (371 m^) or
less in floor area, not located within Earthquake Fault
Zones or Seismic Hazard Zones as shown in the most
recently published nmps from the California Geological
Survey (CGS). Allowable foundation and lateral soil
pressure values may be determined from Table 1804.2.
1803.3 Basis of investigation. Soil classification shall be
based on observation and any necessary tests of the materials
disclosed by borings, test pits or other subsurface exploration
made in appropriate locations. Additional studies shall be
made as necessary to evaluate slope stability, soil strength,
position and adequacy of load-bearing soils, the effect of mois-
ture variation on soil-bearing capacity, compressibility, lique-
faction and expansiveness.
1803.3.1 Scope of investigation. The scope of the
geotechnical investigation including the number and types
of borings or soundings, the equipment used to drill or sam-
ple, the in- situ testing equipment and the laboratory testing
program shall be determined by a registered design profes-
sional.
1803.4 Qualified representative. The investigation procedure
and apparatus shall be in accordance with generally accepted
engineering practice. The registered design professional shall
have a fully qualified representative on site during all boring or
sampling operations.
1803.5 Investigated conditions. Geotechnical investigations
shall be conducted as indicated in Sections 1803.5.1 through
1803.5.12.
1803.5.1 Classification. Soil materials shall be classified in
accordance with ASTM D 2487.
1803.5.2 Questionable soil. Where the classification,
strength or compressibility of the soil is in doubt or where a
load-bearing value superior to that specified in this code is
claimed, the building official shall be permitted to require
that a geotechnical investigation be conducted.
1803.5.3 Expansive soil. In areas likely to have expansive
soil, the building official shall require soil tests to determine
where such soils do exist.
Soils meeting all four of the following provisions shall be
considered expansive, except that tests to show compliance
with Items 1, 2 and 3 shall not be required if the test pre-
scribed in Item 4 is conducted:
1. Plasticity index (PI) of 15 or greater, determined in
accordance with ASTM D 43 1 8.
2. More than 10 percent of the soil particles pass a No.
200 sieve (75 |im), determined in accordance with
ASTM D 422.
3. More than 10 percent of the soil particles are less than
5 micrometers in size, determined in accordance with
ASTM D 422.
4. Expansion index greater than 20, determined in
accordance with ASTM D 4829.
1803.5.4 Ground-water table. A subsurface soil investiga-
tion shall be performed to determine whether the existing
ground- water table is above or within 5 feet (1524 mm)
below the elevation of the lowest floor level where such
floor is located below the finished ground level adjacent to
the foundation.
Exception: A subsurface soil investigation to determine
the location of the ground-water table shall not be
required where waterproofing is provided in accordance
with Section 1805.
1803.5.5 Deep foundations. Where deep foundations will
be used, a geotechnical investigation shall be conducted and
shall include all of the following, unless sufficient data upon
which to base the design and installation is otherwise avail-
able:
1. Recommended deep foundation types and installed
capacities.
2. Recommended center-to-center spacing of deep
foundation elements.
3. Driving criteria.
4. Installation procedures.
5. Field inspection and reporting procedures (to include
procedures for verification of the installed bearing
capacity where required).
6. Load test requirements.
7. Suitability of deep foundation materials for the
intended environment.
8. Designation of bearing stratum or strata.
9. Reductions for group action, where necessary.
1803.5.6 Rock strata. Where subsurface explorations at the
project site indicate variations or doubtful characteristics in
the structure of the rock upon which foundations are to be
constructed, a sufficient number of borings shall be made to
a depth of not less than 10 feet (3048 mm) below the level of
the foundations to provide assurance of the soundness of the
foundation bed and its load-bearing capacity.
1803.5.7 Excavation near foundations. Where excavation
will remove lateral support from any foundation, an investi-
176
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
gation shall be conducted to assess the potential conse-
quences and address mitigation measures.
1803.5.8 Compacted fill material. Where shallow founda-
tions will bear on compacted fill material more than 12
inches (305 mm) in depth, a geotechnical investigation shall
be conducted and shall include all of the following:
1 . Specifications for the preparation of the site prior to
placement of compacted fill material.
2. Specifications for material to be used as compacted
fill.
3. Test methods to be used to determine the maximum
dry density and optimum moisture content of the
material to be used as compacted fill,
4. Maximum allowable thickness of each lift of com-
pacted fill material.
5. Field test method for determining the in-place dry
density of the compacted fill.
6. Minimum acceptable in-place dry density expressed
as a percentage of the maximum dry density deter-
mined in accordance with Item 3.
7. Number and frequency of field tests required to deter-
mine compliance with Item 6.
1803.5.9 Controlled low-strength material (CLSM).
Where shallow foundations will bear on controlled low-
strength material (CLSM), a geotechnical investigation
shall be conducted and shall include all of the following:
1 . Specifications for the preparation of the site prior to
placement of the CLSM.
2. Specifications for the CLSM.
3. Laboratory or field test method(s) to be used to deter-
mine the compressive strength or bearing capacity of
the CLSM.
4. Test methods for determining the acceptance of the
CLSM in the field.
5 . Number and frequency of field tests required to deter-
mine compliance with Item 4.
1803.5.10 Alternate setback and clearance. Where set-
backs or clearances other than those required in Section
1 808.7 are desired, the building official shall be permitted to
require a geotechnical investigation by a registered design
professional to demonstrate that the intent of Section 1 808.7
would be satisfied. Such an investigation shall include con-
sideration of material, height of slope, slope gradient, load
intensity and erosion characteristics of slope material.
1803.5.11 Seismic Design Categories C through E For
structures assigned to Seismic Design Category C, D, E or F
in accordance with Section 1613, a geotechnical investiga-
tion shall be conducted, and shall include an evaluation of
all of the following potential geologic and seismic hazards:
1. Slope instability.
2. Liquefaction.
3. Differential settlement.
4. Surface displacement due to faulting or lateral
spreading.
1803.5.12 Seismic Design Categories D through F. For
structures assigned to Seismic Design Category D, E or F in
accordance with Section 1613, the geotechnical investiga-
tion required by Section 1803.5.11, shall also include:
1 . The determination of lateral pressures on foundation
walls and retaining walls due to earthquake motions.
2. The potential for liquefaction and soil strength loss
evaluated for site peak ground accelerations, magni-
tudes and source characteristics consistent with the
design earthquake ground motions. Peak ground
acceleration shall be permitted to be determined
based on a site-specific study taking into account soil
amplification effects, as specified in Chapter 21 of
ASCE 7, or, in the absence of such a study, peak
ground accelerations shall be assumed equal to
5^5/2.5, where Sj^s is determined in accordance with
Section 1613.5,4.
3 . An assessment of potential consequences of liquefac-
tion and soil strength loss, including estimation of dif-
ferential settlement, lateral movement, lateral loads
on foundations, reduction in foundation soil-bearing
capacity, increases in lateral pressures on retaining
walls and flotation of buried structures.
4. Discussion of mitigation measures such as, but not
limited to, ground stabilization, selection of appropri-
ate foundation type and depths, selection of appropri-
ate structural systems to accommodate anticipated
displacements and forces, or any combination of
these measures and how they shall be considered in
the design of the structure.
1803.6 Reporting. Where geotechnical investigations are
required, a written report of the investigations shall be submit-
ted to the building official by the owner or authorized agent at
the time of permit application. This geotechnical report shall
include, but need not be limited to, the following information:
1 . A plot showing the location of the soil investigations.
2. A complete record of the soil boring and penetration
test logs and soil samples.
3. A record of the soil profile.
4. Elevation of the water table, if encountered.
5. Recommendations for foundation type and design cri-
teria, including but not limited to: bearing capacity of
natural or compacted soil; provisions to mitigate the
effects of expansive soils; mitigation of the effects of
liquefaction, differential settlement and varying soil
strength; and the effects of adjacent loads.
6. Expected total and differential settlement.
7. Deep foundation information in accordance with Sec-
tion 1803.5.5.
8 . Special design and construction provisions for founda-
tions of structures founded on expansive soils, as nec-
essary.
2010 CALIFORNIA BUILDING CODE
177
SOILS AND FOUNDATIONS
9. Compacted fill material properties and testing in accor-
dance with Section 1803.5.8.
1 0. Controlled low-strength material properties and testing
in accordance with Section 1803.5.9.
11. [OSHPD 2] The report shall consider the ejfects of
>l I seismic hazard in accordance with Section 1803.7,
1803.7 Engineering geologic reports, [OSHPD 2]
1803.7.1 Geologic and earthquake engineering reports
shall be required for all proposed construction.
Exceptions:
1. Reports are not required for one-story, wood-
frame and light- steel-frame buildings of Type V
construction and 4,000 square feet (371 m^) or less
in floor area, not located within Earthquake Fault
Zones or Seismic Hazard Zones as shown in the
most recently published maps from the California
Geological Survey (CGS); nonstructural, associ-
I I ated structural or voluntary structural alterations
and incidental structural additions or alterations,
and structural repairs for other than earthquake
damage (See Section 3402 A. 1 for definitions of
terms in this section).
2. A previous report for a specific site may be resub-
mitted, provided that a reevaluation is made and
the report is found to be currently appropriate.
1803.7.2 The purpose of the engineering geologic report
shall be to identify geologic and seismic conditions that may
require project mitigations. The reports shall contain data
which provide an assessment of the nature of the site and
potential for earthquake damage based on appropriate
investigations of the regional and site geology, project foun-
dation conditions and the potential seismic shaking at the
site. The report shall be prepared by a California-certified
engineering geologist in consultation with a California-reg-
istered geotechnical engineer
The preparation of the engineering geologic report shall
consider the most recent CGS Note 48; Checklist for the
Review of Engineering Geology and Seismology Reports for
California Public School, Hospitals, and Essential Services
Buildings. In addition, the most recent version of CGS Spe-
cial Publication 42, Fault Rupture Hazard Zones in Califor-
nia, shall be considered for project sites proposed within an
Alquist-Priolo Earthquake Fault Zone. The most recent ver-
sion of CGS Special Publication 117, Guidelines for Evalu-
ating and Mitigating Seismic Hazards in California, shall
be considered for project sites proposed within a Seismic
Hazard Zone. All conclusions shall be fully supported by
satisfactory data and analysis.
In addition to requirements in Sections 1803.5.11 and
1803.5.12, the report shall include, but shall not be limited
to, the following. •
1. Geologic investigation.
2. Evaluation of the known active and potentially active
faults, both regional and local.
3. Ground-motion parameters, as required by Section
1613andASCE7.
SECTION 1804
EXCAVATION, GRADING AND FILL
1504.1 Excavation near foundations. Excavation for any pur-
pose shall not remove lateral support from any foundation
without first underpinning or protecting the foundation against
settlement or lateral translation.
1804.2 Placement of backfilL The excavation outside the
foundation shall be backfilled with soil that is free of organic
material, construction debris, cobbles and boulders or with a
controlled low-strength material (CLSM). The backfill shall be
placed in lifts and compacted in a manner that does not damage
the foundation or the waterproofing or dampproofing material.
Exception: CLSM need not be compacted.
1804.3 Site grading. The ground immediately adjacent to the
foundation shall be sloped away from the building at a slope of
not less than one unit vertical in 20 units horizontal (5 -percent
slope) for a minimum distance of 10 feet (3048 mm) measured
perpendicular to the face of the wall. If physical obstructions or
lot lines prohibit 10 feet (3048 mm) of horizontal distance, a
5-percent slope shall be provided to an approved alternative
method of diverting water away from the foundation. Swales
used for this purpose shall be sloped a minimum of 2 percent
where located within 10 feet (3048 mm) of the building foun-
dation. Impervious surfaces within 10 feet (3048 mm) of the
building foundation shall be sloped a minimum of 2 percent
away from the building.
Exception: Where climatic or soil conditions warrant, the
slope of the ground away from the building foundation shall
be permitted to be reduced to not less than one unit vertical
in 48 units horizontal (2-percent slope).
The procedure used to establish the final ground level adja-
cent to the foundation shall account for additional settlement of
the backfill.
1804.4 Grading and fill in flood hazard areas. In flood haz-
ard areas established in Section 1612.3, grading and/or fill
shall not be approved:
1 . Unless such fill is placed, compacted and sloped to mini-
mize shifting, slumping and erosion during the rise and
fall of flood water and, as applicable, wave action.
2. In floodways, unless it has been demonstrated through
hydrologic and hydraulic analyses performed by a regis-
tered design professional in accordance with standard
engineering practice that the proposed grading or fill, or
both, will not result in any increase in flood levels during
the occurrence of the design flood.
3. In flood hazard areas subject to high- velocity wave
action, unless such fill is conducted and/or placed to
avoid diversion of water and waves toward any building
or structure.
4. Where design flood elevations are specified but
floodways have not been designated, unless it has been
demonstrated that the cumulative effect of the proposed
178
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
flood hazard area encroachment, when combined with
all other existing and anticipated flood hazard area
encroachment, will not increase the design flood eleva-
tion more than 1 foot (305 mm) at any point.
1804.5 Compacted fill material. Where shallow foundations
will bear on compacted fill material, the compacted fill shall
comply with the provisions of an approved geotechnical report,
as set forth in Section 1803.
Exception: Compacted fill material 12 inches (305 mm) in
depth or less need not comply with an approved report, pro-
vided the in-place dry density is not less than 90 percent of
the maximum dry density at optimum moisture content
determined in accordance with ASTM D 1557. The com-
paction shall be verified by special inspection in accordance
with Section 1704.7.
1804.6 Controlled low-strength material (CLSM). Where
shallow foundations will bear on controlled low-strength mate-
rial (CLSM), the CLSM shall comply with the provisions of an
approved geotechnical report, as set forth in Section 1803.
SECTION 1805
DAMPPROOFING AND WATERPROOFING
1805.1 General. Walls or portions thereof that retain earth and
enclose interior spaces and floors below grade shall be water-
proofed and dampproofed in accordance with this section, with
the exception of those spaces containing groups other than resi-
dential and institutional where such omission is not detrimental
to the building or occupancy.
Ventilation for crawl spaces shall comply with Section
1203.4.
1805.1.1 Story above grade plane. Where a basement is
considered a story above grade plane and the finished
ground level adjacent to the basement wall is below the
basement floor elevation for 25 percent or more of the per-
imeter, the floor and walls shall be dampproofed in accor-
dance with Section 1805.2 and a foundation drain shall be
installed in accordance with Section 1805.4,2. The founda-
tion drain shall be installed around the portion of the perim-
eter where the basement floor is below ground level. The
provisions of Sections 1803.5.4, 1805.3 and 1805.4.1 shall
not apply in this case.
1805.1.2 Under-floor space. The finished ground level of
an under-floor space such as a crawl space shall not be
located below the bottom of the footings. Where there is evi-
dence that the ground-water table rises to within 6 inches
(1 52 mm) of the ground level at the outside building perime-
ter, or that the surface water does not readily drain from the
building site, the ground level of the under-floor space shall
be as high as the outside finished ground level, unless an
approved drainage system is provided. The provisions of
Sections 1803.5.4, 1805.2, 1805.3 and 1805.4 shall not
apply in this case.
1805.1.2.1 Flood hazard areas. For buildings and struc-
tures in flood hazard areas as established in Section
1612.3, the finished ground level of an under-floor space
such as a crawl space shall be equal to or higher than the
outside finished ground level on at least one side.
Exception: Under-floor spaces of Group R-3 build-
ings ±at meet the requirements of FEMA/FIA-TB-1 1 .
1805.1.3 Ground- water control. Where the ground- water
table is lowered and maintained at an elevation not less than
6 inches (152 mm) below the bottom of the lowest floor, the
floor and walls shall be dampproofed in accordance with
Section 1805.2. The design of the system to lower the
ground-water table shall be based on accepted principles of
engineering that shall consider, but not necessarily be lim-
ited to, permeability of the soil, rate at which water enters
the drainage system, rated capacity of pumps, head against
which pumps are to operate and the rated capacity of the dis-
posal area of the system.
1805.2 Dampproofing. Where hydrostatic pressure will not
occur as determined by Section 1803.5.4, floors and walls for
other than wood foundation systems shall be dampproofed in
accordance with this section. Wood foundation systems shall
be constructed in accordance with AF&PA PWF.
1805.2.1 Floors. Dampproofing materials for floors shall
be installed between the floor and the base course required
by Section 1805.4.1, except where a separate floor is pro-
vided above a concrete slab.
Where installed beneath the slab, dampproofing shall
consist of not less than 6-mil (0.006 inch; 0.152 mm) poly-
ethylene with joints lapped not less than 6 inches (152 mm),
or other approved methods or materials. Where permitted to
be installed on top of the slab, dampproofing shall consist of
mopped-on bitumen, not less than 4-mil (0.004 inch; 0.102
mm) polyethylene, or other approved methods or materials.
Joints in the membrane shall be lapped and sealed in accor-
dance with the manufacturer's installation instructions.
1805.2.2 Walls. Dampproofing materials for walls shall be
installed on the exterior surface of the wall, and shall extend
from the top of the footing to above ground level.
Dampproofing shall consist of a bituminous material, 3
pounds per square yard (16 N/m^) of acrylic modified
cement, Vg inch (3.2 mm) coat of surface-bonding mortar
complying with ASTM C 887, any of the materials permit-
ted for waterproofing by Section 1805.3.2 or other
approved methods or materials.
1805.2.2.1 Surface preparation of walls. Prior to appli-
cation of dampproofing materials on concrete walls,
holes and recesses resulting from the removal of form
ties shall be sealed with a bituminous material or other
approved methods or materials. Unit masonry walls shall
be parged on the exterior surface below ground level with
not less than Vg inch (9.5 mm) of portland cement mortar.
The parging shall be coved at the footing.
Exception: Parging of unit masonry walls is not
required where a material is approved for direct appli-
cation to the masonry.
1805.3 Waterproofing. Where the ground- water investigation
required by Section 1803.5.4 indicates that a hydrostatic pres-
sure condition exists, and the design does not include a
2010 CALIFORNIA BUILDING CODE
179
SOILS AND FOUNDATIONS
ground- water control system as described in Section 1 805. 1 .3,
walls and floors shall be waterproofed in accordance with this
section.
1805.3.1 Floors. Floors required to be waterproofed shall
be of concrete and designed and constructed to withstand
the hydrostatic pressures to which the floors will be sub-
jected.
Waterproofing shall be accomplished by placing a mem-
brane of rubberized asphalt, butyl rubber, ftilly adhered/fully
bonded HDPE or polyolefin composite membrane or not less
than 6-mil [0.006 inch (0.152 mm)] polyvinyl chloride with
joints lapped not less than 6 inches (152 mm) or other
approved materials under the slab. Joints in the membrane
shall be lapped and sealed in accordance with the manufac-
turer's installation instructions.
1805.3.2 Walls. Walls required to be waterproofed shall be
of concrete or masonry and shall be designed and con-
structed to withstand the hydrostatic pressures and other lat-
eral loads to which the walls will be subjected.
Waterproofing shall be applied from the bottom of the
wall to not less than 12 inches (305 mm) above the maxi-
mum elevation of the ground-water table. The remainder of
the wall shall be dampproofed in accordance with Section
1805.2.2. Waterproofing shall consist of two-ply
hot-mopped felts, not less than 6-mil (0.006 inch; 0.152
mm) polyvinyl chloride, 40-mil (0.040 inch; 1.02 mm)
polymer-modified asphalt, 6-mil (0.006 inch; 0.152 mm)
polyethylene or other approved methods or materials capa-
ble of bridging nonstructural cracks. Joints in the membrane
shall be lapped and sealed in accordance with the manufac-
turer's installation instructions.
1805.3.2.1 Surface preparation of walls. Prior to the
application of waterproofing materials on concrete or
masonry walls, the walls shall be prepared in accordance
with Section 1805.2.2.1.
1805.3.3 Joints and penetrations. Joints in walls and
floors, joints between the wall and floor and penetrations of
the wall and floor shall be made water-tight utilizing
approved methods and materials.
1805.4 Subsoil drainage system. Where a hydrostatic pres-
sure condition does not exist, dampproofing shall be provided
and a base shall be installed under the floor and a drain installed
around the foundation perimeter, A subsoil drainage system
designed and constructed in accordance with Section 1805. 1 .3
shall be deemed adequate for lowering the ground- water table.
1805.4.1 Floor base course. Floors of basements, except as
provided for in Section 1 805 .1.1, shall be placed over a floor
base course not less than 4 inches ( 1 02 mm) in thickness that
consists of gravel or crushed stone containing not more than
lOpercentof material that passes throughaNo. 4(4.75 mm)
sieve.
Exception: Where a site is located in well-drained gravel
or sand/gravel mixture soils, a floor base course is not
required.
1805.4.2 Foundation drain. A drain shall be placed around
the perimeter of a foundation that consists of gravel or
crushed stone containing not more than 10-percent material
that passes through a No. 4 (4.75 mm) sieve. The drain shall
extend a minimum of 12 inches (305 mm) beyond the out-
side edge of the footing. The thickness shall be such that the
bottom of the drain is not higher than the bottom of the base
under the floor, and that the top of the drain is not less than 6
inches (152 mm) above the top of the footing. The top of the
drain shall be covered with an approved filter membrane
material. Where a drain tile or perforated pipe is used, the
invert of the pipe or tile shall not be higher than the floor ele-
vation. The top of joints or the top of perforations shall be
protected with an approved filter membrane material. The
pipe or tile shall be placed on not less than 2 inches (5 1 mm)
of gravel or crushed stone complying with Section
1805.4.1, and shall be covered with not less than 6 inches
(152 mm) of the same material.
1805.4.3 Drainage discharge. The floor base and founda-
tion perimeter drain shall discharge by gravity or mechani-
cal means into an approved drainage system that complies
with the California Plumbing Code.
Exception: Where a site is located in well-drained gravel
or sand/gravel mixture soils, a dedicated drainage system
is not required.
SECTION 1806
PRESUMPTIVE LOAD-BEARING VALUES OF SOILS
1806.1 Load combinations. The presumptive load-bearing
values provided in Table 1806.2 shall be used with the allow-
able stress design load combinations specified in Section
1605.3. The values of vertical foundation pressure and lateral
bearing pressure given in Table 1806.2 shall be permitted to be
increased by one-third where used with the alternative basic
load combinations of Section 1605.3.2 that include wind or
earthquake loads.
1806.2 Presumptive load-bearing values. The load-bearing
values used in design for supporting soils near the surface shall
not exceed the values specified in Table 1806.2 unless data to
substantiate the use of higher values are submitted and
approved. Where the building official has reason to doubt the
classification, strength or compressibility of the soil, the
requirements of Section 1803.5.2 shall be satisfied.
Presumptive load-bearing values shall apply to materials
with similar physical characteristics and dispositions. Mud,
organic silt, organic clays, peat or unprepared fill shall not be
assumed to have a presumptive load-bearing capacity unless
data to substantiate the use of such a value are submitted.
Exception: A presumptive load-bearing capacity shall be
permitted to be used where the building official deems the
load-bearing capacity of mud, organic silt or unprepared fill
is adequate for the support of lightweight or temporary
structures.
1806.3 Lateral load resistance. Where the presumptive val-
ues of Table 1806.2 are used to determine resistance to lateral
loads, the calculations shall be in accordance with Sections
1806.3.1 through 1806.3.4.
180
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1806.3.1 Combined resistance. The total resistance to lat-
eral loads shall be permitted to be determined by combining
the values derived from the lateral bearing pressure and the
lateral sliding resistance specified in Table 1806.2.
1806.3.2 Lateral sliding resistance limit. For clay, sandy
clay, silty clay, clayey silt, silt and sandy silt, in no case shall
the lateral sliding resistance exceed one-half the dead load.
1806.3.3 Increase for depth. The lateral bearing pressures
specified in Table 1806.2 shall be permitted to be increased
by the tabular value for each additional foot (305 mm) of
depth to a maximum of 15 times the tabular value.
1806.3.4 Increase for poles. Isolated poles for uses such as
flagpoles or signs and poles used to support buildings that
are not adversely affected by a V2 inch (12.7 mm) motion at
the ground surface due to short-term lateral loads shall be
permitted to be designed using lateral bearing pressures
equal to two times the tabular values.
SECTION 1807
FOUNDATION WALLS, RETAINING WALLS AND
EMBEDDED POSTS AND POLES
1807.1 Foundation walls. Foundation walls shall be designed
and constructed in accordance with Sections 1807.1.1 through
1807.1.6. Foundation walls shall be supported by foundations
designed in accordance with Section 1808.
1807.1.1 Design lateral soil loads. Foundation walls shall
be designed for the lateral soil loads set forth in Section
1610.
1807.1.2 Unbalanced backfill height. Unbalanced backfill
height is the difference in height between the exterior finish
ground level and the lower of the top of the concrete footing
that supports the foundation wall or the interior finish
ground level. Where an interior concrete slab on grade is
provided and is in contact with the interior surface of the
foundation wall, the unbalanced backfill height shall be per-
mitted to be measured from the exterior finish ground level
to the top of the interior concrete slab.
1807.1.3 Rubble stone foundation walls. Foundafion
walls of rough or random rubble stone shall not be less than
1 6 inches (406 mm) thick. Rubble stone shall not be used for
foundation walls of structures assigned to Seismic Design
Category C, D, E or F.
1807.1.4 Permanent wood foundation systems. Permanent
wood foundation systems shall be designed and installed in
accordance with AF&PA PWF. Lumber and plywood shall
be treated in accordance with AWPA Ul (Commodity Speci-
fication A, Use Category 4B and Section 5.2) and shall be
identified in accordance with Section 2303.1.8.1.
1807.1.5 Concrete and masonry foundation walls. Con-
crete and masonry foundation walls shall be designed in
accordance with Chapter 19 or 21, as applicable.
Exception: Concrete and masonry foundation walls shall
be permitted to be designed and constructed in accordance
with Section 1807.1.6.
1807.1.6 Prescriptive design of concrete and masonry
foundation walls. Concrete and masonry foundation walls
that are laterally supported at the top and bottom shall be
permitted to be designed and constructed in accordance
with this section,
1807.1.6.1 Foundation wall thickness. The thickness
of prescriptively designed foundation walls shall not be
less than the thickness of the wall supported, except that
foundation walls of at least 8-inch (203 mm) nominal
width shall be permitted to support brick- veneered frame
walls and 10-inch- wide (254 mm) cavity walls provided
the requirements of Section 1807.1.6.2 or 1807.1.6.3 are
met.
TABLE 1806.2
PRESUMPTIVE LOAD-BEARING VALUES
CLASS OF MATERIALS
VERTICAL FOUNDATION
PRESSURE (psf)
LATERAL BEARING
PRESSURE
(psf/ft below natural grade)
LATERAL SLIDING RESISTANCE
Coefficient of friction^
Cohesion (psf)**
1 . Crystalline bedrock
12,000
1,200
0.70
—
2. Sedimentary and foliated rock
4,000
400
0.35
—
3. Sandy gravel and/or gravel (GW and
GP)
3,000
200
0,35
~
4. Sand, silty sand, clayey sand, silty
gravel and clayey gravel (SW, SP,
SM, SC, GM and GC)
2,000
150
0.25
—
5. Clay, sandy clay, silty clay, clayey
silt, silt and sandy silt (CL, ML, MH
and CH)
1,500
100
~
130
For SI: 1 pound per square foot = 0.0479 kPa, 1 pound per square foot per foot = 0.157 kPa/m.
a. Coefficient to be multiplied by the dead load.
b. Cohesion value to be multiplied by the contact area, as limited by Section 1806.3.2.
2010 CALIFORNIA BUILDING CODE
181
SOILS AND FOUNDATIONS
1807.1.6.2 Concrete foundation walls. Concrete foun-
dation walls shall comply with the following:
1. The thickness shall comply with the requirements
of Table 1807.1.6.2.
2.
The size and spacing of vertical reinforcement
shown in Table 1807.1.6.2 is based on the use of
reinforcement with a minimum yield strength of
60,000 pounds per square inch (psi) (414 MPa).
Vertical reinforcement with a minimum yield
strength of 40,000 psi (276 MPa) or 50,000 psi
(345 MPa) shall be permitted, provided the same
size bar is used and the spacing shown in the table
is reduced by multiplying the spacing by 0.67 or
0.83, respectively.
3. Vertical reinforcement, when required, shall be
placed nearest the inside face of the wall a dis-
tance, d, from the outside face (soil face) of the
wall. The distance, d, is equal to the wall thickness,
f, minus 1.25 inches (32 nam) plus one-half the bar
diameter, J^, [ J = f - ( 1 .25 -i- J^, / 2) ] . The reinforce-
ment shall be placed within a tolerance of ± % inch
(9.5 mm) where d is less than or equal to 8 inches
(203 mm) or ± Vj inch ( 1 2.7 mm) where d is greater
than 8 inches (203 mm).
4. In lieu of the reinforcement shown in Table
1807.1.6.2, smaller reinforcing bar sizes with
closer spacings that provide an equivalent
cross-sectional area of reinforcement per unit
length shall be permitted.
TABLE 1807.1.6.2
CONCRETE FOUNDATION WALLS" '
MAXIMUM
MAXIMUM
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Design lateral soil load° (psf per foot of depth)
30^
45^
60
WALL
HEIGHT
UNBALANCED
BACKFILL
Minimum wall thickness (inches)
(feet)
HEIGHr (feet)
7.5
9.5
11.5
7.5
9.5
11.5
7.5
9.5
11.5
5
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
6
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
6
PC
PC
PC
PC
PC
PC
PC
PC
PC
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
7
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
6
PC
PC
PC
PC
PC
PC
#5 at 48
PC
PC
7
PC
PC
PC
#5 at 46
PC
PC
#6 at 48
PC
PC
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
8
6
PC
PC
PC
PC
PC
PC
#5 at 43
PC
PC
7
PC
PC
PC
#5 at 41
PC
PC
#6 at 43
PC
PC
8
#5 at 47
PC
PC
#6 at 43
PC
PC
#6 at 32
#6 at 44
PC
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
9
6
PC
PC
PC
PC
PC
PC
#5 at 39
PC
PC
7
PC
PC
PC
#5 at 37
PC
PC
#6 at 38
#5 at 37
PC
8
#5 at 41
PC
PC
#6 at 38
#5 at 37
PC
#7 at 39
#6 at 39
#4 at 48
9d
#6 at 46
PC
PC
#7 at 41
#6 at 41
PC
#7 at 31
#7 at 41
#6 at 39
4
PC
PC
PC
PC
PC
PC
PC
PC
PC
5
PC
PC
PC
PC
PC
PC
PC
PC
PC
6
PC
PC
PC
PC
PC
PC
#5 at 37
PC
PC
10
7
PC
PC
PC
#6 at 48
PC
PC
#6 at 35
#6 at 48
PC
8
#5 at 38
PC
PC
#7 at 47
#6 at 47
PC
#7 at 35
#7 at 47
#6 at 45
9d
#6 at 41
#4 at 48
PC
#7 at 37
#7 at 48
#4 at 48
#6 at 22
#7 at 37
#7 at 47
10^
#7 at 45
#6 at 45
PC
#7 at 31
#7 at 40
#6 at 38
#6 at 22
#7 at 30
#7 at 38
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157kPa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.2.
c. "PC" means plain concrete.
d. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 16 10. 1 are used, the requirements for 30 and 45 psf per foot of depth are
not applicable (see Section 1610).
e. For height of unbalanced backfill, see Section 1807.1.2.
182
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATBONS
5. Concrete cover for reinforcement measured from
the inside face of the wall shall not be less than V4
inch (19.1 mm). Concrete cover for reinforcement
measured from the outside face of the wall shall
not be less than 1 V2 inches (38 mm) for No. 5 bars
and smaller, and not less than 2 inches (5 1 nmi) for
larger bars.
6. Concrete shall have a specified compressive
strength,/^, of not less than 2,500 psi (17.2 MPa).
7. The unfactored axial load per linear foot of wall
shall not exceed 1.2 tf\ where t is the specified
wall thickness in inches.
1807.1.6.2.1 Seismic requirements. Based on the
seismic design category assigned to the structure in
accordance with Section 1613, concrete foundation
walls designed using Table 1807.1.6.2 shall be sub-
ject to the following limitations:
1. Seismic Design Categories A and B. No addi-
tional seismic requirements, except provide
reinforcement around openings in accordance
with Section 1909.6.3.
2. Seismic Design Categories C, D, E and F.
Tables shall not be used except as allowed for
plain concrete members in Section 1908.1.8.
1807.1.6.3 Masonry foundation walls. Masonry foun-
dation walls shall comply with the following:
1. The thickness shall comply with the require-
ments of Table 1807.1.6.3(1) for plain masonry
walls or Table 1807.1.6.3(2), 1807.1.6.3(3) or
1807.1.6.3(4) for masonry walls with reinforce-
ment.
2. Vertical reinforcement shall have a minimum
yield strength of 60,000 psi (414 MPa).
3 . The specified location of the reinforcement shall
equal or exceed the effective depth distance, d,
noted in Tables 1807.1.6.3(2), 1807.1.6.3(3) and
1807.1.6.3(4) and shall be measured from the
face of the exterior (soil) side of the wall to the
center of the vertical reinforcement. The rein-
forcement shall be placed within the tolerances
specified in TMS 602/ACI 530.1/ASCE 6, Arti-
cle 3.3.B.8 of the specified location.
4. Grout shall comply with Section 2103.12.
5. Concrete masonry units shall comply with
ASTM C 90.
6. Clay masonry units shall comply with ASTM C
652 for hollow brick, except compliance with
ASTM C 62 or ASTM C 216 shall be permitted
where solid masonry units are installed in accor-
dance with Table 1807.1.6.3(1) for plain
masonry.
TABLE 1807.1.6.3(1)
PLAIN MASONRY FOUNDATION WALLS^*' '^
MAXIMUM WALL HEIGHT
(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHr(feet)
MINIMUM NOMINAL WALL THICKNESS (inches)
Design lateral soil load° (psf per foot of depth)
30^
45^
60
7
4 (or less)
5
6
7
8
8
10
12
8
10
12
10 (solid'=)
8
10
10 (solid'=)
10 (solid'^)
8
4 (or less)
5
6
7
8
8
8
10
12
10 (solid'^)
8
10
12
12 (solid^)
12 (solid^)
8
12
12 (solid^)
Noted
Noted
9
4 (or less)
5
6
7
8
9f
8
8
12
12 (solid^)
12 (solid'^)
Noted
8
10
12
12 (solid^)
Noted
Noted
8
12
12 (solid^)
Noted
Noted
Noted
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157kPa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements speciied in Section 1807.1.6.3.
c. Solid grouted hollow units or solid masonry units.
d. A design in compliance with Chapter 21 or reinforcement in accordance with 'Eible 1807.1.6.3(2) is required.
e. For height of unbalanced backfill, see Section 1807.1.2.
f. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1 61 0. 1 are used, the requirements for 30 and 45 psf per foot of depth are
not applicable (see Section 1610).
2010 CALIFORNIA BUILDING CODE
183
SOILS AND FOUNDATIONS
7. Masonry units shall be laid in running bond and
installed with Type M or S mortar in accordance
with Section 2103.8.
8. The unfactored axial load per linear foot of wall
shall not exceed 1.2 tf'^ where t is the specified
wall thickness in inches and/'^ is the specified
compressive strength of masonry in pounds per
square inch.
9 . At least 4 inches ( 1 02 mm) of solid masonry shall
be provided at girder supports at the top of hol-
low masonry unit foundation walls.
10. Corbeling of masonry shall be in accordance
with Section 2104.2. Where an 8-inch (203 mm)
wall is corbeled, the top corbel shall not extend
higher than the bottom of the floor framing and
shall be a full course of headers at least 6 inches
(152 mm) in length or the top course bed joint
shall be tied to the vertical wall projection. The
tie shall be W2.8 (4.8 mm) and spaced at a maxi-
mum horizontal distance of 36 inches (914 mm).
The hollow space behind the corbelled masonry
shall be filled with mortar or grout.
1807.1.6.3.1 Alternative foundation wall reinforce-
ment. In lieu of the reinforcement provisions for
masonry foundation walls in Table 1807.1.6.3(2),
1807.1.6.3(3) or 1807.1.6.3(4), alternative reinforcing
bar sizes and spacings having an equivalent cross-sec-
tional area of reinforcement per linear foot (nma) of
wall shall be permitted to be used, provided the spacing
of reinforcement does not exceed 72 inches (1 829 mm)
and reinforcing bar sizes do not exceed No. 1 1 .
TABLE 1807.1.6.3(2)
8-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 5 INCHES^'* *
MAXIMUM WALL HEIGHT
(feet-inches)
MAXIMUM UNBALANCED
BACKFILL HEIGHT*^
(feet-inches)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Design lateral soil load^(psf per foot of depth)
30®
45®
60
7-4
4-0 (or less)
5-0
6-0
7-4
#4 at 48
#4 at 48
#4 at 48
#5 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
. #4 at 48
#4 at 48
#5 at 48
#7 at 48
8-0
4-0 (or less)
5-0
6-0
7-0
8-0
#4 at 48
#4 at 48
#4 at 48
#5 at 48
#5 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#6 at 48
#4 at 48
#4 at 48
#5 at 48
#7 at 48
#7 at 48
8-8
4-0 (or less)
5-0
6-0
7-0
8-8^
#4 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#8 at 48
9-4
4-0 (or less)
5-0
6-0
7-0
8-0
9-4^
#4 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#8 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#8 at 48
#9 at 48
10-0
4-0 (or less)
5-0
6-0
7-0
8-0
9-0^
10-0^
#4 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#7 at 48
#4 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#8 at 48
#9 at 48
#4 at 48
#5 at 48
#6 at 48
#7 at 48
#8 at 48
#9 at 48
#9 at 48
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157kPa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3.
c. For alternative reinforcement, see Section 1807.1.6.3.1.
d. For height of unbalanced backfill, see Section 1 807. 1 .2.
e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 16 1 0. 1 are used, the requirements for 30 and 45 psf per foot of depth are
not applicable. See Section 1610.
184
2010 CALIFORNIA BUILDING CODE
1807.1.6.3.2 Seismic requirements. Based on the
seismic design category assigned to the structure in
accordance with Section 1613, masonry foundation
walls designed using Tables 1807.1.6.3(1) through
1 807. 1 .6.3(4) shall be subject to the following limita-
tions:
1. Seismic Design Categories A and B. No addi-
tional seismic requirements.
2. Seismic Design Category C. A design using
Tables 1807.1.6.3(1) through 1807.1.6.3(4) is
subject to the seismic requirements of Section
1.17.4.3 of TMS 402/ACI 530/ASCE 5.
3. Seismic Design Category D. A design using
Tables 1807.1.6.3(2) through 1807.1.6.3(4) is
SOILS AND FOUNDATIONS
subject to the seismic requirements of Section
1.17.4.4 of TMS 402/ACI 530/ASCE 5.
4. Seismic Design Categories E and F. A design
using Tables 1807.1.6.3(2) through
1807.1.6.3(4) is subject to the seismic require-
ments of Section 1.17.4.5 of TMS 402/ACI
530/ASCE 5.
1807.2 Retaining walls. Retaining walls shall be designed in
accordance with Sections 1807.2.1 through 1807.2.3.
1807.2.1 General, Retaining walls shall be designed to
ensure stability against overturning, sliding, excessive foun-
dation pressure and water uplift. Where a key way is extended
below the wall base with the intent to engage passive pressure
and enhance sliding stability, lateral soil pressures on both
TABLE 1807,1.6.3(3)
10-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 6.75 INCHES ^'^"^
MAXIMUM WALL HEIGHT
(feet-inches)
MAXIMUM UNBALANCED
BACKFILL HEIGHr*
(feet-Inches)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Design lateral soil ioad° (psf per foot of depth)
30®
45®
60
7-4
4-0 (or less)
5-0
6-0
7-4
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
8-0
4-0 (or less)
5-0
6-0
7-0
8-0
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#4 at 56
#4 at 5
#4 at 56
#5 at 56
#6 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
#7 at 56
8-8
4-0 (or less)
5-0
6-0
7-0
8-8^
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#7 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
#8 at 56
9-4
4-0 (or less)
5-0
6-0
7-0
8-0
9-4^
#4 at 56
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
#4 at 56
#4 at 56
#5 at 56
#5 at 56
#6 at 56
#7 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
#7 at 56
#7 at 56
10-0
4-0 (or less)
5-0
6-0
7-0
8-0
9-0^
10-0^
#4 at 56
#4 at 56
#4 at 56
#5 at 56
#5 at 56
#6 at 56
#7 at 56
#4 at 56
#4 at 56
#5 at 56
#6 at 56
#7 at 56
#7 at 56
#8 at 56
#4 at 56
#4 at 56
#5 at 56
#7 at 56
#8 at 56
#9 at 56
#9 at 56
For SI: 1 inch = 25.4 mm, 1 foot = 304.8, 1 pound per square foot per foot = 1.157k:Pa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3.
c. For alternative reinforcement, see Section 1807.1.6.3.1.
d. For height of unbalanced backfill, See Section 1 807 .1.2.
e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610. 1 are used, the requirements for 30 and 45 psf per foot of depth are
not applicable. See Section 1610.
2010 CALIFORNIA BUILDING CODE
185
SOILS AND FOUNDATIONS
sides of the key way shall be considered in the sliding analy-
sis.
1807.2.2 Design lateral soil loads. Retaining walls shall be
designed for the lateral soil loads set forth in Section 1610.
1807.2.3 Safety factor. Retaining walls shall be designed to
resist the lateral action of soil to produce sliding and over-
turning with a minimum safety factor of 1.5 in each case.
The load combinations of Section 1605 shall not apply to
this requirement. Instead, design shall be based on 0.7 times
nominal earthquake loads, 1.0 times other nominal loads,
and investigation with one or more of the variable loads set
to zero. The safety factor against lateral sliding shall be
taken as the available soil resistance at the base of the retain-
ing wall foundation divided by the net lateral force applied
to the retaining wall.
Exception: Where earthquake loads are included, the
minimum safety factor for retaining wall sliding and
overturning shall be 1.1.
1807.3 Embedded posts and poles. Designs to resist both
axial and lateral loads employing posts or poles as columns
embedded in earth or in concrete footings in earth shall be in
accordance with Sections 1807.3.1 through 1807.3.3.
1807.3.1 Limitations. The design procedures outlined in
this section are subject to the following limitations:
1 . The frictional resistance for structural walls and slabs
on silts and clays shall be limited to one-half of the
normal force imposed on the soil by the weight of the
footing or slab.
2. Posts embedded in earth shall not be used to provide
lateral support for structural or nonstructural materi-
TABLE 1807.1.6.3(4)
12-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 8.75 INCHES^' '^'^
MAXIMUM WALL HEIGHT
(feet-inches)
MAXIMUM UNBALANCED
BACKFILL HEIGHT*
(feet-Inches)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Design lateral soil load° (psf per foot of depth)
30«
45°
60
7-4
4 (or less)
5-0
6-0
7-4
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
8-0
4 (or less)
5-0
6-0
7-0
8-0
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#8 at 72
8-8
4 (or less)
5-0
6-0
7-0
8-8^
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#7 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#8 at 72
9-4
4 (or less)
5-0
6-0
7-0
8-0
9-4^
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#4 at 72
#4 at 72
#5 at 72
#5 at 72
#6 at 72
#7 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#7 at 72
#8 at 72
10-0
4 (or less)
5-0
6-0
7-0
8-0
9-0^
10-0^
#4 at 72
#4 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#7 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#6 at 72
#7 at 72
#8 at 72
#4 at 72
#4 at 72
#5 at 72
#6 at 72
#7 at 72
#8 at 72
#9 at 72
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, I pound per square foot per foot = 0.157 kPa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3.
c. For alternative reinforcement, see Section 1 807. 1 .6.3. 1 .
d. For height of unbalanced backfill, see Section 1807.1.2,
e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610. 1 are used, the requirements for 30 and 45 psf per foot of depth are
not applicable. See Section 1610.
186
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
als such as plaster, masonry or concrete unless brac-
ing is provided that develops the limited deflection
required.
Wood poles shall be treated in accordance with AWPA
Ul for sawn timber posts (Commodity Specification A, Use
Category 4B) and for round timber posts (Commodity
Specification B, Use Category 4B).
1807.3.2 Design criteria. The depth to resist lateral loads
shall be determined using the design criteria established in
Sections 1807.3.2.1 through 1807.3.2.3, or by other meth-
ods approved by the building official.
1807.3.2.1 Nonconstrained. The following formula
shall be used in determining the depth of embedment
required to resist lateral loads where no lateral constraint
is provided at the ground surface, such as by a rigid floor
or rigid ground surface pavement, and where no lateral
constraint is provided above the ground surface, such as
by a structural diaphragm.
d=0,5A{l + [l+(4.36h/A)y^^}
where:
(Equation 18-1)
d =
h =
A = 234P/S^b,
b = Diameter of round post or footing or diagonal
dimension of square post or footing, feet (m).
Depth of embedment in earth in feet (m) but not
over 12 feet (3658 mm) for purpose of comput-
ing lateral pressure.
Distance in feet (m) from ground surface to point
of application of "P."
P = Applied lateral force in pounds (kN).
Si = Allowable lateral soil-bearing pressure as set
forth in Section 1806.2 based on a depth of
one-third the depth of embedment in pounds per
square foot (psf) (kPa).
1807.3.2.2 Constrained. The following formula shall be
used to determine the depth of embedment required to
resist lateral loads where lateral constraint is provided at
the ground surface, such as by a rigid floor or pavement.
d =
425Ph
S^b
or alternatively
4.25M^
S^b
(Equation 18-2)
(Equation 18-3)
where:
Mg = Moment in the post at grade, in foot-pounds
(kN-m).
53 = Allowable lateral soil-bearing pressure as set
forth in Section 1806,2 based on a depth equal to
the depth of embedment in pounds per square
foot (kPa).
1807.3.2.3 Vertical load. The resistance to vertical loads
shall be determined using the vertical foundation pres-
sure set forth in Table 1806.2.
1807.3.3 Backfill. The backfill in the annular space around
columns not embedded in poured footings shall be by one of
the following methods:
1. Backfill shall be of concrete with a specified com-
pressive strength of not less than 2,000 psi (13.8
MPa). The hole shall not be less than 4 inches (102
mm) larger than the diameter of the column at its bot-
tom or 4 inches (102 mm) larger than the diagonal
dimension of a square or rectangular colunrn.
2. Backfill shall be of clean sand. The sand shall be thor-
oughly compacted by tamping in layers not more than
8 inches (203 mm) in depth.
3. Backfill shall be of controlled low-strength material
(CLSM).
SECTION 1808
FOUNDATIONS
1808.1 General. Foundations shall be designed and con-
structed in accordance with Sections 1808.2 through 1808.9.
Shallow foundations shall also satisfy the requirements of Sec-
tion 1809. Deep foundations shall also satisfy the requirements
of Section 1810.
1808.2 Design for capacity and settlement. Foundations
shall be so designed that the allowable bearing capacity of the
soil is not exceeded, and that differential settlement is mini-
mized. Foundations in areas with expansive soils shall be
designed in accordance with the provisions of Section 1808.6.
1808.3 Design loads. Foundations shall be designed for the
most unfavorable effects due to the combinations of loads spec-
ified in Section 1605.2 or 1605.3. The dead load is permitted to
include the weight of foundations and overlying fill. Reduced
live loads, as specified in Sections 1607.9 and 1607. 11, shall be
permitted to be used in the design of foundations.
1808.3.1 Seismic overturning. Where foundations are pro-
portioned using the load combinations of Section 1605.2 or
1605.3.1, and the computation of seismic overturning
effects is by equivalent lateral force analysis or modal anal-
ysis, the proportioning shall be in accordance with Section
12.13.4 of ASCE 7.
1808.4 Vibratory loads. Where machinery operations or other
vibrations are transmitted through the foundation, consider-
ation shall be given in the foundation design to prevent detri-
mental disturbances of the soil.
1808.5 Shifting or moving soils. Where it is known that the
shallow subsoils are of a shifting or moving character, founda-
tions shall be carried to a sufficient depth to ensure stability.
2010 CALIFORNIA BUILDING CODE
187
SOILS AND FOUNDATIONS
1808.6 Design for expansive soils. Foundations for buildings
and structures founded on expansive soils shall be designed in
accordance with Section 1808.6.1 or 1808.6.2.
Exception: Foundation design need not comply with Sec-
tion 1808.6.1 or 1808.6.2 where one of the following condi-
tions is satisfied:
1. The soil is removed in accordance with Section
1808.6.3; or
2. The building official approves stabilization of the soil
in accordance with Section 1808.6.4.
1808.6.1 Foundations. Foundations placed on or within the
active zone of expansive soils shall be designed to resist dif-
ferential volume changes and to prevent structural damage
to the supported structure. Deflection and racking of the
supported structure shall be limited to that which will not
interfere with the usability and serviceability of the struc-
ture.
Foundations placed below where volume change occurs
or below expansive soil shall comply with the following
provisions:
1. Foundations extending into or penetrating expansive
soils shall be designed to prevent uplift of the sup-
ported structure.
2. Foundations penetrating expansive soils shall be
designed to resist forces exerted on the foundation
due to soil volume changes or shall be isolated from
the expansive soil.
1808.6.2 Slab-on-ground foundations. Moments, shears
and deflections for use in designing slab-on-ground, mat or
raft foundations on expansive soils shall be determined in
accordance with WRI/CRSI Design of Slah-on-Ground Foun-
dations or PTI Standard Requirements for Analysis of Shal-
low Concrete Foundations on Expansive Soils. Using the
moments, shears and deflections determined above,
nonprestressed slabs-on-ground, mat or raft foundations on
expansive soils shall be designed in accordance with
WRI/CRSI Design of Slah-on-Ground Foundations and
post-tensioned slab-on-ground, mat or raft foundations on
expansive soils shall be designed in accordance with PTI
Standard Requirements for Design of Shallow Post-
Tensioned Concrete Foundations on Expansive Soils, It shall
be permitted to analyze and design such slabs by other meth-
ods that account for soil- structure interaction, the deformed
shape of the soil support, the plate or stiffened plate action of
the slab as well as both center lift and edge lift conditions.
Such alternative methods shall be rational and the basis for all
aspects and parameters of the method shall be available for
peer review.
1808.6.3 Removal of expansive soil. Where expansive soil
is removed in Heu of designing foundations in accordance
with Section 1808,6.1 or 1808.6.2, the soil shall be removed
to a depth sufficient to ensure a constant moisture content in
the remaining soil. Fill material shall not contain expansive
soils and shall comply with Section 1804.5 or 1804.6.
Exception: Expansive soil need not be removed to the
depth of constant moisture, provided the confining pres-
sure in the expansive soil created by the fill and sup-
ported structure exceeds the swell pressure.
1808.6.4 Stabilization. Where the active zone of expansive
soils is stabilized in Heu of designing foundations in accor-
dance with Section 1808.6.1 or 1808.6.2, the soil shall be
stabilized by chemical, dewatering, presaturation or equiva-
lent techniques.
1808.7 Foundations on or adjacent to slopes. The placement
of buildings and structures on or adjacent to slopes steeper than
one unit vertical in three units horizontal (33.3-percent slope)
shall comply with Sections 1808.7.1 through 1808.7.5.
1808.7.1 Building clearance from ascending slopes. In
general, buildings below slopes shall be set a sufficient dis-
tance from the slope to provide protection from slope drain-
age, erosion and shallow failures. Except as provided in
Section 1808.7.5 and Figure 1808.7.1, the following criteria
will be assumed to provide this protection. Where the exist-
ing slope is steeper than one unit vertical in one unit hori-
zontal (100-percent slope), the toe of the slope shall be
assumed to be at the intersection of a horizontal plane drawn
from the top of the foundation and a plane drawn tangent to
the slope at an angle of 45 degrees (0.79 rad) to the horizon-
tal. Where a retaining wall is constructed at the toe of the
slope, the height of the slope shall be measured from the top
of the wall to the top of the slope.
FACE OF
FOOTING
FACE OF
STRUCTURE
For SI: 1 foot = 304.8 mm.
AT LEAST THE SMALLER OF H/2 AND 15 FEET
FIGURE 1808.7.1
FOUNDATION CLEARANCES FROM SLOPES
188
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1808.7.2 Foundation setback from descending slope sur-
face. Foundations on or adjacent to slope surfaces shall be
founded in firm material with an embedment and set back
from the slope surface sufficient to provide vertical and lat-
eral support for the foundation without detrimental settle-
ment. Except as provided for in Section 1808.7.5 and Figure
1808.7.1, the following setback is deemed adequate to meet
the criteria. Where the slope is steeper than 1 unit vertical in 1
unit horizontal (100-percent slope), the required setback shall
be measured from an imaginary plane 45 degrees (0.79 rad)
to the horizontal, projected upward from the toe of the slope.
1808.7.3 Pools. The setback between pools regulated by
this code and slopes shall be equal to one-half the building
footing setback distance required by this section. That por-
tion of the pool wall within a horizontal distance of 7 feet
(2134 mm) from the top of the slope shall be capable of sup-
porting the water in the pool without soil support.
1808.7.4 Foundation elevation. On graded sites, the top of
any exterior foundation shall extend above the elevation of
the street gutter at point of discharge or the inlet of an
approved drainage device a minimum of 12 inches (305
mm) plus 2 percent. Alternate elevations are permitted sub-
ject to the approval of the building official, provided it can
be demonstrated that required drainage to the point of dis-
charge and away from the structure is provided at all loca-
tions on the site.
1808.7.5 Alternate setback and clearance. Alternate set-
backs and clearances are permitted, subject to the approval
of the building official. The building official shall be permit-
ted to require a geotechnical investigation as set forth in Sec-
tion 1803.5.10.
1808.8 Concrete foundations. The design, materials and con-
struction of concrete foundations shall comply with Sections
1808.8.1 through 1808.8.6 and the provisions of Chapter 19.
Exception: Where concrete footings supporting walls of
light-frame construction are designed in accordance with
Table 1809.7, a specific design in accordance with Chapter
19 is not required.
1808.8.1 Concrete or grout strength and mix propor-
tioning. Concrete or grout in foundations shall have a speci-
fied compressive strength (f 'c) not less than the largest
applicable value indicated in Table 1808.8.1.
Where concrete is placed through a funnel hopper at the
top of a deep foundation element, the concrete mix shall be
designed and proportioned so as to produce a cohesive
workable mix having a slump of not less than 4 inches (102
mm) and not more than 8 inches (204 mm). Where concrete
or grout is to be pumped, the mix design including slump
shall be adjusted to produce a pumpable mixture.
1808.8.2 Concrete cover. The concrete cover provided for
prestressed and nonprestressed reinforcement in foundations
shall be no less than the largest applicable value specified in
Table 1 808.8.2. Longitudinal bars spaced less than 1 V2 inches
(38 mm) clear distance apart shall be considered bundled bars
for which the concrete cover provided shall also be no less
than that required by Section 7.7.4 of ACI 318. Concrete
cover shall be measured from the concrete surface to the out-
ermost surface of the steel to which the cover requirement
applies. Where concrete is placed in a temporary or perma-
nent casing or a mandrel, the inside face of the casing or man-
drel shall be considered the concrete surface.
1808.8.3 Placement of concrete. Concrete shall be placed in
such a manner as to ensure the exclusion of any foreign mat-
ter and to secure a full-size foundation. Concrete shall not be
placed through water unless a tremie or other method
approved by the building official is used. Where placed under
or in the presence of water, the concrete shall be deposited by
approved means to ensure minimum segregation of the mix
and negUgible turbulence of the water. Where depositing
concrete from the top of a deep foundation element, the con-
crete shall be chuted directly into smooth-sided pipes or tubes
or placed in a rapid and continuous operation through a fun-
nel hopper centered at the top of the element.
1808.8.4 Protection of concrete. Concrete foundations
shall be protected from freezing during depositing and for a
period of not less than five days thereafter. Water shall not
be allowed to flow through the deposited concrete.
1808.8.5 Forming of concrete. Concrete foundations are
permitted to be cast against the earth where, in the opinion
of the building official, soil conditions do not require
formwork. Where formwork is required, it shall be in accor-
dance with Chapter 6 of ACI 318.
1808.8.6 Seismic requirements. See Section 1908 for
additional requirements for foundations of structures
assigned to Seismic Design Category C, D, E or F.
For structures assigned to Seismic Design Category D, E
or F, provisions of ACI 318, Sections 21,12.1 through
21.12.4, shall apply where not in conflict with the provi-
sions of Sections 1808 through 1810.
Exceptions:
1. Detached one- and two-family dwellings of
light- frame construction and two stories or less
above grade plane are not required to comply with
the provisions of ACI 318, Sections 21.12.1
through 21.12.4.
2. Section 21.12.4.4(a) of ACI 318 shall not apply.
1808.9 Vertical masonry foundation elements. Vertical
masonry foundation elements that are not foundation piers as
defined in Section 2102.1 shall be designed as piers, walls or
columns, as applicable, in accordance with TMS 402/ACI
530/ASCE 5.
SECTION 1809
SHALLOW FOUNDATIONS
1809.1 General. Shallow foundations shall be designed and
constructed in accordance with Sections 1809.2 through
1809.13.
1809.2 Supporting soils. Shallow foundations shall be built on
undisturbed soil, compacted fill material or controlled
low-strength material (CLSM). Compacted fill material shall
be placed in accordance with Section 1804.5. CLSM shall be
placed in accordance with Section 1804.6.
2010 CALIFORNIA BUILDING CODE
189
SOILS AND FOUNDATIONS
TABLE 1808.8.1
MINIMUM SPECIFIED COMPRESSIVE STRENGTH f'c OF CONCRETE OR GROUT
FOUNDATION ELEMENT OR CONDITION
SPECIFIED COMPRESSIVE
STRENGTH, f '^
1. Foundations for structures assigned to Seismic Design Category A, B or C
2,500 psi
2a. Foundations for Group R or U occupancies of light-frame construction, two stories or less in height,
assigned to Seismic Design Category D, E or F
2,500 psi
2b. Foundations for other structures assigned to Seismic Design Category D, E or F
3,000 psi
3. Precast nonprestressed drived piles
4,000 psi
4. Socketed drilled shafts
4,000 psi
5. Micropiles
4,000 psi
6. Precast prestressed driven piles
5,000 psi
For SI: 1 pound per square inch = 0.00689 MPa.
TABLE 1808.8.2
MINIMUM CONCRETE COVER
FOUNDATION ELEMENT OR CONDITION
MINIMUM COVER
1. Shallow foundations
In accordance with Section 7.7 of ACI 318
2. Precast nonprestressed deep foundation elements
Exposed to seawater
Not manufactured under plant conditions
Manufactured under plant control conditions
3 inches
2 inches
In accordance with Section 7.7.3 of ACI 318
3. Precast prestressed deep foundation elements
Exposed to seawater
Other
2.5 inches
In accordance with Section 7.7.3 of ACI 318
4. Cast-in-place deep foundation elements not enclosed by a steel pipe, tube or permanent
casing
2.5 inches
5. Cast-in-place deep foundation elements enclosed by a steel pipe, tube or permanent casing
1 inch
6. Structural steel core within a steel pipe, tube or permanent casing
2 inches
7. Cast-in-place drilled shafts enclosed by a stable rock socket
1.5 inches
For SI: 1 inch = 25.4 mm.
190
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1809.3 Stepped footings. The top surface of footings shall be
level. The bottom surface of footings shall be permitted to have
a slope not exceeding one unit vertical in 10 units horizontal
(10-percent slope). Footings shall be stepped where it is neces-
sary to change the elevation of the top surface of the footing or
where the surface of the ground slopes more than one unit verti-
cal in 10 units horizontal (10-percent slope).
1809.4 Depth and width of footings. The minimum depth of
footings below the undisturbed ground surface shall be 12
inches (305 mm). Where applicable, the requirements of Sec-
tion 1809.5 shall also be satisfied. The minimum width of foot-
ings shall be 12 inches (305 mm).
1809.5 Frost protection. Except where otherwise protected
from frost, foundations and other permanent supports of build-
ings and structures shall be protected from frost by one or more
of the following methods:
1. Extending below the frost line of the locality;
2. Constructing in accordance with ASCE 32; or
3. Erecting on solid rock.
Exception: Free-standing buildings meeting all of the fol-
lowing conditions shall not be required to be protected:
1. Assigned to Occupancy Category I, in accordance
with Section 1604.5;
2. Area of 600 square feet (56 m^) or less for light-frame
construction or 400 square feet (37 m^) or less for
other than light-frame construction; and
3. Eave height of 10 feet (3048 mm) or less.
Shallow foundations shall not bear on frozen soil unless such
frozen condition is of a permanent character.
1809.6 Location of footings. Footings on granular soil shall be
so located that the line drawn between the lower edges of
adjoining footings shall not have a slope steeper than 30
degrees (0.52 rad) with the horizontal, unless the material sup-
porting the higher footing is braced or retained or otherwise lat-
erally supported in an approved manner or a greater slope has
been properly established by engineering analysis.
1809.7 Prescriptive footings for light-frame construction.
Where a specific design is not provided, concrete or
masonry-unit footings supporting walls of light-frame con-
struction shall be permitted to be designed in accordance with
Table 1809.7.
1809.8 Plain concrete footings. The edge thickness of plain
concrete footings supporting walls of other than light-frame
construction shall not be less than 8 inches (203 mm) where
placed on soil or rock.
Exception: For plain concrete footings supporting Group
R-3 occupancies, the edge thickness is permitted to be 6
inches (152 mm), provided that the footing does not extend
beyond a distance greater than the thickness of the footing
on either side of the supported wall.
TABLE 1809.7
PRESCRIPTIVE FOOTINGS SUPPORTING WALLS OF
LIGHT-FRAME CONSTRUCTION^- "' «=' «*' ^
NUMBER OF FLOORS
SUPPORTED BY THE
FOOTING*
WIDTH OF FOOTING
(inches)
THICKNESS OF
FOOTING (inches)
1
12
6
2
15
6
3
18
gg
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Depth of footings shall be in accordance with Section 1809.4.
b. The ground under the floor shall be permitted to be excavated to the elevation
of the top of the footing.
c. Interior stud-bearing walls shall be permitted to be supported by isolated
footings. The footing width and length shall be twice the width shown in this
table, and footings shall be spaced not more than 6 feet on center
d. See Section 1908 for additional requirements for concrete footings of struc-
tures assigned to Seismic Design Category C, D, E or F.
e. For thickness of foundation walls, see Section 1 807. 1 .6.
f. Footings shall be permitted to support a roof in addition to the stipulated
number of floors. Footings supporting roof only shall be as required for sup-
porting one floor.
g. Plain concrete footings for Group R-3 occupancies shall be permitted to be 6
inches thick.
1809.9 Masonry-unit footings. The design, materials and
construction of masonry-unit footings shall comply with Sec-
tions 1809.9.1 and 1809.9.2, and the provisions of Chapter 21.
Exception: Where a specific design is not provided,
masonry-unit footings supporting walls of light-frame con-
struction shall be permitted to be designed in accordance
with Table 1809.7.
1809.9.1 Dimensions. Mansonry-unit footings shall be
laid in Type M or S mortar complying with Section 2103.8
and the depth shall not be less than twice the projection
beyond the wall, pier or column. The width shall not be less
than 8 inches (203 mm) wider than the wall supported
thereon.
1809.9.2 Offsets. The maximum offset of each course in
brick foundation walls stepped up from the footings shall be
IV2 inches (38 mm) where laid in single courses, and 3
inches (76 mm) where laid in double courses.
1809.10 Pier and curtain wall foundations. Except in 5'^/^-
mic Design Categories D, E and F, pier and curtain wall foun-
dations shall be permitted to be used to support light-frame
construction not more than two stories above grade plane, pro-
vided the following requirements are met:
1. All load-bearing walls shall be placed on continuous
concrete footings bonded integrally with the exterior
wall footings.
2. The minimum actual thickness of a load-bearing
masonry wall shall not be less than 4 inches (102 mm)
nominal or 3Vg inches (92 mm) actual thickness, and
shall be bonded integrally with piers spaced 6 feet (1829
mm) on center (o.c).
2010 CALIFORNIA BUILDING CODE
191
SOILS AND FOUNDATIONS
3. Piers shall be constructed in accordance with Chapter 21
and the following:
3.1. The unsupported height of the masonry piers
shall not exceed 10 times their least dimension.
3.2. Where structural clay tile or hollow concrete
masonry units are used for piers supporting
beams and girders, the cellular spaces shall be
filled solidly with concrete or Type M or S mor-
tar.
Exception: Unfilled hollow piers shall be permitted
where the unsupported height of the pier is not more
than four times its least dimension.
3.3. Hollow piers shall be capped with 4 inches
(102 mm) of solid masonry or concrete or the
cavities of the top course shall be filled with
concrete or grout.
4. The maximum height of a 4-inch ( 1 02 mm) load-bearing
masonry foundation wall supporting wood frame walls
and floors shall not be more than 4 feet (1219 mm) in
height.
5. The unbalanced fill for 4-inch (102 mm) foundation
walls shall not exceed 24 inches (610 mm) for solid
masonry, nor 12 inches (305 mm) for hollow masonry.
1809.11 Steel grillage footings. Grillage footings of structural
steel shapes shall be separated with approved steel spacers and
be entirely encased in concrete with at least 6 inches (152 mm)
on the bottom and at least 4 inches (102 mm) at all other points.
The spaces between the shapes shall be completely filled with
concrete or cement grout.
1809.12 Timber footings. Timber footings shall be permitted
for buildings of Type V construction and as otherwise
approved by the building official Such footings shall be treated
in accordance with AWPA Ul (Commodity Specification A,
Use Category 4B). Treated timbers are not required where
placed entirely below permanent water level, or where used as
capping for wood piles that project above the water level over
submerged or marsh lands. The compressive stresses perpen-
dicular to grain in untreated timber footings supported upon
treated piles shall not exceed 70 percent of the allowable
stresses for the species and grade of timber as specified in the
AF&PANDS.
1809.13 Footing seismic ties. Where a structure is assigned to
Seismic Design Category D, E or F in accordance with Section
1613, individual spread footings founded on soil defined in
Section 1613.5.2 as Site Class E or F shall be interconnected by
ties. Unless it is demonstrated that equivalent restraint is pro-
vided by reinforced concrete beams within slabs on grade or
reinforced concrete slabs on grade, ties shall be capable of car-
rying, in tension or compression, a force equal to the lesser of
the product of the larger footing design gravity load times the
seismic coefficient, ^^i^, divided by 10 and 25 percent of the
smaller footing design gravity load.
SECTION 1810
DEEP FOUNDATIONS
1810.1 General. Deep foundations shall be analyzed,
designed, detailed and installed in accordance with Sections
1810.1 through 1810.4.
1810.1.1 Geotechnical investigation. Deep foundations
shall be designed and installed on the basis of a geotechnical
investigation as set forth in Section 1803.
1810.1.2 Use of existing deep foundation elements. Deep
foundation elements left in place where a structure has been
demolished shall not be used for the support of new con-
struction unless satisfactory evidence is submitted to the
building official, which indicates that the elements are
sound and meet the requirements of this code. Such ele-
ments shall be load tested or redriven to verify their capaci-
ties. The design load applied to such elements shall be the
lowest allowable load as determined by tests or redriving
data.
1810.1.3 Deep foundation elements classified as col-
umns. Deep foundation elements standing unbraced in air,
water or fluid soils shall be classified as columns and
designed as such in accordance with the provisions of this
code from their top down to the point where adequate lateral
support is provided in accordance with Section 1810.2.1.
Exception: Where the unsupported height to least hori-
zontal dimension of a cast-in-place deep foundation ele-
ment does not exceed three, it shall be permitted to
design and construct such an element as a pedestal in
accordance with ACI 318.
1810.1.4 Special types of deep foundations. The use of
types of deep foundation elements not specifically men-
tioned herein is permitted, subject to the approval of the
building official, upon the submission of acceptable test
data, calculations and other information relating to the
structural properties and load capacity of such elements.
The allowable stresses for materials shall not in any case
exceed the limitations specified herein.
1810.2 Analysis. The analysis of deep foundations for design
shall be in accordance with Sections 1810.2.1 through
1810.2.5.
1810.2.1 Lateral support. Any soil other than fluid soil
shall be deemed to afford sufficient lateral support to pre-
vent buckling of deep foundation elements and to permit the
design of the elements in accordance with accepted engi-
neering practice and the applicable provisions of this code.
Where deep foundation elements stand unbraced in air,
water or fluid soils, it shall be permitted to consider them
laterally supported at a point 5 feet (1524 mm) into stiff soil
or 10 feet (3048 mm) into soft soil unless otherwise
approved by the building official on the basis of a geotechni-
cal investigation by a registered design professional.
1810.2.2 Stability. Deep foundation elements shall be
braced to provide lateral stability in all directions. Three or
more elements connected by a rigid cap shall be considered
braced, provided that the elements are located in radial
directions from the centroid of the group not less than 60
192
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
degrees (1 rad) apart. A two-element group in a rigid cap
shall be considered to be braced along the axis connecting
the two elements. Methods used to brace deep foundation
elements shall be subject to the approval of the building offi-
cial.
Deep foundation elements supporting walls shall be
placed alternately in lines spaced at least 1 foot (305 mm)
apart and located symmetrically under the center of gravity
of the wall load carried, unless effective measures are taken
to provide for eccentricity and lateral forces, or the founda-
tion elements are adequately braced to provide for lateral
stability.
Exceptions:
1. Isolated cast-in-place deep foundation elements
without lateral bracing shall be permitted where
the least horizontal dimension is no less than 2 feet
(610 mm), adequate lateral support in accordance
with Section 1810.2.1 is provided for the entire
height and the height does not exceed 12 times the
least horizontal dimension.
2. A single row of deep foundation elements without
lateral bracing is permitted for one- and two-fam-
ily dwellings and lightweight construction not
exceeding two stories above grade plane or 35 feet
(10 668 mm) in building height, provided the cen-
ters of the elements are located within the width of
the supported wall.
1810.2.3 Settlement. The settlement of a single deep foun-
dation element or group thereof shall be estimated based on
approved methods of analysis. The predicted settlement
shall cause neither harmful distortion of, nor instability in,
the structure, nor cause any element to be loaded beyond its
capacity.
1810.2.4 Lateral loads. The moments, shears and lateral
deflections used for design of deep foundation elements
shall be estabUshed considering the nonlinear interaction of
the shaft and soil, as determined by a registered design pro-
fessional. Where the ratio of the depth of embedment of the
element to its least horizontal dimension is less than or equal
to six, it shall be permitted to assume the element is rigid.
1810.2.4.1 Seismic Design Categories D through F.
For structures assigned to Seismic Design Category D, E
or F, deep foundation elements on Site Class E or F sites,
as determined in Section 1613.5.2, shall be designed and
constructed to withstand maximum imposed curvatures
from earthquake ground motions and structure response.
Curvatures shall include free-field soil strains modified
for soil-foundation-structure interaction coupled with
foundation element deformations associated with earth-
quake loads imparted to the foundation by the structure.
Exception: Deep foundation elements that satisfy the
following additional detailing requirements shall be
deemed to comply with the curvature capacity
requirements of this section.
1. Precast prestressed concrete piles detailed in
accordance with Section 1810.3.8.3.3.
2. Cast-in-place deep foundation elements with a
minimum longitudinal reinforcement ratio of
0.005 extending the full length of the element
and detailed in accordance with Sections
21.6.4.2, 21.6.4.3 and 21.6.4.4 of ACT 318 as
required by Section 1810.3.9.4.2.2.
1810.2.5 Group effects. The analysis shall include group
effects on lateral behavior where the center-to-center spac-
ing of deep foundation elements in the direction of lateral
force is less than eight times the least horizontal dimension
of an element. The analysis shall include group effects on
axial behavior where the center-to-center spacing of deep
foundation elements is less than three times the least hori-
zontal dimension of an element.
1810.3 Design and detailing. Deep foundations shall be
designed and detailed in accordance with Sections 1810.3.1
through 1810.3.12.
1810.3.1 Design conditions. Design of deep foundations
shall include the design conditions specified in Sections
1810.3.1.1 through 1810.3.1.6, as applicable.
1810.3.1.1 Design methods for concrete elements.
Where concrete deep foundations are laterally supported
in accordance with Section 1810.2. 1 for the entire height
and applied forces cause bending moments no greater
than those resulting from accidental eccentricities, struc-
tural design of the element using the load combinations
of Section 1605.3 and the allowable stresses specified in
this chapter shall be permitted. Otherwise, the structural
design of concrete deep foundation elements shall use
the load combinations of Section 1605.2 and approved
strength design methods.
1810.3.1.2 Composite elements. Where a single deep
foundation element comprises two or more sections of
different materials or different types spliced together,
each section of the composite assembly shall satisfy the
applicable requirements of this code, and the maximum
allowable load in each section shall be limited by the
structural capacity of that section.
1810.3.1.3 Mislocation. The foundation or superstruc-
ture shall be designed to resist the effects of the
mislocation of any deep foundation element by no less
than 3 inches (76 mm). To resist the effects of
mislocation, compressive overload of deep foundation
elements to 110 percent of the allowable design load
shall be permitted.
1810.3.1.4 Driven piles. Driven piles shall be designed
and manufactured in accordance with accepted engineer-
ing practice to resist all stresses induced by handling,
driving and service loads.
1810.3.1.5 Helical piles. Helical piles shall be designed
and manufactured in accordance with accepted engineer-
ing practice to resist all stresses induced by installation
into the ground and service loads.
1810JJ.5.1 Helical Piles Seismic Requirements,
[OSHPD 2] For structures assigned to Seismic
Design Category D.EorF, capacities of helical piles
shall be determined in accordance with Section
2010 CALIFORNIA BUILDING CODE
193
SOILS AND FOUNDATIONS
1810.3.3 by at least two project specific preproduc-
tion tests for each soil profile, size and depth of helical
pile. At least two percent of all production piles shall
be proof tested to design ultimate strength determined
by using load combinations in Section 1605.2.1.
Helical piles shall satisfy corrosion resistance
requirements oflCC-ESAC 358. In addition, all heli-
cal pile materials that are subject to corrosion shall
include at least Vj^-inch corrosion allowance.
Helical piles shall not be considered as carrying
any horizontal loads.
1810.3.1.6 Casings. Temporary and permanent casings
shall be of steel and shall be sufficiently strong to resist
collapse and sufficiently water tight to exclude any for-
eign materials during the placing of concrete. Where a
permanent casing is considered reinforcing steel, the
steel shall be protected under the conditions specified in
Section 1810.3.2.5. Horizontal joints in the casing shall
be spliced in accordance with Section 1810.3.6.
1810.3.2 Materials. The materials used in deep foundation
elements shall satisfy the requirements of Sections
1810.3.2.1 through 1810.3.2.8, as applicable.
1810.3.2.1 Concrete. Where concrete is cast in a steel
pipe or where an enlarged base is formed by compacting
concrete, the maximum size for coarse aggregate shall be
V4 inch (19.1 mm). Concrete to be compacted shall have
a zero slump.
1810.3.2.1.1 Seismic hooks. For structures assigned
to Seismic Design Category C, D, E or F in accor-
dance with Section 1613, the ends of hoops, spirals
and ties used in concrete deep foundation elements
shall be terminated with seismic hooks, as defined in
ACI 318, and shall be turned into the confined con-
crete core.
1810.3.2.1.2 ACI 318 Equation (10-5). Where this
chapter requires detailing of concrete deep founda-
tion elements in accordance with Section 21.6.4.4 of
ACI 318, compliance with Equation (10-5) of ACI
318 shall not be required.
1810.3.2.2 Prestressing steel. Prestressing steel shall
conform to ASTM A 416.
1810.3.2.3 Structural steel. Structural steel piles, steel
pipe and fully welded steel piles fabricated from plates
shall conform to ASTM A 36, ASTM A 252, ASTM A
283, ASTM A 572, ASTM A 588, ASTM A 690, ASTM
A 913 or ASTM A 992.
1810.3.2.4 Timber. Timber deep foundation elements
shall be designed as piles or poles in accordance with
AF&PA NDS. Round timber elements shall conform to
ASTM D 25. Sawn timber elements shall conform to
DOC PS-20.
1810.3.2.4.1 Preservative treatment. Timber deep
foundation elements used to support permanent struc-
tures shall be treated in accordance with this section
unless it is established that the tops of the untreated
timber elements will be below the lowest
ground-water level assumed to exist during the life of
the structure. Preservative and minimum final reten-
tion shall be in accordance with AWPA Ul (Com-
modity Specification E, Use Category 4C) for round
timber elements and AWPA Ul (Commodity Specifi-
cation A, Use Category 4B) for sawn timber elements.
Preservative-treated timber elements shall be subject
to a quality control program administered by an
approved agency. Element cutoffs shall be treated in
accordance with AWPA M4.
1810.3.2.5 Protection of materials. Where boring
records or site conditions indicate possible deleterious
action on the materials used in deep foundation elements
because of soil constituents, changing water levels or
other factors, the elements shall be adequately protected
by materials, methods or processes approved by the
building official. Protective materials shall be applied to
the elements so as not to be rendered ineffective by
installation. The effectiveness of such protective mea-
sures for the particular purpose shall have been thor-
oughly established by satisfactory service records or
other evidence.
1810.3.2.6 Allowable stresses. The allowable stresses
for materials used in deep foundation elements shall not
exceed those specified in Table 1810.3.2.6.
1810.3.2.7 Increased allowable compressive stress for
cased cast-in-place elements. The allowable compres-
sive stress in the concrete shall be permitted to be
increased as specified in Table 1810.3.2.6 for those por-
tions of permanently cased cast-in-place elements that
satisfy all of the following conditions:
1. The design shall not use the casing to resist any
portion of the axial load imposed.
2. The casing shall have a sealed tip and be mandrel
driven.
3. The thickness of the casing shall not be less than
manufacturer's standard gage No. 14 (0.068 inch)
(1.75 mm).
4. The casing shall be seamless or provided with
seams of strength equal to the basic material and be
of a configuration that will provide confinement to
the cast-in-place concrete.
5. The ratio of steel yield strength {Fy) to specified
compressive strength {f '^) shall not be less than
six.
6. The nominal diameter of the element shall not be
greater than 16 inches (406 mm).
1810.3.2.8 Justification of higher allowable stresses.
Use of allowable stresses greater than those specified in
Section 1810.3.2.6 shall be permitted where supporting
data justifying such higher stresses is filed with the build-
ing official. Such substantiating data shall include:
1. A geotechnical investigation in accordance with
Section 1803; and
194
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
2. Load tests in accordance with Section
1810.3.3.1.2, regardless of the load supported by
the element.
The design and installation of the deep foundation ele-
ments shall be under the direct supervision of a regis-
tered design professional knowledgeable in the field of
soil mechanics and deep foundations who shall submit a
report to the building official stating that the elements as
installed satisfy the design criteria.
1810.3.3 Determination of allowable loads. The allow-
able axial and lateral loads on deep foundation elements
shall be determined by an approved formula, load tests or
method of analysis.
1810.3.3.1 Allowable axial load. The allowable axial
load on a deep foundation element shall be determined in
accordance with Sections 1810.3.3.1.1 through
1810.3.3.1.9.
1810.3.3.1.1 Driving criteria. The allowable com-
pressive load on any driven deep foundation element
where determined by the apphcation of an approved
driving formula shall not exceed 40 tons (356 kN).
For allowable loads above 40 tons (356 kN), the wave
equation method of analysis shall be used to estimate
driveability for both driving stresses and net displace-
ment per blow at the ultimate load. Allowable loads
shall be verified by load tests in accordance with Sec-
tion 1810.3.3.1.2. The formula or wave equation load
shall be determined for gravity-drop or power-actu-
ated hammers and the hammer energy used shall be
the maximum consistent with the size, strength and
weight of the driven elements. The use of a follower is
permitted only with the approval of the building offi-
cial. The introduction of fresh hammer cushion or pile
cushion material just prior to final penetration is not
permitted.
1810.3.3.1.2 Load tests. Where design compressive
loads are greater than those determined using the
allowable stresses specified in Section 1810.3.2.6,
where the design load for any deep foundation ele-
ment is in doubt, or where cast-in-place deep founda-
tion elements have an enlarged base formed either by
compacting concrete or by driving a precast base,
control test elements shall be tested in accordance
with ASTM D 1 143 or ASTM D 4945. At least one
element shall be load tested in each area of uniform
subsoil conditions. Where required by the building
official, additional elements shall be load tested where
TABLE 1810.3.2.6
ALLOWABLE STRESSES FOR MATERIALS USED IN DEEP FOUNDATION ELEMENTS
MATERIAL TYPE AND CONDITION
MAXIMUM ALLOWABLE STRESS ^
1 . Concrete or grout in compression"
Cast-in-place with a permanent casing in accordance with Section 1810,3.2.7
Cast-in-place in a pipe, tube, other permanent casing or rock
Cast-in-place without a permanent casing
Precast nonprestressed
Precast prestressed
0.4/',
0.33/',
0.3/',
0.33/',
0.33/', -0.27/,,
2. Nonprestressed reinforcement in compression
0.4/3, < 30,000 psi
3. Structural steel in compression
Cores within concrete-filled pipes or tubes
Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8
Pipes or tubes for micropiles
Other pipes, tubes or H-piles
Helical piles
0.5 Fy < 32,000 psi
0,5 F3,< 32,000 psi
0.4 Fy < 32,000 psi
0.35 Fy < 16,000 psi
0.6F^<0.5F,
4. Nonprestressed reinforcement in tension
Within micropiles
Other conditions
0.6/,
0.5/^ < 24,000 psi
5. Structural steel in tension
Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8
Other pipes, tubes or H-piles
Hehcal piles
0.5 Fy< 32,000 psi
0.35 F^< 16,000 psi
0.6F,.<0.5F„
6. Timber
In accordance with the AF&PA NDS
a. / \ is the specified compressive strength of the concrete or grout;^^ is the compressive stress on the gross concrete section due to effective prestress forces only /^ is
the specified yield strength of reinforcement; Fy is the specified minimum yield stress of structural steel; F,, is the specified minimum tensile stress of structural
steel.
b. The stresses specified apply to the gross cross-sectional area within the concrete surface. Where a temporary or permanent casing is used, the inside face of the cas-
ing shall be considered the concrete surface.
2010 CALIFORNIA BUILDING CODE
195
SOILS AND FOUNDATIONS
necessary to establish the safe design capacity. The
resulting allowable loads shall not be more than
one-half of the ultimate axial load capacity of the test
element as assessed by one of the published methods
hsted in Section 1810.3.3.1.3 with consideration for
the test type, duration and subsoil. The ultimate axial
load capacity shall be determined by a registered
design professional with consideration given to toler-
able total and differential settlements at design load in
accordance with Section 1810.2.3, In subsequent
installation of the balance of deep foundation ele-
ments, all elements shall be deemed to have a support-
ing capacity equal to that of the control element where
such elements are of the same type, size and relative
length as the test element; are installed using the same
or comparable methods and equipment as the test ele-
ment; are installed in similar subsoil conditions as the
test element; and, for driven elements, where the rate
of penetration (e.g., net displacement per blow) of
such elements is equal to or less than that of the test
element driven with the same hammer through a com-
parable driving distance.
1810.3.3.1.3 Load test evaluation methods. It shall
be permitted to evaluate load tests of deep foundation
elements using any of the following methods:
1. Davisson Offset Limit.
2. Brinch-Hansen 90% Criterion.
3. Butler-Hoy Criterion.
4. Other methods approved by the building offi-
cial.
1810.3.3.1.4 Allowable frictional resistance. The
assumed frictional resistance developed by any
uncased cast-in-place deep foundation element shall
not exceed one-sixth of the bearing value of the soil
material at minimum depth as set forth in Table
1 806.2, up to a maximum of 500 psf (24 kPa), unless a
greater value is allowed by the building official on the
basis of a geotechnical investigation as specified in
Section 1 803 or a greater value is substantiated by a
load test in accordance with Section 1810.3.3.1.2.
Frictional resistance and bearing resistance shall not
be assumed to act simultaneously unless determined
by a geotechnical investigation in accordance with
Section 1803.
1810.3.3.1.5 Uplift capacity of a single deep foun-
dation element. Where required by the design, the
uplift capacity of a single deep foundation element
shall be determined by an approved method of analy-
sis based on a minimum factor of safety of three or by
load tests conducted in accordance with ASTM D
3689. The maximum allowable uplift load shall not
exceed the ultimate load capacity as determined in
Section 1810.3.3.1.2, using the results of load tests
conducted in accordance with ASTM D 3689, divided
by a factor of safety of two.
Exception: Where uplift is due to wind or seismic
loading, the minimum factor of safety shall be two
where capacity is determined by an analysis and
one and one-half where capacity is determined by
load tests.
1810.3.3.1.6 Uplift capacity of grouped deep foun-
dation elements. For grouped deep foundation ele-
ments subjected to uplift, the allowable working uplift
load for the group shall be calculated by an approved
method of analysis where the deep foundation ele-
ments in the group are placed at a center-to-center
spacing of at least 2.5 times the least horizontal
dimension of the largest single element, the allowable
working uplift load for the group is permitted to be
calculated as the lesser of:
1. The proposed individual uplift working load
times the number of elements in the group.
2. Two-thirds of the effective weight of the group
and the soil contained within a block defined by
the perimeter of the group and the length of the
element.
1810.3.3.1.7 Load-bearing capacity. Deep founda-
tion elements shall develop ultimate load capacities of
at least twice the design working loads in the desig-
nated load-bearing layers. Analysis shall show that no
soil layer underlying the designated load-bearing lay-
ers causes the load-bearing capacity safety factor to
be less than two.
1810.3.3.1.8 Bent deep foundation elements. The
load-bearing capacity of deep foundation elements
discovered to have a sharp or sweeping bend shall be
determined by an approved method of analysis or by
load testing a representative element.
1810.3.3.1.9 Helical piles. The allowable axial
design load, P^, of helical piles shall be determined as
follows:
P. = 0.5P„
(Equation 18-4)
where P„ is the least value of:
1. Sum of the areas of the helical bearing plates
times the ultimate bearing capacity of the soil or
rock comprising the bearing stratum.
2. Ultimate capacity determined from well-docu-
mented correlations with installation torque.
3. Ultimate capacity determined from load tests.
4. Ultimate axial capacity of pile shaft.
5. Ultimate axial capacity of pile shaft couplings.
6. Sum of the ultimate axial capacity of helical
bearing plates affixed to pile.
1810.3.3.2 Allowable lateral load. Where required by
the design, the lateral load capacity of a single deep foun-
dation element or a group thereof shall be determined by
an approved method of analysis or by lateral load tests to
at least twice the proposed design working load. The
resulting allowable load shall not be more than one-half
of the load that produces a gross lateral movement of 1
inch (25 mm) at the lower of the top of foundation ele-
196
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
merit and the ground surface, unless it can be shown that
the predicted lateral movement shall cause neither harm-
ful distortion of, nor instability in, the structure, nor
cause any element to be loaded beyond its capacity.
1810.3.4 Subsiding soils. Where deep foundation elements
are installed through subsiding fills or other subsiding strata
and derive support from underlying firmer materials, con-
sideration shall be given to the downward frictional forces
that may be imposed on the elements by the subsiding upper
strata.
Where the influence of subsiding fills is considered as
imposing loads on the element, the allowable stresses speci-
fied in this chapter shall be permitted to be increased where
satisfactory substantiating data are submitted.
1810.3.5 Dimensions of deep foundation elements. The
dimensions of deep foundation elements shall be in accor-
dance with Sections 1810.3.5.1 through 1810.3.5.3, as
applicable.
1810.3.5.1 Precast. The minimum lateral dimension of
precast concrete deep foundation elements shall be 8
inches (203 mm). Comers of square elements shall be
chamfered.
1810.3.5.2 Cast-in-place or grouted-in-place. Cast-
in-place and grouted-in-place deep foundation elements
shall satisfy the requirements of this section.
1810.3.5.2.1 Cased. Cast-in-place deep foundation
elements with a permanent casing shall have a nomi-
nal outside diameter of not less than 8 inches (203
mm).
1810.3.5.2.2 Uncased. Cast-in-place deep founda-
tion elements without a permanent casing shall have a
diameter of not less than 12 inches (305 nmi). The ele-
ment length shall not exceed 30 times the average
diameter.
Exception: The length of the element is permitted
to exceed 30 times the diameter, provided the
design and installation of the deep foundations are
under the direct supervision of a registered design
professional knowledgeable in the field of soil
mechanics and deep foundations. The registered
design professional shall submit a report to the
building official stating that the elements were
installed in compliance with the approved con-
struction documents.
1810.3.5.2.3 Micropiles. Micropiles shall have an
outside diameter of 12 inches (305 mm) or less. The
minimum diameter set forth elsewhere in Section
1810.3.5 shall not apply to micropiles.
1810.3.5.3 Steel. Steel deep foundation elements shall
satisfy the requirements of this section.
1810.3.5.3.1 H-piles. Sections of H-piles shall com-
ply with the following:
1. The flange projections shall not exceed 14
times the minimum thickness of metal in either
the flange or the web and the flange widths shall
not be less than 80 percent of the depth of the
section.
2. The nominal depth in the direction of the web
shall not be less than 8 inches (203 mm).
3. Ranges and web shall have a minimum nomi-
nal thickness of Vg inch (9.5 mm).
1810.3.5.3.2 Steel pipes and tubes. Steel pipes and
tubes used as deep foundation elements shall have a
nominal outside diameter of not less than 8 inches
(203 mm). Where steel pipes or tubes are driven open
ended, they shall have a minimum of 0.34 square inch
(219 mm^) of steel in cross section to resist each 1,000
foot-pounds (1356 Nm) of pile hammer energy, or
shall have the equivalent strength for steels having a
yield strength greater than 35,000 psi (241 MPa) or
the wave equation analysis shall be permitted to be
used to assess compression stresses induced by driv-
ing to evaluate if the pile section is appropriate for the
selected hammer. Where a pipe or tube with wall
thickness less than 0.179 inch (4.6 nmi) is driven open
ended, a suitable cutting shoe shall be provided. Con-
crete-filled steel pipes or tubes in structures assigned
to Seismic Design Category C, D, E or F shall have a
wall thickness of not less than Vjg inch (5 mm). The
pipe or tube casing for socketed drilled shafts shall
have a nominal outside diameter of not less than 18
inches (457 mm), a wall thickness of not less than Vg
inch (9.5 mm) and a suitable steel driving shoe welded
to the bottom; the diameter of the rock socket shall be
approximately equal to the inside diameter of the cas-
ing.
Exceptions:
1. There is no minimum diameter for steel
pipes or tubes used in micropiles.
2. For mandrel-driven pipes or tubes, the mini-
mum wall thickness shall be Vjq inch (2.5
mm).
1810.3.5.3.3 Helical piles. Dimensions of the central
shaft and the number, size and thickness of helical
bearing plates shall be sufficient to support the design
loads.
1810.3.6 Splices. Splices shall be constructed so as to pro-
vide and maintain true alignment and position of the compo-
nent parts of the deep foundation element during installation
and subsequent thereto and shall be designed to resist the
axial and shear forces and moments occurring at the loca-
tion of the splice during driving and for design load combi-
nations. Where deep foundation elements of the same type
are being spliced, splices shall develop not less than 50 per-
cent of the bending strength of the weaker section. Where
deep foundation elements of different materials or different
types are being spliced, sphces shall develop the full com-
pressive strength and not less than 50 percent of the tension
and bending strength of the weaker section. Where struc-
tural steel cores are to be spliced, the ends shall be milled or
ground to provide full contact and shall be full-depth
welded.
2010 CALIFORNIA BUILDING CODE
197
SOILS AND FOUNDATIONS
Splices occurring in the upper 10 feet (3048 mm) of the
embedded portion of an element shall be designed to resist at
allowable stresses the moment and shear that would result
from an assumed eccentricity of the axial load of 3 inches (76
nmi), or the element shall be braced in accordance with Sec-
tion 1810.2.2 to other deep foundation elements that do not
have splices in the upper 10 feet (3048 mm) of embedment.
1810.3.6.1 Seismic Design Categories C through F.
For structures assigned to Seismic Design Category C, D,
E or F splices of deep foundation elements shall develop
the lesser of the following:
1. The full strength of the deep foundation element;
and
2, The axial and shear forces and moments from the
load combinations with overstrength factor in Sec-
tion 12 A3. 2 of ASCE 7.
1810.3.7 Top of element detailing at cutoffs. Where a mini-
mum length for reinforcement or the extent of closely spaced
confinement reinforcement is specified at the top of a deep
foundation element, provisions shall be made so that those
specified lengths or extents are maintained after cutoff.
1810.3.8 Precast concrete piles. Precast concrete piles
shall be designed and detailed in accordance with Sections
1810.3.8.1 through 1810.3.8.3.
1810.3.8.1 Reinforcement. Longitudinal steel shall be
arranged in a symmetrical pattern and be laterally tied
with steel ties or wire spiral spaced center to center as fol-
lows:
1 . At not more than 1 inch (25 mm) for the first five
ties or spirals at each end; then
2. At not more than 4 inches (102 nam), for the
remainder of the first 2 feet (610 mm) from each
end; and then
3. At not more than 6 inches (152 mm) elsewhere.
The size of ties and spirals shall be as follows:
1 . For piles having a least horizontal dimension of 1 6
inches (406 mm) or less, wire shall not be smaller
than 0.22 inch (5.6 mm) (No. 5 gage).
2. For piles having a least horizontal dimension of
more than 16 inches (406 mm) and less than 20
inches (508 mm), wire shall not be smaller than
0.238 inch (6 mm) (No. 4 gage).
3 . For piles having a least horizontal dimension of 20
inches (508 mm) and larger, wire shall not be
smaller than V4 inch (6.4 mm) round or 0.259 inch
(6.6 mm) (No. 3 gage).
1810.3.8.2 Precast nonprestressed piles. Precast
nonprestressed concrete piles shall comply with the
requirements of Sections 1810.3.8.2.1 through
1810.3.8.2.3.
1810.3.8.2.1 Minimum reinforcement. Longitudi-
nal reinforcement shall consist of at least four bars
with a minimum longitudinal reinforcement ratio of
0.008.
1810.3.8.2.2 Seismic reinforcement in Seismic
Design Categories C through F. For structures
assigned to Seismic Design Category C, D, E or F in
accordance with Section 1613, precast nonpre-
stressed piles shall be reinforced as specified in this
section. The minimum longitudinal reinforcement
ratio shall be 0.01 throughout the length. Transverse
reinforcement shall consist of closed ties or spirals
with a minimum Vg inch (9.5 mm) diameter. Spacing
of transverse reinforcement shall not exceed the
smaller of eight times the diameter of the smallest lon-
gitudinal bar or 6 inches (152 mm) within a distance
of three times the least pile dimension from the bot-
tom of the pile cap. Spacing of transverse reinforce-
ment shall not exceed 6 inches (152 mm) throughout
the remainder of the pile.
1810.3.8.2.3 Additional seismic reinforcement in
Seismic Design Categories D through F. For struc-
tures assigned to Seismic Design Category D, E or F
in accordance with Section 1613, transverse rein-
forcement shall be in accordance with Section
1810.3.9.4,2.
1810.3.8.3 Precast prestressed piles. Precast pre-
stressed concrete piles shall comply with the require-
ments of Sections 1810.3.8.3.1 through 1810.3.8.3.3.
1810.3.8.3.1 Effective prestress. The effective pre-
stress in the pile shall not be less than 400 psi (2.76
MPa) for piles up to 30 feet (9144 mm) in length, 550
psi (3.79 MPa) for piles up to 50 feet (15 240 mm) in
length and 700 psi (4.83 MPa) for piles greater than
50 feet (15 240 mm) in length.
Effective prestress shall be based on an assumed
loss of 30,000 psi (207 MPa) in the prestressing steel.
The tensile stress in the prestressing steel shall not
exceed the values specified in ACI 318.
1810.3.8.3.2 Seismic reinforcement in Seismic
Design Category C. For structures assigned to 5^/^-
mic Design Category C in accordance with Section
1613, precast prestressed piles shall have transverse
reinforcement in accordance with this section. The
volumetric ratio of spiral reinforcement shall not be
less than the amount required by the following for-
mula for the upper 20 feet (6096 mm) of the pile.
p,=0.12/V/,.
where:
(Equation 18-5)
f\ = Specified compressive strength of concrete,
psi (MPa).
fyh = Yield strength of spiral reinforcement
< 85,000 psi (586 MPa).
p^ = Spiral reinforcement index (vol, spiral/vol.
core).
At least one-half the volumetric ratio required by
Equation 18-5 shall be provided below the upper 20
feet (6096 mm) of the pile.
198
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1810.3.8.3.3 Seismic reinforcement in Seismic
Design Categories D through F. For structures
assigned to Seismic Design Category D, E or F in
accordance with Section 1613, precast prestressed
piles shall have transverse reinforcement in accor-
dance with the following:
1 . Requirements in ACI 318, Chapter 2 1 , need not
apply, unless specifically referenced,
2. Where the total pile length in the soil is 35 feet
(10 668 mm) or less, the lateral transverse rein-
forcement in the ductile region shall occur
through the length of the pile. Where the pile
length exceeds 35 feet (10 668 mm), the ductile
pile region shall be taken as the greater of 35
feet (10 668 nun) or the distance from the
underside of the pile cap to the point of zero cur-
vature plus three times the least pile dimension.
3. In the ductile region, the center-to-center spac-
ing of the spirals or hoop reinforcement shall
not exceed one-fifth of the least pile dimension,
six times the diameter of the longitudinal strand
or 8 inches (203 mm), whichever is smallest.
4. Circular spiral reinforcement shall be spliced
by lapping one full turn and bending the end of
each spiral to a 90-degree hook or by use of a
mechanical or welded splice complying with
Section 12.14.3 of ACI 318.
5. Where the transverse reinforcement consists of
circular spirals, the volumetric ratio of spiral
transverse reinforcement in the ductile region
shall comply with the following:
Ps =025(f\/fy,)(A^/A,,-L0)
[0.5 + 1.4P/(f',A,)]
(Equation 18-6)
but not less than:
Ps =0.12(f',//J[0.5 + 1.4P/(/-',Ap]
>0.12/V/,.
and need not exceed:
p, =0.021
where:
(Equation 18-7)
(Equation 18-8)
Ag = Pile cross-sectional area, square inches
(mm^).
A^ft = Core area defined by spiral outside diam-
eter, square inches (mm^).
f\= Specified compressive strength of con-
crete, psi (MPa)
fyf^ = Yield strength of spiral reinforcement
< 85,000 psi (586 MPa).
P = Axial load on pile, pounds (kN), as deter-
mined from Equations 16-5 and 16-7.
p= Volumetric ratio (vol. spiral/ vol. core).
This required amount of spiral reinforcement
is permitted to be obtained by providing an
inner and outer spiral.
Where transverse reinforcement consists of
rectangular hoops and cross ties, the total
cross-sectional area of lateral transverse rein-
forcement in the ductile region with spacing, 5,
and perpendicular dimension, /z^, shall conform
to:
A,,=03sKrc/fyk)(A,/A,,'hO)
[0,5 + lAP/(f\A^)]
(Equation 18-9)
but not less than:
A,, = 0. 12^ K (f'c Ifyn) [0.5 + 1 APHfc \)^
(Equation 18-10)
where:
/,, = < 70,000 psi (483 MPa).
h^ = Cross-sectional dimension of pile core
measured center to center of hoop rein-
forcement, inch (mm).
s = Spacing of transverse reinforcement
measured along length of pile, inch
(mm).
A^f^ = Cross-sectional area of tranverse rein-
forcement, square inches (mm^).
f\ = Specified compressive strength of con-
crete, psi (MPa).
The hoops and cross ties shall be equivalent to
deformed bars not less than No. 3 in size. Rectangular
hoop ends shall terminate at a comer with seismic
hooks.
Outside of the length of the pile requiring trans-
verse confinement reinforcing, the spiral or hoop
reinforcing with a volumetric ratio not less than
one-half of that required for transverse confinement
reinforcing shall be provided.
1810.3.9 Cast-in-place deep foundations. Cast-in-place
deep foundation elements shall be designed and detailed in
accordance with Sections 1810.3.9.1 through 1810.3.9.6.
1810.3.9.1 Design cracliing moment. The design
cracking moment ((|)M„) for a cast-in-place deep founda-
tion element not enclosed by a structural steel pipe or
tube shall be determined using the following equation:
<l>M„=34fX.
(Equation 18-11)
where:
2010 CALIFORNIA BUILDING CODE
199
SOILS AND FOUNDATIONS
f'c=- Specified compressive strength of concrete or
grout, psi (MPa)
S^ = Elastic section modulus, neglecting reinforce-
ment and casing, cubic inches (mm^)
1810.3.9.2 Required reinforcement. Where subject to
uplift or where the required moment strength determined
using the load combinations of Section 1605.2 exceeds
the design cracking moment determined in accordance
with Section 1810.3,9.1, cast-in-place deep foundations
not enclosed by a structural steel pipe or tube shall be
reinforced.
1810.3.9.3 Placement of reinforcement. Reinforce-
ment where required shall be assembled and tied
together and shall be placed in the deep foundation ele-
ment as a unit before the reinforced portion of the ele-
ment is filled with concrete.
Exceptions:
1. Steel dowels embedded 5 feet (1524 mm) or
less shall be permitted to be placed after con-
creting, while the concrete is still in a semifluid
state.
2. For deep foundation elements installed with a
hollow-stem auger, tied reinforcement shall be
placed after elements are concreted, while the
concrete is still in a semifluid state. Longitudi-
nal reinforcement without lateral ties shall be
placed either through the hollow stem of the
auger prior to concreting or after concreting,
while the concrete is still in a semifluid state.
3. For Group R-3 and U occupancies not exceed-
ing two stories of light-frame construction,
reinforcement is permitted to be placed after
concreting, while the concrete is still in a semi-
fluid state, and the concrete cover requirement
is permitted to be reduced to 2 inches (51 mm),
provided the construction method can be dem-
onstrated to the satisfaction of the building offi-
cial
1810.3.9.4 Seismic reinforcement. Where a structure is
assigned to Seismic Design Category C, reinforcement
shall be provided in accordance with Section
1810.3.9.4.1. Where a structure is assigned to Seismic
Design Category D, E or F, reinforcement shall be pro-
vided in accordance with Section 1810.3.9.4.2.
Exceptions:
1. Isolated deep foundation elements supporting
posts of Group R-3 and U occupancies not
exceeding two stories of light-frame construc-
tion shall be permitted to be reinforced as
required by rational analysis but with not less
than one No. 4 bar, without ties or spirals,
where detailed so the element is not subject to
lateral loads and the soil provides adequate lat-
eral support in accordance with Section
1810.2.1.
2. Isolated deep foundation elements supporting
posts and bracing from decks and patios appur-
tenant to Group R-3 and U occupancies not
exceeding two stories of light- frame construc-
tion shall be permitted to be reinforced as
required by rational analysis but with not less
than one No. 4 bar, without ties or spirals,
where the lateral load, E, to the top of the ele-
ment does not exceed 200 pounds (890 N) and
the soil provides adequate lateral support in
accordance with Section 1810.2.1.
3. Deep foundation elements supporting the con-
crete foundation wall of Group R-3 and U occu-
pancies not exceeding two stories of
light-frame construction shall be permitted to
be reinforced as required by rational analysis
but with not less than two No. 4 bars, without
ties or spirals, where the design cracking
moment determined in accordance with Section
1810.3.9.1 exceeds the required moment
strength determined using the load combina-
tions with overstrength factor in Section
12.4.3.2 of ASCE 7 and the soil provides ade-
quate lateral support in accordance with Sec-
tion 1810.2.1.
4. Closed ties or spirals where required by Section
1810.3.9.4.2 shall be permitted to be limited to
the top 3 feet (914 nun) of deep foundation ele-
ments 10 feet (3048 mm) or less in depth sup-
porting Group R-3 and U occupancies of
Seismic Design Category D, not exceeding two
stories of light-frame construction.
1810.3.9.4.1 Seismic reinforcement in Seismic
Design Category C. For structures assigned to Seis-
mic Design Category C in accordance with Section
1613, cast-in-place deep foundation elements shall be
reinforced as specified in this section. Reinforcement
shall be provided where required by analysis.
A minimum of four longitudinal bars, with a mini-
mum longitudinal reinforcement ratio of 0.0025, shall
be provided for throughout the minimum reinforced
length of the element as defined below starting at the
top of the element. The minimum reinforced length of
the element shall be taken as the greatest of the fol-
lowing:
1. One-third of the element length;
2. A distance of 10 feet (3048 mm);
3. Three times the least element dimension; and
4. The distance from the top of the element to the
point where the design cracking moment deter-
mined in accordance with Section 1810.3.9.1
exceeds the required moment strength deter-
mined using the load combinations of Section
1605.2.
Transverse reinforcement shall consist of closed
ties or spirals with a minimum Vg inch (9.5 mm) diam-
eter. Spacing of transverse reinforcement shall not
200
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
exceed the smaller of 6 inches (152 mm) or 8-longitu-
dinal-bar diameters, within a distance of three times
the least element dimension from the bottom of the
pile cap. Spacing of transverse reinforcement shall
not exceed 16 longitudinal bar diameters throughout
the remainder of the reinforced length.
Exceptions:
1. The requirements of this section shall not
apply to concrete cast in structural steel
pipes or tubes.
2. A spiral- welded metal casing of a thickness
not less than manufacturer's standard gage
No. 14 gage (0.068 inch) is permitted to pro-
vide concrete confinement in lieu of the
closed ties or spirals. Where used as such,
the metal casing shall be protected against
possible deleterious action due to soil con-
stituents, changing water levels or other fac-
tors indicated by boring records of site
conditions.
1810.3.9.4.2 Seismic reinforcement in Seismic
Design Categories D through F. For structures
assigned to Seismic Design Category D, E or F in
accordance with Section 1613, cast-in-place deep
foundation elements shall be reinforced as specified
in this section. Reinforcement shall be provided
where required by analysis.
A minimum of four longitudinal bars, with a mini-
mum longitudinal reinforcement ratio of 0.005, shall
be provided throughout the minimum reinforced
length of the element as defined below starting at the
top of the element. The minimum reinforced length of
the element shall be taken as the greatest of the fol-
lowing:
1 . One-half of the element length;
2. A distance of 10 feet (3048 mm);
3. Three times the least element dimension; and
4. The distance from the top of the element to the
point where the design cracking moment deter-
mined in accordance with Section 1810.3.9.1
exceeds the required moment strength deter-
mined using the load combinations of Section
1605.2.
Transverse reinforcement shall consist of closed
ties or spirals no smaller than No. 3 bars for elements
with a least dimension up to 20 inches (508 nun), and
No. 4 bars for larger elements. Throughout the
remainder of the reinforced length outside the regions
with transverse confinement reinforcement, as speci-
fied in Section 1810.3.9.4.2.1 or 1810.3.9.4.2.2, the
spacing of transverse reinforcement shall not exceed
the least of the following:
1. 12 longitudinal bar diameters;
2. One-half the least dimension of the element;
and
3. 12 inches (305 mm).
Exceptions:
1. The requirements of this section shall not
apply to concrete cast in structural steel
pipes or tubes.
2. A spiral-welded metal casing of a thickness
not less than manufacturer's standard gage
No. 14 gage (0.068 inch) is permitted to pro-
vide concrete confinement in lieu of the
closed ties or spirals. Where used as such,
the metal casing shall be protected against
possible deleterious action due to soil con-
stituents, changing water levels or other fac-
tors indicated by boring records of site
conditions.
1810.3.9.4.2.1 Site Classes A through D. For Site
Class A, B, C or D sites, transverse confinement
reinforcement shall be provided in the element in
accordance with Sections 21.6.4.2, 21.6.4.3 and
21.6.4.4 of ACI 318 within three times the least
element dimension of the bottom of the pile cap. A
transverse spiral reinforcement ratio of not less
than one-half of that required in Section
21. 6.4.4(a) of ACI 318 shall be permitted.
1810.3.9.4.2.2 Site Classes E and F. For Site
Class E or F sites, transverse confinement rein-
forcement shall be provided in the element in
accordance with Sections 21.6.4.2, 21.6.4.3 and
21.6.4.4 of ACI 318 within seven times the least
element dimension of thfe pile cap and within seven
times the least element dimension of the interfaces
of strata that are hard or stiff and strata that are
liquefiable or are composed of soft- to medium-
stiff clay.
1810.3.9.5 Belled drilled shafts. Where drilled shafts
are belied at the bottom, the edge thickness of the bell
shall not be less than that required for the edge of foot-
ings. Where the sides of the bell slope at an angle less
than 60 degrees (1 rad) from the horizontal, the effects of
vertical shear shall be considered.
1810.3.9.6 Socketed drilled shafts. Socketed drilled
shafts shall have a permanent pipe or tube casing that
extends down to bedrock and an uncased socket drilled
into the bedrock, both filled with concrete. Socketed
drilled shafts shall have reinforcement or a structural
steel core for the length as indicated by an approved
method of analysis.
The depth of the rock socket shall be sufficient to
develop the full load-bearing capacity of the element
with a minimum safety factor of two, but the depth shall
not be less than the outside diameter of the pipe or tube
casing. The design of the rock socket is permitted to be
predicated on the sum of the allowable load-bearing
pressure on the bottom of the socket plus bond along the
sides of the socket.
2010 CALIFORNIA BUILDING CODE
201
SOILS AND FOUNDATIONS
Where a structural steel core is used, the gross
cross-sectional area of the core shall not exceed 25 per-
cent of the gross area of the drilled shaft.
1810.3.10 Micropiles. Micropiles shall be designed and
detailed in accordance with Sections 1810.3.10.1 through
1810.3.10.4.
1810.3.10.1 Construction. Micropiles shall develop
their load-carrying capacity by means of a bond zone in
soil, bedrock or a combination of soil and bedrock.
Micropiles shall be grouted and have either a steel pipe or
tube or steel reinforcement at every section along the
length. It shall be permitted to transition from deformed
reinforcing bars to steel pipe or tube reinforcement by
extending the bars into the pipe or tube section by at least
their development length in tension in accordance with
ACI318.
1810.3.10.2 Materials. Reinforcement shall consist of
deformed reinforcing bars in accordance with ASTM A
615 Grade 60 or 75 or ASTM A 722 Grade 150.
The steel pipe or tube shall have a minimum wall
thickness of Vj^ inch (4.8 mm). Splices shall comply with
Section 1 8 10.3.6. The steel pipe or tube shall have a min-
imum yield strength of 45,000 psi (310 MPa) and a mini-
mum elongation of 15 percent as shown by mill
certifications or two coupon test samples per 40,000
pounds (18 160 kg) of pipe or tube.
1810.3.10.3 Reinforcement. For micropiles or portions
thereof grouted inside a temporary or permanent casing
or inside a hole drilled into bedrock or a hole drilled with
grout, the steel pipe or tube or steel reinforcement shall
be designed to carry at least 40 percent of the design
compression load. Micropiles or portions thereof
grouted in an open hole in soil without temporary or per-
manent casing and without suitable means of verifying
the hole diameter during grouting shall be designed to
carry the entire compression load in the reinforcing steel.
Where a steel pipe or tube is used for reinforcement, the
portion of the grout enclosed within the pipe is permitted
to be included in the determination of the allowable
stress in the grout.
1810.3.10.4 Seismic reinforcement. For structures
assigned to Seismic Design Category C, a permanent
steel casing shall be provided from the top of the
micropile down to the point of zero curvature. For struc-
tures assigned to Seismic Design Category D, E or F, the
micropile shall be considered as an alternative system in
accordance with Section 1810.8.4.1, Chapter 1, Division
II. The alternative system design, supporting documen-
tation and test data shall be submitted to the building offi-
cial for review and approval.
1810.3J0.4J Seismic requirements. [OSHPD 2]
For structures assigned to Seismic Design Category
D,EorF, a permanent steel casing having a minimum
thickness o/Vg-inch shall be provided from the top of
the micropile down to a minimum of 1 20 percent of the
point of zero curvature. Capacity of micropiles shall
be determined in accordance with Section 1810.3.3
by at least two project specific pre-production tests
for each soil profile, size and depth of micropile. At
least two percent of all production piles shall be proof
tested to design ultimate strength determined by using
load combinations in Section 1605.2.1.
Steel casing length in soil shall be considered as
unbonded and shall not be considered as contributing
to friction. Casing shall provide confinement at least
equivalent to hoop reinforcing required by ACI 318
Section 21.12.4.
Reinforcement shall have Class 1 corrosion protec-
tion in accordance with PTI Recommendations for
P res tressed Rock and Soil Anchors. Steel casing
design shall include at least V/^" corrosion allow-
ance.
Micropiles shall not be considered as carrying any
horizontal loads.
1810.3.11 Pile caps. Pile caps shall be of reinforced con-
crete, and shall include all elements to which vertical deep
foundation elements are connected, including grade beams
and mats. The soil immediately below the pile cap shall not
be considered as carrying any vertical load. The tops of ver-
tical deep foundation elements shall be embedded not less
than 3 inches (76 mm) into pile caps and the caps shall
extend at least 4 inches (102 mm) beyond the edges of the
elements. The tops of elements shall be cut or chipped back
to sound material before capping.
1810.3.11.1 Seismic Design Categories C through F.
For structures assigned to Seismic Design Category C, D,
E or F in accordance with Section 1613, concrete deep
foundation elements shall be connected to the pile cap by
embedding the element reinforcement or field-placed
dowels anchored in the element into the pile cap for a dis-
tance equal to their development length in accordance
with ACI 318. It shall be permitted to connect precast
prestressed piles to the pile cap by developing the ele-
ment prestressing strands into the pile cap provided the
connection is ductile. For deformed bars, the develop-
ment length is the full development length for compres-
sion, or tension in the case of uplift, without reduction for
excess reinforcement in accordance with Section 12.2.5
of ACI 318. Alternative measures for laterally confining
concrete and maintaining toughness and ductile-like
behavior at the top of the element shall be permitted pro-
vided the design is such that any hinging occurs in the
confined region.
The minimum transverse steel ratio for confinement
shall not be less than one-half of that required for col-
unms.
For resistance to uplift forces, anchorage of steel
pipes, tubes or H-piles to the pile cap shall be made by
means other than concrete bond to the bare steel section.
Concrete-filled steel pipes or tubes shall have reinforce-
ment of not less than 0.01 times the cross-sectional area
of the concrete fill developed into the cap and extending
into the fill a length equal to two times the required cap
embedment, but not less than the development length in
tension of the reinforcement.
202
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1810.3.11.2 Seismic Design Categories D tlirough F.
For structures assigned to Seismic Design Category D, E
or F in accordance with Section 1613, deep foundation
element resistance to uplift forces or rotational restraint
shall be provided by anchorage into the pile cap,
designed considering the combined effect of axial forces
due to uplift and bending moments due to fixity to the
pile cap. Anchorage shall develop a minimum of 25 per-
cent of the strength of the element in tension. Anchorage
into the pile cap shall be capable of developing the fol-
lowing:
1. In the case of uplift, the least of the following:
nominal tensile strength of the longitudinal rein-
forcement in a concrete element; the nominal ten-
sile strength of a steel element; the frictional force
developed between the element and the soil multi-
plied by 1.3; and the axial tension force resulting
from the load combinations with overstrength fac-
tor in Section 12.4.3.2 of ASCE 7.
2. In the case of rotational restraint, the lesser of the
following: the axial force, shear forces and bend-
ing moments resulting from the load combinations
with overstrength factor in Section 12.4.3.2 of
ASCE 7 or development of the full axial, bending
and shear nominal strength of the element.
Where the vertical lateral- force-resisting elements are
columns, the pile cap flexural strengths shall exceed the
column flexural strength. The connection between batter
piles and pile caps shall be designed to resist the nominal
strength of the pile acting as a short column. Batter piles
and their connection shall be capable of resisting forces
and moments from the load combinations with
overstrength factor in Section 12.4.3.2 of ASCE 7.
1810.3.12 Grade beams. For structures assigned to Seismic
Design Category D, E or F in accordance with Section 1613,
grade beams shall comply with the provisions in Section
2 1 . 1 2.3 of ACI 3 1 8 for grade beams, except where they have
the capacity to resist the forces from the load combinations
with overstrength factor in Section 12.4.3.2 of ASCE 7.
1810.3.13 Seismic ties. For structures assigned to Seismic
Design Category C, D, E or F in accordance with Section
1613, individual deep foundations shall be interconnected
by ties. Unless it can be demonstrated that equivalent
restraint is provided by reinforced concrete beams within
slabs on grade or reinforced concrete slabs on grade or con-
finement by competent rock, hard cohesive soils or very
dense granular soils, ties shall be capable of carrying, in ten-
sion or compression, a force equal to the lesser of the prod-
uct of the larger pile cap or column design gravity load times
the seismic coefficient, S^s^ divided by 10, and 25 percent of
the smaller pile or column design gravity load.
Exception: In Group R-3 and U occupancies of
light-frame construction, deep foundation elements sup-
porting foundation walls, isolated interior posts detailed
so the element is not subject to lateral loads or exterior
decks and patios are not subject to interconnection where
the soils are of adequate stiffness, subject to the approval
of the building official.
1810.4 Installation. Deep foundations shall be installed in
accordance with Section 1810.4. Where a single deep founda-
tion element comprises two or more sections of different mate-
rials or different types spliced together, each section shall
satisfy the applicable conditions of installation.
1810.4.1 Structural integrity. Deep foundation elements
shall be installed in such a manner and sequence as to pre-
vent distortion or damage that may adversely affect the
structural integrity of adjacent structures or of foundation
elements being installed or already in place and as to avoid
compacting the surrounding soil to the extent that other
foundation elements cannot be installed properly.
1810.4.1.1 Compressive strength of precast concrete
piles. A precast concrete pile shall not be driven before the
concrete has attained a compressive strength of at least 75
percent of the specified compressive strength (f\), but not
less than the strength sufficient to withstand handling and
driving forces.
1810.4.1.2 Casing. Where cast-in-place deep founda-
tion elements are formed through unstable soils and con-
crete is placed in an open-drilled hole, a casing shall be
inserted in the hole prior to placing the concrete. Where
the casing is withdrawn during concreting, the level of
concrete shall be maintained above the bottom of the cas-
ing at a sufficient height to offset any hydrostatic or lat-
eral soil pressure. Driven casings shall be mandrel driven
their full length in contact with the surrounding soil.
1810.4.1.3 Driving near uncased concrete. Deep foun-
dation elements shall not be driven within six element
diameters center to center in granular soils or within
one-half the element length in cohesive soils of an
uncased element filled with concrete less than 48 hours
old unless approved by the building official. If the con-
crete surface in any completed element rises or drops, the
element shall be replaced. Driven uncased deep founda-
tion elements shall not be installed in soils that could
cause heave.
1810.4.1.4 Driving near cased concrete. Deep founda-
tion elements shall not be driven within four and one-half
average diameters of a cased element filled with concrete
less than 24 hours old unless approved by the building
official. Concrete shall not be placed in casings within
heave range of driving.
1810.4.1.5 Defective timber piles. Any substantial sud-
den increase in rate of penetration of a timber pile shall
be investigated for possible damage. If the sudden
increase in rate of penetration cannot be correlated to soil
strata, the pile shall be removed for inspection or
rejected.
1810.4.2 Identification. Deep foundation materials shall be
identified for conformity to the specified grade with this
identity maintained continuously from the point of manu-
facture to the point of installation or shall be tested by an
approved agency to determine conformity to the specified
grade. The approved agency shall furnish an affidavit of
compHance to the building official
2010 CALIFORNIA BUILDING CODE
203
SOILS AND FOUNDATIONS
1810.4.3 Location plan. A plan showing the location and
designation of deep foundation elements by an identifica-
tion system shall be filed with the building official prior to
installation of such elements. Detailed records for elements
shall bear an identification corresponding to that shown on
the plan.
1810.4.4 Preexcavation. The use of jetting, augering or
other methods of preexcavation shall be subject to the
approval of the building official. Where permitted,
preexcavation shall be carried out in the same manner as
used for deep foundation elements subject to load tests and
in such a manner that will not impair the carrying capacity of
the elements already in place or damage adjacent structures.
Element tips shall be driven below the preexcavated depth
until the required resistance or penetration is obtained.
1810.4.5 Vibratory driving. Vibratory drivers shall only be
used to install deep foundation elements where the element
load capacity is verified by load tests in accordance with
Section 1810.3.3.1.2. The installation of production ele-
ments shall be controlled according to power consumption,
rate of penetration or other approved means that ensure ele-
ment capacities equal or exceed those of the test elements.
1810.4.6 Heaved elements. Deep foundation elements that
have heaved during the driving of adjacent elements shall be
redriven as necessary to develop the required capacity and
penetration, or the capacity of the element shall be verified
by load tests in accordance with Section 1810.3.3.1.2.
1810.4.7 Enlarged base cast-in-place elements. Enlarged
bases for cast-in-place deep foundation elements formed by
compacting concrete or by driving a precast base shall be
formed in or driven into granular soils. Such elements shall
be constructed in the same manner as successful prototype
test elements driven for the project. Shafts extending
through peat or other organic soil shall be encased in a per-
manent steel casing. Where a cased shaft is used, the shaft
shall be adequately reinforced to resist column action or the
annular space around the shaft shall be filled sufficiently to
reestablish lateral support by the soil. Where heave occurs,
the element shall be replaced unless it is demonstrated that
the element is undamaged and capable of carrying twice its
design load.
1810.4.8 Hollow-stem angered, cast-in-place elements.
Where concrete or grout is placed by pumping through a
hollow-stem auger, the auger shall be permitted to rotate in a
clockwise direction during withdrawal. As the auger is
withdrawn at a steady rate or in increments not to exceed 1
foot (305 mm), concreting or grouting pumping pressures
shall be measured and maintained high enough at all times
to offset hydrostatic and lateral earth pressures. Concrete or
grout volumes shall be measured to ensure that the volume
of concrete or grout placed in each element is equal to or
greater than the theoretical volume of the hole created by the
auger. Where the installation process of any element is inter-
rupted or a loss of concreting or grouting pressure occurs,
the element shall be redrilled to 5 feet (1524 mm) below the
elevation of the tip of the auger when the installation was
interrupted or concrete or grout pressure was lost and
reformed. Augered cast-in-place elements shall not be
installed within six diameters center to center of an element
filled with concrete or grout less than 12 hours old, unless
approved by the building official. If the concrete or grout
level in any completed element drops due to installation of
an adjacent element, the element shall be replaced.
1810.4.9 Socketed drilled shafts. The rock socket and pipe
or tube casing of socketed drilled shafts shall be thoroughly
cleaned of foreign materials before filling with concrete.
Steel cores shall be bedded in cement grout at the base of the
rock socket.
1810.4.10 Micropiles. Micropile deep foundation elements
shall be permitted to be formed in holes advanced by rotary
or percussive drilling methods, with or without casing. The
elements shall be grouted with a fluid cement grout. The
grout shall be pumped through a tremie pipe extending to
the bottom of the element until grout of suitable quality
returns at the top of the element. The following require-
ments apply to specific installation methods:
1 . For micropiles grouted inside a temporary casing, the
reinforcing bars shall be inserted prior to withdrawal
of the casing. The casing shall be withdrawn in a con-
trolled manner with the grout level maintained at the
top of the element to ensure that the grout completely
fills the drill hole. During withdrawal of the casing,
the grout level inside the casing shall be monitored to
verify that the flow of grout inside the casing is not
obstructed.
2. For a micropile or portion thereof grouted in an open
drill hole in soil without temporary casing, the mini-
mum design diameter of the drill hole shall be verified
by a suitable device during grouting.
3. For micropiles designed for end bearing, a suitable
means shall be employed to verify that the bearing
surface is properly cleaned prior to grouting.
4. Subsequent micropiles shall not be drilled near ele-
ments that have been grouted until the grout has had
sufficient time to harden.
5. Micropiles shall be grouted as soon as possible after
drilling is completed.
6. For micropiles designed with a full-length casing, the
casing shdl be pulled back to the top of the bond zone
and reinserted or some other suitable means
employed to assure grout coverage outside the casing.
1810.4.11 Helical piles. HeUcal piles shall be installed to
specified embedment depth and torsional resistance criteria
as determined by a registered design professional. The
torque applied during installation shall not exceed the maxi-
mum allowable installation torque of the helical pile.
1810.4.12 Special inspection. Special inspections in accor-
dance with Sections 1704.8 and 1704.9 shall be provided
for driven and cast-in-place deep foundation elements,
respectively. Special inspections in accordance with Section
1704.10 shall be provided for helical piles.
204
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER MA - SOILS AND FOUNDATIONS
Adopting agency
BSC
SFWI
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
Adopt entire ciiapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
205
206 201 CALIFORNIA BUILDING CODE
CHAPTER 184
SOILS AND FOUNDATIONS
This chapter has been revised in its entirety; there will be no marginal markings.
SECTION 18014
GENERAL
1801A.1 Scope. The provisions of this chapter shall apply to
building and foundation systems.
Refer to Appendix J, Grading, for requirements governing
grading, excavation and earthwork construction, including
fills and embankments.
1801 AJ,1 Application. The scope of application of Chap-
ter 18A is as follows :
1. Structures regulated by the Division of the State
Architect — Structural Safety, which include those
applications listed in Section 1.9.2.1 (DSA-SS), and
L9.2.1 (DSA-SS/CC). These applications include
public elementary and secondary schools, community
colleges and state-owned or state-leased essential
services buildings
I I 2. Applications listed in Section 1.10.1 and 1.10.4 regu-
lated by the Office of Statewide Health Planning and
Development (OSHPD),These applications include
hospitals, skilled nursing facilities, intermediate care
facilities and correctional treatment centers.
Exception: [OSHPD 21 Single-story Type V
skilled nursing or intermediate care facilities uti-
lizing wood-frame or light-steel-frame construc-
tion as defined in Health and Safety Code Section
129725, which shall comply with Chapter 18 and
any applicable amendments therein.
1801 A A, 2 Amendments in this chapter, DSA-SS
DSA-SS/CC adopt this chapter and all amendments.
and
II
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1. Division of the State Architect-Structural Safety:
[DSA-SS] For applications listed in Section
1.9.2.1.
[DSA-SS/CC] For applications listed in Section
1.9.2.1.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD 1] - For applications listed in Section
1.10.1.
[OSHPD 4] - For applications listed in Section
1.10.4.
1801A,L3 Reference to other chapters.
I801A.L3.1 [DSA-SS/CC] Where reference within this
chapter is made to sections in Chapters 16 A, 19 A, 21 A,
22A and 34A, the provisions in Chapters 16, 19, 21, 22
and 34 respectively shall apply instead.
1801A. 2 Design basis. Allowable bearing pressures, allowable
stresses and design formulas provided in this chapter shall be
used with the allowable stress design load combinations speci-
fied in Section 1605A.3. The quality and design of materials
used structurally in excavations and foundations shall comply
with the requirements specified in Chapters 16A, 19A, 21A,
22A and 23 of this code. Excavations and fills shall also comply
with Chapter 33.
SECTION 18024
DEFINITIONS
1802A.1 Definitions. The following words and terms shall, for
the purposes of this chapter, have the meanings shown herein.
DEEP FOUNDATION. A deep foundation is a foundation
element that does not satisfy the definition of a shallow founda-
tion.
DRILLED SHAFT. A drilled shaft is a cast-in-place deep
foundation element constructed by drilhng a hole (with or
without permanent casing) into soil or rock and filling it with
fluid concrete.
Socketed drilled shaft. A socketed drilled shaft is a drilled
shaft with a permanent pipe or tube casing that extends
down to bedrock and an uncased socket drilled into the bed-
rock.
HELICAL PILE. Manufactured steel deep foundation ele-
ment consisting of a central shaft and one or more helical bear-
ing plates. A helical pile is installed by rotating it into the
ground. Each helical bearing plate is formed into a screw thread
with a uniform defined pitch.
MICROPILE. A micropile is a bored, grouted-in-place deep
foundation element that develops its load-carrying capacity by
means of a bond zone in soil, bedrock or a combination of soil
and bedrock.
SHALLOW FOUNDATION. A shallow foundation is an
individual or strip footing, a mat foundation, a slab-on-grade
foundation or a similar foundation element.
2010 CALIFORNIA BUILDING CODE
207
SOILS AND FOUNDATIONS
SECTION 18034
GEOTECHNICAL INVESTIGATIONS
1803A.1 General. Geotechnical investigations shall be con-
ducted in accordance with Section 1803A.2 and reported in
>l I accordance with Section 1S03A.7. The classification and
investigation of the soil shall be made under the responsible
charge of a California registered geotechnical engineer All
recommendations contained in geotechnical and engineering
geology reports shall be subject to the approval of the enforce-
> ment agency . All reports shall be prepared and signed by a reg-
istered geotechnical engineer and an engineering geologist
where applicable.
1803A.2 Investigations required. Geotechnical investiga-
tions shall be conducted in accordance with Sections 1803A.3
I I through 1803A.6.
Exception: Geotechnical reports are not required for
one-story, wood-frame and light- steel-frame buildings of
Type II or Type V construction and 4,000 square feet (371
m^) or less in floor area, not located within Earthquake
Fault Zones or Seismic Hazard Zones as shown in the most
recently published maps from the California Geological
Survey (CGS). Allowable foundation and lateral soilpres-
I I sure values may be determined from Table I806A,2.
1803A.3 Basis of investigation. Soil classification shall be
based on observation and any necessary tests of the materials
disclosed by borings, test pits or other subsurface exploration
made in appropriate locations. Additional studies shall be
made as necessary to evaluate slope stability, soil strength,
position and adequacy of load-bearing soils, the effect of mois-
ture variation on soil-bearing capacity, compressibility, lique-
faction and expansiveness.
1803A.3.1 Scope of investigation. The scope of the
geotechnical investigation including the number and types
of borings or soundings, the equipment used to drill or sam-
ple, the in- situ testing equipment and the laboratory testing
program shall be determined by a registered design profes-
sional.
There shall not be less than one boring or exploration
shaft for each 5,000 square feet (465 m^) of building area at
the foundation level with a minimum oftwo provided for any
> one building. A boring may be considered to reflect
subsurface conditions relevant to more than one building,
subject to the approval of the enforcement agency.
Borings shall be of sufficient size to permit visual exami-
nation of the soil in place or, in lieu thereof, cores shall be
taken.
Borings shall be of sufficient depth and size to adequately
characterize subsurface conditions.
1803A.4 Qualified representative. The investigation proce-
dure and apparatus shall be in accordance with generally
accepted engineering practice. The registered design profes-
sional shall have a fully qualified representative on site during
all boring or sampling operations.
1803A.5 Investigated conditions. Geotechnical investiga-
tions shall be conducted as indicated in Sections 1803A.5.1
through 1803A.5.12,
1803A.5,1 Classification. Soil materials shall be classified
in accordance with ASTM D 2487.
1803A.5.2 Questionable soil. Where the classification,
strength or compressibility of the soil is in doubt or where a
load-bearing value superior to that specified in this code is
claimed, the building official shall be permitted to require
that a geotechnical investigation be conducted.
1803A.5.3 Expansive soil. In areas likely to have expansive
soil, the building official shall require soil tests to determine
where such soils do exist.
Soils meeting all four of the following provisions shall be
considered expansive, except that tests to show compliance
with Items 1 , 2 and 3 shall not be required if the test pre-
scribed in Item 4 is conducted:
1. Plasticity index (PI) of 15 or greater, determined in
accordance with ASTM D 4318.
2. More than 10 percent of the soil particles pass a No.
200 sieve (75 |im), determined in accordance with
ASTM D 422.
3. More than 10 percent of the soil particles are less than
5 micrometers in size, determined in accordance with
ASTM D 422.
4. Expansion index greater than 20, determined in
accordance with ASTM D 4829.
1803A.5.4 Ground- water table. A subsurface soil investi-
gation shall be performed to determine whether the existing
ground- water table is above or within 5 feet (1524 mm)
below the elevation of the lowest floor level where such
floor is located below the finished ground level adjacent to
the foundation.
1803A.5.5 Deep foundations. Where deep foundations
will be used, a geotechnical investigation shall be conducted
and shall include all of the following, unless sufficient data
upon which to base the design and installation is otherwise
available:
1. Reconomended deep foundation types and installed
capacities.
2. Recommended center-to-center spacing of deep
foundation elements.
3. Driving criteria.
4. Installation procedures.
5. Field inspection and reporting procedures (to include
procedures for verification of the installed bearing
capacity where required).
6. Load test requirements.
7. Suitability of deep foundation materials for the
intended environment.
8. Designation of bearing stratum or strata.
9. Reductions for group action, where necessary.
1803A.5.6 Rock strata. Where subsurface explorations at
the project site indicate variations or doubtful characteris-
tics in the structure of the rock upon which foundations are
to be constructed, a sufficient number of borings shall be
208
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATDONS
made to a depth of not less than 10 feet (3048 mm) below the
level of the foundations to provide assurance of the sound-
ness of the foundation bed and its load-bearing capacity.
1803A.5.7 Excavation near foundations. Where excava-
tion will remove lateral support from any foundation, an
investigation shall be conducted to assess the potential con-
sequences and address mitigation measures.
1803A.5.8 Compacted fill material. Where shallow foun-
dations will bear on compacted fill material more than 12
inches (305 mm) in depth, a geotechnical investigation shall
be conducted and shall include all of the following:
1. Specifications for the preparation of the site prior to
placement of compacted fill material.
2. Specifications for material to be used as compacted
fill.
3. Test methods to be used to determine the maximum
dry density and optimum moisture content of the
material to be used as compacted fill.
4. Maximum allowable thickness of each lift of com-
pacted fill material.
5. Field test method for determining the in-place dry
density of the compacted fill.
6. Minimum acceptable in-place dry density expressed
as a percentage of the maximum dry density deter-
mined in accordance with Item 3.
7 . Number and frequency of field tests required to deter-
mine compliance with Item 6.
1803A.5.9 Controlled low-strength material (CLSM).
Where shallow foundations will bear on controlled
low- strength material (CLSM), a geotechnical investigation
shall be conducted and shall include all of the following:
1. Specifications for the preparation of the site prior to
placement of the CLSM.
2. Specifications for the CLSM.
3. Laboratory or field test method(s) to be used to deter-
mine the compressive strength or bearing capacity of
the CLSM.
4. Test methods for determining the acceptance of the
CLSM in the field.
5 . Number and frequency of field tests required to deter-
mine compliance with Item 4.
1803A.5.10 Alternate setback and clearance. Where set-
backs or clearances other than those required in Section
1808A.7 are desired, the building official shall be permitted
to require a geotechnical investigation by a registered
design professional to demonstrate that the intent of Section
1808A.7 would be satisfied. Such an investigation shall
include consideration of material, height of slope, slope gra-
dient, load intensity and erosion characteristics of slope
material.
1803A.5.11 Seismic Design Categories C through F. For
structures assigned to Seismic Design Category C, D, E or F
in accordance with Section 1 6 1 3A, a geotechnical investiga-
tion shall be conducted, and shall include an evaluation of
all of the following potential geologic and seismic hazards:
1. Slope instability.
2. Liquefaction.
3. Differential settlement.
4. Surface displacement due to faulting or lateral
spreading.
1803A.5.12 Seismic Design Categories D through E For
structures assigned to Seismic Design Category D, E or F in
accordance with Section 1613A, the geotechnical investiga-
tion required by Section 1803 A. 5.11, shall also include:
1. The determination of lateral pressures on foundation
walls and retaining walls due to earthquake motions.
2. The potential for liquefaction and soil strength loss
evaluated for site peak ground accelerations, magni-
tudes and source characteristics consistent with the
design earthquake ground motions. Peak ground
acceleration shall be permitted to be determined
based on a site-specific study taking into account soil
amplification effects, as specified in Chapter 21 of
ASCE 7, or, in the absence of such a study, peak
ground accelerations shall be assumed equal to
Sjr)sl2,5, where S^^ is determined in accordance with
Section 1613A.5.4.
3. An assessment of potential consequences of liquefac-
tion and soil strength loss, including estimation of dif-
ferential settlement, lateral movement, lateral loads
on foundations, reduction in foundation soil-bearing
capacity, increases in lateral pressures on retaining
walls and flotation of buried structures.
4. Discussion of mitigation measures such as, but not
limited to, ground stabilization, selection of appropri-
ate foundation type and depths, selection of appropri-
ate structural systems to acconunodate anticipated
displacements and forces, or any combination of
these measures and how they shall be considered in
the design of the structure.
1803A.6 Site data.
1803 A.6 A Engineering geologic reports,
1803A.6,1,1 Geologic and earthquake engineering
reports shall be required for all proposed construction.
Exceptions:
1. Reports are not required for one- story, wood-
frame and light-steel-frame buildings of Type II
or Type V construction and 4,000 square feet
(371 m^) or less in floor area, not located within
Earthquake Fault Zones or Seismic Hazard
Zones as shown in the most recently published
maps from the California Geological Survey
(CGS); nonstructural, associated structural or
voluntary structural alterations and incidental I
structural additions or alterations, and struc-
tural repairs for other than earthquake dam-
age.
2010 CALIFORNIA BUILDING CODE
209
SOILS AND FOUNDATIONS
II
II
>
II
2. A previous report for a specific site may be
resubmitted, provided that a reevaluation is
made and the report is found to be currently
appropriate.
1803A.6J,2 The purpose of the engineering geologic
report shall be to identify geologic and seismic condi-
tions that may require project mitigations. The reports
shall contain data which provide an assessment of the
nature of the site and potential for earthquake damage
based on appropriate investigations of the regional and
site geology, project foundation conditions and the
potential seismic shaking at the site. The report shall be
prepared by a California- certified engineering geologist
in consultation with a California-registered geotechni-
cal engineer
The preparation of the engineering geologic report
shall consider the most recent CGS Note 48: Checklist
for the Review of Engineering Geology and Seismology
Reports for California Public School, Hospitals, and
Essential Services Buildings. In addition, the most recent
version of CGS Special Publication 42, Fault Rupture
Hazard Zones in California, shall be considered for pro-
ject sites proposed within an Alquist-Priolo Earthquake
Fault Zone. The most recent version of CGS Special Pub-
lication 117, Guidelines for Evaluating and Mitigating
Seismic Hazards in California, shall be considered for
project sites proposed within a Seismic Hazard Zone. All
conclusions shall be supported by satisfactory data and
analysis.
In addition to requirements in Sections 1803 A. 5. 11
and 1803A.5.12, the report shall include, but shall not be
limited to, the following:
1. Geologic investigation.
2. Evaluation of the known active and potentially
active faults, both regional and local.
3. Ground-motion parameters, as required by Sec-
tions 161 3 A and 161 5 A, andASCE 7.
I803A,6,2 Supplemental ground-response report. If site-
specific ground-motion procedures, as set forth in ASCE 7
Chapter 21, or ground-motion response history analysis, as
set forth in ASCE 7 Chapter 16, Section 17.3 or Section
18.2.3, are used for design, then a supplemental ground-
response report may be required. All conclusions and
ground-motion parameters shall be supported by data and
analysis.
The three Next Generation Attenuation (NGA) relations
used for the 2008 USGS seismic hazards maps for Western
United States (WUS) shall be utilized to determine the
site-specific ground motion. When supported by data and
analysis, other NGA relations, that were not used for the
2008 USGS maps, shall be permitted as additions or substi-
tutions. No fewer than three NGA relations shall be utilized.
Site-specific Probabilistic Site Hazard Analyses (PSHA)
for structures that incorporate the NGA relations shall use
the maximum rotated component of ground motion.
Site-specific Deterministic Site Hazard Analyses (DSHA)
for structures that incorporate the NGA relations shall use
the 84th percentile of the maximum rotated component of
ground motion.
I803A.6.2,1 The ground-motion element shall be pre-
pared by a registered geotechnical engineer or geophy si-
cist (depending on the scope of the element), or
engineering geologist licensed in the state of California,
and having professional specialization in earthquake
analyses. The ground-motion element shall present a
detailed characterization of earthquake ground motions
for the site, which incorporates data given in the
geotechnical report. The level of ground motion consid-
ered by the ground-motion element shall be as described
in ASCE 7 Chapter 21. The characterization of ground
motion in the ground-motion element shall be given,
according to the requirements of the analysis, in terms
of:
L Elastic structural response spectra.
2. Time-history plot of predicted ground motion at
the site.
3. Other analyses in conformance with accepted
engineering and seismological practice.
I803A.6.2,2 The advanced geotechnical element shall
contain the results of dynamic geotechnical analyses
specified by the approved geotechnical report. Where
site response analysis, as set forth in ASCE 7 Section
21.1, is required, the response model shall be fully
explained. The input data and assumptions shall be fully
documented, and the surface ground motions recom-
mended for design shall be clearly identified.
The supplemental ground-response report shall be
submitted to the enforcement agency for review and
approval. The review shall determine whether the
ground-motion response evaluations of the site are ade-
quately represented. The enforcement agency may
require additional information, analysis or clarification
of potential ground-response issues reported in the sup-
plemental ground-response report for the proposed
building site.
1803 A, 7 Geotechnical reporting. Where geotechnical investi- I I \
gations are required, a written report of the investigations shall
be submitted to the building official by the owner or authorized
agent at the time of permit application. The geotechnical report
shall provide completed evaluations of the foundation condi-
tions of the site and the potential geologic/seismic hazards
affecting the site. The geotechnical report shall include, but
shall not be limited to, site-specific evaluations of design crite-
ria related to the nature and extent of foundation materials,
groundwater conditions, liquefaction potential, settlement
potential and slope stability. The report shall contain the
results of the analyses of problem areas identified in the engi-
neering geologic report. The geotechnical report shall incor-
porate estimates of the characteristics of site ground motion
provided in the engineering geologic report. This geotechnical
210
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
report shall include, but need not he limited to, the following
information:
1 . A plot showing the location of the soil investigations.
2. A complete record of the soil boring and penetration
test logs and soil samples.
3. A record of the soil profile.
4. Elevation of the water table, if encountered. Historic
high ground water elevations shall be addressed in the
report to adequately evaluate liquefaction and settle-
ment potential.
5. Recommendations for foundation type and design cri-
teria, including but not limited to: bearing capacity of
natural or compacted soil; provisions to mitigate the
effects of expansive soils; mitigation of the effects of
liquefaction, differential settlement and varying soil
strength; and the effects of adjacent loads.
6. Expected total and differential settlement.
7. Deep foundation information in accordance with Sec-
tion 1803A.5.5.
8. Special design and construction provisions for founda-
tions of structures founded on expansive soils, as nec-
essary.
9. Compacted fill material properties and testing in accor-
dance with Section 1803A.5.8.
10. Controlled low-strength material properties and testing
in accordance with Section 1803 A. 5. 9.
1 1 . The report shall consider the effects of stepped footings
I I addressed in Section 1809 A. 3.
12. The report shall consider the effects of seismic hazards
I I in accordance with Section 1803A.6.
SECTION 18044
EXCAVATION, GRADING AND FILL
1804A.1 Excavation near foundations. Excavation for any
purpose shall not remove lateral support from any foundation
without first underpinning or protecting the foundation against
settlement or lateral translation.
1804A.2 Placement of backfill. The excavation outside the
foundation shall be backfilled with soil that is fi'ee of organic
material, construction debris, cobbles and boulders or with a
controlled low-strength material (CLSM). The backfill shall be
placed in lifts and compacted in a manner that does not damage
the foundation or the waterproofing or dampproofing material.
Exception: CLSM need not be compacted.
1804A.3 Site grading. The ground immediately adjacent to the
foundation shall be sloped away from the building at a slope of
not less than one unit vertical in 20 units horizontal (5 -percent
slope) for a minimum distance of 10 feet (3048 mm) measured
perpendicular to the face of the wall. If physical obstructions or
lot lines prohibit 10 feet (3048 mm) of horizontal distance, a
5 -percent slope shall be provided to an approved alternative
method of diverting water away from the foundation. Swales
used for this purpose shall be sloped a minimum of 2 percent
where located within 10 feet (3048 mm) of the building foun-
dation. Impervious surfaces within 10 feet (3048 mm) of the
building foundation shall be sloped a minimum of 2 percent
away from the building.
Exception: Where climatic or soil conditions warrant, the
slope of the ground away from the building foundation shall
be permitted to be reduced to not less than one unit vertical
in 48 units horizontal (2-percent slope).
The procedure used to establish the final ground level adja-
cent to the foundation shall account for additional settlement of
the backfill.
1804A.4 Grading and fill in flood hazard areas. In flood haz-
ard areas established in Section 1612A.3, grading and/or fill
shall not be approved:
1 . Unless such fill is placed, compacted and sloped to mini-
mize shifting, slumping and erosion during the rise and
fall of flood water and, as applicable, wave action.
2. In floodways, unless it has been demonstrated through
hydrologic and hydraulic analyses performed by a regis-
tered design professional in accordance with standard
engineering practice that the proposed grading or fill, or
both, will not result in any increase in flood levels during
the occurrence of the design flood.
3. In flood hazard areas subject to high- velocity wave
action, unless such fill is conducted and/or placed to
avoid diversion of water and waves toward any building
or structure.
4. Where design flood elevations are specified but
floodways have not been designated, unless it has been
demonstrated that the cumulative effect of the proposed
flood hazard area encroachment, when combined with
all other existing and anticipated flood hazard area
encroachment, will not increase the design flood eleva-
tion more than 1 foot (305 mm) at any point.
1804A.5 Compacted fill material. Where shallow founda-
tions will bear on compacted fill material, the compacted fill
shall comply with the provisions of an approved geotechnical
report, as set forth in Section 1 803A.
Exception: Compacted fill material 12 inches (305 mm) in
depth or less need not comply with an approved report, pro-
vided the in-place dry density is not less than 90 percent of
the maximum dry density at optimum moisture content
determined in accordance with ASTM D 1557. The com-
paction shall be verified by special inspection in accordance
with Section 1704A.7.
1804A.6 Controlled low-strength material (CLSM). Where
shallow foundations will bear on controlled low-strength mate-
rial (CLSM), the CLSM shall comply with the provisions of an
approved geotechnical report, as set forth in Section 1803A.
SECTION 1805A
DAMPPROOFING AND WATERPROOFING
1805A.1 General. Walls or portions thereof that retain earth
and enclose interior spaces and floors below grade shall be
waterproofed and dampproofed in accordance with this sec-
2010 CALIFORNIA BUILDING CODE
211
SOILS AND FOUNDATIONS
tion, with the exception of those spaces containing groups
other than residential and institutional where such omission is
not detrimental to the building or occupancy.
Ventilation for crawl spaces shall comply with Section 1203.4.
1805A.1.1 Story above grade plane. Where a basement is
considered a story above grade plane and the finished
ground level adjacent to the basement wall is below the
basement floor elevation for 25 percent or more of the per-
imeter, the floor and walls shall be dampproofed in accor-
dance with Section 1 805A.2 and a foundation drain shall be
installed in accordance with Section 1805A.4.2. The foun-
dation drain shall be installed around the portion of the per-
imeter where the basement floor is below ground level. The
provisions of Sections 1803A.5.4, 1805A.3 and 1805A.4.1
shall not apply in this case.
1805A.1.2 Under-floor space. The finished ground level of
an under-floor space such as a crawl space shall not be
located below the bottom of the footings. Where there is evi-
dence that the ground-water table rises to within 6 inches
(152 nun) of the ground level at the outside building perime-
ter, or that the surface water does not readily drain from the
building site, the ground level of the under-floor space shall
be as high as the outside finished ground level, unless an
approved drainage system is provided. The provisions of
Sections 1803A.5.4, 1805A.2, 1805A.3 and 1805A.4 shall not
apply in this case.
1805A. 1.2.1 Flood hazard areas. For buildings and
structures in flood hazard areas as established in Section
1612A.3, the finished ground level of an under-floor
space such as a crawl space shall be equal to or higher
than the outside finished ground level on at least one side.
Exception: Under-floor spaces of Group R-3 build-
ings that meet the requirements of FEMAMA-TB- 1 1 .
1805A.1.3 Ground- water control. Where the ground-
water table is lowered and maintained at an elevation not
less than 6 inches (152 mm) below the bottom of the lowest
floor, the floor and walls shall be dampproofed in accor-
dance with Section 1805A.2. The design of the system to
lower the ground-water table shall be based on accepted
principles of engineering that shall consider, but not neces-
sarily be limited to, permeability of the soil, rate at which
water enters the drainage system, rated capacity of pumps,
head against which pumps are to operate and the rated
capacity of the disposal area of the system.
1805A.2 DampprooOng. Where hydrostatic pressure will not
> occur as determined by Section 1803 A. 5. 4, floors and walls
> shall be dampproofed in accordance with this section.
1805A.2.1 Floors. Dampproofing materials for floors shall
be installed between the floor and the base course required
by Section 1805A.4.1, except where a separate floor is pro-
vided above a concrete slab.
Where installed beneath the slab, dampproofing shall
consist of not less than 6-mil (0.006 inch; 0.152 mm) poly-
ethylene with joints lapped not less than 6 inches (152 mm),
or other approved methods or materials. Where permitted to
be installed on top of the slab, dampproofing shall consist of
mopped-on bitumen, not less than 4-mil (0.004 inch; 0.102
mm) polyethylene, or other approved methods or materials.
Joints in the membrane shall be lapped and sealed in accor-
dance with the manufacturer's installation instructions.
1805A.2.2 Walls. Dampproofing materials for walls shall
be installed on the exterior surface of the wall, and shall
extend from the top of the footing to above ground level.
Dampproofing shall consist of a bituminous material, 3
pounds per square yard (16 N/m^) of acrylic modified
cement, Vg inch (3.2 mm) coat of surface-bonding mortar
complying with ASTM C 887, any of the materials permit-
ted for waterproofing by Section 1805A.3.2 or other
approved methods or materials.
1805A. 2.2.1 Surface preparation of walls. Prior to
application of dampproofing materials on concrete walls,
holes and recesses resulting from the removal of form ties
shall be sealed with a bituminous material or other
approved methods or materials. Unit masonry walls shall
be parged on the exterior surface below ground level with
not less than Vg inch (9.5 mm) of portland cement mortar.
The parging shall be coved at the footing.
Exception: Parging of unit masonry walls is not
required where a material is approved for direct appli-
cation to the masonry.
1805A.3 Waterproofing. Where the ground- water investiga-
tion required by Section 1803A.5.4 indicates that a hydrostatic
pressure condition exists, and the design does not include a
ground-water control system as described in Section
1805AA.1.3, walls and floors shall be waterproofed in accor-
dance with this section.
1805A.3.1 Floors. Floors required to be waterproofed shall
be of concrete and designed and constructed to withstand
the hydrostatic pressures to which the floors will be sub-
jected.
Waterproofing shall be accomplished by placing a mem-
brane of rubberized asphalt, butyl rubber, fully adhered/fully
bonded HDPE or polyolefin composite membrane or not less
than 6-mil [0.006 inch (0.152 mm)] polyvinyl chloride with
joints lapped not less than 6 inches (152 mm) or other
approved materials under the slab. Joints in the membrane
shall be lapped and sealed in accordance with the manufac-
turer's installation instructions.
1805A.3.2 Walls. Walls required to be waterproofed shall
be of concrete or masonry and shall be designed and con-
structed to withstand the hydrostatic pressures and other lat-
eral loads to which the walls will be subjected.
Waterproofing shall be applied from the bottom of the
wall to not less than 12 inches (305 mm) above the maxi-
mum elevation of the ground- water table. The remainder of
the wall shall be dampproofed in accordance with Section
1805A.2.2. Waterproofing shall consist of two-ply
hot-mopped felts, not less than 6-mil (0.006 inch; 0.152
mm) polyvinyl chloride, 40-mil (0.040 inch; 1.02 mm)
polymer-modified asphalt, 6-mil (0.006 inch; 0.152 mm)
polyethylene or other approved methods or materials capa-
ble of bridging nonstructural cracks. Joints in the membrane
shall be lapped and sealed in accordance with the manufac-
turer's installation instructions.
212
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATBONS
1805A. 3.2.1 Surface preparation of walls. Prior to the
application of waterproofing materials on concrete or
masonry walls, the walls shall be prepared in accordance
with Section 1805A. 2.2.1.
1805A.3.3 Joints and penetrations. Joints in walls and
floors, joints between the wall and floor and penetrations of
the wall and floor shall be made water-tight utilizing
approved methods and materials.
1805A.4 Subsoil drainage system. Where a hydrostatic pres-
sure condition does not exist, dampproofing shall be provided
and a base shall be installed under the floor and a drain installed
around the foundation perimeter. A subsoil drainage system
designed and constructed in accordance with Section
1805 A. 1.3 shall be deemed adequate for lowering the
ground-water table.
1805A.4.1 Floor base course. Floors of basements, except
as provided for in Section 1 805A. 1.1, shall be placed over a
floor base course not less than 4 inches (102 mm) in thick-
ness that consists of gravel or crushed stone containing not
more than 10 percent of material that passes through a No. 4
(4.75 mm) sieve.
Exception: Where a site is located in well-drained gravel
or sand/gravel mixture soils, a floor base course is not
required.
1805A.4.2 Foundation drain. A drain shall be placed
around the perimeter of a foundation that consists of gravel
or crushed stone containing not more than 10-percent mate-
rial that passes through a No. 4 (4.75 mm) sieve. The drain
shall extend a minimum of 12 inches (305 mm) beyond the
outside edge of the footing. The thickness shall be such that
the bottom of the drain is not higher than the bottom of the
base under the floor, and that the top of the drain is not less
than 6 inches (152 mm) above the top of the footing. The top
of the drain shall be covered with an approved filter mem-
brane material. Where a drain tile or perforated pipe is used,
the invert of the pipe or tile shall not be higher than the floor
elevation. The top of joints or the top of perforations shall be
protected with an approved filter membrane material. The
pipe or tile shall be placed on not less than 2 inches (5 1 mm)
of gravel or crushed stone complying with Section
1805A.4.1, and shall be covered with not less than 6 inches
(152 mm) of the same material.
1805A.4.3 Drainage discharge. The floor base and foun-
dation perimeter drain shall discharge by gravity or
mechanical means into an approved drainage system that
compHes with the California Plumbing Code.
Exception: Where a site is located in well-drained gravel
or sand/gravel mixture soils, a dedicated drainage system
is not required.
SECTION 18064
PRESUMPTIVE LOAD-BEARING VALUES OF SOILS
1806A.1 Load combinations. The presumptive load-bearing
values provided in Table 1806A.2 shall be used with the allow-
able stress design load combinations specified in Section
1605A.3. The values of vertical foundation pressure and lateral
bearing pressure given in Table 1806A.2 shall be permitted to
be increased by one-third where used with the alternative basic
load combinations of Section 1605A.3.2 that include wind or
earthquake loads.
1806A.2 Presumptive load-bearing values. The load-bearing
values used in design for supporting soils near the surface shall
not exceed the values specified in Table 1 806A. 2 unless data to
substantiate the use of higher values are submitted and
approved. Where the building official has reason to doubt the
classification, strength or compressibility of the soil, the
requirements of Section 1803A.5.2 shall be satisfied.
Presumptive load-bearing values shall apply to materials
with similar physical characteristics and dispositions. Mud,
organic silt, organic clays, peat or unprepared fill shall not be
assumed to have a presumptive load-bearing capacity unless
data to substantiate the use of such a value are submitted.
Exception; A presumptive load-bearing capacity shall be
permitted to be used where the building official deems the
load-bearing capacity of mud, organic silt or unprepared fill
is adequate for the support of lightweight or temporary
structures.
1806A.3 Lateral load resistance. Where the presumptive val-
ues of Table 1 806A. 2 are used to determine resistance to lateral
loads, the calculations shall be in accordance with Sections
1806A.3.1 through 1806A.3.4.
1806A.3.1 Combined resistance. The total resistance to
lateral loads shall be permitted to be determined by combin-
ing the values derived from the lateral bearing pressure and
the lateral sliding resistance specified in Table 1806A.2.
1806A.3.2 Lateral sliding resistance limit. For clay, sandy
clay, silty clay, clayey silt, silt and sandy silt, in no case shall
the lateral sliding resistance exceed one-half the dead load.
1806A.3.3 Increase for depth. The lateral bearing pres-
sures specified in Table 1806A.2 shall be permitted to be
increased by the tabular value for each additional foot (305
nmi) of depth to a maximum of 1 5 times the tabular value.
1806A.3.4 Increase for poles. Isolated poles for uses such
as flagpoles or signs and poles used to support buildings that
are not adversely affected by a V2 inch (12.7 mm) motion at
the ground surface due to short-term lateral loads shall be
permitted to be designed using lateral bearing pressures
equal to two times the tabular values.
SECTION 1807A
FOUNDATION WALLS, RETAINING WALLS
AND EMBEDDED POSTS AND POLES
1807A.1 Foundation walls. Foundation walls shall be
designed and constructed in accordance with Sections
1807A.1.1 through 1807A.1.6. Foundation walls shall be sup-
ported by foundations designed in accordance with Section
1808A.
1807A. 1.1 Design lateral soil loads. Foundation walls shall
be designed for the lateral soil loads determined by a
geotechnical investigation in accordance with Section
1803A.
2010 CALIFORNIA BUILDING CODE
213
SOILS AND FOUNDATIONS
TABLE 1806A2
PRESUMPTIVE LOAD-BEARING VALUES
CLASS OF MATERIALS
VERTICAL FOUNDATION
PRESSURE (psf)
LATERAL BEARING
PRESSURE
(psf/ft below natural grade)
LATERAL SLIDING RESISTANCE
Coefficient of friction^
Cohesion (psf)''
1. Crystalline bedrock
12,000
1,200
0.70
—
2. Sedimentary and foli-
ated rock
4,000
■
400
0.35
—
3. Sandy gravel and/or
gravel (GW and GP)
3,000
200
0.35
—
4. Sand, silty sand, clayey
sand, silty gravel and
clayey gravel (SW, SP,
SM, SC, GM and GC)
2,000
150
0.25
—
5. Clay, sandy clay, silty
clay, clayey silt, silt and
sandy silt (CL, ML,
MH and CH)
1,500
100
—
130
For SI: 1 pound per square foot = 0.0479 kPa, 1 pound per square foot per foot = 0. 157 kPa/m.
a. Coefficient to be multiplied by the dead load.
b. Cohesion value to be muldplied by the contact area, as limited by Section 1806A.3.2.
1807A. 1.2 Unbalanced backfill height. Unbalanced back-
fill height is the difference in height between the exterior
finish ground level and the lower of the top of the concrete
footing that supports the foundation wall or the interior fin-
ish ground level. Where an interior concrete slab on grade is
provided and is in contact with the interior surface of the
foundation wall, the unbalanced backfill height shall be per-
mitted to be measured from the exterior finish ground level
to the top of the interior concrete slab.
1807A.1.3 Rubble stone foundation walls. Not permitted
by DSA-SS or DSA-SS/CC & OSHPD.
1807A. 1.4 Permanent wood foundation systems. Not per-
mitted by DSA-SS or DSA-SS/CC Sl OSHPD.
1807A. 1.5 Concrete and masonry foundation walls. Con-
crete and masonry foundation walls shall be designed in
accordance with Chapter 19A or 21A, as applicable.
1807A.2 Retaining walls. Retaining walls shall be designed in
accordance with Sections 1807A.2.1 through 1807A.2.3. Free-
standing cantilever walls shall be designed in accordance with
Section 1807A.2.4.
1807A.2.1 General. Retaining walls shall be designed to
ensure stability against overturning, sliding, excessive foun-
dation pressure and water uplift. Where a keyway is
extended below the wall base with the intent to engage pas-
sive pressure and enhance sliding stability, lateral soil pres-
sures on both sides of the keyway shall be considered in the
sliding analysis.
1807A.2.2 Design lateral soil loads. Retaining walls shall
I I be designed for the lateral soil loads determined by a
geotechnical investigation
1803A.
in accordance with Section
1807A.2.3 Safety factor. Retaining walls shall be designed
to resist the lateral action of soil to produce sliding and over-
turning with a minimum safety factor of 1.5 in each case.
The load combinations of Section 1605A shall not apply to
this requirement. Instead, design shall be based on 0.7 times
nominal earthquake loads, 1.0 times other nominal loads,
and investigation with one or more of the variable loads set
to zero. The safety factor against lateral sliding shall be
taken as the available soil resistance at the base of the retain-
ing wall foundation divided by the net lateral force applied
to the retaining wall.
Exception: Where earthquake loads are included, the
minimum safety factor for retaining wall sliding and
overturning shall be 1.1.
1807A,2.4 Freestanding cantilever walls. A stability check
against the possibility of overturning shall be performed for
isolated spread footings which support freestanding canti-
lever walls. The stability check shall be made by dividing Rp
used for the wall by 2.0, The allowable soil pressure may be
doubled for this evaluation.
Exception: For overturning about the principal axis of
rectangular footings with symmetrical vertical loading
and the design lateral force applied, a triangular or trap-
ezoidal soil pressure distribution which covers the full
width of the footing will meet the stability requirement
1807A.3 Embedded posts and poles. Designs to resist both
axial and lateral loads employing posts or poles as columns
embedded in earth or in concrete footings in earth shall be in
accordance with Sections 1807A.3.1 through 1807A.3.3.
214
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1807A.3.1 Limitations. The design procedures outlined in
this section are subject to the following limitations:
1 . The frictional resistance for structural walls and slabs
on silts and clays shall be limited to one-half of the
normal force imposed on the soil by the weight of the
footing or slab.
2. Posts embedded in earth shall not be used to provide
lateral support for structural or nonstructural materi-
als such as plaster, masonry or concrete unless brac-
ing is provided that develops the limited deflection
required.
Wood poles shall be treated in accordance with AWPA
Ul for sawn timber posts (Commodity Specification A, Use
Category 4B) and for round timber posts (Commodity
Specification B, Use Category 4B).
1807A.3.2 Design criteria. The depth to resist lateral loads
shall be determined using the design criteria established in
Sections 1807A.3.2.1 through 1807A.3.2.3, or by other
methods approved by the building official.
1807A.3.2.1 Nonconstrained. The following formula
shall be used in determining the depth of embedment
required to resist lateral loads where no lateral constraint
is provided at the ground surface, such as by a rigid floor
or rigid ground surface pavement, and where no lateral
constraint is provided above the ground surface, such as
by a structural diaphragm.
d = .
|4.25M^
(Equation 18.4
i S,b
where:
M,:
= Moment
(kN-m).
in the
post
at grade,
, in foot-pounds
d=0.5A{ 1 + [1 H^.36h/A)y^^}
(Equation 18A-1)
^3 = Allowable lateral soil-bearing pressure as set
forth in Section 1806A.2 based on a depth equal
to the depth of embedment in pounds per square
foot (kPa).
1807A. 3.2.3 Vertical load. The resistance to vertical
loads shall be determined using the vertical foundation
pressure set forth in Table 1806A.2.
1807A.3.3 Backfill. The backfill in the annular space
around columns not embedded in poured footings shall be
by one of the following methods:
1. Backfill shall be of concrete with a specified com-
pressive strength of not less than 2,000 psi (13.8
MPa). The hole shall not be less than 4 inches (102
mm) larger than the diameter of the column at its bot-
tom or 4 inches (102 mm) larger than the diagonal
dimension of a square or rectangular column.
2. Backfill shall be of clean sand. The sand shall be thor-
oughly compacted by tamping in layers not more than
8 inches (203 mm) in depth.
3. Backfill shall be of controlled low-strength material
(CLSM).
where:
A = 234P/S,b.
b = Diameter of round post or footing or diagonal
dimension of square post or footing, feet (m).
d = Depth of embedment in earth in feet (m) but not
over 12 feet (3658 mm) for purpose of comput-
ing lateral pressure.
h = Distance in feet (m) from ground surface to point
of application of "P."
P = Applied lateral force in pounds (kN).
Si = Allowable lateral soil-bearing pressure as set
forth in Section 1806A.2 based on a depth of
one-third the depth of embedment in pounds per
square foot (psf) (kPa).
1807A.3.2.2 Constrained. The following formula shall
be used to determine the depth of embedment required to
resist lateral loads where lateral constraint is provided at
the ground surface, such as by a rigid floor or pavement.
425Ph
S^b
(Equation 18A-2)
or alternatively
SECTION 18084
FOUNDATIONS
1808A.1 General. Foundations shall be designed and con-
structed in accordance with Sections 1808A.2 through
1808A.9. Shallow foundations shall also satisfy the require-
ments of Section 1809A. Deep foundations shall also satisfy
the requirements of Section 1810A.
1808A.2 Design for capacity and settlement. Foundations
shall be so designed that the allowable bearing capacity of the
soil is not exceeded, and that differential settlement is mini-
mized. Foundations in areas with expansive soils shall be
designed in accordance with the provisions of Section
1808A.6.
The enforcing agency may require an analysis of foundation I I
elements to determine subgrade deformations in order to eval-
uate their effect on the superstructure, including story drift, I I
1808A.3 Design loads. Foundations shall be designed for the
most unfavorable effects due to the combinations of loads spec-
ified in Section 1605A.2 or 1605A.3. The dead load is permit-
ted to include the weight of foundations and overlying fill.
Reduced live loads, as specified in Sections 1607A.9 and
1607A. 1 1 , shall be permitted to be used in the design of foun-
dations.
2010 CALIFORNIA BUILDING CODE
215
SOILS AND FOUNDATIONS
1808A.3.1 Seismic overturning. Where foundations are
proportioned using the load combinations of Section 1605.2
or 1605 A. 3.1, and the computation of seismic overturning
effects is by equivalent lateral force analysis or modal anal-
ysis, the proportioning shall be in accordance with Section
12.13.4 of ASCE 7.
1808A,4 Vibratory loads. Where machinery operations or
other vibrations are transmitted through the foundation, con-
sideration shall be given in the foundation design to prevent
detrimental disturbances of the soil.
1808A.5 Shifting or moving soils. Where it is known that the
shallow subsoils are of a shifting or moving character, founda-
tions shall be carried to a sufficient depth to ensure stability.
1808A.6 Design for expansive soils. Foundations for build-
ings and structures founded on expansive soils shall be
designed in accordance with Section 1808A.6.1 or 1808A.6.2.
Exception: Foundation design need not comply with Sec-
tion 1808A.6.1 or 1808A.6,2 where one of the following
conditions is satisfied:
1. The soil is removed in accordance with Section
1808A.6.3; or
2. The building official approves stabilization of the soil
in accordance with Section 1808A.6.4.
1808A.6.1 Foundations. Foundations placed on or within
the active zone of expansive soils shall be designed to resist
differential volume changes and to prevent structural dam-
age to the supported structure. Deflection and racking of the
supported structure shall be limited to that which will not
interfere with the usability and serviceability of the struc-
ture.
Foundations placed below where volume change occurs
or below expansive soil shall comply with the following
provisions:
1 . Foundations extending into or penetrating expansive
soils shall be designed to prevent uplift of the sup-
ported structure.
2. Foundations penetrating expansive soils shall be
designed to resist forces exerted on the foundation
due to soil volume changes or shall be isolated from
the expansive soil.
1808A.6.2 Slab-on-ground foundations. Moments, shears
and deflections for use in designing slab-on-ground, mat or
raft foundations on expansive soils shall be determined in
accordance with WRI/CRSI Design of Slah-on-Ground
Foundations or PTI Standard Requirements for Analysis of
Shallow Concrete Foundations on Expansive Soils. Using
the moments, shears and deflections determined above,
nonprestressed slabs-on-ground, mat or raft foundations on
expansive soils shall be designed in accordance with
WRI/CRSI Design of Slab-on-Ground Foundations and
post-tensioned slab-on-ground, mat or raft foundations on
expansive soils shall be designed in accordance with PTI
Standard Requirements for Design of Shallow Post-
Tensioned Concrete Foundations on Expansive Soils. It
shall be permitted to analyze and design such slabs by other
methods that account for soil -structure interaction, the
deformed shape of the soil support, the plate or stiffened
plate action of the slab as well as both center lift and edge lift
conditions. Such alternative methods shall be rational and
the basis for all aspects and parameters of the method shall
be available for peer review.
1808A.6.3 Removal of expansive soil. Where expansive
soil is removed in lieu of designing foundations in accor-
dance with Section 1808A.6. 1 or 1808A.6.2, the soil shall be
removed to a depth sufficient to ensure a constant moisture
content in the remaining soil. Fill material shall not contain
expansive soils and shall comply with Section 1804A.5 or
1804A.6.
Exception: Expansive soil need not be removed to the
depth of constant moisture, provided the confining pres-
sure in the expansive soil created by the fill and sup-
ported structure exceeds the swell pressure.
1808A.6.4 Stabilization. Where the active zone of expan-
sive soils is stabilized in lieu of designing foundations in
accordance with Section 1808A.6.1 or 1808A6.2, the soil
shall be stabilized by chemical, dewatering, presaturation or
equivalent techniques.
1808A.7 Foundations on or adjacent to slopes. The place-
ment of buildings and structures on or adjacent to slopes
steeper than one unit vertical in three units horizontal
(33.3-percent slope) shall comply with Sections 1808A.7.1
through 1808A.7.5.
1808A.7.1 Building clearance from ascending slopes. In
general, buildings below slopes shall be set a sufficient dis-
tance from the slope to provide protection from slope drain-
age, erosion and shallow failures. Except as provided in
Section 1808A.7.5 and Figure 1808A.7.1, the following cri-
teria will be assumed to provide this protection. Where the
existing slope is steeper than one unit vertical in one unit
horizontal (100-percent slope), the toe of the slope shall be
assumed to be at the intersection of a horizontal plane drawn
from the top of the foundation and a plane drawn tangent to
the slope at an angle of 45 degrees (0.79 rad) to the horizon-
tal. Where a retaining wall is constructed at the toe of the
slope, the height of the slope shall be measured from the top
of the wall to the top of the slope.
1808A.7.2 Foundation setback from descending slope
surface. Foundations on or adjacent to slope surfaces shall
be founded in firm material with an embedment and set back
from the slope surface sufficient to provide vertical and lat-
eral support for the foundation without detrimental settle-
ment. Except as provided for in Section 1808A.7.5 and
Figure 1808A.7.1, the following setback is deemed ade-
quate to meet the criteria. Where the slope is steeper than 1
unit vertical in 1 unit horizontal (100-percent slope), the
required setback shall be measured from an imaginary plane
45 degrees (0.79 rad) to the horizontal, projected upward
from the toe of the slope.
1808A.7.3 Pools. The setback between pools regulated by
this code and slopes shall be equal to one-half the building
footing setback distance required by this section. That por-
tion of the pool wall within a horizontal distance of 7 feet
216
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
(2 1 34 mm) from the top of the slope shall be capable of sup-
porting the water in the pool without soil support.
1808A.7.4 Foundation elevation. On graded sites, the top
of any exterior foundation shall extend above the elevation
of the street gutter at point of discharge or the inlet of an
approved drainage device a minimum of 12 inches (305
nmi) plus 2 percent. Alternate elevations are permitted sub-
ject to the approval of the building official, provided it can
be demonstrated that required drainage to the point of dis-
charge and away from the structure is provided at all loca-
tions on the site.
1808A.7.5 Alternate setback and clearance. Alternate
setbacks and clearances are permitted, subject to the
approval of the building official. The building official shall
be permitted to require a geotechnical investigation as set
forth in Section 1803A.5.10.
1808A.8 Concrete foundations. The design, materials and
construction of concrete foundations shall comply with Sec-
tions 1808A.8.1 through 1808A.8.6 and the provisions of
Chapter 19A.
1808A.8.1 Concrete or grout strength and mix propor-
tioning. Concrete or grout in foundations shall have a speci-
fied compressive strength (f '^) not less than the largest
applicable value indicated in Table 1808A.8.1.
Where concrete is placed through a funnel hopper at the
top of a deep foundation element, the concrete mix shall be
designed and proportioned so as to produce a cohesive
workable mix having a slump of not less than 4 inches (102
mm) and not more than 8 inches (204 nmi). Where concrete
or grout is to be pumped, the mix design including slump
shall be adjusted to produce a pumpable mixture.
1808A.8.2 Concrete cover. The concrete cover provided for
prestressed and nonprestressed reinforcement in foundations
shall be no less than the largest applicable value specified in
Table 1808A.8.2. Longitudinal bars spaced less than IV2
inches (38 mm) clear distance apart shall be considered bun-
dled bars for which the concrete cover provided shall also be
no less than that required by Section 7.7.4 of ACI 318. Con-
crete cover shall be measured from the concrete surface to the
outermost surface of the steel to which the cover requirement
applies. Where concrete is placed in a temporary or
permanent casing or a mandrel, the inside face of the casing
or mandrel shall be considered the concrete surface.
1808A.8.3 Placement of concrete. Concrete shall be
placed in such a manner as to ensure the exclusion of any
foreign matter and to secure a full-size foundation. Concrete
shall not be placed through water unless a tremie or other
method approved by the building official is used. Where
placed under or in the presence of water, the concrete shall
be deposited by approved means to ensure minimum segre-
gation of the mix and negligible turbulence of the water.
Where depositing concrete from the top of a deep founda-
tion element, the concrete shall be chuted directly into
smooth-sided pipes or tubes or placed in a rapid and contin-
uous operation through a funnel hopper centered at the top
of the element.
1808A.8.4 Protection of concrete. Concrete foundations
shall be protected from freezing during depositing and for a
period of not less than five days thereafter. Water shall not
be allowed to flow through the deposited concrete.
1808A.8.5 Forming of concrete. Concrete foundations are
permitted to be cast against the earth where, in the opinion
of the building official, soil conditions do not require
formwork. Where formwork is required, it shall be in accor-
dance with Chapter 6 of ACI 318.
1808A.8.6 Seismic requirements. See Section 1908A for
additional requirements for foundations of structures
assigned to Seismic Design Category D, E or F. <C
For structures assigned to Seismic Design Category D, E
or F, provisions of ACI 318, Sections 21.12.1 through
21.12.4, shall apply where not in conflict with the provi-
sions of Sections 1808A through 18 IDA
1808A.9 Vertical masonry foundation elements. Vertical
masonry foundation elements that are not foundation piers as
defined in Section 2102.1 shall be designed as piers, walls or
columns, as applicable, in accordance with TMS 402/ACI
530/ASCE 5.
FACE OF
smucwRE
For SI: 1 foot = 304.8 mm.
MLBABT THE SMALLER OFH/2mO 15 FEET
FIGURE 1808A7.1
FOUNDATION CLEARANCES FROM SLOPES
2010 CALIFORNIA BUILDING CODE
217
SOILS AND FOUNDATIONS
TABLE 18084.8.1
MINIMUM SPECIFIED COMPRESSIVE STRENGTH f^Of CONCRETE OR GROUT
FOUNDATION ELEMENT OR CONDITION
SPECIFIED COMPRESSIVE
STRENGTH, f'^
L Foundations for other structures assigned to Seismic Design Category D, E or F
3,000 psi
2. Precast nonprestressed driven piles
4,000 psi
5. Socketed drilled shafts
4,000 psi
4. Micropiles
4,000 psi
5. Precast prestressed driven piles
5,000 psi
For SI: 1 pound per square inch = 0.00689 MPa.
TABLE 1808A8.2
MINIMUM CONCRETE COVER
FOUNDATION ELEMENT OR CONDITION
MINIMUM COVER
1. Shallow foundations
In accordance with Section 7.7 of ACI 318
2. Precast nonprestressed deep foundation elements
Exposed to seawater
Not manufactured under plant conditions
Manufactured under plant control conditions
3 inches
2 inches
In accordance with Section 7.7.3 of ACI 318
3. Precast prestressed deep foundation elements
Exposed to seawater
Other
2.5 inches
In accordance with Section 7.7.3 of ACI 318
4. Cast-in-place deep foundation elements not enclosed by a steel pipe, tube or permanent
casing
2.5 inches
5. Cast-in-place deep foundation elements enclosed by a steel pipe, tube or permanent casing
1 inch
6. Structural steel core within a steel pipe, tube or permanent casing
2 inches
7. Cast-in-place drilled shafts enclosed by a stable rock socket
1 .5 inches
For SI: 1 inch = 25.4 mm.
SECTION 1809A
SHALLOW FOUNDATIONS
1809A.1 General. Shallow foundations shall be designed and
constructed in accordance with Sections 1809A.2 through
1809A.13.
1809A.2 Supporting soils. Shallow foundations shall be built
on undisturbed soil, compacted fill material or controlled
low-strength material (CLSM). Compacted fill material shall
be placed in accordance with Section 1804A.5. CLSM shall be
placed in accordance with Section 1804A.6.
1809A.3 Stepped footings. The top surface of footings shall be
level. The bottom surface of footings shall be permitted to have
a slope not exceeding one unit vertical in 10 units horizontal
(10-percent slope). Footings shall be stepped where it is neces-
sary to change the elevation of the top surface of the footing or
where the surface of the ground slopes more than one unit verti-
cal in 10 units horizontal (10-percent slope).
Individual steps in continuous footings shall not exceed 18
inches (457 mm) in height and the slope of a series of such steps
shall not exceed 1 unit vertical to 2 units horizontal (50 percent
slope) unless otherwise recommended by a geotechnical
report. The steps shall be detailed on the drawings. The local
effects due to the discontinuity of the steps shall be considered
in the design of the foundation,
1809A.4 Depth and width of footings. The minimum depth of
footings below the undisturbed ground surface shall be 12
inches (305 mm). Where applicable, the requirements of Sec-
tion 1809A.5 shall also be satisfied. The minimum width of
footings shall be 12 inches (305 mm).
1809A.5 Frost protection. Except where otherwise protected
from frost, foundations and other permanent supports of build-
#
218
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
#1
ings and structures shall be protected from frost by one or more
of the following methods:
1. Extending below the frost line of the locality;
2. Constructing in accordance with ASCE 32; or
3. Erecting on solid rock.
Exception: Free-standing buildings meeting all of the fol-
lowing conditions shall not be required to be protected:
1. Assigned to Occupancy Category I, in accordance
with Section 1604A.5;
2. Area of 600 square feet (56 m^) or less for light-frame
construction or 400 square feet (37 m^) or less for
other than light-frame construction; and
3. Eave height of 10 feet (3048 mm) or less.
Shallow foundations shall not bear on frozen soil unless such
frozen condition is of a permanent character.
1809A.6 Location of footings. Footings on granular soil shall
be so located that the line drawn between the lower edges of
adjoining footings shall not have a slope steeper than 30
degrees (0.52 rad) with the horizontal, unless the material sup-
porting the higher footing is braced or retained or otherwise lat-
erally supported in an approved manner or a greater slope has
been properly established by engineering analysis.
1809A.7 Prescriptive footings for light-frame construction.
Not permitted by DSA-SS, DSA-SS/CC or OSHPD,
1809A.8 Plain concrete footings. Not permitted by DSA-SS,
DSA-SS/CC or OSHPD.
1809A.9 Masonry-unit footings. Not permitted by DSA-SS,
DSA-SS/CC or OSHPD.
1809A.10 Reserved.
1809A.11 Steel grillage footings. Grillage footings of struc-
tural steel shapes shall be separated with approved steel spacers
and be entirely encased in concrete with at least 6 inches (152
mm) on the bottom and at least 4 inches (102 mm) at all other
points. The spaces between the shapes shall be completely
filled with concrete or cement grout.
1809A.12 Timber footings.
DSA-SS/CC or OSHPD.
Not permitted by DSA-SS,
1809A.13 Footing seismic ties. Where a structure is assigned
to Seismic Design Category D, E or F in accordance with Sec-
tion 1613A, individual spread footings founded on soil defined
in Section 1613A.5.2 as Site Class E or F shall be intercon-
nected by ties. Unless it is demonstrated that equivalent
restraint is provided by reinforced concrete beams within slabs
on grade or reinforced concrete slabs on grade, ties shall be
capable of carrying, in tension or compression, a force equal to
the lesser of the product of the larger footing design gravity
load times the seismic coefficient, S^s^ divided by 10 and 25
percent of the smaller footing design gravity load.
1809 A, 14 Pipes and trenches. Unless otherwise recommended
by the soils report, open or backfilled trenches parallel with a
footing shall not be below a plane having a downward slope of
1 unit vertical to 2 units horizontal (50 percent slope) from a
line 9 inches (229 mm) above the bottom edge of the footing,
and not closer than 18 inches (457 mm) from the face of such
footing.
Where pipes cross under footings, the footings shall be spe-
cially designed. Pipe sleeves shall be provided where pipes
cross through footings or footing walls and sleeve clearances
shall provide for possible footing settlement, but not less than 1
inch (25 mm) all around pipe.
Exception: Alternate trench locations and pipe clearances
are permitted when accepted by the registered design pro-
fessional in responsible charge and the enforcement agent.
SECTION 18104
DEEP FOUNDATIONS
1810A.1 General. Deep foundations shall be analyzed,
designed, detailed and installed in accordance with Sections
1810A.1 through 1810A.4.
1810A.1.1 Geotechnical investigation. Deep foundations
shall be designed and installed on the basis of a geotechnical
investigation as set forth in Section 1 803A.
1810A.1.2 Use of existing deep foundation elements.
Deep foundation elements left in place where a structure has
been demolished shall not be used for the support of new
construction unless satisfactory evidence is submitted to the
building official, which indicates that the elements are
sound and meet the requirements of this code. Such ele-
ments shall be load tested or redriven to verify their capaci-
ties. The design load applied to such elements shall be the
lowest allowable load as determined by tests or redriving
data.
1810A.1.3 Deep foundation elements classified as col-
umns. Deep foundation elements standing unbraced in air,
water or fluid soils shall be classified as columns and
designed as such in accordance with the provisions of this
code from their top down to the point where adequate lateral
support is provided in accordance with Section 1 8 1 OA. 2. 1 .
Exception: Where the unsupported height to least hori-
zontal dimension of a cast-in-place deep foundation ele-
ment does not exceed three, it shall be permitted to
design and construct such an element as a pedestal in
accordance with ACI 318.
1810A.1.4 Special types of deep foundations. The use of
types of deep foundation elements not specifically men-
tioned herein is permitted, subject to the approval of the
building official, upon the submission of acceptable test
data, calculations and other information relating to the
structural properties and load capacity of such elements.
The allowable stresses for materials shall not in any case
exceed the limitations specified herein.
1810A.2 Analysis. The analysis of deep foundations for design
shall be in accordance with Sections 1810A.2.1 through
1810A.2.5.
1810A.2.1 Lateral support. Any soil other than fluid soil
shall be deemed to afford sufficient lateral support to pre-
vent buckling of deep foundation elements and to permit the
2010 CALIFORNIA BUILDING CODE
219
SOILS AND FOUNDATIONS
design of the elements in accordance with accepted engi-
neering practice and the apphcable provisions of this code.
Where deep foundation elements stand unbraced in air,
water or fluid soils, it shall be permitted to consider them
laterally supported at a point 5 feet (1524 mm) into stiff soil
or 10 feet (3048 mm) into soft soil unless otherwise
approved by the building official on the basis of a geotechni-
cal investigation by a registered design professional.
1810A.2.2 Stability. Deep foundation elements shall be
braced to provide lateral stability in all directions. Three or
more elements connected by a rigid cap shall be considered
braced, provided that the elements are located in radial
directions from the centroid of the group not less than 60
degrees (1 rad) apart. A two-element group in a rigid cap
shall be considered to be braced along the axis connecting
the two elements. Methods used to brace deep foundation
elements shall be subject to the approval of the building offi-
cial.
Deep foundation elements supporting walls shall be
placed alternately in lines spaced at least 1 foot (305 mm)
apart and located symmetrically under the center of gravity
of the wall load carried, unless effective measures are taken
to provide for eccentricity and lateral forces, or the founda-
tion elements are adequately braced to provide for lateral
stability.
Exceptions:
1. Isolated cast-in-place deep foundation elements
without lateral bracing shall be permitted where
the least horizontal dimension is no less than 2 feet
(610 mm), adequate lateral support in accordance
with Section 1810A.2.1 is provided for the entire
height and the height does not exceed 12 times the
least horizontal dimension.
2. A single row of deep foundation elements without
lateral bracing is permitted for one- and two-fam-
ily dwellings and lightweight construction not
exceeding two stories above grade plane or 35 feet
(10 668 nam) in building height, provided the cen-
ters of the elements are located within the width of
the supported wall.
1810A.2.3 Settlement. The settlement of a single deep
foundation element or group thereof shall be estimated
based on approved methods of analysis. The predicted set-
tlement shall cause neither harmful distortion of, nor insta-
bility in, the structure, nor cause any element to be loaded
beyond its capacity.
1810A.2.4 Lateral loads. The moments, shears and lateral
deflections used for design of deep foundation elements
shall be established considering the nonlinear interaction of
the shaft and soil, as determined by a registered design pro-
fessional. Where the ratio of the depth of embedment of the
element to its least horizontal dimension is less than or equal
to six, it shall be permitted to assume the element is rigid.
1810A.2.4.1 Seismic Design Categories D through R
For structures assigned to Seismic Design Category D, E
or F, deep foundation elements on Site Class E or F sites,
as determined in Section 1613A.5.2, shall be designed
and constructed to withstand maximum imposed curva-
tures from earthquake ground motions and structure
response. Curvatures shall include free-field soil strains
modified for soil-foundation- structure interaction cou-
pled with foundation element deformations associated
with earthquake loads imparted to the foundation by the
structure.
Exception: Deep foundation elements that satisfy the
following additional detailing requirements shall be
deemed to comply with the curvature capacity
requirements of this section.
1. Precast prestressed concrete piles detailed in
accordance with Section 1810^4.3.8.3.3.
2. Cast-in-place deep foundation elements with a
minimum longitudinal reinforcement ratio of
0.005 extending the full length of the element
and detailed in accordance with Sections
21.6.4.2, 21.6.4.3 and 21.6.4.4 of ACI 318 as
required by Section 1810A.3.9.4.2.2.
1810A.2.5 Group effects. The analysis shall include group
effects on lateral behavior where the center-to-center spac-
ing of deep foundation elements in the direction of lateral
force is less than eight times the least horizontal dimension
of an element. The analysis shall include group effects on
axial behavior where the center-to-center spacing of deep
foundation elements is less than three times the least hori-
zontal dimension of an element.
1810A.3 Design and detailing. Deep foundations shall be
designed and detailed in accordance with Sections 1810A.3.1
through 1810A.3.12.
1810A.3.1 Design conditions. Design of deep foundations
shall include the design conditions specified in Sections
1810A.3.1.1 through 1810A.3.1.6, as applicable.
1810A.3.1.1 Design methods for concrete elements.
Where concrete deep foundations are laterally supported
in accordance with Section 1810A.2.1 for the entire
height and applied forces cause bending moments no
greater than those resulting from accidental eccentrici-
ties, structural design of the element using the load com-
binations of Section 1605 A. 3 and the allowable stresses
specified in this chapter shall be permitted. Otherwise,
the structural design of concrete deep foundation ele-
ments shall use the load combinations of Section
1605A.2 and approved strength design methods.
1810A.3.1.2 Composite elements. Where a single deep
foundation element comprises two or more sections of
different materials or different types spliced together,
each section of the composite assembly shall satisfy the
applicable requirements of this code, and the maximum
allowable load in each section shall be limited by the
structural capacity of that section.
1810A. 3.1.3 Mislocation. The foundation or superstruc-
ture shall be designed to resist the effects of the
mislocation of any deep foundation element by no less
than 3 inches (76 mm). To resist the effects of
mislocation, compressive overload of deep foundation
220
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
•I
elements to 110 percent of the allowable design load
shall be permitted.
1810A.3.1.4 Driven piles. Driven piles shall be designed
and manufactured in accordance with accepted engineer-
ing practice to resist all stresses induced by handling,
driving and service loads.
1810A.3.1.5 Helical piles. Helical piles shall be
designed and manufactured in accordance with accepted
engineering practice to resist all stresses induced by
installation into the ground and service loads.
1810A3.1.5.1 Helical Piles Seismic Requirements.
For structures assigned to Seismic Design Category
D, E or F, capacities of helical piles shall be deter-
mined in accordance with Section 1810A.3,3 by at
least two project specific preproduction tests for each
soil profile, size and depth of helical pile. At least two
percent of all production piles shall be proof tested to
the load determined in accordance with Section
1615AL10,
Helical piles shall satisfy corrosion resistance
requirements oflCC-ESAC 358. In addition, all heli-
cal pile materials that are subject to corrosion shall
include at least V;^ inch corrosion allowance.
Helical piles shall not be considered as carrying
any horizontal loads.
1810A.3.1.6 Casings. Temporary and permanent cas-
ings shall be of steel and shall be sufficiently strong to
resist collapse and sufficiently water tight to exclude any
foreign materials during the placing of concrete. Where a
permanent casing is considered reinforcing steel, the
steel shall be protected under the conditions specified in
Section 1810A.3.2.5. Horizontal joints in the casing shall
be spUced in accordance with Section 1810A.3.6.
1810A.3.2 Materials. The materials used in deep founda-
tion elements shall satisfy the requirements of Sections
1810A.3.2.1 through 1810A.3.2.8, as applicable.
1810A.3.2.1 Concrete. Where concrete is cast in a steel
pipe or where an enlarged base is formed by compacting
concrete, the maximum size for coarse aggregate shall be
V4 inch (19.1 mm). Concrete to be compacted shall have
a zero slump.
1810A.3.2.1.1 Seismic hooks. For structures
assigned to Seismic Design Category C, D, E or F in
accordance with Section 1613A, the ends of hoops,
spirals and ties used in concrete deep foundation ele-
ments shall be terminated with seismic hooks, as
defined in ACl 318, and shall be turned into the con-
fined concrete core.
1810A.3.2.2 Prestressing steel. Prestressing steel shall
conform to ASTM A 416.
18 lOA. 3.2.3 Structural steel. Structural steel piles, steel
pipe and fully welded steel piles fabricated from plates
shall conform to ASTM A 36, ASTM A 252, ASTM A
283, ASTM A 572, ASTM A 588, ASTM A 690, ASTM
A 913 or ASTM A 992.
1810A.3.2.4 Timber. Not permitted by DSA-SS,
DSA~SS/CC or OSHPD.
1810A. 3.2.5 Protection of materials. Where boring
records or site conditions indicate possible deleterious
action on the materials used in deep foundation elements
because of soil constituents, changing water levels or
other factors, the elements shall be adequately protected
by materials, methods or processes approved by the
building official. Protective materials shall be applied to
the elements so as not to be rendered ineffective by
installation. The effectiveness of such protective mea-
sures for the particular purpose shall have been thor-
oughly established by satisfactory service records or
other evidence.
1810A.3.2.6 Allowable stresses. The allowable stresses
for materials used in deep foundation elements shall not
exceed those specified in Table 1810A.3.2.6.
1810A.3.2.7 Increased allowable compressive stress
for cased cast-in-place elements. The allowable com-
pressive stress in the concrete shall be permitted to be
increased as specified in Table 1810A.3.2.6 for those
portions of permanently cased cast-in-place elements
that satisfy all of the following conditions:
L The design shall not use the casing to resist any
portion of the axial load imposed.
2. The casing shall have a sealed tip and be mandrel
driven.
3. The thickness of the casing shall not be less than
manufacturer's standard gage No. 14 (0.068 inch)
(1.75 mm),
4. The casing shall be seamless or provided with
seams of strength equal to the basic material and be
of a configuration that will provide confinement to
the cast-in-place concrete.
5. The ratio of steel yield strength {Fy) to specified
compressive strength if'^ shall not be less, than
six.
6. The nominal diameter of the element shall not be
greater than 16 inches (406 mm).
1810A. 3.2.8 Justification of higher allowable stresses.
Use of allowable stresses greater than those specified in
Section 1810A.3.2.6 shall be permitted where supporting
data justifying such higher stresses is filed with the build-
ing official. Such substantiating data shall include:
1. A geotechnical investigation in accordance with
Section 1803 A; and
2. Load tests in accordance with Section
1810A.3.3.1.2, regardless of the load supported by
the element.
The design and installation of the deep foundation ele-
ments shall be under the direct supervision of a regis-
tered design professional knowledgeable in the field of
soil mechanics and deep foundations who shall submit a
report to the building official stating that the elements as
installed satisfy the design criteria.
2010 CALIFORNIA BUILDING CODE
221
SOILS AND FOUNDATIONS
TABLE 1 81 0A3.2.6
ALLOWABLE STRESSES FOR MATERIALS USED IN DEEP FOUNDATION ELEMENTS
MATERIAL TYPE AND CONDITION
MAXIMUM ALLOWABLE STRESS °
1. Concrete or grout in compression''
Cast-in-place with a permanent casing in accordance with Section 1810A.3.2.7
Cast-in-place in a pipe, tube, other permanent casing or rock
Cast-in-place without a permanent casing
Precast nonprestressed
Precast prestressed
0.4/',
0.33/',
0.3/',
0.33/',
0.33/', -0.27/,,
2. Nonprestressed reinforcement in compression
0.4/^ < 30,000 psi
3. Structural steel in compression
Cores within concrete-filled pipes or tubes
Pipes, tubes or H-piles, where justified in accordance with Section 1810A.3.2.8
Pipes or tubes for micropiles
Other pipes, tubes or H-piles
HeHcal piles
0.5 F^< 32,000 psi
0.5 Fy < 32,000 psi
0.4 F^< 32,000 psi
0.35 F,,< 16,000 psi
0.6 Fy < 0.5 F„
4. Nonprestressed reinforcement in tension
Within micropiles
Other conditions
0.6/,
0.5/, < 24,000 psi
5. Structural steel in tension
Pipes, tubes or H-piles, where justified in accordance with Section 1810A.3.2.8
Other pipes, tubes or H-piles
HeUcal piles
0.5 F,< 32,000 psi
0.35 F,< 16,000 psi
0.6 Fy < 0.5 F„
6. Timber
In accordance with the AF&PA NDS
a. f\ is the specified compressive strength of the concrete or grout;_^^ is the compressive stress on the gross concrete section due to effective prestress forces only ;/y is
the specified yield strength of reinforcement; F^ is the specified minimum yield stress of structural steel; F^ is the specified minimum tensile stress of structural
steel.
b. The stresses specified apply to the gross cross-sectional area within the concrete surface. Where a temporary or permanent casing is used, the inside face of the cas-
ing shall be considered the concrete surface.
1810A,3.3 Determination of allowable loads. The allow-
able axial and lateral loads on deep foundation elements
shall be determined by an approved formula, load tests or
method of analysis.
1810A. 3.3.1 Allowable axial load. The allowable axial
load on a deep foundation element shall be determined in
accordance with Sections 1810A.3.3.1.1 through
1810A.3.3.1.9.
1810A.3.3.1.1 Driving criteria. The allowable com-
pressive load on any driven deep foundation element
where determined by the application of an approved
driving formula shall not exceed 40 tons (356 kN). For
allowable loads above 40 tons (356 kN), the wave
equation method of analysis shall be used to estimate
driveability for both driving stresses and net displace-
ment per blow at the ultimate load. Allowable loads
shall be verified by load tests in accordance with Sec-
tion 1810A.3.3.1.2. The formula or wave equation load
shall be determined for gravity-drop or power-actuated
hammers and the hammer energy used shall be the
maximum consistent with the size, strength and weight
of the driven elements. The use of a follower is permit-
ted only with the approval of the building official The
introduction of fresh hammer cushion or pile cushion
material just prior to final penetration is not permitted.
1810A.3.3.1.2 Load tests. Where design compres-
sive loads are greater than those determined using the
allowable stresses specified in Section 1810A.3.2.6,
where the design load for any deep foundation ele-
ment is in doubt, or where cast-in-place deep founda-
tion elements have an enlarged base formed either by
compacting concrete or by driving a precast base,
control test elements shall be tested in accordance
with ASTM D 1 143 or ASTM D 4945. At least one
element shall be load tested in each area of uniform
subsoil conditions. Where required by the building
official, additional elements shall be load tested where
necessary to establish the safe design capacity. The
resulting allowable loads shall not be more than
one-half of the ultimate axial load capacity of the test
element as assessed by one of the published methods
listed in Section 1810A.3.3.1.3 with consideration for
the test type, duration and subsoil. The ultimate axial
load capacity shall be determined by a registered
design professional with consideration given to toler-
able total and differential settlements at design load in
accordance with Section 1810A.2.3. In subsequent
installation of the balance of deep foundation ele-
ments, all elements shall be deemed to have a support-
ing capacity equal to that of the control element where
such elements are of the same type, size and relative
222
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
length as the test element; are installed using the same
or comparable methods and equipment as the test ele-
ment; are installed in similar subsoil conditions as the
test element; and, for driven elements, where the rate
of penetration (e.g., net displacement per blow) of
such elements is equal to or less than that of the test
element driven with the same hammer through a com-
parable driving distance.
1810A.3.3.1.3 Load test evaluation methods. It
shall be permitted to evaluate load tests of deep foun-
dation elements using any of the following me±ods:
1. Davisson Offset Limit.
2. Brinch-Hansen 90% Criterion.
3. Butler-Hoy Criterion.
4. Other methods approved by the building offi-
cial.
1810A.3.3.1.4 Allowable frictional resistance. The
assumed frictional resistance developed by any
uncased cast-in-place deep foundation element shall
not exceed one-sixth of the bearing value of the soil
material at minimum depth as set forth in Table
1 806A. 2, up to a maximum of 500 psf (24 kPa), unless
a greater value is allowed by the building official on
the basis of a geotechnical investigation as specified
in Section 1 803 A or a greater value is substantiated by
a load test in accordance with Section 1810A.3.3.1.2.
Frictional resistance and bearing resistance shall not
be assumed to act simultaneously unless determined
by a geotechnical investigation in accordance with
Section 1803A.
1810A.3.3.1.5 Uplift capacity of a single deep foun-
dation element. Where required by the design, the
uplift capacity of a single deep foundation element
shall be determined by an approved method of analy-
sis based on a minimum factor of safety of three or by
load tests conducted in accordance with ASTM D
3689. The maximum allowable uplift load shall not
exceed the ultimate load capacity as determined in
Section 1810A.3.3.L2, using the results of load tests
conducted in accordance with ASTM D 3689, divided
by a factor of safety of two.
Exception: Where uplift is due to wind or seismic
loading, the minimum factor of safety shall be two
where capacity is determined by an analysis and
one and one-half where capacity is detennined by
load tests.
1810A.3.3.1.6 Uplift capacity of grouped deep
foundation elements. For grouped deep foundation
elements subjected to uplift, the allowable working
uplift load for the group shall be calculated by an
approved method of analysis where the deep founda-
tion elements in the group are placed at a cen-
ter-to-center spacing of at least 2.5 times the least
horizontal dimension of the largest single element,
the allowable working uplift load for the group is per-
mitted to be calculated as the lesser of:
1. The proposed individual uplift working load
times the number of elements in the group.
2. Two-thirds of the effective weight of the group
and the soil contained within a block defined by
the perimeter of the group and the length of the
element.
1810A.3.3.1.7 Load-bearing capacity. Deep foun-
dation elements shall develop ultimate load capacities
of at least twice the design working loads in the desig-
nated load-bearing layers. Analysis shall show that no
soil layer underlying the designated load-bearing lay-
ers causes the load-bearing capacity safety factor to
be less than two.
1810A. 3.3.1.8 Bent deep foundation elements. The
load-bearing capacity of deep foundation elements
discovered to have a sharp or sweeping bend shall be
determined by an approved method of analysis or by
load testing a representative element.
1810A.3.3.1.9 Helical piles. The allowable axial
design load, P^, of helical piles shall be determined as
follows:
where P„ is the least value of:
(Equation 18A-4)
1. Sum of the areas of the helical bearing plates
times the ultimate bearing capacity of the soil or
rock comprising the bearing stratum.
2. Ultimate capacity determined from well-docu-
mented correlations with installation torque.
3. Ultimate capacity determined from load tests.
4. Ultimate axial capacity of pile shaft.
5 . Ultimate axial capacity of pile shaft couplings.
6. Sum of the ultimate axial capacity of helical
bearing plates affixed to pile.
1810A.3.3.2 Allowable lateral load. Where required by
the design, the lateral load capacity of a single deep foun-
dation element or a group thereof shall be determined by
an approved method of analysis or by lateral load tests to
at least twice the proposed design working load. The
resulting allowable load shall not be more than one-half
of the load that produces a gross lateral movement of 1
inch (25 mm) at the lower of the top of foundation ele-
ment and the ground surface, unless it can be shown that
the predicted lateral movement shall cause neither harm-
ful distortion of, nor instability in, the structure, nor
cause any element to be loaded beyond its capacity.
1810A.3.4 Subsiding soils. Where deep foundation ele-
ments are installed through subsiding fills or other subsid-
ing strata and derive support from underlying firmer
materials, consideration shall be given to the downward
frictional forces that may be imposed on the elements by the
subsiding upper strata.
Where the influence of subsiding fills is considered as
imposing loads on the element, the allowable stresses speci-
2010 CALIFORNIA BUILDING CODE
223
SOILS AND FOUNDATIONS
fied in this chapter shall be permitted to be increased where
satisfactory substantiating data are submitted.
1810A.3.5 Dimensions of deep foundation elements. The
dimensions of deep foundation elements shall be in accor-
dance with Sections 1810A.3.5.1 through 1810A.3.5.3, as
applicable.
1810A.3.5.1 Precast. The minimum lateral dimension of
precast concrete deep foundation elements shall be 8
inches (203 mm). Comers of square elements shall be
chamfered.
1810A.3.5.2 Cast-in-place or grouted-in-place. Cast-
in-place and grouted-in-place deep foundation elements
shall satisfy the requirements of this section.
1810A.3.5.2.1 Cased. Cast-in-place deep foundation
elements with a permanent casing shall have a nomi-
nal outside diameter of not less than 8 inches (203
mm).
1810A. 3.5.2.2 Uncased. Cast-in-place deep founda-
tion elements without a permanent casing shall have a
diameter of not less than 12 inches (305 mm). The ele-
ment length shall not exceed 30 times the average
diameter.
Exception: The length of the element is permitted
to exceed 30 times the diameter, provided the design
and installation of the deep foundations are under
the direct supervision of a registered design profes-
sional knowledgeable in the field of soil mechanics
and deep foundations. The registered design profes-
sional shall submit a report to the building official
stating that the elements were installed in compli-
ance with the approved construction documents.
1810A. 3.5.2.3 Micropiles.-Micropiles shall have an
outside diameter of 12 inches (305 mm) or less. The
minimum diameter set forth elsewhere in Section
1810A.3.5 shall not apply to micropiles.
1810A. 3.5.3 Steel. Steel deep foundation elements shall
satisfy the requirements of this section.
1810A.3.5.3.1 H-piles. Sections of H-piles shall
comply with the following:
1 . The flange projections shall not exceed 14 times
the minimum thickness of metal in either the
flange or the web and the flange widths shall not
be less than 80 percent of the depth of the sec-
tion.
2. The nominal depth in the direction of the web
shall not be less than 8 inches (203 mm).
3. Flanges and web shall have a minimum nomi-
nal thickness of Vg inch (9.5 mm).
1810A. 3.5.3.2 Steel pipes and tubes. Steel pipes and
tubes used as deep foundation elements shall have a
nominal outside diameter of not less than 8 inches (203
mm). Where steel pipes or tubes are driven open ended,
they shall have a minimum of 0.34 square inch (219
mm^) of steel in cross section to resist each 1,000
foot-pounds (1356 Nm) of pile hammer energy, or
shall have the equivalent strength for steels having a
yield strength greater than 35,000 psi (241 MPa) or the
wave equation analysis shall be permitted to be used to
assess compression stresses induced by driving to eval-
uate if the pile section is appropriate for the selected
hammer. Where a pipe or tube with wall thickness less
than 0.179 inch (4.6 mm) is driven open ended, a suit-
able cutting shoe shall be provided. Concrete-filled
steel pipes or tubes in structures assigned to Seismic
Design Category C, D, E or F shall have a wall thick-
ness of not less than Vi^ i^^ch (5 mm). The pipe or tube
casing for socketed drilled shafts shall have a nominal
outside diameter of not less than 1 8 inches (457 nmi), a
wall thickness of not less than Vg inch (9.5 mm) and a
suitable steel driving shoe welded to the bottom; the
diameter of the rock socket shall be approximately
equal to the inside diameter of the casing.
Exceptions:
1. There is no minimum diameter for steel
pipes or tubes used in micropiles.
2. For mandrel-driven pipes or tubes, the mini-
mum wall thickness shall be Vjo inch (2.5
mm).
1810A.3.5,3.3 Helical piles. Dimensions of the
central shaft and the number, size and thickness of
helical bearing plates shall be sufficient to support the
design loads.
1810A.3.6 Splices. Splices shall be constructed so as to pro-
vide and maintain true alignment and position of the compo-
nent parts of the deep foundation element during installation
and subsequent thereto and shall be designed to resist the
axial and shear forces and moments occurring at the loca-
tion of the splice during driving and for design load combi-
nations. Where deep foundation elements of the same type
are being sphced, sphces shall develop not less than 50 per-
cent of the bending strength of the weaker section. Where
deep foundation elements of different materials or different
types are being spliced, splices shall develop the full com-
pressive strength and not less than 50 percent of the tension
and bending strength of the weaker section. Where struc-
tural steel cores are to be spliced, the ends shall be milled or
ground to provide full contact and shall be full-depth
welded.
Splices occurring in the upper 10 feet (3048 mm) of the
embedded portion of an element shall be designed to resist
at allowable stresses the moment and shear that would result
from an assumed eccentricity of the axial load of 3 inches
(76 vam), or the element shall be braced in accordance with
Section 1810A.2.2 to other deep foundation elements that
do not have splices in the upper 10 feet (3048 mm) of
embedment.
1810A.3.6.1 Seismic Design Categories C through E
For structures assigned to Seismic Design Category C, D,
E or F splices of deep foundation elements shall develop
the lesser of the following:
1 . The full strength of the deep foundation element;
and
224
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
2. The axial and shear forces and moments from the
load combinations with overstrength factor in Sec-
tion 12.4.3.2 of ASCE 7.
1810A.3.7 Top of element detailing at cutoffs. Where a
minimum length for reinforcement or the extent of closely
spaced confinement reinforcement is specified at the top of
a deep foundation element, provisions shall be made so that
those specified lengths or extents are maintained after cut-
off.
1810A.3.8 Precast concrete piles. Precast concrete piles
shall be designed and detailed in accordance with Sections
1810A.3.8.1 through 1810A.3.8.3.
1810A.3.8.1 Reinforcement. Longitudinal steel shall be
arranged in a symmetrical pattern and be laterally tied
with steel ties or wire spiral spaced center to center as fol-
lows:
1 . At not more than 1 inch (25 mm) for the first five
ties or spirals at each end; then
2. At not more than 4 inches (102 mm), for the
remainder of the first 2 feet (610 mm) from each
end; and then
3. At not more than 6 inches (152 mm) elsewhere.
The size of ties and spirals shall be as follows:
1 . For piles having a least horizontal dimension of 16
inches (406 mm) or less, wire shall not be smaller
than 0.22 inch (5.6 nmi) (No. 5 gage).
2. For piles having a least horizontal dimension of
more than 16 inches (406 mm) and less than 20
inches (508 mm), wire shall not be smaller than
0.238 inch (6 mm) (No. 4 gage).
3. For piles having a least horizontal dimension of 20
inches (508 mm) and larger, wire shall not be
smaller than V4 inch (6.4 mm) round or 0.259 inch
(6.6 mm) (No. 3 gage).
1810A. 3.8.2 Precast nonprestressed piles. Precast
nonprestressed concrete piles shall comply with the
requirements of Sections 1 8 lOA. 3.8.2.1 through
1810A.3.8.2.3.
1810A, 3.8.2.1 Minimum reinforcement. Longitudi-
nal reinforcement shall consist of at least four bars
with a minimum longitudinal reinforcement ratio of
0.008.
1810A.3.8.2.2 Seismic reinforcement in Seismic
Design Categories C through F. For structures
assigned to Seismic Design Category C, D, E or F in
accordance with Section 1613A, precast
nonprestressed piles shall be reinforced as specified
in this section. The minimum longitudinal reinforce-
ment ratio shall be 0.01 throughout the length. Trans-
verse reinforcement shall consist of closed ties or
spirals with a minimum ^/g inch (9.5 mm) diameter.
Spacing of transverse reinforcement shall not exceed
the smaller of eight times the diameter of the smallest
longitudinal bar or 6 inches (152 mm) within a dis-
tance of three times the least pile dimension from the
bottom of the pile cap. Spacing of transverse rein-
forcement shall not exceed 6 inches (152 mm)
throughout the remainder of the pile.
1810A. 3.8.2.3 Additional seismic reinforcement in
Seismic Design Categories D through F. For struc-
tures assigned to Seismic Design Category D, E or F
in accordance with Section 1613A, transverse rein-
forcement shall be in accordance with Section
1810A.3.9.4.2.
1810A. 3.8.3 Precast prestressed piles. Precast pre-
stressed concrete piles shall comply with the requirements
of Sections 1810A.3.8.3.1 through 1810A.3.8.3.3.
1810A.3.8.3.1 Effective prestress. The effective pre-
stress in the pile shall not be less than 400 psi (2.76
MPa) for piles up to 30 feet (9144 mm) in length, 550
psi (3.79 MPa) for piles up to 50 feet (15 240 mm) in
length and 700 psi (4.83 MPa) for piles greater than
50 feet (15 240 mm) in length.
Effective prestress shall be based on an assumed
loss of 30,000 psi (207 MPa) in the prestressing steel.
The tensile stress in the prestressing steel shall not
exceed the values specified in ACI 318.
1810A. 3.8.3.2 Seismic reinforcement in Seismic
Design Category C. Not permitted by DSA-SS,
DSA-SS/CC or OSHPD,
18 lOA. 3.8.3.3 Seismic reinforcement in Seismic
Design Categories D through F. For structures
assigned to Seismic Design Category D, E or F in
accordance with Section 1613A, precast prestressed
piles shall have transverse reinforcement in accor-
dance with the following:
1 . Requirements in ACI 318, Chapter 2 1 , need not
apply, unless specifically referenced.
2. Where the total pile length in the soil is 35 feet
(10 668 mm) or less, the lateral transverse rein-
forcement in the ductile region shall occur
through the length of the pile. Where the pile
length exceeds 35 feet (10 668 mm), the ductile
pile region shall be taken as the greater of 35
feet (10 668 mm) or the distance from the
underside of the pile cap to the point of zero cur-
vature plus three times the least pile dimension.
3. In the ductile region, the center- to-center spac-
ing of the spirals or hoop reinforcement shall
not exceed one-fifth of the least pile dimension,
six times the diameter of the longitudinal strand
or 8 inches (203 mm), whichever is smallest.
4. Circular spiral reinforcement shall be spliced
by lapping one full turn and bending the end of
each spiral to a 90-degree hook or by use of a
mechanical or welded splice complying with
Section 12.14.3 of ACI 318.
2010 CALIFORNIA BUILDING CODE
225
SOILS AND FOUNDATIONS
5. Where the transverse reinforcement consists of
circular spirals, the volumetric ratio of spiral
transverse reinforcement in the ductile region
shall comply with the following:
Ps =0.25(fV/..)(A,M,,-
[0.5 + 1.4P/rcA,)]
but not less than:
1.0)
(Equation ia4-6)
p . = 0.\2(f\ Ify,) [0.5 + 1.4P/(/-', A,)]
> 0A2f\/fy, (Equation 18A-7)
and need not exceed:
p, = 0.021
where:
(Equation ISA -8)
Ag = Pile cross-sectional area, square inches
(mm^).
A^f, = Core area defined by spiral outside diam-
eter, square inches (mm^).
f\ = Specified compressive strength of con-
crete, psi (MPa)
fyh = Yield strength of spiral reinforcement
< 85,000 psi (586 MPa).
P = Axial load on pile, pounds (kN), as deter-
mined from Equations 16A-5 and 16A-7.
p^ = Volumetric ratio (vol. spiral/vol. core).
6. Where transverse reinforcement consists of
rectangular hoops and cross ties, the total
cross-sectional area of lateral transverse rein-
forcement in the ductile region with spacing, s,
and perpendicular dimension, h^, shall conform
to:
As,=03sK(f'Jfy,){Ag/A,,-L0)
[0,5 ^ I AP/ifc A,)]
(Equation 18A-9)
but not less than:
A,, =0A2sKrc/fyH) [0.5 + lAP/ifcA,)]
(Equation 18A-10)
where:
fyh
= < 70,000 psi (483 MPa).
= Cross-sectional dimension of pile core
measured center to center of hoop rein-
forcement, inch (nun).
= Spacing of transverse reinforcement
measured along length of pile, inch
(mm).
= Cross-sectional area of tranverse rein-
forcement, square inches (mm^).
f'c- specified compressive strength of con-
crete, psi (MPa).
The hoops and cross ties shall be equivalent to
deformed bars not less than No. 3 in size. Rectangular
hoop ends shall terminate at a comer with seismic
hooks.
Outside of the length of the pile requiring trans-
verse confinement reinforcing, the spiral or hoop
reinforcing with a volumetric ratio not less than
one-half of that required for transverse confinement
reinforcing shall be provided.
1810A.3.9 Cast-in-place deep foundations. Cast-in-
place deep foundation elements shall be designed and
detailed in accordance with Sections 1810A.3.9.1 through
1810A.3.9,6.
1810A.3.9.1 Design cracking moment. The design
cracking moment ((t)M„) for a cast-in-place deep founda-
tion element not enclosed by a structural steel pipe or
tube shall be determined using the following equation:
<j>M^=34fX.
(Equation 18A-11)
where:
/'c =
Specified compressive strength of concrete or
grout, psi (MPa)
Elastic section modulus, neglecting reinforce-
ment and casing, cubic inches (mm^)
1810A. 3.9.2 Required reinforcement. Where subject
to uplift or where the required moment strength deter-
mined using the load combinations of Section 1605 A. 2
exceeds the design cracking moment determined in
accordance with Section 1 8 lOA. 3.9.1, cast-in-place deep
foundations not enclosed by a structural steel pipe or
tube shall be reinforced.
1810A.3.9.3 Placement of reinforcement. Reinforce-
ment where required shall be assembled and tied
together and shall be placed in the deep foundation ele-
ment as a unit before the reinforced portion of the ele-
ment is filled with concrete.
Exceptions:
1. Steel dowels embedded 5 feet (1524 mm) or
less shall be permitted to be placed after con-
creting, while the concrete is still in a semifluid
state.
2. For deep foundation elements installed with a
hollow-stem auger, tied reinforcement shall be
placed after elements are concreted, while the
concrete is still in a semifluid state. Longitudi-
nal reinforcement without lateral ties shall be
placed either through the hollow stem of the
auger prior to concreting or after concreting,
while the concrete is still in a semifluid state.
3. For Group R-3 and U occupancies not exceed-
ing two stories of light-frame construction,
reinforcement is permitted to be placed after
concreting, while the concrete is still in a semi-
226
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
fluid state, and the concrete cover requirement
is permitted to be reduced to 2 inches (5 1 nun),
provided the construction method can be dem-
onstrated to the satisfaction of the building offi-
cial.
1810A.3.9.4 Seismic reinforcement. Where a structure
is assigned to Seismic Design Category C, reinforcement
shall be provided in accordance with Section
1810A.3.9.4.1. Where a structure is assigned to Seismic
Design Category D, E or F, reinforcement shall be pro-
vided in accordance with Section 1810A.3.9.4,2.
Exceptions:
1. Isolated deep foundation elements supporting
posts of Group R-3 and U occupancies not
exceeding two stories of Hght- frame construc-
tion shall be permitted to be reinforced as
required by rational analysis but with not less
than one No. 4 bar, without ties or spirals,
where detailed so the element is not subject to
lateral loads and the soil provides adequate lat-
eral support in accordance with Section
1810A.2.1.
2. Isolated deep foundation elements supporting
posts and bracing from decks and patios appur-
tenant to Group R-3 and U occupancies not
exceeding two stories of light-frame construc-
tion shall be permitted to be reinforced as
required by rational analysis but with not less
than one No. 4 bar, without ties or spirals,
where the lateral load, E, to the top of the ele-
ment does not exceed 200 pounds (890 N) and
the soil provides adequate lateral support in
accordance with Section 1810A.2.1.
3. Deep foundation elements supporting the con-
crete foundation wall of Group R-3 and U occu-
pancies not exceeding two stories of
light-frame construction shall be permitted to
be reinforced as required by rational analysis
but with not less than two No. 4 bars, without
ties or spirals, where the design cracking
moment determined in accordance with Section
1810A.3.9.1 exceeds the required moment
strength determined using the load combina-
tions with overstrength factor in Section
12.4.3.2 of ASCE 7 and the soil provides ade-
quate lateral support in accordance with Sec-
tion 1810A2.1.
4. Closed ties or spirals where required by Section
1810A.3.9.4.2 shall be permitted to be limited
to the top 3 feet (914 mm) of deep foundation
elements 10 feet (3048 nmi) or less in depth
supporting Group R-3 and U occupancies of
Seismic Design Category D, not exceeding two
stories of light-frame construction.
1810A.3.9.4.1 Seismic reinforcement in Seismic
Design Category C. For structures assigned to Seis-
mic Design Category C in accordance with Section
1613A, cast-in-place deep foundation elements shall
be reinforced as specified in this section. Reinforce-
ment shall be provided where required by analysis.
A minimum of four longitudinal bars, with a mini-
mum longitudinal reinforcement ratio of 0.0025, shall
be provided for throughout the minimum reinforced
length of the element as defined below starting at the
top of the element. The minimum reinforced length of
the element shall be taken as the greatest of the fol-
lowing:
1 . One-third of the element length;
2. A distance of 10 feet (3048 mm);
3. Three times the least element dimension; and
4. The distance from the top of the element to the
point where the design cracking moment deter-
mined in accordance with Section 1810A.3.9,1
exceeds the required moment strength deter-
mined using the load combinations of Section
1605A.2.
Transverse reinforcement shall consist of closed
ties or spirals with a minimum V^ inch (9.5 mm) diam-
eter. Spacing of transverse reinforcement shall not
exceed the smaller of 6 inches (152 mm) or 8-longitu-
dinal-bar diameters, within a distance of three times
the least element dimension from the bottom of the
pile cap. Spacing of transverse reinforcement shall
not exceed 16 longitudinal bar diameters throughout
the remainder of the reinforced length.
Exceptions:
1. The requirements of this section shall not
apply to concrete cast in structural steel
pipes or tubes.
2. A spiral- welded metal casing of a thickness
not less than manufacturer's standard gage
No. 14 gage (0.068 inch) is permitted to pro-
vide concrete confinement in lieu of the
closed ties or spirals. Where used as such,
the metal casing shall be protected against
possible deleterious action due to soil con-
stituents, changing water levels or other fac-
tors indicated by boring records of site
conditions.
1810A.3.9.4.2 Seismic reinforcement in Seismic
Design Categories D through F. For structures
assigned to Seismic Design Category D, E or F in
accordance with Section 1613A, cast-in-place deep
foundation elements shall be reinforced as specified
in this section. Reinforcement shall be provided
where required by analysis.
A minimum of four longitudinal bars, with a mini-
mum longitudinal reinforcement ratio of 0.005, shall
2010 CALIFORNIA BUILDING CODE
227
SOILS AND FOUNDATIONS
II
be provided throughout the minimum reinforced
length of the element as defined below starting at the
top of the element. The minimum reinforced length of
the element shall be taken as the greatest of the fol-
lowing:
1 . One-half of the element length;
2. A distance of 10 feet (3048 mm);
3. Three times the least element dimension; and
4. The distance from the top of the element to the
point where the design cracking moment deter-
mined in accordance with Section 1810A.3.9.1
exceeds the required moment strength deter-
mined using the load combinations of Section
1605A.2.
Transverse reinforcement shall consist of closed
ties or spirals no smaller than No. 3 bars for elements
with a least dimension up to 20 inches (508 mm), and
No. 4 bars for larger elements. Throughout the
remainder of the reinforced length outside the regions
with transverse confinement reinforcement, as speci-
fied in Section 1810A.3.9.4.2.1 or 1810A.3.9.4.2.2,
the spacing of transverse reinforcement shall not
exceed the least of the following:
1. 12 longitudinal bar diameters;
2. One-half the least dimension of the element;
and
3. 12 inches (305 mm).
Exceptions:
1. The requirements of this section shall not
apply to concrete cast in structural steel
pipes or tubes.
2. A spiral- welded metal casing of a thickness
not less than manufacturer's standard gage
No. 14 gage (0.068 inch) is permitted to pro-
vide concrete confinement in lieu of the
closed ties or spirals. Where used as such,
the metal casing shall be protected against
possible deleterious action due to soil con-
stituents, changing water levels or other fac-
tors indicated by boring records of site
conditions.
1810A. 3.9.4.2.1 Site Classes A through D. For
Site Class A, B, C or D sites, transverse confine-
ment reinforcement shall be provided in the ele-
ment in accordance with Sections 21.6.4.2,
21.6.4.3 and 21.6.4.4 of ACI 318 within three
times the least element dimension of the bottom of
the pile cap. A transverse spiral reinforcement
ratio of not less than one-half of that required in
Section 21.6.4.4(a) of ACI 318 shall be permitted
for concrete deep foundation elements,
1810A.3.9.4.2.2 Site Classes E and F. For Site
Class E or F sites, transverse confinement rein-
forcement shall be provided in the element in
accordance with Sections 21.6.4.2, 21.6.4.3 and
21.6.4.4 of ACI 318 within seven times the least
element dimension of the pile cap and within seven
times the least element dimension of the interfaces
of strata that are hard or stiff and strata that are
liquefiable or are composed of soft- to medium-
stiff clay.
1810A.3.9.5 Belled drilled shafts. Where drilled shafts
are belled at the bottom, the edge thickness of the bell
shall not be less than that required for the edge of foot-
ings. Where the sides of the bell slope at an angle less
than 60 degrees (1 rad) from the horizontal, the effects of
vertical shear shall be considered.
1810A.3.9.6 Socketed drilled shafts. Socketed drilled
shafts shall have a permanent pipe or tube casing that
extends down to bedrock and an uncased socket drilled
into the bedrock, both filled with concrete. Socketed
drilled shafts shall have reinforcement or a structural
steel core for the length as indicated by an approved
method of analysis.
The depth of the rock socket shall be sufficient to
develop the full load-bearing capacity of the element
with a minimum safety factor of two, but the depth shall
not be less than the outside diameter of the pipe or tube
casing. The design of the rock socket is permitted to be
predicated on the sum of the allowable load-bearing
pressure on the bottom of the socket plus bond along the
sides of the socket.
Where a structural steel core is used, the gross
cross-sectional area of the core shall not exceed 25 per-
cent of the gross area of the drilled shaft.
1810A.3.10 Micropiles. Micropiles shall be designed and
detailed in accordance with Sections 1810A.3.10.1 through
1810A.3.10.4.
1810A.3.10.1 Construction. Micropiles shall develop
their load-carrying capacity by means of a bond zone in
soil, bedrock or a combination of soil and bedrock.
Micropiles shall be grouted and have either a steel pipe or
tube or steel reinforcement at every section along the
length. It shall be permitted to transition from deformed
reinforcing bars to steel pipe or tube reinforcement by
extending the bars into the pipe or tube section by at least
their development length in tension in accordance with
ACI 318.
1810A.3.10.2 Materials. Reinforcement shall consist of
deformed reinforcing bars in accordance with ASTM A
615 Grade 60 or 75 or ASTM A 722 Grade 150.
The steel pipe or tube shall have a minimum wall
thickness of Vjg inch (4.8 mm). Splices shall comply with
Section 1810A.3.6. The steel pipe or tube shall have a
minimum yield strength of 45,000 psi (310 MPa) and a
minimum elongation of 15 percent as shown by mill cer-
tifications or two coupon test samples per 40,000 pounds
(18 160 kg) of pipe or tube.
1810A.3.10.3 Reinforcement. For micropiles or por-
tions thereof grouted inside a temporary or permanent
casing or inside a hole drilled into bedrock or a hole
drilled with grout, the steel pipe or tube or steel rein-
228
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
forcement shall be designed to carry at least 40 percent of
the design compression load. Micropiles or portions
thereof grouted in an open hole in soil without temporary
or permanent casing and without suitable means of veri-
fying the hole diameter during grouting shall be designed
to carry the entire compression load in the reinforcing
steel. Where a steel pipe or tube is used for reinforce-
ment, the portion of the grout enclosed within the pipe is
permitted to be included in the determination of the
allowable stress in the grout.
1810A,3,10.4 Seismic requirements. For structures
assigned to Seismic Design Category D,EorF, a perma-
nent steel casing having a minimum thickness of % inch
(10 mm) shall be provided from the top of the micropile
down to a minimum of 120 percent of the point of zero
curvature. Capacity of micropiles shall be determined in
accordance with Section 1810A33 by at least two pro-
ject specific preproduction tests for each soil profile, size
and depth of micropile. At least two percent of all produc-
tion piles shall be proof tested to the load determined in
accordance with Section 161 5 A, 1.10.
Steel casing length in soil shall be considered as
unbonded and shall not be considered as contributing to
friction. Casing shall provide confinement at least equiv-
alent to hoop reinforcing required by ACI 318 Section
21.12.4.
Reinforcement shall have Class 1 corrosion protection
in accordance with PTI Recommendations for P re-
stressed Rock and Soil Anchors. Steel casing design shall
include at least Vy^ inch corrosion allowance.
Micropiles shall not be considered as carrying any
horizontal loads.
1810A.3.11 Pile caps. Pile caps shall be of reinforced con-
crete, and shall include all elements to which vertical deep
foundation elements are connected, including grade beams
and mats. The soil immediately below the pile cap shall not
be considered as carrying any vertical load. The tops of ver-
tical deep foundation elements shall be embedded not less
than 3 inches (76 mm) into pile caps and the caps shall
extend at least 4 inches (102 mm) beyond the edges of the
elements. The tops of elements shall be cut or chipped back
to sound material before capping.
1810A.3.11.1 Seismic Design Categories C through F.
For structures assigned to Seismic Design Category C, D,
E or F in accordance with Section 1613A, concrete deep
foundation elements shall be connected to the pile cap by
embedding the element reinforcement or field-placed
dowels anchored in the element into the pile cap for a dis-
tance equal to their development length in accordance
with ACI 318. It shall be permitted to connect precast
prestressed piles to the pile cap by developing the ele-
ment prestressing strands into the pile cap provided the
connection is ductile. For deformed bars, the develop-
ment length is the full development length for compres-
sion, or tension in the case of uplift, without reduction for
excess reinforcement in accordance with Section 12.2.5
of ACI 318. Alternative measures for laterally confining
concrete and maintaining toughness and ductile-like
behavior at the top of the element shall be permitted pro-
vided the design is such that any hinging occurs in the
confined region.
The minimum transverse steel ratio for confinement
shall not be less than one-half of that required for col-
umns.
For resistance to uplift forces, anchorage of steel
pipes, tubes or H-piles to the pile cap shall be made by
means other than concrete bond to the bare steel section.
Concrete-filled steel pipes or tubes shall have reinforce-
ment of not less than 0.01 times the cross- sectional area
of the concrete fill developed into the cap and extending
into the fill a length equal to two times the required cap
embedment, but not less than the development length in
tension of the reinforcement.
1810A.3.11.2 Seismic Design Categories D through F.
For structures assigned to Seismic Design Category D, E
or F in accordance with Section 161 3A, deep foundation
element resistance to uplift forces or rotational restraint
shall be provided by anchorage into the pile cap,
designed considering the combined effect of axial forces
due to uplift and bending moments due to fixity to the
pile cap. Anchorage shall develop a minimum of 25 per-
cent of the strength of the element in tension. Anchorage
into the pile cap shall be capable of developing the fol-
lowing:
1. In the case of uplift, the least of the following:
nominal tensile strength of the longitudinal rein-
forcement in a concrete element; the nominal ten-
sile strength of a steel element; the frictional force
developed between the element and the soil multi-
plied by 1.3; and the axial tension force resulting
from the load combinations with overstrength fac-
tor in Section 12.4.3.2 of ASCE 7.
2. In the case of rotational restraint, the lesser of the
following: the axial force, shear forces and bend-
ing moments resulting from the load combinations
with overstrength factor in Section 12.4.3.2 of
ASCE 7 or development of the full axial, bending
and shear nominal strength of the element.
Where the vertical lateral-force-resisting elements are
columns, the pile cap flexural strengths shall exceed the
column flexural strength. The connection between batter
piles and pile caps shall be designed to resist the nominal
strength of the pile acting as a short column. Batter piles
and their connection shall be capable of resisting forces
and moments from the load combinations with
overstrength factor in Section 12.4.3.2 of ASCE 7.
1810A.3.12 Grade beams. For structures assigned to 5^/^"-
mic Design Category D, E or F in accordance with Section
1613A, grade beams shall comply with the provisions in
Section 21.12.3 of ACI 318 for grade beams, except where
they have the capacity to resist the forces from the load com-
binations with overstrength factor in Section 12.4.3.2 of
ASCE 7.
1810A.3.13 Seismic ties. For structures assigned to Seismic
Design Category C, D, E or F in accordance with Section
2010 CALIFORNIA BUILDING CODE
229
SOILS AND FOUNDATIONS
1613A, individual deep foundations shall be interconnected
by ties. Unless it can be demonstrated that equivalent
restraint is provided by reinforced concrete beams within
slabs on grade or reinforced concrete slabs on grade or con-
finement by competent rock, hard cohesive soils or very
dense granular soils, ties shall be capable of carrying, in ten-
sion or compression, a force equal to the lesser of the prod-
uct of the larger pile cap or column design gravity load times
the seismic coefficient, Sj^s, divided by 10, and 25 percent of
the smaller pile or colunrn design gravity load.
Exception: In Group R-3 and U occupancies of
light-frame construction, deep foundation elements sup-
porting foundation walls, isolated interior posts detailed
so the element is not subject to lateral loads or exterior
decks and patios are not subject to interconnection where
the soils are of adequate stiffness, subject to the approval
of the building official.
1810A.4 Installation. Deep foundations shall be installed in
accordance with Section 1810A.4. Where a single deep foun-
dation element comprises two or more sections of different
materials or different types spliced together, each section shall
satisfy the applicable conditions of installation.
1810A.4.1 Structural integrity. Deep foundation elements
shall be installed in such a manner and sequence as to pre-
vent distortion or damage that may adversely affect the
structural integrity of adjacent structures or of foundation
elements being installed or akeady in place and as to avoid
compacting the surrounding soil to the extent that other
foundation elements cannot be installed properly.
1810A.4.1.1 Compressive strength of precast con-
crete piles. A precast concrete pile shall not be driven
before the concrete has attained a compressive strength
of at least 75 percent of the specified compressive
strength (f\), but not less than the strength sufficient to
withstand handling and driving forces.
1810A.4.1.2 Casing. Where cast-in-place deep founda-
tion elements are formed through unstable soils and con-
crete is placed in an open-drilled hole, a casing shall be
inserted in the hole prior to placing the concrete. Where
the casing is withdrawn during concreting, the level of
concrete shall be maintained above the bottom of the cas-
ing at a sufficient height to offset any hydrostatic or lat-
eral soil pressure. Driven casings shall be mandrel driven
their full length in contact with the surrounding soil.
1810A.4.1.3 Driving near uncased concrete. Deep
foundation elements shall not be driven within six ele-
ment diameters center to center in granular soils or
within one-half the element length in cohesive soils of an
uncased element filled with concrete less than 48 hours
old unless approved by the building official. If the con-
crete surface in any completed element rises or drops, the
element shall be replaced. Driven uncased deep founda-
tion elements shall not be installed in soils that could
cause heave.
1810A. 4.1.4 Driving near cased concrete. Deep foun-
dation elements shall not be driven within four and
one-half average diameters of a cased element filled with
concrete less than 24 hours old unless approved by the
building official. Concrete shall not be placed in casings
within heave range of driving.
1810A.4.1.5 Defective timber piles. Not permitted by
DSA-SS, DSA-SS/CC or OSHPD.
1810A.4.2 Identification. Deep foundation materials shall
be identified for conformity to the specified grade with this
identity maintained continuously from the point of manu-
facture to the point of installation or shall be tested by an
approved agency to determine conformity to the specified
grade. The approved agency shall furnish an affidavit of
compliance to the building official.
1810A.4.3 Location plan. A plan showing the location and
designation of deep foundation elements by an identifica-
tion system shall be filed with the building official prior to
installation of such elements. Detailed records for elements
shall bear an identification corresponding to that shown on
the plan.
1810A.4.4 Preexcavation. The use of jetting, angering or
other methods of preexcavation shall be subject to the
approval of the building official. Where permitted,
preexcavation shall be carried out in the same manner as
used for deep foundation elements subject to load tests and
in such a manner that will not impair the carrying capacity of
the elements already in place or damage adjacent structures.
Element tips shall be driven below the preexcavated depth
until the required resistance or penetration is obtained.
1810A.4.5 Vibratory driving. Vibratory drivers shall only
be used to install deep foundation elements where the ele-
ment load capacity is verified by load tests in accordance
with Section 1810A.3.3.1.2. The installation of production
elements shall be controlled according to power consump-
tion, rate of penetration or other approved means that ensure
element capacities equal or exceed those of the test ele-
ments.
1810A.4.6 Heaved elements. Deep foundation elements
that have heaved during the driving of adjacent elements
shall be redriven as necessary to develop the required capac-
ity and penetration, or the capacity of the element shall be
verified by load tests in accordance with Section
1810A.3.3.1.2.
1810A.4.7 Enlarged base cast-in-place elements.
Enlarged bases for cast-in-place deep foundation elements
formed by compacting concrete or by driving a precast base
shall be formed in or driven into granular soils. Such ele-
ments shall be constructed in the same manner as successful
prototype test elements driven for the project. Shafts
extending through peat or other organic soil shall be
encased in a permanent steel casing. Where a cased shaft is
used, the shaft shall be adequately reinforced to resist col-
umn action or the annular space around the shaft shall be
filled sufficiently to reestablish lateral support by the soil.
Where heave occurs, the element shall be replaced unless it
is demonstrated that the element is undamaged and capable
of carrying twice its design load.
230
2010 CALIFORNIA BUILDING CODE
SOILS AND FOUNDATIONS
1810A.4.8 Hollow-stem augered, cast-in-place elements.
Where concrete or grout is placed by pumping through a
hollow-stem auger, the auger shall be permitted to rotate in a
clockwise direction during withdrawal. As the auger is
withdrawn at a steady rate or in increments not to exceed 1
foot (305 mm), concreting or grouting pumping pressures
shall be measured and maintained high enough at all times
to offset hydrostatic and lateral earth pressures. Concrete or
grout volumes shall be measured to ensure that the volume
of concrete or grout placed in each element is equal to or
greater than the theoretical volume of the hole created by the
auger. Where the installation process of any element is inter-
rupted or a loss of concreting or grouting pressure occurs,
the element shall be redrilled to 5 feet (1524 mm) below the
elevation of the tip of the auger when the installation was
interrupted or concrete or grout pressure was lost and
reformed. Angered cast-in-place elements shall not be
installed within six diameters center to center of an element
filled with concrete or grout less than 12 hours old, unless
approved by the building officiaL If the concrete or grout
level in any completed element drops due to installation of
an adjacent element, the element shall be replaced.
1810A.4.9 Socketed drilled shafts. The rock socket and
pipe or tube casing of socketed drilled shafts shall be thor-
oughly cleaned of foreign materials before filling with con-
crete. Steel cores shall be bedded in cement grout at the base
of the rock socket.
1810A.4.10 Mieropiles. Micropile deep foundation ele-
ments shall be permitted to be formed in holes advanced by
rotary or percussive drilling methods, with or without cas-
ing. The elements shall be grouted with a fluid cement
grout. The grout shall be pumped through a tremie pipe
extending to the bottom of the element until grout of suit-
able quality returns at the top of the element. The following
requirements apply to specific installation methods:
1 . For mieropiles grouted inside a temporary casing, the
reinforcing bars shall be inserted prior to withdrawal
of the casing. The casing shall be withdrawn in a con-
trolled manner with the grout level maintained at the
top of the element to ensure that the grout completely
fills the drill hole. During withdrawal of the casing,
the grout level inside the casing shall be monitored to
verify that the flow of grout inside the casing is not
obstructed.
2. For a micropile or portion thereof grouted in an open
drill hole in soil without temporary casing, the mini-
mum design diameter of the drill hole shall be verified
by a suitable device during grouting.
3. For mieropiles designed for end bearing, a suitable
means shall be employed to verify that the bearing
surface is properly cleaned prior to grouting.
4. Subsequent mieropiles shall not be drilled near ele-
ments that have been grouted until the grout has had
sufficient time to harden.
5. Mieropiles shall be grouted as soon as possible after
drilling is completed.
II
6. For mieropiles designed with a full-length casing, the
casing shall be pulled back to the top of the bond zone
and reinserted or some other suitable means
employed to assure grout coverage outside the casing.
1810A.4.11 Helical piles. Hehcal piles shall be installed to
specified embedment depth and torsional resistance criteria
as determined by a registered design professional. The
torque applied during installation shall not exceed the maxi-
mum allowable installation torque of the helical pile.
1810A.4.12 Special inspection. Special inspections in
accordance with Sections 1704A.8 and 1704A.9 shall be
provided for driven and cast-in-place deep foundation ele-
ments, respectively. Special inspections in accordance with
Section 1704A.10 shall be provided for helical piles.
SECTION 1811 A I I
PRESTRESSED ROCK AND
SOIL FOUNDATION ANCHORS
181 1 A, 1 General The requirements of this section address the
use of vertical rock and soil anchors in resisting seismic or
wind overturning forces resulting in tension on shallow foun-
dations.
1811A.2 Adoption, Except for the modifications as set forth in
Sections 1811 A. 3 and 181 lAA, all Prestressed Rock and Soil
Foundation Anchors shall be designed in accordance with PTl
Recommendations for Prestressed Rock and Soil Anchors.
1811A.3 Geotechnical Requirements. Geotechnical report for
the Prestressed Rock and Soil Foundation Anchors shall
address the following:
1. Minimum diameter and minimum spacing for the
anchors including consideration of group effects.
2. Maximum unbonded length and minimum bonded
length of the tendon.
3. Maximum recommended anchor tension capacity
based upon the soil or rock strength/grout bond and
anchor depth/spacing.
4. Allowable bond stress at the ground/grout interface
and applicable factor of safety for ultimate bond stress.
5. Anchor axial tension stiffness recommendations at the
anticipated anchor axial tension displacements, when
required for structural analysis.
6. Minimum grout pressure for installation and
post-grout pressure.
7. Class I Corrosion Protection is required for all perma-
nent anchors. Geotechnical report shall specify the
corrosion protection recommendations for temporary
anchors.
8. Performance test shall be at a minimum of 1.6 times the
design loads. There shall be a minimum of two
preproduction test anchors. Preproduction test
anchors shall be tested to ultimate load or 0.80 times
the specified minimum tensile strength of the tendon. A
Creep test is required for all prestressed anchors with
greater than 10 kips of lock-off prestressing load.
2010 CALIFORNIA BUILDING CODE
231
SOILS AND FOUNDATIONS
9. Lock'OJf pre stressing load requirements.
10, Acceptable drilling methods.
11. Geotechnical observation and monitoring require-
ments.
1S11A.4 Structural requirements,
1. Tendons shall be thread-bar anchors conforming to
ASTMA 722.
2. The anchors shall be placed vertical.
3. Design Loads shall be based upon the load combinations
in Section 1605A.3.1 and shall not exceed 60 percent of
the specified minimum tensile strength of the tendons.
I I 4. Ultimate Load shall be based upon Section 161 5 A. 1.10
and shall not exceed 80 percent of the specified minimum
tensile strength of the tendons.
5. The anchor shall be designed to fail in grout bond to the
soil or rock before pullout of the soil wedge by group
effect.
6. Foundation design shall incorporate the affect of lock-
offloads.
7. Design shall account for as-built locations of soil
anchors considering all the acceptable construction tol-
erances.
8. Design shall account for both short and long term defor-
mation.
9. Enforcement agency may require consideration of
anchor deformation in evaluating deformation compati-
bility or building drift where it may be significant.
232
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 19 - CONCRETE
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
1901.1.1
X
1901.1.2
X
1901.1.3
X
1901.1.4
X
1908.1.2
X
1908.1.3
X
1908.1.9.1
X
1911.11.1
X
1912.1.1
X
1912.1.2
X
1912.2 & subsections
X
1916.1
X
1916.1.2
X
1916.1.3
X
1916.1.4
X
1916.1.5
X
1916.1.6
X
1916.1.7
X
1916.1.8
X
1916.1.9
X
1916.1.10
X
1916.1.11
X
1916.1.11.1
X
1916.1.11.2
X
1916.1.11.3
X
1916.1.11.4
X
1916.1.11.5
X
1916.2.1
X
1916.2.2
X
1916.3.1
X
1916.3.2.1
X
1916.3.2.2
X
1916.3.3.1
X
1916.3.3.2
X
1916.4.1
X
1916.4.2
X
(continued)
2010 CALIFORNIA BUILDING CODE
233
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 19 - CONCRETE— continued
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
1916.4.3
X
1916.4.4
X
1916.4.5
X
1916.4.6
X
1916.4.7
X
1916.4.8
X
1916.4.9
X
1916.4.10
X
1916.5.1
X
1916.5.2
X
1916.5.3
X
1916.5.4
X
1916.5.5
X
1916.6
X
234
2010 CALIFORNIA BUILDING CODE
CHAPTER 19
CONCRETE
Italics are used for text within Sections 1903 through 1908 of this code to indicate provisions that differ from ACI 318.
SECTION 1901
GENERAL
1901.1 Scope. The provisions of this chapter shall govern the
materials, quality control, design and construction of concrete
used in structures.
1901.1.1 Application. The scope of application of Chapter
19 is as follows:
Community college buildings regulated by the Division
of the State Architect-Structural Safety/Community Col-
leges (DSA-SS/CC), as listed in Section 1,9,2.2.
1901.1.2 Amendments in this chapter. DSA-SS/CC adopts
this chapter and all amendments.
Exceptions: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency^ as follows:
Division of the State Architect-Structural Safety/
Community Colleges:
[DSA-SS/CC] For applications listed in Section
1.9.2.2.
1901.1.3 Reference to other chapters. [DSA-SS/CC]
Where reference within this chapter is made to sections in
Chapters 17 and 18, the provisions in Chapters 17 A, and
ISA, respectively, shall apply instead.
1901.1.4 Amendments. [DSA-SS/CC] See Section 1916 for
additional requirements applicable to community colleges,
1901.2 Plain and reinforced concrete. Structural concrete
shall be designed and constructed in accordance with the
requirements of this chapter and ACI 318 as amended in Sec-
tion 1908 of this code. Except for the provisions of Sections
1904 and 1910, the design and construction of slabs on grade
shall not be governed by this chapter unless they transmit verti-
cal loads or lateral forces from other parts of the structure to the
soil.
1901.3 Source and applicability. The format and subject mat-
ter of Sections 1902 through 1907 of this chapter are patterned
after, and in general conformity with, the provisions for struc-
tural concrete in ACI 318.
1901.4 Construction documents. The construction docu-
ments for structural concrete construction shall include:
1 . The specified compressive strength of concrete at the
stated ages or stages of construction for which each
concrete element is designed.
2. The specified strength or grade of reinforcement.
3. The size and location of structural elements, reinforce-
ment and anchors.
4. Provision for dimensional changes resulting from
creep, shrinkage and temperature.
5. The magnitude and location of prestressing forces.
6. Anchorage length of reinforcement and location and
length of lap splices.
7. Type and location of mechanical and welded splices of
reinforcement.
8. Details and location of contraction or isolation joints
specified for plain concrete.
9. Minimum concrete compressive strength at time of
posttensioning.
10. Stressing sequence for posttensioning tendons.
1 1 . For structures assigned to Seismic Design Category D,
E or F, a statement if slab on grade is designed as a
structural diaphragm (see Section 21. 12.3.4 of ACI
318).
1901.5 Special inspection. The special inspection of concrete
elements of buildings and structures and concreting operations
shall be as required by Chapter 17.
SECTION 1902
DEFINITIONS
1902.1 General. The words and terms defined in ACI 318
shall, for the purposes of this chapter and as used elsewhere in
this code for concrete construction, have the meanings shown
in ACI 318 as modified by Section 1908.1.1.
SECTION 1903
SPECIFICATIONS FOR TESTS AND MATERIALS
1903.1 General. Materials used to produce concrete, concrete
itself and testing thereof shall comply with the applicable stan-
dards listed in ACI 318. Where required, special inspections
and tests shall be in accordance with Chapter 1 7,
1903.2 Glass fiber reinforced concrete. Glass fiber rein-
forced concrete (GFRC) and the materials used in such con-
crete shall be in accordance with the PCIMNL 128 standard.
2010 CALIFORNIA BUILDING CODE
235
CONCRETE
SECTION 1904
DURABILITY REQUIREMENTS
1904.1 Water-cementitious materials ratio. Where maximum
water-cementitious materials ratios are specified in ACI 318,
they shall be calculated in accordance with ACI 318, Section 4. 1 .
1904.2 Exposure categories and classes. Concrete shall be
assigned to exposure classes in accordance with ACI 318, Sec-
tion 4.2, based on:
1 . Exposure to freezing and thawing in a moist condition or
deicer chemicals;
2. Exposure to sulfates in water or soil;
3. Exposure to water where the concrete is intended to have
low permeability; and
4. Exposure to chlorides from deicing chemicals, salt,
saltwater, brackish water, seawater or spray from these
sources, where the concrete has steel reinforcement.
1904.3 Concrete properties. Concrete mixtures shall conform
to the most restrictive maximum water-cementitious materials
ratios and minimum specified concrete compressive strength
requirements of ACI 318, Section 4.3, based on the exposure
classes assigned in Section 1904.2.
Exception: For occupancies and appurtenances thereto in
Group R occupancies that are in buildings less than four
stories above grade plane, normal-weight aggregate con-
crete is permitted to comply with the requirements of Table
1904.3 based on the weathering classification (freezing and
thawing) determined from Figure 1904.3 in lieu of the
requirements of ACI 31 8y Table 4.3.1.
1904.4 Freezing and thawing exposures. Concrete that will
be exposed to freezing and thawing, in the presence of mois-
ture, with or without deicing chemicals being present, shall
comply with Sections 1904.4.1 and 1904.4.2.
1904.4.1 Air entrainment. Concrete exposed to freezing
and thawing while moist shall be air entrained in accordance
with ACI 318, Section 4.4.1.
1904.4.2 Deicing chemicals. For concrete exposed to
freezing and thawing in the presence of moisture and
deicing chemicals, the maximum weight of fly ash, other
pozzolans, silica fume or slag that is included in the con-
crete shall not exceed the percentages of the total weight of
cementitious materials permitted by ACI 318, Section
4.4.2.
1904.5 Alternative cementitious materials for sulfate expo-
sure. Alternative combinations of cementitious materials for use
in sulfate-resistant concrete to those listed in ACI 318, Table
4.3.1 shall be permitted in accordance with ACI 318, Section
4.5.1.
SECTION 1905
CONCRETE QUALITY, MIXING AND PLACING
1905.1 General. The required strength and durability of con-
crete shall be determined by compliance with the proportion-
ing, testing, mixing and placing provisions of Sections
1905.1.1 through 1905.13.
1905.1.1 Strength. Concrete shall be proportioned to pro-
vide an average compressive strength as prescribed in Sec-
tion 1905.3 and shall satisfy the durability criteria of Section
1904. Concrete shall be produced to minimize the frequency
of strengths below/'^ as prescribed in Section 1905.6.3. For
concrete designed and constructed in accordance with this
chapter, f\ shall not be less than 2,500 psi (17.22 MPa). No
maximum specified compressive strength shall apply unless
restricted by a specific provision of this code or ACI 318.
1905.2 Selection of concrete proportions. Concrete propor-
tions shall be determined in accordance with the provisions of
ACI 318, Section 5.2.
1905.3 Proportioning on tlie basis of field experience
and/or trial mixtures. Concrete proportioning determined on
the basis of field experience and/or trial mixtures shall be done
in accordance with ACI 318, Section 5.3.
TABLE 1904.3
MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f ^
TYPE OR LOCATION OF CONCRETE CONSTRUCTION
MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f '^at 28 days, psi)
Negligible exposure
Moderate exposure
Severe exposure
Basement walls'^ and foundations not exposed to the weather
2,500
2,500
2,500^
Basement slabs and interior slabs on grade, except garage floor slabs
2,500
2,500
2,500^
Basement walls^, foundation walls, exterior walls and other vertical
concrete surfaces exposed to the weather
2,500
3,000*>
3,000^
Driveways, curbs, walks, patios, porches, carport slabs, steps and
other flatwork exposed to the weather, and garage floor slabs
2,500
3,000*''^
3,500'''^
For SI: 1 pound per square inch = 0.00689 MPa.
a. Concrete in these locations that can be subjected to freezing and thawing during construction shall be of air-entrained concrete in accordance with Section
1904.2.1.
b. Concrete shall be air entrained in accordance with Section 1904.4.1,
c. Structural plain concrete basement walls are exempt from the requirements for exposure conditions of Section 1904.3 (see Section 1909.6.1).
d. For garage floor slabs where a steel trowel finish is used, the total air content required by Section 1904.4.1 is permitted to be reduced to not less than 3 percent, pro-
vided the minimum specified compressive strength of the concrete is increased to 4,000 psi.
236
2010 CALIFORNIA BUILDING CODE
CONCRETE
NEGLIGIBLE
FIGURE 1904.3
WEATHERING PROBABILITY MAP FOR CONCRETE^' ^' ""
a. Lines defining areas are approximate only. Local areas can be more or less severe than indicated by the region classification.
b. A "severe" classification is where weather conditions encourage or require the use of deicing chemicals or where there is potential for a continuous presence of
moisture during frequent cycles of freezing and thawing. A "moderate" classification is where weather conditions occasionally expose concrete in the presence of
moisture to freezing and thawing, but where deicing chemicals are not generally used. A "negligible" classification is where weather conditions rarely expose con-
crete in the presence of moisture to freezing and thawing.
c. Alaska and Hawaii are classified as severe and negligible, respectively.
1905.4 Proportioning without field experience or trial mix-
tures. Concrete proportioning determined without field expe-
rience or trial mixtures shall be done in accordance with ACI
318, Section 5.4.
1905.5 Average strength reduction. As data become avail-
able during construction, it is permissible to reduce the amount
by which the average compressive strength (f'^) is required to
exceed the specified value off\ in accordance with ACI 318,
Section 5.5.
1905.6 Evaluation and acceptance of concrete. The criteria
for evaluation and acceptance of concrete shall be as specified
in Sections 1905.6.2 through 1905.6.5.
1905.6.1 Qualified technicians. Concrete shall be tested in
accordance with the requirements in Sections 1905.6.2
through 1905.6.5. Qualified field testing technicians shall
perform tests on fresh concrete at the job site, prepare speci-
mens required for curing under field conditions, prepare
specimens required for testing in the laboratory and record
the temperature of the fresh concrete when preparing speci-
mens for strength tests. Qualified laboratory technicians
shall perform all required laboratory tests.
1905.6.2 Frequency of testing. The frequency of conduct-
ing strength tests of concrete and the minimum number of
tests shall be as specified in ACI 318, Section 5.6.2.
Exception: When the total volume of a given class of
concrete is less than 50 cubic yards (38 m^), strength tests
are not required when evidence of satisfactory strength is
submitted to and approved by the building official.
1905.6.3 Strength test specimens. Specimens prepared for
acceptance testing of concrete in accordance with Section
1905.6.2 and strength test acceptance criteria shall comply
with the provisions of ACI 318, Section 5.6.3.
1905.6.4 Field-cured specimens. Where required by the
building official to determine adequacy of curing and pro-
tection of concrete in the structure, specimens shall be pre-
2010 CALIFORNIA BUILDING CODE
237
CONCRETE
pared, cured, tested and test results evaluated for acceptance
in accordance with ACI 318, Section 5.6.4.
1905.6.5 Low-strength test results. Where any strength
test (see ACI 318, Section 5.6.2.4) falls below the specified
value of/'c, the provisions of ACI 318, Section 5.6.5, shall
apply.
1905.7 Preparation of equipment and place of deposit. Prior
to concrete being placed, the space to receive the concrete and
the equipment used to deposit it shall comply with ACI 318,
Section 5.7.
1905.8 Mixing. Mixing of concrete shall be performed in
accordance with ACI 318, Section 5.8.
1905.9 Conveying. The method and equipment for conveying
concrete to the place of deposit shall comply with ACI 318,
Section 5.9.
1905.10 Depositing. The depositing of concrete shall comply
with the provisions of ACI 318, Section 5.10.
1905.11 Curing. The length of time, temperature and moisture
conditions for curing of concrete shall be in accordance with
ACI 318, Section 5.11.
1905.12 Cold weather requirements. Concrete to be placed
during freezing or near-freezing weather shall comply with the
requirements of ACI 318, Section 5.12.
1905.13 Hot weather requirements. Concrete to be placed
during hot weather shall comply with the requirements of ACI
318, Section 5.13.
SECTION 1906
FORMWORK, EMBEDDED PIPES AND
CONSTRUCTION JOINTS
1906.1 Formwork. The design, fabrication and erection of
forms shall comply with ACI 318, Section 6.1.
1906.2 Removal of forms, shores and reshores. The removal
of forms and shores, including from slabs and beams (except
where cast on the ground), and the installation of reshores shall
comply with ACI 318, Section 6,2.
1906.3 Conduits and pipes embedded in concrete. Conduits,
pipes and sleeves of any material not harmful to concrete and
within the limitations of ACI 318, Section 6.3, are permitted to
be embedded in concrete with approval of the registered design
professional.
1906.4 Construction joints. Construction joints, including
their location, shall comply with the provisions of ACI 318,
Section 6.4.
SECTION 1907
DETAILS OF REINFORCEMENT
1907.1 Hoolis. Standard hooks on reinforcing bars used in
concrete construction shall comply with ACI 318, Section 7.1.
1907.2 Minimum bend diameters. Minimum reinforcement
bend diameters utilized in concrete construction shall comply
with ACI 318, Section 7.2.
1907.3 Bending. The bending of reinforcement shall comply
with ACI 318, Section 7.3.
1907.4 Surface conditions of reinforcement. The surface
conditions of reinforcement shall comply with the provisions
of ACI 318, Section 7.4.
1907.5 Placing reinforcement. The placement of reinforce-
ment, including tolerances on depth and cover, shall comply
with the provisions of ACI 318, Section 7.5. Reinforcement
shall be accurately placed and adequately supported before
concrete is placed.
1907.6 Spacing limits for reinforcement. The clear distance
between reinforcing bars, bundled bars, tendons and ducts
shall comply with ACI 318, Section 7.6.
1907.7 Concrete protection for reinforcement. The mini-
mum specified concrete cover for reinforcement shall comply
with Sections 1907.7.1 through 1907.7.8.
1907.7.1 Cast-in-place concrete (nonprestressed). Mini-
mum specified concrete cover shall be provided for rein-
forcement in nonprestressed, cast-in-place concrete
construction in accordance with ACI 318, Section 7.7.1.
1907.7.2 Cast-in-place concrete (prestressed). The mini-
mum specified concrete cover for prestressed and
nonprestressed reinforcement, ducts and end fittings in
cast-in-place prestressed concrete shall comply with ACI
318, Section 7.7.2.
1907.7.3 Precast concrete (manufactured under plant
control conditions). The minimum specified concrete
cover for prestressed and nonprestressed reinforcement,
ducts and end fittings in precast concrete manufactured
under plant control conditions shall comply with ACI 318,
Section 7.7.3.
1907.7.4 Bundled bars. The minimum specified concrete
cover for bundled bars shall comply with ACI 318, Section
7.7.4.
1907.7.5 Headed shear stud reinforcement. For headed
shear stud reinforcement, the minimum specified concrete
cover shall comply with ACI 318, Section 7.7.5.
1907.7.6 Corrosive environments. In corrosive environ-
ments or other severe exposure conditions, prestressed and
nonprestressed reinforcement shall be provided with addi-
tional protection in accordance with ACI 318, Section 7.7.6.
1907.7.7 Future extensions. Exposed reinforcement,
inserts and plates intended for bonding with future exten-
sions shall be protected from corrosion.
1907.7.8 Fire protection. When this code requires a thick-
ness of cover for fire protection greater than the minimum
concrete cover in Section 1907.7, such greater thickness
shall be specified.
1907.8 Special reinforcement details for columns. Offset
bent longitudinal bars in columns and load transfer in structural
steel cores of composite compression members shall comply
with the provisions of ACI 318, Section 7.8.
1907.9 Connections. Connections between concrete framing
members shall comply with the provisions of ACI 318, Section
7.9.
238
2010 CALIFORNIA BUILDING CODE
CONCRETE
1907.10 Lateral reinforcement for compression members.
Lateral reinforcement for concrete compression members shall
comply with the provisions of ACI 318, Section 7.10.
1907.11 Lateral reinforcement for flexural members. Lat-
eral reinforcement for compression reinforcement in concrete
flexural members shall comply with the provisions of ACI 318,
Section 7.11.
1907.12 Shrinkage and temperature reinforcement. Rein-
forcement for shrinkage and temperature stresses in concrete
members shall comply with the provisions of ACI 318, Section
7.12.
1907.13 Requirements for structural integrity. The detail-
ing of reinforcement and connections between concrete mem-
bers shall comply with the provisions of ACI 318, Section 7.13,
to improve structural integrity.
SECTION 1908
MODIFICATIONS TO ACI 318
1908.1 General. The text of ACI 3 1 8 shall be modified as indi-
cated in Sections 1908.1.1 through 1908.1.10.
1908.1.1 ACI 318, Section 2.2. Modify existing definitions
and add the following definitions to ACI 318, Section 2.2.
DESIGN DISPLACEMENT. Total lateral displacement
expected for the design-basis earthquake, as specified by
Section 12.8,6 ofASCE 7.
DETAILED PLAIN CONCRETE STRUCTURAL WALL
A wall complying with the requirements of Chapter 22,
including 22,6 J,
ORDINARY PRECAST STRUCTURAL WALL, A precast
wall complying with the requirements of Chapters 1 through
18.
ORDINARY REINFORCED CONCRETE STRUC-
TURAL WALL. A cast-in-place wall complying with the
requirements of Chapters 1 through 18.
ORDINARY STRUCTURAL PLAIN CONCRETE
WALL. A wall complying with the requirements of Chapter
22, excluding 22.6.7.
SPECIAL STRUCTURAL WALL. A cast-in place or
precast wall complying with the requirements of 21.1.3
through 21.1.7,21.9 and 2 1 . 1 0, as appUcable, in addition to
the requirements for ordinary reinforced concrete structural
walls or ordinary precast structural walls, as applicable.
Where ASCE 7 refers to a ''special reinforced concrete
structural wall/* it shall be deemed to mean a ''special
structural wall."
WALL PIER, A wall segment with a horizontal length-
to-thickness ratio of at least 2.5, but not exceeding 6, whose
clear height is at least two times its horizontal length.
1908.1.2 ACI 318, Section 21.1.1. Modify ACI 318 Sec-
tions 21.1.1.3 and 21.1.1.7 to read as follows:
21.1.1.3 - Structures assigned to Seismic Design Cate-
gory A shall satisfy requirements of Chapters 1 to 19 and
22; Chapter 21 does not apply. Structures assigned to
Seismic Design Category B, C, D, E or F also shall satisfy
21.1.1.4 through 21.1.1.8, as applicable. Except for
structural elements of plain concrete complying with
Section 1908.1.8 of the California Building Code, struc-
tural elements of plain concrete are prohibited in struc-
tures assigned to Seismic Design Category C, D,EorF.
21.1.1.7 - Structural systems designated as part of the
seismic-force-resisting system shall be restricted to
those permitted by ASCE 7. Except for Seismic Design
Category A, for which Chapter 2 1 does not apply, the fol-
lowing provisions shall be satisfied for each structural
system designated as part of the seismic-force-resisting
system, regardless of the Seismic Design Category:
(a) Ordinary moment frames shall satisfy 21.2.
(b) Ordinary reinforced concrete structural walls
and ordinary precast structural walls need not
satisfy any provisions in Chapter 21.
(c) Intermediate moment frames shall satisfy 21.3.
(d) Intermediate precast structural walls shall satisfy
21.4.
(e) Special moment frames shall satisfy 21.5
through 21.8.
(f) Special structural walls shall satisfy 21.9.
(g) Special structural walls constructed using pre-
cast concrete shall satisfy 21.10.
(h) [BSC] In Seismic Design Category D, E or F,
concrete tilt-up wall panels which exceed the
limitations of intermediate precast structural
wall systems shall satisfy 21.9 in addition to
21.4.2. and 21.4.3,
All special moment frames and special structural
walls shall also satisfy 21.1.3 through 21.1.7.
1908.1.3 ACI 318, Section 21.4. Modify ACI 318, Section
21.4, by renumbering Section 21.4.3 to become 21.4.4 and
adding new Sections 21.4.3, 21.4.5, 21,4.6 and 21.4.7 to
read as follows:
21.4.3 - Connections that are designed to yield shall be
capable of maintaining 80 percent of their design
strength at the deformation induced by the design dis-
placement or shall use Type 2 mechanical splices.
2 1 .4.4 - Elements of the connection that are not designed
to yield shall develop at least 1.5 Sy.
21.4.5- [BSCl Wall piers in Seismic Design Category D,
E or F shall comply with Section 1908.1.4 of this code.
21.4.6 - Wall piers not designed as part of a moment
frame in SDC C shall have transverse reinforcement
designed to resist the shear forces determined from
21.3.3. Spacing of transverse reinforcement shall not
exceed 8 inches (203 mm). Transverse reinforcement
shall be extended beyond the pier clear height for at least
12 inches (305 mm).
Exceptions:
1 . Wall piers that satisfy 21.13.
2010 CALIFORNIA BUILDING CODE
239
CONCRETE
2. Wall piers along a wall line within a story
where other shear wall segments provide lat-
eral support to the wall piers and such seg-
ments have a total stiffness of at least six times
the sum of the stiffnesses of all the wall piers.
2L4.7~ Wall segments with a horizontal length-to-thick-
ness ratio less than 2.5 shall be designed as columns.
1908.1.4 ACI 318, Section 21.9. Modify ACI 318, Section
2L9, by adding new Section 21.9.10 to read as follows:
21.9,10- Wall piers and wall segments.
21.9.10.1 - Wall piers not designed as a part of a special
moment frame shall have transverse reinforcement
designed to satisfy the requirements in 21.9.10.2.
Exceptions:
1. Wall piers that satisfy 21.13.
2. Wall piers along a wall line within a story
where other shear wall segments provide lat-
eral support to the wall piers and such seg-
ments have a total stiffness of at least six times
the sum of the stiffnesses of all the wall piers.
21,9.10.2- Transverse reinforcement with seismic hooks
at both ends shall be designed to resist the shear forces
determined from 21.6.5.1. Spacing of transverse rein-
forcement shall not exceed 6 inches (152 mm). Trans-
verse reinforcement shall be extended beyond the pier
clear height for at least 12 inches (305 mm),
21.9.10.3 - Wall segments with a horizontal length-to-
thickness ratio less than 2.5 shall be designed as col-
umns.
1908.1.5 ACI 318, Section 21.10. Modify ACI 318, Sec-
tion 21.10.2, to read as follows:
21 . 10.2 - Special structural walls constructed using pre-
cast concrete shall satisfy all the requirements of 21 .9 for
cast-in-place special structural walls in addition to Sec-
tions 21.4.2 through 21.4.4.
1908.1.6 ACI 318, Section 21.12.1.1. Modify ACI 318,
Section 21.12.1.1, to read as follows:
21.12.1.1 - Foundations resisting earthquake-induced
forces or transferring earthquake-induced forces between
a structure and ground shall comply with the requirements
of Section 21.12 and other applicable provisions of ACI
318 unless modified by Chapter 18 of the California
Building Code.
1908.1.7 ACI 318, Section 22.6. Modify ACI 318, Section
22.6, by adding new Section 22.6.7 to read as follows:
22.6. 7 - Detailed plain concrete structural walls.
22.6.7.1 - Detailed plain concrete structural walls are
walls conforming to the requirements of ordinary struc-
tural plain concrete walls and 22.6. 7.2.
22.6.7.2 - Reinforcement shall be provided as follows:
(a) Vertical reinforcement of at least 0.20 square
inch (129 mm^) in cross-sectional area shall be
provided continuously from support to support
at each corner, at each side of each opening and
at the ends of walls. The continuous vertical bar
required beside an opening is permitted to sub-
stitute for one of the two No. 5 bars required by
22.6.6.5.
(b) Horizontal reinforcement at least 0.20 square
inch (129 mm^) in cross-sectional area shall be
provided:
1. Continuously at structurally connected roof
and floor levels and at the top of walls;
2. At the bottom of load-bearing walls or in the
top of foundations where doweled to the
wall; and
3. At a maximum spacing of 120 inches (3048
mm).
Reinforcement at the top and bottom of open-
ings, where used in determining the maximum
spacing specified in Item 3 above, shall be con-
tinuous in the wall.
1908.1.8 ACI 318, Section 22.10. Delete ACI 318, Section
22.10, and replace with the following:
22.10 ~ Plain concrete in structures assigned to Seismic
Design Category C, D, E or F.
22.10.1 - Structures assigned to Seismic Design Cate-
gory C, D, E or F shall not have elements of structural
plain concrete, except as follows:
(a) Structural plain concrete basement, foundation
or other walls below the base are permitted in
detached one- and two-family dwellings three
stories or less in height constructed with
stud-bearing walls. In dwellings assigned to
Seismic Design Category D or E, the height of
the wall shall not exceed 8 feet (2438 mm), the
thickness shall not be less than 7^2 inches (190
mm), and the wall shall retain no more than 4 feet
(1219 mm) of unbalanced fill Walls shall have
reinforcement in accordance with 22.6.6.5.
(b) Isolated footings of plain concrete supporting
pedestals or columns are permitted, provided the
projection of the footing beyond the face of the
supported member does not exceed the footing
thickness.
Exception: In detached one- and two-family
dwellings three stories or less in height, the
projection of the footing beyond the face of the
supported member is permitted to exceed the
footing thickness.
(c) Plain concrete footings supporting walls are per-
mitted, provided the footings have at least two
continuous longitudinal reinforcing bars. Bars
shall not be smaller than No. 4 and shall have a
total area of not less than 0.002 times the gross
cross-sectional area of the footing. For footings
that exceed 8 inches (203 mm) in thickness, a min-
imum of one bar shall be provided at the top and
240
2010 CALIFORNIA BUILDING CODE
CONCRETE
bottom of the footing. Continuity of reinforcement
shall be provided at comers and intersections.
Exceptions:
1. In detached one- and two-family dwell-
ings three stories or less in height and
constructed with stud-bearing walls,
plain concrete footings without longitu-
dinal reinforcement supporting walls are
permitted,
2. For foundation systems consisting of a
plain concrete footing and a plain con-
crete stemwall, a minimum of one bar
shall be provided at the top of the
stemwall and at the bottom of the footing.
3. Where a slab on ground is cast
monolithically with the footing, one No. 5
bar is permitted to be located at either the
top of the slab or bottom of the footing,
1908.1.9 ACI 318, Section D.3.3. Modify ACI 318, Sec-
tions D.3.3.4 and D.3.3.5 to read as follows:
D.3.3. 4 - Anchors shall be designed to be governed by
the steel strength of a ductile steel element as determined
in accordance with D.5.1 and D.6.1, unless either
D.3.3.5 or D.3.3.6 is satisfied.
Exceptions:
1. Anchors in concrete designed to support non-
structural components in accordance with
ASCE 7 Section 13.4.2 need not satisfy Section
D,3.3.4.
2. Anchors designed to resist wall out-of-plane
forces with design strengths equal to or greater
than the force determined in accordance with
ASCE 7 Equation 12.11-1 or 12.14-10 neednot
satisfy Section D,3.3.4.
D.3.3.5 - Instead of D.3.3.4, the attachment that the
anchor is connecting to the structure shall be designed so
that the attachment will undergo ductile yielding at a
force level corresponding to anchor forces no greater
than the design strength of anchors specified in D.3.3. 3.
Exceptions:
1. Anchors in concrete designed to support
nonstructural components in accordance with
ASCE 7 Section 13,4,2 need not satisfy Section
D.3,3,5.
2. Anchors designed to resist wall out-of-plane
forces with design strengths equal to or greater
than the force determined in accordance with
ASCE 7 Equation 12.1 1-1 or 12.14-10 neednot
satisfy Section D.3,3,5.
1908.1.9.1 ACI 318, Section D3.3. [BSC] Modify ACI
318, Section D3.3.1 and add Section D.3.3. 7 to read as
follows:
D3,3, 1 - The provisions of Appendix D do not apply to
the design of anchors in plastic hinge zones of con-
crete structures under earthquake forces or anchors
defined in Section D3.3.7.
D3,3.7-For anchors of wood sill plates with nominal
diameters not exceeding V^ in. (15.9 mm) with
embedment of 7 in. (1 78 mm) or greater, located a
minimum of 2. 5d from edge of concrete and 15dfrom
end of concrete, design strength in shear parallel to
edge of concrete shall be permitted to be determined
in accordance with Section 2305.
1908.1.10 ACI 318, Section D.4.2.2. Delete ACI 318, Sec-
tion D.A.l.l, and replace with the following:
D.4,2.2 - The concrete breakout strength requirements for
anchors in tension shall be considered satisfied by the
design procedure of D, 5.2 provided Equation D-8 is not
used for anchor embedments exceeding 25 inches. The con-
crete breakout strength requirements for anchors in shear
with diameters not exceeding 2 inches shall be considered
satisfied by the design procedure of D, 6.2. For anchors in
shear with diameters exceeding 2 inches, shear anchor rein-
forcement shall be provided in accordance with the proce-
dures of D. 6.2. 9.
SECTION 1909
STRUCTURAL PLAIN CONCRETE
1909.1 Scope. The design and construction of structural plain
concrete, both cast-in-place and precast, shall comply with the
minimum requirements of Section 1909 and ACI 318, Chapter
22, as modified in Section 1908.
1909.1.1 Special structures. For special structures, such as
arches, underground utility structures, gravity walls and
shielding walls, the provisions of this section shall govern
where applicable.
1909.2 Limitations. The use of structural plain concrete shall
be limited to:
1. Members that are continuously supported by soil, such
as walls and footings, or by other structural members
capable of providing continuous vertical support.
2. Members for which arch action provides compression
under all conditions of loading.
3. Walls and pedestals.
The use of structural plain concrete columns and structural
plain concrete footings on piles is not permitted. See Section
1908. 1.8 for additional hmitations on the use of structural plain
concrete.
2010 CALIFORNIA BUILDING CODE
241
CONCRETE
1909.3 Joints. Contraction or isolation joints shall be provided
to divide structural plain concrete members into flexurally dis-
continuous elements in accordance with ACI 318, Section 22.3.
1909.4 Design. Structural plain concrete walls, footings and
pedestals shall be designed for adequate strength in accordance
with ACI 318, Sections 22.4 through 22.8.
Exception: For Group R-3 occupancies and buildings of
other occupancies less than two stories above grade plane
of light-frame construction, the required edge thickness of
ACI 318 is permitted to be reduced to 6 inches (152 mm),
provided that the footing does not extend more than 4 inches
(102 mm) on either side of the supported wall.
1909.5 Precast members. The design, fabrication, transporta-
tion and erection of precast, structural plain concrete elements
shall be in accordance with ACI 318, Section 22.9.
1909.6 Walls. In addition to the requirements of this section,
structural plain concrete walls shall comply with the applicable
requirements of ACI 318, Chapter 22.
1909.6.1 Basement walls. The thickness of exterior base-
ment walls and foundation walls shall be not less than 7V2
inches (191 mm).
1909.6.2 Other walls. Except as provided for in Section
1909.6.1, the thickness of bearing walls shall be not less
than V24 the unsupported height or length, whichever is
shorter, but not less than 5V2 inches (140 mm).
1909.6.3 Openings in walls. Not less than one No. 5 bar
shall be provided around window, door and similar sized
openings. The bar shall be anchored to develop^ in tension
at the corners of openings.
SECTION 1910
MINIMUM SLAB PROVISIONS
1910.1 General. The thickness of concrete floor slabs supported
directly on the ground shall not be less than 3 V2 inches (89 mm).
A 6-mil (0.006 inch; 0.15 mm) polyethylene vapor retarder with
joints lapped not less than 6 inches (152 mm) shall be placed
between the base course or subgrade and the concrete floor slab,
or other approved equivalent methods or materials shall be used
to retard vapor transmission through the floor slab.
Exception: A vapor retarder is not required:
1 . For detached structures accessory to occupancies in
Group R-3, such as garages, utility buildings or other
unheated facilities.
2. For unheated storage rooms having an area of less
than 70 square feet (6.5 m^) and carports attached to
occupancies in Group R-3.
3. For buildings of other occupancies where migration
of moisture through the slab from below will not be
detrimental to the intended occupancy of the building.
4. For driveways, walks, patios and other flatwork
which will not be enclosed at a later date.
5. Where approved based on local site conditions.
SECTION 1911
ANCHORAGE TO CONCRETE-
ALLOWABLE STRESS DESIGN
1911.1 Scope. The provisions of this section shall govern the
allowable stress design of headed bolts and headed stud
anchors cast in normal- weight concrete for purposes of trans-
mitting structural loads from one connected element to the
other. These provisions do not apply to anchors installed in
hardened concrete or where load combinations include earth-
quake loads or effects. The bearing area of headed anchors
shall be not less than one and one-half times the shank area.
Where strength design is used, or where load combinations
include earthquake loads or effects, the design strength of
anchors shall be determined in accordance with Section 1912.
Bolts shall conform to ASTM A 307 or an approved equiva-
lent.
1911. LI Power actuated fasteners. [OSHPD 2] Power
actuated fasteners qualified in accordance with ICC-ESAC
70 shall be deemed to satisfy the requirements of this sec-
tion.
Power actuated fasteners shall be permitted for seismic
shear when they are specifically listed in ICC-ES Report
(ICC-ESR)for such service and for interior nonshear wall
partitions. Power actuated fastener shall not be used to
anchor exterior cladding or curtain wall systems,
1911.2 Allowable service load. The allowable service load for
headed anchors in shear or tension shall be as indicated in Table
191 1.2. Where anchors are subject to combined shear and ten-
sion, the following relationship shall be satisfied:
where:
(Equation 19-1)
P^ = Applied tension service load, pounds (N).
P, = Allowable tension service load from Table 1911.2,
pounds (N).
1/ = Applied shear service load, pounds (N).
V^ = Allowable shear service load from Table 1911.2,
pounds (N).
1911.3 Required edge distance and spacing. The allowable
service loads in tension and shear specified in Table 191 1.2 are
for the edge distance and spacing specified. The edge distance
and spacing are permitted to be reduced to 50 percent of the val-
ues specified with an equal reduction in allowable service load.
Where edge distance and spacing are reduced less than 50 per-
cent, the allowable service load shall be determined by linear
interpolation.
1911.4 Increase in allowable load. Increase of the values in
Table 191 1 .2 by one- third is permitted where the provisions of
Section 1605.3.2 permit an increase in allowable stress for
wind loading.
1911.5 Increase for special inspection. Where special inspec-
tion is provided for the installation of anchors, a 100-percent
increase in the allowable tension values of Table 191 1 .2 is per-
mitted. No increase in shear value is permitted.
242
2010 CALIFORNIA BUILDING CODE
CONCRETE
TABLE 1911.2
ALLOWABLE SERVICE LOAD ON EMBEDDED BOLTS (pounds)
BOLT
DIAMETER
(inches)
MINIMUM
EMBEDMENT
(inches)
EDGE
DISTANCE
(Inches)
SPACING
(inches)
MINIMUM CONCRETE STRENGTH (psi)
f'c =
2,500
f', = 3,000
f'c =
4,000
Tension
Shear
Tension
Shear
Tension
Shear
V4
2%
IV,
3
200
500
200
500
200
500
\
3
2%
4V,
500
1,100
500
1,100
500
1,100
%
4
4
3
5
6
6
950
1,450
1,250
1,600
950
1,500
1,250
1,650
950
1,550
1,250
1,750
\
4'/,
4'/,
3%
6V4
7V,
1,500
2,125
2,750
2,950
1,500
2,200
2,750
3,000
1,500
2,400
2,750
3,050
'U
5
5
1%
9
9
2,250
2,825
3,250
4,275
2,250
2,950
3,560
4,300
2,250
3,200
3,560
4,400
\
6
5%
IOV2
2,550
3,700
2,550
4,050
2,550
4,050
1
7
6
12
3,050
4,125
3,250
4,500
3,650
5,300
iVs
8
6V4
I3V2
3,400
4,750
3,400
4,750
3,400
4,750
1V4
9
7%
15
4,000
5,800
4,000
5,800
4,000
5,800
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound = 4.45 N.
SECTION 1912
ANCHORAGE TO CONCRETE-
STRENGTH DESIGN
1912.1 Scope. The provisions of this section shall govern the
strength design of anchors installed in concrete for purposes
of transmitting structural loads from one connected element
to the other. Headed bolts, headed studs and hooked (J- or L-)
bolts cast in concrete and expansion anchors and undercut
anchors installed in hardened concrete shall be designed in
accordance with Appendix D of ACI 3 1 8 as modified by Sec-
tions 1908.1.9 and 1908.1.10, provided they are within the
scope of Appendix D.
The strength design of anchors that are not within the scope
of Appendix D of ACI 318, and as amended in Sections
1908.1.9 and 1908.1.10, shall be in accordance with an
approved procedure.
1912.1.1 Mechanical anchors and specialty inserts,
[OSHPP 2] Mechanical anchors qualified in accordance
with ICC-ES AC 193 shall be deemed to satisfy the require-
ments of this section.
Specialty inserts, including cast-in-place specialty
inserts, tested in accordance with ICC-ES AC 193 shall be
deemed to satisfy the requirements of this section.
Exception: Anchors prequalified for seismic applica-
tions need not be governed by the steel strength of a duc-
tile steel element.
1912.1.2 Post-installed adhesive anchors, [OSHPD 2]
Adhesive anchors qualified in accordance with ICC-ES AC
308 shall be deemed to satisfy the requirements of this sec-
tion.
Exceptions:
1. Adhesive anchors shall not be permitted in over-
head applications or application with sustained
(continuous) tension load that can lead to creep.
2. Anchors prequalified for seismic applications
need not be governed by the steel strength of a duc-
tile steel element.
1912.2 Tests for post-installed anchors in concrete. [OSHPD
2] When post-installed anchors are used in lieu of cast-in place
bolts, the installation verification test loads, frequency, and
acceptance criteria shall be in accordance with this section.
1912.2.1 General. Test loads or torques and acceptance cri-
teria shall be shown on the construction documents.
If any anchor fails testing, all anchors of the same type
shall be tested, which are installed by the same trade, not
previously tested until twenty (20) consecutive anchors
pass, then resume the initial test frequency.
1912.2.2 Test loads. Required test loads shall be determined
by one of the following methods:
1. Twice the maximum allowable tension load or one
and a quarter (V/4) times the maximum design
strength of anchors as provided in International Code
Council - Evaluation Service Report (ICC-ESR) or
determined in accordance with Appendix D of ACI
318.
Tension test load need not exceed 80 percent of the
nominal yield strength of the anchor element (=0.8
^seJya/'
<
<
2010 CALIFORNIA BUILDING CODE
243
CONCRETE
2. The manufacturer' s recommended installation
torque as approved in an ICC-ESR.
1912.2.3 Test frequency. When post-installed anchors are
used for sill plate bolting applications, 10 percent of the
anchors shall be tested.
I I When post-installed anchors are used for other structural
> applications, all such anchors shall be tested,
I I When post-installed anchors are used for nonstructural
applications such as equipment anchorage, 50 percent or
alternate bolts in a group, including at least one-half the
> anchors in each group, shall be tested.
>| I The testing of the post-installed anchors shall be done in
the presence of the special inspector and a report of the test
> results shall be submitted to the enforcement agency.
Exceptions:
1. Undercut anchors that allow visual confirmation
of full set shall not require testing.
2. Where the factored design tension on anchors is
less than 100 lb and those anchors are clearly
noted on the approved construction documents,
only 10 percent of those anchors shall be tested,
3. Where adhesive anchor systems are used to install
reinforcing dowel bars in hardened concrete, only
25 percent of the dowels shall be tested if all of the
following conditions are met:
a. The dowels are used exclusively to transmit
shear forces across joints between existing
and new concrete,
b. The number of dowels in any one member
equals or exceeds twelve (12).
c. The dowels are uniformly distributed across
seismic force resisting members (such as
shear walls, collectors and diaphragms).
Anchors to be tested shall be selected at ran-
dom by the special inspector/inspector of
record (lOR).
4. Testing of shear dowels across cold joints in slabs
on grade, where the slab is not part of the lateral
force-resisting system shall not be required.
5. Testing is not required for power actuated fasten-
ers used to attach tracks of interior nonshear wall
partitions for shear only, where there are at least
three fasteners per segment of track.
1912.2.4 Test acceptance criteria. Acceptance criteria for
post-installed anchors shall be based on ICC-ESR or manu-
facturers written instruction, acceptable to the enforcement
agency. Field test shall satisfy following minimum require-
ments.
1. Hydraulic ram method:
Anchors tested with a hydraulic jack or spring loaded
devices shall maintain the test load for a minimum of
15 seconds and shall exhibit no discernable move-
ment during the tension test, e.g., as evidenced by
loosening of the washer under the nut.
For adhesive anchors, where other than bond is being
tested, the testing device shall not restrict the concrete
shear cone type failure mechanism from occurring.
2. Torque wrench method:
Anchors tested with a calibrated torque wrench must
attain the specified torque within V2 turn of the nut.
Exceptions:
a. Wedge or sleeve type:
One-quarter fVJ turn of the nut for a % in.
sleeve anchor only.
b. Threaded type:
One-quarter fV^j turn of the screw after ini-
tial seating of the screw head.
1912,2,5 Testing procedure. Test procedure shall be as
required by the ICC-ESR, Manufacturer's recommendation
for testing may be approved by the enforcement agency,
when ICC-ESR does not provide a testing procedure.
SECTION 1913
SHOTCRETE
1913.1 General. Shotcrete is mortar or concrete that is pneu-
matically projected at high velocity onto a surface. Except as
specified in this section, shotcrete shall conform to the require-
ments of this chapter for plain or reinforced concrete.
1913.2 Proportions and materials. Shotcrete proportions
shall be selected that allow suitable placement procedures
using the delivery equipment selected and shall result in fin-
ished in-place hardened shotcrete meeting the strength require-
ments of this code.
1913.3 Aggregate. Coarse aggregate, if used, shall not exceed
V4 inch (19.1 mm).
1913.4 Reinforcement. Reinforcement used in shotcrete con-
struction shall comply with the provisions of Sections 1913.4. 1
through 1913.4.4.
1913.4.1 Size. The maximum size of reinforcement shall be
No. 5 bars unless it is demonstrated by preconstruction tests
that adequate encasement of larger bars will be achieved.
1913.4.2 Clearance. When No. 5 or smaller bars are used,
there shall be a minimum clearance between parallel rein-
forcement bars of 2'/2 inches (64 mm). When bars larger
than No. 5 are permitted, there shall be a minimum clear-
ance between parallel bars equal to six diameters of the bars
used. When two curtains of steel are provided, the curtain
nearer the nozzle shall have a minimum spacing equal to 12
bar diameters and the remaining curtain shall have a mini-
mum spacing of six bar diameters.
Exception: Subject to the approval of the building offi-
cial, required clearances shall be reduced where it is
demonstrated by preconstruction tests that adequate
encasement of the bars used in the design will be
achieved.
1913.4.3 Splices. Lap splices of reinforcing bars shall uti-
lize the noncontact lap splice method with a minimum clear-
ance of 2 inches (5 1 mm) between bars. The use of contact
244
2010 CALIFORNIA BUILDING CODE
CONCRETE
lap splices necessary for support of the reinforcing is per-
mitted when approved by the building official, based on sat-
isfactory preconstruction tests that show that adequate
encasement of the bars will be achieved, and provided that
the splice is oriented so that a plane through the center of the
spliced bars is perpendicular to the surface of the shotcrete.
1913.4.4 Spirally tied columns. Shotcrete shall not be
applied to spirally tied columns.
1913.5 Preconstruction tests. When required by the building
official, a test panel shall be shot, cured, cored or sawn, exam-
ined and tested prior to commencement of the project. The
sample panel shall be representative of the project and simulate
job conditions as closely as possible. The panel thickness and
reinforcing shall reproduce the thickest and most congested
area specified in the structural design. It shall be shot at the
same angle, using the same nozzleman and with the same con-
crete mix design that will be used on the project. The equip-
ment used in preconstruction testing shall be the same
equipment used in the work requiring such testing, unless sub-
stitute equipment is approved by the building official.
1913.6 Rebound. Any rebound or accumulated loose aggre-
gate shall be removed from the surfaces to be covered prior to
placing the initial or any succeeding layers of shotcrete.
Rebound shall not be used as aggregate.
1913.7 Joints. Except where permitted herein, unfinished
work shall not be allowed to stand for more than 30 minutes
unless edges are sloped to a thin edge. For structural elements
that will be under compression and for construction joints
shown on the approved construction documents, square joints
are permitted. Before placing additional material adjacent to
previously applied work, sloping and square edges shall be
cleaned and wetted.
1913.8 Damage. In-place shotcrete that exhibits sags, sloughs,
segregation, honeycombing, sand pockets or other obvious
defects shall be removed and replaced. Shotcrete above sags
and sloughs shall be removed and replaced while still plastic.
1913.9 Curing. During the curing periods specified herein,
shotcrete shall be maintained above 40°F (4°C) and in moist
condition.
1913.9.1 Initial curing. Shotcrete shall be kept continu-
ously moist for 24 hours after shotcreting is complete or
shall be sealed with an approved curing compound.
1913.9.2 Final curing. Final curing shall continue for seven
days after shotcreting, or for three days if high-
early-strength cement is used, or until the specified strength
is obtained. Final curing shall consist of the initial curing
process or the shotcrete shall be covered with an approved
moisture-retaining cover.
1913.9.3 Natural curing. Natural curing shall not be used
in lieu of that specified in this section unless the relative
humidity remains at or above 85 percent, and is authorized
by the registered design professional and approved by the
building official
1913.10 Strength tests. Strength tests for shotcrete shall be
made by an approved agency on specimens that are representa-
tive of the work and which have been water soaked for at least
24 hours prior to testing. When the maximum-size aggregate is
larger than % inch (9.5 mm), specimens shall consist of not less
than three 3-inch-diameter (76 mm) cores or 3-inch (76 mm)
cubes. When the maximum-size aggregate is Vg inch (9.5 mm)
or smaller, specimens shall consist of not less than
2-inch-diameter (51 mm) cores or 2-inch (51 mm) cubes.
1913.10.1 Sampling. Specimens shall be taken from the
in-place work or from test panels, and shall be taken at least
once each shift, but not less than one for each 50 cubic yards
(38.2 m^) of shotcrete.
1913.10.2 Panel criteria. When the maximum-size aggre-
gate is larger than % inch (9.5 mm), the test panels shall
have minimum dimensions of 18 inches by 18 inches (457
mm by 457 nmi). When the maximum size aggregate is ^/g
inch (9.5 mm) or smaller, the test panels shall have mini-
mum dimensions of 12 inches by 12 inches (305 mm by 305
mm). Panels shall be shot in the same position as the work,
during the course of the work and by the nozzlemen doing
the work. The conditions under which the panels are cured
shall be the same as the work.
1913.10.3 Acceptance criteria. The average compressive
strength of three cores from the in-place work or a single test
panel shall equal or exceed 0.85/'^ with no single core less
than 0.75 / \, The average compressive strength of three
cubes taken from the in-place work or a single test panel
shall equal or exceed /'^ with no individual cube less than
0.88/V To check accuracy, locations represented by erratic
core or cube strengths shall be retested.
SECTION 1914
REINFORCED GYPSUM CONCRETE
1914.1 General. Reinforced gypsum concrete shall comply
with the requirements of ASTM C 317 and ASTM C 956.
1914.2 Minimum thickness. The minimum thickness of rein-
forced gypsum concrete shall be 2 inches (5 1 nmi) except the
minimum required thickness shall be reduced to 1 V2 inches (38
mm), provided the following conditions are satisfied:
1. The overall thickness, including the formboard, is not
less than 2 inches (51 mm).
2. The clear span of the gypsum concrete between supports
does not exceed 33 inches (838 mm).
3. Diaphragm action is not required.
4. The design live load does not exceed 40 pounds per
square foot (psf) (1915 Pa).
SECTION 1915
CONCRETE-FILLED PIPE COLUMNS
1915.1 General. Concrete-filled pipe columns shall be manu-
factured from standard, extra-strong or double-extra-strong
steel pipe or tubing that is filled with concrete so placed and
manipulated as to secure maximum density and to ensure com-
plete filling of the pipe without voids.
2010 CALIFORNIA BUILDING CODE
245
CONCRETE
1915.2 Design. The safe supporting capacity of concrete-filled
pipe columns shall be computed in accordance with the
approved rules or as determined by a test.
1915.3 Connections. Caps, base plates and connections shall
be of approved types and shall be positively attached to the
shell and anchored to the concrete core. Welding of brackets
without mechanical anchorage shall be prohibited. Where the
pipe is slotted to accommodate webs of brackets or other con-
nections, the integrity of the shell shall be restored by welding
to ensure hooping action of the composite section.
1915.4 Reinforcement. To increase the safe load-supporting
capacity of concrete-filled pipe columns, the steel reinforce-
ment shall be in the form of rods, structural shapes or pipe
embedded in the concrete core with sufficient clearance to
ensure the composite action of the section, but not nearer than 1
inch (25 mm) to the exterior steel shell. Structural shapes used
as reinforcement shall be milled to ensure bearing on cap and
base plates.
1915.5 Fire-resistance-rating protection. Pipe columns shall
be of such size or so protected as to develop the required
fire-resistance ratings specified in Table 601. Where an outer
steel shell is used to enclose the fire protective covering, the
shell shall not be included in the calculations for strength of the
column section. The minimum diameter of pipe columns shall
be 4 inches (102 mm) except that in structures of Type V con-
struction not exceeding three stories above grade plane or 40
feet (12 192 mm) in building height, pipe columns used in
basements and as secondary steel members shall have a mini-
mum diameter of 3 inches (76 mm).
1915.6 Approvals. Details of column connections and splices
shall be shop fabricated by approved methods and shall be
approved only after tests in accordance with the approved
rules. Shop-fabricated concrete-filled pipe columns shall be
inspected by the building official or by an approved representa-
tive of the manufacturer at the plant.
SECTION 1916
ADDITIONAL REQUIREMENTS [DSA-SS/CC]
1916,1 Tests and materials. Where required, special inspec-
tions and tests shall be in accordance with Chapter 1 7 A and
this section.
1916,1,1 Glass fiber reinforced concrete. Glass fiber rein-
forced concrete (GFRC) and the materials used in such con-
crete shall be in accordance with the PCIMNL128 standard.
I I 1916,1,2 Fly ash. Replace ACI 3 18 Section 3.2.2 as follows :
Fly ash or other pozzolan can be used as a partial substi-
tute for ASTM C 150 Portland cement , as follows:
1. Fly ash or other pozzolan shall conform to ASTM
C 618 for Class N or Class F materials (Class C is
not permitted), and
2. More than 15 percent by weight of fly ash or other
pozzolans shall be permitted to be substituted for
ASTM C 150 Portland cement if the mix design is
proportioned per Section 1905.3. See Section
1904 for durability requirements.
3. More than 40 percent by weight of ground- granu-
lated blast-furnace slag conforming to ASTM C
989 shall be permitted to be substituted for ASTM
C 150 Portland cement if the mix design is propor-
tioned per Section 1905.3. See Section 1904 for ' '
durability requirements.
1916.1.3 ACI 318, Section 3.3,2, Modify ACI 318 Section
3.3.2 by adding the following:
Aggregate size limitations waiver shall be approved by
the enforcement agency.
Evidence that the aggregate used is not reactive in the
presence of cement alkalis may be required by the
enforcement agency. If new aggregate sources are to be
used or if past experience indicates problems with exist-
ing aggregate sources, test the aggregate for potential
reactivity according to ASTM C 289 to determine poten-
tial reactivity in the presence of cement.
If the results of the test are other than innocuous,
selected concrete proportions using the aggregate (see
Section 1 905.2) shall be tested in accordance with ASTM I I
C 1567. If the results of this test indicate an expansion
greater than 0.10 percent at 1 6-day s age, provide mitiga-
tion with one of the cementitious material systems noted
below such that an expansion of less than 0. 10 percent at
1 6-day s age is obtained:
1. Low-alkali portland cement containing not more
than 0.6 percent total alkali when calculated as
sodium oxide, as determined by the method given
inASTMClM.
2. Blended hydraulic cement, Type IS or IP, con-
forming to ASTM C 595, except that Type IS
cement shall not contain less than 40 percent slag
constituent.
3. Replacement of not less than 15 percent by weight
of the Portland cement used by a mineral admix-
ture conforming to ASTM C 618 for Class N or F
materials (Class C is not permitted).
4. Replacement of not less than 40 percent by weight
of the Portland cement used by a ground granu-
lated blast-furnace slag conforming to ASTM C
989.
1916.1.4 Discontinuous steel fibers - Modify ACI 318 Sec-
tion 3.5.1 by adding the following:
Discontinuous steel fibers shall not be permitted.
1916.1.5 Cementitious material. The concrete supplier
shall furnish to the enforcement agency certification that the
cement proposed for use on the project has been manufac-
tured and tested in compliance with the requirements of
ASTM C 150 for Portland cement and ASTM C 595 or ASTM
C 1157 for blended hydraulic cement, whichever is applica-
ble. When a mineral admixture or ground granulated
blast-furnace slag is proposed for use, the concrete supplier
shall furnish to the enforcement agency certification that
they have been manufactured and tested in compliance with
ASTM C 618 or ASTM C 989, whichever is applicable. The
concrete producer shall provide copies of the cementitious
246
2010 CALIFORNIA BUILDING CODE
CONCRETE
material supplier's certificate of compliance that represents
the materials used by date of shipment for concrete.
Cementitious materials without certification of compliance
shall not be used.
1916.1.6 Tests of reinforcing bars. Where samples are
taken from bundles as delivered from the mill, with the bun-
dles identified as to heat number and provided the mill anal-
yses accompany the report, one tensile test and one bend
test shall be made from a specimen from each 10 tons (9080
kg) or fraction thereof of each size of reinforcing steel.
Where positive identification of the heat number cannot
be made or where random samples are to be taken, one
series of tests shall be made from each 2^/ 2 tons (2270 kg) or
fraction thereof of each size of reinforcing steel
Tests of reinforcing bars may be waived by the structural
engineer with the approval of the Building Official for
one-story buildings provided certified mill test reports are
provided for each shipment of such reinforcement.
1916.1.7 Tests for prestressing steel and anchorage. All
wires or bars of each size from each mill heat and all strands
from each manufactured reel to be shipped to the site shall
be assigned an individual lot number and shall be tagged in
such a manner that each lot can be accurately identified at
the job site. Each lot of tendon and anchorage assemblies
and bar couplers to be installed shall be likewise identified.
The following samples of materials and tendons selected
by the engineer or the designated testing laboratory from
the prestressing steel at the plant or job site shall be fur-
nished by the contractor and tested by an approved inde-
pendent testing agency:
L For wire, strand or bars, 7 -foot-long (2134 mm) sam-
ples shall be taken of the coil of wire or strand reel or
rods. A minimum of one random sample per 5,000
pounds (2270 kg) of each heat or lot used on the job
shall be selected.
2. For prefabricated prestressing tendons other than
bars, one completely fabricated tendon 10 feet (3048
mm) in length between grips with anchorage assem-
bly at one end shall be furnished for each size and type
of tendon and anchorage assembly.
Variations of the bearing plate size need not be
considered.
The anchorages of unbonded tendons shall
develop at least 95 percent of the minimum specified
ultimate strength of the prestressing steel. The total
elongation of the tendon under ultimate load shall not
be less than 2 percent measured in a minimum gage
length of 10 feet (3048 mm).
Anchorages of bonded tendons shall develop at
least 90 percent of the minimum specified strength of
the prestressing steel tested in an unbonded state. All
couplings shall develop at least 95 percent of the min-
imum specified strength of the prestressing steel and
shall not reduce the elongation at rupture below the
requirements of the tendon itself
3. If the prestressing tendon is a bar, one 7-foot (2134
mm) length complete with one end anchorage shall be
furnished and, in addition, if couplers are to be used
with the bar, two 4-foot (1219 mm) lengths of bar fab-
ricated to fit and equipped with one coupler shall be
furnished.
4. Mill tests of materials used for end anchorages shall
be furnished. In addition, at least one Brinnell hard-
ness test shall be made of each thickness of bearing
plate.
1916.1.8 Composite construction cores. Cores of the com-
pleted composite concrete construction shall be taken to
demonstrate the shear strength along the contact surfaces.
The cores shall be tested when the cast-in-place concrete is
approximately 28 days old and shall be tested by a shear
loading parallel to the joint between the precast concrete
and the cast-in-place concrete. The minimum unit shear
strength of the contact surface area of the core shall not be
less than 100 psi (689 kPa).
At least one core shall be taken from each building for
each 5,000 square feet (465 m^) of area of composite con-
crete construction and not less than three cores shall be
taken from each project. The architect or structural engi-
neer in responsible charge of the project or his or her repre-
sentative shall designate the location for sampling.
1916.1.9 Tests ofshotcrete. Testing ofshotcrete shall follow
the provisions of Section 191 3 A and the general require-
ments ofACI 318 Section 5.6.
1916.1.10 Gypsum field tests. Field tests shall be made dur-
ing construction to verify gypsum strength. One sample con-
sisting of three specimens shall be made for each 5,000
square feet (465 m^) or fraction thereof of all gypsum
poured, but not less than one sample shall be taken from
each half -day 's pour.
1916.1.11 Tests for post-installed anchors in concrete.
When post-installed anchors are used in lieu of cast-in-
place bolts, the installation verification test loads frequency
and acceptance criteria shall be in accordance with this
section.
1916.1.11.1 General. Test loads or torques and accep-
tance criteria shall be shown on the construction docu-
ments.
If any anchor fails testing, all anchors of the same type
shall be tested, which are installed by the same trade, not
previously tested until twenty (20) consecutive anchors
pass, then resume the initial test frequency.
1916.1.11.2 Test loads. Required test loads shall be
determined by one of the following methods:
1. Twice the maximum allowable tension load or one
and a quarter (V/4) times the maximum design
strength of anchors as provided in International
Code Council - Evaluation Service Report
(ICC-ESR) or determined in accordance with
Appendix D of AC 1 318.
<
<
2010 CALIFORNIA BUILDING CODE
247
CONCRETE
Tension test load need not exceed 80 percent of
the nominal yield strength of the anchor element
(^0.8 A JJ.
2. The manufacturer's recommended installation
torque as approved in an ICC-ESR.
1916.1.11.3 Test frequency. When post-installed
anchors are used for sill plate bolting applications, 10
> percent of the anchors shall be tested.
I I When post-installed anchors are used for other struc-
> tural applications, all such anchors shall be tested,
I I When post-installed anchors are used for
nonstructural applications such as equipment anchor-
age, 50 percent or alternate bolts in a group, including at
> least one-half the anchors in each group, shall be tested,
> I I The testing of the post-installed anchors shall be done
in the presence of the special inspector and a report of
the test results shall be submitted to the enforcement
> agency.
Exceptions:
1. Undercut anchors that allow visual confirma-
tion of full set shall not require testing.
2. Where the factored design tension on anchors
is less than 100 lb and those anchors are clearly
noted on the approved construction documents,
only 10 percent of those anchors shall be tested.
3. Where adhesive anchor systems are used to
install reinforcing dowel bars in hardened con-
crete, only 25 percent of the dowels shall be
tested if all the following conditions are met:
a. The dowels are used exclusively to trans-
mit shear forces across joints between
existing and new concrete.
h The number of dowels in any one member
equals or exceeds 12.
c. The dowels are uniformly distributed
across seismic force resisting members
(such as shear walls, collectors and dia-
phragms).
Anchors to be tested shall be selected at ran-
dom by the special inspector/inspector of
record (lOR).
4. Testing of shear dowels across cold joints in
slabs on grade, where the slab is not part of the
lateral force-resisting system shall not be
required.
5. Testing is not required for power actuated fas-
teners used to attach tracks of interior
nonshear wall partitions for shear only, where
there are at least three fasteners per segment of
track.
1916.1.11.4 Test acceptance criteria. Acceptance crite-
ria for post-installed anchors shall be based on ICC-ESR
or manufacturers written instruction, acceptable to the
1916,2,2 Sample frequency,
5.6.2.1 as follows:
Replace ACI 318 Section
5.6.2.1 Samples for strength tests of each class of con-
crete placed each day shall be taken not less than once a
day, or not less than once for each 50 cubic yards (345
m^) of concrete, or not less than once for each 2,000
square feet (186 m^) of surface area for slabs or walls.
Additional samples for seven-day compressive strength
tests shall be taken for each class of concrete at the
beginning of the concrete work or whenever the mix or
aggregate is changed.
1916,3 Formworky embedded pipes and construction joints,
1916,3,1 Removal of forms f shores and reshores. No por-
tion of the forming and shoring system may be removed less
than 12 hours after placing. When stripping time is less than
the specified curing time, measures shall be taken to provide
adequate curing and thermal protection of the stripped con-
crete.
enforcement agency. Field test shall satisfy following
minimum requirements.
1. Hydraulic ram method:
Anchors tested with a hydraulic jack or spring
loaded devices shall maintain the test load for a
minimum of 15 seconds and shall exhibit no
discernable movement during the tension test, e.g.,
as evidenced by loosening of the washer under the
nut.
For adhesive anchors, where other than bond is
being tested, the testing device shall not restrict the
concrete shear cone type failure mechanism from
occurring.
2. Torque wrench method:
Anchors tested with a calibrated torque wrench
must attain the specified torque within V2 turn of
the nut.
Exceptions:
1. Wedge or sleeve type:
One-quarter (VJ turn of the nut for a %
in. sleeve anchor only.
2. Threaded type:
One-quarter f VJ turn of the screw after
initial seating of the screw head.
1916,1,11,5, Testing procedure. Test procedure shall be
as required by the ICC-ESR. Manufacturer's recommen-
dation for testing may be approved by the enforcement
agency, when ICC-ESR does not provide a testing proce-
dure.
1916,2 Concrete quality, mixing and testing,
1916,2,1 Selection of concrete proportions, A registered
civil engineer with experience in concrete mix design shall
select the relative amounts of ingredients to be used as basic
proportions of the concrete mixes proposed for use under
ACI 318, Section 5.2. I I
II
248
2010 CALIFORNIA BUILDING CODE
CONCRETE
1916,3,2 Conduits and pipes embedded in concrete.
1916.3.2.1 Large openings. Openings larger than 12
inches (305 mm) in any dimension shall be detailed on
the structural plans. Nothing in this section shall be con-
strued to permit work in violation of fire and panic or
other safety standards.
1916.3.2.2 Adequate support. Pipes and conduits shall
be adequately supported and secured against displace-
ment before concrete is placed.
I I 1916,3,3 Construction joints,
1916.3.3.1 Joint details. Typical details and proposed
locations of construction joints.shall be indicated on the
plans.
1916.3.3.2 Surface preparation. The surface of all hori-
zontal construction joints shall be cleaned and rough-
ened by exposing clean aggregate solidly embedded in
mortar matrix.
In the event that the contact surface becomes coated
with earth, sawdust, etc., after being cleaned, the entire
surface so coated shall be recleaned.
II 1916.4 Modifications to ACl 318
1916.4.1 AC1318, Section 14,9, Modify ACI 318 by adding
Section 14.9 as follows:
14.9 — Foundation walls. Horizontal reinforcing of con-
crete foundation walls for wood-frame or light- steel
buildings shall consist of the equivalent of not less than
one No. 5 bar located at the top and bottom of the wall
Where such walls exceed 3 feet (9 14 mm) in height, inter-
mediate horizontal reinforcing shall be provided at spac-
ing not to exceed 2 feet (610 mm) on center Minimum
vertical reinforcing shall consist of No. 3 bars at 24
inches (610 mm) on center.
Where concrete foundation walls or curbs extend
above the floor line and support wood-frame or
light-steel exterior, bearing or shear walls, they shall be
doweled to the foundation wall below with a minimum of
No. 3 bars at 24 inches (610 mm) on center Where the
height of the wall above the floor line exceeds 18 inches
(457 mm), the wall above and below the floor line shall
meet the requirements of ACI 318 Section 14.3.
1916.4.2 ACI 318, Section 18.21, Add Section 18.21.5 to
ACI 318 as follows:
18.21.5 — Prequalification of anchorages and coupler.
Post-tensioned anchorages and couplers for unbonded
tendons shall be prequalifledfor use in prestressed con-
crete. Data shall be submitted by the post-tensioning
materials fabricator from an approved independent test-
ing agency to show compliance with the following
dynamic test requirements:
A dynamic test shall be performed on a representative
specimen and the tendon shall withstand, without fail-
ure, 500,000 cycles from 60 percent to 66 percent of its
minimum specified ultimate strength and 50 cycles from
40 percent to 80 percent of its minimum specified ulti-
mate strength. The period of each cycle involves the
change from the lower stress level to the upper stress
level and back to the lower. The specimen used for the
second dynamic test need not be the same used for the
first dynamic test. Systems utilizing multiple strands,
wires or bars may be tested utilizing a test tendon of
smaller capacity than the full-size tendon. The test ten-
don shall duplicate the behavior of the full-size tendon
and generally shall not have less than 10 percent of the
capacity of the full-size tendon.
The above test data must be on file at the enforcement
agency for post-tensioning systems to be used. General
approval will be based on satisfactory performance.
Tests shall be required for pre stressing steel and anchor-
ages.
The average bearing stress, P/Af,, on the concrete cre-
ated by the anchorage plates shall not exceed the follow-
ing:
At service load
U = 0.6 f ^4 A',/ A,
but not greater thanf^
At transfer load
U =0.8f:,4A',/A,-0.2
but not greater than 1.25 f^^ where:
fp = Permissible compressive concrete stress.
fc = Compressive strength of concrete.
f^. = Compressive strength of concrete at time of
initial prestress.
A\ = Maximum area of the portion of the concrete
anchorage surface that is geometrically simi-
lar to and concentric with the area of the an-
chorage.
A^ - Bearing area of the anchorage.
P = Prestress force in tendon.
1916.4,3 ACI 318, Section 18, Add Section 18.23 to ACI
318 as follows:
18.23 - Post-tensioned flat slab. \\
18.23.1 — Span-depth ratio. The ratio of the span to
depth of the slab continuous over at least three sup-
ports with cantilevers at the ends shall not be greater
than 40 for floor slabs or 44 for roof slabs.
18.23.2 — Distribution of tendons. The use of banded
tendons is acceptable. Maximum tendon spacing
shall be six times the slab thickness, not to exceed 42
inches (1067 mm). A minimum prestress level of 125
psi (861 kPa) on the local slab section tributary to the
tendon or tendon group is required. A minimum of two
tendons in flat slabs shall be placed over columns in
each direction. Tendons at slab edges shall be placed
6 inches (152 mm) clear of the slab edge. Tendons
shall be firmly supported at intervals not exceeding
42 inches (1067 mm) to prevent displacement during
concrete placement. Tendons shall not be bundled in
groups greater than five monostrand tendons. At hori-
zontal plane deviations grouped tendons at curved
2010 CALIFORNIA BUILDING CODE
249
CONCRETE
portions must be separated with 1 -inch-minimum (25
mm) clear between each tendon,
18,23,3 — Slab edge reinforcement. The slab edges,
including interior openings with anchorages, shall be
reinforced with two No. 5 bars, one top and one bot-
tom, minimum, with a No. 3 hairpin placed each side
of each anchorage or tendon carrying an effective
prestressing force of 50,000 pounds (223 kN) or less.
These hairpins shall be increased to No. 4 hairpins if
the effective force per anchorage or tendon is greater
than 50,000 pounds (223 kN).
1916.4.4 ACI 318, Section 21.4. In addition to the require-
ments of Section 1908.1.3, wall piers in Seismic Design Cat-
egory D, EorF shall comply with Section 1908.1.4.
1916.4.5 ACI 318, Section 21.9.2.2. Modify ACl 318, Sec-
tion 21.9.2.2 by adding the following:
Where boundary members are not required by ACI 318
I I Section 21.9.6, minimum reinforcement parallel to the
edges of all structural walls and the boundaries of all open-
ings shall consist of twice the cross-sectional area of the
minimum shear reinforcement required per lineal foot of
wall Horizontal extent of boundary element shall be per
ACI 318 Section 21.9,6.4 (a) and (b),
1916.4.6 ACI 318, Section 21.9.4. Modify ACI 3 18 by add-
ing Section 21.9.4.6 as follows:
21,9.4.6 - Walls and portions of walls with P„ > 0.35P^
shall not be considered to contribute to the calculated
strength of the structure for resisting earth-
quake-induced forces. Such walls shall conform to the
requirements of ACI 318 Section 21,13,
1916.4.7 ACI 318, Section 21.1 L4. ModifyACI 318 Section
21.11.4 by adding the following:
Collector and boundary elements in topping slabs
placed over precast floor and roof elements shall not be
less than 3 inches (76 mm) or 6 d^ thick, where db is the
diameter of the largest reinforcement in the topping slab.
1916.4.8 ACI 318, Section21.1L7. ModifyACI 318 Section
21.11.7 by adding Section 21.1 L7. 7 as follows:
21.11.7.7 - Where boundary members are not required
by ACI 318 Section 21.11.7.5, minimum reinforcement
parallel to the edges of all diaphragms and the bound-
aries of all openings shall consist of twice the cross-sec-
tional area of the minimum shear reinforcement required
per linear foot of diaphragm,
1916.4.9 ACI 318, Chapter 22. Plain concrete is not permit-
ted.
1916.4.10 ACI 318, SectionD.3.3. ModifyACI 318, Section
D.3.3.1 and add Section D.3.3. 7 to read as follows:
D.3.3.1 - The provisions of Appendix D do not apply to
the design of anchors in plastic hinge zones of concrete
structures under earthquake forces or to anchors that
meet the requirements of Section D.3,3,7.
D.3.3.7 ~ For wood sill plates a minimum of V/j inches
(38 mm) in net thickness, the allowable lateral design
values of cast-in anchors in shear parallel to the grain of
the wood sill plate are permitted to be determined in
accordance with Section 2305 of the International Build-
ing Code, provided they comply with all of the following:
1. Their maximum nominal diameter is V^ inches (16
mm);
2. They are embedded into the concrete a minimum of
7 inches (178 mm);
3. They are located a minimum of 2^/ 2 anchor diame-
ters from the edges of the concrete parallel to the
grain of the wood sill plate; and
4. They are located a minimum of 15 anchor diame-
ters from the end of the concrete perpendicular to
the grain of the wood sill plate.
1916.5 Shotcrete.
1916.5.1 Preconstruction tests. A test panel prepared in
accordance with Section 1913.5 is required. Approval from
the enforcement agency must be obtained prior to perform-
ing test panels. <
1916.5.2 Surface preparation. Concrete or masonry to I I
receive shotcrete shall have the entire surface thoroughly
cleaned and roughened by sand blasting, and just prior to
receiving shotcrete, shall be thoroughly cleaned of all debris,
dirt and dust. Concrete and masonry shall be wetted before
shotcrete is deposited, but not so wet as to overcome suction.
191 6. 5. 3 Joints. The film oflaitance which forms on the sur- II'
face of the shotcrete shall be removed within approximately
two hours after application by brushing with a stiff broom. If
this film is not removed within two hours, it shall be removed
by thorough wire brushing or sand blasting. Construction
joints over eight hours old shall be thoroughly cleaned with
air and water prior to receiving shotcrete.
1916.5.4 Forms and ground wires for shotcrete. Forms for
shotcrete shall be substantial and rigid. Forms shall be built
and placed so as to permit the escape of air and rebound.
Adequate ground wires, which are to be used as screeds,
shall be placed to establish the thickness, surface planes
and form of the shotcrete work. All surfaces shall be rodded
to these wires,
1916.5.5 Placing. Shotcrete shall be placed in accordance
with ACI 506.
1916.6 Existing concrete structures. The structural use of
existing concrete with a core strength less than 1,500 psi
(10.3MPa) is not permitted in rehabilitation work.
For existing concrete structures, sufficient cores shall be taken
at representative locations throughout the structure, as desig-
nated by the architect or structural engineer, so that knowledge
will be had of the in-place strength of the concrete. At least
three cores shall be taken from each building for each 4,000
square feet (372 m^) of floor area, or fraction thereof Cores
shall be at least 4 inches (102 mm) in diameter. Cores as small
as 2,75 inches (70 mm) in diameter may be allowed by the
enforcement agency when reinforcement is closely spaced and
the coarse aggregate does not exceed % inch (19 mm).
250
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 19A - CONCRETE
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed betow
Chapter/Section
2010 CALIFORNIA BUILDING CODE
251
252 201 CALIFORNIA BUILDING CODE
CHAPTER 19>V
CONCRETE
Italics are used for text within Sections 1903A through 1908A of this code to indicate provisions that differ from ACI 318.
State of California amendments in these sections are shown in italics and underlined.
SECTION 19014
GENERAL
1901A.1 Scope. The provisions of this chapter shall govern the
materials, quahty control, design and construction of concrete
used in structures.
1901 A, 1.1 Application, The scope of application of Chap-
ter 19 A is as follows:
1. Structures regulated by the Division of the State
Architect-Structural Safety (DSA-SS), which include
those applications listed in Section 1.9.2. These
applications include public elementary and second-
ary schools, community colleges and state- owned or
state-leased essential services buildings
II 2. Applications listed in Sections LI 0.1 and 1. 1 0.4, reg-
ulated by the Office of Statewide Health Planning and
Development (OSHPD). These applications include
hospitals, skilled nursing facilities, intermediate care
facilities and correctional treatment centers.
Exception: [OSHPD 2] Single-story Type V
skilled nursing or intermediate care facilities uti-
lizing wood-frame or light- steel-frame construc-
tion as defined in Health and Safety Code Section
129725, which shall comply with Chapter 19 and
any applicable amendments therein.
1901AJ.2 Amendments in this chapter, DSA-SS
OSHPD adopt this chapter and all amendments.
and
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1 . Division of the State A rchitect — Structural Safety:
[DSA-SS] For applications listed in Section 1.9.2.
2. Office of Statewide Health Planning and Develop-
ment.
II
[OSHPD 1]
LIO.I.
For applications listed in Section
[OSHPD 4] ' For applications listed in Section
LIOA.
1901A.2 Plain and reinforced concrete. Structural concrete
shall be designed and constructed in accordance with the
requirements of this chapter and ACI 318 as amended in Sec-
tion 1908A of this code. Except for the provisions of Sections
I904A and 1910A, the design and construction of slabs on
grade shall not be governed by this chapter unless they transmit
vertical loads or lateral forces from other parts of the structure
to the soil.
190L4.3 Source and applicability. The format and subject
matter of Sections 1902A through 1907A of this chapter are
patterned after, and in general conformity with, the provisions
for structural concrete in ACI 318.
1901A.4 Construction documents. The construction docu-
ments for structural concrete construction shall include:
1. The specified compressive strength of concrete at the
stated ages or stages of construction for which each
concrete element is designed.
2. The specified strength or grade of reinforcement.
3. The size and location of structural elements, reinforce-
ment and anchors.
4. Provision for dimensional changes resulting from
creep, shrinkage and temperature.
5. The magnitude and location of prestressing forces.
6. Anchorage length of reinforcement and location and
length of lap splices.
7. Type and location of mechanical and welded splices of
reinforcement.
8. Details and location of contraction or isolation joints
specified for plain concrete.
9. Minimum concrete compressive strength at time of
posttensioning.
10. Stressing sequence for posttensioning tendons.
1 1 . For structures assigned to Seismic Design Category D,
E or F, a statement if slab on grade is designed as a
structural diaphragm (see Section 21.12.3.4 of ACI
318).
190L4.5 Special inspection. The special inspection of con-
crete elements of buildings and structures and concreting oper-
ations shall be as required by Chapter 17A.
SECTION 19024
DEFINITIONS
1902A.1 General. The words and terms defined in ACI 318
shall, for the purposes of this chapter and as used elsewhere in
this code for concrete construction, have the meanings shown
in ACI 318 as modified by Section 1908A.1.1.
2010 CALIFORNIA BUILDING CODE
253
CONCRETE
TABLE 1904A.3
MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f g
TYPE OR LOCATION OF CONCRETE CONSTRUCTION
MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f '^at 28 days, psi)
Negligible exposure
Moderate exposure
Severe exposure
Basement walls^ and foundations not exposed to the weather
2,500
2,500
2,500^
Basement slabs and interior slabs on grade, except garage floor
slabs
2,500
2,500
2,500^
Basement walls^ foundation walls, exterior walls and other
vertical concrete surfaces exposed to the weather
2,500
3,000*^
3,000^
Driveways, curbs, walks, patios, porches, carport slabs, steps and
other flatwork exposed to the weather, and garage floor slabs
2,500
3,000'''^
3,500*'- '^
For SI: I pound per square inch = 0.00689 MPa.
a. Concrete in these locations that can be subjected to freezing and thawing during construction shall be of air-entrained concrete in accordance with
Section 1904A2.1.
b. Concrete shall be air entrained in accordance with Section 1904>A.4.1 .
c. Structural plain concrete basement walls are exempt from the requirements for exposure conditions of Section 1 904>A.3 (see Section 1 909/4.6. 1 ).
d. For garage floor slabs where a steel trowel finish is used, the total air content required by Section 1904>4.4.1 Is permitted to be reduced to not less
than 3 percent, provided the minimum specified compressive strength of the concrete is increased to 4,000 psi.
NEGLIGIBLE
FIGURE 1904A3
WEATHERING PROBABILITY MAP FOR CONCRETE^' *"' *^
a. Lines defining areas are approximate only. Local areas can be more or less severe than indicated by the region classification.
b. A "severe" classification is where weather conditions encourage or require the use of deicing chemicals or where there is potential for a continuous
presence of moisture during frequent cycles of freezing and thawing. A "moderate" classification is where weather conditions occasionally expose
concrete in the presence of moisture to freezing and thawing, but where deicing chemicals are not generally used. A "negligible" classification is where
weather conditions rarely expose concrete in the presence of moisture to freezing and thawing.
c. Alaska and Hawaii are classified as severe and negligible, respectively.
254
2010 CALIFORNIA BUILDING CODE
CONCRETE
SECTION 19034
SPECIFICATIONS FOR TESTS AND MATERIALS
1903A.1 General. Materials used to produce concrete, con-
crete itself and testing thereof shall comply with the applicable
standards listed in ACI 318. Where required, special inspec-
tions and tests shall he in accordance with Chapter 1 7 A and
Section 1916A,
1903A.2 Glass fiber reinforced concrete. Glass fiber rein-
forced concrete (GFRC) and the materials used in such con-
crete shall be in accordance with the PCIMNL 128 standard.
1903A .3 Reporting requirements ■
3,2,1 by the following:
Modify ACI 318 Section
Each component fa] through (gl when present, as a per-
centage of total cementitious materials shall he reported for
each mix design.
1903A.4 Fly ash. RpplacP. ACJ 318 Section 3.2.2 as follows:
Fly ash or other pozz olan can he used as a partial substitute for
ASTM C 150 Portland cement, as follows:
L Fly ash or other pozzolan shall conform to ASTM C 618
for Class Nor Class F materials (Class C is not permit-
ted), and
L More than 15 percent by weight of fly ash or other
po77olans shall he permitted to be s ubstituted for ASTM
C 150 Portland cement if the mix design is proportioned
per Section 1 905 A J. See Section 1904Afor durability
requirements,
L More than 40 percent by weight of ground - granulated
blast-furnace slag conforming to ASTM C 989 shall be
permitted to be substituted for ASTM C J 50 portland
cement if the mix design is proportioned per Section
I905A.3. See Section J 904A for durability requirements.
1903A,5 ACI 31S Section 3.3.2. Modify ACJ 318. Section3.3.2
by adding the following:
Aggregate size limitations waiver shall he approvpA by the
enforcement agency.
Evidence that the aggregate used is not reactive in the
presence of cement alkalis may he required by the enforce-
ment agency, ffnew aggregate sources are to he used or if
past experience indicates problems with existing aggregate
source ff. test the aggregate for potential reactivity according
to ASTM C 289 to determine potential reactivity in the pres-
ence of cement.
{fthe results of the test are other than innocuous, selected
concrete proportions using the aggregate (see Section
1905A.2) shall be tested in accordance with ASTM C 1567.
If the results of this test indicate an ex pansion greater than
0.10 percent at 1 6-day s age, provide mitigation with one of
the cementitious material systems note d below such that an
expansion of less than 0.10 percent at 16-days age is
obtained:
h Low-alkali Portland cement containing not more than
0.6 percent total alkali when calculated as sodium.
oxide, as determined by the method given in ASTM C
Ltd.
Z. Blended hydraulic cement. Type IS or IP. conforming
to ASTM C 595. except that Type IS cement shall not
contain less than 40 percent sla g constituent.
i. Replaceme nt of not less than 15 percent by weight of
the Portland cement used by a mineral admixture con-
forming to ASTM C 618 for Class N or F materials
(Class C is not permitted).
i Replacement of not less than 40 percent by weight of
the Portland cement used by a ground granulated
blast-furnace slag conforming to ASTM C 989.
1903 A,6 Discontinuous steel fibers. Modify ACI 318 Section
3.5.1 by adding the following:
Discontinuous steel fibers are not permitted.
1903 A. 7 Welding of reinforcing bars. Modify ACI 318 Section
3.5 .2 by a dding the following:
If mill test reports are not availahle. chemical analysis shall
be made of bars representative of the bars to be welded.
Bars with a carbon equivalent (C. E. ) above 0. 75 shall not be
welded. Welding shall not be done on or within two bar
diameters of any bent portion of a bar that has been bent
cold. Welding of crossing bars shall not be permitted for
assembly of reinforcement unless authorized by the struc-
tural engineer and approved by the enforcement agency per
approved procedures,
SECTION 19044
DURABILITY REQUIREMENTS
1904A.1 Water-cementitious materials ratio. Where maxi-
mum water-cementitious materials ratios are specified in ACI
318, they shall be calculated in accordance with ACI 318, Sec-
tion 4.1.
1904A.2 Exposure categories and classes. Concrete shall be
assigned to exposure classes in accordance with ACI 318, Sec-
tion 4.2, based on:
1 . Exposure to freezing and thawing in a moist condition or
deicer chemicals;
2. Exposure to sulfates in water or soil;
3 . Exposure to water where the concrete is intended to have
low permeability; and
4. Exposure to chlorides from deicing chemicals, salt,
saltwater, brackish water, seawater or spray from these
sources, where the concrete has steel reinforcement.
1904A.3 Concrete properties. Concrete mixtures shall con-
form to the most restrictive maximum water-cementitious
materials ratios and minimum specified concrete compressive
strength requirements of ACI 318, Section 4.3, based on the
exposure classes assigned in Section 1904A.2.
Exception: For occupancies and appurtenances thereto in
Group R occupancies that are in buildings less than four
stories above grade plane, normal-weight aggregate con-
crete is permitted to comply with the requirements of Table
1904 A. 3 based on the weathering classification (freezing
and thawing) determined from Figure 1904 A3 in lieu of the
requirements of ACI 318, Table 4, 3, L
2010 CALIFORNIA BUILDING CODE
255
CONCRETE
1904A.4 Freezing and thawing exposures. Concrete that will
be exposed to freezing and thawing, in the presence of mois-
ture, with or without deicing chemicals being present, shall
comply with Sections 1904A.4.1 and 1904A.4.2.
1904A.4.1 Air entrainment. Concrete exposed to freezing
and thawing while moist shall be air entrained in accordance
with ACI 318, Section 4.4.1.
1904A.4.2 Deicing chemicals. For concrete exposed to
freezing and thawing in the presence of moisture and
deicing chemicals, the maximum weight of fly ash, other
pozzolans, silica fume or slag that is included in the concrete
shall not exceed the percentages of the total weight of
cementitious materials permitted by ACI 318, Section 4,4.2.
1904A.5 Alternative cementitious materials for sulfate
exposure. Alternative combinations of cementitious materials
for use in sulfate-resistant concrete to those listed in ACI 318,
Table 4.3.1 shall be permitted in accordance with ACI 318,
Section 4.5.1.
SECTION 19054
CONCRETE QUALITY, MIXING AND PLACING
1905A.1 General. The required strength and durability of con-
crete shall be determined by compliance with the proportion-
ing, testing, mixing and placing provisions of Sections
1905A.1.1 through 1905A.13.
1905A.1.1 Strength. Concrete shall be proportioned to pro-
vide an average compressive strength as prescribed in Sec-
tion 1905 A. 3 and shall satisfy the durability criteria of
Section 1904A. Concrete shall be produced to minimize the
frequency of strengths below /'^ as prescribed in Section
1905 A. 6. 3. For concrete designed and constructed in accor-
dance with this chapter, f'c ^^^^ ^^t be less than 3.000 psi
(20. 7 MPa) . No maximum specified compressive strength
shall apply unless restricted by a specific provision of this
code or ACI 318. Reinforced concrete with specified com-
pressive strength higher than 8.000 p si shall >
require prior
approval of structural design method and acceptance crite-
ria by the enforcement agency.
1905A.2 Selection of concrete proportions. Concrete propor-
tions shall be determined in accordance with the provisions of
ACI 318, Section 5.2.
A registered civil engineer with experience in concrete mix
design shall select th e relative amounts of ingredients to be
used as basic proportions of the concrete m ixes proposed for
use under this provision,
1905A.3 Proportioning on the basis of field experience
and/or trial mixtures. Concrete proportioning determined on
the basis of field experience and/or trial mixtures shall be done
in accordance with ACI 318, Section 5.3.
1905A.4 Proportioning without field experience or trial
mixtures. Concrete proportioning determined without field
experience or trial mixtures shall be done in accordance with
ACI 318, Section 5.4.
1905A.5 Average strength reduction. As data become avail-
able during construction, it is permissible to reduce the amount
by which the average compressive strength (f'^ is required to
exceed the specified value off\ in accordance with ACI 318,
Section 5.5.
1905A.6 Evaluation and acceptance of concrete. The criteria
for evaluation and acceptance of concrete shall be as specified
in Sections 1905A.6.2 through 1905A.6.5.
1905A.6.1 Qualified technicians. Concrete shall be tested
in accordance with the requirements in Sections 1905A.6.2
through 1905A.6.5. Qualified field testing technicians shall
perform tests on fresh concrete at the job site, prepare speci-
mens required for curing under field conditions, prepare
specimens required for testing in the laboratory and record
the temperature of the fresh concrete when preparing speci-
mens for strength tests. Qualified laboratory technicians
shall perform all required laboratory tests.
1905A.6.2 Frequency of testing. The frequency of con-
ducting strength tests of concrete and the minimum number
of tests shall be as specified in ACI 318, Section 5.6.2 except
as modified in Section 1905A.6.2.L
12Q5A.6,2,1 Sample frequency. Replace ACf 318 Sec-
tion 5.(5.2. / as follows:
5,6,2 J Samples for Strength tests of each class of con-
crete placed each day shall be taken not less than once
a day or not less than once for ea ch 50 cubic yards
(345 m{) of concrete, or not less than once for each
2 MO square feet (186 m^) of surface area for slabs or
walls. Additional samples for seven-day compressive
strength test s shall he taken for each class of concrete
at the beginning of the concrete work or whenever the
mix or aggregate is changed,
1905A.6.3 Strength test specimens. Specimens prepared
for acceptance testing of concrete in accordance with Sec-
tion 1905A.6.2 and strength test acceptance criteria shall
comply with the provisions of ACI 318, Section 5.6.3.
1905A.6.4 Field-cured specimens. Where required by the
building official to determine adequacy of curing and pro-
tection of concrete in the structure, specimens shall be pre-
pared, cured, tested and test results evaluated for acceptance
in accordance with ACI 318, Section 5.6.4.
1905A.6.5 Low-strength test results. Where any strength
test (see ACI 318, Section 5.6.2.4) falls below the specified
value off\, the provisions of ACI 318, Section 5.6.5, shall
apply.
1905A.7 Preparation of equipment and place of deposit.
Prior to concrete being placed, the space to receive the concrete
and the equipment used to deposit it shall comply with ACI
318, Section 5.7.
1905A.8 Mixing. Mixing of concrete shall be performed in
accordance with ACI 318, Section 5.8.
1905A.9 Conveying. The method and equipment for convey-
ing concrete to the place of deposit shall comply with ACI 318,
Section 5.9.
1905A.10 Depositing. The depositing of concrete shall com-
ply with the provisions of ACI 318, Section 5.10.
256
2010 CALIFORNIA BUILDING CODE
CONCRETE
m
J90SA,10.1 Consolidation in congested areas. Where con-
ditiom make comolidation difficult or where reinforcement
is congested, a m ix design with smaller size aggregates.
shall he used as approved by the architect, structural engi-
neer and the enfor cement agency.
1905A.11 Curing. The length of time, temperature and mois-
ture conditions for curing of concrete shall be in accordance
with ACI 318, Section 5,11.
1905A.12 Cold weather requirements. Concrete to be placed
during freezing or near-freezing weather shall comply with the
requirements of ACI 318, Section 5.12.
When mixing concrete during cold weather the mix shall
have a temperature of at least 50° F (10.0°C). but not more than
90° F (32,2X), The concrete shall be maintained at a tempera-
ture of at least 50°F (10.0°C)fo r not less than 72 hours after
placing. When necessary, concrete materials shall he heated
before mixing. Special precautions shall be taken for the pro-
tection of transit-mix ed concrete to maintain a temperature of
at le ast 50°F ( 10,0 X ),
1905A.13 Hot weather requirements. Concrete to be placed
during hot weather shall comply with the requirements of ACI
318, Section 5.13.
SECTION 19064
FORMWORK, EMBEDDED PIPES AND
CONSTRUCTION JOINTS
1906A.1 Formwork. The design, fabrication and erection of
forms shall comply with ACI 318, Section 6.1.
1906A.2 Removal of forms, shores and reshores. The
removal of forms and shores, including from slabs and beams
(except where cast on the ground), and the installation of
reshores shall comply with ACI 318, Section 6.2,
No portion of the forming and shoring system may be
removed less than 12 hours after placing. When stripping time
is less tha n the specifie d curing time, measu res shall be taken to
provide adequate curing and thermal protection of the stripped
concrete.
1906A.3 Conduits and pipes embedded in concrete. Con-
duits, pipes and sleeves of any material not harmful to concrete
and within the limitations of ACI 318, Section 6.3, are permit-
ted to be embedded in concrete with approval of the registered
design professional.
13QM.3.1 Large openings. Openings larger than 12 inches
(305 mm) in any dimension shall be detailed on the struc-
tural plans. Nothing in this section shall be construed to
permit work in violation of fire and panic or other safety
Standards.
1906AJ.2 Adequate support Pipes and conduits shall be
adequately supported and secured against displacement
before concrete is placed,
1906A.4 Construction joints. Construction joints, including
their location, shall comply with the provisions of ACI 318,
Section 6.4.
Typical details and proposed locations of construction joints
shall be indicated on the plans.
1906AAA Surface preparation. The surface of all horizon-
tal construction joints shall he cleaned and roughened by
exposing clean aggregate solidly embedded in mortar
matrix.
In the event that the contact surface beco mes coated with
earth, sawdust, etc.. after being cleaned, the entire surface
so coated shall be recleaned.
SECTION 1907>4
DETAILS OF REINFORCEMENT
1907A.1 Hooks. Standard hooks on reinforcing bars used in
concrete construction shall comply with ACI 318, Section 7.1.
1907A.2 Minimum bend diameters. Minimum reinforce-
ment bend diameters utilized in concrete construction shall
comply with ACI 318, Section 7.2.
1907A.3 Bending. The bending of reinforcement shall comply
with ACI 318, Section 7.3.
1907A.4 Surface conditions of reinforcement. The surface
conditions of reinforcement shall comply with the provisions
of ACI 318, Section 7.4.
1907A.5 Placing reinforcement. The placement of reinforce-
ment, including tolerances on depth and cover, shall comply
with the provisions of ACI 318, Section 7.5. Reinforcement
shall be accurately placed and adequately supported before
concrete is placed.
1907A5J Prestressing tendons, Prestressing tendons
shall be placed within plus or minus V^ inch (6.4mm) toler-
ance for member depths equal to and less than 8 inches (203
mm) and not to exceed the lesser of^^ inch (9,5 mm) or one
third the minimum concrete cover for member depths
greater than 8 inches (203 mm).
1907A.6 Spacing limits for reinforcement. The clear distance
between reinforcing bars, bundled bars, tendons and ducts
shall comply with ACI 318, Section 7.6.
1907A.7 Concrete protection for reinforcement. The mini-
mum specified concrete cover for reinforcement shall comply
with Sections 1907A.7.1 through 1907A.7.8.
1907A.7.1 Cast-in-place concrete (nonprestressed). Min-
imum specified concrete cover shall be provided for rein-
forcement in nonprestressed, cast-in-place concrete
construction in accordance with ACI 318, Section 7,7.1.
1907A.7.2 Cast-in-place concrete (prestressed). The min-
imum specified concrete cover for prestressed and
nonprestressed reinforcement, ducts and end fittings in
cast-in-place prestressed concrete shall comply with ACI
318, Section 7.7.2.
1907A.7.3 Precast concrete (manufactured under plant
control conditions). The minimum specified concrete
cover for prestressed and nonprestressed reinforcement,
ducts and end fittings in precast concrete manufactured
under plant control conditions shall comply with ACI 318,
Section 7.7.3.
<
2010 CALIFORNIA BUILDING CODE
257
CONCRETE
1907A.7.4 Bundled bars. The minimum specified concrete
cover for bundled bars shall comply with ACI 318, Section
7.7.4.
1907A.7.5 Headed shear stud reinforcement. For headed
shear stud reinforcement, the minimum specified concrete
cover shall comply with ACI 318, Section 7.7.5.
1907A.7.6 Corrosive environments. In corrosive environ-
ments or other severe exposure conditions, prestressed and
nonprestressed reinforcement shall be provided with addi-
tional protection in accordance with ACI 318, Section 7 .7.6.
1907A.7,7 Future extensions. Exposed reinforcement,
inserts and plates intended for bonding with future exten-
sions shall be protected from corrosion.
1907A.7.8 Fire protection. When this code requires a
thickness of cover for fire protection greater than the mini-
mum concrete cover in Section 1907A.7, such greater thick-
ness shall be specified.
1907A.8 Special reinforcement details for columns. Offset
bent longitudinal bars in columns and load transfer in structural
steel cores of composite compression members shall comply
with the provisions of ACI 318, Section 7.8.
1907A.9 Connections. Connections between concrete fram-
ing members shall comply with the provisions of ACI 318, Sec-
tion 7.9.
1907A.10 Lateral reinforcement for compression mem-
bers. Lateral reinforcement for concrete compression mem-
bers shall comply with the provisions of ACI 318, Section 7.10.
1907A.11 Lateral reinforcement for flexural members. Lat-
eral reinforcement for compression reinforcement in concrete
flexural members shall comply with the provisions of ACI 318,
Section 7.11.
1907A.12 Shrinkage and temperature reinforcement. Rein-
forcement for shrinkage and temperature stresses in concrete
members shall comply with the provisions of ACI 318, Section
7.12.
1907A.13 Requirements for structural integrity. The detail-
ing of reinforcement and connections between concrete mem-
bers shall comply with the provisions of ACI 318, Section 7.13,
to improve structural integrity.
SECTION 19084
MODIFICATIONS TO ACI 318
1908A.1 General. The text of ACI 318 shall be modified as
M indicated in Sections 1908A.1.1 through 19Q8A.1J2 .
1908A.1.1 ACI 318, Section 2.2. Modify existing definitions
and add the following definitions to ACI 318, Section 2.2.
DESIGN DISPLACEMENT. Total lateral displacement
> expected for the design earthquake, as specified by Section
12.8.6ofASCE7.
DETAILED PLAIN CONCRETE STRUCTURAL WALL.
A wall complying with the requirements of Chapter 22,
including 22.6.7.
ORDINARY PRECAST STRUCTURAL WALL A precast
wall complying with the requirements of Chapters 1 through
18.
ORDINARY REINFORCED CONCRETE STRUC-
TURAL WALL. A cast-in-place wall complying with the
requirements of Chapters 1 through 18.
ORDINARY STRUCTURAL PLAIN CONCRETE
WALL. A wall complying with the requirements of Chapter
22, excluding 22.6.7.
SPECIAL STRUCTURAL WALL. A cast-in-place or pre-
cast wall complying with the requirements of 21 . 1 .3 through
21.1.7, 21.9 and 21.10, as appUcable, in addition to the
requirements for ordinary reinforced concrete structural
walls or ordinary precast structural walls, as applicable.
Where ASCE 7 refers to a ''special reinforced concrete struc-
tural wall," it shall be deemed to mean a ''special structural
wall"
WALL PIER, A wall segment with a horizontal length-
to-thickness ratio of at least 2.5, but not exceeding 6, whose
clear height is at least two times its horizontal length.
1 9 8AJ J A CI 3 18, S ectio n 8 J3 S R eplac e ACI 31 8 S ec-
tion 8 A 3, 5 as follows:
8.13.5 - Permanent burned clay or concrete tile fillers
shall he considered only as forms and shall not he
included in the ca lculations involving shear or bending
moments.
The thickness of the concrete slab on the permanent fill-
ers shall be designed as described in ACI Section 8,13,6
as modified in Section J908A.1.3.
I90SA.L3 ACI 318. Section S. 13.6. Replace ACI 318 Sec-
tion 8.13.6 as follows:
8.13.6 - Where removable forms or fillers are used, the
thickness of the concrete slab shall not be less than V^ of
the clear distance between joists and in no case less than
2V. inch(^s (64 mm). Such slab shall be rein forced at right
angles to the joists with at least the amount of reinforce-
ment requirp.d for fipxure. considering load concentra-
tions, {fany. hut in no case shall the reinforcement be less
than that required by ACI 318 Section 7.12.
I90HA.L4 ACI 318. Section 8.13. Add Section 8.13.9 to
ACJ 3 18 as fol l ow s:
8 J 3,9 Concrete bridging. Concrete bridging shall be
provided as follow s: one near the center of spans for 20
to 30 feet (6096 mm to 9144 mm) spans and two near the
third points of spans over 30 feet (9144 mm). Such bridg-
ing shall he either:
(a) A continuous concrete web having a depth equal
to the joist and a width not less than 5V . inches
(89 mm) reinforced with a minimum of one No, 4
bar in the t op and bottom: or
IhX. Any other concrete element capable oftrani^er-
ring a concentrated load of 1.000 pounds (4.5
kN)from any joist to the two adjacent joists.
Such bridging shall not be required in roof framing if
an individual member is capable of carrying dead load
258
2010 CALIFORNIA BUILDING CODE
CONCRETE
plus a concentrate d load of ] .500 pounds (6, 7 kN) at any
point
X908A U A CI 318 , Sec tio n 1 0.5 J . M odi fy ACI 318 S ec-
tion 10.5. 3 hy adding the following:
This section shall not he used for members that resist
seismic loads, except that reinforcement provided for
foundation elements for one-story wood-frame or
one-story light s teel buildings need n ot he more than
one-third greater than that required by analysis for all
loading conditions.
190HA.L6ACI318, Section 12.14,3. Add Section 12 14.3.6
to ACI 318 as follows:
12. 14.3.6 ' Welded splices and mechanical connections
shall maintain the clearance and coverage requirements
ofACISectiom 7,6 and 7,7.
1908A JJ A C U18 , Section 14X 6. R eplace ACI 3 18 S ec-
tion 14.2,6 a s f ollo w s:
14. 2.6- Walls shall he anchored to intersecting elements
such as floors or roofs or to columns, pilasters, buttresses
and intersecting walls and footings with reinforcement at
least equivalent to No. 4 bars at 12 inches (305 mm) on
center for each layer of reinforcement,
1908A18 R e serve d,
190SA,L9 Reserved.
190SA.1.10 ACI 318. Section 14.5 - Empirical design
method. Not permitted by OS HP D a nd DS A- SS ,
J90SA.LJ1ACI31S, Section 14.6.L Replace ACI 318 Sec-
tion 14.6A as follows:
14.6.1 - Nonhearing walls or nonbearing shear walls
shall have a thickness of not less than 4 inches ( 102 mm)
nor a thickness less than V ^ of the shorter unsupported
distance between vertical or horizontal stiffening ele-
ments.
Where walls are supported laterally by vertical ele-
ments, the stiffness of each vertical element shall exceed
that of the tributary area of the wall.
190 8 AJJ2ACI3 1 8 , S ectio n 14 .9 . Mod i fy A C I 3 1 8 by a dd-
ing Section 14,9 as follows;
14.9 - Foundation walls. Horizontal reinforcing of con-
crete foundation walls for wood-frame or light-steel
buildings shall consist of the equivale nt of not less than
one No. 5 bar located at the top and bottom of the wall
Where such walls exceed 3 feet (914 mm) in height, inter-
mediate horizontal reinforcing shall be provided at spac-
ing not to exceed! feet (610 mm) on center Minimum
vertical reinforcing shall consist of No, 3 bars at 24
inches (610 mm) on center
Where concrete foundation walls or curbs extend
above the floor line and support wood-frame or
light-steel exterior bearing or shear walls, they shall be
doweled to the foundation wall below with a minimum of
No. 3 bars at 24 inches (610 mm) on center Where the
height of the wall above the floor line exceeds 18 inches
(457 mm), the wall above and below the floor line shall
meet the requirements of ACI 318 Section 14.3.
1908AJ. 13 Reserved.
190MJJ4 ACI 318 Section 1 6, A d d Sectio n 16,11 to ACI
318 as follows:
16.11 - Reinforcement. Perimeters of precast walls shall
be reinforced continuously with a minimum of one No. 5
bar extending the full height and width of the wall panel.
Bars shall be continuous around corners. Where wall
panels do not abut columns or other wall panels, perime-
ter bars shall be retained by hooked wall bars. Edges of
openings in precast walls shall be reinforced with a mini-
mum, of one No. 5 bar contin uous past corners sufflcient
to develop the bar
A continuous tie or bond beam shall be provided at the
roof line either as a part of the roof structure or part of
the wall panels as described in the next paragraph below.
This tie may be designed as the edge member of the roof
diaphragm but, in any case, shall not be less than equiva-
lent to two No, 6 bars continuous, A continuous tie equiv-
alent to two No. 5 bars mini mum shall also be provided
either in the footing or with an enlarged section of the
floor slab.
Wall panels of shear wall buildings shall be connected
to columns or to each other in such a manner as to
develop at least 7 5 percent of the horizontal wall steel.
Half of this continuous horizontal reinforcing may be
concentrated in b ond or tie b eams at the top and bottom
of the walls and at points of intermediate lateral support.
If possible, cast in-place joints with reinforcing bars
extending from the panels into the joint a sufficient dis-
tance to meet the splice requirements of ACI 318 Section
12, 15 for Class A shall be used. The reinforcing bars or
welded tie details shall not be spaced over eight times the
wall thickness vertically nor fewer than four used in the
wall panel height. Where wall panels are designed for
their respective overturning forces, the panel connec-
tions need not comply with the requirements of this para-
graph.
Where splicing of reinforcement must he made at
points of maximum stress or at closer spacing than per-
mitted hy ACI 318 Section 7.6. welding may be used
when the entire procedure is suitable for the particular
quality of steel used and the ambient conditions. Unless
the welds develop 125 percent of the specified yield
strength of the steel used, reinforcement in the form of
continuous bars o r fully anchored dowels shall be added
to provide 25 percent excess steel area and the welds
shall develop not less than the specified yield strength of
the Steel
Exception; Nonbearing, nonshear panels such as
nonstructural architectural cladding panels or col-
umn covers are not required to meet the provisions of
this section,
2010 CALIFORNIA BUILDING CODE
259
CONCRETE
12QSA.L15 ACI 318, Section U.^.h Mnd{fv ACmRSec
tion 17.5 J by adding Sectiom 17,5 J, J and 17.5 J2 as fol-
lows:
17.5.1. J ' Full transfer ofhorirnntal shear forces may he
assumed when all of the following are satisfied:
J. Contact surfaces are clean, free of laitance and
intentionally roughened to full amplitude of
approximately ^4 i^^h (6.4 mml
2^ Minimum tie^s are provided in accordance with
ACT. VS Section J 7.6.
3. Weh members are designed to resist total vertical
shear, and
i^All shear reinforcement is fully anchored into all
interconnected elements.
17.5.1.2- If all requirements of AC! 318 Section 17.5.1.1
are not satisfied, horizontal shear shall be investigated in
accordance withACHlS Section 17.5.3 or 17.5.4.
1908 A JJ6ACn i 8, S e c tion 1 8 JJ . Mod i fy A C! 3 18 Sec-
tion 18.2.3 hy adding the following:
For prestressed concrete members with recessed or
dapped ends, an analysis of the connections shall be
made in accordance with procedures given in PCI
Design Handbook. 7^ Edition.
12QSAJJ7 ACI 318 Section 18.2,4, Mod i fy ACI 318 Sec-
tion 18.2.4 by adding the following:
Where prestressed concrete elements are re strained from
movement, an analysis of the stresses in the prestressed
elements and loads in the adjoining structural system
induced hy the above-described effects shall he made in
accordance with PCI Design Handbook. 7^ Edition.
1908AJ J8 A CI 318, S ectio n 18 , 2 . A dd S ection 18, 2 , 7 to
ACI 318 as follows:
18.2. 7 ' Span to depth ratio. Span to depth ratios for pre-
stressed concrete members shall not exceed the follow-
ing, except when calculations of deflections prove that
greater values may be used without adverse effects:
Beams 30
One-way slabs 40
Two-way floor slabs 40
Two-way roof slabs 44
Flat s lab s , , . .S ee CB C S ecti o n 1908A ,L 2 1
These ratios should be decreased for special condi-
tions such as heavy loads and simple spans.
Maximum defle ction criteria shall be in accordance
wi th ACI 318 S e c t ion 9 ,5 ,
190SA.7.79 Reserved.
1908 A J.20ACI3J8 , S ectio n 1 8 M. A dd Se ction 1 8 ,211 .5 to
ACI 318 as follows ;
I8.2L5 - Prequalification of anchorages and coupler
Posttensioned anchorages and couplers for unbonded
tendons shall be prequaljfiedfor use in prestressed con-
crete, Data shall be submitted by the posttensioning
materials fabricator from an app roved independent test-
ing agency to show compliance with the following
dynamic test requirements:
A dynamic test shal l be performed on a representative
specimen and the tendon shall withstand, without fail-
ure. 500.000 cycles from 60 percent to 66 percent of its
minimum specified ultimate strength and 50 cycles from
40 percent to 80 percent of its minimum specified ulti-
mate stre ngth. The period of each cycle involves the
change from the lower stress level to the upper stress
level and back to the lower. The specimen used for the
second dynamic test need not be the same used for the
first dynamic test. Systems utilizing multiple strands,
wires or bars may be tested utilizing a test tendon of
smaller capacity than the full-size tendon. The test ten-
don shall duplicate the behavior of the full-size tendon
and gene rally shall not have less than 10 percent of the
capacity of the full-size tendon.
The above test data must be on file at the enforcement
agency for posttensioning systems to be used. General
approval will be based on satisfactory performance.
Tests shal l be required for prestre ssing steel and anchor-
ag es.
The average bearing stress. P/A^. on the concrete cre-
ated by the anchorage plates shall not exceed thefollow-
mgi
At service load
f^^0.6f:^Al/A^
but not greater thanf\
At transfer load
f^ = 0^8fUAl/A,-0,2
but not greater than 1.25 f'^ where;
f^ = permissible compressive concrete stress,
fl^ - compressive strength of concrete,
/V = compressiv e strength of concrete at time of ini-
tial prestress,
A \ = maximum , area of the portion of the concrete
anchorage surface that is geometrically similar to
and concentric with the area of the anchorage.
A^ = bearing area of the anchorage,
P = prestress force in tendon,
190SA.L21 ACT 318, Section 18. Add Section 18.23 to ACI
318 as follows;
J 8.23 - Prestressed flat slab.
18.23.1 - Span depth ratio. The ratio of the span to
depth of the slab continuous over at least three sup-
ports with cantilevers at the ends shall not be greater
than 40 for floor slabs or 44 for roof slabs.
18.23.2 - Distribution of tendons. The use of banded
tendons is acceptable. Maximum tendon spacing
shall be six times the slab thickness, not to exceed 42
inches (1067 mm). A minimum prestress level of 125
260
2010 CALIFORNIA BUILDING CODE
CONCRETE
psi (861 kP a) on the local slab section tributary to the
tendon or tendon group is required. A minimum of two
tendom in flat slab^s f>hall be placed over columm in
e ach dir e ction. Tendom at dab edges shall be placed
6 inches (J 52 mm) clear of the slab edge, Tendom
shall be firmly supported at intervals not exceeding
42 inches (1067 mm) to prevent displacement during
concrete placement. Tendons shall not be bundled in
groups greater than five monostrand tendons. At hori-
zontal plane deviations grouped tendons at curved
portions must be sep arated with 1 -inch-minimum (25
mm) clear between each tendon.
18.23.3 - Slab edge reinforcement. The slab edges.
including interior openings with anchorages, shall be
forced with two No, 5 bars, one top and one bot-
reinfo
torn, minimum, with a No. 3 hairpin placed each side
of each anchorage or tendon carrying an effective
prestressing force of 50.000 pounds (223 kN) or less.
These hairpins shall be increased to No, 4 hairpins if
the effective force per anchorage or tendon is greater
than MOOO pounds (223 k N ) ,
1908A.L22 (Chapter 19. Section 1908.L2) ACI 318, Sec-
tion 21.1.1. Modify ACI 3 1 8 Sections 2 1 . 1 . L3 and 21 . 1 . 1 .7
to read as follows:
21.1.1.3 - Structures shall satisfy requirements of Chap-
ters 1 to 19. Structures assigned to Seismic Design Cate-
gory D, E or F also shall satisfy 21.1.1.4 through
2 1 . 1 . 1 . 8, as applicable. Structural elements of plain con-
crete are prohibited in structures assigned to Seismic
Design Category D, E or E
21.1.1.7 - Structural systems designated as part of the
seismic-force-resisting system shall be restricted to
those permitted by ASCE 7. The following provisions
shall be satisfied for each structural system designated as
part of the seismic-force-resisting system, regardless of
the Seismic Design Category:
(a) [DSA-SS] Intermediate precast structural wails
shall satisfy 21.4.
(b) Special moment frames shall satisfy 21.5
through 21.8.
(c) Special structural walls shall satisfy 21.9.
(d) Special structural walls constructed using pre-
cast concrete shall satisfy 21.10.
All special moment frames and special structural
walls shall also satisfy 21.1.3 through 21.1.7.
1 908AJ J3 (C hap te r 19, Sec tio n 1908, J J ) ACI 318, Sec-
tion 21.4. [DSA-SS] Modify ACI 318, Section 21.4, by
renumbering Section 21.4.3 to become 21.4.4 and adding
new Sections 21.4.3, 21.4.5 and 21.4.6 to read as follows:
21.4.3 - Connections that are designed to yield shall be
capable of maintaining 80 percent of their design
strength at the deformation induced by the design dis-
placement or shall use Type 2 mechanical splices.
21.4.4- Elements of the connection that are not designed
to yield shall develop at least 1 .5 Sy.
21A.5- Wall piers in Seismic Design Category D, EorF
shall comply with Section 1908.1.26 of this code
21.4.6- Wall segments with a horizontal length-to-thick-
ness ratio less than 2.5 shall be designed as columns.
190HAJJ4 A C I 3J8, S ectio n 2L 9 JJ. Mod if y ACI 318 ,
Section 21,9.2,2 by adding the following:
Where boundary members are not required by ACI 318
Section 21.9.6, minimum reinforcement parallel to the
edges of all structural walls and the boundaries of all
openings shall consist of twice the cross-sectional area
of the minimum shear reinforc ement required per lineal
foot of wall. Hori7ontal extent of boundary element shall
be p er A CI 318 Se cti on 21, 9 ,6.4 (a) & (b) .
1M8A.L25 ACI 318, Section 2L9.4. Modjiy ACJ 318 by
adding Section 21.9,4,6 as follows:
21,9.4,6 - Walls and portions of walls with P^ > 0.35 P^
shall not be consid ered to contribute to the calculated
strength of the structure for resisting earth-
quake-induced forces. Such walls shall conform to the
requirements of ACI 318 Section 21.13.
1908AJ.26 (Chapter 19, Section 1908.1.4) ACI 318, Sec-
tion 21.9. Modify ACI 318, Section 21.9, by adding new
Section 21.9.10 to read as follows:
21.9.10- Wall piers and wall segments.
21.9.10.1 - Wall piers not designed as a part of a spe-
cial moment frame shall have transverse reinforce-
ment designed to satisfy the requirements in
21.9.10.2.
Exceptions:
1. Wall piers that satisfy 21.13.
2. Wall piers along a wall line within a story
where other shear wall segments provide
lateral support to the wall piers and such
segments have a total stijfness of at least six
times the sum of the stiffnesses of all the wall
piers.
21.9.10.2 - Transverse reinforcement with seismic
hooks at both ends shall be designed to resist the
shear forces determined from 21.6.5.1. Spacing of
transverse reinforcement shall not exceed 6 inches
(152 mm). Transverse reinforcement shall be
extended beyond the pier clear height for at least 12
inches (305 mm).
21.9.10.3 - Wall segments with a horizontal length-
to-thickness ratio less than 2.5 shall be designed as
columns.
1908AJ.27 (Chapter 19, Section 1908.1.5) ACI 318, Sec-
tion 21.10. Modify ACI 318, Section 21 . 10.2, to read as fol-
lows:
21.10.2 - Special structural walls constructed using pre-
cast concrete shall satisfy all the requirements of 2 1 .9 for
cast-in-place special structural walls in addition to Sec-
tions 21.4.2 through 21.4.4.
2010 CALIFORNIA BUILDING CODE
261
CONCRETE
mSAUSACLVS, Section 2LU A M odi fy AC U 18 S ec-
tion 21JL4 by adding the following:
Collector and hnundary elements i n topping slabs
placed over precast floor and roof elements shall not he
less than 3 inches (76 mm) or 6 d^ thicL where d ^ is the
diameter of the largest reinforcement in the topping slab.
J908 A, U 9 Aa 31 8 , S ectio n2Llh 7. Mo di fyA CI 318 S ec-
tion 21.] 1.7 by adding Section 2L1L7.7 as follows :
21A1JJ - Where boundary members a re not required
by ACf 3J8 Section 2J.1J.7. 5, minimum reinforcement
parallel to the edges of all d iaphragms and the bound-
aries of all openings shall consist of twice the cross-sec-
tional area of the minimum shear reinforcement required
per linear foot of diaphragm.
190SA,L30 (Chapter 19, Section 1908,1.6) ACI 318, Sec-
tion 21.12.1.1. Modify ACI 318, Section 21.12.1.1, to read
as follows:
21.12.1.1 - Foundations resisting earthquake-induced
forces or transferring earthquake-induced forces between
a structure and ground shall comply with the requirements
of Section 21.12 and other applicable provisions of ACI
318 unless modified by Chapter ISA of the California
Building Code.
1908AJJ1 (Chapter 19, Section 1908.1.9) ACI 318, Sec-
tion D.3.3. Modify ACI 318, Sections DJ.3.L D.3.3.4 and
D.3.3.5, andaddD.3.3.7 to read as follows:
D.3.3. 1 - The provisions of Appendix D do not apply to
the design of anchors in plastic hinge zones of concrete
structures under earthquake forces or to anchors that
meet the requirem ents of Section D.33J.
D.3.3.4 - Anchors shall be designed to be governed by
the steel strength of a ductile steel element as determined
in accordance with D.5.1 and D.6.1, unless either
D.3.3.5 or D.3.3.6 is satisfied.
Exception: Anchors designed to resist wall out-of-
plane forces with design strengths equal to or greater
than the force determined in accordance withASCE 7
Equation 12.11-1 or 12.14-10 need not satisfy Sec-
tion D.3.3 A.
D.3.3.5 - Instead of D.3.3.4, the attachment that the
anchor is connecting to the structure shall be designed so
that the attachment will undergo ductile yielding at a
force level corresponding to anchor forces no greater
than the design strength of anchors specified in D.3.3. 3.
Exception: Anchors designed to resist wall out-of-
plane forces with design strengths equal to or greater
than the force determined in accordance withASCE 7
Equation 12.11-1 or 12.14-10 need not satisfy Sec-
tion D.3.3.5.
D.3.3 J - For wood sill plate s a minimum of /V . inches
(38 mm) in net thickness, the allowable lateral design
values of cast-in anchors in shear parallel to the grain of
the wood sill plate are permitted to be determined in
accordance with Section 2305 of the California Building
Code, provided they comp ly with all of the following:
L Their maximum, nominal diameter is V ^ inches (16
mm);
2. They are embedded into the concrete a minimum of
7 inches (178 mm);
L They are located a minimum of 2 ^Li a nch o r d iame-
ters from the edges of the concrete parallel to the
grain of the wood sill plate; and
i^ They are located a minimum of 1 5 anch or d iam e -
ters from the end of the concrete perpendicular to
the grain of the wood sill plate.
1908AJJ2 (Chapter 19, Section 1908.10) ACI 318, Sec-
tion D.4.2.2. Delete ACI 318, Section D.4.2.2, and replace
with the following:
D.4.2.2 - The concrete breakout strength requirements for
anchors in tension shall be considered satisfied by the
design procedure of D.5.2 provided Equation D-8 is not
used for anchor embedments exceeding 25 inches. The con-
crete breakout strength requirements for anchors in shear
with diameters not exceeding 2 inches shall be considered
satisfied by the design procedure ofD.6.2. For anchors in
shear with diameters exceeding 2 inches, shear anchor rein-
forcement shall be provided in accordance with the proce-
dures of D.6.2.9.
SECTION 19094
STRUCTURAL PLAIN CONCRETE
NOT PERMITTED BY OSHPD AND DSA-SS
SECTION 1 91 OA
MINIMUM SLAB PROVISIONS
1910A.1 General. The thickness of concrete floor slabs sup-
ported directly on the ground shall not be less than 3 V2 inches (89
mm). A 6-mil (0.006 inch; 0.15 mm) polyethylene vapor
retarder with joints lapped not less than 6 inches (152 mm) shall
be placed between the base course or subgrade and the concrete
floor slab, or other approved equivalent methods or materials
shall be used to retard vapor transmission through the floor slab.
Exception: A vapor retarder is not required:
1. For detached structures accessory to occupancies in
Group R-3, such as garages, utility buildings or other
unheated facilities.
2. For unheated storage rooms having an area of less
than 70 square feet (6.5 m^) and carports attached to
occupancies in Group R-3.
3. For buildings of other occupancies where migration
of moisture through the slab from below will not be
detrimental to the intended occupancy of the building.
4. For driveways, walks, patios and other flatwork
which will not be enclosed at a later date.
5. Where approved based on local site conditions.
I I
<
262
2010 CALIf=ORNIA BUILDING CODE
CONCRETE
SECTION 19114
ANCHORAGE TO CONCRETE-
ALLOWABLE STRESS DESIGN
191L4.1 Scope. The provisions of this section shall govern the
allowable stress design of headed bolts and headed stud
anchors cast in normal- weight concrete for purposes of trans-
mitting structural loads from one connected element to the
other. These provisions do not apply to anchors installed in
hardened concrete or where load combinations include earth-
quake loads or effects. The bearing area of headed anchors
shall be not less than one and one-half times the shank area.
Where strength design is used, or where load combinations
include earthquake loads or effects, the design strength of
anchors shall be determined in accordance with Section 1 9 1 2A.
Bolts shall conform to ASTM A 307 or an approved eqaivalcnt
1911 A. 1.1 Power actuated fasteners. Power actuated fas-
teners qualified in accordance with ICC-ES AC 70 shall be
deemed to satisfy the requirements of this section.
Power actuated fasteners shall be permitted for seismic
shear when they are specifically listed in ICC-ES Report
(ICC-ESR)for such service and for interior nonshear wall
partitions. Power actuated fastener shall not be used to
anchor exterior cladding or curtain wall systems.
1911A.2 Allowable service load. The allowable service load
for headed anchors in shear or tension shall be as indicated in
Table 19I1A.2. Where anchors are subject to combined shear
and tension, the following relationship shall be satisfied:
(PsIPtf + (Vsiyt)"^ ^ 1 (Equation 19A-1)
where:
P^ - Applied tension service load, pounds (N).
jP, = Allowable tension service load from Table 1911A.2,
pounds (N).
y^ = Applied shear service load, pounds (N).
Vf = Allowable shear service load from Table 1911A.2,
pounds (N).
1911A.3 Required edge distance and spacing. The allowable
service loads in tension and shear specified in Table 1911A.2
are for the edge distance and spacing specified. The edge dis-
tance and spacing are permitted to be reduced to 50 percent of
the values specified with an equal reduction in allowable ser-
vice load. Where edge distance and spacing are reduced less
than 50 percent, the allowable service load shall be determined
by linear interpolation.
1911A.4 Increase in allowable load. Increase of the values in
Table 1911A.2 by one-third is permitted where the provisions
of Section 1605A.3.2 permit an increase in allowable stress for
wind loading.
1911A.5 Increase for special inspection. Where special
inspection is provided for the installation of anchors, a
100-percent increase in the allowable tension values of Table
1 9 11 A. 2 is permitted. No increase in shear value is permitted.
SECTION 191 2 A
ANCHORAGE TO CONCRETE-
STRENGTH DESIGN
1912A.1 Scope. The provisions of this section shall govern the
strength design of anchors installed in concrete for purposes of
transmitting structural loads from one connected element to the
other. Headed bolts, headed studs and hooked (J- or L-) bolts cast
in concrete and expansion anchors and undercut anchors installed
in hardened concrete shall be designed in accordance with Appen-
dix D of ACI 318 as modified by Sections 1908A1.30 and
1908A.1.3f provided they are within the scope of Appendix D. ^
TABLE 1 911 A2
ALLOWABLE SERVICE LOAD ON EMBEDDED BOLTS (pounds)
BOLT
DIAMETER
(inches)
MINIMUM
EMBEDMENT
(inches)
EDGE
DISTANCE
(inches)
SPACING
(inches)
MINIMUM CONCRETE STRENGTH (psi)
f'^r: 2,500
f'^= 3,000
r^ = 4,000
Tension
Shear
Tension
Shear
Tension
Shear
%
2\
I'/a
3
200
500
200
500
200
500
\
3
2V4
4V,
500
1,100
500
1,100
500
1,100
%
4
4
3
5
6
6
950
1,450
1,250
1,600
950
1,500
1,250
1,650
950
1,550
1,250
1,750
%
4'/,
4'/,
3V4
1%
1%
1,500
2,125
2,750
2,950
1,500
2,200
2,750
3,000
1,500
2,400
2,750
3,050
%
5
5
7'4
9
9
2,250
2,825
3,250
4,275
2,250
2,950
3,560
4,300
2,250
3,200
3,560
4,400
%
6
5V4
IOV2
2,550
3,700
2,550
4,050
2,550
4,050
1
7
6
12
3,050
4,125
3,250
4,500
3,650
5,300
iVs
8
e\
1372
3,400
4,750
3,400
4,750
3,400
4,750
\%
9
1%
15
4,000
5,800
4,000
5,800
4,000
5,800
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound = 4.45 N.
2010 CALIFORNIA BUILDING CODE
263
CONCRETE
The strength design of anchors that are not within the scope
of Appendix D of ACI 318, and as amended in Sections
1908AJ30 and 1908A.131, shall be in accordance with an
approved procedure.
19 12 AAA Specialty inserts. Specialty inserts, including
cast-in-place specialty inserts^ tested in accordance with
ICC-ESAC 193 shall be deemed to satisfy the requirements
of this section.
SECTION 1 91 3>»
SHOTCRETE
1913A.1 General. Shotcrete is mortar or concrete that is pneu-
matically projected at high velocity onto a surface. Except as
specified in this section, shotcrete shall conform to the require-
> ments of this chapter for reinforced concrete and the provisions
of ACI 506. The specified compressive strength of shotcrete
shall not be less than 3,000 psi (20.69 mPa).
Concrete or masonry to receive shotcrete shall have the
entire surface thoroughly cleaned and roughened by sand
blasting, and just prior to receiving shotcrete, shall be thor-
oughly cleaned of all debris, dirt and dust Concrete and
masonry shall be wetted before shotcrete is deposited, but not
so wet as to overcome suction. Sand for sand blasting shall be
clean, sharp and uniform in size, with no particles that will
pass a 50-mesh screen.
1913A.2 Proportions and materials. Shotcrete proportions
shall be selected that allow suitable placement procedures
using the delivery equipment selected and shall result in fin-
ished in-place hardened shotcrete meeting the strength require-
ments of this code.
1913A.3 Aggregate. Coarse aggregate, if used, shall not
exceed V4 inch (19.1 mm).
For shear walls, when total rebar in any direction is more
than 0.31 in^/ft or rebar size is larger than #5, shotcrete shall
conform to course aggregate grading No. 2 per Table 1.1 of
ACI 506
1913A.4 Reinforcement. Reinforcement used in shotcrete
construction shall comply with the provisions of Sections
1913A.4.1 through 1913A.4.4.
1913A.4.1 Size. The maximum size of reinforcement shall
be No. 5 bars unless it is demonstrated by preconstruction
tests that adequate encasement of larger bars will be
achieved.
1913A.4.2 Clearance. When No. 5 or smaller bars are used,
there shall be a minimum clearance between parallel rein-
forcement bars of 2V2 inches (64 mm). When bars larger
than No. 5 are permitted, there shall be a minimum clear-
ance between parallel bars equal to six diameters of the bars
used. When two curtains of steel are provided, the curtain
nearer the nozzle shall have a minimum spacing equal to 12
bar diameters and the remaining curtain shall have a mini-
mum spacing of six bar diameters.
Exception: Subject to the approval of the building offi-
cial, required clearances shall be reduced where it is
demonstrated by preconstruction tests that adequate
encasement of the bars used in the design will be
achieved.
1913A.4.3 Splices. Lap splices of reinforcing bars shall uti-
lize the noncontact lap splice method with a minimum clear-
ance of 2 inches (51 mm) between bars. The use of contact
lap splices necessary for support of the reinforcing is per-
mitted when approvedhy the building official, based on sat-
isfactory preconstruction tests that show that adequate
encasement of the bars will be achieved, and provided that
the splice is oriented so that a plane through the center of the
spliced bars is perpendicular to the surface of the shotcrete.
1913A.4.4 Spirally tied columns. Shotcrete shall not be
applied to spirally tied columns.
1913A.5 Preconstruction tests. A test panel shall be shot, <
cured, cored or sawn, examined and tested prior to commence-
ment of the project. The sample panel shall be representative of
the project and simulate job conditions as closely as possible.
The panel thickness and reinforcing shall reproduce the thick-
est and most congested area specified in the structural design. It
shall be shot at the same angle, using the same nozzleman and
with the same concrete mix design that will be used on the pro-
ject. The equipment used in preconstruction testing shall be the
same equipment used in the work requiring such testing, unless
substitute equipment is approved by the building official.
1913A.6 Rebound. Any rebound or accumulated loose aggre-
gate shall be removed from the surfaces to be covered prior to
placing the initial or any succeeding layers of shotcrete.
Rebound shall not be used as aggregate.
1913A.7 Joints. Except where permitted herein, unfinished
work shall not be allowed to stand for more than 30 minutes
unless edges are sloped to a thin edge. For structural elements
that will be under compression and for construction joints
shown on the approved construction documents, square joints
are permitted. Before placing additional material adjacent to
previously applied work, sloping and square edges shall be
cleaned and wetted.
The film of laitance which forms on the surface of the
shotcrete shall be removed within approximately two hours
after application by brushing with a stiff broom. If this film is
not removed within two hours, it shall be removed by thorough
wire brushing or sand blasting. Construction joints over eight
hours old shall be thoroughly cleaned with air and water prior
to receiving shotcrete.
1913A.8 Damage. In-place shotcrete that exhibits sags,
sloughs, segregation, honeycombing, sand pockets or other
obvious defects shall be removed and replaced. Shotcrete
above sags and sloughs shall be removed and replaced while
still plastic.
1913A.9 Curing. During the curing periods specified herein,
shotcrete shall be maintained above 40°F (4°C) and in moist
condition.
1913A.9.1 Initial curing. Shotcrete shall be kept continu-
ously moist for 24 hours after shotcreting is complete or
shall be sealed with an approved curing compound.
1913A.9.2 Final curing. Final curing shall continue for
seven days after shotcreting, or for three days if high-
264
2010 CALIFORNIA BUILDING CODE
CONCRETE
early-Strength cement is used, or until the specified strength
is obtained. Final curing shall consist of the initial curing
process or the shotcrete shall be covered with an approved
moisture-retaining cover.
1913A.9.3 Natural curing. Natural curing shall not be used
in lieu of that specified in this section unless the relative
humidity remains at or above 85 percent, and is authorized
by the registered design professional and approved by the
building official.
1913A.10 Strength tests. Strength tests for shotcrete shall be
made in accordance with ASTM standards by an approved
agency on specimens that are representative of the work and
which have been water soaked for at least 24 hours prior to test-
ing. When the maximum-size aggregate is larger than Vg inch
(9.5 mm), specimens shall consist of not less than three
3-inch-diameter (76 nmi) cores or 3-inch (76 mm) cubes.
When the maximum-size aggregate is Vg inch (9.5 mm) or
smaller, specimens shall consist of not less than 2-inch-diame-
ter (51 mm) cores or 2-inch (51 mm) cubes.
1913A.10.1 Sampling. Specimens shall be taken from the
in-place work or from test panels, and shall be taken at least
once each shift, but not less than one for each 50 cubic yards
(38.2 m^) of shotcrete.
1913A,10.2 Panel criteria. When the maximum-size
aggregate is larger than Vg inch (9.5 mm), the test panels
shall have minimum dimensions of 18 inches by 18 inches
(457 mm by 457 mm). When the maximum size aggregate is
^/g inch (9.5 mm) or smaller, the test panels shall have mini-
mum dimensions of 12 inches by 12 inches (305 mm by 305
mm). Panels shall be shot in the same position as the work,
during the course of the work and by the nozzlemen doing
the work. The conditions under which the panels are cured
shall be the same as the work. Approval from the enforce-
ment agency shall be obtained prior to performing the test
panel method.
1913A.10.3 Acceptance criteria. The average compressive
strength of three cores from the in-place work or a single test
panel shall equal or exceed 0.85/'^ with no single core less
than 0.75 / \. The average compressive strength of three
cubes taken from the in-place work or a single test panel
shall equal or exceed /'^ with no individual cube less than
0.88/'^. To check accuracy, locations represented by erratic
core or cube strengths shall be retested.
1913AJ1 Forms and ground wires for shotcrete. Forms for
shotcrete shall be substantial and rigid. Forms shall be built
and placed so as to permit the escape of air and rebound.
Adequate ground wires, which are to be used as screeds,
shall be placed to establish the thickness, surface planes and
form of the shotcrete work. All surfaces shall be rodded to these
wires.
1913AA2 Placing, Shotcrete shall be placed in accordance
with ACI 506.
SECTION 191 44
REINFORCED GYPSUM CONCRETE
1914A.1 General. Reinforced gypsum concrete shall comply
with the requirements of ASTM C 3 17 and ASTM C 956. Rein-
forced gypsum concrete shall be considered as an alternative
system.
1914A.2 Minimum thickness. The minimum thickness of
reinforced gypsum concrete shall be 2 inches (51 mm) except
the minimum required thickness shall be reduced to 1 Vj inches
(38 mm), provided the following conditions are satisfied:
1. The overall thickness, including the formboard, is not
less than 2 inches (51 mm).
2. The clear span of the gypsum concrete between supports
does not exceed 33 inches (838 mm).
3. Diaphragm action is not required.
4. The design live load does not exceed 40 pounds per
square foot (psf) (1915A Pa).
SECTION 1 91 5i4
CONCRETE-FILLED PIPE COLUMNS
1915A.1 General. Concrete-filled pipe columns shall be man-
ufactured from standard, extra-strong or double-extra-strong
steel pipe or tubing that is filled with concrete so placed and
manipulated as to secure maximum density and to ensure com-
plete filling of the pipe without voids.
1915A.2 Design. The safe supporting capacity of con-
crete-filled pipe columns shall be computed in accordance with
the approved rules or as determined by a test.
1915A.3 Connections. Caps, baseplates and connections shall
be of approved types and shall be positively attached to the
shell and anchored to the concrete core. Welding of brackets
without mechanical anchorage shall be prohibited. Where the
pipe is slotted to accommodate webs of brackets or other con-
nections, the integrity of the shell shall be restored by welding
to ensure hooping action of the composite section.
1915A.4 Reinforcement. To increase the safe load-supporting
capacity of concrete-filled pipe columns, the steel reinforce-
ment shall be in the form of rods, structural shapes or pipe
embedded in the concrete core with sufficient clearance to
ensure the composite action of the section, but not nearer than 1
inch (25 mm) to the exterior steel shell. Structural shapes used
as reinforcement shall be milled to ensure bearing on cap and
base plates.
1915A.5 Fire-resistance-rating protection. Pipe columns
shall be of such size or so protected as to develop the required
fire-resistance ratings specified in Table 601. Where an outer
steel shell is used to enclose the fire protective covering, the
shell shall not be included in the calculations for strength of the
column section. The minimum diameter of pipe columns shall
be 4 inches (102 mm) except that in structures of Type V con-
struction not exceeding three stories above grade plane or 40
feet (12 192 mm) in building height, pipe columns used in
basements and as secondary steel members shall have a mini-
mum diameter of 3 inches (76 mm).
2010 CALIFORNIA BUILDING CODE
265
CONCRETE
1915A.6 Approvals. Details of column connections and
splices shall be shop fabricated by approved methods and shall
be approved only after tests in accordance with the approved
rules. Shop-fabricated concrete-filled pipe columns shall be
inspected by the building official or by an approved vepTQStntSi-
tive of the manufacturer at the plant.
SECTION 1916A
CONCRETE, REINFORCEMENT
AND ANCHOR TESTING
1916 A.l Cementitious material The concrete supplier shall
furnish to the enforcement agency certification that the cement
proposed for use on the project has been manufactured and
tested in compliance with the requirements ofASTM C 150 for
Portland cement andASTM C 595 orASTM C 11 57 for blended
hydraulic cement, whichever is applicable. When a mineral
admixture or ground granulated blast-furnace slag is proposed
for use, the concrete supplier shall furnish to the enforcement
agency certification that they have been manufactured and
tested in compliance with ASTM C618 orASTM C 989, which-
ever is applicable,. The concrete producer shall provide copies
of the cementitious material supplier's Certificate of Compli-
ance that represents the materials used by date of shipment for
concrete. Cementitious materials without Certification of
Compliance shall not be used.
1916A.2 Tests of reinforcing bars. Where samples are taken
from bundles as delivered from the mill, with the bundles identi-
fied as to heat number and provided the mill analyses accom-
pany the report, one tensile test and one bend test shall be made
from a specimen from each 10 tons (9080 kg) or fraction thereof
of each size of reinforcing steel
Where positive identification of the heat number cannot be
made or where random samples are to be taken, one series of
tests shall be made from each 2^/2 tons (2270 kg) or fraction
> thereof of each size of reinforcing steel
Tests of reinforcing bars may be waived by the structural
engineer with the approval of the Building Official for
one-story buildings, provided certified mill test reports are pro-
vided for each shipment of such reinforcement,
19I6A.3 Tests for prestressing steel and anchorage. All wires
or bars of each size from each mill heat and all strands from
each manufactured reel to be shipped to the site shall be
assigned an individual lot number and shall be tagged in such a
manner that each lot can be accurately identified at thejobsite.
Each lot of tendon and anchorage assemblies and bar couplers
to be installed shall be likewise identified.
The following samples of materials and tendons selected by
the engineer or the designated testing laboratory from the
prestressing steel at the plant or jobsite shall be furnished by
the contractor and tested by an approved independent testing
agency:
1. For wire, strand or bars, 7-foot-long (2134 mm) samples
shall be taken of the coil of wire or strand reel or rods, A
minimum of one random sample per 5,000 pounds (2270
kg) of each heat or lot used on the job shall be selected.
2. For prefabricated prestressing tendons other than bars,
one completely fabricated tendon 10 feet (3048 mm) in
length between grips with anchorage assembly at one
end shall be furnished for each size and type of tendon
and anchorage assembly.
Variations of the bearing plate size need not be con-
sidered.
The anchorages of unbonded tendons shall develop at
least 95 percent of the minimum specified ultimate
strength of the prestressing steel. The total elongation of
the tendon under ultimate load shall not be less than 2
percent measured in a minimum gage length of 10 feet
(3048 mm).
Anchorages of bonded tendons shall develop at least
90 percent of the minimum specified strength of the
prestressing steel tested in an unbonded state. All cou-
plings shall develop at least 95 percent of the minimum
specified strength of the prestressing steel and shall not
reduce the elongation at rupture below the requirements
of the tendon itself
3. If the prestressing tendon is a bar, one 7 -foot (2134 mm)
length complete with one end anchorage shall be fur-
nished and, in addition, if couplers are to be used with
the bar, two 4-foot (1219 mm) lengths of bar fabricated
to fit and equipped with one coupler shall be furnished,
4. Mill tests of materials used for end anchorages shall be
furnished. In addition, at least one Brinnell hardness test
shall be made of each thickness of bearing plate, ^
1916 A.4 Composite construction cores. Cores of the com-
pleted composite concrete construction shall be taken to dem-
onstrate the shear strength along the contact surfaces. The
cores shall be tested when the cast-in-place concrete is approx-
imately 28 days old and shall be tested by a shear loading par-
allel to the joint between the precast concrete and the
cast-in-place concrete. The minimum unit shear strength of the
contact surface area of the core shall not be less than 100 psi
(689 kPa).
At least one core shall be taken from each building for each
5,000 square feet (465 m^j of area of composite concrete con-
struction and not less than three cores shall be taken from each
project. The architect or structural engineer in responsible
charge of the project or his or her representative shall desig-
nate the location for sampling,
1916A.5 Tests ofshotcrete. Testing ofshotcrete shall follow the
provisions of Section 191 3 A and the general requirements of
ACl 318 Section 5.6,
1916A.6 Gypsum field tests. Field tests shall be made during
construction to verify gypsum strength. One sample consisting
of three specimens shall be made for each 5,000 square feet
(465 m^) or fraction thereof of all gypsum poured, but not less
than one sample shall be taken from each half day's pour,
I9I6A.7 Tests for post-installed anchors in concrete. When
post-installed anchors are used in lieu of cast-in place bolts, <
the installation verification test loads, frequency and accep-
tance criteria shall be in accordance with this section.
266
2010 CALIFORNIA BUILDING CODE
CONCRETE
1916 A J, 1 General Test loads or torques and acceptance
criteria shall be shown on the construction documents.
If any anchor fails testing, all anchors of the same type
shall be tested, which are installed by the same trade, not
previously tested until twenty (20) consecutive anchors
pass, then resume the initial test frequency,
1916 A,7, 2 Test loads. Required test loads shall be deter-
mined by one of the following methods:
L Twice the maximum allowable tension load or one
and a quarter (V/4) times the maximum design
strength of anchors as provided in International Code
Council - Evaluation Service Report (ICC-ESR) or
determined in accordance with Appendix D of ACI
318.
Tension test load need not exceed 80 percent of the
nominal yield strength of the anchor element (=0.8
2. The manufacturer's recommended installation
torque as approved in an ICC-ESR.
1916A.7,3 Test frequency. When post-installed anchors are
used for sill plate bolting applications, 10 percent of the
> anchors shall be tested.
I I When post-installed anchors are used for other structural
> applications, all such anchors shall be tested.
1 1 I When post-installed anchors are used for nonstructural
applications such as equipment anchorage, 50 percent or
alternate bolts in a group, including at least one-half the
anchors in each group, shall be tested.
> I I The testing of the post-installed anchors shall be done in
the presence of the special inspector and a report of the test
> results shall be submitted to the enforcement agency.
Exceptions:
1. Undercut anchors that allow visual confirmation
of full set shall not require testing.
2. Where the factored design tension on anchors is
less than 100 lb and those anchors are clearly
noted on the approved construction documents,
only 10 percent of those anchors shall be tested.
3. Where adhesive anchor systems are used to install
reinforcing dowel bars in hardened concrete, only
25 percent of the dowels shall be tested if all of the
following conditions are met:
a. The dowels are used exclusively to transmit
shear forces across joints between existing
and new concrete.
b. The number of dowels in any one member
equals or exceeds 12.
c. The dowels are uniformly distributed across
seismic force resisting members (such as
shear walls, collectors and diaphragms).
Anchors to be tested shall be selected at
random by the special inspector/inspector of
record (lOR).
4. Testing of shear dowels across cold joints in slabs
on grade, where the slab is not part of the lateral
force-resisting system shall not be required.
5. Testing is not required for power actuated fasten-
ers used to attach tracks of interior non-shear wall
partitions for shear only, where there are at least
three fasteners per segment of track.
1916AJ,4 Test acceptance criteria. Acceptance criteria for
post-installed anchors shall be based on ICC-ESR or manu-
facturers written instruction, acceptable to the enforcement
agency. Field test shall satisfy following minimum require-
ments.
1. Hydraulic ram method:
Anchors tested with a hydraulic jack or spring loaded
devices shall maintain the test load for a minimum of
15 seconds and shall exhibit no discemable move-
ment during the tension test, e.g., as evidenced by
loosening of the washer under the nut.
For adhesive anchors, where other than bond is being
tested, the testing device shall not restrict the concrete
shear cone type failure mechanism from occurring.
2. Torque wrench method:
Anchors tested with a calibrated torque wrench must
attain the specified torque within V2 turn of the nut.
Exceptions:
a. Wedge or sleeve type:
One-quarter fVJ turn of the nut for a % in.
sleeve anchor only.
b. Threaded type:
One-quarter fVJ turn of the screw after ini-
tial seating of the screw head.
1916A.7,5 Testing procedure. Test procedure shall be as
required by the ICC-ESR. Manufacturer's recommendation
for testing may be approved by the enforcement agency,
when ICC-ESR does not provide a testing procedure.
SECTION 1917A
EXISTING CONCRETE STRUCTURES
1917 A.1, Existing concrete structures.
The structural use of existing concrete with a core strength less
than 1,500 psi (lO.SMPa) is not permitted in rehabilitation
work.
For existing concrete structures, sufficient cores shall be
taken at representative locations throughout the structure, as
designated by the architect or structural engineer, so that
knowledge will be had of the in-place strength of the concrete.
At least three cores shall be taken from each building for each
4,000 square feet (372 m^) of floor area, or fraction thereof.
Cores shall be at least 4 inches (102 mm) in diameter. Cores as
small as 2. 75 inches (70 mm) in diameter may be allowed by the
enforcement agency when reinforcement is closely spaced and
the coarse aggregate does not exceed V^ inch (19 mm).
2010 CALIFORNIA BUILDING CODE
267
CONCRETE
1917A.2 Crack repair by epoxy injection. [OSHPD 1 & 4]
Crack repair by epoxy injection of concrete and masonry mem-
ber shall conform to all requirements ofACI 503, 7.
1917 A3 Concrete strengthening by externally bonded fiber
reinforced polymer (FRP), Design and construction of exter-
nally bonded FRP systems for strengthening concrete struc-
tures shall be in accordance with ACI 440.2R,
Exceptions:
1) Near-Surface Mounted (NSM) FRP bars shall not be
permitted,
2) Strengthening of shear walls and diaphragms
(including chords and collectors) shall be considered
as an alternative system.
Design capacities y reliability, serviceability of FRP materi-
als shall be permitted to be established in accordance with
ICC-ES AC 125, Minimum inspection requirements of FRP
composite systems shall be in accordance with ICC-ES AC
178,
268 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 20 - ALUMINUM
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
2003
X
X
2003.1
X
X
2010 CALIFORNIA BUILDING CODE
269
270 201 CALIFORNIA BUILDING CODE
CHAPTER 20
ALUMINUM
SECTION 2001
GENERAL
2001.1 Scope. This chapter shall govern the quality, design,
fabrication and erection of aluminum.
SECTION 2002
MATERIALS
2002.1 General. Aluminum used for structural purposes in
buildings and structures shall comply with AA ASM 35 and
AA ADM 1. The nominal loads shall be the minimum design
loads required by Chapter 16.
SECTION 2003
INSPECTION
2003.1 Inspection. [DSA-SS, DSA-SS/CC, OSHPD 1 & 4]
Inspection of aluminum shall be required in accordance with
the requirements for steel in Chapter 17A.
2010 CALIFORNIA BUILDING CODE 271
272 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 21 - MASONRY
Adopting agency
BSC
SFM
HCD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
—
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
Adopt only those sections that
are listed below
X
Chapter/Section
X
2101.1.1
2101.1.2
X
2101.1.3
X
2101.1.4
X
2113.9.1
X
2114.1
X
2114.2
X
2114.3
X
2114.4
X
2114.5
X
2114.6.1
X
2114.6.2
X
2114.7
X
2114.8
X
2114.9.1
X
2114.9.2.1
X
2114.9.2.2
X
2114.9.3
X
2114.10
X
2114.11.1
X
2114.11.2
X
2114.11.3
X
2114.12
X
2114.13
X
2114.14
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section l.Il.
2010 CALIFORNIA BUILDING CODE
273
274 2010 CALIFORNIA BUILDING CODE
CHAPTER 21
MASONRY
t
SECTION 2101
GENERAL
2101.1 Scope. This chapter shall govern the materials, design,
construction and quality of masonry.
2101.1 A Division of the State Architect-Structural Safety/
Community Colleges (DSA-SS/CC) - Application, The
scope of application of Chapter 21 is as follows:
Community college buildings regulated by the Division
of the State Architect-Structural Safety/Community Col-
leges (DSA-SS/CC) as listed in Section 1.9.2.2.
2101.1.2 Amendments in this chapter, DSA-SS/CC adopts
this chapter and all amendments.
Exception: Division of the State Architect- Structural
Safety/Community Colleges (DSA-SS/CC) amendments
appear in this chapter preceded with the appropriate
acronym, as follows:
(Division of the State Architect- Structural Safety/
Community Colleges:
[DSA-SS/CC] - For community college buildings
listed in Section 1.9.2.2.
2101.1.3 Reference to other chapters, [DSA-SS/CC]
Where reference within this chapter is made to sections in
Chapters 17 and 18, the provisions in Chapters 17 A and
ISA respectively shall apply instead.
2101.1.4 Amendments, [DSA-SS/CC] See Section 21 14 for
additional requirements.
2101.2 Design methods. Masonry shall comply with the pro-
visions of one of the following design methods in this chapter
as well as the requirements of Sections 2101 through 2104.
Masonry designed by the allowable stress design provisions of
Section 2101.2.1, the strength design provisions of Section
2101.2.2 or the prestressed masonry provisions of Section
2101.2.3 shall comply with Section 2105.
2101.2.1 Allowable stress design. Masonry designed by
the allowable stress design method shall comply with the
provisions of Sections 2106 and 2107.
2101.2.2 Strength design. Masonry designed by the
strength design method shall comply with the provisions of
Sections 2106 and 2108, except that autoclaved aerated con-
crete (AAC) masonry shall comply with the provisions of
Section 2106, Section 1613.6.4 and Chapter 1 and Appen-
dix A of TMS 402/ACI 530/ASCE 5.
2101.2.3 Prestressed masonry. Prestressed masonry shall
be designed in accordance with Chapters 1 and 4 of TMS
402/ACI 530/ASCE 5 and Section 2106. Special inspection
during construction shall be provided as set forth in Section
1704.5.
2101.2.4 Empirical design. Masonry designed by the
empirical design method shall comply with the provisions
of Sections 2106 and 2109 or Chapter 5 of TMS 402/ACI
530/ASCE 5.
2101.2.5 Glass unit masonry. Glass unit masonry shall
comply with the provisions of Section 2110 or Chapter 7 of
TMS 402/ACI 530/ASCE 5.
2101.2.6 Masonry veneer. Masonry veneer shall comply
with the provisions of Chapter 14 or Chapter 6 of TMS
402/ACI 530/ASCE 5.
2101,3 Construction documents. The construction docu-
ments shall show all of the items required by this code includ-
ing the following:
1. Specified size, grade, type and location of reinforce-
ment, anchors and wall ties.
2. Reinforcing bars to be welded and welding procedure.
3. Size and location of structural elements.
4. Provisions for dimensional changes resulting from elas-
tic deformation, creep, shrinkage, temperature and mois-
ture.
5. Loads used in the design of masonry.
6. Specified compressive strength of masonry at stated ages
or stages of construction for which masonry is designed,
except where specifically exempted by this code.
7. Details of anchorage of masonry to structural members,
frames and other construction, including the type, size
and location of connectors.
8. Size and location of conduits, pipes and sleeves.
9. The minimum level of testing and inspection as defined
in Chapter 17, or an itemized testing and inspection pro-
gram that meets or exceeds the requirements of Chapter
17.
2101.3.1 Fireplace drawings. The construction documents
shall describe in sufficient detail the location, size and con-
struction of masonry fireplaces. The thickness and charac-
teristics of materials and the clearances from walls,
partitions and ceilings shall be indicated.
SECTION 2102
DEFINITIONS AND NOTATIONS
2102.1 General. The following words and terms shall, for the
purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
AAC MASONRY. Masonry made of autoclaved aerated con-
crete (AAC) units, manufactured without internal reinforce-
ment and bonded together using thin- or thick-bed mortar.
ADOBE CONSTRUCTION. Construction in which the exte-
rior load-bearing and nonload-bearing walls and partitions are
of unfired clay masonry units, and floors, roofs and interior
2010 CALIFORNIA BUILDING CODE
275
MASONRY
framing are wholly or partly of wood or other approved materi-
als,
Adobe, stabilized. Unfired clay masomy units to which
admixtures, such as emulsified asphalt, are added during the
manufacturing process to limit the units' water absorption
so as to increase their durability.
Adobe, unstabilized. Unfired clay masonry units that do
not meet the definition of "Adobe, stabihzed."
ANCHOR. Metal rod, wire or strap that secures masonry to its
structural support.
ARCHITECTURAL TERRA COTTA. Plain or ornamental
hard-burned modified clay units, larger in size than brick, with
glazed or unglazed ceramic finish.
AREA.
Bedded. The area of the surface of a masonry unit that is in
contact with mortar in the plane of the joint.
Gross cross-sectional. The area delineated by the out-
to-out specified dimensions of masonry in the plane under
consideration.
Net cross-sectional. The area of masonry units, grout and
mortar crossed by the plane under consideration based on
out-to-out specified dimensions.
AUTOCLAVED AERATED CONCRETE (AAC). Low
density cementitious product of calcium silicate hydrates,
whose material specifications are defined in ASTM C 1386.
BED JOINT. The horizontal layer of mortar on which a
masonry unit is laid.
BOND BEAM. A horizontal grouted element within masonry
in which reinforcement is embedded.
BRICK.
Calcium silicate (sand lime brick). A masonry unit made
of sand and lime.
Clay or shale. A masonry unit made of clay or shale, usu-
ally formed into a rectangular prism while in the plastic state
and burned or fired in a kiln.
Concrete. A masonry unit having the approximate shape of
a rectangular prism and composed of inert aggregate parti-
cles embedded in a hardened cementitious matrix.
CAST STONE. A building stone manufactured from portland
cement concrete precast and used as a trim, veneer or facing on
or in buildings or structures.
CELL. A void space having a gross cross-sectional area
greater than 1 V2 square inches (967 mm^).
CHIMNEY. A primarily vertical enclosure containing one or
more passageways for conveying flue gases to the outside
atmosphere.
CHIMNEY TYPES.
High-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
high-heat appliances producing combustion gases in excess
of 2,000T (1093X) measured at the appliance flue outlet
(see Section 2113.11.3).
Lov»^-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
low-heat appliances producing combustion gases not in
excess of 1,000°F (538°C) under normal operating condi-
tions, but capable of producing combustion gases of
1,400°F (760°C) during intermittent forces firing for peri-
ods up to 1 hour. Temperatures shall be measured at the
appliance flue outlet.
Masonry type. A field-constructed chimney of solid
masonry units or stones.
Medium-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
medium-heat appliances producing combustion gases not
exceeding 2,000°F (1093°C) measured at the appliance flue
outlet (see Section 21 13.11.2).
CLEANOUT. An opening to the bottom of a grout space of
sufficient size and spacing to allow the removal of debris.
COLLAR JOINT. Vertical longitudinal joint between wythes
of masonry or between masonry and backup construction that
is permitted to be filled with mortar or grout. ^
COMPRESSIVE STRENGTH OF MASONRY. Maximum
compressive force resisted per unit of net cross-sectional area
of masonry, determined by the testing of masonry prisms or a
function of individual masonry units, mortar and grout.
CONNECTOR. A mechanical device for securing two or
more pieces, parts or members together, including anchors,
wall ties and fasteners.
COVER. Distance between surface of reinforcing bar and
edge of member. ^
DIMENSIONS.
Actual. The measured dimension of a masonry unit or ele-
ment.
Nominal. The specified dimension plus an allowance for
the joints with which the units are to be laid. Thickness is
given first, followed by height and then length.
Specified. The dimensions specified for the manufacture or
construction of masonry, masonry units, joints or any other
component of a structure. ^
FIREPLACE. A hearth and fire chamber or similar prepared
place in which a fire may be made and which is built in con-
junction with a chimney.
FIREPLACE THROAT. The opening between the top of the
firebox and the smoke chamber.
FOUNDATION PIER. An isolated vertical foundation mem-
ber whose horizontal dimension measured at right angles to its
thickness does not exceed three times its thickness and whose
height is equal to or less than four times its thickness.
GROUTED MASONRY.
Grouted hollow-unit masonry. That form of grouted
masonry construction in which certain designated cells of
hollow units are continuously filled with grout.
276
2010 CALIFORNIA BUILDING CODE
MASONRY
Grouted multiwythe masonry. That form of grouted
masonry construction in which the space between the
wythes is solidly or periodically filled with grout.
HEAD JOINT. Vertical mortar joint placed between masonry
units within the wythe at the time the masonry units are laid.
HEIGHT, WALLS. The vertical distance from the foundation
wall or other immediate support of such wall to the top of the
wall.
MASONRY. A built-up construction or combination of build-
ing units or materials of clay, shale, concrete, glass, gypsum,
stone or other approved units bonded together with or without
mortar or grout or other accepted methods of joining.
Ashlar masonry. Masonry composed of various-sized rect-
angular units having sawed, dressed or squared bed sur-
faces, properly bonded and laid in mortar.
Coursed ashlar. Ashlar masonry laid in courses of stone of
equal height for each course, although different courses
shall be permitted to be of varying height.
Glass unit masonry. Masonry composed of glass units
bonded by mortar.
Plain masonry. Masonry in which the tensile resistance of
the masonry is taken into consideration and the effects of
stresses in reinforcement are neglected.
Random ashlar. Ashlar masonry laid in courses of stone set
without continuous joints and laid up without drawn pat-
terns. When composed of material cut into modular heights,
discontinuous but aligned horizontal joints are discernible.
Reinforced masonry. Masonry construction in which rein-
forcement acting in conjunction with the masonry is used to
resist forces.
Solid masonry. Masonry consisting of solid masonry units
laid contiguously with the joints between the units filled
with mortar.
Unreinforced (plain) masonry. Masonry in which the ten-
sile resistance of masonry is taken into consideration and
the resistance of the reinforcing steel, if present, is
neglected.
MASONRY UNIT. Brick, tile, stone, glass block or concrete
block conforming to the requirements specified in Section
2103.
Clay. A building unit larger in size than a brick, composed
of burned clay, shale, fired clay or mixtures thereof.
Concrete. A building unit or block larger in size than 12
inches by 4 inches by 4 inches (305 mm by 102 mm by 102
mm) made of cement and suitable aggregates.
Hollow. A masonry unit whose net cross-sectional area in
any plane parallel to the load-bearing surface is less than 75
percent of its gross cross-sectional area measured in the
same plane.
Solid. A masonry unit whose net cross-sectional area in
every plane parallel to the load-bearing surface is 75 percent
or more of its gross cross-sectional area measured in the
same plane.
MORTAR. A plastic mixture of approved cementitious mate-
rials, fine aggregates and water used to bond masonry or other
structural units.
MORTAR, SURFACE-BONDING. A mixture to bond con-
crete masonry units that contains hydraulic cement, glass fiber
reinforcement with or without inorganic fillers or organic mod-
ifiers and water.
PRESTRESSED MASONRY. Masonry in which internal
stresses have been introduced to counteract potential tensile
stresses in masonry resulfing from applied loads.
PRISM. An assemblage of masonry units and mortar with or
without grout used as a test specimen for determining proper-
ties of the masonry.
RUBBLE MASONRY. Masonry composed of roughly
shaped stones.
Coursed rubble. Masonry composed of roughly shaped
stones fitting approximately on level beds and well bonded.
Random rubble. Masonry composed of roughly shaped
stones laid without regularity of coursing but well bonded
and fitted together to form well-divided joints.
Rough or ordinary rubble. Masonry composed of
unsquared field stones laid without regularity of coursing
but well bonded.
RUNNING BOND. The placement of masonry units such that
head joints in successive courses are horizontally offset at least
one-quarter the unit length.
SHEAR WALL.
Detailed plain masonry shear wall. A masonry shear wall
designed to resist lateral forces neglecting stresses in rein-
forcement, and designed in accordance with Section
2106.1.
Intermediate prestressed masonry shear wall. A pre-
stressed masonry shear wall designed to resist lateral forces
considering stresses in reinforcement, and designed in
accordance with Section 2106. L
Intermediate reinforced masonry shear wall. A masonry
shear wall designed to resist lateral forces considering
stresses in reinforcement, and designed in accordance with
Section 2106.1.
Ordinary plain masonry shear wall. A masonry shear
wall designed to resist lateral forces neglecting stresses in
reinforcement, and designed in accordance with Section
2106.1.
Ordinary plain prestressed masonry shear wall. A pre-
stressed masonry shear wall designed to resist lateral forces
considering stresses in reinforcement, and designed in
accordance with Section 2106.1,
Ordinary reinforced masonry shear wall. A masonry
shear wall designed to resist lateral forces considering
stresses in reinforcement, and designed in accordance with
Section 2106.1.
Special prestressed masonry shear wall. A prestressed
masonry shear wall designed to resist lateral forces consid-
ering stresses in reinforcement and designed in accordance
2010 CALIFORNIA BUILDING CODE
277
MASONRY
with Section 2106.1 except that only grouted, laterally
restrained tendons are used.
Special reinforced masonry shear wall. A masonry shear
wall designed to resist lateral forces considering stresses in
reinforcement, and designed in accordance with Section
2106.1.
SHELL. The outer portion of a hollow masonry unit as placed
in masonry.
SPECIFIED. Required by construction documents.
SPECIFIED COMPRESSIVE STRENGTH OF
MASONRY,/'^. Minimum compressive strength, expressed
as force per unit of net cross-sectional area, required of the
masonry used in construction by the construction documents,
and upon which the project design is based. Whenever the
quantity/'^ is under the radical sign, the square root of numeri-
cal value only is intended and the result has units of pounds per
square inch (psi) (MPa).
STACK BOND. The placement of masonry units in a bond
pattern is such that head joints in successive courses are verti-
cally aUgned. For the purpose of this code, requirements for
stack bond shall apply to masonry laid in other than running
bond.
STONE MASONRY. Masonry composed of field, quarried or
cast stone units bonded by mortar.
Ashlar stone masonry. Stone masonry composed of rect-
angular units having sawed, dressed or squared bed surfaces
and bonded by mortar.
Rubble stone masonry. Stone masonry composed of irreg-
ular-shaped units bonded by mortar.
STRENGTH.
Design strength. Nominal strength multiplied by a strength
reduction factor.
Nominal strength. Strength of a member or cross section
calculated in accordance with these provisions before appU-
cation of any strength-reduction factors.
Required strength. Strength of a member or cross section
required to resist factored loads.
THIN-BED MORTAR. Mortar for use in construction of
AAC unit masonry with joints 0.06 inch (1.5 mm) or less.
TIE, LATERAL. Loop of reinforcing bar or wire enclosing
longitudinal reinforcement.
TIE, WALL. A connector that connects wythes of masonry
walls together.
TILE. A ceramic surface unit, usually relatively thin in relation
to facial area, made from clay or a mixture of clay or other
ceramic materials, called the body of the tile, having either a
"glazed" or "unglazed" face and fired above red heat in the
course of manufacture to a temperature sufficiently high
enough to produce specific physical properties and characteris-
tics.
TILE, STRUCTURAL CLAY. A hollow masonry unit com-
posed of burned clay, shale, fire clay or mixture thereof, and
having parallel cells.
WALL. A vertical element with a horizontal length-to-thick-
ness ratio greater than three, used to enclose space.
Cavity wall. A wall built of masonry units or of concrete, or
a combination of these materials, arranged to provide an air-
space within the wall, and in which the inner and outer parts
of the wall are tied together with metal ties.
Composite wall. A wall built of a combination of two or
more masonry units bonded together, one forming the
backup and the other forming the facing elements.
Dry-stacked, surface-bonded wall. A wall built of con-
crete masonry units where the units are stacked dry, without
mortar on the bed or head joints, and where both sides of the
wall are coated with a surface-bonding mortar.
Masonry-bonded hollow wall. A wall built of masonry
units so arranged as to provide an airspace within the wall,
and in which the facing and backing of the wall are bonded
together with masonry units.
Parapet wall. The part of any wall entirely above the roof
line.
WEB. An interior solid portion of a hollow masonry unit as
placed in masonry.
WYTHE. Each continuous, vertical section of a wall, one
masonry unit in thickness.
NOTATIONS. ^
df, = Diameter of reinforcement, inches (mm).
F^ = Allowable tensile or compressive stress in reinforce-
ment, psi (MPa).
f^ = Modulus of rupture, psi (MPa). .
/mc = Specified compressive strength of AAC masonry, the
minimum compressive strength for a class of AAC
masonry as specified in ASTM C 1386, psi (MPa).
f'^ = Specified compressive strength of masonry at age of 28
days, psi (MPa).
f'mi = Specified compressive strength of masonry at the time
of prestress transfer, psi (MPa).
K = The lesser of the masonry cover, clear spacing between
adjacent reinforcement, or five times J^, inches (mm).
L^ = Distance between supports, inches (mm). .
/j = Required development length or lap length of rein-
forcement, inches (mm). .
P = The applied load at failure, pounds (N).
Sf = Thickness of the test specimen measured parallel to the
direction of load, inches (mm).
S^ = Width of the test specimen measured parallel to the
loading cyHnder, inches (mm).
SECTION 2103
MASONRY CONSTRUCTION MATERIALS
2103.1 Concrete masonry units. Concrete masonry units
shall conform to the following standards: ASTM C 55 for con-
crete brick; ASTM C 73 for calcium silicate face brick; ASTM
278
2010 CALIFORNIA BUILDING CODE
MASONRY
C 90 for load-bearing concrete masonry units or ASTM C 744
for prefaced concrete and calcium silicate masonry units.
2103.2 Clay or shale masonry units. Clay or shale masonry
units shall conform to the following standards: ASTM C 34 for
structural clay load-bearing wall tile; ASTM C 56 for struc-
tural clay nonload-bearing wall tile; ASTM C 62 for building
brick (solid masonry units made from clay or shale); ASTM C
1088 for solid units of thin veneer brick; ASTM C 126 for
ceramic-glazed structural clay facing tile, facing brick and
solid masonry units; ASTM C 212 for structural clay facing
tile; ASTM C 216 for facing brick (solid masonry units made
from clay or shale); ASTM C 652 for hollow brick (hollow
masonry units made from clay or shale) or ASTM C 1405 for
glazed brick (single-fired soHd brick units).
Exception: Structural clay tile for nonstructural use in fire-
proofmg of structural members and in wall furring shall not
be required to meet the compressive strength specifications.
The fire-resistance rating shall be determined in accordance
with ASTM E 119 or UL 263 and shall comply with the
requirements of Table 602.
2103.3 AAC masonry. AAC masonry units shall conform to
ASTM C 1386 for the strength class specified.
2103.4 Stone masonry units. Stone masonry units shall con-
form to the following standards: ASTM C 503 for marble
building stone (exterior); ASTM C 568 for limestone building
stone; ASTM C 615 for granite building stone; ASTM C 616
for sandstone building stone; or ASTM C 629 for slate building
stone.
2103.5 Ceramic tile. Ceramic tile shall be as defined in, and
shall conform to the requirements of, ANSI A137.1.
2103.6 Glass unit masonry. Hollow glass units shall be par-
tially evacuated and have a minimum average glass face thick-
ness of V,6 inch (4.8 mm). Solid glass-block units shall be
provided when required. The surfaces of units intended to be in
contact with mortar shall be treated with a polyvinyl butyral
coating or latex-based paint. Reclaimed units shall not be used.
2103.7 Second-hand units. Second-hand masonry units shall
not be reused unless they conform to the requirements of new
units. The units shall be of whole, sound materials and free
from cracks and other defects that will interfere with proper
laying or use. Old mortar shall be cleaned from the unit before
reuse.
2103.8 Mortar. Mortar for use in masonry construction shall
conform to ASTM C 270 and Articles 2.1 and 2.6 A of TMS
602/ ACI 530.1/ASCE 6, except for mortars listed in Sections
2103.9, 2103.10 and 2103.1 1. Type S or N mortar conforming
to ASTM C 270 shall be used for glass unit masonry.
2103.9 Surface-bonding mortar. Surface-bonding mortar
shall comply with ASTM C 887. Surface bonding of concrete
masonry units shall comply with ASTM C 946.
2103.10 Mortars for ceramic wall and floor tile. Portland
cement mortars for installing ceramic wall and floor tile shall
comply with ANSI A108.1A and ANSI A108.1B and be of the
compositions indicated in Table 2103.10.
TABLE 2103.10
CERAMIC TILE MORTAR COMPOSITIONS
LOCATION
MORTAR
COMPOSITION
Walls
Scratchcoat
1 cement; V5 hydrated lime;
4 dry or 5 damp sand
Setting bed and
leveling coat
1 cement; V2 hydrated lime;
5 damp sand to 1 cement
1 hydrated lime, 7 damp sand
Floors
Setting bed
1 cement; V^q hydrated lime;
5 dry or 6 damp sand; or 1
cement; 5 dry or 6 damp sand
Ceilings
Scratchcoat and
sand bed
1 cement; V2 hydrated lime;
2V2 dry sand or 3 damp sand
2103.10.1 Dry-set portland cement mortars. Premixed
prepared portland cement mortars, which require only the
addition of water and are used in the installation of ceramic
tile, shall comply with ANSI A118.1. The shear bond
strength for tile set in such mortar shall be as required in
accordance with ANSI Al 18.1. Tile set in dry-set portland
cement mortar shall be installed in accordance with ANSI
A108.5.
2103.10.2 Latex-modified portland cement mortar.
Latex-modified portland cement thin- set mortars in which
latex is added to dry- set mortar as a replacement for all or
part of the gauging water that are used for the installation of
ceramic tile shall comply with ANSI A118.4. Tile set in
latex-modified portland cement shall be installed in accor-
dance with ANSI A 108. 5.
2103.10.3 Epoxy mortar. Ceramic tile set and grouted with
chemical-resistant epoxy shall comply with ANSI Al 18.3.
Tile set and grouted with epoxy shall be installed in accor-
dance with ANSI A 108.6.
2103.10.4 Furan mortar and grout. Chemical-resistant
furan mortar and grout that are used to install ceramic tile
shall comply with ANSI A 11 8.5. Tile set and grouted with
furan shall be installed in accordance with ANSI A 108.8.
2103.10.5 Modified epoxy-emulsion mortar and grout.
Modified epoxy-emulsion mortar and grout that are used to
install ceramic tile shall comply with ANSI Al 18.8. Tile set
and grouted with modified epoxy-emulsion mortar and
grout shall be installed in accordance with ANSI A 108.9.
2103.10.6 Organic adhesives. Water-resistant organic
adhesives used for the installation of ceramic tile shall com-
ply with ANSI A136.1. The shear bond strength after water
immersion shall not be less than 40 psi (275 kPa) for Type I
adhesive and not less than 20 psi (138 kPa) for Type II adhe-
sive when tested in accordance with ANSI A 136.1. Tile set
in organic adhesives shall be installed in accordance with
ANSI A108.4.
2103.10.7 Portland cement grouts. Portland cement
grouts used for the installation of ceramic tile shall comply
with ANSI A118.6. Portland cement grouts for tile work
shall be installed in accordance with ANSI A108.10.
2010 CALIFORNIA BUILDING CODE
279
MASONRY
2103.11 Mortar for AAC masonry. Thin-bed mortar for AAC
masonry shall comply with Article 2.1 C.l of IMS 602/ACI
530.1/ASCE 6. Mortar used for the leveUng courses of AAC
masonry shall comply with Article 2.1 C.2 of TMS 602/ACI
530.1/ASCE 6.
2103.12 Grout. Grout shall comply with Article 2.2 of TMS
602/ACI 530.1/ASCE 6.
2103.13 Metal reinforcement and accessories. Metal rein-
forcement and accessories shall conform to Article 2.4 of TMS
602/ACI 530.1/ASCE 6. Where unidentified reinforcement is
approved for use, not less than three tension and three bending
tests shall be made on representative specimens of the rein-
forcement from each shipment and grade of reinforcing steel
proposed for use in the work.
SECTION 2104
CONSTRUCTION
2104.1 Masonry construction. Masonry construction shall
comply with the requirements of Sections 2104.1.1 through
2104.4 and with TMS 602/ACI 530.1/ASCE 6.
2104.1.1 Tolerances. Masonry, except masonry veneer,
shall be constructed within the tolerances specified in TMS
602/ACI 530.1/ASCE 6.
2104.1.2 Placing mortar and units. Placement of mortar,
grout, and clay, concrete, glass, and AAC masonry units
shall comply with TMS 602/ACI 530. 1/ASCE 6.
2104.1.3 Installation of wall ties. Wall ties shall be
installed in accordance with TMS 602/ACI 530. 1/ASCE 6.
2104.1.4 Chases and recesses. Chases and recesses shall be
constructed as masonry units are laid. Masonry directly
above chases or recesses wider than 12 inches (305 mm)
shall be supported on lintels.
2104.1.5 Lintels. The design for lintels shall be in accor-
dance with the masonry design provisions of either Section
2107 or 2108.
2104.1.6 Support on wood. Masonry shall not be sup-
ported on wood girders or other forms of wood construction
except as permitted in Section 2304.12.
2104.2 Corbeled masonry. Corbeled masonry shall comply
with the requirements of Section 1.12 of TMS 402/ ACI
530/ASCE 5.
2104.2.1 Molded cornices. Unless structural support and
anchorage are provided to resist the overturning moment,
the center of gravity of projecting masonry or molded cor-
nices shall lie within the middle one-third of the supporting
wall. Terra cotta and metal cornices shall be provided with a
structural frame of approved noncombustible material
anchored in an approved manner.
2104.3 Cold weather construction. The cold weather con-
struction provisions of TMS 602/ACI 530.1/ASCE 6, Article
1.8 C, shall be implemented when the ambient temperature
falls below 40°F (4°C).
2104.4 Hot weather construction. The hot weather construc-
tion provisions of TMS 602/ACI 530.1/ASCE 6, Article 1.8 D,
shall be implemented when the ambient air temperature
exceeds lOOT (37.8°C), or 90T (32.2°C) with a wind velocity
greater than 8 mph (12.9 km/hr).
SECTION 2105
QUALITY ASSURANCE
2105.1 General. A quality assurance program shall be used to
ensure that the constructed masonry is in compliance with the
construction documents.
The quality assurance program shall comply with the
inspection and testing requirements of Chapter 17.
2105.2 Acceptance relative to strength requirements.
2105.2.1 Compliance with / '^ and / '^c* Compressive
strength of masonry shall be considered satisfactory if the
compressive strength of each masonry wythe and grouted
collar joint equals or exceeds the value of/'^ for clay and
concrete masonry and/'^c for AAC masonry. For partially
grouted clay and concrete masonry, the compressive
strength of both the grouted and ungrouted masonry shall
equal or exceed the applicable/'^ . At the time of prestress,
the compressive strength of the masonry shall equal or
exceed/'^,, which shall be less than or equal to/'„.
2105.2.2 Determination of compressive strength. The
compressive strength for each wythe shall be determined by
the unit strength method or by the prism test method as spec-
ified herein.
2105.2.2.1 Unit strength method.
2105.2.2.1.1 Clay masonry. The compressive
strength of masonry shall be determined based on the
strength of the units and the type of mortar specified
using Table 2105.2.2.1.1, provided:
1. Units are sampled and tested to verify compli-
ance with ASTM C 62, ASTM C 216 or ASTM
C 652.
2. Thickness of bed joints does not exceed Vg inch
(15.9 mm).
3 . For grouted masonry, the grout meets one of the
following requirements:
3.1. Grout conforms to Article 2.2 of TMS
602/ACI 530.1/ASCE 6.
3.2. Minimum grout compressive strength
equals or exceeds / '^ but not less than
2,000 psi ( 1 3.79 MPa). The compressive
strength of grout shall be determined in
accordance with ASTM C 1019.
280
2010 CALIFORNIA BUILDING CODE
MASONRY
TABLE 2105.2.2.1.1
COMPRESSIVE STRENGTH OF CLAY MASONRY
NET AREA COMPRESSIVE STRENGTH
OF CLAY MASONRY UNITS (psi)
NET AREA COMPRESSIVE
STRENGTH OF MASONRY
(psi)
Type M or S mortar
Type N mortar
1,700
2,100
1,000
3,350
4,150
1,500
4,950
6,200
2,000
6,600
8,250
2,500
8,250
10,300
3,000
9,900
—
3,500
11,500
—
4,000
For SI: 1 pound per square inch = 0.00689 MPa.
2105.2.2.1.2 Concrete masonry. The compressive
strength of masonry shall be determined based on the
strength of the unit and type of mortar specified using
Table 2105.2.2.1.2, provided:
1. Units are sampled and tested to verify
compliance with ASTM C 55 or ASTM C 90.
2. Thickness of bed joints does not exceed Vg inch
(15.9 mm).
3 . For grouted masonry, the grout meets one of the
following requirements:
3.1. Grout conforms to Article 2.2 of TMS
602/ACI530.1/ASCE6.
3.2. Minimum grout compressive strength
equals or exceeds/'^ but not less than
2,000 psi (13.79 MPa). The compres-
sive strength of grout shall be deter-
mined in accordance with ASTM C
1019.
TABLE 2105.2.2.1.2
COMPRESSIVE STRENGTH OF CONCRETE MASONRY
NET AREA COMPRESSIVE STRENGTH OF
CONCRETE MASONRY UNITS (psi)
NET AREA
COMPRESSIVE
STRENGTH OF
MASONRY (psi)«
Type M or S mortar
Type N mortar
1,250
1,300
1,000
1,900
2,150
1,500
2,800
3,050
2,000
3,750
4,050
2,500
4,800
5,250
3,000
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
a. For units less than 4 inches in height, 85 percent of the values listed.
2105.2.2.1.3 AAC masonry. The compressive
strength of AAC masonry shall be based on the
strength of the AAC masonry unit only and the fol-
lowing shall be met:
1. Units conform to ASTM C 1386.
2. Thickness of bed joints does not exceed Vg inch
(3.2 mm).
3 . For grouted masonry , the grout meets one of the
following requirements:
3.1. Grout conforms to Article 2.2 of TMS
602/ACI530.1/ASCE6.
3.2. Minimum grout compressive strength
equals or exceeds/'^c t>ut not less than
2,000 psi (13.79 MPa). The compres-
sive strength of grout shall be deter-
mined in accordance with ASTM C
1019.
2105.2.2.2 Prism test method.
2105.2.2.2.1 General. The compressive strength of
clay and concrete masonry shall be determined by the
prism test method:
1 . Where specified in the construction documents,
2. Where masonry does not meet the requirements
for application of the unit strength method in
Section 2105.2.2.1.
2105.2.2.2.2 Number of prisms per test. A prism
test shall consist of three prisms constructed and
tested in accordance with ASTM C 1314.
2105.3 Testing prisms from constructed masonry. When
approved by the building official, acceptance of masonry that
does not meet the requirements of Section 2105.2.2.1 or
2105.2.2.2 shall be permitted to be based on tests of prisms cut
from the masonry construction in accordance with Sections
2105.3.1, 2105.3.2 and 2105.3.3.
2105.3.1 Prism sampling and removal. A set of three
masonry prisms that are at least 28 days old shall be saw cut
from the masonry for each 5,000 square feet (465 m^) of the
wall area that is in question but not less than one set of three
masonry prisms for the project. The length, width and height
dimensions of the prisms shall comply with the requirements
of ASTM C 1314. Transporting, preparation and testing of
prisms shall be in accordance with ASTM C 1314.
2105.3.2 Compressive strength calculations. The com-
pressive strength of prisms shall be the value calculated in
accordance ASTM C 1314, except that the net cross-sec-
tional area of the prism shall be based on the net mortar bed-
ded area.
2105.3.3 Compliance. Compliance with the requirement
for the specified compressive strength of masonry,/'^, shall
be considered satisfied provided the modified compressive
strength equals or exceeds the specified/'^. Additional test-
ing of specimens cut from locations in question shall be per-
mitted.
SECTION 2106
SEISMIC DESIGN
2106.1 Seismic design requirements for masonry. Masonry
structures and components shall comply with the requirements
in Section 1.17 of TMS 402/ACI 530/ASCE 5 depending on
the structure's seismic design category as determined in Sec-
tion 1613.
2010 CALIFORNIA BUILDING CODE
281
MASONRY
SECTION 2107
ALLOWABLE STRESS DESIGN
2107.1 General. The design of masonry structures using
allowable stress design shall comply with Section 2106 and the
requirements of Chapters 1 and 2 of TMS 402/ACI 530/ASCE
5 except as modified by Sections 2107.2 through 2107.5.
2107.2 TMS 402/ACI 530/ASCE 5, Section 2.1.2, load com-
binations. Delete Section 2. 1 .2. 1 .
2107.3 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7.1.1, lap
splices. Modify Section 2.1.9.7.1.1 as follows:
2.1.7.1.1 The minimum length of lap splices for reinforcing
bars in tension or compression, /j, shall be
/,= 0.002^/,
(Equation 21-1)
ForSI:/, = 0.2H/,
but not less than 12 inches (305 mm). In no case shall die
length of the lapped splice be less than 40 bar diameters.
where:
di, = Diameterof reinforcement, inches (mm).
/^ = Computed stress in reinforcement due to design
loads, psi (MPa).
In regions of moment where the design tensile stresses in
the reinforcement are greater than 80 percent of the allow-
able steel tension stress, F^, the lap length of spHces shall be
increased not less than 50 percent of the minimum required
length. Other equivalent means of stress transfer to accom-
plish the same 50 percent increase shall be permitted. Where
epoxy coated bars are used, lap length shall be increased by
50 percent.
2107.4 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7, splices
of reinforcement. Modify Section 2.1.9.7 as follows:
2.1.9.7 Splices of reinforcement. Lap splices, welded
splices or mechanical splices are permitted in accordance
with the provisions of this section. All welding shall conform
to AWS D1.4. Welded splices shall be of ASTM A706 steel
reinforcement. Reinforcement larger than No, 9 (M #29)
shall be spliced using mechanical connections in accordance
with Section 2.1,9.7.3.
2107.5 TMS 402/ACI 530/ASCE 5, Section 2.3.6, maximum
bar size. Add the following to Chapter 2:
2.3.6 Maximum bar size. The bar diameter shall not exceed
one-eighth of the nominal wall thickness and shall not
exceed one-quarter of the least dimension of the cell, course
or collar joint in which it is placed.
SECTION 2108
STRENGTH DESIGN OF MASONRY
2108.1 General. The design of masonry structures using
strength design shall comply with Section 2106 and the
requirements of Chapters 1 and 3 of TMS 402/ACI 530/ASCE
5, except as modified by Sections 2108.2 through 2108.3.
Exception: A AC masonry shall comply with the require-
ments of Chapter 1 and Appendix A of TMS 402/ACI
530/ASCE 5.
2108.2 TMS 402/ACI 530/ASCE 5, Section 3.3.3.3 develop-
ment. Modify the second paragraph of Section 3.3.3.3 as follows:
The required development length of reinforcement shall
be determined by Equation (3-16), but shall not be less than
12 inches (305 mm) and need not be greater than 72 ^^.
2108.3 TMS 402/ACI 530/ASCE 5, Section 3.3.3.4, splices.
Modify items (b) and (c) of Section 3.3.3.4 as follows:
3.3.3.4 (b). A welded splice shall have the bars butted and
welded to develop at least 125 percent of the yield strength,
fy , of the bar in tension or compression, as required. Welded
splices shall be of ASTM A 706 steel reinforcement.
Welded splices shall not be permitted in plastic hinge zones
of intermediate or special reinforced walls or special
moment frames of masonry.
3.3.3.4 (c). Mechanical splices shall be classified as Type 1
or 2 according to Section 21.2.6.1 of ACI 318. Type 1
mechanical splices shall not be used within a plastic hinge
zone or within a beam-column joint of intermediate or spe-
cial reinforced masonry shear walls or special moment
frames. Type 2 mechanical splices are permitted in any loca-
tion within a member.
SECTION 2109
EMPIRICAL DESIGN OF MASONRY
2109.1 General. Empirically designed masonry shall conform
to the requirements of Chapter 5 of TMS 402/ACI 530/ASCE
5, except where otherwise noted in this section.
2109.1.1 Limitations. The use of empirical design of
masonry shall be limited as noted in Section 5.1.2 of TMS
402/ACI 530/ASCE 5. The use of dry-stacked, surface-
bonded masonry shall be prohibited in Occupancy Category
IV structures. In buildings that exceed one or more of the
hmitations of Section 5.1.2 of TMS 402/ACI 530/ASCE 5,
masonry shall be designed in accordance with the engi-
neered design provisions of Section 2101.2.1, 2101.2.2 or
2101.2.3 or the foundation wall provisions of Section
1807.1.5.
2109.2 Surface-bonded walls. Dry-stacked, surface-bonded
concrete masonry walls shall comply with the requirements of
Chapter 5 of TMS 402/ACI 530/ASCE 5, except where other-
wise noted in this section.
2109.2.1 Strength. Dry-stacked, surface-bonded concrete
masonry walls shall be of adequate strength and proportions
to support all superimposed loads without exceeding the
allowable stresses listed in Table 2109.2.1. Allowable
stresses not specified in Table 2109.2.1 shall comply with
the requirements of TMS 402/ACI 530/ASCE 5.
282
2010 CALIFORNIA BUILDING CODE
MASONRY
TABLE 2109.2.1
ALLOWABLE STRESS GROSS CROSS-SECTIONAL
AREA FOR DRY-STACKED, SURFACE-BONDED
CONCRETE MASONRY WALLS
DESCRIPTION
MAXIMUM ALLOWABLE STRESS
(psi)
Compression standard block
45
Flexural tension
Horizontal span
Vertical span
30
18
Shear
10
For SI: 1 pound per square inch = 0.006895 MPa.
2109.2.2 Construction. Construction of dry-stacked, sur-
face-bonded masonry walls, including stacking and level-
ing of units, mixing and application of mortar and curing
and protection shall comply with ASTM C 946.
2109.3 Adobe construction. Adobe construction shall comply
with this section and shall be subject to the requirements of this
code for Type V construction, Chapter 5 of TMS 402/ACI
530/ASCE 5, and this section.
2109.3.1 Unstabilized adobe.
2109.3.1.1 Compressive strength. Adobe units shall have
an average compressive strength of 300 psi (2068 kPa)
when tested in accordance with ASTM C 67. Five samples
shall be tested and no individual unit is permitted to have a
compressive strength of less than 250 psi (1724 kPa).
2109.3.1.2 Modulus of rupture. Adobe units shall have
an average modulus of rupture of 50 psi (345 kPa) when
tested in accordance with the following procedure. Five
samples shall be tested and no individual unit shall have a
modulus of rupture of less than 35 psi (241 kPa).
2109.3.1.2.1 Support conditions. A cured unit shall
be simply supported by 2-inch-diameter (51 mm)
cylindrical supports located 2 inches (5 1 mm) in from
each end and extending the full width of the unit.
2109.3.1.2.2 Loading conditions. A 2-inch-diameter
(5 1 mm) cylinder shall be placed at midspan parallel
to the supports.
2109.3.1.2.3 Testing procedure. A vertical load shall
be applied to the cylinder at the rate of 500 pounds per
minute (37 N/s) until failure occurs.
2109.3.1.2.4 Modulus of rupture determination.
The modulus of rupture shall be determined by the
equation:
/, = 3 PL, a S^ (5,2) (Equation 21-2)
where, for the purposes of this section only:
S^ = Width of the test specimen measured parallel to
the loading cylinder, inches (mm).
/^ = Modulus of rupture, psi (MPa).
Lj = Distance between supports, inches (mm).
Sf = Thickness of the test specimen measured paral-
lel to the direction of load, inches (mm).
P = The applied load at failure, pounds (N).
2109.3.1.3 Moisture content requirements. Adobe
units shall have a moisture content not exceeding 4 per-
cent by weight.
2109.3.1.4 Shrinkage cracks. Adobe units shall not
contain more than three shrinkage cracks and any single
shrinkage crack shall not exceed 3 inches (76 mm) in
length or Vg inch (3.2 mm) in width.
2109.3.2 Stabilized adobe.
2109.3.2.1 Material requirements. Stabilized adobe
shall comply with the material requirements of
unstabilized adobe in addition to Sections 2109.3.2.1.1
and 2109.3,2.1.2.
2109.3.2.1.1 Soil requirements. Soil used for stabi-
lized adobe units shall be chemically compatible with
the stabilizing material.
2109.3.2.1.2 Absorption requirements, A 4-inch
(102 mm) cube, cut from a stabilized adobe unit dried
to a constant weight in a ventilated oven at 212°F to
239°F (lOOX to 115°C), shall not absorb more than
2V2 percent moisture by weight when placed upon a
constantly water-saturated, porous surface for seven
days. A minimum of five specimens shall be tested
and each specimen shall be cut from a separate unit.
2109.3.3 Allowable stress. The allowable compressive
stress based on gross cross-sectional area of adobe shall not
exceed 30 psi (207 kPa).
2109.3,3.1 Bolts. Bolt values shall not exceed those set
forth in Table 2109.3.3.1.
TABLE 2109.3.3.1
ALLOWABLE SHEAR ON BOLTS IN ADOBE MASONRY
DIAMETER OF BOLTS
(inches)
MINIMUM EMBEDMENT
(inches)
SHEAR
(pounds)
%
'/.
12
200
%
15
300
y.
18
400
1
21
500
iVs
24
600
For SI: 1 inch = 25.4 mm, 1 pound = 4.448 N.
2109.3.4 Construction.
2109.3.4.1 General. Adobe construction shall be limited
as stated in Sections2109.3.4.1.1through2109.3.4.1.4.
2109.3.4.1.1 Height restrictions. Adobe construc-
tion shall be limited to buildings not exceeding one
story, except that two-story construction is allowed
when designed by a registered design professional.
2109.3.4.1.2 Mortar restrictions. Mortar for stabi-
lized adobe units shall comply with Chapter 21 or
adobe soil. Adobe soil used as mortar shall comply
with material requirements for stabilized adobe. Mor-
tar for unstabilized adobe shall be portland cement
mortar.
2010 CALIFORNIA BUILDING CODE
283
MASONRY
2109.3.4.1.3 Mortar joints. Adobe units shall be laid
with full head and bed joints and in full running bond.
2109.3.4.1.4 Parapet wails. Parapet walls con-
structed of adobe units shall be waterproofed.
2109.3.4.2 Wall thickness. The minimum thickness of
exterior walls in one-story buildings shall be 10 inches
(254 mm). The walls shall be laterally supported at inter-
vals not exceeding 24 feet (7315 mm). The minimum
thickness of interior load-bearing walls shall be 8 inches
(203 mm). In no case shall the unsupported height of any
wall constructed of adobe units exceed 10 times the
thickness of such wall.
2109.3.4.3 Foundations. Foundations for adobe con-
struction shall be in accordance with Sections
2109.3.4.3.1 and 2109.3.4.3.2.
2109.3.4.3.1 Foundation support. Walls and parti-
tions constructed of adobe units shall be supported by
foundations or footings that extend not less than 6
inches (152 mm) above adjacent ground surfaces and
are constructed of sohd masonry (excluding adobe) or
concrete. Footings and foundations shall comply with
Chapter 18.
2109.3.4.3.2 Lower course requirements. Stabi-
lized adobe units shall be used in adobe walls for the
first 4 inches (102 mm) above the finished first-floor
elevation.
2109.3.4.4 Isolated piers or columns. Adobe units shall
not be used for isolated piers or columns in a load-bear-
ing capacity. Walls less than 24 inches (610 mm) in
length shall be considered isolated piers or columns.
2109.3.4.5 Tie beams. Exterior walls and interior
load-bearing walls constructed of adobe units shall have
a continuous tie beam at the level of the floor or roof
bearing and meeting the following requirements.
2109.3.4.5.1 Concrete tie beams. Concrete tie
beams shall be a minimum depth of 6 inches (152
mm) and a minimum width of 10 inches (254 mm).
Concrete tie beams shall be continuously reinforced
with a minimum of two No. 4 reinforcing bars. The
specifed compressive strength of concrete shall be at
least 2,500 psi (17.2 MPa).
2109.3.4.5.2 Wood tie beams. Wood tie beams shall
be solid or built up of lumber having a minimum nomi-
nal thickness of 1 inch (25 mm), and shall have a mini-
mum depth of 6 inches (152 mm) and a minimum
width of 10 inches (254 mm). Joints in wood tie beams
shall be spliced a minimum of 6 inches (152 nmi). No
splices shall be allowed within 12 inches (305 mm) of
an opening. Wood used in tie beams shall be approved
naturally decay-resistant or preservative-treated wood.
2109.3.4.6 Exterior finish. Exterior walls constructed
of unstabilized adobe units shall have their exterior sur-
face covered with a minimum of two coats of portland
cement plaster having a minimum thickness of V4 inch
(19.1 mm) and conforming to ASTM C 926. Lathing
shall comply with ASTM C 1063. Fasteners shall be
spaced at 16 inches (406 mm) o.c. maximum. Exposed
wood surfaces shall be treated with an approved wood
preservative or other protective coating prior to lath
application.
2109.3.4.7 Lintels. Lintels shall be considered structural
members and shall be designed in accordance with the
applicable provisions of Chapter 16.
SECTION 2110
GLASS UNIT MASONRY
2110.1 General. Glass unit masonry construction shall comply
with Chapter 7 of TMS 402/ACI 530/ASCE 5 and tiiis section.
2110.1.1 Limitations. Solid or hollow approved glass
block shall not be used in fire walls, party walls, fire barri-
ers, fire partitions or smoke barriers, or for load-bearing
construction. Such blocks shall be erected with mortar and
reinforcement in metal channel-type frames, structural
frames, masonry or concrete recesses, embedded panel
anchors as provided for both exterior and interior walls or
other approved joint materials. Wood strip framing shall not
be used in walls required to have a fire-resistance rating by
other provisions of this code.
Exceptions:
1. Glass-block assemblies having a fire protection
rating of not less than V4 hour shall be permitted as
opening protectives in accordance with Section
7 1 5 in fire barriers, fire partitions and smoke barri-
ers that have a required fire-resistance rating of 1
hour or less and do not enclose exit stairways, exit
ramps or exit passageways.
2. Glass-block assemblies as permitted in Section
404.6, Exception 2.
SECTION 2111
MASONRY FIREPLACES
2111.1 Definition. A masonry fireplace is a fireplace con-
structed of concrete or masonry. Masonry fireplaces shall be
constructed in accordance with this section.
2111.2 Footings and foundations. Footings for masonry fire-
places and their chimneys shall be constructed of concrete or
solid masonry at least 12 inches (305 mm) thick and shall
extend at least 6 inches (153 mm) beyond the face of the fire-
place or foundation wall on all sides. Footings shall be founded
on natural undisturbed earth or engineered fill below frost
depth. In areas not subjected to freezing, footings shall be at
least 12 inches (305 mm) below finished grade.
2111.2.1 Ash dump cleanout. Cleanout openings, located
within foundation walls below fireboxes, when provided,
shall be equipped with ferrous metal or masonry doors and
frames constructed to remain tightly closed, except when in
use. Cleanouts shall be accessible and located so that ash
removal will not create a hazard to combustible materials.
2111.3 Seismic reinforcing. Masonry or concrete fireplaces
shall be constructed, anchored, supported and reinforced as
required in this chapter. In Seismic Design Category C or D,
284
2010 CALIFORNIA BUILDING CODE
MASONRY
masonry and concrete fireplaces shall be reinforced and
anchored as detailed in Sections 2111.3.1, 211L3.2, 2111.4
and 2111.4.1 for chimneys serving fireplaces. In Seismic
Design Category A or B, reinforcement and seismic anchorage
is not required. In Seismic Design Category E or F, masonry
and concrete chimneys shall be reinforced in accordance with
the requirements of Sections 2101 through 2108.
2111.3.1 Vertical reinforcing. For fireplaces with chim-
neys up to 40 inches (1016 mm) wide, four No. 4 continuous
vertical bars, anchored in the foundation, shall be placed in
the concrete between wythes of solid masonry or within the
cells of hollow unit masonry and grouted in accordance with
Section 2103.12. For fireplaces with chimneys greater than
40 inches (1016 mm) wide, two additional No. 4 vertical
bars shall be provided for each additional 40 inches (1016
mm) in width or fraction thereof.
2111.3.2 Horizontal reinforcing. Vertical reinforcement
shall be placed enclosed within V4-inch (6.4 mm) ties or
other reinforcing of equivalent net cross- sectional area,
spaced not to exceed 1 8 inches (457 mm) on center in con-
crete; or placed in the bed joints of unit masonry at a mini-
mum of every 18 inches (457 mm) of vertical height. Two
such ties shall be provided at each bend in the vertical bars.
2111.4 Seismic anchorage. Masonry and concrete chimneys
in Seismic Design Category C or D shall be anchored at each
floor, ceiling or roof line more than 6 feet (1829 mm) above
grade, except where constructed completely within the exterior
walls. Anchorage shall conform to the following requirements.
2111.4.1 Anchorage. Two Vi^-inch by 1-inch (4.8 mm by
25.4 mm) straps shall be embedded a minimum of 12 inches
(305 mm) into the chimney. Straps shall be hooked around
the outer bars and extend 6 inches (152 mm) beyond the
bend. Each strap shall be fastened to a minimum of four
floor joists with two Vj-inch (12.7 mm) bolts.
2111.5 Firebox wails. Masonry fireboxes shall be constructed
of solid masonry units, hollow masonry units grouted solid,
stone or concrete. When a lining of firebrick at least 2 inches
(5 1 mm) in thickness or other approved lining is provided, the
minimum thickness of back and sidewalls shall each be 8
inches (203 mm) of solid masonry, including the lining. The
width of joints between firebricks shall not be greater than V4
inch (6.4 mm). When no hning is provided, the total minimum
thickness of back and sidewalls shall be 10 inches (254 mm) of
solid masonry. Firebrick shall conform to ASTM C 27 or
ASTM C 1261 and shall be laid with medium-duty refractory
mortar conforming to ASTM C 199.
2111.5.1 Steel fireplace units. Steel fireplace units are per-
mitted to be installed with soUd masonry to form a masonry
fireplace provided they are installed according to either the
requirements of their Usting or the requirements of this sec-
tion. Steel fireplace units incorporating a steel firebox lining
shall be constructed with steel not less than V4 inch (6.4 mm)
in thickness, and an air-circulating chamber which is ducted
to the interior of the building. The firebox hning shall be
encased with solid masonry to provide a total thickness at the
back and sides of not less than 8 inches (203 mm), of which
not less than 4 inches (102 mm) shall be of solid masonry or
concrete. Circulating air ducts employed with steel fireplace
units shall be constructed of metal or masonry.
2111.6 Firebox dimensions. The firebox of a concrete or
masonry fireplace shall have a minimum depth of 20 inches
(508 mm). The throat shall not be less than 8 inches (203 mm)
above the fireplace opening. The throat opening shall not be
less than 4 inches (102 mm) in depth. The cross-sectional area
of the passageway above the firebox, including the throat,
damper and smoke chamber, shall not be less than the
cross-sectional area of the flue.
Exception: Rumford fireplaces shaU be permitted provided
that the depth of the fireplace is at least 12 inches (305 mm) and
at least one-third of the width of the fireplace opening, and the
throat is at least 12 inches (305 mm) above the lintel, and at
least V20 the cross-sectional area of the fireplace opening.
2111.7 Lintel and throat. Masonry over a fireplace opening
shall be supported by a lintel of noncombustible material. The
minimum required bearing length on each end of the fireplace
opening shall be 4 inches (102 mm). The fireplace throat or
damper shall be located a minimum of 8 inches (203 mm)
above the top of the fireplace opening.
2111.7.1 Damper. Masonry fireplaces shall be equipped
with a ferrous metal damper located at least 8 inches (203
mm) above the top of the fireplace opening. Dampers shall
be installed in the fireplace or at the top of the flue venting
the fireplace, and shall be operable from the room contain-
ing the fireplace. Damper controls shall be permitted to be
located in the fireplace.
2111.8 Smoke chamber walls. Smoke chamber walls shall be
constructed of solid masonry units, hollow masonry units
grouted soUd, stone or concrete. The total minimum thickness
of front, back and sidewalls shall be 8 inches (203 mm) of solid
masonry. The inside surface shall be parged smooth with
refractory mortar conforming to ASTM C 199. When a lining
of firebrick at least 2 inches (5 1 mm) thick, or a lining of vitri-
fied clay at least Vg inch (15.9 mm) thick, is provided, the total
minimum thickness of front, back and sidewalls shall be 6
inches (152 mm) of solid masonry, including the lining. Fire-
brick shall conform to ASTM C 1261 and shall be laid with
refractory mortar conforming to ASTM C 199. Vitrified clay
linings shall conform to ASTM C 315.
2111.8.1 Smoke chamber dimensions. The inside height of
the smoke chamber from the fireplace throat to the beginning
of the flue shall not be greater than the inside width of the fu-e-
place opening. The inside surface of the smoke chamber shall
not be inclined more than 45 degrees (0.76 rad) from vertical
when prefabricated smoke chamber Unings are used or when
the smoke chamber walls are rolled or sloped rather than
corbeled. When the inside surface of the smoke chamber is
formed by corbeled masonry, the walls shall not be corbeled
more than 30 degrees (0.52 rad) from vertical.
2111.9 Hearth and hearth extension. Masonry fireplace
hearths and hearth extensions shall be constructed of concrete
or masonry, supported by noncombustible materials, and rein-
forced to carry their own weight and all imposed loads. No
combustible material shall remain against the underside of
hearths or hearth extensions after construction.
2010 CALIFORNIA BUILDING CODE
285
MASONRY
2111.9.1 Hearth thickness. The minimum thickness of
fireplace hearths shall be 4 inches (102 mm).
2111.9.2 Hearth extension thickness. The minimum
thickness of hearth extensions shall be 2 inches (51 mm).
Exception: When the bottom of the firebox opening is
raised at least 8 inches (203 mm) above the top of the
hearth extension, a hearth extension of not less than
Vg-inch-thick (9.5 mm) brick, concrete, stone, tile or
other approved noncombustible material is permitted.
2111.10 Hearth extension dimensions. Hearth extensions
shall extend at least 16 inches (406 mm) in front of, and at least
8 inches (203 mm) beyond, each side of the fireplace opening.
Where the fireplace opening is 6 square feet (0.557 m^) or
larger, the hearth extension shall extend at least 20 inches (508
mm) in front of, and at least 12 inches (305 mm) beyond, each
side of the fireplace opening.
2111.11 Fireplace clearance. Any portion of a masonry fire-
place located in the interior of a building or within the exterior
wall of a building shall have a clearance to combustibles of not
less than 2 inches (51 nun) from the front faces and sides of
masonry fireplaces and not less than 4 inches (102 mm) from the
back faces of masonry fireplaces. The airspace shall not be filled,
except to provide fireblocking in accordance with Section
2111.12.
Exceptions:
1 . Masonry fireplaces listed and labeled for use in contact
with combustibles in accordance with UL 127 and
installed in accordance with the manufacturer's instal-
lation instructions are permitted to have combustible
material in contact with their exterior surfaces.
2. When masonry fireplaces are constructed as part of
masonry or concrete walls, combustible materials
shall not be in contact with the masonry or concrete
walls less than 12 inches (306 mm) from the inside
surface of the nearest firebox lining.
3. Exposed combustible trim and the edges of sheathing
materials, such as wood siding, flooring and drywall,
are permitted to abut the masonry fireplace sidewalls
and hearth extension, in accordance with Figure
2111.11, provided such combustible trim or sheath-
CXJMBUSTIB^ SHEATHING
EDGE ABUTTir^ MA^NRY
12' MiN.FFOyi FIREBOX
2" CLiARANCe (AIRSPACI^
^loogmmimjc framing
woa>MANTe.
For SI: 1 inch = 25.4 mm
FIGURE 2111.11
ILLUSTRATION OF EXCEPTION TO
FIREPLACE CLEARANCE PROVISION
ing is a minimum of 12 inches (306 mm) fi-om the
inside surface of the nearest firebox lining.
4. Exposed combustible mantels or trim is permitted to be
placed directly on the masonry fireplace front sur-
rounding the fireplace opening, provided such com-
bustible materials shall not be placed within 6 inches
(153 mm) of a fireplace opening. Combustible material
directly above and within 12 inches (305 mm) of the
fireplace opening shall not project more than Vg inch
(3.2 nam) for each 1-inch (25 mm) distance from such
opening. Combustible materials located along the
sides of the fireplace opening that project more than
1 V2 inches (38 mm) from the face of the fireplace shall
have an additional clearance equal to the projection.
2111.12 Fireplace fireblocking. All spaces between fireplaces
and floors and ceilings through which fireplaces pass shall be
fireblocked with noncombustible material securely fastened in
place. The fireblocking of spaces between wood joists, beams or
headers shall be to a depth of 1 inch (25 mm) and shall only be
placed on strips of metal or metal lath laid across the spaces
between combustible material and the chimney.
2111.13 Exterior air. Factory-built or masonry fireplaces cov-
ered in this section shall be equipped with an exterior air supply
to ensure proper fuel combustion unless the room is mechani-
cally ventilated and controlled so that the indoor pressure is
neutral or positive.
2111.13.1 Factory-built fireplaces. Exterior combustion
air ducts for factory-built fireplaces shall be listed compo-
nents of the fireplace, and installed according to the fire-
place manufacturer's instructions.
2111.13.2 Masonry fireplaces. L/5^^ J combustion air ducts
for masonry fireplaces shall be installed according to the
terms of their listing and manufacturer's instructions.
2111.13.3 Exterior air intake. The exterior air intake shall
be capable of providing all combustion air from the exterior
of the dwelling. The exterior air intake shall not be located
within a garage, attic, basement or crawl space of the dwell-
ing nor shall the air intake be located at an elevation higher
than the firebox. The exterior air intake shall be covered
with a corrosion-resistant screen of V4-inch (6.4 mm) mesh.
2111.13.4 Clearance. Unlisted combustion air ducts shall
be installed with a minimum 1-inch (25 mm) clearance to
combustibles for all parts of the duct within 5 feet (1524
mm) of the duct outlet.
2111.13.5 Passageway. The combustion air passageway
shall be a minimum of 6 square inches (3870 mm^) and not
more than 55 square inches (0,035 m^), except that combus-
tion air systems for listed fireplaces or for fireplaces tested
for emissions shall be constructed according to the fireplace
manufacturer's instructions.
2111.13.6 Outlet. The exterior air outlet is permitted to be
located in the back or sides of the firebox chamber or within
24 inches (610 mm) of the firebox opening on or near the
floor The outlet shall be closable and designed to prevent
burning material from dropping into concealed combustible
spaces.
286
2010 CALIFORNIA BUILDING CODE
MASONRY
SECTION 2112
MASONRY HEATERS
2112.1 Definition. A masonry heater is a heating appliance
constructed of concrete or solid masonry, hereinafter referred
to as "masonry" which is designed to absorb and store heat
from a solid fuel fire built in the firebox by routing the exhaust
gases through internal heat exchange channels in which the
flow path downstream of the firebox may include flow in a hor-
izontal or downward direction before entering the chinmey and
which delivers heat by radiation from the masonry surface of
the heater.
2112.2 Installation. Masonry heaters shall be installed in accor-
dance with this section and comply with one of the following:
1 , Masonry heaters shall comply with the requirements of
ASTM E 1602; or
2. Masonry heaters shall be listed and labeled in accor-
dance with UL 1482 and installed in accordance with the
manufacturer's installation instructions.
2112.3 Footings and foundation. The firebox floor of a
masonry heater shall be a minimum thickness of 4 inches (102
mm) of noncombustible material and be supported on a
noncombustible footing and foundation in accordance with
Section 2113.2.
2112.4 Seismic reinforcing. In Seismic Design Category D, E
and F, masonry heaters shall be anchored to the masonry foun-
dation in accordance with Section 2 11 3. 3. Seismic reinforcing
shall not be required within the body of a masonry heater with a
height that is equal to or less than 3.5 times its body width and
where the masonry chimney serving the heater is not supported
by the body of the heater. Where the masonry chimney shares a
common wall with the facing of the masonry heater, the chim-
ney portion of the structure shall be reinforced in accordance
with Section 2113.
2112.5 Masonry heater clearance. Combustible materials
shall not be placed within 36 inches (765 mm) of the outside
surface of a masonry heater in accordance with NFPA 211,
Section 8-7 (clearances for solid fuel-burning appliances), and
the required space between the heater and combustible material
shall be fully vented to permit the free flow of air around all
heater surfaces.
Exceptions:
1. When the masonry heater wall thickness is at least 8
inches (203 mm) thick of solid masonry and the wall
thickness of the heat exchange channels is at least 5
inches (127 mm) thick of solid masonry, combustible
materials shall not be placed within 4 inches (102
nmi) of the outside surface of a masonry heater. A
clearance of at least 8 inches (203 mm) shall be pro-
vided between the gas-tight capping slab of the heater
and a combustible ceiling.
2. Masonry heaters listed and labeled in accordance
with UL 1482 and installed in accordance with the
manufacturer's instructions.
SECTION 2113
MASONRY CHIMNEYS
2113.1 Definition. A masonry chimney is a chimney con-
structed of concrete or masonry, hereinafter referred to as
"masonry." Masonry chimneys shall be constructed, anchored,
supported and reinforced as required in this chapter.
2113.2 Footings and foundations. Footings for masonry
chimneys shall be constructed of concrete or solid masonry at
least 12 inches (305 mm) thick and shall extend at least 6 inches
(152 nam) beyond the face of the foundation or support wall on
all sides. Footings shall be founded on natural undisturbed
earth or engineered fill below frost depth. In areas not subjected
to freezing, footings shall be at least 12 inches (305 mm) below
finished grade.
2113.3 Seismic reinforcing. Masonry or concrete chimneys
shall be constructed, anchored, supported and reinforced as
required in this chapter. In Seismic Design Category C or D,
masonry and concrete chimneys shall be reinforced and
anchored as detailed in Sections 2113.3.1, 2113.3.2 and
2 1 1 3 .4. In Seismic Design Category A or B , reinforcement and
seismic anchorage is not required. In Seismic Design Category
E or F, masonry and concrete chimneys shall be reinforced in
accordance with the requirements of Sections 2101 through
2108.
2113.3.1 Vertical reinforcing. For chimneys up to 40
inches (1016 mm) wide, four No. 4 continuous vertical bars
anchored in the foundation shall be placed in the concrete
between wythes of solid masonry or within the cells of hol-
low unit masonry and grouted in accordance with Section
2103.12. Grout shall be prevented from bonding with the
flue liner so that the flue liner is free to move with thermal
expansion. For chimneys greater than 40 inches (1016 mm)
wide, two additional No. 4 vertical bars shall be provided for
each additional 40 inches (1016 mm) in width or fraction
thereof.
2113.3.2 Horizontal reinforcing. Vertical reinforcement
shall be placed enclosed within V4-inch (6.4 mm) ties, or
other reinforcing of equivalent net cross- sectional area,
spaced not to exceed 1 8 inches (457 mm) o.c. in concrete, or
placed in the bed joints of unit masonry, at a minimum of
every 1 8 inches (457 mm) of vertical height. Two such ties
shall be provided at each bend in the vertical bars.
2113.4 Seismic anchorage. Masonry and concrete chimneys
and foundations in Seismic Design Category C or D shall be
anchored at each floor, ceiling or roof line more than 6 feet
(1829 mm) above grade, except where constructed completely
within the exterior walls. Anchorage shall conform to the fol-
lowing requirements.
2113.4.1 Anchorage. Two Vi^-inch by 1-inch (4.8 mm by
25 mm) straps shall be embedded a minimum of 12 inches
(305 mm) into the chimney. Straps shall be hooked around
the outer bars and extend 6 inches (152 mm) beyond the
bend. Each strap shall be fastened to a minimum of four
floor joists with two Vj-inch (12.7 mm) bolts.
2113.5 Corbeling. Masonry chimneys shall not be corbeled
more than half of the chimney's wall thickness from a wall or
foundation, nor shall a chimney be corbeled from a wall or
2010 CALIFORNIA BUILDING CODE
287
MASONRY
foundation that is less than 12 inches (305 nun) in thickness
unless it projects equally on each side of the wall, except that on
the second story of a two- story dwelling, corbeling of chim-
neys on the exterior of the enclosing walls is permitted to equal
the wall thickness. The projection of a single course shall not
exceed one-half the unit height or one-third of the unit bed
depth, whichever is less.
2113.6 Changes in dimension. The chimney wall or chimney
flue hning shall not change in size or shape within 6 inches
(152 mm) above or below where the chimney passes through
floor components, ceiling components or roof components.
2113.7 Offsets. Where a masonry chimney is constructed with
a fireclay flue liner surrounded by one wythe of masonry, the
maximum offset shall be such that the centerline of the flue
above the offset does not extend beyond the center of the chim-
ney wall below the offset. Where the chimney offset is sup-
ported by masonry below the offset in an approved manner, the
maximum offset limitations shall not apply. Each individual
corbeled masonry course of the offset shall not exceed the pro-
jection limitations specified in Section 2113.5.
2113.8 Additional load. Chimneys shall not support loads
other than their own weight unless they are designed and con-
structed to support the additional load. Masonry chimneys are
permitted to be constructed as part of the masonry walls or con-
crete walls of the building.
2113.9 Termination. Chimneys shall extend at least 2 feet
(610 mm) higher than any portion of the building within 10 feet
(3048 mm), but shall not be less than 3 feet (914 mm) above the
highest point where the chimney passes through the roof.
I I 2113.9.1 Spark arresters. [SFMJAll chimneys attached to
any appliance or fireplace that burns solid fuel shall be
equipped with an approved spark arrester The spark
arrestor shall meet all of the following requirements:
1 . The net free area of the spark arrester shall not be less
than four times the net free area of the outlet of the
chimney.
2. The spark arrester screen shall have heat and corro-
sion resistance equivalent to 12- gage wire, 19- gage
galvanized wire or 24-gage stainless steel.
3. Openings shall not permit the passage of spheres hav-
. ing a diameter larger than V2 ^^^^ (12.7 mm) and
shall not block the passage of spheres having a diam-
eter of less than % inch (9.5 mm).
4. The spark arrestor shall be accessible for cleaning and
the screen or chimney cap shall be removable to allow
for cleaning of the chimney flue.
2113.10 Wall thickness. Masonry chimney walls shall be con-
structed of concrete, solid masonry units or hollow masonry
units grouted solid with not less than 4 inches (102 mm) nomi-
nal thickness.
2113.10.1 Masonry veneer chimneys. Where masonry is
used as veneer for a framed chimney, through flashing and
weep holes shall be provided as required by Chapter 14.
2113.11 Flue lining (material). Masonry chimneys shall be
lined. The lining material shall be appropriate for the type of
appliance connected, according to the terms of the appliance
listing and the manufacturer's instructions.
2113.11.1 Residential-type appliances (general). Flue
lining systems shall comply with one of the following:
1. Clay flue hning complying with the requirements of
ASTMC315.
2. Listed chimney lining systems complying with UL
1777.
3. Factory-built chimneys or chimney units listed for
installation within masonry chimneys.
4. Other approved materials that will resist corrosion,
erosion, softening or cracking from flue gases and
condensate at temperatures up to 1,800°F (982°C).
2113.11.1.1 Flue linings for specific appliances. Flue
linings other than those covered in Section 2113.11.1
intended for use with specific appliances shall comply
with Sections 2113.11.1.2 through 2113.11.1.4 and Sec-
tions 2113.11.2 and 2113.11.3.
2113.11.1.2 Gas appliances. Flue lining systems for gas
appliances shall be in accordance with the California
Mechanical Code.
2113.11.1.3 Pellet fuel-burning appliances. Flue lining
and vent systems for use in masonry chimneys with pel-
let fuel-burning appliances shall be limited to flue lining
systems complying with Section 2113.11.1 and pellet
vents listed for installation within masonry chimneys
(see Section 2113.11.1.5 for marking).
2113.11.1.4 Oil-fired appliances approved for use
with L-vent. Flue lining and vent systems for use in
masonry chimneys with oil-fired appliances approved
for use with Type L vent shall be limited to flue lining
systems complying with Section 2113.11.1 and listed
chimney liners complying with UL 641 (see Section
2113.11.1.5 for marking),
2113.11.1.5 Notice of usage. When a flue is relined with
a material not complying with Section 2113.11.1, the
chimney shall be plainly and permanently identified by a
label attached to a wall, ceiling or other conspicuous
location adjacent to where the connector enters the chim-
ney. The label shall include the following message or
equivalent language: "This chimney is for use only with
(type or category of appliance) that bums (type of fuel).
Do not connect other types of appliances."
2113.11.2 Concrete and masonry chimneys for medium-
heat appliances.
2113.11.2.1 General. Concrete and masonry chimneys
for medium-heat appliances shall comply with Sections
2113.1 through 2113.5.
2113.11.2.2 Construction. Chimneys for medium-heat
appliances shall be constructed of solid masonry units or
of concrete with walls a minimum of 8 inches (203 mm)
thick, or with stone masonry a minimum of 12 inches
(305 mm) thick.
2113.11.2.3 Lining. Concrete and masonry chimneys
shall be lined with an approved medium-duty refractory
288
2010 CALIFORNIA BUILDING CODE
MASONRY
brick a minimum of 4V2 inches (1 14 mm) thick laid on
the 4V2-inch bed (114 mm) in an approved medium-
duty refractory mortar. The Hning shall start 2 feet (610
mm) or more below the lowest chimney connector
entrance. Chimneys terminating 25 feet (7620 mm) or
less above a chimney connector entrance shall be lined
to the top.
2113.11.2.4 Multiple passageway. Concrete and
masonry chimneys containing more than one passage-
way shall have the liners separated by a minimum
4-inch-thick (102 mm) concrete or solid masonry wall.
2113.11.2.5 Termination height. Concrete and
masonry chimneys for medium-heat appliances shall
extend a minimum of 10 feet (3048 mm) higher than any
portion of any building within 25 feet (7620 mm).
2113.11.2.6 Clearance. A minimum clearance of 4
inches (102 mm) shall be provided between the exterior
surfaces of a concrete or masonry chimney for
medium-heat appliances and combustible material.
2113.11.3 Concrete and masonry chimneys for
high-heat appliances.
2113.11.3.1 General. Concrete and masonry chimneys
for high-heat appliances shall comply with Sections
2113.1 through 21 13.5.
2113.11.3.2 Construction. Chimneys for high-heat
appliances shall be constructed with double walls of
solid masonry units or of concrete, each wall to be a mini-
mum of 8 inches (203 mm) thick with a minimum air-
space of 2 inches (51 mm) between the walls.
2113.11.3.3 Lining. The inside of the interior wall shall
be lined with an approved high-duty refractory brick, a
minimum of 4V2 inches (114 mm) thick laid on the
4 V2-inch bed (114 mm) in an approved high-duty refrac-
tory mortar. The lining shall start at the base of the chim-
ney and extend continuously to the top.
2113.11.3.4 Termination height. Concrete and
masonry chimneys for high-heat appliances shall extend
a minimum of 20 feet (6096 mm) higher than any portion
of any building within 50 feet (15 240 mm).
2113.11.3.5 Clearance. Concrete and masonry chim-
neys for high-heat appliances shall have approved clear-
ance from buildings and structures to prevent
overheating combustible materials, permit inspection
and maintenance operations on the chimney and prevent
danger of bums to persons.
2113.12 Clay flue lining (installation). Clay flue liners shall
be installed in accordance with ASTM C 1283 and extend from
a point not less than 8 inches (203 mm) below the lowest inlet
or, in the case of fireplaces, from the top of the smoke chamber
to a point above the enclosing walls. The lining shall be carried
up vertically, with a maximum slope no greater than 30 degrees
(0.52 rad) from the vertical.
Clay flue liners shall be laid in medium-duty refractory mor-
tar conforming to ASTM C 199 with tight mortar joints left
smooth on the inside and installed to maintain an air space or
insulation not to exceed the thickness of the flue liner separat-
ing the flue liners from the interior face of the chimney
masonry walls. Flue lining shall be supported on all sides. Only
enough mortar shall be placed to make the joint and hold the
liners in position.
2113.13 Additional requirements.
2113.13.1 Listed materials. Listed materials used as flue
linings shall be installed in accordance with the terms of
their hstings and the manufacturer's instructions.
2113.13.2 Space around lining. The space surrounding a
chimney lining system or vent installed within a masonry
chimney shall not be used to vent any other appliance.
Exception: This shall not prevent the installation of a
separate flue lining in accordance with the manufac-
turer's instructions.
2113.14 Multiple flues. When two or more flues are located
in the same chimney, masonry wythes shall be built between
adjacent flue linings. The masonry wythes shall be at least 4
inches (102 mm) thick and bonded into the walls of the chim-
ney.
Exception: When venting only one appliance, two flues are
permitted to adjoin each other in the same chimney with
only the flue lining separation between them. The joints of
the adjacent flue linings shall be staggered at least 4 inches
(102 mm).
2113.15 Flue area (appliance). Chimney flues shall not be
smaller in area than the area of the connector from the appli-
ance. Chimney flues connected to more than one appliance
shall not be less than the area of the largest connector plus 50
percent of the areas of additional chimney connectors.
Exceptions:
1. Chimney flues serving oil-fired appliances sized in
accordance with NFPA 31.
2. Chimney flues serving gas-flred appliances sized in
accordance with the California Mechanical Code.
2113.16 Flue area (masonry fireplace). Flue sizing for chim-
neys serving fireplaces shall be in accordance with Section
2113.16.1 or 2113.16.2.
2113.16.1 Minimum area. Round chimney flues shall have a
minimum net cross-sectional area of at least 7^2 of the fire-
place opening. Square chimney flues shall have a minimum
net cross-sectionad area of at least Vio of the fireplace opening.
Rectangular chinmey flues with an aspect ratio less than 2 to
1 shall have a minimum net cross-sectional area of at least V^q
of the fireplace opening. Rectangular chimney flues with an
aspect ratio of 2 to 1 or more shall have a minimum net
cross-sectional area of at least Vg of the fireplace opening.
2113.16.2 Determination of minimum area. The mini-
mum net cross-sectional area of the flue shall be determined
in accordance with Figure 21 13. 16. A flue size providing at
least the equivalent net cross-sectional area shall be used.
Cross-secfional areas of clay flue Unings are as provided in
Tables 2113.16(1) and 2113.16(2) or as provided by the
manufacturer or as measured in the field. The height of the
chimney shall be measured from the firebox floor to the top
of the chimney flue.
2010 CALIFORNIA BUILDING CODE
289
MASONRY
m ;
124
91
§2 .
68
M
X-'
'. 3000
,-^
,^
. .. ?RAn
.^
^ V^
■ ■
■^
>^-
„ , , -^finn
^
v^
■^
>^
;^^-,,
^1 ^
^
.^*
^
'' '?7nn
^ ■■
'-^.
i^1
"^ ^S^ ■
,„->^
^t^-.
r,™,-,™™*™™™ '^000
^
>^
,--^
*rf'
: ^-^
< to/
^-^
>*'^
s
'•-<'
^
<?^
If^O
;<
^,^*^
-^-^
^. ,
P i:40 I
„:,,ii,nil«
-rf^
.-^
■■■■
...»»..»» irfon
-iimitrff*^
.-.--^
^tu
tn^i'^**'
..^
.
§ lip
P*^
J..^^
-.''-<'
*^
Q
„-----
,*..*-—
«it--
.--— ^
■^
, ^^
rr^
1 r6
'""^
p*-^
:::*-^
,*--
r-?^
■m
_ -
^-*--r
i*-^.
■ ■ ' ;
1, , , fron
M ^9
--^
^— •
.-, ■
53
^*^
*-*"^
"---r
,-«*—
: -- -
U--^
*——
■32: :
,„_._„ 'inrt
.
a-:
osfSv
og:^:
ill
ia :
14^
15
OFt
16 ■
TO
EASUf
PSTIC
FOF
>NGH
Flue
AMBERTO
(TO
25 ^
For SI: 1 inch = 25.4 mm, 1 square inch = 645 mnf .
FIGURE 2113.16
FLUE SIZES FOR MASONRY CHIMNEYS
TABLE 2113.16(1)
NET CROSS-SECTIONAL AREA OF ROUND FLUE SIZES^
FLUE SIZE, INSIDE DIAMETER
(inches)
CROSS-SECTIONAL AREA
(square inches)
6
28
7
38
8
50
10
78
10%
90
12
113
15
176
18
254
TABLE 2113.16(2)
NET CROSS-SECTIONAL AREA OF SQUARE
AND RECTANGULAR FLUE SIZES
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mnf.
a. Flue sizes are based on ASTM C 315.
FLUE SIZE, OUTSIDE NOMINAL DIMENSIONS
(Inches)
CROSS-SECTIONAL AREA
(square Inches)
4.5 X 8.5
23
4.5 X 13
34
8x8
42
8.5 X 8.5
49
8x12
67
8.5x13
76
12x12
102
8.5x18
101
13x13
127
12x16
131
13x18
173
16x16
181
16x20
222
18x18
233
20x20
298
20x24
335
24x24
431
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm?.
290
2010 CALIFORNIA BUILDING CODE
MASONRY
2113.17 Inlet. Inlets to masonry chimneys shall enter from the
side. Inlets shall have a thimble of fireclay, rigid refractory
material or metal that will prevent the connector from pulling
out of the inlet or from extending beyond the wall of the liner.
2113.18 Masonry chimney cleanout openings. Cleanout
openings shall be provided within 6 inches (152 mm) of the
base of each flue within every masonry chimney. The upper
edge of the cleanout shall be located at least 6 inches (152
mm) below the lowest chimney inlet opening. The height of
the opening shall be at least 6 inches (152 mm). The cleanout
shall be provided with a noncombustible cover.
Exception: Chimney flues serving masonry fireplaces,
where cleaning is possible through the fireplace opening.
2113.19 Chimney clearances. Any portion of a masonry
chimney located in the interior of the building or within the
exterior wall of the building shall have a minimum airspace
clearance to combustibles of 2 inches (51 mm). Chimneys
located entirely outside the exterior walls of the building,
including chimneys that pass through the soffit or cornice,
shall have a minimum airspace clearance of 1 inch (25 mm).
The airspace shall not be filled, except to provide
fireblocking in accordance with Section 2113.20.
Exceptions:
1. Masonry chimneys equipped with a chimney lining
system listed and labeled for use in chimneys in con-
tact with combustibles in accordance with UL 1777,
and installed in accordance with the manufacturer' s
instructions, are permitted to have combustible mate-
rial in contact with their exterior surfaces.
2. Where masonry chimneys are constructed as part of
masonry or concrete walls, combustible materials
shall not be in contact with the masonry or concrete
wall less than 12 inches (305 mm) from the inside sur-
face of the nearest flue lining.
3. Exposed combustible trim and the edges of sheathing
materials, such as wood siding, are permitted to abut
the masonry chimney sidewalls, in accordance with
Figure 2113.19, provided such combustible trim or
sheathing is a minimum of 12 inches (305 mm) from
the inside surface of the nearest flue lining. Combusti-
ble material and trim shall not overlap the comers of
the chimney by more than 1 inch (25 mm).
MASONRY ABUmr^
COMBUSTIBLE SHEATHING
12"FR0MFyJEUNING
r CLEAFIANC^ (At F^PACE)
TOOCSVIBUSTIBIE SHEATHII^
For SI: 1 inch = 25.4 mm.
FIGURE 2113.19
ILLUSTRATION OF EXCEPTION THREE
CHIMNEY CLEARANCE PROVISION
2113.20 Chimney fireblocking. All spaces between chimneys
and floors and ceilings through which chimneys pass shall be
fireblocked with noncombustible material securely fastened in
place. The fireblocking of spaces between wood joists, beams
or headers shall be to a depth of 1 inch (25 mm) and shall only
be placed on strips of metal or metal lath laid across the spaces
between combustible material and the chimney.
SECTION 2114
ADDITIONAL REQUIREMENTS [DSA-SS/CC]
2114.1 General In addition to the provisions of this chapter,
the following requirements shall apply to community college
buildings regulated by the Division of the State Archi-
tect-Structural Safety/Community Colleges (DSA-SS/CC).
2114,1.1 Prohibitions. The following design, systems and
materials are not permitted by DSA:
L Unreinforced masonry
2. Autoclaved aerated concrete (AAC) masonry
3. Empirical design of masonry
4. Ordinary reinforced masonry shear walls
5. Intermediate reinforced masonry shear walls
6. Prestressed masonry shear walls
2114.2 Mortar. Mortar for use in masonry construction shall
conform to ASTM C270 Type S or M, except for mortars listed
in Sections 2103.9 and 2103,10. Type S mortar conforming to
ASTM C270 shall be used for glass unit masonry,
2114.3 Additives and Admixtures.
2114.3.1 General Additives and admixtures to mortar or
grout shall not be used unless approved by the enforcement
agency.
2114.3.2 Antifreeze compounds. Antifreeze liquids, chlo-
ride salts or other such substances shall not be used in mor-
tar or grout.
2114.3.3 Air entrainment. Air-entraining substances shall
not be used in mortar or grout unless tests are conducted to
determine compliance with the requirements of this code.
2114.4 Tolerances. The maximum thickness of the initial bed
joint in fully grouted masonry walls shall not exceed V/4 in.
(31.7 mm).
2114.5 Glass unit masonry. All mortar for glass unit masonry
contact surfaces shall be treated to ensure adhesion between
mortar and glass,
2114.6 Grouted masonry.
2114.6.1 General conditions. Prior to grouting, the grout
space shall be clean so that all spaces to be filled with grout
do not contain mortar projections greater than % inch (6.4
mm), mortar droppings and other foreign material.
Reinforcement shall be clean, properly positioned and
solidly embedded in the grout.
The grouting of any section of wall shall be completed in
one day with no interruptions greater than one hour At the
time of laying, all masonry units shall be free of dust and dirt.
<
<
2010 CALIFORNIA BUILDING CODE
291
MASONRY
>
>
Between grout pours, a horizontal construction joint
shall be formed by stopping all wythes at the same elevation
and with the grout stopping a minimum of V/2 inches (38
mm) below a mortar joint, except at the top of the wall
Where bond beams occur, the grout pour shall be stopped a
minimum of^/j inch (12.7 mm) below the top of the masonry.
The construction documents shall completely describe
grouting procedures, subject to approval ofDSA.
2114,6,2 Construction requirements. Reinforcement and
embedded items shall be placed and securely anchored
against moving prior to grouting. Bolts shall be accurately
set with templates or by approved equivalent means and
held in place to prevent dislocation during grouting.
Grout shall be consolidated by mechanical vibration dur-
ing placement before loss of plasticity in a manner to fill the
grout space. Grout pours greater than 12 inches (300 mm)
in height shall be reconsolidated by mechanical vibration to
minimize voids due to water loss. Grout not mechanically
vibrated shall be puddled.
2114.7 Aluminum equipment. Grout shall not be handled nor
pumped utilizing aluminum equipment unless it can be demon-
strated with the materials and equipment to be used that there
will be no deleterious effect on the strength of the grout.
2114.8 Specified compressive strength. The specified com-
pressive strength, /'^ , assumed in design shall be not less than
1,500 psi (10.34 MPa) for all masonry construction using
materials and details of construction required herein. Testing
of the constructed masonry shall be provided in accordance
with Section 2105.4.
In no case shall thef^^ assumed in design exceed 3,000 psi
(20.68 MPa).
2114.9 Additional testing requirements,
2114.9.1 Mortar and grout tests. At the beginning of all
masonry work, at least one test sample of the mortar and
grout shall be taken on three successive working days and at
least at one-week intervals thereafter They shall meet the
minimum strength requirement given in Sections 2103.8
and 2103.12 for mortar and grout, respectively. Additional
samples shall be taken whenever any change in materials or
job conditions occur, or whenever in the judgment of the
architect, structural engineer or the enforcement agency
such tests are necessary to determine the quality of the
material. When the prism test method of Section 2105.2.2.2
is used, the tests in this section are not required.
Test specimens for mortar and grout shall be made as set
forth in ASTM C 1586 andASTM C 1019
2114.9.2 Prism test method.
2114,9,2,1 Number of prisms per test. Prior to the start
of construction, three prisms shall be constructed and
tested in accordance with ASTM C 1314. A set of three
masonry prisms shall be built during construction in
accordance with ASTM C 13 14 for each 5,000 square feet
(465 m^) of wall area, but not less than one set of three
prisms for the project. Each set of prisms shall equal or
exceed f'^.
2114,9,2,2 Testing prisms from constructed masonry.
Acceptance of masonry that does not meet the require-
ments of Sections 2114.10.1 or 2114.10.2.3 may be
based on prism tests conducted in accordance with Sec-
tion 2105.3.
2114,9,3 Masonry core testing. Not less than two cores
shall be taken from each building for each 5,000 square feet
(465 m^) of the greater of the masonry wall area or the floor
area or fraction thereof The architect or structural engi-
neer in responsible charge of the project or his or her repre-
sentative (inspector) shall select the areas for sampling.
Cores shall be a minimum of 3 % inches (76 mm) in diame-
ter and shall be taken in such a manner as to exclude
masonry unit webs and reinforcing steel. The inspector of
record or testing agency shall inspect the coring of the
masonry walls.
Visual examination of all cores shall be made and the con-
dition of the cores reported. One half of the number of cores
taken shall be tested in shear. The shear test shall test both
joints between the grout core and the outside wythes or face
shells of the masonry. Shear testing apparatus shall be of a
design approved by the enforcement agency. Core samples
shall not be soaked before testing. The unit shear on the
cross section of the core shall not be less than 2.5 y'mPsi,
All cores shall be submitted to the laboratory for exami-
nation regardless of whether the core specimens failed dur-
ing cutting operation. The laboratory shall report the
location where each core was taken, the findings of their
visual examination of each core, identify which cores were
selected for shear testing and the results of the shear tests.
2114,10 Modifications to TMS 402/ACI 530/ASCE 5,
2114, 10,1 Modify TMS 402/ACl 530/ASCE 5, Section 1.17
as follows:
1, Minimum reinforcement requirements for masonry
walls. The total area of reinforcement in reinforced
masonry walls shall not be less than 0.003 times the
sectional area of the wall. Neither the horizontal nor
the vertical reinforcement shall be less than one third
of the total. Horizontal and vertical rebars shall be
spaced at not more than 24 inches (610 mm) center to
center. The minimum reinforcing shall be No. 4,
except that No. 3 bars may be used for ties and stir-
rups. Vertical wall steel shall have dowels of equal
size and equal matched spacing in all footings. Rein-
forcement shall be continuous around wall comers
and through intersections. Only reinforcement which
is continuous in the wall shall be considered in com-
puting the minimum area of reinforcement. Rein-
forcement with splices conforming to TMS 402/ACI
530/ASCE 5 as modified by Section 2107 shall be
considered as continuous reinforcement.
Horizontal reinforcement shall be provided in the
top of footings, at the top of wall openings, at roof and
floor levels, and at the top of parapet walls. For walls
12 inches (nominal) (305 mm) or more in thickness,
reinforcing shall be equally divided into two layers,
except where designed as retaining walls. Where
»
292
2010 CALIFORNIA BUILDING CODE
MASONRY
fi
1 1
>
II
reinforcement is added above the minimum require-
ments, such additional reinforcement need not be so
divided.
In bearing walls of every type of reinforced
masonry, there shall not be less than one No. 5 bar or
two No. 4 bars on all sides of and adjacent to, every
opening which exceeds 16 inches (406 mm) in either
direction, and such bars shall extend not less than 48
diameters, but in no case less than 24 inches (610
mm) beyond the corners of the opening. The bars
required by this paragraph shall be in addition to the
minimum reinforcement elsewhere required.
When the reinforcement in bearing walls is
designed, placed and anchored in position as for col-
umns, the allowable stresses shall be as for columns.
Joint reinforcement shall not be used as principal
reinforcement in masonry designed by the strength
design method.
2. Minimum reinforcement for masonry columns. The
spacing of column ties shall be as follows: not greater
than 8 bar diameters, 24 tie diameters, or one half the
least dimension of the column for the full column
height. Ties shall be at least % inch (10 mm) in diame-
ter and shall be embedded in grout. Top tie shall be
within 2 inches (51 mm) of the top of the column or of
the bottom of the horizontal bar in the supported
beam.
2114.11 Additional requirements for Allowable Stress
Design.
2114.1U IMS 402/ACI 530/ASCE 5. Modify by adding
Sections 2.1.4.3.4 and 2.1.4.3.5 as follows. '
2.1.4.3.4 - Edge distance and spacing. Where the anchor
bolt edge distance, Ibe, in the direction of load is less
than 12 bolt diameters, the value ofB^ in Formula (2-7)
shall be reduced by linear interpolation to zero at an 4^
distance of V/2 inches (38 mm) and confining reinforce-
ment consisting of not less than No. 3 hairpins, hooks or
stirrups for end bolts and between horizontal reinforcing
for other bolts shall be provided. Where adjacent anchors
are spaced closer than Sd^, the allowable shear of the
adjacent anchors determined by Formula (2-7) shall be
reduced by linear interpolation to 0. 75 times the allow-
able shear value at a center-to-center spacing of four bolt
diameters.
2.1.4.3.5 - Anchor bolts size and materials. Anchor bolts
shall be hex headed bolts conforming to ASTM A 307 or
F1554 with the dimensions of the hex head conforming to
ANS1/ASMEB18.2.1 or plain rod conforming to ASTM A
36 with threaded ends and double hex nuts at the anchored
end. Bent bar anchor bolts shall not be used.
The maximum size anchor shall be ^/2-inch (13 mm)
diameter for 6-inch (152 mm) nominal masonry, ^/ 4-inch
(19 mm) diameter for 8-inch (203 mm) nominal masonry,
Vg-inch (22 mm) diameter for 10-inch (254 mm) nominal
masonry, and 1-inch (25 mm) diameter for 12-inch
(304.8 mm) nominal masonry.
2114.11.2 TMS 402/ACI 530/ASCE 5, Section 2.1.8. Mod-
ify by adding the following:
Structural members framing into or supported by walls or
columns shall be securely anchored. The end support of
girders, beams or other concentrated loads on masonry
shall have at least 3 inches (76 mm) in length upon solid
bearing not less than 4 inches (102 mm) thick or upon
metal bearing plate of adequate design and dimensions to
distribute the loads safely on the wall or pier, or upon a
continuous reinforced masonry member projecting not
less than 3 inches (76 mm) from the face of the wall or
other approved methods.
Joists shall have bearing at least 3 inches (76 mm) in
length upon solid masonry at least 2^/2 inches (64 mm)
thick, or other provisions shall be made to distribute
safely the loads on the wall or pier
2114.11.3 TMS 402/ACI 530/ASCE 5 [DSA-SS/CC] Mod-
ify by adding Section 2.1.10 as follows:
2.1.10 - Walls and piers.
Thickness of walls. For thickness limitations of walls as
specified in this chapter, nominal thickness shall be used.
Stresses shall be determined on the basis of the net thick-
ness of the masonry, with consideration for reduction,
such as raked joints.
The thickness of masonry walls shall be designed so
that allowable maximum stresses specified in this chap-
ter are not exceeded. Also, no masonry wall shall exceed
the height or length-to-thickness ratio or the minimum
thickness as specified in this chapter and as set forth in
Table 2114.11.3.
Piers. Every pier or wall section which width is less than
three times its thickness shall be designed and con-
structed as required for columns if such pier is a struc-
tural member. Every pier or wall section which width is
between three and five times its thickness or less than one
half the height of adjacent openings shall have all hori-
zontal steel in the form of ties except that in walls 12
inches (305 mm) or less in thickness such steel may be in
the form of hair-pins.
2010 CALIFORNIA BUILDING CODE
293
MASONRY
TABLE 2114.11.3
MINIMUM THICKNESS OF MASONRY WALLS^'^ [DSA-SS/CC]
TYPE OF MASONRY
MAXIMUM RATIO
UNSUPPORTED
HEIGHT OR LENGTH
TO THICKNES^'^
NOMINAL
MINIMUM
THICKNESS
(inches)
BEARING OR SHEAR WALLS:
L Stone masonry
2. Reinforced grouted masonry
3. Reinforced hollow-unit masonry
14
25
25
16
6
6
NONBEARING WALLS:
4. Exterior reinforced walls
5. Interior partitions reinforced
30
36
6
4
1. For walls of varying thickness, use the least thickness when determining the
height or length to thickness ratio.
2. In determining the height or length-to-thickness ratio of a cantilevered wall
the dimension to be used shall be twice the dimension of the end of the wall
from the lateral support.
3. Cantilevered walls not part of a building and not carrying applied vertical
loads need not meet these minimum requirements hut their design must com-
ply with stress and overturning requirements.
2114.12 Glass unit masonry construction. Masonry of glass
blocks shall be permitted in nonload- bearing exterior or inte-
rior walls and shall conform to the requirements of Section
2114.14. Stresses in glass block shall not be utilized. Glass
block may be solid or hollow and may contain inserts.
2114.13 Nonbearing walls. All nonbearing masonry walls
shall be reinforced as specified in Section 2114.11. 1. 1. Fences
and interior nonbearing nonshear walls may be of hollow-unit
masonry construction grouted in cells containing vertical and
horizontal reinforcement Nonbearing walls may be used to
carry a superimposed load of not more than 200 pounds per
linear foot (2.92 kN/m).
1, Thickness, Every nonbearing masonry wall shall be so
constructed and have a sufficient thickness to withstand
all vertical loads and horizontal loads, but in no case
shall the thickness of such walls be less than the values
set forth in Table 2114.11.3.
Plaster shall not be considered as contributing to the
thickness of a wall in computing the height-to-thickness
ratio.
2, Anchorage, All nonbearing walls shall be anchored as
required by Section 1604.8.2 and ASCE 7 Chapter 13.
Suspended ceilings or other nonstructural elements
shall not be used to provide anchorage for masonry
walls.
2114,14 Masonry screen walls. Masonry units may be used in
nonbearing decorative screen walls. Units may be laid up in
panels with units on edge with the open pattern of the unit
exposed in the completed wall.
1, Horizontal Forces, The panels shall be capable of span-
ning between supports to resist the horizontal forces
specified in Chapter 16. Wind loads shall be based on
gross projected area of the block.
2, Mortar Joints, Horizontal and vertical joints shall not
be less than V^ inch (6 mm) thick. All joints shall be com-
pletely filled with mortar and shall be "shoved joint"
work. The units of a panel shall be so arranged that
either the horizontal or the verticaljoint containing rein-
forcing is continuous without offset. This continuous
joint shall be reinforced with a minimum of 0.03 square
inch (19mm^) of reinforcing steel. Reinforcement may be
embedded in mortar.
3, Reinforcing, Joint reinforcing may be composed of two
wires made with welded ladder or trussed wire cross ties.
In calculating the resisting capacity of the system, com-
pression and tension in the spaced wires may be utilized.
Ladder wire reinforcing shall not be spliced and shall be
the widest that the mortar joint will accommodate,
allowing V2 inch (13 mm) of mortar cover.
4, Size of Panels, The maximum size of panels shall be 144
square feet (13.4 m^J, with the maximum dimension in
either direction of 15 feet (4572 mm).
5, Panel Support, Each panel shall be supported on all
edges by a structural member of concrete, masonry or
steel. Supports at the top and ends of the panel shall be by
means of confinement of the masonry by at least V2 i^ch
(13 mm) into and between the flanges of a steel channel.
The space between the end of the panel and the web of the
channel shall be filled with resilient material. The use of
equivalent configuration in other steel section or in
masonry or concrete is acceptable.
•
294
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 21 A - MASONRY
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire ciiapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
X
Chapter/Section
2113A.9.1
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.1 L
2010 CALIFORNIA BUILDING CODE
295
296 2010 CALIFORNIA BUILDING CODE
CHAPTER 214
MASONRY
II
II
II
SECTION 21014
GENERAL
2101A.1 Scope, This chapter shall govern the materials,
design, construction and quality of masonry.
2 101 A. 1.1 Application. The scope of application of Chap-
ter 21 A is as follows:
L Applications listed in Section 1,9. 2 A regulated by the
Division of the State Architect- Structural Safety
(DSA-SS). These applications include public elemen-
tary and secondary schools, community colleges and
state-owned or state-leased essential services build-
ings.
2. Applications listed in Sections 1,10.1, and LI 0.4 reg-
ulated by the Office of Statewide Health Planning and
Development (OSHPD).These applications include
hospitals, skilled nursing facilities, intermediate care
facilities and correctional treatment centers.
Exception: [OSHPD 2] Single-story Type V
skilled nursing or intermediate care facilities uti-
lizing wood-frame or light-steel-frame construc-
tion as defined in Health and Safety Code Section
129725, which shall comply with Chapter 21 and
any applicable amendments therein,
2 101 A. 1.2 Amendments in this chapter. DSA-SS adopts
this chapter and all amendments.
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1. Division of the State Architect-Structural Safety:
[DSA'SS] For applications listed in Section
1.9.2.1.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD 1] - For applications listed in Section
1.10,1.
[OSHPD 4] - For applications listed in Section
1,10.4.
2 101 A, 1.3 Prohibition: The following design, systems, and
materials are not permitted by DSA-SS and OSHPD:
1. Unreinforced masonry
2. Autoclaved aerated concrete (AAC) masonry
3. Empirical design of masonry
4. Adobe construction
5. Ordinary reinforced masonry shear walls
6. Intermediate reinforced masonry shear walls
7. Prestressed masonry shear walls
210M.2 Design methods. Masonry shall comply with the pro-
visions of one of the following design methods in this chapter
as well as the requirements of Sections 2101A through 2104A.
Masonry designed by the allowable stress design provisions of
Section 2101A.2.1, the strength design provisions of Section
2101A.2.2 or the prestressed masonry provisions of Section
2101A.2.3 shall comply with Section 2105A.
2101A.2.1 Allowable stress design. Masonry designed by
the allowable stress design method shall comply with the
provisions of Sections 2106A and 2107A.
2101A.2.2 Strength design. Masonry designed by the
strength design method shall comply with the provisions of
Sections 2106A and 2108A.
2101A.2.3 Prestressed masonry. Not permitted by DSA-SS
and OSHPD.
210M.2.4 Empirical design. Not permitted by DSA-SS and
OSHPD.
210L4.2.5 Glass unit masonry. Glass unit masonry shall
comply with the provisions of Section 2110A.
2101A.2.6 Masonry veneer. Masonry veneer shall comply
with the provisions of Chapter 14 or Chapter 6 of TMS
402/ACI530/ASCE5.
2101A.3 Construction documents. The construction docu-
ments shall show all of the items required by this code includ-
ing the following:
1. Specified size, grade, type and location of reinforce-
ment, anchors and wall ties.
2. Reinforcing bars to be welded and welding procedure.
3. Size and location of structural elements.
4. Provisions for dimensional changes resulting from elas-
tic deformation, creep, shrinkage, temperature and mois-
ture.
5. Loads used in the design of masonry.
6. Specified compressive strength of masonry at stated ages
or stages of construction for which masonry is designed,
except where specifically exempted by this code.
7. Details of anchorage of masonry to structural members,
frames and other construction, including the type, size
and location of connectors.
8. Size and location of conduits, pipes and sleeves.
9. The minimum level of testing and inspection as defined
in Chapter 17A, or an itemized testing and inspection
program that meets or exceeds the requirements of Chap-
ter 17A.
2101A.3.1 Fireplace drawings. The construction docu-
ments shall describe in sufficient detail the location, size and
construction of masonry fireplaces. The thickness and char-
<
<
2010 CALIFORNIA BUILDING CODE
297
MASONRY
acteristics of materials and the clearances from walls, parti-
tions and ceilings shall be indicated.
SECTION 21 02iA
DEFINITIONS AND NOTATIONS
2102A. 1 General. The following words and terms shall, for the
purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
AAC MASONRY. Masonry made of autoclaved aerated con-
crete (AAC) units, manufactured without internal reinforce-
ment and bonded together using thin- or thick-bed mortar.
ADOBE CONSTRUCTION. Construction in which the exte-
rior load-bearing and nonload-bearing walls and partitions are
of unfired clay masonry units, and floors, roofs and interior
framing are wholly or partly of wood or other approved materi-
als.
Adobe, stabilized. Unfired clay masonry units to which
admixtures, such as emulsified asphalt, are added during the
manufacturing process to limit the units' water absorption
so as to increase their durability.
Adobe, unstabilized. Unfired clay masonry units that do
not meet the definition of "Adobe, stabilized."
ANCHOR. Metal rod, wire or strap that secures masonry to its
structural support.
ARCHITECTURAL TERRA COTTA. Plain or ornamental
hard-burned modified clay units, larger in size than brick, with
glazed or unglazed ceramic finish.
AREA.
Bedded. The area of the surface of a masonry unit that is in
contact with mortar in the plane of the joint.
Gross cross-sectional. The area delineated by the out-
to-out specified dimensions of masonry in the plane under
consideration.
Net cross-sectional. The area of masonry units, grout and
mortar crossed by the plane under consideration based on
out-to-out specified dimensions.
AUTOCLAVED AERATED CONCRETE (AAC). Low-
density cementitious product of calcium silicate hydrates,
whose material specifications are defined in ASTM C 1386.
BED JOINT. The horizontal layer of mortar on which a
masonry unit is laid.
BOND BEAM. A horizontal grouted element within masonry
in which reinforcement is embedded.
BRICK.
Calcium silicate (sand lime brick). A masonry unit made
of sand and lime.
Clay or shale. A masonry unit made of clay or shale, usu-
ally formed into a rectangular prism while in the plastic state
and burned or fired in a kiln.
Concrete. A masonry unit having the approximate shape of
a rectangular prism and composed of inert aggregate parti-
cles embedded in a hardened cementitious matrix.
CAST STONE. A building stone manufactured from portland
cement concrete precast and used as a trim, veneer or facing on
or in buildings or structures.
CELL. A void space having a gross cross- sectional area
greater than IV2 square inches (967 mm^).
CHIMNEY. A primarily vertical enclosure containing one or
more passageways for conveying flue gases to the outside
atmosphere.
CHIMNEY TYPES.
High-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
high-heat appliances producing combustion gases in excess
of 2,000°F (1093°C) measured at the appliance flue outlet
(see Section 21 13A.1 1.3).
Low-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
low-heat appliances producing combustion gases not in
excess of 1,000°F (538°C) under normal operating condi-
tions, but capable of producing combustion gases of
1,400°F (760°C) during intermittent forces firing for peri-
ods up to 1 hour. Temperatures shall be measured at the
appliance flue outlet.
Masonry type. A field-constructed chimney of solid
masonry units or stones.
Medium-heat appliance type. An approved chimney for
removing the products of combustion from fuel-burning,
medium-heat appliances producing combustion gases not
exceeding 2,000°F (1093°C) measured at the appliance flue
outlet (see Section 21 13A. 1 1 .2).
CLEANOUT. An opening to the bottom of a grout space of
sufficient size and spacing to allow the removal of debris.
COLLAR JOINT. Vertical longitudinal joint between wythes
of masonry or between masonry and backup construction that
is permitted to be filled with mortar or grout. ^
COMPRESSIVE STRENGTH OF MASONRY. Maximum
compressive force resisted per unit of net cross-sectional area
of masonry, determined by the testing of masonry prisms or a
function of individual masonry units, mortar and grout.
CONNECTOR. A mechanical device for securing two or
more pieces, parts or members together, including anchors,
wall ties and fasteners.
COVER. Distance between surface of reinforcing bar and
edge of member. ^
DIMENSIONS.
Actual. The measured dimension of a masonry unit or ele-
ment.
Nominal. The specified dimension plus an allowance for
the joints with which the units are to be laid. Thickness is
given first, followed by height and then length.
Specified. The dimensions specified for the manufacture or
construction of masonry, masonry units, joints or any other
component of a structure. ^
298
2010 CALIFORNIA BUILDING CODE
MASONRY
FIREPLACE. A hearth and fire chamber or similar prepared
place in which a fire may be made and which is built in con-
junction with a chimney.
FIREPLACE THROAT, The opening between the top of the
firebox and the smoke chamber.
FOUNDATION PIER. An isolated vertical foundation mem-
ber whose horizontal dimension measured at right angles to its
thickness does not exceed three times its thickness and whose
height is equal to or less than four times its thickness.
GROUTED MASONRY.
Grouted hollow-unit masonry. That form of grouted
masonry construction in which certain designated cells of
hollow units are continuously filled with grout.
Grouted multiwythe masonry. That form of grouted
masonry construction in which the space between the
wythes is solidly or periodically filled with grout.
HEAD JOINT. Vertical mortar joint placed between masonry
units within the wythe at the time the masonry units are laid.
HEIGHT, WALLS. The vertical distance from the foundation
wall or other immediate support of such wall to the top of the
wall.
MASONRY. A built-up construction or combination of build-
ing units or materials of clay, shale, concrete, glass, gypsum,
stone or other approved units bonded together with or without
mortar or grout or other accepted methods of joining.
Ashlar masonry. Masonry composed of various-sized rect-
angular units having sawed, dressed or squared bed sur-
faces, properly bonded and laid in mortar.
Coursed ashlar. Ashlar masonry laid in courses of stone of
equal height for each course, although different courses
shall be permitted to be of varying height.
Glass unit masonry. Masonry composed of glass units
bonded by mortar.
Plain masonry. Masonry in which the tensile resistance of
the masonry is taken into consideration and the effects of
stresses in reinforcement are neglected.
Random ashlar. Ashlar masonry laid in courses of stone set
without continuous joints and laid up without drawn pat-
terns. When composed of material cut into modular heights,
discontinuous but aligned horizontal joints are discernible.
Reinforced masonry. Masonry construction in which rein-
forcement acting in conjunction with the masonry is used to
resist forces.
Solid masonry. Masonry consisting of solid masonry units
laid contiguously with the joints between the units filled
with mortar.
Unreinforced (plain) masonry. Masonry in which the ten-
sile resistance of masonry is taken into consideration and
the resistance of the reinforcing steel, if present, is
neglected.
MASONRY UNIT. Brick, tile, stone, glass block or concrete
block conforming to the requirements specified in Section
2103A.
Clay. A building unit larger in size than a brick, composed
of burned clay, shale, fired clay or mixtures thereof.
Concrete. A building unit or block larger in size than 12
inches by 4 inches by 4 inches (305 mm by 102 mm by 102
mm) made of cement and suitable aggregates.
Hollow. A masonry unit whose net cross-sectional area in
any plane parallel to the load-bearing surface is less than 75
percent of its gross cross-sectional area measured in the
same plane.
Solid. A masonry unit whose net cross- sectional area in
every plane parallel to the load-bearing surface is 75 percent
or more of its gross cross-sectional area measured in the
same plane.
MORTAR. A plastic mixture of approved cementitious mate-
rials, fine aggregates and water used to bond masonry or other
structural units.
MORTAR, SURFACE-BONDING. A mixture to bond con-
crete masonry units that contains hydraulic cement, glass fiber
reinforcement with or without inorganic fillers or organic mod-
ifiers and water.
PRESTRESSED MASONRY. Masonry in which internal
stresses have been introduced to counteract potential tensile
stresses in masonry resulting from applied loads.
PRISM. An assemblage of masonry units and mortar with or
without grout used as a test specimen for determining proper-
ties of the masonry.
RUBBLE MASONRY. Masonry composed of roughly
shaped stones.
Coursed rubble. Masonry composed of roughly shaped
stones fitting approximately on level beds and well bonded.
Random rubble. Masonry composed of roughly shaped
stones laid without regularity of coursing but well bonded
and fitted together to form well-divided joints.
Rough or ordinary rubble. Masonry composed of
unsquared field stones laid without regularity of coursing
but well bonded.
RUNNING BOND. The placement of masonry units such that
head joints in successive courses are horizontally offset at least
one-quarter the unit length.
SHEAR WALL.
Detailed plain masonry shear wall. A masonry shear wall
designed to resist lateral forces neglecting stresses in rein-
forcement, and designed in accordance with Section
2106A1.
Intermediate prestressed masonry shear wall. A pre-
stressed masonry shear wall designed to resist lateral forces
considering stresses in reinforcement, and designed in
accordance with Section 2106A. 1.
Intermediate reinforced masonry shear wall. A masonry
shear wall designed to resist lateral forces considering
stresses in reinforcement, and designed in accordance with
Section 2 106A.1.
2010 CALIFORNIA BUILDING CODE
299
MASONRY
Ordinary plain masonry shear wall. A masonry shear
wall designed to resist lateral forces neglecting stresses in
reinforcement, and designed in accordance with Section
2106A.1.
Ordinary plain prestressed masonry shear wall. A pre-
stressed masonry shear wall designed to resist lateral forces
considering stresses in reinforcement, and designed in
accordance with Section 2106A.1.
Ordinary reinforced masonry shear wall. A masonry
shear wall designed to resist lateral forces considering
stresses in reinforcement, and designed in accordance with
Section 2 106A1.
Special prestressed masonry shear wall. A prestressed
masonry shear wall designed to resist lateral forces consid-
ering stresses in reinforcement and designed in accordance
with Section 2106A.1 except that only grouted, laterally
restrained tendons are used.
Special reinforced masonry shear wall. A masonry shear
wall designed to resist lateral forces considering stresses in
reinforcement, and designed in accordance with Section
2106A1.
SHELL. The outer portion of a hollow masonry unit as placed
in masonry.
SPECIFIED. Required by construction documents.
SPECIFIED COMPRESSIVE STRENGTH OF
MASONRY,/'^. Minimum compressive strength, expressed
as force per unit of net cross- sectional area, required of the
masonry used in construction by the construction documents,
and upon which the project design is based. Whenever the
quantity/'^ is under the radical sign, the square root of numeri-
cal value only is intended and the result has units of pounds per
square inch (psi) (MPa).
STACK BOND. The placement of masonry units in a bond
pattern is such that head joints in successive courses are verti-
cally aligned. For the purpose of this code, requirements for
stack bond shall apply to masonry laid in other than running
bond.
STONE MASONRY. Masonry composed of field, quarried or
cast stone units bonded by mortar.
Ashlar stone masonry. Stone masonry composed of rect-
angular units having sawed, dressed or squared bed surfaces
and bonded by mortar.
Rubble stone masonry. Stone masonry composed of irreg-
ular-shaped units bonded by mortar.
STRENGTH.
Design strength. Nominal strength multiplied by a strength
reduction factor.
Nominal strength. Strength of a member or cross section
calculated in accordance with these provisions before appli-
cation of any strength-reduction factors.
Required strength. Strength of a member or cross section
required to resist factored loads.
THIN-BED MORTAR. Mortar for use in construction of
AAC unit masonry with joints 0.06 inch (1.5 mm) or less.
TIE, LATERAL. Loop of reinforcing bar or wire enclosing
longitudinal reinforcement.
TIE, WALL. A connector that connects wythes of masonry
walls together.
TILE. A ceramic surface unit, usually relatively thin in relation
to facial area, made from clay or a mixture of clay or other
ceramic materials, called the body of the tile, having either a
"glazed" or "unglazed" face and fired above red heat in the
course of manufacture to a temperature sufficiently high
enough to produce specific physical properties and characteris-
tics.
TILE, STRUCTURAL CLAY. A hollow masonry unit com-
posed of burned clay, shale, fire clay or mixture thereof, and
having parallel cells.
WALL. A vertical element with a horizontal length-to-thick-
ness ratio greater than three, used to enclose space.
Cavity wall. A wall built of masonry units or of concrete, or
a combination of these materials, arranged to provide an air-
space within the wall, and in which the inner and outer parts
of the wall are tied together with metal ties.
Composite wall. A wall built of a combination of two or
more masonry units bonded together, one forming the
backup and the other forming the facing elements.
Dry-stacked, surface-bonded wall. A wall built of con-
crete masonry units where the units are stacked dry, without
mortar on the bed or head joints, and where both sides of the
wall are coated with a surface-bonding mortar.
Hollow-unit masonry wall Type of construction made with
hollow masonry units in which the units are laid and set in
mortar, reinforced and grouted solid except as provided in
Section 2114A.
Masonry-bonded hollow wall. A wall built of masonry
units so arranged as to provide an airspace within the wall,
and in which the facing and backing of the wall are bonded
together with masonry units.
Parapet wall. The part of any wall entirely above the roof
line.
WEB. An interior solid portion of a hollow masonry unit as
placed in masonry.
WYTHE. Each continuous, vertical section of a wall, one
masonry unit in thickness.
NOTATIONS.
d^ = Diameter of reinforcement, inches (nmi).
F^ = Allowable tensile or compressive stress in reinforce-
ment, psi (MPa).
/, = Modulus of rupture, psi (MPa).
/ A4C = Specified compressive strength of AAC masonry, the
minimum compressive strength for a class of AAC
masonry as specified in ASTM C 1386, psi (MPa).
f'^ = Specified compressive strength of masonry at age of 28
days, psi (MPa).
f'^i = Specified compressive strength of masonry at the time
of prestress transfer, psi (MPa).
300
2010 CALIFORNIA BUILDING CODE
MASONRY
K = The lesser of the masonry cover, clear spacing between
adjacent reinforcement, or five times d^,, inches (mm).
Ls = Distance between supports, inches (mm).
l^ = Required development length or lap length of rein-
forcement, inches (mm).
P - The applied load at failure, pounds (N).
Sf = Thickness of the test specimen measured parallel to the
direction of load, inches (mm).
S^ = Width of the test specimen measured parallel to the
loading cylinder, inches (mm).
SECTION 21034
MASONRY CONSTRUCTION MATERIALS
2103A.1 Concrete masonry units. Concrete masonry units
shall conform to the following standards: ASTM C 55 for con-
crete brick; ASTM C 73 for calcium silicate face brick; ASTM
C 90 for load-bearing concrete masonry units or ASTM C 744
for prefaced concrete and calcium silicate masonry units.
2103A.2 Clay or shale masonry units. Clay or shale masonry
units shall conform to the following standards: ASTM C 34 for
structural clay load-bearing wall tile; ASTM C 56 for struc-
tural clay nonload-bearing wall tile; ASTM C 62 for building
brick (solid masonry units made from clay or shale); ASTM C
1088 for soHd units of thin veneer brick; ASTM C 126 for
ceramic-glazed structural clay facing tile, facing brick and
solid masonry units; ASTM C 212 for structural clay facing
tile; ASTM C 216 for facing brick (soHd masonry units made
from clay or shale); ASTM C 652 for hollow brick (hollow
masonry units made from clay or shale) or ASTM C 1405 for
glazed brick (single-fired solid brick units).
Exception: Structural clay tile for nonstructural use in fire-
proofing of structural niembers and in wall furring shall not
be required to meet the compressive strength specifications.
The fire-resistance rating shall be determined in accordance
with ASTM E 119 or UL 263 and shall comply with the
requirements of Table 602.
M 2103A,3 AAC mBSonry. Not permitted.
2103A.4 Stone masonry units. Stone masonry units shall con-
form to the following standards: ASTM C 503 for marble
building stone (exterior); ASTM C 568 for Hmestone building
stone; ASTM C 615 for granite building stone; ASTM C 616
for sandstone building stone; or ASTM C 629 for slate building
stone.
2103A.5 Ceramic tile. Ceramic tile shall be as defined in, and
shall conform to the requirements of, ANSI A137.1.
2103A.6 Glass unit masonry. Hollow glass units shall be par-
tially evacuated and have a minimum average glass face thick-
ness of Vi6 inch (4.8 mm). SoHd glass-block units shall be
provided when required. The surfaces of units intended to be in
contact with mortar shall be treated with a polyvinyl butyral
coating or latex-based paint. Reclaimed units shall not be used.
2103A.7 Second-hand units. Second-hand masonry units
shall not be reused unless they conform to the requirements of
new units. The units shall be of whole, sound materials and free
from cracks and other defects that will interfere with proper
laying or use. Old mortar shall be cleaned from the unit before
reuse.
2103A. 8 Mortar, Mortar for use in masonry construction shall
conform to ASTM C 270 Type S orM, except for mortars listed
in Sections 2103A.9 and 2103 A. 10. Type S mortar conforming
to ASTM C 270 shall be used for glass unit masonry.
2103A.9 Surface-bonding mortar. Surface-bonding mortar
shall comply with ASTM C 887. Surface bonding of concrete
masonry units shall comply with ASTM C 946.
2103A.10 Mortars for ceramic wall and floor tile. Portland
cement mortars for installing ceramic wall and floor tile shall
comply with ANSI A108.1A and ANSI A108.1B and be of the
compositions indicated in Table 2103A.10.
TABLE 21034.10
CERAMIC TILE MORTAR COMPOSITIONS
<
<
LOCATION
MORTAR
COMPOSITION
Walls
Scratchcoat
1 cement; V5 hydrated lime;
4 dry or 5 damp sand
Setting bed and
leveling coat
1 cement; V2 hydrated lime;
5 damp sand to 1 cement
1 hydrated lime, 7 damp sand
Floors
Setting bed
1 cement; Vjq hydrated lime;
5 dry or 6 damp sand; or 1
cement; 5 dry or 6 damp sand
Ceilings
Scratchcoat and
sand bed
1 cement; Vj hydrated Ume;
2V2 dry sand or 3 damp sand
2103A.10.1 Dry-set portland cement mortars. Premixed
prepared portland cement mortars, which require only the
addition of water and are used in the installation of ceramic
tile, shall comply with ANSI A118.1. The shear bond
strength for tile set in such mortar shall be as required in
accordance with ANSI Al 18.1. Tile set in dry-set portland
cement mortar shall be installed in accordance with ANSI
A108.5.
2103A.10.2 Latex-modified portland cement mortar.
Latex-modified portland cement thin-set mortars in which
latex is added to dry-set mortar as a replacement for all or
part of the gauging water that are used for the installation of
ceramic tile shall comply with ANSI A118.4. Tile set in
latex-modified portland cement shall be installed in accor-
dance with ANSI A 108.5.
2103A10.3 Epoxy mortar. Ceramic tile set and grouted
with chemical-resistant epoxy shall comply with ANSI
Al 18.3. Tile set and grouted with epoxy shall be installed in
accordance with ANSI A 108. 6.
2103A.10.4 Furan mortar and grout. Chemical-resistant
furan mortar and grout that are used to install ceramic tile
shall comply with ANSI Al 18.5. Tile set and grouted with
furan shall be installed in accordance with ANSI A 108.8.
2103A.10.5 Modified epoxy-emulsion mortar and grout.
Modified epoxy-emulsion mortar and grout that are used to
install ceramic tile shall comply with ANSI Al 1 8.8. Tile set
and grouted with modified epoxy-emulsion mortar and
grout shall be installed in accordance with ANSI A 108.9.
2010 CALIFORNIA BUILDING CODE
301
MASONRY
'i
2103A.10.6 Organic adhesives. Water-resistant organic
adhesives used for the installation of ceramic tile shall com-
ply with ANSI A 1 3 6 . 1 . The shear bond strength after water
immersion shall not be less than 40 psi (275 kPa) for Type I
adhesive and not less than 20 psi (138 kPa) for Type II adhe-
sive when tested in accordance with ANSI A 136.1. Tile set
in organic adhesives shall be installed in accordance with
ANSIA108.4.
2103A.10.7 Portland cement grouts. Portland cement
grouts used for the installation of ceramic tile shall comply
with ANSI All 8.6. Portland cement grouts for tile work
shall be installed in accordance with ANSI A108.10.
2103A.11 Mortar for A AC masonry. Not permitted.
2103A.12 Grout. Grout shall comply with Article 2.2 of TMS
602/ACI530.1/ASCE6.
2103 A, 12,1 Water, Water content shall be adjusted to pro-
vide proper workability and to enable proper placement
under existing field conditions y without segregation.
2103A,12,2 Selecting proportions. Proportions of ingredi-
ents and any additives shall be based on laboratory or field
experience with the grout ingredients and the masonry units
to be used. For coarse grout, the coarse and fine aggregates
shall be combined such that the fine aggregate part is not
greater than 80 percent of the total aggregate weight
(mass). Coarse grout proportioned by weight shall contain
not less than 564 pounds of cementitious material per cubic
yard (335 kg/m^).
2103AA2,3 Aggregate, Coarse grout shall be used in grout
spaces 2 inches (51 mm) or more in width and in all
filled-cell masonry construction.
2103A.13 Metal reinforcement and accessories. Metal rein-
forcement and accessories shall conform to Article 2.4 of TMS
602/ACI 530.1/ASCE 6. Where unidentified reinforcement is
approved for use, not less than three tension and three bending
tests shall be made on representative specimens of the rein-
forcement from each shipment and grade of reinforcing steel
proposed for use in the work.
2103 A,14 Additives and admixtures,
2 103 A, 14,1 General, Additives and admixtures to mortar
or grout shall not be used unless approved by the enforce-
ment agency.
2103A,14,2 Antifreeze compounds. Antifreeze liquids,
chloride salts or other such substances shall not be used in
mortar or grout.
2 103 A, 14,3 Air entrainment. Air-entraining substances
shall not be used in mortar or grout unless tests are con-
ducted to determine compliance with the requirements of
this code.
SECTION 21044
CONSTRUCTION
2104A.1 Masonry construction. Masonry construction shall
comply with the requirements of Sections 2104A. 1.1 through
2104A.4 and with TMS 602/ACI 530.1/ASCE 6.
2104A.1.1 Tolerances. Masonry, except masonry veneer,
shall be constructed within the tolerances specified in TMS
602/ACI 530.1/ASCE 6.
Exception: The maximum thickness of the initial bed
joint in fully grouted masonry walls shall not exceed V/4
in. (31.7 mm).
2104A. 1.2 Placing mortar and units. Placement of mortar,
grout, and clay, concrete, and glass, masonry units shall
comply with TMS 602/ACI 530.1/ASCE 6. All mortar for
glass unit masonry contact surfaces shall be treated to
ensure adhesion between mortar and glass.
2104A.1.3 Installation of wall ties. Wall ties shall be
installed in accordance with TMS 602/ACI 530. 1/ASCE 6.
2104A.1.4 Chases and recesses. Chases and recesses shall
be constructed as masonry units are laid. Masonry directly
above chases or recesses wider than 12 inches (305 mm)
shall be supported on lintels.
2104A.1.5 Lintels. The design for lintels shall be in accor-
dance with the masonry design provisions of either Section
2107Aor2108A.
2104A.1.6 Support on wood. Masonry shall not be sup-
ported on wood girders or other forms of wood construction
except as permitted in Section 2304.12.
2104A1, 7 Grouted masonry. Grouted masonry shall be in
accordance with Section 2104A.5.
2104A.2 Corbeled masonry. Corbeled masonry shall comply
with the requirements of Section 1.12 of TMS 402/ ACI
530/ASCE 5.
2104A.2.1 Molded cornices. Unless structural support and
anchorage are provided to resist the overturning moment,
the center of gravity of projecting masonry or molded cor-
nices shall lie within the middle one-third of the supporting
wall. Terra cotta and metal cornices shall be provided with a
structural frame of approved noncombustible material
anchored in an approved manner.
2104A.3 Cold weather construction. The cold weather con-
struction provisions of TMS 602/ACI 530.1/ASCE 6, Article
1.8 C, shall be implemented when the ambient temperature
falls below 40°F (4°C).
2104A.4 Hot weather construction. The hot weather con-
struction provisions of TMS 602/ACI 530.1/ASCE 6, Article
1 .8 D, shall be implemented when the ambient air temperature
exceeds 100°F (37.8°C), or 90°F (32.2°C) with a wind velocity
greater than 8 mph (12.9 km/hr) .
2104A,5 Grouted masonry,
2104A.5,1 General conditions. Grouted masonry shall be
constructed in such a manner that all elements of the
masonry act together as a structural element. Prior to
grouting, the grout space shall be clean so that all spaces to
be filled with grout do not contain mortar projections
greater than V^ inch (6.4 mm), mortar droppings and other
foreign material. Grout shall be placed so that all spaces to
be grouted do not contain voids.
Grout materials and water content shall be controlled to
provide adequate fluidity for placement without segregation
302
2010 CALIFORNIA BUILDING CODE
MASONRY
of the constituents, and shall be mixed thoroughly. Rein-
forcement shall be clean, properly positioned and solidly
embedded in the grout.
The grouting of any section of wall shall be completed in
one day with no interruptions greater than 1 hour.
Between grout pours, a horizontal construction joint
shall be formed by stopping all wythes at the same eleva-
tion and with the grout stopping a minimum of IV2 inches
(38 mm) below a mortar joint, except at the top of the wall.
Where bond beams occur, the grout pour shall be stopped a
minimum of V2 inch (12.7 mm) below the top of the
masonry.
2104A,5,1,1 Reinforced grouted masonry.
2104A.5.1J.1 General Reinforced grouted masonry
is that form of construction made with clay or shale
brick or made with solid concrete building brick in
which interior joints of masonry are filled by pouring
grout around reinforcing therein as the work pro-
gresses.
At the time of laying, all masonry units shall be free
of dust and dirt.
2104A,5, 1,1,2 Low-lift grouted construction.
Requirements for construction shall be as follow s:
1. All units in the two outer wythes shall be laid
with full-shoved head joint and bed mortar
joints. Masonry headers shall not project into
the grout space.
2. The minimum grout space for low -lift grout
masonry shall be 2V2 inches (64 mm). Floaters
shall be used where the grout space exceeds 5
inches (127 mm) in width. The thickness of
grout between masonry units and floaters shall
be a minimum ofl inch (25 mm). Floaters shall
be worked into fresh puddled grout using a
vibrating motion until half of the floater is
embedded in the grout. All reinforcing and wire
ties shall be embedded in the grout. The thick-
ness of the grout between masonry units and
reinforcing shall be a minimum of one bar
diameter.
3. One tier of a grouted reinforced masonry wall
may be carried up 12 inches (305 mm) before
grouting, but the other tier shall be laid up and
grouted in lifts not to exceed one masonry unit
in height. All grout shall be puddled with a
mechanical vibrator or wood stick immediately
after placing so as to completely fill all voids
and to consolidate the grout. All vertical and
horizontal steel shall be held firmly in place by
a frame or suitable devices.
4. If the work is stopped for one hour or more, the
horizontal construction joints shall be formed
by stopping all wythes at the same elevation.
and with the grout V2 inch (13 mm) below the
top.
5. Toothing of masonry walls is prohibited. Rack-
ing is to be held to a minimum.
2104A,5, 1,1,3 High-lift grouted construction.
Where high-lift grouting is used, the method shall be
subject to the approval of the enforcement agency.
Requirements for construction shall be as follows:
L All units in the two wythes shall be laid with full
head and bed mortar joints.
2. The two wythes shall he bonded together with
wall ties. Ties shall not be less than No. 9 wire
in the form of rectangles 4 inches (102 mm)
wide and 2 inches (51 mm) in length less than
the overall wall thickness. Kinks, water drips,
or deformations shall not be permitted in the
ties. One tier of the wall shall be built up not
more than 16 inches (406 mm) ahead of the
other tier. Ties shall be laid not to exceed 24
inches (610 mm) on center horizontally and 16
inches (406 mm) on center vertically for run-
ning bond, and not more than 24 inches (610
mm) on center horizontally and 12 inches (305
mm) on center vertically for stack bond.
3. Cleanouts shall be provided for each pour by
leaving out every other unit in the bottom tier of
the section being poured or by cleanout open-
ings in the foundation. The foundation or other
horizontal construction joints shall be cleaned
of all loose material and mortar droppings
before each pour. The cleanouts shall be sealed
before grouting, after inspection.
4. The grout space in high-lift grouted masonry
shall be a minimum of 3^/2 inches (89 mm). All
reinforcing and wire ties shall be embedded in
the grout. The thickness of the grout between
masonry units and reinforcing shall be a mini-
mum of one bar diameter.
5. Vertical grout barriers or dams shall be built of
solid masonry across the grout space the entire
height of the wall to control the flow of the grout
horizontally. Grout barriers shall not be more
than 30 feet (9144 mm) apart.
6. An approved admixture of a type that reduces
early water loss and produces an expansive
action shall be used in high-lift grout
7. Grouting shall be done in a continuous pour in
lifts not exceeding 4 feet (1219 mm).Grout shall
be consolidated by mechanical vibration only,
and shall be reconsolidated after excess moisture
has been absorbed, but before plasticity is lost
The grouting of any section of a wall between
control barriers shall be completed in one day,
with no interruptions greater than one hour.
2010 CALIFORNIA BUILDING CODE
303
MASONRY
2104A,5J,2 Reinforced hollow-unit masonry,
2104A.5J.2.1 General Reinforced hollow-unit
masonry is that type of construction made with hol-
low-masonry units in which cells are continuously
filled with grout, and in which reinforcement is
embedded. All cells shall be solidly filled with grout in
reinforced hollow-unit masonry, except as provided in
Section 2II4AJ. Construction shall be one of the two
following methods: The low-lift method where the
maximum height of construction laid before grouting
is 4 feet (1220 mm), or the high- lift method where the
full height of construction between horizontal cold
joints is grouted in one operation. General require-
ments for construction shall be as follows:
L All reinforced hollow -unit masonry shall be
built to preserve the unobstructed vertical con-
tinuity of the cells to be filled. All head joints
shall be solidly filled with mortar for a distance
in from the face of the wall or unit not less than
the thickness of the longitudinal face shells.
2. Mortar shall be as specified in Section 2 103 A.
3. Walls and cross webs forming such cells to be
filled shall be full bedded in mortar to prevent
leakage of grout.
4. Bond shall be provided by lapping units in suc-
cessive vertical courses. Where stack bond is
used in reinforced hollow-unit masonry, the
open-end type of unit shall be used with vertical
reinforcement spaced a maximum of 16 inches
(406 mm) on center.
5. Vertical cells to be fdled shall have vertical
alignment sufficient to maintain a clear unob-
structed, continuous vertical cell measuring
not less than 2 inches by 3 inches (51 mm by 76
mm), except the minimum cell dimension for
high-lift grout shall be 3 inches (76 mm).
6. At the time of laying, all masonry units shall be
free of dust and dirt.
7. Grout shall be a workable mix suitable for plac-
ing without segregation and shall be thor-
oughly mixed. Grout shall be placed by
pumping or an approved alternate method and
shall be placed before initial set or hardening
occurs. Grout shall be consolidated by
mechanical vibration during placing and
reconsolidated after excess moisture has been
absorbed, but before workability is lost. The
grouting of any section of a wall shall be com-
pleted in one day, with no interruptions greater
than one hour.
8. All reinforcing and wire ties shall be embedded
in the grout. The space between masonry unit
surfaces and reinforcing shall be a minimum of
one bar diameter.
9. Horizontal reinforcement shall be placed in
bond beam units with a minimum grout cover of
1 inch (25 mm) above steel for each grout pour.
The depth of the bond beam channel below the
top of the unit shall be a minimum ofV/2 inches
(38 mm) and the width shall be 3 inches (76
mm) minimum.
2104A,5. 1.2,2 Low-lift grouted construction. Units
shall be laid a maximum of 4 feet (1220 mm) before
grouting, and all over-hanging mortar and mortar
droppings shall be removed. Grouting shall follow
each 4 feet (1220 mm) of construction laid and shall
be consolidated so as to completely fill all voids and
embed all reinforcing steel. When grouting is stopped
for 1 hour or longer, horizontal construction joints
shall be formed by stopping the pour of grout not less
than V2 inch (13 mm) or more than 2 inches (51 mm)
below the top of the uppermost unit grouted. Horizon-
tal steel shall be fully embedded in grout in an unin-
terrupted pour
2104A.5. 1,2.3 High-lift grouted construction.
Where high-lift grouting is used, the method shall be
approved by the enforcement agency. Cleanout open-
ings shall be provided in every cell at the bottom of
each pour of grout. Alternatively, if the course at the
bottom of the pour is constructed entirely of inverted
open-end bond beam units, cleanout openings need
only be provided in every reinforced cell at the bottom
of each pour of grout. The foundation or other hori-
zontal construction joints shall be cleaned of all loose
material and mortar droppings before each pour The
cleanout s shall be sealed before grouting. An
approved admixture that reduces early water loss and
produces an expansive action shall be used in the
grout.
Vertical barriers of masonry may be built across
the grout space. The grouting of any section of wall
between barriers shall be completed in one day with
no interruption longer than one hour
2104A,5,2 Construction requirements. Reinforcement and
embedded items shall be placed and securely anchored
against moving prior to grouting. Bolts shall be accurately
set with templates or by approved equivalent means and
held in place to prevent dislocation during grouting.
Segregation of the grout materials and damage to the
masonry shall be avoided during the grouting process.
Grout shall be consolidated by mechanical vibration dur-
ing placement before loss of plasticity in a manner to fill the
grout space. Grout pours greater than 12 inches (300 mm)
in height shall be reconsolidated by mechanical vibration to
minimize voids due to water loss. Grout not mechanically
vibrated shall be puddled.
2I04A.6 Aluminum equipment. Grout shall not be handled
nor pumped utilizing aluminum equipment unless it can be
demonstrated with the materials and equipment to be used that
there will be no deleterious effect on the strength of the grout.
304
2010 CALIFORNIA BUILDING CODE
MASONRY
II
SECTION 21054
QUALITY ASSURANCE
2105A.1 General. A quality assurance program shall be used
to ensure that the constructed masonry is in compliance with
the construction documents.
The quality assurance program shall comply with the
inspection and testing requirements of Chapter \1A.
2105A.2 Acceptance relative to strength requirements.
2105A.2.1 Compliance with/'^. Compressive strength of
masonry shall be considered satisfactory if the compressive
strength of each masonry wythe and grouted collar joint
equals or exceeds the value of / '^ for clay and concrete
masonry and requirements of Section 2105A.2.2 is satisfied.
For partially grouted clay and concrete masonry, the com-
pressive strength of both the grouted and ungrouted
masonry shall equal or exceed the applicable/'^ . The speci-
fied compressive strength, /'^ , assumed in design shall be
1,500 psi (10.34 MPa)for all masonry construction using
materials and details of construction required herein. Test-
ing of the constructed masonry shall be provided in accor-
dance with Section 2105A.4.
Exception: Subject to the approval of the enforcement
agency, higher values off^ may be used in the design of
reinforced grouted masonry and reinforced hollow-unit
masonry. The approval shall be based on prism test
results submitted by the architect or engineer which dem-
onstrate the ability of the proposed construction to meet
prescribed performance criteria for strength and stiff-
ness. The design shall assume that the reinforcement will
be placed in a location that will produce the largest
stresses within the tolerances allowed in Section
2 104 A. 1.1 and shall take into account the mortar joint
depth. In no case shall thef^^ assumed in design exceed
3,000 psi (20.7 MPa).
Where anf'^ greater than 1,500 psi (10.34 MPa) is
approved, the architect or structural engineer shall
establish a method of quality control of the masonry con-
struction acceptable to the enforcement agency which
shall be described in the contract specifications. Compli-
ance with the requirements for the specified compressive
strength of masonry f'^ shall be provided in accordance
with Sections 2105A.2.2.2, 2105A.4 and 2105A.5. Sub-
stantiation for the specified compressive strength prior
to the start of construction may be obtained in accor-
dance with Section 2105A.2.2.3.
2105A.2.2 Determination of compressive strength. The
compressive strength for each wythe shall be determined by
the unit strength method or by the prism test method as spec-
ified herein.
2105A. 2.2.1 Unit strength method.
2105A.2.2.1.1 Clay masonry. The compressive
strength of masonry shall be determined based on the
strength of the units and the type of mortar specified
using Table 2105A.2.2.1.1, provided:
1. Units are sampled and tested to verify compli-
ance with ASTM C 62, ASTM C 216 or ASTM
C652.
2. Thickness of bed joints does not exceed Vg inch
(15.9 mm).
3 . For grouted masonry, the grout meets one of the
following requirements:
3.1. Grout conforms to Article 2.2 of TMS
602/ACI530.1/ASCE6.
3.2. Minimum grout compressive strength
equals or exceeds / '„ but not less than
2,000 psi (13.79 MPa). The compressive
strength of grout shall be determined in
accordance with ASTM C 1019.
TABLE 21 05A2.2.1.1
COMPRESSIVE STRENGTH OF CLAY MASONRY
NET AREA COMPRESSIVE STRENGTH
OF CLAY MASONRY UNITS (psi)
NET AREA COMPRESSIVE
STRENGTH OF MASONRY
(psi)
Type M or S mortar
Type N mortar
1,700
2,100
1,000
3,350
4,150
1,500
4,950
6,200
2,000
6,600
8,250
2,500
8,250
10,300
3,000
9,900
—
3,500
11,500
—
4,000
For SI: 1 pound per square inch = 0.00689 MPa.
2 105A. 2.2.1.2 Concrete masonry. The compressive
strength of masonry shall be determined based on the
strength of the unit and type of mortar specified using
Table 2105A.2.2.1.2, provided:
1. Units are sampled and tested to verify
compUance with ASTM C 55 or ASTM C 90.
2. Thickness of bed joints does not exceed Vg inch
(15.9 mm).
3 . For grouted masonry, the grout meets one of the
following requirements:
3.1. Grout conforms to Article 2.2 of TMS
602/ACI530.1/ASCE6.
3.2. Minimum grout compressive strength
equals or exceeds /'„j but not less than
2,000 psi (13.79 MPa). The compres-
sive strength of grout shall be deter-
mined in accordance with ASTM C
1019.
2010 CALIFORNIA BUILDING CODE
305
MASONRY
TABLE2105A2.2.1.2
COMPRESSIVE STRENGTH OF CONCRETE MASONRY
NET AREA COMPRESSIVE STRENGTH OF
CONCRETE MASONRY UNITS (psi)
NET AREA
COMPRESSIVE
STRENGTH OF
MASONRY (psl)^
Type M or S mortar
Type N mortar
1,250
1,300
1,000
1,900
2,150
1,500
2,800
3,050
2,000
3,750
4,050
2,500
4,800
5,250
3,000
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa.
a. For units less than 4 inches in height, 85 percent of the values listed.
I I 2105A. 2.2.1.3 A AC masonry. Not permitted,
2105A,2.2,1,4 Mortar and grout tests. These tests are
to establish whether the masonry components meet
the specified component strengths. At the beginning of
all masonry work, at least one test sample of the mor-
tar and grout shall be taken on three successive work-
ing days and at least at one-week intervals thereafter
They shall meet the minimum strength requirement
given in Sections 2103A.8 and 2103 A.12 for mortar
and grout, respectively. Additional samples shall be
taken whenever any change in materials or job condi-
tions occur, or whenever in the judgment of the archi-
tect, structural engineer or the enforcement agency
such tests are necessary to determine the quality of the
material When the prism test method of Section
2105A.2.2.2 is used, the tests in this section are not
required.
Test specimens for mortar and grout shall be made
as set forth in ASTM C 1586 and ASTM C 1019
2105A.2.2.2 Prism test method.
2105A. 2.2.2.1 General. The compressive strength of
clay and concrete masonry shall be determined by the
prism test method prior to the start of construction
and during construction:
1 . Where specified in the construction documents,
2. Where masonry does not meet the requirements
for application of the unit strength method in
Section 2105A.2.2.1.
3. Where required by Section 2105A.2.L
2105A. 2.2.2.2 Number of prisms per test. Prior to
the start of construction, a prism test shall consist of
five prisms constructed and tested in accordance with
ASTM C 13 14. A set of three masonry prisms shall be
built during construction in accordance with ASTM C
13 14 for each 5,000 square feet (465 m^) of wall area,
but not less than one set of three prisms for the project.
Each set of prisms shall equal or exceed f'^.
2105A.3 Testing prisms from constructed masonry. When
approved by the building official, acceptance of masonry that
does not meet the requirements of Section 2105A. 2.2.1,
2105A.2.2.2, 2105A.4 or 2105A,2.2,L4 shall be permitted to I
be based on tests of prisms cut from the masonry construction
in accordance with Sections 2105A,3.1, 2105A.3.2 and
2105A.3.3.
2105A.3.1 Prism sampling and removal. A set of three
masonry prisms that are at least 28 days old shall be saw cut
from the masonry for each 5,000 square feet (465 m^) of the
wall area that is in question but not less than one set of three
masonry prisms for the project. The length, width and
height dimensions of the prisms shall comply with the
requirements of ASTM C 1314. Transporting, preparation
and testing of prisms shall be in accordance with ASTM C
1314.
2105A,3.2 Compressive strength calculations. The com-
pressive strength of prisms shall be the value calculated in
accordance ASTM C 1314, except that the net cross-sec-
tional area of the prism shall be based on the net mortar bed-
ded area.
2105A.3.3 Compliance. Compliance with the requirement
for the specified compressive strength of masonry,/'^, shall
be considered satisfied provided the modified compressive
strength equals or exceeds the specified/'^. Additional test-
ing of specimens cut from locations in question shall be per-
mitted.
2 105 A*4 Masonry core testing. Not less than two cores shall be <
taken from each building for each 5,000 square feet (465 m^) of
the greater of the masonry wall area or the floor area or frac-
tion thereof The architect or structural engineer in responsible
charge of the project or his or her representative (inspector)
shall select the areas for sampling. Cores shall be a minimum
of 3 % inches (76 mm) in diameter and shall be taken in such a
manner as to exclude masonry unit webs and reinforcing steel.
The inspector of record or testing agency shall inspect the cor-
ing of the masonry walls.
Visual examination of all cores shall be made and the condi-
tion of the cores reported. One half of the number of cores taken
shall be tested in shear The shear test shall test both joints
between the grout core and the outside wythes or face shells of
the masonry. Shear testing apparatus shall be of a design
approved by the enforcement agency. Core samples shall not be
soaked before testing. The unit shear on the cross section of the
core shall not be less than 2.5 v/'^ psi.
All cores shall be submitted to the laboratory for examina-
tion regardless of whether the core specimens failed during
cutting operation. The laboratory shall report the location
where each core was taken, the findings of their visual exami-
nation of each core, identify which cores were selected for
shear testing and the results of the shear tests.
SECTION 21064
SEISMIC DESIGN
2106A.1 Seismic design requirements for masonry.
Masonry structures and components shall comply with the
requirements in Section 1.17 of TMS 402/ACI 530/ASCE 5
306
2010 CALIFORNIA BUILDING CODE
MASONRY
J
.fi
depending on the structure's seismic design category as deter-
mined in Section 1613A.
2106A.L1 Modifications to IMS 402/ACI 530/ASCE 5.
2106AJJ.1 Modify TMS 402/ACI 530/ASCE 5/Section
1.17 as follows:
i. Minimum reinforcement requirements for
masonry walls. The total area of reinforcement in
reinforced masonry walls shall not be less than
0.003 times the sectional area of the wall. Neither
the horizontal nor the vertical reinforcement shall
be less than one third of the total. Horizontal and
vertical rebars shall be spaced at not more than 24
inches (610 mm) center to center. The minimum
reinforcing shall be No. 4, except that No. 3 bars
may be used for ties and stirrups. Vertical wall
steel shall have dowels of equal size and equal
matched spacing in all footings. Reinforcement
shall be continuous around wall corners and
through intersections. Only reinforcement which
is continuous in the wall shall be considered in
computing the minimum area of reinforcement.
Reinforcement with splices conforming to TMS
402/ACI 530/ASCE 5 as modified by Section
2 107 A shall be considered as continuous rein-
forcement.
Horizontal reinforcement shall be provided in
the top of footings, at the top of wall openings, at
roof and floor levels, and at the top of parapet
walls. For walls 12 inches (nominal) (305 mm) or
more in thickness^ reinforcing shall be equally
divided into two layers, except where designed as
retaining walls. Where reinforcement is added
above the minimum requirements, such additional
reinforcement need not be so divided.
In bearing walls of every type of reinforced
masonry, there shall not be less than one No. 5 bar
or two No. 4 bars on all sides of and adjacent to,
every opening which exceeds 16 inches (406 mm)
in either direction, and such bars shall extend not
less than 48 diameters, but in no case less than 24
inches (610 mm) beyond the corners of the open-
ing. The bars required by this paragraph shall be
in addition to the minimum reinforcement else-
where required.
When the reinforcement in bearing walls is
designed, placed and anchored in position as for
columns, the allowable stresses shall be as for col-
umns.
Joint reinforcement shall not be used as princi-
pal reinforcement in masonry designed by the
strength design method.
2. Minimum reinforcement for masonry columns.
The spacing of column ties shall be as follows: not
greater than 8 bar diameters, 24 tie diameters, or
one half the least dimension of the column for the
full column height. Ties shall be at least % inch (10
mm) diameter and shall be embedded in grout. Top
tie shall be within 2 inches (51 mm) of the top of the
column or of the bottom of the horizontal bar in the
supported beam.
Lateral support. Lateral support of masonry may
be provided by cross walls, columns, pilasters,
counterforts or buttresses where spanning hori-
zontally or by floors, beams, girts or roofs where
spanning vertically. Where walls are supported
laterally by vertical elements, the stiffness of each
vertical element shall exceed that of the tributary
area of the wall.
The clear distance between lateral supports of a
beam shall not exceed 32 times the least width of
the compression area.
SECTION 21 07 A
ALLOWABLE STRESS DESIGN
2107A.1 GeneraL The design of masonry structures using
allowable stress design shall comply with Section 2106A and
the requirements of Chapters 1 and 2 of TMS 402/ACI
530/ASCE 5 except as modified by Sections 2107A.2 through
2107A.9.
2107A.2 TMS 402/ACI 530/ASCE 5, Section 2.1.2, load
combinations. Delete Section 2. 1 .2. 1 .
2107A.3 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7.1.1, lap
splices. Modify Section 2.1.9.7.1.1 as follows:
2.1.9.7.1.1 The minimum length of lap splices for reinforc-
ing bars in tension or compression, Z^, shall be
I I
/,=o.oo2^j;
I
(Equation 21A-1)
For SI: /^ = 0.29^/,
but not less than 12 inches (305 mm). In no case shall the
length of the lapped splice be less than 40 bar diameters.
where:
J^ = Diameter of reinforcement, inches (mm).
f - Computed stress in reinforcement due to design
loads, psi (MPa).
In regions of moment where the design tensile stresses in
the reinforcement are greater than 80 percent of the allow-
able steel tension stress, F^, the lap length of splices shall be
increased not less than 50 percent of the minimum required
length. Other equivalent means of stress transfer to accom-
phsh the same 50 percent increase shall be permitted. Where
epoxy coated bars are used, lap length shall be increased by
50 percent.
2107A.4 (Chapter 21, Section 2107.4) TMS 402/ACI
530/ASCE 5, Section 2.1.9.7, splices of reinforcement.
2.1.9.7 — Sphces of reinforcement. Lap sphces, welded
splices or mechanical splices are permitted in accordance
with the provisions of this section. All welding shall con-
form to AWS D1.4. Reinforcement larger than No. 9 (M
#29) shall be spliced using mechanical connections in
accordance with Section 2.1.9.7.3.
2010 CALIFORNIA BUILDING CODE
307
MASONRY
fi
I I 2107 A,5 (Chapter 21, Section 2107.5) TMS402/ACI
530/ASCE 5, Section 2.3.6, maximum bar size. Add the fol-
lowing to Chapter 2:
2.3.6 Maximum bar size. The bar diameter shall not exceed
one-eighth of the nominal wall thickness and shall not
exceed one-quarter of the least dimension of the cell, course
or collar joint in which it is placed.
2107A.6 TMS 402/ACI 530/ASCE 5. Modify by adding Sec-
tions 2,1.43.4 and 2.1.4.3.5 as follows:
2.1.4.3.4 Edge Distance and Spacing. Where the anchor
bolt edge distance, If^^, in the direction of load is less than 12
bolt diameters, the value of B^ in Formula (2-7) shall be
reduced by linear interpolation to zero at an Ibe distance of
V/2 inches (38 mm) and confining reinforcement consisting
of not less than No. 3 hairpins, hooks or stirrups for end
bolts and between horizontal reinforcing for other bolts
shall be provided. Where adjacent anchors are spaced
closer than Sd^,, the allowable shear of the adjacent anchors
determined by Formula (2-7) shall be reduced by linear
interpolation to 0. 75 times the allowable shear value at a
center- to-center spacing of four bolt diameters.
2.1.4.3.5 - Anchor bolts size and materials. Anchor bolts
shall be hex headed bolts conforming to ASTM A 307 or
F1554 with the dimensions of the hex head conforming to
ANSl/ASMEB 18.2.1 or plain rod conforming to ASTM A
36 with threaded ends and double hex nuts at the anchored
end. Bent bar anchor bolts shall not be used.
The maximum size anchor shall be ^/2-inch (13 mm) diam-
eter for 6-inch (152 mm) nominal masonry, ^/^-inch (19 mm)
diameter for 8-inch (203 mm) nominal masonry, Vg-inch (22
mm) diameter for 10-inch (254 mm) nominal masonry, and
1-inch (25mm) diameter for 12-inch (304.8 mm) nominal
masonry.
I I 2107A. 7 TMS 402/ACI 530/ASCE 5 Section 2.1.8. Modify by
adding the following:
Structural members framing into or supported by walls or
columns shall be securely anchored. The end support of gird-
ers, beams or other concentrated loads on masonry shall have
at least 3 inches (76 mm) in length upon solid bearing not less
than 4 inches (102 mm) thick or upon metal bearing plate of
adequate design and dimensions to distribute the loads safely
on the wall or pier, or upon a continuous reinforced masonry
member projecting not less than 3 inches (76 mm) from the face
of the wall or other approved methods.
Joists shall have bearing at least 3 inches (76 mm) in length
upon solid masonry at least 2V2 inches (64 mm) thick, or other
provisions shall be made to distribute safely the loads on the
wall or pier
2107A.8 TMS 402/ACI 530/ASCE 5. Modijy by adding Sec-
tion 2.1.10 as follows:
2.L10 - Walls and Piers.
Thickness of Walls. For thickness limitations of walls as
specified in this chapter, nominal thickness shall be used.
Stresses shall be determined on the basis of the net thickness
of the masonry, with consideration for reduction, such as
rakedjoints.
The thickness of masonry walls shall be designed so that
allowable maximum stresses specified in this chapter are
not exceeded. Also, no masonry wall shall exceed the height
or length-to-thickness ratio or the minimum thickness as
specified in this chapter and as set forth in Table 2107A.8. I l<
Piers. Every pier or wall section which width is less than
three times its thickness shall be designed and constructed
as required for columns if such pier is a structural member.
Every pier or wall section which width is between three and
five times its thickness or less than one half the height of
adjacent openings shall have all horizontal steel in the form
of ties except that in walls 12 inches (305 mm) or less in
thickness such steel may be in the form of hair-pins.
TABLE 21 07 A.8 I I
MINIMUM THICKNESS OF MASONRY WALLS''^
TYPE OF MASONRY
MAXIMUM RATIO
UNSUPPORTED
HEIGHT OR
LENGTH TO
THICKNES^'^
NOMINAL
MINIMUM
THICKNESS
(inches)
BEARING OR SHEAR WALLS:
L Stone masonry
2. Reinforced grouted masonry
3. Reinforced hollow-unit masonry
14
25
25
16
6
6
NONBEARING WALLS:
4. Exterior reinforced walls
5. Interior partitions reinforced
30
36
6
4
1. For walls of varying thickness, use the least thickness when determining the
height or length to thickness ratio.
2. In determining the height or length-to-thickness ratio of a cantilevered wall,
the dimension to be used shall be twice the dimension of the end of the wall
from the lateral support.
3. Cantilevered walls not part of a building and not carrying applied vertical
loads need not meet these minimum requirements but their design must com-
ply with stress and overturning requirements.
2107A.9 [OSHPD 1 & 4] Modify TMS402/ACI 530/ASCE 5,
Section 2.3.3.4 by the following: All reinforced masonry com-
ponents that are subjected to in-plane forces shall have a maxi-
mum reinforcement ratio, p^^^x* not greater than that computed
by Equation 2-22.
SECTION 2108^
STRENGTH DESIGN OF MASONRY
2108A,1 General. The design of masonry structures using
strength design shall comply with Section 2106A and the
requirements of Chapters 1 and 3 of TMS 402/ACI 530/ASCE
5, except as modified by Sections 2108A.2 through 2108A.3.
2108A.2 TMS 402/ACI 530/ASCE 5, Section 3.3.3.3 develop-
ment. Modify the second paragraph of Section 3.3.3.3 as follows:
The required development length of reinforcement shall
be determined by Equation (3-16), but shall not be less than
12 inches (305 mm) and need not be greater than 72 df^.
2108A.3 TMS 402/ACI 530/ASCE 5, Section 3.3.3.4, splices.
Modify items (b) and (c) of Section 3.3.3.4 as follows:
3.3.3.4 (b). A welded splice shall have the bars butted and
welded to develop at least 125 percent of the yield strength,
M
308
2010 CALIFORNIA BUILDING CODE
MASONRY
I I
>ll
•r
fy , of the bar in tension or compression, as required. Welded
splices shall be of ASTM A 706 steel reinforcement.
Welded splices shall not be permitted in plastic hinge zones
of intermediate or special reinforced walls or special
moment frames of masonry.
3.3.3.4 (c). Mechanical splices shall be classified as Type 1
or 2 according to Section 21.2.6.1 of ACI 318. Type 1
mechanical splices shall not be used within a plastic hinge
zone or within a beam-column joint of intermediate or spe-
cial reinforced masonry shear walls or special moment
frames. Type 2 mechanical splices are permitted in any loca-
tion within a member.
SECTION 21 Og>t
EMPIRICAL DESIGN OF MASONRY
Not permitted by OSHPD and DSA-SS.
SECTION 21104
GLASS UNIT MASONRY
2110A.1 GeneraL Masonry of glass blocks shall be permitted
in nonload-bearing exterior or interior walls and shall con-
form to the requirements of Section 21 15 A. Stresses in glass
block shall not be utilized. Glass block may be solid or hollow
and may contain inserts.
SECTION 21114
MASONRY FIREPLACES
2111A.1 Definition. A masonry fireplace is a fireplace con-
structed of concrete or masonry. Masonry fireplaces shall be
constructed in accordance with this section.
2111A.2 Footings and foundations. Footings for masonry
fireplaces and their chimneys shall be constructed of concrete
or solid masonry at least 12 inches (305 mm) thick and shall
extend at least 6 inches (153 mm) beyond the face of the fire-
place or foundation wall on all sides. Footings shall be founded
on natural undisturbed earth or engineered fill below frost
depth. In areas not subjected to freezing, footings shall be at
least 12 inches (305 mm) below finished grade.
211L4.2.1 Ash dump cleanout. Cleanout openings,
located within foundation walls below fireboxes, when pro-
vided, shall be equipped with ferrous metal or masonry
doors and frames constructed to remain tightly closed,
except when in use. Cleanouts shall be accessible and
located so that ash removal will not create a hazard to com-
bustible materials.
211M.3 Seismic reinforcing. Masonry or concrete fireplaces
shall be constructed, anchored, supported and reinforced as
required in this chapter. In Seismic Design Category C or D,
masonry and concrete fireplaces shall be reinforced and
anchored as detailed in Sections 21 IIA.3.1, 21 IIA.3.2, 21 11A.4
and 2111A.4.1 for chinmeys serving fireplaces. In Seismic
Design Category A or B, reinforcement and seismic anchorage
is not required. In Seismic Design Category E or F, masonry and
concrete chimneys shall be reinforced in accordance with the
requirements of Sections 2101A through 2108A.
2111A.3.1 Vertical reinforcing. For fireplaces with chim-
neys up to 40 inches (1016 mm) wide, four No. 4 continuous
vertical bars, anchored in the foundation, shall be placed in
the concrete between wythes of solid masonry or within the
cells of hollow unit masonry and grouted in accordance with
Section 2103A.12. For fireplaces with chimneys greater
than 40 inches (1016 mm) wide, two additional No. 4 verti-
cal bars shall be provided for each additional 40 inches
(1016 mm) in width or fraction thereof.
2111A.3.2 Horizontal reinforcing. Vertical reinforcement
shall be placed enclosed within V4-inch (6.4 mm) ties or
other reinforcing of equivalent net cross -sectional area,
spaced not to exceed 18 inches (457 mm) on center in con-
crete; or placed in the bed joints of unit masonry at a mini-
mum of every 18 inches (457 mm) of vertical height. Two
such ties shall be provided at each bend in the vertical bars .
211L4.4 Seismic ancliorage. Masonry and concrete chimneys
in Seismic Design Category C or D shall be anchored at each
floor, ceiling or roof line more than 6 feet (1829 nmi) above
grade, except where constructed completely within the exterior
walls. Anchorage shall conform to the following requirements.
2111A.4.1 Anchorage. Two Vj^-inch by 1-inch (4.8 mm by
25.4 mm) straps shall be embedded a minimum of 12 inches
(305 nmi) into the chinmey. Straps shall be hooked around
the outer bars and extend 6 inches (152 mm) beyond the
bend. Each strap shall be fastened to a minimum of four
floor joists with two Vs-inch (12.7 mm) bolts.
2111A.5 Firebox walls. Masonry fireboxes shall be con-
structed of solid masonry units, hollow masonry units grouted
solid, stone or concrete. When a lining of firebrick at least 2
inches (51 mm) in thickness or other approved lining is pro-
vided, the minimum thickness of back and sidewalls shall each
be 8 inches (203 mm) of solid masonry, including the lining.
The width of joints between firebricks shall not be greater than
V4 inch (6.4 mm). When no lining is provided, the total mini-
mum thickness of back and sidewalls shall be 10 inches (254
mm) of solid masonry. Firebrick shall conform to ASTM C 27
or ASTM C 1261 and shall be laid with medium-duty refrac-
tory mortar conforming to ASTM C 199.
2111A.5.1 Steel fireplace units. Steel fireplace units are per-
mitted to be installed with solid masonry to form a masonry
fireplace provided they are installed according to either the
requirements of their listing or the requirements of this sec-
tion. Steel fireplace units incorporating a steel firebox lining
shall be constructed with steel not less than V4 inch (6.4 mm)
in thickness, and an air-circulating chamber which is ducted
to the interior of the building. The firebox Hning shall be
encased with solid masonry to provide a total thickness at the
back and sides of not less than 8 inches (203 nam), of which
not less than 4 inches (102 mm) shall be of solid masonry or
concrete. Circulating air ducts employed with steel fireplace
units shall be constructed of metal or masonry.
2111A.6 Firebox dimensions. The firebox of a concrete or
masonry fireplace shall have a minimum depth of 20 inches
(508 mm). The throat shall not be less than 8 inches (203 mm)
above the fireplace opening. The throat opening shall not be
less than 4 inches (102 mm) in depth. The cross-sectional area
of the passageway above the firebox, including the throat,
2010 CALIFORNIA BUILDING CODE
309
MASONRY
damper and smoke chamber, shall not be less than the
cross-sectional area of the flue.
Exception: Rumford fireplaces shall be permitted provided
that the depth of the fireplace is at least 12 inches (305 mm) and
at least one-third of the width of the fireplace opening, and the
throat is at least 12 inches (305 mm) above the lintel, and at
least V20 the cross-sectional area of the fireplace opening.
2111A.7 Lintel and throat. Masonry over a fireplace opening
shall be supported by a lintel of noncombustible material. The
minimum required bearing length on each end of the fireplace
opening shall be 4 inches (102 mm). The fireplace throat or
damper shall be located a minimum of 8 inches (203 mm)
above the top of the fireplace opening.
211 LA. 7.1 Damper. Masonry fireplaces shall be equipped
with a ferrous metal damper located at least 8 inches (203
mm) above the top of the fireplace opening. Dampers shall
be installed in the fireplace or at the top of the flue venting
the fireplace, and shall be operable from the room contain-
ing the fireplace. Damper controls shall be permitted to be
located in the fireplace.
211M.8 Smoke chamber walls. Smoke chamber walls shall
be constructed of solid masonry units, hollow masonry units
grouted solid, stone or concrete. The total minimum thickness
of front, back and sidewalls shall be 8 inches (203 mm) of solid
masonry. The inside surface shall be parged smooth with
refractory mortar conforming to ASTM C 199. When a lining
of firebrick at least 2 inches (5 1 nrmi) thick, or a lining of vitri-
fied clay at least Vg inch (15.9 mm) thick, is provided, the total
minimum thickness of front, back and sidewalls shall be 6
inches (152 mm) of solid masonry, including the lining. Fire-
brick shall conform to ASTM C 1261 and shall be laid with
refractory mortar conforming to ASTM C 199. Vitrified clay
linings shall conform to ASTM C 315.
211M.8.1 Smoke chamber dimensions. The inside height
of the smoke chamber fi-om the fireplace throat to the begin-
ning of the flue shall not be greater than the inside width of
the fireplace opening. The inside surface of the smoke cham-
ber shall not be inclined more than 45 degrees (0.76 rad) from
vertical when prefabricated smoke chamber linings are used
or when the smoke chamber walls are rolled or sloped rather
than corbeled. When the inside surface of the smoke chamber
is formed by corbeled masonry, the walls shall not be
corbeled more than 30 degrees (0.52 rad) from vertical.
2111A.9 Hearth and hearth extension. Masonry fireplace
hearths and hearth extensions shall be constructed of concrete
or masonry, supported by noncombustible materials, and rein-
forced to carry their own weight and all imposed loads. No
combustible material shall remain against the underside of
hearths or hearth extensions after construction.
211M.9.1 Hearth thickness. The minimum thickness of
fireplace hearths shall be 4 inches (102 mm).
211L4.9.2 Hearth extension thickness. The minimum
thickness of hearth extensions shall be 2 inches (51 mm).
Exception: When the bottom of the firebox opening is
raised at least 8 inches (203 mm) above the top of the
hearth extension, a hearth extension of not less than
Vg-inch-thick (9.5 mm) brick, concrete, stone, tile or
other approved noncombustible material is permitted.
211M.10 Hearth extension dimensions. Hearth extensions
shall extend at least 16 inches (406 mm) in front of, and at least
8 inches (203 mm) beyond, each side of the fireplace opening.
Where the fireplace opening is 6 square feet (0.557 m^) or
larger, the hearth extension shall extend at least 20 inches (508
mm) in front of, and at least 12 inches (305 mm) beyond, each
side of the fireplace opening.
211L4.11 Fireplace clearance. Any portion of a masonry fire-
place located in the interior of a building or within the exterior
wall of a building shall have a clearance to combustibles of not
less than 2 inches (51 nmi) from the front faces and sides of
masonry fireplaces and not less than 4 inches (102 mm) from the
back faces of masonry fireplaces. The airspace shall not be filled,
except to provide fireblocking in accordance with Section
2111A.12.
Exceptions:
1 . Masonry fireplaces listed and labeled for use in contact
with combustibles in accordance with UL 127 and
installed in accordance with the manufacturer's instal-
lation instructions are permitted to have combustible
material in contact with their exterior surfaces.
2. When masonry fireplaces are constructed as part of
masonry or concrete walls, combustible materials
shall not be in contact with the masonry or concrete
walls less than 12 inches (306 mm) from the inside
surface of the nearest firebox lining.
3. Exposed combustible trim and the edges of sheathing
materials, such as wood siding, flooring and dry wall,
are permitted to abut the masonry fireplace sidewalls
and hearth extension, in accordance with Figure
21 1 lA. 1 1, provided such combustible trim or sheath-
ing is a minimum of 12 inches (306 mm) from the
inside surface of the nearest firebox lining.
4. Exposed combustible mantels or trim is permitted to be
placed directly on the masonry fireplace front sur-
rounding the fireplace opening, provided such com-
bustible materials shall not be placed within 6 inches
(153 mm) of a fireplace opening. Combustible material
directly above and within 12 inches (305 mm) of the
fireplace opening shall not project more than Vg inch
(3.2 mm) for each 1-inch (25 mm) distance from such
opening. Combustible materials located along the
sides of the fireplace opening that project more than
1 V2 inches (38 mm) from the face of the fireplace shall
have an additional clearance equal to the projection.
310
2010 CALIFORNIA BUILDING CODE
MASONRY
S^E ABUTTINO MASONRY
IZyiRFFO^ FIREBOX
^TOcamusiimM fraiviing
FRAME WAli
For SI: 1 inch = 25.4 mm
FIGURE 2111A11
ILLUSTRATION OF EXCEPTION TO
FIREPLACE CLEARANCE PROVISION
2111A.12 Fireplace fireblocking. All spaces between fire-
places and floors and ceilings through which fireplaces pass
shall be fireblocked with noncombustible material securely
fastened in place. The fireblocking of spaces between wood
joists, beams or headers shall be to a depth of 1 inch (25 mm)
and shall only be placed on strips of metal or metal lath laid
across the spaces between combustible material and the chim-
ney.
211L4.13 Exterior air. Factory-built or masonry fireplaces
covered in this section shall be equipped with an exterior air
supply to ensure proper fuel combustion unless the room is
mechanically ventilated and controlled so that the indoor pres-
sure is neutral or positive.
2111A.13.1 Factory -built fireplaces. Exterior combustion
air ducts for factory-built fireplaces shall be listed compo-
nents of the fireplace, and installed according to the fire-
place manufacturer's instructions.
211M.13.2 Masonry fireplaces. Listed combustion air
ducts for masonry fireplaces shall be installed according
to the terms of their listing and manufacturer's instruc-
tions.
211M.13.3 Exterior air intake. The exterior air intake
shall be capable of providing all combustion air from the
exterior of the dwelling. The exterior air intake shall not be
located within a garage, attic, basement or crawl space of
the dwelling nor shall the air intake be located at an elevation
higher than the firebox. The exterior air intake shall be cov-
ered with a corrosion-resistant screen of V4-inch (6.4 mm)
mesh.
211L4. 13.4 Clearance. Unhsted combustion air ducts shall
be installed with a minimum 1-inch (25 mm) clearance to
combustibles for all parts of the duct within 5 feet (1524
mm) of the duct outlet.
211L4.13.5 Passageway. The combustion air passageway
shall be a minimum of 6 square inches (3870 mm^) and not
more than 55 square inches (0.035 m^), except that combus-
tion air systems for listed fireplaces or for fireplaces tested
for emissions shall be constructed according to the fireplace
manufacturer's instructions.
2111A.13.6 Outlet. The exterior air oudet is permitted to be
located in the back or sides of the firebox chamber or within
24 inches (610 nun) of the firebox opening on or near the
floor. The outlet shall be closable and designed to prevent
burning material from dropping into concealed combustible
spaces.
SECTION 211 24
MASONRY HEATERS
2112A.1 Definition. A masonry heater is a heating appliance
constructed of concrete or solid masonry, hereinafter referred
to as "masonry," which is designed to absorb and store heat
from a solid fuel fire built in the firebox by routing the exhaust
gases through internal heat exchange channels in which the
flow path downstream of the firebox may include flow in a hor-
izontal or downward direction before entering the chimney and
which delivers heat by radiation from the masonry surface of
the heater.
2112A.2 Installation. Masonry heaters shall be installed in
accordance with this section and comply with one of the follow-
ing:
1. Masonry heaters shall comply with the requirements of
ASTM E 1602; or
2. Masonry heaters shall be listed and labeled in accor-
dance with UL 1482 and installed in accordance with the
manufacturer's installation instructions.
2112A.3 Footings and foundation. The firebox floor of a
masonry heater shall be a minimum thickness of 4 inches (102
mm) of noncombustible material and be supported on a
noncombustible footing and foundation in accordance with
Section 2113.2.
2112A.4 Seismic reinforcing. In Seismic Design Category D,
E and F, masonry heaters shall be anchored to the masonry
foundation in accordance with Section 21 13A.3. Seismic rein-
forcing shall not be required within the body of a masonry
heater with a height that is equal to or less than 3.5 times its
body width and where the masonry chimney serving the heater
is not supported by the body of the heater. Where the masonry
chimney shares a common wall with the facing of the masonry
heater, the chimney portion of the structure shall be reinforced
in accordance with Section 2113A.
2112A.5 Masonry heater clearance. Combustible materials
shall not be placed within 36 inches (765 mm) of the outside
surface of a masonry heater in accordance with NFPA 211,
Section 8-7 (clearances for solid fuel-burning apphances), and
the required space between the heater and combustible material
shall be fully vented to permit the free flow of air around all
heater surfaces.
Exceptions:
1 . When the masonry heater wall thickness is at least 8
inches (203 mm) thick of solid masonry and the wall
thickness of the heat exchange channels is at least 5
inches (127 nun) thick of solid masonry, combustible
materials shall not be placed within 4 inches (102
mm) of the outside surface of a masonry heater. A
clearance of at least 8 inches (203 mm) shall be pro-
2010 CALIFORNIA BUILDING CODE
311
MASONRY
vided between the gas-tight capping slab of the heater
and a combustible ceiling.
2. Masonry heaters listed and labeled in accordance
with UL 1482 and installed in accordance with the
manufacturer's instructions.
SECTION 21134
MASONRY CHIMNEYS
2113A.1 Definition. A masonry chimney is a chimney con-
structed of concrete or masonry, hereinafter referred to as
'^masonry." Masonry chimneys shall be constructed, anchored,
supported and reinforced as required in this chapter.
2113A.2 Footings and foundations. Footings for masonry
chimneys shall be constructed of concrete or solid masonry at
least 12 inches (305 nun) thick and shall extend at least 6 inches
(152 mm) beyond the face of the foundation or support wall on
all sides. Footings shall be founded on natural undisturbed
earth or engineered fill below frost depth. In areas not subjected
to freezing, footings shall be at least 12 inches (305 mm) below
finished grade.
2113A.3 Seismic reinforcing. Masonry or concrete chimneys
shall be constructed, anchored, supported and reinforced as
required in this chapter. In Seismic Design Category C or D,
masonry and concrete chimneys shall be reinforced and
anchored as detailed in Sections 2113A.3.1, 2113A.3.2 and
2113A.4. In Seismic Design Category A or B, reinforcement
and seismic anchorage is not required. In Seismic Design Cate-
gory E or F, masonry and concrete chimneys shall be reinforced
in accordance with the requirements of Sections 2101A
through 2108A.
2113A.3.1 Vertical reinforcing. For chimneys up to 40
inches (1016 mm) wide, four No. 4 continuous vertical bars
anchored in the foundation shall be placed in the concrete
between wythes of solid masonry or within the cells of hol-
low unit masonry and grouted in accordance with Section
2103A. 12. Grout shall be prevented from bonding with the
flue liner so that the flue liner is free to move with thermal
expansion. For chimneys greater than 40 inches (1016 mm)
wide, two additional No. 4 vertical bars shall be provided for
each additional 40 inches (1016 mm) in width or fraction
thereof.
2113A.3.2 Horizontal reinforcing. Vertical reinforcement
shall be placed enclosed within V4-inch (6.4 mm) ties, or
other reinforcing of equivalent net cross-sectional area,
spaced not to exceed 18 inches (457 mm) o.c. in concrete, or
placed in the bed joints of unit masonry, at a minimum of
every 18 inches (457 nun) of vertical height. Two such ties
shall be provided at each bend in the vertical bars.
2113A.4 Seismic anchorage. Masonry and concrete chimneys
and foundations in Seismic Design Category C or D shall be
anchored at each floor, ceiHng or roof line more than 6 feet
(1829 mm) above grade, except where constructed completely
within the exterior walls. Anchorage shall conform to the fol-
lowing requirements.
2113A.4.1 Anchorage. Two Vi^-inch by 1-inch (4.8 mm by
25 mm) straps shall be embedded a minimum of 12 inches
(305 mm) into the chinmey. Straps shall be hooked around
the outer bars and extend 6 inches (152 mm) beyond the
bend. Each strap shall be fastened to a minimum of four
floor joists with two Vs-inch (12,7 mm) bolts.
2113A.5 Corbeling. Masonry chimneys shall not be corbeled
more than half of the chimney's wall thickness from a wall or
foundation, nor shall a chimney be corbeled from a wall or
foundation that is less than 12 inches (305 mm) in thickness
unless it projects equally on each side of the wall, except that on
the second story of a two-story dwelling, corbeling of chim-
neys on the exterior of the enclosing walls is permitted to equal
the wall thickness. The projection of a single course shall not
exceed one-half the unit height or one-third of the unit bed
depth, whichever is less.
2113A.6 Changes in dimension. The chimney wall or chim-
ney flue lining shall not change in size or shape within 6 inches
(152 mm) above or below where the chimney passes through
floor components, ceiling components or roof components.
2113A.7 Offsets. Where a masonry chimney is constructed
with a fireclay flue liner surrounded by one wythe of masonry,
the maximum offset shall be such that the centerline of the flue
above the offset does not extend beyond the center of the chim-
ney wall below the offset. Where the chimney offset is sup-
ported by masonry below the offset in an approved manner, the
maximum offset limitations shall not apply. Each individual
corbeled masonry course of the offset shall not exceed the pro-
jection limitations specified in Section 2113A.5.
2113A.8 Additional load. Chimneys shall not support loads
other than their own weight unless they are designed and con-
structed to support the additional load. Masonry chimneys are
permitted to be constructed as part of the masonry walls or con-
crete walls of the building.
2113A.9 Termination. Chimneys shall extend at least 2 feet
(610 mm) higher than any portion of the building within 10 feet
(3048 mm), but shall not be less than 3 feet (914 mm) above the
highest point where the chinmey passes through the roof.
2113A.9.1 Sparli arrestors. [SFM] All chimneys attached
to any appliance or fireplace that burns solid fiiel shall be
equipped with an approved spark arrester. The spark
arrestor shall meet all of the following requirements:
1 . The net free area of the spark arrester shall not be less
than four times the net free area of the outlet of the
chimney.
2. The spark arrester screen shall have heat and corro-
sion resistance equivalent to 12- gage wire, 19- gage
galvanized wire or 24-gage stainless steel.
3. Openings shall not permit the passage of spheres hav-
ing a diameter larger than V2 inch (12.7 mm) and
shall not block the passage of spheres having a diam-
eter of less than % inch (9.5 mm).
4. The spark arrestor shall be accessible for cleaning and
the screen or chimney cap shall be removable to allow
for cleaning of the chimney flue.
2113A.10 Wall thicliness. Masonry chimney walls shall be
constructed of concrete, solid masonry units or hollow
<•
312
2010 CALIFORNIA BUILDING CODE
MASONRY
masonry units grouted solid with not less than 4 inches (102
mm) nominal thickness.
2113A. 10.1 Masonry veneer chimneys. Where masonry is
used as veneer for a framed chimney, through flashing and
weep holes shall be provided as required by Chapter 14.
2113A.11 Flue lining (material). Masonry chimneys shall be
lined. The lining material shall be appropriate for the type of
appliance connected, according to the terms of the appliance
listing and the manufacturer's instructions.
2113A.11.1 Residential-type appliances (general). Flue
lining systems shall comply with one of the following:
1 . Clay flue lining complying with the requirements of
ASTMC315.
2. Listed chimney lining systems complying with UL
1777.
3. Factory -built chimneys or chimney units listed for
installation within masonry chimneys.
4. Other approved materials that will resist corrosion,
erosion, softening or cracking from flue gases and
condensate at temperatures up to 1,800°F (982°C).
2113A. 11.1.1 Flue linings for specific appliances. Flue
hnings other than those covered in Section 2113A.11.1
intended for use with specific appHances shall comply
with Sections 2113A.11.1.2 through 2113A.1L1.4 and
Sections 2113A.11.2 and 2113A.11.3.
2113A. 11.1.2 Gas appliances. Flue lining systems for
gas appliances shall be in accordance with the Interna-
tional Fuel Gas Code,
2113A. 11.1.3 Pellet fuel-burning appliances. Flue lin-
ing and vent systems for use in masonry chimneys with
pellet fuel-burning appliances shall be limited to flue lin-
ing systems complying with Section 2113A.1L1 and
pellet vents listed for installation within masonry chim-
neys (see Section 21 13A. 11.1,5 for marking).
2113A. 11.1.4 Oil-fired appliances approved for use
with L-vent. Flue lining and vent systems for use in
masonry chimneys with oil-fired appliances approved
for use with Type L vent shall be limited to flue lining
systems complying with Section 2113A.1L1 and listed
chimney liners complying with UL 641 (see Section
2113A.11.1.5 for marking).
2113A. 11.1.5 Notice of usage. When a flue is relined
with a material not complying with Section 2 1 1 3A. 1 1 . 1 ,
the chimney shall be plainly and permanently identified
by a label attached to a wall, ceiling or other conspicuous
location adjacent to where the connector enters the chim-
ney. The label shall include the following message or
equivalent language: "This chimney is for use only with
(type or category of appliance) that bums (type of fuel).
Do not connect other types of appliances."
2113A.11.2 Concrete and masonry chimneys for
medium-heat appliances.
2113A. 11.2.1 General. Concrete and masonry chim-
neys for medium-heat appliances shall comply with Sec-
tions 21 13A. 1 through 2113A5.
21 13A. 11.2.2 Construction. Chimneys for medium-
heat apphances shall be constructed of sohd masonry
units or of concrete with walls a minimum of 8 inches
(203 mm) thick, or with stone masonry a minimum of 12
inches (305 mm) thick.
2113A. 11.2.3 Lining. Concrete and masonry chimneys
shall be lined with an approved xnQdixxm-dMiy refractory
brick a minimum of 472 inches (114 mm) thick laid on
the 4V2-inch bed (114 mm) in an approved medium-
duty refractory mortar. The lining shall start 2 feet (610
mm) or more below the lowest chimney connector
entrance. Chimneys terminating 25 feet (7620 mm) or
less above a chimney connector entrance shall be lined
to the top.
2113A. 11,2.4 Multiple passageway. Concrete and
masonry chimneys containing more than one passage-
way shall have the liners separated by a minimum
4-inch-thick (102 mm) concrete or soUd masonry wall.
21 13A. 11.2.5 Termination height. Concrete and
masonry chimneys for medium-heat appliances shall
extend a minimum of 10 feet (3048 mm) higher than any
portion of any building within 25 feet (7620 mm).
2113A. 11.2.6 Clearance. A minimum clearance of 4
inches (102 mm) shall be provided between the exterior
surfaces of a concrete or masonry chimney for
medium-heat appliances and combustible material.
2113A.11.3 Concrete and masonry chimneys for high-
heat appliances.
21 13A. 11.3.1 General. Concrete and masonry chim-
neys for high-heat appliances shall comply with Sections
21 13A.1 through 21 13A.5.
2113A. 11.3.2 Construction. Chimneys for high-heat
appliances shall be constructed with double walls of
solid masonry units or of concrete, each wall to be a mini-
mum of 8 inches (203 mm) thick with a minimum air-
space of 2 inches (51 mm) between the walls.
2 113A. 11.3.3 Lining. The inside of the interior wall
shall be lined with an approved high-duty refractory
brick, a minimum of 472 inches (114 mm) thick laid on
the 4V2-inch bed (114 mm) in an approved high-duty
refractory mortar. The lining shall start at the base of the
chimney and extend continuously to the top.
2113A. 11.3.4 Termination height. Concrete and
masonry chimneys for high-heat appliances shall extend
a minimum of 20 feet (6096 mm) higher than any portion
of any building within 50 feet (15 240 nmi).
21 13A. 11.3.5 Clearance. Concrete and masonry chim-
neys for high-heat appliances shall have approved clear-
ance from buildings and structures to prevent
overheating combustible materials, permit inspection
and maintenance operations on the chimney and prevent
danger of burns to persons.
2113A.12 Clay flue lining (installation). Clay flue hners shall
be installed in accordance with ASTM C 1283 and extend from
a point not less than 8 inches (203 mm) below the lowest inlet
or, in the case of fireplaces, from the top of the smoke chamber
2010 CALIFORNIA BUILDING CODE
313
MASONRY
to a point above the enclosing walls. The lining shall be carried
up vertically, with a maximum slope no greater than 30 degrees
(0.52 rad) from the vertical.
Clay flue liners shall be laid in medium-duty refractory mor-
tar conforming to ASTM C 199 with tight mortar joints left
smooth on the inside and installed to maintain an air space or
insulation not to exceed the thickness of the flue liner separat-
ing the flue liners from the interior face of the chimney
masonry walls. Flue Hning shall be supported on all sides. Only
enough mortar shall be placed to make the joint and hold the
liners in position.
2113A.13 Additional requirements.
2113A.13,1 Listed materials. Listed materials used as flue
linings shall be installed in accordance with the terms of
their listings and the manufacturer's instructions.
2113A.13.2 Space around lining. The space surrounding a
chimney lining system or vent installed within a masonry
chimney shall not be used to vent any other appliance.
Exception: This shall not prevent the installation of a
separate flue lining in accordance with the manufac-
turer's instructions.
2113A. 14 Multiple flues. When two or more flues are located
in the same chimney, masonry wythes shall be built between
adjacent flue linings. The masonry wythes shall be at least 4
inches (102 mm) thick and bonded into the walls of the chim-
ney.
Exception: When venting only one appliance, two flues are
permitted to adjoin each other in the same chimney with
only the flue lining separation between them. The joints of
the adjacent flue linings shall be staggered at least 4 inches
(102 mm).
2113A.15 Flue area (appliance). Chimney flues shall not be
smaller in area than the area of the connector from the appli-
ance. Chimney flues connected to more than one appliance
shall not be less than the area of the largest connector plus 50
percent of the areas of additional chimney connectors.
Exceptions:
1. Chinmey flues serving oil-fired appliances sized in
accordance with NFPA 31.
2. Chimney flues serving gas-fired appliances sized in
accordance with the International Fuel Gas Code.
2113A.16 Flue area (masonry fireplace). Flue sizing for
chimneys serving fireplaces shall be in accordance with Sec-
tion 21 13A. 16.1 or 211 3A 16.2.
2113A.16.1 Minimum area. Round chimney flues shall
have a minimum net cross-sectional area of at least 7^2 of the
fireplace opening. Square chimney flues shall have a mini-
mum net cross-sectional area of at least V^o of the fireplace
opening. Rectangular chimney flues with an aspect ratio
less than 2 to 1 shall have a minimum net cross-sectional
area of at least Vjo of the fireplace opening. Rectangular
chimney flues with an aspect ratio of 2 to 1 or more shall
have a minimum net cross-sectional area of at least Vg of the
fireplace opening.
2113A.16.2 Determination of minimum area. The mini-
mum net cross-sectional area of the flue shall be determined
in accordance with Figure 21 13A. 16. A flue size providing
at least the equivalent net cross-sectional area shall be used.
Cross-sectional areas of clay flue Unings are as provided in
Tables 21 13A. 16(1) and 21 13A. 16(2) or as provided by the
manufacturer or as measured in the field. The height of the
chimney shall be measured from the firebox floor to the top
of the chinmey flue.
TABLE 211 3 A1 6(1)
NET CROSS-SECTIONAL AREA OF ROUND FLUE SIZES'
FLUE SIZE, INSIDE DIAMETER
(inches)
CROSS-SECTIONAL AREA
(square inches)
6
28
7
38
8
50
10
78
10 V4
90
12
113
15
176
18
254
For SI: 1 inch = 25.4 mm, 1 square inch = 645. 16 mnf .
a. Flue sizes are based on ASTM C 315.
TABLE 21134.16(2)
NET CROSS-SECTIONAL AREA OF SQUARE
AND RECTANGULAR FLUE SIZES
FLUE SIZE, OUTSIDE NOiVIINAL DIMENSIONS
(inches)
CROSS-SECTIONAL AREA
(square inches)
4.5 X 8.5
23
4.5 X 13
34
8x8
42
8.5 X 8.5
49
8x12
67
8.5 x 13
76
12x12
102
8.5 X 18
101
13x13
127
12x16
131
13x18
173
16x16
181
16x20
222
18x18
233
20x20
298
20x24
335
24x24
431
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm?.
2113A. 17 Inlet. Inlets to masonry chimneys shall enter from
the side. Inlets shall have a thimble of fireclay, rigid refrac-
tory material or metal that will prevent the connector from
pulling out of the inlet or from extending beyond the wall of
the liner.
314
2010 CALIFORNIA BUILDING CODE
MASONRY
224
140
70
S3
32
■ .269:
214^
168
124
91
82
58
37
,^
3000
^
•^
——— *>^T\
^
.-^f
^
•^
'^p.rvfs
,^
^
^
'fA.C^
>-s
**^^
^
p
,(*^
^
< Hni^iWkiw '>'>fliri
I-
;ji***^"
^
^
>-^
^'
,v-r^
-"^'^^
^
*?V\V>V\
i
™mM-lrt!S
.^-^
■^■'
;i»^^
.-^-^
ifinn
a
s-
,,r.i<r
x.-^'
.>*
'^'"
-1600
^■
' ---^
\<^
:y»*'*^"''
o
;
^^.-^
... .-1. i^nn
g
i
— 1-— '
-— — "
^.i*'
CO
;:.,;^^
-i- — '
<0
o
.-— -*
"*■
fy
^
.^.---
.-— -
"^ ■
-*— -
^-— ^
^
— ^^
_^
.— -^
— ouu
2:-
" '
— '
--^
.,.,„„ „„, ^00
^
'
.
_. ^
.-. — '
: __,
— 1 -*■
'^rtrt
1
:gi
ill
1-3
14
15
OFC
16
;OMB
TO
17
=ASUF
USTIC
POF
18
)NCH
FLUe
n 20 21 22 23 24 2§
ROMFtbOR §§§
u.O<;
For SI: 1 inch = 25.4 mm, 1 square inch = 645 mnf .
FIGURE 21134.16
FLUE SIZES FOR MASONRY CHIMNEYS
2113A.18 Masonry chimney cleanout openings. Cleanout
openings shall be provided within 6 inches (152 mm) of the
base of each flue within every masonry chimney. The upper
edge of the cleanout shall be located at least 6 inches (152
mm) below the lowest chimney inlet opening. The height of
the opening shall be at least 6 inches (152 mm). The cleanout
shall be provided with a noncombustible cover.
Exception: Chimney flues serving masonry fireplaces,
where cleaning is possible through the fireplace opening.
2113A.19 Chimney clearances. Any portion of a masonry
chimney located in the interior of the building or within the
exterior wall of the building shall have a minimum airspace
clearance to combustibles of 2 inches (51 mm). Chimneys
located entirely outside the exterior walls of the building,
including chimneys that pass through the soffit or cornice,
shall have a minimum airspace clearance of 1 inch (25 mm).
The airspace shall not be filled, except to provide
fireblocking in accordance with Section 2113A.20.
Exceptions:
1. Masonry chimneys equipped with a chimney lining
system listed and labeled for use in chimneys in con-
tact with combustibles in accordance with UL 1777,
and installed in accordance with the manufacturer' s
instructions, are permitted to have combustible mate-
rial in contact with their exterior surfaces.
2. Where masonry chimneys are constructed as part of
masonry or concrete walls, combustible materials
shall not be in contact with the masonry or concrete
wall less than 12 inches (305 mm) from the inside sur-
face of the nearest flue lining.
3. Exposed combustible trim and the edges of sheathing
materials, such as wood siding, are permitted to abut
the masonry chimney sidewalls, in accordance with
Figure 2113A. 19, provided such combustible trim or
sheathing is a minimum of 12 inches (305 mm) from
the inside surface of the nearest flue lining. Combusti-
ble material and trim shall not overlap the comers of
the chimney by more than 1 inch (25 mm).
2113A.20 Chimney fireblocking. All spaces between chim-
neys and floors and ceiUngs through which chimneys pass shall
be fireblocked with noncombustible material securely fastened
in place. The fireblocking of spaces between wood joists,
beams or headers shall be to a depth of 1 inch (25 mm) and shall
only be placed on strips of metal or metal lath laid across the
spaces between combustible material and the chimney.
2010 CALIFORNIA BUILDING CODE
315
MASONRY
MA^NRY ABUTTING
COf^l^TIBLE SHEATHING
12^ FROM FLUE UNiNG
r OEARANC^ {AIRSPACE)
TO COMBUSTIBLE SHiATHIMS
For SI: 1 inch = 25.4 mm.
FIGURE 2113A19
ILLUSTRATION OF EXCEPTION THREE
CHIMNEY CLEARANCE PROVISION
SECTION 211 4A
NONBEARING WALLS
2114AJ General. All nonbearing masonry walls shall be rein-
I I forced as specified in Section 2 106 A. 1,1. Fences and interior
nonbearing nonshear walls may be of hollow -unit masonry
construction grouted in cells containing vertical and horizon-
tal reinforcement Nonbearing walls may be used to carry a
superimposed load of not more than 200 pounds per linear foot
(2.92 IcN/m).
1. Thickness, Every nonbearing masonry wall shall be so
constructed and have a sufficient thickness to withstand
all vertical loads and horizontal loads, but in no case
shall the thickness of such walls be less than the values
set forth in Table 2107A8.
Plaster shall not be considered as contributing to the
thickness of a wall in computing the height-to- thickness
ratio.
2. Anchorage. All nonbearing walls shall be anchored as
I I required by Section 1604 A 8.2 andASCE 7 Chapter 13.
Suspended ceilings or other nonstructural elements
shall not be used to provide anchorage for masonry
walls.
I I
forcing is continuous without offset. This continuous
joint shall be reinforced with a minimum of 0.03 square
inch (19 mm^) of reinforcing steel. Reinforcement may be
embedded in mortar.
3. Reinforcing. Joint reinforcing may be composed of two
wires made with welded ladder or trussed wire cross ties.
In calculating the resisting capacity of the system, com-
pression and tension in the spaced wires may be utilized.
Ladder wire reinforcing shall not be spliced and shall be
the widest that the mortar joint will accommodate,
allowing V2 l^ch (13 mm) of mortar cover.
4. Size of Panels. The maximum size of panels shall be 144
square feet (13.4 m^), with the maximum dimension in
either direction of 15 feet (4572 mm).
5. Panel Support. Each panel shall be supported on all
edges by a structural member of concrete, masonry or
steel. Supports at the top and ends of the panel shall be by
means of confinement of the masonry by at least V2 inch
(13 mm) into and between the flanges of a steel channel.
The space between the end of the panel and the web of the
channel shall be filled with resilient material The use of
an equivalent configuration in other steel sections or in
masonry or concrete is acceptable.
SECTION 21 ISA
MASONRY SCREEN WALLS
21 ISA. 1 General. Masonry units may be used in nonbearing
decorative screen walls. Units may be laid up in panels with
units on edge with the open pattern of the unit exposed in the
completed wall.
1. Horizontal Forces. The panels shall be capable of span-
ning between supports to resist the horizontal forces
specified in Chapter 16 A. Wind loads shall be based on
the gross projected area of the block.
2. Mortar Joints. Horizontal and vertical joints shall not
be less than % inch (6 mm) thick. All joints shall be com-
pletely filled with mortar and shall be "shoved joint"
work. The units of a panel shall be so arranged that
either the horizontal or the vertical joint containing rein-
316
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 22 - STEEL
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire ciiapter
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
Adopt only those sections that
are listed below
Chapter/Section
2201.1.1
X
2201.1.2
X
2201.1.3
X
2201.1.4
X
2211.1.1
X
2211.1.2
X
2211.1.3
X
2211.2.1
X
2211.2.2
X
2211.3
X
2211.3.1
X
2211.4.1.1
X
2211.4.1.2
X
2211.4.2
X
2211.4.3
X
2211.5.1
X
2211.5.2
X
2010 CALIFORNIA BUILDING CODE
317
31 8 201 CALIFORNIA BUILDING CODE
CHAPTER 22
STEEL
SECTION 2201
GENERAL
2201.1 Scope. The provisions of this chapter govern the qual-
ity, design, fabrication and erection of steel used structurally in
buildings or structures.
220LL1 Application, [DSA-SS/CC] The scope of applica-
tion of Chapter 22 is as follows:
Community college buildings regulated by the Division
of the State Architect-Structural Safety/Community Col-
leges (DSA-SS/CC), as listed in Section L9.2.2.
220LL2 Identification of amendments, [DSA-SS/CC]
Division of the State Architect-Structural Safety/Com-
munity Colleges amendments appear in this chapter pre-
ceded with the appropriate acronym^ as follows:
[DSA'SS/CC] - For community college buildings
listed in Section 1.9,2,2.
2201.1.3 Reference to other chapters. [DSA-SS/CC]
Where reference within this chapter is made to sections in
Chapter 17 the provisions in Chapter 17 A shall apply
instead.
2201.1.4 Amendments. [DSA-SS/CC] See Section 2211 for
additional requirements.
SECTION 2203
IDENTIFICATION AND PROTECTION
OF STEEL FOR STRUCTURAL PURPOSES
2203.1 Identification. Identification of structural steel mem-
bers shall comply with the requirements contained in AISC
360. Identification of cold-formed steel members shall comply
with the requirements contained in AISI S 100. Identification of
cold-formed steel light-frame construction shall also comply
with the requirements contained in AISI S200. Other steel fur-
nished for structural load-carrying purposes shall be properly
identified for conformity to the ordered grade in accordance
with the specified ASTM standard or other specification and
the provisions of this chapter. Steel that is not readily identifi-
able as to grade from marking and test records shall be tested to
determine conformity to such standards.
2203.2 Protection. Painting of structural steel members shall
comply with the requirements contained in AISC 360. Painting
of open-web steel joists and joist girders shall comply with the
requirements of SJI CJ-1.0, SJI JG-1.1, SJI K-1.1 and SJI
LH/DLH-1.1. Individual structural members and assembled
panels of cold-formed steel construction shall be protected
against corrosion in accordance with the requirements con-
tained in AISI SIOO. Protection of cold-formed steel light-
frame construction shall also comply with the requirements
contained in AISI S200.
SECTION 2202
DEFINITIONS
2202.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meaning shown herein.
STEEL CONSTRUCTION, COLD-FORMED. That type
of construction made up entirely or in part of steel structural
members cold formed to shape from sheet or strip steel such as
roof deck, floor and wall panels, studs, floor joists, roof joists
and other structural elements.
STEEL JOIST. Any steel structural member of a building or
structure made of hot-rolled or cold- formed solid or open- web
sections, or riveted or welded bars, strip or sheet steel mem-
bers, or slotted and expanded, or otherwise deformed rolled
sections.
STEEL MEMBER, STRUCTURAL. Any steel structural
member of a building or structure consisting of a rolled steel struc-
tural shape other than cold-formed steel, or steel joist members.
SECTION 2204
CONNECTIONS
2204.1 Welding. The details of design, workmanship and tech-
nique for welding, inspection of welding and qualification of
welding operators shall conform to the requirements of the
specifications listed in Sections 2205, 2206, 2207, 2209 and
2210. Special inspection of welding shall be provided where
required by Section 1704.
IIMJI Bolting. The design, installation and inspection of bolts
shall be in accordance with the requirements of the specifica-
tions listed in Sections 2205, 2206, 2209 and 2210. Special
inspection of the installation of high-strength bolts shall be pro-
vided where required by Section 1704.
2204.2.1 Anchor rods. Anchor rods shall be set accurately
to the pattern and dimensions called for on the plans. The
protrusion of the threaded ends through the connected mate-
rial shall be sufficient to fully engage the threads of the nuts,
but shall not be greater than the length of the threads on the
bolts.
2010 CALIFORNIA BUILDING CODE
319
STEEL
SECTION 2205
STRUCTURAL STEEL
2205.1 GeneraL The design, fabrication and erection of struc-
tural steel for buildings and structures shall be in accordance
with AISC 360. Where required, the seismic design of steel
structures shall be in accordance with the additional provisions
of Section 2205.2.
2205.2 Seismic requirements for steel structures. The
design of structural steel structures to resist seismic forces shall
be in accordance with the provisions of Section 2205.2.1 or
2205.2.2 for the appropriate seismic design category.
2205.2.1 Seismic Design Category A, B or C. Structural
steel structures assigned to Seismic Design Category A, B or
C shall be of any construction permitted in Section 2205. An
R factor as set forth in Section 12.2.1 of ASCE 7 for the
appropriate steel system is permitted where the structure is
designed and detailed in accordance with the provisions of
AISC 341, Part I. Systems not detailed in accordance with
the above shall use the R factor in Section 12.2. 1 of ASCE 7
designated for "structural steel systems not specifically
detailed for seismic resistance."
2205.2.2 Seismic Design Category D, E or F. Structural
steel structures assigned to Seismic Design Category D, E or
F shall be designed and detailed in accordance with AISC
341, Part I.
2205.3 Seismic requirements for composite construction.
The design, construction and quality of composite steel and
concrete components that resist seismic forces shall conform to
the requirements of the AISC 360 and ACI 3 1 8. An /? factor as
set forth in Section 12.2. 1 of ASCE 7 for the appropriate com-
posite steel and concrete system is permitted where the struc-
ture is designed and detailed in accordance with the provisions
of AISC 341, Part IL In Seismic Design Category B or above,
the design of such systems shall conform to the requirements of
AISC 341, Part II.
2205.3.1 Seismic Design Categories D, E and F. Compos-
ite structures are permitted in Seismic Design Categories D ,
E and F, subject to the limitations in Section 1 2.2. 1 of ASCE
7, where substantiating evidence is provided to demonstrate
that the proposed system will perform as intended by AISC
341, Part II. The substantiating evidence shall be subject to
building official approval. Where composite elements or
connections are required to sustain inelastic deformations,
the substantiating evidence shall be based on cyclic testing.
SECTION 2206
STEEL JOISTS
2206.1 General. The design, manufacture and use of open web
steel joists and joist girders shall be in accordance with one of
the following Steel Joist Institute (SJI) specifications:
I 1. SJICJ-1.0
2. SJIK-1.1
3. SJILH/DLH-1.1
4. SJI JG- 1.1
Where required, the seismic design of buildings shall be in
accordance with the additional provisions of Section 2205.2 or
2210.5.
2206.2 Design. The registered design professional shall indi-
cate on the construction documents the steel joist and/or steel
joist girder designations from the specifications listed in Sec-
tion 2206.1 and shall indicate the requirements for joist and
joist girder design, layout, end supports, anchorage, non-SJI
standard bridging, bridging termination connections and bear-
ing connection design to resist uplift and lateral loads. These
documents shall indicate special requirements as follows:
1. Special loads including:
1.1. Concentrated loads ;
1.2. Nonuniform loads;
1.3. Net uplift loads;
1.4. Axial loads;
1.5. End moments; and
1.6. Connection forces.
2. Special considerations including:
2.1. Profiles for nonstandard joist and joist girder
configurations (standard joist and joist girder
configurations are as indicated in the SJI cata-
log);
2.2. Oversized or other nonstandard web openings;
and
2.3. Extended ends.
3. Deflection criteria for live and total loads for non-SJI
standard joists.
2206.3 Calculations. The steel joist and joist girder manufac-
turer shall design the steel joists and/or steel joist girders in
accordance with the current SJI specifications and load tables
to support the load requirements of Section 2206.2. The regis-
tered design professional may require submission of the steel
joist and joist girder calculations as prepared by a registered
design professional responsible for the product design. If
requested by the registered design professional, the steel joist
manufacturer shall submit design calculations with a cover let-
ter bearing the seal and signature of the joist manufacturer's
registered design professional. In addition to standard calcula-
tions under this seal and signature, submittal of the following
shall be included:
1. Non-SJI standard bridging details (e.g. for cantilevered
conditions, net uplift, etc.).
2. Connection details for:
2.1. Non-SJI standard connections (e.g. flush-framed
or framed connections);
2.2. Field splices; and
2.3. Joist headers.
2206.4 Steel joist drawings. Steel joist placement plans shall
be provided to show the steel joist products as specified on the
construction documents and are to be utilized for field installa-
tion in accordance with specific project requirements as stated
320
2010 CALIFORNIA BUILDING CODE
STEEL
in Section 2206.2. Steel placement plans shall include, at a
minimum, the following:
1 . Listing of all applicable loads as stated in Section 2206.2
and used in the design of the steel joists and joist girders
as specified in the construction documents.
2. Profiles for nonstandard joist and joist girder configura-
tions (standard joist and joist girder configurations are as
indicated in the SJI catalog).
3. Connection requirements for:
3.1. Joist supports;
3.2. Joist girder supports;
3.3. Field sphces; and
3.4. Bridging attachments.
4. Deflection criteria for live and total loads for non-SJI
standard joists.
5. Size, location and connections for all bridging.
6. Joist headers.
Steel joist placement plans do not require the seal and signa-
ture of the joist manufacturer's registered design professional.
2206.5 Certification. At completion of manufacture, the steel
joist manufacturer shall submit a certificate of compliance in
accordance with Section 1704.2.2 stating that work was per-
formed in accordance with approved construction documents
and with SJI standard specifications.
SECTION 2209
COLD-FORMED STEEL
2209.1 General. The design of cold-formed carbon and
low-alloy steel structural members shall be in accordance with
AISI SI 00. The design of cold-formed stainless- steel struc-
tural members shall be in accordance with ASCE 8.
Cold-formed steel light-frame construction shall also comply
with Section 2210.
2209.2 Steel decks. The design and construction of
cold-formed steel decks shall be in accordance with this sec-
tion.
2209.2.1 Composite slabs on steel decks. Composite slabs
of concrete and steel deck shall be designed and constructed
in accordance with ASCE 3.
2209.2.2 Noncomposite steel floor decks. Noncomposite
steel floor decks shall be permitted to be designed and con-
structed in accordance with ANSI/SDI-NCl.O, as modified
in Section 2209.2.2.1.
2209.9.2.2.1 ANSI/SDI-NCl.O Section 2.4B1. Replace
Section 2.4B1 of ANSI/SDI-NCl.O with the following:
1. General: The design of the concrete slabs shall be
done in accordance with the ACI Building Code
Requirements for Reinforced Concrete. The mini-
mum concrete thickness above the top of the deck
shall be 1 V2 inches (38 mm).
2209.2.3 Steel roof deck. Steel roof decks shall be permit-
ted to be designed and constructed in accordance with
ANSI/SDI-RDl.O,
SECTION 2207
STEEL CABLE STRUCTURES
2207.1 General. The design, fabrication and erection includ-
ing related connections, and protective coatings of steel cables
for buildings shall be in accordance with ASCE 19.
2207.2 Seismic requirements for steel cable. The design
strength of steel cables shall be determined by the provisions of
ASCE 19 except as modified by these provisions.
1 . A load factor of 1 . 1 shall be applied to the prestress force
included in T^ and r4as defined in Section 3.12.
2. In Section 3.2. 1 , Item (c) shall be replaced with "1.5 7^3"
and Item (d) shall be replaced with "1.5 T^.'"
SECTION 2208
STEEL STORAGE RACKS
2208.1 Storage racks. The design, testing and utiUzation of
industrial steel storage racks made of cold-formed or hot-rolled
steel structural members, shall be in accordance with the
RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic
design of storage racks shall be in accordance with the provi-
sions of Section 15.5.3 of ASCE 7, except that items (1), (2)
and (3) of Section 15.5.3 of ASCE 7 do not apply when the rack
design satisfies RMI/ANSI MH 16.1.
SECTION 2210
COLD-FORMED STEEL
LIGHT-FRAME CONSTRUCTION
2210.1 General. The design and installation of structural
members and nonstructural members utilized in cold-formed
steel Hght-frame construction where the specified minimum
base steel thickness is between 0.0179 inches (0.455 mm) and
0.1180 inches (2.997 mm) shall be in accordance with AISI
S200 and Sections 2210.2 through 2210.7, as applicable.
2210.2 Header design. Headers, including box and back-
to-back headers, and double and single L-headers shall be
designed in accordance with AISI S212 or AISI SIOO.
2210.3 Trusses.
2210.3.1 Design, Cold-formed steel trusses shall be
designed in accordance with AISI S214, Sections 2210.3.1
through 2210.3.5 and accepted engineering practice.
2210.3.2 Truss design drawings. The truss design draw-
ings shall conform to the requirements of Section B2.3 of
AISI S214 and shall be provided with the shipment of
trusses delivered to the job site. The truss design drawings
shall include the details of permanent individual truss mem-
ber restraint/bracing in accordance with Section B6(a) or
B6(c) of AISI S214 where these methods are utilized to pro-
vide restraint/bracing.
2010 CALIFORNIA BUILDING CODE
321
STEEL
2210.3.3 Deferred submittals. AISI Section B4.2 shall be
deleted.
2210.3.4 Trussses spanning 60 feet or greater. The owner
shall contract with a registered design professional for the
design of the temporary installation restraint/bracing and
the permanent individual truss member restraint/bracing for
trusses with clear spans 60 feet (18 288 mm) or greater. Spe-
cial inspection of trusses over 60 feet (18 288 mm) in length
shall conform to Section 1704.
2210.3.5 Truss quality assurance. Trusses not part of a
manufacturing process that provides requirements for qual-
ity control done under the supervision of a third-party qual-
ity control agency, shall be manufactured in compliance
with Sections 1704.2 and 1704.3, as applicable.
2210.4 Wall stud design. Wall studs shall be designed in
accordance with either AISI S21 1 or AISI SIOO.
2210.5 Floor and roof system design. Framing for floor and
roof systems in buildings shall be designed in accordance with
either AISI S210 or AISI SIOO.
2210.6 Lateral design. Light-frame shear walls, diagonal
strap bracing that is part of a structural wall and diaphragms
used to resist wind, seismic and other in-plane lateral loads
shall be designed in accordance with AISI S213.
2210.7 Prescriptive framing. Detached one- and two-family
dwellings and townhouses, less than or equal to three stories
above grade plane, shall be permitted to be constructed in
accordance with AISI S230 subject to the limitations therein.
SECTION 2211
ADDITIONAL REQUIREMENTS [DSA-SS/CC]
2211,1 Connections,
221 LU Welded splice. No welded splices shall be made
except those shown on approved plans. Welded butt splices
subject to tension greater than 33 percent of the expected
yield strength under the load combinations with
overstrength factors, shall have tapered transitions as
required per AWS D1.8 Clause 4.2.
221 LI, 2 Consumables for welding,
2211.1.2.1 Seismic Force Resisting System (SFRS)
welds. All welds used in members and connections in the
SFRS shall be made with filler metals meeting the
requirements specified in AWS D1.8 Clause 6.3, AWS
D1.8 Clauses 6.3.5, 6.3.6, 6.3.7 and 6.3.8 shall apply
only to demand critical welds.
2211.1.2.2 Demand critical welds. Where welds are des-
ignated as demand critical, they shall be made with filler
metals meeting the requirements specified in AWS D1.8
Clause 6.3.
2211,1,3 Welded shear connectors. Where welded shear
connectors are used as part of the seismic force resisting
system their shear and tensile strength shall be reduced by
25 percent from the specified strengths given in AISC 360
Chapter I.
Exception: The 25 percent reduction is not necessary for
collector components in structures designed for load
combinations with overstrength factor
2211,1.4 Column base plate. When shear and/or tensile
forces are intended to be transferred between column base
plates and anchor bolts, provision shall be made in the
design to eliminate the effects of oversized holes permitted
in base plates by AISC 360 by use of shear lugs and/or
welded shear transfer plates or other means acceptable to
the enforcement agency, when the oversized holes are larger
than the anchor bolt by more than Vg inch (3.2 mm). When
welded shear transfer plates and shear lugs or other means
acceptable to the enforcement agency are not used, the
anchor bolts shall be checked for the induced bending
stresses in combination with the shear stresses.
2211.2 Steel joists,
2211.2.1 Design approval. Joist and joist girder design cal-
culations and profiles with member sizes and connection
details, and joist placement plans shall be provided to the
enforcement agency and approved prior to joist fabrication,
in accordance with Title 24, Part 1. Joist and joist girder
design calculations and profiles with member sizes and con-
nection details shall bear the signature and stamp or seal of
the registered engineer or licensed architect responsible for
the joist design. Alterations to the approved joist and joist
girder design calculations and profiles with member sizes
and connection details, or to fabricated joists are subject to
the approval of the enforcement agency.
2211.2.2 Joist chord bracing. The chords of all joists shall
be laterally supported at all points where the chords change
direction.
2211.3 Cold-formed steel,
2211,3,1 Steel deck diaphragms. Diaphragm chord com-
pression and tension forces resulting from in-plane shear
shall be resisted by flange members and not by the steel deck
diaphragm. Reinforced structural concrete on steel deck fill
may be used to resist chord forces.
2211.4 Cold-formed steel light-frame construction,
2211,4,1 Trusses,
2211.4.1.1 Analysis submittals. Complete engineering
analysis and truss design drawings shall accompany the
construction documents submitted to the enforcement
agency for approval When load testing is required, the
test report shall be submitted with the truss design draw-
ings and engineering analysis to the enforcement
agency.
2211.4.1.2 Deferred submittals. AISI Section B4.2 shall
not be deleted.
I I
322
2010 CALIFORNIA BUILDING CODE
STEEL
2211,4. 2 Anchorage for shear, Coldformed steel stud foun-
dation plates or sills shall be bolted or fastened to the foun-
dation or foundation wall in accordance with Section
23043.4, Item 2.
' I 2211,4,3 Limitations on shear wall assemblies. Shear wall
assemblies per Section C2.23 ofAISI-S213 are not permit-
ted within the seismic force-resisting system of buildings or
structures assigned to Occupancy Category II, III, IV or
buildings designed to be relocatable.
I I 221L5 Testing,
2211.5.1 Tests of high-strength bolts, nuts and washers.
High-strength bolts, nuts and washers shall be sampled and
tested by an approved independent testing laboratory for
M I conformance with the requirements of Section 2205.
2211.5.2 Tests of end-welded studs. End-welded studs shall
be sampled and tested per the requirements of the AWS
DLL
201 CALIFORNIA BUILDING CODE 323
324 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 22A - STEEL
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
,
2010 CALIFORNIA BUILDING CODE
325
326 2010 CALIFORNIA BUILDING CODE
CHAPTER 224
STEEL
SECTION 2201 >»
GENERAL
220L4.1 Scope. The provisions of this chapter govern the qual-
ity, design, fabrication and erection of steel used structurally in
buildings or structures.
2201 A J. 1 Application, The scope of application of Chap-
ter 22 A is as follows:
1. Structures regulated by the Division of the State
Architect-Structural Safety (DSA-SS), which include
I I those applications listed in Section 1.9.2.L These
applications include public elementary and second-
ary schools, community colleges and state- owned or
state-leased essential services buildings,
2. Structures regulated by the Office of Statewide
Health Planning and Development (OSHPD), which
I I include those applications listed in Sections 1,10.1,
I I and LI 0.4. These applications include hospitals,
skilled nursing facilities, intermediate care facilities
and correctional treatment centers.
Exception: [OSHPD 2] Single-story Type V
skilled nursing or intermediate care facilities
utilizing wood-frame or light-steel-frame
construction as defined in Health and Safety Code
Section 129725, which shall comply with Chapter
22 and any applicable amendments therein.
2201A.L2 Identification of amendments. DSA-SS and
OSHPD adopt this chapter and all amendments.
Exception: Amendments adopted by only one agency
appear in this chapter preceded with the appropriate
acronym of the adopting agency, as follows:
1. Division of the State Architect-Structural Safety:
[DSA-SS] For applications listed in Section
1.9.2.1.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD I] - For applications listed in Section
LlO.l.
[OSHPD 4] - For applications listed in Section
1.10.4.
II
I
II
J I
SECTION 2202A
DEFINITIONS
2202A.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meaning shown herein.
STEEL CONSTRUCTION, COLD-FORMED. That type
of construction made up entirely or in part of steel structural
members cold formed to shape from sheet or strip steel such as
roof deck, floor and wall panels, studs, floor joists, roof joists
and other structural elements.
STEEL JOIST. Any steel structural member of a building or
structure made of hot-rolled or cold-formed solid or open- web
sections, or riveted or welded bars, strip or sheet steel mem-
bers, or slotted and expanded, or otherwise deformed rolled
sections.
STEEL MEMBER, STRUCTURAL. Any steel structural
member of a building or structure consisting of a rolled steel struc-
tural shape other than cold-formed steel, or steel joist members.
SECTION 2203A
IDENTIFICATION AND PROTECTION
OF STEEL FOR STRUCTURAL PURPOSES
2203A.1 Identification. Identification of structural steel mem-
bers shall comply with the requirements contained in AISC
360. Identification of cold-formed steel members shall comply
with the requirements contained in AISI S 100. Identification of
cold-formed steel light-frame construction shall also comply
with the requirements contained in AISI S200. Other steel fur-
nished for structural load-carrying purposes shall be properly
identified for conformity to the ordered grade in accordance
with the specified ASTM standard or other specification and
the provisions of this chapter. Steel that is not readily identifi-
able as to grade from marking and test records shall be tested to
determine conformity to such standards.
2203A.2 Protection. Painting of structural steel members shall
comply with the requirements contained in AISC 360. Painting
of open-web steel joists and joist girders shall comply with the
requirements of SJI CJ-1.0, SJI JG-1.1, SJI K-Ll and SJI
LH/DLH-1.1. Individual structural members and assembled
panels of cold-formed steel construction shall be protected
against corrosion in accordance with the requirements con-
tained in AISI SI 00. Protection of cold- formed steel light-
frame construction shall also comply with the requirements
contained in AISI S200.
SECTION 2204A
CONNECTIONS
2204A.1 Welding. The details of design, workmanship and
technique for welding, inspection of welding and qualification
of welding operators shall conform to the requirements of the
specifications listed in Sections 2205 A, 2206 A, 2207 A, 2209 A
and 2210A. Special inspection of welding shall be provided
where required by Section 1704.
2204 A, 1.1 Welded splice. No welded splices shall be made
except those shown on approved plans. Welded butt splices
subject to tension greater than 33 percent of the expected
yield strength under the load combinations with
overstrength factors, shall have tapered transitions as
required per AWS D1.8 Clause 4.2.
2010 CALIFORNIA BUILDING CODE
327
STEEL
2204AJ.2 Consumables for welding.
2204AJ.2.L Seismic Force Resisting System (SFRS)
Welds.
All welds used in members and connections in the
SFRS shall be made with filler metals meeting the
requirements specified in AWS D1.8 Clause 6.3. AWS
DL8 Clauses 6.3.5, 6.3.6, 6.3.7 and 6.3.8 shall apply
only to demand critical welds.
2204AJ,2,2, Demand critical welds.
Where welds are designated as demand critical, they
shall be made with filler metals meeting the requirements
specified in AWS D1.8 Clause 6.3.
2204AJ.3 Welded shear connectors. Where welded shear
connectors in composite members are used as part of the
seismic force resisting system, their shear and tensile
strength shall be reduced by 25 percent from the specified
strengths given in AISC 360 Chapter L
Exception: The 25 percent reduction is not necessary for
collector components designed for load combinations
that include the overstrength factor
2204A.2 Bolting. The design, installation and inspection of
bolts shall be in accordance with the requirements of the speci-
fications Hsted in Sections 2205 A, 2206A, 2209A and 2210A.
Special inspection of the installation of high-strength bolts
shall be provided where required by Section 1704.
2204A.2.1 Anchor rods. Anchor rods shall be set accu-
rately to the pattern and dimensions called for on the plans.
The protrusion of the threaded ends through the. connected
material shall be sufficient to fully engage the threads of the
nuts, but shall not be greater than the length of the threads on
the bolts.
2204A,2,2 Column base plate. When shear and/or tensile
forces are intended to be transferred between column base
plates and anchor bolts, provisions shall be made in the
design to eliminate the effects of oversized holes permitted
in base plates by AISC 360 by use of shear lugs and/or
welded shear transfer plates or other means acceptable to
the enforcement agency, when the oversized holes are larger
than the anchor bolt by more than % inch (3.2 mm). When
welded shear transfer plates and shear lugs or other means
acceptable to the enforcement agency are not used, the
anchor bolts shall be checked for the induced bending
stresses in combination with the shear stresses.
SECTION 2205A
STRUCTURAL STEEL
2205 A. 1 GeneraL The design, fabrication and erection of
structural steel for buildings and structures shall be in accor-
dance with AISC 360. Where required, the seismic design of
steel structures shall be in accordance with the additional pro-
visions of Section 2205A.2,
2205A.2 Seismic requirements for steel structures. The
design of structural steel structures to resist seismic forces shall
be in accordance with the provisions of Section 2205A.2.2 for
the appropriate seismic design category.
2205A.2.1 Seismic Design Category A, B or C. Not per-
mitted by DSA-SS or OSHPD.
2205A.2.2 Seismic Design Category D, E or F. Structural
steel structures assigned to Seismic Design Category D, E or
F shall be designed and detailed in accordance with AISC
341, Part I irrespective ofR values, unless approved other-
wise by the enforcement agency.
2205A.3 Seismic requirements for composite construction.
The design, construction and quality of composite steel and
concrete components that resist seismic forces shall conform to
the requirements of the AISC 360 and ACI 3 18. An 7? factor as
set forth in Section 12.2.1 of ASCE 7 for the appropriate com-
posite steel and concrete system is permitted where the struc-
ture is designed and detailed in accordance with the provisions
of AISC 341, Part II. In Seismic Design Category B or above,
the design of such systems shall conform to the requirements of
AISC 341, Part II.
2205A.3.1 Seismic Design Categories D, E and F. Com-
posite structures are permitted in Seismic Design Catego-
ries D , E and F, subject to the limitations in Section 12.2.1
of ASCE 7, and shall be considered on an alternative sys-
tem, where substantiating evidence is provided to demon-
strate that the proposed system will perform as intended by
AISC 341, Part II. The substantiating evidence shall be sub-
ject to building official approval. Where composite ele-
ments or connections are required to sustain inelastic
deformations, the substantiating evidence shall be based on
cyclic testing.
2205 AA Modifications to AISC 34L [OSHPD 1 and 4]
2205A.4.1 Part I, Structural Steel Building Provisions
Modifications.
2205A.4.1.1 Part I, Section 9, Special Moment Frame
(SMF) Modifications,
2205A.4,1,1,1 AISC 341, Part I, Section 9JA,
Requirements for Beam-to-Column Connections,
Replace Item (1) as follows:
The connection shall be capable of sustaining
an interstory drift angle of at least 0.04 radians
and an inelastic rotation of 0.03 radians.
2205A,4.1,1.2 AISC 341, Parti, Section 9,2b(a), Use
of SMF connections designed in accordance with
ANSI/AISC 358 shall be as modified in Section
2205A.5
2205A,4,I,2 Part I, Section 10, Intermediate Moment
Frame (IMF), Not permitted by OSHPD.
2205A,4,1,3 Part I, Section 11, Ordinary Moment
Frame (OMF), Not permitted by OSHPD.
2205A,4,1,4 Part I, Section 12, Special Truss Moment
Frame (STMF), Not permitted by OSHPD.
2205A.4.1.5 Part I, Section 13, Special Concentrically
Braced Frames (SCBF) Modifications,
328
2010 CALIFORNIA BUILDING CODE
STEEL
2205A.4.L5.1 AISC 341, Part I, Section 13, Mem-
bers, Add a new section as follows:
AISC 341, I3.2f— Member Types
The use of rectangular HSS are not permitted for
bracing members, unless filled solid with cement
grout having a minimum compressive strength of
3000 psi (20, 7 MPa) at 28 days. The effects of com-
posite action in the filled composite brace shall be
considered in the sectional properties of the system
where it results in the more severe loading condi-
tion or detailing.
2205A.4.L5.2 Part I, Section 13: Add Section 13.7
as follows.
13.7 Beam to Column Connections.
SCBF frames shall have moment-resisting
beam-column connections that can resist a
moment equal to the lesser of the available flexural
strength of the beam or the column in the SCBF
bays. The connection shall include CJP welds from
the beam flanges to the column flange, or to a plate
in the case of column weak axis connections.
2205A.4.1.6 Part I, Section 14, Ordinary Concentric
cally Braced Frames (OCBF). Not permitted by
OSHPD.
2205 A.4, 1.7 Part I, Section 15, Eccentrically Braced
Frames (EBF) Modifications.
Part I, 15.4 Link-to-Column Connections.
Exception: Not permitted by OSHPD.
2205A.4.2 Appendix S, Qualifying Cyclic Tests of Beam-
tO'Column and Link-to-Column Connections Modifica-
tions.
2205A.4.2.1 Appendix S, S3, Definitions. Replace the
definition of *' Inelastic rotation" with the following:
INELASTIC ROTATION. The permanent or plastic
portion of the rotation angle between a beam and the
column, or between a link and the column of the test
specimen, measured in radians. The inelastic rotation
shall be computed based upon an analysis of the test
specimen deformations. Sources of inelastic rotation
include yielding of members and connectors, yielding
of connection elements and slip between members
and connection elements. For beam-to-column
moment connections in special moment frames, the
inelastic rotation is represented by the plastic chord
rotation angle calculated as the plastic deflection of
the beam or girder, at the center of its span divided by
the distance between the center of the beam span and
the centerline of the panel zone of the beam-column
connection. For link-to-column connections in eccen-
trically braced frames, inelastic rotation shall be
computed based upon the assumption that inelastic
action is concentrated at a single point located at the
intersection of the centerline of the link with the face
of the column.
2205A.4.2.2 Appendix S, S3, Definitions. Add the fol-
lowing:
RAPID STRENGTH DETERIORATION. A mode
of behavior characterized by a sudden loss of
strength. In a cyclic test with constant or increasing
deformation amplitude, a loss of strength of more
than 50 percent of the strength attained in the previ-
ous excursion in the same loading direction.
2205A.4.2.3 Appendix S, Section S5.2, Size of Mem-
bers. Replace as follows:
The size of the beam or link used in the test speci-
men shall be within the following limits:
1. At least one of the test beams or links shall be no
less than 100 percent of the depth of the proto-
type beam or link. For the remaining speci-
mens, the depth of the test beam or link shall be
no less than 90 percent of the depth of the proto-
type beam or link.
2. At least one of the test beams or links shall be no
less than 100 percent of the weight per foot of
the prototype beam or link. For the remaining
specimens, the weight per foot of the test beam
or link shall be no less than 75 percent of the
weight per foot of the prototype beam or link.
The size of the column used in the test specimen
shall properly represent the inelastic action in the
column, as per the requirements in Section S5.1. In
addition, the depth of the test column shall be no
less than 90 percent of the depth of the prototype
column.
Extrapolation beyond the limitations stated in this
section shall be permitted subject to peer review and
approval by the enforcement agency.
2205A.4.2.4 Appendix S, Section SIO, Acceptance Cri-
teria. Replace as follows:
The test specimens must satisfy the strength,
interstory drift angle, or link rotation angle, and
inelastic rotation requirements of these provisions for
the special moment frame and eccentrically braced
frame connection as applicable. The test specimen
must sustain the required interstory drift angle, or link
rotation angle, and inelastic rotation for at least two
complete loading cycles without exhibiting rapid
strength deterioration.
2205AA3 Appendix T, Qualifying Cyclic Tests ofBuck-
ling-Restrained Braces Modification.
AISC 341, T5.3, Similarity of Brace Test Specimen and
Prototype, replace Item 2 with the following:
The axial yield strength of the steel core Fy sc of the brace
test specimen shall not be more than 20 percent above nor
50 percent less than that of the test specimen where both
strengths are based on the core area, Asc, multiplied by the
yield strength as determined from a coupon test. In addition,
the material of the test specimen shall be the same ASTM
classification and grade as the prototype.
2010 CALIFORNIA BUILDING CODE
329
STEEL
2205 A.5 MODIFICATIONS TOAISC358, [OSHPD I&4]
2205A.5J 2. Design Requirements, 2,1 Special and Inter-
mediate Moment Frame Connection Types, Table 2-1
Prequalified Moment Connections modifications
>| I The prequalified bolted moment connections, with bolts
>| I (except erection bolts), are not permitted in buildings.
The prequalification of moment connections at orthogo-
nal moment frames sharing common columns or moment
connections attached to other than one side or two opposite
sides of a column is not permitted by OSHPD.
SECTION 2206A
STEEL JOISTS
2206 A. 1 General. The design, manufacture and use of open
web steel joists and joist girders shall be in accordance with one
of the following Steel Joist Institute (SJI) specifications:
I 1. SnCJ-1.0
2. SJIK-1.1
3. SJILH/DLH-1.1
4. SJIJG-1.1
Where required, the seismic design of buildings shall be in
accordance with the additional provisions of Section 2205 A.2
or2210A.5.
2206 A.2 Design. The registered design professional shall indi-
cate on the construction documents the steel joist and/or steel
joist girder designations from the specifications listed in Sec-
tion 2206A.1 and shall indicate the requirements for joist and
joist girder design, layout, end supports, anchorage, non-SJI
standard bridging, bridging termination connections and bear-
ing connection design to resist uplift and lateral loads. These
documents shall indicate special requirements as follows:
1. Special loads including:
1.1. Concentrated loads;
1.2. Nonuniform loads;
1.3. Net uplift loads;
1.4. Axial loads;
1.5. End moments; and
1.6. Connection forces.
2. Special considerations including:
2.1. Profiles for nonstandard joist and joist girder
configurations (standard joist and joist girder
configurations are as indicated in the SJI cata-
log);
2.2. Oversized or other nonstandard web openings;
and
2.3. Extended ends.
3. Deflection criteria for live and total loads for non-SJI
standard joists.
2206A.3 Calculations. The steel joist and joist girder manu-
facturer shall design the steel joists and/or steel joist girders in
accordance with the current SJI specifications and load tables
to support the load requirements of Section 2206A.2. The reg-
istered design professional may require submission of the steel
joist and joist girder calculations as prepared by a registered
design professional responsible for the product design. If
requested by the registered design professional, the steel joist
manufacturer shall submit design calculations with a cover let-
ter bearing the seal and signature of the joist manufacturer's
registered design professional. In addition to standard calcula-
tions under this seal and signature, submittal of the following
shall be included:
1. Non-SJI standard bridging details (e.g. for cantilevered
conditions, net uplift, etc.).
2. Connection details for:
2.1. Non-SJI standard connections (e.g. flush- framed
or framed connections);
2.2. Field splices; and
2.3. Joist headers.
2206A.4 Steel joist drawings. Steel joist placement plans
shall be provided to show the steel joist products as specified on
the construction documents and are to be utilized for field
installation in accordance with specific project requirements as
stated in Section 2206A.2. Steel placement plans shall include,
at a minimum, the following:
1. Listing of all applicable loads as stated in Secfion
2206 A.2 and used in the design of the steel joists and
joist girders as specified in the construction documents.
2. Profiles for nonstandard joist and joist girder configura-
tions (standard joist and joist girder configurations are as
indicated in the SJI catalog).
3. Connection requirements for:
3.1. Joist supports;
3.2. Joist girder supports;
3.3. Field splices; and
3.4. Bridging attachments.
4. Deflection criteria for live and total loads for non-SJI
standard joists.
5. Size, location and connections for all bridging.
6. Joist headers.
2206A,4.1 Design approval [DSA-SS] Joist and joist
girder design calculations and profiles with member sizes
and connection details, and joist placement plans shall be
provided to the enforcement agency and approved prior to
joist fabrication, in accordance with Title 24, Part L Joist
and joist girder design calculations and profiles with mem-
ber sizes and connection details shall bear the signature
and stamp or seal of the registered engineer or licensed
architect responsible for the joist design. Alterations to the
approved joist and joist girder design calculations and pro-
files with member sizes and connection details, or to fabri-
cated joists are subject to the approval of the enforcement
agency,
2206A.5 Certification. At completion of manufacture, the
steel joist manufacturer shall submit a certificate of compliance
in accordance with Section 1704.2.2 stating that work was per-
<
II
330
2010 CALIFORNIA BUILDING CODE
STEEL
formed in accordance with approved construction documents
and with SJI standard specifications.
2206 A.6 Joist chord bracing. The chords of all joists shall be
laterally supported at all points where the chords change direc-
tion.
SECTION 2207A
STEEL CABLE STRUCTURES
2207A.1 GeneraL The design, fabrication and erection includ-
ing related connections, and protective coatings of steel cables
for buildings shall be in accordance with ASCE 19.
2207A.2 Seismic requirements for steel cable. The design
strength of steel cables shall be determined by the provisions of
ASCE 19 except as modified by these provisions.
1 . A load factor of 1 . 1 shall be applied to the prestress force
included in T^ and T^ as defined in Section 3, 12.
2. In Section 3.2.1, Item (c) shall be replaced with "1.5 Tg"
and Item (d) shall be replaced with "1.5 T^r
SECTION 2208A
STEEL STORAGE RACKS
2208A.1 Storage racks. The design, testing and utilization of
industrial steel storage racks made of cold-formed or hot-rolled
steel structural members, shall be in accordance with the
RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic
design of storage racks shall be in accordance with the provi-
sions of Section 15.5.3 of ASCE 7, except that items (1), (2)
and (3) of Section 15.5.3 of ASCE 7 do not apply when the rack
design satisfies RMI/ANSI MH 16.1.
SECTION 2209A
COLD-FORMED STEEL
2209 A. 1 GeneraL The design of cold-formed carbon and
low-alloy steel structural members shall be in accordance with
AISI SIOO. The design of cold-formed stainless-steel struc-
tural members shall be in accordance with ASCE 8.
Cold-formed steel light-frame construction shall also comply
with Section 221 OA.
2209A.2 Steel decks. The design and construction of
cold-formed steel decks shall be in accordance with this sec-
tion.
2209A.2.1 Composite slabs on steel decks. Composite
slabs of concrete and steel deck shall be designed and con-
structed in accordance with ASCE 3.
2209A.2.2 Noncomposite steel floor decks. Noncompos-
ite steel floor decks shall be permitted to be designed and
constructed in accordance with ANSI/SDI-NCl .0, as modi-
fied in Section 2209A.2.2.1.
2209A.9.2.2.1 ANSI/SDI-NCl.O Section 2.4B1.
Replace Section 2.4B1 of ANSI/SDI-NCl.O with the
following:
1. General: The design of the concrete slabs shall be
done in accordance with the ACI Building Code
Requirements for Reinforced Concrete, The mini-
mum concrete thickness above the top of the deck
shall be 1 V2 inches (38 mm).
2209A.2.3 Steel roof deck. Steel roof decks shall be per-
mitted to be designed and constructed in accordance with
ANSI/SDI-RDl.O.
2209 A,3 Steel deck diaphragms. Steel deck diaphragms shall
comply with the requirements of this section. The design of the
diaphragm as well as the construction details may be based on
test information acceptable to the enforcement agency. Steel
deck and concrete-filled steel deck diaphragms that are tested
per ICC-ES AC 43 shall be considered to meet the requirements
of this section.
Diaphragm chord forces both compression and tension
forces resulting from in-plane shear shall be resisted by flange
members and not by the steel deck diaphragm.
The base material thickness of steel deck for diaphragms
shall not be less than 0.0359 inch (0.9 mm) (20 gage), unless
tests acceptable to the enforcement agency have been per-
formed.
SECTION 2210 A
COLD-FORMED STEEL
LIGHT-FRAME CONSTRUCTION
2210A.1 General. The design and installation of structural
members and nonstructural members utilized in cold-formed
steel light-frame construction where the specified minimum
base steel thickness is between 0.0179 inches (0.455 mm) and
0.1180 inches (2.997 mm) shall be in accordance with AISI
S200 and Sections 2210A.2 through 2210A.7, as applicable.
2210A.2 Header design. Headers, including box and back-
to-back headers, and double and single L-headers shall be
designed in accordance with AISI S212 or AISI SIOO.
2210A.3 Trusses.
2210A.3.1 Design. Cold-formed steel trusses shall be
designed in accordance with AISI S214, Sections
2210A.3.1 through 2210A.3.5 and accepted engineering
practice.
Complete engineering analysis and truss design draw-
ings shall accompany the construction documents submit-
ted to the enforcement agency for approval When load
testing is required, the test report shall be submitted with the
truss design drawings and engineering analysis to the
enforcement agency.
2210A.3.2 Truss design drawings. The truss design draw-
ings shall conform to the requirements of Section B2.3 of
AISI S214 and shall be provided with the shipment of
trusses delivered to the job site. The truss design drawings
shall include the details of permanent individual truss mem-
ber restraint/bracing in accordance with Section B of AISI
S214 where these methods are utilized to provide restraint/
bracing.
2210A.3.3 Deferred submittals. Not permitted by DSA-SS
or OSHPD.
<
2010 CALIFORNIA BUILDING CODE
331
STEEL
2210A.3.4 Trussses spanning 60 feet or greater. The
owner shall contract with a registered design professional
for the design of the temporary installation restraint/bracing
and the permanent individual truss member restraint/brac-
ing for trusses with clear spans 60 feet (18 288 mm). or
greater. Special inspection of trusses over 60 feet (18 288
mm) in length shall conform to Section 1704.
2210A.3.5 Truss quality assurance. Trusses not part of a
manufacturing process that provides requirements for qual-
ity control done under the supervision of a third-party qual-
ity control agency,' shall be manufactured in compliance
with Sections 1704.2 and 1704.3, as applicable.
2210A.4 Wall stud design. Wall studs shall be designed in
accordance with either AISI S21 1 or AISI SIOO.
Cold formed steel stud foundation plates or sills shall be
bolted or fastened to the foundation or foundation wall in
accordance with Section 2304.3.4, Item 2.
2210A.5 Floor and roof system design. Framing for floor and
roof systems in buildings shall be designed in accordance with
either AISI S210 or AISI SIOO.
2210A.6 Lateral design. Light-frame shear walls, diagonal
strap bracing that is part of a structural wall and diaphragms
used to resist wind, seismic and other in-plane lateral loads
shall be designed in accordance with AISI S213,
Shear wall assemblies per Section C2.2:3 ofAISI-S2I3 are
not permitted within the seismic force-resisting system ofbuild-
> ings.
2210A.7 Prescriptive framing. Not permitted by DSA-SS and
OSHPD.
SECTION 221 1A [DSA-SS]
LIGHT MODULAR STEEL MOMENT FRAMES FOR
PUBLIC ELEMENTARY AND SECONDARY
SCHOOLS, AND COMMUNITY COLLEGES
2211A.1 General
2211 AAA Conjiguratioh. Light modular steel moment
frame buildings shall be constructed of factory-assembled
modules comprising a single-story moment-resisting space
frame supporting a floor and roof Individual modules shall
not exceed a width of 14 feet (4.25 m) nor a length of 72 feet
(22 m). All connections of beams to corner columns shall be
designed as moment-resisting in accordance with the crite-
ria of Section 2211A.2. Modules may be stacked to form
multistory structures not exceeding 35 feet or two stories in
height. When stacked modules are evaluated separately,
seismic forces on each module shall be distributed in accor-
dance with Section 12.8.3 ofASCE 7, considering the mod-
ules in the stacked condition. See Section 2211A.2.5 of this
code.
2211AA,2 Design, fabrication and erection. The design,
fabrication and erection of light modular steel moment-
frame buildings shall be in accordance with theAlSC Speci-
fication for Structural Steel Buildings (ANSI/AISC 360) and
the AISI North American Specification for the Design of
Cold Formed Structural Members (AlSl/COS/NASPEC), as
applicable, and the requirements of this section. The maxi-
mum dead load of the roof and elevated floor shall not
exceed 25 psf and 50 psf(1197 Pa and 2394 Pa), respec-
tively. The maximum dead load of the exterior walls shall
not exceed 45 psf (2155 Pa).
2211A,2 Seismic requirements. In addition to the other
requirements of this code, the design, materials and workman-
ship of light modular steel moment frames shall comply with
the requirements of this section. The response modification
coefficient R shall be equal to 3^/2. Cd and WO shall be equal to
3.0.
2211A.2A Base materials. Beams, columns and connection
materials shall be limited to those materials permitted
under the AISC Specification for Structural Members
(ANSI/AISC 360) and the AISI North American Specifica-
tion for the Design of Cold Formed Structural Members
(AISI/COS/NASPEC).
2211A,2,2 Beam-tO'Column strength ratio. At each
moment-resisting connection the following shall apply:
y SbiFybi
^ ^1-4
/^ ScjFycj
(Equation 22A-1)
• where:
Fyf^i = The specified yield stress of beam "/. "
Fy^j = The specified yield stress of column "j. "
Sfji = Theflexural section modulus of each beam "i" that
is moment connected to the column *7" ^t the con-
nection.
Scj , = The flexural section modulus of each column "j"
that is moment connected to the beam 'H " at the con-
nection.
Exceptions:
1. Beam-to-column connections at the floor level
beams of first or second-story modules need not
comply with this requirement.
2. Beam-to-column strength ratios less than 1.4 are
allowed if proven to be acceptable by analysis or
testing.
2211A,2,3 Welding, Weld filler metals shall be capable of
producing weld metal with a minimum Charpy V-Notch
toughness of 20 ft-lb at O^'F. Where beam bottom fianges
attach to columns with complete joint penetration groove
welds and weld backing is used at the bottom surface of the
beam fiange, such backing shall be removed and the root
pass back-gouged, repaired and reinforced with a minimum
V;5 inch (5 mm) fillet weld.
2211A,2,4 Connection design. Connections of beams to
columns shall have the design strength to resist the maxi-
mum seismic load effect, E^ , calculated in accordance with
Section 12.4.3 ofASCE 7.
2211A,2,5 Multistory assemblies. Analysis of multistory
assemblies shall be permitted to consider the stacked mod-
332
2010 CALIFORNIA BUILDING CODE
STEEL
ules as a single assembly, with restraint conditions between
the stacked units that represent the actual method of attach-
ment. Alternatively, it shall be permitted to analyze the indi-
vidual modules of stacked assemblies independently, with
lateral and vertical reactions from modules above applied as
concentrated loads at the top of the supporting module.
SECTION 221 2A
TESTING
2212 A,l Tests of high-strength bolts, nuts and washers.
High-strength bolts, nuts and washers shall be sampled and
tested by an approved independent testing laboratory for con-
formance with the requirements of Section 2205 A,
2212 A,2 Tests of end-welded studs. End-welded studs shall be
sampled and tested per the requirements of the AWS DLL
201 CALIFORNIA BUILDING CODE 333
334 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 23 - WOOD
Adopting agency
esc
SFM
HCD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
X
X
X
Adopt only those sections that
are listed below
X
X
Chapter/Section
2301.1
X
X
2301.1.1
X
X
X
X
X
2301.1.2
X
X
X
X
X
2301.1.3
X
X
X
X
X
2301.1.3.1
X
2301.1.3.2
X
2301.2
X
X
X
2301 .2, Item 4, Exception
X
X
2303.1.3.1
X
X
X
X
X
2303.2-2303.2.9
X
2303.4.1.2. Exceptions
X
X
2303.4.1.4.1
X
X
X
2303.4.3.1
X
X
X
X
X
2304.3.4
X
X
X
X
X
2304.4.1
X
X
2304.4.4.1
X
X
X
2304.5
X
X
2304.6.1, Exception
X
X
X
X
2304.9.1.1
X
X
X
X
2304.11.2.1.1
X
2304.11.2.2, w/Exception
X
X
X
X
2304.11.2.4.1
X
X
X
X
2304.11.2.8
X
2305.1.2
X
X
X
X
X
X
2305.1.3
X
X
X
X
X
2305.1.4
X
X
X
X
X
2305.1.7
X
2305.2, Exception
X
X
X
X
X
2305.3, Exception
X
X
X
X
X
Table 2306.3, Footnote m
X
X
X
X
X
2306.3.1
X
X
X
X
X
2306.4
X
X
X
X
X
2306.7, Exception
X
X
X
X
X
2308.1
X
X
X
X
2308.2, Item 8
X
X
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section LIL
2010 CALIFORNIA BUILDING CODE
335
336 2010 CALIFORNIA BUILDING CODE
CHAPTER 23
WOOD
SECTION 2301
GENERAL
2301.1 Scope. The provisions of this chapter shall govern the
materials, design, construction and quality of wood members
and their fasteners.
[HCD 1] For limited-density owner-built rural dwellings,
owner-produced or used materials and appliances may he uti-
lized unless found not to be of sufficient strength or durability to
perform the intended function; owner-produced or used lum-
ber, or shakes and shingles may be utilized unless found to con-
tain dry rot, excessive splitting or other defects obviously
rendering the material unfit in strength or durability for the
intended purpose.
I I 230LL1 Application. [DSA-SS, DSA-SS/CC and OSHPD
1,2&,4] The scope of application of Chapter 23 is as fol-
lows:
1. Applications listed in Sections 1.9.2.1 and 1.9.2.2,
regulated by the Division of the State Architect-Struc-
tural Safety (DSA-SS, and DSA-SS/CC). These appli-
cations include public elementary and secondary
schools, community colleges and state-owned or
state-leased essential services buildings.
I I 2. Applications listed in Section 1.10, regulated by the
Office of Statewide Health Planning and Develop-
ment (OSHPD). These applications include hospi-
tals, skilled nursing facilities, intermediate care
facilities and correctional treatment centers.
Exception: For applications listed in Section
LI 0.3 (Licensed Clinics), the provisions of this
chapter without OSHPD amendments identified in
accordance with Section 2301.1.2 shall apply.
2301.1.2 Identification of amendments, [DSA-SS,
I I DSA-SS/CC and OSHPD 1,2&4] Amendments appear in
this chapter preceded with the appropriate acronym, as fol-
lows:
L Division of the State Architect-Structural Safety:
[DSA-SS] - For applications listed in Section 1.9.2.1.
[DSA-SS/CC] - For applications listed in Section
1.92.2.
2. Office of Statewide Health Planning and Develop-
ment:
[OSHPD 1] - For applications listed in Section 1.10.1.
[OSHPD 2] - For applications listed in Section 1.10.2.
[OSHPD 4] - For applications listed in Section 1.10.4.
2301.1.3 Reference to other chapters,
I I 2301,1,3,1 [DSA-SS and OSHPD 1 & 4] Where refer-
ence within this chapter is made to sections in Chapters
16, 17, 18, 19, 21, 22 and 34, the provisions in Chapters
16A, 17 A, ISA, 19A, 21A, 22A and34A respectively shall
apply instead.
Exception: For DSA-SS, the requirements of Chapter
34 shall apply instead of Chapter 34A
2301.1,3,2 [DSA-SS/CC] Where reference within this
chapter is made to sections in Chapters 17 and 18, the
provisions in Chapters 17 A and ISA respectively shall
apply instead.
2301.2 General design requirements. The design of struc-
tural elements or systems, constructed partially or wholly of
wood or wood-based products, shall be in accordance with one
of the following methods:
1. Allowable stress design in accordance with Sections
2304, 2305 and 2306.
2. Load and resistance factor design in accordance with
Sections 2304, 2305 and 2307.
3. Conventional light-frame construction in accordance
with Sections 2304 and 2308.
Exception: Buildings designed in accordance with
the provisions of the AF&PA WFCM shall be deemed
to meet the requirements of the provisions of Section
2308.
4. The design and construction of log structures shall be in
accordance with the provisions of ICC 400.
Exception: [DSA-SS, DSA-SS/CC and OSHPD 7, 2
& 4] Log structures are not permitted.
2301.3 Nominal sizes. For the purposes of this chapter, where
dimensions of lumber are specified, they shall be deemed to be
nominal dimensions unless specifically designated as actual
dimensions (see Section 2304.2).
SECTION 2302
DEFINITIONS
2302.1 Definitions. The following words and terms shall, for
the purposes of this chapter, have the meanings shown herein.
ACCREDITATION BODY. An approved, third-party organi-
zation that is independent of the grading and inspection agen-
cies, and the lumber mills, and that initially accredits and
subsequently monitors, on a continuing basis, the competency
and performance of a grading or inspection agency related to
carrying out specific tasks.
BRACED WALL LINE. A series of braced wall panels in a
single story that meets the requirements of Section 2308.3 or
2308.12.4.
BRACED WALL PANEL. A section of wall braced in accor-
dance with Section 2308.9.3 or 2308.12.4.
2010 CALIFORNIA BUILDING CODE
337
WOOD
COLLECTOR. A horizontal diaphragm element parallel and
in line with the applied force that collects and transfers dia-
phragm shear forces to the vertical elements of the lateral-
force-resisting system and/or distributes forces within the dia-
phragm.
CONVENTIONAL LIGHT-FRAME CONSTRUCTION.
A type of construction whose primary structural elements are
formed by a system of repetitive wood-framing members. See
Section 2308 for conventional light-frame construction provi-
sions.
CRIPPLE WALL. A framed stud wall extending from the top
of the foundation to the underside of floor framing for the low-
est occupied floor level.
DIAPHRAGM, UNBLOCKED. A diaphragm that has edge
naiUng at supporting members only. Blocking between sup-
porting structural members at panel edges is not included. Dia-
phragm panels are field nailed to supporting members.
DRAG STRUT. See "Collector."
FIBERBOARD. A fibrous, homogeneous panel made from
lignocellulosic fibers (usually wood or cane) and having a den-
sity of less than 3 1 pounds per cubic foot (pcf) (497 kg/m^) but
more than 10 pcf (160 kg/m^).
GLUED BUILT-UP MEMBER. A structural element, the
section of which is composed of built-up lumber, wood struc-
tural panels or wood structural panels in combination with lum-
ber, all parts bonded together with structural adhesives.
GRADE (LUMBER). The classification of lumber in regard
to strength and utiUty in accordance with American Softwood
Lumber Standard DOC PS 20 and the grading rules of an
approved lumber rules-writing agency.
HARDBOARD. A fibrous-felted, homogeneous panel made
from lignocellulosic fibers consolidated under heat and pres-
sure in a hot press to a density not less than 3 1 pcf (497 kg/m^).
NAILING, BOUNDARY. A special nailing pattern required
by design at the boundaries of diaphragms.
NAILING, EDGE. A special nailing pattern required by
design at the edges of each panel within the assembly of a dia-
phragm or shear wall.
NAILING, FIELD. Nailing required between the sheathing
panels and framing members at locations other than boundary
naihng and edge nailing.
NATURALLY DURABLE WOOD. The heartwood of the
following species with the exception that an occasional piece
with corner sapwood is permitted if 90 percent or more of the
width of each side on which it occurs is heartwood.
Decay resistant. Redwood, cedar, black locust and black
walnut.
Termite resistant. Redwood, Alaska yellow-cedar. Eastern
redcedar and both heartwood and all sapwood of Western
redcedar.
NOMINAL SIZE (LUMBER). The commercial size desig-
nation of width and depth, in standard sawn lumber and
glued-laminated lumber grades; somewhat larger than the stan-
dard net size of dressed lumber, in accordance with DOC PS 20
for sawn lumber and with the AF&PA NDS for glued-lami-
nated lumber.
PARTICLEBOARD. A generic term for a panel primarily
composed of cellulosic materials (usually wood), generally in
the form of discrete pieces or particles, as distinguished from
fibers. The cellulosic material is combined with synthetic resin
or other suitable bonding system by a process in which the
interparticle bond is created by the bonding system under heat
and pressure.
PREFABRICATED WOOD I- JOIST. Structural member
manufactured using sawn or structural composite lumber
flanges and wood structural panel webs bonded together with
exterior exposure adhesives, which forms an "I" cross-sectional
shape.
SHEAR WALL. A wall designed to resist lateral forces paral-
lel to the plane of a wall.
Shear wall, perforated. A wood structural panel sheathed
wall with openings, that has not been specifically designed
and detailed for force transfer around openings.
Shear wall segment, perforated. A section of shear wall
with full-height sheathing that meets the height- to- width
ratio limits of Section 4.3.4 of AF&PA SDPWS.
STRUCTURAL COMPOSITE LUMBER. Structural mem-
ber manufactured using wood elements bonded together with
exterior adhesives. Examples of structural composite lumber
are:
Laminated veneer lumber (LVL). A composite of wood
veneer sheet elements with wood fibers primarily oriented
along the length of the member.
Parallel strand lumber (PSL). A composite of wood
strand elements with wood fibers primarily oriented along
the length of the member.
STRUCTURAL GLUED-LAMINATED TIMBER. An
engineered, stress-rated product of a timber laminating plant,
comprised of assemblies of specially selected and prepared
wood laminations in which the grain of all laminations is
approximately parallel longitudinally and the laminations are
bonded with adhesives.
SUBDIAPHRAGM. A portion of a larger wood diaphragm
designed to anchor and transfer local forces to primary dia-
phragm struts and the main diaphragm.
TIE-DOWN (HOLD-DOWN). A device used to resist uplift
of the chords of shear walls.
TREATED WOOD. Wood and wood-based materials that use
vacuum-pressure impregnation processes to enhance fire retar-
dant or preservative properties.
Fire-retardant-treated wood. Pressure-treated lumber
and plywood that exhibit reduced surface-burning charac-
teristics and resist propagation of fire.
Preservative-treated wood. Pressure-treated wood prod-
ucts that exhibit reduced susceptibility to damage by fungi,
insects or marine borers.
WOOD SHEAR PANEL. A wood floor, roof or wall compo-
nent sheathed to act as a shear wall or diaphragm.
338
2010 CALIFORNIA BUILDING CODE
WOOD
WOOD STRUCTURAL PANEL. A panel manufactured
from veneers, wood strands or wafers or a combination of
veneer and wood strands or wafers bonded together with water-
proof synthetic resins or other suitable bonding systems.
Examples of wood structural panels are:
Composite panels. A wood structural panel that is com-
prised of wood veneer and reconstituted wood-based mate-
rial and bonded together with waterproof adhesive;
Oriented strand board (OSB). A mat-formed wood struc-
tural panel comprised of thin rectangular wood strands
arranged in cross-aligned layers with surface layers nor-
mally arranged in the long panel direction and bonded with
waterproof adhesive; or
Plywood. A wood structural panel comprised of plies of
wood veneer arranged in cross-aligned layers. The plies are
bonded with waterproof adhesive that cures on application
of heat and pressure.
SECTION 2303
MINIMUM STANDARDS AND QUALITY
2303.1 General. Structural sawn lumber; end-jointed lumber;
prefabricated wood I-joists; structural glued-laminated timber;
wood structural panels, fiberboard sheathing (when used struc-
turally); hardboard siding (when used structurally);
particleboard; preservative-treated wood; structural log mem-
bers; structural composite lumber; round timber poles and
pilQs; fire-retardant-treated wood; hardwood plywood; wood
trusses; joist hangers; nails; and staples shall conform to the
applicable provisions of this section.
2303.1.1 Sawn lumber. Sawn lumber used for load-sup-
porting purposes, including end-jointed or edge-glued lum-
ber, machine stress-rated or machine-evaluated lumber,
shall be identified by the grade mark of a lumber grading or
inspection agency that has been approved by an accredita-
tion body that complies with DOC PS 20 or equivalent.
Grading practices and identification shall comply with rules
published by an agency approved in accordance with the
procedures of DOC PS 20 or equivalent procedures. In lieu
of a grade mark on the material, a certificate of inspection as
to species and grade issued by a lumber grading or inspec-
tion agency meeting the requirements of this section is per-
mitted to be accepted for precut, remanufactured or
rough-sawn lumber and for sizes larger than 3 inches (76
mm) nominal thickness.
Approved end-jointed lumber is permitted to be used
interchangeably with solid-sawn members of the same spe-
cies and grade.
2303.1.2 Prefabricated wood I-joists. Structural capaci-
ties and design provisions for prefabricated wood I-joists
shall be established and monitored in accordance with
ASTM D 5055.
2303.1.3 Structural glued-laminated timber. Glued-lam-
inated timbers shall be manufactured and identified as
required in ANSI/AITC A 190.1 and ASTM D 3737.
2303,1,3.1 Additional requirements, [DSA-SS,
DSA-SS/CC and OSHPD 1, 2 & 4] The construction
documents shall indicate the following:
I I
II
7. Dry or wet service conditions, <;
2. Laminating combinations and stress require-
ments. ^
3. Species group, ^
4. Preservative material and retention^ when preser-
vative treatment is required, ^
5. Provisions for protection during shipping and
field handling, such as sealing and wrapping in
accordance with AITC 111,
When mechanical reinforcement such as radial ten-
sion reinforcement is required, such reinforcement shall
comply with AITC 404 and shall he detailed accordingly
in the construction documents. Construction documents
shall specify that the moisture content of laminations at
the time of manufacture shall not exceed 12 percent for
dry conditions of use.
The design of fasteners and connections shall comply
with AITC 117, Section 7, Item 6 (Connection Design),
and NDS Appendix E.
Refer to Section 1704A.6,3 for special inspection
requirements during fabrication of structural glued lam-
inated timbers.
Exception: [OSHPD 2] Special inspection shall be
per Chapter 17 instead of 17 A,
2303.1.4 Wood structural panels. Wood structural panels,
when used structurally (including those used for siding, roof
and wall sheathing, subflooring, diaphragms and built-up
members), shall conform to the requirements for their type
in DOC PS 1 or PS 2. Each panel or member shall be identi-
fied for grade and glue type by the trademarks of an
approved testing and grading agency. Wood structural panel
components shall be designed and fabricated in accordance
with the applicable standards listed in Section 2306.1 and
identified by the trademarks of an approved testing and
inspection agency indicating conformance with the applica-
ble standard. In addition, wood structural panels when per-
manently exposed in outdoor applications shall be of
exterior type, except that wood structural panel roof sheath-
ing exposed to the outdoors on the underside is permitted to
be interior type bonded with exterior glue, Exposure 1.
2303.1.5 Fiberboard. Fiberboard for its various uses shall
conform to ASTM C 208. Fiberboard sheathing, when used
structurally, shall be identified by an approved agency as
conforming to ASTM C 208.
2010 CALIFORNIA BUILDING CODE
339
WOOD
2303.1.5.1 Jointing. To ensure tight-fitting assemblies,
edges shall be manufactured with square, shiplapped,
beveled, tongue-and-groove or U-shaped joints.
2303.1.5.2 Roof insulation. Where used as roof insula-
tion in all types of construction, fiberboard shall be pro-
tected with an approved roof covering.
2303.1.5.3 Wall insulation. Where installed and
fireblocked to comply with Chapter 7, fiberboards are
permitted as wall insulation in all types of construction.
In fire walls and fire barriers, unless treated to comply
with Section 803. 1 for Class A materials, the boards shall
be cemented directly to the concrete, masonry or other
noncombustible base and shall be protected with an
approved noncombustible veneer anchored to the base
without intervening airspaces.
2303.1.5.3.1 Protection. Fiberboard wall insulation
applied on the exterior of foundation walls shall be
protected below ground level with a bituminous coat-
ing.
2303.1.6 Hardboard. Hardboard siding used structurally
shall be identified by an approved agency conforming to
CPA/ANSI A 135.6. Hardboard underlayment shall meet
the strength requirements of ^/32-inch (5.6 mm) or V4-inch
(6.4 mm) service class hardboard planed or sanded on one
side to a uniform thickness of not less than 0.200 inch (5. 1
mm). Prefinished hardboard paneling shall meet the
requirements of CPA/ANSI A135.5, Other basic hardboard
products shall meet the requirements of CPA/ANSI A 1 35 .4.
Hardboard products shall be installed in accordance with
manufacturer's recommendations.
2303.1.7 Particleboard. Particleboard shall conform to
ANSI A208 . 1 . Particleboard shall be identified by the grade
mark or certificate of inspection issued by an approved
agency. Particleboard shall not be utilized for applications
other than indicated in this section unless the particleboard
complies with the provisions of Section 2306.5.
2303.1.7.1 Floor underlayment. Particleboard floor
underlayment shall conform to Type PBU of ANSI
A208.1. Type PBU underlayment shall not be less than
V4-inch (6.4 mm) thick and shall be installed in accor-
dance with the instructions of the Composite Panel Asso-
ciation.
2303.1.8 Preservative-treated wood. Lumber, timber, ply-
wood, piles and poles supporting permanent structures
required by Section 2304, 1 1 to be preservative treated shall
conform to the requirements of the applicable AWPA Stan-
dard Ul and M4 for the species, product, preservative and
end use. Preservatives shall be listed in Section 4 of AWPA
Ul . Lumber and plywood used in wood foundation systems
shall conform to Chapter 18.
2303.1.8.1 Identification. Wood required by Section
2304.1 1 to be preservative treated shall bear the quality
mark of an inspection agency that maintains continuing
supervision, testing and inspection over the quality of the
preservative-treated wood. Inspection agencies for pre-
servative-treatedwood shall be listedby an accreditation
body that complies with the requirements of the Ameri-
can Lumber Standards Treated Wood Program, or equiv-
alent. The quality mark shall be on a stamp or label
affixed to the preservative-treated wood, and shall
include the following information:
1 . Identification of treating manufacturer.
2. Type of preservative used.
3. Minimum preservative retention (pcf).
4. End use for which the product is treated.
5 . AWPA standard to which the product was treated.
6. Identity of the accredited inspection agency.
2303.1.8.2 Moisture content. Where preserva-
tive-treated wood is used in enclosed locations where
drying in service cannot readily occur, such wood shall
be at a moisture content of 19 percent or less before being
covered with insulation, interior wall finish, floor cover-
ing or other materials.
2303.1.9 Structural composite lumber. Structural capaci-
ties for structural composite lumber shall be established and
monitored in accordance with ASTM D 5456.
2303.1.10 Structural log members. Stress grading of
structural log members of nonrectangular shape, as typi-
cally used in log buildings, shall be in accordance with
ASTM D 3957 . Such structural log members shall be identi-
fied by the grade mark of an approved lumber grading or
inspection agency. In lieu of a grade mark on the material, a
certificate of inspection as to species and grade issued by a
lumber grading or inspection agency meeting the require-
ments of this section shall be permitted.
2303.1.11 Round timber poles and piles. Round timber
poles and piles shall comply with ASTM D 3200 and ASTM
D 25, respectively.
2303.2 Fire-retardant-treated wood. Fire-retardant-treated
wood is any wood product which, when impregnated with
chemicals by a pressure process or other means during manu-
facture, shall have, when tested in accordance with ASTM E 84
or UL 723, a listed f\2im& spread index of 25 or less and show no
evidence of significant progressive combustion when the test is
continued for an additional 20-minute period. Additionally, the
flame front shall not progress more than IOV2 feet (3200 mm)
beyond the centerline of the burners at any time during the test.
2303.2.1 Pressure process. For wood products impreg-
nated with chemicals by a pressure process, the process
shall be performed in closed vessels under pressures not less
than 50 pounds per square inch gauge (psig) (345 kPa).
2303.2.2 Other means during manufacture. For wood
products produced by other means during manufacture, the
treatment shall be an integral part of the manufacturing pro-
cess of the wood product. The treatment shall provide per-
manent protection to all surfaces of the wood product.
2303.2.3 Testing. For wood products produced by other
means during manufacture, other than a pressure process,
all sides of the wood product shall be tested in accordance
with and produce the results required in Section 2303.2.
Wood structural panels shall be permitted to test only the
front and back faces.
340
2010 CALIFORNIA BUILDING CODE
WOOD
2303.2.4 Labeling. Fire-retardant-treated lumber and wood
structural panels shall be labeled. The label shall contain the
following items:
1. The identification mark of an approved agency in
accordance with Section 1703.5.
2. Identification of the treating manufacturer.
3. The name of the fire-retardant treatment.
4. The species of wood treated.
5. Flame spread and smoke-developed index.
6. Method of drying after treatment.
7. Conformance with appropriate standards in accor-
dance with Sections 2303.2.2 through 2303.2.5.
8. For fire-retardant-treated wood exposed to weather,
damp or wet locations, include the words "No
increase in the listed classification when subjected to
the Standard Rain Test" (ASTM D 2898).
2303.2.5 Strength adjustments. Design values for
untreated lumber and wood structural panels, as specified
in Section 2303.1, shall be adjusted for fire-retar-
dant-treated wood. Adjustments to design values shall be
based on an approved method of investigation that takes
into consideration the effects of the anticipated tempera-
ture and humidity to which th^ fire-retardant-treated wood
will be subjected, the type of treatment and redrying proce-
dures.
2303.2.5.1 Wood structural panels. The effect of
treatment and the method of redrying after treatment,
and exposure to high temperatures and high humidities
on the flexure properties of fire-retardant-treated soft-
wood plywood shall be determined in accordance with
ASTM D 5516. The test data developed by ASTM D
5516 shall be used to develop adjustment factors, maxi-
mum loads and spans, or both, for untreated plywood
design values in accordance with ASTM D 6305. Each
manufacturer shall publish the allowable maximum
loads and spans for service as floor and roof sheathing
for its treatment.
2303.2.5.2 Lumber. For each species of wood that is
treated, the effects of the treatment, the method of
redrying after treatment and exposure to high tempera-
tures and high humidities on the allowable design prop-
erties of fire-retardant-treated lumber shall be
determined in accordance with ASTM D 5664. The test
data developed by ASTM D 5664 shall be used to
develop modification factors for use at or near room tem-
perature and at elevated temperatures and humidity in
accordance with ASTM D 6841. Each manufacturer
shall publish the modification factors for service at tem-
peratures of not less than 80°F (27°C) and for roof fram-
ing. The roof framing modification factors shall take into
consideration the cHmatological location.
2303.2.6 Exposure to weather, damp or wet locations.
Whtrc fire-retardant-treated wood is exposed to weather,
or damp or wet locations, it shall be identified as "Exte-
rior" to indicate there is no increase in the listed flame
spread index as defined in Section 2303.2 when subjected
to ASTM D 2898.
2303.2.7 Interior applications. Interior fire-retar-
dant-treated wood shall have moisture content of not over
28 percent when tested in accordance with ASTM D 3201
procedures at 92-percent relative humidity. Interior
fire-retardant-treated wood shall be tested in accordance
with Section 2303.2.5.1 or 2303.2.5.2. Inimor fire-retar-
dant-treated wood designated as Type A shall be tested in
accordance with the provisions of this section.
2303.2.8 Moisture content. Fire-retardant-treated wood
shall be dried to a moisture content of 19 percent or less for
lumber and 15 percent or less for wood structural panels
before use. For wood kiln dried after treatment (KDAT),
the kiln temperatures shall not exceed those used in kiln
drying the lumber and plywood submitted for the tests
described in Secfion 2303.2.5.1 for plywood and
2303.2.5.2 for lumber.
2303.2.9 Type I and II construction applications. See
Section 603.1 for limitations on the use of fire-retar-
dant-treated wood in buildings of Type I or II construction.
2303.3 Hardwood and plywood. Hardwood and decorative
plywood shall be manufactured and identified as required in
HPVAHP-1.
2303.4 Trusses.
2303.4.1 Design. Wood trusses shall be designed in accor-
dance with the provisions of this code and accepted engi-
neering practice. Members are permitted to be joined by
nails, glue, bolts, timber connectors, metal connector plates
or other approved framing devices.
2303.4.1.1 Truss design drawings. The written, graphic
and pictorial depiction of each individual truss shall be
provided to the building ofifcial for approval prior to
installation. Truss design drawings shall also be pro-
vided with the shipment of trusses delivered to the job
site. Truss design drawings shall include, at a minimum,
the information specified below:
1. Slope or depth, span and spacing;
2. Location of all joints and support locations;
3. Number of plies if greater than one;
4. Required bearing widths;
5. Design loads as applicable, including;
5.1. Top chord Hve load;
5.2. Top chord dead load;
5.3. Bottom chord live load;
5.4. Bottom chord dead load;
5.5. Additional loads and locations; and
5.6. Environmental design criteria and loads
(wind, rain, snow, seismic, etc.),
6. Other lateral loads, including drag strut loads;
7 . Adjustments to wood member and metal connec-
tor plate design value for conditions of use;
2010 CALIFORNIA BUILDING CODE
341
WOOD
8. Maximum reaction force and direction, includ-
ing maximum uplift reaction forces where appli-
cable;
9. Metal-connector-plate type, size and thickness or
gage, and the dimensioned location of each metal
connector plate except where symmetrically
located relative to the joint interface;
10. Size, species and grade for each wood member;
1 1 . Truss-to-truss connections and truss field assem-
bly requirements;
12. Calculated span-to-deflection ratio and maxi-
mum vertical and horizontal deflection for live
and total load as applicable;
13. Maximum axial tension and compression forces
in the truss members; and
14. Required permanent individual truss member
restraint location and the method and details of
restraint/bracing to be used in accordance with
Section 2303.4.1.2.
2303.4.1.2 Permanent individual truss member
restraint. Where permanent restraint of truss members
is required on the truss design drawings, it shall be
accomplished by one of the following methods:
1 . Permanent individual truss member restraint/brac-
ing shall be installed using standard industry lat-
eral restraint/bracing details in accordance with
generally accepted engineering practice. Loca-
tions for lateral restraint shall be identified on the
truss design drawing.
2. The trusses shall be designed so that the buckling
of any individual truss member is resisted inter-
nally by the individual truss through suitable
means (i.e., buckling reinforcement by T-rein-
forcement or L-reinforcement, proprietary rein-
forcement, etc.). The buckling reinforcement of
individual members of the trusses shall be installed
as shown on the truss design drawing or on supple-
mental truss member buckling reinforcement
details provided by the truss designer.
3. A project- specific permanent individual truss
member restraint/bracing design shall be permit-
ted to be specified by any registered design profes-
sional.
2303.4.1.3 Trusses spanning 60 feet or greater. The
owner shall contract with any qualified registered design
professional for the design of the temporary installation
restraint/bracing and the permanent individual truss
member restraint/bracing for all trusses with clear spans
60 feet (18 288 mm) or greater.
2303.4.1.4 Truss designer. The individual or organiza-
tion responsible for the design of trusses.
2303.4.1.4.1 Truss design drawings. Where
required by the registered design professional, the
building official or the statutes of the jurisdiction in
which the project is to be constructed, each individual
truss design drawing shall bear the seal and signature
of the truss designer.
Exceptions:
1. Where a cover sheet and truss index sheet
are combined into a single sheet and
attached to the set of truss design drawings,
the single cover/truss index sheet is the only
document required to be signed and sealed
by the truss designer.
2. When a cover sheet and a truss index sheet
are separately provided and attached to the
set of truss design drawings, the cover sheet
and the truss index sheet are the only docu-
ments required to be signed and sealed by
the truss designer.
3. [DSA-SS, DSA-SS/CCand OSHPD 1, 2 &
4] Exceptions 1 and 2 are not permitted by
DSA or OSHPD.
2303.4.2 Truss placement diagram. The truss manufac-
turer shall provide a truss placement diagram that identifies
the proposed location for each individually designated truss
and references the corresponding truss design drawing. The
truss placement diagram shall be provided as part of the
truss submittal package, and with the shipment of trusses
delivered to the job site. Truss placement diagrams that
serve only as a guide for installation and do not deviate from
the permit submittal drawings shall not be required to bear
the seal or signature of the truss designer.
2303.4.3 Truss submittal package. The truss submittal
package provided by the truss manufacturer shall consist of
each individual truss design drawing, the truss placement
diagram, the permanent individual truss member restraint/
bracing method and details and any other structural details
germane to the trusses; and, as applicable, the cover/truss
index sheet.
2303,4,3.1 Additional requirements, [DSA-SS,
DSA-SS/CC and OSHPD 1,2&4] In addition to Sec- I
tions 2304.1 and 23042, the following requirements
apply:
1. Construction documents. The construction docu-
ments prepared by the registered engineer or
licensed architect for the project shall indicate all
requirements for the truss design, including:
1.1. Deflection criteria.
1. 2. Connection details to structural and
non- structural elements (e.g, nonbearing
partitions).
2. Requirements for approval. The truss design
drawings and engineering analysis shall be pro-
vided to the enforcement agency and approved
prior to truss fabrication, in accordance with
C. C.R. Title 24, Parti. Alterations to the approved
truss design drawings or manufactured trusses are
subject to the approval of the enforcement agency.
3. Special inspection during truss manufacture.
Refer to Section 1704A.6.2 for special inspection
342
2010 CALIFORNIA BUILDING CODE
WOOD
requirements during the manufacture of open-web
trusses.
2303.4.4 Anchorage. The design for the transfer of loads
and anchorage of each truss to the supporting structure is the
responsibihty of the registered design professional.
2303.4.5 Alterations to trusses. Truss members and com-
ponents shall not be cut, notched, drilled, spliced or other-
wise altered in any way without written concurrence and
approval of a registered design professional Alterations
resulting in the addition of loads to any member (e.g.,
HVAC equipment, piping, additional roofing or insulation,
etc.) shall not be permitted without verification that the truss
is capable of supporting such additional loading.
2303.4.6 TPI 1 specifications. In addition to Sections
2303.4.1 through 2303.4.5, the design, manufacture and
quality assurance of metal-plate-connected wood trusses
shall be in accordance with TPI I. Job-site inspections shall
be in compliance with Section 110.4, as applicable.
2303.4.7 Truss quality assurance. Trusses not part of a
manufacturing process in accordance with either Section
2303.4.6 or a standard listed in Chapter 35, which provides
requirements for quality control done under the supervision
of a third-party quality control agency, shall be manufac-
tured in comphance with Sections 1704.2 and 1704.6, as
applicable.
2303.5 Test standard for joist hangers and connectors. For
the required test standards for joist hangers and connectors, see
Section 1716.1.
2303.6 Nails and staples. Nails and staples shall conform to
requirements of ASTM F 1667. Nails used for framing and
sheathing connections shall have minimum average bending
yield strengths as follows: 80 kips per square inch (ksi) (551
MPa) for shank diameters larger than 0. 1 77 inch (4.50 mm) but
not larger than 0.254 inch (6.45 mm), 90 ksi (620 MPa) for
shank diameters larger than 0.142 inch (3.61 mm) but not
larger than 0.177 inch (4.50 mm) and 100 ksi (689 MPa) for
shank diameters of at least 0.099 inch (2.5 1 mm) but not larger
than 0.142 inch (3.61 mm).
2303.7 Shrinkage. Consideration shall be given in design to
the possible effect of cross-grain dimensional changes consid-
ered vertically which may occur in lumber fabricated in a green
condition.
SECTION 2304
GENERAL CONSTRUCTION REQUIREMENTS
2304.1 General. The provisions of this section apply to design
methods specified in Section 2301.2.
2304.2 Size of structural members. Computations to deter-
mine the required sizes of members shall be based on the net
dimensions (actual sizes) and not nominal sizes.
2304.3 Wall framing. The framing of exterior and interior
walls shall be in accordance with the provisions specified in
Section 2308 unless a specific design is furnished.
2304.3.1 Bottom plates. Studs shall have full bearing on a
2-inch-thick (actual 1 Vs-inch, 38 mm) or larger plate or sill
having a width at least equal to the width of the studs.
2304.3.2 Framing over openings. Headers, double joists,
trusses or other approved assemblies that are of adequate
size to transfer loads to the vertical members shall be pro-
vided over window and door openings in load-bearing walls
and partitions.
2304.3.3 Shrinkage. Wood walls and bearing partitions
shall not support more than two floors and a roof unless an
analysis satisfactory to the building official shows that
shrinkage of the wood framing will not have adverse effects
on the structure or any plumbing, electrical or mechanical
systems, or other equipment installed therein due to exces-
sive shrinkage or differential movements caused by shrink-
age. The analysis shall also show that the roof drainage
system and the foregoing systems or equipment will not be
adversely affected or, as an alternate, such systems shall be
designed to accommodate the differential shrinkage or
movements.
2304J.4 Additional requirements. [DSA-SS,DSA-SS/CC 1 I
and OSHPD 1, 2 & 4] The following additional require- I I
ments apply:
1. Engineering analysis shall be furnished that demon-
strates compliance of wall framing elements and con-
nections with Section 2301.2, Item I or 2.
2. Construction documents shall include detailing of sill
plate anchorage to supporting masonry or concrete
for all exterior and interior bearing, nonbearing and
shear walls. Unless specifically designed in accor-
dance with item 1 above, sills under exterior walls,
bearing walls and shear walls shall be bolted to
masonry or concrete with V^ inch diameter by 12 inch
(16 mm by 305 mm) bolts spaced not more than four
(4) feet (1219 mm) on center, with a minimum of two
(2) bolts for each piece of sill plate. Anchor bolts shall
have a 4 inch (1016 mm) minimum and a 12 inch
(304,8 mm) maximum clearance to the end of the sill
plate, and 7 inch (177.8 mm) minimum embedment
into concrete or masonry.
Unless specifically designed in accordance with
Item I above, sill plates under nonbearing interior
partitions on concrete floor slabs shall be anchored
at not more than four (4) feet (1219 mm) on center to
resist a minimum allowable stress shear of 100
pounds per linear foot (1.4 kN/m) acting either paral-
lel or perpendicular to the wall.
3. Construction documents shall include detailing and
limitations for notches and bored holes in wall studs,
plates and sills. <
2304.4 Floor and roof framing. The framing of wood-joisted
floors and wood framed roofs shall be in accordance with the
provisions specified in Section 2308 unless a specific design is
furnished.
2010 CALIFORNIA BUILDING CODE
343
WOOD
2304,4 J Additional requirements, [DSA-SS, DSA-SS/CC
and OSHPD 1, 2 & 4] The following additional require-
ments apply:
1. Engineering analysis shall be furnished that demon-
strates compliance of floor, roof and ceiling framing
elements and connections with Section 2301.2, Items
lor 2.
2. Construction documents shall include detailing and
limitations for notches and bored holes in floor and
roof framing members.
2304.5 Framing around flues and chimneys. Combustible
framing shall be a minimum of 2 inches (5 1 mm), but shall not
be less than the distance specified in Sections 2111 and 2113
and the California Mechanical Code, from flues, chimneys and
fireplaces, and 6 inches (152 mm) away from flue openings.
2304.6 Wall sheathing. Except as provided for in Section 1405
for weatherboarding or where stucco construction that com-
plies with Section 25 10 is installed, enclosed buildings shall be
sheathed with one of the materials of the nominal thickness
specified in Table 2304.6 or any other approved material of
equivalent strength or durability.
2304.6.1 Wood structural panel sheathing. Where wood
structural panel sheathing is used as the exposed finish on
the exterior of outside walls, it shall have an exterior expo-
sure durability classification. Where wood structural panel
sheathing is used elsewhere, but not as the exposed finish, it
shall be of a type manufactured with exterior glue (Expo-
sure 1 or Exterior). Wood structural panel wall sheathing or
siding used as structural sheathing shall be capable of resist-
ing wind pressures in accordance with Section 1609. Maxi-
mum wind speeds for wood structural panel sheathing used
to resist wind pressures shall be in accordance with Table
2304.6. 1 for enclosed buildings with a mean roof height not
greater than 30 feet (9144 mm), an importance factor (/) of
1.0 and a topographic factor (K^ ^) of 1.0.
Exception: [DSA-SSand OSHPD 1Sl4] Wind pressure
shall be calculated in accordance with Section 1609 A.
2304.6.2 Interior paneling. Softwood wood structural
panels used for interior paneling shall conform to the pro-
visions of Chapter 8 and shall be installed in accordance
with Table 2304.9.1. Panels shall comply with DOC PS 1
or PS 2. Prefinished hardboard paneling shall meet the
requirements of CPA/ANSI A 135.5. Hardwood plywood
shall conform to HPVA HP-1 .
2304.7 Floor and roof sheathing.
2304.7.1 Structural floor sheathing. Structural floor
sheathing shall be designed in accordance with the general
provisions of this code and the special provisions in this sec-
tion.
Floor sheathing conforming to the provisions of Table
2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(4) shall be
deemed to meet the requirements of this section.
2304.7.2 Structural roof sheathing. Structural roof sheath-
ing shall be designed in accordance with the general provi-
sions of this code and the special provisions in this section.
Roof sheathing conforming to the provisions of Table
2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(5) shall be
deemed to meet the requirements of this section. Wood struc-
tural panel roof sheathing shall be bonded by exterior glue.
2304.8 Lumber decking.
2304.8.1 General. Lumber decking shall be designed and
installed in accordance with the general provisions of this
code and Section 2304.8. Each piece shall be square end
trimmed. When random lengths are furnished, each piece
shall be square end trimmed across the face so that at least
90 percent of the pieces are within 0.5 degrees (0.00873 rad)
of square. The ends of the pieces shall be permitted to be
beveled up to 2 degrees (0.0349 rad) from the vertical with
the exposed face of the piece slightly longer than the oppo-
site face of the piece. Tongue-and-groove decking shall be
installed with the tongues up on sloped or pitched roofs with
pattern faces down.
2304.8.2 Layup patterns. Lumber decking is permitted to
be laid up following one of five standard patterns as defined
in Sections 2304.8.2.1 through 2304.8.2.5. Other patterns
are permitted to be used provided they are substantiated
through engineering analysis.
TABLE 2304.6
MINIMUM THICKNESS OF WALL SHEATHING
SHEATHING TYPE
MINIMUM THICKNESS
MAXIMUM WALL STUD SPACING
Wood boards
Vg inch
24 inches on center
Fiberboard
V2 inch
16 inches on center
Wood structural panel
In accordance with Tables 2308.9.3(2) and 2308.9.3(3)
—
M-S "Exterior Glue" and M-2
"Exterior Glue" Particleboard
In accordance with Tables 2306.5 and 2308.9.3(4)
—
Gypsum sheathing
V2 inch
16 inches on center
Gypsum wallboard
72 inch
24 inches on center
Reinforced cement mortar
1 inch
24 inches on center
For SI; 1 inch = 25.4 mm.
344
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2304.6.1
MAXIMUM BASIC WIND SPEED (mph) (3-SECOND GUST) PERMITTED FOR
WOOD STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND PRESSURES^ "■'^
MINIMUM NAIL
MINIMUM WOOD
STRUCTURAL
PANEL SPAN
RATING
MINIMUM
NOMINAL PANEL
THICKNESS
(inches)
MAXIMUM
WALL STUD
SPACING
(inches)
PANEL NAIL SPACING
MAXIMUM WIND SPEED (MPH)
Size
Penetration
(inclies)
Edges
(inches o.c.)
Field
(inches o.c.)
Wind exposure category
B
c
D
6d common
(2.0" X 0.113")
1.5
24/0
\
16
6
12
110
90
85
24/16
^/l6
16
6
12
110
100
90
6
150
125
110
8d common
(2.5" X 0.131")
1.75
24/16
^/l6
16
6
12
130
110
105
6
150
125
110
24
6
12
110
90
85
6
110
90
85
For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.
a. Panel strength axis shall be parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied
with panel strength axis perpendicular to supports.
b. The table is based on wind pressures acting toward and away from building surfaces in accordance with Section 6.4,2.2 of ASCE 7. Lateral requirements shall be in
accordance with Section 2305 or 2308.
c. Wood structural panels with span ratings of wall- 16 or wall-24 shall be permitted as an alternative to panels with a 24/0 span rating. Plywood siding rated 16 o.c. or
24 o.c. shall be permitted as an alternative to panels with a 24/16 span rating. Wall-16 and plywood siding 16 o.c. shall be used with studs spaced a maximum of 16
inches o.c.
TABLE 2304.7(1)
ALLOWABLE SPANS FOR LUMBER FLOOR AND ROOF SHEATHING'' '^
SPAN (inches)
MINIMUM NET THICKNESS (inches) OF LUMBER PLACED
Perpendicular to supports
Diagonally to supports
Surfaced dry''
Surfaced unseasoned
Surfaced dry''
Surfaced unseasoned
Floors
24
16
'%2
%
%
"/,5
Roofs
24
% ■
%6
%
"/32
For SI: 1 inch = 25.4 mm.
a. Installation details shall conform to Sections 2304.7.1 and 2304.7.2 for floor and roof sheathing, respecti/ely.
b. Floor or roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
c. Maximum 19-percent moisture content.
2010 CALIFORNIA BUILDING CODE
345
WOOD
TABLE 2304.7(2)
SHEATHING LUMBER, MINIMUM GRADE REQUIREMENTS: BOARD GRADE
SOLID FLOOR OR ROOF SHEATHING
SPACED ROOF SHEATHING
GRADING RULES
Utility
Standard
NLGA, WCLIB, WWPA
4 common or utility
3 common or standard
NLGA, WCLIB, WWPA, NSLB or NELMA
No. 3
No. 2
SPIB
Merchantable
Construction common
RIS
TABLE 2304.7(3)
ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL PANEL SHEATHING AND
SINGLE-FLOOR GRADES CONTINUOUS OVER TWO OR MORE SPANS WITH
STRENGTH AXIS PERPENDICULAR TO SUPPORTS^'**
SHEATHING GRADES
ROOF'=
FLOORS
Panel span rating
roof/floor span
Panel thickness
(inches)
Maximum span (Inches)
Load^(psf)
Maximum span
(inches)
With edge support*
Without edge support
Total load
Live load
16/0
\
16
16
40
30
20/0
%
20
20
40
30
24/0
%,'U,%
24
20^
40
30
24/16
'/l6,V2
24
24
50
40
16
32/16
^32' ^2' 4
32
28
40
30
16^
40/20
^32' 4' ^4' ^8
40
32
40
30
20h-i
48/24
^V3,.X%
48
36
45
35
24
54/32
%,1
54
40
45
35
32
60/32
%i%
60
48
45
35
32
SINGLE FLOOR GRADES
ROOF'=
FLOOR''
Panel span rating
Panel thickness
(inches)
Maximum span (inches)
Load^(psf)
Maximum span
(inches)
With edge support*
Without edge support
Total load
Live load
16 o.c.
^2' ^32' ^8
24
24
50
40
16^
20 o.c.
%2,'U^%
32
32
40
30
20h'i
24 o.c.
'%1^'U
48
36
35
25
24
32 o.c.
%,1
48
40
50
40
32
48 o.c.
1^2,1 Vs
60
48
50
40
48
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m^.
a. Applies to panels 24 inches or wider.
b. Floor and roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
c. Uniform load deflection limitations V^go of span under live load plus dead load, ^1^^ under live load only.
d. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking unless V4-inch minimum thickness underlayment or 1 72 inches of
approved cellular or lightweight concrete is placed over the subfloor, or finish floor is V4-inch wood strip. Allowable uniform load based on deflection of Vg^^ of
span is 100 pounds per square foot except the span rating of 48 inches on center is based on a total load of 65 pounds per square foot.
e. Allowable load at maximum span.
f. Tongue-and-groove edges, panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center), lumber block-
ing or other. Only lumber blocking shall satisfy blocked diaphragm requirements.
g. For V2-inch panel, maximum span shall be 24 inches.
h. Span is permitted to be 24 inches on center where ^/4-inch wood strip flooring is installed at right angles to joist.
i. Span is permitted to be 24 inches on center for floors where l'/2 inches of cellular or lightweight concrete is applied over the panels.
346
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2304.7(4)
ALLOWABLE SPAN FOR WOOD STRUCTURAL PANEL COMBINATION SUBFLOOR-UNDERLAYMENT (SINGLE FLOOR)^ "
(Panels Continuous Over Two or More Spans and Strength Axis Perpendicular to Supports)
IDENTIFICATION
MAXIMUM SPACING OF JOISTS (inches)
16
20
24
32
48
Species group*^
Thickness (inches)
1
%
%
%
—
—
2,3
\
\
%
—
—
4
\
\
1
—
—
Single floor span rating'^
16 o.c.
20 o.c.
24 o.c.
32 o.c.
48 o.c.
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m^.
a. Spans limited to value shown because of possible effects of concentrated loads. Allowable uniform loads based on deflection of Vg^Q of span is 100 pounds per
square foot except allowable total uniform load for 1 Vg-inch wood structural panels over joists spaced 48 inches on center is 65 pounds per square foot. Panel edges
shall have approved tongue-and-groove joints or shall be supported with blocking, unless 74-inch minimum thickness underlaymentor 1 V2 inches of approved cel-
lular or lightweight concrete is placed over the subfloor, or finish floor is ^-inch wood strip.
b. Floor panels conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
c. Applicable to all grades of sanded exterior-type plywood. See DOC PS 1 for plywood species groups.
d. Applicable to Underlayment grade, C-C (Plugged) plywood, and Single Floor grade wood structural panels.
TABLE 2304.7(5)
ALLOWABLE LOAD (PSF) FOR WOOD STRUCTURAL PANEL ROOF SHEATHING CONTINUOUS OVER
TWO OR MORE SPANS AND STRENGTH AXIS PARALLEL TO SUPPORTS
(Plywood Structural Panels Are Five-Ply, Five-Layer Unless Otherwise Noted)^' "
PANEL GRADE
THICKNESS (inch)
MAXIMUM SPAN (inches)
LOAD AT MAXIMUM SPAN (psf)
Live
Total
'/,6
24
20
30
'V32
24
35c
45c
Structural I sheathing
%
24
40^
50^
'%2,%
24
70
80
'%2,%
24
90
100
'/16
16
40
50
%2
24
20
25
Sheathing, other grades
covered in DOC PS 1 or
DOC PS 2
'%2
24
24
25
40^
30
50<^
%
24
45^=
55^
"/32,V4
24
60^^
65^
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m^.
a. Roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
b. Uniform load deflection limitations Vjgo of span under live load plus dead load, V240 under live load only. Edges shall be blocked with lumber or other approved type
of edge supports.
c. For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds per square foot.
2010 CALIFORNIA BUILDING CODE
347
WOOD
2304.8.2.1 Simple span pattern. All pieces shall be sup-
ported on their ends (i.e., by two supports).
2304.8.2.2 Two-span continuous pattern. All pieces
shall be supported by three supports, and all end joints
shall occur in line on alternating supports. Supporting
members shall be designed to accommodate the load
redistribution caused by this pattern.
2304.8.2.3 Combination simple and two-span contin-
uous pattern. Courses in end spans shall be alternating
simple- span pattern and two- span continuous pattern.
End joints shall be staggered in adjacent courses and
shall bear on supports.
2304.8.2.4 Cantilevered pieces intermixed pattern.
The decking shall extend across a minimum of three
spans. Pieces in each starter course and every third
course shall be simple span pattern. Pieces in other
courses shall be cantilevered over the supports with end
joints at alternating quarter or third points of the spans.
Each piece shall bear on at least one support.
2304.8.2.5 Controlled random pattern. The decking
shall extend across a minimum of three spans. End joints
of pieces within 6 inches (152 mm) of the end joints of
the adjacent pieces in either direction shall be separated
by at least two intervening courses. In the end bays, each
piece shall bear on at least one support. Where an end
joint occurs in an end bay, the next piece in the same
course shall continue over the first inner support for at
least 24 inches (610 mm). The details of the controlled
random pattern shall be as specified for each decking
material in Section 2304.8.3.3, 2304.8.4.3 or 2304.8.5.3.
Decking that cantilevers beyond a support for a hori-
zontal distance greater than 18 inches (457 mm), 24
inches (610 mm) or 36 inches (914 mm) for 2-inch (51
mm), 3-inch (76 mm) and 4-inch (102 mm) nominal
thickness decking, respectively, shall comply with the
following:
1 . The maximum cantilevered length shall be 30 per-
cent of the length of the first adjacent interior span.
2. A structural fascia shall be fastened to each deck-
ing piece to maintain a continuous, straight line.
3. There shall be no end joints in the decking between
the cantilevered end of the decking and the center-
line of the first adjacent interior span.
2304.8.3 Mechanically laminated decking.
2304.8.3.1 General. Mechanically laminated decking con-
sists of square-edged dimension lumber laminations set on
edge and nailed to the adjacent pieces and to the supports.
2304.8.3.2 Nailing. The length of nails connecting lami-
nations shall not be less than two and one-half times the
net thickness of each lamination. Where decking sup-
ports are 48 inches (1219 mm) on center (o.c.) or less,
side nails shall be installed not more than 30 inches (762
mm) o.c. alternating between top and bottom edges, and
staggered one-third of the spacing in adjacent lamina-
tions. Where supports are spaced more than 48 inches
(1219 mm) o.c, side nails shall be installed not more
than 18 inches (457 mm) o.c. alternating between top and
bottom edges and staggered one-third of the spacing in
adjacent laminations. Two side nails shall be installed at
each end of butt-jointed pieces.
Laminations shall be toenailed to supports with 20d or
larger common nails. Where the supports are 48 inches
(1219 mm) o.c. or less, alternate laminations shall be
toenailed to alternate supports; where supports are
spaced more than 48 inches (1219 mm) o.c, alternate
laminations shall be toenailed to every support.
2304.8.3.3 Controlled random pattern. There shall be
a minimum distance of 24 inches (610 mm) between end
joints in adjacent courses. The pieces in the first and sec-
ond courses shall bear on at least two supports with end
joints in these two courses occurring on alternate sup-
ports. A maximum of seven intervening courses shall be
permitted before this pattern is repeated.
2304.8.4 Two-inch sawn tongue-and-groove decking.
2304.8.4.1 General. Two-inch (51 mm) decking shall
have a maximum moisture content of 15 percent. Decking
shall be machined with a single tongue-and-groove pat-
tern. Each decking piece shall be nailed to each support.
2304.8.4.2 Nailing. Each piece of decking shall be
toenailed at each support with one 16d common nail
through the tongue and face-nailed with one 16d common
nail.
2304.8.4.3 Controlled random pattern. There shall be
a minimum distance of 24 inches (610 mm) between end
joints in adjacent courses. The pieces in the first and sec-
ond courses shall bear on at least two supports with end
joints in these two courses occurring on alternate sup-
ports. A maximum of seven intervening courses shall be
permitted before this pattern is repeated.
2304.8.5 Three- and 4-incli sawn tongue-and-groove
decking.
2304.8.5.1 General. Three-inch (76 mm) and 4-inch
(102 mm) decking shall have a maximum moisture con-
tent of 19 percent. Decking shall be machined with a
double tongue-and-groove pattern. Decking pieces shall
be interconnected and nailed to the supports.
2304.8.5.2 Nailing. Each piece shall be toenailed at each
support with one 40d common nail and face-nailed with
one 60d common nail. Courses shall be spiked to each
other with 8-inch (203 mm) spikes at maximum intervals
of 30 inches (762 mm) through predrilled edge holes pen-
etrating to a depth of approximately 4 inches (102 mm).
One spike shall be installed at a distance not exceeding 10
inches (254 mm) from the end of each piece.
2304.8.5.3 Controlled random pattern. There shall be
a minimum distance of 48 inches (1219 mm) between
end joints in adjacent courses. Pieces not bearing on a
support are permitted to be located in interior bays pro-
vided the adjacent pieces in the same course continue
over the support for at least 24 inches (610 mm). This
condition shall not occur more than once in every six
courses in each interior bay.
348
2010 CALIFORNIA BUILDING CODE
WOOD
2304.9 Connections and fasteners.
2304.9.1 Fastener requirements. Connections for wood
members shall be designed in accordance with the appropri-
ate methodology in Section 2301.2, The number and size of
fasteners connecting wood members shall not be less than
that set forth in Table 2304.9.1.
2304,9,1.1 Additional requirements. [DSA-SS and
OSHPD 1, 2 & 4] Fasteners used for the attachment of
exterior wall coverings shall be of hot-dipped zinc-
coated galvanized steel, mechanically deposited
zinc-coated steel, stainless steel, silicon bronze or cop-
per The coating weights for hot-dipped zinc-coated fas-
teners shall be in accordance with ASTM A 153, The
coating weights for mechanically deposited zinc-coated
fasteners shall be in accordance with ASTM B 695, Class
55 minimum.
2304.9.2 Sheathing fasteners. Sheathing nails or other
approved sheathing connectors shall be driven so that their
head or crown is flush with the surface of the sheathing.
2304.9.3 Joist hangers and framing anchors. Connec-
tions depending on joist hangers or framing anchors, ties
and other mechanical fastenings not otherwise covered are
permitted where approved. The vertical load-bearing capac-
ity, torsional moment capacity and deflection characteris-
tics of joist hangers shall be determined in accordance with
Section 1716.1.
2304.9.4 Other fasteners. Clips, staples, glues and other
approved methods of fastening are permitted where
approved.
2304.9.5 Fasteners and connectors in contact with pre-
servative-treated and fire-retardant-treated wood. Fas-
teners and connectors in contact with preservative-treated
Siud fire-retardant-treated wood shall be in accordance with
Sections 2304.9.5.1 through 2304.9.5.4. The coating
weights for zinc-coated fasteners shall be in accordance
with ASTM A 153.
2304.9.5.1 Fasteners and connectors for preserva-
tive-treated wood. Fasteners in contact with preserva-
tive-treated wood shall be of hot-dipped zinc-coated
galvanized steel, stainless steel, silicon bronze or copper.
Fasteners other than nails, timber rivets, wood screws
and lag screws shall be permitted to be of mechanically
deposited zinc-coated steel with coating weights in
accordance with ASTM B 695, Class 55 minimum. Con-
nectors that are used in exterior applications and in con-
tact with preservative-treated wood shall have coating
types and weights in accordance with the treated wood or
connector manufacturer's recommendations. In the
absence of manufacturer's recommendations, a mini-
mum of ASTM A 653, type G185 zinc-coated galva-
nized steel, or equivalent, shall be used.
Exception: Plain carbon steel fasteners in SBX/DOT
and zinc borate preservative-treated wood in an inte-
rior, dry environment shall be permitted.
2304.9.5.2 Fastenings for wood foundations. Fasten-
ings for wood foundations shall be as required in AF&PA
PWF.
2304.9.5.3 Fasteners for fire-retardant-treated wood
used in exterior applications or wet or damp loca-
tions. Fasteners for fire-retardant-treated wood used in
exterior applications or wet or damp locations shall be of
hot-dipped zinc-coated galvanized steel, stainless steel,
silicon bronze or copper. Fasteners other than nails, tim-
ber rivets, wood screws and lag screws shall be permitted
to be of mechanically deposited zinc-coated steel with
coating weights in accordance with ASTM B 695, Class
55 minimum.
2304.9.5.4 Fasteners for fire-retardant-treated wood
used in interior applications. Fasteners for fire-retar-
dant-treated wood used in interior locations shall be in
accordance with the manufacturer's recommendations.
In the absence of manufacturer's recommendations, Sec-
tion 2304.9.5.3 shall apply.
2304.9.6 Load path. Where wall framing members are not
continuous from foundation sill to roof, the members shall
be secured to ensure a continuous load path. Where
required, sheet metal clamps, ties or clips shall be formed
of galvanized steel or other approved corrosion-resistant
material not less than 0.040 inch (1.01 mm) nominal thick-
ness.
2304.9.7 Framing requirements. Wood columns and posts
shall be framed to provide full end bearing. Alternatively,
column-and-post end connections shall be designed to resist
the full compressive loads, neglecting end-bearing capacity.
Column-and-post end connections shall be fastened to resist
lateral and net induced uplift forces.
2304.10 Heavy timber construction.
2304.10.1 Columns. Columns shall be continuous or super-
imposed throughout all stories by means of reinforced con-
crete or metal caps with brackets, or shall be connected by
properly designed steel or iron caps, with pintles and base
plates, or by timber splice plates affixed to the columns by
metal connectors housed within the contact faces, or by
other approved methods.
2304.10.1.1 Column connections. Girders and beams
shall be closely fitted around columns and adjoining
ends shall be cross tied to each other, or intertied by caps
or ties, to transfer horizontal loads across joints. Wood
bolsters shall not be placed on tops of columns unless the
columns support roof loads only.
2304.10.2 Floor framing. Approved wall plate boxes or
hangers shall be provided where wood beams, girders or
trusses rest on masonry or concrete walls. Where intermedi-
ate beams are used to support a floor, they shall rest on top of
girders, or shall be supported by ledgers or blocks securely
fastened to the sides of the girders, or they shall be sup-
ported by an approved metal hanger into which the ends of
the beams shall be closely fitted.
2010 CALIFORNIA BUILDING CODE
349
WOOD
TABLE 2304.9.1
FASTENING SCHEDULE
CONNECTION
FASTENING^'"
LOCATION
1. Joist to sill or girder
3 - 8d common (2V2" x 0.131")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
2. Bridging to joist
2 - 8d common (2V2" x 0.131")
2 - 3" X 0.131" nails
2 - 3" 14 gage staples
toenail each end
3. 1" X 6" subfloor or less to each joist
2 - 8d common (2V2" x 0.131")
face nail
4. Wider than 1" x 6" subfloor to each joist
3 - 8d common (2V2" x 0.131")
face nail
5 . T subfloor to joist or girder
2 - 16d common (3V2" x 0.162")
blind and face nail
6. Sole plate to joist or blocking
Sole plate to joist or blocking at braced
wall panel
16d(3V2"x0.135")atl6"o.c.
3" x 0.131" nails at 8" o.c.
3" 14 gage staples at 12" o.c.
3-16d(3V2"x0.135")atl6"o.c.
4 - 3" X 0.131" nails at 16" o.c.
4 - 3" 14 gage staples at 16" o.c.
typical face nail
braced wall panels
7. Top plate to stud
2 - 16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
end nail
8. Stud to sole plate
4 - 8d common (2V2" x 0.131")
4 - 3" X 0.131" nails
3 - 3" 14 gage staples
2 - 16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
end nail
9. Double studs
16d(3V2"x0.135")at24"o.c.
3" X 0.131" nail at 8" o.c.
3" 14 gage staple at 8" o.c.
face nail
10. Double top plates
Double top plates
16d(3V2"x0.135")atl6"o.c.
3" X 0.131" nail at 12" o.c.
3" 14 gage staple at 12" o.c.
8 - 16d common (3V2" x 0.162")
12- 3" X 0.131" nails
12 - 3" 14 gage staples
typical face nail
lap splice
1 1 . Blocking between joists or rafters to top plate
3 - 8d common (2 V2" x 0.131")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
1 2 . Rim j oist to top plate
8d(2V2"x0.131")at6"o.c.
3" X 0.131" nail at 6" o.c.
3" 14 gage staple at 6" o.c.
toenail
13. Top plates, laps and intersections
2 - 16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
face nail
14. Continuous header, two pieces
16d common (3 Vj" x 0.162")
16" o.c. along edge
15. Ceiling joists to plate
3 - 8d common (2 Vj" x 0. 13 1")
5 - 3" X 0.131" nails
5 - 3" 14 gage staples
toenail
16. Continuous header to stud
4 -8d common (2V2"x 0.131")
toenail
{continued)
350
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2304.9.1— continued
FASTENING SCHEDULE
CONNECTION
FASTENING^'"
LOCATION
17. Ceiling joists, laps over partitions
(see Section 2308.10.4.1, Table 2308.10.4.1)
3 - 16d conmion (3 Vj" x 0.162") minimum,
Table 2308.10.4.1
4- 3" X 0.131" nails
4 - 3" 14 gage staples
face nail
18. Ceiling joists to parallel rafters
(see Section 2308.10.4.1, Table 2308.10.4.1)
3 - 16d common &l{ x 0.162") minimum,
Table 2308.10.4.1
4 - 3" x 0.131" nails
4 - 3" 14 gage staples
face nail
19. Rafter to plate
(see Section 2308.10.1, Table 2308.10.1)
3 -8d common (27/ X 0.131")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
20. 1" diagonal brace to each stud and plate
2 - 8d common 01 {' x 0.131")
2 - 3" X 0.131" nails
3 - 3" 14 gage staples
face nail
21. 1" X 8" sheathing to each bearing
3 -8d common (2V2"x 0.131")
face nail
22. Wider than 1" x 8" sheathing to each bearing
3-8dcommon(2V2"x0.131")
face nail
23. Built-up comer studs
16d common (3V2" x 0.162")
3" X 0.131" nails
3" 14 gage staples
24" o.c.
16" o.c.
16" o.c.
24. Built-up girder and beams
20d common (4" x 0. 192") 32" o.c.
3" X 0.131" nail at 24" o.c.
3" 14 gage staple at 24" o.c.
2 - 20d common (4" x 0.192")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
face nail at top and bottom staggered
on opposite sides
face nail at ends and at each splice
25. 2" planks
16d common (3V2"x 0.162")
at each bearing
26. Collar tie to rafter
3 - lOd common (3" X 0.148")
4 - 3" X 0.131" nails
4 - 3" 14 gage staples
face nail
27. Jack rafter to hip
3 - lOd common (3" x 0.148")
4 - 3" X 0.131" nails
4 - 3" 14 gage staples
2 - 16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
face nail
28. Roof rafter to 2-by ridge beam
2 - 16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
2 -16d common (3V2" x 0.162")
3 - 3" X 0.131" nails
3 - 3" 14 gage staples
toenail
face nail
29. Joist to band joist
3 - 16d common (3V2" x 0.162")
4 - 3" X 0.131" nails
4 - 3" 14 gage staples
face nail
(continued)
2010 CALIFORNIA BUILDING CODE
351
WOOD
TABLE 2304.9.1— continued
FASTENING SCHEDULE
CONNECTION
FASTENING^'"
LOCATION
30. Ledger strip
3 - 16d common (3V2" x 0.162")
4 - 3" X 0.131" nails
4 - 3" 14 gage staples
face nail at each joist
3 1 . Wood structural panels and particleboard''
Subfloor, roof and wall sheathing (to framing)
Single floor (combination subfloor-underlayment
to framing)
V2" and less
^V32"toV
Vtol"
iVg'tolV
^/4" and less
Vtol"
iV/'tolV/
6d^''
2 VxO-113"nair
IV 16 gage°
8d^or6d^
2Vx0.113"nailP
2"16gageP
Sd'^
lOd^ or 8d^
6d^
8d^
lOd^ or 8d^
32. Panel siding (to framing)
V2" or less
6df
8df
33. Fiberboard sheathing^
'%2
No. 1 1 gage roofing nail^
6d common nail (2" x 0.1 13")
No. 16 gage staple'
No. 1 1 gage roofing nail^
8d common nail (2V2" x 0.131'0
No. 16 gage staple'
34. Interior paneling
4dJ
6d'^
For SI: 1 inch = 25.4 mm.
a. Common or box nails are permitted to be used except where otherwise stated.
b. Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports except 6 inches at supports where spans are 48 inches or more. For naihng of wood
structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
c. Common or deformed shank (6d - T x 0.1 13"; 8d - l^l^' x 0. 131"; lOd - T x 0.148").
d. Common (6d - T x 0.1 13"; 8d - 27/ x 0.131"; lOd - 3" x 0.148").
e. Deformed shank (6d - 2" x 0. 1 13"; 8d - 27/' x 0. 1 31"; lOd - 3" x 0. 148").
f. Corrosion-resistant siding (6d - 1 V x 0.106"; 8d - 2V x 0.128") or casing (6d - 2" x 0.099"; 8d - 272" ^ 0.113") nail.
g. Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate supports, when used as structural sheathing. Spacing shall be 6 inches
on center on the edges and 12 inches on center at intermediate supports for nonstructural applications.
h. Corrosion-resistant roofing nails with ''/jg-inch-diameter head and 1 72-inch length for 72-inch sheathing and lV4-inch length for ^V32-inch sheathing.
i. Corrosion-resistant staples with nominal Vi^-inch crown or 1-inch crown and 1 74-inch length for 72-inch sheathing and 1 72-inch length for ^/32-inch sheathing.
Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).
j. Casing (l72" x 0.080") or finish (I72" x 0.072") nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
k. Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
1. For roof sheathing applications, 8d nails (272" ^ 0.1 13") are the minimum required for wood structural panels.
m. Staples shall have a minimum crown width of Vi^ inch.
n. For roof sheathing applications, festeners spaced 4 inches on center at edges, 8 inches at intermediate supports.
o. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor and wall sheathing and 3 inches on center at edges, 6 inches at interme-
diate supports for roof sheathing.
p. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.
352
2010 CALIFORNIA BUILDING CODE
WOOD
2304.10.3 Roof framing. Every roof girder and at least
every alternate roof beam shall be anchored to its supporting
member; and every monitor and every sawtooth construc-
tion shall be anchored to the main roof construction. Such
anchors shall consist of steel or iron bolts of sufficient
strength to resist vertical uplift of the roof.
2304.10.4 Floor decks. Floor decks and covering shall not
extend closer than V2 inch (12.7 mm) to walls. Such 72-inch
(12,7 mm) spaces shall be covered by a molding fastened to
the wall either above or below the floor and arranged such
that the molding will not obstruct the expansion or contrac-
tion movements of the floor. Corbeling of masonry walls
under floors is permitted in place of such molding.
2304.10.5 Roof decks. Where supported by a wall, roof
decks shall be anchored to walls to resist uplift forces deter-
mined in accordance with Chapter 16. Such anchors shall
consist of steel or iron bolts of sufficient strength to resist
vertical uplift of the roof.
2304.11 Protection against decay and termites.
2304.11.1 General. Where required by this section, protec-
tion from decay and termites shall be provided by the use of
naturally durable or preservative-treated wood.
2304.11.2 Wood used above ground. Wood used above
ground in the locations specified in Sections 2304.11.2.1
through 2304. 1 1 .2.7, 2304. 1 1 .3 and 2304. 1 1.5 shall be nat-
urally durable wood or preservative -treated wood using
water-borne preservatives, in accordance with AWPA Ul
(Commodity Specifications A or F) for above-ground use.
2304.11.2.1 Joists, girders and subfloor. Where wood
joists or the bottom of a wood structural floor without
joists are closer than 18 inches (457 mm), or wood girders
are closer than 12 inches (305 mm) to the exposed ground
in crawl spaces or unexcavated areas located within the
perimeter of the building foundation, the floor construc-
tion (including posts, girders, joists and subfloor) shall be
of naturally durable or preservative-treated wood.
2304,11,2,1,1 [SPCB] There shall be a clearance of
at least 18 inches (457 mm) between the underside of
wood floor joists and the finished surface of the
ground, and at least 12 inches (305 mm) between the
underside of any other wood horizontal framing
member and the finished surface of the ground. The
ground underneath floor joists shall be leveled or
smoothed off so as to maintain a reasonably even sur-
face.
Exception: For purposes of structural pest control
inspection, a minimum of 12 inches (305 mm) of
clearance under-floor joists shall be considered
adequate except that such clearance shall not be
necessary where the subarea soil is of such a
nature as to prevent excavation or where excava-
tion would create a hazard from shifting soil or
other causes,
2304.11.2.2 Wood supported by exterior foundation
walls. Wood framing members, including wood sheath-
ing, that rest on exterior foundation walls and are less
than 8 inches (203 mm) from exposed earth shall be of
naturally durable or preservative-treated wood.
Exception: [DSA-SS and OSHPD 1,2&4] At exte-
rior walls where the earth is paved with an asphalt or
concrete slab at least 18 inches (457 mm) wide and
draining away from the building, the bottom of sills
are permitted to be 6 inches (152 mm) above the top of
such slab. Other equivalent means of termite and
decay protection may be accepted by the enforcement
agency,
2304.11.2.3 Exterior walls below grade. Wood fram-
ing members and furring strips attached directly to the
interior of exterior masonry or concrete walls below
grade shall be of approved naturally durable ox preserva-
tive-treated wood.
2304.11.2.4 Sleepers and sUls. Sleepers and sills on a
concrete or masonry slab that is in direct contact with earth
shall be of naturally durable or preservative-treatedwood,
2304,11,2,4.1 Additional requirements, [DSA-SS
and OSHPD 1, 2 Sl 41 Stud walls or partitions at
shower or toilet rooms with more than two fixtures,
and stud walls adjacent to unroofed paved areas shall
rest on a concrete curb extending at least 6 inches
(152 mm) above finished floor or pavement level
2304.11.2.5 Girder ends. The ends of wood girders
entering exterior masonry or concrete walls shall be pro-
vided with a V2-inch (12.7 mm) air space on top, sides
and end, unless naturally durable or preservative-treated
wood is used,
2304.11.2.6 Wood siding. Clearance between wood sid-
ing and earth on the exterior of a building shall not be less
than 6 inches (152 mm) or less than 2 inches (51 mm)
vertical from concrete steps, porch slabs, patio slabs and
similar horizontal surfaces exposed to the weather except
where siding, sheathing and wall framing are of naturally
durable or preservative-treated wood.
2304.11.2.7 Posts or columns. Posts or columns sup-
porting permanent structures and supported by a con-
crete or masonry slab or footing that is in direct contact
with the earth shall be of naturally durable or preserva-
tive-treated wood.
Exceptions:
1. Posts or columns that are either exposed to the
weather or located in basements or cellars, sup-
ported by concrete piers or metal pedestals pro-
jected at least 1 inch (25 mm) above the slab or
deck and 6 inches (152 mm) above exposed
earth, and are separated therefrom by an imper-
vious moisture barrier.
2. Posts or colunins in enclosed crawl spaces or
unexcavated areas located within the periphery of
the building, supported by a concrete pier or metal
pedestal at a height greater than 8 inches (203
nrni) from exposed ground, and are separated
therefrom by an impervious moisture barrier.
2010 CALIFORNIA BUILDING CODE
353
WOOD
2304,11,2.8 Separate wood framing, [SPCB] Correct
the conditions in frame and stucco walls and similar
appurtenant construction so that the wood framing is
separate from the main structure by a complete concrete
or masonry plug with no voids that will allow infesta-
tions to enter the structure from the wall If there is no
plug, the foundation shall be 2 inches (51 mm) or more
above the grade levels and at least as high as the adjoin-
ing slabs or 4-inch (102 mm) concrete barrier seat off
installed.
2304.11.3 Laminated timbers. The portions of glued-lam-
inated timbers that form the structural supports of a building
or other structure and are exposed to weather and not fully
protected from moisture by a roof, eave or similar covering
shall be pressure treated with preservative or be manufac-
tured from naturally durable or preservative-treated wood.
2304.11.4 Wood in contact with the ground or fresh water.
Wood used in contact with the ground (exposed earth) in the
locations specified in Sections 2304.11.4.1 and 2304.11.4.2
shaU be naturally durable (species for both decay and termite
resistance) or preservative treated using water-borne preser-
vatives in accordance with AWPA Ul (Commodity Specifi-
cations A or F) for soil or fresh water use.
Exception: Untreated wood is permitted where such
wood is continuously and entirely below the ground-
water level or submerged in fresh water,
2304.11.4.1 Posts or columns. Posts and columns sup-
porting permanent structures that are embedded in con-
crete that is in direct contact with the earth, embedded in
concrete that is exposed to the weather or in direct con-
tact with the earth shall be of preservative-treated wood.
2304.11.4.2 Wood structural members. Wood struc-
tural members that support moisture-permeable floors or
roofs that are exposed to the weather, such as concrete or
masonry slabs, shall be of naturally durable or preserva-
tive-treated wood unless separated from such floors or
roofs by an impervious moisture barrier.
2304.11.5 Supporting member for permanent appurte-
nances. Naturally durable or preservative-treated wood
shall be utilized for those portions of wood members that
form the structural supports of buildings, balconies, porches
or similar permanent building appurtenances where such
members are exposed to the weather without adequate pro-
tection from a roof, eave, overhang or other covering to pre-
vent moisture or water accumulation on the surface or at
joints between members.
Exception: When a building is located in a geographical
region where experience has demonstrated that climatic
conditions preclude the need to use durable materials
where the structure is exposed to the weather.
2304.11.6 Termite protection. In geographical areas
where hazard of termite damage is known to be very heavy,
wood floor framing shall be of naturally durable species
(termite resistant) or preservative treated in accordance with
AWPA Ul for the species, product preservative and end use
or provided with approved methods of termite protection.
2304.11.7 Wood used in retaining walls and cribs. Wood
installed in retaining or crib walls shall be preservative
treated in accordance with AWPA Ul (Commodity Specifi-
cations A or F) for soil and fresh water use.
2304.11.8 Attic ventilation. For attic ventilation, see Sec-
tion 1203.2.
2304.11.9 Under-floor ventilation (crawl space). For
under- floor ventilation (crawl space), see Section 1203.3.
2304.11.10 Earth fills, [SPCB] Separate the earth fills such
as under porches or paving from all woodwork by concrete,
masonry, good quality cement plaster or other material
approved by local building codes. Chemical treatment of
earth fills is considered adequate if the foundation adjoin-
ing the fill meets standards of the current building codes.
2304.12 Long-term loading. Wood members supporting con-
crete, masonry or similar materials shall be checked for the
effects of long-term loading using the provisions of the
AF&PA NDS. The total deflection, including the effects of
long-term loading, shall be limited in accordance with Section
1604.3.1 for these supported materials.
Exception: Horizontal wood members supporting masonry
or concrete nonstructural floor or roof surfacing not more
than 4 inches (102 mm) thick need not be checked for long-
term loading.
SECTION 2305
GENERAL DESIGN REQUIREMENTS FOR
LATERAL-FORCE-RESISTING SYSTEMS
2305.1 General. Structures using wood shear walls and dia-
phragms to resist wind, seismic and other lateral loads shall
be designed and constructed in accordance with AF&PA
SDPWS and the provisions of Sections 2305, 2306 and
2307.
2305.1.1 Openings in shear panels. Openings in shear
panels that materially affect their strength shall be detailed
on the plans, and shall have their edges adequately rein-
forced to transfer all shearing stresses.
2305.1.2 Additional requirements, [DSA-SS, DSA-SS/
CC and OSHPD 1, 2 &4] The following limitations shall
apply:
1. Straight-sheathed horizontal lumber diaphragms are
not permitted.
2. Gypsum-based sheathing shear walls and portland
cement plaster shear walls are not permitted.
3. Shear wall foundation anchor bolt washers shall be
provided in accordance with AF&PA SDPWS Section
4.3.6.4.3. The exception to AF&PA SDPWS Section
4.3.6.4.3 shall not apply.
4. Wood structural panel shear walls and diaphragms
using staples as fasteners are not permitted.
5. Unblocked shear walls are not permitted.
2305.1.3 Diaphragms and shear walls, [DSA-SS,
DSA-SS/CC and OSHPD 1, 2 & 4 ] Any wood structural
panel sheathing used for diaphragms and shear walls that
b
354
2010 CALIFORNIA BUILDING CODE
WOOD
are part of the seismic force-resisting system shall be
applied directly to framing members.
Exception: Wood structural panel sheathing in a dia-
phragm is permitted to be fastened over solid lumber
planking or laminated decking, provided the panel joints
and lumber planking or laminated decking joints do not
coincide.
2305, 1.4 Sill plate anchor bolts. [BSQ DSA-SS, DSA-SS/
CC and OSHPD 1, 2, 3 & 4] As specified in Section
1908 J. 31 modifications to ACI 318, the allowable lateral
design strength for sill plate anchor bolts in shear parallel
to grain is permitted to be determined using the lateral
design value for a bolt attaching a wood sill plate to con-
crete, as specified in AF&PA NDS Table HE, provided the
anchor bolts comply with all of the following:
1. The maximum anchor bolt diameter is V^ inches (16
mm).
2. The anchor bolt is embedded at least 7 inches (1 78
mm) into concrete.
3. The anchor bolt is located a minimum of 2^/2 anchor
diameters from any concrete edge that is parallel to
the sill plate; and
4. The anchor bolt is located a minimum of 15 anchor
diameters from any concrete end that is perpendicu-
lar to the sill plate.
2305.2 Diaphragm deflection. The deflection (A) of a
blocked wood structural panel diaphragm uniformly fastened
throughout with staples is permitted to be calculated by using
the following equation. If not uniformly fastened, the con-
stant 0.1 88 (For SI: 1/1627) in the third term shall be modified
accordingly.
SvU
vL
- + — ^ + 0.188i>„
%EAb 4Gt
2(A,X)
2b
(Equation 23-1)
^ ^^ ^ 0.052 vL' vL Le^ 2(A,X)
For SI: A = + + — - + — ^^
EAb AGt 1627 2b
where:
A
B
E
Gt
L
V
Area of chord cross section, in square inches (mm^).
Diaphragm width, in feet (mm).
Elastic modulus of chords, in pounds per square
inch (N/mm^).
Staple deformation, in inches (mm) [see Table
2305.2(1)].
Panel rigidity through the thickness, in pounds per
inch (N/mm) of panel width or depth [see Table
2305.2(2)].
Diaphragm length, in feet (mm).
Maximum shear due to design loads in the direction
under consideration, in pounds per linear foot (plf)
(N/mm).
The calculated deflection, in inches (mm).
2 (A^= Sum of individual chord-splice slip values on both
sides of the diaphragm, each multiplied by its dis-
tance to the nearest support.
ExcepHon: [DSA-SS, DSA-SS/CC and OSHPD 1,2& 4].
Section 2305.2 is not permitted.
TABLE 2305.2(1)
e„ VALUES (inches) FOR USE IN CALCULATING DIAPHRAGM
AND SHEAR WALL DEFLECTION DUE TO FASTENER SLIP
(Structural l)^''
LOAD PER FASTENER**
(pounds)
FASTENER DESIGNATIONS
14-Ga staple x 2 inches long
60
0.011
80
0.018
100
0.028
120
0.04
140
0.053
160
0-068
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N.
a. Increase e^ values 20 percent for plywood grades other than Structural I.
b. Load per fastener = maximum shear per foot divided by the number of fas-
teners per foot at interior panel edges.
c. Decrease e„ values 50 percent for seasoned lumber (moisture content < 19
percent).
2305.3 Shear wall deflection. The deflection (A) of a blocked
wood structural panel shear wall uniformly fastened through-
out with staples is permitted to be calculated by the use of the
following equation:
. %vh v/z -^_, , h
A = + — + 0.75/ze„ -\-d^ -
EAb Gt " " ^
(Equation 23-2)
For SI: A =
where:
vh^ vh he
3EAb Gt
407.6 b
A = Area of boundary element cross section in square inches
(mm^) (vertical member at shear wall boundary).
b = Wall width, in feet (mm).
d^ = Vertical elongation of overturning anchorage
(including fastener slip, device elongation, anchor
rod elongation, etc.) at the design shear load (v).
E = Elastic modulus of boundary element (vertical mem-
ber at shear wall boundary), in pounds per square inch
(N/mm2).
e„ = Staple deformation, in inches (mm) [see Table
2305.2(1)].
Gt = Panel rigidity through the thickness, in pounds per
inch (N/mm) of panel width or depth [see Table
2305.2(2)].
h = Wall height, in feet (mm).
V = Maximum shear due to design loads at the top of the
wall, in pounds per linear foot (N/mm).
A = The calculated deflection, in inches (mm).
Exception: [DSA-SS, DSA-SS/CC and OSHPD 1,2 &4]
Section 2305.3 is not permitted.
r\
2010 CALIFORNIA BUILDING CODE
355
WOOD
TABLE 2305.2(2)
VALUES OF Gt FOR USE IN CALCULATING DEFLECTION OF WOOD STRUCTURAL PANEL SHEAR WALLS AND DIAPHRAGMS
PANEL
TYPE
SPAN
RATING
VALUES OF Gf (lb/In. panel depth or width)
OTHER
STRUCTURAL 1
3-ply
Plywood
4.ply
Plywood
5-piy
Plywood^
OSB
3-piy
Plywood
4-ply
Plywood
5-ply
Plywood^
OSB
Sheathing
24/0
25,000
32,500
37,500
77,500
32,500
42,500
41,500
77,500
24/16
27,000
35,000
40,500
83,500
35,000
45,500
44,500
83,500
32/16
27,000
35,000
40,500
83,500
35,000
45,500
44,500
83,500
40/20
28,500
37,000
43,000
88,500
37,000
48,000
47,500
88,500
48/24
31,000
40,500
46,500
96,000
40,500
52,500
51,000
96,000
Single Floor
160.C.
27,000
35,000
40,500
83,500
35,000
45,500
44,500
83,500
20 o.c.
28,000
36,500
42,000
87,000
36,500
47,500
46,000
87,000
24 0.C.
30,000
39,000
45,000
93,000
39,000
50,500
49,500
93,000
32 0.C.
36,000
47,000
54,000
110,000
47,000
61,000
59,500
110,000
48 o.c.
50,500
65,500
76,000
155,000
65,500
85,000
83,500
155,000
OTHER
STRUCTURAL 1
Thickness
(in.)
A-A,
A-C
Marine
Another
Grades
A-A,
A-C
Marine
All other
Grades
Sanded
Plywood
%
24,000
31,000
24,000
31,000
31,000
31,000
%2
25,500
33,000
25,500
33,000
33,000
33,000
%
26,000
34,000
26,000
34,000
34,000
34,000
%2
38,000
49,500
38,000
49,500
49,500
49,500
%
38,500
50,000
38,500
50,000
50,000
50,000
%2
49,000
63,500
49,000
63,500
63,500
63,500
%
49,500
64,500
49,500
64,500
64,500
64,500
'%2
50,500
65,500
50,500
65,500
65,500
65,500
%
51,000
66,500,
51,000
66,500
66,500
66,500
\
52,500
68,500
52,500
68,500
68,500
68,500
1
73,500
95,500
73,500
95,500
95,500
95,500
iVs
75,000
97,500
75,000
97,500
97,500
97,500
For SI: 1 inch = 25.4 mm, 1 pound/inch = 0. 175 1 N/mm.
a. Applies to plywood with five or more layers; for five-ply/three-layer plywood, use values for four
ply.
356
2010 CALIFORNIA BUILDING CODE
WOOD
SECTION 2306
ALLOWABLE STRESS DESIGN
2306.1 Allowable stress design. The structural analysis and
construction of wood elements in structures using allowable
stress design shall be in accordance with the following applica-
ble standards:
American Forest & Paper Association.
NDS National Design Specification for Wood Construction
SDPWS Special Design Provisions for Wind and Seismic
American Institute of Timber Construction.
Typical Construction Details
Standard Appearance Grades for Structural
Glued Laminated Timber
Standard for Dimensions of Structural Glued
Laminated Timber
Standard Specifications for Structural Glued
Laminated Timber of Softwood Species
Standard Specifications for Structural Glued
Laminated Timber of Hardwood Species
AITC 104
AITCllO
AITC 113
AITC 117
AITC 119
ANSI/
AITC A190. 1 Structural Glued Laminated Timber
AITC 200 Inspection Manual
American Society of Agricultural Engineers.
ASAE EP 484.2 Diaphragm Design of Metal-clad, Post-
Frame Rectangular Buildings
ASAE EP 486.1 Shallow Post Foundation Design
ASAE 559 Design Requirements and Bending Properties
for Mechanically Laminated Columns
APA — The Engineered Wood Association.
Panel Design Specification
Plywood Design Specification Supplement 1 -
Design & Fabrication of Plywood Curved Panel
Plywood Design Specification Supplement 2 -
Design & Fabrication of Glued Plywood-lumber Beams
Plywood Design Specification Supplement 3 -
Design & Fabrication of Plywood Stressed-skin Panels
Plywood Design Specification Supplement 4 -
Design & Fabrication of Plywood Sandwich Panels
Plywood Design Specification Supplement 5 -
Design & Fabrication of All-plywood Beams
EWS T300 Glulam Connection Details
EWS S560 Field Notching and Drilling of Glued Lami-
nated Timber Beams
EWS S475 Glued Laminated Beam Design Tables
EWS X450 Glulam in Residential Construction
EWS X440 Product and Application Guide: Glulam
EWS R540 Builders Tips: Proper Storage and Handling of
Glulam Beams
Truss Plate Institute, Inc.
TPI 1 National Design Standard for Metal Plate Connected
Wood Truss Construction
2306.1.1 Joists and rafters. The design of rafter spans is
permitted to be in accordance with the AF&PA Span Tables
for Joists and Rafters.
2306.1.2 Plank and beam flooring. The design of plank
and beam flooring is permitted to be in accordance with the
AF&PA Wood Construction Data No. 4.
2306.1.3 Treated wood stress adjustments. The allowable
unit stresses for preservative-treated wood need no adjust-
ment for treatment, but are subject to other adjustments.
The allowable unit stresses for fire-retardant-treated
wood, including fastener values, shall be developed from an
approved method of investigation that considers the effects of
anticipated temperature and humidity to which ihe, fire-retar-
dant-treated wood will be subjected, the type of treatment
and the redrying process. Other adjustments are applicable
except that the impact load duration shall not apply.
2306.1.4 Lumber decking. The capacity of lumber decking
arranged according to the patterns described in Section
2304.8.2 shall be the lesser of the capacities determined for
flexure and deflection according to the formulas in Table
2306.1.4.
TABLE 2306.1.4
ALLOWABLE LOADS FOR LUMBER DECKING
PATTERN
ALLOWABLE AREA LOAD^' "
Flexure
Deflection
Simple span
3S4AE' d^
""' ~ 5t 12
Two-span continuous
' e 6
nSAE'd'
""' ~ I' 12
Combination simple- and
two-span continuous
" I' 6
UlAE'd'
""" " t 12
Cantilevered pieces intermixed
20F^d'
""' 31' 6
105A£;'^'
"^= l^ 12
Controlled random layup
Mechanically laminated decking
IQF^d'
"'"' 31' 6
lOOAE' d'
^^= t 12
2-inch decking
lOF^d'
'""" 31' 6
lOOA^' d'
^^- t 12
3 -inch and 4-inch decking
IQF' d'
''^= 31' 6
lieAE'd'
^^= l^ 12
For SI: 1 inch = 25.4 mm.
a. a^ = Allowable total uniform load limited by bending.
o^ = Allowable total uniform load limited by deflection.
b. d = Actual decking thickness.
/ = Span of decking.
F^ = Allowable bending stress adjusted by applicable factors.
£" = Modulus of elasticity adjusted by applicable factors.
2010 CALIFORNIA BUILDING CODE
357
WOOD
2306.2 Wood diaphragms.
2306.2.1 Wood structural panel diaphragms. Wood
structural panel diaphragms shall be designed and con-
structed in accordance with AF&PA SDPWS. Wood struc-
tural panel diaphragms are permitted to resist horizontal
forces using the allowable shear capacities set forth in Table
2306.2.1(1) or 2306.2.1(2). The allowable shear capacities
in Tables 2306.2.1(1) and 2306.2.1(2) are permitted to be
increased 40 percent for wind design.
2306.2.2 Single diagonally sheathed lumber dia-
phragms. Single diagonally sheathed lumber diaphragms
shall be designed and constructed in accordance with
AF&PA SDPWS.
2306.2.3 Double diagonally sheathed lumber dia-
phragms. Double diagonally sheathed lumber diaphragms
shall be designed and constructed in accordance with
AF&PA SDPWS.
2306.2.4 Gypsum board diaphragm ceilings. Gypsum
board diaphragm ceilings shall be in accordance with Sec-
tion 2508.5.
2306.3 Wood structural panel shear walls. Wood structural
panel shear walls shall be designed and constructed in accordance
with AF&PA SDPWS. Wood structural panel shear waUs are per-
mitted to resist horizontal forces using the allowable capacities set
forth in Table 2306.3. Allowable capacities in Table 2306.3 are
permitted to be increased 40 percent for wind design,
2306.3 J Additional requirements, [DSA-SS and DSA-SS/
CC and OSHPD 1, 2 & 3] Any wood structural panel
sheathing used for diaphragms and shear walls that are
part of the seismic force-resisting system shall be applied
directly to framing members, unless installed in accordance
with Section 2305.1.3.
2306.4 Lumber sheathed shear walls. Single and double
diagonally sheathed lumber shear walls shall be designed and
constructed in accordance with AF&PA SDPWS. Single and
double diagonally sheathed lumber walls shall not be used to
resist seismic forces in structures assigned to Seismic Design
Category E or F.
Additional Requirements: [DSA/SS, DSA/SS-CC and
OSHPD lf2&4] Single and double diagonally sheathed lum-
ber walls shall not be used to resist seismic forces in structures
assigned to Seismic Design Category D.
2306.5 Particleboard shear walls. Particleboard shear walls
shall be designed and constructed in accordance with AF&PA
SDPWS. Particleboard shear walls shall be permitted to resist
horizontal forces using the allowable shear capacities set forth
in Table 2306.5. Allowable capacities in Table 2306.5 are per-
mitted to be increased 40 percent for wind design.
Particleboard shall not be used to resist seismic forces in struc-
tures assigned to Seismic Design Category D, E or F.
2306.6 Fiberboard shear walls. Fiberboard shear walls shall
be designed and constructed in accordance with AF&PA
SDPWS. Fiberboard shear walls are permitted to resist hori-
zontal forces using the allowable shear capacities set forth in
Table 2306.6. Allowable capacities in Table 2306.6 are permit-
ted to be increased 40 percent for wind design. Fiberboard shall
not be used to resist seismic forces in structures assigned to
Seismic Design Category D, E or F.
2306.7 Shear walls sheathed with other materials. Shear
walls sheathed with portland cement plaster, gypsum lath, gyp-
sum sheathing or gypsum board shall be designed and con-
structed in accordance with AF&PA SDPWS. Shear walls
sheathed with these materials are permitted to resist horizontal
forces using the allowable shear capacities set forth in Table
2306.7. Shear walls sheathed with portland cement plaster,
gypsum lath, gypsum sheathing or gypsum board shall not be
used to resist seismic forces in structures assigned to Seismic
Design Category E or F.
Exception: [DSA/SS, DSA/SS-CC and OSHPD 1, 2 & 4]
Shear walls sheathed with portland cement plaster, gypsum
lath, gypsum sheathing or gypsum board shall not be used to
resist seismic forces in structures assigned to Seismic
Design Category D.
SECTION 2307
LOAD AND RESISTANCE FACTOR DESIGN
2307.1 Load and resistance factor design. The structural
analysis and construction of wood elements and structures
using load and resistance factor design shall be in accordance
with AF&PA NDS and AF&PA SDPWS.
2307.1.1 Wood structural panel shear walls. In Seismic
Design Category D, E or F, where shear design values
exceed 490 pounds per foot (7154 N/m), all framing mem-
bers receiving edge nailing from abutting panels shall not be
less than a single 3-inch (76 nmi) nominal member or two
2-inch (51 mm) nominal members fastened together in
accordance with AF&PA NDS to transfer the design shear
value between framing members. Wood structural panel
joint and sill plate nailing shall be staggered at all panel
edges. See Sections 4.3.6.1 and 4.3.6.4.3 of AF&PA
SDPWS for sill plate size and anchorage requirements.
SECTION 2308
CONVENTIONAL LIGHT-FRAME CONSTRUCTION
2308.1 General. The requirements of this section are intended
for conventional light-frame construction. Other methods are
permitted to be used, provided a satisfactory design is submitted
showing compliance with other provisions of this code. Interior
nonload-bearing partitions, ceilings and curtain walls of conven-
tional light-frame construction are not subject to the limitations
of this section. Alternatively, compliance with AF&PA WFCM
shall be permitted subject to the limitations therein and the limi-
tations of this code. Detached one- and two-family dwellings
and multiple single-family dwellings (townhouses) not more
than three stories above grade plane in height with a separate
means of egress and their accessory structures shall comply with
the California Residential Code.
2308.1.1 Portions exceeding limitations of conventional
construction. When portions of a building of otherwise
conventional construction exceed the limits of Section
2308.2, these portions and the supporting load path shall be
designed in accordance with accepted engineering practice
and the provisions of this code. For the purposes of this sec-
tion, the term "portions" shall mean parts of buildings con-
taining volume and area such as a room or a series of rooms.
358
2010 CALIFORNIA BUILDING CODE
ro
o
o
O
>
o
J}
z
>
w
c
o
o
o
a
m
TABLE 2306.2.1(1)
ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL DIAPHRAGMS WITH
FRAMING OF DOUGLAS FIR-LARCH, OR SOUTHERN PINE' FOR WIND OR SEISMIC LOADING^
PANEL
GRADE
COMMON NAIL
SIZE OR STAPLE^
LENGTH AND
GAGE
MINIMUM
FASTENER
PENETRATION
IN FRAMING
(inches)
MINIMUM
NOMINAL
PANEL
THICKNESS
(inch)
MINIMUM
NOMINAL
WIDTH OF
FRAMING
MEMBERS AT
ADJOINING
PANEL
EDGES AND
BOUNDARIES^
(inches)
BLOCKED DIAPHRAGMS
UNBLOCKED DIAPHRAGMS
Fastener spacing (inches) at diaphragm boundaries (all cases)
at continuous panel edges parallel to load
(Cases 3, 4), and at all panel edges (Cases 5, 6)''
Fasteners spaced 6" max. at supported edges'*
6
4
2V,'=
2C
Case1
(No unblocked edges
or continuous joints
parallel to load)
All other
configurations
(Cases 2, 3, 4, 5 and 6)
Fastener spacing (inches) at other panel edges
(Cases 1,2, 3 and 4)''
6
6
4
3
Structural I
grades
8d(2V2"x 0.131")
1%
%
2
270
360
530
600
240
180
3
300
400
600
675
265
200
lV2l6Gage
1
2
175
235
350
400
155
115
3
200
265
395
450
175
130
10dd(3"x0.148'0
IV2
'%2
2
320
425
640
730
285
215
3
360
480
720
820
320
240
lV2l6Gage
1
2
175
235
350
400
155
120
3
200
265
395
450
175
130
Sheathing, single
floor and other
grades covered in
DOC PS land
PS 2
6dM2"xO.113'0
IV.
%
2
185
250
375
420
165
125
8d(2V2"x 0.131")
1%
3
210
280
420
475
185
140
2
240
320
480
545
215
160
3
270
360
540
610
240
180
lV2l6Gage
1
2
160
210
315
360
140
105
3
180
235
355
400
160
120
8d(2V2"x0.131")
1%
'U
2
255
340
505
575
230
170
3
285
380
570
645
255
190
172 16 Gage
1
2
165
225
335
380
150
110
3
190
250
375
425
165
125
8d(2V2"x 0.131")
1%
'%2
2
270
360
530
600
240
180
3
300
400
600
675
265
200
10d^(3"x0.148")
1V2
2
290
385
575
655
255
190-
3
325
430
650
735
290
215
lV2l6Gage
1
2
160
210
315
360
140
105
3
180
235
355
405
160
120
10d^(3"x0.148")
1V2
'%2
2
320
425
640
730
285
215
3
360
480
720
820
320
240
1% 16 Gage
1
2
175
235
350
400
155
115
3
200
265
395
450
175
130
(O
continued
O
O
WOOD
TABLE 2306.2.1(1)— continued
ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL
PANEL DIAPHRAGMS WITH FRAMING OF DOUGLAS FIR-LARCH,
OR SOUTHERN PINE^ FOR WIND OR SEISMIC LOADING*^
FRAMING
LOADiiU
CASE1
I . I
SVi : i
s
DIAPHRAGM BOUNDARY
BLOCKING
IF USED
CASE 3
III niM 1
- - : - ^:fE
Ml
CASE 4
-T^
^
^-■■■■■-
CONTINUOUS PANEL JOINTS
JUUULJt
/ BLOCKING
CASE 6 /IF USED
/
^
^m
CASES
' FRAMING
^
u
CONTINUOUS PANEL JOINTS '
CONTINUOUS PANEL JOINTS '
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.
a. For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I
panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find
shear value from table above for nail size for actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [ 1 -(0.5 -
SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1.
b. Space fasteners maximum 12 inches o.c. along intermediate framing members (6 inches o,c. where supports are spaced 48 inches o.c).
c. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 2V2
inches o.c. or less.
d. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met:
(1) lOd nails having penetration into framing of more than IV2 inches and (2) panel edge nailing is specified at 3 inches o.c. or less.
e. 8d is recommended minimum for roofs due to negative pressures of high winds.
f. Staples shall have a minimum crown width of V,^ inch and shall be installed with their crowns parallel to the long dimension of the framing members.
g. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.
h. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
360
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2306.2.1 (2)
ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS
UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF
DOUGLAS FIR-LARCH OR SOUTHERN PINE« FOR WIND OR SEISMIC LOADING'^-^'^
PANEL
GRADE*^
COMMON
NAIL SIZE OR
STAPLE'
GAGE
MINIMUM
FASTENER
PENETRATION
IN FRAMING
(inches)
MINIMUM
NOMINAL
PANEL
THICKNESS
(inch)
MINIMUM
NOMINAL
WIDTH OF
FRAMING
MEMBER AT
ADJOINING
PANEL EDGES
AND
BOUNDARIES^
LINES OF
FASTENERS
BLOCKED DIAPHRAGMS
Cases 1 and 2^
Fastener Spacing Per Line at Boundaries
(inches)
4
2%
2
Fastener Spacing Per Line at Other Panel Edges
(inches)
6
4
4
3
3
2
Structural I
grades
lOd
common nails
iV,
^^/32
3
4
4
2
2
3
605
700
875
815
915
1,220
875
1,005
1,285
1,150
1,290
1,395
—
—
'%2
3
4
4
2
2
3
670
780
965
880
990
1,320
965
1,110
1,405
1,255
1,440
1,790
—
—
''1,2
3
4
4
2
2
3
730
855
1,050
955
1,070
1,430
1,050
1,210
1,525
1,365
1,565
1,800
—
_
14 gage
staples
2
'%2
3
4
2
3
600
860
600
900
860
1,160
960
1,295
1,060
1,295
1,200
1,400
%2
3
4
2
3
600
875
600
900
875
1,175
960
1,440
1,075
1,475
1,200
1,795
Sheathing single
floor and other
grades covered in
DOC PS 1 and
PS 2
lOd
common nails
1V2
'%2
3
4
4
2
2
3
525
605
765
725
815
1,085
765
875
1,130
1,010
1,105
1,195
__.
—
%2
3
4
4
2
2
3
650
755
935
860
965
1,290
935
1,080
1,365
1,225
1,370
1,485
—
—
'%2
3
4
4
2
2
3
710
825
1,020
935
1,050
1,400
1,020
1,175
1,480
1,335
1,445
1,565
—
—
14 gage
staples
2
%2
3
4
2
3
540
735
540
810
735
1,005
865
1,105
915
1,105
1,080
1,195
%2
3
4
2
3
600
865
600
900
865
1,130
960
1,430
1,065
1,370
1,200
1,485
'%2
4
3
865
900
1,130
1,490
1,430
1,545
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.
a. For framing of other species : ( 1 ) Find specific gravity for species of framing lumber in AF&PA NDS . (2) For staples, find shear value from table above for Struc-
tural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails,
find shear value from table above for nail size of actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [ 1- (0.5
- SG)], where SG = Specific gravity of the framing lumber. This adjustment factor shall not be greater than 1.
b. Fastening along intermediate framing members: Space fasteners a maximum of 1 2 inches on center, except 6 inches on center for spans greater than 32 inches.
c. Panels conforming to PS 1 or PS 2.
d. This table gives shear values for Cases 1 and 2 as shown in Table 2306.2. 1(1). The values shown are applicable to Cases 3, 4, 5 and 6 as shown in Table 2306.2. 1(1),
providing fasteners at all continuous panel edges are spaced in accordance with the boundary festener spacing.
e. The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or
adjoining panel edges shall be 2 inches.
f. Staples shall have a minimum crown width of ■'/j^ inch, and shall be installed with their crowns parallel to the long dimension of the framing members.
g. High load diaphragms shall be subject to special inspection in accordance with Section 1704.6.1.
h. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
2010 CALIFORNIA BUILDING CODE
361
WOOD
TABLE 2306.2.1(2)— continued
ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS
UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF
DOUGLAS FIR-LARCH OR SOUTHERN PINE FOR WIND OR SEISMIC LOADING
r 1/4"
2 1/2"-
1 1/4**
ML
3/8"
^
V2'
3/8"
-V
i
:£
v^'
V\NELJaiNT
■^
TABIE
5PACIN0
3" NOMINAL— TWO LINES
^
31/2'
^^/4^r
13/4"
ML
1/2*
VT
3/8"
sis;
1/2"
1/2"
"W
Ar
[ ^/-fANELJDlNT
±
■\/~?A
-^
TABLE
.<>
SPACING
4" NOMINAL— THREE LINES
li3/4'
3 1/2"
1 3/4"
1/2"
m
r/t
y2
^
3/4-
\/T
■V
'^
TABLE
^TH'AHEL JOINT
r2:
y^A
SPACING
4" NOMINAL-TWO LINES
..<L
fANELEDGE
*>to
'::S
V^
TABLE
SPACING
TYPICAL BOUNDARY FASTENING
(Shown is iwo lines staggered.)
NOTE: SPACE PANEL END AND EDGE JOINT 1/8-INCH: REDUCE SPACING BETWEEN LINES OF NAILS AS NECESSARY TO
MAINTAIN MINIMUM 3/8-INCH FASTENER EDGE MARGINS, MINIMUM SPACING BETWEEN LINES IS 3/8-INCH
362
2010 CALIFORNIA BUILDING CODE
o
O
O
Z
>
w
c
o
o
o
D
m
TABLE 2306.3
ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL SHEAR WALLS WITH
FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINE« FOR WIND OR SEISMIC LOADING'' ^'J""
PANEL GRADE
MINIMUM NOMINAL PANEL
THICKNESS (inch)
MINIMUM FASTENER
PENETRATION IN
FRAMING (inches)
PANELS APPLIED DIRECT TO FRAMING
PANELS APPLIED OVER 7/ OR V/' GYPSUM SHEATHING'"
NAIL (common or galvanized box)
or staple size*
Fastener spacing at panel edges (inches)
NAIL (common or galvanized box)
or staple size'
Fastener spacing at panel edges (inches)
6
4
3
2«
6
4
3
2^
Structural I
sheathing
%
1%
8d(2V2"x 0.131" common,
2V/ X 0.1 13" galvanized box)
230**
360^^
460^
610*^
lOd (3" X 0.148" common,
3" X 0.128" galvanized box)
280
430
550^
730
1
lV2l6Gage
155
235
315
400
2 16 Gage
155
235
310
400
\e
1%
SdClV/x 0.131" common,
2V2" X 0.1 13" galvanized box)
255^*
395'^
505^
670^
lOd (3" X 0.148" common,
3" X 0.128" galvanized box)
280
430
550^
730
1
iV^ieCage
170
260
345
440
2 16 Gage
155
235
310
400
%2
1%
8d(2V2"x 0.131" common,
2 V2" X 0. 1 1 3" galvanized box)
280
430
550
730
lOd (3" X 0.148" common,
3" X 0.1218" galvanized box)
280
430
550^
730
1
l'/2l6Gage
185
280
375
475
2 16 Gage
155
235
300
400
X%
lOd (3" X 0.148" common,
3" X 0. 128" galvanized box)
340
510
665^
870
lOd (3" X 0. 148" common,
3" X 0.128" galvanized box)
-
—
—
—
Sheathing,
plywood siding*
except Group 5
Species
^/i6^orV/
' 1%
6d (2" X 0.1 13" common,
2" X 0.099" galvanized box)
180
270
350
450
8d (2'/2" X 0.131" common,
2'/2" X 0.1 13" galvanized box)
180
270
350
450
1
lV2l6Gage
145
220
295
375
2 16 Gage
110
165
220
285
%e'
iV.
6d(2"x0.099")
140
210
275
360
8d(2V2"x 0.113")
140
210
275
360
\
1%
8d(2V2"x0.113")
160
240
310
410
10d(3"x0.128")
160
240
310^
410
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.
a. For framing of other species: ( 1 ) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by
0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table above for nail size for actual grade and multiply value by the following adjustment factor:
Specific Gravity Adjustment Factor = [l-(0.5 - SO)], where SO = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1.
b. Panel edges backed with 2-inch nominal or wider fi-aming. Install panels eitiier horizontally or vertically. Space fasteners maximum 6 inches on center along intermediate framing members for Vg-inch and ^/|g-inch panels
installed on studs spaced 24 inches on center. For other conditions and panel diickness, space fasteners maximum 12 inches on center on intermediate supports.
c. ''/g-inch panel thickness or siding with a span rating of 16 inches on center is the minimum recommended where applied directly to framing as exterior siding. For grooved panel siding, the nominal panel thickness
is the diickness of die panel measured at the point of nailing.
d. Allowable shear values are permitted to be increased to values shown for ' V32-inch sheathing with same nailing provided (a) studs are spaced a maximum of 16 inches on center, or (b) panels are apphed with long
dimension across studs.
e. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 2 inches on center or less.
f . Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met: ( 1 ) 1 Od (3" x 0. 1 48") nails having penetration into
framing of more than 1 V2 inches and (2) panel edge nailing is specified at 3 inches on center or less.
g. Values apply to all-veneer plywood. Thickness at point of fastening on panel edges governs shear values.
h. Where panels are applied on both faces of a wall and nail spacing is less than 6 inches o.c. on either side, panel joints shall be offset to fall on different framing members. Or framing shall be 3-inch nominal or thicker
at adjoining panel edges and nails at all panel edges shall be staggered,
i. In Seismic Design Category D, E or F, where shear design values exceed 350 pounds per linear foot, all framing members receiving edge nailing from abutting panels shall not be less than a single 3-inch nominal
member, or two 2-inch nominal members fastened together in accordance with Section 2306. 1 to transfer the design shear value between framing members. Wood structural panel joint and sill plate nailing shall be
staggered at all panel edges. See Sections 4.3.6.1 and 4.3.6.4.3 of AF&PA SDPWS for sill plate size and anchorage requirements,
j. Galvanized nails shall be hot dipped or tumbled.
k. Staples shall have a minimum crown width of V,^ inch and shall be installed with their crowns parallel to the long dimension of the framing members.
1. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
m. [DSA/SS, DSA/SS-CC and OSHPD 1,2 & 4] Refer to Section 2305. 1 . 3, which requires any wood structural panel sheathing used for diaphragms and shear walls that are part of the seismic force-resisting system
to be applied directly to framing members.
II
CO
O
o
o
WOOD
TABLE 2306.5
ALLOWABLE SHEAR FOR PARTICLEBOARD SHEAR WALL SHEATHING*"
PANEL GRADE
MINIMUM NOMINAL
PANEL THICKNESS
(inch)
MINIMUM NAIL
PENETRATION IN
FRAMING
(Inches)
PANELS APPLIED DIRECT TO FRAMING
Nail size (common or
galvanized box)
Allowable shear (pounds per foot) nail spacing at
panel edges (inches)^
6
4
3
2
M-S "Exterior Glue"
and M-2 "Exterior
Glue"
%
IV,
6d
120
180
230
300
\
IV,
8d
130
190
240
315
%
140
210
270
350
%
1%
lOd
185
275
360
460
\
200
305
395
520
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.
a. Values are not permitted in Seismic Design Category D, E or F.
b. Galvanized nails shall be hot-dipped or tumbled.
TABLE 2306.6
ALLOWABLE SHEAR VALUES (pif) FOR WIND OR SEISMIC LOADING ON
SHEAR WALLS OF FIBERBOARD SHEATHING BOARD CONSTRUCTION FOR TYPE V CONSTRUCTION ONLY« '^'^ ^^
THICKNESS AND
GRADE
FASTENER SIZE
ALLOWABLE SHEAR VALUE
(pounds per linear foot)
NAIL SPACING AT PANEL EDGES (inches^
4
3
2
Structural
No. 1 1 gage galvanized
roofing nail 1 Vj" long for ^^32" with Vg" head
170
230
260
No. 1 1 gage galvanized staple, Vj^" crown*^
150
200
225
No. 11 gage galvanized staple, 1" crown*"
220
290
325
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m.
a. Fiberboard sheathing shall not be used to brace concrete or masonry walls.
b. Panel edges shall be backed with 2-inch or wider framing of Douglas fir-larch or Southern pine. For framing of other species : ( 1 ) Find specific gravity for species of
framing lumber in AF&PA NDS. (2) For staples, multiply the shear value from the table above by 0. 82 for species with specific gravity of 0.42 or greater, or 0.65 for
all other species. (3) For nails, multiply the shear value from the table above by the following adjustment factor: specific gravity adjustment factor = [1 -(0.5-SG)],
where SG = Specific gravity of the framing lumber.
c. Values shown are for fiberboard sheathing on one side only with long panel dimension either parallel or perpendicular to studs.
d. Fastener shall be spaced 6 inches on center along intermediate framing members.
e. Values are not permitted in Seismic Design Category D, E or F.
f. Staple length shall not be less than IV2 inches for ^^j'i^'^l' sheathing or 1 V4 inches for V2-inch sheathing.
364
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2306.7
ALLOWABLE SHEAR FOR WIND OR SEISMIC FORCES FOR SHEAR WALLS OF LATH
AND PLASTER OR GYPSUM BOARD WOOD FRAMED WALL ASSEMBLIES
TYPE OF MATERIAL
THICKNESS
OF MATERIAL
WALL
CONSTRUCTION
FASTENER SPACING**
MAXIMUM (inches)
SHEAR VALUE^'®
(pit)
MINIMUM
FASTENER SIZE'^'^'l*^
1. Expanded metal or woven wire
lath and portland cement plaster
7/ //
Unblocked
6
180
No. 1 1 gage 1 V/ long, V,/' head
No. 16 gage galv. staple, ''//' legs
2. Gypsum lath, plain or perforated
with vertical joints staggered
^/g" lath and
V2" plaster
Unblocked
5
180
No. Bgagegalv. I'V'long, 'V
head, plasterboard nail
3. Gypsum lath, plain or perforated
^/g" lath and
V2" plaster
Unblocked
5
100
No. 16 gage galv. staple, 1 V/' long,
0.120" nail, min. V head, IV4 "
long
4. Gypsum board, gypsum veneer
base or water-resistant gypsum
backing board
•//
Unblocked^
7
75
5d cooler (l%"x 0.086") or
wallboard 0.120" nail, min. % "
head, IV/' long
No. 16 gage galv. staple, \^i{ long
Unblocked^
4
110
Unblocked
7
100
Unblocked
4
125
Blocked^
7
125
Blocked^
4
150
Unblocked
8/12^^
60
No. 6—1 V/' screws'
Blocked^
4/16*^
160
Blocked^' s
4/12^
155
Blocked^
8/12*^
70
Blocked^
6/12^
90
%"
Unblocked^
7
115
6d cooler (iVx 0-092") or
wallboard
0.120" nail, min. %" head, 1 V/ long
No. 16 gage galv. staple, Vl{ legs,
l%"long
4
145
Blocked^
7
145
4
175
Blocked^
Two-ply
Base ply: 9
Face ply: 7
250
Base ply-6d cooler (1 V x 0.092")
or wallboard iV/' x 0.120" nail, min.
Vg" head l^/g" 16 gage galv. staple
1%" 16 gage galv. staple
Face ply-8d cooler (2%" x 0.1 13")
or wallboard
0.120" nail, min. %" head, 2%" long
No. 15 gage galv. staple, 2V4" long
Unblocked
8/12*^
70
No. 6— IV/' screws'
Blocked^
8/12^
90
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per foot = 14.5939 N/m.
a. These shear walls shall not be used to resist loads imposed by masonry or concrete walls (see Section 4. 1 .5 of AF & PA SDPWS). Values shown are for short-term
loading due to wind or seismic loading. Walls resisting seismic loads shall be subject to the limitations in Section 12.2. 1 of ASCE 7. Values shown shall be reduced
25 percent for normal loading.
b. Applies to fastening at studs, top and bottom plates and blocking.
c. Alternate fasteners are permitted to be used if their dimensions are not less than the specified dimensions. Drywall screws are permitted to substitute for the 5d
(1^/g" X 0.086"). and 6d (iV/' x 0.092")(cooler) nails listed above, and No. 6 17^ inch Type S or W screws for 6d {Vi{ x 0.092) (cooler) nails.
d. For properties of cooler nails, see ASTM C 514.
e. Except as noted, shear values are based on a maximum framing spacing of 16 inches on center
f. Maximum framing spacing of 24 inches on center
g. All edges are blocked, and edge fastening is provided at all supports and all panel edges.
h. First number denotes fastener spacing at the edges; second number denotes fastener spacing at intermediate framing members,
i. Screws are Type W or S.
j. Staples shall have a minimum crown width of Vj^ inch, measured outside the legs, and shall be installed with their crowns parallel to the long dimension of the fram-
ing members,
k. Staples for the attachment of gypsum lath and woven-wire lath shall have a minimum crown width of '^i^ inch, measured outside the legs.
2010 CALIFORNIA BUILDING CODE
365
WOOD
2308.2 Limitations. Buildings are permitted to be constructed
in accordance with the provisions of conventional light-frame
construction, subject to the following limitations, and to fur-
ther limitations of Sections 2308.11 and 2308.12.
1 . Buildings shall be limited to a maximum of three stories
above grade plane. For the purposes of this section, for
buildings in Seismic Design Category D or E as deter-
mined in Section 1613, cripple stud walls shall be con-
sidered to be a story.
Exception: Solid blocked cripple walls not exceeding
14 inches (356 mm) in height need not be considered a
story.
2. Maximum floor-to-floor height shall not exceed 1 1 feet,
7 inches (3531 mm). Bearing wall height shall not
exceed a stud height of 10 feet (3048 mm).
3. Loads as determined in Chapter 16 shall not exceed the
following:
3.1. Average dead loads shall not exceed 15 psf (718
N/m^) for combined roof and ceiling, exterior
walls, floors and partitions.
Exceptions:
1. Subject to the limitations of Sections
2308.11.2 and 2308.12.2, stone or masonry
veneer up to the lesser of 5 inches (127 mm)
thick or 50 psf (2395 N/m^) and installed in
accordance with Chapter 14 is permitted to a
height of 30 feet (9144 mm) above a
noncombustible foundation, with an addi-
tional 8 feet (2438 mm) permitted for gable
ends.
2. Concrete or masonry fireplaces, heaters and
chimneys shall be permitted in accordance
with the provisions of this code.
3.2. Live loads shall not exceed 40 psf (1916 N/m^)
for floors.
3.3. Ground snow loads shall not exceed 50 psf (2395
N/m^).
4. Wind speeds shall not exceed 100 miles per hour (mph)
(44 m/s) (3 -second gust).
Exception: Wind speeds shall not exceed 110 mph
(48.4 m/s) (3 -second gust) for buildings in Exposure
Category B that are not located in a hurricane-prone
region.
5. Roof trusses and rafters shall not span more than 40 feet
(12 192 mm) between points of vertical support.
6. The use of the provisions for conventional light-frame
construction in this section shall not be permitted for
Occupancy Category IV buildings assigned to Seismic
Design Category B, C, D, E or F, as determined in Sec-
tion 1613.
7. Conventional light-frame construction is limited in
irregular structures in Seismic Design Category D or E,
as specified in Section 2308.12.6.
8. [DSA-SS, DSA'SS/CCandOSHPD2]Theuseofcon- \ \
ventional light-frame construction provisions in this sec-
tion is permitted, subject to the following conditions:
8.1. The design and construction shall also comply
with Sections 2304 and 2305.
8.2. In conjunction with the use of provisions in Sec-
tion 2308.3 (Braced Wall Lines), engineering
analysis shall be furnished that demonstrates
compliance of lateral-force -resisting systems
with Section 2305.
8.3. In addition to the use of provisions in Section
2308.8 (Floor Joists), engineering analysis shall
be furnished that demonstrates compliance of
floor framing elements and connections with
Section 2301.2, Item 1 or 2.
8.4. In addition to the use of provisions in Section
2308.9 (Wall Framing), engineering analysis
shall be furnished that demonstrates compliance
of wall framing elements and connections with
Section 2301.2, Item 1 or 2.
8.5. In addition to the use of provisions in Section
2308.10 (Roof and Ceiling Framing), engineer-
ing analysis shall be furnished demonstrating
compliance of roof and ceiling framing elements
and connections with Section 2301.2, Item 1 or 2.
2308.2.1 Basic wind speed greater than 100 mph (3-sec-
ond gust). Where the basic wind speed exceeds 100 mph
(3-second gust), the provisions of either AF&PA WFCM or
ICC 600 are permitted to be used.
2308.2.2 Buildings in Seismic Design Category B, C, D or
E. Buildings of conventional light-frame construction in
Seismic Design Category B or C, as determined in Section
1613, shall comply with the additional requirements in Sec-
tion 2308.11.
Buildings of conventional light-frame construction in
Seismic Design Category D or E, as determined in Section
1613, shall comply with the additional requirements in Sec-
tion 2308.12.
2308.3 Braced wall lines. Buildings shall be provided with
exterior and interior braced wall lines as described in Section
2308.9.3 and installed in accordance with Sections 2308.3.1
through 2308.3.4.
2308.3.1 Spacing. Spacing of braced wall lines shall not
exceed 35 feet (10 668 mm) o.c. in both the longitudinal and
transverse directions in each story.
2308.3.2 Braced wall line connections. Wind and seismic
lateral forces shall be transferred from the roofs and floors
to braced wall lines and from the braced wall lines in upper
stories to the braced wall lines in the story below in accor-
dance with is section.
366
2010 CALIFORNIA BUILDING CODE
WOOD
Braced wall line top plates shall be fastened to joists, raf-
ters or full-depth blocking above in accordance with Table
2304.9.1, Items 11, 12, 15 or 19 as applicable based on the
orientation of the joists or rafters to the braced wall line.
Braced wall line bottom plates shall be connected to j oists or
blocking below in accordance with Table 2304.9.1, Item 6,
or to foundations in accordance with Section 2308.3,3. At
exterior gable end walls, braced wall panel sheathing in the
top story shall be extended and fastened to roof framing
where the spacing between parallel exterior braced wall
lines is greater than 50 feet (15 240 mm).
Exception: Where roof trusses are used and are installed
perpendicular to an exterior braced wall line, lateral
forces shall be transferred from the roof diaphragm to the
braced wall by blocking of the ends of the trusses or by
other approved methods providing equivalent lateral
force transfer. Blocking shall be a minimum of 2 inches
(51 nrni) nominal in thickness and equal to the depth of
the truss at the wall line and shall be fastened to the
braced wall line top plate as specified in Table 2304.9.1,
Item 11.
2308.3.3 Sill anchorage. Where foundations are required
by Section 2308.3.4, braced wall line sills shall be anchored
to concrete or masonry foundations. Such anchorage shall
conform to the requirements of Section 2308.6 except that
such anchors shall be spaced at not more than 4 feet (1219
mm) o.c. for structures over two stories above grade plane.
The anchors shall be distributed along the length of the
braced wall line. Other anchorage devices having equivalent
capacity are permitted.
2308.3.3.1 Anchorage to all- wood foundations. Where
all-wood foundations are used, the force transfer from
the braced wall lines shall be determined based on calcu-
lation and shall have a capacity greater than or equal to
the connections required by Section 2308.3.3.
2308.3.4 Braced wall line support. Braced wall lines shall
be supported by continuous foundations.
Exception: For structures with a maximum plan dimen-
sion not over 50 feet (15 240 mm), continuous founda-
tions are required at exterior walls only.
2308.4 Design of elements. Combining of engineered ele-
ments or systems and conventionally specified elements or sys-
tems is permitted subject to the following limits:
2308.4.1 Elements exceeding limitations of conven-
tional constructioUo When a building of otherwise con-
ventional construction contains structural elements
exceeding the limits of Section 2308.2, these elements and
the supporting load path shall be designed in accordance
with accepted engineering practice and the provisions of
this code.
2308.4.2 Structural elements or systems not described
herein. When a building of otherwise conventional con-
struction contains structural elements or systems not
described in Section 2308, these elements or systems shall
be designed in accordance with accepted engineering
practice and the provisions of this code. The extent of such
design need only demonstrate compliance of the
nonconventional elements with other applicable provi-
sions of this code and shall be compatible with the perfor-
mance of the conventionally framed system.
2308.5 Connections and fasteners. Connections and fasten-
ers used in conventional construction shall comply with the
requirements of Section 2304.9.
2308.6 Foundation plates or sills. Foundations and footings
shall be as specified in Chapter 18. Foundation plates or sills
resting on concrete or masonry foundations shall comply with
Section 2304.3.1. Foundation plates or sills shall be bolted or
anchored to the foundation with not less than V2-inch-diameter
(12.7 mm) steel bolts or approved anchors spaced to provide
equivalent anchorage as the steel bolts. Bolts shall be embed-
ded at least 7 inches (178 mm) into concrete or masonry, and
spaced not more than 6 feet (1829 mm) apart. There shall be a
minimum of two bolts or anchor straps per piece with one bolt
or anchor strap located not more than 12 inches (305 mm) or
less than 4 inches (102 mm) from each end of each piece. A
properly sized nut and washer shall be tightened on each bolt to
the plate.
2308.7 Girders. Girders for single-story construction or gird-
ers supporting loads from a single floor shall not be less than 4
inches by 6 inches (102 mm by 152 mm) for spans 6 feet
(1829 mm) or less, provided that girders are spaced not more
than 8 feet (2438 mm) o.c. Spans for built-up 2-inch (51 mm)
girders shall be in accordance with Table 2308.9.5 or
2308.9.6. Other girders shall be designed to support the loads
specified in this code. Girder end joints shall occur over sup-
ports.
Where a girder is spliced over a support, an adequate tie shall
be provided. The ends of beams or girders supported on
masonry or concrete shall not have less than 3 inches (76 mm)
of bearing.
2308.8 Floor joists. Spans for floor joists shall be in accor-
dance with Table 2308.8(1) or 2308.8(2). For other grades and
or species, refer to the AF&PA Span Tables for Joists and Raf-
ters,
2308.8.1 Bearing. Except where supported on a 1-inch by
4-inch (25.4 mm by 102 nam) ribbon strip and nailed to the
adjoining stud, the ends of each joist shall not have less than
VI 2 inches (38 mm) of bearing on wood or metal, or less
than 3 inches (76 mm) on masonry.
2010 CALIFORNIA BUILDING CODE
367
00
O)
00
TABLE 2308.8(1)
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES
(Residential Sleeping Areas, Live Load =-30 psf, L/A = 360)
JOIST
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD = 10 DSf
DEAD LOAD = 20 Dsf
2x6 1 2x8 2x10 1 2x12
2x6 2x8 2x10 2x12
Maximum floor ioist spans
(ft. -in.)
(ft. - in.)
(ft.- in.)
(ft. - in.)
(ft. - in.)
(ft. -In.)
(ft. - in.)
(ft. - in.)
12
Douglas Fir-Larch SS
Douglas Fir-Larch #1
Douglas Fir-Larch #2
Douglas Fir-Larch #3
12-6
12-0
11-10
9-8
16-6
15-10
15-7
12-4
2i-0
20-3
19-10
15-0
25-7
24-8
23-0
17-5
12-6
12-0
11-6
8-8
16-6
15-7
14-7
11-0
21-0
19-0
17-9
13-5
25-7
22-0
20-7
15-7
Hem-Fir SS
Hem-Fir #1
Hem-Fir #2
Hem-Fir #3
11-10
11-7
11-0
9-8
15-7
15-3
14-6
12-4
19-10
19-5
18-6
15-0
24-2
23-7
22-6
17-5
11-10
11-7
11-0
8-8
15-7
15-2
14-4
11-0
19-10
18-6
17-6
13-5
24-2
21-6
20-4
15-7
Southern Pine SS
Southern Pine #1
Southern Pine #2
Southern Pine #3
12-3
12-0
11-10
10-5
16-2
15-10
15-7
13-3
20-8
20-3
19-10
15-8
25-1
24-8
24-2
18-8
12-3
12-0
n-10
9-4
16-2
15-10
15-7
11-U
20-8
20-3
18-7
14-0
25-1
24-8
21-9
16-8
Spruce-Pine-Fir SS
Spruce-Pine-Fir #1
Spruce-Pine-Fir #2
Spruce-Pine-Fir #3
11-7
11-3
11-3
9-8
15-3
14-11
14-11
12-4
19-5
19-0
19-0
15-0
23-7
23-0
23-0
17-5
11-7
11-3
11-3
8-8
15-3
14-7
14-7
11-0
19-5
17-9
17-9
13-5
23-7
20-7
20-7
15-7
16
Douglas Fir-Larch SS
Douglas Fir-Larch #1
Douglas Fir-Larch #2
Douglas Fir-Larch #3
11-4
10-11
10-9
8-5
15-0
14-5
14-1
10-8
19-1
18-5
17-2
13-0
23-3
21-4
19-11
15-1
11-4
10-8
9-11
7-6
15-0
13-6
12-7
9-6
19-1
16-5
15-5
11-8
23-0
19-1
17-10
13-6
Hem-Fir ^ SS
Hem-Fir #1
Hem-Fir #2
Hem-Fir #3
10-9
10-6
10-0
8-5
14-2
13-10
13-2
10-8
18-0
17-8
16-10
13-0
21-11
20-9
19-8
15-1
10-9
10-4
9-10
7-6
14-2
13-1
12-5
9-6
18-0
16-0
15-2
U-8
21-11
18-7
17-7
13-6
Southern Pine SS
Southern Pine #1
Southern Pine #2
Southern Pine #3
11-2
10-11
10-9
9-0
14-8
14-5
14-2
11-6
18-9
18-5
18-0
13-7
22-10
22-5
21-1
16-2
11-2
10-11
10-5
8-1
14-8
14-5
13-6
10-3
18-9
17-11
16-1
12-2
22-10
21-4
18-10
14-6
Spruce-Pine-Fir SS
Spruce-Pine-Fir #1
Spruce-Pine-Fir #2
Spruce-Pine-Fir #3
10-6
10-3
10-3
8-5
13-10
13-6
13-6
10-8
17-8
17-2
17-2
13-0
21-6
19-11
19-11
15-1
10-6
9-11
9-11
7-6
13-10
12-7
12-7
9-6
17-8
15-5
15-5
11-8
21-4
17-10
17-10
13-6
o
o
a
(continued)
o
TABLE 2308.8(1)— continued
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES
(Residential Sleeping Areas, Live Load =■ 30 psf, L/A - 360)
JOIST
SPACING
(inches)
DEAD LOAD = 10 DSf
DEAD LOAD = 20 DSf
2x6
2X8
2x10
2x12
2x6
2x8
2x10
2x12
Maximum floor Joist spans
SPECIES AND GRADE
(ft. - in.)
(ft. -in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
Douglas Fir-Larch
SS
10-8
14-1
18-0
21-10
10-8
14-1
18-0
21-0
Douglas Fir-Larch
#1
10-4
13-7
16-9
19-6
9-8
12-4
15-0
17-5
Douglas Fir-Larch
#2
10-1
12-10
15-8
18-3
9-1
11-6
14-1
16-3
Douglas Fir-Larch
#3
7-8
9-9
11-10
13-9
6-10
8-8
10-7
12-4
Hem-Fir
SS
10-1
13-4
17-0
20-8
10-1
13-4
17-0
20-7
Hem-Fir
#1
9-10
13-0
16-4
19-0
9-6
12-0
14-8
17-0
Hem-Fir
#2
9-5
12-5
15-6
17-1
8-11
11-4
13-10
16-1
19.2
Hem-Fir
#3
7-8
9-9
11-10
13-9
6-10
8-8
10-7
12-4
Southern Pine
SS
10-6
13-10
17-8
21^6
10-6
13-10
17-8
21-6 .
Southern Pine
#1
10-4
13-7
17-4
21-1
10-4
13-7
16-4
19-6
Southern Pine
#2
10-1
13-4
16-5
19-3
9-6
12-4
14-8
17-2
Southern Pine
#3
8-3
10-6
12-5
14-9
7-4
9-5
11-1
13-2
Spnice-Pine-Fir
SS
9-10
13-0
16-7
20-2
9-10
13-0
16-7
19-6
Spruce-Pine-Fir
#1
9-8
12-9
15-8
18-3
9-1
11-6
14-1
16-3
Spruce-Pine-Fir
#2
9-8
12-9
15-8
18-3
9-1
11-6
14-1
16-3
Spruce-Pine-Fir
#3
7-8
9-9
11-10
13-9
6-10
8-8
10-7
12-4
Douglas Fir-Larch
SS
9-11
13-1
16-8
20-3
9-11
13-1
16-2
18-9
Douglas Fir-Larch
#1
9-7
12-4
15-0
17-5
8-8
11-0
13-5
15-7
Douglas Fir-Larch
#2
9-1
11-6
14-1
16-3
8-1
10-3
12-7
14-7
Douglas Fir-Larch
#3
6-10
8-8
10-7
12-4
6-2
7-9
9-6
11-0
Hem-Fir
SS
9-4
12-4
15-9
■ 19-2
9-4
12-4
15-9
18-5
Hem-Fir
#1
9-2
12-0
14-8
17-0
8-6
10-9
13-1
15-2
Hem-Fir
#2
8-9
11-4
13-10
16-1
8-0
10-2
12-5
14-4
24
Hem-Fir
#3
6-10
8-8
ia7
12-4
6-2 .
7-9
9-6
11-0
Southern Pine
SS
9-9
12-10
16-5
19-11
9-9
12-10
16-5
19-11
Southern Pine
#1
9-7
12-7
16-1
19-6
9-7
12-4
14-7
17-5
Southern Pine
#2
9-4
12-4
14-8
17-2
8-6
11-0
13-1
15-5
Southern Pine
#3
7-4
9-5
11-1
13-2
6-7
8-5
9-11
11-10
Spruce-Pine-Fir
SS
9-2
12-1
15-5
18-9
9-2
12-1
15-0
17-5
Spruce-Pine-Fir
#1
8-11
11-6
14-1
16-3
8-1
10-3
12-7
14-7
Spruce-Pine-Fir
#2
8-11
11-6
14-1
16-3
8-1
10-3
12-7
14-7
Spruce-Pine-Fir
#3
6-10
8-8
10-7
12-4
6-2
7-9
9-6
11-0
CO
Oi
Check sources for availability of lumber
For SI: 1 inch = 25.4 mm, 1 foot = 304.i
in lengths greater than 20 feet.
I mm, 1 pound per square foot = 47.8 N/m\
•Nl
o
TABLE 2308.8(2)
FLOOR JOIST SPANS FOR COMMON
(Residential Living Areas, Live Load :
LUMBER SPECIES
= 40 psf , UA = 360)
JOIST
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD = 10 DSf
DEAD LOAD = 20 Dsf
2x6 2x8 1 2x10 I 2x12
2x6 1 2x8 1 2x10 1 2x12
Maximum floor ioist spans
(ft. -in.)
(ft. -in.)
(ft. -in.)
(ft. -in.)
(ft. -in.)
(ft. -in.)
(ft. -in.)
(ft. - in.)
12
Douglas Fir-Larch SS
Douglas Fir-Larch #1
Douglas Fir-Larch #2
Douglas Fir-Larch #3
11-4
10-11
10-9
8-8
15-0
14-5
14-2
11-0
19-1
18-5
17-9
13-5
23-3
22-0
20-7
15-7
11-4
10-11
10-6
7-11
15-0
14-2
13-3
10-0
19-1
17-4
16-3
12-3
23-3
20-1
18-10
14-3
Hem-Fir SS
Hem-Fir #1
Hem-Fir #2
Hem-Fir #3
10-9
10-6
10-0
8-8
14-2
13-10
13-2
1 1-0
18-0
17-8
16-10
13-5
21-11
21-6
20-4
15-7
10-9
10-6
10-0
7-11
14-2
13-10
13-1
10-0
18-0
16-11
16-0
12-3
21-11
19-7
18-6
14-3
Southern Pine SS
Southern Pine #1
Southern Pine #2
Southern Pine #3
11-2
10-11
10-9
9-4
14-8
14-5
14-2
11-11
18-9
18-5
18-0
14-0
22-10
22-5
21-9
16-8
11-2
10-11
10-9
8-6
14-8
14-5
14-2
10-10
18-9
18-5
16-11
12-10
22-10
22-5
19-10
15-3
Spnice-Pine-Fir SS
Spruce-Pine-Fir #1
Spruce-Pine-Fir #2
Spruce-Pine-Fir #3
10-6
10-3
10-3
8-8
13-10
13-6
13-6
11-0
17-8
17-3
17-3
13-5
21-6
20-7
20-7
15-7
10-6
10-3
10-3
7-11
13-10
13-3
13-3
10-0
17-8
16-3
16-3
12-3
21-6
18-10
18-10
14-3
16
Douglas Fir-Larch SS
Douglas Fir-Larch #1
Douglas Fir-Larch #2
Douglas Fir-Larch #3
10-4
9-11
9-9
7-6
13-7
13-1
12-7
9-6
17-4
16-5
15-5
11-8
21-1
19-1
17-10
13-6
10-4
9-8
9-1
6-10
13-7
12-4
11-6
8-8
17-4
15-0
14-1
10-7
21-0
17-5
16-3
12-4
Hem-Fir SS
Hem-Fir #1
Hem-Fir #2
Hem-Fir #3
9-9
9-6
9-1
7-6
12-10
12-7
12-0
9-6
16-5
16-0
15-2
11-8
19-11
18-7
17-7
13-6 ^
9-9
9-6
8-11
6-10
12-10
12-0
11-4
8-8
16-5
14-8
13-10
10-7
19-11
17-0
16-1
12-4
Southern Pine SS
Southern Pine #1
Southern Pine #2
Southern Pine #3
10-2
9-11
9-9
8-1
13-4
13-1
12-10
10-3
17-0
16-9
16-1
12-2
20-9
20-4
18-10
14-6
10-2
9-11
9-6
7-4
13-4
13-1
12-4
9-5
17-0
16-4
14-8
11-1
20-9
19-6
17-2
13-2
Spruce-Pine-Fir SS
Spruce-Pine-Fir #1
Spruce-Pine-Fir #2
Spruce-Pine-Fir #3
9-6
9-4
9-4
7-6
12-7
12-3
12-3
9-6
16-0
15-5
15-5
11-8
19-6
17-10
17-10
13-6
9-6
9-1
9-1
6-10
12-7
11-6
11-6
8-8
16-0
14-1
14-1
10-7
19-6
16-3
16-3
12-4
o
o
o
(continued)
o
O
TABLE 2308.8(2)-^ontlnued
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES
(Residential Living Areas, Live Load = 40 psf, L/A = 360)
JOIST
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD ^10 psf
DEAD LOAD = 20 psf
2x6
2x8
2x10
2x12
2x6
2x8
2x10
2x12
iVtaximum floor joist spans
(ft. - in.)
m.-ln.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft. . In.)
(ft. - in.)
Douglas Fir-Larch
SS
9-8
12-10
16-4
19-10
9-8
12-10
16-4
19-2
Douglas Fir-Larch
#1
9-4
12-4
15-0
17-5
8-10
11-3
13-8
15-11
Douglas Fir-Larch
#2
9-1
1L6
14-1
16-3
8-3
10-6
12-10
14-10
Douglas Fir-Larch
#3
6-10
8-8
10-7
12-4
6-3
7-11
9-8
11-3
Hem-Fir
SS
9-2
12-1
15-5
18-9
9-2
12-1
15-5
18-9
Hem-Fir
#1
9-0
11-10
14-8
17-0
8-8
10-11
13-4
15-6
Hem-Fir
#2
8-7
11-3
13-10
16-1
8-2
10-4
12-8
14-8
19.2
Hem-Fir
#3
6-10
8-8
10-7
12-4
6-3
7-11
9-8
11-3
Southern Pine
SS
9-6
12-7
16-0
19-6
9-6
12-7
16-0
19-6
Southern Pine
#1
9-4
12-4
15-9
19-2
9-4
12-4
14-11
17-9
Southern Pine
#2
9-2
12-1
14-8
17-2
8-8
11-3
13-5
15-8
Southern Pine
#3
7-4
9-5
11-1
13-2
6-9
8-7
10-1
12-1
Spruce-Pine-Fir
SS
9-0
11-10
15-1
18-4
9-0
11-10
15-1
17-9
Spruce-Pine-Fir
#1
8-9
11-6
14-1
16-3
8-3
10-6
12-10
14-10
Spruce-Pine-Fir
#2
8-9
11-6
14-1
16-3
8-3
10-6
12-10
14-10
Spruce-Pine-Fir
#3
6-10
8-8
10-7
12-4
6-3
7-11
9-8
11-3
Douglas Fir-Larch
SS
9-0
IMl
15-2
18-5
9-0
11-11
14-9
17-1
Douglas Fir-Larch
#1
8-8
11-0
13-5
15-7
7-11
10-0
12-3
14-3
Douglas Fir-Larch
#2
8-1
10-3
12-7
14-7
7-5
9-5
il-6
13-4
Douglas Fir-Larch
#3
6-2
7-9
9-6
11-0
5-7
7-1
8-8
10-1
Hem-Fir
SS
8-6
11-3
14-4
17-5
8-6
11-3
14-4
16-10^
Hem-Fir
#1
8-4
10-9
13-1
15-2
7-9
9-9
11-11
13-10
Hem-Fir
#2
7-11
10-2
12-5
14-4
7-4
9-3
11-4
13-1
24
Hem-Fir
#3
6-2
7-9
9-6
11-0
5-7
7-1
8-8
10-1
Southern Pine
SS
8-10
11-8
14-11
18-1
8-10
11-8
14-11
18-1
Southern Pine
#1
8-8
11-5
14-7
17-5
8-8
11-3
13-4
15-11
Southern Pine
#2
8-6
11-0
13-1
15-5
7-9
10-0
12-0
14-0
Southem Pine
#3
6-7
8-5
9-11
11-10
6-0
7-8
9-1
10-9
Spruce-Pine-Fir
SS
8-4
11-0
14-0
17-0
8-4
11-0
13-8
15-11
Spruce-Pine-Fir
#1
8-1
10-3
12-7
14-7
7-5
9-5
11-6
13-4
Spruce-Pine-Fir
#2
8-1
10-3
12-7
14-7
7-5
9-5
11-6
13-4
Spruce-Pine-Fir
#3
6-2
7-9
9-6
11-0
5-7
7-1
8-8
10-1
-si
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/ml
a. End bearing length shall be increased to 2 inches.
O
o
D
WOOD
2308.8.2 Framing details. Joists shall be supported later-
ally at the ends and at each support by solid blocking except
where the ends of the joists are nailed to a header, band or
rim joist or to an adjoining stud or by other means. SoHd
blocking shall not be less than 2 inches (5 1mm) in thickness
and the full depth of the joist. Notches on the ends of joists
shall not exceed one-fourth the joist depth. Holes bored in
joists shall not be within 2 inches (5 1 mm) of the top or bot-
tom of the joist, and the diameter of any such hole shall not
exceed one-third the depth of the joist. Notches in the top or
bottom of joists shall not exceed one- sixth the depth and
shall not be located in the middle third of the span.
Joist framing from opposite sides of a beam, girder or
partition shall be lapped at least 3 inches (76 mm) or the
opposing joists shall be tied together in an approved manner.
Joists framing into the side of a wood girder shall be sup-
ported by framing anchors or on ledger strips not less than 2
inches by 2 inches (51 mm by 5 1 mm).
2308.8.2.1 Engineered wood products. Cuts, notches
and holes bored in trusses, structural composite lumber,
structural glue-laminated members or I-joists are not
permitted except where permitted by the manufacturer's
recommendations or where the effects of such alterations
are specifically considered in the design of the member
by a registered design professional.
2308.8.3 Framing around openings. Trimmer and header
joists shall be doubled, or of lumber of equivalent cross sec-
tion, where the span of the header exceeds 4 feet (1219 mm) .
The ends of header joists more than 6 feet (1829 mm) long
shall be supported by framing anchors or joist hangers
unless bearing on a beam, partition or wall. Tail joists over
12 feet (3658 mm) long shall be supported at the header by
framing anchors or on ledger strips not less than 2 inches by
2 inches (51 nmi by 51 mm).
2308.8.4 Supporting bearing partitions. Bearing parti-
tions parallel to joists shall be supported on beams, girders,
doubled joists, walls or other bearing partitions. Bearing
partitions perpendicular to joists shall not be offset from
supporting girders, walls or partitions more than the joist
depth unless such joists are of sufficient size to carry the
additional load.
2308.8.5 Lateral support. Floor, attic and roof framing
with a nominal depth-to-thickness ratio greater than or
equal to 5: 1 shall have one edge held in line for the entire
span. Where the nominal depth- to- thickness ratio of the
framing member exceeds 6:1, there shall be one line of
bridging for each 8 feet (2438 mm) of span, unless both
edges of the member are held in line. The bridging shall
consist of not less than 1-inch by 3-inch (25 mm by 76 mm)'
lumber, double nailed at each end, of equivalent metal
bracing of equal rigidity, full-depth solid blocking or other
approved means. A line of bridging shall also be required
at supports where equivalent lateral support is not other-
wise provided.
2308.8.6 Structural floor sheathing. Structural floor
sheathing shall comply with the provisions of Section
2304.7.1.
2308.8.7 Under-floor ventilation. For under-floor ventila-
tion, see Section 1203.3.
2308.9 Wail framing.
2308.9.1 Size, height and spacing. The size, height and
spacing of studs shall be in accordance with Table 2308.9. 1
except that utility-grade studs shall not be spaced more than
16 inches (406 mm) o.c, or support more than a roof and
ceiling, or exceed 8 feet (2438 mm) in height for exterior
walls and load-bearing walls or 10 feet (3048 mm) for inte-
rior nonload-bearing walls. Studs shall be continuous from
a support at the sole plate to a support at the top plate to resist
loads perpendicular to the wall. The support shall be a foun-
dation or floor, ceiling or roof diaphragm or shall be
designed in accordance with accepted engineering practice.
Exception: Jack studs, trimmer studs and cripple studs
at openings in walls that comply with Table 2308.9.5.
TABLE 2308.9.1
SIZE, HEIGHT AND SPACING OF WOOD STUDS
STUD SIZE
(Inches)
BEARING WALLS
NONBEARING WALLS
Laterally unsupported
stud height^ (feet)
Supporting roof
and ceiling only
Supporting one floor, Supporting two floors,
roof and cefling roof and ceiling
Laterally
unsupported stud
height^ (feet)
Spacing
(inches)
Spacinc
1 (inches)
2x3^
10
16
2x4
10
24
16
14
24
3x4
10
24
24
16
14
24
2x5
10
24
24
16
24
2x6
10
24
24
16
20
24
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where
justified by an analysis.
b. Shall not be used in exterior walls.
372
2010 CALIFORNIA BUILDING CODE
WOOD
2308.9.2 Framing details. Studs shall be placed with their
wide dimension perpendicular to the wall. Not less than three
studs shall be installed at each comer of an exterior wall
Exception: At comers, two studs are permitted, provided
wood spacers or backup cleats of Vg-inch-thick (9.5 mm)
wood stmctural panel, ^/g-inch (9.5 mm) Type M "Exterior
Glue" particleboard, 1 -inch-thick (25 mm) lumber or
other approved devices that will serve as an adequate
backing for the attachment of facing materials are used.
Where fire-resistance ratings or shear values are involved,
wood spacers, backup cleats or other devices shall not be
used unless specifically approved for such use.
2308.9.2.1 Top plates. Bearing and exterior wall studs
shall be capped with double top plates installed to pro-
vide overlapping at comers and at intersections with
other partitions. End joints in double top plates shall be
offset at least 48 inches (1219 mm), and shall be nailed
with not less than eight 16d face nails on each side of the
joint. Plates shall be a nominal 2 inches (5 1 mm) in depth
and have a width at least equal to the width of the studs.
Exception: A single top plate is permitted, provided
the plate is adequately tied at joints, corners and inter-
secting walls by at least the equivalent of 3-inch by
6-inch (76 mm by 152 mm) by 0.036-inch-thick
(0.9 14 mm) galvanized steel that is nailed to each wall
or segment of wall by six 8d nails or equivalent, pro-
vided the rafters, joists or trusses are centered over the
studs with a tolerance of no more than 1 inch (25 mm).
2308.9.2.2 Top plates for studs spaced at 24 inches
(610 mm). Where bearing studs are spaced at 24-inch
(610 mm) intervals and top plates are less than two
2-inch by 6-inch (51 mm by 152 mm) or two 3 -inch by
4-inch (76 mm by 102 mm) members and where the floor
joists, floor tmsses or roof trusses that they support are
spaced at more than 16-inch (406 mm) intervals, such
joists or tmsses shall bear within 5 inches (127 mm) of
the studs beneath or a third plate shall be installed.
2308.9.2.3 Nonbearing walls and partitions. In
nonbearing walls and partitions, studs shall be spaced not
more than 28 inches (711 mm) o.c. and are permitted to
be set with the long dimension parallel to the wall. Inte-
rior nonbearing partitions shall be capped with no less
than a single top plate installed to provide overlapping at
comers and at intersections with other walls and parti-
tions. The plate shall be continuously tied at joints by
solid blocking at least 16 inches (406 mm) in length and
equal in size to the plate or by V2-inch by 1 Vs-inch (12.7
mm by 38 mm) metal ties with spliced sections fastened
with two 16d nails on each side of the joint.
2308.9.2.4 Plates or sills. Studs shall have full bearing
on a plate or sill not less than 2 inches (5 1 mm) in thick-
ness having a width not less than that of the wall studs.
2308.9.3 Bracing. Braced wall lines shall consist of braced
wall panels that meet the requirements for location, type and
amount of bracing as shown in Figure 2308.9.3, specified in
Table 2308.9.3(1) and are in line or offset from each other
by not more than 4 feet (1219 mm). Braced wall panels shall
start not more than 12 V2 feet (3810 mm) from each end of a
braced .wall line. Braced wall panels shall be clearly indi-
cated on the plans. Construction of braced wall panels shall
be by one of the following methods:
1. Nominal 1-inch by 4-inch (25 mm by 102 nmi) con-
tinuous diagonal braces let into top and bottom plates
and intervening studs, placed at an angle not more
than 60 degrees (1.0 rad) or less than 45 degrees (0.79
rad) from the horizontal and attached to the framing in
conformance with Table 2304.9.1.
2. Wood boards of Vg inch (15.9 mm) net minimum
thickness applied diagonally on studs spaced not over
24 inches (610 mm) o.c.
3. Wood stmctural panel sheathing with a thickness not
less than Vg inch (9.5 nmi) for 16-inch (406 mm) or
24-inch (610 mm) stud spacing in accordance with
Tables 2308.9.3(2) and 2308.9.3(3).
4. Fiberboard sheathing panels not less than V2 inch
(12.7 mm) thick applied vertically or horizontally on
studs spaced not over 16 inches (406 mm) o.c. where
installed with fasteners in accordance with Section
2306.6 and Table 2306.6.
5. Gypsum board [sheathing V2-inch- thick (12.7 mm)
by 4-feet-wide (1219 mm) wallboard or veneer base]
on studs spaced not over 24 inches (610 mm) o.c. and
nailed at 7 inches (178 mm) o.c. with nails as required
by Table 2306.7.
6. Particleboard wall sheathing panels where installed in
accordance with Table 2308.9.3(4).
7. Portland cement plaster on studs spaced 16 inches
(406 mm) o.c. installed in accordance with Section
2510.
8 . Hardboard panel siding where installed in accordance
with Section 2303.1.6 and Table 2308.9.3(5).
For cripple wall bracing, see Section 2308.9.4.1. For
Methods 2, 3, 4, 6, 7 and 8, each panel must be at least 48
inches (1219 mm) in length, covering three stud spaces
where studs are spaced 16 inches (406 mm) apart and cover-
ing two stud spaces where studs are spaced 24 inches (610
mm) apart.
For Method 5, each panel must be at least 96 inches (2438
mm) in length where applied to one face of a panel and 48
inches (1219 mm) where applied to both faces. All vertical
joints of panel sheathing shall occur over studs and adjacent
panel joints shall be nailed to common framing members.
Horizontal joints shall occur over blocking or other framing
equal in size to the studding except where waived by the
installation requirements for the specific sheathing materi-
als. Sole plates shall be nailed to the floor framing and top
plates shall be connected to the framing above in accordance
with Section 2308.3.2. Where joists are perpendicular to
braced wall lines above, blocking shall be provided under
and in line with the braced wall panels.
2010 CALIFORNIA BUILDING CODE
373
WOOD
SEISMIC DESIGN CATEGORY
MAXIMUM WALL SPACING (feet)
REQUIRED BRACING LENGTH, b
A, B and C
35'-0"
Table 2308.9.3(1) and Section 2308.9.3
DandE
25'-0"
Table 2308.12.4
UPTO4'-0"
OFFSET ALLOWED IN
BRACED WALL LINE
BRACED WALL
LINE NO. 4
BRACED WALL LINE X
12'6''AMXTO
FIRST BRACED
WALL PANEL
BRACED
WALL
LINE NOJ
BRACED WALL
LINE NO. 3
BRACED
WALL
LINEY
BRACED
WALL
PANELS
BRACED
WALL LINE Z
BRACED WALL
LINE NO. 2 DOES
NOT NEED TO
ALIGN WITH N0.3
AS LONG AS IT
HAS A BRACED
WALL PANEL
AT EACH END
BRACED WALL LINE
NO,2
BRACED
WALL LINE
BRACED WALL
LINE NO. 1
EXTERIOR
BRACED WALL
PANELS ARE
IN ONE PLANE
VERTICALLY
EXCEPT AS
PROVIDED FOR
IN SECTION
2308.12.6
NOTES:
(1 j SUM OF BRACED WALL PANEL
LENGTHS FOR BRACED WALL
LINE NO. 1 ='W + "B" + "C"
UP TO 4-0"
OFFSET ALLOWED IN
BRACED WALL LINE
CONTINUOUS
FOUNDATION AND
BRACED CRIPPLE
WALL RECOMMENDED
UNDER LOWER STORY
BRACED WALL PANELS
BRACED
WALL
PANELS - b
BRACED PANEL ABOVE MAY EXTEND UP TO
V-0" OVER WINDOW OR DOOR BELOW
For SI: 1 foot = 304.8 mm.
FIGURE 2308.9.3
BASIC COMPONENTS OF THE LATERAL BRACING SYSTEM
374
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2308.9.3(1)
BRACED WALL PANELS^
SEISMIC DESIGN
CATEGORY
CONDITION
CONSTRUCTION METHODS"-^
BRACED PANEL LOCATION
AND LENGTH**
1
2
3
4
5
6
7
8
AandB
One story, top of two or
three story
X
X
X
X
X
X
X
X
Located in accordance with
Section 2308.9.3 and not
more than 25 feet on center.
First story of two story or
second story of three story
X
X
X
X
X
X
X
X
First story of three story
—
X
X
X
x^
X
X
X
C
One story or top of two
story
—
X
X
X
X
X
X
X
Located in accordance with
Section 2308.9.3 and not
more than 25 feet on center.
First story of two story
—
X
X
X
x^
X
X
X
Located in accordance with
Section 2308.9.3 and not
more than 25 feet on center,
but total length shall not be
less than 25% of building
length*^.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. This table specifies minimum requirements for braced panels that form interior or exterior braced wall lines.
b. See Section 2308.9.3 for full description.
c. See Sections 2308.9.3. 1 and 2308.9.3.2 for alternative braced panel requirements.
d. Building length is the dimension parallel to the braced wall length.
e. Gypsum wallboard applied to framing supports that are spaced at 16 inches on center
f The required lengths shall be doubled for gypsum board applied to only one fece of a braced wall panel.
TABLE 2308.9.3(2)
EXPOSED PLYWOOD PANEL SIDING
MINIMUM THICKNESS^
(inch)
MINIMUM NUMBER OF PLIES
STUD SPACING
(inches)
Plywood siding applied directly
to studs or over sheathing
%
3
16^
%
4
24
For SI: 1 inch = 25.4 mm.
a. Thickness of grooved panels is measured at bottom of grooves.
b. Spans are permitted to be 24 inches if ply wood siding applied with face grain perpendicular to studs or over one of the following: (1)1 -inch board sheathing, (2) ''1^^
-inch wood structural panel sheathing or (3) ^/g-inch wood structural panel sheathing with strength axis (which is the long direction of the panel unless otherwise
marked) of sheathing perpendicular to studs.
TABLE 2308.9.3(3)
WOOD STRUCTURAL PANEL WALL SHEATHING**
(Not Exposed to the Weather, Strength Axis Parallel or Perpendicular to Studs Except as Indicated Below)
MINIMUM THICKNESS
(inch)
PANEL SPAN RATING
STUD SPACING (inches)
Siding nailed to studs
Nailable sheathing
Sheathing parallel to studs
Sheathing perpendicular to studs
%/V3„V,
16/0, 20/0, 24/0, 32/16
Wall-24" o.c.
24
16
24
^6' ^32' ^2
24/0, 24/16, 32/16
Wall-24"o.c.
24
24^
24
For SI: 1 inch = 25.4 mm.
a. Plywood shall consist of four or more plies.
b. Blocking of horizontal joints shall not be required except as specified in Sections 2306.3 and 2308.12.4.
2010 CALIFORNIA BUILDING CODE
375
WOOD
TABLE 2308.9.3(4)
ALLOWABLE SPANS FOR PARTICLEBOARD WALL SHEATHING
(Not Exposed to the Weather, Long Dimension of the Panel Para I lei or Perpendicular to Studs)
GRADE
THICKNESS
(inch)
STUD SPACING (inches)
Siding nailed
to studs
Sheathing under coverings specified in
Section 2308.9.3 parallel or perpendicular to studs
M-S "Exterior Glue"
and M-2"Exterior Glue"
^8
16
—
%
16
16
For SI: 1 inch = 25.4 mm.
TABLE 2308.9.3(5)
HARDBOARD SIDING
SIDING
MINIMUM NOMINAL
THICKNESS
(inch)
2x4 FRAMING
MAXIMUM SPACING
NAIL
5l2Ea.b,d
NAIL SPACING
General
Bracing panels'^
1. Lap siding
Direct to studs
^8
16"o.c.
8d
16" o.c.
Not applicable
Over sheathing
^8
16"o.c.
lOd
16" o.c.
Not applicable
2. Square edge panel siding
Direct to studs
\
24" o.c.
6d
6" o.c. edges;
12" o.c. at intermediate supports
4" o.c. edges;
8" o.c. at intermediate supports
Over sheathing
%
24" o.c.
8d
6" o.c. edges;
12" o.c. at intermediate supports
4" o.c. edges;
8" o.c. at intermediate supports
3. Shiptap edge panel siding
Direct to studs
\
16" o.c.
6d
6" o.c. edges;
12" o.c. at intermediate supports
4" o.c. edges;
8" o.c. at intermediate supports
Over sheathing
\
16" o.c.
8d
6" o.c. edges;
12" o.c. at intermediate supports
4" o.c. edges;
8" o.c. at intermediate supports
For SI: 1 inch = 25.4 mm.
a. Nails shall be corrosion resistant.
b. Minimum acceptable nail dimensions:
Panel Siding
(inch)
Lap Siding
(inch)
Shank diameter
Head diameter
0.092
0.225
0.099
0.240
c. Where used to comply with Section 2308.9.3.
d. Nail length must accommodate the sheathing and penetrate framing 172 inches.
376
2010 CALIFORNIA BUILDING CODE
WOOD
2308.9.3.1 Alternative bracing. Any bracing required
by Section 2308.9.3 is permitted to be replaced by the
following:
1. In one-story buildings, each panel shall have a
length of not less than 2 feet 8 inches (813 mm) and
a height of not more than 10 feet (3048 mm). Each
panel shall be sheathed on one face with
^/g-inch-minimum-thickness (9.5 mm) wood struc-
tural panel sheathing nailed with 8d common or gal-
vanized box nails in accordance with Table
2304.9.1 and blocked at wood structural panel
edges. Two anchor bolts installed in accordance
with Section 2308.6 shall be provided in each panel.
Anchor bolts shall be placed at each panel outside
quarter points. Each panel end stud shall have a
tie-down device fastened to the foundation, capable
of providing an approved upHft capacity of not less
than 1,800 pounds (8006 N). The tie-down device
shall be installed in accordance with the manufac-
turer's recommendations. The panels shall be sup-
ported directly on a foundation or on floor framing
supported directly on a foundation that is continu-
ous across the entire length of the braced wall hne.
This foundation shall be reinforced with not less
than one No. 4 bar top and bottom.
Where the continuous foundation is required to
have a depth greater than 12 inches (305 mm), a
minimum 12-inch by 12-inch (305 mm by 305
mm) continuous footing or turned down slab edge
is permitted at door openings in the braced wall
line. This continuous footing or turned down slab
edge shall be reinforced with not less than one No.
4 bar top and bottom. This reinforcement shall be
lapped 15 inches (381 mm) with the reinforcement
required in the continuous foundation located
directly under the braced wall line.
2. In the first story of two-story buildings, each wall
panel shall be braced in accordance with Section
2308.9.3.1, Item 1, except that the wood structural
panel sheathing shall be provided on both faces,
three anchor bolts shall be placed at one-quarter
points, and tie-down device uplift capacity shall
not be less than 3,000 pounds (13 344 N).
2308.9.3.2 Alternate bracing wall panel adjacent to a
door or window opening. Any bracing required by Sec-
tion 2308.9.3 is permitted to be replaced by the following
when used adjacent to a door or window opening with a
full-length header:
1. In one-story buildings, each panel shall have a
length of not less than 16 inches (406 nrni) and a
height of not more than 10 feet (3048 mm). Each
panel shall be sheathed on one face with a single
layer of Vg inch (9.5 mm) minimum thickness
wood structural panel sheathing nailed with 8d
conmion or galvanized box nails in accordance
with Figure 2308.9.3.2. The wood structural panel
sheathing shall extend up over the solid sawn or
glued-laminated header and shall be nailed in
accordance with Figure 2308.9.3.2. A built-up
header consisting of at least two 2 x 12s and fas-
tened in accordance with Item 24 of Table
2304.9. 1 shall be permitted to be used. A spacer, if
used, shall be placed on the side of the built-up
beam opposite the wood structural panel sheath-
ing. The header shall extend between the inside
faces of the first full-length outer studs of each
panel. The clear span of the header between the
inner studs of each panel shall be not less than 6
feet (1829 mm) and not more than 18 feet (5486
mm) in length. A strap with an uplift capacity of
not less than 1,000 pounds (4,400 N) shall fasten
the header to the inner studs opposite the sheath-
ing. One anchor bolt not less than Vg inch (15.9
mm) diameter and installed in accordance with
Section 2308.6 shall be provided in the center of
each sill plate. The studs at each end of the panel
shall have a tie-down device fastened to the foun-
dation with an uplift capacity of not less than 4,200
pounds (18 480 N).
Where a panel is located on one side of the open-
ing, the header shall extend between the inside face
of the first full-length stud of the panel and the bear-
ing studs at the other end of the opening. A strap
with an upUft capacity of not less than 1 ,000 pounds
(4400 N) shall fasten the header to the bearing
studs. The bearing studs shall also have a tie-down
device fastened to the foundation with an uplift
capacity of not less than 1,000 pounds (4400 N).
The tie-down devices shall be an embedded
strap type, installed in accordance with the manu-
facturer's recommendations. The panels shall be
supported directly on a foundation that is continu-
ous across the entire length of the braced wall line.
This foundation shall be reinforced with not less
than one No. 4 bar top and bottom.
Where the continuous foundation is required to
have a depth greater than 12 inches (305 nmi), a
minimum 12-inch by 12-inch (305 mm by 305
mm) continuous footing or turned down slab edge
is permitted at door openings in the braced wall
line. This continuous footing or turned down slab
edge shall be reinforced with not less than one No.
4 bar top and bottom. This reinforcement shall be
lapped not less than 15 inches (381 mm) with the
reinforcement required in the continuous founda-
tion located directly under the braced wall line.
2. In the first story of two-story buildings, each wall
panel shall be braced in accordance with Item 1
above, except that each panel shall have a length of
not less than 24 inches (610 mm).
2308.9.4 Cripple walls. Foundation cripple walls shall be
framed of studs not less in size than the studding above with
a minimum length of 14 inches (356 mm), or shall be framed
of solid blocking. Where exceeding 4 feet (1219 mm) in
height, such walls shall be framed of studs having the size
required for an additional story.
2010 CALIFORNIA BUILDING CODE
377
WOOD
EXTENT OF HEADER
"DOUBLE PORTAL FRAME (TWO BRACED WALL PANELS)
EXTENT OF HEADER
SINGLE PORTAL FRAME (ONE BRACED WALL PANEL)
FASTEN TOP PLATE TO HEADER WITH TWO
ROWS OF 16D SINKER NAILS AT 3" O.C. TYR
1000 LB STRAP OPPOSITE SHEATHING
FASTEN SHEATHING TO HEADER WITH 8D COMMON OR
GALVANIZED BOX NAILS IN 3" GRID PATTERN AS SHOWN AND
3' O.C. IN ALL FRAMING (STUDS. BLOCKING. AND SILLS) TYP.
MIN. WIDTH = 16" FOR ONE STORY STRUCTURES
MIN. WIDTH ^ 24" FOR USE (N THE FIRST OF TWO
STORY STRUCTURES
MIN. 2x4 FRAMING
3/8" MIN. THICKNESS WOOD
STRUCTURAL PANEL SHEATHING
MIN. 4200 LB TIE-DOWN DEVICE (EMBEDDED INTO
CONCRETE AND NAILED INTO FRAMING)
SEE SECTION 2308.9,3.2
TYPICAL PORTAL —
FRAME
CONSTRUCTION
FOR A PANEL SPLICE
(IF NEEDED), PANEL
EDGES SHALL BE
BLOCKED. AND OCCUR
WITHIN 24" OF MID-
HEIGHT ONE ROW OF
TYP SHEATHING-TO-
FRAMING NAILING IS
REQUIRED.
IF 2X4 BLOCKING iS
USED, THE 2X4'S MUST
BE NAILED TOG ETHER
WITH 3 16D SINKERS
' MIN. 1000 LB
TIE DOWN
DEVICE
U
t
L
::^x:f:^.
For SI: 1 foot = 304.8 mm; 1 inch = 25.4 mm; 1 pound = 4.448 N.
FIGURE 2308.9.3.2
ALTERNATE BRACED WALL PANEL ADJACENT TO A DOOR OR WINDOW OPENING
2308.9.4.1 Bracing. For the purposes of this section,
cripple walls having a stud height exceeding 14 inches
(356 mm) shall be considered a story and shall be braced
in accordance with Table 2308.9.3(1) for Seismic Design
Category A, B or C. See Section 2308.12.4 for Seismic
Design Category D or E.
2308.9.4.2 Nailing of bracing. Spacing of edge nailing
for required wall bracing shall not exceed 6 inches (152
nun) O.C. along the foundation plate and the top plate of
the cripple wall. Nail size, nail spacing for field nailing
and more restrictive boundary nailing requirements shall
be as required elsewhere in the code for the specific brac-
ing material used.
2308.9.5 Openings in exterior walls.
2308.9.5.1 Headers. Headers shall be provided over
each opening in exterior-bearing walls. The spans in
Table 2308.9.5 are permitted to be used for one- and
two-family dwellings. Headers for other buildings shall
be designed in accordance with Section 2301 .2, Item 1 or
2. Headers shall be of two pieces of nominal 2-inch (5 1
mm) framing lumber set on edge as permitted by Table
2308.9.5 and nailed together in accordance with Table
2304.9.1 or of solid lumber of equivalent size.
2308.9.5.2 Header support. Wall studs shall support the
ends of the header in accordance with Table 2308.9.5.
Each end of a lintel or header shall have a length of bear-
ing of not less than 1 V2 inches (38 mm) for the full width
of the lintel.
2308.9.6 Openings in interior bearing partitions. Head-
ers shall be provided over each opening in interior bearing
partitions as required in Section 2308.9.5. The spans in
Table 2308.9.6 are permitted to be used. Wall studs shall
support the ends of the header in accordance with Table
2308.9.5 or 2308.9.6, as appropriate.
2308.9.7 Openings in interior nonbearing partitions.
Openings in nonbearing partitions are permitted to be
framed with single studs and headers. Each end of a lintel or
header shall have a length of bearing of not less than 1 V2
inches (38 mm) for the full width of the lintel.
2308.9.8 Pipes in walls. Stud partitions containing
plumbing, heating or other pipes shall be so framed and
the joists underneath so spaced as to give proper clear-
ance for the piping. Where a partition containing such
piping runs parallel to the floor joists, the joists under-
neath such partitions shall be doubled and spaced to per-
mit the passage of such pipes and shall be bridged. Where
plumbing, heating or other pipes are placed in or partly in
a partition, necessitating the cutting of the soles or plates,
a metal tie not less than 0.058 inch (1.47 mm) (16 galva-
nized gage) and V/2 inches (38 mm) wide shall be fas-
tened to each plate across and to each side of the opening
with not less than six 16d nails.
378
2010 CALIFORNIA BUILDING CODE
lO
o
O
>
O
z
>
CD
O
o
o
D
m
TABLE 2308.9.5
HEADER AND GIRDER SPANS^ FOR EXTERIOR BEARING WALLS
(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Plne-Fir" and Required Number of Jack Studs)
HEADERS
SUPPORTING
SIZE
GROUND SNOW LOAD (psf)''
30
50
Building width' (feet)
20
28
36
20
28
36
Span
NJ"
Span
NJ-
Span
NJ*-
Span
NJ**
Span
NJ**
Span
NJ^
Roof & Ceiling
2-2x4
3-6
3-2
1
2-10
1
3-2
1
2-9
1
2-6
1
2-2x6
5-5
4-8
1
4-2
1
4-8
I
4-1
I
3-8
2
2-2x8
6-10
5-11
2
5-4
2
5-11
2
5-2
2
4-7
2
2-2 X 10
8-5
7-3
2
6-6
2
7-3
2
6-3
2
5-7
2
2-2 X 12
9-9
8-5
2
7-6
2
8-5
2
7-3
2
6-6
2
3-2x8
8-4
7-5
1
6-8
1
7-5
1
6-5
2
5-9
2
3-2 X 10
10-6
9-1
2
8-2
2
9-1
2
7-10
2
7-0
2
3-2 X 12
12-2
10-7
2
9-5
2
10-7
2
9-2
2
8-2
2
4-2x8
9-2
8-4
1
7-8
1
8-4
1
7-5
1
6-8
1
4-2x10
11-8
10-6
1
9-5
2
10-6
1
9-1
2
8-2
2
4-2 X 12
14-1
12-2
2
10-11
2
12-2
2
10-7
2
9-5
2
Roof, Ceiling & 1
Center-Bearing Floor
2-2x4
3-1
2-9
1
2-5
1
2-9
1
2-5
1
2-2
1
2-2x6
4-6
4-0
1
3-7
2
4-1
1
3-7
2
3-3
2
2-2x8
5-9
5-0
2
4-6
2
5-2
2
4-6
2
4-1
2
2-2x10
7-0
6-2
2
5-6
2
6-4
2
5-6
2
5-0
2
2-2x12
8-1
7-1
2
6-5
2
7-4
2
6-5
2
5-9
3
3-2x8
7-2
6-3
2
5-8
2
6-5
2
5-8
2
5-1
2
3-2x10
8-9
7-8
2
6-11
2
7-11
2
6-11
2
6-3
2
3-2 x 12
10-2
8-11
2
8-0
2
9-2
2
8-0
2
7-3
2
4-2x8
8-1
7-3
1
6-7
1
7-5
1
6-6
1
5-11
2
4-2x10
10-1
8-10
2
8-0
2
9-1
2
8-0
2
7-2
2
4-2x12
11-9
10-3
2
9-3
2
10-7
2
9-3
2
8-4
2
Roof, Ceiling & 1 Clear
Span Floor
2-2x4
2-8
2-4
1
2-1
1
2-7
1
2-3
1
2-0
1
2-2x6
3-11
3-5
2
3-0
2
3-10
2
3-4
2
3-0
2
2-2x8
5-0
2
4-4
2
3-10
2
4-10
2
4-2
2
3-9
2
2-2 X 10
6-1
2
5-3
2
4-8
2
5-11
2
5-1
2
4-7
3
2-2x12
7-1
2
6-1
3
5-5
3
6-10
2
5-11
3
5-4
3
3-2x8
6-3
2
5-5
2
4-10
2
6-1
2
5-3
2
4-8
2
3-2 x 10
7-7
2
6-7
2
5-11
2
7-5
2
6-5
2
5-9
2
3-2x12
8-10
2
7-8
2
6-10
2
8-7
2
7-5
2
6-8
2
4-2x8
7-2
1
6-3
2
5-7
2
7-0
1
6-1
2
5-5
2
4-2 X 10
8-9
2
7-7
2
6-10
2
8-7
2
7-5
2
6-7
2
4-2x12
10-2
2
8-10
2
7-11
2
9-11
2
8-7
2
7-8
2
(continued)
O
>
O
3D
>
00
TABLE 2308.9.5— continued
HEADER AND GIRDER SPANS^FOR EXTERIOR BEARING WALLS
(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Pine-FIr'^ and Required Number of Jack Studs)
HEADERS
SUPPORTING
SIZE
GROUND SNOW LOAD (psf)'
30
50
Building width' (feet)
20
28
36
20
28
36
Span
NJ**
Span
NJ--
Span
NJ*^
Span
NJ"
Span
NJ"
Span
NJ'
Roof, Ceiling & 2
Center-Bearing
Floors
2-2x4
2-7
]
2-3
1
2-0
I
2-6
1
2-2
1
1-11
1
2-2x6
3-9
2
3-3
2
2-11
2
3-8
2
3-2
2
2-10
2
2-2x8
4-9
2
4-2
2
3-9
2
4-7
2
4-0
2
3-8
2
2-2x10
5-9
2
5-1
2
4-7
3
5-8
2
4-11
2
4-5
3
2-2x12
6-8
2
5-10
3
5-3
3
6-6
2
5-9
3
5-2
3
3-2x8
5-11
2
5-2
2
4-8
2
5-9
2
5-1
2
4-7
2
3-2x10
7-3
2
6-4
2
5-8
2
7-1
2
6-2
2
5-7
2
3-2x12
8-5
2
7-4
2
6-7
2
8-2
2
7-2
2
6-5
3
4-2x8
6-10
1
6-0
2
5-5
2
6-8
1
5-10
2
5-3
2
4-2 X 10
8-4
2
7-4
2
6-7
2
8-2
2
7-2
2
6-5
2
4-2x12
9-8
2
8-6
2
7-8
2
9-5
2
8-3
2
7-5
2
Roof, Ceiling & 2
Clear Span Floors
2-2x4
2-1
1
1-8
1
1-6
2
2-0
1
1-8
1
1-5
2
2-2x6
3-1
2
2-8
2
2-4
2
3-0
2
2-7
2
2-3
2
2-2x8
3-10
2
3-4
2
3-0
3
3-10
2
3-4
2
2-11
3
2-2 X IQ
4-9
2
4-1
3
3-8
3
4-8
2
4-0
3
3-7
3
2-2 X 12
5-6
3
4-9
3
4-3
3
5-5
3
4-8
3
4-2
3
3-2x8
4-10
2
4-2
2
3-9
2
4-9
2
4-1
2
3-8
2
3-2x10
5-11
2
5-1
2
4-7
3
5-10
2
5-0
2
4-6
3
3-2 X 12
6-10
2
5-11
3
5-4
3
6-9
2
5-10
3
5-3
3
4-2x8
5-7
2
4-10
2
4-4
2
5-6
2
, 4-9
2
4-3
2
4-2x10
6-10
2
5-11
2
5-3
2
6-9
2
5-10
2
5-2
2
4-2 X 12
7-11
2
6-10
2
6-2
3
7-9
2
6-9
2
6-0
3
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m^.
a. Spans are given in feet and inches (ft-in).
b. Tabulated values are for No. 2 grade lumber.
c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
d. NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved framing anchor attached to the full-height wall
stud and to the header.
e. Use 30 pounds per square foot ground snow load for cases in which ground snow load is less than 30 pounds per square foot and the roof live load is equal to or less than 20 pounds per square foot.
O
O
a
o
o
o
a
WOOD
TABLE 2308.9.6
HEADER AND GIRDER SPANS'* FOR INTERIOR BEARING WALLS
(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Pine-FIr" and Required Number of Jack Studs)
HEADERS AND GIRDERS
SUPPORTING
SIZE
BUILDING WIDTH*^ (feet)
20
28
36
Span
NJ^
Span
NJ'*
Span
NJ^
One Floor Only
2-2x4
3-1
1
2-8
1
2-5
1
2-2x6
4-6
1
3-11
1
3-6
1
2-2x8
5-9
1
5-0
2
4-5
2
2-2 xIO
7-0
2
6-1
2
5-5
2
2-2 xl2
8-1
2
7-0
2
6-3
2
3-2x8
7-2
1
6-3
1
5-7
2
3-2x10
8-9
1
7-7
2
6-9
2
3-2x12
10-2
2
8-10
2
7-10
2
4-2x8
9-0
1
7-8
1
6-9
1
4-2 xlO
10-1
1
8-9
1
7-10
2
4-2x12
11-9
1
10-2
2
9-1
2
Two Floors
2-2x4
2-2
1
1-10
1
1-7
1
2-2x6
3-2
2
2-9
2
2-5
2
2-2x8
4-1
2
3-6
2
3-2
2
2-2x10
4-11
2
4-3
2
3-10
3
2-2x12
5-9
2
5-0
3
4-5
3
3-2x8
5-1
2
4-5
2
3-11
2
3-2x10
6-2
2
5-4
2
4-10
2
3-2x12
7-2
2 '
6-3
2
5-7
3
4-2x8
6-1
1
5-3
2
4-8
2
4-2 xlO
7-2
2
6-2
2
5-6
2
4-2 xl2
8-4
2
7-2
2
6-5
2
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Spans are given in feet and inches (ft-in).
b. Tabulated values are for No. 2 grade lumber.
c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
d. NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the headers are permitted to be supported by an
approved framing anchor attached to the full-height wall stud and to the header.
2010 CALIFORNIA BUILDING CODE
381
WOOD
TABLE 2308.10.1
REQUIRED RATING OF APPROVED UPLIFT CONNECTORS (poundsf'^'^'^^'S
,h
BASIC WIND SPEED
(3-second gust)
ROOF SPAN (feet)
OVERHANGS
(pounds/feet)''
12
20
24
28
32
36
40
85
-72
-120
-145
-169
-193
-217
-241
-38.55
90
-91
-151
-181
-212
-242
-272
-302
-43,22
100
-131
-281
-262
-305
-349
-393
-436
-53.36
110
-175
-292
-351
-409
-467
-526
-584
-64.56
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 1.61 km/hi; 1 pound = 0.454 Kg, 1 pound/foot = 14.5939 N/m.
a. The uplift connection requirements are based on a 30-foot mean roof height located in Exposure B. For Exposure C or D and for other mean roof heights, multiply
the above loads by the adjustment coeflTicients below.
Mean Roof Height (feet)
EXPOSURE
15
20
25
30
35
40
45
50
55
60
B
1.00
1.00
1.00
1.00
1.05
1.09
1.12
1.16
1.19
1.22
C
1.21
1.29
1.35
1.40
1.45
1.49
1.53
1.56
1.59
1.62
D
1.47
1.55
1.61
1.66
1.70
1.74
1.78
1.81
1.84
1.87
b. The upUft connection requirements are based on the framing being spaced 24 inches on center. Multiply by 0.67 for framing spaced 16 inches on center and multi-
ply by 0.5 for framing spaced 12 inches on center
c. The uplift connection requirements include an allowance for 10 pounds of dead load.
d. The uplift connection requirements do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads
found in the table. The overhang loads are also based on framing spaced 24 inches on center. The overhang loads given shall be multiplied by the overhang projec-
tion and added to the roof uplift value in the table.
e. The uplift connection requirements are based upon wind loading on end zones as defined in Figure 6-2 of ASCE 7. Connection loads for connections located a dis-
tance of 20 percent of the least horizontal dimension of the building from the corner of the building are permitted to be reduced by multiplying the table connection
value by 0.7 and multiplying the overhang load by 0.8.
f. For wall-to-wall and wall-to-foundation connections, the capacity of the uplift connector is permitted to be reduced by 100 pounds for each full wall above. (For
example, if a 500-pound rated connector is used on the roof framing, a 400-pound rated connector is permitted at the nett floor level down).
g. Interpolation is permitted for intermediate values of basic wind speeds and roof spans.
h. The rated capacity of approved tie-down devices is permitted to include up to a 60-percent increase for wind effects where allowed by material specifications.
2308.9.9 Bridging. Unless covered by interior or exterior
wall coverings or sheathing meeting the minimum require-
ments of this code, stud partitions or walls with studs hav-
ing a height-to-least-thickness ratio exceeding 50 shall
have bridging not less than 2 inches (51 mm) in thickness
and of the same width as the studs fitted snugly and nailed
thereto to provide adequate lateral support. Bridging shall
be placed in every stud cavity and at a frequency such that
no stud so braced shall have a height-to-least-thickness
ratio exceeding 50 with the height of the stud measured
between horizontal framing and bridging or between
bridging, whichever is greater.
2308.9.10 Cutting and notching. In exterior walls and
bearing partitions, any wood stud is permitted to be cut or
notched to a depth not exceeding 25 percent of its width.
Cutting or notching of studs to a depth not greater than 40
percent of the width of the stud is permitted in nonbearing
partitions supporting no loads other than the weight of the
partition.
2308.9.11 Bored holes. A hole not greater in diameter
than 40 percent of the stud width is permitted to be bored
in any wood stud. Bored holes not greater than 60 percent
of the width of the stud are permitted in nonbearing parti-
tions or in any wall where each bored stud is doubled, pro-
vided not more than two such successive doubled studs
are so bored.
In no case shall the edge of the bored hole be nearer than
Vg inch (15.9 mm) to the edge of the stud.
Bored holes shall not be located at the same section of
stud as a cut or notch.
2308.10 Roof and ceiling framing. The framing details
required in this section apply to roofs having a minimum
slope of three units vertical in 12 units horizontal (25-percent
slope) or greater. Where the roof slope is less than three units
vertical in 12 units horizontal (25 -percent slope), members
supporting rafters and ceiling joists such as ridge board, hips
and valleys shall be designed as beams.
2308.10.1 Wind uplift. The roof construction shall have
rafter and truss ties to the wall below. Resultant uplift loads
shall be transferred to the foundation using a continuous
load path. The rafter or truss to wall connection shall com-
ply with Tables 2304.9.1 and 2308.10.1.
2308.10.2 Ceiling joist spans. Allowable spans for ceiling
joists shall be in accordance with Table 2308.10.2(1) or
2308.10.2(2). For other grades and species, refer to the
AF&PA Span Tables for Joists and Rafters,
2308.10.3 Rafter spans. Allowable spans for rafters shall
be in accordance with Table 2308.10.3(1), 2308.10.3(2),
2308.10.3(3), 2308.10.3(4), 2308.10.3(5) or 2308.10.3(6).
For other grades and species, refer to the AF&PA Span
Tables for Joists and Rafters.
382
2010 CALIFORNIA BUILDING CODE
TABLE 2308.10.2(1)
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES
(Uninhabitable Attics Without Storage, Live Load = 10 pounds psf, UA = 240)
O
>
O
31
z
>
CO
g
z
o
o
o
o
m
CEILING JOIST SPACING
(Inches)
SPECIES AND GRADE
DEAD LOAD = 5 pounds per square foot
2x4 1 2x6 1 2x8 I 2x10
Maximum celling ioist spans
(ft. -in.)
(ft. -In.)
(ft. - in.)
(ft. -in.)
12
Douglas Fir-Larch SS
13-2
20-8
Note a
Note a
Douglas Fir-Larch #1
12-8
19-11
Note a
Note a
Douglas Fir-Larch #2
12-5
19-6
25-8
Note a
Douglas Fir-Larch #3
10-10
15-10
20-1
24-6
Hem-Fir SS
12-5
19-6
25-8
Note a
Hem-Fir #1
12-2
19-1
25-2
Note a
Hem-Fir #2
11-7
18-2
24-0
Note a
Hem-Fir #3
10-10
15-10
20-1
24-6
Southern Pine SS
12-11
20-3
Note a
Note a
Southern Pine #1
12-8
19-11
Note a
Note a
Southern Pine #2
12-5
19-6
25-8
Note a
Southern Pine #3
11-6
17-0
21-8
25-7
Spruce-Pine-Fir SS
12-2
19-1
25-2
Note a
Spruce-Pine-Fir #1
11-10
18-8
24-7
Note a
Spruce-Pine-Fir #2
11-10
18-8
24-7
Note a
Spruce-Pine-Fir #3
10-10
15-10
20-1
24-6
16
Douglas Fir-Larch SS
11-11
18-9
24-8
Note a
Douglas Fir-Larch #1
11-6
18-1
23-10
Note a
Douglas Fir-Larch #2
11-3
17-8
23-0
Note a
Douglas Fir-Larch #3
9-5
13-9
17-5
21-3
Hem-Fir SS
11-3
17-8
23-4
Note a
Hem-Fir #1
11-0
17-4
22-10
Note a
Hem-Fir #2
10-6
16-6
21-9
Note a
Hem-Fir #3
9-5
13-9
17-5
21-3
Southern Pine SS
11-9
18-5
24-3
Note a
Southern Pine #1
11-6
18-1
23-1
Note a
Southern Pine #2
11-3
17-8
23-4
Note a
Southern Pine #3
10-0
14-9
18-9
22-2
Spruce-Pine-Fir SS
11-0
17-4
22-10
Note a
Spruce-Pine-Fir #1
10-9
16-11
22-4
Note a
Spruce-Pine-Fir #2
10-9
16-11
22-4
Note a
Spruce-Pine-Fir #3
9-5
13-9
17-5
21-3
00
CO
(continued)
00
TABLE 2308.10.2(1)— continued
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES
^Uninhabitable Attics Without Storage, Live Load = 10 pounds psf, UA = 240)
o
O
>
o
XI
z
>
CD
C
o
o
o
a
m
CEILING JOIST SPACING
finches)
SPECIES AND GRADE
DEAD LOAD = 5 Dounds oer sauare foot
2x4 1 2x6 1 2x8 1 2x10
Maximum ceilinq joist soans
m. - in.)
(ft. - in.)
m. - in.)
m.-in.)
19.2
Douglas Fir-Larch SS
11-3
17-8
23-3
Note a
Douglas Fir-Larch #1
10-10
17-0
22-5
Note a
Douglas Fir-Larch #2
10-7
16-7
21-0
25-8
Douglas Fir-Larch #3
8-7
12-6
15-10
19-5
Hem-Fir SS
10-7
16-8
21-11
Note a
Hem-Fir #1
10-4
16-4
21-6
Note a
Hem-Fir #2
9-11
15-7
20-6
25-3
Hem-Fir #3
8-7
12-6
15-10
19-5
Southern Pine SS
11-0
17-4
22-10
Note a
Southern Pine #1
10-10
17-0
22-5
Note a
Southern Pine #2
10-7
16-8
21-11
Note a
Southern Pine #3
9-1
13-6
17-2
20-3
Spruce-Pine-Fir SS
10-4
16-4
21-6
Note a
Spruce-Pine-Fir #1
10-2
15-11
21-0
25-8
Spruce-Pine-Fir #2
10-2
15-11
21-0
25-8
Spruce-Pine-Fir #3
8-7
12-6
15-10
19-5
24
Douglas Fir-Larch SS
10-5
16-4
21-7
Note a
Douglas Fir-Larch #1
10-0
15-9
20-1
24-6
Douglas Fir-Larch #2
9-10
14-10
18-9
22-11
Douglas Fir-Larch #3
7-8
11-2
14-2
17-4
Hem-Fir SS
9-10
15-6
20-5
Note a
Hem-Fir #1
9-8
15-2
19-7
23-11
Hem-Fir #2
9-2
14-5
18-6
22-7
Hem-Fir #3
7-8
11-2
14-2
17-4
Southern Pine SS
10-3
16-1
21-2
Note a
Southern Pine #1
10-0
15-9
20-10
Note a
Southern Pine #2
9-10
15-6
20-1
23-11
Southern Pine #3
8-2
12-0
15-4
18-1
Spruce-Pine-Fir SS
9-8
15-2
19-11
25-5
Spmce-Pine-Fir #1
9-5
14-9
18-9
22-11
Spruce-Pine-Fir #2
9-5
14-9
18-9
22-11
Spruce-Pine-Fir #3
7-8
11-2
14-2
17-4
o
o
o
For SL 1 inch = 25.4 mm, 1 foot =
a. Span exceeds 26 feet in length,
= 304.8 mm, 1 pound per square foot = 47.8 N/m^
Check sources for availability of lumber in lengths greater than 20 feet.
o
o
O
>
Tl
O
33
Z
>
CD
C
o
o
o
o
m
TABLE 2308.10.2(2)
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES
(Uninhabitable Attics With Limited Storage, Live Load - 20 pounds per square foot, L/A = 240)
CEILING JOIST SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD = 10 Dounds oer sauare foot
2x4
2x6 1 2x8
2x10
Maximum cellina ioist spans
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - In.)
12
Douglas Fir-Larch SS
10-5
16-4
21-7
Note a
Douglas Fir-Larch #1
10-0
15-9
20-1
24-6
Douglas Fir-Larch #2
9-10
14-10
18-9
22-11
Douglas Fir-Larch #3
7-8
11-2
14-2
17-4
Hem-Fir SS
9-10
15-6
20-5
Note a
Hem-Fir #1
9-8
15-2
19-7
23-11
Hem-Fir #2
9-2
14-5
18-6
22-7
Hem-Fir #3
7-8
11-2
14-2
17-4
Southern Pine SS
10-3
16-1
21-2
Note a
Southern Pine #1
10-0
15-9
20-10
Note a
Southern Pine #2
9-10
15-6
20-1
23-11
Southern Pine #3
8-2
12-0
15-4
18-1
Spruce-Pine-Fir SS
9-8
15-2
19-11
25-5
Spruce-Pine-Fir #1
9-5
14-9
18-9
22-11
Spruce-Pine-Fir #2
9-5
14-9
18-9
22-11
Spruce-Pine-Fir #3
7-8
11-2
14-2
17-4
16
Douglas Fir-Larch SS
9-6
14-11
19-7
25-0
Douglas Fir-Larch #1
9-1
13-9
17-5
21-3
Douglas Fir-Larch #2
8-9
12-10
16-3
19-10
Douglas Fir-Larch #3
6-8
9-8
12-4
15-0
Hem-Fir SS
8-11
14-1
18-6
23-8
Hem-Fir #1
8-9
13-5
16-10
20-8
Hem-Fir #2
8-4
12-8
16-0
19-7
Hem-Fir #3
6-8
9-8
12-4
15-0
Southern Pine SS
9-4
14-7
19-3
24-7
Southern Pine #1
9-1
14-4
18-11
23-1
Southern Pine #2
8-11
13-6
17-5
20-9
Southern Pine #3
7-1
10-5
13-3
15-8
Spruce-Pine-Fir SS
8-9
13-9
18-1
23-1
Spruce-Pine-Fir #1
8-7
12-10
16-3
19-10
Spruce-Pine-Fir #2
8-7
12-10
16-3
19-10
Spruce-Pine-Fir #3
6-8
9-8
12-4
15-0
00
(continued)
O
O
a
00
TABLE 2308.10.2(2)— continued
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES
(Uninhabitable Attics With Limited Storage, Live Load = 20 pounds per square foot, UA = 240)
O
O
a
ro
o
O
o
3)
z
>
CD
C
o
o
o
o
m
CEILING JOIST SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD - 1 pounds oer sauare foot
2x4
2x6
2x8
2x10
Maximum ceih'nq joist spans i
m.-in.^
m.-\n.)
m.-in.)
m.-in.)
19.2
Douglas Fir-Larch
SS
8-11
14-0
18-5
23-4
Douglas Fir-Larch
#1
8-7
12-6
15-10
19-5
Douglas Fir-Larch
#2
8-0
11-9
14-10
18-2
Douglas Fir-Larch
#3
6-1
8-10
11-3
13-8
Hem-Fir
SS
8-5
13-3
17-5
22-3
Hem-Fir
#1
8-3
12-3
15-6
18-11
Hem-Fir
#2
7-10
11-7
14-8
17-10
Hem-Fir
#3
6-1
8-10
11-3
13-8
Southern Pine
SS
8-9
13-9
18-1
23-1
Southern Pine
#1
8-7
13-6
17-9
21-1
Southern Pine
#2
8-5
12-3
15-10
18-11
Southern Pine
#3
6-5
9-6
12-1
14-4
Spruce-Pine-Fir
SS
8-3
12-11
17-1
21-8
Spnice-Pine-Fir
#1
8-0
11-9
14-10
18-2
Spruce-Pine-Fir
#2
8-0
11-9
14-10
18-2
Spruce-Pine-Fir
#3
6-1
8-10
11-3
13-8
24
Douglas Fir-Larch
SS
8-3
13-0
17-1
20-11
Douglas Fir-Larch
#1
7-8
11-2
14-2
17-4
Douglas Fir-Larch
#2
7-2
10-6
13-3
16-3
Douglas Fir-Larch
#3
5-5
7-11
10-0
12-3
Hem-Fir
SS
7-10
12-3
16-2
20-6
Hem-Fir
#1
7-6
10-11
13-10
16-11
Hem-Fir
#2
7-1
10-4
13-1
16-0
Hem-Fir
#3
5-5
7-11
10-0
12-3
Southern Pine
SS
8-1
12-9
16-10
21-6
Southern Pine
#1
8-0
12-6
15-10
18-10
Southern Pine
#2
7-8
11-0
14-2
16-11
Southern Pine
#3
5-9
8-6
10-10
12-10
Spruce-Pine-Fir
SS
7-8
12-0
15-10
19-5
Spruce-Pine-Fir
#1
7-2
10-6
13-3
16-3
Spruce-Pine-Fir
#2
7-2
10-6
13-3
16-3
Spruce-Pine-Fir
#3
5-5
7-11
10-0
12-3
For SI: 1 inch = 25.4 mm, 1 foot =
a. Span exceeds 26 feet in length.
: 304.8 mm, 1 pound per square foot = 47.8 N/m\
Check sources for availability of lumber in lengths greater than 20 feet.
ro
o
TABLE 2308.10.3(1)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Roof Live Load = 20 pounds per square foot, Ceiling Not Attached to Rafters, UA = 180)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD = 10 pounds per sauare foot
DEAD LOAD = 20 Dounds per sauare foot
2x4 1 2x6 1 2x8 1 2x10 1 2x12
2x4 1 2x6 2x8 1 2x10 1 2x12
IMaximum rafter soans
m. - in.)
(ft. - in.)
m.-in.)
m. - In.)
m.-in.)
m. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft. -in.)
12
Douglas Fir-Larch SS
11-6
18-0
23-9
Note a
Note a
11-6
18-0
23-5
Note a
Note a
Douglas Fir-Larch #1
11-1
17-4
22-5
Note a
Note a
10-6
15-4
19-5
23-9
Note a
Douglas Fir-Larch #2
10-10
16-7
21-0
25-8
Note a
9-10
14-4
18-2
22-3
25-9
Douglas Fir-Larch #3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Hem-Fir SS
10-10
17-0
22-5
Note a
Note a
10-10
17-0
22-5
Note a
Note a
Hem-Fir #1
10-7
16-8
21-10
Note a
Note a
10-3
14-11
18-11
23-2
Note a
Hem-Fir #2
10-1
15-11
20-8
25-3
Note a
9-8
14-2
17-11
21-11
25-5
Hem-Fir #3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Southern Pine SS
11-3
17-8
23-4
Note a
Note a
U-3
17-8
23-4
Note a
Note a
Southern Pine #1
11-1
17-4
22-11
Note a
Note a
11-1
17-3
21-9
25-10
Note a
Southern Pine #2
10-10
17-0
22-5
Note a
Note a
10-6
15-1
19-5
23-2
Note a
Southern Pine #3
9-1
13-6
17-2
20-3
24-1
7-11
11-8
14-10
17-6
20-11
Spruce-Pine-Fir SS
10-7
16-8
21-11
Note a
Note a
10-7
16-8
21-9
Note a
Note a
Spruce-Pine-Fir #1
10-4
16-3
21-0
25-8
Note a
9-10
14-4
18-2
22-3
25-9
Spruce-Pine-Fir #2
10-4
16-3
21-0
25-8
Note a
9-10
14-4
18-2
22-3
25-9
Spruce-Pine-Fir #3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
16
Douglas Fir-Larch SS
10-5
16-4
21-7
Note a
Note a
10-5
16-0
20-3
24-9
Note a
Douglas Fir-Larch #1
10-0
15-4
19-5
23-9
Note a
9-1
13-3
16-10
20-7
23-10
Douglas Fir-Larch #2
9-10
14-4
18-2
22-3
25-9
8-6
12-5
15-9
19-3
22-4
Douglas Fir-Larch #3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
11-11
14-6
16-10
Hem-Fir SS
9-10
15-6
20-5
Note a
Note a
9-10
15-6
19-11
24-4
Note a
Hem-Fir #1
9-8
14-11
18-11
23-2
Note a
8-10
12-11
16-5
20-0
23-3
Hem-Fir #2
9-2
14-2
17-11
21-11
25-5
8-5
12-3
15-6
18-11
22-0
Hem-Fir #3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
U-U
14-6
16-10
Southern Pine SS
10-3
16-1
21-2
Note a
Note a
10-3
16-1
21-2
Note a
Note a
Southern Pine #1
10-0
15-9
20-10
25-10
Note a
10-0
15-0
18-10
22-4
Note a
Southern Pine #2
9-10
15-1
19-5
23-2
Note a
9-1
13-0
16-10
20-1
23-7
Southern Pine #3
7-11
11-8
14-10
17-6
20-11
6-10
10-1
12-10
15-2
18-1
Spruce-Pine-Fir SS
9-8
15-2
19-11
25-5
Note a
9-8
14-10
18-10
23-0
Note a
Spruce-Pine-Fir #1
9-5
14-4
18-2
22-3
25-9
8-6
12-5
15-9
19-3
22-4
Spruce-Pine-Fir #2
9-5
14-4
18-2
22-3
25-9
8-6
12-5
15-9
19-3
22-4
Spruce-Pine-Fir #3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
11-11
14-6
16-10
09
(continued)
O
O
o
09
00
TABLE 2308.10.3(1)— continued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Roof Live Load = 20 pounds per square foot, Ceiling Not Attaclied to Rafters, L/A :
180)
RAFTER
SPACING
finches)
SPECIES AND GRADE
DEAD LOAD
= 10 Dounds per sauare foot
DEAD LOAD
= 20 Dounds oer sauare foot
2x4
2x6
2x8 1 2x10
2x12
2x4
2x6
2x8 1 2x10
2x12
Maximum rafter soans
(ft. - In.)
(ft. - in.)
m. - in.>
m. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft. - in.)
(ft. -in.)
19.2
Douglas Fir-Larch
SS
9-10
15-5
20-4
25-11
Note a
9-10
14-7
18-6
22-7
Note a
Douglas Fir-Larch
#1
9-5
14-0
17-9
21-8
25-2
8-4
12-2
15-4
18-9
21-9
Douglas Fir-Larch
#2
8-11
13-1
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Douglas Fir-Larch
#3
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
^ 15-5
Hem-Fir
SS
9-3
14-7
19-2
24-6
Note a
9-3
14-4
18-2
22-3
25-9
Hem-Fir
#1
9-1
13-8
17-4
21-1
24-6
8-1
11-10
15-0
18-4
21-3
Hem-Fir
#2
8-8
12-U
16-4
20-0
23-2
7-8
11-2
14-2
17-4
20-1
Hem-Fir
#3
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
15-5
Southern Pine
SS
9-8
15-2
19-11
25-5
Note a
9-8
15-2
19-11
25-5
Note a
Southern Pine
#1
9-5
14-10
19-7
23-7
Note a
9-3
13-8
17-2
20-5
24-4
Southern Pine
#2
9-3
13-9
17-9
21-2
24-10
8-4
11-11
15-4
18-4
21-6
Southern Pine
#3
7-3
10-8
13-7
16-0
19-1
6-3
9-3
11-9
13-10
16-6
Spruce-Pine-Fir
SS
9-1
14-3
18-9
23-11
Note a
9-1
13-7
17-2
21-0
24-4
Spruce-Pine-Fir
#1
8-10
13-1
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Spruce-Pine-Fir
#2
8-10
13-1
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Spruce-Pine-Fir
#3
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
15-5
24
Douglas Fir-Larch
SS
9-1
14-4
18-10
23-4
Note a
8-11
13-1
16-7
20-3
23-5
Douglas Fir-Larch
#1
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Douglas Fir-Larch
#2
8-0
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Douglas Fir-Larch
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
11-10
13-9
Hem-Fir
SS
8-7
13-6
17-10
22-9
Note a
8-7
12-10
16-3
19-10
23-0
Hem-Fir
#1
8-4
12-3
15-6
18-11
21-11
7-3
10-7
13-5
16-4
19-0
Hem-Fir
#2
7-11
11-7
14-8
17-10
20-9
6-10
10-0
12-8
15-6
17-11
Hem-Fir
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
11-10
13-9
Southern Pine
SS
8-11
14-1
18-6
23-8
Note a
8-11
14-1
18-6
22-11
Note a
Southern Pine
#1
8-9
. 13-9
17-9
21-1
25-2
8-3
12-3
15-4
18-3
21-9
Southern Pine
#2
8-7
12-3
15-10
18-11
22-2
7-5
10-8
13-9
16-5
19-3
Southern Pine
#3
6-5
9-6
12-1
14-4
17-1
5-7
8-3
10-6
12-5
14-9
Spruce-Pine-Fir
SS
8-5
13-3
17-5
21-8
25-2
8-4
12-2
15-4
18-9
21-9
Spruce-Pine-Fir
#1
8-0
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Spruce-Pine-Fir
#2
8-0
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Spruce-Pine-Fir
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
n-to
13-9
o
o
o
G
m
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, I pound per square foot = 47.9
a. Span exceeds 26 feet in length. Check sources for availability of lumber in
N/m'.
lengths greater than 20 feet.
O
o
D
TABLE 2308.10.3(2)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Roof Live Load = 20 pounds per square foot, Ceiling Not Attached to Rafters, L/A = 240)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD
= 10 Dounds per square foot
DEAD LOAD = 20 pounds per square foot
2x4
2x6
2x8 2x10
2x12
2x4
2x6
2x8
2x10
2x12
Maximum rafter spans
m.-in,)
m. - in.)
m. - in.)
(ft. - In.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
12
Douglas Fir-Larch
SS
10-5
16-4
21-7
Note a
Note a
10-5
16-4
21-7
Note a
Note a
Douglas Fir-Larch
#1
10-0
15-9
20-10
Note a
Note a
10-0
15-4
19-5
23-9
Note a
Douglas Fir-Larch
#2
9-10
15-6
20-5
25-8
Note a
9-10
14-4
18-2
22-3
25-9
Douglas Fir-Larch
#3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Hem-Fir
SS
9-10
15-6
20-5
Note a
Note a
9-10
15-6
20-5
Note a
Note a
Hem-Fir
#1
9-8
15-2
19-11
25-5
Note a
9-8
14-11
18-11
23-2
Note a
Hem-Fir
#2
. 9-2
14-5
19-0
24-3
Note a
9-2
14-2
17-11
21-11
25-5
Hem-Fir
#3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Southern Pine
SS
10-3
16-1
21-2
Note a
Note a
10-3
16-1
21-2
Note a
Note a
Southern Pine
#1
10-0
15-9
20-10
Note a
Note a
10-0
15-9
20-10
25-10
Note a
Southern Pine
#2
9-10
15-6
20-5
Note a
Note a
9-10
15-1
19-5
23-2
Note a
Southern Pine
#3
9-1
13-6
17-2
20-3
24-1
7-11
11-8
14-10
17-6
20-11
Spruce-Pine-Fir
SS
9-8
15-2
19-11
25-5
Note a
9-8
15-2
19-11
25-5
Note a
Spruce-Pine-Fir
#1
9-5
14-9
19-6
24-10
Note a
9-5
14-4
18-2
22-3
25-9
Spruce-Pine-Fir
#2
9-5
14-9
19-6
24-10
Note a
9-5
14-4
18-2
22-3
25-9
Spruce-Pine-Fir
#3
8-7
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
16
Douglas Fir-Larch
SS
9-6
14-11
19-7
25-0
Note a
9-6
14-11
19-7
24-9
Note a
Douglas Fir-Larch
#1
9-1
14-4
18-11
23-9
Note a
9-1
13-3
16-10
20-7
23-10
Douglas Fir-Larch
#2
8-11
14-1
18-2
22-3.
25-9
8-6
12-5
15-9
19-3
22-4
Douglas Fir-Larch
#3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
11-11
14-6
16-10
Hem-Fir
SS
8-11
14-1
18-6
23-8
Note a
8-11
14-1
18-6
23-8
Note a
Hem-Fir
#1
8-9
13-9
18-1
23-1
Note a
8-9
12-11
.16-5
20-0
23-3
Hem-Fir
#2
8-4
13-1
17-3
21-11
25-5
8-4
12-3
15-6
18-11
22-0
Hem-Fir
#3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
11-11
14-6
16-10
Southern Pine
SS
9-4
14-7
19-3
24-7
Note a
9-4
14-7
19-3
24-7
Note a
Southern Pine
#1
9-1
14-4
18-11
24-1
Note a
9-1
14-4
18-10
22-4
Note a
Southem Pine
#2
8-11
14-1
18-6
23-2
. Note a
8-11
13-0
16-10
20-1
23-7
Southern Pine
#3
7-11
11-8
14-10
17-6
20-11
6-10
10-i
12-10
15-2
18-1
Spruce-Pine-Fir
SS
8-9
13-9
18-1
. 23-1
Note a
8-9
13-9
18-1
23-0
Note a
Spruce-Pine-Fir
#1
8-7
13-5
17-9
22-3
25-9
8-6
12-5
15-9
19-3
22-4
Spruce-Pine-Fxr
#2
8-7
13-5
17-9
22-3
25-9
8-6
12-5
15-9
19-3
22-4
Spruce-Pine-Fir
#3
7-5
10-10
13-9
16-9
19-6
6-5
9-5
11-11
14-6
16-10
00
(O
(continued)
5
O
O
o
CO
(O
o
TABLE 2308.10.3(2)— continued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Roof Live Load = 20 pounds per square foot, Ceiling Not Attached to Rafters, L/A = 240)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD = 10 pounds per square foot
DEAD LOAD = 20 pounds per sauare foot 1
2x4
2x6
2x8 1 2x10
2x12
2x4
2x6
2x8
2x10
2x12
Maximum raft
Bf spans 1
(ft. - in.)
(ft. - In.)
(ft. - In.)
m. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - In.)
(ft. - in.)
19.2
Douglas Fir-Larch
SS
8-11
14-0
18-5
23-7
Note a
8-11
14-0
18-5
22-7
Note a
Douglas Fir-Larch
#1
8-7
13-6
17-9
21-8
25-2
8-4
12-2
15-4
18-9
21-9
Douglas Fir-Larch
#2
8-5
13-1
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Douglas Fir-Larch
#3
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
15-5
Hem-Fir
SS
8-5
13-3
17-5
22-3
Note a
8-5
13-3
17-5
22-3
25-9
Hem-Fir
#1
8-3
12-11
17-1
21-1
24-6
8-1
11-10
15-0
18-4
21-3
Hem-Fir
#2
7-10
12-4
16-3
20-0
23-2
7-8
11-2
14-2
17-4
20-1
Hem-Fir
#3
■
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
15-5
Southern Pine
SS
8-9
13-9
18-1
23-1
Note a
8-9
13-9
18-1
23-1
Note a
Southern Pine
#1
8-7
13-6
17-9
22-8
Note a
8-7
13-6
17-2
20-5
24-4
Southern Pine
#2
8-5
13-3
17-5
21-2
24-10
8-4
11-11
15-4
18-4
21-6
Southern Pine
#3
7-3
10-8
13-7
16-0
19-1
6-3
9-3
11-9
13-10
16-6
Spruce-Pine-Fir
SS
8-3
12-11
17-1
21-9
Note a
8-3
12-11
17-1
21-0
24-4
Spruce-Pine-Fir
#1
8-1
12-8
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Spruce-Pine-Fir
#2
8-1
12-8
16-7
20-3
23-6
7-9
11-4
14-4
17-7
20-4
Spruce-Pine-Fir
#3
6-9
9-11
12-7
15-4
17-9
5-10
8-7
10-10
13-3
15-5
24
Douglas Fir-Larch
SS
8-3
13-0
17-2
21-10
Note a
8-3
13-0
16-7
20-3
23-5
Douglas Fir-Larch
#1
8-0
12-6
15-10
19-5
22-6
7-5
10-10
13-9
16-9
19-6
Douglas Fir-Larch
#2
7-10
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Douglas Fir-Larch
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
11-10
13-9
Hem-Fir
SS
7-10
12-3
16-2
20-8
25-1
7-10
12-3
16-2
19-10
23-0
Hem-Fir
#1
7-8
12-0
15-6
18-11
21-11
7-3
10-7
13-5
16-4
19-0
Hem-Fir
#2
7-3
11-5
14-8
17-10
20-9
6-10
10-0
12-8
15-6
17-11
Hem-Fir
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
11-10
13-9
Southern Pine
SS
8-1
12-9
16-10
21-6
Note a
8-1
12-9
16-10
21-6
Note a
Southem Pine
#1
8-0
12-6
16-6
21-1
25-2
8-0
12-3
15-4
18-3
21-9
Southem Pine
#2
7-10
12-3
15-10
18-11
22-2
7-5
10-8
13-9
16-5
19-3
Southem Pine
#3
6-5
9-6
12-1
14-4
17-1
5-7
8-3
10-6
12-5
14-9
Spruce-Pine-Fir
SS
7-8
12-0
15-10
20-2
24-7
7-8
12-0
15-4
18-9
21-9
Spruce-Pine-Fir
#1
7-6
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Spruce-Pine-Fir
#2
7-6
11-9
14-10
18-2
21-0
6-11
10-2
12-10
15-8
18-3
Spruce-Pine-Fir
#3
6-1
8-10
11-3
13-8
15-11
5-3
7-8
9-9
11-10
13-9
o
o
o
o
m
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
a. Span exceeds 26 feet in length. Check
mm, 1 pound per square foot = 47.9
sources for availability of lumber in
lengths greater than 20 feet.
O
o
a
o
TABLE 2308.10.3(3)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 30 pounds per square foot, Ceiling Not Attached to Rafters, L/A =
180)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD
= 10 pounds Der square foot
DEAD LOAC
= 20 Dounds oer sauare foot
2x4
2X6
2x8 1 2x10
2x12
2x4
2x6
2x8 I 2x10
2x12
Maximum rafter scans
(ft. - in.)
(ft. - in.^
rft.-m.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - In.)
(ft. -in.)
(ft. - in.)
(ft. - in.)
12
Douglas Fir-Larch
SS
10-0
15-9
20-9
Note a
Note a
10-0
15-9
20-1
24-6
Note a
Douglas Fir-Larch
#1
9-8
14-9
18-8
22-9
Note a
9-0
13-2
16-8
20-4
23-7
Douglas Fir-Larch
#2
9-5
13-9
17-5
21-4
24-8
8-5
12-4
15-7
19-1
22-1
Douglas Fir-Larch
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Hem-Fir
SS
9-6
14-10
19-7
25-0
Note a
9-6
14-10
19-7
24-1
Note a
Hem-Fir
#1
9-3
14-4
18-2
22-2
25-9
8-9
12-10
16-3
19-10
23-0
Hem-Fir
#2
8-10
13-7
17-2
21-0
24-4
8-4
12-2
15-4
18-9
21-9
Hem-Fir
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Southern Pine
SS
9-10
15-6
20-5
Note a
Note a
9-10
15-6
20-5
Note a
Note a
Southern Pine
#1
9-8
15-2
20-0
24-9
Note a
9-8
14-10
18-8
22-2
Note a
Southern Pine
#2
9-6
14-5
18-8
22-3
Note a
9-0
12-11
16-8
19-11
23-4
Southern Pine
#3
7-7
11-2
14-3
16-10
20-0
6-9
10-0
12-9
15-1
17-11
Spruce-Pine-Fir
SS
9-3
14-7
19-2
24-6
Note a
9-3
14-7
18-8
22-9
Note a
Spruce-Pine-Fir
#1
9-1
13-9
17-5
21-4
24-8
8-5
12-4
15-7
19-1
22-1
Spruce-Pine-Fir
#2
9-1
13-9
17-5
21-4
24-8
8-5
12-4
15-7
19-1
22-1
Spruce-Pine-Fir
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
16
Douglas Fir-Larch
SS
9-1
14-4
18-10
23-9
Note a
9-1
13-9
17-5
21-3
24-8
Douglas Fir-Larch
#1
8-9
12-9
16-2
19-9
22-10
7-10
11-5
14-5
17-8
20-5
Douglas Fir-Larch
#2
8-2
11-11
15-1
18-5
21-5
7-3
10-8
13-6
16-6
19-2
Douglas Fir-Larch
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
Hem-Fir
SS
8-7
13-6
17-10
22-9
Note a
8-7
13-6
17-1
20-10
24-2
Hem-Fir
#1
8-5
12-5
15-9
19-3
22-3
7-7
11-1
14-1
17-2
19-11
Hem-Fir
#2
8-0
11-9
14-11
18-2
21-1
7-2
10-6
13-4
16-3
18-10
Hem-Fir
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
Southern Pine
SS
8-11
14-1
18-6
23-8
Note a
8-11
14-1
18-6
23-8
Note a
Southern Pine
#1
8-9
13-9
18-1
21-5
25-7
8-8
12-10
16-2
19-2
22-10
Southern Pine
#2
8-7
12-6
16-2
19-3
22-7
7-10
11-2
14-5
17-3
20-2
Southern Pine
#3
6-7
9-8
12-4
14-7
17-4
5-10
8-8
11-0
13-0
15-6
Spruce-Pine-Fir
SS
8-5
13-3
17-5
22-1
25-7
8-5
12-9
16-2
19-9
22-10
Spruce-Pine-Fir
#1
8-2
11-11
15-1
18-5
21-5
7-3
10-8
13-6
16-6
19-2
Spruce-Pine-Fir
#2
8-2
11-11
15-1
18-5
21-5
7-3
10-8
13-6
16-6
19-2
Spruce-Pine-Fir
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
CO
(continued)
O
o
o
TABLE 2308.10.3(3)— continued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 30 pounds per squarefoot, Ceiling Not Attached to Rafters, A/A = 180)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAC
- 1 pounds per sauare foot ■
DEAD LOAD = 20 pounds per sauare foot
2x4
2x6
2x8 i 2x10
2x12
2x4
2x6
2x8 1 2x10
2x12
Maximum rafter scans
(ft. - in.)
(ft. -in.)
m. - in.)
m. - in.)
m. - in.)
m. - in.)
m. - in.)
m.-in.)
m.-in.)
m. - in.)
19.2
Doufilas Fir-Larch
SS
8-7
13-6
17-9
21-8
25-2
8-7
12-6
15-10
19-5
22-6
Douglas Fir-Larch
#1
7-11
11-8
14-9
18-0
20-11
7-1
10-5
13-2
16-1
18-8
Douglas Fir-Larch
#2
7-5
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Douglas Fir-Larch
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
Hem-Fir
SS
8-1
12-9
16-9
21-4
24-8
8-1
12-4
15-7
19-1
22-1
Hem-Fir
#1
7-9
11-4
14-4
17-7
. 20-4
6-11
10-2
12-10
15-8
18-2
Hem-Fir
#2
7-4
10-9
13-7
16-7
19-3
6-7
9-7
12-2
14-10
17-3
Hem-Fir
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
Southern Pine
SS
8-5
13-3
17-5
22-3
Note a
8-5
13-3
17-5
22-0
25-9
Southern Pine
#1
8-3
13-0
16-6
19-7
23-4
7-11
11-9
14-9
17-6
20-11
Southern Pine
#2
7-11
11-5
14-9
17-7
20-7
7-1
10-2
13-2
15-9
18-5
Southern Pine
#3
6-0
8-10
11-3
13-4
15-10
5-4
7-11
10-1
11-11
14-2
Spruce-Pine-Fir
SS
7-11
12-5
16-5
20-2
23-4
7-11
11-8
14-9
18-0
20-11
Spruce-Pine-Fir
#1
7-5
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Spruce-Pine-Fir
#2
7-5
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Spruce-Pine-Fir
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
24
Douglas Fir-Larch
SS
7-1 i
12-6
15-10
19-5
22-6
7-8
11-3
14-2
17-4
20-1
Douglas Fir-Larch
#1
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Douglas Fir-Larch
#2
6-8
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Douglas Fir-Larch
#3
5-0
7-4
9-4
il-5
13-2
4-6
6-7
8-4
10-2
11-10
Hem-Fir
SS
7-6
11-10
15-7
19-1
22-1
7-6
11-0
13-11
17-0
19-9
Hem-Fir
#1
6-11
10-2
12-10
15-8
18-2
6-2
9-1
11-6
14-0
16-3
Hem-Fir
#2
6-7
9-7
12-2
14-10
17-3
5-10
8-7
10-10
13-3
15-5
Hem-Fir
#3
5-0
7-4
9-4
11-5
13-2
4-6
6-7
8-4
10-2
11-10
Southern Pine
SS
7-10
12-3
16-2
20-8
25-1
7-10
12-3
16-2
19-8
23-0
Southern Pine
#1
7-8
11-9
14-9
17-6
20-11
7-1
10-6
13-2
15-8
18-8
Southern Pine
#2
7-1
10-2
13-2 ^
15-9
18-5
6-4
9-2
11-9
14-1
16-6
Southern Pine
#3
5-4
7-11
10-1
11-11
14-2
4-9
7-1
9-0
10-8
12-8
Spruce-Pine-Fir
SS
7-4
11-7
14-9
18-0
20- n
7-1
10-5
13-2
16-1
18-8
Spruce-Pine-Fir
#1
6-8
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Spruce-Pine-Fir
#2
6-8
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Spruce-Pine-Fir
#3
5-0
7-4
9-4
11-5
13-2
4-6
6-7
8-4
10-2
11-10
o
o
o
D
m
For SL 1 inch = 25.4 mm, 1 foot = 304.8
a. Span exceeds 26 feet in length. Check
mm, 1 pound per square foot = 47.9
sources for availability of lumber in
lengths greater than 20 feet.
O
o
o
to
o
TABLE 2308.10.3(4)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 50 pounds per square foot, Ceiling Not Attached to Rafters, L/A
= 180)
RAFTER
SPACING
finches)
SPECIES AND GRADE
DEAD LOAD = 10 pounds per sauare foot
DEAD LOAD = 20 Dounds Der sauare foot
2x4 1 2x6 1 2x8 1 2x10 1 2x12
2x4 1 2x6 1 2x8 1 2x10 1 2x12
Maximum rafter soans
m. - in.)
(ft. - in.)
m.-m.)
(ft. - in.)
(ft., in.)
(ft. -in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
12
Douglas Fir-Larch SS
8-5
13-3
17-6
22-4
26-0
8-5
13-3
17-0
20-9
24-10
Douglas Fir-Larch #1
8-2
12-0
15-3
18-7
21-7
7-7
11-2
14-1
17-3
20-0
Douglas Fir-Larch #2
7-8
11-3
14-3
17-5
20-2
7-1
10-5
13-2
16-1
18-8
Douglas Fir-Larch #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Hem-Fir SS
8-0
12-6
16-6
21-1
25-6
8-0
12-6
16-6
20-4
23-7
Hem-Fir #1
7-10
11-9
14-10
18-1
21-0
7-5
10-10
13-9
16-9
19-5
Hem-Fir #2
7-5
11-1
14-0
17-2
19-11
7-0
10-3
13-0
15-10
18-5
Hem-Fir #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Southern Pine SS
8-4
13-0
17-2
21-11
Note a
8-4
13-0
17-2
21-11
Note a
Southern Pine #1
8-2
12-10
16-10
20-3
24-1
8-2
12-6
15-9
18-9
22-4
Southern Pine #2
8-0
11-9
15-3
18-2
21-3
7-7
10-11
14-1
16-10
19-9
Southern Pine #3
6-2
9-2
11-8
13-9
16-4
5-9
8-5
10-9
12-9
15-2
Spruce-Pine-Fir SS
7-10
12-3
16-2
20-8
24-1
7-10
12-3
15-9
19-3
22-4
Spruce-Pine-Fir #1
7-8
11-3
14-3
17-5
20-2
7-1
10-5
13-2
16-1
18-8
Spruce-Pine-Fir #2
7-8
11-3
14-3
17-5
20-2
7-1
10-5
13-2 .
16-1
18-8
Spruce-Pine-Fir #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
16
Douglas Fir-Larch SS
7-8
12-1
15-10
19-5
22-6
7-8
11-7
14-8
17-11
20-10
Douglas Fir-Larch #1
7-1
10-5
13-2
16-1
18-8
6-7
9-8
12-2
14-11
17-3
Douglas Fir-Larch #2
6-8
9-9
12-4
15-1
17-6
6-2
9-0
11-5
13-11
16-2
Douglas Fir-Larch #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
Hem-Fir SS
7-3
11-5
15-0
19-1
22-1
7-3
11-5
14-5
17-8
20-5
Hem-Fir #1
6-11
10-2
12-10
15-8
18-2
6-5
9-5
11-11
14-6
16-10
Hem-Fir #2
6-7
9-7
12-2
14-10
17-3
6-1
8-11
11-3
13-9
15-11
Hem-Fir #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
Southern Pine SS
7-6
11-10
15-7
19-11
24-3
7-6
11-10
15-7
19-11
23-10
Southern Pine #1
7-5
11-7
14-9
17-6
20-11
7-4
10-10
13-8
16-2
19-4
Southern Pine #2
7-1
10-2
13-2
15-9
18-5
6-7
9-5
12-2
14-7
17-1
Southern Pine #3
5-4
7-11
10-1
11-11
14-2
4-11
7-4
9-4
11-0
13-1
Spruce-Pine-Fir SS
7-1
11-2
14-8
18-0
20-11
7-1
10-9
13-8
16-8
19-4
Spruce-Pine-Fir #1
6-8
9-9
12-4
15-1
17-6
6-2
9-0
11-5
13-11
16-2
Spruce-Pine-Fir #2
6-8
9-9
12-4
15-1
17-6
6-2
9-0
11-5
13-11
16-2
Spruce-Pine-Fir #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
CO
CO
(continued)
O
O
o
TABLE 2308.10.3(4)— continued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 50 pounds per square foot, Ceiling Not Attached to Rafters, L/A
= 180)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD
= 10 pounds per square foot
DEAD LOAD =
2x4
2x6
2x8 1 2x10
2x12
2x4
2x6
2x8 1 2x10
2x12
Maximum rafter spans
(ft. -in.)
(ft. - in.)
m. - in.)
m. - in.)
m. - in.)
(ft. - in.)
m. ■ In.)
m. - in.)
m. - In.)
m.-ln.)
19.2
Douglas Fir-Larch
SS
7-3
11-4
14-6
17-8
20-6
7-3
10-7
13-5
16-5
19-0
Douglas Fir-Larch
#1
6-6
9-6
12-0
14-8
17-1
6-0
8-10
11-2
13-7
15-9
Douglas Fir-Larch
#2
6-1
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Douglas Fir-Larch
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
Hem-Fir
SS
6-10
10-9
14-2
17-5
20-2
6-10
10-5
13-2
16-1
18-8
Hem-Fir
#1
6-4
9-3
11-9
14-4
16-7
5-10
8-7
10-10
13-3
15-5
Hem-Fir
#2
6-0
8-9
11-1
13-7
15-9
5-7
8-1
10-3
12-7
14-7
Hem-Fir
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
Southern Pine
SS
7-1
11-2
14-8
18-9
22-10
7-1
11-2
14-8
18-7
21-9
Southern Pine
#1
7-0
10-8
13-5
16-0
19-1
6-8
9-11
12-5
14-10
17-8
Southern Pine
#2
6-6
9-4
12-0
14-4
16-10
6-0
8-8
11-2
13-4
15-7
Southern Pine
#3
4-11
7-3
9-2
10-10
12-11
4-6
6-8
8-6
10-1
12-0
Spruce-Pine-Fir
SS
6-8
10-6
13-5
16-5
19-1
6-8
9-10
12-5
15-3
17-8
Spruce-Pine-Fir
#1
6-1
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Spnice-Pine-Fir
#2
6-1
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Spruce-Pine-Fir
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
24
Douglas Fir-Larch
SS
6-8
10-3
13-0
15-10
18-4
6-6
9-6
12-0
14-8
17-0
Douglas Fir-Larch
#1
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Douglas Fir-Larch
#2
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Douglas Fir-Larch
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
Hem-Fir
SS
6-4
9-11
12-9
15-7
18-0
6-4
9-4
11-9
14-5
16-8
Hem-Fir
#1
5-8
8-3
10-6
12-10
14-10
5-3
7-8
9-9
11-10
13-9
Hem-Fir
#2
5-4
7-10
9-11
12-1
14-1
4-11
7-3
9-2
11-3
13-0
Hem-Fir
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
Southern Pine
SS
6-7
10-4
13-8
17-5
21-0
6-7
10-4
13-8
16-7
19-5
Southern Pine
#1
6-5
9-7
12-0
14-4
17-1
6-0
8-10
11-2
13-3
15-9
Southern Pine
#2
5-10
8-4
10-9
12-10
15-1
5-5
7-9
10-0
11-11
13-11
Southern Pine
#3
4-4
6-5
8-3
9-9
11-7
4-1
6-0
7-7
9-0
10-8
Spruce-Pine-Fir
SS
6-2
9-6
12-0
14-8
17-1
6-0
8-10
11-2
13-7
15-9
Spruce-Pine-Fir
#1
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Spruce-Pine-Fir
#2
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Spruce-Pine-Fir
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
o
o
o
a
m
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.9 N/m\
a. Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
O
O
D
o
TABLE 2308.10.3(5)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 30 pounds per square foot, Ceiling Attached to Rafters, L/A =
240)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAC
t = 10 pounds per square foot
DEAD LOAE
= 20 Dounds oer square foot
2x4
2x6
2x8 1 2x10
2x12
2x4
2x6
2x8 i 2x10
2x12
Maximum r
after scans
(n.-\n.)
(ft. - \r\.)
(ft. -in.)
(ft.-in.)
(ft. - in.>
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft. -in.)
(ft. -In.)
12
Douglas Fir-Larch
SS
9-1
14-4
18-10
24-1
Note a
9-1
14-4
18-10
24-1
Note a
Douglas Fir-Larch
#1
8-9
13-9
18-2
22-9
Note a
8-9
13-2
16-8
20-4
23-7
Douglas Fir-Larch
#2
8-7
13-6
17-5
21-4
24-8
8-5
12-4
15-7
19-1
22-1
Douglas Fir-Larch
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Hem-Fir
SS
8-7
13-6
17-10
22-9
Note a
8-7
13-6
17-10
22-9
Note a
Hem-Fir
#1
8-5
13-3
17-5
22-2
25-9
8-5
12-10
16-3
19-10
23-0
Hem-Fir
#2
8-0
12-7
16-7
21-0
24-4
8-0
12-2
15-4
18-9
21-9
Hem-Fir
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Southern Pine
SS
8-11
14-1
18-6
23-8
Note a
8-11
14-1
18-6
23-8
Note a
Southern Pine
#1
8-9
13-9
18-2
23-2
Note a
8-9
13-9
18-2
22-2
Note a
Southern Pine
#2
8-7
13-6
17-10
22-3
Note a
8-7
12-11
16-8
19-11
23-4
Southern Pine
#3
7-7
11-2
14-3
16-10
20-0
6-9
10-0
12-9
15-1
17-11
Spruce-Pine-Fir
SS
8-5
13-3
17-5
22-3
Note a
8-5
13-3
17-5
22-3
Note a
Spruce-Pine-Fir
#1
8-3
12-11
17-0
21-4
24-8
8-3
12-4
15-7
19-1
22-1
Spruce-Pine-Fir
#2
8-3
12-11
17-0
21-4
24-8
8-3
12-4
15-7
19-1
22-1
Spruce-Pine-Fir
#3
7-1
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
16
Douglas Fir-Larch
SS
8-3
13-0
17-2
21-10
Note a
8-3
13-0
17-2
21-3
24-8
Douglas Fir-Larch
#1
8-0
12-6
16-2
19-9
22-10
7-10
11-5
14-5
17-8
20-5
Douglas Fir-Larch
#2
7-10
11-11
15-1
18-5
21-5
7-3
10-8
L 13-6
16-6
19-2
Douglas Fir-Larch
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
Hem-Fir
SS
7-10
12-3
16-2
20-8
25-1
7-10
12-3
16-2
20-8
24-2
Hem-Fir
#1
7-8
12-0
15-9
19-3
22-3
7-7
11-1
14-1
17-2
19-11
Hem-Fir
#2
7-3
11-5
14-11
18-2
21-1
7-2
10-6
13-4
16-3
18-10
Hem-Fir
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
Southern Pine
SS
8-1
12-9
16-10
21-6
Note a
8-1
12-9
16-10
21-6
Note a
Southern Pine
#1
8-0
12-6
16-6
21-1
25-7 _J
8-0
12-6
16-2
19-2
22-10
Southern Pine
#2
7-10
12-3
16-2
19-3
22-7
7-10
11-2
14-5
17-3
20-2
Southern Pine
#3
6-7
9-8
12-4
14-7
17-4
5-10
8-8
11-0
13-0
15-6
Spruce-Pine-Fir
SS
7-8
12-0
15-10
20-2
24-7
7-8
12-0
15-10
19-9
22-10
Spruce-Pine-Fir
#1
7-6
11-9
15-1
18-5
21-5
7-3
10-8
13-6
16-6
19-2
Spruce-Pine-Fi
#2
7-6
11-9
15-1
18-5
21-5
7-3
10-8
13-6
16-6
19-2
Spruce-Pine-Fi
#3
6-2
9-0
11-5
13-11
16-2
5-6
8-1
10-3
12-6
14-6
(continued)
c;i
O
O
D
TABLE 2308.10.3(5)— continued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 30 pounds per square foot, Ceifing Attached to Rafters, L/A :
240)
RAh 1 bK
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD
= 10 pounds per square foot
DEAD LOAD = 20 Dounds oer sauare foot
2x4
■ ■
2x6
2x8 1 2x10
2x12
2x4
2x6
2x8 1 2x10
2x12
Maximum r
after soans
m.-in.)
(ft. -in.)
m. - in.)
m.-in.)
m.-in.)
m. - in.)
m.-in.)
m.-ln.)
m. - in.)
m.-in.)
19.2
Douglas Fir-Larch
SS
7-9
12-3
16-1
20-7
25-0
7-9
12-3
15-10
19-5
22-6
Douglas Fir-Larch
#1
7-6
11-8
14-9
18-0
20-11
7-1
10-5
13-2
16-1
18-8
Douglas Fir-Larch
#2
7-4
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Douglas Fir-Larch
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
Hem-Fir
SS
7-4
11-7
15-3
19-5
23-7
7-4
11-7
15-3
19-1
22-1
Hem-Fir
#1
7-2
11-4
14-4
17-7
20-4
6-11
10-2
12-10
15-8
18-2
Hem-Fir
#2
6-10
10-9
13-7
16-7
19-3
6-7
9-7
12-2
14-10
17-3
Hem-Fir
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
Southern Pine
SS
7-8
12-0
15-10
20-2
24-7
7-8
12-0
15-10
20-2
24-7
Southern Pine
#1
7-6
11-9
15-6
19-7
23-4
7-6
11-9
14-9
17-6
20-11
Southern Pine
#2
7-4
11-5
14-9
17-7
20-7
7-1
10-2
13-2
15-9
18-5
Southern Pine
#3
6-0
8-10
11-3
13-4
15-10
5-4
7-11
10-1
11-11
14-2
Spruce-Pine-Fir
SS
7-2
11-4
14-11
19-0
23-1
7-2
11-4
14-9
18-0
20-11
Spruce-Pine-Fir
#1
7-0
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Spruce-Pine-Fir
#2
7-0
10-11
13-9
16-10
19-6
6-8
9-9
12-4
15-1
17-6
Spruce-Pine-Fir
#3
5-7
8-3
10-5
12-9
14-9
5-0
7-4
9-4
11-5
13-2
24
Douglas Fir-Larch
SS
7-3
11-4
15-0
19-1
22-6
7-3
11-3
14-2
17-4
20-1
Douglas Fir-Larch
#1
7-0
10-5
13-2
16-1
18-8
6-4
9-4
11-9
14-5
16-8
Douglas Fir-Larch
#2
6-8
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Douglas Fir-Larch
#3
5-0
7-4
9-4
11-5
13-2
4-6
6-7
8-4
10-2
11-10
Hem-Fir
SS
6-10
10-9
14-2
18-0
21-11
6-10
10-9
13-11
17-0
19-9
Hem-Fir
#1
6-8
10-2
12-10
15-8
18-2
6-2
9-1
11-6
14-0
16-3
Hem-Fir
#2
6-4
9-7
12-2
14-10
17-3
5-10
8-7
10-10
13-3
15-5
Hem-Fir
#3
5-0
7-4
9-4
11-5
13-2
4-6
6-7
8-4
10-2
11-10
Southern Pine
SS
7-1
11-2
14-8
18-9
22-10
7-1
11-2
14-8
18-9
22-10
Southern Pine
#1
7-0
10-11
14-5
17-6
20-11
7-0
10-6
13-2 "
15-8
18-8
Southern Pine
#2
6-10
10-2
13-2
15-9
18-5
6-4
9-2
11-9
14-1
16-6
Southern Pine
#3
5-4
7-11
10-1
11-11
14-2
4-9
7-1
9-0
10-8
12-8
Spruce-Pine-Fir
SS
6-8
10-6
13-10
17-8
20-11
6-8
10-5
13-2
16-1
18-8
Spruce- Pine-Fir
#1
6-6
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Spruce-Pine-Fir
#2
6-6
9-9
12-4
15-1
17-6
5-11
8-8
11-0
13-6
15-7
Spruce-Pine-Fir
#3
5-0
7-4
9-4
11-5
13-2
4-6
6-7
8-4
10-2
11-10
o
o
o
a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8
a. Span exceeds 26 feet in length. Check
mm, 1 pound per square foot = 47.9
sources for availability of lumber in
N/m^
lengths greater than 20 feet.
O
o
o
o
TABLE 2308.10.3(6)
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 50 pounds per square foot, Ceiling Attached to Rafters, UA :
240)
RAFTER
SPACING
(Inches)
SPECIES AND GRADE
DEAD LOAD = 10 oounds per sauare foot
DEAD LOAD = 20 pounds per sauare foot
2x4 1 2x6 1 2x8 1 2x10 1 2x12
2x4 1 2x6 1 2x8 1 2x10 1 2x12
Maximum rafter scans
m.-in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft. -In.)
(ft. - in.)
(ft. -in.)
(ft. -in.)
(ft. - in.)
12
Douglas Fir-Larch SS
7-8
12-1
15-11
20-3
24-8
7-8
12-1
15-11
20-3
24-0
Douglas Fir-Larch #1
7-5
11-7
15-3
18-7
21-7
7-5
11-2
14-1
17-3
20-0
Douglas Fir-Larch #2
7-3
11-3
14-3
17-5
20-2
7-1
10-5
13-2
16-1
18-8
Douglas Fir-Larch #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Hem-Fir SS
7-3
11-5
15-0
19-2
23-4
7-3
11-5
15-0
19-2
23-4
Hem-Fir #1
7-1
11-2
14-8
18-1
21-0
7-1
10-10
13-9
16-9
19-5
Hem-Fir #2
6-9
10-8
14-0
17-2
19-11
6-9
10-3
13-0
15-10
18-5
Hem-Fir #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Southern Pine SS
7-6
11-0
15-7
19-11
24-3
7-6
11-10
15-7
19-11
24-3
Southern Pine #1
7-5
11-7
15-4
19-7
23-9
7-5
11-7
15-4
18-9
22-4
Southern Pine #2
7-3
11-5
15-0
18-2
21-3
7-3
10-11
14-1
16-10
19-9
Southern Pine #3
6-2
9-2
11-8
13-9
16-4
5-9
8-5
10-9
12-9
15-2
Spruce-Pine-Fir SS
7-1
11-2
14-8
18-9
22-10
7-1
11-2
14-8
18-9
22-4
Spruce-Pine-Fir #1
6-11
10-11
14-3
17-5
20-2
6-11
10-5
13-2
16-1
18-8
Spruce-Pine-Fir #2
6-11
10-11
14-3 '
17-5
20-2
6-11
10-5
13-2
16-1
18-8
Spruce-Pine-Fir #3
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
16
Douglas Fir-Larch SS
7-0
11-0
14-5
18-5
22-5
7-0
11-0
14-5
17-11
20-10
Douglas Fir-Larch #1
6-9
10-5
13-2
16-1
18-8
6-7
9-8
12-2
14-11
17-3
Douglas Fir-Larch #2
6-7
9-9
12-4
15-1
17-6
6-2
9-0
11-5
13-11
16-2
Douglas Fir-Larch #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
Hem-Fir SS
6-7
10-4
13-8
17-5
21-2
6-7
10-4
13-8
17-5
20-5
Hem-Fir #i
6-5
10-2
12-10
15-8
18-2
6-5
9-5
11-11
14-6
16-10
Hem-Fir #2
6-2
9-7
12-2
14-10
17-3
6-1
8-11
11-3
13-9
15-11
Hem-Fir #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
Southern Pine SS
6-10
10-9
14-2
18-1
22-0
6-10
10-9
14-2
18-1
22-0
Southern Pine #1
6-9
10-7
13-11
17-6
20-11
6-9
10-7
13-8
16-2
19-4
Southern Pine #2
6-7
10-2
13-2
15-9
18-5
6-7
9-5
12-2
14-7
17-1
Southern Pine #3
5-4
7-11
10-1
11-11
14-2
4-il
7-4
9-4
11-0
13-1
Spruce-Pine-Fir SS
6-5
10-2
13-4
17-0
20-9
6-5
10-2
13-4
16-8
19-4
Spruce-Pine-Fir #1
6-4
9-9
12-4
15-1
17-6
6-2
9-0
1.-5
13-11
16-2
Spnice-Pine-Fir #2
6-4
9-9
12-4
15-1
17-6
6-2
9-0
11-5
13-11
16-2
Spruce-Pine-Fir #3
5-0
7-4
9-4
11-5
13-2
4-8
6-10
8-8
10-6
12-3
(continued)
O
O
o
CO
(D
00
TABLE 2308.10.3(6)— <;ontinued
RAFTER SPANS FOR COMMON LUMBER SPECIES
(Ground Snow Load = 50 pounds per square foot, Ceiling Attached to Rafters, L/A =
240)
RAFTER
SPACING
(inches)
SPECIES AND GRADE
DEAD LOAD
= 10 pounds per sauare foot
DEAD LOAD
= 20 pounds oer sauare foot
2x4
2x6
2x8 i 2x10
2x12
2x4
2x6
2x8 1 2x10
2x12
Maximum rafter scans 1
(ft. - In.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. - in.)
(ft. -in.)
(ft., in.)
(ft., in.)
(ft. - in.)
(ft. -in.)
19.2
Douglas Fir-Larch
SS
6-7
10-4
13-7
17-4
20-6
6-7
10-4
13-5
16-5
19-0
Douglas Fir-Larch
#1
6-4
9-6
12-0
14-8
17-1
6-0
8-10
11-2
13-7
15-9
Douglas Fir-Larch
#2
6-1
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Douglas Fir-Larch
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
Hem-Fir
SS
6-2
9-9
12-10
16-5
19-11
6-2
9-9
12-10
16-1
18-8
Hem-Fir
#1
6-1
9-3
11-9
14-4
16-7
5-10
8-7
10-10
13-3
15-5
Hem-Fir
#2
5-9
8-9
11-1
13-7
15-9
5-7
8-1
10-3
12-7
14-7
Hem-Fir
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
Southern Pine
SS
6-5
10-2
13-4
17-0
20-9
6-5
10-2
13-4
17-0
20-9
Southern Pine
#1
6-4
9-11
13-1
16-0
19-1
6-4
9-11
12-5
14-10
17-8
Southern Pine
#2
6-2
9-4
12-0
14-4
16-10
6-0
8-8
11-2
13-4
15-7
Southern Pine
#3
4-11
7-3
9-2
10-10
12-11
4-6
6-8
8-6
10-1
12-0
Spruce-Pine-Fir
SS
6-1
9-6
12-7
16-0
19-1
6-1
9-6
12-5
15-3
17-8
Spruce-Pine-Fir
#1
5-11
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Spruce-Pine-Fir
#2
5-11
8-11
11-3
13-9
15-11
5-7
8-3
10-5
12-9
14-9
Spruce-Pine-Fir
#3
4-7
6-9
8-6
10-5
12-1
4-3
6-3
7-11
9-7
11-2
24
Douglas Fir-Larch
SS
6-1
9-7
12-7
15-10
18-4
6-1
9-6
12-0
14-8
17-0
Douglas Fir-Larch
#1
5-10
8-6
10-9
13-2
15-3
5-5
7-10
10-0
12-2
14-1
Douglas Fir-Larch
#2
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Douglas Fir-Larch
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
Hem-Fir
SS
5-9
9-1
11-11
15-12
18-0
5-9
9-1
11-9
14-5
16-8
Hem-Fir
#1
5-8
8-3
10-6
12-10
14-10
5-3
7-8
9-9
11-10
13-9
Hem-Fir
#2
5-4
7-10
9-11
12-1
14-1
4-11
7-3
9-2
11-3
13-0
Hem-Fir
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
Southern Pine
SS
6-0
9-5
12-5
15-10
19-3
6-0
9-5
12-5
15-10
19-3
Southern Pine
#1
5-10
9-3
12-0
14-4
17-1
5-10
8-10
11-2
13-3
15-9
Southern Pine
#2
5-9
8-4
10-9
12-10
15-1
5-5
7-9
10-0
11-11
13-11
Southern Pine
#3
4-4
6-5
8-3
9-9
11-7
4-1
6-0
7-7
9-0
10-8
Spruce-Pine-Fir
SS
5-8
8-10
11-8
14-8
17-1
5-8
8-10
11-2
13-7
15-9
Spruce-Pine-Fir
#1
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Spruce-Pine-Fir
#2
5-5
7-11
10-1
12-4
14-3
5-0
7-4
9-4
11-5
13-2
Spnice-Pine-Fir
#3
4-1
6-0
7-7
9-4
10-9
3-10
5-7
7-1
8-7
10-0
— For SI: 1 inch = 25.4 mm, 1 foot = 304.8 nrni, 1 pound per square foot = 47.9 N/m\
O
O
o
o
m
o
o
o
WOOD
TABLE 2308.10.4.1
RAFTER TIE CONNECTIONSs
RAFTER
SLOPE
TIE SPACING
(inches)
GROUND SNOW LOAD (pound per square foot)
NO SNOW LOAD
30 pounds per square foot
50 pounds per square foot
Roof span (feet)
12
20 28
36
12
20
28
36
12
20
28
36
Required number of 16d common (aVg" x 0.162") nails^' ^ per connection''' ^'^'^
3:12
12
4
6
8
10
4
6
8
11
5
8
12
15
16
5
7
10
13
5
8
11
14
6
11
15
20
24
7
11
15
19
7
11
16
21
9
16
23
30
32
10
14
19
25
10
16
22
28
12
27
30
40
48
14
21
29
37
14
32
36
42
18
32
46
60
4:12
12
3
4
5
6
3
5
6
8
4
6
9
11
16
3
5
7
8
4
6
8
11
5
8
12
15
24
4
7
10
12
5
9
12
16
7
12
17
22
32
6
9
13
16
8
12
16
22
10
16
24
30
48
8
14
19
24
10
18
24
32
14
24
34
44
5:12
12
3
3
4
5
3
4
5
7
3
5
7
9
16
3
4
5
7
3
5
7
9
4
7
9
12
24
4
6
8
10
4
7
10
13
6
10
14
18
32
5
8
10
13
6
10
14
18
8
14
18
24
48
7
11
15
20
8
14
20
26
12
20
28
36
7:12
12
3
3
3
4
3
3
4
5
3
4
5
7
16
3
3
4
5
3
4
5
6
3
5
7
9
24
3
4
6
7
3
5
7
9
4
7
10
13
32
4
6
8
10
4
8
10
12
6
10
14
18
48
5
8
11
14
6
10
14
18
9
14
20
26
9:12
12
3
3
3
3
3
3
3
4
3
3
4
5
16
3
3
3
4
3
3
4
5
3
4
5
7
24
3
3
5
6
3
4
6
7
3
6
8
10
32
3
4
6
8
4
6
8
10
5
8
10
14
48
4
6
9
11
5
8
12
14
7
12
16
20
12:12
12
3
3
3
3
3
3
3
3
3
3
3
4
16
3
3
3
3
3
3
3
4
3
3
4
5
24
3
3
3
4
3
3
4
6
3
4
6
8
32
3
3
4
5
3
5
6
8
4
6
8
10
48
3
4
6
7
4
7
8
12
6
8
12
16
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 NAn^.
a. 40d box (5" x 0.162") or 16d sinker (37/' x 0.148") nails are permitted to be substituted for 16d common (3V2" x 0.16") nails.
b. Nailing requirements are permitted to be reduced 25 percent if nails are clinched.
c. Rafter tie heel joint connections are not required where the ridge is supported by a load-bearing \\all, header or ridge beam.
d. When intermediate support of the rafter is provided by vertical struts or purlins to a load-bearing wall, the tabulated heel joint connection requirements are permit-
ted to be reduced proportionally to the reduction in span.
e. Equivalent nailing patterns are required for ceiling joist to ceihng joist lap spUces.
f. Connected members shall be of sufficient size to prevent splitting due to nailing.
g. For snow loads less than 30 pounds per square foot, the required number of nails is permitted to be reduced by multiplying by the ratio of actual snow load plus 1
divided by 40, but not less than the number required for no snow load.
2010 CALIFORNIA BUILDING CODE
399
WOOD
2308.10.4 Ceiling joist and rafter framing. Rafters shall
be framed directly opposite each other at the ridge. There
shall be a ridge board at least 1-inch (25 mm) nominal thick-
ness at ridges and not less in depth than the cut end of the raf-
ter. At valleys and hips, there shall be a single valley or hip
rafter not less than 2-inch (51 nam) nominal thickness and
not less in depth than the cut end of the rafter.
2308.10.4.1 Ceiling joist and rafter connections. Ceil-
ing joists and rafters shall be nailed to each other and the
assembly shall be nailed to the top wall plate in accor-
dance with Tables 2304.9.1 and 2308.10.1. Ceiling joists
shall be continuous or securely joined where they meet
over interior partitions and fastened to adjacent rafters in
accordance with Tables 2308.10.4.1 and 2304.9.1 to pro-
vide a continuous rafter tie across the building where such
joists are parallel to the rafters. Ceiling joists shall have a
bearing surface of not less than 1 V2 inches (38 mm) on the
top plate at each end.
Where ceiling joists are not parallel to rafters, an equiv-
alent rafter tie shall be installed in a manner to provide a
continuous tie across the building, at a spacing of not more
than 4 feet (1219 mm) o.c. The connections shall be in
accordance with Tables 2308. 10.4. 1 and 2304.9. 1 , or con-
nections of equivalent capacities shall be provided. Where
ceihng joists or rafter ties are not provided at the top of the
rafter support walls, the ridge formed by these rafters shall
also be supported by a girder conforming to Section
2308.4.
Rafter ties shall be spaced not more than 4 feet (1219
mm) o.c. Rafter tie connections shall be based on the
equivalent rafter spacing in Table 2308.10.4.1. Where
rafter ties are spaced at 32 inches (813 mm) o.c, the
number of 1 6d common nails shall be two times the num-
ber specified for rafters spaced 16 inches (406 mm) o.c,
with a minimum of four 16d common nails where no
snow loads are indicated. Where rafter ties are spaced at
48 inches (1219 mm) o.c, the number of 16d common
nails shall be two times the number specified for rafters
spaced 24 inches (610 mm) o.c, with a minimum of six
16d common nails where no snow loads are indicated.
Rafter/ceiling joist connections and rafter/tie connec-
tions shall be of sufficient size and number to prevent
splitting from nailing.
2308.10.4.2 Notches and holes. Notching at the ends
of rafters or ceiling joists shall not exceed one-fourth
the depth. Notches in the top or bottom of the rafter or
ceiling joist shall not exceed one- sixth the depth and
shall not be located in the middle one-third of the span,
except that a notch not exceeding one-third of the depth
is permitted in the top of the rafter or ceiling joist not
further from the face of the support than the depth of the
member.
Holes bored in rafters or ceiling joists shall not be
within 2 inches (5 1 mm) of the top and bottom and their
diameter shall not exceed one-third the depth of the
member.
2308.10.4.3 Framing around openings. Trimmer and
header rafters shall be doubled, or of lumber of equiva-
lent cross section, where the span of the header exceeds 4
feet (1219 mm). The ends of header rafters more than 6
feet (1829 mm) long shall be supported by framing
anchors or rafter hangers unless bearing on a beam, parti-
tion or wall.
2308.10.5 Purlins. Purlins to support roof loads are permit-
ted to be installed to reduce the span of rafters within allow-
able limits and shall be supported by struts to bearing walls.
The maximum span of 2-inch by 4-inch (5 1 mm by 1 02 mm)
purlins shall be 4 feet (1219 mm). The maximum span of the
2-inch by 6-inch (51 mm by 152 mm) purlin shall be 6 feet
(1829 mm), but in no case shall the purlin be smaller than
the supported rafter. Struts shall not be smaller than 2-inch
by 4-inch (51 mm by 102 mm) members. The unbraced
length of struts shall not exceed 8 feet (2438 mm) and the
minimum slope of the struts shall not be less than 45 degrees
(0.79 rad) from the horizontal.
2308.10.6 Blocking. Roof rafters and ceiling joists shall be
supported laterally to prevent rotation and lateral displace-
ment in accordance with the provisions of Section 2308 .8.5 .
2308.10.7 Engineered wood products. Prefabricated
wood I-joists, structural glued-laminated timber and struc-
tural composite lumber shall not be notched or drilled
except where permitted by the manufacturer's recommen-
dations or where the effects of such alterations are specifi-
cally considered in the design of the member by a registered
design professional.
2308.10.8 Roof sheathing. Roof sheathing shall be in
accordance with Tables 2304.7(3) and 2304.7(5) for wood
structural panels, and Tables 2304.7(1) and 2304.7(2) for
lumber and shall comply with Section 2304.7.2.
2308.10,8.1 Joints. Joints in lumber sheathing shall
occur over supports unless approved end-matched lum-
ber is used, in which case each piece shall bear on at least
two supports.
2308.10.9 Roof planking. Planking shall be designed in
accordance with the general provisions of this code.
In lieu of such design, 2-inch (51 mm) tongue-and-
groove planking is permitted in accordance with Table
2308.10,9. Joints in such planking are permitted to be ran-
domly spaced, provided the system is applied to not less
than three continuous spans, planks are center matched and
end matched or splined, each plank bears on at least one sup-
port, and joints are separated by at least 24 inches (610 mm)
in adjacent pieces.
2308.10.10 Wood trusses. Wood trusses shall be designed
in accordance with Section 2303.4.
2308.10.11 Attic ventilation. For attic ventilation, see Sec-
tion 1203.2.
2308.11 Additional requirements for conventional con-
struction in Seismic Design Category B or C. Structures of
conventional light-frame construction in Seismic Design Cate-
gory B or C, as determined in Section 1613, shall comply with
Sections 2308. 11.1 through 2308. 1 1 .3, in addition to the provi-
sions of Sections 2308.1 through 2308.10.
400
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2308.10.9
ALLOWABLE SPANS FOR 2-INCH TONGUE- AN D-GROOVE DECKING
SPAN«
(feet)
LIVE LOAD
(pound per square foot)
DEFLECTION LIMIT
BENDING STRESS (/)
(pound per square inch)
MODULUS OF ELASTICITY (£)
(pound per square inch)
Roofs
4
20
1/240
1/360
160
170,000
256,000
30
1/240
1/360
210
256,000
384,000
40
1/240
1/360
270
340,000
512,000
4.5
20
1/240
1/360
200
242,000
305,000
30
1/240
1/360
270
363,000
405,000
40
1/240
1/360
350
484,000
725,000
5.0
20
1/240
1/360
250
332,000
500,000
30
1/240
1/360
330
495,000
742,000
40
1/240
1/360
420
660,000
1,000,000
5.5
20
1/240
1/360
300
442,000
660,000
30
1/240
1/360
400
662,000
998,000
40
1/240
1/360
500
884,000
1,330,000
6.0
20
1/240
1/360
360
575,000
862,000
30
1/240
1/360
480
862,000
1,295,000
40
1/240
1/360
600
1,150,000
1,730,000
6.5
20
1/240
1/360
420
595,000
892,000
30
1/240
1/360
560
892,000
1,340,000
40
1/240
1/360
700
1,190,000
1,730,000
(continued)
2010 CALIFORNIA BUILDING CODE
401
WOOD
TABLE 2308.1 0.9-continued
ALLOWABLE SPANS FOR 2-INCH TONGUE- AN D-GROOVE DECKING
SPAN^
(feet)
LIVE LOAD
(pound per square foot)
BENDING STRESS (0
DEFLECTION LIMIT (pound per square inch)
MODULUS OF ELASTICITY (£)
(pound per square inch)
Roofs
7.0
20
1/240
1/360
490
910,000
1,360,000
30
1/240
1/360
650
1,370,000
2,000,000
40
1/240
1/360
810
1,820,000
2,725,000
7.5
20
1/240
1/360
560
1,125,000
1,685,000
30
1/240
1/360
750
1,685,000
2,530,000
40
1/240
1/360
930
2,250,000
3,380,000
8.0
20
1/240
1/360
640
1,360,000
2,040,000
30
1/240
1/360
850
2,040,000
3,060,000
Floors
4
4.5
5.0
40
1/360
840
950
1,060
1,000,000
1,300,000
1,600,000
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kN/m^, 1 pound per square inch = 0.00689 N/mnf .
a. Spans are based on simple beam action with 10 pounds per square foot dead load and provisions for a 300-pound concentrated load on a 12-inch width of decking.
Random layup is permitted in accordance with the provisions of Section 2308.10.9. Lumber thickness is IV2 inches nominal.
2308.11.1 Number of stories. Structures of conventional
light-frame construction shall not exceed two stories above
grade plane in Seismic Design Category C.
2308.11.2 Concrete or masonry. Concrete or masonry
walls and stone or masonry veneer shall not extend above a
basement.
Exceptions:
1. Stone and masonry veneer is permitted to be used
in the first two stories above grade plane or the
first three stories above grade plane where the
lowest story has concrete or masonry walls in Seis-
mic Design Category B, provided that structural
use panel wall bracing is used and the length of
bracing provided is one- and one-half times the
required length as determined in Table
2308.9.3(1).
2. Stone and masonry veneer is permitted to be used
in the first story above grade plane or the first two
stories above grade plane where the lowest story
has concrete or masonry walls in Seismic Design
Category B or C.
3. Stone and masonry veneer is permitted to be used
in both stories of buildings with two stories above
grade plane in Seismic Design Categories B and
C, provided the following criteria are met:
3.1. Type of brace per Section 2308.9.3 shall be
Method 3 and the allowable shear capacity
in accordance with Table 2306.3 shall be a
minimum of 350 plf (5108 N/m).
3.2. Braced wall panels in the second story
shall be located in accordance with Section
2308.9.3 and not more than 25 feet (7620
mm) on center, and the total length of
braced wall panels shall be not less than 25
percent of the braced wall line length.
Braced wall panels in the first story shall be
located in accordance with Section
2308.9.3 and not more than 25 feet (7620
mm) on center, and the total length of
braced wall panels shall be not less than 45
percent of the braced wall line length.
3.3. Hold-down connectors shall be provided at
the ends of each braced wall panel for the
second story to first story connection with an
allowable design of 2,000 pounds (8896 N).
Hold-down connectors shall be provided at
the ends of each braced wall panel for the
first story to foundation connection with an
402
2010 CALIFORNIA BUILDING CODE
WOOD
allowable capactiy of 3,900 pounds (17
347 N). In all cases, the hold-down con-
nector force shall be transferred to the
foundation.
3.4. Cripple walls shall not be permitted.
2308.11.3 Framing and connection details. Framing and
connection details shall conform to Sections 2308.11.3.1
through 2308.11.3.3.
2308.11.3.1 Anchorage. Braced wall lines shall be
anchored in accordance with Section 2308.6 at founda-
tions.
2308.11.3.2 Stepped footings. Where the height of a
required braced wall panel extending from foundation to
floor above varies more than 4 feet (1219 mm), the fol-
lowing construction shall be used:
1 . Where the bottom of the footing is stepped and the
lowest floor framing rests directly on a sill bolted
to the footings, the sill shall be anchored as
required in Section 2308,3.3.
2. Where the lowest floor framing rests directly on a
sill bolted to a footing not less than 8 feet (2438
mm) in length along a line of bracing, the line shall
be considered to be braced. The double plate of the
cripple stud wall beyond the segment of footing
extending to the lowest framed floor shall be spliced
to the sill plate with metal ties, one on each side of
the sill and plate. The metal ties shall not be less than
0.058 inch [1.47 nmi (16 galvanized gage)] by IV2
inches (38 mm) wide by 48 inches (1219 mm) with
eight 16d common nails on each side of the sphce
location (see Figure 2308.11.3.2). The metal tie
shall have a minimum yield of 33,000 pounds per
square inch (psi) (227 MPa).
3. Where cripple walls occur between the top of the
footing and the lowest floor framing, the bracing
requirements for a story shall apply.
2308.11.3.3 Openings in horizontal diaphragms.
Openings in horizontal diaphragms with a dimension per-
pendicular to the joist that is greater than 4 feet (1219 mm)
shall be constructed in accordance with the following:
1. Blocking shall be provided beyond headers.
2. Metal ties not less than 0.058 inch [1.47 mm (16
galvanized gage)] by VI 2 inches (38 mm) wide
with eight 16d common nails on each side of the
header-joist intersection shall be provided (see
Figure 2308.11.3.3). The metal ties shall have a
minimum yield of 33,000 psi (227 MPa).
2308.12 Additional requirements for conventional construc-
tion in Seismic Design Category D or E. Structures of conven-
tional light-frame construction in Seismic Design Category D or
E, as determined in Section 1613, shall conform to Sections
2308.12.1 through 2308.12.9, in addition to the requirements
for Seismic Design Category B or C in Section 2308.1 1.
2308.12.1 Number of stories. Structures of conventional
light-frame construction shall not exceed one story above
grade plane in Seismic Design Category D or E.
2308.12.2 Concrete or masonry. Concrete or masonry
walls and stone or masonry veneer shall not extend above a
basement.
Exception: Stone and masonry veneer is permitted to be
used in the first story above grade plane in Seismic Design
Category D, provided the following criteria are met:
1 . Type of brace in accordance with Section 2308.9.3
shall be Method 3 and the allowable shear capacity
in accordance with Table 2306.3 shall be a mini-
mum of 350 plf (5 108 N/m).
2. The bracing of the first story shall be located at
each end and at least every 25 feet (7620 mm) o.c.
but not less than 45 percent of the braced wall line.
3. Hold-down connectors shall be provided at the
ends of braced walls for the first floor to founda-
tion with an allowable capacity of 2,100 pounds
(9341 N).
4. Cripple walls shall not be permitted.
2308.12.3 Braced wall line spacing. Spacing between inte-
rior and exterior braced wall lines shall not exceed 25 feet
(7620 mm).
2308.12.4 Braced wall line sheathing. Braced wall lines
shall be braced by one of the types of sheathing prescribed by
Table 2308.12.4 as shown in Figure 2308.9.3. The sum of
lengths of braced wall panels at each braced wall line shall
conform to Table 2308. 12.4. Braced wall panels shall be dis-
tributed along the length of the braced wall line and start at
not more than 8 feet (2438 mm) from each end of the braced
wall line. Panel sheathing joints shall occur over studs or
blocking. Sheathing shall be fastened to studs, top and bot-
tom plates and at panel edges occurring over blocking. Wall
framing to which sheathing used for bracing is applied shall
be nominal 2 inch wide [actual IV2 inch (38 mm)] or larger
members.
Cripple walls having a stud height exceeding 14 inches
(356 mm) shall be considered a story for the purpose of this
section and shall be braced as required for braced wall lines
in accordance with Table 2308.12.4. Where interior braced
wall lines occur without a continuous foundation below, the
length of parallel exterior cripple wall bracing shall be one
and one-half times the lengths required by Table 2308.12.4.
Where the cripple wall sheathing type used is Type S-W and
this additional length of bracing cannot be provided, the
capacity of Type S-W sheathing shall be increased by reduc-
ing the spacing of fasteners along the perimeter of each
piece of sheathing to 4 inches (102 mm) o.c.
2010 CALIFORNIA BUILDING CODE
403
WOOD
2x SILL PLATE
CONCRETE
STEPPED FOOTING
2'-0" MIN.
< ►
SPLICE -
WHERE FOOTING SECTION "A" IS MORE THAN 8'-0",
PROVIDE METAL TIE 16GAx 1 1/2" x4'-0'" MIN, EACH SIDE
W/ 8-1 6d COMMON NAILS
EACH SIDE OF SPLICE
t^pz^t:^:^^^/:.
FOOTING SECTION "A"
^^< ►
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
;\\\V/ sWVAWW.xW
2x CRIPPLE
STUD WALL
0777Z7777-777
NOTE: WHERE FOOTING SECTION "A"
IS LESS THAN B'-O" LONG IN A
25'-0" TOTAL LENGTH WALL. PROVIDE
BRACING AT CRIPPLE STUD WALL
FIGURE 2308.11.3.2
STEPPED FOOTING CONNECTION DETAILS
PLYWOOD SHEATHING
DIAPHRAGM OPENING
METALTIE16GA.X1 1/2"x4'-0" MIN., (4 TOTAL)
W/ 16-16d COMMON NAILS AS SHOWN
-OR-
METALTIE16GA. x1 1/2" x (OPENING WIDTH + 4'-0") MIN.,
(2 TOTAL) W/ 24-1 6d COMMON NAILS
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
FIGURE 2308.11 .3.3
OPENINGS IN HORIZONTAL DIAPHRAGMS
404
2010 CALIFORNIA BUILDING CODE
WOOD
TABLE 2308.12.4
WALL BRACING IN SEISMIC DESIGN CATEGORIES D AND E
(Minimum Length of Wall Bracing per each 25 Linear Feet of Braced Wall Line°)
CONDITION
SHEATHING TYPE''
Sds< 0.50
0.50 < Sos<0.75
0.75 <Sos< 1.00
S^s>1.00
One story
G-F
10 feet 8 inches
14 feet 8 inches
18 feet 8 inches
25 feet inches
S-W
5 feet 4 inches
8 feet inches
9 feet 4 inches
12 feet inches
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. Minimum length of panel bracing of one face of the wall for S-W sheathing or both faces of the wall for G-P sheathing; h/w ratio shall not exceed 2: 1 . For S-W
panel bracing of the same material on two faces of the wall, the minimum length is permitted to be one-half the tabulated value but the h/w ratio shall not exceed 2: 1
and design for uplift is required.
b. G-P = gypsum board, fiberboard, particleboard, lath and plaster or gypsum sheathing boards; S-W = wood structural panels and diagonal wood sheathing.
c. Nailing as specified below shall occur at all panel edges at studs, at top and bottom plates and, where occurring, at blocking:
For V2-inch gypsum board, 5d (0. 1 13 inch diameter) cooler nails at 7 inches on center;
For ^/g-inch gypsum board, No. 1 1 gage (0.120 inch diameter) at 7 inches on center;
For gypsum sheathing board, P/4 inches long by ^/j^-inch head, diamond point galvanized nails at 4 inches on center;
For gypsum lath, No. 13 gage (0,092 inch) by iVg inches long, ^V64-inch head, plasterboard at 5 inches on center;
For Portland cement plaster. No. 1 1 gage (0.120 inch) by IV2 inches long, "^/jg- inch head at 6 inches on center;
For fiberboard and particleboard, No. 11 gage (0.120 inch) by IV2 inches long, ■'/j^-inch head, galvanized nails at 3 inches on center.
2308.12.5 Attachment of sheathing. Fastening of braced
wall panel sheathing shall not be less than that prescribed in
Table 2308.12.4 or 2304.9. L Wall sheathing shall not be
attached to framing members by adhesives,
2308.12.6 Irregular structures. Conventional light-frame
construction shall not be used in irregular portions of struc-
tures in Seismic Design Category D or E. Such irregular por-
tions of structures shall be designed to resist the forces
specified in Chapter 16 to the extent such irregular features
affect the performance of the conventional framing system.
A portion of a structure shall be considered to be irregular
where one or more of the conditions described in Items 1
through 6 below are present.
1 . Where exterior braced wall panels are not in one plane
vertically from the foundation to the uppermost story
in which they are required, the structure shall be con-
sidered to be irregular [see Figure 2308.12.6(1)].
Exception: Floors with cantilevers or setbacks not
exceeding four times the nominal depth of the
floor joists [see Figure 2308. 12.6(2)] are permitted
to support braced wall panels provided:
1 . Floor joists are 2 inches by 10 inches (5 1 mm
by 254 mm) or larger and spaced not more
than 16 inches (406 mm) o.c.
2. The ratio of the back span to the cantilever is
at least 2:1.
3. Floor joists at ends of braced wall panels are
doubled.
4. A continuous rim joist is connected to the
ends of cantilevered joists. The rim joist is
permitted to be spliced using a metal tie not
less than 0.058 inch (1.47 mm) (16 galva-
nized gage) and IV2 inches (38 mm) wide
fastened with six 16d common nails on each
side. The metal tie shall have a minimum
yield of 33,000 psi (227 MPa).
5. Joists at setbacks or the end of cantilevered
joists shall not carry gravity loads from more
than a single story having uniform wall and
roof loads, nor carry the reactions from
headers having a span of 8 feet (2438 mm) or
more.
2. Where a section of floor or roof is not laterally sup-
ported by braced wall lines on all edges, the structure
shall be considered to be irregular [see Figure
2308.12.6(3)].
Exception: Portions of roofs or floors that do not
support braced wall panels above are permitted to
extend up to 6 feet (1829 nmi) beyond a braced
wall line [see Figure 2308.12.6(4)].
3 . Where the end of a required braced wall panel extends
more than 1 foot (305 mm) over an opening in the wall
below, the structure shall be considered to be irregu-
lar. This requirement is applicable to braced wall pan-
els offset in plane and to braced wall panels offset out
of plane as permitted by the exception to Item 1 above
in this section [see Figure 2308.12.6(5)].
Exception: Braced wall panels are permitted to
extend over an opening not more than 8 feet (2438
mm) in width where the header is a 4-inch by
12-inch (102 mm by 305 mm) or larger member.
4. Where portions of a floor level are vertically offset
such that the framing members on either side of the
offset cannot be lapped or tied together in an
approved manner, the structure shall be considered to
be irregular [see Figure 2308.12.6(6)].
Exception: Framing supported directly by foun-
dations need not be lapped or tied directly together.
5 . Where braced wall lines are not perpendicular to each
other, the structure shall be considered to be irregular
[see Figure 2308.12.6(7)].
6. Where openings in floor and roof diaphragms having
a maximum dimension greater than 50 percent of the
2010 CALIFORNIA BUILDING CODE
405
WOOD
distance between lines of bracing or an area greater
than 25 percent of the area between orthogonal pairs
of braced wall lines are present, the structure shall be
considered to be irregular [see Figure 2308. 12.6(8)].
2308.12.7 Anchorage of exterior means of egress compo-
nents. Exterior egress balconies, exterior exit stairways and
similar means of egress components shall be positively
anchored to the primary structure at not over 8 feet (2438
mm) o.c. or shall be designed for lateral forces. Such attach-
ment shall not be accomplished by use of toenails or nails
subject to withdrawal.
2308.12.8 Sill plate anchorage. Sill plates shall be
anchored with anchor bolts with steel plate washers
between the foundation sill plate and the nut, or approved
anchor straps load rated in accordance with Section 1716.1.
Such washers shall be a minimum of 0.229 inch by 3 inches
by 3 inches (5.82 mm by 76 mm by 76 mm) in size. The hole
in the plate washer is permitted to be diagonally slotted with
a width of up to V^g inch (4.76 mm) larger than the bolt diam-
eter and a slot length not to exceed 1 V4 inches (44 mm), pro-
vided a standard cut washer is placed between the plate
washer and the nut.
2308.12.9 Sill plate anchorage in Seismic Design Cate-
gory E. Steel bolts with a minimum nominal diameter of Vg
inch (15.9 mm) or approved foundation anchor straps load
rated in accordance with Section 1716.1 and spaced to pro-
vide equivalent anchorage shall be used in Seismic Design
Category E.
OUT OF PLANE
OFFSET IN EXTERIOR
BRACED WALL PANELS
SECTION VIEW
SECTION VIEW
FIGURE 2308.12.6(1)
BRACED WALL PANELS OUT OF PLANE
1
f
^ >
\
\
1 4'-0"
w/2x12
CANTILEVER/SET BACK
SHALL ONLY SUPPORT ROOF
AND WALL WEIGHT
1
r ; ;
4'-0" :
s.
w/2x12 j'
SECTION THRU CANTILEVER
SECTION THRU SET BACK
For SI: 1 foot = 304.8 mm.
FIGURE 2308.12.6(2)
BRACED WALL PANELS SUPPORTED BY CANTILEVER OR SET BACK
406
2010 CALIFORNIA BUILDING CODE
WOOD
I
DASHED LINE INDICATES BRACED
WALL LINE BELOW
THERE IS NO BRACED WALL LINE
ON THIS EDGE OF THE ROOF
PLAN VIEW
FIGURE 2308.12.6(3)
FLOOR OR ROOF NOT SUPPORTED ON ALL EDGES
ROOF OR FLOOR SHALL BE PERMITTED
TO EXTEND UP TO 6' BEYOND
THE BRACED WALL LINE
PLAN VIEW
NO BRACED WALL PANEL ABOVE
PERMITTED AT THIS LOCATION
For SI: 1 foot = 304.8 mm.
FIGURE 2308.12.6(4)
ROOF OR FLOOR EXTENSION BEYOND BRACED WALL LINE
REQUIRED BRACED
WALL PANEL
MORE THAN r-0"
EXTERIOR ELEVATION
ForSL- 1 foot = 304.8 mm.
EXTERIOR ISOMETRIC
FIGURE 2308.12.6(5)
BRACED WALL PANEL EXTENSION OVER OPENING
2010 CALIFORNIA BUILDING CODE
407
WOOD
FLOOR JOISTS
CANNOT BE
"
^
•^
TIED DIRECTLY
TOGt 1 HER
h
f
SECTION VIEW
SECTION VIEW
FIGURE 2308.12.6(6)
PORTIONS OF FLOOR LEVEL OFFSET VERTICALLY
BRACED WALL LINES ARE NOT
PERPENDICULAR
PLAN VIEW
FIGURE 2308.12.6(7)
BRACED WALL LINES NOT PERPENDICULAR
r-
MORE THAN b1/2
IS IRREGULAR
11
MORE THAN b2/2
IS IRREGULAR
A^ — /
PLAN VIEW
PLAN VIEW
FIGURE 2308.12.6(8)
OPENING LIMITATIONS FOR FLOOR AND ROOF DIAPHRAGMS
408
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 24 - GLASS AND GLAZING
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
2403.2.1
X
X
X
X
Table 2403.2.1
X
X
X
X
2406
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
409
410 2010 CALIFORNIA BUILDING CODE
CHAPTER 24
GLASS AND GLAZING
SECTION 2401
GENERAL
2401.1 Scope. The provisions of this chapter shall govern the
materials, design, construction and quality of glass, light-
transmitting ceramic and light-transmitting plastic panels for
exterior and interior use in both vertical and sloped applica-
tions in buildings and structures.
2401.2 Glazing replacement. The installation of replacement
glass shall be as required for new installations.
SECTION 2402
DEFINITIONS
2402.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
DALLE GLASS. A decorative composite glazing material
made of individual pieces of glass that are embedded in a cast
matrix of concrete or epoxy.
DECORATIVE GLASS. A carved, leaded or Dalle glass or
glazing material whose purpose is decorative or artistic, not
functional; whose coloring, texture or other design qualities or
components cannot be removed without destroying the glazing
material and whose surface, or assembly into which it is incor-
porated, is divided into segments.
SECTION 2403
GENERAL REQUIREMENTS FOR GLASS
2403.1 Identification. Each pane shall bear the manufacturer's
mark designating the type and thickness of the glass or glazing
material. The identification shall not be omitted unless
approved and an affidavit is furnished by the glazing contractor
certifying that each light is glazed in accordance with approved
construction documents that comply with the provisions of this
chapter. Safety glazing shall be identified in accordance with
Section 2406.2.
Each pane of tempered glass, except tempered spandrel
glass, shall be permanently identified by the manufacturer. The
identification mark shall be acid etched, sand blasted, ceramic
fired, laser etched, embossed or of a type that, once applied,
cannot be removed without being destroyed.
Tempered spandrel glass shall be provided with a removable
paper marking by the manufacturer.
2403.2 Glass supports. Where one or more sides of any pane
of glass are not firmly supported, or are subjected to unusual
load conditions, detailed construction documents, detailed
shop drawings and analysis or test data assuring safe perfor-
mance for the specific installation shall be prepared by a regis-
tered design professional.
2403.2 J Additional Requirements. [DSA-SS, DSA-SS/CC
and OSHPD l&4]In addition to the requirements of Section
2403.2, glass supports shall comply with the following:
1. The construction documents and analysis or test data
required per Section 2403.2 shall be submitted to the
enforcement agency for approval.
2. Glass firmly supported on all four edges shall be
glazed with minimum laps and edge clearances set
forth in Table 2403.2.1.
2403.3 Framing. To be considered firmly supported, the fram-
ing members for each individual pane of glass shall be
designed so the deflection of the edge of the glass perpendicu-
lar to the glass pane shall not exceed V175 of the glass edge
length or V4 inch (19.1 mm), whichever is less, when subjected
to the larger of the positive or negative load where loads are
combined as specified in Section 1605.
2403.4 Interior glazed areas. Where interior glazing is
installed adjacent to a walking surface, the differential deflec-
tion of two adjacent unsupported edges shall not be greater than
the thickness of the panels when a force of 50 pounds per linear
foot (plf) (730 N/m) is applied horizontally to one panel at any
point up to 42 inches (1067 mm) above the walking surface.
2403.5 Louvered windows or jalousies. Roat, wired and pat-
terned glass in louvered windows and jalousies shall be no thin-
ner than nominal V16 inch (4.8 mm) and no longer than 48
inches (1219 mm). Exposed glass edges shall be smooth.
Wired glass with wire exposed on longitudinal edges shall
not be used in louvered windows or jalousies.
Where other glass types are used, the design shall be submit-
ted to the building official for approval.
SECTION 2404
WIND, SNOW, SEISMIC
AND DEAD LOADS ON GLASS
2404.1 Vertical glass. Glass sloped 15 degrees (0.26 rad) or
less from vertical in windows, curtain and window walls, doors
and other exterior applications shall be designed to resist the
wind loads in Section 1609 for components and cladding.
Glass in glazed curtain walls, glazed storefronts and glazed
partitions shall meet the seismic requirements of ASCE 7, Sec-
tion 13.5.9. The load resistance of glass under uniform load
shall be determined in accordance with ASTM E 1300.
The design of vertical glazing shall be based on the follow-
ing equation:
F <F
^ gw ~~ ^ ga
(Equation 24-1)
where:
Fg^ = Wind load on the glass computed in accordance with
Section 1609.
Fga = Short duration load on the glass as determined in accor-
dance with ASTM E 1300.
2010 CALIFORNIA BUILDING CODE
411
GLASS AND GLAZING
TABLE 2403.2.1 [DSA-SS, DSA-SS/CC and OSHPD 1 & 4]
MINIMUM GLAZING REQUIREMENTS
Fixed Windows and Openable Windows Other Than Horizontai Siding
GLASS AREA
UP TO 6
SQ.FT.
6 TO 14
SQ.FT.
14 TO 32
SQ.FT.
32TO50
SQ.FT.
OVER 50
SQ.FT.
X 0.0929 for m^, x 25.4 for mm
1. Minimum Frame Lap
i/r
1/4"
5/1&'
3/8''
1/2"
2. Minimum Glass Edge
Clearance
J/gna,b
ygna,b
3/16"^
1/r
1/4" a
3. Continuous Glazing Rabbet
and Glass Retainer''
Required
4. Resilient Setting Material ^
Not Required
Required
Sliding Doors and Horizontal Sliding Windows
GLASS AREA
UP TO 14
SQ.FT.
14 TO 32
SQ.FT.
32 TO 50
SQ.FT.
OVER 50
SQ.FT.
X 0.0929 for m^, x 25.4 for mm
5. Minimum Glass Frame Lap
1/r
5/1&'
3/8"
1/r
6. Minimum Glass Edge Clearance
1/8"'
3/W'
1/r
1/r
7. Continuous Glazing Rabbet c
ind Glass Retainer ^
Required above
third story
Required
8. Resilient Setting Material^
Not Required
Required
a. Glass edge clearance infixed openings shall not be less than required to provide for wind and earthquake drift.
b. Glass edge clearance at all sides of pane shall be a minimum of^/j^ inch (4.8 mm) where height of glass exceeds 3 feet (914 mm).
c. Glass retainers such as metal, wood or vinyl face stops, glazing beads, gaskets, glazing clips and glazing channels shall be of sufficient strength and fixation to
serve this purpose.
d. Resilient setting material shall include preformed rubber or vinyl plastic gaskets or other materials which are proved to the satisfaction of the building official to
remain resilient.
2404.2 Sloped glass. Glass sloped more than 15 degrees (0.26
rad) from vertical in skylights, sunrooms, sloped roofs and
other exterior applications shall be designed to resist the most
critical of the following combinations of loads.
(Equation 24-2)
(Equation 24-3)
(Equation 24-4)
F, = W, + D + 0.55
F^ = Q.5Wi + D-\-S
where:
D = Glass dead load psf (kN/m^).
For glass sloped 30 degrees (0.52 rad) or less from hori-
zontal,
= 13 r, (For SI: 0.0245 g.
For glass sloped more than 30 degrees (0.52 rad) from
horizontal,
= 13 ?^ cos e (For SI: 0.0245 t^ cos 6).
Fg = Total load, psf (kN/m^) on glass.
S = Snow load, psf(kN/m^) as determined in Section 1608.
tg = Total glass thickness, inches (mm) of glass panes and
plies.
Wi = Inward wind force, psf (kN/m^) as calculated in Section
1609.
W^ = Outward wind force, psf (kN/m^) as calculated in Sec-
tion 1609.
8 - Angle of slope from horizontal.
Exception: Unit skyhghts shall be designed in accordance
with Section 2405.5.
The design of sloped glazing shall be based on the following
equation:
F <F
^ g — ^ ga
where
F.
(Equation 24-5)
= Total load on the glass determined from the load com-
binations above.
Fg^ = Short duration load resistance of the glass as deter-
mined according to ASTM E 1300 for Equations 24-2
and 24-3; or the long duration load resistance of the
glass as determined according to ASTM E 1300 for
Equation 24-4.
2404.3 Wired, patterned and sandblasted glass.
2404.3.1 Vertical wired glass. Wired glass sloped 15
degrees (0.26 rad) or less from vertical in windows, curtain
412
2010 CALIFORNIA BUILDING CODE
GLASS AND GLAZING
and window walls, doors and other exterior applications
shall be designed to resist the wind loads in Section 1609 for
components and cladding according to the following equa-
tion:
where:
(Equation 24-6)
Fg^- Is the wind load on the glass computed per Section
1609.
Fg^ = Nonfactored load from ASTM E 1300 using a thick-
ness designation for monolithic glass that is not
greater than the thickness of wired glass.
2404,3,2 Sloped wired glass. Wired glass sloped more than
15 degrees (0.26 rad) from vertical in skylights, sunspaces,
sloped roofs and other exterior applications shall be
designed to resist the most critical of the combinations of
loads from Section 2404.2.
For Equations 24-2 and 24-3:
F,<0.5F,.
For Equation 24-4:
F,<0.3F,.
(Equation 24-7)
(Equation 24-8)
where:
Fg = Total load on the glass.
Fg, = Nonfactored load from ASTM E 1300.
2404.3.3 Vertical patterned glass. Patterned glass sloped
15 degrees (0.26 rad) or less from vertical in windows, cur-
tain and window walls, doors and other exterior applications
shall be designed to resist the wind loads in Section 1609 for
components and cladding according to the following equa-
tion:
where:
(Equation 24-9)
Fg^= Wind load on the glass computed per Section 1609.
Fg, = Nonfactored load from ASTM E 1300. The value for
patterned glass shall be based on the thinnest part of
the glass. Interpolation between nonfactored load
charts in ASTM E 1300 shall be permitted.
2404.3.4 Sloped patterned glass. Patterned glass sloped
more than 15 degrees (0.26 rad) from vertical in skylights,
sunspaces, sloped roofs and other exterior applications shall
be designed to resist the most critical of the combinations of
loads from Section 2404.2.
For Equations 24-2 and 24-3:
Fg<LOFg^
For Equation 24-4:
where
Fg = Total load on the glass.
(Equation 24-10)
(Equation 24-11)
Fg^ = Nonfactored load from ASTM E 1300. The value for
patterned glass shall be based on the thinnest part of
the glass. Interpolation between the nonfactored load
charts in ASTM E 1300 shall be permitted.
2404.3.5 Vertical sandblasted glass. Sandblasted glass
sloped 15 degrees (0.26 rad) or less from vertical in win-
dows, curtain and window walls, doors, and other exterior
applications shall be designed to resist the wind loads in
Section 1609 for components and cladding according to the
following equation:
Fg< 0.5 Fg, (Equation 24-12)
where:
Fg = Total load on the glass.
Fg, = Nonfactored load from ASTM E 1300. The value for
sandblasted glass is for moderate levels of sandblast-
ing.
2404.4 Other designs. For designs outside the scope of this
section, an analysis or test data for the specific installation shall
be prepared by a registered design professional.
SECTION 2405
SLOPED GLAZING AND SKYLIGHTS
2405.1 Scope. This section applies to the installation of glass
and other transparent, translucent or opaque glazing material
installed at a slope more than 15 degrees (0.26 rad) from the
vertical plane, including glazing materials in skylights, roofs
and sloped walls.
2405.2 Allowable glazing materials and limitations. Sloped
glazing shall be any of the following materials, subject to the
listed limitations.
1. For monolithic glazing systems, the glazing material of
the single light or layer shall be laminated glass with a
minimum 30-mil (0.76 mm) polyvinyl butyral (or equiv-
alent) interlayer, wired glass, light-transmitting plastic
materials meeting the requirements of Section 2607,
heat- strengthened glass or fully tempered glass.
2. For multiple-layer glazing systems, each light or layer
shall consist of any of the glazing materials specified in
Item 1 above.
Annealed glass is permitted to be used as specified within
Exceptions 2 and 3 of Section 2405.3.
For additional requirements for plastic skyhghts, see Section
2610. Glass-block construction shall conform to the require-
ments of Section 2101.2.5.
2405.3 Screening. Where used in monolithic glazing systems,
heat-strengthened glass and fuUy tempered glass shall have
screens installed below the glazing material. The screens and
their fastenings shall: (1) be capable of supporting twice the
weight of the glazing; (2) be firmly and substantially fastened to
the framing members and (3) be installed within 4 inches (102
mm) of the glass. The screens shall be constructed of a
noncombustible material not thinner than No. 12 B&S gage
(0.0808 inch) with mesh not larger than 1 inch by 1 inch (25 mm
by 25 nun). In a corrosive atmosphere, structurally equivalent
2010 CALIFORNIA BUILDING CODE
413
GLASS AND GLAZING
noncorrosive screen materials shall be used. Heat- strengthened
glass, fully tempered glass and wired glass, when used in multi-
ple-layer glazing systems as the bottom glass layer over the
walking surface, shall be equipped with screening that conforms
to the requirements for monolithic glazing systems.
Exception: In monolithic and multiple-layer sloped glazing
systems, the following applies:
1. Fully tempered glass installed without protective
screens where glazed between intervening floors at a
slope of 30 degrees (0.52 rad) or less from the vertical
plane shall have the highest point of the glass 10 feet
(3048 mm) or less above the walking surface.
2. Screens are not required below any glazing material,
including annealed glass, where the walking surface
below the glazing material is permanently protected
from the risk of falling glass or the area below the
glazing material is not a walking surface.
3. Any glazing material, including annealed glass, is
permitted to be installed without screens in the sloped
glazing systems of commercial or detached
noncombustible greenhouses used exclusively for
growing plants and not open to the public, provided
that the height of the greenhouse at the ridge does not
exceed 30 feet (9144 mm) above grade.
4. Screens shall not be required within individual dwell-
ing units in Groups R-2, R-3 and R-4 where fully tem-
pered glass is used as single glazing or as both panes
in an insulating glass unit, and the following condi-
tions are met:
4.1. Each pane of the glass is 16 square feet (1.5
m^) or less in area.
4.2. The highest point of the glass is 12 feet (3658
mm) or less above any walking surface or
other accessible area.
4.3. The glass thickness is Vj^ inch (4.8 mm) or
less.
5 . Screens shall not be required for laminated glass with
a 15 -mil (0.38 mm) polyvinyl butyral (or equivalent)
interlayer used within individual dwelling units in
Groups R-2, R-3 and R-4 within the following limits:
5.1. Each pane of glass is 16 square feet (1.5 m^) or
less in area.
5.2. The highest point of the glass is 12 feet (3658
mm) or less above a walking surface or other
accessible area,
2405.4 Framing. In Type I and II construction, sloped glazing
and skylight frames shall be constructed of noncombustible
materials. In structures where acid fumes deleterious to metal
are incidental to the use of the buildings, approved pres-
sure-treated wood or other approved noncorrosive materials
are permitted to be used for sash and frames. Framing support-
ing sloped glazing and skylights shall be designed to resist the
tributary roof loads in Chapter 16. Skylights set at an angle of
less than 45 degrees (0.79 rad) from the horizontal plane shall
be mounted at least 4 inches (102 mm) above the plane of the
roof on a curb constructed as required for the frame. Skylights
shall not be installed in the plane of the roof where the roof
pitch is less than 45 degrees (0.79 rad) from the horizontal.
Exception: Installation of a skylight without a curb shall be
permitted on roofs with a minimum slope of 14 degrees
(three units vertical in 12 units horizontal) in Group R-3
occupancies. All unit skylights installed in a roof with a
pitch flatter than 14 degrees (0.25 rad) shall be mounted at
least 4 inches (102 mm) above the plane of the roof on a curb
constructed as required for the frame unless otherwise spec-
ified in the manufacturer's installation instructions.
2405,5 Unit skylights. Unit skyUghts shall be tested and
labeled as complying with AAMA/WDMA/CSA 101/
I.S.2/A440. The label shall state the name of the manufacturer,
the approved labeling agency, the product designation and the
performance grade rating as specified in AAMAAVDMA/CS A
101/I.S.2/A440. If the product manufacturer has chosen to
have the performance grade of the skylight rated separately for
positive and negative design pressure, then the label shall state
both performance grade ratings as specified in
AAMAAVDMA/CSA 101/I.S.2/A440 and the skylight shall
comply with Section 2405.5.2. If the skylight is not rated sepa-
rately for positive and negative pressure, then the performance
grade rating shown on the label shall be the performance grade
rating determined in accordance with AAMAAVDMA/CSA
101/I.S.2/A440 for both positive and negative design pressure
and the skyhght shall conform to Section 2405.5.1.
2405.5.1 Unit skylights rated for the same performance
grade for both positive and negative design pressure.
The design of unit skylights shall be based on the following
equation:
F^<PG
where:
(Equation 24-13)
Fg = Maximum load on the skylight determined
from Equations 24-2 through 24-4 in Section
2404.2.
PG = Performance grade rating of the skylight.
2405.5.2 Unit skylights rated for separate performance
grades for positive and negative design pressure. The
design of unit skyUghts rated for performance grade for both
positive and negative design pressures shall be based on the
following equations:
(Equation 24-14)
(Equation 24-15)
Fgo ^ f'^^Neg
where:
^^pos = Performance grade rating of the skylight under
positive design pressure;
PG^^g = Performance grade rating of the skylight under
negative design pressure; and
Fgi and F^^ are determined in accordance with the following:
For W, > D,
where:
W^ = Outward wind force, psf (kN/m^) as calculated in
Section 1609.
414
2010 CALIFORNIA BUILDING CODE
GLASS AND GLAZING
D = The dead weight of the glazing, psf (kN/m^) as
determined in Section lA^A.l for glass, or by the
weight of the plastic, psf (kN/m^) for plastic glaz-
ing.
Fgi = Maximum load on the skylight determined from
Equations 24-3 and 24-4 in Section 2404.2.
Fgo - Maximum load on the skylight determined from
Equation 24-2.
For W^ < D,
where:
D
Is the outward wind force, psf (kN/m^) as calcu-
lated in Section 1609.
The dead weight of the glazing, psf (kN/m^) as
determined in Section 2404.2 for glass, or by the
weight of the plastic for plastic glazing.
Maximum load on the skylight determined from
Equations 24-2 through 24-4 in Section 2404.2.
0.
SECTION 2406
SAFETY GLAZING
2406.1 Human impact loads. Individual glazed areas, includ-
ing glass mirrors, in hazardous locations as defined in Section
2406.4 shall comply with Sections 2406. 1 . 1 through 2406. 1 .4.
2406.1.1 Impact test. Except as provided in Sections
2406. 1 .2 through 2406, 1 .4, all glazing shall pass the impact
test requirements of Section 2406.2.
2406.1.2 Plastic glazing. Plastic glazing shall meet the
weathering requirements of ANSI Z97. 1 .
2406.1.3 Glass block. Glass-block walls shall comply with
Section 2101.2.5.
2406.1.4 Louvered windows and jalousies. Louvered
windows and jalousies shall comply with Section 2403.5.
2406.2 Impact test. Where required by other sections of this
code, glazing shall be tested in accordance with CPSC 16 CFR
1201. Glazing shall comply with the test criteria for Category I
or II as indicated in Table 2406,2(1).
Exception: Glazing not in doors or enclosures for hot tubs,
whirlpools, saunas, steam rooms, bathtubs and showers
shall be permitted to be tested in accordance with ANSI
Z97.1. Glazing shall comply with the test criteria for Class
A or B as indicated in Table 2406.2(2).
2406.3 Identification of safety glazing. Except as indicated in
Section 2406.3. 1, each pane of safety glazing installed in haz-
ardous locations shall be identified by a manufacturer's desig-
nation specifying who applied the designation, the
manufacturer or installer and the safety glazing standard with
which it complies, as well as the information specified in Sec-
tion 2403 . 1 . The designation shall be acid etched, sand blasted,
ceramic fired, laser etched, embossed or of a type that once
applied, cannot be removed without being destroyed. A label as
defined in Section 202.1 and meeting the requirements of this
section shall be permitted in lieu of the manufacturer's designa-
tion.
Exceptions:
1. For other than tempered glass, manufacturer's designa-
tions are not required, provided the building official
approves the use of a certificate, affidavit or other evi-
dence confirming compliance with this code.
2. Tempered spandrel glass is permitted to be identified by
the manufacturer with a removable paper designation
TABLE 2406.2(1)
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING CPSC 16 CFR 1201
EXPOSED SURFACE
AREA OF ONE SIDE
OF ONE LITE
GLAZING IN
STORM OR
COMBINATION
DOORS
(Category class)
GLAZING IN
DOORS
(Category class)
GLAZED PANELS
REGULATED BY
ITEM 7 OF
SECTION 2406.4
(Category class)
GLAZED PANELS
REGULATED BY
ITEM 6 OF
SECTION 2406.4
(Category class)
DOORS AND
ENCLOSURES
REGULATED BY ITEM
5 OF SECTION 2406.4
(Category class)
SLIDING GLASS
DOORS PATIO TYPE
(Category class)
9 square feet or less
I
I
No requirement
I
II
II
More than 9 square feet
n
II
II
II
n
II
For SI: 1 square foot = 0.0929 m^
TABLE 2406.2(2)
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING ANSI Z97.1
EXPOSED SURFACE AREA OF ONE
SIDE OF ONE LITE
GLAZED PANELS REGULATED BY
ITEM 7 OF SECTION 2406.4
(Category class)
GLAZED PANELS REGULATED
BY ITEM 6 OF SECTION 2406.4
(Category class)
DOORS AND ENCLOSURES
REGULATED
BY ITEM 5 OF SECTION 2406.4"
(Category class)
9 square feet or less
No requirement
B
A
More than 9 square feet
A
A
A
For SI: 1 square foot = 0.0929 m^
a. Use is only permitted by the exception to Section 2406.2,
2010 CALIFORNIA BUILDING CODE
415
GLASS AND GLAZING
2406.3.1 Multi-pane assemblies. Multi-pane glazed
assemblies having individual panes not exceeding 1 square
foot (0.09 m^) in exposed areas shall have at least one pane
in the assembly marked as indicated in Section 2406.3.
Other panes in the assembly shall be marked "CPSC 16
CFR 1201" or "ANSI Z97.1," as appropriate.
2406.4 Hazardous locations. The following shall be consid-
ered specific hazardous locations requiring safety glazing
materials:
1. Glazing in swinging doors except jalousies (see Sec-
tion 2406.4.1).
2. Glazing in fixed and sliding panels of sliding door
assemblies and panels in sliding and bifold closet door
assemblies.
3. Glazing in storm doors.
4. Glazing in unframed swinging doors.
5. Glazing in doors and enclosures for hot tubs, whirl-
pools, saunas, steam rooms, bathtubs and showers.
Glazing in any portion of a building wall enclosing
these compartments where the bottom exposed edge of
the glazing is less than 60 inches (1524 mm) above a
standing surface.
6. Glazing in an individual fixed or operable panel adja-
cent to a door where the nearest exposed edge of the
glazing is within a 24-inch (610 mm) arc of either verti-
cal edge of the door in a closed position and where the
bottom exposed edge of the glazing is less than 60
inches (1524 mm) above the walking surface.
Exceptions:
1. Panels where there is an intervening wall or
other permanent barrier between the door and
glazing.
2. Where access through the door is to a closet or
storage area 3 feet (914 mm) or less in depth.
Glazing in this apphcation shall comply with
Section 2406.4, Item 7.
3. Glazing in walls perpendicular to the plane of
the door in a closed position, other than the
wall towards which the door swings when
opened, in one- and two-family dwellings or
within dwelling units in Group R-2.
7. Glazing in an individual fixed or operable panel, other
than in those locations described in preceding Items 5
and 6, which meets all of the following conditions:
7.1. Exposed area of an individual pane greater than 9
square feet (0.84 m^);
7.2. Exposed bottom edge less than 18 inches (457
mm) above the floor;
7.3. Exposed top edge greater than 36 inches (914
mm) above the floor; and
7.4. One or more walking surface(s) within 36 inches
(914 mm) horizontally of the plane of the glaz-
ing.
Exception: Safety glazing for Item 7 is not required for the fol-
lowing installations:
1. A protective bar IV2 inches (38 mm) or
more in height, capable of withstanding a
horizontal load of 50 pounds plf (730
N/m) without contacting the glass, is
installed on the accessible sides of the
glazing 34 inches to 38 inches (864 mm
to 965 mm) above the floor.
2. The outboard pane in insulating glass
units or multiple glazing where the bot-
tom exposed edge of the glass is 25 feet
(7620 mm) or more above any grade,
roof, walking surface or other horizontal
or sloped (within 45 degrees of horizon-
tal) (0.78 rad) surface adjacent to the
glass exterior.
8. Glazing in guards and railings, including structural
baluster panels and nonstructural in-fiU panels, regard-
less of area or height above a walking surface.
9. Glazing in walls and fences enclosing indoor and out-
door swimming pools, hot tubs and spas where all of
the following conditions are present:
9. 1 . The bottom edge of the glazing on the pool or spa
side is less than 60 inches (1524 mm) above a
walking surface on the pool or spa side of the
glazing; and
9.2. The glazing is within 60 inches (1524 mm) hori-
zontally of the water's edge of a swimming pool
or spa.
10. Glazing adjacent to stairways, landings and ramps
within 36 inches (914 mm) horizontally of a walking
surface; when the exposed surface of the glass is less
than 60 inches (1524 mm) above the plane of the adja-
cent walking surface.
11. Glazing adjacent to stairways within 60 inches (1524
mm) horizontally of the bottom tread of a stairway in
any direction when the exposed surface of the glass is
less than 60 inches (1524 mm) above the nose of the
tread.
Exception: Safety glazing for Item 10 or 11 is not
required for the following installations where:
1. The side of a stairway, landing or ramp which
has a guard or handrail, including balusters or
in-fill panels, complying with the provisions of
Sections 1013 and 1607.7; and
2. The plane of the glass is greater than 1 8 inches
(457 mm) from the railing.
416
2010 CALIFORNIA BUILDING CODE
GLASS AND GLAZING
2406.4.1 Exceptions. The following products, materials
and uses shall not be considered specific hazardous loca-
tions:
1. Openings in doors through which a 3-inch (76 mm)
sphere is unable to pass.
2. Decorative glass in Section 2406.4, Item 1, 6 or 7.
3. Glazing materials used as curved glazed panels in
revolving doors.
4. Commercial refrigerated cabinet glazed doors.
5. Glass-block panels complying with Section 2101.2.5.
6. Louvered windows and jalousies complying with the
requirements of Section 2403.5.
7. Mirrors and other glass panels mounted or hung on a
surface that provides a continuous backing support.
2406.5 Fire department access panels. Fire department glass
access panels shall be of tempered glass. For insulating glass
units, all panes shall be tempered glass.
SECTION 2407
GLASS IN HANDRAILS AND GUARDS
2407.1 Materials. Glass used as a handrail assembly or a
guard section shall be constructed of either single fully tem-
pered glass, laminated fully tempered glass or laminated heat-
strengthened glass. Glazing in railing in-fill panels shall be of
an approved safety glazing material that conforms to the provi-
sions of Section 2406.1.1. For all glazing types, the minimum
nominal thickness shall be V4 inch (6.4 mm). Fully tempered
glass and laminated glass shall comply with Category II of
CPSC 16 CFR 1201 or Class A of ANSI Z97,l, Hsted in Chap-
ter 35.
2407.1.1 Loads. The panels and their support system shall
be designed to withstand the loads specified in Section
1607.7. A safety factor of four shall be used.
2407.1.2 Support. Each handrail or guard section shall be
supported by a minimum of three glass balusters or shall be
otherwise supported to remain in place should one baluster
panel fail. Glass balusters shall not be installed without an
attached handrail or guard.
Exception: A top rail shall not be required where the
glass balusters are laminated glass with two or more
glass plies of equal thickness and the same glass type
when approved by the building official. The panels shall
be designed to withstand the loads specified in Section
1607.7.
2407.1.3 Parking garages. Glazing materials shall not be
installed in handrails or guards in parking garages except
for pedestrian areas not exposed to impact from vehicles.
2407.1.4 Glazing in wind-borne debris regions. Glazing
installed in in-fill panels or balusters in wind-borne debris
regions shall comply with the following:
2407.1.4.1 Ballusters and in-fill panels. Glass installed
in exterior railing in-fiU panels or balusters shall be lami-
nated glass complying with Category II of CPSC 16 CP^
1201 or Class A of ANSI Z97.1.
2407.1.4.2 Glass supporting top rail. When the top rail
is supported by glass, the assembly shall be tested
according to the impact requirements of Section
1 609. 1 .2. The top rail shall remain in place after impact.
SECTION 2408
GLAZING IN ATHLETIC FACILITIES
2408.1 General. Glazing in athletic facilities and similar uses
subject to impact loads, which forms whole or partial wall sec-
tions or which is used as a door or part of a door, shall comply
with this section.
2408.2 Racquetball and squash courts.
2408.2.1 Testing. Test methods and loads for individual
glazed areas in racquetball and squash courts subject to
impact loads shall conform to those of CPSC 16 CFR or
ANSI Z97.1, listed in Chapter 35, with impacts being
applied at a height of 59 inches (1499 mm) above the play-
ing surface to an actual or simulated glass wall installation
with fixtures, fittings and methods of assembly identical to
those used in practice.
Glass walls shall comply with the following conditions:
1 . A glass wall ift a racquetball or squash court, or simi-
lar use subject to impact loads, shall remain intact fol-
lowing a test impact.
2. The deflection of such walls shall not be greater than
1 V2 inches (38 mm) at the point of impact for a drop
height of 48 inches (1219 mm).
Glass doors shall comply with the following conditions:
1 . Glass doors shall remain intact following a test impact
at the prescribed height in the center of the door.
2, The relative deflection between the edge of a glass
door and the adjacent wall shall not exceed the thick-
ness of the wall plus Vj inch (12.7 mm) for a drop
height of 48 inches (1219 mm).
2408.3 Gymnasiums and basketball courts. Glazing in mul-
tipurpose gymnasiums, basketball courts and similar athletic
facilities subject to human impact loads shall comply with Cat-
egory II of CPSC 16 CFR 1201 or Class A of ANSI Z97.1,
listed in Chapter 35.
SECTION 2409
GLASS IN ELEVATOR HOISTWAYS
AND ELEVATOR CARS
2409.1 Glass in elevator hoist way enclosures. Glass in eleva-
tor hoistway enclosures and hoistway doors shall be laminated
glass conforming to ANSI Z97, 1 or CPSC 1 6 CFR Part 1 20 1 .
2409.1.1 Fire-resistance-rated hoistways. Glass installed
in hoistways and hoistway doors where the hoistway is
required to have a fire-resistance rating shall also comply
with Section 715.
2409.1.2 Glass hoistway doors. The glass in glass
hoistway doors shall be not less than 60 percent of the total
visible door panel surface area as seen from the landing side.
2010 CALIFORNIA BUILDING CODE
417
GLASS AND GLAZING
2409.2 Glass visions panels. Glass in vision panels in elevator
hoistway doors shall be permitted to be any transparent glazing
material not less than ^1^ inches (0.64 mm) in thickness con-
forming to Class A in accordance with ANSI Z97.1 or Cate-
gory II in accordance with CPSC 16 CFR Part 1201. The area
of any single vision panel shall not be less than 24 square
inches (15 484 mm^) and the total area of one or more vision
panels in any hoistway door shall be not more than 85 square
inches (54 839 mm^).
2409.3 Glass in elevator cars.
2409.3.1 Glass types. Glass in elevator car enclosures,
glass elevator car doors and glass used for lining walls and
ceilings of elevator cars shall be laminated glass conforming
to Class A in accordance with ANSI Z97. 1 or Category II in
accordance with CPSC 16 CFR Part 1201.
Exception: Tempered glass shall be permitted to be used
for lining walls and ceilings of elevator cars provided:
1. The glass is bonded to a nonpolymeric coating,
sheeting or film backing having a physical integ-
rity to hold the fragments when the glass breaks.
2. The glass is not subjected to further treatment such
as sandblasting; etching; heat treatment or painting
that could alter the original properties of the glass.
3. The glass is tested to the acceptance criteria for
laminated glass as specified for Class A in accor-
dance with ANSI Z97.1 or Category II in accor-
dance with CPSC 16 CFR Part 1201 .
2409.3.2 Surface area. The glass in glass elevator car doors
shall be not less than 60 percent of the total visible door panel
surface area as seen from the car side of the doors.
418
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 25 - GYPSUM BOARD AND PLASTER
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
2501.2
X
X
X
X
2503.2
X
X
X
X
2504.2
X
X
X
X
2504.2.1
X
X
X
X
2505.3
X
X
X
X
2507.3
X
X
X
X
2508.5.6
X
X
X
X
2510.7.1
X
X
X
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
419
420 2010 CALIFORNIA BUILDING CODE
CHAPTER 25
GYPSUM BOARD AND PLASTER
SECTION 2501
GENERAL
2501.1 Scope.
2501.1.1 General. Provisions of this chapter shall govern
the materials, design, construction and quality of gypsum
board, lath, gypsum plaster and cement plaster.
2501.1.2 Performance. Lathing, plastering and gypsum
board construction shall be done in the manner and with the
materials specified in this chapter, and when required for
fire protection, shall also comply with the provisions of
Chapter 7.
2501.1.3 Other materials. Other approved wall or ceiling
coverings shall be permitted to be installed in accordance
with the recommendations of the manufacturer and the con-
ditions of approval.
I I 2501.2 Additional requirements. [DSA-SS & DSA-SS/CC]
Details of attachment for wall and ceiling coverings which are
not provided for in these regulations shall be detailed in the
I I approved construction documents.
SECTION 2502
DEFINITIONS
2502.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
CEMENT PLASTER. A mixture of portland or blended
cement, portland cement or blended cement and hydrated lime,
masonry cement or plastic cement and aggregate and other
approved materials as specified in this code.
EXTERIOR SURFACES. Weather-exposed surfaces.
GYPSUM BOARD. Gypsum wallboard, gypsum sheathing,
gypsum base for gypsum veneer plaster, exterior gypsum soffit
board, predecorated gypsum board or water-resistant gypsum
backing board complying with the standards listed in Tables
2506.2, 2507.2 and Chapter 35.
GYPSUM PLASTER. A mixture of calcined gypsum or cal-
cined gypsum and lime and aggregate and other approved
materials as specified in this code.
GYPSUM VENEER PLASTER. Gypsum plaster applied to
an approved base in one or more coats normally not exceeding
V4 inch (6.4 mm) in total thickness.
INTERIOR SURFACES. Surfaces other than weather-
exposed surfaces.
WEATHER-EXPOSED SURFACES. Surfaces of walls,
ceilings, floors, roofs, soffits and similar surfaces exposed to
the weather except the following:
1. Ceilings and roof soffits enclosed by walls, fascia, bulk-
heads or beams that extend a minimum of 12 inches (305
nmi) below such ceiling or roof soffits.
2. Walls or portions of walls beneath an unenclosed roof
area, where located a horizontal distance from an open
exterior opening equal to at least twice the height of the
opening.
3. Ceiling and roof soffits located a minimum horizontal
distance of 10 feet (3048 mm) from the outer edges of the
ceiling or roof soffits.
WIRE BACKING. Horizontal strands of tautened wire
attached to surfaces of vertical supports which, when covered
with the building paper, provide a backing for cement plaster.
SECTION 2503
INSPECTION
2503.1 Inspection. Lath and gypsum board shall be inspected
in accordance with Section 110.3.5, Chapter 7, Division II. I I
2503.2 Additional requirements for inspection and testing.
[DSA-SS, DSA-SS/CC and OSHPD 1&4] II
1. Lath and gypsum board shall be inspected in accordance
with Chapter 1 7 A and Title 24, Part 1. \\
2. No lath or gypsum wallboard or their attachments shall
be covered or finished until it has been inspected and
approved by the inspector of record and/or special
inspector.
3. The enforcement agency may require tests in accor-
dance with Table 2506.2 to determine compliance with \ |
the provisions of these regulations.
4. The testing of gypsum and gypsum products shall con-
form with standards listed in Table 2506.2.
SECTION 2504
VERTICAL AND HORIZONTAL ASSEMBLIES
2504.1 Scope. The following requirements shall be met where
construction involves gypsum board, lath and plaster in vertical
and horizontal assembUes.
2504.1.1 Wood framing. Wood supports for lath or gypsum
board, as well as wood stripping or furring, shall not be less
than 2 inches (5 1 mm) nominal thickness in the least dimen-
sion.
Exception: The minimum nominal dimension of wood
furring strips installed over soHd backing shall not be less
than 1 inch by 2 inches (25 mm by 51 mm).
2504.1.2 Studless partitions. The minimum thickness of
vertically erected studless solid plaster partitions of Vg-inch
(9.5 mm) and ^-inch (19.1 mm) rib metal lath or
2010 CALIFORNIA BUILDING CODE
421
GYPSUM BOARD AND PLASTER
V2-inch-thick (12.7 mm) long-length gypsum lath and gyp-
sum board partitions shall be 2 inches (51 mm).
I I 2504,2 Additional requirements. [DSA'SS, DSA-SS/CCand
OSHPD 1 &4]In addition to the requirements of this section,
the horizontal and vertical assemblies of plaster or gypsum
board shall be designed to resist the loads specified in Chapter
16A of this code. For wood framing, see Chapter 23, For metal
I I framing, see Chapter 22A ([DSA/SS/CC] Chapter 22). For
suspended acoustical ceiling systems, see Section 2506. For
gypsum construction see Section 2508.
2504,2.1 Wood furring strips. Wood furring strips for ceil-
ings fastened to floor or ceiling joist shall be nailed at each
bearing with two common wire nails, one of which shall be a
slant nail and the other a face nail, or by one nail having spi-
rally grooved or annular grooved shanks approved by the
enforcement agency for this purpose. All stripping nails
shall penetrate not less than 7% inches (44.5 mm) into the
member receiving the point Holes in stripping at joints
shall be subdrilled to prevent splitting.
Where common wire nails are used to support horizontal
wood stripping for plaster ceilings, such stripping shall be
wire tied to the joists 4 feet (1219 mm) on center with two
strands of No. 18 W&M gage galvanized annealed wire to
an 8d common wire nail driven into each side of the joist 2
inches (51 mm) above the bottom of the joist or to each end
ofal6d common wire nail driven horizontally through the
joist 2 inches (51 mm) above the bottom of the joist, and the
ends of the wire secured together with three twists of the
wire.
SECTION 2505
SHEAR WALL CONSTRUCTION
2505.1 Resistance to shear (wood framing). Wood-framed
shear walls sheathed with gypsum board, lath and plaster shall
be designed and constructed in accordance with Section
2306.7 and are permitted to resist wind and seismic loads.
Walls resisting seismic loads shall be subject to the limitations
in Section 12.2.1 of ASCE 7,
2505.2 Resistance to shear (steel framing). Cold-formed
steel-framed shear walls sheathed with gypsum board and con-
structed in accordance with the materials and provisions of
Section 2210.6 are permitted to resist wind and seismic loads.
Walls resisting seismic loads shall be subject to the limitations
in Section 12.2.1 of ASCE 7.
I 2505J [DSA-SS, DSA-SS/CCandOSHPD 1,2 & 4] Sections
2505.1 and 2505.2 are not permitted.
SECTION 2506
GYPSUM BOARD MATERIALS
2506.1 General. Gypsum board materials and accessories
shall be identified by the manufacturer's designation to indi-
cate compliance with the appropriate standards referenced in
this section and stored to protect such materials from the
weather.
2506.2 Standards. Gypsum board materials shall conform to
the appropriate standards listed in Table 2506.2 and Chapter 35
and, where required for fire protection, shall conform to the
provisions of Chapter 7.
TABLE 2506.2
GYPSUM BOARD MATERIALS AND ACCESSORIES
MATERIAL
STANDARD
Accessories for gypsum board
ASTM C 1047
Adhesives for fastening gypsum
wallboard
ASTM C 557
Elastomeric joint sealants
ASTM C 920
Exterior soffit board
ASTM C 931
Fiber-reinforced gypsum panels
ASTM C 1278
Glass mat gypsum backing panel
ASTM C 1178
Glass mat gypsum panel
ASTM C 1658
Glass mat gypsum substrate
ASTM CI 177
Gypsum backing board and gypsum
shaftliner board
ASTM C 442
Gypsum ceiUng board
ASTM C 1395
Gypsum sheathing
ASTM C 79
Gypsum wallboard
ASTM C 36
Joint reinforcing tape and compound
ASTM C 474; C 475
Nails for gypsum boards
ASTM C 514,
F 547, F 1667
Predecorated gypsum board
ASTM C 960
Steel screws
ASTM C 954; C 1002
Steel studs, load-bearing
ASTM C 955
Steel studs, nonload-bearing
ASTM C 645
Standard specification for gypsum board
ASTM C 1396
Testing gypsum and gypsum products
ASTM C 22; C 472;
C473
Water-resistant gypsum backing board
ASTM C 630
2506.2.1 Other materials. Metal suspension systems for
acoustical and lay-in panel ceilings shall conform with
ASTM C 635 Usted in Chapter 35 and Section 13.5.6 of
ASCE 7 for installation in high seismic areas.
SECTION 2507
LATHING AND PLASTERING
2507.1 General. Lathing and plastering materials and accesso-
ries shall be marked by the manufacturer's designation to indi-
cate compliance with the appropriate standards referenced in
this section and stored in such a manner to protect them from
the weather.
422
2010 CALIFORNIA BUILDING CODE
GYPSUM BOARD AND PLASTER
2507.2 Standards. Lathing and plastering materials shall con-
form to the standards listed in Table 2507.2 and Chapter 35
and, where required for fire protection, shall also conform to
the provisions of Chapter 7.
TABLE 2507.2
LATH, PLASTERING MATERIALS AND ACCESSORIES
MATERIAL
STANDARD
Accessories for gypsum veneer base
ASTM C 1047
Blended cement
ASTM C 595
Exterior plaster bonding compounds
ASTM C 932
Gypsum base for veneer plasters
ASTM C 588
Gypsum casting and molding plaster
ASTM C 59
Gypsum Keene's cement
ASTM C 61
Gypsum lath
ASTM C 37
Gypsum plaster
ASTM C 28
Gypsum veneer plaster
ASTM C 587
Interior bonding compounds, gypsum
ASTM C 631
Lime plasters
ASTM C 5; C 206
Masonry cement
ASTM C 91
Metal lath
ASTM C 847
Piaster aggregates
Sand
Periite
Vermiculite
ASTM C 35; C 897
ASTM C 35
ASTM C 35
Plastic cement
ASTM C 1328
Portland cement
ASTM C 150
Steel screws
ASTM C 1002; C 954
Steel studs and track
ASTM C 645; C 955
Welded wire lath
ASTM C 933
Woven wire plaster base
ASTM C 1032
2507.3 Lath attachment to horizontal wood supports.
[DSA'SS, DSA-SS/CC and OSHPD 1&4] Where interior or
exterior lath is attached to horizontal wood supports, either of
the following attachments shall be used in addition to the meth-
ods of attachment described in referenced standards listed in
Table 2507.2.
1. Secure lath to alternate supports with ties consisting of a
double strand of No. 18 W <& M gage galvanized
annealed wire at one edge of each sheet of lath. Wire ties
shall be installed not less than 3 inches (76 mm) back
from the edge of each sheet and shall be looped around
stripping, or attached to an 8d common wire nail driven
into each side of the joist 2 inches (51 mm) above the bot-
tom of the joist or to each end of a 16d common wire nail
driven horizontally through the joist 2 inches (51 mm)
above the bottom of the joist and the ends of the wire
secured together with three twists of the wire.
2. Secure lath to each support with ^/2-inch-wide (12.7
mm), P/2-inch-long (38 mm) No. 9WSlM gage, ring
shank, hook staple placed around a lOd common nail
laid flat under the surface of the lath not more than 3
inches (76 mm) from edge of each sheet. Such staples
may be placed over ribs ofVg-inch (9.5 mm) rib lath or
over back wire of welded wire fabric or other approved
lath, omitting the lOd nails.
SECTION 2508
GYPSUM CONSTRUCTION
2508.1 General. Gypsum board and gypsum plaster construc-
tion shall be of the materials Hsted in Tables 2506.2 and 2507.2.
These materials shall be assembled and installed in compliance
with the appropriate standards listed in Tables 2508.1 and
2511.1.1, and Chapter 35.
TABLE 2508.1
INSTALLATION OF GYPSUM CONSTRUCTION
MATERIAL
STANDARD
Gypsum board
GA-216; ASTM C 840
Gypsum sheathing
ASTM C 1280
Gypsum veneer base
ASTM C 844
Interior lathing and furring
ASTM C 841
Steel framing for gypsum boards
ASTM C 754; C 1007
2508.2 Limitations. Gypsum wallboard or gypsum plaster
shall not be used in any exterior surface where such gypsum
construction will be exposed directly to the weather. Gypsum
wallboard shall not be used where there will be direct exposure
to water or continuous high humidity conditions. Gypsum
sheathing shall be installed on exterior surfaces in accordance
with ASTM C1280.
2508.2.1 Weather protection. Gypsum wallboard, gypsum
lath or gypsum plaster shall not be installed until weather
protection for the installation is provided.
2508.3 Single-ply application. Edges and ends of gypsum
board shall occur on the framing members, except those edges
and ends that are perpendicular to the framing members. Edges
and ends of gypsum board shall be in moderate contact except
in concealed spaces where fire-resistance-rated construction,
shear resistance or diaphragm action is not required.
2508.3.1 Floating angles. Fasteners at the top and bottom
plates of vertical assemblies, or the edges and ends of hori-
zontal assemblies perpendicular to supports, and at the wall
line are permitted to be omitted except on shear resisting
elements or fire-resistance-rated assemblies. Fasteners shall
be applied in such a manner as not to fracture the face paper
with the fastener head.
2508.4 Joint treatment. Gypsum board fire-resistance-rated
assemblies shall have joints and fasteners treated.
Exception: Joint and fastener treatment need not be pro-
vided where any of the following conditions occur:
1. Where the gypsum board is to receive a decorative
finish such as wood paneling, battens, acoustical fin-
ishes or any similar apphcation that would be equiva-
lent to joint treatment.
2. On single-layer systems where joints occur over
wood framing members.
2010 CALIFORNIA BUILDING CODE
423
GYPSUM BOARD AND PLASTER
3. Square edge or tongue-and- groove edge gypsum
board (V-edge), gypsum backing board or gypsum
sheathing.
4. On multilayer systems where the joints of adjacent
layers are offset from one to another.
5. Assemblies tested without joint treatment.
2508.5 Horizontal gypsum board diaphragm ceilings. Gyp-
sum board shall be permitted to be used on wood joists to create
a horizontal diaphragm ceiling in accordance with Table
2508.5.
2508.5.1 Diaphragm proportions. The maximum allow-
able diaphragm proportions shall be V/2'l between shear
resisting elements. Rotation or cantilever conditions shall
not be permitted.
2508.5.2 Installation. Gypsum board used in a horizontal
diaphragm ceiling shall be installed perpendicular to ceiling
framing members. End joints of adjacent courses of gypsum
board shall not occur on the same joist.
2508.5.3 Blocking of perimeter edges. All perimeter edges
shall be blocked using a wood member not less than 2-inch
by 6-inch (51 mm by 159 mm) nominal dimension. Block-
ing material shall be installed flat over the top plate of the
wall to provide a nailing surface not less than 2 inches (5 1
mm) in width for the attachment of the gypsum board.
2508.5.4 Fasteners. Fasteners used for the attachment of
gypsum board to a horizontal diaphragm ceiling shall be as
defined in Table 2508.5. Fasteners shall be spaced not more
than 7 inches (178 mm) on center (o.c.) at all supports,
including perimeter blocking, and not more than Vg inch
(9.5 mm) from the edges and ends of the gypsum board,
2508.5.5 Lateral force restrictions. Gypsum board shall
not be used in diaphragm ceilings to resist lateral forces
imposed by masonry or concrete construction.
2508.5.6 Diaphragm ceiling connection to partitions.
[DSA-SS, DSA-SS/CCand OSHPD 1&4] Gypsum board
shall not be used in diaphragm ceilings to resist lateral
forces imposed by partitions. Connection of diaphragm
ceiling to the vertical lateral force resisting elements shall
be designed and detailed to transfer lateral forces.
SECTION 2509
GYPSUM BOARD IN SHOWERS
AND WATER CLOSETS
2509.1 Wet areas. Showers and public toilet walls shall con-
form to Sections 1210,2 and 1210.3.
2509.2 Base for tile. Glass mat water-resistant gypsum back-
ing panels, discrete nonasbestos fiber-cement interior substrate
sheets or nonasbestos fiber-mat reinforced cement substrate
sheets in compliance with ASTM C 1178, C 1288 or C 1325
and installed in accordance with manufacturer recommenda-
tions shall be used as a base for wall tile in tub and shower areas
and wall and ceiling panels in shower areas. Water-resistant
gypsum backing board shall be used as a base for tile in water
closet compartment walls when installed in accordance with
GA-216 or ASTM C 840 and manufacturer recommendations.
Regular gypsum wallboard is permitted under tile or wall pan-
els in other wall and ceiling areas when installed in accordance
with GA-216 or ASTM C 840.
2509.3 Limitations. Water-resistant gypsum backing board
shall not be used in the following locations:
1. Over a vapor retarder in shower or bathtub compart-
ments.
2. Where there will be direct exposure to water or in areas
subject to continuous high humidity.
3. On ceilings where frame spacing exceeds 12 inches (305
mm) o.c. for Vj-inch-thick (12.7 mm) water-resistant
gypsum backing board and more than 16 inches (406
mm) o.c. for Vg-inch-thick (15.9 mm) water-resistant
gypsum backing board.
SECTION 2510
LATHING AND FURRING FOR
CEMENT PLASTER (STUCCO)
2510.1 General. Exterior and interior cement plaster and lath-
ing shall be done with the appropriate materials listed in Table
2507.2 and Chapter 35.
2510.2 Weather protection. Materials shall be stored in such a
manner as to protect such materials from the weather.
TABLE 2508.5
SHEAR CAPACITY FOR HORIZONTAL WOOD FRAMED GYPSUM BOARD DIAPHRAGM CEILING ASSEMBLIES
MATERIAL
THICKNESS OF MATERIAL
(MINIMUM) (inches)
SPACING OF FRAMING MEMBERS
(MAXIMUM) (inches)
SHEAR VALUE^''
(pif of ceiling)
MIMIMUM FASTENER SIZE
Gypsum board
%
16 O.C.
90
5d cooler or wallboard nail;
l^/g-inch long; 0.086-inch shank;
^Vfi4 -inch head'^
Gypsum board
%
24 o.c.
70
5d cooler or wallboard nail;
1%-inch long; 0.086-inch shank;
1^64 -inch head'^
For SI: 1 inch = 25.4 mm, 1 pound per foot =14.59 N/m. <»
a. Values are not cumulative with other horizontal diaphragm values and are for short-term loading due to wind or seismic loading. Values shall be reduced 25 percent
for normal loading.
b. Values shall be reduced 50 percent in Seismic Design Categories D, E and F.
c. 1 V4-inch, No. 6 Type S or W screws are permitted to be substituted for the listed nails.
424
2010 CALIFORNIA BUILDING CODE
GYPSUM BOARD AND PLASTER
2510.3 Installation. Installation of these materials shall be in
compliance with ASTM C 926 and ASTM C 1063.
2510.4 Corrosion resistance. Metal lath and lath attachments
shall be of corrosion-resistant material,
2510.5 Backing. Backing or a lath shall provide sufficient
rigidity to permit plaster applications.
2510.5.1 Support of lath. Where lath on vertical surfaces
extends between rafters or other similar projecting mem-
bers, solid backing shall be installed to provide support for
lath and attachments.
2510.5.2 Use of gypsum backing board.
2510.5.2.1 Use of gypsum board as a backing board.
Gypsum lath or gypsum wallboard shall not be used as a
backing for cement plaster.
Exception: Gypsum lath or gypsum wallboard is per-
mitted, with a water-resistive barrier, as a backing for
self-furred metal lath or self-furred wire fabric lath
and cement plaster where either of the following con-
ditions occur:
1. On horizontal supports of ceilings or roof sof-
fits.
2. On interior walls.
2510.5.2.2 Use of gypsum sheathing backing. Gypsum
sheathing is permitted as a backing for metal or wire fab-
ric lath and cement plaster on walls. A water-resistive
barrier shall be provided in accordance with Section
2510.6.
2510.5.3 Backing not required. Wire backing is not
required under expanded metal lath or paperbacked wire
fabric lath.
2510.6 Water-resistive barriers. Water-resistive barriers
shall be installed as required in Section 1404.2 and, where
applied over wood-based sheathing, shall include a
water-resistive vapor-permeable barrier with a performance at
least equivalent to two layers of Grade D paper.
Exception: Where the water-resistive barrier that is
applied over wood-based sheathing has a water resistance
equal to or greater than that of 60-minute Grade D paper and
is separated from the stucco by an intervening, substantially
nonwater-absorbing layer or drainage space.
2510.7 Preparation of masonry and concrete. Surfaces shall
be clean, free from efflorescence, sufficiently damp and rough
for proper bond. If the surface is insufficiently rough, approved
bonding agents or a portland cement dash bond coat mixed in
proportions of not more than two parts volume of sand to one
part volume of portland cement or plastic cement shall be
applied. The dash bond coat shall be left undisturbed and shall
be moist cured not less than 24 hours.
2510,7.1 Additional requirements. [DSA-SS, DSA-SS/CC
and OSHPD 1&4] Bonding agents shall conform with the
provisions of United States Government Military Specifica-
tions MIL-B-19235.
SECTION 2511
INTERIOR PLASTER
2511.1 General. Plastering gypsum plaster or cement plaster
shall not be less than three coats where applied over metal lath
or wire fabric lath and not less than two coats where applied
over other bases permitted by this chapter.
Exception: Gypsum veneer plaster and cement plaster spe-
cifically designed and approved for one-coat applications.
2511.1.1 Installation. Installation of lathing and plaster
materials shall conform with Table 2511.1.1 and Section
2507.
TABLE 2511.1.1
INSTALLATION OF PLASTER CONSTRUCTION
MATERIAL
STANDARD
Cement plaster
ASTM C 926
Gypsum plaster
ASTM C 842
Gypsum veneer plaster
ASTM C 843
Interior lathing and furring
(gypsum plaster)
ASTM C 841
Lathing and furring (cement plaster)
ASTM C 1063
Steel framing
ASTM C 754; C 1007
2511.2 Limitations. Plaster shall not be applied directly to
fiber insulation board. Cement plaster shall not be applied
directly to gypsum lath or gypsum plaster except as specified in
Sections 2510.5.1 and 2510.5.2.
2511.3 Grounds. Where installed, grounds shall ensure the
minimum thickness of plaster as set forth in ASTM C 842 and
ASTM C 926. Plaster thickness shall be measured from the
face of lath and other bases.
2511.4 Interior masonry or concrete. Condition of surfaces
shall be as specified in Section 2510.7. Approved specially pre-
pared gypsum plaster designed for application to concrete sur-
faces or approved acoustical plaster is permitted. The total
thickness of base coat plaster applied to concrete ceilings shall
be as set forth in ASTM C 842 or ASTM C 926. Should ceiling
surfaces require more than the maximum thickness permitted
in ASTM C 842 or ASTM C 926, metal lath or wire fabric lath
shall be installed on such surfaces before plastering.
2511.5 Wet areas. Showers and public toilet walls shall con-
form to Sections 1210.2 and 1210.3. When wood frame walls
and partitions are covered on the interior with cement plaster or
tile of similar material and are subject to water splash, the fram-
ing shall be protected with an approved moisture barrier.
SECTION 2512
EXTERIOR PLASTER
2512.1 General. Plastering with cement plaster shall be not
less than three coats when applied over metal lath or wire fabric
lath or gypsum board backing as specified in Section 2510.5
and shall be not less than two coats when applied over masonry
or concrete. If the plaster surface is to be completely covered by
veneer or other facing material, or is completely concealed by
another wall, plaster application need only be two coats, pro-
vided the total thickness is as set forth in ASTM C 926.
2010 CALIFORNIA BUILDING CODE
425
GYPSUM BOARD AND PLASTER
2512.1.1 On-grade floor slab. On wood framed or steel
stud construction with an on-grade concrete floor slab sys-
tem, exterior plaster shall be applied in such a manner as to
cover, but not to extend below, the lath and paper. The appli-
cation of lath, paper and flashing or drip screeds shall com-
ply with ASTM C 1063.
2512.1.2 Weep screeds. A minimum 0.019-inch (0.48 mm)
(No. 26 galvanized sheet gage), corrosion-resistant weep
screed with a minimum vertical attachment flange of 3V2
inches (89 mm) shall be provided at or below the foundation
plate line on exterior stud walls in accordance with ASTM C
926. The weep screed shall be placed a minimum of 4 inches
(102 mm) above the earth or 2 inches (5 1 mm) above paved
areas and be of a type that will allow trapped water to drain
to the exterior of the building. The water-resistive barrier
shall lap the attachment flange. The exterior lath shall cover
and terminate on the attachment flange of the weep screed.
2512.2 Plasticity agents. Only approved plasticity agents and
approved amounts thereof shall be added to portland cement or
blended cements. When plastic cement or masonry cement is
used, no additional lime or plasticizers shall be added.
Hydrated lime or the equivalent amount of lime putty used as a
plasticizer is permitted to be added to cement plaster or cement
and hme plaster in an amount not to exceed that set forth in
ASTM C 926.
2512.3 Limitations. Gypsum plaster shall not be used on exte-
rior surfaces.
2512.4 Cement plaster. Plaster coats shall be protected from
freezing for a period of not less than 24 hours after set has
occurred. Plaster shall be applied when the ambient tempera-
ture is higher than 40°F (4°C), unless provisions are made to
keep cement plaster work above 40°F (4°C) during application
and 48 hours thereafter.
2512.5 Second-coat application. The second coat shall be
brought out to proper thickness, rodded and floated sufficienfly
rough to provide adequate bond for the finish coat. The second
coat shall have no variation greater than V4 inch (6.4 mm) in any
direction under a 5-foot (1524 mm) straight edge.
2512.6 Curing and interval. First and second coats of cement
plaster shall be applied and moist cured as set forth in ASTM C
926 and Table 2512.6.
TABLE 2512.6
CEMENT PLASTERS^
COAT
MINIMUM PERIOD MOIST
CURING
MINIMUM INTERVAL
BETWEEN COATS
First
48 hours^
48 hours''
Second
48 hours
7 days^
Finish
—
Notec
a. The first two coats shall be as required for the first coats of exterior plaster,
except that the moist-curing time period between the first and second coats
shall not be less than 24 hours. Moist curing shall not be required where job
and weather conditions are favorable to the retention of moisture in the
cement plaster for the required time period.
b. Twenty-four-hour minimum interval between coats of interior cement plas-
ter. For alternate method of application, see Section 2512.8.
c. Finish coat plaster is permitted to be applied to interior cement plaster base
coats after a 48-hour period.
2512.7 Application to solid backings. Where appHed over
gypsum backing as specified in Section 2510.5 or directly to
unit masonry surfaces, the second coat is permitted to be
apphed as soon as the first coat has attained sufficient hardness.
2512.8 Alternate method of application. The second coat is
permitted to be appHed as soon as the first coat has attained suf-
ficiently rigidity to receive the second coat.
2512.8.1 Admixtures. When using this method of applica-
tion, calcium aluminate cement up to 15 percent of the
weight of the portland cement is permitted to be added to the
mix.
2512.8.2 Curing. Curing of the first coat is permitted to be
omitted and the second coat shall be cured as set forth in
ASTM C 926 and Table 2512.6.
2512.9 Finish coats. Cement plaster finish coats shall be
applied over base coats that have been in place for the time peri-
ods set forth in ASTM C 926. The third or finish coat shall be
applied with sufficient material and pressure to bond and to
cover the brown coat and shall be of sufficient thickness to con-
ceal the brown coat.
SECTION 2513
EXPOSED AGGREGATE PLASTER
2513.1 General. Exposed natural or integrally colored aggre-
gate is permitted to be partially embedded in a natural or col-
ored bedding coat of cement plaster or gypsum plaster, subject
to the provisions of this section.
2513.2 Aggregate. The aggregate shall be applied manually or
mechanically and shall consist of marble chips, pebbles or sim-
ilar durable, moderately hard (three or more on the Mohs hard-
ness scale), nonreactive materials.
2513.3 Bedding coat proportions. The bedding coat for inte-
rior or exterior surfaces shall be composed of one part portland
cement and one part Type S lime; or one part blended cement
and one part Type S lime; or masonry cement; or plastic
cement, and a maximum of three parts of graded white or natu-
ral sand by volume. The bedding coat for interior surfaces shall
be composed of 100 pounds (45.4 kg) of neat gypsum plaster
and a maximum of 200 pounds (90.8 kg) of graded white sand.
A factory-prepared bedding coat for interior or exterior use is
permitted. The bedding coat for exterior surfaces shall have a
minimum compressive strength of 1,000 pounds per square
inch (psi) (6895 kPa).
2513.4 Application. The bedding coat is permitted to be
applied directly over the first (scratch) coat of plaster, provided
the ultimate overall thickness is a minimum of % inch (22 mm),
including lath. Over concrete or masonry surfaces, the overall
thickness shall be a minimum of V2 inch (12.7 mm).
2513.5 Bases. Exposed aggregate plaster is permitted to be
applied over concrete, masonry, cement plaster base coats or
gypsum plaster base coats installed in accordance with Section
2511 or 2512.
2513.6 Preparation of masonry and concrete. Masonry and
concrete surfaces shall be prepared in accordance with the pro-
visions of Section 2510.7.
426
2010 CALIFORNIA BUILDING CODE
GYPSUM BOARD AND PLASTER
2513.7 Curing of base coats. Cement plaster base coats shall
be cured in accordance with ASTM C 926. Cement plaster bed-
ding coats shall retain sufficient moisture for hydration (hard-
ening) for 24 hours minimum or, where necessary, shall be kept
damp for 24 hours by light water spraying.
2010 CALIFORNIA BUILDING CODE
427
428 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 26 - PLASTIC
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
429
430 201 CALIFORNIA BUILDING CODE
CHAPTER 26
PLASTIC
SECTION 2601
GENERAL
2601.1 Scope. These provisions shall govern the materials,
design, application, construction and installation of foam plas-
tic, foam plastic insulation, plastic veneer, interior plastic finish
and trim and light-transmitting plastics. See Chapter 14 for
requirements for exterior wall finish and trim.
SECTION 2602
DEFINITIONS
2602.1 General. The following vv^ords and terms shall, for the
purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
FIBER REINFORCED POLYMER. A polymeric compos-
ite material consisting of reinforcement fibers impregnated
with a fiber-binding polymer which is then molded and hard-
ened.
FIBERGLASS REINFORCED POLYMER. A polymeric
composite material consisting of glass reinforcement fibers
impregnated with a fiber-binding polymer which is then
molded and hardened.
FOAM PLASTIC INSULATION. A plastic that is intention-
ally expanded by the use of a foaming agent to produce a
reduced-density plastic containing voids consisting of open or
closed cells distributed throughout the plastic for thermal insu-
lating or acoustical purposes and that has a density less than 20
pounds per cubic foot (pcf) (320 kg/m^).
LIGHT-DIFFUSING SYSTEM. Construction consisting in
whole or in part of lenses, panels, grids or baffles made with
light-transmitting plastics positioned below independently
mounted electrical light sources, skylights or light-transmitting
plastic roof panels. Lenses, panels, grids and baffles that are
part of an electrical fixture shall not be considered as a
light-diffusing system.
LIGHT-TRANSMITTING PLASTIC ROOF PANELS.
Structural plastic panels other than skylights that are fastened
to structural members, or panels or sheathing and that are used
as hght-transmitting media in the plane of the roof.
LIGHT-TRANSMITTING PLASTIC WALL PANELS.
Plastic materials that are fastened to structural members, or to
structural panels or sheathing, and that are used as light-trans-
mitting media in exterior walls,
PLASTIC, APPROVED. Any thermoplastic, thermosetting
or reinforced thermosetting plastic material that conforms to
combustibility classifications specified in the section applica-
ble to the application and plastic type.
PLASTIC GLAZING. Plastic materials that are glazed or set
in frame or sash and not held by mechanical fasteners that pass
through the glazing material.
THERMOPLASTIC MATERIAL. A plastic material that is
capable of being repeatedly softened by increase of tempera-
ture and hardened by decrease of temperature.
THERMOSETTING MATERIAL. A plastic material that is
capable of being changed into a substantially nonreformable
product when cured.
SECTION 2603
FOAM PLASTIC INSULATION
2603.1 General. The provisions of this section shall govern the
requirements and uses of foam plastic insulation in buildings
and structures.
2603.2 Labeling and identification. Packages and containers
of foam plastic insulation and foam plastic insulation compo-
nents delivered to the job site shall bear the label of an
approved agency showing the manufacturer's name, product
hsting, product identification and information sufficient to
determine that the end use will comply with the code require-
ments.
2603.3 Surface-burning characteristics. Unless otherwise
indicated in this section, foam plastic insulation and foam plas-
tic cores of manufactured assemblies shall have a flame spread
index of not more than 75 and a smoke-developed index of not
more than 450 where tested in the maximum thickness
intended for use in accordance with ASTM E 84 or UL 723.
Loose fill-type foam plastic insulation shall be tested as board
stock for the flame spread and smoke-developed indexes.
Exceptions:
1. Smoke-developed index for interior trim as provided
for in Section 2604.2.
2. In cold storage buildings, ice plants, food plants, food
processing rooms and similar areas, foam plastic
insulation where tested in a thickness of 4 inches (102
mm) shall be permitted in a thickness up to 10 inches
(254 mm) where the building is equipped throughout
with an automatic fire sprinkler system in accordance
with Section 903.3.1.1. The approved automatic
sprinkler system shall be provided in both the room
and that part of the building in which the room is
located.
3 . Foam plastic insulation that is a part of a Class A, B or
C roof-covering assembly provided the assembly
with the foam plastic insulation satisfactorily passes
FM 4450 or UL 1256. The smoke-developed index
shall not be limited for roof applications.
4. Foam plastic insulation greater than 4 inches (102
mm) in thickness shall have a maximum flame spread
index of 75 and a smoke-developed index of 450
where tested at a minimum thickness of 4 inches (102
mm), provided the end use is approved in accordance
2010 CALIFORNIA BUILDING CODE
431
PLASTIC
with Section 2603.9 using the thickness and density
intended for use.
5. Flame spread and smoke-developed indexes for foam
plastic interior signs in covered mall buildings pro-
vided the signs comply with Section 402.15.
2603.4 Thermal barrier. Except as provided for in Sections
2603.4.1 and 2603.9, foam plastic shall be separated from the
interior of a building by an approved thermal barrier of Vj-inch
(12.7 mm) gypsum wallboard or equivalent thermal barrier
material that will limit the average temperature rise of the unex-
posed surface to not more than 250°F (120°C) after 15 minutes
of fire exposure, complying with the standard time-tempera-
ture curve of ASTM E 1 19 or UL 263. The thermal barrier shall
be installed in such a manner that it will remain in place for 15
minutes based on FM 4880, UL 1040, NFPA 286 or UL 1715.
Combustible concealed spaces shall comply with Section 717.
2603.4.1 Thermal barrier not required. The thermal bar-
rier specified in Section 2603.4 is not required under the
conditions set forth in Sections 2603 .4. LI through
2603.4.1.13.
2603.4.1.1 Masonry or concrete construction. A ther-
mal barrier is not required for foam plastic installed in a
masonry or concrete wall, floor or roof system where the
foam plastic insulation is covered on each face by a mini-
mum of 1 inch (25 mm) thickness of masonry or con-
crete.
2603.4.1.2 Cooler and freezer walls. Foam plastic
installed in a maximum thickness of 10 inches (254 mm)
in cooler and freezer walls shall:
1. Have a flame spread index of 25 or less and a
smoke-developed index of not more than 450,
where tested in a minimum 4 inch (102 mm) thick-
ness.
2. Have flash ignition and self-ignition temperatures
of not less than 600°F and 800°F (316°C and
427°C), respectively.
3. Have a covering of not less than 0.032-inch (0.8
mm) aluminum or corrosion-resistant steel having
a base metal thickness not less than 0.0160 inch
(0.4 mm) at any point.
4. Be protected by an automatic sprinkler system in
accordance with Section 903.3.1.1. Where the
cooler or freezer is within a building, both the
cooler or freezer and that part of the building in
which it is located shall be sprinklered.
2603.4.1.3 Walk-in coolers. In nonsprinklered build-
ings, foam plastic having a thickness that does not
exceed 4 inches (102 mm) and a maximum flame spread
index of 75 is permitted in walk-in coolers or freezer
units where the aggregate floor area does not exceed 400
square feet (37 m^) and the foam plastic is covered by a
metal facing not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a minimum
base metal thickness of 0.016 inch (0.41 mm). A thick-
ness of up to 10 inches (254 mm) is permitted where pro-
tected by a thermal barrier.
2603.4.1.4 Exterior walls— -one-story buildings. For
ont-story buildings, foam plastic having a flame spread
index of 25 or less, and a smoke-developed index of not
more than 450, shall be permitted without thermal barri-
ers in or on exterior walls in a thickness not more than 4
inches (102 mm) where the foam plastic is covered by a
thickness of not less than 0.032-inch-thick (0.81 mm)
aluminum or corrosion-resistant steel having a base
metal thickness of 0.0160 inch (0.41 mm) and the build-
ing is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1.
2603.4.1.5 Roofing. Foam plastic insulation under a roof
assembly or roof covering that is installed in accordance
with the code and the manufacturer's instructions shall
be separated from the interior of the building by wood
structural panel sheathing not less than 0.47 inch (11.9
mm) in thickness bonded with exterior glue, with edges
supported by blocking, tongue-and -groove joints or
other approved type of edge support, or an equivalent
material. A thermal barrier is not required for foam plas-
tic insulation that is a part of a Class A, B or C roof-cover-
ing assembly, provided the assembly with the foam
plastic insulation satisfactorily passes FM 4450 or UL
1256.
2603.4.1.6 Attics and crawl spaces. Within an attic or
crawl space where entry is made only for service of utili-
ties, foam plastic insulation shall be protected against
ignition by 1 V2-inch- thick (38 mm) mineral fiber insula-
tion; V4-inch-thick (6.4 mm) wood structural panel,
particleboard or hardboard; Vg-inch (9.5 mm) gypsum
wallboard, corrosion-resistant steel having a base metal
thickness of 0.016 inch (0.4 mm) or other approved
material installed in such a manner that the foam plastic
insulation is not exposed. The protective covering shall
be consistent with the requirements for the type of con-
struction.
2603.4.1.7 Doors not required to have a fire protec-
tion rating. Where pivoted or side-hinged doors are per-
mitted without a fire protection rating, foam plastic
insulation, having a flame spread index of 75 or less and a
smoke-developed index of not more than 450, shall be
permitted as a core material where the door facing is of
metal having a minimum thickness of 0.032-inch (0.8
mm) aluminum or steel having a base metal thickness of
not less than 0.016 inch (0.4 mm) at any point.
2603.4.1.8 Exterior doors in buildings of Group R-2
or R-3. In occupancies classified as Group R-2 or R-3,
foam-filled exterior entrance doors to individual dwell-
ing units that do not require a fire-resistance rating shall
be faced with wood or other approved materials.
2603.4.1.9 Garage doors. Where garage doors are per-
mitted without a fire-resistance rating and foam plastic is
used as a core material, the door facing shall be metal
having a minimum thickness of 0.032-inch (0.8 mm) alu-
minum or 0.010-inch (0.25 mm) steel or the facing shall
be minimum 0.125-inch-thick (3.2 mm) wood. Garage
doors having facings other than those described above
432
2010 CALIFORNIA BUILDING CODE
PLASTIC
shall be tested in accordance with, and meet the accep-
tance criteria of, DASMA 107.
Exception: Garage doors using foam plastic insula-
tion complying with Section 2603.3 in detached and
attached garages associated with one- and two-family
dwellings need not be provided with a thermal barrier.
2603.4.1.10 Siding backer board. Foam plastic insula-
tion of not more than 2,000 British thermal units per
square feet (Btu/sq. ft.) (22.7 mJ/m^) as determined by
NFPA 259 shall be permitted as a siding backer board
with a maximum thickness of V2 inch (12.7 mm), pro-
vided it is separated from the interior of the building by
not less than 2 inches (5 1 mm) of mineral fiber insulation
or equivalent or where applied as insulation with residing
over existing wall construction.
2603.4.1.11 Interior trim. Foam plastic used as interior
trim in accordance with Section 2604 shall be permitted
without a thermal barrier.
2603.4.1.12 Interior signs. Foam plastic used for inte-
rior signs in covered mall buildings in accordance with
Section 402. 16 shall be permitted without a thermal bar-
rier. Foam plastic signs that are not affixed to interior
building surfaces shall comply with Chapter 8 of the
International Fire Code.
2603.4.1.13 Type V construction. Foam plastic spray
applied to a sill plate and header of Type V construction
is subject to all of the following:
1. The maximum thickness of the foam plastic shall
be 3V4 inches (82.6 nun).
2. The density of the foam plastic shall be in the range
of 1.5 to 2.0 pcf (24 to 32 kg/m^).
3 . The foam plastic shall have a flame spread index of
25 or less and an accompanying smoke-developed
index of 450 or less when tested in accordance
with ASTM E 84 or UL 723.
2603.5 Exterior walls of buildings of any height. Exterior
walls of buildings of Type 1, 11, III or IV construction of any
height shall comply with Sections 2603,5.1 through 2603.5.7.
Exterior walls of cold storage buildings required to be con-
structed of noncombustible materials, where the building is
more than one story in height, shall also comply with the provi-
sions of Sections 2603.5.1 through 2603.5.7. Exterior walls of
buildings of Type V construction shall comply with Sections
2603.2, 2603.3 and 2603.4.
2603.5.1 Fire-resistance-rated walls. Where the wall is
required to have a fire-resistance rating, data based on tests
conducted in accordance with ASTM E 1 19 or UL 263 shall
be provided to substantiate that the fire-resistance rating is
maintained.
2603.5.2 Thermal barrier. Any foam plastic insulation
shall be separated from the building interior by a thermal
barrier meeting the provisions of Section 2603.4, unless
special approval is obtained on the basis of Section 2603.9.
Exception: One-story buildings complying with Section
2603.4.1.4.
2603.5.3 Potential heat. The potential heat of foam plastic
insulation in any portion of the wall or panel shall not
exceed the potential heat expressed in Btu per square feet
(mJ/m^) of the foam plastic insulation contained in the wall
assembly tested in accordance with Section 2603.5.5. The
potential heat of the foam plastic insulation shall be deter-
mined by tests conducted in accordance with NFPA 259 and
the results shall be expressed in Btu per square feet (mJ/m^) .
Exception: One-story buildings complying with Section
2603.4,1.4.
2603.5.4 Flame spread and smoke-developed indexes.
Foam plastic insulation, exterior coatings and facings shall
be tested separately in the thickness intended for use, but not
to exceed 4 inches (102 mm), and shall each have a flame
spread index of 25 or less and a smoke-developed index of
450 or less as determined in accordance with ASTM E 84 or
UL 723.
Exception: Prefabricated or factory-manufactured pan-
els having minimum 0.020-inch (0.51 mm) aluminum
facings and a total thickness of V4 inch (6.4 mm) or less
are permitted to be tested as an assembly where the foam
plastic core is not exposed in the course of construction.
2603.5.5 Test standard. The wall assembly shall be tested
in accordance with and comply with the acceptance criteria
of NFPA 285.
Exception: One-story buildings complying with Section
2603.4,1.4.
2603.5.6 Label required. The edge or face of each piece of
foam plastic insulation shall bear the label of an approved
agency. The label shall contain the manufacturer's or dis-
tributor's identification, model number, serial number or
definitive information describing the product or materials'
performance characteristics and approved agency's identi-
fication.
2603.5.7 Ignition. Exterior walls shall not exhibit sustained
flaming where tested in accordance with NFPA 268. Where
a material is intended to be installed in more than one thick-
ness, tests of the minimum and maximum thickness
intended for use shall be performed.
Exception: Assemblies protected on the outside with
one of the following:
1 . A thermal barrier complying with Section 2603.4.
2. A minimum 1 inch (25 nrni) thickness of concrete
or masonry.
3. Glass-fiber-reinforced concrete panels of a mini-
mum thickness of Vg inch (9.5 mm).
4. Metal-faced panels having minimum 0.019-
inch-thick (0.48 mm) aluminum or 0.016-inch-
thick (0.41 mm) corrosion-resistant steel outer fac-
ings.
5. A minimum Vg inch (22.2 mm) thickness of stucco
complying with Section 2510.
2603.6 Roofing. Foam plastic insulation meeting the require-
ments of Sections 2603.2, 2603.3 and 2603,4 shall be permit-
ted as part of a roof-covering assembly, provided the assembly
2010 CALIFORNIA BUILDING CODE
433
PLASTIC
with the foam plastic insulation is a Class A, B or C roofing
assembly where tested in accordance with ASTM E 108 or UL
790.
2603.7 Plenums. Foam plastic insulation shall not be used as
interior wall or ceiling finish in plenums except as permitted in
Section 2604 or when protected by a thermal barrier in accor-
dance with Section 2603.4.
2603.8 Protection against termites. In areas where the proba-
bility of termite infestation is very heavy in accordance with
Figure 2603.8, extruded and expanded polystyrene,
polyisocyanurate and other foam plastics shall not be installed
on the exterior face or under interior or exterior foundation
walls or slab foundations located below grade. The clearance
between foam plastics installed above grade and exposed earth
shall be at least 6 inches (152 mm).
Exceptions:
1. Buildings where the structural members of walls,
floors, ceilings and roofs are entirely of non-
combustible materials or preservative-treated wood.
2. An approved method of protecting the foam plastic
and structure from subterranean termite damage is
provided.
3. On the interior side of basement walls.
2603.9 Special approval. Foam plastic shall not be required to
comply with the requirements of Sections 2603.4 through
2603.7 where specifically approved based on large-scale tests
such as, but not limited to, NFPA 286 (with the acceptance cri-
teria of Section 803.2), FM 4880, UL 1040 or UL 1715. Such
testing shall be related to the actual end-use configuration and
be performed on the finished manufactured foam plastic
assembly in the maximum thickness intended for use. Foam
plastics that are used as interior finish on the basis of special
tests shall also conform to the flame spread requirements of
Chapter 8. Assemblies tested shall include seams, joints and
other typical details used in the installation of the assembly and
shall be tested in the manner intended for use.
SECTION 2604
INTERIOR FINISH AND TRIM
2604.1 General. Plastic materials installed as interior finish or
trim shall comply with Chapter 8. Foam plastics shall only be
installed as interior finish where approved in accordance with
the special provisions of Section 2603.9. Foam plastics that are
used as interior finish shall also meet the flame-spread index
requirements for interior finish in accordance with Chapter 8.
Foam plastics installed as interior trim shall comply with Sec-
tion 2604.2.
VERY HEAVY
bSilM MODERATE TO HEAVY
SLIGHT TO MODERATE
NONE TO SLIGHT
FIGURE 2603.8
TERMITE INFESTATION PROBABILITY MAP
434
2010 CALIFORNIA BUILDING CODE
PLASTIC
[F] 2604.2 Interior trim. Foam plastic used as interior trim
shall comply with Sections 2604.2.1 through 2604.2.4.
[F] 2604.2.1 Density. The minimum density of the interior
trim shall be 20 pcf (320 kg/m^).
[F] 2604.2.2 Thickness. The maximum thickness of the
interior trim shall be V2 inch (12.7 nmi) and the maximum
width shall be 8 inches (204 mm).
[F] 2604.2.3 Area limitation. The interior trim shall not
constitute more than 10 percent of the specific wall or ceil-
ing areas to which it is attached.
[F] 2604.2.4 Flame spread. The flame spread index shall
not exceed 75 where tested in accordance with ASTM E 84
or UL 723 . The smoke-developed index shall not be limited.
Exception: When the interior trim material has been
tested as an interior finish in accordance with NFPA 286
and complies with the acceptance criteria in Section
803.1.2.1, it shall not be required to be tested for flame
spread index in accordance with ASTM E 84 or UL 723.
SECTION 2605
PLASTIC VENEER
2605.1 Interior use. Where used within a building, plastic
veneer shall comply with the interior finish requirements of
Chapter 8.
2605.2 Exterior use. Exterior plastic veneer, other than plastic
siding, shall be permitted to be installed on the exterior walls of
buildings of any type of construction in accordance with all of
the following requirements:
1. Plastic veneer shall comply with Section 2606.4.
2. Plastic veneer shall not be attached to any exterior wall to
a height greater than 50 feet (15 240 mm) above grade.
3. Sections of plastic veneer shall not exceed 300 square
feet (27.9 m^) in area and shall be separated by a mini-
mum of 4 feet (1219 nun) vertically.
Exception: The area and separation requirements and
the smoke-density limitation are not applicable to
plastic veneer applied to buildings constructed of
Type VB construction, provided the walls are not
required to have a fire-resistance rating.
2605.3 Plastic siding. Plastic siding shall comply with the
requirements of Sections 1404 and 1405.
SECTION 2606
LIGHT-TRANSMITTING PLASTICS
2606.1 General. The provisions of this section and Sections
2607 through 2611 shall govern the quality and methods of
application of light-transmitting plastics for use as light-trans-
mitting materials in buildings and structures. Foam plastics
shall comply with Section 2603. Light- transmitting plastic
materials that meet the other code requirements for walls and
roofs shall be permitted to be used in accordance with the other
applicable chapters of the code.
2606.2 Approval for use. Sufficient technical data shall be
submitted to substantiate the proposed use of any light-trans-
mitting material, as approved by the building official and sub-
ject to the requirements of this section.
2606.3 Identification. Each unit or package of light-transmit-
ting plastic shall be identified with a mark or decal satisfactory
to the building official, which includes identification as to the
material classification.
2606.4 Specifications. Light-transmitting plastics, including
thermoplastic, thermosetting or reinforced thermosetting plas-
tic material, shall have a self-ignition temperature of 650°F
(343°C) or greater where tested in accordance with ASTM D
1929; a smoke-developed index not greater than 450 where
tested in the manner intended for use in accordance with
ASTM E 84 or UL 723, or a maximum average smoke density
rating not greater than 75 where tested in the thickness intended
for use in accordance with ASTM D 2843 and shall conform to
one of the following combustibility classifications:
Class CCl : Plastic materials that have a burning extent of 1
inch (25 mm) or less where tested at a nominal thickness of
0.060 inch (1.5 mm), or in the thickness intended for use, in
accordance with ASTM D 635.
Class CC2: Plastic materials that have a burning rate of 2 V2
inches per minute ( 1 .06 mm/s) or less where tested at a nom-
inal thickness of 0.060 inch (1.5 mm), or in the thickness
intended for use, in accordance with ASTM D 635.
2606.5 Structural requirements. Light-transmitting plastic
materials in their assembly shall be of adequate strength and
durability to withstand the loads indicated in Chapter 16. Tech-
nical data shall be submitted to establish stresses, maximum
unsupported spans and such other information for the various
thicknesses and forms used as deemed necessary by the build-
Ifig official.
2606.6 Fastening. Fastening shall be adequate to withstand the
loads in Chapter 16. Proper allowance shall be made for expan-
sion and contraction of light-transmitting plastic materials in
accordance with accepted data on the coefficient of expansion
of the material and other material in conjunction with which it
is employed.
2606.7 Light-diffusing systems. Unless the building is
equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1, light-diffusing systems
shall not be installed in the following occupancies and loca-
tions:
1. Group A with an occupant load of 1,000 or more.
2. Theaters with a stage and proscenium opening and an
occupant load of 700 or more.
3. Group 1-2.
4. Group 1-3.
5. Vertical exit enclosures and exit passageways.
2606.7.1 Support. Light-transmitting plastic diffusers shall
be supported directly or indirectly from ceiling or roof con-
struction by use of noncombustible hangers. Hangers shall
be at least No. 12 steel-wire gage (0.106 inch) galvanized
wire or equivalent.
2010 CALIFORNIA BUILDING CODE
435
PLASTIC
2606.7.2 Installation. Light-transmitting plastic diffusers
shall comply with Chapter 8 unless the light-transmitting
plastic diffusers will fall from the mountings before ignit-
ing, at an ambient temperature of at least 200°F (111°C)
below the ignition temperature of the panels. The panels
shall remain in place at an ambient room temperature of
175°F (79°C) for a period of not less than 15 minutes.
2606.7.3 Size limitations. Individual panels or units shall
not exceed 10 feet (3048 mm) in length nor 30 square feet
(2.79 m^) in area.
2606.7.4 Fire suppression system. In buildings that are
equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1, plastic light-diffusing
systems shall be protected both above and below unless the
sprinkler system has been specifically approved for installa-
tion only above the light-diffusing system. Areas of
light-diffusing systems that are protected in accordance
with this section shall not be limited.
2606.7.5 Electrical luminaires. Light-transmitting plastic
panels and light-diffuser panels that are installed in
approved electrical luminaires shall comply with the
requirements of Chapter 8 unless the light-transmitting
plastic panels conform to the requirements of Section
2606.7.2. The area of approved light-transmitting plastic
materials that are used in required exits or corridors shall
not exceed 30 percent of the aggregate area of the ceiling in
which such panels are installed, unless the building is
equipped throughout with an automatic sprinkler system in
accordance with Section 903 .3.1.1.
2606.8 Partitions. Light-transmitting plastics used in or as
partitions shall comply with the requirements of Chapters 6
and 8.
2606.9 Bathroom accessories. Light-transmitting plastics
shall be permitted as glazing in shower stalls, shower doors,
bathtub enclosures and similar accessory units. Safety glazing
shall be provided in accordance with Chapter 24.
2606.10 Awnings, patio covers and similar structures. Awn-
ings constructed of light-transmitting plastics shall be con-
structed in accordance with the provisions specified in Section
3105 and Chapter 32 for projections. Patio covers constructed
of light-transmitting plastics shall comply with Section 2606.
Light-transmitting plastics used in canopies at motor fuel-dis-
pensing facilities shall comply with Section 2606, except as
modified by Section 406.5,3.
2606.11 Greenhouses. Light-transmitting plastics shall be
permitted in lieu of plain glass in greenhouses.
2606.12 Solar collectors. Light-transmitting plastic covers on
solar collectors having noncombustible sides and bottoms shall
be permitted on buildings not over three stories above grade
plane or 9,000 square feet (836.1 m^) in total floor area, pro-
vided the light-transmitting plastic cover does not exceed 33.33
percent of the roof area for CCl materials or 25 percent of the
roof area for CC2 materials.
Exception: Light-transmitting plastic covers having a
thickness of 0.010 inch (0.3 mm) or less or shall be permit-
ted to be of any plastic material provided the area of the solar
collectors does not exceed 33.33 percent of the roof area.
SECTION 2607
LIGHT-TRANSMITTING PLASTIC WALL PANELS
2607.1 General. Light-transmitting plastics shall not be
used as wall panels in exterior walls in occupancies in
Groups A-i, A-2, H, 1-2 and 1-3. In other groups, light-trans-
mitting plastics shall be permitted to be used as wall panels
in exterior walls, provided that the walls are not required to
have a fire-resistance rating and the installation conforms to
the requirements of this section. Such panels shall be erected
and anchored on a foundation, waterproofed or otherwise
protected from moisture absorption and sealed with a coat of
mastic or other approved waterproof coating. Light-trans-
mitting plastic wall panels shall also comply with Section
2606.
2607.2 Installation. Exterior wa// panels installed as provided
for herein shall not alter the type of construction classification
of the building.
2607.3 Height limitation. Light-transmitting plastics shall not
be installed more than 75 feet (22 860 mm) above grade plane,
except as allowed by Section 2607.5.
2607 A Area limitation and separation. The maximum area
of a single wall panel and minimum vertical and horizontal sep-
aration requirements for exterior light-transmitting plastic wall
panels shall be as provided for in Table 2607.4. The maximum
percentage of wall area of any story in light- transmitting plastic
wall panels shall not exceed that indicated in Table 2607.4 or
the percentage of unprotected openings permitted by Section
705.8, whichever is smaller.
Exceptions:
1. In structures provided with approved flame barri-
ers extending 30 inches (760 mm) beyond the exte-
rior wall in the plane of the floor, a vertical
separation is not required at the floor except that
provided by the vertical thickness of the flame bar-
rier projection.
2. Veneers of approved weather-resistant light-trans-
mitting plastics used as exterior siding in buildings of
Type V construction in compliance with Section
1406.
3. The area of light-transmitting plastic wall panels in
exterior walls of greenhouses shall be exempt from
the area limitations of Table 2607,4 but shall be lim-
ited as required for unprotected openings in accor-
dance with Section 704.8.
2607.5 Automatic sprinkler system. Where the building is
equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1, the maximum percentage
area of exterior wall in any story in light-transmitting plastic
wall panels and the maximum square footage of a single area
given in Table 2607.4 shall be increased 100 percent, but the
area of light-transmitting plastic wall panels shall not exceed
50 percent of the wall area in any story, or the area permitted
by Section 704.8 for unprotected openings, whichever is
smaller. These installations shall be exempt from height limi-
tations.
436
2010 CALIFORNIA BUILDING CODE
PLASTIC
TABLE 2607.4
AREA LIMITATION AND SEPARATION REQUIREMENTS FOR
LIGHT-TRANSMITTING PLASTIC WALL PANELS^
FIRE SEPARATION DISTANCE
(feet)
CLASS OF
PLASTIC
MAXIMUM PERCENTAGE
AREA OF EXTERIOR WALL IN
PLASTIC WALL PANELS
MAXIMUM SINGLE AREA
OF PLASTIC WALL PANELS
(square feet)
MINIMUM SEPARATION OF
PLASTIC WALL PANELS (feet)
Vertical
Horizontal
Less than 6
—
Not Permitted
Not Permitted
—
—
6 or more but less than 1 1
CCl
10
50
8
4
CC2
Not Permitted
Not Permitted
—
—
1 1 or more but less than or equal to 30
CCl
25
90
6
4
CC2
15
70
8
4
Over 30
CCl
50
Not Limited
3^
CC2
50
100
6''
3
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 ml
a. For combinations of plastic glazing and plastic wall panel areas permitted, see Section 2607.6.
b. For reductions in vertical separation allowed, see Section 2607.4.
2607.6 Combinations of glazing and wall panels. Combina-
tions of light-transmitting plastic glazing and light-transmit-
ting plastic wall panels shall be subject to the area, height and
percentage limitations and the separation requirements appli-
cable to the class of light-transmitting plastic as prescribed for
light- transmitting plastic wall panel installations.
SECTION 2608
LIGHT-TRANSMITTING PLASTIC GLAZING
2608.1 Buildings of Type VB construction. Openings in the
exterior walls of buildings of Type VB construction, where not
required to be protected by Section 704, shall be permitted to be
glazed or equipped with light-transmitting plastic. Light-trans-
mitting plastic glazing shall also comply with Section 2606.
2608.2 Buildings of other types of construction. Openings in
the exterior walls of buildings of types of construction other
than Type VB, where not required to be protected by Section
704, shall be permitted to be glazed or equipped with
light-transmitting plastic in accordance with Section 2606 and
all of the following:
1. The aggregate area of light-transmitting plastic glazing
shall not exceed 25 percent of the area of any wall face of
the story in which it is installed. The area of a single pane
of glazing installed above the first story above grade
plane shall not exceed 16 square feet (1.5 m^) and the
vertical dimension of a single pane shall not exceed 4 feet
(1219 mm).
Exception: Where an automatic sprinkler system is
provided throughout in accordance with Section
903.3.1.1, the area of allowable glazing shall be
increased to a maximum of 50 percent of the wall face of
the story in which it is installed with no limit on the max-
imum dimension or area of a single pane of glazing.
2. Approved flame barriers extending 30 inches (762 mm)
beyond the exterior wall in the plane of the floor, or verti-
cal panels not less than 4 feet (1219 mm) in height, shall be
installed between glazed units located in adjacent stories.
Exception: Buildings equipped throughout with an
automatic sprinkler system in accordance with Sec-
tion 903.3.1.1.
3. Light-transmitting plastics shall not be installed more
than 75 feet (22 860 mm) above grade level.
Exception: Buildings equipped throughout with an
automatic sprinkler system in accordance with Sec-
tion 903.3.1.1.
SECTION 2609
LIGHT-TRANSMITTING PLASTIC ROOF PANELS
2609.1 General. Light-transmitting plastic roof panels shall
comply with this section and Section 2606. Light-transmitting
plastic roof panels shall not be installed in Groups H, 1-2 and
1-3. In all other groups, light-transmitting plastic roof panels
shall comply with any one of the following conditions:
1 . The building is equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.1.
2. The roof construction is not required to have a fire-resis-
tance rating by Table 601.
3 . The roof panels meet the requirements for roof coverings
in accordance with Chapter 15.
2609.2 Separation. Individual roof panels shall be separated
from each other by a distance of not less than 4 feet (1219 mm)
measured in a horizontal plane.
Exceptions:
1 . The separation between roof panels is not required in a
building equipped throughout with an automatic sprin-
kler system in accordance with Section 903.3.1.1.
2. The separation between roof panels is not required in
low-hazard occupancy buildings complying with the
conditions of Section 2609.4, Exception 2 or 3.
2010 CALIFORNIA BUILDING CODE
437
PLASTIC
2609.3 Location. Where exterior wall openings are required to
be protected by Section 705.8, a roof panel shall not be
installed within 6 feet (1829 nun) of such exterior wall
2609.4 Area limitations. Roof panels shall be limited in area
and the aggregate area of panels shall be limited by a percent-
age of the floor area of the room or space sheltered in accor-
dance with Table 2609.4.
Exceptions:
1. The area Hmitations of Table 2609.4 shall be permit-
ted to be increased by 100 percent in buildings
equipped throughout with an automatic sprinkler sys-
tem in accordance with Section 903.3.1.1.
2. Low-hazard occupancy buildings, such as swimming
pool shelters, shall be exempt from the area hmitations
of Table 2609,4, provided that the buildings do not
exceed 5,000 square feet (465 m^) in area and have a
minimum fire separation distance of 10 feet (3048
mm).
3. Greenhouses that are occupied for growing plants on
a production or research basis, without public access,
shall be exempt from the area limitations of Table
2609.4 provided they have a minimum fire separation
distance of 4 feet (1220 mm).
4. Roof coverings over terraces and patios in occupan-
cies in Group R-3 shall be exempt from the area limi-
tations of Table 2609.4 and shall be permitted with
light- transmitting plastics.
TABLE 2609.4
AREA LIMITATIONS FOR LIGHT-TRANSMITTING
PLASTIC ROOF PANELS
CLASS
OF
PLASTIC
MAXIMUM AREA OF
INDIVIDUAL ROOF PANELS
(square feet)
MAXIMUM AGGREGATE
AREA OF ROOF PANELS
(percent of floor area)
CCl
300
30
CC2
100
25
For SI: 1 square foot = 0.0929 m^
SECTION 2610
LIGHT-TRANSMITTING PLASTIC
SKYLIGHT GLAZING
2610.1 Light-transmitting plastic glazing of skylight
assemblies. Skylight assemblies glazed with light- transmitting
plastic shall conform to the provisions of this section and Sec-
tion 2606. Unit skylights glazed with light-transmitting plastic
shall also comply with Section 2405.5.
Exception: Skylights in which the hght-transmitting plastic
conforms to the required roof-covering class in accordance
with Section 1505.
2610.2 Mounting. The light-transmitting plastic shall be
mounted above the plane of the roof on a curb constructed in
accordance with the requirements for the type of construction
classilBcation, but at least 4 inches ( 1 02 mm) above the plane of the
roof. Edges of hght-transmitting plastic skyhghts or domes shall
be protected by metal or other approved noncombustible material,
or the Hght-transmittmg plastic dome or skyhght shall be shown to
be able to resist ignition where exposed at tfie edge to a flame from
a Class B brand as described in ASTM E 108 or UL 790.
Exceptions:
1 . Curbs shall not be required for skylights used on roofs
having a minimum slope of three units vertical in 12
units horizontal (25-percent slope) in occupancies in
Group R-3 and on buildings with a nonclassified roof
covering.
2. The metal or noncombustible edge material is not
required where nonclassified roof coverings are per-
mitted.
2610.3 Slope. Rat or corrugated light-transmitting plastic sky-
lights shall slope at least four units vertical in 12 units horizon-
tal (4:12). Dome-shaped skylights shall rise above the
mounting flange a minimum distance equal to 10 percent of the
maximum span of the dome but not less than 3 inches (76 mm).
Exception: Skyhghts that pass the Class B Burning Brand
Test specified in ASTM E 108 or UL 790.
2610.4 Maximum area of skylights. Each skylight shall have
a maximum area within the curb of 100 square feet (9.3 m^).
Exception: The area limitation shall not apply where the
building is equipped throughout with an automatic sprin-
kler system in accordance with Section 903.3.1.1 or the
building is equipped with smoke and heat vents in accor-
dance with Section 910.
2610.5 Aggregate area of skylights. The aggregate area of
skylights shall not exceed 33V3 percent of the floor area of the
room or space sheltered by the roof in which such skylights are
installed where Class CCl materials are utihzed, and 25 per-
cent where Class CC2 materials are utilized.
Exception: The aggregate area limitations of light-trans-
mitting plastic skylights shall be increased 100 percent
beyond the hmitations set forth in this section where the
building is equipped throughout with an automatic sprin-
kler system in accordance with Section 903.3.1.1 or the
building is equipped with smoke and heat vents in accor-
dance with Section 910.
2610.6 Separation. Skylights shall be separated from each
other by a distance of not less than 4 feet (1219 mm) measured
in a horizontal plane.
Exceptions:
1. Buildings equipped throughout with an automatic
sprinkler system in accordance with Section
903.3.1.1.
2. In Group R-3, multiple skylights located above the
same room or space with a combined area not exceed-
ing the limits set forth in Section 2610.4.
2610.7 Location. Where exterior wall openings are required to
be protected in accordance with Section 705, a skylight shall
not be installed within 6 feet ( 1 829 nam) of such exterior wall.
438
2010 CALIFORNIA BUILDING CODE
PLASTIC
2610.8 Combinations of roof panels and skylights. Combi-
nations of light-transmitting plastic roof panels and skylights
shall be subject to the area and percentage limitations and sepa-
ration requirements applicable to roof panel installations.
SECTION 2611
LIGHT-TRANSMITTING PLASTIC INTERIOR SIGNS
2611.1 General. Light-transmitting plastic interior wall signs
shall be limited as specified in Sections 2611 .2 through 26 11 .4.
Light-transmitting plastic interior wall signs in covered mall
buildings shall comply with Section 402.16. Light-transmit-
ting plastic interior signs shall also comply with Section 2606.
2611.2 Aggregate area. The sign shall not exceed 20 percent
of the wall area.
2611.3 Maximum area. The sign shall not exceed 24 square
feet (2.23 m^).
2611.4 Encasement. Edges and backs of the sign shall be fully
encased in metal.
SECTION 2612
FIBER REINFORCED POLYMER AND
FIBERGLASS REINFORCED POLYMER
2612.1 General. The provisions of this section shall govern the
requirements and uses of fiber reinforced polymer or fiberglass
reinforced polymer in and on buildings and structures.
2612.2 Labeling and identification. Packages and containers
of fiber reinforced polymer or fiberglass reinforced polymer
and their components delivered to the job site shall bear the
label of an approved agency showing the manufacturer's name,
product listing, product identification and information suffi-
cient to determine that the end use will comply with the code
requirements.
2612.3 Interior finish. Fiber reinforced polymer or fiberglass
reinforced polymer used as interior finish shall comply with
Chapter 8.
2612 A Decorative materials and trim. Fiber reinforced poly-
mer or fiberglass reinforced polymer used as decorative mate-
rials or trim shall comply with Section 806.
2612.5 Light-transmitting materials. Fiber reinforced poly-
mer or fiberglass reinforced polymer used as light-transmitting
materials shall comply with Sections 2606 through 2611 as
required for the specific application.
2612.6 Exterior use. Fiber reinforced polymer or fiberglass
reinforced polymer shall be permitted to be installed on the
exterior walls of buildings of any type of construction when
such polymers meet the requirements of Section 2603.5 and is
fireblocked in accordance with Section 717. The fiber rein-
forced polymer or the fiberglass reinforced polymer shall be
designed for uniform live loads as required in Table 1607.1 as
well as for snow loads, wind loads and earthquake loads as
specified in Sections 1608, 1609 and 1613, respectively.
Exceptions:
1. When all of the following conditions are met:
1.1. When the area of the fiber reinforced polymer
or the fiberglass reinforced polymer does not
exceed 20 percent of the respective wall area,
the fiber reinforced polymer or the fiberglass
reinforced polymer shall have a flame spread
index of 25 or less or when the area of the fiber
reinforced polymer or the fiberglass reinforced
polymer does not exceed 10 percent of the re-
spective wall area, the fiber reinforced polymer
or the fiberglass reinforced polymer shall have
a flame spread index of 75 or less. The flame
spread index requirement shall not be required
for coatings or paints having a thickness of less
than 0.036 inch (0.9 mm) that are applied di-
rectly to the surface of the fiber reinforced
polymer or the fiberglass reinforced polymer.
1.2. Fireblocking complying with Section 717.2.6
shall be installed.
1.3. The fiber reinforced polymer or the fiberglass
reinforced polymer shall be installed directly
to a noncombustible substrate or be separated
from the exterior wall by one of the following
materials: corrosion-resistant steel having a
minimum base metal thickness of 0.016 inch
(0.41 mm) at any point, aluminum having a
minimum thickness of 0.019 inch (0.5 mm) or
other approved noncombustible material.
1 .4. The fiber reinforced polymer or the fiberglass
reinforced polymer shall be designed for uni-
form Hve loads as required in Table 1607.1 as
well as for snow loads, wind loads and earth-
quake loads as specified in Sections 1608,
1609 and 1613, respectively.
2. When installed on buildings that are 40 feet (12 190
mm) or less above grade, the fiber reinforced polymer
or the fiberglass reinforced polymer shall meet the
requirements of Section 1406.2 and shall comply
with all of the following conditions:
2.1. Where the fire separation distance is 5 feet
(1524 mm) or less, the area of the fiber rein-
forced polymer or the fiberglass reinforced
polymer shall not exceed 10 percent of the
wall area. Where the fire separation distance
is greater than 5 feet (1524 mm), there shall be
no limit on the area of the exterior wall cover-
age using fiber reinforced polymer or the fi-
berglass reinforced polymer.
2.2. The fiber reinforced polymer or the fiberglass
reinforced polymer shall have a flame spread
index of 200 or less. The flame spread index
requirement shall not be required for coatings
or paints having a thickness of less than 0.036
inch (0.9 mm) that are applied directly to the
surface of the fiber reinforced polymer or the
fiberglass reinforced polymer.
2.3. Fireblocking complying with Section 717.2.6
shall be installed.
2010 CALIFORNIA BUILDING CODE
439
PLASTIC
2.4. The fiber reinforced polymer or the fiberglass
reinforced polymer shall be designed for uni-
form live loads as required in Table 1607.1 as
well as for snow loads, wind loads and earth-
quake loads as specified in Sections 1608,
1609 and 1613, respectively.
SECTION 2613
REFLECTIVE PLASTIC CORE INSULATION
2613.1 General. The provisions of this section shall govern the
requirements and uses of reflective plastic core insulation in
buildings and structures. Reflective plastic core insulation shall
comply with the requirements of Section 2613.2 and of one of
the following: Section 2613.3 or 2613.4.
2613.2 Identification. Packages and containers of reflective
plastic core insulation delivered to the job site shall show the
manufacturer's or supplier's name, product identification and
information sufficient to determine that the end use will com-
ply with the code requirements.
2613.3 Surface-burning characteristics. Reflective plastic
core insulation shall have a flame spread index of not more than
25 and a smoke-developed index of not more than 450 when
tested in accordance with ASTM E 84 or UL 723. The reflec-
tive plastic core insulation shall be tested at the maximum
thickness intended for use and shall be tested using one of the
mounting methods in Section 2613.3.1 or 2613.3.2.
2613.3.1 Mounting of test specimen. The test specimen shall
be mounted on 2-inch-high (5 1 mm) metal frames so as to cre-
ate an air space between the unexposed face of the reflective
plastic core insulation and the lid of the test apparatus.
2613.3.2 Specific testing. A set of specimen preparation
and mounting procedures shall be used which are specific to
the testing of reflective plastic core insulation.
2613.4 Room corner test lieat release. Reflective plastic core
insulation shall comply with the acceptance criteria of Section
803.1.2.1 when tested in accordance with NFPA 286 or UL
1 7 1 5 in the manner intended for use and at the maximum thick-
ness intended for use.
440
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 27 - ELECTRICAL
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire ciiapter as
amended (amended sections
listed below)
X
Adopt only those sections that
are listed below
Chapter/Section
2702.2.5
X
2702.2.6
X
2702.2.15
X
2702.2.21
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
441
442 201 CALIFORNIA BUILDING CODE
CHAPTER 27
ELECTRICAL
Refer to California Electrical Code, Title 24, Part 3
II
SECTION 2701
GENERAL
2701.1 Scope. This chapter governs the electrical components,
equipment and systems used in buildings and structures cov-
ered by this code. Electrical components, equipment and sys-
tems shall be designed and constructed in accordance with the
provisions of the California Electrical Code.
[F] SECTION 2702
EMERGENCY AND STANDBY POWER SYSTEMS
[F] 2702.1 Installation. Emergency and standby power sys-
tems required by this code or the California Fire Code shall be
installed in accordance with this code, NFPA 110 and 111.
[F] 2702.1.1 Stationary generators. Stationary emergency
and standby power generators required by this code shall be
listed in accordance with UL 2200.
[F] 2702.2 Where required. Emergency and standby power
systems shall be provided where required by Sections 2702.2. 1
through 2702.2.20.
[F] 2702.2.1 Group A occupancies. Emergency power
shall be provided for emergency voice/alarm communica-
tion systems in Group A occupancies in accordance with
Section 907.5.2.2.4.
[F] 2702.2.2 Smoke control systems. Standby power shall
be provided for smoke control systems in accordance with
Section 909.11.
[F] 2702,2.3 Exit signs. Emergency power shall be pro-
vided for exit signs in accordance with Section 101 1.5.3.
[F] 2702.2.4 Means of egress illumination. Emergency
power shall be provided for means of egress illumination in
accordance with Section 1006.3.
[F] 2702.2.5 Accessible means of egress elevators. Standby
power shall be provided for elevators that are part of an acces-
sible means of egress in accordance with Section 1007.4.
[F] 2702.2.6 Accessible means of egress platform lifts.
Standby power in accordance with this section or ASME A
18.1 shall be provided for platform lifts that are part of an
accessible means of egress in accordance with Section 1007.5.
[F] 2702.2.7 Horizontal sliding doors. Standby power
shall be provided for horizontal sliding doors in accordance
with Section 1008.1.4.3.
[F] 2702.2.8 Semiconductor fabrication facilities. Emer-
gency power shall be provided for semiconductor fabrica-
tion facilities in accordance with Section 415.8.10.
[F] 2702.2.9 Membrane structures. Standby power shall
be provided for auxiliary inflation systems in accordance
with Section 3102.8.2. Emergency power shall be provided
for exit signs in temporary tents and membrane structures in
accordance with the California Fire Code.
[F] 2702.2.10 Hazardous materials. Emergency or stand-
by power shall be provided in occupancies with hazardous
materials in accordance with Section 414.5.4.
[F] 2702.2.11 Highly toxic and toxic materials. Emer-
gency power shall be provided for occupancies with highly
toxic or toxic materials in accordance with the California
Fire Code.
[F] 2702.2.12 Organic peroxides. Standby power shall be
provided for occupancies with silane gas in accordance with
the California Fire Code.
[F] 2702.2.13 Pyrophoric materials. Emergency power
shall be provided for occupancies with silane gas in accor-
dance with the California Fire Code.
[F] 2702.2.14 Covered mall buildings. Standby power
shall be provided for voice/alarm communication systems
in covered mall buildings in accordance with Section
402.14.
[F] 2702.2.15 High-rise buildings and Group 1-2 occu-
pancies having occupied floors located more than 75 feet
above the lowest level of fire department vehicle access.
Emergency and standby power shall be provided in
high-rise buildings and Group 1-2 occupancies having
occupied floors located more than 75 feet above the lowest
level of fire department vehicle access in accordance with
Sections 403.4.7 and 403.4.8.
[F] 2702.2.16 Underground buildings. Emergency and
standby power shall be provided in underground buildings
in accordance with Sections 405.8 and 405.9.
[F] 2702.2.17 Group 1-3 occupancies. Emergency power
shall be provided for doors in Group 1-3 occupancies in
accordance with Section 408.4.2.
[F] 2702.2.18 Airport traffic control towers. Standby
power shall be provided in airport traffic control towers in
accordance with Section 412.3.5.
[F] 2702.2.19 Elevators. Standby power for elevators shall
be provided as set forth in Sections 3003.1, 3007.7 and
3008.15.
[F] 2702,2.20 Smokeproof enclosures. Standby power
shall be provided for smokeproof enclosures as required by
Section 909.20.6.2.
2702.2.21 Group L-Occupancy. Emergency power shall be
provided in Group L occupancies in accordance with this
chapter and Section 443.4.6.1.
[F] 2702.3 Maintenance. Emergency and standby power sys-
tems shall be maintained and tested in accordance with the Cal-
ifornia Fire Code.
2010 CALIFORNIA BUILDING CODE
443
444 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 28 - MECHANICAL SYSTEMS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
8L
SLC
1
2
1-AC
AC
88
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
X
Adopt only those sections that
are listed below
Chapter/Section
2802
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
445
446 201 CALIFORNIA BUILDING CODE
CHAPTER 28
MECHANICAL SYSTEMS
Refer to California Mechanical Code, Title 24, Part 4
SECTION 2801
GENERAL
2801.1 Scope. Mechanical appliances, equipment and systems
shall be constructed, installed and maintained in accordance
with the California Mechanical Code, Masonry chimneys,
fireplaces and barbecues shall comply with the California
Mechanical Code and Chapter 21 of this code.
2802 Spark Arrester. [SFM] All chimneys attached to any
appliance or fireplace that burns solid fuel shall be equipped
with an approved spark arrester. The spark arrestor shall meet
all of the following requirements:
1. The net free area of the spark arrester shall not be less
than four times the net free area of the outlet of the chim-
ney.
2. The spark arrester screen shall have heat and corrosion
resistance equivalent to 12- gage wire, 19- gage galva-
nized wire or 24-gage stainless steel.
3. Openings shall not permit the passage of spheres having
a diameter larger than ^/2 inch (12.7 mm) and shall not
block the passage of spheres having a diameter of less
than % inch (9.5 mm).
4. The spark arrestor shall be accessible for cleaning, and
the screen or chimney cap shall be removable to allow
for cleaning of the chimney flue.
2010 CALIFORNIA BUILDING CODE 447
448 201 CALIFORNIA BUILDING CODE
CHAPTER 29
PLUMBING SYSTEMS
(Not adopted by the State of California)
Refer to California Plumbing Code, Title 24, Part 5
II
SECTION 2901
GENERAL
2901.1 Scope. The provisions of the California Plumbing
Code shall govern the erection, installation, alteration, repairs,
relocation, replacement, addition to, use or maintenance of
plumbing equipment and systems. Plumbing systems and
equipment shall be constructed, installed and maintained in
accordance with the California Plumbing Code. Private sew-
age disposal systems shall conform to the California Plumbing
Code.
For minimum plumbing fixture requirements, see Table 4-1
of the California Plumbing Code.
[P] TABLE 2902.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES^
(See Sections 2902.2 and 2902.3)
No.
CLASSIFICATION
OCCUPANCY
DESCRIPTION
WATER CLOSETS
{URINALS SEE SECTION 419.2 OF
THE CALIFORNIA PLUMBING
CODE^
LAVATORIES
BATHTUBS/
SHOWERS
DRINKING ,
FOUNTAINS®'^
(SEE SECTION
410.1 OF THE
CALIFORNIA
PLUMBING CODE)
OTHER
MALE
FEMALE
MALE
FEMALE
1
Assembly
A-l^
Theaters and other
buildings for the
performing arts and
motion pictures
1 per 125
1 per 65
1 per 200
--
1 per 500
1
service
sink
A-l"
Nightclubs, bars,
taverns, dance halls and
buildings for similar
purposes
1 per 40
1 per 40
1 per 75
—
1 per 500
1
service
sink
Restaurants, banquet
halls and food courts
1 per 75
1 per 75
1 per 200
—
1 per 500
1
service
sink
A-B'^
Auditoriums without
permanent seating, art
galleries, exhibition
halls, museums, lecture
halls, libraries, arcades
and gymnasiums
1 per 125
1 per 65
1 per 200
—
1 per 500
1
service
sink
Passenger terminals and
transportation facilities
1 per 500
1 per 500
1 per 750
—
1 per 1,000
1
service
sink
Places of worship and
other religious services
1 per 150
1 per 75
1 per 200
—
1 per 1,000
1
service
sink
A-4
Coliseums, arenas,
skating rinks, pools and
tennis courts for indoor
sporting events and
activities
1 per 75 for the
first 1,500 and
1 per 120 for
the remainder
exceeding
1,500
1 per 40 for the
first 1,520 and
1 per 60 for the
remainder
exceeding
1,520
1 per 200
1 per 150
—
1 per 1,000
1
service
sink
A-5
Stadiums, amusement
parks, bleachers and
grandstands for outdoor
sporting events and
activities
1 per 75 for the
first 1,500 and
1 per 120 for
the remainder
exceeding
1,500
1 per 40 for the
first 1,520 and
1 per 60 for the
remainder
exceeding
1,520
1 per 200
1 per 150
—
1 per 1,000
1
service
sink
(continued)
2010 CALIFORNIA BUILDING CODE
449
PLUMBING SYSTEMS
[P] TABLE 2902.1— continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES^
No.
CLASSIFICATION
OCCUPANCY
DESCRIPTION
WATER CLOSETS
(URINALS SEE SECTION 419.2 OF
THE CALIFORNIA PLUMBING
CODE)
LAVATORIES
BATHTUBS
OR
SHOWERS
DRINKING ,
FOUNTAINS®'*
(SEE SECTION
410.1 OF THE
CAUFORNIA
PLUMBING CODE)
OTHER
MALE
FEMALE
MALE
FEMALE
2
Business
B
Buildings for the
transaction of
business, professional
services, other
services involving
merchandise, office
buildings, banks,
light industrial and
similar uses
1 per 25 for the first 50 and 1
per 50 for the remainder
exceeding 50
1 per 40 for the first
80 and 1 per 80 for
the remainder
exceeding 80
1 per 100
1 service
sink
3
Educational
E
Educational facilities
1 per 50
1 per 50
—
1 per 100
1 service
sink
4
Factory and
industrial
F-landF-2
Structures in which
occupants are
engaged in work
fabricating, assembly
or processing of
products or materials
1 per 100
1 per 100
See Section
411 of the
International
Plumbing
Code
1 per 400
1 service
sink
5
Institutional
I-l
Residential care
1 per 10
1 per 10
IperS
1 per 100
1 service
sink
1-2
Hospitals,
ambulatory nursing
home patients''
1 per per room*^
1 per per room'^
1 per 15
1 per 100
1 service
sink
Employees, other
than residential care''
1 per 25
1 per 35
—
1 per 100
—
Visitors, other than
residential care
1 per 75
1 per 100
—
1 per 500
—
1-3
Prisons''
1 per cell
1 per cell
1 per 15
1 per 100
1 service
sink
1-3
Reformatories,
detention centers and
correctional centers''
1 per 15
1 per 15
1 per 15
1 per 100
1 service
sink
Employees''
1 per 25
1 per 35
—
1 per 100
—
1-4
Aduh day care and
child care
1 per 15
1 per 15
1
1 per 100
1 service
sink
6
Mercantile
M
Retail stores, service
stations, shops,
salesrooms, markets
and shopping centers
1 per 500
1 per 750
—
1 per 1,000
1 service
sink
7
Residential
R-1
Hotels, motels,
boarding houses
(transient)
1 per sleeping unit
1 per sleeping unit
1 per sleeping
unit
—
1 service
sink
R-2
Dormitories,
fraternities, sororities
and boarding houses
(not transient)
1 per 10
1 per 10
IperS
1 per 100
1 service
sink
R-2
Apartment house
1 per dwelling unit
1 per dwelling unit
1 per
dwelling unit
—
1 kitchen
sink per
dwelling
unit; 1
automatic
clothes
washer
connection
per 20
dwelling
units
(continued)
450
2010 CALIFORNIA BUILDING CODE
PLUMBING SYSTEMS
[P] TABLE 2902.1— continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES"
No.
CLASSIFICATION
OCCUPANCY
DESCRIPTION
WATER CLOSETS
(URINALS SEE SECTION 419.2 OF
THE CALIFORNIA PLUMBING CODE)
LAVATORIES
BATHTUBS/
SHOWERS
DRINKING ,
FOUNTAINS®''
(SEE SECTION
410.1 OF THE
CALIFORNIA
PLUMBING CODE)
OTHER
MALE
FEMALE
MALE
FEMALE
7
Residential
R-3
Congregate living
facilities with 16 or
fewer persons
1 per 10
1 per 10
IperS
1 per 100
1 service
sink
R-4
Residential
care/assisted living
faciUties
1 per 10
1 per 10
IperS
1 per 100
1 service
sink
8
Storage
S-1
S-2
Structures for the
storage of goods,
warehouses,
storehouses and
freight depots, low
and moderate hazard
1 per 100
1 per 100
Seethe
California
Plumbing
Code
1 per 1,000
1 service
sink
The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated.
The number of occupants shall be determined by this code.
Toilet facilities for employees shall be separate from facilities for inmates or patients.
A single-occupant toilet room with one water closet and one lavatory serving not more than two adj acent patient sleeping units shall be permitted where such room
is provided with direct access from each patient sleeping unit and with provisions for privacy.
The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of fecilities required.
The minimum number of required drinking fountains shall comply with Chapter 1 IB and the California Plumbing Code.
Drinking fountains are not required for an occupant load of 15 or faver.
2010 CALIFORNIA BUILDING CODE
451
452 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 30 - ELEVATORS AND CONVEYING SYSTEMS
Adopting agency
BBC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
88
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
Adopt only those sections that
are listed below
X
X
X
X
Chapter/Section
3001.1
X
X
X
3001.1 w/Exception
X
3001.3
X
X
X
X
3001.5
X
3002.4a -3002.4.7a
X
3002.9 - 3002.9.5
X
3003.2.1 -3003.2.1.2
X
3004.1
X
3004.3.1
X
3006.5 - 3006.5.5
X
3009
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
453
454 201 CALIFORNIA BUILDING CODE
CHAPTER 30
ELEVATORS AND CONVEYING SYSTEMS
SECTION 3001
GENERAL
3001.1 Scope. This chapter governs the design, construction,
installation, alteration and repair of elevators and conveying
systems and their components.
Exception: [DSA-AC & HCD 1-AC] For accessibility
requirements for platform (wheelchair) lifts and elevators,
see California Code of Regulations y Title 8 and Title 24, Part
2, Sections 1124A and 1116B.
3001.2 Referenced standards. Except as otherwise provided
for in this code, the design, construction, installation, alter-
ation, repair and maintenance of elevators and conveying sys-
tems and their components shall conform to ASME A17.1/
CSA B44, ASME A90.1, ASME B20.1, ALI ALCTV, and
ASCE 24 for construction in flood hazard areas established in
Section 1612.3.
3001.3 Accessibility. Passenger elevators and platform
(wheelchair) lifts required to be accessible by Chapter 11 A or
IIB shall conform to Chapter llAfor applications listed in
Section 1.8,2.1,2 regulated by the Department of Housing and
Community Development or Chapter IIB for applications
listed in Section 1.9.1 regulated by the Division of the State
Architect-Access Compliance,
3001.4 Change in use. A change in use of an elevator from
freight to passenger, passenger to freight, or from one freight
class to another freight class shall comply with Section 8.7 of
ASMEA17.1/CSAB44.
3001.5 Elevators utilized to transport hazardous materials.
Elevators utilized to transport hazardous materials shall also
comply with California Fire Code Section 2703.10.4,
SECTION 3002
HOISTWAY ENCLOSURES
3002.1 Hoistveay enclosure protection. Elevator, dumbwaiter
and other hoistway enclosures shall be shaft enclosures com-
plying with Section 708.
3002.1.1 Opening protectives. Openings in hoistway
enclosures shall be protected as required in Chapter 7.
Exception: The elevator car doors and the associated
hoistway enclosure doors at the floor level designated for
recall in accordance with Section 3003.2 shall be permit-
ted to remain open during Phase I Emergency Recall
Operation.
3002.1.2 Hardware. Hardware on opening protectives
shall be of an approved type installed as tested, except that
approved interlocks, mechanical locks and electric con-
tacts, door and gate electric contacts and door-operating
mechanisms shall be exempt from the fire test requirements.
3002.2 Number of elevator cars in a hoistway. Where four or
more elevator cars serve all or the same portion of a building,
the elevators shall be located in at least two separate hoistways.
Not more than four elevator cars shall be located in any single
hoistway enclosure.
3002.3 Emergency signs. An approved pictohal sign of a stan-
dardized design shall be posted adjacent to each elevator call
station on all floors instructing occupants to use the exit stair-
ways and not to use the elevators in case of fire. The sign shall
read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR.
USE EXIT STAIRS.
Exceptions:
1. The emergency sign shall not be required for elevators
that are part of an accessible means of egress complying
with Section 1007.4.
2. The emergency sign shall not be required for elevators
that are used for occupant self-evacuation in accordance
with Section 3008.
3002.4 Elevator car to accommodate ambulance stretcher.
Where elevators are provided in buildings four or more stories
above, or four or more stories below, grade plane, at least one
elevator shall be provided for fire department emergency
access to all floors. The elevator car shall be of such a size and
arrangement to accommodate an ambulance stretcher 24
inches by 84 inches (610 mm by 2134 mm) with not less than
5-inch (127 mm) radius comers, in the horizontal, open posi-
tion and shall be identified by the international symbol for
emergency medical services (star of life). The symbol shall not
be less than 3 inches (76 mm) high and shall be placed inside on
both sides of the hoistway door frame.
The following California sections replace the corresponding
model code section for applications specified in Section 1.11
for the Office of the State Fire Marshal.
3002,4a General Stretcher Requirements. A// buildings and
structures with one or more passenger service elevators shall
be provided with not less than one medical emergency service
elevator to all landings meeting the provisions of Section
3002,4a.
Exceptions:
L Elevators in structures used only by maintenance and
operating personnel,
2. Elevators in jails and penal institutions.
3. Elevators in buildings or structures where each land-
ing is at ground level or is accessible at grade level or
by a ramp.
4. Elevator(s) in two-story buildings or structures
equipped with stairs of a configuration that will
accommodate the carrying of the gurney or stretcher
as permitted by the local jurisdictional authority.
II
II
2010 CALIFORNIA BUILDING CODE
456
ELEVATORS AND CONVEYING SYSTEMS
5, Elevators in buildings or structures less than four sto-
ries in height for which the local jurisdictional
authority has granted an exception in the form of a
written document,
3002,4,1a Gurney size. The medical emergency service ele-
vator shall accommodate the loading and transport of an
ambulance gurney or stretcher [maximum size 24 inches by
84 inches (610 mm by 2134 mm) with not less than 5 -inch
(127 mm) radius corners] in the horizontal position.
3002.4,2a Hoistway doors. The hoistway landing openings
shall be provided with power-operated doors,
3002,4,3a Elevator entrance openings and car size. The
elevator car shall be of such a size and arrangement to
accommodate a 24-inch by 84-inch (610 mm by 2134 mm)
ambulance gurney or stretcher with not less than 5-inch
(127 mm) radius corners, in the horizontal, open position,
shall be provided with a minimum clear distance between
walls or between walls and door excluding return panels not
less than 80 inches by 54 inches (2032 mm by 1372 mm),
and a minimum distance from wall to return panel not less
than 51 inches (1295 mm) with a 42-inch (1067 mm) side
slide door
Exception: The elevator car dimensions and/or the clear
entrance opening dimensions may be altered where it
can be demonstrated to the local jurisdictional author-
ity's satisfaction that the proposed configuration will
handle the designated gurney or stretcher with equiva-
lent ease. Documentation from the local authority shall
be provided to the Occupational Safety and Health Stan-
dards Board.
3002,4,4a Elevator recall. The elevator(s) designated the
medical emergency elevator shall be equipped with a key
switch to recall the elevator nonstop to the main floor. For
the purpose of this section, elevators in compliance with
Section 3003.2 shall be acceptable.
3002,4,5a Designation, Medical emergency elevators shall
be identified by the international symbol (Star of Life) for
emergency medical services.
3002,4,6a Symbol size. The symbol shall not be less than 3
inches (76 mm) in size.
3002,4,7a Symbol location. A symbol shall be permanently
attached to each side of the hoistway doorframe on the por-
tion of the frame at right angles to the hallway or landing
area. Each symbol shall be not less than 78 inches (1981
mm) and not more than 84 inches (2134 mm) above the floor
level at the threshold.
3002.5 Emergency doors. Where an elevator is installed in a
single blind hoistway or on the outside of a building, there shall
be installed in the blind portion of the hoistway or blank face of
the building, an emergency door in accordance with ASME
A17.1/CSAB44.
3002.6 Prohibited doors. Doors, other than hoistway doors
and the elevator car door, shall be prohibited at the point of
access to an elevator car unless such doors are readily openable
from the car side without a key, tool, special knowledge or
effort.
3002.7 Common enclosure withi stairway. Elevators shall not
be in a common shaft enclosure with a stairway.
Exception: Open parking garages.
3002.8 Glass in elevator enclosures. Glass in elevator enclo-
sures shall comply with Section 2409.1.
3002.9 Photoelectric tube bypass switch,
3002.9.1 Elevators equipped with photoelectric tube devices
which control the closing of automatic, power-operated car
or hoistway doors, or both, shall have a switch in the car
which, when actuated, will render the photoelectric tube
device ineffective.
3002.9.2 The switch shall be constant-pressure type, requir-
ing not less than 10 pounds (44. 5N) or more than 15 pounds
(66. 7 N) pressure to actuate.
3002.9.3 The switch shall be located not less than 6 feet
(1 829 mm) or more than 6 feet 6 inches (1981 mm) above the
car floor and shall be located in or adjacent to the operating
panel.
3002.9.4 The switch shall be clearly labeled TO BE USED
IN CASE OF HRE ONLY.
3002.9.5 Switches shall be kept in working order or be
removed when existing installations are arranged to comply
with Section 3002.9.5, Exception 1 or 2.
Exceptions:
1. Elevators installed and maintained in compliance
with Section 3003.
2. Where alternate means acceptable to the fire
authority having jurisdiction are provided that
will ensure the doors can close under adverse
smoke conditions.
[F] SECTION 3003
EMERGENCY OPERATIONS
[F] 3003.1 Standby power. In buildings and structures where
standby power is required or furnished to operate an elevator,
the operation shall be in accordance with Sections 3003.1.1
through 3003.1.4.
[F] 3003.1.1 Manual transfer. Standby power shall be
manually transferable to all elevators in each bank.
[F] 3003.1.2 One elevator. Where only one elevator is
installed, the elevator shall automatically transfer to standby
power within 60 seconds after failure of normal power.
[F] 3003.1.3 Two or more elevators. Where two or more
elevators are controlled by a common operating system, all
elevators shall automatically transfer to standby power
within 60 seconds after failure of normal power where the
standby power source is of sufficient capacity to operate all
elevators at the same time. Where the standby power source
is not of sufficient capacity to operate all elevators at the
same time, all elevators shall transfer to standby power in
sequence, return to the designated landing and disconnect
from the standby power source. After all elevators have
been returned to the designated level, at least one elevator
shall remain operable from the standby power source.
456
2010 CALIFORNIA BUILDING CODE
ELEVATORS AND CONVEYING SYSTEMS
[F] 3003.1.4 Venting. Where standby power is connected to
elevators, the machine room ventilation or air conditioning
shall be connected to the standby power source.
[F] 3003.2 Fire-fighters' emergency operation. Elevators
shall be provided with Phase I emergency recall operation and
Phase II emergency in-car operation in accordance with ASME
A17.1/CSAB44.
3003,2.1 Floor numbers. Elevator hoistways shall have a
floor number not less than 4 inches (102 mm) in height,
placed on the walls and/or doors of the hoistway at intervals
such that a person in a stalled elevator, upon opening the
car door, can determine the floor position.
3003.2.1.1 Fire signs. All automatic elevators shall have
not less than one sign at each landing printed on a con-
trasting background in letters not less than ^/2 inch (12. 7
mm) high to read: IN CASE OF FIRE USE STAIRWAY
FOR EXIT. DO NOT USE ELEVATOR.
3003.2.1.2 Call and car operation buttons. Automatic
passenger elevators shall have call and car operation
buttons within 60 inches (1524 mm) of the floor. Emer-
gency telephones shall also be within 60 inches (1524
mm) of the floor.
SECTION 3004
HOISTWAY VENTING
3004.1 Vents required. Hoistways of elevators and dumbwait-
ers penetrating more than three stories shall be provided with a
means for venting smoke and hot gases to the outer air in case
of fire.
Exceptions:
II 1. In occupancies of other than Groups R-1, R-2, R-2.1,
1-2 and similar occupancies with overnight sleeping
units, venting of hoistways is not required where the
building is equipped throughout with an approved
automatic sprinkler system installed in accordance
with Section 903.3.L1 or 903.3.1.2.
2. Sidewalk elevator hoistways are not required to be
vented.
3. Elevators contained within and serving open parking
garages only.
4. Elevators within individual residential dwelling units.
3004.2 Location of vents. Vents shall be located at the top the
hoistway and shall open either directly to the outer air or
through noncombustible ducts to the outer air. Noncombustible
ducts shall be permitted to pass through the elevator machine
room, provided that portions of the ducts located outside the
hoistway or machine room are enclosed by construction having
not less than the fire-resistance rating required for the
hoistway. Holes in the machine room floors for the passage of
ropes, cables or other moving elevator equipment shall be lim-
ited as not to provide greater than 2 inches (51 mm) of clear-
ance on all sides.
3004.3 Area of vents. Except as provided for in Section
3004.3. 1 , the area of the vents shall not be less than 3 Vj percent
of the area of the hoistway nor less than 3 square feet (0.28 m^)
for each elevator car, and not less than 3 V2 percent nor less than
0.5 square feet (0.047 m^) for each dumbwaiter car in the
hoistway, whichever is greater. Of the total required vent area,
not less than one-third shall be permanently open. Closed por-
tions of the required vent area shall consist of openings glazed
with annealed glass not greater than Vg inch (3.2 nmi) in thick-
ness.
Exception: The total required vent area shall not be
required to be permanently open where all the vent openings
automatically open upon detection of smoke in the elevator
lobbies or hoistway, upon power failure and upon activation
of a manual override control. The manual override control
shall be capable of opening and closing the vents and shall
be located in an approved location.
3004.3.1 Reduced vent area. Where mechanical ventila-
tion conforming to the California Mechanical Code is pro-
vided, a reduction in the required vent area is allowed
provided that all of the following conditions are met:
1 . The occupancy is not in Group R-1 , R-2, R-2. 1 or 1-2
or of a similar occupancy with overnight sleeping
units.
2. The vents required by Section 3004.2 do not have out-
side exposure.
3. The hoistway does not extend to the top of the build-
ing.
4. The hoistway and machine room exhaust fan is auto-
matically reactivated by thermostatic means.
5. Equivalent venting of the hoistway is accomplished.
3004.4 Plumbing and mechanical systems. Plumbing and
mechanical systems shall not be located in an elevator shaft.
Exception: Floor drains, sumps and sump pumps shall be
permitted at the base of the shaft provided they are indirectly
connected to the plumbing system.
SECTION 3005
CONVEYING SYSTEMS
3005.1 General. Escalators, moving walks, conveyors, per-
sonnel hoists and material hoists shall comply with the provi-
sions of this section.
3005.2 Escalators and moving walks. Escalators and moving
walks shall be constructed of approved noncombustible and
fire-retardant materials. This requirement shall not apply to
electrical equipment, wiring, wheels, handrails and the use of
Vjg-inch (0.9 mm) wood veneers on balustrades backed up with
noncombustible materials.
3005.2.1 Enclosure. Escalator floor openings shall be
enclosed with shaft enclosures complying with Section 708.
3005.2.2 Escalators. Where provided in below-grade trans-
portation stations, escalators shall have a clear width of 32
inches (815 mm) minimum.
Exception: The clear width is not required in existing
facilities undergoing alterations.
3005.3 Conveyors. Conveyors and conveying systems shall
comply with ASME B20.1.
2010 CALIFORNIA BUILDING CODE
457
ELEVATORS AND CONVEYING SYSTEMS
3005.3.1 Enclosure. Conveyors and related equipment con-
necting successive floors or levels shall be enclosed with
shaft enclosures complying with Section 708.
3005.3.2 Conveyor safeties. Power-operated conveyors,
belts and other material-moving devices shall be equipped
with automatic limit switches which will shut off the power
in an emergency and automatically stop all operation of the
device.
3005.4 Personnel and material hoists. Personnel and mate-
rial hoists shall be designed utilizing an approved method that
accounts for the conditions imposed during the intended opera-
tion of the hoist device. The design shall include, but is not lim-
ited to, anticipated loads, structural stability, impact, vibration,
stresses and seismic restraint. The design shall account for the
construction, installation, operation and inspection of the hoist
tower, car, machinery and control equipment, guide members
and hoisting mechanism. Additionally, the design of personnel
hoists shall include provisions for field testing and mainte-
nance which will demonstrate that the hoist device functions in
accordance with the design. Field tests shall be conducted upon
the completion of an installation or following a major alter-
ation of a personnel hoist.
SECTION 3006
MACHINE ROOMS
3006.1 Access. An approved means of access shall be provided
to elevator machine rooms and overhead machinery spaces.
3006.2 Venting. Elevator machine rooms that contain
solid-state equipment for elevator operation shall be provided
with an independent ventilation or air-conditioning system to
protect against the overheating of the electrical equipment. The
system shall be capable of maintaining temperatures within the
range estabhshed for the elevator equipment.
3006.3 Pressurization. The elevator machine room serving a
pressurized elevator hoistway shall be pressurized upon activa-
tion of a heat or smoke detector located in the elevator machine
room.
3006.4 Machine rooms and machinery spaces. Elevator
machine rooms and machinery spaces shall be enclosed with
fire barriers constructed in accordance with Section 707 or
horizontal assemblies constructed in accordance with Section
7 12, or both. The^ fire-resistance rating shall not be less than the
required rating of the hoistway enclosure served by the
machinery. Openings in ih^fire barriers shall be protected with
assemblies having a fire protection rating not less than that
required for the hoistway enclosure doors.
Exceptions:
1. Where machine rooms and machinery spaces do not
abut and have no openings to the hoistway enclosure
they serve ih^fire barriers constructed in accordance
with Section 707 or horizontal assemblies con-
structed in accordance with Section 7 1 2, or both, shall
be permitted to be reduced to a \-\io\ir fire-resistance
rating.
2. In buildings four stories or less above grade plane
when machine room and machinery spaces do not
abut and have no openings to the hoistway enclosure
they serve, the machine room and machinery spaces
are not required to be fire-resistance rated.
3006.5 Shunt trip. Where elevator hoistways or elevator
machine rooms containing elevator control equipment are pro-
tected with automatic sprinklers, a means installed in accor-
dance with NFPA 72, Section 6.16, Elevator Shutdown, shall
be provided to disconnect automatically the main line power
supply to the affected elevator prior to the application of water.
This means shall not be self -resetting. The activation of sprin-
klers outside the hoistway or machine room shall not discon-
nect the main line power supply.
3006.5.1 Elevator power shunt-trip shall not activate prior
to the completion of elevator Phase I emergency recall oper-
ation to the designated recall floor.
3006.5.2 Elevator power shunt-trip capability shall be dis-
abled during Phase II emergency in-car operation.
3006.5.3 Audible and visual annunciation shall be provided
at the fire alarm control unit indicating the disabling of ele-
vator power shunt-trip capability under Phase II operation.
3006.5.4 Audible and visual annunciation shall be provided
at the fire alarm control unit indicating that the automatic
sprinklers, smoke detectors or heat detectors in the elevator
hoistway or elevator machine room have activated.
3006.5.5 Visual annunciation shall be provided inside all
elevator cars indicating that the automatic sprinklers,
smoke detectors or heat detectors in the elevator hoistway
or elevator machine room have activated.
3006.6 Plumbing systems. Plumbing systems shall not be
located in elevator equipment rooms.
SECTION 3007
FIRE SERVICE ACCESS ELEVATOR
3007.1 General. Where required by Section 403.6.1, every
floor of the building shall be served by a fire service access ele-
vator. Except as modified in this section, the fire service access
elevator shall be installed in accordance with this chapter and
ASMEA17.1/CSAB44,
3007.2 Hoistway enclosures protection. The fire service
access elevator shall be located in a shaft enclosure complying
with Section 708.
3007.3 Hoistway lighting. When firefighters' emergency
operation is active, the entire height of the hoistway shall be
illuminated at not less than 1 foot-candle (11 lux) as measured
from the top of the car of each fire service access elevator.
3007.4 Fire service access elevator lobby. The fire service
access elevator shall open into a fire service access elevator
lobby in accordance with Sections 3007.4. 1 through 3007.4.4.
Exception: Where a fire service access elevator has two
entrances onto a floor, the second entrance shall be permit-
ted to open into an elevator lobby in accordance with Sec-
tion 708.14.1.
3007.4.1 Access. The fire service access elevator lobby
shall have direct access to an exit enclosure.
458
2010 CALIFORNIA BUILDING CODE
ELEVATORS AND CONVEYING SYSTEMS
3007.4.2 Lobby enclosure. The fire service access elevator
lobby shall be enclosed with a smoke barrier having a mini-
mum l-hom fire-resistance rating, except that lobby door-
ways shall comply with Section 3007.4.3.
Exception: Enclosed fire service access elevator lobbies
are not required at the street floor.
3007.4.3 Lobby doorways. Each fire service access eleva-
tor lobby shall be provided with a doorway that is protected
with a V4-hour^r^ door assembly complying with Section
715.4. The^r-^ door assembly shall also comply with the
smoke and draft control door assembly requirements of
Section 7 15.4.3. 1 with the UL 1784 test conducted without
the artificial bottom seat.
3007.4.4 Lobby size. Each enclosed fire service access ele-
vator lobby shall be a minimum of 150 square feet (14 m^) in
an area with a minimum dimension of 8 feet (2440 mm).
3007.5 Standpipe hose connection. A Class I standpipe hose
connection in accordance with Section 905 shall be provided in
the exit enclosure having direct access from the fire service
access elevator lobby.
3007.6 Elevator system monitoring. The fire service access
elevator shall be continuously monitored at the fire command
center by a standard emergency service interface system meet-
ing the requirements of NFPA 72.
3007.7 Electrical power The following features serving each
fire service access elevator shall be supplied by both normal
power and Type 60/Class 2/Level 1 standby power:
1. Elevator equipment.
2. Elevator hoistway lighting.
3. Elevator machine room ventilation and cooling equip-
ment.
4. Elevator controller cooling equipment.
3007.7.1 Protection of wiring or cables. Wires or cables
that provide normal and standby power, control signals,
communication with the car, lighting, heating, air condi-
tioning, ventilation and fire-detecting systems to fire service
access elevators shall be protected by construction having a
minimum l-honr fire -resistance rating or shall be circuit
integrity cable having a minimum l-hour fire-resistance
rating.
SECTION 3008
OCCUPANT EVACUATION ELEVATORS
3008.1 General. Where elevators are to be used for occupant
self-evacuation during fires, all passenger elevators for general
public use shall comply with this section. Where other eleva-
tors are used for occupant self-evacuation, they shall also com-
ply with this section.
3008.2 Fire safety and evacuation plan. The building shall
have an approved fire safety and evacuation plan in accordance
with the applicable requirements of Section 404 of the Interna-
tional Fire Code, The fire safety and evacuation plan shall
incorporate specific procedures for the occupants using evacu-
ation elevators.
3008.3 Operation. The occupant evacuation elevators shall be
used for occupant self-evacuation only in the normal elevator
operating mode prior to Phase I Emergency Recall Operation
in accordance with the requirements in ASME A17.1/CSA
B44 and the building's fire safety and evacuation plan.
3008.4 Additional exit stairway. Where an additional means
of egress is required in accordance with Section 403.5.2, an
additional exit stairway shall not be required to be installed in
buildings having elevators used for occupant self-evacuation in
accordance with this section.
3008.5 Emergency voice/alarm communication system.
The building shall be provided with an emergency voice/alarm
communication system. The emergency voice/alarm commu-
nication system shall be accessible to the fire department. The
system shall be provided in accordance with Section 907.5.2.2.
3008.5.1 Notification appliances. A minimum of one audi-
ble and one visible notification appliance shall be installed
within each occupant evacuation elevator lobby.
3008.6 Automatic sprinkler system. The building shall be
protected throughout by an approved, electrically-supervised
automatic sprinkler system in accordance with Section
903.3.1.1, except as otherwise permitted by Section
903.3.1.1.1 and as prohibited by Secfion 3008.6.1.
3008.6.1 Prohibited locations. Automatic sprinklers shall
not be installed in elevator machine rooms and elevator
machine spaces for occupant evacuation elevators.
3008.6.2 Sprinkler system monitoring. The sprinkler sys-
tem shall have a sprinkler control valve supervisory switch
and waterflow-initiating device provided for each floor that
is monitored by the building's fire alarm system.
3008.7 High-hazard content areas. No building areas shall
contain high-hazard contents exceeding the maximum allow-
able quantities per control area as addressed in Section 414.2.
3008.8 Shunt trip. Means for elevator shutdown in accordance
with Section 3006.5 shall not be installed on elevator systems
used for occupant evacuation elevators.
3008.9 Hoistway enclosure protection. The occupant evacua-
tion elevators shall be located in hoistway enclosure(s) com-
plying with Section 708.
3008.10 Water protection. The occupant evacuation elevator
hoistway shall be designed utilizing an approved method to
prevent water from the operation of the automatic sprinkler
system from infiltrating into the hoistway enclosure.
3008.11 Occupant evacuation elevator lobby. The occupant
evacuation elevators shall open into an elevator lobby in accor-
dance with Sections 3008.11.1 through 3008.11.4.
3008.11.1 Access. The occupant evacuation elevator lobby
shall have direct access to an exit enclosure.
3008.11.2 Lobby enclosure. The occupant evacuation ele-
vator lobby shall be enclosed with a smoke barrier having a
minimum l-hour fire-resistance rating, except that lobby
doorways shall comply with Section 3008.11.5.
Exception: Enclosed occupant evacuation elevator lob-
bies are not required at the level(s) of exit discharge.
2010 CALIFORNIA BUILDING CODE
459
ELEVATORS AND CONVEYING SYSTEMS
3008.11.3 Lobby doorways. Each occupant evacuation
elevator lobby shall be provided with a doorway that is pro-
tected with a V4-hour fire door assembly complying with
Section 715.4.
3008.11.3.1 Vision panel. A vision panel shall be
installed in QSich fire door assembly protecting the lobby
doorway. The vision panel shall consist of fire-protec-
tion-rated glazing and shall be located to furnish clear
vision of the occupant evacuation elevator lobby.
3008.11.3.2 Door closing. Each^r^ door assembly pro-
tecting the lobby doorway shall be automatic-closing
upon receipt of any fire alarm signal from the emergency
voice/alarm communication system serving the build-
ing.
3008.11.4 Lobby size. Each occupant evacuation elevator
lobby shall have minimum floor area as follows:
1. The occupant evacuation elevator lobby floor area
shall acconomodate, at 3 square feet (0.28 m^) per per-
son, a minimum of 25 percent of the occupant load of
the floor area served by the lobby.
2. The occupant evacuation elevator lobby floor area
also shall accommodate one wheelchair space of 30
inches by 48 inches (760 mm by 1220 mm) for each
50 persons, or portion thereof, of the occupant load of
the floor area served by the lobby.
Exception: The size of lobbies serving multiple
banks of elevators shall have the minimum floor
area approved on an individual basis and shall be
consistent with the building's fire safety and evac-
uation plan.
3008.11.5 Signage. An approved sign indicating elevators
are suitable for occupant self-evacuation shall be posted on
all floors adjacent to each elevator call station serving occu-
pant evacuation elevators.
3008.12 Lobby status indicator. Each occupant evacuation
elevator lobby shall be equipped with a status indicator
arranged to display all of the following information:
1. An illuminated green light and the message, "Elevators
available for occupant evacuation" when the elevators
are operating in normal service and the fire alarm system
is indicating an alarm in the building.
2. An illuminated red light and the message, "Elevators out
of service, use exit stairs" when the elevators are in Phase
I emergency recall operation in accordance with the
requirements in ASME A17.1/CSA B44.
3. No illuminated light or message when the elevators are
operating in normal service.
3008.13 Two-way communication system. A two-way com-
munication system shall be provided in each occupant evacua-
tion elevator lobby for the purpose of initiating communication
with the fire command center or an alternative location
approved by the fire department.
3008.13.1 Design and installation. The two-way com-
munication system shall include audible and visible sig-
nals and shall be designed and installed in accordance
with the requirements of ICC Al 17. 1 .
3008.13.2 Instructions. Instructions for the use of the
two-way communication system along with the location
of the station shall be permanently located adjacent to
each station. Signage shall comply with the ICC A 1 17.1
requirements for visual characters.
3008.14 Elevator system monitoring. The occupant evacua-
tion elevators shall be continuously monitored at the fire com-
mand center or a central control point approved by the fire
department and arranged to display all of the following infor-
mation:
1 . Floor location of each elevator car.
2. Direction of travel of each elevator car.
3. Status of each elevator car with respect to whether it is
occupied.
4. Status of normal power to the elevator equipment, eleva-
tor controller cooling equipment, and elevator machine
room ventilation and cooling equipment.
5. Status of standby or emergency power system that pro-
vides backup power to the elevator equipment, elevator
controller cooling equipment, and elevator machine
room ventilation and cooling equipment.
6. Activation of any fire alarm-initiating device in any ele-
vator lobby, elevator machine room or machine space, or
elevator hoistway.
3008.14.1 Elevator recall. The fire command center or an
alternative location approvedhy the fire department shall be
provided with the means to manually initiate a Phase I
Emergency Recall of the occupant evacuation elevators in
accordance with ASME A17.1/CSA B44.
3008.15 Electrical power. The following features serving
each occupant evacuation elevator shall be supplied by both
normal power and Type 60/Class 2/Level 1 standby power:
1. Elevator equipment.
2. Elevator machine room ventilation and cooling equip-
ment.
3. Elevator controller cooling equipment.
3008.15.1 Protection of wiring or cables. Wires or cables
that provide normal and standby power, control signals,
communication with the car, lighting, heating, air condi-
tioning, ventilation and fire-detecting systems to occupant
evacuation elevators shall be protected by construction hav-
ing a minimum 1-hom fire-resistance rating or shall be cir-
cuit integrity cable having a minimum 1-hour fire-
resistance rating.
SECTION 3009
SPECIAL REQUIREMENTS FOR
ELEVATORS IN HOSPITALS
3009,1 General. [OSHPD 1] In hospital buildings, all eleva-
tors shall comply with the provisions of this section.
460
2010 CALIFORNIA BUILDING CODE
ELEVATORS AND CONVEYING SYSTEMS
3009.1.1 Seismic switch. The seismic switch, as required by
ASMEA 17,1, shall be connected to the essential electrical
system.
3009.1.2 Annunciator, Either a visible or an audible
annunciator shall be connected to the essential electrical
system and be located in the elevator machine room. The
annunciator will indicate if the seismic switch is inoperative
due to a loss of power If a visual annunciator is used, it shall
be clearly visible in the room.
3009.1.3 Travel speed. After a seismic switch has been trig-
gered, the elevator shall have the ability to operate at a "go
slow " speed until the elevator can be inspected ''Go slow''
speed is defined as a travel speed of not more than 150 feet
per minute (45. 72 meters per minute).
3009.1.4 Cable-operated elevators. For cable-operated
elevators, an additional sensor switch shall be installed on
the governor rope/sheave. The sensor shall prevent car
movement when the governor tail sheave is dislodged from
its normal position.
2010 CALIFORNIA BUILDING CODE
461
462 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 31 - SPECIAL CONSTRUCTION
Adopting agency
esc
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
Adopt only those sections that
are listed below
X
X
Chapter/Section
3101
X
3102
X
3102.3.1
X
3103
X
3104
X
3104.2, Exception 2 only
X
3104.2
X
X
X
3105
X
3105.4
X
3106
X
3109
t
t
3109.4.4
X
3110
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
The state agency does not adopt sections identified by the following symbol: f
2010 CALIFORNIA BUILDING CODE
463
464 2010 CALIFORNIA BUILDING CODE
CHAPTER 31
SPECIAL CONSTRUCTION
SECTION 3101
GENERAL
3101.1 Scope. The provisions of this chapter shall govern spe-
cial building construction including membrane structures,
temporary structures, pedestrian walkways and tunnels, auto-
matic vehicular gates, awnings and canopies, marquees, signs,
and towers and antennas.
SECTION 3102
MEMBRANE STRUCTURES
3102.1 General. The provisions of this section shall apply to
air- supported, air-inflated, membrane-covered cable and
membrane-covered frame structures, collectively known as
membrane structures, erected for a period of 180 days or lon-
ger. Those erected for a shorter period of time shall comply
with the California Fire Code. Membrane structures covering
water storage facilities, water clarifiers, water treatment plants,
sewage treatment plants, greenhouses and similar facilities not
used for human occupancy are required to meet only the
requirements of Sections 3102.3.1 and 3102.7. Membrane
structures erected on a building, balcony, deck or other struc-
ture for any period of time shall comply with this section.
3102.2 Definitions. The following words and terms shall, for
the purposes of this section and as used elsewhere in this code,
have the meanings shown herein.
AIR-INFLATED STRUCTURE. A structure that uses
air-pressurized membrane beams, arches or other elements to
enclose space. Occupants of such a structure do not occupy the
pressurized area used to support the structure.
AIR-SUPPORTED STRUCTURE. A building wherein the
shape of the structure is attained by air pressure and occupants
of the structure are within the elevated pressure area. Air-sup-
ported structures are of two basic types:
Double skin. Similar to a single skin, but with an attached
liner that is separated from the outer skin and provides an
airspace which serves for insulation, acoustic, aesthetic or
similar purposes.
Single skin. Where there is only the single outer skin and
the air pressure is directly against that skin.
CABLE-RESTRAINED, AIR-SUPPORTED STRUC-
TURE. A structure in which the uphft is resisted by cables or
webbings which are anchored to either foundations or dead
men. Reinforcing cable or webbing is attached by various
methods to the membrane or is an integral part of the mem-
brane. This is not a cable-supported structure.
MEMBRANE-COVERED CABLE STRUCTURE, A
nonpressurized structure in which a mast and cable system pro-
vides support and tension to the membrane weather barrier and
the membrane imparts stability to the structure.
MEMBRANE-COVERED FRAME STRUCTURE. A
nonpressurized building wherein the structure is composed of a
rigid framework to support a tensioned membrane which pro-
vides the weather barrier.
NONCOMBUSTIBLE MEMBRANE STRUCTURE. A
membrane structure in which the membrane and all component
parts of the structure are noncombustible.
3102.3 Type of construction. Noncombustible membrane
structures shall be classified as Type IIB construction.
Noncombustible frame or cable-supported structures covered
by an approved membrane in accordance with Section
3102.3.1 shall be classified as Type IIB construction. Heavy
timber frame- supported structures covered by an approved
membrane in accordance with Section 3 102.3. 1 shall be classi-
fied as Type IV construction. Other membrane structures shall
be classified as Type V construction.
Exception: Plastic less than 30 feet (9144 mm) above any
floor used in greenhouses, where occupancy by the general
public is not authorized, and for aquaculture pond covers is
not required to meet the fire propagation performance crite-
ria of NFPA 701.
3102.3.1 Membrane and interior liner material. Mem-
branes and interior liners shall be either noncombustible as
set forth in Section 703.4 or meet the fire propagation per-
formance criteria of NFPA 701 and the manufacturer's test
protocol. All fabrics and all interior decorative fabrics or
materials shall be flame resistant in accordance with appro-
priate standards set forth in CCR, Title 19, Division 1,
Chapter 8. Tops and sidewalls shall be made either from
fabric which has been flame resistant treated with an
approved exterior chemical process by an approved appli-
cation concern, or from inherently flame resistant fabric
approved and listed by the State Fire Marshal (see CCR,
Title 19, Division 1, Chapter 8).
Exception: Plastic less than 20 mil (0.5 nmi) in thickness
used in greenhouses, where occupancy by the general
public is not authorized, and for aquaculture pond covers
is not required to meet the fire propagation performance
criteria of NFPA 701.
3102.4 Allowable floor areas. The area of a membrane struc-
ture shall not exceed the Hmitations set forth in Table 503,
except as provided in Section 506.
3102.5 Maximum height. Membrane structures shall not
exceed one story nor shall such structures exceed the height
limitations in feet set forth in Table 503.
Exception: Noncombustible membrane structures serving
as roofs only.
3102.6 Mixed construction. Membrane structures shall be
permitted to be utilized as specified in this section as a portion
of buildings of other types of construction. Height and area
2010 CALIFORNIA BUILDING CODE
465
SPECIAL CONSTRUCTION
limits shall be as specified for the type of construction and
occupancy of the building.
3102.6.1 Noncombustible membrane. A noncombustible
membrane shall be permitted for use as the roof or as a sky-
light of any building or atrium of a building of any type of
construction provided it is at least 20 feet (6096 mm) above
any floor, balcony or gallery.
3102.6.1.1 Membrane. A membrane meeting the fire
propagation performance criteria of NFPA 701 shall be
permitted to be used as the roof or as a skyhght on build-
ings of Types IIB, III, IV and V construction, provided it
is at least 20 feet (6096 mm) above any floor, balcony or
gallery.
3102.7 Engineering design. The structure shall be designed
and constructed to sustain dead loads; loads due to tension or
inflation; live loads including wind, snow or flood and seismic
loads and in accordance with Chapter 16.
3102.8 Inflation systems. Air-supported and air-inflated
structures shall be provided with primary and auxiliary infla-
tion systems to meet the minimum requirements of Sections
3102.8.1 through 3102.8.3.
3102.8.1 Equipment requirements. This inflation system
shall consist of one or more blowers and shall include provi-
sions for automatic control to maintain the required infla-
tion pressures. The system shall be so designed as to prevent
overpressurization of the system.
3102.8.1.1 Auxiliary inflation system. In addition to
the primary inflation system, in buildings exceeding
1,500 square feet (140 m^) in area, an auxiliary inflation
system shall be provided with sufficient capacity to
maintain the inflation of the structure in case of primary
system failure. The auxiUary inflation system shall oper-
ate automatically when there is a loss of internal pressure
and when the primary blower system becomes inopera-
tive.
3102.8.1.2 Blower equipment. Blower equipment shall
meet all of the following requirements:
L Blowers shall be powered by continuous-rated
motors at the maximum power required for any
flow condition as required by the structural design.
2. Blowers shall be provided with inlet screens, belt
guards and other protective devices as required by
the building official to provide protection from
injury,
3. Blowers shall be housed within a weather-protect-
ing structure.
4. Blowers shall be equipped with backdraft check
dampers to minimize air loss when inoperative.
5 . Blower inlets shall be located to provide protection
from air contamination. The location of inlets shall
be approved.
3102.8.2 Standby power. Wherever an auxiliary inflation
system is required, an approved standby power-generating
system shall be provided. The system shall be equipped with
a suitable means for automatically starting the generator set
upon failure of the normal electrical service and for auto-
matic transfer and operation of all of the required electrical
functions at full power within 60 seconds of such service
failure. Standby power shall be capable of operating inde-
pendently for a minimum of 4 hours.
3102.8.3 Support provisions. A system capable of sup-
porting the membrane in the event of deflation shall be pro-
vided for in air-supported and air-inflated structures having
an occupant load of 50 or more or where covering a swim-
ming pool regardless of occupant load. The support system
shall be capable of maintaining membrane structures used
as a roof for Type I construction not less than 20 feet (6096
mm) above floor or seating areas. The support system shall
be capable of maintaining other membranes at least 7 feet
(2134 mm) above the floor, seating area or surface of the
water.
SECTION 3103
TEMPORARY STRUCTURES
3103.1 General. The provisions of this section shall apply to
structures erected for a period of less than 180 days. Tents and
other membrane structures erected for a period of less than 1 80
days shall comply with the California Fire Code. Those erected
for a longer period of time shall comply with applicable sec-
tions of this code.
3103.1.1 Permit required. Temporary structures that cover
an area in excess of 120 square feet (11.16 m^), including
connecting areas or spaces with a conamon means of egress
or entrance which are used or intended to be used for the
gathering together of 10 or more persons, shall not be
erected, operated or maintained for any purpose without
obtaining a permit from the building official.
3103.2 Construction documents. A permit application and
construction documents shall be submitted for each installation
of a temporary structure. The construction documents shall
include a site plan indicating the location of the temporary
structure and information delineating the means of egress and
the occupant load.
3103.3 Location. Temporary structures shall be located in
accordance with the requirements of Table 602 based on the
fire-resistance rating of the exterior walls for the proposed type
of construction.
3103.4 Means of egress. Temporary structures shall conform
to the means of egress requirements of Chapter 10 and shall
have a maximum exit access travel distance of 100 feet (30 480
mm).
SECTION 3104
PEDESTRIAN WALKWAYS AND TUNNELS
3104.1 General. This section shall apply to connections
between buildings such as pedestrian walkways or tunnels,
located at, above or below grade level, that are used as a means
of travel by persons. The pedestrian walkway shall not contrib-
ute to the building area or the number of stories or height of
connected buildings.
466
2010 CALIFORNIA BUILDING CODE
SPECIAL CONSTRUCTION
3104.2 Separate structures. Connected buildings shall be
considered to be separate structures.
Exceptions:
1 . Buildings on the same lot in accordance with Section
503.1.2.
2. [DSA-AC & HCD 1-AC] For purposes of accessibil-
ity as required by Chapter 11 A, structurally con-
nected buildings, buildings connected by stairs,
walkways, or roofs, and buildings with multiple
wings shall be considered one structure.
3104.3 Construction. The pedestrian walkway shall be of
noncombustible construction.
Exceptions:
1, Combustible construction shall be permitted where
connected buildings are of combustible construction.
2. Fire-retardant-treated wood, in accordance with
Section 603.1, Item 25.3, shall be permitted for the
roof construction of the pedestrian walkway where
connected buildings are a minimum of Type I or II
construction.
3104.4 Contents. Only materials and decorations approvedby
the building official shall be located in the pedestrian walkway,
3104.5 Fire barriers between pedestrian walkways and
buUdings. Walkways shall be separated from the interior of the
building by not less than 2-hour fire barriers constructed in
accordance with Section 707 or horizontal assemblies con-
structed in accordance with Section 712, or both. This protec-
tion shall extend vertically from a point 10 feet (3048 mm)
above the walkway roof surface or the connected building roof
line, whichever is lower, down to a point 10 feet (3048 mm)
below the walkway and horizontally 10 feet (3048 mm) from
each side of the pedestrian walkway. Openings within the
10-foot (3048 mm) horizontal extension of the protected walls
beyond the walkway shall be equipped with devices providing
2iV^-\iom fire protection rating in accordance with Section 715.
Exception: The walls separating the pedestrian walkway
from a connected building and the openings within the 10-
foot (3048 mm) horizontal extension of the protected walls
beyond the walkway are not required to have di fire-resis-
tance rating by this section where any of the following con-
ditions exist:
1 . The distance between the connected buildings is more
than 10 feet (3048 mm). The pedestrian walkway and
connected buildings, except for open parking garages,
are equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1 . The wall
is capable of resisting the passage of smoke or is con-
structed of a tempered, wired or laminated glass wall
and doors subject to the following:
1.1. The wall or glass separating the interior of the
building from the pedestrian walkway shall be
protected by an automatic sprinkler system in
accordance with Section 903.3.1.1 and the
sprinkler system shall completely wet the en-
tire surface of interior sides of the wall or glass
when actuated;
1.2. The glass shall be in a gasketed frame and in-
stalled in such a manner that the framing sys-
tem will deflect without breaking (loading)
the glass before the sprinkler operates; and
1.3. Obstructions shall not be installed between
the sprinkler heads and the wall or glass.
2. The distance between the connected buildings is more
than 10 feet (3048 mm) and both sidewalls of the
pedestrian walkway are at least 50 percent open with
the open area uniformly distributed to prevent the
accumulation of smoke and toxic gases.
3. Buildings are on the same lot in accordance with Sec-
tion 503.1.2.
4. Where exterior walls of connected buildings are
required by Section 705 to have di fire-resistance rat-
ing greater than 2 hours, the walkway shall be
equipped throughout with an automatic sprinkler sys-
tem installed in accordance with Section 903.3.1.1.
The previous exception shall apply to pedestrian walkways
having a maximum height above grade of three stories or 40
feet (12 192 mm), or five stories or 55 feet (16 764 nrni) where
sprinklered.
3104.6 Public way. Pedestrian walkways over a public way
shall also comply with Chapter 32.
3104.7 Egress. Access shall be provided at all times to sipedes-
trian walkway that serves as a required exit,
3104.8 Width. The unobstructed width of pedestrian walk-
ways shall not be less than 36 inches (914 nrni). The total width
shall not exceed 30 feet (9144 mm).
3104.9 Exit access travel. The length of exit access travel shall
not exceed 200 feet (60 960 mm).
Exceptions:
1 . Exit access travel distance on a pedestrian walkway
equipped throughout with an automatic sprinkler sys-
tem in accordance with Section 903.3.1.1 shall not
exceed 250 feet (76 200 mm).
2. Exit access travel distance on a pedestrian walkway
constructed with both sides at least 50 percent open
shall not exceed 300 feet (91 440 mm).
3. Exit access travel distance on 2i pedestrian walkway
constructed with both sides at least 50 percent open,
and equipped throughout with an automatic sprinkler
system in accordance with Section 903.3 . 1.1, shall not
exceed 400 feet (122 m).
3104.10 Hinneled walkway. Separation between the tunneled
walkway and the building to which it is connected shall not be
less than 2-hour fire-resistant construction and openings
therein shall be protected in accordance with Table 715.4.
SECTION 3105
AWNINGS AND CANOPIES
3105.1 General. Awnings or canopies shall comply with the
requirements of this section and other applicable sections of
this code.
2010 CALIFORNIA BUILDING CODE
467
SPECIAL CONSTRUCTION
3105.2 Definition. The following term shall, for the purposes
of this section and as used elsewhere in this code, have the
meaning shown herein.
RETRACTABLE AWNING. A retractable awning is a cover
with a frame that retracts against a building or other structure to
which it is entirely supported.
3105.3 Design and construction. Awnings and canopies shall
be designed and constructed to withstand wind or other lateral
loads and live loads as required by Chapter 16 with due allow-
ance for shape, open construction and similar features that
relieve the pressures or loads. Structural members shall be pro-
tected to prevent deterioration. Awnings shall have frames of
noncombustible material, fire-retardant-treated wood, wood
of Type IV size, or 1-hour construction with combustible or
noncombustible covers and shall be either fixed, retractable,
folding or collapsible.
3105.4 Canopy materials. Canopies shall be constructed of a
rigid framework with an approved covering that meets the fire
propagation performance criteria of NFPA 701 or has di flame
spread index not greater than 25 when tested in accordance
with ASTM E 84 or UL 123, All fabrics and all interior decora-
tive fabrics or materials shall be flame resistant in accordance
with appropriate standards set forth in CCR, Title 19, Division
7, Chapter 8. Tops and sidewalls shall be made either from fab-
ric which has been flame resistant treated with an approved
exterior chemical process by an approved application concern,
or from inherently flame resistant fabric approved and listed by
the State Fire Marshal (see CCR, Title 19, Division 1, Chapter
8).
SECTION 3106
MARQUEES
3106.1 General. Marquees shall comply with this section and
other applicable sections of this code.
3106.2 Thickness. The maximum height or thickness of a mar-
quee measured vertically from its lowest to its highest point
shall not exceed 3 feet (914 mm) where the marquee projects
more than two-thirds of the distance from the property line to
the curb line, and shall not exceed 9 feet (2743 mm) where the
marquee is less than two-thirds of the distance from the prop-
erty line to the curb line.
3106.3 Roof construction. Where the roof or any part thereof
is a skylight, the skylight shall comply with the requirements of
Chapter 24. Every roof and skylight of a marquee shall be
sloped to downspouts that shall conduct any drainage from the
marquee in such a manner so as not to spill over the sidewalk.
3106.4 Location prohibited. Every marquee shall be so
located as not to interfere with the operation of any exterior
standpipe, and such that the marquee does not obstruct the clear
passage of stairways or exit discharge from the building or the
installation or maintenance of street lighting.
3106.5 Construction. A marquee shall be supported entirely
from the building and constructed of noncombustible materi-
als. Marquees shall be designed as required in Chapter 16.
Structural members shall be protected to prevent deterioration.
SECTION 3107
SIGNS
3107.1 General. Signs shall be designed, constructed and
maintained in accordance with this code.
SECTION 3108
TELECOMMUNICATION AND
BROADCAST TOWERS
3108.1 General, Towers shall be designed and constructed in
accordance with the provisions of TIA-222.
Exception: Single free-standing poles used to support
antennas not greater than 75 feet (22 860 mm), measured
from the top of the pole to grade, shall not be required to be
noncombustible.
3108.2 Location and access. Towers shall be located such that
guy wires and other accessories shall not cross or encroach
upon any street or other public space, or over above-ground
electric utility lines, or encroach upon any privately owned
property without the written consent of the owner of the
encroached-upon property, space or above-ground electric
utility lines. Towers shall be equipped with cHmbing and work-
ing facilities in compliance with TIA-222. Access to the tower
sites shall be limited as required by applicable OSHA, FCC and
EPA regulations.
SECTION 3109
SWIMMING POOL ENCLOSURES AND
SAFETY DEVICES
3109.1 GeneraL Swimming pools shall comply with the
requirements of this section and other applicable sections of
this code.
3109.2 Definition. The following word and term shall, for the
purposes of this section and as used elsewhere in this code,
have the meaning shown herein.
SWIMMING POOLS. Any structure intended for swimming,
recreational bathing or wading that contains water over 24
inches (610 mm) deep. This includes in-ground, above-ground
and on-ground pools; hot tubs; spas and fixed-in-place wading
pools.
3109.3 Public swimming pools. Public swimming pools shall
be completely enclosed by a fence at least 4 feet (1290 nun) in
height or a screen enclosure. Openings in the fence shall not
permit the passage of a 4-inch-diameter (102 mm) sphere. The
fence or screen enclosure shall be equipped with self-closing
and self-latching gates.
468
2010 CALIFORNIA BUILDING CODE
SPECIAL CONSTRUCTION
3109.4 Residential swimming pools. Residential swiniming
pools shall comply with Sections 3109.4.1 through 3109.4.3.
Exception: A swimming pool with a power safety cover or
a spa with a safety cover complying with ASTM F 1346.
3109.4.1 Barrier height and clearances. The top of the
barrier shall be at least 48 inches (1219 mm) above grade
measured on the side of the barrier that faces away from the
swimming pool. The maximum vertical clearance between
grade and the bottom of the barrier shall be 2 inches (51
mm) measured on the side of the barrier that faces away
from the swimming pool. Where the top of the pool struc-
ture is above grade, the barrier is authorized to be at ground
level or mounted on top of the pool structure, and the maxi-
mum vertical clearance between the top of the pool structure
and the bottom of the barrier shall be 4 inches (102 mm).
3109.4.1.1 Openings. Openings in the barrier shall not
allow passage of a 4-inch-diameter (102 mm) sphere.
3109.4.1.2 Solid barrier surfaces. Solid barriers which
do not have openings shall not contain indentations or
protrusions except for normal construction tolerances
and tooled masonry joints.
3109.4.1.3 Closely spaced horizontal members.
Where the barrier is composed of horizontal and vertical
members and the distance between the tops of the hori-
zontal members is less than 45 inches (1143 mm), the
horizontal members shall be located on the swimming
pool side of the fence. Spacing between vertical mem-
bers shall not exceed IV4 inches (44 mm) in width.
Where there are decorative cutouts within vertical mem-
bers, spacing within the cutouts shall not exceed P/4
inches (44 mm) in width.
3109.4.1.4 Widely spaced horizontal members.
Where the barrier is composed of horizontal and vertical
members and the distance between the tops of the hori-
zontal members is 45 inches (1 143 mm) or more, spacing
between vertical members shall not exceed 4 inches (102
mm). Where there are decorative cutouts within vertical
members, spacing within the cutouts shall not exceed P/4
inches (44 mm) in width.
3109.4.1.5 Chain link dimensions. Maximum mesh
size for chain link fences shall be a 2V4 inch square (57
mm square) unless the fence is provided with slats fas-
tened at the top or the bottom which reduce the openings
to no more than 1 V4 inches (44 mm).
3109.4.1.6 Diagonal members. Where the barrier is
composed of diagonal members, the maximum opening
formed by the diagonal members shall be no more than
IV4 inches (44 mm).
3109.4.1.7 Gates. Access doors or gates shall comply
with the requirements of Sections 3109.4.1.1 through
3109.4.1.6 and shall be equipped to accommodate a
locking device. Pedestrian access doors or gates shall
open outward away from the pool and shall be self-clos-
ing and have a self-latching device. Doors or gates other
than pedestrian access doors or gates shall have a
self-latching device. Release mechanisms shall be in
accordance with Sections 1008.1.9 and 1109.12. Where
the release mechanism of the self-latching device is
located less than 54 inches (1372 mm) from the bottom
of the door or gate, the release mechanism shall be
located on the pool side of the door or gate at least 3
inches (76 mm) below the top of the door or gate, and the
door or gate and barrier shall have no opening greater
than V2 inch (12.7 mm) within 18 inches (457 mm) of the
release mechanism.
3109.4.1.8 Dwelling wall as a barrier. Where a wall of a
dwelling serves as part of the barrier, one of the following
shall apply:
1. Doors with direct access to the pool through that
wall shall be equipped with an alarm that produces
an audible warning when the door and/or its screen,
if present, are opened. The alarm shall be listed and
labeled in accordance with UL 2017. In dwellings
not required to be Accessible units. Type A units or
Type B units, the deactivation switch shall be
located 54 inches (1372 mm) or more above the
threshold of the door. In dwelUngs required to be
Accessible units. Type A units or Type B units, the
deactivation switch(es) shall be located at 54 inches
(1372 mm) maximum and 48 inches (1219 mm)
minimum above the threshold of the door.
2. The pool shall be equipped with a power safety
cover that complies with ASTM F 1346.
3. Other means of protection, such as self-closing
doors with self-latching devices, which are
approved, shall be accepted so long as the degree
of protection afforded is not less than the protec-
tion afforded by Section 3109.4.1.8, Item 1 or 2.
3109.4.1.9 Pool structure as barrier. Where an above-
ground pool structure is used as a barrier or where the
barrier is mounted on top of the pool structure, and the
means of access is a ladder or steps, then the ladder or
steps either shall be capable of being secured, locked or
removed to prevent access, or the ladder or steps shall be
surrounded by a barrier which meets the requirements of
Sections 3109.4.1.1 through 3109.4.1.8. When the lad-
der or steps are secured, locked or removed, any opening
created shall not allow the passage of a 4-inch-diameter
(102 mm) sphere.
3109.4.2 Indoor swimming pools. Walls surrounding
indoor swimming pools shall not be required to comply
with Section 3109.4.1.8.
3109.4.3 Prohibited locations. Barriers shall be located so
as to prohibit permanent structures, equipment or similar
objects from being used to climb the barriers.
3109.4.4 Private swimming pools (statewide). These regu-
lations are subject to local government modification. The
applicable local government requirements at the time of
application for a building permit should be verified. These
standards become applicable commencing January 1,
1998, to a private, single-family home for which a construc-
tion permit for a new swimming pool has been issued on or
after January 1, 1998.
2010 CALIFORNIA BUILDING CODE
469
SPECIAL CONSTRUCTION
3109.4.4.1 Definitions, As used in this division, the fol-
lowing terms have the following meanings:
APPROVED SAFETY POOL COVER means a manu-
ally or power-operated safety pool cover that meets all of
the performance standards of the American Society for
Testing and Materials (ASTM), in compliance with Stan-
dard F 1346-91.
ENCLOSURE means a fence, wall or other barrier that
isolates a swimming pool from access to the home.
EXIT ALARMS means devices that make audible, con-
tinuous alarm sounds when any door or window that per-
mits access from the residence to the pool area, that is
without any intervening enclosure, is opened or is left
ajar Exit alarms may be battery operated or may be con-
nected to the electrical wiring of the building.
PUBLIC SWIMMING POOL means a swimming pool
operatedfor the use of the general public with or without
charge, or for the use of the members and guests of a pri-
vate club. Public swimming pool does not include a
swimming pool located on the grounds of a private sin-
gle-family home,
SWIMMING POOL or POOL means any structure
intended for swimming or recreational bathing that con-
tains water over 18 inches (457 mm) deep. Swimming
pool includes in- ground and above-ground structures
and includes, but is not limited to, hot tubs, spas, porta-
ble spas and nonportable wading pools.
Authority: Health and Safety Code Section 18942(b)
Reference: Health and Safety Code Section 115921
Ab 3305, Statutes 1996, C.925
3109.4.4.2 Construction permit; safety features
required. Commencing January 1, 2007, except as pro-
vided in Section 3109.4.4.5, whenever a building permit
is issued for construction of a new swimming pool or spa,
or any building permit is issued for remodeling of an
existing pool or spa, at a private, single -family home, it
shall be equipped with at least one of the following seven
drowning prevention safety features:
1 . The pool shall be isolated from access to a home by
an enclosure that meets the requirements of Sec-
tion 3109.4.4.3.
2. The pool shall incorporate removable mesh pool
fencing that meets American Society for Testing
and Materials (ASTM) Specifications F 2286 stan-
dards in conjunction with a gate that is self-closing
and self-latching and can accommodate a key
lockable device,
3. The pool shall be equipped with an approved
safety pool cover that meets all requirements of the
ASTM Specifications F 1346.
4. The residence shall be equipped with exit alarms
on those doors providing direct access to the pool
5. All doors providing direct access from the home to
the swimming pool shall be equipped with a
self-closing, self-latching device with a release
mechanism placed no lower than 54 inches (1372
mm) above the floor.
6. Swimming pool alarms that, when placed in pools,
will sound upon detection of accidental or unau-
thorized entrance into the water. These pool
alarms shall meet and be independently certified
to the ASTM Standard F 2208 ''Standards Specifi-
cation for Pool Alarms" which includes surface
motion, pressure, sonar, laser and infrared type
alarms. For purposes of this article, ''swimming
pool alarms" shall not include swimming protec-
tion alarm devices designed for individual use,
such as an alarm attached to a child that sounds
when the child exceeds a certain distance or
becomes submerged in water.
7. Other means of protection, if the degree of protec-
tion afforded is equal to or greater than that
afforded by any of the devices set forth in items 1 -4,
and have been independently verified by an
approved testing laboratory as meeting standards
for those devices established by the ASTM or the
American Society of Testing Mechanical Engi-
neers (ASME).
Prior to the issuance of any final approval for the com-
pletion of permitted construction or remodeling work,
the local building code official shall inspect the drown-
ing safety prevention devices required by this act and if
no violations are found, shall give final approval.
Authority: Health and Safety Code Section 18942(b)
Reference: Health and Safety Code Section 115922
AB 3305 (Statutes 1996, c.925); AB 2977 (Statutes 2006,
C.926); AB 382 (Statutes 2007, c.XXX)
3109.4.4.3 Enclosure; required characteristics. An
enclosure shall have all of the following characteristics:
1. Any access gates through the enclosure open away
from the swimming pool and are self-closing with
a self-latching device placed no lower than 60
inches (1524 mm) above the ground.
2. A minimum height of 60 inches (1524 mm).
3. A maximum vertical clearance from the ground to
the bottom of the enclosure of 2 inches (51 mm).
4. Gaps or voids, if any, do not allow passage of a
sphere equal to or greater than 4 inches (102 mm)
in diameter.
5. An outside surface free of protrusions, cavities or
other physical characteristics that would serve as
handholds or footholds that could enable a child
below the age of five years to climb over.
Authority: Health and Safety Code Section
18942(b)
Reference: Health and Safety Code Section
115923
Ab 3305, Statutes 1996, C925
3109.4.4.4 Agreements to build; notice of provisions.
Any person entering into an agreement to build a swim-
ming pool or spa, or to engage in permitted work on a
470
2010 CALIFORNIA BUILDING CODE
SPECIAL CONSTRUCTION
pool or spa covered by this article, shall give the con-
sumer notice of the requirements of this article.
Pursuant to existing law, the Department of Health
Services shall have available on the department's web
site, commencing January I, 2007, approved pool safety
information available for consumers to download. Pool
contractors are encouraged to share this information
with consumers regarding the potential dangers a pool
or spa poses toddlers. Additionally, pool contractors
may provide the consumer with swimming pool safety
materials produced from organizations such as the
United States Consumer Product Safety Commission,
Drowning Prevention Foundation, California Coalition
for Children's Safety & Health, Safe Kids Worldwide,
Association of Pool and Spa Professionals, or the Ameri-
can Academy of Pediatrics.
Authority: Health and Safety Code Section 18942(b)
Reference: Health and Safety Code Section 115926
AB 3305 (Statutes 1996, c.925); AB 2977 (Statutes
2006, C.926); AB 382 (Statutes 2007, c.XXX)
3109.4.4.5 Exempt facilities. The requirements of this
article shall not apply to any of the following:
1. Public swimming pools.
2. Hot tubs or spas with locking safety covers that
comply with the American Society for Testing
Materials Emergency Performance Specification
(ASTMES 13-89).
3. Any pool within the jurisdiction of any political
subdivision that adopts an ordinance for swim-
ming pool safety that includes requirements that
are at least as stringent as this division.
4. An apartment complex or any residential setting
other than a single-family home.
Authority: Health and Safety Code Section
18942(b)
Reference: Health and Safety Code Section
115925
Ab 3305, (Statutes 1996, c.925); AB 2977 (Stat-
utes 2006, c.926); AB 382 (Statutes 2007,c.XXX)
3109.4.4.6 Application to facilities regulated by
Department of Social Services, This division does not
apply to any facility regulated by the State Department of
Social Services even if the facility is also used as a pri-
vate residence of the operator Pool safety in those facili-
ties shall be regulated pursuant to regulations adopted
therefor by the State Department of Social Services.
Authority: Health and Safety Code Section 18942(b)
Reference: Health and Safety Code Section 115926
Ab 3305, Statutes 1996, c.925); AB 2977 (Statutes 2006,
c.926); AB 382 (Statutes 2007, c.XXX)
3109.4.4.7 Modification and interpretation of division.
Notwithstanding any other provision of law, this article
shall not be subject to further modification or interpreta-
tion by any regulatory agency of the state, this authority
being reserved exclusively to local jurisdictions, as pro-
vided for in Item 5 of Section 3109.4.4.2 and Item 3 of
Section 3109.4.4.5.
Authority: Health and Safety Code Section 18942(b)
Reference: Health and Safety Code Section 115927
AB 3305 (Statutes 1996, c.925); AB 2977 (Statutes 2006,
c.926); AB 382 (Statutes 2007, c.XXX)
3109,4.4,8 Construction requirements for building a
pool or spa. Whenever a building permit is issued for the
construction a new swimming pool or spa, the pool or
spa shall meet all of the following requirements:
1. The suction outlet of the pool or spa for which the
permit is issued shall be equipped to provide circu-
lation throughout the pool or spa as prescribed in
Paragraph 2.
2. The swimming pool or spa shall have at least two
circulation drains per pump that shall be hydrauli-
cally balanced and symmetrically plumbed
through one or more ''T" fittings, and that are sep-
arated by a distance of at least three feet in any
dimension between the drains. Suction outlets that
are less than 12 inches across shall be covered
with antientrapment grates, as specified in the
ASME/ANSl Standard A 112.19.8, that cannot be
removed except with the use of tools. Slots of open-
ings in the grates or similar protective devices
shall be of a shape, area and arrangement that
would prevent physical entrapment and would
pose any suction hazard to bathers.
3. Any backup safety system that an owner of a new
swimming pools or spa may choose to install in
addition to the requirements set forth in subdivi-
sions (1) and (2) shall meet the standards as pub-
lished in the document, "Guidelines for
Entrapment Hazards: Making Pools and Spas
Safer," Publication Number 363, March 2005,
United States Consumer Products Safety Commis-
sion.
4. Whenever a building permit is for the remodel or
modification of any existing swimming pool, tod-
dler pool or spa, the permit shall require that the
suction outlet of the existing swimming pool, tod-
dler pool or spa be upgraded so as to be equipped
with an antientrapment cover meeting current
standards of the American Society for Testing and
Materials (ASTM) or the American Society of
Mechanical Engineers (ASME),
Authority: Health and Safety Code Section
18942(b)
Reference: Health and Safety Code Section
115928 AB 3305 (Statutes 1996, c.925); AB 2977
(Statutes 2006, c.926); AB 382 (Statutes 2007,
c.XXX)
3109.5 Entrapment avoidance. Suction outlets shall be
designed and installed in accordance with ANSI/APSP-7.
2010 CALIFORNIA BUILDING CODE
471
SPECIAL CONSTRUCTION
SECTION 3110
AUTOMATIC VEHICULAR GATES
3110.1 General. Automatic vehicular gates shall comply with
the requirements of this section and other applicable sections of
this code.
3110.2 Definitions. The following word and term shall, for the
purposes of this section and as used elsewhere in this code,
have the meaning shown herein.
VEHICULAR GATE. A gate that is intended for use at a
vehicular entrance or exit to a facility, building or portion
thereof, and that is not intended for use by pedestrian traffic.
3110.3 Vehicular gates intended for automation. Vehicular
gates intended for automation shall be designed, constructed
and installed to comply with the requirements of ASTM F
2200.
3110.4 Vehicular gate openers. Vehicular gate openers, when
provided, shall be listed in accordance with UL 325.
472 2010 CALIFORNIA BUILDING CODE
CHAPTER 31 A
RESERVED
201 CALIFORNIA BUILDING CODE 473
474 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 31 B - PUBLIC SWIMMING POOLS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SB
ss/cc
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
X
Chapter/Section
3113B.1 w/Exception 4 only
X
2010 CALIFORNIA BUILDING CODE
475
476 2010 CALIFORNIA BUILDING CODE
CHAPTER 31 B[DPH]
PUBLIC SWIMMING POOLS
Division I— GENERAL
SECTION 31 01 B
SCOPE
The provisions of this chapter shall apply to the construction,
installation, alteration, addition, relocation, replacement or
use of any public swimming pool, to its appurtenant auxiliary
areas and facilities and to its mechanical equipment and
related piping.
Notes:
1. Examples of public pools include those located in the
following: commercial building, hotel, motel, resort,
automobile and trailer park, automobile court, mo-
bile home park, campground, apartment house, con-
dominium, townhouse, homeowner association, club,
community building, public or private school, gymna-
sium and health establishments.
2. See the California Energy Code, Part 6, for additional
swimming pool standards.
SECTION 31 02B
DEFINITIONS
For the purpose of this chapter, the following terms shall
have the meanings indicated:
AUXILIARY AREA is a public dressing, locker, shower or toi-
let area or building space intended to be used by bathers.
BACKWASH is the process of thoroughly cleansing the filter
media and/or elements and the contents of the filter vessel.
BATHER is a person using a pool and adjoining deck areas for
the purpose of water sports such as diving, swimming, wading
or related activities.
CLEAN POOL WATER is a pool water that is free of dirt, oils,
scum, algae, floating materials or other visible organic and
inorganic materials that would sully the water.
CLEAR POOL WATER is pool water that is free from cloudi-
ness and is transparent.
CORROSION RESISTANT is capable of maintaining origi-
nal surface characteristics under the prolonged influence of
the use environment.
DECK is an area surrounding a pool which is specifically con-
structed or installed for use by bathers.
DRAIN is a fitting or fixture, usually at or near the bottom of a
pool, through which water leaves the pool normally to the
recirculation pump.
EFFECTIVE PARTICLE SIZE is the theoretical size of sieve
that will pass 10 percent by weight of sand.
ENFORCING AGENCY means the health officer or director
of environmental health or their designated registered sanitar-
ian representative.
EQUIPMENT AREA is an area used for pool recirculation
and purification equipment and related piping appurtenances.
INLET is a fitting or fixture through which circulation water
enters the pool
LADDER is a series of vertically separate treads or rungs
either connected by vertical rail members or independently
fastened to an adjacent vertical pool wall
MEDICAL POOL is a special-purpose pool used by a
state-recognized medical institution engaged in the healing
arts under the direct supervision of licensed medical personnel
for treatment of the infirm.
OVERFLOW SYSTEM is the system which includes perime-
ter-type overflow gutters, surface skimmers, surge or collector
tanks, other surface water collective system components and
their interconnecting piping.
POOL is a constructed or prefabricated artificial basin, cham-
ber or tank intended to be used primarily by bathers, and not
for cleaning of the body or for individual therapeutic use.
POOL VOLUME is the amount of water expressed in gallons
(liters), that a pool holds when filled.
PRIVATE POOL is any constructed pool, permanent or porta-
ble, which is intended for noncommercial use as a swimming
pool by not more than three owner families and their guests.
Note: A single-family residence is a Group R, Division 3
occupancy.
PUBLIC POOL is a pool other than a private pool.
RECESSED STEPS is a riser/tread or series of risers/treads
extending down into the deck with the bottom riser or tread ter-
minating at the pool wall (thus creating a "stairwell").
RECESSED TREADS are a series of vertically spaced cavi-
ties in the pool wall creating tread areas for step holes.
RECIRCULATION SYSTEM is the interconnected system
traversed by the recirculated water from the pool until it is
returned to the pool, i.e., from the pool through the collector or
surge tank, recirculation pump, filters, chemical treatment and
heater (if provided), and returned to the pool.
SHALLOW POOL is a pool that has a maximum depth of less
than 6 feet (1829 mm).
SLIP RESISTANT is a rough finish that is not abrasive to the
barefoot.
STAIRS are series of two or more steps.
STEP is a riser and tread.
2010 CALIFORNIA BUILDING CODE
477
PUBLIC SWIMMING POOLS
STEPS, RECESSED STEPS, LADDERS AND RECESSED
TREADS are those means of entry and exit to and from the pool
which may he used in conjunction with each other
TREATMENT OF WATER is the process of conditioning and
disinfection of pool water by means of a combination of filtra-
tion and the addition of chemicals to the water
TURNOVER TIME is the period of time, in hours, required to
circulate a volume of water equal to the pool capacity,
UNIFORMITY COEFFICIENT is the ratio of theoretical
size of a sieve that will pass 60 percent of the sand to the theo-
retical size of sieve that will pass 10 percent.
WATERLINE shall be defined in one of the following:
1. Skimmer system. The waterline shall be the midpoint of
the operating range of the skimmers,
2. Overflow system. The waterline shall be the top edge of
the overflow rim.
SECTION 3103B
SPECIAL POOL CLASSIFICATIONS
3103B,1 Spa pool. A spa pool is a pool not used under medical
supervision, that incorporates a water jet system, an aeration
system or a combination of the two systems, and which may
also utilize artificially heated water The surface water area of
a spa pool shall not exceed 250 square feet (23 m^), and the
water depth shall not exceed 4 feet (1219 mm).
Note: See also Section 3119B.1.2.
3I03B.2 Special-purpose pool A special-purpose pool is a
pool intended to be used exclusively for a single purpose, such
as wading, instruction, diving, competition or for medical
treatment where a licensed professional in the healing arts is in
attendance.
3103B.3 Temporary training pool A temporary training pool
is a pool intended to be used for instruction in swimming, hav-
ing a maximum water depth of 36 inches (914 mm), and so con-
structed as to be readily disassembled for storage or for
transporting to and reassembly to its original integrity at a dif-
ferent location. A temporary training pool shall be limited to a
maximum use of three months at any one geographical location
during any 12 -month period.
3103B.4 Wading pool A wading pool is a pool intended to be
used for wading by small children and having a maximum
depth of 18 inches (457 mm) at the deepest point and a maxi-
mum depth of 12 inches (305 mm) at side walls.
SECTION 31 04B
ACCESSIBILITY TO THE PHYSICALLY
HANDICAPPED PERSON
Swimming pools and their appurtenances shall be in compli-
ance with the requirements of the state architect for access to
public accommodations by physically handicapped persons.
Note: See Chapter 11 A.
SECTION 3105B
ALTERNATE EQUIPMENT, MATERIALS AND
METHODS OF CONSTRUCTION
3105B.1 The enforcing agency may approve an alternate
equipment, material or method of construction, provided it
finds that the proposed design is satisfactory and complies with
the provisions of this chapter, that the equipment, material,
method or work offered is, for the purpose intended, at least
equivalent to that prescribed in suitability, strength, effective-
ness, fire resistance, durability, safety and sanitation, or that
the methods of installation proposed conform to other accept-
able nationally recognized standards, and providing the alter-
nate has been approved and its use authorized by the enforcing
agency,
3105B.2 The enforcing agency shall require that sufficient evi-
dence or proof be submitted to substantiate any claims that
may be made regarding its use,
3105B.3 Whenever there is insufficient evidence of compliance
with the provisions of this chapter, the enforcing agency may
require tests as proof of compliance to be made at no expense to
the enforcing agency. Tests shall be made in accordance with
approved standards, but in the absence of such standards, the
enforcing agency shall specify the test procedure.
POOL STRUCTURE
SECTION 31 06B
POOL CONSTRUCTION
3106BJ Shell structural integrity. The pool shall be designed
and durably built of reinforced concrete, or material equiva-
lent in strength, water tight, and able to withstand anticipated
stresses under both full and empty conditions, taking into con-
sideration climatic effect, geological conditions, integration of
the pool with other structures and similar factors,
3106B,2 Finish. The finished pool shell shall be lined with a
smooth waterproof interior finish that will withstand repeated
brushing, scrubbing and cleaning procedures. The interior
pool finish shall completely line the pool to the tile lines, coping
or cantilevered deck.
3106B3 Finish color. The finish color shall be white except
for:
1 . Lane and other required pool markings described in Sec-
tion 3109B;
2. Handholds;
3. Copings;
4. The top surface edges of benches; and
5. The edge of spa steps.
Exception: A spa pool shall be permitted to be finished in a
light (pastel) color other than white when approved by the
enforcing agency.
3106B,4 Projections and recessed areas. The surfaces of the
pool shall not have any projections or recessed areas except for
478
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
handholds, recessed treads, steps, ladders, stairs, pool inlets
and outlets, skimmers and perimeter overflow systems.
Exception: Benches shall be permitted in a spa pool, pro-
viding that the water depth over the bench does not exceed
24 inches (610 mm).
SECTION 3107B
ADDITIONAL REQUIREMENTS FOR A TEMPORARY
TRAINING POOL
3107B,1 A temporary training pool shall comply with this sec-
tion in addition to the provisions contained in Section 3106B.
3107BJJ Installation site, A temporary training pool shall
be installed on a paved level surface extending at least 10
feet (3048 mm) beyond all pool walls.
3 107 B, 1,2 Cover, The temporary training pool shall be pro-
vided with a solid cover. The cover shall be installed during
periods when the pool is not open for use and shall be
secured to the pool in a manner to prevent unauthorized
removal.
3107B,1,3 Design, The pool cover shall be designed to sup-
port a uniform live load of 40 pounds per square foot (1.9
kN/m^). The structural design of the pool cover shall be
approved by a California-registered professional engineer.
SECTION 3108B
POOL GEOMETRY
3108B,1 Dimensions and slopes. The dimensions and slopes
of a pool shall conform to the appropriate Figure 31B-1
through 31B-3.
Exception: A special-purpose pool shall be permitted a
depth greater than 3 Vifeet (1067 mm) at the shallowest end.
3108B,2 Drainahle, The pool shall be completely drainable
through a main drain which shall be located at the deepest
point in the pool.
3108B,3 Dimensional tolerance, A construction tolerance
shall be permitted on all dimensions in Figures 31B-1, 31B-2
and31B-3y not to exceed! inches (51 mm) except that the toler-
ance of the water level of a pool with a nonadjustable overflow
system shall not exceed V^ inch (3.2 mm).
3108B,4 Slope break from shallow to deep water. When a pool
has a change in bottom slope from shallow to deep water,
flush-mounted devices for fastening a safety rope and buoys
across the pool shall be installed where the water depth is 4 Vi
feet (1372 mm).
contrasting color across the bottom of the pool where the water
depth is 4 Vifeet (1372 mm).
Exception: Pools having a maximum depth of 5 feet (1524
mm) or less shall not be required to have a depth marking
line.
3109B.3 Decorative designs. Designs on the bottom or walls of
the pool which are shaped in a form that might reasonably be
mistaken f on or give the illusion of being, a human form shall
be prohibited.
3109B.4 Water depth markers,
3109B,4,1 General, The water depth shall be clearly
marked at the following locations:
1. Maximum depth;
2. Minimum depth;
3. Each end;
4. At the break in the bottom slop between the shallow
and deep portions of the pool (see also Section
3108B.4); and
5. On the perimeter of the pool at distances not to exceed
25 feet (7620 mm)
Exception: A spa or wading pool shall have a min-
imum of two depth markers indicating the maxi-
mum depth.
3109B,4,2 Location, Depth markers shall be located on the
vertical pool walls at each end and side of the pool at or
above the water level. If a pool exceeds 20 feet (6096 mm) in
width, additional markers shall be located on the edge of the
deck next to the pool.
Exception: If depth markers cannot be located on the
vertical pool walls above the waterline because of the
pool design, the depth markers shall be located so as to
be clearly visible to bathers in the pool.
3109B,4,3 Tolerance, Depth markers shall be positioned to
indicate the water depth accurate to the nearest 6 inches
(152 mm).
3109B,4,4 Size of markers. Depth markers shall:
1. Have numerals a minimum of 3 inches (76 mm) in
height and of a color contrasting with the back-
ground.
2. Be made of a durable material that is resistant to
weathering; and
3. Be slip resistant when they are located on the pool
deck.
SECTION 31 09B
PERMANENT MARKINGS
3109B,1 Lane markings. Slip-resistant lane lines or other
markings at the bottom of the pool shall not exceed 12 inches
(305 mm) in width.
3I09B.2 Depth marking line. There shall be installed a
straight line of slip-resistant tile, 4 inches (102 mm) wide, of
2010 CALIFORNIA BUILDING CODE
479
PUBLIC SWIMMING POOLS
DEPTHS AND CLEARANCES FOR POOLS WITH BOARDS ABOVE 30"
PLAN VIEW
UNOBSTRUCTED HEADROOM
AREA FOR DIVERS
M^^IMUM 3'-6'
®
3' -44" — —
1-10 MAXIMUM SLOPE
1-3 MAXIMUM SLOPE
— L-3 4^ L-4 i— -4
LONGITUDINAL SECTION
FIGURE 1
TABLE 1
MINIMUM REQUIRED DEPTHS AND CLEARANCES
FOR 1 -METER AND 3-METER BOARDS
w9t^^ 4" WOT0*
•-I
o-t
L»»<t»
t-1
L-«
4.-4
751
4--cr
•'-4r
t'.«r
♦•-•"
»'-<ritf<r
ir-4* irf-<r
I'ltoffcf •«»<
4'«r ior-«'
ll'-«"
rfnr
4'-*'
^<*
ii'-4- i^-flT nr-o*
•-or
Notes for Rgure 1 and Table 1 .
1. Maximum radius at shallow end shall be V (T.
2. Springfine (D>1) shall extend to the break in slope between the shallow area and the diving bowl.
3. See exception to Section 31 08B.
4. Dimension t>ased on maximum slope and other minimum or maximum dimensions.
FIGURE 31 B-1— DEPTH AND CLEARANCE FOR POOLS WITH BOARDS ABOVE 30 INCHES (762 mm)
480
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
^
Dtptht ond CkarancM for Poott with Diving Boards
30" or tits Qbovt wattr Itvst.
Table 2
iiiaatil
•-*«««««
fH^ f lir...r
Lt*«tl> •' 0*ett«B ]
0-1
0-1
D-l
0-4
0-ft
0-«
t-l
U-l
L-» t-4
•-I
»-«
MimiMwi
B*.<y*
l-«»
t'-cT
•V
•v
V-«'
I'-o-
nZ-o''
••-o"»-.o-
^-0"
y-<f
«-.-
«'V
itf-<r
Drain
TRANSVERSe SECTION AT D-4
Notes for Figure 2 and Table 2.
1. Maximum radius at shallow end shall be V CT.
2. Springtine (D-1) shall extend to the break In slope between the shallow area and the diving bowl.
3. See exception to Section 3108B.
4. DImenston W-t and W-2 shall apply from wall at deep end to 0-6.
5. Dimension based on maximum slope and other minimum or maximum dimensions.
FIGURE 31 B-2— DEPTH AND CLEARANCES FOR POOLS WITH DIVING BOARDS
2010 CALIFORNIA BUILDING CODE
481
PUBLIC SWIMMING POOLS
Dtptht ond Cteoronctt for Pools without Diving Boards
®D-l
D-2 D-3
Wottr Surfoct
<Y^^M^^MWI M ^A^^
Moilmimi
i-tr
CD
*I0 IteBlmum ttot*
>|i3 Motlmum ilop«
LONGITUDINAL SCCTION
Figures
Rt^ttifttf DlpH ll
Tablea
0«ttti 0f W«t«r
Lcnf tH vf SMttWk I
0-1
0-t
0-)
0-4
L-l
L-2
M«fkt
MMltM««ft
l'-«-
•'.<r
••-•-
v-«-
s'-i"
1-0-
Notes for Rgure 3 and Tabre 3.
1 . Maximum radius at shallow end shall be V 0*.
2. Springline (D-1) shafi extend to the break in slope between the shallow area and the diving bowl.
3. See exception to Section 3108B.
4. Width of ooot at Section D-2 shall be at least 15'-(r.
FIGURE 31 B-3— DEPTH AND CLEARANCES FOR POOLS WITHOUT DIVING BOARDS
SECTION 311 OB
STEPS, RECESSED STEPS, LADDERS AND
RECESSED STAIRS (TREADS)
3110B.1 Construction, A means of entry and exit to and from
the pool shall consist of steps, recessed steps, ladders or stairs,
or a combination of them. One means of entry and exit shall be
provided in the shallowest portion of a pool if the vertical dis-
tance from the bottom of the pool to the deck is over 2 feet (610
mm). A second means of entry and exit shall be provided in the
deep portion of a pool having a depth greater than 4V2 feet
(1372 mm). Where the width of the pool exceeds 30 feet (9144
mm), such means of entry and exit shall be provided at each
side, not more than 100 feet (30 480 mm) apart.
3110B,2 Ladders, Ladders with a handhold shall be corrosion
resistant and shall be equipped with slip-resistant tread sur-
faces. Ladders shall be rigidly installed and shall provide a
clearance of not less than 3 inches (76 mm) or more than 5
inches (127 mm) between any part of the ladder and the pool
wall.
3110B,3 Stairs, Each step of a stair shall have the same dimen-
sions with a tread not less than 12 inches (305 mm) wide, except
that if the top step is curved convexly, the top step tread shall
not be less than 18 inches (457 mm) wide as measured at the
point of maximum curvature. Risers shall be uniform and shall
not exceed 12 inches (305 mm) in height. A safety railing shall
be provided, extending from the deck to not less than a point
above the top of the lowest step and with the upper railing sur-
face not less than 28 inches (711 mm) above the deck.
3110B.4 Steps and step holes. Steps and step holes shall have a
minimum tread of 5 inches (127 mm), width of 14 inches (356
mm) and shall be designed to be readily cleaned.
3110B,5 Hand railings. Hand railings shall be provided at the
top of both sides and shall extend over the coping or edge of the
deck for each ladder and step hole.
3 HOB, 6 Steps for a spa pool Each step of a spa pool shall
have a tread width not less than 12 inches (305 mm). Risers
shall not exceed 9 inches (229 mm) in height when one handrail
is provided, or 12 inches (305 mm) in height when two hand-
rails are provided. A handrail shall be installed over the steps,
with the leading railing edge extending up to a point not less
than 12 inches (305 mm) from the plane of the bottom riser. The
steps shall be located where the deck is at least 4 feet (1219
mm) wide.
482
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
SECTION 3111 B
HANDHOLDS
311 IB, 1 General, Every pool shall he provided with hand-
holds (perimeter overflow system, bull-nosed coping or canti-
levered decking) around the entire perimeter installed not
greater than 9 inches (229 mm) above the waterline.
Exception: Handholds are not requiredfor wading pools.
3111B,2 For special-use pools used for instruction or competi-
tive swimming, a handhold at water level similar to the rim of a
perimeter overflow system is required,
3111B,3 Where perimeter overflow systems are not provided, a
bull-nosed coping or cantilevered decking or reinforced con-
crete, or material equivalent in strength and durability, with
rounded, slip-resistant edges shall be provided. The overhang
for either bull-nosed coping or cantilevered decking shall not
exceed 2 inches (51 mm) or be less than 1 inch (25 mm) and
shall not exceed 2^2 inches (64 mm) in thickness.
Exception: The enforcing agency may accept handholds
other than those specified for spa pools.
SECTION 31 12B
DIVING BOARDS
3112B,1 General, Diving boards and their supports, platforms
and steps shall be substantially constructed and shall be of suf-
ficient structural strength to carry the maximum anticipated
load. Steps shall be of corrosion-resistant material, easily
cleanable and of slip-resistant design,
3112B,2 Railings, Handrails shall be provided at all steps and
ladders leading to diving boards more than 1 meter above the
water, except those steps or ladders set 15 degrees or less from
the vertical. Guardrails extending to a point on the platform
directly above the water's edge shall be provided on both sides
of all platforms and diving boards which are over 1 meter high.
Guardrails shall be 36 inches (914 mm) above the platform or
diving board.
SECTION 31 13B
POOL DECKS
3113B,1 General, A minimum continuous and unobstructed
4 -foot wide (1219 mm) slip-resistant, nonabrasive deck area of
concrete or like material shall be provided flush with the top of
the pool shell wall extending completely around the pool, and
the deck area shall further extend 4 feet (1219 mm) on both
sides and rear of any diving board or slide and their appurte-
nances. The deck width shall be measured from the poolside
edge of the coping lip.
Exceptions:
1, A deck at least 4 feet (1219 mm) in width shall extend
around 50 percent or more of the perimeter of a spa
pool. For spa pools that have their walls extending
above the ground or floor level, the deck area require-
ment shall apply at the ground or floor level unless
otherwise specified by the enforcing agency.
2. The deck width separating a spa pool from an adja-
cent pool shall not be less than 6 feet (1 829 mm) wide.
3. The deck may be omitted from around a temporary
training pool.
4. [DSA-AC] Any mechanism provided to assist persons
with disabilities in gaining entry into the pool and in
exiting from the pool shall comply with Chapter IIB,
Section 1104B.4.3, Participation Areas.
3113B,2 Deck drainage. The pool deck surface shall be sloped
a minimum of^/4 inch (6.4 mm) per foot to deck drains or other
approved surface water disposal areas. The pool deck surface
shall not drain into the pool, its perimeter overflow channel,
into an adjoining spa or other pool or be connected to the retic-
ulation system.
Note: A deck drain system of one 4-inch (102 mm) drain
inlet per 400 square feet (37 m^) of tributary deck area, with
drains spaced 25 feet (7620 mm) apart, usually provides
adequate surface water disposal.
3113B,3 Coping, Pool coping shall be slip resistant.
3113B,4 Coverings, Artificial covering shall be permitted on
the deck area when approved by the enforcing agency.
Note: Deck slopes to provide proper drainage may vary with
the texture of the surface. It is recommended that the mini-
mum slope be creased if artificial covering or exposed
aggregate concrete surface is contemplated.
3113B,5 Handrails shall be provided around the perimeter of
any raised deck of a temporary training pool.
3113B,6 Unpaved areas. Landscape plants, flower beds or
similar unpaved areas shall not be located within 4 feet (1219
mm) of a spa pool.
SECTION 31 14B
POOL LIGHTING
3I14B,I General, Where pool lighting is provided, it shall be
such that lifeguards or other persons may observe, without
interference from direct and reflected glare from the lighting
sources, every part of the underwater area and swimming pool
surface, all diving boards or other pool appurtenances.
Notes: See (Part 3) Article 680 for electrical installation
requirements,
3114B,2 Nighttime use. Pools used at night shall be equipped
with underwater lighting fixtures that will provide complete
illumination to all underwater areas of the pool with no blind
spots. Illumination shall enable a lifeguard or other persons to
determine whether:
1, A bather is lying on the bottom of the pool, and
2. The pool water conforms to the definition of *' Clear pool
water,"
Exception: Pools provided with a system of overhead
lighting fixtures, where it can be demonstrated to the
enforcing agency that the system is equivalent to the
underwater fixture system.
2010 CALIFORNIA BUILDING CODE
483
PUBUC SWIMMING POOLS
3114B.3 Deck area lighting. Where the pool is to be used at
night, pool deck areas shall be provided with lighting so that
persons walking on the deck can identify hazards. Lighting fix-
tures shall be aimed toward the deck area and away from the
pool surface insofar as practical.
ANCILLARY AREAS AND FACILITIES
3115B,4J Showers and lavatories shall be provided with
hot and cold water faucets.
3115B.4,2 Tempered water shall be permitted in lieu of indi-
vidual hot- and cold-water faucets.
3115B,43 A means to limit the hot water to IWF (6rC)
maximum shall be provided to prevent scalding. This tem-
perature limit control shall not be adjustable by the bather.
SECTION 311 5B
BATHHOUSE DRESSING,
SHOWER AND TOILET FACILITIES
31 15 B J Shower and dressing facilities shall be provided for
users of a pool.
Exceptions:
1. Shower and dressing facilities may not be required
when bathers have access to such facilities in adja-
cent living quarters.
2. Public toilet facilities may be omitted when bathers
have access to toilet facilities either in living quarters
located not more than 300 feet (91 440 mm) in travel
distance from the pool, or in an adjacent building
such as a recreational facility, clubhouse or cabana.
3115B.2 Number of sanitary facilities. For the purpose of this
subsection, one bather shall be considered for ever 15 square
feet (1.39 m^) of pool water surface area.
31153,2,1 Showers, One shower shall be provided for every
50 bathers.
3115B,2,2 Toilets, Separate toilet facilities shall be pro-
vided for each sex. One toilet shall be provided for every 60
women, and one toilet plus one urinal for every 75 men.
3115B,2,3 Lavatories,
every 80 bathers.
3115B,3 Construction,
One lavatory shall be provided for
3115B,3,1 Floors, Floors shall have a hard, nonabsorbent
surface such as portland cement concrete, ceramic tile or
other approved material, which extends upward onto the
wall at least 5 inches (127 mm) with a coved base. Floors
which may be walked on by a wet bather shall be slip resis-
tant. Floors shall be sloped not less than V^ inch (6.4 mm)
per foot to floor drains or other approved surface water dis-
posal areas. Carpeting and other similar artificial floor
covering shall not be permitted on shower and toilet room
floors.
Note: Rough rotary, raised rubber or wood float finish of
concrete usually provides a slip-resistant finish.
3115B3,2 Interior wall surfaces. The materials used in the
walls, except for structural elements, shall be of a type of
which is not adversely affected by moisture.
3115B,3,3 Privacy, All doors and windows shall be
arranged to prevent viewing of the interior from any portion
of the building used by the opposite sex and from view from
the outdoors. View screens shall be permitted for this pur-
pose.
3115B,4 Water supply.
SECTION 311 6B
DRINKING FOUNTAINS
One guarded jet drinking fountain shall be provided for the
first 250 bathers and an additional fountain shall be provided
for each additional 200 bathers or fraction thereof The num-
ber of bathers shall be determined according to Section
3115B.2.
Exception: Drinking fountains shall not be required when
drinking water is available at adjacent living quarters, or in
an adjacent building such as a bathhouse, cabana, club-
house or recreational facility.
SECTION 3117B
HOSE BIBBS
Hose bibbs shall be provided for each pool and located so
that all portions of the pool deck area may be reached with a
7 5 -foot (22 860 mm) length of hose attached to the hose bibb.
Hose bibbs shall be located so that they do not constitute a
safety hazard and shall be protected against backftow.
SECTION 31 18B
ENCLOSURE OF POOL AREA
3118B,1 Enclosure, The pool shall be enclosed by one or a
combination of the following: a fence, portion of a building,
wall or other approved durable enclosure. Doors, openable
windows or gates of living quarters or associated private pre-
mises shall not be permitted as part of the pool enclosure. The
enclosure, doors and gates shall meet all of the following speci-
fications:
1 . The enclosure shall have a minimum effective perpendic-
ular height of 5 feet (1524 mm) as measured from the out-
side as depicted in Figures 31B-4 and 31B-5.
2. Openings, holes or gaps in the enclosure, doors and/or
gates shall not allow the passage of a 4-inch (102 mm)
diameter sphere. The bottom of the enclosure shall be
within 2 inches (51 mm) of the finished grade
3. The enclosure shall be designed and constructed so that
it cannot be readily climbed by small children. Horizon-
tal and diagonal member designs, which might serve as a
ladder for small children, are prohibited. Horizontal
members shall be spaced at least 48 inches (1219 mm)
apart. Planters or other structures shall not be permitted
to encroach upon the clear span area as depicted in Fig-
ure 31B-5. Chain link may be used, provided that open-
ings are not greater than 7% inches (44 mm) measured
horizontally.
484
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
3118B.2 Gates, Gates and doors opening into the pool enclo-
sure shall also meet the following specifications:
1. Gates and doors shall he equipped with self-closing and
self-latching devices. The self-latching device shall be
designed to keep the gate or door securely closed. Gates
and doors shall open outward away from the pool except
where otherwise prohibited by law. Hand-activated
door- or gate-opening hardware shall be located at least
3^/2 feet (1067 mm) above the deck or walkway.
2. Except as otherwise provided herein, gates and doors
shall he capable of being locked during times when the
pool is closed. Exit doors which comply with Chapter 10
shall be considered as meeting these requirements.
Exception: Doors leading from areas of hotels and
motels, as defined in Business and Professions Code
Section 25503.16(b), which are open to the general
public, e.g., restaurants, lobbies, bars, meeting rooms
and retail shops, need not be self-latching.
3. The pool enclosure shall have at least one means of
egress without a key for emergency purposes. Unless all
gates or doors are so equipped, those gates and/or doors
which will allow egress without a key shall be clearly and
conspicuously labeled in letters at least 4 inches (102
mm) high ''EMERGENCY EXIT'
4. The enclosure shall be designed and constructed so that
all persons will be required to pass through common
pool enclosure gates or doors in order to gain access to
the pool area. All gates and doors exiting the pool area
shall open into a public area or walkway accessible by
all patrons of the pool.
3118BJ Retroactivity, Sections 3118B.1 and 31I8B.2 shall
apply only to a public swimming pool constructed on or after
July 1, 1994.
3118B,4 Enclosure of pools constructed prior to July i, 1994,
When the physical characteristics of a site preclude providing a
4-foot (1219 mm) deck around the perimeter of an existing
pool, the enforcing agency may allow the installation of an
enclosure which reduces the pool deck to less than 4 feet (1219
mm) in width.
SECTION 311 9B
SIGNS
3119BJ Occupant load sign. A sign with clearly legible letters
not less than 4 inches (102 mm) high shall be posted in a con-
spicuous place near the main entrance to a pool which shall
indicate the number of occupants permitted for each pool.
3119B,L1 Spa pool The occupant capacity of a spa pool
shall be based on one bather for ever 10 square feet (0,929
m^) of pool water surface area,
3119B.1.2 Other pools. The occupant capacity of all other
pools shall be based on one bather for every 20 square feet
(1.858 m^) of pool water surface area.
Exception: Occupant capacity requirements do not
apply to wading pools,
3119B,2 Signs for shallow pool Signs with clearly legible let-
ters not less than 4 inches (102 mm) high shall be posted in a
conspicuous place and shall state: NO DIVING ALLOWED,
3119B,3 Warning sign for pool using gas chlorine. Pools at
which gas chlorine is used for disinfection shall have a con-
spicuously posted sign on the exterior side of the entry door to
the chlorine room, or on the adjacent wall area. In addition to
displaying the appropriate hazard identification symbol for
gas chlorine, the sign shall state with clearly legible letters not
less than 4 inches (102 mm) high the following: DANGER:
GASEOUS OXIDIZER— CHLORINE.
3119B,4 Warning sign for pool without pool lighting. Where
pool lighting fixtures which comply with Section 31 MB are not
provided, a sign with clearly legible letters not less than 4
inches (102 mm) high shall be posted in a prominent place near
each entrance to the pool area. This sign shall state: NO USE
OF POOL ALLOWED AFTER DARK.
3119B.5 Warning sign for a spa pool, A precaution sign with
clearly legible letters shall be posted in a prominent place near
the entrance to a spa pool which shall contain the following
language:
CAUTION
1. Elderly persons, pregnant women, infants and those
with health conditions requiring medical care should
consult with a physician before entering a spa.
2. Unsupervised use by children under the age of 14 is
prohibited,
3. Hot-water immersion while under the influence of al-
cohol, narcotics, drugs or medicines may lead to seri-
ous consequences and is not recommended.
4. Do not use alone.
5. Long exposure may result in nausea, dizziness or
fainting.
31I9B.6 Approved signs. Approved signs shall be maintained
in a legible manner.
2010 CALIFORNIA BUILDING CODE
485
PUBLIC SWIMMING POOLS
';sa5sr
FIGURE 31 B-4— PERPENDICULAR FENCING DIMENSIONS ON SLOPING GROUND
INSIDE
OUTSIDE
FIGURE 31 B-5— EFFECTIVE FENCING HEIGHT
486
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
SECTION 31 20B
INDOOR POOL VENTILATION
A pool located indoors shall be ventilated according to
acceptable engineering principles.
Note: See Section 1202,2 for ventilation requirements for
dressing and toilet rooms.
SECTION 31 21 B
FOUNDATIONS FOR POOL EQUIPMENT
Pool equipment shall be mounted on a portland cement con-
crete or other easily cleanable nonabsorbent floor material.
Floors shall be sloped a minimum of^/4 inch (6,4 mm) per foot
to drains or other drainage disposal methods approved by the
local enforcing agency.
SECTION 3122B
GAS CHLORINATION EQUIPMENT ROOM
Compressed chlorine gas storage containers and associated
chlorinating equipment, when installed indoors, shall be in a
separate room of not less than 1 -hour fire-resistive construc-
tion and shall comply with all of the following sections.
3122BJ Location, The room shall not be located in a base-
ment or below ground.
3122B.2 Entry, The entry door to the room shall open to the
exterior of the building or structure and shall not open directly
toward the pool or pool deck.
3122B3 Ventilation. A mechanically operated exhaust venti-
lation system shall be provided sufficient to produce 60 air
changes per hour. The exhaust ventilation shall be taken at a
point at or near the floor level. The system shall be vented to the
outside air, and at the point of discharge shall be at least 10 feet
(3048 mm) from any openable windows, an adjacent building,
and above the adjoining grade level. Fresh-air intakes directly
communicating with the outdoors shall be located within 6
inches (152 mm) of the ceiling.
RECIRCULATION AND
TREATMENT SYSTEM COMPONENTS
SECTION 3123B
GENERAL REQUIRMENTS
3123BJ System description. Each pool shall be provided with
a separate recirculation and treatment system designed for
continuous recirculation, filtration and disinfection of the pool
water The system shall consist of pumps, filters, chemical feed-
ers, skimmers or perimeter overflow systems, and all valves,
pipes, connections, fittings and appurtenances.
Exception: Pools using fresh water equivalent inflow to the
requirements of Section 3124B.
Notes:
1. Fresh makeup pool water shall conform to the
physical and bacteriological standards of Califor-
nia Code of Regulations, Title 22, Chapter 20,
Section 65531.
2. Two spa pools shall be permitted to share one
recirculation and treatment system, providing the
flow and chlorinationfeed rate to each spa pool is
individually metered and adjustable.
3123B.2 Installation, All recirculation and treatment system
components shall be installed according to this code and in
accordance with the equipment manufacturer's written
instructions.
3123B.3 Accessibility, All filters, valves, pumps, strainers and
equipment requiring adjustment shall be readily accessible for
repair and replacement.
Note: Readily accessible means capable of being reached
quickly for operation, renewal or inspections, without
requiring those to whom ready access is requisite to climb
over or remove obstacles or to resort to portable ladders,
chairs, etc.
SECTION 31 24B
TURNOVER TIME
The recirculation and purification system shall have suffi-
cient capacity to provide a complete turnover of pool water in:
1. One -half hour or less for a spa pool.
2. One hour or less for a wading pool.
3. Two hours or less for a temporary training pool.
4. Six hours or less for all other types of public pools.
SECTION 3125B
RECIRCULATION PIPING SYSTEM AND
COMPONENTS
3125B,1 Line sizes. Piping systems, including all parts and fit-
tings other than inlet devices or venturi throats, shall be sized
so that the flow velocity shall not exceed 10 feet per second
(3.048 m/s) excepting that the flow velocity shall not exceed 8
feet per second (2.438 m/s) in any copper piping or in any
pump suction piping.
3125B.2 Gages for filters. A gage shall be provided on each fil-
ter influent and effluent line. Each gage shall have a scale
range approximately 1 V^ times the maximum anticipated work-
ing pressure and shall be accurate within 2 percent of scale. A
vacuum gage shall be provided for suction-type filters.
3125B.3 Flow meter. The recirculation system shall be pro-
vided with a flow meter, accurate within 10 percent of actual
flow.
3125B.4 Strainers. A hair-and-lint strainer shall be provided
on the suction side of the recirculation pump.
Exception: A pump used with a vacuum filter where the fil-
ter elements are not removed for cleaning.
3 125B.5 Backwash piping. Piping, including necessary valves
conforming to Section 3125B.1, shall be provided for each fil-
ter vessel or element which is of a type of requiring periodic
backwashing.
2010 CALIFORNIA BUILDING CODE
487
PUBLIC SWIMMING POOLS
3125B,6 Valves. Valves shall be accessible for operation and
repair and shall not be located under any required deck area
surrounding a pool Valves^ or other approved means of con-
trol, shall be installed on all recirculation, backwashing and
drain system lines which require shutoff isolation, adjustment
or control of the rate of flow. Each valve shall be identified with
appropriate markings affixed directly to or near the valve.
SECTION 31 26B
RECIRCULATION PUMP CAPACITY
3126B,1 Pumps shall have design capacity at the following
heads:
1. Pressure diatomaceous earth. At least 60 feet (18 288
mm).
2. Vacuum diatomaceous earth. Twenty inches (508 mm)
vacuum on the suction side and 40 feet (12 192 mm) total
head,
3, Rapid sand. At least 45 feet (13 716 mm),
4, High-rate sand. At least 60 feet (18 288 mm).
3126B,2 Pumps with other hydraulic (flow-head) characteris-
tics shall be permitted which comply with the flow capacity in
Section 3124B.
SECTION 31 27B
WATER SUPPLY INLETS
3127B,1 General, The pool shall be supplied with water by
means of a permanently installed pipeline from a public water
supply system holding a permit from the Department of Health
Services or from another approved source.
Exception: The enforcing agency may exempt spa poolSy
temporary pools and pools less than 1,500 gallons (5678 L)
capacity from having to use permanently installed fill lines,
3127B,2 Backflow protection. There shall not be a direct con-
nection between any domestic water supply system and the
pool or its piping system unless protected against backflow in
an approved manner,
3127B,3 Air-gap separation for pool fill inlets. Water supply
inlets to a pool shall be installed not less than 1 inch (25 mm) or
less than two pipe diameters above the overflow rim of the pool.
Over-the-rim spouts shall be installed under a diving board or
shall be properly guarded to prevent tripping.
Exception: Vacuum breakers, or other backflow prevention
devices, may be used instead of air-gap separation. Such
devices shall be installed on the discharge side of the last
inlet valve with the critical level not less than 6 inches (152
mm) above the overflow rim of the swimming pool
SECTION 3128B
FILTERS (ALL TYPES)
3128B,1 General requirements. All filters, regardless of type,
shall be designed and constructed to withstand normal contin-
uous use without deterioration which could affect filter opera-
tion. Each filter shall comply with all of the following provi-
sions:
1, Maintain clean and clear pool water under anticipated
operating conditions,
2, Structural or functional failures shall not permit the pas-
sage ofunfiltered water
3, Filtration surfaces shall be easily disassembled and in-
spected.
4, Filtration surfaces shall be easily restored to the design
capacity.
5, Filter parts shall be capable of resisting electrolytic cor-
rosion (galvanic electric currents) due to the use of dis-
similar metals.
3128B,2 Minimum pressure drop. The maximum pressure
drop of a pressure-type filter, measured from the filter housing
inlet to the filter housing discharge, shall not exceed 3 pounds
per square inch gage (psig) (20.68 kPa gage) when initially
operating at design flow rate,
3128B,3 Installation. Each filter vessel and element shall be
installed, piped and provided with necessary valves so that it
can be isolated from the system for repairs and backwashed
individually,
3128B.4 Air release. When the design of the filter perm its
accumulation of air in the top of the housing or vessel, the filter
vessel shall be equipped with an air-release valve connected at
the top of the housing that will expel air which enters the filter
vessel or tank.
3128B,5 Underdrain system. The underdrain system for sand
filters shall provide uniform distribution and collection of the
flow during filtering and backwashing. The underdrain system
shall be constructed of corrosion-resistant material and shall
be nonclogging,
3128B,6 Freeboard. For sand filters, not less than 10 inches
(254 mm) of freeboard shall be provided between the upper
surface of the filter sand and the lowest portion of the pipes or
drains which serve as overflows during backwashing.
SECTION 31 29B
RAPID SAND PRESSURE FILTERS
3129B,1 Flow rates. The filtration rate shall not exceed 3 gal-
lons per minute (gpm) per square foot (122,24 Umper m^). The
design backwash rate shall not be less than 12 gpm per square
foot (488.96 Um per m^) of filter area.
3129B,2 Filter media. The filter shall contain not less than 20
inches (508 mm) of depth of sand and not less than 10 inches
(254 mm) of filter gravel above the underdrain system.
3129B,2,1 The filter sand shall have an effective particle
size ofO. 3 to 0.5 mm and a uniformity coefficient of not more
than 1.75.
3129B,2,2 The filter gravel shall be graded and placed to
provide uniform flow distribution from the underdrain sys-
tem and to support the bed of filter sand without loss of sand
to the pool or without development of jet streams or chan-
neling in the filtration media.
488
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
3129B3 Coagulant addition. Facilities with dosage-control
features shall be provided for adding coagulating chemicals
ahead of the filter when required by the enforcing agency.
SECTION 31 30B
DIATOMACEOUS EARTH FILTERS
3130B.1 Flow rates. The filtration rate for both pressure and
vacuum-type diatomaceous earth filters shall not exceed 2 gpm
per square foot (81.49 L/m per m^) excepting that filters
designed for continuous feeding of filter aid shall not exceed 2
V2 gpm per square foot (101.87 L/m per m^j.
Note: See also Section 3128Bfor other requirements.
3130B.2 Precoatng. Provisions shall be made for precoating
with diatomaceous earth filter aid. Continuous feeding of filter
aid shall be required in a pool with a water surface area 2,000
square feet (186 m^) or more, and the continuous feeding
equipment shall be capable of feeding not less than 0.1 pound
(0.045 kg) per 24 hours per square foot (0.093 m^) of filter
area.
SECTION 3131 B
HIGH-RATE SAND FILTERS
3131B.1 Permissible use. Sand filters operating at filtration
rates higher than the maximum rate specified in Section 3129B
shall be permitted by the enforcing agency under the condi-
tions as set forth in Section 3105B.
3131B,2 Design and operating requirements, A sand filter
permitted under Sections 3105B.1, 3105B.2 and3105B.3 shall
comply with the following requirements instead of the require-
ments contained in Section 3129B.
1. The filter shall contain not less than 12 inches (305 mm)
of depth of filter sand.
2. The filter sand shall not have an ejfective particle size
greather than 0.45 mm and a uniformity coefficient not
greater than 1.50.
3. The design backwash rate shall not be less than 15 gpm
per square foot (611.21 L/m per m^) of filter area.
4. The filter bed shall not show any signs of migration or
vary more than 1 inch (25 mm) on the surface after 15 min-
utes of backwashing, followed by 15 minutes of filtration.
Note: See Section 3128Bfor other requirements.
SECTION 31 32B
CHEMICAL FEEDERS
All chemical feeders, including disinfectant feeders, and the
auxiliary components shall comply with all of the provisions of
this section.
Note: Chemical feeders include those used for solutions,
slurries or solids and also include auxiliary parts such as
pumps, strainers, tubing connections, tanks, injection fit-
tings and other required components.
3132B,1 General design requirements. Chemical feeder
equipment shall comply with all of the following:
1. Equipment shall be capable of being easily disassembled
for cleaning and repair.
2. Equipment shall be constructed of corrosion-resistant
materials.
3. Equipment shall be constructed to permit repeated ad-
justments without loss of output rate accuracy if
equipped with an adjustable output rate device.
4. Equipment shall be constructed to minimize a stoppage
from chemicals intended to be used therein or from for-
eign materials that may be contained in said chemicals.
3132B.2 Piping. Piping used for the chemical feeder and its
auxiliary equipment shall be resistant to the chemical and ero-
sion action of the chemicals intended to be used therein and
shall be installed to permit cleaning or otherwise to prevent
clogging of the parts with chemicals.
3132B.3 Installation. The feeder and its auxiliary equipment
shall be constructed and installed to prevent uncontrolled dis-
charge or siphonage of chemicals and fumes directly into the
pool, its recirculating system or the pool area.
SECTION 31 33B
DISINFECTANT FEEDERS
Disinfectant feeders shall comply with the provisions con-
tained in this section in addition to the provisions contained in
Section 3132B.
3133B.1 Minimum capacity. The disinfectant feeder shall be
capable of supplying not less than the equivalent of 3 pounds (1
kg) of chlorine per day (PPD)per 10,000 gallons (37 850 L) of
pool water capacity.
Exception: A feeder of lesser capacity shall be permitted
when it can be demonstrated to the enforcing agency that
the lesser capacity feeder can comply with the disinfection
requirements of Section 65529, Title 22, Chapter 20, Cali-
fornia Code of Regulations.
3133B.2 Rate of flow adjustment. Each feeder shall have a
graduated and clearly marked rate of flow adjustment feature
capable of providing disinfectant flows from 25 percent to 100
percent of rated capacity. The graduated markings shall be
accurate within 10 percent of the flow rate at any setting.
3133B.3 Compressed chlorine gas disinfection equipment
Compressed chlorine gas disinfectant equipment shall comply
with the provisions contained in this section in addition to the
provisions contained in Sections 3133B.1 and 3133B.2.
Note: See Section 3122B for special construction require-
ments of a room containing compressed chlorine gas disin-
fectant equipment.
3133B.3.1 Chlorine containers. Each chlorine gas con-
tainer or cylinder shall be firmly secured to prevent acci-
dental movement. A precaution cap shall be provided in
place at all times when the cylinder is not connected to the
chlorinatoK
2010 CALIFORNIA BUILDING CODE
489
PUBLIC SWIMMING POOLS
3133BJ.2 Container scale. A means of weighing chlorine
containers shall be provided in the gas chlorinator room,
31338.3,3 Chlorine feeding device. In addition to the
requirements contained in Section 3133B.1, the chlorine
feeding device shall be capable of delivering chlorine in
aqueous solution at maximum design rate. The device shall
not allow the backflow of water into the chlorine solution
container. The device shall not allow the release of chlorine
gas to the atmosphere under normal operating conditions.
The devices shall be designed and installed to conduct chlo-
rine gas leaks to the outdoors during an accident or an
interruption of the water supply.
3133B3.4 Piping. Piping carrying chlorine gas under
pressure shall not be located outside the chlorination equip-
ment room.
SECTION 3134B
POOL FITTINGS
The pool shall be equipped with one or more skimming meth-
ods which, when combined, shall be capable of continually
withdrawing not less than 75 percent of the required circula-
tion capacity, to provide continuous skimming of the water sur-
face and to provide an overflow drainage system.
3134B.1 Surface skimmers. Each surface skimmer shall com-
ply with all of the following provisions:
1. The skimmer shall be of the built-in type, recessed into
the pool wall.
2. Each skimmer shall be individually adjustable for the
rate of flow with either an external or internal device.
3. The skimmer weir shall automatically adjust to varia-
tions in the pool water level over a range of not less than
4 inches (102 mm).
4. The skimmer shall be provided with an air-lock protec-
tive device which shall not permit leakage of air into the
recirculation suction piping system. This device shall not
leak more than 3 gpm (11.356 L/m) of water during nor-
mal operations.
5. Each skimmer shall be provided with a removable and
cleanable screen or basket to trap large solids.
6. There shall not be less than one skimmer for each 500
square feet (46.45 m^) of pool water surface area, or
fractional part thereof
7. The skimmer shall be constructed with suitable materials
and methods to withstand anticipated use conditions.
8. Each skimmer shall be located in relation to pool inlets to
aid recirculation and skimming
Exception: Skimmers shall not be used as the required over-
flow devices on a pool with a water surface area over 5,000
square feet (464.52 m^).
3134B.2 Perimeter overflow systems. A perimeter overflow
system shall comply with all of the following provisions:
1. Location. The overflow system shall be built into the
walls and extend completely around the pool except
where steps require interruption.
2. Channel detail. The overflow channel shall not be less
than 3 inches (76 mm) deep, the section shall not diverge
with depth and the width of the bottom shall not be less
than 3 inches (76 mm). The opening beneath the coping
into the overflow system shall be a minimum of 4 inches
(102 mm) beneath of the coping in any direction mea-
sured radially from the inner edge of the overflow chan-
nel lip.
3. Channel lip. The overflow channel lip shall not be more
than 12 inches (305 mm) below the level of the deck. The
lip edge shall be rounded and shall not be thicker than 2
V2 inches (64 mm) or thinner then 1 inch (25 mm) from
the top 2 inches (51 mm).
4. Channel covering. Covered overflow channels shall be
permitted, providing bathers cannot enter it or get their
arms or legs caught in the cover.
5. Channel outlets. Overflow channel outlets shall not be
less than 2^/2 inches (64 mm) in diameter spaced not
more than 15 feet (4572 mm) apart and the channel bot-
tom slope to the drain shall not be less than V4 inch (6.4
mm) per foot.
Exception: Other drain spacing or channel bottom
slope shall be permitted if hydraulically designed in
accordance with acceptable engineering principles.
6. Channel outlet covers. Overflow channel outlets shall
be provided with a clear opening area in the grating not
less than 1.5 times the cross-sectional area of the outlet
required in Section 3134B.
7. Overflow drain piping. Overflow drain piping shall pro-
vide drainage of the overflow system, shall carry over-
flow water to a surge storage chamber and shall
establish hydraulic equilibrium in the pool and return to
skimming within 10 minutes after being flooded by a sud-
den large use of the pool by bathers.
8. Surge storage capacity. A perimeter overflow system
shall be provided with a minimum surge storage of not
less than 1 gallon per square foot (40. 75 Um^) of pool
water surface area. Surge storage shall be permitted in
the perimeter overflow channel, the overflow water drain
piping returning to the surge chamber and in the surge
chamber.
9. Surge flow control. Automatic makeup (fresh) water-flow
controls with a manual override provision shall be pro-
vided to maintain the proper operating pool water level.
3134B.3 Outlets. Each pool shall be provided with a bottom
drain and outlets through which circulation shall take place
and by which the pool can be emptied. The bottom drain and
recirculation outlets shall be covered with grates or other pro-
tective devices which shall be removable only with tools. Slots
or openings in grates or covers shall not exceed % i^ch (12.7
mm) in the smaller dimension and shall be of such area, shape
and arrangement to prevent physical entrapment or a suction
hazard to bathers.
Exception: Recirculation outlets for a spa pool shall be
either a safety type which cannot be completely covered by
any part of the body, or shall be installed in duplicate so as
to prevent a suction hazard to bathers.
490
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
3134B.4 Hydrostatic devices. In areas of anticipated high
groundwater table, an approved hydrostatic relief device shall
he installed,
3134B.5 Inlet Fittings, Each pool shall be provided with not
less than two recirculation inlets for the first 1 0,000- gallon (37
850 L) capacity and one additional inlet for each additional
10,000~gallon (37 850 L) capacity, or fractional part thereof
Exception: A spa pool shall be provided with not less than
one inlet.
3134B,5.1 Construction, Inlet fittings shall not protrude
greater than V/4 inches (32 mm) into the pool and shall be
shaped, rounded and smooth.
31348,5,2 Inlet fittings shall be located greater than 18
inches (457 mm) below the waterline, except for the spa
pool or wading pool One floor inlet shall be provided for
each 10,000 gallons (37 850 L) of pool capacity for a pool
which exceeds 40 feet (12 192 mm) in width. Inlet fittings
shall be separated by at least 10 feet (3048 mm) and shall be
located to ensure uniform circulation.
3134B.5.3 Adjustment, Provisions shall be made for
adjusting the volume of flow through each inlet. Wall inlets
shall be capable of adjusting the direction of flow and to
produce sufficient velocity to impart a substantial circula-
tory movement to the pool water
SECTION 3135B
SPA POOL SPECIAL REQUIREMENTS
3135B,1 Aeration system. A spa pool aeration and/or jet sys-
tem shall be completely separate from its filtration system and
shall not be interconnected with any nonspa pool.
3135B.2 Maximum operating temperature. The maximum
allowable water temperature shall be 104°F (57.8'^C)foraspa
pool.
well, OK when approved, such water may be disposed of by
surface or subsurface irrigation.
3137B.1,2 Diatomaceous earth filters. The backwash
waste water from a diatomaceous earth filter shall dis-
charge into a receiving chamber installed to collect the
waste diatomaceous earth mixture, or, when approved, such
waste shall be permitted to be disposed of by other means
such as to a sanitary sewer
3137B.L3 Piping, Sumps and drain piping shall have suffi-
cient capacity to receive pool system backwash without
overflow of the sump receiver
3 137 B, 1,4 Visual indicator, A sight glass shall be installed
on the waste water discharge line from a filter
Exception: The sight glass shall not be required when an
air-gap connection from the filter vessel to a sewer or
other drainage system is clearly visible to the operator
during actual backwash operation.
3137B,2 Prohibited connection. No direct connection of the
pool or its recirculation system shall be permitted with a sani-
tary sewer, storm drain or drainage system. When permitted by
local regulations, discharge to a sanitary sewer shall be
through an air-gap-type separation.
SECTION 31 38B
Reserved
SECTION 3139B
Reserved
SECTION 3140B
Reserved
SECTION 31368
CLEANING SYSTEMS
A built-in or portable-type vacuum cleaning system shall be
provided which is capable of removing sediment from all parts
of the pool floor When jet-type units are used, they shall be pro-
vided with approved-type backfiow protection for the water
system.
SECTION 3141 B
Reserved
SECTION 31 42B
Reserved
SECTION 31 37B
WASTE WATER DISPOSAL
3137B,1 General requirements. Material cleaned from filters,
waste water from temporary training pool showers and back-
wash water from any pool system shall be disposed of in a man-
ner which will not create a (public) nuisance.
3137B.1J Sand filters. In accordance with applicable
local regulations, the backlash water from a sand filter
shall be disposed of to a storm drain or sewer system, dry
SECTION 31 43B
Reserved
SECTION 31 44B
Reserved
SECTION 3145B
Reserved
2010 CALIFORNIA BUILDING CODE
491
PUBLIC SWIMMING POOLS
SECTION 3146B
Reserved
SECTION 3147B
Reserved
SECTION 3148B
Reserved
SECTION 3149B
Reserved
SECTION 3150B
Reserved
SECTION 31 51 B
Reserved
SECTION 3152B
Reserved
SECTION 3153B
Reserved
SECTION 3154B
Reserved
SECTION 31 55B
Reserved
SECTION 3156B
Reserved
SECTION 31 57B
Reserved
Division II— PUBLIC SWIMMING POOLS
Note: These building standards are in statute but have not been
adopted through the regulatory process. Enforcement of these
standards set forth in this section does not depend upon adop-
tion of regulations; therefore^ enforcement agencies shall
enforce the standards pursuant to the timeline set forth in this
section prior to adoption of related regulations.
SECTION 31 60B
1. "Public swimming pool/' as used in this section, means
any swimming pool operated for the use of the general
public with or without charge, or for the use of the mem-
bers and guests of a private club, including any swim-
ming pool located on the grounds of a hotel, motel, inn,
an apartment complex or any residential setting other
than a single-family home. For purposes of this section,
"public swimming pool" shall not include a swimming
pool located on the grounds of a private single-family
home, or a swimming pool owned or operated by the
state or any local governmental entity as set forth in Sec-
tion 116049 of the Health and Safety Code.
2. All dry-niche light fixtures, and all underwater wet-niche
light fixtures operating at more than 15 volts in public
swimming pools, as defined in this section, shall be pro-
tected by a ground fault circuit interrupter in the branch
circuit, and all light fixtures in public swimming pools
shall have encapsulated terminals.
3. Any public swimming pool that does not meet the re-
quirements specified in Item 2 by January 1, 1998, shall
be retrofitted to comply with these requirements by July
1, 1998.
4. The ground-fault circuit interrupter required pursuant to
this section shall comply with Underwriter's Laboratory
standards.
5. The owner or operator of a public swimming pool shall
have its public swimming pool inspected by a qualified
inspector on or before September 1, 1998, to determine
compliance with this section.
6. All electrical work required for compliance with this sec-
tion shall be performed by an electrician licensed pursu-
ant to Chapter 9 (commencing with Section 7000) of
Division 3 of the Business and Professions Code.
SECTION 3158B
Reserved
SECTION 3159B
Reserved
SECTION 31 61 B
L "Public wading pool " means a pool that meets all of the
following criteria:
1.1. It has a maximum water depth not exceeding 18
inches (457 mm).
492
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
1.2. It is a pool other than a pool that is located on the
premises of a one-unit or two-unit residence, in-
tended solely for the use of the residents or
guests.
2. ''Public wading pool" includes, but is not limited to, a
pool owned or operated by private persons or agencies,
or by state or local governmental agencies.
3. "Public wading pool" includes, but is not limited to, a
pool located in an apartment house, hotel or similar set-
ting that is intended for the use of residents or guests.
4. "Alteration" means any of the following:
4.1. To change, modify or rearrange the structural
parts or the design.
4.2. To enlarge.
4.3. To move the location of.
4.4. To install a new water circulation system.
4.5. To make any repairs costing fifty dollars ($50) or
more to an existing circulation system.
5. A public wading pool shall have at least two circulation
drains per pump that are hydraulically balanced and
symmetrically plumbed through one or more T fittings,
and are separated by a distance of at least 3 feet (914
mm) in any dimension between drains.
6. All public wading pool main drain suction outlets that
are under 12 inches (305 mm) across shall be covered
with antivortex grates or similar protective devices. All
main drain suction outlets shall be covered with grates or
antivortex plates that cannot be removed except with the
use of tools. Slots or openings in the grates or similar
protective devices shall be of a shape, area and arrange-
ment that would prevent physical entrapment and would
not pose any suction hazard to bathers.
7. The maximum velocity in the pump suction hydraulic
system shall not exceed 6 feet per second (1.8 m/s) when
100 percent of the pump's flow comes from the main
drain system and any main drain suction fitting in the
system is completely blocked.
8. On and after January 1, 1 998, all newly constructed pub-
lic wading pools shall be constructed in compliance with
this section.
9. Commencing January 1, 1998, whenever a construction
permit is issued for alteration of an existing public wad-
ing pool, it shall be retrofitted so as to be in compliance
with this section.
lO.By January 1, 2000, every public wading pool, regard-
less of the date of original construction, shall be retrofit-
ted to comply with this section.
[SB 873, Statues of 1997, C.913]
SECTION 3162B
ANTI-ENTRAPMENT DEVICES AND SYSTEMS
1 . The legislature finds and declares that the public health
interest requires that there be uniform statewide health
and safety standards for public swimming pools to pre-
vent physical entrapment and serious injury to children
and adults. It is the intent of the legislature to occupy
the whole field of health and safety standards for public
swimming pools and the requirements established in
this article and the regulations adopted pursuant to this
article shall be exclusive to all local health and safety
standards related to public swimming pools.
2. As used in this section, the following words have the fol-
lowing meanings:
a. ^^ASME/ANSI performance standard^' means a
standard that is accredited by the American
National Standards Institute and published by the
American Society of Mechanical Engineers.
b. ASTM performance standard means a standard
that is developed and published by ASTM Interna-
tional.
c. Main drain means a submerged suction outlet typ-
ically located at the bottom of a swimming pool
that conducts water to a recirculating pump.
d. Public swimming pool means an outdoor or
indoor structure, whether in-ground or above-
ground, intended for swimming of recreational
bathing, including a swimming pool, hot tub, spa,
or nonportable wading pool, that is any of the fol-
lowing:
L Open to the public generally, whether for a
fee or free of charge.
a. Open exclusively to members of an organi-
zation and their guests, residents of a
multiunit apartment building, apartment
complex, residential real estate develop-
ment, or other multifamily residential
area, or patrons of a hotel or other public
accommodations facility.
Hi. Located on the premises of an athletic
club, or public or private school.
e. Qualified individual means a contractor who
holds a current valid license issued by the State of
California or a professional engineer licensed in
the State of California who has experience work-
ing on public swimming pools.
f Safety vacuum release system means a vacuum
release system that ceases operation of the pump,
reverses the circulation flow, or otherwise pro-
vides a vacuum release at a suction outlet when a
blockage is detected.
g. Skimmer equalizer line means a suction outlet
located below the water line and connected to the
body of a skimmer that prevents are from being
drawn into the pump if the water level drops below
the skimmer weir. However, a skimmer equalizer
line is not a main drain.
h. Unblockable drain means a drain of any size and
shape that a human body cannot sufficiently block
to create a suction entrapment hazard.
2010 CALIFORNIA BUILDING CODE
493
PUBUC SWIMMING POOLS
3. Subject to Subdivision (4), an ASME/ANSI or ASTM
performance standard relating to anti-entrapment de-
vices or systems or an amendment or successor to, or
later published edition of an ASME/ANSI or ASTM per-
formance standard relating to anti-entrapment devices
or systems shall become the applicable standard in
California 90 days after publication by ASME/ANSI or
ASTM, respectively, provided that the performance
standard or amendment or successor to, or later pub-
lished edition is approved by the department within 90
days of the publication of the performance standard by
ASME/ANSI or ASTM, respectively. Notwithstanding
any other law, the department may implement, interpret
or make specific the provisions of this section by means
of a policy letter or similar instruction and this action
by the department shall not be subject to the
rulemaking requirements of the Administrative Proce-
dures Act (Chapter 3,5 (commencing with Section
1 1 340) of Part I of Division 3 of Title 2 of the Govern-
ment Code).
4. Subject to Subdivision (7), every public swimming pool
shall be equipped with anti-entrapment devices or sys-
tems that comply with ASME/ANSI performance stan-
dard Al 12.19.8, as in effect December 31, 2009, or any
applicable ASME/ANSI performance standard that has
been adopted by the department pursuant to Subdivi-
sion (3).
5. Subject to Subdivisions (6) and (7), every public swim-
ming pool with a single main drain that is not an
unblockable drain shall be equipped with at least one
or more of the following devices or systems that are de-
signed to prevent physical entrapment by pool drain:
a. A safety vacuum release system that has been
tested by a department-approved independent
third party and found to conform to ASME/ANSI
performance standard Al 12.19.17, as in effect on
December 31, 2009, or any applicable
ASME/ANSI performance standard that has been
approved by the department pursuant to Subdivi-
sion (3) or ASTM performance standard F23 87, as
in effect on December 31, 2009, or any applicable
ASTM performance standard that has been
approved by the department pursuant to Subdivi-
sion (3).
b. A suction-limiting vent system with a tamper- resis-
tant atmospheric opening, provided that it con-
forms to any applicable ASME/ANSI or ASTM
performance standard that has been approved by
the department pursuant to Subdivision (3),
c. A gravity drainage system that utilizes a collector
tank, provided that it conforms to any applicable
ASME/ANSI or ASTM performance standard that
has been adopted by the pursuant to Subdivision
(3).
d. An automatic pump shut-off system tested by a
department-approved independent third party and
found to conform to any applicable ASME/ANSI or
ASTM performance standard that has been
adopted by the department pursuant to Subdivi-
sion (3).
e. Any other system that is deemed, in accordance
with federal law, to be equally effective as, or more
effective than, the systems described in para-
graphs (a) and (d), inclusive, at preventing or
eliminating the risk of injury or death associated
with pool drainage systems.
6. Every public swimming pool constructed on or after
January 1, 2010, shall have at least two main drains
per pump that are hydraulically balanced and symmet-
rically plumbed through one or more "T" fittings, and
are separated by a distance of at least three feet in any
dimension between the drains. A public swimming pool
constructed on or after January 1, 2010, that meets the
requirements of this subdivision, shall be exempt from
the requirements of Subdivision (5).
7. A public swimming pool constructed prior to January
1, 2010, shall be retrofitted to comply with Subdivisions
(4) and (5) by no later than July 1, 2010, except that no
further retrofitting is required for a public swimming
pool that completed a retrofit between December 19,
2007, and January 1, 2010, that complied with the Vir-
ginia Graeme Baker Pool and Spa Safety Act (15 U. S. C.
Sec, 8001 et seq.) as in effect on the date of issue of the
construction permit, or for a nonportable wading pool
that completed a retrofit prior to January 1, 2010, that
complied with state law on the date of issue of the con-
struction permit. A public swimming pool owner who
meets the exception described in this subdivision shall
do one of the following prior to September 30, 2010:
a. File the form issued by the department pursuant to
Subdivision (8), as otherwise provided in Subdivi-
sion (9).
b. File a signed statement attesting that the required
work has been completed.
c. Provide a document providing the name and
license number of the qualified individual who
completed the required work.
d. Provide either a copy of the final building permit,
if required by the local agency, or a copy of one of
the following documents if no permit was
required:
i. A document that describes the modifica-
tion in a manner that provides sufficient
information to document the work that has
been done to comply with federal law.
a. A copy of the final paid invoice. The
amount paid for the services may be omit-
ted or redacted from the final invoice prior
to submission.
8. Prior to March 31, 2010, the department shall issue a
form for use by the owner of a public swimming pool to
494
2010 CALIFORNIA BUILDING CODE
PUBLIC SWIMMING POOLS
indicate compliance with this section. The department
shall consult with county health officers and directors
of departments of environmental health in developing
the form and shall post the form on the department's
internet website. The form shall be completed by the
owner of a public swimming pool prior to filling the
form with the appropriate city^ county, or city and
county department of environmental health. The form
shall include, but not be limited to, the following infor-
mation:
a. A statement of whether the pool operates with a
single or split main drain.
b. Identification of the type of anti-entrapment
devices or systems that have been installed pursu-
ant to Subdivision (4) and the date or dates of
installation.
c. Identification of the type of devices or systems
designed to prevent physical entrapment that have
been installed pursuant to Subdivision (5) in a
public swimming pool with a single main drain
that is not an unblockable drain and the date or
dates of the installation of the reason why the
requirement is not applicable.
d. A signature and license number of a qualified indi-
vidual who certifies that the factual information
provided on the form in response to paragraphs
(a) to (c), inclusive, is true to the best of his or her
knowledge.
9. A qualified individual who improperly certifies infor-
mation pursuant to Paragraph (d) of Subdivision (8)
shall be subject to potential disciplinary action at the
discretion of the licensing authority.
10. Except as provided in Subdivision (7), each public
swimming pool owner shall file a completed copy of the
form issued by the department pursuant to this section
with the city, county, or city and county department of
environmental health in the city, county, or city and
county in which the swimming pool is located. The form
shall be filed within 30 days following the completion of
the swimming pool construction of installation re-
quired pursuant to this section or, if the construction or
installation is completed prior to the date that the de-
partment issues the form pursuant to this section,
within 30 days of the date that the department issues the
form. The public swimming pool owner or operator
shall not make a false statement, representation, certifi-
cation, record, report, or otherwise falsify information
that he or she is required to file or maintain pursuant to
this section.
11. In enforcing this section, health officers and directors
of city, county, or city and county departments of envi-
ronmental health shall consider documentation filed on
or with the form issued pursuant to this section by the
owner of a public swimming pool as evidence of com-
pliance with this section. A city, county, or city and
county department of environmental health may verify
the accuracy of the information filed on or with the
form.
12. To the extent that the requirements for public wading
pools imposed by Section 116064 conflict with this sec-
tion, the requirements of this section shall prevail.
a. Until January 1, 2014, the department may assess
an annual fee on the owners of each public swim-
ming pool, to be collected by the applicable local
health department, in an amount not to exceed the
amount necessary to defray the department's costs
of carrying out its duties under Section 116064.1
and this, but in no case shall this fee exceed six dol-
lars ($6).
b. The local health department may retain a portion
of the fee collected pursuant to Paragraph (a) in
an amount necessary to cover the administrative
costs of collecting the fee, but in no case to exceed
one dollar ($1).
c. The local health department shall bill the owner of
each public swimming pool in its jurisdiction for
the amount of the state fee. The local health
department shall transmit the collected state fee to
the controller for deposit into the Recreational
Health Fund, which is hereby created in the State
Treasury. The local health department shall not be
required to take action to collect an unpaid state
fee, but shall submit to the department, every six
months, a list containing the name and address of
the owner of each public swimming pool who has
failed to pay the state fee for more than 90 days
after the date that the bill was provided to the
owner of the public swimming pool
d. Owners that are exempt from local swimming pool
permit fees shall also be exempt from the fees
imposed pursuant to this subdivision.
e. Except as provided in Paragraph (b), all moneys
collected by the department pursuant to this sec-
tion be deposited into the Recreational Health
Fund. Notwithstanding Section 16305.7 of the
Government Code, interest and dividends on mon-
eys in the Recreational Health Fund shall also be
deposited in the fund. Moneys in the fund shall,
upon appropriation by the legislature, be avail-
able to the department for carrying out its duties
under Section 116064.1 and this section and shall
not be redirected for any other purpose.
2010 CALIFORNIA BUILDING CODE
495
496 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 31 C - RADIATION
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
497
498 201 CALIFORNIA BUILDING CODE
CHAPTER 31 C[DHS]
RADIATION
SECTION 3101 C
SCOPE
For the purpose of this chapter, the following terms shall
have the meaning indicated:
PRIMARY PROTECTIVE BARRIER is a barrier to attenu-
ate the useful beam.
SECONDARY PROTECTIVE BARRIER is a barrier to
attenuate stray radiation.
STRAY RADIATION is radiation not serving any useful pur-
pose, which includes leakage and scattered radiation.
USEFUL BEAM is the radiation which passes through the
window, aperture, cone or other collimating device of the tube
housing.
SECTION 31 02C
RADIATION SHIELDING BARRIERS
All radiation shielding barriers in rooms and enclosures
housing machines shall meet the requirements of Section
12-31C-101, Chapter 12-3 IC, Part 12, Calif omia Referenced
Standards Code. The Department of Health Services is the only
agency that may grant a variance or exception to these stan-
dards.
SECTION 31 03C
MEDICAL RADIOGRAPHIC AND
PHOTOFLUOROGRAPHIC INSTALLATIONS
3103CJ Operator station. The operator's station at the con-
trol shall be behind a protective barrier either in a separate
room, in a protected booth or behind a shield which will inter-
cept the useful beam and any radiation which has been scat-
tered only once.
3103C2 Patient observation and communication. Provision
shall be made for the operator to observe and communicate
with the patient without leaving the shielded position at the
control panel. When an observation window is used, it must
provide radiation attenuation equal to that required in the sur-
rounding barrier.
2. The control station shall be provided with a window hav-
ing radiation attenuation equal to that required by the
adjacent barrier, or a mirror system, or a closed-circuit
television viewing screen. The patient area must be visi-
ble to the operator without having to leave the protected
area during exposure.
3104C3 Equipment operating above 150 kVp, Equipment
operating above 150 kVp shall conform to the following:
1. The treatment room shall be provided with interlocks so
that when any door of the treatment room is opened, ei-
ther the machine will shut off automatically or the radia-
tion level within the room will be reduced to an average
of not more than 2 milliroentgens per hour and a maxi-
mum of 10 milliroentgens per hour at a distance of one
meter in any direction from the target. After such shutoff
or reduction in output, it shall be possible to restore the
machine to full operation only from the control panel.
2, The control station shall be within a protective booth or
in an adjacent room.
3104C.4 A minimum of one door shall be provided with an aux-
iliary means for being opened in case of power failure or
mechanical breakdown, where large power-driven doors offer
the only access to the room.
3104C,5 A flashing red warning signal light energized only
when the useful beam is on shall be located adjacent to the
entrance(s) to a therapy room with equipment capable of oper-
ating above 500 kVp.
SECTION 3104C
MEDICAL THERAPEUTIC X-RAY INSTALLATIONS
3104C1 General All wall, floor and ceiling areas that can be
struck by the useful beam, plus a border of 1 foot (305 mm),
shall be provided with primary protective barriers.
3104C,2 Equipment operating above 50 kVp, Equipment
operating above 50 kVp shall conform with the following. -
1. The control station shielding shall either be an integral
part of the building or anchored to the building.
2010 CALIFORNIA BUILDING CODE
499
500 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 31 D - FOOD ESTABLISHMENTS
Adopting agency
BBC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
601
502 201 CALIFORNIA BUILDING CODE
CHAPTER 31 D[DPH]
FOOD ESTABLISHMENTS
SECTION 3101 D
SCOPE
The provisions of this chapter shall apply to the construction
of commissaries serving mobile food preparation units.
SECTION 3102D
DEFINITIONS
For the purpose of this chapter, the following term shall have
the meaning indicated:
COMMISSARIES SERVING MOBILE FOOD PREPA^
RATION UNITS are food establishments in which food, con-
tainers, equipment or supplies are stored or handled for use in
vehicles, mobile food preparation units, food carts or vending
machines.
SECTION 3103D
BUILDING AND STRUCTURES
3103D,I Light. Ten foot candles (107.6 lux) of uniformly dis-
tributed light as measured 30 inches (762 mm) above the floor
shall be provided in all rooms and areas in commissaries serv-
ing mobile food preparation units.
201 CALIFORNIA BUILDING CODE 503
504 201 CALIFORNIA BUILDING CODE
CHAPTER 31 E
RESERVED
2010 CALIFORNIA BUILDING CODE 505
506 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 31 F - MARINE OIL TERMINALS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
507
508 201 CALIFORNIA BUILDING CODE
CHAPTER 31 F[SLC]
MARINE OIL TERMINALS
Division I
SECTION 31 01 F[SLC]
INTRODUCTiON
3 101 El General The Lempert-Keene-Seastrand oil spill pre-
vention and response act of 1990 (act), as amended, authorized
the California State Lands Commission (SLC) to regulate
marine oil terminals (MOTs) in order to protect public health,
safety and the environment. The authority for this regulation is
contained in Sections 8755 and 8756 of the California Public
Resources Code, This act defines ''oil " as any kind of petro-
leum, liquid hydrocarbons, or petroleum products or any frac-
tion or residues thereof, including but not limited to, crude oil,
bunker fuel, gasoline, dieselfuel, aviation fuel, oil sludge, oil
refuse, oil mixed with waste, and liquid distillates from unpro-
cessed natural gas. The provisions of this chapter regulate
marine oil terminals as defined under this act.
3101F.2 Purpose, The purpose of this code is to establish mini-
mum engineering, inspection and maintenance criteria for
MOTs in order to prevent oil spills and to protect public health,
safety and the environment. This code does not, in general,
address operational requirements. Relevant provisions from
existing codes, industry standards, recommended practices,
regulations and guidelines have been incorporated directly or
through reference, as part of this code.
Where there are differing requirements between this code
and/or references cited herein, the choice of application shall
be subject to approval of the Marine Facilities Division (Divi-
sion) of the SLC.
In special circumstances where certain requirements of these
standards cannot be met, alternatives that provide an equal or
better protection of the public health, safety and the environ-
ment shall be subject to Division approval.
3 101F3 Applicability, The provisions of this chapter are appli-
cable to the evaluation of existing MOTs and design of new
MOTs in California. Each provision is classified as New (N),
Existing (E), or Both (N/E) and shall be applied accordingly. If
no classification is indicated, the classification shall be consid-
ered to be (N/E).
Existing (E) requirements apply to MOTs that are in opera-
tion on the date this code is adopted. For these MOTs, equiva-
lent or in-kind replacement of existing equipment, short
pipeline sections, or minor modification of existing compo-
nents shall also be subject to the existing (E) requirements.
New (N) requirements apply to:
1. A MOT or berthing system (Subsection 3I02F.1.3) that
commences or recommences operation with a new or
modified operations manual after adoption of this code.
2. Addition of new structural components or systems at an
existing MOT that are structurally independent of exist-
ing components or systems.
3. Addition of new (nonreplacement) equipment, piping,
pipelines, components or systems to an existing MOT.
4. Major repairs or substantially modified in-place systems.
5. Any associated major installations or modifications.
3101F,4 Overview, This Code ensures that a MOT can be safely
operated within its inherent structural and equipment-related
constraints.
Section 3102F defines minimum requirements for audit,
inspection and evaluation of the structural, electrical and
mechanical systems on a prescribed periodic basis, or follow-
ing a significant damage-causing event.
Section 3103F , 3104F and 3 I07F provide criteria for structural
loading, deformation and performance-based evaluation consider-
ing earthquake, wind, wave, current, seiche and tsunami effects.
Section 3 1 05 F provides requirements for the safe mooring and
berthing of tank vessels and barges.
Section 3I06F describes requirements for geotechnical haz-
ards and foundation analyses, including consideration of slope
stability and soil failure.
Section 3 1 08F provides requirements for fire prevention, detec-
tion and suppression including appropriate water and foam vol-
umes.
Sections 3I09F through 3 1 01 IF provide requirements for pip-
ing, mechanical and electrical equipment.
English units are prescribed herein; however, many of the units
in the references are in System International (SI).
3101F,5 Risk reduction strategies. Risk reduction strategies,
such as pipeline segmentation devices, system flexibility and
spill containment devices may be used to reduce the size of a
potential oil spill. Such strategies may reduce the MOT risk
classification as determined from Table 3IF-4-I.
3101F,6 Review requirements,
3101F,6,1 Quality assurance. All audits, inspections, engi-
neering analyses or design shall be reviewed by a profes-
sional having similar or higher qualifications as the person
who performed the work, to ensure quality assurance. This
review may be performed in-house.
Peer review is required for nonlinear dynamic structural
analyses and alternative lateral force procedures not pre-
scribed herein. The peer review may be from an independent
internal or external source. The peer reviewer shall be a
California registered civil or structural engineer
3101F,6,2 Division review. The following will be subject to
review and approval by the Division or its designated repre-
sentative(s)for compliance with this code:
1. Any audit, inspection, analysis or evaluation of existing
MOTs.
2. Any significant change, modification or re-design of a
structural, mooring, fire, piping/pipelines, mechanical or
electrical system at an existing MOT, prior to use or reuse.
3. Engineering analysis and design for any new MOT
prior to construction.
4. Construction inspection team and the construction
inspection report(s).
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE
509
MARINE OIL TERMINALS
Division 2
SECTION 31 02F
AUDIT AND INSPECTION
3102E1 General
3102EL1 Purpose, Section 3102F defines minimum require-
ments for audit, inspection, and evaluation of the structural,
mechanical and electrical components and systems,
3102F.L2 Audit and inspections types. The audit and
inspections described in this Chapter (3 IF) and 2 CCR
2320 (a) and (b) [2,1] are:
L Annual inspection
2, Audit
3, Post- event inspection
Each has a distinct purpose and is conducted either at a
defined interval (see Tables 31F-2-1 and 31F-2-2), as a result
of a potentially damaging event or a significant change in
operations. In the time between audits and inspections, oper-
ators are expected to conduct periodic walk-down examina-
tions of the MOT to detect potentially unsafe conditions.
TABLE 31 F-2'1
INITIAL AUDIT REPORT SUBMISSION DEADLINE
FOR EXISTING BERTHING SYSTEMS
RISK CLASSIFICA TION'
SUBMISSION DEADLINE
Hi^h
30 Months
Medium
48 Months
Low
60 Months
> ;. As defined in Table 31F-4-L
2. From the effective date of this Chapter (31F).
3102FJ,3 Berthing systems. For the purpose of assigning
structural ratings and documenting the condition of
mechanical and electrical systems, an MOT shall be divided
into independent "berthing systems" A berthing system
consists of the wharf and supporting structure, mechanical
and electrical components that serve the berth and pipeline
systems as defined in Title 2 CCR §2560 and 2561 (n).
For example, a MOT consisting of wharves with three berths
adjacent to the shoreline could contain three independent
''berthing systems" if the piping does not route through adja-
cent berths. Therefore, a significant defect that would restrict
the operation of one berth would have no impact on the other
two berths. Conversely, if a T-head Pier, with multiple berths
sharing a trestle that supports all piping to the shoreline, had a
significant deficiency on the common trestle, the operation of
all berths could be adversely impacted. This configuration is
classified as a single berthing system.
The physical boundaries of a berthing system may
exclude unused sections of a structure. Excluded sections
must be physically isolated from the berthing system.
Expansion joints may provide this isolation.
3102FJ.4 Records, AllMOTs shall have records reflecting
current, as-built conditions for all berthing systems.
Records shall include, but not be limited to modifications
and/or replacement of structural components, electrical or
mechanical equipment or relevant operational changes,
new construction including design drawings, calculations,
engineering analyses, soil borings, equipment manuals,
specifications, shop drawings, technical and maintenance
manuals and documents.
Chronological records and reports of annual inspections,
audits and post-event inspections and documentation of
equipment or structural changes shall be maintained.
Records shall be indexed and be readily accessible to the
Division (see 2 CCR Section 2320 (c) (2)) [2.1].
3102F,L5 Baseline inspection. If "as-built" or subsequent
modification drawings are not available, incomplete or inac-
TABLE31F-2-2
MAXIMUM INTERVAL BETWEEN UNDERWATER AUDIT INSPECTIONS (YEARS)'
CONDITION
RATING FROM
PREVIOUS
INSPECTION
CONSTRUCTION MATERIAL
Unwrapped Timber or Unprotected Steel
(no coating orcathodic protection f
Concrete, Wrapped Timl
Composite Materials
jer. Protected Steel or
(FRP, plastic, etc.f
CHANNEL BOTTOM OR MUD
LINE— SCOUR*
Benign^
Environment
Aggressive^
Environment
Benign^
Environment
Aggressive^
Environment
Benign^
Environment
Aggressive^
Environment
6 (Good)
6
4
6
5
6
5
5 (Satisfactory)
6
4
6
5
6
5
4 (Fair)
5
3
5
4
6
5
3 (Poor)
4
3
5
4
6
5
2 (Serious)
2
1
2
2
2
2
} (Critical)
N/A^
N/A^
N/A^
N/A^
N/A^
N/A^
L The maximum interval between Underwater Audit Inspections shall be reduced as appropriate based on the extent of deterioration observed on a structure, the
rate of further anticipated deterioration or other factors.
2. Benign environments include fresh water and maximum current velocities less than 1.5 knots for the majority of the days in a calendar year.
3. Aggressive environments include brackish or salt water, polluted water, or waters with current velocities greater than 7.5 knots for the majority of the days in the
calendar year.
4. For most structures, two maximum intervals will be shown in this table, one for the assessment of construction material (timber, concrete, steel, etc.) and one for
scour (last 2 columns). The shorter interval of the two should dictate the maximum interval used.
5. MOTs rated "Critical" will not be operational; and Emergency Action shall be required in accordance with Table 3 IF -2-7.
510
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
«
curate, the audit must include a baseline inspection to gather
data in sufficient detail to adequately evaluate the MOT.
The level of detail required shall he such that structural
member sizes, connection and reinforcing details are docu-
mented, if required in the structural analysis. In addition,
the strength and/or ductility characteristics of construction
materials shall be determined, as appropriate. Nondestruc-
tive testing, partially destructive testing and/or laboratory
testing methods may be used.
All fire, piping, mechanical and electrical systems shall
be documented as to location, capacity, operating limits and
physical conditions,
3102E2 Annual inspection. The annual inspection required
by 2 CCR 2320 (a)(1) [2,1], may include an engineering exam-
ination of the topside and underside areas of the dock, includ-
ing the splash zone. The Division shall perform the inspection,
with cooperation from the owner/operator. Observations will
be recorded and a report of violations and deficiencies shall be
provided to the operator.
Subject to operating procedures, a boat shall be provided to
facilitate the inspection of the dock undersides and piles down
to the splash zone. If a boat is not available or the under dock
inspection cannot be performed by the Division during the
annual inspection, the MOT operator shall carry out or cause
to be carried out, such an inspection. The operator will then
provide the Division with a report detailing the examination
results including photographs, videos and sketches as neces-
sary to accurately depict the state of the underside of the dock.
3102E3 Audit.
3102F,3,1 Objective, The objective of the audit is to review
structural, mechanical and electrical systems on a pre-
scribed periodic basis to verify that each berthing system is
fit for its specific defined purpose. The audit includes both
above water and underwater inspections, as well as engi-
neering analyses,
3102E3,2 Overview, The initial audit shall include above
water and underwater structural inspections, mooring,
berthing and structural evaluations, and electrical/
mechanical systems evaluation. The audit is performed by a
multidisciplinary team of engineers, qualified inspectors
and may include Division representatives.
The above water inspection involves an examination of all
structural, mechanical and electrical components above the
waterline. Structural defects and their severity shall be doc-
umented, but the exact size and location of each deficiency is
typically not required.
A rational and representative underwater sampling of
piles may be acceptable with Division approval, for cases of
limited visibility, heavy marine growth, restricted inspec-
tion times because of environmental factors (currents, water
temperatures, etc.) or a very large number of piles,
A global condition assessment rating (CAR) shall be
assigned to above and underwater structural systems (Table
31F'2-5),
Remedial action priorities (RAP) shall be assigned for
component deficiencies (Table 31F-2-6). Recommendations
for remediation and/or upgrading shall be prescribed as nec-
essary.
An audit is not considered complete until the audit report
is received by the Division.
3102F.3,3 Schedule,
3I02F,3,3,I Initial audit. Table 31F-2-1 provides the
deadlines for the submission of the initial audit report.
The MOT classification in Table 31F-2-1 is determined
from the higher assigned risk classification obtained
from Table 31F-4-1.
For a new MOT berthing system, the initial audit shall
be performed within three years of commencement of
operations.
3102F,3,3,2 Subsequent audits. An above water audit of
structural, mechanical and electrical systems shall be
completed at a maximum interval of 3 years. This interval
may be reduced, based on the recommendation of the
audit team leader, and with the approval of the Division,
depending on the extent and rate of deterioration or other
factors.
The maximum interval for underwater audits is
dependent upon the condition of the facility, the con-
struction material type and/or the environment at the
mudline; as shown in Table 31F-2-2.
If there are no changes in the defined purpose (see Sec-
tion 3102F,3.6,1) of the berthing system, then analyses
from previous audits may be referenced. However, if
there is a significant change in a berthing system, or
when deterioration or damage must be considered, a new
analysis may be required.
The Division may require an audit to justify changes in
the use of a berthing system. An example of such change
would be in the berthing and mooring configuration of
larger or smaller vessels relative to dolphin and fender
spacing, and potential resultant modification to opera-
tional environmental limitations (e.g., wind speed).
Subsequent audits of the above water and underwater
structures and mechanical and electrical systems may or
may not be performed concurrently, depending upon the
required inspection intervals based on the prior audit
report.
3I02F,3.4 Audit team.
3102F,3,4J Project manager. The audit shall be con-
ducted by a multidisciplinary team under the direction of
a project manager representing the MOT. The project
manager shall have specific knowledge of the MOT and
may serve other roles on the audit team.
3102F.3,4,2 Audit team leader. The audit team leader
shall lead the on-site audit team and shall be responsible
for directing field activities, including the inspection of all
structural, mechanical and electrical systems. The team
2010 CALIFORNIA BUILDING CODE
511
MARINE OIL TERMINALS
leader shall be a California registered civil or structural
engineer and may serve other roles on the audit team,
3102FJ.4.3 Structural inspection team. The structural
inspection shall be conducted under the direction of a
registered civil or structural engineer
All members of the structural inspection team shall be
graduates of a 4-year civil/structural engineering, or
closely related (ocean/coastal) engineering curriculum,
and shall have been certified as an Engineer-in-Train-
ing; or shall be technicians who have completed a course
of study in structural inspections. The minimum accept-
able course in structural inspections shall include 80
hours of instruction specifically related to structural
inspection, followed by successful completion of a com-
prehensive examination. An example of an acceptable
course is the U,S, Department of Transportation's
"Safety Inspection of In- Service Bridges." Certification I I
as a Level IV Bridge Inspector by the National Institute
of Certification in Engineering Technologies (NICET)
shall also be acceptable [2,2].
For underwater inspections, the registered civil or
structural engineer directing the underwater structural
inspection shall also be a commercially trained diver or I I
equivalent and shall actively participate in the inspec-
tion, by personally conducting a minimum of 25 percent
of the underwater examination [2.2],
Each underwater team member shall also be a com-
mercially trained diver, or equivalent. Divers performing
I I
TABLE 31 F-2'3
UNDERWATER INSPECTION LEVELS OF EFFORT [2,2]
LEVEL
PURPOSE
DETECTABLE DEFECTS
Steel
Concrete
Timber
Composite
I
General visual/tactile
inspection to confirm
as-built condition and
detect severe damage
Extensive corrosion, holes
Severe mechanical damage
Major spalling and cracking
Severe reinforcement corrosion
Broken piles
Major loss of section
Broken piles and bracings
Severe abrasion or marine
borer attack
Permanent deformation
Broken piles
Major cracking or
mechanical damage
II
To detect surface defects
normally obscured by
marine growth
Moderate mechanical damage
Corrosion pitting and loss of
section
Surface cracking and spalling
Rust staining
Exposed reinforcing steel
and/or prestressing strands
External pile damage due to
marine borers
Splintered piles
Loss of bolts and fasteners
Rot or insect infestation
Cracking
Delamination
Material degradation
III
To detect hidden or
interior damage, evaluate
loss of cross-sectional
area, or evaluate material
homogeneity
Thickness of material
Electrical potentials for
cathodic protection
Location of reinforcing steel
Beginning of corrosion of
reinforcing steel
Internal voids
Change in material strength
Internal damage due to marine
borers {internal voids)
Decrease in material
strength
N/A
1 1
TABLE 31F'2'4
SCOPE OF UNDERWATER INSPECTIONS [2.2]
SAMPLE SIZE AND METHODOLOGY^'
Steel
Concrete
Timber
Composite
Sloe
Protection,
Bulkheads/
Bulkheads/
Bulkheads/
Bottom or Mud
LEVEL
Piles
Retaining Walls
Piles
Retaining Walls
Piles
Retaining Walls
Piles
Line-Scour
I
Sample Size:
100%
100%
100%
100%
100%
100%
100%
100%
Method:
Visual/Tactile
Visual/Tactile
Visual/Tactile
Visual/Tactile
Visual/Tactile
Visual/Tactile
Visual/Tactile
Visual/Tactile
Sample Size:
10%
Every 100 LF
10%
Every WOLF
10%
Every 50 LF
10%
0%
Method:
Visual: Removal
Visual: Removal
Visual-
Visual: Removal
Visual:
Visual: Removal
Visual:
of marine growth
of marine growth
Removal of
of marine
Removal of
of marine
Removal of
II
in 3 bands
in 1 SF areas
marine growth
growth in 1 SF
marine growth
growth in 1 SF
marine growth
in 3 bands
areas
on 3 bands
areas
in 3 bands
Measurement:
Remaining
diameter
Sample Size:
5%
Every 200 LF
0%
0%
5%
Every 100 LF
0%
0%
Method:
Remaining
thickness
measurement;
Remaining
thickness
measurement;
N/A
N/A
Internal
marine borer
infestation
Internal marine
borer
infestation
III
electrical potential
measurement;
corrosion
profiling as
necessary
electrical potential
measurement;
corrosion
profiling as
necessary
evaluation
evaluation
^ 1. The minimum inspection sampling size for small structures shall include at least two components.
LF = Linear Feet; SF = Square Feet; N/A ~ Not Applicable
512
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
TABLE 31 F-2-5
CONDITION ASSESSMENT RATINGS (CAR) [2.2]
RATING
DESCRIPTION OF STRUCTURAL SYSTEMS, ABOVE AND BELOW WATER LINE
6
Good
No problems or only minor problems noted. Structural elements may show very minor deterioration, but no overstressing observed.
The capacity of the structure meets the requirements of this standard.
The structure should be considered fit-for-purpose. No repairs or upgrades are required.
5
Satisfactory
Limited minor to moderate defects or deterioration observed, but no overstressing observed. The capacity of the structure meets the
requirements of this standard.
The structure should be considered fit-for-purpose. No repairs or upgrades are required.
4
Fair
All primary structural elements are sound; but minor to moderate defects or deterioration observed. Localized areas of moderate to
advanced deterioration may be present, but do not significantly reduce the load bearing capacity of the structure. The capacity of the
structure is no more than 15 percent below the structural requirements of this standard, as determined from an engineering evaluation.
The structure should be considered as marginal. Repair and/or upgrade measures may be required to remain operational. Facility
may remain operational provided a plan and schedule for remedial action is presented to and accepted by the Division.
3
Poor
Advanced deterioration or overstressing observed on widespread portions of the structure, but does not significantly reduce the load
bearing capacity of the structure. The capacity of the structure is no more than 25 percent below the structural requirements of this
standard, as determined from an engineering evaluation.
The structure is not fit-for-purpose. Repair and/or upgrade measures may be required to remain operational The facility may be
allowed to remain operational on a restricted or contingency basis until the deficiencies are corrected, provided a plan and schedule
for such work is presented to and accepted by the Division.
2
Serious
Advanced deterioration, overstressing or breakage may have significantly affected the load bearing capacity of primary structural
components. Local failures are possible and loading restrictions may be necessary. The capacity of the structure is more than 25
percent below than the structural requirements of this standard, as determined from an engineering evaluation.
The structure is not fit-for-purpose. Repairs and/or upgrade measures may be required to remain operational. The facility may be
allowed to remain operational on a restricted basis until the deficiencies are corrected, provided a plan and schedule for such work
is presented to and accepted by the Division.
1
Critical
Very advanced deterioration, overstressing or breakage has resulted in localized failure(s) of primary structural components. More
widespread failures are possible or likely to occur and load restrictions should be implemented as necessary. The capacity of the
structure is critically deficient relative to the structural requirements of this standard.
The structure is not fit-for-purpose. The facility shall cease operations until deficiencies are corrected and accepted by the Division.
TABLE 31 F-2'6
COMPONENT DEFICIENCY REMEDIAL ACTION PRIORITIES (RAP)
REMEDIAL
PRIORITIES
DESCRIPTION AND REMEDIAL ACTIONS
PI
Specified whenever a condition that poses an immediate threat to public health, safety or the environment is observed. Emergency actions
may consist of barricading or closing all or portions of the berthing system, evacuating product lines and ceasing transfer operations.
The berthing system is not fit-for-purpose. Immediate remedial actions are required prior to the continuance of normal operations.
P2
Specified whenever defects or deficiencies pose a potential threat to public health, safety and the environment. Actions may consist of limiting
or restricting operations until remedial measures have been completed.
The berthing system is not fit-for-purpose. This priority requires investigation, evaluation and urgent action.
P3
Specified whenever systems require upgrading in order to comply with the requirement of these standards or current applicable codes. These
deficiencies do not require emergency or urgent actions.
The MOT may have limitations placed on its operational status.
P4
Specified whenever damage or defects requiring repair are observed.
The berthing system is fit-for-purpose. Repair can be performed during normal maintenance cycles, but not to exceed one year
R
Recommended action is a good engineering/maintenance practice, but not required by these standards.
The berthing system is fit-for-purpose.
2010 CALIFORNIA BUILDING CODE
513
MARINE OIL TERMINALS
I I
TABLE 31 F-2-7
STRUCTURAL FOLLOW-UP ACTIONS [2.2]
FOLLOW-UP ACTION
DESCRIPTION
Emergency Action
Specified whenever a condition which poses an immediate threat to public health, safety or the environment is observed.
Emergency Actions may consist of barricading or closing all or portions of the berthing system, limiting vessel size, placing load
restrictions, evacuating product lines, ceasing transfer operations, etc.
Engineering Evaluation
Specified whenever structural damage or deficiencies are observed which require further investigation or evaluation to determine
appropriate follow-up actions.
Repair Design Inspection
Specified whenever damage or defects requiring repair are observed. The repair design inspection is performed to the level of
detail necessary to prepare appropriate repair plans, specifications and estimates.
Upgrade Design and
Implementation
Specified whenever the structural system requires upgrading in order to comply with the requirements of these standards and
current applicable codes.
Special Inspection
Typically specified to determine the cause or significance ofnontypical deterioration, usually prior to designing repairs. Special
testing, laboratory analysis, monitoring or investigation using nonstandard equipment or techniques are typically required.
Develop and Implement
Repair Plans
Specified when the Repair Design Inspection and required Special Inspections have been completed. Indicates that the structure is
ready to have repair plans prepared and implemented.
No Action
Specified when no further action is necessary until the next scheduled audit or inspection.
Example
EXECUTIVE SUMMARY TABLE (ES-1)
GLOBAL STRUCTURAL CONDITION ASSESSMENT RATINGS (CAR)
BERTHING
SYSTEM
SYSTEM
CONDITION
ASSESSMENT RA TING
fROM THIS
AUDit
FROM PREVIOUS
AUDit
NEXTAUDIT
DUE(MO/YR)
ASSIGNED FOLLOW-UP
ACTIONS
FIT'FOR-
PURPOSE?
North Wharf
Above Water
Structure
4 (Fair)
4 (date)
—
6/2004
Upgrade Design and
Implementation
No
Underwater
Structure
5 (Satisfactory)
—
4 (date)
10/2006
—
Yes
South Wharf
Above Water
Structure
4 (Fair
4 (date)
—
6/2004
Repair Design Inspection
No
Underwater
Structure
3 (Poor)
—
4 (date)
10/2006
Special Inspection; Repair
Design Inspection
No
Dolphin, Trestle, etc.
—
—
—
1. Place check mark and date of respective audit in proper column to indicate for each structural system, whether the system was included in the current auditor the
results are summarized from a previous audit.
Example
EXECUTIVE SUMMARY TABLE (ES-2)
COMPONENT DEFICIENCY REMEDIAL ACTION PRIORITIES (RAP)
BERTHING
SYSTEM
DEFICIENCY
REMEDIAL ACTION
PRIORITY(RAP) (P1-P4)
FROM THIS
AUDIT
FROM PREVIOUS
AUDIT
NEXTAUDIT
DUE(MO/YR)
DESCRIPTION OF
PLANNED REMEDIAL ACTION
FIT-FOR-
PURPOSE?
North Wharf
Fire main leaking
P3
4 (date)
6/2004
Repair
No
Pipeline badly
corroded
P2
4 (date)
—
Investigate;
urgent action required
Electrical (Class I
Div 2 violation)
PI
4 (date)
—
Immediate remedial action
required
II
TABLE 31 F-2'8
POST-EVENT RATINGS AND REMEDIAL ACTIONS [2.2]
RATING
SUMMARY OF DAMAGE
REMEDIAL ACTIONS
A
No significant event-induced damage observed.
No further action required. The berthing system may continue
operations.
B
Minor to moderate event-induced damage observed but all primary structural
elements and electrical/mechanical systems are sound.
Repairs or mitigation may be required to remain operational. The
berthing system may continue operations.
C
Moderate to major event-induced damage observed which may have
significantly affected the load bearing capacity of primary structural elements
or the functionality of key electrical/mechanical systems.
Repairs or mitigation may be necessary to resume or remain
operational. The berthing system may be allowed to resume limited
operations.
D
Major event-induced damage has resulted in localized or widespread failure of
primary structural components; or the functionality of key electrical/
mechanical systems has been significantly affected. Additional failures are
possible or likely to occur.
The berthing system may not resume operations until the
deficiencies are corrected.
514
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
manual tasks such as cleaning or supporting the diving
operation, but not conducting or reporting on inspec-
tions, may have lesser technical qualifications [2.2],
3102F,3A.4 Seismic structural analyst A California
registered civil or structural engineer shall perform the
seismic structural evaluation required for the audit,
3102E3,4,5 Electrical inspection team, A registered
electrical engineer shall direct the on-site team perform-
ing the inspection and evaluation of electrical compo-
nents and systems,
3102F,3,4.6 Mechanical inspection team, A registered
engineer shall direct the on-site team performing the
inspection of pipeline, mechanical and fire systems.
3102F,3,4,7 Divisional representation. The Division
representative(s) may participate in any audit as
observer(s) and may provide guidance,
3 102 E3, 4.8 Geotechnical analyst A California regis-
tered civil engineer with a California authorization as a
geotechnical engineer shall perform the geotechnical
evaluation required for the audit and all other
geotechnical evaluations,
3102F,3,5 Scope of inspection,
3102F,3,5,1 Above water structural inspection. The
above water inspection shall include all accessible com-
ponents above +3ftMLLW. Accessible components shall
be defined as those components above and below deck
that are reachable without the need for excavation or
extensive removal of materials that may impair visual
inspection. The above water inspection shall include but
not be limited to the following:
L Piles
2. Pile caps
3. Beams
4. Deck soffit
5. Bracing
6. Retaining walls and bulkheads
7. Connections
8. Seawalls
9. Slope protection
10. Deck topside s and curbing
11. Expansion joints
12. Fender system components
13. Dolphins and deadmen
14. Mooring points and hardware
15. Navigation aids
16. Platforms, ladders, stairs, handrails and gangways
1 7. Bacilli (sinkholes/differential settlement)
3102E3,5.2 Underwater structural inspection. The under-
water inspection shall include all accessible components
from -\-3 ft MLLW to the mudline, including the slope and
slope protection, in areas immediately surrounding the
MOT. The water depth at the berth(s) shall be evaluated,
verifying the maximum or loaded draft specified in the
MOTs Operations Manual (2 CCR 2385 (d)) [2.1].
The underwater structural inspection shall include the
Level 1, 11 and HI inspection efforts, as shown in Tables
31F-2-3 and 31F-2-4. The underwater inspection levels
of effort are described below, per [2.2]:
Level I— Includes a close visual examination, or a tactile
examination using large sweeping motions of the hands
where visibility is limited. Although the Level I effort is often
referred to as a ''swim-by" inspection, it must be detailed
enough to detect obvious major damage or deterioration
due to overstress or other severe deterioration. It should
confirm the continuity of the full length of all members and
detect undermining or exposure of normally buried ele-
ments. A Level I effort may also include limited probing of
the substructure and adjacent channel bottom.
Level II— A detailed inspection which requires marine
growth removal from a representative sampling of compo-
nents within the structure. For piles, a 12-inch high band
should be cleaned at designated locations, generally near
the low waterline, at the mud-line, and midway between
the low waterline and the mudline. On a rectangular pile,
the marine growth removal should include at least three
sides; on an octagon pile, at least six sides; on a round
pile, at least three-fourths of the perimeter. On large diam-
eter piles, 3 ft or greater, marine growth removal should be
effected on 1 ft by 1 ft areas at four locations approxi-
mately equally spaced around the perimeter, at each ele-
vation. On large solid faced elements such as retaining
structures, marine growth removal should be effected on 1
ft by 1ft areas at the three specified elevations. The inspec-
tion should also focus on typical areas of weakness, such
as attachment points and welds. TheLevel II effort is
intended to detect and identify damaged and deteriorated
areas that may be hidden by surface biofouling. The thor-
oughness of marine growth removal should be governed
by what is necessary to discern the condition of the under-
lying structural material. Removal of all biofouling stain-
ing is generally not required.
Level III^A detailed inspection typically involving
nondestructive or partially-destructive testing, conducted
to detect hidden or interior damage, or to evaluate mate-
rial homogeneity.
Typical inspection and testing techniques include the
use of ultrasonics, coring or boring, physical material
sampling and in-situ hardness testing. Level III testing is
generally limited to key structural areas, areas which are
suspect, or areas which may be representative of the
underwater structure.
3102F,3,5,3 Special inspection considerations,
3102F,3,5,3,1 Coated components. For coated steel
components, Level I and Level II efforts should focus
on the evaluation of the integrity and effectiveness of
the coating. The piles should be inspected without
damaging the coating. Level III efforts should include
2010 CALIFORNIA BUILDING CODE
515
MARINE OIL TERMINALS
ultrasonic thickness measurements without removal
of the coating, where feasible,
3102E3,5.3,2 Encased components. For steel, con-
crete or timber components that have been encased,
the Level I and II efforts should focus on the evaluation
of the integrity of the encasement. If evidence of signifi-
cant damage to the encasement is present, or if evi-
dence of significant deterioration of the underlying
component is present, then the damage evaluation
should consider whether the encasement was provided
for protection and/or structural capacity. Encasements
should not typically be removed for an audit.
For encasements on which the formwork has been
left in place, the inspection should focus on the integ-
rity of the encasement, not the formwork Level I and
Level II efforts in such cases should concentrate on the
top and bottom of the encasement. For concrete com-
ponents, if deterioration, loss of bonding, or other sig-
nificant problems with the encasement are suspected, it
may be necessary to conduct a special inspection,
including coring of the encasement and laboratory
evaluation of the materials.
3I02F,3.5,3J Wrapped components. For steel, con-
crete or timber components that have been wrapped,
the Level I and II efforts should focus on the evaluation
of the integrity of the wrap. Since the effectiveness of a
wrap may be compromised by removal, and since the
removal and re-installation of wraps is time-consum-
ing, it should not be routinely done. However, if evi-
dence of significant damage exists, or if the
effectiveness of the wraps is in question, then samples
should be removed to facilitate the inspection and eval-
uation. The samples may be limited to particular zones
or portions of members if damage is suspected, based
on the physical evidence of potential problems. A mini-
mum sample size of three members should be used. A
five-percent sample size, up to 30 total members, may
be adequate as an upper limit.
For wrapped timber components. Level III efforts
should consist of removal of the wraps from a represen-
tative sample of components in order to evaluate the
condition of the timber beneath the wrap. The sample
may be limited to particular zones or portions of the
members if damage is suspected (e.g., at the mudline/
bottom of wrap or in the tidal zone). The sample size
should be determined based on the physical evidence
of potential problems and the aggressiveness of the
environment. A minimum sample size of three members
should be used. A five-percent sample size, up to 30
total members, may be adequate as an upper limit.
3102F3.5.4 Mechanical electrical equipment The inspec-
tion of mechanical and electrical equipment shall include
but not be limited to the following components and systems:
1. Loading arms
2. Cranes and lifting equipment, including cables
3. Piping/manifolds and supports
4. Oil transfer hoses
5. Fire detection and suppression systems
6. Vapor control system
7. Sumps/sump tanks
8. Vent systems
9. Pumps and pump systems
10. Lighting
11. Communications equipment
12. Gangways
13. Electrical switches and junction boxes
14. Emergency power equipment
15. Air compressors
16. Meters
1 7. Cathodic protection systems
18. Winches
19. ESD and other control systems
20. Ladders
All alarms, limit switches, load cells, current meters,
anemometers, leak detection equipment, etc., shall be
operated and/or tested to the extent feasible, to ensure
proper function.
3102F3.6 Evaluation and assessment
3102F.3.6.1 Terminal operating limits. The physical
boundaries of the facility shall be defined by the berthing
system operating limits, along with the vessel size limits
and environmental conditions.
The audit shall include a ''Statement of Terminal
Operating Limits,'' which must provide a concise state-
ment of the purpose of each berthing system in terms of
operating limits. This description must at least include,
the minimum and maximum vessel sizes, including
Length Overall (LOA), beam, and maximum draft with
associated displacement (see Fig. 31F-2-1).
In establishing limits for both the minimum and maxi-
mum vessel sizes, due consideration shall be given to
water depths, dolphin spacing, fender system limita-
tions, manifold height and hose/loading arm reach, with
allowances for tidal fluctuations, surge and drift.
Maximum wind, current or wave conditions, or combi-
nations thereof shall be clearly defined as limiting con-
ditions for vessels at each berth, both with and without
active product transfer
3102E3,6,2 Mooring and berthing. Mooring and berth-
ing analyses shall be performed in accordance with Sec-
tion 3I0SE The analyses shall be consistent with the
terminal operating limits and the structural configuration
of the wharf and/or dolphins and associated hardware.
3102F,3,6.3 Structure, A structural evaluation, includ-
ing a seismic analysis, shall be performed in accordance
with Sections 3103F through 3107F. Such evaluation
shall consider local or global reduction in capacity, as
determined from the inspection.
516
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
Based on inspection results, structural analyses and
engineering judgment, CARs shall be assigned on a
global basis, independently for above and underwater
structures. The CARs defined in Table 31F-2-S shall be
used for this purpose. The CAR documents the structural
fitness-for-purpose. Structural component deficiencies
may be assigned RAPs as per Table 31F-2-6. The
assigned ratings shall remain in effect until all the signifi-
cant corrective action has been completed to the satisfac-
tion of the division, or until completion of the next audit.
3 102 R3, 6,4 Mechanical and electrical systems. An eval-
uation of all mechanical and electrical systems and com-
ponents shall be performed in accordance with Sections
3108F through 311 IF of these standards. If a pipeline
analysis is required, forces and imposed seismic displace-
ments resulting from the structural analysis shall be con-
sidered. Mechanical and electrical component
deficiencies shall be assigned ratings from Table 31F-2-6.
3102F.3 J Follow-up actions. Structural follow-up actions
as described in Table 31F-2-7 shall be prescribed. Multiple
follow-up actions may be assigned; however, guidance
should be provided as to the order in which the follow-up
actions should be carried out.
If a CAR of "7 " (Table 31F-2-5) or a RAP of 'Tl " (Table
31F-2-6) or "Emergency Action" using Table 31F-2-7, is
assigned to a berthing system, the Division shall be notified
immediately. The audit report shall include implementation
schedules for all follow-up and remedial actions. Follow-up
and remedial actions and implementation schedules are
subject to Division approval. Follow-up actions shall also
state the maximum interval before the next audit.
3 102F,3,8 Documentation and reporting. The audit report
shall be signed and stamped by the audit team leader.
Each audit, whether partial or complete, shall be adequately
documented. Partial audits cover only specific systems or
equipment examined. The resulting report shall summarize
and reference relevant previous ratings and deficiencies.
The contents of the audit report for each berthing system
shall, at a minimum, include the following as appropriate:
Executive summary — a concise summary of the audit
results and analyses conclusions. It shall include sum-
mary information for each berthing system, including an
overview of the as signed follow -up actions (See Example
Tables ES-1 and ES-2).
Table of contents
Body of report
Introduction — a brief description of the purpose and
scope of the audit, as well as a description of the inspec-
tion/evaluation methodology used for the audit.
Existing conditions — a brief description, along with a
summary of the observed conditions. Subsections should
be used to describe the above water structure, underwa-
ter structure and mechanical and electrical systems, to
the extent each are included in the scope of the audit.
Photos, plan views and sketches shall be utilized as
appropriate to describe the structure and the observed
conditions. Details of the inspection results such as test
data, measurements data, etc., shall be documented in an
appendix.
Evaluation and assessment — a CAR shall be assigned
to structural systems (above and under water). Mooring
and berthing analyses, structural analysis results, and
all supporting calculations shall be included in appendi-
ces as appropriate to substantiate the ratings. However,
the results and recommendations of the engineering
analyses shall be included in this section. Component
deficiencies should be described and a corresponding
RAP assigned.
Follow-up actions — Specific structural follow-up
actions shall be documented (Table 3 IF -2-7), and reme-
dial schedules included, for each audited system. Audit
team leaders shall specify which follow-up actions
require a California registered engineer to certify that
the completion is acceptable.
Appendices — When appropriate, the following appendi-
ces shall be included:
1. Background data on the terminal - description of the
service environment (wind/waves/currents), extent
and type of marine growth, unusual environmental
conditions, etc.
2. Inspection/testing data
3. Mooring and berthing analyses
4. Structural and seismic analyses and calculations
5. Geotechnical report
6. MOT Fire Plan
7. Pipeline stress and displacement analyses
8. Mechanical and electrical system documentation
9. Photographs and/or sketches shall be included to
document typical conditions and referenced defi-
ciencies, and to justify CARs and RAPs.
10. Condition assessment rating (CAR) report and sup-
porting data
11. Remedial action priorities (RAP) report and sup-
porting data
3102F.3.9 Action plan implementation report. Within 90
days of completion of the remedial measures (for serious
deficiencies, such as PI, P2 or any structural CAR less than
5) specified in the follow-up action plan(s), a report shall be
submitted to the Division and shall include:
1. A description of each action taken
2. Updated RAPs and CARs
3. Supporting documentation with calculations and/or
relevant data
3102F.4 Post-Event inspection, A post-event inspection is a
focused inspection following a significant, potentially dam-
age-causing event such as an earthquake, storm, vessel impact,
fire, explosion or tsunami. The primary purpose is to assess the
integrity of structural, mechanical and electrical systems. This
2010 CALIFORNIA BUILDING CODE
517
MARINE OIL TERMINALS
assessment will determine the operational status and/or any
remedial measures required.
3102FA.1 Notification and action plan. Notification as per
2 CCR 2325(e) [2.1] shall he provided to the local area
Division field ofiice. The notification shall include, as a min-
imum:
L Brief description of the event
2, Brief description of the nature^ extent and signifi-
cance of any damage observed as a result of the event
3, Operational status and any required restrictions
4, Statement as to whether a Post-Event inspection will
he carried out
The Division may carry out or cause to be carried out, a
post-event inspection. In the interim, the Division may
direct a change in the operations manual, per 2 CCR 2385
(f)(3) [2,11
If a post-event inspection is required, an action plan shall
be submitted to the Division within five (5) days after the
event. This deadline may be extended in special circum-
stances. The action plan shall include the scope of the
inspection (above water, underwater, electrical, mechanical
systems, physical limits, applicable berthing systems, etc)
and submission date of the final report. The action plan is
subject to Division approval
3102F.4,2 Inspection team. The qualifications of the
inspection team shall be the same as those prescribed in
Section 3102F.3.4. Division representatives may partici-
pate in any post-event inspection, as observers, and may
provide guidance.
3102E4.3 Scope* The post-event inspection shall focus on
the possible damage caused by the event. General observa-
tions of long-term or preexisting deterioration such as sig-
nificant corrosion-related damage or other deterioration
should be made as appropriate, but should not be the focus
of the inspection. The inspection shall always include an
above-water assessment of structural, mechanical and elec-
trical components.
The inspection team leader shall determine the need for,
and methodology of, an underwater structural assessment,
in consultation with the Division. Above water observa-
tions, such as shifting or differential settlement, misalign-
ments, significant cracking or spalling, bulging, etc., shall
be used to determine whether or not an underwater assess-
ment is required. Similarly, the inspection team leader shall
determine, in consultation with the Division, the need for,
and methodology of any supplemental inspections (e.g.,
special inspections (see Section 3102K3.5.3).
The following information may be important in determin-
ing the need for, and methodology of, the post-event inspec-
tion:
1. Earthquakes or vessel or debris impact typically
cause damage both above and below the water line.
Following a major earthquake, the inspection should
focus on components likely to attract highest lateral
loads (batter or shorter piles in the rear of the struc-
ture, etc). In case of vessel or debris impact, the
inspection effort should focus on components in the
path of the impact mass.
2. Major floods or tsunamis may cause undermining of
the structure, and/or scouring at the mud line,
3. Fire damage varies significantly with the type of con-
struction materials but all types may be adversely
affected. Special inspections (sampling and labora-
tory testing) shall be conducted, as determined by the
inspection team leader, in order to determine the
nature and extent of damage.
4. High wind or wave events often cause damage both
above and below the water line. An underwater
inspection may be required if damage is visible above
the waterline. Structural damage may be potentially
increased if a vessel was at the berth during the event.
The effects of high wind may be most prevalent on
equipment and connections of such equipment to the
structure.
The methodology of conducting an underwater post-
event inspection should be established with due consider-
ation of the structure type and type of damage anticipated.
Whereas slope failures or scour may be readily apparent in
waters of adequate visibility, overstressing cracks on piles
covered with marine growth will not be readily apparent.
Where such hidden damage is suspected, marine growth
removal should be performed on a representative sampling
of components in accordance with the Level II effort
requirements described in Section 3102F3.5.2. The cause
of the event will determine the appropriate sample size and
locations.
3102F,4.4 Post-Event ratings. A post-event rating [2.2]
shall be assigned to each berthing system upon completion
of the inspection (see Table 31F-2-8). All observations of
the above and under water structure, mechanical and elec-
trical components and systems shall be considered in
assigning a post-event rating.
Ratings should consider only damage that was likely
caused by the event. Pre-existing deterioration such as cor-
rosion damage should not be considered unless the struc-
tural integrity is immediately threatened or safety systems
or protection of the environment may be compromised.
Assignment of ratings should reflect an overall character-
ization of the berthing system being rated. The rating shall
consider both the severity of the deterioration and the extent
to which it is widespread throughout the facility. The fact
that the facility was designed for loads that are lower than
the current standards for design should have no influence
upon the ratings.
3I02F,4,5 Follow-up actions. Follow-up actions shall be
assigned upon completion of the post-event inspection of
each berthing system. Table 31F-2-6 specifies remedial
action priorities and actions for mechanical and electrical
deficiencies. Table 31F-2-7 specifies various options for
structural systems. Multiple follow-up actions may be
assigned; however, guidance should be provided as to the
order in which the follow-up actions should be carried-out.
Follow-up actions shall be subject to Division approval.
518
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
3102R4.6 Documentation and reporting. Documentation
of the specific attributes of each defect shall not he required
during a post-event inspection. However, a narrative
description of significant damage shall be used. The
description shall be consistent with and shall justify the
post-event rating assigned.
A report shall be prepared and submitted to the Division
upon completion of the post-event inspection and shall, at a
minimum, include:
L Brief description of the facility including the physi-
cal limits of the structure, type of construction mate-
rial(s), and the mechanical and electrical systems
present
2. Brief description of the event triggering the inspec-
tion
3. Scope of the inspection (above water, underwater,
electrical or mechanical)
4. Date of the inspection
5. Names and affiliations of inspection team
6. Description of the nature, extent and significance of
any observed damage resulting from the event
7. Photographs should be provided to substantiate the
descriptions and justify the condition rating
S. Assignment of a post-event rating
9. Statement regarding whether the facility is fit to
resume operations and, if so, under what conditions
10. Assignment of follow-up action(s)
11. Inspection data, drawings, calculations and other
relevant engineering materials
12. Signature and stamp of team leader(s)
3102F.4J Action Plan Report Upon completion of all
actions delineated in the action plan, a final report shall be
submitted to the Division to document the work completed.
Supporting documentation such as calculations or other
relevant data shall be provided in appendices.
3102K5 References,
[2.1] California Code of Regulations (CCR), Title 2, Divi-
sion 3, Chapter 1, Article5, Marine Terminals Inspec-
tion and Monitoring, Sections 2315, 2320, 2325 and
2385 (short form example: 2 CCR 2315 (Title 2 of
California Code of Regulations, Section 2315).
I I [2.2] Childs, K.M., editor, 2001, "Underwater Investiga-
tions - Standard Practice Manual, " American Society
of Civil Engineers, Reston, VA.
Authority: Sections 8755 and 8757, Public Resources Code
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE 519
U1
lO
o
I
P
eim^HINO SYSTEM NAME;
FACILITY ASDI^SS:
EXAMPLE
STATEMENT OF TERMINAL OPERATING LIMITS
timB_
«0i OF "mANSFS^SnrEAR;
i
CO
ALL yOCMINC ONES SHALL HAS/t
A MMum m^m^G sm:mm op.
MAX DRAFT AT BERTH
MAX FREEBOARD AT BERTH
yAxiyyy vessel
MINIMUM VESSEL
am
a.EAM -
BEm -
ygjp m
^mi.wKJEmmpiH^
WfTMUNPiRKiitCLiARAP^iOF ...
^mo^ OPERATIC^ mnum
PHYSICAL SOU^DARIES OF BERTHII^ SYSTEM^
BgRTKINQ §Y$TP^ SQUTOiWEy
^-^""
O
O
>
Tl
O
>
DO
C
n
g
z
o
o
o
a
m
'^^m^^^M;^^
>j^^
WEST 8iRm
L_u ■:
r r- — piPEvmy
f AST ^RTH
%.
FIGURE 31F-2'1
ENVtR pNMENTAL CONDITION LIMffS:
(Must BE DUALIFIED AI4D eOCUfcCNTBD fiV
•:'i^.
FENOiR t^ag
VWNS RESTRICTiON CHA3RAM
NOTE.
LEQgllD;
MARINE OIL TERMINALS
Division 3
SECTION 3103F
STRUCTURAL LOADING CRITERIA
3 103 El General Section 3I03F establishes the environmen-
tal and operating loads acting on the marine oil terminal
(MOT) structures and on moored vessel(s). The analysis proce-
dures are presented in Sections 3104F - 3107E
3103F.2 Dead loads,
3103F,2J General Dead loads shall include the weight of the
entire structure, including permanent attachments such as
loading arms, pipelines, deck crane, fire monitor tower, gang-
way structure, vapor control equipment and mooring hard-
ware. Unit weights specified in Section 3103F2.2 may be used
for MOT structures if actual weights are not available.
3103F.2.2 Unit weights. The unit weights in Table 31F-3-1
may be used for both existing and new MOTs.
TABLE 31 F'3-1
UNIT WEIGHTS
MATERIAL
UNIT WEIGHT (pen*
Steel or cast steel
490
Cast iron
450
Aluminum alloys
175
Timber (untreated)
40-50
Timber (treated)
45-60
Concrete, reinforced (normal weight)
145-160
Concrete, reinforced (lightweight)
90-120
Asphalt paving.
150
* pounds per cubic foot
3103F.2.3 Equipment and Piping Area Loads, The equip-
ment and piping area loads in Table 31F-3-2 may be used,
as a minimum, in lieu of detailed as-built data.
TABLE 31 F-3'2
EQUIPMENT AND PIPING AREA LOADS
LOCATION
AREA LOADS (psf)***
Open areas
20*
Areas containing eauipment and piping
55**
Trestle roadway
20*
* Allowance for incidental items such as railings, lighting, miscellaneous
equipment, etc.
^"^35 psfisfor miscellaneous general items such as walkways, pipe supports,
lighting and instrumentation. Major equipment weight shall be established
and added into this weight for piping manifold, valves, deck crane, fire moni-
tor tower, gangway structure and similar ma/or equipment.
*** pounds per square foot
3103F.3 Live loads and buoyancy. The following vertical live
loading shall be considered, where appropriate: uniform load-
ing, truck loading, crane loading and buoyancy. Additionally,
MOT specific, nonpermanent equipment shall be identified and
used in loading computations.
3103E4 Earthquake loads.
3103E4J General Earthquake loads are described in terms
of Peak Ground Acceleration (PGA), spectral acceleration
and earthquake magnitude. The required seismic analysis
procedures (Tables 31F~4-2 and 31F-4-3) are dependent on
the risk classification obtained from Table 31F-4-1.
3103E.4.2 Design earthquake motion parameters. The
earthquake ground motion parameters of peak ground
acceleration, spectral acceleration and earthquake magni-
tude are modified for site amplification and near fault
directivity effects. The resulting values are the design peak
ground acceleration (DPGA), design spectral acceleration
(DSA) and design earthquake magnitude (DEM).
The peak ground and spectral acceleration may be evalu-
ated using:
L U.S. Geological Survey (USGS) or California Geo-
logical Survey [CGS, formerly the California Divi-
sion of Mines and Geology (CDMG)] maps as
discussed in Section 3103F.4.2.2,
2. A site -specific probabilistic seismic hazard analysis
(PSHA) as discussed in Section 3103F.4.2.3.
3. For the Ports of Los Angeles, Long Beach and Port
Hueneme, PSHA results are provided in Section
3103F.4.2.3.
Unless stated otherwise, the DSA values arefor 5 percent
damping; values at other levels may be obtained as per Sec-
tion 3103 F.4.2. 9,
The appropriate probability levels associated with DPGA
and DSA for different seismic performance levels are pro-
vided in Table 31F-4 -2. Deterministic earthquake motions,
which are used only for comparison to the probabilistic
results, are addressed in Section 3 103 F.4.2. 7.
The evaluation of Design Earthquake Magnitude (DEM),
is discussed in Section 3103F.4.2.8. This parameter is
required when acceleration time histories (Section
3103F.4.2.10) are addressed or if liquefaction potential
(Section 3106F3) is being evaluated.
3103F.4.2.1 Site classes. The following site classes,
defined in Section 3106F.2, shall be used in developing
values of DSA and DPGA:
A^ '^Bf '^Cf ^D* E ana op.
For Sf, a site-specific response analysis is required per
Section 3 103F4.2.5.
3103F.4.2.2 Earthquake motions from USGS maps.
Earthquake ground motion parameters can be obtained
from the Maps 29-32 in the National Earthquake Haz-
ard Reduction Program (NEHRP) design map set dis-
cussed in subsection 1.6.1 of [3.1], or the USGS web-
site: (http .'//earthquake, usgs.gov/research/hazmaps/).
These are available as peak ground acceleration and
spectral acceleration values at 5 percent damping for
10 and 2 percent probability ofexceedance in 50 years,
which correspond to Average Return Periods (ARPs) of
475 and 2, 47 5 years, respectively. The spectral acceler-
ation values are available for 0.2, and 1.0 second spec-
tral periods. In obtaining peak ground acceleration and
spectral acceleration values from the USGS web site,
the site location can be specified in terms of site longi-
tude and latitude or the zip code when appropriate. The
2010 CALIFORNIA BUILDING CODE
521
MARINE OIL TERMINALS
II
resulting values of peak ground acceleration and spec-
tral acceleration correspond to surface motions for Site
Classification approximately corresponding to the
boundary of Site Class Sb and S^.
Once peak ground acceleration and spectral accelera-
tion values are obtained for 10 and! percent probability
ofexceedence in 50 years, the corresponding values for
other probability levels may be obtained. A procedure is
presented in subsection L6 of Chapter 1 of [3.1].
3103F,4,2,3 Earthquake motions from site-specific
probabilistic seismic hazard analyses. Peak ground accel-
eration and spectral acceleration values can be obtained
using site-specific probabilistic seismic hazard analysis
(PSHA). In this approach, the seismic sources and their
characterization used in the analysis shall be based on the
published data from the California Geological Survey,
which can be obtained online at the following website:
(http.'/Avww. conservation, ca. gov/CGS/Pages/Index. aspx)
[3.2].
Appropriate attenuation relationships shall be used to
obtain values of peak ground acceleration and spectral
acceleration at the ground surface for site conditions corre-
sponding to the boundary of Site Class Sq and S^ regardless
of the actual subsurface conditions at the site. These results
shall be compared to those based on the FEMA/USGS
maps discussed in Section 3103E4.2.2. If the two sets of
values are significantly different, a justification for using
the characterization chosen shall be provided.
Alternatively, peak ground acceleration and spectral
accelerations at the ground surface for the subsurface
conditions that actually exist at the site may be directly
obtained by using appropriate attenuation relationships
in a site- specific PSHA. This approach is not permissible
for Site Classes S^ and Sp.
For site-specific PSHA, peak ground acceleration and
spectral acceleration values corresponding to the seis-
mic performance level (See Table 31F-4-2) shall be
obtained.
For peak ground acceleration, PSHA may be conducted
using the "magnitude weighting" procedure in Idriss
[3.3]. The actual magnitude weighting values should fol-
low the Southern California Earthquake Center (SCEC)
procedures [3.4]. This magnitude weighting procedure
incorporates the effects of duration corresponding to vari-
ous magnitude events in the PSHA results. The resulting
peak ground acceleration shall be used only for liquefac-
tion assessment (see Section 3106F.4).
PSHA have been developed for the Ports of Los
Angeles and Long Beach [3.5, 3. 6] and provide site-spe-
cific information for seismic analyses. Table 31F-3-3
provides response spectra, for a 475 year return period
earthquake and 5 percent critical damping. Figure
31F-3-1 provides the corresponding spectra for the two
ports. Additionally, these references provide spectra for
return periods from 72 to 2,500 years.
For the port of Port Hueneme, a PSHA was performed
by Lawrence Livermore National Laboratory [3. 7] and
the results are shown in Table 31F-3-4 and Figure
31F-3-2. These results are provided only for site classifi-
cation "Sc" and five percent critical damping. To obtain
appropriate values for piles and/or the mudline, the sim-
plified procedures of Section 3103F4.2.4 may be used.
1.40
1.20
J
^
k.
1 III
—k- Port of Los Angel
1 1
es
y
C-^
S
\
\
" " » Port of Long Beacn p
,/
/
1
^
^i^
s
/
/
^
\
/
■
\
1
\
N
s
s
1.00
o 0.80
I
S 0.60
0.40
0.20
0.00
0.01
0.1
Period -Seconds
10
FIGURE 31F-3-1 DESIGN ACCELERATION RESPONSE SPECTRA FOR THE PORTS OF LOS ANGELES
AND LONG BEACH, 475 YEAR RETURN PERIOD (5% Critical Damping)
522
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
0.7m) ^
. .
QMm^
^ ^
\
^^., „,-,.. -^
i
\
1 i^i^r^..
\
"■""""""
]•
)
k
ii i\Af^ .
i
X
g Wi^'Hw
^
V
i
N.
ft-i*^^ ,
>
1
aic^^
:
|.,..
'
0.C^^
t>m
&J0
2m
ZM-
FIGURE 31F'3'2 RESPONSE SPECTRA FOR PORT HUENEME,
475 YEAR RETURN PERIOD (5% Critical Damping)
3103FA.2A Simplified evaluation of site amplification
effects. When the MOT Site Class is dijf event from the Sg -
Sc boundary, site amplification effects shall be incorpo-
rated in peak ground accelerations and spectral acceler-
ations. This may be accomplished using a simplified
method or a site-specific evaluation (Section
3103F.4,2.5).
For a given site class, the following procedure [3.1]
presents a simplified method that may be used to incor-
porate the site amplification effects for peak ground
acceleration and spectral acceleration computed for the
Sq and Sc boundary.
I. Calculate the spectral acceleration values at 0.20
and 1,0 second period:
(3-1)
(3-2)
where:
F^ = site coefficient obtained from Table 31F-3-5
F^ = site coefficient obtained from Table 31F-3-6
Ss = short period (usually at 0.20 seconds) spectral
acceleration value (for the boundary ofS^ and
Sc) obtained using Section 3 1 03 F .4.2.2, or at
Si =
Sxs~
the period corresponding to the peak in spec-
tral acceleration values when obtained from
Section 3103F.4.2.3
spectral acceleration value (for the boundary
ofSs and Sc) at 1.0 second period
spectral acceleration value obtained using the
short period S, and factored by Table 31F-3-5
for the Site Class under consideration.
spectral acceleration value obtained using the
1.0 second period Sj and factored by Table
31F-3-6 for the Site Class under consider-
ation.
2. SetPGAx = 0.4Sxs
where:
(3-3)
PGAx = peak ground acceleration corresponding to
the Site Class under consideration.
When the value ofPGAx is less than the peak ground
acceleration obtained following Section 3103F.4.2.2 or
Section 3103F4.2.3, an explanation of the results shall
be provided.
3. PGAx, Sxsy cind Sxi constitute three spectral accel-
eration values for the Site Class under consider-
ation corresponding to periods ofO, Ss (usually 0,2
seconds), and 1.0 second, respectively.
4. The final response spectra, without consideration
for near-fault directivity effects, values of S^ for
the Site Class under consideration may be
obtained using the following equations (for 5 per-
cent critical damping):
for 0<T<0.2To
K^(Sxs)(OA + 3T/To) (3-4)
where:
T = Period corresponding to calculated S^
Tq = Period at which the constant acceleration and
constant velocity regions of the design spec-
trum intersect
for 0.2To<T<To
^a - SxS
for T>To
where:
(3-5)
(3-6)
(3-7)
The resulting PGAx is the DPGA. However, the S^
(except for the ports of Los Angeles, Long Beach and
Port Hueneme) shall be modified for near-fault
directivity effects, per Section 3103F.4.2. 6 to obtain the
final DSAs.
2010 CALIFORNIA BUILDING CODE
523
MARINE OIL TERMINALS
TABLE 31 F-3'3
DESIGN ACCELERATION RESPONSE SPECTRA FOR THE
PORTS OF LOS ANGELES AND LONG BEACH, 475 YEAR
RETURN PERIOD (5% Critical Damping)
TABLE 31 F-3-6
VALUES OF F^
Period (sec)
Spectral Acceleration (g's)
Port of Los Angeles
Port of Long Beach
0.01
0.520
0.500
0.03
0.520
0.500
0.1
0.931
0.910
0.2
1.154
1.132
0.3
1.270
1.121
0.4
1.223
1.050
0.5
L148
0.980
0.75
0.937
0.840
1.0
0.740
0.717
1.5
0.510
0.510
2.0
0.380
0.362
3.0
0.210
0.199
4.0
0.135
0.128
5.0
0.094
0.091
6.0
0.069
0.068
8.0
0.041
0.041
10.0
0.027
0.027
TABLE 31 F-3-4
RESPONSE SPECTRA FOR PORT HUENEME,
475 YEAR RETURN PERIOD (5% Critical Damping)
SITE CLASS *'C"
(Shear Wave Velocity from 1200-2500 ft/sec)
Period (sec)
Frequency (H^
Spectral Acceleration (g's)
0.03
33.33
0.41
0.05
20.00
0.46
0.10
10.0
0.63
0.15
6.67
0.75
0.20
5.0
0.80
0.30
3.33
0.78
0.50
2.00
0.69
1.0
1.0
0.49
2,0
0.50
0.28
TABLE 31 F-3-5
VALUES OF F„
SITE
CLASS
Ss
<0.25
0.5
0.75
,.0
> 1.25
Sa
0.8
0.8
0.8
0.8
0.8
s.
1.0
1.0
1.0
1.0
1.0
Sr
1.2
1.2
1.1
1.0
1.0
Sn
1.6
1.4
1.2
1.1
1.0
Sk
2.5
1.7
1.2
0.9
0.9
Sf
*
*
*
*
*
SITE
CLASS
St
<0.1
0.2
0.3
0.4
>0.5
Sa
0.8
0.8
0.8 ,
0.8
0.8
Sb
1.0
1.0
1.0
1.0
1.0
Sc
1.7
1.6
1.5
1.4
1.3
Sn
2.4
2.0
1.8
1.6
1.5
Se
3.5
3.2
2.8
2.4
2.4
s.
*
*
*
*
*
NOTE: Linear interpolation can he used to estimate values ofF^for intermedi-
ate values ofSg.
* Site-specific dynamic site response analysis shall he performed.
NOTE: Linear interpolation can he used to estimate values ofFJor intermedi-
ate values ofSj.
* Site-specific dynamic site response analysis shall he performed.
3103E4,2.5 Site-specific evaluation of amplification
effects. As an alternative to the procedure presented in
Section 3103F.4.2.4, a site-specific response analysis may
be performed. For S^ a site specific response analysis is
required. The analysis shall be either an equivalent linear
or nonlinear analysis. Appropriate acceleration time his-
tories as discussed in Section 3103E4.2.10shall be used.
In general, an equivalent linear analysis using, for
example, SHAKE91 [3.8] is acceptable when the strength
and stiffness of soils are unlikely to change significantly
during the seismic shaking, and the level of shaking is not
large. A nonlinear analysis should be used when the
strength and/or stiffness of soils could significantly
change during the seismic shaking or significant
nonlinearity of soils is expected because of high seismic
shaking levels.
The choice of the method used in site response analysis
shall be justified considering the expected stress-strain
behavior of soils under the shaking level considered in
the analysis.
Site- specific site response analysis may be performed
using one-dimensional analysis. However, to the extent
that MOTs often involve slopes or earth retaining struc-
tures, the one -dimensional analysis should be used judi-
ciously. When one -dimensional analysis cannot be
justified or is not adequate, two-dimensional equivalent
linear or nonlinear response analysis shall be per-
formed. Site-specific response analysis results shall be
compared to those based on the simplified method of Sec-
tion 3103F.4.2.4for reasonableness.
For the port areas of Los Angeles, Long Beach and
Port Hueneme, the resulting response spectra shall not
fall below values obtained in Section 3I03F4.2.3.
The peak ground accelerations obtained from this
site-specific evaluation are DPGAs and the spectral
accelerations are DSAs as long as the near-fault
directivity effects addressed in Section 3103F.4.2. 6 are
appropriately incorporated into the time histories (Sec-
tion 3103F4.2.10).
3103F.4,2,6 Directivity effects. When the site is 15 km (9.3
miles) or closer to a seismic source that can significantly
affect the site, near-fault directivity effects shall be
refiected in the spectral acceleration values and in the
524
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
deterministic spectral acceleration values of Section
3103FA.2, 7. However, Tables 31F-3-3 and 31F'3-4for
the port areas of Los Angeles, Long Beach and Port
Hueneme already have these effects included.
Two methods are available for incorporating
directivity effects,
L Directivity effects may be reflected in the spectral
acceleration values in a deterministic manner by
using, for example, the equation on pg, 213 (and
Tables 6 and 7) ofSomerville, et al, [3,9], The criti-
cal seismic sources and their characterization
developed as part of the deterministic ground
motion parameters (Section 3103FA,2. 7) should
be used to evaluate the directivity effects. The
resulting adjustments in spectral acceleration val-
ues may be applied in the probabilistic spectral
acceleration values developed per Section
3103F.4.2.4 or 3103F.4.2,5. Such adjustment can
be independent of the probability levels of spectral
accelerations.
2. Directivity effects may be incorporated in the results
of site specific PSHA per Section 3103F.4.2.3. In this
case, the directivity effects will also depend on the
probability level of spectral accelerations.
If spectral accelerations are obtained in this manner,
the effects of site amplification using either Section
3103F.4.2A, 3103F.4,2.5 or an equivalent method (if
justified) shall be incorporated.
3103F,4,2J Deterministic earthquake motions. Deter-
ministic ground motions from "scenario" earthquakes
may be used for comparison purposes. Deterministic peak
ground accelerations and spectral accelerations may be
obtained using the ''Critical Seismic Source " with maxi-
mum earthquake magnitude and its closest appropriate
distance to the MOT. ''Critical Seismic Source" is that
which results in the largest computedmedian peak ground
acceleration and spectral acceleration values when
appropriate attenuation relationships are used. The val-
ues obtained from multiple attenuation relationships
should be used to calculate the median peak ground accel-
eration and spectral acceleration values.
For comparison, the values of peak ground accelera-
tions and spectral accelerations may be obtained from
the USGS maps [3.1], corresponding to the Maximum
Considered Earthquake (MCE). In this case, the median
values of peak ground acceleration and spectral acceler-
ation values shall be 213 (see Subsection 1.6 of [3.1]) of
the values shown on the USGS maps.
m
o
Q
m
m
>
o
*.II
;
u*
s
,mm^
i.l
:■:
^
:'■ 1'
s
k.i<u
r- ii '
,: :
-^
..
l*#
Ni;
s
^Jj.
: ! \
=">;
V,,
J
o.t
-•i
s
^
: ;
"s
0.1
, .
^
'"h
S
-^-1
0-f
•N,
S
1
.
ii)
9.*
mm,d
i
WIND OyitilTlON> t
FIGURE 31F-3'3 WIND SPEED CONVERSION FACTOR [3. 12]
1 1 HH J
2010 CALIFORNIA BUILDING CODE
525
MARINE OIL TERMINALS
I A
mmuiwm
dtol^ Vertical V«(#eli^ GrpdlftM Wlit
A$$(i{!n«d To Vaiy A^goitiinsi To
%/7 f^m&t Uw
20 30 40 50 40 70 80
FIGURE 31F-3-4 CURRENT VELOCITY CORRECTION FACTOR (p. 23, OCIMF , 1997 [3, 13])
90
100
3103F,4,2,8 Design earthquake magnitude. The design
earthquake magnitude used in developing site-specific
acceleration time histories (Section 3I03E4.2.10) or liq-
uefaction assessment (Section 3106E3) is obtained using
either of the following two methods.
1. The design earthquake may be selected as the larg-
est earthquake magnitude associated with the crit-
ical seismic source. The distance shall be taken as
the closest distance from the source to the site. The
resulting design earthquake shall be associated
with all DPGA values for the site, irrespective of
probability levels.
2. The design earthquake (DEQ) may be obtained for
each DPGA or DSA value and associated proba-
bility level by determining the corresponding dom-
inant distance and magnitude. These are the
values of the distance and magnitude that contrib-
ute the most to the mean seismic hazards estimates
for the probability of interest. They are usually
determined by locating the summits of the 3-D sur-
face of contribution of each small interval of mag-
nitude and distance to the total mean hazards
estimate. If this 3-D surface shows several modes
with approximate weight of more than 20 percent
of the total, several DEQs may be considered, and
the DEQ leading to the most conservative design
parameters shall be used.
3103F.4,2.9 Design spectral acceleration for various
damping values. Design spectral acceleration (DSA)
values at damping other than 5 percent shall be obtained
by using a procedure given in [3.1], and is denoted as
DSA^. The following procedure does not include
near-fault directivity effects,
ForO<T< 0.2 Tq
DSA, = S^s [(5/Bs -2) T/To + 0.4]
Eor0.2To<T<To
DSA, = DSA/Bs
For T>Tn
(3-8)
(3-9)
DSA, = S,/(BjT) (3-10)
where:
T = period
Eg = Coefficient used to adjust the short period spectral
response, for the effect of viscous damping.
Bj = Coefficient used to adjust one-second period spec-
tral response, for the effect of viscous damping
526
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
Values of B sand B} are obtained from Table 31F-3-7.
Such a procedure shall incorporate the near-fault
directivity effects when the MOT is 15 km (9.3 miles) or
closer to a significant seismic source.
TABLE 31 F-3'7 [3,1]
VALUES OF Bs AND B,
DAMPING (%)
Bs
Bi
<2
0.8
0.8
5
1.0
1.0
10
1.3
1.2
20
1.8
1.5
30
2.3
1.7
40
2.7
1.9
>50
3.0
2.0
Note: Linear interpolation should be used for damping values not
specifically listed.
3103F,4.2.10 Development of acceleration time
histories. When acceleration time histories are utilized,
target spectral acceleration values shall be initially
selected corresponding to the DSA values at appropriate
probability levels. For each set of target spectral
acceleration values corresponding to one probability
level, at least three sets of horizontal time histories (one or
two horizontal acceleration time histories per set) shall be
developed.
Initial time histories shall consider magnitude, distance
and the type of fault that are reasonably similar to those
associated with the conditions contributing most to the
probabilistic DSA values. Preferred initial time histories
should have their earthquake magnitude and distance to
the seismic source similar to the mode-magnitude and
mode-distance derived from the PSHA or from appropri-
ate maps. When an adequate number of recorded time his-
tories are not available, acceleration time histories from
simulations may be used as supplements.
Scaling or adjustments, either in the frequency domain
or in the time domain (preferably), prior to generating
acceleration time histories should be kept to a minimum.
When the target spectral accelerations include
near-fault directivity effects (Section 3I03F.4.2.6), the
initial time histories should exhibit directivity effects.
When three sets of time histories are used in the analy-
sis, the envelope of the spectral acceleration values from
each time history shall be equal to or higher than the tar-
get spectral accelerations. If the envelope values fall
below the target values, adjustments shall be made to
ensure that the spectral acceleration envelope is higher
than target spectral accelerations. If the envelope is not
higher, then a justification shall be provided.
When seven or more sets of time histories are used, the
average of the spectral acceleration values from the set
of time histories shall be equal or higher than the target
spectral acceleration values. If the average values fall
below the target values, adjustments shall be made to
ensure that average values are higher than the target
spectral accelerations. If this is not the case, then an
explanation for the use ofthese particular spectral accel-
eration values shall be provided.
When three sets of time histories are used in the analysis,
the maximum value of each response parameter shall be
used in the design, evaluation and rehabilitation. When
seven or more sets of time histories are used in the analysis,
the average value of each response parameter may be used.
3103F,5 Mooring loads on vessels.
3103F.5,1 General. Forces acting on a moored vessel may be
generated by wind, waves, current, tidal variations, tsuna-
mis, seiches and hydrodynamic effects of passing vessels.
Forces from wind and current acting directly on the MOT
structure (not through the vessel in the form of mooring and/
or breasting loads) shall be determined in Section 3103F.7.
The vessel's moorings shall be strong enough to hold dur-
ing all expected conditions of surge, current and weather
and long enough to allow adjustment for changes in draft,
drift and tide (2 CCR 2340 (c) (I)) [3.10]. I
3103F,5.2 Wind loads. Wind loads on a vessel, moored at a
MOT , shall be determined using procedures described in
this section. Wind loads shall be calculated for each of the
load cases identified in Section 3105F.2.
3103F.5.2,1 Design wind speed. The design wind speed
is the maximum wind speed of 30- second duration used
in the mooring analysis (see Section 3105F).
3I03F,5,2J.l Operating condition. The operating
condition is the wind envelope in which a vessel may
conduct transfer operations. It is determined from the
mooring analysis (Section 3I05F). Transfer opera-
tions shall cease, at an existing MOT, when the wind
exceeds the maximum velocity of the envelope.
3103F.5.2.1.2 Survival condition. The survival con-
dition is defined as the state wherein a vessel can
remain safely moored at the berth during severe
winds. For new MOTs, the survival condition thresh-
old is the maximum wind velocity, for a 30-second
gust and a 25-year return period, obtained from his-
torical data.
For an existing MOT , a reduced survival condition
threshold is acceptable (see Figure 31F-2-1). If the
wind rises above these levels, the vessel must depart
the berth; it shall be able to depart within 30 minutes
(see 2 CCR 2340 (c) (28)) [3. 10]. \
The 30-second duration wind speed shall be deter-
mined from the annual maximum wind data. Average
annual summaries cannot be used. Maximum wind
speed data for eight directions (45-degree increments)
shall be obtained. If other duration wind data is avail-
able, it shall be adjusted to a 30-second duration, in
accordance with Equation (3.12). The 2 5 -year return
period shall be used to establish the design wind speed
for each direction. Once these wind speeds are estab-
lished for each increment, the highest wind speed shall
be used to determine the mooring/berthing risk classi-
fication, from Table 31F-5-1. In order to simplify the
2010 CALIFORNIA BUILDING CODE
527
MARINE OIL TERMINALS
analysis for barges (or other small vessels), they may
be considered to be solid free-standing walls (Chapter
6 ofASCE 7 [3.11]). This will eliminate the need to
perform a computer assisted mooring analysis.
3103K5,2.2 Wind speed corrections. Wind speed mea-
sured at an elevation of 33 feet (10 meters) above the
water surface, with duration of 30 seconds shall be used
to determine the design wind speed. If these conditions
are not met, the following corrections shall be applied.
The correction for elevation is obtained from the equa-
tion:
m
(3-11)
where:
V^ - wind speed at elevation 33 ft. (10 m.)
Vf, = wind speed at elevation h
h = elevation above water surface of wind data [feet]
The available wind duration shall be adjusted to a
30-second value, using the following formula:
where:
^t = 30 sec = wif^d speed for a 30-second duration
y^ - wind speed over a given duration
C( = conversion factor from Figure 31F-3-3
If wind data is available over land only, the following
equation shall be used to convert the wind speed from
over-land to over-water conditions [3.10]:
V=1.10Vr
(3-13)
where:
V^ = over water wind speed
Vi = over land wind speed
3103F,5,2.3 Static wind loads on vessels. The "Predic-
I I tion of Wind and Current Loads on VLCC's" [3.13] or
the "British Standard Code of Practice for Maritime
I I Structures" [3.14] shall be used to determine the wind
loads for all tank vessels.
Alternatively, wind loads for any type of vessel may be
calculated using the guidelines in Ferritto et al, 1999
I I [3.15].
3103F,5,3 Current loads. Environmental loads induced by
currents at MOTs shall be calculated as specified in this
subsection.
3103E5JJ Design current velocity. Maximum ebb and
flood currents, annual river runoff's and controlled
releases shall be considered when establishing the design
current velocities for both existing and new MOTs.
Local current velocities may be obtained from NOAA
I I [3.16] or other sources, but must be supplemented by
site-specific data, if the current velocity is higher than
1.5 knots.
Site-specific data shall be obtained by real time mea-
surements over a one-year period. If this information is
not available, a safety factor of L2 5 shall be applied to the
best available data until real time measurements are
obtained.
If the facility is not in operation during annual river
runoffs and controlled releases, the current loads may be
adjusted.
Operational dates need to be clearly stated in the defi-
nition of the terminal operating limits (see Section
3102F3.6).
3103F.5,3.2 Current velocity adjustment factors. An
average current velocity (VJ shall be used to compute
forces and moments. If the current velocity profile is
known, the average current velocity can be obtained
from the following equation:
v'=llT]{v^fds
(3-14)
where:
V^ = average current velocity (knots)
T = draft of vessel
v^ = current velocity as a function of depth (knots)
s = water depth measured from the surface
If the velocity profile is not known, the velocity at a
known water depth should be adjusted by the factors pro-
vided in Figure 31F-3-4 to obtain the equivalent average
velocity over the draft of the vessel.
3103E5,3.3 Static current loads. The OCIMF [3.13],
the British Standard [3.14] or the UFC 4-159-03 [3.17]
procedures shall be used to determine current loads for
moored tank vessels.
3103F.5.3.4 Sea level rise (SLR). All MOTs shall con-
sider the predicted SLR over the remaining life of the ter-
minal, due to subsidence or climate change combined
with maximum high tide and storm surge. Consideration
shall include but not be limited to variation in fender
locations, additional berthing loads (deeper draft ves-
sels) and any components near the splash zone.
3103F.5.4 Wave loads. When the significant wave period, Ts,
is greater than 4 seconds (See Section 3 1 05 F 3.1), the trans-
verse wave induced vessel reactions shall be calculated using
a simplified dynamic mooring analysis described below.
The horizontal water particle accelerations shall be cal-
culated for the various wave conditions, taken at the
mid-depth of the loaded vessel draft. The water particle
accelerations shall then be used to calculate the wave exci-
tation forces to determine the static displacement of the ves-
sel. The Froude-Krylov method discussed in Chakrabarti's
Chapter 7 [3.18] may be used to calculate the wave excita-
tion forces, by conservatively approximating the vessel as a
rectangular box with dimensions similar to the actual
528
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
dimensions of the vessel. The horizontal water particle
accelerations shall be calculated for the various wave con-
ditions, taken at the mid-depth of the loaded vessel draft.
The computed excitation force assumes a 90-degree inci-
dence angle with the longitudinal axis of the vessel, which
will result in forces that are significantly greater than the
forces that will actually act upon the vessel from quartering
seas. A load reduction factor may be used to account for the
design wave incidence angle from the longitudinal axis of
the ship. The overall excursion of the vessel shall be deter-
mined for each of the wave conditions by calculating the
dynamic response of the linear spring mass system.
3103E5,5 Passing vessels. When required in Section
3105F.3, the sway and surge forces, as well as yaw moment,
on a moored vessel, due to passing vessels, shall be estab-
lished considering the following:
1. Ratio of length of moored vessel to length of passing
vessel.
2. Distance from moored vessel to passing vessel.
3. Ratio of midship section areas of the moored and
passing vessels.
4. Underkeel clearances of the moored and passing ves-
sels.
5. Draft and trim of the moored vessel and draft of the
passing vessel.
6. Mooring line tensions.
The passing vesseVs speed should take into consideration
the ebb or flood current. Normal operating wind and cur-
rent conditions can be assumed when calculating forces due
to a passing vessel. Either method ofKrieble [3. 19] or Wang
[3.20] may be used to determine forces on a moored vessel.
KriebeVs recent wave tank study improves on an earlier
work ofSeelig [3.21].
3103R5.6 Seiche. The penetration of long period low
amplitude waves into a harbor can result in resonant stand-
ing wave systems, when the wave forcing frequency coin-
cides with a natural frequency of the harbor. The resonant
standing waves can result in large surge motions if this fre-
quency is close to the natural frequency of the mooring sys-
tem. Section 3105F.3.3 prescribes the procedure for the
evaluation of these effects.
3103K5.7 Tsunamis, A tsunami may be generated by an
earthquake or a subsea or coastal landslide, which may
induce large wave heights and excessive currents. The large
wave or surge and the excessive currents are potentially
damaging, especially if there is a tank vessel moored along-
side the MOT wharf.
Tsunamis can be generated either by a distant or near
source. A tsunami generated by a distant source (far field
event) may allow operators to have an adequate warning for
mitigating the risk by depart the MOT and go into deep water
For near-field events, with sources less than 500 miles away,
the vessel may not have adequate time to depart. Each MOT
shall have a ''tsunami plan '* describing what actions will be
performed, in the event of a distant tsunami.
Recent tsunami studies have been completed for both
Southern and Northern California, For the Ports of Los
Angeles and Long Beach, one of those recent studies
focused on near field tsunamis with predicted return periods
of 5,000 to 10,000 years [3.22], These maximum water lev-
els (run-up) would not normally be used for MOT design.
However, because the study also provides actual tidal
records from recent distant tsunamis, it should be used for
design.
The run-up value for Port Hueneme was obtained from an
earlier study by Synolakis et at. [3.23].
Run up-values: Port of Los Angeles and Long Beach = 8ft,
Port Hueneme = 11 ft.
For the San Francisco Bay, a recent study provides the
maximum credible tsunami water levels and current speeds.
These results are deterministic and are based on the most
severe seismic sources that could reasonably impact MOTs
in the San Francisco Bay [3,24]. Table 31F-3-8 provides
values for the marine oil terminal locations within San
Francisco Bay. Water levels could be positive or negative
and current velocities may vary in direction. In order to
determine the maximum run-up at a MOT, the largest values
should be added to the mean high tide. Further details are
available in [3.24].
Loads from tsunami-induced waves can be calculated for
various structural configurations [3.25]. Tsunami wave
heights in shallow water and particle kinematics can also be
obtained. Other structural considerations include uplift and
debris impact,
TABLE 31 F-3-8
TSUNAMI RUN-UP VALUES (ft) AND CURRENT SPEEDS (ft/sec)
IN THE SAN FRANCISCO BAY AREA [AFTER 3.24]
S.F. Bay Locale
Maximum Water
Levels (ft.)
Current Velocity
(ft/sec)
Richmond, outer
7.5
4.9
Richmond, inner
7,9
8.9
Martinez
2.3
1.3
Selby
2.6
1.6
Rodeo
2.6
2.0
Benicia
2.0
1.0
2 n
where:
^vessel = Berthing energy of vessel [ft-lbs]
3103F,6 Berthing Loads,
3103F.6.1 General Berthing loads are quantified in terms
of transfer of kinetic energy of the vessel into potential
energy dissipated by thefender(s). The terms and equations
below are based on those in UFC 4-152-01, "Piers and
Wharves" [3.26]. An alternate procedure is presented in
PIANC [3.27].
Kinetic energy shall be calculated from the following
equation:
(3-15)
2010 CALIFORNIA BUILDING CODE
529
MARINE OIL TERMINALS
W = Total weight of vessel and cargo in pounds [long
tons X 2240]
g = Acceleration due to gravity [32.2 ft/sec^]
V„ = Berthing velocity normal to the berth [ft/sec]
The following correction factors shall be used to modify
the actual energy to be absorbed by the fender system:
■^ fender ~^ b '^n
(3-16)
where:
^fender = Energy to be absorbed by the fender system
Cf, = Berthing Coefficient
Cfn = Effective mass or virtual mass coefficient (see Sec-
tion 3103K6.6)
The berthing coefficient, Q, is given by:
C. =C,C^C,C, (3-17)
where:
Q = Eccentricity Coefficient
Q = Configuration Coefficient
Cg = Geometric Coefficient
Q = Deformation Coefficient
These coefficients are defined in Sections 3103R6.2
through 3 103F.6.5.
The approximate displacement of the vessel (when only
partially loaded) at impact, DT, can be determined from an
I extension of an equation from Gaythwaite [3.28]:
DT= L25DWT(d^,^/dU (3-18)
where:
DWT = Dead Weight Tonnage (in long tons)
^actual = Actual arrival draft of the vessel
d,^ = Maximum loaded vessel draft
The berthing load shall be based on the fender reaction
due to the kinetic berthing energy. The structural capacity
shall be established based on allowable concrete, steel or
timber properties in the structural components, as defined
in Section 3107F.
3103F,6J Eccentricity coefficient (CJ, During the berth-
ing maneuver, when the vessel is not parallel to the berthing
line (usually the wharf face), not all the kinetic energy of the
vessel will be transmitted to the fenders. Due to the reaction
from the fender(s), the vessel will start to rotate around the
contact point, thus dissipating part of its energy. Treating
the vessel as a rigid rod of negligible width in the analysis of
the energy impact on the fenders leads to the equation:
C =
a'^e
(3-19)
where:
k = Longitudinal radius of gyration of the vessel [ft]
a = Distance between the vessel's center of gravity
and the point of contact on the vessel's side, pro-
jected onto the vessel's longitudinal axis [ft]
3103F.63 Geometric coefficient (Cg), The geometric coef-
ficient, Cg, depends upon the geometric configuration of the
ship at the point of impact. It varies from 0.85 for an increas-
ing convex curvature to 1,25 for concave curvature. Gener-
ally, 0.95 is recommended for the impact point at or beyond
the quarter points of the ship, and 1.0 for broadside berth-
ing in which contact is made along the straight side [3.26],
3103F.6 A Deformation coefficient (CJ. This accounts for the
energy reduction effects due to local deformation of the ships
hull and deflection of the whole ship along its longitudinal
axis. The energy absorbed by the ship depends on the relative
stiffness of the ship and the obstruction. The deformation coef-
ficient varies from 0.9 for a nonresilient fender to nearly 1.0 for
a flexible fender. For larger ships on energy-absorbing fender
.systems, little or no deformation of the ship takes place; there-
fore, a coefficient of 1,0 is recommended.
3103F,6.5 Configuration coefficient (CJ. This factor
accounts for the difference between an open pier or wharf
and a solid pier or wharf. In theflrst case, the movements of
the water surrounding the berthing vessel is not (or is
hardly) affected by the berth. In the second case, the water
between the berthing vessel and the structure introduces a
cushion effect that represents an extra force on the vessel
away from the berth and reduces the energy to be absorbed
by the fender system.
For open berth and corners of solid piers, C^^ 1.0
For solid piers with parallel approach, C^ = 0.8
For berths with different conditions, Q may be interpo-
lated between these values [3.26].
3103R6,6 Effective mass or virtual mass coefficient (CJ.
In determining the kinetic energy of a berthing vessel, the
effective or the virtual mass is the sum of vessel mass and
hydrodynamic mass. The hydrodynamic mass does not nec-
essarily vary with the mass of the vessel, but is closely
related to the projected area of the vessel at right angles to
the direction of motion.
Other factors, such as the form of vessel, water depth,
berthing velocity, and acceleration or deceleration of the
vessel, will have some effect on the hydrodynamic mass.
Taking into account both model and prototype experiments,
the effective or virtual mass coefficient can be estimated as:
C =1 + 2-
d.
B
(3-20)
where:
d actual - Actual arrival draft of the vessel
B = Beam of vessel
The value of C^ for use in design should be a minimum of
1.5 and need not exceed 2,0 [3.26],
3 1 03 F,6.7 Berthing velocity and angle. The berthing veloc-
ity, V^, is influenced by a large number of factors such as envi-
ronmental conditions of the site (wind, current and wave).
530
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
•
method of berthing (with or without tugboat assistance), con-
dition of the vessel during berthing (ballast or fully laden)
and human factors (experience of the tugboat captain).
The berthing velocity, normal to berth, shall be in accor-
dance with Table 31F-3-9, for existing berths. Site condition
is determined from Table 31F-3-I0. For new berths, the
berthing velocity, V„, is established according to Table 4.2.1
of the PIANC guidelines [3.27].
Subject to Division approval, if an existing MOT can dem-
onstrate lower velocities by velocity monitoring equipment,
then such a velocity may be used.
In order to obtain the normal berthing velocity, V„, an
approach angle, defined as the angle formed by the fender
line and the longitudinal axis of the vessel must be deter-
mined. The berthing angles, used to compute the normal
berthing velocity, for various vessel sizes are shown in Table
31F-3-1L
TABLE 31 F'3'11
MAXIMUM BERTHING ANGLE
VESSEL SIZE (DVn)
ANGLE [degrees]
Barge
15
< 10,000
10
10,000-50,000
8
> 50,000
6
3103FJ Wind And current loads on structures.
3103F.7.1 General This section provides methods to deter-
mine the wind and current loads acting on the structure
directly, as opposed to wind and current forces acting on the
structure from a moored vessel.
3103E7.2 Windloads. Chapter6ofASCE7[3.11] shallbe
used to establish minimum wind loads on the structure.
Additional information about wind loads may be obtained
from Simiu and Scanlan [3.29]. I
3103F,7,3 Current loads. The current forces acting on the
structure may be established using the current velocities,
per Section 3103F.5.3.
3103F,8 Load combinations. As a minimum, each compo- \
nent of the structure shall be analyzed for all applicable
load combinations given in Table 31F-3-12 or 31F-3-13,
depending on component type. For additional load combi-
nations see "Piers and Wharves," DOD UFC 4-152-01
[3.26].
The ''vacant condition " is the case wherein there is no ves-
sel at the berth. The "mooring and breasting condition''
exists after the vessel is securely tied to the wharf. The "berth-
ing condition'' occurs as the vessel impacts the wharf, and
the "earthquake condition " assumes no vessel is at the berth,
and there is no wind or current forces on the structure.
The use of various load types is discussed below:
3103 F,8J Dead load (D). Upper and lower bound values of
dead load are applied for the vacant condition to check the
maximum moment and shear with minimum axial load.
3103F.8.2 Live load (L), The live load on MOTs is typically
small and is therefore neglected for combinations including
earthquake loads.
3103F.83 Buoyancy load (B). Buoyancy forces shall be
considered for any submerged or immersed substructures
(including pipelines, sumps and structural components).
3103F.8.4 Wind (W) and current (C) on the structure. Wind
and currents on the vessel are included in the mooring and
breasting condition. The wind and current loads acting on the
structure are therefore additional loads that can act simulta-
neously with the mooring, breasting and/or berthing loads.
TABLE 31 F-3'9
BERTHING VELOCITY V„ (NORMAL TO BERTH)
VESSEL SIZE (dwt)
TUG BOAT ASSISTANCE
SITE CONDITIONS
Unfavorable
Moderate
Favorable
< 10,000'
No
1.31 ft/sec
0.98 ft/sec
0.53ft/sec
10,000 - 50,000
Yes
0.78 ft/sec
0.66 Mec
0,33 ft/sec
50,000 '100,000
Yes
0.53 ft/sec
0.39 ft/sec
0.26 ft/sec
> 100,000
Yes
0.39 ft/sec
0.33 ft/sec
0.26 ft/sec
1. If tug boat is used for vessel size smaller than 10,000 DWT the berthing velocity maybe reduced by 20%
TABLE 31 F-3'10
SITE CONDITIONS
SITE CONDITIONS
DESCRIPTION
WIND SPEED^
SIGNIFICANT WAVE HEIGHT
CURRENT SPEElf
Unfavorable
Strong Wind
Strong Currents
High Waves
> 38 knots
> 6.5 ft
> 2 knots
Moderate
Strong Wind
Moderate Current
Moderate Waves
> 38 knots
< 6.5 ft
< 2 knots
Favorable
Moderate Wind
Moderate Current
Moderate Waves
< 38 knots
< 6.5 ft
< 2 knots
1. A 30-second duration measured at a height of 33 ft.
2. Taken at 0.5 x water depth
2010 CALIFORNIA BUILDING CODE
531
MARINE OIL TERMINALS
II
TABLE 31 F-3-12
LRFD LOAD FACTORS FOR LOAD COMBINATIONS [3.26]
LOAD TYPE
VACANT CONDITION
MOORING & BREASTING
CONDITION
BERTHING CONDITION
EARTHQUAKE CONDITIOhP
Dead Load (D)
L2
0.9
L2
1.2
1.2 + k^
0.9-k^
Live Load (L)
1.6
L6'
1.0
1.0
Buoyancy (B)
L2
0.9
L2
1.2
1.2^
0.9^
Wind on Structure (W)
L6
L6
L6
1.6
Current on Structure (C)
L2
0.9
1.2
1.2
J.2
0.9
Earth Pressure on the Structure (H)
L6
L6
L6
1.6
I.C
1.6^
Mooring/Breasting Load (M)
L6
Berthing Load (BJ
L6
Earthquake Load (E)
—
—
—
LO
1.0
1 . k = 0.50 (PGA) The k factor (k=0.5(PGA)) and buoyancy (B) shall be applied to the vertical dead load (D) only and not to the inertial mass of the structure.
2. The load factor for live load (L) may be reduced to 1.3 for the maximum outrigger float load from a truck crane.
3. For Level 1 and 2 earthquake conditions with strain levels defined in Division 7, the current on structure (C) may not be required.
4. An earth pressure on the Structure factor (H) of 1.0 may be used for pile or bulkhead structures.
TABLE 31F-3-13
SERVICE OR ASD LOAD FACTORS FOR LOAD COMBINATIONS [3.26]
LOAD TYPE
VACANT
CONDITION
MOORING & BREASTING
CONDITION
BERTHING
CONDITION
EARTHQUAKE
CONDITION
Dead Load (D)
1.0
1.0
1.0
l + OJk^
l-0.7k^
Live Load (L)
LO
LO
0.75
Buoyancy (B)
1.0
LO
1.0
LO
0.6
Wind on Structure (W)
1.0
1.0
0.75
Current on Structure (C)
LO
LO
LO
Earth Pressure on the structure (H)
1.0
LO
1.0
LO
1.0
Mooring/Breasting Load (M)
LO
Berthing Load (Be)
LO
Earthquake Load (E)
0.7
0.7
% Allowable Stress
100
100
100
100^
1. k = 0.5 (PGA)
2. Increase in allowable stress shall not be used with these load combinations unless it can be demonstrated that such increase is justified by structural behavior
caused by rate or duration of load. See ASCE 7 [3.111
3103KS.5 Earth pressure on the structure (H). The soil
pressure on end walls, typically concrete cut-off walls, steel
sheet pile walls on wharf type structures and/or piles shall
be considered.
3103K8,6 Mooring line/breasting loads (M). Mooring line
and breasting loads can occur simultaneously or individu-
ally, depending on the combination of wind and current.
Multiple load cases for operating and survival conditions
may be required (see Sections 3103E5.2 and 3105F.2). In
addition, loads caused by passing vessels shall be consid-
ered for the ''mooring and breasting condition.'' Refer to
Sections 3105F.2 and 3105F.3 for the determination of
mooring line and breasting loads,
3103F,8 J Berthing load (BJ. Berthing is a frequent occur-
rence, and shall be considered as a normal operating load.
No increase in allowable stresses shall be applied for ASD,
and a load factor of 1.7 shall be applied for the LRFD
approach.
3103K8,8 Earthquake loads (E), In LRFD or perfor-
mance based design, use a load factor of LO; for ASD use
0. 7. A load factor ofl. shall be assigned to the earthquake
loads. Performance based seismic analysis methodology
requires that the actual force demand be limited to defined
strains in concrete, steel and timber. For the deck and pile
evaluation, two cases of dead load (upper and lower
bound) shall be considered in combination with the seis-
mic load.
3I03F.9 Safety factors for mooring lines. Safety factors for
different material types of mooring lines are given in Table
3IF-3-14. The safety factors should be applied to the minimum
number of lines specified by the mooring analysis, using the
highest loads calculated for the environmental conditions. The
minimum breaking load (mbl) of new ropes is obtained from the
certificate issued by the manufacturer. If nylon tails are used in
combination with steel wire ropes, the safety factor shall be
based on the weaker of the two ropes.
3103F.I0 Mooring hardware. Marine hardware consists of
quick release hooks, other mooring fittings and base bolts. The
certificate issued by the manufacturer normally defines the
allowable working loads of this hardware.
532
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
TABLE 31 F-3'14
SAFETY FACTORS FOR ROPES*
Steel Wire Rope
1.82
Nylon
2.2
Synthetic
2.0
Polyester Tail
2.3
Nylon Tail
2.5
^From Mooring Equipment Guidelines', OCIMF[3.27]
3103FJ0.1 Quick release hooks. For new MOTs or Berth-
ing Systems, a minimum of three quick-release hooks are
required for each breasting line location for tankers larger
than 50,000 DWT. At least two hooks at each location shall
be provided for breasting lines for tankers less than 50,000
DWT,
All hooks and supporting structures shall withstand the
minimum breaking load (MBL) of the strongest line with a
safety factor of 1,2 or greater. Only one mooring line shall
be placed on each quick release hook.
For multiple quick release hooks, the minimum horizontal
load for the design of the tie-down shall be:
F,= 1.2xMBLx[l-\'0.75(n~l)]
(3-21)
Fj = Minimum factored demand for assembly
tie-down.
n = Number of hooks on the assembly.
The capacity of the supporting structures must be larger
than F^ (See Section 3107F4.3).
3 103 F. 10,2 Other Fittings, Other fittings include cleats,
bitts and bollards.
If the allowable working loads for existing fittings are not
available, the values listed in Table 31F-3-15 may be used
for typical sizes, bolt patterns and layout. The allowable
working loads are defined for mooring line angles up to 60
degrees from the horizontal. The combination of vertical
and horizontal loads must be considered,
TABLE 31F-3-15
ALLOWABLE WORKING LOADS
TYPE OF FITTINGS
NO. OF BOLTS
BOLT SIZE (in)
WORKING
LOAD (kips)
30 in. Cleat
4
1%
20
42 in. Cleat
6
1%
40
Lx)w Bitt
10
1%
60 per column
High Bitt
10
1%
75 per column
44 V2 in. Fit. Bollard
4
1%
70
44 V2 in. Fit. Bollard
8
2'U
200
48 in. Fit. Bollard
12
2%
450
Note: This table is modified from Table 6-11, UFC 4-159-03 [3.17]
3103FJ0.3 Base holts. Base bolts are subjected to both
shear and uplift. Forces on bolts shall be determined using
the following factors:
1, Height of load application on bitts or bollards.
2. Actual vertical angles of mooring lines for the highest
and lowest tide and vessel draft conditions, for all
sizes of vessels at each particular berth,
3. Actual horizontal angles from the mooring line con-
figurations, for all vessel sizes and positions at each
particular berth.
4. Simultaneous loads from more than one vessel.
For existing MOTs, the deteriorated condition of the base
bolts and supporting members shall be considered in deter-
mining the capacity of the fitting,
3103F.11 Miscellaneous loads. Handrails and guardrails
shall be designed for 25 plfwith a 200-pound minimum con-
centrated load in any location or direction,
3103FJ2 Symbols.
a = Distance between the vessel 's center of gravity and
the point of contact on the vessel's side, projected
onto the vessel's longitudinal axis [ft]
B = Beam of vessel
Bj - Coefficient used to adjust one-second period spectral
response, for the effect of viscous damping
B^ = Coefficient used to adjust the short period spectral
response, for the effect ofvisous damping.
Ci^ = Berthing Coefficient
C^ - Configuration Coefficient
Cg = Geometric Coefficient
Q = Deformation Coefficient
Q = Eccentricity Coefficient
C^ = Effective mass or virtual mass coefficient
Cf = Windspeed conversion factor
DSA = Design Spectral Acceleration
DSA^ = DSA values at damping other than 5 percent
DT = Displacement of vessel
DWT = Dead weight tons
^actual ~ Arrival maximum draft of vessel at berth
^max = Maximum vessel draft (in open seas)
^fender = Energy to be absorbed by the fender system
^vessel - Berthing energy of vessel [ft-lbs]
F^ F^ = Site coefficients from Tables 31F-3-5 and 31F-3-6
g - Acceleration due to gravity [32.2 ft/sec^]
h = Elevation above water surface [feet]
K = Current velocity correction factor (Fig 3IF-3-4)
k = Radius of longitudinal gyration of the vessel [ft]
PGAx = Peak ground acceleration corresponding to the Site
Class under consideration,
s = Water depth measured from the surface
S^ = Spectral acceleration
Sj ~ Spectral acceleration value (for the boundary of Sg
and SJ at 1,0 second
2010 CALIFORNIA BUILDING CODE
533
MARINE OIL TERMINALS
T
T
To
S^-Sf = Site classes as defined in Table 31F-6-I
Ss = Spectral acceleration value (for the boundary of S^
and S J at 0.2
Sxi = Spectral acceleration value at 1.0 second corre-
sponding to the Site Class under consideration
Sxs = Spectral acceleration value at 0.2 second corre-
sponding to the period ofSg and the Site Class under
consideration
= Draft of vessel (see Fig 31F-3-4)
= Period (Sec)
= Period at which the constant acceleration and con-
stant velocity regions of the design spectrum intersect
Vc - Average current velocity [knots]
Vc = Current velocity as a function of depth [knots]
Vf, - Wind speed (knots) at elevation h
Vi - Over land wind speed
V„ = Berthing velocity normal to the berth [ft/sec]
Vf = Velocity over a given time period
^t=30sec - Wind speed for a 30 second interval
V^ - Wind speed at 33ft. (10 m) elevation [knots]
W = Total weight of vessel and cargo inpounds [displace-
ment tonnage x 2240]
WD = Water Depth (Fig 3 lF-3-4)
3103E13 References,
[3.1] Federal Emergency Management Agency, FEMA
-356, Nov. 2000, '' Prestandard and Commentary
for the Seismic Rehabilitation of Buildings, " Wash-
ington, D.C.
California Geological Survey, 2003, ''Seismic
Shaking Hazards in California, " Sacramento, CA.
Idriss, I.M., August 1985, ''Evaluating Seismic Risk
in Engineering Practice, "Proceedings, Theme Lec-
ture No. 6, XI International Conference on Soil
Mechanics and Foundation Engineering, San Fran-
cisco, CA, vol. I, pp. 255-320.
Southern California Earthquake Center (SCEC),
March 1999, "Recommended Procedures for
Implementation of DMG Special Publication 117
Guidelines for Analyzing and Mitigating Liquefac-
tion in California, " University of Southern Califor-
nia, Los Angeles.
Earth Mechanics, Inc., "Port-Wide Ground Motion
and Palos Verdes Fault Study - Port of Los Angeles,
California, FINAL REPORT, '' December 22, 2006,
Fountain Valley, CA.
Earth Mechanics, Inc., "Port-Wide Ground Motion
Study - Port of Long Beach, California, FINAL
REPORT, " August 7, 2006, Fountain Valley, CA.
Savy, J. and Foxall, W, 2002, "Probabilistic Seis-
mic Hazard Analysis for Southern California
[3.2]
[3.3]
[3.4]
[3.5]
[3.6]
[3.7]
Coastal Facilities," 2003, Lawrence Livermore
National Laboratory.
[3.8] Idriss, LM. and Sun, J. 1, 1992, "User's Manual for
SHAKE91, A Computer Program for Conducting
Equivalent Linear Seismic Response Analyses of
Horizontally Layered Soil Deposits, " Center for
Geotechnical Modeling, Department of Civil and
Environmental Engineering, University of Califor-
nia, Davis, CA.
[3,9] Somerville, Paul G, Smith, Nancy F., Graves, Rob-
ert W., and Abrahamson, Norman A., 1997, "Modi-
fication of Empirical Strong Ground Motion
Attenuation Relations to Include the Amplitude and
Duration Effects of Rupture Directivity, " Seismo-
logical Research Letters, Volume 68, Number 1,
pp. 199-222.
[3.10] California Code of Regulations, "Marine Termi-
nals, Inspection and Monitoring, " Title 2, Division
3, Chapter 1, Articles. California State Lands Com-
mission, Sacramento, CA.
[3.11] American Society of Civil Engineers, Jan. 2000,
"Minimum Design Loads for Buildings and Other
Structures,'' ASCE 7-98, Revision of ANSI/ASCE
9-95, Reston, VA.
[3.12] Pile Buck Production, 1992, "Mooring Systems,"
Pile Buck Inc., Jupiter, Florida.
[3.13] Oil Companies International Marine Forum
(OCIMF), 1977, "Prediction of Wind and Current
Loads on VLCCs, " London, England.
[3A4] British Standards Institution, 2000, "British Stan-
dard Code of Practice for Maritime Structures -
Part 1. General Criteria" BS6349, Part 1, London,
England.
[3.15] Ferritto, J., Dickenson, S., Priestley N., Werner, S.,
Taylor, C, Burke D., Seelig W., and Kelly, S., 1999,
"Seismic Criteria for California Marine Oil Termi-
nals, " Vol. I and Vol. 2, Technical Report
TR-2103-SHR, Naval Facilities Engineering Ser-
vice Center, Port Hueneme, CA.
[3.16] National Oceanic and Atmospheric Administration,
Contact: National PORTS Program Manager, Cen-
ter for Operational Oceanographic Products and
Services, 1305 EW Highway, Silver Spring, MD
20910.
[3.17] Dept. of Defense, 3 October 2005, Unified Facilities
Criteria (UFC) 4-159-03 "Moorings," Washing-
ton, D.C.
[3.18] Chakrabarti, S. K., 1987, "Hydrodynamics of Off-
shore Structures, " Computational Mechanics.
[3.19] Kriebel, David, "Mooring Loads Due to Parallel
Passing Ships", Technical Report TR-6056-OCN,
US Naval Academy, 30 September 2005.
[3.20] Wang, Shen, August 1975, "Dynamic Effects of Ship
Passage on Moored Vessels, " Journal of the Water-
ways, Harbors and Coastal Engineering Division,
534
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
m
Proceedings of the American Society of Civil Engi-
neers, Vol 101 WW3, Reston, VA.
[3.21] Seelig, William N., 20 November 2001, ''Passing
Ship Effects on Moored Ships, " Technical Report
TR-6027-OCN, Naval Facilities Engineering Ser-
vice Center, Washington, D.C
[3,22] Moffatt Sl Nichol, April 2007, 'Tsunami Hazard
Assessment for the Ports of Long Beach and Los
Angeles - FINAL REPORT", prepared for the Ports
of Long Beach and Los Angeles,
[3.23] Synolakis, C, "Tsunami and Seiche, " Chapter 9 in
Earthquake Engineering Handbook, Chen, W.,
Scawthom, C. S. and Arros, J. K., editors, 2002,
CRC Press, Boca Raton, FL
[3.24] Borrero, Jose, Dengler, Lori, Uslu, Burak and
Synolakis, Costas, June 2006, "Numerical Model-
ing of Tsunami Effects at Marine Oil Terminals in
San Francisco Bay, " Report for the Marine Facili-
ties Division of the California State Lands Commis-
sion.
[3.25] Camfield, Frederick E., February 1980, "Tsunami
Engineering, " U.S. Army, Corps of Engineers,
Coastal Research Center, Special Report No. 6.
[3.26] Dept. of Defense, "Piers and Wharves," Unified
Facilities Criteria (UFC) 4-152-01, 28 July 2005,
Washington, D. C.
[3.27] Permanent International Association of Navigation
Congresses (PIANC), 2002, "Guidelines for the
Design of Fender Systems: 2002, " Brussels.
[3.28] Gaythwaite, John, 2004, "Design of Marine Facili-
ties for the Berthing, Mooring and Repair of Ves-
sels, " American Society of Civil Engineers, Reston,
VA.
[3.29] Simiu E. and Scanlan R., 1978, "Wind Effects on
Structures: An Introduction to Wind Engineering, "
Wiley-Interscience Publications, New York.
[3.30] Oil Companies International Marine Forum
(OCIMF), 1997, "Mooring equipment Guidelines, "
2nded., London, England.
Authority: Sectic ns 8755 and 8757, Public Resources Code.
Reference: Sections 8750,8751,8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE 535
MARINE OIL TERMINALS
Division 4
SECTION 31 04F
SEISI\/liC ANALYSIS AND STRUCTURAL
PERFORMANCE
3104FJ General
3104F,1J Purpose, The purpose of this section is to estab-
lish minimum standards for seismic analysis and structural
performance. Seismic performance is evaluated at two cri-
teria levels. Level 1 requirements define a performance cri-
terion to ensure MOT functionality. Level 2 requirements
safeguard against major structural damage or collapse.
3104FJ,2 Applicability, Section 3104F applies to all new
and existing MOTs structures. Structures supporting load-
ing arms, pipelines, oil transfer and storage equipment,
critical nonstructural systems and vessel mooring struc-
tures, such as mooring and breasting dolphins are included.
Catwalks and similar components that are not part of the
lateral load carrying system and do not support oil transfer
equipment may be excluded.
3104F.L3 Oil spill risk classification. Each existing MOT
shall be catagorized into one of three risk classifications
(high, medium or low) as shown in Table 31F-4-1, based on
the highest of the following:
L Exposed total volume of oil during transfer ( ''total
volume" as calculated in Section 3108F.2.3)
2. Number of oil transfer operations per berthing system
per year
3. Maximum vessel size (DWT) that may call at the
berthing system
If risk reduction strategies (see Section 3101 K5) are
adopted such that the maximum volume of exposed oil dur-
ing transfer is less than 1,200 barrels, the classification
level of the facility may be lowered. All new MOTs are clas-
sified as high risk.
3104FJ,4 Configuration classification. Each MOT shall
be designated as regular or irregular, in accordance with
Figure 31F-4-L
Irregular configurations, such as the 'T" layout, may be
analyzed as regular if the presence of expansion joints divides
the T-configuration into two or more regular segments.
Expansion joints in this context are defined as joints that sep-
arate each structural segment in such a manner that each seg-
ment will move independently during an earthquake.
If an irregular MOT is divided into seismically isolated
sections, an evaluation of the relative movement of pipelines
"T" teydut
IRREGULAR
ECZ
"Island wfT^rf*
RSGUUR
t5i
IRREGULAR
*Margfrtal wharf
REaytAH:
*yaf gsfiai wharf"
■L
IRREGUUR
IRREGULAR
FIGURE 31 F-4'1
PIER AND WHARF CONFIGURATIONS
and supports shall be considered, including phase differ-
ences (Section 3109F3).
3104F.2 Existing MOTs
3104F.2,1 Design earthquake motions. Two levels of
design seismic performance shall be considered. These lev-
els are defined as follows:
Level 1 Seismic performance:
• Minor or no structural damage
o Temporary or no interruption in operations
Level 2 Seismic performance:
• Controlled inelastic structural behavior with
repairable damage
• Prevention of structural collapse
m Temporary loss of operations, restorable within
months
• Prevention of major spill (> 1200 bbls)
3104F,2,2 Basis for evaluation. Component capacities shall
be based on existing conditions, calculated as ''best esti-
mates," taking into account the mean material strengths,
strain hardening and degradation overtime. The capacity of
components with little or no ductility, which may lead to brit-
tle failure scenarios, shall be calculated based on lower
bound material strengths. Methods to establish component
strength and deformation capacities for typical structural
TABLE 31F-4-1
MOT RISK CLASSIFICATION
RISK CLASSIFICATION
EXPOSED OIL (bbls)
TRANSFERS PER YEAR PER
BERTHING SYSTEM
MAXIMUM VESSEL SIZE (DWTxIOOO)
High
>I200
NA.
NA.
Medium
<1200
>90
>30
Low
<}200
<90
<30
536
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
materials and components are provided in Section 3107E
Geotechnical considerations are discussed in Section 3106F.
3104E2.3 Analytical procedures. The objective of the seis-
mic analysis is to verify that the displacement capacity of the
structure is greater than the displacement demand, for each
performance level defined in Table 31F-4-2. The required
analytical procedures are summarized in Table 31F-4-3.
The displacement capacity of the structure shall be calcu-
lated using the nonlinear static (pushover) procedure. It is
also acceptable to use a nonlinear dynamic procedure for
capacity evaluation. Methods used to calculate the dis-
placement demand are linear modal, nonlinear static and
nonlinear dynamic.
Any rational method, subject to the division 's approval,
can be used in lieu of the required analytical procedures
shown in Table 31F-4-3.
3104F,2,3J Nonlinear static capacity procedure (push-
over). Two-dimensional nonlinear static (pushover)
analyses shall be performed; three-dimensional analy-
ses are optional A model that incorporates the nonlinear
load deformation characteristics of all components for
the lateral force-resisting system shall be displaced to a
target displacement to determine the internal deforma-
tions and forces. The target displacement depends on the
seismic performance level under consideration. Model-
ing details are as follows:
3104F.2.3d*l Modeling, A series of nonlinear push-
over analyses may be required depending on the com-
plexity of the MOT structure. At a minimum, pushover
analysis of a two-dimensional model shall be con-
ducted in both the longitudinal and transverse direc-
tions. The piles shall be represented by nonlinear
elements that capture the moment-curvature/rotation
relationships for components with expected inelastic
behavior in accordance with Section 3107F A nonlin-
ear element is not required to represent each pile
location. Piles with similar lateral force-deflection
behavior may be lumped in fewer larger springs,
provided that the overall torsional ejfects are cap-
tured.
Linear material component behavior is acceptable
where nonlinear response will not occur All compo-
nents shall be based on effective moment of inertia
calculated in accordance with Section 3107F. Spe-
cific requirements for timber pile structures are dis-
cussed in the next section.
3104E2JJ,2 Timber pile supported structures. For
all timber pile supported structures, linear elastic
procedures may be used. Alternatively, the nonlinear
static procedure may be used to estimate the target
displacement demand, A^.
A simplified single pile model for a typical timber pile
supported structure is shown in Figure 31F-4-2. The
pile-deck connections may be assumed to be ''pinned."
The lateral bracing can often be ignored if it is in poor
condition. These assumptions shall be used for the anal-
ysis, unless a detailed condition assessment and lateral
analysis indicate that the existing bracing and connec-
tions may provide reliable lateral resistance.
•^on^Jar^
As-fiulH SlTiidiiFis
yeat!^ Pie ymi^
FIGURE 31 F-4-2— SIMPLIFIED SINGLE PILE MODEL OF A
TIMBER PILE SUPPORTED STRUCTURE
TABLE 31F-4-2
SEISMIC PERFORMANCE CRITERIA
RISK CLASSIFICATION
SEISMIC PERFORMANCE LEVEL
PROBABILITY OF EXCEEDANCE
RETURN PERIOD
High
Level 1
50% in 50 years
72 years
Level!
10% in 50 years
475 years
Medium
Level 1
65% in 50 years
48 years
Level 2
15% in 50 years
308 years
Low
Level I
75% in 50 years
36 years
Level 2
20% in 50 years
224 years
TABLE 31 F-4-3
MINIMUM REQUIRED ANALYTICAL PROCEDURES
RISK CLASSIFICATION
CONFIGURATION
SUBSTRUCTURE MATERIAL
DISPLACEMENT DEMAND
PROCEDURE
DISPLACEMENT CAPACITY
PROCEDURE
High/Medium
Irregular
Concrete/Steel
Linear Modal
Nonlinear Static
High/Medium
Regular
Concrete/Steel
Nonlinear Static
Nonlinear Static
Low
Regular/Irregular
Concrete/Steel
Nonlinear Static
Nonlinear Static
High/Medium/Low
Regular/Irregular
Timber
Nonlinear Static
Nonlinear Static
2010 CALIFORNIA BUILDING CODE
537
MARINE OIL TERMINALS
A series of single pile analyses may be sufficient to
establish the nonlinear springs required for the push-
over analysis,
3104F,2.3A,3 Soil-structure interaction (SSI).
Load-deformation characteristics for foundations
shall be modeled as per Section 3106F.5. Selection of
soil springs shall be based on the following:
L Effect of the large difference in up and down
slope stiffnesses for wharf type structures
2. Effect of upper and lower bound soil parame-
ters, especially for t-z curves used to model bat-
ter pile behavior
A separate analysis that captures the demand (Section
3104F.2.3.2) on the piles due to permanent ground
deformations, at embankments only, shall be performed,
ffa simplified methodology is followed, the piles need
to be checked for the following load combinations:
L0H,^0.25E,^,,,,,
where:
^inertiai = Incrtlal sclsmlc load
H^ - Foundation deformation load
3104F.2.3.2 Nonlinear static demand procedure, A
nonlinear static procedure shall be used to determine the
displacement demand for all concrete and steel struc-
tures, with the exception of irregular configurations with
high or moderate seismic risk classifications. The fol-
lowing Sections (3104E2.3.2.1 through 3104F2.3.4)
describe the procedure of Priestly et al. [4.1]; an alter-
nate procedure is presented in ATC 40 [4.2], which is
improved in FEMA 440 [4.3]. A linear modal procedure
is requiredfor irregular structures with high or moderate
seismic risk classifications, and may be used for all other
classifications in lieu of the nonlinear static procedure.
3104F.23.2.1 Lateral stiffness. The lateral stiffness, k,
is calculated from the force-displacement relation as
the total base shear, Vy, corresponding to the yield dis-
placement of the structure A^ Ay is the displacement at
first yield in the pile/deck connection reinforcement.
3104F,2.3.2.2 Structural period. The fundamental
period, T, of the structure in the direction under con-
sideration shall be calculated as follows:
T^l^Jf
(4-1)
where.
m
k
= mass of structure in kips/g
= stiffness in direction under consideration in
kips/ft
g = gravity, 32 ft/sec^ (9.8 meters/sec^)
3104F,2.3.2.3 Target displacement demand. The
target displacement demand of the structure, Ad,
can be calculated by multiplying the spectral
response acceleration, 5^, corresponding to the
period, T, by V-/4%^.
A. =5,
Alt'
(4-2)
IfT < Tq, where Tq is the period corresponding to the
peak of the acceleration response spectrum, a refined
analysis (see Section 3104F.2.3.2.5) shall be used to
calculate the displacement demand. Multidirectional
excitation shall be addressed per Section 3104F.4.2.
3104F.23,2A Damping, The displacement demand
established in Section 3104F2.3.2.3 is based on 5
percent damping. Higher damping values obtained
from a refined analysis may be used to calculate the
displacement demand.
31 04F,2,3,2, 5 Refined analyses. Refined displacement
demand analyses may be calculated as per Chapters 4
and 5 of [4.1] and is briefiy summarized below.
1 ' Determine A^ , from Section 3 1 04F.2. 3. 2. 3.
2. From the nonlinear pushover analysis, deter-
mine the structural yield displacement A^.
3. The ductility level, \i^ is found from A^/A_y. Use
the appropriate relationship between ductility
and damping, for the component undergoing
inelastic deformation, to estimate the effective
structural damping, ^^^ In lieu of more de-
tailed analysis, the relationship shown in Fig-
ure 31F-4-3 or equation (4-3) may be used for
concrete and steel piles connected to the deck
through dowels embedded in the concrete.
^.^=0.05 +
n
1-
1-
--y\
(4-3)
where:
- ratio of second slope over elastic slope
(see Fisure 31F-4-5)
049
m^
xo
FIGURE 31 F-4-3
RELATION BETWEEN DUCTILITY, ^a,
AND EFFECTIVE DAMPING, ^eff [4.1]
538
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
4, From the acceleration response spectra, cre-
ate elastic displacement spectra, Sq, using
equation (4-4) for various levels of damping.
So =
Atz
r^.
(4-4)
II
A'
k
A
Ad
J
f
i
1
i
H Period T
FIGURE 31 F-4-4
DESIGN DISPLACEMENT RESPONSE SPECTRA
5, Using the curve applicable to the effective
structural damping, ^, find the effective pe-
riod, T^ (see Figure 31 F-4-4),
6, In order to convert from a design displace-
ment response spectra to another spectra for
a different damping level, the adjustment fac-
tors in Section 3103F.4.2,9 shall be used,
7, The effective stiffness k^ can then be found from:
k =
An'
M
(4-5)
where:
M = mass ofdeck considered in the analysis.
T^ = effective structural period
8. The required strength F^ can now be esti-
mated by:
F=kA,
(4-6)
9. F^ and A^ can be plotted on the force-displace-
ment curve established by the pushover analy-
sis. Since this is an iterative process, the
intersection ofF^^ and A^ most likely will not
fall on the force -displacement curve and a
second iteration will be required. An adjusted
value of A^ taken as the intersection between
the force-displacement curve and a line be-
tween the origin and F^ and A^, can be used to
find M-A-
10. Repeat the process until a satisfactory solu-
tion is obtained (see Figure 31F-4-5).
2
B
«0
Disptac^nent
FIGURE 31 F-4-5
EFFECTIVE STIFFNESS, ke [4.1]
3104E2,3.3 Linear modal demand procedure. For
irregular concrete/steel structures with moderate or high
risk classifications, a linear analysis is required to pre-
dict the global displacement demands. A 3-D linear elas-
tic response analysis shall be used, with effective moment
of inertia applied to components to establish lateral dis-
placement demands.
Sufficient modes shall be included in the analysis such
that 90 percent of the participating mass is captured in
each of the principal horizontal directions for the struc-
ture. For modal combinations, the complete quadratic
combination rule shall be used. Multidirectional excita-
tion shall be accounted for in accordance with Section
3104F.4.2.
The lateral stiffness of the linear elastic response
model shall be based on the initial stiffness of the nonlin-
ear pushover curve as shown in Figure 31F-4-6 (also see
Section 3106F5.1). The p-y springs shall be adjusted
based on the secant method approach. Most of the p-y
springs will typically be based on their initial stiffness;
no iteration is required.
If the fundamental period in the direction under con-
sideration is less than Tq, as defined in Section
3104F.2,3,2.3, then the displacement demand shall be
amplified as specified in Section 3104F,2.3.2.5.
1
I
FIGURE 31 F-4-6
STIFFNESS FOR LINEAR MODAL ANALYSIS
2010 CALIFORNIA BUILDING CODE
539
MARINE OIL TERMINALS
3104K2.3,4 Nonlinear dynamic analysis. Nonlinear
dynamic time history analysis is optional, and if per-
formed, a peer review is required (see Section
3101F.6.1). Multiple acceleration records shall be used,
as explained in Section 3103F.4.2J0. The following
assumptions may be made:
L Equivalent '' super piles" can represent groups of
piles.
2. If the deck has sufficient rigidity (both in-plane
and out-of plane) to justify its approximation as a
rigid element, a 2-D plan simulation may be ade-
quate.
A time-history analysis should always be compared
with a simplified approach to ensure that results are rea-
sonable. Displacements calculated from the nonlinear
time history analyses may be used directly in design, but
shall not be less than 80 percent of the values obtained
from Section 3104F.2.3.2.
3104F.2.3,5 Alternative procedures. Alternative lat-
eral-force procedures using rational analyses based on
well-established principles of mechanics may be used in
lieu of those prescribed in these provisions. As per Sec-
tion 3101F.6.1, peer review is required.
3104F3 New MOTs, The analysis and design requirements
described in Section 3I04F.2 shall also apply to new MOTs.
Additional requirements are as follows:
1. Site- specific response spectra analysis (see Section
3103F.4.2.3).
2. Soil parameters based on site-specific and new borings
(see Section 3 106F.2.2).
3104E4 General analysis and design requirements,
3104F,4,1 Load combinations. Earthquake loads shall be
used in the load combinations described in Section 3103F.8.
3104F,4,2 Combination of orthogonal effects. The design
displacement demand, A^, shall be calculated by combining
the longitudinal, la^ and transverse, A^, displacements in the
horizontal plane (Figure 31F-4-7):
-4^.
+ A,
where:
= A^+0.3A„
Lii^^Md:
:#' « • 1
■m- m
*
r
tt »
*
m
» ■»
■^^
m
^ 1
♦
m
e
)i 1
Sswwl
Bdp
(a>Pla
avie^
m
(4-7)
(4-8)
(4-9)
(4-10)
(4-11)
and A^ =a3A^, +A^
or
and A^ =A^^+0.3A^
A. =0.3A^+A^
whichever results in the greater design displacement
demand.
In lieu of combining the displacement demands as pre-
sented above, the design displacement demand for marginal
wharf type MOTs may be calculated as:
A, =A^^l + (0.3(l+20./L,))'
(4-12)
where:
Ay = transverse displacement demand
e = eccentricity between center of mass and center of
rigidity
Li = longitudinal length between wharf expansion
This equation is only valid for wharf aspect ratios (length/
breadth) greater than 3.
3104F.4.3 jP-A Effects. The P-A effect (i.e., the additional
moment induced by the total vertical load multiplied by the
lateral deck deflection) shall be considered unless the fol-
lowing relationship is satisfied (see Figure 31F-4-8):
(4-13)
W H
where:
V = base shear strength of the structure obtained from
a plastic analysis
W = dead load of the frame
A^ = displacement demand
H = distance from the location of maximum in- ground
moment to center of gravity of the deck
For wharf structures where the lateral displacement is
limited by almost fully embedded piles y P-A effects may be
ignored; however, the individual stability of the piles shall
be checked in accordance with Section 3107F.2.5.2.
If the landside batter piles are allowed to fail in a Level 2
evaluation, the remaining portion of the wharf shall be
checked for P-A effects.
_J^*' !l- ^ "'"*^ZI^^
FIGURE 31 F-4-7
PLAN VEW OF WHARF SEGMENT UNDER XAND V SEISMIC EXCITA TIONS [4.3]
540
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
iW
4
FIGURE 31 F-4-8
P-A EFFECT
3 104E4,4 Expansion joints. The effect of expansion joints
shall be considered in the seismic analysis.
3104E4,5 Shear key forces. Shear force across shear keys
connecting adjacent wharf segments, V,^, (approximate
upper bound to the shear key force [4.4]) shall be calculated
as follows:
V,,^l5(e/L,)V^r (4-14)
where:
V^j = total segment lateral force found from a push-over
analysis
Li = segment length
e = eccentricity between the center of rigidity and the
center of mass
3104F,4.6 Connections, For an existing wharf, the deterio-
rated conditions at the junction between the pile top and pile
cap shall be considered in evaluating the moment capacity.
Connection detail between the vertical pile and pile cap
shall be evaluated to determine whether full or partial
moment capacity can be developed under seismic action.
For new MOTs, the connection details shall develop the
full moment capacities.
The modeling shall simulate the actual moment capacity
(full or partial) of the joint in accordance with Section
3107F.2. 7.
3104F,4,7 Batter piles. Batter piles primarily respond to
earthquakes by developing large axial compression or ten-
sion forces. Bending moments are generally of secondary
importance. Failure in compression may be dictated by the
deck-pile connection (most common type), material com-
pression, buckling, or by excessive local shear in deck mem-
bers adjacent to the batter pile. Failure in tension may be
dictated by connection strength or by pile pull out. (p. 3-83
of[4A]).
When the controlling failure scenario is reached and the
batter pile fails, the computer model shall be adjusted to
consist of only the vertical pile acting either as a full or par-
tial moment frame based on the connection details between
the pile top and pile cap. The remaining displacement
capacity, involving vertical piles, before the secondary fail-
ure stage develops, shall then be established (see Section
3107F.2.8).
Axial p-z curves shall be modeled. In compression, dis-
placement capacity should consider the effect of the reduc-
tion in pile modulus of elasticity at high loads and the
increase in effective length for friction piles. This proce-
dure allows the pile to deform axially before reaching ulti-
mate loads, thereby increasing the displacement ductility
[4.4]. I I
Horizontal nonlinear p-y springs are only applied to bat-
ter piles with significant embedment, such as for landside
batter piles in a wharf structure. Moment fixity can be
assumed for batter piles that extend well above the ground
such as waterside batter piles in a wharf structure or batter
piles in a pier type structure.
3104F,5 Nonstructural components. Nonstructural compo-
nents including, but not limited to pipelines, loading arms,
raised platforms, control rooms and vapor control equipment
may affect the global structural response. In such cases, the
seismic characteristics (mass and/or stiffness) of the
nonstructural components shall be considered in the structural
analysis.
3104F,5,1 Mass contribution. The weight of permanently
attached nonstructural components shall be included in
the dead load of the structure, per Section 3I03F.2. An
exception is an MOT pipeline that is allowed to slide
between anchor points and hence the pipeline response is
typically out of phase with the structural response. Thus,
the pipeline may be subjected to a different acceleration
than the substructure, even if the pipeline cannot slide
between anchor points. In such cases, the pipeline mass
shall not be included directly in the seismic mass of the
structure.
3104F.5,2 Seismic loads. In general, for nonstructural
components, the evaluation procedures of Section 3I10F.8
are adequate.
For pipelines, the seismic analysis shall be performed in
accordance with Section 3109F.3, in lieu of Section
3II0F.8. If an analysis has been performed and support
reactions are available, they may be used to determine the
forces on the support structure.
A pipeline segment under consideration shall extend
between two adjacent anchor points. A simplified pipeline
analysis may be used when the relative displacement
demands of anchor points are considered. As an option, a
full nonlinear time-history analysis can be used to capture
the nonlinear interaction between the structure and the
pipeline.
3104F,6 Nonstructural critical systems assessment, A seismic
assessment of the survivability and continued operation during
a Level 2 earthquake (see Table 3 IF -4-2) shall be performed
for critical systems such as fire protection, emergency shut-
down and electrical power systems. The assessment shall con-
sider the adequacy and condition of anchorage, flexibility and
seismically -induced interaction. The results shall be included
in the Audit.
3104E,7 Symbols,
e — Eccentricity between center of mass and center of
rigidity
2010 CALIFORNIA BUILDING CODE
541
MARINE OIL TERMINALS
Einertiai = Imrtial seismic load
F„ = Required strength at maximum response
H = Distance from maximum in-ground moment to
center of gravity of the deck
H^ = Foundation deformation load
k = Stiffness in direction under consideration in k/ft
kg = Effective stiffness
Li = Longitudinal length between wharf expansion
joints
m = Mass of structure in kips/g
M = Mass of deck considered in the analysis
r = Ratio of second slope over elastic slope
S^ = Spectral response acceleration, at T
Sj) = Displacement response spectrum, at T
Sap = Spectral response acceleration of pipeline seg-
ment under consideration
T - Fundamental period of structure
T^ = Effective structural period
V = Base shear strength of the structure obtained from
a plastic analysis
Vy = total base shear
VjiT= total segment lateral force
V,i, = Shear force across shear keys
W = Dead load of the frame
Wp = Weight of pipeline segment under consideration
A^ = Design displacement demand
Aj, = Longitudinal displacement demand
Aj^ =X displacement under X direction excitation
Aj^ =X displacement under Y direction excitation
Ay = Transverse displacement demand
Ay^ ~Y displacement under X direction excitation
Ayy ^Y displacement under Y direction excitation
|J,A = Ductility level
^ <9r ^ = Effective structural damping
3104E8 References.
[4.1] Priestley, MJ.N., Sieble, F„ Calvi, GM., 1996,
"Seismic Design and Retrofit of Bridges, *' John Wiley
& Sons, Inc., New York, USA.
[4.2] Applied Technology Council, ATC-40, 1996, "Seis-
mic Evaluation and Retrofit of Concrete Buildings, "
Vols. 1 and 2, Redwood City, CA.
[4.3] Applied Technology Council (ATC-55 Project), June
2005, "FEMA 440 Improvement of Nonlinear Static
Seismic Analysis Procedures, " Redwood City, CA.
[4.4] Ferritto, J., Dickenson, S., Priestley N, Werner, S.,
Taylor, C, Burke D., Seelig W., and Kelly, S., 1999,
"Seismic Criteria for California Marine Oil Termi-
nals, " Vol. 1 and Vol. 2, Technical Report
TR-2103-SHR, Naval Facilities Engineering Service
Center, Port Hueneme, CA.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750,8751,8755 and 8757, Public
Resources Code.
542
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
Division 5
SECTION 3105F
MOORING AND BERTHING ANALYSIS AND DESIGN
3105FJ General,
3 1 05 E 1.1 Purpose* This section establishes minimum stan-
dards for safe mooring and berthing of vessels atMOTs.
3 105 El. 2 Applicability. This section applies to onshore
MOTs; Figure 3 lF-5-1 shows typical pier and wharf config-
urations.
*T*taymil
r
3
'tl^tayoui
FIGURE 31 F'5-1
TYPICAL PIER AND WHARF CONFIGURATIONS
3105F.1.3 Mooring/berthing risk classification. Each
MOT shall be assigned a mooring/berthing risk classifica-
tion of high, medium or low, as determined from Table
31F-5-1, based on the following site-specific parameters:
L Wind
2. Current
3. Hydrodynamic effects of passing vessels
4. Change in vessel draft
Exceedance of any of the defined condition thresholds in
Table 31F-5-1 places the MOT in the appropriate moor-
ing/berthing risk classification.
The maximum wind, V^, (corrected for duration, height
and over water) and maximum current, V^, shall be obtained
(see Section 3103F5).
In order to determine if there are significant potential
passing vessel effects on moored vessels at an MOT , see
Section 3105F.3.2,
The range of vessel draft shall be based on the local tidal
variation and the operational limits of the vessels berthing
at the MOT
Multiple berth MOTs shall use the same conditions for
each berth unless it can be demonstrated that there are sig-
nificant differences.
MOTs with high mooring/berthing risk classifications
(Table 31F-5-1) shall have the following equipment in oper-
ation: an anemometer (N/E), a current meter (N/E) (may be
omitted if safety factor according to Section 3I03F.5J.1 is
applied to current) and remote reading tension load devices
(N).
3105F.L4 New MOTs. Quick release hooks are required at
all new MOTs, except for spring line fittings. Quick release
hooks shall be sized, within normal allowable stresses, for the
safe working load of the largest size mooring line and config-
uration. To avoid accidental release, the freeing mechanism
shall be activated by a two-step process. Quick release hooks
shall be insulated electrically from the mooring structure,
and should be supported so as not to contact the deck.
3105F,1,5 Analysis and design of mooring components.
The existing condition of the MOT shall be used in the moor-
ing analysis (see Section 3102F). Structural characteristics
of the MOT , including type and configuration of mooring
fittings such as bollards, bitts, hooks and capstans and
material properties and condition, shall be determined in
accordance with Sections 3 107 FA and 3 103 F 10.
The analysis and design of mooring components shall be
based on the loading combinations and safety factors
defined in Sections 3103F8 through 3103F.10, and in
accordance with ACl 318 15.1], AISC [5.2] and
ANSl/AF&PA NDS [5.3], as applicable.
3105F,2 Mooring analyses, A mooring analysis shall be per-
formed for each berthing system, to justify the safe berthing of
the various deadweight capacities of vessels expected at the
MOT The forces acting on a moored vessel shall be determined
in accordance with Section 3103F5. Mooring line and breasting
load combinations shall be in accordance with Section 3103F.8.
Two procedures, manual and numerical are available for
performing mooring analyses. These procedures shall conform
to either the OCIMF documents, ''Mooring Equipment Guide-
lines" [5.4] and ''Prediction of Wind and Current Loads on
VLCCs " [5.5] or the Department of Defense "Moorings " doc-
ument [5.6]. The manual procedure (Section 3105F2,1) may
be used for barges.
A new mooring assessment shall be performed when condi-
tions change, such as any modification in the mooring configu-
ration, vessel size or new information indicating greater wind,
current or other environmental loads.
In general, vessels shall remain in contact with the breasting
orfendering system. Vessel motion (sway) of up to 2 feet off the
breasting structure may be allowed under the most severe envi-
ronmental loads, unless greater movement can be justified by an
appropriate mooring analysis that accounts for potential
dynamic effects. The allowable movement shall be consistent
with mooring analysis results, indicating that forces in the moor-
ing lines and their supports are within the allowable safety fac-
tors. Also, a check shall be made as to whether the movement is
within the limitations of the cargo transfer equipment.
<
<
2010 CALIFORNIA BUILDING CODE
543
MARINE OIL TERMINALS
TABLE 31 F-5-1
MOORING/BERTHING RISK CLASSIFICATION
RiSK CLASSIFICATION
WIND, (V^) (knots)
CURRENT, (V^ (knots)
PASSING VESSEL EFFECTS
CHANGE IN DRAFT (ft)
High
>50
>L5
Yes
>8
Medium
30 to 50
L0toL5
No
6 to 8
Low
<30
<L0
No
<6
The most severe combination of the environmental loads has
to be identified for each mooring component. At a minimum,
the following conditions shall be considered:
L Two current directions (maximum ebb and flood; See
Section 3103F.5.3)
2. Two tide levels (highest high and lowest low)
3. Two vessel loading conditions (ballast and maximum
draft at the terminal)
4. Eight wind directions (45 degree increments)
3105K2.1 Manual procedure. ForMOTs classified as Low
risk (Table 31 F-5-1), simplified calculations may be used to
determine the mooring forces, except if any of the following
conditions exist (Figures 31F-5-2 and 31F-5-3, below).
1. Mooring layout is significantly asymmetrical
2. Horizontal mooring line angles (a) on bow and stern
exceed 45 degrees
3. Horizontal breast mooring line angles exceed 15 nor-
mal to the hull
4. Horizontal spring mooring line angles exceed 10
degrees from a line parallel to the hull
FIGURE 31 F-5'2
HORIZONTAL LINE ANGLES [5.4]
eCW. STIRN, mo B^iAST LIMES
^^mn^ sim^ruRB
SPBINO irNES
FIGURE 31 F-5-3
VERTICAL LINE ANGLES [5.4]
5. Vertical mooring line angles (Q) exceed 25 degrees
6. Mooring lines for lateral loads not grouped at bow
and stern
When the forces have been determined and the distance
between the bow and stern mooring points is known, the
yaw moment can be resolved into lateral loads at the bow
and stern. The total environmental loads on a moored vessel
are comprised of the lateral load at the vessel bow, the lat-
eral load at the vessel stern and the longitudinal load. Line
pretension loads must be added.
Four load cases shall be considered:
1. Entire load is taken by mooring lines
2. Entire load is taken by breasting structures
3. Load is taken by combination of mooring lines and
breasting structures
4. Longitudinal load is taken only by spring lines
3105F.2,2 Numerical procedure, A numerical procedure is
required to obtain mooring forces for MOTs classified as
Medium or High (See Table 31 F-5-1) and for those that do
not satisfy the requirements for using simplified calculations.
Computer program(s) shall be based on mooring analysis
procedures that consider the characteristics of the mooring
system, calculate the environmental loads and provide result-
ing mooring line forces and vessel motions (surge and sway).
3105E3 Wave, passing vessel, seiche and tsunami
3105F,3.1 Wind waves. MOTs are generally located in shel-
tered waters such that typical wind waves can be assumed
not to affect the moored vessel if the significant wave period,
T^, is less than 4 seconds. However, if the period is equal to
or greater than 4 seconds, then a simplified dynamic analy-
sis (See Section 3103F.5.4) is required. The wave period
shall be established based on a 1-year significant wave
height, H^. For MOTs within a harbor basin, the wave
period shall be based on the locally generated waves with
relatively short fetch.
3105F.3.2 Passing vessels. These forces generated by pass-
ing vessels are due to pressure gradients associated with the
flow pattern. These pressure gradients cause the moored
vessel to sway, surge, and yaw, thus imposing forces on the
mooring lines.
Passing vessel analysis shall be conducted when all of the
following conditions exist (See Figure 31F-5-4):
1. Passing vessel size is greater than 25,000 dwt.
2. Distance L is 500 feet or less
3. Vessel speed V is greater than V^^^f
where:
■■ 1.5 + 4.5( knots)
500-25 ^ ^
(5-1)
Exception: lfL< 2B, passing vessel loads shall he
considered.
544
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
L and Bare shown in Figure 3 IF- 5 -4, in units of feet. Vis
defined as the speed of vessel over land minus the current
velocity, when traveling with the current y or the speed of
vessel over land plus the current velocity, when traveling
against the current.
B
FIGURE 31 F-5-4
PASSING VESSEL
When such conditions (1, 2 and 3 above) exist, the surge
and sway forces and the yaw moment acting on the moored
vessel shall, as a minimum, be established in accordance
with Section 3103F5.5. If the demands from such evaluation
are greater than 75 percent of the mooring system capacity
(breaking strength of mooring lines), then a more sophisti-
cated dynamic analysis is required.
For MOTs located in ports, the passing distance, L, may
be established based on channel width and vessel traffic
patterns. The guidelines established in the Department of
Defense, UFC 4-150-06, Figure 5-17 [5,7] for interior
channels may be used. The ''vertical bank" in Figure 5-17
of [5, 7] shall be replaced by the side of the moored vessel
when establishing the distance, "L ."
For MOTs, not located within a port, the distance, "L,"
must be determined from observed traffic patterns.
The following passing vessel positions shall be investi-
gated:
1. Passing vessel is centered on the moored ship. This
position produces maximum sway force.
2. The midship of the passing vessel is fore or aft of the
centerline of the moored ship by a distance of 0.40
times the length of the moored ship. This position is
assumed to produce maximum surge force and yaw
moment at the same time.
The mooring loads due to a passing vessel shall be added
to the mooring loads due to wind and current,
3105F.3.3 Seiche, A seiche analysis is required for existing
MOTs located within a harbor basin and which have histor-
ically experienced seiche. A seiche analysis is required for
new MOTs inside a harbor basin prone to penetration of
ocean waves.
The standing wave system or seiche is characterized by a
series of ''nodes" and "antinodes." Seiche typically has
wave periods ranging from 20 seconds up to several hours,
with wave heights in the range of 0.1 to 0,4 ft [5.7].
The following procedure may be used, as a minimum, in
evaluating the effects of seiche within a harbor basin. In
more complex cases where the assumptions below are not
applicable, dynamic methods are required,
L Calculate the natural period of oscillation of the
basin. The basin may be idealized as rectangular,
closed or open at the seaward end. Use Chapter 2 of
UFC 4 - 1 50-06 [5. 7] to calculate the wave period and
length for different modes. The first three modes shall
be considered in the analysis.
2. Determine the location of the moored ship with
respect to the antinode and node of the first three
modes to determine the possibility of resonance.
3. Determine the natural period of the vessel and moor-
ing system. The calculation shall be based on the total
mass of the system and the stiffness of the mooring
lines in surge. The surge motion of the moored vessel
is estimated by analyzing the vessel motion as a har-
monically forced linear single degree of freedom
spring mass system. Methods outlined in a paper by
F.A. Kilner [5,8] can be used to calculate the vessel
motion.
4. Vessels are generally berthed parallel to the chan-
nel; therefore, only longitudinal (surge) motions
shall be considered, with the associated mooring
loads in the spring lines. The loads on the mooring
lines (spring lines) are then determined from the
computed vessel motion and the stiffness of those
mooring lines,
3105F.3.4 Tsunami, Run-up and current velocity shall be
considered in the tsunami assessment. Table 31F-3-8 pro-
vides run-up values for the San Francisco Bay area, Los
Angeles/Long Beach Harbors and Port Hueneme.
3105F.4 Berthing analysis and design. In general and for new
MOTs, the fender system alone shall be designed to absorb the
berthing energy. For existing MOTs, the berthing analysis may
include the fender and structure.
The analysis and design of berthing components shall be
based on the loading combinations and safety factors defined
in Sections 3103F.8 and 3103F.9 and in accordance with ACI
318 [5.1], AISC [5.2], andANSI/AF&PA NDS [5.3], as appli-
cable.
3105F,4.1 Berthing energy demand. The kinetic berthing
energy demand shall be determined in accordance with Sec-
tion 3103 F.6.
3105FA,2 Berthing energy capacity. For existing MOTs,
the berthing energy capacity shall be calculated as the area
under the force-deflection curve for the combined structure
and fender system as indicated in Figure 31F-5-5. Fender
piles may be included in the lateral analysis to establish the
total force -deflection curve for the berthing system. Load-
deflection curves for other fender types shall be obtained
from manufacturer's data. The condition offenders shall be
taken into account when performing the analysis.
When batter piles are present, the fender system typically
absorbs most of the berthing energy. This can be established
by comparing the force-deflection curves for the fender sys-
tem and batter piles. In this case only the fender system
energy absorption shall he considered.
2010 CALIFORNIA BUILDING CODE
545
MARINE OIL TERMINALS
TABLE 31F-5-3
COEFFICIENT OF FRICTION
Detection (d)
FIGURE 31 F-5-5
BERTHING ENERGY CAPACITY
3105K4.3 Tanker contact length,
3105K4,3,1 Continuous fender system. A continuous
fender system consists offender piles, chocks, wales, and
rubber or spring fender units.
The contact length of a ship during berthing depends
on the spacing of the fender piles and fender units, and
the connection details of the chocks and wales to the
fender piles.
The contact length, L^ can be approximated by the
chord formed by the curvature of the bow and the berth-
ing angle as shown in Equation 5-2 below.
L^ = 2rsina
(5-2)
where:
Lc = contact length
r - Bow radius
a = Berthing Angle
In lieu of detailed analysis to determine the contact
length. Table 31F-5-2 may be used. The contact length
for a vessel within the range listed in the table can be
obtained by interpolation.
TABLE 31 F'5-2
CONTACT LENGTH
VESSEL SIZE (dwti
CONTACT LENGTH
330
25ft
1,000 to 2,500
35ft
5,000 to 26,000
40 ft
35,000 to 50,000
50 ft
65,000
60ft
100,000 to 125,000
70ft
3105E4J.2 Discrete fender system. For discrete fender
systems (i.e., not continuous), one fender unit or breast-
ing dolphin shall be able to absorb the entire berthing
energy.
3105E4,4 Longitudinal and vertical berthing forces.
The longitudinal and vertical components of the hori-
zontal berthing force shall be calculated using appropri-
ate coefficients of friction between the vessel and the
fender. In lieu of as-built data, the values in Table
31F-5-3 may be usedfor typical fender/vessel materials:
CONTACT MA TERIALS
FRICTION COEFFICIENT
Timber to Steel
0.4 to 0.6
Urethane to Steel
0.4 to 0.6
Steel to Steel
0.25
Rubber to Steel
0.6 to 0.7
UHMW to Steel
0.1 to 0.2
'^Ultra-high molecular weight plastic rubbing strips.
Longitudinal and verticalforces shall be determined by:
F = \iN
(5-3)
where:
F = longitudinal or vertical component of horizon-
tal berthing force
|I = coefficient of friction of contact materials
N = maximum horizontal berthing force (normal to
fender)
3 105F,4,5 Design and selection of new fender systems. For
guidelines on new fender designs, refer to the Department of
Defense "Piers and Wharves'' document (UFC 4-152-01)
[5.9] and the PIANC Guidelines for the Design of Fenders
Systems: 2002 [5.101
3105F.5 Layout of new MOTs. The number and spacing of
independent mooring dolphins and breasting dolphins
depends on the DWTand length overall (LOA) of vessels to be
accommodated.
Breasting dolphins shall be positioned adjacent to the paral-
lel body of the vessel when berthed. A minimum of two breast-
ing dolphins shall be provided. The spacing of breasting
dolphins shall be adequate for all sizes of vessels that may
berth at the MOT
Mooring dolphins shall be set back from the berthing line
(fender line) for a distance between 115 ft and 165 ft, so that
longer bow, stern and breast lines can be deployed.
For a preliminary layout, the guidelines in the British Stan-
dards, Part 4, Section 2 [5.11], may be used in conjunction with
the guidelines below.
1. If four breasting dolphins are provided, the spacing
between exterior breasting dolphins shall be between 0.3
and 0.4 LOA of the maximum sized vessel expected to
call at the MOT. The spacing between interior breasting
dolphins shall be approximately 0.3 to OALOA of the
minimum sized vessel expected to call at the MOT.
2. If only two breasting dolphins are provided, the spacing
between the dolphins shall be the smaller (0.3 LOA) of
the guidelines specified above.
3. If bow and stern lines are usedfor mooring, the spacing
between exterior mooring dolphins shall be 1.35 times
the LOA of the maximum sized vessel expected to call at
the MOT.
546
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
4. The spacing between interior mooring dolphins s hall he
0,8 times the LOA of the maximum sized vessel expected
to call at the MOT,
The final layout of the mooring and breasting dolphins shall
be determined based on the results of the mooring analysis that
provides optimal mooring line and breasting forces for the
range of vessels to be accommodated. The breasting force
under the mooring condition shall not exceed the maximum
fender reaction of the fender unit when it is being compressed
at the manufacturers rated deflection.
3105F.6 Symbols.
a = Berthing Angle, It also indicates the angle of hori-
zontal mooring lines, see Fig 5-2,
A - Deflection
= Vertical mooring line angles
B = Beam of vessel
F - Longitudinal or vertical component of horizontal
normal berthing force
L - Distance between passing and moored vessels
L^ = Contact length
N = Maximum horizontal berthing force
r = Bow radius
|i = Coefficient of friction of contact materials
V = Ground speed (knots)
V^ - Maximum current (knots).
V^„Y - Ground speed (knots) above which passing loads
must be considered
V^ = Maximum wind speed (knots)
3 105E7 References.
[5.1] American Concrete Institute, ACI 318-05, 2005,
"Building Code Requirements for Structural Con-
Crete (318-05) and Commentary (318R-05),"
Farmington Hills, Michigan.
[5.2] American Institute of Steel Construction Inc. (AISC),
2005, "Steel Construction Manual, " Thirteenth Edi-
tion, Chicago, IL,
[5.3] American Forest & Paper Association, 2005,
"National Design Specification for Wood Construc-
tion, " ANSI/AF&PA NDS-2005, Washington, D.C.
[5.4] Oil Companies International Marine Forum
(OCIMF), 1997, "Mooring Equipment Guidelines, "
2""^ Ed,, London, England.
[5,5] Oil Companies International Marine Forum
(OCIMF), 1977, "Prediction of Wind and Current
Loads on VLCCs, ** London, England.
[5,6] Department of Defense, 3 October 2005, "Moor-
ings", Unified Facilities Criteria (UFC) 4-152-03,
Washington D.C, USA.
[5.7] Department of Defense, 12 December 2001, "Mili-
tary Harbors and Coastal Facilities '\ Unified Facili-
ties Criteria (UFC) 4-150-06, Washington D.C,
USA.
[5,8] Kilner F.A., 1961, "Model Tests on the Motion of
Moored Ships Placed on Long Waves. " Proceedings
of 7th Conference on Coastal Engineering, August
1960, The Hague, Netherlands, published by the
Council on Wave Research - The Engineering Foun-
dation.
[5,9] Department of Defense, 28 July 2005, "Piers and
Wharves, " Unified Facilities Criteria (UFC),
4-152-01, Washington D.C, USA.
[5. 10] Permanent International Association of Navigation
Congresses (PIANC), 2002, "Guidelines for the
Design of Fender Systems: 2002, " Brussels.
[5.11 [British Standards Institution, 1994, "British Stan-
dard Code of Practice for Maritime Structures - Part
4. Code of Practice for Design of Fendering and
Mooring Systems, " BS6349, London, England.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE
547
MARINE OIL TERMINALS
Division 6
SECTION 3106F
GEOTECHNICAL HAZARDS AND FOUNDATIONS
3106FJ General.
3106F,U Purpose, This section provides minimum stan-
dards for analyses and evaluation of geotechnical hazards
and foundations.
3 106F.L2 Applicability. The requirements provided herein
apply to all new and existing MOTs.
3106F.L3 Seismic loading. The seismic loading for
geotechnical hazard assessment and foundation analyses is
provided in Section 3I03F.4.
3106F.2 Site Characterization.
3106F.2.1 Site classes. Each MOT shall be assigned at least
one site class, based on site-specific geotechnical informa-
tion. Site Classes S^, Sg, Sq Sq, and S^ are defined in Table
31F-6-1 and Site Class Sp is defined as follows:
L Soils vulnerable to significant potential loss of stiff-
ness, strength, and/or volume under seismic loading,
such as liquefiable soils, quick and highly sensitive
clays, and collapsible weakly cemented soils.
2. Peats and/or highly organic clays, where the thick-
ness of peat or highly organic clay exceeds 10 feet.
3. Very high plasticity clays with a plasticity index (PI)
greater than 75, where depth of clay exceeds 25 feet.
4. Very thick soft/medium stiff clays, where the depth of
clay exceeds 1 20 feet.
3106F.2.2 Site-Specific information. In general, geotech-
nical characterization shall be based on site-specific infor-
mation. This information may be obtained from existing or
new sources. However, if existing or nonsite specific infor-
mation is used, the geotechnical engineer of record shall
provide adequate justification for its use.
Site-specific investigations shall include, at a minimum, bor-
ings and/or cone penetration tests, soil classifications, config-
uration, foundation loading and an assessment of seismic
hazards. The array (number and depths) of exploratory
borings and cone penetration tests (CPT) will depend on the
proposed or existing structures and site stratigraphy. The
investigation or testing activities shall be completed following
the procedures in Section 5 ofSCEC [6.3]. CPT data may also
be used by first converting to standard penetration test (SPT)
data, using an appropriate method, that reflects the efiects of soil
gradation. If geotechnical data other than SPT and CPT are
used, an adequate explanation and rationale shall be provided.
Quantitative soil information is required to a depth of 100
feet below the mudline, for assigning a Site Class (see Table
3 IF- 6-1). When data to a depth of 100 feet is unavailable,
other information such as geologic considerations may be
used to determine the Site Class.
3106F.3 Liquefaction. A liquefaction assessment shall
address triggering and the resulting hazards, using residual
shear strengths of liquefied soils.
3106F.3.1 Triggering assessment. Liquefaction triggering
shall be expressed in terms of the factor of safety (SF):
SF=CRR/CSR
(6-1)
where:
CRR = Cyclic Resistance Ratio
CSR = The Cyclic Stress Ratio induced by Design Peak
Ground Acceleration (DPGA) or other postu-
lated shaking
The CRR shall be determined from Figure 7.1 in SCEC
[6.3]. If available, both the SPT and CPT data can be used.
CSR shall be evaluated using the simplified procedure in
Section 3106F.3.1.1 or site-specific response analysis pro-
cedures in Section 3106F.3.1.2.
Shaking-induced shear strength reductions in liquefiable
materials are determined as follows:
L SF>1.4
Reductions of shear strength for the materials for
postearthquake conditions may be neglected.
TABLE 31F-6-1
SITE CLASSES
SITE CLASS
SOIL PROFILE NAME/GENERIC
DESCRIPTION
A VERAGE VALUES FOR TOP 100 FEET OF SOIL PROFILE
Shear Wave Velocity,
Vs [ft/sec]
Standard Penetration Test
[blowsm]
Undrained Shear Strength,
Su[psf]
Sa
Hard Rock
> 5,000
Sr
Rock
2,500 to 5,000
Sr
Very Stiff/Dense Soil and Soft Rock
1,200
>50
> 2,000
Sn
Stiff/Dense Soil Profile
600 to 1,200
15 to 50
1,000 to 2,000
Se
Soft/Loose Soil Profile
<600
<i5
< 1,000
Sf
Defined in Section 3106F.2.1
Notes:
1. Site Class SF shall require site-specific geotechnical information as discussed in Sections 3106E2.2 and 3103F.4.
2. Site Class SE also includes any soil profile with more than lOfeetofsoficlay defined as a soil with a plasticity index, Pl>20, water content > 40 percent and
Sij<500psf
3. The plasticity index, PI, and the moisture content shall be determined in accordance with ASTM D4318 [6. 1] and ASTM D2216 [6. 2], respectively.
548
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
2. L0<SF<L4
A strength value intermediate to the material's initial
strength and residual undrained shear strength should be
selected based on the level of residual excess pore water
pressure expected to be generated by the ground shaking
(e.g., Figure 10 of Seed and Harden [6.4]).
3. SF<1.0
Reduction of the material shear strength to a residual
undrained shear strength level shall be considered, as
described in Section 3106F.3.2.
3106F,3J.l Simplified procedure. The simplified pro-
cedure to evaluate liquefaction triggering shall follow
Section 7 ofSCEC [6.3]. Cyclic stress ratio (CSR) is used
to define seismic loading, in terms of the Design Peak
Ground Acceleration (DPGA) and Design Earthquake
Magnitude (DEM). DPGA and DEM are addressed in
Section 3103F4.2, CSR is defined as:
CSR = 0.65
'T)
(6-2)
where:
g = gravitational constant
a^ = the vertical total stress
a'^~ the vertical effective stress
r^ = a stress reduction factor
^MSF = ^^^ magnitude scaling factor
For values ofr^^sF ^^^ ^d> ^^^ SCEC [6.3] Figures 7.2
and 7.3, respectively To evaluate r^^^r^ the DEM value
associated with DPGA shall be used.
3106F,3,1,2 Site specific response procedure. In lieu of
the simplified procedure, either one-dimensional or
two-dimensional site response analysis may be per-
formed using the ground motion parameters discussed in
Section 3103F.4. The computed cyclic stresses at various
points within the pertinent soil layers shall be expressed
as values of CSR.
3106F.3.2 Residual strength. The residual undrained shear
strength may be estimated from Figure 7.7 of SCEC [6.3].
When necessary, a conservative extrapolation of the range
should be made. Under no circumstances, shall the residual
shear strength be higher than the shear strength based on
effective strength parameters.
The best estimate value should correspond to ^/^from the
lower bound of the range for a given value of equivalent
clean sand SPT blowcount. When a value other than the " Vj
value" is selected for the residual shear strength, the selec-
tion shall be justified. An alternate method is provided in
Stark and Mesri [6.5]. The residual strength of liquefied
soils may be obtained as a function of effective confining
pressures if a justification is provided. The resulting resid-
ual shear strength shall be used as the postearthquake shear
strength of liquefied soils.
3106F,4 Other geotechnical hazards. For a SF less than 1.4,
the potential for the following hazards shall be evaluated:
1. Flow slides
2. Slope movements
3. Lateral spreading
4. Ground settlement and differential settlement
5. Other surface manifestations
These hazards shall be evaluated, using the residual shear
strength described above (Section 3106F.3.2).
3106F,4J Stability of earth structures. If a slope failure
could affect the MOT, a stability analysis of slopes and earth
retaining structures shall be performed. The analysis shall
use limit equilibrium methods that satisfy all of the force
and/or moment equilibrium conditions and determine the
slope stability safety factor.
i- Slope stability safety factor >1.2
Flow slides can be precluded; however, seismically
induced ground movements shall be addressed.
2. 1,0 < Slope stability safety factor < 1.2
Seismically induced ground movements should be evalu-
ated using the methods described below.
3. Slope stability safety factor < 1.0
Mitigation measures shall be implemented per Section
3106F6.
3106F.4.2 Simplified ground movement analysis. The seis-
mically induced ground settlement may be estimated using
Section 7.6 of SCEC [6.3]. Surface manifestation of lique-
faction may be evaluated using Section 7. 7 of SCEC Results
shall be evaluated to determine if mitigation measures are
required.
Seismically induced deformation or displacement of
slopes shall be evaluated using the Makdisi-Seed [6.6] sim-
plified method as described below.
The stability analysis shall be used with the residual shear
strengths of soils to estimate the yield acceleration coeffi-
cient, Ky, associated with the critical potential movement
plane. In general, the DPGA shall be used as K^^^ (see [6. 6])
and DEM as the earthquake magnitude, M. These parame-
ters shall be used together with the upper bound curves Fig-
ures 9-11 of [6.6], to estimate the seismically induced
ground movement along the critical plane.
However, the value of K^^ may be different from the
DPGA value to include the effects of amplification, incoher-
ence, etc. When such adjustments are made in converting
DPGA to K,,^ a justification shall be provided. Linear
interpolation using the upper bound curves in Figure 10
(ordinate scale should be divided by 10) in [6.6] or Figure
4-10 in Ferritto et al [6.7] can be used to estimate the seis-
mically induced ground movement for other earthquake
magnitudes.
For the Ports of Los Angeles and Long Beach, Newmark
displacement curves are available and are site-specific
[3.5, 3.6]. Curves are provided for both Level 1 and Level 2
2010 CALIFORNIA BUILDING CODE
549
MARINE OIL TERMINALS
earthquakes, and plot yield acceleration versus lateral dis-
placement.
For screening purposes only, lateral spreading shall be
evaluated, using the simplified equations in Youd et al
[6.8]. The total seismically induced ground displacement
shall include all contributory directions.
1. When the resulting displacement from the screening
method is > O.I ft., the Makdisi-Seed simplified
method or other similar methods shall be used to esti-
mate lateral spreading.
2. If the computed displacement from the simplified
method(s) is < 0.5ft., the effects can be neglected.
3. If the computed displacements using simplified meth-
ods are > 0.5ft., the use of a detailed ground move-
ment analysis (see Section 3I06F.4.3) may be
considered.
4. If the final resulting displacement, regardless of the
method used, remains > 0.5ft., it shall be considered
in the structural analysis.
3106F,4,3 Detailed ground movement analysis. As an
alternative to the simplified methods discussed above, a
two-dimensional (2-D) equivalent linear or nonlinear
dynamic analysis of the MOT and/or slopes and earth
retaining systems may be performed.
An equivalent linear analysis is adequate when the stiff-
ness and/or strength of the soils involved are likely to
degrade by less than one-third, during seismic excitation of
less than 0.5 g's. Appropriate time histories need to be
obtained to calculate seismically induced displacement (see
Section 3I03F.4.2). Such analysis should account for the
accumulating effects of displacement if double-integration
of acceleration time histories is used. The seismic stresses
or stress time histories from equivalent linear analysis may
be used to estimate seismically induced deformation.
A nonlinear analysis should be used if the stiffness and/or
strength of the soils involved are likely to degrade by more
than one-third during seismic motion.
If the structure is included in the analysis, the ground
motion directly affects the structural response. Otherwise,
the uncoupled, calculated movement of the soil on the struc-
ture shall be evaluated.
3106F.5 Soil structure interaction.
3106F.5J Soil parameters. Soil structure interaction (SSI)
shall be addressed for the seismic evaluation of MOT struc-
tures. SSI may consist of linear or non-linear springs (and
possibly dash-pots) for various degrees of freedom, includ-
ing horizontal, vertical, torsional, and rotational, as
required by the structural analysis.
Pile capacity parameters may be evaluated using the pro-
cedures in Chapter 4 of FEM A 356 [6.9]. The "p-y'' curves,
*'t-z'* curves, and tip load — displacement curves for piles
(nonlinear springs for horizontal and vertical modes and
nonlinear vertical springs for the pile tip, respectively) and
deep foundations shall be evaluated using Section 6 of API
RP 2A-WSD [6.10] including the consideration of pile
group effects. Equivalent springs (and dashpots) represent-
ing the degrading properties of soils may be developed.
Where appropriate, alternative procedures can be used to
develop these parameters. Rationale for the use of alterna-
tive procedures shall be provided. One simplified method is
presented in Chapter 4 of the UFC 3-220-01 A [6.1 1] and
provides deflection and moment for an isolated pile, subject
to a lateral load.
3106F,5,2 Shallow foundations. Shallow foundations shall
be assumed to move with the ground. Springs and dashpots
may be evaluated as per Gazetas [6.12].
3106F,5,3 Underground structures. Buried flexible struc-
tures or buried portions of flexible structures including piles
and pipelines shall be assumed to deform with estimated
ground movement at depth.
As the soil settles, it shall be assumed to apply shear
forces to buried structures or buried portions of structures
including deep foundations.
3I06F,6 Mitigation measures and alternatives. If the hazards
and consequences addressed in Sections 31 06F.3 and 3106F4
are beyond the specified range, the following options shall be
considered:
1. Perform a more sophisticated analysis
2. Modify the structure
3. Modify the foundation soil
Examples of possible measures to modify foundation soils
are provided in Table 4-1 of [6.7].
3106R7 Symbols,
SF = Safety Factor
CRR = Cyclic Resistance Ratio
CSR = Cyclic Stress Ratio induced by DPGA
g = Gravitational constant
o^ = the vertical total stress
c\= the vertical effective stress
r^ = a stress reduction factor
^MSF = ^^^ magnitude scaling factor
3106R8 References,
[6.1] American Society for Testing and Materials
(ASTM), 2002, "D43 18-00 Standard Test Methods
for Liquid Limit, Plastic Limit, and Plasticity Index
of Soils, " West Conshohocken , PA
[6.2] American Society for Testing and Materials
(ASTM), 2002, "D2216-98 Standard Test Method
for Laboratory Determination of Water (Moisture)
Content of Soil and Rock by Mass, " West
Conshohocken , PA.
[6.3] Southern California Earthquake Center (SCEC),
March 1999, ''Recommended Procedures for
Implementation of DMG Special Publication 117
Guidelines for Analyzing and Mitigating Liquefac-
tion in California, " University of Southern Califor-
nia, Los Angeles.
550
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
[6.4] Seed, R,B. and Harder, C.F., 1999, SPT-Based
Analysis of Cyclic Pore Pressure Generation and
Undrained Residual Strength, Proceedings of the
H.B. Seed Memorial Symposium, Editor: J.M.
Duncan, BiTech Publishers Ltd., v. 2, pp. 351-3 76.
[6.5] Stark, T.D., and Mesri, G., 1992, Undrained shear
strength of liquefied sands for stability analysis,
Journal of Geotechnical Engineering, American
Society of Civil Engineers, vll8, nil, pp
1727-1747.
[6.6] Makdisi, F.l. and Seed, H.B., "Simplified Proce-
dure for Estimating Dam and Embankment Earth-
quake-Induced Deformations," ASCE Journal of
the Geotechnical Engineering Division, Vol. 104,
No. 7, pp. 849-867.
[6.7] Ferritto, J., Dickenson, S., Priestley N., Werner, S.,
Taylor, C, Burke D, Seelig W., and Kelly, S., 1999,
"Seismic Criteria for California Marine Oil Termi-
nals," Vol.1 and Vol.2, Technical Report
TR-2103-SHR, Naval Facilities Engineering Ser-
vice Center, Port Hueneme, CA.
[6.8] Youd, T. L, Hansen, C. M., and Bartlett, S. F.,
"Revised MLR Equations for Predicting Lateral
Spread Displacement" Proceedings of the 7th
U.S.- Japan Workshop on Earthquake Resistant
Design of Lifeline Facilities and Countermeasures
Against Soil Liquefaction, 1999. "
[6.9] Federal Emergency Management Agency, FEMA
-356, Nov. 2000, "Prestandard and Commentary
for the Seismic Rehabilitation of Buildings, " Wash-
ington, D.C.
[6.10] American Petroleum Institute, December 2000,
Recommended Practice 2A-WSD (API RP
2A-WSD), "Recommended Practice for Planning,
Designing and Constructing Fixed Offshore Plat-
forms — Working Stress Design, " Washington, D. C.
[6.11] Department of Defense, 16 January 2004, Unified
Facilities Criteria (UFC) 3-220-01 A, ''Deep Foun-
dations," Washington, D.C.
[6.12] Gazetas,G., ''Formulas and Charts for Impedances
of Surface and Embedded Foundations, " Journal of
Geotechnical Engineering, ASCE, Vol. 117, No. 9,
September, 1991.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
201 CALIFORNIA BUILDING CODE 551
MARINE OIL TERMINALS
Division 7
SECTION 31 07F
STRUCTURAL ANALYSIS AND
DESIGN OF COMPONENTS
3107F.1 General
3 1 07 F, 1,1 Purpose, This section establishes the minimum
performance standards for structural components. Evalua-
tion procedures for seismic performance, strength and
deformation characteristics of concrete, steel and timber
components are prescribed herein. Analytical procedures
for structural systems are presented in Section 3104F.
3107F,1,2 Applicability. This section addresses MOTs con-
structed using the following structural components:
1. Reinforced concrete decks supported by batter and/or
vertical concrete piles
2. Reinforced concrete decks supported by batter and/or
vertical steel piles, including pipe piles filled with con-
crete
3. Reinforced concrete decks supported by batter and/or
vertical timber piles
4. Timber decks supported by batter or vertical timber,
concrete or steel pipe piles
5. Retaining structures constructed of steel, concrete
sheet piles or reinforced concrete.
3107F.2 Concrete deck with concrete or steel piles,
3107F,2,1 Component strength. The following parameters
shall be established in order to compute the component
strength:
1. Specified concrete compressive strengths
2. Concrete and steel modulus of elasticity
3. Yield and tensile strength of mild reinforcing and
prestressed steel and corresponding strains
4. Confinement steel strength and corresponding
strains
5. Embedment length
6. Concrete cover
7. Yield and tensile strength of structural steel
8. Ductility
In addition, for ''existing " components, the following
conditions shall be considered:
9. Environmental effects, such as reinforcing steel corro-
sion, concrete spalling, cracking and chemical attack
10. Fire damage
11. Past and current loading effects, including over-
load, fatigue or fracture
12. Earthquake damage
13. Discontinuous components
14. Construction deficiencies
3107F.2.1.1 Material properties. Material properties of
existing components, not determined from testing proce-
dures, and of new components, shall be established using
the following methodology.
The strength of structural components shall be evalu- <
ated based on the following values (Section 5.3 of [7.11
and pp. 3-73 and 3-74 of [7.2]):
Specified material strength shall be used for nonduc-
tile components (shear controlled), all mechanical, elec-
trical and mooring equipment (attachments to the deck)
and for all non seismic load combinations:
fc=I-Of\
fy =1-0 f^
fp =1^0f^
(7-la)
(7-lb)
(7-lc)
In addition, these values (7-la, 7-lb and 7-lc) may be
used conservatively as alternatives to determine the
nominal strength of ductile components (N).
Expected lower bound estimates of material strength
shall be used for determination of moment-curvature
relations and nominal strength of all ductile compo-
nents:
fy =l-lfy
fp =l-Ofp
(7-2a)
(7-2b)
(7-2c)
Upper bound estimates of material strength shall be
used for the determination of moment-curvature rela-
tions, to obtain the feasible maximum demand on capac-
ity protected members:
f'c=1.7f\ (7-3a)
fy =1.3fy (7-3b)
fp =l.lfp (7-3c)
where:
f\= Specified compressive strength of concrete
fy = Specified yield strength of reinforcement or
specified minimum yield stress steel
fp - Specified yield strength ofprestress strands
*' Capacity Design'' (Section 5.3 of [7.11) ensures that
the strength at protected components (such as pile caps
and decks), joints and actions (such as shear), is greater
than the maximum feasible demand (over strength),
based on realistic upper bound estimates of plastic hinge
flexural strength. An additional series of nonlinear anal-
yses using moment curvature characteristics of pile
hinges may be required.
Alternatively, if a moment-curvature analysis is per-
formed that takes into account the strain hardening of the
steel, the demands used to evaluate the capacity pro-
tected components may be estimated by multiplying the
moment-curvature values by 1.25.
552
2010 CALIFORNIA BUILDING CODE
Based on a historical review of the building materials
used in the twentieth century, guidelines for tensile and
yield properties of concrete reinforcing bars and the com-
pressive strength of structural concrete have been estab-
lished (see Tables 6-1 to 6-3 ofFEMA 356 [7.3]. The values
shown in these tables can be used as default properties,
only if as-built information is not available and testing is
not performed. The values in Tables 31F-7-1 and31F-7-2,
are adjusted according to equations (7-1) through (7-3).
3107F.2.1.2 Knowledge factor (k). Knowledge factor, k,
shall be applied on a component basis.
The following information is required, at a minimum,
for a component strength assessment:
1. Original construction records, including draw-
ings and specifications.
MARINE OIL TERMINALS
2. A set of ''as-built" drawings and/or sketches, doc-
umenting both gravity and lateral systems (Section
31 02 F. 1.5) and any postconstruction modification
data.
3. A visual condition survey, for structural compo-
nents including identification of the size, location
and connections of these components.
4. In the absence of material properties, values from
limited in-situ testing or conservative estimates of
material properties (Tables 3 lF-7-1 and31F-7-2).
5. Assessment of component conditions, from an in-
situ evaluation, including any observable deterio-
ration.
6. Detailed geotechnical information, based on
recent test data, including risk of liquefaction, lat-
eral spreading and slope stability.
TABLE 31 F'7-1
COMPRESSIVE STRENGTH OF STRUCTURAL CONCRETE (psif
TIMEFRAME
PILING
BEAMS
SLABS
1900-1919
1500-3,000
2,000-3,000
1,500^3,000
1920-1949
3,000-4,000
2,000-3,000
2,000-3,000
1950-1965
4,000-5,000
3,000-4,000
3,000-4,000
1966-present
5,000-6,000
3,000-5,000
3,000-5,000
1. Concrete strengths are likely to be highly variable for an older structure.
TABLE 31 F'7'2
TENSILE AND YIELD PROPERTIES OF REINFORCING BARS FOR VARIOUS ASTM SPECIFICATIONS AND PERIODS
(after Table 6-2 of [7.3])
ASTM
STEEL TYPE
YEAR
RANG^
GRADE
structuraU
INTERMEDIATE^
HARD^
33
40
50
60
70
75
Minimum
Yieltf (psi)
33,000
40,000
50,000
60,000
70,000
75,000
Minimum
Tensile' (psi)
55,000
70,000
60,000
90,000
95,000
100,000
A15
Billet
1911-1966
X
X
X
A16
Raif
1913-1966
X
A61
Raif
1963-1966
X
A160
Axle
1936-1964
X
X
X
A160
Axle
1965-1966
X
X
X
X
A408
Billet
1957-1966
X
X
X
A431
Billet
1959-1966
X
A432
Billet
1959-1966
X
A615
Billet
1968-1972
X
X
X
A615
Billet
1974-1986
X
X
A615
Billet
1987-1997
X
X
X
A616
Rait^
1968-1997
X
X
A617
Axle
1968-1997
X
X
A706
Low-Alloy^
1974-1997
X
A955
Stainless
1996-1997
X
X
X
II
General Note: An entry "X" indicates that grade was available in those years.
1. The terms structural, intermediate and hard became obsolete in 1968.
2. Actual yield and tensile strengths may exceed minimum values.
3. Untilabout 1920, a variety of proprietary reinforcing steels were used. Yield strengths are likely to be in the range from 33, 000 psi to 55,000 psi, but higher values
are possible. Plain and twisted square bars were sometimes used between 1900 and 1949.
4. Rail bars should be marked with the letter "R."
5. ASTM steel is marked with the letter "W."
2010 CALIFORNIA BUILDING CODE
553
MARINE OIL TERMINALS
The knowledge factor, k, is 1.0 when comprehensive
knowledge as specified above is utilized. Otherwise^ the
knowledge factor shall be 0. 75. Further guidance on the
determination of the appropriate k value can be found in
Table 2-1 ofFEMA 356 [7.3].
3107F.2,2 Component stiffness. Stiffness that takes into
account the stress and deformation levels experienced by
the component shall be used. Nonlinear load-deformation
relations shall be used to represent the component
load- deformation response. However, in lieu of using non-
linear methods to establish the stiffness and moment cur-
vature relation of structural components, the equations of
Table 31F-7-3 may be used to approximate the effective
elastic stiffness, EI^, for lateral analyses (see Section
3 1 07 F.5 for definition of symbols).
TABLE 31 F-7-3
EFFECTIVE ELASTIC STIFFNESS
CONCRETE COMPONENT
f/e/f^o
Reinforced Pile
0.3 + N/(f\A,)
Pile/Deck Dowel Connection^
0.3^N/(f\A;)
Prestressed Pile^
0.6 <Ei,/EI^< 0.75
Steel Pile
1.0
Concrete w/Steel Casing
E,I,^0.25EcIc
{E,Is + E^I,)
Deck
0.5
1. The pile/deck connection and prestressed pile may also be approximated as one
member with an average stiffness of 0.42 Ei^/El^ (Ferritto et al, 1999 [7.2])
N = is the axial load level.
E^ = Young s modulus for steel
/j = Moment of inertia for steel section
Ef. = Young s modulus for concrete
I^ = Moment of inertia for uncracked concrete section
3107F.2.3 Deformation capacity of flexural members.
Stress-strain models for confined and unconfined con-
crete, mild and prestressed steel presented in Section
3107F.2.4 shall be used to perform the moment-curvature
analysis.
The stress-strain characteristics of steel piles shall be
based on the actual steel properties. If as-built information
is not available, the stress-strain relationship may be
obtained per Section 3107F.2.4.2.
For concrete in-filled steel piles, the stress-strain model
for confined concrete shall be in accordance with Section
3107F.2.4.L
Each structural component expected to undergo inelastic
deformation shall be defined by its moment-curvature relation.
The displacement demand and capacity shall be calculated
per Sections 3104F.2 and 3104E3, as appropriate.
The moment-rotation relationship for concrete compo-
nents shall be derived from the moment-curvature analysis
per Section 3107F2.5.4 and shall be used to determine lat-
eral displacement limitations of the design. Connection
details shall be examined per Section 3107F.2. 7.
3107F,2A Stress-Strain models.
3107F.2.4.1 Concrete, The stress-strain model and
terms for confined and unconfined concrete are shown in
Figure 31F-7-1.
3107F.2,4.2 Reinforcement steel and structural steel
The stress-strain model and terms for reinforcing and
structural steel are shown in Figure 31F-7-2.
3107F.2A3 Prestressed steel The stress-strain model of
Blakeley and Park [7.4] may be used for prestressed steel.
The model and terms are illustrated in Figure 31 F-7-3.
3107F.2.4.4 Alternative stress-strain models. Alterna-
tive stress-strain models are acceptable if adequately
documented and supported by test results, subject to
Division approval
Compression Str»in»€:c
FIGURE 31 F'7-1
STRESS-STRAIN CURVES FOR CONFINED
AND UNCONFINED CONCRETE [7.1]
c« f -
i
V5 f V '
1 '
1. \ I
Steel Strain, e^
FIGURE 31 F-7'2
STRESS-STRAIN CURVE FOR MILD REINFORCING STEEL OR
STRUCTURAL STEEL [7. 1]
FIGURE 31 F-7-3
STRESS-STRAIN CURVE FOR PRESTRESSED STEEL [7.4]
554
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
3107E2.5 Concrete piles.
3107E2,5J General The capacity of concrete piles is
based on permissible concrete and steel strains corre-
sponding to the desired performance criteria.
Different values may apply for plastic hinges forming
at in- ground andpile-top locations. These procedures
are applicable to circular, octagonal, rectangular and
square pile cross sections.
3107F,2,5,2 Stability. Stability considerations are
important to pier-type structures. The moment-axial
load interaction shall consider effects of high slender-
ness ratios (kl/r). An additional bending moment due to
axial load eccentricity shall be incorporated unless:
e/h < 0.10
(7-4)
where:
e = eccentricity of axial load
h = width of pile in considered direction
3107F.2.5.3 Plastic hinge length. The plastic hinge
length is required to convert the moment-curvature rela-
tionship into a moment-plastic rotation relationship for
the nonlinear pushover analysis.
The pile 's plastic hinge length, Lp (above ground), when
the plastic hinge forms against a supporting member is:
(7-5)
L^=0.08L +0.15/^,^,, > 0.3/,,^,,
where:
L - the distance from the critical section of the plas-
tic hinge to the point of contraflexure
dfji = the diameter of the longitudinal reinforcement
fy^ = design yield strength of longitudinal reinforce-
ment (ksi)
If a large reduction in moment capacity occurs due to
spalling, then the plastic hinge length shall be:
L,=03fyJ,
(7-6)
When the plastic hinge forms in-ground, the plastic
hinge length may be determined from Figure 31F-7-4
(see page 311 of [7.1]).
H ~ distance from ground to
pile point of ccrttraflexure
^ ■ -~ ■ 1(5 m m . im lio ilo m
FIGURE aiF-T-a
INFLUENCE OF PILE/SOIL STIFFNESS RATIO ON PLASTIC
HINGE LENGTH (after Fig. 5.30 of [7. 1])
The stiffness parameter (x-axis) is:
[D^]EI^
(7-7)
where:
EI^= the effective stiffness
K = the subgrade modulus
D = pile diameter
D*= reference diameter of 6 ft
If site specific soil information is not available then the
values for K in Table 31F-7-4 may be used.
TABLE 31 F-7-4
SUBGRADE MODULUS K
SOIL TYPE
AVGUNDRAINED
SHEAR STRENGTH
[psn
SUBGRADE
MODULUS K
[Ib/in^
Soft Clay
250-500
30
Medium Clay
500-1000
100
StiffClay
1000-2000
500
Very Stiff Clay
2000-4000
1000
Hard Clay
4000-8000
2000
Loose Sand (above WT/submerged)
—
25/20
Medium Sand (above WT/submerged)
90/60
Sand (above WT/submerged)
—
275/125
3107E2,5.4 Plastic rotation. The plastic rotation, 6^,
can be determined from Equation 7-8, by using
moment-curvature analysis and applicable strain limita-
tions, as shown in Figure 31F-7-5.
The plastic rotation is:
ep=Mp=(^„ -</>,) (7-8)
where:
Lp - plastic hinge length
^p - plastic curvature
(|)^ = maximum curvature
^y = yield curvature
The maximum curvature, (|)^ shall be determined by the
concrete or steel strain limit state at the prescribed per-
formance level, whichever comes first.
Alternatively, the maximum curvature, (|)^ may be cal-
culated as:
0™ =-^
(7-9)
where:
e^^= max limiting compression strain for the pre-
scribed performance level (Table 31F-7-5)
c„ = neutral-axis depth, at ultimate strength of section
2010 CALIFORNIA BUILDING CODE
555
MARINE OIL TERMINALS
Secant stitfn^s
throMQh first yield
Nominal strongth laNen
at e^ = 0.004
First yield or
e^= 0.002. whichever
comes first
^Y Ptoslic Curmlum ^m
FIGURE 31 F-7-5
MOMENT CURVA TURE ANALYSIS
The yield curvature, (j)^ is the curvature at the intersec-
tion of the secant stiffness, EI^, throughfirst yield and the
nominal strength, (e^ ~ 0.004)
^v =
EI
(7-10)
3107F.2,5.5 Ultimate concrete and steel flexural
strains. Strain values computed in the nonlinear push-
over analysis shall be compared to the following limits.
3107K2,5.5J Unconfined concrete piles: An uncon-
fined concrete pile is defined as a pile having no con-
finement steel or one in which the spacing of the
confinement steel exceeds 12 inches.
Ultimate concrete compressive strain:
£,„ =0.005 (7-11)
3107E2.5,5,2 Confined concrete piles:
Ultimate concrete compressive strain [7.1]:
e,„ = 0.004 + (L4pj^,zj/f\, > 0,005 (7-12)
e,^< 0,025
where:
Ps = effective volume ratio ofconfming steel
fyh = yield stress of confining steel
%n = strain at peak stress ofconfming reinforce-
ment, 0,15 for grade 40, 0,10 for grade 60
f \^ = confined strength of concrete approximated
hyL5f\
3107R2.5.6 Component acceptance/damage criteria.
The maximum allowable concrete strains may not exceed
the ultimate values defined in Section 3107F.2.5.5, The
following limiting values (Table 31 F-7-5) apply for each
performance level for both existing and new structures.
The "Level 1 orT' refer to the seismic performance cri-
teria (see Section 3104F.2,1),
II
IK
0.35
Curvnturc
Di^tillly
Factor
Biaxial DucUfNy
Uniajtlat Ductility {
Asirefiimcfit
He^pk
AiSfirssDfteitt
Dcsigf»
1
0.29/3,5
0J$/3J
0.29/3,5
0.25 /3,tt
3
0.29/3.5
0.25/ 3.0
5
OJ tvi
0.<m/LO
7
0.1 /1.2
0.083/1.0
13
^MfiU
<MM27a5
15
M%iM
0.042/0.5
k Sliinils/IJSjRUs
- 3.5
3.0
V^-kvCA,
gn
1J2
3,6
.5
8 10 12
Curvature DyctlHty Factor
FIGURE 31 F-7'6
CONCRETE SHEAR MECHANISM
(from Fig. 3-30 of [7.2])
16
ia
20
556
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
For all nonseismic loading combinations, concrete
components shall be designed in accordance with the
ACI requirements [7.5],
Note that for existing facilities, the pile/deck hinge may
be controlled by the capacity of dowel reinforcement in
accordance with Section 317E2. Z
TABLE 31 F-7'5
LIMITS OF STRAIN
COMPONENT STRAIN
LEVEL 1
LEVEL 2
MCCS
Pile/deck hinse
z,< 0.004
e^ < 0.025
MCCS
In-Ground hinge
t,<0M4
z,< 0,008
MRSTS
Pile/deck hinge
E,<0.01
E,<0.05
MRSTS
In-ground hinge
e, < 0.01
e,< 0.025
MPSTS
In-ground hinge
Ep< 0.005
(incremental)
tp< 0.025
(total strain)
MCCS - Maximum Concrete Compression Strain, e^
MRSTS = Maximum Reinforcing Steel Tension Strain, e^
MPSTS = Maximum Prestressing Steel Tension Strain, e^
3107F,2,5J Shear design. If expected lower hound of
material strength Section 3107E2JJ Equations (7-2a,
7'2h, 7-2c) are used in obtaining the nominal shear
strength, a new nonlinear analysis utilizing the upper
bound estimate of material strength Section 3107F.2JJ
Equations (7-3a, 7-3 b, 7- 3c) shall be used to obtain the
plastic hinge shear demand. An alternative conservative
approach is to multiply the maximum shear demand, V.^^
from the original analysis by 1.4 (Section 8.16.4.4.2 of
ATC-32 [7.6]):
design
■■ 1.4V™
(7-13)
If moment curvature analysis that takes into account
strain-hardening, an uncertaintyfactor of 1.25 maybe used:
^design ^•'^-'^ m
(7-14)
Shear capacity shall be based on nominal material
strengths, and reduction factors according to ACI-318
[7.5].
As an alternative, the method of Kowaiski and
I I Priestley [7. 7] may be used. Their method is based on a
three -parameter model with separate contributions to
shear strength from concrete (VJ, transverse reinforce-
ment (VJ, and axial load (Vp) to obtain nominal shear
strength (VJ:
v„ =v +y +v
(7-15)
A shear strength reduction factor of 0.85 shall be
applied to the nominal strength, V„, to determine the
design shear strength. Therefore:
y,esi,n^^-^^n
The equations to determine V^, V^ and Vp are:
Vc=k4f\Ae
(7-16)
(7-17)
k = factor dependent on the curvature ductility
fi^ = , within the plastic hinge region, from
<t>y
Figure 31F-7-6. For regions greater than 2Dp (see
Equation 7-18) from the plastic hinge location, the
strength can be based on \i^-1.0 (see Ferritto et. at.
[7.2]).
f'c = concrete compressive strength
Ag - 0.8Ag is the effective shear area
Circular spirals or hoops [7.2]:
iA^pf^,{Dp-c~c^)coi{d)
V. =-
(7-18)
where:
A^p= spiral or hoop cross section area
fyh - yield strength of transverse or hoop reinforce-
ment
Dp = pile diameter or gross depth (in case of a rect-
angular pile with spiral confinement)
c = depth from extreme compression fiber to neu-
tral axis (IV.A.) atflexural strength (see Fig.
31F-7-7)
Cq = concrete cover to center of hoop or spiral (see
Fig. 31F-7-7)
6 = angle of critical crack to the pile axis (see Fig.
31F-7-7) taken as 30"^ for existing structures,
and 35° for new design
s = spacing of hoops or spiral along the pile axis
N
■4-
5
5
FIGURE 31 F-7'7
TRANSVERSE SHEAR MECHANISM
Rectangular hoops or spirals [7.2]:
_ AJy,{Dp-c-^c^)cot{e)
s
where:
(7-19)
where:
Afj = total area of transverse reinforcement, parallel
to direction of applied shear cut by an inclined
shear crack
2010 CALIFORNIA BUILDING CODE
557
MARINE OIL TERMINALS
Shear strength from axial mechanism, Vp (see Fig,
31F-7-8):
Vp=^(N^^Fp)tana (7-20)
where:
A^„ = external axial compression on pile including
seismic load. Compression is taken as positive;
tension as negative
Fp = prestress compressive force in pile
a = angle between line joining centers offlexural
compression in the deck/pile and in-ground
hinges, and the pile axis
O = 1.0 for existing structures, and 0.85 for new
design
DeckjPile Hmge
^ V - MN^Fp) tan a
N,-*- Fp Compression fc^rce
• En ground hinge
FIGURE 31F-7-8
AXIAL FORCE SHEAR MECHANISM
3107E2.6 Steel piles.
3107FJ,6J General, The capacity of steel piles is based
on allowable strains corresponding to the desired per-
formance criteria and design earthquake.
3107E2.6.2 Stability, Section 3107F.2.5.2 applies to
steel piles.
3107F,2,6,3 Plastic hinge length. The plastic hinge
length depends on the section shape and the slope of the
moment diagram in the vicinity of the plastic hinge.
For plastic hinges forming in steel piles at the deck/pile
interface and where the hinge forms in the steel section
rather than in a special connection detail (such as a rein-
forced concrete dowel connection), allowance should be
made for strain penetration into the pile cap. This increase
may be taken as 0.2 5 Dp, where Dp is the pile diameter or
pile depth in the direction of the applied shear force.
3107F.2.6.4 Ultimate flexural strain capacity. The fol-
lowing limiting value applies:
Strain at extreme-fiber, 8„ < 0.035
3107F.2,6.5 Component acceptance/damage criteria.
The maximum allowable strain may not exceed the ulti-
mate value defined in Section 3107F.2.6.4. Table
3 lF-7 -6 provides limiting strain values for each perfor-
mance level, for both new and existing structures.
Steel components for noncompact hollow piles (Dp
/t <0,07x E/fy ) and for all nonseismic loading com-
binations shall be designed in accordance with AISC
TABLE 31 F-7-6
STRUCTURAL STEEL STRAIN LIMITS, e^
COMPONENTS
LEVEL 1
LEVEL 2
Concrete Filled Pipe
0.008
0.030
Hollow Pipe
0.008
0.025
Level I or 2 refer to the seismic performance criteria (Section 3104E2. 1}
3107F.2.6.6 Shear design. The procedures of Section
3107E2.5, 7, which are used to establish V design ^^^ appli-
cable to steel piles.
The shear capacity shall be established from the AISC
[7.8], For concrete filled pipe, equation (7-15) may be
used to determine shear capacity; however, Vp^^must be
substituted for V^.
V = (^/2)?f.,p,feK -c-c„)cot e (7-21)
where:
t = steel pile wall thickness
fy,piie ~ yield Strength of Steel pile
Co = distance from outside of steel pipe to center of
hoop or spiral
[All other terms are as listed for Equation (7-18)].
3 107 F.2J Pile/deck connection strength,
3107F.2, 7,1 Joint shear capacity. The Joint shear capac-
ity shall be computed in accordance with ACI318 [7.5].
For existing MOTs, the method [7.1, 7.2] given below
may be used:
L Determine the nominal shear stress in the joint
region corresponding to the pile plastic moment
capacity.
0.9M„
(7-22)
^h.D
dv^l
where:
i<
V. = Nominal shear stress
Mp = Overjstrength moment demand of the plastic \ \
hinge (the maximum possible moment in the
pile) as determined from the procedure of
Section 3107F.2.5.7.
l^^ = Vertical development length, see Figure
31F-7-9
D = Diameter of pile
558
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
t<N
-4-
FIGURE31F-7'9
DEVELOPMENT LENGTH
2. Determine the nominal principal tension pt, stress
in the joint region:
Pt =
where:
N
(D.+h,)
(7-23)
(7-24)
is the average compressive stress at the joint center
caused by the pile axial compressive force N and hi is
the deck depth. Note, if the pile is subjected to axial ten-
sion under seismic load, the value ofN, andf will be
negative.
IfPf > 5.0 ^f ^ y psi, joint failure will occur at a lower
moment than the column plastic moment capacity Mp. In
this case, the maximum moment that can be developed at
the pile/deck interface will be limited by the joint princi-
pal tension stress capacity, which will continue to
degrade as the joint rotation increases, as shown in Fig-
ure 31F-7-10. The moment capacity of the connection at
which joint failure initiates can be established from
Equations 7-26 and 7-27.
042
H
0.00015 0,0007 0.01 0,04
FIGURE 31 F'7-10
DEGRADA TION OF EFFECTIVE
PRINCIPAL TENSION STRENGTH WITH JOINT
SHEAR STRAIN (rotation) [7. 1, pg. 564]
For Pt = 5.0 ^[f\, determine the corresponding
joint shear stress, vf
(7-25)
^j =4Pt{Pt-fa)
3. The moment capacity of the connection can be
approximated as:
M,=lj^^SyjhX<M^ (7-26)
This will result in a reduced strength and effective
stiffness for the pile in a pushover analysis. The maxi-
mum displacement capacity of the pile should be
based on a drift angle of 0.04 radians.
If no mechanisms are available to provide residual
strength, the moment capacity will decrease to zero as
the joint shear strain increases to 0.04 radians, as
shown in Figure 31F-7-1L
0.0007
0.04
Rotation
FIGURE 31 F-7-11
REDUCED PILE MOMENT CAPACITY
If deck stirrups are present within h/2 of the face of
the pile, the moment capacity, M^^ at the maximum
plastic rotation of 0.04 radians may be increasedfrom
zero to the following (see Figure 3IF-7-12):
M,^,=2AJ^{h,-d,) + N(^-d) (7-27)
A, = Area of slab stirrups on one side of joint
h^ = See Figure 3IF-7-9 (deck thickness)
d^ = Depth from edge of concrete to center of main
reinforcement
In addition, the bottom deck steel (A^, deckbottom)
area within h/2 of the face of the pile shall satisfy:
K^ec^o,.o.^05-A, (7-28)
0.0007
Rotatlim (radians)
FIGURE 31F-7-12
JOINT ROTATION
om
2010 CALIFORNIA BUILDING CODE
559
MARINE OIL TERMINALS
4. Using the same initial stiffness as in Section
3107F.2.5.4, the moment-curvature relationship
established for the pile top can now be adjusted to
account for the joint degradation.
The adjusted yield curvature, ^'y , can be found
from:
t>\ =
<t>yM,
— 12.
M„
(7-29)
M„ is defined in Figure 31F-7-5.
The plastic curvature, ^p, corresponding to a
joint rotation of 0.04 can be calculated as:
<p.=
0.04
(7-30)
Where Lp, is given by equation 7-5.
The adjusted ultimate curvature, (|) '„, can now be
calculated as:
<t>\=<t>,^
(7-31)
Note that M^,. = unless deck stirrups are pres-
ent as discussed above. Examples of adjusted
moment curvature relationships are shown in Fig-
ure 31F-7-13.
pleandloim
FIGURE 31F-7-13
EQUIVALENT PILE CURVA JURE
3107F,2,7.2 Development Length. The development
length, Ij^ is:
hc^
0.025- d,-f
b J ye
(7-32)
When the development length is less than that calcu-
lated by the equation 7-32, the moment capacity shall be
calculated using a proportionately reduced yield
strength, fy^^ for the vertical pile reinforcement:
fye.r=fye~ (7-33)
where:
l^ = actual development length
fy^ = expected yield strength of dowel
3107R2,8 Batter piles.
3107F.2,8,1 Existing ordinary batter piles. Wharves or
piers with ordinary (not fused, plugged or having a seis-
mic release mechanism) batter piles typically have a very
stiff response when subjected to lateral loads in the
direction of the batter The structure often maintains
most of its initial stiffness all the way to failure of the first
row of batter piles. Since batter piles most likely will fail
under a Level 2 seismic event, the following method may
be used to evaluate the post-failure behavior of the wharf
or pier:
1. Identify the failure mechanism of the batter
pile-deck connection (refer to Section 3104F.4. 7)
for typical failure scenarios) and the correspond-
ing lateral displacement.
2. Release the lateral load between the batter pile
and the deck when the lateral failure displacement
is reached.
3. Push on the structure until subsequent failure(s)
have been identified.
As an example, following these steps will result
in a force-displacement (pushover) curve similar
to the one shown in Figure 31F-7-14 for a wharf
supported by one row of batter piles.
Displacement
where:
d}, = dowel bar diameter
fyg - expected yield strength of dowel
f ^ = compressive strength of concrete
In assessing existing details, actual or estimated val-
ues for fy^ andfc rather than nominal strength should be
used in accordance with Section 3107F.2.L1.
FIGURE31F-7-14
PUSHOVER CURVE FOR ORDINARY BATTER PILES
When the row of batter piles fail in tension or
shear, stored energy will be released. The structure
will therefore experience a lateral displacement
demand following the nonductile pile failures. If
the structure can respond to this displacement
demand without exceeding other structural limita-
560
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
•>
tions, it may be assumed that the structure is stable
and will start to respond to further shaking with a
much longer period and corresponding lower seis-
mic demands. The wharf structure may therefore
be able to sustain larger seismic demands follow-
ing the loss of the batter piles than before the loss
of pile capacity^ because of a much softer seismic
response.
The area under the pushover curve before the
batter pile failures is compared to the equivalent
area under the post failure pushover curve (refer to
Figure 31F-7-14). If no other structural limita-
tions are reached with the new displacement
demandy it is assumed that the structure is capable
of absorbing the energy. It should be noted that
even though the shear failure is nonductile, it is
expected that energy will be absorbed and the
damping will increase during the damage of the
piles. The above method is, therefore, considered
conservative.
Following the shear failure of a batter pile row,
the period of the structure increases such that
equal displacement can be assumed when estimat-
ing the post-failure displacement demand. The
new period may be estimated from the initial stiff-
ness of the post-failure system as shown in Figure
3IF-7-I4. A new displacement demand can then
be calculated in accordance with Section 3I04F2.
3I07F,2,8,2 Nonordinary Batter Piles, For the case of a
plugged batter pile system, an appropriate displacement
force relationship considering plug friction may be used
in modeling the structural system.
For fused and seismic release mechanism batter pile
systems, a nonlinear modeling procedure shall be used
and peer reviewed (Section 3I0IF.6.I).
3107F.2.9 Concrete pile caps with concrete deck. Pile
caps and decks are capacity protected components. Use the
procedure of Section 3I07F.2.5.7 to establish the over
strength demand of the plastic hinges. Component capacity
shall be based on nominal material strengths, and reduction
factors according toACI-318 [7.5].
3107F2.9.1 Component acceptance/damage criteria. For
new pile caps and deck. Level 1 seismic performance shall
utilize the design methods inACI-318 [7.5]; Level 2 seismic
performance shall be limited to the following strains:
Deck/pile cap:
Reinforcing steel tension strain:
E,< 0.005
Es<0.01
For existing pile caps and deck, the limiting strain val-
ues are defined in Table 3IF-7-5.
Concrete components for all nonseismic loading com-
binations shall be designed in accordance with ACI 318
[7.5].
3I07E2,9.2 Shear capacity (strength). Shear capacity
shall be based on nominal material strengths; reduction
factors shall be in accordance with ACI3I8 [7.5].
3107F.2.10 Concrete detailing. For new MOTs, the
required development splice length, cover and detailing
shall conform to ACI 318 [7.5], with the following excep-
tions:
1. For pile/deck dowels, the development length may
be calculated in accordance with Section 3107F.2.
7.2.
2. The minimum concrete cover for prestressed con-
crete piles shall be three inches, unless corrosion
inhibitors are used, in which case a cover of
two-and-one-half inches is acceptable.
3. The minimum concrete cover for wharf beams and
slabs, and all concrete placed against soil shall be
three inches, except for headed reinforcing bars
(pile dowels or shear stirrups) the cover may be
reduced to two-and-one-half inch cover at the top
surface only. If corrosion inhibitors are used, a
cover of two-and-one-half inches is acceptable.
3I07F.3 Timber piles and deck components.
3107 F. 3.1 Component strength. The following parameters
shall be established in order to assess component strength:
New and existing components:
1. Modulus of rupture
2. Modulus of elasticity
3. Type and grade of timber
Existing components only:
1. Original cross-section shape and physical dimen-
sions
2. Location and dimension of braced frames
3. Current physical condition of members including
visibe deformation
4. Degradation may include environmental effects
(e.g., decay, splitting, fire damage, biological and
chemical attack) including its effect on the moment of
inertia, I
5. Loading and displacement effects (e.g., overload,
damage from earthquakes, crushing and twisting)
Section 3I04F.2.2 discusses existing material
properties. At a minimum, the type and grade of
wood shall be established. The adjusted design
stress values in the ANSI/AF&PA NDS [7.9] may
be used as default values by replacing the Format
Conversion Factor of ANSI/AF&PA NDS [7.9]
with the factor 2.8 divided by the Resistance Fac-
tor (Table Nl [7.9]).
For deck components, the adjusted design
stresses shall be limited to the values of
ANSI/AF&PA NDS [7.9]. Piling deformation lim-
its shall be calculated based on the strain limits in
accordance with Section 3I07F.3.3.3.
The values shown in the ANSI/AF&PA NDS
[7.9] are not developed specifically for MOTs and
can be used as default properties only if as-built
information is not available, the member is not
2010 CALIFORNIA BUILDING CODE
561
MARINE OIL TERMINALS
II
II
damaged and testing is not performed. To account
for the inherent uncertainty in establishing compo-
nent capacities for existing structures with limited
knowledge about the actual material properties, a
reduction (knowledge) factor ofk- 0.75 shall be
included in the component strength and deforma-
tion capacity analyses in accordance with Section
3107R2.L2.
The modulus of elasticity shall be based on tests
or the ANSI/AF&PA NDS Tables 6A and 6B [7.9],
Alternatively the values shown in Table 31F-7~7
may be used for typical timber piles.
TABLE 31F-7'7 [after (7.9)]
MODULUS OF ELASTICITY (E) FOR TYPICAL TIMBER PILES
SPECIES
E(psl)
Pacific Coast Douglas Fir
1,500,000
Red Oak
1,250,000
Red Pine
1,280,000
Southern Pine
1,500,000
3107E3,2 Deformation capacity of flexural members. The
displacement demand and capacity of existing timber struc-
tures may be established per Section 3104F2.
The soil spring requirements for the lateral pile analysis
shall be in accordance with Section 3I06F.
A linear curvature distribution may be assumed along the
full length of a timber pile.
The displacement capacity of a timber pile can then be
established per Section 3107F.3.3.2,
3107R3J Timber piles,
3107E3JJ Stability, Section 3107K2.5.2 shall apply to
timber piles.
3107F,3,3,2 Displacement capacity, A distinction shall
be made between a pier-type pile, with a long unsup-
ported length and a wharf-landside -type pile with a short
unsupported length between the deck and soil. The effec-
tive length, L, is the distance between the pinned
deck/pile connection and in- ground fixity as shown in
Figure 31F-7-15. For pier-type (long unsupported
length) vertical piles, three simplified procedures to
determine fixity or displacement capacity are described
in UFC 4-151-10 [7.10], UFC 3-220-OlA [7.11] and
Chai[7.12].
In order to determine fixity in soft soils, another alter-
native is to use Table 31F-7-8.
The displacement capacity. A, for a pile pinned at the
top, with effective length, L, (see Table 31F-7-8 and UFC
4-151-10[7.10]), and moment, M, is:
A =
ML'
3E1
(7-34)
Pinned P»!s-Deck Connection
^^//■^
/
Assumed In-Ground Fixity
FIGURE31F'7-15
ASSUMED IN-GROUND FIXITY
where:
E = Modulus of elasticity
1 = Moment of inertia
Assuming linear curvature distribution along the pile,
the allowable curvature, ^^, can be established from:
■^■-t
(7-35)
where:
allowable strain limit according to Section
3107F.3.3.3
Cy = distance to neutral axis which can be taken as
D/2, where Dp is the diameter of the pile
The curvature is defined as:
^ EI
The maximum allowable moment therefore becomes:
M^—^EI (7-37)
(7-36) ir
The displacement capacity is therefore given by:
A =
3Z)„
(7-38)
TABLE31F-7-8
DISTANCE BELOW GROUND TO POINT OF FIXITY
PILEEIg
SOFT CLAYS
LOOSE GRANULAR &
MEDIUM CLAYS
< 10^^ lb ir?
lOfeet
8feet
> 10^^ lb in^
Ufeet
10 feet
3107K3.3,3 Component acceptance/damage criteria.
The following limiting strain values apply for each seis-
mic performance level for existing structures:
TABLE31F-7'9
LIMITiNG STRAIN VALUES FOR TIMBER
EARTHQUAKE LEVEL
MAX. TIMBER STRAIN
Level I
0.002
Level!
0.004
For new and alternatively, for existing structures
ANSI/AF&PA NDS [7,9] may be used.
562
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
Timber components for all nonseismic loading combi-
nations shall be designed in accordance with ANSI/
AF&PANDS17.9],
I I 3107K3.3,4 Shear design. To account for material
strength uncertainties, the maximum shear demand,
^max> established from the single pile lateral analysis
shall be multiplied by 1.2:
V =\2V
' demand m
(7-39)
The factored maximum shear stress demand T,„^ in a
circular pile can then be determined:
10 V,,
(7-40)
Jtr
where:
r = radius of pile
For the seismic load combinations, the maximum
allowable shear stress, l^^p^^ity^ ^^ ^^^ design shear
strength, idesignJrom the ANSI/AF&PA NDS [7,9] multi-
plied by a factor of 2.8,
capacity "^-o t- design
(7-41)
The shear capacity must be greater than the maximum
demand.
3107FA Retaining structures. Retaining structures con-
structed of steel or concrete shall conform to AISC [7. 8] orACI
318 [7.5] respectively. For the determination of static and seis-
mic loads on the sheet pile and sheet pile behavior, the follow-
ing references are acceptable: NCEL [7.13], Strom and
Ebeling [7.14], and PIANC TC-7 (Technical Commentary - 7)
[7.15]. The applied loads and analysis methodology shall be
determined by a California registered geotechnical engineer,
and may be subject to peer review.
3107F,5 Mooring and berthing components. Mooring com-
ponents include bitts, bollards, cleats, pelican hooks, capstans,
mooring dolphins and quick release hooks.
Berthing components include fender piles and fenders,
which may be camels, fender panels or wales.
Applicable safety factors to be applied to the demand are
provided in Section 3 103 F. 10.
3107F.5.1 Component strength. The following parameters
shall be established in order to calculate component
strength:
New and existing components:
1. Yield and tensile strength of structural steel
2. Structural steel modulus of elasticity
3. Yield and tensile strength of bolts
4. Concrete infill compressive strength
5. Concrete infill modulus of elasticity
Additional parameters for existing components:
1. Condition of steel including corrosion
2. Effective cross-sectional areas
3. Condition of embedment material such as con-
crete slab or timber deck
3107F.5.2 Mooring and berthing component demand. The
maximum mooring line forces (demand) shall be estab-
lished per Section 3105F Multiple lines may be attached to
the mooring component at varying horizontal and vertical
angles. Mooring components shall therefore be checked for
all the mooring analysis load cases. The maximum demand
on breasting dolphins and fender piles shall be established
according to Sections 3103F.6 and 3105F.
3107F.5.3 Capacity of mooring and berthing components.
The structural and connection capacity of mooring compo-
nents bolted to the deck shall be established in accordance
withAISC [7.8], ACI-318[7.5], ANSl/AF&PANDS [7.9] as
appropriate. The mooring component capacity may be gov-
erned by the strength of the deck material Therefore, a
check of the deck capacity to withstand mooring component
loads shall be performed.
3107F.6 Symbols.
Ag = Effective shear area
Ag = Uncracked, gross section area
Afi = Total area of transverse reinforcement, parallel to
direction of applied shear cut by an inclined shear
crack
A, = Area of reinforcing steel
A^p = Spiral or hoop cross section area
c = Depth from extreme compression fiber to neutral
axis atflexural strength
Co ~ Outside of steel pipe to center of hoop or spiral or
concrete cover to center of hoop or spiral
c^ = Value of neutral axis depth at ultimate strength of
section
D - Pile diameter
D* = Reference diameter of 6 ft
df, = Dowel bar diameter
d^ = Depth from edge of concrete to center of reinforce-
ment
diji = Diameter of the longitudinal reinforcement
D^ - Depth of pile cap
Dp = Pile diameter or gross depth (in case of a rectan-
gular pile with spiral confinement)
e = Eccentricity of axial load
e^ = Allowable strain limit
e^m - ^^^ extreme fiber compression strain
^dcu - Ultimate concrete compressive strain
e^^ = Strain at peak stress of confining reinforcement
e„ = Ultimate steel strain
E - Modulus of elasticity
f\ - Concrete compression strength
f\c = Confined strength of concrete
2010 CALIFORNIA BUILDING CODE
563
MARINE OIL TERMINALS
fp
f,
Jye
Jyh
tyh
= Prestress compression force in pile
= Yield strength of prestress strands
= Yield strength of steel
= Design yield strength of longitudinal or dowel
reinforcement (ksi)
- Yield stress of confining steel
= Yield strength of transverse or hoop reinforcement
fy,piie= Yield Strength of steel pile
fy^^ = Reduced dowel yield strength
h = Width of pile in considered direction
h^ = Deck depth
H = Distance from ground to pile point of
contraflexure
4 = Moment of inertia of uncracked section
h - Effective moment of inertia
Ig = Gross moment of inertia
K = Subgrade modulus
k = Factor dependent on the curvature ductility |J,^ =
^/^yy within the plastic hinge region
k = Knowledge factor
L = The distance from the critical section of the plastic
hinge to the point of contraflexure
Lp = Plastic hinge length
/j^ = Minimum development length
l^ = Existing development length
hv - Vertical development length
Mc = Moment capacity of the connection
M^= Moment capacity at plastic rotation
M„ = Moment at secant stiffness
Mp = Moment as determined from a pushover analysis
at displacements corresponding to the damage
control limit state
My = Moment at first yield
N - Pile axial compressive force
N^ = External axial compression on pile including load
due to earthquake action
p^ = Effective volume ratio of confining steel
Pj = Nominal principal tension
r = Radius of circular pile
s = Spacing of hoops or spiral along the pile axis
t = Pile wall thickness
A = Displacement
O = 7 . Ofor existing structures, and 0, 85 for new design
6 = Angle of critical crack to the pile axis (taken as 30 °
for existing structures, and 35° for new design)
9„ = Plastic rotation
a =
^a =
^. =
K =
^y =
T =
Vc =
Vj =
^ max
V. =
K =
Angle between line joining centers offlexural com-
pression in the deck/pile and in-ground hinges,
and the pile axis
Allowable curvature
Maximum curvature
Plastic curvature
Ultimate curvature
Adjusted ultimate curvature
Yield curvature
Adjusted yield curvature
Maximum shear stress
Concrete shear strength
Joint shear stress
Design shear strength
Maximum shear demand
Nominal shear strength
Transverse reinforcement shear capacity
(strength)
Shear strength of steel pile
II
II
3107K6 References.
[7,1] Priestley, MJ.N, Seible, F. and Calvi, G.M, "Seis- \ \i
mic Design and Retrofit of Bridges, " 1996, New
York.
[7.2] Ferritto, J., Dickenson, S., Priestley N., Werner, S.,
Taylor, C, Burke D., Seelig W., and Kelly, S., 1999,
"Seismic Criteria for California Marine Oil Termi-
nals, Vol.1 and Vol.2,'' Technical Report
TR-2103-SHR, Naval Facilities Engineering Ser-
vice Center, Port Hueneme, CA.
[7.3] Federal Emergency Management Agency, FEMA
-356, Nov. 2000, "Prestandard and Commentary
for the Seismic Rehabilitation of Buildings, " Wash-
ington, D.C.
[7.4] Blakeley, J.P., Park, R., "Prestressed Concrete Sec-
tions with Cyclic Flexure," Journal of the Structural
Division, American Society of Civil Engineers, Vol
99, No. ST8, Augustl973, pp. 1 71 7-1 742, Reston,
VA.
[7.5] American Concrete Institute,AC13 18-05, 2005,
"Building Code Requirements for Structural Con-
crete (318-05) and Commentary (318R-05), "
Farmington Hills, Michigan.
[7.6] Applied Technology Council, 1996, ATC-32,
''Improved Seismic Design Criteria for California
Bridges: Provisional Recommendations,*' Red-
wood City , CA,
[7. 7] Kowalski, M.J. and Priestley, M.J.N., ''Shear Strength
of Ductile Bridge Columns, " Proc. 5'^ Caltrans Seis-
mic Design Workshop, Sacramento, June 1998.
564
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
II
4
[7,8] American Institute of Steel Construction (AISC),
2005, "Steel Construction Manual, " Thirteenth Edi-
tion, Chicago, IL
[7.9] American Forest S. Paper Association, 2005,
"National Design Specificationfor Wood Construc-
tion, "ANSI/AF&PANDS-2005, Washington, D.C
[7.10] Department of Defense, 10 September 2001, Uni-
fied Facilities Criteria (UFC) 4-151-10, "General
Criteria for Waterfront Construction, Washington,
ac
[7.11] Department of Defense, 16 January 2004, Unified
Facilities Criteria (UFC) 3 -220-01 A, "Deep Foun-
dations, " Washington, D.C.
[7,12] Chai, Y.H., "Flexural Strength and Ductility of
Extended Pile-Shafts, I: Analytical Model", Journal
of Structural Engineering, May 2002, pp. 586-594.
[7.13] Ebeling, Robert M. and Morrison, Ernest E., Jr.,
"The Seismic Design of Waterfront Retaining Struc-
tures", U.S. Army Technical Report lTL-92-ll/U,S.
Navy Technical Report NCEL TR 939, Dept. of
Army, Corps of Engineers, Waterways Experiment
Station, Vicksburg, MS, November 1992.
[7,14] Strom, Ralph W. and Robert M. Ebeling, "State of
the Practice in the Design of Tall, Stiff, and Flexible
Tieback Retaining Walls", Information Technology
Laboratory, Engineer Research and Development
Center, U.S. Army Corps of Engineers, Vicksburg,
MS, December 2001.
[7.15] Permanent International Association of Navigation
Congresses (PIANC), "Seismic Design Guidelines
for Port Structures," Technical Commentary-7,
Working Group No. 34 of the Maritime Navigation
Commission International Navigation Association,
A, A. Balkema, Lisse, Netherlands. 2001.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE 565
MARINE OIL TERMINALS
Division 8
SECTION 31 08F
FIRE PREVENTION, DETECTION AND SUPPRESSION
3108E1 General This section provides minimum standards for
fire prevention, detection and suppression atMOTs. See Section
3101 E3 for definitions of ''new" (N) and ''existing" (E).
3108F,2 Hazard assessment and risk analysis.
3108F.2J Fire hazard assessment and risk analysis (N/E),
A fire hazard assessment and risk analysis shall be per-
formed, considering the loss of commercial power, earth-
quake and other relevant events.
3108F,2,2 Fire plan (N/E), A site-specific fire plan shall be
prepared by a registered engineer or a competent fire pro-
tection professional The plan shall consider the hazards
and risks identified per Section 31 08F.2. 1 and shall include,
but not be limited to, the elements of prefire planning as dis-
cussed in Section 9 of [8 J] and Chapter 3 of [8.2]. The fire
plan shall include goals, resources, organization, strategy
and tactics, including the following :
1. MOT characteristics (e.g., tanker/manifold, prod-
uct pipelines, etc.)
2. Product types and fire scenarios
3. Possible collateral fire damage to adjacent facili-
ties
4. Fire-fighting capabilities, including availability of
water (flow rates and pressure), foam type and asso-
ciated shelf life, proportioning equipment, and
vehicular access [8.1, 8.3]
5. The selection of appropriate extinguishing agents
[8.1, 8.2]
6. Calculation of water and foam capacities, as appli-
cable, consistent with area coverage requirements
[8.1]
7. Coordination of emergency efforts
8. Emergency escape routes [8.2, 8.3]
9. Requirements for fire drills, training of personnel,
and the use of equipment
10. Life safety
1 1 . Rescue for terminal and vessel personnel [8. 1]
12. Cooling water for pipelines and valves exposed to
the heat
13. Contingency planning when supplemental fire sup-
port is not available. Mutual aid agreements can
apply to water and land based support
14. Consideration of adverse conditions, such as electri-
cal power failure, steam failure, fire pump failure, an
earthquake or other damage to the fire water system.
The audit team shall review and field verify the fire-fight-
ing equipment locations and condition and may check its
operability.
3108F.2,3 Cargo liquid and fire hazard classifications
(N/E), The cargo liquid hazard classes are defined in Table
31F-8-1, as either High (H^) or Low (L^), depending on the
flash point.
Fire hazard classifications (Low, Medium or High) are
defined in Table 31F-8-2, and are based on the cargo liquid
hazard class and the sum of all stored and flowing volumes,
prior to the emergency shut down system (ESD) stopping the
flow of oil.
The stored volume is the sum of the H^ andL^ liquid hazard
class piping volumes (V^h and V^J, if the piping is not
stripped.
During a pipeline leak, a quantity of oil is assumed to spill at
the maximum cargo flow rate until the ESD is fully effective.
The ESD valve closure is required to be completed in 60 sec-
onds if installed prior to November 1, 1980 or in 30 seconds if
installed afier that date (2 CCR 2380(h) (3))[8.3]. Thefiowing
volume is the sum of the Hq andL^ liquid hazard class volumes
(Vpij and Vpi), and shall be calculated as follows:
Vp =GcXArx (1/3,600)
where:
(8-1)
Vp = Flowing Volume f V^h or Vpi^ ) [bbl]
Qc = Cargo Transfer Rate [bbUhr]
A^ = ESD time, 30 or 60 seconds
3108F3 Fire prevention.
3108F.3J Ignition source control
3108F.3.1.1 Protection from ignition by static electricity,
lightning or stray currents shall be in accordance with
API RP 2003 [8.5](N/E).
3108F.3.I,2 Requirements to prevent electrical arcing
shall be in conformity with 2 CCR 2341 [8.3] (N/E).
3108F,3JJ Multiberth terminal piers shall be con-
structed so as to provide a minimum of 100 ft between
adjacent manifolds (N).
3108F,3,2 Emergency shutdown systems. An essential
measure of fire prevention is communications in conjunc-
tion with the emergency shutdown. The ESD and isolation
system shall conform to2 CCR 2380 (h) [8.3] and 33 CFR
154.550 [8.6]. An ESD system shall include or provide:
1. An ESD valve, located near the dock manifold con-
nection or loading arm (N/E).
2. ESD valves, with "Local" and "Remote" actuation
capabilities (N).
3. Remote actuation stations strategically located, so
that ESD valve(s) may be shut within required times
(N).
4. Multiple actuation stations installed at strategic
locations, so that one such station is located more
than 100 feet from areas classified as Class I, Group
D, Division 1 or2 [8. 7]. Actuation stations shall be
566
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
TABLE 31 F-8'1
CARGO LIQUID HAZARD CLASS
CLASS
CRITERION
REFERENCE
EXAMPLES
Low (Lc)
Flash Point >140°F
ISGOTT (Chapter 1, [8.4]} —Nonvolatile
#6 Heavy Fuel Oil, residuals, hunker
High (He)
Flash Point <140°F
ISGOTT (Chapter 1, [8.4])— Volatile
Gasoline, JP4, crude oils
TABLE 31 F-8-2
FIRE HAZARD CLASSIFICATIONS
CLASS
STORED VOLUME (bbl)
FLOWING VOLUME (bbl)
CRITERIA (bbls)*
Stripped
VSL
VSH
y^FL
^FH
LOW
y
n
n
y
y
VfL>Vpfj> and Vj-< 1200
LOW
n
y
n
y
n
VsL+V^L<1200
MEDIUM
n
n
y
n
y
Vs^+V^f,<1200
MEDIUM
y
n
n
y
y
Vph>Vfd and Vt< 1200
HIGH
n
n
y
n
y
VsH+V,^>I200
HIGH
y
n
n
y
y
Vj>1200
HIGH
n
y
y
y
y
Vj>1200
HIGH
n
y
n
y
n
VsL+Vj.^>I200
HIGH
n
n
y
n
y
VsH^yfH>1200
y = yes
n~ no
Stripped = product purged from pipeline following product transfer event.
V^^ = stored volume of low-hazard class product
V^fj = stored volume of high-hazard class product
^FL - volume of low-hazard class product flowing through transfer line during 30 - 60 sees. BSD.
^FH - volume of high-hazard class product flowing through transfer line during 30 - 60 sees. BSD.
^T - YsL ^ ^SH "*" ^FL ^ ^FH ~ Total Volumc (stored and flowing)
* Quantities are based on maximum flow rate, including simultaneous transfers.
wired in parallel to achieve redundancy and
arranged so that fire damage to one station will not
disable the BSD system (N).
5. Communications or control circuits to synchronize
simultaneous closure of the shore isolation valves
(SIVs) with the shut down of loading pumps (N).
6. A manual reset to restore the BSD system to an oper-
ational state after each initiation (N).
7. An alarm to indicate failure of the primary power
source (N).
8. A secondary (emergency) power source (N).
9. Periodic testing of the system (N).
10. Fire proofing of motors and control-cables that are
installed in areas classified as Class /, Group D,
Division 1 or 2 [8.7], Fire proofing shall, at a mini-
mum, comply with the recommendations of API
Publication 2218 (see Section 6 of [8.8]) (N).
3108F.33 Shore Isolation valves (SIV), Shore isolation
valve(s) shall:
L Be located onshore for each cargo pipeline. All SIVs
shall be clustered together, for easy access (N).
2. Be clearly identified together with associated pipe-
line (N/B).
3. Have adequate lighting (N/E),
4. Be provided with communications or control circuits
to synchronize simultaneous closure of the BSD sys-
tem with the shut down of loading pumps (N).
5. Have a manual reset to restore the SIV system to an
operational state after each shut down event (N).
6. Be provided with thermal expansion relief to accom-
modate expansion of the liquid when closed. Ther-
mal relief piping shall be properly sized and routed
around the SIV, into the downstream segment of the
pipeline or into other containment (N/E).
SIVs installed in pipelines carrying hazard class,
HC liquids, or at a MOT with a risk classification
"Medium" or '"High" (see Table 31F-4-1), shall be
equipped with ''Local" and ''Remote" actuation
capabilities. Local control SIVs may be motorized
and/or operated manually (N).
3108F,4 Fire detection. An MOT shall have a permanently
installed automated fire detection or sensing system (N).
3108F.5 Fire alarms. Automatic and manual fire alarms shall
be provided at strategic locations. The fire alarm system shall
be arranged to provide a visual and audible alarm that can be
readily discerned by all personnel at the MOT. Additionally,
2010 CALIFORNIA BUILDING CODE
567
MARINE OIL TERMINALS
visual and audible alarms shall be displayed at the Facility 's
Control Center (N/E).
If the fire alarm system is integrated with the BSD system,
the operation shall be coordinated with the closure ofSIVs,
block valves and pumps to avoid adverse hydraulic condi-
tions (N/E).
3108F.6 Fire suppression. Table 31F-8-3 gives the minimum
provisions for fire-water flow rates and fire extinguishers. The
table includes consideration of the fire hazard classification
(Low, Medium or High), the cargo liquid hazard class (Low or
High) and the vessel or barge size. The minimum provisions
may have to be augmented for multi-berth terminals or those
conducting simultaneous transfers, in accordance with the
risks identified in the Fire Plan.
3108F.6.1 Coverage (N/E). The fire suppression system
shall provide coverage for:
L Marine structures including the pier/wharf and
approach trestle
2. Terminal cargo manifold
3. Cargo transfer system including loading arms, hoses
and hose racks
4. Vessel manifold
5. Sumps
6. Pipelines
7. Control stations
3108F,6,2 Fire hydrants. Hydrants shall be located not
greater than 150ft apart, along the wharf and not more than
300 ft apart on the approach trestle [8.4] (N). Additional
hose connections shall be provided at the base of fixed mon-
itors and upstream of the water and foam isolation valves.
Connections shall be accessible to fire trucks or mutual aid
equipment as identified in the fire plan.
Hydrants and hoses shall be capable of applying two
independent water streams covering the cargo manifold,
transfer system, sumps and vessel manifold (N/E).
3108F,6,3 Fire water. The source of fire water should be
reliable and provide sufficient capacity as determined in the
fire plan.
L All wet systems shall be kept pressurized (jockey
pump or other means) (N/E),
2. Wet system headers shall be equipped with a
low-pressure alarm wired to the control room (N).
3. Fire pumps shall be installed at a distance of at least
100 ft from the nearest cargo manifold area (N).
4. Hose connections for fireboats or tugboats shall be
provided on the MOT fire water line, and at least one
connection shall be an international shore fire con-
nection at each berth [8.4]. Connections shall be
installed at a safe access distance from the high-risk
areas such as sumps, manifolds and loading arms
(N/E).
3 108F,6.4 Foam supply (N/E). Product flammability, foam
type, water flow rates and application duration shall be
considered in foam supply calculations.
Fixed foam proportioning equipment shall be located at a
distance of at least 100 ft from the high-risk areas such as
sump, manifold and loading arms, except where hydraulic
limits of the foam delivery system require closer proximity.
MOTs shall have a program to ensure that foam is replaced
according to the manufacturer's recommendations.
TABLE 31 F-8'3
MINIMUM FIRE SUPPRESSION PROVISIONS (N/E)
FIRE HAZARD CLASSIFICATION
(From Table 31 F-6-2)
VESSEL AND CARGO LIQUID HAZARD CLASS
(From Table 31F-S'1)
MINIMUM PROVISIONS
LOW
Barge with Lq (including drums)
500 gpm of water
2x20 lb portable dry chemical and 2 x 110 lb wheeled dry
chemical extinguishers or the equivalent.
Barge with Hq (including drums)
Tankers < 50 KDWT , handling Lc or He
1,500 gpm of water
2x20 lb portable dry chemical and 2 x 165 lb wheeled dry
chemical extinguishers or the equivalent
MEDIUM
Tankers < 50 KDWT handling Lq
1,500 gpm of water
2x20 lb portable dry chemical and 2 x 165 lb wheeled dry
chemical extinguishers or the equivalent.
Tankers < 50 KDWT, handling He
2,000 gpm of water
4x20 lb portable dry chemical and 2 x 165 lb wheeled dry
chemical extinguishers or the equivalent.
HIGH
Tankers < 50 KDWT, handling Lc or He
3,000 gpm of water
4 X 20 lb portable dry chemical and 2 x 165 lb wheeled dry
chemical extinguishers or the equivalent.
LOW, MEDIUM, HIGH
Tankers > 50 KDWT , handling Lc or He
3,000 gpm of water
6x20 lb portable dry chemical and 4 x 165 lb wheeled dry
chemical extinguishers or the equivalent.
Notes: L^ and H^ are defined in Table 31F-8-1. KDWT = Dead Weight Tons (Thousands)
568
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
3108F,6,5 Fire monitor systems. Fire monitors shall be
located to provide coverage of MOT cargo manifolds, load-
ing arms, hoses, and vessel manifold areas. This coverage
shall provide at least two independent streams of
water/foam. Monitors shall be located to provide an unob-
structed path between the monitor and the target area (WE).
If the vessel manifold is more than 30 ft above the wharf
deck, the following factors shall be considered, in order to
determine if monitors located on elevated masts or towers
are required (N/E):
1. Maximum tanker freeboard
2. Tidal variations
3. Pier/wharf/loading platform elevation
4. Winds
5. Fire water line pressure
Sprinklers and/or remotely controlled water/foam moni-
tors shall be installed to protect personnel, escape routes,
shelter locations and the fire water system (N),
Isolation valves shall be installed in the fire water and the
foam lines in order to segregate damaged sections without
disabling the entire system. Readily accessible isolation
valves shall be installed 100 -150 ft from the manifold and
the loading arm/hose area (N).
3108F,6,6 Supplemental Fire Suppression Systems (E). A
supplemental system is an external waterborne or land-
based source providing suppressant and equipment. Sup-
plemental systems may not provide more than one-quarter
of the total water requirements specified in the fire plan.
Additionally, supplementary systems shall not be consid-
ered in afire plan, unless available within 20 minutes fol-
lowing the initiation of a fire alarm. Mutual aid may be
considered as part of the supplemental system.
3108FJ References.
[8.1] American Petroleum Institute, 1998, API Recom-
mended Practice 2001 (APIRP 2001), "Fire Protec-
tion in Refineries, " 7^^ ed., Washington, D.C.
[8,2] Oil Companies International Marine Forum
(OCIMF), 1987, ''Guide on Marine Terminal Fire
Protection and Emergency Evacuation, " P' ed.,
Witherby, London.
[8.3] 2 CCR 2300-2407 (Title 2, California Code of Regu-
lations, Sections 2300-2407).
[8.4] International Chamber of Shipping (ICS), Oil Compa-
nies International Marine Forum (OCIMF), Intema-
I I tional Association of Ports and Harbors (lAPH), 2006,
*' International Safety Guide for Oil Tankers and Ter-
minals (ISGOTT), " 5'^ ed., Witherby, London.
[8.5] American Petroleum Institute, 1998, API Recom-
mended Practice 2003 (APIRP 2003), ''Protection
Against Ignitions Arising Out of Static, Lightning,
and Stray Currents, " &^ed., Washington, D.C.
[8.6] 33 CFR 154.550 (Title 33, Code of Federal Regula-
tions, Section 1 54.550).
[8,7] National Fire Protection Association, 2008, NFPA
70 (Article 500), ''National Electric Code, " Quincy,
MA.
[8.8] American Petroleum Institute, 1999, API Publication
2218, "Fireproofing Practices in Petroleum and Pet-
rochemical Processing Plants, " 2"^ ed., Washington,
D.C.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE
569
MARINE OIL TERMINALS
Division 9
SECTION 31 09F
PIPING AND PIPELINES
3109F.1 General This section provides minimum engineering
standards for piping, pipelines, valves, supports and related
appurtenances at MOTs. This section applies to piping and
pipelines used for transferring:
L Oil (see Section 3101F.1) to or from tank vessels or
barges
2. Oil within the MOT
3. Vapors, including Volatile Organic Compounds (VOCs)
4. Inerting or enriching gases to vapor control systems
Additionally, it also applies to piping or pipelines providing
services, which includes stripping, sampling, venting, vapor
control and fire water.
See Section 3101 E3 for definitions of ''new'* (N) and "exist-
ing" (E),
3109K2 Oil piping and pipeline systems. All pressure piping
and pipelines for oil service shall conform to the provisions of
API Standard 2610 [9,1], ASMEB3L3 [9,2] orB3L4 [9.3] as
appropriate, including the following:
L All piping/pipelines shall be documented on current
P&ID's (N/E).
2. Piping and pipeline systems shall be installed above
deck (N).
3. The systems shall be arranged in a way not to obstruct
access to and removal of other piping components and
equipment (N).
4. Flexibility shall be achieved through adequate expan-
sion loops or joints (N/E),
5. A guide or lateral restraint shall be provided just past
the elbow where a pipe changes direction in order to
minimize excessive axial stress (N).
6. Piping shall be routed to allow for movement due to
thermal expansion and seismic displacement, without
exceeding the allowable stresses in the supports, and
anchor connections (see Section 3109F.3) (N/E).
7. Plastic piping shall not be used unless designated for
oil service (N/E).
8. If a flanged connection exists within 20 pipe diameters
from the end of any replaced section, the pipe shall be
replaced up to and including the flange.
9. Pipelines shall be seamless, electric-resistance-welded
or electric-fusion-welded (N).
10. Piping greater than 2 inches in diameter shall be
butt-welded. Piping 2 inches and smaller shall be
socket welded or threaded.
11. Pipeline connections directly over the water shall be
welded (N). Flanged connections not over water shall
have secondary containment (N).
12. Pipelines that do not have a valid and certified Static
Liquid Pressure Test (SLPT) [9.4] shall be marked
"OUT OF SERVICE. " Out-of- service piping and pipe-
lines shall be purged, gas-freed and physically isolated
from sources of oil.
13. If a pipeline is "out-of-service "for 3 or more years, it
will require Division approval prior to re-use.
3109F3 Pipeline stress analysis (N/E). Pipeline stress analy-
sis shall be performed for:
1. New piping and pipelines
2. Significant rerouting/relocation of existing piping
3. Any replacement of ''not in-kind" piping
4. Any significant rearrangement or replacement of ''not
in-kind" anchors and/or supports
5. Significant seismic displacements calculated from the
structural assessment
Piping stress analysis shall be performed in accordance with
ASME B3L4 [9.3], considering all relevant loads and corre-
sponding displacements determined from the structural analy-
sis described in Section 3104F
Flexibility analysis for piping, considering supports, shall
be performed in accordance with ASME B31.4 [9.3] by using
the largest temperature differential imposed by normal opera-
tion, start-up, shutdown or abnormal conditions. Thermal
loads shall be based upon maximum and minimum local tem-
peratures; heat traced piping shall use the maximum attain-
able temperature of the heat tracing system.
To determine forces at sliding surfaces, the coefficients of
static friction shown in Table 3 IF -9-1 shall be used.
TABLE 31 09F-9'1
COEFFICIENTS OF STATIC FRICTION
SLIDING SURFACE MATERIALS
COEFFICIENT OF STATIC FRICTION
Teflon on Teflon
0.10
Plastic on Steel
0.35
Steel on Steel
0.40
Steel on Concrete
0.45
Steel on Timber
0.49
3109F,4 Anchors and supports. Anchors and supports shall
conform to ASME B3L3 [9,2], ASME B31.4 [9.3], API Stan-
dard 2610 [9.1] and the ASCE Guidelines [9.5](N).
A seismic assessment shall be performed for existing anchors
and supports using recommendations in Section 7 of CalARP
[9.6] or Chapter 11 ofFEMA 356 [9,7], as appropriate (E).
3109E5 Appurtenances.
3109F.5J Valves and fittings. Valves andfittings shall meet
the following requirements:
1. Conform to ASME B3L4 [9.3], API Standard 609
[9.8] and ASME B16.34 [9.9], as appropriate,
based on their service (N).
2. Conform to Section 8 of [9.1] (N/E),
570
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
3. Stems shall be oriented in a way not to pose a hazard
in operation or maintenance (N/E),
4. Nonductile iron, cast iron, and low-melting temper-
ature metals shall not be used in any hydrocarbon
service, fire water or foam service (N/E).
5. Double-block and bleed valves shall be used for
manifold valves. (N/E).
6. Isolation valves shall be fire-safe, in accordance
with API Standard 607 [9 JO] (N).
7. Swing check valves shall not be installed in vertical
down-flow piping (N/E).
8. Pressure relief devices shall be used in any closed
piping system that has the possibility of being over
pressurized due to temperature increase (thermal
relief valves) or surging (N/E).
9. Pressure relief devices shall be sized in accordance
with API RP 520 [9.11] (N). Set pressures and accu-
mulating pressures shall be in accordance with
[9.11] (N).
10. Discharge from pressure relief valves shall be
directed into lower pressure piping for recycling or
proper disposal Discharge shall never be directed
into the open environment, unless secondary con-
tainment is provided (N/E).
11. Threaded, socket-welded, flanged and welded fit-
tings shall conform to Section 8 of [9.1] (N/E).
3I09F.5,2 Valve actuators (N/E).
1. Actuators shall have a readily accessible, manually
operated overriding device to operate the valve dur-
ing a power loss.
2. Torque switches shall be set to stop the motor closing
operation at a specified torque setting.
3. Limit switches shall be set to stop the motor opening
operation at a specified limit switch setting.
4. Critical valves shall be provided with thermal insula-
tion. The insulation shall be inspected and maintained
at periodic intervals. Records of thermal insulation
inspections and condition shall be maintained for at
least 6 years.
5. Electrical insulation for critical valves shall be mea-
sured for resistance following installation and
retested periodically. These records shall be main-
tained for at least 6 years.
3109F.6 Utility and auxiliary piping systems. Utility and aux-
iliary piping includes service for:
1. Stripping and sampling
2. Vapor control
3. Fire water and foam
4. Natural gas
5. Compressed air, venting and nitrogen
Stripping and sampling piping shall conform to Section
3109F.2 (N/E).
Vapor return lines and VOC vapor inerting and enriching
(natural gas) piping shall conform to 33 CFR 154.808 [9.12]
and API RP 1124 [9.13] (N).
Firewater and foam piping and fittings shall meet the follow-
ing requirements:
L Conform to ASME B16.5 [9.1 4]
2. Fire mains shall be carbon steel pipe (N/E)
3. High density polyethylene (HDPE) piping may be used
for buried pipelines (N/E)
4. Piping shall be color-coded (N/E)
Compressed air, venting and nitrogen piping and fittings
shall conform to ASME B 31.3 [9.2] (N).
3109FJ References.
[9. 1 ] American Petroleum Institute (API), 1 994, API Stan-
dard 2610, ''Design, Construction, Operation,
Maintenance, and Inspection of Terminal and Tank
Facilities,'' ANSI/API STD 2610-1994, P^ed., Wash-
ington, D.C.
[9.2] American Society of Mechanical Engineers
(ASME), 1998, ASME B31.3, ''Process Piping, "
New York.
[9.3] American Society of Mechanical Engineers
(ASME), 1998, ASME B31.4, "Pipeline Transpor-
tation Systems For Liquid Hydrocarbons And Other
Liquids, '* New York.
[9.4] 2 CCR 2550 - 2556, 2560 - 2571 (Title 2, California
Code of Regulations (CCR), Sections 2550-2556,
2560-2571).
[9.5] AmericanSociety of Civil Engineers, 1997, "Guide-
lines for Seismic Evaluation and Design of Petro-
chemical Facilities, " New York.
[9.6] CalARP Program Seismic Guidance Committee,
January 2004, "Guidance for California Accidental
Release Prevention (CalARP) Program Seismic
Assessments, " Sacramento, CA.
[9.7] Federal Emergency Management Agency, Nov.
2000, FEMA 356, "Prestandard and Commentary
for the Seismic Rehabilitation of Buildings, " Wash-
ington, D. C.
[9.8] American Petroleum Institute (API), 1997, API
Standard 609, "Butterfly Valves: Double Flanged,
Lug- and Wafer-Type, " 5^^ed., Washington, D.C.
[9.9] American Society of Mechanical Engineers
(ASME), 1996, ASME B16.34, "Valves Flanged
Threaded And Welding End, " New York.
[9.10] American Petroleum Institute (API), 1996, API
Standard 607, "Fire Test for Soft-Seated Quar-
ter-Turn Valves, " 4'^ed., 1993 (reaffirmed 4/1 996),
Washington, D.C.
[9.11] American Petroleum Institute (API), 2000, APIRP
520, "Sizing, Selection, and Installation of Pres-
sure-relieving Devices in Refineries, Parti — Sizing
and Selection, " 7th ed., and Part II — Installation,
2003, 5'^ed., Washington, D.C.
2010 CALIFORNIA BUILDING CODE
571
MARINE OIL TERMINALS
[9,12] 33 CFR 1 54.808 ~~ Vapor Control Systems, Gen-
eral (Title 33, Code of Federal Regulations (CFR),
Section 1 54.808).
[9 J 3] American Petroleum Institute (API), 1991, Recom-
mended Practice 1124 (APIRP 1124), "Ship,
Barge, and Terminal Hydrocarbon Vapor Collec-
tion Manifolds, " P^ ed., Washington, D.C
[9.14] American Society of Mechanical Engineers
(ASME), 1996, ASME B16.5, "Pipe Flanges and
Flanged Fittings, " New York,
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
572 2010 CALIFORNIA BUILDING CODE
Division 10
MARINE OIL TERMINALS
iECTiON3110F
MECHANICAL AND ELECTRICAL EQUIPMENT
3110R1 General This section provides the minimum stan-
dards for mechanical and electrical equipment at MOTs.
See Section 31 OIF. 3 for definitions of ''new'' (N) and ''exist-
ing'' (E).
3110F.2 Marine loadltg arms,
3110F.2.1 Generai criteria. Marine loading arms and
ancillary systems si tail conform to 2 CCR 2380 (b) [10.1],
33 CFR 154.510 [1 1.2] and the "Design and Construction
Specification for Marine Loading Arms," [10.3].
The following shall be considered when determining the
loading arm maximum allowable extension limits:
1. Vessel sizes and manifold locations
2. Lowest-low water level (datum)
3. Highest-high water level
4. Maximum vessel surge and sway
5. Maximum width offendering system
3110R2,2 Electrical and hydraulic power systems.
3110F,2,2.1 Pressure and control systems (N),
1. Pressure gauges shall be mounted in accordance
with ASME B40.100-1 998 [10.4].
2. The hydraulic drive cylinders shall be mounted
and meet either the mounting requirements of
ANS1/(NFPA) T3. 6. 7 R2 -1 996 [10.5] or equiva-
lent.
3. In high velocity current (> 1.5 knots) areas, all new
marine loading arms shall befitted with quick dis-
connect couplers and emergency quick release
systems in conformance with Sections 6.0 and 7.0
of [10.3]. In complying with this requirement,
attention shall be paid to the commentary and
guidelines in Part III of reference [10.3].
4. Out-of-limit, balance and the approach of
out-of -limit alarms shall be located at or near the
loading arm console.
3110F,2,2,2 Electrical components (N), The following
criteria shall be implemented:
1. Equipment shall be provided with a safety discon-
necting device to isolate the entire electrical sys-
tem from the electrical mains in accordance with
Article 430 of the National Electric Code (NEC),
[10,6],
2. Motor controllers and 3-pole motor overload pro-
tection shall be installed and sized in accordance
with Article 430, NEC [10.6].
3. Control circuits shall be limited to 120 volts and
shall comply with Articles 500 and 501 of the NEC
[10.6]. Alternatively, intrinsically safe wiring and
controls may be provided in accordance with Arti-
cle 504, NEC [10.6] and ANSI/UL Std. No. 913
[10.7].
4. Grounding and bonding shall comply with the
requirements of Article 430, NEC [10.6] and Sec-
tion 311 IF.
Section 311 IF includes requirements for electrical
equipment, wiring, cables, controls and electrical auxil-
iaries located in hazardous areas.
3110F,2.2.3 Remote operation. The remote control sys-
tem, where provided, shall conform to the recommenda-
tions of the OCIMF [10.3]. The remote operation shall
be facilitated by either a pendant control system or by a
hand-held radio controller (N).
The pendant control system shall be equipped with a
plug-in capability to an active connector located either
in the vicinity of the loading arms, or at the loading arm
outboard end on the triple swivel, and hard-wired into
the control console. The umbilical cord running from the
triple swivel to the control console shall be attached to
the loading arm. Other umbilical cords shall have suffi-
cient length to reach the maximum operational limits
(N).
The radio controller if installed shall comply with 2
CCR 2370(e) [10.8] and 47CFR Part 15 [10.9] require-
ments for transmitters operating in an industrial envi-
ronment (N/E).
3110F.3 Oil transfer hoses (N/E), Hoses for oil transfer ser-
vice shall be in compliance with 2 CCR 2380 (a) [10.10] and
33 CFR 154.500 [10.11].
Hoses with diameters of 6 inches or larger shall have flanges
that meet ANSIBl 6.5 [10.12]. Hoses with diameters of 4
inches or less may have quick disconnect fittings provided that
they meetASTM F-1122 [10.13].
3110F.4 Lifting equipment: winches and cranes. Lifting
equipment shall conform to [10.1 4], [10.15], [10.16] and
[10.1 7], Electrical equipment shall conform to the provisions
of Section 311 IF
3110F.4,1 Winches.
1. Winches and ancillary equipment shall be suitable for
a marine environment (N/E).
2. Winches shall be provided with a fail-safe braking
system, capable of holding the load under all condi-
tions, including a power failure (N/E).
3. Winches shall be fully reversible (N).
4. Shock, transient and abnormal loads shall be consid-
ered when selecting winch systems (N).
5. Winches shall have limit switches and automatic trip
devices to prevent over-travel of the drum in either
direction. Limit switches shall be tested, and demon-
strated to function correctly under operating condi-
2010 CALIFORNIA BUILDING CODE
573
MARINE OIL TERMINALS
tions without inducing undue tensions or slack in the
winch cables (N/E).
6. Under all operating conditions, there shall be at least
two full turns of cable on grooved drums, and at least
three full turns on ungrooved drums (N/E).
7. Moving winch parts which present caught-in hazards
to personnel shall be guarded (N/E),
8. Winches shall have clearly identifiable and readily
accessible stop controls (N/E).
3110K4,2 Cranes (N/E).
1. Cranes shall not be loaded in excess of the manufac-
turer's rating except during performance tests.
2. Drums on load-hoisting equipment shall be equipped
with positive holding devices.
3. Under all operating conditions, there shall be at least
two full turns of cable on grooved drums, and at least
three full turns on ungrooved drums,
4. Braking equipment shall be capable of stopping, low-
ering, and holding a load of at least the full test load.
5. When not in use, crane booms shall be lowered to
ground level or secured to a rest support against dis-
placement by wind loads or other outside forces,
6. Safety systems including devices that affect the safe
lifting and handling, such as interlocks, limit
switches, load/moment and overload indicators with
shutdown capability, emergency stop switches,
radius and locking indicators, shall be provided
[10.18].
3110F,5 Shore-to-vessel access for personnel This section
applies to shore-to-vessel means of access for personnel and
equipment provided by the terminal. This includes ancillary
structures and equipment, which support, supplement, deploy
and maneuver such vessel access systems.
Shore-to-vessel access for personnel shall conform to 29
CFR 1918.22 [10.19], Sections 19(b) and 21(h) of[10.20].
Chapter 16.4 of [10.21] and the following:
1. Shore-to-vessel access systems shall be designed to with-
stand the forces from dead, live, wind, vibration, impact
loads and the appropriate combination of these loads.
The design shall consider all the critical positions of the
system in the stored, maintenance, maneuvering and
deployed positions, where applicable (N).
2. The minimum live load shall be 50 psfon walkways and
25 plfwith a 200 pounds minimum concentrated load in
any location or direction on handrails (N).
3. The walkway shall be not less than 36 inches in width
(N)and not less than 20 inches for existing walkways (E).
4. The shore-to-vessel access system shall be positioned so
as to not interfere with the safe passage or evacuation of
personnel (N/E),
5. Guardrails shall be provided on both sides of the access
systems with a clearance between the inner most sur-
faces of the guardrails of not less than 36 inches and
shall be maintained for the full length of the walkway
(N).
6. Guardrails shall be at a height not less than 33 inches
above the walkway surface and shall include an interme-
diate rail located midway between the walkway surface
and the top rail (N/E).
7. The walkway surface, including self-leveling treads, if so
equipped, shall be finished with a safe nonslip footing
accommodating all operating gangway inclinations <
(N/E).
8. Under no circumstances shall the operating inclination
of the walkway exceed 60 degrees from the horizontal or
the maximum angle recommended by the manufacturer,
whichever is less (N/E).
9. The undersides of aluminum gangways shall be pro-
tected with hard plastic or wooden strips to prevent
being dragged or rubbed across any steel deck or com-
ponent (N/E).
3110E6 Sumps, discharge containment and ancillary equip-
ment. Sumps, discharge containment and ancillary equipment
shall conform to 2 CCR 2380(f) [10.22], 33 CFR 1 54.530
[10.23] and the following:
1. Sumps for oil drainage shall be equipped with pres-
sure/vacuum vents, automatic draining pumps and shall
be tightly covered (N/E),
2. Sumps which provide drainage for more than one berth
should be equipped with liquid seals so that afire on one
berth does not spread via the sump (N/E),
3. Sumps shall be located at least 25ft from the manifolds,
base of the loading arms or hose towers (N).
4. Conduct periodic integrity testing of the sump containers
and periodic integrity and leak testing of the related
valves and piping.
3110E7 Vapor control systems. Vapor control systems shall
conform to 33 CFR 154.800 through 154,850 [10.24] and API
Standard 2610 [10.25]. The effects of seismic, wind, dead, live
and other loads shall be considered in the analysis and design
of individual tie-downs of components, such as of steel skirts,
vessels, controls and detonation arresters. The analysis and
design shall include the load transfer to supporting deck/pile
structures or foundation elements.
3110F,8 Equipment anchors and supports. For new (N) elec-
trical and mechanical equipment, the seismic lateral loads
(demand) shall be calculated using the methods of Section 6.4
of F EM A 450 [10.26], The design for load transfer to the wharf
deck shall use the same procedures as for mooring and berth-
ing components (see Section 3107F5.3),
For existing (E) equipment, the seismic assessment shall be
performed in accordance with CalARP [10,27], FEMA 356
[10,28] orASCE Guidelines [10,29],
3110E9 References.
[10.1] 2 CCR 2380(b), Title 2, California Code of Regu-
lations, Section 2380(b), Loading Arms.
[10,2] 33 CFR 154.510, Title 33 Code ofFederal Regula-
tions Section 1 54.510.
574
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
[10.3] Oil Companies International Marine Forum
(OCIMF), 1999, *' Design and Construction Speci-
fication for Marine Loading Arms, " 3'''^ ed.,
Witherby, London,
[10.4] American Society of Mechanical Engineers
(ASME), 2000, ASME B40.100-1998, ''Pressure
Gauges and Gauge Attachments, " New York.
[10.5] National Fluid Power Association (NFPA), 1996,
ANSI/(NFPA)T3.6. 7R2-1996, '' Fluid Power Sys-
tems and Products — Square Head Industrial Cyl-
inders - Mounting Dimensions, " Milwaukee, WL
[10.6] National Fire Protection Association, 2002,
NFPA 70, ''National Electric Code, " Quincy, MA.
[10.7] Underwriters Laboratory, Inc., 1997, "Intrinsi-
cally Safe Apparatus and Associated Apparatus
for Use in Class I, II, III, Division 1, Hazardous
(Classified) Locations, " ANSI/UL Standard No.
913, 5^^ ed., Northbrook, IL.
[10.8] 2 CCR2370(e), Title 2 California Code of Regula-
tions, Section 2370(e).
[10.9] 47 CFR Part 15 Private Land Mobile Radio Ser-
vices, Title 47 Code of Federal Regulations (CFR).
[10.10] 2 CCR 2380(a), Title 2, California Code of Regu-
lations, Section 2380(a).
[10.11] 33 CFR 1 54.500 Hose Assemblies, Title 33 Code
of Federal Regulations Section 1 55.500.
[1 0. 1 2] American Society of Mechanical Engineers, 1 996,
ASME/ANSI B16.5, "Pipe Flanges and Flanged
Fittings, " New York.
[1 0. 1 3] American Society for Testing and Materials, 2001,
ASTMF-1 122-87 (1998), "Standard Specification
for Quick Disconnect Couplings, " West
Conshohocken , PA.
[10.14] 29 CFR 1918, Subpart F, Title 29 Code of Federal
Regulations Section 1918, Subpart F.
[10.15] American Society of Mechanical Engineers, 1996,
ASMEB30.4 - 1996, "Portal Tower and Pedestal
Cranes, " New York.
[10.16] American Society of Mechanical Engineers, 2002,
ASME B30. 7 - 2001, "Base Mounted Drum
Hoists, " New York.
[10. 1 7] American Society of Mechanical Engineers, 1999,
ASME HST-4, "Performance Standard for Over-
head Electric Wire-Rope Hoists, " New York.
[10.18] 29 CFR 191 7.46, Title 29 Code of Federal Regula-
tions Section 1917.46 Load Indicating Devices.
[10.19] 29 CFR 1918.22, Title 29 Code of Federal Regula-
tions Section 1918.22, Gangways.
[10.20] US Army Corps of Engineers, 1996, "Safety and
Health Requirements Manual, Sections 19(b) and
21(b), " EM 385-1 ~1, Washington, D.C.
[10.21] Chapter 16.4, Ship/Shore Access, International
Safety Guide for Oil Tankers and Terminals, 5th
ed. 2006, Witherby, London.
[10.22] 2 CCR 2380 (f), Title 2, California Code of Regu-
lations, Section 2380 (f). Small Discharge Con-
tainment.
[10.23] 33 CFR 154.530, Title 33, Code of Federal Regu-
lations, Section 1 54.530 Small Discharge Con-
tainment.
[10.24] 33 CFR 1 54.800 through 1 54.850, Title 33 Code
of federal Regulations, Sections 1 54.800 through
1 54.850.
[10.25] American Petroleum Institute (API), 1994, API
Standard 2610, "Design, Construction, Opera-
tion, Maintenance, and Inspection of Terminal
and Tank Facilities, " ANSI/API STD 2610-1994,
P^ ed., Washington, D.C.
[10.26] Federal Emergency Management Agency, 2003,
"NEHRP Recommended Provisions for Seismic
Regulations for New Buildings and Other Struc-
tures (FEMA 450), " Part 1 — Provisions, Wash-
ington D.C.
[10.27] CalARP Program Seismic Guidance Committee,
January 2004, "Guidance for California Acciden-
tal Release Prevention (CalARP) Program Seis-
mic Assessments, " Sacramento, CA.
[10.28] Federal Emergency Management Agency, Nov.
2000, FEMA 356, "Prestandard and Commentary
for the Seismic Rehabilitation of Buildings, '*
Washington, D.C.
[10.29] American Society of Civil Engineers, 1997,
"Guidelines for Seismic Evaluation and Design of
Petrochemical Facilities, " New York, NY.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
2010 CALIFORNIA BUILDING CODE
575
MARINE OIL TERMINALS
Division 11
SECTION 3111F
ELECTRICAL SYSTEMS
3111F.1 General, This section provides minimum standards
for electrical systems at marine oil terminals.
Electrical systems include the incoming electrical service
and components, the electrical distribution system, branch cir-
cuit cables and the connections. Also included are:
1. Lighting, for operations, security and navigation
2. Controls for mechanical and electrical equipment
3. Supervision and instrumentation systems for mechanical
and electrical equipment
4. Grounding and bonding
5. Corrosion protection through cathodic protection
6. Communications and data handling systems
7. Fire detection systems
8. Fire alarm systems
9. Emergency shutdown systems (BSD)
All electrical systems shall conform to API RP 540 [I LI]
and the National Electrical Code (NEC) [IL2].
See Section 3 1 01 F3 for definitions of "new'* (N) and ** exist-
ing" (E).
3111FJ Hazardous area designations and plans (N/E), Area
classifications shall be determined in accordance with API RP
500 [113], API RP 540 [1 LI] and the NEC, Articles 500, 501,
504, 505 and 515 [11.2]. A marine oil terminal shall have a
current set of scaled plan drawings, with clearly designated
areas showing the hazard class, division and group. The plan
view shall be supplemented with sections, elevations and
details to clearly delineate the area classification at all eleva-
tions starting from low water level. The drawings shall be certi-
fied by aprofessional electrical engineer. The plans shall be
reviewed, and revised when modifications to the structure,
product or equipment change hazardous area identifications
or boundaries.
3111F3 Identification and tagging. All electrical equipment,
cables and conductors shall be clearly identified by means
oftags, plates, color coding or other effective means to facili-
tate troubleshooting and improve safety, and shall conform to
the identification carried out for the adjacent on-shore facili-
ties (N). Topics for such identification are found in the NEC
Articles 110, 200, 210, 230, 384, 480 and 504 [1L2]. Existing
electrical equipment (E) shall be tagged.
Where identification is necessary for the proper and safe
operation of the equipment, the marking shall be clearly visible
and illuminated (N/E). A coded identification system shall
apply to all circuits, carrying low or high voltage power, con-
trol, supervisory or communication (N).
3111FA Purged or pressurized equipment In hazardous loca-
tions (N/E), Purged or pressurized enclosures shall be capable
of preventing the entry of combustible gases into such spaces,
in accordance with NFPA 496 [11.4], Special emphasis shall
be placed on reliability and ease of operation. The pressurizing
equipment shall be electrically monitored and alarms shall be
provided to indicate failure of the pressurizing or purging sys-
tems.
31 11F,5 Electrical service. Where critical circuits are used for
spill prevention, fire control or life safety, an alternative service
derived from a separate source and conduit system, shall be
located at a safe distance from the main power service. A sepa-
rate feeder from a double-ended substation or other source
backed up by emergency generators will meet this requirement.
An uninterrupted power service (UPS) shall be provided for
control and supervisory circuits associated with ESD systems
(N).
1. Electrical, instrument and control systems used to
activiate equipment needed to control afire or mitigate
its consequences shall be protected from fire and remain
operable for 15 minutes in a 2000° F fire, unless
designed to fail-safe during fire exposure. The tempera-
ture around these critical components shall not exceed
200°F during 15 minutes of fire exposure (N).
2. Wiring in fireproof ed conduits shall be derated 15 per-
cent to account for heat buildup during normal opera-
tion. Type Ml (mineral insulated, metal sheathed [1 L2])
cables may be used in lieu offireproofing of wiring (N).
3. Emergency cables and conductors shall be located
where they are protected from damage caused by traffic,
corrosion or other sources (N).
4. Allowance shall be made for electrical faults,
overvoltages and other abnormalities (N).
Where solid state motor controls are used for starting and
speed control, corrective measures shall be incorporated for
mitigating the possible generation of harmonic currents that
may affect the ESD or other critical systems (N).
3111E6 Grounding and bonding (N/E),
L All electrical equipment shall be effectively grounded as
per NEC Article 250 [11.2], All noncurrent carrying
metallic equipment, structures, piping and other ele-
ments shall also be effectively grounded.
2. Grounding shall be considered in any active corrosion
protection system for on-shore piping, submerged sup-
port structures or other systems. Insulation barriers,
including flanges or nonconducting hoses shall be used
to isolate cathodic protection systems from other electri-
cal/static sources. None of these systems shall be com-
promised by grounding or bonding arrangements that
may interconnect the corrosion protection systems or
interfere with them in any way that would reduce their
effectiveness.
3. Bonding of vessels to the MOT structure is not permitted
(2CCR2341(f))[lL5].
4. Whenever flanges of pipelines with cathodic protection
are to be opened for repair or other work, the flanges
shall be bonded prior to separation.
576
2010 CALIFORNIA BUILDING CODE
MARINE OIL TERMINALS
5. Direct wiring to ground shall be provided from all tow-
ers, loading arms or other high structures that are sus-
ceptible to lightning surges or strikes.
3111F J Equipment specifications (N), All electrical systems
and components shall conform to National Electrical Manu-
facturers Association (NEMA) standards or be certified by a
Nationally Recognized Testing Laboratory (NRTL).
3111F.8 Illumination (N/E), Lighting shall conform to 2 CCR
2365 [1L6] and 33 CFR 154.570 (d) [ILJ],
3111F.9 Communications and control systems.
3111F.9J Communication systems (N/E). Communica-
tions systems shall comply with 2 CCR 2370 [IL8], and
conform to Section 6 of[lL9].
3111F.9,2 Overfill monitoring and controls (N/E), Overfill
protection systems shall conform to Appendix C of API RP
2350 [11.10]. These systems shall be tested before each
transfer operation or monthly, whichever is less frequent.
Where vessel or barge overfill sensors and alarms are pro-
vided, they shall comply with 33 CFR 154.812 [11.11].
All sumps shall be provided with level sensing devices to
initiate an alarm to alert the operator at the approach of a
high level condition, A second alarm shall be initiated at a
high-high level to alert the operator. Unless gravity drain-
age is provided, sumps must have an automatic pump, pro-
grammed to start at a predetermined safe level
3IIIFJ0 Corrosion protection,
31IIFJ0J Corrosion assessment (N/E),An assessment
shall be performed to determine the existing and potential
corrosion. This assessment should include all steel or
metallic components, including the structure, pipelines,
supports or other ancillary equipment, with drawings and
specifications for corrosion prevention/protection. The
assessment shall be performed by a licensed professional
engineer, using the methods and criteria prescribed in
[11.12].
3IIIF,I0,2 Inspection, testing and records (N/E), For sac-
rificial anode systems, periodic underwater inspections
shall be performed and observations recorded. For
impressed current systems, monthly rectifier readings and
annual potential readings ofthe protected components shall
be taken. If potential readings for steel structures are out-
side of acceptable limits (between -0.85 [11.13] and -1.10
Volts), corrective actions shall be taken. Voltage drops other
than across the structure-to-electrolyte boundary must be
considered for valid interpretations of potential measure-
ment. Consideration is understood to mean the application
of sound engineering practice in determining the signifi-
cance of voltage drops by methods such as:
1. Measuring or calculating voltage drop(s)
2. Reviewing historical performance of the cathodic
protection system (CPS)
3. Evaluating the physical and electrical characteristics
ofthe structure and the environment
4. Determining whether or not there is physical evi-
dence of corrosion
All isolating sections shall be tested immediately after
installation or replacement, and, at a minimum, annually.
Test results shall be recorded and documented. Electrical
tests on insulating flanges shall make use of specialized
insulator testers. The test instrument shall make use ofRF
signals, capacitive measurements or other means to clearly
determine whether an insulating flange is shorted or open
circuited without being affected by pipe-to-soil potentials,
cathodic protection voltages or whether it is buried or
exposed.
The cathodic protection inspection for buried or sub-
merged pipelines shall conform to API 570 [11.14].
Insulating and isolating arrangements for protection
against static, stray and impressed currents shall be tested
in accordance with 2 CCR 2341(d) and 2380 [11.15].
311IFJ1 References.
[11.1] American Petroleum Institute, 1 999, API Recom-
mended Practice 540 (APIRP 540), ''Electrical
InstalloHons in Petroleum Processing Plants, " 4'^
ed, Washington, D.C.
[1L2] National Fire Protection Association, 2002,
NFPA 70, ''National Electric Code (NEC),''
Quincy, MA.
[11.3] American Petroleum Institute, 1997, API Recom-
mended Practice 500 (API RP 500), "Recom-
mended Practice for Classification of Locations
for Electrical Installations at Petroleum Facilities
Classified as Class I, Division 1 and Division 2,
"2"'^ed., Washington, D.C.
[11.4] National Fire Protection Association, 1998,
NFPA 496, "Standard for Purged and Pressurized
Enclosures for Electrical Equipment, " Quincy,
MA.
[11.5] 2 CCR 2341(f), Title 2, California Code of regula-
tions. Section 2341(f).
[11.6] 2 CCR 2365, Title 2 California Code of Regula-
tions, Section 2365.
[11.7] 33 CFR 154.570(d), Title 33 Code of Federal Reg-
ulations Section 154.570(d).
[11.8] 2 CCR 2370, Title 2 California Code of Regula-
tions, Section 2370.
[11.9] Oil Companies International Marine Forum
(OCIMF), 1987, "Guide on Marine Terminal Fire
Protection and Emergency Evacuation, " P^ ed.,
Witherby, London.
[11.10] American Petroleum Institute, 1996, API Recom-
mended Practice 2350 (API RP 2350), "Overfill
Protection for Storage Tanks, " 2"*^ ed., Washing-
ton, D.C,
[11.11] 33 CFR 1 54.812, Title 33, Code of Federal Regu-
lations, Section 154.812 - Facility Requirements
for Vessel Liquid Overfill Protection.
[11.12] National Association of Corrosion Engineers
(NACE), Standard Recommended Practice, 1994,
RPOl 76-1 994 "Corrosion Control of Steel Fixed
2010 CALIFORNIA BUILDING CODE
577
MARINE OIL TERMINALS
Offshore Platforms Associated with Petroleum
Production, " Houston, TX,
[11.13] Department of Defense, 3 1 January 1 990, Military
Handbook, "Electrical Engineering Cathodic
Protection," MIL-HDBK- 1004/10, Washington,
D.C,
[1L14] American Petroleum Institute, 2002, API570,
"Piping Inspection Code, " 2"^ ed,, October 1998
(February 2000 Addendum 1), Washington, D.C.
[11, 15] 2 CCR 2341(d) and 2380, Title 2, California Code
of Regulations, Sections 2341(d) and 2380.
Authority: Sections 8755 and 8757, Public Resources Code.
Reference: Sections 8750, 8751, 8755 and 8757, Public
Resources Code.
578 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SB
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
2010 CALIFORNIA BUILDING CODE
579
580 2010 CALIFORNIA BUILDING CODE
CHAPTER 32
ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
SECTION 3201
GENERAL
3201.1 Scope. The provisions of this chapter shall govern the
encroachment of structures into the public right-of-way.
3201.2 Measurement. The projection of any structure or por-
tion thereof shall be the distance measured horizontally from
the lot line to the outermost point of the projection.
3201.3 Other laws. The provisions of this chapter shall not be
construed to permit the violation of other laws or ordinances
regulating the use and occupancy of public property.
3201.4 Drainage. Drainage water collected from a roof, awn-
ing, canopy or marquee, and condensate from mechanical
equipment shall not flow over a public walking surface.
SECTION 3202
ENCROACHMENTS
3202.1 Encroachments below grade. Encroachments below
grade shall comply with Sections 3202.1.1 through 3202.1.3.
3202.1.1 Structural support. A part of a building erected
below grade that is necessary for structural support of the
building or structure shall not project beyond the lot lines,
except that the footings of street walls or their supports
which are located at least 8 feet (2438 mm) below grade
shall not project more than 12 inches (305 mm) beyond the
street lot line.
3202.1.2 Vaults and other enclosed spaces. The construc-
tion and utilization of vaults and other enclosed spaces
below grade shall be subject to the terms and conditions of
the appHcable governing authority.
3202.1.3 Area ways. Areaways shall be protected by grates,
guards or other approved means.
^miJl Encroachments above grade and below 8 feet in
height. Encroachments into the public right-of-way above
grade and below 8 feet (2438 mm) in height shall be prohibited
except as provided for in Sections 3202.2.1 through 3202.2.3.
Doors and windows shall not open or project into the pubHc
right-of-way.
3202.2.1 Steps. Steps shall not project more than 12 inches
(305 mm) and shall be guarded by approved devices not less
than 3 feet (914 mm) high, or shall be located between col-
umns or pilasters.
3202.2.2 Architectural features. Columns or pilasters,
including bases and moldings shall not project more than 12
inches (305 mm). Belt courses, lintels, sills, architraves,
pediments and similar architectural features shall not pro-
ject more than 4 inches (102 mm).
3202.2.3 Awnings, The vertical clearance from the public
right-of-way to the lowest part of any awning, including
valances, shall be 7 feet (2134 mm) minimum.
3202.3 Encroachments 8 feet or more above grade.
Encroachments 8 feet (2438 mm) or more above grade shall
comply with Sections 3202.3.1 through 3202.3.4.
3202.3.1 Awnings, canopies, marquees and signs. Awn-
ings, canopies, marquees and signs shall be constructed so
as to support applicable loads as specified in Chapter 16.
Awnings, canopies, marquees and signs with less than 15
feet (4572 mm) clearance above the sidewalk shall not
extend into or occupy more than two-thirds the width of the
sidewalk measured from the building. Stanchions or col-
umns that support awnings, canopies, marquees and signs
shall be located not less than 2 feet (610 mm) in from the
curb line.
3202.3.2 Windows, balconies, architectural features and
mechanical equipment. Where the vertical clearance
above grade to projecting windows, balconies, architectural
features or mechanical equipment is more than 8 feet (2438
mm), 1 inch (25 mm) of encroachment is permitted for each
additional 1 inch (25 mm) of clearance above 8 feet (2438
nam), but the maximum encroachment shall be 4 feet (1219
mm).
3202.3.3 Encroachments 15 feet or more above grade.
Encroachments 15 feet (4572 mm) or more above grade
shall not be limited.
3202.3.4 Pedestrian walkways. The installation of a
pedestrian walkway over a public right-of-way shall be sub-
ject to the approval of the applicable governing authority.
The vertical clearance from the public right-of-way to the
lowest part of di pedestrian walkway shall be 15 feet (4572
mm) minimum.
3202.4 Temporary encroachments. Where allowed by the
applicable governing authority, vestibules and storm enclo-
sures shall not be erected for a period of time exceeding seven
months in any one year and shall not encroach more than 3 feet
(914 mm) nor more than one-fourth of the width of the side-
walk beyond the street lot line. Temporary entrance awnings
shall be erected with a minimum clearance of 7 feet (2134 mm)
to the lowest portion of the hood or awning where supported on
removable steel or other approved noncombustible support.
2010 CALIFORNIA BUILDING CODE
581
582 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 33 - SAFEGUARDS DURING CONSTRUCTION
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
Adopt only those sections that
are listed below
X
X
X
X
Chapter/Section
3306.2
X
X
X
X
3307.2
X
X
X
X
X
3307.3
X
X
X
X
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.1 1.
2010 CALIFORNIA BUILDING CODE
583
584 2010 CALIFORNIA BUILDING CODE
CHAPTER 33
SAFEGUARDS DURING CONSTRUCTION
SECTION 3301
GENERAL
3301.1 Scope. The provisions of this chapter shall govern
safety during construction and the protection of adjacent public
and private properties.
3301.2 Storage and placement. Construction equipment and
materials shall be stored and placed so as not to endanger the
public, the workers or adjoining property for the duration of the
construction project.
SECTION 3302
CONSTRUCTION SAFEGUARDS
3302.1 Remodeling and additions. Required exits, existing
structural elements, fire protection devices and sanitary safe-
guards shall be maintained at all times during remodeling,
alterations, repairs or additions to any building or structure.
Exceptions:
1. When such required elements or devices are being
remodeled, altered or repaired, adequate substitute
provisions shall be made.
2. When the existing building is not occupied.
3302.2 Manner of removal. Waste materials shall be removed
in a manner which prevents injury or damage to persons,
adjoining properties and public rights-of-way.
SECTION 3303
DEMOLITION
3303.1 Construction documents. Construction documents
and a schedule for demolition must be submitted when
required by the building official. Where such information is
required, no work shall be done until such construction docu-
ments or schedule, or both, are approved.
3303.2 Pedestrian protection. The work of demolishing any
building shall not be commenced until pedestrian protection is
in place as required by this chapter.
3303.3 Means of egress. A party wall balcony or horizontal
exit shall not be destroyed unless and until a substitute means of
egress has been provided and approved,
3303.4 Vacant lot. Where a structure has been demolished or
removed, the vacant lot shall be filled and maintained to the
existing grade or in accordance with the ordinances of the juris-
diction having authority.
3303.5 Water accumulation. Provision shall be made to pre-
vent the accumulation of water or damage to any foundations
on the premises or the adjoining property.
3303.6 Utility connections. Service utility connections shall
be discontinued and capped in accordance with the approved
rules and the requirements of the applicable governing author-
ity.
SECTION 3304
SITE WORK
3304.1 Excavation and fill. Excavation and fill for buildings
and structures shall be constructed or protected so as not to
endanger life or property. Stumps and roots shall be removed
from the soil to a depth of at least 12 inches (305 mm) below the
surface of the ground in the area to be occupied by the building.
Wood forms which have been used in placing concrete, if
within the ground or between foundation sills and the ground,
shall be removed before a building is occupied or used for any
purpose. Before completion, loose or casual wood shall be
removed from direct contact with the ground under the build-
ing.
3304.1.1 Slope limits. Slopes for permanent fill shall not be
steeper than one unit vertical in two units horizontal
(50-percent slope). Cut slopes for permanent excavations
shall not be steeper than one unit vertical in two units hori-
zontal (50-percent slope). Deviation from the foregoing
limitations for cut slopes shall be permitted only upon the
presentation of a soil investigation report acceptable to the
building official.
3304.1.2 Surcharge. No fill or other surcharge loads shall
be placed adjacent to any building or structure unless such
building or structure is capable of withstanding the addi-
tional loads caused by the fill or surcharge. Existing foot-
ings or foundations which can be affected by any excavation
shall be underpinned adequately or otherwise protected
against settlement and shall be protected against later move-
ment.
3304.1.3 Footings on adjacent slopes. For footings on
adjacent slopes, see Chapter 18.
3304.1.4 Fill supporting foundations. Fill to be used to
support the foundations of any building or structure shall
comply with Section 1804.5. Special inspections of com-
pacted fill shall be in accordance with Section 1704.7.
SECTION 3305
SANITARY
3305.1 Facilities required. Sanitary facilities shall be pro-
vided during construction, remodeling or demolition activities
in accordance with the California Plumbing Code.
2010 CALIFORNIA BUILDING CODE
585
SAFEGUARDS DURING CONSTRUCTION
SECTION 3306
PROTECTION OF PEDESTRIANS
3306.1 Protection required. Pedestrians shall be protected
during construction, remodeling and demolition activities as
required by this chapter and Table 3306.1. Signs shall be pro-
vided to direct pedestrian traffic.
3306.2 Walkways. A walkway shall be provided for pedes-
trian travel in front of every construction and demolition site
unless the applicable governing authority authorizes the side-
walk to be fenced or closed. Walkways shall be of sufficient
width to accommodate the pedestrian traffic, but in no case
shall they be less than 4 feet (1219 mm) in width. Walkways
shall be provided with a durable walking surface. Walkways
shall be accessible in accordance with Chapter llA or IIB as
applicable, and shall be designed to support all imposed loads
and in no case shall the design live load be less than 1 50 pounds
per square foot (psf) (7.2 kN/m^).
3306.3 Directional barricades. Pedestrian traffic shall be pro-
tected by a directional barricade where the walkway extends
into the street. The directional barricade shall be of sufficient
size and construction to direct vehicular traffic away from the
pedestrian path.
3306.4 Construction railings. Construction railings shall be
at least 42 inches (1067 mm) in height and shall be sufficient to
direct pedestrians around construction areas.
3306.5 Barriers. Barriers shall be a minimum of 8 feet (2438
mm) in height and shall be placed on the side of the walkway
nearest the construction. Barriers shall extend the entire length
of the construction site. Openings in such barriers shall be pro-
tected by doors which are normally kept closed.
3306.6 Barrier design. Barriers shall be designed to resist
loads required in Chapter 16 unless constructed as follows:
1 . Barriers shall be provided with 2-inch by 4-inch (5 1 mm
by 102 mm) top and bottom plates.
2. The barrier material shall be a minimum of ^/4-inch (19.1
mm) boards or V4-inch (6.4 mm) wood structural use
panels.
3. Wood structural use panels shall be bonded with an
adhesive identical to that for exterior wood structural use
panels.
4. Wood structural use panels V4 inch (6.4 mm) or V^^ inch
(23.8 mm) in thickness shall have studs spaced not more
than 2 feet (610 mm) on center (o.c).
5. Wood structural use panels Vg inch (9.5 mm) or V2 inch
(12.7 mm) in thickness shall have studs spaced not more
than 4 feet (1219 mm) on center provided a 2-inch by
4-inch (51 mm by 102 mm) stiffener is placed horizon-
tally at midheight where the stud spacing exceeds 2 feet
(610 mm) o.c.
6. Wood structural use panels % inch (15.9 mm) or thicker
shall not span over 8 feet (2438 mm).
3306.7 Covered walkways. Covered walkways shall have a
minimum clear height of 8 feet (2438 mm) as measured from
the floor surface to the canopy overhead. Adequate lighting
shall be provided at all times. Covered walkways shall be
designed to support all imposed loads. In no case shall the
design live load be less than 150 psf (7.2 kN/m^) for the entire
structure.
Exception: Roofs and supporting structures of covered
walkways for new, light-frame construction not exceeding
two stories above grade plane are permitted to be designed
for a live load of 75 psf (3.6kN/m^) or the loads imposed on
them, whichever is greater. In lieu of such designs, the roof
and supporting structure of a covered walkway are permit-
ted to be constructed as follows:
1 . Footings shall be continuous 2-inch by 6-inch (5 1 mm
by 152 mm) members.
2. Posts not less than 4 inches by 6 inches (102 mm by
152 mm) shall be provided on both sides of the roof
and spaced not more than 12 feet (3658 mm) on cen-
ter.
3. Stringers not less than 4 inches by 12 inches (102 mm
by 305 mm) shall be placed on edge upon the posts.
4. Joists resting on the stringers shall be at least 2 inches
by 8 inches (5 1 mm by 203 mm) and shall be spaced
not more than 2 feet (610 mm) on center.
5. The deck shall be planks at least 2 inches (51 mm)
thick or wood structural panels with an exterior expo-
sure durability classification at least ^V^i i^^^h (18.3
mm) thick nailed to the joists.
TABLE 3306.1
PROTECTION OF PEDESTRIANS
HEIGHT OF
CONSTRUCTION
DISTANCE FROM CONSTRUCTION TO LOT LINE
TYPE OF PROTECTION REQUIRED
8 feet or less
Less than 5 feet
Construction raihngs
5 feet or more
None
More than 8 feet
Less than 5 feet
Barrier and covered walkway
5 feet or more, but not more than one-fourth the height of construction
Barrier and covered walkway
5 feet or more, but between one-fourth and one-half the height of construction
Barrier
5 feet or more, but exceeding one-half the height of construction
None
For SI: 1 foot = 304.8 mm.
586
2010 CALIFORNIA BUILDING CODE
SAFEGUARDS DURING CONSTRUCTION
6. Each post shall be knee braced to joists and stringers
by 2-inch by 4-inch (51 mm by 102 mm) minimum
members 4 feet (1219 mm) long.
7. A 2-inch by 4-inch (51 nmi by 102 mm) minimum
curb shall be set on edge along the outside edge of the
deck,
3306.8 Repair, maintenance and removal. Pedestrian protec-
tion required by this chapter shall be maintained in place and
kept in good order for the entire length of time pedestrians may
be endangered. The owner or the owner's agent, upon the com-
pletion of the construction activity, shall immediately remove
walkways, debris and other obstructions and leave such pubHc
property in as good a condition as it was before such work was
commenced.
3306.9 Adjacent to excavations. Every excavation on a site
located 5 feet (1524 mm) or less from the street lot line shall be
enclosed with a barrier not less than 6 feet (1829 mm) high.
Where located more than 5 feet (1524 mm) from the street lot
line, a barrier shall be erected when required by the building
official. Barriers shall be of adequate strength to resist wind
pressure as specified in Chapter 16.
SECTION 3307
PROTECTION OF ADJOINING PROPERTY
3307.1 Protection required. Adjoining public and private
property shall be protected from damage during construction,
remodeUng and demolition work. Protection must be provided
for footings, foundations, party walls, chimneys, skylights and
roofs. Provisions shall be made to control water runoff and ero-
sion during construction or demolition activities. The person
making or causing an excavation to be made shall provide writ-
ten notice to the owners of adjoining buildings advising them
that the excavation is to be made and that the adjoining build-
ings should be protected. Said notification shall be delivered
not less than 10 days prior to the scheduled starting date of the
excavation.
3307.2 Protection of adjoining property, [DSA-SS/CC &
I OSHPD 1, 2 and 4] The requirements for protection of adja-
cent property and depth to which protection is required shall be
as defined in Section 832, Civil Code.
The owner or governing board shall be responsible to retain
the services of a structural engineer and a geotechnical engi-
neer to review the design of the support system for foundations
of the existing buildings, or soil supporting any portion of the
building. Where the underpinning or support system provides
for the stability of the foundations of an existing hospital, or
essential services building or public school building, the sys-
tem shall be designed and constructed to conform to all
requirements of these regulations.
3307 J Protection of existing buildings, [DSA-SS/CC &
I OSHPD 1, 2 and 4] Where excavation for new construction
affects the stability of the foundations or any portion of such
existing building, a support system shall be provided. Such sys-
tems shall be considered a structural alteration to the existing
building and shall be designed and constructed to conform to
these regulations.
SECTION 3308
TEMPORARY USE OF STREETS, ALLEYS AND
PUBLIC PROPERTY
3308.1 Storage and handling of materials. The temporary
use of streets or public property for the storage or handling of
materials or of equipment required for construction or demoli-
tion, and the protection provided to the public shall comply
with the provisions of the applicable governing authority and
this chapter,
3308.1.1 Obstructions. Construction materials and equip-
ment shall not be placed or stored so as to obstruct access to
fire hydrants, standpipes, fire or police alarm boxes, catch
basins or manholes, nor shall such material or equipment be
located within 20 feet (6096 ram) of a street intersection, or
placed so as to obstruct normal observations of traffic sig-
nals or to hinder the use of public transit loading platforms.
3308.2 Utility fixtures. Building materials, fences, sheds or
any obstruction of any kind shall not be placed so as to obstruct
free approach to any fire hydrant, fire department connection,
utility pole, manhole, fire alarm box or catch basin, or so as to
interfere with the passage of water in the gutter. Protection
against damage shall be provided to such utility fixtures during
the progress of the work, but sight of them shall not be
obstructed.
SECTION 3309
FIRE EXTINGUISHERS
[F] 3309.1 Where required. All structures under construction,
alteration or demolition shall be provided with not less than
one approved portable fire extinguisher in accordance with
Section 906 and sized for not less than ordinary hazard as fol-
lows:
1 . At each stairway on all floor levels where combustible
materials have accumulated.
2. In every storage and construction shed.
3. Additional portable fire extinguishers shall be provided
where special hazards exist, such as the storage and use
of flammable and combustible liquids.
3309.2 Fire hazards. The provisions of this code and the Call-
fornia Fire Code shall be strictly observed to safeguard against
all fire hazards attendant upon construction operations.
2010 CALIFORNIA BUILDING CODE
587
SAFEGUARDS DURING CONSTRUCTION
SECTION 3310
MEANS OF EGRESS
3310.1 Stairways required. Where a building has been con-
structed to a building height of 50 feet (15 240 mm) or four sto-
ries, or where an existing building exceeding 50 feet (15 240
mm) in building height is altered, at least one temporary lighted
stairway shall be provided unless one or more of the permanent
stairways are erected as the construction progresses.
3310.2 Maintenance of means of egress. Required means of
egress shall be maintained at all times during construction,
demolition, remodeling or alterations and additions to any
building.
Exception: Approved temporary means of egress systems
and facilities.
SECTION 3312
AUTOMATIC SPRINKLER SYSTEM
[F] 3312.1 Completion before occupancy. In buildings where
an automatic sprinkler system is required by this code, it shall
be unlawful to occupy any portion of a building or structure
until the automatic sprinkler system installation has been tested
and approved, except as provided in Section 1 1 1.3.
[F] 3312.2 Operation of valves. Operation of sprinkler control
valves shall be permitted only by properly authorized person-
nel and shall be accompanied by notification of duly desig-
nated parties. When the sprinkler protection is being regularly
turned off and on to facilitate connection of newly completed
segments, the sprinkler control valves shall be checked at the
end of each work period to ascertain that protection is in ser-
vice.
SECTION 3311
STANDPIPES
[F] 3311.1 Where required. In buildings required to have
standpipes by Section 905 .3.1, not less than one standpipe shall
be provided for use during construction. Such standpipes shall
be installed when the progress of construction is not more than
40 feet (12 192 mm) in height above the lowest level of fire
department vehicle access. Such standpipe shall be provided
with fire department hose connections at accessible locations
adjacent to usable stairs. Such standpipes shall be extended as
construction progresses to within one floor of the highest point
of construction having secured decking or flooring.
[F] 3311.2 Buildings being demolished. Where a building is
being demolished and a standpipe exists within such a build-
ing, such standpipe shall be maintained in an operable condi-
tion so as to be available for use by the fire department. Such
standpipe shall be demolished with the building but shall not be
demolished more than one floor below the floor being demol-
ished.
3311.3 Detailed requirements. Standpipes shall be installed
in accordance with the provisions of Chapter 9.
Exception: Standpipes shall be either temporary or perma-
nent in nature, and with or without a water supply, provided
that such standpipes conform to the requirements of Section
905 as to capacity, outlets and materials.
3311.4 Water supply. Water supply for fire protection, either
temporary or permanent, shall be made available as soon as
combustible material accumulates.
588
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 34 - EXISTING STRUCTURES
Adopting agency
BBC
SFM
HOD
DBA
OBHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
X
X
Adopt only those sections that
are listed below
X
X
X
X
X
X
X
Chapter/Section
3401
X
3401.1
X
X
X
X
3401.1 (Last Paragraph only)
X
3401.1.1
X
3401.1-3401.3
X
3401.1.2
X
3401.1.3
X
3401.3
X
X
3401.4
X
X
3401.4-3401.4.2
X
3401.4.3
X
X
3401.5
X
X
3401.6
X
3401.7
X
3402
X
X
3403
X
3403.1
X
X
X
3403.1 Exception
X
3403.1.1
X
X
3403.2 Equation
X
3403.4.1
X
X
X
3404
X
3404.1
X
X
3404.1 Exception
X
3404.1.1
X
X
3404.4.1
X
X
3404.6
X
3405
X
3405.1
X
X
X
3405.1 Exception
3405.1.1
X
X
X
3405.1.2
X
X
3406
X
X
3408
X
X
3409 (r^ Paragraph)
X
3410.1
X
X
3410.2
X
X
3411
t
t
2010 CALIFORNIA BUILDING CODE
(continued)
589
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 34 - EXISTING STRUCTURES— continued
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire ciiapter
Adopt entire chapter as
amended (amended sections
listed below)
X
X
Adopt only those sections that
are listed below
X
X
X
X
X
X
X
Chapter/Section
3413
X
3414
X
3415
X
3416
X
3417
X
X
X
3418
X
X
X
3419
X
X
X
3420
X
X
3421
X
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section LIL
590
2010 CALIFORNIA BUILDING CODE
CHAPTER 34
EXISTING STRUCTURES
SECTION 3401
GENERAL
3401.1 Scope. The provisions of this chapter shall control the
alteration, repair, addition and change of occupancy of exist-
ing structures, including state-regulated structures in accor-
dance with Sections 3401.1.1 and 3401.1.2.
[DSA-AC] For applications listed in Section 1.9.1 regulated
by the Division of the State Architect-Access Compliance
for accessibility requirements, see Chapter IIB, Section
1134B.
Exceptions:
1 . Existing bleachers, grandstands and folding and tele-
scopic seating shall comply with ICC 300-02.
2. [HCD 2] For moved buildings and maintenance,
alteration, repair, addition or change of occupancy
to existing buildings and accessory structures in
mobilehome parks or special occupancy parks as
provided in Section L8.2.1.3. See California Code
of Regulations, Title 25, Division 1, Chapters 2 and
2.2.
3. [HCD 1] Limited-density owner-built rural dwell-
ings.
3401.1.1 Existing state-owned structures. The provisions
of Sections 3415 through 3420 establish minimum stan-
dards for earthquake evaluation and design for retrofit of
existing state-owned structures, including buildings owned
by the University of California and the California State Uni-
versity.
The provisions of Sections 3415 through 3420 may be
adopted by a local jurisdiction for earthquake evaluation
and design for retrofit of existing buildings.
3401.1.2 Public school buildings, [DSA-SS] The provi-
sions of Sections 3415 through 3421 establish minimum
standards for earthquake evaluation and design for the
rehabilitation of existing buildings for use as public school
buildings under the jurisdiction of the Division of the State
Architect-Structural Safety (DSA-SS, refer to Section
1.9.2.1) where required by Sections 4-307 and 4-309(c) of
the California Administrative Code.
The provisions of Section 3415 through 3421 also estab-
lish minimum standards for earthquake evaluation and
design for rehabilitation of existing public school buildings
currently under the jurisdiction of DSA-SS.
3401.1.3 Community college buildings. [DSA-SS/CC] The
provisions of Sections 3415 through 3421 establish mini-
mum standards for earthquake evaluation and design for
the rehabilitation of existing buildings for use as community
college buildings under the jurisdiction of the Division of
the State Architect-Structural Safety/Community Colleges
(DSA-SS/CC, refer to Section 1.9.2.2) where required by
Sections 4-307 and 4-309(c) of the California Administra-
tive Code.
The provisions of Section 3415 through 3421 also estab-
lish minimum standards for earthquake evaluation and
design for rehabilitation of existing community college
buildings currently under the jurisdiction of DSA-SS/CC.
3401.2 Maintenance. Buildings and structures, and parts
thereof, shall be maintained in a safe and sanitary condition.
Devices or safeguards which are required by this code shall be
maintained in conformance with the code edition under which
installed. The owner or the owner's designated agent shall be
responsible for the maintenance of buildings and structures. To
determine compliance with this subsection, the building offi-
cial shall have the authority to require a building or structure to
be reinspected. The requirements of this chapter shall not pro-
vide the basis for removal or abrogation of fire protection and
safety systems and devices in existing structures.
3401.3 Compliance. Alterations, repairs, additions and
changes of occupancy to existing structures shall comply with
the provisions for alterations, repairs, additions and changes of
occupancy in the California Fire Code, California Mechanical
Code, California Plumbing Code, California Residential
Code, and California Electrical Code.
[HCD 1] See Chapter 34, Sections 3403.1.4.3, 3403.1.1 and
3404.1.1 and Title 25, Division 1, Chapter 1, Subchapter 1,
commencing with Article 1, Section 1 for existing buildings or
structures.
3401.4 Building materials. Building materials shall comply
with the requirements of this section.
3401.4.1 Existing materials. Materials already in use in a
building in compliance with requirements or approvals in
effect at the time of their erection or installation shall be per-
mitted to remain in use unless determined by the building
code official to be dangerous to life, health or safety. Where
such conditions are determined to be dangerous to life,
health or safety, they shall be mitigated or made safe.
3401.4.2 Nev*' and replacement materials. Except as oth-
erwise required or permitted by this code, materials permit-
ted by the applicable code for new construction shall be
used. Like materials shall be permitted for repairs and alter-
ations, provided no hazard to Hfe, health or property is cre-
ated. Hazardous materials shall not be used where the code
for new construction would not permit their use in buildings
of similar occupancy, purpose and location.
2010 CALIFORNIA BUILDING CODE
591
EXISTING STRUCTURES
3401.4.3 Replacement, retention and extension of original
materials. [HCDl] Local ordinances or regulations shall
permit the replacement, retention and extension of original
materials y and the use of original methods of construction,
for any building or accessory structure, provided such
building or structure complied with the building code provi-
sions in effect at the time of original construction and the
building or accessory structure does not become or con-
tinue to be a substandard building. For additional informa-
tion, see Health and Safety Code Sections 17912, 17920.3,
17922(d), 17922,3, 17958,8 and 17958.9.
3401.5 Adoption ofASCE 41: [OSHPD 2&3] All additions,
alterations, repairs and seismic retrofit to the existing struc-
> tures or portions thereof may be designed in accordance with
the provisions ofASCE 41, as modified herein.
3401.5.1 Referenced Standards. All reference standards
listed inASCE 41 shall be replaced by referenced standards
listed in Chapter 35 of this code and shall include all
amendments to the reference standards in this code.
3401.5.2 ASCE 41 Section 1.4 -Rehabilitation Objectives.
I I Target building performance level shall be Life Safety (LS)
Building Performance Level (3-C) as defined in Section
1.5.3.3 at Basic Safety Earthquake 1 (BSE-l) Seismic Haz-
ard Level as defined in section 1.6.1.2 for Occupancy Cate-
gory 11 Structures and Basic Safety Objective (BSO) Level
as defined in Section 1.4.1 for Occupancy Category 111
Structures.
Occupancy Category IV structures shall satisfy Immedi-
ate Occupancy (10) Building Performance Level of(l-B) as
defined in Section 1.5.3.2 at Basic Safety Earthquake 1
(BSE-1) Seismic Hazard Level as defined in Section 1.6.1.2
and Collapse Prevention (CP) building performance level
(5-E) per Section 1.5.3.4 at Basic Safety Earthquake 2
(BSE 2) Seismic Hazard Level as defined in Section 1.6. 1.1.
3401.5.3 ASCE 41 Section 1.6 -Seismic Hazard. Response
spectra and acceleration time histories shall be constructed
I I in accordance with sections 1613 and 1803.7.
3401.5.4 Analysis procedure. The selection of a particular
analysis procedure from ASCE 41 may be subject to the
approval of the enforcement agent.
I I 3401.5.5 Structural design criteria. Prior to implementa-
tion of ASCE 41 nonlinear dynamic procedures — the
ground motion, analysis and design methods, material
assumptions and acceptance criteria proposed by the engi-
neer shall be reviewed by the enforcement agent.
3401.5.6 Structural observation, testing and inspections.
Construction, testing, inspection and structural observa-
tion requirements shall be as required for new construction.
3401.6 Existing Group R'3 Occupancies. [SFM] For smoke
alarm requirements in existing buildings see Section
907.2.11.5.
3401.7 Dangerous conditions. [ESC] Regardless of the extent
of structural or nonstructural damage, the building code offi-
cial shall have the authority to require the elimination of condi-
tions deemed dangerous.
SECTION 3402
DEFINITIONS
3402.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in the code,
have the meanings shown herein.
DANGEROUS. Any building or structure or portion thereof
that meets any of the conditions described below shall be
deemed dangerous:
1. The building or structure has collapsed, partially col-
lapsed, moved off its foundation or lacks the support of
ground necessary to support it.
2 . There exists a significant risk of coUapse, detachment or dis-
lodgment of any portion, member, appurtenance or oma-
mentation of the building or structure under service loads.
EXISTING STRUCTURE. A structure erected prior to the
date of adoption of the appropriate code, or one for which a
legal building permit has been issued.
PRIMARY FUNCTION. ^^ primary function is a major activ-
ity for which the facility is intended. Areas that contain a pri-
mary function include, but are not limited to, the customer
service lobby of a bank, the dining area of a cafeteria, the meet-
ing rooms in a conference center, as well as offices and other
work areas in which the activities of the pubhc accommodation
or other private entity using the facility are carried out. Mechani-
cal rooms, boiler rooms, supply storage rooms, employee
lounges or locker rooms, janitorial closets, entrances, corridors
and restrooms are not areas containing di primary function.
SUBSTANTIAL STRUCTURAL DAMAGE. A condition
where:
1. In any story, the vertical elements of the lateral
force-resisting system have suffered damage such that
the lateral load-carrying capacity of the structure in any
horizontal direction has been reduced by more than 20
percent from its pre-damage condition; or
2. The capacity of any vertical gravity load-carrying com-
ponent, or any group of such components, that supports
more than 30 percent of the total area of the structure's
floor(s) and roof(s) has been reduced more than 20 per-
cent from its pre-damage condition and the remaining
capacity of such affected elements, with respect to all
dead and live loads, is less than 75 percent of that
required by this code for new buildings of similar struc-
ture, purpose and location.
TECHNICALLY INFEASIBLE. An alteration of a building
or a facility that has little likehhood of being accomplished
because the existing structural conditions require the removal
or alteration of a load-bearing member that is an essential part
of the structural frame, or because other existing physical or
site constraints prohibit modification or addition of elements,
spaces or features which are in full and strict compliance with
the minimum requirements for new construction and which are
necessary to provide accessibility.
592
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
SECTION 3403
ADDITIONS
3403.1 General. Additions to any building or structure shall
comply with the requirements of this code for new construc-
tion. Alterations to the existing building or structure shall be
made to ensure that the existing building or structure together
with the addition are no less conforming with the provisions of
this code than the existing building or structure was prior to the
addition. An existing building together with its additions shall
comply with the height and area provisions of Chapter 5.
Exception: For state-owned buildings, including those
owned by the University of California and the California
State University and the Judicial Council, the requirements
of Sections 3403.3 and 3403.4 are replaced by the require-
ments of Sections 3417 through 3425.
3403, Id Replacement, retention and extension of original
materials. [HCDl] Local ordinances or regulations shall
permit the replacement, retention and extension of original
materials, and the use of original methods of construction,
for any building or accessory structure, provided such
building or structure complied with the building code provi-
sions in effect at the time of original construction and the
building or accessory structure does not become or con-
tinue to be a substandard building. For additional informa-
tion, see Health and Safety Code Sections 17912, 17920.3,
17922(d), 17922.3, 17958.8 and 17958.9.
3403.2 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 1612.3, any addition
that constitutes substantial improvement of the existing struc-
ture, as defined in Section 1612.2, shall comply with the flood
design requirements for new construction, and all aspects of
the existing structure shall be brought into compliance with the
requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 1612.3, any additions that do not constitute
substantial improvement or substantial damage of the existing
structure, as defined in Section 1612.2, are not required to
comply with the flood design requirements for new construc-
tion.
3403.3 Existing structural elements carrying gravity load.
Any existing gravity load-carrying structural element for
which an addition and its related alterations cause an increase
in design gravity load of more than 5 percent shall be strength-
ened, supplemented, replaced or otherwise altered as needed to
carry the increased load required by this code for new struc-
tures. Any existing gravity load-carrying structural element
whose gravity load-carrying capacity is decreased shall be con-
sidered an altered element subject to the requirements of Sec-
tion 3404.3. Any existing element that will form part of the
lateral load path for any part of the addition shall be considered
an existing lateral load-carrying structural element subject to
the requirements of Section 3403.4.
3403.3.1 Design live load. Where the addition does not
result in increased design live load, existing gravity
load-carrying structural elements shall be permitted to be
evaluated and designed for live loads approved prior to the
addition. If the approved live load is less than that required
by Section 1607, the area designed for the nonconforming
live load shall be posted with placards of approved design
indicating the approved live load. Where the addition does
result in increased design live load, the live load required by
Section 1607 shall be used.
3403.4 Existing structural elements carrying lateral load.
Where the addition is structurally independent of the existing
structure, existing lateral load-carrying structural elements
shall be permitted to remain unaltered. Where the addition is
not structurally independent of the existing structure, the exist-
ing structure and its addition acting together as a single struc-
ture shall be shown to meet the requirements of Sections 1609
and 1613.
Exception: Any existing lateral load-carrying structural
element whose demand-capacity ratio with the addition
considered is no more than 10 percent greater than its
demand-capacity ratio with the addition ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applica-
ble load combinations with design lateral loads or forces in
accordance with Sections 1609 and 1613. For purposes of
this exception, comparisons of demand-capacity ratios and
calculation of design lateral loads, forces and capacities
shall account for the cumulative effects of additions and
alterations since original construction.
3403.4.1 Seismic. Seismic requirements for alterations
shall be in accordance with this section. Where the existing
seismic force-resisting system is a type that can be desig-
nated ordinary, values of R, Qq and Q for the existing seis-
mic force-resisting system shall be those specified by this
code for an ordinary system unless it is demonstrated that
the existing system will provide performance equivalent to
that of a detailed intermediate or special system.
SECTION 3404
ALTERATIONS
3404.1 General. Except as provided by Section 3401.4 or this
section, alterations to any building or structure shall comply
with the requirements of the code for new construction. Alter-
ations shall be such that the existing building or structure is no
less complying with the provisions of this code than the exist-
ing building or structure was prior to the alteration.
Exceptions:
1. An existing stairway shall not be required to comply
with the requirements of Section 1009 where the
existing space and construction does not allow a
reduction in pitch or slope.
2. Handrails otherwise required to comply with Section
1009.12 shall not be required to comply with the
requirements of Section 1012.6 regarding full exten-
sion of the handrails where such extensions would be
hazardous due to plan configuration.
3. For state-owned buildings, including those owned by
the University of California and the California State
University and the Judicial Council, the requirements
of Sections 3404.3 through 3404.5 are replaced by
the requirements of Sections 3417 through 3423.
2010 CALIFORNIA BUILDING CODE
593
EXISTING STRUCTURES
3404,1.1 Replacement, retention and extension of original
materials, [HCDl] Local ordinances or regulations shall
permit the replacement, retention and extension of original
materials, and the use of original methods of construction,
for any building or accessory structure, provided such
building or structure complied with the building code provi-
sions in effect at the time of original construction and the
building or accessory structure does not become or con-
tinue to be a substandard building. For additional informa-
tion, see Health and Safety Code Sections 17912, 17920.3,
17922(d), 179223, 17958.8 and 17958.9.
3404.2 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 1612.3, any alter-
ation that constitutes substantial improvement of the existing
structure, as defined in Section 1612.2, shall comply with the
flood design requirements for new construction, and all aspects
of the existing structure shall be brought into comphance with
the requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 1612.3, any alterations that do not constitute
substantial improvement or substantial damage of the existing
structure, as defined in Section 1612.2, are not required to com-
ply with the flood design requirements for new construction.
3404.3 Existing structural elements carrying gravity load.
Any existing gravity load-carrying structural element for
which an alteration causes an increase in design gravity load of
more than 5 percent shall be strengthened, supplemented,
replaced or otherwise altered as needed to carry the increased
gravity load required by this code for new structures. Any
existing gravity load-carrying structural element whose grav-
ity load-carrying capacity is decreased as part of the alteration
shall be shown to have the capacity to resist the applicable
design gravity loads required by this code for new structures.
3404.3.1 Design live load. Where the alteration does not
result in increased design live load, existing gravity
load-carrying structural elements shall be permitted to be
evaluated and designed for live loads approved prior to the
alteration. If the approved live load is less than that required
by Section 1607, the area designed for the nonconforming
live load shall be posted with placards of approved design
indicating the approvedliwe load. Where the alteration does
result in increased design live load, the hve load required by
Section 1607 shall be used.
3404.4 Existing structural elements carrying lateral load.
Except as permitted by Section 3404.5, where the alteration
increases design lateral loads in accordance with Section 1609
or 1613, or where the alteration results in a structural irregular-
ity as defined in ASCE 7, or where the alteration decreases the
capacity of any existing lateral load-carrying structural ele-
ment, the structure of the altered building or structure shall be
shown to meet the requirements of Sections 1609 and 1613.
Exception: Any existing lateral load-carrying structural
element whose demand-capacity ratio with the alteration
considered is no more than 10 percent greater than its
demand-capacity ratio with the alteration ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applica-
ble load combinations with design lateral loads or forces per
Sections 1609 and 1613. For purposes of this exception,
comparisons of demand-capacity ratios and calculation of
design lateral loads, forces, and capacities shall account for
the cumulative effects of additions and alterations since
original construction.
3404.4.1 Seismic. Seismic requirements for alterations
shall be in accordance with this section. Where the existing
seismic force-resisting system is a type that can be desig-
nated ordinary, values of/?, Qq and Q for the existing seis-
mic force-resisting system shall be those specified by this
code for an ordinary system unless it is demonstrated that
the existing system will provide performance equivalent to
that of a detailed intermediate or special system.
3404.5 Voluntary seismic improvements. Alterations to
existing structural elements or additions of new structural ele-
ments that are not otherwise required by this chapter and are
initiated for the purpose of improving the performance of the
seismic force-resisting system of an existing structure or the
performance of seismic bracing or anchorage of existing
nonstructural elements shall be permitted, provided that an
engineering analysis is submitted demonstrating the following:
1. The altered structure and the altered nonstructural ele-
ments are no less in compliance with the provisions of
this code with respect to earthquake design than they
were prior to the alteration.
2. New structural elements are detailed and connected to
the existing structural elements as required by Chapter
16.
3 . New or relocated nonstructural elements are detailed and
connected to existing or new structural elements as
required by Chapter 16.
4. The alterations do not create a structural irregularity as
defined in ASCE 7 or make an existing structural irregu-
larity more severe.
3404.6 Means of egress capacity factors. Alterations to any
existing building or structure shall not be affected by the egress
width factors in Section 1005.1 for new construction in deter-
mining the minimum egress widths or the minimum number of
exits in an existing building or structure. The minimum egress
widths for the components of the means of egress shall be based
on the means of egress width factors in the building code under
which the building was constructed, and shall be considered as
complying means of egress for any alteration if, in the opinion
of the building code official, they do not constitute a distinct
hazard to life.
SECTION 3405
REPAIRS
3405.1 General, Buildings and structures, and parts thereof,
shall be repaired in compliance with Section 3401.2. Work on
nondamaged components that is necessary for the required
repair of damaged components shall be considered part of the
repair and shall not be subject to the requirements for alter-
ations in this chapter. Routine maintenance required by Section
3401.2, ordinary repairs exempt from permit in accordance
with Section 105.2, and abatement of wear due to normal ser-
594
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
vice conditions shall not be subject to the requirements for
repairs in this section.
Exception: For state-owned buildings, including those
owned by the University of California and the California
State University and the Judicial Council, the requirements
of Sections 3405.2 through 3405.4 are replaced by the
requirements of Sections 3417 through 3423.
3405.1.1 Dangerous conditions. Regardless of the extent
of structural or nonstructural damage, the building code
official shall have the authority to require the elimination of
conditions deemed dangerous.
3405 J. 2 Replacement^ retention and extension of original
materials. [HCD 1] Local ordinances or regulations shall
permit the replacement, retention and extension of original
materials, and the use of original methods of construction,
for any building or accessory structure, provided such
building or structure complied with the building codeprovi-
sions in effect at the time of original construction and the
building or accessory structure does not become or con-
tinue to be a substandard building. For additional informa-
tion, see Health and Safety Code Sections 17912, 17920.3,
17922(d), 17922.3, 17958.8 and 17958.9.
3405,2 Substantial structural damage to vertical elements
of the lateral force-resisting system. A building that has sus-
tained substantial structural damage to the vertical elements of
its lateral force-resisting system shall be evaluated and repaired
in accordance with the applicable provisions of Sections
3405.2.1 through 3405.2.3.
3405.2.1 Evaluation. The building shall be evaluated by a
registered design professional, and the evaluation findings
shall be submitted to the code official. The evaluation shall
estabHsh whether the damaged building, if repaired to its
predamage state, would comply with the provisions of this
code for wind and earthquake loads. Evaluation for earth-
quake loads shall be required if the substantial structural
damage was caused by or related to earthquake effects or if
the building is in Seismic Design Category C, D, E or F.
Wind loads for this evaluation shall be those prescribed
in Section 1609. Earthquake loads for this evaluation, if
required, shall be permitted to be 75 percent of those pre-
scribed in Section 1613. Values of R, Wq and Q for the
existing seismic force-resisting system shall be those spec-
ified by this code for an ordinary system unless it is demon-
strated that the existing system will provide performance
equivalent to that of an intermediate or special system.
3405.2.2 Extent of repair for compliant buildings. If the
evaluation establishes compliance of the predamage build-
ing in accordance with Section 3405.2.1, then repairs shall
be permitted that restore the building to its predamage state
using materials and strengths that existed prior to the dam-
age.
3405.2.3 Extent of repair for noncompliant buildings. If
the evaluation does not establish compliance of the predam-
age building in accordance with Section 3405.2.1, then the
building shall be rehabilitated to comply with applicable
provisions of this code for load combinations, including
wind or seismic loads. The wind loads for the repair shall be
as required by the building code in effect at the time of origi-
nal construction, unless the damage was caused by wind, in
which case the wind loads shall be as required by the code in
effect at the time of original construction or as required by
this code, whichever are greater. Earthquake loads for this
rehabilitation design shall be those required for the design
of the predamage building, but not less than 75 percent of
those prescribed in Section 1613. New structural members
and connections required by this rehabilitation design shall
comply with the detailing provisions of this code for new
buildings of similar structure, purpose and location.
3405.3 Substantial structural damage to gravity load-car-
rying components. Gravity load-carrying components that
have sustained substantial structural damage shall be rehabili-
tated to comply with the applicable provisions of this code for
dead and live loads. Snow loads shall be considered if the sub-
stantial structural damage was caused by or related to snow
load effects. Existing gravity load-carrying structural elements
shall be permitted to be designed for live loads approved prior
to the damage. Nondamaged gravity load-carrying compo-
nents that receive dead, live or snow loads from rehabilitated
components shall also be rehabilitated or shown to have the
capacity to carry the design loads of the rehabilitation design.
New structural members and connections required by this
rehabilitation design shall comply with the detailing provisions
of this code for new buildings of similar structure, purpose and
location.
3405.3.1 Lateral force-resisting elements. Regardless of
the level of damage to vertical elements of the lateral
force-resisting system, if substantial structural damage to
gravity load-carrying components was caused primarily
by wind or earthquake effects, then the building shall be
evaluated in accordance with Section 3405.2.1 and, if
noncompliant, rehabilitated in accordance with Section
3405.2.3.
3405.4 Less than substantial structural damage. For dam-
age less than substantial structural damage, repairs shall be
allowed that restore the building to its predamage state using
materials and strengths that existed prior to the damage. New
structural members and connections used for this repair shall
comply with the detailing provisions of this code for new build-
ings of similar structure, purpose and location.
3405.5 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 1612.3, any repair
that constitutes substantial improvement of the existing struc-
ture, as defined in Section 1612.2, shall comply with the flood
design requirements for new construction, and all aspects of
2010 CALIFORNIA BUILDING CODE
595
EXISTING STRUCTURES
the existing structure shall be brought into compliance with the
requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 1612.3, any repairs that do not constitute sub-
stantial improvement or substantial damage of the existing
structure, as defined in Section 1612.2, are not required to
comply with the flood design requirements for new construc-
tion.
SECTION 3406
FIRE ESCAPES
3406.1 Where permitted. Fire escapes shall be permitted only
as provided for in Sections 3406.1.1 through 3406.1.4.
3406.1.1 New buildings. Fire escapes shall not constitute
any part of the required means of egress in new buildings.
3406.1.2 Existing fire escapes. Existing fire escapes shall
be continued to be accepted as a component in the means of
egress in existing buildings only.
3406.1.3 New fire escapes. New fire escapes for existing
buildings shall be permitted only where exterior stairs can-
not be utilized due to lot lines limiting stair size or due to the
sidewalks, alleys or roads at grade level. New fire escapes
shall not incorporate ladders or access by windows.
3406.1.4 Limitations. Fire escapes shall comply with this
section and shall not constitute more than 50 percent of the
required number of exits nor more than 50 percent of the
required exit capacity.
3406.2 Location. Where located on the front of the building
and where projecting beyond the building line, the lowest land-
ing shall not be less than 7 feet (2134 mm) or more than 12 feet
(3658 mm) above grade, and shall be equipped with a counter-
balanced stairway to the street. In alleyways and thoroughfares
less than 30 feet (9144 mm) wide, the clearance under the low-
est landing shall not be less than 12 feet (3658 mm).
3406.3 Construction. The fire escape shall be designed to sup-
port a live load of 100 pounds per square foot (4788 Pa) and
shall be constructed of steel or other approved noncombustible
materials. Fire escapes constructed of wood not less than nomi-
nal 2 inches (5 1 mm) thick are permitted on buildings of Type 5
construction. Walkways and railings located over or supported
by combustible roofs in buildings of Type 3 and 4 construction
are permitted to be of wood not less than nominal 2 inches (5 1
mm) thick.
3406.4 Dimensions. Stairs shall be at least 22 inches (559 mm)
wide with risers not more than, and treads not less than, 8
inches (203 mm) and landings at the foot of stairs not less than
40 inches (1016 mm) wide by 36 inches (914 mm) long,
located not more than 8 inches (203 mm) below the door.
3406.5 Opening protectives. Doors and windows along the
fire escape shall be protected with ^/4-hour opening protectives.
SECTION 3407
GLASS REPLACEMENT
3407.1 Conformance. The installation or replacement of glass
shall be as required for new installations.
SECTION 3408
CHANGE OF OCCUPANCY
3408.1 Conformance. No change shall be made in the use or
occupancy of any building that would place the building in a
different division of the same group of occupancies or in a dif-
ferent group of occupancies, unless such building is made to
comply with the requirements of this code for such division or
group of occupancies. Subject to the approval of the building
official, the use or occupancy of existing buildings shall be per-
mitted to be changed and the building is allowed to be occupied
for purposes in other groups without conforming to all the
requirements of this code for those groups, provided the new or
proposed use is less hazardous, based on hfe and fire risk, than
the existing use.
3408.2 Certificate of occupancy. A certificate of occupancy
shall be issued where it has been determined that the require-
ments for the new occupancy classification have been met.
3408.3 Stairways. Existing stairways in an existing structure
shall not be required to comply with the requirements of a new
stairway as outlined in Section 1009 where the existing space
and construction will not allow a reduction in pitch or slope.
3408.4 Change of occupancy. When a change of occupancy
results in a structure being reclassified to a higher occupancy
category, the structure shall conform to the seismic require-
ments for a new structure of the higher occupancy category.
Where the existing seismic force-resisting system is a type that
can be designated ordinary, values ofR, Q.o and Q for the exist-
ing seismic force-resisting system shall be those specified by
this code for an ordinary system unless it is demonstrated that
the existing system will provide performance equivalent to that
of a detailed, intermediate or special system.
Exceptions:
1 . Specific seismic detailing requirements of this code
or Section 1613 for a new structure shall not be
required to be met where it can be shown that the level
of performance and seismic safety is equivalent to
that of a new structure. Such analysis shall consider
the regularity, over strength, redundancy and ductility
of the structure within the context of the existing and
retrofit (if any) detailing provided.
2. When a change of use results in a structure being
reclassified from Occupancy Category I or II to Occu-
pancy Category III and the structure is located in a
seismic map area where Sj^^ < 0.33, compliance with
the seismic requirements of this code and Section
1613 are not required.
596
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
SECTION 3409
HISTORIC BUILDINGS
[DSA-AC] For applications listed in Section 1.9.1 regulated
by the Division of the State Architect-Access Compliance for
Qualified Historical Buildings y see California Code of Regula-
tions, Title 24, Part 8 (California Historical Building Code).
3409.1 Historic buildings. The provisions of this code relating
to the construction, repair, alteration, addition, restoration and
movement of structures, and change of occupancy shall not be
mandatory for historic buildings where such buildings are
judged by the building official to not constitute a distinct life
safety hazard.
3409.2 Flood hazard areas. Within flood hazard areas estab-
lished in accordance with Section 1612.3, where the work pro-
posed constitutes substantial improvement as defined in
Section 1612.2, the building shall be brought into compliance
with Section 1612.
Exception: Historic buildings that are:
1. Listed or preliminarily determined to be eligible for
listing in the National Register of Historic Places;
2. Determined by the Secretary of the U.S. Department
of Interior as contributing to the historical signifi-
cance of a registered historic district or a district pre-
liminarily determined to qualify as an historic district;
or
3. Designated as historic under a state or local historic
preservation program that is approved by the Depart-
ment of Interior,
SECTION 3410
MOVED STRUCTURES
3410.1 Conformance. Structures moved into or within the
jurisdiction shall comply with the provisions of this code for
new structures.
I I Exception: [BCD 1 & BCD 2] After July 1, 1978, local
ordinances or regulations for moved apartment houses and
dwellings shall permit the retention of existing materials
and methods of construction, provided the apartment house
or dwelling complies with the building standards for foun-
dations applicable to new construction and does not
become or continue to be a substandard building. For addi-
tional information, see Health and Safety Code Section
17958.9.
SECTION 3411
ACCESSIBILITY FOR EXISTING BUILDINGS
3411.1 Scope. The provisions of Sections 3411.1 through
341 1.9 apply to maintenance, change of occupancy, additions
and alterations to existing buildings, including those identified
as historic buildings.
Exception: Type B dwelling or sleeping units required by
Chapter 11 A or IIB as applicable of this code are not
required to be provided in existing buildings and facilities
being altered or undergoing a change of occupancy.
3411.2 Maintenance of facilities. A building, facility or ele-
ment that is constructed or altered to be accessible shall be
maintained accessible during occupancy.
3411.3 Extent of application. An alteration of an existing ele-
ment, space or area of a building or facility shall not impose a
requirement for greater accessibility than that which would be
required for new construction.
Alterations shall not reduce or have the effect of reducing
accessibility of a building, portion of a building or facility.
3411.4 Change of occupancy. Existing buildings that
undergo a change of group or occupancy shall comply with
this section.
3411.4.1 Partial change in occupancy. Where a portion of
the building is changed to a new occupancy classification,
any alterations shall comply with Sections 3411.6, 3411.7
and 3411.8.
3411.4.2 Complete change of occupancy. Where an entire
building undergoes a change of occupancy, it shall comply
with Section 3411.4.1 and shall have all of the following
accessible features:
1. At least one accessible building entrance.
2. At least one accessible route from an accessible
building entrance io primary function areas.
3. Signage complying with Chapter 11 A or IIB as
applicable,
4. Accessible parking, where parking is being provided.
5. At least one accessible passenger loading zone, when
loading zones are provided.
6. At least one accessible route connecting accessible
parking and accessible passenger loading zones to an
accessible entrance.
Where it is technically infeasible to comply with the new
construction standards for any of these requirements for a
change of group or occupancy, the above items shall con-
form to the requirements to the maximum extent technically
feasible.
3411.5 Additions. Provisions for new construction shall apply
to additions. An addition that affects the accessibility to, or
contains an area of, a primary function shall comply with the
requirements in Section 3411.7.
3411.6 Alterations. A building, facility or element that is
altered shall comply with the applicable provisions in Chapter
UA or IIB as applicable of this code and ICC Al 17.1, unless
technically infeasible. Where compliance with this section is
technically infeasible, the alteration shall provide access to the
maximum extent technically feasible.
Exceptions:
1. The altered element or space is not required to be on
an accessible route, unless required by Section
3411.7.
2. Accessible means of egress required by Chapter 10 are
not required to be provided in existing buildings and
facilities.
2010 CALIFORNIA BUILDING CODE
597
EXISTING STRUCTURES
3. The alteration to Type A individually owned dwelling
units within a Group R-2 occupancy shall meet the
provision for a Type B dwelling unit and shall comply
with the applicable provisions in Chapter llA orllB
as applicable.
3411.7 Alterations affecting an area containing a primary
function. Where an alteration affects the accessibility to, or
contains an area oi primary function, the route to the primary
function area shall be accessible. The accessible route to the
primary function area shall include toilet facilities or drinking
fountains serving the area of primary function.
Exceptions:
1 . The costs of providing the accessible route are not
required to exceed 20 percent of the costs of the alter-
ations affecting the area of primary function.
2. This provision does not apply to alterations limited
solely to windows, hardware, operating controls,
electrical outlets and signs.
3. This provision does not apply to alterations limited
solely to mechanical systems, electrical systems,
installation or alteration of fire protection systems
and abatement of hazardous materials.
4. This provision does not apply to alterations under-
taken for the primary purpose of increasing the acces-
sibility of an existing building, facility or element.
3411.8 Scoping for alterations. The provisions of Sections
341 1.8.1 through 341 1.8.14 shall apply to alterations to exist-
ing buildings and facilities.
3411.8.1 EntrsLnces. Accessible entrances shall be provided
I I in accordance with Chapter IIA or IIB as applicable.
Exception: Where an alteration includes alterations to
an entrance, and the building or facility has an accessible
entrance, the altered entrance is not required to be acces-
sible, unless required by Section 3411.7. Signs comply-
I I ing with Chapter llA or IIB as applicable shall be
provided.
3411.8.2 Elevators. Altered elements of existing elevators
shall comply with ASME A17. 1 and ICC Al 17. 1 . Such ele-
ments shall also be altered in elevators programmed to
respond to the same hall call control as the altered elevator.
3411.8.3 Platform lifts. Platform (wheelchair) lifts com-
plying with ICC A117.1 and installed in accordance with
ASME A 18.1 shall be permitted as a component of an
accessible route.
I 3411.8.4 Stairs and escalators in existing buildings. In
I alterations, change of occupancy or additions where an
escalator or stair is added where none existed previously
and major structural modifications are necessary for instal-
lation, an accessible route shall be provided between the
levels served by the escalator or stairs in accordance with
I I Chapter llA or IIB as applicable.
3411.8.5 Ramps. Where slopes steeper than allowed by
Section 1010.2 are necessitated by space limitations, the
slope of ramps in or providing access to existing buildings
or facilities shall comply with Table 3411.8.5.
TABLE 341 1.8.5
RAMPS
SLOPE
MAXIMUM RISE
Steeper than 1:10 but not steeper than 1:8
3 inches
Steeper than 1 : 12 but not steeper than 1:10
6 inches
For SI: 1 inch = 25.4 mm.
3411.8.6 Performance areas. Where it is technically infea-
sible to alter performance areas to be on an accessible route,
at least one of each type of performance area shall be made
accessible.
3411.8.7 Accessible dwelling or sleeping units. Where
Group I-l, 1-2, 1-3, R-1, R-2 or R-4 dwelling or sleeping
units are being altered or added, the requirements of Chap-
ter IIA or I IB as applicable for Accessible units apply only
to the quantity of spaces being altered or added.
3411.8.8 Type A dwelling or sleeping units. Where more
than 20 Group R-2 dwelling or sleeping units are being
added, the requirements of Chapter IIA or IIB as applica-
ble for Type A units apply only to the quantity of the spaces
being added.
3411.8.9 Type B dwelling or sleeping units. Where four or
more Group I- 1 , 1-2, R- 1 , R-2, R-3 or R-4 dwelling or sleep-
ing units are being added, the requirements of Chapter IIA
or I IB as applicable for Type B units apply only to the quan-
tity of the spaces being added.
3411.8.10 Jury boxes and witness stands. In alterations,
accessible wheelchair spaces are not required to be located
within the defined area of raised jury boxes or witness
stands and shall be permitted to be located outside these
spaces where the ramp or lift access restricts or projects into
the means of egress.
3411.8.11 Toilet rooms. Where it is technically infeasible
to alter existing toilet and bathing facilities to be accessible,
an accessible family or assisted-use toilet or bathing facility
constructed in accordance with Chapter IIA or IIB as
applicable is permitted. The family or assisted-use facility
shall be located on the same floor and in the same area as the
existing facilities.
3411.8.12 Dressing, fitting and locker rooms. Where it is
technically infeasible to provide accessible dressing, fitting
or locker rooms at the same location as similar types of
rooms, one accessible room on the same level shall be pro-
vided. Where separate-sex facilities are provided, accessi-
ble rooms for each sex shall be provided. Separate-sex
facilities are not required where only unisex rooms are pro-
vided.
3411.8.13 Fuel dispensers. Operable parts of replacement
fuel dispensers shall be permitted to be 54 inches (1370
mm) maximum measured from the surface of the vehicular
way where fuel dispensers are installed on existing curbs.
3411.8.14 Thresholds. The maximum height of thresholds
at doorways shall be % inch (19.1 mm). Such thresholds
shall have beveled edges on each side.
3411.9 Historic buildings. These provisions shall apply to
buildings and facilities designated as historic structures that
598
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
undergo alterations or a change of occupancy, unless techni-
cally infeasible. Where compliance with the requirements for
accessible routes, entrances or toilet facilities would threaten
or destroy the historic significance of the building or facility, as
determined by the applicable governing authority, the alterna-
tive requirements of Sections 3411.9.1 through 3411.9.4 for
that element shall be permitted.
3411.9.1 Site arrival points. At least one accessible route
from a site arrival point to an accessible entrance shall be
provided.
3411.9.2 Multilevel buildings and facilities. An accessi-
ble route from an accessible entrance to public spaces on the
level of the accessible entrance shall be provided.
3411.9.3 Entrances. At least one main entrance shall be
accessible.
Exceptions:
1. If a main entrance cannot be made accessible, an
accessible nonpublic entrance that is unlocked
while the building is occupied shall be provided; or
2. If a main entrance cannot be made accessible, a
locked accessible entrance with a notification sys-
tem or remote monitoring shall be provided.
Signs complying with Chapter llA or IIB as applicable
shall be provided at the primary entrance and the accessible
entrance.
3411.9.4 Toilet and bathing facilities. Where toilet rooms
are provided, at least one accessible family or assisted-use
toilet room complying with Chapter I lA orllB as applica-
ble shall be provided.
SECTION 3412
COMPLIANCE ALTERNATIVES
3412.1 Compliance. The provisions of this section are
intended to maintain or increase the current degree of public
safety, health and general welfare in existing buildings while
permitting repair, alteration, addition and change of occu-
pancy without requiring full compliance with Chapters 2
through 33, or Sections 3401 .3, and 3403 through 3409, except
where compliance with other provisions of this code is specifi-
cally required in this section.
3412.2 Applicability. Structures existing prior to January 1,
I I 201 1 , in which there is work involving additions, alterations or
changes of occupancy shall be made to comply with the
requirements of this section or the provisions of Sections 3403
through 3409. The provisions in Sections 3412.2.1 through
3412.2.5 shall apply to existing occupancies that will continue
to be, or are proposed to be, in Groups A, B, E, F, M, R, S and U.
These provisions shall not apply to buildings with occupancies
in Group H or I.
3412.2.1 Change in occupancy. Where an existing build-
ing is changed to a new occupancy classification and this
section is applicable, the provisions of this section for the
new occupancy shall be used to determine compliance with
this code.
3412.2.2 Partial change in occupancy. Where a portion of
the building is changed to a new occupancy classification,
and that portion is separated from the remainder of the
building with fire barriers or horizontal assemblies having a
fire-resistance rating as required by Table 508.4 for the sep-
arate occupancies, or with approved compliance alterna-
tives, the portion changed shall be made to comply with the
provisions of this section.
Where a portion of the building is changed to a new occu-
pancy classification, and that portion is not separated from
the remainder of the building with^zr^ barriers or horizontal
assemblies having ?i fire-resistance rating as required by
Table 508.4 for the separate occupancies, or with approved
compliance alternatives, the provisions of this section
which apply to each occupancy shall apply to the entire
building. \Vhere there are conflicting provisions, those
requirements which secure the greater public safety shall
apply to the entire building or structure.
3412.2.3 Additions. Additions to existing buildings shall
comply with the requirements of this code for new construc-
tion. The combined height and area of the existing building
and the new addition shall not exceed the height and area
allowed by Chapter 5. Where difire wall that complies with
Section 706 is provided between the addition and the existing
building, the addition shall be considered a separate building.
3412.2.4 Alterations and repairs. An existing building or
portion thereof, which does not comply with the require-
ments of this code for new construction, shall not be altered
or repaired in such a manner that results in the building
being less safe or sanitary than such building is currently. If,
in the alteration or repair, the current level of safety or sani-
tation is to be reduced, the portion altered or repaired shall
conform to the requirements of Chapters 2 through 12 and
Chapters 14 through 33.
3412.2.4.1 Flood hazard areas. For existing buildings
located in flood hazard areas estabhshed in Section
1612.3, if the alterations and repairs constitute substan-
tial improvement of the existing building, the existing
building shall be brought into compliance with the
requirements for new construction for flood design.
3412.2.5 Accessibility requirements. All portions of the
buildings proposed for change of occupancy shall conform
to the accessibility provisions of Section 341 1.
3412.3 Acceptance. For repairs, alterations, additions and
changes of occupancy to existing buildings that are evaluated
in accordance with this section, compliance with this section
shall be accepted by the building official.
3412.3.1 Hazards. Where the building official determines
that an unsafe condition exists, as provided for in Section
116, such unsafe condition shall be abated in accordance
with Section 116.
3412.3.2 Compliance with other codes. Buildings that are
evaluated in accordance with this section shall comply with
the California Fire Code and the California Property Main-
tenance Code.
3412.4 Investigation and evaluation. For proposed work cov-
ered by this section, the building owner shall cause the existing
2010 CALIFORNIA BUILDING CODE
599
EXISTING STRUCTURES
building to be investigated and evaluated in accordance with
the provisions of this section.
3412.4.1 Structural analysis. The owner shall have a struc-
tural analysis of the existing building made to determine
adequacy of structural systems for the proposed alteration,
addition or change of occupancy. The analysis shall demon-
strate that the building with the work completed is capable
of resisting the loads specified in Chapter 16.
3412.4.2 Submittal. The results of the investigation and
evaluation as required in Section 3412.4, along with pro-
posed compliance alternatives, shall be submitted to the
building official.
3412.4.3 Determination of compliance. The building offi-
cial shall determine whether the existing building, with the
proposed addition, alteration or change of occupancy, com-
plies with the provisions of this section in accordance with
the evaluation process in Sections 3412.5 through 3412.9.
3412.5 Evaluation. The evaluation shall be comprised of three
categories: fire safety, means of egress and general safety, as
defined in Sections 3412.5.1 through 3412.5.3,
3412.5.1 Fire safety. Included within the fire safety cate-
gory are the structural ^zre resistance, automatic fire detec-
tion, fire alarm and fire suppression system features of the
facility.
3412.5.2 Means of egress. Included within the means of
egress category are the configuration, characteristics and
support features for means of egress in the facility.
3412.5.3 General safety. Included within the general safety
category are the fire safety parameters and the means of
egress parameters.
3412.6 Evaluation process. The evaluation process specified
herein shall be followed in its entirety to evaluate existing
buildings. Table 3412.7 shall be utilized for tabulating the
results of the evaluation. References to other sections of this
code indicate that compliance with those sections is required in
order to gain credit in the evaluation herein outlined. In apply-
ing this section to a building with mixed occupancies, where
the separation between the mixed occupancies does not quahfy
for any category indicated in Section 3412.6.16, the score for
each occupancy shall be determined and the lower score deter-
mined for each section of the evaluation process shall apply to
the entire building.
Where the separation between mixed occupancies qualifies
for any category indicated in Section 3412.6.16, the score for
each occupancy shall apply to each portion of the building
based on the occupancy of the space.
3412.6.1 Building height. The value for building height
shall be the lesser value determined by the formula in Sec-
tion 3412.6.1.1. Chapter 5 shall be used to determine the
allowable height of the building, including allowable
increases due to automatic sprinklers as provided for in Sec-
tion 504.2. Subtract the actual building height in feet from
the allowable and divide by 1 2 V2 feet. Enter the height value
and its sign (positive or negative) in Table 3412.7 under
Safety Parameter 3412.6. 1, Building Height, for fire safety,
means of egress and general safety. The maximum score for
a building shall be 10.
3412.6.1.1 Height formula. The following formulas
shall be used in computing the building height value.
Height value, feet =
(AH)-iEBH)
1Z5
xCF
Height value, stories =(A5 - EBS) x CF
(Equation 34-1)
where:
AH = Allowable height in feet from Table 503.
EBH = Existing building height in feet.
AS - Allowable height in stories from Table 503.
EBS = Existing building height in stories.
CF = 1 if (AH) - {EBH) is positive.
CF - Construction-type factor shown in Table
3412.6.6(2) if {AH) - {EBH) is negative.
Note: Where mixed occupancies are separated and indi-
vidually evaluated as indicated in Section 3412.6, the
values AH, AS, EBH and EBS shall be based on the
height of the occupancy being evaluated.
3412.6.2 Building area. The value for building area shall be
determined by the formula in Section 3412.6.2.2. Section
503 and the formula in Section 3412.6.2.1 shall be used to
determine the allowable area of the building. This shall
include any allowable increases due to frontage and auto-
matic sprinklers as provided for in Section 506. Subtract the
actual building area in square feet from the allowable area
and divide by 1,200 square feet. Enter the area value and its
sign (positive or negative) in Table 3412.7 under Safety
Parameter 3412.6.2, Building Area, for fire safety, means of
egress and general safety. In determining the area value, the
maximum permitted positive value for area is 50 percent of
the fire safety score as listed in Table 3412.8, Mandatory
Safety Scores.
3412.6.2.1 Allowable area formula. The following for-
mula shall be used in computing allowable area:
A={\ + y+ 1,) X A, (Equation 34-2)
where:
A^ = Allowable area.
A, = Tabular area per story in accordance with Table
503 (square feet)
1^ = Area increase factor for sprinklers (Section 506 . 3) .
\f = Area increase factor for frontage (Section 506.2).
600
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3412.6.2.2 Area formula. The following formula shall be
used in computing the area value. Determine the area
value for each occupancy floor area on a floor-by-floor
basis. For each occupancy, choose the minimum area
value of the set of values obtained for the particular occu-
pancy.
Allowable
area
Area value i -
where:
1,200 square feet
Actual
area,-
Allowable
area ■
Actual
area„
Allowable
area„
(Equation 34-3)
/ = Value for an individual separated occupancy on a
floor.
n = Number of separated occupancies on a floor.
3412.6.3 Compartmentation. Evaluate the compartments
created by fire barriers or horizontal assemblies which
comply with Sections 3412.6.3.1 and 3412.6.3.2 and which
are exclusive of the wall elements considered under Sec-
tions 3412.6.4 and 3412.6.5. Conforming compartments
shall be figured as the net area and do not include shafts,
chases, stairways, walls or columns. Using Table 3412.6.3,
determine the appropriate compartmentation value (CV)
and enter that value into Table 3412.7 under Safety Parame-
ter 3412.6.3, Compartmentation, for fire safety, means of
egress and general safety.
3412.6.3.1 Wall construction. A wall used to create sepa-
rate compartments shall be afire barrier conforming to
Section 707 with Sifire-resistance rating of not less than 2
hours. Where the building is not divided into more than
one compartment, the compartment size shall be taken as
the total floor area on all floors. Where there is more than
one compartment within a story, each compartmented
area on such story shall be provided with a horizontal exit
conforming to Section 1025. Tho fire door serving as the
horizontal exit between compartments shall be so
installed, fitted and gasketed that such fire door will pro-
vide a substantial barrier to the passage of smoke.
3412.6.3.2 Floor/ceiling construction. A floor/ceiling
assembly used to create compartments shall conform to
Section 712 and shall have afire-resistance rating of not
less than 2 hours.
3412.6.4 Tenant and dwelling unit separations. Evalu-
ate ihQ fire-resistance rating of floors and walls separating
tenants, including dwelling units, and not evaluated under
Sections 3412.6.3 and 3412.6.5. Under the categories and
occupancies in Table 3412.6.4, determine the appropriate
value and enter that value in Table 3412.7 under Safety
Parameter 3412.6.4, Tenant and Dwelling Unit Separa-
tions, for fire safety, means of egress and general safety.
TABLE 3412.6.4
SEPARATION VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
A-1
1
A-2
-5
-3
1
3
A-3,A-4,B,E,F,M,S-1
-4
-3
2
4
R
-4
-2
2
4
S-2
-5
-2
2
4
3412.6.4.1 Categories. The categories for tenant and
dwelling unit separations are:
1. Category a — ^o fire partitions', incomplete /zr^
partitions', no doors; doors not self-closing or
automatic-closing .
2. Category b — Fire partitions or floor assemblies
with less than a l-hom fire-resistance rating or not
constructed in accordance with Sections 709 or
712, respectively.
3. Category c — Fire partitions with a 1-hour or
grtditer fire-resistance rating constructed in accor-
dance with Section 709 and floor assemblies with a
1-hour but less than 2-hour fire-resistance rating
constructed in accordance with Section 712, or
with only one tenant within the floor area.
4. Category d — Fire barriers with a 1-hour but less
than 2-hour fire-resistance rating constructed in
accordance with Section 707 and floor assemblies
with a 2-hour or gxtatev fire-resistance rating con-
structed in accordance with Section 712.
5. Category e — Fire barriers and floor assemblies
with a 2-hour or greater fire-resistance rating and
constructed in accordance with Sections 707 and
712, respectively.
TABLE 3412.6.3
COMPARTMENTATION VALUES
OCCUPANCY
CATEGORIES"
a
Compartment size
equal to or greater than
15,000 square feet
b
Compartment
size of
10,000 square feet
c
Compartment
size of
7,500 square feet
d
Compartment
size of
5,000 square feet
e
Compartment
size of
2,500 square feet or less
A-l,A-3
6
10
14
18
A-2
4
10
14
18
A-4, B, E, S-2
5
10
15
20
F, M, R, S-1
4
10
16
22
For SI: 1 square foot = 0.093 ml
a. For areas between categories, the compartmentation value shall be obtained by linear interpolation.
2010 CALIFORNIA BUILDING CODE
601
EXISTING STRUCTURES
3412.6.5 Corridor walls. Evaluate the^ fire-resistance rat-
ing and degree of completeness of walls which create corri-
dors serving the floor, and constructed in accordance with
Section 1018. This evaluation shall not include the wall ele-
ments considered under Sections 3412.6.3 and 3412.6.4.
Under the categories and groups in Table 3412.6.5, deter-
mine the appropriate value and enter that value into Table
3412.7 under Safety Parameter 3412.6.5, Corridor Walls,
for fire safety, means of egress and general safety.
TABLE 3412.6.5
CORRIDOR WALL VALUES
TABLE 3412.6.6(1)
VERTICAL OPENING PROTECTION VALUE
OCCUPANCY
CATEGORIES
a
b
c^
d^
A-1
-10
-4
2
A-2
-30
-12
2
A-3, F, M, R, S-1
-7
-3
2
A-4, B, E, S-2
-5
-2
5
a. Corridors not providing at least one-half the travel distance for all occupants
on a floor shall use Category b.
3412.6.5.1 Categories. The categories for Corridor
Walls are:
1. Category a — No fire partitions; incomplete fire
partitions; no doors; or doors not self-closing.
2. Category b — Less than l-hom fire-resistance rat-
ing or not constructed in accordance with Section
709.4.
3. Category c — 1-hour to less than 2-hour fire-resis-
tance rating, with doors conforming to Section
715 or without corridors as permitted by Section
1018.
4. Category d — 2-hour or gVQat&r fire-resistance rat-
ing, with doors conforming to Section 715.
3412.6*6 Vertical openings. Evaluate the fire-resistance
rating of exit enclosures, hoistways, escalator openings and
other shaft enclosures within the building, and openings
between two or more floors. Table 3412.6,6(1) contains the
appropriate protection values. Multiply that value by the
construction type factor found in Table 3412.6.6(2). Enter
the vertical opening value and its sign (positive or negative)
in Table 3412.7 under Safety Parameter 3412.6.6, Vertical
Openings, for fire safety, means of egress, and general
safety. If the structure is a one- story building or if all the
unenclosed vertical openings within the building conform
to the requirements of Section 708, enter a value of 2. The
maximum positive value for this requirement shall be 2.
3412.6.6.1 Vertical opening formula. The following
formula shall be used in computing vertical opening
value.
VO = PVx CF (Equation 34-4)
VO = Vertical opening value.
PV = Protection value [Table 34 1 2.6.6( 1 )] .
CF = Construction type factor [Table 34 1 2.6.6(2)] .
PROTECTION
VALUE
None (unprotected opening)
-2 times number floors connected
Less than 1 hour
-1 times number floors connected
1 to less than 2 hours
1
2 hours or more
2
TABLE 3412.6.6(2)
CONSTRUCTION-TYPE FACTOR
FACTOR
TYPE OF CONSTRUCTION
lA
IB
IIA
IIB
IIIA
IIIB
IV
VA
VB
1.2
1.5
2.2
3.5
2.5
3.5
2.3
3.3
7
3412.6.7 HVAC systems. Evaluate the ability of the HVAC
system to resist the movement of smoke and fire beyond the
point of origin. Under the categories in Section 3412.6.7.1,
determine the appropriate value and enter that value into
Table 3412.7 under Safety Parameter 3412.6.7, HVAC Sys-
tems, for fire safety, means of egress and general safety.
3412.6.7.1 Categories. The categories for HVAC sys-
tems are:
1 . Category a — Plenums not in accordance with Sec-
tion 602 of the California Mechanical Code. -10
points.
2. Category b — Air movement in egress elements not
in accordance v^ith Section 1018.5.-5 points.
3. Category c — Both categories a and b are applica-
ble. -15 points.
4. Category d — Compliance of the HVAC system
with Section 1018.5 and Section 602 of the Cali-
fornia Mechanical Code. points.
5. Category e — Systems serving one story; or a cen-
tral boiler/chiller system without ductwork con-
necting two or more stories. 5 points.
3412.6.8 Automatic fire detection. Evaluate the smoke
detection capability based on the location and operation of
automatic fire detectors in accordance with Section 907 and
the California Mechanical Code. Under the categories and
occupancies in Table 3412.6.8, determine the appropriate
value and enter that value into Table 3412.7 under Safety
Parameter 3412.6.8, Automatic Fire Detection, for fire
safety, means of egress and general safety.
TABLE 3412.6.8
AUTOMATIC FIRE DETECTION VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
A-1,A.3,F,
M, R, S-1
-10
-5
2
6
A-2
-25
-5
5
9
A-4, B, E, S-2
-4
-2
4
8
602
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3412.6.8.1 Categories. The categories for automatic fire
detection are:
1. Category a — None.
2. Category b — Existing smoke detectors in HVAC
systems and maintained in accordance with the
California Fire Code.
3. Category c — Smoke detectors in HVAC systems.
The detectors are installed in accordance with the
requirements for new buildings in the California
Mechanical Code,
4. Category d — Smoke detectors throughout all floor
areas other than individual sleeping units, tenant
spaces and dwelling units.
5. Category e — Smoke detectors installed through-
out the floor area.
3412.6.9 Fire alarm systems. Evaluate the capabihty of the
fire alarm system in accordance with Section 907. Under the
categories and occupancies in Table 3412.6.9, determine
the appropriate value and enter that value into Table 3412.7
under Safety Parameter 3412.6.9, Fire Alarm Systems, for
fire safety, means of egress and general safety.
TABLE 3412.6.9
FIRE ALARM SYSTEM VALUES
TABLE 3412.6.10
SMOKE CONTROL VALUES
OCCUPANCY
CATEGORIES
a
b«
c
d
A-1,A-2,A-3,A-4,B,E,R
-10
-5
5
F,M,S
5
10
15
a. For buildings equipped throughout with an automatic sprinkler system, add
2 points for activation by a sprinkler waterflow device.
3412.6.9.1 Categories. The categories for fire alarm sys-
tems are:
1. Category a — None.
2. Category b — Fire alarm system with manual fire
alarm boxes in accordance with Section 907.3 and
alarm notification appliances in accordance with
Section 907.5.2.
3 . Category c — Fire alarm system in accordance with
Section 907.
4. Category d — Category c plus a required emer-
gency voice/alarm communications system and a
fire command center that conforms to Section
403.4.5 and contains the emergency voice/alarm
communications system controls, fire department
communication system controls and any other
controls specified in Section 911 where those sys-
tems are provided.
3412.6.10 Smoke control. Evaluate the ability of a natural
or mechanical venting, exhaust or pressurization system to
control the movement of smoke from a fire. Under the cate-
gories and occupancies in Table 3412.6.10, determine the
appropriate value and enter that value into Table 3412.7
under Safety Parameter 3412.6.10, Smoke Control, for
means of egress and general safety.
OCCUPANCY
CATEGORIES
a
b
c
d
e
f
A-l,A-2,A-3
1
2
3
6
6
A-4,E
1
3
5
B,M,R
2a
3a
3^
3a
4a
F,S
2^
2a
3a
3a
3^
This value shall be if compliance with Category d or e in Section
3412.6.8.1 has not been obtained.
3412.6.10.1 Categories. The categories for smoke con-
trol are:
1. Category a — None.
2. Category b — The building is equipped throughout
with an automatic sprinkler system. Openings are
provided in exterior walls at the rate of 20 square
feet (1.86 m^) per 50 linear feet (15 240 mm) of
exterior wall in each story and distributed around
the building perimeter at intervals not exceeding
50 feet (15 240 mm). Such openings shall be
readily openable from the inside without a key or
separate tool and shall be provided with ready
access thereto. In lieu of operable openings,
clearly and permanently marked tempered glass
panels shall be used.
3. Category c — One enclosed exit stairway, with
ready access thereto, from each occupied floor of
the building. The stairway has operable exterior
windows and the building has openings in accor-
dance with Category b.
4. Category d — One smokeproof enclosure and the
building has openings in accordance with Cate-
gory b.
5. Category e — The building is equipped throughout
with an automatic sprinkler system. Each floor
area is provided with a mechanical air-handling
system designed to accomplish smoke contain-
ment. Return and exhaust air shall be moved
directly to the outside without recirculation to
other floor areas of the building under fire condi-
tions. The system shall exhaust not less than six air
changes per hour from the floor area. Supply air by
mechanical means to the floor area is not required.
Containment of smoke shall be considered as con-
fining smoke to the fire area involved without
migration to other floor areas. Any other tested and
approved design which will adequately accom-
plish smoke containment is permitted.
6. Category f — Each stairway shall be one of the fol-
lowing: a smokeproof enclosure in accordance
with Section 1022.9; pressurized in accordance
with Section 909.20.5 or shall have operable exte-
rior windows.
3412.6.11 Means of egress capacity and number. Evalu-
ate the means of egress capacity and the number of exits
available to the building occupants. In applying this section.
2010 CALIFORNIA BUILDING CODE
603
EXISTING STRUCTURES
the means of egress are required to conform to the following
sections of this code: 1003.7, 1004, 1005.1, 1014.2, 1014.3,
1015.2, 1021, 1025.1, 1027.2, 1027.6, 1028.2, 1028.3,
1028.4 and 1029 [except that the minimum width required
by this section shall be determined solely by the width for
the required capacity in accordance with Table
3412.6.1 1(1)]. The number of exits credited is the number
that is available to each occupant of the area being evalu-
ated. Existing fire escapes shall be accepted as a component
in the means of egress when conforming to Section 3406.
Under the categories and occupancies in Table
3412.6. 1 1(2), determine the appropriate value and enter that
value into Table 3412.7 under Safety Parameter 3412.6.1 1,
Means of Egress Capacity, for means of egress and general
safety.
3412.6.11.1 Categories. The categories for Means of
Egress Capacity and number of exits are:
1. Category a — Compliance with the minimum
required means of egress capacity or number of
exits is achieved through the use of a fire escape in
accordance with Section 3406.
2. Category b — Capacity of the means of egress com-
plies with Section 1004 and the number of exits
complies with the minimum number required by
Section 1021.
3. Category c — Capacity of the means of egress is
equal to or exceeds 125 percent of the required
means of egress capacity, the means of egress
complies with the minimum required width
dimensions specified in the code and the number
of exits complies with the minimum number
required by Section 1021.
4. Category d — The number of exits provided
exceeds the number of exits required by Section
1021. Exits shall be located a distance apart from
each other equal to not less than that specified in
Section 1015.2.
5. Category e — The area being evaluated meets both
Categories c and d.
TABLE 3412.6.11(2)
MEANS OF EGRESS VALUES
OCCUPANCY
CATEGORIES
a^
b
c
d
e
A-1,A-2,A-3,A-4,E
-10
2
8
10
B,F,S
-1
M
-3
1
2
4
R
-3
a. The values indicated are for buildings six stories or less in height. For build-
ings over six stories above grade plane, add an additional -10 points.
3412.6.12 Dead ends. In spaces required to be served by
more than one means of egress, evaluate the length of the
exit access travel path in which the building occupants are
confined to a single path of travel. Under the categories and
occupancies in Table 3412.6.12, determine the appropriate
value and enter that value into Table 3412.7 under Safety
Parameter 3412.6.12, Dead Ends, for means of egress and
general safety.
TABLE 3412.6.12
DEAD-END VALUES
OCCUPANCY
CATEGORIES^
a
b
c
A-1,A-3,A-4,B,E,F,M,R, S
-2
2
A-2,E
-2
2
a. For dead-end distances between categories, the dead-end value shall be
obtained by linear interpolation.
3412.6.12.1 Categories. The categories for dead ends are:
1. Category a — Dead end of 35 feet (10 670 mm) in
nonsprinklered buildings or 70 feet (21 340 mm)
in sprinklered buildings.
2. Category b— Dead end of 20 feet (6096 mm); or 50
feet (15 240 mm) in Group B in accordance with
Section 1018.4, exception 2.
3. Category c — No dead ends; or ratio of length to
width (1/w) is less than 2.5:1.
TABLE 3412.6.11(1)
EGRESS WIDTH PER OCCUPANT SERVED
OCCUPANCY
WITHOUT SPRINKLER SYSTEM
WITH SPRINKLER SYSTEM^
Stairways
(inches per occupant)
other egress components
(inches per occupant)
Stairways
(inches per occupant)
other egress components
(inches per occupant)
Occupancies other than those listed
below
0.3
0.2
0.2
0.15
Hazardous: H-1, H-2, H-3 and H-4
Not Permitted
Not Permitted
0.3
0.2
Institutional: 1-2
Not Permitted
Not Permitted
0.3
0.2
For SI: 1 inch = 25.4 mm.
a. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
604
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3412.6.13 Maximum exit access travel distance. Evaluate
the length of exit access travel to an approved exit. Deter-
mine the appropriate points in accordance with the follow-
ing equation and enter that value into Table 3412.7 under
Safety Parameter 3412.6.13, Maximum Exit Access Travel
Distance, for means of egress and general safety. The maxi-
mum allowable exit access travel distance shall be deter-
mined in accordance with Section 1016.1.
TABLE 3412.6.15
MEANS OF EGRESS EMERGENCY LIGHTING VALUES
Maximum allowable Maximum actual
Points = 20 X
travel distance
travel distance
Max. allowable travel distance
3412.6.14 Elevator control. Evaluate the passenger eleva-
tor equipment and controls that are available to the fire de-
partment to reach all occupied floors. Elevator recall
controls shall be provided in accordance with the California
Fire Code. Under the categories and occupancies in Table
3412.6.14, determine the appropriate value and enter that
value into Table 3412.7 under Safety Parameter 3412.6.14,
Elevator Control, for fire safety, means of egress and gen-
eral safety. The values shall be zero for a single-story build-
ing.
TABLE 3412,6.14
ELEVATOR CONTROL VALUES
ELEVATOR
TRAVEL
CATEGORIES
a
b
c
d
Less than 25 feet of travel
above or below the primary
level of elevator access for
emergency fire-fighting or
rescue personnel
-2
+2
Travel of 25 feet or more above
or below the primary level of
elevator access for emergency
fu-e-fighting or rescue
personnel
-4
NP
+4
For SI: 1 foot = 304.8 mm.
3412.6.14.1 Categories. The categories for elevator
controls are:
1 . Category a — No elevator.
2. Category b — Any elevator without Phase I and II
recall.
3. Category c — All elevators with Phase I and II
recall as required by the California Fire Code.
4. Category d — All meet Category c; or Category b
where permitted to be without recall; and at least
one elevator that complies with new construction
requirements serves all occupied floors.
3412.6.15 Means of egress emergency lighting. Evaluate
the presence of and reliability of means of egress emergency
lighting. Under the categories and occupancies in Table
3412.6.15, determine the appropriate value and enter that
value into Table 3412.7 under Safety Parameter 3412.6.15,
Means of Egress Emergency Lighting, for means of egress
and general safety.
NUMBER OF EXITS
REQUIRED BY
SECTION 1015
CATEGORIES
a
b
c
Two or more exits
NP
4
Minimum of one exit
1
1
3412.6.15.1 Categories. The categories for means of
egress emergency lighting are:
1. Category a — Means of egress lighting and exit
signs not provided with emergency power in
accordance with Chapter 27.
2. Category b — Means of egress lighting and exit
signs provided with emergency power in accor-
dance with Chapter 27.
3. Category c — Emergency power provided to
means of egress lighting and exit signs which pro-
vides protection in the event of power failure to the
site or building.
3412.6.16 Mixed occupancies. Where a building has two or
more occupancies that are not in the same occupancy classifi-
cation, the separation between the mixed occupancies shall
be evaluated in accordance with this section. Where there is
no separation between the mixed occupancies or the separa-
tion between mixed occupancies does not qualify for any of
the categories indicated in Section 3412.6.16.1, the building
shall be evaluated as indicated in Section 3412.6 and the
value for mixed occupancies shall be zero. Under the catego-
ries and occupancies in Table 3412.6.16, determine the
appropriate value and enter that value into Table 3412.7
under Safety Parameter 3412.6.16, Mixed Occupancies, for
fire safety and general safety. For buildings without mixed
occupancies, the value shall be zero.
TABLE 3412.6.16
MIXED OCCUPANCY VALUES^
OCCUPANCY
CATEGORIES
a
b
c
A-1,A-2,R
-10
10
A-3, A-4, B, E, F, M, S
-5
5
a. For fire-resistance ratings between categories, the value shall be obtained by
linear interpolation.
3412.6.16.1 Categories. The categories for mixed occu-
pancies are:
1 . Category a — Occupancies separated by minimum
1-hour fire barriers or minimum 1-hour horizontal
assemblies, or both.
2. Category b — Separations between occupancies in
accordance with Section 508.4.
3. Category c — Separations between occupancies
having a fire-resistance rating of not less than
twice that required by Section 508.3.3.
3412.6.17 Automatic sprinklers. Evaluate the ability to
suppress a fire based on the installation of an automatic
2010 CALIFORNIA BUILDING CODE
605
EXISTING STRUCTURES
sprinkler system in accordance with Section 903.3.1.1.
"Required sprinklers*' shall be based on the requirements of
this code. Under the categories and occupancies in Table
3412.6.17, determine the appropriate value and enter that
value into Table 3412.7 under Safety Parameter 3412.6.17,
Automatic Sprinklers, for fire safety, means of egress
divided by 2 and general safety.
TABLE 3412.6.17
SPRINKLER SYSTEM VALUES
OCCUPANCY
CATEGORIES
a
b
c
d
e
f
A-1,A-3,F,M,R, S-1
-6
-3
2
4
6
A-2
-4
-2
1
2
4
A-4, B, E, S-2
-12
-6
3
6
12
3412.6.17.1 Categories. The categories for automatic
sprinkler system protection are:
1. Category a — Sprinklers are required throughout;
sprinkler protection is not provided or the sprin-
kler system design is not adequate for the hazard
protected in accordance with Section 903.
2. Category b — Sprinklers are required in a portion
of the building; sprinkler protection is not pro-
vided or the sprinkler system design is not ade-
quate for the hazard protected in accordance with
Section 903.
3. Category c — Sprinklers are not required; none are
provided.
4. Category d — Sprinklers are required in a portion
of the building; sprinklers are provided in such
portion; the system is one which complied with the
code at the time of installation and is maintained
and supervised in accordance with Section 903.
5. Category e — Sprinklers are required throughout;
sprinklers are provided throughout in accordance
with Chapter 9.
6. Category f — Sprinklers are not required through-
out; sprinklers are provided throughout in accor-
dance with Chapter 9.
3412.6.18 Standpipes. Evaluate the ability to initiate attack
on a fire by making a supply of water available readily
through the installation of standpipes in accordance with
Section 905. Required standpipes shall be based on the
requirements of this code. Under the categories and occu-
pancies in Table 3412.6. 1 8, determine the appropriate value
and enter that value into Table 3412.7 under Safety Parame-
ter 3412.6.18, Standpipes, for fire safety, means of egress
and general safety.
3412.6.18.1 Standpipe. The categories for standpipe
systems are:
1. Category a — Standpipes are required; standpipe is
not provided or the standpipe system design is not
in compliance with Section 905.3.
2. Category b — Standpipes are not required; none are
provided.
3. Category c — Standpipes are required; standpipes
are provided in accordance with Section 905.
4. Category d — Standpipes are not required;
standpipes are provided in accordance with Sec-
tion 905.
3412.6.18
STANDPIPE SYSTEM VALUES
OCCUPANCY
CATEGORIES
a^
b
c
d
A-1,A-3,F,M,R,S-1
-6
4
6
A-2
-4
2
4
A-4, B, E, S-2
-12
6
12
a. This option cannot be taken if Category a orb in Section 3412,6. 17 is used.
3412.6.19 Incidental accessory occupancy. Evaluate
the protection of incidental accessory occupancies in
accordance with Section 508.2.5. Do not include those
where this code requires suppression throughout the
buildings, including covered mall buildings, high-rise
buildings, public garages and unlimited area buildings.
Assign the lowest score from Table 3412.6.19 for the
building or floor area being evaluated and enter that value
into Table 3412.7 under Safety Parameter 3412.6.19,
Incidental Accessory Occupancy, for fire safety, means of
egress and general safety. If there are no specific occu-
pancy areas in the building or floor area being evaluated,
the value shall be zero.
TABLE 3412.6.19
INCIDENTAL ACCESSORY OCCUPANCY AREA VALUES^
PROTECTION
REQUIRED BY
TABLE 508.2.5
PROTECTION PROVIDED
None
1
Hour
AFSS
AFSS
with
SP
1
Hour
and
AFSS
2
Hours
2
Hours
and
AFSS
2 Hours and AFSS
-4
-3
-2
-2
-1
-2
2 Hours, or 1 Hour
and AFSS
-3
-2
-1
-1
1 Hour and AFSS
-3
-2
-1
-1
-1
IHour
-1
-1
1 Hour, or AFSS
with SP
-1
-1
AFSS with SP
-1
-1
-1
-1
1 Hour or AFSS
-1
a. AFSS = Automatic fire suppression system; SP = Smoke partitions (See
Section 508.2.5).
Note: For Table 3412.7, see next page.
3412.7 Building score. After determining the appropriate data
from Section 3412.6, enter those data in Table 3412.7 and total
the building score.
606
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
TABLE 3412.7
SUMMARY SHEET— BUILDING CODE
Existing occupancy:
Year building was constructed: .
Type of construction:
Proposed occupancy: _
Number of stories: _
Area per floor:
. Height in feet:_
Percentage of open perimeter increase:
Completely suppressed: Yes _
Compartmentation: Yes _
_%
_No
_No
Corridor wall rating:
Required door closers:
Yes
.No
Fire-resistance rating of vertical opening enclosures:
Type of HVAC system:
Automatic fire detection: Yes
Fire alarm system: Yes
Smoke control: Yes
Adequate exit routes: Yes
_, serving number of floors:
.No.
.No_
.No_
No
Type and location: .
Type:
Type:
Dead ends: .
.Yes
No
Maximum exit access travel distance:
Means of egress emergency lighting: Yes
No
Elevator controls: Yes
Mixed occupancies: Yes
.No
No
SAFETY PARAMETERS
FIRE SAFETY (FS)
MEANS OF EGRESS (ME)
GENERAL SAFETY (GS)
3412.6.1 Building Height
3412.6.2 Building Area
34 12.6.3 Compartmentation
3412.6.4 Tenant and Dwelling Unit Separations
3412.6.5 Corridor Walls
3412.6.6 Vertical Openings
3412.6.7 HVAC Systems
3412.6.8 Automatic Fire Detection
3412.6.9 Fire Alarm Systems
3412.6.10 Smoke Control
3412.6.11 Means of Egress Capacity
3412.6.12 Dead Ends
* * * *
* * * *
* * * *
3412.6.13 Maximum Exit Access Travel Distance
3412.6. 14 Elevator Control
3412.6.15 Means of Egress Emergency Lighting
* * * *
3412.6.16 Mixed Occupancies
3412.6.17 Automatic Sprinklers
3412.6.18 Standpipes
3412.6.19 Incidental Accessory Occupancy
* * * *
-5-2=:
Building score — total value
* * * *No appUcable value to be inserted.
2010 CALIFORNIA BUILDING CODE
607
EXISTING STRUCTURES
3412.8 Safety scores. The values in Table 3412.8 are the
required mandatory safety scores for the evaluation process
listed in Section 3412.6.
TABLE 3412.8
MANDATORY SAFETY SCORES^
OCCUPANCY
FIRE
SAFETY
(MFS)
MEANS OF
EGRESS
(MME)
GENERAL
SAFETY
(MGS)
A-1
16
27
27
A-2
19
30
30
A-3
18
29
29
A-4,E
23
34
34
B
24
34
34
F
20
30
30
M
19
36
36
R
17
34
34
S-1
15
25
25
S-2
23
33
33
a. MFS = Mandatory Fire Safety;
MME = Mandatory Means of Egress;
MGS = Mandatory General Safety.
3412.9 Evaluation of building safety. The mandatory safety
score in Table 3412.8 shall be subtracted from the building score
in Table 3412.7 for each category. Where the final score for any
category equals zero or more, the building is in comphance with
the requirements of this section for that category. Where the final
score for any category is less than zero, the building is not in
compliance with the requirements of this section.
3412.9.1 Mixed occupancies. For mixed occupancies, the
following provisions shall apply:
1. Where the separation between mixed occupancies
does not qualify for any category indicated in Section
3412.6.16, the mandatory safety scores for the occu-
pancy with the lowest general safety score in Table
3412.8 shall be utilized (see Section 3412.6.)
Where the separation between mixed occupancies
qualifies for any category indicated in Section
3412.6. 16, the mandatory safety scores for each occu-
pancy shall be placed against the evaluation scores for
the appropriate occupancy.
SECTION 3413
EXISTING GROUP R-1 AND
GROUP R-2 OCCUPANCIES [SFM]
3413.1 Scope. The provisions of this section are intended to
maintain or increase the current degree of public safety, health
and general welfare in existing buildings classified as Group R
Occupancies.
341 3. U Application. In accordance with Health and
Safety Code Section 13143.2, the provisions of Sections
3413.2 through 3413.12 shall only apply to multiple-story
structures existing on January 1, 1975, let for human habi-
tation, including, and limited to, apartment houses, hotels,
and motels wherein rooms used for sleeping are let above
the ground floor
3413.2 Number of exits. Every apartment and every other
sleeping room shall have access to not less than two exits when
the occupant load is 10 or more (exits need not be directly from
the apartment or sleeping room). A fire escape as specified
herein may be used as one required exit.
Subject to approval of the authority having jurisdiction, a
ladder device as specified herein may be used in lieu of afire
escape when the construction feature or the location of the
building on the property cause the installation of afire escape
to be impractical.
3413.3 Stair construction. All stairs shall have a minimum run
of 9 inches (229 mm) and a maximum rise of 8 inches (203 mm)
and a minimum width exclusive of handrails of 30 inches (762
mm). Every stairway shall have at least one handrail A land-
ing having a minimum horizontal dimension of 30 inches (762
mm) shall be provided at each point of access to the stairway.
II
II
a. FS = Fire Safety
ME = Means of Egress
GS = General Safety
TABLE 3412.9
EVALUATION FORMULAS^
FORMULA
T.3410.7
T.3410.8
SCORE
PASS
FAIL
FS-MFS>0
(FS)
(MFS) =
ME-MME>0
(ME)
(MME) =
GS-MGS >
(GS)
(MGS) =
MFS = Mandatory Fire Safety
MME = Mandatory Means of Egress
MGS = Mandatory General Safety
608
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3413.4 Interior stairways. Every interior stairway shall be
enclosed with walls of not less than one -hour fire-resistive con-
struction. Where existing partitions form part of a stairwell
enclosure, wood lath and plaster in good condition will be
acceptable in lieu of one-hour fire-resistive construction.
Doors to such enclosures shall be protected by a self-closing
door equivalent to a solid wood door with a thickness of not
less than P/4 inches (44,5 mm).
Enclosures shall include all landings between flights and
any corridors, passageways or public rooms necessary for
continuous exit to the exterior of the buildings. The stairway
need not be enclosed in a continuous shaft if cut off at each
story by the fire -resistive construction required by this subsec-
tion for stairwell enclosures. Enclosures shall not be required if
an automatic sprinkler system is provided for all portions of the
building except bedrooms, apartments and rooms accessory
thereto. Interior stairs and vertical openings need not be
enclosed in two-story buildings.
3413.5 Exterior stairways. Exterior stairways shall be
noncombustible or of wood of not less than 2-inch (51 mm)
nominal thickness with solid treads and risers.
3413.6 Fire escapes y exit ladder devices. Fire escapes may be
used as one means of egress if the pitch does not exceed 60
degrees, the width is not less than 18 inches (457 mm), the
treads are not less than 4 inches (102mm) wide, and they extend
to the ground or are provided with counterbalanced stairs
reaching to the ground. Access shall be by an opening having a
minimum dimension of 29 inches (737 mm) when open. The sill
shall not be more than 30 inches (762 mm) above the floor and
landing.
A ladder device, when used in lieu ofaflre escape, shall con-
form to Section 3413.6.1 and the following:
Serves an occupant load of nine people or less or a single
dwelling unit or hotel room.
The building does not exceed three stories in height.
The access is adjacent to an opening as specified for emer-
gency egress or rescue or from a balcony.
The device does not pass in front of any building opening
below the unit being served.
The availability of activating the ladder device is accessible
only to the opening or balcony served.
The device as installed will not cause a person using it to be
within 12 feet (3658 mm) of exposed energized high-voltage
conductors.
3413,6,1 Exit ladder devices,
3413.6.1.1 Scope, This standard for exit ladder devices
is applicable where such devices are permitted by the
building official for installation on existing apartment
houses and hotels in conformance with the California
Building Code.
3413.6.1.2 Instructions, Installation shall be in accor-
dance with the manufacturer's instructions. Instructions
shall be illustrated and shall include directions and
information adequate for attaining proper and safe
installation of the product. Where exit ladder devices are
intended for mounting on difi^erent support surfaces, spe-
cific installation instructions shall be provided for each
surface.
3413.6.1.3 General design. All load-bearing surfaces
and supporting hardware shall be of noncombustible
materials. Exit ladder devices shall have a minimum
width of 12 inches (305 mm) when in the position
intended for use. The design load shall not be less than
400 pounds (17 SON) for 16-foot (4877 mm) length and
600 pounds (2699N)for 25-foot (7620 mm) length.
3413. 6.1.4 Performance,
3413.6.1.4.1 Exit ladder devices shall be capable of
withstanding an applied load of four times the design
load when installed in the manner intended for use.
Test loads shall be applied for a period of one hour
3413.6.1.4.2 Exit ladder devices of the retractable
type shall, in addition to the static load requirements
of Section 413. 6.1.4. 1 , be capable of withstanding the \ \
following tests:
1. Rung strength
2. Rung- to- side-rail shear strength
3. Release mechanism
4. Low temperature
3413.6.1.5 Rung-strength test. Rungs of retractable exit
ladder devices shall be capable of withstanding a load of
1,000 pounds (4448N) when applied to a 3^/2-inch-wide
(89mm) block resting at the center of the rung. The test
load shall be applied for a period of one hour The ladder
shall remain operational following this test.
3413.6.1.6 Rung-to-side-rail shear test. Rungs of
retractable exit ladder devices shall be capable of with-
standing 1,000 (4448N) when applied to a 3^/2-inch-wide
(89 mm) block resting on the center rung as near the side
rail as possible. The test load shall be applied for a
period of one hour Upon removal of the test load the fas-
teners attaching the rung to the side rail shall show no
evidence of failure. The ladder shall remain operational
following the test.
3413.6.1,7 Release mechanism test. The release mecha-
nism of retractable exit ladder devices shall operate with
an average applied force of not more than 5 pounds
(22.2N)for hand-operated releasing mechanisms and an
average applied force of not more than 25 pounds (11 IN)
for foot-pedal types of releasing mechanisms. For these
tests, a force gauge shall be applied to the release mecha-
nism, and the average of three consecutive readings shall
be computed.
3413,6,1,8 Low temperature operation test. Representa-
tive samples of the exit ladder devices shall be subjected
to a temperature of-40°C in an environmental chamber
for a period of 24 hours. The release mechanism shall be
operated immediately upon removal from the chamber
The ladder device shall function as intended without any
restriction of operation.
2010 CALIFORNIA BUILDING CODE
609
EXISTING STRUCTURES
3413.7 Doors and openings. Exit doors and openings shall
meet the requirements of Sections 1008.1.2, 1008.8.1.8,
1008.1.9 and 708.6. Doors shall not reduce the required width
of stairway more than 6 inches (152 mm) when open. Transoms
and openings other than doors from corridors to rooms shall be
fixed closed and shall be covered with a minimum of ^/4-inch
(19 mm) plywood or ^/j-inch (13 mm) gypsum wallboard or
equivalent material.
Exceptions:
1. Existing solid-bonded wood-core doors P/g inches
thick (34.9 mm), or their equivalent may be contin-
ued in use.
2. Where the existing frame will not accommodate a
door complying with Section 708.6, a
P/g-inch-thick (35 mm) solid-bonded wood-core
door may be used.
3413.8 Exit signs. Every exit doorway or change of direction of
a corridor shall be marked with a well-lighted exit sign having
letters at least 5 inches (127 mm) high.
3413.9 Enclosure of vertical openings. Elevators, shafts,
ducts and other vertical openings shall be enclosed as required
for stairways in Section 3413.5 or by wired glass set in metal
frames. Doors shall be noncombustible or as regulated in Sec-
tion 3413.5.
3413.10 Separation of occupancies. Occupancy separations
shall be provided as specified in Section 508. Lobbies and pub-
lic dining rooms, not including cocktail lounges, shall not
require a separation if the kitchen is so separated from the din-
ing room. Every room containing a boiler or central heating
plant shall be separated from the rest of the building by not less
than a one-hour fire-resistive occupancy separation.
Exception: A separation shall not be required for such
rooms with equipment serving only one dwelling unit.
3413.11 Equivalent protection. In lieu of the separation of
occupancies required by Section 3413.10, equivalent protec-
tion may be permitted when approved by the enforcement
agency.
Exception: The provisions of Sections 3413.3 through
3413.11 above shall not apply to any existing apartment
house, hotel or motel having floors (as measured from the
top of the floor surface) used for human occupancy located
more than 75 feet (22 860 mm) above the lowest floor level
having building access which is subject to the provisions of
Section 33414, California Building Code, relating to exist-
ing high-rise buildings.
Note: In accordance with Health and Safety Code Sec-
tion 17920.7, the provisions of Sections 3413.3 through
3413.11 above shall apply only to multiple-story struc-
tures existing on January 1, 1975, let for human habita-
tion including, and limited to, apartments, houses, hotels
and motels wherein rooms used for sleeping are let above
the ground floor
3413.12 Fire alarms,
3413,12,1 General, Every apartment house three or more
stories in height or containing more than 15 apartments,
every hotel three or more stories in height or containing 20
or more guest rooms, shall have installed therein an auto-
matic or manually operated fire alarm system. Such fire
alarm systems shall be so designed that all occupants of the
building may be warned simultaneously and shall be in
accordance with the California Fire Code. See Section
3414.14 for special requirements in buildings over 75 feet
(22 860 mm) in height.
Exception: Afire alarm system need not be installed pro-
vided such apartment house or hotel is separated by an
unpierced wall of not less than four-hour fire resistance
in buildings of Type lA, Type IIB, Type III or Type IV con-
struction and two-hour fire resistance in buildings of all
other types of construction provided:
1. Areas do not exceed the number of apartments or
guest rooms stipulated.
2. The fire-resistive wall conforms to the require-
ments of Section 706.6.
3. The wall complies with all other applicable provi-
sions of the California Building Code.
4. The wall extends to all outer edges of horizontal
projecting elements, such as balconies, roof over-
hangs, canopies, marquees or architectural pro-
jections.
5. No openings are permitted for air ducts or similar
penetrations, except that openings for pipes, con-
duits and electrical outlets of copper, sheet steel or
ferrous material shall be permitted through such
wall and need not be protected, provided they do
not unduly impair the required fire resistance of
the assembly.
6. Tolerances around such penetrations shall be
filled with approved noncombustible materials..
3413,12,2 Installation, The installation of all fire alarm
equipment shall be in accordance with the California Fire
Code.
3413,13 Existing Group R Occupancy high-rise buildings,
3413.13.1 General, Regardless of other provisions of these
regulations relating to existing high-rise buildings, require-
ments relative to existing Group R-1 or Group R-2 Occu-
pancies shall not be less restrictive than those established
pursuant to Health and Safety Code Section 13143.2.
3413.13.2 Corridor openings. Openings in corridor walls
and ceilings shall be protected by not less than P/4-inch
(44.5 mm) solid-bonded wood-core doors, ^/4-inch-thick (6
mm) wired glass conforming to Section 715.1, by approved
fire dampers or by equivalent protection in lieu of any of
these items. Transoms shall be fixed closed with material
having a fire-resistive rating equal to ^/2-inch (12,7 mm)
Type X gypsum wallboard or equivalent material installed
on both sides of the opening.
3413.13.3 Fire alarm systems. Notwithstanding the provi-
sions of Section 403, every existing high-rise building used
for the housing of a Group R-1 or Group R-2 Occupancies
shall have installed therein afire alarm system conforming
to this subsection.
610
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3413*13,3.1 General Every apartment house and every
hotel shall have installed therein an automatic or manu-
ally operated fire alarm system. Such fire alarm systems
shall he so designed that all occupants of the building
may be warned simultaneously.
3413.13.3.2 Installation. The installation of all fire
alarm equipment shall be in accordance with the Cali-
fornia Fire Code.
3413.13.3.3 Fire-extinguishing systems. Automatic
fire -extinguishing systems installed in any structure sub-
ject to these regulations shall have an approved flow
indicator electrically interconnected to the required fire
alarm system.
SECTION 3414
EXISTING HIGH-RISE BUILDINGS [SFM]
3414,1 Scope and definition. The provisions of Sections
3414,1 through 3414.27 shall apply to every existing high-rise
building of any type of construction or occupancy having floors
(as measured from the top of the floor surface) used for human
occupancy located more than 75 feet (22 860 mm) above the
lowest floor level having building access.
Exceptions:
1. Hospitals, as defined in Section 1250 of the Health
and Safety Code.
2. The following structures, while classified as high-rise
buildings, shall not be subject to the provisions of
I I Sections 3414.1 through 3414.27, but shall conform
to all applicable provisions of these regulations.
2. 1 Building used exclusively as open parking ga -
rages.
2.2 Buildings where all floors above the 75 foot
(22 860 mm) level are used exclusively as
open parking garages.
2.3 Floors of buildings used exclusively as open
parking garages and located above all other
floors used for human occupancy.
2.4 Buildings such as power plants, look-out tow-
ers, steeples, grain houses, and similar struc-
tures, when so determined by the enforcing
agency.
2.5 Buildings used exclusively for jails and pris-
ons.
For the purposes of this section, "building access*' shall
mean an exterior door opening conforming to all of the fol-
lowing:
1. Suitable and available for fire department use.
2. Located not more than 2 feet (610 mm) above the
adjacent ground level.
3. Leading to a space, room or area having foot traffic
communication capabilities with the remainder of the
building.
4. Designed to permit penetration through the use of fire
department forcible-entry tools and equipment unless
other approved arrangements have been made with
the fire authority having jurisdiction.
** Existing high-rise structure" means a high-rise struc-
ture, the construction of which is commenced or completed
prior to July 1, 1974.
For the purpose of this section, construction shall be
deemed to have commenced when plans and specifications
are more than 50 percent complete and have been presented
to the local jurisdiction prior to July 1, 1974. Actual con-
struction of such buildings shall commence on or before
January 1, 1976, unless all provisions for new buildings
have been met.
Note: it is the intent of this section that, in determining
the level form which the highest occupied floor is to be
measured, the enforcing agency should exercise reason-
able judgment, including consideration of overall acces-
sibility to the building by fire department personnel and
vehicular equipment When a building is situated on
sloping terrain and there is building access on more than
one level, the enforcing agency may select the level which
provides the most logical and adequate fire department
access.
3414.2 Compliance data. Except as may be otherwise speci-
fied, existing high-rise building shall conform to the applicable
requirements of these regulations by April 26, 1979.
Exception: The period of compliance may be extended upon
showing of good cause for such extension if a systematic and
progressive plan of correction is submitted to, and approved
by, the enforcing agency. Such extension shall not exceed
two years from the date of approval of such plan. Any plan of
correction submitted pursuant to this exception shall be
submitted and approved on or before April 26, 1979.
3414.3 Continued use. Existing high-rise building may have
their use continued if they conform, or are made to conform, to
the intent of the provisions of Sections 3414.5 through 3414.27
to provide for the safety of the occupants of the high-rise build-
ings and person involved in fire-suppression activities.
3414.4 Alternate protection. Alternate means of egress, fire
walls or fire barriers, smoke barriers, automatic fire detection
or fire-extinguishing systems, or other fire -protection devices,
equipment or installations may be approved by the enforcing
agency to provide reasonable and adequate life safety as
intended by Sections 3414.5 through 3414.27 for existing
high-rise buildings.
3414.5 Basic provisions. The provisions outlined in Sections
3414.1 through 3414.27 are applicable to every existing high-
rise building.
3414.6 Minimum construction. Existing wood lath and plas-
ter, existing ^/2-inch (12.7 mm) gypsum wallboard, existing
installations of ^/2-inch thick (12.7 mm) wired glass which are
or are rendered inoperative and fixed in a closed position, or
other existing materials having similar fire-resistive capabili-
ties shall be acceptable. All such assemblies shall be in good
repair, free of any condition which would diminish their origi-
nal fire-resistive characteristics.
II
II
2010 CALIFORNIA BUILDING CODE
611
EXISTING STRUCTURES
Where P/4-inch (44.5 mm) solid-bonded wood- core doors
are specified in these regulations for existing high-rise build-
ings, new or existing P/g-inch (34.9 mm) doors shall be accept-
able where existing framing will not accommodate a P/ 4-inch
(44.5 mm) door.
Note: It is the intent of this provisions that existing wood
frames may have their use continued.
3414.7 New construction. All new construction shall be com-
posed of materials and assemblies of materials conforming to
the fire-resistive provisions of these regulations. In no case
shall enclosure walls be required to be of more than one-hour
fire-resistive construction.
Exception: When approved by the enforcing agency, mate-
rials specified in Section 3414.6 may be used for new con-
struction when necessary to maintain continuity of design
and measurement of existing construction.
3414.8 Exits, Every floor from an existing high-rise building
shall have access to two separate means of egress, one of
which, when approved by the enforcing agency, may be an
existing exterior fire escape.
New installations of smoke-proof enclosures shall not be
required.
Note: In determining the adequacy of exits and their design,
Chapter 10 may be used as a guide. It is the intent of this sec-
tion that every existing high-rise building need not
mandatorily conform or be made to conform with the
requirements for new high-rise buildings. Reasonable judg-
ment in the application of requirements must be exercised by
the enforcing agency.
3414.9 Fire escapes. An existing fire escape in good structural
condition may be acceptable as one of the required means of
egress from each floor Access to such fire escapes may be by
any one of the following:
Through a room between the corridor and the fire escape if
the door to the room is operable from the corridor side without
the use of any key, special knowledge or effort.
By a door operable to afire escape from the interior without
the use of any key, special knowledge or effort.
By a window operable from the interior. Such window shall
have a minimum dimension of 29 inches (737 mm) when open.
The sill shall not be more than 30 inches (762 mm) above the
floor and landing.
3414.10 Protection of exterior openings. When an existing fire
escape is accepted as one of the require means of egress, open-
ings onto the fire escape landing and openings within 5 feet
(1524 mm) horizontally of the landings shall be protected in a
manner acceptable to the enforcing agency.
3414.11 Locking of stairway doors. When exit doors from cor-
ridors to exit stairways are locked to prohibit access from the
stairway side, the locking mechanisms shall be retracted to the
unlocked position upon failure of electrical power and a tele-
phone or other two-way communication system connected to
an approved emergency service that operates continuously
shall be provided at not less than every fifth floor in each
required stairway. In lieu thereof master keys which will
unlock all such doors from the stairway side shall be provided
in such numbers and locations as approved by the enforcing
agency.
3414.12 Enclosures, Interior vertical shafts, including but not
limited to, elevators, stairway and utility, shall be enclosed
with construction as set forth in Section 3414.6. | |
3414.13 Opening protection. Doors in other than elevators,
which shall be of a type acceptable to the enforcing agency,
shall be approved one-hour, fire-rated, tight-fitting orgasketed
doors or equivalent protection, and shall be of the normally
closed type, self-closing or a type which will close automati-
cally in accordance with Section 715.
Exception: In lieu of stairway enclosures, smoke barriers
may be provided in such a manner that fire and smoke will
not spread to other floors or otherwise impair exit facilities.
In these instances, smoke barriers shall not be less than
one-hour fire resistive with openings protected by not less
than approved one-third-hour, fire-rated, tight-fitting or
gasketed doors. Such doors shall be of the self-closing type
or of a type which will close automatically in the manner
specified in Section 715.
Doors crossing corridors shall be provided with
wired- glass vision panels set in approved steel frames.
Doors for elevators shall not be of the open-grille type.
3414.14 Fire alarm system. Every existing high-rise building
shall be provided with an approved fire alarm system. In
department stores, retail sales stores and similar occupancies
where the general public is admitted, such systems shall be of a
type capable of alerting staff and employees. In office buildings
and all other high-rise buildings, such systems shall be of a
type capable of alerting all occupants simultaneously.
Exceptions:
1. In areas of public assemblage, the type and location
of audible appliances shall be as determined by the
enforcing agency,
2. When acceptable to the enforcing agency, the occu-
pant voice notification system required by Section
3414.17 may be used in lieu of the fire alarm system
required by Section 3414.14.
3414.15 Existing systems. Existing fire systems, when accept-
able to the enforcing agency, shall be deemed as conforming to
the provisions of these regulations. For requirements for exist-
ing Group R-1 Occupancies, see Section 3412.13. I I
3414.16 Annunciation, When a new fire alarm system is
installed, it shall be connected to an annunciator panel
installed in a location approved by the enforcing agency.
For purposes of annunciation, zoning shall be in accordance
with Section 907.6.3. I I
3414.17 Monitoring, Shall be in accordance with Section
907.6.5. I I
3414.18 Systems interconnection. When an automatic fire
detection system or automatic extinguishing system is
installed, activation of such system shall cause the sounding of
the fire alarm notification appliances at locations designated
by the enforcing agency.
612
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3414.19 Manual fire alarm boxes, A manual fire alarm box
shall be provided in the locations designated by the enforcing
agency. Such locations shall be where boxes are readily acces-
sible and visible and in normal paths of daily travel by occu-
pants of the building.
3414.20 Emergency voice/alarm communication system. An
approved emergency voice/alarm system shall be provided in
every existing high-rise building which exceeds 150 feet (45
720 mm) in height measured in the manner set forth in Section
I I 3412.1. Such system shall provide communication from a loca-
tion available to and designated by the enforcing agency to not
less than all public areas.
The emergency voice/alarm system may be combined with a
fire alarm system provide the combined system has been
approved and listed by the State Fire Marshal. The sounding of
afire alarm signal in any given area or floor shall not prohibit
voice communication to other areas of floors. Combination
systems shall be designed to permit voice transmission to over-
ride the fire alarm signal, but the fire alarm signal shall not ter-
minate in less than three minutes.
3414.21 Fire department system. When it is determined by test
that portable fire department communication equipment is
ineffective^ a communication system acceptable to the enforcing
agency shall be installed within the building to permit emer-
gency communication between fire-suppression personnel
3414.22 Interior wall and ceiling finish. Interior wall and
ceiling finish of exitways shall conform to the provisions of
Chapter 8. Where the materials used in such finishes do not
conform to the provisions of Chapter 8, such finishes may be
surfaced with an approved fire -retardant coating.
3414.23 Ventilation, Natural or mechanical ventilation for the
removal of products of combustion shall be provided in every
story of an existing high-rise building. Such ventilation shall be
any one or combination of the following:
Panels or windows in the exterior wall which can be opened.
Such venting facilities shall be provided at the rate of at least 20
square feet (1 . 86 m^) of opening per 50 lineal feet (15 240 lineal
mm) of exterior wall in each story, distributed around the per-
imeter at not more than 50-foot (15 240 mm) intervals on at
least two sides of the building.
Approved fixed tempered glass may be used in lieu of
openable panels or windows. When only selected panels or
windows are of tempered glass, they shall be clearly identified
as required by the enforcing agency. Any other design which
will produce equivalent results.
3414.24 Smoke control systems. Existing air-circulation sys-
tems shall be provided with an override switch in a location
approved by the enforcing agency which will allow for the man-
ual control of shutdown of the systems.
Exception: Systems which serve only a single floor, or por-
tion thereof without any penetration by ducts or other
means into adjacent floors.
3414.25 Elevator recall smoke detection. Smoke detectors for
emergency operation of elevators shall be provided as required
by Section 3003.
3414.26 Exit signs and illumination. Exits and stairways shall
be provided with exit signs and illumination as required by Sec-
tions 1 011.1 and 1011.2.
3414.27 Automatic sprinkler system-Existing high-rise
buildings. Regardless of any other provisions of these regula-
tions , every existing high-rise building of Type Il-B, Type III-B
or Type V-B construction shall be provided with an approved
automatic sprinkler system conforming to NFPA 13.
SECTION 3415
EXISTING GROUP I OCCUPANCIES [SFM]
3415.1 General, Existing buildings housing existing protective
social-care homes or facilities established prior to March 4,
1972 may have their use continued if they conform, or are made
to conform, to the following provisions:
3415.2 Use of floors. The use of floor levels in buildings of Type
III, IV or V nonfire-rated construction may be as follows :
Nonambulatory—first floor only;
Ambulatory — not higher than the third-floor level, provided
walls and partitions are constructed of materials equal in
fireresistive quality to that of wood lath and plaster in good
repair and all walls are firestopped at each floor level,
3415.3 Enclosure of exits and vertical openings. Except for
two-story structures housing ambulatory guests, all interior
stairs shall be enclosed in accordance with Chapter 10. In lieu
of stairway enclosures, floor separations or smoke barriers
may be provided in such a manner that fire and smoke will not
spread rapidly to floors above or otherwise impair exit facili-
ties. In these instances, floor separations or smoke barriers
shall have afire resistance equal to not less than ^/2-inch (13
mm) gypsum wall board on each side of wood studs with open-
ings protected by not less than a P/ 4-inch (44.5 mm) solid
bonded wood-core door of the self-closing type. All other verti-
cal openings shall be enclosed in accordance with the provi-
sions of Section 3414.6 and 3414.13.
3415.4 Exit access. Each floor or portion thereof of buildings
used for the housing of existing protective social-care homes or
facilities shall have access to not less than two exits in such a
manner as to furnish egress from the building or structure in the
event of an emergency substantially equivalent to the provi-
sions of Chapter 10.
3415.5 Corridor openings. Openings from rooms to interior
corridors shall be protected by not less than P/4-inch (44.5
mm) solid-bonded wood-core doors. Transoms and other simi-
lar openings shall be sealed with materials equivalent to exist-
ing corridor wall construction.
II
2010 CALIFORNIA BUILDING CODE
613
EXISTING STRUCTURES
3415.6 Interior finishes. Interior wall and ceiling finishes
shall conform to the requirements for a Group R-1 Occupancy
as specified in Chapter 8.
3415. 7 Automatic fire sprinklers. Automatic sprinkler systems
shall be installed in existing protective social-care occupan-
I I cies in accordance with the provisions of Section 903.2.6.
3415.8 Fire alarm systems. Automatic fire alarm systems shall
be installed in existing protective social-care homes or facili-
ties in accordance with the provisions of Section 907.2.6.
Exception: When an approved automatic sprinkler system
I I conforming to Section 903.2.6 is installed, a separate fire
alarm system as specified in this section need not be pro-
vided.
SECTION 3416
EXISTING GROUP L OCCUPANCIES [SFM]
3416 Existing Group L Occupancies,
3416.1 Repairs general. Additions, alterations or repairs may
be made to any building or structure without requiring the
existing building or structure to comply with all the require-
ments of this code section, provided the addition, alteration, or
repair conforms to the requirements of this section.
3416.2 Unsafe condition. Additions, repairs or alterations
shall not he made to an existing building or structure that will
cause the existing building or structure to be in violation of any
of the provisions of this code, nor shall such additions or alter-
ations cause the existing building or structure to become
unsafe, or to be in violation of any of the provisions of this code.
An unsafe condition shall be deemed to have been created if an
addition or alteration will cause the existing building or struc-
ture to become structurally unsafe or overloaded; will not pro-
vide adequate egress in compliance with the provisions of this
code or will obstruct existing exits; will create a fire hazard;
will reduce required fire resistance or will otherwise create
conditions dangerous to human life.
3416.3 Changes in use or occupancy. Any buildings that have
alternations or additions, which involves a change in use or
occupancy, shall not exceed the height, number of stories and
area permitted for new buildings
3416.4 Buildings not in compliance with code. Additions or
alterations shall not be made to an existing building or struc-
ture when such existing building or structure is not in full com-
pliance with the provisions of this code except when such
addition or alteration will result in the existing building or
structure being no more hazardous, based on life safety, fire
safety and sanitation, than before such additions or alterations
are undertaken.
3416.5 Maintenance of structural and fire resistive integrity.
Alterations or repairs to an existing building or structure that
are nonstructural and do not adversely affect any structural
member of any part of the building or structure having required
fire resistance may be made with the same materials of which
the building or structure is constructed. The installation or
replacement of glass shall be as required for new installations.
3416.6 Continuation of existing use. Buildings in existence at
the time of the adoption of this code may have their existing use
or occupancy continued if such use or occupancy was legal at
the time of the adoption of this code, provided such continued
use is not dangerous to life.
3416.7 Maximum allowable quantities. Laboratory suites
approved prior to January I, 2008 shall not exceed the maxi-
mum allowable quantities listed in Tables 3416.1 and 3416.2,
SECTION 3417
EARTHQUAKE EVALUATION AND DESIGN FOR
RETROFIT OF EXISTING BUILDINGS
3417.1 Purpose,
3417.1.1 Existing state-owned structures. The provisions
of Sections 341 7 through 3423 establish minimum stan-
dards for earthquake evaluation and design for retrofit of
existing state -owned structures, including buildings owned
by the University of California and the California State Uni-
versity.
The provisions of Sections 341 7 through 3423 may be
adopted by a local jurisdiction for earthquake evaluation
and design for retrofit of existing buildings,
3417.1.2 Public school buildings. The provisions of Sec-
tions 3417 through 3423 establish minimum standards for
earthquake evaluation and design for the rehabilitation of
existing buildings for use as public school buildings under
the jurisdiction of the Division of the State Architect-Struc-
tural Safety (DSA-SS), refer to Section 1.9.2,1,
The provisions of Section 3417 through 3423 also estab-
lish minimum standards for earthquake evaluation and
design for rehabilitation of existing public buildings cur-
rently under the jurisdiction ofDSA-SS.
3417,1,2,1 Reference to other chapters. For public
schools, where reference within this chapter is made to
sections in Chapters 16, 17, 18, 19, 21 or 22, the provi-
sions in Chapters 16 A, 17 A, ISA, 19 A, 21 A and 22 A
respectively shall apply instead.
3417.1.3 Community college buildings. The provisions of
Sections 3417 through 3423 establish minimum standards
for earthquake evaluation and design for the rehabilitation
of existing buildings for use as community college buildings
under the jurisdiction of the Division of the State Archi-
tect-Structural Safety/Community Colleges (DSA-SS/CC),
refer to Section 1.9.2.2.
The provisions of Section 3417 through 3423 also estab-
lish minimum standards for earthquake evaluation and
design for rehabilitation of existing community college
buildings currently under the jurisdiction of DSA-SS/CC.
3417,1,3,1 Reference to other chapters. For community
colleges, where reference within this chapter is made to
sections in Chapters 17 or 18, the provisions in Chapters
17 A and 18A respectively shall apply instead.
3417.2 Scope, All modifications, structurally connected addi-
tions and/or repairs to existing structures or portions thereof
b
614
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
TABLE 3416.7(1)
EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS
PRESENTING A PHYSICAL HAZARD BASIC QUANTITIES PER LABORATORY SUITE"
When two units are given, values within parentheses are in cubic feet (cu. ft) or pounds (lb)
CONDITION
STORAGE
USE CLOSED SYSTEi^S
USE OPEN SYSTEMS
MATERIAL
CLASS
Solid
Pounds
(cu. ft)
Liquid
Gallons
(lb)
Gas
(cu. ft)
Solid
Pounds
(cu. ft)
Liquid
Gaiions
(lb)
Gas
(cu. ft)
Solid
Pounds
(cu.ft)
Liquid
Gallons
(lb)
Gas
(cu. ft)
1. 1 Combustible liquid
11
12<f
120
30
IIl-A
—
33(9
—
330
—
—
80
Ill-B
—
13,20(f-
—
13,200
—
—
3,300
—
L2 Combustible dust IbsJlOOO cu.ft.
1
1
1
1.3 Combustible fiber
(loose)
(baled)
(100)
(1,000)
—
—
(100)
(1,000)
—
—
(20)
(200)
—
—
1.4 Cryogenic, flammable or oxidizing
45
45
10
2.1 Explosives
12
{If
V.
fVj
%
(%)
—
3.1 Flammable solid
125'
25
25
3.2. Flammable gas
(gaseous)
(liquefied)
—
15'
75(f
—
15'
750'
—
—
—
3.3 Flammable liquid Combination
1-A, 1-B, I-C
I-A
3(f
30
10
1-B
—
6(f
—
—
60
—
—
15
—
I-C
—
90^
—
—
90
—
20
—
no'
—
120
—
30
—
4.1 Organic peroxide, unclassified
detonatable
]'
ii9
—
%
CU)
—
%
(%)
—
4.2 Organic peroxide
I
11
III
IV
V
5'
125^
500
N.L
{5f
(50f
(125)'
(500)
N.L
(1)
50
125
500
N.L
(1)
(50)
(125)
(500)
N.L
—
1
10
25
100
N.L
1
(10)
(25)
(100)
N.L
__
4.3 Oxidizer
4
3
2
1
Id"
25(f-
1,000^
(1)'
(10)'
(250)'
(LOOOf
—
2
50
1,000
(%)
(2)
(250)
(1,000)
—
%
2
50
200
eu)
(2)
(50)
(200)
—
4.4 Oxidizer.Gas
(gaseous)
(liquefied)
—
15'
1.500^
—
15'
1,500'
—
—
—
5.1 Pyrophoric
4^
(4)'
50"
1
(1)
10'
6.1 Unstable (reactive)
4
3
2
1
50"
125^
(If
(5f
(50f
(125f
Id"
5(f
250^
75(9-
1
50
125
(1)
(50)
(125)
2'
16'
250'
750'
1
10
25
(%)
(1)
(10)
(25)
7. 1 Water (reactive)
3
2
1
5'
5(f
125'
(5f
(50f
(125f
—
5
50
125
(5)
(50)
(125)'
-
1
10
25
(1)
(10)
(25)
—
/. A laboratory suite is a space up to 10,000 square feet (929 m^) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt
amounts of hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in
this table shall apply. Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh
through 10th floor and below the third basement floor level quantity shall be reduced to 50 percent of this table.
2. Quantities may be increased 100 percent when stored in approved exhausted gas cabinets, exhausted enclosures or fume hoods.
2010 CALIFORNIA BUILDING CODE
615
EXISTING STRUCTURES
TABLE 3416.7(2)
EXEMPT AMOUNTS OF HAZARDOUS MATERIALS, LIQUIDS AND CHEMICALS PRESENTING A HEALTH HAZARD MAXIMUM
QUANTITIES ER LABORATORY SUITE"
When two units are given, values within parentheses are in pounds (lbs.)
MATERIAL
STORAGE
USE CLOSED SYSTEMS
USE OPEN SYSTEMS
Solid lb
Liquid
Gallons (lb)
Gas cu. ft
Solid lb
Liquid
Gallons (lb)
Gas cu. ft
Solid lb
Liquid
Gallons (lb)
L Corrosives
5,000
500
650^
5,000
500
650
1000
100
2a. Highly toxics^
40
10
65
5
1
65
2
V.
2b. Toxics
500
50
65(P
500
50
650
5
V.
3. Irritants
5,000
500
650
5,000
500
650
1000
100
4. Sensitizers
5,000
500
650
5,000
500
650
1,000
100
5, Other health hazards
5,000
500
650
5,000
500
650
1,000
100
, A laboratory suite is a space up to 10,000 square feet (929 m^) bounded by not less than a one-hour fire-resistive occupancy separation within which the exempt
amounts of hazardous materials may be stored, dispensed, handled or used. Up through the third floor and down through the first basement floor, the quantity in
this table shall apply. Fourth, fifth and sixth floors and the second and third basement floor level quantity shall be reduced to 75 percent of this table. The seventh
through 10th floor and below the third basement floor level quantity shall be reduced to 50 percent of this table.
. Permitted only when stored or used in approved exhausted gas cabinets, exhausted enclosures or fume hoods. Quantities of high toxics in use in open systems need
not be reduced above the third floor or below the first basement floor level. Individual container size shall be limited to 2 pounds (0.91 kg) for solids and V^ gallon
(0.95 L) for liquids.
shall, at a minimum, be designed and constructed to resist the
effects of seismic ground motions as provided in this section.
The structural system shall be evaluated by a registered design
professional and, if not meeting or exceeding the minimum
seismic design performance requirements of this section, shall
be retrofitted in compliance with these requirements.
I I Exception: Those structures for which Section 3417.3
determines that assessment is not required, or for which
N Section 34 17 A determines that retrofit is not needed, then
only the requirements of Section 3417.11 apply.
3417 J Applicability.
3417,3,1 Existing state-owned buildings. For existing
state-owned structures including all buildings owned by the
University of California and the California State University,
I I the requirements of Section 341 7 apply whenever the struc-
ture is to be retrofitted, repaired or modified and any of the
following apply:
L Total construction cost, not including cost of furnish-
ings, fixtures and equipment, or normal maintenance,
for the building exceeds 25 percent of the construc-
tion cost for the replacement of the existing building.
The changes are cumulative for past modifications
to the building that occurred after adoption of the
1995 California Building Code and did not require
seismic retrofit,
2. There are changes in occupancy category.
3. The modification to the structural components
increases the seismic forces in or strength require-
ments of any structural component of the existing
structure by more than 10 percent cumulative since
the original construction, unless the component has
the capacity to resist the increased forces determined
I I in accordance with Section 3419. If the building's
seismic base shear capacity has been increased since
the original construction, the percent change in base
shear may be calculated relative to the increased
value.
4. Structural elements need repair where the damage
has reduced the lateral-load-resisting capacity of the
structural system by more than 10 percent.
5. Changes in live or dead load increase story shear by
more than 10 percent.
3417.3.2 Public school buildings. For public schools, the
provisions of Section 341 7 apply when required in accor-
dance with Sections 4-307 and 4- 309(c), Title 24, Part 1.
3417.3.3 Community college buildings. For community
colleges, the provisions of Section 3417 apply when
required in accordance with Sections 4-307 and 4 -309(c),
Title 24, Part 1.
3417.4 Evaluation required. If the criteria in Section 3417.3
apply to the project under consideration, the design profes-
sional of record shall provide an evaluation in accordance with
Section 3417 to determine the seismic performance of the
building in its current configuration and condition. If the struc-
ture's seismic performance as required by Section 3417.5 is
evaluated as satisfactory and the peer reviewer(s), when
Method B of Section 3421 is used, concur, then no structural
retrofit is required.
3417.5 Minimum seismic design performance levels for
structural and nonstructural components. Following the
notations ofASCE 41, the seismic requirements for design and
assessment are based upon a prescribed Earthquake Hazard
Level (BSE-1, BSE-2, BSE-R orBSE-C), a specified structural
performance level (S-1 through S-5) and a non-structural per-
formance level (N-A through N-E). The minimum seismic
performance criteria are given in Table 3417.5 according to
the Building Regulatory Authority and the Occupancy Cate-
gory as determined in Chapter 16 or by the regulatory author-
ity. The building shall be evaluated at both the Level 1 and
Level 2 performance levels, and the more restrictive require-
ments shall apply.
616
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
Exception: If the floor area of an addition is greater than
the larger of 50 per cent of the floor area of the original
building or 1,000 square feet (93 m^), then the Table 341 7.5
entries for BSE-R and BSE-C are replaced by BSE-1 and
BSE-2, respectively.
3417.6 Retrofit required. Where the evaluation indicates the
building does not meet the required performance objectives of
this section, the owner shall take appropriate steps to ensure
that the building's structural system is retrofitted in accor-
dance with the provisions of Section 3415. Appropriate steps
are either: 1) undertake the seismic retrofit as part of the addi-
tions, modifications and/or repairs of the structure; or 2) pro-
vide a plan, acceptable to the building official, to complete the
seismic retrofit in a timely manner. The relocation or moving of
an existing building is considered to be an alteration requiring
filing of the plans and specifications approved by the building
official.
3417.7 The additions, modification or repair to any existing
building are permitted to be prepared in accordance with the
requirements for a new building. Chapter 16, Part 2, Title 24,
C.C.R., 2007 edition, applied to the entire building.
3417.8 The requirements ofASCE 41 Chapter 9 are to apply to
the use of seismic isolation or passive energy systems for the
repair, modification or retrofit of an existing structure. When
seismic isolation or passive energy dissipation is used, the pro-
ject must have project peer review as prescribed in Section
3420.
3417.9 Any construction required by this chapter shall include
structural observation by the registered design professional
who is responsible for the structural design in accordance with
Section 3417.10.
3417.10 Where Method B of Section 3419 is used or is required
by Section 3415.8, the proposed method of building evaluation
and design procedures must be accepted by the building official
prior to the commencement of the work.
3417.11 Voluntary lateral-force-resisting system modifica-
tions. Where the exception of Section 3415.2 applies, modifica-
tions of existing structural components and additions of new
structural components that are initiated for the purpose of
improving the seismic performance of an existing structure and
that are not required by other portions of this chapter are per-
mitted under the requirements of Section 3417.12.
SECTION 3418
DEFINITIONS
3418.1. For the purposes of this chapter, certain terms are
defined as follows:
ADDITION means any work that increases the floor or roof
area or the volume of enclosed space of an existing building,
and is structurally attached to the existing building by connec-
tions that are required for transmitting vertical or horizontal
loads between the addition and the existing structure.
ALTERATION means any change within or to an existing
building, which does not increase and may decrease the floor
or roof area or the volume of enclosed space.
BSE-C RESPONSE ACCELERATION PARAMETERS are
the parameters (SXS and SKI) as determined either: accord-
ing to ASCE 41, Section 1.6.1.3 for a mean return period PR
equal to 975 years; or by a Site Specific Response Spectrum
developed according to ASCE 41, Section 1.6.2 for an Earth-
quake Hazard Level of 5-percent/50-years probability of
exceedance, equivalent to a mean return period of 97 5 years.
BSE-R RESPONSE ACCELERATION PARAMETERS are
the parameters (SXS and SXl) as determined either: accord-
ing to ASCE 41, Section 1.6.1.3 for a mean return period PR
TABLE 3417.5
SEISMIC PERFORMANCE REQUIREMENTS BY BUILDING REGULATORY AUTHORITY AND OCCUPANCY CATEGORY.
ALL BUILDINGS NOT REGULATED BY DSA ARE ASSIGNED AS "STATE-OWNED"
II
PERFORMANCE CRITERIA
Building Regulatory Authority
Occupancy Category
Level 1
Level 2
State-Owned
h II III
BSE-R, 5-5, N-D
BSE-C, S-5, N-E
State-Owned
IV
BSE-R, S-2, N-B
BSE-C, S-4, N-C
Division of the State Architect - Public schools
I
BSE-l S-3, N-C
BSE-2, S'5, N-E
Division of the State Architect - Public schools
II, III
BSE-1, S-2, N-C
BSE-2, S-4, N-D
Division of the State Architect - Public schools
IV
BSE-1, S-2, N-C
BSE-2, S-4, N-C
Division of the State Architect ~ Community college
/, //, ///
BSE-R, S-3, N-D
BSE-2, S-5, N-E
Division of the State Architect - Community college
IV
BSE-R, S-2, N-B
BSE-2, S-4, N-C
1. ASCE 41 provides acceptance criteria (e.g. m, rotation) for Immediate Occupancy (SI), Life Safety (S3), and Collapse Prevention (S5), and specifies that values
for S-2 and S-4 are to be determined by interpolation between the adjacent performance level values.
The required method of interpolation is as follows:
For level S-2, the acceptance value is '/^ of the sum of the tabulated value for Immediate Occupancy (lO level) and twice the tabulated value for the Life Safety
(LS level).
For level S-4, the acceptance value is one-half the sum of the value for the LS level and the value for the Collapse Prevention (CP) level.
For nonstructural components, N-A corresponds to the lO level, N-C to the LS level, and N-D to the Hazards Reduced (HR level).
For evaluation procedures, N-B shall be the same as for N-A. Where numerical values are used, the values for N-B are one half the sum of the appropriate 10 and
LS values. Where 10 or CP values are not given by ASCE 41, then the LS values are permitted to be substituted.
2. Buildings evaluated and retrofitted to meet the requirements for a new building, Chapter 16, Part 2, Title 24, in accordance with the exception in Section 3419.1,
are deemed to meet the seismic performance requirements of this section.
II
2010 CALIFORNIA BUILDING CODE
617
EXISTING STRUCTURES
equal to 225 years; or by a Site Specific Response Spectrum
developed according to ASCE 41, Section 1.6.2 for an Earth-
quake Hazard Level of 20-percent /50-years probability of
exceedance, equivalent to a mean return period of 225 years.
BUILDING OFFICIAL is that individual within the agency
or organization charged with responsibility for compliance
with the requirements of this code. For some agencies this per-
son is termed the "enforcement agent."
DESIGN is the procedure that includes both the evaluation
and retrofit design of an existing component, element or struc-
tural system, and design of a new component, element or struc-
tural system.
ENFORCEMENT AGENCY (Authority Having Jurisdiction
in ASCE 41) is the agency or organization charged with
responsibility for agency or organization compliance with the
requirements of this code.
METHOD A refers to the procedures prescribed in Section
3418.
METHOD B refers to the procedures allowed in Section 3419.
MODIFICATIONS, For this chapter, modification is taken to
include repairs to structures that have been damaged.
N-A, N-B, N'Cf N-D, N-E are seismic nonstructural compo-
nent performance measures as defined in ASCE 41. N-A corre-
sponds to the highest performance level, and N-D the lowest,
while N-E is not considered.
PEER REVIEW refers to the procedures contained in Section
3420.
REPAIR as used in this chapter means the design and con-
struction work undertaken to restore or enhance the structural
and nonstructural load-resisting system participating in the
lateral response and stability of a structure that has experi-
enced damage from earthquakes or other destructive events.
S-ly S'2, S'3,S-4, S-5, S'6 are seismic structural performance
measures as defined in ASCE 41. S-1 corresponds to the high-
est performance level, and S-5 the lowest, while S-6 is not con-
sidered.
SPECIFIC PROCEDURES are the procedures listed in Sec-
tion 3417.1.1.
STRUCTURAL REPAIRS are any changes affecting existing
or requiring new structural components primarily intended to
correct the effects of damage, deterioration or impending or
actual failure, regardless of cause.
SECTION 3419
SEISMIC CRITERIA SELECTION
FOR EXISTING BUILDINGS
3419,1 Basis for evaluation and design. This section deter-
mines what technical approach is to be used for the seismic
evaluation and design for existing buildings. For those build-
I I ings or portions of buildings for which Section 3417 requires
action, the procedures and limitations for the evaluation of
existing buildings and design of retrofit systems and/or repair
thereof shall be implemented in accordance with this section.
One of the following approaches must be used:
1. Method A of Section 3420;
2. Method B of Section 3421 ^ with independent review of
a peer reviewer as required in Section 3420; or
3. For state -owned buildings only, the use of one of the
specific procedures listed in Section 341 9.1.1. \
When Method B is chosen it must be approved by the
building official and, where applicable, by the peer
reviewer. All referenced standards in ASCE 41 shall be
replaced by referenced standards listed in Chapter 35 of this
code.
Exception: For buildings constructed to the require-
ments of California Building Code, 1998 or later edition
as adopted by the governing jurisdiction, that code is
permitted to be used in place of those specified in Section ■
3419.1. I
3419.1.1 Specific procedures. For state-owned buildings,
the following specific procedures taken from the Interna-
tional Existing Building Code (lEBC) Appendix A may be
used, without peer review, for their respective types of con-
struction to comply with the seismic performance require-
ments for Occupancy Catagory I, II or III buildings:
1. Seismic Strengthening Provisions for
Unreinforced Masonry Bearing Wall Buildings
(Chapter Al of the lEBC).
2. Prescriptive Provisions for Seismic Strengthening
of Cripple Walls and Sill Plate Anchorage of Light
Wood-Frame, Residental Buildings (Chapter A3
of the lEBC).
3. Earthquake Hazard Reduction in Existing Rein-
forced Concrete and Reinforced Masonry Wall
Buildings with Flexible Diaphragms (Chapter A2
ofthelEBC).
3419.1.2 When a design project is begun under Method B
the selection of the peer reviewer is subject to the approval
of the building official. Following approval by the peer
reviewer, the seismic criteria for the project and the planned
evaluation provisions must be approved by the building offi-
cial. The approved seismic criteria and evaluation provi-
sions shall apply. Upon approval of the building official
these are permitted to be modified.
3419.1.3 For state -owned and community college buildings,
where unreinforced masonry is not bearing, it may be used
only to resist applied lateral loads. Where unreinforced
masonry walls are part of the structure they must be
assessed for stability under the applicable nonstructural
evaluation procedure.
3419.1.4 Public schools. For public schools, unreinforced
masonry shall not be used to resist in-plane or out-of-plane
seismic forces or superimposed gravity loads.
3419.1.5 Public schools. For public schools of light-frame
construction, horizontal diaphragms and vertical shear
walls shall consist of either diagonal lumber sheathing or
structural panel sheathing. Braced horizontal diaphragms
may be acceptable when approved by DSA. Straight lumber
sheathing may be used in combination with diagonal or
structural panel sheathing as diaphragms or shear walls.
618
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
•i
Let'in bracing, plaster (stucco), hollow clay tile, gypsum
wallboard and particleboard sheathing shall not be
assumed to resist seismic forces,
3419,2 Existing conditions. The existing condition and prop-
erties of the entire structure must be determined and docu-
mented by thorough inspection of the structure and site, review
of all available related construction documents, review of
geotechnical and engineering geologic reports, and perfor-
mance of necessary testing and investigation. Where samples
from the existing structure are taken or in situ tests are per-
formed, they shall be selected and interpreted in a statistically
appropriate manner to ensure that the properties determined
and used in the evaluation or design are representative of the
conditions and structural circumstances likely to be encoun-
tered in the structure as a whole. Adjacent structures or site
features that may affect the retrofit design shall be identified.
The entire load path of the seismic-force-resisting system
shall be determined, documented and evaluated. The load path
includes all the horizontal and vertical elements participating
in the structural response: such as diaphragms, diaphragm
chords, diaphragm collectors, vertical elements such as walls
frames, braces; foundations and the connections between the
components and elements of the load path. Repaired or retrofit-
ted elements and the standards under which the work was con-
structed shall be identified.
Data collection in accordance with ASCE 41 Section 2.2
shall meet the following minimum levels:
L For state-owned buildings, the requirements shall be
met following the data collection requirements of ASCE
41, Section 2.2.
2. For public schools, the "Comprehensive" level as
defined in ASCE 41, Section 2.2.63.
3. For community college buildings constructed in confor-
mance with the Field Act, the ''Usual " level as defined in
ASCE 41, Section 2.2.6.2.
4. For community college buildings not constructed in con-
formance with the Field Act, the "Comprehensive'' level
as defined in ASCE 41, Section 2.2.6.3.
Qualified test data from the original construction may be
accepted, in part or in whole, by the enforcement agency to ful-
fill the data collection requirements.
Exceptions:
1. The number of samples for data collection may be
adjusted with approval of the enforcement agency
when it has been determined that adequate infor-
mation has been obtained or additional informa-
tion is required.
2. Welded steel moment frame connections of build-
ings that may have experienced potentially dam-
aging ground motions shall be inspected in
accordance with Chapters 3 and 4, FEMA 352,
Recommended Post Earthquake Evaluation and
Repair Criteria for Welded Moment-Frame Con-
struction for Seismic Applications (July 2000).
Where original building plans and specifications are not
available, "as-built " plans shall be prepared that depict the
existing vertical and lateral structural systems, exterior ele-
ments, foundations and nonstructural systems in sufficient
detail to complete the design.
Data collection shall be directed and observed by the
project structural engineer or design professional in charge
of the design.
3419.3 Site geology and soil characteristics. Soil profile shall
be assigned in accordance with the requirements of Chapter
18,
3419.4 Occupancy categories. For purposes of earth-
quake-resistant design, each structure shall be placed in one of
the occupancy categories in accordance with the requirements
of this code.
3419.5 Configuration requirements. Each structure shall be
designated structurally regular or irregular in accordance with
the requirements of ASCE 41, Sections 2.4. 1.1.1. to2.4. 1.1.4.
3419.6 General selection of the design method. The require-
ments of Method B (Section 3419) may be used for any existing
building.
3419 J Prescriptive selection of the design method. The
requirements of Method A (Section 3418) or the specific proce-
dures for applicable building types given in Section 3417.1.1
are permitted to be used except under the following conditions,
where the requirements of Method B (Section 3419) must be
used.
3419.7.1 When the building contains pre stressed or post-
tensioned structural components (beams, columns, walls or
slabs) or contains precast structural components (beams,
columns, walls or flooring systems).
3419. 7.2 When the building is classified as irregular in ver-
tical or horizontal plan by application of ASCE/SEI 7-05
Section 12.3 and/or ASCE 41, Sections 2.4.LL1 to
2.4.1.1.4, unless the irregularity is demonstrated not to
affect the seismic performance of the building.
Exception: If the retrofit design removes the configura-
tional attributes that caused the building to be classified
as irregular, then Section 3419.7.2 does not apply and \
Method A may be used.
3419. 7.3 For any building that is assigned to Occupancy
Category IV.
3419.7.4 For any building using undefined or hybrid struc-
tural systems.
3419.7.5 When seismic isolation or energy dissipation sys-
tems are used in the retrofit or repair, either as part of the
existing structure or as part of the modifications.
3419.7.6 When the height of the structure exceeds 240 feet
(73 152 mm).
3419.8 Strength requirements. All components of the lat-
eral-force-resisting system must have the strength to meet the
acceptance criteria prescribed in ASCE 41, Chapter 3, or as
prescribed in the applicable Appendix A chapter of the lEBC if
2010 CALIFORNIA BUILDING CODE
619
EXISTING STRUCTURES
I I a specific procedure in Section 3419.1.1 is used. Any compo-
nent not having this strength shall have its capacity increased
by modifying or supplementing its strength so that it exceeds
the demand, or the demand is reduced to less than the existing
strength by making other modifications to the structural sys-
tem.
Exception: A component's strength is permitted to be less
than that required by the specified seismic load combina-
tions if it can be demonstrated that the associated reduction
in seismic performance of the component or its removal due
to the failure does not result in a structural system that does
not comply with the required performance objectives ofSec-
I I tion 341 7. If this exception is taken for a component, then it
cannot be considered part of the primary lateral-load-
resisting system.
3419.9 Nonstructural component requirements. Where the
nonstructural performance levels required by Section 341 7,
Table 3417.5 are N-D or higher, mechanical, electrical and
plumbing components shall comply with the provisions of
ASCE 41, Chapter 11, Section 11.2.
Exception: Modifications to the procedures and criteria
may be made subject to approval by the building official,
and concurrence of the peer reviewer if applicable. All
reports and correspondance shall also be forwarded to the
building official.
3419.10 Structural observation, testing and inspection.
Structural, geotechnical and construction observation, testing
and inspection as used in this section shall mean meeting the
requirements of Chapter 1 7, with a minimum allowable level of
investigation corresponding to seismic design category (SDC)
D. At a minimum the project site will be visited by the responsi-
ble design professional to observe existing conditions and to
review the construction work for general compliance with
approved plans, specifications and applicable structural regu-
lations. Such visits shall occur at significant construction
stages and at the completion of the structural retrofit. Struc-
tural observation shall be provided for all structures. The plan
for testing and inspection shall be submitted to the building
official for review and approval with the application for permit.
Additional requirements: For public schools and commu-
nity colleges, construction material testing, inspection and
observation during construction shall also comply with
Section 4-333, Part 1, Title 24.
3419.10.1 The registered design professional, or their
designee, responsible for the structural design shall be
retained to perform structural observation and independ-
ently report to the owner of observations and findings as
they relate to adherence to the permitted plans and good
workmanship.
3419.10.2 At the conclusion of construction, the structural
observer shall submit to the enforcement agency and the
owner a final written statement that the required site visits
have been made, that the work, to the best of the structural
observers knowledge and belief, is or is not in general con-
formity to the approved plans and that the observed struc-
tural deficiencies have been resolved and/or listing those
that, to the best of the structural observers knowledge and
belief, have not been satisfactorily corrected.
3419.10.2.1 The requirement for structural observation
shall be noted and prominently displayed on the front
sheet of the approved plans and incorporated into the
general notes on the approved plans.
3419.10.2.2 Preconstruction meeting, A preconstruc-
tion meeting is mandatory for all projects which require
structural observation. The meeting shall include, but is
not limited to, the registered design professional, struc-
tural observer, general constructor, affected subcontrac-
tors, the project inspector and a representative of the
enforcement agency (designated alternates may attend if
approved by the structural observer). The structural
observer shall schedule and coordinate this meeting. The
purpose of the meeting is to identify and clarify all essen-
tial structural components and connections that affect
the lateral and vertical load systems and to review sched-
uling of the required observations for the project's struc-
tural system retrofit.
3419.11 Temporary actions. When compatible with the build-
ing use, and the time phasing for both use and the retrofit pro-
gram, temporary shoring or other structural support is
permitted to be considered. Temporary bracing, shoring and
prevention of falling hazards are permitted to be used to qualify
for Exception 1 in Section 3417.9 that allows inadequate capa-
bility in some existing components, as long as the required per-
formance levels given in Section 3415 can be provided by the
permanent structure. The consideration for such temporary
actions shall be noted in the design documents.
3419.12 Voluntary modifications to the lateral-force resisting
system. Where modifications of existing structural components
and additions of new structural components are initiated for
the purpose of improving the lateral-force resisting strength or
stiffness of an existing structure and they are not required by
other sections of this code, then they are permitted to be designed
to meet an approved seismic performance criteria provided that
an engineering analysis is submitted that follows:
1. The capacity of existing structural components required
to resist forces is not reduced, unless it can be demon-
strated that reduced capacity meets the requirements of y
Section 3419.8. W
2. The lateral loading to or strength requirement of existing
structural components is not increased beyond their
capacity.
3. New structural components are detailed and connected
to the existing structural components as required by this
code for new construction.
4. New or relocated nonstructural components are detailed
and connected to existing or new structural components
as required by this code for new construction.
5. A dangerous condition is not created.
3419,12,1 State-owned buildings. Voluntary modifications
to lateral-force-resisting systems conducted in accordance
620
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
with Appendix A of the lEBC and the referenced standards
of this code shall be permitted,
3419.12,1.1 Design documents. When Section 3419.12
is the basis for structural modifications, the approved
design documents must clearly state the scope of the seis-
mic modifications and the accepted criteria for the
design. The approved design documents must clearly
have the phrase ''The seismic requirements of Chapter
34 for existing buildings have not been checked to deter-
mine if these structural modifications meet CBC require-
ments: the modifications proposed are to a different
seismic performance standard that would be required in
Section 3419 if they were not voluntary as allowed in
Section 3419.12:'
3419.12.2 Public schools and community colleges. When
Section 3419.12 is the basis for structural modifications, the
approved design documents must clearly indicate the scope
of modifications and the acceptance criteria for the design.
SECTION 3420
METHOD A
3420.1 General. The retrofit design shall employ the Linear
Static or Linear Dynamic Procedures of ASCE 41, Section
3.3.1 or 3.3.2, and comply with the applicable general require-
ments of ASCE 41, Chapters 2 and 3. The earthquake hazard
level and performance level given specified in Section 3417.5
for the building's occupancy type shall be used. Structures
shall be designed for seismic forces coming from any horizon-
tal direction.
Exception: The ASCE 41 Simplified Rehabilitation Method
of Chapter 10 may be used if the Level 1 seismic perfor-
mance level is S-3 or lower, the building's structural system
is one of the primary building types described in ASCE 41,
Table 10-2, and ASCE 41, Table 10-1 permits it use for the
building height.
SECTION 3421
METHOD B
3421.1 The existing or retrofitted structure shall be demon-
strated to have the capability to sustain the deformation
response due to the specified earthquake ground motions and
meet the seismic performance requirements of Section 3417.
The registered design professional shall provide an evaluation
of the response of the existing structure in its modified configu-
ration and condition to the ground motions specified. If the
building's seismic performance is evaluated as satisfactory
and the peer reviewer(s,) and the enforcement agency concurs,
then no further structural modifications of the lat-
eral-load-resisting system are required.
When the evaluation indicates the building does not meet the
required performance levels given in Table 3417.5 for the
occupancy type, then a retrofit and/or repair design shall be
prepared that provides a structure that meets these perfor-
mance objectives and reflects the appropriate consideration of
existing conditions. Any approach to analysis and design is
permitted to be used, provided that the approach shall be ratio-
nal, shall be consistent with the established principals of
mechanics and shall use the known performance characteris-
tics of materials and assemblages under reversing loads typi-
cal of severe earthquake ground motions.
Exception: Further consideration of the structure 's seismic
performance may be waived by the enforcement agency if
both the registered design professional and peer reviewer(s)
conclude that the structural system can be expected to per-
form at least as well as required by the provisions of this sec-
tion without completing an analysis of the structure's
compliance with these requirements. A detailed report shall
be submitted to the responsible building official that pres-
ents the reasons and basis for this conclusion. This report
shall be prepared by the registered design professional. The
peer reviewer(s) shall concur in this conclusion and affirm
to it in writing. The building official shall either approve this
decision or require completion of the indicated work speci-
fied in this section prior to approval.
3421.2 The approach, models, analysis procedures, assump-
tions on material and system behavior and conclusions shall be
peer reviewed in accordance with the requirements of Section
3420 and accepted by the peer reviewer(s).
Exceptions:
1. The enforcement agency may perform the work of
peer review when qualified staff is available within
the jurisdiction,
2. The enforcement agency may modify or waive the
requirements for peer review when appropriate.
3421.2.1 The approach used in the development of the
design shall be acceptable to the peer reviewer and the
enforcement agency and shall be the same method as used in
the evaluation of the building. Approaches that are specifi-
cally tailored to the type of building, construction materials
and specific building characteristics may be used, if they are
acceptable to the independent peer reviewer. The use of
Method A allowed procedures may also be used under
Method B.
3421.2.2 Any method of analysis may be used, subject to
acceptance by the peer reviewer(s) and the building official.
The general requirements given in ASCE 41, Chapter 2,
shall be complied with unless exceptions are accepted by the
peer reviewer(s) and building official. Use of other than
ASCE 41 procedures in Method B requires building official
concurrence before implementation.
3421.2.3 Prior to implementation, the procedures, methods,
material assumptions and acceptance/rejection criteria
proposed by the registered design professional will be peer
reviewed as provided in Section 3422. Where nonlinear pro-
cedures are used, prior to any analysis, the representation
of the seismic ground motion shall be reviewed and
approved by the peer review er(s) and the building official
3421.2.4 The conclusions and design decisions shall be
reviewed and accepted by the peer reviewer(s) and the
building official.
2010 CALIFORNIA BUILDING CODE
621
EXISTING STRUCTURES
SECTION 3422
PEER REVIEW REQUIREMENTS
3422.1 General. Independent peer review is an objective, tech-
nical review by knowledgeable reviewer(s) experienced in the
structural design, analysis and performance issues involved.
The reviewer(s) shall examine the available information on the
condition of the building, the basic engineering concepts
employed and the recommendations for action,
3422.2 Timing of independent review. The independent
reviewer(s) shall be selected prior to initiation of substantial
portions of the design and/or analysis work that is to be
reviewed, and review shall start as soon as practical after
Method B is adopted and sufficient information defining the
project is available,
3422.3 Qualifications and terms of employment. The
reviewer(s) shall be independent from the design and construc-
tion team,
3422.3.1 The reviewer(s) shall have no other involvement in
the project before, during or after the review, except in a
review capacity.
3422.3.2 The reviewer(s) shall be selected and paid by the
owner and shall have technical expertise in the evaluation
and retrofit of buildings similar to the one being reviewed,
as determined by the enforcement agency.
3422.3.3 The reviewer (or in the case of review teams, the
chair) shall be a California-licensed structural engineer
who is familiar with the technical issues and regulations
governing the work to be reviewed.
Exception: Other individuals with acceptable qualifica-
tions and experience may be a peer reviewer(s) with the
approval of the building official,
3422.3.4 The reviewer shall serve through completion of the
project and shall not be terminated except for failure toper-
form the duties specified herein. Such termination shall be
in writing with copies to the enforcement agency, owner and
the registered design professional When a reviewer is ter-
minated or resigns, a qualified replacement shall be
appointed within 10 working days, and the reviewer shall
submit copies of all reports, notes and correspondence to
the responsible building official, the owner and the regis-
tered design professional within 10 working days of such
termination.
3422.3.5 The peer reviewer shall have access in a timely
manner to all documents, materials and information
deemed necessary by the peer reviewer to complete the peer
review,
3422.4 Scope of review. Review activities shall include, where
appropriate, available construction documents, design crite-
ria and representative observations of the condition of the
structure, all inspection and testing reports, including methods
of sampling, analytical models and analyses prepared by the
registered design professional and consultants, and the retrofit
or repair design. Review shall include consideration of the pro-
posed design approach, methods, materials, details and
constructability.
Changes observed during construction that affect the seis-
mic-resisting system shall be reported to the reviewer in writing
for review and recommendation.
3422.5 Reports. The reviewer(s) shall prepare a written report
to the owner and building official that covers all aspects of the
review performed, including conclusions reached by the
reviewer(s). Reports shall be issued after the schematic phase,
during design development, and at the completion of construc-
tion documents but prior to submittal of the project plans to the
enforcement agency for plan review. When acceptable to the
building official, the requirement for a report during a specific
phase of the project development may be waived.
Such reports should include, at the minimum, statements of
the following:
1. Scope of engineering design peer review with limitations
defined.
2. The status of the project documents at each review stage.
3. Ability of selected materials and framing systems to meet
performance criteria with given loads and configura-
tion.
4. Degree of structural system redundancy and the defor-
mation compatibility among structural and
nonstructural components.
5. Basic constructibiiity of the retrofit or repair system.
6. Other recommendations that would be appropriate to
the specific project.
7. Presentation of the conclusions of the reviewer identify-
ing any areas that need further review, investigation
and/or clarification.
8. Recommendations.
The last report prepared prior to submittal of permit doc-
uments to the enforcement agency shall include a statement
indicating that the design is in conformance with the
approved evaluation and design criteria
3422.6 Response and resolutions. The registered design pro-
fessional shall review the report from the reviewer(s) and shall
develop corrective actions and responses as appropriate.
Changes observed during construction that affect the seis-
mic-resisting system shall be reported to the reviewer in writing
for review and recommendations. All reports, responses and
resolutions prepared pursuant to this section shall be submit-
ted to the responsible enforcement agency and the owner along
with other plans, specifications and calculations required. If
the reviewer resigns or is terminated prior to completion of the
project, then the reviewer shall submit copies of all reports,
notes and correspondence to the responsible building official,
the owner and the registered design professional within 10
working days of such termination.
622
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3422. 7 Resolution of conflicts. When the conclusions and rec-
ommendations of the peer reviewer conflict with the registered
design professional's proposed design^ the enforcement
agency shall make the final determination of the requirement
for the design.
SECTION 3423
ADDITIONAL REQUIREMENTS FOR PUBLIC
SCHOOLS AND COMMUNITY COLLEGES
The requirements of Section 3423 apply only to public schools
under the jurisdiction of the Division of the State Archi-
tect-Structural Safety (DSA-SS, refer to Section 1.9.2.1) and
community colleges under the jurisdiction of the Division of the
State Architect-Structural Safety/Community Colleges
(DSA-SS/CC). Refer to Section 1.9.2.2.
3423 J Evaluation and design criteria report. During the
schematic phase of the project, the owner or the registered
design professional in charge of the design shall prepare and
sign an Evaluation and Design Criteria Report in accordance
with Part 1, Title 24, C. C. R., Section 4-307(a). The report shall
be submitted to the DSAfor review and approval prior to pro-
ceeding with design development of the rehabilitation.
The Evaluation and Design Criteria Report shall:
1. Identify the building(s) structural and nonstructural
systems, potential deficiencies in the elements or sys-
tems and the proposed method for retrofit.
2. Identify geological and site -related hazards.
3. Propose the methodology for evaluation and retrofit
design.
4. Propose the complete program for data collection
I I (Section 3418.2).
5. Include existing or ''as-built" building plans, reports
and associated documents of the existing construc-
tion.
3423,2 Rehabilitation involving only portions of structures.
Where onlyaportion(s) of a structure is to be rehabilitated, the
public school or community college portion of the structure
shall:
1. Be seismically separated from the unrehabilitated por-
tion in accordance with Chapter 16 of Part 2, Title 24, or
the entire structure shall be rehabilitated in accordance
with this Section. For structures in which the
unrehabilitated portion is above or below the school or
community college portion, the entire structure shall be
rehabilitated in accordance with this division.
2. Be retrofitted as necessary to protect the occupants from
falling hazards of the unrehabilitated portion of the
building, and;
3. Be retrofitted as necessary to protect required exitways
being blocked by collapse or falling hazards of the
unrehabilitated portion.
201 CALIFORNIA BUILDING CODE 623
624 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 344 - EXISTING STRUCTURES
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
625
626 201 CALIFORNIA BUILDING CODE
CHAPTER 34A
EXISTING STRUCTURES
SECTION 34014
GENERAL
340L4. 1 Scope. The provisions of this chapter shall control the
alteration, repair, addition and change of occupancy of existing
stxuctmQS for applications listed in Sections 1.1 O.I (OSHPD 1)
and 1.10 A {OSHPD 4) regulated by the Office of Statewide
Health Planning and Development (OSHPD).
These applications include hospitals, skilled nursing facili-
ties, intermediate care facilities and correctional treatment
centers.
Exception: [OSHPD 2] Single -story Type V skilled nursing
or intermediate care facilities utilizing wood-frame or
light'Steel-frame construction as defined in Health and
Safety Code Section 129725, which shall comply with
Chapter 34 and any applicable amendments therein.
[DSA'AC] For applications listed in Section 1.9.1 regu-
lated by the Division of the State Architect- Access Compli-
ance for accessibility requirements, see Chapter IIB,
Section 1134B.
3401A.2 Maintenance. Buildings and structures, and parts
thereof, shall be maintained in a safe and sanitary condition.
Devices or safeguards vv^hich are required by this code shall be
maintained in conformance with the code edition under which
installed. The owner or the owner's designated agent shall be
responsible for the maintenance of buildings and structures. To
determine compliance with this subsection, the building offi-
cial shall have the authority to require a building or structure to
be reinspected. The requirements of this chapter shall not pro-
vide the basis for removal or abrogation of fire protection and
safety systems and devices in existing structures.
340 L4. 3 Compliance. Alterations, repairs, additions and
changes of occupancy to existing structures shall comply with
the provisions for alterations, repairs, additions and changes of
occupancy in the California Fire Code, California Mechanical
Code, California Plumbing Code and California Electrical
Code.
340 lA. 4 Building materials. Building materials shall comply
with the requirements of this section.
340L4.4.1 Existing materials. Materials already in use in a
building in compliance with requirements or approvals in
effect at the time of their erection or installation shall be per-
mitted to remain in use unless determined by the building
code official to be dangerous to life, health or safety. Where
such conditions are determined to be dangerous to life,
health or safety, they shall be mitigated or made safe.
340L4.4.2 New and replacement materials. Except as
otherwise required or permitted by this code, materials per-
mitted by the applicable code for new construction shall be
used. Like materials shall be permitted for repairs and alter-
ations, provided no hazard to life, health or property is cre-
ated. Hazardous materials shall not be used where the code
for new construction would not permit their use in buildings
of similar occupancy, purpose and location.
SECTION 34024
DEFINITIONS
3402A. 1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in the code,
have the meanings shown herein. Definitions provided in Sec-
tion 1613A.2, ASCE 7 Section 11.2 and ASCE 41 shall apply
when appropriate in addition to terms defined in this section:
ASSOCIATED STRUCTURAL ALTERATIONS means any
change affecting existing structural elements or requiring new
structural elements for vertical or lateral support of an other-
wise nonstructural alteration.
DANGEROUS. Any building or structure or portion thereof
that meets any of the conditions described below shall be
deemed dangerous:
1. The building or structure has collapsed, partially col-
lapsed, moved off its foundation or lacks the support of
ground necessary to support it.
2 . There exists a significant risk of collapse, detachment or dis-
lodgment of any portion, member, appurtenance or orna-
mentation of the building or structure under service loads.
EXISTING STRUCTURE. A structure erected prior to the
date of adoption of the appropriate code, or one for which a
legal building permit has been issued.
GENERAL ACUTE CARE HOSPITAL as used in this chap-
ter means a hospital building as defined in Section 129725 of
the Health and Safety Code and that is also licensed pursuant
to Subdivision (a) of Section 1250 of the Health and Safety
Code, but does not include these buildings if the beds licensed
pursuant to subdivision (a) of Section 1250 of the Health and
Safety Code, comprise 10 percent or less of the total licensed
beds of the total physical plant, and does not include facilities
owned or operated, or both, by the Department of Corrections.
It also precludes hospital buildings that may be licensed under
the above mentioned code sections, but provide skilled nursing,
intermediate care or acute psychiatric services only.
INCIDENTAL STRUCTURAL ALTERATIONS, ADDI-
TIONS OR REPAIRS are alterations, additions or repairs
which would not reduce the story lateral shear force-resisting
capacity by more than 5 percent or increase the story shear by
more than 5 percent in any existing story.
MAJOR STRUCTURAL ALTERATIONS, ADDITIONS OR
REPAIRS are those alterations, or additions or repairs of
greater extent than minor structural alterations or additions.
MINOR STRUCTURAL ALTERATIONS, ADDITIONS OR
REPAIRS are alterations, additions or repairs of greater
extent than incidental structural additions or alterations which
would not reduce the story shear lateral-force-resisting
II
2010 CALIFORNIA BUILDING CODE
627
EXISTING STRUCTURES
capacity by more than 10 percent or increase base shear by
more than 10 percent.
NONSTRUCTURAL ALTERATION is any alteration which
neither affects existing structural elements nor requires new
structural elements for vertical or lateral support and which
does not increase the lateral shear force in any story by more
than 5 percent.
NPC h NPC 2, NFC 3/NPC 3R, NPC 4 and NPC 5 are the
building nonstructural performance categories for Hospital
Buildings defined in Table 11.1 of California Administrative
Code (Part h Title 24 CCR), Chapter 6.
PEER REVIEW refers to procedure contained in Section
3414A,
PRIMARY FUNCTION. A primary function is a major activ-
ity for which the facility is intended. Areas that contain a pri-
mary function include, but are not limited to, the customer
service lobby of a bank, the dining area of a cafeteria, the meet-
ing rooms in a conference center, as well as offices and other
work areas in which the activities of the public accommodation
or other private entity using the facility are carried out. Mechani-
cal rooms, boiler rooms, supply storage rooms, employee
lounges or locker rooms, janitorial closets, entrances, corridors
and restrooms are not areas containing Si primary function.
I I REPAIR as used in this chapter means all the design and con-
struction work affecting existing or requiring new structural
elements undertaken to restore or enhance the structural and
nonstructural load resisting system participating in vertical or
lateral response of a structure primarily intended to correct the
effects of deterioration or impending or actual failure, regard-
less of cause.
SPCly SPC2, SPC3, SPC4andSPC5 are the building struc-
tural performance categories for Hospital Buildings defined in
Table 2.5.3 of California Administrative Code (Part 1, Title 24
CCR), Chapter 6.
SUBSTANTIAL STRUCTURAL DAMAGE. A condition
where:
1. In any story, the vertical elements of the lateral
force-resisting system have suffered damage such that
the lateral load-carrying capacity of the structure in any
horizontal direction has been reduced by more than 10
percent from its predamage condition; or
2. The capacity of any vertical gravity load-carrying com-
ponent, or any group of such components, that supports
more than 30 percent of the total area of the structure's
floor(s) and roof(s) has been reduced more than 10 per-
cent from its predamage condition and the remaining
capacity of such affected elements, with respect to all
dead and live loads, is less than 75 percent of that
required by this code for new buildings of similar struc-
ture, purpose and location.
TECHNICALLY INFEASIBLE. An alteration of a building
or a facility that has little likelihood of being accomplished
because the existing structural conditions require the removal
or alteration of a load-bearing member that is an essential part
of the structural frame, or because other existing physical or
site constraints prohibit modification or addition of elements.
spaces or features which are in full and strict compliance with
the minimum requirements for new construction and which are
necessary to provide accessibihty.
VOLUNTARY STRUCTURAL ALTERATION is any alter-
ation of existing structural element or provision of new struc-
tural elements which is not necessary for vertical or lateral
support of other work and is initiated by the applicant primar-
ily for the purpose of increasing the vertical or lateral
load-carrying strength or stiffness of an existing building.
SECTION 3403A
ADDITIONS
3403A.1 General. Additions to any building or structure shall
comply with the requirements of this code for new construc-
tion. Alterations to the existing building or structure shall be
made to ensure that the existing building or structure together
with the addition are no less conforming with the provisions of
this code than the existing building or structure was prior to the
addition. An existing building together with its additions shall
comply with the height and area provisions of Chapter 5.
3403A.2 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 1612A.3, any addi-
tion that constitutes substantial improvement of the existing
structure, as defined in Section 1612A.2, shall comply with the
flood design requirements for new construction, and all aspects
of the existing structure shall be brought into compliance with
the requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 1612A.3, any additions that do not constitute
substantial improvement or substantial damage of the existing
structure, as defined in Section 1612A.2, are not required to
comply with the flood design requirements for new construc-
tion.
3403A.3 Existing structural elements carrying gravity
load. Any existing gravity load-carrying structural element for
which an addition and its related alterations cause an increase
in design gravity load of more than 5 percent shall be strength-
ened, supplemented, replaced or otherwise altered as needed to
carry the increased load required by this code for new struc-
tures. Any existing gravity load-carrying structural element
whose gravity load-carrying capacity is decreased shall be con-
sidered an altered element subject to the requirements of Sec-
tion 3404 A. 3. Any existing element that will form part of the
lateral load path for any part of the addition shall be considered
an existing lateral load-carrying structural element subject to
the requirements of Section 3403A.4.
3403A.3.1 Design live load. Where the addition does not
result in increased design live load, existing gravity
load-carrying structural elements shall be permitted to be
evaluated and designed for live loads approved prior to the
addition. If the approved live load is less than that required
by Section 1607 A, the area designed for the nonconforming
live load shall be posted with placards of approved design
indicating the approved live load. Where the addition does
result in increased design live load, the live load required by
Section 1607 A shall be used.
II
628
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
3403A.4 Existing structural elements carrying lateral load.
Where the addition is structurally independent of the existing
structure, existing lateral load-carrying structural elements
shall be permitted to remain unaltered. Where the addition is
not structurally independent of the existing structure, the exist-
ing structure and its addition acting together as a single struc-
ture shall be shown to meet the requirements of Sections 1 609 A
and 1613A.
Exception: Any existing lateral load-carrying structural
element whose demand-capacity ratio with the addition
considered is no more than 10 percent greater than its
demand-capacity ratio with the addition ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applica-
ble load combinations with design lateral loads or forces in
accordance with Sections 1609 A and 161 3 A, For purposes
of this exception, comparisons of demand-capacity ratios
and calculation of design lateral loads, forces and capacities
shall account for the cumulative effects of additions and
alterations since original construction.
3403A.4.1 Seismic. Seismic requirements for alterations
shall be in accordance with this section. Where the existing
seismic force-resisting system is a type that can be desig-
nated ordinary or is a welded steel moment frame con-
structed under a permit issued prior to October 25, 1994,
values of R, Qq and Q for the existing seismic force-resist-
ing system shall be those specified by this code for an ordi-
nary system unless it is demonstrated that the existing
system will provide performance equivalent to that of a
detailed intermediate or special system.
SECTION 3404A
ALTERATIONS
3404A. 1 General. Except as provided by this section, alter-
ations to any building or structure shall comply with the
requirements of the code for new construction. Alterations
shall be such that the existing building or structure is no less
complying with the provisions of this code than the existing
building or structure was prior to the alteration.
Exceptions:
1 . An existing stairway shall not be required to comply
with the requirements of Section 1009 where the
existing space and construction does not allow a
reduction in pitch or slope.
2. Handrails otherwise required to comply with Section
1009.12 shall not be required to comply with the
requirements of Section 1012.6 regarding full exten-
sion of the handrails where such extensions would be
hazardous due to plan configuration.
3404A.2 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 1612A.3, any alter-
ation that constitutes substantial improvement of the existing
structure, as defined in Section 1612A.2, shall comply with the
flood design requirements for new construction, and all aspects
of the existing structure shall be brought into compliance with
the requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 1612A.3, any alterations that do not constitute
substantial improvement or substantial damage of the existing
structure, as defined in Section 1612A.2, are not required to
comply with the flood design requirements for new construc-
tion.
3404A.3 Existing structural elements carrying gravity
load. Any existing gravity load-carrying structural element for
which an alteration causes an increase in design gravity load of
more than 5 percent shall be strengthened, supplemented,
replaced or otherwise altered as needed to carry the increased
gravity load required by this code for new structures. Any
existing gravity load-carrying structural element whose grav-
ity load-carrying capacity is decreased as part of the alteration
shall be shown to have the capacity to resist the applicable
design gravity loads required by this code for new structures.
3404A.3.1 Design live load. Where the alteration does not
result in increased design live load, existing gravity
load-carrying structural elements shall be permitted to be
evaluated and designed for live loads approved prior to the
alteration. If the approved live load is less than that required
by Section 1607 A, the area designed for the nonconforming
live load shall be posted with placards of approved design
indicating the approvedlivc load. Where the alteration does
result in increased design live load, the live load required by
Section 1607 A shall be used.
3404A.4 Existing structural elements carrying lateral load.
Except as permitted by Section 3404 A. 5, where the alteration
increases design lateral loads in accordance with Section
1609A or 161 3 A, or where the alteration results in a structural
irregularity as defined in ASCE 7, or where the alteration
decreases the capacity of any existing lateral load-carrying
structural element, the structure of the altered building or struc-
ture shall be shown to meet the requirements of Sections 1609A
and 1613A.
Exception: Any existing lateral load-carrying structural
element whose demand-capacity ratio with the alteration
considered is no more than 10 percent greater than its
demand-capacity ratio with the alteration ignored shall be
permitted to remain unaltered. For purposes of calculating
demand-capacity ratios, the demand shall consider applica-
ble load combinations with design lateral loads or forces per
Sections 1609A and 161 3 A. For purposes of this exception,
comparisons of demand-capacity ratios and calculation of
design lateral loads, forces, and capacities shall account for
the cumulative effects of additions and alterations since
original construction.
3404A.4.1 Seismic. Seismic requirements for alterations
shall be in accordance with this section. Where the existing
seismic force-resisting system is a type that can be desig-
nated ordinary or is a welded steel moment frame con-
structed under a permit issued prior to October 25, 1994,
values ofR, Qq ^^d Q for the existing seismic force-resist-
ing system shall be those specified by this code for an ordi-
nary system unless it is demonstrated that the existing
system will provide performance equivalent to that of a
detailed intermediate or special system.
2010 CALIFORNIA BUILDING CODE
629
EXISTING STRUCTURES
3404A.5 Voluntary seismic improvements. Alterations to
existing structural elements or additions of new structural ele-
ments that are not otherwise required by this chapter and are
initiated for the purpose of improving the performance of the
seismic force-resisting system of an existing structure or the
performance of seismic bracing or anchorage of existing
nonstructural elements shall be permitted, provided that an
engineering analysis is submitted demonstrating the following:
1. The altered structure, and the altered structural and
nonstructural elements are no less in compliance with the
provisions of this code with respect to earthquake design
than they were prior to the alteration.
2. New structural elements are designed, detailed and con-
nected to the existing structural elements as required by
Chapter 16A. Alterations of existing structural elements
shall be based on design demand required by Chapter
16A but need not exceed the maximum load ejfect that
can be transferred to the elements by the system.
Exception: Seismic design in accordance with Sec-
tions 3411 A and 34 12 A shall be permitted.
3. New or relocated nonstructural elements are designed,
detailed and connected to existing or new structural ele-
ments as required by Chapter 16 A.
4. The alterations do not create a structural irregularity as
defined in ASCE 7 or make an existing structural irregu-
larity more severe.
3404A.6 Means of egress capacity factors. Alterations to any
existing building or structure shall not be affected by the egress
width factors in Section 1005.1 for new construction in deter-
mining the minimum egress widths or the minimum number of
exits in an existing building or structure. The minimum egress
widths for the components of the means of egress shall be based
on the means of egress width factors in the building code under
which the building was constructed, and shall be considered as
complying means of egress for any alteration if, in the opinion
of the building code official, they do not constitute a distinct
hazard to life.
SECTION 3405A
REPAIRS
3405A. 1 General, Buildings and structures, and parts thereof,
shall be repaired in compliance with Section 3401 A. 2. Work on
nondamaged components that is necessary for the required
repair of damaged components shall be considered part of the
repair and shall not be subject to the requirements for alter-
ations in this chapter. Routine maintenance required by Section
3401A.2, ordinary repairs exempt from permit in accordance
with Section 105.2, and abatement of wear due to normal ser-
vice conditions shall not be subject to the requirements for
repairs in this section.
3405A.1.1 Dangerous conditions. Regardless of the extent
of structural or nonstructural damage, the building code
official shall have the authority to require the elimination of
conditions deemed dangerous.
3405A. 2 Substantial structural damage to vertical elements
of the lateral force-resisting system. A building that has sus-
tained substantial structural damage to the vertical elements of
its lateral force-resisting system shall be evaluated and repaired
in accordance with the applicable provisions of Sections
3405A.2J through 3405A.2.3.
3405A.2.1 Evaluation. The building shall be evaluated by a
registered design professional, and the evaluation findings
shall be submitted to the code official. The evaluation shaJl
establish whether the damaged building, if repaired to its
predamage state, would comply with the provisions of this
code for wind and earthquake loads. Evaluation for earth-
quake loads shall be required if the substantial structural
damage was caused by or related to earthquake effects or if
the building is in Seismic Design Category D, E or F.
Wind loads for this evaluation shall be those prescribed in
Section 1609 A. Earthquake loads for this evaluation, if
required, shall be permitted to be 75 percent of those pre-
scribed in Section 1613A. Where the existing seismic
force-resisting system is a type that can be designated ordi-
nary or is a welded steel moment frame constructed under a
permit issued prior to October 25, 1994, values ofR, Qg ^^^
Q for the existing seismic force-resisting system shall be
those specified by this code for an ordinary system unless it
is demonstrated that the existing system will provide perfor-
mance equivalent to that of an intermediate or special sys-
tem.
3405A.2.2 Extent of repair for compliant buildings. If the
evaluation establishes compliance of the predamage build-
ing in accordance with Section 3405 A.2,1, then repairs shall
be permitted that restore the building to its predamage state
using materials and strengths that existed prior to the dam-
age.
3405A.2.3 Extent of repair for noncompliant buildings.
If the evaluation does not establish compliance of the
predamage building in accordance with Section 3405A.2.1,
then the building shall be rehabilitated to comply with appli-
cable provisions of this code for load combinations, includ-
ing wind or seismic loads. The wind loads for the repair
shall be as required by the building code in effect at the time
of original construction, unless the damage was caused by
wind, in which case the wind loads shall be as required by
the code in effect at the time of original construction or as
required by this code, whichever are greater Earthquake
loads for this rehabilitation design shall be those required
for the design of the predamage building, but not less than
ninety percent of those prescribed in Section 161 3 A. New
structural members and connections required by this reha-
bilitation design shall comply with the detailing provisions
of this code for new buildings of similar structure, purpose
and location.
3405A.3 Substantial structural damage to gravity load-
carrying components. Gravity load-carrying components that
have sustained substantial structural damage shall be rehabili-
tated to comply with the applicable provisions of this code for
dead and live loads. Snow loads shall be considered if the sub-
stantial structural damage was caused by or related to snow
load effects. Existing gravity load-carrying structural elements
shall be permitted to be designed for live loads approved prior
to the damage. Nondamaged gravity load-carrying compo-
630
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
9)
nents that receive dead, live or snow loads from rehabilitated
components shall also be rehabilitated or shown to have the
capacity to carry the design loads of the rehabilitation design.
New structural members and connections required by this
rehabilitation design shall comply with the detailing provisions
of this code for new buildings of similar structure, purpose and
location.
3405A.3.1 Lateral force-resisting elements. Regardless of
the level of damage to vertical elements of the lateral
force-resisting system, if substantial structural damage to
gravity load-carrying components was caused primarily by
wind or earthquake effects, then the building shall be evalu-
ated in accordance with Section 3405A.2,1 and, if noncom-
pliant, rehabilitated in accordance with Section 3405A.2.3.
3405A.4 Less than substantial structural damage. For dam-
age less than substantial structural damage, repairs shall be
allowed that restore the building to its predamage state using
materials and strengths that existed prior to the damage. New
structural members and connections used for this repair shall
comply with the detailing provisions of this code for new build-
ings of similar structure, purpose and location.
3405A.5 Flood hazard areas. For buildings and structures in
flood hazard areas established in Section 16 12 A3, any repair
that constitutes substantial improvement of the existing struc-
ture, as defined in Section 1612 A.2, shall comply with the flood
design requirements for new construction, and all aspects of
the existing structure shall be brought into compliance with the
requirements for new construction for flood design.
For buildings and structures in flood hazard areas estab-
lished in Section 16 12 A. 3, any repairs that do not constitute
substantial improvement or substantial damage of the existing
structure, as defined in Section 1612A.2, are not required to
comply with the flood design requirements for new construc-
tion.
SECTION 3406A
FIRE ESCAPES
3406A.1 Where permitted. Fire escapes shall be permitted
only as provided for in Sections 3406A. 1 . 1 through 3406A. 1 .4.
3406A.1.1 New buildings. Fire escapes shall not constitute
any part of the required means of egress in new buildings.
3406A. 1.2 Existing fire escapes. Existing fire escapes shall
be continued to be accepted as a component in the means of
egress in existing buildings only.
3406A. 1.3 New fire escapes. New fire escapes for existing
buildings shall be permitted only where exterior stairs can-
not be utilized due to lot lines limiting stair size or due to the
sidewalks, alleys or roads at grade level. New fire escapes
shall not incorporate ladders or access by windows.
3406A.1.4 Limitations. Fire escapes shall comply with this
section and shall not constitute more than 50 percent of the
required number of exits nor more than 50 percent of the
required exit capacity.
3406A.2 Location. Where located on the front of the building
and where projecting beyond the building line, the lowest land-
ing shall not be less than 7 feet (21 34 mm) or more than 12 feet
(3658 mm) above grade, and shall be equipped with a counter-
balanced stairway to the street. In alleyways and thoroughfares
less than 30 feet (9144 mm) wide, the clearance under the low-
est landing shall not be less than 12 feet (3658 mm).
3406A.3 Construction. The fire escape shall be designed to
support a live load of 100 pounds per square foot (4788 Pa) and
shall be constructed of steel or other approved noncombustible
materials. Fire escapes constructed of wood not less than nomi-
nal 2 inches (5 1 mm) thick are permitted on buildings of Type 5
construction. Walkways and railings located over or supported
by combustible roofs in buildings of Type 3 and 4 construction
are permitted to be of wood not less than nominal 2 inches (5 1
mm) thick.
3406A.4 Dimensions. Stairs shall be at least 22 inches (559
mm) wide with risers not more than, and treads not less than, 8
inches (203 mm) and landings at the foot of stairs not less than
40 inches (1016 mm) wide by 36 inches (914 mm) long,
located not more than 8 inches (203 mm) below the door.
3406A.5 Opening protectives. Doors and windows along the
fire escape shall be protected with ^/4-hour opening protectives.
SECTION 3407A
GLASS REPLACEMENT
3407A.1 Conformance. The installation or replacement of
glass shall be as required for new installations.
SECTION 3408A
CHANGE OF OCCUPANCY
3408A. 1 Conformance. No change shall be made in the use or
occupancy of any building that would place the building in a
different division of the same group of occupancies or in a dif-
ferent group of occupancies, unless such building is made to
comply with the requirements of this code for such division or
group of occupancies. Subject to the approval of the building
official, the use or occupancy of existing buildings shall be per-
mitted to be changed and the building is allowed to be occupied
for purposes in other groups without conforming to all the
requirements of this code for those groups, provided the new or
proposed use is less hazardous, based on life and fire risk, than
the existing use.
3408A.2 Certificate of occupancy. A certificate of occupancy
shall be issued where it has been determined that the require-
ments for the new occupancy classification have been met.
3408A.3 Stairways. Existing stairways in an existing structure
shall not be required to comply with the requirements of a new
stairway as outlined in Section 1009 where the existing space
and construcfion will not allow a reduction in pitch or slope.
3408A.4 Change of occupancy. When a change of occupancy
results in a structure being reclassified to a higher occupancy
category, the structure shall conform to the seismic require-
ments for a new structure of the higher occupancy category.
Where the existing seismic force-resisting system is a type that
can be designated ordinary or is a welded steel moment frame
constructed under a permit issued prior to October 25, 1994,
2010 CALIFORNIA BUILDING CODE
631
EXISTING STRUCTURES
II
II
values of R, Qq and Q for the existing seismic force-resisting
system shall be those specified by this code for an ordinary sys-
tem unless it is demonstrated that the existing system will pro-
vide performance equivalent to that of a detailed, intermediate
or special system.
Exception: Specific seismic detailing requirements of this
code or Section 161 3 A for a new structure shall not be
required to be met where it can be shown that the level of
performance and seismic safety is equivalent to that of a new
structure. Such analysis shall consider the regularity, over
strength, redundancy and ductility of the structure within
the context of the existing and retrofit (if any) detailing pro-
vided.
SECTION 34094
HISTORIC BUILDINGS
3409A.1 Historic buildings. The provisions of this code relat-
ing to the construction, repair, alteration, addition, restoration
and movement of structures, and change of occupancy shall not
be mandatory for historic buildings where such buildings are
judged by the building official to not constitute a distinct life
safety hazard.
3409A.2 Flood hazard areas. Within flood hazard areas estab-
lished in accordance with Section 1612.3, where the work pro-
posed constitutes substantial improvement as defined in
Section 1612.2, the building shall be brought into compliance
with Section 1612.
Exception: Historic buildings that are:
1. Listed or preliminarily determined to be eligible for
listing in tiie National Register of Historic Places;
2. Determined by the Secretary of the U.S. Department
of Interior as contributing to the historical signifi-
cance of a registered historic district or a district pre-
liminarily determined to qualify as an historic district;
or
3. Designated as historic under a state or local historic
preservation program that is approved by the Depart-
ment of Interior.
>
SECTION 34104
MOVED STRUCTURES
3410A.1 Conformance. Structures moved into or within the
jurisdiction shall comply with the provisions of this code for
new structures.
SECTION 3411 A
ADDITIONS, ALTERATIONS, REPAIRS AND
SEISMIC RETROFIT TO EXISTING BUILDINGS OR
STRUCTURES DESIGNED IN ACCORDANCE WITH
PRE-1973 BUILDING CODE
3411 AA Seismic retrofit Any seismic retrofit of hospital build-
ing required by Article 2 or Article 11, Chapter 6, Part 1, Title
24, shall meet the requirements of Section 3412A2,
Exception: Hospital buildings evaluated to SPC 1 due to
deficiencies identified by Article 10, Chapter 6, Part 1, Title
24, may be upgraded to SPC 2 by altering, repairing orseis-
mically retrofitting these conditions in accordance with the
requirements of Sections 3404 A or 3412A.2, I I
3411A,2 Alterations, additions and repairs to existing build-
ings or structures not required by Chapter 6, Part 1, Title 24.
3411A,2,1 General Provisions of this section shall apply to
hospital buildings which were originally designed to
pre- 1973 building code and not designated as SPC 3 or
higher in accordance with Chapter 6, Part 1, Title 24.
3411 A,2, 2 Incidental structural alterations, additions or
repairs. Incidental structural additions shall be permitted
provided the additions meet this code for new construction
using importance factor, 1, equal to or greater than 1.0.
Alterations or repairs to the existing affected lateral
load-resisting elements shall meet the requirements of Sec-
tions 3404A or 3405 A respectively.
3411A,2J Minor structural alteration, additions or
repairs. Minor structural additions shall be permitted pro-
vided the additions meet this code for new construction
using importance factor, 1, equal to or greater than 1.0.
Alterations, or repair to existing gravity and lateral
load- resisting systems shall be made to conform to the
requirements of Sections 3404 A or 3 405 A respectively. I I
3411A,2.4 Major structural alteration, additions or
repairs. Major structural alterations, additions or repairs
shall be in accordance with Section 3403 A, 3404 A or 3405 A
respectively.
SECTION 34124
COMPLIANCE ALTERNATIVES FOR ADDITIONS,
ALTERATIONS, REPAIRS AND SEISMIC RETROFIT
TO EXISTING STRUCTURES
3412 A,l Adoption ofASCE 41, Except for the modifications
as set forth in Sections 34 12 A and 341 3 A all additions, alter-
ations, repairs and seismic retrofit to existing structures or por-
tions thereof shall be permitted to be designed in accordance \ \
with the provisions ofASCE 41.
3412A,1,1 Referenced standards. All reference standards
listed in ASCE 41 shall be replaced by referenced standards
listed in Chapter 35 of this code and shall include all
amendments to the reference standards in this code.
3412A.L2 ASCE 41 Section 1,4 - Rehabilitation Objec-
tives, Target building performance level shall be as follows:
a. For general acute care hospitals along with all
structures required for their continuous operation
or access/egress - Immediate Occupancy (10) Struc- \
tural Performance Level (S-1) as defined in Section
1.5.1,1 at Basic Safety Earthquake 1 (BSE-1) Seismic
Hazard Level as defined in Section 1.6.1,2 and Col-
lapse Prevention (CP) Structural performance level
(S-5) per Section L 5. 1.5 at Basic Safety Earthquake 2
(BSE-2) Seismic Hazard Level as defined in Section
r
632
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
L6J.1. The nonstructural performance level shall
satisfy the requirements of this code for new hospital
buildings.
Exceptions: Buildings satisfying requirements of
Sections 341 lA or 3412A2.
b. For pre-1973 buildings which will not be used for
general acute care services after January 1, 2030 -
Basic Safety Objective (BSD) Level as defined in Sec-
tion 1.4.1, BSO level includes Life Safety Building
Performance (3-C) Level as defined in Section 1.5.3.3
at the Basic Safety Earthquake 1 (BSE-1) Seismic
Hazard Level as defined in section 1.6.1.2 and Col-
lapse Prevention (CP) building performance level
(5-E) per Section 1.5.3.4 at the Basic Safety Earth-
quake 2 (BSE-2) Seismic Hazard Level as defined in
Section 1.6.1.1.
Exceptions: Buildings satisfying requirements of
Sections 341 lA or 3412A.2.
c. All Others - Immediate Occupancy (10) Building
Performance Level of (1-B) as defined in Section
1,5.3.2 at Basic Safety Earthquake 1 (BSE-1) Seismic
Hazard Level as defined in Section L6.1.2 and Col-
I I lapse Prevention (CP) building performance level
(5-E) per Section 1.5.3.4 at Basic Safety Earthquake 2
(BSE-2) Seismic Hazard Level as defined in Section
1.6.1,1,
34 12 A, 1,3 Material testing required. Use of material prop-
erties based on historical information as default values
shall not be permitted,
3412 AAA Analysis procedure. The selection of a particu-
lar analysis procedure from ASCE 41 shall be subject to the
approval of the enforcement agent,
3412 A. L5 Structural design criteria. Prior to implementa-
tion of ASCE 41 Nonlinear Dynamic Procedure, the ground
motion, analysis and design methods, material assumptions
and acceptance criteria proposed by the engineer shall be
reviewed by the enforcement agent.
341 2 A, L 6 Structural observation, testing and inspections.
Construction, testing, inspection and structural observa-
tion requirements shall be as required for new construction.
3412 A,2 Seismic evaluation and retrofit of general acute care
hospitals. Not withstanding any other requirements of this
code, all existing general acute care hospitals shall comply
with the requirements specified in Chapter 6, Part 1, Title 24.
3412A,2,1 SPC 5 and NPC 4/NPC 5. Structures and
nonstructural components and systems satisfying the
requirements of this code for new buildings for Occupancy
Category IV shall be considered to satisfy the requirements
of SPC 5 and NPC 4. NPC 4 buildings satisfying opera-
tional requirements for NPC 5 of Table 11,1, Chapter 6, Part
1, Title 24, shall be placed in nonstructural performance
category NPC 5.
3412A.2,2 SPC 5 using ASCE 41, Structures satisfying the
requirements of immediate occupancy structural perfor-
mance level (S-1) per Section 1,5,1,1 of ASCE 41 at BSE-1,
Collapse prevention performance level S-5 per Section
1.5.1.5 of ASCE 41 at BSE-2 and items identified in Chapter
6, Article 10, Part 1, Title 24, satisfying the requirements of
Immediate Occupancy Nonstructural performance level
(N-B)per Section 1,5,2.2 of ASCE 41 at BSE-1 shall be con-
sidered to comply with SPC 5 requirements of Table 2.5.3,
Chapter 6, Part 1, Title 24,
3412A,2,3 SPC 2 using ASCE 41, Structures satisfying the
requirements of life safety structural performance level
(S-3) per Section 1,5.1.3 of ASCE 41 at BSE-1 and items
identified in Chapter 6, Article 10, Title 24, Part 1 satisfying
the requirements of life safety nonstructural performance
level (N-C)per Section 1.5.2.3 of ASCE 41 at BSE- 1, shall
be considered to comply with SPC 2 requirements of Table
2.5.3, Chapter 6, Part 1, Title 24.
3412A,2,4 NPC, Nonstructural components for immediate
occupancy nonstructural performance level (N-B) in Sec-
tion 1.5,2.2 shall meet the requirements of this code for new
buildings. Nonstructural components for operational
nonstructural performance level (N-A) in Section 1.5.2,1
shall meet performance level N-B and Section 34 13 A, 1.30,
Building satisfying the requirements of nonstructural per-
formance level N-A and N-B as described in this section
shall be considered to satisfy the requirements of NPC 5 &
NPC 4 of Table 11.1, Chapter 6, Part 1, Title 24 respectively
Immediate occupancy nonstructural performance level
(N-B) in Section 1.5,2.2 and life safety nonstructural perfor-
mance level (N-C) in Section 1,5.2,3 of ASCE 41 at BSE-1
shall be considered equivalent to NPC 3/NPC 2 and NPC
3R requirements respectively of Table 11,1, Chapter 6, Part
h Title 24, For NPC 3/NPC 3R/NPC 2, only components
listed in Table 11,1, Chapter 6, Part 1, Title 24, for NPC
3/NPC 3R/NPC 2 need to satisfy the requirements specified
above.
Exceptions:
1) Evaluation procedure in Article 11, Chapter 6,
Part 1, Title 24 shall be used for seismic evaluation
of NPC 2, NPC 3/NPC 3R, NPC 4 and NPC 5,
where specific procedure is not outlined in ASCE
41, Administrative and permitting provisions out-
lined in Article 11, Chapter 6, Parti, Title 24 shall
apply.
2) Anchorage and bracing of nonstructural compo-
nents in buildings in seismic performance catego-
ries SPC 1 and SPC 2 with a performance level of
NPC3R may comply with the provisions of Section
1630 A of the 1995 Calif ornia Building Code using
an importance factor Ip -1.0, The capacity of
welds, anchors and fasteners shall be determined
in accordance with requirements of this code.
3) Anchorage and bracing of nonstructural compo-
nents in buildings in seismic performance catego-
ries SPC 1 or SPC 2 with a performance level of
NPC 3 or higher, and SPC 3 or SPC 4, may comply
with the provisions of Section 163 OB of the 1998
California Building Code using an importance
factor Ip =1.5. The capacity of welds, anchors and
fasteners shall be determined in accordance with
requirements of this code.
2010 CALIFORNIA BUILDING CODE
633
EXISTING STRUCTURES
II
A continuous load path of sufficient strength and stiffitess
between the component and the supporting structure shall
he verified. Local elements of the supporting structure shall
be verified for the component loads where they control the
design of the elements or their connections. Increases in Fp
due to anchorage conditions (for example shallow anchors)
need not be considered. For NPC 3R, the adequacy of load
path for nonstructural elements need only be verified when
the total reaction at the point of support (including the
application ofFp) exceeds the following limits:
1 . 250 pounds for components or equipment attached to
light frame walls. For the purposes of this require-
ment, the sum of the absolute value of all reactions
due to component loads on a single stud shall not
exceed 250 pounds.
2. 1 , 000 pounds for components or equipment attached
to roofs, or walls of reinforced concrete or masonry
construction.
3. 2, 000 pounds for components or equipment attached
to floors or slabs-on- grade.
Exception: If the anchorage or bracing is config-
ured in a manner that results in significant torsion
on a supporting structural element, the effects of
the nonstructural reaction force on the structural
element shall be considered in the anchorage
design.
SECTION 3413A
MODIFICATIONS TO ASCE 41
3413 A J General The text of ASCE 41 shall be modified as
indicated in Sections 34 13 A. 1.1 through 341 3 A J. 32.
References in ASCE 41 shall comply with requirements of
Sections 102.4.1 and 102.4.2.
3413A.1J ASCE 41 Section 1,1. Modify ASCE 41 Section
1.1 with the following:
Seismic evaluations shall be performed using procedure
and criteria of ASCE 41 except for general acute care
hospitals, which shall be evaluated per Chapter 6, Part 1,
Title 24 when required per provision of that chapter
3413A.L2 ASCE 41 Section L6 Seismic Hazard. Modify
ASCE 41 Section 1.6 with the following:
Response spectra and acceleration time histories shall
be constructed in accordance with Sections 161 3 A,
161 5 A and 1803A.6. Basic Safety Earthquake 2 (BSE-2)
in ASCE 41 shall be same as Maximum Considered
Earthquake (MCE) in ASCE 7.
3413A.L3 ASCE 41 Section 2.2.6. Modify ASCE 41 Sec-
tion 2.2.6 with the following:
Data collection requirements. The extent of data collec-
tion shall be at Comprehensive level for all structures
except that data collection at Usual level shall be permit-
ted for structures with BSO or lower target performance
objective. Materials properties testing program shall be
pre-approved by the enforcement agent.
Eor buildings, built under an OSHPD permit based on
the 1976 or later edition of the CBC, where materials
properties are shown on design drawings and original
materials test data are available, no materials testing
shall be required when approved by the enforcement
agent.
3413A.1.4 ASCE 41 Section 2.4.1.1. Modify ASCE 41 Sec-
tion 2.4.1.1 with the following:
1. If one or more component DCRs exceed 1.5 for the
Immediate Occupancy Structural Performance Level
(S-1) or 2,0 for the Life Safety Structural Perfor-
mance level (S-3) and any irregularity described in
Section 2.4.1.1.1 through 2.4.1.1.4 is present, then
linear procedures are not applicable and shall not be
used.
2. Linear procedures are not applicable to moment
resisting frames where plastic hinges do not form in
either the beam at the face of column or in the column
panel zone.
3413A.1.5ASCE41 Section 2.4.2.1. Modify ASCE 41 Sec-
tion 2.4.2.1 with the following:
Nonlinear static procedure. If higher mode effects are
significant and building is taller than 75 feet above the
base, the Nonlinear Dynamic Procedure shall be used.
3413A.1.6 ASCE 41 Section 2.4.4.5. Modify ASCE41 Sec-
tion 2.4.4.5 by the following:
Material properties. Expected material properties are
not permitted to be determined by multiplying lower
bound values by the assumed factors specified in Chap-
ters 5 through 8.
3413A.L7 ASCE 41 Section 3.2.10.1. Modify ASCE 41
Section 3.2.10.1 with the following:
Linear procedures. Equation 3-5 is not permitted by
OSHPD.
3413A.L8 ASCE 41 Section 3.3.1.3.5. Replace ASCE 41
Section 3.3.1.3.5 as follows:
Unreinforced masonry buildings. Unreinforced
Masonry not permitted by OSHPD.
3413A.1.9 ASCE 41 Section 3.3.3.2.2. Modify ASCE 41
Section 3.3.3.2.2 with the following:
Simplified NSP Analysis. Not permitted by OSHPD.
3413A.1.10 ASCE 41 Section 3.4.2.2. Modify ASCE 41
Section 3.4.2.2 with the following:
Acceptance criteria for linear procedures - drift limita-
tions. The interstory drift ratio shall not exceed the drift
limits for Occupancy Category FV buildings in ASCE 7
Table 12.12-1 due to forces corresponding to BSE-1,
except that buildings designed to BSO or lower perfor-
mance levels are permitted to meet the drift limits for
Occupancy Category II buildings. For dual systems, the
least interstory drift ratio shall control
Exception: Larger interstory drift ratios shall be per-
mitted where justified by rational analysis that both
#
II
634
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
structural and nonstructural elements can tolerate
such drift and approved by the enforcement agent.
3413A.L11 ASCE 41 Section 3A,3,2.L Modify ASCE 41
Section 3. 4 3, 2 J with the following:
Deformation-controlled actions. For any building
required to meet the Operational Building Performance
level, 1-A or Immediate Occupancy Building Perfor-
mance Level, 1-B, primary components shall be within
the acceptance criteria for primary components and sec-
ondary components shall be within the acceptance crite-
ria for secondary components.
3413AJJ2ASCE41 Section 4.4. Modify ASCE 41 Section
4.4 with thefollowings:
Foundation strength and stiffness. Foundation and soil
strength shall be used to evaluate potential overturning,
uplift and sliding for fixed base assumptions, and stiff-
ness for flexible base assumptions, including deforma-
tions associated with those actions.
3413A.1.13 ASCE 41 Section 4.4.1.1. Replace ASCE 41
Section 4.4.1.1 as follows:
Presumptive capacities. Not permitted by OSHPD.
3413A.L14 ASCE 41 Section 4.4.1.2. Replace ASCE 41
Section 4.4.1.2 as follows:
Prescriptive expected capacities. Not permitted by
OSHPD.
3413A.1.15 ASCE 41 Section 4.4.3.2.2. Modify ASCE 41
Section 4.4.3.2.2 with the following:
Flexible base assumption. The soil strength shall be
evaluated.
3413A.1.16ASCE41 Section 4.5. Modify ASCE41 Section
4.5 with the following:
Seismic earth pressure. Where the grade difference from
one side of the building to another exceeds one-half story
height, the seismic increment of earth pressure shall be
added to the gravity lateral earth pressure to evaluate the
building overturning and sliding stability and the lateral
force resisting system below grade in combination with
the building seismic forces.
3413A.1.17 ASCE 41 Table 5.6. Modify ASCE 41 Table 5.6
with the following:
Acceptance criteria for nonlinear procedures — struc-
tural steel components. For fully and partially
restrained moment connections designed to 1989 or
prior edition of Part 2, Title 24 shall be verified for the
presence of welds using E70T-4 electrodes or other elec-
trodes with equivalent aluminum content. Where E70T-4
or equivalent electrodes are present, the plastic rotation
angles and residual strength ratios used shall be sub-
stantiated by the statistical analysis of three or more
applicable cyclic test results subject to the approval of
the enforcement agent.
3413A.1.18 ASCE 41 Section 6.7.1.1. Modify ASCE 41
Section 6.7.1.1 with the following:
Monolithic reinforced concrete shear walls and wall
segments. For nonlinear procedures, shear walls or wall
segments with axial loads greater than 0.35 P^ shall be
included in the model as primary elements with appro-
priate strength and stiffness degrading properties
assigned to those components subject to the approval of
the enforcement agent. For linear procedures, the effects
of deformation compatibility shall be investigated using
moment-curvature section analyses and cyclic testing
results of similar components to determine whether
strengthening is necessary to maintain the gravity load
carrying capacity of that component.
Horizontal wall segments or spandrels reinforced sim-
ilar to vertical wall segments or piers shall be classified
as wall segments, not shear wall coupling beams, in
Tables 6-18 through 6-21.
3413A.1.19ASCE41 Section 7.3.2. Replace ASCE 41 Sec-
tion 7.3.2 as follows:
Unreinforced masonry walls and piers in-plane. Not
permitted by OSHPD.
3413A.1.20ASCE41 Section 7.3.3. Replace ASCE 41 Sec-
tion 7.3.3 as follows:
Unreinforced masonry walls out-of-plane. Not permit-
ted by OSHPD.
3413A.L21 ASCE 41 7.3.4.2.2 Shear strength of walls and
piers. Modify ASCE 41 Section 7.3.4.2.2 with the following:
The spacing of shear reinforcing, S, shall be less than or
equal to the wall pier clear height divided by 2 or the
story height divided by 2, whichever is smaller.
3413A.1.22 ASCE 41 Section 9.2.4. Modify ASCE 41 Sec-
tion 9.2.4 with the following:
Linear procedures. Verification of the interstory lateral
displacements, isolator displacements, the strength ade-
quacy of the seismic force resisting system and isolation
system, and anchorage to the foundation shall be accom-
plished using the nonlinear dynamic procedure.
3413A.1.23 ASCE 41 Section 9.2.5.1. Modify ASCE 41
Section 9.2.5.1 with the following:
Nonlinear static procedure. Verification of the
interstory lateral displacements, isolator displacements,
the strength adequacy of the seismic force resisting sys-
tem and isolation system, and anchorage to the founda-
tion shall be accomplished using the nonlinear dynamic
procedure.
3413A.1.24 Reserved.
3413A.1.25 Reserved.
3413A.1.26 ASCE 41 Section 9.3.4. Modify ASCE 41 Sec-
tion 9.3.4 with the following:
Linear Procedures. Verification of the interstory lateral
displacements, damper relative velocities and displace-
<
<
2010 CALIFORNIA BUILDING CODE
635
EXISTING STRUCTURES
mentSy the strength adequacy of the seismic force resist-
ing system and damping system, and anchorage to the
foundation shall be accomplished using the nonlinear
dynamic procedure.
3413A.L27 ASCE 41 Section 9J,5.L Modify ASCE 41
Section 9 J. 5.1 with the following:
Nonlinear static procedure. Verification of the
interstory lateral displacements, damper relative veloci-
ties and displacements, the strength adequacy of the seis-
mic force resisting system and damping system, and
anchorage to the foundation shall be accomplished
using the nonlinear dynamic procedure.
>| I 3413A.L28 Reserved
3413AJ,29ASCE41 Chapter 10. Replace ASCE 41 Chap-
ter Was follows:
Simplified rehabilitation. Not permitted by OSHPD.
3413A.L30ASCE41 Section 11.3.2. Modify ASCE 41 Sec-
tion 11.3.2 with the following:
Operational nonstructural performance level (n-a)
requirements. All Structures shall meet immediate occu-
pancy nonstructural performance level (N-B) and facil-
ity shall have on-site supplies of water and holding tanks
for wastewater, sufficient for 72 hours emergency opera-
tions, are integrated into the building plumbing systems.
As an alternative, hook-ups to allow for the use of trans-
portable sources of water and sanitary waste water dis-
posal have been provided. An on-site emergency system
as defined within Part 3, Title 24 is incorporated into the
building electrical system for critical care areas. Addi-
tionally, the system shall provide for radiological service
and an onsitefuel supply for 72 hours of acute care oper-
ation.
3413A.L31 ASCE 41 Section 11.9.4.3.1. Modify ASCE 41
Section 11.9.4.3.1 with the following:
Ceilings in all categories shall satisfy requirements for
ceilings in Category C specified in this section.
3413A.1.32 ASCE 41 Section 11.10.2.4. Modify ASCE 41
Section 11.10.2.4 by the following:
For general acute care hospital, nonstructural evalua-
tion shall comply with requirements of Section 11.2,
Chapter 6, Part 1, Title 24.
SECTION 3414A
PEER REVIEW REQUIREMENTS
3414A.1 General. Independent peer review is an objective
technical review by knowledgeable reviewer(s) experienced in
structural design, analysis and performance issues involved.
The reviewer(s) shall examine the available information on the
condition of building, basic engineering concept employed and
recommendations for action,
3414A.2 Timing of independent review. The independent
reviewer (s) shall be selected prior to initiation of substantial
portion of the design and analysis work that is to be reviewed.
and review shall start as soon as practical and sufficient infor-
mation defining the project is available.
3414A.3 Qualifications and terms of employment. The
reviewer shall be independent from the design and construc-
tion team.
3414A.3.1 The reviewer(s) shall have no other involvement
in the project before, during or after the review, except in a
review capacity.
3414A.3.2 The reviewer shall be selected and paid by owner
and shall have technical expertise in repair of buildings
similar to the one being reviewed, as determined by enforce-
ment agent.
3414A.3.3 The reviewer (in case of review team, the chair)
shall be a California-licensed structural engineer who is
familiar with technical issues and regulations governing the
work to be reviewed.
3414A.3.4 The reviewer shall serve through completion of
the project and shall not be terminated except for failure to
perform the duties specified herein. Such termination shall
be in writing with copies to enforcement agent, owner, and
the engineer of record. When a reviewer is terminated or
resigns, a qualified replacement shall be appointed within
10 working days.
3414A.4 Scope of review. Review activities shall include,
where appropriate, available construction documents, design
criteria, observation of the condition of structure, all new and
original inspection reports, including methods of sampling,
analyses prepared by the engineer of record and consultants,
and the retrofit or repair design. Review shall include consider-
ation of the proposed design approach, method, materials and
details.
3414 A.5 Reports. The reviewer(s) shall prepare a written
report to the owner and responsible enforcement agent that
covers all aspect of the review performed including conclu-
sions reached by the reviewer. Report shall be issued after the
schematic phase, during design development, and at the com-
pletion of construction documents, but prior to their issuance
of permit. Such report shall include, at the minimum, statement
of the following.
1 . Scope of engineering design peer review with limitations
defined.
2. The status of the project documents at each review stage.
3. Ability of selected materials and framing systems to meet
the performance criteria with given loads and configura-
tion.
4. Degree of structural system redundancy and the defor-
mation compatibility among structural and nonstruc-
tural elements.
5. Basic constructability of the retrofit or repair system.
6. Other recommendation that will be appropriate for the
specific project.
7. Presentation of the conclusions of the reviewer identify-
ing any areas that need further review, investigation
and/or clarification.
8. Recommendations.
II
ff
II
636
2010 CALIFORNIA BUILDING CODE
EXISTING STRUCTURES
4
3414A,6 Responses and corrective actions. The engineer of
record shall review the report from the reviewer(s) and shall
develop corrective actions and other responses as appropriate.
Changes observed during construction that affect the seis-
mic-resisting system shall be reported to the reviewer in writing
for review and recommendations. All reports, responses and
corrective actions prepared pursuant to this section shall be
submitted to the responsible enforcement agent and the owner
along with other plans, specifications and calculations
required. If the reviewer resigns or is terminated by the owner
prior to completion of the project, then the reviewer shall sub-
mit copies of all reports, notes, and the correspondence to the
responsible enforcement agent, the owner, and the engineer of
record within 10 working days of such termination.
SECTION 341 5A
EARTHQUAKE MONITORING
INSTRUMENTS FOR EXISTING BUILDINGS
341 5 A. 1 Earthquake recording instrumentation of existing
buildings. All owners of existing structures, selected by the
enforcement agency for the installation of earthquake-record-
ing instruments, shall provide space for the installation and
access to such instruments. Location of said instruments shall
be determined by the enforcement agency. The enforcement
agency shall make arrangements to provide, maintain, and ser-
vice the instruments. Data shall be the property of the enforce-
ment agency, but copies of individual records shall be made
available to the public on request and the payment of an appro-
priate fee.
201 CALIFORNIA BUILDING CODE 637
638 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 35 - REFERENCED STANDARDS
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire cinapter
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
ACI
X
X
AISC
X
X
AITC
X
X
ANSI
X
ASCE/SEI
X
X
ASME
X
ASTM
X
X
ASTM E662-09
X
AWS
X
X
BHMA
X
CPSC
X
ICC
X
X
NFPA
X
X
X
NFPA13D-10
X
NFPA 170-06
X
PCI
X
X
PTI
X
X
ASME BPE-2009
X
ASTM E648-04
X
FM3260-00
X
FM3011-99
X
FM4430-80
X
ICC ES AC 331
X
ICC ES AC 77
X
NFPA 720
X
X
X
NFPA 13-10
X
NFPA13R-10
X
NFPA 14-07
X
NFPA 15-01
X
NFPA 22-03
X
NFPA 24-10
X
NFPA 37-06
X
NFPA 50-01
X
NFPA 54-09
X
NFPA 57-02
X
(continued)
2010 CALIFORNIA BUILDING CODE
639
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
CHAPTER 35 - REFERENCED STANDARDS— continued
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
ss
ss/cc
1
2
3
4
Adopt entire chapter
X
X
X
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
X
X
X
Adopt only those sections that
are listed below
Chapter/Section
X
NFPA 72-10
X
NFPA 92a-09
X
SFM12-3
X
SFM1 2-7-3
X
SFM12-7A-1
X
SFM 12-7A-2
X
SFM 12-7A-3
X
SFM 12-7A-4
X
SFM 12-7A-4A
X
SFM 12-7A-5
X
SFM 12-8-100
X
SFM 12-10-1
X
SFM 12-10-2
X
SFM 12-10-3
X
UBC15-2
X
UBC15-3
X
UBC15-4
X
UL 13-96
X
UL 38-99
X
UL 193-04
X
UL 199-95
X
UL 228-97
X
UL 260-04
X
UL 262-04
X
UL 268A-98
X
UL 312-04
X
UL 346-05
X
UL 464-03
X
UL 4978-04
X
UL 521-99
X
UL 539-00
X
UL 632-00
X
UL 753-04
X
UL 813-96
X
UL 864-03
X
UL 2034
X
X
X
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section Lll.
640
2010 CALIFORNIA BUILDING CODE
CHAPTER 35
REFERENCED STANDARDS
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the
promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this
document that reference the standard. The application of the referenced standards shall be as specified in Chapter 1, Administration,
Division 1, Sections LL5 and LL7, and in Chapter 7, Administration, Division II, Section 102.4.
[DSA'SSy DSA-SS-CC & OSHPD 1 &4] Reference to other chapters. In addition to the code sections referenced, the standards
listed in this chapter are applicable to the respective code sections in Chapters 16 A, 17 A, ISA, 19 A, 21 A, 22 A and 34 A.
AA
Aluminum Association
1525 Wilson Boulevard, Suite 600
Arlington, VA 22209
Standard
reference
number
Title
Referenced
in code
section number
ADM1--05
ASM 35^00
Aluminum Design Manual: Part 1-A Specification for Aluminum Structures, Allowable Stress Design;
and Part 1-B — Aluminum Structures, Load and Resistance Factor Design 1604.3.5, 2002.1
Aluminum Sheet Metal Work in Building Construction (Fourth Edition) 2002.1
AAMA
American Architectural Manufacturers Association
1827 Waldon Office Square, Suite 550
Schaumburg,IL 60173
Standard
reference
number
Title
Referenced
in code
section number
1402—86
AAMAAVDMA/CSA
101/I.S.2/A440— 08
Standard Specifications for Aluminum Siding, Soffit and Fascia
North American Fenestration Standard/Specifications for Windows, Doors and Skylights
.1404.5.1
.1715.5.1,2405.5
ACI
Standard
Referenced
reference
in code
number
Title
section number
216.1—07
318—08
440,2R-08
503.7—07
506—05
530—08
530.1—08
American Concrete Institute
38800 Country Club Drive
Farmington Hills, MI 48331
Title
Standard Method for Determining Fire Resistance of Concrete and
Masonry Construction Assemblies Table 720.1(2), 721.1
Building Code Requirements for Structural Concrete 1604.3.2, 1614.3.1, 1614.4.1, 1704.3.1.3, T^ble 1704.3,
1704.4.1, Table 1704.4, 1708. 2„1 808.8.2, Table 1808.8.2, 1808.8.5, 1808.8.6, 1810.2.4.1, 1810.3.2.1.1,
1810.3.2.1.2, 1810.3.8.3.1, 1810.3.8.3.3, 1810.3.9.4.2.1, 1810.3.9.4.2.2, 1810.3.11.1, 1901.2,
1901.3, 1901.4, 1902.1, 1903.1, 1904.1,1904.2, 1904,3, 1904.4.1, 1904.4.2, 1904.5, 1905.1.1, 1905.2,
1905.3, 1905.4, 1905.5, 1905.6.2, 1905.6.3, 1905.6.4, 1905.6.5, 1905.7, 1905.8, 1905.9,
1905.10, 1905.11, 1905.12, 1905.13, 1906.1, 1906.2, 1906.3, 1906.4, 1907.1, 1907.2, 1907.3,
1907.4, 1907.5, 1907.6, 1907.7.1, 1907.7.2, 1907.7.3, 1907.7.4, 1907.7.5, 1907.7.6, 1907.8, 1907.9, 1907.10,
1907.11, 1907.12, 1907.13, 1908.1, 1908.1.1, 1908.1.2, 1908.1.3, 1908.1.4, 1908.1.5, 1908.1.6,
1908.1.7, 1908.1.8, 1908.1.9, 1908.1.10,1909.1, 1909.3, 1909.4, 1909.5, 1909.6, 1912.1, 2108.3, 2205.3
Guide for the Design and Construction of Externally Bonded FRP Systems for Strengthening Concrete Structures . . . 1917 A3
Specification for Crack Repair by Epoxy Injection 1917A.2
Guide to Shotcrete 1913A
Building Code Requirements for Masonry Structures 1405.5, 1405.5.2, 1405.9, 1604.3.4,
1704.5, 1704.5.1,1^^6 1704.5.1, 1704.5.2, 1704.5.3,
Table 1704.5.3, 1807.1.6.3.2, 1808.9, 2101.2.2, 2101.2.3,
2101.2.4, 2101.2.5, 2101.2.6, 2103.1.3.6, 2106.1,
2107.1, 2107.2, 2107.3, 2107.4, 2107.5, 2108,1, 2108.2, 2108.3,
2109.1, 2109.1.1, 2109.2, 2109.2.1, 2109.3, 2110.1
Specifications for Masonry Structures 1405.5.1, Tkble 1704.5.1, Tkble 1704.5.3, 1807.1.6.3, 2103.8,
2103.11, 2103.12, 2103.13, 2104.1, 2104.1.1, 2104.1.2, 2104.1.3,
2104.2, 2104.3, 2104.4, 2105.2.2.1.1, 2105.2,2.1.2,2105.2.2.1.3
II
2010 CALIFORNIA BUILDING CODE
641
REFERENCED STANDARDS
AF&PA
American Forest & Paper Association
nil 19th St, NW Suite 800
Washington, DC 20036
Standard
Referenced
reference
in code
number
Title
section number
WCD No. 4—89
WFCM— 01
NDS— 05
AF&PA— 93
ANSI/AF&PA PWF— 07
ANSI/AF&PA SDPWS— 08
Wood Construction Data — Plank and Beam Framing for Residential Buildings 2306. 1 .2
Wood Frame Construction Manual for One- and Two-family Dwellings 1609.1.1, 1609.1.1.1, 2301.2, 2308.1, 2308.2.1
National Design Specification (NDS) for Wood Construction with 2005 Supplement 721.6.3.2, 1716.1.1,
1716.1.4, 1809.12, 1810.3.2.4, Table 1810.3.2.6, 2302.1, 2304.12, 2306.1,
Table 2306.2.1(1), Table 2306.2.1(2), Table 2306.3, Table 2306.6, 2307.1, 2307.1.1
Span Tables for Joists and Rafters 2306.1.1, 2308.8, 2308.10.2, 2308.10.3
Permanent Wood Foundation Design Specification 1805.2, 1807.1.4, 2304.9.5.2
Special Design Provisions for Wind and Seismic 1613.6.1, 2305.1, 2306.1, 2306.2.1, 2306.2.2,2306.2.3, 2306.3,
Table 2306.3, 2306.4, 2306.5, 2306.6, 2306.7, Table 2306.7, 2307.1, 2307.1.1
AISC
II
341—05
358-05
360—05
American Institute of Steel Construction
One East Wacker Drive, Suite 700
Chicago, IL 60601-18021
Standard
Referenced
reference
in code
number
Title
section number
Seismic Provisions for Structural Steel Buildings, including Supplement No. 1 dated 2005 1613.6.2, 1707.2,
1708.3, 2205.2.1, 2205.2.2, 2205.3, 2205.3.1
Prequalified Connections for Special and Intermediate Steel Moment Frames
for Seismic Applications including Supplement No. 1 2205 A, 341 3 A
Specification for Structural Steel Buildings 1604.3.3, Table 1704.3, 1704.3.3, 2203.1, 2203.2, 2205.1, 2205.3
AISI
Standard
Referenced
reference
in code
number
Title
section number
S 100— 07
S200— 07
S210— 07
S211— 07
S212— 07
S213— 07
S214— 07
S230— 07
American Iron and Steel Institute
1 140 Connecticut Avenue, 705
Suite 705
Washington, DC 20036
Title
North American Specification for the Design of Cold-formed
Steel Structural Members 1604.3.3, 2203.1, 2203.2, 2209.1, 2210.2, 2210.4, 2210.5
North American Standard for Cold-formed Steel Framing — General Provisions 2203.1, 2203.2, 2210.1
North American Standard for Cold-formed Steel Framing — Floor and Roof System Desiga 2210.5
North American Standard for Cold-formed Steel Framing — Wall Stud Design 2210.4
North American Standard for Cold-formed Steel Framing — Header Design 2210.2
North American Standard for Cold-formed Steel Framing — Lateral Design 2210.6
North American Standard for Cold-formed Steel Framing — Truss
Design, with Supplement 2, dated 2008 2210.3.1 1
Standard for Cold-formed Steel Framing — Prescriptive Method for One- and
Two-family Dwellings, with Supplement 2, dated 2008 1609.1.1, 1609.1.1.1, 2210.7
AITC
AITC Technical
Note 7—96
AITC 104—03
AITC 110—01
AITC 111-05
AITC 113—01
AITC 117—04
American Institute of Timber Construction
Suite 140
7012 S. Revere Parkway
Englewood, CO 80112
Standard
Referenced
reference
in code
number
Title
section number
Calculation of Fire Resistance of Glued Laminated Timbers 721.6.3.3
Typical Construction Details 2306. 1
Standard Appearance Grades for Structural Glued Laminated Timber 2306. 1
Recommended Practice for Protection of Structural Glued Laminated Timber
During Transit, Storage and Erection 2303.1.3.1
Standard for Dimensions of Structural Glued Laminated Timber 2306.1
Standard Specifications for Structural Glued Laminated Timber of Softwood Species 2306.1
642
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
AITC 119—96
AITC 200—04
AITC 404-05
ANSI/AITC A 190.1—07
AITC— continued
Standard Specifications for Structural Glued Laminated Timber of Hardwood Species 2306.1
Manufacturing Quality Control Systems Manual for Structural Glued Laminated Timber 2306.1
Standard for Radially Reinforcing Curved Glued Laminate Timber Members to Resist Radial Tension 2303.1,3,1
Structural Glued Laminated Timber 2303.1.3, 2306.1
ALI
Automotive Lift Institute
P.O. Box 85
Courtland, NY 13045
Standard
reference
number
Tide
Referenced
in code
section number
ALI ALCTV— 2006
Standard for Automobile Lifts — Safety Requirements for Construction, Testing and Validation (ANSI) 3001.2
ANSI
American National Standards Institute
25 West 43rd Street, Fourth Floor
New York, NY 10036
Standard
reference
number
Title
Referenced
in code
section number
A13.1— 96
(Reaffirmed 2002)
A108.1A— 99
A108.1B— 99
A108.4— 99
A 108.5— 99
A108.6— 99
A108.8— 99
A108.9— 99
A108.10— 99
A118.1— 99
All 8.3— 99
Al 18.4—99
Al 18.5—99
Al 18.6—99
Al 18.8— 99
A136.1— 99
A137.1— 88
A208.1— 99
S3A1
Z 97.1—04
Scheme for the Identification of Piping Systems 415.8.6.4
Installation of Ceramic Tile in the Wet-set Method, with Portland Cement Mortar 2103.10
Installation of Ceramic Tile, quarry Tile on a Cured Portland Cement Mortar Setting Bed with
Dry-set or Latex-portland Mortar 2103.10
Installation of Ceramic Tile with Organic Adhesives or Water-cleanable Tile-setting Epoxy Adhesive 2103.10.6
Installation of Ceramic Tile with Dry-set Portland Cement Mortar or Latex-portland Cement Mortar .... 2103.10,1, 2103.10.2
Installation of Ceramic Tile with Chemical-resistant, Water Cleanable Tile-setting and -grouting Epoxy 2103.10.3
Installation of Ceramic Tile with Chemical-resistant Furan Resin Mortar and Grout 2103.10.4
Installation of Ceramic Tile with Modified Epoxy Emulsion Mortar/Grout 2103.10.5
Installation of Grout in Tilework 2103.10.7
American National Standard Specifications for Dry-set Portland Cement Mortar 2103.10.1
American National Standard Specifications for Chemical-resistant, Water-cleanable Tile-setting and
-grouting Epoxy and Water Cleanable Tile-setting Epoxy Adhesive .2103.10.3
American National Standard Specifications for Latex-portland Cement Mortar 2103.10.2
American National Standard Specifications for Chemical Resistant Furan Mortar and Grouts for Tile Installation. . . 2103.10.4
American National Standard Specifications for Cement Grouts for Tile Installation 2103.10.7
American National Standard Specifications for Modified Epoxy Emulsion Mortar/Grout 2103.10.5
American National Standard Specifications for Organic Adhesives for Installation of Ceramic Tile 2103.10.6
American National Standard Specifications for Ceramic Tile 2103.5
Particleboard 2303.1.7, 2303.1.7.1
American National Standard Specifications for Audible Emergency Evacuation Signal 907,5.2.1.3
Safety Glazing Materials Used in Buildings — Safety Performance
Specifications and Methods of Test 2406.1.2, 2406.2, Table 2406.2(2), 2406.3.1, 2407.1,
2407.1.4,1, 2408.2.1, 2408.3, 2409.1, 2409.2, 2409.3.1
II
APA - Engineered Wood Association
4 O 4 7011 South 19th
/^A rV Tacoma, WA 98466
Standard Referenced
reference in code
number Title section number
APA PDS— 04 Panel Design Specification 2306.1
APA PDS
Supplement 1 — 90 Design and Fabrication of Plywood Curved Panels (revised 1995) 2306.1
APA PDS
Supplement 2 — 92 Design and Fabrication of Plywood-lumber Beams (revised 1998) 2306.1
APA PDS
Supplement 3 — 90 Design and Fabrication of Plywood Stressed-skin Panels (revised 1996) 2306.1
APA PDS
Supplement 4 — 90 Design and Fabrication of Plywood Sandwich Panels (revised 1993) 2306.1
2010 CALIFORNIA BUILDING CODE 643
REFERENCED STANDARDS
APA PDS
Supplement 5 — 95
EWS R540— 02
EWS S475— 01
EWS S560— 03
EWS T300— 05
EWS X440— 03
EWS X450— 01
APA^ontinued
Design and Fabrication of All-ply wood Beams (revised 1995) 2306.1
Builders Tips: Proper Storage and Handling of Glulam Beams 2306.1
Glued Laminated Beam Design Tables 2306. 1
Field Notching and Drilling of Glued Laminated Timber Beams 2306.1
Glulam Connection Details 2306.1
Product Guide— <jlulam 2306.1
Glulam in Residential Construction — ^Western Edition 2306.1
APSP
The Association of Pool & Spa Professionals
2111 Eisenhower Avenue
Alexandria, VA 22314
Standard
reference
number
Title
Referenced
in code
section number
ANSI/APSP 7—06
Standard for Suction Entrapment Avoidance in Swimming Pools, Wading Pools, Spas, Hot Tubs and Catch Basins .... 3109.5
ASABE
American Society of Agricultural and Biological Engineers
2950 Niles Road
St. Joseph, MI 49085
Referenced
in code
Title section number
Diaphragm Design of Metal -clad, Post-frame Rectangular Buildings 2306.1
Shallow-post Foundation Design 2306. 1
Design Requirements and Bending Properties for Mechanically Laminated Columns 2306. 1
Standard
reference
number
EP 484.2 (2003)
EP 486. 1(2000)
EP 559 (1997)
ASCE/SEI
American Society of Civil Engineers
Structural Engineering Institute
1801 Alexander Bell Drive
Reston,VA 20191-4400
Standard
Referenced
reference
in code
number
Title
section number
3—91
5—08
6—08
7—05
8—02
19—96
24—05
29—05
32—01
41-06
Structural Design of Composite Slabs 1604.3.3, 2209.2.1
Building Code Requirements for Masonry Structures 1405.6, 1405.6.2, 1405.10, 1604.3.4,
1704.5, 1704.5.1, Table 1704.5.1, 1704.5.2, 1704.5.3,
Table 1704.5.3, 1807.1.6.3.2, 1808.9, 2101.2.2, 2101.2.3,
2101.2.4, 2101.2.5, 2101.2.6, 2103.1.3.6, 2106.1,
2107.1, 2107.2, 2107.3, 2107.4, 2107.5, 2108.1, 2108.2, 2108.3,
2109.1, 2109.1.1, 2109.2, 2109.2.1, 2109.3, 2110.1
Specification for Masonry Structures .
1405.6.1, Table 1704.5.1, Table 1704.5.3, 1807.1.6.3, 2103.8, 2103.11,
2103.12, 2103.13, 2104.1, 2104.1.1, 2104.1.2, 2104.1.3, 2104.2,
2104.3, 2104.4, 2105.2.2.1.1, 2105.2.2.1.2, 2105.2.2.1.3
Minimum Design Loads for Buildings and Other Structures including
Supplements No. 1 and 2, excluding Chapter 14 and Appendix 1 1 A Table 1504.8, 1602.1, 1604.3, 1604.8.2,
1604.10, 1605.1, 1605.2.2, 1605.3.1.2, 1605.3.2, 1607.11.1,
1608.1, 1608.2, 1609.1.1, 1609.1.1.2.1, 1609.1.1.2.2, 1609.1.2, 1609.3, 1609.4.4,
1609.5.1, 1609.5.3, 1609.6, 1609.6.1, 1609.6.1.1, 1609.6.2,Table 1609.6.2(2), 1609.6.3,
1609.6.4.1, 1609.6.4.2, 1611.2, 1612.2, 1612.4, 1613.1, 1613.2,Table 1613.5.3(1), Table 1613.5.3(2),
1613.5.6, 1613.5.6.1, 1613.5.6.2, 1613.6, 1613.6.1, 1613.6.2, 1613.6.3, 1613.6.4, 1613.6.5,
1613.6.6, 1613.6.7, 1613.7, 1702.1, 1705.3.4, 1708.1, 1708.5, 1808.3.1, 1810.3.6.1,
1810.3.9.4, 1810.3.11.2, 1810.3.12, 1908.1.1, 1908.1.2, 1908.1.9, 2205.2.1, 2205.3, 2205.3.1, 2208.1,
Table 2304.6.1, Table 2306.7, Table 2308.10.1, 2404.1, 2505.1, 2505.2, 3404.4, 3404.5
Standard Specification for the Design of Cold-formed Stainless Steel Structural Members 1604.3.3, 2209.1
Structural Applications of Steel Cables for Buildings 2207.1, 2207.2
Hood Resistant Design and Construction 1203.3.2, 1612.4, 1612.5, 3001.2, G103.1, G401.3, G401.4
Standard Calculation Methods for Structural Fire Protection 721.1
Design and Construction of Frost Protected Shallow Foundations 1809.5
Seismic Rehabilitation of Existing Buildings including Supplement No. L 3401.5, 3412A, 34 13 A, 3417.5, 3417.8, 3418,
3419.1,3419.2, 3419.5, 3419.7, 3419.8, 3419.9, 3420, 3421
644
2010 CALiFORNIA BUILDING CODE
REFERENCED STANDARDS
ASME
Standard
Referenced
reference
in code
number
Title
section number
A17.1/CSAB
A18.1— 2005
A90.1— 03
B16.18— 2001
(Reaffirmed 2005)
B 16.22— 2001
(Reaffirmed 2005)
B20. 1—2006
BPE—2009
B3 1.3— 2004
-2007
American Society of Mechanical Engineers
Three Park Avenue
New York, NY 10016-5990
Title
Safety Code for Elevators and Escalators 907.3.3,911.1.5, 1007.4, 1607.8.1, 1613.6.5,3001.2,3001.4,
3002.5, 3003.2, 3007.1, 3008.3, 3008.12, 3008.14.1, 3411.8.2
Safety Standard for Platform Lifts and Stairway Chairlifts 77MJ5.2. 7, 2702.2.6, 3411.8.3
Safety Standard for Belt Manlifts 3001.2
Cast Copper Alloy Solder Joint Pressure Fittings 909.13.1
Wrought Copper and Copper Alloy Solder Joint Pressure Fittings 909.13.1
Safety Standard for Conveyors and Related Equipment 3001.2, 3005.3
Bio-processing Equipment Standard
Process Piping .415.8.6.1
II
II
ASTM
ASTM International
100 Barr Harbor Drive
West Conshohocken, PA 19428-2959
Standard
Referenced
reference
in code
number
Title
section number
A 36/A 36M— 05
A 153/A 153M— 05
A 240/A 240M— 07
A 252—98 (2002)
A 283/A 283M— 03
A 307— 04e01
A416/A416M— 06
A 463/A 463M— 05
A 572/A 572M— 07
A 588/A 588M— 05
A615/A615M— 04a
A 653/A 653M— 07
A 690/A 690M— 07
A 706/A 706M— 05a
A 722/A 722M— 07
A 755/A 755M— 07
A 792/A 792M— 06a
A 875/A 875M— 06
A913/A913M— 04
A 924/A 924M— 07
A 992/A 992M— 06a
B 42— 02e01
B 43—98(2004)
B68— 02
B88— 03
B 101—02
B 209—06
B251— 02e01
Specification for Carbon Structural Steel 1810.3.2.3
Specification for Zinc Coating (Hot-dip) on Iron and Steel Hardware 2304.9.5
Standard Specification for Chromium and Chromium-nickel Stainless Steel Plate,
Sheet and Strip for Pressure Vessels and for General Applications Table 1507.4.3(1)
Specification for Welded and Seamless Steel Pipe Piles 1810.3.2.3
Specification for Low and Intermediate Tensile Strength Carbon Steel Plates 1810.3.2.3
Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength 1911.1
Specification for Steel Strand, Uncoated Seven-wire for Prestressed Concrete 1810.3.2.2
Standard Specificafion for Steel Sheet, Aluminum-coated, by the Hot-dip Process Table 1507.4.3(2)
Specification for High-strength Low-alloy Columbium-vanadium Structural Steel 1810.3.2.3
Specification for High-strength Low-alloy Structural Steel with 50 ksi (345 MPa)
Minimum Yield Point to 4 inches (100 mm) Thick 1810.3.2.3
Specification for Deformed and Plain Billet-steel Bars for Concrete Reinforcement 1708.2, 1810.3.10.2
Specification for Steel Sheet, Zinc-coated Galvanized or Zinc-iron Alloy-coated
Galvannealed by the Hot-dip Process Table 1507.4.3(1), Table 1507.4.3(2), 2304.9.5.1
Standard Specification for High-strength Low-alloy Nickel, Copper, Phosphorus Steel H-piles and
Sheet Piling with Atmospheric Corrosion Resistance for Use in Marine Environments 1810.3.2.3
Specification for Low-alloy Steel Deformed and Plain Bars for
Concrete Reinforcement Table 1704.3, 1704.4.1, 2107.4, 2108.3
Specification for Uncoated High-strength Steel Bar for Prestressing Concrete 1810.3.10.2
Specification for Steel Sheet, Metallic-coated by the Hot-dip Process and Prepainted by the
Coil-coating Process for Exterior Exposed Building Products Table 1507.4.3(1), Table 1507.4.3(2)
Specification for Steel Sheet, 55% Aluminum-zinc Alloy-coated by the
Hot-dip Process Table 1507.4.3(1), Table 1507.4.3(2)
Standard Specification for Steel Sheet Zinc-5 percent. Aluminum Alloy-coated by the Hot-dip Process Table 1507.4.3(2)
Specification for High-strength Low-alloy Steel Shapes of Structural Quality,
Produced by Quenching and Self-tempering Process (QST) 1810.3.2.3
Standard Specification for General Requirements for Steel Sheet,
Metallic-coated by the Hot-dip Process Table 1507.4.3(1)
Standard Specification for Structural Shapes 1810.3.2.3
Specification for Seamless Copper Pipe, Standard Sizes 909.13.1
Specification for Seamless Red Brass Pipe, Standard Sizes .909.13.1
Specification for Seamless Copper Tube, Bright Annealed (Metric) 909.13.1
Specification for Seamless Copper Water Tube 909.13.1
Specification for Lead-coated Copper Sheet and Strip for Building Construction Table 1404.5.3,
Table 1507.2.9.2, Table 1507.4.3(1)
Specification for Aluminum and Aluminum Alloy Steel and Plate Table 1507.4.3(1)
Specification for General Requirements for Wrought Seamless Copper and Copper-alloy Tube 909.13.1
2010 CALIFORNIA BUILDING CODE
645
REFERENCED STANDARDS
B 280— 03
B370--03
B 695—04
C5— 03
C 22/C 22M— 00 (2005)e01
C 27—98 (2002)
C 28/C 28M— 00 (2005)
C31/C31M-06
C33— 03
C 34—03
C 35—01(2005)
C 36/C 36M— 03
C 37/C 37M— 01
C55— 06e01
C56— 05
C 59/C 59M— 00 (2006)
C 61/C 61M— 00 (2006)
C62— 05
C 67—07
C73— 05
C 79— 04a
C 90— 06b
C91— 05
C 94/C 94M— 07
C 126—99 (2005)
C 140— 07
I I C 144-04
C 150— 07
C 172—04
C 199—84 (2005)
C 206— 03
C 208—95 (2001)
C 212—00 (2006)
C 216— 07
C 270—07
I I C 289— 07
C 315— 07
C317/C317M— 00(2005)
C 330— 05
C 331—05
C 406— 06e01
C 442/C 442M— 04
C 472—99 (2004)
C 473— 06a
C 474— 05
C 475—05
C 503—05
C 514—04
C 516—02
C 547—06
C 549—06
C 552—03
C 557— 03e01
C 568—03
C 578—07
C 587— 04
C 588/C 588M-01
ASTM^continued
Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service 909.13.1
Specification for Cold-rolled Copper Sheet and
Strip for Building Construction 1404.5.2, Table 1507.2.9.2, Table 1507.4.3(1)
Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel 2304.9.5.1, 2304.9,5.3
Specification for Quicklime for Structural Purposes Table 2507.2
Specification for Gypsum Table 2506.2
Specification for Standard Classification of Fireclay and High-alumina Refractory Brick 21 1 1.5
Specification for Gypsum Plasters Table 2507.2
Practice for Making and Curing Concrete Test Specimens in the Field Table 1704.4
Specification for Concrete Aggregates 721.3.1.4, 721.4.1.1.3
Specification for Structural Clay Load-bearing Wall Tile 2103.2
Specification for Inorganic Aggregates for Use in Gypsum Plaster Table 2507.2
Specification for Gypsum Wallboard Figure 721.5.1(2), Figure 721.5.1(3), Tkble 2506.2
Specification for Gypsum Lath Table 2507.2
Specification for Concrete Building Brick Table 721.3.2, 2103.1, 2105.2.2.1.2
Specification for Structural Clay Nonload Bearing Tile 2103.2
Specification for Gypsum Casting and Molding Plaster Table 2507.2
Specification for Gypsum Keene's Cement Table 2507.2
Specification for Building Brick (Solid Masonry Units Made from Clay or Shale) 1807.1.6.3, 2103.2, 2105.2.2.1.1
TestMethodsof Sampling and Testing Brick and Structural Clay Tile 721.4.1.1.1,2109.3.1.1
Specification for Calcium Silicate Face Brick (Sand-lime Brick) Table 721.3.2, 2103.1
Specification for Treated Core and Nontreated Core Gypsum Sheathing Board Table 2506.2
Specification for Loadbearing Concrete Masonry Units Table 721.3.2, 1807.1.6.3, 2103.1
Specification for Masonry Cement Table 2507.2
Specification for Ready-mixed Concrete 1 10.3.1
Specification for Ceramic Glazed Structural Clay Facing Tile, Facing Brick and Solid Masonry Units 2103.2
Test Method Sampling and Testing Concrete Masonry Units and Related Units 721.3.1.2
Standard Specification for Aggregate for Masonry Mortar 2103A.8
Specification for Portland Cement Table 2507.2
Practice for Sampling Freshly Mixed Concrete Table 1704.4
Test Method for Pier Test for Refractory Mortars 2111.5,2111.8,2113.12
Specification for Finishing Hydrated Lime Table 2507.2
Specification for Cellulosic Fiber Insulating Board Table 1508.2, 2303.1.5
Specification for Structural Clay Facing Tile 2103.2
Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale) 1807.1.6.3, 2103.2, 2105.2.2.1.1
Specification for Mortar for Unit Masonry 2103.8
Standard Test Method for Potential Alkali- Silica Reactivity of Aggregates 1916.1,3, 1903A,3
Specification for Clay Rue Liners and Chimney Pots 2111.8, 21 13.1 1, Table 21 13.16(1)
Specification for Gypsum Concrete 1914.1
Specification for Lightweight Aggregates for Structural Concrete 721.1.1
Specification for Lightweight Aggregates for Concrete Masonry Units 721.3.1.4, 721.4.1.1.3
Specification for Roofing Slate 1507.7.5
Specification for Gypsum Backing Board andCoreboard and Gypsum Shaftliner Board Table 2506.2
Specification for Standard Test Methods for Physical Testing of Gypsum,
Gypsum Plasters and Gypsum Concrete Table 2506.2
Test Method for Physical Testing of Gypsum Panel Products Table 2506.2
Test Methods for Joint Treatment Materials for Gypsum Board Construction. Table 2506.2
Specification for Joint Compound and Joint Tape for Finishing Gypsum Wallboard Table 2506.2
Specification for Marble Dimension Stone (Exterior) 2103.4
Specification for Nails for the Application of Gypsum Board Table 720. 1 (2), Table 720. 1 (3),
Table 2306.7, Table 2506.2
Specifications for Vermiculite Loose Fill Thermal Insulation 721.3.1.4, 721.4.1.1.3
Specification for Mineral Fiber Pipe Insulation Table 720.1(2), Table 720.1(3)
Specification for Perlite Loose Fill Insulation 721.3.1.4, 721.4.1.1.3
Standard Specification for Cellular Glass Thermal Insulation Table 1508.2
Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing Table 2506.2
Specification for Limestone Dimension Stone 2103.4
Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation Table 1508.2
Specification for Gypsum Veneer Plaster Table 2507.2
Specification for Gypsum Base for Veneer Plasters Table 2507.2
646
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
C 595—07
C 615—03
C 616— 03
C 618-08a
C 629—03
C 630/C 630M— 03
C 631— 95a (2004)
C 635—06
C 636/C 636M— 06
C 645— 07
C 652— 05a
C 728—05
C744--05
C754--04
C836--06
C 840— 07
C 841—03
C 842—05
C 843—99 (2006)
C 844— 04
C 847—06
C 887—05
C 897—05
C 920— 05
C 926— 98a (2005)
C931/C931M— 04
C 932—06
C 933—05
C 946— 91(2001)
C 954— 04
C 955—06
C 956— 04
C 957—06
C 960—04
C 989-09
C 1002—04
C 1007—04
C 1019—05
C 1029— 05a
C 1032—06
C 1047—05
C 1063—06
C 1088— 07a
C 1167—03
C1177/C1177M— 06
C 1178/C1178M— 06
C 1186—07
C 1261—07
C 1278/C 1278M— 06
ASTM— continued
Specification for Blended Hydraulic Cements Table 2507.2
Specification for Granite Dimension Stone 2103.4
Specification for Quartz Dimension Stone 2103.4
Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolanfor Use in Concrete 1903A.3, 1916.1.3
Specification for Slate Dimension Stone 2103.4
Specification for Water-resistant Gypsum Backing Board Table 2506.2
Specification for Bonding Compounds for Interior Gypsum Plastering Table 2507.2
Specification for the Manufacture, Performance and Testing of Metal Suspension
Systems for Acoustical Tile and Lay-in Panel CeiUngs 808.1.1, 2506.2.1, H107.1.1
Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels 808.1.1
Specification for Nonstructural Steel Framing Members Table 2506.2, Table 2507.2
Specification for Hollow Brick (Hollow Masonry Units Made from Clay or Shale) 1807.1.6.3,
2103.2,2105.2.2.1.1
Standard Specification for Perlite Thermal Insulation Board Table 1508.2
Specification for Prefaced Concrete and Calcium Silicate Masonry Units Table 721.3.2, 2103.1
Specification for Installation of Steel Framing Members to Receive Screw-attached
Gypsum Panel Products Table 2508.1, Table 2511.1.1
Specification for High-solids Content, Cold Liquid-applied Elastomeric
Waterproofing Membrane for Use with Separate Wearing Course 1507.15.2
Specification for Application and Finishing of Gypsum Board Table 2508.1, 2509.2
Specification for Installation of Interior Lathing and Furring Table 2508.1, Table 2511.1.1
Specification for Application of Interior Gypsum Plaster Table 251 1.1.1, 2511.3, 2511.4
Specification for Application of Gypsum Veneer Plaster Table 251 1.1.1
Specification for Application of Gypsum Base to Receive Gypsum Veneer Plaster Table 2508.1
Specification for Metal Lath Table 2507.2
Specification for Packaged, Dry Combined Materials for Surfece Bonding Mortar 1805.2.2, 2103.9
Specification for Aggregate for Job-mixed Portland Cement-based Plaster Table 2507.2
Standard for Specification for Elastomeric Joint Sealants Table 2506.2
Specification for Application of Portland Cement-based Plaster. . . 2109.3.4.6, 2510.3, Table 2511.1.1, 2511.3, 2511.4, 2512.1,
2512.1.2, 2512.2, 2512.6, 2512.8.2, 2512.9, 2513.7
Specification for Exterior Gypsum Soffit Board Table 2506.2
Specification for Surface-applied Bonding Compounds Agents for Exterior Plastering Table 2507.2
Specification for Welded Wire Lath Table 2507.2
Specificafion for Practice for Construction of Dry-stacked, Surface-bonded Walls 2103.9, 2109.2.2
Specification for Steel Drill Screws for the Apphcation of
Gypsum Panel Products or Metal Plaster Bases to
Steel Studs from 0.033 inch (0.84 mm) to 0.1 12 inch (2.84 mm) in Thickness Table 2506.2, Table 2507.2
Standard Specification for Load-bearing Transverse and Axial Steel Studs,
Runners Tracks, and Bracing or Bridging, for Screw Application of
Gypsum Panel Products and Metal Plaster Bases Table 2506.2, Table 2507.2
Specification for Installation of Cast-in-place Reinforced Gypsum Concrete 1914.1
Specification for High-solids Content, Cold Liquid-applied Elastomeric
Waterproofing Membrane with Integral Wearing Surface 1507.15.2
Specification for Predecorated Gypsum Board Table 2506.2
Standard Specification for Slag Cement for Use in Concrete and Mortars 1903A.3, 1916.1.3
Specification for Steel Self-piercing Tapping Screws for the Application of
Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs Table 2506.2, Table 2507.2
Specification for Installation of Load Bearing (Transverse and Axial) Steel Studs and
Related Accessories Table 2508.1, Table 2511.1.1
Test Method of Sampling and Testing Grout 2105.2.2.1.1, 2105.2.2.1.2, 2105.2.2.1.3
Specification for Spray -applied Rigid Cellular Polyurethane Thermal Insulation 1507.14.2
Specification for Woven Wire Plaster Base Table 2507.2
Specification for Accessories for Gypsum Wall board and Gypsum Veneer Base Table 2506.2, Table 2507.2
Specification for Installation of Lathing and Furring to Receive Interior and
Exterior Portland Cement-based Plaster 2109.3.4.6, 2510.3, Table 2511.1.1, 2512.1.1
Specification for Thin Veneer Brick Units Made from Clay or Shale Table 720. 1(2), 2103.2
Specification for Clay Roof Tiles 1507.3.4
Specification for Glass Mat Gypsum Substrate for Use as Sheathing Table 2506.2
Specification for Coated Mat Water-resistant Gypsum Backing Panel Table 2506.2, 2509.2
Specification for Flat Nonasbestos Fiber Cement Sheets 1404.10
Specification for Firebox Brick for Residential Fireplaces 21 1 1.5, 21 1 1.8
Specification for Fiber-reinforced Gypsum Panels Table 2506.2
2010 CALIFORNIA BUILDING CODE
647
REFERENCED STANDARDS
C 1280—04
C 1283—07
C 1288—99 (2004)
C 1289—07
C 1314—07
C 1325—04
C 1328—05
C 1386-^7
C 1395/C 1395M— 06a
C 1396M— 06a
C 1405—07
C 1492—03
C 1567-08
C 1586-05
C 1629/C 1629M— 06
C 1658/C 1658M— 06
D 25—99 (2005)
D41— 05
D 43—00 (2006)
D56— 05
D 86— 07a
D93— 07
D 225—04
D 226— 06
D 227—03
D 312—00 (2006)
D 422—63 (2002)e01
D 448— 03a
D 450—07
D 635—06
D1143/D1143M— 07
D 1227—95 (2007)
D 1557— 02e01
D 1586—99
D 1761—06
D 1863—05
D1929— 96(200i)e01
D 1970—01
D 2166—06
D 2178—04
D 2216—05
D 2487—06
D 2626—04
D 2822—05
D 2823—05
D 2843—99 (2004)e01
D 2850— 03a
D 2898—04
3019-94(2007)
D 3161— 06
D 3200—74 (2005)
ASTM— continued
Specification for Application of Gypsum Sheathing Table 2508.1, 2508.2
Practice for Installing Clay Flue Lining 21 13.12
Standard Specification for Discrete Nonasbestos Fiber-cement Interior Substrate Sheets 2509.2
Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board Table 1508.2
Test Method for Compressive Strength of Masonry Prisms 2105.2.2.2.2, 2105.3.1, 2105.3.2
Standard Specification for Nonasbestos Fiber-mat Reinforced Cement Interior Substrate Sheets 2509.2
Specification for Plastic (Stucco Cement) Table 2507.2
Specification for Precast Autoclaved Aerated Concrete (AAC) Wall Construction Units 2102.1, 2103.3, 2105.2.2.1.3
Specification for Gypsum Ceiling Board Table 2506.2
Specification for Gypsum Board Table 2506.2
Standard Specification for Glazed Brick (Single Fired, Solid Brick Units) 2103.2
Standard Specification for Concrete Roof Tile 1507.3.5
Standard Test Method for Determining the Potential Alkali-Silica Reactivity
of the Cementicious Materials and Aggregate 1903A.3, 1916.13
Standard Guide for Quality Assurance of Mortars 2I05A.2.2.1.4, 2114,9.1
Standard Classification for Abuse-resistant Nondecorated Interior Gypsum Panel
Products and Fiber-reinforced Cement Panels 403.2.3.1, 403.2.3.2, 403.2.3.4
Standard Specification for Glass Mat Gypsum Panels 1810.3.2.4, Table 2506.2
Specification for Round Timber Piles 2303.1.1 1
Specification for Asphalt Primer Used in Roofing, Dampproofing and Waterproofing Table 1507.10.2
Specification for Coal Tar Primer Used in Roofing, Dampproofing and Waterproofing Table 1507.10.2
Test Method for Flash Point By Tag Closed Tester 307.2
Test Method for Distillation of Petroleum Products at Atmospheric Pressure 307.2
Test Method for Flash Point By Pensky-Martens Closed Cup Tester 307.2
Specification for Asphalt Shingles (Organic Felt) Surfaced with Mineral Granules 1507.2.5
Specification for Asphalt-saturated Organic Felt Used in Roofing and Waterproofing 1404.2, 1507.2.3, 1507.3.3,
1507.5.3, 1507.6.3, 1507.7.3, Table 1507.8,
1507.8.3, 1507.9.3, 1507.9.5, Ihble 1507.10.2
Specification for Coal-tar-saturated Organic Felt Used in Roofing and Waterproofing Table 1507.10.2
Specification for Asphalt Used in Roofing Table 1507.10.2
Test Method for Particle-size Analysis of Soils 1803.5.3
Standard Classification for Sizes of Aggregate for Road and Bridge Construction 1507.12.3, 1507.13.3
Specification for Coal-tar Pitch Used in Roofing, Dampproofing and Waterproofing Table 1507.10.2
Test Method for Rate of Burning and/or Extent and Time of Burning of
Self-supporting Plastics in a Horizontal Position 2606.4, H107.1.1
Test Method for Piles Under Static Axial Compressive Load 1810.3.3.1.2
Specification for Emulsified Asphalt Used as a Protective Coafing for Roofing Table 1507.10.2, 1507.15.2
Test Method for Laboratory Compaction Characteristics of Soil Using
Modified Effort [56,000 ft-lb/ft^ (2,700 KN m/m^)] 1704.7, 1804.5, J107.6
Specification for Penetration Test and Split-barrel Sampling of Soils 1613.5.5
Test Method for Mechanical Fasteners in Wood 1716.1.1, 1716.1.2, 1716.1.3
Specification for Mineral Aggregate Used on Built-up Roofs Table 1507.10.2
Test Method for Determining Ignition Properties of Plastics 402.16.4, 406.5.3, 1407.1 1.2.1, 2606.4
Specification for Self-adhering Polymer Modified Bituminous Sheet Materials
Used as Steep Roof Underlayment for Ice Dam Protection 1507.2.4, 1507.2.9.2, 1507.3.9,
1507.5.7, 1507.8.8, 1507.9.9
Test Method for Unconfined Compressive Strength of Cohesive Soil 1613.5.5
Specification for Asphalt Glass Felt Used in Roofing and Waterproofing Table 1507.10.2
Test Method for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass 1613.5.5
Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System) Table 1610.1, 1802.3.1
Specification for Asphalt Saturated and Coated Organic Felt Base Sheet Used in Roofing 1507.3.3, Table 1507.10.2
Specification for Asphalt Roof Cement Table 1507. 10.2
Specification for Asphalt Roof Coatings Table 1507.10.2
Test for Density of Smoke from the Burning or Decomposition of Plastics 2606.4
Test Method for Unconsolidated, Undrained Triaxial Compression Test on Cohesive Soils 1613.5.5
Test Methods for Accelerated Weathering of Fire-retardant-treated Wood for Fire Testing 1505.1, 2303.2.4, 2303.2.6
Specification for Lap Cement Used with Asphalt Roll Roofing, Nonfibered, Asbestos Fibered and
Nonasbestos Fibered Table 1507.10.2
Test Method for a Wind Resistance of Asphalt Shingles (Fan Induced Method) 1507.2.7.1, Table 1507.2.7.1(2)
Standard Specification and Test Method for Establishing Recommended Design Stresses for
Round Timber Construction Poles 2303. 1 . 1 1
648
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
D 3201—07
D 3278— (2004)e01
D 3462—07
D 3468—99 (2006)e01
D 3679— 06a
D 3689— 90(1995)
D 3737—07
D 3746—85 (2002)
D 3747—79 (2007)
D 3909— 97b (2004)e01
D 3957—06
D 4022—07
D 4272—03
D 43 18— 05
D 4434—06
D 4479—07
D 4586— 00
D 4601— 04
D 4637—04
D 4829—07
D4869— 05e01
D 4897— 01
D 4945—00
D 4990— 97a (2005)e01
D 5019—07
D 5055—05
D 5456— 05a
D 5516— 03
D 5643--06
D 5664—02
D 5665— 99a (2006)
D 5726—98 (2005)
D6083— O5e01
D 6162— OOA
D 6163— OOeOl
D 6164— 05
D 6222^02e01
D 6223—02
D 6298—05
D 6305— O2e01
D 6380—03
D 6509—00
D 6694—07
D 6754—02
D 6757—07
D 6841—03
D 6878— 06a
D 6947—07
ASTM— continued
Test Method for Hygroscopic Properties of Fire-retardant- treated Wood and Wood-based Products 2303.2.7
Test Methods for Flash Point of Liquids by Small Scale Closed-cup Apparatus 307.2
Specification for Asphalt Shingles Made from Glass Felt and Surfeced with Mineral Granules 1507.2.5
Specification for Liquid-applied Neoprene and Chlorosulfonated Polyethylene Used in
Roofing and Waterproofing 1507. 15.2
Specification for Rigid Poly [Vmyl Chloride (PVC) Siding] 1404.9, 1405.14
Method for Testing Individual Piles Under Static Axial Tensile Load 1810.3.3.1.5
Practice for Establishing Allowable Properties for Structural Glued Laminated Timber (Glulam) 2303.1.3
Test Method for Impact Resistance of Bituminous Roofing Systems 1504.7
Specification for Emulsified Asphalt Adhesive for Adhering Roof Insulation Table 1507.10.2
Specification for Asphalt Roll Roofing (Glass Felt) Surfaced with Mineral Granules . . . 1507.2.9.2, 1507.6.5, Table 1507.10.2
Standard Practices for Establishing Stress Grades for Structural Members Used in Log Buildings 2303.1.10
Specification for Coal Tar Roof Cement, Asbestos Containing Table 1507.10.2
Test Method for Total Energy Impact of Plastic Films by Dart Drop 1504.7
Test Methods for Liquid Limit, Plastic Limit and Plasticity Index of Soils 1613.5.5, 1803.5.3
Specification for Poly (Vinyl Chloride) Sheet Roofing 1507.13.2
Specification for Asphalt Roof Coafings — Asbestos-free Table 1507.10.2
Specification for Asphalt Roof Cement — Asbestos-free Table 1507.10.2
Specification for Asphalt-coated Glass Fiber Base Sheet Used in Roofing Table 1507.10.2
Specification for EPDM Sheet Used in Single-ply Roof Membrane 1507.12.2
Test Method for Expansion Index of Soils 1803.5.3
Specificadon for Asphalt-saturated (Organic Felt) Underlayment Used in
Steep Slope Roofing 1507.2.3, 1507.5.3, 1507.6.3, 1507.7.3, 1507.8.3, 1507.9.3
Specification for Asphalt-coated Glass Fiber Venting Base Sheet Used in Roofing Table 1507.10.2
Test Method for High-strain Dynamic Testing of Piles 1810.3.3.1.2
Specification for Coal Tar Glass Felt Used in Roofing and Waterproofing Table 1507,10.2
Specification for Reinforced Nonvulcanized Polymeric Sheet Used in Roofing Membrane 1507,12.2
Specification for EstabUshing and Monitoring Strucmral Capacities of Prefebricated Wood I-joists 2303.1.2
Specification for Evaluation of Structural Composite Lumber Products 2303.1.9
Test Method of Evaluating the Flexural Properties of Fire-retardant-treated
Softwood Plywood Exposed to the Elevated Temperatures 2303.2.5.1
Specification for Coal Tar Roof Cement, Asbestos-free Table 1507.10.2
Test Methods for Evaluating the Effects of Fire-retardant Treatment and
Elevated Temperatures on Strength Properties of Fire-retardant-treated Lumber 2303.2.5.2
Specification for Thermoplastic Fabrics Used in Cold-applied Roofing and Waterproofing Table 1507.10.2
Specification for Thermoplastic Fabrics Used in Hot-applied Roofing and Waterproofing Table 1507.10.2
Specification for Liquid Applied Acrylic Coating Used in Roofing Table 1507.10.2, 1507.15.2
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous
Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements 1507.11.2
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous
Sheet Materials Using Glass Fiber Reinforcements 1507.1 1.2
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous
Sheet Metal Materials Using Polyester Reinforcements 1507.11.2
Specification for Atactic Polypropylene (APP) Modified Bituminous
Sheet Materials Using Polyester Reinforcements 1507.1 1.2
Specification for Atactic Polypropylene (APP) Modified Bituminous
Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements 1507. 1 1.2
Specification for Fiberglass Reinforced Styrene-butadiene-styrene (SBS)
Modified Bimminous Sheets with a Factory Applied Metal Surface 1507.11.2
Practice for Calculating Bending Strength Design Adjustment Factors for Fire-retardant-treated
Plywood Roof Sheathing 2303.2.5.1
Standard Specification for Asphah Roll Roofing (Organic) Felt 1507.2.9.2, 1507.3.3, 1507.6.5
Standard Specification for Atactic Polypropylene (APP) Modified Bituminous base
Sheet Materials Using Glass Fiber Reinforcements 1507.1 1.2
Standard Specification for Liquid-applied Silicone Coating Used in Spray Polyurethane Foam Roofing 1507.15.2
Standard Specification for Ketone Ethylene Ester Based Sheet Roofing 1507.13.2
Standard Specification for Inorganic Underlayment for Use with Steep Slope Roofing Products 1507.2.3
Standard Practice for Calculating Design Value Treatment Adjustment Factors for Fire-retardant-treated Lumber . . 2303.2.5.2
Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing 1507.13.2
Standard Specification for Liquuid Applied Moisture Cured Polyurethane Coating
Used in Spray Polyurethane Foam Roofing System 1507.15.2
2010 CALIFORNIA BUILDING CODE
649
REFERENCED STANDARDS
D7158--07
E84--07
£90-04
E 96/E 96M— 05
E 108— 07a
El 19— 07
E 136— 04
E 330— 02
E 331—00
E 492— 04
I E 580— 08
E 605—93 (2006)
E 648-04
I E662-09
E 681—04
E 736—00 (2006)
E 814— 06
E 970— 00
E 1300— 04e01
E 1354— 04a
E 1592—01
E 1602—03
E 1886—06
E 1966—01
E 1996—06
E 2072—04
E 2273—03
E2307— 04e01
E 2404— 07a
E 2568—07
E 2570—07
E 2573—07
F 547—01
F 1346—91 (2003)
F 1667—05
ASTM— continued
Standard Test Method for Wind Resistance of Sealed Asphalt Shingles
(Uplift Force/Uplift Resistance Method) 1507.2.7.1, Table 1507.2.7.1(1)
Test Methods for Surface Burning Characteristics of Building Materials 402.1 1, 402.16.4, 406.5.3,
703.4.2, 719.1, 719.4, 802.1, 803.1.1, 803.9, 806.5,
1407.9, 1407.10.1, 2303.2, 2603.3, 2603.4.1.13, 2603.5.4, 2604.2.4, 2606.4, 3105.4, D102.2.8
Test Method for Laboratory Measurement of Airborne Sound Ti-ansmission Loss of
Building Partitions and Elements 1207.2, 1207.2.1
Test Method for Water Vapor Transmission of Materials 202, 1203.2
Test Methods for Fire Tests of Roof Coverings 1505.1,2603.6,2610.2,2610.3
Test Methods for Fire Tests of Building Construction and Materials 703.2, 703.2.1, 703.2.3, 703.3,
703.5, 704.12, 705.7, 705.8.5, 707.6, 712.3.2,
713.3.1, 713.4,1.1, 714.1, 715,2, 715.4.5, 716.5.2, 716.5.3, 716.6.1,
716.6.2.1, Table 720.1(1). 1407.10.2, 2103.2, 2603.4, 2603.5.1
Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C 703:4.1
Test Method for Structural Performance of Exterior Wmdows, Curtain Walls and Doors by
Uniform Static Air Pressure Difference 1715.5.2
Test Method for Water Penetration of Exterior Windows, Skylights, Doors and Curtain Walls by
Uniform Static Air Pressure Difference 1403.2
Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-ceiling
Assemblies Using the Tapping Machine 1207.3
Standard Practice for Installation of Ceiling Suspension Systems for Acoustical Tile and
Lay-in Panels in Areas Subject to Earthquake Ground Motions 1615.10.13, 161 5A, 1.16
Test Method for Thickness and Density of Sprayed Fire-resistive Material (SFRM)
Applied to Strucmral Members 1704.12.4.1, 1704.12.4.2,
1704.12.4.3,1704.12.5
Standard Test Method for Critical Radiant Flux of Floor Covering Systems
Using a Radiant Heat Energy Source 804.4,1, 804.4.2
Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials 804.4.1, 804.4.2
Test Methods for Concentration Limits of Flammability of Chemical Vapors and Gases 307.2
Test Method for Cohesion/Adhesion of Sprayed Fire-resistive Materials Applied to
Structural Members 704.13.2, 1704.12.6
Test Method of Fire Tests of Through-penetration Firestops 702.1, 713.3.1.2, 713.3.2, 713.4.1.1.2
Test Method for Critical Radiant Flux of Exposed Attic Floor Insulation Using ^
a Radiant Heat Energy Source 719.3.1
Practice for Determining Load Resistance of Glass in Buildings 2404,1, 2404.2, 2404.3.1,
2404.3.2, 2404.3.3, 2404.3.4, 2404.3.5
Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products
Using an Oxygen Consumption Calorimeter 402. 12. 1
Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by
Uniform Static Air Pressure Difference 1504.3.2
Guide for Construction of Solid Fuel-burning Masonry Heaters 21 12.2
Test Method for Performance of Exterior Wmdows, Curtain Walls, Doors and
Storm Shutters Impacted by Missiles and Exposed to Cyclic Pressure Differentials 1609.1.2
Test Method for Fire-resistant Joint Systems 702.1, 714.3
Specification for Performance of Exterior Windows, Glazed Curtain Walls,
Doors and Impact Protective Systems Impacted by Windbome Debris in Hurricanes 1609.1.2, 1609.1.2.1
Standard Specification for Photoluminescent (Phosphorescent) Safety Markings 1024.4
Standard Test Method for Determining the Drainage Efficiency of Exterior Insulation and
Finish Systems (EIFS) Clad Wall Assemblies 1408.4.1
Standard Test Method for Determining Fke Resistance of Perimeter Fire Barrier Systems
Using Intermediate-scale, Multistory Test Apparatus 714.4
Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Vinyl Wall or
Ceiling Coverings to Assess Surface Burning Characteristics 803.1.4
Standard Specification for PB Exterior Insulation and Finish Systems (EIFS) 1408.2
Standard Test Method for Evaluating Water-resistive Barrier (WRB) Coatings Used
Under Exterior Insulation and Finish Systems (EIFS) for EIFS with Drainage 1408.4.1.1, 1704.12.1
Standard Practice for Specimen Preparation and Mounting of Site-febricated Stretch
Systems to Assess Surface Burning Characteristics 803.9
Terminology of Nails for Use with Wood and Wood-based Materials Table 2506.2
Performance Specification for Safety Covers and Labeling Requirements for All Covers for
Swimming Pools, Spas and Hot Ibbs 3109.4, 3109.4.1.8
Specification for Driven Fasteners: Nails, Spikes and Staples Table 720.1(2), Table 720.1(3),
1507.2.6, 2303.6, Table 2506.2
650
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
F 2006—00 (2005)
F 2090— Ola (2007)
F 2200—05
G 152—06
G 154—05
G 155— 05a
ASTM— continued
Standard/Safety Specification for Window Fall Prevention Devices for
Nonemergency Escape (Egress) and Rescue (Ingress) \Mndows 1405.13.2
Specification for Window Fall Prevention Devices with Emergency Escape (Egress) Release Mechanisms 1405.13.2
Standard Specification for Automated Vehicular Gate Construction 31 10.3
Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials 1504.6
Practice for Operating Fluorescent Light Apparatus for UV Exposure of Nonmetallic Materials 1504.6
Practice for Operating Xenon Arc Light Apparatus for Exposure of Nonmetallic Materials 1504.6
AWCI
Association of the Wall and Ceiling Industry
513 West Broad Street, Suite 210
Falls Church, VA 22046
Standard
reference
number
Title
Referenced
in code
section number
12-B— 98
Technical Manual 12-B Standard Practice for the Testing and Inspection of
Field Applied Thin Film Intumescent Fire-resistive Materials; an Annotated Guide, First Edition .
. 1704.13
AWPA
Standard
Referenced
reference
in code
number
Title
section number
CI— 03
M4— 06
Ul— 07
American Wood Protection Association
P.O. Box 361784
Birmingham, AL 35236-1784
All Timber Products — Preservative Treatment by Pressure Processes 1505.6
Standard for the Care of Preservative-treated Wood Products 1810.3.2.4.1, 2303.1.8
USE CATEGORY SYSTEM: User Specification for Treated Wood Except Section 6,
Commodity Specification H 1403.5, Table 1507.9.6,
1807.1.4, 1807.3.1, 1809.12, 1810.3.2.4.1, 2303.1.8,
2304. 1 1 .2, 2304. 1 1 .4, 2304. 1 1 .6, 2304. 1 1 .7
AWS
Standard
Referenced
reference
in code
number
Tide
section number
Dl A— 08
B1.3— 08
DL4— 05
DL8-09
QCl-06
American Welding Society
550 N.W. LeJeune Road
Miami, FL 33126
Structural Welding Code— Steel Table 1704.3, 17043.1.1, 1704A.3.1.4
Structural Welding Code— Sheet Steel . .Table 1704.3, 1704.3.1.2
Structural Welding Code— Reinforcing Steel ' Table 1704.3, 1704.3.1.3, Ikble 1704.4, 2107A.4, 2107A.7
Structural Welding Code - Seismic Supplement 1704A.3.1.4, 2204A.1.L 2204A.1.3, 2211.1
Standard for AWS Certification of Welding Inspectors 1704A.3.L4
BHMA
Builders Hardware Manufacturers' Association
355 Lexington Avenue, 17th Floor
New York, NY 10017-6603
Standard
reference
number
Title
Referenced
in code
section number
A 156.10—06
A 156.19—02
Power Operated Pedestrian Doors
Standard for Power Assist and Low Energy Operated Doors .
.1008.1.4.2, 1133B.2.3.2, 1133B.2.5
. 1008. K4.2, 1133B.2.3.2, 1133B.2.5
2010 CALIFORNIA BUILDING CODE
651
REFERENCED STANDARDS
CGSB
37-GP-52M(1984)
37-GP-56M (1980)
CAN/CGSB 37.54—95
Canadian General Standards Board
Place du Portage 111, 6B1
1 1 Laurier Street
Gatlneau, Quebec, Canada KIA 1G6
Title
Roofing and Waterproofing Membrane, Sheet Applied, Elastomeric 1504.7, 1507.12.2
Membrane, Modified, Bituminous, Prefabricated and Reinforced for
Roofing — with December 1985 Amendment 1507.1 1.2
Polyvinyl Chloride Roofing and Waterproofing Membrane 1507.13.2
Standard
Referenced
reference
in code
number
Title
section number
CPA
Composite Panel Association
19465 Deerfield Avenue, Suite 306
Leesburg,VA 20176
Standard
reference
number
Title
Referenced
in code
section number
ANSI A135.4— 2004
Basic Hardboard
1404.3.1, 2303.1.6
ANSI A135.5— 2004
ANSI A135.6— 1998
Prefinished Hardboard Paneling
Hardboard Siding
2303.1.6, 2304.6.2
1404.3.2, 2303.1.6
CPSC
Standard
Referenced
reference
in code
number
Title
section number
16 CFR Part 1201(1977)
16 CFR Part 1209 (1979)
16 CFR Part 1404 (1979)
16 CFR Part 1500 (1991)
16 CFR Part 1500.44 (2001)
16 CFR Part 1507 (2001)
16 CFR Part 1630 (2000)
Consumer Product Safety Commission
4330 East West Highway
Bethesda, MD 20814-4408
Title
Safety Standard for Architectural Glazing Material 2406.2, Table 2406.2(1), 2406.3.1, 2407.1,
2407.1.4.1, 2408.2.1, 2408.3, 2409.1, 2409.2, 2409.3.1
Interim Safety Standard for Cellulose Insulation 719.6
Cellulose Insulation 719.6
Hazardous Substances and Articles; Administration and Enforcement R^ulations 307.2
Method for Determining Extremely Flammable and Flammable Solids 307.2
Fireworks Devices 307.2
Standard for the Surface Flammability of Carpets and Rugs 804.4. 1
CSA
Canadian Standards Association
5060 Spectrum Way
Mississauga, Ontario Canada L4W 5N6
Standard
reference
number
Title
Referenced
in code
section number
101/I.S.2/A440— 08
Specifications for Windows, Doors and Unit Skylights 1715.5.1, 2405.5
CSSB
Cedar Shake and Shingle Bureau
PO. Box 1178
Sumas,WA 98295-1 178
Standard
reference
number
Title
Referenced
in code
section number
CSSB— 97
Grading and Packing Rules for Western Red Cedar Shakes and Western Red Shingles
of the Cedar Shake and Shingle Bureau
.Table 1507.8.5, Table 1507.9.6
652
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
DASMA
Door and Access Systems Manufacturers Association International
1300 Summer Avenue
Cleveland, OH 44115-2851
Standard
Referenced
reference
in code
number
Title
section number
ANSI/DASMA 107—1997
(R2004)
108—05
115—05
Room Fire Test Standard for Garage Doors Using Foam Plastic Insulation 2603.4.1.9
Standard Method for Testing Sectional Garage Doors and Rolling Doors:
Determination of Structural Performance Under Uniform Static Air Pressure Difference 1715.5.2
Standard Method for Testing Sectional Garage Doors and Rolling Doors:
Determination of Structural Performance Under Missile Impact and Cyclic Wmd Pressure 1609.1.2.2
DOC
U.S. Department of Commerce
National Institute of Standards and Technology
1401 Constitution Avenue NW
Washington, DC 20230
Referenced
in code
Title section number
Structural Plywood 2303.1.4, 2304.6.2, Table 2304.7(4), Table 2304.7(5),
Table 2306.2.1(1), Table 2306.2.1(2)
Performance Standard for Wood-based Structural-use Panels 2303.1.4, 2304.6.2,
Table 2304.7(5), Table 2306.2.1(1), Table 2306.2.1(2)
American Softwood Lumber Standard 1810.3.2.4, 2302.1, 2303.1.1
Standard
reference
number
PS- 1—07
PS-2— 04
PS 20— ^5
DOJ
U.S. Department of Justice
950 Pennsylvania Avenue, NW
Civil Rights Division, Disability Rights Section-NYA
Washington, DC 20530
Standard
reference
number
Title
Referenced
in code
section number
DOJ 36 CFR Part 1192
American with Disabilities Act (ADA) Accessibility Guidelines for
Transportation Vehicles (AD A AG) Department of Justice, 1991 . .
.E109.2.4
DOL
U.S. Department of Labor
c/o Superintendent of Documents
U.S. Government Printing Office
Washington, DC 20402-9325
Standard
reference
number
Tide
Referenced
in code
section number
29 CFR Part 1910.1000
(1974)
Air Contaminants 902.1
DOTn
49 CFR Parts 100-185-2005
49 CFR Parts 173.137
(2005)
49 CFR— 1998
U.S. Department of Transportation
c/o Superintendent of Documents
1200 New Jersey Avenue, SE
Washington, DC 20402-9325
Title
Hazardous Materials Regulations 307.2
Shippers — General Requirements for Shipments and Packaging — Class 8 — Assignment of Packing Group 307.2
Specification of Transportation of Explosive and Other Dangerous Articles,
UN 0335, UN 0336 Shipping Containers 307.2
Standard
Referenced
reference
in code
number
Title
section number
2010 CALIFORNIA BUILDING CODE
653
REFERENCED STANDARDS
EN
European Committee for Standardization (EN)
Central Secretariat
Rue de Stassart 36
B-10 50 Brussels
Standard
reference
number
Title
Referenced
in code
section number
EN 1081-98
Resilient Floor Coverings — Determination of the Electrical Resistance 406.5.2
FEMA
Federal Emergency Management Agency
Federal Center Plaza
500 C Street S.W.
Washington, DC 20472
Standard
reference
number
Title
Referenced
in code
section number
FIA-TB11--01
Crawlspace Construction for Buildings Located in Special Flood Hazard Areas 1805.1 .2.1
FM
Standard
Referenced
reference
in code
number
Tide
section number
3260-00
3011-99
4430-80
4450(1989)
4470 (1992)
4474 (04)
4880 (2005)
Factory Mutual Global Research
Standards Laboratories Department
1301 Atwood Avenue, P.O. Box 7500
Johnston, RI 02919
Tide
Radiant Energy-Sensing Fire Detectors for Automatic Fire Alarm Signaling.
Approval Standard for Central Station Service for Fire Alarm and Protective Equipment Supervision
Acceptance Criteria for Smoke and Heat Vents 910.3.1
Approval Standard for Class 1 Insulated Steel Deck Roofs — with
Supplements through July 1992 1508.1, 2603.3, 2603.4.1.5
Approval Standard for Class 1 Roof Covers 1504.7
Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies
Using Static Positive and/or Negative Differential Pressures 1504.3.1
American National Standard for Evaluating Insulated Wall or Wall and Roof/
Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels,
Wall/Ceiling Coating Systems, Interior and Exterior Finish Systems 2603.4, 2603.9
GA
Gypsum Association
810 First Street N.E. #510
Washington, DC 20002-4268
Standard
reference
number
Title
Referenced
in code
section number
GA 216—07
GA 600-06
Application and Finishing of Gypsum Panel Products .
Fire-resistance Design Manual, 18th Edition
Table 2508.1, 2509.2
.Table 720.1(1), Table 720.1(2), Table 720.1(3)
HPVA
Hardwood Plywood Veneer Association
1825 Michael Faraday Drive
Reston, VA 20190
Standard
reference
number
Title
Referenced
in code
section number
HP-1— 2004
Standard for Hardwood and Decorative Plywood. 2303.3, 2304.6.2
654
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
HUD
U.S. Department of Housing and Urban Development
45 17th Street, SW
Washington, DC 20410
Standard
reference
number
Title
Referenced
in code
section number
HUD 24 CFR Part 3280 (1994) Manufactured Home Construction and Safety Standards G201
International Code Council, Inc.
500 New Jersey Ave, NW
Tf^i^ 6thnoor
Av^Vx Washington, DC 20001
Standard Referenced
reference in code
number Title section number
ICC 300—07 ICC Standard on Bleachers, Folding and Telescopic Seating and Grandstands 1028.1.1, Table 1607.1, 3401.1
ICC 400 — 07 Standard on Design and Construction of Log Structures 2301 .2
ICC 500-4)8 ICC/NSSA Standard on the Design and Construction of Storm Shelters 423.1, 423,2
ICC 600—08 Standard for Residential Construction in High Wmd Regions 1609.1.1, 1609.1.1.1, 2308.2.1
ICC ES AC 331 Acceptance Criteria for Smoke and Heat Vents 910J.1
ICC ES AC77 Acceptance Criteria for Smoke Containment Systems Used with Fire-resistance-rated
Elevator Hoistway Doors and Frames 707.14.1
ICC-ESAC 01 — 09* Acceptance Criteria for Expansion Anchors in Masonry Elements 161 5 A. 1.1 4
ICC-ESAC43—09* Acceptance Criteria for Steel Deck Roof and Floor Systems 2209A.3
ICC-ES AC 58 — 09* Acceptance Criteria for Adhesive Anchors in Masonry Elements , 1615A.1.14
ICC-ES AC 70 — 09* Acceptance Criteria for Fasteners Power-Driven into Concrete, Steel and Masonry Elements. 1911 A. IJ
ICC-ESAC 106 — 09* Acceptance Criteria for Predrilled Fasteners (Screw Anchors) in Masonry 161 5A. 1.14
. ICC-ES AC 125 — 09* Acceptance Criteria for Concrete, and Reinforced and Unreinforced Masonry Strengthening Using
Externally Bonded Fiber-Reinforced Polymer (FRP) Composite Systems 1917A.3
ICC-ES AC 1 78 — 09* Acceptance Criteria for Inspection and Verification of Concrete, and Reinforced and Unreinforced Masonry
Strengthening Using Fiber-Reinforced Polymer (FRP) Composite Systems 1917 A.3
ICC-ESAC 193 — 09* Acceptance Criteria for Mechanical Anchors in Concrete Elements 1615A.1.14, 1912A.1.1
ICC-ES AC 308— 09 Acceptance Criteria for Post-Installed Adhesive Anchors in Concrete Elements 1615A.1.14, 1912A.L1
ICC-ESAC 358-09* Acceptance Criteria for Helical Foundation Systems and Devices 1810A.3. 1.5.1
SBCCISSTD 11—97 Test Standard for Determining Wmd Resistance of Concrete or Clay Roof Tiles 1716.2.1, 1716.2.2
* Refers to International Building Code, 2009 as a reference standard.
ISO
International Organization for Standardization
ISO Central Secretariat
1 ch, de la Voie-Creuse, Case Postale 56
CH-1211 Geneva 20, Switzerland
Standard
reference
number
Title
Referenced
in code
section number
ISO 81 15—86
Cotton Bales-Dimensions and Density Table 415.8.2.1.1
National Association of Architectural Metal Manufacturers
1^ A A IV/f l\/f ^^^ Roosevelt Road, Bldg. C, Suite 312
Glen Ellyn,IL 60137
Standard
reference
number
Title
Referenced
in code
section number
FP 1001—97
Guide Specifications for Design of Metal Flag Poles 1609.1.1
NCMA
National Concrete Masonry Association
13750 Sunrise Valley
Hemdon,VA 22071-4662
Standard
reference
number
Title
Referenced
in code
section number
TEK 5-84 (1996)
Details for Concrete Masonry Fire Walls Table 720.1(2)
2010 CALIFORNIA BUILDING CODE
655
REFERENCED STANDARDS
NFPA
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
Referenced
in code
Title section number
Portable Fire Extinguishers 906.2, 906.3.2, 906.3.4, Table 906.3(1), Tkble 906.3(2)
Low Expansion Foam 904.7
Carbon Dioxide Extinguishing Systems 904.8, 904.1 1
Halon 1301 Fire Extinguishing Systems 904.9
Installation of Sprinkler Systems 708.2, 903.3.1.1, 903.3.2, 903.3.5.1.1,
903.3.5.2, 904.1 1, 905.3.4, 907.6.3, 1613.6.3
NFPA 13, Amended Sections as follows:
Revise Section 2.2 and add publications as follows:
22 NFPA PublicaHons.
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2006 California
edition.
Revise Section 8,15.1.2.15 as follows:
8.15.1.2.15 Exterior columns under 10 ft^ (0.93 m^) in total area, formed by studs or wood joist, with no sources of ignition
within the column, supporting exterior canopies that are fully protected with a sprinkler system, shall not require sprinkler pro-
tection.
Revise Section 8.15.7.1* as follows:
8.15.7.1* Unless the requirements of 8.15.7.2 are met, sprinklers shall be installed under ecterior roofs, canopies, porte- coch-
ere, balconies, decks, or similar projections exceeding 4 ft (1.2 m) in width.
Revise Section 8.15.7.2* as follows:
8.15,7.2* Sprinklers shall be permitted to be omitted where the canopies, roofs, balconies, decks, or similar projections are
constructed with materials that are noncombustible, limited-combustible, or fire retardant treated wood as defined in NFPA
703, Standard for Fire Retardant-Treated Wood and Fire-Retardant Coatings for Building Materials.
Delete Section A.8.15.7.2 of Annex
Revise Section 8.15.7.3
8.15.7.3 Sprinklers shall be permitted to be omitted from below the canopies, roofs, balconies, decks, or similar projections
are combustible construction, provided the exposed finish material on the roof, or canopy, is noncombustible, limited-combus-
tible, or fire retardant treated wood as defined in NFPA 703, Standard for Fire Retardant-Treated Wood and Fire-Retardant
Coatings for Building Materials, and the roofs, or canopies contain only sprinklered concealed spaces or any of the following
unsprinklered combustible concealed spaces:
(1) Combustible concealed spaces filled entirely with noncombustible insulation
(2) Light or ordinary hazard occupancies where noncombistible or limited-combustible ceilings are directly attached to
the bottom of solid wood joists so as to create enclosed joist spaces 160 ff (4.5 m^) or less in volume, including space
below insulation that is laid directly on top or within the ceiling joists in an otherwise sprinklered attic
[See I1.2J.1.4(4}(d)l
(3) Concealed spaces over isolated small roofs, or canopies not exceeding 55 ft^ (5.1 m^)
Delete language to section 8.15.7.4 and reserve section number.
8.15.7.4
Revise Annex Section A.8.15. 7.5 as follows:
A.8.15.7.5 The presence of planters, newspaper machines and similar items should not be considered storage.
Add new Sections 8.16.1.1.1.4 and 8.16.1.1.1.5 as follows:
8.16.1.1.1.4 Where a system includes floor control valves, a hydraulic design information sign containing information for the
floor shall be provided at each floor control valve. A hydraulic design information sign shall be provided for each area calcu-
lated. The installing contractor shall identify a hydraulically designed sprinkler system with a permanently marked weather-
proof metal or rigid plastic sign secured with corrosion resistant wire, chain or other approved means. Such signs shall be
placed at the alarm valve, dry pipe valve, preaction valve or deluge valve supplying the corresponding hydraulically designed
area.
8.16.1.1.1.5 Control valves, check valves, drain valves and antifreeze valves shall be readily accessible for inspection, testing
and maintenance. Valves located more than 7 feet above the finished floor shall be provided with a means of opening and clos-
ing the valve from the floor level.
Standard
reference
number
II
10—07
11—05
12—05
12A— 04 Halon 1301
13—70
II
656
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
NFPA — continued
Revise Section 8.16.1,5,1 as follows:
8. 16.1.5.1 Private fire service main systems shall have sectional control valves at appropriate points in order to permit
sectionalizing the system in the event of a break or for the making of repairs or extensions.
Add new Sections 8,16.1,5,1,1, 8,16.1.5,1.2 and 8.16.1,5.1,3 as follows:
8.16.1.5.1.1 Sectional control valves are not required when the fire service main system serves less than six fire appurte-
nances.
8.16.1.5.1.2 Sectional control valves shall be indicating valves in accordance with Section 6.7.1.3.
8.16.1.5.1.3 Sectional control valves shall be located so that no more than five fire appurtenances are afi^ected by shut-down of
any single portion of the fire service main. Each fire hydrant, fire sprinkler system riser and standpipe riser shall be consid-
ered a separate fire appurtenance. In-rack sprinkler systems shall not be considered as a separate appurtenance.
8.16.1.5.1.4 The number of fire appurtenances between sectional control valves is allowed to be modified by the authority hav-
ing jurisdiction.
Revise Section 8.16.1.5.2 as follows:
8.16.1.5.2 A valve shall be provided on each bank where a main crosses a body o/ water or outside the building foundation(s)
where the main or section of main runs under a building.
Add new Section 9.1,3,9.1,1 as follows:
9.1,3.9.1,1 Powder-driven studs used for attaching hangers to the building structure are prohibited in Seismic Design Catego-
ries C, D, E and E
Add a new sentence to the beginning of Section 9.3.5.8.9 as follows:
9.3.5.8.11 Where threaded pipe is used for sway bracing, it shall have a wall thickness of not less than Schedule 40.
Replace Section 9.3.5.9,4 as follows:
Lag screws or power-driven fasteners shall not be used to attach braces to the building structure.
Add language to the beginning of Section 9,3.5,9,6 as follows: I
9.3.5.9.6 Fastening methods other than those identified in Sections 9.3.5.9 and 9.3.7.8 shall not apply to other fastening meth- |
ods, which shall be acceptable for use if certified by a registered professional engineer to support the loads determined in
accordance with the criteria in 9.3.5.6. Calculations shall be submitted to the authority having jurisdiction. | |
Revise Section 9.3.5.9.7.2'^ as follows:
9.3.5.9.7.2* Concrete anchors other than those shown in Figure 9.3.5.9. 1 and identified in Section 9.3.5.8. 1 shall be accept- | |
able for use where designed in accordance with the requirements of the building code and certified by a registered professional
engineer.
Revise Section 9.3.6.1(3) as follows: I I
9.3,6.1*(3) No. 12, 440 lb (200Kg) wire installed at least 45 degrees from the vertical plane and anchored on both sides of the
pipe. Powder-driven fasteners for attaching restraint is allowed to be used provided that the restraint component does not sup-
port the dead load.
Revise Section 10.6,5 as follows:
10.6.5 Pipe joints shall not be located under foundation footings. The pipe under the building or building foundation shall not
contain mechanical joints.
Exceptions:
1. Where allowed in accordance with Section 10.6.2
2. Alternate designs may be utilized where designed by a registered professional engineer and approved by the enforcing
agency.
Revise Section 1 1,2.3.1. 4(4)(i) as follows:
ll,2.3.1.4(4)(i) Exterior columns under 10 ff (0.93 m^) in total area, formed by studs or wood joist, with no sources of ignition
within the column, supporting exterior canopies that are fully protected with a sprinkler system.
Revise Section 11.2.3.2.3.1 as follows:
11.2.3.2.3.1 Where listed quick-response sprinklers, excluding extended coverage quick-response sprinklers, are used through-
out a system or portion of a system having the same hydraulic design basis, the system area of operation shall be permitted to
be reduced without revising the density as indicated in Figure 1 1.2.3.2.3.1 when all of the follaving conditions are satisfied:
(1) Wet pipe system
(2) Light hazard occupancy
2010 CALIFORNIA BUILDING CODE 657
REFERENCED STANDARDS
20
10
NFPA — continued
10 20 30
Ceiling height (ft)
(3) 20 ft (6. 1 m) maximum ceiling height
(4) There are no unprotected ceiling pockets as allowed by 8.6.7 and 8.8.7 exceeding 32 ft^ (3 m^)
Note: y = -^ 55
2
-3jc
For ceiling height > 10 ft and < 20 ft, y = -=^ 55
For ceiling height < 10 ft, y = 40
For ceiling height > 20 ft, j =
For SI units, 1 ft = 0.31m.
FIGURE 11.2.3.2.3.1 Design Area Reduction for Quick-Response Sprinklers.
Revise Section 11.23,2.3,2 as follows:
11.2.3.2.3.2 The number of sprinklers in the design area shall never be less than seven.
Add Section 24.1(5)
24.1 Approval of Sprinkler Systems and Private Fire Service Mains.
The installing contractor shall do the following:
(1) Notify the authority having jurisdiction and the property owner or property owner's authorized representative of the
time and date testing will be performed.
(2) Perform all required testing (see Section 24.2)
(3) Complete and sign the appropriate contractor's material and test certificate(s) (see Figure 24.1)
(4) Remove all caps and straps prior to placing the sprinkler system in service
(5) Upon system acceptance by the authority having jurisdiction a label prescribed by Title 19 California Code of Regula-
tions, Chapter 5 shall be affixed to each system riser
Revise Section 24.4(2) and add Section 24.4(3) as follows:
24.4 Instructions.
The installing contractor shall provide the property owner or the property owner's authorized representative with the follow-
ing:
(1) All literature and instructions provided by the manufacturer describing proper operation and maintenance of any equip-
ment and devices installed
(2) NFPA 25, Standard for the Inspection, testing, and maintenance of Water-Based Fire Protection Systems, 2006 Califor-
nia Edition
(3) Title 19, California Code of Regulations, Chapter 5, "Fire Extinguishing Systems."
Add sentence at the end of Section 24.5.1 as follows:
24.5.1 "Pipe schedule systems shall be provided with a sign indicating that the system was designed and installed as a pipe
schedule system and the hazard classification(s) included in the design."
Revise Section 24.5.2(3) and add Sections 24.5.2(7) to (14) as follows:
24.5.2 The sign shall include the following information:
(3) Required flow and pressure of the system at the base of the riser
(7) Required flow and pressure of the system at the water supply source.
(8) Required flow and pressure of the system at the discharge side of the fire pump where afire pump is installed.
(9) Type or types and number of sprinklers or nozzles installed including the orifice size, temperature rating, orientation,
K-Factor, sprinkler identification number (SIN) for sprinkler heads when applicable, and response type.
658
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
NFPA— continued
(10) The minimum discharge flow rate and pressure required from the hydraulically most demanding sprinkler
(11) The required pressure settings for pressure reducing valves.
(12) For deluge sprinkler systems, the required flow and pressure at the hydraulically most demanding sprinkler or nozzle.
(13) The protection area per sprinkler based on the hydraulic calculations.
(14) The edition ofNFPA 13 to which the system was designed and installed.
Revise Section 24,6.1 as follows:
IAS A California Edition NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection
Systems.
13D — 10 Standard for the Installation of Sprinkler Systems in One- and Two-family Dwellings
and Manufactured Homes as amended"^ 903.3.1.3, 903.3.5.1. 1
NFPA 13D, Amended Sections as follows:
6.2* Water Supply Sources. When the requirements of Section 6.2.2 are met, the following water supply sources shall be
considered to be acceptable by this standard:
(1) A connection to a reliable waterworks system with or without an automatically operated pump
(2) An elevated tank
(3) A pressure tank designed to American Society of Mechanical Engineers (ASME) standards for a pressure \essel with a
reliable pressure source
(4) A stored water source with an automatically operated pump
(5) A well with a pump of sufficient capacity and pressure to meet the sprinkler system demand. The stored water require-
ment of 6. 1 .2 or 6.1.3 shall be permitted to be a combination of the water in the well (including the refill rate) plus the
water in the holding tank if such tank can supply the sprinkler system.
6.2,2 Where a well, pump, tank or combination thereof \% the source of supply for a fire sprinkler system, the water supply
shall serve both domestic and fire sprinkler systems, and the following shall be met:
(1) A test connection shall be provided downstream of the pump that creates a flow of water equal to the smallest sprinkler
on the system. The connection shall return water to the tank.
(2) Any disconnecting means for the pump shall be approved.
(3) A method for refilling the tank shall be piped to the tank.
(4) A method of seeing the water level in the tank shall be provided without having to open the tank.
(5) The pump shall not be permitted to sit directly on the flooE
6.2.2,1 Where afire sprinkler system is supplied by a stored water source with an automatically operated means of pressuriz-
ing the system other than an electric pump, the water supply may serve the sprinkler system only
6.2.4 Where a water supply serves both domestic and fire sprinkler systems, 5 gpm (19 L/min) shall be added to the sprinkler
system demand at the point where the systems are connected, to determine the size of common piping and the size of the total
water supply requirements where no provision is made to prevent flow into the domestic water system upon operation of a
sprinkler
8.6.4* Sprinklers shall not be required in detached garages, open attached porches, carports with no habitable space above,
and similar structures.
13R — 10 Installation of Sprinkler Systems in Residential Occupancies Up to and
Including Four Stories in Height 05 amended"" 903.3.1.2, 903.3.5.1.1, 903.3.5,1.2, 903.4
NFPA 13R, Amended Sections as follows:
Revise Section 2,2 and add publications as follows:
2,2 NFPA Publications.
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2006 California
edition.
Add Section 6.3.5 as follows:
6.3.5 Instructions.
The installing contractor shall provide the property owner or the property owner's authorized representative with the following:
(1) All literature and instructions provided by the manufacturer describing proper operation and maintenance of any
equipment and devices installed
(2) NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems 2006 Califor-
nia Edition and Title 19, California Code of Regulations, Chapter 5.
201 CALIFORNIA BUILDING CODE 659
REFERENCED STANDARDS
14—07
15— OJ
16—01
17—02
17 A— 02
20—07
22—03
24—10
NFPA — continued
(3) Once the system is accepted by the authority having jurisdiction a label as prescribed by Title 19, California Code of
Regulations, Chapter 5, shall be affixed to each system riser
Installation of Standpipe and Hose System, as amended"" 905.2, 905.3 A 905.4.2, 905.6.2, 905.8
NFPA 14f Amended Sections as follows:
Replace Section 6,3.7.1
6.3.7.1 System water supply valves, isolation control valves, and other valves in fire mains shall be supervised in an approved
manner in the open position by one of the following methods:
(1) Where a building has afire alarm system or a sprinkler monitoring system installed, the valve shall be supervised by:
(a) a central station, proprietary, or remote supervising station, or
(b) a local sigruiling service that initiates an audible signal at a constantly attended location.
(2) Where a building does not have afire alarm system or a sprinkler monitoring system installed, the valve shall be
supervised by:
(a) Locking the valves in the open position, or
(b) Sealing of valves and a approved weekly recorded inspection where valves are located within fenced enclosures
under the control of the owner
Water Spray Fixed Systems for Fire Protection
Installation of Foam-water Sprinkler and Foam-water Spray Systems 904.7, 904.1 1
Dry Chemical Extinguishing Systems 904.6, 904. 1 1
Wet Chemical Extinguishing Systems 904.5, 904. 1 1
Installation of Stationary Pumps for Fire Protection 913.1, 913,2.1, 913.5
Water Tanks for Private Fire Protection
Installation of Private Fire Service Mains and Their Appurtenances, as amended*
NFPA 24, Amended Sections as follows:
Amend Section 4.2.1
Section 4.2.1. Installation work shall be done by fully experienced and responsible contractors. Contractors shall be appro-
priately licensed in the State of California to install private fire service mains and their appurtenances.
Revise Section 4.2.2 as follows:
4.2.2 Installation or modification of private fire service mains shall not begin until plans are approved and appropriate per-
mits secured from the authority having jurisdiction.
Add Section 4.2.2.1 as follows:
4.2.2.1 As approved by the authority having jurisdiction, emergency repair of existing system may start immediately, with
plans being submitted to the authority having jurisdiction within 96 hours from the start of the repair work.
Revise Section 5.9.1.2 as follows:
Section 5.9.1.2 Fire department connections shall be properly supported and protected from mechanical damage.
Revise Section 5.9.5.1 as follows:
5.9.5.1 Fire department connections shall be on the street side of buildings and as approved by the authority having jurisdic-
tion.
Revise Section 6..5.1 as follows:
6.5.1 Private fire service main systems shall have sectional control valves at appropriate points in order to permit
sectionalizing the system in the event of a break or for the making of repairs or extensions.
Add Sections 6.5.2.1 - 6.5.2.3
6.5.2.1 Sectional control valves are not required when the fire service main system serves less than six fire appurteruxnces.
6.5.2.2 Sectional control valves shall be indicating valves in accordance with Section 6 J. 1.3.
6.5.2.3 Sectional control valves shall be located so that no more than five fire appurtenances are affected by shut-down of any
single portion of the fire service main. Each fire hydrant, fire sprinkler system riser, and standpipe riser shall be considered a
separate fire appurtenance. In-rack sprinkler systems shall not be considered as a separate appurtenance.
6.5.2.4 The number of fire appurtenances between sectional control valves is allowed to be modified by the authority having
jurisdiction.
660
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
30—08
31—06
32—07
37-06
40—07
52—06
54-09
58—08
61—08
70—08
11—10
II
II
NFPA— continued
Revise Section 6.6.2 as follows: \ \
6.6.2 A sectional valve shall be provided at the following locations:
( 1) On each bank where a main crosses a body c/ water I I
(2) Outside the building foundation(s) where a main or a section of a main runs under a building
Revise Section 10.6,5 as follows:
10.6.5 Pipe joints shall not be located under foundation footings. The pipe under the building or building foundation shall not
contain mechanical joints.
Exceptions:
1. Where allowed in accordance with Section 10.6.2
2. Alternate designs may be utilized where designed by a registered professional engineer and approved by the enforcing
agency.
Revise Section 10.9.1 as follows:
10.9.1 Backfill shall be well tamped in layers or puddle under and around pipes to prevent settlement or lateral movement.
Backfill shall consist of clean fill sand or pea gravel to a minimum 6" below and to a minimum of 12" above the pipe and shall
contain no ashes, cinders, refuse, organic matter, or other corrosive materials. Other backfill materials and methods are per-
mitted where designed by a registered professional engineer and approved by the enforcing agency.
Flammable and Combustible Liquids Code 415.3
Installation of Oil-burning Equipment 2113.15
Dry Cleaning Plants .415.6.4
Installation and Use of Stationary Combustion Engines and Gas Turbines
Storage and Handling of Cellulose Nitrate Film 409.1
Compressed Natural Gas (CNG) Vehicular Fuel Systems Code
National Fuel Gas Code
Liquefied Petroleum Gas Code 415.6.3
Prevention of Fires and Dust Explosions in Agricultural and Food Product Facilities 415.6.1
National Electrical Code 108.3, 415.8.2.8.2, 904.3.1, 907.6.1, 909.12.1,
909.16.3, 1205.4.1, 2701.1, 3401.3, H106.1, H106.2, KlOl, Klll.l
National Fire Alarm Code, as amended* 901.6, 903.4.1, 904.3.5, 907.2, 907.2.5, 907.2.11, I I
907.2.13.2, 907.3, 907.3.3, 907.3.4, 907.5.2.1.2,
907.5.2.2, 907.6, 907.6.1, 907.6.5, 907.7, 907.7.1, 907.7.2, 91 1.1.5, 3006.5, 3007.6
"^NFPA 72, Amended Sections as follows: \ I
10,3.1 Equipment constructed and installed in conformity with this code shall be listed for the purpose for which it is used.
Fire alarm systems and components shall be California State Fire Marshal approved and listed in accordance with California
Code of Regulations, Title 19, Division I. I
10.3.3 All devices and appliances that receive their power from the initiating device circuit or signaling line circuit of a control
unit shall be California State Fire Marshal listed for use with the control unit.
10.6.1 Where approved by the authority having jurisdiction, ECS priority signals when evaluated by stakeholders through risk
analysis in accordance with 24.4.2.2 shall be permitted to take precedence over all other signals.
14.4.7.1 Testing. Household fire alarm systems shall be tested in accordance with the manufacturer's published instructions | |
according to the methods of Table 14.4.2.2.
17.15 Fire Extinguisher Monitoring Device. A fire extinguisher monitoring device shall indicate those conditions for a spe-
cific fire extinguisher required by California Code of Regulations, Title 19, Division 1, Chapter 1, Section 574.2(c) and Call- \ \
fomia Fire Code to afire alarm control unit.
23.4.2.2 (4) Where the vertically run conductors are contained in a 2-hour rated cable assembly, or enclosed (installed) in a
2-hour rated enclosure or a listed circuit integrity (CI.) cable, which meets or exceeds a 2-hour fire resistive rating.
23.8.5.1.2 Where connected to a supervising station, fire alarm systems employing automatic fire detectors or waterflow
detection devices shall include a manual fire alarm box to initiate a signal to the supervising station.
Exception: Fire alarm systems dedicated to elevator recall control, supervisory service and fire sprinkler monitoring.
23.8.5.4.1 Systems equipped with alarm verification features shall be permitted under the following conditions:
(1) The alarm verification feature is not initially enabled unless conditions or occupant activities that are expected to cause
nuisance alarms are anticipated in the area that is protected by the smoks detectors. Enabling of the alarm verification fea-
ture shall be protected by password or limited access.
(2) A smoke detector that is continuously subjected to a smoke concentration above alarm threshold does not delay the
system functions of Sections 10.6 through 10.13, 23.8.1.1, or 21.2.1 by more thanSO seconds.
2010 CALIFORNIA BUILDING CODE
661
REFERENCED STANDARDS
II
II
II
80—07
85—07
92A-09
92B— 05
99—05
101—06
105—07
110—05
111—05
120—04
170-06
211—06
252—03
253—06
257—07
259—03
265—07
268—07
285—06
286—06
288^07
409—04
418—06
484—06
654-06
655--07
664-^7
701--04
704—07
I I 720
1124—06
2001—08
NFPA — continued
(3) Actuation of an alarm-initiating device other than a smoke detector causes the system functions of 4.4.3, 6.8.1.1, or
6.16.2.1 without additional delay.
(4) The current status of the alarm verification feature is shown on the record of completion {see Figure 4.5.2.1, item 10).
(5) Operation of a patient room smoke detector in 1-2 andR-2.1 Occupancies shall not include an alarm verification feature.
29.3.1 All devices, combinations of devices, and equipment to be installed in conformity with this chapter shall be apprcved
or listed by the California State Fire Marshal the for the purposes for which they are intended.
29.5.2.1.1* Smoke and Heat Alarms. Unless exempted by applicable laws, codes, or standards, smoke or heat alarms used to
provide a fire-waming function, and when two or more alarms are installed within a dwelling unit, suite of rooms, or similar
area, shall be arranged so that the operation of any smoke or heat alarm causes all alarms within these locations to sound.
29.7.2.1 The alarm verification feature shall not be used for household fire warning equipment.
29,7.5.7.1 The alarm verification feature shall not be used for household fire warning equipment.
Fire Doors and Other Opening Protectives 410.3.5, 508.2.5.2, 715.4, 715.4.5,
715,4.6, 715.4.7.1, 715.4.8.2, 715.5, 715.5.5, 1008.1.4.3
Boiler and Combustion System Hazards Code 415.6.1
(Note: NFPA 8503 has been incorporated into NFPA 85)
Standard for Smoke-Control Systems Utilizing Barriers and Pressure Differences
Smoke Management Systems in Malls, Atria and Large Spaces 909.8
Standard for Health Care Facilities 407.9
Life Safety Code 1028.6.2
Standard for the Installation of Smoke Door Assembhes 405.4.2, 715.4.3.1, 909.20.4.1
Emergency and Standby Power Systems 2702. 1
Stored Electrical Energy Emergency and Standby Power Systems 2702.1
Coal Preparation Plants .415.6. 1
Standard for Fire Safety and Emergency Symbols 907.1.2
Chimneys, Fireplaces, Vents and Solid Fuel-burning Appliances 21 12.5
StandardMethodsofFireTestsof Door Assemblies 715.3,715.4.1,715.4.2,715.4.3,715.4.7.3.1
Test for Critical Radiant Flux of Floor Covering Systems Using a
Radiant Heat Energy Source 402.12.1, 406.6.4, 804.2, 804.3
Standard for Fire Test for Window and Glass Block Assemblies 715.3, 715.4.3.2, 715.5, 715.5.1, 715.5.2, 715.5.9.1
Test Method for Potential Heat of Building Materials 2603.4.1.10, 2603.5.3
Method of Fire Tests for Evaluating Room Fire Growth Contribution of
Textile Wall Coverings on Full Height Panels and Walls 803.1.3, 803.1.3.1
Standard Test Method for Determining Ignitibility of
Exterior Wall Assemblies Using a Radiant Heat Energy Source 1406.2.1, 1406.2.1.1, 1406.2.1.2, 2603.5.7, D105.1
Standard Method of Test for the Evaluation of Flammability Characteristics of
Exterior Nonload-bearing Wall Assemblies Containing Combustible Components 1407.10.4, 2603,5.5
Standard Method of Fire Test for Evaluating Contribution of Wall and
Ceiling Interior Finish to Room Fire Growth 402.16.4, 803.1.2, 803.1.2.1, 803.9, 2603.4, 2603.9
Standard Method of Fire Tests of Floor Fire Door Assemblies
Installed Horizontally in Fire-resistance-rated Floor Systems 712.8
Aircraft Hangars 412.4.6, Table 412.4.6, 412.4.6.1,412.6.5
Standard for Heliports 412.7.4
Combustible Metals 415.6.1
Prevention of Fire & Dust Explosions from the Manufecturing,
Processing and Handhng of Combustible Particulate Solids 415.6.1
Prevention of Sulfur Fires and Explosions 415.6.1
Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities 415.6. 1
Standard Methods of Fire Tests for Flame-propagation of Textiles and Films 402.12.1, 410,3.6, 801.1.4, 806.1,
806.1.2, 806.2, 3102.3, 3102.3.1,
3102.6.1.1, 3105.4, D102.2.8, H106.iri
Standard System for the Identification of the Hazards of Materials for Emergency Response 414.7.2, 415.2
Standard for the Installation of Carbon Monoxide (CO) Detection and Wzrning Equipment 2009 Edition 420.4
Manufacture, Transportation and Storage of Fireworks and Pyrotechnic Articles 415.3.1
Clean Agent Fire Extinguishing Systems, as amended* Table 901.6.1, 904.10
*NFPA 2001 f Amended Sections as follows:
4.3.5.1.1 Alarms signals from the fire extinguishing system shall not interfere with the building fire alarm signal.
4.3.5.2.1 The lens on visual appliances shall be "red" in color.
Exception: Other lens colors are permitted where approved by the enforcing agency.
662
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
PCI
Precast Prestressed Concrete Institute
209 W. Jackson Boulevard, Suite 500
Chicago, IL 60606-6938
Referenced
in code
Title section number
Design for Fire Resistance of Precast Prestressed Concrete 721.2.3.1
Recommended Practice for Glass Fiber Reinforced Concrete Panels 1903.2
PCI Design Handbook 7th Edition 1908A.1
Standard
reference
number
MNL 124—89
MNL 128—01
PCI 120—10
PTI
Post-Tens ioning Institute
8601 North Black Canyon Highway, Suite 103
Phoenix, AZ 85021
Standard
reference
number
Title
Referenced
in code
section number
PTI~2004 Recommendations for Prestressed Rock and Soil Anchors (4th Edition) 1811A.2, 1810A3J0.4, J106.2.5 \ \
PTI — 2007 Standard Requirements for Analysis of Shallow Concrete Foundations on Expansive Soils, Third Edition 1808.6.2
PTI — 2007 Standard Requirements for Design of Shallow Post-tensioned Concrete Foundation on
Expansive Soils, Second Edition 1808.6.2
State of California
Department of Forestry and Fire Protection
Office of the State Fire Marshal
C 17 ]i/¥ ^ ^- ^^^ 944246
h3L^ IVJ. Sacramento, CA 94246-2460
Standard Referenced
reference in code
number Title section number
12-3 Releasing Systems for Security Bars in Dwellings 1029.4
12-7-3 Fire-testing Furnaces .NA
12-7A-1 Exterior Wall Siding and Sheathing 703A.7, 707A.2
72-Z4-2 Exterior Window 703A.7, 708A.2.1
12-7A-3 Under Eave 703A.7, 707A.8
12-7A-4 Decking 703A.7, 709A.3
SFM 12-7A-4A Decking Alternate Method A 703A.7, 709A.3
SFM 12-7 A-5 Ignition Resistant Building Material 703A.7, 709A.3
12-8-100 Room Fire Tests for Wall and Ceiling Materials NA
12-10-1 Power Operated Exit Doors NA
12-10-2 Single Point Latching or Locking Devices NA
12-10-3 Emergency Exit and Panic Hardware NA
(The Office of the State Fire Marshal standards referred to above are found in the California Code of Regulations, Title 24, Part 12.)
RMI
Rack Manufacturers Institute
8720 Red Oak Boulevard, Suite 201
Charlotte, NC 28217
Standard
reference
number
Title
Referenced
in code
section number
ANSiyMH16.1— 08
Specification for Design, Testing and Utilization of Industrial Steel Storage Racks 2208.1
SDI
Steel Deck Institute
R O. Box 25
Fox River Grove, IL 60021
Standard
reference
number
Title
Referenced
in code
section number
ANSI/NCI. 0—06
ANSI/RDl.O— 06
Standard for Noncomposite Steel EHoor Deck
Standard for Steel Roof Deck
.2209.2.2,2209.2.2.1
2209.2.3
2010 CALIFORNIA BUILDING CODE
663
REFERENCED STANDARDS
SJI
Steel Joist Institute
1 173B London Links Drive
Forest, VA 24551
Standard
reference
number
Referenced
in code
Title section number
Standard Specification for Composite Steel Joists, CJ-series 1604.3.3, 2203.2, 2206.1
Standard Specification for Joist Girders 1604.3.3, 2203.2, 2206.1
Standard Specification for Open Web Steel Joists, K-series 1604.3.3, 2203.2, 2206.1
Standard Specification for Longspan Steel Joists, LH-series
and Deep Longspan Steel Joists, DLH-series 1604.3.3, 2203.2, 2206.1
C J- 1.0— 06
JG-1.1— 05
K- 1.1^05
LH/DLH-1.1— 05
SPRI
Single-Ply Roofing Institute
411 Waverly Oaks Road, Suite 331B
Waltham, MA 02452
Standard
reference
number
Title
Referenced
in code
section number
SPRI/ANSI/ES-1— 03
RP-4--02
Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems .
Wind Design Guide for Ballasted Single-ply Roofing Systems
. 1504.5
.1504.4
TIA
Telecommunications Industry Association
2500 Wilson Boulevard
Arlington, VA 22201-3834
Standard
reference
number
Title
Referenced
in code
section number
TIA-222-G--05
Structural Standards for Steel Antenna Towers and Antenna Supporting
Structures including- Addendum 1, 222-G-l, Dated 2007
.1609.1.1,3108.1,3108.2
TMS
0216—97
0302—07
402—08
602—08
The Masonry Society
3970 Broadway, Unit 201-D
Boulder, CO 80304-1135
Standard
Referenced
reference
in code
number
Title
section number
Standard Method for Determining Fire Resistance of Concrete and
Masonry Construction Assemblies Table 720.1(2), 721.1
Standard Method for Determining the Sound Transmission Class Rating for Masonry Walls 1207.2.1
Building Code Requirements for Masonry Structures 1405.6, 1405.6.2, 1405.10, 1604.3.4, Table 1703.4.5.3,
1704.5, 1704.5.1, Table 1704.5.1, 1704.5.2, 1704.5.3,
1807.1.6.3.2, 1808.9, 2101.2.2, 2101.2.3, 2101.2.4, 2101.2.5,
2101.2.6, 2103.1.3.6, 2106.1, 2107.1, 2107.2, 2107.3, 2107.4,
2107.5, 2108.1, 2108.2, 2108.3,2109.1, 2109.1.1, 2109.2, 2109.2.1, 2109.3, 2110.1
Specification for Masonry Structures .
1405.6.1, Table 1704.5.1, Table 1704.5.3, 1807.1.6.3,
2103.8, 2103.1 1, 2103.12, 2103.13, 2104.1, 2104.1.1, 2104.1.2
2104.1.3, 2104.2, 2104.3, 2104.4, 2105.2.2.1.1, 2105.2.2.1.2, 2105.2.2.1.3
TPI
Truss Plate Institute
218 N. Lee Street, Suite 312
Alexandria, VA 22314
Standard
reference
number
Title
Referenced
in code
section number
TPI 1-2007
National Design Standards for Metal-plate-connected Wood Truss Construction 2303.4.6, 2306.1
664
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
UBC
International Code Council, Inc.
500 New Jersey Avenue, NW 6th Floor
Washington, DC 20001
Referenced
in code
Title section number
Test Standard for Determining the Fire Retardancy of Roof-Covering Materials 1505.6
Wood Shakes 1505.6
WoodShingles 1505.6
Standard
reference
number
UBC Standard 15-2
UBC Standard 15-3
UBC Standard 15-4
UL
Standard
Referenced
reference
in code
number
Title
section number
9—2000
lOA— 98
lOB— 97
lOC—98
13—96
14B— 98
14C— 06
38—99
Underwriters Laboratories, Inc.
333 Pfmgsten Road
Northbrook, IL 60062-2096
Title
Fire Tests of Window Assemblies— with Revisions through April 2005 . . . 715.3, 715.4.3.2, 715.5, 715.5.1, 715.5.2, 715.5.9.1
Tin Clad Fire Doors — with Revisions through March 2003 715.4
Fire Tests of Door Assemblies — with Revisions through October 2001 715.4.2
Positive Pressure Fire Tests of Door Assemblies — with Revisions through November 2001 715.4.1, 715.4.3
Power-limited Circuit Cables
Sliding Hardware for Standard Horizontally-mounted Tin Clad Fire Doors —
with Revisions through July 2000 715.4
Swinging Hardware for Standard Tin Clad Fire Doors Mounted Singly and in Pairs 715.4
Manually Actuated Signaling Boxes — with revisions through February 2, 2005 as amended. *
103—01
127—96
193—04
199—95
199E— 04
217—06
228—97
260—04
262—04
263—03
268—06
268A—98
300--05
305—07
312—04
325—02
346—05
464—03
497B—04
* Amend Section 14.1.5 as follows:
14.L5 A signaling box having a glass panel, disc, md or similar part that must be broken to operate it for a signal or for
access to its actuating means shall satisfactorily complete five part-breaking operations using the means provided with the
box, without jamming of the mechanism or other interference by broken particles. It shall be practicable to remove and
replace the broken parts. A signaling box shall not have a glass panel, disc, rod or similar part requiring a striking action by
grasping a tool to operate it for a signal The force required to activate controls shall be no greater than 5 pounds (22 N) of
force.
"^Add Appendix B chapter to UL 38 (1999) as follows:
Appendix B,
14.1.5 Operation. Controls and operating mechanisms shall be operable with one hand and shall not require tight grasping,
pinching or twisting of the wrist.
Factory-built Chimneys, for Residential Type and Building Heating Appliances —
with Revisions through June 2006 717.2.5.1
Factory-built Fireplaces — with Revisions through November 2006 717.2.5.1, 2111.11
Alarm Valves for Fire-Protection Service
Automatic Sprinklers for Fire Protection Service — with revisions through August 19, 2005
Outline of Investigation for Fire Testing of Sprinklers and Water Spray Nozzles for
Protection of Deep Fat Fryers 904.1 1.4.1
Single and Multiple Station Smoke Alarms — with Revisions through August 2005 907.2.1 1
Door Closers/Holders, with or without Integral Smoke Detectors — with revisions through January 26, 2006
Dry Pipe and Deluge Valves for Fire Protection Service
Gate Valves for Fire Protection Service
Standard for Fire Test of Building Construction and Materials 703.2, 703.2.1, 703.2.3, 703.3, 703.5,
704.12, 705.7, 707.7, 712.3.2, 713.3.1, 713.4.1.1,
714.1, 715.2, 716.5.2, 716.5.3, 716.6.1, Table 716.6.2(1),
Table 720.1(1), 1407.10.2, 2103.2, 2603.4, 2603.5.1
Smoke Detectors for Fire Protective Signaling Systems — with Revisions through January 1999 407.7, 907.2.6.2
Smoke Detectors for Duct Application — with revisions through October 22, 2003
Fire Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Areas 904.1 1
Panic Hardware 1008.1.10
Check Valves for Fire-Protection Service
Door, Drapery, Gate, Louver and Window Operations and Systems —
with Revisions through February 2006 406.1.5, 3110.4
Waterflow Indicators for Fire Protective Signaling Systems
Audible Signal Appliances — with revisions through October 10, 2003
Protectors for Data Communication and Fire Alarm Circuits
2010 CALIFORNIA BUILDING CODE
665
REFERENCED STANDARDS
521—99
539-00
555—2006
555C— 2006
555S— 99
580—2006
632—00
641—95
710B— 04
723--03
753-04
790_W
793-^3
813—96
864—03
UL — continued
Heat Detectors for Fire Protective Signaling Systems — with Revisions through July 20, 2005
Single- and Multiple-Station Heat Detectors — with Revisions through August 15, 2005
Fire Dampers .716.3
Ceiling Dampers 716.3, 716.6.2
Smoke Dampers — with Revisions through July 2006 716.3, 716.3.1.1
Test for Uplift Resistance of Roof Assemblies 1504.3.1, 1504.3.2
Electrically Actuated Transmitters
Type L Low- temperature Venting Systems — with Revisions through August 2005 21 13. U. 1.4
Recirculating Systems — with Revisions through April 2006 904.1 1
Standard for Test for Surface Burning Characteristics of Building Materials —
with Revisions through May 2005 402.1 1, 402.16.4, 406.5.3, 703.4.2, 719.1,
719.4, 802.1, 803.1.1, 803.9, 806.5, 1407.9, 1407.10.1, 2303.2, 2603.3,
2603.4.1.13, 2603.5.4, 2604.2.4, 2606.4, 3105.4, D102.2.8
Alarm Accessories for Automatic Water Supply Valves for Fire Protection Service
Standard Test Methods for Fire Tests of Roof Coverings 1505.1, 2603.6, 2610.2, 2610.3
Standards for Automatically Operated Roof Vents for Smoke and Heat —
with Revisions through April 2004 910.3.1
Commercial Audio Equipment — with revisions through December 7, 1999
Control Units for Fire Protective Signaling Systems, as amended* — with revisions through July 14, 2005 909.12
*AmendNo. 55.1 as follows:
RETARD-RESET-RESTART PERIOD - MAXIMUM 30 SECONDS— No alarm obtained ftvm contwl unit. Maximum
permissible time is 30 seconds.
*Amend Section 55.2.2 as follows:
Where an alarm verification feature is provided, the maximum retard-reset-restart period before an alarm signal can be
confirmed and indicated at the control unit, including any control unit reset time and the power-up time for the detector to
become operational for alarm, shall not exceed 30 seconds. (The balance of the section text is to remain unchanged).
*Add Section 55.2.9 as follovi's:
Smoke detectors connected to an alarm verification feature shall not be used as releasing devices.
Exception: Smoke detectors which operate their releasing function immediately upon alarm actuation independent of
alarm verification feature.
'^Amend Section 89.1.10 as follows:
The existing text of this section is to remain as printed with one editorial amendment as follows:
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 30 SECONDS.
(The balance of the section text is to remain unchanged).
924—06
1040—96
1256—02
1479—03
1482—96
1715—97
1777—04
1784—01
1897—04
1975—06
1994—04
2017—2000
2034
2075
2079—04
2200-04
Standard for Safety Emergency Lighting and Power Equipment 101 1.4
Fire Test of Insulated Wall Construction— with Revisions through June 2001 1407.10.3, 2603.4, 2603.9
Fire Test of Roof Deck Construction— with Revisions through January 2007 1508.1, 2603.3, 2603.4.1.5
Fire Tests of Through-penetration Firestops-with Revisions through April 2007 702.1, 713.3.1.2, 713.3.2, 713.4.1.1.2
Solid-fuel-type Room Heater — with Revisions through November 2006 21 12.2, 21 12.5
Fire Test of Interior Finish Material— with Revisions through March 2004 1407.10.2, 1407.10.3, 2603.4, 2603.9
Chimney Liners 2113.11.1, 2113.19
Air Leakage Tests of Door Assemblies — with Revisions through December 2004 708. 14. 1, 71 1.5.2,
715.4.3.1, 715.4.6.1, 715.4.6.3, 3007.4.3
Uplift Tests for Roof Covering Systems 1504.3.1
Fire Test of Foamed Plastics Used for Decorative Purposes 402.11, 402.12.1, 402.16.5
Standard for Luminous Egress Path Marking Systems — with Revisions through February 2005 41 1.7, 1024.2.1,
1024.2.3, 1024.2.4, 1024.4
Standards for General-purpose Signaling Devices and Systems —
with Revisions through August 2005 3109.4.1.8
Single and Multiple Station Carbon Monoxide Alarms Effective August 1, 2009 420.4
Gas and Vapor Detectors and Sensors Effective September 1, 2009 420.4
Tests for Fire Resistance of Building Joint Systems — with Revisions through March 2006 702.1, 714.3, 714,6
Stationary Engine Generator Assemblies — with Revisions through July 2004 2702.1.1
666
2010 CALIFORNIA BUILDING CODE
REFERENCED STANDARDS
ULC
Underwriters Laboratories of Canada
7 Underwriters Road
Toronto, Ontario, Canada M1R3B4
Referenced
in code
Title section number
Standard Method of Test for Surface Burning Characteristics of Flooring,
Floor Coverings and Miscellaneous Materials and Assemblies — with 2000 Revisions 719.4
United States Code
c/o Superintendent of Documents
U.S. Government Printing Office
Washington, DC 20402-9325
Referenced
in code
Title section number
Importation, Manufacture, Distribution and Storage of Explosive Materials 307.2
Window and Door Manufacturers Association
1400 East Touhy Avenue #470
DesPlainesJL 60018
Referenced
in code
Title section number
Specifications for Windows, Doors and Unit Skylights 1715.5.1, 2405.5
Wire Reinforcement Institute, Inc.
942 Main Street, Suite 300
Hartford, CT 06103
Referenced
^ in code
Title section number
Design of Slab-on-ground Foundations — with 1996 Update 1808.6.2
Standard
reference
number
CAN/ULCS 102.2— 1988
use
Standard
reference
number
18USCPartl,Ch.40
WDMA
Standard
reference
number
AAMAAVDMA/CSA
101/I.S.2/A440— 08
WRI
Standard
reference
number
WRI/CRSI— 81
2010 CALIFORNIA BUILDING CODE
667
^®® 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX A - EMPLOYEE QUALIFICATIONS
(Not Adopted by State Agencies)
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SB
ss/cc
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
669
670 201 CALIFORNIA BUILDING CODE
APPENDIX A
EMPLOYEE QUALIFICATIONS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION A1 01
BUILDING OFFICIAL QUALIFICATIONS
AlOl.l Building officiaL The building official shall have at
least 10 years' experience or equivalent as an architect, engi-
neer, inspector, contractor or superintendent of construction, or
any combination of these, five years of which shall have been
supervisory experience. The building official should be certi-
fied as a building official through a recognized certification
program. The building official shall be appointed or hired by
the applicable governing authority.
A101.2 Chief inspector. The building official can designate
supervisors to administer the provisions of the International
Building, Mechanical and Plumbing Codes and International
Fuel Gas Code, Each supervisor shall have at least 10 years'
experience or equivalent as an architect, engineer, inspector,
contractor or superintendent of construction, or any combina-
tion of these, five years of which shall have been in a supervi-
sory capacity. They shall be certified through a recognized
certification program for the appropriate trade.
A101.3 Inspector and plans examiner. The building official
shall appoint or hire such number of officers, inspectors, assis-
tants and other employees as shall be authorized by the juris-
diction. A person shall not be appointed or hired as inspector of
construction or plans examiner who has not had at least 5 years'
experience as a contractor, engineer, architect, or as a superin-
tendent, foreman or competent mechanic in charge of construc-
tion. The inspector or plans examiner shall be certified through
a recognized certification program for the appropriate trade.
A 101. 4 Termination of employment. Employees in the posi-
tion of building official, chief inspector or inspector shall not be
removed from office except for cause after full opportunity has
been given to be heard on specific charges before such applica-
ble governing authority.
SECTION A1 02
REFERENCED STANDARDS
IBC— 09 Intemational Building Code AlOl .2
IMC — 09 Intemational Mechanical Code A101.2
IPC— 09 Intemational Plumbing Code A 1 1 .2
IFGC— 09 Intemational Fuel Gas Code A101.2
2010 CALIFORNIA BUILDING CODE 671
672 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX B - BOARD OF APPEALS
(Not Adopted by State Agencies)
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
673
674 2010 CALIFORNIA BUILDING CODE
APPENDIX B
BOARD OF APPEALS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION B1 01
GENERAL
BlOl.l Application. The application for appeal shall be filed
on a form obtained from the building official within 20 days
after the notice was served.
B101.2 Membership of board. The board of appeals shall
consist of persons appointed by the chief appointing authority
as follows:
1 . One for five years ; one for four years ; one for three years ;
one for two years; and one for one year.
2. Thereafter, each new member shall serve for five years
or until a successor has been appointed.
The building official shall be an ex officio member of said
board but shall have no vote on any matter before the board.
B 101.2.1 Alternate members. The chief appointing
authority shall appoint two alternate members who shall be
called by the board chairperson to hear appeals during the
absence or disqualification of a member. Alternate mem-
bers shall possess the qualifications required for board
membership and shall be appointed for five years, or until a
successor has been appointed.
BlOl.2.2 Qualifications. The board of appeals shall consist
of five individuals, one from each of the following profes-
sions or disciplines:
1. Registered design professional with architectural
experience or a builder or superintendent of building
construction with at least ten years' experience, five
of which shall have been in responsible charge of
work.
2. Registered design professional with structural engi-
neering experience
3. Registered design professional with mechanical and
plumbing engineering experience or a mechanical
contractor with at least ten years' experience, five of
which shall have been in responsible charge of work.
4. Registered design professional with electrical engi-
neering experience or an electrical contractor with at
least ten years' experience, five of which shall have
been in responsible charge of work.
5. Registered design professional with fire protection
engineering experience or a fire protection contractor
with at least ten years' experience, five of which shall
have been in responsible charge of work.
BlOl.2.3 Rules and procedures. The board is authorized
to establish policies and procedures necessary to carry out
its duties.
BlOl.2.4 Chairperson. The board shall annually select one
of its members to serve as chairperson.
BlOl.2.5 Disqualification of member. A member shall not
hear an appeal in which that member has a personal, profes-
sional or financial interest.
BlOl.2.6 Secretary. The chief administrative officer shall
designate a qualified clerk to serve as secretary to the board.
The secretary shall file a detailed record of all proceedings
in the office of the chief administrative officer.
BlOl.2.7 Compensation of members. Compensation of
members shall be determined by law.
B 101.3 Notice of meeting. The board shall meet upon notice
from the chairperson, within 10 days of the filing of an appeal
or at stated periodic meetings.
BlOl.3.1 Open hearing. All hearings before the board
shall be open to the public. The appellant, the appellant's
representative, the building official and any person whose
interests are affected shall be given an opportunity to be
heard.
BlOl.3.2 Procedure. The board shall adopt and make avail-
able to the public through the secretary procedures under
which a hearing will be conducted. The procedures shall not
require compliance with strict rules of evidence, but shall
mandate that only relevant information be received.
BlOl.3.3 Postponed hearing. When five members are not
present to hear an appeal, either the appellant or the appel-
lant's representative shall have the right to request a post-
ponement of the hearing.
B101.4 Board decision. The board shall modify or reverse the
decision of the building official by a concurring vote of
two-thirds of its members.
B 101. 4.1 Resolution. The decision of the board shall be by
resolution. Certified copies shall be furnished to the appel-
lant and to the building official.
BlOl.4.2 Administration. The building official shall take
immediate action in accordance with the decision of the
board.
2010 CALIFORNIA BUILDING CODE
675
676 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX C - GROUP U - AGRICULTURAL BUILDINGS
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
677
678 201 CALIFORNIA BUILDING CODE
APPENDIX C
GROUP U-AGRICULTURAL BUILDINGS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION CI 01
GENERAL
ClOl.l Scope. The provisions of this appendix shall apply
exclusively to agricultural buildings. Such buildings shall be
classified as Group U and shall include the following uses:
1. Livestock shelters or buildings, including shade struc-
tures and milking bams.
2. Poultry buildings or shelters.
3. Bams.
4. Storage of equipment and machinery used exclusively in
agriculture.
5. Horticultural stmctures, including detached production
greenhouses and crop protection shelters.
6. Sheds.
7. Grain silos.
8. Stables.
SECTION CI 02
ALLOWABLE HEIGHT AND AREA
C102.1 GeneraL Buildings classified as Group U Agricultural
shall not exceed the area or height limits specified in Table
C102.1.
C102.2 One-story unlimited area. The area of a one-story
Group U agricultural building shall not be limited if the build-
ing is surrounded and adjoined by public ways or yards not less
than 60 feet (18 288 mm) in width.
C102.3 Two-story unlimited area. The area of a two-story
Group U agricultural building shall not be limited if the build-
ing is surrounded and adjoined by public ways or yards not less
than 60 feet (18 288 mm) in width and is provided with an
approved automatic sprinkler system throughout in accordance
with Section 903.3.1.1.
SECTION C1 03
MIXED OCCUPANCIES
C103.1 Mixed occupancies. Mixed occupancies shall be pro-
tected in accordance with Section 508.
SECTION CI 04
EXITS
C104.1 Exit facilities. Exits shall be provided in accordance
with Chapters llA or IIB as applicable.
Exceptions:
1. The maximum travel distance from any point in the
building to an approved exit shall not exceed 300 feet (9 1
440 mm).
2. One exit is required for each 15,000 square feet (1393.5
m^) of area or fraction thereof.
TABLE C102.1— BASIC ALLOWABLE AREA FOR A GROUP U,
ONE STORY IN HEIGHT AND MAXIMUM HEIGHT OF SUCH OCCUPANCY
1
II
III and IV
V
A
B
A
B
III A and IV
IIIB
A
B
ALLOWABLE AREA (square feet)»
Unlimited
60,000
27,100
18,000
27,100
18,000
21,100
12,000
MAXIMUM HEIGHT IN STORIES
Unlimited
12
4
2
4
2
3
2
MAXIMUM HEIGHT IN FEET
Unlimited
160
65
55
65
55
50
40
For SI: 1 square foot = 0.0929 ml
a. See Section CI 02 for unlimited area under certain conditions.
2010 CALIFORNIA BUILDING CODE
679
680 2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX D - FIRE DISTRICTS
(Not Adopted by State Agencies)
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
sue
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
681
682 2010 CALIFORNIA BUILDING CODE
APPENDIX D
FIRE DISTRICTS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION D1 01
GENERAL
DlOl.l Scope. The fire district shall include such territory or
portion as outlined in an ordinance or law entitled "An Ordi-
nance (Resolution) Creating and Establishing a Fire District."
Wherever, in such ordinance creating and establishing a fire
district, reference is made to the fire district, it shall be con-
strued to mean the fire district designated and referred to in this
appendix.
DlOl.1.1 Mapping. The fire district complying with the
provisions of Section DlOl.l shall be shown on a map that
shall be available to the public.
D101.2 Establishment of area. For the purpose of this code,
the fire district shall include that territory or area as described in
Sections DlOl.2.1 through DlOl.2.3.
D 101.2.1 Adjoining blocks. Two or more adjoining blocks,
exclusive of intervening streets, where at least 50 percent of
the ground area is built upon and more than 50 percent of the
built-on area is devoted to hotels and motels of Group R-1;
Group B occupancies; theaters, nightclubs, restaurants of
Group A-1 and A-2 occupancies; garages, express and
freight depots, warehouses and storage buildings used for
the storage of finished products (not located with and form-
ing a part of a manufactured or industrial plant); or Group S
occupancy. Where the average height of a building is two
and one-hdlf stories or more, a block should be considered if
the ground area built upon is at least 40 percent.
DlOl.2.2 Buffer zone. Where four contiguous blocks or
more comprise a fire district, there shall be a buffer zone of
200 feet (60 960 mm) around the perimeter of such district.
Streets, rights-of-way and other open spaces not subject to
building construction can be included in the 200-foot (60
960 mm) buffer zone.
DlOl.2.3 Developed blocks. Where blocks adjacent to the
fire district have developed to the extent that at least 25 per-
cent of the ground area is built upon and 40 percent or more
of the built-on area is devoted to the occupancies specified
in Section DlOl .2. 1, they can be considered for inclusion in
the fire district, and can form all or a portion of the 200-foot
(60 960 nam) buffer zone required in Section DlOl. 2.2.
SECTION D1 02
BUILDING RESTRICTIONS
D102.1 Types of construction permitted. Within the fire dis-
trict every building hereafter erected shall be either Type 1, 11,
III or IV, except as permitted in Section D104.
D102.2 Other specific requirements.
D102.2.1 Exterior walls. Exterior walls of buildings
located in the fire district shall comply with the require-
ments in Table 601 except as required in Section D 102.2.6.
D102.2.2 Group H prohibited. Group H occupancies shall
be prohibited from location within the fire district.
D102.2.3 Construction type. Every building shall be con-
structed as required based on the type of construction indi-
cated in Chapter 6.
D102.2.4 Roof covering. Roof covering in the fire district
shall conform to the requirements of Class A or B roof cov-
erings as defined in Section 1505.
D102.2.5 Structural fire rating. Walls, floors, roofs and
their supporting structural members shall be a minimum of
1-hour fire-resistance-rated construction.
Exceptions:
L Buildings of Type IV construction.
2 Buildings equipped throughout with an automatic
sprinkler system in accordance with Section
903.3.1.1.
3. Automobile parking structures.
4. Buildings surrounded on all sides by a permanently
open space of not less than 30 feet (9144 mm).
5 . Partitions complying with Section 603. 1 , Item 10.
D102.2.6 Exterior walls. Exterior load-bearing walls of
Type II buildings shall have a fire-resistance rating of 2
hours or more where such walls are located within 30 feet
(9 144 mm) of a common property line or an assumed prop-
erty line. Exterior nonload-bearing walls of Type II build-
ings located within 30 feet (9144 mm) of a common
property line or an assumed property line shall have
fireresistance ratings as required by Table 601, but not less
than 1 hour. Exterior walls located more than 30 feet (9144
nun) from a common property line or an assumed property
line shall comply with Table 601.
Exception: In the case of one-story buildings that are
2,000 square feet (186 m^) or less in area, exterior walls
located more than 15 feet (4572 mm) from a common
property line or an assumed property line need only com-
ply with Table 601.
D102.2.7 Architectural trim. Architectural trim on build-
ings located in the fire district shall be constructed of
approved noncombustible materials or fire-retardant-
treated wood.
2010 CALIFORNIA BUILDING CODE
683
APPENDIX D
D102.2.8 Permanent canopies. Permanent canopies are
permitted to extend over adjacent open spaces provided all
of the following are met:
1. The canopy and its supports shall be of noncombusti-
ble material, fire-retardant-treated wood. Type IV
construction or of 1-hour fire-resistance-rated con-
struction.
Exception: Any textile covering for the canopy
shall be flame resistant as determined by tests con-
ducted in accordance with NFPA 701 after both
accelerated water leaching and accelerated weath-
ering,
2. Any canopy covering, other than textiles, shall have a
flame spread index not greater than 25 when tested in
accordance with ASTM E 84 or UL 723 in the form
intended for use.
3. The canopy shall have at least one long side open.
4. The maximum horizontal width of the canopy shall
not exceed 15 feet (4572 mm).
5. The fire resistance of exterior walls shall not be
reduced.
D102.2.9 Roof structures. Structures, except aerial sup-
ports 12 feet (3658 mm) high or less, flagpoles, water tanks
and cooling towers, placed above the roof of any building
within the fire district shall be of noncombustible material
and shall be supported by construction of noncombustible
material.
D102.2.10 Plastic signs. The use of plastics complying
with Section 261 1 for signs is permitted provided the struc-
ture of the sign in which the plastic is mounted or installed is
noncombustible.
D 102.2. 11 Plastic veneer. Exterior plastic veneer is not per-
mitted in the fire district.
SECTION D1 03
CHANGES TO BUILDINGS
D103.1 Existing buildings within the fire district. An exist-
ing building shall not hereafter be increased in height or area
unless it is of a type of construction permitted for new buildings
within the fire district or is altered to comply with the require-
ments for such type of construction. Nor shall any existing
building be hereafter extended on any side, nor square footage
or floors added within the existing building unless such modifi-
cations are of a type of construction permitted for new build-
ings within the fire district.
D103.2 Other alterations. Nothing in Section D103.1 shall
prohibit other alterations within the fire district provided there
is no change of occupancy that is otherwise prohibited and the
fire hazard is not increased by such alteration,
D103.3 Moving buildings. Buildings shall not hereafter be
moved into the fire district or to another lot in the fire district
unless the building is of a type of construction permitted in the
fire district.
SECTION D1 04
BUILDINGS LOCATED PARTIALLY
IN THE FIRE DISTRICT
DI04.1 General. Any building located partially in the fire dis-
trict shall be of a type of construction required for the fire dis-
trict, unless the major portion of such building lies outside of
the fire district and no part is more than 10 feet (3048 mm)
inside the boundaries of the fire district.
SECTION D105
EXCEPTIONS TO RESTRICTIONS
IN FIRE DISTRICT
D105.1 General. The preceding provisions of this appendix
shall not apply in the following instances:
1. Temporary buildings used in connection with duly
authorized construction.
2. A private garage used exclusively as such, not more
than one story in height, nor more than 650 square feet
(60 m^) in area, located on the same lot with a dwelling.
3. Fences not over 8 feet (2438 mm) high.
4. Coal tipples, material bins and trestles of Type IV con-
struction.
5 . Water tanks and cooling towers conforming to Sections
1509.3 and 1509.4.
6. Greenhouses less than 15 feet (4572 mm) high.
7. Porches on dwellings not over one story in height, and
not over 10 feet (3048 mm) wide from the face of the
building, provided such porch does not come within 5
feet (1524 mm) of any property line.
8. Sheds open on a long side not over 15 feet (4572 mm)
high and 500 square feet (46 m^) in area.
9. One- and two-family dwellings where of a type of con-
struction not permitted in the fire district can be
extended 25 percent of the floor area existing at the
time of inclusion in the fire district by any type of con-
struction permitted by this code.
10. Wood decks less than 600 square feet (56 m^) where
constructed of 2-inch (51 mm) nominal wood, pressure
treated for exterior use.
1 1 . Wood veneers on exterior walls conforming to Section
1405.5.
12. Exterior plastic veneer complying with Section 2605.2
where installed on exterior walls required to have a
fire-resistance rating not less than 1 hour, provided the
exterior plastic veneer does not exhibit sustained flam-
ing as defined in NFPA 268.
684
2010 CALIFORNIA BUILDING CODE
APPENDIX D
SECTION D106
REFERENCED STANDARDS
ASTM E 84-04 Test Method for Surface D 102.2.8
Burning Characteristics of
Building Materials
NFPA 268-01 Test Method for Determining D105. 1
Ignitability of Exterior Wall
Assemblies Using a Radiant
Heat Energy Source
NFPA 701-99 Methods of Fire Tests for D102.2.8
Flame-Propagation of Textiles
and Films
UL 723-03 Standard for Test for D102.2.8
Surface Burning Characteristics of
Building Materials, with Revisions
through May 2005
201 CALIFORNIA BUILDING CODE 685
686 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX E - RESERVED
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLG
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
..,.
L- ...
2010 CALIFORNIA BUILDING CODE
687
688 2010 CALIFORNIA BUILDING CODE
APPENDIX E
RESERVED 1 1
2010 CALIFORNIA BUILDING CODE 689
690 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX F - RODENTPROOFING
(Not Adopted by State Agencies)
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEC
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
691
692 2010 CALIFORNIA BUILDING CODE
APPENDIX F
RODENTPROOFING
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION F101
GENERAL
FlOl.l General. Buildings or structures and the walls enclos-
ing habitable or occupiable rooms and spaces in which persons
live, sleep or work, or in which feed, food or foodstuffs are
stored, prepared, processed, served or sold, shall be con-
structed in accordance with the provisions of this section,
F101.2 Foundation wall ventilation openings. Foundation
wall ventilator openings shall be covered for their height and
width with perforated sheet metal plates no less than 0.070 inch
(1.8 mm) thick, expanded sheet metal plates not less than 0.047
inch (1.2 mm) thick, cast iron grills or grating, extruded alumi-
num load-bearing vents or with hardware cloth of 0.035 inch
(0.89 mm) wire or heavier. The openings therein shall not
exceed V4 inch (6.4 mm).
F101.3 Foundation and exterior wall sealing. Annular
spaces around pipes, electric cables, conduits, or other open-
ings in the walls shall be protected against the passage of
rodents by closing such openings with cement mortar, concrete
masonry or noncorrosive metal.
F101.4 Doors. Doors on which metal protection has been
applied shall be hinged so as to be free swinging. When closed,
the maximum clearance between any door, door jambs and sills
shall not be greater than Vg inch (9.5 mm).
F101.5 Windows and other openings. Windows and other
openings for the purpose of light or ventilation located in exte-
rior walls within 2 feet (610 mm) above the existing ground
level immediately below such opening shall be covered for
their entire height and width, including frame, with hardware
cloth of at least 0.035 inch (0.89 mm) wire or heavier.
FlOl.5.1 Rodent-accessible openings. Windows and other
openings for the purpose of light and ventilation in the exte-
rior walls not covered in this chapter, accessible to rodents
by way of exposed pipes, wires, conduits and other appurte-
nances, shall be covered with wire cloth of at least 0.035
inch (0.89 mm) wire. In lieu of wire cloth covering, said
pipes, wires, conduits and other appurtenances shall be
blocked from rodent usage by installing solid sheet metal
guards 0.024 inch (0.61 mm) thick or heavier. Guards shall
be fitted around pipes, wires, conduits or other appurte-
nances. In addition, they shall be fastened securely to and
shall extend perpendicularly from the exterior wall for a
minimum distance of 12 inches (305 mm) beyond and on
either side of pipes, wires, conduits or appurtenances.
F101.6 Pier and wood construction.
FlOl.6.1 Sill less than 12 inches above ground. Buildings
not provided with a continuous foundation shall be provided
with protection against rodents at grade by providing either
an apron in accordance with Section F10L6.1.1 or a floor
slab in accordance with Section FlOl.6.1.2.
FlOl.6.1.1 Apron. Where an apron is provided, the
apron shall not be less than 8 inches (203 mm) above, nor
less than 24 inches (610 mm) below, grade. The apron
shall not terminate below the lower edge of the siding
material. The apron shall be constructed of an approved
nondecayable, water-resistant rodentproofing material
of required strength and shall be installed around the
entire perimeter of the building. Where constructed of
masonry or concrete materials, the apron shall not be less
than 4 inches (102 mm) in thickness.
FlOl.6.1.2 Grade floors. Where continuous concrete
grade floor slabs are provided, open spaces shall not be
left between the slab and walls, and openings in the slab
shall be protected.
FlOl.6.2 Sill at or above 12 inches above ground. Build-
ings not provided with a continuous foundation and which
have sills 12 or more inches (305 mm) above the ground
level shall be provide with protection against rodents at
grade in accordance with any of the following:
1. Section FlOl. 6. 1.1 orFlOl.6.1.2;
2. By installing solid sheet metal collars at least 0.024
inch (0.6 mm) thick at the top of each pier or pile and
around each pipe, cable, conduit, wire or other item
which provides a continuous pathway from the
ground to the floor; or
3. By encasing the pipes, cables, conduits or wires in an
enclosure constructed in accordance with Section
F101.6.1.L
2010 CALIFORNIA BUILDING CODE
693
694 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX G - FLOOD RESISTANT CONSTRUCTION
(Not Adopted by State Agencies)
Adopting agency
BSC
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
695
696 2010 CALIFORNIA BUILDING CODE
APPENDIX G
FLOOD-RESISTANT CONSTRUCTION
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION G1 01
ADMINISTRATION
GlOl.l Purpose. The purpose of this appendix is to promote
the public health, safety and general welfare and to minimize
public and private losses due to flood conditions in specific
flood hazard areas through the establishment of comprehen-
sive regulations for management of flood hazard areas
designed to:
1 . Prevent unnecessary disruption of commerce, access and
public service during times of flooding',
2. Manage the alteration of natural flood plains, stream
channels and shorelines;
3. Manage filling, grading, dredging and other develop-
ment v^hich may increase/?<9<9<i damage or erosion poten-
tial;
4. Prevent or regulate the construction of flood barriers
which will divert floodwaters or which can increase
flood hazards; and
5. Contribute to improved construction techniques in the
flood plain.
G101.2 Objectives. The objectives of this appendix are to pro-
tect human life, minimize the expenditure of public money for
flood control projects, minimize the need for rescue and relief
efforts associated -with flooding, minimize prolonged business
interruption, minimize damage to public facilities and utilities,
help maintain a stable tax base by providing for the sound use
and development of flood-prone areas, contribute to improved
construction techniques in the flood plain and ensure that
potential owners and occupants are notified that property is
within flood hazard areas.
G101.3 Scope. The provisions of this appendix shall apply to
all proposed development in a flood hazard area established in
Section 1612 of this code, including certain building work
exempt from permit under Section 105.2.
G101.4 Violations. Any violation of a provision of this appen-
dix, or failure to comply with a permit or variance issued pursu-
ant to this appendix or any requirement of this appendix, shall
be handled in accordance with Section 114.
SECTION G1 02
APPLICABILITY
G102.1 General. This appendix, in conjunction with the Inter-
national Building Code, provides minimum requirements for
development located in flood hazard areas, including the subdi-
vision of land; installation of utilities; placement and replace-
ment of manufactured homes; new construction and repair,
reconstruction, rehabilitation or additions to new construction;
substantial improvement of existing buildings and structures,
including restoration after damage, temporary structures, and
temporary or permanent storage, utility and miscellaneous
Group U buildings and structures, and certain building work
exempt from permit under Section 105.2.
G102.2 Establishment of flood hazard areas. Flood hazard
areas are established in Section 1612.3 of the International
Building Code, adopted by the applicable governing authority
on [INSERT DATE].
SECTION G1 03
POWERS AND DUTIES
G103.1 Permit applications. The building official shall
review all permit applications to determine whether proposed
development sites will be reasonably safe from flooding. If a
proposed development site is in a flood hazard area, all site
development activities (including grading, filling, utility
installation and drainage modification), all new construction
and substantial improvements (including the placement of pre-
fabricated buildings and manufactured homes) and certain
building work exempt from permit under Section 105.2 shall be
designed and constructed with methods, practices and materi-
als that minimize flood damage and that are in accordance with
this code and ASCE 24.
G103.2 Other permits. It shall be the responsibility of the
building official to assure that approval of a proposed develop-
ment shall not be given until proof that necessary permits have
been granted by federal or state agencies having jurisdiction
over such development.
G103.3 Determination of design flood elevations. If design
flood elevations are not specified, the building official is autho-
rized to require the applicant to:
1. Obtain, review and reasonably utilize data available
from a federal, state or other source, or
2. Determine the design flood elevation in accordance with
accepted hydrologic and hydraulic engineering tech-
niques. Such analyses shall be performed and sealed by a
registered design professional. Studies, analyses and
computations shall be submitted in sufficient detail to
allow review and approval by the building official. The
accuracy of data submitted for such determination shall
be the responsibility of the applicant.
G103.4 Activities in riverine flood hazard areas. In riverine
flood hazard areas where design flood elevations are specified
hvXfloodways have not been designated, the building official
shall not permit any new construction, substantial improve-
ment or other development, including fill, unless the applicant
demonstrates that the cumulative effect of the proposed devel-
2010 CALIFORNIA BUILDING CODE
697
APPENDIX G
opment, when combined with all other existing and anticipated
flood hazard area encroachment, will not increase the design
flood elevation more than 1 foot (305 mm) at any point within
the community.
G103.5 Floodway encroachment. Prior to issuing a permit for
any floodway encroachment, including fill, new construction,
substantial improvements and other development or land-dis-
turbing activity, the building official shall require submission
of a certification, along with supporting technical data, that
demonstrates that such development will not cause any
increase of the level of the bsise flood,
G103.5.1 Floodway revisions. A floodway encroachment
that increases the level of the b?ise flood is authorized if the
applicant has applied for a conditional Flood Insurance Rate
Map (FIRM) revision and has received the approval of the
Federal Emergency Management Agency (FEMA).
G103.6 Watercourse alteration. Prior to issuing a permit for
any alteration or relocation of any watercourse, the building
official shall requke the applicant to provide notification of the
proposal to the appropriate authorities of all affected adjacent
government jurisdictions, as well as appropriate state agencies.
A copy of the notification shall be maintained in the permit
records and submitted to FEMA.
G103.6.1 Engineering analysis. The building official shall
require submission of an engineering analysis which dem-
onstrates that the flood-carrying capacity of the altered or
relocated portion of the watercourse will not be decreased.
Such watercourses shall be maintained in a manner which
preserves the channel's flood-carrying capacity.
G103.7 Alterations in coastal areas. Prior to issuing a permit
for any alteration of sand dunes and mangrove stands in flood
hazard areas subject to high velocity wave action, the building
official shall require submission of an engineering analysis
which demonstrates that the proposed alteration will not
increase the potential for flood damage,
G 103.8 Records. The building official shall maintain a perma-
nent record of ail permits issued in flood hazard areas, includ-
ing copies of inspection reports and certifications required in
Section 1612.
SECTION G1 04
PERMITS
G104.1 Required. Any person, owner or authorized agent who
intends to conduct any development in a flood hazard area shall
first make application to the building official and shall obtain
the required permit.
G104.2 Application for permit. The applicant shall file an
application in writing on a form furnished by the building offi-
cial. Such application shall:
1. Identify and describe the development to be covered by
the permit.
2. Describe the land on which the proposed development is
to be conducted by legal description, street address or
similar description that will readily identify and defi-
nitely locate the site.
3. Include a site plan showing the delineation of flood haz-
ard areas, floodway boundaries, flood zones, design
flood elevations, ground elevations, proposed fill and
excavation and drainage patterns and facilities.
4. Indicate the use and occupancy for which the proposed
development is intended.
5. Be accompanied by construction documents, grading
and filling plans and other information deemed appropri-
ate by the building official.
6. State the valuation of the proposed work.
7. Be signed by the applicant or the applicant's authorized
agent.
G104,3 Validity of permit. The issuance of a permit under this
appendix shall not be construed to be a permit for, or approval
of, any violation of this appendix or any other ordinance of the
jurisdiction. The issuance of apermit based on submitted docu-
ments and information shall not prevent the building official
from requiring the correction of errors. The building official is
authorized to prevent occupancy or use of a structure or site
which is in violation of this appendix or other ordinances of this
jurisdiction.
G104.4 Expiration. A permit shall become invalid if the pro-
posed development is not commenced within 1 80 days after its
issuance, or if the work authorized is suspended or abandoned
for a period of 1 80 days after the work commences. Extensions
shall be requested in writing and justifiable cause demon-
strated. The building official is authorized to grant, in writing,
one or more extensions of time, for periods not more than 180
days each.
G104.5 Suspension or revocation. The building official is
authorized to suspend or revoke a permit issued under this
appendix wherever the permit is issued in error or on the basis
of incorrect, inaccurate or incomplete information, or in viola-
tion of any ordinance or code of this jurisdiction.
SECTION G1 05
VARIANCES
G105.1 General. The board of appeals established pursuant to
Section 112 shall hear and decide requests for variances. The
board of appeals shall base its determination on technical justi-
fications, and has the right to attach such conditions to vari-
ances as it deems necessary to further the purposes and
objectives of this appendix and Section 1612.
G105.2 Records. The building official shall maintain a perma-
nent record of all variance actions, including justification for
their issuance.
G 105.3 Historic structures. A variance is authorized to be
issued for the repair or rehabilitation of a historic structure
upon a determination that the proposed repair or rehabilitation
will not preclude the structure's continued designation as ahis-
698
2010 CALIFORNIA BUILDING CODE
APPENDIX G
toric structure, and the variance is the minimum necessary to
preserve the historic character and design of the structure.
Exception: Wi\hin flood hazard areas, historic structures
that are not:
1. Listed or preliminarily determined to be eligible for
listing in the National Register of Historic Places; or
2. Determined by the Secretary of the U.S. Department
of Interior as contributing to the historical signifi-
cance of a registered historic district or a district pre-
liminarily determined to qualify as an historic district;
or
3. Designated as historic under a state or local historic
preservation program that is approved by the Depart-
ment of Interior.
G105.4 Functionally dependent facilities. A variance is
authorized to be issued for the construction or substantial
improvement of a functionally dependent facility provided the
criteria in Section 1612.1 are met and the variance is the mini-
mum necessary to allow the construction or substantial
improvement, and that all due consideration has been given to
methods and materials that minimize flood damages during the
design flood and create no additional threats to public safety.
G105.5 Restrictions. The board of appeals shall not issue a
variance for any proposed development in a floodway if any
increase in flood levels would result during the base flood dis-
charge.
G105.6 Considerations. In reviewing applications for vari-
ances, the board of appeals shall consider all technical evalua-
tions, all relevant factors, all other portions of this appendix and
the following:
1 . The danger that materials and debris may be swept onto
other lands resulting in further injury or damage;
2. The danger to life and property due to flooding or ero-
sion damage;
3. The susceptibility of the proposed development,
including contents, to flood damage and the effect of
such damage on current and future owners;
4. The importance of the services provided by the pro-
posed development to the community;
5. The availability of alternate locations for the proposed
development that are not subject to flooding or erosion;
6. The compatibility of the proposed development with
existing and anticipated development;
7. The relationship of the proposed development to the
comprehensive plan and flood plain management pro-
gram for that area;
8 . The safety of access to the property in times of flood for
ordinary and emergency vehicles;
9. The expected heights, velocity, duration, rate of rise
and debris and sediment transport of the floodwaters
and the effects of wave action, if apphcable, expected at
the site; and
10. The costs of providing governmental services during
and after flood conditions including maintenance and
repair of public utilities and facilities such as sewer,
gas, electrical and water systems, streets and bridges.
G105.7 Conditions for issuance. Variances shall only be
issued by the board of appeals upon:
1 . A technical showing of good and sufficient cause that the
unique characteristics of the size, configuration or
topography of the site renders the elevation standards
inappropriate;
2. A determination that failure to grant the variance would
result in exceptional hardship by rendering the lot
undevelopable;
3. A determination that the granting of a variance will not
result in increased flood heights, additional threats to
public safety, extraordinary public expense, nor create
nuisances, cause fraud on or victimization of the public
or conflict with existing local laws or ordinances;
4. A determination that the variance is the minimum neces-
sary, considering the flood hazard, to afford relief; and
5 . Notification to the applicant in writing over the signature
of the building official that the issuance of a variance to
construct a structure below the base flood level will
result in increased premium rates for flood insurance up
to amounts as high as $25 for $100 of insurance cover-
age, and that such construction below the base flood
level increases risks to life and property.
SECTION G201
DEFINITIONS
G201.1 General. The following words and terms shall, for the
purposes of this appendix, have the meanings shown herein.
Refer to Chapter 2 for general definitions.
G201.2 Definitions.
DEVELOPMENT. Any manmade change to improved or
unimproved real estate, including but not Umited to, buildings
or other structures, temporary structures, temporary or perma-
nent storage of materials, mining, dredging, filling, grading,
paving, excavations, operations and other land-disturbing
activities.
FUNCTIONALLY DEPENDENT FACILITY. A facility
which cannot be used for its intended purpose unless it is
located or carried out in close proximity to water, such as a
docking or port facility necessary for the loading or unloading
of cargo or passengers, shipbuilding or ship repair. The term
does not include long-term storage, manufacture, sales or ser-
vice facilities.
MANUFACTURED HOME. A structure that is transportable
in one or more sections, built on a permanent chassis, designed
for use with or without a permanent foundation when attached
to the required utilities, and constructed to the Federal Mobile
Home Construction and Safety Standards and rules and regula-
tions promulgated by the U.S. Department of Housing and
Urban Development. The term also includes mobile homes,
park trailers, travel trailers and similar transportable structures
that are placed on a site for 180 consecutive days or longer.
2010 CALIFORNIA BUILDING CODE
699
APPENDIX G
MANUFACTURED HOME PARK OR SUBDIVISION. A
parcel (or contiguous parcels) of land divided into two or more
manufactured home lots for rent or sale.
RECREATIONAL VEHICLE. A vehicle that is built on a
single chassis, 400 square feet (37.16 m^) or less when mea-
sured at the largest horizontal projection, designed to be
self-propelled or permanently towable by a light-duty truck,
and designed primarily not for use as a permanent dwelling but
as temporary living quarters for recreational, camping, travel
or seasonal use. A recreational vehicle is ready for highway use
if it is on its wheels or jacking system, is attached to the site
only by quick disconnect-type utilities and security devices and
has no permanently attached additions.
VARIANCE. A grant of relief from the requirements of this
section which permits construction in a manner otherwise pro-
hibited by this section where specific enforcement would result
in unnecessary hardship.
VIOLATION. A development that is not fully compliant with
this appendix or Section 1612, as applicable.
SECTION G301
SUBDIVISIONS
G301.1 General. Any subdivision proposal, including propos-
als for manufactured home parks and subdivisions, or other
proposed new development in a flood hazard area shall be
reviewed to assure that:
1. All such proposals are consistent with the need to mini-
mize flood damage;
2. All public utihties and facihties, such as sewer, gas, elec-
tric and water systems are located and constructed to
minimize or eliminate flood damage; and
3. Adequate drainage is provided to reduce exposure to
flood hazards.
G301.2 Subdivision requirements. The following require-
ments shall apply in the case of any proposed subdivision,
including proposals for manufactured home parks and subdivi-
sions, any portion of which lies within a flood hazard area:
1. The flood hazard area, including floodways and areas
subject to high velocity wave action, as appropriate, shall
be delineated on tentative and final subdivision plats;
2. Design flood elevations shall be shown on tentative and
final subdivision plats;
3 . Residential building lots shall be provided with adequate
buildable area outside the flood way; and
4. The design criteria for utilities and facilities set forth in
this appendix and appropriate International Codes shall
be met.
tice that the proposed encroachment will not result in any
increase in the level of the hsise flood.
G401.2 Flood hazard areas subject to high-velocity wave
action. In flood hazard areas subject to high- velocity wave
action:
1. New buildings and buildings that are substantially
improved shall only be authorized landward of the reach
of mean high tide.
2. The use of fill for structural support of buildings is pro-
hibited.
G401.3 Sewer facilities. All new or replaced sanitary sewer
facilities, private sewage treatment plants (including all pump-
ing stations and collector systems) and on-site waste disposal
systems shall be designed in accordance with Chapter 7, ASCE
24, to minimize or eliminate infiltration of floodwaters into the
facilities and discharge from the facilities into floodwaters, or
impairment of the facilities and systems.
G401.4 Water facilities. All new or replacement water facili-
ties shall be designed in accordance with the provisions of
Chapter 7, ASCE 24, to minimize or eliminate infiltration of
floodwaters into the systems.
G401.5 Storm drainage. Storm drainage shall be designed to
convey the flow of surface waters to minimize or eliminate
damage to persons or property.
G401.6 Streets and sidewalks. Streets and sidewalks shall be
designed to minimize potential for increasing or aggravating
flood levels.
SECTION G501
MANUFACTURED HOMES
G501.1 Elevation. All new and replacement manufactured
homes to be placed or substantially improved in a flood hazard
area shall be elevated such that the lowest floor of the manufac-
tured home is elevated to or above the design flood elevation.
G501.2 Foundations. All new and replacement manufactured
homes, including substantial improvement of existing manu-
factured homes, shall be placed on a permanent, reinforced
foundation that is designed in accordance with Section 1612.
G501.3 Anchoring. All new and replacement manufactured
homes to be placed or substantially improved in di flood hazard
area shall be installed using methods and practices which mini-
mize flood damage. Manufactured homes shall be securely
anchored to an adequately anchored foundation system to
resist flotation, collapse and lateral movement. Methods of
anchoring are authorized to include, but are not limited to, use
of over- the- top or frame ties to ground anchors. This require-
ment is in addition to applicable state and local anchoring
requirements for resisting wind forces.
SECTION G401
SITE IMPROVEMENT
G401.1 Development in floodways. Development or land dis-
turbing activity shall not be authorized in thcfloodway unless it
has been demonstrated through hydrologic and hydraulic anal-
yses performed in accordance with standard engineering prac-
SECTION G601
RECREATIONAL VEHICLES
G601.1 Placement prohibited. The placement of recreational
vehicles shall not be authorized in flood hazard areas subject to
high velocity wave action and m floodways.
700
2010 CALIFORNIA BUILDING CODE
APPENDIX G
G601.2 Temporary placement. Recreational vehicles in flood
hazard areas shall be fully licensed and ready for highway use,
and shall be placed on a site for less than 1 80 consecutive days.
G601.3 Permanent placement. Recreational vehicles that are
not fiilly licensed and ready for highway use, or that are to be
placed on a site for more than 180 consecutive days, shall meet
the requirements of Section G501 for manufactured homes.
SECTION G701
TANKS
G701.1 Underground tanks. Underground tanks in flood haz-
ard areas shall be anchored to prevent flotation, collapse or lat-
eral movement resulting from hydrostatic loads, including the
effects of buoyancy, during conditions of the design flood.
G701.2 Above-ground tanks. Above-ground tanks in flood
hazard areas shall be elevated to or above the design flood ele-
vation or shall be anchored or otherwise designed and con-
structed to prevent flotation, collapse or lateral movement
resulting from hydrodynamic and hydrostatic loads, including
the effects of buoyancy, during conditions of the design flood.
G701.3 Tank inlets and vents. In flood hazard areas, tank
inlets, fill openings, outlets and vents shall be:
1 . At or above the design flood elevation or fitted with cov-
ers designed to prevent the inflow of floodwater or out-
flow of the contents of the tanks during conditions of the
design ^oo^.
2. Anchored to prevent lateral movement resulting from
hydrodynamic and hydrostatic loads, including the
effects of buoyancy, during conditions of the design
flood.
SECTION G801
OTHER BUILDING WORK
G801.1 Detached accessory structures. Detached accessory
structures shall be anchored to prevent flotation, collapse or lat-
eral movement resulting from hydrostatic loads, including the
effects of bouyancy, during conditions of the design flood.
Fully enclosed accessory structures shall have flood openings
to allow for the automatic entry and exit of flood waters.
G801.2 Fences. Fences in floodways that may block the pas-
sage of flood waters, such as stockade fences and wire mesh
fences, shall meet the requirement of Section G103.5.
G801.3 Oil derricks. Oil derricks located in flood hazard
areas shall be designed in conformance with the flood loads in
Sections 1603. L7 and 1612.
G801.4 Retaining walls, sidewalks and driveways. Retain-
ing walls, sidewalks and driveways shall meet the requirements
of Section 1803.4.
G801.5 Prefabricated swimming pools. Prefabricated swim-
ming pools infloodways shall meet the requirements of Section
G103.5.
SECTION G901
TEMPORARY STRUCTURES AND TEMPORARY
STORAGE
G901.1 Temporary structures. Temporary structures shall be
erected for a period of less than 1 80 days. Temporary structures
shall be anchored to prevent flotation, collapse or lateral move-
ment resulting from hydrostatic loads, including the effects of
buoyancy, during conditions of the design flood. Fully
enclosed temporary structures shall have flood openings to
allow for the automatic entry and exit of flood waters.
G901.2 Temporary storage. Temporary storage includes stor-
age of goods and materials for a period of less than 180 days.
Stored materials shall not include hazardous materials.
G901.3 Floodway encroachment. Temporary structures and
temporary storage in floodways shall meet the requirements of
G103.5.
SECTION G1 001
UTILITY AND MISCELLANEOUS GROUP U
GlOOl.l Utility and miscellaneous Group U. Utility and mis-
cellaneous Group U includes buildings that are accessory in
character and miscellaneous structures not classified in any
specific occupancy in the International Building Code, includ-
ing, but not limited to, agricultural buildings, aircraft hangars
(accessory to a one- or two- family residence), bams, carports,
fences more than 6 feet (1829 mm) high, grain silos (accessory
to a residential occupancy), greenhouses, livestock shelters,
private garages, retaining walls, sheds, stables and towers.
G1001.2 Flood loads. Utility and miscellaneous Group U
buildings and structures, including substantial improvement of
such buildings and structures, shall be anchored to prevent flo-
tation, collapse or lateral movement resulting from flood loads,
including the effects of buoyancy, during conditions of the
design flood.
G1001.3 Elevation. Utility and miscellaneous Group U build-
ings and structures, including substantial improvement of such
buildings and structures, shall be elevated such that the lowest
floor, including basement, is elevated to or above the design
flood elevation in accordance with Section 1612 of the Interna-
tional Building Code.
G1001.4 Enclosures below design flood elevation. Fully
enclosed areas below the design flood elevation shall be at or
above grade on all sides and conform to the following:
1. hi flood hazard areas not subject to high- velocity wave
action, enclosed areas shall have flood openings to allow
for the automatic inflow and outflow of floodwaters.
2. In flood hazard areas subject to high- velocity wave
action, enclosed areas shall have walls below the design
flood elevation that are designed to break away or col-
lapse from a water load less than that which would occur
during the design flood, without causing collapse, dis-
placement or other stmctural damage to the building or
structure.
G1001.5 Flood-damage-resistant materials. Flood-dam-
age-resistant materials shall be used below the designflood ele-
vation.
2010 CALIFORNIA BUILDING CODE
701
APPENDIX G
G1001.6 Protection of mechanical, plumbing and electrical
systems. Mechanical, plumbing and electrical systems, includ-
ing plumbing fixtures, shall be elevated to or above the design
flood elevation.
Exception: Electrical systems, equipment and components,
and heating, ventilating, air conditioning, and plumbing
appliances, plumbing fixtures, duct systems and other ser-
vice equipment shall be permitted to be located below the
design /Z6>6><i elevation provided that they are designed and
installed to prevent water from entering or accumulating
within the components and to resist hydrostatic and hydro-
dynamic loads and stresses, including the effects of buoy-
ancy, during the occurrence of flooding to the design flood
elevation in compliance with the flood-resistant construc-
tion requirements of this code. Electrical wiring systems
shall be permitted to be located below the design flood ele-
vation provided they conform to the provisions of NFPA 70.
SECTION G1 101
REFERENCED STANDARDS
ASCE 24-05 Flood Resistance Design
and Construction
G103.1,
G401.3,
G40L4
HUD 24 CFR Manufactured Home
Part 3280 Construction and Safety
(1994) Standards
G201
IBC— 06 International Building Code G102,2
NFPA 70— 08 National Electrical Code G1001.6
702
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX H - SIGNS
(Not Adopted by State Agencies)
Adopting agency
BSD
SFM
HOD
DBA
OSHPD
CSA
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire ciiapter
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
Chapter/Section
2010 CALIFORNIA BUILDING CODE
703
704 201 CALIFORNIA BUILDING CODE
APPENDIX H
SIGNS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION H1 01
GENERAL
HlOl.l General. A sign shall not be erected in a manner that
would confuse or obstruct the view of or interfere with exit
signs required by Chapter 10 or with official traffic signs, sig-
nals or devices. Signs and sign support structures, together with
their supports, braces, guys and anchors, shall be kept in repair
and in proper state of preservation. The display surfaces of
signs shall be kept neatly painted or posted at all times.
H101.2 Signs exempt from permits. The following signs are
exempt from the requirements to obtain a permit before erec-
tion:
1. Painted nonilluminated signs.
2. Temporary signs announcing the sale or rent of property .
3. Signs erected by transportation authorities.
4. Projecting signs not exceeding 2.5 square feet (0.23 m^).
5 . The changing of moveable parts of an approved sign that
is designed for such changes, or the repainting or reposi-
tioning of display matter shall not be deemed an alter-
ation.
SECTION H102
DEFINITIONS
H102.1 General. Unless otherwise expressly stated, the fol-
lowing words and terms shall, for the purposes of this appen-
dix, have the meanings shown herein. Refer to Chapter 2 of the
International Building Code for general definitions.
COMBINATION SIGN, A sign incorporating any combina-
tion of the features of pole, projecting and roof signs.
DISPLAY SIGN. The area made available by the sign struc-
ture for the purpose of displaying the advertising message.
ELECTRIC SIGN. A sign containing electrical wiring, but
not including signs illuminated by an exterior light source.
GROUND SIGN. A billboard or similar type of sign which is
supported by one or more uprights, poles or braces in or upon
the ground other than a combination sign or pole sign, as
defined by this code.
POLE SIGN. A sign wholly supported by a sign structure in
the ground.
PORTABLE DISPLAY SURFACE. A display surface tem-
porarily fixed to a standardized advertising structure which is
regularly moved from structure to structure at periodic inter-
vals.
PROJECTING SIGN. A sign other than a waU sign, which
projects from and is supported by a wall of a building or struc-
ture.
ROOF SIGN. A sign erected upon or above a roof or parapet
of a building or structure.
SIGN. Any letter, figure, character, mark, plane, point, mar-
quee sign, design, poster, pictorial, picture, stroke, stripe, line,
trademark, reading matter or illuminated service, which shall
be constructed, placed, attached, painted, erected, fastened or
manufactured in any manner whatsoever, so that the same shall
be used for the attraction of the public to any place, subject, per-
son, firm, corporation, public performance, article, machine or
merchandise, whatsoever, which is displayed in any manner
outdoors. Every sign shall be classified and conform to the
requirements of that classification as set forth in this chapter.
SIGN STRUCTURE. Any structure which supports or is
capable of supporting a sign as defined in this code. A sign
structure is permitted to be a single pole and is not required to
be an integral part of the building.
WALL SIGN. Any sign attached to or erected against the wall
of a building or structure, with the exposed face of the sign in a
plane parallel to the plane of said wall.
SECTION H1 03
LOCATION
H103.1 Location restrictions. Signs shall not be erected, con-
structed or maintained so as to obstruct any fire escape or any
window or door or opening used as a means of egress or so as to
prevent free passage from one part of a roof to any other part
thereof. A sign shall not be attached in any form, shape or man-
ner to a fire escape, nor be placed in such manner as to interfere
with any opening required for ventilation.
SECTION H104
IDENTIFICATION
H104.1 Identification. Every outdoor advertising display sign
hereafter erected, constructed or maintained, for which a per-
mit is required shall be plainly marked with the name of the per-
son, firm or corporation erecting and maintaining such sign and
shall have affixed on the front thereof the permit number issued
for said sign or other method of identification approved by the
building official.
2010 CALIFORNIA BUILDING CODE
705
APPENDIX H
SECTION H1 05
DESIGN AND CONSTRUCTION
H105.1 General requirements. Signs shall be designed and
constructed to comply with the provisions of this code for use
of materials, loads and stresses.
H105.2 Permits, drawings and specifications. Where a per-
mit is required, as provided in Chapter 1, construction docu-
ments shall be required. These documents shall show the
dimensions, material and required details of construction,
including loads, stresses and anchors.
H105.3 Wind load. Signs shall be designed and constructed to
withstand wind pressure as provided for in Chapter 16.
H105.4 Seismic load. Signs designed to withstand wind pres-
sures shall be considered capable of withstanding earthquake
loads, except as provided for in Chapter 16.
H105.5 Working stresses. In outdoor advertising display
signs, the allowable working stresses shall conform to the
requirements of Chapter 16. The working stresses of wire rope
and its fastenings shall not exceed 25 percent of the ultimate
strength of the rope or fasteners.
Exceptions:
1. The allowable working stresses for steel and wood
shall be in accordance with the provisions of Chapters
22 and 23.
2. The working strength of chains, cables, guys or steel
rods shall not exceed one-fifth of the ultimate strength
of such chains, cables, guys or steel.
H105.6 Attachment. Signs attached to masonry, concrete or
steel shall be safely and securely fastened by means of metal
anchors, bolts or approved expansion screws of sufficient size
and anchorage to safely support the loads applied.
of 2 seconds or less and a burning extent of 5.9 inches (150
mm) or less for 10 specimens.
H106.2 Electrical service. Signs that require electrical service
shall comply with NFPA 70.
SECTION H1 07
COMBUSTIBLE MATERIALS
H107.1 Use of combustibles. Wood, approved plastic or plas-
tic veneer panels as provided for in Chapter 26, or other materi-
als of combustible characteristics similar to wood, used for
moldings, cappings, nailing blocks, letters and latticing, shall
comply with Section H109.1, and shall not be used for other
ornamental features of signs, unless approved.
H107.1.1 Plastic materials. Notwithstanding any other
provisions of this code, plastic materials which bum at a rate
no faster than 2,5 inches per minute (64 mm/s) when tested
in accordance with ASTM D 635 shall be deemed approved
plastics and can be used as the display surface material and
for the letters, decorations and facings on signs and outdoor
display structures.
H107.1.2 Electric sign faces. Individual plastic facings of
electric signs shall not exceed 200 square feet (18.6 m^) in
area.
H107.1.3 Area limitation. If the area of a display surface
exceeds 200 square feet (1 8.6 m^), the area occupied or cov-
ered by approved plastics shall be limited to 200 square feet
(18.6 m^) plus 50 percent of the difference between 200
square feet (18.6 m^) and the area of display surface. The
area of plastic on a display surface shall not in any case
exceed 1,100 square feet (102 m^).
H107.1.4 Plastic appurtenances. Letters and decorations
mounted on an approved plastic facing or display surface
can be made of approved plastics.
SECTION HI 06
ELECTRICAL
H106.1 Illumination. A sign shall not be illuminated by other
than electrical means, and electrical devices and wiring shall be
installed in accordance with the requirements of NFPA 70. Any
open spark or flame shall not be used for display purposes
unless specifically approved.
H106.1.1 Internally illuminated signs. Except as provided
for in Sections 402.16 and 2611, where internally illumi-
nated signs have facings of wood or approved plastic, the
area of such facing section shall not be more than 1 20 square
feet (11.16 m^) and the wiring for electric lighting shall be
entirely enclosed in the sign cabinet with a clearance of not
less than 2 inches (51 mm) from the facing material. The
dimensional limitation of 120 square feet (11.16 m^) shall
not apply to sign facing sections made from flame-resis-
tant-coated fabric (ordinarily known as "flexible sign face
plastic") that weighs less than 20 ounces per square yard
(678 g/m^) and that, when tested in accordance with NFPA
701, meets the fire propagation performance requirements
of both Test 1 and Test 2 or that when tested in accordance
with an approved test method, exhibits an average bum time
SECTION H1 08
ANIMATED DEVICES
H108.1 Fail-safe device. Signs that contain moving sections or
ornaments shall have fail-safe provisions to prevent the section
or ornament from releasing and falUng or shifting its center of
gravity more than 15 inches (381 mm). The fail-safe device
shall be in addition to the mechanism and the mechanism's
housing which operate the movable section or ornament. The
fail-safe device shall be capable of supporting the full dead
weight of the section or ornament when the moving mechanism
releases.
SECTION HI 09
GROUND SIGNS
H109.1 Height restrictions. The structural frame of ground
signs shall not be erected of combustible materials to a height
of more than 35 feet (10668 mm) above the ground. Ground
signs constructed entirely of noncombustible material shall not
be erected to a height of greater than 100 feet (30 480 mm)
above the ground. Greater heights are permitted where
706
2010 CALIFORNIA BUILDING CODE
APPENDIX H
approved and located so as not to create a hazard or danger to
the public.
H109.2 Required clearance. The bottom coping of every
ground sign shall be not less than 3 feet (914 mm) above the
ground or street level, which space can be filled with platform
decorative trim or light wooden construction.
H109.3 Wood anchors and supports. Where wood anchors or
supports are embedded in the soil, the wood shall be pressure
treated with an approved preservative.
SECTION H1 10
ROOF SIGNS
HllO.l General. Roof signs shall be constructed entirely of
metal or other approved noncombustible material except as
provided for in Sections H106.1.1 and H107.1. Provisions
shall be made for electric grounding of metallic parts. Where
combustible materials are permitted in letters or other orna-
mental features, wiring and tubing shall be kept free and insu-
lated therefrom. Roof signs shall be so constructed as to leave a
clear space of not less than 6 feet (1829 mm) between the roof
level and the lowest part of the sign and shall have at least 5 feet
(1524 mm) clearance between the vertical supports thereof. No
portion of any roof sign structure shall project beyond an exte-
rior wall.
Exception: Signs on flat roofs with every part of the roof
accessible.
HI 10.2 Bearing plates. The bearing plates of roof signs shall
distribute the load directly to or upon masonry walls, steel roof
girders, columns or beams. The building shall be designed to
avoid overstress of these members.
HI 10.3 Height of solid signs. A roof sign having a solid sur-
face shall not exceed, at any point, a height of 24 feet (7315
mm) measured from the roof surface.
H110.4 Height of open signs. Open roof signs in which the
uniform open area is not less than 40 percent of total gross area
shall not exceed a height of 75 feet (22 860 mm) on buildings of
Type 1 or Type 2 construction. On buildings of other construc-
tion types, the height shall not exceed 40 feet (12 192 nmi).
Such signs shall be thoroughly secured to the building upon
which they are installed, erected or constructed by iron, metal
anchors, bolts, supports, chains, stranded cables, steel rods or
braces and they shall be maintained in good condition.
HI 10.5 Height of closed signs. A closed roof sign shall not be
erected to a height greater than 50 feet (15 240 mm) above the
roof of buildings of Type 1 or Type 2 construction, nor more
than 35 feet (10 668 mm) above the roof of buildings of Type 3,
4 or 5 construction.
SECTION H1 11
WALL SIGNS
HI 11,1 Materials. Wall signs which have an area exceeding
40 square feet (3.72 m^) shall be constructed of metal or other
approved noncombustible material, except for nailing rails and
as provided for in Sections H106.1.1 and H107.1.
HI 11.2 Exterior wall mounting details. Wall signs attached
to exterior walls of solid masonry, concrete or stone shall be
safely and securely attached by means of metal anchors, bolts
or expansion screws of not less than Vg inch (9.5 nmi) diameter
and shall be embedded at least 5 inches (127 mm). Wood
blocks shall not be used for anchorage, except in the case of
wall signs attached to buildings with walls of wood. A wall sign
shall not be supported by anchorages secured to an unbraced
parapet wall.
HI 11.3 Extension. Wall signs shall not extend above the top of
the wall, nor beyond the ends of the wall to which the signs are
attached unless such signs conform to the requirements for roof
signs, projecting signs or ground signs.
SECTION H1 12
PROJECTING SIGNS
H112.1 General. Projecting signs shall be constructed entirely
of metal or other noncombustible material and securely
attached to a building or structure by metal supports such as
bolts, anchors, supports, chains, guys or steel rods. Staples or
nails shall not be used to secure any projecting sign to any
building or structure. The dead /oa^i of projecting signs not par-
allel to the building or structure and the load due to wind pres-
sure shall be supported with chains, guys or steel rods having
net cross-sectional dimension of not less than Vg inch (9.5 nmi)
diameter. Such supports shall be erected or maintained at an
angle of at least 45 percent (0.78 rad) with the horizontal to
resist the dead load and at angle of 45 percent (0.78 rad) or
more with the face of the sign to resist the specified wind pres-
sure. If such projecting sign exceeds 30 square feet (2.8 m^) in
one facial area, there shall be provided at least two such sup-
ports on each side not more than 8 feet (2438 mm) apart to
resist the wind pressure.
HI 12.2 Attachment of supports. Supports shall be secured to
a bolt or expansion screw that will develop the strength of the
supporting chains, guys or steel rods, with a minimum ^/g-inch
(15,9 mm) bolt or lag screw, by an expansion shield. Turn buck-
les shall be placed in chains, guys or steel rods supporting pro-
jecting signs.
H112.3 Wall mounting details. Chains, cables, guys or steel
rods used to support the live or dead load of projecting signs are
permitted to be fastened to solid masonry walls with expansion
bolts or by machine screws in iron supports, but such supports
shall not be attached to an unbraced parapet wall. Where the
supports must be fastened to walls made of wood, the support-
ing anchor bolts must go through the wall and be plated or fas-
tened on the inside in a secure manner.
H112.4 Height limitation. A projecting sign shall not be
erected on the wall of any building so as to project above the
roof or cornice wall or above the roof level where there is no
cornice wall; except that a sign erected at a right angle to the
building, the horizontal width of which sign is perpendicular to
such a wall and does not exceed 1 8 inches (457 mm), is permit-
ted to be erected to a height not exceeding 2 feet (610 mm)
above the roof or cornice wall or above the roof level where
there is no cornice wall. A sign attached to a comer of a build-
2010 CALIFORNIA BUILDING CODE
707
APPENDIX H
ing and parallel to the vertical line of such comer shall be
deemed to be erected at a right angle to the building wall.
HI 12.5 Additional loads. Projecting sign structures which
will be used to support an individual on a ladder or other ser-
vicing device, whether or not specifically designed for the
servicing device, shall be capable of supporting the antici-
pated additional load, but not less than a 100-pound (445 N)
concentrated horizontal load and a 300-pound ( 1 334 N) con-
centrated vertical load applied at the point of assumed or
most eccentric loading. The building component to which
the projecting sign is attached shall also be designed to sup-
port the additional loads.
TABLE 4-B
THICKNESS OF PROJECTION SIGN
PROJECTION
(feet)
MAXIMUM THICKNESS
(feet)
5
2
4
2.5
3
3
2
3.5
1
4
For SI: 1 foot = 304.8 mm.
SECTION H1 13
MARQUEE SIGNS
H113.1 Materials. Marquee signs shall be constructed entirely
of metal or other approved noncombustible material except as
provided for in Sections HI 06. 1.1 and H107.1.
HI 13.2 Attachment. Marquee signs shall be attached to
approved marquees that are constructed in accordance with
Section 3106.
H113.3 Dimensions. Marquee signs, whether on the front or
side, shall not project beyond the perimeter of the marquee.
HI 13.4 Height limitation. Marquee signs shall not extend
more than 6 feet (1829 mm) above, nor 1 foot (305 mm) below
such marquee, but under no circumstances shall the sign or
signs have a vertical dimension greater than 8 feet (2438 mm) .
SECTION H1 15
REFERENCED STANDARDS
ASTM D 635—03 Test Method for
Rate of Burning and/or
Extent and Time of
Burning of Self-Supporting
Plastics in a Horizontal Position
H107.1.1
NFPA 70—08
National Electrical Code H106.1, H106.2
NFPA 701—99 Methods of Fire Test for H106.1.1
Flame Propagation of Textiles
and Films
SECTION H1 14
PORTABLE SIGNS
H114.1 General. Portable signs shall conform to requirements
for ground, roof, projecting, flat and temporary signs where
such signs are used in a similar capacity. The requirements of
this section shall not be construed to require portable signs to
have connections to surfaces, tie-downs or foundations where
provisions are made by temporary means or configuration of
the structure to provide stability for the expected duration of
the installation.
TABLE 4-A
SIZE, THICKNESS AND TYPE OF GLASS PANELS IN SIGNS
MAXIMUM SIZE OF
EXPOSED PANEL
MINIMUM
THICKNESS
OF GLASS
(inches)
TYPE OF GLASS
Any dimension
(inches)
Area
(square inches)
30
500
%
Plain, plate or wired
45
700
%e
Plain, plate or wired
144
3,600
V4
Plain, plate or wired
>144
> 3,600
%
Wired glass
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mmP.
708
2010 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX I - PATIO COVERS
Adopting agency
BSC
SFM
HCD
DSA
OSHPD
CSA
1
DPH
AGR
DWR
GEO
CA
SL
SLC
1
2
1-AC
AC
SS
SS/CC
1
2
3
4
Adopt entire chapter
X
Adopt entire chapter as
amended (amended sections
listed below)
Adopt only those sections that
are listed below
X
Chapter/Section
1101
X
1102
X
1103
X
2010 CALIFORNIA BUILDING CODE
709
710 2010 CALIFORNIA BUILDING CODE
APPENDIX I
PATIO COVERS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance,
SECTION 1101 (89 mm) thick and further provided that the columns do not
GENERAL support loads in excess of 750 pounds (3.36 kN) per column.
1101. 1 General. Patio covers shall be permitted to be detached
from or attached to dwelling units. Patio covers shall be used
only for recreational, outdoor living purposes and not as car-
ports, garages, storage rooms or habitable rooms. Openings
shall be permitted to be enclosed with insect screening,
approved translucent or transparent plastic not more that 0. 125
inch (3.2 mm) in thickness, glass conforming to the provisions
of Chapter 24 or any combination of the foregoing.
SECTION 1102
DEFINITIONS
1102.1 General. The following word and term shall, for the
purposes of this appendix, have the meaning shown herein.
PATIO COVERS. One story structures not exceeding 12 feet
(3657 mm) in height. Enclosure walls shall be permitted to be
of any configuration, provided the open or glazed area of the
longer wall and one additional wall is equal to at least 65 per-
cent of the area below a minimum of 6 feet 8 inches (2032 mm)
of each wall, measured from the floor.
SECTION 1103
EXTERIOR OPENINGS
1103.1 Light, ventilation and emergency egress. Exterior
openings required for light and ventilation shall be permitted to
open into a patio structure. However, the patio structure shall be
unenclosed if such openings are serving as emergency egress
or rescue openings from sleeping rooms. Where such exterior
openings serve as an exit from the dweUing unit, the patio
structure, unless unenclosed, shall be provided with exits con-
forming to the provision of Chapter 10.
SECTION 1104
STRUCTURAL PROVISIONS
1104.1 Design loads. Patio covers shall be designed and con-
structed to sustain, within the stress limits of this code, all dead
loads plus a minimum vertical live load of 1 pounds per square
foot (0.48 kN/m^) except that snow loads shall be used where
such snow loads exceed this minimum. Such patio covers shall
be designed to resist the minimum wind and seismic loads set
forth in this code.
1104.2 Footings. In areas with a frost depth of zero, a patio
cover shall be permitted to be supported on a concrete slab on
grade without footings, provided tfie slab conforms to the pro-
visions of Chapter 19 of this code, is not less than 3 V2 inches
2010 CALIFORNIA BUILDING CODE 711
71 2 201 CALIFORNIA BUILDING CODE
CALIFORNIA BUILDING CODE-MATRIX ADOPTION TABLE
APPENDIX J - GRADING
Adopting agency
BSC
SFM
HOD
DSA
OSHPD
CSA
DPH
AGR
DWR
CEO
CA
SL
SLC
1
2
1-AC
AC
SS
ss/cc
1
2
3
4
Adopt entire chapter
X
X
Adopt entire chapter as
amended (amended sections
listed below)
X
X
X
Adopt only those sections that
are listed below
X
X
Chapter/Section
J101
X
X
J102
X
X
J104.4
X
X
X
J105
X
X
J105.1
X
X
J106
X
X
J106.2
X
X
J107
X
X
J107.5
X
X
X
X
X
J108
X
X
J109
X
X
J110
X
X
J111
X
X
2010 CALIFORNIA BUILDING CODE
713
714 2010 CALIFORNIA BUILDING CODE
APPENDIX J
GRADING
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
SECTION J1 01
GENERAL
JlOl.l Scope. The provisions of this chapter apply to grading,
excavation and earthwork construction, including fills and
embankments. Where conflicts occur between the technical
requirements of this chapter and the geotechnical report, the
geotechnical report shall govern.
J101.2 Flood hazard areas. The provisions of this chapter shall
not apply to grading, excavation and earthwork construction,
including fills and embankments, in floodways v/iihin flood haz-
ard areas established in Section 1612.3 or in flood hazard areas
where design flood elevations are specified but floodways have
not been designated, unless it has been demonstrated through
hydrologic and hydrauHc analyses performed in accordance
with standard engineering practice that the proposed work will
not result in any increase in the level of the base flood.
SECTION J1 02
DEFINITIONS
J102.1 Definitions. For the purposes of this appendix chapter,
the terms, phrases and words listed in this section and their
derivatives shall have the indicated meanings.
BENCH. A relatively level step excavated into earth material
on which fill is to be placed.
COMPACTION. The densification of a fill by mechanical
means.
CUT. See Excavation.
DOWN DRAIN. A device for collecting water from a swale or
ditch located on or above a slope, and safely delivering it to an
approved drainage facility
EROSION. The wearing away of the ground surface as a result
of the movement of wind, water or ice.
EXCAVATION. The removal of earth material by artificial
means, also referred to as a cut.
FILL. Deposition of earth materials by artificial means.
GRADE. The vertical location of the ground surface.
GRADE, EXISTING. The grade prior to grading.
GRADE, FINISHED. The grade of the site at the conclusion
of all grading efforts.
GRADING. An excavation or fill or combination thereof.
KEY. A compacted fill placed in a trench excavated in earth
material beneath the toe of a slope.
SLOPE. An inclined surface, the inclination of which is
expressed as a ratio of horizontal distance to vertical distance.
TERRACE. A relatively level step constructed in the face of a
graded slope for drainage and maintenance purposes.
SECTION J1 03
PERMITS REQUIRED
J103.1 Permits required. Except as exempted in Section
J103.2, no grading shall be performed without first having
obtained di permit therefor from the building official. A grading
permit does not include the construction of retaining walls or
other structures.
J103.2 Exemptions. A grading permit shall not be required for
the following:
1. Grading in an isolated, self-contained area, provided
there is no danger to the public, and that such grading
will not adversely affect adjoining properties.
2. Excavation for construction of a structure permitted
under this code.
3. Cemetery graves.
4. Refuse disposal sites controlled by other regulations.
5. Excavations for wells, or trenches for utilities.
6. Mining, quarrying, excavating, processing or stockpil-
ing rock, sand, gravel, aggregate or clay controlled by
other regulations, provided such operations do not affect
the lateral support of, or significantly increase stresses
in, soil on adjoining properties.
7. Exploratory excavations performed under the direction
of a registered design professional.
Exemption from the permit requirements of this appendix
shall not be deemed to grant authorization for any work to be
done in any manner in violation of the provisions of this code or
any other laws or ordinances of this jurisdiction.
SECTION J1 04
PERMIT APPLICATION AND SUBMITTALS
J104.1 Submittal requirements. In addition to the provisions
of Section 105.3, the applicant shall state the estimated quanti-
ties of excavation and fill.
J104.2 Site plan requirements. In addition to the provisions of
Section 107, a grading plan shall show the existing grade and fin-
ished grade in contour intervals of sufficient clarity to indicate
the nature and extent of the work and show in detail that it com-
plies with the requirements of this code. The plans shall show the
existing grade on adjoining properties in sufficient detail to iden-
tify how grade changes will conform to the requirements of this
code.
2010 CALIFORNIA BUILDING CODE
715
APPENDIX J
J104.3 Geotechnical report. A geotechnical report prepared
by a registered design professional shall be provided. The
report shall contain at least the following:
1. The nature and distribution of existing soils;
2. Conclusions and recommendations for grading proce-
dures;
3. Soil design criteria for any structures or embankments
required to accomplish the proposed grading; and
4. Where necessary, slope stability studies, and recommen-
dations and conclusions regarding site geology.
Exception: A geotechnical report is not required where the
building code official determines that the nature of the work
applied for is such that a report is not necessary.
J104.4 Liquefaction study. For sites with mapped maximum
considered earthquake spectral response accelerations at short
periods (5^) greater than 0.5g as determined by Section 1613, a
study of the liquefaction potential of the site shall be provided,
and the recommendations incorporated in the plans.
Exceptions:
1. A liquefaction study is not required where the build-
ing official determines from established local data
that the liquefaction potential is low.
2. [OSHPD 1, 2, & 4] Exception 1 not permitted by
OSHPD.
SECTION J1 05
INSPECTIONS
J105.1 General. Inspections shall be governed by Section 109,
Chapter 7, Division II of this code.
J105.2 Special inspections. The special inspection require-
ments of Section 1704.7 shall apply to work performed under a
grading permit where required by the building official.
SECTION J1 06
EXCAVATIONS
J106.1 Maximum slope. The slope of cut surfaces shall be no
steeper than is safe for the intended use, and shall be no steeper
than two units horizontal to one unit vertical (50-percent slope)
unless the owner or authorized agent furnishes a geotechnical
report justifying a steeper slope.
Exceptions:
L A cut surface shall be permitted to be at a slope of 1 .5
units horizontal to one unit vertical (67 -percent slope)
provided that all of the following are met:
LI. It is not intended to support structures or sur-
charges.
L2. It is adequately protected against erosion.
1 .3. It is no more than 8 feet (2438 mm) in height.
1.4. It is approved by the building code official.
1.5. Ground water is not encountered.
2. A cut surface in bedrock shall be permitted to be at a
slope of one unit horizontal to one unit vertical
(100-percent slope).
J106J Earth Retaining Shoring: [OSHPD 1&4]
J 106,2.1 General The requirements of this section shall
apply to temporary and permanent earth retaining shoring
using soldier piles and lagging with or without tie-back
anchors in soil or rock, only when existing or new OSHPD I
or 4 facilities are affected. Shoring used as construction
means and methods only, which does not affect existing or
new OSHPD I or 4 facilities, are not regulated by OSHPD
and shall satisfy the requirements of the authorities having
jurisdiction.
Design, construction, testing and inspection shall satisfy
the requirements of this code except as modified in Sections
JI06.2.2 through JI06.2.8.
J 106,2.2 Duration, Shoring shall be considered temporary
when elements of the shoring will be exposed to site condi-
tions for a period of less than one (I) year, and shall be con-
sidered permanent otherwise. Permanent shoring shall
account for the increase in lateral soil pressure due to earth-
quake. At the end of the construction period, the existing and
new structures shall not rely on the temporary shoring for
support in anyway. Wood components shall not be used for
permanent shoring lasting more than two (2) years. Wood
components of the temporary shoring that may affect the
performance of permanent structure shall be removed after
the shoring is no longer required.
All components of the shoring shall have corrosion pro-
tection or preservative treatment for their expected dura-
tion. Wood components of the temporary shoring that will
not be removed shall be treated in accordance with AWPA
UI (Commodity Specification A, Use Category 4B and Sec-
tion 5.2), and shall be identified in accordance with Section
2303. L8.1.
J106.2.3 Surcharge, Surcharge pressure due to footings,
traffic or other sources shall be considered in design. If the
footing surcharge is located within the semicircular distri-
bution or bulb of earth pressure (when shoring is located
close to a footings), lagging shall be designed for lateral
earth pressure due to footing surcharge. Soil arching effects
may be considered in the design of lagging. Underpinning
of the footing may be used in lieu of designing the shoring
and lagging for surcharge pressure. Alternatively, continu-
ously contacting drilled pier shafts near the footings shall
be permitted. The lateral surcharge design pressure shall be
derived using Boussinesq equations modified for the distri-
bution of stresses in an elastic medium due to a uniform,
concentrated or line surface load as appropriate and soil
arching effects.
J 106,2,4 Design and testing. Except for the modifications
as set forth in Sections J 106.2.4. 1 and J 106.2.4.2 below, all
prestressed rock and soil tie-back anchors shall be designed
and tested in accordance with PTI Recommendations for
Prestressed Rock and Soil Anchors (PTI-2004).
716
2010 CALIFORNIA BUILDING CODE
APPENDIX J
J106.2.4.1 Geotechnical requirements. The
geotechnical report for the earth retaining shoring shall
address the following:
1 . Minimum diameter and minimum spacing for the
anchors including consideration of group
effects.
2. Maximum unbonded length and minimum
bonded length of the tie-back anchors.
3. Maximum recommended anchor tension capac-
ity based upon the soil or rock strength/ grout
bond and anchor depth/spacing.
4. Allowable bond stress at the ground /grout inter-
face and applicable factor of safety for ultimate
bond stress for the anchor. For permanent
anchors, a minimum factor of safety of 2,0 shall
be applied to ground soil interface as required by
PTI-2004 Section 6.6.
5. Minimum grout pressure for installation and
postgrout pressure for the anchor. The presump-
tive postgrout pressure ofSOOpsi may be used for
all soil type.
6. Class I Corrosion Protection is required for all
permanent anchors. The geotechnical report
shall specify the corrosion protection recom-
mendations for temporary anchors.
7. Performance test for the anchors shall be at a
minimum of two (2) times the design loads and
shall not exceed 80 percent of the specified mini-
mum tensile strength of the anchor rod. A creep
test is required for all pre stressed anchors that
are performance tested. All production anchors
shall be tested at 150 percent of design loads and
shall not be greater than 70 percent of the speci-
fied minimum tensile strength of the anchor rod.
8. Earth pressure, surcharge pressure and the seis-
mic increment of earth pressure loading, when
applicable.
9. Maximum recommended lateral deformation at
the top of the soldier pile, at the tie-back anchor
locations and the drilled pier concrete shafts at
the lowest grade level.
10. Allowable vertical soil bearing pressure, friction
resistance and lateral passive soil resistance for
the drilled pier concrete shafts and associated
factors of safety for these allowable capacities.
11. Soil-pier shaft/pile interaction assumptions and
lateral soil stiffness to be used in design for
drilled pier concrete shaft or pile lateral loads.
12. Acceptable drilling methods.
13. Geotechnical observation and monitoring rec-
ommendations.
J106.2,4,2 Structural requirements:
1. Tendons shall be thread-bar anchors conforming
toASTMA722.
2. Anchor design loads shall be based upon the load
combinations in Section 1605 A. 3.1 and shall not
exceed 60 percent of the specified minimum tensile
strength of the tendons.
3. The anchor shall be designed to fail in grout bond
to the soil or rock before pullout of the soil wedge.
4. Design of shoring system shall account for as-built
locations of soil anchors considering all specified
construction tolerances in Section J 106.2.8.
5. Design of shoring system shall account for both
short and long term deformation.
J106.2.4.3 Testing of tie-back anchors:
1. The geotechnical engineer shall keep a record at
job site of all test loads and total anchor move-
ment, and report their accuracy.
2. If a tie-back anchor initially fails the testing
requirements, the anchor shall be permitted to be
regrouted and retested. If anchor continues to fail,
the followings steps shall be taken:
a. The contractor shall determine the cause of
failure - variations of the soil conditions,
installation methods, materials, etc.
b. Contractor shall propose a solution to rem-
edy the problem. The proposed solution will
need to be reviewed and approved by the
geotechnical engineer, shoring design engi-
neer and building official.
3. After a satisfactory test, each anchor shall be
locked off in accordance with Section 8.4 ofPTI
2004.
4. The shoring design engineer shall specify design
loads for each anchor.
J106,2,5 Construction. The construction procedure shall
address the following:
1. Holes drilled for piles/tie-back anchors shall be
done without detrimental loss of ground, sloughing
or caving of materials and without endangering
previously installed shoring members or existing
foundations.
2. Drilling of earth anchor shafts for tie-backs shall
occur when the drill bench reaches two to three feet
below the level of the tie-back pockets.
3. Casing or other methods shall be used where neces-
sary to prevent loss of ground and collapse of the
hole.
4. The drill cuttings from earth anchor shaft shall be
removed prior to anchor installation.
5. Unless tremie methods are used, all water and loose
materials shall be removed from the holes prior to
installing piles/tie-backs.
6. Tie-back anchor rods with attached centralizing
devices shall be installed into the shaft or through
the drill casing. Centralizing device shall not
restrict movement of the grout.
2010 CALIFORNIA BUILDING CODE
717
APPENDIX J
7. After lagging installation, voids between lagging
and soil shall be backfilled immediately to the fiill
height of lagging,
8. The soldier piles shall be placed within specified tol-
erances in the drilled hole and braced against dis-
placement during grouting. Fill shafts with concrete
up to top of footing elevation, rest of the shaft can
generally be filled with lean concrete. Excavation
for lagging shall not be started until concrete has
achieved sufficient strength for all anticipated loads
as determined by the shoring design engineer.
9. Where boulders and/or cobbles have been identified
in the geotechnical reports, contractor shall be pre-
pared to address boulders and/or cobbles that may
be encountered during the drilling of soldier piles
and tie-back anchors.
1 0. The grouting equipment shall produce grout free of
lumps and indispensed cement The grouting equip-
ment shall be sized to enable the grout to be pumped
in continuous operation. The mixer shall be capable
of continuously agitating the grout.
11. The quantity of grout and grout pressure shall be
recorded. The grout pressure shall be controlled to
prevent excessive heave in soils or fracturing rock
formations.
12. If postgrouting is required, postgrouting operation
shall be performed after initial grout has set for
24-hours in the bond length only. Tie-backs shall be
grouted over a sufficient length (anchor bond
length) to transfer the maximum anchor force to the
anchor grout.
13. Testing of anchors may be performed after
postgrouting operations provided grout has
reached strength of 3,000 psi as required by
PTI-2004 Section 6.11.
14. Anchor rods shall be tensioned straight and true.
Excavation directly below the anchors shall not
continue before those anchors are tested.
J 106,2.6 Inspection, survey monitoring and observation,
1. The shoring design engineer or his designee shall
make periodic inspections of the job site for the pur-
pose of observing the installation of shoring system,
testing of tie-back anchors and monitoring of sur-
vey.
2. Testing, inspection and observation shall be in
accordance with testing, inspection and observa-
tion requirements approved by the building official.
The following activities and materials shall be
tested, inspected, or observed by the special inspec-
tor and geotechnical engineer:
a. Sampling and testing of concrete in soldier
pile and tie-back anchor shafts
b. Fabrication of tie-back anchor pockets on
soldier beams
c. Installation and testing of tie-back anchors
d. Survey monitoring of soldier pile and
tie-back load cells
e. Survey monitoring of existing buildings
3. A complete and accurate record of all soldier pile
locations, depths, concrete strengths, tie-back loca-
tions and lengths, tie-back grout strength, quantity
of concrete per pile, quantity of grout per tie-back
and applied tie-back loads shall be maintained by
the special inspector and geotechnical engineer.
The shoring design engineer shall be notified of any
unusual conditions encountered during installation.
4. Calibration data for each test jack, pressure gauge
and master pressure gauge shall be verified by the
special inspector and geotechnical engineer. The
calibration tests shall be performed by an independ-
ent testing laboratory and within 120 calender days
of the data submitted.
5. Monitoring points shall be established at the top
and at the anchor heads of selected soldier piles and
at intermediate intervals as considered appropriate
by the geotechnical engineer.
6. Control points shall be established outside the area
of infiuence of the shoring system to ensure the
accuracy of the monitoring readings.
7. The periodic basis of shoring monitoring, as a
minumum, shall be as follows:
a. Intitial monitoring shall be performed prior
to any excavation.
b. Once excavation has begun, the periodic
readings shall be taken weekly until excava-
tion reaches the estimated subgrade eleva-
tion and the permanent foundation is
complete.
c. If performance of the shoring is within
established guidelines, shoring design engi-
neer may permit the periodic readings to be
bi-weekly. Once initiated, bi-weekly read-
ings shall continue until the building slab at
ground floor level is completed and capable
of transmitting lateral loads to the perma-
nent structure. Thereafter, readings can be
monthly.
d. Where the building has been designed to
resist lateral earth pressures, the periodic
monitoring of the soldier piles and adjacent
structure can be discontinued once the
ground fioor diaphragm and subterranean
portion of the structure is capable of resist-
ing lateral soil loads and approved by the
shoring design engineer, geotechnical engi-
neer and building official.
e. Additional readings shall be taken when
requested by the special inspector, shoring
design engineer, geotechnical engineer or
building official
718
2010 CALIFORNIA BUILDING CODE
APPENDIX J
8. Monitoring reading shall be submitted to the shor-
ing design engineer, engineer in responsible
charge, and the building official within three work-
ing days after they are conducted. Monitoring read-
ings shall be accurate to within 0.01 feet Results are
to be submitted in tabular form showing at least the
intial date of monitoring and reading, current moni-
toring date and reading and difference between the
two readings.
9. If the total cummulative horizontal or vertical move-
ment (from start of construction) of the existing
buildings reaches V2 l^c^ or soldier piles reaches 1
inch all excavation activities shall be suspended.
The geotechnical and shoring design engineer shall
determine the cause of movement, if any, and recom-
mend corrective measures, if necessary, before
excavation continues.
1 0. If the total cummulative horizontal or vertical move-
ment (from start of construction) of the existing
buildings reaches % inch or soldier piles reaches
IV2 inches all excavation activities shall be sus-
pended until the causes, if any, can be determined.
Supplemental shoring shall be devised to eliminate
further movement and the building official shall
review and approve the supplemental shoring
before excavation continues.
IL Monitoring of tie-back anchor loads:
a. Load cells shall be installed at the tie-back
heads adjacent to buildings at maximum
interval of 50 feet, with a minimum of one
load cells per wall.
b. Load cell readings shall be taken once a day
during excavation and once a week during
the remainder of construction.
c. Load cell readings shall be submitted to the
geotechnical engineer, shoring design engi-
neer, engineer in responsible charge and the
building official.
d. Load cell readings can be terminated once
the temporary shoring no longer provides
support for the buildings.
J 106,2,7 Monitoring of existing OSHPD 1 and 4 struc-
tures,
1. The contractor shall complete a written and photo-
graphic log of all existing OSHPD I and 4 structures
within 100 feet or three times depth of shoring, prior
to construction. A licensed surveyor shall document
all existing substantial cracks in adjacent existing
structures.
2. Contractor shall document existing condition of wall
cracks adjacent to shoring walls prior to start of con-
struction.
3. Contracto r shall monitor existing walls for movement
or cracking that may result from adjacent shoring.
4. If excessive movement or visible cracking occurs,
contractor shall stop work and shore/reinforce exca-
vation and contact shoring design engineer and the
building official,
5. Monitoring of the existing structure shall be at rea-
sonable intervals as required by the registered design
professional subject to approval of the building offi-
cial. Monitoring shall be performed by a licensed sur-
veyor and shall consist of vertical and lateral
movement of the existing structures. Prior to starting
shoring installation a preconstruction meeting shall
take place between the contractor, shoring design
engineer, surveyor, geotechnical engineer and the
building official to identify monitoring locations on
existing buildings.
6. If in the opinion of the building official or shoring
design engineer, monitoring data indicate excessive
movement or other distress, all excavation shall cease
until the geotechnical engineer and shoring design
engineer investigates the situation and makes recom-
mendations for remediation or continuing.
7. All reading and measurements shall be submitted to
the building official and shoring design engineer.
J106,2,8 Tolerances, Following tolerances shall be speci-
fied on the construction documents,
1. Soldier piles:
i. Horizontal and vertical construction toler-
ances for the soldier pile locations,
a. Soldier pile plumbness requirements (angle
with vertical line).
2. Tie-back anchors:
i. Allowable deviation of anchor projected angle
from specified vertical and horizontal design
projected angle.
a. Anchor clearance to the existing/new utilities
and structures.
SECTION J1 07
FILLS
J107.1 GeneraL Unless otherwise recommended in the
geotechnical report, fills shall comply with the provisions of
this section.
J107.2 Surface preparation. The ground surface shall be pre-
pared to receive fill by removing vegetation, topsoil and other
unsuitable materials, and scarifying the ground to provide a
bond with the fill material.
J107.3 Benching. Where existing grade is at a slope steeper than
five units horizontal to one unit vertical (20-percent slope) and
the depth of the fill exceeds 5 feet (1524 mm) benching shall be
provided in accordance with Figure J107.3. A key shall be pro-
vided which is at least 1 feet (3048 mm) in width and 2 feet (610
nrni) in depth.
2010 CALIFORNIA BUILDING CODE
719
APPENDIX J
TOP OF FILL
< 5 FT. (1524 mm) OR GREATER
REMOVE UNSUITABLE
MATERIAL
For SI: 1 foot = 304.8 mm.
FIGURE J1 07.3
BENCHING DETAILS
Property
Line
H/5 but 2 ft. (610 mm) minimum ■
and need not exceed
10 ft. (3048 mm) maximum
Property
Line
H/5 but 2 ft. (610 mm) minimum ■
and need not exceed
20 ft. (6096 mm) maximum
Natural or
Finish Grade
Interceptor Drain
(if required)
For SI: 1 foot = 304.8 mm.
FIGURE J108.1
DRAINAGE DIMENSIONS
720
2010 CALIFORNIA BUILDING CODE
APPENDIX J
J107.4 Fill material. Fill material shall not include organic,
frozen or other deleterious materials. No rock or similar irre-
ducible material greater than 1 2 inches (305 mm) in any dimen-
sion shall be included in fills.
J107.5 Compaction. All fill material shall be compacted to 90
percent of maximum density as determined by ASTM D 1557,
Modified Proctor, in lifts not exceeding 12 inches (305 mm) in
depth.
[DSA-SS, DSA'SS/CC & OSHPD 1, 2 & 4] This section
establishes minimum requirements only.
J107.6 Maximum slope. The slope of fill surfaces shall be no
steeper than is safe for the intended use. Fill slopes steeper than
two units horizontal to one unit vertical (50-percent slope) shall
be justified by a geotechnical report or engineering data.
SECTION J1 08
SETBACKS
J108.1 General. Cut and fill slopes shall be set back from the
property lines in accordance with this section. Setback dimen-
sions shall be measured perpendicular to the property line and
shall be as shown in Figure J108. 1 , unless substantiating data is
submitted justifying reduced setbacks.
J108.2 Top of slope. The setback at the top of a cut slope shall
not be less than that shown in Figure J 108. 1 , or than is required
to acconunodate any required interceptor drains, whichever is
greater.
J108.3 Slope protection. Where required to protect adjacent
properties at the toe of a slope from adverse effects of the grad-
ing, additional protection, approved by the building official,
shall be included. Such protection may include but shall not be
limited to:
1. Setbacks greater than those required by Figure J108.1.
2. Provisions for retaining walls or similar construction.
3. Erosion protection of the fill slopes.
4. Provision for the control of surface waters.
SECTION J1 09
DRAINAGE AND TERRACING
J109.1 General. Unless otherwise recommended by a regis-
tered design professional, drainage facilities and terracing
shall be provided in accordance with the requirements of this
section.
Exception: Drainage facilities and terracing need not be
provided where the ground slope is not steeper than 3 hori-
zontal to 1 vertical (33 percent).
J109.2 Terraces. Terraces at least 6 feet (1829 mm) in width
shall be established at not more than 30-foot (9144 mm) verti-
cal intervals on all cut or fill slopes to control surface drainage
and debris. Suitable access shall be provided to allow for clean-
ing and maintenance.
Where more than two terraces are required, one terrace,
located at approximately mid-height, shall be at least 12 feet
(3658 mm) in width.
Swales or ditches shall be provided on terraces. They shall
have a minimum gradient of 20 horizontal to 1 vertical (5 per-
cent) and shall be paved with concrete not less than 3 inches (76
mm) in thickness, or with other materials suitable to the appli-
cation. They shall have a minimum depth of 12 inches (305
nun) and a minimum width of 5 feet (1524 mm).
A single run of swale or ditch shall not collect runoff from a
tributary area exceeding 13,500 square feet (1256 m^) (pro-
jected) without discharging into a down drain.
J109.3 Interceptor drains. Interceptor drains shall be
installed along the top of cut slopes receiving drainage from a
tributary width greater than 40 feet (12 192 mm), measured
horizontally. They shall have a minimum depth of 1 foot (305
mm) and a minimum width of 3 feet (915 mm). The slope shall
be approved by the building official, but shall not be less than
50 horizontal to 1 vertical (2 percent). The drain shall be paved
with concrete not less than 3 inches (76 mm) in thickness, or by
other materials suitable to the apphcation. Discharge from the
drain shall be accomplished in a manner to prevent erosion and
shall be approved by the building official.
J109.4 Drainage across property lines. Drainage across
property lines shall not exceed that which existed prior to grad-
ing. Excess or concentrated drainage shall be contained on site
or directed to an approved drainage facility. Erosion of the
ground in the area of discharge shall be prevented by installa-
tion of nonerosive down drains or other devices.
SECTION J1 10
EROSION CONTROL
JllO.l General. The faces of cut and fill slopes shall be pre-
pared and maintained to control erosion. This control shall be
permitted to consist of effective planting.
Exception: Erosion control measures need not be provided
on cut slopes not subject to erosion due to the erosion-resis-
tant character of the materials.
Erosion control for the slopes shall be installed as soon as
practicable and prior to calling for final inspection.
J110.2 Other devices. Where necessary, check dams, crib-
bing, riprap or other devices or methods shall be employed to
control erosion and provide safety.
SECTION J1 11
REFERENCED STANDARDS
ASTM D Test Method for Laboratory
1557-eOl Compaction Characteristics
of Soil Using Modified Effort
[56,000 ft-lb/ft' (2,700kN-m/m')l.
J107.6
2010 CALIFORNIA BUILDING CODE
721
722 2010 CALIFORNIA BUILDING CODE
APPENDIX K
GROUP R-3 AND GROUP R'3. 1 OCCUPANCIES
PROTECTED BY THE FACILITIES OF THE CENTRAL VALLEY
FLOOD PROTECTION PLAN
Note: The effective date of these standards shall be March 1, 2012 or ninety (90) days after the corresponding maps are
completed and become readily available to the general public, whichever is the later date.
SECTION K101
SCOPE
KlOU General, The provisions of this section shall apply to
new construction, changes of use and to substantial improve-
ment and restoration of substantial damage as defined in Sec-
tion 1612, of Group R-3 and R'3.1 Occupancies in areas
protected by the facilities of the Central Valley Flood Protec-
tion Plan where flood levels are anticipated to exceed three feet
for the 200-year flood event Except as specifically required by
this section, buildings and structures shall meet applicable
provisions of this code.
Exception: Changes of use of Group R-3 to Group R-3. 1
Occupancies, including any substantial improvement done
under the same permit.
K10L1,1 Construction documents. If the land on which the
proposed work is to be constructed is located in an area pro-
tected by the facilities of the Central Valley Flood Protection
Plan, the construction documents shall include the
WSEL200 and the elevation(s) ofthefloor(s), and, as appli-
cable, the elevation(s) and slopes of roofs, of the building or
structure.
SECTION K102
DEFINITIONS
KI02,1 General, The following words and terms shall, for the
purposes of this section, have the meanings shown.
AREAS PROTECTED BY THE FACILITIES OF THE
CENTRAL VALLEY FLOOD PROTECTION PLAN
WHERE FLOOD LEVELS ARE ANTICIPATED TO
EXCEED THREE FEET FOR THE 200'YEAR FLOOD
EVENT, Geographical areas identified by the state as "Areas
Protected by the Facilities of the Central Valley Flood Protec-
tion Plan where Flood Levels are Anticipated to Exceed Three
Feet for the 200-Year Flood Event" in accordance with Health
and Safety Code Section 50465. Published data from the Cali-
fornia Department of Water Resources can he obtained online
at the following website: www.water.ca.gov/BuildingCodes.
Note: The facilities of the Central Valley Flood Protection
Plan are identified in the following counties: Butte, Colusa,
Fresno, Glenn, Lake, Madera, Merced, Plumas, Sacra-
mento, San Joaquin, Solano, Stanislaus, Sutter, Tehama,
Yolo and Yuba. Determination of additional facilities is
ongoing.
CENTRAL VALLEY, Any lands in the bed or along or near the
banks of the Sacramento River and the San Joaquin River, and
any of their tributaries or connected therewith, or upon any
land adjacent thereto, or within any of the overflow basins
thereof, or upon any land susceptible to overflow therefrom.
The following counties and the incorporated municipalities
within these counties, in whole or in part, are in the Central
Valley: Alpine, Amador, Butte, Calaveras, Colusa, El Dorado,
Fresno, Glenn, Lake, Lassen, Madera, Mariposa, Merced,
Modoc, Napa, Nevada, Placer, Plumas, Sacramento, San
Benito, San Joaquin, Shasta, Sierra, Siskiyou, Solano,
Stanislaus, Sutter, Tehama, Tuolumne, Yolo and Yuba. A map
that delineates the Central Valley can be obtained online at the
following website: www.water.ca.gov/BuildingCodes.
EVACUATION LOCATION. A location no less than one (1)
foot (0.30 meter) above the WSEL200 where occupants are
expected to congregate pending evacuation and from which
occupants may be evacuated during conditions of flooding,
such as a space within the building that has an exit door or
operable window; a deck, balcony, porch, rooftop platform or
rooftop area, or combinations thereof
FACILITIES OF THE CENTRAL VALLEY FLOOD PRO-
TECTION PLAN, The facilities referenced herein include the
facilities of State Plan of Flood Control and other flood man-
agement facilities in the Central Valley evaluated under the
Central Valley Flood Protection Plan, which will be completed
in 2012 and updated every 5 years thereafter. The facilities of
State Plan of Flood Control include the state and federal flood
control works (levees, weirs, channels and other features) of
the Sacramento River Flood Control Project described in
Water Code Section 8350, and flood control projects in the Sac-
ramento River and San Joaquin River watersheds authorized
pursuant to Article 2 (commencing with Water Code section
12648) of Chapter 2 of Part 6 of Division 6 for which the Cen-
tral Valley Flood Protection Board or the Department of Water
Resources has provided the assurances of nonfederal coopera-
tion to the United States, and those facilities identified in Water
Code Section 8361.
ROUTE TO THE EVACUATION LOCATION. The path
through and along which occupants move from the habitable
areas of a building or structure that are below the WSEL200 to
the evacuation location,
WSEL200, The water surface elevation (WSEL) of the
200-year flood event that is identified by the state when it iden-
tifies areas that receive protection from the facilities of the Cen-
tral Valley Flood Protection Plan.
2010 CALIFORNIA BUILDING CODE
723
APPENDIX K
SECTION K1 03
STRUCTURAL STABILITY
K103J General Portions of buildings and structures support-
ing evacuation locations shall be designed, constructed, con-
nected and anchored to resist flotation, collapse or permanent
lateral movement resulting from the hydrostatic loads antici-
pated during conditions of flooding anticipated for the
200-year flood event.
K103,2 Determination of loads. Hydrostatic loads, based on
the depth of water determined by the WSEL200, shall be deter-
mined in accordance with Chapter 5 ofASCE 7. Reduction of
hydrostatic loads may be accomplished by allowing for the
automatic entry and exit of floodwaters to minimize unbal-
anced loads. Such means shall be designed by a registered
design professional and include, but are not limited to, open-
ings, valves, and panels designed to yield under load.
Exception: When two flood vents are installed on opposite
sides of the building or structure, one on each side, that
comply with Figure K 1 03.1.
SECTION K104
EVACUATION LOCATIONS
K104,l General An evacuation location and a route to the
evacuation location shall be provided for Group R-3 andR-3.1
Occupancies.
K104,2 Route to evacuation location, A route shall be allowed
through any number of intervening rooms or spaces. Doors
along the route shall be openable without the use of a key or
lock, special knowledge or effort.
Exception: Doors in individual dwelling or sleeping units
having an occupant load of 10 or less are permitted to be
equipped with a night latch, dead bolt or security chain, pro-
vided such devices are openable from the inside without the
use of a key or tool
K104.2,l Group R-3 J Occupancies. The route to an evacu-
ation location shall meet the accessibility requirements of
Chapter llA or IIB as applicable.
K104,3 Minimum size requirements. Evacuation locations
shall provide a minimum gross floor area of? square feet (0.65
m^)per occupant, based on the occupant load of the portions of
the building that are below the WSEL200. The area provided
shall be adequate to accommodate the occupant load of the
upper levels as well as the anticipated occupant load from the
area below the WSEL200.
SECTION K105
SPACE WITHIN THE BUILDING
K105,l General, If the evacuation location is a space within a
building, the evacuation location shall be provided with a
means for occupants to be evacuated out of the building speci-
fied in Sections KlOS.Ll, K105.L2 or K105.1.3.
K105,l.l Windows, minimum size and dimensions, A min-
imum of one window shall be provided that meets the mini-
mum size, minimum dimensions and operational
constraints of Section 1026. The number of such windows
shall be appropriate for the occupancy or occupancies of
the portions of the building that are below the WSEL200.
Note: It is the intent of this section that windows are of
sufficient number, sizes and dimensions to reasonably
accommodate the needs and limitations of the occupants
of the building. Reasonable judgment in the application
of this requirement must be exercised by the building offi-
cial.
K105J,2 Exterior doors to decks, balconies and porches.
Exterior doors to decks, balconies and porches shall be
sized in accordance with Section 1008.
Exception: In Group R-3.1 Occupancies that are subject
to the requirements of Chapters HA or IIB, doors to
decks, balconies or porches shall comply with Section
1132A.1.
K105,l,3 Means of escape to rooftops from spaces within a
building. The means of escape to rooftops shall be permit-
ted to be provided by a stairway, ramp, alternating tread
device, fixed ladder or other means approved by the build-
ing official.
Exception: In Group R-3.1 occupancies that are subject
to the requirements of Chapter HA or IIB, such accessi-
bility requirements shall apply to the means of escape to
rooftops.
SECTION K106
DECKS AND BALCONIES THAT
ARE EVACUATION LOCATIONS
KI06J General. Decks and balconies that have finish floors
no less than one (l)foot (0.30 meter) above the WSEL200 shall
be permitted to be evacuation locations. When a deck or bal-
cony used as an evacuation location is not at the same level as a
floor within the building, it shall be permitted to be accessed by
a stairway, ramp, alternating tread device, fixed ladder or
other means approved by the building ojficial
KI06.2 Live load. Decks and balconies that are evacuation
locations shall be designed for the live load required for the
occupancy as required in Table 1607.2.
K1063 Evacuation route. Evacuation routes to decks and bal-
conies that are evacuation locations shall be permitted to be
provided by a stairway, ramp, alternating tread device, fixed
ladder or other means approved by the building ojficial.
Exception: In Group R-3.1 Occupancies that are subject to
the requirements of Chapter HA orllB, such requirements
shall apply to the evacuation routes to decks and balconies.
724
2010 CALIFORNIA BUILDING CODE
APPENDIX K
EXTEHIOR WALL SIUD (TYP)
2"x4-" BLOCKING F0R PANEL
STUCeO OR WOOD SIDING
SIDING NOT SHOWN
FOR CLARITY
FOUNDATrON
SILL PLATE
hinge; (typ of &)
FOLD^AWAY PANEL
-1/4" GAP
EACH SIDE
2010 CALIFORNIA BUILDING CODE
725
APPENDIX K
STUCGQ
WALL OR
SIDING
GALV.
METAL
HINGE
(TYP)
FOLD-AWAY
PANEL
SILL
PLATE
EXTERIOR WALL STUD
(2"x4")
2''x4" BLOCKING ABOVE
PANEL
GYPSUM WALLBOARD
CAULK ALL JOINTS WITH
WEATHER RESISTANT
CAULKING. INSIDE AND
OUTSIDE OF PANEL
BREAKAWAY PANEL
^ iNiULATlON
GYPSUM WALLBOARD
FOUNDATION
FIGURE K103J
N.T.S.
726
2010 CALIFORNIA BUILDING CODE
APPENDIX K
SECTION K107
ROOFTOP EVACUATION LOCATIONS
K107A General, Rooftop evacuation locations shall he per-
mitted to include rooftop platforms and rooftop areas provided
that they are no less than one (l)foot (0.30 meter) above the
WSEL200, A minimum horizontal distance of three (3) feet
(0.91 meter) shall be provided between the lower edge of the
rooftop evacuation location access point and the evacuation
location lower perimeter
K107,2 Rooftop platforms required, A rooftop platform shall
be provided if the roof covering materials are:
1. Clay tile, concrete tile, slate shingles, wood shingles or
wood shakeSy and the roof slope is three units vertical in
12 units horizontal (25 percent slope) or greater.
2. Metal roof panels or metal roof shingles, and the roof
slope is one unit vertical in 12 units horizontal (8.33 per-
cent slope) or greater.
K1073 Roof live loads. Roof areas that are rooftop evacuation
locations and roofs that support rooftop platforms that are
evacuation locations shall be designed for the roof live load
required for the occupancy as required in Table 1607.2.
K107.4 Evacuation routes to rooftop evacuation locations.
Evacuation routes to rooftop evacuation locations shall be per-
mitted to be provided by a stairway, ramp, alternating tread
device, fixed ladder or other means approved by the building
official
Exception: In Group R-3. 1 occupancies that are subject to
the requirements of Chapter llA or IIB, such requirements
shall apply to the evacuation routes to rooftops.
K107.5 Perimeter protection. For Group R-3 and R-3.1 occu-
pancies, the perimeter of rooftop evacuation locations shall be
protected by:
L Guards per Section 1013 if a rooftop platform is pro-
vided; or
2. A railing that is 12 inches (305 mm) in height if a sloped
roof is provided.
K107.6 Utility/equipment buffer zone. A separation of 48
inches shall be provided between a rooftop evacuation location
and any mechanical equipment, photovoltaic system, utility
service drop or other utility line. Electrical service lines shall
not pass over evacuation locations.
SECTION K108
ATTICS THAT ARE EVACUATION LOCATIONS
K108.1 General. Attics that have finish floors no less than one
(l)foot (0.30 meter) above the WSEL200 shall be permitted to
be evacuation locations.
K108.2 Headroom. When an attic is used as an evacuation
location, the minimum headroom of the required area shall be
30 inches (762 mm) with 50 percent of the required area having
a headroom of 60 inches (1524 mm).
K108.3 Attic flooring. The required area of the evacuation
location shall be solidly sheathed.
K108.4 Attic live loads. Attic areas that are used as evacuation
locations shall be designed for the floor live load required for
the occupancy as required in Table 1607.2.
K108.5 Evacuation routes to attic evacuation locations.
Evacuation routes to attic evacuation locations shall be per-
mitted to be provided by a stairway, ramp^ alternating tread
device, fixed ladder or other means approved by the building
official
Exception: In Group R-3.1 occupancies that are subject to
the requirements of Chapter llA or IIB, such requirements
shall apply to the evacuation routes to attics.
K108.6 Means of escape from attics. The means of escape
from attics shall comply with Section K105.
SECTION K109
ALTERNATE MEANS OF PROTECTION
K109.1 Request for approval of alternate means of protec-
tion. Requests for approval to use an alternative means of pro-
tection shall be made in writing to the building official by the
owner or the owner's authorized representative. The request
shall be accompanied by a full statement of the conditions and
sufficient evidence that the proposed alternate means of protec-
tion provides reasonable protection to occupants. The building
official shall require the owner to obtain a written statement
from the applicable emergency management authority regard-
ing plans and processes related to notification of anticipated
conditions of flooding, warnings, evacuations and other perti-
nent conditions relative to the proximity of nearby levees. The
building official shall also require the owner to obtain a written
statement and findings from the entity that has jurisdiction over
the management, maintenance, monitoring and control of
flood protection works in the vicinity of the location of the
owner's property; such statement shall comment on the viabil-
ity of the proposed alternate means of protection. The building
official may request written statements from the Central Valley
Flood Protection Board, the California Department of Water
Resources, and the California Emergency Management
Agency.
Approval of a request for use of an alternative means of pro-
tection made pursuant to these provisions shall be limited to the
particular case covered by the request and shall not be con-
strued as establishing any precedent for any future request
except in substantially equivalent situations.
Note: Contact information for the California Department of
Water Resources and the Department's Directory of Flood
Officials, which includes levee and reclamation district
boundary maps, is available on-line at the following web
site: www.water.ca.gov/BuildingCodes. The Department of
Water Resources Building Code Project Engineer can be
contacted at 916-574-1451. The Central Valley Flood Con-
trol Board Chief Engineer can be contacted at 916-
574-0609. The California Emergency Management Agency
Inland Region Program Manager can be contacted at
916-845-8488.
2010 CALIFORNIA BUILDING CODE
727
APPENDIX K
K109.2 Appeals. When a request for an alternate means of pro-
tection has been denied by the building official the applicant
may file a written appeal with the board of appeals. In consid-
ering such appeal the board of appeals may provide additional
information to, and request additional written statements from^
the Central Valley Flood Protection Board, the California
Department of Water Resources, and the California Emer-
gency Management Agency, If such additional written state-
ments are provided, the board of appeals shall consider those
statements.
728 2010 CALIFORNIA BUILDING CODE
INDEX
ACCESS OPENINGS
Attic 1209.2
Crawl space 1209.1
Doors 712.3.2
Fire damper 716.4
Fire department 402.17
Mechanical appliances 1209.3
Refuse/laundry chutes 708.13.3
ACCESSIBILITY 1007, Chapters 11 A and 11B,
3411
Accessible fixtures 11 15B.4
Aisles 1133B.6
Airports 412.3.6
Alarms Chapters, 907.9. 1, 907.9.2
Alarms/emergency warning
systems/accessibility 11148.2.2,
907.5.2.1.907.5.2.3
Bathing and toilet facilities
(sanitary facilities) general Chapter 11 A and
1115B
Corridors 1 133B.3
Definitions 1 102B, 202
Design and construction 11 14B. 1
Detectable warnings 1107A.4-D, 1112A.9,
1121B.3.1 (8(a), 1127B.5.7,
1133B.8.5, Part 12
Doors 1 133B.2
Drinking fountains 1 139A
Dwelling units Chapter 1 1A
Egress (see ACCESSIBLE MEANS
OF EGRESS) 1007
Egress and areas of refuge 11 14B.2
Elevators 1007.2.1, 1007.4,
1124A, 1116B,300^.3,3003
Employee work areas 907.5.2.3.2
Entrances Chapter 1 1B (Div III),
1133B.1.1, 1105
Entrances, exits and paths of travel 1133B
Existing buildings 1007.1, Chapter 1 1B (Div V)
Exits Chapter 1 1B (Div IV)
Facility Accessibility 11 14B
Factories and Warehouses 1107B, 1103B.1,
1103B.1(Exc2), 1114B.1.1
Fuel dispensing Chapter 1 1C
General 1114B.2.1, 1007
Group A (Accessibility). 1 104B
Group B (Accessibility) 1 105B, 1 1 14B. 1. 1
Group E (Accessibility) 1 106B, 1 1 14B. 1. 1
Group H (Accessibility) 1 108B
Group I (Accessibility) 1 109B
Group M (Accessibility) 1110B
Group R (Accessibility) 1111B
Hazard 1116A, 1125A, 1133B.8
Kitchens 1 133A
Laundry 1127A, 1135A
Lifts 1007.5, 1124A
Live/work unit 419.7
Multi family dwellings (covered) Chapter 1 1A
New buildings (Accessibility) Chapter 1 1B (Div I)
Paths of travel Chapter 11B (Div IV)
Parking and passenger loading facilities 1109A
Platform (Wheelchair) Lift 1116B.2
Ramps 1010, Chapter 11 A, 1133B.5
Residential occupancies Chapter 1 1A
Route 1114B.1.2
Scoping 1101 A.I, 108.2
Signage Chapter 1 1A
Signs and Identification 11 17B.5
Site Accessibility Chapter 1 1B (Div II)
Stain/vays 1133B.4
Storage Chapter 1 1A
Telephone 1140A ,E106
Toilet and bathing facilities Chapter 1 1A
Train and light rail stations E109
Transient lodging 202, 1 102A,
1107A.20-T,E^04.2,E^04.3
Walks and Sidewalks 1 133B.7
ACCESSIBLE MEANS OF EGRESS 1007
Accessible Routes 11 14B. 1.2
Access to Chapter 1 1B
Alarms/emergency warning
systems/accessibility 1007. 12
Areas of refuge (see AREA OF REFUGE). . . 1007.6,
1114B.1.2
Assembly 1007.1, 1028.8
Applicability 1003. 1
Continuity and components 1007.2, 1114B.1.2
Definition 1002.1
Egress from Chapter 1 1B
Elevators 1007.2.1, 1007.4, 1007.8
1116B,3003
Existing building 1007.1
Exterior area for assisted rescue
(see EXTERIOR AREA FOR
ASSISTED RESCUE) 705, 1007.6.1, 1007.7
Exterior exit stainA^ays 1007.7.2, 1007.3,
1023, 1133B.4
Horizontal exit (see HORIZONTAL EXIT)
Identification 1007.6.5, 1007.8.3,
1117B.5.1 (Item 1,2)
Instructions 1007.6.4, 1 117B.5. 1 (Item 2)
Interior exit stainA^ays 11007.3, 1020, 1133B.4
Mezzanine 505, 1007.1
Openess 1007.5.1, 1007.7.1
Platform lift 1007.5, 1116B (Items 1-4),
1116B.2, 1116B.2.5
Ramps 1010, 1133B.5
Required 1007.1, Chapter 11B
Separation 709, 1007.6.2, 1022
Size 1007.6.1
Stairs 1002.1, 1007.3, 1115A, 1123A, 1133B.4
2010 CALIFORNIA BUILDING CODE
729
INDEX
Signage 7007. /through 1007.11, Chapter 11 A,
1117B.5.1 (Items 2, 3), 3002. 3
Two-way communication 1007.6.3
Visible communication metliod . 1007.6.3.1, 1117B.6
ACCESSORY OCCUPANCIES . . . 303.1 . 305.1 , 508.2
Incidental accessory occupancies . . 508.2.5, 707.3.6
ADAPTABLE DWELLING UNIT (definition) 202,
1107A.1-A
ADDITION 3403. D103.1
Accessibility 1101 A.I
Means of egress 1003, 3302.1 , 3310
ADMINISTRATION (CALIFORNIA) . . Chapter 1 (Div I),
Chapter 1 (Div II)
ADOBE CONSTRUCTION 2102.1, 2109.3
AEROSOLS 307.1, 307.2, 311.2,
414.1.2.1,414.2.5,907.2.16
AGRICULTURAL BUILDINGS
(see GROUP U) 312.1, Appendix
AIR CONDITIONING
(see MECHANICAL) 101 .4.2, 2801.1, 3006.2
AIR INTAKES (see YARDS OR COURTS) . . . 1206.3.2
AIRCRAFT HANGARS 412.4
Aircraft paint hangars 412.6, 507.9
Basements 412.4.2
Construction 412.4.1, 412.6.2
Fire area 412.4.6.2
Fire suppression system 412.4.6, 4 2.6.5
Heliports and helistops 412.7
Residential 412.5, 907.2.21
Unlimited height and area 504.1 , 507.9
AIRCRAFT-RELATED OCCUPANCIES 412
Airport traffic control towers 412.3, 907.2.22
Construction type 412.3.2
Egress. 412.3.3
Fire detection systems, automatic 412.3.4,
907.2.22
Standby power 41 2.3.5, 2702.2.18
Traffic control towers 412.3
Type of construction 412.3.2
AISLE
Access aisle 1 102B
Assembly seating 1028.6, ) 1048.3. 1
Bleachers 1028.1.1
Converging 1028.9.3
Egress 1017, Chapter 11A
Folding and telescopic seating 1028.1.1
Grandstands 1028.1.1
Obstructions 1028.9.6
Tents 3103.4
Walking surfaces 1028.1 1
Width ^028.9, 1133B.6.2
ALARM SYSTEMS, EMERGENCY 908
ALARMS, FIRE (see FIRE ALARM AND SMOKE
DETECTION SYSTEMS)
ALARMS, VISIBLE 420.4.4, 907.5.2.3
Common areas 907.5.2.3.1
Employee work areas 907.2.5.3.2
Group 1-1 907.5.2.3.3
Group R-1 907.5.2.3.3
Group R-2 907.5.2.3.4
Public areas 907.5.2.3.1
ALARMS, VOICE 907.5.2.2
Amusement buildings, special 41 1 .6, 2702.2.1
Covered mall buildings 402.14, 402.15,
907.2.20,2702.2.14
High-rise buildings 403.4.3, 907.2.13
Special amusement buildings 41 1 .6
Underground buildings 405.9.1,
907.2.18,907.2.19
ALLOWABLE STRESS DESIGN 1602.1
Load combinations 1605.3
Masonry design 2101.2.1,2107
Wood design .2301.2, 2306
ALTERATIONS. 3404, D103.1
Compliance alternatives 3412
Means of egress .3302.1,3310.2
ALTERNATIVE MATERIALS,
DESIGN AND METHODS 104.11
ALTERNATING TREAD DEVICES 1009.10
Construction 1009.10.2
Equipment platform 505.5
Galleries, catwalks and gridirons . . 410.5.3, 1015.6.1
Heliports 412.7.3
ALUMINUM 1404.5.1, 1604.3.5, Chapter 20
AMBULATORY HEALTH CARE FACILITIES 422
Fire alarm and smoke detection 907.2.2.1
Smoke compartment 422.2, 422.4
AMUSEMENT BUILDING, SPECIAL 411
Classification 41 1 .1
Emergency voice/alarm
communications system 41 1 .6, 907.2.12
Exit marking 41 1 .7
Fire detection 41 1 .3, 411 .5, 907.2.12
Interior finish 41 1 .8
Smoke detection system 41 1 .3, 41 1 .5, 907.2.12
Sprinklers 41 1 .4
AMUSEMENT PARK STRUCTURES .303
ANCHOR STORE (see COVERED MALL
AND OPEN MALL BUILDINGS) 402
Construction type 402.6
Means of egress 402.4.3.1
Occupant load 402.4.1 .1 , 402.4.1 .3
Separation 402.7.1 , 402.7.3
Sprinkler 402.9
ANCHORAGE 1604.8
Braced wall line sills 2308.3.3
Concrete 1911, 1912
Conventional light-frame construction . . 2308.11.3.1,
2308.12.7, 2308.12.8, 2308.12.9
Decks 1 604.8.3
Seismic anchorage for masonry chimneys ... 21 13.4
Seismic anchorage for masonry fireplaces ... 21 1 1 .4
Walls 1604.8.2
Wood sill plates 2308.3.3
APARTMENT HOUSES 310.1
APPEALS.
.113
730
2010 CALIFORNIA BUILDING CODE
INDEX
APPENDICES 1.1.4
APPROVED (definition) 202
APPROVED LISTING AGENCY (definition) 202
APPROVED TESTING AGENCY (definition) 202
ARCHITECT (see definition for REGISTERED
DESIGN PROFESSIONAL)
ARCHITECTURAL TRIM. . . 603.1, 1406.2.2, D102.2.7
AREA, BUILDING Chapters
Aircraft control towers 412.3.2
Aircraft hangars, residential 412.5.5
Covered mall building 402.6
Enclosed parking garage 509.2, 509.3,
509.4, 509.9
Limitations 503, 505
Membrane structures 3102.4
Mezzanines 505.2, 505.5
Mixed construction types 3102.6
Mixed occupancy 508
Modifications 506, 509
Open mall building 402.6
Open parking garage 406.3.6, 406.3.7,
509.2, 509.3, 509.4,
509.7, 509.8, 509.9
Private garages and carports 406.1 .1 , 406.1 .2
Unlimited area 503.1 .3, 506.2.1 , 507
AREA FOR ASSISTED RESCUE, EXTERIOR
(see EXTERIOR AREAS FOR ASSISTED RESCUE)
AREA OF REFUGE
(see ACCESSIBLE MEANS OF EGRESS)
Definition 1002. 1
Egress and areas of refuge 1114B.2
Identification 1007.6.5, 101 1.2,
1117B.5.1 (Items 1,2)
Instructions 1007.6.4, 1 117B.5. 1 (Item 2)
Requirements 1007.6, 1007.6.1,
1007.6.2,77 746.7.2
Separation 709, 1007.6.2, 1022
Signage 1007.9, 1007.10, 1007.11, 7 7 7S^
Size 1007.6.1. 1009, 11338.4
Two-way communication 1007.6.3,
1007.8,1007.11
Visible communication method 1007.6.3. 1
Where required 1007.2, 1007.3. 1007.4
ASSEMBLY OCCUPANCY (GROUP A) . . . 303, 1028
Accessory 508.2
Aisles 1017.4, 1028.9
Amusement buildings, special 41 1
Area 503, 505, 506, 507, 508
Assistive-listening systems 1104B.2
Bleachers (see BLEACHERS)
Dining, banquet and bar facilities 1104B.5
Egress, special provisions 1008.1.10, 1028.3
Fire alarms 907.2.1
Folding and telescopic seating 1028.1 .1
Guards (Guardrails) 1002.1, 1013.1, 1028.14
Grandstands (see GRANDSTANDS)
Height 503, 504, 505, 506, 508, 509
High-rise 403.1
Interior finishes Table 803.9, 804
Live load Table 1607.1, 1607.9.1.4, 1607.11.2.2
Motion picture theaters 409, 507.1 1
Occupancy category Table 1604.5
Panic hardware 1008.1.10, 1008.2.1
Parking beneath or above 509.2, 509.7, 509.9
Plumbing fixtures 2902
Religious facilities 7 104B.6
Seating, fixed (see SEATING, FIXED)
Seating, smoke-protected 1028.6.2
Special occupancy separation 303.1,
Table 508.2.5, Table 508.4
Sprinklers 507.3, 507.6, 507.7, 507.11, 903.2.1
Stages and platforms 410
Standby power systems 2702.2.1
Standpipes 905.3.2, 905.5.1
Travel distance 1014.3, 1016.1, 1021.2. 1028.7
Unlimited area 507.3, 507.6, 507.7, 507.1 1
ASSISTED LIVING (see RESIDENTIAL
CARE/ASSISTED LIVING FACILITIES)
ASSISTIVE DEVICE 202, 1107A.1-A
ATRIUM 404
Automatic sprinkler protection 404.3
Enclosure 404.6, 707.3.5
Fire alarm system 404.4, 907.2.14
Interior finish 404.8
Smoke control 404.5, 909
Standby power 404.7
Travel distance 404.9, 1014.3, 1016.1, 1021.2
Use. . 404.2
ATTIC
Access 1209.2
Combustible storage 413.2
Draftstopping 717.4
Insulation 719.3.1
Live load Table 1607.1
Unusable space fire protection 712.3.3
Ventilation 1203.2
AUDITORIUM 303.1
Accessibility 1104B.3
Foyers and lobbies 1028.4
Interior balconies and galleries 1028.5
Motion picture projection rooms 409
Stages and platforms 410
AUTOMATIC DOOR (definition) 202, 7 107A. 1-A
AUTOIVIATIC TELLER MACHINE
(POINT OF SALE MACHINE 77778.7
ATM equipment for persons with
vision impairments 1117B.7.6
Clearances and reach range 1117B.7.4
Where one ATM is provided 7 117B.7.4. 1
Where three or more ATMs are provided. .111 7B.4.3
Where two ATMs are provided 7 77S. 7.4.2
Controls 1117B.7.3
Display 1117B.7.5
General 1117B.7.2
AUTOMOBILE PARKING GARAGE
(see GARAGE, AUTOMOBILE PARKING) 406
AVAILABILITY OF CODES 7.7.70
2010 CALIFORNIA BUILDING CODE
731
INDEX
AWNINGS 3105
Design and construction 3105.3
Drainage, water 3201 .4
Encroachment, public right-of-way 3202.2.3,
3202.3.1,3202.4
Fire district D102.2.8
Live load Table 1607.1, 1607.11.2.1,
1607.11.4
Materials 3105.4
Motor vehicle service stations 406.5.3
Permanent D102.2.8
Plastic 2606.10
B
BALCONIES
Accessibility 1120A, 1104B.3.5(Exc. 1),
11118.4.2.1(4), 1133B.3
Assembly 1028.5
Construction, exterior 1406.3
Egress, means of 1016.2, 1019, 1028.5
Emergency escape 1029.1
Exterior egress 1016.2
Guards (or Guardrails) 1002.1, 1013.1
Live load Table 1 607.1
Projection 705.2, 1406.3
Public right-of-way encroachments 3202.3.2,
3202.3.3
Travel distance 1016.2
BARBECUES.
.2801
BARRIERS
Fire (see FIRE BARRIER)
Pedestrian protection 3306
Smoke (see SMOKE BARRIER)
Vehicle 406.2.4, 1602.1, 1607.7.3
BASEMENT (see UNDERGROUND BUILDINGS)
Aircraft hangars 412.4.2
Area modification 506.4, 506.5
Considered a story 502.1
Emergency escape 1029^1
Flood loads 1612.2, 1612.5
Height modifications for 509.5
Prohibited 415.1,415.4,415.5,
415.8.5.2.2,418.1
Rodentproofing Appendix F
Sprinklers 903.2.11.1
Waterproofing and dampproofing 1805
BASEMENT WALLS
Concrete Table 1904.3, 1909.6.1
Soil loads 1610.1
Waterproofing and dampproofing 1805
BASIC WIND SPEED 1609.3
BATHING AND TOILET FACILITIES
(SANITARY FACILITIES) ACCESSIBLE .... 1127A,
1134A
BATHING AND TOILET FACILITIES
(SANITARY FACILITIES) 1115B
Accessories 11 15B.8
Bath and stiower facilities 11 15B.2
Bathtubs (Accessible) 11 15B.4.5
Children (Where used by) 1115B.1.2
Diameter/width
(Grab bar gripping surface) 1115B.7.1
Enclosures (Showers) 11 15B.4.4. 10
Fixtures (Accessible) 11 15B, 1 1 15B.4
Floor slope (Showers) 1 15B.4.4.7
General (Accessibility) 11 15B. 1
Grab bars, tub and shower seats 11 15B.7
Hand-held sprayer unit (Showers) 1115B.4.4.5
Identification symbols 11 15B.6
Lavatories (Accessible) 11 15B.4.3
Lockers (Accessories) 11 15B.8.5
Medicine cabinets (Accessories) 11 15B.8.2
Men's Sanitary Facilities (Symbol) 11 15B.6. 1
Mirrors (Accessories) 11 15B.8. 1
Multiple-accommodation 11 15B.3. 1
Orientation (Showers) 11 15B.4.4.3
Passageways 11 15B.5
Separate and unisex facilities 11 15B. 1. 1
Shower accessories 1115B.4.4.8
Showers (Accessible) 1115B.4.4
Single-accommodation 1115B.3.2
Size and clearances (Showers) 11 15B.4.4. 1
Soap dish (Showers) 11 15B.4.4.9
Sprayer unit alternative (Showers) 1115B.4.4.6
Structural strength
(Grab bars, tub and shower seats) 11 15B. 7.2
Surface (Grab bar/wall) 1115B.7.3
Thresholds (Showers) 1115B.4.4.2
Toilet facilities 11 15B.3
Toilet tissue dispensers (Accessories ) ... 11 15B.8.4
Towel, sanitary napkins, waste receptacles,
dispensers & controls (Accessories). . . . 11 15B.8.3
Uninals (Accessible) 11 15B.4.2
Unisex sanitary facilities (Symbol) 11 15B.6.3
Water closets (Accessible) 11 15B.4. 1
Water controls (Showers) 1115B.4.4.4
Women's sanitary facilities (Symbol) 1115B.6.2
BATHROOM (ACCESSIBLE) 1107A.2-B
For efficiency dwelling units 1208.4
BAY AND ORIEL WINDOWS 1406.4
Public right-of-way encroachments 3202.3.2,
3202.3.3
BLEACHERS 303.1, 1028.1.1, 3401.1
Accessibility 1104B.3.5 (Exc.1), 1104B.4
Egress 1028.1.1
Live load Table 1607.1
Occupant load 1004.7
BLOCK (see CONCRETE BLOCK
AND GLASS UNIT MASONRY)
BOARD OF APPEALS 113, Appendix B
Application for appeal B101.1
Alternate members B101.2.1
Board decision B101.4
Limitations on authority 1 13.2
Membership of board B101 .2
Notice of meeting B101 .3
Qualifications 1 13.3, B101.2.2
732
2010 CALIFORNIA BUILDING CODE
INDEX
BOILER ROOM
Exits 1015.3
BOLTS 2204.2
Anchors ...1911, 1912,2204.2.1
High strength, steel 1704.3.3
BONDING, MASONRY 2103.9, 2109.2
BRACED WALL LINE 2302.1 , 2308.3
Bracing 2309.3
Seisnnic requirements 2308.12.2, 2308.12.4,
2308.12.6
Sill anchorage 2308.3.3
Spacing 2308.3.1
Support 2308.3.4
BRACED WALL PANEL 2302.1, 2308.9.3
Alternative bracing 2308.9.3.1, 2308.9.3.2
Connections 2308.3.2
BRICK (see MASONRY)
BUILDING
Access, fire department 402.17
Accessibility 1 133B. 1
Accessibility (scope) / 101 A. 1
Area (see AREA, BUILDING) 502.1 , 503,
505, 506, 507, 508, 509
Definition 202
Demolition 3303
Existing 202, Chapter 34
Fire walls 706.1
Height (see HEIGHT, BUILDING) 502.1,
503, 504, 505,
506, 508, 509
Occupancy classification Chapter 3
Other building components 1117B
Party walls 706.1 .1
BUILDING ACCESSIBILITY 1103B
Distance to elevators 1 103B.2
Scope 1 103B. 1
Floors or portions of floors
(not customarily occupied) 1103B.1(Exc. 1)
Multistoried office buildings
(other than the professional office
of a health care provider) 1 103B. 1(Exc. 2. 1)
Other privately funded
Multistoried 1103B.1(Exc.2.2)
Privately funded multistory 1 103B. 1(Exc. 2)
BUILDING DEPARTMENT . 103
BUILDING ENTRANCE ON AN
ACCESSIBLE ROUTE (definition). . 202, 1107A.2'B
BUILDING OFFICIAL
Duties and powers 104
Qualifications A101.1
Records 104.7
Termination A101.4
BUILT-UP ROOFS 1507.10
BUSINESS OCCUPANCY (GROUP B) .. . 304, 1105B
Accessory 508.2
Aisles 1017.2
Ambulatory health care facilities 422
Area 503, 505, 506, 507, 508
Assembly 303.1
Business and professional offices 1105B.3.2
Educational 303.1 , 304.1
Fire alarm 907.2.2
Height 503, 504, 505, 506, 508, 509
Interior finishes Table 803.9, 804
Live load Table 1607.1
Miscellaneous general standards 1105B.3.6
Office buildings and personal and
public service facilities 1 105B.3
Parking under or above 509.2, 509.7,
509.8, 509.9
Personal and public service facilities 1 105B.3.3
Plumbing fixtures 2902
Police department, law enforcement, fire
department facilities and courtrooms . . . 1105B.3.5
Public utility facilities 1 105B.3A
Special occupancy separation . . 303.1 , Table 508.2.5
Travel distance 1014.3, 1016.1, 1021.2
Unlimited area 507.3, 507.4
CABLES, STEEL STRUCTURAL 2207
CALCULATED FIRE RESISTANCE
(see FIRE RESISTANCE, CALCULATED)
CANOPIES 3105
Design and construction 3105.3
Drainage, water 3201 .4
Encroachment, public right-of-way 3202.3.1
Fire district D102.2.8
Live load Table 1 607.1 ,
1607.11.2.1, 1607.11.4
Materials 3105.4
Motor vehicle service stations 406.5.3
Permanent D102.2.8
Plastic 2606.10
CALIFORNIA ADMINISTRATION
Chapter 1, Division I
CARBON MONOXIDE ALARI\/IS (residential) . . 420.4
CARE FACILITIES (see HEALTH CARE)
CARPET
Floor covering 804.2
Textile ceiling finish 803.6
Textile wall coverings 803.5
CATWALKS
Live loads Table 1607.1
Means of egress 410.3.2, 1015.6.1
Sprinklers 410.6
CEILING
Acoustical 808
Height 409.2, 909.20.4.3, 1205.2.2, 1208.2
Interior finish 803
Penetration of fire resistant assemblies 713.4,
716.2,716.6
Suspended acoustical 808.1 .1
CELL (definition) 308.4.6
CELL COMPLEX (definition) 308.4.6
CELL TIERS (definition) 308.4.6
2010 CALIFORNIA BUILDING CODE
733
INDEX
CELLULOSE NITRATE FILM 409.1, 903.2.5.3
CERAMIC TILE
Material requirements 2103.5
Mortar 2103.10
CERTIFICATE OF OCCUPANCY . . 106.2, 111, 3408.2
Certificate issued Chapter 1 Div 11-11 1.2
CHANGE OF OCCUPANCY 3408, D103.2
Accessibility 3412.2.5
CHILD CARE (see DAY CARE) 305.2, 308.3.1,
308.5.2,310.1
CHIMNEYS 2102.1, 2111, 2112, 2113
Factory-built 717.2.5
Flashing 1 503.6
Protection from adjacent construction 3307.1
CHURCHES
(see RELIGIOUS WORSHIP, PLACES OF)
CIRCULAR STAIRS (see CURVED STAIRWAYS)
CIRCULATION PATH (definition) 202
CITY, COUNTY, AMENDMENTS,
ADDITIONS OR DELETIONS 1.1.8
Findings and filings 1. 1.8. 1
CLAY ROOF TILE 1507.3
Testing 1716.2
CLINIC
Hospital 308.3
Outpatient (see AMBULATORY
HEALTH CARE FACILITIES) 304.1.1, 422
CLINICS - BIRTHING CLINICS 1226. 16
CLINICS - GENERAL REQUIREMENTS
Application 1226.2
Ceiling Heights 1226.8
Corridors and Hallways 1226.5
Definitions 1226.3
Doors and Door Openings 1226.6
Elevators 1226.11
Garbage-Solid Wastes and Trash Storage . . 1226. 12
General Construction 1226.4
Interior Finishes-Floors and Bases 1226.9
Laundry and Trash Chutes 1226. 13
Scope 1226. 1
Windows and Screens 1226.7
Walls and Ceilings 1226. 10
CLINICS - PRIMARY CARE
Abortion Services 1226. 14
Clinical Facilities 1226. 15
CLINICIS ' PYSCHOLOGY CLINICS 1226.20
CLINICS - SPECIALTY CLINICS
Chronic Dialysis Clinics 1226. 18
Rehabilitation Clinics 1226. 19
Surgical Clinics 1226.17
COAL POCKETS 415.6.1.6
CODES 101.2, 101.4, 102.3,
102.4, 102.6, Chapter 35
COLD STORAGE
(see FOAM PLASTIC INSULATION)
COLD-FORMED STEEL 2202.1 , 2209
Light-frame construction 2210
Special inspection 1704.3.1.2, 1704.3.4,
1706.3, 1707.4
COMBUSTIBLE DUSTS 415.6.1
COMBUSTIBLE LIQUIDS 307.4, 307.5, 415.6.2
COMBUSTIBLE MATERIAL
Concealed spaces 413.2, 717.5
Exterior side of exterior wall 1406
High-pile stock or rack storage 413.1, 910.2.2
Type I and Type II 603, 805
COMBUSTIBLE PROJECTIONS 705.2, 1406.3
COMBUSTIBLE STORAGE 413, 910.2.2
COMMON PATH OF EGRESS TRAVEL 1014.3
COMPARTMENTATION
Ambulatory Health Care Facilities 422.2
Group 1-2 407.4
Group 1-3 408.6
Underground buildings 405.4
Values 3412.6.3
COMPLIANCE ALTERNATIVES 3412
COMPRESSED GAS 307.2, 415.8.7.2.2
CONCEALED SPACES 413.2, 717
CONCRETE Chapter 19
ACI modifications 1901.2, 1901.3
1902.1,1903.1, 1908
Anchorage 1911, 1912
Calculated fire resistance 721.2
Conduits 1906
Construction documents 1901.4
Construction joints 1906
Curing 195.11
Durability 1904
Exposure conditions 1904
Footings 1809
Formwork 1906
Foundation walls 1807.1.5, 1808.8
Materials 1704.4.1, 1903
Mixing 1905.8
Pipe columns, concrete-filled 1915
Pipes 1906
Placing 1905
Plain, structural 1909
Proportioning 1905.2
Quality 1905
Reinforced gypsum concrete 1914
Reinforcement .1 907
Rodentproofing Appendix F
Roof tile 1507.3, 1716.2
Shotcrete 1913
Slab, minimum 1910
Special inspections 1704.4, Table 1704.4
Specifications 1 903
Strength testing 1704.4.1, 1905.6
Wood support 2304.12
CONCRETE MASONRY
Calculated fire resistance 721 .3
Construction 21 04
Design 2101.2, 2108, 2109
Materials 2103.1
734
2010 CALIFORNIA BUILDING CODE
INDEX
Surface bonding 2109.2
Testing 2105.2.2.2. 2105.3
Wood support 2304.12
CONCRETE ROOF TILE 1507.3
Wind resistance 1609.5.3, 1716.2
CONDOMINIUM (see APARTMENT HOUSES)
CONDUIT, PENETRATION PROTECTION 713.3,
1022.4
CONFLICTS IN CODE 102.1
CONGREGATE LIVING FACILITIES 310
CONSTRUCTION (see SAFEGUARDS DURING
CONSTRUCTION)
CONSTRUCTION DOCUMENTS 107, 1603
Concrete construction 1901.4
Design load-bearing capacity 1803.6
Fire alarm and detection systems 907.1.1
Fire-resistant-joint systems 714
Flood 1603.1.7
Floor live load 1603.1.1
Geotechnical 1603.1.6
Masonry 2101.3
Means of egress 107.2.3
Penetrations 713
Permit application 105.1
Retention 107.5
Review 107.3
Roof assemblies 1 503
Roof live load 1603.1 .2
Roof snow load 1603.1 .3
Seismic. 1603.1.5, 1603.1.9
Site plan 107.2.5
Soil classification 1803.6
Special inspections 1703, 1705
Special loads 1603.1 .8
Structural tests .1703
Systems and components 1603.1.9
Temporary structures 3103.2
Wind load 1603.1.4
CONSTRUCTION JOINTS
Concrete 1 906.4
Shotcrete 1913.7
CONSTRUCTION TYPES Chapter 6
Aircraft related 412.3.2
Automobile parking garage Table 406.3.3,
509.2, 509.3, 509.4,
509.7, 509.8, 509.9
Classification 602
Combustible material
in Type I and Type II construction 603, 805
Covered mall and open mall buildings 402.6
Fire district D102.2.3
Fire resistance Table 601 , Table 602
High-rise 403.2
Type I Table 601 , 602.2, 603
Type II Table 601 , 602.2, 603
Type III Table 601, 602.3
Type IV .Table 601, 602.4
Type V Table 601, 602.5
Underground buildings 405.2
CONTRACTOR'S RESPONSIBILITIES. . . 901.5, 1706
CONTROL AREA 414.2,707.3.7
Fire-resistance rating 414.2.4
Number 414.2.3
CONTROLS AND
OPERATING MECHANISMS 1117B.6
Clear floor space 11178.6(2)
General 11178.6(1)
Height 11178.6(3)
Installation heights of electrical
switches and receptacle outlets 1 1178.6(5)
Electrical receptacle outlets 11178.6(5.2)
Electrical switches 1 1178.6(5. 1)
Operation 1 1178.6(4)
CONVENTIONAL LIGHT-FRAME
CONSTRUCTION 2301 .2, 2302.1 , 2308
Additional seismic requirements. . . 2308.1 1 , 2308.12
Braced wall lines 2308.3
Connections and fasteners 2308.5
Design of elements 2308.4
Floor joists 2308.8
Foundation plates or sills 2308.6
Girders 2308.7
Limitations 2308.2
Roof and ceiling framing 2308.10
Wall framing 2308.9
CONVEYING SYSTEMS 3005
Accessibility 1 124A, 3001. 1, 3001.3
CORNICES
Draftstopping 717.2.6
Live load Table 1607.1
Masonry . 2104.2.1
Projection 705.2, 1406.3
Public right-of-way encroachments 3202.3.2,
3202.3.3
CORRECTIONAL TREATMENT CENTERS
Application 1227.2
Ceiling Heights 1227.8
Corridors 1227.5
Definitions 1227.3
Doors and Door Openings 1227.6
Elevators 1227. 10
Garbage-Solid Waste and Trash Storage . . . 1227. 1 1
General Construction 1227.4
Scope 1227. 1
Windows and Screens 1227.7
Interior Finishes 1227.9
CORRECTIONAL TREATMENT CENTERS - BASIC
SERVICES
Administration Space 1227. 16
Central Sterile Supply 1227.17
Dietetic Service Space 1227. 14
Employee Dressing Rooms and Lockers . . . 1227. 19
Housekeeping Room 1227.20
Nursing Service Space 1227. 12
Offices 1227.15
Pharmaceutical Service Space 1227. 13
Storage 1227.18
2010 CALIFORNIA BUILDING CODE
735
INDEX
CORRECTIONAL TREATMENT CENTERS
OPTIONAL SERVICES
24-Hour Mental Health Care Services 1227.23
Outpatient Services 1227.22
Service Spaces 1227.21
CORRIDOR (see CORRIDOR PROTECTION,
EXIT ACCESS and FIRE PARTITIONS) 1018
Aisles 1017, 1 133B.6
Continuity 1018.6
Deadend 1018.4
Elevation change 1003.5
GroupBandM 017.2,11038.1 (Exc.2),
1123B.2(Exc.)
Group 1-2 407.2
Hazardous 415.8.2.2, 415.8.2.7,
415.8.3, 415.8.4, 415.8.6, 415.8.7.1.4
Headroom 1003.2, 1003.3
HPM service 903.2.5.2
Live load Table 1607.1
Walls 709.1,1018.1
Width 1018.2
CORRIDOR PROTECTION, EXIT ACCESS
Construction, fire protection 709.1 ,
Table 1018.1, 1018.6
Doors 715.4
Glazing 715.5
Group 1-2 407.3
Interior finish Table 803.9, 804.4
Opening protection 715, 716.5.4.1
Ventilation 1018.5, 1018.5.1
CORROSIVES 307.6, Table 414.2.5(1), 414.3,
415.7.3,Table 415.8.2.1.1
COURTS (see YARDS OR COURTS) 1206
COVERED MALL AND
OPEN MALL BUILDINGS 402
Construction type 402.6
Fire department 402.3, 402.17
Fire detection/alarm system 402.4.5.1 , 402.1 1 ,
402.12.2,402.15,
907.2.20,2702.2.14
Interior finish 402.8
Kiosk 402.11
Means of egress 402.4, 402.5, 402.13
Occupant load 402.4.1
Playground structures 402.12
Separation 402.7
Signs 402.16
Smoke control 402.10
Sprinklers 402.9
Standby power 402.14, 2702.2.14
Standpipe system 402.9.1 , 905.3.3
Travel distance 402.4, 1014.3, 1016.1, 1021.2
COVERED MULTIFAMILY
DWELLINGS (definition) 202,1 107A.3-C
COVERED WALKWAY 3306.7
CRAWL SPACE
Access 1209.1
Drainage 1805.1 .2
Unusable space fire protection 712.3.3
Ventilation 1203.3
CRIPPLE WALL 2302.1, 2308.9.4
CROSS SLOPE (definition) 202, 1107A.3-C
CRYOGENIC Table 307.1 ,Table 414.5.1 ,
Table 415.8.2.1.1
CURB CUT (definition) 202, 1107A.3'C
CURB RAMP (definition) 202, 1 107A.3-C
DAMPERS (see FIRE DAMPERS
AND SMOKE DAMPERS) 716.2 through 716.5
DAMPPROOFING AND WATERPROOFING .... 1805
Required 1805.2, 1805.3
Subsoil drainage system 1805.4
DAY CARE 305.2, 308.5, 310.1
Adult care 308.5.1
Child care 308.5.2, 310.1
Egress 308.5.2, Table 1004.1.1,
Table 1015.1, Table 1021.2
DAY SURGERY CENTER
(see AMBULATORY HEALTH CARE FACILITIES)
DEADEND 1018.4
DEAD LOAD 1602.1 , 1606
Foundation design load 1808.3
DECK
Anchorage 1604.8.3
Live loads Table 1607.1
DEFINITIONS (Access) Chapter 2, Chapter 1 1A,
Chapter 1 1B, Chapter 1 1C
Dormitory (Group I & R Definitions) . . 308.4.6, 310.2
Means of Egress Definitions:
Accessible Means of Egress 1002. 1
Area of Refuge 1002. 1
Exit 1002.1
Guard (or Guardrail) 1002. 1
Handrail 1002.1
Public Way 1002.1
Stair 1002.1
Stain/vay 1002. 1
Newly Constructed
(Housing accessibility definition) 1107A.14-N
Platform (Use and Occupancy definition) 410.2
Platform (wheelchair) lift
(Use and Occupancy definition) 410.2
Stage (Use and Occupancy definition) 410.2
DEFLECTIONS 1604.3.1
Framing supporting glass 2403.3
Preconstruction load tests 1715.3.2
Wood diaphragms 2305
Wood shear walls 2305
DEMOLITION 3303
DESIGN STRENGTH 1602.1, 2102.1
Conformance to standards 171 1 .1
New materials 171 1 .2
DESIGNATED SEISMIC SYSTEM 1702.1
Seismic qualification 1708.4
736
2010 CALIFORNIA BUILDING CODE
INDEX
Special inspection 1707.8
DETACHED SINGLE-FAMILY DWELLING 202
DETECTABLE WARNING
(definition) 202, 1107A.4-D
DIAPHRAGMS 1602.1,2302.1
Flexible 1613.6.1
Special inspection 1704.6.1, 1706.2, 1707.3
Wood 2305, 2306.2
DIVISION OF THE
STATE ARCHITECT Chapter 1 (Div I), 1.9
Access Compliance (DSA-AC) 1.9. 1
Application (DSA-AC Pn'vately funded) 1.9. 1.2
Sanitary facilities 1.9. 1.2.2
Used by general public 1.9. 1.2. 1
Application (DSA-AC Public housing
& private housing) 1.9. 1.3
Application (DSA-AC Publicly funded) 1.9.1.1
Congregate residences or one- or
two'family dwelling units 1.9. 1. 1.3
Existing publicly funded buildings 1.9.1.1.4
Leased, rented, contracted, sublet,
hired by municipal, county, or state
division of government, special district . . . 1.9. 1. 1.2
Not requiring a building permit 1.9. 1. 1.5
Use of state, county or municipal funds .... 1.9. 1. 1. 1
Authority (DSA-AC) 1.9.1.6
Enforcing agency (DSA-AC) 1.9. 1.4
Building department 1.9. 1.4.3
Director of the Dept of General Services ... 1.9.1.4.1
Governing bodies 1.9. 1.4.2
Law/Reference sited (DSA-AC) 1.9. 1.7
Special conditions for persons with disabilities
(DSA-AC) 1.9.1.5
DIRECTIONAL SIGN 202
DOORS 1008, Chapter 11A, 1133B.2
Access-controlled 1008.1 .4.4
Accessibility 1 126A, 1 132A
Delayed egress locks 903.3.1.1, 907, 1008.1.9.7,
1117B.5.1 (Item 1), 1133B.2.5
Ennergency escape 1029.1
Fire (see OPENING PROTECTIVES) 715.4,
1022.3,1022.4
Glazing 715.4.7, 715.5, 1405.13
Hazardous storage 415.8.5.6
Hardware
(see LOCKS AND LATCHES) 1005.3,
1008.1.4.4, 1008.1.9,
1008.1 A0,1115B.3.1(4.5), 1116B.1.8,
11178.5.1(1), 1125B.4, 11338,2.5,
11338.2.5.2, 11348.2.1 (3.6.11)
Horizontal sliding 1008.1.4.3
Hydrogen cutoff rooms 421 .4.1
Landings 1008.1.5, 1008.1.6
Means of Egress 1008.1, Chapter 11, 11338.2
Operation 1008.1.3, 1008.1.9
Panic and fire exit hardware 1008.1 .10
Power operated 1008.1 .4.2
Revolving 1008.1.4.1
Security grilles 1008.1 .4.5
Side swinging 1008.1.2
Smoke 710.5,711.5
Stainft/ays 1002.1, 1008.1.9.10,17336.4
Stairways, high-rise 403.5.3
Structural testing, exterior 1715.5
Thresholds 1003.5, 1008.1.5, 1008.1.7
Vestibule 1008.1.7
Width 1008.1.1, 1008.1.1.1
DRAFTSTOPPING
Attics 717.4
Floor-ceiling assemblies 717.3
DRESSING AND FITTING ROOMS 1 1178.8
DRINKING FOUNTAINS
Accessible drinking fountains 11178.1
Alcoves 11178.1(3)
Bubbler 11178.1(4)
Clearances 11178.1(2)
Waterflow 11178.1(5)
DRINKING FOUNTAINS 1139A
DRY CLEANING PLANTS 415.6.4
DRYING ROOMS 417
DUCTS AND AIR TRANSFER OPENINGS
(see MECHANICAL) DUMBWAITERS 708.14
DWELLING UNIT, ADAPTABLE
(see ADAPTABLE DWELLING UNIT)
DWELLING UNITS (definition) 202, 1107A.4-D
Accessibility Chapter 11 A, 1107A.4-D, 11026
Accessibility, existing 1102A.2
Adaptable 11118, 11148.1.5.1
Area 1208.3, 1208.4
Group R 310
Live/work units (see LIVE/WORK UNITS)
Scoping 101.2
Separation 420.2, 420.3
Sound transmission 1207
Visible alarms 420.4.4
EARTHQUAKE LOADS (see SEISMIC) 1613
EAVES (see COMBUSTIBLE PROJECTIONS AND
CORNICES)
EDUCATIONAL OCCUPANCY
(GROUP E) 305, 11068
Accessory 508.2
Accessory assembly spaces 303.1
Area 503, 505, 506, 507, 508
Corridors... 1018.1,1018.2
Day care 305.2, 308.5, 310.1
Education for students above the 12th grade 304
Egress, special provisions 1008.1 .10
Fire alarm and detection 907.2.3
Gyms 303.1
Height 503, 504, 505, 506, 508
Laboratory rooms 1 106B.2
Interior finishes Table 803.9, 804
Library general use areas 1 1068.4
Live load Table 1607.1
2010 CALIFORNIA BUILDING CODE
737
INDEX
Manual fire alarm boxes 907.2.3, 907.4.2
Occupancy category Table 1604.5
Panic hardware 1008.1.10
Plumbing fixtures 2902
Religious facilities 303.1
Special occupancy separation . . 303.1 , Table 508.2.5
Sprinkler system 903.2.3
Stages and platforms 410
Teaching facility cubicles, study carrels 1106B.3
Travel distance 1014.3, 1016.1, 1021.2
Unlimited area 507.10
EFFECTIVE DATE OF THIS CODE. 1.1.9
EFFICIENCY DWELLING UNIT 1208.4
EGRESS
(see MEANS OF EGRESS) . . . Chapter 10, 1114B.2
ELECTRICAI 105.2, 112, Chapter 27, Appendix K
Accessible means of egress elevators 2702.2.5
Accessible means of egress platform lifts . . 2702.2.6
ELEVATOR 1116B, 3003, Chapter 30
Accessibility 1007.2.1, 1007.4, 1007.8, 1124A,
^766, 3001.1, 3001.3
Accommodation for
persons with disabilities 11 168. 1. 1
Carcall 1116B.1.7
Car controls 1116B. 1.9
Car inside 11 16B. 1.8
Car size 3001 .3, 3002.4
Construction 708.14, 1116B.1, 1607.8.1
Control values 3412.6.14
Conveying systems . . . 1124A, 3001.1, 3001.3, 3005
Distance to 1 103B.2
Doorjamb marking 11 16B. 1. 14
Door operation 11 16B. 1.3
Door protective and reopening device . . . . 1116B.1.5
Doors and gates 1116B.2.6
Door size 1116B.1.4
Emergency operations 3002.3, 3002.5,
3003, 3007, 3008
Fire service access 403.6.1 , 3007
General (Accessibility) 11 16B. 1. 1
Hall call 1116B.1.6
Hall call buttons 1116B.1.10
Hall lantern 1116B.1.13
Glass 2409, 3002.8
Handrails 1116B.1.11
High-rise 403.2.3, 403.4.7, 403.4.8, 403.6
Hoistway enclosures 403.2.3, 708,
1022.3,3002,3005.3.1
Hoistway venting 3004
Illumination (minimum) 11 16B. 1. 12
Landing size 11 16B.2.3
Lobby 708.14.1, 709.1,
1007.4,3007.4,3008.11
Location 11 16B. 1. 15
Machine rooms Table 1607.1 , 1607.8, 3006
Means of egress 403.6, 1003.7, 1007.2.1,
1007.4, 1116B.2.5,
1116B.2.5.2, 3008
Minimum illumination 11 16B. 1. 12
Number of elevator cars in hoistway 3002.2
Occupant evacuation elevators 403.6.2, 3008
Operation and leveling 11 16B. 1.2
Passenger (definition) 202
Passenger elevators (accessible) . . 1116B.1, 3001.3
Platform (wheelchair) lift 1116B.2, 1116B.3,
3001.1 (Exc), 3001.3
Personnel and material hoists 3005.4
Relationship to path of travel 11 16B.2.4
Restriction sign 1116B.2.7
Roof access 1009.14
Seismic controls 1613.6.5
Shaft enclosure 708.14
Size of cab and control locations 11 16B. 1. 1
Signs 914, 1007.8.2, 3002.3, 3008.11.5
Standards 3001
Standby power . . . 1116B.2.5.1, 2702.2.5, 2702.2.19
Structural design/safeguards/vertical distance
[Platform (wheelchair) lifts)] 1116B.2.1
Unassisted entry
[Platform (wheelchair) lifts)] 1116B.2.3
Underground 405.4.3
EMERGENCY COMMUNICATIONS
Accessible means of egress 1007.8
Alarms (see FIRE ALARMS)
Elevators, occupant evacuation 3008.5
Fire command center 403.4.5, 91 1
Radio coverage 403.4.4, 915
Visible communication method 1007.6.3. 1
EMERGENCY EGRESS OPENINGS 1029
Required Table 1021.2, 1029.1
Window wells 1029.5
EMERGENCY LIGHTING 1006. 1205.5
EMERGENCY POWER 2702.1, 2702.3
Exit signs 101 1 .5.3, 2702.2.3, 2702.2.9
Group A 2702.2.1
Group 1-3 408.4.2, 2702.2.17
Hazardous 414.5.4, 415.8.10, 2702.2.8,
2702.2.10, 2702.2.11, 2702.2.13
High-rise 403.4.8, 2702.2.15
Means of egress illumination 1006.3, 2702.2.4
Semiconductor fabrication 415.8.10, 2702.2.8
Underground buildings 405.9, 2702.2.16
EMERGENCY RESPONDERS
Additional exit stairway 403.5.2
Elevators 403.6, 1007.2.1, 3002.4,
3003, 3007, 3008
Fire command center 403.4.5, 91 1
Fire department access 402.17
Radio coverage 403.4.4, 915
Roof access 1009.13
Safety features 914
EMERGENCY WARNING SYSTEMS 1114B.2.2
EMPIRICAL DESIGN OF MASONRY. . 2101.2.4, 2109
Adobe construction 2109.3
General 2109.1
738
2010 CALIFORNIA BUILDING CODE
INDEX
Special inspection 1704.5
Surface-bonded 2109.2
EMPLOYEE
Accessibility for worl< areas 907.5.2.3.2,
11058.3,2(3), 11058.3.3(2),
11088.5, 11108.1.2, 11238
General (employee areas accessibility) 1 1238. 1
Qualifications A1 01
Termination of employment A1 01 .4
Work stations 1 1238.2
ENCROACHMENTS INTO THE
PUBLIC RIGHT-OF- WAY Chapter 32
END-JOINTED LUMBER 2303.1.1
ENERGY EFFICIENCY 101.4.6,
110.3.7, Chapter 13
ENFORCING AGENCY 202
California Energy Commission 105
California State Lands Commission 114
Corrections Standards Authority 103
Department of Consumer Affairs 104
Department of Food and Agriculture 106
Department of Health Services 107
Division of the State
Architect— Access Compliance 109. 1
Division of the State
Architect— Structural Safety 109.2
Housing and Community Development 108
Office of the State Fire Marshal Ill
Office of Statewide Health Planning and
Development 110
Special Conditions for Persons with Disabilities
Requiring Appeals Action Ratification 109.1.5
State Librarian 112
ENGINEER (see definition for REGISTERED
DESIGN PROFESSIONAL)
ENTRANCES, EXITS AND PATHS OF TRAVEL
(ACCESSIBILITY FOR) Div III 11338
Aisles 11338.6
All entrances & exterior ground-floor
exit doors (8uilding accessibility) . . . 1 1338. 1. 1. 1. 1
Automatic and power-assisted
doors (Hinged doors) 1 1338.2.3.2
8uilding accessibility 1 1338. 1
Change of direction (Ramp-landing). . . . 11338.5.4.6
Changes in level (Walks/Sidewalks) 1 1338.7.4
Continuous surface (Walks/Sidewalks) . . . 11338.7.1
Corridors and hallways over 200 feet / 1338.3.2
Corridors and hallway widths 11338.3, 1
Corridors, hallways and exterior
exit balconies 1 1338.3
Detectable directional texture at
boarding platforms (Hazards) 1 1338.8.4
Detectable warnings at
hazardous vehicular areas (Hazards) . . 11338.8.5
Detectable warnings at
reflecting pools (Hazards) 11338.8.7
Detectable warnings at transit
boarding platforms (Hazards) 11338.8.3
Door closer (Door opening force) 1 1338.2.5. 1
Door opening force 11338.2.5
Doors 1 1338.2
Doors at ramp landings 1 1338.5.4.3
Encroachment of doors at
ramp landings 1 1338.5.4.4
Entrances & exterior ground floor
exit doors (Suilding accessibility) 1 1338. 1.1.1
Entrances (8uilding accessibility) 1 1338. 1. 1
Existing ramps (Landings) / 1338.5.4.8
Five percent gradient (Walks/Sidewalks) . . 1 1338. 7.3
Floor level at doors 1 1338.2.4
Free-standing signs
(Protruding objects-Hazards) 11338.8.6.3
Gates (8uHding accessibility) 1 1338. 1. 1. 1.4
Gratings (Walks/Sidewalks) 11 1338.7.2
Gradient (5 percent) / 1338.7.3
Guards (Ramps) 1 1338.5.7
Guide curbs and wheel
guide rails (Ramps) 1 1338.5.6
Hand-activated door opening
hardware (Door opening force) 1 1338.2.5.2
Handgrips
(Stairways-handrail configuration) .... 11338.4.2.6
Handrails (Stain/vays) 1 1338.4. 1
Handrail configuration (Stairways) 11338.4.2
Handrails for ramps 1 1338.5.5
Hazards 11338.8
Hazards (Ramp-landings) 11338.5.4.9
Headroom
(Protruding objects-Hazards) 11338.8.6.2
Hinged doors 1 1338.2.3
Landings (Ramp) 1 1338.5.4
Landings width (Ramp) 1 1338.5.4.5
Level areas (Walks/Sidewalks) 11338.7.5
Location (Ramp landings) 1 1338.5.4. 1
Maneuvering clearances at doors
(Floor level at doors) 11338.2.4.2
Nosing (StainA/ays) 1 1338.4.5.3
Other intermediate landings (Ramp). . . . 11338.5.4.7
Outdoor ramps 1 1338.5.8
Overhanging obstructions (Hazards) 1 1338.8.2
Pairs of doors (Hinged doors) 1 1338.2.3. 1
Protruding objects (Hazards) 1 1338.8.6
Ramp handrails 1 1338.5.5, 1. 1
Ramps 1 1338.5
Recessed doors (Floor level at doors) . . 1 1338.2.4.5
Recessed doormats
(8uilding accessibility) 1 1338. 1. 1. 1.3
Required handrails (Stairways) 1 1338.4. 1. 1
Revolving doors (Hinged doors) 11338.2.3.3
Risers (StainA/ays) 1 1338.4.5.2
Service entrances
(8uilding accessibility) 1 1338. 1. 1. 1.5
Size of top and bottom landings
(Ramp) 1 1338.5.4.2
Slope (Ramps) 11338.5.3, 11338.5.3.1
Slopes less than 6 percent (Continuous
surface-Walks/Sidewalks) 11338.7.1.1
Slopes 6 percent or greater (Continuous
surface-Walks/Sidewalks) 11338.7. 1.2
2010 CALIFORNIA BUILDING CODE
739
INDEX
Smooth surface (Doors) 1 133B.2.6
Stair treads, risers & nosing (Stairways) . . 1133B.4.5
StainA/ays 1 133B.4
Striping for tlie visually impaired
(StainA/ays) 1133B.4.4
Surface cross slopes (Continuous
surface-Walks/Sidewalks) 1133B.7.1.3
Tactile floor designation
signs in stairways 1 133B.4.3
Temporary restriction
(Building accessibility) 1133B.1.1.1.2
Thresholds (Floor level at doors) 1133B.2.4.1
Treads (Stain^/ays) 1 133B.4.5. 1
Turnstiles, rails & pedestrian
controls (Hinged doors) 1133B.2.3.4
Type of lock or latch (Doors) 1 133B.2. 1
Walks and sidewalks 1133B.7
Warning curbs (Hazards) 1 133B.8. 1
Width (Aisles) 1133B.6.2
Width (Ramps) 1 133B.5.2
Width and height (Doors) 1 133B.2.2
ENTRANCES, EXITS AND PATHS OF TRAVEL
(Building Accessibility) Chapter 1 1A
EQUIVALENT FACILITATION
(definition) 202, 1107A.5-E, 1102B
EQUIVALENT OPENING FACTOR Figure 705.7
ESCALATORS 3005
Accessibility 1 103B. 1, 103B.2,
1116B,1,1121B.3.1(16)
Floor opening protection 708.2
Means of egress 1 003.7
ESSENTIAL FACILITIES
(see OCCUPANCY CATEGORY) 1602.1
EXCAVATION, GRADING AND FILL 1804, 3304
EXISTING BUILDING 102.6, Chapter 34, 1134B
Accessibility 1102A.2, 1134B
Additions 3403, D103.1
Alteration 3404, D103.1
Alteration of single elements 1134B.2.3
Ciiange of occupancy 3408, D103.2
Definition (see BUILDING, EXISTING) 202
Flood resistant 3401 .2, 3403.2, 3404.2, 3405.5,
3409.2, 341 2.2.4.1, Appendix G
General (Accessibility) 1 134B.2
General (Scope) 3401. 1, 1 134B
Historic 3409
Moved structures 3410, D1 03.3
Primary entrance 1 134B.2. 1
Repairs 3405
Rodentproofing Appendix F
Scope (Accessibility) 1 134B. 1
Toilet facilities 1 134B.2.2
EXIT
(see MEANS OF EGRESS) 1020 through 1026
Boiler rooms. 1015.3
Construction 708.2
Definition 1002. 1
Enclosure 707.3.2, 1022.1
Fire resistance 707.3, 1022
Furnace rooms 1015.3
Group H 41 5.8.4.4, 41 5.8.5.5
Horizontal 707.3.3, 1025
Incinerator rooms 1015.3
Interior finish Table 803.9, 804
Luminous 403.5.5, 41 1 .7.1 , 1024
Mezzanines 505.3, 505.4, 1004.6
Number, minimum 403.5, 1015.1, 1021
Passageway 1 023
Ramps, exterior 1026
Refrigerated rooms or spaces 1015.5
Refrigeration machinery rooms 1015.4
Signs 1011
Stairs, exterior 1026
Travel distance 104.2.2, 402.4, 404.9, 407.4,
408.6.1,408.8.1,411.4, 1014.3,
1015.5, 1016,1021.2, 1028.7
Underground buildings 405.7
EXIT ACCESS
(see MEANS OF EGRESS) 1014 through 1019
Aisles 1017
Balconies 1016.2, 1019
Common path 1014.3
Corridors 1018
Doors 1005.2, 1008, 1015, 1020.2
Intervening space 1014.2
Path of egress travel, common 1014.3
Seating at tables 1017.3
Single exit 1015.1.1, 1021.2
Travel distance 402.4, 404.9, 407.4,
408.6.1,408.8.1,411.4,1014.2.2,
1014.3, 1015.5, 1016, 1021.2, 1028.7
EXIT DISCHARGE
(see MEANS OF EGRESS) 1027.5
Horizontal exit 1027.1
Lobbies 1027.1
Marquees 3106.4
Open parking garage 1027.1
Public way 1002.1, 1027.6
Termination 1022.2
Vestibules 1027.1
EXIT PASSAGEWAY
(see MEANS OF EGRESS) 707.3.3, 1023
EXIT SIGNS 1011
Accessibility 1011.3. 11178.5.1(1)
Illumination 1011.2, 1011.4, 1011.5
Required 1011.1
Special amusement buildings 411.7
Tactile exit signs 1011.3, 1117B.5.1 (Item 1)
EXPLOSIVES Table 41 4.5.1,
Table 415.3.1, Table 415.3.2
EXPOSURE CATEGORY
(see WIND LOAD) 1609.4
EXTERIOR AREAS FOR ASSISTED RESCUE
Requirements 1007.7
Signage 1007.9, 1007.10, 1007.11
1 1 1 7B.5. 1(2)(3), Chapter 1 1A
Where required 1007.2
740
2010 CALIFORNIA BUILDING CODE
INDEX
EXTERIOR INSULATION AND
FINISH SYSTEMS (EIFS) 1408
Special inspection 1704.14
EXTERIOR ROUTES OF TRAVEL 1127B
Curb ramps 1 127B.5
Design and construction 1 127B.2
General 1127B. 1
Outside stairways 1 127B.4
Signs 1127B.3
EXTERIOR WALLS
(see WALLS, EXTERIOR) Table 601 , 602,
705, Chapter 14
FACILITY (or FACILITIES)
Accessibility Chapter 1 1 A
FACILITY ACCESSIBILITY 1114B
Adaptable dwelling units 11 11 B, 11 14B. 1.5,
Aisles 1 133B.6
Alarms 907.9. 1, 907.9.2, 1 1 14B.2.2
Bathing and Toilet Facilities 11 15B
Corridors 1 133B.3
Detectable Warnings 1121B.3. 1, Item 8(a),
1127B.5.7, 1133B.8.5, Part 12
Design and construction 11 14B. 1
Doors 1 133B.2
Egress and areas of refuge 11 14B.2
Elevators 1116B
Entrances 1 133B. 1. 1
General (Accessibility) 11 14B. 1. 1
Hazards 1 133B.8
Platform (Wheelchair) Lifts 1116B.2
Primary entry access (Accessible) 1114B.1.3
Ramps 1 133B.5
Route of travel (Accessible) 11 14B. 1.2
Signs and Identification 1114B.1.4, 1117B.5
Stain/vays 1 133B.4
Walks and Sidewalks 1 133B.7
FACTORY OCCUPANCY (GROUP F). . . 306, 1107B
Accessory 508.2
Area 403.1, 503, 503.1.1, 505, 506, 507, 508
Dead end corridor 1018.4
Factories 1 107B. 1
Fire alarm and detection 907.2.4
Height 503, 504, 505, 506, 508
Interior finishes Table 803.9, 804
Live load Table 1607.1
Low hazard occupancy 306.3
Moderate hazard occupancy 306.2
Plumbing fixtures 2902
Smoke and heat vents 91 0.2
Special occupancy separation Table 508.2.5
Travel distance 1014.3, 1015.4,
1015.5, 1016.1, 1021.2
Unlimited area 507.2, 507.3, 507.4
Warehouses 1 107B.2
FAMILY (definition) 202
FARM BUILDINGS Appendix C
FEES, PERMIT 109
Refunds 109.6
Related fees 109.5
Work commencing before issuance 109.4
FENCES 105.2, 312.1
FIBERBOARD 2302.1 , 2303.1 .5
Shear wall 2306.6
FILL MATERIAL 1804, 3304
FINGER-JOINTED LUMBER
(see END-JOINTED LUMBER)
FIRE ALARM AND SMOKE DETECTION SYSTEMS
Aerosol storage 907.2.16
Aircraft hangars, residential 907.2.21
Airport traffic control towers 412.3.4
Ambulatory care facilities 422.6, 907.2.2.1
Assembly 907.2.1
Atriums 907.2.14
Audible alarm 907.9.2 907.5.2.1
Audible alarm signal 907.5.2. 1.3
Average sound pressure 907.5.2. 1. 1
Battery room 907.2.23
Construction documents 907.1 .1
Covered mall and open mall 402.4.5.1, 402.11,
402.12.2,402.15,907.2.20
Education 907.2.3
Emergency system 908
Employee work areas 907.5.2.3.2
Factory 907.2.4
Group H 907.2.5, 907.2.15
Group I 907.2.6, 907.5.2.3.3
Group 1-2 907.5.2. 1
Group M 907.2.7
Group R 907.2.8, 907.2.9, 907.2.10,
907.2.11, 907.5.2.3.3, 907.5.2.3.4
Group R'2. 1, R-3. 1 and R'4 907.5.2.3.5
High-rise 403.4.2, 907.2.13
Institutional occupancy 407.2.1, 407.2.3, 407.6
Live/work 419.5, 907.2.9
Lumber mills 907.2.17
Maximum sound pressure 907.5.2. 1.2
Occupancy requirements 907.2
Patient areas (Audible alarms) 907.5.2. 1
Public and common use areas 907.5.2.3. 1
Special amusement buildings 41 1 .3, 41 1 .5,
907.2.12
Underground buildings 907.2.18, 907.2.19
Visible alarm 420.4.4, 907.5.2.3
FIRE ALARM BOX, MANUAL 907.4.2
FIRE AREA 901.7
Ambulatory health care facilities 903.2.2, 907.2.2
Assembly 903.2.1
Education 903.2.3
Factory 903.2.4
Institutional 903.2.6
Mercantile 903.2.7
Residential 903.2.8
Storage 903.2.9, 903.2.10
FIRE BARRIERS 110.3.6, 707, 708
Continuity 707.5, 708.4
2010 CALIFORNIA BUILDING CODE
741
INDEX
Exterior walls Table 602, 707.4, 708.6
Fire-resistance rating of walls 603.1(21),
603.1(22), 603.1(25),
703, 707.3, 708.3
Glazing, rated 715.5
Incidental accessory occupancies 508.2.5.1
Joints 707.8, 708.9, 714, 2508.4
Marking 703.6
Materials 707.2, 708.3
Opening protection 707.6, 707.9, 708.7,
708.10,713.3,715,71 6.5.2
Penetrations 707.7, 708.8
Shaft enclosure 708.1
Special provisions
Aircraft hangars 412.4.4
Atriums 404.3, 404.6
Covered malls 402.4.6, 402.7.1, 402.7.3
Fire pumps 913.2.1
Flammable finishes 416.2
Group H-2 415.6.1.2,41 5.6.2.2
Group H-3 and H-4 415.7
Group H-5 . . . 415.8.2.2, 41 5.8.2.5,
415.8.5.2,41 5.8.6.3
Group 1-3 408.5, 408.7
Hazardous materials 414.2
High-rise 403.2.1.2, 403.3, 403.4.7.1
Hydrogen cutoff rooms. 421 .4
Organic coating 418.4, 418.5, 418.6
Stages and platforms 410.5.1, 410.5.2
FIRE COMMAND CENTER 403.4.5, 91 1
FIRE DAMPERS 716.2 through 716.5
FIRE DEPARTMENT
(see EMERGENCY RESPONDERS)
FIRE DETECTION SYSTEM (see FIRE ALARM AND
SMOKE DETECTION SYSTEMS)
FIRE DISTRICT Appendix D
FIRE DOOR (see OPENING
PROTECTEES) 715, 1022.3, 1022.4
FIRE ESCAPE 412.7.3, 3406
FIRE EXTINGUISHERS, PORTABLE 906, 3309
FIRE EXTINGUISHING SYSTEMS 416.5,
417.4,903,904
FIRE PARTITION 1 10.3.6, 709
Continuity 709.4
Exterior walls Table 602, 709.5
Fire-resistance rating 603.1(21), 603.1(22),
603.1(25), 703, 709.3
Glazing, rated 71 5.5
Joint treatment gypsum 2508.4
Joints 709.8, 714
Marking 703.6
Materials 709.2
Opening protection 709.6, 713.3, 715, 716.5.4
Penetrations 709.7, 709.9, 713, 716
Special provisions
Covered mall 402.7.2
Group 1-3 408.7
Group 1-1 , R-1 , R-2, R-3 420.2
FIRE PREVENTION 101.4.5
FIRE PROTECTION
Explosion control 414.5.1, 415.6.1.4,
415.8.5.4,421.7
Fire extinguishers, portable 906
Glazing, rated 715.2
Smoke and iieat vents 910
Smoke control systems 909
Sprinkler systems, automatic 903
FIRE PROTECTION SYSTEMS Chapter 9
FIRE PUMPS Table 508.2.5, 913, 914.2
FIRE RESISTANCE
Calculated 721
Conditions of restraint 703.2.3
Ducts and air transfer openings 716
Exterior walls Table 602, 705.5, 709.5
Fire district D102.2.5
High-rise 403.2
Joint systems 714
Prescriptive 720
Ratings Chapter 6, 703, 705.5, 707.3.9
Roof assemblies 1505
Structural members 704
Tests 703
Thermal and sound insulating materials 719.1
FIRE RESISTANCE, CALCULATED 721
Clay brick and tile masonry 721 .4
Concrete assemblies 721 .2
Concrete masonry 721 .3
Steel assemblies 721 .5
Wood assemblies 721 .6
FIRE-RETARDANT-TREATED
WOOD 2302.1, 2303.2
Awnings 3105.3
Balconies 1406.3
Canopies 3105.3
Concealed spaces 717.5
Fastening 2304.9.5
Fire wall vertical continuity. 706.6
Partitions 603.1
Platforms 410.4
Projections 705.2.3
Roof construction . . . Table 601 , 705.1 1 , 706.6, 1505
Shakes and shingles 1505.6
Type I and II construction 603.1(1 0), 603.1(25)
Type III construction 602.3
Type IV construction 602.4
Veneer 1405.5
FIRE SEPARATION DISTANCE Table 602, 702
Exterior walls 1406.2.1.1
FIRE SERVICE
ACCESS ELEVATORS 403.6.1 , 3007
FIRE SHUTTER (see OPENING
PROTECTEES) 715.4, 71 5.4.9,
71 5.4.10,715.5
FIRE WALLS 706
Aircraft 412.6.2
Combustible framing 706.7
742
2010 CALIFORNIA BUILDING CODE
INDEX
Continuity 706.5, 706.6
Exterior walls Table 602, 706.5.1
Fire-resistance rating 703, 706.4
Glazing, rated. 715.5
Inspection 1 10.3.6
Joints 706.10,714
Marking 703.6
Materials 706.3
Opening protection 706.8, 706.1 1 ,
713.3,715,716.5.1
Penetration 706.9, 713.3, 713.4
Special provisions
Aircraft hangars 412.4.6.2
Covered malls 402.7.3
Group H-5 415.8.2.6
Private garages and carports 406.1 .2
Structural stability 706.2
FIRE WINDOWS (see OPENING PROTECTIVES)
FIREBLOCKING 717.2
Chimneys 717.2.5, 2113.20
Fireplaces 2111.12
Wood construction 717.2.1, 717.2.7, 1406.2.4
Wood stairs 717.2.4
FIREPLACES, FACTORY-BUILT 2111.14.1
FIREPLACES, MASONRY 2102.1
Combustibles 21 1 1 .1 1
General provisions 2111
Hearth extension 2111.9,2111.10
Steel units 2111.5.1
FIREWORKS 307.2, 307.3, 307.5
FITTING AND DRESSING ROOMS 1 117B.8
FIXED GUIDEWAY TRANSIST SYSTEMS 303.2,
433
Fire alarm and communication systems. . . . 907.2.26
FIXED OR BUILT-IN SEATING, TABLES,
AND COUNTERS 1122B
Height of work surfaces 1 122B.4
Knee clearance 1 1228.3
Minimum number 1 122B. 1
Sales and service counters, teller
windows, and information counters 1122B.5
Seating 1122B.2
FLAMESPREAD 802, 803.1 .1 , Table 803.9
FLAMMABLE FINISHES 307.1, 416
FLAMMABLE LIQUIDS 307.4, 307.5, 406,
412,414,415
FLAMMABLE SOLIDS 307.5, 415
FLASHING
Roof 1503.2, 1503.6, 1507.2.9
1507.3.9, 1507.5.7,1507.7.7,
1507.8.8, 1507.9.9,1510.6
Wall, veneer 1405.4, 1405.12.7
FLOOD-RESISTANT CONSTRUCTION
Administration G101 through G105
Elevation certificate 1 10.3.3
Existing 3403.2, 3404.2, 3405.5,
3409.2,3412.2.4.1
Flood elevation 107.2.5.1, 1612
Flood loads 1603.1, 1603.1.7,
1612,3001.2,3102.7
Flood resistance 1403.5, 1403.6
Flood resistant construction Appendix G
Grading and fill 1804.4, 1805.1.2.1
Historic buildings G105.3
Interior finishes 801 .1 .3
Manufacturered homes G501
Recreational vehicles G601
Site improvements G401
Site plan 107.2.5
Subdivisions G301
Tanks G701
Temporary G901
Utility G1001
Ventiation, under floor 1203.3.2
FLOOR/CEILING (see FLOOR CONSTRUCTION)
FLOOR CONSTRUCTION (see FLOOR
CONSTRUCTION, WOOD)
Draftstopping 71 7.3
Finishes 804, 805, 1003.4, 1210.1
Fire resistance Table 601 , 712
Loads (see FLOOR LOADS)
Materials Chapter 6
Penetration of fire-resistant assemblies 712,
713.4,716.2,716.6
FLOOR CONSTRUCTION, WOOD
Beams and girders 2304.1 1 .2.1 , 2308.7
Bridging/blocking 2308.8.5, 2308.10.6
Diaphragms 2305.1
Fastening schedule 2304.9.1
Framing Table 602.4, 602.4.2, 602.4.4, 2304.4
Joists 2308.8
Sheathing 2304.7
FLOOR LEVEL 1003.5, 1008.1.5, 1120B
Floor surface 1 120B.2
Floors within each story 1 120B. 1
FLOOR LOADS
Construction documents 1 07.2
Live 1603.1.1, 1607
Posting 106.1
FLOOR OPENING PROTECTION
(see VERTICAL OPENING PROTECTION)
FOAM PLASTICS
Attics. 719.1, 2603.4.1.6
Cold storage 2603.3, 2603.4.1.2, 2603.5
Concealed 603
Covered mall and open mall buildings 402.16.5
Crawl space 2603.4.1 .6
Doors 2603.4.1 .7 through 2603.4.1 .9
Exterior walls of multistory buildings 2603.5
Interior finish 801 .2.2, 2603.9, 2604
Label/identification 2603.2
Metal composite materials (MCM) 1407.1.1,
1407.13
Siding backer board 2603.4.1.10
Stages and platform scenery 410.3.6
Surface burning characteristics 2603.3
Thermal barrier requirements 2603.5.2
2010 CALIFORNIA BUILDING CODE
743
INDEX
Trim 806.3, 2604.2
Type I and II construction 603.1(1), 603.1(2)
Walk-in coolers 2603.4.1 .3
FOLDING AND TELESCOPIC SEATING . . . 1028.1.1,
3401.1
Egress 1028.1.1
Live load Table 1607.1
Occupant load 1004.7
FOOD COURT 402.2
Occupant load 402.4.1 .4
FOOTBOARDS 1028.14.2
FORMWORK, CONCRETE 1906
FOUNDATION (see FOUNDATION, DEEP and
FOUNDATION, SHALLOW) Chapter 18,
1407.13
Roofing 2603.4.1 .5
Basement 1610, 1805.1.1, 1806.3, 1807
Concrete 1808.8, 1809.8, 1810.3.2.1
Damp proofing 1 805.2
Encroachment, public right-of-way 3202.1
Formwork 1906, 3304.1
Geotechnical investigation
(see SOILS AND FOUNDATIONS) 1803
Inspection 1 10.3.1
Load-bearing value 1806, 1808, 1810
Masonry 1 808.9
Pedestrian protection 3306.9
Pier (see FOUNDATION, SHALLOW)
Pile (see FOUNDATION, DEEP)
Plates or sills 2308.6
Protection from adjacent construction 3303.5,
3307.1
Rodentproofing Appendix F
Special inspections 1704.4, 1704.8,
1704.9, 1704.10, 1704.11
Steel 1809.11, 181 0.3.2.2, 101 8.3.2.3
Timber 1809.12, 1810.3.2.4
Waterproofing 1805.3
FORMAT. 1.1.11
FOUNDATION, DEEP 1802.1, 1810
Drilled shaft 1802.1
Existing 1810.10.1.2
Geotechnical investigation 1803.5.5
Grade beams 1810.3.12
Helical pile 1802.1, 1810.3.1.5,
Table 1810.3.2.6, 1810.3.3.1.9,
1810.3.5.3.3, 1810.4.11, 1810.4.12
Micropile 1802.1, Table 1808.8.1,
Table 1810.3.2.6, 1810.3.5.2.3,
1810.3.10, 1810.4.10
Piles Table 1808.8.1, 1809.12,
1810,1810.3.1.4
FOUNDATION, SHALLOW 1802.1, 1809
Piers and curtain wall 1809.10
Slab-on-grade 1 808.6.2
Strip footing 1808.8, 1809
FOYERS
Assembly occupancy 1028.4, 1028.9.5
Corridors 1018.6
Covered mall and open mall 402.1
FRAME INSPECTION 110.3.4
FRATERNITIES 310
FROST PROTECTION 1809.5
FULL-TIME CARE (definition) 310.2
FURNACE ROOMS 1015.3
GALLERIES
Means of egress .410.3.2, 1015.6.1, 1028.5
Sprinklers 410.6
GARAGE, AUTOMOBILE PARKING
(see PARKING GARAGES)
GARAGE, REPAIR 406.6
Floor surface 406.6.4
Gas detection system 406.6.6, 908.5
Sprinklers 903.2.9.1
Ventilation 406.6.3
GARAGES, TRUCK AND BUS
Live load 1607.6, 1607.7.3
Sprinklers 903.2.10.1
GARAGES AND CARPORTS, PRIVATE 406.1
Area limitations 406.1 .2
Separation 406.1.4
GAS 101 .4.1, 105.2, 112
Accessibility 11178.7.1, 1117B.7.2(Exc.5)
Gas detection system 406.6.6, 41 5.8.7,
421.6,908
Hydrogen cutoff room 421 .6
Motor fuel dispensing 406.5
GATES 1008.2
Vehicular 3110
GENERAL CODE PROVISIONS
CA Administration Chapter 1-Div I
ICC Administration Cfiapter 1-Div II
GIFT SHOPS 407.2.4
GIRDERS
Fire resistance Table 601
Materials Chapter 6
Wood construction 2304.1 1 .2.1 , 2308.7
GLASS (see GLAZING)
GLASS BLOCK (see GLASS UNIT MASONRY)
GLASS UNIT MASONRY 2102.1, 2110
Atrium enclosure 404.5
Design method 2101 .2.5
Fire resistance 2110.1.1
Hazardous locations 2406.1 .3
Material requirements 2103.6
GLAZING
Athletic facilities 2408
Doors 705.8,710.5,711.5,
715.4.3.2, 1405.13,1715.5
Elevator hoistway and car 2409
Fire doors 715.4.4, 71 5.4.7
Fire resistant walls 715.4.3.2
Fire windows 703.5, 715.5
744
2010 CALIFORNIA BUILDING CODE
INDEX
Group 1-3 408.7
Guar6s(or Guardrails) 1002.1, 1013.1.1,
2406.4, 2407
Handrail 1002.1, 1009.12, 2407
Identification 2403.1 , 2406.3
Impact loads . . 2406.1 . 2407.1 .4.2, 2408.2.1 , 2408.3
Impact resistant 1609.1 .20
Jalousies 2403.5
Label/identification .... 715.4.6.1, 715.4.7.3, 715.5.9
Loads 2404
Louvered windows 2403.5
Opening protection 715.2
Replacement 2401 .2, 3407
Safety 715.4.7.4, 2406
Security 408.7
Skylights 2405
Sloped 2404.2, 2405
Supports 2403.2
Swimming pools 2406.4
Testing 1715.5, 2406.1 .1, 2408.2.1
Veneer 1405.12
Vertical 2404.1
Wired 715.5.4
GRAB BAR 127A.2
Definition 202, 1107A.7-G
GRADE (ADJACENT GROUND ELEVATION) ....202
GRADE, LUMBER (see LUMBER) 2302.1
GRADE PLANE 502
GRAIN ELEVATORS 415.6.1.5
GRANDSTANDS 303.1, 1028.1.1, 3401.1
Accessibility 1 104B.4
Clubrooms 1104B.4.4
Exit sign exemptions 101 1 .1
Live load Table 1607.1
Occupant load 1004.7
Participation areas 1 104B.4.3
Sanitary and locl<er facilities 11048.4.5
Spectator seating 1 104B.4. 1
Ticket booth 1104B.4.2
GREENHOUSES 312.1
Area 503, 505, 506, 507, 508
Deflections Table 1604.3
Live load 1607.11.2.1
Membrane structure 3102.1
Plastic 2606.11
Sloped glazing 2405
Wind load 1609.1.2
GRIDIRON . .410.2
Means of egress 410.3.2, 1015.6.1
Sprinklers 410.6
GRINDING ROOMS 415.6.1.2
GROUND AND FLOOR SURFACES 1 124B
Carpet 1 124B.3
Changes in level 1 124B.2
General (Along accessible routes/rooms). . . 1 124B. 1
Gratings 1 124B.4
GROSS LEASABLE AREA (see COVERED MALL
AND OPEN MALL BUILDINGS) . . . 402.2, 402.4.1.1
GROUND FLOOR (definition) 202, 1 107 A. 7-G
GROUP A (accessibility) 1 104B
GROUP B (accessibility) 1 105B, 1 1 14B. 1. 1
GROUP E (accessibility) 1 106B, 1 1 14B. 1. 1
GROUP H (accessibility) 1108B
GROUP I (accessibility) 1109B
GROUP M (accessibility) 1110B
GROUP R (accessibility) HUB
GROUT 713.3.1,713.4.1.1,2103.12
GUARD (or GUARDRiL) definition 202, 1002
GUARDS(or Guardrails) 1002.1, 1013
Assembly sealing 1028.1.1, 1028.14
Equipment platform. 505.5.3
Exceptions 1013.1
Glazing 1013.1.1, 1303.1, 2406.4, 2407
Height 1013.2
Loads 1607.7
Mechanical equipment 1013.5
Opening limitations 1013.3
Parking garage 406.2.4
Ramps 1010.10
Residential 1013.2
Roof access 1013.6
Screen porches 1013.4
Stairs 1002.1,1013.1
Vehicle barrier 1607.7.3
Where required 1013.1, 1607.7,2407
GUTTERS 1503.4.3
GYMNASIUMS 303.1
Group E 303.1(4)
Live load Table 1607.1
Occupant loac 1004.1
GYPSUM Chapter 25
Aggregate, exposed 2513
Board Chapter 25
Ceiling diaphragms 2508.5
Concrete, reinforced 1914
Construction 2508
Draftstopping 717.3.1
Exterior soffit Table 2506.2
Fastening Table 2306.7, 2508.1
Fire resistance 718, 721.2.1.4, 721.6.2
Fire-resistant joint treatment 2508.4
Inspection 2503
Lath 2507,2510
Lathing and furring for cement plaster .... 718, 2510
Lathing and plastering 2507
Materials 2506
Plaster, exterior 2512
Plaster, interior 251 1
Shear wall construction 2306.7, 2308.9.3, 2505
Sheathing Table 2304.6
Showers and water closets 2509
Stucco. . 2510
Veneer base 2507.2
Veneer plaster 2507.2
Vertical and horizontal assemblies 2504
Wallboard Table 2506.2
2010 CALIFORNIA BUILDING CODE
745
INDEX
Water-resistant backing board 2506.2, 2509. 2
H
HANDRAILS 1002.1, 1012,
Chapter 11 A, 1607.7
Alternating tread devices 1009.10.1
Assembly aisles 1028.13
Construction 1012.4, 1012.5, 1012.6
Extensions 1012.6
Glazing 2407
Graspability 1012.3
Guar6s(or Guardrails) 1002.1, 1013.2
Height 1012.2
Loads 1607.7
Location 1012.1, 1012.7, 1012.8, 1012.9
Ramps 1010.8
Stairs 1002.1, 1009.12
HARDBOARD 1404.3.2, 2302.1, 2303.1.6
HARDWARE
(see DOORS and LOCKS AND LATCHES)
HARDWOOD
Fastening .2304.9
Quality 2303.1.8.1, 2303.3
Veneer 1404.3.2
HAZARDOUS MATERIALS 307, 414, 415
Control areas 414.2
Explosion control 41 4.5.1 , Table 41 4.5.1 ,
415.6.1.4,415.8.5.4
Special provisions 415.4, 415.5
Sprinklers Table 414.2.5(1), Table 414.2.5(2),
415.5.2, 415.6.2.4, 415.8.11, 903.2.7.1
Ventilation 414.3,414.5.4,415.6.1.4,
415.6.2.8. 415.8.2.6, 415.8.2.8.2,
415.8.4.3,415.8.5.7,415.8.6.3,
415.8.7, 415.8.9.3, 415.8.10, 1203.5
Weather protection .414.6.1
HAZARDS 1133B.8
Detectable directional texture (Boarding
platforms) 1133B.8.4
Detectable warnings (Hazardous
vehicular areas) 1 133B.8.5
Detectable warnings (Reflecting
pools) 1 133B.8.7
Detectable warnings
(Transit boarding platforms) 1133B.8.3
Free-standing signs
(Protruding objects) 1 133B.8.6.3
Headroom (Protruding objects) 1133B.8.6.2
Overhanging obstructions 1133B.8.2
Protruding objects 1133B.8.6
Warning curbs 1 133B.8. 1
HEAD JOINT, MASONRY 2102.1
HEADROOM 406.2.2, 505.1, 1003.2,
1003.3, 1008.1.1, 1008.1.1.1,
1009.2, 1010.5.2,1208.2
HEALTH CARE (see INSTITUTIONAL 1-1
AND INSTITUTIONAL 1-2)
Ambulatory health care facilities 422
Clinics, outpatient 304
Hospitals 308.3
HEALTH-HAZARD MATERIALS 307.2,
Table414.2.5(1), 415.2, 415.4,
Table 415.8.2.1.1, 415.8.6.2
HEAT VENTS 910
HEATING (see MECHANICAL) 101.4.2
Aircraft hangars 412.4.4
Fire pump rooms 913.3
Fireplace 2111
Masonry heaters 2112
Parking garages 406.2.8
Repair garages 406.6.5
HEIGHT, BUILDING 503, 504, 505, 506, 508, 509
Limitations 503
Mixed construction types 509
Modifications 504
Roof structures 504.3
HIGH-PILED
COMBUSTIBLE STORAGE
..413,
907.2.15,910.2.2
HIGH-HAZARD
OCCUPANCY (GROUP H) 307, 414,
415, 1108B
Accessibility 1108B.6
Accessible facilities 1 108B.6
Accessory 508.2
Area 503, 505, 506, 507, 508
Classification 307
Combustible liquids 307.4, 307.5,
414.2.5,414.5.4,415.6.2
Control areas 414.2
Conveyors 415.6.1.3
Corrosives 307.6, Table 414.2.5(1),
414.3, 415.7.3, Table 415.8.2.1.1
Cryogenic Table 307.1 ,
Table 414.5.1, Table 415.8.2.1.1
Dispensing 414.1, 414.5, 414.6, 414.7.2, 415.3
Dry cleaning
(see DRY CLEANING PLANTS)
Emergency alarm systems 414.7, 415.8.3,
415.8.4.6, 415.8.5.8, 908.1, 908.2
Employee work areas 1 108B.5
Exceptions 307.1
Exempt 307.1
Explosives . 307.3, Table 414.5.1, Table 415.3.1
Factory industrial F-1 moderate
hazard occupancy 306.2
Factory industrial F-2 low
hazard occupancy 306.3
Fire alarm and detection 414.7.2, 415.8.8,
901 .6.3, 907.2.5
Fire district D102.2.2
Flammable liquids 307.4, 307.5, 415.6.2
746
2010 CALIFORNIA BUILDING CODE
INDEX
Flammable solids 307.5, 415.1
Floors and levels (accessible) 1 108B.4
Grinding rooms 415.6.1.2
Group H-1 . . . . 307.3, 403.1, 41 5.3.1,41 5.3.2, 415.4
Group H-2 307.4, 403.1, 412.6.1,
415.3,415.5,415.6
Group H-3 307.5, 403.1, 415.3,
415.5,41 5.6.2,415.7
Group H-4 307.6, 415.4, 415.7
Group H-5 307.7, 415.8
Health-hazard materials 307.2, Table 414.2.5(1),
415.2, 415.4, Table 415.8.2.1.1,
415.8.6.2,415.8.7.2
Height 415.4, 415.5, 415.6.1 .1 ,
415.6.1.6,41 5.6.2.1.1,
503, 504, 505, 506, 508
Interior finishes 416.2.1,416.3.1,
Table 803.9, 804
Irritants Table 414.2.5(1),
Table 415.8.2.1.1
Liquid, highly toxic and toxic 307.6,
Table 414.2.5(1), 415.7.3, 415.7.4,
Table 415.8.2.1.1, 908.3
Live load Table 1607.1
Location on property 414.6.1 .2, 415.3
Multiple hazards 307.8
Organic peroxides Table 414.5.1,
Table 415.3.2, 415.4.1,
415.5.1, Table 415.8.2.1.1, 418
Oxidizers, liquid and solid Table 414.2.5(1),
Table 414.5.1, 415.5.1,
Table 415.3.2, Table 415.8.2.1.1
Pyrophoric materials 307.4, Table 307.1(1),
Table 414.5.1, 415.4.1,
Table 415.3.2, 415.5.1,Table 415.8.2.1.1
Routes (accessible) 1 108B.2
Sanitation facilities (accessible) 1108B.2
Sensitizers Table 415.8.2.1.1
Separation from other occupancies 415.3.1,
508.2.4,Table 508.2.5,
508.3,3, 508.4
Solids, highly toxic and toxic 307.6,
Table 414.2.5(1), 415.7.3,
415.7.4, Table 415.8.2.1.1, 908.3
Smoke and heat vents 910.2
Sprinklers 415.5.2, 415.6.2.4,
415.8.6.3,415.8.9,415.8.10.1,
415.8.11,705.8.1,903.2.5
Standby power systems 414.5.4, 2702.2.8,
2702.2.10 through 2702.2.13
Storage 413,414.1,414.2.5,
414.5,414.6,414.7.1,415.2.
415.3, Table 415.3.2, 415.4.1,
415.5,415.6.1,415.6.2
Tanks 415.6.2
Travel distance 1014.3, 1016.1, 1021.2
Unlimited area 507.8
Unstable materials 307.3, Table 414.2.5(1),
Table 414.5.1, Table 415.3.2, 415.4.1,
415.5.1, Table 41 5.8.2.1.1
Water-reactive materials Table 414.5.1 ,
Table 41 5.3.2,415.5,
415.5.1,415.5.2,415.8,
Table 41 5.8.2.1.1
HIGH-RISE BUILDINGS 403
Application 403.1
Construction 403.2
Elevators 403.6, 1007.2.1, 1124A, 3007, 3008
Emergency power 403.4.8, 2702.2.15
Emergency systems 403.4
Fire alarm 403.4.2
Fire alarm anc detection 403.4.1, 907.2.13
Fire command station 403.4.5
Fire department communication . . . 403.4.3, 403.4.4
Fire service elevators 403.6.1 , 3007
Occupant evac:uation elevators 403.6.2, 3008
Smoke removal 403.4.6
Smokeproof enclosure 403.5.4, 1022.9
Sprayed fire-resistant materials (SFRM) 403.2.4
Sprinklers 403.3, 903.2.1 1 .3
Stainways 1002. 1, 403.5
Standby power 403.4.7, 2702.2.5, 2702.2.15
Structural integrity 403.2.3, 1614
Super high-rise (over 420 feet) 403.2.1, 403.2.3,
403.2.4,403.3.1,403.5.2
Voice alarm 403.4.3, 907.2.13
Zones 907.6.3.2
HISTORIC BUILDINGS 1 135B 3409
Accessible 1119B, 11356,3411.9
Flood provisions G105.3
HORIZONTAL ASSEMBLY 712
Continuity 508.2.5.1, 712.4, 708.11, 708.12
Fire-resistance rating 603.1(21), 603.1(22),
603.1(25), 703, 707.3.9, 712.3
Glazing, rated 715.5
Group 1-1 420.3
Group R 420.3
Incidental accessory occupancies 508.2.5.1
Insulation 719, 807, 808
Joints 714, 2508.4
Opening protection 712.8, 713.4, 715, 716.6
Shaft enclosure 708.1
Special provisions
Aircraft hangars 41 2.4.4
Atrium 404.3, 404.6
Covered malt 402.4.6, 402.7.1
Fire pumps 91 3.2.1
Flammable finishes 416.2
Group H-2 415.6.1.2, 415.6.2.2
Group H-3 and H-4 415.7
Group H-5 415.8.2.2, 415.8.5.2
Group 1-2 407.4.3
Groups 1-1 , R-1 , R-2, R-3 420.3
2010 CALIFORNIA BUILDING CODE
747
INDEX
Hazardous materials 414.2
High-rise 403.2.1, 403.3, 403.4.7.1
Hydrogen cutoff 421 .4
Organic coating 418.4, 418.5, 418.6
Stages and platforms 410.5.1, 410.5.2
HORIZONTAL EXIT 1025
Accessible means of egress 1007.2, 1007.2.1,
1007.3, 1007.4, 1007.6, 1007.6.2
Doors 1025.3
Exit discharge 1027.1
Fire resistance 1025.2
Institutional 1-2 occupancy 407.4, 1025.1
Institutional 1-3 occupancy 408.2, 1025.1
Refuge area (see REFUGE AREAS)
HORIZONTAL FIRE SEPARATION
(see HORIZONTAL ASSEMBLY)
HOSE CONNECTIONS
(see STANDPIPES, REQUIRED)
HOSPITAL
(see INSTITUTIONAL GROUP 1-2) 308.3, 407
HOSPITAL
Application 1224.2
Definitions 1224.3
General construction 1224.4
Reserved 1224.5-1224.13
Scope 1224.1
HOSPITAL - BASIC SERVICES
Anesthesia service space 1224.16
Clinical laboratory service space 1224.17
Dietetic service space 1224.20
Nursing service space 1224.14
Pharmaceutical service space 1224.19
Radiological/imaging service space 1224.18
Surgical service space 1224.15
HOSPITAL - SUPPORT SERVICES
Administration space 1224.21
Central sterile supply 1224.22
Employee dressing rooms and lockers 1224.25
Housekeeping rooms 1224.26
Laundry 1224.27
Morgue and autopsy facilities 1224.24
Storage 1224.23
HOSPITAL - SUPPLEMENTAL SERVICES
Emergency service 1224.33
Intensive care units 1224.29
Intermediate-care service space 1224.38
Nuclear medicine 1224.34
Obstetrical facilities (perinatal unit) 1224.32
Outpatient service space 1224.39
Pediatric and adolescent unit 1224.30
Psychiatric nursing unit 1224.31
Rehabilitation therapy department 1224.35
Renal dialysis service space 1224.36
Respiratory therapy service space 1224.37
Skilled nursing service space 1224.40
Social service space 1224.41
Supplemental surgery services 1224.28
HOTEL (or MOTEL) (definition) 202
HURRICANE-PRONE REGIONS
(see WIND LOADS) 1609.2
HURRICANE SHELTER (see STORM SHELTER)
HURRICANE SHUTTERS 1609.1.2
HYDROGEN CUTOFF ROOMS. ... 421 , Table 508.2.5
I
IDENTIFICATION, REQUIREMENTS FOR
Fire barriers 703.6
Fire partitions 703.6
Fire wall 703.6
Glazing 2403.1, 2406.3
Inspection certificate 1702.1
Labeling 1703.5
Preservative-treated wood 2303.1.8.1
Smoke barrier 703.6
Smoke partition 703.6
Steel 2203.1
IMPACT LOAD 1602.1, 1603.1.1, 1607.8
INCIDENTAL USE AREAS
(see ACCESSORY OCCUPANCIES)
INCINERATOR ROOMS 1015.3
INDUSTRIAL (see FACTORY OCCUPANCY)
INSPECTIONS 110, 1704, 1705, 1706, 1707
Alternative methods and materials 1704.15
Approval required 1 10.6
Atrium buildings 909.3
Concrete construction 110.3.1, 110.3.2,
110.3.9,1704.4
Concrete slab 1 10.3.2
Continuous 1702.1
EIFS 110.3.9,1704.14
Energy efficiency 1 10.3.7
Fabricators 1704.2
Fees 109
Final 110.3.10
Fire-resistant materials. . . 110.3.9, 1704.12, 1704.13
Fire-resistant penetrations 1 10.3.6
Footing or foundation 110.3.1, 110.3.9,
1704.4,1704.5,1704.8,
1704.9, 1704.10, 1704.11
Frame 110.3.4
Lath or gypsum board 1 10.3.5, 2503
Liability 104.8
Masonry 110.3.9, 1704.5, 1704.11
Periodic 1702.1
Preliminary 1 1 0.2
Required 1 1 0.3
Right of entry 104.6
Seismic 1 707
Smoke control 104.16, 1704.16
Soils 110.3.9,1704.7
Special (see STRUCTURAL
TESTS AND SPECIAL
INSPECTIONS) 110.3.9, 1704, 1706, 1707
748
2010 CALIFORNIA BUILDING CODE
INDEX
Sprayed fire-resistant materials 1704.12
Sprinklers, automatic 904.4
Steel 110.3.4, 110.3.9, 1704.3
Third party 1 1 0.4
Welding 110.3.9, 1704.3, 2204.1
Wind 110.3.9,1706
Wood, structural 1 10.3.9, 1704.6
INSTITUTIONAL 1-1 [see INSTITUTIONAL
OCCUPANCY (GROUP I)] 308.2
Accessibility 1109B, 1106.7.2, 1107.5.1
Combustible decorations 806.1
Emergency escape and rescue 1029
Fire alarm and detection 907.2.6.1,
907.2.11.2,907.5.2.3.2
Special occupancy separation 420, 508.2.4,
Table 508.2.5, 508.3.3
Sprinklers 903.2.6, 903.3.2
Travel distance 1014.3, 1016.1, 1021.2
Visible alarms 420.4.4, 907.5.2.3.3
INSTITUTIONAL 1-2 [see INSTITUTIONAL
OCCUPANCY (GROUP I)] 308.3, 407
Accessibility 1 109B
Combustible decorations 806.1
Corridors 407.2, 407.3, 1018.2
Doors 1008.1.9.6
Exterior exit stair 1026.2
Fire alarm and detection 407.6, 407.7, 907.2.6.2
Hardware 1008.1.9.6
Hyperbaric facilities 407.9
Occupancy category Table 1604.5
Smoke barriers 407.4
Smoke compartment 407.2.1 , 407.2.3,
407.4, 407.5
Smoke partitions 407.3
Special occupancy separation Table 508.2.5
Sprinklers 407.5, 903.2.6, 903.3.2
Suites 1014.2.2 through 101 4.2.7
Travel distance 407.4, 101 4.2.3.3,
101 4.2.4.3,101 4.2.4.4,
1014.2.6, 1014.3, 1016.1, 1021.2
Yards 407.8
INSTITUTIONAL 1-3 [see INSTITUTIONAL
OCCUPANCY (GROUP I)] 308.4, 408
Accessibility 1 109B
Combustible decorations 806.1
Exit sign exemption 101 1 .1
Fire alarm and detection 408.10, 907.2.6.3
Hardware 408.4, 1008.1.9.9
Means of egress 408.2, 408.3, 408.4
Occupancy category Table 1604.5
Security glazing 408.7
Separation 408.5, 408.8
Smoke barrier 408.6
Smoke compartment 408.4.1 , 408.6, 408.9
Special occupancy separation Table 508.2.5
Sprinklers 903.2.6
Travel distance 408.6.1, 408.8.1 ,
1014.3,1016.1,1021.2
INSTITUTIONAL. 1-4 [see INSTITUTIONAL
OCCUPANCY (GROUP I)] 308.3.1, 308.5
Accessibility 1 109B
Corridor rating 1018.1
Fire alarm 907.2.6
Sprinklers 903.2.6
Travel distance 1014.3, 1016.1, 1021.2
INSTITUTIONAL
OCCUPANCY (GROUP I) 308, 1109B
Accessibility (General) 1 109B. 1
Accessory 508.2
Adult care 308.5.1
Area 503, 505, 506, 507, 508
Child care 308.3.1 , 308.5.2, 310.1
Diagnostic and treatment areas 1109B.6
Entrance 1 109B.2
Group 1-1 308.2
Group 1-2 308.3, 407
Group 1-3 308.4, 408
Group 1-4 day- care facilities . . . 308.3.1, 308.5, 310.1
Height 503, 504, 505, 506, 508
Interior finishes Table 803.9, 804
Live load Table 1607.1
Offices and suites 1 109B.8
Patient bedrooms and toilet rooms 1 109B.3
Patient bedroom areas 1109B.4
Patient toilet rooms and battling facilities . . . 1109B.5
Plumbing fixtures 2902
Special occupancy separation 420, 508.2.4,
Table 508.2.5, 508.3.3
Waiting areas, offices and
sanitary facilities 1109B.7
INSULATION
Concealed 719.2
Duct insulation 71 9.1
Exposed 719.3
Fiberboard 719.1, 1508.1.1,
2303.1.5.2,2303.1.5.3
Foam plastic (see FOAM PLASTICS) 719.1
Loose fill 719.4, 719.6
Pipe insulation 719.1,719.7
Reflective plastic core 2613
Roof 719.5,1508
Sound 719, 807, 1207
Thermal 719, 807, 1508
INTERIOR ENVIRONMENT
Lighting 1205
Rodentproofing Appendix F
Sound transmission 1207
Space dimensions 1208
Temperature control 1204
Ventilation 409.3, 414.3, 415.8.2.6, 1203.4
Yards or courts 1206.2, 1206.3
INTERIOR FINISHES Chapter 8
Acoustical ceiling systems 807, 808
Application 803.10, 804.4
Atriums 404.8
Decorative materials 801.1.2, 806
2010 CALIFORNIA BUILDING CODE
749
INDEX
Floor finish 804, 805
Foam plastic insulation 2603.3, 2603.4
Foam plastic trim 806.3, 2604.2
insulation 807
Light-transmitting plastics 2606
Signs .402.16,2611
Trim 806.5, 806.6
Wall and ceiling finishes 803
Wet location 1210, 2903
INTERNATIONAL SYMBOL OF
ACCESSIBILITY (definition) 202, 1107A.9.-I
INTERPRETATION, CODE 104.1
JAILS (see INSTITUTIONAL 1-3) 308.3, 408
JOINT
Concrete construction joints 1906.4
Gypsum board 2508.4
Lumber sheathing 2308.10.8.1
Shotcrete 1913.7
Structural plain concrete 1909.3
Waterproofing 1805.3.3
JOINTS, FIRE-RESISTANT SYSTEMS 714
K
KICK PLATE (definition) 202, 1 107A.1 1-K
KIOSKS 402.11
KITCHENS Table 508.4(d) , 1 1 17B.3
Accessibility 1 133A,
11 11 BAA, 1114B.1.2, 1117B.3
Dimensions 1208
Means of egress 1014.2
Occupant load Table 1004.1.1
Rooms openings 1210.5
LABORATORIES
Classification of 304.1
Hazardous materials 414, 415
Incidental accessory occupancies .... Table 508.2.5
LADDERS
Boiler, incinerator and furnace rooms 1015.3
Construction 1009.4.2, 1012.2,
1012.6, 1013.2, 1013.3
Emergency escape window wells 1029.5.2
Group 1-3 408.3.5, 1009.11
Heliport 412.7.3, 1021.1.3
Refrigeration machinery room 1015.4
Stage 410.5.3, 1015.6.1
LAMINATED TIMBER,
STRUCTURAL GLUED. .. 602.4, 2303.1, 2304.11.3.
2306.1 , 2308.8.2.1 , 2308.1 0.7
LANDINGS
Doors 1008.1 .6
Ramp 1010.6
Stair 1002.1, 1009.5
LATH, METAL OR WIRE Table 2507.2
LAUNDRIES 304.1, 306.2, Table 508.2.5
LAUNDRY CHUTE 708.13, 903.2.11.2
LEGAL
Federal and state authority 102.2
Liability. 104.8
Notice of violation 1 14.2, 1 16.3
Registered design professional 107.1, 107.3.4
Right of entry 104.6
Unsafe buildings or systems 116
Violation penalties 1 14.4
LEVEL AREA (definition) 202, 1 107A.12-L
LIBRARIES
Classification, other than school 303.1
Classification, school 305.1
Live load Table 1607.1
LIFT, PLATFORM (WHEELCHAIR)
(See PLATFORM (WHEELCHAIR) LIFT)
LIGHT, REQUIRED 1205
Artificial .....1205.3
Emergency (see EMERGENCY LIGHTING)
Natural .....1205.2
StainA^ays ...,.: 1002.1, 1205.4
Yards and courts 1 206
LIGHTS, PLASTIC CEILING DIFFUSERS 2606.7
LINTEL
Adobe 2109.3.4.7
Fire resistance 704.1 1
Masonry 2104.1.5
Masonry, wood support 2304.12
LIQUEFIED PETROLEUM GAS 415.6.3
LISTED (definition) 202
LISTING AGENCY (definition) 202
LIVE LOADS 1602.1, 1607
Construction documents 107.2, 1603.1.1
Posting of 106.1
LIVE/WORK UNITS 310.1, 419
Separation 508.1
LOAD AND RESISTANCE
FACTOR DESIGN (LRFD) 1602.1
Load combinations 1605.2
Wood design 2301.2, 2307
LOAD COMBINATIONS 1605
Allowable stress design 1605.3
Load and resistance factor design 1605.2
Strength design 1605.2
LOADS 106, 1602.1
Combinations 1605
Dead 1602.1, 1606
Flood 1603.1.7.1612
Impact 1602.1, 1607.8
Live 419.6, 1603.1.1, 1607
Rain 1611
Seismic 1603.1.5, 1613
Snow 1603.1.3, 1608
Soillateral 1610
Wind 1603.1.4, 1609
750
2010 CALIFORNIA BUILDING CODE
INDEX
LOBBIES
Assembly occupancy 1028.4
Elevator 708.14.1, 1007.2.1,
1007.4,3007.4,3008.11
Exit discharge 1027.1
LOBBY (definition) 202
LOCAL ENFORCING AGENCY 1 .8.3
LOCKS AND LATCHES 1008.1 .9, 1008.1.10
Access-controlled egress 1008.1.4.4
Delayed egress locks 1008.1 .9.7
Electromagnetically locked 1008.1.9.8
Group 1-2 1008.1.9.6
Group 1-3 408.4, 1008.1.9.9
Group R-4 . . . . 1008.1 .9.5.1
High-rise 403.5.3
LODGING HOUSE (definition) 202
LUMBER
General provisions Chapter 23
Quality standards 2303
M
MAINTENANCE
Accessibility. . . . 1101B.3, 11038.3,1, 11173.5,8.1.2,
1 117B.5. 11. 2(4), 34M. 2
Means of egress 3310.2
MALL (see COVERED MALL AND OPEN MALL
BUILDINGS)
MANUAL FIRE ALARM BOX 907.4.2
Height 907,4,2.2
Operation 11 17B,6(4)
MANUFACTURED HOMES
Flood resistant G501
MARKED CROSSING (definition) . . 202, 1 107 A, 13-M
MARQUEES 3106, H113
Drainage, water 3201 .4
Live load Table 1607.1, 1607.11
MASONRY
Adhered veneer 1405.10
Adobe 2109.3
Anchorage 1604.8.2
Anchored veneer 1405.6
Ashlar stone 2102.1
Autoclaved aerated concrete (AAC) . . 2102.1, 2103.3
Calculated fire resistance 721 .4
Chimneys 2113
Cold weather construction 2104.3
Construction 2104, 2109.2.2
Construction documents 2101.3
Corbelled 2104.2
Damp proofing 1805.2.2
Design, methods 2101.2, 2107 through 2109
Fire resistance, calculated 721.3.2, 721.3.4
Fireplaces 2101 .3.1,2111
Floor anchorage 1604.8.2
Foundation walls 1 807.1 .5
Foundations, adobe 2109.3.4.3
Glass unit 2101.2.5, 2103.6, 2110
Grouted 2102.1
Headers (see BONDING. MASONRY) 2109.2
Heaters 2112
Hot weather construction 2104.4
Inspection, sp€)cial 1704.5
Joint reinforcement 2103.13
Materials 2103
Penetrations 713
Quality assurance 2105
Rodent proofing Appendix F
Roof anchorage 1604.8.1
Rubble stone 2102.1
Seismic provisions 2106
Serviceability 1604.3.4
Stone 2103.4, 2109.2
Support 2304.12
Surface bonding 2103.9
Test proceduress 2105.2.2.2, 2105.3
Tie, wall 21 04.1.3
Veneer 1405.6, 1405.10, 2101.2.6, 2308.11.2
Wall, composite 2102.1
Wall, hollow ,. 2102.1
Wall anchorage 1604.8.2
Waterproofing 1805.3.2
Wythe 2102.1
MATERIALS
Alternates 104.1 1
Aluminum Chapter 20
Concrete Chapter 1 9
Glass and glaring Chapter 24
Gypsum. Chapter 25
Masonry Chapter 21
Noncombustible 703.4
Plastic Chapter 26
Steel Chapter 22
Testing (see TESTING) 1716
Wood Chapter 23
MEANS OF EGRESS Chapter 10
Accessible . . 1007, Chapter 11 A, 2702,2.5, 2702.2.6
Aircraft related 412.3.3, 412.5.2
Alternating tread device 412.7.3, 505.5,
1009.10, 1015.3, 1015.4
Ambulatory care facilities 422.4
Assembly 1007.1 , 1028
Atrium 404.9, 707.3.5
Capacity 1005.1
Child care facilities (see Day-care facilities)
Ceiling height 1003.2
Construction drawings 107.2.3
Covered mall and open mall buildings 402.4,
402.5,402.13
Day-care facilities 308.5, 310.1, Table 1004.1.1,
Table 101 5.1(a), Table 1021 .2(e)
Doors 1005.2, 1008, 1015, 1020.2,
Chapter 11 A, 2702.2.7
During construction 3303.3, 3310
Elevation change 1003.5
Elevators 403.5.2, 403.6.2, 1003.7, 1007, 3008
Emergency escape and rescue 1 029
Equipment platform 505.5
2010 CALIFORNIA BUILDING CODE
751
INDEX
Escalators 1 003.7
Existing buildings 1007.1, 3310, 3404.6,
3406.1,3412.5,3412.6.11
Exit (see EXIT) 1020 through 1026
Exit access
(see EXIT ACCESS) 1014 through 1019
Exit definition 1002.2
Exit discharge (see EXIT DISCHARGE) 1027
Exit enclosures 1022.1
Exit signs 1011, 2702.2.3, 2702.2.9
Fire escapes 3406
Floor identification signs . 1022.8, 1117B.5.1 (Item 1)
Floor surface 804, 1003.4
Gates .1008.2
Group 1-2 407.4
Group 1-3 408.2, 408.3, 408.4, 408.6
Guards (or Guardrails) 1002.1, 1013
Handrails 1002. 7, 1012, Oiapter 1 1A
Hazardous materials 414.6.1.2,
415.8.4.4,415.8.5.5
Headroom 1003.2, 1003.3
Helistops .412.7.3, 1021.1.3
High hazard Group H 415.8.4.4, 41 5.8.5.5
High-rise 403.5, 403.6
Illumination 1006, 2702.2.4, 3412.6.15
Interior finish 803.9, 804
Ladders (see LADDERS)
Live loads Table 1607.1
Live/work units 419.3
Mezzanines 505.3, 505.4, 1004.6, 1007.1
Moving walk 1003.7
Occupant load 1004.1, 1004.1.1, 1004.2
Parking 406.3.8
Protruding objects Cfiapter 1 1A, Cfiapter 1 1B,
1003.3, 1005.2, 11338.8.6
Ramps 1010, 1026
Scoping 101.3, 105.2.2, 108.2, 1001.1
Seating, fixed 1007.1, 1028
Special amusement 41 1 .7
Stages 41 0.3.3, 41 0.5.3, 1015.6
StainA/ays 403.5, 1002.1, 1009, 1022.1, 1026,
Cfiapter 11 A, 11338.4
Temporary structures 3103.4
Travel distance
(see TRAVEL DISTANCE) 1014.3, 1016
Turnstile 1008.3
Underground buildings 405.5.1, 405.7
Width 1005.1, Table 1005.1, 1009.1,
101 0.5.1, 1018.2,1028.6,1028.8
MECHANICAL (see AIR CONDITIONING,
HEATING, REFRIGERATION AND
VENTILATION) 101.4.2
Access 1009.13, 1009.14, 1209.3
Air transfer openings 705.10, 706.1 1 ,
707.9, 708.2(7), 708.10,
709.9,710.8,711.7,712.7,
713.1.1,713.4.1.3,716
Chimneys (see CHIMNEYS)
Code Chapter 28
Disconnected 3303.6
Ducts 704.8, 705.10, 706.11,
707.9, 708.2(4), 708.2(15),
708.10,709.9,710.8,711.7,
712.7,713.1.1,713.4.1.3,716
Encroachment, public right-of-way 3202.3.2
Equipment on roof 1509, 1510.2
Equipment platforms 505.5
Factory-built fireplace 2111.14.1
Fireplaces 2111
Motion picture projection room 409.3
Permit required 105.1, 105.2
Roof access 1009.13
Room separation Table 508.2.5
Seismic inspection and testing 1707.7,
1707.8. 1708.4
Smoke control systems 909
Systems 1613.2, Chapter 28
MECHANICALLY LAMINATED DECKING . . . 2304.8.3
MEMBRANE ROOF COVERINGS 1507.11,
1507.12,1507.13
MEMBRANE STRUCTURES 2702.2.9, 3102
MENTAL HOSPITALS 308.3
MERCANTILE OCCUPANCY (GROUP M)
Accessibility 11 108
Accessory 508.2
Aisles 1017.2, 1017.3
Area 503, 505, 506, 507, 508
Classification 309
Cfieckstands 11 108. 1.3
Circulation 11108.2.1
Fire alarm and detection 907.2.7
Height 503, 504, 505, 506, 508, 509
Interior finishes Table 803.9, 804
Live load Table 1 607.1
Miscellaneous general standards 11 108.2
Parking beneath or above 509.2, 509.7,
509.8, 509.9
Plumbing fixtures 2902
Point-of-sale macfiines 11 108. 1.4
Sales 11108.1
Special occupancy separation . . 309.1 , Table 508.2.5
Sprinkler system, automatic 903.2.7
Storage areas 11 108.2.2
Tfteft prevention barriers 11108. 1.6
Travel distance 402.4, 1014.3, 1016.1. 1021.2
Turnstiles 11 108. 1.5
Unlimited area 507.3, 507.4, 507.12
Workareas 11108.1.2
METAL
Aluminum Chapter 20
Roof coverings 1504.3.2, 1507.5
Steel Chapter 22
Veneer 1404.5
MEZZANINES 505
Accessibility 11038.1, 11218.3.1(6)
Area limitations . 505.2, 505.5.1
Egress 505.3, 505.4, 1004.6, 1007.1
Equipment platforms 505.5
Guards(or Guardrails) 505.5.3, 1002.1, 1013.1
752
2010 CALIFORNIA BUILDING CODE
INDEX
Height 505.1 , 1003.2
Occupant load 1004.6
Stairs 708.2(9), 1002.1, 1009.10, 1022.1
MIRRORS 1008.1, 2406.1, 2406.4.1(7)
MIXED OCCUPANCY (see OCCUPANCY
SEPARATION)
MOISTURE PROTECTION 1210, 1403.2,
1503,2303.2.4,2304.11
MONASTERIES 310.1
MORTAR 2102.1
Ceramic tile 2103.5
Damp proofing 1805.2.2
Fire resistance 713.3.1, 713.4.1.1
Glass unit masonry 2110.1.1
Masonry 2103.8, 2103.9
Rodent proofing Appendix F
MOTEL (definition) 202
MOTELS 310.1
MOTION PICTURE PROJECTION ROOMS 409
Construction 409.2
Exhaust air 409.3.2, 409.3.3
Lighting control 409.3
Supply air 409.3.1
Ventilation 409.3
MOTOR FUEL-DISPENSING SYSTEM 406.5
Accessibility 1117B.7.2 (Exc. 5)
MOTOR VEHICLE FACILITIES 304, 31 1, 406
MOVING, BUILDINGS 3410, D103.3
MOVING WALKS 3005.2
Means of egress 1 003.7
MULTISTORY DWELLING UNIT (definition) .... 202,
1 107 A. 13-M
N
NAILING 2302.1 , 2303.6, 2304.9
NEW BUILDINGS Chapter 1 1B Div I
NONBUILDING STANDARDS 1.1.6
NEWLY CONSTRUCTED (definition) 202,
1107A.14-N
NONCOMBUSTIBLE BUILDING MATERIAL . . . 703.4
NONSTATE-REGULATED BUILDINGS,
STRUCTURES AND APPLICATIONS 1.1.3.1
NOSING (or NOSE) (definition) .... 202, 1107A.14-N
NURSING HOMES
(see INSTITUTIONAL, GROUP 1-2) 308.3, 407
o
OCCUPANCY
Accessory 508.2
Atriums 404.2
Certificates (see CERTIFICATE OF OCCUPANCY)
Change (see CHANGE OF OCCUPANCY)
Floor loads Table 1607.1
Special Chapter 4
OCCUPANCY OVTEGORY
(Seismic Design) 1602.1, 1604.5
Multiple occupancies 1604.5.1
OCCUPANCY CLASSIFICATION 302
Covered mall and open mall buildings 402
HPM 415.8
Mixed 508.3
Mixed occupancy values . 508, 3412.6.16
Special Chapter 4
OCCUPANCY SIEPARATION
Accessory 508.2
Aircraft related 412.4.4, 412.5.1
Covered mall c.nd open mall building 402.7
Incidental accessory occupancies . . 508.2.5, 707.3.6
Mixed occupancy 508, 509, 707.3.8
Parking garage.'S 406.1.4, 406.2.7,
Table 508.3.3(c)
Repair garage;; 406.6.2
Required fire resistance Table 508.4, 509
Stages 410.5.1 , 41 0.5.2
OCCUPANT EVACUATION ELEVATORS .... 403.5.2,
403.6.2, 3008
OCCUPANT LOAD
Actual 1004.1.1
Certificate of occupancy 111
Covered mall and open mall building 402.4.1
Determination of 1004.1, 1004.1.1
Increased 1 004.2
Outdoors 1004.8
Seating, fixed 1004.7
Signs 1004.3
OFFICE BUILDINGS
Classification 304
Live loads Table 1607.1 , 1607.5
OPEN MALL BUILDINGS (see COVERED MALL
AND OPEN MALL BUILDINGS)
OPEN RISER (definition) 202, 1107A.15
OPENING PROTECTION,
EXTERIOR WALLS 705.8
OPENING PROTECTION, FLOORS
(see VERTICAL OPENING PROTECTION)
OPENING PROTECTIVES 705.8, 706.8,
707.6, 708.7, 709.6,
710.5,712.8,715
Automatic closing devices 715.4.8, 909.5.2
Fire door and shutter assemblies 705.8.2,
712.8,715.4
Fire windows .715.5
Glazing 715.5
Glass unit masonry
(see GLASS UNIT MASONRY) 2110.1.1
Self-closing 715.4.7
ORDER OF PRECEDENCE AND USE 1.1.7
Conflicts 1.1.7.3
Differences 1.1.7.1
Specific provisions 1. 1.7.2
ORGANIC COATINGS 418
ORGANIC PEROXIDES 307.4, 307.5
2010 CALIFORNIA BUILDING CODE
753
INDEX
OTHER BUILDING COMPONENTS 1117B
Accessibility signs (General) 1117B.5. 1(3)
Accessible drinking fountains 1117B.1
Accessible sinks 1 1178.9
Assistive listening systems 11178.5.8.4
ATM equipment for persons with
vision impairments 11178.7.6
ATM (Where 1 is provided) 11178.7.4.1
ATMs (Where 3 or more are provided). . 1 1178.7.4.3
ATMs (Where 2 are provided) 11178.7.4.2
Automated teller machines (ATMs) and
point of sale machines 11178.7
Braille (Signs & identification) 11178.5.6
Character height (Signs & identification) . . 11178.5.4
Cleaner air symbol 1 1178.5. 1 1
Clear floor space (Controls/operating
mechanisms) 11 178.6(2)
Clear floor/ground space (Telephones) . . . 11178.2.2
Color and size of symbol (Cleaner air) . 11178.5.11.1
Clearances and reach range (ATMs) 11178.7.3
Color of symbol (ISA) 11178.5.8.1.1
Conditions of use (Cleaner air) 1 1178.5. 1 1.2
Controls (ATMs) 11178.7.3
Controls (Text telephones) / 1178.2. 10
Controls and operating mechanisms 11178.6
Cord length (Text telephones) 11 178.2. 1 1
Directional/informational
signs (General) 1 1178.5. 1(2)
Display (LED/cathode ray/
screen device) 11178.7.5
Electrical receptacle outlets (Controls/
operating mechanisms) height 11178.6(5.2)
Electrical switches (Controls/operating
mechanisms) height 1 1178.6(5. 1)
Enclosures (Telephones) 11178.2.7
Entrance sign (ISA) 11178.5.8.1.2
Finish/contrast (Signs & identification). ... 11178.5.2
Fitting/dressing rooms 1 1178.8
Floor surfaces of wheelchair
spaces (Telephones) 1 1178.2.5
Height (Controls/operating
mechanisms) 1 1178.6(3)
Height of electrical switches/
receptacle outlets (Controls/operating
mechanisms) 1 1178.6(5)
Identification signs (General) 11178.5.1(1)
Information posted (ISA) 11178.5.8.1.3
International symbol of accessibility
([ISA] Signs & identification) 1 1178.5.8. 1
International TTY symbol 11178.5.8.2
Kitchens 11178.3
Mounting location and height
(Signs & identification) 11 178.5.7
Mounting height (Telephones) 11178.2.6
Operation (Controls/operating
mechanisms) / 1178.6(4)
Proportions (Signs & identification) 11178.5.3
Raised characters/pictorial symbol signs
(Signs & identification) 1 1178.5.5
Reach range/clearances (ATMs) 11178.7.4
Removal of symbol (Cleaner air) 11178.5.11.3
Relationship of maneuvering clearances
to wheelchair spaces (Telephones) .... 11178.2.4
Signage
(Text telephones) 11178.2.9.3, 11178.5.10
Signs and identification 11178.5, 11178.5.1
Sinks (Accessible) 11 178.9
Size and approach (Telephones) 1 1178.2.3
Swimming pools 1 1178.4
Symbols of accessibility
(Signs & identification) 1 1178.5.8
Telephone books (Text telephones) 1 1178.2. 12
Telephone equipment for hearing
impaired persons 1 1178.2.8
Telephones / 1178.2
Text telephones 11178.2.9, 11178.2.9.2
Traffic control devices / 1178.5.9
Volume control telephones 11 178.5.8.3
Where required (Text telephones) 1 1178.2.9. 1
OUTDOOR OCCUPANCIES 11328
General 1 1328. 1
Highway rest areas 1 1328.3
Parks and recreational areas 1 1328.2
Permanent facilities
(Highway rest areas) 1 1328.3. 1
OXIDIZERS, LIQUID AND SOLID 307.2
PANIC HARDWARE 1008.1.10
PARAPET, EXTERIOR WALL . . . 705.11, 2109.3.4.1.4
Construction 705.1 1.1
Fire wall 706.6
Height 705.11.1
PARKING, ACCESSIBLE 1108A , 11298
General (Accessible parking) 1 1298. 1
Identification of parking spaces for
off-street parking facilities 1 1298.4
Medical care outpatient facilities 1 1298.2
Parking space size 1 1298.3
PARKING GARAGES 406.2
Accessibility. Chapter 1 1A, 1 1308.2
Barriers, vehicle 406.2.4, 1602.1, 1607.7.3
Classification 31 1 , 406.2.1
Construction type 406.3.3, Table 503, Table 601
Enclosed
(see PARKING GARAGE, ENCLOSED) .... 406.4
Gates 3110
Guar6s(or Guardrails) . . . 406.2.3, , 1002.1, 2407.1.3
Height, clear 406.2.2, Chapter 1 1A
Live loads Table 1607.1, 1607.9.1.3
Occupancy separation 406.2.7, 508, 509
Open (see PARKING GARAGE, OPEN) 406.3
Special provisions 509
Springs, garage door 1211
Sprinklers 903.2.10
Underground 405
754
2010 CALIFORNIA BUILDING CODE
INDEX
PARKING GARAGES, ENCLOSED 406.4
Area and height [see STORAGE OCCUPANCY
(GROUPS)] 406.4.1
Means of egress 1003.2, 1010.1, 1021.1.2
Ventilation 406.4.2
PARKING GARAGES, OPEN 403.1 , 406.3
Area and height [see STORAGE
OCCUPANCY (GROUP S)] 406.3.5, 406.3
Construction type 406.3.3
IVIeans of egress 406.3.8, 1003.2, 1007.3,
1007.4, 1010.1, 1016.1, 1018.1,
1021.1.2, 1022.1, 1024.1, 1027.1
Occupancy separation 406.3.4
Standpipes 406.3.9
Ventilation 406.3.12
PARKING STRUCTURES 1130B
PARTICLEBOARD 2302.1
Draftstopping 717.3.1
Moisture protection 1403.2, 1405.2
Quality 2303.1.7
Shear walls 2306.5
Veneer 1 405.5
Wall bracing 2308.9.3
PARTITIONS
Fire (see FIRE PARTITION)
Live loads 1607.5, 1607.13
Materials 602.4.6, 603.1(1 0), 603.1(25)
Occupancy, specific 709.1
Smoke (see SMOKE PARTITION)
Toilets 2903
PARTY WALLS
(see FIRE WALLS) 706.1.1, Table 715.5
PASSAGE DOOR (definition) 202,1 107 A. 16-P
PASSAGEWAY, EXIT (see EXIT) 1023.1
PASSENGER DROP-OFF AND
LOADING ZONES 1131B
Bus stop pads and shelters 1 131 B.4
Location 1 131B. 1
Passenger loading zones 1 131B.2
Valet parking 1131B.3
PASSENGER ELEVATOR (definition) 202
PASSENGER STATIONS 303
PASSIVE SOLAR ENERGY
COLLECTOR (definition) 202
PATIO COVERS 2606.10, Appendix I
PEDESTRIAN
Definition 202, 1107A.16'P
Protection at construction site 3303.2, 3306
Walkways and tunnels 3104, 3202.3.4
PEDESTRIAN GRADE SEPARATION
(Overpasses/Underpasses) 1 128B
PEDESTRIAN RAIVIP (definition) . . . 202, 1 107 A. 16-P
PEDESTRIAN WAY (definition) 202, 1107A.16-P
PENALTIES 1 14.4
PENETRATION-FIRESTOP SYSTEM
Fire-rated walls 71 3.3.2
Fire-rated horizontal assemblies 713.4.1.2
PENETRATIONS 713, 716
Fire-resistant assemblies
Exterior wall 705.10
Fire barrier 707.7, 707.9
Fire partition 709.7, 709.9
Firewall 706.9, 706.11
Horizontal assemblies 712.5, 712.7, 713.4
Shaft enclosures 708.1 , 708.2, 708.8, 708.10
Smoke barriers. 710.6, 710.8, 713.5
Smoke partitions 71 1 .6, 71 1 .7
Walls 713.3
Nonfire-resistant assemblies 713.4.2
PERLITE Table 720.1(1), Table 2507.2
PERMITS 105
Application for 104.2, 105.1, 105.3
Drawings and specifications 107.2.1
Expiration 1 05.5
Fees 109
Liability for issuing 104.8
Placement of permit 105.7
Plan review 104.2, 107.3
Suspension or revocation 1 05.6
Time limitations 105.3.2, 105.5
PERSONS WITH DISABILITIES (definition) .... 202,
1107A.16-P
PIER FOUNDATIONS
(see FOUNDATION, SHALLOW)
PILE FOUNDATIONS (see FOUNDATION, DEEP)
PIPES
Embedded in concrete 1906.3
Embedded in fire protection 704.8
Insulation covering 719.1, 719.7
Penetration protection 713, 1022.4
Under platform 410.4
PLAIN CONCRETE (see CONCRETE) 1909
PLAN REVIEW 107.3
PLASTER
Fire-resistance requirements 718
Gypsum 718.1, 718.2
Inspection 11 0.3.5
Portland cement 718.5,
Table 2507.2, Table 251 1.1.1
PLASTIC Chapter 26
Approval for use 2606.2
Core insulation, reflective plastic 2613
Fiber reinforced polymer 2612
Fiberglass-reinforced polymer 2612
Finish and trim, interior 2604
Light-transmitting panels 2401 .1 , 2607
Roof panels 2609
Signs 402.16,2611,
D102.2.10, H107.1.1
Thermal barrier 2603.4
Veneer 1404.8, 2605, D102.2.11
Walls, exterior 2603.4.1.4, 2603.5
PLASTIC, FOAM
Insulation (see FOAM PLASTICS) 2603
Interior finish 803.4, 2603.9
2010 CALIFORNIA BUILDING CODE
755
INDEX
Malls 402.11,402.12.1,402.16.5
Stages and platforms 410.3.6
PLASTIC, LIGHT-TRANSMITTING
Awnings and patio covers 2606.10
Bathroom accessories 2606.9
Exterior wall panels 2607
Fiber reinforced polymer 2612.5
Fiberglass-reinforced polymer 2612.5
Glazing 2608
Greenhouses 2606.11
Light-diffusing systems 2606.7
Roof panels 2609
Signs, interior 261 1
Skylight 2610
Solar collectors 2606.12
Structural requirements 2606.5
Unprotected openings 2608.1, 2608.2
Veneer, exterior 603.1(1 4), 603.1(1 6), 2605
Wall panels 2607
PLATFORM (see STAGES AND PLATFORMS). .410
Construction 410.4
Temporary 410.4.1
PLATFORM LIFTS, WHEELCHAIR
Accessible means of egress 1007.2, 1007.5,
1009.1,2702.2.6
Accessibility 1116B, 1120B.1
PLATFORM (WHEELCHAIR) LIFT . . 202, 1 107 A. 16-P
PLUMBING (see TOILET AND
TOILET ROOMS) 101.4.3, 105.2, Chapter 29
Aircraft hangars, residential 412.5.4
Facilities, minimum 2902, 3305.1
Fixtures Table 2902.1
Room requirements 1210, 2406.2,
2406.4, 2606.9, 2903
PLYWOOD
(see WOOD STRUCTURAL PANELS) 2302.1
Preservative-treated 2303.1 .8.1
POINT OF SALE MACHINES (ATM) 1117B.7
ATM equipment for persons with
vision impairments 1 117B.7.6
Clearances and reacli range 1117B.7.4
Wliere one ATMs is provided 1117B.7.4.1
Wtiere tfiree or more ATMs
are provided 1 117B.4.3
Wiiere two ATMs are provided. 111 7B. 7.4. 2
Controls 1117B.7.3
Display 1117B.7.5
General 1117B.7.2
POWDER ROOM (definition) 202,1 107A. 16-P
PRESCRIPTIVE FIRE RESISTANCE ... 720
PRESERVATIVE-TREATED WOOD . 2302.1
Fastenings 2304.9.5
Quality. 2303.1.8
Required 1403.5, 2304.1 1
Shakes, roof covering 1507.9.6, 1507.9.8
PRIMARY ENTRY ACCESS . . . . 1114B.1.3, 1133B.1.1
PRIMARY ENTRY LEVEL (definition) 202,
1107A.16-P
PROJECTION ROOMS
Motion picture 409
PROJECTIONS, COMBUSTIBLE .... 705.2.3, 1406.3
PROPERTY LINE (see FIRE
SEPARATION DISTANCE) 705.3
PROPERTY MAINTENANCE 101.4.4
PROSCENIUM
Opening protection 410.3.5
Wall 410.3.4
PUBLIC ACCOMODATION (definition) 202
PUBLIC ADDRESS SYSTEM
(see EMERGENCY COMMUNICATIONS)
Covered mall and open mall building 402.15,
907.2.20,2702.2.14
Special amusement buildings 411.6
PUBLIC ENTRANCE (definition) 202
PUBLIC PROPERTY Chapter 32, Chapter 33
PUBLIC RIGHT-OF-WAY
Encroachments Chapter 32
PUBLIC USE AREA (definition) .... 202, 1 107A. 16-P
PUBLICLY FUNDED (definition) 202
PYROPHORIC MATERIALS .... Table 307.1(1), 307.4
R
RAILING (see GUARDS or GUARDRAILS AND
HANDRAILS)
RAMPS 1010, 1133B.5
Assembly occupancy 1028.1 1
Construction 1010.2 through 1010.5.3,
1010.7, 1010.9
Definition 202, 1107A.18-R
Exterior 1026, 3201.4
Guide curbs & wiieel guide rails 1133B.5.6
Guards (or Guardrails) 1002.1, 1010.10, 1013,
7 7338.5.7,1607.7
Handrails 1002.1, 1010.8, 1012,
7 7338.5.5,1607.7
Landings 1010.6
Outdoor ramps 7 133B.5.8
Parking garage 406.2.5
Slope 1010.2, 1133B.5.3,
Width 1133B.5.2
REACH RANGES
(AND SPACE ALLOWANCE) 77738
Clear floor or ground space for wheelchairs . 1118B.4
Forward reach 7 7 736.5
Maneuvering clearances to wheelchair . . 11 18B.4(2)
Side reach 7 7 738.6
Size and approach 7 7 18B.4(1)
Surfaces for wheelchair spaces 7 7 18B.4(3)
Wheelchair passage width 7 7 738. 7
Wheelchair turning space 7 7 736.3
Width for wheelchair passage 7 7 736.2
756
2010 CALIFORNIA BUILDING CODE
INDEX
REFERENCED CODES 1.1.5
RECOMMEND (definition) 202
REFERENCED STANDARDS Chapter 35
Applicability 102.3, 102.4
Fire resistance 703.2
List Chapter 35
Organizations Chapter 35
REFORMATORIES 308.4
REFRIGERATION (see MECHANICAL) 101.4.2
Machinery roonn 1 01 5.4
REFUGE AREAS
(see HORIZONTAL EXIT, SMOKE
COMPARTMENTS, STORM SHELTERS). . . 407.4.1 ,
408.4.1, 408.6, 422.3, 423.1 .1, 1025.4
REFUSE CHUTE 708.13
REINFORCED CONCRETE (see CONCRETE)
General 1901.2
Inspections 1704.4
REINFORCEMENT
Concrete 1907, 1913.4, 1915.4
Masonry 2103.13
RELIGIOUS WORSHIP, PLACES OF
Balcony 1028.5
Classification 303, 305.1
Door operations 1008.1.9.3
Egress 1028
Fire alarm 907.2.1
Interior finishes Table 803.9, 804
Special occupancy separation . . 303.1, Table 508.2.5
Unlimited area 507.6, 507.7
REPAIRS, BUILDING 3405
Compliance alternatives. . . 3412.1, 3412.2.4, 3412.3
Flood 1612.1, 1612.2, 3405.5
Minor 105.2.2
Permit required 105.1
Scope 1.1.1, 101.2,1613.3,3401.1,
3401.3,3409.1
RESIDENTIAL CARE/ASSISTED
LIVING FACILITIES 308.1
Fire alarms 907.2.6, 907.5.2.3.3
Separations Table 508.2.5, Table 508.4
Smoke alarms 907.2.1 1 .2
Sprinklers 903.2.6, 903.3.2
RESIDENTIAL HOTELS (maii receptacles) 424
RESIDENTIAL
OCCUPANCY (GROUP R) 310, 1111B
Access to beds Ill 1B.4.3
Accessibility Chapter 11A,111 IB. 1
Accessible route
(Guest rooms & suites) Chapter 1 1 A,
1111B.4.2.2
Accessory 508.2, G801 .1
Alterations in existing facilities Chapter 1 1A,
1111B.4.2.4
Area 503, 505, 506, 507, 508
Available range of accommodations 1111B.4.1
Bathrooms in hotels, motels, inns, dormitories,
resorts, homeless shelters, halfway houses,
transient group homes and similar places of
transient lodging Ill 1B.4.6
Buildings and complexes containing
publicly funded dwelling units 1111B.5
Carbon monoxide alarms 420.4
Corridors 1018.1, 1018.2
Doors 1008.1.1, 1111B.4.2.3
Dormitory rooms Ill 1B.4.8
Draftstopping 71 7.3.2, 71 7.4.2
Emergency escape and rescue 1029.1
Exit sign exemptions 101 1 .1
Fire alarm and detection 907.2.8,
907.2.9,907.2.10
Group R-1 310.1
Group R-2 . .310.1
Group R-2.1 310. 1
Group R-3 310.1
Group R-3.1 310.1
Group R-4 310.1, 1008.1.9.5.1
Guest rooms and suites Ill 1B.4.2
Height 503, 504, 505, 506, 508, 509
Hotels, motels, inns, dormitories,
resorts, homeless shelters, halfway
houses, transient group homes
and similar places of transient lodging . . . 1111B.4
Interior finishes Table 803.9, 804
Kitchens, kitchenettes or
wet bar facilities Ill 1B.4.4
Live load Table 1607.1
Parking, private 406.1
Parking beneath or above 509
Partitions 420, 709.1
Plumbing fixtures 2902
Public and common use rooms or areas. ... Ill 1B.2
Recreational facilities Ill 1B.3
Smoke alarms 907.2.1 1
Spaces (in Guest rooms & suites) Ill 1B.4.2. 1
Special occupancy separation. ... 419, 420, 508.2.4,
Table 508.2.5, 508.3.3
Special provisions 509.5, 509.6
Sprinklers 903.2.8, 903.3.2
Storage areas Ill 1B.4.7
Swimming pools 3109.4, Chapter 31 B
Telephones Ill 1B.4.5.3
Travel distance 1014.3, 1016.1, 1021.2
Visible alarms 420.4.4, 907.5.2.3.3,
907.5.2.3.4, 1111B.4.5.1
RESTRICTED ENTRANCE (definition) 202
RETAINING WALLS 1807.2, 2304.11.7
Flood provisions G801 .4
Seismic 1803.5.12
REVIEWING STANDS (see BLEACHERS AND
GRANDSTANDS) 1028.1.1
Live load Table 1607.1
RISER (definition) 202, 1107A.18'R
2010 CALIFORNIA BUILDING CODE
757
INDEX
RISERS, STAIR (see STAIRWAY CONSTRUCTION)
Aisle stairways 1028. 1 1.2
Alternating tread device 1009.10,1009.10.2
Assembly 1028.5.1, 1028.6,
1028.7, 1028.9,1028.11
Closed 1009.4.5
Curved stairways 1009.8
Dimension reference surface 1009.4. 1
Dimensional uniformity 1009.4.4
Existing stain/vays replacement 3403. 1 (Exc. 2),
1134B
General 1009.4
Group 1-3 1009.4.2 Exc. 7
Group R-3 1009.4.2 Exc. 5
Handrails 1009.10, 1133BA.1
Nonuniform riser dimensions
of aisle stairs 1028. 1 1.2
Profile 1009.4.5
Riser height and tread depth 1009.4.2
Ships ladders 1009. 1 1
Spiral 1009.9
Spiral stains/ays 1009.9
Spiral stairways 1009.9
Stair treads and risers . . . 1009.4, 1009.4.1, 1009.4.5
Uniformity 1009.4.4
Winder treads 1009.4.3
Winders, consistently shaped 1009.4.2
RODENTPROOFING Appendix F
ROLL ROOFING 1507.6
ROOF ACCESS .
1009.13,1009.14
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
Cooling towers '. 1509.4
Drainage 1503.4, 3201 .4
Fire classification .1505
Fire district D1 02.2.9
Height modifications 504.3
Impact resistance 1504.7
Materials 1506
Parapet walls 1503.3, 1503.6
Penthouses 1509.2
Tanks 1509.3
Towers, spires, domes and cupolas 1509.5
Weather protection 1503
Wind resistance 1504.1, 1609.5
ROOF CONSTRUCTION
Construction walkways 3306.7
Coverings (see ROOF COVERINGS) 1609.5.2
Deck 1609.5.1
Draftstopping 717.4
Fire resistance Table 601
Fireblocking 717.2
Live loads Table 1607.1, 1607.11
Materials Chapter 6
Penetration of fire resistant assemblies 713
Protection from adjacent construction 3307.1
Rain loads 1611
Roof structures 504.3, 1509, D1 02.2.9
Signs, roof mounted H1 10
Slope, minimum Chapter 15
Snow load 1608
Trusses 2210.3, 2303.4, 2308.10.10
Wood (see ROOF CONSTRUCTION, WOOD)
ROOF CONSTRUCTION, WOOD .... 602.4.3, 602.4.5
Anchorage to walls 1604.8.2
Attic access 1209.2
Ceiling joists 2308.10.2
Diaphragms 2305.1 , 2306.2
Fastening schedule 2304.9
FIre-retardant-treated Table 601, 603.1(25)
Framing 2304.10.3, 2308.10
Rafters 2306.1.1
Sheathing 2304.7, 2308.10.8
Trusses 2303.4, 2308.10.10
Ventilation, attic 1203.2
Wind uplift . .2308.10.1
ROOF COVERINGS 1507
Asphalt shingles 1507.2
Built up 1507.10
Clay tile 1507.3
Concrete tile 1507.3
Fire district D102.2.4
Fire resistance 603.1(3), 1505
Flashing 1503.2, 1503.6, 1507.2.9,
1507.3.9, 1507.5.7,1507.7.7,
1507.8.8,1507.9.9,1510.6
Impact resistance 1504.7
Insulation 1508
Liquid applied coating 1507.15
Membrane 3102
Metal panels 1507.4
Metal shingles 1507.5
Modified bitumen 1507.1 1
Plastics, light-transmitting panels 2609
Replacement/recovering .1510.3
Reroofing 1510
Roll 1507.6
Single-ply 1507.12
Slate shingles 1507.7
Sprayed polyurethane foam 1507.14
Thermoplastic single-ply 1507.13
Wind loads 1504.1, 1609.5
Wood shakes 1507.9
Wood shingles 1507.8
ROOF DRAINAGE 1503.4
ROOF REPLACEMENT/RECOVERING. ...... 1510.3
ROOF STRUCTURE (see ROOF ASSEMBLIES
AND ROOFTOP STRUCTURES)
ROOM DIMENSIONS 1208
ROOMING HOUSE 310
ROUTE OF TRAVEL (ACCESSIBLE) 11 14B. 1.2,
1102B, 1114B, 1124B, 1133B.3, 1133B.5, 1133B.7
s
SAFEGUARDS DURING
CONSTRUCTION Chapter 33
Adjoining property protection 3307
Construction 3302
758
2010 CALIFORNIA BUILDING CODE
INDEX
Demolition 3303
Evacuations 1804.1
Fire extinguishers 3309
Means of egress 331
Protection of pedestrians 3306
Sanitary facilities 3305
Site work 3304
Sprinkler system, automatic 3312
Standpipes 3308.1 .1 , 331 1
Temporary use of streets, alleys
and public property 3308
Walkways 3306.2, Chapter 1 1B
SANITARY FACILITIES (see BATHING AND TOILET
FACILITIES (Sanitary Facilities)
SAFETY GLAZING 71 5.4.7.4, 2406
SANITARY FACILITY
Definition 202
SCHOOLS (see EDUCATIONAL OCCUPANCY)
SCOPE (Accessibility)
Buildings or facilities (or portions of) 11018.1(1)
Commercial facilities located in
private residences 1 1018.6
Construction and manufacturing
Tolerances 1 1018.5
Design 1 1018.2
Dimension conventions 11018.4
Equivalent facilitation (Determining) 11018.1(3)
Maintenance (of Accessible features) 11018.3
Provisions for adults 1 1018.7
Tecfinical & scoping (Departures from) . . 11018.1(2)
DSA-AC 1.9.1.5, 11018
SEATING, FIXED OR BUILTIN 1028, 11228
Accessibility 11048.3.1, 11228
Aisles 1017.4, 1028.9
Bleachers (see BLEACHERS)
Grandstands (see GRANDSTANDS)
Height of work surfaces 1 1228.4
Knee clearance 1 1228.3
Live load Table 1607.1
Minimum number (Accessible) 1 1228. 1
Occupant load 1004.7
Sales and service counters, teller
windows, and information counters 11228.5
Temporary 108
Tables, counters, seating
(Fixed or 8uilt-in) 11228
Seating 1 1228.2
SECURITY GLAZING 408.7
SECURITY GRILLES 1008.1.4.5
SEISMIC 1613
Construction documents 107, 1603.1.5,
1603.1.9, 1709
Existing building 3403.4.1 , 3404.4.1 ,
3404.5, 3405.2, 3408.4
Fire-resistance 704.12
Geotechnical investigation 1803.5.11, 1803.5.12
Glazing 2404
Loads 1613
Masonry 2106
Membrane structure 3102.7
Seismic design category 1613.2, 1613.5.6
Seismic detailing 1604.10
Site class 1613.2. 1613.5.2, 1613.5.5
Site classification for seismic design 1613.5.5
Site coefficients 1613.2, 1613.5.3
Statement of special inspections 1705.3
Steel 2205
Structural observations 1707, 1710
Structural testing 1708
Wood 2305, 2308.11, 2308.12
SERVICE STATION
(see MOTOR FUEL-DISPENSING FACILITIES)
SHAFT (see SHAFT ENCLOSURE
AND VERTICAL OPENING PROTECTION) .... 702
SHAFT ENCLOSURE (see VERTICAL
OPENING PROTECTION) 708
Continuity 708.5, 708.1 1 , 708.12
Elevators 708.14
Exceptions 708.2, 1016.1, 1022.1
Exterior walls 708.6
Fire-resistance rating 707.3.1 , 708.4
Group 1-3 408.5
High-rise buildings 403.2.1 .2, 403.2.3,
403.3.1.1,403.5.1
Joints 708.9, 714
Materials 708.3
Opening protection 708.8, 708.10, 713, 716.5.3
Penetrations 708.8
Refuse and laundry chutes 708.13
Required 708.2
SHEAR WALL
Gypsum board and plaster 2505
Masonry 2102.1
Wood 2302.1 , 2305.1 , 2306.3 through 2306.7
SHEATHING
Clearance from earth 2304.1 1 .2.2
Fastening 2304.9
Fiberboard 2306.6
Floor 2304.7, 2308.8.6
Gypsum 2306.2.4
Moisture protection 2304.1 1 .2.2
Particleboard 2306.5
Roof 2304.7
Roof sheathing 2308.10.8
Wall 2304.6.1, 2308.9.3
Wood structural panels 2303.1 .4, 221 1 .3
SHOPPING CENTER (or SHOPPING MALL)
(definition) 202
SHOPPING CENTERS 309
SHOULD 202
SHOTCRETE 1913
SHUTTERS, FIRE
(see OPENING PROTECTEES) 715.4
2010 CALIFORNIA BUILDING CODE
759
INDEX
SIDEWALKS 05.2(6), G801.4 1133B.7
Definition 202, 1107A.23-W
Live loads Table 1 607.1
SIGNS AND IDENTinCATION 1114B.1.4,
77778.5, 3107, Appendix H
Accessibility 1011.3, 1143A
Accessibility signs 7 117B.5. 1(3)
Accessible means of egress 7002.7,1007.8.2,
1007.9 through 1007.11
Animated devices HI 08
Braille 1117B.5.6
Character heiglit 1117B.5.4
Cleaner air symbol 7 117B.5. 1 1
Construction H105, H107
Covered mall and open mall building 402.16
Directional and informational signs .... 1117B.5.1(2)
Doors 1008.1.4.4, 1008.1.9.3, 1008.1.9.7
Electrical H106
Elevators 1 124A, 3002.3, 3008.1 1 .5
Encroachment, public right-of-way 3202.3.1
Exit 1011, 2702.2.3, 2702.2.9
Finish and contrast 7 117B.5.2)
Floor loads 106.1
General 1117B.5.1
Ground H109
Height limitation H109.1, H112.4
Identification signs 7 117B.5.1(1)
Illumination H106.1
Luminous 403.5.5, 1011.4, 1024
Marquee H1 13
Mounting location and height 1117B.5.7
Obstruction 1003.3.2, 1003.3.3, H103
Occupant load, assembly 1004.3
Parking spaces 1 109A.8.8
Plan review and inspection 7 117B.5. 1(4)
Plastic 2611, D102.2.10
Portable H1 14
Projecting H1 12
Proportions 7 117B.5.3
Protruding objects 1003.3, Chapter 1 1 B
Raised characters and pictorial
symbol signs 7 117B.5.5
Roof H110
Signs for text telephones 7 117B.5. 10
Stair identification . . . 1022.7, 1022.8, 1110.2, 1110.3
Standpipe control valve 905.7.1
Symbols of accessibility 1117B.5.8
International symbol of accessibility . . 1117B.5.8.1
International TTY symbol 1117B.5.8.2
Volume control telephone 1117B.5.8.3
Assistive listening systems 1117B.5.8.4
Traffic control devices 7 7 17B.5.9
Walls 703.6, Hill
SINGLE-ACCOMODATiON SANITARY
FACILITY (definition) 202
SINKS (ACCESSIBLE) 77776.9
SITE (definition) 202
SITE ACCESSIBILITY (Div II) 1127B—1132B.3.1
Accessible parking required 7 129B
Exterior routes of travel 7727S
Outdoor occupancies 7 132B
Parking structures 7 730S
Passenger drop-off and loading zones 7 737S
Pedestrian grade separation
(Overpasses/underpasses) 7 128B
SITE DEVELOPMENT (definition) 202
SITE DRAWINGS 107.2.5
SITE WORK 3304
SKILLED NURSING AND INTERMEDIATE-CARE
FACILITIES-GENERAL REQUIREMENTS
Activity programming space 1225.7
Application 1224.2
Dietetic service space 1225.5
General construction 1224.3
Nursing service space 1225.4
Pharmaceutical service space 1225.6
Scope 1225. 1
SKILLED NURSING AND INTERMEDIATE-CARE
FACILITIES-OPTIONAL SERVICES
General 1225, 14
Occupational Therapy Space 1225. 16
Physical Therapy Space 1225. 15
Social Work Service 1225. 18
Special Treatment Program Space 1225. 19
Speech Pathology and/or
Audiology Service 1225.17
SKILLED NURSING AND INTERMEDIATE-CARE
FACILITIES-SUPPORT SERVICES
Administration Space 1225.8
Employee Dressing Rooms and Lockers . . . 1225. 1 1
Laundry 1225. 13
Housekeeping Rooms 1225. 12
Sterile Supplies 1225.9
Storage 1225. 10
SKYLIGHTS 2405, 3106.3
Light, required 1205.2
Loads 2404
Plastic 2610
Protection from adjacent construction 3307.1
SLAB, COMPOSITE
STEEL DECK/CONCRETE 2209.2.1
SLAB ON GROUND, CONCRETE. .1910, 2304.11.2.3
SLATE SHINGLES 1507.7
SLEEPING ACCOMODATIONS (definition) 202,
1107A19-S
SLEEPING UNITS 202
Group 308
Group R 310
Scoping 101.2
Separation 420.2, 420.3
SLOPE (definition) 202, 1107A.19-S
SMOKE ALARMS
Live/work unit 907.2.1 1 .2
Multiple-station 907.2.1 1
Residential aircraft hangars 412.5.3,
412.5.4,907.2.21
Residential occupancies 907.2.1 1 .1 , 907.2.1 1 .2
760
2010 CALIFORNIA BUILDING CODE
INDEX
Single-Station 907.2.1 1
SMOKE BARRIERS 710
Ambulatory care facilities 422.2
Construction 407.4.3, 710.4, 909.5
Doors 710.5, 715.4.3, 909.5.2
Fire-resistance rating 703, 710.3
Glazing, rated 715.5
Horizontal assemblies 712.9
Inspection 11 0.3.6
Joints 710.7,714
Marking 703.6
Materials 71 0.2
Opening protection 710.5, 713.3, 713.5,
715,716.5.5,909.5.2
Penetrations 710.6, 713
Smoke control 909.5
Special provisions
Ambulatory care facilities 422
Group 1-2 407.4
Group 1-3 408.6, 408.7
Underground 405.4.2, 405.4.3
SMOKE COMPARTMENT 407, 408, 422
Refuge area (see REFUGE AREA)
SMOKE CONTROL 909
Amusement buildings, special 41 1 .1
Atrium buildings 404.5
Covered mall and open mall building 402.10
Group 1-3 408.9
High-rise 403.4.6, 403.5.4, 1022.9
Special inspections 1704.16
Stages 410.3.7.2
Standby power systems 909.20.6.2, 2702.2.2
Systems 909
Underground buildings 405.5
Values 3412.6.10.1
SMOKE DAMPERS 716.2 through 71 6.5
SMOKE DETECTION SYSTEM (see FIRE ALARM
AND SMOKE DETECTION SYSTEMS) 907
SMOKE DETECTORS
Covered mall and open mall 402.4.5.1, 907.2.20
High-rise buildings 403.4.1, 907.2.13
HPM 415.8.9.3
Institutional 1-2 407.7
Smoke activated doors 71 5.4.8.3
Special amusement buildings 41 1 .5
Underground buildings 907.2.18, 907.2.19
SMOKE-DEVELOPEMENT 802,
803.1.1, Table 803.9
SMOKE EXHAUST SYSTEMS
Underground buildings 405.5, 907.2.18, 909.2
SMOKE PARTITIONS 711
Continuity. 71 1 .4
Doors 711.5
Ducts and air transfer openings 71 1 .7
Fire- resistance rating 71 1 .3
Inspection 1 10.3.6
Joints 711.6
Marking 703.6
Materials 71 1 .2
Opening protection 71 1 .5, 716.5.7
Penetrations 711.6
Special provisions
Atriums 404.6
Group 1-2 407.3
SMOKE REMOVAL 403.4.6
SMOKE VENTS 410.3.7.1, 910
SMOKEPROOF ENCLOSURES 403.5.4, 1022.9
Design 909.20
SNOW LOAD 1608
Glazing 2404
SOILS AND FOUNDATIONS
(see FOUNDATION) Chapter 18
Depth of footings 1809.4
Excavation, grading and fill 1804, 3304,
J106, J107
Expansive 1803.5.3, 1808.6
Flood hazard 1 808.4
Footings and foundations 1808
Footings on or adjacent to slopes . . 1808.7, 3304.1 .3
Foundation walls 1807.1.5, 3304.1.4
Geotechnical investigation 1803
Grading 1804.3, Appendix J
Loadbearing values 1806
Soil boring and sampling 1803.4
Soil lateral load 1610
Special inspection 1704.7
SORORITIES 310.1
SOUND-INSULATING MATERIALS
(see INSULATION) 719
SOUND TRANSMISSION 1207
SPACE (definition) 202
SPACE ALLOWANCE AND
REACH RANGES 1118B
Clear floor or ground space for wheelchairs . 1118B.4
Forward reach 11 18B.5
Maneuvering clearances to wheelchair . . 11 188.4(2)
Side reach 11 18B.6
Size and approach 11 188.4(1)
Surfaces for wheelchair spaces 11188.4(3)
Wheelchair passage width 11 188. 1
Wheelchair turning space 11 188.3
Width for wheelchair passing 11 188.2
SPECIAL CONSTRUCTION Chapter 31
Automatic vehicular gates 31 10
Awnings and canopies
(see AWNINGS and CANOPIES) 3105
Marquees (see MARQUEE) 3106
Membrane structures
(see MEMBRANE STRUCTURES) 3102
Pedestrian walkways and tunnels
(see WALKWAYS and
TUNNELED WALKWAYS) 3104
Signs (see SIGNS) 3107
Swimming pools enclosures and
safety devices (see SWIMMING POOL) 3109
Telecommunication and broadcast towers
(see TOWERS) 3108
2010 CALIFORNIA BUILDING CODE
761
INDEX
Temporary structures
(see TEMPORARY STRUCTURES) 3103
SPECIAL CONSTRUCTION
Separate structures 3104.2 (Exc. 2)
SPECIAL INSPECTIONS
(see INSPECTIONS and STRUCTURAL
TESTS AND SPECIAL INSPECTIONS)
SPECIAL STANDARDS OF ACCESSIBILITY FOR
BUILDINGS WITH HISTORICAL
SIGNIFICANCE 1119B
SPIRAL STAIRS 1009.9
Construction 1009.1, 1009.2, 1009.9
Exceptions. . . 1009.4.2, 1009.4.3, 1009.4.5, 1009.12
Group 1-3 408.3.4
Live/work 419.3.3
Stages 410.5.3, 1015.6.1
SPRAY-APPLIED FIRE RESISTANT
MATERIALS 1702.1
Inspection 1704.12, 1704.13
Steel column calculated fire resistance 721 .5.2.2
SPRINKLER SYSTEMS, AUTOMATIC 903, 3312
Exempt locations 903.3.1 .1 .1
Fire department location 912
Seismic design 161 3.6.3
Signs 914.2
Substitute for fire rating Table 601 (4)
Values 3412.6.17
SPRINKLERS, REQUIRED 903
Aircraft related 412.4.6, 412.6.5
Ambulatory health care facilities 422.5, 903.2.2
Amusement buildings, special 41 1 .4
Area increase 506.3
Assembly 903.2.1, 903.2.11.5, 1028.6.2.3
Atrium building 404.3
Basements 903.2.11.1
Combustible storage 413
Construction 903.2.12
Covered mall and open mall building 402.9
Drying rooms 417.4
Education 903.2.3
Exempt locations 903.3.1 .1 .1
Factory 903.2.4
Fire areas 707.3.9
Garages 406.3.10, 903.2.9.1, 903.2.10.1
Hazardous materials Table 414.2.5(1),
Table 414.2.5(2), 903.2.11.4
Hazardous occupancies 415.5.2, 415.6.2.4,
415.8.6.3, 415.8.11, 705.8.1, 903.2.5
Height increase 504.2
High-rise buildings 403.2, 403.3, 903.2.11.3
Incidental accessory occupancies .... Table 508.2.5
Institutional 407.5, 903.2.6, 903.3.2
Laundry chutes, refuse chutes,
termination rooms and
incinerator rooms 708.13, 903.2.1 1 .2
Live/work units 419.5, 903.2.8
Mercantile 903.2.7
Mezzanines 505.4, 505.5.2
Multistory buildings 903.2.1 1 .3
Residential 903.2.8, 903.3.2
Special amusement buildings 41 1.4
Spray finishing booth 416.5
Stages 410.6
Storage 903.2.9, 903.2.10
Supervision
(see SPRINKLERS, SUPERVISION). ...... 903.4
Underground buildings 405.3, 903.2.11.1
Unlimited area 507
SPRINKLERS, SUPERVISION 903.4
Service 901 .6
Underground buildings 405.3
STAGES AND PLATFORMS 303, 410
Dressing rooms 41 0.5
Egress 410.5.3, 1015.6
Fire barrier wall 410.5.1, 410.5.2
Floor finish and floor covering 410.3, 410.4,
804.4, 805.1
Horizontal assembly 410.5.1, 410.5.2
Platform, temporary 410.4.1
Platform construction 410.4, 603.1(1 1)
Proscenium curtain 410.3.5
Proscenium wall 410.3.4
Roof vents . 410.3.7.1
Scenery 410.3.6
Smoke control 410.3.7.2
Sprinkler system 41 0.6
Stage construction 410.3, 603.1(11)
Standpipes 410.7, 905.3.4
Ventilation 410.3.7
Wheelchair (Platform lifts) 1116B.2
STAIRWAY (see ALTERNATING TREAD DEVICES,
SPIRAL STAIRS, STAIRWAY CONSTRUCTION and
STAIRWAY ENCLOSURE)
STAIRWAY CONSTRUCTION
Aisle 1028.9
Alterations 3404.1
Alternating tread 1009.10
Circular (see Curved)
Construction 1009.6
Curved 1009.3, 1009.8
Discharge barrier 1022.7
During construction 3310.1
Elevators 1009.14, 1022.3, 3002.7
Enclosure under 1009.6.3
Existing 3404.1 , 3408.3
Exterior exitway 1026.1 , 1027.1
Fireblocking 717.2.4
G\jar6s(or Guardrails) 7002.7,1013.1,
1013.2,1607.7
Handrails 10021, 1009.12,
1012, 7 7338.4, 1607.7
Headroom 1 009.2
Illumination 1006.1, 1205.4, 1205.5
Ladders 1009.11
Landings 1009.5, 1009.7
Live load Table 1607.1, 1607.7
762
2010 CALIFORNIA BUILDING CODE
INDEX
Luminous 403.5.5,411.7.1, 1024
Nosing 1133B.4.5
Roof access 1009.13, 1009.14
Seismic anchorage 2308.12.7
Spiral (see SPIRAL STAIRS) 408.3.4,
410.5.3,419.3.3, 1009.9
Striping for the visually impaired 1133B.4.4
Tactile floor designation signs 1133B.4.3
Treads and risers 1009.3, 1009.4
Width 1009.1
Winders 1009.3, 1009.4.2,
1009.4.3, 1009.4.4, 1009.8
STAIRWAY ENCLOSURE 708.2, 1022.1
Access. . 1022.1.9.2
Construction 1022.4
Discharge 1027.1
Doors 715.4.8, 1008.1.9.10
Elevators within 1022.3, 3002.7
Exterior walls 705.2, 707.4, 708.6,
709.5,1022,1026.6
Fire-resistant construction 1022.1
Group 1-3 408.3.8
High-rise 403.5
Penetrations 1022.4
Pressurization 909.6, 909.20.5
Space below, use 1009.6.3
Ventilation 1022.5
STANDARDS (see REFERENCED STANDARDS)
STANDBY POWER 2702.1 , 2702.3
Aircraft traffic control towers 412.3.5, 2702.2.18
Atriums 404.7, 2702.2.2
Covered mall and open mall building 402.14,
2702.2.14
Elevators. 1007.4, 2702.2.5, 2702.2.19,
3003.1,3007.7,3008.15
Hazardous occupancy 414.5.4, 421 .8,
2702.2.10,2702.2.12
High-rise 403.4.7, 2702.2.15
Horizontal sliding doors 1008.1.4.3, 2702.2.7
Membrane structures 2702.2.9, 3102.8.2
Platform lifts 1007.5, 2702.2.6
Smoke control 909.1 1 , 2702.2.2
Smokeproof enclosure 909.20.6.2, 2702.2.20
Underground buildings 405.8, 2702.2.16
STANDPIPE AND HOSE SYSTEMS
(see STANDPIPES, REQUIRED) 905, 3106.4,
3308.1.1,3311
Cabinet locks 905.7.2
Dry 905.8
Hose connection location 905.1 ,
905.4 through 905.6, 912
STANDPIPES, REQUIRED
Assembly 905.3.2, 905.5.1
Covered mall and open mall buildings 402.9.1,
905.3.3
During construction 905.10
Elevators, fire service access 3007.5
Helistops . .905.3.6
Marinas 905.3.7
Parking garages 406.3.6, 406.3.9
Stages 410.7, 905.3.4
Underground buildings 405.10, 905.3.5
STATE LAW 102.2
STATE-REGULATED BUILDINGS,
STRUCTURES AND APPLICATIONS 1.1.3.2
STEEL Chapter 22
Bolting 2204.2
Cable structures 2207
Calculated fire resistance 721 .5
Cold-formed. 2202.1 , 2209, 2210
Conditions of restraint 703.2.3
Decks 2209.2
Identification and protection 2203
Joists 2202.1, 2206
Open web joist 2206
Parapet walls 1503.3, 1503.6
Reinforcement, concrete 1907
Seismic provisions 2205
Special inspections 1704.3
Storage racks 2208
Welding 2204.1
STONE VENEER 1405.7
Slab-type 1405.8
STOP WORK ORDERS 115
STORAGE 1125B
Clear floor space 1 125B.2
General 1 125B. 1
Hardware 1 125B.4
Height 1125B.3
STORAGE OCCUPANCY (GROUP S) 311
Accessory 508.2
Area 406.3.5, 406.3.6,
406.4.1, 503, 505, 506, 507, 508
Automobile parking garage 406
Hazard storage, low. Group S-2 31 1 .3
Hazard storage, moderate. Group S-1 311.2
Height 406.3.5, 406.4.1, 503,
504, 505, 506, 508, 509
High-piled combustible 413
Interior finishes. Table 803.9, 804
Live loads Table 1607.1
Parking garages 406.1 , 406.2, 406.3, 406.4
Plumbing fixtures 2902
Smoke and heat vents 910.2
Special occupancy separation . . 309.1 , Table 508.2.5
Sprinkler system, automatic 903.2.10
Travel distance 1014.3, 1016.1, 1021.2
Unlimited area 507.2, 507.3, 507.4
STORM SHELTER 423
Refuge area (see REFUGE AREA)
STRENGTH
Design requirements 1604.2
Masonry 2102.1
Nominal 1602.1
Required 1602.1
2010 CALIFORNIA BUILDING CODE
763
INDEX
STRENGTH DESIGN 1602.1, 1604.1
Masonry 2101.2.2, 2108
STRUCTURAL DESIGN Chapter 16
Aluminum Chapter 20
Concrete Chapter 1 9
Foundations Chapter 18
Grab bars 1607.7.2, 1607A.7.2
Loads on handrails 1607.7, 1607A.7
Masonry Chapter 21
Steel Chapter 22
Wood Chapter 23
STRUCTURAL TESTS AND SPECIAL
INSPECTIONS (see INSPECTIONS
AND TESTING) 110.3.9,
Chapter 17
Alternative test procedure 1712
Approvals 1 703
Contractor responsibilities 1709
Design strengths of materials 171 1
General 1701
In-situ load tests 1714
Material and test standards 1716
Preconstruction load tests 1715
Special inspections 1704, 1706, 1707
Statement of special inspections 1705
Structural observations 1710
Structural testing 1708
Test safe load 1713
STRUCTURAL OBSERVATION 1702.1, 1710
STUCCO 2512
SWIMMING POOL 3109, 1117B.4, 1104B.4.3
Deck mechanism for accessibility . . 31 13B. 1(Exc. 4),
11048.4.3
Flood provisions G801 .5
Gates, access 3109.4.1.7
Glass 406.4
Participation areas 1 104B.4.3, 31 13B. 1 (Exc .4)
Indoor 3109.4.2
Public 3109.3, Chapter31B
Residential 3109.4
TACTILE (definition) 202
TELEPHONES
Clear floor or ground space 1117B.2.2
Controls (push-button) 1 117B.2. 10
Cord length 1117B.2.11
Enclosures 11 17B.2.7
Equipment for hearing impaired 1117B.2.8
Floor surfaces of wheelchair spaces 1117B.2.5
Maneuvering clearances 11 17B.2.4
Mounting height 11 17B.2.6
Signage (Text telephones) / 117B.2.9.3
Size and approach / 117B.2.3
Telephone books 1 117B.2. 12
Text telephones 1 117B.2.9
TELEPHONE EXCHANGES 304
TELESCOPIC SEATING (see FOLDING AND
TELESCOPIC SEATING)
TEMPORARY STRUCTURES 3103
Certificate of occupancy 108.3
Conformance 108.2
Construction documents 3103.2
Encroachment, public right-of-ways 3202.3
Flood provisions G901
Means of egress 31 03.4
Permit. 108.1,3103.1.1
Power, temporary 108.3
Termination of approval 108.4
TENANT SEPARATION
Covered mall buildings 402.7, 709.1
TENTS
Standby and emergency power 2702.2.9
TERMITES, PROTECTION FROM 2304.1 1
TERRA COTTA 1405.9
TESTING
Building official required 104.11.1
Concrete 1905.6
Fire-resistant materials 703.2
Glazing 2406, 2408.2.1
Roof tile 1716.2
Seismic 1708
Smoke control 909.3
Soils 1803
Sprinklers 904.4
Structural (see STRUCTURAL TESTS AND
SPECIAL INSPECTIONS)
TESTING AGENCY (definition) 202
THEATERS [see ASSEMBLY OCCUPANCY
(GROUP A, PROJECTION ROOMS and
STAGES AND PLATFORMS)] 303, 1 1 16B.2
THERMAL BARRIER,
FOAM PLASTIC INSULATION .... 2603.4, 2603.5.2
THERMAL-INSULATING MATERIALS
(see INSULATION) 719
TILE 2102.1
Ceramic (see CERAMIC TILE)
Fire resistance, clay or shale 720.1
TOILET FACILITIES (see BATHING AND TOILET
FACILITIES)
TOILETS and TOILET ROOMS Chapter 1 1B,
Chapter 29, 3305
Accessible 1127A, 1134A, 1115B, 1607.7.2
Construction/materials 1210, 2903
Family- or assisted-use 2902.1.2, 2902.2
Grab bars 1127A.4, 1607.7.2
Location 2902.3.2, 2902.3.3, 2902.3.4
Partitions .2903
Public facilities 2902.3
Rooms openings 1210.5
764
2010 CALIFORNIA BUILDING CODE
INDEX
Signs 1127A.7
Unisex 1 127A.7.2.3
Ventilation 1203.4.3
TORNADO SHELTER (see STORM SHELTER)
TOWERS
Airport traffic control 412.3
Cooling. 1509.4
Location and access 3108.2
Radio 3108
Television 31 08
TOXIC MATERIALS [see HIGH-HAZARD
OCCUPANCY (GROUP H)]
Classification 307.6, 414, 415
Gas detection system 415.8.7, 421.6, 908.3
TRANSIENT LODGING
(definition) 202, 1 107A.20-T
TRANSPORTATION FACILITIES 1 121 B
Airports 1 121B.4
Bus stop sitting/alterations 1 121B.2.2
Bus stops/terminals 1 121B.2
Existing faciiities (Alterations) 1 120B.3.2
Fixed facilities/stations 1 121B.3
General 1121B.1
New construction (Airports) 1 121B.4. 1
New construction
(Bus stops/terminals) 1 121B.2. 1
New construction
(Fixed facilities/stations) 1 121B.3. 1
TRAVEL DISTANCE
Area of refuge 1 007.6
Assennbly seating 1028.7
Atrium 404.9
Balcony, exterior 1016.2
Common path of travel 1014.3
Mall 402.4.2, 402.4.4
Measurement 1016.1
Refrigeration machinery/
refrigerated rooms 1015.4, 1015.5
Smoke compartments (Group 1-2 and 1-3) .... 407.4,
408.6.1,408.8.1
Special amusement building 41 1 .4
Stories with one exit 1021 .2
Suites (Group 1-2) 1014.2.3.3, 101
4.2.4.3,1014.2.4.4, 1014.2.6
TREAD (definition) 202,1 107A.20-T
TREAD DEPTH (definition) 1 107A.20'T
TREAD RUN (definition) 1107A20'T
TREADS, STAIR (see STAIRWAY
CONSTRUCTION)
Concentrated live load Table 1607.1
TREATED WOOD 2302.1
Fire-Retardant treated wood 2303.2
Pressure-treated wood 2303.1 .8
Stress adjustments 2306.1 .3
TRUSSES
Cold-formed steel 2210.3
Fire Resistance 704.5
Materials Chapter 6
Metal-plate-connected wood 2303.4.6
Wood 2303.4
TUNNELED WALKWAY 3104, 3202.1
TURNSTILES 1008.3
u
UNDERGROUND BUILDINGS 405
Compartmentation 405.4
Construction type 405.2
Elevators 405.4.3
Emergency power loads 405.10, 2702.2.16
Exits 405.8
Fire alarm system 405.6
Smoke barrier 405.4.2, 405.4.3
Smoke exhaust/control 405.5
Smokeproof enclosure 405.7.2, 1022.9
Sprinkler system 405.3
Standby power 405.8, 2702.2.16
Standpipe system 405.1 1 , 905.3.5
UNLIMITED AREA BUILDINGS 507
UNSAFE STRUCTURES AND EQUIPMENT
(see STRUCTURES, UNSAFE) 115
Appeals 113, Appendix B
Restoration 1 15.5
Revocation of permit 105.6
Stop work orders 115
Utilities disconnection 1 12.3
UNSTABLE MATERIALS .... 307.3, Table 414.2.5(1),
Table 414.5.1, Table 415.3.2,
415.5.1,415.8
UNUSABLE SPACE 712.3.3
USE AND OCCUPANCY Chapter 3
Accessory 508.2
Incidental accessory occupancy 508.2.5,
Table 508.2.5
Mixed 508.3, 508.4
USE AND OCCUPANCY CLASSIFICATIONS
Assembly 302.1(1), 303, 1104B
Business 302.1(2), 304, 1105B
Classification 307.6, 414, 415
Educational 302.1(3), 305, 1106B
Factory and Industrial 302.1(4), 306
High Hazard 302.1(5), 307, 1108B
Institutional 302. 1(6), 308, 1 109B
Laboratory 202, 302. 1(7), 443, 307, 1 106B.2
Mercantile 302.1(8), 309, 1110B
Organized Camps 302. 1(9), 440
Research Laboratories 302.1(10), 443, 1106B.2
Residential 302.1(11), 310, HUB
Storage 302.1(12), 311,
1111BA.7, 1114B.1.2, 1125B
Utility and Miscellaneous 302. 1(13), 312,
1105B.3.1(3), 1105B.3.4,
1117B.5.8.1.2(Exc.2),
1133B.2.5(3Exc. 1)
UTILITIES 112
Service connection 1 12.1
Service disconnection 1 12.3
2010 CALIFORNIA BUILDING CODE
765
INDEX
Temporary connection 11 2.2
UTILITY AND MISCELLANEOUS
OCCUPANCY (GROUP U) 312
Accessibility Chapter 11A , 1104.3.1
Accessory 508.2, G801 .1
Agricultural buildings Appendix
Area 503, 505, 506, 507, 508
Egress iilumination 1006.1
Flood provisions G1001
Height 503, 504, 505, 506, 508, 509
Live loads Table 1607.1
Special occupancy separation Table 508.2.5
Sprinkler system, automatic 903.2.1 1
Travel distance 1014.3, 1016.1, 1021.2
V
VALIDITY 1.1.12
VALUATION OR VALUE
(see FEES, PERMIT) 109.3
VAPOR RETARDERS 1405
VEHICLE BARRIER SYSTEMS 406.2.4,
1602.1, 1607.7.3
VEHICLE SHOW ROOMS 304
VEHICULAR FUELING 406.5.2
VEHICULAR GATES 3110
VEHICULAR OR PEDESTRIAN
ARRIVAL POINTS (definition). . . . 202, 1107A.22-V
VENDING MACHINES AND
OTHER EQUIPMENT 1126B
VENEER
Cement plaster 1405.15
Fastening 1405.17
Fiber cement siding 1 405.1 6
Glazing 1405.12
Masonry, adhered 1405.10
Masonry, anchored 1405.6
Metal .1405.11
Plastic 2605
Slab-type 1405.8
Stone 1405.7
Terra cotta 1405.9
Vinyl 1405.14
Wood 1405.5
VENTILATION (see MECHANICAL) 101.4.2
Attic 1203.2
Aircraft hangars, residential 412.5.4
Aircraft paint hangars 412.6.6
Bathrooms 1203.4.2.1
Crawl space 1203.3
Elevator hoistways 3004
Exhaust, hazardous 1203.5
Exhaust, HPM 415.8.10
Exit enclosure 1022.5
Fabrication areas, HPM 41 5.8.2.6
Hazardous 414.3, 414.5.4, 415.6.1.4,
415.6.2.8, 415.8.2.8.2, 415.8.5.7,
415.8.6.3,415.8.7,415.8.9.3
High-rise 1022.9
HPM service corridors 41 5.8.4.3
Live/work unit 419.8
Mechanical 1203.1
Natural 1203.4
Parking 406.3.12, 406.4.2
Projection rooms 409.3
Repair garages 406.6.3
Roof 1203.2, 1503.5
Smokeproof enclosures 909.20.3,
909.20.4, 909.20.6
Spray rooms and spaces 416.2.1, 416.3
Stages 410.3.7
Under-floor ventilation 1203.3
VENTS, PENETRATION PROTECTION 713
VERMICULITE, FIRE RESISTANT 720
VERTICAL OPENING PROTECTION
Atriums 404.6
Duct penetrations 716.1
Elevators 708.14
Exceptions 708.2, 1022.1
Group 1-3 .. 408.5
High-rise 403.2.1 .2, 403.2.3,
403.3.1.1.403.5.1
Shaft enclosure 708, 1016.1, 1022.1
Value 3412.6.6.1
VESTIBULES, EXIT DISCHARGE 1027.1
VINYL
Expanded 802, 803.7, 803.8
Rigid 1405.14
VIOLATIONS 114
VOICE ALARM (see ALARMS, VOICE)
W
WALK (definition) 202, 1107A.23-W
WALKS/SIDEWALKS 1133B.7
Changes in level 1 133B.7.4
Continuous surface 1 133B.7. 1
Five percent gradient 1 133B.7.3
Gratings 1 133B.7.2
Level areas 1133B.7.5
Slopes 6 percent or greater 1133B.7.1.2
Slopes less than 6 percent 1 133B.7. 1. 1
Surface cross slopes 1 133B.7. 1.3
WALKWAY 3104
During construction 3306
Encroachment, public right-of-way 3202.3.4
Fire resistance Table 601
Live load .Table 1607.1
Materials per construction type Chapter 6
Opening protection 715, 716
WALL, EXTERIOR 705
Bearing Chapter 6
Coverings 1405
Exterior Insulation and
Finish Systems (EIFS) 1408
Exterior structural members 704.10
766
2010 CAUFORNIA BUILDING CODE
INDEX
Fire district D102.1, D102.2.6
Fire-resistance ratings Table 602, 703, 705.5,
706.5.1,707.4. 1403.4
Flasiiing, veneered walls 1405.4
Foam plastic insulation 2603.4.1 .4, 2603.5
Glazing, rated 715.5
Joints 705.9,714
Light-transmitting plastic panels 2607
Materials 705.4, 1406
Metal Composite Materials (MCM) 1407
Nonbearing Chapter 6
Opening protection 705.8, 705.10, 71 6.5.6
Parapets 705.1 1
Projections 705.2
Structural stability 705.6
Veneer (see VENEER)
Weather resistance 1403.2, 1405.2,
1407.6, 1408.4
Weather resistant barriers 1405.2
WALL, FIRE (see FIRE WALLS)
WALL, FOUNDATION (see FOUNDATION)
WALL, INTERIOR
Finishes 803, 1210.2, 1210.3
Opening protection 715, 716
WALL, INTERIOR NONBEARING (see PARTITIONS)
WALL, MASONRY 2102.1
Wood contact 2304.1 1 .2.3, 2304.1 1 .2.5
WALL, PARAPET 705.11, 1503.3,
1503.6,2109.3.4.1.4
WALL, PARTY (see FIRE WALLS)
WALL, PENETRATIONS 713.3
WALL, RETAINING (see RETAINING WALL)
WALL, VENEERED (see VENEER) Chapter 14
WALL, WOOD CONSTRUCTION
Bracing 2308.9.3
Cutting, notching, boring 2308.9.10
Exterior framing 2308.9
Fastening schedule 2304.9
Framing 2304.3, 2308.9
Interior bearing partition 2308.9.1
Interior nonbearing partition 2308.9.2.3
Openings 2308.9.5, 2308.9.6, 2308.9.7
Shear walls 2305.1 , 2306.3 through 2306.7
Sheathing (see SHEATHING)
Studs 2308.9.1
Top plates 2308.9.2.1
WATER-REACTIVE MATERIALS Table 307.1(1)
WEATHER, COLD
Concrete construction 1905.12
Masonry construction 2104.3
WEATHER, HOT
Concrete construction 1905.13
Masonry construction 2104.4
WEATHER PROTECTION
Exterior walls 1405.2
Roofs 1503
WELDING 2204.1
Materials, verification of
steel reinforcement 1704.4.1
Special inspections 1704.3.1, 1707.2, 1707.4
Splices of reinforcement in masonry 2107.4
Structural testing 1708.2, 1708.3
WHEELCHAIR (definition) 202
WHEELCHAIR SPACE (definition) 202
WIND LOAD 1609
Alternate all-heights method 1609.6
Basic wind speed 1609.3
Construction documents 107, 1603.1.4, 1709
Exposure category 1609.4
Glass block 2110
Glazing 1609.1 .2, 2404
Hurricane-prone regions 1609.2
Provisions for walls 2306.2
Roofs 1504.1, 1609.5, 2308.10.1
Seismic detailing required 1604.10
Special inspection 1706
Statement of special inspections 1705.4
Wind-borne debris region 1609.2
Wind tunnel testing 1609.1.1.2, 1716.2.2
WINDERS, STAIR (see STAIRWAY CONSTRUCTION)
WINDOW
Accessibility 1109.13.1
Emergency egress 1029
Exterior, structural testing 1715.5
Fire (see OPENING PROTECTIVES) 715.4.9,
715.4.10
Glass (see GLAZING) 1405.13
Required light 1205.2
Wells 1029.5
WIRES, PENETRATION PROTECTION 713
WOOD Chapter 23
Allowable stress design 2306
Bracing, walls 2308.9.3
Calculated fire resistance 721 .6
Ceiling framing 2308.10
Connections and fasteners 2304.9
Contacting concrete, masonry or earth . . . 2304.11.4
Decay, protection against 2304.1 1
Diaphragms 2305.1, 2305.2, 2306.2
Draftstopping 717.3, 717.4
End-jointed lumber 2303.1 .1
Fiberboard 2303.1 .5, 2306.6
Fire-retardant treated 2303.2
Fireblocking 717.2
Floor and roof framing
(see FLOOR CONSTRUCTION, WOOD) . . 2304.4
Floor sheathing 2304.7
Foundation 1807.1.4, 2308.3.3.1
Grade, lumber 2303.1.1
Hardboard 2303.1.6
Heavy timber construction 2304.10
Hurricane shutters 1609.1.2
l-joist 2303.1.2
2010 CALIFORNIA BUILDING CODE
767
INDEX
Inspection, special 1704.6, 1706.2, 1707.3
Lateral force- resisting systems 2305
Light-frame construction, conventional 2308
Load and resistance factor design 2307
Moisture content 2303.1.8.2, 2303.2.6
Nails and staples 2303.6
Particleboard shear walls 2306.5
Plywood, hardwood 2303.3
Preservative treated 1403.5, 1403.6, 2303.1.8
Roof framing
(see ROOF CONSTRUCTION, WOOD) . . . 2304.4
Roof sheathing 2304.7
Seismic provisions . . . 2305, 2306, 2308.11, 2308.12
Shear walls 2305, 2306.3 through 2306.7
Standards and quality, minimum 2303
Structural panels 2302.1 , 2303.1 .4
Supporting concrete or masonry 2304.12
Termite, protection against 2304.1 1
Trusses 2303.4
Veneer Chapter 14
Wall framing
(see WALL, WOOD CONSTRUCTION) .... 2304.3
Wall sheathing 2304.6
WOOD SHINGLES AND SHAKES .... 1507.8, 1507.9
WOOD STRUCTURAL PANELS
(see WOOD) 2302.1 , 2303.1 .4
Bracing 2308.9.3
Decorative 2303.3
Design requirements 2301
Diaphragms 2305.1 , 2306.2
Fastening 2304.9
Fire-retardant-treated 2303.2
Quality. 2303.1 .4
Roof sheathing 2304.7, 2308.10.8
Seismic shear panels 2305.1, 2308.12.4
Shear walls 2306.3
Sheathing 2304.6.1
Standards 2306.1
Subfloors 804.4
Veneer 1405.5
YARDS OR COURTS 1206
Group 1-2 407.8
Group 1-3 408.3.6, 408.6
Light, natural 1205
Motor fuel-dispensing facilities 406.5.3
Occupant load 1004.8
Parking garage, open 406.3.6
768
2010 CALIFORNIA BUILDING CODE
HISTORY NOTE APPENDIX
California Building Code
(Title 24, Part 2, California Code of Regulations)
For prior history, see the History Note Appendix to the California Building Code (CBC), 2010 Triennial Edition, effective
January 1, 2011.
1. (BSC 02/09, DSA-AC 01/09, DSA-SS 02/09, HCD 01/09, OSHPD 05/09 & 07/09, SFM 03/09, DWR 01/09) Adoption by refer-
ence of the 2009 International Building Code (IBC) with necessary state amendments into the 2010 CBC and repeal of the 2006
edition of the IBC, effective on January 1, 201 1.
201 CALIFORNIA BUILDING CODE 769
770 2010 CALIFORNIA BUILDING CODE
California Code of Regulations
Title 24, Part 8
California Building Standards Commission
Effective Dgte: January 1, , 2011
(For Errata andSypplements, see HistoRi'-Nqte Appendix)
2010 California Historical Building Code
California Code of Regulations, Title 24, Part 8
First Printing: June 2010
ISBN 978-1-58001-974-3
Published by
International Code Council
500 New Jersey Avenue, NW, 6th Floor
Washington, D.C. 20001
1-888-422-7233
COPYRIGHT ©2010
held by
California Building Standards Commission
2525 Natomas Park Drive, Suite 130
Sacramento, California 95833-2936
PRINTED IN THE U.S.A.
PREFACE
This document is the 8th of 12 parts of the official triennial compilation and publication of the adoptions, amendments
and repeal of administrative regulations to California Code of Regulations, Title 24, also referred to as the California
Building Standards Code. This part is known as the California Historical Building Code,
The California Building Standards Code is published in its entirety every three years by order of the California legis-
lature, with supplements published in intervening years. The California legislature delegated authority to various state
agencies, boards, commissions and departments to create building regulations to implement the State's statutes. These
building regulations, or standards, have the same force of law, and take effect 1 80 days after their publication unless oth-
erwise stipulated. The California Building Standards Code applies to occupancies in the State of California as
annotated.
A city, county, or city and county may establish more restrictive building standards reasonably necessary because of
local climatic, geological or topographical conditions. Findings of the local condition(s) and the adopted local building
standard(s) must be filed with the California Building Standards Commission to become effective and may not be effec-
tive sooner than the effective date of this edition of the California Building Standards Code. Local building standards
that were adopted and applicable to previous editions of the California Building Standards Code do not apply to this
edition without appropriate adoption and the required filing.
Should you find publication (e.g., typographical) errors or inconsistencies in this code or wish to offer conunents
toward improving its format, please address your comments to:
California Building Standards Commission
2525 Natomas Park Drive, Suite 130
Sacramento, CA 95833-2936
Phone: (916) 263-0916
Fax: (916) 263-0959
Web Page: www.bsc.ca.gov
For questions on California state agency amendments, please refer to the contact list on page vii.
201 CALIFORNIA HISTORICAL BUILDING CODE ill
PART 8 CONTAINS ALTERNATIVE REGULATIONS FOR
QUALIFIED HISTORICAL BUILDINGS
The California Historical Building Code (CHBC) is unique
among state regulations. The authoring of the original CHBC
required state agencies promulgating regulations for building
construction to work in harmony with representatives of other
design and construction disciplines. The result was a totally
new approach to building codes for historical structures, which
maintains currently acceptable life-safety standards.
These regulations are also unique in that they are performance
oriented rather than prescriptive. The provisions of the CHBC
are to be applied by the enforcing authority of every city,
county, city and county, or state agency in permitting repairs,
alterations and additions necessary for the preservation, reha-
bilitation, relocation, related construction, change of use or
continued use of a qualified historical building.
The authority for use of the CHBC is vested in Sections 18950
through 18961 of the Health and Safety Code. Section 18954
states, "The building department of every city or county shall
apply the provisions of alternative building standards and
building regulations adopted by the CHBC Board pursuant to
Section 1 8959.5 in permitting repairs, alterations and additions
necessary for the preservation, restoration, rehabilitation,
moving or continued use of an historical building or structure.
A state agency shall apply the alternative building regulations
adopted by the CHBC Board pursuant to Section 18959.5 in
permitting repairs, alterations and additions necessary for the
preservation, restoration, rehabilitation, moving or continued
use of an historical building or structure."
However, be aware that in order to use the CHBC, the structure
under consideration must be qualified by being designated as
an historical building or structure. Section 18955 states, "For
the purposes of this part, a qualified historical building or struc-
ture is any structure or collection of structures, and their associ-
ated sites deemed of importance to the history, architecture or
culture of an area by an appropriate local or state governmental
jurisdiction. This shall include structures on existing or future
national, state or local historical registers or official invento-
ries, such as the National Register of Historic Places, State His-
torical Landmarks, State Points of Historical Interest, and city
or county registers or inventories of historical or architecturally
significant sites, places, historic districts or landmarks."
The regulations of the CHBC have the same authority as state
law and are to be considered as such. Liability is the same as for
prevailing law.
The intent of the CHBC is to save CaHfomia's architectural
heritage by recognizing the unique construction problems
inherent in historical buildings and by providing a code to deal
with these problems.
Iv
2010 CALIFORNIA HISTORICAL BUILDING CODE
HISTORICAL PREFACE
The background of the California Historical Building Code
can be traced to December 1973, when the State Department of
Parks and Recreation pubhshed the Cahfomia History Plan,
Volume I, in which Recommendation No. 1 1 was proposed by
the then Cahfomia Landmarks Advisory Committee (later to
become The State Historical Resources Commission). This
proposal expressed a need for a new building code to meet the
intent of protecting the public health and safety and also retain
"enough flexibiUty to allow restoration of a Historic feature
while still retaining its Historic integrity." No. 1 1 of this His-
tory Plan supported this need by stating that "... restoration . . .
is frequently made difficult by unnecessarily rigid interpreta-
tion of building . . . codes."
In March of 1974, the Landmarks Committee by resolution
recommended that the Director of the State Department of
Parks and Recreation and the State Architect initiate a study to
develop this needed code. These two officials accepted this
concept and jointly called a statewide meeting in Sacramento
on May 14th of that year. Attending were representatives from
both the public and private sectors, such as members of the
building industry, design professions, local and state building
officials, and others interested in this problem.
Out of this open conference, a steering committee was formed
to explore in depth the ways and means of implementing the
new historical building code concept. This ad hoc committee
was chaired by a representative from the California Council,
American Institute of Architects and composed of a compre-
hensive cross section of the professional organizations
and government agencies concerned with design and code
enforcement.
Meetings began late in 1974 and continued into early 1975. By
April of that year, a legislative subcommittee of the ad hoc
group drafted a sample bill for the proposed code and requested
that it be carried by Senator James R. Mills, President Pro Tem-
pore of the Senate. After further development and refinement,
the enacting legislation to create the authority for the code and
an advisory board to prepare regulations to implement it (SB
927, Mills) was supported by both the legislature and the pub-
lic. It was signed by the governor in September 1975, and
became effective January 1, 1976.
The members of the advisory board, which were required by
law to include local and state building officials, individuals
from the building industry and design professions, as well as
representatives from city and county governments, were
appointed and held their first session in Sacramento, February
24, 1976. This Board's duties included the preparation of code
regulations and the review of specific historic building cases,
when officially requested by governing bodies.
Several of the Board's members were a part of the original ad
hoc steering committee and thus provided a continuity and
smooth transition from the inception of the code's philosophy
to its pragmatic implementation in these performance-oriented
regulations.
The first comprehensive regulations were codified in August
and October 1979, after years of careful deliberation. Those
regulations allowed all jurisdictions to utilize them at their dis-
cretion in replacing or modifying details of prevailing prescrip-
tive codes.
Changes made in law in 1984 and 1991, and to the code, make
the application of the California Historical Building Code stat-
utes and regulations applicable for all agencies and at the dis-
cretion of the owner for local jurisdictions when dealing with
qualified historical buildings.
These current performance regulations were adopted by the
Board on June 23, 1998, and approved by the California Build-
ing Standards Commission on January 29, 2007.
2010 CALIFORNIA HISTORICAL BUILDING CODE
vi 201 CALIFORNIA HISTORICAL BUILDING CODE
CALIFORNIA CODE OF REGULATIONS, TITLE 24
California Agency Information Contact List
California Energy Commission
Energy Hotline (800) 772-3300
or (916) 654-5106
Building Efficiency Standards
Appliance Efficiency Standards
Compliance Manual/Forms
California State Lands Commission
Marine Oil Terminals (562) 499-6317
California State Library
Resources and Information (916) 654-0261
Government Publication Section (916) 654-0069
Corrections Standards Authority
Local Adult Jail Standards (916) 324-1914
Local Juvenile Facility Standards (^i^) 324-1914
Department of Consumer Affairs - Acupuncture Board
Office Standards (916) 445-3021
Department of Consumer Affairs - Board of Pharmacy
Pharmacy Standards (916) 574-7900
Department of Consumer Affairs - Bureau of Bartering
And Cosmetolog y
Barber and Beauty Shop and
College Standards (916) 574-7570
(800) 952-5210
Department of Consumer Affairs - Bureau of
Home Furnishings and Thermal Insulation
Insulation Testing Standards (916) 574-2041
Department of Consumer Affairs -
Structural Pest Control Board
Structural Standards (800) 737-8188
(916) 561-8708
Department of Consumer Affairs -
Veterinary Medical Board
Veterinary Hospital Standard (916) 263-2610
Department of Food and Agriculture
Meat and Poultry Packing Plant
Standards (916) 654-1447
Dairy Standards (916) 654-1447
Department of Public Health
Organized Camps Standards (916) 449-5661
Public Swimming Pools Standards (916) 449-5693
Asbestos Standards (510) 620-2874
Department of Housing and Community Development
Residential - Hotels, Motels, Apartments,
Single-Family Dwellings (916) 445-9471
Permanent Structures in Mobilehome and
Special Occupancy Parks (916) 445-9471
Factory-Built Housing, Manufactured
Housing and Commercial Modular (916) 445-3338
Mobilehomes - Permits and Inspections
Northern Region (916) 225-2501
Southern Region (951) 782-4420
Employee Housing Standards (916) 445-9471
Department of Water Resources
Gray Water Installations Standards (916) 651-9667
Division of the State Architect - Access Compliance
Access Compliance Standards (916) 445-8100
Division of the State Architect - Structural Safety
Public Schools Standards (916) 445-8100
Essential Services Building Standards (916) 445-8100
Community College Standards (916) 445-8100
Division of the State Architect - State Historical Building
Safety Board
Alternative Building Standards (916) 445-8100
Office of Statewide Health Planning and Development
Hospital Standards (916) 440-8409
Skilled Nursing Facility Standards (916) 440-8409
Clinic Standards (916) 440-8409
Permits (916) 440-8409
Office of the State Fire Marshal
Code Development and Analysis (916)445-8200
Fire Safety Standards (916)445-8200
Fireplace Standards (916)445-8200
Day-Care Centers Standards (916)445-8200
Exit Standards (916)445-8200
2010 CALIFORNIA HISTORICAL BUILDING CODE
VII
HOW TO DETERMINE WHERE
CHANGES HAVE BEEN MADE
Symbols in the margins indicate where changes have been
made or language has been deleted.
This symbol indicates that a change has been made.
> This symbol indicates deletion of language.
viii 2010 CALIFORNIA HISTORICAL BUILDING CODE
TABLE OF CONTENTS
CHAPTER 8-1 ADMINISTRATION 1
Section
8-101 Title, Purpose and Intent 1
8-102 Application 1
8-103 Organization and Enforcement 1
8-104 Review and Appeals 2
8-105 Construction Methods and Materials 2
8-106 SHBSB Rulings 2
CHAPTER 8-2 DEFINITIONS 3
Section
8-201 Definitions 3
CHAPTER 8-3 USE AND OCCUPANCY 5
Section
8-301 Purpose and Scope 5
8-302 General 5
8-303 Residential Occupancies 5
CHAPTER 8-4 FIRE PROTECTION 7
Section
8-401 Purpose, Intent and Scope 7
8-402 Fire-resistive Construction 7
8-403 Interior Finish Materials 7
8-404 Wood Lath and Plaster 7
8-405 Occupancy Separation 7
8-406 Maximum Floor Area 7
8-407 Vertical Shafts 7
8-408 Roof Covering 7
8-409 Fire Alarm Systems 8
8-410 Automatic Sprinkler Systems 8
8-411 Other Technologies 8
8-412 High-rise Buildings 8
CHAPTER 8-5 MEANS OF EGRESS 9
Section
8-501 Purpose, Intent and Scope 9
8-502 General 9
8-503 Escape or Rescue Windows and Doors 10
8-504 Railings and Guardrails 10
CHAPTER 8-6 ACCESSIBILITY 11
Section
8-601 Purpose, Intent and Scope 11
8-602 Basic Provisions 11
8-603 Alternatives 11
8-604 Equivalent Facilitation 12
CHAPTER 8-7 STRUCTURAL REGULATIONS . . 13
Section
8-701 Purpose, Intent and Scope 13
8-702 General 13
8-703 Structural Survey 13
8-704 Nonhistorical Additions and Nonhistorical
Alterations 13
8-705 Structural Regulations 13
8-706 Lateral Load Regulations 13
CHAPTER 8-8 ARCHAIC MATERIALS AND
METHODS OF CONSTRUCTION 15
Section
8-801 Purpose, Intent and Scope 15
8-802 General Engineering Approaches 15
8-803 Nonstructural Archaic Materials 15
8-804 Allowable Conditions for Specific Materials .... 15
8-805 Masonry 15
8-806 Adobe 16
8-807 Wood 16
8-808 Concrete 16
8-809 Steel and Iron 16
8-810 Hollow Clay Tile 17
8-811 Veneers 17
8-812 Glass and Glazing 17
CHAPTER 8-9 MECHANICAL, PLUMBING AND
ELECTRICAL REQUIREMENTS « . 19
Section
8-901 Purpose, Intent and Scope 19
8-902 Mechanical 19
8-903 Plumbing 20
8-904 Electrical 21
2010 CALIFORNIA HISTORICAL BUILDING CODE
ix
CHAPTER 8-10 QUALIFIED HISTORICAL
DISTRICTS, SITES AND OPEN SPACES 23
Section
8-1001 Purpose and Scope 23
8-1002 Application 23
8-1003 Site Relations 23
APPENDIX A 25
HISTORY NOTE APPENDIX 29
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-1
ADMINISTRATION
Note: The California Historical Building Code, Part 8 of Title 24, governs for all
qualified historical buildings or properties in the State of California.
SECTION 8-101
TITLE, PURPOSE AND INTENT
8-101.1 Title. These regulations shall be known as the Califor-
nia Historical Building Code and will be referred to herein as
"the CHBC."
8-101.2 Purpose. The purpose of the CHBC is to provide regu-
lations for the preservation, restoration, rehabiUtation, reloca-
tion or reconstruction of buildings or properties designated as
qualified historical buildings or properties (Chapter 8-2). The
CHBC is intended to provide solutions for the preservation of
qualified historical buildings or properties, to promote
sustainability, to provide access for persons with disabilities, to
provide a cost-effective approach to preservation, and to pro-
vide for the reasonable safety of the occupants or users. The
CHBC requires enforcing agencies to accept solutions that are
reasonably equivalent to the regular code (as defined in Chap-
ter 8-2) when deaUng with qualified historical buildings or
properties.
8-101.3 Intent. The intent of the CHBC is to facilitate the pres-
ervation and continuing use of qualified historical buildings or
properties while providing reasonable safety for the building
occupants and access for persons with disabilities.
SECTION 8-102
APPLICATION
8-102.1 Application. The CHBC is applicable to all issues
regarding code compliance for qualified historical buildings or
properties. The CHBC may be used in conjunction with the
regular code to provide solutions to facilitate the preservation
of qualified historical buildings or properties. The CHBC shall
be used by any agency with jurisdiction and whenever compli-
ance with the code is required for qualified historical buildings
or properties.
1, The state or local enforcing agency shall apply the pro-
visions of the CHBC in permitting repairs, alterations
and additions necessary for the preservation, restora-
tion, reconstruction, rehabilitation, relocation or con-
tinued use of a qualified historical building or property
when so elected by the private property owner.
2. State agencies. All state agencies shall apply the provi-
sions of the CHBC in permitting repairs, alterations and
additions necessary for the preservation, restoration,
rehabilitation, safety, relocation, reconstruction or con-
tinued use of qualified historical buildings or proper-
ties.
8-102.1.1 Additions, alterations and repairs. It is the
intent of the CHBC to allow nonhistorical expansion or
addition to a qualified historical building or property, pro-
vided nonhistorical additions shall conform to the
requirements of the regular code. See Chapter 8-2.
8-102.1.2 Relocation. Relocated qualified historical build-
ings or properties shall be sited to comply with the regular
code or with the solutions listed in the CHBC. Nonhistorical
new construction related to relocation shall comply with the
regular code. Reconstruction and restoration related to relo-
cation is permitted to comply with the provisions in the
CHBC.
8-102.1.3 Change of occupancy. For change of use or
occupancy, see Chapter 8-3, Use and Occupancy.
8-102.1.4 Continued use. QuaHfied historical buildings or
properties may have their existing use or occupancy contin-
ued if such use or occupancy conformed to the code or to the
standards of construction in effect at the time of construc-
tion, and such use or occupancty does not constitute a dis-
tinct hazard to life safety as defined in the CHBC.
8-102.1.5 Unsafe buildings or properties. When a quali-
fied historical building or property is determined to be
unsafe as defined in the regular code, the requirements of
the CHBC are applicable to the work necessary to correct
the unsafe conditions. Work to remediate the buildings or
properties need only address the correction of the unsafe
conditions, and it shall not be required to bring the entire
qualified historical building or property into compliance
with regular code.
8-102.1.6 Additional work. Qualified historical buildings
or properties shall not be subject to additional work required
by the regular code, regulation or ordinance beyond that
required to complete the work undertaken. Certain excep-
tions for accessibility and for distinct hazards exist by man-
date and may require specific action, within the parameters
of the CHBC.
SECTION 8-103
ORGANIZATION AND ENFORCEMENT
8-103,1 Authority. The state or local enforcing agency, pursu-
ant to authority provided under Section 18954 of the Health
and Safety Code, shall administer and enforce the provisions of
the CHBC in permitting repairs, alterations and additions nec-
essary for the preservation, restoration, reconstruction, reha-
bilitation, relocation or continued use of a qualified historical
building or property.
8-103.2 State enforcement. All state agencies pursuant to
authority provided under Section 18954 and Section 18961 of
the Health and Safety Code shall administer and enforce the
CHBC with respect to qualified historical buildings or proper-
ties under their respective jurisdiction.
2010 CALIFORNIA HISTORICAL BUILDING CODE
ADMINISTRATION
8-103.3 Liability. Prevailing law regarding immunity of build-
ing officials is unaffected by the use and enforcement of the
CHBC.
SECTION 8-104
REVIEW AND APPEALS
8-104.1 State Historical Building Safety Board (SHBSB). In
order to provide for interpretation of the provisions of the
CHBC and to hear appeals, the SHBSB shall act as an appeal
and review body to state and local agencies or any affected
party.
8-104.2 SHBSB review. When a proposed design, material or
method of construction is being considered by the enforcing
agency, the agency chief, the building official or the local board
of appeals may file a written request for opinion to the SHBSB
for its consideration, advice or findings. In considering such
request, the SHBSB may seek the advice of other appropriate
private or public boards, individuals, or state or local agencies.
The SHBSB shall, after considering all of the facts presented,
including any recommendation of other appropriate boards,
agencies or other parties, determine if, for the purpose
intended, the proposal is reasonably equivalent to that allowed
by these regulations in proposed design, material or method of
construction, and it shall transmit such findings and its decision
to the enforcing agency for its application. The Board may
recover the costs of such reviews and shall report the decision
in printed form, copied to the California Building Standards
Commission.
8-104.2.1 State agencies. All state agencies with ownership
of, or that act on behalf of state agency owners of, qualified
historical buildings or properties, shall consult and obtain
SHBSB review prior to taking action or making decisions or
appeals that affect qualified historical buildings or proper-
ties, per Section 18961 of the Health and Safety Code.
8-104.2.2 Imminent threat. Where an emergency is
declared and a qualified historical building or property is
declared an imminent threat to life and safety, the state
agency assessing such a threat shall consult with the
SHBSB before any demolition is undertaken, per Section
18961 of the Health and Safety Code.
8-104.3 SHBC appeals. If any local agency administering and
enforcing the CHBC or any person adversely affected by any
regulation, rule, omission, interpretation, decision or practice
of the agency enforcing the CHBC wishes to appeal the issue
for resolution to the SHBSB, either of these parties may appeal
directly to the Board. The Board may accept the appeal only if
it determines that issues involved are of statewide significance.
The Board may recover the costs of such reviews and shall
make available copies of decisions in printed form at cost, cop-
ied to the California Building Standards Commission.
8-104.4 Local agency fees. Local agencies, when actively
involved in the appeal, may also charge affected persons rea-
sonable fees not to exceed the cost of obtaining reviews and
appeals from the Board.
SECTION 8-105
CONSTRUCTION METHODS AND MATERIALS
8-105.1 Repairs. Repairs to any portion of a qualified histori-
cal building or property may be made in-kind with historical
materials and the use of original or existing historical methods
of construction, subject to conditions of the CHBC. (See Chap-
ter 8-8.)
8-105.2 Solutions to the California Historical Building
Code, Solutions provided in the CHBC, or any other acceptable
regulation or methodology of design or construction and used
in whole or in part, with the regular code, or with any combina-
tion of the regular code and the CHBC, shall be allowed. The
CHBC does not preclude the use of any proposed alternative or
method of design or construction not specifically prescribed or
otherwise allowed by these regulations. Any alternative may be
submitted for evaluation to the appropriate enforcing agency
for review and acceptance. The enforcing agency may request
that sufficient evidence or proof be submitted to substantiate
any claims that may be made regarding such solutions. Any
alternative offered in lieu of that prescribed or allowed in the
CHBC shall be reasonably equivalent in quality, strength,
effectiveness, durability and safety to that of the CHBC.
SECTION 8-106
SHBSB RULINGS
8-106.1 General. Rulings of the SHBSB (i.e., formal appeals,
case decisions, code interpretations and administrative resolu-
tions, etc.) that are issues of statewide application are required
to be submitted to the California Building Standards Commis-
sion in printed form. These rulings may be used to provide
guidance for similar cases or issues.
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-2
DEFINITIONS
SECTION 8-201
DEFINITIONS
For the purpose of the CHBC, certain terms and phrases, words
and their derivatives shall be construed as specified in this
chapter. Additional definitions and/or terms may appear in the
various other chapters relative to terms or phrases primarily
applicable thereto. Any reference to "authority having jurisdic-
tion" does not necessarily preclude the appellate process of
Section 8-104.3.
ADDITION. A nonhistorical extension or increase in floor
area or height of a building or property.
ALTERATION. A modification to a qualified historical build-
ing or property that affects the usability of the building or
property, or part thereof. Alterations include, but are not lim-
ited to, remodeling, renovation, rehabilitation, reconstruction,
historical restoration, changes or rearrangement of the struc-
tural parts or elements, and changes or rearrangements in the
plan configuration of walls and full-height partitions.
BUILDING STANDARD. Any guideline, regulation or code
that may be applied to a qualified historical building or
property.
CHARACTER-DEFINING FEATURE. Those visual
aspects and physical elements that comprise the appearance of
a historical building or property, and that are significant to its
historical, architectural and cultural values, including the over-
all shape of the historical building or property, its materials,
craftsmanship, decorative details, interior spaces and features,
as well as the various aspects of its site and environment.
CULTURAL RESOURCE. Building, site, property, object or
district evaluated as having significance in prehistory or
history.
DISTINCT HAZARD. Any clear and evident condition that
exists as an immediate danger to the safety of the occupants or
public right of way. Conditions that do not meet the require-
ments of current regular codes and ordinances do not, of them-
selves, constitute a distinct hazard. Section 8-104.3, SHBC
appeals, remains applicable.
ENFORCING AGENCY, Authority Having Jurisdiction,
Local Agency with Jurisdiction. An entity with the responsibil-
ity for regulating, enforcing, reviewing or otherwise that exerts
control of or administration over the process of gaining per-
mits, approvals, decisions, variances, appeals for qualified his-
torical buildings or properties.
EXIT LADDER DEVICE. An exit ladder device is a perma-
nently installed, fixed, folding, retractable or hinged ladder
intended for use as a means of emergency egress from areas of
the second or third stories. Unless approved specifically for a
longer length, the ladder shall be limited to 25 feet (7620 mm)
in length. Exit ladders are permitted where the area served by
the ladder has an occupant load less than 10 persons.
FIRE HAZARD. Any condition which increases or may con-
tribute to an increase in the hazard or menace of fire to a greater
degree than customarily recognized by the authority having
jurisdiction, or any condition or act which could obstruct,
delay, hinder or interfere with the operations of firefighting
personnel or the egress of occupants in the event of fire. Section
8-104.3, SHBC appeals, remains applicable.
HISTORICAL FABRIC OR MATERIALS. Original and
later- added historically significant construction materials,
architectural finishes or elements in a particular pattern or con-
figuration which form a qualified historical property, as deter-
mined by the authority having jurisdiction.
HISTORICAL SIGNIFICANCE. Importance for which a
property has been evaluated and found to be historical, as deter-
mined by the authority having jurisdiction.
IMMINENT THREAT. Any condition within or affecting a
qualified historical building or property which, in the opinion
of the authority having jurisdiction, would qualify a building or
property as dangerous to the extent that the life, health, prop-
erty or safety of the public, its occupants or those performing
necessary repair, stabilization or shoring work are in immedi-
ate peril due to conditions affecting the building or property.
Potential hazards to persons using, or improvements within,
the right-of-way may not be construed to be '^imminent threats"
solely for that reason if the hazard can be mitigated by shoring,
stabilization, barricades or temporary fences.
INTEGRITY. Authenticity of a building or property's his-
torical identity, evidenced by the survival of physical charac-
teristics that existed during the property's historical or
prehistorical period of significance.
LIFE-SAFETY EVALUATION. An evaluation of the
life-safety hazards of a qualified historical building or property
based on procedures similar to those contained in NFPA 909,
Standard for the Protection of Cultural Resources, Appendix B,
Fire Risk Assessment in Heritage Premises.
LIFE SAFETY HAZARD. See Distinct Hazard.
PERIOD OF SIGNIFICANCE. The period of time when a
qualified historical building or property was associated with
important events, activities or persons, or attained the charac-
teristics for its listing or registration.
PRESERVATION. The act or process of applying measures
necessary to sustain the existing form, integrity and materials
of a qualified historical building or property. Work, including
preliminary measures to protect and stabilize the property, gen-
erally focuses upon the ongoing maintenance and repair of his-
toric materials and features rather than extensive replacement
and new construction. New exterior additions are not within the
scope of this treatment; however, the limited and sensitive
upgrading of mechanical, electrical and plumbing systems and
other code-related work to make properties functional is appro-
priate within a preservation project.
2010 CALIFORNIA HISTORICAL BUILDING CODE
DEFINITIONS
QUALIFIED HISTORICAL BUILDING OR PROP-
ERTY. As defined in Health and Safety Code Section 1 8955 as
"Qualified Historical Building or Property." Any building, site,
object, place, location, district or collection of structures, and
their associated sites, deemed of importance to the history,
architecture or culture of an area by an appropriate local, state
or federal governmental jurisdiction. This shall include histori-
cal buildings or properties on, or determined eligible for,
national, state or local historical registers or inventories, such
as the National Register of Historic Places, California Register
of Historical Resources, State Historical Landmarks, State
Points of Historical Interest, and city or county registers, inven-
tories or surveys of historical or architecturally significant
sites, places or landmarks.
RECONSTRUCTION. The act or process of depicting, by
means of new construction, the form, features and detailing of a
nonsurviving site, landscape, building, property or object for
the purpose of replicating its appearance at a specific period of
time.
REGULAR CODE. The adopted regulations that govern the
design and construction or alteration of nonhistorical buildings
and properties within the jurisdiction of the enforcing agency.
REHABILITATION. The act or process of making possible a
compatible use for qualified historical building or property
through repair, alterations and additions while preserving those
portions or features which convey its qualified historical, cul-
tural or architectural values.
RELOCATION. The act or process of moving any qualified
historical building or property or a portion of a qualified histor-
ical building or property to a new site, or a different location on
the same site.
REPAIR. Renewal, reconstruction or renovation of any por-
tion of an existing property, site or building for the purpose of
its continued use.
RESTORATION. The act or process of accurately depicting
the form, features and character of a qualified building or
property as it appeared at a particular period of time by the
means of the removal of features from other periods in its his-
tory and reconstruction of missing features from the restoration
period. The limited and sensitive upgrading of mechanical,
electrical and plumbing systems and other code-required work
to make properties functional is appropriate within a restora-
tion project.
STRUCTURE. That which is built or constructed, an edifice
or a building of any kind, or any piece of work artificially built
up or composed of parts joined together in some definite
manner.
TREATMENT. An act of work to carry out preservation, res-
toration, stabilization, rehabilitation or reconstruction.
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-3
USE AND OCCUPANCY
SECTION 8-301
PURPOSE AND SCOPE
8-301.1 Purpose. The purpose of the CHBC is to provide reg-
ulations for the determination of occupancy classifications and
conditions of use for qualified historical buildings or
properties.
8-301.2 Scope. Every qualified historical building or property
for which a permit or approval has been requested shall be clas-
sified prior to permit issuance according to its use or the char-
acter of its occupancy in accordance with the regular code and
applicable provisions of this chapter.
SECTION 8-302
GENERAL
8-302.1 Existing use. The use or character of occupancy of a
qualified historical building or property, or portion thereof,
shall be permitted to continue in use regardless of any period of
time in which it may have remained unoccupied or in other
uses, provided such building or property otherwise conforms to
all applicable requirements of the CHBC.
8-302.2 Change in occupancy. The use or character of the
occupancy of a qualified historical building or property may be
changed from or returned to its historical use or character, pro-
vided the qualified historical building or property conforms to
the requirements applicable to the new use or character of
occupancy as set forth in the CHBC. Such change in occupancy
shall not mandate conformance with new construction require-
ments as set forth in regular code.
8-302.3 Occupancy separations. Required occupancy sepa-
rations of more than one hour may be reduced to one-hour
fire-resistive construction with all openings protected by not
less than three-fourths-hour fire-resistive assemblies of the
self-closing or automatic-closing type when the building is
provided with an automatic sprinkler system throughout the
entire building in accordance with Section 8-410.4. Doors
equipped with automatic-closing devices shall be of a type
which will function upon activation of a device which responds
to products of combustion other than heat.
Required occupancy separations of one hour may be omitted
when the building is provided with an automatic sprinkler sys-
tem throughout.
8-302.4 Maximum floor area. Regardless of the use or char-
acter of occupancy, the area of a one-story qualified historical
building or property may have, but shall not exceed, a floor area
of 15,000 square feet (1393.5 m^) unless such an increase is
otherwise permitted in regular code. Multistory qualified his-
torical buildings (including basements and cellars) shall be in
accordance with regular code requirements.
Exception: Historical buildings may be unlimited in floor
area without fire-resistive area separation walls:
1. When provided with an automatic sprinkler, or
2. Residential occupancies of two stories or less when pro-
vided with a complete fire alarm and annunciation sys-
tem and where the exiting system conforms to regular
code.
8-302.5 Maximum height. The maximum height and number
of stories of a qualified historical building or property shall not
be limited because of construction type, provided such height
or number of stories does not exceed that of its historical
design.
8-302.5.1 High-rise buildings. Occupancies B,F-l,F-2 or
S in high-rise buildings with floors located more than 75
feet above the lowest floor level having building access may
be permitted with only the stories over 75 feet provided with
an automatic fire sprinkler system if :
1. The building construction type and the exits con-
form to regular code, and
2. A complete building fire alarm and annunciation
system is installed, and
3. A fire barrier is provided between the sprinklered
and nonsprinklered floors.
8-302.6 Fire-resistive construction. See Chapter 8-4.
8-302.7 Light and ventilation. Existing provisions for light
and ventilation which do not, in the opinion of the enforcing
agency, constitute a safety hazard may remain. See Section
8-303.6 for residential requirements. See Section 8-503 for
Escape or Rescue Windows and Doors.
SECTION 8-303
RESIDENTIAL OCCUPANCIES
8-303.1 Purpose. The purpose of this section is to provide reg-
ulations for those buildings designated as qualified historical
buildings or properties and classified as occupancies. The
CHBC requires enforcing agencies to accept any reasonably
equivalent to the regular code when dealing with qualified his-
torical buildings and properties.
8-303.2 Intent. The intent of the CHBC is to preserve the
integrity of qualified historical buildings and properties while
maintaining a reasonable degree of protection of life, health
and safety for the occupants.
8-303.3 Application and scope. The provisions of this section
shall apply to all qualified historical buildings used for human
habitation. Those dwelling units intended only for display, or
public use with no residential use involved, need not comply
with the requirements of this section.
2010 CALIFORNIA HISTORICAL BUILDING CODE
USE AND OCCUPANCY
8-303.4 Fire escapes. See Chapter 8-5.
8-303.5 Room dimensions. Rooms used for sleeping purposes
may contain a minimum of 50 square feet (4.6 m^) floor area,
provided there is maintained an average ceiling height of 7 feet
(2134 mm). Other habitable rooms need only be of adequate
size to be functional for the purpose intended.
8-303.6 Light and ventilation. Windows in habitable rooms
shall have an area of 6 percent of the floor area, or 6 square feet
(0.56 m^), whichever is greater. Windows in sleeping rooms
shall be openable (see Section 8-503). Residential occupancies
need not be provided with electrical lighting.
8-303.7 Alteration and repair. The alteration and repair of
qualified historical buildings or properties may permit the
replacement, retention and extension of original materials and
the continued use of original methods of construction, pro-
vided a life-safety hazard is not created or continued. Alter-
ations and repairs shall be consistent with the CHBC.
The amount of alterations and repairs is not limited, pro-
vided there is no nonhistorical increase in floor area, volume or
size of the building or property.
8-303.8 Exiting. See Chapter 8-5.
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-4
FIRE PROTECTION
SECTION 8-401
PURPOSE, INTENT AND SCOPE
8-401.1 Purpose. The purpose of this chapter is to provide for
fire protection of qualified historical buildings or properties.
The CHBC requires enforcing agencies to accept any reason-
ably equivalent to the regular code when dealing with qualified
historical buildings or properties.
8-401.2 Intent. The intent of the CHBC is to preserve the
integrity of qualified historical buildings or properties while
maintaining a reasonable degree of fire protection based
primarily on the life safety of the occupants and firefighting
personnel.
8-401.3 Scope. This chapter shall apply when required by the
provisions of Section 8-102.
SECTION 8-402
FIRE-RESISTIVE CONSTRUCTION
8-402.1 Exterior wall construction. The fire-resistance
requirement for existing exterior walls and existing opening
protection may be satisfied when an automatic sprinkler sys-
tem designed for exposure protection is installed per the
CHBC. The automatic sprinklers may be installed on the exte-
rior with at least one sprinkler located over each opening
required to be protected. Additional sprinklers shall also be dis-
tributed along combustible walls under the roof lines that do
not meet the fire-resistive requirement due to relationship to
property lines as required by regular code. Such sprinkler sys-
tems may be connected to the domestic water supply on the
supply-main side of the building shut-off valve. A shut-off
valve may be installed for the sprinkler system, provided it is
locked in an open position.
8-402.2 One-hour construction. Upgrading an existing quali-
fied historical building or property to one-hour fire-resistive
construction and one-hour fire-resistive corridors shall not be
required regardless of construction or occupancy when one of
the following is provided:
1 . An automatic sprinkler system throughout. See Section
8-410.2 for automatic sprinkler systems.
2. An approved Hfe-safety evaluation.
3. Other alternative measures as approved by the enforc-
ing agency.
8-402.3 Openings in fire-rated systems. Historical glazing
materials and solid wood unrated doors in interior walls
required to have one-hour fire rating may be approved when
operable windows and doors are provided with appropriate
smoke seals and when the area affected is provided with an
automatic sprinkler system. See Section 8-410 for automatic
sprinkler systems.
SECTION 8-403
INTERIOR FINISH MATERIALS
New nonhistorical interior wall and ceiling finish shall con-
form to the provisions of the regular code. Existing noncon-
forming materials used for wood lath and plaster walls, see
Section 8-404.
Exception: When an automatic sprinkler system is pro-
vided throughout the building, existing finishes shall be
approved.
SECTION 8-404
WOOD LATH AND PLASTER
Wood lath and plaster walls may be considered in accordance
with codes, standards and listings published prior to 1943
whereby a wood stud wall assembly with gypsum or lime plas-
ter on hand split or sawn wooden lath obtains a one-half-hour
fire-resistive rating. This rating may be increased for interior
walls to as much as one hour by filling the wall with mineral
fiber or glass fiber.
SECTION 8-405
OCCUPANCY SEPARATION
See Chapter 8-3,
SECTION 8-406
MAXIMUM FLOOR AREA
See Chapter 8-3.
SECTION 8-407
VERTICAL SHAFTS
Vertical shafts need not be enclosed when such shafts are
blocked at every floor level by the installation of not less than 2
full inches (51 mm) of soHd wood or equivalent construction
installed so as to prevent the initial passage of smoke and flame.
Automatic sprinkler systems or other solutions may be consid-
ered on a case-by-case basis, in lieu of enclosure of vertical
shafts and stairwells.
SECTION 8-408
ROOF COVERING
Existing or original roofing materials may be repaired or recon-
structed subject to the following requirements:
1. The original or historical roofing system shall be
detailed or modified as necessary in order to be capable
of providing shelter while preserving the historical
materials and appearance of the roof,
2. Wooden roof materials may be utilized where fire resis-
tance is required, provided they are treated with
2010 CALIFORNIA HISTORICAL BUILDING CODE
FIRE PROTECTION
fire-retardant treatments to achieve a Class "B" roof
covering rating. Wood roofing in state designated
Urban Wildland and High Fire Zones shall be permitted
when installed in class "A" assemblies.
3. Jurisdictions that prohibit wood roofmg materials for
application as roof coverings and roof assemblies shall
submit documentation for the adoption. Express Terms,
statement of reasons and minutes of the action by the
adopting authority Health and Safety Code, Section
18959(f).
SECTION 8-409
FIRE ALARM SYSTEMS
Every qualified historical building or property shall be pro-
vided with fire alarm systems as required for the use or occu-
pancy by the regular code or other approved alternative.
SECTION 8-411
OTHER TECHNOLOGIES
Fire alarm systems, smoke and heat detection systems, occu-
pant notification and annunciation systems, smoke control sys-
tems and fire modeling, times egress analysis and modehng,
as well as other engineering methods and technologies may
be accepted by the enforcing agency to address areas of non-
conformance.
SECTION 8-412
HIGH-RISE BUILDINGS
Qualified historical buildings having floors for human occu-
pancy located more than 75 feet above the lowest floor level
having building access shall conform to the provisions of the
regular code for existing high-rise buildings as amended by the
CHBC.
SECTION 8-410
AUTOMATIC SPRINKLER SYSTEMS
8-410.1 Every quahfied historical building or property which
cannot be made to conform to the construction requirements
specified in the regular code for the occupancy or use, and
which constitutes a distinct fire hazard (for definition of "dis-
tinct hazard," see Chapter 8-2), shall be deemed to be in com-
pliance if provided with an automatic sprinkler system or a
life- safety system or other technologies as approved by the
enforcing agency. ("Automatic" is defined in the regular code.
Sprinkler System is defined in this section.)
8-410.2 When required by the CHBC, an automatic sprinkler
systems is defined by the following standards (for nonhazard-
ous occupancies).
1. Buildings of four stories or less: NFPA 13R, 2002 edi-
tion.
2. For floors above the fourth, NFPA 13, 2002, SFM
amended edition.
3. Buildings with floors above 75 feet, NFPA 13, 2002
edition.
4. When the building is free standing or with property line
separation, two floors and 1500 sf per floor or less,
NFPA 13D, 2002 Edition,
5. For exterior wall and opening protection. As required
by this section.
Exception: When the automatic sprinkler systems
are used to reach compliance using this code, in three
or more occasions, the system shall be NFPA standard
13D shall be increased to NFPA 13R Standard, or
NI^A 13R standard shall be increased to a NFPA 13
standard.
8-410.3 Automatic sprinkler systems shall not be used to sub-
stitute for or act as an alternate to the required number of exits
from any facility. (See Chapter 8-5 for exiting requirements.)
8-410.4 An automatic sprinkler system shall be provided in all
detention facilities.
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-5
MEANS OF EGRESS
SECTION 8-501
PURPOSE, INTENT AND SCOPE
8-501.1 Purpose. The purpose of this chapter is to establish
minimum means of egress regulations for qualified historical
buildings or properties. The CHBC requires enforcing agen-
cies to accept reasonably equivalent alternatives to the means
of egress requirements in the regular code.
8-501.2 Intent. The intent of these regulations is to provide an
adequate means of egress.
8-501.3 Scope. Every qualified historical building or portion
thereof shall be provided with exits as required by the CHBC
when required by the provisions of Section 8-102.
SECTION 8-502
GENERAL
8-502.1 General. The enforcing agency shall grant reasonable
exceptions to the specific provisions of applicable egress regu-
lations where such exceptions will not adversely affect life
safety.
8-502.2. Existing door openings and corridor widths of less
than dimensions required by regular code shall be permitted
where there is sufficient width and height for the occupants to
pass through the opening or traverse the exit.
8-502.3 Stairs. Existing stairs having risers and treads or
width at variance with the regular code are allowed if deter-
mined by the enforcing agency to not constitute a distinct haz-
ard. Handrails with nonconforming grip size or extensions are
allowed if determined by the enforcing agency to not constitute
a distinct hazard.
8-502,4 Main entry doors. The front or main entry doors
need not be rehung to swing in the direction of exit travel, pro-
vided other means or conditions of exiting, as necessary to
serve the total occupant load, are provided.
8-502.5 Existing fire escapes. Existing previously approved
fu*e escapes and fire escape ladders shall be acceptable as one
of the required means of egress, provided they extend to the
ground and are easily negotiated, adequately signed and in
good working order. Access shall be by an opening having a
minimum width of 29 inches (737mm) when open with a sill
no more than 30 inches (762mm) above the adjacent floor,
landing or approved step.
8-502.6 New fire escapes and fire escape ladders. New fire
escapes and fire escape ladders which comply with this section
shall be acceptable as one of the required means of egress. New
fire escapes and new fire escape ladders shall comply with the
following:
1 . Access from a corridor shall not be through an interven-
ing room.
2. All openings within 10 feet (3048 mm) shall be pro-
tected by three-fourths-hour fire assemblies. When
located within a recess or vestibule, adjacent enclosure
walls shall be of not less than one-hour fire-resistive
construction.
3. Egress from the building shall be by a clear opening
having a minimum dimension of not less than 29 inches
(737 mm). Such openings shall be openable from the
inside without the use of a key or special knowledge or
effort. The sill of an opening giving access shall not be
more than 30 inches (737 mm) above the floor, step or
landing of the building or balcony.
4. Fire escape stairways and balconies shall support the
dead load plus a live load of not less than 100 pounds
per square foot (4.79 kN/m^) and shall be provided with
a top and intermediate handrail on each side. The pitch
of the stairway shall not exceed 72 degrees with a mini-
mum width of 18 inches (457 mm). Treads shall not be
less than 4 inches (102 mm) in width, and the rise
between treads shall not exceed 10 inches (254 mm).
All stair and balcony railings shall support a horizontal
force of not less than 50 pounds per lineal foot (729.5
N/m^) of railing.
5. Balconies shall not be less than 44 inches (1118 mm) in
width with no floor opening other than the stairway
opening greater than Vg inch (15.9 mm) in width. Stair-
way openings in such balconies shall not be less than 22
inches by 44 inches (559 by 1 1 18 mm). The balustrade
of each balcony shall not be less than 36 inches (914
mm) high with not more than 9 inches (287 mm)
between balusters.
6. Fire escapes shall extend to the roof or provide an
approved gooseneck ladder between the top floor land-
ing and the roof when serving buildings four or more
stories in height having roofs with less than 4 units ver-
tical in 12 units horizontal (33.3 percent slope). Fire
escape ladders shall be designed and connected to the
building to withstand a horizontal force of 100 pounds
(445 N) placed anywhere on the rung. All ladders shall
be at least 15 inches (381 mm) wide, located within 12
inches (305 mm) of the building. Ladder rungs shall be
V4 inch (19.1 mm) in diameter and shall be located 12
inches (305 mm) on center. Openings for roof access
ladders through cornices and similar projections shall
have minimum dimensions of 30 inches by 33 inches
(762 by 838 mm).
The length of fire escapes and exit ladder devices
shall be limited to that approved by the building offi-
cial based on products listed by a recognized testing
laboratory,
7. The lowest balcony shall not be more than 1 8 feet (5486
mm) from the ground. Fire escapes shall extend to the
ground or be provided with counterbalanced stairs
reaching to the ground.
2010 CALIFORNIA HISTORICAL BUILDING CODE
MEANS OF EGRESS
8. Fire escapes shall not take the place of stairways
required by the codes under which the building was
constructed.
9. Fire escapes shall be kept clear and unobstructed at all
times and maintained in good working order.
SECTION 8-503
ESCAPE OR RESCUE WINDOWS AND DOORS
Basements in dwelling units and every sleeping room below
the fourth floor shall have at least one openable window or door
approved for emergency escape which shall open directly into a
public street, public way, yard or exit court. Escape or rescue
windows or doors shall have a minimum clear area of 3.3
square feet (0.31 m^) and a minimum width or height dimen-
sion of 18 inches (457 mm) and be operable from the inside to
provide a full, clear opening without the use of special tools.
SECTION 8-504
RAILINGS AND GUARDRAILS
The height of railings and guard railings and the spacing of bal-
usters may continue in their historical height and spacing
unless a distinct hazard has been identified or created by a
change in use or occupancy.
10 201 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-6
ACCESSIBILITY
SECTION 8-601
PURPOSE, INTENT AND SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alter-
native regulations to facilitate access and use by persons with
disabilities to and throughout faciUties designated as qualified
historical buildings or properties. These regulations require
enforcing agencies to accept alternatives to regular code when
dealing with qualified historical buildings or properties.
8-601.2 Intent. The intent of this chapter is to preserve the
integrity of qualified historical buildings and properties while
providing access to and use by persons with disabilities.
8-601.3 Scope. The CHBC shall apply to every qualified his-
torical building or property that is required to provide access to
persons with disabilities.
1 . Provisions of this chapter do not apply to new construc-
tion or reconstruction/replicas of historical buildings.
2. Where provisions of this chapter apply to alteration of
qualified historical buildings or properties, alteration is
defined in California Building Code (CBC), Chapter 2,
Definitions and Abbreviations. 202 - A. Alter or Alter-
ation.
8-601.4 General application. The provisions in the CHBC
apply to local, state and federal governments (Title II entities);
alteration of commercial facilities and places of public accom-
modation (Title III entities); and barrier removal in commercial
facilities and places of public accommodation (Title III enti-
ties). Except as noted in this chapter.
SECTION 8-602
BASIC PROVISIONS
8-602.1 Regular code. The regular code for access for people
with disabihties (Title 24, Part 2, Vol. 1, Chapter 1 IB) shall be
applied to qualified historical buildings or properties unless
strict compliance with the regular code will threaten or destroy
the historical significance or character-defining features of the
building or property.
8-602.2 Alternative provisions. If the historical significance
or character-defining features are threatened, alternative provi-
sions for access may be appUed pursuant to this chapter, pro-
vided the following conditions are met:
1. These provisions shall be applied only on an
item-by-item or a case-by-case basis,
2. Documentation is provided, including meeting minutes
or letters, stating the reasons for the application of the
alternative provisions. Such documentation shall be
retained in the permanent file of the enforcing agency.
SECTION 8-603
ALTERNATIVES
8-603.1 Alternative minimum standards. The alternative
minimum standards for alterations of qualified historical build-
ings or facilities are contained in Section 4. 1 .7(3) of ADA Stan-
dards for Accessible Design, as incorporated and set forth in
federal regulation 28 C.F.R. Pt. 36.
8-603.2 Entry. These alternatives do not allow exceptions for
the requirement of level landings in front of doors, except as
provided in Section 8-603.4.
1 . Access to any entrance used by the general public and
no further than 200 feet (60 960 mm) from the primary
entrance.
2. Access at any entrance not used by the general public
but open and unlocked with directional signs at the pri-
mary entrance and as close as possible to, but no further
than 200 feet (60 960 mm) from, the primary entrance.
3. The accessible entrance shall have a notification sys-
tem. Where security is a problem, remote monitoring
may be used.
8-603.3 Doors. Alternatives listed in order of priority are:
1. Single-leaf door which provides a minimum 30 inches
(762 mm) of clear opening.
2. Single-leaf door which provides a minimum 29V2
inches (749 mm) clear opening
3. Double door, one leaf of which provides a minimum
297^ inches (749 mm) clear opening,
4. Double doors operable with a power-assist device to
provide a minimum 2972 inches (749 mm) clear open-
ing when both doors are in the open position.
8-603.4 Power-assisted doors. Power-assisted door or doors
may be considered an equivalent alternative to level landings,
strikeside clearance and door-opening forces required by the
regular code.
8-603.5 Toilet rooms. In lieu of separate-gender toilet facili-
ties as required in the regular code, an accessible unisex toilet
facility may be designated.
8-603.6 Exterior and interior ramps and lifts. Alternatives
listed in order of priority are:
1. A lift or a ramp of greater than standard slope but no
greater than 1:10, for horizontal distances not to exceed
5 feet (1525 mm). Signs shall be posted at upper and
lower levels to indicate steepness of the slope.
2. Access by ramps of 1 : 6 slope for horizontal distance not
to exceed 13 inches (330 mm). Signs shall be posted at
upper and lower levels to indicate steepness of the
slope.
2010 CALIFORNIA HISTORICAL BUILDING CODE
11
ACCESSIBILITY
SECTION 8-604
EQUIVALENT FACILITATION
Use of other designs and technologies, or deviation from par-
ticular technical and scoping requirements, are permitted if the
application of the alternative provisions contained in Section
8-603 would threaten or destroy the historical significance
or character-defining features of the historical building or
property.
1. Such alternatives shall be applied only on an
item-by-item or a case-by-case basis.
2. Access provided by experiences, services, functions,
materials and resources through methods including, but
not limited to, maps, plans, videos, virtual reality and
related equipment, at accessible levels. The alternative
design and/or technologies used will provide substan-
tially equivalent or greater accessibility to, and usability
of, the facility.
3. The official charged with the enforcement of the stan-
dards shall document the reasons for the application of
the design and/or technologies and their effect on the
historical significance or character-defining features.
Such documentation shall be in accordance with Sec-
tion 8-602.2, Item 2, and shall include the opinion and
comments of state or local accessibility officials, and
the opinion and comments of representative local
groups of people with disabilities. Such documentation
shall be retained in the permanent file of the enforcing
agency. Copies of the required documentation should
be available at the facility upon request.
Note: For commercial facilities and places of public
accommodation (Title III entities).
Equivalent facilitation for an element of a building or prop-
erty when applied as a waiver of an ADA accessibility require-
ment will not be entitled to the Federal Department of Justice
certification of this code as rebuttable evidence of comphance
for that element.
12 2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-7
STRUCTURAL REGULATIONS
SECTION 8-701
PURPOSE, INTENT AND SCOPE
8-701.1 Purpose. The purpose of the CHBC is to provide alter-
native regulations for the structural safety of buildings desig-
nated as qualified historical buildings or properties. The CHBC
requires enforcing agencies to accept any reasonably equiva-
lent alternatives to the regular code when deaUng with qudified
historical buildings or properties.
8-701.2 Intent. The intent of the CHBC is to encourage the
preservation of qualified historical buildings or properties
while providing a reasonable level of structural safety for occu-
pants and the public at large through the application of the
CHBC.
8-701.3 Application. The alternative structural regulations
provided by Section 8-705 are to be applied in conjunction with
the regular code whenever a structural upgrade or reconstruc-
tion is undertaken for qualified historical buildings or proper-
ties.
SECTION 8-702
GENERAL
8-702.1 The CHBC shall not be construed to allow the
enforcing agency to approve or permit a lower level of safety of
structural design and construction than that which is reason-
ably equivalent to the regular code provisions in occupancies
which are critical to the safety and welfare of the public at large,
including, but not limited to, public and private schools, hospi-
tals, municipal police and fire stations and essential services
facilities.
8-702.2 Nothing in these regulations shall prevent voluntary
and partial seismic upgrades when it is demonstrated that such
upgrades will improve life safety and when a full upgrade
would not otherwise be required.
SECTION 8-703
STRUCTURAL SURVEY
8-703.1 Scope. When a structure or portion of a structure is to
be evaluated for structural capacity under the CHBC, it shall be
surveyed for structural conditions by an architect or engineer
knowledgeable in historical structures. The survey shall evalu-
ate deterioration or signs of distress. The survey shall deter-
mine the details of the structural framing and the system for
resistance of gravity and lateral loads. Details, reinforcement
and anchorage of structural systems and veneers shall be deter-
mined and documented where these members are relied on for
seismic resistance.
8-703.2 The results of the survey shall be utilized for evaluating
the structural capacity and for designing modifications to the
structural system to reach compliance with this code.
8-703.3 Historical records. Past historical records of the
structure or similar structures may be used in the evaluation,
including the effects of subsequent alterations.
SECTION 8-704
NONHISTORICAL ADDITIONS AND
NONHISTORICAL ALTERATIONS
8-704.1 New nonhistorical additions and nonhistorical alter-
ations which are structurally separated from an existing histori-
cal structure shall comply with regular code requirements.
8-704.2 New nonhistorical additions which impose vertical or
lateral loads on an existing structure shall not be permitted
unless the affected part of the supporting structure is evaluated
and strengthened, if necessary, to meet regular code require-
ments.
Note: For use of archaic materials, see Chapter 8-8.
SECTION 8-705
STRUCTURAL REGULATIONS
8-705.1 Gravity loads. The capacity of the structure to resist
gravity loads shall be evaluated and the structure strengthened
as necessary. The evaluation shall include all parts of the load
path. Where no distress is evident, and a complete load path is
present, the structure may be assumed adequate by having
withstood the test of time if anticipated dead and live loads will
not exceed those historically present.
8-705.2 Wind and seismic loads. The ability of the structure to
resist wind and seismic loads shall be evaluated. The evaluation
shall be based on the requirements of Section 8-706.
8.705.2.1 Any unsafe conditions in the lateral-load-resisting
system shall be corrected, or alternative resistance shall be pro-
vided. Additional resistance shall be provided to meet the mini-
mum requirements of this code.
8.705.2.2 The architect or engineer shall consider additional
measures with minimal loss of, and impact to, historical mate-
rials which will reduce damage and needed repairs in future
earthquakes to better preserve the historical structure in
perpetuity. These additional measures shall be presented to
the owner for consideration as part of the rehabilitation or
restoration.
SECTION 8-706
LATERAL LOAD REGULATIONS
8-706.1 Lateral loads. The forces used to evaluate the struc-
ture for resistance to wind and seismic loads need not exceed
0.75 times the seismic forces prescribed by the 1995 edition of
the California Building Code (CBC). The seismic forces may
be computed based on the Rw values tabulated in the regular
code for similar lateral-force-resisting systems. All deviations
2010 CALIFORNIA HISTORICAL BUILDING CODE
13
STRUCTURAL REGULATIONS
of the detailing provisions of the lateral-force-resisting sys-
tems shall be evaluated for stability and the ability to maintain
load-carrying capacity at increased lateral loads.
Unreinforced masonry bearing wall buildings shall comply
with Appendix Chapter 1 of the Uniform Code for Building
Conservation^^ (UCBC™), 1994 edition, and as modified by
this code. Reasonably equivalent standards may be used on a
case-by-case basis when approved by the authority having
jurisdiction.
8-706.2 Existing building performance. The seismic resis-
tance may be based upon the ultimate capacity of the structure
to perform, giving due consideration to ductility and reserve
strength of the lateral-force-resisting system and materials
while maintaining a reasonable factor of safety. Broad
judgment may be exercised regarding the strength and perfor-
mance of materials not recognized by regular code require-
ments. (See Chapter 8-8, Archaic Materials and Methods of
Construction.)
8-706.2.1A11 structural materials or members that do not
comply with detailing and proportioning requirements of
the regular code shall be evaluated for potential seismic per-
formance and the consequence of noncompliance. All
members which might fail and lead to possible collapse, or
threaten life safety, when subjected to seismic demands in
excess of those prescribed in Section 8-706.1, shall be
judged unacceptable, and appropriate structural strengthen-
ing shall be developed. Anchorages for veneers and decora-
tive ornamentation shall be included in this evaluation.
8-706.3 Load path. A complete and continuous load path,
including connections, from every part or portion of the struc-
ture to the ground shall be provided for the required forces. It
shall be verified that the structure is adequately tied together to
perform as a unit when subjected to earthquake forces.
8-706.4 Parapets. Parapets and exterior decoration shall be
investigated for conformance with regular code requirements
for anchorage and ability to resist prescribed seismic forces.
An exception to regular code requirements shall be permit-
ted for those parapets and decorations which are judged not to
be a hazard to life safety.
8-706.5 Nonstructural features. Nonstructural features of
historical structure, such as exterior veneer, cornices and deco-
rations, which might fall and create a life- safety hazard in an
earthquake, shall be investigated. Their ability to resist seismic
forces shall be verified, or the feature shall be strengthened.
8-706.5.1 Partitions and ceilings of corridors and stairways
serving an occupant load of 30 or more shall be investigated
to determine their ability to remain in place when the build-
ing is subjected to earthquake forces.
14
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-8
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
SECTION 8-801
PURPOSE, INTENT AND SCOPE
8-801.1 Purpose. The purpose of the CHBC is to provide regu-
lations for the use of historical methods and materials of con-
struction that are at variance with regular code requirements or
are not otherwise codified, in buildings or structures desig-
nated as qualified historical buildings or properties. The CHBC
require enforcing agencies to accept any reasonably equivalent
alternatives to the regular code when dealing with qualified his-
torical buildings or properties.
8-801.2 Intent. It is the intent of the CHBC to provide for the
use of historical methods and materials of construction that are
at variance with specific code requirements or are not other-
wise codified.
8-801.3 Scope. Any construction type or material that is, or
was, part of the historical fabric of a structure is covered by this
chapter. Archaic materials and methods of construction present
in a historical structure may remain or be reinstalled or be
installed with new materials of the same class to match existing
conditions.
SECTION 8-802
GENERAL ENGINEERING APPROACHES
Allowable stresses or ultimate strengths for archaic materials
shall be assigned based upon similar conventional codified
materials, or on tests as hereinafter indicated. The archaic
materials and methods of construction shall be thoroughly
investigated for their details of construction in accordance with
Section 8-703, Testing shall be performed when applicable to
evaluate existing conditions. The architect or structural engi-
neer in responsible charge of the project shall assign allowable
stresses or ultimate strength values to archaic materials. Such
assigned allowable stresses, or ultimate strength values, shall
not be greater than those provided for in the following sections
without adequate testing, and shall be subject to the concur-
rence of the enforcing agency.
SECTION 8-803
NONSTRUCTURAL ARCHAIC MATERIALS
Where nonstructural historical materials exist in uses which do
not meet the requirements of the regular code, their continued
use is allowed by this code, provided that any public health and
life-safety hazards are mitigated subject to the concurrence of
the enforcing agency.
SECTION 8-804
ALLOWABLE CONDITIONS FOR SPECIFIC
MATERIALS
Archaic materials which exist and are to remain in historical
structures shall be evaluated for their condition and for loads
required by this code. The structural survey required in Section
8-703 of this code shall document existing conditions, rein-
forcement, anchorage, deterioration and other factors pertinent
to establishing allowable stresses and adequacy of the archaic
materials. The remaining portion of this chapter provides addi-
tional specific requirements for commonly encountered
archaic materials.
SECTION 8-805
MASONRY
For adobe, see Section 8-806.
8-805.1 Existing solid masonry. Existing solid masonry walls
of any type, except adobe, may be allowed, without testing, a
maximum value of nine pounds per square inch (62.1 kPa) in
shear where there is a qualifying statement by the architect or
engineer that an inspection has been made, that mortar joints
are filled and that both brick and mortar are reasonably good.
The allowable shear stress above applies to unreinforced
masonry, except adobe, where the maximum ratio of unsup-
ported height or length to thickness does not exceed 12, and
where minimum quality mortar is used or exists. Wall height or
length is measured to supporting or resisting elements that are
at least twice as stiff as the tributary wall. Stiffness is based on
the gross section. Allowable shear stress may be increased by
the addition of 10 percent of the axial direct stress due to the
weight of the wall directly above. Higher-quality mortar may
provide a greater shear value and shall be tested in accordance
with UBC Standard 21-6.
8-805.2 Stone masonry.
8-805.2.1 Solid-backed stone masonry. Stone masonry
solidly backed with brick masonry shall be treated as solid
brick masonry as described in Section 8-805.1 and in the
UCBC, provided representative testing and inspection veri-
fies solid collar joints between stone and brick and that a
reasonable number of stones lap with the brick wythes as
headers or that steel anchors are present. Solid stone
masonry where the wythes of stone effectively overlap to
provide the equivalent header courses may also be treated as
solid brick masonry.
8-805.2.2 Independent wythe stone masonry. Stone
masonry with independent face wythes may be treated as
sohd brick masonry as described in Section 8-805. 1 and the
UCBC, provided representative testing and inspection ver-
ify that the core is essentially solid in the masonry wall and
that steel ties are epoxied in drilled holes between outer
stone wythes at floors, roof and not to exceed 4 feet (1219
mm) on center in each direction, between floors and roof.
8-805.2.3 Testing of stone masonry. Testing of stone
masonry shall be similar to UBC Standard 21-6, except that
representative stones which are not interlocked shall be
2010 CALIFORNIA HISTORICAL BUILDING CODE
15
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
pulled outward from the wall and shear area appropriately
calculated after the test.
8-805.3 Reconstructed walls. Totally reconstructed walls uti-
lizing original brick or masonry, constructed similar to origi-
nal, shall be constructed in accordance with the regular code.
Repairs or infills may be constructed in a similar manner to the
original walls without conforming to the regular code.
SECTION 8-806
ADOBE
8-806.1 General. Unbumed clay masonry may be constructed,
reconstructed, stabilized or rehabilitated subject to this chapter.
Alternative approaches which provide an equivalent or greater
level of safety may be used, subject to the concurrence of the
enforcing agency.
8-806.2 Protection. Provisions shall be made to protect adobe
structures from moisture and deterioration. The unreinforced
adobe shall be maintained in reasonably good condition. Par-
ticular attention shall be given to moisture content of adobe
walls. Unmaintained or unstabilized walls or ruins shall be
evaluated for safety based on their condition and stabiHty.
Additional safety measures may be required subject to the con-
currence of the enforcing agency.
8-806.3 Requirements. Unreinforced new or existing adobe
walls shall meet the following requirements. Existing sod or
rammed earth walls shall be considered similar to the extent
these provisions apply. Where existing dimensions do not meet
these conditions, additional strengthening measures may be
required.
1. One-story adobe load-bearing walls shall not exceed a
height-to-thickness ratio of 6.
2. Two-story adobe buildings or structures' height-
to-thickness wall ratio shall not exceed 5 at the ground
floor and 6 at the second floor, and shall be measured at
floor-to-floor height when the second floor and attic
ceiling/roof are connected to the wall as described
below.
3. Nonload-bearing adobe partitions and gable end walls
shall be evaluated for stability and anchored against
out-of-plane failure.
4. A bond beam or equivalent structural element shall be
provided at the top of all adobe walls, and for two-story
buildings at the second floor. The size and configura-
tion of the bond beam shall be designed in each case to
meet the requirements of the existing conditions and
provide an effective brace for the wall, to tie the build-
ing together and connect the wall to the floor or roof.
8-806.4 Repair or reconstruction. Repair or reconstruction of
wall area may utilize unstabilized brick or adobe masonry
designed to be compatible with the constituents of the existing
adobe materials.
8-806.5 Shear values. Existing adobe may be allowed a maxi-
mum value of four pounds per square inch (27.6 kPa) for shear,
with no increase for lateral forces.
8-806.6 Mortar. Mortar may be of the same soil composition
as that used in the existing wall, or in new walls as necessary to
be compatible with the adobe brick.
SECTION 8-807
WOOD
8-807.1 Existing wood diaphragms or walls. Existing wood
diaphragms or walls of straight or diagonal sheathing shall be
assigned shear resistance values appropriate with the fasteners
and materials functioning in conjunction with the sheathing.
The structural survey shall determine fastener details and spac-
ings and verify a load path through floor construction. Shear
values of Tables 8-8-A and 8-8-B.
8-807.2 Wood lath and plaster. Wood lath and plaster walls
and ceilings may be utilized using the shear values referenced
in Section 8-807.1.
8-807.3 Existing wood framing. Existing wood framing
members may be assigned allowable stresses consistent with
codes in effect at the time of construction. Existing or new
replacement wood framing may be of archaic types originally
used if properly researched, such as balloon and single wall.
Wood joints such as dovetail and mortise and tenon types may
be used structurally, provided they are well made. Lumber
selected for use and type need not bear grade marks, and
greater or lesser species such as low-level pine and fir, box-
wood and indigenous hardwoods and other variations may be
used for specific conditions where they were or would have
been used.
Wood fasteners such as square or cut nails may be used with
a maximum increase of 50 percent over wire nails for shear.
SECTION 8-808
CONCRETE
8-808.1 Materials. Natural cement concrete, unreinforced
rubble concrete and similar materials may be utilized wherever
that material is used historically. Concrete of low strength and
with less reinforcement than required by the regular code may
remain in place. The architect or engineer shall assign appro-
priate values of strength based on testing of samples of the
materials. Bond and development lengths shall be determined
based on historical information or tests.
8-808.2 Detailing. The architect or engineer shall carefully
evaluate all detailing provisions of the regular code which are
not met and shall consider the implications of these variations
on the ultimate performance of the structure, giving due con-
sideration to ductility and reserve strength.
SECTION 8-809
STEEL AND IRON
The hand-built, untested use of wrought or black iron, the use
of cast iron or grey iron, and the myriad of joining methods that
are not specifically allowed by code may be used wherever
applicable and wherever they have proven their worth under the
considerable span of years involved with most qualified histor-
ical structures. Uplift capacity should be evaluated and
16
2010 CALIFORNIA HISTORICAL BUILDING CODE
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
strengthened where necessary. Fixed conditions or midheight
lateral loads on cast iron columns that could cause failure
should be taken into account. Existing structural wrought,
forged steel or grey iron may be assigned the maximum work-
ing stress prevalent at the time of original construction.
SECTION 8-810
HOLLOW CLAY TILE
The historical performance of hollow clay tile in past earth-
quakes shall be carefully considered in evaluating walls of
hollow clay tile construction. Hollow clay tile bearing walls
shall be evaluated and strengthened as appropriate for lateral
loads and their ability to maintain support of gravity loads.
Suitable protective measures shall be provided to prevent
blockage of exit stairways, stairway enclosures, exit ways and
public ways as a result of an earthquake.
SECTION 8-811
VENEERS
8-811.1 Terra cotta and stone. Terra cotta, cast stone and nat-
ural stone veneers shall be investigated for the presence of suit-
able anchorage. Steel anchors shall be investigated for deterio-
ration or corrosion. New or supplemental anchorage shall be
provided as appropriate.
8-811.2 Anchorage. Brick veneer with mechanical anchorage
at spacings greater than required by the regular code may
remain, provided the anchorages have not corroded. Nail
strength in withdrawal in wood sheathing may be utilized to its
capacity in accordance with code values.
SECTION 8-812
GLASS AND GLAZING
8-812.1 Glazing subject to human impact. Historical glazing
material located in areas subject to human impact may be
approved subject to the concurrence of the enforcing agency
when alternative protective measures are provided. These mea-
sures may include, but not be limited to, additional glazing pan-
els, protective film, protective guards or systems, and devices
or signs which would provide adequate pubUc safety.
8-812.2 Glazing in fire-rated systems. See Section 8-402.3.
TABLE8-8A
ALLOWABLE VALUES FOR EXISTING MATERIALS
EXISTING MATERIALS OR CONFIGURATIONS OF MATERIALS^
ALLOWABLE VALUES
x1 4.594 for N/m
L Horizontal diaphragms^
1 . 1 Roofs with straight sheathing and roofing applied directly
to the sheathing
1 .2 Roofs with diagonal sheathing and roofing apphed
directly to the sheathing
1 .3 Floors with straight tongue-and-groove sheathing
1.4 Floors with straight sheathing and finished wood flooring
with board edges offset or perpendicular
1.5 Floors with diagonal sheathing and finished
100 lbs per foot for seismic shear
250 lbs per foot for seismic shear
100 lbs per foot for seismic shear
500 lbs per foot for seismic shear
600 lbs per foot for seismic shear
2. Crosswalls''
2. 1 Plaster on wood or metal lath
2.2 Plaster on gypsum lath
2.3 Gypsum wallboard, unblocked edges
2.4 Gypsum wallboard, blocked edges
Per side: 200 lbs per foot for seismic shear
175 lbs per foot for seismic shear
75 lbs per foot for seismic shear
125 lbs per foot for seismic shear
Existing footings, wood framing, structural steel and reinforced
steel
3. 1 Plain concrete footings
3.2 Douglas fir wood
3.3 Reinforcing steel
3.4 Structural steel
/' = 1,500 psi (10.34 MPa) unless otherwise shown by tests'"
Allowable stress same as D.F. No. I'*
/ = 18,000 lbs per square inch (124.1 N/mm^) maximum
I = 200,00 lbs per square inch (137.9 N/mm') maximum
'Material must be sound and in good condition.
^A one-third increase in allowable stress is not allowed.
^Shear values of these materials may be combined, except the total combined value shall not exceed 300 pounds per
foot (4380 N/m).
"Stresses given may be increased for combinations of loads as specified in the regular code.
2010 CALIFORNIA HISTORICAL BUILDING CODE
17
ARCHAIC MATERIALS AND METHODS OF CONSTRUCTION
TABLE 8-8B
ALLOWABLE VALUES OF NEW MATERIALS USED IN CONNECTION WITH EXISTING CONSTRUCTION
NEW MATERIALS OR CONFIGURATIONS OF MATERIALS
ALLOWABLE VALUES^
1. Horizontal diaphragms^
1 . 1 Plywood sheathing nailed directly over existing straight
sheathing with ends of plywood sheets bearing on joists or
rafters and edges of plywood located on center of
individual sheathing boards
1.2 Plywood sheathing nailed directly over existing diagonal
sheathing with ends of plywood sheets bearing on joists or
rafters
1 .3 Plywood sheathing nailed directly over existing straight or
diagonal sheathing with ends of plywood sheets bearing
on joists or rafters with edges of plywood located over
new blocking and nailed to provide a minimum nail
penetration into framing and blocking of iVg inch
(41 mm)
225 lbs per foot (3283 N/m)
375 lbs per foot (5473 N/m)
75 percent of the values specified in the regular code
2. Shear walls: (general procedure)
Plywood sheathing applied directly over wood studs. No value
shall be given to plywood applied over existing plaster or wood
sheathing
100 percent of the value specified in the regular code for shear
walls
3. Crosswalls: (special procedure only)
3.1 Plywood sheathing applied directly over wood studs. No
value shall be given to plywood applied over existing
plaster or wood sheathing
3.2 Dry wall or plaster applied directly over wood studs
3.3 Dry wall or plaster applied to sheathing over existing wood
studs
133 percent of the value specified in the regular code for shear
walls
100 percent of the values in the regular code
The values specified in the regular code reduced as noted.^ (UBC
Table 25-1, Footnote 1)
4. Tension bolts
4. 1 Bolts extending entirely through unreinforced masonry
walls secured with bearing plates on far side of a
three-wythe-minimum wall with at least 30 square inches
(19 350 mm') of area''
4.2 Bolts extending to the exterior face of the wall with a
2y2-inch (63.5 mm) round plate under the head and drilled
at an angle of 22^2 degrees to the horizontal, installed as
specified for shear bolts*'^'^
1,800 lbs (8006 N) per bolt'
900 lbs (4003 N) per bolt for two-wythe walls'
1,200 lbs (5338 N) per bolt
5. Shear bolts
Bolts embedded a minimum of 8 inches (203 mm) into
unreinforced masonry walls and centered in a
272-inch-diameter (63.5 mm) hole filled with dry-pack or
nonshrink grout. Through bolts with first 8 inches (203 mm) as
noted above and embedded bolts as noted in Item 4,2^"^
7, inch (12.7 mm) diameter = 350 lbs (1557 N)'
% inch (15.9 mm) diameter = 500 lbs (2224 N)'
X inch (19 mm) diameter = 750 lbs (3336 N)'
6. Infilled walls
Reinforced masonry infilled openings in existing unreinforced
masonry walls. Provide keys or dowels to match reinforcing.
Same as values specified for unreinforced masonry walls
7. Reinforced masonry
Masonry piers and walls reinforced per the regular code
Same as values specified in the regular code^
8. Reinforced concrete
Concrete footings, walls and piers reinforced as specified in the
regular code and designed for tributary loads
Same values as specified in the regular code*
'a one-third Increase in allowable stress is not allowed, except as noted.
Values and limitations are for nailed plywood. Higher values may be used for other fastening systems such as wood screws or staples when approved by the enforcing
authority.
^In addition to existing sheathing value.
"^Bolts to be Vj-inch (12.7 mm) minimum diameter.
^Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tools shall not be used for drilling holes or tightening anchors and shear bolt nuts.
^Other bolt sizes, values and installation methods may be used, provided a testing program is conducted in accordance with regular code standards. Bolt spacing shall
not exceed 6 feet (1830 mm) on center and shall not be less than 12 inches (305) mm) on center
^Embedded bolts to be tested as specified in regular code standards.
^Stresses given may be increased for combinations of loads as specified in the regular code.
18
2010 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-9
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
SECTION 8-901
PURPOSE, INTENT AND SCOPE
8-901.1 Purpose. The purpose of the CHBC is to provide regu-
lations for the mechanical, plumbing and electrical systems of
buildings designated as qualified historical buildings or prop-
erties. The CHBC requires enforcing agencies to accept any
reasonable equivalent solutions to the regular code when deal-
ing with qualified historical buildings or properties.
8-901.2 Intent. The intent of the CHBC is to preserve the
integrity of qualified historical buildings or properties while
providing a reasonable level of protection from fire, health and
life-safety hazards (hereinafter referred to as safety hazards)
for the building occupants.
8-901.3 Scope. The CHBC shall be applied in conjunction with
the regular code whenever compliance with the regular code is
required for qualified historical buildings or properties.
8-901.4 Safety hazard. No person shall permit any safety haz-
ard to exist on premises under their control, or fail to take
inmiediate action to abate such hazard. Existing systems which
constitute a safety hazard when operational may remain in
place, provided they are completely and permanently rendered
inoperative. Safety hazards created by inoperative systems
shall not be permitted to exist. Requirements of the regular
code concerning general regulations shall be complied with,
except that the enforcing agency shall accept solutions which
do not cause a safety hazard.
8-901.5 Energy conservation. Qualified historical buildings
or properties covered by this part are exempted from compli-
ance with energy conservation standards. When new
nonhistorical lighting and space conditioning system compo-
nents, devices, appliances and equipment are installed, they
shall comply with the requirements of Title 24, Part 6, The Cal-
ifornia Energy Code, except where the historical significance
or character-defining features are threatened.
SECTION 8-902
MECHANICAL
8-902.1 General. Mechanical systems shall comply with the
regular code unless otherwise modified by this chapter.
8-902.1.1 The provisions of the CHBC shall apply to the
acceptance, location, installation, alteration, repair, reloca-
tion, replacement or addition of any heating, ventilating, air
conditioning, domestic incinerators, kilns or miscellaneous
heat-producing appliances or equipment within or attached
to a historical building.
8-902.1.2 Existing systems which do not, in the opinion of
the enforcing agency, constitute a safety hazard may remain
in use.
8-902.1.3 The enforcing agency may approve any alterna-
tive to the CHBC which would achieve equivalent life
safety.
8-902.2 Heating facilities. All dwelling-type occupancies
covered under this chapter shall be provided with heating facil-
ities. Wood-burning or pellet stoves or fireplaces may be
acceptable as heating facilities.
8-902.3 Fuel oil piping and tanks. Fuel oil piping and tanks
shall comply with regular code requirements except that the
enforcing agency may waive such requirements where the
lack of compliance does not create a safety or environmental
hazard.
8-902.4 Heat-producing and cooling equipment. Heat-pro-
ducing and cooling equipment shall comply with the regular
code requirements governing equipment safety, except that the
enforcing agency may accept alternatives which do not create a
safety hazard.
8-902.5 Combustion air.
8-902.5.1 All fuel-burning appliances and equipment shall
be provided a sufficient supply of air for proper fuel com-
bustion, ventilation and draft hood dilution.
8-902.5.2 The enforcing agency may require operational
tests for combustion air systems which do not comply with
appUcable requirements of the regular code.
8-902.6 Venting of appliances.
8-902.6.1 Every appliance required to be vented shall be
connected to an approved venting system. Venting systems
shall develop a positive flow adequate to convey all combus-
tion products to the outside atmosphere.
8-902.6.2 Masonry chimneys in structurally sound condi-
tion may remain in use for all fuel-burning appliances, pro-
vided the flue is evaluated and documentation provided that
the masonry and grout are in good condition. Terra cotta
chimneys and Type C metallic vents installed in concealed
spaces shall not remain in use unless otherwise mitigated
and approved on a case-by-case basis.
8-902.6.3 The enforcing agency may require operational
tests for venting systems which do not comply with applica-
ble requirements of the regular code.
8-902.7 Ducts.
8-902.7.1 New ducts shall be constructed and installed in
accordance with applicable requirements of the regular
code.
8-902.7.2 Existing duct systems which do not comply with
applicable requirements of the regular code and do not, in
the opinion of the enforcing agency, constitute a safety or
health hazard may remain in use.
8-902.8 Ventilating systems.
2010 CALIFORNIA HISTORICAL BUILDING CODE
19
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
8-902.8.1 Ventilating systems shall be installed so that no
safety hazard is created.
8-902.8.2 Grease hoods and grease hood exhaust systems
shall be furnished and installed in accordance with applica-
ble requirements of the regular code. Existing systems
which are altered shall comply with the regular code.
8-902.9 Miscellaneous equipment requirements.
8-902.9.1 The following appliances and equipment shall be
installed so that no safety hazard is created: warm air fur-
naces, space heating equipment, vented decorative appH-
ances, floor furnaces, vented wall furnaces, unit heaters,
room heaters, absorption units, refrigeration equipment,
duct furnaces, infrared radiant heaters, domestic incinera-
tors, miscellaneous heat-producing appliances and water
heaters.
8-902.9.2 Storage- type water heaters shall be equipped with
a temperature- and pressure-relief valve in accordance with
applicable requirements of the regular code.
SECTION 8-903
PLUMBING
8-903.1 General. Plumbing systems shall comply with the reg-
ular code unless otherwise noted.
8-903.1.1 The provisions of the CHBC shall apply to the
acceptance, location, installation, alteration, repair, reloca-
tion, replacement or addition of any plumbing system or
equipment within or attached to a historical building.
8-903.1.2 Existing systems which do not, in the opinion of
the enforcing agency, constitute a safety hazard may remain
in use.
8-903.1.3 The enforcing agency may approve any alterna-
tive to these regulations which achieves reasonably equiva-
lent life safety.
8-903.2 Residential occupancies.
8-903.2.1 Where toilet facilities are provided, alternative
sewage disposal methods may be acceptable if approved by
the local health department. In hotels, where private facili-
ties are not provided, water closets at the ratio of one for
each 15 rooms may be acceptable.
8-903.2,2 Toilet facilities are not required to be on the same
floor or in the same building as sleeping rooms. Water-flush
toilets may be located in a building immediately adjacent to
the sleeping rooms. When alternative sewage disposal
methods are utilized, they shall be located a minimum dis-
tance from the sleeping rooms or other locations as
approved by the local health department.
8-903.2.3 Kitchen sinks shall be provided in all kitchens.
The sink and countertop may be of any smooth
nonabsorbent finish which can be maintained in a sanitary
condition.
8-903.2.4 Hand washing facilities shall be provided for each
dwelling unit and each hotel guest room. A basin and
pitcher may be acceptable as adequate hand washing
facilities.
8-903.2.5 Hot or cold running water is not required for each
plumbing fixture, provided a sufficient amount of water is
supplied to permit the fixture's normal operation,
8-903.2.6 Bathtubs and lavatories with filler spouts less than
1 inch (25.4 mm) above the fixture rim may remain in use,
provided there is an acceptable overflow below the rim.
8-903.2.7 Original or salvage water closets, urinals and
flushometer valves shall be permitted in qualified historical
buildings or properties. Historically accurate reproduction,
nonlow-consumption water closets, urinals and flushometer
valves shall be permitted except where historically accurate
fixtures that comply with the regular code are available.
8-903.3 Materials. New nonhistorical materials shall comply
with the regular code requirements. The enforcing agency shall
accept alternative materials which do not create a safety hazard
where their use is necessary to maintain the historical integrity
of the building.
8-903.4 Drainage and vent systems. Plumbing fixtures shall
be connected to an adequate drainage and vent system. The
enforcing agency may require operational tests for drainage
and vent systems which do not comply with applicable require-
ments of the regular code. Vent terminations may be installed in
any location which, in the opinion of the enforcing agency,
does not create a safety hazard.
8-903.5 Indirect and special vv^astes. Indirect and special
waste systems shall be installed so that no safety hazard is cre-
ated. Chemical or industrial liquid wastes which may detri-
mentally affect the sanitary sewer system shall be pretreated to
render them safe prior to discharge.
8-903.6 Traps and interceptors. Traps and interceptors shall
comply with the regular code requirements except that the
enforcing agency shall accept solutions which do not increase
the safety hazard. Properly maintained "S*' and drum traps may
remain in use.
8-903.7 Joints and connections.
8-903.7.1 Joints and connections in new plumbing systems
shall comply with applicable requirements of the regular
code.
8-903.7.2 Joints and connections in existing or restored sys-
tems may be of any type that does not create a safety hazard.
8-903.8 Water distribution. Plumbing fixtures shall be con-
nected to an adequate water distribution system. The enforcing
agency may require operational tests for water distribution sys-
tems which do not comply with applicable requirements of reg-
ular code. Prohibited (unlawful) connections and cross
connections shall not be permitted.
8-903.9 Building sewers and private sewage disposal sys-
tems. New building sewers and new private sewage disposal
systems shall comply with applicable requirements of the regu-
lar code.
8-903.10 Fuel-gas piping. Fuel-gas piping shall comply with
the regular code requirements except that the enforcing agency
shall accept solutions which do not increase the safety hazard.
20
2010 CALIFORNIA HISTORICAL BUILDING CODE
MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS
SECTION 8-904
ELECTRICAL
8-904.1 GeneraL Electrical systems shall comply with the
regular code unless otherwise permitted by this code, or
approved by the authority having jurisdiction.
8-904.1.1 The provisions of the CHBC shall apply to the
acceptance, location, installation, alteration, repair, reloca-
tion, replacement or addition of any electrical system or por-
tion thereof, the premise wiring, or equipment fixed in place
as related to restoration within or attached to a qualified his-
torical building or property.
8-904.1.2 Existing systems, wiring methods and electrical
equipment which do not, in the opinion of the enforcing
agency, constitute a safety hazard may remain in use.
8-904.1.3 The enforcing agency may approve any alterna-
tive to the CHBC which achieves equivalent safety.
8-904.1.4 Archaic methods that do not appear in present
codes may remain and may be extended if, in the opinion of
the enforcing agency, they constitute a safe installation.
8-904.2 Wiring methods.
8-904.2.1 Where existing branch circuits do not include an
equipment grounding conductor and, in the opinion of the
enforcing agency, it is impracticable to connect an equip-
ment grounding conductor to the grounding electrode sys-
tem, receptacle convenience outlets may remain the
nongrounding type.
8-904.2.2 Ground fault circuit interrupter (GFCI) protected
receptacles shall be installed where replacements are made
at receptacle outlets that are required to be so protected by
the regular code in effect at the time of replacement. Metal-
lic face plates shall either be grounded to the grounded
metal outlet box or be grounded to the grounding-type
device when used with devices supplied by branch circuits
without equipment grounding conductors.
8-904.2.3 Grounding-type receptacles shall not be used
without a grounding means in an existing receptacle outlet
unless GFCI protected. Existing nongrounding receptacles
shall be permitted to be replaced with nongrounding or
grounding-type receptacles where supplied through a
ground fault circuit interrupter.
8-904.2.4 Extensions of existing branch circuits without
equipment-grounding conductors shall be permitted to sup-
ply grounding-type devices only when the equipment
grounding conductor of the new extension is grounded to
any accessible point on the grounding electrode system.
8-904.2.5 Receptacle outlet spacing and other related dis-
tance requirements shall be waived or modified if deter-
mined to be impracticable by the enforcing agency.
8-904.2.6 For the replacement of lighting fixtures on an
existing nongrounded lighting outlet, or when extending an
existing nongrounding lighting outlet, the following shall
apply:
1. The exposed conductive parts of lighting fixtures
shall be connected to any acceptable point on the
grounding electrode system, or
2. The lighting fixtures shall be made of insulating
material and shall have no exposed conductive parts.
Exception: Lighting fixtures mounted on electri-
cally nonconductive ceilings or walls where
located not less than either 8 feet (2438 mm) verti-
cally or 5 feet (1524 mm) horizontally from
grounded surfaces.
8-904.2.7 Lighting load calculations for services and feed-
ers may be based on actual loads as installed in lieu of the
"watts per square foot" method.
8-904.2.8 Determination of existing loads may be based on
maximum demand recordings in lieu of calculations, pro-
vided all of the following are met:
1. Recordings are provided by the serving agency.
2. The maximum demand data is available for a
one-year period.
Exception: If maximum demand data for a
one-year period is not available, the maximum
demand data shall be permitted to be based on the
actual amperes continuously recorded over a mini-
mum 30-day period by a recording ammeter con-
nected to the highest loaded phase of the feeder or
service. The recording should reflect the maxi-
mum demand when the building or space is occu-
pied and include the measured or calculated load at
the peak time of the year, including the larger of the
heating or cooling equipment load.
3. There has been no change in occupancy or character
of load during the previous 12 months.
4. The anticipated load will not change, or the existing
demand load at 125 percent plus the new load does
not exceed the ampacity of the feeder or rating of the
service.
2010 CALIFORNIA HISTORICAL BUILDING CODE
21
22 201 CALIFORNIA HISTORICAL BUILDING CODE
CHAPTER 8-10
QUALIFIED HISTORICAL DISTRICTS, SITES AND OPEN SPACES
SECTION 8-1001
PURPOSE AND SCOPE
8-1001.1 Purpose. The purpose of this chapter is to provide
regulations for the preservation, rehabilitation, restoration and
reconstruction of associated historical features of qualified his-
torical buildings, properties or districts (as defined in Chapter
8-2), and for which Chapters 8-3 through 8-9 of the CHBC may
not apply.
8-1001.2 Scope. This chapter applies to the associated histori-
cal features of qualified historical buildings or properties such
as historical districts that are beyond the buildings themselves
which include, but are not limited to, natural features and
designed site and landscape plans with natural and man-made
landscape elements that support their function and aesthetics.
This may include, but will not be limited to:
1. Site plan layout configurations and relationships
(pedestrian, equestrian and vehicular site circulation,
topographical grades and drainage, and use areas).
2. Landscape elements (plant materials, site structures
other than the qualified historical building, bridges and
their associated structures, lighting, water features, art
ornamentation, and pedestrian, equestrian and vehicu-
lar surfaces).
3. Functional elements (utility placement, erosion control
and environmental mitigation measures).
SECTION 8-1002
APPLICATION
8-1002.1 The CHBC shall apply to all sites and districts and
their features associated with qualified historical buildings or
qualified historical districts as outlined in 8-100L2 Scope.
8-1002.2 Where the application of regular code may impact
the associated features of qualified historical properties beyond
their footprints, by work performed secondarily, those impacts
shall also be covered by the CHBC.
8-1002.3 This chapter shall be applied for all issues regarding
code compliance or other standard or regulation as they affect
the purpose of this chapter.
8-1002.4 The application of any code or building standard
shall not unduly restrict the use of a qualified historical build-
ing or property that is otherwise permitted pursuant to Chapter
8-3 and the intent of the State Historical Building Code, Sec-
tion 18956.
SECTION 8-1003
SITE RELATIONS
The relationship between a building or property and its site, or
the associated features of a district (including qualified histori-
cal landscape), site, objects and their features are critical com-
ponents that may be one of the criteria for these buildings and
properties to be qualified under the CHBC. The CHBC recog-
nizes the importance of these relationships. This chapter shall
be used to provide context sensitive solutions for treatment of
qualified historical buildings, properties, district or their asso-
ciated historical features, or when work to be performed sec-
ondarily impacts the associated historical features of a
qualified historical building or property.
2010 CALIFORNIA HISTORICAL BUILDING CODE
23
24 2010 CALIFORNIA HISTORICAL BUILDING CODE
APPENDIX A
CHAPTER 8-1
When modification must be made to qualified historical build-
ings and properties, the CHBC is intended to work in conjunc-
tion with the United States Secretary of Interior Standards for
the Treatment of Historic Properties with Guidelines for Pre-
serving, Rehabilitating, Restoring and Reconstructing Historic
Buildings and the Secretary of Interior's Standards for the
Treatment of Historic Properties with Guidelines for the Treat-
ment of Cultural Landscapes.
CHAPTER 8-6
TABLE 1— PROVISION APPLICABILITY
Title II
Public Entities
Title III
Private Entities
Title III
Barrier
Removal
SECTION 8-601 PURPOSE, INTENT, SCOPE
8-601.1 Purpose. The purpose of the CHBC is to provide alternative regulations to
facilitate access and use by persons with disabilities to and throughout facilities
designated as qualified historical buildings or properties. These regulations require
enforcing agencies to accept alternatives to regular code when dealing with qualified
historical buildings or properties.
8-601.2 Intent. The intent of this chapter is to preserve the integrity of qualified
historical buildings and properties while providing access to and use by people with
disabilities.
8-601.3 Scope. The CHBC shall apply to every qualified historical building or property
that is required to provide access to people with disabilities.
1. Provisions of this chapter do not apply to new construction or
reconstruction/replicas of historical buildings.
2. Where provisions of this chapter apply to alteration of qualified historical buildings
or properties, alteration is defined in California Building Code (CBC), Chapter 2,
Definitions and Abbreviations. 202 - A. Alter or Alteration.
8-601.4 General application. The provisions in the CHBC apply to local, state and federal
governments (Title II entities); alteration of commercial facilities and places of public
accommodation (Title III entities); and barrier removal in commercial facilities and places
of public accommodation (Title III entities). Except as noted in this chapter.
Applies
Applies
AppMes
SECTION 8-602 — BASIC PROVISIONS
8-602.1 Regular code. The regular code for access for people with disabilities (Title 24,
Part 2, Vol.1, Chapter 1 IB) shall be applied to qualified historical buildings or properties
unless strict compliance with the regular code will threaten or destroy the historical
significance or character-defining features of the building or property.
8-602.2 Alternative provisions. If the historical significance or character-defining
features are threatened, alternative provisions for access may be applied pursuant to this
chapter, provided the following conditions are met:
1. These provisions shall be apphed only on an itera-by-item or case-by-case basis.
2. Documentation is provided, including meeting minutes or letters, stating the
reasons for the application of the alternative provisions. Such documentation shall
be retained in the permanent file of the enforcing agency.
Applies
AppUes
Applies
(continued)
2010 CALIFORNIA HISTORICAL BUILDING CODE
25
APPENDIX A
TABLE 1— PROVISION APPLICABILITY— continued
Title II
Public Entities
Title III
Private Entities
Title III
Barrier
Removal
SECTION 8-603 — ALTERNATIVES
8-603.1 Alternative minimum standards. The alternative minimum standards for
alterations of qualified historical buildings or facilities are contained in Section 4.1.7(3)
of ADA Standards for Accessible Design, as incorporated and set forth in federal
regulation 28 C.F.R. Pt. 36.
8-603.2 Entry. These alternatives do not allow exceptions for the requirement of level
landings in front of doors, except as provided in Section 8-603.4.
1. Access to any entrance used by the general pubHc and no further than 200 feet
(60 960 nmi) from the primary entrance.
2. Access at any entrance not used by general public but open and unlocked with
directional signs at the primary entrance and as close as possible to, but no further
than 200 feet (60 960 mm) from, the primary entrance.
3. The accessible entrance shall have a notification system. Where security is a
problem, remote monitoring may be used.
Applies
Applies
Applies
Applies
Applies
Applies
8-603.3 Doors. Alternatives listed in order of priority are:
1. Single-leaf door which provides a minimum 30 inches (762 mm) of clear opening.
2. Single-leaf door which provides a minimum 29 7^ inches (749 mm) clear opening.
3. Double door, one leaf of which provides a minimum 2972 inches (749 ram) clear
opening.
4. Double doors operable with a power-assist device to provide a minimum 2972
inches (749 mm) clear opening when both doors are in the open position.
Exception: Alternatives in this section do not apply to alteration of commercial facil-
ities and places of public accommodation (Title III entities).
Does not
apply
Does not
apply
Applies
8-603.4 Power-assisted doors. Power-assisted door or doors may be considered an
equivalent alternative to level landings, strikeside clearance and door-opening forces
required by regular code.
8-603.5 Toilet rooms. In lieu of separate-gender toilet facihties as requked in the regular
code, an accessible unisex toilet may be designated.
8-603.6 Exterior and interior ramps and lifts. Alternatives listed in order of priority
are:
1 . A lift or a ramp of greater than standard slope but no greater than 1:10, for
horizontal distances not to exceed 5 feet (1525 nmi). Signs shall be posted at upper
and lower levels to indicate steepness of the slope.
2. Access by ramps of 1:6 slope for horizontal distance not to exceed 13 inches (330
mm). Signs shall be posted at upper and lower levels to indicate steepness of the
slope.
Applies
Applies
Applies
Applies
Applies
Applies
Applies
Applies
Applies
(continued)
26
2010 CALIFORNIA HISTORICAL BUILDING CODE
APPENDIX A
TABLE I—PROVISION APPUCABILITY— continued
Title II
Public
Entities
Title III
Private Entities
Title III
Barrier
Removal
SECTION 8-604 — EQUIVALENT FACILITATION
Use of other designs and technologies, or deviation from particular technical and
scoping requirements, are permitted if the application of the alternative provisions
contained in Section 8-603 would threaten or destroy the historical significance or
character-defining features of the qualified historical building or property.
1 . Such alternatives shall be applied only on an item-by-item or case-by-case basis.
2. Access provided by experiences, services, functions, materials and resources
through methods including, but not limited to, maps, plans, videos, virtual reality
and related equipment, at accessible levels. The alternative design and/or
technologies used will provide substantially equivalent or greater accessibihty to,
and usability of, the facility.
3. The official charged with the enforcement of the standards shall document the
reasons for the application of the design and/or technologies and their effect on
the historical significance or character-defining features. Such documentation
shall be in accordance with Section 8-602.2, Item 2, and shall include the opinion
and comments of state or local accessibility officials, and the opinion and
conunents of representative local groups of people with disabilities. Such
documentation shall be retained in the permanent file of the enforcing agency.
Copies of the required documentation should be available at the facility upon
request.
Note: For commercial facilities and places of public accommodation (Title III enti-
ties).
Equivalent facilitation for an element of a building or property when applied as a
waiver of an ADA accessibility requirement will not be entitled to the Federal
Department of Justice certification of this code as rebuttable evidence of compliance
for that element.
Applies
Waivers
If a builder
applies for a
waiver of an
ADA
accessibility
requirement for
an element of a
building, he or
she will not be
entitled to
certification's
rebuttable
evidence of
compliance for
that element.
This limitation
on the
certification
determination
should be noted
in any
publication of
Chapter 8-6 if
certification is
granted.
Applies
Notes: The regular code for Chapter 8-6 is contained in Title 24, Part 2, Vol.1, Chapter 11, which contain standards for new construction.
Provisions of this chapter may be used in conjunction with all other provisions of the regular code and ADA regulations.
2010 CALIFORNIA HISTORICAL BUILDING CODE
27
28 2010 CALIFORNIA HISTORICAL BUILDING CODE
HISTORY NOTE APPENDIX
CAUFORNIA HISTORICAL BUILDING CODE
(Title 24, Part 8, California Code of Regulations)
For prior history, see History Note Appendix to the California
Historical Building Code, 2001 Triennial Edition, effective
November 1,2002.
1 . The 2007 Triennial Edition, California Historical Build-
ing Code, was approved by the California Building Standards
Commission on January 29, 2007. The California Building
Standards Commission established January 1, 2008, as the
effective date.
2. Editorial correction to Chapter 8-8, Section 8-812, Tables
8-8A and 8-8B. Include missing tables in 2007 annual code
adoption supplement.
201 CALIFORNIA HISTORICAL BUILDING CODE 29
30 2010 CALIFORNIA HISTORICAL BUILDING CODE
'F".^I-i -
h^: ' ; 1 - = '-:■
)
J:.\\M
4 \\
v' M ■ - ': .
r(^?^;M HKtj r-H ^M^q HV'^^---S^^-\:|
'[>:. '^/ Lilid y^U^I l^^r.O H;vi^ i^ir^
Californii»^Cbde<)f Regulations
Title 24, ^grt 10
California Buildirtg Standards Comrnission.
Based on the 2009 International Exjstan|:
^\
ir^K
H ■' ': ' ? '" - ■' '• .; ; '- •
?\
-A
..j^
INTERNATIONAL^
CODECOUMCIL^
■_ f - 5 I
(For Errata anii|)#rt^|^^^^^^
2010 California Existing Building Code
California Code of Regulations, Title 24, Part 10
First Printing: June 2010
ISBN 978-1-58001-974-3
Copyright ©2010
Held by
California Building Standards Commission
2525 Natomas Park Drive, Suite 130
Sacramento, CA 95833-2936
ALL RIGHTS RESERVED. This 2010 California Existing Building Code contains substantial copyrighted material from the 2009
International Existing Building Code, which is a copyrighted work owned by the International Code Council, Inc. Without advance
written permission from the copyright owner, no part of this book may be reproduced, distributed or transmitted in any form or by
any means, including, without limitation, electronic, optical or mechanical means (by way of example and not limitation, photo - _
copying, or recording by or in an information storage retrieval system). For information on permission to copy material exceedin^^^
fair use, please contact: Publications, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICC-SAFi^^
(422-7233).
Trademarks: "International Code Council," the "International Code Council" logo and the "International Existing Building Code"
are trademarks of the International Code Council, Inc.
PRINTED IN THE U.S.A.
TABLE OF CONTENTS
APPENDIX CHAPTER Al
SEISMIC STRENGTHENING PROVISIONS
FOR UNREINFORCED MASONRY
BEARING WALL BUILDINGS 3
Section
AlOO Application 3
AlOl Purpose 3
A102 Scope 3
A103 Definitions 3
A104 Symbols and Notations 4
A105 General Requirements 5
A106 Materials Requirements 5
A107 Quality Control 7
A108 Design Strengths 8
A 109 Analysis and Design Procedure 8
Al 10 General Procedure 8
Al 11 Special Procedure 9
All 2 Analysis and Design 10
Al 13 Detailed System Design Requirements 11
Al 14 Wails of Unburned Clay,
Adobe or Stone Masonry 12
REFERENCED STANDARDS 19
HISTORY NOTE APPENDIX 27
2010 CALIFORNIA EXISTING BUILDING CODE ill
iv 2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1 - SEISMIC STRENGTHENING PROVISIONS
FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS
Adopting Agency
BSC
HCD
DSA
1
2
1/AC
AC
SS
Adopt Entire Chapter
Adopt Entire Chapter as amended
(amended sections listed below)
X
X
X
Adopt only those sections that are
listed below
Chapter /Section
Codes
A100
CA
X
X
X
A103- BUILDING
CODE
CA
X
X
X
NOTES:
1. For essential services buildings, refer to Part 1, Chapter 4, Articles 1, 2 and 3, Title 24, C.C.R., for administrative regulations of the
Division of the State Architect-Structural Safety Section.
2. For private schools, refer to Education Code section 39160-76, and Health and Safety Code section 18941.5.
3. For historical buildings, refer to Part 8, Titie 24, C.C.R.
4. For application and enforcement authority, refer to Part 2, Chapter 1, sections 101, 102 and 108, Title 24, C.C.R.
5. For local jurisdiction exemption program, refer to Health and Safety Code section 18941.6.
2010 CALIFORNIA EXISTING BUILDING CODE
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
SEISMIC STRENGTHENING PROVISIONS
FOR UNREINFORCED MASONRY BEARING WALL BUILDINGS
SECTION A1 00
APPLICATION
AlOO.l Vesting authority. When adopted by a state agency, the
provisions of these regulations shall be enforced by the appro-
priate enforcing agency, but only to the extent of authority
granted to such agency by the state legislature.
Following is a list of the state agencies that adopt building
standards, the specific scope of application of the agency
re sponsible for enforcement, and the specific statutory author-
ity of each agency to adopt and enforce such provisions of
building standards of this code, unless otherwise stated.
L BSC — California Building Standards Commission.
Application — Existing buildings as specified in Section
A 102 having at least one unreinforced masonry bearing
wall, with the exception of buildings subject to building
standards pursuant to Health and Safety Code, com-
mencing with Section 17910.
Enforcing Agency — State or local agency specified by
the applicable provisions of the law.
Authority Cited — Health and Safety Code Section
18934.6,
Reference — Health and Safety Code Sections 18901
through 18949.
2. BCD 1 — The Department of Housing and Community
Development
Application — Hotels, motels, lodging houses, apartment
houses, dwellings, employee housing and factory-built
housing.
Enforcing Agency — The local building department or
the Department of Housing and Community Develop-
ment.
Authority Cited — Health and Safety Code Sections
17040, 17921, 17922, 19990.
Reference — Health and Safety Code Sections 1 7000
through 1 7060, 1 7910 through 1 7990, 19960 through
19997; and Government Code Section 12955.1.
3. HCD 2 — The Department of Housing and Community
Development
Application — Permanent buildings and permanent
accessory buildings or structures constructed within
mobilehome parks and special occupancy parks.
Enforcing Agency— The local building department or
the Department of Housing and Community Develop-
ment
Authority Cited— Health and Safety Code Sections
18300, 18620, 18640, 18865, 18873 and 188732.
Reference — Health and Safety Code Sections 18200
through 18700 and 18860 through 18874.
SECTION A1 01
PURPOSE
The purpose of this chapter is to promote public safety and
welfare by reducing the risk of death or injury that may result
from the effects of earthquakes on existing unreinforced
masonry bearing wall buildings.
The provisions of this chapter are intended as minimum
standards for structural seismic resistance, and are established
primarily to reduce the risk of life loss or injury. Compliance
with these provisions will not necessarily prevent loss of life or
injury, or prevent earthquake damage to rehabilitated build-
ings.
SECTION A1 02
SCOPE
A102.1 General. The provisions of this chapter shall apply to
all existing buildings having at least one unreinforced masonry
bearing wall. The elements regulated by this chapter shall be
determined in accordance with Table Al-A. Except as pro-
vided herein, other structural provisions of the building code
shall apply. This chapter does not apply to the alteration of
existing electrical, plumbing, mechanical or fire safety sys-
tems.
A102.2 Essential and hazardous facilities. The provisions of
this chapter shall not apply to the strengthening of buildings or
structures in Occupancy Category III when assigned to Seismic
Design Category C, D, or E or buildings or structures in Occu-
pancy Category IV. Such buildings or structures shall be
strengthened to meet the requirements of the California Build-
ing Code for new buildings of the same occupancy category or
other such criteria that have been established by the jurisdic-
tion.
SECTION A1 03
DEFINITIONS
For the purpose of this chapter, the applicable definitions in
the California Building Code as adopted by the California
Building Standards Commission (BSC) shall also apply:
BUILDING CODE. The code currently adopted by the
jurisdiction for new buildings. [BSC, HCD 1 and HCD 2]
"Building Code" shall mean the most current edition of the
California Building Code, Title 24, Part 2 as adopted by the
California Building Standards Commission (BSC).
COLLAR JOINT. The vertical space between adjacent
wythes. A collar joint may contain mortar or grout.
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
CROSSWALL. A new or existing wall that meets the require-
ments of Section All 1 .3 and the definition of Section Al 1 1 .3.
A cross wall is not a shear wall.
CROSSWALL SHEAR CAPACITY. The unit shear value
times the length of the crosswall, vj^^
DIAPHRAGM EDGE. The intersection of the horizontal dia-
phragm and a shear wall.
DIAPHRAGM SHEAR CAPACITY. The unit shear value
times the depth of the diaphragm, vj).
NORMAL WALL. A wall perpendicular to the direction of
seismic forces.
OPEN FRONT. An exterior building wall line without vertical
elements of the lateral-force-resisting system in one or more
stories.
POINTING. The partial reconstruction of the bed joints of an
unreinforced masonry wall as defined in UBC Standard 21-8.
RIGID DIAPHRAGM. A diaphragm of reinforced concrete
construction supported by concrete beams and columns or by
structural steel beams and colunms.
UNREINFORCED MASONRY. Includes burned clay, con-
crete or sand-lime brick; hollow clay or concrete block; plain
concrete; and hollow clay tile. These materials shall comply
with the requirements of Section A 106 as apphcable.
UNREINFORCED MASONRY BEARING WALL. A
URM wall that provides the vertical support for the reaction of
floor or roof-framing members.
UNREINFORCED MASONRY (URM) WALL. A masonry
wall that relies on the tensile strength of masonry units, mortar
and grout in resisting design loads, and in which the area of
reinforcement is less than 25 percent of the minimum ratio
required by the building code for reinforced masonry.
YIELD STORY DRIFT. The lateral displacement of one level
relative to the level above or below at which yield stress is first
developed in a frame member.
SECTION A1 04
SYMBOLS AND NOTATIONS
For the purpose of this chapter, the following notations sup-
plement the applicable symbols and notations in the building
code.
a„ = Diameter of core multiplied by its length or the
area of the side of a square prism.
A - Cross-sectional area of unreinforced masonry pier
or wall, square inches (10'^ m^),
A^ = Total area of the bed joints above and below the test
specimen for each in-place shear test, square
inches (10'^ m^).
D = In-plane width dimension of pier, inches (10'^ m),
or depth of diaphragm, feet (m).
DCR = Demand-capacity ratio specified in Section
Alll.4.2.
r^ =
Jsp
F
H =
h/t =
4
Pd =
P. =
R
V =
^ ca
Vet =
Vn =
Compressive strength of masonry.
Tensile- splitting strength of masonry.
Force applied to a wall at level x, pounds (N).
Least clear height of opening on either side of a
pier, inches (10"^ m).
Height-to-thickness ratio of URM wall. Height, h,
is measured between wall anchorage levels and/or
slab-on-grade.
Span of diaphragm between shear walls, or span
between shear wall and open front, feet (m).
Length of crosswall, feet (m).
Effective span for an open-front building specified
in Section All 1.8, feet (m).
Applied force as determined by standard test
method of ASTM C 496 or ASTM E 519, pounds
(N).
Superimposed dead load at the location under con-
sideration, pounds (kN). For determination of the
rocking shear capacity, dead load at the top of the
pier under consideration shall be used.
Press resulting from the dead plus actual live load
in place at the time of testing, pounds per square
inch (kPa).
Weight of wall, pounds (N).
Response modification factor for Ordinary plain
masonry shear walls in Bearing Wall System from
Table 12.2-1 of ASCE 7, where R=l,5.
Design spectral acceleration at short period, in g
units.
Design spectral acceleration at 1 -second period, in
g units.
The shear strength of any URM pier, v^A/1.5
pounds (N).
Unit shear capacity value for a crosswall sheathed
with any of the materials given in Table Al-D or
Al-E, pounds per foot (N/m).
Shear strength of unreinforced masonry, pounds
per square inch (kPa).
The shear strength of any URM pier or wall, pounds
(N).
Total shear capacity of crosswalls in the direction
of analysis immediately above the diaphragm level
being investigated, v^^* pounds (N).
Total shear capacity of crosswalls in the direction
of analysis immediately below the diaphragm level
being investigated, v^Z^, pounds (N).
Shear force assigned to a pier on the basis of its rel-
ative shear rigidity, pounds (N).
Pier rocking shear capacity of any URM wall or
wall pier, pounds (N).
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
V, = Mortar shear strength as specified in Section
A106.3.3.5, pounds per square inch (kPa).
Vig,t = Load at incipient cracking for each in-place shear
test per UBC Standard 21-6, pounds (kN).
Vjo = Mortar shear test values as specified in Section
A106.3.3.5, pounds per square inch (kPa).
v„ = Unit shear capacity value for a diaphragm
sheathed with any of the materials given in Table
Al-D or Al-E, pounds per foot (N/m).
V^^ = Total shear force resisted by a shear wall at the
level under consideration, pounds (N).
W - Total seismic dead load as defined in the building
code, pounds (N).
W^ = Total dead load tributary to a diaphragm level,
pounds (N).
W^ = Total dead load of a URM wall above the level un-
der consideration or above an open-front building,
pounds (N).
W^^ = Dead load of a URM wall assigned to level x half-
way above and below the level under consider-
ation, pounds (N).
2vj/) = Sum of diaphragm shear capacities of both ends of the
diaphragm, pounds (N).
HEvJ) = For diaphragms coupled with crosswalls, vj) in-
cludes the sum of shear capacities of both ends of
diaphragms coupled at and above the level under
consideration, pounds (N).
2W^ = Total dead load of all the diaphragms at and above
the level under consideration, pounds (N).
the exterior face is veneer, the type of veneer, its
thickness and its bonding and/or ties to the structural wall
masonry shall also be noted.
3. The type of interior wall and ceiling materials, and fram-
ing.
4. The extent and type of existing wall anchorage to floors
and roof when used in the design.
5. The extent and type of parapet corrections that were pre-
viously performed, if any.
6. Repair details, if any, of cracked or damaged
unreinforced masonry walls required to resist forces
specified in this chapter.
7. All other plans, sections and details necessary to delin-
eate required retrofit construction.
8. The design procedure used shall be stated on both the
plans and the permit application.
9. Details of the anchor prequalification program required
by UBC Standard 21-7, if used, including location and
results of all tests.
A 105.4 Structural observation, testing and inspection.
Structural observation, in accordance with Section 1709 of the
California Building Code, shall be required for all structures in
which seismic retrofit is being performed in accordance with
this chapter. Structural observation shall include visual
observation of work for conformance with the approved con-
struction documents and confirmation of existing conditions
assumed during design.
Structural testing and inspection for new construction mate-
rials shall be in accordance with the California Building Code,
except as modified by this chapter.
SECTION A1 05
GENERAL REQUIREMENTS
A105.1 General. The seismic-force-resisting system specified
in this chapter shall comply with the building code, except as
modified herein.
A105.2 Alterations and repairs. Alterations and repairs
required to meet the provisions of this chapter shall comply
with applicable structural requirements of the building code
unless specifically provided for in this chapter.
A105.3 Requirements for plans. The following construction
information shall be included in the plans required by this
chapter:
1. Dimensioned floor and roof plans showing existing
walls and the size and spacing of floor and roof-framing
members and sheathing materials. The plans shall indi-
cate all existing and new crosswalls and shear walls and
their materials of construction. The location of these
walls and their openings shall be fully dimensioned and
drawn to scale on the plans.
2. Dimensioned wall elevations showing openings, piers,
wall classes as defined in Section A106.3.3.8, thickness,
heights, wall shear test locations, cracks or damaged por-
tions requiring repairs, the general condition of the mor-
tar joints, and if and where pointing is required. Where
SECTION A1 06
MATERIALS REQUIREMENTS
A106.1 General. Materials permitted by this chapter, includ-
ing their appropriate strength design values and those existing
configurations of materials specified herein, may be used to
meet the requirements of this chapter.
A106.2 Existing materials. Existing materials used as part of
the required vertical-load-carrying or lateral-force-resisting
system shall be in sound condition, or shall be repaired or
removed and replaced with new materials. All other
unreinforced masonry materials shall comply with the follow-
ing requirements:
1. The lay-up of the masonry units shall comply with Sec-
tion A106.3.2, and the quality of bond between the units
has been verified to the satisfaction of the building offi-
cial;
2. Concrete masonry units are verified to be load-bearing
units complying with UBC Standard 21-4 or such other
standard as is acceptable to the building official; and
3. The compressive strength of plain concrete walls shall be
determined based on cores taken from each class of con-
crete wall. The location and number of tests shall be the
same as those prescribed for tensile-splitting strength
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
tests in Sections A106.3.3.3 and A106.3.3.4, or in Sec-
tion A108.1.
The use of materials not specified herein or in Section
A108.1 shall be based on substantiating research data or engi-
neering judgment, with the approval of the building official.
A106.3 Existing unreinforced masonry.
A106.3.1 General. Unreinforced masonry walls used to
carry vertical loads or seismic forces parallel and perpendic-
ular to the wall plane shall be tested as specified in this sec-
tion. All masonry that does not meet the minimum standards
established by this chapter shall be removed and replaced
with new materials, or alternatively, shall have its structural
functions replaced with new materials and shall be anchored
to supporting elements.
A106.3.2 Lay-up of walls.
A106.3.2.1 Multiwythe solid brick. The facing and
backing shall be bonded so that not less than 10 percent
of the exposed face area is composed of solid headers
extending not less than 4 inches (102 mm) into the back-
ing. The clear distance between adjacent full-length
headers shall not exceed 24 inches (610 mm) vertically
or horizontally. Where the backing consists of two or
more wythes, the headers shall extend not less than 4
inches ( 1 02 mm) into the most distant wythe, or the back-
ing wythes shall be bonded together with separate head-
ers with their area and spacing conforming to the
foregoing. Wythes of walls not bonded as described
above shall be considered veneer. Veneer wythes shall
not be included in the effective thickness used in calcu-
lating the height-to-thickness ratio and the shear capacity
of the wall.
Exception: Veneer wythes anchored as specified in
the building code and made composite with backup
masonry may be used for calculation of the effective
thickness, where 5^; exceeds 0.3.
A106.3.2.2 Grouted or ungrouted hollow concrete or
clay block and structural hollow clay tile. Grouted or
ungrouted hollow concrete or clay block and structural
hollow clay tile shall be laid in a running bond pattern.
A 106.3.2.3 Other lay-up patterns. Lay-up patterns
other than those specified in Sections A106.3.2.1 and
A 106.3.2.2 above are allowed if their performance can
be justified.
A106.3.3 Testing of masonry.
A 106.3.3.1 Mortar tests. The quality of mortar in all
masonry walls shall be determined by performing
in-place shear tests in accordance with the following:
1. The bed joints of the outer wythe of the masonry
should be tested in shear by laterally displacing a
single brick relative to the adjacent bricks in the
same wythe. The head joint opposite the loaded
end of the test brick should be carefully excavated
and cleared. The brick adjacent to the loaded end
of the test brick should be carefully removed by
sawing or drilling and excavating to provide space
for a hydraulic ram and steel loading blocks. Steel
blocks, the size of the end of the brick, should be
used on each end of the ram to distribute the load to
the brick. The blocks should not contact the mortar
joints. The load should be applied horizontally, in
the plane of the wythe. The load recorded at first
movement of the test brick as indicated by spalling
of the face of the mortar bed joints is V,^^, in Equa-
tion (Al-3).
2. Alternative procedures for testing shall be used
where in-place testing is not practical because of
crushing or other failure mode of the masonry unit
(see Section A106.3.3.2).
A106.3.3.2 Alternative procedures for testing
masonry. The tensile-splitting strength of existing
masonry,/^^, or the prism strength of existing masonry,/^
may be determined in accordance with one of the follow-
ing procedures:
1 . Wythes of solid masonry units shall be tested by
sampling the masonry by drilled cores of not less
than 8 inches (203 mm) in diameter. A bed joint in-
tersection with a head joint shall be in the center of
the core. The tensile- splitting strength of these
cores should be determined by the standard test
method of ASTM C 496. The core should be
placed in the test apparatus with the bed joint 45
degrees from the horizontal. The tensile- splitting
strength should be determined by the following
equation:
f =
IP
7ia„
(Equation Al-1)
Hollow unit masonry constructed of
through-the-wall units shall be tested by sampling
the masonry by a sawn square prism of not less
than 18 inches square (11 613 mm^). The ten-
sile-splitting strength should be determined by the
standard test method of ASTM E 519. The diago-
nal of the prism should be placed in a vertical posi-
tion. The tensile-splitting strength should be
determined by the following equation:
J sp
0.494P
(Equation Al-2)
3. An alternative to material testing is estimation of
the /^ of the existing masonry. This alternative
should be limited to recently constructed masonry.
The determination of /„ requires that the unit cor-
respond to a specification of the unit by an ASTM
standard and classification of the mortar by type.
A106.3.3.3 Location of tests. The shear tests shall be
taken at locations representative of the mortar conditions
throughout the entire building, taking into account varia-
tions in workmanship at different building height levels,
variations in weathering of the exterior surfaces, and
variations in the condition of the interior surfaces due to
deterioration caused by leaks and condensation of water
and/or by the deleterious effects of other substances con-
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
tained within the building. The exact test locations shall
be determined at the building site by the engineer or
architect in responsible charge of the structural design
work. An accurate record of all such tests and their loca-
tions in the building shall be recorded, and these results
shall be submitted to the building department for
approval as part of the structural analysis.
A 106.3.3.4 Number of tests. The minimum number of
tests per class shall be as follows:
1 . At each of both the first and top stories, not less
than two tests per wall or line of wall elements pro-
viding a common line of resistance to lateral
forces.
2. At each of all other stories, not less than one test
per wall or line of wall elements providing a com-
mon Hne of resistance to lateral forces.
3. In any case, not less than one test per 1 ,500 square
feet (139.4 m^) of wall surface and not less than a
total of eight tests.
A106.3.3.5 Minimum quality of mortar.
1. Mortar shear test values, v,^, in pounds per square
inch (kPa) shall be obtained for each in-place shear
test in accordance with the following equation:
"^to = C^tes/^b) -Pd^l (Equation A1.3)
2. Individual unreinforced masonry walls with v^^
consistently less than 30 pounds per square inch
(207 kPa) shall be entirely pointed prior to retest-
ing.
3 . The mortar shear strength, v^ is the value in pounds
per square inch (kPa) that is exceeded by 80 per-
cent of the mortar shear test values, v^^,
4. Unreinforced masonry with mortar shear strength,
v^ , less than 30 pounds per square inch (207 kPa)
shall be removed, pointed and retested or shall
have its structural function replaced, and shall be
anchored to supporting elements in accordance
with Sections A106.3.1 and A113.8. When exist-
ing mortar in any wythe is pointed to increase its
shear strength and is retested, the condition of the
mortar in the adjacent bed joints of the inner wythe
or wy thes and the opposite outer wythe shall be ex-
amined for extent of deterioration. The shear
strength of any wall class shall be no greater than
that of the weakest wythe of that class.
A106.3.3.6 Minimum quality of masonry.
1. The minimum average value of tensile-splitting
strength determined by Equation (A 1-1) or (A 1-2)
shall be 50 pounds per square inch (344.7 kPa).
The minimum value of /^ determined by categori-
zation of the masonry units and mortar should be
1,000 pounds per square inch (6895 kPa).
2. Individual unreinforced masonry walls with aver-
age tensile-splitting strength of less than 50
pounds per square inch (344.7 kPa) shall be en-
tirely pointed prior to retesting.
3. Hollow unit unreinforced masonry walls with esti-
mated prism compressive strength of less than
1,000 pounds per square inch (6895 kPa) shall be
grouted to increase the average net area compres-
sive strength.
A106.3.3.7 Collar joints. The collar joints shall be
inspected at the test locations during each in-place shear
test, and estimates of the percentage of adjacent wythe
surfaces that are covered with mortar shall be reported
along with the results of the in-place shear tests.
A106.3.3.8 Unreinforced masonry classes. Existing
unreinforced masonry shall be categorized into one or
more classes based on shear strength, quality of con-
struction, state of repair, deterioration and weathering. A
class shall be characterized by the allowable masonry
shear stress determined in accordance with Section
A108.2. Classes shall be defined for whole walls, not for
small areas of masonry within a wall.
A106.3.3.9 Pointing. Deteriorated mortar joints in
unreinforced masonry walls shall be pointed according
to UBC Standard 21-8. Nothing shall prevent pointing of
any deteriorated masonry wall joints before the tests are
made, except as required in Section A107.1.
SECTION A1 07
QUALITY CONTROL
A107,l Pointing. Preparation and mortar pointing shall be per-
formed with special inspection.
Exception: At the discretion of the building official,
incidental pointing may be performed without special
inspection.
A107.2 Masonry shear tests. In-place masonry shear tests
shall comply with Section A 106. 3. 3.1. Testing of masonry for
determination of tensile-splitting strength shall comply with
Section A106.3.3.2.
A107.3 Existing wall anchors. Existing wall anchors used as
all or part of the required tension anchors shall be tested in pull-
out according to UBC Standard 21-7. The minimum number of
anchors tested shall be four per floor, with two tests at walls
with joists framing into the wall and two tests at walls with
joists parallel to the wall, but not less than 1 percent of the total
number of existing tension anchors at each level.
A107.4 New bolts. All new embedded bolts shall be subject to
periodic special inspection in accordance with the building
code, prior to placement of the bolt and grout or adhesive in the
drilled hole. Five percent of all bolts that do not extend through
the wall shall be subject to a direct-tension test, and an addi-
tional 20 percent shall be tested using a calibrated torque
wrench. Testing shall be performed in accordance with UBC
Standard 21-7. New bolts that extend through the wall with
steel plates on the far side of the wall need not be tested.
Exception: Special inspection in accordance with the build-
ing code may be provided during installation of new
anchors in lieu of testing.
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
All new embedded bolts resisting tension forces or a combi-
nation of tension and shear forces shall be subject to periodic
special inspection in accordance with the building code, prior
to placement of the bolt and grout or adhesive in the drilled
hole. Five percent of all bolts resisting tension forces shall be
subject to a direct-tension test, and an additional 20 percent
shall be tested using a calibrated torque wrench. Testing shall
be performed in accordance with UBC Standard 21-7. New
through-bolts need not be tested.
SECTION A1 08
DESIGN STRENGTHS
A108.1 Values.
1. Strength values for existing materials are given in Table
Al-D and for new materials in Table Al-E.
2. Capacity reduction factors need not be used.
3. The use of new materials not specified herein shall be
based on substantiating research data or engineering
judgment, with the approval of the building official.
A108.2 Masonry shear strength. The unreinforced masonry
shear strength, v ^, shall be determined for each masonry class
from one of the following equations:
1. The unreinforced masonry shear strength, v^ shall be
determined by Equation (A 1-4) when the mortar shear
strength has been determined by Section A106.3.3.1.
v^=0.56v, -H-
m t
0.75Pn
(Equation Al-4)
The mortar shear strength values, v ^ shall be deter-
mined in accordance with Section 106.3.3.5 and shall not
exceed 100 pounds per square inch (689.5 kPa) for the
determination of v ^.
The unreinforced masonry shear, v ^ shall be determined
by Equation (Al-5) when tensile- splitting strength has
been determined in accordance with Section A106.3.3.2,
Item 1 or 2.
=0.8/,^ +0.5^
(Equation Al-5)
When f^ has been estimated by categorization of the
units and mortar in accordance with Section 2105.2.2.1
of the California Building Code, the unreinforced ma-
sonry shear strength, v ^ shall not exceed 200 pounds per
square inch (1380 kPa) or the lesser of the following:
a) 2.5^7^ or
b) 200 psi or
c)v + 0.75^
A
(Equation Al-6)
For SI: 1 psi = 6.895 kPa.
where:
V = 62.5 psi (430 kPa) for running bond masonry not
grouted solid.
V =100 psi (690 kPa) for running bond masonry
grouted solid.
V =25 psi (170 kPa) for stack bond grouted solid.
A108.3 Masonry compression. Where any increase in dead
plus live compression stress occurs, the compression stress in
unreinforced masonry shall not exceed 300 pounds per square
inch (2070 kPa).
A 108.4 Masonry tension. Unreinforced masonry shall be
assumed to have no tensile capacity.
A 108.5 Existing tension anchors. The resistance values of the
existing anchors shall be the average of the tension tests of
existing anchors having the same wall thickness and joist ori-
entation.
A108.6 Foundations. For existing foundations, new total dead
loads may be increased over the existing dead load by 25 per-
cent. New total dead load plus live load plus seismic forces may
be increased over the existing dead load plus live load by 50
percent. Higher values may be justified only in conjunction
with a geotechnical investigation.
SECTION A1 09
ANALYSIS AND DESIGN PROCEDURE
A 109.1 General. The elements of buildings hereby required to
be analyzed are specified in Table Al-A.
A 109.2 Selection of procedure. Buildings with rigid dia-
phragms shall be analyzed by the general procedure of Section
Alio, which is based on the building code. Buildings with
flexible diaphragms shall be analyzed by the general procedure
or, when applicable, may be analyzed by the special procedure
of Section All 1.
SECTION A110
GENERAL PROCEDURE
AllO.l Minimum design lateral forces. Buildings shall be
analyzed to resist minimum lateral forces assumed to act non-
concurrently in the direction of each of the main axes of the
structure in accordance with the following:
V
0755^
R
(Equation Al-7)
A110.2 Lateral forces on elements of structures. Parts and
portions of a structure not covered in Sections A 1 10.3 shall be
analyzed and designed per the current building code, using
force levels defined in Section AllO.l.
Exceptions:
1. Unreinforced masonry walls for which
height-to-thickness ratios do not exceed ratios set
forth in Table Al-B need not be analyzed for
out-of-plane loading. Unreinforced masonry walls
that exceed the allowable h/t ratios of Table Al-B
shall be braced according to Section Al 13.5.
2. Parapets complying with Section Al 13.6 need not be
analyzed for out-of-plane loading.
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
3. Walls shall be anchored to floor and roof diaphragms
in accordance with Section Al 13.1.
A110.3 In-piane loading of URM shear walls and frames.
Vertical lateral-load-resisting elements shall be analyzed in
accordance with Section Al 12.
A110.4 Redundancy and overstrength factors. Any redun-
dancy or overstrength factors contained in the building code
may be taken as unity. The vertical component of earthquake
load (E^) may be taken as zero.
SECTION Al 11
SPECIAL PROCEDURE
All 1.1 Limits for the application of this procedure. The
special procedures of this section may be applied only to build-
ings having the following characteristics:
1. Flexible diaphragms at all levels above the base of the
structure.
2. Vertical elements of the lateral-force-resisting system
consisting predominantly of masonry or concrete shear
walls.
3. Except for single-story buildings with an open front on
one side only, a minimum of two lines of vertical ele-
ments of the lateral-force-resisting system parallel to
each axis of the building (see Section All 1.8 for
open-front buildings).
A111.2 Lateral forces on elements of structures. With the
exception of the provisions in Sections All 1.4 through
All 1.7, elements of structures shall comply with Sections
Al 10.2 through Al 10.4.
A111.3 Crosswalls. Crosswalls shall meet the requirements of
this section.
All 1,3.1 Crosswall definition. A crosswall is a
wood-framed wall sheathed with any of the materials
described in Table Al-D or Al-E or other system as defined
in Section All 1.3.5. Crosswalls shall be spaced no more
than 40 feet (12 192 mm) on center measured perpendicular
to the direction of consideration, and shall be placed in each
story of the building. Crosswalls shall extend the full story
height between diaphragms.
Exceptions:
1. Crosswalls need not be provided at all levels when
used in accordance with Section Al 1 1 .4.2, Item 4.
2. Existing crosswalls need not be continuous below
a wood diaphragm at or within 4 feet (1219 mm) of
grade, provided:
2.1 Shear connections and anchorage require-
ments of Section Al 1 1 .5 are satisfied at all
edges of the diaphragm.
2.2 Crosswalls with total shear capacity of
0.55i)iXW^ interconnect the diaphragm to
the foundation.
2.3 The demand-capacity ratio of the dia-
phragm between the crosswalls that are
continuous to their foundations does not
exceed 2.5, calculated as follows:
DCR =
{21S,,W, +V,^
)
2vD
(Equation A1.8)
All 1.3.2 Crosswall shear capacity. Within any 40 feet (12
192 mm) measured along the span of the diaphragm, the
sum of the crosswall shear capacities shall be at least 30 per-
cent of the diaphragm shear capacity of the strongest dia-
phragm at or above the level under consideration.
Alll.3.3 Existing crosswalls. Existing crosswalls shall
have a maximum height-to-length ratio between openings
of 1.5 to 1. Existing crosswall connections to diaphragms
need not be investigated as long as the crosswall extends to
the framing of the diaphragms above and below.
All 1.3.4 New crosswalls. New crosswall connections to
the diaphragm shall develop the crosswall shear capacity.
New crosswalls shall have the capacity to resist an overturn-
ing moment equal to the crosswall shear capacity times the
story height. Crosswall overturning moments need not be
cumulative over more than two stories.
Alll.3.5 Other crosswall systems. Other systems, such as
moment-resisting frames, may be used as crosswalls pro-
vided that the yield story drift does not exceed 1 inch (25,4
mm) in any story.
All 1.4 Wood diaphragms.
Alll.4.1 Acceptable diaphragm span. A diaphragm is
acceptable if the point {L,DCR ) on Figure A 1-1 falls within
Region 1, 2 or 3.
Alll.4.2 Demand-capacity ratios. Demand-capacity
ratios shall be calculated for the diaphragm at any level
according to the following formulas:
1 . For a diaphragm without qualifying crosswalls at lev-
els immediately above or below:
DCR = 2ASo^WJ^vJ)
(Equation Al-9)
2. For a diaphragm in a single-story building with quali-
fying crosswalls, or for a roof diaphragm coupled by
crosswalls to the diaphragm directly below:
DCR = 2.1 5o 1 WJiX vfi + Vcb ) (Equation Al-10)
3 . For diaphragms in a multistory building with quaUfy-
ing crosswalls in all levels:
DCR = 2ASj)yY.WJ(ZLvJ) + VJ (Equation Al-11)
DCR shall be calculated at each level for the set of
diaphragms at and above the level under consider-
ation. In addition, the roof diaphragm shall also meet
the requirements of Equation (Al-10).
4. For a roof diaphragm and the diaphragm directly be-
low, if coupled by crosswalls:
DCR = 2AS ox^W JZl.v fi (Equation AM2)
All 1.4.3 Chords. An analysis for diaphragm flexure need
not be made, and chords need not be provided.
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
All 1.4.4 Collectors. An analysis of diaphragm collector
forces shall be made for the transfer of diaphragm edge
shears into vertical elements of the lateral-force-resisting
system. Collector forces may be resisted by new or existing
elements.
Alll.4.5 Diaphragm openings.
1. Diaphragm forces at comers of openings shall be in-
vestigated and shall be developed into the diaphragm
by new or existing materials.
2. In addition to the demand-capacity ratios of Section
Al 1 1 .4.2, the demand-capacity ratio of the portion of
the diaphragm adjacent to an opening shall be calcu-
lated using the opening dimension as the span.
3 . Where an opening occurs in the end quarter of the dia-
phragm span, the calculation of v„Z) for the de-
mand-capacity ratio shall be based on the net depth of
the diaphragm.
All 1.5 Diaphragm shear transfer. Diaphragms shall be con-
nected to shear walls with connections capable of developing
the diaphragm-loading tributary to the shear wall given by the
lesser of the following formulas:
V= 1.2 5^ 1 Cp W^ (Equation Al-13)
using the C^ values in Table Al-C, or
V=v^ (Equation Al-14)
A111.6 Shear walls (In-plane loading).
A 111.6.1 Wall story force. The wall story force distributed
to a shear wall at any diaphragm level shall be the lesser
value calculated as:
2. In Region 2, height-to-thickness ratios for buildings
with cross walls may be used whether or not qualify-
ing crosswalls are present.
3. In Region 3, height-to-thickness ratios for "all other
buildings" shall be used whether or not qualifying
crosswalls are present.
A 111.7.2 Walls with diaphragms in different regions.
When diaphragms above and below the wall under consid-
eration have demand-capacity ratios in different regions of
Figure Al-1, the lesser height-to-thickness ratio shall be
used.
A111.8 Open-front design procedure. A single-story build-
ing with an open front on one side and crosswalls parallel to the
open front may be designed by the following procedure:
1 . Effective diaphragm span, L,, for use in Figure Al-1 shall
be determined in accordance with the following formula:
L, = 2[(W^/W^)L+L] (Equation AM8)
2. Diaphragm demand-capacity ratio shall be calculated as:
DCR=2A2Sj,,{W,^W^)/[{vJ)) + V,,]
(Equation Al-19)
SECTION A1 12
ANALYSIS AND DESIGN
A112.1 General. The following requirements are applicable to
both the general procedure and the special procedure for ana-
lyzing vertical elements of the lateral-force-resisting system.
but need not exceed
(Equation Al-15) A112.2 Existing unreinforced masonry walls.
(Equation Al-16)
Alll.6.2 Wall story shear. The wall story shear shall be the
sum of the wall story forces at and above the level of consid-
eration.
V =1F
(Equation Al-17)
Alll.6.3 Shear wall analysis. Shear walls shall comply
with Section A112.
Alll.6.4 Moment frames. Moment frames used in place
of shear walls shall be designed as required by the building
code, except that the forces shall be as specified in Section
Alll.6.1, and the story drift ratio shall be limited to 0.015,
except as further limited by Section A 1 12.4.2.
A111.7 Out-of-plane forces — unreinforced masonry walls.
Al 11.7.1 Allowable unreinforced masonry wall
height-to-thickness ratios. The provisions of Section
A 110.2 are applicable, except the allowable height-to-
thickness ratios given in Table Al-B shall be determined
from Figure Al-1 as follows:
1. In Region 1, height- to- thickness ratios for buildings
with crosswalls may be used if qualifying crosswalls
are present in all stories.
A112.2.1 Flexural rigidity. Flexural components of deflec-
tion may be neglected in determining the rigidity of an
unreinforced masonry wall.
Al 12.2.2 Shear walls with openings. Wall piers shall be
analyzed according to the following procedure, which is
diagramed in Figure Al-2.
1. For any pier,
1.1. The pier shear capacity shall be calculated as:
V, = vJl n .5 (Equation A1.20)
1 .2. The pier rocking shear capacity shall be calcu-
lated as:
V =0.9 Pj:)D/H
(Equation Al-21)
2. The wall piers at any level are acceptable if they com-
ply with one of the following modes of behavior:
2.1. Rocking controlled mode. When the pier
rocking shear capacity is less than the pier
shear capacity, i.e., V^ < V^ for each pier in a
level, forces in the wall at that level, V^^ shall
be distributed to each pier in proportion to
PJ)/H.
For the wall at that level:
OJV^^KlV,
(Equation Al-22)
10
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
2.2. Shear controlled mode. Where the pier shear
capacity is less than the pier rocking capacity,
i.e., V^ < y^ in at least one pier in a level, forces
in the wall at the level, V^^ shall be distributed
to each pier in proportion to D/H.
For each pier at that level:
Vp<V^ (Equation Al-23)
and
Vp<V, (Equation Al-24)
If Vp < V^ for each pier and Vp > V, for one or
more piers, such piers shall be omitted from
the analysis, and the procedure shall be re-
peated for the remaining piers, unless the wall
is strengthened and reanalyzed.
3. Masonry pier tension stress. Unreinforced masonry
wall piers need not be analyzed for tension stress.
A112.2.3 Shear walls without openings. Shear walls with-
out openings shall be analyzed the same as for walls with
openings, except that V, shall be calculated as follows:
V, = 03 (Po+ 0.5 P J D/H
(Equation Al-25)
A112.3 Plywood-sheathed shear walls. Plywood- sheathed
shear walls may be used to resist lateral forces for buildings
with flexible diaphragms analyzed according to provisions of
Section Al 1 1. Plywood-sheathed shear walls may not be used
to share lateral forces with other materials along the same line
of resistance.
A112.4 Combinations of vertical elements.
A112.4.1 Lateral-force distribution. Lateral forces shall
be distributed among the vertical-resisting elements in pro-
portion to their relative rigidities, except that
moment-resisting frames shall comply with Section
Al 12.4.2.
A112.4.2 Moment-resisting frames. Moment-resisting
frames shall not be used with an unreinforced masonry wall
in a single line of resistance unless the wall has piers that
have adequate shear capacity to sustain rocking in accor-
dance with Section Al 12.2.2. The frames shall be designed
in accordance with the building code to carry 100 percent of
the lateral forces tributary to that line of resistance, as deter-
mined from Equation (A 1-7). The story drift ratio shall be
limited to 0.0075.
SECTION A1 13
DETAILED SYSTEM DESIGN REQUIREMENTS
A113.1 Wall anchorage.
A113.1.1 Anchor locations. Unreinforced masonry walls
shall be anchored at the roof and floor levels as required in
Section A110.2. Ceilings of plaster or similar materials,
when not attached directly to roof or floor framing and
where abutting masonry walls, shall either be anchored to
the walls at a maximum spacing of 6 feet (1 829 mm), or be
removed.
A113.1.2 Anchor requirements. Anchors shall consist of
bolts installed through the wall as specified in Table Al-E,
or an approved equivalent at a maximum anchor spacing of
6 feet (1829 mm). All wall anchors shall be secured to the
joists to develop the required forces.
A113.1.3 Minimum wall anchorage. Anchorage of
masonry walls to each floor or roof shall resist a minimum
force determined as 0.95 j^s times the tributary weight or 200
pounds per linear foot (2920 N/m), whichever is greater,
acting normal to the wall at the level of the floor or roof.
Existing wall anchors, if used, must meet the requirements
of this chapter or must be upgraded.
A113.1.4 Anchors at comers. At the roof and floor levels,
both shear and tension anchors shall be provided within 2
feet (610 mm) horizontally from the inside of the comers of
the walls.
A113.2 Diaphragm shear transfer. Bolts transmitting shear
forces shall have a maximum bolt spacing of 6 feet (1829 mm)
and shall have nuts installed over malleable iron or plate wash-
ers when bearing on wood, and heavy -cut washers when bear-
ing on steel.
A113.3 Collectors, Collector elements shall be provided that
are capable of transferring the seismic forces originating in
other portions of the building to the element providing the
resistance to those forces.
A113.4 Ties and continuity. Ties and continuity shall conform
to the requirements of the building code.
A113.5 Wall bracing.
Al 13.5.1 General. Where a wall height-to- thickness ratio
exceeds the specified limits, the wall may be laterally sup-
ported by vertical bracing members per Section A 1 13.5.2 or
by reducing the wall height by bracing per Section
A113.53.
Al 13.5.2 Vertical bracing members. Vertical bracing
members shall be attached to floor and roof construction for
their design loads independently of required wall anchors.
Horizontal spacing of vertical bracing members shall not
exceed one-half of the unsupported height of the wall or 10
feet (3048 mm). Deflection of such bracing members at
design loads shall not exceed one-tenth of the wall thick-
ness.
Al 13.5.3 Intermediate wall bracing. The wall height may
be reduced by bracing elements connected to the floor or
roof. Horizontal spacing of the bracing elements and wall
anchors shall be as required by design, but shall not exceed 6
feet (1829 nmi) on center. Bracing elements shall be
detailed to minimize the horizontal displacement of the wall
by the vertical displacement of the floor or roof.
A113.6 Parapets. Parapets and exterior wall appendages not
conforming to this chapter shall be removed, or stabilized or
braced to ensure that the parapets and appendages remain in
their original positions.
The maximum height of an unbraced unreinforced masonry
parapet above the lower of either the level of tension anchors or
the roof sheathing shall not exceed the height-to-thickness
ratio shown in Table Al-F. If the required parapet height
exceeds this maximum height, a bracing system designed for
the forces determined in accordance with the building code
2010 CALIFORNIA EXISTING BUILDING CODE
11
APPENDIX CHAPTER A1
shall support the top of the parapet. Parapet corrective work
must be performed in conjunction with the installation of ten-
sion roof anchors.
The minimum height of a parapet above any wall anchor
shall be 12 inches (305 nam).
Exception: If a reinforced concrete beam is provided at the
top of the wall, the minimum height above the wall anchor
may be 6 inches (152 mm).
A113.7 Veneer.
1 . Veneer shall be anchored with approved anchor ties con-
forming to the required design capacity specified in the
building code and shall be placed at a maximum spacing
of 24 inches (610 mm) with a maximum supported area
of 4 square feet (0.372 m^).
Exception: Existing anchor ties for attaching brick
veneer to brick backing may be acceptable, provided
the ties are in good condition and conform to the fol-
lowing minimum size and material requirements.
Existing veneer anchor ties may be considered ade-
quate if they are of corrugated galvanized iron strips
not less than 1 inch (25.4 mm) in width, 8 inches (203
mm) in length and V^^ inch (1.6 mm) in thickness, or
the equivalent.
2. The location and condition of existing veneer anchor ties
shall be verified as follows:
2.1. An approved testing laboratory shall verify the
location and spacing of the ties and shall submit a
report to the building official for approval as part
of the structural analysis,
2.2. The veneer in a selected area shall be removed to
expose a representative sample of ties (not less
than four) for inspection by the building official.
A113.8 Nonstructural masonry walls. Unreinforced
masonry walls that carry no design vertical or lateral loads and
that are not required by the design to be part of the lateral-force
resisting system shall be adequately anchored to new or exist-
ing supporting elements. The anchors and elements shall be
designed for the out-of -plane forces specified in the building
code. The height- or length-to-thickness ratio between such
supporting elements for such walls shall not exceed nine.
A113.9 Truss and beam supports. Where trusses and beams
other than rafters or joists are supported on masonry, independ-
ent secondary columns shall be installed to support vertical
loads of the roof or floor members.
Exception: Secondary supports are not required where S j^i
is less than 0.3g.
A113.10 Adjacent buildings. Where elements of adjacent
buildings do not have a separation of at least 5 inches (127
mm), the allowable height-to-thickness ratios for "all other
buildings" per Table Al-B shall be used in the direction of con-
sideration.
SECTION A1 14
WALLS OF UNBURNED CLAY, ADOBE OR STONE
MASONRY
A114.1 General. Walls of unbumed clay, adobe or stone
masonry construction shall conform to the following:
1 . Walls of unbumed clay, adobe or stone masonry shall not
exceed a height- or length-to-thickness ratio specified in
Table Al-G.
2. Adobe may be allowed a maximum value of 9 pounds per
square inch (62.1 kPa) for shear unless higher values are
justified by test.
3. Mortar for repointing may be of the same soil composi-
tion and stabilization as the brick, in lieu of cement-mor-
tar.
12
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
TABLE A1 -A— ELEMENTS REGULATED BY THIS CHAPTER
BUILDING ELEMENTS
So^
>0.067„<0.133p
3 0.133„<0.20p
>0.20p<0.30„
>0.30^
Parapets
X
X
X
X
Walls, anchorage
X
X
X
X
Walls, h/t ratios
X
X
X
Walls, in-plane shear
X
X
X
Diaphragms^
X
X
Diaphragms, shear transfer'^
X
X
X
Diaphragms, demand-capacity ratios**
X
X
a. Applies only to buildings designed according to the general procedures of Section A 110.
b. Applies only to buildings designed according to the special procedures of Section Al 1 1.
TABLE A1-B— ALLOWABLE VALUE OF HEIGHT-TO-THICKNESS
RATIO OF UNREINFORCED MASONRY WALLS
WALL TYPES
0.13^<Sf„<0.25g
0.25^ <S^< 0.4^
So^ > 0.4^ BUILDINGS
WITH CRDSSWALLS^
Sai>0.4
ALL OTHER BuIdINGS
Walls of one-story buildings
20
16
16b>c
13
First-story wall of multistory building
20
18
16
15
Walls in top story of multistory building
14
14
14b,c
9
All other walls
20
16
16
13
a. Applies to the special procedures of Section Al 1 1 only. See Section Al 1 1 .7 for other restrictions.
b. This value of height-to- thickness ratio may be used only where mortar shear tests establish a tested mortar shear strength, v,, of not less than 1 00 pounds per square
inch (690 kPa). This value may also be used where the tested mortar shear strength is not less than 60 pounds per square inch (414 kPa), and where a visual examina-
tion of the collar joint indicates not less than 50-percent mortar coverage.
c. Where a visual examination of the collar joint indicates not less than 50-percent mortar coverage, and the tested mortar shear strength, v,, is greater than 30 pounds
per square inch (207 kPa) but less than 60 pounds per square inch (414 kPa), the allowable height-to-thickness ratio may be determined by linear interpolation
between the larger and smaller ratios in direct proportion to the tested mortar shear strength.
TABLE A1-C— HORIZONTAL FORCE FACTOR, C^
CONFIGURATION OF MATERIALS
Co
Roofs with straight or diagonal sheathing and roofing applied directly to the sheathing, or floors with straight
tongue-and-groove sheathing.
Diaphragms with double or mulitple layers of boards with edges offset, and blocked plywood systems.
Diaphragms of metal deck without topping:
Minimal welding or mechanical attachment.
Welded or mechanically attached for seismic resistance.
0.50
0.75
0.6
0.68
2010 CALIFORNIA EXISTING BUILDING CODE
13
APPENDIX CHAPTER A1
TABLE A1-D— STRENGTH VALUES FOR EXISTING MATERIALS
STRENGTH VALUES
EXISTING WIATEHfALb OH
CONFIGURATION OF MATERIALS^
X 14.594 for N/m
Horizontal
diaphragms
Roofs with straight sheathing and roofmg applied directly to the sheathing.
300 lbs. per ft. for seismic shear
Roofs with diagonal sheathing and roofing applied directly to the sheathing.
750 lbs. per ft. for seismic shear
Floors with straight tongue-and-groove sheathing.
300 lbs, per ft. for seismic shear
Floors with straight sheathing and finished wood flooring with board edges offset or
perpendicular.
1,500 lbs. per ft. for seismic shear
Floors with diagonal sheathing and finished wood flooring.
1,800 lbs. per ft. for seismic shear
Metal deck welded with minimal welding.'^
1,800 lbs, per ft. for seismic shear
Metal deck welded for seismic resistance.^
3,000 lbs. per ft. for seismic shear
Crosswalls''
Plaster on wood or metal lath.
600 lbs. per ft. for seismic shear
Plaster on gypsum lath.
550 lbs. per ft. for seismic shear
Gypsum wallboard, unblocked edges.
200 lbs. per ft. for seismic shear
Gypsum wallboard, blocked edges.
400 lbs. per ft. for seismic shear
Existing
footing, wood
framing,
structural steel,
reinforcing
steel
Plain concrete footings.
/;= 1,500 psi (10.34 MPa) unless
otherwise shown by tests
Douglas fir wood.
Same as D.F. No. 1
Reinforcing steel.
Fy = 40,000 psi (124.1 N/mm^)
maximum
Structural steel.
Fy = 33,000 psi (137.9 N/mm^)
maximum
a. Material must be sound and in good condition.
b. Shear values of these materials may be combined, except the total combined value should not exceed 900 pounds per foot (4380 N/m).
c. Minimum 22-gage steel deck with welds to supports satisfying the standards of the Steel Deck Institute.
d. Minimum 22-gage steel deck with ^/^ (p plug welds at an average spacing not exceeding 8 inches (203 mm) and with sidelap welds appropriate for the deck span.
14
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
TABLE A1-E— STRENGTH VALUES OF NEW MATERIALS USED
IN CONJUNCTION WITH EXISTING CONSTRUCTION
NEW MATERIALS OR CONFIGURATION OF MATERIALS
STRENGTH VALUES
Horizontal
diaphragms
Plywood sheathing applied directly over existing straight sheathing with
ends of plywood sheets bearing on joists or rafters and edges of plywood
located on center of individual sheathing boards.
675 lbs. per ft.
Crosswalls
Plywood sheathing applied directly over wood studs; no value should be
given to plywood applied over existing plaster or wood sheathing.
1,2 times the value specified in the current
building code.
Dry wall or plaster applied directly over wood studs.
The value specified in the current building
code.
Dry wall or plaster applied to sheathing over existing wood studs.
50 percent of the value specified in the
current building code.
Tension bolts^
Bolts extending entirely through unreinforced masonry wall secured with
bearing plates on far side of a three-wythe- minimum wall with at least 30
square inches of area.^'''
5,400 lbs. per bolt
2 JOO lbs. for two-wythe walls
Shear bolts^
Bolts embedded a minimum of 8 inches into unreinforced masonry walls;
bolts should be centered in 2V2-inch-diameter holes with dry-pack or
nonshrink grout around the circumference of the bolt.
The value for plain masonry specified for
sohd masonry in the current building
code; no value larger than those given for
V4-inch bolts should be used.
Combined tension
and shear bolts
Through-bolts — bolts meeting the requirements for shear and for tension
bolts.'''^
Tension — same as for tension bolts
Shear — same as for shear bolts
Embedded bolts — bolts extending to the exterior face of the wall with a
2V2-inch round plate under the head and drilled at an angle of 22 V2
degrees to the horizontal; installed as specified for shear bolts/'^'^
Tension— 3,600 lbs. per bolt
Shear — same as for shear bolts
Infilled walls
Reinforced masonry infilled openings in existing unreinforced masonry
walls; provide keys or dowels to match reinforcing.
Same as values specified for unreinforced
masonry walls
Reinforced masonry"*
Masonry piers and walls reinforced per the current building code.
The value specified in the current building
code for strength design.
Reinforced concrete''
Concrete footings, walls and piers reinforced as specified in the current
building code.
The value specified in the current building
code for strength design.
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mrai^, 1 pound = 4.4 N.
a. Embedded bolts to be tested as specified in Section A 107.4.
b. Bolts to be V2 inch (12.7 mm) minimum in diameter.
c. Drilling for bolts and dowels shall be done with an electric rotary drill; impact tools should not be used for drilling holes or tightening anchors and shear bolt nuts .
d. No load factors or capacity reduction fector shall be used.
e. Other bolt sizes, values and installation methods may be used, provided a testing program is conducted in accordance with UBC Standard 21-7. The useable value
shall be determined by multiplying the calculated allowable value, as determined by UBC Standard 21-7, by 3.0, and the useable value shall be limited to a maxi-
mum of 1 .5 times the value given in the table. Bolt spacing shall not exceed 6 feet (1 829 mm) on center and shall not be less than 12 inches (305 mm) on center.
TABLE A1-F— MAXIMUM ALLOWABLE HEIGHT-TO-THICKNESS RATIOS FOR PARAPETS
Soi
o^^g<SD^<o.25g
0.25^ ^ S„ < 0.4g
SD^ ^ 0.4^
Maximum allowable height-to-thickness ratios
2.5
2.5
1.5
TABLE A1-G— MAXIMUM HEIGHT-TO-THICKNESS RATIOS FOR ADOBE OR STONE WALLS
S01
0.13^ <S^,<0.25^
0.25^ <So,<0.4^
Sdi ^ 0.4g
One-story buildings
Two-story buildings
First story
Second story
12
14
12
10
11
10
8
9
8
2010 CALIFORNIA EXISTING BUILDING CODE
15
APPENDIX CHAPTER A1
P
LU
UJ
LL
QC E
Oq:
SO
O >«
<
cc
I
Q.
<
Q
540
480
420
360
300
240
180
120
60
1
©
\
\
y
\
\
\
\
\
\
\
\
N
/
\
®
/
/
\
V
/
/
\
/
®
\
1
\
\
12 3 4
DEMAND-CAPAClPi' RATIO, DCR
L Region of demand-capacity ratios where cross walls may be used to increase M ratios.
2. Region of demand-capacity ratios where h/t ratios of "buildings with crosswalls" may be used, whether or not crosswalls are present.
3. Region of demand-capacity ratios where h/t ratios of '*all other buildings" shall be used, whether or not crosswalls are present.
FIGURE A1-1
ACCEPTABLE DIAPHRAGM SPAN
16
2010 CALIFORNIA EXISTING BUILDING CODE
APPENDIX CHAPTER A1
IN EACH PIER
ROCKING
CONTROLLED
MODE
COMPARE
V.ANDV^a
IN EACH PIER
SHEAR FORCE IN AN
INDIVIDUAL PIER IS
PROPORTIONAL TO
PoO/H, INDIVIDUAL
PIERS CAN ROCK
SAFELY
tin^^m,
f^_ ' — (ok)
ROCKING SHEAR IS
ADEQUATE; ROCmNO
OFPIERSYSTEMIS
SAf=E
(D
SHEAR
COHTROLLEP
l«OD£
IN AT LEAST
ONEPtER
ALl:PIERS
RELATIVE
RIC^IDITY
ANAirt'SlS
SHEAR FORCE IN AN
INDIVfDUALPlERIS
PRCiPdRTIQNALtO
ROCKING SHEAR OF
PIER SYSTEM IS NOT
ADEQUATE
RETURN
INM LEAST
GNEPIER
OMIT FROM / — \
ANALYSIS ANY ( 3 )
PIER WITH V^^Vp ^ — ^
DISTRIBUTION OF
SHEAR FORCES IN
PIERS CANNOT BE
DETERMINED
RETURN
SHEAR STRESS IS
OK
PIERISQVERSTRESSED
IN SHEAR
RETURN
Vq = Allowable shear strength of a pier
Vp = Shear force assigned to a pier on the basis of a relative shear rigidity analysis.
V^ - Rocking shear capacity of pier.
^wx ~ Total shear force resisted by the wall.
l,Vr- Rocking shear capacity of all piers in the wall.
FIGURE A1 -2
ANALYSIS OF URM WALL IN-PLANE SHEAR FORCES
2010 CALIFORNIA EXISTING BUILDING CODE
17
18 2010 CALIFORNIA EXISTING BUILDING CODE
REFERENCED STANDARDS
UNIFORM BUILDING CODE STANDARD 21-4
HOLLOW AND SOLID LOAD-BEARING
CONCRETE MASONRY UNITS
Based on Standard Specification C 90-95 of the ASTM International.
Extracted, with permission, from the Annual Book of ASTM Standards, copyright
ASTIM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428
Note: See Appendix Chapter 1, Section A106, California Existing Building Code
Section 21 .401 — Scope
This standard covers solid (units with 75 percent or more net
area) and hollow load-bearing concrete masonry units made
from Portland cement, water and mineral aggregates with or
without the inclusion of other materials.
Section 21 .402 — Classification
21.402.1 Types. Two types of concrete masonry units in each
of two grades are covered as follows:
21.402.1.1 Type I, moisture-controlled units. Units desig-
nated as Type I shall conform to all requirements of this stan-
dard including the moisture content requirements of Table
2 1-4- A.
21.402.1.2 Type II, nonmoisture-controlled units. Units des-
ignated as Type II shall conform to all requirements of this
standard except the moisture content requirements of Table
21-4-A.
21.402.2 Grades. Concrete masonry units manufactured in
accordance with this standard shall conform to two grades as
follows:
21.402.2.1 Grade N. Units having a weight classification of 85
pcf (1360 kg/m^) or greater, for general use such as in exterior
walls below and above grade that may or may not be exposed to
moisture penetration or the weather and for interior walls and
backup.
21.402.2.2 Grade S. Units having a weight classification of
less than 85 pcf (1360 kg/m^), for uses limited to above-grade
installation in exterior walls with weather-protective coatings
and in walls not exposed to the weather.
Section 21.403 — l\/laterials
21.403.1 Cementitious materials. Materials shall conform to
the following applicable standards:
1. Portland Cement— ASTM C 150 modified as follows:
Limitation on insoluble residue — 1 .5 percent maximum.
Limitation on air content of mortar,
Volume percent — 22 percent maximum.
Limitation on loss on ignition — 7 percent maximum.
Limestone with a minimum 85 percent calcium carbon-
ate (CaC03) content may be added to the cement, pro-
vided the requirements of ASTM C 150 as modified
above are met.
2, Blended Cements— ASTM C 595.
3. Hydrated Lime, Type S— UBC Standard 21-13.
21.403.2 Other constituents and aggregates. Air-entraining
agents, coloring pigments, integral water repellents, finely
ground silica, aggregates, and other constituents, shall be pre-
viously established as suitable for use in concrete or shall be
shown by test or experience to not be detrimental to the durabil-
ity of the concrete.
Section 21 .404 — Physical Requirements
At the time of delivery to the work site, the units shall conform
to the physical requirements prescribed in Table 21-4-B. The
moisture content of Type I concrete masonry units at time of
delivery shall conform to the requirements prescribed in Table
21-4-A.
At the time of delivery to the purchaser, the linear shrinkage
of Type II units shall not exceed 0.065 percent.
Section 21.405 — (Minimum Face-shell and Web
Thicknesses
Face-shell (FST) and web (WT) thicknesses shall conform to
the requirements listed in Table 21-4-C.
Section 21 .406 — Permissible Variations in
Dimensions
21.406.1 Precision units. For precision units, no overall
dimension (width, height and length) shall differ by more than
7g inch (3.2 mm) from the specified standard dimensions.
21.406.2 Particular feature units. For particular feature units,
dimensions shall be in accordance with the following:
1. For molded face units, no overall dimension (width,
height and length) shall differ by more than Vg inch (3.2
mm) from the specified standard dimension. Dimensions
of molded features (ribs, scores, hex-shapes, patterns,
etc.) shall be within Vjg inch (1.6 mm) of the specified
standard dimensions and shall be within Vie inch (1.6
mm) of the specified placement of the unit.
2. For split-faced units, all non- split overall dimensions
(width, height and length) shall differ by no more than Vg
2010 CALIFORNIA EXISTING BUILDING CODE
19
REFERENCED STANDARDS
inch (3.2 mm) from the specified standard dimensions.
On faces that are spUt, overall dimensions will vary. Lo-
cal suppliers should be consulted to determine dimen-
sional tolerances achievable.
3. For slumped units, no overall height dimension shall dif-
fer by more than Vg inch (3.2 mm) from the specified
standard dimension. On faces that are slumped, overall
dimensions will vary. Local suppliers should be con-
sulted to determine dimension tolerances achievable.
Note: Standard dimensions of units are the manufacturer's des-
ignated dimensions. Nominal dimensions of modular size
units, except slumped units, are equal to the standard dimen-
sions plus Vg inch (9.5 mm), the thickness of one standard mor-
tar joint. Slumped units are equal to the standard dimensions
plus V2 inch (13 mm), the thickness of one standard mortar
joint. Nominal dimensions of nonmodular size units usually
exceed the standard dimensions by Vg inch to V4 inch (3.2 mm
to 6.4 mm).
Section 21 .407 — Visual Inspection
All units shall be sound and free of cracks or other defects that
would interfere with the proper placing of the unit or impair the
strength or permanence of the construction. Units may have
minor cracks incidental to the usual method of manufacture, or
minor chipping resulting from customary methods of handling
in shipment and delivery.
Units that are intended to serve as a base for plaster or stucco
shall have a sufficiently rough surface to afford a good bond.
Where units are to be used in exposed wall construction, the
face or faces that are to be exposed shall be free of chips, cracks
or other imperfections when viewed from 20 feet (6100 mm),
except that not more than 5 percent of a shipment may have
slight cracks or small chips not larger than 1 inch (25.4 mm).
Section 21 .408 — IVIethods of Sampling and Testing
The purchaser or authorized representative shall be accorded
proper facilities to inspect and sample the units at the place of
manufacture from the lots ready for delivery.
Sample and test units in accordance with ASTM C 140.
Total linear drying shrinkage shall be based on tests of con-
crete masonry units made with the same materials, concrete
mix design, manufacturing process and curing method, con-
ducted in accordance with ASTM C 426 and not more than 24
months prior to delivery.
Section 21 ,409 — Rejection
If the samples tested from a shipment fail to conform to the
specified requirements, the manufacturer may sort it, and new
specimens shall be selected by the purchaser from the retained
lot and tested at the expense of theO manufacturer. If the second
set of specimens fails to conform to the specified requirements,
the entire lot shall be rejected.
TABLE 21-4-A
MOISTURE CONTENT REQUIREMENTS FOR TYPE I UNITS
LINEAR SHRINKAGE, PERCENT
MOISTURE CONTENT, MAX. PERCENT OF TOTAL ABSORPTION
(Average of 3 Units)
Humidity Conditions at Job site or Point of Use
Humid^
Intermediate^
Arid^
0.03 or less
From 0.03 to 0.045
0.045 to 0.065, max.
45
40
35
40
35
30
35
30
25
^Average annual relative humidity above 75 percent.
^Average annual relative humidity 50 to 75 percent.
^Average annual relative humidity less than 50 percent.
TABLE 21--4-B
STRENGTH AND ABSORPTION REQUIREMENTS
COMPRESSIVE STRENGTH, MIN, psi (MPa)
WATER ABSORPTION, MAX, Ibyft. (I^g/m) (Average of 3 Units)
Average Net Area
Weight Classification— Oven-dry Weight of Concrete, ibift. (kg/m )
Individual Unit
Lightweight,
Less than 105 (1680)
Medium Weight,
105 to less than 125
(1680-2000)
Normal Weight,
125 (2000) or more
1900(13.1)
1700(11.7)
18 (288)
15 (240)
13 (208)
20
2010 CALIFORNIA EXISTING BUILDING CODE
REFERENCED STANDARDS
TABLE 21-4-C
MINIMUM THICKNESS OF FACE-SHELLS AND WEBS
NOMINAL WIDTH (W) OF UNIT
(inches)
FACE-SHELL THICKNESS
(FST)MIN., (inches)^*
WEB THICKNESS (WT)
Webs^ Min., (Inches)
Equivalent Web Thickness,
Min., InJLin. FL^
X 25.4 for mm
X 83 for mm/lin. m
3 and 4
6
8
10
12
1
IV,
1V4^
V4
1
1
1%
2V4
2%
^Average of measurements on three units taken at the thinnest point.
^Sum of the measured thickness of all webs in the unit, multiplied by 12 (305 when using metric), and divided by the length of the unit. In the case of open-ended units
where the open-ended portion is solid grouted, the length of that open-ended portion shall be deducted from the o/erall length of the unit.
^This face-shell thickness (FST) is applicable where allowable design load is reduced in proportion to the reduction in thicknesses shown, except that allowable
design load on solid-grouted units shall not be reduced.
^For split-faced units, a maximum of 10 percent of a shipment may have face-shell thicknesses less than those shown, but in no case less than % inch (19 mm).
2010 CALIFORNIA EXISTING BUILDING CODE
21
REFERENCED STANDARDS
UNIFORM BUILDING CODE STANDARD 21-6
IN-PLACE MASONRY SHEAR TESTS
See Appendix Chapter 1, Sections A1 06.3.3 and A1 07.2, Uniform Code for Building Conservation
Note: See Appendix CfiapterAI, Section A 104, California Existing Building Code.
SECTION 21.601 — SCOPE
This standard applies when the Uniform Code for Building Conservation (California Existing Building Code) requires in-place test-
ing of the quality of masonry mortar.
SECTION 21.602 — PREPARATION OF SAMPLE
The bed joints of the outer wythe of the masonry shall be tested in shear by laterally displacing a single brick relative to the adjacent
bricks in the same wythe. The head joint opposite the loaded end of the test brick shall be carefully excavated and cleared. The brick
adjacent to the loaded end of the test brick shall be carefully removed by sawing or drilling and excavating to provide space for a
hydraulic ram and steel loading blocks.
SECTION 21.603 — APPLICATION OF LOAD AND DETERMINATION OF RESULTS
Steel blocks, the size of the end of the brick, shall be used on each end of the ram to distribute the load to the brick. The blocks shall
not contact the mortar joints. The load shall be applied horizontally, in the plane of the wythe, until either a crack can be seen or slip
occurs. The strength of the mortar shall be calculated by dividing the load at the first cracking or movement of the test brick by the
nominal gross area of the sum of the two bed joints.
UNIFORM BUILDING CODE STANDARD 21-7
TESTS OF ANCHORS IN UNREINFORCED MASONRY WALLS
See Appendix Chapter 1, Section A1 07.3 and A1 07.4, Uniform Code for Building Conservation
Note: See Appendix Chapter A 1, Section A105,A 107.3, A 107 A and
Table A1-E, California Existing Building Code.
SECTION 21.701 — SCOPE
Shear and tension anchors in existing masonry construction shall be tested in accordance with this standard when required by the
Uniform Code for Building Conservation (California Existing Building Code),
SECTION 21.702 — DIRECT TENSION TESTING OF EXISTING ANCHORS AND NEW BOLTS
The test apparatus shall be supported by the masonry wall. The distance between the anchor and the test apparatus support shall not
be less than one half the wall thickness for existing anchors and 75 percent of the embedment for new embedded bolts. Existing wall
anchors shall be given a preload of 300 pounds ( 1 335 N) prior to establishing a datum for recording elongation. The tension test load
reported shall be recorded at Vg inch (3.2 mm) relative movement of the existing anchor and the adjacent masonry surface. New
embedded tension bolts shall be subject to a direct tension load of not less than 2.5 times the design load but not less than 1,500
pounds (6672 N) for five minutes (10 percent deviation).
SECTION 21.703 — TORQUE TESTING OF NEW BOLTS
Bolts embedded in unreinforced masonry walls shall be tested using a torque-calibrated wrench to the following minimum torques:
Vj-inch-diameter (13 mm) bolts — 40 footpounds (54.2 N • m) Vg-inch-diameter (16 mm) bolts — 50 foot pounds (67.8 N • m) V4-inch-diame-
ter (19 mm) bolts— 60 foot pounds (81.3 N • m)
SECTION 21.704 — PREQUALIFICATION TEST FOR BOLTS AND OTHER TYPES OF ANCHORS
This section is applicable when it is desired to use tension or shear values for anchors greater than those permitted by Table A- 1 -E of
the Uniform Code for Building Conservation (California Existing Building Code). The direct-tension test procedure set forth in
Section 2 1.702 for existing anchors may be used to determine the allowable tension values for new embedded or through bolts,
except that no preload is required. Bolts shall be installed in the same manner and using the same materials as will be used in the
actual construction. A minimum of five tests for each bolt size and type shall be performed for each class of masonry in which they
are proposed to be used. The allowable tension values for such anchors shall be the lesser of the average ultimate load divided by a
factor of safety of 5.0 or the average load of which Vg inch (3.2 mm) elongation occurs for each size and type of bolt and class of
masonry.
Shear bolts may be similarly prequalified. The test procedure shall comply with ASTM E 488-90 or another approved procedure.
The allowable values determined in this manner may exceed those set forth in Table A-l-E of the Uniform Code for Building Con-
servation (California Existing Building Code).
SECTION 21.705 — REPORTS
Results of all tests shall be reported. The report shall include the test results as related to anchor size and type, orientation of loading,
details of the anchor installation and embedment, wall thickness, and joist orientation.
22 2010 CALIFORNIA EXISTING BUILDING CODE
REFERENCED STANDARDS
UNIFORM BUILDING CODE STANDARD 21-8
POINTING OF UNREINFORCED MASONRY WALLS
See Appendix Chapter 1, Section A1 06.3.3.2, Uniform Code for Building Conservation
Note: See Appendix Chapter A1, Section A103 and A1 06.3.3.9, California Existing Building Code.
SECTION 21.801 — SCOPE
Pointing of deteriorated mortar joints when required by the Uniform Code for Building Conservation (California Existing Building
Code) shall be in accordance with this standard.
SECTION 21.802 — JOINT PREPARATION
The old or deteriorated mortar joint shall be cut out, by means of a toothing chisel or nonimpact power tool, to a uniform depth of ^/4
inch (19 mm) until sound mortar is reached. Care shall be taken not to damage the brick edges. After cutting is complete, all loose
material shall be removed with a brush, air or water stream.
SECTION 21.803 — MORTAR PREPARATION
The mortar mix shall be Type N or Type S proportioned as required by the construction specifications. The pointing mortar shall be
pre-hydrated by first thoroughly mixing all ingredients dry and then mixing again, adding only enough water to produce a damp
unworkable mix which will retain its form when pressed into a ball. The mortar shall be kept in a damp condition for one and
one-half hours; then sufficient water shall be added to bring it to a consistency that is somewhat drier than conventional masonry
mortar.
SECTION 21.804 — PACKING
The joint into which the mortar is to be packed shall be damp but without freestanding water. The mortar shall be tightly packed into
the joint in layers not exceeding V4 inch (6.4 mm) in depth until it is filled; then it shall be tooled to a smooth surface to match the
original profile.
2010 CALIFORNIA EXISTING BUILDING CODE 23
REFERENCED STANDARDS
UNIFORM BUILDING CODE STANDARD 21-13
HYDRATED LIME FOR MASONRY PURPOSES
Based on Standard Specification C 207-91 (Reapproved 1992) of tlie ASTM International.
Extracted, with permission, from the Annual Book of ASTM Standards, copyright
ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428
See Section 2102.2, Item 3, Uniform Building Code
Note: See Referenced Standard UBC 21-4
Section 21.1301 — Scope
This standard covers four types of hydrated lime. Types N and
S are suitable for use in mortar, in the scratch and brown coats
of cement plaster, for stucco, and for addition to port-
land-cement concrete. Types NA and SA are air-entrained
hydrated limes that are suitable for use in any of the above uses
where the inherent properties of lime and air entrainment are
desired. The four types of lime sold under this specification
shall be designated as follows:
Type N — Normal hydrated lime for masonry purposes.
Type S — Special hydrated lime for masonry purposes.
Type NA — Normal air-entraining hydrated lime for
masonry purposes.
Type SA — Special air-entraining hydrated lime for
masonry purposes.
Note: Type S, special hydrated lime, and Type SA, spe-
cial air-entraining hydrated lime, are differentiated from
Type N, normal hydrated lime, and Type NA, normal
air-entraining hydrated lime, principally by their ability
to develop high, early plasticity and higher water
retentivity and by a limitation on their unhydrated oxide
content.
Section 21.1305 — Chemical Requirements
Composition
Hydrated lime for masonry purposes shall conform to the
requirements as to chemical composition set forth in Table
2I-13-A.
Section 21.1306 — Residue, Popping and Pitting
The four types of hydrated lime for masonry purposes shall
conform to one of the following requirements:
1 . The residue retained on a No. 30 (600 jam) sieve shall not
be more than 0.5 percent, or
2. If the residue retained on a No. 30 (600 jam) sieve is over
0.5 percent, the lime shall show no pops and pits when
tested.
Section 21.1307 — Plasticity
The putty made from Type S, special hydrate, or Type S A, spe-
cial air-entraining hydrate, shall have a plasticity figure of not
less than 200 within 30 minutes after mixing with water, when
tested.
Section 21.1302 — Definition
HYDRATED LIME. The hydrated lime covered by Type N or
S in this standard shall contain no additives for the purpose of
entraining air. The air content of cement-lime mortars made
with Type N or S shall not exceed 7 percent. Types NA and S A
shall contain an air-entraining additive as specified by Section
21.1305. The air content of cement-lime mortars made with
Type NA or S A shall have a minimum of 7 percent and a maxi-
mum of 14 percent.
Section 21.1303 — Additions
Types NA and S A hydrated lime covered by this standard shall
contain additives for the purpose of entraining air.
Section 21 .1308 — Water Retention
Hydrated lime mortar made with Type N, normal hydrated
lime, or Type NA, normal air-entraining hydrated lime, after
suction for 60 seconds, shall have a water-retention value of not
less than 75 percent when tested in a standard mortar made
from the dry hydrate or from putty made from the hydrate
which has been soaked for a period of 16 to 24 hours.
Hydrated lime mortar made with Type S, special hydrated
lime, or Type SA, special air-entraining hydrated lime, after
suction for 60 seconds, shall have a water-retention value of not
less than 85 percent when tested in a standard mortar made
from the dry hydrate.
Section 21.1304 — Manufacturer's Statement
Where required, the nature, amount and identity of the
air-entraining agent used and of any processing addition that
may have been used shall be provided, as well as test data
showing compliance of such air-entraining addition.
Section 21.1309 — Special Marking
When Type NA or S A air-entraining hydrated lime is delivered
in packages, the type under this standard and the words
"air-entraining" shall be plainly indicated thereon or, in case of
bulk shipments, so indicated on shipping notices.
24
2010 CALIFORNIA EXISTING BUILDING CODE
REFERENCED STANDARDS
Section 21 .1310 — Quality Control
Every 90 days, each lime producer shall retain an approved
agency to obtain a random sample from a local point of supply
in the market area served by the producer.
The agency shall test the lime for compliance with the physi-
cal requirements of Sections 21.1306, 21.1307 and 21.1308.
Upon request of the building official, the producer shall furnish
(at no cost) test results to the building official, architect, struc-
tural engineer, general contractor and masonry contractor.
TABLE 21 -13-A— CHEMICAL REQUIREMENTS
HYDRATE TYPES
N
NA
S
SA
Calcium and magnesium oxides (nonvolatile basis), min. percent
95
95
95
95
Carbon dioxide (as-received basis), max. percent
If sample is taken at place of manufacture
If sample is taken at any other place
5
7
5
7
5
7
5
7
Unhydrated oxides (as-received basis), max. percent
—
8
8
2010 CALIFORNIA EXISTING BUILDING CODE
25
26 2010 CALIFORNIA EXISTING BUILDING CODE
HISTORY NOTE APPENDIX
CALIFORNIA EXISTING BUILDING CODE
(Title 24, Part 10, California Code of Regulations)
For prior history, see the History Note Appendix to the Califor-
nia Code for Building Conservation, 2007 Triennial Edition,
effective January 1, 2008.
1. (BSC 06/09, HCD 06/09) Adoption of Appendix Chapter
Al of the 2009 International Existing Building Code with
necessary California amendments, effective January 1,
2011.
201 CALIFORNIA EXISTING BUILDING CODE 27
28 2010 CALIFORNIA EXISTING BUILDING CODE