Skip to main content

Full text of "ICC IBC (2009): International Building Code"

See other formats


mm- 



tw * * * * <w< 




> 






NOTICE OF INCORPORATION 

United States Legal Document 

$3T All citizens and residents are hereby advised that 

this is a legally binding document duly incorporated by 

reference and that failure to comply with such 

requirements as hereby detailed within may subject you 

to criminal or civil penalties under the law. Ignorance of 

the law shall not excuse noncompliance and it is the 

responsibility of the citizens to inform themselves as to 

the laws that are enacted in the United States of America 

and in the states and cities contained therein. ~^k 

* * 
* 

ICC IBC (2009), the International Building Code, 
as mandated and incorporated by the States and 
Municipalities including Alabama, Florida, 
Idaho, Iowa, Maine, Massachusetts, Michigan, 
Montana, Las Vegas (Nevada) , New Hampshire, 
New Jersey, New Mexico, North Carolina, North 
Dakota, Ohio, Oklahoma, Oregon, Pennsylvania, 
Rhode Island, Utah, West Virginia, Wisconsin, 
et. alia. 



T.sswa&.'v 



^*"*1 



a 












m^mmk:* * * * mm^mmmxm 



INTERNATIONAL CODE FAMILY^ 




INTERNATIONAL BUILDING CODE' 




Y* 



W, 



A MEMBER OF THE INTERNATIONAL CODE FAMILY® 



I 





INTERNATIONAL 
CODE COUNCIL 8 



INTERNATIONAL BUILDING CODE® 










Receive FREE updates) excerpts of code references) technical 
articles) and more when you register your code book. Go to 

www.iccsafe.org/CodesPlus today! 




2009 International Building Code® 



First Printing: February 2009 



ISBN: 978-1-58001-725-1 (soft-cover edition) 
ISBN: 978-1-58001-724-4 (loose-leaf edition) 



COPYRIGHT © 2009 

by 

INTERNATIONAL CODE COUNCIL, INC 



ALL RIGHTS RESERVED. This 2009 International Building Code®is a copyrighted work owned by the International Code Coun- 
cil, Inc. Without advance written permission from the copyright owner, no part of this book may be reproduced, distributed or trans- 
mitted in any form or by any means, including, without limitation, electronic, optical or mechanical means (by way of example, and 
not limitation, photocopying or recording by or in an information storage retrieval system). For information on permission to copy 
material exceeding fair use, please contact: Publications, 4051 West Flossmoor Road, Country Club Hills, IL 60478. Phone 
1-888-ICC-SAFE (422-7233). 

Trademarks: "International Code Council," the "International Code Council" logo and the "International Building Code" are trade- 
marks of the International Code Council, Inc. 



PRINTED IN THE U.S.A. 



PREFACE 



Introduction 

Internationally, code officials recognize the need for a modern, up-to-date building code addressing the design and installation of 
building systems through requirements emphasizing performance. The International Building Code® in this 2009 edition, is 
designed to meet these needs through model code regulations that safeguard the public health and safety in all communities, large 
and small. 

This comprehensive building code establishes minimum regulations for building systems using prescriptive and perfor- 
mance-related provisions. It is founded on broad-based principles that make possible the use of new materials and new building 
designs. This 2009 edition is fully compatible with all the International Codes @(l -Codes (p> published by the International Code 
Council (ICC) @, including the International Energy Conservation Code @ International Existing Building Code @ International 
Fire Code @ International Fuel Gas Code @ International Mechanical Code (2) ICC Performance Code @ International Plumbing 
Code @ International Private Sewage Disposal Code @ International Property Maintenance Code @ International Residential 
Code @ International Wildland-Urban Interface Code™ and International Zoning Code® 

The International Building Code provisions provide many benefits, among which is the model code development process that 
offers an international forum for building professionals to discuss performance and prescriptive code requirements. This forum pro- 
vides an excellent arena to debate proposed revisions. This model code also encourages international consistency in the application 
of provisions. 

Development 

The first edition of the International Building Code (2000) was the culmination of an effort initiated in 1997 by the ICC. This 
included five drafting subcommittees appointed by ICC and consisting of representatives of the three statutory members of the 
International Code Council at that time, including: Building Officials and Code Administrators International, Inc. (BOCA), Inter- 
national Conference of Building Officials (1CBO) and Southern Building Code Congress International (SBCCI). The intent was to 
draft a comprehensive set of regulations for building systems consistent with and inclusive of the scope of the existing model codes. 
Technical content of the latest model codes promulgated by BOCA, ICBO and SBCCI was utilized as the basis for the development, 
followed by public hearings in 1997, 1998 and 1999 to consider proposed changes. This 2009 edition presents the code as originally 
issued, with changes reflected in the 2003 and 2006 editions and further changes approved through the ICC Code Development Pro- 
cess through 2008. A new edition such as this is promulgated every 3 years. 

This code is founded on principles intended to establish provisions consistent with the scope of a building code that adequately 
protects public health, safety and welfare; provisions that do not unnecessarily increase construction costs; provisions that do not 
restrict the use of new materials, products or methods of construction; and provisions that do not give preferential treatment to par- 
ticular types or classes of materials, products or methods of construction. 

Adoption 

The International Building Code is available for adoption and use by jurisdictions internationally. Its use within a governmental 
jurisdiction is intended to be accomplished through adoption by reference in accordance with proceedings establishing thejurisdic- 
tion's laws. At the time of adoption, jurisdictions should insert the appropriate information in provisions requiring specific local 
information, such as the name of the adopting jurisdiction. These locations are shown in bracketed words in small capital letters in 
the code and in the sample ordinance. The sample adoption ordinance on page xv addresses several key elements of a code adoption 
ordinance, including the information required for insertion into the code text. 

Maintenance 

The International Building Code is kept up to date through the review of proposed changes submitted by code enforcing officials, 
industry representatives, design professionals and other interested parties. Proposed changes are carefully considered through an 
open code development process in which all interested and affected parties may participate. 

The contents of this work are subject to change both through the Code Development Cycles and the governmental body that 
enacts the code into law. For more information regarding the code development process, contact the Code and Standard Develop- 
ment Department of the International Code Council. 

While the development procedure of the International Building Code assures the highest degree of care, ICC, its members and 
those participating in the development of this code do not accept any liability resulting from compliance or noncompliance with the 
provisions because ICC does not have the power or authority to police or enforce compliance with the contents of this code. Only the 
governmental body that enacts the code into law has such authority. 

2009 INTERNATIONAL BUILDING CODE® iii 



Letter Designations in Front of Section Numbers 

In each code development cycle, proposed changes to the code are considered at the Code Development Hearings by the applicable 
ICC Code Development Committee, whose action constitutes a recommendation to the voting membership for final action on the 
proposed change. Proposed changes to a code section that has a number beginning with a letter in brackets are considered by a dif- 
ferent code development committee. For example, proposed changes to code sections that have [F] in front of them (e.g., [F] 
903.1.1.1) are considered by the ICC Fire Code Development Committee at the code development hearings. 

The content of sections in this code that begin with a letter designation are maintained by another code development committee in 
accordance with the following : 

\E\ = International Energy Conservation Code Development Committee; 

[EB] = International Existing Building Code Development Committee; 

[F] = International Fire Code Development Committee; 

[FG] = International Fuel Gas Code Development Committee; 

[M] = International Mechanical Code Development Committee; and 

[P] = International Plumbing Code Development Committee. 

Marginal Markings 

Solid vertical lines in the margins within the body of the code indicate a technical change from the requirements of the 2006 edition. 
Deletion indicators in the form of an arrow (■► ) are provided in the margin where an entire section, paragraph, exception or table 
has been deleted or an item in a list of items or a table has been deleted. 

Chapter 7 user note: Chapter 7 of the code has been reorganized from the 2006 edition as a result of an approved code change 
proposal. This proposal renumbered what was Section 714 in the 2006 edition to Section 704 in this edition, which in turn resulted in 
renumbering Sections 704 through 713 in the 2006 edition to Sections 705 through 714 in this edition. Marginal markings are 
included at each section number but have not been included to reflect the subsection renumbering. 

Coordination between the International Building and Fire Codes 

Because the coordination of technical provisions is one of the benefits of adopting the ICC family of model codes, users will find the 
ICC codes to be a very flexible set of model documents. To accomplish this flexibility some technical provisions are duplicated in 
some of the model code documents. While the International Codes are provided as a comprehensive set of model codes for the built 
environment, documents are occasionally adopted as a stand-alone regulation. When one of the model documents is adopted as the 
basis of a stand-alone code, that code should provide a complete package of requirements with enforcement assigned to the entity 
for which the adoption is being made. 

The model codes can also be adopted as a family of complimentary codes. When adopted together there should be no conflict of 
any of the technical provisions. When multiple model codes are adopted in ajurisdiction it is important for the adopting authority to 
evaluate the provisions in each code document and determine how and by which agency(ies) they will be enforced. It is important, 
therefore, to understand that where technical provisions are duplicated in multiple model documents that enforcement duties must 
be clearly assigned by the local adoptingjurisdiction. ICC remains committed to providing state-of-the-art model code documents 
that, when adopted locally, will reduce the cost to government of code adoption and enforcement and protect the public health, 
safety and welfare. 

Italicized Terms 

Selected terms set forth in Chapter 2, Definitions, are italicized where they appear in code text (except those in Sections 1903 
through 1908 where italics indicate provisions that differ from ACI 318). Such terms are not italicized where the definition set forth 
in Chapter 2 does not impart the intended meaning in the use of the term. The terms selected have definitions which the user should 
read carefully to facilitate better understanding of the code. 



2009 INTERNATIONAL BUILDING CODE® 



Effective Use of the International Building Code 



The International Building Code @(IBC(£) is a model code that provides minimum requirements to safeguard the public health, 
safety and general welfare of the occupants of new and existing buildings and structures. The IBC is fully compatible with the ICC 
family of codes, including: International Energy Conservation CWe®(IECC(8), International Existing Building Code®(IEBC($), 
International Fire Code®(lFC®), International Fuel Gas Code® (IFGC (S), International Mechanical Code® (IMC®), ICC Perfor- 
mance Code®(ICCPC($), International Plumbing Code® (IPC (§), International Private Sewage Disposal Code®(IPSDC($), Interna- 
tional Property Maintenance Code® (IPMC(S), International Residential Code® (IRC(§), International Wildland-Urban Interface 
Code™ (IWUICd) and International Zoning Code® (IZCd). 

The IBC addresses structural strength, means of egress, sanitation, adequate lighting and ventilation, accessibility, energy con- 
servation and life safety in regards to new and existing buildings, facilities and systems. The codes are promulgated on a 3-year cycle 
to allow for new construction methods and technologies to be incorporated into the codes. Alternative materials, designs and meth- 
ods not specifically addressed in the code can be approved by the code official where the proposed materials, designs or methods 
comply with the intent of the provisions of the code (see Section 104.11). 

The IBC applies to all occupancies, including one- and two-family dwellings and townhouses that are not within the scope of the 
IRC. The IRC is referenced for coverage of detached one- and two-family dwellings and townhouses as defined in the Exception to 
Section 101.2 and the definition for "townhouse" in Chapter 2. The IBC applies to all types of buildings and structures unless 
exempted. Work exempted from permits is listed in Section 105.2. 

Arrangement and Format of the 2009 IBC 

Before applying the requirements of the IBC, it is beneficial to understand its arrangement and format. The IBC, like other codes 
published by ICC, is arranged and organized to follow sequential steps that generally occur during a plan review or inspection. 



Chapters 


Subjects 


1-2 


Administration and definitions 


3 


Use and occupancy classifications 


4,31 


Special requirements for specific occupancies or elements 


5-6 


Height and area limitations based on type of construction 


7-9 


Fire resistance and protection requirements 


10 


Requirements for evacuation 


11 


Specific requirements to allow use and access to a building for persons with disabilities 


12-13,27-30 


Building systems, such as lighting, HVAC, plumbing fixtures, elevators 


14-26 


Structural components-performance and stability 


32 


Encroachment outside of property lines 


33 


Safeguards during construction 


34 


Existing building allowances 


35 


Referenced standards 


Appendices A-K 


Appendices 



2009 INTERNATIONAL BUILDING CODE® 



The IBC requirements for high hazard, fire-resistance-rated construction, interior finish, fire protection systems, means of 
egress, emergency and standby power, and temporary structures are directly correlated with the requirements of the IFC. The fol- 
lowing chapters/sections of the IBC are correlated to the IFC: 



IBC 
Chapter/Section 


IFC 
Chapter/Section 


Subject 


Sections 307,414,415 


Chapters 27-44 


High-hazard requirements 


Chapter 7 


Chapter 7 


Fire- resistance- rated construction 


Chapter 8 


Chapter 8 


Interior finish, decorative materials and furnishings 


Chapter 9 


Chapter 9 


Fire protection systems 


Chapter 10 


Chapter 10 


Means of egress 


Chapter 27 


Section 604 


Standby and emergency power 


Section 3103 


Chapter 24 


Temporary structures 



The IBC requirements for smoke control systems, and smoke and fire dampers are directly correlated to the requirements of the 
IMC. IBC Chapter 28 is a reference to the IMC and the IFGC for chimney, fireplaces and barbeques, and all aspects of mechanical 
systems. The following chapters/sections of the IBC are correlated with the IMC: 



IBC 
Chapter/Section 


IMC 
Chapter/Section 


Subject 


Section 716 


Section 607 


Smoke and fire dampers 


Section 909 


Section 513 


Smoke control 



The IBC requirements for plumbing fixtures and toilet rooms are directly correlated to the requirements of the IPC. The following 
chapters/sections of the IBC are correlated with the IPC: 



IBC 
Chapter/Section 


IPC 
Chapter/Section 


Subject 


Chapter 29 


Chapters 3 & 4 


Plumbing fixtures and facilities 



The following is a chapter-by-chapter synopsis of the scope and intent of the provisions of the International Building Code. 

Chapter 1 Scope and Administration. Chapter 1 establishes the limits of applicability of the code and describes how the code is to 
be applied and enforced. Chapter 1 is in two parts, Part I-Scope and Application (Sections 101-102) and Part 2-Administration 
and Enforcement (Sections 103-1 16). Section 101 identifies which buildings and structures come under its purview and references 
other ICC codes as applicable. Standards and codes are scoped to the extent referenced (see Section 102.4). 

The building code is intended to be adopted as a legally enforceable document and it cannot be effective without adequate provi- 
sions for its administration and enforcement. The provisions of Chapter 1 establish the authority and duties of the code official 
appointed by thejurisdiction having authority and also establish the rights and privileges of the design professional, contractor and 
property owner. 

Chapter 2 Definitions. All terms that are defined in the code are listed alphabetically in Chapter 2. Terms are defined in Chapter 2 
or there is a reference to the section where the definition is located. While a defined term may be listed in one chapter or another, the 
meaning is applicable throughout the code. 

Codes are technical documents and every word, term and punctuation mark can impact the meaning of the code text and the 
intended results. The code often uses terms that have a unique meaning in the code and the code meaning can differ substantially 
from the ordinarily understood meaning of the term as used outside of the code. Where understanding of a term's definition is espe- 
cially key to or necessary for understanding a particular code provision, the term is shown in italics wherever it appears in the code. 



2009 INTERNATIONAL BUILDING CODE® 



This is true only for those terms that have a meaning that is unique to the code. In other words, the generally understood meaning 
of a term or phrase might not be sufficient or consistent with the meaning prescribed by the code; therefore, it is essential that the 
code-defined meaning be known. 

Definitions are deemed to be of prime importance in establishing the meaning and intent of the code text that uses the terms. The 
user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of 
the code and because the user may not be aware that a term is defined. 

Chapter 3 Use and Occupancy Classification. Chapter 3 provides for the classification of buildings, structures and parts thereof 
based on the purpose or purposes for which they are used. Section 302 identifies the groups into which all buildings, structures and 
parts thereof must be classified. Sections 303 through 312 identify the occupancy characteristics of each group classification. In 
some sections, specific group classifications having requirements in common are collectively organized such that one term applies 
to all. For example, Groups A-I, A-2, A-3, A-4 and A-5 are individual groups for assembly-type buildings. The general term 
"Group A," however, includes each of these individual groups. Other groups include Business (B), Educational (E), Factory (F-l, 
F-2), High Hazard (H-l, H-2, H-3, H-4, H-5), Institutional (1-1, 1-2, 1-3, 1-4), Mercantile (M), Residential (R-l, R-2, R-3, R-4), Stor- 
age (S-I, S-2) and Utility (U). In some occupancies, the smaller number means a higher hazard, but that is not always the case. 

Defining the use of the buildings is very important as it sets the tone for the remaining chapters of the code. Occupancy works 
with the height, area and construction type requirements in Chapters 5 and 6, as well as the special provisions in Chapter 4, to deter- 
mine" equivalent risk," or providing a reasonable level of protection or life safety for building occupants. The determination of 
equivalent risk involves three interdependent considerations: (1) the level of fire hazard associated with the specific occupancy of 
the facility; (2) the reduction of fire hazard by limiting the floor area(s) and the height of the building based on the fuel load (combus- 
tible contents and burnable building components) and (3) the level of overall fire resistance provided by the type of construction 
used for the building. The greater the potential fire hazards indicated as a function of the group, the lesser the height and area allow- 
ances for a particular construction type. 

Occupancy classification also plays a key part in organizing and prescribing the appropriate protection measures. As such, 
threshold requirements for fire protection and means of egress systems are based on occupancy classification (see Chapters 9 and 
10). Other sections of the code also contain requirements respective to the classification of building groups. For example, Section 
706 deals with requirements for fire wall fire-resistance ratings that are tied to the occupancy classification of a building and Section 
803.9 contains interior finish requirements that are dependent upon the occupancy classification. The use of the space, rather than 
the occupancy of the building is utilized for determining occupant loading (Section 1004) and live loading (Section 1607). 

Chapter 4 Special Detailed Requirements Based On Use and Occupancy. Chapter 4 contains the requirements for protecting 
special uses and occupancies, which are supplemental to the remainder of the code. Chapter 4 contains provisions that may alter 
requirements found elsewhere in the code; however, the general requirements of the code still apply unless modified within the 
chapter. For example, the height and area limitations established in Chapter 5 apply to all special occupancies unless Chapter 4 con- 
tains height and area limitations. In this case, the limitations in Chapter 4 supersede those in other sections. An example of this is the 
height and area limitations for open parking garages given in Section 406.3.5, which supersede the limitations given in Section 503. 

In some instances, it may not be necessary to apply the provisions of Chapter 4. For example, if a covered mall building complies 
with the provisions of the code for Group M, Section 402 does not apply; however, other sections that deal with a use, process or 
operation must be applied to that specific occupancy, such as stages and platforms, special amusement buildings and hazardous 
materials (Sections 410,411 and 414). 

The chapter includes requirements for buildings and conditions that apply to one or more groups, such as high-rise buildings, 
underground buildings or atriums. Special uses may also imply specific occupancies and operations, such as for Group H, hazard- 
ous materials, application of flammable finishes, drying rooms, organic coatings and combustible storage or hydrogen cutoff 
rooms, all of which are coordinated with the IFC. Unique consideration is taken for special use areas, such as covered mall build- 
ings, motor-vehicle-related occupancies, special amusement buildings and aircraft-related occupancies. Special facilities within 
other occupancies are considered, such as stages and platforms, motion picture projection rooms and storm shelters. Finally, in 
order that the overall package of protection features can be easily understood, unique considerations for specific occupancies are 
addressed: Groups 1-1,1-2,1-3, R-l, R-2, R-3 (by definition R-4), ambulatory care facilities and live/work units. 

Chapter 5 General Building Heights and Areas. Chapter 5 contains the provisions that regulate the minimum type of construc- 
tion for area limits and height limits based on the occupancy of the building. Height and area increases (including allowances for 
basements, mezzanines and equipment platforms) are permitted based on open frontage for fire department access, and the type of 
sprinkler protection provided and separation (Sections 503-506, 509). These thresholds are reduced for buildings over three stories 
in height in accordance with Section 506.4.1. Provisions include the protection and/or separation of incidental accessory occupan- 
cies (Table 508.2.5), accessory occupancies (Sections 508.2) and mixed uses in the same building (Sections 506.5, 508.3, 508.4 and 
509). Unlimited area buildings are permitted in certain occupancies when they meet special provisions (Section 507). 



2009 INTERNATIONAL BUILDING CODE® 



Table 503 is the keystone in setting thresholds for building size based on the building's use and the materials with which it is con- 
structed. If one then looks at Table 503, the relationship among group classification, allowable heights and areas and types of con- 
struction becomes apparent. Respective to each group classification, the greater the fire-resistance rating of structural elements, as 
represented by the type of construction, the greater the floor area and height allowances. The greater the potential fire hazards indi- 
cated as a function of the group, the lesser the height and area allowances for a particular construction type. 

Chapter 6 Types of Construction. The interdependence of these fire safety considerations can be seen by first looking at Tables 
601 and 602, which show the fire-resistance ratings of the principal structural elements comprising a building in relation to the five 
classifications for types of construction. Type I construction is the classification that generally requires the highest fire-resistance 
ratings for structural elements, whereas Type V construction, which is designated as a combustible type of construction, generally 
requires the least amount of fire-resistance-rated structural elements. The greater the potential fire hazards indicated as a function of 
the group, the lesser the height and area allowances for a particular construction type. Section 603 includes a list of combustible ele- 
ments that can be part of a noncombustible building (Types I and II construction). 

Chapter 7 Fire and Smoke Protection Features. The provisions of Chapter 7 present the fundamental concepts of fire perfor- 
mance that all buildings are expected to achieve in some form. This chapter identifies the acceptable materials, techniques and meth- 
ods which proposed construction can be designed and evaluated against to determine a building's ability to limit the impact of fire. 
The fire-resistance-rated construction requirements within Chapter 7 provide passive resistance to the spread and effects of fire. 
Types of separations addressed include fire walls, fire barriers, fire partitions, horizontal assemblies, smoke barriers and smoke par- 
titions. A fire produces heat that can weaken structural components and smoke products that cause property damage and place occu- 
pants at risk. The requirements of Chapter 7 work in unison with height and area requirements (Chapter 5), active fire detection and 
suppression systems (Chapter 9) and occupant egress requirements (Chapter 10) to contain a fire should it occur while helping 
ensure occupants are able to safely exit. 

Chapter 8 Interior Finishes. This chapter contains the performance requirements for controlling fire growth within buildings by 
restricting interior finish and decorative materials. Past fire experience has shown that interior finish and decorative materials are 
key elements in the development and spread of fire. The provisions of Chapter 8 require materials used as interior finishes and deco- 
rations to meet certain flame-spread index or flame-propagation criteria based on the relative fire hazard associated with the occu- 
pancy. As smoke is also a hazard associated with fire, this chapter contains limits on the smoke development characteristics of 
interior finishes. The performance of the material is evaluated based on test standards. 

Chapter 9 Fire Protection Systems. Chapter 9 prescribes the minimum requirements for active systems of fire protection equip- 
ment to perform the following functions: detect a fire; alert the occupants or fire department of a fire emergency; and control smoke 
and control or extinguish the fire. Generally, the requirements are based on the occupancy, the height and the area of the building, 
because these are the factors that most affect fire-fighting capabilities and the relative hazard of a specific building or portion 
thereof. This chapter parallels and is substantially duplicated in Chapter 9 of the International Fire Code (IFC); however, the IFC 
Chapter 9 also contains periodic testing criteria that are not contained in the IBC. In addition, the special fire protection system 
requirements based on use and occupancy found in IBC Chapter 4 are duplicated in IFC Chapter 9 as a user convenience. 

Chapter 10 Means of Egress. The general criteria set forth in Chapter 10 regulating the design of the means of egress are estab- 
lished as the primary method for protection of people in buildings by allowing timely relocation or evacuation of building occu- 
pants. Both prescriptive and performance language is utilized in this chapter to provide for a basic approach in the determination of a 
safe exiting system for all occupancies. It addresses all portions of the egress system (i.e., exit access, exits and exit discharge) and 
includes design requirements as well as provisions regulating individual components. The requirements detail the size, arrange- 
ment, number and protection of means of egress components. Functional and operational characteristics also are specified for the 
components that will permit their safe use without special knowledge or effort. The means of egress protection requirements work 
in coordination with other sections of the code, such as protection of vertical openings (see Chapter 7), interior finish (see Chapter 
8), fire suppression and detection systems (see Chapter 9) and numerous others, all having an impact on life safety. Chapter 10 of the 
IBC is duplicated in Chapter 10 of the IFC; however, the IFC contains two additional sections on the means of egress system in exist- 
ing buildings. 

Chapter 11 Accessibility. Chapter 11 contains provisions that set forth requirements for accessibility of buildings and their associ- 
ated sites and facilities for people with physical disabilities. The fundamental philosophy of the code on the subject of accessibility 
is that everything is required to be accessible. This is reflected in the basic applicability requirement (see Section 1103.1). The 
code's scoping requirements then address the conditions under which accessibility is not required in terms of exceptions to this gen- 
eral mandate. While the IBC contains scoping provisions for accessibility (e.g., what, where and how many), ICC/ ANSI AI17.1, 
Accessible and Usable Buildings and Facilities, is the referenced standard for the technical provisions (i.e., how). 

There are many accessibility issues that not only benefit people with disabilities, but also provide a tangible benefit to people 
without disabilities. This type of requirement can be set forth in the code as generally applicable without necessarily identifying it 



2009 INTERNATIONAL BUILDING CODE® 



specifically as an accessibility-related issue. Such a requirement would then be considered as having been "mainstreamed." For 
example, visible alarms are located in Chapter 9 and ramp requirements are addressed in Chapter 10. 

Accessibility criteria for existing buildings are addressed in Section 341 1. Appendix E is supplemental information included in 
the code to address accessibility for items in the new Americans with Disabilities Act/ Architectural Barriers Act Accessibility 
Guidelines (AD A/ ABA) that were not typically enforceable through the standard traditional building code enforcement approach 
system (e.g., beds, room signage). The International Residential Code (IRC) references Chapter 11 for accessibility provisions; 
therefore, this chapter may be applicable to housing covered under the IRC. 

Chapter 12 Interior Environment. Chapter 12 provides minimum standards for the interior environment of a building. The stan- 
dards address the minimum sizes of spaces, minimum temperature levels, and minimum light and ventilation levels. The collection 
of requirements addresses limiting sound transmission through walls, ventilation of attic spaces and under floor spaces (crawl 
spaces). Finally, the chapter provides minimum standards for walls, partitions and floors to resist water intrusion and damage in 
rooms such as toilet and shower facilities, where water is frequently in use. 

Chapter 13 Energy Efficiency. The purpose of Chapter 13 is to provide minimum design requirements that will promote efficient 
utilization of energy in buildings. The requirements are directed toward the design of building envelopes with adequate thermal 
resistance and low air leakage, and toward the design and selection of mechanical, water heating, electrical and illumination systems 
that promote effective use of depletable energy resources. For the specifics of these criteria, Chapter 13 requires design and con- 
struction in compliance with the International Energy Conservation Code (IECC). 

Chapter 14 Exterior Walls. This chapter addresses requirements for exterior walls of buildings. Minimum standards for wall cov- 
ering materials, installation of wall coverings and the ability of the wall to provide weather protection are provided. This chapter 
also requires exterior walls that are close to lot lines, or that are bearing walls for certain types of construction, to comply with the 
minimum fire-resistance ratings specified in Chapters 6 and 7. The installation of each type of wall covering, be it wood, masonry, 
vinyl, metal composite material or an exterior insulation and finish system, is critical to its long-term performance in protecting the 
interior of the building from the elements and the spread of fire. Special attention to the use of combustible materials on the exterior 
of the building such as balconies, eaves, decks and architectural trim is the focus of Section 1406. 

Chapter 15 Roof Assemblies and Rooftop Structures. Chapter 15 provides standards for both roof assemblies as well as struc- 
tures which sit on top of the roof of buildings. The criteria address roof construction and covering which includes the weather-pro- 
tective barrier at the roof and, in most circumstances, a fire-resistant barrier. The chapter is prescriptive in nature and is based on 
decades of experience with various traditional materials. These prescriptive rules are very important for satisfying performance of 
one type of roof covering or another. Section 1509 addresses rooftop structures including penthouses, tanks, towers and spires. 
Rooftop penthouses larger than prescribed in this chapter must be treated as a story under Chapter 5. 

Chapter 16 Structural Design. Chapter 16 prescribes minimum structural loading requirements for use in the design and construc- 
tion of buildings and structural components. It includes minimum design loads, as well as permitted design methodologies. Stan- 
dards are provided for minimum design loads (live, dead, snow, wind, rain, flood and earthquake as well as load combinations). The 
application of these loads and adherence to the serviceability criteria will enhance the protection of life and property. The chapter 
references and relies on many nationally recognized design standards. A key standard is the American Society of Civil Engineer's 
Minimum Design Loads for BUildings and Other Structures (ASCE 7). Structural design needs to address the conditions of the site 
and location. Therefore maps of rainfall, seismic, snow and wind criteria in different regions are provided. 

Chapter 17 Structural Tests and Special Inspections. Chapter 17 provides a variety of procedures and criteria for testing materi- 
als and assemblies, for labeling materials and assemblies, and for special inspection of structural assemblies. This chapter expands 
on the requirements of Chapter 1 regarding the roles and responsibilities of the building official regarding approval of building com- 
ponents. It also provides additional duties and responsibilities for the owner, contractor, design professionals and special inspectors. 
Proper assembly of structural components, proper quality of materials used, and proper application of materials are essential to 
ensuring that a building, once constructed, complies with the structural and fire-resistance minimums of the code and the approved 
design. To determine this compliance often requires continuous or frequent inspection and testing. Chapter 17 establishes these spe- 
cial inspection and testing standards as well as reporting of the work to the building official. 

Chapter 18 Soils and Foundations. Chapter 18 contains minimum requirements for design, construction and resistance to water 
intrusion of foundation systems for buildings and other structures. It provides criteria for the geotechnical and structural consider- 
ations in the selection and installation of adequate support for the loads transferred from the structure above. The uncertainties of 
foundation construction make it extremely difficult to address every potential failure within the text of the code. The chapter 
includes requirements for soils investigation and site preparation for receiving a foundation including the allowed load-bearing val- 
ues for soils and for protecting the foundation from water intrusion. Section 1808 addresses the basic requirements for all founda- 
tion types. Later sections address foundation requirements that are specific to shallow foundations and deep foundations. Due care 



2009 INTERNATIONAL BUILDING CODE® 



must be exercised in the planning and design of foundation systems based on obtaining sufficient soils information, the use of 
accepted engineering procedures, experience and good technical judgment. 

Chapter 19 Concrete. This chapter provides minimum accepted practices to the design and construction of buildings and structural 
components using concrete-both plain and reinforced. Chapter 19 is formatted to parallel American Concrete Institute (ACI) 318, 
BUilding Code Requirements for Structural Concrete. The chapter also includes references to additional standards. Structural con- 
crete must be designed and constructed to comply with this code and all listed standards. There are specific sections of the chapter 
addressing concrete slabs, anchorage to concrete, shotcrete, reinforced gypsum concrete and concrete-filled pipe columns. Because 
of the variable properties of material and numerous design and construction options available in the uses of concrete, due care and 
control throughout the construction process is necessary. 

Chapter 20 Aluminum. Chapter 20 contains standards for the use of aluminum in building construction. Only the structural appli- 
cations of aluminum are addressed. The chapter does not address the use of aluminum in specialty products such as storefront or 
window framing or architectural hardware. The use of aluminum in heating, ventilating or air-conditioning systems is addressed in 
the International Mechanical Code (IMC). The chapter references national standards from the Aluminum Association for use of 
aluminum in building construction, AA ASM 35, Aluminum Sheet Metal Work in BUilding Construction, and AA ADM 1, Alumi- 
num Design Manual. By utilizing the standards set forth, a proper application of this material can be obtained. 

Chapter 21 Masonry. This chapter provides comprehensive and practical requirements for masonry construction. The provisions 
of Chapter 21 require minimum accepted practices and the use of standards for the design and construction of masonry structures. 
The provisions address: material specifications and test methods ; types of wall construction; criteria for engineered and empirical 
designs; required details of construction including the execution of construction. Masonry design methodologies including allow- 
able stress design, strength design and empirical design are covered by provisions of the chapter. Also addressed are masonry fire- 
places and chimneys, masonry heaters and glass unit masonry. Fire-resistant construction using masonry is also required to comply 
with Chapter 7. Masonry foundations are also subject to the requirements of Chapter 18. 

Chapter 22 Steel. Chapter 22 provides the requirements necessary for the design and construction of structural steel (including 
composite construction), cold-formed steel, steeljoists, steel cable structures and steel storage racks. The chapter specifies appro- 
priate design and construction standards for these types of structures. It also provides a road map of the applicable technical require- 
ments for steel structures. Steel is a noncombustible building material commonly associated with Types I and II construction; 
however, it is permitted to be used in all types of construction. The code requires that materials used in the design of structural steel 
members conform to designated national standards. Chapter 22 is involved with the design and use of steel materials using the speci- 
fications and standards of the American Institute for Steel Construction, the American Iron and Steel Institute, the Steel Joist Insti- 
tute and the American Society of Civil Engineers. 

Chapter 23 Wood. This chapter provides minimum guidance for the design of buildings and structures that use wood and 
wood-based products in their framing and fabrication . The chapter is organized around three design methodologies : allowable 
stress design (ASD) , load and resistance-factor design (LRFD) and conventional light-frame construction. Included in the chapter 
are references to design and manufacturing standards for various wood and wood-based products; general construction require- 
ments; design criteria for lateral-force-resisting systems and specific requirements for the application of the three design methods. 
In general, only Type III, IV or V buildings may be constructed of wood. Accordingly Chapter 23 is referenced when the combina- 
tion of the occupancy (determined in Chapter 3) and the height and area of the building (determined in Chapter 5) indicate that con- 
struction can be Type III, IV or V. 

Chapter 24 Glass and Glazing. This chapter establishes regulations for glass and glazing used in buildings and structures that, 
when installed, are subjected to wind, snow and dead loads. Engineering and design requirements are included in the chapter. Addi- 
tional structural requirements are found in Chapter 16. A second concern of this chapter is glass and glazing used in areas where it is 
likely to have an impact on the occupants. Section 2406 identifies hazardous locations where glazing installed must either be safety 
glazing or blocked to prevent human impact. Safety glazing must meet stringent standards and be appropriately marked or identi- 
fied. Additional standards for glass and glazing in guards, handrails, elevator hoistways and elevator cars, and in athletic facilities 
are provided. 

Chapter 25 Gypsum Board and Plaster. Chapter 25 contains the provisions and referenced standards that regulate the design, 
construction and quality of gypsum board and plaster. These represent the most common interior and exterior finish materials in the 
building industry. This chapter primarily addresses quality-control-related issues with regard to material specifications and installa- 
tion requirements. Most products are manufactured under the control of industry standards. The building official or inspector pri- 
marily needs to verify that the appropriate product is used and properly installed for the intended use and location. While often 
simply used as wall and ceiling coverings, proper design and application are necessary to provide weather resistance and required 
fire protection for both structural and nonstructural building components. 

Chapter 26 Plastic. The use of plastics in building construction and components is addressed in Chapter 26. This chapter provides 
standards addressing foam plastic insulation, foam plastics used as interior finish and trim, and other plastic veneers used on the 



2009 INTERNATIONAL BUILDING CODE® 



inside or outside of a building. Plastic siding is regulated by Chapter 14. Sections 2606 through 2611 address the use of light-trans- 
mitting plastics in various configurations such as walls, roof panels, skylights, signs and as glazing. Requirements for the use of 
fiber reinforced polymers, fiberglass reinforced polymers and reflective plastic core insulation are also contained in this chapter. 
Some plastics exhibit rapid flame spread and heavy smoke density characteristics when exposed to fire. Additionally, exposure to 
the heat generated by a fire can cause some plastics to deform, which can affect their performance. The requirements and limitations 
of this chapter are necessary to control the use of plastic and foam plastic products such that they do not compromise the safety of 
building occupants. 

Chapter 27 Electrical. Since electrical systems and components are an integral part of almost all structures, it is necessary for the 
code to address the installation of such systems. For this purpose, Chapter 27 references the National Electrical Code (NEC). In 
addition, Section 2702 addresses emergency and standby power requirements. Such systems must comply with the International 
Fire Code (IFC) and referenced standards. This section also provides references to the various code sections requiring emergency 
and standby power, such as high-rise buildings and buildings containing hazardous materials. 

Chapter 28 Mechanical Systems. Nearly all buildings will include mechanical systems. This chapter provides references to the 
International Mechanical Code (IMC) and the International Fuel Gas Code (IFGC) for the design and installation of mechanical 
systems. In addition, the chapter references Chapter 21 of the IBC for masonry chimneys, fireplaces and barbecues. 

Chapter 29 Plumbing Systems. Chapter 29 regulates the minimum number of plumbing fixtures that must be provided for every 
type of building. This chapter also regulates the location of the required fixtures in various types of buildings and the construction of 
toilet rooms. This section requires separate facilities for males and females except for certain types of small occupancies. The regu- 
lations in this chapter come directly from Chapters 3 and 4 of the International Plumbing Code (IPC). 

Chapter 30 Elevators and Conveying Systems. Chapter 30 provides standards for the installation of elevators into buildings. Ref- 
erenced standards provide the requirements for the elevator system and mechanisms. Detailed standards are provided in the chapter 
for hoistway enclosures, hoistway venting and machine rooms. New provisions are added in the 2009 IBC for Fire Service Access 
Elevators required in high-rise buildings and for the optional choice of Occupant Evacuation Elevators (see Section 403). 

Chapter 31 Special Construction. Chapter 31 contains a collection of regulations for a variety of unique structures and architec- 
tural features. Pedestrian walkways and tunnels connecting two buildings are addressed in Section 3104. Membrane and air-sup- 
ported structures are addressed by Section 3102. Safeguards for swimming pool safety are found in Section 3109. Standards for 
temporary structures, including permit requirements are provided in Section 3103. Structures as varied as awnings, marquees, 
signs, telecommunication and broadcast towers and automatic vehicular gates are also addressed (see Sections 3105 through 3108 
and 3110). 

Chapter 32 Encroachments into the Public Right-of-way. Buildings and structures from time to time are designed to extend over 
a property line and into the public right-of-way. Local regulations outside of the building code usually set limits to such encroach- 
ments, and such regulations take precedence over the provisions of this chapter. Standards are provided for encroachments below 
grade for structural support, vaults and areaways. Encroachments above grade are divided into below 8 feet, 8 feet to 15 feet, and 
above 15 feet, because of headroom and vehicular height issues. This includes steps, columns, awnings, canopies, marquees, signs, 
windows, balconies. Similar architectural features above grade are also addressed. Pedestrian walkways must also comply with 
Chapter 31. 

Chapter 33 Safeguards During Construction. Chapter 33 provides safety requirements during construction and demolition of 
buildings and structures. These requirements are intended to protect the public from injury and adjoining property from damage. In 
addition the chapter provides for the progressive installation and operation of exit stairways and standpipe systems during construc- 
tion. 

Chapter 34 Existing Structures. The provisions in Chapter 34 deal with alternative methods or reduced compliance requirements 
when dealing with existing building constraints. This chapter allows for a controlled departure from full compliance with the techni- 
cal codes, without compromising the minimum standards for fire prevention and life safety features of the rehabilitated building. 
Provisions are divided by addition, alterations, repairs, change of occupancy and moved structures . There are further allowances for 
registered historic buildings. There are also special allowances for replacement of existing stairways, replacement of glass and 
accessibility requirements. The fire escape requirements in Section 3406 are consistent with the fire escape requirements in Section 
1030 of the International Fire Code (IFC). 

Section 3412, Compliance Alternatives, allows for existing buildings to be evaluated so as to show that alterations, while not 
meeting new construction requirements, will improve the current existing situation. Provisions are based on a numerical scoring 
system involving 18 various safety parameters and the degree of code compliance for each issue. 

Chapter 34 is repeated in the International Existing Building Code (IEBC). Sections 3402 through 3409 are repeated as IEBC 
Chapter 3 and Section 3410 as Chapter 13. 



2009 INTERNATIONAL BUILDING CODE® 



Chapter 35 Referenced Standards. The code contains numerous references to standards that are used to regulate materials and 
methods of construction. Chapter 35 contains a comprehensive list of all standards that are referenced in the code, including the 
appendices. The standards are part of the code to the extent of the reference to the standard (see Section 102.4). Compliance with the 
referenced standard is necessary for compliance with this code. By providing specifically adopted standards, the construction and 
installation requirements necessary for compliance with the code can be readily determined. The basis for code compliance is, 
therefore, established and available on an equal basis to the building code official, contractor, designer and owner. 

Chapter 35 is organized in a manner that makes it easy to locate specific standards. It lists all of the referenced standards, alpha- 
betically, by acronym of the promulgating agency of the standard. Each agency's standards are then listed in either alphabetical or 
numeric order based upon the standard identification. The list also contains the title of the standard; the edition (date) of the standard 
referenced; any addenda included as part of the ICC adoption; and the section or sections of this code that reference the standard. 

Appendices. Appendices are provided in the IBC to offer optional or supplemental criteria to the provisions in the main chapters of 
the code. Appendices provide additional information for administration of the Department of Building Safety as well as standards 
not typically administered by all building departments. Appendices have the same force and effect as the first 35 chapters of the IBC 
only when explicitly adopted by the jurisdiction. 

Appendix A Employee Qualifications. Effective administration and enforcement of the family of International Codes depends on 
the training and expertise of the personnel employed by the jurisdiction and his or her knowledge of the codes. Section 103 of the 
code establishes the Department of Building Safety and calls for the appointment of a building official and deputies such as plans 
examiners and inspectors. Appendix A provides standards for experience, training and certification for the building official and the 
other staff mentioned in Chapter 1. 

Appendix B Board of Appeals. Section 112 of Chapter 1 requires the establishment of a board of appeals to hear appeals regarding 
determinations made by the building official. Appendix B provides qualification standards for members of the board as well as 
operational procedures of such board. 

Appendix C Group V- Agricultural Buildings. Appendix C provides a more liberal set of standards for the construction of agri- 
cultural buildings, rather than strictly following the Utility building provision, reflective of their specific usage and limited occupant 
load. The provisions of the appendix, when adopted, allow reasonable heights and areas commensurate with the risk of agricultural 
buildings. 

Appendix D Fire Districts. Fire districts have been a tool used to limit conflagration hazards in areas of a city with intense and con- 
centrated development. More frequently used under the model codes which preceded the International Building Code (IBC) , the 
appendix is provided to allowjurisdictions to continue the designation and use of fire districts. Fire District standards restrict certain 
occupancies within the district, as well as setting higher minimum construction standards. 

Appendix E Supplemental Accessibility Requirements. The Architectural and Transportation Barriers Compliance Board (U.S. 
Access Board) has revised and updated its accessibility guidelines for buildings and facilities covered by the Americans with Dis- 
abilities Act (ADA) and the Architectural Barriers Act (ABA) . Appendix E includes scoping requirements contained in the new 
AD A/ ABA Accessibility Guidelines that are not in Chapter 11 and not otherwise mentioned or mainstreamed throughout the code. 
Items in the appendix deal with subjects not typically addressed in building codes (e.g., beds, room signage, transportation facili- 
ties) . 

Appendix F Rodentproofing. The provisions of this appendix are minimum mechanical methods to prevent the entry of rodents 
into a building. These standards, when used in conjunction with cleanliness and maintenance programs, can significantly reduce the 
potential of rodents invading a building. 

Appendix G Flood-resistant Construction. Appendix G is intended to fulfill the flood-plain management and administrative 
requirements of the National Flood Insurance Program (NFIP) that are not included in the code. Communities that adopt the Inter- 
national Building Code (IBC) and Appendix G will meet the minimum requirements of NFIP as set forth in Title 44 of the Code of 
Federal Regulations. 

Appendix H Signs. Appendix H gathers in one place the various code standards that regulate the construction and protection of out- 
door signs. Whenever possible, the appendix provides standards in performance language, thus allowing the widest possible appli- 
cation. 

Appendix I Patio Covers. Appendix I provides standards applicable to the construction and use of patio covers. It is limited in 
application to patio covers accessory to dwelling units. Covers of patios and other outdoor areas associated with restaurants, mer- 
cantile buildings, offices, nursing homes or other nondwelling occupancies would be subject to standards in the main code and not 
this appendix. 

Appendix J Grading. Appendix J provides standards for the grading of properties. The appendix also provides standards for 
administration and enforcement of a grading program including permit and inspection requirements. Appendix J was originally 



2009 INTERNATIONAL BUILDING CODE® 



developed in the 1960s and used for many years injurisdictions throughout the western states. It is intended to provide consistent 
and uniform code requirements anywhere grading is considered an issue. 

Appendix K Administrative Provisions. Appendix K primarily provides administrative provisions for jurisdictions adopting and 
enforcing NFPA 70-the National Electrical Code (NEC). The provisions contained in this appendix are compatible with adminis- 
trative and enforcement provisions contained in Chapter 1 of the IBC and the other International Codes. Annex H ofNFPA 70 also 
contains administrative provisions for the NEC; however, some of its provisions are not compatible with IBC Chapter 1. Section 
KIIO also contains technical provisions that are unique to this appendix and are in addition to technical standards of NFPA 70. 



2009 INTERNATIONAL BUILDING CODE® 



2009 INTERNATIONAL BUILDING CODE® 



ORDINANCE 

The International Codes are designed and promulgated to be adopted by reference by ordinance. Jurisdictions wishing to adopt the 
2009 International Building Code as an enforceable regulation governing structures and premises should ensure that certain factual 
information is included in the adopting ordinance at the time adoption is being considered by the appropriate governmental body. 
The following sample adoption ordinance addresses several key elements of a code adoption ordinance, including the information 
required for insertion into the code text. 

SAMPLE ORDINANCE FOR ADOPTION OF 

THE INTERNATIONAL BUILDING CODE 

ORDINANCE NO. 

An ordinance of the [JURISDICTION] adopting the 2009 edition of the International Building Code, regulating and governing the 
conditions and maintenance of all property, buildings and structures; by providing the standards for supplied utilities and facilities 
and other physical things and conditions essential to ensure that structures are safe, sanitary and fit for occupation and use; and the 
condemnation of buildings and structures unfit for human occupancy and use and the demolition of such structures in the [JURISDIC- 
TION]; providing for the issuance of permits and collection of fees therefor; repealing Ordinance No. of the [JURISDICTION] 
and all other ordinances and parts of the ordinances in conflict therewith. 

The [GOVERNING BODY] of the [JURISDICTION] does ordain as follows: 

Section 1. That a certain document, three (3) copies of which are on file in the office of the [TITLE OF JURISDICTION'S KEEPER OF 
RECORDS] of [NAME OF JURISDICTION], being marked and designated as the International Building Code, 2009 edition, including 
Appendix Chapters [FILL IN THE APPENDIX CHAPTERS BEING ADOPTED] (see International Building Code Section 101.2.1, 2009 
edition), as published by the International Code Council, be and is hereby adopted as the Building Code of the [JURISDICTION], in 
the State of [STATE NAME] for regulating and governing the conditions and maintenance of all property, buildings and structures; by 
providing the standards for supplied utilities and facilities and other physical things and conditions essential to ensure that structures 
are safe, sanitary and fit for occupation and use; and the condemnation of buildings and structures unfit for human occupancy and 
use and the demolition of such structures as herein provided; providing for the issuance of permits and collection of fees therefor; 
and each and all of the regulations, provisions, penalties, conditions and terms of said Building Code on file in the office of the 
[JURISDICTION] are hereby referred to, adopted, and made a part hereof, as if fully set out in this ordinance, with the additions, inser- 
tions, deletions and changes, if any, prescribed in Section 2 of this ordinance. 

Section 2. The following sections are hereby revised: 

Section 101.1. Insert: [NAME OF JURISDICTION] 

Section 1612.3. Insert: [NAME OF JURISDICTION] 

Section 1612.3. Insert: [DATE OF ISSUANCE] 

Section 3412.2. Insert: [DATE IN ONE LOCATION] 

Section 3. That Ordinance No. of [JURISDICTION] entitled [FILL IN HERE THE COMPLETE TITLE OF THE ORDINANCE OR 

ORDINANCES IN EFFECT AT THE PRESENT TIME SO THAT THEY WILL BE REPEALED BY DEFINITE MENTION] and all Other ordinances 
or parts of ordinances in conflict herewith are hereby repealed. 

Section 4. That if any section, subsection, sentence, clause or phrase of this ordinance is, for any reason, held to be unconstitutional, 
such decision shall not affect the validity of the remaining portions of this ordinance. The [GOVERNING BODY] hereby declares that it 
would have passed this ordinance, and each section, subsection, clause or phrase thereof, irrespective of the fact that anyone or more 
sections, subsections, sentences, clauses and phrases be declared unconstitutional. 

Section 5. That nothing in this ordinance or in the Building Code hereby adopted shall be construed to affect any suit or proceeding 
impending in any court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or existing, under any 
act or ordinance hereby repealed as cited in Section 3 of this ordinance; nor shall anyj ust or legal right or remedy of any character be 
lost, impaired or affected by this ordinance. 

Section 6. That the [JURISDICTION'S KEEPER OF RECORDS] is hereby ordered and directed to cause this ordinance to be published. 
(An additional provision may be required to direct the number of times the ordinance is to be published and to specify that it is to be 
in a newspaper in general circulation. Posting may also be required.) 

Section 7. That this ordinance and the rules, regulations, provisions, requirements, orders and matters established and adopted 
hereby shall take effect and be in full force and effect [TIME PERIOD] from and after the date of its final passage and adoption. 

2009 INTERNATIONAL BUILDING CODE® XV 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



CHAPTER 1 SCOPE AND ADMINISTRATION. . . . 1 312 Utility and Miscellaneous Group U 



36 



PART I-SCOPE AND APPLICATION 

Section 

101 General 

102 Applicability 

PART 2-ADMINISTRATION AND 
ENFORCEMENT 

103 Department of Building Safety 

104 Duties and Powers of Building Official 

105 Permits 

106 Floor and Roof Design Loads 

107 Submittal Documents 

108 Temporary Structures and Uses 

109 Fees 

110 Inspections 

111 Certificate of Occupancy 

112 Service Utilities 

113 Board of Appeals 

114 Violations 

115 Stop Work Order 

116 Unsafe Structures and Equipment 

CHAPTER 2 DEFINITIONS 
Section 

201 General 

202 Definitions 



CHAPTER 4 SPECIAL DETAILED 

REQUIREMENTS BASED ON 
USE AND OCCUPANCY 



37 



CHAPTER 3 



USE AND OCCUPANCY 
CLASSIFICATION 



1 
1 


Section 




401 


Scope 


37 




402 


Covered Mall and Open Mall Buildings 


37 


2 


403 


High-rise Buildings 


40 


2 


404 


Atriums 


43 


2 


405 


Underground Buildings 


44 


3 


406 


Motor- vehicle-related Occupancies 


45 


5 


407 


Group 1-2 


49 


5 


408 


Group 1-3 


50 


6 


409 


Motion Picture Projection Rooms 


52 


6 


410 


Stages and Platforms 


53 


7 


411 


Special Amusement Buildings 


54 


8 


412 


Aircraft-related Occupancies 


55 


8 


413 


Combustible Storage 


58 


8 


414 


Hazardous Materials 


58 


9 


415 


Groups H-l, H-2, H-3, H-4 and H-5 


62 


9 


416 


Application of Flammable Finishes 


74 


9 


417 


Drying Rooms 


75 


1 


418 


Organic Coatings 


75 




419 


Live/work Units 


75 


1 


420 


Groups 1-1, R-l, R-2, R-3 


76 


1 


421 


Hydrogen Cutoff Rooms 


76 




422 


Ambulatory Health Care Facilities 


77 




423 


Storm Shelters 


77 



23 



Section 

301 General 

302 Classification 

303 Assembly Group A 

304 Business Group B 

305 Educational Group E 

306 Factory Group F 

307 High-hazard Group H 

308 Institutional Group I 

309 Mercantile Group M 

310 Residential Group R 

311 Storage Group S 



CHAPTER 5 GENERAL BUILDING 



23 




rtmUrt 1 ^ AINU AKilA^ 


/^ 


23 


Section 




23 


501 


General 


79 


24 


502 


Definitions 


79 


24 


503 


General Building Height and Area Limitations . 


. 79 


24 


504 


Building Height 


79 


25 


505 


Mezzanines 


81 


33 


506 


Building Area Modifications 


82 


34 


507 


Unlimited Area Buildings 


83 


35 


508 


Mixed Use and Occupancy 


84 


35 


509 


Special Provisions 


87 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



CHAPTER 6 TYPES OF CONSTRUCTION 

Section 



89 CHAPTER 9 FIRE PROTECTION SYSTEMS . 
Section 



181 



601 


General 


89 


901 


General 


181 


602 


Construction Classification 


89 


902 


Definitions 


. ... 181 


603 


Combustible Material in 




903 


Automatic Sprinkler Systems 


184 




Type I and II Construction 


91 


904 


Alternative Automatic 

Fire-extinguishing Systems 


188 


CHAPTER 7 FIRE AND SMOKE 




905 


Standpipe Systems 


190 




PROTECTION FEATURES 


93 


906 


Portable Fire Extinguishers 


192 


Section 




907 


Fire Alarm and Detection Systems 


194 


701 


General 


93 


908 


Emergency Alarm Systems 


204 


702 


Definitions 


93 


909 


Smoke Control Systems 


204 


703 


Fire-resistance Ratings and Fire Tests 


94 


910 


Smoke and Heat Vents 


211 


704 


Fire-resistance Rating of 




911 


Fire Command Center 


213 




Structural Members 


95 


912 


Fire Department Connections 


214 


705 


Exterior Walls 


97 


913 


Fire Pumps 


214 


706 


Fire Walls 


101 


914 


Emergency Responder Safety Features 


215 


707 


Fire Barriers 


103 


915 


Emergency Responder Radio Coverage 


215 


708 


Shaft Enclosures 


104 








709 


Fire Partitions 


107 


CHAPTER 10 MEANS OF EGRESS 


217 


710 


Smoke Barriers 


. . . 108 


Section 




711 


Smoke Partitions 


. . . 109 


1001 


Administration 


217 


712 
713 
714 


Horizontal Assemblies 

Penetrations 

Fire-resistant Joint Systems 


109 

...110 

113 


1002 
1003 
1004 
1005 


Definitions 

General Means of Egress 
Occupant Load 
Egress Width 


217 
218 
219 
221 


715 


Opening Protectives 


113 


1006 


Means of Egress Illumination 


221 


716 


Ducts and Air Transfer Openings 


117 


1007 


Accessible Means of Egress 


222 


717 


Concealed Spaces 


121 


1008 


Doors, Gates and Turnstiles 


224 


718 


Fire-resistance Requirements for Plaster 


124 


1009 


Stairways 


230 


719 


Thermal- and Sound-insulating Materials 


124 


1010 


Ramps 


233 


720 


Prescriptive Fire Resistance 


125 


1011 


Exit Signs 


234 


721 


Calculated Fire Resistance 


125 


1012 


Handrails 


235 








1013 


Guards 


236 


CHAPTER 8 INTERIOR FINISHES 


175 


1014 


Exit Access 


237 


Section 




1015 


Exit and Exit Access Doorways 


238 


801 


General 


175 


1016 


Exit Access Travel Distance 


240 


802 


Definitions 


. . . 175 


1017 


Aisles 


240 


803 


Wall and Ceiling Finishes 


175 


1018 


Corridors 


241 


804 


Interior Floor Finish 


178 


1019 


Egress Balconies 


242 


805 


Combustible Materials in Type I 




1020 


Exits 


243 




and II Construction 


178 


1021 


Number of Exits and Continuity 


243 


806 


Decorative Materials and Trim 


178 


1022 


Exit Enclosures 


244 


807 


Insulation 


179 


1023 


Exit Passageways 


245 


808 


Acoustical Ceiling Systems 


179 


1024 


Luminous Egress Path Markings 


246 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



1025 Horizontal Exits 

1026 Exterior Exit Ramps and Stairways 

1027 Exit Discharge 

1028 Assembly 

1029 Emergency Escape and Rescue 

CHAPTER 11 ACCESSIBILITy 

Section 

1101 General 

1102 Definitions 

1103 Scoping Requirements 

1104 Accessible Route 

1105 Accessible Entrances 

1106 Parking and Passenger Loading Facilities 

1107 Dwelling Units and Sleeping Units 

1108 Special Occupancies 

1109 Other Features and Facilities 

1110 Signage 

CHAPTER 12 INTERIOR ENVIRONMENT 

Section 

1201 General 

1202 Definitions 

1203 Ventilation 

1204 Temperature Control 

1205 Lighting 

1206 Yards or Courts 

1207 Sound Transmission 

1208 Interior Space Dimensions 

1209 Access to Unoccupied Spaces 

1210 Surrounding Materials 

CHAPTER 13 ENERGY EFFICIENCY 

Section 

1301 General 

CHAPTER 14 EXTERIOR WALLS 

Section 

1401 General 

1402 Definitions 

1403 Performance Requirements 

1404 Materials 

1405 Installation of Wall Coverings 

1406 Combustible Materials on the 

Exterior Side of Exterior Walls 

1407 Metal Composite Materials (MCM) 



247 


1408 


Exterior Insulation and 




248 




Finish Systems (EIFS) 


285 


249 


CHAPTER 15 ROOF ASSEMBLIES AND 




250 




ROOFTOP STRUCTURES 


287 


254 


Section 




257 


1501 
1502 


General 
Definitions 


287 
287 


257 
257 


1503 
1504 


Weather Protection 
Performance Requirements 


287 
288 


257 
258 
259 
260 
260 


1505 
1506 
1507 


Fire Classification 

Materials 

Requirements for Roof Coverings 


289 
289 
290 


1508 
1509 


Roof Insulation 
Rooftop Structures 


299 
300 


264 


1510 


Reroofing 


301 


266 


CHAPTER 16 STRUCTURAL DESIGN 


303 


269 


Section 




271 


1601 


General 


303 


1602 


Definitions and Notations 


303 


271 


1603 


Construction Documents 


304 


271 


1604 


General Design Requirements 


305 


271 


1605 


Load Combinations 


308 


272 


1606 


Dead Loads 


309 


272 


1607 


Live Loads 


309 


273 


1608 


Snow Loads 


315 


273 


1609 


Wind Loads 


315 


273 


1610 


Soil Lateral Loads 


331 


274 


1611 


Rain Loads 


332 


274 


1612 


Flood Loads 


338 



275 

275 
277 

277 
277 
277 
278 
279 

283 
284 



1613 Earthquake Loads 340 

1614 Structural Integrity 345 

CHAPTER 17 STRUCTURAL TESTS AND 

SPECIAL INSPECTIONS 367 

Section 

1701 General 367 

1702 Definitions 367 

1703 Approvals 367 

1704 Special Inspections 368 

1705 Statement of Special Inspections 379 

1706 Special Inspections for Wind Requirements 381 

1707 Special Inspections for Seismic Resistance 381 

1708 Structural Testing for Seismic Resistance 382 

1709 Contractor Responsibility 383 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



1710 Structural Observations 

1711 Design Strengths of Materials 

1712 Alternative Test Procedure 

1713 Test Safe Load 

1714 In-situ Load Tests 

1715 Preconstruction Load Tests 

1716 Material and Test Standards 

CHAPTER 18 SOILS AND FOUNDATIONS 

Section 

1801 General 

1802 Definitions 

1803 Geotechnical Investigations 

1804 Excavation, Grading and Fill 

1805 Dampproofing and Waterproofing 

1806 Presumptive Load-bearing Values of Soils 

1807 Foundation Walls, Retaining Walls and 

Embedded Posts and Poles 

1808 Foundations 

1809 Shallow Foundations 

1810 Deep Foundations 

CHAPTER 19 CONCRETE 

Section 

1901 General 

1902 Definitions 

1903 Specifications for Tests and Materials 

1904 Durability Requirements 

1905 Concrete Quality, Mixing and Placing 

1906 Formwork, Embedded Pipes and 

Construction Joints 

1907 Details of Reinforcement 

1908 Modifications to ACI 318 

1909 Structural Plain Concrete 

1910 Minimum Slab Provisions 

1911 Anchorage to Concrete-Allowable 

Stress Design 

1912 Anchorage to Concrete-Strength Design 

1913 Shotcrete 

1914 Reinforced Gypsum Concrete 

1915 Concrete-filled Pipe Columns 

CHAPTER 20 ALUMINUM 

Section 

2001 General 

2002 Materials 



383 


CHA1 


PTER21 MASONRy 


429 


383 


Section 




383 


2101 


General 


429 


384 


2102 


Definitions and Notations 


429 


384 


2103 


Masonry Construction Materials 


432 


384 


2104 


Construction 


433 


385 


2105 


Quality Assurance 


434 




2106 


Seismic Design 


435 


387 


2107 


Allowable Stress Design 


435 




2108 


Strength Design of Masonry 


436 


387 


2109 


Empirical Design of Masonry 


436 


387 


2110 


Glass Unit Masonry 


438 


387 


2111 


Masonry Fireplaces 


438 


389 


2112 


Masonry Heaters 


440 


390 
391 


2113 


Masonry Chimneys 


441 




CHAPTER 22 STEEL 


447 


392 


Section 




398 


2201 


General 


447 


402 


2202 


Definitions 


447 


403 


2203 


Identification and Protection of Steel 
for Structural Purposes 


447 


417 


2204 


Connections 


447 




2205 


Structural Steel 


447 


417 


2206 


Steel Joists 


448 


417 


2207 


Steel Cable Structures 


449 


417 


2208 


Steel Storage Racks 


449 


417 


2209 


Cold-formed Steel 


449 


419 


2210 


Cold-formed Steel Light-frame Construction . 


.. 449 


420 


CHAPTER 23 WOOD 


451 


420 


Section 




420 


2301 


General 


451 


423 


2302 


Definitions 


451 


423 


2303 


Minimum Standards and Quality 


452 




2304 


General Construction Requirements 


456 


424 
424 


2305 


General Design Requirements for 
Lateral-foree-resisting Systems 


466 


425 


2306 


Allowable Stress Design 


468 


426 


2307 


Load and Resistance Factor Design 


469 


426 


2308 


Conventional Light-frame Construction 


469 


427 


CHAPTER 24 GLASS AND GLAZING 

Section 


521 


427 


2401 


General 


521 


427 


2402 


Definitions 


521 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



2403 
2404 


General Requirements for Glass 
Wind, Snow, Seismic and 


521 




Dead Loads on Glass 


521 


2405 


Sloped Glazing and Skylights 


523 


2406 


Safety Glazing 


524 


2407 


Glass in Handrails and Guards 


526 


2408 


Glazing in Athletic Facilities 


526 


2409 


Glass in Elevator Hoistways and 






Elevator Cars 


527 



CHAPTER 25 GYPSUM BOARD 

AND PLASTER 529 

Section 

2501 General 529 

2502 Definitions 529 

2503 Inspection 529 

2504 Vertical and Horizontal Assemblies 529 

2505 Shear Wall Construction 529 

2506 Gypsum Board Materials 530 

2507 Lathing and Plastering 530 

2508 Gypsum Construction 530 

2509 Gypsum Board in Showers and 

Water Closets 531 

2510 Lathing and Furring for Cement 

Plaster (Stucco) 532 

25 1 1 Interior Plaster 532 

2512 Exterior Plaster 533 

2513 Exposed Aggregate Plaster 533 

CHAPTER 26 PLASTIC 535 

Section 

2601 General 535 

2602 Definitions 535 

2603 Foam Plastic Insulation 535 

2604 Interior Finish and Trim 538 

2605 Plastic Veneer. 539 

2606 Light-transmitting Plastics 539 

2607 Light-transmitting Plastic Wall Panels 540 

2608 Light-transmitting Plastic Glazing 541 

2609 Light-transmitting Plastic Roof Panels 541 

2610 Light-transmitting Plastic Skylight Glazing 542 

2611 Light-transmitting Plastic Interior Signs 542 

2612 Fiber Reinforced Polymer and 

Fiberglass-reinforced Polymer 543 

2613 Reflective Plastic Core Insulation 544 



CHAPTER 27 ELECTRICAL 545 

Section 

2701 General 545 

2702 Emergency and Standby Power Systems 545 

CHAPTER 28 MECHANICAL SySTEMS 547 

Section 

2801 General 547 

CHAPTER 29 PLUMBING SYSTEMS 549 

Section 

2901 General 549 

2902 Minimum Plumbing Facilities 549 

2903 Toilet Room Requirements 552 

CHAPTER 30 ELEVATORS AND 

CONVEYING SYSTEMS 553 

Section 

3001 General 553 

3002 Hoistway Enclosures 553 

3003 Emergency Operations 553 

3004 Hoistway Venting 554 

3005 Conveying Systems 554 

3006 Machine Rooms 555 

3007 Fire Service Access Elevator 555 

3008 Occupant Evacuation Elevators 556 

CHAPTER 31 SPECIAL CONSTRUCTION 559 

Section 

3101 General 559 

3102 Membrane Structures 559 

3103 Temporary Structures 560 

3104 Pedestrian Walkways and Tunnels 560 

3105 Awnings and Canopies 561 

3106 Marquees 562 

3107 Signs 562 

3108 Telecommunication and Broadcast Towers 562 

3109 Swimming Pool Enclosures and 

Safety Devices 562 

3110 Automatic Vehicular Gates 563 

CHAPTER 32 ENCROACHMENTS INTO THE 

PUBLIC RIGHT-OF-WAy 565 

Section 

3201 General 565 

3202 Encroachments 565 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



CHAPTER 33 SAFEGUARDS DURING 
CONSTRUCTION 

Section 



567 



3301 


General 


567 


3302 


Construction Safeguards 


567 


3303 


Demolition 


567 


3304 


Site Work 


567 


3305 


Sanitary 


567 


3306 


Protection of Pedestrians 


568 


3307 


Protection of Adjoining Property 


569 


3308 


Temporary Use of Streets, Alleys and 
Public Property 


569 


3309 


Fire Extinguishers 


569 


3310 


Means of Egress 


569 


3311 


Standpipes 


569 


3312 


Automatic Sprinkler System 


570 


CHAPTER 34 EXISTING STRUCTURES 


571 


Section 




3401 


General 


571 


3402 


Definitions 


571 


3403 


Additions 


572 


3404 


Alterations 


572 


3405 


Repairs 


573 


3406 


Fire Escapes 


574 


3407 


Glass Replacement 


575 


3408 


Change of Occupancy 


575 


3409 


Historic Buildings 


575 


3410 


Moved Structures 


575 


3411 


Accessibility for Existing Buildings 


575 


3412 


Compliance Alternatives 


577 



CHAPTER 35 REFERENCED STANDARDS 587 



APPENDIX A EMPLOYEE 

QUALIFICATIONS 

Section 

A101 Building Official Qualifications 

A 102 Referenced Standards 

APPENDIX B BOARD OF APPEALS 

Section 

B101 General 



607 

607 
607 

609 
609 



APPENDIX C GROUP U-AGRICULTURAL 
BUILDINGS 

Section 

C101 General 

CI 02 Allowable Height and Area 

C103 Mixed Occupancies 

CI 04 Exits 

APPENDIX D FIRE DISTRICTS 

Section 

D101 General 

D102 Building Restrictions 

D 103 Changes to Buildings 

D 104 Buildings Located Partially in the 
Fire District 



D 105 Exceptions to Restrictions in Fire District 
D106 Referenced Standards 



611 

611 
611 
611 
611 

613 

613 
613 
614 

614 
614 
615 



APPENDIX E SUPPLEMENTARY ACCESSIBILITY 



REQUIREMENTS 

Section 

E101 General 

El 02 Definitions 

E103 Accessible Route 

E104 Special Occupancies 

El 05 Other Features and Facilities 

E 106 Telephones 

E107 Signage 

E108 Bus Stops 

E 109 Transportation Facilities and Stations 

El 10 Airports 

El 11 Referenced Standards 

APPENDIX F RODENTPROOFING 

Section 

F101 General 

APPENDIX G FLOOD-RESISTANT 
CONSTRUCTION 

Section 

G101 Administration 

G102 Applicability 

G103 Powers and Duties 

G104 Permits 

G105 Variances 



617 

617 
617 
617 
617 
618 
618 
619 
620 
620 
621 
621 

623 

623 

625 

625 
625 
625 
626 
626 



2009 INTERNATIONAL BUILDING CODE® 



TABLE OF CONTENTS 



G201 


Definitions 


627 


G301 


Subdivisions 


628 


G401 


Site Improvement. 


628 


G501 


Manufactured Homes 


628 


G601 


Recreational Vehicles 


628 


G701 


Tanks 


629 


G801 


Other Building Work 


629 


G901 


Temporary Structures and 
Temporary Storage 


629 


G1001 


Utility and Miscellaneous Group U 


629 


GII01 Referenced Standards 


630 



APPENDIX H SIGNS 

Section 

HI01 General 

HI02 Definitions 

HI03 Location 

HI04 Identification 

HI 05 Design and Construction 

HI06 Electrical 

HI07 Combustible Materials 

HI08 Animated Devices 

HI09 Ground Signs 

H110 Roof Signs 

Hill Wall Signs 

HI 12 Projecting Signs 

HI 13 Marquee Signs 

HI 14 Portable Signs 

HI1S Referenced Standards 



631 

631 
631 
631 
631 
632 
632 
632 
632 
632 
633 
633 
633 
634 
634 
634 



JI07 Fills 

JI08 Setbacks 

J 109 Drainage and Terracing 

J 110 Erosion Control 

Jill Referenced Standards 

APPENDIX K ADMINISTRATIVE 
PROVISIONS 

Section 

KI01 General 

KI02 Applicability 

KI03 Permits 

K104 Construction Documents 

K105 Alternative Engineered Design 

K106 Required Inspections 

KI07 Prefabricated Construction 

KI08 Testing 

KI09 Reconnection 

KIIO Condemning Electrical Systems 

Kill Electrical Provisions 

INDEX 



638 
638 
640 
640 
640 

641 

641 
641 
641 
642 
642 
642 
642 
643 
643 
643 
643 

645 



APPENDIX I PATIO COVERS 

Section 

1101 General 

1102 Definitions 

1103 Exterior Openings 

1104 Structural Provisions 



635 

635 
635 
635 
635 



APPENDIX J GRADING 

Section 

JI01 General 

JI02 Definitions 

JI03 Permits Required 

JI04 Permit Application and Submittals 

JI05 Inspections 

JI06 Excavations 



637 

637 
637 
637 
637 
638 
638 



2009 INTERNATIONAL BUILDING CODE® 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 1 

SCOPE AND ADMINISTRATION 



I PART 1 -SCOPE AND APPLICATION 



SECTION 101 
GENERAL 

101.1 Title. These regulations shall be known as the BUilding 
Code of [NAME OF JURISDICTION], hereinafter referred to as 
"this code." 

101.2 Scope. The provisions of this code shall apply to the con- 
struction, alteration, movement, enlargement, replacement, 
repair, equipment, use and occupancy, location, maintenance, 
removal and demolition of every building or structure or any 
appurtenances connected or attached to such buildings or 
structures. 

Exception: Detached one- and two-family dwellings and 
multiple single-family dwellings (townhouses) not more 
than three stories above grade plane in height with a sepa- 
rate means of egress and their accessory structures shall 
comply with the International Residential Code. 

101.2.1 Appendices. Provisions in the appendices shall not 
apply unless specifically adopted. 

101.3 Intent. The purpose of this code is to establish the mini- 
mum requirements to safeguard the public health, safety and 
general welfare through structural strength, means of egress 
facilities, stability, sanitation, adequate light and ventilation, 
energy conservation, and safety to life and property from fire 
and other hazards attributed to the built environment and to 
provide safety to fire fighters and emergency responders dur- 
ing emergency operations. 

101.4 Referenced codes. The other codes listed in Sections 
101.4.1 through 101.4.6 and referenced elsewhere in this code 
shall be considered part of the requirements of this code to the 
prescribed extent of each such reference. 

101.4.1 Gas. The provisions of the International Fuel Gas 
Code shall apply to the installation of gas piping from the 
point of delivery, gas appliances and related accessories as 
covered in this code. These requirements apply to gas piping 
systems extending from the point of delivery to the inlet 
connections of appliances and the installation and operation 
of residential and commercial gas appliances and related 
accessories. 

101.4.2 Mechanical. The provisions of the International 
Mechanical Code shall apply to the installation, alterations, 
repairs and replacement of mechanical systems, including 
equipment, appliances, fixtures, fittings and/or appurte- 
nances, including ventilating, heating, cooling, air-condi- 
tioning and refrigeration systems, incinerators and other 
energy-related systems. 

101.4.3 Plumbing. The provisions of the International 
Plumbing Code shall apply to the installation, alteration, 
repair and replacement of plumbing systems, including 



equipment, appliances, fixtures, fittings and appurtenances, 
and where connected to a water or sewage system and all 
aspects of a medical gas system. The provisions of the Inter- 
national Private Sewage Disposal Code shall apply to pri- 
vate sewage disposal systems. 

101.4.4 Property maintenance. The provisions of the 
International Property Maintenance Code shall apply to 
existing structures and premises; equipment and facilities; 
light, ventilation, space heating, sanitation, life and fire 
safety hazards; responsibilities of owners, operators and 
occupants; and occupancy of existing premises and struc- 
tures. 

101.4.5 Fire prevention. The provisions of the Interna- 
tional Fire Code shall apply to matters affecting or relating 
to structures, processes and premises from the hazard of fire 
and explosion arising from the storage, handling or use of 
structures, materials or devices; from conditions hazardous 
to life, property or public welfare in the occupancy of struc- 
tures or premises; and from the construction, extension, 
repair, alteration or removal of fire suppression and alarm 
systems or fire hazards in the structure or on the premises 
from occupancy or operation. 

101.4.6 Energy. The provisions of the International Energy 
Conservation Code shall apply to all matters governing the 
design and construction of buildings for energy efficiency. 



SECTION 102 
APPLICABILITY 

102.1 General. Where there is a conflict between a general 
requirement and a specific requirement, the specific require- 
ment shall be applicable. Where, in any specific case, different 
sections of this code specify different materials, methods of 
construction or other requirements, the most restrictive shall 
govern. 

102.2 Other laws. The provisions of this code shall not be 
deemed to nullify any provisions of local, state or federal law. 

102.3 Application ofreferences. References to chapter or sec- 
tion numbers, or to provisions not specifically identified by 
number, shall be construed to refer to such chapter, section or 
provision of this code. 

102.4 Referenced codes and standards. The codes and stan- 
dards referenced in this code shall be considered part of the 
requirements of this code to the prescribed extent of each such 
reference. Where differences occur between provisions of this 
code and referenced codes and standards, the provisions of this 
code shall apply. 

102.5 Partial invalidity. In the event that any part or provision 
of this code is held to be illegal or void, this shall not have the 
effect of making void or illegal any of the other parts or provi- 
sions. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



102.6 Existing structures. The legal occupancy of any struc- 
ture existing on the date of adoption of this code shall be per- 
mitted to continue without change, except as is specifically 
covered in this code, the International Property Maintenance 
Code or the International Fire Code, or as is deemed necessary 
by the building officialfor the general safety and welfare of the 
occupants and the public. 



I PART 2-ADMINISTRATION AND ENFORCEMENT 



SECTION 103 
DEPARTMENT OF BUILDING SAFETY 

103.1 Creation of enforcement agency. The Department of 
Building Safety is hereby created and the official in charge 
thereof shall be known as the building official. 

103.2 Appointment. The building official shall be appointed 
by the chief appointing authority of the jurisdiction. 

103.3 Deputies. In accordance with the prescribed procedures 
of this jurisdiction and with the concurrence of the appointing 
authority, the bUilding official shall have the authority to 
appoint a deputy building official, the related technical offi- 
cers, inspectors, plan examiners and other employees. Such 
employees shall have powers as delegated by the building offi- 
cial. For the maintenance of existing properties, see the Inter- 
national Property Maintenance Code. 



SECTION 104 
DUTIES AND POWERS OF BUILDING OFFICIAL 

104.1 General. The bUilding officialis hereby authorized and 
directed to enforce the provisions of this code. The building 
official sbd\\ have the authority to render interpretations of this 
code and to adopt policies and procedures in order to clarify the 
application of its provisions. Such interpretations, policies and 
procedures shall be in compliance with the intent and purpose 
of this code. Such policies and procedures shall not have the 
effect of waiving requirements specifically provided for in this 
code. 

104.2 Applications and permits. The bUilding official shall 
receive applications, review construction documents and issue 
permits for the erection, and alteration, demolition and moving 
of buildings and structures, inspect the premises for which such 
permitshave been issued and enforce compliance with the pro- 
visions of this code. 

104.3 Notices and orders. The bUilding official shall issue all 
necessary notices or orders to ensure compliance with this 
code. 

104.4 Inspections. The bUilding official shall make all of the 
required inspections, or the building official shall have the 
authority to accept reports of inspection by approved agencies 
or individuals. Reports of such inspections shall be in writing 
and be certified by a responsible officer of such approved 
agencyorby the responsible individual. The building officialis 
authorized to engage such expert opinion as deemed necessary 
to report upon unusual technical issues that arise, subject to the 
approval of the appointing authority. 



104.5 Identification. The building official shall carry proper 
identification when inspecting structures or premises in the 
performance of duties under this code. 

104.6 Right of entry. Where it is necessary to make an inspec- 
tion to enforce the provisions of this code, or where the build- 
ing officialhas reasonable cause to believe that there exists in a 
structure or upon a premises a condition which is contrary to or 
in violation of this code which makes the structure or premises 
unsafe, dangerous or hazardous, the building officialis autho- 
rized to enter the structure or premises at reasonable times to 
inspect or to perform the duties imposed by this code, provided 
that if such structure or premises be occupied that credentials 
be presented to the occupant and entry requested. If such struc- 
ture or premises is unoccupied, the bUilding official shall first 
make a reasonable effort to locate the owner or other person 
having charge or control of the structure or premises and 
request entry. If entry is refused, the building official shall have 
recourse to the remedies provided by law to secure entry. 

104.7 Department records. The building official shall keep 
official records of applications received, permits and certifi- 
cates issued, fees collected, reports of inspections, and notices 
and orders issued. Such records shall be retained in the official 
records for the period required for retention of public records. 

104.8 Liability. The building official, member of the board of 
appeals or employee charged with the enforcement of this 
code, while acting for thejurisdiction in good faith and without 
malice in the discharge of the duties required by this code or 
other pertinent law or ordinance, shall not thereby be rendered 
liable personally and is hereby relieved from personal liability 
for any damage accruing to persons or property as a result of 
any act or by reason of an act or omission in the discharge of 
official duties. Any suit instituted against an officer or 
employee because of an act performed by that officer or 
employee in the lawful discharge of duties and under the provi- 
sions of this code shall be defended by legal representative of 
thejurisdiction until the final termination of the proceedings. 
The building official or any subordinate shall not be liable for 
cost in any action, suit or proceeding that is instituted in pursu- 
ance of the provisions of this code. 

104.9 Approved materials and equipment. Materials, equip- 
ment and devices approved by the bUilding official shall be 
constructed and installed in accordance with such approval. 

104.9.1 Used materials and equipment. The use of used 
materials which meet the requirements of this code for new 
materials is permitted. Used equipment and devices shall 
not be reused unless approvedby the building official. 

104.10 Modifications. Wherever there are practical difficul- 
ties involved in carrying out the provisions of this code, the 
bUilding official shall have the authority to grant modifications 
for individual cases, upon application of the owner or owner's 
representative, provided the building officialshaW first find that 
special individual reason makes the strict letter of this code 
impractical and the modification is in compliance with the 
intent and purpose of this code and that such modification does 
not lessen health, accessibility, life and fire safety, or structural 
requirements. The details of action granting modifications 
shall be recorded and entered in the files of the department of 
building safety. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



104.11 Alternative materials, design and methods of con- 
struction and equipment. The provisions of this code are not 
intended to prevent the installation of any material or to pro- 
hibit any design or method of construction not specifically pre- 
scribed by this code, provided that any such alternative has 
been approved. An alternative material, design or method of 
construction shall be approvedwhere the building official finds 
that the proposed design is satisfactory and complies with the 
intent of the provisions of this code, and that the material, 
method or work offered is, for the purpose intended, at least the 
equivalent of that prescribed in this code in quality, strength, 
effectiveness, fire resistance, durability and safety. 

104.11.1 Research reports. Supporting data, where neces- 
sary to assist in the approval of materials or assemblies not 
specifically provided for in this code, shall consist of valid 
research reports from approve d sources. 

104.11.2 Tests. Whenever there is insufficient evidence of 
compliance with the provisions of this code, or evidence 
that a material or method does not conform to the require- 
ments of this code, or in order to substantiate claims for 
alternative materials or methods, the bUilding official shall 
have the authority to require tests as evidence of compliance 
to be made at no expense to the jurisdiction. Test methods 
shall be as specified in this code or by other recognized test 
standards. In the absence of recognized and accepted test 
methods, the building official shall approve the testing pro- 
cedures. Tests shall be performed by an approved agency. 
Reports of such tests shall be retained by the building offi- 
cial for the period required for retention of public records. 



SECTION 105 
PERMITS 

105.1 Required. Any owner or authorized agent who intends 
to construct, enlarge, alter, repair, move, demolish, or change 
the occupancy of a building or structure, or to erect, install, 
enlarge, alter, repair, remove, convert or replace any electrical, 
gas, mechanical or plumbing system, the installation of which 
is regulated by this code, or to cause any such work to be done, 
shall first make application to the bUilding official and obtain 
the required permit. 

105.1.1 Annual permit. In lieu of an individual permit for 
each alteration to an already approved electrical, gas, 
mechanical or plumbing installation, the building officially 
authorized to issue an annual permitupon application there- 
for to any person, firm or corporation regularly employing 
one or more qualified tradepersons in the building, structure 
or on the premises owned or operated by the applicant for 
the permit. 

105.1.2 Annual permit records. The person to whom an 
annual permit is issued shall keep a detailed record of alter- 
ations made under such annual permit. The building official 
shall have access to such records at all times or such records 
shall be filed with the building official as designated. 

105.2 Work exempt from permit. Exemptions from permit 
requirements of this code shall not be deemed to grant authori- 
zation for any work to be done in any manner in violation of the 



provisions of this code or any other laws or ordinances of this 
jurisdiction. Permits shall not be required for the following: 

Building: 

1. One-story detached accessory structures used as 
tool and storage sheds, playhouses and similar uses, 
provided the floor area does not exceed 120 square 
feet (11 m 2 ). 

2. Fences not over 6 feet (1829 mm) high. 

3. Oil derricks. 

4. Retaining walls that are not over 4 feet (1219 mm) in 
height measured from the bottom of the footing to 
the top of the wall, unless supporting a surcharge or 
impounding Class I, II or MA liquids. 

5. Water tanks supported directly on grade if the 
capacity does not exceed 5,000 gallons (18 925 L) 
and the ratio of height to diameter or width does not 
exceed 2:1. 

6. Sidewalks and driveways not more than 30 inches 
(762 mm) above adjacent grade, and not over any 
basement or story below and are not part of an 
accessible route. 

1. Painting, papering, tiling, carpeting, cabinets, coun- 
ter tops and similar finish work. 

8. Temporary motion picture, television and theater 
stage sets and scenery. 

9. Prefabricated swimming pools accessory to a Group 
R-3 occupancy that are less than 24 inches (610 mm) 
deep, do not exceed 5,000 gallons (18925 L) and are 
installed entirely above ground. 

10. Shade cloth structures constructed for nursery or 
agricultural purposes, not including service sys- 
tems. 

11. Swings and other playground equipment accessory 
to detached one- and two -family dwellings. 

12. Window awnings supported by an exterior wa//that 
do not project more than 54 inches (1372 mm) from 
the exterior wall and do not require additional sup- 
port of Groups R-3 and U occupancies. 

13. Nonfixed and movable fixtures, cases, racks, coun- 
ters and partitions not over 5 feet 9 inches (1753 
mm) in height. 

Electrical: 

Repairs and maintenance: Minor repair work, includ- 
ing the replacement of lamps or the connection of 
approvedportable electrical equipment to approvedper- 
manently installed receptacles. 

Radio and television transmitting stations: The provi- 
sions of this code shall not apply to electrical equipment 
used for radio and television transmissions, but do apply 
to equipment and wiring for a power supply and the 
installations of towers and antennas. 

Temporary testing systems: A permit shall not be 
required for the installation of any temporary system 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



required for the testing or servicing of electrical equip- 
ment or apparatus. 

Gas: 

1. Portable heating appliance. 

2. Replacement of any minor part that does not alter 
approval of equipment or make such equipment 
unsafe. 

Mechanical: 

1. Portable heating appliance. 

2. Portable ventilation equipment. 

3. Portable cooling unit. 

4. Steam, hot or chilled water piping within any heating 
or cooling equipment regulated by this code. 

5. Replacement of any part that does not alter its 
approval or make it unsafe. 

6. Portable evaporative cooler. 

7. Self-contained refrigeration system containing 10 
pounds (5 kg) or less of refrigerant and actuated by 
motors of 1 horsepower (746 W) or less. 

Plumbing: 

1. The stopping of leaks in drains, water, soil, waste or 
vent pipe, provided, however, that if any concealed 
trap, drain pipe, water, soil, waste or vent pipe 
becomes defective and it becomes necessary to 
remove and replace the same with new material, such 
work shall be considered as new work and a permit 
shall be obtained and inspection made as provided in 
this code. 

2. The clearing of stoppages or the repairing of leaks in 
pipes, valves or fixtures and the removal and reinstal- 
lation of water closets, provided such repairs do not 
involve or require the replacement or rearrangement 
of valves, pipes or fixtures. 

105.2.1 Emergency repairs. Where equipment replace- 
ments and repairs must be performed in an emergency situa- 
tion, the permit application shall be submitted within the 
next working business day to the bUilding official. 

105.2.2 Repairs. Application or notice to the building offi- 
cial is not required for ordinary repairs to structures, 
replacement of lamps or the connection of approved porta- 
ble electrical equipment to approved permanently installed 
receptacles. Such repairs shall not include the cutting away 
of any wall, partition or portion thereof, the removal or cut- 
ting of any structural beam or load-bearing support, or the 
removal or change of any required means of egress, or rear- 
rangement of parts of a structure affecting the egress 
requirements; nor shall ordinary repairs include addition to, 
alteration of, replacement or relocation of any standpipe, 
water supply, sewer, drainage, drain leader, gas, soil, waste, 
vent or similar piping, electric wiring or mechanical or other 
work affecting public health or general safety. 

105.2.3 Public service agencies. A permit shall not be 
required for the installation, alteration or repair of genera- 
tion, transmission, distribution or metering or other related 



equipment that is under the ownership and control of public 
service agencies by established right. 

105.3 Application for permit. To obtain a permit, the appli- 
cant shall first file an application therefor in writing on a form 
furnished by the department of building safety for that purpose. 
Such application shall: 

1. Identify and describe the work to be covered by the per- 
mit for which application is made. 

2. Describe the land on which the proposed work is to be 
done by legal description, street address or similar 
description that will readily identify and definitely locate 
the proposed building or work. 

3. Indicate the use and occupancy for which the proposed 
work is intended. 

4. Be accompanied by construction documents and other 
information as required in Section 107. 

5. State the valuation of the proposed work. 

6. Be signed by the applicant, or the applicant's authorized 
agent. 

7. Give such other data and information as required by the 
bUilding official. 

105.3.1 Action on application. The building official shall 
examine or cause to be examined applications for permits 
and amendments thereto within a reasonable time after fil- 
ing. If the application or the construction documents do not 
conform to the requirements of pertinent laws, the bUilding 
official shall reject such application in writing, stating the 
reasons therefor. If the bUilding officially satisfied that the 
proposed work conforms to the requirements of this code 
and laws and ordinances applicable thereto, the bUilding 
official shall issue a permit therefor as soon as practicable. 

105.3.2 Time limitation of application. An application for 
a permit for any proposed work shall be deemed to have 
been abandoned 180 days after the date of filing, unless such 
application has been pursued in good faith or a permit has 
been issued; except that the bUilding officialis authorized to 
grant one or more extensions of time for additional periods 
not exceeding 90 days each. The extension shall be 
requested in writing andjustifiable cause demonstrated. 

105.4 Validity of permit. The issuance or granting of apermit 
shall not be construed to be a permit for, or an approval of, any 
violation of any of the provisions of this code or of any other 
ordinance of the jurisdiction. Permits presuming to give 
authority to violate or cancel the provisions of this code or 
other ordinances of thejurisdiction shall not be valid. The issu- 
ance of a permit based on construction documents and other 
data shall not prevent the bUilding official from requiring the 
correction of errors in the construction documents and other 
data. The building officialis also authorized to prevent occu- 
pancy or use of a structure where in violation of this code or of 
any other ordinances of this jurisdiction. 

105.5 Expiration. Every permit issued shall become invalid 
unless the work on the site authorized by such permit is com- 
menced within 180 days after its issuance, or if the work autho- 
rized on the site by suchpermitis suspended or abandoned for a 
period of 180 days after the time the work is commenced. The 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



1 



building officialis authorized to grant, in writing, one or more 
extensions of time, for periods not more than 180 days each. 
The extension shall be requested in writing and justifiable 
cause demonstrated. 

105.6 Suspension or revocation. The bUilding official is 
authorized to suspend or revoke & permit issued under the pro- 
visions of this code wherever the permitis issued in error or on 
the basis of incorrect, inaccurate or incomplete information, or 
in violation of any ordinance or regulation or any of the provi- 
sions of this code. 

105.7 Placement of permit. The building permit or copy shall 
be kept on the site of the work until the completion of the pro- 
ject. 



SECTION 106 
FLOOR AND ROOF DESIGN LOADS 

106.1 Live loads posted. Where the live loads for which each 
floor or portion thereof of a commercial or industrial building 
is or has been designed to exceed 50 psf (2.40 kN/m 2 ) , such 
design live loads shall be conspicuously posted by the owner in 
that part of each story in which they apply, using durable signs. 
It shall be unlawful to remove or deface such notices 

106.2 Issuance of certificate of occupancy. A certificate of 
occupancy required by Section 111 shall not be issued until the 
floor load signs, required by Section 106. 1, have been installed. 

106.3 Restrictions on loading. It shall be unlawful to place, or 
cause or permit to be placed, on any floor or roof of a building, 
structure or portion thereof, a load greater than is permitted by 
this code. 



SECTION 107 
SUBMITTAL DOCUMENTS 

107.1 General. Submittal documents consisting of construc- 
tion documents, statement of special inspections, geotechnical 
report and other data shall be submitted in two or more sets 
with each permit application. The construction documents 
shall be prepared by a registered design professional where 
required by the statutes of the jurisdiction in which the project 
is to be constructed. Where special conditions exist, the build- 
ing officialis authorized to require additional construction doc- 
uments to be prepared by a registered design professional 

Exception: The building officialis authorized to waive the 
submission of construction documents and other data not 
required to be prepared by a registered design professional 
if it is found that the nature of the work applied for is such 
that review of construction documents is not necessary to 
obtain compliance with this code. 

107.2 Construction documents. Construction documents 
shall be in accordance with Sections 107.2.1 through 107.2.5. 

107.2.1 Information on construction documents. Con- 
struction documents shall be dimensioned and drawn upon 
suitable material. Electronic media documents are permit- 
ted to be submitted when approvedby the bUilding official. 
Construction documents shall be of sufficient clarity to indi- 
cate the location, nature and extent of the work proposed 



and show in detail that it will conform to the provisions of 
this code and relevant laws, ordinances, rules and regula- 
tions' as determined by the bUilding official. 

107.2.2 Fire protection system shop drawings. Shop draw- 
ings for the fire protection system(s) shall be submitted to 
indicate conformance to this code and the construction docu- 
ments and shall be app r ov e dp rior to the start of system instal- 
lation. Shop drawings shall contain all information as 
required by the referenced installation standards in Chapter 9. 

107.2.3 Means of egress. The construction documents shall 
show in sufficient detail the location, construction, size and 
character of all portions of the means of egress in compli- 
ance with the provisions of this code. In other than occupan- 
cies in Groups R-2, R-3, and 1-1, the construction 
documents shall designate the number of occupants to be 
accommodated on every floor, and in all rooms and spaces. 

107.2.4 Exterior wall envelope. Construction documents 
for all buildings shall describe the exterior wall envelope in 
sufficient detail to determine compliance with this code. 
The construction documents shall provide details of the 
exterior wall envelope as required, including flashing, inter- 
sections with dissimilar materials, corners, end details, con- 
troljoints, intersections at roof, eaves or parapets, means of 
drainage, water-resistive membrane and details around 
openings. 

The construction documents shall include manufac- 
turer's installation instructions that provide supporting doc- 
umentation that the proposed penetration and opening 
details described in the construction documents maintain 
the weather resistance of the exterior wall envelope. The 
supporting documentation shall fully describe the exterior 
wall system which was tested, where applicable, as well as 
the test procedure used. 

107.2.5 Site plan. The construction documents submitted 
with the application for permit shall be accompanied by a 
site plan showing to scale the size and location of new con- 
struction and existing structures on the site, distances from 
lot lines, the established street grades and the proposed fin- 
ished grades and, as applicable, flood hazard areas, 
floodways, and design flood elevations; and it shall be 
drawn in accordance with an accurate boundary line survey. 
In the case of demolition, the site plan shall show construc- 
tion to be demolished and the location and size of existing 
structures and construction that are to remain on the site or 
plot. The bUilding officialis authorized to waive or modify 
the requirement for a site plan when the application for per- 
mitis for alteration or repair or when otherwise warranted. 

107.2.5.1 Design flood elevations. Where design flood 
elevations are not specified, they shall be established in 
accordance with Section 1612.3.1. 

107.3 Examination of documents. The building official shall 
examine or cause to be examined the accompanying submittal 
documents and shall ascertain by such examinations whether 
the construction indicated and described is in accordance with 
the requirements of this code and other pertinent laws or ordi- 
nances. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



107.3.1 Approval of construction documents. When the 
bUilding officialissues ^permit, the construction documents 
shall be approved, in writing or by stamp, as "Reviewed for 
Code Compliance." One set of construction documents so 
reviewed shall be retained by the bUilding official. The other 
set shall be returned to the applicant, shall be kept at the site 
of work and shall be open to inspection by the building offi- 
cialor a duly authorized representative. 

107.3.2 Previous approvals. This code shall not require 
changes in the construction documents, construction or des- 
ignated occupancy of a structure for which a lawful permit 
has been heretofore issued or otherwise lawfully autho- 
rized, and the construction of which has been pursued in 
good faith within 180 days after the effective date of this 
code and has not been abandoned. 

107.3.3 Phased approval. The building officials autho- 
rized to issue apermitfor the construction of foundations or 
any other part of a building or structure before the construc- 
tion documents for the whole building or structure have 
been submitted, provided that adequate information and 
detailed statements have been filed complying with perti- 
nent requirements of this code. The holder of such permit 
for the foundation or other parts of a building or structure 
shall proceed at the holder's own risk with the building oper- 
ation and without assurance that a permit for the entire 
structure will be granted. 

107.3.4 Design professional in responsible charge. 

107.3.4.1 General. When it is required that documents 
be prepared by a registered design professional, the 
bUilding official shall be authorized to require the owner 
to engage and designate on the building permit applica- 
tion a registered design professional who shall act as the 
registered design professional in responsible charge. If 
the circumstances require, the owner shall designate a 
substitute registered design professional in responsible 
chargewho shall perform the duties required of the origi- 
nal registered design professional in responsible charge. 
The bUilding official shall be notified in writing by the 
owner if the registered designpr of essionalin responsible 
charge is changed or is unable to continue to perform the 
duties. 

The registered design professional in responsible 
charge shall be responsible for reviewing and coordinat- 
ing submittal documents prepared by others, including 
phased and deferred submittal items, for compatibility 
with the design of the building. 

107.3.4.2 Deferred submittals. For the purposes of this 
section, deferred submittals are defined as those portions 
of the design that are not submitted at the time of the 
application and that are to be submitted to the building 
official within a specified period. 

Deferral of any submittal items shall have the prior 
approval of the building official. The registered design 
professional in responsible charge shall list the deferred 
submittals on the construction documents for review by 
the bUilding official. 



Documents for deferred submittal items shall be sub- 
mitted to the registered design professional in responsi- 
ble charge who shall review them and forward them to 
the bUilding official with a notation indicating that the 
deferred submittal documents have been reviewed and 
found to be in general conformance to the design of the 
building. The deferred submittal items shall not be 
installed until the deferred submittal documents have 
been approved^ the building official. 

107.4 Amended construction documents. Work shall be 
installed in accordance with the approved construction docu- 
ments, and any changes made during construction that are not 
in compliance with the approved construction documents shall 
be resubmitted for approval as an amended set of construction 
documents. 

107.5 Retention of construction documents. One set of 
approved construction documents shall be retained by the 
building officialfor a period of not less than 180 days from date 
of completion of the permitted work, or as required by state or 
local laws. 



SECTION 108 
TEMPORARY STRUCTURES AND USES 

108.1 General. The building official is authorized to issue a 
permit for temporary structures and temporary uses. Such per- 
mits shall be limited as to time of service, but shall not be per- 
mitted for more than 180 days. The building official is 
authorized to grant extensions for demonstrated cause. 

108.2 Conformance. Temporary structures and uses shall con- 
form to the structural strength, fire safety, means of egress, 
accessibility, light, ventilation and sanitary requirements of 
this code as necessary to ensure public health, safety and gen- 
eral welfare. 

108.3 Temporary power. The building officialis authorized to 
give permission to temporarily supply and use power in part of 
an electric installation before such installation has been fully 
completed and the final certificate of completion has been 
issued. The part covered by the temporary certificate shall 
comply with the requirements specified for temporary lighting, 
heat or power in NFPA 70. 

108.4 Termination of approval. The building officialis autho- 
rized to terminate such permit for a temporary structure or use 
and to order the temporary structure or use to be discontinued. 



SECTION 109 
FEES 

109.1 Payment of fees. A permit shall not be valid until the 
fees prescribed by law have been paid, nor shall an amendment 
to apermitbc released until the additional fee, if any, has been 
paid. 

109.2 Schedule of permit fees. On buildings, structures, elec- 
trical, gas, mechanical, and plumbing systems or alterations 
requiring a permit, a fee for each permit shall be paid as 
required, in accordance with the schedule as established by the 
applicable governing authority. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



109.3 Building permit valuations. The applicant for apermit 
shall provide an estimated perm lvalue at time of application. 
Permit valuations shall include total value of work, including 
materials and labor, for which the permitis being issued, such 
as electrical, gas, mechanical, plumbing equipment and perma- 
nent systems. If, in the opinion of the building official, the valu- 
ation is underestimated on the application, the permit shall be 
denied, unless the applicant can show detailed estimates to 
meet the approval of the building official. Final building permit 
valuation shall be set by the building official. 

109.4 Work commencing before permit issuance. Any person 
who commences any work on a building, structure, electrical, 
gas, mechanical or plumbing system before obtaining the neces- 
sary permits shall be subject to a fee established by the bUilding 
official that shall be in addition to the required permit fees. 

109.5 Related fees. The payment of the fee for the construc- 
tion, alteration, removal or demolition for work done in 
connection to or concurrently with the work authorized by a 
building permit shall not relieve the applicant or holder of the 
permit from the payment of other fees that are prescribed by 
law. 

109.6 Refunds. The bUilding officially authorized to establish 
a refund policy. 



SECTION 110 
INSPECTIONS 

110.1 General. Construction or work for which a permit is 
required shall be subject to inspection by the bUilding official 
and such construction or work shall remain accessible and 
exposed for inspection purposes until approved. Approval as a 
result of an inspection shall not be construed to be an approval 
of a violation of the provisions of this code or of other ordi- 
nances of the jurisdiction. Inspections presuming to give 
authority to violate or cancel the provisions of this code or of 
other ordinances of thejurisdiction shall not be valid. It shall be 
the duty of the permit applicant to cause the work to remain 
accessible and exposed for inspection purposes. Neither the 
bUilding officialnor thejurisdiction shall be liable for expense 
entailed in the removal or replacement of any material required 
to allow inspection. 

110.2 Preliminary inspection. Before issuing a permit, the 
building official is authorized to examine or cause to be exam- 
ined buildings, structures and sites for which an application has 
been filed. 

110.3 Required inspections. The bUilding official, upon noti- 
fication, shall make the inspections set forth in Sections 
110.3.1 through 110.3.10. 

110.3.1 Footing and foundation inspection. Footing and 
foundation inspections shall be made after excavations for 
footings are complete and any required reinforcing steel is 
in place. For concrete foundations, any required forms shall 
be in place prior to inspection. Materials for the foundation 
shall be on the job, except where concrete is ready mixed in 
accordance with ASTM C 94, the concrete need not be on 
the job. 



110.3.2 Concrete slab and under-floor inspection. Con- 
crete slab and under-floor inspections shall be made after 
in- slab or under-floor reinforcing steel and building service 
equipment, conduit, piping accessories and other ancillary 
equipment items are in place, but before any concrete is 
placed or floor sheathing installed, including the subfloor. 

1 10.3.3 Lowest floor elevation. In flood hazard areas, upon 
placement of the lowest floor, including the basement, and 
prior to further vertical construction, the elevation certifica- 
tion required in Section 1612.5 shall be submitted to the 
bUilding official. 

110.3.4 Frame inspection. Framing inspections shall be 
made after the roof deck or sheathing, all framing, 
fireblocking and bracing are in place and pipes, chimneys 
and vents to be concealed are complete and the rough elec- 
trical, plumbing, heating wires, pipes and ducts are 
approved. 

110.3.5 Lath and gypsum board inspection. Lath and 
gypsum board inspections shall be made after lathing and 
gypsum board, interior and exterior, is in place, but before 
any plastering is applied or gypsum boardjoints and fasten- 
ers are taped and finished. 

Exception: Gypsum board that is not part of a fire-resis- 
tance-rated assembly or a shear assembly. 

110.3.6 Fire- and smoke-resistant penetrations. proteC- 1 
tion of joints and penetrations in fire-resistance-rated 
assemblies, smoke barriers and smoke partitions shall not 
be concealed from view until inspected and approved. 

110.3.7 Energy efficiency inspections. Inspections shall 
be made to determine compliance with Chapter 13 and shall 
include, but not be limited to, inspections for: envelope 
insulation R- and V-values, fenestration V-value, duct sys- 
tem R- value, and HVAC and water-heating equipment effi- 
ciency. 

110.3.8 Other inspections. In addition to the inspections 
specified above, the bUilding official is authorized to make 
or require other inspections of any construction work to 
ascertain compliance with the provisions of this code and 
other laws that are enforced by the department of building 
safety. 

110.3.9 Special inspections. For special inspections, see 
Section 1704. 

110.3.10 Final inspection. The final inspection shall be 
made after all work required by the building permitis com- 
pleted. 

110.4 Inspection agencies. The bUilding official is authorized 
to accept reports of approved inspection agencies, provided 
such agencies satisfy the requirements as to qualifications and 
reliability. 

110.5 Inspection requests. It shall be the duty of the holder of 
the building permit or their duly authorized agent to notify the 
bUilding official when work is ready for inspection. It shall be 
the duty of the/? ermit holder to provide access to and means for 
inspections of such work that are required by this code. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



110.6 Approval required. Work shall not be done beyond the 
point indicated in each successive inspection without first 
obtaining the approval of the bUilding official. The bUilding 
official, upon notification, shall make the requested inspections 
and shall either indicate the portion of the construction that is 
satisfactory as completed, or notify the permit holder or his or 
her agent wherein the same fails to comply with this code. Any 
portions that do not comply shall be corrected and such portion 
shall not be covered or concealed until authorized by the build- 
ing official. 



building officialshaU set a time period during which the tempo- 
rary certificate of occupancy is valid. 

111.4 Revocation. The bUilding official is authorized to, in 
writing, suspend or revoke a certificate of occupancy or com- 
pletion issued under the provisions of this code wherever the 
certificate is issued in error, or on the basis of incorrect infor- 
mation supplied, or where it is determined that the building or 
structure or portion thereof is in violation of any ordinance or 
regulation or any of the provisions of this code. 



SECTION 111 
CERTIFICATE OF OCCUPANCY 

111.1 Use and occupancy. No building or structure shall be 
used or occupied, and no change in the existing occupancy 
classification of a building or structure or portion thereof shall 
be made, until the building official has issued a certificate of 
occupancy therefor as provided herein. Issuance of a certificate 
of occupancy shall not be construed as an approval of a viola- 
tion of the provisions of this code or of other ordinances of the 
jurisdiction. 

Exception: Certificates of occupancy are not required for 
work exempt from permits under Section 105.2. 

111.2 Certificate issued. After the building official inspects 
the building or structure and finds no violations of the provi- 
sions of this code or other laws that are enforced by the depart- 
ment of building safety, the bUilding official shall issue a 
certificate of occupancy that contains the following: 

1. The building permit number. 

2. The address of the structure. 

3. The name and address of the owner. 

4. A description of that portion of the structure for which 
the certificate is issued. 

5. A statement that the described portion of the structure 
has been inspected for compliance with the require- 
ments of this code for the occupancy and division of 
occupancy and the use for which the proposed occu- 
pancy is classified. 

6. The name of the building official. 

7. The edition of the code under which the permit was 
issued. 

8. The use and occupancy, in accordance with the provi- 
sions of Chapter 3. 

9. The type of construction as defined in Chapter 6. 

10. The design occupant load. 

11. If an automatic sprinkler system is provided, whether 
the sprinkler system is required. 

12. Any special stipulations and conditions of the building 
permit. 

111.3 Temporary occupancy. The building officials autho- 
rized to issue a temporary certificate of occupancy before the 
completion of the entire work covered by the permit, provided 
that such portion or portions shall be occupied safely. The 



SECTION 112 
SERVICE UTILITIES 

112.1 Connection of service utilities. No person shall make 
connections from a utility, source of energy, fuel or power to 
any building or system that is regulated by this code for which a 
permitis required, until released by the building official. 

112.2 Temporary connection. The bUilding off iciahh^W have 
the authority to authorize the temporary connection of the 
building or system to the utility source of energy, fuel or power. 

112.3 Authority to disconnect service utilities. The bUilding 
official shall have the authority to authorize disconnection of 
utility service to the building, structure or system regulated by 
this code and the referenced codes and standards set forth in 
Section 101.4 in case of emergency where necessary to elimi- 
nate an immediate hazard to life or property or when such util- 
ity connection has been made without the approval required by 
Section 112.1 or 112.2. The bUilding official shall notify the 
serving utility, and wherever possible the owner and occupant 
of the building, structure or service system of the decision to 
disconnect prior to taking such action. If not notified prior to 
disconnecting, the owner or occupant of the building, structure 
or service system shall be notified in writing, as soon as practi- 
cal thereafter. 



SECTION 113 
BOARD OF APPEALS 

113.1 General. In order to hear and decide appeals of orders, 
decisions or determinations made by the building officialreia- 
tive to the application and interpretation of this code, there shall 
be and is hereby created a board of appeals. The board of 
appeals shall be appointed by the applicable governing author- 
ity and shall hold office at its pleasure. The board shall adopt 
rules of procedure for conducting its business. 

113.2 Limitations on authority. An application for appeal 
shall be based on a claim that the true intent of this code or the 
rules legally adopted thereunder have been incorrectly inter- 
preted, the provisions of this code do not fully apply or an 
equally good or better form of construction is proposed. The 
board shall have no authority to waive requirements of this 
code. 

113.3 Qualifications. The board of appeals shall consist of 
members who are qualified by experience and training to pass 
on matters pertaining to building construction and are not 
employees of the jurisdiction. 



2009 INTERNATIONAL BUILDING CODE® 



SCOPE AND ADMINISTRATION 



SECTION 114 
VIOLATIONS 

114.1 Unlawful acts. It shall be unlawful for any person, firm 
or corporation to erect, construct, alter, extend, repair, move, 
remove, demolish or occupy any building, structure or equip- 
ment regulated by this code, or cause same to be done, in con- 
flict with or in violation of any of the provisions of this code. 

1 14.2 Notice ofviolation. The building officially authorized to 
serve a notice of violation or order on the person responsible 
for the erection, construction, alteration, extension, repair, 
moving, removal, demolition or occupancy of a building or 
structure in violation of the provisions of this code, or in viola- 
tion of apermit or certificate issued under the provisions of this 
code. Such order shall direct the discontinuance of the illegal 
action or condition and the abatement of the violation. 

1 14.3 Prosecution ofviolation. If the notice ofviolation is not 
complied with promptly, the building ojflcialis authorized to 
request the legal counsel of the jurisdiction to institute the 
appropriate proceeding at law or in equity to restrain, correct or 
abate such violation, or to require the removal or termination of 
the unlawful occupancy of the building or structure in violation 
of the provisions of this code or of the order or direction made 
pursuant thereto. 

114.4 Violation penalties. Any person who violates a provi- 
sion of this code or fails to comply with any of the requirements 
thereof or who erects, constructs, alters or repairs a building or 
structure in violation of the approved construction documents 
or directive of the bUilding official, or of a permit or certificate 
issued under the provisions of this code, shall be subject to pen- 
alties as prescribed by law. 



SECTION 115 
STOP WORK ORDER 

115.1 Authority. Whenever the building official finds any 
work regulated by this code being performed in a manner either 
contrary to the provisions of this code or dangerous or unsafe, 
the bUilding official is authorized to issue a stop work order. 

115.2 Issuance. The stop work order shall be in writing and 
shall be given to the owner of the property involved, or to the 
owner's agent, or to the person doing the work. Upon issuance 
of a stop work order, the cited work shall immediately cease. 
The stop work order shall state the reason for the order, and the 
conditions under which the cited work will be permitted to 
resume. 

115.3 Unlawful continuance. Any person who shall continue 
any work after having been served with a stop work order, 
except such work as that person is directed to perform to 
remove a violation or unsafe condition, shall be subject to pen- 
alties as prescribed by law. 



tilation, or which constitute a fire hazard, or are otherwise dan- 
gerous to human life or the public welfare, or that involve ille- 
gal or improper occupancy or inadequate maintenance, shall be 
deemed an unsafe condition. Unsafe structures shall be taken 
down and removed or made safe, as the bUilding official deems 
necessary and as provided for in this section. A vacant structure 
that is not secured against entry shall be deemed unsafe. 

116.2 Record. The building official shall cause a report to be 
filed on an unsafe condition. The report shall state the occu- 
pancy of the structure and the nature of the unsafe condition. 

116.3 Notice. If an unsafe condition is found, the bUilding offi- 
cial shall serve on the owner, agent or person in control of the 
structure, a written notice that describes the condition deemed 
unsafe and specifies the required repairs or improvements to be 
made to abate the unsafe condition, or that requires the unsafe 
structure to be demolished within a stipulated time. Such notice 
shall require the person thus notified to declare immediately to 
the building official acceptance or rejection of the terms of the 
order. 

116.4 Method of service. Such notice shall be deemed prop- 
erly served if a copy thereof is (a) delivered to the owner per- 
sonally; (b) sent by certified or registered mail addressed to the 
owner at the last known address with the return receipt 
requested; or (c) delivered in any other manner as prescribed by 
local law. If the certified or registered letter is returned showing 
that the letter was not delivered, a copy thereof shall be posted 
in a conspicuous place in or about the structure affected by such 
notice. Service of such notice in the foregoing manner upon the 
owner's agent or upon the person responsible for the structure 
shall constitute service of notice upon the owner. 

116.5 Restoration. The structure or equipment determined to 
be unsafe by the bUilding offlcialis permitted to be restored to a 
safe condition. To the extent that repairs, alterations or addi- 
tions are made or a change of occupancy occurs during the res- 
toration of the structure, such repairs, alterations, additions or 
change of occupancy shall comply with the requirements of 
Section 105.2.2 and Chapter 34. 



SECTION 116 
UNSAFE STRUCTURES AND EQUIPMENT 

116.1 Conditions. Structures or existing equipment that are or 
hereafter become unsafe, insanitary or deficient because of 
inadequate means of egress facilities, inadequate light and ven- 



2009 INTERNATIONAL BUILDING CODE® 



10 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 2 

DEFINITIONS 



SECTION 201 
GENERAL 

201.1 Scope. Unless otherwise expressly stated, the following 
words and terms shall, for the purposes of this code, have the 
meanings shown in this chapter. 

201.2 Interchangeability. Words used in the present tense 
include the future; words stated in the masculine gender 
include the feminine and neuter; the singular number includes 
the plural and the plural, the singular. 

201.3 Terms defined in other codes. Where terms are not 
defined in this code and are defined in the International Fuel 
Gas Code, International Fire Code, International Mechanical 
Code or International Plumbing Code, such terms shall have 
the meanings ascribed to them as in those codes. 

201.4 Terms not defined. Where terms are not defined 
through the methods authorized by this section, such terms 
shall have ordinarily accepted meanings such as the context 
implies. 



SECTION 202 
DEFINITIONS 

AAC MASONRY. See Section 2102.1. 

ACCESSIBLE. See Section 1102.1. 

ACCESSIBLE MEANS OF EGRESS. See Section 1002.1. 

ACCESSIBLE ROUTE. See Section 1102.1. 

ACCESSIBLE UNIT. See Section 1102.1. 

ACCREDITATION BODY. See Section 2302.1. 

ADDITION. An extension or increase in floor area or height 
of a building or structure. 

ADHERED MASONRY VENEER. See Section 1402.1. 

ADOBE CONSTRUCTION. See Section 2102.1. 

Adobe, stabilized. See Section 2102.1. 

Adobe, unstabilized. See Section 2102.1. 
[F] AEROSOL. See Section 307.2. 

Levell aerosol products. See Section 307.2. 

Level 2 aerosol products. See Section 307.2. 

Level 3 aerosol products. See Section 307.2. 

[F] AEROSOL CONTAINER. See Section 307.2. 

I AGGREGATE. See Section 1502.1. 

AGRICULTURAL, BUILDING. A structure designed and 
constructed to house farm implements, hay, grain, poultry, live- 
stock or other horticultural products. This structure shall not be 
a place of human habitation or a place of employment where 
agricultural products are processed, treated or packaged, nor 
shall it be a place used by the public. 



AIR-INFLATED STRUCTURE. See Section 3102.2. 
AIR-SUPPORTED STRUCTURE. See Section 3102.2. 

Double skin. See Section 3102.2. 

Single skin. See Section 3102.2. 

AISLE. See Section 1002.1. 

AISLE ACCESSWAY. See Section 1002.1. 

[F] ALARM NOTIFICATION APPLIANCE. See Section 
902.1. 

[F] ALARM SIGNAL. See Section 902.1. 

[F] ALARM VERIFICATION FEATURE. See Section 
902.1. 

ALLOWABLE STRESS DESIGN. See Section 1602.1. 

ALTERATION. Any construction or renovation to an existing 
structure other than repair or addition. 

ALTERNATING TREAD DEVICE. See Section 1002.1. 

AMBULATORY HEALTH CARE FACILITY. Buildings or 
portions thereof used to provide medical, surgical, psychiatric, 
nursing or similar care on a less than 24-hour basis to individu- 
als who are rendered incapable of self-preservation. 

ANCHOR. See Section 2102.1. 

ANCHOR BUILDING. See Section 402.2. 

ANCHORED MASONRY VENEER. See Section 1402.1. 

ANNULAR SPACE. See Section 702.1. 

[F] ANNUNCIATOR. See Section 902.1. 

APPROVED. Acceptable to the code official or authority hav- 
ingjurisdiction. 

APPROVED AGENCY. See Section 1702.1. 

APPROVED FABRICATOR. See Section 1702.1. 

APPROVED SOURCE. An independent person, firm or cor- 
poration, approvedby the building official, who is competent 
and experienced in the application of engineering principles to 
materials, methods or systems analyses. 

ARCHITECTURAL TERRACOTTA. See Section 2102.1. 

AREA (for masonry). See Section 2102.1. I 

Bedded. See Section 2102.1. 

Gross cross-sectional. See Section 2102.1. 

Net cross-sectional. See Section 2102.1. 

AREA, BUILDING. See Section 502.1. 

AREA OF REFUGE. See Section 1002.1. 

AREAWAY. A subsurface space adjacent to a building open at 
the top or protected at the top by a grating or guard. 

ASSISTED LIVING FACILITIES. See Section 310.2, "Res- 
idential Care/Assisted living facilities." 



2009 INTERNATIONAL BUILDING CODE® 



11 



DEFINITIONS 



ATRIUM. See Section 404.1.1. 

ATTIC. The space between the ceiling beams of the top story 
and the roof rafters. 

[F] AUDIBLE ALARM NOTIFICATION APPLIANCE. 
See Section 902.1. 

AUTOCLAVED AERATED CONCRETE (AAC). See Sec- 
tion 2102.1. 

[F] AUTOMATIC. See Section 902.1. 

[F] AUTOMATIC FIRE-EXTINGUISHING SYSTEM. 
See Section 902.1. 

I [FT AUTOMATIC SMOKE DETECTION SYSTEM. See 
Section 902.1. 

[F] AUTOMATIC SPRINKLER SYSTEM. See Section 
902.1. 

[F] AVERAGE AMBIENT SOUND LEVEL. See Section 
902.1. 

AWNING. An architectural projection that provides weather 
protection, identity or decoration and is wholly supported by 

I the building to which it is attached. An awning is comprised of 
a lightweight frame structure over which a covering is attached. 

• BACKING. See Section 1402.1. 

[F] BALED COTTON. See Section 307.2. 

[F] BALED COTTON, DENSELY PACKED. See Section 

307.2. 

I BALLAST. See Section 1502.1. 

[F] BARRICADE. See Section 307.2. 

Artificial barricade. See Section 307.2. 

Natural barricade. See Section 307.2. 
BASE FLOOD. See Section 1612.2. 
BASE FLOOD ELEVATION. See Section 1612.2. 

I BASEMENT (for other than flood loads). See Section 502.1. 
BASEMENT (for flood loads). See Section 1612.2. 
BEARING WALL STRUCTURE. See Section 1614.2. 
BED JOINT. See Section 2102.1. 
BLEACHERS. See Section 1002.1. 
BOARDING HOUSE. See Section 310.2. 
[F] BOILING POINT. See Section 307.2. 
BOND BEAM. See Section 2102.1. 
BRACED WALL LINE. See Section 2302.1. 
BRACED WALL PANEL. See Section 2302.1. 
BRICK. See Section 2102.1. 

Calcium silicate (sand lime brick). See Section 2102.1. 
Clay or shale. See Section 2102.1. 
Concrete. See Section 2102.1. 

BUILDING. Any structure used or intended for supporting or 
sheltering any use or occupancy. 

I BUILDING ELEMENT. See Section 702.1. 



BUILDING LINE. The line established by law, beyond which 
a building shall not extend, except as specifically provided by 
law. 

BUILDING OFFICIAL. The officer or other designated 
authority charged with the administration and enforcement of 
this code, or a duly authorized representative. 

BUILT-UP ROOF COVERING. See Section 1502 1 

CABLE-RESTRAINED, AIR-SUPPORTED STRUC- 
TURE. See Section 3102.2. 

CANOPY. A permanent structure or architectural projection 
of rigid construction over which a covering is attached that pro- 
vides weather protection, identity or decoration, and shall be 
structurally independent or supported by attachment to a build- 
ing on one end and by not less than one stanchion on the outer 
end. 

[FT CARBON DIOXIDE EXTINGUISHING SYSTEMS. 
See Section 902.1. 

CAST STONE. See Section 2102.1. 

[FT CEILING LIMIT. See Section 902.1. 

CEILING RADIATION DAMPER. See Section 702.1 . 

CELL. See Section 408.1.1. 

CELL (masonry). See Section 2102.1. 

CELL TIER. See Section 408.1 .1. 

CEMENT PLASTER. See Section 2502.1. 

CERAMIC FIBER BLANKET. See Section 721.1.1. 

CERTIFICATE OF COMPLIANCE. See Section 1702.1. 

CHILD CARE FACILITIES. See Section 308.3.1. I 

CHIMNEY. See Section 2102.1. 

CHIMNEY TYPES. See Section 2102.1. 

High-heat appliance type. See Section 2102.1. 

Low-heat appliance type. See Section 2102.1. 

Masonry type. See Section 2102.1. 

Medium-heat appliance type. See Section 2102.1. 

CIRCULATION PATH. See Section 1102.1. 

[F] CLEAN AGENT. See Section 902.1. 

CLEANOUT. See Section 2102.1. 

CLINIC, OUTPATIENT. See Section 304.1.1. I 

[FT CLOSED SYSTEM. See Section 307.2. 

COLLAR JOINT. See Section 2102.1. 

COLLECTOR. See Section 2302.1. 

COMBINATION FIRE/SMOKE DAMPER. See Section 
702.1. 

[F] COMBUSTIBLE DUST. See Section 307.2. 

[FT COMBUSTIBLE FIBERS. See Section 307.2. 

[F] COMBUSTIBLE LIQUID. See Section 307.2. 

Class II. See Section 307.2. 



12 



2009 INTERNATIONAL BUILDING CODE® 



DEFINITIONS 



Class I1IA. See Section 307.2. 

Class IIIB. See Section 307.2. 

COMMON USE. See Section 1102.1. 

COMMON PATH OF EGRESS TRAVEL. See Section 
1002.1. 

[F] COMPRESSED GAS. See Section 307.2. 

COMPRESSIVE STRENGTH OF MASONRY. See Sec- 
tion 2102.1. 

CONCRETE, CARBONATE AGGREGATE. See Section 
721.1.1. 

CONCRETE, CELLULAR. See Section 721.1.1. 

CONCRETE, LIGHTWEIGHT AGGREGATE. See Sec- 
tion 721.1.1. 

CONCRETE, PERLITE. See Section 721.1 .1. 

CONCRETE, SAND-LIGHTWEIGHT. See Section 721.1.1. 

CONCRETE, SILICEOUS AGGREGATE. See Section 
721.1.1. 

CONCRETE, VERMICULITE. See Section 721.1.1. 

CONGREGATE LIVING FACILITIES. See Section 310.2. 

CONNECTOR. See Section 2102.1. 

[F] CONSTANTLY ATTENDED LOCATION. See Section 
902.1. 

CONSTRUCTION DOCUMENTS. Written, graphic and 
pictorial documents prepared or assembled for describing the 
design, location and physical characteristics of the elements of 
a project necessary for obtaining a building permit. 

CONSTRUCTION TYPES. See Section 602. 

Type I. See Section 602.2. 

Type II. See Section 602.2. 

Type III. See Section 602.3. 

Type IV. See Section 602.4. 

Type V. See Section 602.5. 

[F] CONTINUOUS GAS DETECTION SYSTEM. See 

Section 415 .2. 

\F] CONTROL AREA. See Section 307.2. 

CONTROLLED LOW-STRENGTH MATERIAL. A 

self-compacted, cementitious material used primarily as a 
backfill in place of compacted fill. 

CONVENTIONAL LIGHT-FRAME CONSTRUCTION. 

See Section 2302.1. 

CORRIDOR. See Section 1002.1. 

CORROSION RESISTANCE. The ability of a material to 
withstand deterioration of its surface or its properties when 
exposed to its environment. 

[F] CORROSIVE. See Section 307.2. 



COURT. An open, uncovered space, unobstructed to the sky, 
bounded on three or more sides by exterior building walls or 
other enclosing devices. 

COVER. See Section 2102.1. 

COVERED MALL BUILDING. See Section 402.2. 

Mall. See Section 402.2. 

Open mall. See Section 402.2. 

Open mall building. See Section 402.2. 

CRIPPLE WALL. See Section 2302.1. 

[F] CRYOGENIC FLUID. See Section 307.2. 

DALLE GLASS. See Section 2402.1. 

DAMPER. See Section 702.1. 

DANGEROUS. See Section 3402.1. 

[F] DAY BOX. See Section 307.2. 

DEAD LOADS. See Section 1602.1. 

DECORATIVE GLASS. See Section 2402.1. 

[F] DECORATIVE MATERIALS. All materials applied 
over the building interior finish for decorative, acoustical or 
other effect (such as curtains, draperies, fabrics, streamers and 
surface coverings), and all other materials utilized for decora- 
tive effect (such as batting, cloth, cotton, hay, stalks, straw, 
vines, leaves, trees, moss and similar items), including foam 
plastics and materials containing foam plastics. Decorative 
materials do not include floor coverings, ordinary window 
shades, interior finish and materials 0.025 inch (0.64 mm) or 
less in thickness applied directly to and adhering tightly to a 
substrate. 

DEEP FOUNDATION. See Section 1802.1. 

[F] DEFLAGRATION. See Section 307.2. 

[F] DELUGE SYSTEM. See Section 902.1 . 

DESIGN DISPLACEMENT. See Section 1908.1.1. 

DESIGN EARTHQUAKE GROUND MOTION. See Sec- 
tion 1613.2. 

DESIGN FLOOD. See Section 1612.2. 

DESIGN FLOOD ELEVATION. See Section 1612.2. 

DESIGN STRENGTH. See Section 1602.1. 

DESIGNATED SEISMIC SYSTEM. See Section 1702.1. 

[F] DETACHED BUILDING. See Section 415.2. 

DETAILED PLAIN CONCRETE STRUCTURAL WALL. 

See Section 1908.1.1. 

DETECTABLE WARNING. See Section 1102.1. 
[F] DETECTOR, HEAT. See Section 902.1. 
[F] DETONATION. See Section 307.2. 
DETOXIFICATION FACILITY. See Section 308.3.1. 
DIAPHRAGM. See Sections 1602.1 and 2302.1. 
Diaphragm, blocked. See Section 1602.1. 



i 



2009 INTERNATIONAL BUILDING CODE® 



13 



DEFINITIONS 



Diaphragm, boundary. See Section 1602.1. 

Diaphragm, chord. See Section 1602.1. 

Diaphragm, flexible. See Section 1602.1. 

Diaphragm, rigid. See Section 1602.1. 

Diaphragm, unblocked. See Section 2302.1. 
DIMENSIONS. See Section 2102.1. 

Actual. See Section 2102.1. 

Nominal. See Section 2102.1. 

Specified. See Section 2102.1. 
\F] DISPENSING. See Section 307.2. 
DOOR, BALANCED. See Section 1002.1. 
DORMITORY. See Section 310.2. 
DRAFTSTOP. See Section 702.1. 
DRAG STRUT. See Section 2302.1. 

I DRILLED SHAFT. See Section 1802.1. 
Socketed drilled shaft. See Section 1802.1. 

[F] DRY-CHEMICAL EXTINGUISHING AGENT. See 
Section 902.1. 

DRY FLOODPROOFING. See Section 1612.2. 

DURATION OF LOAD. See Section 1602.1. 

DWELLING. A building that contains one or two dwelling 
units used, intended or designed to be used, rented, leased, let 
or hired out to be occupied for living purposes. 

DWELLING UNIT. A single unit providing complete, inde- 
pendent living facilities for one or more persons, including per- 
manent provisions for living, sleeping, eating, cooking and 
sanitation. 

DWELLING UNIT OR SLEEPING UNIT, MULTI- 
STORY. See Section 1102.1. 

DWELLING UNIT OR SLEEPING UNIT, TYPE A. See 

Section 1102.1. 

DWELLING UNIT OR SLEEPING UNIT, TYPE B. See 

Section 1102.1. 

EGRESS COURT. See Section 1002.1. 

I ELEVATOR GROUP. See Section 902.1. 

[F] EMERGENCY ALARM SYSTEM. See Section 902.1. 

[F] EMERGENCY CONTROL STATION. See Section 
415.2. 

EMERGENCY ESCAPE AND RESCUE OPENING. See 

Section 1002.1. 

[F] EMERGENCY VOICE/ALARM COMMUNICA- 
TIONS. See Section 902.1. 

EMPLOYEE WORK AREA. See Section 1102.1. 

EQUIPMENT PLATFORM. See Section 502.1. 

ESSENTIAL FACILITIES. See Section 1602.1. 

\F] EXHAUSTED ENCLOSURE. See Section 415.2. 



EXISTING CONSTRUCTION. See Section 1612.2. 

EXISTING STRUCTURE. See Sections 1612.2 and 3402.1. 

EXIT. See Section 1002.1. 

EXIT ACCESS. See Section 1002.1. 

EXIT ACCESS DOORWAY. See Section 1002.1. I 

EXIT DISCHARGE. See Section 1002.1. 

EXIT DISCHARGE, LEVEL OF. See Section 1002.1. 

EXIT ENCLOSURE. See Section 1002.1. 

EXIT, HORIZONTAL. See Section 1002.1. 

EXIT PASSAGEWAY. See Section 1002.1. 

EXPANDED VINYL WALL COVERING. See Section 
802.1. 

[FT EXPLOSION. See Section 307.2. 

[FT EXPLOSIVE. See Section 307.2. 

High explosive. See Section 307.2. 

Low explosive. See Section 307.2. 

Mass detonating explosives. See Section 307.2. 

UN/DOTn Class 1 Explosives. See Section 307.2. 

Division 1.1. See Section 307.2. 

Division 1.2. See Section 307.2. 

Division 1.3. See Section 307.2. 

Division 1.4. See Section 307.2. 

Division 1.5. See Section 307.2. 

Division 1.6. See Section 307.2. 

EXTERIOR INSULATION AND FINISH SYSTEM (EIFS). I 
See Section 1402.1. 

EXTERIOR INSULATION AND FINISH SYSTEM 
(EIFS) WITH DRAINAGE. See Section 1402.1. 

EXTERIOR SURFACES. See Section 2502.1. 

EXTERIOR WALL. See Section 1402.1. 

EXTERIOR WALL COVERING. See Section 1402.1. 

EXTERIOR WALL ENVELOPE. See Section 1402.1 . 

F RATING. See Section 702.1. 

FABRIC PARTITION. See Section 1602.1. 

FABRICATED ITEM. See Section 1702.1. 

[F] FABRICATION AREA. See Section 415.2. 

FACILITY. See Section 1102.1. 

FACTORED LOAD. See Section 1602.1. 

FIBER CEMENT SIDING. See Section 1402.1. 

FIBER REINFORCED POLYMER. See Section 2602.1. 

Fiberglass Reinforced Polymer. See Section 2602.1. 

FIBERBOARD. See Section 2302.1. 

FIRE ALARM BOX, MANUAL. See Section 902.1. 

[F] FIRE ALARM CONTROL UNIT. See Section 902.1. 



i 



14 



2009 INTERNATIONAL BUILDING CODE® 



DEFINITIONS 



[F] FIRE ALARM SIGNAL. See Section 902.1. 

\F] FIRE ALARM SYSTEM. See Section 902.1. 

FIRE AREA. See Section 902.1. 

FIRE BARRIER. See Section 702.1. 

[F] FIRE COMMAND CENTER. See Section 902.1. 

FIRE DAMPER. See Section 702.1. 

\F] FIRE DETECTOR, AUTOMATIC. See Section 902.1 . 

FIRE DOOR. See Section 702.1. 

FIRE DOOR ASSEMBLY. See Section 702.1. 

FIRE EXIT HARDWARE. See Section 1002.1. 

[F] FIRE LANE. A road or other passageway developed to 
allow the passage of fire apparatus. A fire laneis not necessar- 
ily intended for vehicular traffic other than fire apparatus . 

FIRE PARTITION. See Section 702.1. 

FIRE PROTECTION RATING. See Section 702.1. 

\F] FIRE PROTECTION SYSTEM. See Section 902.1. 

FIRE RESISTANCE. See Section 702.1. 

FIRE-RESISTANCE RATING. See Section 702.1. 

FIRE-RESISTANT JOINT SYSTEM. See Section 702.1. 

[F] FIRE SAFETY FUNCTIONS. See Section 902.1. 

FIRE SEPARATION DISTANCE. See Section 702.1. 

FIRE WALL. See Section 702.1. 

FIRE WINDOW ASSEMBLY. See Section 702.1. 

FIREBLOCKING. See Section 702.1. 

FIREPLACE. See Section 2102.1. 

FIREPLACE THROAT. See Section 2102.1. 

\F] FIREWORKS. See Section 307.2. 

Fireworks, 1.3G. See Section 307.2. 

Fireworks, 1.4G. See Section 307.2. 
I FIXED BASE OPERATOR (FBO). See Section 412.2. 
FLAME SPREAD. See Section 802.1. 
FLAME SPREAD INDEX. See Section 802.1. 
[F] FLAMMABLE GAS. See Section 307.2. 
[F] FLAMMABLE LIQUEFIED GAS. See Section 307.2. 
\F] FLAMMABLE LIQUID. See Section 307.2. 

Class IA. See Section 307.2. 

Class IB. See Section 307.2. 

Class IC. See Section 307.2. 
[F] FLAMMABLE MATERIAL. See Section 307.2. 
\F] FLAMMABLE SOLID. See Section 307.2. 
[F] FLAMMABLE VAPORS ORFUMES. See Section 415.2. 
• \F] FLASH POINT. See Section 307.2. 
I FLIGHT. See Section 1002.1. 

FLOOD OR FLOODING. See Section 1612.2. 



FLOOD DAMAGE-RESISTANT MATERIALS. See Sec- 
tion 1612.2. 

FLOOD HAZARD AREA. See Section 1612.2. 

FLOOD HAZARD AREA SUBJECT TO HIGH- VELOC- 
ITY WAVE ACTION. See Section 1612.2. 

FLOOD INSURANCE RATE MAP (FIRM). See Section 
1612.2. 

FLOOD INSURANCE STUDY. See Section 1612.2. 

FLOODWAY. See Section 1612.2. 

FLOOR AREA, GROSS. See Section 1002.1. 

FLOOR AREA, NET. See Section 1002.1. 

FLOOR FIRE DOOR ASSEMBLY. See Section 702.1. 

FLY GALLERY. See Section 410.2. 

[F] FOAM-EXTINGUISHING SYSTEMS. See Section 
902.1. 

FOAM PLASTIC INSULATION. See Section 2602.1. 

FOLDING AND TELESCOPIC SEATING. See Section 
1002.1. 

FOOD COURT. See Section 402.2. 

FOUNDATION PIER. See Section 2102.1. 

FRAME STRUCTURE. See Section 1614.2. 

\F] GAS CABINET. See Section 415.2. 

[F] GAS ROOM. See Section 415.2. 

[F] GASEOUS HYDROGEN SYSTEM. See Section 421.2. 

GLASS FIBERBOARD. See Section 721.1.1. 

GLUED BUILT-UP MEMBER. See Section 2302.1. 

GRADE FLOOR OPENING. A window or other opening 
located such that the sill height of the opening is not more than 
44 inches (1118 mm) above or below the finished ground level 
adjacent to the opening. 

GRADE (LUMBER). See Section 2302.1. 

GRADE PLANE. See Section 502.1. 

GRANDSTAND. See Section 1002.1. 

GRIDIRON. See Section 410.2. 

GROSS LEASABLE AREA. See Section 402.2. 

GROUTED MASONRY. See Section 2102.1. 

Grouted hollow-unit masonry. See Section 2102.1. 

Grouted multiwythe masonry. See Section 2102.1. 

GUARD. See Section 1002.1. 

GYPSUM BOARD. See Section 2502.1. 

GYPSUM PLASTER. See Section 2502.1. 

GYPSUM VENEER PLASTER. See Section 2502.1 . 

HABITABLE SPACE. A space in a building for living, sleep- 
ing, eating or cooking. Bathrooms, toilet rooms, closets, halls, 
storage or utility spaces and similar areas are not considered 
habitable spaces. 



2009 INTERNATIONAL BUILDING CODE® 



15 



DEFINITIONS 



[F] HALOGENATED EXTINGUISHING SYSTEMS. See 
Section 902.1. 

[F] HANDLING. See Section 307.2. 

HANDRAIL. See Section 1002.1. 

HARDBOARD. See Section 2302.1. 

[FT HAZARDOUS MATERIALS. See Section 307.2. 

[F] HAZARDOUS PRODUCTION MATERIAL (HPM). 
See Section 415.2. 

HEAD JOINT. See Section 2102.1. 

[F] HEALTH HAZARD. See Section 307.2. 

HEIGHT, BUILDING. See Section 502.1. 

HEIGHT, WALLS. See Section 2102.1. 

HELICAL PILE. See Section 1802.1. 

HELIPORT. See Section 412.2. 

HELISTOP. See Section 412.2. 

HIGH-RISE BUILDING. A building with an occupied floor 
located more than 75 feet (22 860 mm) above the lowest level 
of fire department vehicle access. 

[F] HIGHLY TOXIC. See Section 307.2. 

HISTORIC BUILDINGS. Buildings that are listed in or eligi- 
ble for listing in the National Register of Historic Places, or 
designated as historic under an appropriate state or local law 
(see Sections 3409 and 3411.9). 

HORIZONTAL ASSEMBLY. See Section 702.1. 

I HOSPITALS AND MENTAL HOSPITALS. See Section 
308.3.1. 

I HOUSING UNIT. See Section 408.1.1. 

\F] HPM FLAMMABLE LIQUID. See Section 415.2. 

[F] HPM ROOM. See Section 415.2. 

HURRICANE-PRONE REGIONS. See Section 1609.2. 

\F] HYDROGEN CUTOFF ROOM. See Section 421.2. 

[F] IMMEDIATELY DANGEROUS TO LIFE AND 
HEALTH (IDLH). See Section 415.2. 

IMPACT LOAD. See Section 1602.1. 

[F] INCOMPATIBLE MATERIALS. See Section 307.2. 

[F] INERT GAS. See Section 307.2. 

[F] INITIATING DEVICE. See Section 902.1. 

INSPECTION CERTIFICATE. See Section 1702.1. 

INTENDED TO BE OCCUPIED AS A RESIDENCE. See 

Section 1102.1. 

INTERIOR FINISH. See Section 802.1. 

INTERIOR FLOOR FINISH. See Section 802.1. 

[F] INTERIOR FLOOR- WALL BASE. See Section 802.1. 

INTERIOR SURFACES. See Section 2502.1. 

INTERIOR WALL AND CEILING FINISH. See Section 
802.1. 



INTERLAYMENT. See Section 1502.1. 

INTUMESCENT FIRE-RESISTANT COATINGS. See 

Section 1702.1. 

JOINT. See Section 702.1. 

JURISDICTION. The governmental unit that has adopted 
this code under due legislative authority. 

LABEL. An identification applied on a product by the manu- 
facturer that contains the name of the manufacturer, the func- 
tion and performance characteristics of the product or material, 
and the name and identification of an approved agency and that 
indicates that the representative sample of the product or mate- 
rial has been tested and evaluated by an approved agency (see 
Section 1703.5 and "Inspection certificate," "Manufacturer's 
designation" and "Mark"). 

LABELED. Equipment, materials or products to which has 
been affixed a label, seal, symbol or other identifying mark of a 
nationally recognized testing laboratory, inspection agency or 
other organization concerned with product evaluation that 
maintains periodic inspection of the production of the 
above-labeled items and whose labeling indicates either that 
the equipment, material or product meets identified standards 
or has been tested and found suitable for a specified purpose. 

LIGHT-DIFFUSING SYSTEM. See Section 2602.1. 

LIGHT-FRAME CONSTRUCTION. A type of construction 
whose vertical and horizontal structural elements are primarily 
formed by a system of repetitive wood or cold-formed steel 
framing members. 

LIGHT-TRANSMITTING PLASTIC ROOF PANELS. 

See Section 2602.1. 

LIGHT-TRANSMITTING PLASTIC WALL PANELS. 

See Section 2602.1. 

LIMIT STATE. See Section 1602.1. 

[F] LIQUID. See Section 415.2. 

[F] LIQUID STORAGE ROOM. See Section 415.2. 

[F] LIQUID USE, DISPENSING AND MIXING ROOM. 

See Section 415.2. 

LISTED. Equipment, materials, products or services included 
in a list published by an organization acceptable to the code 
official and concerned with evaluation of products or services 
that maintains periodic inspection of production of listed 
equipment or materials or periodic evaluation of services and 
whose listing states either that the equipment, material, product 
or service meets identified standards or has been tested and 
found suitable for a specified purpose. 

LIVE LOADS. See Section 1602.1. 

LIVE LOADS (ROOF). See Section 1602.1. 

LOAD AND RESISTANCE FACTOR DESIGN (LRFD). 

See Section 1602.1. 

LOAD EFFECTS. See Section 1602.1. 

LOAD FACTOR. See Section 1602.1. 

LOADS. See Section 1602.1. 

LOT. A portion or parcel of land considered as a unit. 



I 



16 



2009 INTERNATIONAL BUILDING CODE® 



DEFINITIONS 



LOT LINE. A line dividing one lot from another, or from a 
street or any public place. 

[F] LOWER FLAMMABLE LIMIT (LFL). See Section 
415.2. 

LOWEST FLOOR. See Section 1612.2. 

MAIN WINDFORCE-RESISTING SYSTEM. See Section 
1702.1. 

[F] MANUAL FIRE ALARM BOX. See Section 902.1 . 

MANUFACTURERS DESIGNATION. An identification 
applied on a product by the manufacturer indicating that a 
product or material complies with a specified standard or set of 
rules (see also "Inspection certificate," "Label' and" Mark"). 

MARK. An identification applied on a product by the manu- 
facturer indicating the name of the manufacturer and the func- 
tion of a product or material (see also "Inspection certificate," 
"Label' and "Manufacturer's designation"). 

MARQUEE. A permanent roofed structure attached to and 
supported by the building and that projects into the public 
right-of-way. 

MASONRY. See Section 2102.1. 

Ashlar masonry. See Section 2102.1. 

Coursed ashlar. See Section 2102.1. 

Glass unit masonry. See Section 2102.1. 

Plain masonry. See Section 2102.1. 

Random ashlar. See Section 2102.1. 

Reinforced masonry. See Section 2102.1. 

Solid masonry. See Section 2102.1. 

Unreinforced (plain) masonry. See Section 2102.1. 
MASONRY UNIT. See Section 2102.1. 

Clay. See Section 2102.1. 

Concrete. See Section 2102.1. 

Hollow. See Section 2102.1. 

Solid. See Section 2102.1. 

MASTIC FIRE-RESISTANT COATINGS. See Section 
1702.1. 

MAXIMUM CONSIDERED EARTHQUAKE GROUND 
MOTION. See Section 1613.2. 

MEANS OF EGRESS. See Section 1002.1. 

MECHANICAL-ACCESS OPEN PARKING GARAGES. 

See Section 406.3.2. 

MECHANICAL EQUIPMENT SCREEN. See Section 
1502.1. 

MECHANICAL SYSTEMS. See Section 1613.2. 

MEMBRANE-COVERED CABLE STRUCTURE. See 

Section 3102.2. 

MEMBRANE-COVERED FRAME STRUCTURE. See 

Section 3102.2. 

MEMBRANE PENETRATION. See Section 702.1. 



MEMBRANE-PENETRATION FIRESTOP. See Section 
702.1. 

MENTAL HOSPITALS. See Section 308.3.1. I 

MERCHANDISE PAD. See Section 1002.1. 

METAL COMPOSITE MATERIAL (MCM). See Section 
1402.1. 

METAL COMPOSITE MATERIAL (MCM) SYSTEM. 

See Section 1402.1. 

METAL ROOF PANEL. See Section 1502.1. 

METAL ROOF SHINGLE. See Section 1502.1. 

MEZZANINE. See Section 502.1. 

MICROPILE. See Section 1802.1. 

MINERAL BOARD. See Section 721.1 .1. 

MINERAL FIBER. See Section 702.1 . 

MINERAL WOOL. See Section 702.1. 

MODIFIED BITUMEN ROOF COVERING. See Section 
1502.1. 

MORTAR. See Section 2102.1. 

MORTAR, SURFACE-BONDING. See Section 2102.1. 

MULTILEVEL ASSEMBLY SEATING. See Section 
1102.1. 

[F] MULTIPLE-STATION ALARM DEVICE. See Section 
902.1. 

[F] MULTIPLE-STATION SMOKE ALARM. See Section 
902.1. 

MULTISTORY UNITS. See Section 1102.1. 

NAILING, BOUNDARY. See Section 2302.1. 

NAILING, EDGE. See Section 2302.1. 

NAILING, FIELD. See Section 2302.1. 

NATURALLY DURABLE WOOD. See Section 2302.1. 

Decay resistant. See Section 2302.1. 

Termite resistant. See Section 2302.1. 
NOMINAL LOADS. See Section 1602.1. 
NOMINAL SIZE (LUMBER). See Section 2302.1. 

NONCOMBUSTIBLE MEMBRANE STRUCTURE. See 

Section 3102.2. 

[F] NORMAL TEMPERATURE AND PRESSURE 

(NTP). See Section 415.2. 

NOSING. See Section 1002.1. 

NOTIFICATION ZONE. See Section 902 . 1. I 

[F] NUISANCE ALARM. See Section 902.1. 

NURSING HOMES. See Section 308.3 .1. I 

OCCUPANCY CATEGORY. See Section 1602.1. 

OCCUPANT LOAD. See Section 1002.1. 

OCCUPIABLE SPACE. A room or enclosed space designed 
for human occupancy in which individuals congregate for 



2009 INTERNATIONAL BUILDING CODE® 



17 



DEFINITIONS 



amusement, educational or similar purposes or in which occu- 
pants are engaged at labor, and which is equipped with means 
of egress and light and ventilation facilities meeting the 
requirements of this code. 

OPEN PARKING GARAGE. See Section 406.3.2. 

\F] OPEN SYSTEM. See Section 307.2. 

[F] OPERATING BUILDING. See Section 307.2. 

ORDINARY PRECAST STRUCTURAL WALL. See Sec- 
tion 1908.1.1. 

ORDINARY REINFORCED CONCRETE STRUC- 
TURAL WALL. See Section 1908.1.1. 

ORDINARY STRUCTURAL PLAIN CONCRETE 
WALL. See Section 1908.1.1. 

DP] ORGANIC PEROXIDE. See Section 307.2. 

Class! See Section 307.2. 

Class II. See Section 307.2. 

Class III. See Section 307.2. 

Class IV. See Section 307.2. 

Class V. See Section 307.2. 

Unclassified detonable. See Section 307.2. 

ORTHOGONAL. See Section 1613.2. 

OTHER STRUCTURES. See Section 1602.1. 

OWNER. Any person, agent, firm or corporation having a 
legal or equitable interest in the property. 

\F] OXIDIZER. See Section 307.2. 

Class 4. See Section 307.2. 

Class 3. See Section 307.2. 

Class 2. See Section 307.2. 

Class 1. See Section 307.2. 

[F] OXIDIZING GAS. See Section 307.2. 

PANEL (PART OF A STRUCTURE). See Section 1602.1. 

PANIC HARDWARE. See Section 1002.1. 

PARTICLEBOARD. See Section 2302.1. 

PENETRATION FIRESTOP. See Section 702.1. 

PENTHOUSE. See Section 1502.1. 

PERMIT. An official document or certificate issued by the 
authority havingjurisdiction which authorizes performance of 
a specified activity. 

PERSON. An individual, heirs, executors, administrators or 
assigns, and also includes a firm, partnership or corporation, its 
or their successors or assigns, or the agent of any of the afore- 
said. 

PERSONAL CARE SERVICE. See Section 310.2. 

I PHOTOLUMINESCENT. See Section 1002.1. 

[F] PHYSICAL HAZARD. See Section 307.2. 

[F] PHYSIOLOGICAL WARNING THRESHOLD 
LEVEL. See Section 415.2. 



PINRAIL. See Section 410.2. 

PLASTIC, APPROVED. See Section 2602.1. 

PLASTIC GLAZING. See Section 2602.1. 

PLATFORM. See Section 410.2. 

POSITIVE ROOF DRAINAGE. See Section 1502.1. 

PREFABRICATED WOOD I- JOIST. See Section 2302.1. 

PRESTRESSED MASONRY. See Section 2102.1. 

PRIMARY FUNCTION. See Section 3402.1. 

PRIMARY STRUCTURAL FRAME. The primary struc- 
tural frame shall include all of the following structural mem- 
bers: 

1. The columns; 

2. Structural members having direct connections to the col- 
umns, including girders, beams, trusses and spandrels; 

3. Members of the floor construction and roof construction 
having direct connections to the columns; and 

4. Bracing members that are essential to the vertical stabil- 
ity of the primary structural frame under gravity loading 
shall be considered part of the primary structural frame 
whether or not the bracing member carries gravity loads. 

PRISM. See Section 2102.1. 

PROSCENIUM WALL. See Section 410.2. 

PUBLIC ENTRANCE. See Section 1102.1. 

PUBLIC-USE AREAS. See Section 1102.1. 

PUBLIC WAY. See Section 1002.1. 

[F] PYROPHORIC. See Section 307.2. 

[F] PYROTECHNIC COMPOSITION. See Section 307.2. 

RAMP. See Section 1002.1. 

RAMP-ACCESS OPEN PARKING GARAGES. See Sec- 
tion 406.3.2. 

[F] RECORD DRAWINGS. See Section 902.1. 

REFLECTIVE PLASTIC CORE FOIL INSULATION. 

An insulation material packaged in rolls, that is less than 0.5 
inches thick, with at least one exterior low emittance surface 
(0.1 or less) and a core material containing voids or cells. 

REGISTERED DESIGN PROFESSIONAL. An individual 
who is registered or licensed to practice their respective design 
profession as defined by the statutory requirements of the pro- 
fessional registration laws of the state or jurisdiction in which 
the project is to be constructed. 

REGISTERED DESIGN PROFESSIONAL IN RESPON- 
SIBLE CHARGE. A registered design professional engaged 
by the owner to review and coordinate certain aspects of the 
project, as determined by the building official, for compatibil- 
ity with the design of the building or structure, including 
submittal documents prepared by others, deferred submittal 
documents and phased submittal documents. 

RELIGIOUS WORSHIP, PLACE OF. A building or portion 
thereof intended for the performance of religious services. 



I 



2009 INTERNATIONAL BUILDING CODE® 



DEFINITIONS 



REPAIR. The reconstruction or renewal of any part of an exist- 
ing building for the purpose of its maintenance. 

REROOFING. See Section 1502.1. 

RESIDENTIAL AIRCRAFT HANGAR. See Section 412.2. 

RESIDENTIAL CARE/ASSISTED LIVING FACILI- 
TIES. See Section 310.2. 

RESISTANCE FACTOR. See Section 1602.1. 

RESTRICTED ENTRANCE. See Section 1102.1. 

RETRACTABLE AWNING. See Section 3105.2. 

ROOF ASSEMBLY. See Section 1502.1. 

ROOF COVERING. See Section 1502.1. 

ROOF COVERING SYSTEM. See Section 1502.1. 

ROOF DECK. See Section 1502.1. 

ROOF RECOVER. See Section 1502.1. 

ROOF REPAIR. See Section 1502.1. 

ROOF REPLACEMENT. See Section 1502.1. 

ROOF VENTILATION. See Section 1502.1. 

ROOFTOP STRUCTURE. See Section 1502.1. 

RUBBLE MASONRY. See Section 2102.1. 

Coursed rubble. See Section 2102.1. 

Random rubble. See Section 2102.1. 

Rough or ordinary rubble. See Section 2102.1. 

RUNNING BOND. See Section 2102.1. 

I SALLYPORT. See Section 408.1.1. 

SCISSOR STAIR. See Section 1002.1. 

SCUPPER. See Section 1502.1. 

SECONDARY MEMBERS. The following structural mem- 
bers shall be considered secondary members and not part of the 
primary structural frame: 

1. Structural members not having direct connections to the 
columns; 

2. Members of the floor construction not having direct con- 
nections to the columns; and 

3. Bracing members other than those that are part of the pri- 
mary structural frame. 

SEISMIC DESIGN CATEGORY. See Section 1613.2. 

SEISMIC-FORCE-RESISTING SYSTEM. See Section 
1613.2. 

SELF-CLOSING. See Section 702.1. 

I SELF-LUMINOUS. See Section 1002.1. 

SELF-SERVICE STORAGE FACILITY. See Section 
1102.1. 

[F] SERVICE CORRIDOR. See Section 415.2. 

SERVICE ENTRANCE. See Section 1102.1. 

SHAFT. See Section 702.1. 

SHAFT ENCLOSURE. See Section 702.1. 



SHALLOW FOUNDATION. See Section 1802.1. I 

SHEAR WALL. See Sections 2102.1 and 2302.1. 

Detailed plain masonry shear wall. See Section 2102.1. 

Intermediate prestressed masonry shear wall. See Sec- 
tion 2102.1. 

Intermediate reinforced masonry shear wall. See Section 
2102.1. 

Ordinary plain masonry shear wall. See Section 2102.1. 

Ordinary plain prestressed masonry shear wall. See Sec- 
tion 2102.1. 

Ordinary reinforced masonry shear wall. See Section 
2102.1. 

Perforated shear wall. See Section 2302.1. 

Perforated shear wall segment. See Section 2302.1. 

Special prestressed masonry shear wall. See Section 
2102.1. 

Special reinforced masonry shear wall. See Section 
2102.1. 

SHELL. See Section 2102.1. 

SINGLE-PLY MEMBRANE. See Section 1502.1. 

[F] SINGLE-STATION SMOKE ALARM. See Section 
902.1. 

SITE. See Section 1102.1. 

SITE CLASS. See Section 1613.2. 

SITE COEFFICIENTS. See Section 1613.2. - 

SITE-FABRICATED STRETCH SYSTEM. See Section I 
802.1. 

SKYLIGHT, UNIT. A factory-assembled, glazed fenestration 
unit, containing one panel of glazing material that allows for 
natural lighting through an opening in the roof assembly while 
preserving the weather-resistant barrier of the roof. 

SKYLIGHTS AND SLOPED GLAZING. Glass or other 
transparent or translucent glazing material installed at a 
slope of 15 degrees (0.26 rad) or more from vertical. Glazing 
material in skylights, including unit skylights, solariums, 
sunrooms, roofs and sloped walls, are included in this defini- 
tion. 

SLEEPING UNIT. A room or space in which people sleep, 
which can also include permanent provisions for living, eating, 
and either sanitation or kitchen facilities but not both. Such 
rooms and spaces that are also part of a dwelling unit are not 
sleeping units. 

[F] SMOKE ALARM. See Section 902.1. 

SMOKE BARRIER. See Section 702.1. 

SMOKE COMPARTMENT. See Section 702.1. 

SMOKE DAMPER. See Section 702.1. 

[FT SMOKE DETECTOR. See Section 902.1. 

SMOKE-DEVELOPED INDEX. See Section 802.1. 



2009 INTERNATIONAL BUILDING CODE® 



19 



DEFINITIONS 



SMOKE-PROTECTED ASSEMBLY SEATING. See Sec- 
tion 1002.1. 

SMOKEPROOF ENCLOSURE. See Section 902.1. 

\F] SOLID. See Section 415.2. 

SPECIAL AMUSEMENT BUILDING. See Section 411.2. 

SPECIAL FLOOD HAZARD AREA. See Section 1612.2. 

SPECIAL INSPECTION. See Section 1702.1. 

SPECIAL INSPECTION, CONTINUOUS. See Section 
1702.1. 

SPECIAL INSPECTION, PERIODIC. See Section 1702.1. 

I SPECIAL STRUCTURAL WALL. See Section 1908.1.1. 

SPECIFIED. See Section 2102.1. 

SPECIFIED COMPRESSIVE STRENGTH OF 
MASONRY (f'J. See Section 2102.1. 

SPLICE. See Section 702.1. 

SPRAYED FIRE-RESISTANT MATERIALS. See Section 
1702.1. 

STACK BOND. See Section 2102.1. 

STAGE. See Section 410.2. 

STAIR. See Section 1002.1. 

STAIRWAY. See Section 1002.1. 

STAIRWAY, EXTERIOR. See Section 1002.1. 

STAIRWAY, INTERIOR. See Section 1002.1. 

STAIRWAY, SPIRAL. See Section 1002.1. 

[F] STANDPIPE SYSTEM, CLASSES OF. See Section 
902.1. 

Class I system. See Section 902.1 . 

Class II system. See Section 902.1. 

Class III system. See Section 902.1. 
\F] STANDPIPE, TYPES OF. See Section 902.1. 

Automatic dry. See Section 902.1. 

Automatic wet. See Section 902.1 . 

Manual dry. See Section 902.1. 

Manual wet. See Section 902.1. 

Semiautomatic dry. See Section 902.1. 

START OF CONSTRUCTION. See Section 1612.2. 

STEEL CONSTRUCTION, COLD-FORMED. See Section 
2202.1. 

STEEL JOIST. See Section 2202.1. 

STEEL MEMBER, STRUCTURAL. See Section 2202.1. 

STEEP SLOPE. A roof slope greater than two units vertical in 
12 units horizontal (17 -percent slope) . 

STONE MASONRY. See Section 2102.1. 

Ashlar stone masonry. See Section 2102.1. 

Rubble stone masonry. See Section 2102.1. 



[Fl STORAGE, HAZARDOUS MATERIALS. See Section 
415.2. 

STORM SHELTER. See Section 423.2. 

Community storm shelter. See Section 423.2. 

Residential storm shelter. See Section 423.2. 

STORY. That portion of a building included between the upper 
surface of a floor and the upper surface of the floor or roof next 
above (also see "Basement," "Mezzanine" and Section 502.1). 
It is measured as the vertical distance from top to top of two 
successive tiers of beams or finished floor surfaces and, for the 
topmost story, from the top of the floor finish to the top of the 
ceiling joists or, where there is not a ceiling, to the top of the 
roof rafters. 

STORY ABOVE GRADE PLANE. Any story having its fin- I 
ished floor surface entirely above grade plane, or in which the 
finished surface of the floor next above is: 

1. More than 6 feet (1829 mm) above grade plane; or 

2. More than 12 feet (3658 mm) above the finished ground 
level at any point. 

STRENGTH. See Section 2102.1. 

Design strength. See Section 2102.1. 

Nominal strength. See Sections 1602.1 and 2102.1. 

Required strength. See Sections 1602.1 and 2102.1. 

STRENGTH DESIGN. See Section 1602.1. 

STRUCTURAL COMPOSITE LUMBER. See Section 
2302.1. 

Laminated veneer lumber (LVL). See Section 2302.1. 

Parallel strand lumber (PSL). See Section 2302.1. 

STRUCTURAL GLUED-LAMINATED TIMBER. See 

Section 2302.1. 

STRUCTURAL OBSERVATION. See Section 1702.1. 

STRUCTURE. That which is built or constructed. 

SUBDIAPHRAGM. See Section 2302.1. 

SUBSTANTIAL DAMAGE. See Section 1612.2. 

SUBSTANTIAL IMPROVEMENT. See Section 1612.2. 

SUBSTANTIAL STRUCTURAL DAMAGE. See Section 
3402.1. 

SUITE. See Section 1002.1. 

SUNROOM. See Section 1202.1. 

[F] SUPERVISING STATION. See Section 902.1. 

[F] SUPERVISORY SERVICE. See Section 902.1 . 

[F] SUPERVISORY SIGNAL. See Section 902.1. 

[F] SUPERVISORY SIGNAL-INITIATING DEVICE. See 
Section 902.1. 

SWIMMING POOLS. See Section 3109.2. 

T RATING. See Section 702.1. 

TECHNICALLY INFEASIBLE. See Section 3402.1. 



20 



2009 INTERNATIONAL BUILDING CODE® 



DEFINITIONS 



TENT. A structure, enclosure or shelter, with or without side- 
walls or drops, constructed of fabric or pliable material sup- 
ported in any manner except by air or the contents it protects. 

THERMAL ISOLATION. See Section 1202.1. 

THERMOPLASTIC MATERIAL. See Section 2602.1. 

THERMOSETTING MATERIAL. See Section 2602.1. 

THIN-BED MORTAR. See Section 2102.1. 

THROUGH PENETRATION. See Section 702.1. 

THROUGH-PENETRATION FIRESTOP SYSTEM. See 

Section 702.1. 

TIE-DOWN (HOLD-DOWN). See Section 2302.1. 

TIE, LATERAL. See Section 2102.1. 

TIE, WALL. See Section 2102.1. 

TILE. See Section 2102.1. 

TILE, STRUCTURAL CLAY. See Section 2102.1. 

[F] TIRES, BULK STORAGE OF. See Section 902.1. 

TOWNHOUSE. A single-family dwelling unit constructed in 
a group of three or more attached units in which each unit 
extends from the foundation to roof and with open space on at 
least two sides. 

[F] TOXIC. See Section 307.2. 

TRANSIENT. See Section 310.2. 

I TRANSIENT AIRCRAFT. See Section 412.2. 

TREATED WOOD. See Section 2302.1. 

IFire-retardant-treated wood. See Section 2302.1. 
Preservative-treated wood. See Section 2302.1. 
TRIM. See Section 802.1. 
[F] TROUBLE SIGNAL. See Section 902.1. 
TYPE A UNIT. See Section 1102.1. 
TYPE B UNIT. See Section 1102.1. 
UNDERLAYMENT. See Section 1502.1. 

[F] UNSTABLE (REACTIVE) MATERIAL. See Section 

307.2. 

Class 4. See Section 307.2. 

Class 3. See Section 307.2. 

Class 2. See Section 307.2. 

Class 1. See Section 307.2. 

[F] USE (MATERIAL). See Section 415.2. 

VAPOR-PERMEABLE MEMBRANE. A material or cover- 
ing having a permeance rating of 5 perms (52.9 xl 0- 10 kg/Pa . s • m 2 ) 
or greater, when tested in accordance with the dessicant method 
using Procedure A of ASTM E 96. A vapor-permeable material 
permits the passage of moisture vapor. 

I VAPOR RETARDER CLASS. A measure of a material or 
assembly's ability to limit the amount of moisture that passes 



through that material or assembly. Vapor retarder class shall be 
defined using the desiccant method of ASTM E 96 as follows: 

Class I: 0.1 perm or less. 

Class II: 0.1 < perm < 1.0 perm. 

Class III: 1.0 < perm < 10 perm. 

VEHICLE BARRIER SYSTEM. See Section 1602.1. 

VEHICULAR GATE. See Section 3110.2. I 

VENEER. See Section 1402.1. 

VENTILATION. The natural or mechanical process of sup- 
plying conditioned or unconditioned air to, or removing such 
air from, any space. 

VINYL SIDING. See Section 1402.1. 

[F] VISIBLE ALARM NOTIFICATION APPLIANCE. 
See Section 902.1. 

WALKWAY, PEDESTRIAN. A walkway used exclusively as 
a pedestrian trafficway. 

WALL. See Section 2102.1. 

Cavity wall. See Section 2102.1. 

Composite wall. See Section 2102.1. 

Dry-stacked, surface-bonded wall. See Section 2102.1. 

Masonry-bonded hollow wall. See Section 2102.1. 

Parapet wall. See Section 2102.1. 

WALL, LOAD-BEARING. Any wall meeting either of the 
following classifications: 

1. Any metal or wood stud wall that supports more than 100 
pounds per linear foot (1459 N/m) of vertical load in 
addition to its own weight. 

2. Any masonry or concrete wall that supports more than 
200 pounds per linear foot (2919 N/m) of vertical load in 
addition to its own weight. 

WALL, NONLOAD-BEARING. Any wall that is not a load- 
bearing wall. 

WALL PIER. See Section 1908.1.1. 

[F] WATER-REACTIVE MATERIAL. See Section 307.2. 

Class 3. See Section 307.2. 

Class 2. See Section 307.2. 

Class 1. See Section 307.2. 

WATER-RESISTIVE BARRIER. See Section 1402.1. 

WEATHER-EXPOSED SURFACES. See Section 2502.1. 

WEB. See Section 2102.1. 

[F] WET-CHEMICAL EXTINGUISHING SYSTEM. See 
Section 902.1. 

WHEELCHAIR SPACE. See Section 1102.1. 

WIND-BORNE DEBRIS REGION. See Section 1609.2. 

WINDER. See Section 1002.1. 

WIRE BACKING. See Section 2502.1. 



2009 INTERNATIONAL BUILDING CODE® 



21 



DEFINITIONS 



[F] WIRELESS PROTECTION SYSTEM. See Section 
902.1. 

WOOD SHEAR PANEL. See Section 2302.1. 

WOOD STRUCTURAL PANEL. See Section 2302.1. 

Composite panels. See Section 2302.1. 

Oriented strand board (OSB). See Section 2302.1. 

Plywood. See Section 2302.1. 

\F] WORKSTATION. See Section 415.2. 

WYTHE. See Section 2102.1. 

YARD. An open space, other than a court, unobstructed from 
the ground to the sky, except where specifically provided by 
this code, on the lot on which a building is situated. 

[F] ZONE. See Section 902.1. 

ZONE, NOTIFICATION. See Section 902.1. 



22 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 3 

USE AND OCCUPANCY CLASSIFICATION 



SECTION 301 
GENERAL 

301.1 Scope. The provisions of this chapter shall control the 
classification of all buildings and structures as to use and occu- 
pancy. 



SECTION 302 
CLASSIFICATION 

302.1 General. Structures or portions of structures shall be 
classified with respect to occupancy in one or more of the 
groups listed below. A room or space that is intended to be 
occupied at different times for different purposes shall comply 
with all of the requirements that are applicable to each of the 
purposes for which the room or space will be occupied. Struc- 
tures with multiple occupancies or uses shall comply with Sec- 
tion 508. Where a structure is proposed for a purpose that is not 
specifically provided for in this code, such structure shall be 
classified in the group that the occupancy most nearly resem- 
bles, according to the fire safety and relative hazard involved. 

1. Assembly (see Section 303): Groups A-I, A-2, A-3, 
A-4 and A-5 

2. Business (see Section 304): Group B 

3. Educational (see Section 305): Group E 

4. Factory and Industrial (see Section 306) : Groups F-l 
and F-2 

5. High Hazard (see Section 307): Groups H-l, H-2, H-3, 
H-4 and H-5 

6. Institutional (see Section 308): Groups 1-1,1-2,1-3 and 
1-4 

7. Mercantile (see Section 309): Group M 

8. Residential (see Section 310): Groups R-l, R-2, R-3 
and R-4 

9. Storage (see Section 311): Groups S-l and S-2 

10. Utility and Miscellaneous (see Section 312): Group U 



SECTION 303 
ASSEMBLY GROUP A 

303.1 Assembly Group A. Assembly Group A occupancy 
includes, among others, the use of a building or structure, or a 
portion thereof, for the gathering of persons for purposes such 
as civic, social or religious functions; recreation, food or drink 
consumption or awaiting transportation. 

Exceptions: 

1. A building or tenant space used for assembly pur- 
poses with an occupant load of less than 50 persons 
shall be classified as a Group B occupancy. 



2. A room or space used for assembly purposes with an 
occupant load of "less than 50 persons and accessory 
to another occupancy shall be classified as a Group B 
occupancy or as part of that occupancy. 

3. A room or space used for assembly purposes that is 
less than 750 square feet (70 m 2 ) in area and accessory 
to another occupancy shall be classified as a Group B 
occupancy or as part of that occupancy. 

4. Assembly areas that are accessory to Group E occu- 
pancies are not considered separate occupancies 
except when applying the assembly occupancy 
requirements of Chapter 11. 

5. Accessory religious educational rooms and religious 
auditoriums with occupant loads of less than 100 are 
not considered separate occupancies. 

Assembly occupancies shall include the following: 

A-I Assembly uses, usually with fixed seating, intended for 
the production and viewing of the performing arts or 
motion pictures including, but not limited to : 

Motion picture theaters 

Symphony and concert halls 

Television and radio studios admitting an audience 

Theaters 

A-2 Assembly uses intended for food and/or drink con- 
sumption including, but not limited to: 

Banquet halls 
Night clubs 
Restaurants 
Taverns and bars 

A-3 Assembly uses intended for worship, recreation or 
amusement and other assembly uses not classified else- 
where in Group A including, but not limited to: 

Amusement arcades 
Art galleries 
Bowling alleys 
Community halls 
Courtrooms 

Dance halls (not including food or drink consump- 
tion) 
Exhibition halls 
Funeral parlors 

Gymnasiums (without spectator seating) 
Indoor swimming pools (without spectator seating) 
Indoor tennis courts (without spectator seating) 
Lecture halls 
Libraries 
Museums 

Places of religious worship 
Pool and billiard parlors 
Waiting areas in transportation terminals 



2009 INTERNATIONAL BUILDING CODE® 



23 



USE AND OCCUPANCY CLASSIFICATION 



A-4 Assembly uses intended for viewing of indoor sporting 
events and activities with spectator seating including, 
but not limited to: 

Arenas 
Skating rinks 
Swimming pools 
Tennis courts 

A-5 Assembly uses intended for participation in or viewing 
outdoor activities including, but not limited to: 

Amusement park structures 

Bleachers 

Grandstands 

Stadiums 



SECTION 304 
BUSINESS GROUP B 

304.1 Business Group B. Business Group B occupancy 
includes, among others, the use of a building or structure, or a 
portion thereof, for office, professional or service-type transac- 
tions, including storage of records and accounts. Business 
occupancies shall include, but not be limited to, the following: 

Airport traffic control towers 

Ambulatory health care facilities 

Animal hospitals, kennels and pounds 

Banks 

Barber and beauty shops 

Car wash 

Civic administration 

Clinic-outpatient 

Dry cleaning and laundries: pick-up and delivery stations 
and self-service 

Educational occupancies for students above the 12th grade 

Electronic data processing 

Laboratories: testing and research 

Motor vehicle showrooms 

Post offices 

Print shops 

Professional services (architects, attorneys, dentists, physi- 
cians, engineers, etc.) 

Radio and television stations 

Telephone exchanges 

Training and skill development not within a school or aca- 
demic program 

304.1.1 Definitions. The following words and terms shall, 
for the purposes of this section and as used elsewhere in this 
code, have the meanings shown herein. 

CLINIC, OUTPATIENT. Buildings or portions thereof 
used to provide medical care on less than a 24-hour basis to 
individuals who are not rendered incapable of self-preserva- 
tion by the services provided. 



SECTION 305 
EDUCATIONAL GROUP E 

305.1 Educational Group E. Educational Group E occupancy 
includes, among others, the use of a building or structure, or a 



portion thereof, by six or more persons at anyone time for 
educational purposes through the 12th grade. Religious educa- 
tional rooms and religious auditoriums, which are accessory to 
places of religious worship in accordance with Section 303.1 
and have occupant loads of less than 100, shall be classified as 
A -3 occupancies. 

305.2 Day care. The use of a building or structure, or portion 
thereof, for educational, supervision ox personal care services 
for more than five children older than 2 V 2 years of age, shall be 
classified as a Group E occupancy. 



SECTION 306 
FACTORY GROUP F 

306.1 Factory Industrial Group F. Factory Industrial Group 
F occupancy includes, among others, the use of a building or 
structure, or a portion thereof, for assembling, disassembling, 
fabricating, finishing, manufacturing, packaging, repair or pro- 
cessing operations that are not classified as a Group H hazard- 
ous or Group S storage occupancy. 

306.2 Factory Industrial F-l Moderate-hazard Occupancy. 
Factory industrial uses which are not classified as Factory 
Industrial F-2 Low Hazard shall be classified as F-l Moderate 
Hazard and shall include, but not be limited to, the following: 

Aircraft (manufacturing, not to include repair) 

Appliances 

Athletic equipment 

Automobiles and other motor vehicles 

Bakeries 

Beverages: over 16-percent alcohol content 

Bicycles 

Boats 

Brooms or brushes 

Business machines 

Cameras and photo equipment 

Canvas or similar fabric 

Carpets and rugs (includes cleaning) 

Clothing 

Construction and agricultural machinery 

Disinfectants 

Dry cleaning and dyeing 

Electric generation plants 

Electronics 

Engines (including rebuilding) 

Food processing 

Furniture 

Hemp products 

Jute products 

Laundries 

Leather products 

Machinery 

Metals 

Millwork (sash and door) 

Motion pictures and television filming (without spectators) 

Musical instruments 

Optical goods 

Paper mills or products 

Photographic film 



24 



2009 INTERNATIONAL BUILDING CODE® 



USE AND OCCUPANCY CLASSIFICATION 



Plastic products 

Printing or publishing 

Recreational vehicles 

Refuse incineration 

Shoes 

Soaps and detergents 

Textiles 

Tobacco 

Trailers 

Upholstering 

Wood; distillation 

Woodworking (cabinet) 

306.3 Factory Industrial F-2 Low-hazard Occupancy. Fac- 
tory industrial uses that involve the fabrication or manufactur- 
ing of noncombustible materials which during finishing, 
packing or processing do not involve a significant fire hazard 
shall be classified as F-2 occupancies and shall include, but not 
be limited to, the following: 

Beverages: up to and including 16-percent alcohol content 

Brick and masonry 

Ceramic products 

Foundries 

Glass products 

Gypsum 

Ice 

Metal products (fabrication and assembly) 



SECTION 307 
HIGH-HAZARD GROUP H 

[F] 307.1 High-hazard Group H. High-hazard Group H occu- 
pancy includes, among others, the use of a building or struc- 
ture, or a portion thereof, that involves the manufacturing, 
processing, generation or storage of materials that constitute a 
physical or health hazard in quantities in excess of those 
allowed in controlareas complying with Section 414, based on 
the maximum allowable quantity limits for control areas set 
forth in Tables 307.1 (1) and 307.1 (2). Hazardous occupancies 
are classified in Groups H-l, H-2, H-3, H-4 and H-5 and shall 
be in accordance with this section, the requirements of Section 
415 and the International Fire Code. Hazardous materials 
stored, or used on top of roofs or canopies shall be classified as 
outdoor storage or use and shall comply with the International 
Fire Code. 

Exceptions: The following shall not be classified as Group 
H, but shall be classified as the occupancy that they most 
nearly resemble. 

1. Buildings and structures occupied for the applica- 
tion of flammable finishes, provided that such build- 



ings or areas conform to the requirements of Section 
416 and the International Fire Code. 

2. Wholesale and retail sales and storage of flammable 
and combustible liquids in mercantile occupancies 
conforming to the International Fire Code. 

3. Closed piping system containing flammable or 
combustible liquids or gases utilized for the opera- 
tion of machinery or equipment. 

4. Cleaning establishments that utilize combustible 
liquid solvents having a flash point of 140°F (60°C) 
or higher in closed systems employing equipment 
listedby an approved testing agency, provided that 
this occupancy is separated from all other areas of 
the building by I-hour fire barriers constructed in 
accordance with Section 707 or I-hour horizontal 
assemblies constructed in accordance with Section 
712, or both. 

5. Cleaning establishments that utilize a liquid solvent 
having a flash point at or above 200°F (93°C). 

6. Liquor stores and distributors without bulk storage. 

7. Refrigeration systems. 

8. The storage or utilization of materials for agricul- 
tural purposes on the premises. 

9. Stationary batteries utilized for facility emergency 
power, uninterrupted power supply or telecommu- 
nication facilities, provided that the batteries are 
provided with safety venting caps and ventilation is 
provided in accordance with the International 
Mechanical Code. 

10. Corrosives shall not include personal or household 
products in their original packaging used in retail 
display or commonly used building materials. 

11. Buildings and structures occupied for aerosol stor- 
age shall be classified as Group S-I, provided that 
such buildings conform to the requirements of the 
International Fire Code. 

12. Display and storage of nonflammable solid and non- 
flammable or noncombustible liquid hazardous 
materials in quantities not exceeding the maximum 
allowable quantity per control area in Group M or S 
occupancies complying with Section 414.2.5. 

13. The storage of black powder, smokeless propellant 
and small arms primers in Groups M and R-3 and 
special industrial explosive devices in Groups B, F, 
M and S, provided such storage conforms to the 
quantity limits and requirements prescribed in the 
International Fire Code. 



2009 INTERNATIONAL BUILDING CODE® 



25 



[F] TABLE 307.1 (1) 
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDaj 


m, n, p 




MATERIAL 


CLASS 


GROUP WHEN 
THE MAXIMUM 
ALLOWABLE 
QUANTITY IS 
EXCEEDED 


STORAGE b 


USE-CLOSED SYSTEMS' 3 


USE-OPEN SYSTEMS' 3 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Gas 

(cubic feet 

at NTP) 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Gas 

(cubic feet 

at NTP) 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Combustible liquid , i 


n 

I1IA 
TTTR 


H-2 or H-3 
H-2 or H-3 

N/A 


N/A 


120d,e 

330d,e 

13,200e,f 


N/A 


N/A 


120 d 

330 d 

13,200 f 


N/A 


N/A 


30 d 

BOd 

3,300 f 


Combustible fiber 


Loose 
Baledo 


H-3 


(100) 
(1,000) 


N/A 


N/A 


(100) 
(1,000) 


N/A 


N/A 


(20) 
(200) 


N/A 


Consumer fireworks 
(Class C, Common) 


1.4G 


H-3 


12Sd,e,i 


N/A 


N/A 


N/A 


N/A 


N/A 


N/A 


N/A 


Cryogenics, flammable 


N/A 


H-2 


N/A 


4S d 


N/A 


N/A 


4S d 


N/A 


N/A 


IOd 


Cryogenics, inert 


N/A 


N/A 


N/A 


N/A 


NL 


N/A 


N/A 


NL 


N/A 


N/A 


Cryogenics, oxidizing 


N/A 


H-3 


N/A 


4S d 


N/A 


N/A 


4S d 


N/A 


N/A 


IOd 


Explosives 


Division 1.1 
Division 1.2 
Division 1.3 
Division 1.4 
Division I.4G 
Division l.S 
Division 1.6 


H-I 
H-I 
H-I or H-2 
H-3 
H-3 
H-I 
H-I 


Ie,g 
Ie,g 
se,g 

soe,g 

12&Ui 

Ie,g 

14e,g 


(De,g 

(De,g 
(s)e,g 
(so)e,g 

N/A 

(De,g 

N/A 


N/A 
N/A 
N/A 
N/A 
N/A 
N/A 
N/A 


0.2Sg 

0.2S § 

Ig 

sog 

N/A 
0.2S g 

N/A 


(0.2S)g 

(0.2S)g 

(l)g 

(S0)g 

N/A 
(0.2S)g 

N/A 


N/A 
N/A 
N/A 
N/A 
N/A 
N/A 
N/A 


0.2Sg 

0.2Sg 

Ig 

N/A 
N/A 
0.2Sg 

N/A 


(0.2S)g 

(0.2S)g 

(l)g 

N/A 

N/A 

(0.2S)g 

N/A 


Flammable gas 


Gaseous 
Liquefied 


H-2 


N/A 


N/A 
(lS0)d,e 


l,000d,e 

N/A 


N/A 


N/A 
(lS0)d,e 


l,000d,e 

N/A 


N/A 


N/A 


Flammable liquid 


IA 
IB and IC 


H-2 
orH-3 


N/A 


304 e 

120d,e 


N/A 


N/A 


30 d 
120 d 


N/A 


N/A 


IOd 
30 d 


Flammable liquid, 
combination (1A, IB, IC) 


N/A 


H-2 
orH-3 


N/A 


120d,e,h 


N/A 


N/A 


120d,h 


N/A 


N/A 


30d,h 


Flammable solid 


N/A 


H-3 


12Sd,e 


N/A 


N/A 


12S d 


N/A 


N/A 


2S d 


N/A 


Inert gas 


Gaseous 
Liquefied 


N/A 
N/A 


N/A 
N/A 


N/A 
N/A 


NL 
NL 


N/A 
N/A 


N/A 
N/A 


NL 
NL 


N/A 
N/A 


N/A 
N/A 


Organic peroxide 


UD 
I 

n 
m 

IV 
V 


H-I 
H-2 
H-3 
H-3 

N/A 
N/A 


le,g 

Sd,e 
S0d,e 
12Sd,e 

NL 
NL 


(l)e,g 

(S)d,e 
(S0)d,e 
(12S)d,e 

NL 
NL 


N/A 
N/A 
N/A 
N/A 
N/A 
N/A 


0.2S g 
Id 

SOd 
12S d 

NL 
NL 


(0.2S)g 

(1) 

(S0)d 
(12S)d 

NL 
NL 


N/A 
N/A 
N/A 
N/A 
N/A 
N/A 


0.2Sg 

Id 

IOd 

2S d 

NL 
NL 


(0.2S)g 
(l)d 
(10)d 

(2S)d 

NL 
NL 


Oxidizer 


4 

3 k 
2 
1 


H-I 

H-2 or H-3 

H-3 

N/A 


Ie,g 

I0d,e 

2S0d,e 

4,000e,f 


(De,g 

(10)d,e 

(2S0)d,e 

(4,000)e,f 


N/A 
N/A 
N/A 
N/A 


0.2S g 

2 d 
2S0 d 
4,000f 


(0.2S)g 

(2)d 
(2S0)d 
(4,000)f 


N/A 
N/A 
N/A 
N/A 


0.2Sg 

2 d 

SOd 
l,000f 


(0.2S)g 
(2)d 
(S0)d 

(l,000)f 



c 
</) 
m 

> 
z 
o 
o 
o 
o 
c 

o 

< 
o 



8 

o 



(continued) 



ho 

o 

& 



-I 
m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 



[F] TABLE 307.1 (1 )-continued 
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARDaJ, m, n, P 



MATERIAL 


CLASS 


GROUP WHEN 
THE MAXIMUM 
ALLOWABLE 
QUANTITY IS 
EXCEEDED 


STORAGE b 


USE-CLOSED SYSTEMS b 


USE-OPEN SYSTEMS b 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Gas 

(cubic feet 

at NTP) 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Gas 

(cubic feet 

at NTP) 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds) 


Oxidizing gas 


Gaseous 
Liquefied 


H-3 


N/A 
N/A 


N/A 
(lSO)d,e 


I,SOOd,e 

N/A 


N/A 
N/A 


N/A 
(lSO)d,e 


I,S00d,e 

N/A 


N/A 
N/A 


N/A 
N/A 


Pyrophoric material 


N/A 


H-2 


4e,g 


(4)e,g 


soe,g 


19 


(l)g 


109 








Unstable (reactive) 


4 

3 
2 
I 


H-I 

H-I or H-2 

H-3 

N/A 


Ie,g 

Sd,e 
S0d,e 

NL 


d)e,g 
(S)d,e 
(S0)d, e 

NL 


109 

S0d,e 
2S0d,e 

NL 


0.2S§ 
Id 
SOd 

NL 


(0.2S)g 
d)d 
(S0)d 

NL 


2e,g 
I0d,e 
2S0d,e 

NL 


0.2S§ 
Id 

IOd 

NL 


(0.2S)g 
d)d 
(IO)d 
NL 


Water reactive 


3 
2 
I 


H-2 
H-3 

N/A 


Sd,e 
S0d,e 

NL 


(S)d,e 
(S0)d,e 

NL 


N/A 
N/A 
N/A 


Sd 
SOd 

NL 


(S)d 
(S0)d 

NL 


N/A 
N/A 
N/A 


Id 

IOd 

NL 


(l)d 
(IO)d 
NL 



For SI: 1 cubic foot = 0.028 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L. 
NL = Not Limited; N/A = Not Applicable; UD = Unclassified Detonable 

a. For use of control areas, see Section 414.2. 

b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. 

c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales 
occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not 
being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. 

d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3. 1 . 1 . Where Note e also applies, the increase for 
both notes shall be applied accumulatively. 

e. Maximum allowable quantities shall be increased 100 percent when stored in approved stomge cabinets, day boxes, gas cabinets or exhausted enclosures or in listed safety cans in accordance with Section 
2703.9.10 of the International Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively. 

f. The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 

g. Permitted only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 
h. Containing not more than the maximum allowable quantity per control area of Class 1A, IB or IC flammable liquids. 

i. The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2 of the International Fire Code. 

j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. 

k. A maximum quantity of 200 pounds of solid or 20 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment. Storage contain- 
ers and the manner of storage shall be approved. 

1 . Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, 
shall be used. 

m. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 2703.1.2 of the International Fire Code. 

n. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2). 

o. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. 

p. The following shall not be included in determining the maximum allowable quantities: 

1. Liquid or gaseous fuel in fuel tanks on vehicles. 

2. Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with this code. 

3. Gaseous fuels in piping systems and fixed appliances regulated by the International Fuel Gas Code. 

4. Liquid fuels in piping systems and fixed appliances regulated by the International Mechanical Code. 



C 
</) 
m 

> 

z 

D 
O 
O 

o 

c 

T3 

> 

Z 

o 
-< 

o 






o 
> 

o 



USE AND OCCUPANCY CLASSIFICATION 



[F] TABLE 307.1(2) 
MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARDS, c, i 



MATERIAL 


STORAGE d 


USE-CLOSED SYSTEMS d 


USE-OPEN SYSTEMS d 


Solid pounds 
(cubic feet) 


Liquid gallons 
(pounds)e, t 


Gas (cubic feet 
at NTP)e 


Solid 
pounds e 


Liquid gallons 
(pounds)e 


Gas (cubic feet 
at NTP)e 


Solid 
pounds e 


Liquid gallons 
(pounds)e 


Corrosive 


5,000 


500 


Gaseous 81 f 

Liquefied 

(150)h 


5,000 


500 


Gaseous 81 f 

Liquefied 

(150)h 


1,000 


100 


Highly toxic 


10 


(!0)h 


Gaseous 20 g 
Liquefied (4)g, h 


10 


(10)i 


Gaseous 20 g 
Liquefied (4)g, h 


3 


(3)i 


Toxic 


500 


(500)h 


Gaseous 81 f 

Liquefied 

(150)f,h 


500 


(500) 1 


Gaseous 81 f 

Liquefied 

(150)f,h 


125 


(125) 



For SI: 1 cubic foot = 0.028 m 3 , 1 pound = 0.454 kg, 1 gallon = 3.785 L. 

a. For use of control areas, see Section 414.2. 

b. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics , containing not more than 50 per- 
cent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are pack- 
aged in individual containers not exceeding 1.3 gallons. 

c. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 
414.2.5(2). 

d. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. 

e. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with 
Section 903.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively. 

f. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the 
International Fire Code. Where Note e also applies, the increase for both notes shall be applied accumulatively. 

g. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures as specified in the International Fire Code. 
h. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. 

i. For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 2703.1.2 of the International Fire Code. 



307.1.1 Hazardous materials. Hazardous materials in any 
quantity shall conform to the requirements of this code, 
including Section 414, and the International Fire Code. 

\F] 307.2 Definitions. The following words and terms shall, 
for the purposes of this section and as used elsewhere in this 
code, have the meanings shown herein. 

AEROSOL. A product that is dispensed from an aerosol con- 
tainer by a propellant. 

Aerosol products shall be classified by means of the calcula- 
tion of their chemical heats of combustion and shall be desig- 
nated Levell, 2 or 3. 

Levell aerosol products. Those with a total chemical heat 
of combustion that is less than or equal to 8,600 British ther- 
mal units per pound (Btu/lb) (20 kJ/g). 

Level 2 aerosol products. Those with a total chemical heat 
ofcombustionthatis greater than 8,600 Btu/lb (20 kJ/g), but 
less than or equal to 13,000 Btu/lb (30 kJ/g). 

Level 3 aerosol products. Those with a total chemical heat 
combustion that is greater than 13,000 Btu/lb (30 kJ/g). 

AEROSOL CONTAINER. A metal can or a glass or plastic 
bottle designed to dispense an aerosol. Metal cans shall be lim- 
ited to a maximum size of 3 3. 8 fluid ounces (1000 ml) . Glass or 
plastic bottles shall be limited to a maximum size of 4 fluid 
ounces (118 ml). 

BALED COTTON. A natural seed fiber wrapped in and 
secured with industry accepted materials, usually consisting of 
burlap, woven polypropylene, polyethylene or cotton or sheet 
polyethylene, and secured with steel, synthetic or wire bands or 



wire; also includes linters (lint removed from the cottonseed) 
and motes (residual materials from the ginning process). 

BALED COTTON, DENSELY PACKED. Cotton made into 
banded bales with a packing density of at least 22 pounds per 
cubic foot (360 kg/m 3 ), and dimensions complying with the fol- 
lowing: a length of 55 inches (1397 ± 20 mm), a width of 21 
inches (533.4 ± 20 mm) and a height of 27. 6 to 35.4 inches (701 
to 899 mm). 

BARRICADE. A structure that consists of a combination of 
walls, floor and roof, which is designed to withstand the rapid 
release of energy in an explosion and which is fully confined, 
partially vented or fully vented; or other effective method of 
shielding from explosive materials by a natural or artificial bar- 
rier. 

Artificial barricade. An artificial mound or revetment a 
minimum thickness of 3 feet (914 mm). 

Natural barricade. Natural features of the ground, such as 
hills, or timber of sufficient density that the surrounding 
exposures that require protection cannot be seen from the 
magazine or building containing explosives when the trees 
are bare of leaves. 

BOILING POINT. The temperature at which the vapor pres- 
sure of a liquid equals the atmospheric pressure of 14.7 pounds 
per square inch (psi) (101 kPa) gage or 760 mm of mercury. 
Where an accurate boiling point is unavailable for the material 
in question, or for mixtures which do not have a constant boil- 
ing point, for the purposes of this classification, the 20-percent 
evaporated point of a distillation performed in accordance with 
ASTM D 86 shall be used as the boiling point of the liquid. 



28 



2009 INTERNATIONAL BUILDING CODE® 



USE AND OCCUPANCY CLASSIFICATION 



CLOSED SYSTEM. The use of a solid or liquid hazardous 
material involving a closed vessel or system that remains 
closed during normal operations where vapors emitted by the 
product are not liberated outside of the vessel or system and the 
product is not exposed to the atmosphere during normal opera- 
tions; and all uses of compressed gases. Examples of closed 
systems for solids and liquids include product conveyed 
through a piping system into a closed vessel, system or piece of 
equipment. 

COMBUSTIBLE DUST. Finely divided solid material that is 
420 microns or less in diameter and which, when dispersed in 
air in the proper proportions, could be ignited by a flame, spark 
or other source of ignition. Combustible dust will pass through 
a U.S. No. 40 standard sieve. 

COMBUSTIBLE FIBERS. Readily ignitable and free-burn- 
ing materials in a fibrous or shredded form, such as cocoa fiber, 
cloth, cotton, excelsior, hay, hemp, henequen, istlejute, kapok, 
oakum, rags, sisal, Spanish moss, straw, tow, wastepaper, cer- 
tain synthetic fibers or other like materials. This definition does 
not include densely packed baled cotton. 

COMBUSTIBLE LIQUID. A liquid having a closed cup 
flash point at or above 100°F (38°C). Combustible liquids shall 
be subdivided as follows: 

Class II. Liquids having a closed cup flash point at or above 
100°F (38°C) and below 140°F (60°C). 

Class I1IA. Liquids having a closed cup flash point at or 
above 140°F (60°C) and below 200°F (93°C). 

Class IIIB. Liquids having a closed cup flash point at or 
above 200°F (93°C). 

The category of combustible liquids does not include com- 
pressed gases or cryogenic fluids. 

COMPRESSED GAS. A material, or mixture of materials, 
that: 

1. Is a gas at 68°F (20°C) or less at 14.7 pounds per square 
inch atmosphere (psia) (101 kPa) of pressure; and 

2. Has a boiling point of 68°F (20°C) or less at 14.7 psia 
(101 kPa) which is either liquefied, nonliquefied or in 
solution, except those gases which have no other health- 
or physical-hazard properties are not considered to be 
compressed until the pressure in the packaging exceeds 
41 psia (282 kPa) at 68°F (20°C). 

The states of a compressed gas are categorized as follows: 

1. Nonliquefied compressed gases are gases, other than 
those in solution, which are in a packaging under the 
charged pressure and are entirely gaseous at a tempera- 
ture of 68°F (20°C). 

2. Liquefied compressed gases are gases that, in a packag- 
ing under the charged pressure, are partially liquid at a 
temperature of 68°F (20°C). 

3. Compressed gases in solution are nonliquefied gases that 
are dissolved in a solvent. 

4. Compressed gas mixtures consist of a mixture of two or 
more compressed gases contained in a packaging, the 



hazard properties of which are represented by the proper- 
ties of the mixture as a whole. 

CONTROL AREA. Spaces within a building where quanti- 
ties of hazardous materials not exceeding the maximum allow- 
able quantities per control area are stored, dispensed, used or 
handled. See also the definition of "Outdoor control area" in 
the International Fire Code. 

CORROSIVE. A chemical that causes visible destruction of, 
or irreversible alterations in, living tissue by chemical action at 
the point of contact. A chemical shall be considered corrosive 
if, when tested on the intact skin of albino rabbits by the method 
described in DOTn 49 CFR, Part 173.137, such a chemical 
destroys or changes irreversibly the structure of the tissue at the 
point of contact following an exposure period of 4 hours. This 
term does not refer to action on inanimate surfaces. 

CRYOGENIC FLUID. A liquid having a boiling point lower 
than -150°F (-101°C) at 14.7 pounds per square inch atmo- 
sphere (psia) (an absolute pressure of 101 kPa). 

DAY BOX. A portable magazine designed to hold explosive 
materials constructed in accordance with the requirements for 
a Type 3 magazine as defined and classified in Chapter 33 of 
the International Fire Code. 

DEFLAGRATION. An exothermic reaction, such as the 
extremely rapid oxidation of a flammable dust or vapor in air, 
in which the reaction progresses through the unburned material 
at a rate less than the velocity of sound. A deflagration can have 
an explosive effect. 

DETONATION. An exothermic reaction characterized by the 
presence of a shock wave in the material which establishes and 
maintains the reaction. The reaction zone progresses through 
the material at a rate greater than the velocity of sound. The 
principal heating mechanism is one of shock compression. 
Detonations have an explosive effect. 

DISPENSING. The pouring or transferring of any material 
from a container, tank or similar vessel, whereby vapors, dusts, 
fumes, mists or gases are liberated to the atmosphere. 

EXPLOSION. An effect produced by the sudden violent 
expansion of gases, which may be accompanied by a shock 
wave or disruption, or both, of enclosing materials or struc- 
tures. An explosion could result from any of the following: 

1. Chemical changes such as rapid oxidation, deflagration 
or detonation, decomposition of molecules and runaway 
polymerization (usually detonations). 

2. Physical changes such as pressure tank ruptures. 

3. Atomic changes (nuclear fission or fusion). 

EXPLOSIVE. A chemical compound, mixture or device, the 
primary or common purpose of which is to function by explo- 
sion. The term includes, but is not limited to, dynamite, black 
powder, pellet powder, initiating explosives, detonators, safety 
fuses, squibs, detonating cord, igniter cord, igniters and display 
fireworks, 1.3G (Class B, Special). 

The term" explosive" includes any material determined to be 
within the scope of USC Title 18: Chapter 40 and also includes 
any material classified as an explosive other than consumer 



2009 INTERNATIONAL BUILDING CODE® 



29 



USE AND OCCUPANCY CLASSIFICATION 



I fireworks, 1.4G (Class C, Common) by the hazardous materi- 
als regulations of DOTn 49 CFR Parts 100-185. 

High explosive. Explosive material, such as dynamite, 
which can be caused to detonate by means of a No. 8 test 
blasting cap when unconfined. 

Low explosive. Explosive material that will burn or defla- 
grate when ignited. It is characterized by a rate of reaction 
that is less than the speed of sound. Examples of low explo- 
sives include, but are not limited to, black powder; safety 
fuse; igniters; igniter cord; fuse lighters; fireworks, 1.3G 
(Class B, Special) and propellants, 1.3C. 

Mass-detonating explosives. Division 1.1, 1.2 and 1.5 
explosives alone or in combination, or loaded into various 
types of ammunition or containers, most of which can be 
expected to explode virtually instantaneously when a small 
portion is subjected to fire, severe concussion, impact, the 
impulse of an initiating agent or the effect of a considerable 
discharge of energy from without. Materials that react in 
this manner represent a mass explosion hazard. Such an 
explosive will normally cause severe structural damage to 
adjacent objects. Explosive propagation could occur imme- 
diately to other items of ammunition and explosives stored 
sufficiently close to and not adequately protected from the 
initially exploding pile with a time interval short enough so 
that two or more quantities must be considered as one for 
quantity-distance purposes. 

UN/DOTn Class 1 explosives. The former classification 
system used by DOTn included the terms "high" and "low" 
explosives as defined herein. The following terms further 
define explosives under the current system applied by 
DOTn for all explosive materials defined as hazard Class 1 
materials. Compatibility group letters are used in concert 
with the division to specify further limitations on each divi- 
sion noted (Le., the letter G identifies the material as a pyro- 
technic substance or article containing a pyrotechnic 
substance and similar materials). 

Division 1.1. Explosives that have a mass explosion haz- 
ard. A mass explosion is one which affects almost the 
entire load instantaneously. 

Division 1.2. Explosives that have a projection hazard 
but not a mass explosion hazard. 

Division 1.3. Explosives that have a fire hazard and 
either a minor blast hazard or a minor projection hazard 
or both, but not a mass explosion hazard. 

Division 1.4. Explosives that pose a minor explosion 
hazard. The explosive effects are largely confined to the 
package and no projection of fragments of appreciable 
size or range is to be expected. An external fire must not 
cause virtually instantaneous explosion of almost the 
entire contents of the package. 

Division 1.5. Very insensitive explosives. This division 
is comprised of substances that have a mass explosion 
hazard, but that are so insensitive there is very little prob- 
ability of initiation or of transition from burning to deto- 
nation under normal conditions of transport. 



Division 1.6. Extremely insensitive articles which do not 
have a mass explosion hazard. This division is comprised 
of articles that contain only extremely insensitive deto- 
nating substances and which demonstrate a negligible 
probability of accidental initiation or propagation. 

FIREWORKS. Any composition or device for the purpose of 
producing a visible or audible effect for entertainment pur- 
poses by combustion, deflagration or detonation that meets the 
definition of 1.4G fireworks or 1.3G fireworks as set forth 
herein. 

Fireworks, 1.3G. (Formerly Class B, Special Fireworks.) 
Large fireworks devices, which are explosive materials, 
intended for use in fireworks displays and designed to pro- 
duce audible or visible effects by combustion, deflagration 
or detonation. Such 1.3G fireworks include, but are not lim- 
ited to, firecrackers containing more than 130 milligrams (2 
grains) of explosive composition, aerial shells containing 
more than 40 grams of pyrotechnic composition, and other 
display pieces which exceed the limits for classification as 
1.4G fireworks. Such 1.3G fireworks are also described as 
fireworks, UN0335 by the DOTn. 

Fireworks, 1.4G. (Formerly Class C, Common Fireworks.) 
Small fireworks devices containing restricted amounts of 
pyrotechnic composition designed primarily to produce vis- 
ible or audible effects by combustion. Such 1.4G fireworks 
which comply with the construction, chemical composition 
and labeling regulations of the DOTn for fireworks, 
UN0336, and the U.S. Consumer Product Safety Commis- 
sion (CPSC) as set forth in CPSC 16 CFR: Parts 1500 and 
1507, are not explosive materials for the purpose of this 
code. 

FLAMMABLE GAS. A material that is a gas at 68°F (20°C) 
or less at 14.7 pounds per square inch atmosphere (psia) (101 
kPa) of pressure [a material that has a boiling point of 68 of 
(20°C) or less at 14.7 psia (101 kPa)] which: 

1. Is ignitable at 14.7 psia (101 kPa) when in a mixture of 13 
percent or less by volume with air; or 

2. Has a flammable range at 14.7 psia (101 kPa) with air of 
at least 12 percent, regardless of the lower limit. 

The limits specified shall be determined at 14.7 psi (101 kPa) 
of pressure and a temperature of 68 °F (20°C) in accordance 
with ASTME 681. 

FLAMMABLE LIQUEFIED GAS. A liquefied compressed 
gas which, under a charged pressure, is partially liquid at a tem- 
perature of 68°F (20°C) and which is flammable. 

FLAMMABLE LIQUID. A liquid having a closed cup flash 
point below 100°F (38°C). Flammable liquids are further cate- 
gorized into a group known as Class I liquids. The Class I cate- 
gory is subdivided as follows: 

Class IA. Liquids having a flash point below 73°F (23°C) 
and a boiling point below 100°F (38°C). 

Class IB. Liquids having a flash point below 73°F (23°C) 
and a boiling point at or above 100°F (38°C). 

Class IC. Liquids having a flash point at or above 73°F 
(23°C) and below 100°F (38°C). 



30 



2009 INTERNATIONAL BUILDING CODE® 



USE AND OCCUPANCY CLASSIFICATION 



The category of flammable liquids does not include com- 
pressed gases or cryogenic fluids. 

FLAMMABLE MATERIAL. A material capable of being 
readily ignited from common sources of heat or at a temperature 
of600°F (316°C) or less. 

FLAMMABLE SOLID. A solid, other than a blasting agent or 
explosive, that is capable of causing fire through friction, 
absorption or moisture, spontaneous chemical change, or 
retained heat from manufacturing or processing, or which has an 
ignition temperature below 212°F (100°C) or which burns so 
vigorously and persistently when ignited as to create a serious 
hazard. A chemical shall be considered a flammable solid as 
determined in accordance with the test method of CPSC 16 
CFR; Part 1500.44, if it ignites and burns with a self- sustained 
flame at a rate greater than 0.1 inch (2.5 mm) per second along its 
major axis. 

FLASH POINT. The minimum temperature in degrees Fahren- 
heit at which a liquid will give off sufficient vapors to form an 
ignitable mixture with air near the surface or in the container, but 
will not sustain combustion. The flash point of a liquid shall be 
determined by appropriate test procedure and apparatus as spec- 
ified in ASTM D 56, ASTM D 93 or ASTM D 3278. 

HANDLING. The deliberate transport by any means to a point 
of storage or use. 

HAZARDOUS MATERIALS. Those chemicals or substances 
that are physical hazards or health hazards as defined and classi- 
fied in this section and the International Fire Code, whether the 
materials are in usable or waste condition. 

HEALTH HAZARD. A classification of a chemical for which 
there is statistically significant evidence that acute or chronic 
health effects are capable of occurring in exposed persons. The 
term "health hazard" includes chemicals that are toxic or highly 
toxic, and corrosive. 

HIGHLY TOXIC. A material which produces a lethal dose or 
lethal concentration that falls within any of the following catego- 
ries: 

1. A chemical that has a median lethal dose (LD S0 ) of 50 mil- 
ligrams or less per kilogram of body weight when admin- 
istered orally to albino rats weighing between 200 and 300 
grams each. 

2. A chemical that has a median lethal dose (LD S0 ) of 200 
milligrams or less per kilogram of body weight when 
administered by continuous contact for 24 hours (or less if 
death occurs within 24 hours) with the bare skin of albino 
rabbits weighing between 2 and 3 kilograms each. 

3. A chemical that has a median lethal concentration (LC S0 ) 
in air of 200 parts per million by volume or less of gas or 
vapor, or 2 milligrams per liter or less of mist, fume or 
dust, when administered by continuous inhalation for 1 
hour (or less if death occurs within 1 hour) to albino rats 
weighing between 200 and 300 grams each. 

Mixtures of these materials with ordinary materials, such as 
water, might not warrant classification as highly toxic. While 
this system is basically simple in application, any hazard evalua- 
tion that is required for the precise categorization of this type of 



material shall be performed by experienced, technically compe- 
tent persons. 

INCOMPATIBLE MATERIALS. Materials that, when 
mixed, have the potential to react in a manner that generates 
heat, fumes, gases or byproducts which are hazardous to life or 
property. 

INERT GAS. A gas that is capable of reacting with other mate- 
rials only under abnormal conditions such as high tempera- 
tures' pressures and similar extrinsic physical forces. Within 
the context of the code, inert gases do not exhibit either physi- 
calor health properties as defined (other than acting as a simple 
asphyxiant) or hazard properties other than those of a com- 
pressed gas. Some of the more common inert gases include 
argon, helium, krypton, neon, nitrogen and xenon. 

OPEN SYSTEM. The use of a solid or liquid hazardous mate- 
rial involving a vessel or system that is continuously open to the 
atmosphere during normal operations and where vapors are 
liberated, or the product is exposed to the atmosphere during 
normal operations. Examples of open systems for solids and 
liquids include dispensing from or into open beakers or con- 
tainers, dip tank and plating tank operations. 

OPERATING BUILDING. A building occupied in conjunc- 
tion with the manufacture, transportation or use of explosive 
materials. Operating buildings are separated from one another 
with the use of intraplant or intraline distances. 

ORGANIC PEROXIDE. An organic compound that contains 
the bivalent -0-0- structure and which may be considered to be 
a structural derivative of hydrogen peroxide where one or both 
of the hydrogen atoms have been replaced by an organic radi- 
cal. Organic peroxides can pose an explosion hazard (detona- 
tion or deflagration) or they can be shock sensitive. They can 
also decompose into various unstable compounds over an 
extended period of time. 

Class I. Those formulations that are capable of deflagration 
but not detonation. 

Class II. Those formulations that burn very rapidly and that 
pose a moderate reactivity hazard. 

Class III. Those formulations that burn rapidly and that 
pose a moderate reactivity hazard. 

Class IV. Those formulations that burn in the same manner 
as ordinary combustibles and that pose a minimal reactivity 
hazard. 

Class V. Those formulations that burn with less intensity 
than ordinary combustibles or do not sustain combustion 
and that pose no reactivity hazard. 

Unclassified detonable. Organic peroxides that are capable 
of detonation. These peroxides pose an extremely high 
explosion hazard through rapid explosive decomposition. 

OXIDIZER. A material that readily yields oxygen or other 
oxidizing gas, or that readily reacts to promote or initiate com- 
bustion of combustible materials and, if heated or contami- 
nated' can result in vigorous self-sustained decomposition. 

Class 4. An oxidizer that can undergo an explosive reaction 
due to contamination or exposure to thermal or physical 
shock and that causes a severe increase in the burning rate of 



2009 INTERNATIONAL BUILDING CODE® 



31 



USE AND OCCUPANCY CLASSIFICATION 



combustible materials with which it comes into contact. 
Additionally, the oxidizer causes a severe increase in the 
burning rate and can cause spontaneous ignition of combus- 
tibles. 

Class 3. An oxidizer that causes a severe increase in the 
burning rate of combustible materials with which it comes 
in contact. 

Class 2. An oxidizer that will cause a moderate increase in 
the burning rate of combustible materials with which it 
comes in contact. 

Class 1. An oxidizer that does not moderately increase the 
burning rate of combustible materials. 

OXIDIZING GAS. A gas that can support and accelerate 
combustion of other materials. 

PHYSICAL HAZARD. A chemical for which there is evi- 
dence that it is a combustible liquid, cryogenic fluid, explosive, 
flammable (solid, liquid or gas), organic peroxide (solid or liq- 
uid) , oxidizer (solid or liquid), oxidizing gas, pyrophoric 
(solid, liquid or gas), unstable (reactive) material (solid, liquid 
or gas) or water-reactive material (solid or liquid). 

PYROPHORIC. A chemical with an autoignition tempera- 
ture in air, at or below a temperature of 130°F (54.4°C). 

PYROTECHNIC COMPOSITION. A chemical mixture 
that produces visible light displays or sounds through a 
self-propagating, heat-releasing chemical reaction which is 
initiated by ignition. 

TOXIC. A chemical falling within any of the following cate- 
gories: 

1. A chemical that has a median lethal dose (LD S0 ) of more 
than 50 milligrams per kilogram, but not more than 500 
milligrams per kilogram of body weight when adminis- 
tered orally to albino rats weighing between 200 and 300 
grams each. 

2. A chemical that has a median lethal dose (LD S0 ) of more 
than 200 milligrams per kilogram, but not more than 
1,000 milligrams per kilogram of body weight when 
administered by continuous contact for 24 hours (or less 
if death occurs within 24 hours) with the bare skin of 
albino rabbits weighing between 2 and 3 kilograms each. 

3. A chemical that has a median lethal concentration (LC S0 ) 
in air of more than 200 parts per million, but not more 
than 2,000 parts per million by volume of gas or vapor, or 
more than 2 milligrams per liter but not more than 20 mil- 
ligrams per liter of mist, fume or dust, when adminis- 
tered by continuous inhalation for 1 hour (or less if death 
occurs within 1 hour) to albino rats weighing between 
200 and 300 grams each. 

UNSTABLE (REACTIVE) MATERIAL. A material, other 
than an explosive, which in the pure state or as commercially 
produced, will vigorously polymerize, decompose, condense 
or become self-reactive and undergo other violent chemical 
changes, including explosion, when exposed to heat, friction or 
shock, or in the absence of an inhibitor, or in the presence of 
contaminants, or in contact with incompatible materials. 
Unstable (reactive) materials are subdivided as follows: 



Class 4. Materials that in themselves are readily capable of 
detonation or explosive decomposition or explosive reac- 
tion at normal temperatures and pressures. This class 
includes materials that are sensitive to mechanical or local- 
ized thermal shock at normal temperatures and pressures. 

Class 3. Materials that in themselves are capable of detona- 
tion or of explosive decomposition or explosive reaction but 
which require a strong initiating source or which must be 
heated under confinement before initiation. This class 
includes materials that are sensitive to thermal or mechani- 
cal shock at elevated temperatures and pressures. 

Class 2. Materials that in themselves are normally unstable 
and readily undergo violent chemical change but do not det- 
onate. This class includes materials that can undergo chemi- 
cal change with rapid release of energy at normal 
temperatures and pressures, and that can undergo violent 
chemical change at elevated temperatures and pressures. 

Class 1. Materials that in themselves are normally stable but 
which can become unstable at elevated temperatures and 
pressure. 

WATER-REACTIVE MATERIAL. A material that 
explodes; violently reacts; produces flammable, toxic or other 
hazardous gases; or evolves enough heat to cause autoignition 
or ignition of combustibles upon exposure to water or mois- 
ture. Water-reactive materials are subdivided as follows: 

Class 3. Materials that react explosively with water without 
requiring heat or confinement. 

Class 2. Materials that react violently with water or have the 
ability to boil water. Materials that produce flammable, 
toxic or other hazardous gases or evolve enough heat to 
cause autoignition or ignition of combustibles upon expo- 
sure to water or moisture. 

Class 1. Materials that react with water with some release of 
energy, but not violently. 

[F] 307.3 High-hazard Group H-l. Buildings and structures 
containing materials that pose a detonation hazard shall be 
classified as Group H-l. Such materials shall include, but not 
be limited to, the following: 

Detonable pyrophoric materials 

Explosives: 

Division 1.1 
Division 1.2 
Division 1.3 

Exception: Materials that are used and maintained in 
a form where either confinement or configuration will 
not elevate the hazard from a mass fire to mass explo- 
sion hazard shall be allowed in H-2 occupancies. 

Division 1.4 

Exception: Articles, including articles packaged for 
shipment, that are not regulated as an explosive under 
Bureau of Alcohol, Tobacco and Firearms regula- 
tions, or unpackaged articles used in process opera- 
tions that do not propagate a detonation or 
deflagration between articles shall be allowed in H-3 
occupancies. 



32 



2009 INTERNATIONAL BUILDING CODE® 



USE AND OCCUPANCY CLASSIFICATION 



Division 1.5 
Division 1.6 

Organic peroxides, unclassified detonable 

Oxidizers, Class 4 

Unstable (reactive) materials, Class 3 detonable and Class 4 

[F] 307.4 High-hazard Group H-2. Buildings and structures 
containing materials that pose a deflagration hazard or a hazard 
from accelerated burning shall be classified as Group H-2. 
Such materials shall include, but not be limited to, the follow- 
ing: 

Class I, II or I1IA flammable or combustible liquids which 
are used or stored in normally open containers or sys- 
tems, or in closed containers or systems pressurized at 
more than 15 psi (103.4 kPa) gage. 

Combustible dusts 

Cryogenic fluids, flammable 

Flammable gases 

Organic peroxides, Class I 

Oxidizers, Class 3, that are used or stored in normally open 
containers or systems, or in closed containers or systems 
pressurized at more than 15 psi (103 kPa) gage 

Pyrophoric liquids, solids and gases, nondetonable 

Unstable (reactive) materials, Class 3, nondetonable 

Water-reactive materials, Class 3 

[F] 307.5 High-hazard Group H-3. Buildings and structures 
containing materials that readily support combustion or that 
pose a physical hazard shall be classified as Group H-3. Such 
materials shall include, but not be limited to, the following: 

Class I, II or I1IA flammable or combustible liquids that 
are used or stored in normally closed containers or 
systems pressurized at 15 pounds per square inch gauge 
(103.4 kPa) or less 

Combustible fibers, other than densely packed baled cotton 

Consumer fireworks, 1.4G (Class C, Common) 

Cryogenic fluids, oxidizing 

Flammable solids 

Organic peroxides, Class II and III 

Oxidizers, Class 2 

Oxidizers, Class 3, that are used or stored in normally 
closed containers or systems pressurized at 15 pounds per 
square inch gauge (103 kPa) or less 

Oxidizing gases 

Unstable (reactive) materials, Class 2 

Water-reactive materials, Class 2 

[F] 307.6 High-hazard Group H-4. Buildings and structures 
which contain materials that are health hazards shall be classi- 
fied as Group H-4. Such materials shall include, but not be lim- 
ited to, the following: 

Corrosives 

Highly toxic materials 

Toxic materials 

[F] 307.7 High-hazard Group H-5 structures. Semiconduc- 
tor fabrication facilities and comparable research and develop- 
ment areas in which hazardous production materials (HPM) 
are used and the aggregate quantity of materials is in excess of 
those listed in Tables 307.1 (1) and 307.1 (2) shall be classified 



as Group H-5. Such facilities and areas shall be designed and 
constructed in accordance with Section 415.8. 

[F] 307.8 Multiple hazards. Buildings and structures containing 
a material or materials representing hazards that are classified in 
one or more of Groups H-l, H-2, H-3 and H-4 shall conform to the 
code requirements for each of the occupancies so classified. 



SECTION 308 
INSTITUTIONAL GROUP I 

308.1 Institutional Group I. Institutional Group I occupancy 
includes, among others, the use of a building or structure, or a 
portion thereof, in which people are cared for or live in a super- 
vised environment, having physical limitations because of 
health or age are harbored for medical treatment or other care 
or treatment, or in which people are detained for penal or cor- 
rectional purposes or in which the liberty of the occupants is 
restricted. Institutional occupancies shall be classified as 
Group 1-1,1-2,1-3 or 1-4. 

308.2 Group 1-1. This occupancy shall include buildings, 
structures or parts thereof housing more than 16 persons, on a 
24-hour basis, who because of age, mental disability or other 
reasons, live in a supervised residential environment that pro- 
vides personal care services. The occupants are capable of 
responding to an emergency situation without physical assis- 
tance from staff. This group shall include, but not be limited to, 
the following: 

Alcohol and drug centers 
Assisted living facilities 
Congregate care facilities 
Convalescent facilities 
Group homes 
Halfway houses 

Residential board and care facilities 
Social rehabilitation facilities 

A facility such as the above with five or fewer persons shall 
be classified as a Group R-3 or shall comply with the Interna- 
tional Residential Code in accordance with Section 101.2. A 
facility such as above, housing at least six and not more than 16 
persons, shall be classified as Group R-4. 

308.3 Group 1-2. This occupancy shall include buildings and 
structures used for medical, surgical, psychiatric, nursing or 
custodial care for persons who are not capable of self-preserva- 
tion. This group shall include, but not be limited to, the follow- 
ing: 

Child care facilities 
Detoxification facilities 
Hospitals 
Mental hospitals 
Nursing homes 

308.3.1 Definitions. The following words and terms shall, 
for the purposes of this section and as used elsewhere in this 
code, have the meanings shown herein. 

CHILD CARE FACILITIES. Facilities that provide 
care on a 24-hour basis to more than five children, 2V 2 
years of age or less. 



2009 INTERNATIONAL BUILDING CODE® 



}} 



USE AND OCCUPANCY CLASSIFICATION 



DETOXIFICATION FACILITIES. Facilities that 
serve patients who are provided treatment for substance 
abuse on a 24-hour basis and who are incapable of 
self-preservation or who are harmful to themselves or 
others. 

HOSPITALS AND MENTAL HOSPITALS. 

Buildings or portions thereof used on a 24-hour basis for 
the medical, psychiatric, obstetrical or surgical treatment 
of inpatients who are incapable of self-preservation. 

NURSING HOMES. Nursing homes are long-term care 
facilities on a 24-hour basis, including both intermediate 
care facilities and skilled nursing facilities, serving more 
than five persons and any of the persons are incapable of 
self-preservation. 

308.4 Group 1-3. This occupancy shall include buildings and 
structures that are inhabited by more than five persons who are 
under restraint or security. An 1-3 facility is occupied by per- 
sons who are generally incapable of self-preservation due to 
security measures not under the occupants' control. This group 
shall include, but not be limited to, the following: 

Correctional centers 

Detention centers 

Jails 

Prerelease centers 

Prisons 

Reformatories 

Buildings of Group 1-3 shall be classified as one of the occu- 
pancy conditions indicated in Sections 308.4.1 through 
308.4.5 (see Section 408.1). 

308.4.1 Condition 1. This occupancy condition shall 
include buildings in which free movement is allowed from 
sleeping areas, and other spaces where access or occupancy 
is permitted, to the exterior via means of egress without 
restraint. A Condition 1 facility is permitted to be con- 
structed as Group R. 

308.4.2 Condition 2. This occupancy condition shall 
include buildings in which free movement is allowed from 
sleeping areas and any other occupied smoke compartment 
to one or more other smoke compartments. Egress to the 
exterior is impeded by locked exits. 

308.4.3 Condition 3. This occupancy condition shall 
include buildings in which free movement is allowed within 
individual smoke compartments, such as within a residen- 
tial unit comprised of individual sleeping units and group 
activity spaces, where egress is impeded by remote-con- 
trolled release of means of egress from such a smoke com- 
partment to another smoke compartment. 

308.4.4 Condition 4. This occupancy condition shall 
include buildings in which free movement is restricted from 
an occupied space. Remote-controlled release is provided to 
permit movement from sleeping units, activity spaces and 
other occupied areas within the smoke compartment to 
other smoke compartments. 



308.4.5 Condition 5. This occupancy condition shall 
include buildings in which free movement is restricted from 
an occupied space. Staff-controlled manual release is pro- 
vided to permit movement from sleeping units, activity 
spaces and other occupied areas within the smoke compart- 
ment to other smoke compartments . 

308.5 Group 1-4, day care facilities. This group shall include 
buildings and structures occupied by persons of any age who 
receive custodial care for less than 24 hours by individuals 
other than parents or guardians, relatives by blood, marriage or 
adoption, and in a place other than the home of the person cared 
for. A facility such as the above with five or fewer persons shall 
be classified as a Group R-3 or shall comply with the Interna- 
tional Residential Code in accordance with Section 101.2. 
Places of worship during religious functions are not included. 

308.5.1 Adult care facility. A facility that provides accom- 
modations for less than 24 hours for more than five unre- 
lated adults and provides supervision and personal care 
services shall be classified as Group 1-4. 

Exception: A facility where occupants are capable of 
responding to an emergency situation without physical 
assistance from the staff shall be classified as Group R-3. 

308.5.2 Child care facility. A facility that provides supervi- 
sion and personal care on less than a 24-hour basis for more 
than five children 2 V 2 years of age or less shall be classified 
as Group 1-4. 

Exception: A child day care facility that provides care 
for more than five but no more than 100 children 2V 2 
years or less of age, where the rooms in which the chil- 
dren are cared for are located on a level of exit discharge 
serving such rooms and each of these child care rooms 
has an exitdoor directly to the exterior, shall be classified 
as Group E. 



SECTION 309 
MERCANTILE GROUP M 

309.1 Mercantile Group M. Mercantile Group M occupancy 
includes, among others, the use of a building or structure or a 
portion thereof, for the display and sale of merchandise and 
involves stocks of goods, wares or merchandise incidental to 
such purposes and accessible to the public. Mercantile occu- 
pancies shall include, but not be limited to, the following : 

Department stores 

Drug stores 

Markets 

Motor fuel-dispensing facilities 

Retail or wholesale stores 

Sales rooms 

309.2 Quantity of hazardous materials. The aggregate quan- 
tity of nonflammable solid and nonflammable or 
noncombustible liquid hazardous materials stored or displayed 
in a single control area of a Group M occupancy shall not 
exceed the quantities in Table 414.2.5(1). 



34 



2009 INTERNATIONAL BUILDING CODE® 



USE AND OCCUPANCY CLASSIFICATION 



SECTION 310 
RESIDENTIAL GROUP R 

310.1 Residential Group R. Residential Group R includes, 
among others, the use of a building or structure, or a portion 
thereof, for sleeping purposes when not classified as an Institu- 
tional Group I or when not regulated by the International Resi- 
dential Code in accordance with Section 101.2. Residential 
occupancies shall include the following : 

R-l Residential occupancies containing sleeping units where 
the occupants are primarily transient in nature, including: 

Boarding houses (transient) 
Hotels (transient) 
Motels (transient) 

Congregate living facilities (transient) with 10 or fewer 
occupants are permitted to comply with the construction 
requirements for Group R-3. 

R-2 Residential occupancies containing sleeping units or more 
than two dwelling units where the occupants are primarily per- 
manent in nature, including: 

Apartment houses 

Boarding houses (nontransient) 

Convents 

Dormitories 

Fraternities and sororities 

Hotels (nontransient) 

Live/work units 

Monasteries 

Motels (nontransient) 

Vacation timeshare properties 

Congregate living facilities with 16 or fewer occupants are 
permitted to comply with the construction requirements for 
Group R-3. 

R-3 Residential occupancies where the occupants are primar- 
ily permanent in nature and not classified as Group R-l, R-2, 
R-4 or I, including: 

Buildings that do not contain more than two dwelling units. 
Adult care facilities that provide accommodations for five 

or fewer persons of any age for less than 24 hours. 
Child care facilities that provide accommodations for five or 

fewer persons of any age for less than 24 hours. 
Congregate living facilities with 16 or fewer persons. 

Adult care and child care facilities that are within a sin- 
gle-family home are permitted to comply with the Interna- 
tional Residential Code. 

R-4 Residential occupancies shall include buildings arranged 
for occupancy as residential care/assisted living facilities 
including more than five but not more than 16 occupants, 
excluding staff. 

Group R-4 occupancies shall meet the requirements for con- 
struction as defined for Group R-3, except as otherwise pro- 
vided for in this code or shall comply with the International 
Residential Code provided the building is protected by an auto- 
matic sprinkler system installed in accordance with Section 
903.2.7. 



310.2 Definitions. The following words and terms shall, for the 
purposes of this section and as used elsewhere in this code, 
have the meanings shown herein. 

BOARDING HOUSE. A building arranged or used for lodg- 
ing for compensation, with or without meals, and not occupied 
as a single-family unit. 

CONGREGATE LIVING FACILITIES. A building or part 
thereof that contains sleeping units where residents share bath- 
room and/or kitchen facilities . 

DORMITORY. A space in a building where group sleeping 
accommodations are provided in one room, or in a series of 
closely associated rooms, for persons not members of the same 
family group, under joint occupancy and single management, 
as in college dormitories or fraternity houses. 

PERSONAL CARE SERVICE. The care of residents who do 
not require chronic or convalescent medical or nursing care. 
Personal care involves responsibility for the safety of the resi- 
dent while inside the building. 

RESIDENTIAL CARE/ASSISTED LIVING FACILI- 
TIES . A building or part thereof housing persons, on a 24- hour 
basis, who because of age, mental disability or other reasons, 
live in a supervised residential environment which provides 
personal care services. The occupants are capable of respond- 
ing to an emergency situation without physical assistance from 
staff. This classification shall include, but not be limited to, the 
following: residential board and care facilities, assisted living 
facilities, halfway houses, group homes, congregate care facili- 
ties, social rehabilitation facilities, alcohol and drug abuse cen- 
ters and convalescent facilities. 

TRANSIENT. Occupancy of a dwelling unit or sleeping unit 
for not more than 30 days. 



SECTION 311 
STORAGE GROUP S 

311.1 Storage Group S. Storage Group S occupancy includes, 
among others, the use of a building or structure, or a portion 
thereof, for storage that is not classified as a hazardous occu- 
pancy. 

311.2 Moderate-hazard storage, Group S-I. Buildings 
occupied for storage uses that are not classified as Group S-2, 
including, but not limited to, storage of the following: 

Aerosols, Levels 2 and 3 

Aircraft hangar (storage and repair) 

Bags: cloth, burlap and paper 

Bamboos and rattan 

Baskets 

Belting: canvas and leather 

Books and paper in rolls or packs 

Boots and shoes 

Buttons, including cloth covered, pearl or bone 

Cardboard and cardboard boxes 

Clothing, woolen wearing apparel 

Cordage 

Dry boat storage (indoor) 

Furniture 



2009 INTERNATIONAL BUILDING CODE® 



35 



USE AND OCCUPANCY CLASSIFICATION 



I 



Furs 

Glues, mucilage, pastes and size 

Grains 

Horns and combs, other than celluloid 

Leather 

Linoleum 

Lumber 

Motor vehicle repair garages complying with the maximum 

allowable quantities of hazardous materials listed in 

Table 307.1 (1) (see Section 406.6) 
Photo engravings 
Resilient flooring 
Silks 
Soaps 
Sugar 

Tires, bulk storage of 
Tobacco, cigars, cigarettes and snuff 
Upholstery and mattresses 
Wax candles 

311.3 Low-hazard storage, Group S-2. Includes, among oth- 
ers, buildings used for the storage of noncombustible materials 
such as products on wood pallets or in paper cartons with or 
without single thickness divisions; or in paper wrappings. Such 
products are permitted to have a negligible amount of plastic 
trim, such as knobs, handles or film wrapping. Group S-2 stor- 
age uses shall include, but not be limited to, storage of the fol- 
lowing: 

Asbestos 

Beverages up to and including 16-percent alcohol in metal, 

glass or ceramic containers 
Cement in bags 
Chalk and crayons 

Dairy products in nonwaxed coated paper containers 
Dry cell batteries 
Electrical coils 
Electrical motors 
Empty cans 
Food products 

Foods in noncombustible containers 
Fresh fruits and vegetables in nonplastic trays or containers 
Frozen foods 
Glass 

Glass bottles, empty or filled with noncombustible liquids 
Gypsum board 
Inert pigments 
Ivory 
Meats 

Metal cabinets 

Metal desks with plastic tops and trim 
Metal parts 
Metals 
Mirrors 

Oil- filled and other types of distribution transformers 
Parking garages, open or enclosed 
Porcelain and pottery 
Stoves 

Talc and soapstones 
Washers and dryers 



SECTION 312 
UTILITY AND MISCELLANEOUS GROUP U 

312.1 General. Buildings and structures of an accessory char- 
acter and miscellaneous structures not classified in any specific 
occupancy shall be constructed, equipped and maintained to 
conform to the requirements of this code commensurate with 
the fire and life hazard incidental to their occupancy. Group U 
shall include, but not be limited to, the following: 

Agricultural buildings 

Aircraft hangars, accessory to a one- or two-family 

residence (see Section 412.5) 
Barns 
Carports 

Fences more than 6 feet (1829 mm) high 
Grain silos, accessory to a residential occupancy 
Greenhouses 
Livestock shelters 
Private garages 
Retaining walls 
Sheds 
Stables 
Tanks 
Towers 



36 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 4 

SPECIAL DETAILED REQUIREMENTS BASED 
ON USE AND OCCUPANCY 



SECTION 401 
SCOPE 

401.1 Detailed use and occupancy requirements. In addition 
to the occupancy and construction requirements in this code, 
the provisions of this chapter apply to the special uses and 
occupancies described herein. 



SECTION 402 
COVERED MALL AND OPEN MALL BUILDINGS 

402.1 Scope. The provisions of this section shall apply to 
buildings or structures defined herein as cover edmall buildings 
not exceeding three floor levels at any point nor more than three 
stories above grade plane. Except as specifically required by 
this section, coveredmall buildings shall meet applicable pro- 
visions of this code. 

Exceptions: 

1. Foyers and lobbies of Groups B, R-l and R-2 are not 
required to comply with this section. 

2. Buildings need not comply with the provisions of this 
section when they totally comply with other applica- 
ble provisions of this code. 

402.2 Definitions. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

ANCHOR BUILDING. An exterior perimeter building of a 
group other than H having direct access to a coveredmall build- 
ing but having required means of egress independent of the 
mall. 

COVERED MALL BUILDING. A single building enclosing 
a number of tenants and occupants, such as retail stores, drink- 
ing and dining establishments, entertainment and amusement 
facilities, passenger transportation terminals, offices and other 
similar uses wherein two or more tenants have a main entrance 
into one or more malls. For the purpose of this chapter, anchor 
buildings shall not be considered as a part of the coveredmall 
building. The term" coveredmall building" shall include open 
mall buildings as defined below. 

Mall. A roofed or covered common pedestrian area within a 
coveredmall bUilding that serves as access for two or more 
tenants and not to exceed three levels that are open to each 
other. The term "mall" shall include open malls as defined 
below. 

Open mall. An unroofed common pedestrian way serving a 
number of tenants not exceeding three levels. Circulation at 
levels above grade shall be permitted to include open exte- 
rior balconies leading to exits discharging at grade. 

Open mall building. Several structures housing a number 
of tenants, such as retail stores, drinking and dining estab- 



lishments, entertainment and amusement facilities, offices, 
and other similar uses, wherein two or more tenants have a 
main entrance into one or more open malls. For the purpose 
of Chapter 4 of the International Building Code, anchor 
buildings are not considered as a part of the open mall build- 
ing. 

FOOD COURT. A public seating area located in the mall that 
serves adjacent food preparation tenant spaces. 

GROSS LEASABLE AREA. The total floor area designed 
for tenant occupancy and exclusive use. The area of tenant 
occupancy is measured from the centerlines of joint partitions 
to the outside of the tenant walls. All tenant areas, including 
areas used for storage, shall be included in calculating gross 
leasable area. 

402.3 Lease plan. Each coveredmall bUilding owner shall pro- 
vide both the building and fire departments with a lease plan 
showing the location of each occupancy and its exits after the 
certificate of occupancy has been issued. No modifications or 
changes in occupancy or use shall be made from that shown on 
the lease plan without prior approval of the building official. 

402.4 Means of egress. Each tenant space and the coveredmall 
bUilding shall be provided with means of egress as required by 
this section and this code. Where there is a conflict between the 
requirements of this code and the requirements of this section, 
the requirements of this section shall apply. 

402.4.1 Determination of occupant load. The occupant 
loa d permitted in any individual tenant space in a covered 
mall building shall be determined as required by this code. 
Means of egress requirements for individual tenant spaces 
shall be based on the occupant load thus determined. 

402.4.1.1 Occupant formula. In determining required 
means of egress of the mall, the number of occupants for 
whom means of egress are to be provided shall be based 
on gross leasable area of the covered mall building 
(excluding anchor buildings) and the occupant loadfac- 
tor as determined by the following equation. 



a LP= (0.00007) (CLA) + 25 



where: 



(Equation 4-1) 



aLP = The occupant load factor (square feet per per- 
son). 

CLA = The gross leasable area (square feet). 

Exception: Tenant spaces attached to a coveredmall 
building but with a means of egress system that is 
totally independent of the coveredmall bUilding shall 
not be considered as gross leasable area for determin- 
ing the required means of egress for the coveredmall 
bUilding. 



2009 INTERNATIONAL BUILDING CODE® 



37 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



402.4.1.2 OLF range. The occupant load factor (OLE) 
is not required to be less than 30 and shall not exceed 50. 

402.4.1.3 Anchor buildings. The occupant load of 
anchor buildings opening into the mall shall not be 
included in computing the total number of occupants for 
the mall. 

402.4.1.4 Food courts. The occupant load of a food 
court shall be determined in accordance with Section 
1004. For the purposes of determining the means of 
egress requirements for the mall, the food court occupant 
loa d shall be added to the occupant load of the covered 
mall bUilding as calculated above. 

402.4.2 Number of means of egress. Wherever the dis- 
tance of travel to the mall from any location within a tenant 
space used by persons other than employees exceeds 75 
feet (22 860 mm) or the tenant space has an occupantload 
of 50 or more, not less than two means of egress shall be 
provided. 

402.4.3 Arrangements of means of egress. Assembly 
occupancies with an occupant load of 500 or more shall be 
so located in the covered mall bUilding that their entrance 
will be immediately adjacent to a principal entrance to the 
mall and shall have not less than one-half of their required 
means of egress opening directly to the exterior of the cov- 
ered mall building. 

402.4.3.1 Anchor building means of egress. Required 
means of egress for anchor bUildings shall be provided 
independently from the mall means of egress system. 
The occupant load of anchor bUildings opening into the 
mall shall not be included in determining means of egress 
requirements for the mall. The path of egress travel of 
malls shall not exit through anchor buildings. Malls ter- 
minating at an anchor building where no other means of 
egress has been provided shall be considered as a 
dead-end mall. 

402.4.4 Distance to exits. Within each individual tenant 
space in a covered mall bUilding, the maximum distance of 
travel from any point to an exit or entrance to the mall shall 
not exceed 200 feet (60 960 mm). 

The maximum distance of travel from any point within a 
mall to an exit shall not exceed 200 feet (60 960 mm). 

402.4.5 Access to exits. Where more than one exit is 
required, they shall be so arranged that it is possible to travel 
in either direction from any point in a mall to separate exits. 
The minimum width of an exitpassagewayox corridorfrom 
a mall shall be 66 inches (1676 mm). 

Exception: Dead ends not exceeding a length equal to 
twice the width of the mall measured at the narrowest 
location within the dead-end portion of the mall. 

402.4.5.1 Exit passageways. Where exit passageways 
provide a secondary means of egress from a tenant space, 
doorways to the exit passageway shall be protected by 
I-hour fire door assemblies that are self- or automatic- 
closing by smoke detection in accordance with Section 
715.4.8.3. 



402.4.6 Service areas fronting on exit passageways. 
Mechanical rooms, electrical rooms, building service areas 
and service elevators are permitted to open directly into exit 
passageways, provided the exit passageway is separated 
from such rooms with not less than I-hour fire barriers con- 
structed in accordance with Section 707 or horizontal 
assemblies constructed in accordance with Section 712, or 
both. The minimum fire protection rating of openings in the 
fire barriers shall be 1 hour. 

402.5 Mall width. For the purpose of providing required egress, 
malls are permitted to be considered as corridors but need not 
comply with the requirements of Section 1005.1 of this code 
where the width of the mall is as specified in this section. 

402.5.1 Minimum width. The minimum width of the mall 
shall be 20 feet (6096 mm). The mall width shall be suffi- 
cient to accommodate the occupantloadserved. There shall 
be a minimum of 10 feet (3048 mm) clear exit width to a 
height of 8 feet (2438 mm) between any projection of a ten- 
ant space bordering the mall and the nearest kiosk, vending 
machine, bench, display opening, food court or other 
obstruction to means of egress travel. 

402.5.2 Minimum width open mall. The minimum floor 
and roof opening width above grade shall be 20 feet (9096 
mm) in open malls. 

402.6 Types of construction. The area of any covered mall 
building, including anchor buildings, of Types I, II, IE and IV 
construction, shall not be limited provided the covered mall 
bUilding and attached anchor bUildings and parking garages 
are surrounded on all sides by a permanent open space of not 
less than 60 feet (18 288 mm) and the anchor bUildings do not 
exceed three stories above grade plane. The allowable height 
and area of anchor bUildings greater than three stories above 
grade plane shall comply with Section 503, as modified by 
Sections 504 and 506. The construction type of open parking 
garages and enclosed parking garages shall comply with Sec- 
tions 406.3 and 406.4, respectively. 

402.6.1 Reduced open space. The permanent open space of 
60 feet (18 288 mm) shall be permitted to be reduced to not 
less than 40 feet (12 192 mm), provided the following requ- 
irements are met: 

1. The reduced open space shall not be allowed for more 
than 75 percent of the perimeter of the covered mall 
building and anchor buildings. 

2. The exterior wall facing the reduced open space shall 
have a minimum fire -resistance rating of 3 hours. 

3. Openings in the exterior wa//facing the reduced open 
space shall have opening protectives with a minimum 
fire protection rating of 3 hours. 

4. Group E, H, lor R occupancies are not within the cov- 
eredmall building or anchor stores. 

402.7 Fire-resistance-rated separation. Fire-resis- 
tance-rated separation is not required between tenant spaces 
and the mall. Fire-resistance-rated separation is not required 
between a food court and adjacent tenant spaces or the mall. 

402.7.1 Attached garage. An attached garage for the stor- 
age of passenger vehicles having a capacity of not more than 



38 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



nine persons and open parking garages shall be considered 
as a separate building where it is separated from the covered 
mall bUilding by not less than 2-hour fire barriers con- 
structed in accordance with Section 707 or horizontal 
assemblies constructed in accordance with Section 712, or 
both. 

Exception: Where an open parking garage or enclosed 
parking garage is separated from the coveredmall build- 
ing or anchor building a distance greater than 10 feet 
(3048 mm), the provisions of Table 602 shall apply. 
Pedestrian walkways and tunnels that attach the open 
parking garage or enclosed parking garage to the cov- 
ered mall bUilding or anchor bUilding shall be con- 
structed in accordance with Section 3104. 

402.7.2 Tenant separations. Each tenant space shall be 
separated from other tenant spaces by a fire partition com- 
plying with Section 709. A tenant separation wall is not 
required between any tenant space and the mall. 

402.7.3 Anchor building separation. An anchor bUilding 
shall be separated from the covered mall bUilding by fire 
walls complying with Section 706. 

Exception: Anchor buildings of not more than three sto- 
ries above grade plane that have an occupancy classifi- 
cation the same as that permitted for tenants of the 
covered mall building shall be separated by 2-hour 
fire-resistive fire barriers complying with Section 707. 

402.7.3.1 Openings between anchor building and 
mall. Except for the separation between Group R-l 
sleeping units and the mall, openings between anchor 
buildings of Type 1A, IB, IIA and 1IB construction and 
the mall need not be protected. 

402.8 Interior finish. Interior wall mid ceiling finishes within 
the mall and exits shall have a minimum flame spreadindexsmd 
smoke-developed index of Class B in accordance with Chapter 
8. Interior floor finishes shall meet the requirements of Section 
804. 

[F] 402.9 Automatic sprinkler system. The covered mall 
bUilding and buildings connected shall be equipped throughout 
with an automatic sprinkler system in accordance with Section 
903.3.1.1, which shall comply with the following: 

1. The automatic sprinkler system shall be complete and 
operative throughout occupied space in the coveredmall 
building prior to occupancy of any of the tenant spaces. 
Unoccupied tenant spaces shall be similarly protected 
unless provided with approved alternative protection. 

2. Sprinkler protection for the mall shall be independent 
from that provided for tenant spaces or anchors. Where 
tenant spaces are supplied by the same system, they shall 
be independently controlled. 

Exception: An automatic sprinkler system shall not be 
required in spaces or areas of open parking garages con- 
structed in accordance with Section 406.3. 

[F] 402.9.1 Standpipe system. The coveredmall bUilding 
shall be equipped throughout with a standpipe system as 
required by Section 905.3.3. 



402.10 Smoke control. Where a coveredmall building con- 
tains an atrium, a smoke control system shall be provided in 
accordance with Section 404.5. 

Exception: A smoke control system is not required in cov- 
ered mall bUildings when an atrium connects only two sto- 
ries. 

402.11 Kiosks. Kiosks and similar structures (temporary or 
permanent) shall meet the following requirements : 

1. Combustible kiosks or other structures shall not be 
located within the mall unless constructed of any of the 
following materials: 

7.7. Fire-retardant-treated wood complying with 
Section 2303.2. 

1.2. Foam plastics having a maximum heat-release 
rate not greater than 100 kilowatts (105 Btu/h) 
when tested in accordance with the exhibit booth 
protocol in UL 1975. 

1.3. Aluminum composite material (ACM) having a 
flame spread index of not more than 25 and a 
smoke-developed index of not more than 450 
when tested as an assembly in the maximum 
thickness intended for use in accordance with 
ASTM E 84 or UL 723. 

2. Kiosks or similar structures located within the mall shall 
be provided with approved fire suppression detection 
devices. 

3. The minimum horizontal separation between kiosks or 
groupings thereof and other structures within the mall 
shall be 20 feet (6096 mm). 

4. Each kiosk or similar structure or groupings thereof shall 
have a maximum area of 300 square feet (28 m 2 ). 

402.12 Children's playground structures. Structures 
intended as children's playgrounds that exceed 10 feet (3048 
mm) in height and 150 square feet (14 m 2 ) in area shall comply 
with Sections 402.12.1 through 402.12.4. 

402.12.1 Materials. Children's playground structures shall 
be constructed of noncombustible materials or of combusti- 
ble materials that comply with the following: 

7. Fire-retardant-treated wood. 

2. Light-transmitting plastics complying with Section 
2606. 

3. Foam plastics (including the pipe foam used in 
soft-contained play equipment structures) having a 
maximum heat-release rate not greater than 100 
kilowatts when tested in accordance with UL 1975. 

4. Aluminum composite material (ACM) meeting the 
requirements of Class A interior finish in accordance 
with Chapter 8 when tested as an assembly in the 
maximum thickness intended for use. 

5. Textiles and films complying with the flame propaga- 
tion performance criteria contained in NFPA 701. 

6. Plastic materials used to construct rigid components 
of soft-contained play equipment structures (such as 
tubes, windows, panels, junction boxes, pipes, slides 



i 



2009 INTERNATIONAL BUILDING CODE® 



39 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



I 



and decks) exhibiting a peak rate of heat release not 
exceeding 400 kW/m 2 when tested in accordance with 
ASTM E 1354 at an incident heat flux of 50 kW/m 2 in 
the horizontal orientation at a thickness of 6 mm. 

7. Ball pool balls, used in soft-contained play equipment 
structures, having a maximum heat-release rate not 
greater than 100 kilowatts when tested in accordance 
with UL 1975. The minimum specimen test size shall 
be 36 inches by 36 inches (914 mm by 914 mm) by an 
average of 21 inches (533 mm) deep, and the balls 
shall be held in a box constructed of galvanized steel 
poultry netting wire mesh. 

8. Foam plastics shall be covered by a fabric, coating or 
film meeting the flame propagation performance cri- 
teria of NFP A 701. 

9. The floor covering placed under the children's play- 
ground structure shall exhibit a Class I interior floor 
finish classification, as described in Section 804, 
when tested in accordance with NFPA 253. 

402.12.2 Fire protection. Children's playground structures 
located within the mall shall be provided with the same level 
of app roved fire suppression and detection devices required 
for kiosks and similar structures. 

402.12.3 Separation. Children's playground structures 
shall have a minimum horizontal separation from other 
structures within the mall of 20 feet (6090 mm). 

402.12.4 Area limits. Children's playground structures 
shall not exceed 300 square feet (28 m 2 ) in area, unless a 
special investigation has demonstrated adequate fire safety. 

402.13 Security grilles and doors. Horizontal sliding or verti- 
cal security grilles or doors that are a part of a required means of 
egress shall conform to the following : 

1. They shall remain in the full open position during the 
period of occupancy by the general public. 

2. Doors or grilles shall not be brought to the closed posi- 
tion when there are 10 or more persons occupying spaces 
served by a single exit or 50 or more persons occupying 
spaces served by more than one exit. 

3. The doors or grilles shall be openable from within with- 
out the use of any special knowledge or effort where the 
space is occupied. 

4. Where two or more exits are required, not more than 
one-half of the exits shall be permitted to include either a 
horizontal sliding or vertical rolling grille or door. 

[F] 402.14 Standby power. Coveredmall buildings exceeding 
50,000 square feet (4645 m 2 ) shall be provided with standby 
power systems that are capable of operating the emergency 
voice/alarm communication system. 

[F] 402.15 Emergency voice/alarm communication system. 
Covered mall buildings exceeding 50,000 square feet (4645 
m 2 ) in total floor area shall be provided with an emergency 
voice/alarm communication system. Emergency voice/alarm 
communication systems serving a mall, required or otherwise, 
shall be accessible to the fire department. The system shall be 
provided in accordance with Section 907.5.2.2. 



402.16 Plastic signs. Plastic signs affixed to the storefront of 
any tenant space facing the mall shall be limited as specified in 
Sections 402.16.1 through 402.16.5.2. 

402.16.1 Area. Plastic signs shall not exceed 20 percent of 
the wall area facing the mall. 

402.16.2 Height and width. Plastic signs shall not exceed a 
height of 36 inches (914 mm), except that if the sign is verti- 
cal, the height shall not exceed 96 inches (2438 mm) and the 
width shall not exceed 36 inches (914 mm). 

402.16.3 Location. Plastic signs shall be located a mini- 
mum distance of 18 inches (457 mm) from adjacent tenants. 

402.16.4 Plastics other than foam plastics. Plastics other 
than foam plastics used in signs shall be light-transmitting 
plastics complying with Section 2606.4 or shall have a 
self-ignition temperature of 650°F (343°C) or greater when 
tested in accordance with ASTM D 1929, and a flame 
spread index not greater than 75 and smoke-developed 
index not greater than 450 when tested in the manner 
intended for use in accordance with ASTM E 84 or UL 723 
or meet the acceptance criteria of Section 803.1.2.1 when 
tested in accordance with NFPA 286. 

402.16.4.1 Encasement. Edges and backs of plastic 
signs in the mall shall be fully encased in metal. 

402.16.5 Foam plastics. Foam plastics used in signs shall 
have flame-retardant characteristics such that the sign has a 
maximum heat-release rate of 150 kilowatts when tested in 
accordance with UL 1975 and the foam plastics shall have 
the physical characteristics specified in this section. Foam 
plastics used in signs installed in accordance with Section 
402.16 shall not be required to comply with the flame 
spread and smoke-developed indexes specified in Section 
2603.3. 

402.16.5.1 Density. The minimum density of foam plas- 
tics used in signs shall not be less than 20 pounds per 
cubic foot (pcf) (320 kg/m 3 ). 

402.16.5.2 Thickness. The thickness of foam plastic 
signs shall not be greater than i/ 2 inch (12.7 mm). 

\F] 402.17 Fire department access to equipment. Rooms or 
areas containing controls for air-conditioning systems, auto- 
matic fire-extinguishing systems or other detection, suppres- 
sion or control elements shall be identified for use by the fire 
department. 



SECTION 403 
HIGH-RISE BUILDINGS 

403.1 Applicability. High-rise buildings shall comply with 
Sections 403 .2 through 403.6. 

Exception: The provisions of Sections 403.2 through 403.6 
shall not apply to the following buildings and structures: 

1. Airport traffic control towers in accordance with Sec- 
tion 412.3. 

2. Open parking garages in accordance with Section 
406.3. 



40 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



3. Buildings with a Group A-5 occupancy in accordance 
with Section 303.1. 

4. Special industrial occupancies in accordance with 
Section 503.1.1. 

5. Buildings with a Group H-l, H-2 or H-3 occupancy in 
accordance with Section 415. 

403.2 Construction. The construction of high-rise buildings 
shall comply with the provisions of Sections 403.2.1 through 
403.2.4. 

403.2.1 Reduction in fire-resistance rating. The 
fire-resistance-rating reductions listed in Sections 
403.2.1.1 and 403.2.1.2 shall be allowed in buildings that 
have sprinkler control valves equipped with supervisory ini- 
tiating devices and water-flow initiating devices for each 
floor. 

403.2.1.1 Type of construction. The following reduc- 
tions in the minimum fire- resistance rating of the build- 
ing elements in Table 601 shall be permitted as follows: 

1. For buildings not greater than 420 feet (128 m) in 
bUilding height, the fire-resistance rating of the 
building elements in Type IA construction shall be 
permitted to be reduced to the minimum fire-resis- 
tance ratings for the building elements in Type IB. 

Exception: The required fire-resistance rating 
of columns supporting floors shall not be per- 
mitted to be reduced. 

2. In other than Group F-l, M and S-l occupancies, 
the fire -resistance rating of the building elements 
in Type IB construction shall be permitted to be 
reduced to the fire-resistance ratings in Type IIA. 

3. The building height mid building area limitations 
of a building containing building elements with 
reduced fire -resistance ratings shall be permitted 
to be the same as the building without such reduc- 
tions. 

403.2.1.2 Shaft enclosures. For buildings not greater 
than 420 feet (128 m) in bUilding height, the required 
fire-resistance rating of the fire barriers enclosing verti- 
cal shafts, other than exit enclosures and elevator 
hoistway enclosures, is permitted to be reduced to 1 hour 
where automatic sprinklers are installed within the shafts 
at the top and at alternate floor levels . 

403.2.2 Seismic considerations. For seismic consider- 
ations, see Chapter 16. 

403.2.3 Structural integrity of exit enclosures and eleva- 
tor hoistway enclosures. For high-rise buildings of occu- 
pancy category III or IV in accordance with Section 1604.5, 
and for all buildings that are more than 420 feet (128 m) in 
building height, exit enclosures and elevator hoistway 
enclosures shall comply with Sections 403.2.3.1 through 
403.2.3.4. 

403.2.3.1 Wall assembly. The wall assemblies making 
up the exit enclosures and elevator hoistway enclosures 
shall meet or exceed Soft Body Impact Classification 



Level 2 as measured by the test method described in 
ASTM C 1629/C 1629M. 

403.2.3.2 Wall assembly materials. The face of the wall 
assemblies making up the exit enclosures and elevator 
hoistway enclosures that are not exposed to the interior 
of the exit enclosure or elevator hoistway enclosure shall 
be constructed in accordance with one of the following 
methods: 

1. The wall assembly shall incorporate not less than 
two layers of impact-resistant construction board 
each of which meets or exceeds Hard Body Impact 
Classification Level 2 as measured by the test 
method described in ASTM C 1629/C 1629M. 

2. The wall assembly shall incorporate not less than 
one layer of impact-resistant construction material 
that meets or exceeds Hard Body Impact Classifi- 
cation Level 3 as measured by the test method 
described in ASTM C 1629/C 1629M. 

3. The wall assembly incorporates multiple layers of 
any material, tested in tandem, that meet or exceed 
Hard Body Impact Classification Level 3 as mea- 
sured by the test method described in ASTM C 
1629/C 1629M. 

403.2.3.3 Concrete and masonry walls. Concrete or 
masonry walls shall be deemed to satisfy the require- 
ments of Sections 403.2.3.1 and 403.2.3.2. 

403.2.3.4 Other wall assemblies. Any other wall assem- 
bly that provides impact resistance equivalent to that 
required by Sections 403.2.3.1 and 403.2.3.2 for Hard 
Body Impact Classification Level 3, as measured by the 
test method described in ASTM C 1629/C 1629M, shall 
be permitted. 

403.2.4 Sprayed fire-resistant materials (SFRM). The 
bond strength of the SFRM installed throughout the build- 
ing shall be in accordance with Table 403.2.4. 

TABLE 403.2.4 
MINIMUM BOND STRENGTH 



HEIGHT OF BUILDING a 


SFRM MINIMUM BOND STRENGTH 


Up to 420 feet 


430 psf 


Greater than 420 feet 


l,000psf 



For 51 : 1 foot = 304.8 mm, 1 pound per square foot (pst) = 0.0479 kWyin 2 . 
a. Above the lowest level of fire department vehicle access. 

[F] 403.3 Automatic sprinkler system. Buildings and struc- 
tures shall be equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1 and a secondary 
water supply where required by Section 903.3.5.2. 

Exception: An automatic sprinkler system shall not be 
required in spaces or areas of: 

1. Open parking garages in accordance with Section 
406.3. 

2. Telecommunications equipment buildings used 
exclusively for telecommunications equipment, asso- 
ciated electrical power distribution equipment, bat- 
teries and standby engines, provided that those spaces 



2009 INTERNATIONAL BUILDING CODE® 



41 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



or areas are equipped throughout with an automatic 
fire detection system in accordance with Section 
907.2 and are separated from the remainder of the 
building by not less than I-hour fire barriers con- 
structed in accordance with Section 707 or not less 
than 2-hour horizontal assemblies constructed in 
accordance with Section 712, or both. 

[F] 403.3.1 Number of sprinkler risers and system 
design. Each sprinkler system zone in buildings that are 
more than 420 feet (128 m) in building height shall be sup- 
plied by a minimum of two risers. Each riser shall supply 
sprinklers on alternate floors. If more than two risers are 
provided for a zone, sprinklers on adjacent floors shall not 
be supplied from the same riser. 

[F] 403.3.1.1 Riser location. Sprinkler risers shall be 
placed in exit enclosures that are remotely located in 
accordance with Section 1015.2. 

[F] 403.3.2 Water supply to required fire pumps. 
Required fire pumps shall be supplied by connections to a 
minimum of two water mains located in different streets. 
Separate supply piping shall be provided between each con- 
nection to the water main and the pumps. Each connection 
and the supply piping between the connection and the 
pumps shall be sized to supply the flow and pressure 
required for the pumps to operate. 

Exception: Two connections to the same main shall be 
permitted provided the main is valved such that an inter- 
ruption can be isolated so that the water supply will con- 
tinue without interruption through at least one of the 
connections. 

403.4 Emergency systems. The detection, alarm and emer- 
gency systems of high-rise buildings shall comply with Sec- 
tions 403.4.1 through 403.4.8. 

[F] 403.4.1 Smoke detection. Smoke detection shall be 
provided in accordance with Section 907.2.13.1. 

[F] 403.4.2 Fire alarms systems. A fire alarm system shall 
be provided in accordance with Section 907.2.13. 

[F] 403.4.3 Emergency voice/alarm communication sys- 
tem. An emergency voice/alarm communication system 
shall be provided in accordance with Section 907.5.2.2. 

[F] 403.4.4 Emergency responder radio coverage. Emer- 
gency responder radio coverage shall be provided in accor- 
dance with Section 510 of the International Fire Code. 

[F] 403.4.5 Fire command. A fire command center com- 
plying with Section 911 shall be provided in a location 
approvedby the fire department. 

403.4.6 Smoke removal. To facilitate smoke removal in 
post-fire salvage and overhaul operations, buildings and 
structures shall be equipped with natural or mechanical ven- 
tilation for removal of products of combustion in accor- 
dance with one of the following: 

1. Easily identifiable, manually operable windows or 
panels shall be distributed around the perimeter of 
each floor at not more than 50-foot (15 240 mm) inter- 
vals. The area of operable windows or panels shall not 



be less than 40 square feet (3.7 m 2 ) per 50 linear feet 
(15 240 mm) of perimeter. 

Exceptions: 

1. In Group R-l occupancies, each sleeping 
unit or suite having an exterior wall shall be 
permitted to be provided with 2 square feet 
(0.19 m 2 ) of venting area in lieu of the area 
specified in Item 1. 

2. Windows shall be permitted to be fixed pro- 
vided that glazing can be cleared by fire 
fighters. 

2. Mechanical air-handling equipment providing one 
exhaust air change every 15 minutes for the area 
involved. Return and exhaust air shall be moved 
directly to the outside without recirculation to other 
portions of the building. 

3. Any other approved design that will produce equiva- 
lent results. 

[F] 403.4.7 Standby power. A standby power system com- 
plying with Chapter 27 shall be provided for standby power 
loads specified in Section 403.4.7.2. 

[F] 403.4.7.1 Special requirements for standby power 
systems. If the standby system is a generator set inside a 
building, the system shall be located in a separate room 
enclosed with 2-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. System 
supervision with manual start and transfer features shall 
be provided at the fire command center. 

[F] 403.4.7.2 Standby power loads. The following are 
classified as standby power loads: 

1. Power and lighting for the fire command center 
required by Section 403.4.5; 

2. Ventilation and automatic fire detection equip- 
ment for smokeproof enclosures; and 

3. Standby power shall be provided for elevators in 
accordance with Sections 1007.4,3003,3007 and 
3008. 

\F] 403.4.8 Emergency power systems. An emergency 
power system complying with Chapter 27 shall be provided 
for emergency power loads specified in Section 403.4.8.1. 

[F] 403.4.8.1 Emergency power loads. The following 
are classified as emergency power loads: 

1. Exit signs and means of egress illumination 
required by Chapter 10; 

2. Elevator car lighting; 

3. Emergency voice/alarm communications systems; 

4. Automatic fire detection systems; 

5. Fire alarm systems; and 

6. Electrically powered fire pumps. 

403.5 Means of egress and evacuation. The means of egress 
in high-rise buildings shall comply with Sections 403.5.1 
through 403.5.6. 



42 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



403.5.1 Remoteness of exit stairway enclosures. The 
required exit stairway enclosures shall be separated by a dis- 
tance not less than 30 feet (9144 mm) or not less than 
one-fourth of the length of the maximum overall diagonal 
dimension of the building or area to be served, whichever is 
less. The distance shall be measured in a straight line 
between the nearest points of the exit stairway enclosures. 
In buildings with three or more exit stairway enclosures, at 
least two of the exit stairway enclosures shall comply with 
this section. Interlocking or scissor stairs shall be counted 
as one exit stairway. 

403.5.2 Additional exit stairway. For buildings other than 
Group R-2 that are more than 420 feet (128 m) in bUilding 
height, one additional exit stairway meeting the require- 
ments of Sections 1009 and 1022 shall be provided in addi- 
tion to the minimum number of exits required by Section 
1021.1. The total width of any combination of remaining 
exit stairways with one exit stairway removed shall not be 
less than the total width required by Section 1005.1. Scissor 
stairs shall not be considered the additional exit stairway 
required by this section. 

Exception: An additional exit stairway shall not be 
required to be installed in buildings having elevators 
used for occupant self-evacuation in accordance with 
Section 3008. 

403.5.3 Stairway door operation. Stairway doors other 
than the exit discharge doors shall be permitted to be locked 
from the stairway side. Stairway doors that are locked from 
the stairway side shall be capable of being unlocked simul- 
taneously without unlatching upon a signal from the fire 
command center. 

403.5.3.1 Stairway communication system. A tele- 
phone or other two-way communications system con- 
nected to an approved constantly attended station shall 
be provided at not less than every fifth floor in each stair - 
way where the doors to the stairway are locked. 

403.5.4 Smokeproof exit enclosures. Every required level 
exit stairway serving floors more than 75 feet (22 860 mm) 
above the lowest level of fire department vehicle access 
shall comply with Sections 909.20 and 1022.9. 

403.5.5 Luminous egress path markings. Luminous 
egress path markings shall be provided in accordance with 
Section 1024. 

403.5.6 Emergency escape and rescue. Emergency escape 
and rescue openings required by Section 1029 are not 
required. 

403.6 Elevators. Elevator installation and operation in 
high-rise buildings shall comply with Chapter 30 and Sections 
403.6.1 and 403.6.2. 

403.6.1 Fire service access elevator. In buildings with an 
occupied floor more than 120 feet (36 576 mm) above the 
lowest level of fire department vehicle access, a minimum 
of one fire service access elevator shall be provided in accor- 
dance with Section 3007. 

403.6.2 Occupant evacuation elevators. Where installed 
in accordance with Section 3008, passenger elevators for 



general public use shall be permitted to be used for occupant 
self-evacuation. 



SECTION 404 
ATRIUMS 

404.1 General. In other than Group H occupancies, and where 
permitted by Exception 5 in Section 708.2, the provisions of 
this section shall apply to buildings or structures containing 
vertical openings defined herein as 'Atriums." 

404.1.1 Definition. The following word and term shall, for 
the purposes of this chapter and as used elsewhere in this 
code, have the meaning shown herein. 

ATRIUM. An opening connecting two or more stories 
other than enclosed stairways, elevators, hoistways, escala- 
tors, plumbing, electrical, air-conditioning or other equip- 
ment, which is closed at the top and not defined as a mall. 
Stories, as used in this definition, do not include balconies 
within assembly groups or mezzanines that comply with 
Section 505. 

404.2 Use. The floor of the atrium shall not be used for other 
than low fire hazard uses and only approvedmatermis and dec- 
orations in accordance with the International Fire Code shall 
be used in the atrium space. 

Exception: The atrium floor area is permitted to be used for 
any approved use where the individual space is provided 
with an automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1. 

[F] 404.3 Automatic sprinkler protection. An approved 
automatic sprinkler system shall be installed throughout the 
entire building. 

Exceptions: 

1. That area of a building adjacent to or above the atrium 
need not be sprinklered provided that portion of the 
building is separated from the atrium portion by not 
less than 2-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. 

2. Where the ceiling of the atrium is more than 55 feet 
(16 764 mm) above the floor, sprinkler protection at 
the ceiling of the atrium is not required. 

[F] 404.4 Fire alarm system. A fire alarm system shall be pro- 
vided in accordance with Section 907.2.14. 

404.5 Smoke control. A smoke control system shall be 
installed in accordance with Section 909. 

Exception: Smoke control is not required for atriums that 
connect only two stories. 

404.6 Enclosure of atriums. Atrium spaces shall be separated 
from adjacent spaces by a I-hour fire barrier constructed in 
accordance with Section 707 or a horizontal assembly con- 
structed in accordance with Section 712, or both. 

Exceptions: 

1. A glass wall forming a smoke partition where auto- 
matic sprinklers are spaced 6 feet (1829 mm) or less 
along both sides of the separation wall, or on the room 



2009 INTERNATIONAL BUILDING CODE® 



43 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



1 



1 



side only if there is not a walkway on the atrium side, 
and between 4 inches and 12 inches (102 mm and 305 
mm) away from the glass and designed so that the 
entire surface of the glass is wet upon activation of the 
sprinkler system without obstruction. The glass shall 
be installed in a gasketed frame so that the framing 
system deflects without breaking (loading) the glass 
before the sprinkler system operates. 

2. A glass-block wall assembly in accordance with Sec- 
tion 2110 and having a 3/ 4 -hour fire protection rating. 

3. The adjacent spaces of any three floors of the atrium 
shall not be required to be separated from the atrium 
where such spaces are accounted for in the design of 
the smoke control system. 

[F] 404.7 Standby power. Equipment required to provide 
smoke control shall be connected to a standby power system in 
accordance with Section 909.11. 

404.8 Interior finish. The interior finish of walls and ceilings 
of the atrium shall not be less than Class B with no reduction in 
class for sprinkler protection. 

404.9 Travel distance. In other than the lowest level of the 
atrium, where the required means of egress is through the 
atrium space, the portion of exit access travel distance within 
the atrium space shall not exceed 200 feet (60 960 mm). The 
travel distance requirements for areas of buildings open to the 
atrium and where access to the exits is not through the atrium, 
shall comply with the requirements of Section 1016. 



SECTION 405 
UNDERGROUND BUILDINGS 

405.1 General. The provisions of this section apply to building 
spaces having a floor level used for human occupancy more 
than 30 feet (9144 mm) below the finished floor of the lowest 
level of exit discharge. 

Exceptions: 

1. One- and two-family dwellings, sprinklered in accor- 
dance with Section 903.3.1.3. 

2. Parking garages with automatic sprinkler systems in 
compliance with Section 405.3. 

3. Fixed guideway transit systems. 

4. Grandstands, bleachers, stadiums, arenas and similar 
facilities . 

5. Where the lowest story is the only story that would 
qualify the building as an underground building and 
has an area not exceeding 1,500 square feet (139 m 2 ) 
and has an occupant load less than 10. 

6. Pumping stations and other similar mechanical 
spaces intended only for limited periodic use by ser- 
vice or maintenance personnel. 

405.2 Construction requirements. The underground portion 
of the building shall be of Type I construction. 

[F] 405.3 Automatic sprinkler system. The highest level of 
exit discharge serving the underground portions of the building 
and all levels below shall be equipped with an automatic sprin- 



kler system installed in accordance with Section 903.3.1.1. 
Water-flow switches and control valves shall be supervised in 
accordance with Section 903.4. 

405.4 Compartmentation. Compartmentation shall be in 
accordance with Sections 405.4.1 through 405.4.3. 

405.4.1 Number of compartments. A building having a 
floor level more than 60 feet (18 288 mm) below the finished 
floor of the lowest level of exit discharge shall be divided 
into a minimum of two compartments of approximately 
equal size. Such compartmentation shall extend through the 
highest level of exit discharge serving the underground por- 
tions of the building and all levels below. 

Exception: The lowest storyneed not be compartmented 
where the area does not exceed 1,500 square feet (139 
m 2 ) and has an occupant load of less than 10. 

405.4.2 Smoke barrier penetration. The compartments 
shall be separated from each other by a smoke barrier in 
accordance with Section 710. Penetrations between the two 
compartments shall be limited to plumbing and electrical 
piping and conduit that are firestopped in accordance with 
Section 713. Doorways shall be protected by fire door 
assemblies that are automatic-closing by smoke detection in 
accordance with Section 715.4.8.3 and are installed in 
accordance with NFPA 105 and Section 715.4.3. Where 
provided, each compartment shall have an air supply and an 
exhaust system independent of the other compartments. 

405.4.3 Elevators. Where elevators are provided, each 
compartment shall have direct access to an elevator. Where 
an elevator serves more than one compartment, an elevator 
lobby shall be provided and shall be separated from each 
compartment by a smoke barrierin accordance with Section 
710. Doors shall be gasketed, have a drop sill and be auto- 
matic-closing by smoke detection in accordance with Sec- 
tion 715.4.8.3. 

[F] 405.5 Smoke control system. A smoke control system 
shall be provided in accordance with Sections 405.5.1 and 
405.5.2. 

[F] 405.5.1 Control system. A smoke control system is 
required to control the migration of products of combustion 
in accordance with Section 909 and the provisions of this 
section. Smoke control shall restrict movement of smoke to 
the general area of fire origin and maintain means of egress 
in a usable condition. 

[F] 405.5.2 Compartment smoke control system. Where 
compartmentation is required, each compartment shall have 
an independent smoke control system. The system shall be 
automatically activated and capable of manual operation in 
accordance with Sections 907.2.18 and 907.2.19. 

[F] 405.6 Fire alarm systems. A fire alarm system shall be 
provided where required by Sections 907.2.18 and 907.2.19. 

405.7 Means of egress. Means ofegress shall be in accordance 
with Sections 405.7.1 and 405.7.2. 

405.7. 1 Number of exits. Each floor level shall be provided 
with a minimum of two exits. Where compartmentation is 
required by Section 405.4, each compartment shall have a 



44 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



minimum of one exitand shall also have an exit access door- 
way into the adjoining compartment. 

405.7.2 Smokeproof enclosure. Every required stairway 
serving floor levels more than 30 feet (9144 mm) below the 
finished floor of its level of exit discharge shall comply with 
the requirements for a smokeproof enclosure as provided in 
Section 1022.9. 

[F] 405.8 Standby power. A standby power system complying 
with Chapter 27 shall be provided standby power loads speci- 
fied in Section 405.8.1. 

[Fj 405.8.1 Standby power loads. The following loads are 
classified as standby power loads: 

1. Smoke control system. 

2. Ventilation and automatic fire detection equipment 
for smokeproof enclosures. 

3. Fire pumps. 

Standby power shall be provided for elevators in accor- 
dance with Section 3003. 

[F] 405.8.2 Pick-up time. The standby power system shall 
pick up its connected loads within 60 seconds of failure of 
the normal power supply. 

[F] 405.9 Emergency power. An emergency power system 
complying with Chapter 27 shall be provided for emergency 
power loads specified in Section 405 .9.1. 

[F] 405.9.1 Emergency power loads. The following loads 
are classified as emergency power loads: 

1. Emergency voicelalarm communications systems. 

2. Fire alarm systems. 

3. Automatic fire detection systems. 

4. Elevator car lighting. 

5. Means of egress and exit sign illumination as required 
by Chapter 10. 

[F] 405.10 Standpipe system. The underground building shall 
be equipped throughout with a standpipe system in accordance 
with Section 905. 



SECTION 406 
MOTOR-VEHICLE-RELATED OCCUPANCIES 

406.1 Private garages and carports. 

406.1.1 Classification. Buildings or parts of buildings clas- 
sified as Group U occupancies because of the use or charac- 
ter of the occupancy shall not exceed 1,000 square feet (93 
m 2 ) in area or one story m height except as provided in Sec- 
tion 406.1.2. Any building or portion thereof that exceeds 
the limitations specified in this section shall be classified in 
the occupancy group other than Group U that it most nearly 
resembles. 

406.1.2 Area increase. Group U occupancies used for the 
storage of private or pleasure-type motor vehicles where no 
repair work is completed or fuel is dispensed are permitted 



to be 3,000 square feet (279 m 2 ) when the following provi- 
sions are met: 

1. For a mixed occupancy building, the exterior walland 
opening protection for the Group U portion of the 
building shall be as required for the major occupancy 
of the building. For such a mixed occupancy building, 
the allowable floor area of the building shall be as per- 
mitted for the major occupancy contained therein. 

2. For a building containing only a Group U occupancy, 
the exterior wall shall not be required to have a 
fire-resistance rating and the area of openings shall 
not be limited when the fire separation distance is 5 
feet (1524 mm) or more. 

More than one 3, 000- square-foot (279 m^ Group U 
occupancy shall be permitted to be in the same building, 
provided each 3,000-square-foot (279 m 2 ) area is separated 
by fire walls complying with Section 706. 

406.1.3 Garages and carports. Carports shall be open on at 
least two sides. Carport floor surfaces shall be of approved 
noncombustible material. Carports not open on at least two 
sides shall be considered a garage and shall comply with the 
provisions of this section for garages. 

Exception: Asphalt surfaces shall be permitted at 
ground level in carports . 

The area of floor used for parking of automobiles or other 
vehicles shall be sloped to facilitate the movement of liquids 
to a drain or toward the main vehicle entry doorway. 

406.1.4 Separation. Separations shall comply with the fol- 
lowing: 

1. The private garage shall be separated from the dwell- 
ing unit and its attic area by means of a minimum 
liz-inch (12.7 mm) gypsum board applied to the 
garage side. Garages beneath habitable rooms shall be 
separated from all habitable rooms above by not less 
than a sis-inch (15.9 mm) Type X gypsum board or 
equivalent. Door openings between a private garage 
and the dwelling unit shall be equipped with either 
solid wood doors or solid or honeycomb core steel 
doors not less than 1 3 / s inches (34.9 mm) thick, or 
doors in compliance with Section 715.4.3. Openings 
from a private garage directly into a room used for 
sleeping purposes shall not be permitted. Doors shall 
be self-closing and self-latching. 

2. Ducts in a private garage and ducts penetrating the 
walls or ceilings separating the dwelling unit from the 
garage shall be constructed of a minimum 0.019-inch 
(0.48 mm) sheet steel and shall have no openings into 
the garage. 

3. A separation is not required between a Group R-3 and 
U carport, provided the carport is entirely open on two 
or more sides and there are not enclosed areas above . 

406.1.5 Automatic garage door openers. Automatic 
garage door openers, if provided, shall be listed in accor- 
dance with UL 325. 



i 



2009 INTERNATIONAL BUILDING CODE® 



45 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



406.2 Parking garages. 

406.2.1 Classification. Parking garages shall be classified 
as either open, as defined in Section 406.3, or enclosed and 
shall meet the appropriate criteria in Section 406.4. Also see 
Section 509 for special provisions for parking garages. 

406.2.2 Clear height. The clear height of each floor level in 
vehicle and pedestrian traffic areas shall not be less than 7 
feet (2134 mm). Vehicle and pedestrian areas accommodat- 
ing van-accessible parking required by Section 1 106.5 shall 
conform to ICC A 117.1. 

406.2.3 Guards. Guards shall be provided in accordance 
with Section 1013. Guards serving as vehicle barrier sys- 
tems shall comply with Sections 406.2.4 and 1013. 

406.2.4 Vehicle barrier systems. Vehicle barrier systems 
not less than 2 feet 9 inches (835 mm) high shall be placed at 
the end of drive lanes, and at the end of parking spaces 
where the vertical distance to the ground or surface directly 
below is greater than 1 foot (305 mm). Vehicle barrier sys- 
tems shall comply with the loading requirements of Section 
1607.7.3. 

Exception: Vehicle storage compartments in a mechani- 
cal access parking garage. 

406.2.5 Ramps. Vehicle ramps shall not be considered as 
required exits unless pedestrian facilities are provided. 
Vehicle ramps that are utilized for vertical circulation as 
well as for parking shall not exceed a slope of 1: 15 (6.67 
percent). 

406.2.6 Floor surface. Parking surfaces shall be of concrete 
or similar noncombustible and nonabsorbent materials. 

The area of floor used for parking of automobiles or other 
vehicles shall be sloped to facilitate the movement of liquids 
to a drain or toward the main vehicle entry doorway. 

Exceptions: 

1. Asphalt parking surfaces shall be permitted at 
ground level. 

2. Floors of Group S-2 parking garages shall not be 
required to have a sloped surface. 

406.2.7 Mixed occupancy separation. Parking garages 
shall be separated from other occupancies in accordance 
with Section 508.1. 

406.2.8 Special hazards. Connection of a parking garage 
with any room in which there is a fuel-fired appliance shall 
be by means of a vestibule providing a two-doorway separa- 
tion. 

Exception: A single door shall be allowed provided the 
sources of ignition in the appliance are at least 18 inches 
(457 mm) above the floor. 

406.2.9 Attached to rooms. Openings from a parking 
garage directly into a room used for sleeping purposes shall 
not be permitted. 



406.3 Open parking garages. 

406.3.1 Scope. Except where specific provisions are made 
in Sections 406.3.2 through 406.3.13, other requirements of 
this code shall apply. 

406.3.2 Definitions. The following words and terms shall, 
for the purposes of this chapter and as used elsewhere in this 
code, have the meanings shown herein. 

MECHANICAL- ACCESS OPEN PARKING GARAGES. 

Open parking garages employing parking machines, lifts, 
elevators or other mechanical devices for vehicles moving 
from and to street level and in which public occupancy is 
prohibited above the street level. 

OPEN PARKING GARAGE. A structure or portion of a 
structure with the openings as described in Section 
406.3.3.1 on two or more sides that is used for the parking or 
storage of private motor vehicles as described in Section 
406.3.4. 

RAMP-ACCESS OPEN PARKING GARAGES. Open 
parking garages employing a series of continuously rising 
floors or a series of interconnecting ramps between floors 
permitting the movement of vehicles under their own power 
from and to the street level. 

406.3.3 Construction. Open parking garages shall be of 
Type I, II or IV construction. Open parking garages shall 
meet the design requirements of Chapter 16. For vehicle 
barrier systems, see Section 406.2.4. 

406.3.3.1 Openings. For natural ventilation purposes, 
the exterior side of the structure shall have uniformly dis- 
tributed openings on two or more sides. The area of such 
openings in exterior walls on a tier must be at least 20 
percent of the total perimeter wall area of each tier. The 
aggregate length of the openings considered to be pro- 
viding natural ventilation shall constitute a minimum of 
40 percent of the perimeter of the tier. Interior walls shall 
be at least 20 percent open with uniformly distributed 
openings. 

Exception: Openings are not required to be distrib- 
uted over 40 percent of the building perimeter where 
the required openings are uniformly distributed over 
two opposing sides of the building. 

406.3.4 Uses. Mixed uses shall be allowed in the same 
building as an openparking garage subject to the provisions 
of Sections 402.7.1, 406.3.13, 508.1, 509.3, 509.4 and 
509.7. 

406.3.5 Area and height. Area and height of openparking 
garages shall be limited as set forth in Chapter 5 for Group 
S-2 occupancies and as further provided for in Section 
508.1. 

406.3.5.1 Single use. When the open parking garage is 
used exclusively for the parking or storage of private 
motor vehicles, with no other uses in the building, the 
area and height shall be permitted to comply with Table 



46 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



406.3.5, along with increases allowed by Section 
406.3.6. 

Exception: The grade-level tier is permitted to con- 
tain an office, waiting and toilet rooms having a total 
combined area of not more than 1,000 square feet (93 
m 2 ). Such area need not be separated from the open 
parking garage. 

In open parking garages having a spiral or sloping 
floor, the horizontal projection of the structure at any 
cross section shall not exceed the allowable area per 
parking tier. In the case of an open parking garage hav- 
ing a continuous spiral floor, each 9 feet 6 inches (2896 
mm) of height, or portion thereof, shall be considered a 
tier. 

The clear height of a parking tier shall not be less than 
7 feet (2134 mm), except that a lower clear height is per- 
mitted in mechanical-access open parking garages 
where approvedby the building official. 

406.3.6 Area and height increases. The allowable area and 
height of open parking garages shall be increased in accor- 
dance with the provisions of this section. Garages with sides 
open on three-fourths of the building's perimeter are permit- 
ted to be increased by 25 percent in area and one tier in 
height. Garages with sides open around the entire building's 
perimeter are permitted to be increased by 50 percent in area 
and one tier in height. For a side to be considered open under 
the above provisions, the total area of openings along the 
side shall not be less than 50 percent of the interior area of 
the side at each tier and such openings shall be equally dis- 
tributed along the length of the tier. 

Allowable tier areas in Table 406.3.5 shall be increased 
for open parking garages constructed to heights less than 
the table maximum. The gross tier area of the garage shall 
not exceed that permitted for the higher structure. At least 
three sides of each such larger tier shall have continuous 
horizontal openings not less than 30 inches (762 mm) in 
clear height extending for at least 80 percent of the length of 
the sides and no part of such larger tier shall be more than 
200 feet (60 960 mm) horizontally from such an opening. In 
addition, each such opening shall face a street or y a rd acces- 
sible to a street with a width of at least 30 feet (9144 mm) for 
the full length of the opening, and standpipes shall be pro- 
vided in each such tier. 



Open parking garages of Type II construction, with all 
sides open, shall be unlimited in allowable area where the 
bUilding height does not exceed 75 feet (22 860 mm). For a 
side to be considered open, the total area of openings along 
the side shall not be less than 50 percent of the interior area 
of the side at each tier and such openings shall be equally 
distributed along the length of the tier. All portions of tiers 
shall be within 200 feet (60 960 mm) horizontally from such 
openings or other natural ventilation openings as defined in 
Section 406.3.3.1. These openings shall be permitted to be 
provided in courts with a minimum dimension of 20 feet 
(6096 mm) for the full width of the openings. 

406.3.7 Fire separation distance. Exterior walls and open- 
ings in exterior walls shall comply with Tables 601 and 602. 
The distance to an adjacent lot line shall be determined in 
accordance with Table 602 and Section 705. 

406.3.8 Means of egress. Where persons other than parking 
attendants are permitted, open parking garages shall meet 
the means of egress requirements of Chapter 10. Where no 
persons other than parking attendants are permitted, there 
shall not be less than two 36-inch-wide (914 mm) exit stair- 
ways. Lifts shall be permitted to be installed for use of 
employees only, provided they are completely enclosed by 
noncombustible materials. 

406.3.9 Standpipes. Standpipes shall be installed where 
required by the provisions of Chapter 9. 

406.3.10 Sprinkler systems. Where required by other pro- 
visions of this code, automatic sprinkler systems and 
standpipes shall be installed in accordance with the provi- 
sions of Chapter 9. 

406.3.11 Enclosure of vertical openings. Enclosure shall 
not be required for vertical openings except as specified in 
Section 406.3.8. 

406.3.12 Ventilation. Ventilation, other than the percentage 
of openings specified in Section 406.3.3.1, shall not be 
required. 

406.3.13 Prohibitions. The following uses and alterations 
are not permitted: 

1. Vehicle repair work. 

2. Parking of buses, trucks and similar vehicles. 



TABLE 406.3.5 
OPEN PARKING GARAGES AREA AND HEIGHT 



TYPE OF CONSTRUCTION 


AREA PER TIER 
(square feet) 


HEIGHT (in tiers) 


Ramp access 


Mechanical access 


Automatic sprinkler system 


No 


Yes 


IA 


Unlimited 


Unlimited 


Unlimited 


Unlimited 


IB 


Unlimited 


12 tiers 


12 tiers 


18 tiers 


nA 


50,000 


10 tiers 


10 tiers 


15 tiers 


1IB 


50,000 


8 tiers 


8 tiers 


12 tiers 


IV 


50,000 


4 tiers 


4 tiers 


4 tiers 



For 51: 1 square foot = 0.0929 i 



2009 INTERNATIONAL BUILDING CODE® 



47 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



3. Partial or complete closing of required openings in 
exterior walls by tarpaulins or any other means. 

4. Dispensing of fuel. 

406.4 Enclosed parking garages. 

406.4.1 Heights and areas. Enclosed vehicle parking 
garages and portions thereof that do not meet the definition 
of open parking garages shall be limited to the allowable 
heights and areas specified in Table 503 as modified by Sec- 
tions 504, 506 and 507. Roof parking is permitted. 

406.4.2 Ventilation. A mechanical ventilation system shall 
be provided in accordance with the International Mechani- 
cal Code. 

406.5 Motor fuel-dispensing facilities. 

406.5.1 Construction. Motor fuel-dispensing facilities 
shall be constructed in accordance with the International 
Fire Code and Sections 406.5.1 through 406.5.3. 

406.5.2 Vehicle fueling pad. The vehicle shall be fueled on 
noncoated concrete or other approve d paving material hav- 
ing a resistance not exceeding 1 megohm as determined by 
the methodology in EN 1081. 

406.5.3 Canopies. Canopies under which fuels are dis- 
pensed shall have a clear, unobstructed height of not less 
than 13 feet 6 inches (4115 mm) to the lowest projecting ele- 
ment in the vehicle drive-through area. Canopies and their 
supports over pumps shall be of noncombustible materials, 
fire-retardant-treated wood complying with Chapter 23, 
wood of Type IV sizes or of construction providing I-hour 
fire resistance. Combustible materials used in or on a can- 
opy shall comply with one of the following: 

1. Shielded from the pumps by a noncombustible ele- 
ment of the canopy, or wood of Type IV sizes; 

2. Plastics covered by aluminum facing having a mini- 
mum thickness of 0.010 inch (0.30 mm) or corro- 
sion-resistant steel having a minimum base metal 
thickness of 0.016 inch (0.41 mm). The plastic shall 
have a flame spread index of 25 or less and a 
smoke-developed index of 450 or less when tested in 
the form intended for use in accordance with ASTM E 
84 or UL 723 and a self-ignition temperature of 650°F 
(343°C) or greater when tested in accordance with 
ASTM D 1929; or 

3. Panels constructed of light- transmitting plastic mate- 
rials shall be permitted to be installed in canopies 
erected over motor vehicle fuel-dispensing station 
fuel dispensers, provided the panels are located at 
least 10 feet (3048 mm) from any building on the 
same lot and face yards or streets not less than 40 feet 
(12 192 mm) in width on the other sides. The aggre- 
gate areas of plastics shall not exceed 1,000 square 
feet (93 m 2 ) . The maximum area of any individual 
panel shall not exceed 100 square feet (9.3 m 2 ). 

406.5.3. 1 Canopies used to support gaseous hydrogen 
systems. Canopies that are used to shelter dispensing 
operations where flammable compressed gases are 



located on the roof of the canopy shall be in accordance 
with the following: 

1. The canopy shall meet or exceed Type I construc- 
tion requirements. 

2. Operations located under canopies shall be limited 
to refueling only. 

3. The canopy shall be constructed in a manner that 
prevents the accumulation of hydrogen gas. 

406.6 Repair garages. 

406.6.1 General. Repair garages shall be constructed in 
accordance with the International Fire Code and Sections 

406.6.1 through 406.6.6. This occupancy shall not include 
motor fuel-dispensing facilities, as regulated in Section 
406.5. 

406.6.2 Mixed uses. Mixed uses shall be allowed in the 
same building as a repair garage subject to the provisions of 
Section 508.1. 

406.6.3 Ventilation. Repair garages shall be mechanically 
ventilated in accordance with the International Mechanical 
Code. The ventilation system shall be controlled at the 
entrance to the garage. 

406.6.4 Floor surface. Repair garage floors shall be of con- 
crete or similar noncombustible and nonabsorbent materi- 
als. 

Exception: Slip-resistant, nonabsorbent, interior floor 
finishes having a critical radiant flux not more than 0.45 
W/cm 2 as determined by NFPA 253, shall be permitted. 

406.6.5 Heating equipment. Heating equipment shall be 
installed in accordance with the International Mechanical 
Code. 

\F] 406.6.6 Gas detection system. Repair garages used for 
repair of vehicles fueled by nonodorized gases, such as 
hydrogen and nonodorized LNG, shall be provided with an 
app roved flammable gas detection system. 

[F] 406.6.6.1 System design. The flammable gas detec- 
tion system shall be calibrated to the types of fuels or 
gases used by vehicles to be repaired. The gas detection 
system shall be designed to activate when the level of 
flammable gas exceeds 25 percent of the lower explosive 
limit. Gas detection shall also be provided in lubrication 
or chassis repair pits of garages used for repairing 
nonodorized LNG-fueled vehicles. 

\F] 406.6.6.2 Operation. Activation of the gas detection 
system shall result in all of the following: 

1. Initiation of distinct audible and visual alarm sig- 
nals in the repair garage. 

2. Deactivation of all heating systems located in the 
repair garage. 

3. Activation of the mechanical ventilation system, 
where the system is interlocked with gas detection. 

[Fj 406.6.6.3 Failure of the gas detection system. Fail- 
ure of the gas detection system shall result in the deacti- 
vation of the heating system, activation of the 
mechanical ventilation system when the system is inter- 



48 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



I 



locked with the gas detection system and cause a trouble 
signal to sound in an approve d location. 



SECTION 407 
GROUP 1-2 

407.1 General. Occupancies in Group 1-2 shall comply with 
the provisions of Sections 407.1 through 407.9 and other appli- 
cable provisions of this code. 

407.2 Corridors. Corridors in occupancies in Group 1-2 shall 
be continuous to the exits and separated from other areas in 
accordance with Section 407.3 except spaces conforming to 
Sections 407.2.1 through 407.2.4. 

407.2.1 Waiting and similar areas. Waiting areas and sim- 
ilar spaces constructed as required for corridors shall be 
permitted to be open to a corridor, only where all of the fol- 
lowing criteria are met: 

1. The spaces are not occupied for patient sleeping units, 
treatment rooms, hazardous or incidental accessory 
occupancies in accordance with Section 508.2. 

2. The open space is protected by an automatic fire 
detection system installed in accordance with Section 
907. 

3. The corridors onto which the spaces open, in the 
same smoke compartment, are protected by an auto- 
matic fire detection system installed in accordance 
with Section 907, or the smoke compartment in which 
the spaces are located is equipped throughout with 
quick-response sprinklers in accordance with Section 
903.3.2. 

4. The space is arranged so as not to obstruct access to 
the required exits. 

401.22 Nurses' stations. Spaces for doctors' and nurses' 
charting, communications and related clerical areas shall be 
permitted to be open to the corridor, when such spaces are 
constructed as required for corridors. 

407.2.3 Mental health treatment areas. Areas wherein 
mental health patients who are not capable of self-preserva- 
tion are housed, or group meeting or multipurpose therapeu- 
tic spaces other than incidental accessory occupancies in 
accordance with Section 508.2.5, under continuous super- 
vision by facility staff, shall be permitted to be open to the 
corridor, where the following criteria are met: 

1. Each area does not exceed 1,500 square feet (140 m 2 ). 

2. The area is located to permit supervision by the facil- 
ity staff. 

3. The area is arranged so as not to obstruct any access to 
the required exits. 

4. The area is equipped with an automatic fire detection 
system installed in accordance with Section 907.2. 

5. Not more than one such space is permitted in anyone 
smoke compartment. 

6. The walls and ceilings of the space are constructed as 
required for corridors. 



407.2.4 Gift shops. Gift shops less than 500 square feet 
(46.5 m 2 ) in area shall be permitted to be open to the corri- 
dor provided the gift shop and storage areas are fully 
sprinklered and storage areas are protected in accordance 
with Section 508.2.5. 

407.3 Corridor walls. Co rridor walls shall be constructed as 
smoke partitions in accordance with Section 711. 

407.3.1 Corridor doors. Corridor doors, other than those 
in a wall required to be rated by Section 508.2.5 or for the 
enclosure of a vertical opening or an exit, shall not have a 
required fire protection rating and shall not be required to be 
equipped with self-closing or automatic-closing devices, 
but shall provide an effective barrier to limit the transfer of 
smoke and shall be equipped with positive latching. Roller 
latches are not permitted. Other doors shall conform to Sec- 
tion 715.4. 

407.3.2 Locking devices. Locking devices that restrict 
access to the patient room from the corridor, and that are 
operable only by staff from the corridor side, shall not 
restrict the means of egress from the patient room except for 
patient rooms in mental health facilities. 

407.4 Smoke barriers. Smoke barriers shall be provided to 
subdivide every story used by patients for sleeping or treatment 
and to divide other stories with an occupant loadof 50 or more 
persons, into at least two smoke compartments. Such stories 
shall be divided into smoke compartments with an area of not 
more than 22,500 square feet (2092 m 2 ) and the travel distance 
from any point in a smoke compartment to a smoke barrier 
door shall not exceed 200 feet (60 960 mm). The smoke barrier 
shall be in accordance with Section 710. 

407 .4. 1 Refuge area. At least 30 net square feet (2.8 m 2 ) per 
patient shall be provided within the aggregate area of corri- 
dors, patient rooms, treatment rooms, lounge or dining 
areas and other low-hazard areas on each side of each smoke 
barrier. On floors not housing patients confined to a bed or 
litter, at least 6 net square feet (0.56 m 2 ) per occupant shall 
be provided on each side of each smoke barrier -for the total 
number of occupants in adjoining smoke compartments. 

407.4.2 Independent egress. A means of egress shall be 
provided from each smoke compartment created by smoke 
barriers without having to return through the smoke com- 
partment from which means of egress originated. 

407.4.3 Horizontal assemblies. Horizontal assemblies 
supporting smoke barriers required by this section shall be 
designed to resist the movement of smoke and shall comply 
with Section 712.9. 

\F] 407.5 Automatic sprinkler system. Smoke compartments 
containing patient sleeping units shall be equipped throughout 
with an automatic sprinkler system in accordance with Section 
903.3.1.1. The smoke compartments shall be equipped with 
approved quick-response or residential sprinklers in accor- 
dance with Section 903.3.2. 

\F] 407.6 Fire alarm system. A fire alarm system shall be pro- 
vided in accordance with Section 907.2.6. 

[F] 407.7 Automatic fire detection. Corridors in nursing 
homes (both intermediate care and skilled nursing facilities), 



2009 INTERNATIONAL BUILDING CODE® 



49 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



1 



detoxification facilities and spaces permitted to be open to the 
corridorsby Section 407.2 shall be equipped with an automatic 
fire detection system. Hospitals shall be equipped with smoke 
detection as required in Section 407.2. 

Exceptions: 

1. Corridor smoke detection is not required where 
patient sleeping units are provided with smoke detec- 
tors that comply with UL 268. Such detectors shall 
provide a visual display on the corridor side of each 
patient sleeping unit and an audible and visual alarm 
at the nursing station attending each unit. 

2. Corridor smoke detection is not required where 
patient sleeping unit doors are equipped with auto- 
matic door-closing devices with integral smoke 
detectors on the unit sides installed in accordance 
with their listing, provided that the integral detectors 
perform the required alerting function. 

407.8 Secured yards. Grounds are permitted to be fenced and 
gates therein are permitted to be equipped with locks, provided 
that safe dispersal areas having 30 net square feet (2.8 m 2 ) for 
bed and litter patients and 6 net square feet (0.56 m 2 ) for ambu- 
latory patients and other occupants are located between the 
building and the fence . Such provided safe dispersal areas shall 
not be located less than 50 feet (15 240 mm) from the building 
they serve. 

407.9 Hyperbaric facilities. Hyperbaric facilities in Group 1-2 
occupancies shall meet the requirements contained in Chapter 
20ofNFPA99. 



SECTION 408 
GROUP 1-3 

408.1 General. Occupancies in Group 1-3 shall comply with 
the provisions of Sections 408.1 through 408.10 and other 
applicable provisions of this code (see Section 308.4). 

408.1.1 Definition. The following words and terms shall, 
for the purposes of this chapter and as used elsewhere in this 
code, have the meanings shown herein. 

CELL. A room within a housing unit in a detention or cor- 
rectional facility used to confine inmates or prisoners. 

CELL TIER. Levels of cells vertically stacked above one 
another within a housing unit. 

HOUSING UNIT. A dormitory or a group of cells with a 
common dayroom in Group 1-3. 

SALLYPORT. A security vestibule with two or more doors 
or gates where the intended purpose is to prevent continuous 
and unobstructed passage by allowing the release of only 
one door or gate at a time. 

408.2 Other occupancies. Buildings or portions of buildings 
in Group 1-3 occupancies where security operations necessitate 
the locking of required means of egress shall be permitted to be 
classified as a different occupancy. Occupancies classified as 
other than Group 1-3 shall meet the applicable requirements of 
this code for that occupancy provided provisions are made for 
the release of occupants at all times. 



Means of egress from detention and correctional occupan- 
cies that traverse other use areas shall, as a minimum, conform 
to requirements for detention and correctional occupancies. 

Exception: It is permissible to exit through a horizontal exit 
into other contiguous occupancies that do not conform to 
detention and correctional occupancy egress provisions but 
that do comply with requirements set forth in the appropri- 
ate occupancy, as long as the occupancy is not a Group H 
use. 

408.3 Means of egress. Except as modified or as provided for 
in this section, the provisions of Chapter 10 shall apply. 

408.3.1 Door width. Doors to resident sleeping units shall 
have a clear width of not less than 28 inches (711 mm). 

408.3.2 Sliding doors. Where doors in a means of egress are 
of the horizontal- sliding type, the force to slide the door to its 
fully open position shall not exceed 50 pounds (220 N) with a 
perpendicular force against the door of 50 pounds (220 N). 

408.3.3 Guard tower doors. A hatch or trap door not less 
than 16 square feet (610 m 2 ) in area through the floor and 
having minimum dimensions of not less than 2 feet (610 
mm) in any direction shall be permitted to be used as a por- 
tion of the means of egress from guard towers. 

408.3.4 Spiral stairways. Spiral stairways that conform to 
the requirements of Section 1009.9 are permitted for access 
to and between staff locations. 

408.3.5 Ship ladders. Ship ladders shall be permitted for 
egress from control rooms or elevated facility observation 
rooms in accordance with Section 1009.11. 

408.3.6 Exit discharge. Exits are permitted to discharge 
into a fenced or walled courtyard. Enclosed yards or courts 
shall be of a size to accommodate all occupants, a minimum 
of 50 feet (15 240 mm) from the building with a net area of 
15 square feet (1.4 m 2 ) per person. 

408.3.7 Sallyports. A sallyport shall be permitted in a 
means of egress where there are provisions for continuous 
and unobstructed passage through the sallyport during an 
emergency egress condition. 

408.3.8 Exit enclosures. One of the required exit enclo- 
sures in each building shall be permitted to have glazing 
installed in doors and interior walls at each landing level 
providing access to the enclosure, provided that the follow- 
ing conditions are met: 

1. The exit enclosure shall not serve more than four floor 
levels. 

2. Exit doors shall not be less than 3/4-hour fire door 
assemblies complying with Section 715.4 

3. The total area of glazing at each floor level shall not 
exceed 5,000 square inches (3 m 2 ) and individual pan- 
els of glazing shall not exceed 1,296 square inches 
(0.84 m 2 ). 

4. The glazing shall be protected on both sides by an 
automatic sprinkler system. The sprinkler system 
shall be designed to wet completely the entire surface 
of any glazing affected by fire when actuated. 



50 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



5. The glazing shall be in a gasketed frame and installed 
in such a manner that the framing system will deflect 
without breaking (loading) the glass before the sprin- 
kler system operates. 

6. Obstructions, such as curtain rods, drapery traverse 
rods, curtains, drapes or similar materials shall not be 
installed between the automatic sprinklers and the 
glazing. 

408.4 Locks. Egress doors are permitted to be locked in accor- 
dance with the applicable use condition. Doors from a refuge 
area to the exterior are permitted to be locked with a key in lieu 
of locking methods described in Section 408.4.1. The keys to 
unlock the exterior doors shall be available at all times and the 
locks shall be operable from both sides of the door. 

408.4.1 Remote release. Remote release of locks on doors 
in a means of egress shall be provided with reliable means of 
operation, remote from the resident living areas, to release 
locks on all required doors. In Occupancy Conditions 3 or 4, 
the arrangement, accessibility and security of the release 
mechanism(s) required for egress shall be such that with the 
minimum available staff at any time, the lock mechanisms 
are capable of being released within 2 minutes. 

Exception: Provisions for remote locking and unlocking 
of occupied rooms in Occupancy Condition 4 are not 
required provided that not more than 10 locks are neces- 
sary to be unlocked in order to move occupants from one 
smoke compartment to a refuge area within 3 minutes. 
The opening of necessary locks shall be accomplished 
with not more than two separate keys. 

408.4.2 Power-operated doors and locks. Power-operated 
sliding doors or power-operated locks for swinging doors 
shall be operable by a manual release mechanism at the 
door, and either emergency power or a remote mechanical 
operating release shall be provided. 

Exception: Emergency power is not required in facilities 
with 10 locks or less complying with the exception to 
Section 408.4.1. 

408.4.3 Redundant operation. Remote release, mechani- 
cally operated sliding doors or remote release, mechanically 
operated locks shall be provided with a mechanically oper- 
ated release mechanism at each door, or shall be provided 
with a redundant remote release control. 

408.4.4 Relock capability. Doors remotely unlocked under 
emergency conditions shall not automatically relock when 
closed unless specific action is taken at the remote location 
to enable doors to relock. 

408.5 Protection of vertical openings. Any vertical opening 
shall be protected by a shaft enclosure in accordance with Sec- 
tion 708, or shall be in accordance with Section 408.5.1. 



408.5.1 Floor openings. Openings in floors within a hous- 
ing unit are permitted without a shaft enclosure, provided all 
of the following conditions are met: 

1. The entire normally occupied areas so interconnected 
are open and unobstructed so as to enable observation 
of the areas by supervisory personnel; 

2. Means of egress capacity is sufficient for all occu- 
pants from all interconnected cell tiers and areas; 

3. The height difference between the floor levels of the 
highest and lowest cell tiers shall not exceed 23 feet 
(7010 mm); and 

4. Egress from any portion of the cell tier to an exit or 
exit access door shall not require travel on more than 
one additional floor level within the housing unit. 

408.5.2 Shaft openings in communicating floor levels. 

Where a floor opening is permitted between communicat- 
ing floor levels of a housing unit in accordance with Section 
408.5.1, plumbing chases serving vertically staked individ- 
ual cells contained with the housing unit shall be permitted 
without a shaft enclosure. 

408.6 Smoke barrier. Occupancies in Group 1-3 shall have 
smoke barriers complying with Sections 408.8 and 710 to 
divide every story occupied by residents for sleeping, or any 
other storyhaving an occupant loadof 50 or more persons, into 
at least two smoke compartments . 

Exception: Spaces having a direct exitto one of the follow- 
ing, provided that the locking arrangement of the doors 
involved complies with the requirements for doors at the 
smoke barrier for the use condition involved: 

1 . A public way. 

2. A building separated from the resident housing area 
by a 2-hour fire-resistance-rated assembly or 50 feet 
(15 240 mm) of open space. 

3. A secured yard or court having a holding space 50 
feet (15 240 mm) from the housing area that provides 
6 square feet (0.56 m 2 ) or more of refuge area per 
occupant, including residents, staff and visitors. 

408.6.1 Smoke compartments. The maximum number of 
residents in any smoke compartment shall be 200. The 
travel distance to a door in a smoke barrier from any room 
door required as exit access shall not exceed 150 feet (45 
720 mm). The travel distance to a door in a smoke barrier 
from any point in a room shall not exceed 200 feet (60 960 
mm). 

408.6.2 Refuge area. At least 6 net square feet (0.56 m 2 ) per 
occupant shall be provided on each side of each smoke bar- 
rier fox the total number of occupants in adjoining smoke 
compartments. This space shall be readily available wher- 
ever the occupants are moved across the smoke barrier'm a 
fire emergency. 



2009 INTERNATIONAL BUILDING CODE® 



51 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



1: 



408.6.3 Independent egress. A means of egress shall be 
provided from each smoke compartment created by smoke 
barriers without having to return through the smoke com- 
partment from which means of egress originates. 

408.7 Security glazing. In occupancies in Group 1-3, windows 
and doors in I-hour fire barriers constructed in accordance 
with Section 707, fire partitions constructed in accordance with 
Section 709 and smoke barriers constructed in accordance with 
Section 710 shall be permitted to have security glazing 
installed provided that the following conditions are met. 

1. Individual panels of glazing shall not exceed 1,296 
square inches (0.84 m 2 ). 

2. The glazing shall be protected on both sides by an auto- 
matic sprinkler system. The sprinkler system shall be 
designed to, when actuated, wet completely the entire 
surface of any glazing affected by fire. 

3. The glazing shall be in a gasketed frame and installed in 
such a manner that the framing system will deflect with- 
out breaking (loading) the glass before the sprinkler sys- 
tem operates. 

4. Obstructions, such as curtain rods, drapery traverse rods, 
curtains, drapes or similar materials shall not be installed 
between the automatic sprinklers and the glazing. 

408.8 Subdivision of resident housing areas. Sleeping areas 
and any contiguous day room, group activity space or other 
common spaces where residents are housed shall be separated 
from other spaces in accordance with Sections 408.8.1 through 
408.8.4. 

408.8.1 Occupancy Conditions 3 and 4. Each sleeping 
area in Occupancy Conditions 3 and 4 shall be separated 
from the adjacent common spaces by a smoke-tight parti- 
tion where the travel distance from the sleeping area 
through the common space to the co rri do r exceeds 50 feet 
(15 240 mm). 

408.8.2 Occupancy Condition 5. Each sleeping area in 
Occupancy Condition 5 shall be separated from adjacent 
sleeping areas, corridors and common spaces by a smoke- 
tight partition. Additionally, common spaces shall be sepa- 
rated from the corridor by a smoke-tight partition. 

408.8.3 Openings in room face. The aggregate area of 
openings in a solid sleeping room face in Occupancy Condi- 
tions 2,3,4 and 5 shall not exceed 120 square inches (77 419 
mm 2 ). The aggregate area shall include all openings includ- 
ing door undercuts, food passes and grilles. Openings shall 
be not more than 36 inches (914 mm) above the floor. In 
Occupancy Condition 5, the openings shall be closeable 
from the room side. 

408.8.4 Smoke-tight doors. Doors in openings in partitions 
required to be smoke tight by Section 408.8 shall be sub- 
stantial doors, of construction that will resist the passage of 
smoke. Latches and door closures are not required on cell 
doors. 

408.9 Windowless buildings. For the purposes of this section, 
a windowless building or portion of a building is one with 
nonopenable windows, windows not readily breakable or with- 
out windows. Windowless buildings shall be provided with an 



engineered smoke control system to provide a tenable environ- 
ment for exiting from the smoke compartment in the area of fire 
origin in accordance with Section 909 for each windowless 
smoke compartment. 

[F] 408.10 Fire alarm system. A fire alarm system shall be 
provided in accordance with Section 907.2.6.3. 



SECTION 409 
MOTION PICTURE PROJECTION ROOMS 

409.1 General. The provisions of Sections 409.1 through 
409.5 shall apply to rooms in which ribbon-type cellulose ace- 
tate or other safety film is utilized in conjunction with electric 
arc, xenon or other light- source projection equipment that 
develops hazardous gases, dust or radiation. Where cellulose 
nitrate film is utilized or stored, such rooms shall comply with 
NFPA40. 

409.1.1 Projection room required. Every motion picture 
machine projecting film as mentioned within the scope of 
this section shall be enclosed in a projection room. Appurte- 
nant electrical equipment, such as rheostats, transformers 
and generators, shall be within the projection room or in an 
adjacent room of equivalent construction. 

409.2 Construction of projection rooms. Every projection 
room shall be of permanent construction consistent with the 
construction requirements for the type of building in which the 
projection room is located. Openings are not required to be pro- 
tected. 

The room shall have a floor area of not less than 80 square 
feet (7.44 m 2 ) for a single machine and at least 40 square feet 
(3.7 m 2 ) for each additional machine. Each motion picture pro- 
jector, floodlight, spotlight or similar piece of equipment shall 
have a clear working space of not less than 30 inches by 30 
inches (762 mm by 762 mm) on each side and at the rear 
thereof, but only one such space shall be required between two 
adjacent projectors. The projection room and the rooms appur- 
tenant thereto shall have a ceiling height of not less than 7 feet 6 
inches (2286 mm). The aggregate of openings for projection 
equipment shall not exceed 25 percent of the area of the wall 
between the projection room and the auditorium. Openings 
shall be provided with glass or other approvedmaterial, so as to 
close completely the opening. 

409.3 Projection room and equipment ventilation. Ventila- 
tion shall be provided in accordance with the International 
Mechanical Code. 

409.3.1 Supply air. Each projection room shall be provided 
with adequate air supply inlets so arranged as to provide 
well-distributed air throughout the room. Air inlet ducts 
shall provide an amount of air equivalent to the amount of 
air being exhausted by projection equipment. Air is permit- 
ted to be taken from the outside; from adjacent spaces 
within the building, provided the volume and infiltration 
rate is sufficient; or from the building air-conditioning sys- 
tem, provided it is so arranged as to provide sufficient air 
when other systems are not in operation. 

409.3.2 Exhaust air. Projection rooms are permitted to be 
exhausted through the lamp exhaust system. The lamp 



52 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



exhaust system shall be positively interconnected with the 
lamp so that the lamp will not operate unless there is the 
required airflow. Exhaust air ducts shall terminate at the 
exterior of the building in such a location that the exhaust air 
cannot be readily recirculated into any air supply system. 
The projection room ventilation system is permitted to also 
serve appurtenant rooms, such as the generator and rewind 
rooms. 

409.3.3 Projection machines. Each projection machine 
shall be provided with an exhaust duct that will draw air 
from each lamp and exhaust it directly to the outside of the 
building. The lamp exhaust is permitted to serve to exhaust 
air from the projection room to provide room air circulation. 
Such ducts shall be of rigid materials, except for a flexible 
connector approvedfor the purpose. The projection lamp or 
projection room exhaust system, or both, is permitted to be 
combined but shall not be interconnected with any other 
exhaust or return system, or both, within the building. 

409.4 Lighting control. Provisions shall be made for control 
of the auditorium lighting and the means of egress lighting sys- 
tems of theaters from inside the projection room and from at 
least one other convenient point in the building. 

409.5 Miscellaneous equipment. Each projection room shall 
be provided with rewind and film storage facilities. 



SECTION 410 
STAGES AND PLATFORMS 

410.1 Applicability. The provisions of Sections 410.1 through 
410.7 shall apply to all parts of buildings and structures that 
contain stages or platforms and similar appurtenances as herein 
defined. 

410.2 Definitions. The following words and terms shall, for the 
purposes of this section and as used elsewhere in this code, 
have the meanings shown herein. 

FLY GALLERY. A raised floor area above a stage from which 
the movement of scenery and operation of other stage effects 
are controlled. 

GRIDIRON. The structural framing over a stage supporting 
equipment for hanging or flying scenery and other stage 
effects. 

PINRAIL. A rail on or above a stage through which belaying 
pins are inserted and to which lines are fastened. 

PLATFORM. A raised area within a building used for wor- 
ship, the presentation of music, plays or other entertainment; 
the head table for special guests; the raised area for lecturers 
and speakers ; boxing and wrestling rings; theater-in-the-round 
stages; and similar purposes wherein there are no overhead 
hanging curtains, drops, scenery or stage effects other than 
lighting and sound. A temporary platform is one installed for 
not more than 30 days. 

PROSCENIUM WALL. The wall that separates the stage 
from the auditorium or assembly seating area. 

STAGE. A space within a building utilized for entertainment 
or presentations, which includes overhead hanging curtains, 
drops, scenery or stage effects other than lighting and sound. 



410.3 Stages. Stage construction shall comply with Sections 
410.3.1 through 410.3.7. 

410.3.1 Stage construction. Stages shall be constructed of 
materials as required for floors for the type of construction 
of the building in which such stages are located. 

Exceptions: 

1. Stages of Type 1IB or IV construction with a nomi- 
nal 2-inch (51 mm) wood deck, provided that the 
stage is separated from other areas in accordance 
with Section 410.3.4. 

2. In buildings of Types IIA, I1IA and VA construc- 
tion, a fire-resistance-rated floor is not required, 
provided the space below the stage is equipped 
with an automatic fire-extinguishing system in 
accordance with Section 903 or 904. 

3. In all types of construction, the finished floor shall be 
constructed of wood or approved noncombustible 
materials. Openings through stage floors shall be 
equipped with tight-fitting, solid wood trap doors 
with approved safety locks. 

410.3.1.1 Stage height and area. Stage areas shall be 
measured to include the entire performance area and 
adjacent backstage and support areas not separated from 
the performance area by fire-resistance-rated construc- 
tion. Stage height shall be measured from the lowest 
point on the stage floor to the highest point of the roof or 
floor deck above the stage. 

410.3.2 Galleries, gridirons, catwalks and pinrails. 
Beams designed only for the attachment of portable or fixed 
theater equipment, gridirons, galleries and catwalks shall be 
constructed of approved materials consistent with the 
requirements for the type of construction of the building; 
and a fire-resistance rating shall not be required. These 
areas shall not be considered to be floors, stories, mezza- 
nines or levels in applying this code. 

Exception: Floors of fly galleries and catwalks shall be 
constructed of any approved material. 

410.3.3 Exterior stage doors. Where protection of open- 
ings is required, exterior exit doors shall be protected with 
fire door assemblies that comply with Section 715 . Exterior 
openings that are located on the stage for means of egress or 
loading and unloading purposes, and that are likely to be 
open during occupancy of the theater, shall be constructed 
with vestibules to prevent air drafts into the auditorium. 

410.3.4 Proscenium wall. Where the stage height is greater 
than 50 feet (15 240 mm), all portions of the stage shall be 
completely separated from the seating area by a proscenium 
wall with not less than a 2-hour fire-resistance rating 
extending continuously from the foundation to the roof. 

410.3.5 Proscenium curtain. Where a proscenium wall is 
required to have a fire-resistance rating, the stage opening 
shall be provided with a fire curtain complying with NFPA 
80 or an approved water curtain complying with Section 
903.3.1.1 or, in facilities not utilizing the provisions of 
smoke-protected assembly seating in accordance with Sec- 
tion 1028.6.2, a smoke control system complying with Sec- 



2009 INTERNATIONAL BUILDING CODE® 



53 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



I 



tion 909 or natural ventilation designed to maintain the 
smoke level at least 6 feet (1829 mm) above the floor of the 
means of egress. 

410.3.6 Scenery. Combustible materials used in sets and 
scenery shall meet the fire propagation performance criteria 
ofNFPA 701, in accordance with Section 806 and the Inter- 
national Fire Code. Foam plastics and materials containing 
foam plastics shall comply with Section 2603 and the Inter- 
national Fire Code. 

410.3.7 Stage ventilation. Emergency ventilation shall be 
provided for stages larger than 1,000 square feet (93 m 2 ) in 
floor area, or with a stage height greater than 50 feet (15 240 
mm). Such ventilation shall comply with Section 410.3.7.1 
or 410.3.7.2. 

410.3.7.1 Roof vents. Two or more vents constructed to 
open automatically by approved heat-activated devices 
and with an aggregate clear opening area of not less than 
5 percent of the area of the stage shall be located near the 
center and above the highest part of the stage area. Sup- 
plemental means shall be provided for manual operation 
of the ventilator. Curbs shall be provided as required for 
skylights in Section 2610.2. Vents shall be labeled. 

[F] 410.3.7.2 Smoke control. Smoke control in accor- 
dance with Section 909 shall be provided to maintain the 
smoke layer interface not less than 6 feet (1829 mm) 
above the highest level of the assembly seating or above 
the top of the proscenium opening where a proscenium 
wall is provided in compliance with Section 410.3.4. 

410.4 Platform construction. Permanent platforms shall be 
constructed of materials as required for the type of construction 
of the building in which the permanent platform is located. Per- 
manent platforms are permitted to be constructed of fire-retar- 
dant-treated woodfor Types I, II and IV construction where the 
platforms are not more than 30 inches (762 mm) above the 
main floor, and not more than one-third of the room floor area 
and not more than 3,000 square feet (279 m 2 ) in area. Where the 
space beneath the permanent platform is used for storage or any 
purpose other than equipment, wiring or plumbing, the floor 
assembly shall not be less than I-hour fire-resistance-rated 
construction. Where the space beneath the permanent platform 
is used only for equipment, wiring or plumbing, the underside 
of the permanent platform need not be protected. 

410.4.1 Temporary platforms. Platforms installed for a 
period of not more than 30 days are permitted to be con- 
structed of any materials permitted by the code. The space 
between the floor and the platform above shall only be used 
for plumbing and electrical wiring to platform equipment. 

410.5 Dressing and appurtenant rooms. Dressing and appur- 
tenant rooms shall comply with Sections 410.5.1 through 
410.5.3. 

410.5.1 Separation from stage. The stage shall be sepa- 
rated from dressing rooms, scene docks, property rooms, 
workshops, storerooms and compartments appurtenant to 
the stage and other parts of the building by fire barriers con- 
structed in accordance with Section 707 or horizontal 
assemblies constructed in accordance with Section 712, or 
both. The minimum fire-resistance rating shall be 2 hours 



for stage heights greater than 50 feet (15 240 mm) and 1 
hour for stage heights of 50 feet (15 240 mm) or less. 

410.5.2 Separation from each other. Dressing rooms, 
scene docks, property rooms, workshops, storerooms and 
compartments appurtenant to the stage shall be separated 
from each other by not less than I-hour fire barriers con- 
structed in accordance with Section 707 or horizontal 
assemblies constructed in accordance with Section 712, or 
both. 

410.5.3 Stage exits. At least one approvedmeans of egress 
shall be provided from each side of the stage and from each 
side of the space under the stage. At least one means of 
escape shall be provided from each fly gallery and from the 
gridiron. A steel ladder, alternating tread device or spiral 
stairway is permitted to be provided from the gridiron to a 
scuttle in the stage roof. 

[F] 410.6 Automatic sprinkler system. Stages shall be 
equipped with an automatic fire-extinguishing system in 
accordance with Chapter 9. Sprinklers shall be installed under 
the roof and gridiron and under all catwalks and galleries over 
the stage. Sprinklers shall be installed in dressing rooms, per- 
former lounges, shops and storerooms accessory to such 
stages. 

Exceptions: 

1. Sprinklers are not required under stage areas less than 
4 feet (1219 mm) in clear height that are utilized 
exclusively for storage of tables and chairs, provided 
the concealed space is separated from the adjacent 
spaces by not less than 5/ s -inch (15.9 mm) Type X 
gypsum board. 

2. Sprinklers are not required for stages 1,000 square 
feet (93 m 2 ) or less in area and 50 feet (15 240 mm) or 
less in height where curtains, scenery or other com- 
bustible hangings are not retractable vertically. Com- 
bustible hangings shall be limited to a single main 
curtain, borders, legs and a single backdrop. 

3. Sprinklers are not required within portable orchestra 
enclosures on stages. 

[F] 410.7 Standpipes. Standpipe systems shall be provided in 
accordance with Section 905. 



SECTION 411 
SPECIAL AMUSEMENT BUILDINGS 

411.1 General. Special amusement buildings having an occu- 
pant load of 50 or more shall comply with the requirements for 
the appropriate Group A occupancy and Sections 411.1 
through 411.8. Amusement buildings having an occupant load 
of less than 50 shall comply with the requirements for a Group 
B occupancy and Sections 411.1 through 411.8. 

Exception: Amusement buildings or portions thereof that 
are without walls or a roof and constructed to prevent the 
accumulation of smoke. 

For flammable decorative materials, see the International 
Fire Code. 



54 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



411.2 Definition. The following word and term shall, for the 
purpose of this section and as used elsewhere in this code, have 
the meaning shown herein. 

SPECIAL AMUSEMENT BUILDING. A special amuse- 
ment bUilding is any temporary or permanent building or por- 
tion thereof that is occupied for amusement, entertainment or 
educational purposes and that contains a device or system that 
conveys passengers or provides a walkway along, around or 
over a course in any direction so arranged that the means of 
egress path is not readily apparent due to visual or audio dis- 
tractions or is intentionally confounded or is not readily avail- 
able because of the nature of the attraction or mode of 
conveyance through the building or structure. 

[F] 411.3 Automatic fire detection. Special amusement build- 
ings shall be equipped with an automatic fire detection system 
in accordance with Section 907. 

[F] 411.4 Automatic sprinkler system. Special amusement 
buildings shall be equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1. Where 
the special amusement bUilding is temporary, the sprinkler 
water supply shall be of an approve d temporary means. 

Exception: Automatic sprinklers are not required where the 
total floor area of a temporary special amusement building 
is less than 1,000 square feet (93 m 2 ) and the travel distance 
from any point to an exit is less than 50 feet (15 240 mm). 

\F] 411.5 Alarm. Actuation of a single smoke detector, the 
automatic sprinkler system or other automatic fire detection 
device shall immediately sound an alarm at the building at a 
constantly attendedlocation from which emergency action can 
be initiated including the capability of manual initiation of 
requirements in Section 907.2.12.2. 

[F] 411.6 Emergency voice/alarm communications system. 
An emergency voice/alarm communications system shall be 
provided in accordance with Sections 907.2.12 and 907.5.2.2, 
which is also permitted to serve as a public address system and 
shall be audible throughout the entire special amusement 
bUilding. 

411.7 Exit marking. Exit signs shall be installed at the 
required exit or exit access doorways of amusement buildings 
in accordance with this section and Section 1011. Approved 
directional exit markings shall also be provided. Where mir- 
rors, mazes or other designs are utilized that disguise the path 
of egress travel such that they are not apparent, approved and 
listedlow-Ievel exit signs that comply with Section 101 1.4, and 
directional path markings listed in accordance with UL 1994, 
shall be provided and located not more than 8 inches (203 mm) 
above the walking surface and on or near the path of egress 
travel. Such markings shall become visible in an emergency. 
The directional exit marking shall be activated by the automatic 
fire detection system and the automatic sprinkler system in 
accordance with Section 907.2.12.2. 

411.7.1 Photo luminescent exit signs. Where photo lumi- 
nescent exit signs are installed, activating light source and 
viewing distance shall be in accordance with the listing and 
markings of the signs. 

411.8 Interior finish. The interior finish shall be Class A in 
accordance with Section 803.1. 



SECTION 412 
AIRCRAFT-RELATED OCCUPANCIES 

412.1 General. Aircraft-related occupancies shall comply 
with Sections 412.1 through 412.7 and the International Fire 
Code. 

412.2 Definitions. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

FIXED BASE OPERATOR (FBO). A commercial business 
granted the right by the airport sponsor to operate on an airport 
and provide aeronautical services, such as fueling, hangaring, 
tie-down and parking, aircraft rental, aircraft maintenance and 
flight instruction. 

HELIPORT. An area of land or water or a structural surface 
that is used, or intended for the use, for the landing and taking 
off of helicopters, and any appurtenant areas that are used, or 
intended for use, for heliport buildings or other heliport facili- 
ties. 

HELISTOP. The same as "heliport," except that no fueling, 
defueling, maintenance, repairs or storage of helicopters is per- 
mitted. 

RESIDENTIAL AIRCRAFT HANGAR. An accessory 
building less than 2,000 square feet (186 m 2 ) and 20 feet (6096 
mm) in building height constructed on a one- or two-family 
property where aircraft are stored. Such use will be considered 
as a residential accessory use incidental to the dwelling. 

TRANSIENT AIRCRAFT. Aircraft based at another location 
and at the transient location for not more than 90 days. 

412.3 Airport traffic control towers. 

412.3.1 General. The provisions of Sections 412.3.1 
through 412.3.6 shall apply to airport traffic control towers 
not exceeding 1,500 square feet (140 m 2 ) per floor occupied 
only for the following uses: 

1. Airport traffic control cab. 

2. Electrical and mechanical equipment rooms. 

3. Airport terminal radar and electronics rooms. 

4. Office spaces incidental to the tower operation. 

5. Lounges for employees, including sanitary facilities. 

412.3.2 Type of construction. Airport traffic control tow- 
ers shall be constructed to comply with the height and area 
limitations of Table 412.3.2. 

TABLE 412.3.2 

HEIGHT AND AREA LIMITATIONS FOR AIRPORT 

TRAFFIC CONTROL TOWERS 



TYPE OF 
CONSTRUCTION 


HEIGHT a 

(feet) 


MAXIMUM AREA 
(square feet) 


IA 


Unlimited 


1,500 


IB 


240 


1,500 


IIA 


100 


1,500 


UB 


85 


1,500 


I1IA 


65 


1,500 



For 51: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 
a. Height to be measured from grade plane to cab floor. 



2009 INTERNATIONAL BUILDING CODE® 



55 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



412.3.3 Egress. A minimum of one exit stairway shall be 
permitted for airport traffic control towers of any height pro- 
vided that the occupant load per floor does not exceed 15. 
The stairway shall conform to the requirements of Section 
1009. The stairway shall be separated from elevators by a 
minimum distance of one-half of the diagonal of the area 
served measured in a straight line. The exit stairway and ele- 
vator hoistway are permitted to be located in the same shaft 
enclosure, provided they are separated from each other by a 
4-hour fire barrierhaving no openings. Such stairway shall 
be pressurized to a minimum of 0.15 inch of water column 
(43 Pa) and a maximum of 0.35 inch of water column (101 
Pa) in the shaft relative to the building with stairway doors 
closed. Stairways need not extend to the roof as specified in 
Section 1009.11. The provisions of Section 403 do not 
apply. 

Exception: Smokeproof enclosures as set forth in Sec- 
tion 1022.9 are not required where required stairways 
are pressurized. 

[F] 4123 A Automatic fire detection systems. Airport traf- 
fic control towers shall be provided with an automatic fire 
detection system installed in accordance with Section 
907.2. 

[F] 412.3.5 Standby power. A standby power system that 
conforms to Chapter 27 shall be provided in airport traffic 
control towers more than 65 feet (19 812 mm) in height. 
Power shall be provided to the following equipment: 

1. Pressurization equipment, mechanical equipment and 
lighting. 

2. Elevator operating equipment. 

3. Fire alarm and smoke detection systems. 

412.3.6 Accessibility. Airport traffic control towers need not 
be accessible as specified in the provisions of Chapter 11. 

412.4 Aircraft hangars. Aircraft hangars shall be in accor- 
dance with Sections 412.4.1 through 412.4.6. 

412.4.1 Exterior walls. Exterior walls located less than 30 
feet (9144 mm) from lot lines or a public way shall have a 
fire-resistance rating not less than 2 hours. 

412.4.2 Basements. Where hangars have basements, floors 
over basements shall be of Type IA construction and shall be 
made tight against seepage of water, oil or vapors. There 
shall be no opening or communication between basements 
and the hangar. Access to basements shall be from outside 
only. 

412.4.3 Floor surface. Floors shall be graded and drained 
to prevent water or fuel from remaining on the floor. Floor 
drains shall discharge through an oil separator to the sewer 
or to an outside vented sump . 

Exception: Aircraft hangars with individual lease 
spaces not exceeding 2,000 square feet (186 m 2 ) each in 
which servicing, repairing or washing is not conducted 
and fuel is not dispensed shall have floors that are graded 
toward the door, but shall not require a separator. 



412.4.4 Heating equipment. Heating equipment shall be 
placed in another room separated by 2-hour fire barriers 
constructed in accordance with Section 707 or horizontal 
assemblies constructed in accordance with Section 712, or 
both. Entrance shall be from the outside or by means of a 
vestibule providing a two-doorway separation. 

Exceptions: 

1. Unit heaters and vented infrared radiant heating 
equipment suspended at least 10 feet (3048 mm) 
above the upper surface of wings or engine enclo- 
sures of the highest aircraft that are permitted to be 
housed in the hangar and at least 8 feet (2438 mm) 
above the floor in shops, offices and other sections 
of the hangar communicating with storage or ser- 
vice areas. 

2. A single interior door shall be allowed, provided 
the sources of ignition in the appliances are at least 
18 inches (457 mm) above the floor. 

412.4.5 Finishing. The process of "doping," involving use 
of a volatile flammable solvent, or of painting, shall be car- 
ried on in a separate detached building equipped with auto- 
matic fire-extinguishing equipment in accordance with 
Section 903. 

412.4.6 Fire suppression. Aircraft hangars shall be pro- 
vided with a fire suppression system designed in accordance 
with NFPA 409, based upon the classification for the hangar 
given in Table 412.4.6. 

Exception: When a fixed base operator has separate 
repair facilities on site, Group II hangars operated by a 
fixed base operator used for storage of transient aircraft 
only shall have a fire suppression system, but the system 
is exempt from foam requirements. 

412.4.6.1 Hazardous operations. Any Group III air- 
craft hangar according to Table 412.4.6 that contains 
hazardous operations including, but not limited to, the 
following shall be provided with a Group I or II fire sup- 
pression system in accordance with NFPA 409 as appli- 
cable: 

1. Doping. 

2. Hot work including, but not limited to, welding, 
torch cutting and torch soldering. 

3 . Fuel transfer. 

4. Fuel tank repair or maintenance not including 
defueled tanks in accordance with NFPA 409, 
inerted tanks or tanks that have never been fueled. 

5. Spray finishing operations. 

6. Total fuel capacity of all aircraft within the 
unsprinklered single fire area in excess of 1,600 
gallons (6057 L). 

7. Total fuel capacity of all aircraft within the maxi- 
mum single fire area in excess of 7,500 gallons 
(28 390 L) for a hangar with an automatic sprin- 
kler system in accordance with S ection 903 .3.1.1. 



56 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 412.4.6 
HANGAR FIRE SUPPRESSION REQUIREMENTSa,b,c 



MAXIMUM SINGLE 
FIRE AREA, SQ. FT. 


TYPE OF CONSTRUCTION 


IA 


IB 


IIA 


MB 


NiA 


1MB 


IV 


VA 


VB 


> 40,001 


Group I 


Group I 


Group I 


Group I 


Group I 


Group I 


Group I 


Group I 


Group I 


40,000 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


30,000 


Group III 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


20,000 


Group III 


Group III 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


Group II 


15,000 


Group III 


Group III 


Group III 


Group II 


Group III 


Group II 


Group III 


Group II 


Group II 


12,000 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group II 


Group II 


8,000 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group II 


5,000 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 


Group III 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 - 

a. Aircraft hangars with a door height greater than 28 feet shall be provided with fire suppression for a Group I hangar regardless of maximum fire area. 

b. Groups shall be as classified in accordance with NFPA 409 . 

c. Membrane structures complying with Section 3102 shall be classified as a Group IV hangar. 



412.4.6.2 Separation ofmaximum single fire areas. Max- 
imum single fire areas established in accordance with han- 
gar classification and construction type in Table All A. 6 
shall be separated by 2-hour fire walls constructed in accor- 
dance with Section 706. 

412.5 Residential aircraft hangars. Residential aircraft han- 
gars as defined in Section 412.2 shall comply with Sections 
412.5.1 through 412.5.2. 

412.5.1 Fire separation. A hangar shall not be attached to a 
dwelling unless separated by a fire barrier having a 
fire -resistance rating of not less than 1 hour. Such separa- 
tion shall be continuous from the foundation to the under- 
side of the roof and unpierced except for doors leading to the 
dwelling unit. Doors into the dwelling unit must be 
equipped with self-closing devices and conform to the 
requirements of Section 715 with at least a 4- inch (102 mm) 
noncombustible raised sill. Openings from a hanger directly 
into a room used for sleeping purposes shall not be permit- 
ted. 

412.5.2 Egress. A hangar shall provide two means ofegress. 
One of the doors into the dwelling shall be considered as 
meeting only one of the two means ofegress. 

[F] 412.5.3 Smoke alarms. Smoke alarms shall be pro- 
vided within the hangar in accordance with Section 
907.2.21. 

412.5.4 Independent systems. Electrical, mechanical and 
plumbing drain, waste and vent (DWV) systems installed 
within the hangar shall be independent of the systems 
installed within the dwelling. Building sewer lines shall be 
permitted to be connected outside the structures. 

Exception: Smoke detector wiring and feed for electri- 
cal subpanels in the hangar. 



412.5.5 Height and area limits. Residential aircraft han- I 
gars shall not exceed 2,000 square feet (186 m 2 ) in area and 
20 feet (6096 mm) in building height. 

\F] 412.6 Aircraft paint hangars. Aircraft painting opera- 
tions where flammable liquids are used in excess of the maxi- 
mum allowable quantities per control area listed in Table 
307.7(1) shall be conducted in an aircraft paint hangar that 
complies with the provisions of Sections 412.6.1 through 
412.6.6. 

[F] 412.6.1 Occupancy group. Aircraft paint hangars shall 
be classified as Group H-2. Aircraft paint hangars shall 
comply with the applicable requirements of this code and 
the International Fire Code for such occupancy. 

412.6.2 Construction. The aircraft paint hangar shall be of 
Type I or 1 1 construction. 

[F] 412.6.3 Operations. Only those flammable liquids nec- 
essary for painting operations shall be permitted in quantities 
less than the maximum allowable quantities per control area 
in Table 307.1 (1) . Spray equipment cleaning operations shall 
be conducted in a liquid use, dispensing and mixing room. 

[F] 412.6.4 Storage. Storage of flammable liquids shall be 
in a liquid storage room. 

[F] 412.6.5 Fire suppression. Aircraft paint hangars shall 
be provided with fire suppression as required by NFPA 409. 

412.6.6 Ventilation. Aircraft paint hangars shall be pro- 
vided with ventilation as required in the International 
Mechanical Code. 

412.7 Heliports and helistops. Heliports and helistops shall 
be permitted to be erected on buildings or other locations where 
they are constructed in accordance with Sections 412.7.1 
through 412.7.4. 



2009 INTERNATIONAL BUILDING CODE® 



57 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



412.7.1 Size. The landing area for helicopters less than 
3,500 pounds (1588 kg) shall be a minimum of20 feet (6096 
mm) in length and width. The landing area shall be sur- 
rounded on all sides by a clear area having a minimum aver- 
age width at roof level of 15 feet (4572 mm) but with no 
width less than 5 feet (1524 mm). 

412.7.2 Design. Helicopter landing areas and the supports 
thereof on the roof of a building shall be noncombustible 
construction. Landing areas shall be designed to confine any 
flammable liquid spillage to the landing area itself and pro- 
visions shall be made to drain such spillage away from any 
exitor stairway serving the helicopter landing area or from a 
structure housing such exit or stairway. For structural 
design requirements, see Section 1605.4. 

412.7.3 Means of egress. The means of egress from heli- 
ports and helistops shall comply with the provisions of 
Chapter 10. Landing areas located on buildings or structures 
shall have two or more means of egress. For landing areas 
less than 60 feet (18 288 mm) in length or less than 2,000 
square feet (186 m 2 ) in area, the second means of egress is 
permitted to be a fire escape, alternating tread device or lad- 
der leading to the floor below. 

412.1 A Rooftop heliports and helistops. Rooftop heli- 
ports and helistops shall comply with NFPA 418. 



SECTION 413 
COMBUSTIBLE STORAGE 

413.1 General. High-piled stock or rack storage in any occu- 
pancy group shall comply with the International Fire Code. 

413.2 Attic, under-floor and concealed spaces. Attic, 
under-floor and concealed spaces used for storage of combusti- 
ble materials shall be protected on the storage side as required 
for I-hour fire-resistance-rated construction. Openings shall 
be protected by assemblies that are self-closing and are of 
noncombustible construction or solid wood core not less than 
l 3 / 4 inch (45 mm) in thickness. 

Exceptions: 

1. Areas protected by approved automatic sprinkler sys- 
tems. 



2. Group R-3 and U occupancies. 



SECTION 414 
HAZARDOUS MATERIALS 

[F] 414.1 General. The provisions of Sections 414.1 through 
414.7 shall apply to buildings and structures occupied for the 
manufacturing, processing, dispensing, use or storage of haz- 
ardous materials. 

[F] 414.1.1 Other provisions. Buildings and structures 
with an occupancy in Group H shall also comply with the 
applicable provisions of Section 415 and the International 
Fire Code. 

\F] 414.1.2 Materials. The safe design of hazardous mate- 
rial occupancies is material dependent. Individual material 
requirements are also found in Sections 307 and 415, and in 



the International Mechanical Code and the International 
Fire Code. 

[F] 414.1.2.1 Aerosols. Level 2 and 3 aerosol products 
shall be stored and displayed in accordance with the 
International Fire Code. See Section 311 .2 and the Inter- 
national Fire Code for occupancy group requirements. 

[F] 414.1.3 Information required. A report shall be sub- 
mitted to the building official identifying the maximum 
expected quantities of hazardous materials to be stored, 
used in a closed system and used in an open system, and sub- 
divided to separately address hazardous material classifica- 
tion categories based on Tables 307.1(1) and 307.1(2). The 
methods of protection from such hazards, including but not 
limited to control areas, fire protection systems and Group 
H occupancies shall be indicated in the report and on the 
construction documents. The opinion and report shall be 
prepared by a qualified person, firm or corporation 
approved by the building official and provided without 
charge to the enforcing agency. 

For buildings and structures with an occupancy in Group 
H, separate floor plans shall be submitted identifying the 
locations of anticipated contents and processes so as to 
reflect the nature of each occupied portion of every building 
and structure. 

\F] 414.2 Control areas. Control areas shall comply with Sec- 
tions 414.2.1 through 414.2.5 and the International Fire Code. 

414.2.1 Construction requirements. Control areas shall 
be separated from each other by fire barriers constructed in 
accordance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. 

[F] 414.2.2 Percentage of maximum allowable quanti- 
ties. The percentage of maximum allowable quantities of 
hazardous materials per control area permitted at each floor 
level within a building shall be in accordance with Table 
414.2.2. 

[F] 414.2.3 Number. The maximum number of control 
areas within a building shall be in accordance with Table 
414.2.2. 

414.2 .4 Fire-resistance-rating requirements. The re- 
quired fire-resistance rating for fire barriers shall be in 
accordance with Table 414.2.2. The floor assembly of the 
control area and the construction supporting the floor of the 
control area shall have a minimum 2-hour fire-resistance 
rating. 

Exception: The floor assembly of the control area and 
the construction supporting the floor of the control area 
are allowed to be I-hour fire-resistance rated in buildings 
of Types IIA, I1IA and VA construction, provided that 
both of the following conditions exist: 

1. The building is equipped throughout with an auto- 
matic sprinkler system in accordance with Section 
903.3.1.1; and 

2. The building is three stories or less above grade 
plane. 



58 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 414.2.2 
DESIGN AND NUMBER OF CONTROL AREAS 



FLOOR LEVEL 


PERCENTAGE OF THE MAXIMUM ALLOWABLE 
QUANTITY PER CONTROL AREA a 


NUMBER OF CONTROL 
AREAS PER FLOOR 


FIRE-RESISTANCE RATING 
FOR FIRE BARRIERS IN HOURS b 


Above grade 
plane 


Higher than 9 

7-9 

6 

5 
4 

3 
2 
1 


5 

5 
12.5 
12.5 
12.5 
50 
75 
100 


1 

2 
2 
2 
2 
2 
3 
4 


2 
2 
2 
2 
2 


Below grade 
plane 


1 

2 

Lower than 2 


75 

50 

Not Allowed 


3 

2 

Not Allowed 


Not Allowed 



a. Percentages shall be of the maximum allowable quantity per control area shown in Tables 307.1(1) and 307.1(2) , with all increases allowed in the notes to those 
tables. 

b. Fire barriers shall include walls and floors as necessary to provide separation from other portions of the building. 



[F] 414.2.5 Hazardous material in Group M display and 
storage areas and in Group S storage areas. The aggre- 
gate quantity of nonflammable solid and nonflammable or 
noncombustible liquid hazardous materials permitted 
within a single control area of a Group M display and stor- 
age area, a Group S storage area or an outdoor control area 
is permitted to exceed the maximum allowable quantities 
per control area specified in Tables 307.1 (1) and 307.1 (2) 
without classifying the building or use as a Group H occu- 
pancy, provided that the materials are displayed and stored 
in accordance with the International Fire Code and quanti- 
ties do not exceed the maximum allowable specified in 
Table 414.2.5(1). 

In Group M occupancy wholesale and retail sales uses, 
indoor storage of flammable and combustible liquids shall 
not exceed the maximum allowable quantities per control 
area as indicated in Table 414.2.5(2), provided that the 
materials are displayed and stored in accordance with the 
International Fire Code. 

The maximum quantity of aerosol products in Group M 
occupancy retail display areas, storage areas adjacent to 
retail display areas and retail storage areas shall be in accor- 
dance with the International Fire Code. 

[F] 414.3 Ventilation. Rooms, areas or spaces of Group H in 
which explosive, corrosive, combustible, flammable or 
highly toxic dusts, mists, fumes, vapors or gases are or may be 
emitted due to the processing, use, handling or storage of 
materials shall be mechanically ventilated as required by the 
International Fire Code and the International Mechanical 
Code. 

Ducts conveying explosives or flammable vapors, fumes or 
dusts shall extend directly to the exterior of the building with- 
out entering other spaces. Exhaust ducts shall not extend into or 
through ducts and plenums. 

Exception: Ducts conveying vapor or fumes having flam- 
mable constituents less than 25 percent of their lower flam- 
mable limit (LFL) are permitted to pass through other 
spaces. 



Emissions generated at workstations shall be confined to the 
area in which they are generated as specified in the Interna- 
tional Fire Code and the International Mechanical Code. 

The location of supply and exhaust openings shall be in 
accordance with the International Mechanical Code. Exhaust 
air contaminated by highly toxic material shall be treated in 
accordance with the International Fire Code. 

A manual shutoff control for ventilation equipment required 
by this section shall be provided outside the room adjacent to 
the principal access door to the room. The switch shall be of the 
break-glass type and shall be labeled: VENTILATION SyS- 
TEM EMERGENCY SHUTOFF. 

[F] 414.4 Hazardous material systems. Systems involving 
hazardous materials shall be suitable for the intended applica- 
tion. Controls shall be designed to prevent materials from 
entering or leaving process or reaction systems at other than the 
intended time, rate or path. Automatic controls, where pro- 
vided, shall be designed to be fail safe. 

\F] 414.5 Inside storage, dispensing and use. The inside stor- 
age, dispensing and use of hazardous materials in excess of the 
maximum allowable quantities per control area of Tables 
307.1 (1) and 307.1 (2) shall be in accordance with Sections 
414.5.1 through 414.5.5 of this code and the International Fire 
Code. 

\F] 414.5.1 Explosion control. Explosion control shall be 
provided in accordance with the International Fire Code as 
required by Table 414.5.1 where quantities of hazardous 
materials specified in that table exceed the maximum allow- 
able quantities in Table 307.1 (1) or where a structure, room 
or space is occupied for purposes involving explosion haz- 
ards as required by Section 415 or the International Fire 
Code. 

[F] 414.5.2 Monitor control equipment. Monitor control 
equipment shall be provided where required by the Interna- 
tional Fire Code. 

\F] 414.5.3 Automatic fire detection systems. Group H 
occupancies shall be provided with an automatic fire detec- 
tion system in accordance with Section 907.2. 



2009 INTERNATIONAL BUILDING CODE® 



59 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 414.2.5(1) 

MAXIMUM ALLOWABLE QUANTITY PER INDOOR AND OUTDOOR CONTROL AREA IN GROUP M AND S OCCUPANCIES 

NONFLAMMABLE SOLIDS AND NONFLAMMABLE AND NONCOMBUSTIBLE LIQUIDSd,e,f 



CONDITION 


MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA 


Material 


Class 


Solids 
pounds 


Liquids 
gallons 


A. Health-hazard materials-nonflammable and noncombustible solids and liquids 


1. Corrosives ,c 


Not Applicable 


9,750 


975 


2. Highly taxies 


Not Applicable 


20b, c 


2b, c 


3. Toxics", c 


Not Applicable 


1,000 


100 


B. Physical-hazard materials-nonflammable and noncombustible solids and liquids 


1. Oxidizers ,c 


4 


Not Allowed 


Not Allowed 


3 


1,1508 


115 


2 


2,250 h 


225 


1 


18,000i,j 


i,8ooy 


2. Unstable (reactives)b,c 


4 


Not Allowed 


Not Allowed 


3 


550 


55 


2 


1,150 


115 


1 


Not Limited 


Not Limited 


3. Water (reactives) 


3b, c 


550 


55 


2b, c 


1,150 


115 


1 


Not Limited 


Not Limited 



For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L. 

a. Hazard categories are as specified in the International Fire Code. 

b. Maximum allowable quantities shall be increased 100 percent in buildings that are sprinklered in accordance with Section 903 .3. 1. 1. When Note c also applies, the 
increase for both notes shall be applied accumulatively. 

c. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, in accordance with the International Fire Code. When 
Note b also applies, the increase for both notes shall be applied accumulatively. 

d. See Table 414.2.2 for design and number of control areas. 

e. Allowable quantities for other hazardous material categories shall be in accordance with Section 307. 

f. Maximum quantities shall be increased 100 percent in outdoor control areas. 

g. Maximum amounts are permitted to be increased to 2,250 pounds when individual packages are in the original sealed containers from the manufacturer or 
packager and do not exceed 10 pounds each. 

h. Maximum amounts are permitted to be increased to 4,500 pounds when individual packages are in the original sealed containers from the manufacturer or 

packager and do not exceed 10 pounds each, 
i. The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance withSection 903.3.1.1. 
j. Quantities are unlimited in an outdoor control area. 

TABLE [F] 414.2.5(2) 

MAXIMUM ALLOWABLE QUANTITY OF FLAMMABLE AND COMBUSTIBLE LIQUIDS 

IN WHOLESALE AND RETAIL SALES OCCUPANCIES PER CONTROL AREA a 



TYPE OF LIQUID 


MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA (gallons) 


Sprinklered in accordance with note b 
densities and arrangements 


Sprinklered in accordance with Tables 

3404.3.6.3(4) through 3404.3.6.3(8) and Table 

3404.3.7.5.1 of the International Fire Code 


Nonsprinklered 


Class IA 


60 


60 


30 


Class IB, IC, II and I1IA 


7,500 c 


15,000c 


1,600 


Class I1IB 


Unlimited 


Unlimited 


13,200 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 , 1 gallon = 3.785 L, 1 gallon per minute per square foot = 40.75 L/min/m 2 . 

a. Control areas shall be separated from each other by not less than a I-hour fire barrier wall. 

b. To be considered as sprinklered, a building shall be equipped throughout with an approved automatic sprinkler system with a design providing minimum densities 
as follows: 

1. For uncartoned commodities on shelves 6 feet or less in height where the ceiling height does not exceed 18 feet, quantities are those permitted with a mini- 
mum sprinkler design density of Ordinary Hazard Group 2. 

2. For cartoned, palletized or racked commodities where storage is 4 feet 6 inches or less in height and where the ceiling height does not exceed 18 feet, quanti- 
ties are those permitted with a minimum sprinkler design density of 0.21 gallon per minute per square foot over the most remote 1,500-square-foot area. 

c. Where wholesale and retail sales or storage areas exceed 50,000 square feet in area, the maximum allowable quantities are allowed to be increased by 2 percent for 
each 1,000 square feet of area in excess of 50,000 square feet, up to a maximum of 100 percent of the table amounts. A control area separation is not required. The 
cumulative amounts, including amounts attained by having an additional control area, shall not exceed 30,000 gallons. 



60 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 414.5.1 
EXPLOSION CONTROL REQUIREMENTS 3 



MATERIAL 


CLASS 


EXPLOSION CONTROL METHODS 


Barricade construction 


Explosion (deflagration) venting 

or explosion (deflagration) 

prevention systems b 


HAZARD CATEGORY 


Combustible dusts 




Not Required 


Required 


Cryogenic flammables 


- 


Not Required 


Required 


Explosives 


Division 1.1 
Division 1.2 
Division 1.3 
Division 1.4 
Division 1.5 
Division 1.6 


Required 
Required 
Not Required 
Not Required 
Required 
Required 


Not Required 
Not Required 
Required 
Required 
Not Required 
Not Required 


Flammable gas 


Gaseous 
Liquefied 


Not Required 
Not Required 


Required 
Required 


Flammable liquid 


lAd 
IBe 


Not Required 
Not Required 


Required 
Required 


Organic peroxides 


U 

I 


Required 
Required 


Not Permitted 
Not Permitted 


Oxidizer liquids and solids 


4 


Required 


Not Permitted 


Pyrophoric gas 




Not Required 


Required 


Unstable (reactive) 


4 

3 Detonable 

3 Nondetonable 


Required 

Required 

Not Required 


Not Permitted 

Not Permitted 

Required 


Water-reactive liquids and solids 


3 

2g 


Not Required 
Not Required 


Required 
Required 


SPECIAL USES 


Acetylene generator rooms 




Not Required 


Required 


Grain processing 


- 


Not Required 


Required 


Liquefied petroleum gas-distribution facilities 


- 


Not Required 


Required 


Where explosion hazards exist f 


Detonation 
Deflagration 


Required 
Not Required 


Not Permitted 
Required 



a. See Section 414.1.3. 

b. See the International Fire Code. 

c. As generated during manufacturing or processing. See definition of "Combustible dust" in Chapter 3. 

d. Storage or use. 

e. In open use or dispensing. 

f. Rooms containing dispensing and use of hazardous materials when an explosive environment can occur because of the characteristics or nature of the hazardous 
materials or as a result of the dispensing or use process. 

g. A method of explosion control shall be provided when Class 2 water-reactive materials can form potentially explosive mixtures. 



2009 INTERNATIONAL BUILDING CODE® 



61 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] 414.5.4 Standby or emergency power. Where mechan- 
ical ventilation, treatment systems, temperature control, 
alarm, detection or other electrically operated systems are 
required, such systems shall be provided with an emergency 
or standby power system in accordance with Chapter 27. 

Exceptions: 

1. Mechanical ventilation for storage of Class IB and 
Class IC flammable and combustible liquids in 
closed containers not exceeding 6.5 gallons (25 L) 
capacity. 

2. Storage areas for Class 1 and 2 oxidizers. 

3. Storage areas for Class II, III, IV and V organic 
peroxides. 

4. Storage, use and handling areas for asphyxiant, 
irritant and radioactive gases. 

5. For storage, use and handling areas for highly toxic 
or toxic materials, see Sections 3704.2.2.8 and 
3704.3.4.2 of the International Fire Code. 

6. Standby power for mechanical ventilation, treat- 
ment systems and temperature control systems 
shall not be required where an approved fail-safe 
engineered system is installed. 

\F] 414.5.5 Spill control, drainage and containment. 
Rooms, buildings or areas occupied for the storage of solid 
and liquid hazardous materials shall be provided with a 
means to control spillage and to contain or drain off spillage 
and fire protection water discharged in the storage area 
where required in the International Fire Code. The methods 
of spill control shall be in accordance with the International 
Fire Code. 

[F] 414.6 Outdoor storage, dispensing and use. The outdoor 
storage, dispensing and use of hazardous materials shall be in 
accordance with the International Fire Code. 

[F] 414.6.1 Weather protection. Where weather protection 
is provided for sheltering outdoor hazardous material stor- 
age or use areas, such areas shall be considered outdoor 
storage or use when the weather protection structure com- 
plies with Sections 414.6.1.1 through 414.6.1.3. 

[F] 414.6.1.1 Walls. Walls shall not obstruct more than 
one side of the structure. 

Exception: Walls shall be permitted to obstruct por- 
tions of multiple sides of the structure, provided that 
the obstructed area does not exceed 25 percent of the 
structure's perimeter. 

[F] 414.6.1.2 Separation distance. The distance from 
the structure to buildings, lot lines, public ways or means 
of egress to a public way shall not be less than the dis- 
tance required for an outside hazardous material storage 
or use area without weather protection. 

[F] 414.6.1.3 Noncombustible construction. The overhead 
structure shall be of approved noncombustible construction 
with a maximum area of 1,500 square feet (140 m 2 ). 

Exception: The increases permitted by Section 506 
apply. 



[F] 414.7 Emergency alarms. Emergency alarms for the 
detection and notification of an emergency condition in Group 
H occupancies shall be provided as set forth herein. 

[F] 414.7.1 Storage. An approved manual emergency 
alarm system shall be provided in buildings, rooms or areas 
used for storage of hazardous materials. Emergency 
alarm -initiating devices shall be installed outside of each 
interior exit or exit access door of storage buildings, rooms 
or areas. Activation of an emergency alarm- initiating device 
shall sound a local alarm to alert occupants of an emergency 
situation involving hazardous materials. 

[F] 414.7.2 Dispensing, use and handling. Where hazard- 
ous materials having a hazard ranking of 3 or 4 in accor- 
dance with NFPA 704 are transported through corridors or 
exit enclosures, there shall be an emergency telephone sys- 
tem, a local manual alarm station or an approved alarm-ini- 
tiating device at not more than ISO-foot (45 720 mm) 
intervals and at each exit and exit access doorway through- 
out the transport route. The signal shall be relayed to an 
approved central, proprietary or remote station service or 
constantly attended on-site location and shall also initiate a 
local audible alarm. 

[F] 414.7.3 Supervision. Emergency alarm systems shall 
be supervised by an approved central, proprietary or remote 
station service or shall initiate an audible and visual signal at 
a constantly attended on-site location. 



SECTION 415 
GROUPS H-1, H-2, H-3, H-4 AND H-5 

[F] 415.1 Scope. The provisions of Sections 415.1 through 
415.8 shall apply to the storage and use of hazardous materials 
in excess of the maximum allowable quantities per control area 
listed in Section 307.1. Buildings and structures with an occu- 
pancy in Group H shall also comply with the applicable provi- 
sions of Section 414 and the International Fire Code. 

[F] 415.2 Definitions. The following words and terms shall, 
for the purposes of this chapter and as used elsewhere in the 
code, have the meanings shown herein. 

\F] CONTINUOUS GAS DETECTION SYSTEM. A gas 
detection system where the analytical instrument is maintained 
in continuous operation and sampling is performed without 
interruption. Analysis is allowed to be performed on a cyclical 
basis at intervals not to exceed 30 minutes. 

\F] DETACHED BUILDING. A separate single-story bUild- I 
ing, without a basement or crawl space, used for the storage or 
use of hazardous materials and located an approved distance 
from all structures. 

\F] EMERGENCY CONTROL STATION. An approved 
location on the premises where signals from emergency equip- 
ment are received and which is staffed by trained personnel. 

\F] EXHAUSTED ENCLOSURE. An appliance or piece of 
equipment that consists of a top, a back and two sides providing 
a means of local exhaust for capturing gases, fumes, vapors and 
mists. Such enclosures include laboratory hoods, exhaust fume 
hoods and similar appliances and equipment used to locally 
retain and exhaust the gases, fumes, vapors and mists that could 



62 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



be released. Rooms or areas provided with general ventilation, 
in themselves, are not exhausted enclosures. 

\F] FABRICATION AREA. An area within a semiconductor 
fabrication facility and related research and development areas 
in which there are processes using hazardous production mate- 
rials. Such areas are allowed to include ancillary rooms or areas 
such as dressing rooms and offices that are directly related to 
the fabrication area processes. 

\F] FLAMMABLE VAPORS OR FUMES. The concentra- 
tion of flammable constituents in air that exceed 25 percent of 
their lower flammable limit (LFL). 

[F] GAS CABINET. A fully enclosed, noncombustible enclo- 
sure used to provide an isolated environment for compressed 
gas cylinders in storage or use. Doors and access ports for 
exchanging cylinders and accessing pressure-regulating con- 
trols are allowed to be included. 

[F] GAS ROOM. A separately ventilated, fully enclosed room 
in which only compressed gases and associated equipment and 
supplies are stored or used. 

[F] HAZARDOUS PRODUCTION MATERIAL (HPM). 
A solid, liquid or gas associated with semiconductor manufac- 
turing that has a degree-of-hazard rating in health, 
flammability or instability of Class 3 or 4 as ranked by NFPA 
704 and which is used directly in research, laboratory or pro- 
duction processes which have as their end product materials 
that are not hazardous. 

[F] HPM FLAMMABLE LIQUID. An HPM liquid that is 
defined as either a Class I flammable liquid or a Class II or 
Class MA combustible liquid. 

\F] HPM ROOM. A room used in conjunction with or serving 
a Group H-5 occupancy, where HPM is stored or used and 
which is classified as a Group H-2, H-3 or H-4 occupancy. 

[F] IMMEDIATELY DANGEROUS TO LIFE AND 
HEALTH (IDLH). The concentration of air-borne contami- 
nants which poses a threat of death, immediate or delayed per- 
manent adverse health effects, or effects that could prevent 
escape from such an environment. This contaminant concentra- 
tion level is established by the National Institute of Occupational 
Safety and Health (NIOSH) based on both toxicity and 
flammability. It generally is expressed in parts per million by 
volume (ppmv/v) or milligrams per cubic meter (mg/m 3 ). If ade- 
quate data do not exist for precise establishment of IDLH con- 
centrations, an independent certified industrial hygienist, 
industrial toxicologist, appropriate regulatory agency or other 
source approved by the bUilding official shall make such 
determination. 

[F] LIQUID. A material that has a melting point that is equal to 
or less than 68°F (20°C) and a boiling point that is greater than 
68°F (20°C) at 14.7 pounds per square inch absolute (psia) 
(101 kPa). When not otherwise identified, the term "liqUid" 
includes both flammable and combustible liquids. 

\F] LIQUID STORAGE ROOM. A room classified as a 
Group H-3 occupancy used for the storage of flammable or 
combustible liquids in a closed condition. 



[F] LIQUID USE, DISPENSING AND MIXING ROOM. 

A room in which Class I, II and MA flammable or combustible 
liquids are used, dispensed or mixed in open containers. 

[F] LOWER FLAMMABLE LIMIT (LFL). The minimum 
concentration of vapor in air at which propagation of flame will 
occur in the presence of an ignition source. The LFL is some- 
times referred to as "LEL" or "lower explosive limit." 

[F] NORMAL TEMPERATURE AND PRESSURE 
(NTP). A temperature of 70°F (21°C) and a pressure of 1 atmo- 
sphere [14.7 psia (101 kPa)]. 

[F] PHYSIOLOGICAL WARNING THRESHOLD 
LEVEL. A concentration of air-borne contaminants, normally 
expressed in parts per million (ppm) or milligrams per cubic meter 
(mg/m 3 ), that represents the concentration at which persons can 
sense the presence of the contaminant due to odor, irritation or 
other quick-acting physiological response. When used in 
conjunction with the permissible exposure limit (PEL) the physio- 
logical warning threshold levels are those consistent with the classi- 
fication system used to establish the PEL. See the definition of 
"Permissible exposure limit (PEL)" in the International Fire Code. 

[F] SERVICE CORRIDOR. A fully enclosed passage used 
for transporting HPM and purposes other than required means 
ofegress. 

[F] SOLID. A material that has a melting point, decomposes or 
sublimes at a temperature greater than 68°F (20°C) . 

[FT STORAGE, HAZARDOUS MATERIALS. 

1. The keeping, retention or leaving of hazardous materials 
in closed containers, tanks, cylinders or similar vessels, or 

2. Vessels supplying operations through closed connec- 
tions to the vessel. 

[F] USE (MATERIAL). Placing a material into action, includ- 
ing solids, liquids and gases. 

[F] WORKSTATION. A defined space or an independent prin- 
cipal piece of equipment using HPM within a fabrication area 
where a specific function, laboratory procedure or research 
activity occurs. Approved or listed hazardous materials storage 
cabinets, flammable liquid storage cabinets or gas cabinets serv- 
ing a workstation are included as part of the workstation. A 
workstation is allowed to contain ventilation equipment, fire 
protection devices, detection devices, electrical devices and 
other processing and scientific equipment. 

[F] 415.3 Fire separation distance. Group H occupancies 
shall be located on property in accordance with the other provi- 
sions of this chapter. In Groups H-2 and H-3, not less than 25 
percent of the perimeter wall of the occupancy shall be an exte- 
rior wall 

Exceptions: 

1. Liquid use, dispensing and mixing rooms having a 
floor area of not more than 500 square feet (46.5 m 2 ) 
need not be located on the outer perimeter of the 
building where they are in accordance with the Inter- 
national Fire Code and NFPA 30. 



2009 INTERNATIONAL BUILDING CODE® 



63 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



2. Liquid storage rooms having a floor area of not more 
than 1,000 square feet (93 m 2 ) need not be located on 
the outer perimeter where they are in accordance with 
the International Fire Code and NFPA 30. 

3. Spray paint booths that comply with the International 
Fire Code need not be located on the outer perimeter. 

[F] 415.3.1 Group" occupancy minimum fire separa- 
tion distance. Regardless of any other provisions, buildings 
containing Group H occupancies shall be set back to the 
minimum fire separation distance as set forth in Items 1 
through 4 below. Distances shall be measured from the 
walls enclosing the occupancy to lot lines, including those 
on a public way. Distances to assumed lot lines established 
for the purpose of determining exterior wall and opening 
protection are not to be used to establish the minimum fire 
separation distance for buildings on sites where explosives 
are manufactured or used when separation is provided in 
accordance with the quantity distance tables specified for 
explosive materials in the International Fire Code. 

1. Group H-l. Not less than 75 feet (22 860 mm) and not 
less than required by the International Fire Code. 

Exceptions: 

1. Fireworks manufacturing buildings sepa- 
rated in accordance with NFPA 1124. 

2. Buildings containing the following materi- 
als when separated in accordance with Table 
415.3.1: 



2.1. Organic peroxides, 
detonable. 



unclassified 



2.2. Unstable reactive materials, Class 4. 

2.3. Unstable reactive materials, Class 3 
detonable. 

2.4. Detonable pyrophoric materials. 

2. Group H-2. Not less than 30 feet (9144 mm) where 
the area of the occupancy exceeds 1,000 square feet 
(93 m 2 ) and it is not required to be located in a 
detached building. 

3. Groups H-2 and H-3. Not less than 50 feet (15 240 
mm) where a detached building is required (see Table 
415.3.2). 

4. Groups H-2 and H-3. Occupancies containing materi- 
als with explosive characteristics shall be separated as 
required by the International Fire Code. Where sepa- 
rations are not specified, the distances required shall 
not be less than the distances required by Table 
415.3.1. 

[F] 415.3.2 Detached buildings for Group "-1, "-2 or 
"-3 occupancy. The storage of hazardous materials in 
excess of those amounts listed in Table 415.3.2 shall be in 
accordance with the applicable provisions of Sections 415 .4 
and 415.5. Where a detached building is required by Table 
415.3.2, there are no requirements for wall and opening pro- 
tection based on fire separation distance. 

[F] 415.4 Special provisions for Group "-1 occupancies. 
Group H-l occupancies shall be in buildings used for no other 



purpose, shall not exceed one story in height and be without 
basements, crawl spaces or other under-floor spaces. Roofs 
shall be of lightweight construction with suitable thermal insu- 
lation to prevent sensitive material from reaching its decompo- 
sition temperature. Group H-l occupancies containing 
materials that are in themselves both physical and health haz- 
ards in quantities exceeding the maximum allowable quantities 
per control area in Table 307.1. (2) shall comply with require- 
ments for both Group H-l and H-4 occupancies. 

[F] 415.4.1 Floors in storage rooms. Floors in storage 
areas for organic peroxides, pyrophoric materials and unsta- 
ble (reactive) materials shall be of liquid-tight, noncombust- 
ible construction. 

[F] 415.5 Special provisions for Groups "-2 and "-3 occu- 
pancies. Groups H-2 and H-3 occupancies containing quanti- 
ties of hazardous materials in excess of those set forth in Table 
415.3.2 shall be in buildings used for no other purpose, shall 
not exceed one storyin height and shall be without basements, 
crawl spaces or other under-floor spaces. 

Groups H-2 and H-3 occupancies containing water-reactive 
materials shall be resistant to water penetration. Piping for con- 
veying liquids shall not be over or through areas containing 
water reactives, unless isolated by approved liquid-tight con- 
struction. 

Exception: Fire protection piping. 

[F] 415.5.1 Floors in storage rooms. Floors in storage 
areas for organic peroxides, oxidizers, pyrophoric materi- 
als' unstable (reactive) materials and water-reactive solids 
and liquids shall be of liquid-tight, noncombustible con- 
struction. 

[F] 415.5.2 Waterproof room. Rooms or areas used for the 
storage of water-reactive solids and liquids shall be con- 
structed in a manner that resists the penetration of water 
through the use of waterproof materials. Piping carrying 
water for other than approved automatic fire sprinkler sys- 
tems shall not be within such rooms or areas. 

\F] 415.6 Group "-2. Occupancies in Group H-2 shall be con- 
structed in accordance with Sections 415.6.1 through 415.6.4 
and the International Fire Code. 

[F] 415.6.1 Combustible dusts, grain processing and 
storage. The provisions of Sections 415.6.1.1 through 
415.6.1.6 shall apply to buildings in which materials that 
produce combustible dusts are stored or handled. Buildings 
that store or handle combustible dusts shall comply with the 
applicable provisions of NFPA 61, NFPA 85, NFPA 120, 
NFPA 484, NFPA 654, NFPA 655 and NFPA 664, and the 
International Fire Code. 

\F] 415.6.1.1 Type of construction and height excep- 
tions. Buildings shall be constructed in compliance with 
the height and area limitations of Table 503 for Group 
H-2; except that where erected of Type I or II construc- 
tion, the heights and areas of grain elevators and similar 
structures shall be unlimited, and where of Type IV con- 
struction, the maximum height shall be 65 feet (19 812 
mm) and except further that, in isolated areas, the maxi- 
mum height of Type IV structures shall be increased to 
85 feet (25 908 mm). 



64 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 415.3.1 
MINIMUM SEPARATION DISTANCES FOR BUILDINGS CONTAINING EXPLOSIVE MATERIALS 


QUANTITY OF EXPLOSIVE MATERIAL a 


MINIMUM DISTANCE (feet) 


Lot lines b and inhabited buildings 


Separation of magazines d ,e, t 


Pounds over 


Pounds not over 


Barricaded d 


Unbarricaded 


2 


5 


70 


140 


12 


5 


10 


90 


180 


16 


10 


20 


110 


220 


20 


20 


30 


125 


250 


22 


30 


40 


140 


280 


24 


40 


50 


150 


300 


28 


50 


75 


170 


340 


30 


75 


100 


190 


380 


32 


100 


125 


200 


400 


36 


125 


150 


215 


430 


38 


150 


200 


235 


470 


42 


200 


250 


255 


510 


46 


250 


300 


270 


540 


48 


300 


400 


295 


590 


54 


400 


500 


320 


640 


58 


500 


600 


340 


680 


62 


600 


700 


355 


710 


64 


700 


800 


375 


750 


66 


800 


900 


390 


780 


70 


900 


1,000 


400 


800 


72 


1,000 


1,200 


425 


850 


78 


1,200 


1,400 


450 


900 


82 


1,400 


1,600 


470 


940 


86 


1,600 


1,800 


490 


980 


88 


1,800 


2,000 


505 


1,010 


90 


2,000 


2,500 


545 


1,090 


98 


2,500 


3,000 


580 


1,160 


104 


3,000 


4,000 


635 


1,270 


116 


4,000 


5,000 


685 


1,370 


122 


5,000 


6,000 


730 


1,460 


130 


6,000 


7,000 


770 


1,540 


136 


7,000 


8,000 


800 


1,600 


144 


8,000 


9,000 


835 


1,670 


150 


9,000 


10,000 


865 


1,730 


156 


10,000 


12,000 


875 


1,750 


164 


12,000 


14,000 


885 


1,770 


174 


14,000 


16,000 


900 


1,800 


180 


16,000 


18,000 


940 


1,880 


188 


18,000 


20,000 


975 


1,950 


196 


20,000 


25,000 


1,055 


2,000 


210 


25,000 


30,000 


1,130 


2,000 


224 


30,000 


35,000 


1,205 


2,000 


238 


35,000 


40,000 


1,275 


2,000 


248 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



65 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



TABLE 415.3.1-continued 
MINIMUM SEPARATION DISTANCES FOR BUILDINGS CONTAINING EXPLOSIVE MATERIALS 







MINIMUM DISTANCE (feet) 


QUANTITY OF EXPLOSIVE MATERIAL 3 


Lot lines b and inhabited buildings 


Separation of magazines d ,e, i 


Pounds over 


Pounds not over 


Barricaded d 


Unbarricaded 


40,000 


45,000 


1,340 


2,000 


258 


45,000 


50,000 


1,400 


2,000 


270 


50,000 


55,000 


1,460 


2,000 


280 


55,000 


60,000 


1,515 


2,000 


290 


60,000 


65,000 


1,565 


2,000 


300 


65,000 


70,000 


1,610 


2,000 


310 


70,000 


75,000 


1,655 


2,000 


320 


75,000 


80,000 


1,695 


2,000 


330 


80,000 


85,000 


1,730 


2,000 


340 


85,000 


90,000 


1,760 


2,000 


350 


90,000 


95,000 


1,790 


2,000 


360 


95,000 


100,000 


1,815 


2,000 


370 


100,000 


110,000 


1,835 


2,000 


390 


110,000 


120,000 


1,855 


2,000 


410 


120,000 


130,000 


1,875 


2,000 


430 


130,000 


140,000 


1,890 


2,000 


450 


140,000 


150,000 


1,900 


2,000 


470 


150,000 


160,000 


1,935 


2,000 


490 


160,000 


170,000 


1,965 


2,000 


510 


170,000 


180,000 


1,990 


2,000 


530 


180,000 


190,000 


2,010 


2,010 


550 


190,000 


200,000 


2,030 


2,030 


570 


200,000 


210,000 


2,055 


2,055 


590 


210,000 


230,000 


2,100 


2,100 


630 


230,000 


250,000 


2,155 


2,155 


670 


250,000 


275,000 


2,215 


2,215 


720 


275,000 


300,000 


2,275 


2,275 


770 



For SI: 1 pound = 0.454 kg, 1 foot = 304.8 mm, 1 square foot = 0.0929m 2 - 

a. The number of pounds of explosives listed is the number of pounds of trinitrotoluene (TNT) or the equivalent pounds of other explosive. 

b. The distance listed is the distance to lot line, including lot lines at public ways. 

c. For the purpose of this table, an inhabited building is any building on the same lot that is regularly occupied by people. Where two or more buildings containing 
explosives or magazines are located on the same lot, each building or magazine shall comply with the minimum distances specified from inhabited buildings and, 
in addition, they shall be separated from each other by not less than the distance shown for" Separation of magazines, " except that the quantity of explosive materi- 
als contained in detonator buildings or magazines shall govern in regard to the spacing of said detonator buildings or magazines from buildings or magazines con- 
taining other explosive materials. If any two or more buildings or magazines are separated from each other by less than the specified "Separation of Magazines" 
distances, then such two or more buildings or magazines, as a group, shall be considered as one building or magazine, and the total quantity of explosive materials 
stored in such group shall be treated as if the explosive were in a single building or magazine located on the site of any building or magazine of the group, and shall 
comply with the minimum distance specified from other magazines or inhabited buildings. 

d. Barricades shall effectively screen the building containing explosives from other buildings, public ways or magazines . Where mounds or revetted walls of earth are 
used for barricades, they shall not be less than 3 feet in thickness. A straight line from the top of any side wall of the building containing explosive materials to the 
eave line of any other building, magazine or a point 12 feet above the centerline of a public way shall pass through the barricades. 

e. Magazine is a building or structure, other than an operating building, approved for storage of explosive materials. Portable or mobile magazines not exceeding 120 
square feet in area need not comply with the requirements of this code, hONever, all magazines shall comply with the International Fire Code. 

f. The distance listed is permitted to be reduced by 50 percent where approved natural or artificial barriers are provided in accordance with the requirements in Note d. 



66 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 





[F] TABLE 415.3.2 
DETACHED BUILDING REQUIRED 




A DETACHED BUILDING IS REQUIRED WHEN THE QUANTITY OF MATERIAL EXCEEDS THAT LISTED HEREIN 


Material 


Class 


Solids and Liquids (tons)a, b 


Gases (cubic feet)a, b 


Explosives 


Division 1.1 
Division 1.2 
Division 1.3 
Division 1.4 
Division 1.4c 
Division 1.5 
Division 1.6 


Maximum Allowable Quantity 
Maximum Allowable Quantity 
Maximum Allowable Quantity 
Maximum Allowable Quantity 

1 
Maximum Allowable Quantity 
Maximum Allowable Quantity 


Not Applicable 


Oxidizers 


Class 4 


Maximum Allowable Quantity 


Maximum Allowable Quantity 


Unstable (reactives) detonable 


Class 3 or 4 


Maximum Allowable Quantity 


Maximum Allowable Quantity 


Oxidizer, liquids and solids 


Class 3 
Class 2 


1,200 
2,000 


Not Applicable 
Not Applicable 


Organic peroxides 


Detonable 
Class I 
Class II 
Class III 


Maximum Allowable Quantity 
Maximum Allowable Quantity 

25 
50 


Not Applicable 
Not Applicable 
Not Applicable 
Not Applicable 


Unstable (reactives) nondetonable 


Class 3 
Class 2 


1 

25 


2,000 
10,000 


Water reactives 


Class 3 
Class 2 


1 

25 


Not Applicable 
Not Applicable 


Pyrophoric gases 


Not Applicable 


Not Applicable 


2,000 



For SI: 1 ton = 906 kg, 1 cubic foot = 0.02832 m 3 , 1 pound = 0.454 kg. 

a. For materials that are detonable, the distance to other buildings or lot lines shall be as specified in Table 415 .3. 1 based on trinitrotoluene (TNT) equivalence of the 
material. For materials classified as explosives, see Chapter 33 the International Fire Code. For all other materials, the distance shall be as indicated in Section 
415.3.1. 

b. "Maximum Allowable Quantity" means the maximum allowable quantity per control area set forth in Table 307.7(1) . 

c. Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco 
and Firearms (BATF) regulations or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing 
the net explosive weight of individual articles does not exceed 1 pound. 



[F] 415.6.1.2 Grinding rooms. Every room or space 
occupied for grinding or other operations that produce 
combustible dusts shall be enclosed with fire barriers 
constructed in accordance with Section 707 or horizon- 
tal assemblies constructed in accordance with Section 
712, or both. The minimum fire-resistance rating shall 
be 2 hours where the area is not more than 3,000 square 
feet (279 m 2 ) , and 4 hours where the area is greater than 
3,000 square feet (279 m 2 ). 

[F] 415.6.1.3 Conveyors. Conveyors, chutes, piping and 
similar equipment passing through the enclosures of 
rooms or spaces shall be constructed dirt tight and vapor 
tight, and be of approved noncombustible materials 
complying with Chapter 30. 

[F] 415.6.1.4 Explosion control. Explosion control 
shall be provided as specified in the International Fire 
Code, or spaces shall be equipped with the equivalent 
mechanical ventilation complying with the International 
Mechanical Code. 

\F] 415.6.1.5 Grain elevators. Grain elevators, malt 
houses and buildings for similar occupancies shall not be 
located within 30 feet (9144 mm) of interior lot lines or 
structures on the same lot, except where erected along a 
railroad right-of-way. 

[F] 415.6.1.6 Coal pockets. Coal pockets located less 
than 30 feet (9144 mm) from interior lot lines or from 



structures on the same lot shall be constructed of not less 
than Type IB construction. Where more than 30 feet 
(9144 mm) from interior lot lines, or where erected along 
a railroad right-of-way, the minimum type of construc- 
tion of such structures not more than 65 feet (19 812 mm) 
in building height shall be Type IV. 

\F] 415.6.2 Flammable and combustible liquids. The 
storage, handling, processing and transporting of flamma- 
ble and combustible liquids in Groups H-2 and H-3 occu- 
pancies shall be in accordance with Sections 415.6.2.1 
through 415.6.2.10, the International Mechanical Code and 
the International Fire Code. 

\F] 415.6.2.1 Mixed occupancies. Where the storage 
tank area is located in a building of two or more occupan- 
cies and the quantity of liquid exceeds the maximum 
allowable quantity for one control area, the use shall be 
completely separated from adjacent occupancies in 
accordance with the requirements of Section 508.4. 

[F] 415.6.2.1.1 Height exception. Where storage 
tanks are located within a building no more than one 
story above grade plane, the height limitation of Sec- 
tion 503 shall not apply for Group H. 

[F] 415.6.2.2 Tank protection. Storage tanks shall be 
noncombustible and protected from physical damage. 
Fire barriers or horizontal assemblies or both around the 



2009 INTERNATIONAL BUILDING CODE® 



67 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



storage tank(s) shall be permitted as the method of pro- 
tection from physical damage. 

[F] 415.6.2.3 Tanks. Storage tanks shall be approved 
tanks conforming to the requirements of the Interna- 
tional Fire Code. 

\F] 415.6.2.4 Suppression. Group H shall be equipped 
throughout with an approved automatic sprinkler sys- 
tem, installed in accordance with Section 903 . 

[F] 415.6.2.5 Leakage containment. A liquid-tight con- 
tainment area compatible with the stored liquid shall be 
provided. The method of spill control, drainage control 
and secondary containment shall be in accordance with 
the International Fire Code. 

Exception: Rooms where only double-wall storage 
tanks conforming to Section 415.6.2.3 are used to 
store Class I, II and MA flammable and combustible 
liquids shall not be required to have a leakage contain- 
ment area. 

[F] 415.6.2.6 Leakage alarm. An approved automatic 
alarm shall be provided to indicate a leak in a storage 
tank and room. The alarm shall sound an audible signal, 
15 dBa above the ambient sound level, at every point of 
entry into the room in which the leaking storage tank is 
located. An approvedsign shall be posted on every entry 
door to the tank storage room indicating the potential 
hazard of the interior room environment, or the sign shall 
state: WARNING, WHEN ALARM SOUNDS, THE 
ENVIRONMENT WITHIN THE ROOM MAY BE 
HAZARDOUS. The leakage alarm shall also be super- 
vised in accordance with Chapter 9 to transmit a trouble 
signal. 

[F] 415.6.2.7 Tank vent. Storage tank vents for Class I, 
II or I1IA liquids shall terminate to the outdoor air in 
accordance with the International Fire Code. 

\F] 415.6.2.8 Room ventilation. Storage tank areas stor- 
ing Class I, II or MA liquids shall be provided with 
mechanical ventilation. The mechanical ventilation sys- 
tem shall be in accordance with the International 
Mechanical Code and the International Fire Code. 

[F] 415.6.2.9 Explosion venting. Where Class I liquids 
are being stored, explosion venting shall be provided in 
accordance with the International Fire Code. 

[F] 415.6.2.10 Tank openings other than vents. Tank 
openings other than vents from tanks inside buildings 
shall be designed to ensure that liquids or vapor concen- 
trations are not released inside the building. 

[F] 415.6.3 Liquefied petroleum gas facilities. The con- 
struction and installation of liquefied petroleum gas facili- 
ties shall be in accordance with the requirements of this 
code, the International Fire Code, the International 
Mechanical Code, the International Fuel Gas Code and 
NFPA58. 



[F] 415.6.4 Dry cleaning plants. The construction and 
installation of dry cleaning plants shall be in accordance 
with the requirements of this code, the International 
Mechanical Code, the International Plumbing Code and 
NFPA 32. Dry cleaning solvents and systems shall be classi- 
fied in accordance with the International Fire Code. 

[F] 415.7 Groups H-3 and H-4. Groups H-3 and H-4 shall be 
constructed in accordance with the applicable provisions of 
this code and the International Fire Code. 

[F] 415.7.1 Flammable and combustible liquids. The 
storage, handling, processing and transporting of flamma- 
ble and combustible liquids in Group H-3 occupancies shall 
be in accordance with Section 415.6.2. 

[F] 415.7.2 Gas rooms. When gas rooms are provided, such 
rooms shall be separated from other areas by not less than 
I-hom fire barriers constructed in accordance with Section 
707 or horizontal assemblies constructed in accordance 
with Section 712, or both. 

[F] 415.7.3 Floors in storage rooms. Floors in storage 
areas for corrosive liquids and highly toxic or toxic materials 
shall be of liquid- tight, noncombustible construction. 

[F] 415.7.4 Separation-highly toxic solids and liquids. 
Highly toxic solids and liquids not stored in approvedhaz- 
ardous materials storage cabinets shall be isolated from 
other hazardous materials storage by not less than I-hour 
fire barriers constructed in accordance with Section 707 or 
horizontal assemblies constructed in accordance with Sec- 
tion 712, or both. 

[F] 415.8 Group H-5. 

[F] 415.8.1 General. In addition to the requirements set 
forth elsewhere in this code, Group H-5 shall comply with 
the provisions of Sections 415.8.1 through 415.8.11 and the 
International Fire Code. 

\F] 415.8.2 Fabrication areas. 

[F] 415.8.2.1 Hazardous materials in fabrication 
areas. 

[F] 415.8.2.1.1 Aggregate quantities. The aggregate 
quantities of hazardous materials stored and used in a 
single fabrication area shall not exceed the quantities 
set forth in Table 415.8.2.1.1. 

Exception: The quantity limitations for any haz- 
ard category in Table 415.8.2.1.1 shall not apply 
where the fabrication area contains quantities of 
hazardous materials not exceeding the maximum 
allowable quantities per control area established 
by Tables 307.1 (1) and 307.1 (2). 

[F] 415.8.2.1.2 Hazardous production materials. 
The maximum quantities of hazardous production 
materials (HPM) stored in a single fabrication area 
shall not exceed the maximum allowable quantities 
per control area established by Tables 307.1 (1) and 
307.1(2). 



68 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] TABLE 415.8.2.1.1 
QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN A SINGLE FABRICATION AREA IN GROUP H-5 a 



HAZARD CATEGORY 


SOLIDS 
(pounds per square feet) 


LIQUIDS 
(gallons per square feet) 


GAS 
(feet 3 @ NTP/square feet) 


PHYSICAL-HAZARD MATERIALS 


Combustible dust 


Note b 


Not Applicable 


Not Applicable 


Combustible fiber Loose 
Baled 


Note b 
Notes b,c 


Not Applicable 


Not Applicable 


Combustible liquid II 

I1IA 
I1JB 

Combination Class I, II and MA 


Not Applicable 


0.01 

0.02 

Not Limited 

0.04 


Not Applicable 


Cryogenic gas Flammable 
Oxidizing 


Not Applicable 


Not Applicable 


Noted 
1.25 


Explosives 


Note b 


Note b 


Note b 


Flammable gas Gaseous 
Liquefied 


Not Applicable 


Not Applicable 


Noted 
Noted 


Flammable liquid IA 
IB 
IC 

Combination Class 1A,IB and IC 
Combination Class I, II and MA 


Not Applicable 


0.0025 
0.025 
0.025 
0.025 
0.04 


Not Applicable 


Flammable solid 


0.001 


Not Applicable 


Not Applicable 


Organic peroxide 

Unclassified detonable 
Class I 
Class II 
Class m 
Class IV 
Class V 


Note b 

Note b 

0.025 

0.1 

Not Limited 

Not limited 


Not Applicable 


Not Applicable 


Oxidizing gas Gaseous 
Liquefied 

Combination of gaseous 
and liquefied 


Not Applicable 


Not Applicable 


1.25 
1.25 

1.25 


Oxidizer Class 4 
Class 3 
Class 2 
Class 1 

Combination Class 1, 2,3 


Note b 
0.003 
0.003 
0.003 
0.003 


Note b 
0.03 
0.03 
0.03 
0.03 


Not Applicable 


Pyrophoric material 


Noteb 


0.00125 


Notes d and e 


Unstable reactive Class 4 
Class 3 
Class 2 
Class 1 


Note b 

0.025 

0.1 

Not Limited 


Note b 

0.0025 

0.01 

Not Limited 


Note b 

Note b 

Note b 

Not Limited 


Water reactive Class 3 
Class 2 
Class 1 


Note b 

0.25 

Not Limited 


0.00125 

0.025 

Not Limited 


Not Applicable 


HEALTH-HAZARD MATERIALS 


Corrosives 


Not Limited 


Not Limited 


Not Limited 


Highly toxic 


Not Limited 


Not Limited 


Noted 


Toxics 


Not Limited 


Not Limited 


Noted 



For SI: 1 pound per square foot = 4.882 kg/m 2 , 1 gallon per square foot = 40.7 L/m 2 , 1 cubic foot @ NTP/square foot = 0.305 m 3 @ NTP/m 2 , 
1 cubic foot = 0.02832 m 3 . 

a. Hazardous materials within piping shall not be included in the calculated quantities. 

b. Quantity of hazardous materials in a single fabrication shall not exceed the maximum allowable quantities per control area in Tables 307.1(1) and 307.1(2). 

c. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class. 

d. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 cubic feet at NTP. 

e. The aggregate quantity ofpyrophoric gases in the building shall not exceed the amounts set forth in Table 415.3.2. 



2009 INTERNATIONAL BUILDING CODE® 



69 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] 415.8.2.2 Separation. Fabrication areas, whose 
sizes are limited by the quantity of hazardous materials 
allowed by Table 415.8.2.1.1, shall be separated from 
each other, from corridors and from other parts of the 
building by not less than l-hour fire barriers constructed 
in accordance with Section 707 or horizontal assemblies 
constructed in accordance with Section 712, or both. 

Exceptions: 

1. Doors within such //re barrier walls, including 
doors to corridors, shall be only self-closing 
fire door assemblies having a fire protection 
rating of not less than 3/ 4 hour. 

2. Windows between fabrication areas and cor- 
ridors are permitted to be fixed glazing listed 
and labeled for a fire protection rating of at 
least 3/ 4 hour in accordance with Section 715. 

[F] 415.8.2.3 Location of occupied levels. Occupied 
levels of fabrication areas shall be located at or above the 
first story above grade plane. 

[F] 415.8.2.4 Floors. Except for surfacing, floors within 
fabrication areas shall be of noncombustible construc- 
tion. 

Openings through floors of fabrication areas are per- 
mitted to be unprotected where the interconnected levels 
are used solely for mechanical equipment directly 
related to such fabrication areas (see also Section 
415.8.2.5). 

Floors forming a part of an occupancy separation shall 
be liquid tight. 

[F] 415.8.2.5 Shafts and openings through floors. Ele- 
vator shafts, vent shafts and other openings through 
floors shall be enclosed when required by Section 708. 
Mechanical, duct and piping penetrations within a fabri- 
cation area shall not extend through more than two 
floors. The annular space around penetrations for 
cables, cable trays, tubing, piping, conduit or ducts shall 
be sealed at the floor level to restrict the movement of air. 
The fabrication area, including the areas through which 
the ductwork and piping extend, shall be considered a 
single conditioned environment. 

[F] 415.8.2.6 Ventilation. Mechanical exhaust ventila- 
tion at the rate of not less than 1 cubic foot per minute per 
square foot [0.0051 m 3 /(s .m 2 )] of floor area shall be pro- 
vided throughout the portions of the fabrication area 
where HPM are used or stored. The exhaust air duct sys- 
tem of one fabrication area shall not connect to another 
duct system outside that fabrication area within the 
building. 

A ventilation system shall be provided to capture and 
exhaust gases, fumes and vapors at workstations. 

Two or more operations at a workstation shall not be 
connected to the same exhaust system where either one 
or the combination of the substances removed could con- 
stitute a fire, explosion or hazardous chemical reaction 
within the exhaust duct system. 



Exhaust ducts penetrating occupancy separations 
shall be contained in a shaft of equivalent fire-resis- 
tance-rated construction. Exhaust ducts shall not pene- 
trate fire walls. 

Fire dampers shall not be installed in exhaust ducts. 

[F] 415.8.2.7 Transporting hazardous production 
materials to fabrication areas. HPM shall be trans- 
ported to fabrication areas through enclosed piping or 
tubing systems that comply with Section 415.8.6.1, 
through service corridors complying with Section 
415.8.4, or in corridors as permitted in the exception to 
Section 415.8.3. The handling or transporting of HPM 
within service corridors shall comply with the Interna- 
tional Fire Code. 

[F] 415.8.2.8 Electrical. 

[F] 415.8.2.8.1 General. Electrical equipment and 
devices within the fabrication area shall comply with 
NFPA 70. The requirements for hazardous locations 
need not be applied where the average air change is at 
least four times that set forth in Section 415.8.2.6 and 
where the number of air changes at any location is not 
less than three times that required by Section 
415.8.2.6. The use of recirculated air shall be permit- 
ted. 

\F] 415.8.2.8.2 Workstations. Workstations shall not 
be energized without adequate exhaust ventilation. 
See Section 415.8.2.6 for workstation exhaust venti- 
lation requirements. 

[F] 415.8.3 Corridors. Corridors shall comply with Chap- 
ter 10 and shall be separated from fabrication areas as speci- 
fied in Section 415.8.2.2. Corridors shall not contain HPM 
and shall not be used for transporting such materials, except 
through closed piping systems as provided in Section 
415.8.6.3. 

Exception: Where existing fabrication areas are altered 
or modified, HPM is allowed to be transported in existing 
corridors, subject to the following conditions: 

1. Corridors. Corridors adjacent to the fabrication 
area where the alteration work is to be done shall 
comply with Section 1018 for a length determined 
as follows: 

1.1. The length of the common wall of the cor- 
ridor and the fabrication area; and 

1.2. For the distance along the corridor to the 
point of entry of HPM into the corridor 
serving that fabrication area. 

2. Emergency alarm system. There shall be an emer- 
gency telephone system, a local manual alarm sta- 
tion or other approved alarm-initiating device 
within corridors at not more than ISO-foot (45720 
mm) intervals and at each exit and doorway. The 
signal shall be relayed to an approve d central, pro- 
prietary or remote station service or the emergency 
control station and shall also initiate a local audible 
alarm. 



70 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



3. Pass-throughs. Self-closing doors having a fire 
protection rating of 'not less than 1 hour shall sepa- 
rate pass-throughs from existing corridors. 
Pass-throughs shall be constructed as required for 
the corridors and protected by an approved auto- 
matic fire-extinguishing system. 

[F] 415.8.4 Service corridors. 

[F] 415.8.4.1 Occupancy. Service corridors shall be 
classified as Group H-5. 

[F] 415.8.4.2 Use conditions. Service corridors shall be 
separated from corridors as required by Section 
415.8.2.2. Service corridors shall not be used as a 
required corridor. 

[F] 415.8.4.3 Mechanical ventilation. Service corridors 
shall be mechanically ventilated as required by Section 
415.8.2.6 or at not less than six air changes per hour, 
whichever is greater. 

[F] 415.8.4.4 Means of egress. The maximum distance 
of travel from any point in a service corridor to an exit, 
exit access corridor or door into a fabrication area shall 
not exceed 75 feet (22 860 mm). Dead ends shall not 
exceed 4 feet (1219 mm) in length. There shall be not less 
than two exits, and not more than one-half of the required 
means of egress shall require travel into a fabrication 
area. Doors from service corridors shall swing in the 
direction of egress travel and shall be self-closing. 

[F] 415.8.4.5 Minimum width. The minimum clear 
width of a service corridor shall be 5 feet (1524 mm), or 
33 inches (838 mm) wider than the widest cart or truck 
used in the corridor, whichever is greater. 

[F] 415.8.4.6 Emergency alarm system. Emergency 
alarm systems shall be provided in accordance with this 
section and Sections 414.7.1 and 414.7.2. The maximum 
allowable quantity per control area provisions shall not 
apply to emergency alarm systems required for HPM. 

[F] 415.8.4.6.1 Service corridors. An emergency 
alarm system shall be provided in service corridors, 
with at least one alarm device in each service corridor. 

[F] 415.8.4.6.2 Exit access corridors and exit enclo- 
sures. Emergency alarms for exit access corridors 
and exit enclosures shall comply with Section 
414.7.2. 

[F] 415.8.4.6.3 Liquid storage rooms, "PM rooms 
and gas rooms. Emergency alarms for liquid storage 
rooms, HPM rooms and gas rooms shall comply with 
Section 414.7.1. 

[F] 415.8.4.6.4 Alarm-initiating devices. An 
approved emergency telephone system, local alarm 
manual pull stations, or other approvedalarm-initiat- 
ing devices are allowed to be used as emergency 
alarm -initiating devices. 

[F] 415.8.4.6.5 Alarm signals. Activation of the 
emergency alarm system shall sound a local alarm 
and transmit a signal to the emergency control station. 



[F] 415.8.5 Storage of hazardous production materials. 

[F] 415.8.5.1 General. Storage of HPM in fabrication 
areas shall be within approved ox listed storage cabinets 
or gas cabinets or within a workstation. The storage of 
HPM in quantities greater than those listed in Section 
1804.2 of the International Fire Code shall be in liquid 
storage rooms, HPM rooms or gas rooms as appropriate 
for the materials stored. The storage of other hazardous 
materials shall be in accordance with other applicable 
provisions of this code and the International Fire Code. 

\F] 415.8.5.2 Construction. 

\F] 415.8.5.2.1 "PM rooms and gas rooms. HPM 
rooms and gas rooms shall be separated from other 
areas by fire barriers constructed in accordance with 
Section 707 or horizontal assemblies constructed in 
accordance with Section 712, or both. The minimum 
fire-resistance rating shall be 2 hours where the area 
is 300 square feet (27.9 m 2 ) or more and 1 hour where 
the area is less than 300 square feet (27.9 m 2 ). 

[F] 415.8.5.2.2 Liquid storage rooms. Liquid stor- 
age rooms shall be constructed in accordance with the 
following requirements: 

1. Rooms in excess of 500 square feet (46.5 m 2 ) 
shall have at least one exterior door approved 
for fire department access. 

2. Rooms shall be separated from other areas by 
fire barriers constructed in accordance with 
Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or 
both. The fire -resistance rating shall be not less 
than 1 hour for rooms up to 150 square feet 
(13.9 m 2 ) in area and not less than 2 hours where 
the room is more than 150 square feet (13.9 m 2 ) 
in area. 

3. Shelving, racks and wainscotting in such areas 
shall be of noncombustible construction or 
wood of not less than I-inch (25 mm) nominal 
thickness. 

4. Rooms used for the storage of Class I flamma- 
ble liquids shall not be located in a basement. 

[F] 415.8.5.2.3 Floors. Except for surfacing, floors of 
HPM rooms and liquid storage rooms shall be of 
noncombustible liquid-tight construction. Raised 
grating over floors shall be of noncombustible materi- 
als. 

[F] 415.8.5.3 Location. Where HPM rooms, liquid stor- 
age rooms and gas rooms are provided, they shall have at 
least one exterior walland such wall shall be not less than 
30 feet (9144 mm) from lotlines, including lotlines adja- 
cent to public ways. 

[F] 415.8.5.4 Explosion control. Explosion control 
shall be provided where required by Section 414.5.1. 



2009 INTERNATIONAL BUILDING CODE® 



71 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



\F] 415.8.5.5 Exits. Where two exits are required from 
HPM rooms, liquid storage rooms and gas rooms, one 
shall be directly to the outside of the building. 

[F] 415.8.5.6 Doors. Doors in afire barrier wall, includ- 
ing doors to corridors, shall be self-closing fire door 
assemblies having a fire-protection rating of not less 
than 3/ 4 hour. 

[F] 415.8.5.7 Ventilation. Mechanical exhaust ventila- 
tion shall be provided in liquid storage rooms, HPM 
rooms and gas rooms at the rate of not less than 1 cubic 
foot per minute per square foot (0.044 L/s/m 2 ) of floor 
area or six air changes per hour, whichever is greater, for 
categories of material. 

Exhaust ventilation for gas rooms shall be designed to 
operate at a negative pressure in relation to the surround- 
ing areas and direct the exhaust ventilation to an exhaust 
system. 

[F] 415.8.5.8 Emergency alarm system. An approved 
emergency alarm system shall be provided for HPM 
rooms, liquid storage rooms and gas rooms. 

Emergency alarm-initiating devices shall be installed 
outside of each interior exit door of such rooms. 

Activation of an emergency alarm-initiating device 
shall sound a local alarm and transmit a signal to the 
emergency control station. 

An approved emergency telephone system, local 
alarm manual pull stations or other approve d alarm -initi- 
ating devices are allowed to be used as emergency 
alarm -initiating devices. 

[F] 415.8.6 Piping and tubing. 

[F] 415.8.6.1 General. Hazardous production materials 
piping and tubing shall comply with this section and 
ASMEB31.3. 

[F] 415.8.6.2 Supply piping and tubing. 

[F] 415.8.6.2.1 "PM having a health-hazard rank- 
ing of 3 or 4. Systems supplying HPM liquids or 
gases having a health-hazard ranking of 3 or 4 shall be 
welded throughout, except for connections, to the 
systems that are within a ventilated enclosure if the 
material is a gas, or an approved method of drainage 
or containment is provided for the connections if the 
material is a liquid. 

[F] 415.8.6.2.2 Location in service corridors. Haz- 
ardous production materials supply piping or tubing 
in service corridors shall be exposed to view. 

[F] 415.8.6.2.3 Excess flow control. Where HPM 
gases or liquids are carried in pressurized piping 
above 15 pounds per square inch gauge (psig) (103.4 
kPa) , excess flow control shall be provided. Where 
the piping originates from within a liquid storage 
room, HPM room or gas room, the excess flow con- 
trol shall be located within the liquid storage room, 
HPM room or gas room. Where the piping originates 
from a bulk source, the excess flow control shall be 
located as close to the bulk source as practical. 



[F] 415.8.6.3 Installations in corridors and above 
other occupancies. The installation of HPM piping and 
tubing within the space defined by the walls of corridors 
and the floor or roof above, or in concealed spaces above 
other occupancies, shall be in accordance with Section 
415.8.6.2 and the following conditions: 

1. Automatic sprinklers shall be installed within the 
space unless the space is less than 6 inches (152 
mm) in the least dimension. 

2. Ventilation not less than six air changes per hour 
shall be provided. The space shall not be used to 
convey air from any other area. 

3. Where the piping or tubing is used to transport 
HPM liquids, a receptor shall be installed below 
such piping or tubing. The receptor shall be 
designed to collect any discharge or leakage and 
drain it to an approvedlocation. The I-hour enclo- 
sure shall not be used as part of the receptor. 

4. HPM supply piping and tubing and nonmetallic 
waste lines shall be separated from the corridor 
and from occupancies other than Group H-5 by 
fire barriers that have a fire-resistance rating of 
not less than 1 hour. Where gypsum wallboard is 
used, joints on the piping side of the enclosure are 
not required to be taped, provided the joints occur 
over framing members. Access openings into the 
enclosure shall be protected by approved fire pro- 
tection-rated assemblies. 

5. Readily accessible manual or automatic remotely 
activated fail-safe emergency shutoff valves shall 
be installed on piping and tubing other than waste 
lines at the following locations: 

5.1. At branch connections into the fabrication 
area. 

5.2. At entries into corridors. 

Exception: Transverse crossings of the 
corridors by supply piping that is 
enclosed within a ferrous pipe or tube for 
the width of the corridorneed not comply 
with Items 1 through 5. 

[F] 415.8.6.4 Identification. Piping, tubing and HPM 
waste lines shall be identified in accordance with ANSI 
A 13.1 to indicate the material being transported. 

[F] 415.8.7 Continuous gas detection systems. A continu- 
ous gas detection system shall be provided for HPM gases 
when the physiological warning threshold level of the gas is 
at a higher level than the accepted PEL for the gas and for 
flammable gases in accordance with Sections 415.8.7.1 and 
415.8.7.2. 

[F] 415.8.7.1 Where required. A continuous gas detec- 
tion system shall be provided in the areas identified in 
Sections 415.8.7.1.1 through 415.8.7.1.4. 

[F] 415.8.7.1.1 Fabrication areas. A continuous gas 
detection system shall be provided in fabrication 
areas when gas is used in the fabrication area. 



72 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[¥] 415.8.7.1.2 TM rooms. A continuous gas 
detection system shall be provided in HPM rooms 
when gas is used in the room. 

[F] 415.8.7.1.3 Gas cabinets, exhausted enclosures 
and gas rooms. A continuous gas detection system 
shall be provided in gas cabinets and exhausted enclo- 
sures. A continuous gas detection system shall be pro- 
vided in gas rooms when gases are not located in gas 
cabinets or exhausted enclosures. 

[F] 415.8.7.1.4 Corridors. When gases are trans- 
ported in piping placed within the space defined by 
the walls of a corridor and the floor or roof above the 
corridor, a continuous gas detection system shall be 
provided where piping is located and in the corridor. 

Exception: A continuous gas detection system is 
not required for occasional transverse crossings of 
the corridors by supply piping that is enclosed in a 
ferrous pipe or tube for the width of the corridor. 

[F] 415.8.7.2 Gas detection system operation. The 
continuous gas detection system shall be capable of 
monitoring the room, area or equipment in which the gas 
is located at or below all the following gas concentra- 
tions: 

1. Immediately dangerous to life and health (IDLH) 
values when the monitoring point is within an 
exhausted enclosure, ventilated enclosure or gas 
cabinet. 

2. Permissible exposure limit (PEL) levels when the 
monitoring point is in an area outside an exhausted 
enclosure, ventilated enclosure or gas cabinet. 

3. For flammable gases, the monitoring detection 
threshold level shall be vapor concentrations in 
excess of 25 percent of the lower flammable limit 
(LFL) when the monitoring is within or outside an 
exhausted enclosure, ventilated enclosure or gas 
cabinet. 

4. Except as noted in this section, monitoring for 
highly toxic and toxic gases shall also comply with 
Chapter 37 of the International Fire Code. 

\F] 415.8.7.2.1 Alarms. The gas detection system 
shall initiate a local alarm and transmit a signal to the 
emergency control station when a short-term hazard 
condition is detected. The alarm shall be both visual 
and audible and shall provide warning both inside and 
outside the area where the gas is detected. The audible 
alarm shall be distinct from all other alarms. 

[F] 415.8.7.2.2 Shutoff ofgas supply. The gas detec- 
tion system shall automatically close the shutoff valve 
at the source on gas supply piping and tubing related 
to the system being monitored for which gas is 
detected when a short-term hazard condition is 
detected. Automatic closure of shutoff valves shall 
comply with the following: 

1. Where the gas detection sampling point initiat- 
ing the gas detection system alarm is within a 
gas cabinet or exhausted enclosure, the shutoff 



valve in the gas cabinet or exhausted enclosure 
for the specific gas detected shall automatically 
close. 

2. Where the gas detection sampling point initiat- 
ing the gas detection system alarm is within a 
room and compressed gas containers are not in 
gas cabinets or an exhausted enclosure, the 
shutoff valves on all gas lines for the specific 
gas detected shall automatically close. 

3. Where the gas detection sampling point initiat- 
ing the gas detection system alarm is within a 
piping distribution manifold enclosure, the 
shutoff valve supplying the manifold for the 
compressed gas container of the specific gas 
detected shall automatically close. 

Exception: Where the gas detection sampling 
point initiating the gas detection system alarm is at 
the use location or within a gas valve enclosure of a 
branch line downstream of a piping distribution 
manifold, the shutoff valve for the branch line 
located in the piping distribution manifold enclo- 
sure shall automatically close. 

[F] 415.8.8 Manual fire alarm system. An approvedman- 
ual fire alarm system shall be provided throughout buildings 
containing Group H-5. Activation of the alarm system shall 
initiate a local alarm and transmit a signal to the emergency 
control station. The fire alarm system shall be designed and 
installed in accordance with Section 907. 

[F] 415.8.9 Emergency control station. An emergency 
control station shall be provided in accordance with Sec- 
tions 415.8.9.1 through 415.8.9.3. 

[F] 415.8.9.1 Location. The emergency control station 
shall be located on the premises at an approvedlocation 
outside the fabrication area. 

[F] 415.8.9.2 Staffing. Trained personnel shall continu- 
ously staff the emergency control station. 

[F] 415.8.9.3 Signals. The emergency control station 
shall receive signals from emergency equipment and 
alarm and detection systems. Such emergency equip- 
ment and alarm and detection systems shall include, but 
not be limited to, the following where such equipment or 
systems are required to be provided either in this chapter 
or elsewhere in this code: 

1. Automatic sprinkler system alarm and monitoring 
systems. 

2. Manual fire alarm systems. 

3. Emergency alarm systems. 

4. Continuous gas detection systems. 

5. Smoke detection systems. 

6. Emergency power system. 

7. Automatic detection and alarm systems for 
pyrophoric liquids and Class 3 water-reactive liq- 
uids required in Section 1805.2.3.4 of the Interna- 
tional Fire Code. 



2009 INTERNATIONAL BUILDING CODE® 



73 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



8. Exhaust ventilation flow alarm devices for 
pyrophoric liquids and Class 3 water-reactive liq- 
uids cabinet exhaust ventilation systems required 
in Section 1805.2.3.4 of the International Fire 
Code. 

[F] 415.8.10 Emergency power system. An emergency 
power system shall be provided in Group H-5 occupancies 
where required in Section 415.8.10.1. The emergency 
power system shall be designed to supply power automati- 
cally to required electrical systems when the normal electri- 
cal supply system is interrupted. 

[F] 415.8.10.1 Required electrical systems. Emer- 
gency power shall be provided for electrically operated 
equipment and connected control circuits for the follow- 
ing systems: 

1. HPM exhaust ventilation systems. 

2. HPM gas cabinet ventilation systems. 

3. HPM exhausted enclosure ventilation systems. 

4. HPM gas room ventilation systems. 

5. HPM gas detection systems. 

6. Emergency alarm systems. 

7. Manual fire alarm systems. 

8. Automatic sprinkler system monitoring and 
alarm systems. 

9. Automatic alarm and detection systems for 
pyrophoric liquids and Class 3 water-reactive 
liquids required in Section 1805.2.3.4 of the 
International Fire Code. 

10. Flow alarm switches for pyrophoric liquids and 
Class 3 water-reactive liquids cabinet exhaust 
ventilation systems required in Section 
1805.2.3.4 of the International Fire Code. 

11. Electrically operated systems required elsewhere 
in this code or in the International Fire Code 
applicable to the use, storage or handling of 
HPM. 

[F] 415.8.10.2 Exhaust ventilation systems. Exhaust 
ventilation systems are allowed to be designed to operate 
at not less than one-half the normal fan speed on the 
emergency power system where it is demonstrated that 
the level of exhaust will maintain a safe atmosphere. 

[F] 415.8.11 Automatic sprinkler system protection in 
exhaust ducts for "PM. 

[F] 415.8.11.1 Exhaust ducts for "PM. An approved 
automatic sprinkler system shall be provided in exhaust 
ducts conveying gases, vapors, fumes, mists or dusts 
generated from HPM in accordance with this section and 
the International Mechanical Code. 

[F] 415.8.11.2 Metallic and noncombustible nonme- 
tallic exhaust ducts. An approved automatic sprinkler 
system shall be provided in metallic and noncombustible 



nonmetallic exhaust ducts when all of the following con- 
ditions apply: 

1. Where the largest cross-sectional diameter is equal 
to or greater than 10 inches (254 mm). 

2. The ducts are within the building. 

3. The ducts are conveying flammable gases, vapors 
or fumes. 

[F] 415.8.11.3 Combustible nonmetallic exhaust 
ducts. Automatic sprinkler system protection shall be 
provided in combustible nonmetallic exhaust ducts 
where the largest cross-sectional diameter of the duct is 
equal to or greater than 10 inches (254 mm). 

Exceptions: 

1. Ducts listed or approvedfor applications with- 
out automatic fire sprinkler system protection. 

2. Ducts not more than 12 feet (3658 mm) in 
length installed below ceiling level. 

[F] 415.8.11.4 Automatic sprinkler locations. Sprin- 
kler systems shall be installed at 12-foot (3658 mm) 
intervals in horizontal ducts and at changes in direction. 
In vertical ducts, sprinklers shall be installed at the top 
and at alternate floor levels. 



SECTION 416 
APPLICATION OF FLAMMABLE FINISHES 

[F] 416.1 General. The provisions of this section shall apply to 
the construction, installation and use of buildings and struc- 
tures, or parts thereof, for the spraying of flammable paints, 
varnishes and lacquers or other flammable materials or mix- 
tures or compounds used for painting, varnishing, staining or 
similar purposes. Such construction and equipment shall com- 
ply with the International Fire Code. 

\F] 416.2 Spray rooms. Spray rooms shall be enclosed with 
not less than I-hour fire barriers constructed in accordance 
with Section 707 or horizontal assemblies constructed in 
accordance with Section 712, or both. Floors shall be water- 
proofed and drained in an app roved manner. 

[F] 416.2.1 Surfaces. The interior surfaces of spray rooms 
shall be smooth and shall be so constructed to permit the 
free passage of exhaust air from all parts of the interior and 
to facilitate washing and cleaning, and shall be so designed 
to confine residues within the room. Aluminum shall not be 
used. 

[F] 416.3 Spraying spaces. Spraying spaces shall be venti- 
lated with an exhaust system to prevent the accumulation of 
flammable mist or vapors in accordance with the International 
Mechanical Code. Where such spaces are not separately 
enclosed, noncombustible spray curtains shall be provided to 
restrict the spread of flammable vapors. 

[F] 416.3.1 Surfaces. The interior surfaces of spraying 
spaces shall be smooth and continuous without edges; shall 
be so constructed to permit the free passage of exhaust air 
from all parts of the interior and to facilitate washing and 



74 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



cleaning; and shall be so designed to confine residues within 
the spraying space. Aluminum shall not be used. 

[F] 416.4 Spray booths. Spray booths shall be designed, con- 
structed and operated in accordance with the International Fire 
Code. 

\F] 416.5 Fire protection. An automatic fire-extinguishing 
system shall be provided in all spray, dip and immersing spaces 
and storage rooms and shall be installed in accordance with 
Chapter 9. 



SECTION 417 
DRYING ROOMS 

[F] 417.1 General. A drying room or dry kiln installed within a 
building shall be constructed entirely of approved 
noncombustible materials or assemblies of such materials reg- 
ulated by the approve d rules or as required in the general and 
specific sections of Chapter 4 for special occupancies and 
where applicable to the general requirements of Chapter 28. 

[F] 417.2 Piping clearance. Overhead heating pipes shall have 
a clearance of not less than 2 inches (51 mm) from combustible 
contents in the dryer. 

[F] 417.3 Insulation. Where the operating temperature of the 
dryer is 175°F (79°C) or more, metal enclosures shall be insu- 
lated from adjacent combustible materials by not less than 12 
inches (305 mm) of airspace, or the metal walls shall be lined 
with 1/4-inch (6.35 mm) insulating mill board or other approved 
equivalent insulation. 

[F] 417.4 Fire protection. Drying rooms designed for 
high-hazard materials and processes, including special occu- 
pancies as provided for in Chapter 4, shall be protected by an 
approve d automatic fire-extinguishing system complying with 
the provisions of Chapter 9. 



SECTION 418 
ORGANIC COATINGS 

[F] 418.1 Building features. Manufacturing of organic coat- 
ings shall be done only in buildings that do not have pits or 
basements. 

[F] 418.2 Location. Organic coating manufacturing opera- 
tions and operations incidental to or connected therewith shall 
not be located in buildings having other occupancies. 

[F] 418.3 Process mills. Mills operating with close clearances 
and that process flammable and heat-sensitive materials, such 
as nitrocellulose, shall be located in a detached building or 
noncombustible structure. 

[F] 418.4 Tank storage. Storage areas for flammable and com- 
bustible liquid tanks inside of structures shall be located at or 
above grade and shall be separated from the processing area by 
not less than 2-hour fire barriers constructed in accordance 
with Section 707 or horizontal assemblies constructed in 
accordance with Section 712, or both. 

[F] 418.5 Nitrocellulose storage. Nitrocellulose storage shall 
be located on a detached pad or in a separate structure or a room 
enclosed with no less than 2-hour fire barriers constructed in 



accordance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. 

[F] 418.6 Finished products. Storage rooms for finished prod- 
ucts that are flammable or combustible liquids shall be sepa- 
rated from the processing area by not less than 2-hour fire 
barriers constructed in accordance with Section 707 or hori- 
zontal assemblies constructed in accordance with Section 712, 
or both. 



SECTION 419 
LIVE/WORK UNITS 

419.1 General. A live/work unit is a dwelling unit or sleeping 
unitin which a significant portion of the space includes a non- 
residential use that is operated by the tenant and shall comply 
with Sections 419.1 through 419.8. 

Exception: Dwelling or sleeping units that include an 
office that is less than 10 percent of the area of the dwell- 
ing unit shall not be classified as a live/work unit. 

419.1.1 Limitations. The following shall apply to all 
live/work areas: 

1. The live/work unit is permitted to be a maximum of 
3,000 square feet (279 m 2 ); 

2. The nonresidential area is permitted to be a maximum 
50 percent of the area of each live/work unit; 

3. The nonresidential area function shall be limited to 
the first or main floor only of the live/work unit; and 

4. A maximum of five nonresidential workers or 
employees are allowed to occupy the nonresidential 
area at anyone time. 

419.2 Occupancies. Live/work units shall be classified as a 
Group R-2 occupancy. Separation requirements found in Sec- 
tions 420 and 508 shall not apply within the live/work unit 
when the live/work unit is in compliance with Section 419. 
High-hazard and storage occupancies shall not be permitted in 
a live/work unit. The aggregate area of storage in the nonresi- 
dential portion of the live/work unit shall be limited to 10 per- 
cent of the space dedicated to nonresidential activities. 

419.3 Means of egress. Except as modified by this section, the 
provisions for Group R-2 occupancies in Chapter 10 shall 
apply to the entire live/work unit. 

419.3.1 Egress capacity. The egress capacity for each ele- 
ment of the live/work unit shall be based on the occupant 
load for the function served in accordance with Table 
1004.1.1. 

419.3.2 Sliding doors. Where doors in a means ofegress&iz 
of the horizontal- sliding type, the force to slide the door to 
its fully open position shall not exceed 50 pounds (220 N) 
with a perpendicular force against the door of 50 pounds 
(220 N). 

419.3.3 Spiral stairways. Spiral stairways that conform to 
the requirements of Section 1009.9 shall be permitted. 

4193 A Locks. Egress doors shall be permitted to be locked 
in accordance with Exception 4 of Section 1008.1.9.3. 



2009 INTERNATIONAL BUILDING CODE® 



75 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



419.4 Vertical openings. Floor openings between floor levels 
of a live/work unit are permitted without enclosure. 

419.5 Fire protection. The live/work unit shall be provided 
with a monitored fire alarm system where required by Section 
907.2.9 and an automatic sprinkler system in accordance with 
Section 903.2.8. 

419.6 Structural. Floor loading for the areas within a 
live/work unit shall be designed to conform to Table 1607.1 
based on the function within the space. 

419.7 Accessibility. Accessibility shall be designed in accor- 
dance with Chapter 11. 

419.8 Ventilation. The applicable requirements of the Interna- 
tional Mechanical Code shall apply to each area within the 
live/work unit for the function within that space. 



SECTION 420 
GROUPS 1-1, R-1, R-2, R-3 

420.1 General. Occupancies in Groups 1-1, R-1, R-2 and R-3 
shall comply with the provisions of this section and other appli- 
cable provisions of this code. 

420.2 Separation walls. Walls separating dwelling units in the 
same building, walls separating sleeping units in the same 
building and walls separating dwelling or sleeping units from 
other occupancies contiguous to them in the same building 
shall be constructed as fire partitions in accordance with Sec- 
tion 709. 

420.3 Horizontal separation. Floor assemblies separating 
dwelling units in the same buildings, floor assemblies separat- 
ing sleeping units in the same building and floor assemblies 
separating dwelling or sleeping units from other occupancies 
contiguous to them in the same building shall be constructed as 
horizontal assemblies in accordance with Section 712. 



SECTION 421 
HYDROGEN CUTOFF ROOMS 

[F] 421.1 General. When required by the International Fire 
Code, hydrogen cutoff rooms shall be designed and con- 
structed in accordance with Sections 421.1 through 421.8. 

[F] 421.2 Definitions. The following words and terms shall, 
for the purposes of this chapter and as used elsewhere in this 
code, have the meanings shown herein. 

[F] GASEOUS HYDROGEN SYSTEM. An assembly of 
piping, devices and apparatus designed to generate, store, con- 
tain, distribute or transport a nontoxic, gaseous hydrogen-con- 
taining mixture having at least 95-percent hydrogen gas by 
volume and not more than I-percent oxygen by volume. Gas- 
eous hydrogen systems consist of items such as compressed 
gas containers, reactors and appurtenances, including pressure 
regulators, pressure relief devices, manifolds, pumps, com- 
pressors and interconnecting piping and tubing and controls. 

\F] HYDROGEN CUTOFF ROOM. A room or space that is 
intended exclusively to house a gaseous hydrogen system. 

[F] 421.3 Location. Hydrogen cutoff rooms shall not be 
located below grade. 



[F] 421.4 Design and construction. Hydrogen cutoff rooms 
shall be classified with respect to occupancy in accordance 
with Section 302.1 and separated from other areas of the build- 
ing by not less than I-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies constructed in 
accordance with Section 712, or both; or as required by Section 
508.2, 508.3 or 508.4, as applicable. 

[F] 421.4.1 Opening protectives. Doors within the fire bar- 
riers, including doors to corridors, shall be self-closing in 
accordance with Section 715. Interior door openings shall 
be electronically interlocked to prevent operation of the 
hydrogen system when doors are opened or ajar or the room 
shall be provided with a mechanical exhaust ventilation sys- 
tem designed in accordance with Section 421.4.1.1. 

[F] 421.4.1.1 Ventilation alternative. When an exhaust 
system is used in lieu of the interlock system required by 
Section 421.4.1, exhaust ventilation systems shall oper- 
ate continuously and shall be designed to operate at a 
negative pressure in relation to the surrounding area. The 
average velocity of ventilation at the face of the door 
opening with the door in the fully open position shall not 
be less than 60 feet per minute (0.3048 m/s) with a mini- 
mum of 45 feet per minute (0.2287 m/s) at any point in 
the door opening. 

[F] 421.4.2 Windows. Operable windows in interior walls 
shall not be permitted. Fixed windows shall be permitted 
when in accordance with Section 715. 

[F] 421.5 Ventilation. Cutoff rooms shall be provided with 
mechanical ventilation in accordance with the applicable pro- 
visions for repair garages in Chapter 5 of the International 
Mechanical Code. 

[F] 421.6 Gas detection system. Hydrogen cutoff rooms shall 
be provided with an approved flammable gas detection system 
in accordance with Sections 421 .6.1 through 421 .6.3. 

[F] All. 6.1 System design. The flammable gas detection 
system shall be listed for use with hydrogen and any other 
flammable gases used in the room. The gas detection system 
shall be designed to activate when the level of flammable 
gas exceeds 25 percent of the lower flammability limit 
(LFL) for the gas or mixtures present at their anticipated 
temperature and pressure. 

[F] 421.6.2 Operation. Activation of the gas detection sys- 
tem shall result in all of the following: 

1. Initiation of distinct audible and visual alarm signals 
both inside and outside of the cutoff room. 

2. Activation of the mechanical ventilation system. 

[F] 421.6.3 Failure of the gas detection system. Failure of 
the gas detection system shall result in activation of the 
mechanical ventilation system, cessation of hydrogen gen- 
eration and the sounding of a trouble signal in an approved 
location. 

[F] 421.7 Explosion control. Explosion control shall be pro- 
vided in accordance with Chapter 9 of the International Fire 
Code. 



76 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY 



[F] 421.8 Standby power. Mechanical ventilation and gas 
detection systems shall be connected to a standby power sys- 
tem in accordance with Chapter 27. 



Residential storm shelter. A storm shelter serving occu- 
pants of dwelling units and having an occupant load not 
exceeding 16 persons. 



i 



SECTION 422 
AMBULATORY HEALTH CARE FACILITIES 

422.1 General. Occupancies classified as Group B ambulatory 
health care facilities shall comply with the provisions of Sec- 
tions 422.1 through 422.6 and other applicable provisions of 
this code. 

422.2 Smoke barriers. Smoke barriers shall be provided to 
subdivide every ambulatory care facility greater than 10,000 
square feet (929 m 2 ) into a minimum of two smoke compart- 
ments per story. The travel distance from any point in a smoke 
compartment to a smoke barrier door shall not exceed 200 feet 
(60 960 mm). The smoke barrier shall be installed in accor- 
dance with Section 710. 

422.3 Refuge area. At least 30 net square feet (2.8 m 2 ) per 
nonambulatory patient shall be provided within the aggregate 
area of corridors, patient rooms, treatment rooms, lounge or 
dining areas and other low-hazard areas on each side of each 
smoke barrier. 

422.4 Independent egress. A means of egress shall be pro- 
vided from each smoke compartment created by smoke barri- 
ers without having to return through the smoke compartment 
from which means of egress originated. 

422.5 Automatic sprinkler systems. Automatic sprinkler sys- 
tems shall be provided for ambulatory care facilities in accor- 
dance with Section 903.2.2. 

422.6 Fire alarm systems. A fire alarm system shall be pro- 
vided in accordance with Section 907.2.2.1. 



SECTION 423 
STORM SHELTERS 

423.1 General. In addition to other applicable requirements in 
this code, storm shelters shall be constructed in accordance 
with ICC-SOO. 

423.1.1 Scope. This section applies to the construction of 
storm shelters constructed as separate detached buildings or 
constructed as safe rooms within buildings for the purpose 
of providing safe refuge from storms that produce high 
winds, such as tornados and hurricanes. Such structures 
shall be designated to be hurricane shelters, tornado shel- 
ters, or combined hurricane and tornado shelters. 

423.2 Definitions. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

STORM SHELTER. A building, structure or portions(s) 
thereof, constructed in accordance with ICC S00 and desig- 
nated for use during a severe wind storm event, such as a hurri- 
cane or tornado. 

Community storm shelter. A storm shelter not defined as a 
"Residential Storm Shelter." 



2009 INTERNATIONAL BUILDING CODE® 



77 



78 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 5 

GENERAL BUILDING HEIGHTS AND AREAS 



SECTION 501 
GENERAL 

501.1 Scope. The provisions of this chapter control the height 
and area of structures hereafter erected and additions to exist- 
ing structures. 

\F] 501.2 Address identification. New and existing buildings 
shall be provided with approved address numbers or letters. 
Each character shall be a minimum 4 inches (102 mm) high and 
a minimum of 0.5 inch (12.7 mm) wide. They shall be installed 
on a contrasting background and be plainly visible from the 
street or road fronting the property. Where access is by means 
of a private road and the building address cannot be viewed 
from the public way, a monument, pole or other approvedsign 
or means shall be used to identify the structure. 



SECTION 502 
DEFINITIONS 

502.1 Definitions. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

AREA, BUILDING. The area included within surrounding 
exterior walls (or exterior walls and fire walls) exclusive of 
vent shafts and courts. Areas of the building not provided with 
surrounding walls shall be included in the building area if such 
areas are included within the horizontal projection of the roof 
or floor above. 

BASEMENT. A storythatis not a story above grade plane (see 
"Story above grade plane" in Section 202). 

The definition of "Basement" does not apply to the provi- 
sions of Section 1612 for flood loads (see "Basement" in Sec- 
tion 1612.2). 

EQUIPMENT PLATFORM. An unoccupied, elevated plat- 
form used exclusively for mechanical systems or industrial 
process equipment, including the associated elevated walk- 
ways, stairs, alternating tread devices and ladders necessary to 
access the platform (see Section 505.5). 

GRADE PLANE. A reference plane representing the average 
of finished ground level adjoining the building at exterior 
walls. Where the finished ground level slopes away from the 
exterior walls, the reference plane shall be established by the 
lowest points within the area between the building and the lot 
line or, where the lot line is more than 6 feet (1829 mm) from 
the building, between the building and a point 6 feet (1829 mm) 
from the building. 

HEIGHT, BUILDING. The vertical distance from grade 
plane to the average height of the highest roof surface. 



MEZZANINE. An intermediate level or levels between the 
floor and ceiling of any story and in accordance with Section 
505. 



SECTION 503 

GENERAL BUILDING HEIGHT AND 

AREA LIMITATIONS 

503.1 General. The bUilding height and area shall not exceed 
the limits specified in Table 503 based on the type of construc- 
tion as determined by Section 602 and the occupancies as 
determined by Section 302 except as modified hereafter. Each 
portion of a building separated by one or more fire walls com- 
plying with Section 706 shall be considered to be a separate 
building. 

503.1.1 Special industrial occupancies. Buildings and 
structures designed to house special industrial processes 
that require large areas and unusual bUilding heights to 
accommodate craneways or special machinery and equip- 
ment, including, among others, rolling mills; structural 
metal fabrication shops and foundries; or the production 
and distribution of electric, gas or steam power, shall be 
exempt from the building height and area limitations of 
Table 503. 

503.1.2 Buildings on same lot. Two or more buildings on 
the same lot shall be regulated as separate buildings or shall 
be considered as portions of one building if the bUilding 
height of each building and the aggregate building area of 
the buildings are within the limitations of Table 503 as mod- 
ified by Sections 504 and 506. The provisions of this code 
applicable to the aggregate building shall be applicable to 
each building. 

503.1.3 Type I construction. Buildings of Type I construc- 
tion permitted to be of unlimited tabular building heights 
and areas are not subject to the special requirements that 
allow unlimited area buildings in Section 507 or unlimited 
building height in Sections 503.1.1 and 504.3 or increased 
building heights and areas for other types of construction. 



SECTION 504 
BUILDING HEIGHT 

504.1 General. The bUilding height permitted by Table 503 
shall be increased in accordance with this section. 

Exception: The building height of one-story aircraft han- 
gars, aircraft paint hangars and buildings used for the manu- 
facturing of aircraft shall not be limited if the building is 
provided with an automatic fire-extinguishing system in 
accordance with Chapter 9 and is entirely surrounded by 
public ways oryards not less in width than one and one-half 
times the bUilding height. 



2009 INTERNATIONAL BUILDING CODE® 



79 



GENERAL BUILDING HEIGHTS AND AREAS 

TABLE 503 
ALLOWABLE BUILDING HEIGHTS AND AREAS 3 
Building height limitations shown in feet above grade plane. Story limitations shown as stories above 
Building area limitations shown in square feet, as determined by the definition of "Area, building," 



grade plane, 
per story 







TYPE OF CONSTRUCTION 




TYPE 1 


TYPE II 


TYPE III 


TYPE IV 


TYPE V 






A 


B 


A 


B 


A 


B 


HT 


A 


B 


GROUP 


HEIGHT(feet) 


UL 


160 


65 


55 


65 


55 


65 


50 


40 


STORIES(S) 

AREA (A) 


A-I 


S 

A 


UL 
UL 


5 
UL 


3 
15,500 


2 
8,500 


3 
14,000 


2 
8,500 


3 
15,000 


2 
11,500 


1 
5,500 


A-2 


S 

A 


UL 
UL 


11 
UL 


3 
15,500 


2 
9,500 


3 
14,000 


2 
9,500 


3 
15,000 


2 
11,500 


1 
6,000 


A-3 


S 

A 


UL 
UL 


11 
UL 


3 
15,500 


2 
9,500 


3 
14,000 


2 
9,500 


3 
15,000 


2 
11,500 


1 
6,000 


A-4 


S 
A 


UL 
UL 


11 
UL 


3 
15,500 


2 
9,500 


3 
14,000 


2 
9,500 


3 
15,000 


2 
11,500 


1 
6,000 


A-5 


S 
A 


UL 
UL 


UL 

UL 


UL 
UL 


UL 

UL 


UL 
UL 


UL 

UL 


UL 
UL 


UL 
UL 


UL 
UL 


B 


S 
A 


UL 
UL 


11 
UL 


5 
37,500 


3 
23,000 


5 
28,500 


3 
19,000 


5 
36,000 


3 
18,000 


2 
9,000 


E 


S 
A 


UL 

UL 


5 
UL 


3 
26,500 


2 
14,500 


3 
23,500 


2 
14,500 


3 
25,500 


1 
18,500 


1 
9,500 


F-l 


S 
A 


UL 

UL 


11 
UL 


4 
25,000 


2 
15,500 


3 
19,000 


2 
12,000 


4 
33,500 


2 
14,000 


1 

8,500 


F-2 


S 
A 


UL 
UL 


11 
UL 


5 
37,500 


3 
23,000 


4 
28,500 


3 
18,000 


5 
50,500 


3 
21,000 


2 
13,000 


H-l 


S 

A 


1 
21,000 


1 
16,500 


1 
11,000 


1 
7,000 


1 
9,500 


1 

7,000 


1 
10,500 


1 

7,500 


NP 
NP 


H-2 d 


S 

A 


UL 

21,000 


3 
16,500 


2 
11,000 


1 
7,000 


2 
9,500 


1 
7,000 


2 
10,500 


1 

7,500 


l 
3,000 


H-3 d 


S 

A 


UL 
UL 


6 
60,000 


4 
26,500 


2 
14,000 


4 
17,500 


2 
13,000 


4 
25,500 


2 
10,000 


1 
5,000 


H-4 


S 

A 


UL 
UL 


7 
UL 


5 
37,500 


3 
17,500 


5 
28,500 


3 
17,500 


5 
36,000 


3 
18,000 


2 
6,500 


H-5 


S 

A 


4 
UL 


4 
UL 


3 
37,500 


3 
23,000 


3 
28,500 


3 
19,000 


3 
36,000 


3 
18,000 


2 
9,000 


1-1 


S 
A 


UL 

UL 


9 
55,000 


4 
19,000 


3 
10,000 


4 
16,500 


3 
10,000 


4 
18,000 


3 
10,500 


2 
4,500 


1-2 


S 
A 


UL 
UL 


4 
UL 


2 
15,000 


1 

11,000 


1 
12,000 


NP 

NP 


1 
12,000 


1 
9,500 


NP 

NP 


1-3 


S 
A 


UL 

UL 


4 
UL 


2 
15,000 


1 

10,000 


2 
10,500 


l 

7,500 


2 
12,000 


2 
7,500 


l 
5,000 


1-4 


S 
A 


UL 

UL 


5 
60,500 


3 
26,500 


2 
13,000 


3 
23,500 


2 
13,000 


3 
25,500 


1 
18,500 


1 
9,000 


M 


S 
A 


UL 

UL 


11 
UL 


4 
21,500 


2 
12,500 


4 
18,500 


2 
12,500 


4 
20,500 


3 
14,000 


1 
9,000 


R-l 


S 

A 


UL 
UL 


11 
UL 


4 
24,000 


4 
16,000 


4 
24,000 


4 
16,000 


4 
20,500 


3 
12,000 


2 
7,000 


R-2 


S 

A 


UL 
UL 


11 
UL 


4 
24,000 


4 
16,000 


4 
24,000 


4 
16,000 


4 
20,500 


3 
12,000 


2 
7,000 


R-3 


S 

A 


UL 
UL 


11 
UL 


4 
UL 


4 
UL 


4 
UL 


4 
UL 


4 
UL 


3 
UL 


3 
UL 


R-4 


S 

A 


UL 
UL 


11 
UL 


4 
24,000 


4 
16,000 


4 
24,000 


4 
16,000 


4 
20,500 


3 
12,000 


2 
7,000 


S-l 


S 

A 


UL 
UL 


11 
48,000 


4 
26,000 


2 
17,500 


3 
26,000 


2 
17,500 


4 

25,500 


3 
14,000 


1 
9,000 


S_2b, c 


S 
A 


UL 

UL 


11 
79,000 


5 
39,000 


3 
26,000 


4 
39,000 


3 
26,000 


5 
38,500 


4 
21,000 


2 
13,500 


u 


S 
A 


UL 
UL 


5 
35,500 


4 
19,000 


2 
8,500 


3 
14,000 


2 
8,500 


4 
18,000 


2 
9,000 


1 
5,500 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 - 

A = building area per story, S = stories above grade plane, UL = Unlimited, NP = Not permitted. 

a. See the following sections for general exceptions to Table 503 : 

1. Section 504.2, Allowable building height and story increase due to automatic sprinkler system installation. 

2. Section 506.2, Allowable building area increase due to street frontage. 

3. Section 506.3, Allowable building area increase due to automatic sprinkler system installation. 

4. Section 507, Unlimited area buildings. 

b. For open parking structures, see Section 406.3. 

c. For private garages, see Section 406.1. 

d. See Section 415.5 for limitations. 



80 



2009 INTERNATIONAL BUILDING CODE® 



GENERAL BUILDING HEIGHTS AND AREAS 



504.2 Automatic sprinkler system increase. Where a build- 
ing is equipped throughout with an approved automatic sprin- 
kler system in accordance with Section 903.3.1.1, the value 
specified in Table 503 for maximum bUilding height is 
increased by 20 feet (6096 mm) and the maximum number of 
stories is increased by one. These increases are permitted in 
addition to the building area increase in accordance with Sec- 
tions 506.2 and 506.3. For Group R buildings equipped 
throughout with an approved automatic sprinkler system in 
accordance with Section 903.3.1.2, the value specified in Table 
503 for maximum bUilding height is increased by 20 feet (6096 
mm) and the maximum number of stories is increased by one, 
but shall not exceed 60 feet (18 288 mm) or four stories, respec- 
tively. 

Exceptions: 

1. Buildings, or portions of buildings, classified as a 
Group 1-2 occupancy of Type 1IB, III, IV or V con- 
struction. 

2. Buildings, or portions of buildings, classified as a 
Group H-l, H-2, H-3 or H-5 occupancy. 

3. Fire-resistance rating substitution in accordance 
with Table 601, Note d. 

504.3 Roof structures. Towers, spires, steeples and other roof 
structures shall be constructed of materials consistent with the 
required type of construction of the building except where 
other construction is permitted by Section 1509.2.4. Such 
structures shall not be used for habitation or storage. The struc- 
tures shall be unlimited in height if of noncombustible materi- 
als and shall not extend more than 20 feet (6096 mm) above the 
allowable bUilding height if of combustible materials (see 
Chapter 15 for additional requirements). 



SECTION 505 
MEZZANINES 

505.1 General. A mezzanine or mezzanines in compliance 
with Section 505 shall be considered a portion of the story m 
which it is contained. Such mezzanines shall not contribute to 
either the bUilding area or number of stories as regulated by 
Section 503.1. The area of the mezzanine shall be included in 
determining the fire area defined in Section 902. The clear 
height above and below the mezzanine floor construction shall 
not be less than 7 feet (2134 mm) . 

505.2 Area limitation. The aggregate area of a mezzanine or 
mezzanines within a room shall not exceed one-third of the 
floor area of that room or space in which they are located. The 
enclosed portion of a room shall not be included in a determina- 
tion of the floor area of the room in which the mezzanine is 
located. In determining the allowable mezzanine area, the area 
of the mezzanine shall not be included in the floor area of the 
room. 

Exceptions: 

1. The aggregate area of mezzanines in buildings and 
structures of Type I or II construction for special 
industrial occupancies in accordance with Section 
503.1.1 shall not exceed two-thirds of the floor area of 
the room. 



2. The aggregate area of mezzanines in buildings and 
structures of Type lor II construction shall not exceed 
one-half of the floor area of the room in buildings and 
structures equipped throughout with an approved 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1 and an approved emergency 
voice/alarm communication system in accordance 
with Section 907.5.2.2. 

505.3 Egress. Each occupant of a mezzanine shall have access 
to at least two independent means of egress where the common 
path of egress travel exceeds the limitations of Section 1014.3. 
Where a stairway provides a means of exit access from a mez- 
zanine, the maximum travel distance includes the distance trav- 
eled on the stairway measured in the plane of the tread nosing. 
Accessible means of egress shall be provided in accordance 
with Section 1007. 

Exception: A single means of egress shall be permitted in 
accordance with Section 1015.1. 

505.4 Openness. A mezzanine shall be open and unobstructed 
to the room in which such mezzanine is located except for walls 
not more than 42 inches (1067 mm) high, columns and posts. 

Exceptions: 

1. Mezzanines or portions thereof are not required to be 
open to the room in which the mezzanines are located, 
provided that the occupant load of the aggregate area 
of the enclosed space does not exceed 10. 

2. A mezzanine having two or more means of egress is 
not required to be open to the room in which the mez- 
zanine is located if at least one of the means of egress 
provides direct access to an exit from the mezzanine 
level. 

3. Mezzanines or portions thereof are not required to be 
open to the room in which the mezzanines are located, 
provided that the aggregate floor area of the enclosed 
space does not exceed 10 percent of the mezzanine 
area. 

4. In industrial facilities, mezzanines used for control 
equipment are permitted to be glazed on all sides. 

5. In occupancies other than Groups H and I, that are no 
more than two stories above grade plane and 
equipped throughout with an automatic sprinkler sys- 
tem in accordance with Section 903.3.1.1, a mezza- 
nine having two or more means of egress shall not be 
required to be open to the room in which the mezza- 
nine is located. 

505.5 Equipment platforms. Equipment platforms in build- 
ings shall not be considered as a portion of the floor below. 
Such equipment platforms shall not contribute to either the 
building area or the number of stories as regulated by Section 
503.1. The area of the equipmentplatform shall not be included 
in determining the fire area in accordance with Section 903. 
Equipment platforms shall not be a part of any mezzanine and 
such platforms and the walkways, stairs, alternating tread 
devices and ladders providing access to an equipmentplatform 
shall not serve as a part of the means of egress from the build- 
ing. 



2009 INTERNATIONAL BUILDING CODE® 



81 



GENERAL BUILDING HEIGHTS AND AREAS 



i 

1 



505.5.1 Area limitations. The aggregate area of all equip- 
mentplatforms within a room shall not exceed two-thirds of 
the area of the room in which they are located. Where an 
equipment platform is located in the same room as a mezza- 
nine, the area of the mezzanine shall be determined by Sec- 
tion 505.2 and the combined aggregate area of the 
equipment platforms and mezzanines shall not exceed 
two-thirds of the room in which they are located. 

[F] 505.5.2 Fire suppression. Where located in a building 
that is required to be protected by an automatic sprinkler 
system, equipment platforms shall be fully protected by 
sprinklers above and below the platform, where required by 
the standards referenced in Section 903.3. 

505.5.3 Guards. Equipment platforms shall have guards 
where required by Section 1013.1. 



SECTION 506 
BUILDING AREA MODIFICATIONS 

506.1 General. The bUilding areas limited by Table 503 shall 
be permitted to be increased due to frontage (IJ and automatic 
sprinkler system protection (I) in accordance with the follow- 
ing: 



4={>W4 x/ '] + [4 x/ 4 



(Equation 5-1) 



where: 

A a = Allowable bUilding area per story (square feet). 

A t — Tabular bUilding area per story in accordance with 
Table 503 (square feet). 

I f = Area increase factor due to frontage as calculated in 
accordance with Section 506.2. 

= Area increase factor due to sprinkler protection as cal- 
culated in accordance with Section 506.3. 

506.2 Frontage increase. Every building shall adjoin or have 
access to a public way to receive a bUilding area increase for 
frontage. Where a building has more than 25 percent of its per- 
imeter on a, public way or open space having a minimum width 
of 20 feet (6096 mm), the frontage increase shall be determined 
in accordance with the following: 



lf==[F/P-0.25]W/30 



(Equation 5-2) 



where: 

If = Area increase due to frontage. 

F = Building perimeter that fronts on a public way or open 
space having 20 feet (6096 mm) open minimum width 
(feet) . 

P = Perimeter of entire building (feet). 

W = Width of public way or open space (feet) in accordance 
with Section 506.2.1. 

506.2.1 Width limits. The value of Wshall be at least 20 
feet (6096 mm). Where the value of Wvaries along the per- 
imeter of the building, the calculation performed in accor- 
dance with Equation 5-2 shall be based on the weighted 
average of each portion of exterior wall and open space 



where the value of Wis greater than or equal to 20 feet (6096 
mm). Where the value of Wexceeds 30 feet (9144 mm), a 
value of 30 feet (9144 mm) shall be used in calculating the 
weighted average, regardless of the actual width of the open 
space. Where two or more buildings are on the same lot, W 
shall be measured from the exterior face of a building to the 
exterior face of an opposing building, as applicable. 

Exception: The value of W divided by 30 shall be per- 
mitted to be a maximum of 2 when the building meets all 
requirements of Section 507 except for compliance with 
the 60-foot (18288 mm) public wayoxyardrequirement, 
as applicable. 

506.2.2 Open space limits. Such open space shall be either 
on the same lot or dedicated for public use and shall be 
accessed from a street or approved fire lane. 

506.3 Automatic sprinkler system increase. Where a build- 
ing is equipped throughout with an approved automatic sprin- 
kler systemin accordance with Section 903.3.1.1, the building 
area limitation in Table 503 is permitted to be increased by an 
additional 200 percent (I s = 2) for buildings with more than one 
story above grade plane and an additional 300 percent (I s = 3) 
for buildings with no more than one story above grade plane. 
These increases are permitted in addition to the height and 
story increases in accordance with Section 504.2. 

Exception: The building area limitation increases shall not 
be permitted for the following conditions: 

1. The automatic sprinkler system increase shall not 
apply to buildings with an occupancy in Group H-l. 

2. The automatic sprinkler system increase shall not 
apply to the bUilding area of an occupancy in Group 
H-2 or H-3. For buildings containing such occupan- 
cies, the allowable building area shall be determined 
in accordance with Section 508.4.2, with the sprinkler 
system increase applicable only to the portions of the 
building not classified as Group H-2 or H-3. 

3. Fire-resistance rating substitution in accordance 
with Table 601, Note d. 

506.4 Single occupancy buildings with more than one story. 
The total allowable bUilding area of a single occupancy build- 
ing with more than one story above grade plane shall be deter- 
mined in accordance with this section. The actual aggregate 
building area at all stories in the building shall not exceed the 
total allowable building area. 

Exception: A single basement need not be included in the 
total allowable bUilding area, provided such basement does 
not exceed the area permitted for a building with no more 
than one story above grade plane. 

506.4.1 Area determination. The total allowable building 
area of a single occupancy building with more than one 
story above grade plane shall be determined by multiplying 
the allowable building area per story (A^, as determined in 
Section 506.1, by the number of stories above grade plane 
as listed below: 

1. For buildings with two stories above grade plane, 
multiply by 2; 



82 



2009 INTERNATIONAL BUILDING CODE® 



GENERAL BUILDING HEIGHTS AND AREAS 



2. For buildings with three or more stories above grade 
plane, multiply by 3; and 

3. No story shall exceed the allowable bUilding area per 
story (Aa), as determined in Section 506.1, for the 
occupancies on that story. 

Exceptions: 

1. Unlimited area buildings in accordance with Sec- 
tion 507. 

2. The maximum area of a building equipped 
throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.2 shall be deter- 
mined by multiplying the allowable area per story 
(A J, as determined in Section 506.1, by the num- 
ber of stories above grade plane. 

506.5 Mixed occupancy area determination. The total allow- 
able building area for buildings containing mixed occupancies 
shall be determined in accordance with the applicable provi- 
sions of this section. A single basement need not be included in 
the total allowable bUilding area, provided such basement does 
not exceed the area permitted for a building with no more than 
one story above grade plane. 

506.5.1 No more than one story above grade plane. For 
buildings with no more than one story above grade plane 
and containing mixed occupancies, the total building area 
shall be determined in accordance with the applicable provi- 
sions of Section 508.1. 

506.5.2 More than one story above grade plane. For 
buildings with more than one story above grade plane and 
containing mixed occupancies, each storyshall individually 
comply with the applicable requirements of Section 508.1. 
For buildings with more than three stories above grade 
plane, the total building area shall be such that the aggregate 
sum of the ratios of the actual area of each story divided by 
the allowable area of such stories based on the applicable 
provisions of Section 508.1 shall not exceed 3. 



SECTION 507 
UNLIMITED AREA BUILDINGS 

507.1 General. The area of buildings of the occupancies and 
configurations specified herein shall not be limited. 

507.2 Nonsprinklered, one story. The area of a Group F-2 or 
S-2 building no more than one storyin height shall not be lim- 
ited when the building is surrounded and adjoined by public 
ways or yards not less than 60 feet (18 288 mm) in width. 

507.3 Sprinklered, one story. The area of a Group B, F, M or S 
building no more than one story above grade plane, or a Group 
A-4 building no more than one story above gradeplane of other 
than Type V construction, shall not be limited when the build- 
ing is provided with an automatic sprinkler system throughout 
in accordance with Section 903.3.1.1 and is surrounded and 
adjoined by public ways oxyardsnoi less than 60 feet (18 288 
mm) in width. 

Exceptions: 

1. Buildings and structures of Types I and II construc- 
tion for rack storage facilities that do not have access 



by the public shall not be limited in height, provided 
that such buildings conform to the requirements of 
Sections 507.3,903.3.1.1 and Chapter 23 of\h& Inter- 
national Fire Code. 

2. The automatic sprinkler system shall not be required 
in areas occupied for indoor participant sports, such 
as tennis, skating, swimming and equestrian activities 
in occupancies in Group A-4, provided that: 

2.1. Exit doors directly to the outside are provided 
for occupants of the participant sports areas; 
and 

2.2. The building is equipped with a fire alarm sys- 
tem with manual fire alarm boxes installed in 
accordance with Section 907. 

507.3.1 Mixed occupancy buildings with Groups A-I 
and A-2. Group A-I and A-2 occupancies of other than 
Type V construction shall be permitted within mixed occu- 
pancy buildings of unlimited area complying with Section 
507.3, provided: 

1. Group A-I and A-2 occupancies are separated from 
other occupancies as required for separated occupan- 
cies in Section 508.4.4 with no reduction allowed in 
the fire -resistance ratingoi 'the separation based upon 
the installation of an automatic sprinkler system; 

2. Each area of the portions of the building used for 
Group A-lor A-2 occupancies shall not exceed the 
maximum allowable area permitted for such occu- 
pancies in Section 503.1; and 

3. All exit doors from Group A-I and A-2 occupancies 
shall discharge directly to the exterior of the building. 

507.4 Two story. The area of a Group B, F, M or S building no 
more than two stories above grade plane shall not be limited 
when the building is equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1, and is 
surrounded and adjoined by public ways oryardsnoi less than 
60 feet (18 288 mm) in width. 

507.5 Reduced open space. The public ways or yards of 60 
feet (18 288 mm) in width required in Sections 507.2, 507.3, 
507.4,507.6 and 507.11 shall be permitted to be reduced to not 
less than 40 feet (12 192 mm) in width provided all of the fol- 
lowing requirements are met: 

1. The reduced width shall not be allowed for more than 75 
percent of the perimeter of the building. 

2. The exterior walls facing the reduced width shall have a 
minimum fire-resistance rating of 3 hours. 

3. Openings in the exterior walls facing the reduced width 
shall have opening protectives with a minimum fire pro- 
tection rating of 3 hours. 

507.6 Group A-3 buildings of Type II construction. The area 
of a Group A-3 building no more than one story above grade 
plane, used as a place of religious worship, community hall, 
dance hall, exhibition hall, gymnasium, lecture hall, indoor 
swimming pool or tennis court of Type II construction, shall 
not be limited when all of the following criteria are met: 

1. The building shall not have a stage other than a platform. 



2009 INTERNATIONAL BUILDING CODE® 



83 



GENERAL BUILDING HEIGHTS AND AREAS 



2. The building shall be equipped throughout with an auto- 
matic sprinkler system in accordance with Section 
903.3.1.1. 

3. The building shall be surrounded and adjoined by public 
ways ovyards not less than 60 feet (18 288 mm) in width. 

507.7 Group A-3 buildings of Types III and IV construc- 
tion. The area of a Group A-3 building no more than one story 
above grade plane, used as aplace ofreligious worship, com- 
munity hall, dance hall, exhibition hall, gymnasium, lecture 
hall, indoor swimming pool or tennis court of Type III or IV 
construction, shall not be limited when all of the following cri- 
teria are met: 

1 . The building shall not have a stage other than a platform. 

2. The building shall be equipped throughout with an auto- 
matic sprinkler system in accordance with Section 
903.3.1.1. 

3. The assembly floor shall be located at or within 21 inches 
(533 mm) of street or grade level and all exits are pro- 
vided with ramps complying with Section 1010.1 to the 
street or grade level. 

4. The building shall be surrounded and adjoined by public 
ways ovyards not less than 60 feet (18288 mm) in width. 

507.8 Group H occupancies. Group H-2, H-3 and H-4 occu- 
pancies shall be permitted in unlimited area buildings contain- 
ing Group F and S occupancies, in accordance with Sections 
507.3 and 507.4 and the limitations of this section. The aggre- 
gate floor area of the Group H occupancies located at the per- 
imeter of the unlimited area building shall not exceed 10 
percent of the area of the building nor the area limitations for 
the Group H occupancies as specified in Table 503 as modified 
by Section 506.2, based upon the percentage of the perimeter 
of each Group H floor area that fronts on a street or other unoc- 
cupied space. The aggregate floor area of Group H occupancies 
not located at the perimeter of the building shall not exceed 25 
percent of the area limitations for the Group H occupancies as 
specified in Table 503. Group H occupancies shall be separated 
from the rest of the unlimited area building and from each other 
in accordance with Table 508.4. For two- story unlimited area 
buildings, the Group H occupancies shall not be located more 
than one story above grade plane unless permitted by the 
allowable height in stories and feet as set forth in Table 503 
based on the type of construction of the unlimited area build- 
ing. 

507.9 Aircraft paint hangar. The area of a Group H-2 aircraft 
paint hangar no more than one story above grade plane shall 
not be limited where such aircraft paint hangar complies with 
the provisions of Section 412.6 and is surrounded and adjoined 
by public ways or yards not less in width than one and one-half 
times the building height. 

507.10 Group E buildings. The area of a Group E building no 
more than one story above grade plane, of Type II, I1IA or IV 
construction, shall not be limited when all of the following cri- 
teria are met: 

1. Each classroom shall have not less than two means of 
egress, with one of the means ofegressbzing a direct exit 



to the outside of the building complying with Section 
1020. 

2. The building is equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1. 

3. The building is surrounded and adjoined by public ways 
or yards not less than 60 feet (18 288 mm) in width. 

507.11 Motion picture theaters. In buildings of Type II con- 
struction, the area of a motion picture theater located on the 
first story above grade plane shall not be limited when the 
building is provided with an automatic sprinkler system 
throughout in accordance with Section 903.3.1.1 and is sur- 
rounded and adjoined by public ways or yards not less than 60 
feet (18 288 mm) in width. 

507.12 Covered mall buildings and anchor stores. The area 
of covered mall buildings and anchor stores not exceeding 
three stories in height that comply with Section 402.6 shall not 
be limited. 



SECTION 508 
MIXED USE AND OCCUPANCY 

508.1 General. Each portion of a building shall be individually 
classified in accordance with Section 302.1. Where a building 
contains more than one occupancy group, the building or por- 
tion thereof shall comply with the applicable provisions of Sec- 
tion 508.2,508.3 or 508.4, or a combination of these sections. 

Exceptions: 

1. Occupancies separated in accordance with Section 
509. 

2. Where required by Table 415.3.2, areas of Group 
H-l, H-2 and H-3 occupancies shall be located in a 
separate and detached building or structure. 

3. Uses within live/work units, complying with Section 
419, are not considered separate occupancies. 

508.2 Accessory occupancies. Accessory occupancies are 
those occupancies that are ancillary to the main occupancy of 
the building or portion thereof. Accessory occupancies shall 
comply with the provisions of Sections 508.2.1 through 
508.2.5.3. 

508.2.1 Area limitations. Aggregate accessory occupan- 
cies shall not occupy more than 10 percent of the building 
area of the story in which they are located and shall not 
exceed the tabular values in Table 503, without building 
area increases in accordance with Section 506 for such 
accessory occupancies. 

508.2.2 Occupancy classification. Accessory occupancies 
shall be individually classified in accordance with Section 
302. 1. The requirements of this code shall apply to each por- 
tion of the building based on the occupancy classification of 
that space. 

508.2.3 Allowable building area and height. The allow- 
able building area and height of the building shall be based 
on the allowable bUildingarea andheightfov the main occu- 
pancy in accordance with Section 503.1. The height of each 
accessory occupancy shall not exceed the tabular values in 



84 



2009 INTERNATIONAL BUILDING CODE® 



GENERAL BUILDING HEIGHTS AND AREAS 



Table 503, without increases in accordance with Section 
504 for such accessory occupancies. The bUilding area of 
the accessory occupancies shall be in accordance with Sec- 
tion 508.2.1. 

508.2.4 Separation of occupancies. No separation is 
required between accessory occupancies and the main 
occupancy. 

Exceptions: 

1. Group H-2, H-3, H-4 and H-5 occupancies shall be 
separated from all other occupancies in accor- 
dance with Section 508.4. 

2. Incidental accessory occupancies required to be 
separated or protected by Section 508.2.5. 

3. Group 1-1, R-I, R-2 and R-3 dwelling units and 
sleeping units shall be separated from other dwell- 
ingor sleeping units and from accessory occupan- 
cies contiguous to them in accordance with the 
requirements of Section 420. 

508.2.5 Separation of incidental accessory occupancies. 
The incidental accessory occupancies listed in Table 



508.2.5 shall be separated from the remainder of the 
building or equipped with an automatic fire-extinguishing 
system, or both, in accordance with Table 508.2.5. 

Exception: Incidental accessory occupancies within and 
serving a dwelling unit are not required to comply with 
this section. 

508.2.5.1 Fire-resistance-rated separation. Where 
Table 508.2.5 specifies a fire-resistance-rated separa- 
tion, the incidental accessory occupancies shall be sepa- 
rated from the remainder of the bUildingby afire barrier 
constructed in accordance with Section 707 or a horizon- 
tal assembly constructed in accordance with Section 
712, or both. Construction supporting I-hour fire-resis- 
tance-rated fire barriers or horizontal assemblies used 
for incidental accessory occupancy separations in build- 
ings of Type 1IB, IIIB and VB construction are not 
required to be fire-resistance rated unless required by 
other sections of this code. 

508.2.5.2 Nonfire-resistance-rated separation and 
protection. Where Table 508.2.5 permits an automatic 
fire-extinguishing system without afire barrier, the inci- 



TABLE 508.2.5 
INCIDENTAL ACCESSORY OCCUPANCIES 



ROOM OR AREA 


SEPARATION AND/OR PROTECTION 


Furnace room where any piece of equipment is over 400,000 Btu per 
hour input 


1 hour or provide automatic fire-extinguishing system 


Rooms with boilers where the largest piece of equipment is over 15 
psi and 10 horsepower 


1 hour or provide automatic fire-extinguishing system 


Refrigerant machinery room 


1 hour or provide automatic sprinkler system 


Hydrogen cutoff rooms, not classified as Group H 


1 hour in Group B, F, M, Sand U occupancies; 2 hours in Group A, 
E, I and R occupancies. 


Incinerator rooms 


2 hours and automatic sprinkler system 


Paint shops, not classified as Group H, located in occupancies other 
than Group F 


2 hours; or 1 hour and provide automatic fire-extinguishing system 


Laboratories and vocational shops, not classified as Group H, located 
in a Group E or 1-2 occupancy 


1 hour or provide automatic fire-extinguishing system 


Laundry rooms over 100 square feet 


1 hour or provide automatic fire-extinguishing system 


Group 1-3 cells equipped with padded surfaces 


1 hour 


Group 1-2 waste and linen collection rooms 


1 hour 


Waste and linen collection rooms over 100 square feet 


1 hour or provide automatic fire-extinguishing system 


Stationary storage battery systems having a liquid electrolyte 
capacity of more than 50 gallons, or a lithium-ion capacity of 1,000 
pounds used for facility standby power, emergency power or 
uninterrupted power supplies 


1 hour in Group B, F, M, Sand U occupancies; 2 hours in Group A, 
E, I and R occupancies. 


Rooms containing fire pumps in nonhigh-rise buildings 


2 hours; or 1 hour and provide automatic sprinkler system throughout 
the building 


Rooms containing fire pumps in high-rise buildings 


2 hours 



For 51 : 1 square foot = 0.0929 m 2 , 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 
1 gallon = 3.785 L. 



2009 INTERNATIONAL BUILDING CODE® 



85 



GENERAL BUILDING HEIGHTS AND AREAS 



dental accessory occupancies shall be separated from the 
remainder of the building by construction capable of 
resisting the passage of smoke. The walls shall extend 
from the top of the foundation or floor assembly below to 
the underside of the ceiling that is a component of a 
fire-resistance-rated floor assembly or roof assembly 
above or to the underside of the floor or roof sheathing, 
deck or slab above. Doors shall be self- or automatic- 
closing upon detection of smoke in accordance with Sec- 
tion 715.4.8.3. Doors shall not have air transfer openings 
and shall not be undercut in excess of the clearance per- 
mitted in accordance with NFPA 80. Walls surrounding 
the incidental accessory occupancy shall not have air 
transfer openings unless provided with smoke dampers 
in accordance with Section 711.7. 

508.2.5.3 Protection. Except as specified in Table 
508.2.5 for certain incidental accessory occupancies, 
where an automatic fire-extinguishing system or an 
automatic sprinkler system is provided in accordance 
with Table 508.2.5, only the space occupied by the inci- 
dental accessory occupancy need be equipped with such 
a system. 

508.3 Nonseparated occupancies. Buildings or portions of 
buildings that comply with the provisions of this section shall 
be considered as nonseparated occupancies. 

508.3.1 Occupancy classification. Nonseparated occupan- 
cies shall be individually classified in accordance with Sec- 
tion 302.1. The requirements of this code shall apply to each 
portion of the building based on the occupancy classifica- 



tion of that space except that the most restrictive applicable 
provisions of Section 403 and Chapter 9 shall apply to the 
building or portion thereof in which the nonseparated occu- 
pancies are located. 

508.3.2 Allowable building area and height. The allow- 
able building area and height of the building or portion 
thereof shall be based on the most restrictive allowances for 
the occupancy groups under consideration for the type of 
construction of the building in accordance with Section 
503.1. 

508.3.3 Separation. No separation is required between 
nonseparated occupancies. 

Exceptions: 

1. Group H-2, H-3, H-4 and H-5 occupancies shall be 
separated from all other occupancies in accor- 
dance with Section 508.4. 

2. Group 1-1, R-l, R-2 and R-3 dwelling units and 
sleeping units shall be separated from other dwell- 
ing or sleeping units and from other occupancies 
contiguous to them in accordance with the require- 
ments of Section 420. 

508.4 Separated occupancies. Buildings or portions of build- 
ings that comply with the provisions of this section shall be 
considered as separated occupancies. 

508.4.1 Occupancy classification. Separated occupancies 
shall be individually classified in accordance with Section 
302.1. Each separated space shall comply with this code 



TABLE 508.4 
REQUIRED SEPARATION OF OCCUPANCIES (HOURS) 



OCCUPANCY 


Ad, E 


1-1,1-3,1-4 


1-2 


R 


F-2, 5-2 b , U 


B, F-1, M, 5-1 


H-1 


H-2 


H-3, H-4, H-5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


5 


N5 


Ad, E 


N 


N 


1 


2 


2 


NP 


1 


2 


N 


1 


1 


2 


NP 


NP 


3 


4 


2 


3 a 


1-1,1-3,1-4 


- 


- 


N 


N 


2 


NP 


1 


NP 


1 


2 


1 


2 


NP 


NP 


3 


NP 


2 


NP 


1-2 


- 


- 


- 


- 


N 


N 


2 


NP 


2 


NP 


2 


NP 


NP 


NP 


3 


NP 


2 


NP 


R 


- 


- 


- 


- 


- 


- 


N 


N 


lc 


2 C 


1 


2 


NP 


NP 


3 


NP 


2 


NP 


F-2,S-2 b , U 


- 


- 


- 


- 


- 


- 


- 


- 


N 


N 


1 


2 


NP 


NP 


3 


4 


2 


3 a 


B, F-l, M, 
S-l 






















N 


N 


NP 


NP 


2 


3 


1 


2 a 


H-l 


























N 


NP 


NP 


NP 


NP 


NP 


H-2 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


N 


NP 


1 


NP 


H-3, H-4, H-5 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


kf 


NP 



For SI : 1 square foot = 0.0929 m 2 . 

S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. 

NS = Buildings not equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. 

N = No separation requirement. 

NP = Not permitted. 

a. For Group H-5 occupancies, see Section 903.2.5.2. 

b. The required separation from areas used only for private or pleasure vehicles shall be reduced by 1 hour but to not less than 1 hour. 

c. See Section 406.1.4. 

d. Commercial kitchens need not be separated from the restaurant seating areas that they serve. 

e. Separation is not required between occupancies of the same classification. 

f. For H-5 occupancies, see Section 415.8.2.2. 



86 



2009 INTERNATIONAL BUILDING CODE® 



GENERAL BUILDING HEIGHTS AND AREAS 



based on the occupancy classification of that portion of the 
building. 

508.4.2 Allowable building area. In each story, the build- 
ing area shall be such that the sum of the ratios of the actual 
bUilding area of each separated occupancy divided by the 
allowable building area of each separated occupancy shall 
not exceed 1. 

508.4.3 Allowable height. Each separated occupancy shall 
comply with the building height limitations based on the 
type of construction of the building in accordance with Sec- 
tion 503.1. 

Exception: Special provisions permitted by Section 
509. 

508.4.4 Separation. Individual occupancies shall be sepa- 
rated from adjacent occupancies in accordance with Table 
508.4. 

508.4.4.1 Construction. Required separations shall be 
fire barriers constructed in accordance with Section 707 
or horizontal assemblies constructed in accordance with 
Section 712, or both, so as to completely separate adja- 
cent occupancies. 



SECTION 509 
SPECIAL PROVISIONS 

509.1 General. The provisions in this section shall permit the 
use of special conditions that are exempt from, or modify, the 
specific requirements of this chapter regarding the allowable 
heights and areas of buildings based on the occupancy classifi- 
cation and type of construction, provided the special condition 
complies with the provisions specified in this section for such 
condition and other applicable requirements of this code. The 
provisions of Sections 509.2 through 509.8 are to be consid- 
ered independent and separate from each other. 

509.2 Horizontal building separation allowance. A building 
shall be considered as separate and distinct buildings for the 
purpose of determining area limitations, continuity of fire 
walls, limitation of number of stories and type of construction 
where all of the following conditions are met: 

1. The buildings are separated with a horizontal assembly 
having a minimum 3-hour fire -resistance rating. 

2. The building below the horizontal assembly is no more 
than one story above grade plane. 

3. The building below the horizontal assembly is of Type 
IA construction. 

4. Shaft, stairway, ramp and escalator enclosures through 
the horizontal assembly shall have not less than a 2-hour 
fire-resistance rating with opening protectives in accor- 
dance with Section 715.4. 

Exception: Where the enclosure walls below the hor- 
izontal assembly have not less than a 3-hour fire-resis- 
tance rating with opening protectives in accordance 
with Section 715.4, the enclosure walls extending 



above the horizontal assembly shall be permitted to 
have a I-hour fire-resistance rating, provided: 

1. The building above the horizontal assembly is 
not required to be of Type I construction; 

2. The enclosure connects less than four stories; 
and 

3. The enclosure opening protectives above the 
horizontal assembly have a minimum I-hour 
fire protection rating. 

5. The building or buildings above the horizontal assembly 
shall be permitted to have multiple Group A occupancy 
uses, each with an occupant load of less than 300, or 
Group B, M, R or S occupancies. 

6. The building below the horizontal assembly shall be pro- 
tected throughout by an approved automatic sprinkler 
system in accordance with Section 903.3.1.1, and shall 
be permitted to be any of the following occupancies: 

6.1. Group S-2 parking garage used for the parking 
and storage of private motor vehicles; 

6.2. Multiple Group A, each with an occupantloadof 
less than 300; 

6.3. Group B; 

6.4. Group M; 

6.5. Group R; and 

6.6. Uses incidental to the operation of the building 
(including entry lobbies, mechanical rooms, 
storage areas and similar uses). 

7. The maximum bUilding height in feet (mm) shall not 
exceed the limits set forth in Section 503 for the building 
having the smaller allowable height as measured from 
the grade plane. 

509.3 Group S-2 enclosed parking garage with Group S-2 
open parking garage above. A Group S-2 enclosed parking 
garage with no more than one story above grade plane and 
located below a Group S-2 openparkinggarage shall be classi- 
fied as a separate and distinct building for the purpose of deter- 
mining the type of construction where all of the following 
conditions are met: 

1. The allowable area of the building shall be such that the 
sum of the ratios of the actual area divided by the allow- 
able area for each separate occupancy shall not exceed 1. 

2. The Group S-2 enclosed parking garage is of Type I or II 
construction and is at least equal to the fire -resistance 
requirements of the Group S-2 open parking garage. 

3. The height and the number of tiers of the Group S-2 open 
parking garage shall be limited as specified in Table 
406.3.5. 

4. The floor assembly separating the Group S-2 enclosed 
parking garage and Group S-2 openparkinggarage shall 
be protected as required for the floor assembly of the 
Group S-2 enclosed parking garage. Openings between 
the Group S-2 enclosed parking garage and Group S-2 



i 



2009 INTERNATIONAL BUILDING CODE® 



87 



GENERAL BUILDING HEIGHTS AND AREAS 



open parking garage, except exit openings, shall not be 
required to be protected. 

5. The Group S-2 enclosed parking garage is used exclu- 
sively for the parking or storage of private motor vehi- 
cles, but shall be permitted to contain an office, waiting 
room and toilet room having a total area of not more than 
1,000 square feet (93 m 2 ), and mechanical equipment 
rooms incidental to the operation of the building. 

509.4 Parking beneath Group R. Where a maximum one 
story above grade plane Group S-2 parking garage, enclosed or 
open, or combination thereof, of Type I construction or open of 
Type IV construction, with grade entrance, is provided under a 
building of Group R, the number of stories to be used in deter- 
mining the minimum type of construction shall be measured 
from the floor above such a parking area. The floor assembly 
between the parking garage and the Group R above shall com- 
ply with the type of construction required for the parking 
garage and shall also provide a fire-resistance rating not less 
than the mixed occupancy separation required in Section 
508.4. 

509.5 Group R-l and R-2 buildings of Type I1IA construc- 
tion. The height limitation for buildings of Type I1IA construc- 
tion in Groups R-l and R-2 shall be increased to six stories and 
75 feet (22 860 mm) where the first floor assembly above the 
basement has a fire-resistance rating of not less than 3 hours 
and the floor area is subdivided by 2-hour fire-resistance-rated 
fire walls into areas of not more than 3,000 square feet (279 
m 2 ). 

509.6 Group R-l and R-2 buildings of Type IIA construc- 
tion. The height limitation for buildings of Type IIA construc- 
tion in Groups R-l and R-2 shall be increased to nine stories 
and 100 feet (30 480 mm) where the building is separated by 
not less than 50 feet (15 240 mm) from any other building on 
the lot and from lot lines, the exits are segregated in an area 
enclosed by a 2-hour fire-resistance-rated fire walland the first 
floor assembly has afire-resistance rating of not less than lV 2 
hours. 

509.7 Open parking garage beneath Groups A, I, B, M and 
R. Open parking garages constructed under Groups A, I, B, M 
and R shall not exceed the height and area limitations permitted 
under Section 406.3. The height and area of the portion of the 
building above the open parking garage shall not exceed the 
limitations in Section 503 for the upper occupancy. The height, 
in both feet and stories, of the portion of the building above the 
open parking garage shall be measured from grade plane and 
shall include both the open parking garage and the portion of 
the building above the parking garage. 

509.7.1 Fire separation. Fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712 between the 
parking occupancy and the upper occupancy shall corre- 
spond to the required fire -resistance rating prescribed in 
Table 508.4 for the uses involved. The type of construction 
shall apply to each occupancy individually, except that 
structural members, including main bracing within the open 
parking structure, which is necessary to support the upper 
occupancy, shall be protected with the more restrictive 
fire-resistance-rated assemblies of the groups involved as 



shown in Table 601. Means of egress for the upper occu- 
pancy shall conform to Chapter 10 and shall be separated 
from the parking occupancy by fire barriershaving at least a 
2-hour fire-resistance rating as required by Section 706 
with self-closing doors complying with Section 715 or hori- 
zontal assemblies having at least a 2-hour fire-resistance 
rating as required by Section 712, with self-closing doors 
complying with Section 715. Means of egress from the open 
parking garage shall comply with Section 406.3. 

509.8 Group B or M with Group 5-2 open parking garage. 
Group B or M occupancies located no higher than the first story 
above grade plane shall be considered as a separate and distinct 
building for the purpose of determining the type of construc- 
tion where all of the following conditions are met: 

1. The buildings are separated with a horizontal assembly 
having a minimum 2-hour fire -resistance rating. 

2. The occupancies in the building below the horizontal 
assembly arc limited to Groups Band M. 

3. The occupancy above the horizontal assembly is limited 
to a Group S-2 open parking garage. 

4. The building below the horizontal assembly is of Type I 
or II construction but not less than the type of construc- 
tion required for the Group S-2 open parking garage 
above. 

5. The height and area of the building below the horizontal 
assembly does not exceed the limits set forth in Section 
503. 

6. The height and area of the Group S-2 open parking 
garage does not exceed the limits set forth in Section 
406.3. The height, in both feet and stories, of the Group 
S-2 open parking garage shall be measured from grade 
plane and shall include the building below the horizontal 
assembly. 

7. Exits serving the Group S-2 open parking garage dis- 
charge directly to a street or public wayand are separated 
from the building below the horizontal assembly by 
2-hour fire barriers constructed in accordance with Sec- 
tion 707 or 2-hour horizontal assemblies constructed in 
accordance with Section 712, or both. 

509.9 Multiple buildings above Group 5-2 parking garages. 
Where two or more buildings are provided above the horizon- 
tal assembly separating a Group S-2 open or closed parking 
garage from the buildings above in accordance with the special 
provisions in Sections 509.2, 509.3 or 509.8, the buildings 
above the horizontal assembly shall be regarded as separate 
and distinct buildings from each other and shall comply with all 
other provisions of this code as applicable to each separate and 
distinct building. 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 6 

TYPES OF CONSTRUCTION 



SECTION 601 
GENERAL 

601.1 Scope. The provisions of this chapter shall control the 
classification of buildings as to type of construction. 



SECTION 602 
CONSTRUCTION CLASSIFICATION 

602.1 General. Buildings and structures erected or to be 
erected, altered or extended in height or area shall be classified 
in one of the five construction types defined in Sections 602.2 
through 602.5. The building elements shall have a fire-resis- 
tance rating not less than that specified in Table 601 and exte- 
rior walls shall have a fire-resistance rating not less than that 
specified in Table 602. Where required to have afire-resistance 
ratingby Table 601, building elements shall comply with the 
applicable provisions of Section 703 .2. The protection of open- 
ings, ducts and air transfer openings in building elements shall 
not be required unless required by other provisions of this code. 



602.1.1 Minimum requirements. A building or portion 
thereof shall not be required to conform to the details of a 
type of construction higher than that type which meets the 
minimum requirements based on occupancy even though 
certain features of such a building actually conform to a 
higher type of construction. 

602.2 Types I and II. Types I and II construction are those 
types of construction in which the building elements listed in 
Table 601 are of noncombustible materials, except as permitted 
in Section 603 and elsewhere in this code. 

602.3 Type III. Type III construction is that type of construc- 
tion in which the exterior walls are of noncombustible materi- 
als and the interior building elements are of any material 
permitted by this code. Fire-retardant-treated wood framing 
complying with Section 2303.2 shall be permitted within exte- 
rior wall assemblies of a 2-hour rating or less. 

602.4 Type IV. Type IV construction (Heavy Timber, HT) is 
that type of construction in which the exterior walls are of 
noncombustible materials and the interior building elements 
are of solid or laminated wood without concealed spaces. The 



TABLE 601 
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (hours) 



BUILDING ELEMENT 


TYPE I 


TYPE II 


TYPE III 


TYPE IV 


TYPE V 


A 


B 


Ad 


B 


Ad 


B 


HT 


Ad 


B 


Primary structural frame g 
(see Section 202) 


3 a 


2 a 


1 





1 





HT 


1 





Bearing walls 
Exterior f , g 
Interior 


3 

3 a 


2 
2 a 


1 
1 






2 
1 


2 



2 
1/HT 


1 
1 






Nonbearing walls and partitions 
Exterior 


See Table 602 


Nonbearing walls and partitions 
Interior 6 




















See Section 602.4.6 








Floor construction and secondary 
members (see Section 202) 


2 


2 


1 





1 





HT 


1 





Roof construction and secondary 
members (see Section 202) 


1 1 / 2 b 


1b, c 


1b, c 


oc 


1b, c 





HT 


1b, c 






For SI: 1 foot = 304.8 mm. 

a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only. 

b. Except in Group F-l, H, M and S-l occupancies, fire protection of structural members shall not be required, including protection of roof framing and decking 
where every part of the roof construction is 20 feet or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used 
for such unprotected members. 

c. In all occupancies, heavy timber shall be allowed where a I-hour or less fire-resistance rating is required. 

d. An approved automatic sprinkler system in accordance with Section 903.3.1.1 shall be allowed to be substituted for I-hour fire-resistance-rated construction, pro- 
vided such system is not otherwise required by other provisions of the code or used for an allowable area increase in accordance with Section 506.3 or an allowable 
height increase in accordance with Section 504.2. The I-hour substitution for the fire resistance of exterior walls shall not be permitted. 

e. Not less than the fire-resistance rating required by other sections of this code. 

f. Not less than the fire-resistance rating based on fire separation distance (see Table 602). 

g. Not less than the fire-resistance rating as referenced in Section 704.10 



2009 INTERNATIONAL BUILDING CODE® 



89 



TYPES OF CONSTRUCTION 



details of Type IV construction shall comply with the provi- 
sions of this section. Fire-retardant-treated wood framing 
complying with Section 2303.2 shall be permitted within exte- 
rior wall assemblies with a 2-hour rating or less. Minimum 
solid sawn nominal dimensions are required for structures built 
using Type IV construction (HT) . For glued-laminated mem- 
bers the equivalent net finished width and depths correspond- 
ing to the minimum nominal width and depths of solid sawn 
lumber are required as specified in Table 602.4. 

602.4.1 Columns. Wood columns shall be sawn or glued 
laminated and shall not be less than 8 inches (203 mm), 
nominal, in any dimension where supporting floor loads and 
not less than 6 inches (152 mm) nominal in width and not 
less than 8 inches (203 mm) nominal in depth where sup- 
porting roof and ceiling loads only. Columns shall be con- 
tinuous or superimposed and connected in an approved 
manner. 

602.4.2 Floor framing. Wood beams and girders shall be of 
sawn or glued-laminated timber and shall be not less than 6 
inches (152 mm) nominal in width and not less than 10 
inches (254 mm) nominal in depth. Framed sawn or 
glued-laminated timber arches, which spring from the floor 
line and support floor loads, shall be not less than 8 inches 
(203 mm) nominal in any dimension. Framed timber trusses 



supporting floor loads shall have members of not less than 8 
inches (203 mm) nominal in any dimension. 

602.4.3 Roof framing. Wood-frame or glued-laminated 
arches for roof construction, which spring from the floor 
line or from grade and do not support floor loads, shall have 
members not less than 6 inches (152 mm) nominal in width 
and have not less than 8 inches (203 mm) nominal in depth 
for the lower half of the height and not less than 6 inches 
(152 mm) nominal in depth for the upper half. Framed or 
glued-laminated arches for roof construction that spring 
from the top of walls or wall abutments, framed timber 
trusses and other roof framing, which do not support floor 
loads, shall have members not less than 4 inches (102 mm) 
nominal in width and not less than 6 inches (152 mm) nomi- 
nal in depth. Spaced members shall be permitted to be com- 
posed of two or more pieces not less than 3 inches (76 mm) 
nominal in thickness where blocked solidly throughout 
their intervening spaces or where spaces are tightly closed 
by a continuous wood cover plate of not less than 2 inches 
(51 mm) nominal in thickness secured to the underside of 
the members. Splice plates shall be not less than 3 inches (76 
mm) nominal in thickness. Where protected by approved 
automatic sprinklers under the roof deck, framing members 
shall be not less than 3 inches (76 mm) nominal in width. 



TABLE 602 
FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE 3 , . 



FIRE SEPARATION DISTANCE =X 

(feet) 


TYPE OF CONSTRUCTION 


OCCUPANCY 
GROUPH f 


OCCUPANCY 
GROUP F-1, M, S-19 


OCCUPANCY 
GROUP A, B, E, F-2, 1, R, S-29, U b 


X< 5 C 


All 


3 


2 


1 


5<X<10 


IA 
Others 


3 
2 


2 

1 


1 
1 


10<X<30 


IA,IB 
IIB, VB 
Others 


2 

1 
1 


1 

1 


l d 

l d 


X>30 


All 












For SI: 1 foot = 304.8 mm. 

a. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601. 

b. For special requirements for Group U occupancies, see Section 406.1.2. 

c. See Section 706. 1. 1 for party walls. 

d. Open parking garages complying with Section 406 shall not be required to have a fire-resistance rating. 

e. The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located. 

f. For special requirements for Group H occupancies, see Section 415.3. 

g. For special requirements for Group S aircraft hangars, see Section 412.4.1. 

TABLE 602.4 
WOOD MEMBER SIZE 



MINIMUM NOMINAL SOLID SAWN SIZE 


MINIMUM GLUED-LAMINATED NET SIZE 


Width, inch 


Depth, inch 


Width, inch 


Depth, inch 


8 


8 


63/ 4 


8% 


6 


10 


5 


10 1 / 2 


6 


8 


5 


8% 


6 


6 


5 


6 


4 


6 


3 


6 7 >s 



For SI: 1 inch = 25.4 mm. 



90 



2009 INTERNATIONAL BUILDING CODE® 



TYPES OF CONSTRUCTION 



602 .4 .4 Floors. Floors shall be without concealed spaces. 
Wood floors shall be of sawn or glued-laminated planks, 
splined or tongue-and-groove, of not less than 3 inches (76 
mm) nominal in thickness covered with I-inch (25 mm) 
nominal dimension tongue-and-groove flooring, laid cross- 
wise or diagonally, or 0.5-inch (12.7 mm) particleboard or 
planks not less than 4 inches (102 mm) nominal in width set 
on edge close together and well spiked and covered with 
I-inch (25 mm) nominal dimension flooring or i5/ 32 -inch 
(12 mm) wood structural panel or 0.5-inch (12.7 mm) 
particleboard. The lumber shall be laid so that no continu- 
ous line of joints will occur except at points of support. 
Floors shall not extend closer than 0.5 inch (12.7 mm) to 
walls. Such 0.5-inch (12.7 mm) space shall be covered by a 
molding fastened to the wall and so arranged that it will not 
obstruct the swelling or shrinkage movements of the floor. 
Corbeling of masonry walls under the floor shall be permit- 
ted to be used in place of molding. 

602.4.5 Roofs. Roofs shall be without concealed spaces and 
wood roof decks shall be sawn or glued laminated, splined 
or tongue-and-groove plank, not less than 2 inches (51 mm) 
nominal in thickness, lVs-inch-thick (32 mm) wood struc- 
tural panel (exterior glue), or of planks not less than 3 inches 
(76 mm) nominal in width, set on edge close together and 
laid as required for floors. Other types of decking shall be 
permitted to be used if providing equivalent fire resistance 
and structural properties. 

602.4.6 Partitions. Partitions shall be of solid wood con- 
struction formed by not less than two layers of I-inch (25 
mm) matched boards or laminated construction 4 inches 
(102 mm) thick, or of I-hour fire-resistance-rated construc- 
tion. 

602.4.7 Exterior structural members. Where a horizontal 
separation of 20 feet (6096 mm) or more is provided, wood 
columns and arches conforming to heavy timber sizes shall 
be permitted to be used externally. 

602.5 Type V. Type V construction is that type of construction 
in which the structural elements, exterior walls and interior 
walls are of any materials permitted by this code. 



SECTION 603 

COMBUSTIBLE MATERIAL IN TYPE I 

AND II CONSTRUCTION 

603.1 Allowable materials. Combustible materials shall be 
permitted in buildings of Type I or II construction in the follow- 
ing applications and in accordance with Sections 603.1.1 
through 603.1.3: 

1. Thermal and acoustical insulation, other than foam 
plastics, having aflame spread index of noi more than 

25. 

Exceptions: 

1. Insulation placed between two layers of 
noncombustible materials without an interven- 
ing airspace shall be allowed to have a flame 
spread index of noi more than 100. 



2. Insulation installed between a finished floor 
and solid decking without intervening airspace 
shall be allowed to have aflame spreadindexof 
not more than 200. 

2. Foam plastics in accordance with Chapter 26. 

3. Roof coverings that have an A, B or C classification. 

4. Interior floor finish and floor covering materials 
installed in accordance with Section 804. 

5. Millwork such as doors, door frames, window sashes 
and frames. 

6. Interior wall and ceiling finishes installed in accor- 
dance with Sections 801 and 803. 

7. Trim installed in accordance with Section 806. 

8. Where not installed over 15 feet (4572 mm) above 
grade, show windows, nailing or furring strips and 
wooden bulkheads below show windows, including 
their frames, aprons and show cases. 

9. Finish flooring installed in accordance with Section 
805. 

10. Partitions dividing portions of stores, offices or similar 
places occupied by one tenant only and that do not 
establish a corridor serving an occupant load of 30 or 
more shall be permitted to be constructed of fire -retar- 
dant-treated wood, I-hour fire-resistance-rated con- 
struction or of wood panels or similar light construction 
up to 6 feet (1829 mm) in height. 

11. Stages and platforms constructed in accordance with 
Sections 410.3 and 410.4, respectively. 

12. Combustible exterior wall coverings, balconies and 
similar projections and bay or oriel windows in accor- 
dance with Chapter 14. 

13. Blocking such as for handrails, millwork, cabinets and 
window and door frames. 

14. Light-transmitting plastics as permitted by Chapter 26. 

15. Mastics and caulking materials applied to provide flex- 
ible seals between components of exterior wall con- 
struction. 

16. Exterior plastic veneer installed in accordance with 
Section 2605.2. 

17. Nailing or furring strips as permitted by Section 803.4. 

18. Heavy timber as permitted by Note c to Table 601 and 
Sections 602.4.7 and 1406.3. 

19. Aggregates, component materials and admixtures as 
permitted by Section 703.2.2. 

20. Sprayed fire-resistant materials and intumescent and 
mastic fire-resistant coatings, determined on the basis 
of fire-resistance tests in accordance with Section 
703.2 and installed in accordance with Sections 
1704.12 and 1704.13, respectively. 

21. Materials used to protect penetrations in fire-resis- 
tance-rated assemblies in accordance with Section 713. 

22. Materials used to protect joints in fire-resistance-rated 
assemblies in accordance with Section 714. 



2009 INTERNATIONAL BUILDING CODE® 



91 



TYPES OF CONSTRUCTION 



23. Materials allowed in the concealed spaces of buildings 
of Types I and II construction in accordance with Sec- 
tion 717.5. 

24. Materials exposed within plenums complying with 
Section 602 of the International Mechanical Code. 

25. Fire-retardant-treated woo d shall be permitted in: 

25.1. Nonbearing partitions where the required 
fire-resistance ratingis 2 hours or less. 

25.2. Nonbearing exterior walls where no fire rating 
is required. 

25.3. Roof construction, including girders, trusses, 
framing and decking. 

Exception: In buildings of Type IA construc- 
tion exceeding two stories above grade plane, 
fire-retardant-treated woodis not permitted in 
roof construction when the vertical distance 
from the upper floor to the roof is less than 20 
feet (6096 mm). 

603.1.1 Ducts. The use of nonmetallic ducts shall be per- 
mitted when installed in accordance with the limitations of 
the International Mechanical Code. 

603.1.2 Piping. The use of combustible piping materials 
shall be permitted when installed in accordance with the 
limitations of the International Mechanical Code and the 
International Plumbing Code. 

603.1.3 Electrical. The use of electrical wiring methods 
with combustible insulation, tubing, raceways and related 
components shall be permitted when installed in accor- 
dance with the limitations of this code. 



92 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 7 

FIRE AND SMOKE PROTECTION FEATURES 



I 



SECTION 701 
GENERAL 

701.1 Scope. The provisions of this chapter shall govern the 
materials, systems and assemblies used for structural fire resis- 
tance and fire-resistance-rated construction separation of adja- 
cent spaces to safeguard against the spread of fire and smoke 
within a building and the spread of fire to or from buildings. 



SECTION 702 
DEFINITIONS 

702.1 Definitions. The following words and terms shall, for the 
purposes of this chapter, and as used elsewhere in this code, 
have the meanings shown herein. 

ANNULAR SPACE. The opening around the penetrating 
item. 

I BUILDING ELEMENT. A fundamental component of build- 
ing construction, listed in Table 601, which mayor may not be 
of fire-resistance-rated construction and is constructed of 
materials based on the building type of construction. 

CEILING RADIATION DAMPER. A listeddevice installed 
in a ceiling membrane of a fire-resistance-rated floor/ceiling or 
roof/ceiling assembly to limit automatically the radiative heat 
transfer through an air inlet/outlet opening. 

COMBINATION FIRE/SMOKE DAMPER. A listed 
device installed in ducts and air transfer openings designed to 
close automatically upon the detection of heat and resist the 
passage of flame and smoke. The device is installed to operate 
automatically, controlled by a smoke detection system, and 
where required, is capable of being positioned from a fire com- 
mand center. 

DAMPER. See "Ceiling radiation damper," "Combination 
fire/smoke damper, " "Fire damper" and "Smoke damper. " 

DRAFTSTOP. A material, device or construction installed to 
restrict the movement of air within open spaces of concealed 
areas of building components such as crawl spaces, floor/ceil- 
ing assemblies, roof/ceiling assemblies and attics. 

F RATING. The time period that the through-penetration 
firestop system limits the spread of fire through the penetration 
when tested in accordance with ASTM E 814 or UL 1479. 

FIRE BARRIER. A fire-resistance-rated wall assembly of 
materials designed to restrict the spread of fire in which conti- 
nuity is maintained. 

FIRE DAMPER. A listed device installed in ducts and air 
transfer openings designed to close automatically upon detec- 
tion of heat and resist the passage of flame. Fire dampers are 
classified for use in either static systems that will automatically 
shut down in the event of a fire, or in dynamic systems that con- 
tinue to operate during a fire. A dynamic fire damper is tested 
and rated for closure under elevated temperature airflow. 



FIRE DOOR. The door component of afire door assembly. 

FIRE DOOR ASSEMBLY. Any combination of afire door, 
frame, hardware and other accessories that together provide a 
specific degree of fire protection to the opening. 

FIRE PARTITION. A vertical assembly of materials 
designed to restrict the spread of fire in which openings are pro- 
tected. 

FIRE PROTECTION RATING. The period of time that an 
opening protective will maintain the ability to confine a fire as 
determined by tests prescribed in Section 715. Ratings are 
stated in hours or minutes. 

FIRE RESISTANCE. That property of materials or their 
assemblies that prevents or retards the passage of excessive 
heat, hot gases or flames under conditions of use. 

FIRE-RESISTANCE RATING. The period of time a build- 
ing element, component or assembly maintains the ability to 
confine a fire, continues to perform a given structural function, 
or both, as determined by the tests, or the methods based on 
tests, prescribed in Section 703. 

FIRE-RESISTANT JOINT SYSTEM. An assemblage of 
specific materials or products that are designed, tested and 
fire-resistance rated in accordance with either ASTM E 1966 or 
UL 2079 to resist for a prescribed period of time the passage of 
fire through joints made in or between fire-resistance-rated 
assemblies. 

FIRE SEPARATION DISTANCE. The distance measured 
from the building face to one of the following: 

1. The closest interior lot line; 

2. To the centerline of a street, an alley or public way; or 

3. To an imaginary line between two buildings on the prop- 
erty. 

The distance shall be measured at right angles from the face 
of the wall. 

FIRE WALL. A fire- resistance- rated wall having protected 
openings, which restricts the spread of fire and extends contin- 
uously from the foundation to or through the roof, with suffi- 
cient structural stability under fire conditions to allow collapse 
of construction on either side without collapse of the wall. 

FIRE WINDOW ASSEMBLY. A window constructed and 
glazed to give protection against the passage of fire. 

FIREBLOCKING. Building materials or materials for use as 
fireblocking, installed to resist the free passage of flame to 
other areas of the building through concealed spaces. 

FLOOR FIRE DOOR ASSEMBLY. A combination of afire 
door, a frame, hardware and other accessories installed in a hor- 
izontal plane, which together provide a specific degree of fire 
protection to a through-opening in a fire-resistance-rated floor 
(see Section 712.8). 



2009 INTERNATIONAL BUILDING CODE® 



93 



FIRE AND SMOKE PROTECTION FEATURES 



HORIZONTAL ASSEMBLY. A fire-resistance-rated floor 
or roof assembly of materials designed to restrict the spread of 
fire in which continuity is maintained. 

JOINT. The linear opening in or between adjacent fire-resis- 
tance-rated assemblies that is designed to allow independent 
movement of the building in any plane caused by thermal, seis- 
mic, wind or any other loading. 

MEMBRANE PENETRATION. An opening made through 
one side (wall, floor or ceiling membrane) of an assembly. 

MEMBRANE-PENETRATION FIRESTOP. A material, 
device or construction installed to resist for a prescribed time 
period the passage of flame and heat through openings in a pro- 
tective membrane in order to accommodate cables, cable trays, 
conduit, tubing, pipes or similar items. 

MINERAL FIBER. Insulation composed principally of fibers 
manufactured from rock, slag or glass, with or without binders. 

MINERAL WOOL. Synthetic vitreous fiber insulation made 
by melting predominately igneous rock or furnace slag, and 
other inorganic materials, and then physically forming the melt 
into fibers. 

PENETRATION FIRESTOP. A through penetration 
firestop or a membrane-penetration firestop. 

SELF-CLOSING. As applied to afire door or other opening 
protective, means equipped with an device that will ensure 
closing after having been opened. 

SHAFT. An enclosed space extending through one or more 
stories of a building, connecting vertical openings in succes- 
sive floors, or floors and roof. 

SHAFT ENCLOSURE. The walls or construction forming 
the boundaries of a shaft. 

SMOKE BARRIER. A continuous membrane, either vertical 
or horizontal, such as a wall, floor or ceiling assembly, that is 
designed and constructed to restrict the movement of smoke. 

SMOKE COMPARTMENT. A space within a building 
enclosed by smoke barriers on all sides, including the top and 
bottom. 

SMOKE DAMPER. A listed device installed in ducts and air 
transfer openings designed to resist the passage of smoke. The 
device is installed to operate automatically, controlled by a 
smoke detection system, and where required, is capable of 
being positioned from a fire command center. 

SPLICE. The result of a factory and/or field method ofjoining 
or connecting two or more lengths of a fire-resistant joint sys- 
tem into a continuous entity. 

T RATING. The time period that the penetration firestop sys- 
tem, including the penetrating item, limits the maximum tem- 
perature rise to 325°F (163°C) above its initial temperature 
through the penetration on the nonfire side when tested in 
accordance with ASTM E 814 or UL 1479. 

THROUGH PENETRATION. An opening that passes 
through an entire assembly. 

THROUGH-PENETRATION FIRESTOP SYSTEM. An 

assemblage of specific materials or products that are designed, 
tested and fire-resistance rated to resist for a prescribed period 



of time the spread of fire through penetrations. The F and T 
rating criteria for penetration firestop systems shall be in accor- 
dance with ASTM E 814 or UL 1479. See definitions of "F rat- 
ing" and "T rating." 



SECTION 703 
FIRE-RESISTANCE RATINGS AND FIRE TESTS 

703.1 Scope. Materials prescribed herein for fire resistance 
shall conform to the requirements of this chapter. 

703.2 Fire-resistance ratings. The fire-resistance rating of 
building elements, components or assemblies shall be deter- 
mined in accordance with the test procedures set forth in 
ASTM E 119 or UL 263 or in accordance with Section 703.3. 
Where materials, systems or devices that have not been tested 
as part of a fire-resistance-rated assembly are incorporated into 
the building element, component or assembly, sufficient data 
shall be made available to the building officialto show that the 
required fire-resistance rating is not reduced. Materials and 
methods of construction used to protect joints and penetrations 
in fire-resistance-rated building elements, components or 
assemblies shall not reduce the required fire-resistance rating. 

Exception: In determining the fire-resistance rating of 
exterior bearing walls, compliance with the ASTM E 119 or 
UL 263 criteria for unexposed surface temperature rise and 
ignition of cotton waste due to passage of flame or gases is 
required only for a period of time corresponding to the 
required fire-resistance rating of an exterior nonbearing 
wall with the same fire separation distance, and in a build- 
ing of the same group. When the fire-resistance rating 
determined in accordance with this exception exceeds the 
fire-resistance rating determined in accordance with ASTM 
E 119 or UL 263, the fire exposure time period, water pres- 
sure and application duration criteria for the hose stream test 
of ASTM E 119 or UL 263 shall be based upon the 
fire-resistance rating determined in accordance with this 
exception. 

703.2.1 Nonsymmetrical wall construction. Interior walls 
and partitions of nonsymmetrical construction shall be 
tested with both faces exposed to the furnace, and the 
assigned fire-resistance rating shall be the shortest duration 
obtained from the two tests conducted in compliance with 
ASTM E 119 or UL 263. When evidence is furnished to 
show that the wall was tested with the least fire-resistant side 
exposed to the furnace, subject to acceptance of the building 
official, the wall need not be subjected to tests from the 
opposite side (see Section 705.5 for exterior walls). 

703.2.2 Combustible components. Combustible aggre- 
gates are permitted in gypsum and portland cement concrete 
mixtures for fire-resistance-rated construction. Any compo- 
nent material or admixture is permitted in assemblies if the 
resulting tested assembly meets the fire-resistance test 
requirements of this code. 

703.2.3 Restrained classification. Fire-resistance-rated 
assemblies tested under ASTM E 1 19 or UL 263 shall not be 
considered to be restrained unless evidence satisfactory to 
the bUilding official is furnished by the registered design 
professional showing that the construction qualifies for a 



94 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



restrained classification in accordance with ASTM E 119 or 
UL 263. Restrained construction shall be identified on the 
plans. 

703.3 Alternative methods for determining fire resistance. 

The application of any of the alternative methods listed in this 
section shall be based on the fire exposure and acceptance crite- 
ria specified in ASTM E 1 19 or UL 263. The required fire resis- 
tance of a building element, component or assembly shall be 
permitted to be established by any of the following methods or 
procedures: 

1. Fire-resistance designs documented in sources. 

2. Prescriptive designs of fire-resistance-rated building 
elements, components or assemblies as prescribed in 
Section 720. 

3. Calculations in accordance with Section 721 . 

4. Engineering analysis based on a comparison of building 
element, component or assemblies designs having 
fire-resistance ratings as determined by the test proce- 
dures set forth in ASTM E 119 or UL 263. 

5. Alternative protection methods as allowed by Section 
104.11. 

703.4 Noncombustibility tests. The tests indicated in Sections 
703.4.1 and 703.4.2 shall serve as criteria for acceptance of 
building materials as set forth in Sections 602.2, 602.3 and 

602.4 in Type I, II, III and IV construction. The term 
"noncombustible" does not apply to the flame spread charac- 
teristics of interior finish or trim materials. A material shall not 
be classified as a noncombustible building construction mate- 
rial if it is subject to an increase in combustibility or flame 
spread beyond the limitations herein established through the 
effects of age, moisture or other atmospheric conditions. 

703.4.1 Elementary materials. Materials required to be 
noncombustible shall be tested in accordance with ASTM E 
136. 

703.4.2 Composite materials. Materials having a struc- 
tural base of noncombustible material as determined in 
accordance with Section 703.4.1 with a surfacing not more 
than 0.125 inch (3.18 mm) thick that has aflame spread 
index not greater than 50 when tested in accordance with 
ASTM E 84 or UL 723 shall be acceptable as 
noncombustible materials. 

703.5 Fire-resistance-rated glazing. Fire-resistance-rated 
glazing, when tested in accordance with ASTM E 119 or UL 
263 and complying with the requirements of Section 707, shall 
be permitted. Fire-resistance-rated glazing shall bear a label or 
other identification showing the name of the manufacturer, the 
test standard and the identifier "W-XXX," where the "XXX" is 
the fire-resistance rating in minutes. Such label or identifica- 
tion shall be issued by an agency and shall be permanently 
affixed to the glazing. 

703.6 Marking and identification. Fire walls, fire barriers, 
fire partitions, smoke barriers and smoke partitions or any 
other wall required to have protected openings or penetrations 



shall be effectively and permanently identified with signs or 
stenciling. Such identification shall: 

1. Be located in accessible concealed floor, floor-ceiling or 
attic spaces; 

2. Be repeated at intervals not exceeding 30 feet (914 mm) 
measured horizontally along the wall or partition; and 

3. Include lettering not less than 0.5 inch (12.7 mm) in 
height, incorporating the suggested wording: "FIRE 
AND/OR SMOKE BARRIER-PROTECT ALL 
OPENINGS," or other wording. 

Exception: Walls in Group R-2 occupancies that do 
not have a removable decorative ceiling allowing 
access to the concealed space. 



SECTION 704 

FIRE-RESISTANCE RATING OF 

STRUCTURAL MEMBERS 

704.1 Requirements. The fire-resistance ratings of structural 
members and assemblies shall comply with this section and the 
requirements for the type of construction as specified in Table 
601. The fire-resistance ratings shall not be less than the rat- 
ings required for the fire-resistance-rated assemblies supported 
by the structural members. 

Exception: Fire barriers, fire partitions, smoke barriers 
and horizontal assemblies as provided in Sections 707.5, 
709.4, 710.4 and 712.4, respectively. 

704.2 Column protection. Where columns are required to be 
fire-resistance rated, the entire column shall be provided indi- 
vidual encasement protection by protecting it on all sides for 
the full column length, including connections to other struc- 
tural members, with materials having the required fire-resis- 
tance rating. Where the column extends through a ceiling, the 
encasement protection shall be continuous from the top of the 
foundation or floor/ceiling assembly below through the ceiling 
space to the top of the column. 

704.3 Protection of the primary structural frame other 
than columns. Members of the primary structural frame other 
than columns that are required to have a fire-resistance rating 
and support more than two floors or one floor and roof, or sup- 
port a load-bearing wall or a nonload-bearing wall more than 
two stories high, shall be provided individual encasement pro- 
tection by protecting them on all sides for their full length, 
including connections to other structural members, with mate- 
rials having the required fire-resistance rating. 

Exception: Individual encasement protection on all sides 
shall be permitted on all exposed sides provided the extent 
of protection is in accordance with the required fire-resis- 
tance rating, as determined in Section 703 . 

704.4 Protection of secondary members. Secondary mem- 
bers that are required to have a fire-resistance rating shall be 
protected by individual encasement protection, by the mem- 
brane or ceiling of a horizontal assembly in accordance with 
Section 712, or by a combination of both. 



2009 INTERNATIONAL BUILDING CODE® 



95 



FIRE AND SMOKE PROTECTION FEATURES 



704.4.1 Light-frame construction. King studs and bound- 
ary elements that are integral elements in load-bearing 
walls of light-frame construction shall be permitted to have 
required fire-resistance ratings provided by the membrane 
protection provided for the load-bearing wall. 

704.5 Truss protection. The required thickness and construc- 
tion of fire-resistance-rated assemblies enclosing trusses shall 
be based on the results of full-scale tests or combinations of 
tests on truss components or on appro vedcalculations based on 
such tests that satisfactorily demonstrate that the assembly has 
the required fire resistance. 

704.6 Attachments to structural members. The edges of 
lugs, brackets, rivets and bolt heads attached to structural mem- 
bers shall be permitted to extend to within 1 inch (25 mm) of the 
surface of the fire protection. 

704.7 Reinforcing. Thickness of protection for concrete or 
masonry reinforcement shall be measured to the outside of the 
reinforcement except that stirrups and spiral reinforcement ties 
are permitted to project not more than 0.5-inch (12.7 mm) into 
the protection. 

704.8 Embedments and enclosures. Pipes, wires, conduits, 
ducts or other service facilities shall not be embedded in the 
required fire protective covering of a structural member that is 
required to be individually encased. 

704.9 Impact protection. Where the fire protective covering 
of a structural member is subject to impact damage from mov- 
ing vehicles, the handling of merchandise or other activity, the 
fire protective covering shall be protected by corner guards or 
by a substantialjacket of metal or other noncombustible mate- 
rial to a height adequate to provide full protection, but not less 
than 5 feet (1524 mm) from the finished floor. 

I Exception: Corner protection is not required on concrete 
columns in open or enclosed parking garages. 

704.10 Exterior structural members. Load-bearing struc- 
tural members located within the exterior walls or on the out- 
side of a building or structure shall be provided with the highest 
fire-resistance ratings determined in accordance with the fol- 
lowing: 

1. As required by Table 601 for the type of building ele- 
ment based on the type of construction of the building; 

2. As required by Table 601 for exterior bearing walls 
based on the type of construction; and 

3. As required by Table 602 for exterior walls based on the 
fire separation distance. 

704.11 Bottom flange protection. Fire protection is not 
required at the bottom flange of lintels, shelf angles and plates, 
spanning not more than 6 feet (1829 mm) whether part of the 
primary structural frame or not, and from the bottom flange of 
lintels, shelf angles and plates not part of the primary structural 
frame, regardless of span. 

704.12 Seismic isolation systems. Fire-resistance ratings for 
the isolation system shall meet the fire -re si stance rating 
required for the columns, walls or other structural elements in 
which the isolation system is installed in accordance with Table 
601. Isolation systems required to have afire-resistance rating 
shall be protected with approved materials or construction 



assemblies designed to provide the same degree of fire resis- 
tance as the structural element in which it is installed when 
tested in accordance with ASTM E 119 or UL 263 (see Section 
703.2). 

Such isolation system protection applied to isolator units 
shall be capable of retarding the transfer of heat to the isolator 
unit in such a manner that the required gravity load-carrying 
capacity of the isolator unit will not be impaired after exposure 
to the standard time-temperature curve fire test prescribed in 
ASTM E 119 or UL 263 for a duration not less than that 
required for the fire-resistance rating of the structure element 
in which it is installed. 

Such isolation system protection applied to isolator units 
shall be suitably designed and securely installed so as not to 
dislodge, loosen, sustain damage or otherwise impair its ability 
to accommodate the seismic movements for which the isolator 
unit is designed and to maintain its integrity for the purpose of 
providing the required fire-resistance protection. 

704.13 Sprayed fire-resistant materials (SFRM). Sprayed 
fire-resistant materials (SFRM) shall comply with Sections 
704.13.1 through 704.13.5. 

704.13.1 Fire-resistance rating. The application of SFRM 
shall be consistent with the fire-resistance rating and the 
listing, including, but not limited to, minimum thickness 
and dry density of the applied SFRM, method of applica- 
tion, substrate surface conditions and the use of bonding 
adhesives, sealants, reinforcing or other materials. 

704.13.2 Manufacturer's installation instructions. The 
application of SFRM shall be in accordance with the manu- 
facturer's installation instructions. The instructions shall 
include, but are not limited to, substrate temperatures and 
surface conditions and SFRM handling, storage, mixing, 
conveyance, method of application, curing and ventilation. 

704.13.3 Substrate condition. The SFRM shall be applied 
to a substrate in compliance with Sections 704.13.3.1 
through 704.13.3.2. 

704.13.3.1 Surface conditions. Substrates to receive 
SFRM shall be free of dirt, oil, grease, release agents, 
loose scale and any other condition that prevents adhe- 
sion. The substrates shall also be free of primers, paints 
and encapsulants other than those fire tested and listedby 
a nationally recognized testing agency. Primed, painted 
or encapsulated steel shall be allowed, provided that test- 
ing has demonstrated that required adhesion is main- 
tained. 

704.13.3.2 Primers, paints and encapsulants. Where 
the SFRM is to be applied over primers, paints or 
encapsulants other than those specified in the listing, the 
material shall be field tested in accordance with ASTM E 
736. Where testing of the SFRM with primers, paints or 
encapsulants demonstrates that required adhesion is 
maintained, SFRM shall be permitted to be applied to 
primed, painted or encapsulated wide flange steel shapes 
in accordance with the following conditions: 

1. The beam flange width does not exceed 12 inches 
(305 mm); or 



96 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



2. The column flange width does not exceed 16 
inches (400 mm); or 

3. The beam or column web depth does not exceed 16 
inches (400 mm). 

4. The average and minimum bond strength values 
shall be determined based on a minimum of five 
bond tests conducted in accordance with ASTM E 
736. Bond tests conducted in accordance with 
ASTM E 736 shall indicate a minimum average 
bond strength of 80 percent and a minimum indi- 
vidual bond strength of 50 percent, when com- 
pared to the bond strength of the SFRM as applied 
to clean uncoated l/ s -inch-thick (3-mm) steel plate. 

704.13.4 Temperature. A minimum ambient and substrate 
temperature of 40°F (4.44°C) shall be maintained during 
and for a minimum of 24 hours after the application of the 
SFRM, unless the manufacturer's installation instructions 
allow otherwise. 

704.13.5 Finished condition. The finished condition of 
SFRM applied to structural members or assemblies shall 
not, upon complete drying or curing, exhibit cracks, voids, 
spalls, delamination or any exposure of the substrate. Sur- 
face irregularities of SFRM shall be deemed acceptable. 



SECTION 705 
EXTERIOR WALLS 

705.1 General. Exterior walls shall comply with this section. 

705.2 Projections. Cornices, eave overhangs, exterior balco- 
nies and similar projections extending beyond the exterior wall 
shall conform to the requirements of this section and Section 
1406. Exterior egress balconies and exterior exit stairways 
shall also comply with Sections 1019 and 1026, respectively. 
Projections shall not extend beyond the distance determined by 
the following three methods, whichever results in the lesser 
projection: 

1. A point one-third the distance from the exterior face of 
the wall to the lot line where protected openings or a 
combination of protected and unprotected openings are 
required in the exterior wall 

2. A point one-half the distance from the exterior face of the 
wall to the lot line where all openings in the exterior wall 
are permitted to be unprotected or the building is 
equipped throughout with an automatic sprinkler system 
installed under the provisions of Section 705.8.2. 

3. More than 12 inches (305 mm) into areas where open- 
ings are prohibited. 

Buildings on the same lot and considered as portions of one 
building in accordance with Section 705 .3 are not required to 
comply with this section. 

705.2.1 Type land II construction. Projections from walls 

of Type I or II construction shall be of noncombustible 
materials or combustible materials as allowed by Sections 
1406.3 and 1406.4. 



705.2.2 Type III, IV or V construction. Projections from 
walls of Type III, IV or V construction shall be of any 
approved material. 

705.2.3 Combustible projections. Combustible projec- 
tions located where openings are not permitted or where 
protection of openings is required shall be of at least I-hour 
fire-resistance-rated construction, Type IV construction, 
fire-retardant-treated wood or as required by Section 

1406.3. 

Exception: Type V construction shall be allowed for R-3 
occupancies. 

705.3 Buildings on the same lot. For the purposes of deter- 
mining the required wall and opening protection and roof-cov- 
ering requirements, buildings on the same lot shall be assumed 
to have an imaginary line between them. 

Where a new building is to be erected on the same lot as an 
existing building, the location of the assumed imaginary line 
with relation to the existing building shall be such that the exte- 
rior wall mid opening protection of the existing building meet 
the criteria as set forth in Sections 705.5 and 705.8. 

Exception: Two or more buildings on the same lot shall 
either be regulated as separate buildings or shall be consid- 
ered as portions of one building if the aggregate area of such 
buildings is within the limits specified in Chapter 5 for a sin- 
gle building. Where the buildings contain different occu- 
pancy groups or are of different types of construction, the 
area shall be that allowed for the most restrictive occupancy 
or construction. 

705.4 Materials. Exterior walls shall be of materials permitted 
by the building type of construction. 

705.5 Fire-resistance ratings. Exterior walls shall be 
fire-resistance rated in accordance with Tables 601 and 602 and 
this section. The required fire -resistance rating of exterior 
walls with a fire separation distance of greater than 10 feet 
(3048 mm) shall be rated for exposure to fire from the inside. 
The required fire -resistance rating of exterior walls with afire 
separation distance of less than or equal to 10 feet (3048 mm) 
shall be rated for exposure to fire from both sides. 

705.6 Structural stability. The wall shall extend to the height 
required by Section 705 .11 and shall have sufficient structural 
stability such that it will remain in place for the duration of time 
indicated by the required fire-resistance rating. 

705.7 Unexposed surface temperature. Where protected 
openings are not limited by Section 705.8, the limitation on the 
rise of temperature on the unexposed surface of exterior walls 
as required by ASTM E 119 or UL 263 shall not apply. Where 
protected openings are limited by Section 705.8, the limitation 
on the rise of temperature on the unexposed surface of exterior 
walls as required by ASTM E 119 or UL 263 shall not apply 
provided that a correction is made for radiation from the unex- 
posed exterior wall surface in accordance with the following 
formula: 



A e =A+(A f xFJ 

where: 

A e = Equivalent area of protected openings. 



(Equation 7-1) 



2009 INTERNATIONAL BUILDING CODE® 



97 



FIRE AND SMOKE PROTECTION FEATURES 



A = Actual area of protected openings. 

A f = Area of exterior wall surface in the sto ry under consid- 
eration exclusive of openings, on which the tempera- 
ture limitations of ASTM E 1 19 or UL 263 for walls are 
exceeded. 

F eo = An "equivalent opening factor" derived from Figure 
705.7 based on the average temperature of the unex- 
posed wall surface and the fire-resistance rating of the 
wall. 

705.8 Openings. Openings in exterior walls shall comply with 
Sections 705.8.1 through 705.8.6. 

705.8.1 Allowable area of openings. The maximum area of 
unprotected and protected openings permitted in an exterior 
wall in any story of a building shall not exceed the percent- 
ages specified in Table 705.8. 

Exceptions: 

1. In other than Group H occupancies, unlimited 
unprotected openings are permitted in the first 
story above grade either: 

1.1. Where the wall faces a street and has afire 
separation distance of more than 15 feet 
(4572 mm); or 



1.2. Where the wall faces an unoccupied space. 
The unoccupied space shall be on the same 
lot or dedicated for public use, shall not be 
less than 30 feet (9144 mm) in width and 
shall have access from a street by a posted 
fire lane in accordance with the Interna- 
tional Fire Code. 

2. Buildings whose exterior bearing walls, exterior 
nonbearing walls and exterior primary structural 
frame are not required to be fire-resistance rated 
shall be permitted to have unlimited unprotected 
openings. 

705.8.2 Protected openings. Where openings are required 
to be protected, fire doors and fire shutters shall comply 
with Section 715.4 and fire window assemblies shall comply 
with Section 715.5. 

Exception: Opening protectives are not required where 
the building is equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1 
and the exterior openings are protected by a water curtain 
using automatic sprinklers approved for that use. 

705.8.3 Unprotected openings. Where unprotected open- 
ings are permitted, windows and doors shall be constructed 
of any approved materials. Glazing shall conform to the 
requirements of Chapters 24 and 26. 



at 

c 
"c 

2L 



o- 

LU 



For 51: °C = [(OF) -32] / 1.8. 



1.0 
0.9 
0.8 

' 0.7 

0.6 
0.5 

0.4 
0.3 
0.2 
0.1 



O200 400 600 800 1,000 1,200 1,400 1,600 1,800 2,000 
Average temperature of unexposed surface (OF) 



FIGURE 705.7 
EQUIVALENT OPENING FACTOR 

























3 
















§1 


J 






















4 


r H 












i 







































































































































98 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 705.8 
MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING PROTECTION 



FIRE SEPARATION DISTANCE 

(feet) 


DEGREE OF OPENING PROTECTION 


ALLOWABLE AREA a 


Oto less than 3 b ,c 


Unprotected, Nonsprinklered (UP, NS) 


Not Permitted 


Unprotected, Sprinklered (UP, S)i 


Not Permitted 


Protected (?) 


Not Permitted 


3 to less than 5 d ,e 


Unprotected, Nonsprinklered (UP, NS) 


Not Permitted 


Unprotected, Sprinklered (UP, S)i 


15% 


Protected (P) 


15% 


5 to less than 10 e ,f 


Unprotected, Nonsprinklered (UP, NS) 


10%h 


Unprotected, Sprinklered (UP, S)i 


25% 


Protected (P) 


25% 


10 to less than 15 e ,f, g 


Unprotected, Nonsprinklered (UP, NS) 


15%h 


Unprotected, Sprinklered (UP, S)i 


45% 


Protected (?) 


45% 


15 to less than 20 f , g 


Unprotected, Nonsprinklered (UP, NS) 


25% 


Unprotected, Sprinklered (UP, S)i 


75% 


Protected (?) 


75% 


20 to less than 25 f , g 


Unprotected, Nonsprinklered (UP, NS) 


45% 


Unprotected, Sprinklered (UP, S)i 


No Limit 


Protected (?) 


No Limit 


25 to less than 30 f , g 


Unprotected, Nonsprinklered (UP, NS) 


70% 


Unprotected, Sprinklered (UP, S)i 


No Limit 


Protected (?) 


No Limit 


30 or greater 


Unprotected, Nonsprinklered (UP, NS) 


No Limit 


Unprotected, Sprinklered (UP, S)i 


Not Required 


Protected (?) 


Not Required 



For SI: 1 foot = 304.8 mm. 

UP, NS = Unprotected openings in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 
UP, S = Unprotected openings in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 
P = Openings protected with an opening protective assembly in accordance with Section 705.8.2. 

a. Values indicated are the percentage of the area of the exterior wall, per story. 

b. For the requirements for fire walls of buildings with differing heights, see Section 706.6.1. 

c. For openings in a fire wall for buildings on the same lot, see Section 706.8. 

d. The maximum percentage of unprotected and protected openings shall be 25 percent for Group R-3 occupancies. 

e. Unprotected openings shall not be permitted for openings with a :fire separation distance of less than 15 feet for Group H-2 and H-3 occupancies. 

f. The area of unprotected and protected openings shall not be limited for Group R-3 occupancies, with afire separation distance of 5 feet or greater. 

g. The area of openings in an open parking structure with a :fire separation distance of 10 feet or greater shall not be limited, 
h. Includes buildings accessory to Group R-3. 

i. Not applicable to Group H-l, H-2 and H-3 occupancies. 



2009 INTERNATIONAL BUILDING CODE® 



99 



FIRE AND SMOKE PROTECTION FEATURES 



705.8.4 Mixed openings. Where both unprotected and pro- 
tected openings are located in the exterior wall in any story 
of a building, the total area of openings shall be determined 
in accordance with the following: 



(AJa) + (AJa u )<l 
where: 



(Equation 7-2) 



A p = Actual area of protected openings, or the equivalent 
area of protected openings, A e (see Section 705.7). 

a p = Allowable area of protected openings. 

Au = Actual area of unprotected openings. 

au = Allowable area of unprotected openings. 

705.8.5 Vertical separation of openings. Openings in exte- 
rior walls in adjacent stories shall be separated vertically to 
protect against fire spread on the exterior of the buildings 
where the openings are within 5 feet (1524 mm) of each 
other horizontally and the opening in the lower storyis not a 
protected opening with a fire protection rating of not less 
than 3/ 4 hour. Such openings shall be separated vertically at 
least 3 feet (914 mm) by spandrel girders, exterior walls or 
other similar assemblies that have a fire-resistance rating of 
at least 1 hour or by flame barriers that extend horizontally 
at least 30 inches (762 mm) beyond the exterior wall Flame 
barriers shall also have a fire-resistance rating of at least 1 
hour. The unexposed surface temperature limitations speci- 
fied in ASTM E 119 or UL 263 shall not apply to the flame 
barriers or vertical separation unless otherwise required by 
the provisions of this code. 

Exceptions: 

1. This section shall not apply to buildings that are 
three stories or less above grade plane. 

2. This section shall not apply to buildings equipped 
throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1 or 903.3.1.2. 

3. Open parking garages. 

705.8.6 Vertical exposure. For buildings on the same lot, 
opening protectives having a fire protection rating of not 
less than 3/4 hour shall be provided in every opening that is 
less than 15 feet (4572 mm) vertically above the roof of an 
adjacent building or structure based on assuming an imagi- 
nary line between them. The opening protectives are 
required where the fire separation distance between the 
imaginary line and the adjacent building or structure is less 
than 15 feet (4572 mm). 

Exceptions: 

1. Opening protectives are not required where the 
roof assembly of the adjacent building or structure 
has a fire-resistance rating of not less than 1 hour 
for a minimum distance of 10 feet (3048 mm) from 
the exterior wall facing the imaginary line and the 
entire length and span of the supporting elements 
for the fire-resistance-rated roof assembly has a 
fire-resistance rating of noi less than 1 hour. 

2. Buildings on the same lot and considered as por- 
tions of one building in accordance with Section 



705.3 are not required to comply with Section 
705.8.6. 

705.9 Joints. Joints made in or between exterior walls required 
by this section to have a fire-resistance rating shall comply 
with Section 714. 

Exception: Joints in exterior walls that are permitted to 
have unprotected openings. 

705.9.1 Voids. The void created at the intersection of a 
floor/ceiling assembly and an exterior curtain wall assem- 
bly shall be protected in accordance with Section 714.4. 

705.10 Ducts and air transfer openings. Penetrations by air 
ducts and air transfer openings in fire-resistance-rated exterior 
walls required to have protected openings shall comply with 
Section 716. 

Exception: Foundation vents installed in accordance with 
this code are permitted. 

705.11 Parapets. Parapets shall be provided on exterior walls 
of buildings. 

Exceptions: A parapet need not be provided on an exterior 
wall where any of the following conditions exist: 

1. The wall is not required to be fire-resistance rated in 
accordance with Table 602 because of fire separation 
distance. 

2. The building has an area of not more than 1,000 
square feet (93 m 2 ) on any floor. 

3. Walls that terminate at roofs of not less than 2-hour 
fire-resistance-rated construction or where the roof, 
including the deck or slab and supporting construc- 
tion, is constructed entirely of noncombustible mate- 
rials. 

4. One-hour fire-resistance-rated exterior walls that ter- 
minate at the underside of the roof sheathing, deck or 
slab, provided: 

4.1. Where the roof/ceiling framing elements are 
parallel to the walls, such framing and ele- 
ments supporting such framing shall not be of 
less than I-hour fire-resistance-rated con- 
struction for a width of 4 feet (1220 mm) for 
Groups Rand U and 10 feet (3048 mm) for 
other occupancies, measured from the interior 
side of the wall. 

4.2. Where roof/ceiling framing elements are not 
parallel to the wall, the entire span of such 
framing and elements supporting such fram- 
ing shall not be of less than I-hour fire-resis- 
tance-rated construction. 

4.3. Openings in the roof shall not be located 
within 5 feet (1524 mm) of the I-hour fire- re- 
sistance-rated exterior wall fox Groups Rand 
U and 10 feet (3048 mm) for other occupan- 
cies, measured from the interior side of the 
wall. 

4.4. The entire building shall be provided with not 
less than a Class B roof covering. 



100 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



5. In Groups R-2 and R-3 where the entire building is 
provided with a Class C roof covering, the exterior 
wall shall be permitted to terminate at the underside of 
the roof sheathing or deck in Type III, IV and V con- 
struction, provided: 

5.1. The roof sheathing or deck is constructed of 
approved noncombustible materials or of 
fire-retardant-treated woodfox a distance of 4 
feet (1220 mm); or 

5.2. The roof is protected with 0.625-inch (16 
mm) Type X gypsum board directly beneath 
the underside of the roof sheathing or deck, 
supported by a minimum of nominal 2-inch 
(51 mm) ledgers attached to the sides of the 
roof framing members for a minimum dis- 
tance of 4 feet (1220 mm). 

6. Where the wall is permitted to have at least 25 percent 
of the exterior wall areas containing unprotected 
openings based on fire separation distance as deter- 
mined in accordance with Section 705.8. 

705.11.1 Parapet construction. Parapets shall have the 
same fire -resistance rating as that required for the support- 
ing wall, and on any side adjacent to a roof surface, shall 
have noncombustible faces for the uppermost 18 inches 
(457 mm), including counterflashing and coping materials. 
The height of the parapet shall not be less than 30 inches 
(762 mm) above the point where the roof surface and the 
wall intersect. Where the roof slopes toward a parapet at a 
slope greater than two units vertical in 12 units horizontal 
(16.7 -percent slope), the parapet shall extend to the same 
height as any portion of the roof within afire separation dis- 
tance where protection of wall openings is required, but in 
no case shall the height be less than 30 inches (762 mm). 



SECTION 706 
FIRE WALLS 

706.1 General. Each portion of a building separated by one or 
more fire walls that comply with the provisions of this section 
shall be considered a separate building. The extent and location 
of such fire walls shall provide a complete separation. Where a 
fire wall also separates occupancies that are required to be sep- 
arated by afire barrier wall, the most restrictive requirements 
of each separation shall apply. 

706.1.1 Party walls. Any wall located on a lot line between 
adjacent buildings, which is used or adapted for joint service 
between the two buildings, shall be constructed as afire wall 
in accordance with Section 706. Party walls shall be con- 
structed without openings and shall create separate build- 
ings. 

Exception: Openings in a party wall separating an 
anchor building and a mall shall be in accordance with 
Section 402.7.3.1. 

706.2 Structural stability. Fire walls shall have sufficient 
structural stability under fire conditions to allow collapse of 
construction on either side without collapse of the wall for the 



duration of time indicated by the required fire-resistance rat- 
ing. 

706.3 Materials. Fire walls shall be of any approved 
noncombustible materials. 

Exception: Buildings of Type V construction. 

706.4 Fire-resistance rating. Fire walls shall have afire-resis- 
tance rating of not less than that required by Table 706.4. 

TABLE 706.4 
FIRE WALL FIRE-RESISTANCE RATINGS 



GROUP 


FIRE-RESISTANCE RATING (hours) 


A, B, E, H-4, I, R-l, R-2, U 


3 a 


F-l, H-3 b , H-S, M, 5-1 


3 


H-l, H-2 


4 b 


F-2, 5-2, R-3, R-4 


2 



a. In Type II or V construction, walls shall be permitted to have a 2-hour 
fire-resistance rating. 

b. For Group H-l, H-2 or H-3 buildings, also see Sections 415.4 and 415.5. 

706.5 Horizontal continuity. Fire walls shall be continuous 
from exterior wall to exterior wall and shall extend at least 18 
inches (457 mm) beyond the exterior surface of exterior walls. 

Exceptions: 

1. Fire walls shall be permitted to terminate at the inte- 
rior surface of combustible exterior sheathing or sid- 
ing provided the exterior wall has a fire-resistance 
rating of at least 1 hour for a horizontal distance of at 
least 4 feet (1220 mm) on both sides of the fire wall. 
Openings within such exterior walls shall be pro- 
tected by opening protectives having a fire protection 
rating of not less than 3/ 4 hour. 

2. Fire walls shall be permitted to terminate at the inte- 
rior surface of noncombustible exterior sheathing, 
exterior siding or other noncombustible exterior fin- 
ishes provided the sheathing, siding, or other exterior 
noncombustible finish extends a horizontal distance 
of at least 4 feet (1220 mm) on both sides of the fire 
wall. 

3. Fire walls shall be permitted to terminate at the inte- 
rior surface of noncombustible exterior sheathing 
where the building on each side of the fire wallis pro- 
tected by an automatic sprinkler system installed in 
accordance with Section 903.3.1.1 or 903.3.1.2. 

706.5.1 Exterior walls. Where the fire wall intersects exte- 
rior walls, the fire-resistance rating and opening protection 
of the exterior walls shall comply with one of the following: 

1. The exterior walls on both sides of the fire wall shall 
have a I-hom fire-resistance rating with 3/4-hour pro- 
tection where opening protection is required by Sec- 
tion 705.8. The fire-resistance rating of the exterior 
wall shall extend a minimum of 4 feet (1220 mm) on 
each side of the intersection of the fire wallto exterior 
wall. Exterior wall intersections at //re walls that form 
an angle equal to or greater than 180 degrees (3.14 
rad) do not need exterior wall protection. 



2009 INTERNATIONAL BUILDING CODE® 



101 



FIRE AND SMOKE PROTECTION FEATURES 



2. Buildings or spaces on both sides of the intersecting 
fire wall shall assume to have an imaginary lot line at 
the fire wall and extending beyond the exterior of the 
fire wall. The location of the assumed line in relation 
to the exterior walls and the fire wa//shall be such that 
the exterior wall and opening protection meet the 
requirements set forth in Sections 705.5 and 705.8. 
Such protection is not required for exterior walls ter- 
minating at fire walls that form an angle equal to or 
greater than 180 degrees (3.14 rad). 

706.5.2 Horizontal projecting elements. Fire walls shall 
extend to the outer edge of horizontal projecting elements 
such as balconies, roof overhangs, canopies, marquees and 
similar projections that are within 4 feet (1220 mm) of the 
fire wall. 

Exceptions: 

1. Horizontal projecting elements without concealed 
spaces, provided the exterior wall behind and 
below the projecting element has not less than 
I-hour fire-resistance-rated construction for a dis- 
tance not less than the depth of the projecting ele- 
ment on both sides of the fire wall. Openings 
within such exterior walls shall be protected by 
opening protectives having afire protection rating 
of not less than Ji 4 hour. 

2. Noncombustible horizontal projecting elements 
with concealed spaces, provided a minimum 
I-hour fire-resistance-rated wall extends through 
the concealed space. The projecting element shall 
be separated from the building by a minimum of 
I-hour fire-resistance-rated construction for a dis- 
tance on each side of the fire wa//equal to the depth 
of the projecting element. The wall is not required 
to extend under the projecting element where the 
building exterior wall is not less than I-hour 
fire- resistance rated for a distance on each side of 
the fire wall equal to the depth of the projecting 
element. Openings within such exterior walls shall 
be protected by opening protectives having a fire 
protection rating of not less than 3/ 4 hour. 

3. For combustible horizontal projecting elements 
with concealed spaces, the fire wall need only 
extend through the concealed space to the outer 
edges of the projecting elements. The exterior wall 
behind and below the projecting element shall be 
of not less than I-hour fire-resistance-rated con- 
struction for a distance not less than the depth of 
the projecting elements on both sides of the fire 
wall. Openings within such exterior walls shall be 
protected by opening protectives having a 
fire-protection rating of not less than 3/ 4 hour. 

706.6 Vertical continuity. Fire walls shall extend from the 
foundation to a termination point at least 30 inches (762 mm) 
above both adjacent roofs. 

Exceptions: 

1. Stepped buildings in accordance with Section 
706.6.1. 



2. Two-hour fire-resistance-rated walls shall be permit- 
ted to terminate at the underside of the roof sheathing, 
deck or slab, provided: 

2.1. The lower roof assembly within 4 feet (1220 
mm) of the wall has not less than a I-hour 
fire-resistance rating and the entire length 
and span of supporting elements for the rated 
roof assembly has a fire-resistance rating of 
not less than 1 hour. 

2.2. Openings in the roof shall not be located 
within 4 feet (1220 mm) of the fire wall. 

2.3. Each building shall be provided with not less 
than a Class B roof covering. 

3. Walls shall be permitted to terminate at the underside 
of noncombustible roof sheathing, deck or slabs 
where both buildings are provided with not less than a 
Class B roof covering. Openings in the roof shall not 
be located within 4 feet (1220 mm) of the fire wall. 

4. In buildings of Type III, IV and V construction, walls 
shall be permitted to terminate at the underside of 
combustible roof sheathing or decks, provided: 

4.1. There are no openings in the roof within 4 feet 
(1220 mm) of the fire wall, 

4.2. The roof is covered with a minimum Class B 
roof covering, and 

4.3. The roof sheathing or deck is constructed of 
fire-retardant-treated woodfor a distance of 4 
feet (1220 mm) on both sides of the wall or the 
roofis protected with 5/ s -inch (15.9 mm) Type 
X gypsum board directly beneath the under- 
side of the roof sheathing or deck, supported 
by a minimum of 2-inch (51 mm) nominal 
ledgers attached to the sides of the roof fram- 
ing members for a minimum distance of 4 feet 
(1220 mm) on both sides of the fire wall. 

5. In buildings designed in accordance with Section 
509.2, fire walls located above the 3 -hour horizontal 
assembly required by Section 509.2, Item 1 shall be 
permitted to extend from the top of this horizontal 
assembly. 

706.6.1 Stepped buildings. Where a fire wall serves as an 
exterior wall for a building and separates buildings having 
different roof levels, such wall shall terminate at a point not 
less than 30 inches (762 mm) above the lower roof level, 
provided the exterior wall fox a height of 15 feet (4572 mm) 
above the lower roof is not less than I-hour fire- resis- 
tance-rated construction from both sides with openings pro- 
tected by fire assemblies having a fire protection rating of 
not less than 31 4 hour. 

Exception: Where the fire wall terminates at the under- 
side of the roof sheathing, deck or slab of the lower roof, 
provided: 

1. The lower roof assembly within 10 feet (3048 mm) 
of the wall has not less than a I-hour fire-resis- 
tance rating and the entire length and span of sup- 



102 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



porting elements for the rated roof assembly has a 
fire- resistance rating of not less than 1 hour. 

2. Openings in the lower roof shall not be located 
within 10 feet (3048 mm) of the fire wall. 

706.7 Combustible framing in fire walls. Adjacent combusti- 
ble members entering into a concrete or masonry fire wa//from 
opposite sides shall not have less than a 4-inch (102 mm) dis- 
tance between embedded ends. Where combustible members 
frame into hollow walls or walls of hollow units, hollow spaces 
shall be solidly filled for the full thickness of the wall and for a 
distance not less than 4 inches (102 mm) above, below and 
between the structural members, with noncombustible materi- 
als approved fox fireblocking. 

706.8 Openings. Each opening through afire wall shall be pro- 
tected in accordance with Section 715.4 and shall not exceed 
156 square feet (15 m 2 ). The aggregate width of openings at 
any floor level shall not exceed 25 percent of the length of the 
wall. 

Exceptions: 

1. Openings are not permitted in party walls constructed 
in accordance with Section 706.1.1. 

2. Openings shall not be limited to 156 square feet (15 
m 2 ) where both buildings are equipped throughout 
with an automatic sprinkler system installed in accor- 
dance with Section 903.3.1.1. 

706.9 Penetrations. Penetrations of fire walls shall comply 
with Section 713. 

706.10 Joints. Joints made in or between fire walls shall com- 
ply with Section 714. 

706.11 Ducts and air transfer openings. Ducts and air trans- 
fer openings shall not penetrate fire walls. 

Exception: Penetrations by ducts and air transfer openings 
of fire walls that are not on a lot line shall be allowed pro- 
vided the penetrations comply with Section 716. The size 
and aggregate width of all openings shall not exceed the lim- 
itations of Section 706.8. 



SECTION 707 
FIRE BARRIERS 

707.1 General. Fire barriers installed as required elsewhere in 
this code or the International Fire Code shall comply with this 
section. 

707.2 Materials. Fire barriers shall be of materials permitted 
by the building type of construction. 

707.3 Fire-resistance rating. The fire-resistance rating of fire 
barriers shall comply with this section. 

707.3.1 Shaft enclosures. The fire-resistance rating of the 
fire barrier separating building areas from a shaft shall com- 
ply with Section 708.4. 

707.3.2 Exit enclosures. The fire-resistance rating of the 
fire barrier separating building areas from an exitshall com- 
ply with Section 1022.1. 



707.3.3 Exit passageway. The fire-resistance rating of the 
fire barrier separating building areas from an exit passage- 
way shall comply with Section 1023.3. 

707.3.4 Horizontal exit. The fire-resistance rating of the 
separation between building areas connected by a horizon- 
tal exit shall comply with Section 1025.1. 

707.3.5 Atriums. The fire -resistance rating of the fire bar- 
rier separating atriums shall comply with Section 404.6. 

707.3.6 Incidental accessory occupancies. The fire bar- I 
rierseparating incidental accessory occupancies from other 
spaces in the building shall have & fire-resistance rating of 
not less than that indicated in Table 508.2.5. 

707.3.7 Control areas. Fire barriers separating control 
areas shall have afire-resistance rating of not less than that 
required in Section 414.2.4. 

707.3.8 Separated occupancies. Where the provisions of 
Section 508.4 are applicable, the fire barrier separating 
mixed occupancies shall have afire-resistance rating of not 
less than that indicated in Table 508.4 based on the occupan- 
cies being separated. 

707.3.9 Fire areas. The //re barriers or horizontal assem- 
blies, or both, separating a single occupancy into different 
fire areas shall have a fire-resistance rating of not less than 
that indicated in Table 707.3.9. The fire barriers or horizon- 
tal assemblies, or both, separating fire areas of mixed occu- 
pancies shall have afire-resistance rating of not less than the 
highest value indicated in Table 707.3.9 for the occupancies 
under consideration. 



TABLE 707.3.9 

FIRE-RESISTANCE RATING REQUIREMENTS FOR FIRE 

BARRIER ASSEMBLIES OR HORIZONTAL ASSEMBLIES 

BETWEEN FIRE AREAS 



OCCUPANCY GROUP 


FIRE-RESISTANCE RATING (hours) 


H-l, H-2 


4 


F-l, H-3,5-1 


3 


A, B,E, F-2, H-4, H-5, 
I, M, R, 5-2 


2 


U 


1 



707.4 Exterior walls. Where exterior walls serve as a part of a 
required fire-resistance-rated shaft or exitenclosure, or separa- 
tion, such walls shall comply with the requirements of Section 
705 for exterior walls and the fire-resistance-rated enclosure or 
separation requirements shall not apply. 

Exception: Exterior walls required to be fire-resistance 
rated in accordance with Section 1019 for exterior egress 
balconies, Section 1022.6 for exit enclosures and Section 
1026.6 for exterior exit ramps and stairways. 

707.5 Continuity. Fire barriers shall extend from the top of the 
floor/ceiling assembly below to the underside of the floor or 
roof sheathing, slab or deck above and shall be securely 
attached thereto. Such//r£ barriers shall be continuous through 
concealed spaces, such as the space above a suspended ceiling. 



2009 INTERNATIONAL BUILDING CODE® 



103 



FIRE AND SMOKE PROTECTION FEATURES 



707.5.1 Supporting construction. The supporting con- 
struction for a fire barrier shall be protected to afford the 
required fire-resistance rating of "the fire barrier supported. 
Hollow vertical spaces within a fire barrier shall be 
fireblocked in accordance with Section 717.2 at every floor 
level. 

Exceptions: 

1. The maximum required fire -resistance rating for 
assemblies supporting fire barriers separating 
tank storage as provided for in Section 415.6.2.1 
shall be 2 hours, but not less than required by Table 
601 for the building construction type. 

2. Shaft enclosures shall be permitted to terminate at 
a top enclosure complying with Section 708.12. 

3. Supporting construction for I-hour fire barriers 
required by Table 508.2.5 in buildings of Type 
1IB, IIIB and VB construction is not required to be 
fire-resistance rated unless required by other sec- 
tions of this code. 

707.6 Openings. Openings in afire barrier shall be protected 
in accordance with Section 715. Openings shall be limited to a 
maximum aggregate width of 25 percent of the length of the 
wall, and the maximum area of any single opening shall not 
exceed 156 square feet (15 m 2 ). Openings in exit enclosures 
and exit passageways shall also comply with Sections 1022.3 
and 1023.5, respectively. 

Exceptions: 

1. Openings shall not be limited to 156 square feet (15 
m 2 ) where adjoining floor areas are equipped 
throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1. 

2. Openings shall not be limited to 156 square feet (15 
m 2 ) or an aggregate width of 25 percent of the length 
of the wall where the opening protective is afire door 
serving an exit enclosure. 

3. Openings shall not be limited to 156 square feet (15 
m 2 ) or an aggregate width of 25 percent of the length 
of the wall where the opening protective has been 
tested in accordance with ASTM E 1 19 or UL 263 and 
has a minimum fire-resistance rating not less than the 
fire-resistance rating of the wall. 

4. Fire window assemblies permitted in atrium separa- 
tion walls shall not be limited to a maximum aggre- 
gate width of 25 percent of the length of the wall. 

5. Openings shall not be limited to 156 square feet (15 
m 2 ) or an aggregate width of 25 percent of the length 
of the wall where the opening protective is afire door 
assembly in afire barrier separating an exit enclosure 
from an exit passageway in accordance with Section 
1022.2.1. 

707.7 Penetrations. Penetrations of fire barriers shall comply 
with Section 713. 

707.7.1 Prohibited penetrations. Penetrations into an exit 
enclosure or an ^xzYpassageway shall be allowed only when 
permitted by Section 1022.4 or 1023.6, respectively. 



707.8 Joints. Joints made in or between fire barriers, andjoints 
made at the intersection of fire barriers with underside of the 
floor or roof sheathing, slab or deck above, shall comply with 
Section 714. 

707.9 Ducts and air transfer openings. Penetrations in afire 
barrier by ducts and air transfer openings shall comply with 
Section 716. 



SECTION 708 
SHAFT ENCLOSURES 

708.1 General. The provisions of this section shall apply to 
shafts required to protect openings and penetrations through 
floor/ceiling and roof/ceiling assemblies. Shaft enclosures 
shall be constructed as fire barriers in accordance with Section 
707 or horizontal assemblies in accordance with Section 712, 
or both. 

708.2 Shaft enclosure required. Openings through a 
floor/ceiling assembly shall be protected by a shaft enclosure 
complying with this section. 



I 



Exceptions: 



A shaft enclosure is not required for openings totally 
within an individual residential dwelling unit and 
connecting four stories or less. 

A shaft enclosure is not required in a building 
equipped throughout with an automatic sprinkler sys- 
tem in accordance with Section 903.3.1.1 for an esca- 
lator opening or stairway that is not a portion of the 
means of egress protected according to Item 2.1 or 
2.2. 

2.1. Where the area of the floor opening between 
stories does not exceed twice the horizontal 
projected area of the escalator or stairway and 
the opening is protected by a draft curtain and 
closely spaced sprinklers in accordance with 
NFPA 13. In other than Groups Band M, this 
application is limited to openings that do not 
connect more than four stories. 

2.2. Where the opening is protected by approved 
power-operated automatic shutters at every 
penetrated floor. The shutters shall be of 
noncombustible construction and have a 
fire-resistance rating of not less than 1.5 
hours. The shutter shall be so constructed as to 
close immediately upon the actuation of a 
smoke detector installed in accordance with 
Section 907.3 and shall completely shut off 
the well opening. Escalators shall cease oper- 
ation when the shutter begins to close. The 
shutter shall operate at a speed of not more 
than 30 feet per minute (152.4 mm/s) and shall 
be equipped with a sensitive leading edge to 
arrest its progress where in contact with any 
obstacle, and to continue its progress on re- 
lease therefrom. 



104 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



3. A shaft enclosure is not required for penetrations by 
pipe, tube, conduit, wire, cable and vents protected 
in accordance with Section 713.4. 

4. A shaft enclosure is not required for penetrations by 
ducts protected in accordance with Section 716.6. 
Grease ducts shall be protected in accordance with 
the International Mechanical Code. 

5. In other than Group H occupancies, a shaft enclo- 
sure is not required for floor openings complying 
with the provisions for atriums in Section 404. 

6. A shaft enclosure is not required for approved 
masonry chimneys where annular space is 
fireblocked at each floor level in accordance with 
Section 717.2.5. 

7. In other than Groups 1-2 and 1-3, a shaft enclosure is 
not required for a floor opening or an air transfer 
opening that complies with the following: 

7.1. Does not connect more than two stories. 

7.2. Is not part of the required means of egress sys- 
tem. 

7.3. Is not concealed within the construction of a 
wall or a floor/ceiling assembly. 

7.4. Is not open to a corridorin Group I and R oc- 
cupancies. 

7.5. Is not open to a corridor on nonsprinklered 
floors in any occupancy. 

7.6. Is separated from floor openings and air trans- 
fer openings serving other floors by construc- 
tion conforming to required shaft enclosures. 

7.7. Is limited to the same smoke compartment. 

8. A shaft enclosure is not required for automobile 
ramps in open and enclosed parking garages con- 
structed in accordance with Sections 406.3 and 
406.4, respectively. 

9. A shaft enclosure is not required for floor openings 
between a mezzanine and the floor below. 

10. A shaft enclosure is not required for j oints protected 
by a fire-resistant joint system in accordance with 
Section 714. 

11. A shaft enclosure shall not be required for floor 
openings created by unenclosed stairs or ramps in 
accordance with Exception 3 or 4 in Section 1016.1. 

12. Floor openings protected by floor fire doors in 
accordance with Section 712.8. 

13. In Group 1-3 occupancies, a shaft enclosure is not 
required for floor openings in accordance with Sec- 
tion 408.5. 

14. A shaft enclosure is not required for elevator 
hoistways in open or enclosed parking garages that 
serve only the parking garage. 

15. In open or enclosed parking garages a shaft enclo- 
sure is not required to enclose mechanical exhaust or 



supply duct systems when such duct system is con- 
tained within and serves only the parking garage. 

16. Where permitted by other sections of this code. 

708.3 Materials. The shaft enclosure shall be of materials per- 
mitted by the building type of construction. 

708.4 Fire-resistance rating. Shaft enclosures shall have a 
fire-resistance rating of 'not less than 2 hours where connecting 
four stories or more, and not less than 1 hour where connecting 
less than four stories. The number of stories connected by the 
shaft enclosure shall include any basements but not any mezza- 
nines. Shaft enclosures shall have a fire-resistance rating not 
less than the floor assembly penetrated, but need not exceed 2 
hours. Shaft enclosures shall meet the requirements of Section 
703.2.1. 

708.5 Continuity. Shaft enclosures shall be constructed as fire 
barriers in accordance with Section 707 or horizontal assem- 
blies constructed in accordance with Section 712, or both, and 
shall have continuity in accordance with Section 707.5 for fire 
barriers or Section 712.4 for horizontal assemblies as applica- 
ble. 

708.6 Exterior walls. Where exterior walls serve as a part of a 
required shaft enclosure, such walls shall comply with the 
requirements of Section 705 for exterior walls and the 
fire-resistance-rated enclosure requirements shall not apply. 

Exception: Exterior walls required to be fire-resistance 
rated in accordance with Section 1019.2 for exterior egress 
balconies, Section 1022.6 for exit enclosures and Section 
1026.6 for exterior exit ramps and stairways. 

708.7 Openings. Openings in a shaft enclosure shall be pro- 
tected in accordance with Section 715 as required for fire barri- 
ers. Doors shall be self- or automatic-closing by smoke 
detection in accordance with Section 715.4.8.3. 

708.7.1 Prohibited openings. Openings other than those 
necessary for the purpose of the shaft shall not be permitted 
in shaft enclosures. 

708.8 Penetrations. Penetrations in a shaft enclosure shall be 
protected in accordance with Section 713 as required for fire 
barriers. 

708.8.1 Prohibited penetrations. Penetrations other than 
those necessary for the purpose of the shaft shall not be per- 
mitted in shaft enclosures. 

708.9 Joints. Joints in a shaft enclosure shall comply with Sec- 
tion 714. 

708.10 Ducts and air transfer openings. Penetrations of a 
shaft enclosure by ducts and air transfer openings shall comply 
with Section 716. 

708.11 Enclosure at the bottom. Shafts that do not extend to 
the bottom of the building or structure shall comply with one of 
the following: 

1. They shall be enclosed at the lowest level with construc- 
tion of the same fire-resistance ratings the lowest floor 
through which the shaft passes, but not less than the rat- 
ing required for the shaft enclosure. 



2009 INTERNATIONAL BUILDING CODE® 



105 



FIRE AND SMOKE PROTECTION FEATURES 



2. They shall terminate in a room having a use related to the 
purpose of the shaft. The room shall be separated from 
the remainder of the building by fire barriers constructed 
in accordance with Section 707 or horizontal assemblies 
constructed in accordance with Section 712, or both. The 
fire-resistance rating and opening protectives shall be at 
least equal to the protection required for the shaft enclo- 
sure. 

3. They shall be protected by approved fire dampers 
installed in accordance with their listing at the lowest 
floor level within the shaft enclosure. 

Exceptions: 

1. The fire-resistance-rated room separation is not 
required, provided there are no openings in or pen- 
etrations of the shaft enclosure to the interior of the 
building except at the bottom. The bottom of the 
shaft shall be closed off around the penetrating 
items with materials permitted by Section 717.3.1 
for draftstopping, or the room shall be provided 
with an approved automatic fire suppression sys- 
tem. 

2. A shaft enclosure containing a refuse chute or 
laundry chute shall not be used for any other pur- 
pose and shall terminate in a room protected in 
accordance with Section 708.13.4. 

3. The fire-resistance-rated room separation and the 
protection at the bottom of the shaft are not 
required provided there are no combustibles in the 
shaft and there are no openings or other penetra- 
tions through the shaft enclosure to the interior of 
the building. 

708.12 Enclosure at the top. A shaft enclosure that does not 
extend to the underside of the roof sheathing, deck or slab of the 
building shall be enclosed at the top with construction of the 
same fire-resistance rating as the topmost floor penetrated by 
the shaft, but not less than the fire -resistance rating required for 
the shaft enclosure. 

708.13 Refuse and laundry chutes. Refuse and laundry 
chutes, access and termination rooms and incinerator rooms 
shall meet the requirements of Sections 708.13.1 through 
708.13.6. 

Exception: Chutes serving and contained within a single 
dwelling unit. 

708.13.1 Refuse and laundry chute enclosures. A shaft 
enclosure containing a refuse or laundry chute shall not be 
used for any other purpose and shall be enclosed in accor- 
dance with Section 708.4. Openings into the shaft, includ- 
ing those from access rooms and termination rooms, shall 
be protected in accordance with this section and Section 
715. Openings into chutes shall not be located in corridors. 
Doors shall be self- or automatic-closing upon the actuation 
of a smoke detector in accordance with Section 715.4.8.3, 
except that heat-activated closing devices shall be permitted 
between the shaft and the termination room. 



708.13.2 Materials. A shaft enclosure containing a refuse 
or laundry chute shall be constructed of materials as permit- 
ted by the building type of construction. 

708.13.3 Refuse and laundry chute access rooms. Access 
openings for refuse and laundry chutes shall be located in 
rooms or compartments enclosed by not less than I-hour 
fire barriers constructed in accordance with Section 707 or 
horizontal assemblies constructed in accordance with Sec- 
tion 712, or both. Openings into the access rooms shall be 
protected by opening protectives having a fire protection 
rating of not less than 3/4 hour. Doors shall be self- or auto- 
matic-closing upon the detection of smoke in accordance 
with Section 715.4.8.3. 

708.13.4 Termination room. Refuse and laundry chutes 
shall discharge into an enclosed room separated from the 
remainder of the building by not less than I-hour fire barri- 
ers constructed in accordance with Section 707 or horizon- 
tal assemblies constructed in accordance with Section 712, 
or both. Openings into the termination room shall be pro- 
tected by opening protectives having afire protection rating 
of not less than 3/4 hour. Doors shall be self- or auto- 
matic-closing upon the detection of smoke in accordance 
with Section 715.4.8.3. Refuse chutes shall not terminate in 
an incinerator room. Refuse and laundry rooms that are not 
provided with chutes need only comply with Table 508.2.5. 

708.13.5 Incinerator room. Incinerator rooms shall com- 
ply with Table 508.2.5. 

708.13.6 Automatic sprinkler system. An approved auto- 
matic sprinkler system shall be installed in accordance with 
Section 903.2.11.2. 

708.14 Elevator, dumbwaiter and other hoistways. Elevator, 
dumbwaiter and other hoistway enclosures shall be con- 
structed in accordance with Section 708 and Chapter 30. 

708.14.1 Elevator lobby. An enclosed elevator lobby shall 
be provided at each floor where an elevator shaft enclosure 
connects more than three stories. The lobby enclosure shall 
separate the elevator shaft enclosure doors from each floor 
by fire partitions. In addition to the requirements in Section 
709 fox fire partitions, doors protecting openings in the ele- 
vator lobby enclosure walls shall also comply with Section 
715.4.3 as required for corridor walls and penetrations of 
the elevator lobby enclosure by ducts and air transfer open- 
ings shall be protected as required for corridors in accor- 
dance with Section 716.5.4. 1. Elevator lobbies shall have at 
least one means of egress complying with Chapter 10 and 
other provisions within this code. 

Exceptions: 

1. Enclosed elevator lobbies are not required at the 
street floor, provided the entire street floor is 
equipped with an automatic sprinkler system in 
accordance with Section 903.3.1.1. 

2. Elevators not required to be located in a shaft in 
accordance with Section 708.2 are not required to 
have enclosed elevator lobbies. 

3. Enclosed elevator lobbies are not required where 
additional doors are provided at the hoistway 



106 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



opening in accordance with Section 3002.6. Such 
doors shall be tested in accordance with UL 1784 
without an artificial bottom seal. 

4. Enclosed elevator lobbies are not required where 
the building is protected by an automatic sprinkler 
system installed in accordance with Section 
903.3.1.1 or 903.3.1.2. This exception shall not 
apply to the following : 

4.1. Group 1-2 occupancies; 

4.2. Group 1-3 occupancies; and 

4.3. High-rise buildings. 

5. Smoke partitions shall be permitted in lieu of fire 
partitions to separate the elevator lobby at each 
floor where the building is equipped throughout 
with an automatic sprinkler system installed in 
accordance with Section 903 .3.1.1 or 903.3.1 .2. In 
addition to the requirements in Section 711 for 
smoke partitions, doors protecting openings in the 
smoke partitions shall also comply with Sections 
711.5.2, 711.5.3, and 715.4.8 and duct penetra- 
tions of the smoke partitions shall be protected as 
required for corridors in accordance with Section 
716.5.4.1. 

6. Enclosed elevator lobbies are not required where 
the elevator hoistway is pressurized in accordance 
with Section 708.14.2. 

7. Enclosed elevator lobbies are not required where 
the elevator serves only open parking garages in 
accordance with Section 406.3. 

708.14.1.1 Areas of refuge. Areas of refuge shall be pro- 
vided as required in Section 1007. 

708.14.2 Enclosed elevator lobby. Where elevator hoist- 
way pressurization is provided in lieu of required enclosed 
elevator lobbies, the pressurization system shall comply 
with this section. 

708.14.2.1 Pressurization requirements. Elevator 
hoistways shall be pressurized to maintain a minimum 
positive pressure of 0.10 inches of water (25 Pa) and a 
maximum positive pressure of 0.25 inches of water (67 
Pa) with respect to adjacent occupied space on all floors. 
This pressure shall be measured at the midpoint of each 
hoistway door, with all elevator cars at the floor of recall 
and all hoistway doors on the floor of recall open and all 
other hoistway doors closed. The opening and closing of 
hoistway doors at each level must be demonstrated dur- 
ing this test. The supply air intake shall be from an out- 
side, uncontaminated source located a minimum 
distance of 20 feet (6096 mm) from any air exhaust sys- 
tem or outlet. 

708.14.2.2 Rational analysis. A rational analysis com- 
plying with Section 909.4 shall be submitted with the 
construction documents. 

708.14.2.3 Ducts for system. Any duct system that is 
part of the pressurization system shall be protected with 
the same fire-resistance rating as required for the eleva- 
tor shaft enclosure. 



708.14.2.4 Fan system. The fan system provided for the 
pressurization system shall be as required by this section. 

708.14.2.4.1 Fire resistance. When located within 
the building, the fan system that provides the pressur- 
ization shall be protected with the same fire-resis- 
tance ra^mg required for the elevator shaft enclosure. 

708.14.2.4.2 Smoke detection. The fan system shall 
be equipped with a smoke detector that will automati- 
cally shut down the fan system when smoke is 
detected within the system. 

708.14.2.4.3 Separate systems. A separate fan sys- 
tem shall be used for each elevator hoistway. 

708.14.2.4.4 Fan capacity. The supply fan shall 
either be adjustable with a capacity of at least 1,000 
cfm (.4719 m 3 /s) per door, or that specified by a regis- 
tered design professionals meet the requirements of 
a designed pressurization system. 

708.14.2.5 Standby power. The pressurization system 
shall be provided with standby power from the same 
source as other required emergency systems for the 
building. 

708.14.2.6 Activation of pressurization system. The 
elevator pressurization system shall be activated upon 
activation of the building fire alarm system or upon acti- 
vation of the elevator lobby smoke detectors . Where both 
a building fire alarm system and elevator lobby smoke 
detectors are present, each shall be independently capa- 
ble of activating the pressurization system. 

708.14.2.7 Special inspection. Special inspection for 
performance shall be required in accordance with Sec- 
tion 909.18.8. System acceptance shall be in accordance 
with Section 909.19. 

708.14.2.8 Marking and identification. Detection and 
control systems shall be marked in accordance with Sec- 
tion 909.14. 

708.14.2.9 Control diagrams. Control diagrams shall 
be provided in accordance with Section 909.15. 

708.14.2.10 Control panel. A control panel complying 
with Section 909 . 16 shall be provided. 

708.14.2.11 System response time. Hoistway pressur- 
ization systems shall comply with the requirements for 
smoke control system response time in Section 909.1 7. 



SECTION 709 
FIRE PARTITIONS 

709.1 General. The following wall assemblies shall comply 
with this section. 

1. Walls separating dwelling units in the same building as 
required by Section 420.2. 

2. Walls separating sleeping units in the same building as 
required by Section 420.2. 

3. Walls separating tenant spaces in coveredmall buildings 
as required by Section 402.7.2. 



2009 INTERNATIONAL BUILDING CODE® 



107 



FIRE AND SMOKE PROTECTION FEATURES 



I 



4. Corridor walls as required by Section 1018.1. 

5. Elevator lobby separation as required by Section 
708.14.1. 

709.2 Materials. The walls shall be of materials permitted by 
the building type of construction. 

709.3 Fire-resistance rating. Fire partitions shall have a 
fire-resistance rating of not less than 1 hour. 

Exceptions: 

1. Corridor walls permitted to have a i/ 2 hour fire-resis- 
tance rating by Table 1018.1. 

2. Dwelling unit and sleeping unit separations in build- 
ings of Type 1IB, IIIB and VB construction shall have 
fire-resistance ratings of not less than i/ 2 hour in 
buildings equipped throughout with an automatic 
sprinkler system in accordance with Section 
903.3.1.1. 

709.4 Continuity. Fire partitions shall extend from the top of 
the foundation or floor/ceiling assembly below to the under- 
side of the floor or roof sheathing, slab or deck above or to the 
fire-resistance-rated floor/ceiling or roof/ceiling assembly 
above, and shall be securely attached thereto. If the partitions 
are not continuous to the sheathing, deck or slab, and where 
constructed of combustible construction, the space between the 
ceiling and the sheathing, deck or slab above shall be 
fireblocked or draftstopped in accordance with Sections 717.2 
and 717.3 at the partition line. The supporting construction 
shall be protected to afford the required fire-resistance rating 
of the wall supported, except for walls separating tenant spaces 
in covered mall buildings, walls separating dwelling units, 
walls separating sleeping units and corridor walls in buildings 
of Type 1IB, IIIB and VB construction. 

Exceptions: 

1. The wall need not be extended into the crawl space 
below where the floor above the crawl space has a 
minimum I-hour fire -resistance rating. 

2. Where the room-side fire-resistance-rated membrane 
of the corridor is carried through to the underside of 
the floor or roof sheathing, deck or slab of a fire-resis- 
tance-rated floor or roof above, the ceiling of the cor- 
ridor shall be permitted to be protected by the use of 
ceiling materials as required for a I-hour fire-resis- 
tance-rated floor or roof system. 

3. Where the corri dor ceiling is constructed as required 
for the corridorwalls, the walls shall be permitted to 
terminate at the upper membrane of such ceiling 
assembly. 

4. The fire partitions separating tenant spaces in a cov- 
ered mall bUilding, complying with Section 402.7.2, 
are not required to extend beyond the underside of a 
ceiling that is not part of a fire-resistance-rated assem- 
bly. A wall is not required in attic or ceiling spaces 
above tenant separation walls . 

5. Fireblocking or draftstopping is not required at the 
partition line in Group R-2 buildings that do not 



exceed four stories above grade plane, provided the 
attic space is subdivided by draftstopping into areas 
not exceeding 3,000 square feet (279 m 2 ) or above 
every two dwelling units, whichever is smaller. 

6. Fireblocking or draftstopping is not required at the 
partition line in buildings equipped with an automatic 
sprinkler system installed throughout in accordance 
with Section 903.3.1.1 or 903.3.1.2, provided that 
automatic sprinklers are installed in combustible 
floor/ceiling and roof/ceiling spaces. 

709.5 Exterior walls. Where exterior walls serve as a part of a 
required fire-resistance-rated separation, such walls shall com- 
ply with the requirements of Section 705 for exterior walls, and 
the fire-resistance-rated separation requirements shall not 
apply. 

Exception: Exterior walls required to be fire-resistance 
rated in accordance with Section 1019.2 for exterior egress 
balconies, Section 1022.6 for exit enclosures and Section 
1026.6 for exterior £;nYramps and stairways. 

709.6 Openings. Openings in afire partition shall be protected 
in accordance with Section 715. 

709.7 Penetrations. Penetrations of fire partitions shall com- 
ply with Section 713. 

709.8 Joints. Joints made in or between fire partitions shall 
comply with Section 714. 

709.9 Ducts and air transfer openings. Penetrations in afire 
partition by ducts and air transfer openings shall comply with 
Section 716. 



SECTION 710 
SMOKE BARRIERS 

710.1 General. Smoke barriers shall comply with this section. 

710.2 Materials. Smoke barriers shall be of materials permit- 
ted by the building type of construction. 

710.3 Fire-resistance rating. A I-hour fire -resistance rating 
is required for smoke barriers. 

Exception: Smoke barriers constructed of minimum 
0.10-inch-thick (2.5 mm) steel in Group 1-3 buildings. 

710.4 Continuity. Smoke barriers shall form an effective 
membrane continuous from outside wall to outside wall and 
from the top of the foundation or floor/ceiling assembly below 
to the underside of the floor or roof sheathing, deck or slab 
above, including continuity through concealed spaces, such as 
those found above suspended ceilings, and interstitial struc- 
tural and mechanical spaces. The supporting construction shall 
be protected to afford the required fire -resistance rating of the 
wall or floor supported in buildings of other than Type 1IB, IIIB 
or VB construction. 

Exception: Smoke-barrier walls are not required in intersti- 
tial spaces where such spaces are designed and constructed 
with ceilings that provide resistance to the passage of fire 
and smoke equivalent to that provided by the smoke-barrier 
walls. 



108 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



710.5 Openings. Openings in a smoke barrier shall be pro- 
tected in accordance with Section 715. 

Exceptions: 

1. In Group 1-2, where doors are installed across corri- 
dors, a pair of opposite-swinging doors without a cen- 
ter mullion shall be installed having vision panels 
with fire-protection-rated glazing materials in 
fire-protection-rated frames, the area of which shall 
not exceed that tested. The doors shall be close fitting 
within operational tolerances, and shall not have 
undercuts in excess of 3/ 4 -inch, louvers or grilles. The 
doors shall have head and jamb stops, astragals or 
rabbets at meeting edges and shall be automatic-clos- 
ing by smoke detection in accordance with Section 
715.4.8.3. Where permitted by the door manufac- 
turer's listing, positive-latching devices are not 
required. 

2. In Group 1-2, horizontal sliding doors installed in 
accordance with Section 1008.1.4.3 and protected in 
accordance with Section 715. 

710.6 Penetrations. Penetrations of smoke barriers shall com- 
ply with Section 713. 

710.7 Joints. Joints made in or between smoke barriers shall 
comply with Section 714. 

710.8 Ducts and air transfer openings. Penetrations in a 
smoke barrierby ducts and air transfer openings shall comply 
with Section 716. 



SECTION 711 
SMOKE PARTITIONS 

711.1 General. Smoke partitions installed as required else- 
where in the code shall comply with this section. 

711.2 Materials. The walls shall be of materials permitted by 
the building type of construction. 

71 1.3 Fire-resistance rating. Unless required elsewhere in the 
code, smoke partitions are not required to have a fire -resistance 
rating. 

Ill A Continuity. Smoke partitions shall extend from the top 
of the foundation or floor below to the underside of the floor or 
roof sheathing, deck or slab above or to the underside of the 
ceiling above where the ceiling membrane is constructed to 
limit the transfer of smoke. 

711.5 Openings. Windows shall be sealed to resist the free pas- 
sage of smoke or be automatic-closing upon detection of smoke. 
Doors in smoke partitions shall comply with this section. 

711.5.1 Louvers. Doors in smoke partitions shall not 
include louvers. 

711.5.2 Smoke and draft control doors. Where required 
elsewhere in the code, doors in smoke partitions shall meet 
the requirements for a smoke and draft control door assem- 
bly tested in accordance with UL 1784. The air leakage rate 
of the door assembly shall not exceed 3.0 cubic feet per min- 
ute per square foot (0.015424 m 3 / (s . m 2 )) of door opening at 
0.10 inch (24.9 Pa) of water for both the ambient tempera- 



ture test and the elevated temperature exposure test. 
Installation of smoke doors shall be in accordance with 
NFPA 105. 

711.5.3 Self- or automatic-closing doors. Where required 
elsewhere in the code, doors in smoke partitions shall be 
self- or automatic-closing by smoke detection in accordance 
with Section 715.4.8.3. 

711.6 Penetrations andjoints. The space around penetrating 
items and in joints shall be filled with an approve d material to 
limit the free passage of smoke. 

711.7 Ducts and air transfer openings. The space around a 
duct penetrating a smoke partition shall be filled with an 
approved material to limit the free passage of smoke. Air trans- 
fer openings in smoke partitions shall be provided with a smoke 
damper complying with Section 716.3.2.2. 

Exception: Where the installation of a smoke damper will 
interfere with the operation of a required smoke control sys- 
tem in accordance with Section 909, approved alternative 
protection shall be utilized. 



SECTION 712 
HORIZONTAL ASSEMBLIES 

712.1 General. Floor and roof assemblies required to have a 
fire-resistance rating shall comply with this section. 
Nonfire-resistance-rated floor and roof assemblies shall com- 
ply with Section 713.4.2. 

712.2 Materials. The floor and roof assemblies shall be of 
materials permitted by the building type of construction. 

712.3 Fire-resistance rating. The fire-resistance rating of 
floor and roof assemblies shall not be less than that required by 
the building type of construction. Where the floor assembly 
separates mixed occupancies, the assembly shall have a 
fire-resistance rating of not less than that required by Section 

508.4 based on the occupancies being separated. Where the 
floor assembly separates a single occupancy into different fire 
areas, the assembly shall have a fire-resistance rating of not 
less than that required by Section 707.3.9. Horizontal assem- 
blies separating dwelling units in the same building and hori- 
zontal assemblies separating sleeping units in the same 
building shall be a minimum of I-hour fire-resistance-rated 
construction. 

Exception: Dwelling unit Mid sleeping unit separations in 
buildings of Type 1IB, IIIB and VB construction shall have 
fire-resistance ratings of not less than i/ 2 hour in buildings 
equipped throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1. 

712.3.1 Ceiling panels. Where the weight of lay-in ceiling 
panels, used as part of fire-resistance-rated floor/ceiling or 
roof/ceiling assemblies, is not adequate to resist an upward 
force of 1 pound per square foot (48 Pa), wire or other 
approved devices shall be installed above the panels to pre- 
vent vertical displacement under such upward force. 

712.3.2 Access doors. Access doors shall be permitted in 
ceilings of fire-resistance-rated floor/ceiling and roof/ceil- 
ing assemblies provided such doors are tested in accordance 



i 



2009 INTERNATIONAL BUILDING CODE® 



109 



FIRE AND SMOKE PROTECTION FEATURES 



with ASTM E 119 or UL 263 as horizontal assemblies and 
labeled by an approved agency for such purpose. 

712.3.3 Unusable space. In I-hour fire-resistance-rated 
floor assemblies, the ceiling membrane is not required to be 
installed over unusable crawl spaces. In I-hour fire-resis- 
tance-rated roof assemblies, the floor membrane is not 
required to be installed where unusable attic space occurs 
above. 

712.4 Continuity. Assemblies shall be continuous without 
openings, penetrations orjoints except as permitted by this sec- 
tion and Sections 708.2,713.4,714 and 1022.1. Skylights and 
other penetrations through a fire-resistance-rated roof deck or 
slab are permitted to be unprotected, provided that the struc- 
tural integrity of the fire-resistance-rated roof assembly is 
maintained. Unprotected skylights shall not be permitted in 
roof assemblies required to be fire-resistance rated in accor- 
dance with Section 704.10. The supporting construction shall 
be protected to afford the required fire -resistance rating of the 
horizontal assembly supported. 

Exception: In buildings of Type 1IB, IIIB or VB construc- 
tion, the construction supporting the horizontal assembly is 
not required to be fire-resistance-rated at the following: 

1. Horizontal assemblies at the separations of incidental 
uses as specified by Table 508.2.5, provided the 
required fire-resistance rating does not exceed 1 
hour. 

2. Horizontal assemblies at the separations of dwelling 
units and sleeping units as required by Section 420.3. 

3. Horizontal assemblies at smoke barriers constructed 
in accordance with Section 710. 

712.5 Penetrations. Penetrations of horizontal assemblies 
shall comply with Section 713. 

712.6 Joints. Joints made in or between horizontal assemblies 
shall comply with Section 714. The void created at the intersec- 
tion of a floor/ceiling assembly and an exterior curtain wall 
assembly shall be protected in accordance with Section 714.4. 

712.7 Ducts and air transfer openings. Penetrations in hori- 
zontal assemblies^ ducts and air transfer openings shall com- 
ply with Section 716. 

712.8 Floor fire door assemblies. Floor fire door assemblies 
used to protect openings in fire-resistance-rated floors shall be 
tested in accordance with NFPA 288, and shall achieve a 
fire -resistance rating not less than the assembly being pene- 
trated. Floor fire door assemblies shall be labeled by an 
approved agency. The label shall be permanently affixed and 
shall specify the manufacturer, the test standard and the 
fire-resistance rating. 

112.9 Smoke barrier. Where horizontal assemblies are 
required to resist the movement of smoke by other sections of 
this code in accordance with the definition of smoke barrier, 
penetrations and joints in such horizontal assemblies shall be 
protected as required for smoke barriers in accordance with 
Sections 713.5 and 714.6. Regardless of the number of stories 
connected by elevator shaft enclosures, doors located in eleva- 
tor shaft enclosures that penetrate the horizontal assembly shall 
be protected by enclosed elevator lobbies complying with Sec- 



tion 708.14.1. Openings through horizontal assemblies shall 
be protected by shaft enclosures complying with Section 708. 
Horizontal assemblies shall not be allowed to have unprotected 
vertical openings. 



SECTION 713 
PENETRATIONS 

713.1 Scope. The provisions of this section shall govern the 
materials and methods of construction used to protect through 
penetrations and membrane penetrations of horizontal assem- 
blies and fire-resistance-rated wall assemblies. 

713.1.1 Ducts and air transfer openings. Penetrations of 
fire-resistance-rated walls by ducts that are not protected 
with dampers shall comply with Sections 713.2 through 
713.3.3. Penetrations of horizontal assemblies not pro- 
tected with a shaft as permitted by Exception 4 of Section 
708.2, and not required to be protected with fire dampers by 
other sections of this code, shall comply with Sections 713.4 
through 713 .4. 2.2. Ducts and air transfer openings that are 
protected with dampers shall comply with Section 716. 

713.2 Installation details. Where sleeves are used, they shall 
be securely fastened to the assembly penetrated. The space 
between the item contained in the sleeve and the sleeve itself 
and any space between the sleeve and the assembly penetrated 
shall be protected in accordance with this section. Insulation 
and coverings on or in the penetrating item shall not penetrate 
the assembly unless the specific material used has been tested 
as part of the assembly in accordance with this section. 

713.3 Fire-resistance-rated walls. Penetrations into or 
through fire walls, fire barriers, smoke barrier walls and fire 
partitions shall comply with Sections 713 .3 . 1 through 713 .3.3. 
Penetrations in smoke barrier walls shall also comply with 
Section 713.5. 

713.3.1 Through penetrations. Through penetrations of 
fire-resistance-rated walls shall comply with Section 
713.3.1.1 or 713.3.1.2. 

Exception: Where the penetrating items are steel, fer- 
rous or copper pipes, tubes or conduits, the annular 
space between the penetrating item and the fire- resis- 
tance-rated wall is permitted to be protected as follows: 

1. In concrete or masonry walls where the penetrat- 
ing item is a maximum 6-inch (152 mm) nominal 
diameter and the area of the opening through the 
wall does not exceed 144 square inches (0.0929 
m 2 ) , concrete, grout or mortar is permitted where it 
is installed the full thickness of the wall or the 
thickness required to maintain the fire-resistance 
rating, or 

2. The material used to fill the annular space shall 
prevent the passage of flame and hot gases suffi- 
cient to ignite cotton waste when subjected to 
ASTM E 119 or UL 263 time-temperature fire 
conditions under a minimum positive pressure dif- 
ferential of 0.01 inch (2.49 Pa) of water at the loca- 
tion of the penetration for the time period 



i 



110 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



equivalent to the fire -resistance rating of the con- 
struction penetrated. 

713.3.1.1 Fire-resistance-rated assemblies. Penetra- 
tions shall be installed as tested in an approvedfire-resis- 
tance-rated assembly. 

713.3.1.2 Through-penetration firestop system. 
Through penetrations shall be protected by an approved 
penetration firestop system installed as tested in accor- 
dance with ASTM E 814 or UL 1479, with a minimum 
positive pressure differential of 0.01 inch (2.49 Pa) of 
water and shall have an F rating of not less than the 
required fire-resistance rating of the wall penetrated. 

713.3.2 Membrane penetrations. Membrane penetrations 
shall comply with Section 713.3.1. Where walls or parti- 
tions are required to have a fire -resistance rating, recessed 
fixtures shall be installed such that the required fire-resis- 
tance will not be reduced. 

Exceptions: 

1. Membrane penetrations of maximum 2-hour 
fire-resistance-rated walls and partitions by steel 
electrical boxes that do not exceed 16 square 
inches (0.0103 m 2 ) in area, provided the aggregate 
area of the openings through the membrane does 
not exceed 100 square inches (0.0645 m 2 ) in any 
100 square feet (9.29 m 2 ) of wall area. The annular 
space between the wall membrane and the box 
shall not exceed i/ s inch (3.1 mm). Such boxes on 
opposite sides of the wall or partition shall be sepa- 
rated by one of the following: 

1.1. By a horizontal distance of not less than 24 
inches (610 mm) where the wall or parti- 
tion is constructed with individual 
noncommunicating stud cavities; 

1.2. By a horizontal distance of not less than the 
depth of the wall cavity where the wall cav- 
ity is filled with cellulose loose-fill, 
rockwool or slag mineral wool insulation; 

1.3. By solid fireblocking in accordance with 
Section 717.2.1; 

1.4. By protecting both outlet boxes with listed 
putty pads; or 

1.5. By other liste d materials and methods. 

2. Membrane penetrations by listed electrical boxes 
of any material, provided such boxes have been 
tested for use in fire-resistance-rated assemblies 
and are installed in accordance with the instruc- 
tions included in the listing. The annular space 
between the wall membrane and the box shall not 
exceed i/ s inch (3.1 mm) unless listed otherwise. 
Such boxes on opposite sides of the wall or parti- 
tion shall be separated by one of the following: 

2.1. By the horizontal distance specified in the 
listing of the electrical boxes; 

2.2. By solid fireblocking in accordance with 
Section 717.2.1; 



2.3. By protecting both boxes with listed putty 
pads; or 

2.4. By other liste d materials and methods. 

3. Membrane penetrations by electrical boxes of any 
size or type, which have been listed as part of a 
wall opening protective material system for use in 
fire-resistance-rated assemblies and are installed 
in accordance with the instructions included in the 
listing. 

4. Membrane penetrations by boxes other than elec- 
trical boxes, provided such penetrating items and 
the annular space between the wall membrane and 
the box, are protected by an approved membrane 
penetration firestop system installed as tested in 
accordance with ASTM E 814 or UL 1479, with a 
minimum positive pressure differential of 0.01 
inch (2.49 Pa) of water, and shall have an F and T 
rating of not less than the required fire -resistance 
rating of the wall penetrated and be installed in 
accordance with their listing. 

5. The annular space created by the penetration of an 
automatic sprinkler, provided it is covered by a 
metal escutcheon plate. 

713.3.3 Dissimilar materials. Noncombustible penetrating 
items shall not connect to combustible items beyond the 
point of firestopping unless it can be demonstrated that the 
fire-resistance integrity of the wall is maintained. 

713.4 Horizontal assemblies. Penetrations of a floor, 
floor/ceiling assembly or the ceiling membrane of a roof/ceil- 
ing assembly not required to be enclosed in a shaft by Section 
708.2 shall be protected in accordance with Sections 713.4.1 
through 713.4.2.2. 

713.4.1 Fire-resistance-rated assemblies. Penetrations of 
the fire-resistance-rated floor, floor/ceiling assembly or the 
ceiling membrane of a roof/ceiling assembly shall comply 
with Sections 713.4.1.1 through 713.4.1.4. Penetrations in 
horizontal smoke barriers shall also comply with 713.5. 

713.4.1.1 Through penetrations. Through penetrations 
of fire-resistance-rated horizontal assemblies shall com- 
ply with Section 713.4.1.1.1 or 713.4.1.1.2. 

Exceptions: 

1. Penetrations by steel, ferrous or copper con- 
duits, pipes, tubes or vents or concrete or 
masonry items through a single fire- resistance- 
rated floor assembly where the annular space is 
protected with materials that prevent the pas- 
sage of flame and hot gases sufficient to ignite 
cotton waste when subjected to ASTM E 1 19 or 
UL 263 time-temperature fire conditions under 
a minimum positive pressure differential of 
0.01 inch (2.49 Pa) of water at the location of 
the penetration for the time period equivalent to 
the fire-resistance rating of the construction 
penetrated. Penetrating items with a maximum 
6-inch (152 mm) nominal diameter shall not be 
limited to the penetration of a single fire-resis- 



2009 INTERNATIONAL BUILDING CODE® 



111 



FIRE AND SMOKE PROTECTION FEATURES 



I 



tance-rated floor assembly, provided the aggre- 
gate area of the openings through the assembly 
does not exceed 144 square inches (92 900 
mm 2 ) in any 100 square feet (9.3 m 2 ) of floor 
area. 

2. Penetrations in a single concrete floor by steel, 
ferrous or copper conduits, pipes, tubes or vents 
with a maximum 6-inch (152 mm) nominal 
diameter, provided the concrete, grout or mor- 
tar is installed the full thickness of the floor or 
the thickness required to maintain the 
fire-resistance rating. The penetrating items 
shall not be limited to the penetration of a single 
concrete floor, provided the area of the opening 
through each floor does not exceed 144 square 
inches (92 900 mm2). 

3. Penetrations by listed electrical boxes of any 
material, provided such boxes have been tested 
for use in fire-resistance-rated assemblies and 
installed in accordance with the instructions 
included in the listing. 

713.4.1.1.1 Installation. Through penetrations shall 
be installed as tested in the approved fire-resis- 
tance-rated assembly. 

113 AAA. 2 Through-penetration firestop system. 
Through penetrations shall be protected by an 
approved through-penetration [irestop system 
installed and tested in accordance with ASTM E 814 
or UL 1479, with a minimum positive pressure differ- 
ential of 0.01 inch of water (2.49 Pa). The system shall 
have an F rating/T rating of not less than 1 hour but not 
less than the required rating of the floor penetrated. 

Exception: Floor penetrations contained and 
located within the cavity of a wall above the floor 
or below the floor do not require a T rating . 

713.4.1.2 Membrane penetrations. Penetrations of 
membranes that are part of a horizontal assembly shall 
comply with Section 713.4.1.1.1 or 713.4.1.1.2. Where 
floor/ceiling assemblies are required to have a fire -resis- 
tance rating, recessed fixtures shall be installed such that 
the required fire resistance will not be reduced. 

Exceptions: 

1. Membrane penetrations by steel, ferrous or 
copper conduits, pipes, tubes or vents, or con- 
crete or masonry items where the annular space 
is protected either in accordance with Section 
713.4.1.1 or to prevent the free passage of 
flame and the products of combustion. The 
aggregate area of the openings through the 
membrane shall not exceed 100 square inches 
(64 500 mm 2 ) in any 100 square feet (9.3 m 2 ) of 
ceiling area in assemblies tested without pene- 
trations . 

2. Ceiling membrane penetrations of maximum 
2-hour horizontal assemblies by steel electrical 



boxes that do not exceed 16 square inches (10 
323 mm 2 ) in area, provided the aggregate area 
of such penetrations does not exceed 100 
square inches (44 500 mm 2 ) in any 100 square 
feet (9.29 m 2 ) of ceiling area, and the annular 
space between the ceiling membrane and the 
box does not exceed i/ 8 inch (3.2 mm). 

3. Membrane penetrations by electrical boxes of 
any size or type, which have been listed as part 
of an opening protective material system for 
use in horizontal assemblies and are installed in 
accordance with the instructions included in the 
listing. 

4. Membrane penetrations by listed electrical 
boxes of any material, provided such boxes 
have been tested for use in fire-resistance-rated 
assemblies and are installed in accordance with 
the instructions included in the listing. The 
annular space between the ceiling membrane 
and the box shall not exceed i/ 8 inch (3.2 mm) 
unless listed otherwise. 

5. The annular space created by the penetration of 
a fire sprinkler, provided it is covered by a 
metal eschutcheon plate. 

713.4.1.3 Ducts and air transfer openings. Penetra- 
tions of horizontal assemblies by ducts and air transfer 
openings shall comply with Section 716. 

713.4.1.4 Dissimilar materials. Noncombustible pene- 
trating items shall not connect to combustible materials 
beyond the point offirestopping unless it can be demon- 
strated that the fire-resistance integrity of the horizontal 
assembly is maintained. 

713.4.2 Nonfire-resistance-rated assemblies. Penetra- 
tions of nonfire-resistance-rated floor or floor/ceiling 
assemblies or the ceiling membrane of a nonfire-resistance- 
rated roof/ceiling assembly shall meet the requirements of 
Section 708 or shall comply with Section 713.4.2.1 or 
713.4.2.2. 

713.4.2.1 Noncombustible penetrating items. 
Noncombustible penetrating items that connect not more 
than three stories are permitted, provided that the annu- 
lar space is filled to resist the free passage of flame and 
the products of combustion with an approved 
noncombustible material or with a fill, void or cavity 
material that is tested and classified for use in 
through-penetration firestop systems. 

713.4.2.2 Penetrating items. Penetrating items that con- 
nect not more than two stories are permitted, provided 
that the annular space is filled with an approv edmaterial 
to resist the free passage of flame and the products of 
combustion. 

713.5 Penetrations in smoke barriers. Penetrations in smoke 
barriers shall be tested in accordance with the requirements of 
UL 1479 for air leakage. The air leakage rate of the penetration 
assemblies measured at 0.30 inch (7.47 Pa) of water in both the 



112 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



ambient temperature and elevated temperature tests, shall not 
exceed: 

1. 5.0 cfm per square foot (0.025m 3 / s . m 2 ) of penetration 
opening for each through-penetration firestop system; or 

2. A total cumulative leakage of 50 cfm (0.024m 3 /s) for any 
100 square feet (9.3 m 2 ) of wall area, or floor area. 



SECTION 714 
FIRE-RESISTANT JOINT SYSTEMS 

714.1 General. Joints installed in or between fire-resis- 
tance-rated walls, floor or floor/ceiling assemblies and roofs or 
roof/ceiling assemblies shall be protected by an approved 
fire-resistant) oint system designed to resist the passage of fire 
for a time period not less than the required fire-resistance rat- 
in gof the wall, floor or roof in or between which it is installed. 
Fire-resistant] oint systems shall be tested in accordance with 
Section 714.3. The void created at the intersection of a 
floor/ceiling assembly and an exterior curtain wall assembly 
shall be protected in accordance with Section 714.4. 

Exception: Fire-resistant) oint systems shall not be required 
for joints in all of the following locations: 

1. Floors within a single dwelling unit. 

2. Floors where the joint is protected by a shaft enclo- 
sure in accordance with Section 708. 

3. Floors within atriums where the space adjacent to the 
atrium is included in the volume of the atrium for 
smoke control purposes. 

4. Floors within malls. 

5. Floors and ramps within open and enclosed parking 
garages or structures constructed in accordance with 
Sections 406.3 and 406.4, respectively. 

6. Mezzanine floors. 

7. Walls that are permitted to have unprotected open- 
ings. 

8. Roofs where openings are permitted. 

9. Control joints not exceeding a maximum width of 
0.625 inch (15.9 mm) and tested in accordance with 
ASTME 119 or UL 263. 

714.2 Installation. Fire-resistant joint systems shall be 
securely installed in or on the joint for its entire length so as not 
to dislodge, loosen or otherwise impair its ability to accommo- 
date expected building movements and to resist the passage of 
fire and hot gases. 

714.3 Fire test criteria. Fire-resistant) oint systems shall be 
tested in accordance with the requirements of either ASTM E 
1966 or UL 2079. Nonsymmetrical walljoint systems shall be 
tested with both faces exposed to the furnace, and the assigned 
fire-resistance rating shall be the shortest duration obtained 
from the two tests . When evidence is furnished to show that the 
wall was tested with the least fire-resistant side exposed to the 



furnace, subject to acceptance of the building official, the wall 
need not be subjected to tests from the opposite side. 

Exception: For exterior walls with a horizontal fire separa- 
tion distance greater than 5 feet (1524 mm), the joint system 
shall be required to be tested for interior fire exposure only. 

714.4 Exterior curtain wall/floor intersection. Where fire 
resistance-rated floor or floor/ceiling assemblies are required, 
voids created at the intersection of the exterior curtain wall 
assemblies and such floor assemblies shall be sealed with an 
approved system to prevent the interior spread of fire. Such 
systems shall be securely installed and tested in accordance 
with ASTM E 2307 to prevent the passage of flame for the time 
period at least equal to the fire-resistance rating of the floor 
assembly and prevent the passage of heat and hot gases suffi- 
cient to ignite cotton waste. Height and fire-resistance require- 
ments for curtain wall spandrels shall comply with Section 
705.8.5. 

714.4.1 Exterior curtain wall/nonfire-resistance-rated 
floor assembly intersections. Voids created at the intersec- 
tion of exterior curtain wall assemblies and nonfire-resis- 
tance-rated floor or floor/ceiling assemblies shall be sealed 
with an approved material or system to retard the interior 
spread of fire and hot gases between stories. 

714.5 Spandrel wall. Height and fire-resistance requirements 
for curtain wall spandrels shall comply with Section 705 .8.5 . 
Where Section 705 .8.5 does not require a fire-resistance-rated 
spandrel wall, the requirements of Section 714.4 shall still 
apply to the intersection between the spandrel wall and the 
floor. 

714.6 Fire-resistant joint systems in smoke barriers. 
Fire-resistantjoint systems in smoke barriers, and joints at the 
intersection of a horizontal smoke barrier and an exterior cur- 
tain wall, shall be tested in accordance with the requirements of 
UL 2079 for air leakage. The air leakage rate of the joint shall 
not exceed 5 cfm per lineal foot (0.00775 m 3 /s . m) of joint at 
0.30 inch (7.47 Pa) of water for both the ambient temperature 
and elevated temperature tests. 



SECTION 715 
OPENING PROTECTIVES 

715.1 General. Opening protectives required by other sections 
of this code shall comply with the provisions of this section. 

715.2 Fire-resistance-rated glazing. Fire-resistance-rated 
glazing tested as part of a fire-resistance-rated wall assembly in 
accordance with ASTM E 119 or UL 263 and labeled in accor- 
dance with Section 703.5 shall be permitted in fire doors and 
fire window assemblies in accordance with their listings and 
shall not otherwise be required to comply with this section. 

715.3 Alternative methods for determining fire protection 
ratings. The application of any of the alternative methods 
listed in this section shall be based on the fire exposure and 
acceptance criteria specified in NFPA 252, NFPA 257 or UL 9. 
The required fire resistance of an opening protective shall be 



2009 INTERNATIONAL BUILDING CODE® 



113 



FIRE AND SMOKE PROTECTION FEATURES 



I 



permitted to be established by any of the following methods or 
procedures: 

1. Designs documented in approve d sources. 

2. Calculations performed in an approve d manner. 

3. Engineering analysis based on a comparison of opening 
protective designs having fire protection ratings as 
determined by the test procedures set forth in NFPA 252, 
NFPA 257 or UL 9. 

4. Alternative protection methods as allowed by Section 
104.11. 

715.4 Fire door and shutter assemblies. Approved fire door 
and fire shutter assemblies shall be constructed of any material 
or assembly of component materials that conforms to the test 
requirements of Section 715 .4. 1 ,7 15 .4.2 or 715.4.3 and the fire 
protection rating indicated in Table 715.4. Fire door frames 
with transom lights, sidelights or both shall be permitted in 
accordance with Section 715.4.5. Fire door assemblies and 
shutters shall be installed in accordance with the provisions of 
this section and NFPA 80. 

Exceptions: 

1. Labeled protective assemblies that conform to the 
requirements of this section or UL 10 A, UL 14B and 
UL 14C for tin-clad fire door assemblies. 

2. Floor fire door assemblies in accordance with Section 

712.8. 

715.4.1 Side-hinged or pivoted swinging doors. Fire door 
assemblies with side-hinged and pivoted swinging doors 
shall be tested in accordance with NFPA 252 or UL IOC. 
After 5 minutes into the NFPA 252 test, the neutral pressure 



level in the furnace shall be established at 40 inches (1016 
mm) or less above the sill. 

715.4.2 Other types of assemblies. Fire door assemblies 
with other types of doors, including swinging elevator doors 
and fire shutter assemblies, shall be tested in accordance 
with NFPA 252 or UL 10B . The pressure in the furnace shall 
be maintained as nearly equal to the atmospheric pressure as 
possible. Once established, the pressure shall be maintained 
during the entire test period. 

715.4.3 Door assemblies in corridors and smoke barri- 
ers. Fire door assemblies required to have a minimum fire 
protection rating of 20 minutes where located in corridor 
walls or smoke barrierwalls having afire-resistance rating 
in accordance with Table 715.4 shall be tested in accordance 
with NFPA 252 or UL 10C without the hose stream test. 

Exceptions: 

1. Viewports that require a hole not larger than 1 inch 
(25 mm) in diameter through the door, have at least 
a 0.25-inch-thick (6.4 mm) glass disc and the 
holder is of metal that will not melt out where sub- 
ject to temperatures of 1,700°F (927°C). 

2. Corridordoor assemblies in occupancies of Group 
1-2 shall be in accordance with Section 407.3.1. 

3. Unprotected openings shall be permitted for corri- 
dors in multitheater complexes where each motion 
picture auditorium has at least one-half of its 
required exit or exit access doorways opening 
directly to the exterior or into an exitpassageway. 

4. Horizontal sliding doors in smoke barriers that 
comply with Sections 408.3 and 408.8.4 in occu- 
pancies in Group 1-3. 



TABLE 715.4 
FIRE DOOR AND FIRE SHUTTER FIRE PROTECTION RATINGS 



TYPE OF ASSEMBLY 


REQUIRED ASSEMBLY RATING 

(hours) 


MINIMUM FIRE DOOR AND FIRE 
SHUTTER ASSEMBLY RATING (hours) 


Fire walls and fire barriers having a required fire-resistance 
rating greater than 1 hour 


4 

3 

2 

lV 2 


3 
3 a 
1V 2 
lV 2 


Fire barriers having a required fire-resistance rating of 1 hour: 
Shaft, exit enclosure and exit passageway walls 
Other fire barriers 


1 
1 


1 

3/ 4 


Fire partitions: 
Corridor walls 

Other fire partitions 


1 

0.5 

1 

0.5 


l/ 3 b 

I/3 b 

3/ 4 
17 3 


Exterior walls 


3 
2 

1 


1V 2 
lV 2 

3/ 4 


Smoke barriers 


1 


I/3 b 



a. Two doors, each with a fire protection rating of 1 V 2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection 
rating to one 3 -hour fire door. 

b. For testing requirements, see Section 715.4.3. 



114 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



715.4.3.1 Smoke and draft control. Fire door assem- 
blies shall also meet the requirements for a smoke and 
draft control door assembly tested in accordance with 
UL 1784. The air leakage rate of the door assembly shall 
not exceed 3.0 cubic feet per minute per square foot 
(0.01524 m 3 /s . m 2 ) of door opening at 0.10 inch (24.9 
Pa) of water for both the ambient temperature and ele- 
vated temperature tests. Louvers shall be prohibited. 
Installation of smoke doors shall be in accordance with 
NFPA 105. 

715.4.3.2 Glazing in door assemblies. In a 20-minute 
fire door assembly, the glazing material in the door itself 
shall have a minimum fire-protection-rated glazing of 20 
minutes and shall be exempt from the hose stream test. 
Glazing material in any other part of the door assembly, 
including transom lights and sidelights, shall be tested in 
accordance with NFPA 257 or UL 9, including the hose 
stream test, in accordance with Section 715.5. 

715.4.4 Doors in exit enclosures and exit passageways. 
Fire door assemblies in exit enclosures and exit passage- 
ways shall have a maximum transmitted temperature end 
point of not more than 450°F (250°C) above ambient at the 
end of 30 minutes of standard fire test exposure. 

Exception: The maximum transmitted temperature rise 
is not required in buildings equipped throughout with an 
automatic sprinkler system installed in accordance with 
Section 903.3.1.1 or 903.3.1.2. 

715.4.4.1 Glazing in doors. Fire-protection-rated glaz- 
ing in excess of 100 square inches (0.065 m 2 ) shall be 
permitted mfire door assemblies when tested as compo- 
nents of the door assemblies and not as glass lights, and 
shall have a maximum transmitted temperature rise of 
450°F (250°C) in accordance with Section 715.4.4. 

Exception: The maximum transmitted temperature 
rise is not required in buildings equipped throughout 
with an automatic sprinkler system installed in accor- 
dance with Section 903.3.1.1 or 903.3.1.2. 

715.4.5 Fire door frames with transom lights and side- 
lights. Door frames with transom lights, sidelights, or both, 
shall be permitted where a 3/ 4 -hour fire protection rating or 
less is required in accordance with Table 715.4. Where afire 
protection rating exceeding 3/4-hour is required in accor- 
dance with Table 715.4, fire door frames with transom 
lights, sidelights, or both, shall be permitted where installed 
with fire-resistance-rated glazing tested as an assembly in 
accordance with ASTM El 19 or UL 263. 

715.4.6 Labeled protective assemblies. Fire door assem- 
blies shall be labeled by an approved agency. The labels 
shall comply with NFPA 80, and shall be permanently 
affixed to the door or frame. 

715.4.6.1 Fire door labeling requirements. Fire doors 
shall be labeled showing the name of the manufacturer or 
other identification readily traceable back to the manu- 
facturer, the name or trademark of the third-party inspec- 
tion agency, the fire protection rating and, where 



required for fire doors in exit enclosures and exit 
passageways by Section 715.4.4, the maximum trans- 
mitted temperature end point. Smoke and draft control 
doors complying with UL 1784 shall be labeled as such 
and shall also comply with Section 715.4.6.3. Labels 
shall be approved and permanently affixed. The label 
shall be applied at the factory or location where fabrica- 
tion and assembly are performed. 

715.4.6.2 Oversized doors. Oversized fire doors shall 
bear an oversized fire doorlabelby an approved agency 
or shall be provided with a certificate of inspection fur- 
nished by an approvedte sting agency. When a certificate 
of inspection is furnished by an approvedtesting agency, 
the certificate shall state that the door conforms to the 
requirements of design, materials and construction, but 
has not been subjected to the fire test. 

715.4.6.3 Smoke and draft control door labeling 
requirements. Smoke and draft control doors comply- 
ing with UL 1784 shall be labeled in accordance with 
Section 715.4.6.1 and shall show the letter" S" on the fire 
rating label of the door. This marking shall indicate that 
the door and frame assembly are in compliance when 
listed or labeled gasketing is also installed. 

715.4.6.4 Fire door frame labeling requirements. Fire 
door frames shall be labeled showing the names of the 
manufacturer and the third-party inspection agency. 

715.4.7 Glazing material. Fire-protection-rated glazing 
conforming to the opening protection requirements in Sec- 
tion 715.4 shall be permitted in fire Jo or assemblies. 

715.4.7.1 Size limitations. Fire-protection-rated glazing 
used in fire doors shall comply with the size limitations 
ofNFPA80. 

Exceptions: 

1. Fire-protection-rated glazing in fire doors 
located in fire walls shall be prohibited except 
where serving in afire door in a horizontal exit, 
a self-closing swinging door shall be permitted 
to have a vision panel of not more than 100 
square inches (0.065 m 2 ) without a dimension 
exceeding 10 inches (254 mm). 

2. Fire-protection-rated glazing shall not be 
installed in fire doors having a l 1 / 2 -hour fire 
protection rating intended for installation in 
fire barriers, unless the glazing is not more than 

100 square inches (0.065 m 2 ) in area. 

715.4.7.2 Exit and elevator protectives. Approved 
fire-protection-rated glazing used mfire door assemblies 
in elevator and exit enclosures shall be so located as to 
furnish clear vision of the passageway or approach to the 
elevator, ramp or stairway. 

715.4.7.3 Labeling. Fire-protection-rated glazing shall 
bear a label or other identification showing the name of 
the manufacturer, the test standard and information 
required in Section 715.5.9.1 that shall be issued by an 



2009 INTERNATIONAL BUILDING CODE® 



115 



FIRE AND SMOKE PROTECTION FEATURES 



approved agency and shall be permanently affixed to the 
glazing. 

715.4.7.3.1 Identification. For fire protection-rated 
glazing, the label shall bear the following four-part 
identification: "D - H or NH - T or NT - XXX. " "D" 
indicates that the glazing shall be used in fire door 
assemblies and that the glazing meets the fire protec- 
tion requirements of NFPA 252 . "H" shall indicate 
that the glazing meets the hose stream requirements of 
NFPA 252. "NH" shall indicate that the glazing does 
not meet the hose stream requirements of the test. "T" 
shall indicate that the glazing meets the temperature 
requirements of Section 715.4.4.1. "NT" shall indi- 
cate that the glazing does not meet the temperature 
requirements of Section 715.4.4.1. The placeholder 
"XXX" shall specify the fire-protection-rating 
period, in minutes. 

715.4.7.4 Safety glazing. Fire-protection-rated glazing 
installed in fire doors in areas subject to human impact in 
hazardous locations shall comply with Chapter 24. 

715.4.8 Door closing. Fire doors shall be self- or auto- 
matic-closing in accordance with this section. 

Exceptions: 

1. Fire doors located in common walls separating 
sleeping units in Group R-l shall be permitted 
without automatic- or self-closing devices. 

2. The elevator car doors and the associated hoistway 
enclosure doors at the floor level designated for 
recall in accordance with Section 3003.2 shall be 
permitted to remain open during Phase I emer- 
gency recall operation. 

715.4.8.1 Latch required. Unless otherwise specifically 
permitted, single fire doors and both leaves of pairs of 
side-hinged swinging fire doors shall be provided with 
an active latch bolt that will secure the door when it is 
closed. 

715.4.8.2 Automatic-closing fire door assemblies. 
Automatic-closing fire door assemblies shall be 
self-closing in accordance with NFPA 80. 

715.4.8.3 Smoke-activated doors. Automatic-closing 
doors installed in the following locations shall be auto- 
matic-closing by the actuation of smoke detectors 
installed in accordance with Section 907.3 or by loss of 
power to the smoke detector or hold-open device. Doors 
that are automatic-closing by smoke detection shall not 
have more than a 10- second delay before the door starts 
to close after the smoke detector is actuated: 

1. Doors installed across a corridor. 

2. Doors that protect openings in exits or corridors 
required to be of fire-resistance-rated construc- 
tion. 



3. Doors that protect openings in walls that are 
capable of resisting the passage of smoke in 
accordance with Section 508.2.5.2. 

4. Doors installed in smoke barriers in accordance 
with Section 710.5. 

5. Doors installed in fire partitions in accordance 
with Section 709.6. 

6. Doors installed in a fire wall in accordance with 
Section 706.8. 

7. Doors installed in shaft enclosures in accordance 
with Section 708.7. 

8. Doors installed in refuse and laundry chutes and 
access and termination rooms in accordance with 
Section 708.13. 

9. Doors installed in the walls for 
compartmentation of underground buildings in 
accordance with Section 405.4.2. 

10. Doors installed in the elevator lobby walls of 
underground buildings in accordance with Sec- 
tion 405.4.3. 

1 1 . Doors installed in smoke partitions in accordance 
with Section 711.5.3. 

715.4.8.4 Doors in pedestrian ways. Vertical sliding or 
vertical rolling steel fire doors in openings through 
which pedestrians travel shall be heat activated or acti- 
vated by smoke detectors with alarm verification. 

715.4.9 Swinging fire shutters. Where fire shutters of the 
swinging type are installed in exterior openings, not less 
than one row in every three vertical rows shall be arranged to 
be readily opened from the outside, and shall be identified 
by distinguishing marks or letters not less than 6 inches (152 
mm) high. 

715.4.10 Rolling fire shutters. Where fire shutters of the 
rolling type are installed, such shutters shall include 
approved automatic-closing devices. 

715.5 Fire-protection-rated glazing. Glazing in fire window 
assemblies shall be fire-protection rated in accordance with 
this section and Table 715.5. Glazing in fire door assemblies 
shall comply with Section 715.4.7. Fire-protection-rated glaz- 
ing shall be tested in accordance with and shall meet the accep- 
tance criteria of NFPA 257 or UL 9. Fire-protection-rated 
glazing shall also comply with NFPA 80. Openings in 
nonfire-resistance-rated exterior wall assemblies that require 
protection in accordance with Section 705.3, 705.8, 705.8.5 or 
705.8.6 shall have a fire-protection rating of not less than 3/ 4 
hour. 

Exceptions: 

1. Wired glass in accordance with Section 715.5.4. 

2. Fire protection-rated glazing in 0.5 -hour fire-resis- 
tance-rated partitions is permitted to have an 
0.33-hour fire-protection rating. 



116 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 715.5 
FIRE WINDOW ASSEMBLY FIRE PROTECTION RATINGS 



TABLE 715.5.4 
LIMITING SIZES OF WIRED GLASS PAN 



ELS 



TYPE OF ASSEMBLY 


REQUIRED 

ASSEMBLY 

RATING (hours) 


MINIMUM FIRE 

WINDOW 

ASSEMBLY 

RATING (hours) 


Interior walls: 


Fire walls 


All 


Npa 


Fire barriers 


> 1 
1 


Npa 

3/ 4 


Smoke barriers 


1 


3/ 4 


Fire partitions 


1 

l/ 2 


3/ 4 
l/ 3 


Exterior walls 


> 1 
1 


1V 2 

3/4 


Party wall 


All 


NP 



NP = Not Permitted. 

a. Not permitted except as specified in Section 715.2. 

715.5.1 Testing under positive pressure. NFPA 257 orUL 
9 shall evaluate fire-protection-rated glazing under positive 
pressure. Within the first 10 minutes of a test, the pressure in 
the furnace shall be adjusted so at least two-thirds of the test 
specimen is above the neutral pressure plane, and the neutral 
pressure plane shall be maintained at that height for the bal- 
ance of the test. 

715.5.2 Nonsymmetrical glazing systems. Nonsymmetri- 
cal fire-protection-rated glazing systems in fire partitions, 
fire barriers or in exterior walls with a fire separation dis- 
tance of 5 feet (1524 mm) or less pursuant to Section 705 
shall be tested with both faces exposed to the furnace, and 
the assigned, fire protection rating shall be the shortest dura- 
tion obtained from the two tests conducted in compliance 
with NFPA 257 or UL 9. 

715.5.3 Safety glazing. Fire-protection-rated glazing 
installed in fire window assemblies in areas subject to 
human impact in hazardous locations shall comply with 
Chapter 24. 

715.5.4 Wired glass. Steel window frame assemblies of 
0.125-inch (3.2 mm) minimum solid section or of not less 
than nominal 0.048 -inch-thick (1.2 mm) formed sheet steel 
members fabricated by pressing, mitering, riveting, inter- 
locking or welding and having provision for glazing with 
1/4-inch (6.4 mm) wired glass where securely installed in the 
building construction and glazed with i/ 4 -inch (6.4 mm) 
labeled wired glass shall be deemed to meet the require- 
ments for a 3i A -ho\xi fire window assembly. Wired glass pan- 
els shall conform to the size limitations set forth in Table 
715.5.4. 

715.5.5 Nonwired glass. Glazing other than wired glass in 
fire window assemblies shall be fire-protection-rated glaz- 
ing installed in accordance with and complying with the size 
limitations set forth in NFPA 80. 

715.5.6 Installation. Fire-protection-rated glazing shall be 
in the fixed position or be automatic-closing and shall be 
installed in approved frames. 



OPENING FIRE 

PROTECTION 

RATING 


MAXIMUM 
AREA 

(square inches) 


MAXIMUM 
HEIGHT 

(inches) 


MAXIMUM 
WIDTH 

(inches) 


3 hours 











yV 2 -hour doors in 
exterior walls 











1 and l 1 / 2 hours 


100 


33 


10 


3/4 hour 


1,296 


54 


54 


20 minutes 


Not Limited 


Not Limited 


Not Limited 


Fire window 
assemblies 


1,296 


54 


54 



For SI: 1 inch = 25.4 mm, 1 square inch = 645 .2 mm 2 - 

715.5.7 Window mullions. Metal mullions that exceed a 
nominal height of 12 feet (3658 mm) shall be protected with 
materials to afford the same fire-resistance rating as 
required for the wall construction in which the protective is 
located. 

715.5.8 Interior fire window assemblies. Fire-protec- 
tion-rated glazing used in/ire window assemblies located in 
fire partitions and fire barriers shall be limited to use in 
assemblies with a maximum fire -resistance rating of 1 hour 
in accordance with this section. 

715.5.8.1 Where 3/ 4 -hour fire protection window 
assemblies permitted. Fire-protection-rated glazing 
requiring 45-minute opening protection in accordance 
with Table 715.5 shall be limited to fire partitions 
designed in accordance with Section 709 and fire barri- 
ers utilized in the applications set forth in Sections 
707.3.6 and 707.3.8 where the fire-resistance rating does 
not exceed 1 hour. 

715.5.8.2 Area limitations. The total area of windows 
shall not exceed 25 percent of the area of a common wall 
with any room. 

715.5.9 Labeling requirements. Fire-protection-rated 
glazing shall bear a label 01 other identification showing the 
name of the manufacturer, the test standard and information 
required in Section 715.5.9.1 that shall be issued by an 
approved agency and shall be permanently affixed to the 
glazing. 

715.5.9.1 Identification. For fire-protection-rated glaz- 
ing, the labelshall bear the following two-part identifica- 
tion: "OH - XXX." "OH" indicates that the glazing 
meets both the fire protection and the hose- stream 
requirements of NFPA 257 or UL 9 and is permitted to be 
used in openings. "XXX" represents the fire-protection 
rating period, in minutes, that was tested. 



SECTION 716 
DUCTS AND AIR TRANSFER OPENINGS 

716.1 General. The provisions of this section shall govern the 
protection of duct penetrations and air transfer openings in 
assemblies required to be protected. 



2009 INTERNATIONAL BUILDING CODE® 



117 



FIRE AND SMOKE PROTECTION FEATURES 



1 



716.1.1 Ducts that penetrate fire- resistance-rated 
assemblies without dampers. Ducts that penetrate 
fire-resistance-rated assemblies and are not required by this 
section to have dampers shall comply with the requirements 
of Sections 713.2 through 713.3.3. Ducts that penetrate hor- 
izontal assemblies not required to be contained within a 
shaft and not required by this section to have dampers shall 
comply with the requirements of Sections 713.4 through 
713.4.2.2. 

716.1.1.1 Ducts that penetrate nonfire-resis- 
tance-rated assemblies. The space around a duct pene- 
trating a nonfire-resistance-rated floor assembly shall 
comply with Section 716.6.3. 

716.2 Installation. Fire dampers, smoke dampers, combina- 
tion fire/smoke dampers and ceiling radiation dampers located 
within air distribution and smoke control systems shall be 
installed in accordance with the requirements of this section, 
the manufacturer's installation instructions and the dampers' 
listing. 

716.2.1 Smoke control system. Where the installation of a 
fire damper will interfere with the operation of a required 
smoke control system in accordance with Section 909, 
approved alternative protection shall be utilized. Where 
mechanical systems including ducts and dampers utilized 
for normal building ventilation serve as part of the smoke 
control system, the expected performance of these systems 
in smoke control mode shall be addressed in the rational 
analysis required by Section 909.4. 

716.2.2 Hazardous exhaust ducts. Fire dampers for haz- 
ardous exhaust duct systems shall comply with the Interna- 
tional Mechanical Code. 

716.3 Damper testing, ratings and actuation. Damper test- 
ing, ratings and actuation shall be in accordance with Sections 
716.3.1 through 716.3.3. 

716.3.1 Damper testing. Dampers shall be listed and bear 
the label of an approved testing agency indicating compli- 
ance with the standards in this section. Fire dampers shall 
comply with the requirements ofUL 555. Only fire dampers 
labeled for use in dynamic systems shall be installed in heat- 
ing, ventilation and air-conditioning systems designed to 
operate with fans on during a fire. Smoke dampers shall 
comply with the requirements of UL 555S. Combination 
fire/smoke dampers shall comply with the requirements of 
both UL 555 and UL 555S. Ceiling radiation dampers shall 
comply with the requirements of UL 555C. 

716.3.2 Damper rating. Damperratings shall be in accor- 
dance with Sections 716.3.2.1 through 716.3.2.3. 

716.3.2.1 Fire damper ratings. Fire dampers shall have 
the minimum fire protection rating specified in Table 

716.3.2.1 for the type of penetration. 

716.3.2.2 Smoke damper ratings. Smoke damperieak- 
age ratings shall not be less than Class II. Elevated tem- 
perature ratings shall not be less than 250°F (121°C). 



TABLE 716.3.2.1 
FIRE DAMPER RATING 



TYPE OF 
PENETRATION 


MINIMUM DAMPER RATING 
(hours) 


Less than 3-hour fire-resistance-rated 
assemblies 


1.5 


3-hour or greater fire-resistance-rated 
assemblies 


3 



716.3.2.3 Combination fire/smoke damper ratings. 
Combination fire/smoke dampers shall have the mini- 
mum fire protection rating specified for fire dampers in 
Table 716.3.2.1 for the type of penetration and shall also 
have a minimum Class II leakage rating and a minimum 
elevated temperature rating of 250°F (121°C) . 

716.3.3 Damper actuation. Damper actuation shall be in 
accordance with Sections 716.3.3.1 through 716.3.3.4 as 
applicable. 

716.3.3.1 Fire damper actuation device. The fire 
damper actuation device shall meet one of the following 
requirements: 

1. The operating temperature shall be approximately 
50°F (10°C) above the normal temperature within 
the duct system, but not less than 160°F (71 °C) . 

2. The operating temperature shall be not more than 
350°F (177°C) where located in a smoke control 
system complying with Section 909. 

716.3.3.2 Smoke damper actuation. The smoke 
damper shall close upon actuation of a listed smoke 
detector or detectors installed in accordance with Section 
907.3 and one of the following methods, as applicable: 

1. Where a smoke damperis installed within a duct, a 
smoke detector shall be installed in the duct within 
5 feet (1524 mm) of the damperwith no air outlets 
or inlets between the detector and the damper. The 
detector shall be listedfor the air velocity, temper- 
ature and humidity anticipated at the point where it 
is installed. Other than in mechanical smoke con- 
trol systems, dampers shall be closed upon fan 
shutdown where local smoke detectors require a 
minimum velocity to operate. 

2. Where a smoke damper is installed above smoke 
barrier doors in a smoke barrier, a spot-type 
detector listed for releasing service shall be 
installed on either side of the smoke barrier door 
opening. 

3. Where a smoke damper is installed within an air 
transfer opening in a wall, a spot-type detector 
listedfor releasing service shall be installed within 
5 feet (1524 mm) horizontally of the damper. 

4. Where a smoke damper is installed in a corridor 
wall or ceiling, the dampershall be permitted to be 



118 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



controlled by a smoke detection system installed in 
the corridor. 

5. Where a total-coverage smoke detector system is 
provided within areas served by a heating, ventila- 
tion and air-conditioning (HVAC) system, smoke 
dampers shall be permitted to be controlled by the 
smoke detection system. 

716.3.3.3 Combination fire/smoke damper actuation. 
Combination fire/smoke damper actuation shall be in 
accordance with Sections 716.3.3.1 and 716.3.3.2. Com- 
bination fire/smoke dampers installed in smoke control 
system shaft penetrations shall not be activated by local 
area smoke detection unless it is secondary to the smoke 
management system controls. 

716.3.3.4 Ceiling radiation damper actuation. The 
operating temperature of a ceiling radiation damper 
actuation device shall be 50°F (27.8°C) above the normal 
temperature within the duct system, but not less than 
160°F (71°C). 

716.4 Access and identification. Fire and smoke dampers 
shall be provided with an approved means of access, which is 
large enough to permit inspection and maintenance of the 
damper Mid its operating parts. The access shall not affect the 
integrity of fire-resistance-rated assemblies. The access open- 
ings shall not reduce the fire-resistance rating of the assembly. 
Access points shall be permanently identified on the exterior 
by a label having letters not less than i/ 2 inch (12.7 mm) in 
height reading: FIRE/SMOKE DAMPER, SMOKE DAMPER 
or FIRE DAMPER. Access doors in ducts shall be tight fitting 
and suitable for the required duct construction. 

716.5 Where required. Fire dampers, smoke dampers and 
combination fire/smoke dampers shall be provided at the loca- 
tions prescribed in Sections 716.5.1 through 716.5.7 and 
716.6. Where an assembly is required to have both fire dampers 
and smoke dampers, combination fire/smoke dampers or afire 
damper and a smoke damper shall be required. 

716.5.1 Fire walls. Ducts and air transfer openings permit- 
ted in fire walls in accordance with Section 706.11 shall be 
protected with listed fire dampers installed in accordance 
with their listing. 

716.5.1.1 Horizontal exits. A listed smoke damper 
designed to resist the passage of smoke shall be provided 
at each point a duct or air transfer opening penetrates a 
fire wall that serves as a horizontal exit. 

716.5.2 Fire barriers. Ducts and air transfer openings of 
fire barriers shall be protected with approved fire dampers 
installed in accordance with their listing. Ducts and air 
transfer openings shall not penetrate ex/renclosures and exit 
passageways except as permitted by Sections 1022.4 and 
1023.6, respectively. 

Exception: Fire dampers are not required at penetra- 
tions of fire barriers where any of the following apply: 

1. Penetrations are tested in accordance with ASTM 
E 119 or UL 263 as part of the fire-resistance-rated 
assembly. 



2. Ducts are used as part of an approved smoke con- 
trol system in accordance with Section 909 and 
where the use of afire damperwould interfere with 
the operation of a smoke control system. 

3. Such walls are penetrated by ducted HVAC sys- 
tems, have a required fire-resistance rating of 1 
hour or less, are in areas of other than Group Hand 
are in buildings equipped throughout with an auto- 
matic sprinkler system in accordance with Section 
903.3.1.1 or 903.3.1.2. For the purposes of this 
exception, a ducted HVAC system shall be a duct 
system for conveying supply, return or exhaust air 
as part of the structure's HVAC system. Such a 
duct system shall be constructed of sheet steel not 
less than No. 26 gage thickness and shall be con- 
tinuous from the air-handling appliance or equip- 
ment to the air outlet and inlet terminals. 

716.5.2.1 Horizontal exits. A listed smoke damper 
designed to resist the passage of smoke shall be provided 
at each point a duct or air transfer opening penetrates a 
fire barrier that serves as a horizontal exit. 

716.5.3 Shaft enclosures. Shaft enclosures that are permit- 
ted to be penetrated by ducts and air transfer openings shall 
be protected with approved fire and smoke dampers 
installed in accordance with their listing. 

Exceptions: 

1. Fire dampers are not required at penetrations of 
shafts where: 

1.1. Steel exhaust subducts are extended at 
least 22 inches (559 mm) vertically in 
exhaust shafts, provided there is a continu- 
ous airflow upward to the outside ; or 

1.2. Penetrations are tested in accordance with 
ASTM E 119 or UL 263 as part of the 
fire-resistance-rated assembly; or 

1.3. Ducts are used as part of an approved 
smoke control system designed and 
installed in accordance with Section 909 
and where the fire damper will interfere 
with the operation of the smoke control 
system; or 

1.4. The penetrations are in parking garage 
exhaust or supply shafts that are separated 
from other building shafts by not less than 
2-hour fire-resistance-rated construction. 

2. In Group Band R occupancies equipped through- 
out with an automatic sprinkler system in accor- 
dance with Section 903.3.1.1, smoke dampers are 
not required at penetrations of shafts where: 

2.1. Kitchen, clothes dryer, bathroom and toilet 
room exhaust openings are installed with 
steel exhaust subducts, having a minimum 
wall thickness ofO. 187-inch (0.4712 mm) 
(No. 26 gage); 

2.2. The subducts extend at least 22 inches (559 
mm) vertically; and 



2009 INTERNATIONAL BUILDING CODE® 



119 



FIRE AND SMOKE PROTECTION FEATURES 



2.3. An exhaust fan is installed at the upper ter- 
minus of the shaft that is powered continu- 
ously in accordance with the provisions of 
Section 909.11, so as to maintain a contin- 
uous upward airflow to the outside. 

3. Smoke dampers are not required at penetration of 
exhaust or supply shafts in parking garages that are 
separated from other building shafts by not less 
than 2-hour fire-resistance-rated construction. 

4. Smoke dampers are not required at penetrations of 
shafts where ducts are used as part of an approved 
mechanical smoke control system designed in 
accordance with Section 909 and where the smoke 
damper will interfere with the operation of the 
smoke control system. 

5. Fire dampers and combination fire/smoke damp- 
ers are not required in kitchen and clothes dryer 
exhaust systems when installed in accordance with 
the International Mechanical Code. 

716.5.4 Fire partitions. Ducts and air transfer openings 
that penetrate fire partitions shall be protected with listed 
fire dampers installed in accordance with their listing. 

Exceptions: In occupancies other than Group H, fire 
dampers are not required where any of the following 
apply: 

1. Corridor walls in buildings equipped throughout 
with an automatic sprinkler system in accordance 
with Section 903.3.1.1 or 903.3.1.2 and the duct is 
protected as a through penetration in accordance 
with Section 713. 

2. Tenant partitions in coveredmall buildings where 
the walls are not required by provisions elsewhere 
in the code to extend to the underside of the floor or 
roof sheathing, slab or deck above. 

3. The duct system is constructed of approved mate- 
rials in accordance with the International Mechan- 
ical Code and the duct penetrating the wall 
complies with all of the following requirements: 

3.1. The duct shall not exceed 100 square 
inches (0.06 m 2 ). 

3.2. The duct shall be constructed of steel a 
minimum of 0.0217 inch (0.55 mm) in 
thickness. 

3.3. The duct shall not have openings that com- 
municate the corridorwith adjacent spaces 
or rooms. 

3 .4. The duct shall be installed above a ceiling. 

3.5. The duct shall not terminate at a wall regis- 
ter in the fire-resistance-rated wall. 

3.6. A minimum 12-inch-long (305 mm) by 
0.060-inch-thick (1.52 mm) steel sleeve 
shall be centered in each duct opening. The 
sleeve shall be secured to both sides of the 
wall and all four sides of the sleeve with 
minimum l 1 / 2 -inch by l 1 / 2 -inch by 



0.060-inch (38 mm by 38 mm by 1.52 mm) 
steel retaining angles. The retaining angles 
shall be secured to the sleeve and the wall 
with No. 10 (M5) screws. The annular 
space between the steel sleeve and the wall 
opening shall be filled with mineral wool 
batting on all sides. 

716.5.4.1 Corridors. A listed smoke damper designed to 
resist the passage of smoke shall be provided at each 
point a duct or air transfer opening penetrates a corridor 
enclosure required to have smoke and draft control doors 
in accordance with Section 715.4.3. 

Exceptions: 

1. Smoke dampers are not required where the 
building is equipped throughout with an 
app roved smoke control system in accordance 
with Section 909, and smoke dampers are not 
necessary for the operation and control of the 
system. 

2. Smoke dampers are not required in corridor 
penetrations where the duct is constructed of 
steel not less than 0.019 inch (0.48 mm) in 
thickness and there are no openings serving the 
corridor. 

716.5.5 Smoke barriers. A listed smoke damper designed 
to resist the passage of smoke shall be provided at each point 
a duct or air transfer opening penetrates a smoke barrier. 
Smoke dampers and smoke damper actuation methods shall 
comply with Section 716.3.3.2. 

Exception: Smoke dampers are not required where the 
openings in ducts are limited to a single smoke compart- 
ment and the ducts are constructed of steel. 

716.5.6 Exterior walls. Ducts and air transfer openings in 
fire-resistance-rated exterior walls required to have pro- 
tected openings in accordance with Section 705 . 10 shall be 
protected with listed fire dampers installed in accordance 
with their listing. 

716.5.7 Smoke partitions. A listed smoke damper designed 
to resist the passage of smoke shall be provided at each point 
that an air transfer opening penetrates a smoke partition. 
Smoke dampers and smoke damper actuation methods shall 
comply with Section 716.3.3.2. 

Exception: Where the installation of a smoke damper 
will interfere with the operation of a required smoke con- 
trol system in accordance with Section 909, approved 
alternative protection shall be utilized. 

716.6 Horizontal assemblies. Penetrations by ducts and air 
transfer openings of a floor, floor/ceiling assembly or the ceil- 
ing membrane of a roof/ceiling assembly shall be protected by 
a shaft enclosure that complies with Section 708 or shall com- 
ply with Sections 716.6.1 through 716.6.3. 

716.6.1 Through penetrations. In occupancies other than 
Groups 1-2 and 1-3, a duct constructed of approvedmaterials 
in accordance with the International Mechanical Code that 
penetrates a fire-resistance-rated floor/ceiling assembly 
that connects not more than two stories is permitted without 



120 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



I 



shaft enclosure protection, provided a listed fire damper is 
installed at the floor line or the duct is protected in accor- 
dance with Section 713.4. For air transfer openings, see 
Exception 7 to Section 708.2. 

Exception: A duct is permitted to penetrate three floors 
or less without afire damper at each floor, provided such 
duct meets all of the following requirements: 

1. The duct shall be contained and located within the 
cavity of a wall and shall be constructed of steel 
having a minimum wall thickness of 0.187 inches 
(0.4712 mm) (No. 26 gage). 

2. The duct shall open into only one dwelling or 
sleeping unit and the duct system shall be continu- 
ous from the unit to the exterior of the building. 

3. The duct shall not exceed 4-inch (102 mm) nomi- 
nal diameter and the total area of such ducts shall 
not exceed 100 square inches (0.065 m 2 ) in any 
100 square feet (9.3 m 2 ) of floor area. 

4. The annular space around the duct is protected 
with materials that prevent the passage of flame 
and hot gases sufficient to ignite cotton waste 
where subjected to ASTM E 119 or UL 263 
time-temperature conditions under a minimum 
positive pressure differential of 0.01 inch (2.49 Pa) 
of water at the location of the penetration for the 
time period equivalent to the fire -resistance rating 
of the construction penetrated. 

5. Grille openings located in a ceiling of a fire-resis- 
tance-rated floor/ceiling or roof/ceiling assembly 
shall be protected with a listed ceiling radiation 
damper installed in accordance with Section 
716.6.2.1. 

716.6.2 Membrane penetrations. Ducts and air transfer 
openings constructed of approve d materials in accordance 
with the International Mechanical Code that penetrate the 
ceiling membrane of a fire-resistance-rated floor/ceiling or 
roof/ceiling assembly shall be protected with one of the fol- 
lowing: 

1. A shaft enclosure in accordance with Section 708. 

2. A listed ceiling radiation damper installed at the ceil- 
ing line where a duct penetrates the ceiling of a 
fire-resistance-rated floor/ceiling or roof/ceiling 
assembly. 

3. A listed ceiling radiation damper installed at the ceil- 
ing line where a diffuser with no duct attached pene- 
trates the ceiling of a fire-resistance-rated 
floor/ceiling or roof /ceiling assembly. 

716.6.2.1 Ceiling radiation dampers. Ceiling radiation 
dampers shall be tested as part of a fire-resistance-rated 
floor/ceiling or roof/ceiling assembly in accordance with 
ASTM E 1 19 or UL 263. Ceilingradiation dampers shall 
be installed in accordance with the details listed in the 
fire-resistance-rated assembly and the manufacturer's 
installation instructions and the listing. Ceilingradiation 



dampers are not required where either of the following 
applies: 

1. Tests in accordance with ASTM E 119 or UL 263 
have shown that ceilingradiation dampers are not 
necessary in order to maintain the fire-resistance 
rating of the assembly. 

2. Where exhaust duct penetrations are protected in 
accordance with Section 713.4.1.2, are located 
within the cavity of a wall and do not pass through 
another dwelling unit or tenant space. 

716.6.3 Nonfire-resistance-rated floor assemblies. Duct 
systems constructed of approved materials in accordance 
with the International Mechanical Code that penetrate 
nonfire-resistance-rated floor assemblies shall be protected 
by any of the following methods: 

1. A shaft enclosure in accordance with Section 708. 

2. The duct connects not more than two stories, and the 
annular space around the penetrating duct is pro- 
tected with an approvednoncombustible material that 
resists the free passage of flame and the products of 
combustion. 

3. The duct connects not more than three stories, and the 
annular space around the penetrating duct is pro- 
tected with an approvednoncombustibie material that 
resists the free passage of flame and the products of 
combustion and afire dampens installed at each floor 
line. 

Exception: Fire dampers are not required in ducts 
within individual residential dwelling units. 

716.7 Flexible ducts and air connectors. Flexible ducts and 
air connectors shall not pass through any fire-resistance-rated 
assembly. Flexible air connectors shall not pass through any 
wall, floor or ceiling. 



SECTION 717 
CONCEALED SPACES 

717.1 General. Fireblocking and draftstopping shall be 
installed in combustible concealed locations in accordance 
with this section. Fireblocking shall comply with Section 
717.2. Draftstopping in floor/ceiling spaces and attic spaces 
shall comply with Sections 717.3 and 717.4, respectively. The 
permitted use of combustible materials in concealed spaces of 
buildings of Type I or II construction shall be limited to the 
applications indicated in Section 717.5. 

717.2 Fireblocking. In combustible construction, fireblocking 
shall be installed to cut off concealed draft openings (both ver- 
tical and horizontal) and shall form an effective barrier between 
floors, between a top story and a roof or attic space. 
Fireblocking shall be installed in the locations specified in Sec- 
tions 717.2.2 through 111 2.1. 

111.2.1 Fireblocking materials. Fireblocking shall consist 
of the following materials: 

1. Two-inch (51 mm) nominal lumber. 



2009 INTERNATIONAL BUILDING CODE® 



121 



FIRE AND SMOKE PROTECTION FEATURES 



2. Two thicknesses of I-inch (25 mm) nominal lumber 
with broken lap joints. 

3. One thickness of 0.719-inch (18.3 mm) wood struc- 
tural panels with joints backed by 0.719-inch (18.3 
mm) wood structural panels. 

4. One thickness of0.7S-inch (19.1 mm) particleboard 
with joints backed by 0.7S-inch (19 mm) 
particleboard. 

5. One-half-inch (12.7 mm) gypsum board. 

6. One-fourth-inch (6.4 mm) cement-based millboard. 

7. Batts or blankets of mineral wool, mineral fiber or 
other approv edmateriais installed in such a manner as 
to be securely retained in place. 

717.2. LIB atts or blankets of mineral wool or mineral 
fiber. Batts or blankets of mineral wool or mineral fiber 
or other approved nonrigid materials shall be permitted 
for compliance with the 10-foot (3048 mm) horizontal 
fireblocking in walls constructed using parallel rows of 
studs or staggered studs. 

717.2.1.2 Unfaced fiberglass. Unfaced fiberglass batt 
insulation used as fireblocking shall fill the entire cross 
section of the wall cavity to a minimum height of 16 
inches (406 mm) measured vertically. When piping, con- 
duit or similar obstructions are encountered, the insula- 
tion shall be packed tightly around the obstruction. 

717.2.1.3 Loose-fill insulation material. Loose-fill 
insulation material, insulating foam sealants and caulk 
materials shall not be used as a fireblock unless specifi- 
cally tested in the form and manner intended for use to 
demonstrate its ability to remain in place and to retard the 
spread of fire and hot gases. 

717.2.1.4 Fireblocking integrity. The integrity of 
fireblocks shall be maintained. 

717.2.1.5 Double stud walls. Batts or blankets of min- 
eral or glass fiber or other approved nonrigid materials 
shall be allowed as fireblocking in walls constructed 
using parallel rows of studs or staggered studs. 

717.2.2 Concealed wall spaces. Fireblocking shall be pro- 
vided in concealed spaces of stud walls and partitions, 
including furred spaces, and parallel rows of studs or stag- 
gered studs, as follows: 

1. Vertically at the ceiling and floor levels. 

2. Horizontally at intervals not exceeding 10 feet (3048 
mm). 

717.2.3 Connections between horizontal and vertical 
spaces. Fireblocking shall be provided at interconnections 
between concealed vertical stud wall or partition spaces and 
concealed horizontal spaces created by an assembly of floor 
joists or trusses, and between concealed vertical and hori- 
zontal spaces such as occur at soffits, drop ceilings, cove 
ceilings and similar locations. 

717.2.4 Stairways. Fireblocking shall be provided in con- 
cealed spaces between stair stringers at the top and bottom 



of the run. Enclosed spaces under stairs shall also comply 
with Section 1009.6.3. 

717.2.5 Ceiling and floor openings. Where required by 
Exception 6 of Section 708.2, Exception 1 of Section 
713.4.1.2 or Section 713.4.2, fireblocking of the annular 
space around vents, pipes, ducts, chimneys and fireplaces at 
ceilings and floor levels shall be installed with a material 
specifically tested in the form and manner intended for use 
to demonstrate its ability to remain in place and resist the 
free passage of flame and the products of combustion. 

717.2.5.1 Factory-built chimneys and fireplaces. Fac- 
tory-built chimneys and fireplaces shall be fireblocked in 
accordance with UL 103 and UL 127. 

717.2.6 Architectural trim. Fireblocking shall be installed 
within concealed spaces of exterior wall finish and other 
exterior architectural elements where permitted to be of 
combustible construction as specified in Section 1406 or 
where erected with combustible frames, at maximum inter- 
vals of 20 feet (6096 mm), so that there will be no open 
space exceeding 100 square feet (9.3 m 3 ). Where wood fur- 
ring strips are used, they shall be of approvedwood of natu- 
ral decay resistance or preservative-treated wood. If 
noncontinuous, such elements shall have closed ends, with 
at least 4 inches (102 mm) of separation between sections. 

Exceptions: 

1. Fireblocking of cornices is not required in sin- 
gle-family dwellings. Fireblocking of cornices of a 
two -family dwelling is required only at the line of 
dwelling unit separation. 

2. Fireblocking shall not be required where installed 
on noncombustible framing and the face of the 
exterior wall finish exposed to the concealed space 
is covered by one of the following materials: 

2.1. Aluminum having a minimum thickness of 
0.019 inch (0.5 mm). 

2.2. Corrosion-resistant steel having a base 
metal thickness not less than 0.016 inch 
(0.4 mm) at any point. 

2.3. Other approved noncombustible materi- 
als. 

717.2.7 Concealed sleeper spaces. Where wood sleepers 
are used for laying wood flooring on masonry or concrete 
fire-resistance-rated floors, the space between the floor slab 
and the underside of the wood flooring shall be filled with an 
approved material to resist the free passage of flame and 
products of combustion or fireblocked in such a manner that 
there will be no open spaces under the flooring that will 
exceed 100 square feet (9.3 m 2 ) in area and such space shall 
be filled solidly under permanent partitions so that there is 
no communication under the flooring between adjoining 
rooms. 

Exceptions: 

1. Fireblocking is not required for slab-on-grade 
floors in gymnasiums. 



122 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



2. Fireblocking is required only at the juncture of 
each alternate lane and at the ends of each lane in a 
bowling facility. 

717.3 Draftstopping in floors. In combustible construction, 
draftstopping shall be installed to subdivide floor/ceiling 
assemblies in the locations prescribed in Sections 717.3.2 
through 717.3.3. 

717.3.1 Draftstopping materials. Draftstopping materials 
shall not be less thanl/z-inch (12.7 mm) gypsum board, 
3/ s -inch (9.5 mm) wood structural panel, 3/ s -inch (9.5 mm) 
particleboard, I-inch (2S-mm) nominal lumber, cement 
fiberboard, batts or blankets of mineral wool or glass fiber, 
or other approved materials adequately supported. The 
integrity of draftstops shall be maintained. 

717.3.2 Groups R-l, R-2, R-3 and R-4. Draftstopping 
shall be provided in floor/ceiling spaces in Group R-l build- 
ings, in Group R-2 buildings with three or more dwelling 
units, in Group R-3 buildings with two dwelling units and in 
Group R-4 buildings. Draftstopping shall be located above 
and in line with the dwelling unit and sleeping unit separa- 
tions. 

Exceptions: 

1. Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1. 

2. Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.2, pro- 
vided that automatic sprinklers are also installed in 
the combustible concealed spaces. 

717.3.3 Other groups. In other groups, draftstopping shall 
be installed so that horizontal floor areas do not exceed 
1,000 square feet (93 m 2 ). 

Exception: Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler system 
in accordance with Section 903.3.1.1. 

717.4 Draftstopping in attics. In combustible construction, 
draftstopping shall be installed to subdivide attic spaces and 
concealed roof spaces in the locations prescribed in Sections 
71 7.4.2 and 71 7.4.3. Ventilation of concealed roof spaces shall 
be maintained in accordance with Section 1203.2. 

717.4.1 Draftstopping materials. Materials utilized for 
draftstopping of attic spaces shall comply with Section 

717.3.1. 

Ill AAA Openings. Openings in the partitions shall be 
protected by self-closing doors with automatic latches 
constructed as required for the partitions. 

717.4.2 Groups R-l and R-2. Draftstopping shall be pro- 
vided in attics, mansards, overhangs or other concealed roof 
spaces of Group R-2 buildings with three or more dwelling 
units and in all Group R-l buildings. Draftstopping shall be 
installed above, and in line with, sleeping unit and dwelling 



unit separation walls that do not extend to the underside of 
the roof sheathing above. 

Exceptions: 

1. Where corridor walls provide a sleeping unit or 
dwelling unit separation, draftstopping shall only 
be required above one of the corridor walls. 

2. Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1. 

3. In occupancies in Group R-2 that do not exceed 
four stories above grade plane, the attic space 
shall be subdivided by draftstops into areas not 
exceeding 3,000 square feet (279 m^ or above 
every two dwelling units, whichever is smaller. 

4. Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.2, pro- 
vided that automatic sprinklers are also installed in 
the combustible concealed spaces. 

717.4.3 Other groups. Draftstopping shall be installed in 
attics and concealed roof spaces, such that any horizontal 
area does not exceed 3,000 square feet (279 m 7 ). 

Exception: Draftstopping is not required in buildings 
equipped throughout with an automatic sprinkler system 
in accordance with Section 903.3.1.1. 

717.5 Combustible materials in concealed spaces in Type I 
or II construction. Combustible materials shall not be permit- 
ted in concealed spaces of buildings of Type I or II construc- 
tion. 

Exceptions: 

1. Combustible materials in accordance with Section 
603. 

2. Combustible materials exposed within plenums com- 
plying with Section 602 of the International Mechan- 
ical Code. 

3. Class A interior finish materials classified in accor- 
dance with Section 803. 

4. Combustible piping within partitions or shaft enclo- 
sures installed in accordance with the provisions of 
this code. 

5. Combustible piping within concealed ceiling spaces 
installed in accordance with the International 
Mechanical Code and the International Plumbing 
Code. 

6. Combustible insulation and covering on pipe and tub- 
ing, installed in concealed spaces other than plenums, 
complying with Section 719.7. 



2009 INTERNATIONAL BUILDING CODE® 



123 



FIRE AND SMOKE PROTECTION FEATURES 



SECTION 718 

FIRE-RESISTANCE REQUIREMENTS 

FOR PLASTER 

718.1 Thickness of plaster. The minimum thickness of gyp- 
sum plaster or portland cement plaster used in a fire- resis- 
tance-rated system shall be determined by the prescribed fire 
tests. The plaster thickness shall be measured from the face of 
the lath where applied to gypsum lath or metal lath. 

718.2 Plaster equivalents. For fire-resistance purposes, i/ 2 
inch (12.7 mm) of unsanded gypsum plaster shall be deemed 
equivalent to 3/ 4 inch (19.1 mm) of one-to-three gypsum sand 
plaster or 1 inch (25 mm) of portland cement sand plaster. 

718.3 Noncombustible furring. In buildings of Type I and II 
construction, plaster shall be applied directly on concrete or 
masonry or on approved noncombustible plastering base and 
furring. 

718.4 Double reinforcement. Plaster protection more than 1 
inch (25 mm) in thickness shall be reinforced with an addi- 
tionallayer of approve d lath embedded at least 3/ 4 inch (19.1 
mm) from the outer surface and fixed securely in place. 

Exception: Solid plaster partitions or where otherwise 
determined by fire tests. 

718.5 Plaster alternatives for concrete. In reinforced con- 
crete construction, gypsum plaster or portland cement plaster is 
permitted to be substituted for i/ 2 inch (12.7 mm) of the 
required poured concrete protection, except that a minimum 
thickness of 3/ 8 inch (9.5 mm) of poured concrete shall be pro- 
vided in reinforced concrete floors and 1 inch (25 mm) in rein- 
forced concrete columns in addition to the plaster finish. The 
concrete base shall be prepared in accordance with Section 
2510.7. 



SECTION 719 
THERMAL- AND SOUND-INSULATING MATERIALS 

719.1 General. Insulating materials, including facings such as 
vapor retarders and vapor-permeable membranes, similar cov- 
erings and all layers of single and multilayer reflective foil 
insulations, shall comply with the requirements of this section. 
Where a flame spread index or a smoke-developed index is 
specified in this section, such index shall be determined in 
accordance with ASTM E 84 or UL 723. Any material that is 
subject to an increase in flame spread index or smoke-devel- 
oped index beyond the limits herein established through the 
effects of age, moisture or other atmospheric conditions shall 
not be permitted. 

Exceptions: 

1. Fiberboard insulation shall comply with Chapter 23. 

2. Foam plastic insulation shall comply with Chapter 26. 

3. Duct and pipe insulation and duct and pipe coverings 
and linings in plenums shall comply with the Interna- 
tional Mechanical Code. 

4. All layers of single and multilayer reflective plastic 
core insulation shall comply with Section 2613. 



719.2 Concealed installation. Insulating materials, where 
concealed as installed in buildings of any type of construction, 
shall have a flame spread index of not more than 25 and a 
smoke-developed index of not more than 450. 

Exception: Cellulose loose-fill insulation that is not spray 
applied, complying with the requirements of Section 719.6, 
shall only be required to meet the smoke-developed index of 
not more than 450. 

719.2.1 Facings. Where such materials are installed in con- 
cealed spaces in buildings of Type III, IV or V construction, 
the flame spread and smoke-developed limitations do not 
apply to facings, coverings, and layers of reflective foil 
insulation that are installed behind and in substantial contact 
with the unexposed surface of the ceiling, wall or floor fin- 
ish. 

Exception: All layers of single and multilayer reflective 
plastic core insulation shall comply with Section 2613. 

719.3 Exposed installation. Insulating materials, where 
exposed as installed in buildings of any type of construction, 
shall have a flame spread index of not more than 25 and a 
smoke-developed index of not more than 450. 

Exception: Cellulose loose-fill insulation that is not spray 
applied complying with the requirements of Section 719.6 
shall only be required to meet the smoke-developed index of 
not more than 450. 

719.3.1 Attic floors. Exposed insulation materials installed 
on attic floors shall have a critical radiant flux of not less 
than 0.12 watt per square centimeter when tested in accor- 
dance with ASTM E 970. 

719.4 Loose-fill insulation. Loose-fill insulation materials 
that cannot be mounted in the ASTM E 84 or UL 723 apparatus 
without a screen or artificial supports shall comply with the 
flame spread and smoke-developed limits of Sections 719.2 
and 719.3 when tested in accordance with CAN/ULC S102.2. 

Exception: Cellulose loose-fill insulation shall not be 
required to be tested in accordance with CAN/ULC S 102.2, 
provided such insulation complies with the requirements of 
Section 719.2 or 719.3, as applicable, and Section 719.6. 

719.5 Roofinsulation. The use of combustible roof insulation 
not complying with Sections 719.2 and 719.3 shall be permit- 
ted in any type of construction provided it is covered with 
approved roof coverings directly applied thereto. 

719.6 Cellulose loose-fill insulation. Cellulose loose-fill insu- 
lation shall comply with CPSC 16 CFR, Part 1209 and CPSC 
16 CFR, Part 1404. Each package of such insulating material 
shall be clearly labeled in accordance with CPSC 16 CFR, Part 
1209 and CPSC 16 CFR, Part 1404. 

719.7 Insulation and covering on pipe and tubing. Insula- 
tion and covering on pipe and tubing shall have a flame spread 
index of not more than 25 and a smoke-developed index of not 
more than 450. 

Exception: Insulation and covering on pipe and tubing 
installed in plenums shall comply with the International 
Mechanical Code. 



124 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



SECTION 720 
PRESCRIPTIVE FIRE RESISTANCE 

720.1 General. The provisions of this section contain prescrip- 
tive details of fire-resistance-rated building elements, compo- 
nents or assemblies. The materials of construction listed in 
Tables 720.1 (1), 720.1 (2), and 720.1 (3) shall be assumed to 
have the fire-resistance ratings prescribed therein. Where 
materials that change the capacity for heat dissipation are 
incorporated into a fire-resistance-rated assembly, fire test 
results or other substantiating data shall be made available to 
the bUilding official to show that the required fire-resis- 
tance-rating time period is not reduced. 

720.1.1 Thickness of protective coverings. The thickness 
of fire-resistant materials required for protection of struc- 
tural members shall be not less than set forth in Table 
720.1 (1), except as modified in this section. The figures 
shown shall be the net thickness of the protecting materials 
and shall not include any hollow space in back of the protec- 
tion. 

720.1.2 Unit masonry protection. Where required, metal 
ties shall be embedded in bedjoints of unit masonry for pro- 
tection of steel columns. Such ties shall be as set forth in 
Table 720.1 (1) or be equivalent thereto. 

720.1.3 Reinforcement for cast-in-place concrete col- 
umn protection. Cast-in-place concrete protection for steel 
columns shall be reinforced at the edges of such members 
with wire ties of not less than 0. 18 inch (4.6 mm) in diameter 
wound spirally around the columns on a pitch of not more 
than 8 inches (203 mm) or by equivalent reinforcement. 

720.1.4 Plaster application. The finish coat is not required 
for plaster protective coatings where they comply with the 
design mix and thickness requirements of Tables 720.1 (1), 
720.1(2) and 720.1 (3). 

720.1.5 Bonded prestressed concrete tendons. For mem- 
bers having a single tendon or more than one tendon 
installed with equal concrete cover measured from the near- 
est surface, the cover shall not be less than that set forth in 
Table 720.1 (1). For members having multiple tendons 
installed with variable concrete cover, the average tendon 
cover shall not be less than that set forth in Table 720.1 (1), 
provided: 

1. The clearance from each tendon to the nearest 
exposed surface is used to determine the average 
cover. 

2. In no case can the clear cover for individual tendons 
be less than one-half of that set forth in Table 
720.1(1). A minimum cover of 3/ 4 inch (19.1 mm) for 
slabs and 1 inch (25 mm) for beams is required for any 
aggregate concrete. 

3. For the purpose of establishing a fire-resistance rat- 
ing, tendons having a clear covering less than that set 
forth in Table 720. 1(1) shall not contribute more than 
50 percent of the required ultimate moment capacity 
for members less than 350 square inches (0.226 m 2 ) in 
cross-sectional area and 65 percent for larger mem- 
bers. For structural design purposes, however, ten- 



dons having a reduced cover are assumed to be fully 
effective. 



SECTION 721 
CALCULATED FIRE RESISTANCE 

721.1 General. The provisions of this section contain proce- 
dures by which the fire resistance of specific materials or com- 
binations of materials is established by calculations. These 
procedures apply only to the information contained in this sec- 
tion and shall not be otherwise used. The calculated fire resis- 
tance of concrete, concrete masonry and clay masonry 
assemblies shall be permitted in accordance with ACI 
216.1/TMS 0216. The calculated/^ resistance of steel assem- 
blies shall be permitted in accordance with Chapter 5 of ASCE 
29. The calculated fire resistance of exposed wood members 
and wood decking shall be permitted in accordance with Chap- 
ter 16 of ANSI/AF&PA National Design Specification for 
Wood Construction (NDS). 

721.1.1 Definitions. The following words and terms shall, 
for the purposes of this chapter and as used elsewhere in this 
code, have the meanings shown herein. 

CERAMIC FIBER BLANKET. A mineral wool insula- 
tion material made of alumina-silica fibers and weighing 4 
to 10 pounds per cubic foot (pcf) (64 to 160 kg/m 3 ). 

CONCRETE, CARBONATE AGGREGATE. Concrete 
made with aggregates consisting mainly of calcium or mag- 
nesium carbonate, such as limestone or dolomite, and con- 
taining 40 percent or less quartz, chert or flint. 

CONCRETE, CELLULAR. A lightweight insulating 
concrete made by mixing a preformed foam with portland 
cement slurry and having a dry unit weight of approxi- 
mately 30 pcf (480 kg/m 3 ). 

CONCRETE, LIGHTWEIGHT AGGREGATE. Con- 
crete made with aggregates of expanded clay, shale, slag or 
slate or sintered fly ash or any natural lightweight aggregate 
meeting ASTM C 330 and possessing equivalent fire-resis- 
tance properties and weighing 85 to 115 pcf (1360 to 1840 
kg/m 3 ). 

CONCRETE, PERLITE. A lightweight insulating con- 
crete having a dry unit weight of approximately 30 pcf (480 
kg/m 3 ) made with perlite concrete aggregate. Perlite aggre- 
gate is produced from a volcanic rock which, when heated, 
expands to form a glass-like material of cellular structure. 

CONCRETE, SAND-LIGHTWEIGHT. Concrete made 
with a combination of expanded clay, shale, slag, slate, 
sintered fly ash, or any natural lightweight aggregate meet- 
ing ASTM C 330 and possessing equivalent fire-resistance 
properties and natural sand. Its unit weight is generally 
between 105 and 120 pcf (1680 and 1920 kg/m 3 ). 

CONCRETE, SILICEOUS AGGREGATE. Concrete 
made with normal-weight aggregates consisting mainly of 
silica or compounds other than calcium or magnesium car- 
bonate, which contains more than 40-percent quartz, chert 
or flint. 

(Section 721. 1.1, Definitions, continued on page 146) 



2009 INTERNATIONAL BUILDING CODE® 



125 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1(1) 

MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS 

FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS" 1 



STRUCTURAL 
PARTS TO BE 
PROTECTED 



ITEM 
NUMBER 



INSULATING MATERIAL USED 



MINIMUM THICKNESS OF 

INSULATING MATERIAL 

FOR THE FOLLOWING 

FIRE-RESISTANCE 

PERIODS (inches) 



4 
hour 



3 
hour 



2 
hour 



1 
hour 



1. Steel columns 
and all of primary 

trusses 



1-1.1 



1-1.2 



1-1.3 



1-1.4 



1-1.5 



1-1.6 



1-2.1 



1-3.1 



1-3.2 



1-3.3 



1-3.4 



1-4.1 



1-5.1 



1-6.1 



1-6.2 



1-6.3 



1-6.4 



Carbonate, lightweight and sand-lightweight aggregate concrete, members 6" x 6" or 
greater (not including sandstone, granite and siliceous gravel). a 



2V, 



IV, 



Carbonate, lightweight and sand-lightweight aggregate concrete, members ! 
greater (not including sandstone, granite and siliceous gravel), a 



IV, 



Carbonate, lightweight and sand-lightweight aggregate concrete, members 
12" x 12" or greater (not including sandstone, granite and siliceous gravel) .a 



Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 6" 
or greater .a 



x6" 



Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members ! 
or greater .a 



2V, 



Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 
12" x 12" or greater. a 



Clay or shale brick with brick and mortar fill. a 



4" hollow clay tile in two 2" layers; i/ 2 " mortar between tile and column; 3/ 8 " metal 
mesh 0.046" wire diameter in horizontalj pints; tile fill. a 



2" hollow clay tile; 3/ 4 " mortar between tile and column; 3/ 8 " metal mesh 0.046" wire 
diameter in horizontal joints; limestone concrete fill; a plastered with 3/ 4 " gypsum 
plaster. 



2" hollow clay tile with outside wire ties 0.08" diameter at each course of tile or 3/ 8 ' 
metal mesh 0.046" diameter wire in horizontalj oints; limestone or trap-rock 
concrete fill a extending 1" outside column on all sides. 



2" hollow clay tile with outside wire ties 0.08" diameter at each course of tile with or 
without concrete fill; 3/ 4 " mortar between tile and column. 



Cement plaster over metal lath wire tied to 3/ 4 " cold-rolled vertical channels with 

0.049" (No. 18 B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 

1:2 i/ 2 by volume, cement to sand. 



Vermiculite concrete, 1:4 mix by volume over paperbacked wire fabric lath wrapped 
directly around column with additional 2" x 2" 0.065 70.065" (No. 16/16 B.W. gage) 
wire fabric placed 3/ 4 " from outer concrete surface. Wire fabric tied with 0.049" (No. 
18 B.W. gage) wire spaced 6" on center for inner layer and 2" on center for outer 
layer. 



Perlite or vermiculite gypsum plaster over metal lath wrapped around column and 
furred l 1 / 4 " from column flanges. Sheets lapped at ends and tied at 6" intervals with 
0.049" (No. 18 B.W. gage) tie wire. Plaster pushed through to flanges. 



lV, 



Perlite or vermiculite gypsum plaster over self-furring metal lath wrapped directly 
around column, lapped 1" and tied at 6" intervals with 0.049" (No. 18 B.W. gage) 
wire. 



l 3 /4 



Perlite or vermiculite gypsum plaster on metal lath applied to 3/ 4 " cold-rolled 
channels spaced 24" apart vertically and wrapped flatwise around column. 



IV, 



Perlite or vermiculite gypsum plaster over two layers of i/ 2 " plain full-length gypsum 
lath applied tight to column flanges. Lath wrapped with 1" hexagonal mesh of No. 
20 gage wire and tied with doubled 0.035" diameter (No. 18 B.W. gage) wire ties 
spaced 23" on center. For three-coat work, the plaster mix for the second coat shall 
not exceed 100 pounds of gypsum to 2 l / 2 cubic feet of aggregate for the 3-hour 
system. 



2V, 



(continued) 



126 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (1 )--continued 

MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS 

FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS" 1 



STRUCTURAL 
PARTS TO BE 
PROTECTED 



ITEM 
NUMBER 



INSULATING MATERIAL USED 



MINIMUM THICKNESS OF 

INSULATING MATERIAL 

FOR THE FOLLOWING 

FIRE-RESISTANCE 

PERIODS (inches) 

A 3 2 1 

hour hour hour hour 



1-6.5 



Perlite or vermiculate gypsum plaster over one layer of i/ 2 " plain full-length gypsum 
lath applied tight to column flanges. Lath tied with doubled 0.049" (No. 18 B.W. 
gage) wire ties spaced 23" on center and scratch coat wrapped with 1" hexagonal 
mesh 0.035" (No. 20 B.W. gage) wire fabric. For three-coat work, the plaster mix for 
the second coat shall not exceed 100 pounds of gypsum to 2h 2 cubic feet of 
aggregate. 



1-7.1 



Multiple layers of i/ 2 " gypsum wallboard c adhesivelyd secured to column flanges and 
successive layers. Wallboard applied without horizontal joints. Corner edges of each 
layer staggered. Wallboard layer below outer layer secured to column with doubled 
0.049" (No. 18 B.W. gage) steel wire ties spaced 15" on center. Exposed corners 
taped and treated. 



1-7.2 



Three layers of 5/ s " Type X gypsum wallboard. First and second layer held in place 
by i/ s " diameter by l 3 / s " long ring shank nails with 5/ 16 " diameter heads spaced 24" 
on center at corners. Middle layer also secured with metal straps at mid-height and 
18" from each end, and by metal corner bead at each corner held by the metal straps. 
Third layer attached to corner bead with 1" long gypsum wallboard screws spaced 
12" on center. 



i% 



1. Steel columns 
and all of 
primary trusses 
(continued) 



1-7.3 



Three layers of 5/ s " Type X gypsum wallboard,c each layer screw attached to l 5 / s " 
steel studs 0.018" thick (No. 25 carbon sheet steel gage) at each corner of column. 
Middle layer also secured with 0.049" (No. 18 B.W. gage) double-strand steel wire 
ties, 24" on center. Screws are No. 6 by 1" spaced 24" on center for inner layer, No. 
6 by l 5 / s " spaced 12" on center for middle layer and No. 8 by 2 1 / 4 " spaced 12" on 
center for outer layer. 



l 7 /. 



1-8.1 



Wood-fibered gypsum plaster mixed 1:1 by weight gypsum-to-sand aggregate 
applied over metal lath. Lath lapped 1" and tied 6" on center at all end, edges and 
spacers with 0.049" (No. 18 B.W. gage) steel tie wires. Lath applied over i/ 2 " spacers 
made of 3/ 4 " furring channel with 2" legs bent around each corner. Spacers located 1" 
from top and bottom of member and a maximum of 40" on center and wire tied with 
a single strand of 0.049" (No. 18 B.W. gage) steel tie wires. Corner bead tied to the 
lath at 6" on center along each corner to provide plaster thickness. 



P/, 



1-9.1 



Minimum W8x35 wide flange steel column (w/d > 0.75) with each web cavity filled 
even with the flange tip with normal weight carbonate or siliceous aggregate 
concrete (3,000 psi minimum compressive strength with 145 pcf ± 3 pcf unit 
weight). Reinforce the concrete in each web cavity with a minimum No. 4 deformed 
reinforcing bar installed vertically and centered in the cavity, and secured to the 
column web with a minimum No . 2 horizontal deformed reinforcing bar welded to 
the web every 18" on center vertically. As an alternative to the No. 4 rebar, 3/ 4 " 
diameter by 3" long headed studs, spaced at 12" on center vertically, shall be welded 
on each side of the web midway between the column flanges. 



See 

Note 

n 



2. Webs or 
flanges of 
steel beams and 
girders 



2-1.1 



2-1.2 



Carbonate, lightweight and sand-lightweight aggregate concrete (not including 
sandstone, granite and siliceous gravel) with 3" or finer metal mesh placed 1" from 
the finished surface anchored to the top flange and providing not less than 0.025 
square inch of steel area per foot in each direction. 

Siliceous aggregate concrete and concrete excluded in Item 2-1.1 with 3" or finer 
metal mesh placed 1" from the finished surface anchored to the top flange and 
providing not less than 0.025 square inch of steel area per foot in each direction. 



IV, 



2 1 /, 



1% 



2-2.1 



Cement plaster on metal lath attached to 3/ 4 " cold-rolled channels with 0.04" (No. 18 
B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 1:2 i/ 2 by volume, 
cement to sand. 



2V 2 b 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



127 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (1 )--continued 

MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS 

FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS" 1 









MINIMUM THICKNESS OF 








INSULATING MATERIAL 








FOR THE FOLLOWING 








FIRE-RESISTANCE 


STRUCTURAL 
PARTS TO BE 


ITEM 




PERIODS (inches) 


4 


3 


2 


1 


PROTECTED 


NUMBER 


INSULATING MATERIAL USED 


hour 


hour 


hour 


hour 






Vermiculite gypsum plaster on a metal lath cage, wire tied to 0.165" diameter (No. 8 












2-3.1 


B.W. gage) steel wire hangers wrapped around beam and spaced 16" on center. 
Metal lath ties spaced approximately 5" on center at cage sides and bottom. 


- 


7/ 8 


- 


- 




Two layers of 5/ 8 " Type X gypsum wallboard c are attached to U-shaped brackets 














spaced 24" on center. 0.018" thick (No. 25 carbon sheet steel gage) l 5 / 8 " deep by 1" 














galvanized steel runner channels are first installed parallel to and on each side of the 














top beam flange to provide a i/ 2 " clearance to the flange. The channel runners are 














attached to steel deck or concrete floor construction with approved fasteners spaced 














12" on center. U-shaped brackets are formed from members identical to the channel 














runners. At the bent portion of the U-shaped bracket, the flanges of the channel are 














cut out so that l 5 / 8 " deep corner channels can be inserted without attachment parallel 














to each side of the lower flange. 












2-4.1 


As an alternate, 0.021" thick (No. 24 carbon sheet steel gage) l"x 2" runner and 






I 1 /, 






corner angles may be used in lieu of channels, and the web cutouts in the U-shaped 






i M 








brackets may be omitted. Each angle is attached to the bracket with i/ 2 "-long No. 8 










2. Webs or 




self-drilling screws. The vertical legs of the U-shaped bracket are attached to the 










flanges of steel 




runners with one i/ 2 " long No. 8 self-drilling screw. The completed steel framing 










beams and 




provides a 2 1 / 8 " and l 1 / 2 '' space between the inner layer of wallboard and the sides 










girders 




and bottom of the steel beam, respectively. The inner layer of wallboard is attached 










(continued) 




to the top runners and bottom corner channels or corner angles with l 1 / 4 "-long No. 6 
self-drilling screws spaced 16" on center. The outer layer of wallboard is applied 
with l 3 / 4 "-long No. 6 self-drilling screws spaced 8" on center. The bottom corners 
are reinforced with metal corner beads. 












Three layers of 5/ 8 " Type X gypsum wallboard attached to a steel suspension system 














as described immediately above utilizing the 0.018" thick (No. 25 carbon sheet steel 














gage) 1" x 2" lower corner angles. The framing is located so that a 2 1 / 8 " and 2" space 














is provided between the inner layer of wallboard and the sides and bottom of the 














beam, respectively. The first two layers of wallboard are attached as described 












2-4.2 


immediately above. A layer of 0.035" thick (No. 20 B.W. gage) 1" hexagonal 




l 7 /« 








galvanized wire mesh is applied under the soffit of the middle layer and up the sides 




x ' 8 










approximately 2". The mesh is held in position with the No. 6 l 5 / 8 "-long screws 














installed in the vertical leg of the bottom corner angles. The outer layer of wallboard 














is attached with No. 6 2 1 / 4 "-long screws spaced 8" on center. One screw is also 














installed at the mid-depth of the bracket in each layer. Bottom corners are finished as 














described above. 










3. Bonded 




Carbonate, lightweight, sand-lightweight and siliceous f aggregate concrete 


4§ 


3 g 


2 1 /, 


1V 2 


pretensioned 




Beams or girders 


z, / 2 


reinforcement in 


3-1.1 












prestressed 








2 


l 1 /, 


1 


concrete e 




Solid slabs 11 






x ' 2 






Carbonate, lightweight, sand-lightweight and siliceous f aggregate concrete 














Unrestrained members: 












4-1.1 


Solid slabs' 1 


- 


2 


1V 2 


- 


4. Bonded or 




Beams and girders^ 










unbonded 




8" wide 




4V 2 


2V 2 


1% 


post-tensioned 
tendons in 




greater than 12" wide 


3 


2 1 /? 


2 


l 1 /? 




Carbonate, lightweight, sand-lightweight and siliceous aggregate 










prestressed 




Restrained members: k 










concretee,i 


4-1.2 


Solid slabs' 1 
Beams and girder^ 


iv 4 


1 


3/ 4 








8" wide 


2V 2 


2 


1% 








greater than 12" wide 


2 


l 3 / 4 


l 1 /? 


- 



(continued) 



128 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (1 )--continued 

MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS 

FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS" 1 



STRUCTURAL 
PARTS TO BE 
PROTECTED 


ITEM 
NUMBER 


INSULATING MATERIAL USED 


MINIMUM THICKNESS OF 

INSULATING MATERIAL 

FOR THE FOLLOWING 

FIRE-RESISTANCE 

PERIODS (inches) 


4 
hour 


3 
hour 


2 
hour 


1 

hour 


5. Reinforcing 
steel in reinforced 
concrete columns, 
beams girders and 
trusses 


5-1.1 


Carbonate, lightweight and sand-lightweight aggregate concrete, members 12" or 
larger, square or round. (Size limit does not apply to beams and girders monolithic 
with floors.) 

Siliceous aggregate concrete, members 12" or larger, square or round. (Size limit 
does not apply to beams and girders monolithic with floors.) 


1V 2 

2 


1V 2 
1V 2 




1V 2 
1V 2 


6. Reinforcing 
steel in reinforced 
concrete joists 1 


6-1.1 
6-1.2 


Carbonate, lightweight and sand-lightweight aggregate concrete. 
Siliceous aggregate concrete. 


1V 4 

1^4 


l'/4 

1V 2 


1 
1 


3/ 4 


7. Reinforcing and 
tie rods in floor 
and roof slabs 1 


7-1.1 

7-1.2 


Carbonate, lightweight and sand-lightweight aggregate concrete. 
Siliceous aggregate concrete. 


1 

1''4 


1 
1 


^4 
1 


3/4 

3/ 4 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm z , 1 cubic foot = 0.0283 m 3 , 1 pound per cubic foot = 16.02 kg/m 3 - 

a. Reentrant parts of protected members to be filled solidly. 

b. Two layers of equal thickness with a 3/ 4 -inch airspace between. 

c. For all of the construction with gypsum wallboard described in Table 720.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall be 
permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard and thejoints on the face layer are reinforced, 
and the entire surface is covered with a minimum of i/ 16 -inch gypsum veneer plaster. 

d. An approved adhesive qualified under ASTM E 119 or UL 263. 

e. Where lightweight or sand-lightweight concrete having an oven-dry weight of 1 10 pounds per cubic foot or less is used, the tabulated minimum cover shall be per- 
mitted to be reduced 25 percent, except that in no case shall the cover be less than 3/ 4 inch in slabs or l 1 /^ inches in beams or girders. 

f. For solid slabs of siliceous aggregate concrete, increase tendon cover 20 percent. 

g. Adequate provisions against spalling shall be provided by U-shaped or hooped stirrups spaced not to exceed the depth of the member with a clear cover of 1 inch, 
h. Prestressed slabs shall have a thickness not less than that required in Table 720.1 (3) for the respective fire -resistance time period. 

i . Fire coverage and end anchorages shall be as follows: Cover to the prestressing steel at the anchor shall be //zinch greater than that required away from the anchor. 
Minimum cover to steel-bearing plate shall be 1 inch in beams and 3/ 4 inch in slabs. 

j . For beam widths between 8 inches and 12 inches, cover thickness shall be permitted to be determined by interpolation. 

k. Interior spans of continuous slabs, beams and girders shall be permitted to be considered restrained. 

1. For use with concrete slabs having a comparable fire endurance where members are framed into the structure in such a manner as to provide equivalent perfor- 
mance to that of monolithic concrete construction. 

m. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in GA 600 shall be accepted as if herein listed. 

n. No additional insulating material is required on the exposed outside face of the column flange to achieve a I-hour fire-resistance rating. 



2009 INTERNATIONAL BUILDING CODE® 



129 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (2) 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a,a, 


p 








MATERIAL 


ITEM 
NUMBER 


CONSTRUCTION 


MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 

hour 


1. Brick of clay or 
shale 


1-1.1 


Solid brick of clay or shale - 


6 


4.9 


3.8 


2.7 


1-1.2 


Hollow brick, not filled. 


5.0 


4.3 


3.4 


2.3 


1-1.3 


Hollow brick unit wall, grout or filled with perlite vermiculite or expanded shale 
aggregate. 


6.6 


5.5 


4.4 


3.0 


1-2.1 


4" nominal thick units at least 75 percent solid backed with a hat-shaped metal 
furring channel 3/ 4 " thick formed from 0.021" sheet metal attached to the brick 
wall on 24" centers with approved fasteners , and i/ 2 " Type X gypsum wallboard 
attached to the metal furring strips with l"-long Type S screws spaced 8" on 
center. 






5d 




2. Combination of 
clay brick and 
load-bearing 
hollow clay tile 


2-1.1 


4" solid brick and 4" tile (at least 40 percent solid) . 




8 






2-1.2 


4" solid brick and 8" tile (at least 40 percent solid) . 


12 


- 


- 


- 


3. Concrete 
masonry units 


3-l.lf.g 


Expanded slag or pumice. 


4.7 


4.0 


3.2 


2.1 


3-1.2f, g 


Expanded clay, shale or slate . 


5.1 


4.4 


3.6 


2.6 


3-1.3 f 


Limestone, cinders or air-cooled slag. 


5.9 


5.0 


4.0 


2.7 


3-1.4f, g 


Calcareous or siliceous gravel. 


6.2 


5.3 


4.2 


2.8 


4. Solid concrete 11 ,! 


4-1.1 


Siliceous aggregate concrete. 


7.0 


6.2 


5.0 


3.5 


Carbonate aggregate concrete. 


6.6 


5.7 


4.6 


3.2 


Sand-lightweight concrete. 


5.4 


4.6 


3.8 


2.7 


Lightweight concrete. 


5.1 


4.4 


3.6 


2.5 


5. Glazed or 
unglazed facing 
tile, nonload- 
bearing 


5-1.1 


One 2" unit cored 15 percent maximum and one 4" unit cored 25 percent 
maximum with 3/ 4 " mortar-filled collar joint. Unit positions reversed in alternate 
courses. 




6 3 / 8 






5-1.2 


One 2" unit cored 15 percent maximum and one 4" unit cored 40 percent 
maximum with 3/ 4 " mortar-filled collarjoint. Unit positions side with 3/ 4 " gypsum 
plaster. Two wythes tied together every fourth course with No . 22 gage 
corrugated metal ties. 


- 


6 3 / 4 


- 


- 


5-1.3 


One unit with three cells in wall thickness, cored 29 percent maximum. 


- 


- 


6 


- 


5-1.4 


One 2" unit cored 22 percent maximum and one 4" unit cored 41 percent 
maximum with i/ 4 " mortar-filled collarjoint. Two wythes tied together every 
third course with 0.030" (No. 22 galvanized sheet steel gage) corrugated metal 
ties. 






6 




5-1.5 


One 4" unit cored 25 percent maximum with 3/ 4 " gypsum plaster on one side. 






4% 




5-1.6 


One 4" unit with two cells in wall thickness, cored 22 percent maximum. 


- 


- 


- 


4 


5-1.7 


One 4" unit cored 30 percent maximum with 3/ 4 " vermiculite gypsum plaster on 
one side. 


- 


- 


4>/ 2 


- 


5-1.8 


One 4" unit cored 39 percent maximum with 3/ 4 " gypsum plaster on one side. 


- 


- 


- 


4V 2 



(continued) 



130 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a,a, 


p 








MATERIAL 


ITEM 
NUMBER 


CONSTRUCTION 


MINIMUM FINISHED 

THICKNESS 

FACE-TO-FACE b 

(inches) 


4 
hour 


3 
hour 


2 
hour 


l 
hour 


6. Solid gypsum 
plaster 


6-1.1 


3/ 4 " by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16" 
on center with 2.6-pound flat metal lath applied to one face and tied with 0.049" 
(No. 18 B.W. Gage) wire at 6" spacing. Gypsum plaster each side mixed 1:2 by 
weight, gypsum to sand aggregate. 








2 d 


6-1.2 


3/ 4 " by 0.05" (No. 16 carbon sheet steel gage) cold-rolled channels 16" on center 
with metal lath applied to one face and tied with 0.049" (No. 18 B.W. gage) wire 
at 6" spacing. Perlite or vermiculite gypsum plaster each side. For three-coat 
work, the plaster mix for the second coat shall not exceed 100 pounds of gypsum 
to 2h 2 cubic feet of aggregate for the I-hour system. 


- 


- 


2 7 // 


2 d 


6-1.3 


3/ 4 " by 0.055" (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 16" 
on center with 3/ 8 " gypsum lath applied to one face and attached with sheet metal 
clips. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate. 








2 d 


6-2.1 


Studless with i/ 2 " full-length plain gypsum lath and gypsum plaster each side. 
Plaster mixed 1: 1 for scratch coat and 1:2 for brown coat, by weight, gypsum to 
sand aggregate. 


- 


- 


- 


2 d 


6-2.2 


Studless with i/ 2 " full-length plain gypsum lath and perlite or vermiculite gypsum 
plaster each side. 


- 


- 


2V 


2 d 


6-2.3 


Studless partition with 3/ 8 " rib metal lath installed vertically adjacent edges tied 
6" on center with No. 18 gage wire ties, gypsum plaster each side mixed 1:2 by 
weight, gypsum to sand aggregate. 








2 d 


7. Solid perlite 
and portland 
cement 


7-1.1 


Perlite mixed in the ratio of 3 cubic feet to 100 pounds of portland cement and 
machine applied to stud side of 1i L / 2 n mesh by 0.OS8-inch (No. 17 B.W. gage) 
paper-backed woven wire fabric lath wire-tied to 4" -deep steel trussed wire^ studs 
16" on center. Wire ties of 0.049" (No. 18 B.W. gage) galvanized steel wire 6" on 
center vertically. 


- 


- 


J / 8 


- 


8. Solid neat wood 
fibered gypsum 
plaster 


8-1.1 


3/ 4 " by QOSS-inch (No. 16 carbon sheet steel gage) cold-rolled channels, 12" on 
center with 2. S -pound flat metal lath applied to one face and tied with 0.049" 
(No. 18 B.W. gage) wire at 6" spacing. Neat gypsum plaster applied each side. 






2 d 




9. Solid wallboard 
partition 


9-1.1 


One full-length layer i/ 2 " Type X gypsum wallboard 6 laminated to each side of 1" 
full-length V-edge gypsum coreboard with approved laminating compound. 
Vertical joints of face layer and coreboard staggered at least 3". 






2 d 




10. Hollow 
(studless) gypsum 
wallboard 
partition 


10-1.1 


One full-length layer of 5/ 8 " Type X gypsum wallboard 6 attached to both sides of 
wood or metal top and bottom runners laminated to each side of 1" x 6" 
full-length gypsum coreboard ribs spaced 2" on center with approved laminating 
compound. Ribs centered at vertical joints of face plies andjoints staggered 24" 
in opposing faces. Ribs may be recessed 6" from the top and bottom. 


- 


- 


- 


2V 


10-1.2 


1" regular gypsum V-edge full-length backing board attached to both sides of 
wood or metal top and bottom runners with nails or 1 5 / 8 " drywall screws at 24" 
on center. Minimum width of rumors 1 5 / 8 " . Face layer of n 2 " regular full-length 
gypsum wallboard laminated to outer faces of backing board with approved 
laminating compound. 






4V 





(continued) 



2009 INTERNATIONAL BUILDING CODE® 



131 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a,a, 


p 








MATERIAL 


ITEM 
NUMBER 


CONSTRUCTION 


MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


11. Noncombustible 
studs-interior 
partition with plaster 
each side 


11-1.1 


3%" x 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 24" on center. 
5/ 8 " gypsum plaster on metal lath each side mixed 1:2 by weight, gypsum to 
sand aggregate. 








4 3 // 


11-1.2 


3v§" x 0.055" (No. 16 carbon sheet steel gage) approved nailable k studs spaced 
24" on center. 5/ 8 " neat gypsum wood-fibered plaster each side over 3/ 8 " rib 
metal lath nailed to studs with 6d common nails, 8" on center. Nails driven 
/%" and bent over. 


- 


- 


&8 


- 


11-1.3 


4" x 0.044" (No. 18 carbon sheet steel gage) channel- shaped steel studs at 16" 
on center. On each side approved resilient clips pressed onto stud flange at 16" 
vertical spacing, i/ 4 " pencil rods snapped into or wire tied onto outer loop of 
clips, metal lath wire-tied to pencil rods at 6" intervals, 1" perlite gypsum 
plaster, each side. 




7%« 






11-1.4 


2V 2 " x 0.044" (No. 18 carbon sheet steel gage) steel studs spaced 16" on center. 
Wood fibered gypsum plaster mixed 1: 1 by weight gypsum to sand aggregate 
applied on 3 / 4 -pound metal lath wire tied to studs, each side. 3/ 4 " plaster applied 
over each face, including finish coat. 


- 


- 


4 1 // 


- 


12. Wood studs 
interior partition 
with plaster each 
side 


12-1.11, m 


2" x 4" wood studs 16" on center with 5/ 8 " gypsum plaster on metal lath. Lath 
attached by 4d common nails bent over or No. 14 gage by 7 7 / 4 " by 31 4 n crown 
width staples spaced 6" on center. Plaster mixed /:/ l / 2 for scratch coat and 1:3 
for brown coat, by weight, gypsum to sand aggregate. 








5\ 


12-1.21 


2" x 4" wood studs 16" on center with metal lath and 7/ 8 " neat wood-fibered 
gypsum plaster each side. Lath attached by 6d common nails, 7" on center. 
Nails driven P/4" and bent over. 


- 


- 


5V 


- 


12-1.31 


2" x 4" wood studs 16" on center with 3/ 8 " perforated or plain gypsum lath and 
i/ 2 " gypsum plaster each side. Lath nailed with P/g" by No. 13 gage by 19 / M " 
head plasterboard blued nails, 4" on center. Plaster mixed 1:2 by weight, 
gypsum to sand aggregate. 


- 


- 


- 


5% 


12-1.41 


2" x 4" wood studs 16" on center with J 8 " Type X gypsum lath and i/ 2 " gypsum 
plaster each side. Lath nailed with 1 1 / 8 " by No. 13 gage by 19 / M " head 
plasterboard blued nails, S" on center. Plaster mixed 1:2 by weight, gypsum to 
sand aggregate. 








5% 


1 3 .Noncombustible 
studs -interior 
partition with 
gypsum wallboard 
each side 


13-1.1 


0.018" (No. 25 carbon sheet steel gage) channel- shaped studs 24" on center 
with one full-length layer of 5/ 8 Type X gypsum wallboard 6 applied vertically 
attached with 1" long No. 6 drywall screws to each stud. Screws are 8" on 
center around the perimeter and 12" on center on the intermediate stud. The 
wallboard may be applied horizontally when attached to 3 5 / 8 " studs and the 
horizontal joints are staggered with those on the opposite side. Screws for the 
horizontal application shall be 8" on center at vertical edges and 12" on center 
at intermediate studs. 


- 


- 


- 


2V 


13-1.2 


0.018" (No. 25 carbon sheet steel gage) channel-shaped studs 25" on center 
with two full-length layers of i/ 2 " Type X gypsum wallboard 6 applied vertically 
each side. First layer attached with l"-long, No. 6 drywall screws, 8" on center 
around the perimeter and 12" on center on the intermediate stud. Second layer 
applied with vertical joints offset one stud space from first layer using 1 5 / 8 " 
long, No. 6 drywall screws spaced 9" on center along verticaljoints, 12" on 
center at intermediate studs and 24" on center along top and bottom runners . 


- 


- 


3V 


- 


13-1.3 


0.055" (No. 16 carbon sheet steel gage) approved nailable metal studs 6 24" on 
center with full-length 5/ 8 " Type X gypsum wallboard 6 applied vertically and 
nailed 7" on center with 6d cement-coated common nails. Approved metal 
fastener grips used with nails at vertical butt joints along studs. 








4 ? /8 



(continued) 



132 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a )£ 


i,p 








MATERIAL 


ITEM 
NUMBER 


CONSTRUCTION 


MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


14. Wood 
studs -interior 
partition with 
gypsum wallboard 
each side 


14-1. ln,m 


2" x 4" wood studs 16" on center with two layers of 3/ s " regular gypsum 
wallboard 6 each side, 4d cooler 11 or wallboard 11 nails at 8" on center first layer, 5d 
cooler 11 or wallboard 11 nails at 8" on center second layer with laminating 
compound between layers, joints staggered. First layer applied full length 
vertically, second layer applied horizontally or vertically. 








5 


14-1.21,m 


2" x 4" wood studs 16" on center with two layers V 2 ' regular gypsum wallboard 6 
applied vertically or horizontally each side k , joints staggered. Nail base layer 
with 5d cooler 11 or wallboard 11 nails at 8" on center face layer with 8d cooler 11 or 
wallboard 11 nails at 8" on center. 


- 


- 


- 


5h 2 


14-1.31, m 


2" x 4" wood studs 24" on center with sis" Type X gypsum wallboard 6 applied 
vertically or horizontally nailed with 6d cooler 11 or wallboard 11 nails at 7" on 
renter with end joints; on nailing members Staggerjnints; earn side 








4 3 U 


14-1.4 1 


2" x 4" fire-retardant-treated wood studs spaced 24" on center with one layer of 
sis" Type X gypsum wallboard 6 applied with face paper grain (long dimension) 
parallel to studs. Wallboard attached with 6d cooler 11 or wallboard 11 nails at 7" on 
center. 


- 


- 


- 


4 3 / 4 d 


14-1.51, m 


2" x 4" wood studs 16" on center with two layers Sis" Type X gypsum 
wallboard 6 each side. Base layers applied vertically and nailed with 6d cooler 11 
or wallboard 11 nails at 9" on center. Face layer applied vertically or horizontally 
and nailed with 8d cooler 11 or wallboard 11 nails at 7" on center. For nail-adhesive 
application, base layers are nailed 6" on center. Face layers applied with coating 
of approved wallboard adhesive and nailed 12" on center. 






6 




14-1.6 1 


2" x 3" fire-retardant-treated wood studs spaced 24" on center with one layer of 
Sis" Type X gypsum wallboard 6 applied with face paper grain (long dimension) 
at right angles to studs. Wallboard attached with 6d cement-coated box nails 
spaced 7" on center. 


- 


- 


- 


&d 


15 . Exterior or 
interior walls 


15-1.11, m 


Exterior surface with 3i 4 " drop siding over i/ 2 " gypsum sheathing on 2" x 4" 
wood studs at 16" on center, interior surface treatment as required for 
I-hour-rated exterior or interior 2" x 4" wood stud partitions. Gypsum sheathing 
nailed with 1 3 / 4 " by No. 11 gage by 7i 16 " head galvanized nails at 8" on center. 
Siding nailed with 7d galvanized smooth box nails. 








Varies 


15-1.21,m 


2" x 4" wood studs 16" on center with metal lath and 3/ 4 " cement plaster on each 
side. Lath attached with 6d common nails 7" on center driven to 1" minimum 
penetration and bent over. Plaster mix 1:4 for scratch coat and 1:5 for brown 
coat, by volume, cement to sand. 


- 


- 


- 


?'s 


15-1.31,m 


2" x 4" wood studs 16" on center with 7is" cement plaster (measured from the 
face of studs) on the exterior surface with interior surface treatment as required 
for interior wood stud partitions in this table . Plaster mix 1 :4 for scratch coat and 
1:5 for brown coat, by volume, cement to sand. 








Varies 


15-1.4 


3^/s" No. 16 gage noncombustible studs 16" on center with 71 s" cement plaster 
(measured from the face of the studs) on the exterior surface with interior 
surface treatment as required for interior, nonbearing, noncombustible stud 
partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, 
by volume, cement to sand. 


- 


- 


- 


Varies d 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



133 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a,o, P 



MATERIAL 



ITEM 
NUMBER 



CONSTRUCTION 



MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 



4 
hour 



3 
hour 



2 
hour 



1 
hour 



15-1.5 n 



2 1 / 4 " x $/ 4 " clay face brick with cored holes over n 2 " gypsum sheathing on 
exterior surface of 2" x 4" wood studs at 16" on center and two layers 5/ 8 " Type 
X gypsum wallboard 6 on interior surface. Sheathing placed horizontally or 
vertically with vertical joints over studs nailed 6" on center with 1 3 / 4 " x No. 11 
gage by 7/ 16 " head galvanized nails. Inner layer of wallboard placed horizontally 
or vertically and nailed 8" on center with 6d cooler" or wallboard" nails. Outer 
layer of wallboard placed horizontally or vertically and nailed 8" on center with 
8d cooler" or wallboard" nails. All joints staggered with vertical joints over 
studs. Outer layer joints taped and finished with compound. Nail heads covered 
with joint compound. 0.035 inch (No. 20 galvanized sheet gage) corrugated 
galvanized steel wall ties 3/ 4 " by 6 5 / 8 " attached to each stud with two 8d cooler" 
or wallboard" nails every sixth course of bricks. 



15-1.61, m 



2" x 6" fire-retardant-treated wood studs 16" on center. Interior face has two 
layers of 5/ 8 " Type X gypsum with the base layer placed vertically and attached 
with 6d box nails 12" on center. The face layer is placed horizontally and 
attached with 8d box nails 8" on center at joints and 12" on center elsewhere. 
The exterior face has a base layer of 5/ 8 " Type X gypsum sheathing placed 
vertically with 6d box nails 8" on center at joints and 12" on center elsewhere. 
An approved building paper is next applied, followed by self- furred exterior lath 
attached with 2 1 / 2 ", No. 12 gage galvanized roofing nails with a 3i 8 " diameter 
head and spaced 6" on center along each stud. Cement plaster consisting of a i/ 2 " 
brown coat is then applied. The scratch coat is mixed in the proportion of 1:3 by 
weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of 
approved additives or admixtures per sack of cement. The brown coat is mixed 
in the proportion of 1:4 by weight, cement to sand with the same amounts of 
hydrated lime and approved additives or admixtures used in the scratch coat. 



15. Exterior or 
interior walls 
(continued) 



15-1.71, m 



2" x 6" wood studs 16" on center. The exterior face has a layer of 5/ 8 " Type X 
gypsum sheathing placed vertically with 6d box nails 8" on center at joints and 
12" on center elsewhere. An approved building paper is next applied, followed 
by 1" by No. 18 gage self- furred exterior lath attached with 8d by 2 i / 2 " long 
galvanized roofing nails spaced 6" on center along each stud. Cement plaster 
consisting of alh" scratch coat, a bonding agent and alh" brown coat and a 
finish coat is then applied. The scratch coat is mixed in the proportion of 1:3 by 
weight, cement to sand with 10 pounds of hydrated lime and 3 pounds of 
approved additives or admixtures per sack of cement. The brown coat is mixed 
in the proportion of 1:4 by weight, cement to sand with the same amounts of 
hydrated lime and approved additives or admixtures used in the scratch coat. 
The interior is covered with 3/ 8 " gypsum lath with 1" hexagonal mesh of 0.035 
inch (No. 20 B.W. gage) woven wire lath furred out 5/ 16 " and 1" perlite or 
vermiculite gypsum plaster. Lath nailed with /%" by No. 13 gage by 19 / 64 " head 
plasterboard glued nails spaced 5" on center. Mesh attached by 1 3 / 4 " by No. 12 
gage by 3/ 8 " head nails with 3/ 8 " furrings, spaced 8" on center. The plaster mix 
shall not exceed 100 pounds of gypsum to 2 7? cubic feet of aggregate. 



15-1.81, n 



2" x 6" wood studs 16" on center. The exterior face has a layer of 5/ 8 " Type X 
gypsum sheathing placed vertically with 6d box nails 8" on center at joints and 
12" on center elsewhere. An approved building paper is next applied, followed 
by V/f by No. 17 gage self-furred exterior lath attached with 8d by 2 1 / 2 " long 
galvanized roofing nails spaced 6" on center along each stud. Cement plaster 
consisting of alh" scratch coat, and alh" brown coat is then applied. The 
plaster may be placed by machine. The scratch coat is mixed in the proportion of 
1:4 by weight, plastic cement to sand. The brown coat is mixed in the proportion 
of 1:5 by weight, plastic cement to sand. The interior is covered with 3/ 8 
gypsum lath with 1" hexagonal mesh of No. 20 gage woven wire lath furred out 
5/ 16 " and 1" perlite or vermiculite gypsum plaster. Lath nailed with 7%" by No. 
13 gage by l9 /^" head plasterboard glued nails spaced 5" on center. Mesh 
attached by 1 3 / 4 " by No. 12 gage by 3i 8 " head nails with 3/ 8 " furrings, spaced 8" 
on center. The plaster mix shall not exceed 100 pounds of gypsum to 2 1 i 2 cubic 
feet of aggregate. 



10 



#/, 



#/, 



{continued) 



134 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a.a.p 



ITEM 
NUMBER 



CONSTRUCTION 



MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 

4 hour 3 hour 2 hour 1 hour 



15-1.9 



4" No. 18 gage, nonload-bearing metal studs, 16" on center, with I" portland 
cement lime plaster [measured from the back side of the 3/^-pound expanded 
metal lath] on the exterior surface. Interior surface to be covered with 1" of 
gypsum plaster on 3/4-pound expanded metal lath proportioned by weight- 1 :2 
for scratch coat, 1:3 for brown, gypsum to sand. Lath on one side of the partition 
fastened to II4" diameter pencil rods supported by No. 20 gage metal clips, 
located 16" on center vertically, on each stud. 3" thick mineral fiber insulating 
batts friction fitted between the studs. 



15-1.10 



Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, with liz" Glass Fiber 
Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex 
anchors at 24" on center, with 5" leg welded to studs with two l/ z "-long 
flare-bevel welds, and 4" foot attached to the GFRC skin with Sis" thick GFRC 
bonding pads that extend 2ht beyond the flex anchor foot on both sides. Interior 
surface to have two layers of liz" Type X gypsum wallboard. 6 The first layer of 
wallboard to be attached with l"-long Type S buglehead screws spaced 24" on 
center and the second layer is attached with P/ s "-long Type S screws spaced at 
12" on center. Cavity is to be filled with 5" of 4 pcf (nominal) mineral fiber batts. 
GFRC has / y~" returns packed with mineral fiber and caulked on the exterior. 



15-1.11 



15. Exterior or 
interior walls 
(continued) 



Steel studs 0.060" thick, 4" deep or 6" at 16" or 24" centers, respectively, with 
liz" Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is 
attached with flex anchors at 24" on center, with 5" leg welded to studs with two 
l/ z "-long flare-bevel welds, and 4" foot attached to the GFRC skin with 5/ s " -thick 
GFRC bonding pads that extend 2 / z " beyond the flex anchor foot on both sides. 
Interior surface to have one layer of Sis" Type X gypsum wallboard 6 , attached 
with V/4-long Type S buglehead screws spaced 12" on center. Cavity is to be 
filled with 5" of 4 pcf (nominal) mineral fiber batts. GFRC has I / z " returns 
packed with mineral fiber and caulked on the exterior. 



15-1. 12q 



2" x 6" wood studs at 16" with double top plates, single bottom plate; interior and 
exterior sides covered with Sis" Type X gypsum wallboard, 4' wide, applied 
horizontally or vertically with vertical joints over studs, and fastened with 2V4" 
Type S drywall screws, spaced 12" on center. Cavity to be filled with 5 / z " 
mineral wool insulation. 



2" x 6" wood studs at 16" with double top plates, single bottom plate; interior and 
exterior sides covered with Sis" Type X gypsum wallboard, 4' wide, applied 
15-1. 13^| vertically with all joints over framing or blocking and fastened with 2y/' Type S 
drywall screws, spaced 12" on center. R-19 mineral fiber insulation installed in 
stud cavity. 



15-1. 14^ 



2" x 6" wood studs at 16" with double top plates, single bottom plate; interior and 
exterior sides covered with Sis" Type X gypsum wallboard, 4' wide, applied 
horizontally or vertically with vertical joints over studs, and fastened with 2V4" 
Type S drywall screws, spaced 7" on center. 



15-1.15Q 



2" x 4" wood studs at 16" with double top plates, single bottom plate; interior and 
exterior sides covered with Sis" Type X gypsum wallboard and sheathing, 
respectively, 4' wide, applied horizontally or vertically with vertical joints over 
studs, and fastened with 2V4" Type S drywall screws, spaced 12" on center. 
Cavity to be filled with 3 / z " mineral wool insulation. 



15-1. 16Q 



2" x 6" wood studs at 24" centers with double top plates, single bottom plate; 
interior and exterior side covered with two layers of sis" Type X gypsum 
wallboard, 4' wide, applied horizontally with vertical joints over studs. Base layer 
fastened with 2V4" Type S drywall screws, spaced 24" on center and face layer 
fastened with Type S drywall screws, spaced 8" on center, wallboard joints 
covered with paper tape and joint compound, fastener heads covered with joint 
compound. Cavity to be filled with 5 / z " mineral wool insulation. 



&* 



6+/ 7 



6 1 /, 



6 3 / 4 



6 3 / 4 



6 3 / 4 



4 3 / 4 



A4 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



135 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, op 



MATERIAL 



ITEM 
NUMBER 



CONSTRUCTION 



MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 



4 hour 3 hour 2 hour 1 hour 



15-2. l d 



3 5 / s " No. 16 gage steel studs at 24" on center or 2" x 4" wood studs at 24" on 
center. Metal lath attached to the exterior side of studs with minimum 1" long 
No. 6 dry wall screws at 6" on center and covered with minimum 3/ 4 " thick 
Portland cement plaster. Thin veneer brick units of clay or shale complying with 
ASTM C 1088, Grade TBS or better, installed in running bond in accordance 
with Section 1405.10. Combined total thickness of the portland cement plaster, 
mortar and thin veneer brick units shall be not less than l 3 / 4 " . Interior side 
covered with one layer of s/ s n thick Type X gypsum wallboard attached to studs 
with I" long No. 6 dry wall screws at 12" on center. 



15-2. 2 d 



15. Exterior or 
interior walls 
(continued) 



3 5 / s - No. 16 gage steel studs at 24" on center or 2" x 4" wood studs at 24" on 
center. Metal lath attached to the exterior side of studs with minimum 1" long 
No. 6 dry wall screws at 6" on center and covered with minimum 3/ 4 " thick 
portland cement plaster. Thin veneer brick units of clay or shale complying with 
ASTM C 1088, Grade TBS or better, installed in running bond in accordance 
with Section 1405.10. Combined total thickness of the portland cement plaster, 
mortar and thin veneer brick units shall be not less than 2". Interior side covered 
with two layers of 5/ s " thick Type X gypsum wallboard. Bottom layer attached to 
studs with I" long No. 6 dry wall screws at 24" on center. Top layer attached to 
studs with l 5 / s " long No. 6 dry wall screws at 12" on center. 



15-2.3 d 



3 5 / s " No. 16 gage steel studs at 16" on center or 2" x 4" wood studs at 16" on 
center. Where metal lath is used, attach to the exterior side of studs with 
minimum I" long No. 6 dry wall screws at 6" on center. Brick units of clay or 
shale not less than 2 5 / s " thick complying with ASTM C 216 installed in 
accordance with Section 1405.6 with a minimum I" air space. Interior side 
covered with one layer of s/ s n thick Type X gypsum wallboard attached to studs 
with I" long No. 6 dry wall screws at 12" on center. 



15-2.4 d 



3 5 / s " No. 16 gage steel studs at 16" on center or 2" x 4" wood studs at 16" on 
center. Where metal lath is used, attach to the exterior side of studs with 
minimum I" long No. 6 dry wall screws at 6" on center. Brick units of clay or 
shale not less than 2 5 /s" thick complying with ASTM C 216 installed in 
accordance with Section 1405.6 with a minimum I" air space. Interior side 
covered with two layers of 5/s" thick Type X gypsum wallboard. Bottom layer 
attached to studs with I" long No. 6 dry wall screws at 24" on center. Top layer 
attached to studs with l 5 / s " long No. 6 dry wall screws at 12" on center. 



7 7 / s 



16. Exterior walls 
rated for fire 
resistance from 
the inside only in 
accordance with 
Section 705.5. 



16-1. lq 



2" x 4" wood studs at 16" centers with double top plates, single bottom plate; 
interior side covered with 5/ s " Type X gypsum wallboard, 4' wide, applied 
horizontally unblocked, and fastened with 2 1 / 4 " Type S dry wall screws, spaced 
12" on center, wallboard joints covered with paper tape and joint compound, 
fastener heads covered with joint compound. Exterior covered with 3/s" wood 
structural panels, applied vertically, horizontal joints blocked and fastened with 
6d common nails (bright) - 12" on center in the field, and 6" on center panel 
edges. Cavity to be filled with 3 1 / 2 " r 
for exposure from interior side only. 



4V, 



(continued) 



136 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (2)-continued 
RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONS a, op 



ITEM 
NUMBER 



CONSTRUCTION 



MINIMUM FINISHED 

THICKNESS FACE-TO-FACE b 

(inches) 

4 hour 3 hour 2 hour 1 hour 



16-1.2° 



16. Exterior walls 
rated for fire 
resistance from 
the inside only in 
accordance with 
Section 705.5. 
(continued) 



16-1.3 



2" x 6" (51mm x 152 mm) wood studs at 16 " centers with double top plates, single 
bottom plate; interior side covered with 5/ 8 " Type X gypsum wallboard, 4' wide, 
applied horizontally or vertically with vertical joints over studs and fastened with 
2V 4 " Type S drywall screws, spaced 12" on center, wallboard joints covered with 
paper tape and joint compound, fastener heads covered with joint compound, exterior 
side covered with 7/ 16 " wood structural panels fastened with 6d common nails (bright) 
spaced 12" on center in the field and 6" on center along the panel edges. Cavity to be 
filled with 5 l / 2 " mineral wool insulation. Rating established from the gypsum-covered 
side only. 

2" x 6" wood studs at 16" centers with double top plates, single bottom plates; 
interior side covered with 5/ 8 " Type X gypsum wallboard, 4' wide, applied 
vertically with alljoints over framing or blocking and fastened with 2 1 / 4 " Type S 
drywall screws spaced 7" on center. Joints to be covered with tape andjoint 
compound. Exterior covered with 3/ 8 " wood structural panels, applied vertically 
with edges over framing or blocking and fastened with 6d common nails (bright) 
at 12" on center in the field and 6" on center on panel edges. R-19 mineral fiber 
insulation installed in stud cavity. Rating established from the gypsum-covered 
side only. 



6 9 / 



6% 



For SI: 1 inch = 25.4 mm, 1 square inch = 645 .2 mm 2 , 1 cubic foot = 0.0283 m 3 - 

a. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. 

b. Thickness shown for brick and clay tile is nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and clay 
masonry is equivalent thickness defined in Section 721 .3. 1 for concrete masonry and Section 721 .4.1.1 for clay masonry. Where all cells are solid grouted or filled 
with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalent thickness 
shall be the thickness of the block or brick using specified dimensions as defined in Chapter 21 . Equivalent thickness may also include the thickness of applied plas- 
ter and lath or gypsum wallboard, where specified. 

c. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sec- 
tional area measured in the same plane. 

d. Shall be used for nonbearing purposes only. 

e. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size , thickness and core type shall be permit- 
ted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and 
the entire surface is covered with a minimum of 1/16-inch gypsum veneer plaster. 

f. The fire-resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire-resistance rating in Item 3, and having a 
thickness of not less than 7 5 / 8 inches is 4 hours when cores which are not grouted are filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill 
insulation; or expanded clay, shale or slate lightweight aggregate, sand or slag having a maximum particle size of 3/ 8 inch. 

g. The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete masonry 
shall be determined in accordance with ACI 216.1ITMS 0216. Lightweight aggregates shall have a maximum combined density of 65 pounds per cubic foot. 

h. See also Note b. The equivalent thickness shall be permitted to include the thickness of cement plaster or 1.5 times the thickness of gypsum plaster applied in accor- 
dance with the requirements of Chapter 25 . 

i. Concrete walls shall be reinforced with horizontal and vertical temperature reinforcement as required by Chapter 19. 

j. Studs are welded truss wire studs with 0.18 inch (No. 7 B.W gage) flange wire and 0.18 inch (No. 7 B.W gage) truss wires. 

k. Nailable metal studs consist of two channel studs spot welded back to back with a crimped web forming a nailing groove. 

1. Wood structural panels shall be permitted to be installed between the fire protection and the wood studs on either the interior or exterior side of the wood frame 
assemblies in this table , provided the length of the fasteners used to attach the fire protection is increased by an amount at least equal to the thickness of the wood 
structural panel. 

m.The design stress of studs shall be reduced to 78 percent of allowable P cwith the maximum not greater than 78 percent of the calculated stress with studs having a 
slenderness ratio I id of 33. 

n. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667. 

o. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed. 

p. NCMA TEK 5-8A shall be permitted for the design of fire walls. 

q. The design stress of studs shall be equal to a maximum of 100 percent of the allowable P ccalculated in accordance with Section 2306. 



2009 INTERNATIONAL BUILDING CODE® 



137 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (3) 
MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, 


q 














FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR 

OR ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 

hour 


2 
hour 


1 
hour 


4 
hour 


3 
hour 


2 
hour 


1 

hour 


1. Siliceous 
aggregate concrete 


1-1.1 


Slab (no ceiling required) . Minimum cover over 
nonprestressed reinforcement shall not be less than 

3/ 4 " b. 


7.0 


6.2 


5.0 


3.5 










2. Carbonate 
aggregate concrete 


2-1.1 


6.6 


5.7 


4.6 


3.2 










3. Sand-lightweight concrete 


3-1.1 


5.4 


4.6 


3.8 


2.7 


- 


- 


- 


- 


4. Lightweight concrete 


4-1.1 


5.1 


4.4 


3.6 


2.5 


_ 


_ 


_ 


_ 


5 . Reinforced 
concrete 


5-1.1 


Slab with suspended ceiling of vermiculite gypsum 
plaster over metal lath attached to 3/ 4 " cold-rolled 
channels spaced 12" on center. Ceiling located 6" 
minimum below joists. 


3 


2 


- 


- 


1 


3/ 4 


- 


- 


5-2.1 


3/ 8 " Type X gypsum wallboard c attached to 0.018 
inch (No. 25 carbon sheet steel gage) by7/ 8 " deep by 
2 5 / 8 " hat-shaped galvanized steel channels with 
l"-long No. 6 screws. The channels are spaced 24" 
on center, span 35" and are supported along their 
length at 35" intervals by 0.033" (No. 21 galvanized 
sheet gage) galvanized steel flat strap hangers 
having formed edges that engage the lips of the 
channel. The strap hangers are attached to the side 
of the concrete joists with 5/ 32 " by IV4" long 
power-driven fasteners. The wallboard is installed 
with the long dimension perpendicular to the 
channels. All end joints occur on channels and 
supplementary channels are installed parallel to the 
main channels, 12" each side, at end joint 
occurrences. The finished ceiling is located 
approximately 12" below the soffit of the floor slab. 


- 


- 


2V 2 


- 


- 


- 


5/ 8 


- 


6. Steel joists constructed with 
a poured reinforced concrete 
slab on metal lath forms or 
steel form units d , e 


6-1.1 


Gypsum plaster on metal lath attached to the bottom 
cord with single No. 16 gage or doubled No. 18 
gage wire ties spaced 6" on center. Plaster mixed 1:2 
for scratch coat, 1:3 for brown coat, by weight, 
gypsum-to-sand aggregate for 2-hour system. For 
3-hour system plaster is neat. 






2V 2 


2V 4 






3/ 4 


5/ 8 


6-2.1 


Vermiculite gypsum plaster on metal lath attached to 
the bottom chord with single No. 16 gage or doubled 
0.049-inch (No. 18 B.W. gage) wire ties 6" on center. 


- 


2 


- 


- 


- 


5/ 8 


- 


- 


6-3.1 


Cement plaster over metal lath attached to the 
bottom chord of joists with single No. 16 gage or 
doubled 0.049" (No. 18 B.W. gage) wire ties spaced 
6" on center. Plaster mixed 1:2 for scratch coat, 1:3 
for brown coat for I-hour system and 1 : 1 for scratch 
coat, 1:1 V 2 for brown coat for 2-hour system, by 
weight, cement to sand. 








2 








5/ f 


6-4.1 


Ceiling of 5/ 8 " Type X wallboard attached to 7/ 8 " 
deep by 2 5 / 8 " by 0.021 inch (No. 25 carbon sheet 
steel gage) hat- shaped furring channels 12" on 
center with 1" long No. 6 wallboard screws at 8" on 
center. Channels wire tied to bottom chord of joists 
with doubled 0.049 inch (No. 18 B.W. gage) wire or 
suspended below] oists on wire hangers. 8 


- 


- 


2V 2 


- 


- 


- 


5/ 8 


- 


6-5.1 


Wood-fibered gypsum plaster mixed 1:1 by weight 
gypsum to sand aggregate applied over metal lath. 
Lath tied 6" on center to 3/ 4 " channels spaced 13 1 / 2 '' 
on center. Channels secured to joists at each 
intersection with two strands of 0.049 inch (No. 18 
B.W. gage) galvanized wire. 


- 


- 


2V 2 


- 


- 


- 


3/ 4 


- 



(continued) 



138 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa, 


q 














FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR 

OR ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


4 
hour 


3 
hour 


2 
hour 


i 

hour 


7. Reinforced concrete slabs 
and joists with hollow clay tile 
fillers laid end to end in rows 
2 1 / 2 " or more apart; 
reinforcement placed between 
rows and concrete cast around 
and over tile. 


7-1.1 


5/s" gypsum plaster on bottom of floor or roof 
construction. 






8 h 








sis 




7-1.2 


None 


- 


- 


- 


5hi 


- 


- 


- 


- 


8. Steel joists constructed with 
a reinforced concrete slab on 
top poured on allv deep steel 
deck. 6 


8-1.1 


Vermiculite gypsum plaster on metal lath attached 
to 3/ 4 " cold-rolled channels with 0.049" (No. 18 
B.W. gage) wire ties spaced 6" on center. 


2^ 








^ 








9.3" deep cellular steel deck 
with concrete slab on top. Slab 
thickness measured to top. 


9-1.1 


Suspended ceiling of vermiculite gypsum plaster 
base coat and vermiculite acoustical plaster on metal 
lath attached at 6" intervals to 31 4 cold-rolled 
channels spaced 12" on center and secured to I 1 // 
cold-rolled channels spaced 36" on center with 
0.065" (No. 16 B.W. gage) wire. i l / 2 " channels 
supported by No. 8 gage wire hangers at 36" on 
center. Beams within envelope and with a 2 i / 2 " 
airspace between beam soffit and lath have a 4-hour 
rating . 


2% 


- 


- 


- 


yy 


- 


- 


- 


10. 1 l / 2 "-deep steel roof deck 
on steel framing. Insulation 
board, 30 pcf density, 
composed of wood fibers with 
cement binders of thickness 
shown bonded to deck with 
unified asphalt adhesive. 
Covered with a Class A or B 
roof covering. 


10-1.1 


Ceiling of gypsum plaster on metal lath. Lath 
attached to 31 4 furring channels with 0.049" (No. 18 
B.W. gage) wire ties spaced 6" on center. 31 4 
channel saddle tied to 2" channels with doubled 
0.065" (No. 16 B.W. gage) wire ties. 2" channels 
spaced 36" on center suspended 2" below steel 
framing and saddle-tied with 0.165" (No. 8 B.W. 
gage) wire. Plaster mixed 1:2 by weight, 
gypsum-to-sand aggregate. 


- 


- 


1 7 's 


1 


- 


- 


V 


V 


11. 7 7 / 2 " -deep steel roof deck 
on steel-framing wood fiber 
insulation board, 17.5 pcf 
density on top applied over a 
15-lb asphalt-saturated felt. 
Class A or B roof covering. 


11-1.1 


Ceiling of gypsum plaster on metal lath. Lath 
attached to 3/ 4 " furring channels with 0.049" (No. 18 
B.W. gage) wire ties spaced 6" on center. 3/ 4 " 
channels saddle tied to 2" channels with doubled 
0.065" (No. 16 B.W. gage) wire ties. 2" channels 
spaced 36" on center suspended 2" below steel 
framing and saddle tied with 0.165" (No. 8 B.W. 
gage) wire. Plaster mixed 1:2 for scratch coat and 
1:3 for brown coat, by weight, gypsum-to-sand 
aggregate for I-hour system. For 2-hour system, 
plaster mix is 1:2 by weight, gypsum-to-sand 
aggregate. 


- 


- 


1*'2 


1 


- 


- 


7/ i 


y 4 1 



{continued) 



2009 INTERNATIONAL BUILDING CODE® 



139 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa,q 














FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR 

OR ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


12. lV 2 " deep steel roof deck 
on steel-framing insulation of 
rigid board consisting of 
expanded perlite and fibers 
impregnated with integral 
asphalt waterproofing ; density 
9 to 12 pcf secured to metal 
roof deck by i/ 2 " wide ribbons 
of waterproof, cold-process 
liquid adhesive spaced 6" 
apart. Steel joist or light steel 
construction with metal roof 
deck, insulation, and Class A 
or B built-up roof covering. 6 


12-1.1 


Gypsum-vermiculite plaster on metal lath wire tied 
at 6" intervals to 3/ 4 " furring channels spaced 12" on 
center and wire tied to 2" runner channels spaced 
32" on center. Runners wire tied to bottom chord of 
steeljoists. 


- 


- 


1 


- 


- 


- 


7/ 8 


- 


13. Double wood floor over 
woodjoists spaced 16" on 
center.ffi,n 


13-1.1 


Gypsum plaster over 3/ 8 " Type X gypsum lath. Lath 
initially applied with not less than four lV 8 " by No. 
13 gage by i9/ 64 " head plasterboard blued nails per 
bearing. Continuous stripping over lath along all 
joist lines. Stripping consists of 3" wide strips of 
metal lath attached by l 1 / 2 " by No. 11 gage by i/ 2 " 
head roofing nails spaced 6" on center. Alternate 
stripping consists of 3" wide 0.049" diameter wire 
stripping weighing 1 pound per square yard and 
attached by No. 16 gage by 1 1 / 2 M by 3/ 4 " crown width 
staples, spaced 4" on center. Where alternate 
stripping is used, the lath nailing may consist of two 
nails at each end and one nail at each intermediate 
bearing. Plaster mixed 1:2 by weight, 
gypsum-to-sand aggregate. 
















7/ 8 


13-1.2 


Cement or gypsum plaster on metal lath. Lath 
fastened with lV 2 " by No. 11 gage by 7/ 16 " head 
barbed shank roofing nails spaced 5" on center. 
Plaster mixed 1:2 for scratch coat and 1:3 for brown 
coat, by weight, cement to sand aggregate. 
















5/ 8 


13-1.3 


Perlite or vermiculite gypsum plaster on metal lath 
secured to joists with lV 2 " by No. 11 gage by 7/ 16 " 
head barbed shank roofing nails spaced 5" on center. 


- 


- 


- 


- 


- 


- 


- 


5/ 8 


13-1.4 


i/ 2 " Type X gypsum wallboard c nailed to joists with 
5d coolero or wallboardo nails at 6" on center. End 
ioints of wallboard centered on ioists. 
















17 2 


14. Plywood stressed skin 
panels consisting of 5/ 8 "-thick 
interior C-D (exterior glue) 
top stressed skin on 2" x 6" 
nominal (minimum) stringers. 
Adjacent panel edges joined 
with 8d common wire nails 
spaced 6" on center. Stringers 
spaced 12" maximum on 
center. 


14-1.1 


i/ 2 " -thick wood fiberboard weighing 15 to 18 
pounds per cubic foot installed with long dimension 
parallel to stringers or 3/ 8 " C-D (exterior glue) 
plywood glued and/or nailed to stringers. Nailing to 
be with 5d coolero or wallboardo nails at 12" on 
center. Second layer of i/ 2 " Type X gypsum 
wallboard applied with long dimension 
perpendicular to joists and attached with 8d coolero 
or wallboardo nails at 6" on center at end joints and 
8" on center elsewhere. Wallboard joints staggered 
with respect to fiberboard ioints. 


- 


- 


- 


- 


- 


- 


- 


1 



(continued) 



140 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 





TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa, 


q 














FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR 

OR ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 
hour 


2 
hour 


l 
hour 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


15 . Vermiculite concrete slab 
proportioned 1:4 (portland 
cement to vermiculite 
aggregate) on a lyf-deep 
steel deck supported on 
individually protected steel 
framing. Maximum span of 
deck 6'- 10" where deck is less 
than 0.019 inch (No. 26 
carbon steel sheet gage) or 
greater. Slab reinforced with 
4" x 8" 0.109/0.083" (No. 12 /u 
B.W. gage) welded wire mesh. 


15-1.1 


None 


- 


- 


- 


3J 


- 


- 


- 


- 


16. Perlite concrete slab 
proportioned 1:6 (portland 
cement to perlite aggregate) 
on a 1V4 '-deep steel deck 
supported on individually 
protected steel framing. Slab 
reinforced with 4" x 8" 
0.109/0.083" (No. i2 /j4B.W. 
gage) welded wire mesh. 


16-1.1 


None 


- 


- 


- 


Ml 


- 


- 


- 


- 


17. Perlite concrete slab 
proportioned 1:6 (portland 
cement to perlite aggregate) 
on a 9/]^ "-deep steel deck 
supported by steel joists 4' on 
center. Class A or B roof 
covering on top. 


17-1.1 


Perlite gypsum plaster on metal lath wire tied to 3/4' 
furring channels attached with 0.065" (No. 16 B.W. 
gage) wire ties to lower chord ofjoists. 


- 


2P 


2P 


- 


- 


7/ s 


3/ 4 


- 


18. Perlite concrete slab 
proportioned 1:6 (portland 
cement to perlite aggregate) 
on 1 //'-deep steel deck 
supported on individually 
protected steel framing. 
Maximum span of deck 6'- 10" 
where deck is less than 0.019" 
(No. 26 carbon sheet steel 
gage) and 8'-0" where deck is 
0.019" (No. 26 carbon sheet 
steel gage) or greater. Slab 
reinforced with 0.042" (No. 19 
B.W. gage) hexagonal wire 
mesh. Class A or B roof 
covering on top. 


18-1.1 


None 


- 


2V 4 p 


2V 4 p 


- 


- 


- 


- 


- 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



141 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa,q 



FLOOR OR ROOF 
CONSTRUCTION 



ITEM 
NUMBER 



CEILING CONSTRUCTION 



THICKNESS OF FLOOR OR 

ROOF SLAB 

(inches) 



4 hour 3 hour 



2 hour 



1 hour 



MINIMUM THICKNESS 

OF CEILING 

(inches) 



4 hour 3 hour 2 hour 



1 hour 



19. Floor and beam 
construction consisting of 
3" -deep cellular steel floor 
unit mounted on steel 
members with 1:4 
(proportion of portland 
cement to perlite 
aggregate) perlite-concrete 
floor slab on top . 



19-1.1 



Suspended envelope ceiling of perlite 
gypsum plaster on metal lath attached to 
3/ 4 " cold-rolled channels, secured to 1 1 / 2 " 
cold-rolled channels spaced 42" on center 
supported by 0.203 inch (No. 6 B.W. gage) 
wire 36" on center. Beams in envelope with 
3" minimum airspace between beam soffit 
and lath have a 4- hour rating. 



2P 



20 . Perlite concrete 
proportioned 1:6 (portland 
cement to perlite 
aggregate) poured to i/ 8 " 
thickness above top of 
corrugations of 7 5 / /6 "-deep 
galvanized steel deck 
maximum span 8'-0" for 
0.024" (No. 24 galvanized 
sheet gage) or 6' 0" for 
0.019" (No. 26 galvanized 
sheet gage) with deck 
supported by individually 
protected steel framing . 
Approved polystyrene 
foam plastic insulation 
board having a flame 
spread not exceeding 75 
(1" to 4" thickness) with 
vent holes that 
approximate 3 percent of 
the board surface area 
placed on top of perlite 
slurry. A 2' by 4' insulation 
board contains six 2 3 / 4 " 
diameter holes. Board 
covered with 2 1 / 4 " 
minimum perlite concrete 
slab. 



20-1.1 



None 



Varies 



(continued) 



142 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa,q 



FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR OR 

ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


(continued) 
20. Slab reinforced with mesh 
consisting of 0.042" (No. 19 
B.W. gage) galvanized steel 
wire twisted together to form 
2" hexagons with straight 
0.065" (No. 16 B.W. gage) 
galvanized steel wire woven 
into mesh and spaced 3". 
Alternate slab reinforcement 
shall be permitted to consist of 
4" x8", 0.109/0.238" (No. 12/4 
B.W. gage), or 2" x 2", 
0.083/0.083" (No. 14/14 B.W. 
gage) welded wire fabric. Class 
A or B roof covering on top. 


20-1.1 


None 


- 


- 


Varies 


- 


- 


- 


- 


- 


21. Woodjoists, wood I-joists, 
floor trusses and flat or pitched 
roof trusses spaced a maximum 
24" o.c. with i/ 2 " wood 
structural panels with exterior 
glue applied at right angles to 
top ofjoist or top chord of 
trusses with 8d nails. The wood 
structural panel thickness shall 
not be less than nominal i/ 2 " 
nor less than required by 
Chapter 23. 


21-1.1 


Base layer 5/ s " Type X gypsum wallboard applied 
at right angles to joist or truss 24" o.c. with IV4" 
Type S or Type W dry wall screws 24" o.c. Face 
layer 5/s" Type X gypsum wallboard or veneer 
base applied at right angles to joist or truss 
through base layer with l 7 / s " Type S or Type W 
drywall screws 12" o.c. at joints and intermediate 
joist or truss. Face layer Type G drywall screws 
placed 2" back on either side of face layer end 
joints, 12" o.c. 








Varies 








iv 4 


22. Steel joists, floor trusses 
and flat or pitched roof trusses 
spaced a maximum 24" o.c. 
with i/ 2 " wood structural panels 
with exterior glue applied at 
right angles to top ofjoist or 
top chord of trusses with No. 8 
screws. The wood structural 
panel thickness shall not be less 
than nominal i/ 2 " nor less than 
required by Chapter 23. 


22-1.1 


Base layer 5/ s " Type X gypsum board applied at 
right angles to steel framing 24" on center with 1" 
Type S drywall screws spaced 24" on center. Face 
layer 5/s" Type X gypsum board applied at right 
angles to steel framing attached through base 
layer with l 5 / s " Type S drywall screws 12" on 
center at end joints and intermediate joints and 
l 1 / 2 " Type G drywall screws 12 inches on center 
placed 2" back on either side of face layer end 
joints. Joints of the face layer are offset 24" from 
theioints of the base layer. 








Varies 








iv 4 


23. Wood I-joist (minimum 
joist depth 9 1 / 4 " with a 
minimum flange depth of 15/ 16 " 
and a minimum flange cross- 
sectional area of 2.3 square 
inches) at 24" o.c. spacing with 
1 inch by 4 inch (nominal) 
wood furring strip spacer 
applied parallel to and covering 
the bottom of the bottom flange 
of each member, tacked in 
place . 2" mineral wool 
insulation, 3.5 pcf (nominal) 
installed adjacent to the bottom 
flange of the I-joist and 
supported by the 1" x 4" 
furring strip spacer. 


23-1.1 


i/ 2 " deep single leg resilient channel 16" on center 
(channels doubled at wallboard endjoints), placed 
perpendicular to the furring strip and joist and 
attached to each joist by l 7 / s " Type S drywall 
screws. 5/ s " Type C gypsum wallboard applied 
perpendicular to the channel with endjoints 
staggered at least 4' and fastened with 1 V s " Type 
S drywall screws spaced 7" on center. Wallboard 
joints to be taped and covered with joint 
compound. 


- 


- 


- 


Varies 


- 


- 


- 


5/ s 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



143 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOR AND ROOF SVSTEMSa,q 



FLOOR OR ROOF 
CONSTRUCTION 


ITEM 
NUMBER 


CEILING CONSTRUCTION 


THICKNESS OF FLOOR OR 

ROOF SLAB 

(inches) 


MINIMUM THICKNESS 

OF CEILING 

(inches) 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


4 
hour 


3 
hour 


2 
hour 


1 
hour 


24. Wood I-joist (minimum 
I-joist depth 9 1 / 4 " with a 
minimum flange depth of 1 V 2 " 
and a minimum flange 
cross-sectional area of 5.25 
square inches; minimum web 
thickness of 3/ 8 „) @ 24" o.c, 
1 l i 2 mineral wool insulation 
(2.5 pcf-nominal) resting on 
hat-shaped furring channels . 


24-1.1 


Minimum 0.026" thick hat-shaped channel 16" 
o.c. (channels doubled at wallboard endjoints), 
placed perpendicular to the joist and attached to 
eachjoistby l 5 / 8 " Type S drywall screws. 5/ 8 " 
Type C gypsum wallboard applied 
perpendicular to the channel with endjoints 
staggered and fastened with 1 V 8 " Type S 
drywall screws spaced 12" o.c. in the field and 
8" o.c. at the wallboard ends. Wallboard joints 
to be taped and covered with joint compound. 


- 


- 


- 


Varies 


- 


- 


- 


5/ 8 


25. Wood I-joist (minimum 
I-joist depth 9 1 / 4 " with a 
minimum flange depth of lV 2 " 
and a minimum flange 
cross-sectional area of 5.25 
square inches; minimum web 
thickness of 7/ 16 ") @ 24" o.c, 
1 l i 2 " mineral wool insulation 
(2.5 pcf-nominal) resting on 
resilient channels. 


25-1.1 


Minimum 0.019" thick resilient channel 16" o.c. 
(channels doubled at wallboard endjoints), 
placed perpendicular to the joist and attached to 
eachjoistby l 5 / 8 " Type S drywall screws. 5/ 8 " 
Type C gypsum wallboard applied 
perpendicular to the channel with endjoints 
staggered and fastened with 1" Type S drywall 
screws spaced 12" o.c. in the field and 8" o.c. at 
the wallboard ends. Wallboard joints to be taped 
and covered with joint compound. 


- 


- 


- 


Varies 


- 


- 


- 


5/ 8 


26. Wood I-joist (minimum 
I-joist depth 9 1 / 4 " with a 
minimum flange thickness of 
l 1 / 2 " and a minimum flange 
cross-sectional area of 2.25 
square inches; minimum web 
thickness of 3/ 8 „) @ 24" o.c. 


26-1.1 


Two layers of i/ 2 " Type X gypsum wallboard 
applied with the long dimension perpendicular 
to the I-joists with endjoints staggered. The 
base layer is fastened with l 5 / 8 - Type S drywall 
screws spaced 12" o.c. and the face layer is 
fastened with 2" Type S drywall screws spaced 
12" o.c. in the field and 8" o.c. on the edges. 
Face layer endjoints shall not occur on the same 
I-joist as base layer endjoints and edge joints 
shall be offset 24" from base layerjoints. Face 
layer to also be attached to base layer with l 1 / 2 " 
Type G drywall screws spaced 8" o.c. placed 6" 
from face layer endjoints. Face layer wallboard 
joints to be taped and covered with joint 
compound. 








Varies 








1 


27. Wood I-joist (minimum 
I-joist depth 9 1 / 2 " with a 
minimum flange depth of 
l 15 / 16 " and a minimum flange 
cross-sectional area of 1.95 
square inches; minimum web 
thickness of 3/ 8 ") @ 24" o.c. 


27-1.1 


Minimum 0.019" thick resilient channel 16" o.c. 
(channels doubled at wallboard endjoints), 
placed perpendicular to the joist and attached to 
eachjoist by l 5 / 8 " Type S drywall screws. Two 
layers of i/ 2 " Type X gypsum wallboard applied 
with the long dimension perpendicular to the 
I-joists with endjoints staggered. The base layer 
is fastened with l 1 / 4 " Type S drywall screws 
spaced 12" o.c. and the face layer is fastened 
with l 5 / 8 - Type S drywall screws spaced 12" 
o.c. Face layer endjoints shall not occur on the 
same I-joist as base layer endjoints and edge 
joints shall be offset 24" from base layerjoints. 
Face layer to also be attached to base layer with 
l 1 / 2 " Type G drywall screws spaced 8" o.c. 
placed 6" from face layer endjoints. Face layer 
wallboard joints to be taped and covered with 
joint compound. 


- 


- 


- 


Varies 


- 


- 


- 


1 



(continued) 



144 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



FLOOR OR ROOF 
CONSTRUCTION 



28. Wood I-joist (minimum 
I-joist depth 9 1 / 4 M with a 
minimum flange depth of 
1 h 2 and a minimum flange 
cross-sectional area of 2.25 
square inches; minimum web 
thickness of 3/s") @ 24" o.c, 
Unfaced fiberglass insulation 
is installed between the 
I-joists supported on the 
upper surface of the flange b^ 
stay wires spaced 12" o.c. 



29. Channel-shaped 18 gage 
steel joists (minimum depth 
8") spaced a maximum 24" 
o.c. supporting 
tongue-and-groove wood 
structural panels (nominal 
minimum 3/ 4 " thick) applied 
perpendicular to framing 
members. Structural panels 
attached with l- 5 /s" Type 
S-12 screws spaced 12" o.c. 



TABLE 720.1 (3)-continued 
MINIMUM PROTECTION FOR FLOOFNVM^ROOF SVSTEMSa,q 



ITEM 
NUMBER 



28-1.1 



29-1.1 



CEILING CONSTRUCTION 

Base layer of 5/s" Type C gypsum wallboard 
attached directly to I-joists with l 5 / s " Type S 
drywall screws spaced 12" o.c. with ends 
staggered. Minimum 0.0179" thick hat-shaped 
7/ s -inch furring channel 16" o.c. (channels 
doubled at wallboard end joints), placed 
perpendicular to the joist and attached to each 
joist by l 5 / s " Type S drywall screws after the 
base layer of gypsum wallboard has been 
applied. The middle and face layers of 5/s" Type 
C gypsum wallboard applied perpendicular to 
the channel with end joints staggered. The 
middle layer is fastened with 1" Type S drywall 
screws spaced 12" o.c. The face layer is applied 
parallel to the middle layer but with the edge 
joints offset 24" from those of the middle layer 
and fastened with l 5 / s " Type S drywall screws 
8" o.c. Thejoints shall be taped and covered 
withioint compound. 

Base layer 5/s" Type X gypsum board applied 
perpendicular to bottom of framing members 
with 1 V s" Type S-12 screws spaced 12" o.c. 
Second layer 5/s" Type X gypsum board 
attached perpendicular to framing members with 
l 5 / 8 " Type S-12 screws spaced 12" o.c. Second 
layer joints offset 24" from base layer. Third 
layer 5/ s " Type X gypsum board attached 
perpendicular to framing members with 2 3 / s " 
Type S-12 screws spaced 12" o.c. Third layer 
joints offset 12" from second layerjoints. 
Hat- shaped 7/s-inch rigid furring channels 
applied at right angles to framing members over 
third layer with two 2 3 /s" Type S-12 screws at 
each framing member. Face layer 5/s" Type X 
gypsum board applied at right angles to furring 
channels with lV s " Type S screws spaced 12" 



THICKNESS OF FLOOR OR 

ROOF SLAB 

(inches) 



4 
hour 



3 
hour 



2 
hour 



Varies 



1 
hour 



Varies 



MINIMUM THICKNESS 

OF CEILING 

finches) 



4 
hour 



3 
hour 



2 
hour 



2 3 / 4 



3 3 /, 



l 
hour 



2009 INTERNATIONAL BUILDING CODE® 



145 



FIRE AND SMOKE PROTECTION FEATURES 



Table 720.1(3) Notes. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 cubic foot = 0.0283m 3 , 
1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 1.4882 kg/m. 

a. Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. 

b. When the slab is in an unrestrained condition, minimum reinforcement cover shall not be less than I Ss inches for 4-hour (siliceous aggregate only); f/ 4 inches for 
4- and 3-hour; 1 inch for 2-hour (siliceous aggregate only) ; and 3/ 4 inch for all other restrained and unrestrained conditions. 

c. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permit- 
ted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and 
the entire surface is covered with a minimum of r/ y6 -inch gypsum veneer plaster. 

d. Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units. 

e. (a) The maximum allowable stress level for H-Seriesjoists shall not exceed 22,000 psi. 

(b) The allowable stress for K-Seriesjoists shall not exceed 26,000 psi, the nominal depth of suchjoist shall not be less than 10 inches and the nominaljoist weight 
shall not be less than 5 pounds per lineal foot. 

f. Cement plaster with 15 pounds of hydrated lime and 3 pounds of approved additives or admixtures per bag of cement. 

g. Gypsum wallboard ceilings attached to steel framing shall be permitted to be suspended with 1 / z -inch cold-formed carrying channels spaced 48 inches on center, 
which are suspended with No. 8 SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 
SWG galvanized wire hangers spaced 48 inches on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire (double 
strand) and spaced as required for direct attachment to the framing. This alternative is also applicable to those steel framing assemblies recognized under 
Noteq. 

h. Six-inch hollow clay tile with 2-inch concrete slab above. 

i. Four-inch hollow clay tile with 1 7 z -inch concrete slab above . 

j . Thickness measured to bottom of steel form units . 

k. Five-eighths inch of vermiculite gypsum plaster plus //zinch of approved vermiculite acoustical plastic. 

1. Furring channels spaced 12 inches on center. 

m. Double wood floor shall be permitted to be either of the following: 

(a) Subfloor of I-inch nominal boarding, a layer of asbestos paper weighing not less than 14 pounds per 100 square feet and a layer of I-inch nominal 
tongue-and-groove finished flooring; or 

(b) Subfloor of I-inch nominal tongue-and-groove boarding or ls/3z-inch wood structural panels with exterior glue and a layer of I-inch nominal 
tongue-and-groove finished flooring or l^z-inch wood structural panel finish flooring or a layer of Type I Grade M-l particleboard not less than sis-inch thick. 

n. The ceiling shall be permitted to be omitted over unusable space, and flooring shall be permitted to be omitted where unusable space occurs above. 

o. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667. 

p. Thickness measured on top of steel deck unit. 

q. Generic fire-resistance ratings (those not designated as PROPRIETARY* in the listing) in the GA 600 shall be accepted as if herein listed. 



(Section 721.1.1 continued from page 125) 

CONCRETE, VERMICULITE. A lightweight insulating 
concrete made with vermiculite concrete aggregate which is 
laminated micaceous material produced by expanding the 
ore at high temperatures. When added to a portland cement 
slurry the resulting concrete has a dry unit weight of approx- 
imately 30 pcf (480 kg/m 3 ). 

GLASS FIBERBOARD. Fibrous glass roof insulation 
consisting of inorganic glass fibers formed into rigid boards 
using a binder. The board has a top surface faced with 
asphalt and kraft reinforced with glass fiber. 

MINERAL BOARD. A rigid felted thermal insulation 
board consisting of either felted mineral fiber or cellular 
beads of expanded aggregate formed into flat rectangular 
units. 

721.2 Concrete assemblies. The provisions of this section 
contain procedures by which the fire-resistance ratings of con- 
crete assemblies are established by calculations. 

721.2.1 Concrete walls. Cast-in-place and precast concrete 
walls shall comply with Section 72 1 .2. 1 . 1 . Multiwythe con- 
crete walls shall comply with Section 721.2.1.2. Joints 
between precast panels shall comply with Section 
721.2.1.3. Concrete walls with gypsum wallboard or plaster 
finish shall comply with Section 721.2.1.4. 

721.2.1.1 Cast-in-place or precast walls. The mini- 
mum equivalent thicknesses of cast-in-place or precast 
concrete walls for fire-resistance ratings of 1 hour to 4 
hours are shown in Table 721.2.1.1. For solid walls with 



flat vertical surfaces, the equivalent thickness is the same 
as the actual thickness. The values in Table 721.2.1.1 
apply to plain, reinforced or prestressed concrete walls. 

TABLE 721.2.1.1 

MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR 

PRECAST CONCRETE WALLS, LOAD-BEARING OR 

NONLOAD-BEARING 



CONCRETE 
TYPE 


MINIMUM SLAB THICKNESS (inches) 
FOR FIRE-RESISTANCE RATING OF 


l-hour 


1 l / 2 -hour 


2-hour 


3-hour 


4-hour 


Siliceous 


3.5 


4.3 


5.0 


6.2 


7.0 


Carbonate 


3.2 


4.0 


4.6 


5.7 


6.6 


Sand-Lightweight 


2.7 


3.3 


3.8 


4.6 


5.4 


Lightweight 


2.5 


3.1 


3.6 


4.4 


5.1 



For SI: 1 inch = 25.4 mm. 



721.2.1.1.1 Hollow-core precast wall panels. For 
hollow-core precast concrete wall panels in which the 
cores are of constant cross section throughout the 
length, calculation of the equivalent thickness by 
dividing the net cross-sectional area (the gross cross 
section minus the area of the cores) of the panel by its 
width shall be permitted. 

721.2.1.1.2 Core spaces filled. Where all of the core 
spaces of hollow-core wall panels are filled with 
loose-fill material, such as expanded shale, clay, or 
slag, or vermiculite or perlite, the fire-resistance rat- 



146 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



ing of the wall is the same as that of a solid wall of the 
same concrete type and of the same overall thickness. 

721.2.1.1.3 Tapered cross sections. The thickness of 
panels with tapered cross sections shall be that deter- 
mined at a distance 2 tor 6 inches (152 mm), which- 
ever is less, from the point of minimum thickness, 
where tis the minimum thickness. 

721.2.1.1.4 Ribbed or undulating surfaces. The 
equivalent thickness of panels with ribbed or undulat- 
ing surfaces shall be determined by one of the follow- 
ing expressions: 

For s > At, the thickness to be used shall be t 

For s<2t, the thickness to be used shall be t e 

For At > s > It, the thickness to be used shall be 



INSIDEWYTHE 
CARBONATE 



INSIDEWYTHE 
SILICEOUS 




1 ^3^5 



1 ^3^1- :5 



THICKNESS OF INSIDEWYTHE, INCHES 



OUTSIDE WYTHE 

CARBONATE 
. I V I I I I 



OUTSIDE WYTHE 
SILICEOUS 
I I 




12345 12345 

THICKNESS OF INSIDE WYTHE OF SAND-LIGHTWEIGHT CONCRETE, INCHES 



t + 



At 



-1 



t -t 
e 



(Equation 7-3) 



where: 

s Spacing of ribs or undulations. 

Minimum thickness. 

t e Equivalent thickness of the panel calculated 

as the net cross-sectional area of the panel di- 
vided by the width, in which the maximum 
thickness used in the calculation shall not ex- 
ceed 2t. 

721.2.1.2 Multiwythe walls. For walls that consist of 
two wythes of different types of concrete, the fire -resis- 
tance ratings shall be permitted to be determined from 
Figure 721.2.1.2. 



For 51: 1 inch = 25.4 mm. 



FIGURE 721.2.1.2 
FIRE-RESISTANCE RATINGS OF 
TWO-WYTHE CONCRETE WALLS 



721.2.1.2.1 Two or more wythes. The fire-resistance 
ratingforwaU panels consisting of two or more wythes 
shall be permitted to be determined by the formula : 



R= (R f .59 + Ra59 + ... + R 



o.59) 1.7 



(Equation 7-4) 



where: 

R = The fire endurance of the assembly, minutes. 

R p R 2 , and R n =The fire endurances of the individual 
wythes, minutes. Values of R n o.59 for use in Equation 7-4 
are given in Table 721.2.1.2(1). Calculated fire-resis- 
tance ratings are shown in Table 721.2.1.2(2). 



TABLE 721.2.1.2(1) 
VALUES OF Ro. 59 FOR USE IN EQUATION 7-4 



TYPE OF MATERIAL 


THICKNESS OF MATERIAL (inches) 


l\ 


2 


2% 


3 


3\ 


4 


4% 


5 


5\ 


6 


6 l / 2 


7 


Siliceous aggregate 
concrete 


5.3 


6.5 


8.1 


9.5 


11.3 


13.0 


14.9 


16.9 


18.8 


20.7 


22.8 


25.1 


Carbonate aggregate 
concrete 


5.5 


7.1 


8.9 


10.4 


12.0 


14.0 


16.2 


18.1 


20.3 


21.9 


24.7 


27.2 C 


Sand-lightweight 
concrete 


6.5 


8.2 


10.5 


12.8 


15.5 


18.1 


20.7 


23.3 


26.0° 


Note c 


Note c 


Note c 


Lightweight concrete 


6.6 


8.8 


11.2 


13.7 


16.5 


19.1 


21.9 


24.7 


27.8 C 


Note c 


Note c 


Note c 


Insulating concrete 3 


9.3 


13.3 


16.6 


18.3 


23.1 


26. 5 C 


Note c 


Note c 


Note c 


Note c 


Note c 


Note c 


Airspace b 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 


- 



For 51 : 1 inch = 25.4 mm, 1 pound per cubic foot = 16.02 kg/m 3 . 

a. Dry unit weight of 35 pcf or less and consisting of cellular, perlite or vermiculite concrete. 

b. The R n o. value for one V 2 " to 3 V 2 " airspace is 3.3. The R n o. value for two V 2 " to 3 7 2 " airspaces is 6.7. 

c. The fire-resistance rating for this thickness exceeds 4 hours. 



2009 INTERNATIONAL BUILDING CODE® 



147 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.2.1.2(2) 
FIRE-RESISTANCE RATINGS BASED ON RO. 5 



R a , MINUTES 


RO.59 


60 
120 
180 
240 


11.20 
16.85 
21.41 

25.37 



a. Based on Equation 7-4. 

721.2.1.2.2 Foam plastic insulation. The fire-resis- 
tance ratings of precast concrete wall panels consist- 
ing of a layer of foam plastic insulation sandwiched 
between two wythes of concrete shall be permitted to 
be determined by use of Equation 7-4. Foam plastic 
insulation with a total thickness of less than 1 inch (25 
mm) shall be disregarded. The R n value for thickness 
of foam plastic insulation of 1 inch (25 mm) or 
greater, for use in the calculation, is 5 minutes; there- 
fore R n °59 = 2.5. 

721.2.1.3 Joints between precast wall panels. Joints 
between precast concrete wall panels which are not insu- 
lated as required by this section shall be considered as 
openings in walls. Uninsulatedjoints shall be included in 
determining the percentage of openings permitted by 
Table 705.8. Where openings are not permitted or are 
required by this code to be protected, the provisions of 
this section shall be used to determine the amount ofjoint 
insulation required. Insulatedjoints shall not be consid- 
ered openings for purposes of determining compliance 
with the allowable percentage of openings in Table 
705.8. 

721.2.1.3.1 Ceramic fiber joint protection. Figure 
721.2.1.3.1 shows thicknesses of ceramic fiber blan- 
kets to be used to insulate joints between precast con- 
crete wall panels for various panel thicknesses and for 
joint widths of 3/ 8 inch (9.5 mm) and 1 inch (25 mm) 



for fire-resistance ratings of 1 hour to 4 hours. For 
joint widths between 3/ 8 inch (9.5 mm) and 1 inch (25 
mm), the thickness of ceramic fiber blanket is allowed 
to be determined by direct interpolation. Other tested 
and labeled materials are acceptable in place of 
ceramic fiber blankets. 

721 .2. 1 .4 Walls with gypsum wallboard or plaster fin- 
ishes. The fire-resistance rating of cast-in-place or pre- 
cast concrete walls with finishes of gypsum wallboard or 
plaster applied to one or both sides shall be permitted to 
be calculated in accordance with the provisions of this 
section. 

721.2.1.4.1 Nonfire-exposed side. Where the finish 
of gypsum wallboard or plaster is applied to the side 
of the wall not exposed to fire, the contribution of the 
finish to the total fire-resistance rating shall be deter- 
mined as follows: The thickness of the finish shall 
first be corrected by multiplying the actual thickness 
of the finish by the applicable factor determined from 
Table 721.2.1.4(1) based on the type of aggregate in 
the concrete. The corrected thickness of finish shall 
then be added to the actual or equivalent thickness of 
concrete and fire-resistance rating of the concrete and 
finish determined from Table 721.2.1.1, Figure 
721.2.1.2 or Table 721.2.1.2(1). 

721.2.1.4.2 Fire-exposed side. Where gypsum wall- 
board or plaster is applied to the fire-exposed side of 
the wall, the contribution of the finish to the total 
fire-resistance rating shall be determined as follows: 
The time assigned to the finish as established by Table 
721.2.1.4(2) shall be added to the fire-resistance rat- 
ing determined from Table 721.2.1.1 or Figure 
721.2.1.2, or Table 721.2.1.2(1) for the concrete 
alone, or to the rating determined in Section 
721.2.1.4.1 for the concrete and finish on the 
nonfire-exposed side. 



1 IN( 


:h joir 
\ 
\ 


JT WID1 
\> 


"H \ 


^ 


\ 
\ 


A 




\\o 1 






^N 




V 




^ 


JJir^ 


% 







3 4 5 6 7 

PANEL THICKNESS, INCHES 



3 ,... 




For 51: 1 inch = 25.4 mini. 



3 4 5 6 7 

PANEL THICKNESS, INCHES 



I 
u 

z 



Q 



1 INCH MAXIMUM REGARDLESS 
OF OPENING RATING 



CERAMIC FIBER 
BLANKET 



H3 



JOINT 
WIDTH 



CARBONATE OR 

SILICEOUS AGGREGATE 

CONCRETE 

SAND-LIGHTWEIGHT 

OR LIGHTWEIGHT 

CONCRETE 



FIGURE 721.2.1.3.1 
CERAMIC FIBER JOINT PROTECTION 



148 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.2.1.4(1) 
MULTIPLYING FACTOR FOR FINISHES ON NON FIRE-EXPOSED SIDE OF WALL 



TYPE OF FINISH APPLIED TO CONCRETE OR 
CONCRETE MASONRY WALL 


TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY 


Concrete: siliceous 

or carbonate 

Concrete Masonry: 

siliceous or carbonate; 

solid clay brick 


Concrete: sand-lightweight 
Concrete Masonry: clay tile; 
hollow clay brick; concrete 
masonry units of expanded 
shale and <20% sand 


Concrete: lightweight 

Concrete Masonry: 

concrete masonry units 

of expanded shale, 

expanded clay, 
expanded slag, or 
pumice < 20% sand 


Concrete Masonry: 
concrete masonry units 

of expanded slag, 
expanded clay, or pumice 


Portland cement-sand plaster 


1.00 


0.75 3 


0.75 3 


0.50 3 


Gypsum- sand plaster 


1.25 


1.00 


1.00 


1.00 


Gypsum-vermiculite or perlite plaster 


1.75 


1.50 


1.25 


1.25 


Gypsum wallboard 


3.00 


2.25 


2.25 


2.25 



For 51 : 1 inch = 25.4 mm. 

a. For portland cement-sand plaster 5/ 8 inch or less in thickness and applied directly to the concrete or concrete masonry on the nonfire-exposed side of the wall, the 
multiplying factor shall be 1.00. 

TABLE 721.2.1.4(2) 
TIME ASSIGNED TO FINISH MATERIALS ON FIRE-EXPOSED SIDE OF WALL 



I 



FINISH DESCRIPTION 


TIME (minute) 


Gypsum wallboard 




3/ 8 inch 


10 


i/ 2 inch 


15 


5/ 8 inch 


20 


2 layers of 3/ 8 inch 


25 


1 layer 3/ 8 inch, 1 layer i/ 2 inch 


35 


2 layers i/ ? inch 


40 


Type X gypsum wallboard 




i/ 2 inch 


25 


5/ 8 inch 


40 


Portland cement-sand plaster applied directly to concrete masonry 


See Note a 


Portland cement- sand plaster on metal lath 




3/ 4 inch 


20 


7/ 8 inch 


25 


1 inch 


30 


Gypsum sand plaster on 3/ 8 -inch gypsum lath 




i/ 2 inch 


35 


5/ 8 inch 


40 


3/ 4 inch 


50 


Gypsum sand plaster on metal lath 




3/ 4 inch 


50 


7/ 8 inch 


60 


1 inch 


80 



For 51 : 1 inch = 25.4 mm. 

a. The actual thickness of portland cement-sand plaster, provided i t is 5/ 8 inch or less in thickness, shall be permitted to be included in determining the equivalent 
thickness of the masonry for use in Table 721 .3.2. 



721.2.1.4.3 Nonsymmetrical assemblies. For a wall 
having no finish on one side or different types or 
thicknesses of finish on each side, the calculation pro- 
cedures of Sections 721.2.1.4.1 and 721.2.1.4.2 shall 
be performed twice, assuming either side of the wall 
to be the fire-exposed side. The fire-resistance rating 
of the wall shall not exceed the lower of the two val- 
ues. 

Exception: For an exterior wall with afire separa- 
tion distance greater than 5 feet (1524 mm) the fire 
shall be assumed to occur on the interior side only. 



721.2.1.4.4 Minimum concrete fire-resistance rat- 
ing. Where finishes applied to one or both sides of a 
concrete wall contribute to the fire-resistance rating, 
the concrete alone shall provide not less than one-half 
of the total required fire-resistance rating. Addition- 
ally, the contribution to the fire resistance of the finish 
on the nonfire-exposed side of a load-bearing wall 
shall not exceed one-half the contribution of the con- 
crete alone. 

721. 2.1 .4. 5 Concrete finishes. Finishes on concrete 
walls that are assumed to contribute to the total 



2009 INTERNATIONAL BUILDING CODE® 



149 



FIRE AND SMOKE PROTECTION FEATURES 



fire-resistance rating of the wall shall comply with the 
installation requirements of Section 721.3.2.5. 

721.2.2 Concrete floor and roof slabs. Reinforced and 
prestressed floors and roofs shall comply with Section 
721.2.2.1. Multicourse floors and roofs shall comply with 
Sections 721.2.2.2 and 721.2.2.3, respectively. 

721.2.2.1 Reinforced and prestressed floors and 
roofs. The minimum thicknesses of reinforced and pre- 
stressed concrete floor or roof slabs for fire-resistance 
ratings of 1 hour to 4 hours are shown in Table 72 1 .2.2. 1 . 

TABLE 721.2.2.1 
MINIMUM SLAB THICKNESS (inches) 



CONCRETE TYPE 


FIRE-RESISTANCE RATING (hour) 


1 


1% 


2 


3 


4 


Siliceous 


3.5 


4.3 


5.0 


6.2 


7.0 


Carbonate 


3.2 


4.0 


4.6 


5.7 


6.6 


S and-lightweight 


2.7 


3.3 


3.8 


4.6 


5.4 


Lightweight 


2.5 


3.1 


3.6 


4.4 


5.1 



For 51: 1 inch = 25.4 mm. 

721.2.2.1.1 Hollow-core prestressed slabs. For hol- 
low-core prestressed concrete slabs in which the cores 
are of constant cross section throughout the length, 
the equivalent thickness shall be permitted to be 
obtained by dividing the net cross-sectional area of 
the slab including grout in the joints, by its width. 

721.2.2.1.2 Slabs with sloping soffits. The thickness 
of slabs with sloping soffits (see Figure 721.2.2.1.2) 
shall be determined at a distance 2t or 6 inches (152 
mm), whichever is less, from the point of minimum 
thickness, where tis the minimum thickness. 



DETERMINE THICKNESS HERE 



t + 



At 



-1 



t -t 
e 



(Equation 7-5) 



where: 

s - Spacing of ribs or undulations. 

= Minimum thickness. 

t e = Equivalent thickness of the slab calculated as 
the net area of the slab divided by the width, in 
which the maximum thickness used in the cal- 
culation shall not exceed 2t. 




•;iiai :>^j-!i h i- i ^. i :i.i « i:m ii iiwu i ni iiik:kn ks 



For 51: 1 inch = 25.4 mm. 

FIGURE 721.2.2.1.3 
SLABS WITH RIBBED OR UNDULATING SOFFITS 

721.2.2.2 Multicourse floors. The fire-resistance rat- 
ings of floors that consist of a base slab of concrete with a 
topping (overlay) of a different type of concrete shall 
comply with Figure 721.2.2.2. 

CARBONATE BASE 



fey 



^s, 


T 1 1 1 


— 1 — 


- 


>vjx4ht 


- 








" 


^Sjhr. ^v X. 


\ 


- 


i i i\ i 


1J 





SILICEOUS BASE 




*%. 


1 1 1 1 


1 


^ 


\ \4hr. 


" 




^\2 hrN. X^ 






^S^lhr. X. Xw 






j i X i 





-2tOR 6 INCHES, 
WHICHEVER IS LESS 



1 "> 3 5 3 5 

THICKNESS OF NORMAL-WEIGHT CONCRETE BASE SLAB, INCHES 



For 51: 1 inch = 25.4 mm. 



FIGURE 721.2.2.1.2 

DETERMINATION OF SLAB THICKNESS 

FOR SLOPING SOFFITS 

721.2.2.1.3 Slabs with ribbed soffits. The thickness 
of slabs with ribbed or undulating soffits (see Figure 
721.2.2.1.3) shall be determined by one of the follow- 
ing expressions, whichever is applicable: 

For s> 4t, the thickness to be used shall be t 

For s<2t, the thickness to be used shall be t e 

For At > s > 2t, the thickness to be used shall be 



CARBONATE OVERLAY 

-i r 



SILICEOUS OVERLAY 




THICKNESS OF SAND-LIGHTWEIGHT CONCRETE BASE SLAB, INCHES 

For 51 : 1 inch = 25.4 mm. 

FIGURE 721.2.2.2 

FIRE-RESISTANCE RATINGS FOR TWO-COURSE 

CONCRETE FLOORS 



150 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



721.2.2.3 Multicourse roofs. The fire-resistance ratings 
of roofs which consist of a base slab of concrete with a 
topping (overlay) of an insulating concrete or with an 
insulating board and built-up roofing shall comply with 
Figures 721.2.2.3(1) and 721.2.2.3(2). 

721.2.2.3.1 Heat transfer. For the transfer of heat, 
three-ply built-up roofing contributes 10 minutes to 
the fire-resistance rating. The fire-resistance rating 
for concrete assemblies such as those shown in Figure 
721.2.2.3(1) shall be increased by 10 minutes. This 
increase is not applicable to those shown in Figure 
721.2.2.3(2). 

721.2.2.4 Joints in precast slabs. Joints between adja- 
cent precast concrete slabs need not be considered in cal- 
culating the slab thickness provided that a concrete 
topping at least 1 inch (25 mm) thick is used. Where no 
concrete topping is used, joints must be grouted to a 
depth of at least one-third the slab thickness at the joint, 
but not less than 1 inch (25 mm), or the joints must be 
made fire resistant by other app rove d methods. 

721.2.3 Concrete cover over reinforcement. The mini- 
mum thickness of concrete cover over reinforcement in con- 
crete slabs, reinforced beams and prestressed beams shall 
comply with this section. 

721.2.3.1 Slab cover. The minimum thickness of con- 
crete cover to the positive moment reinforcement shall 
comply with Table 721.2.3(1) for reinforced concrete 
and Table 721.2.3(2) for prestressed concrete. These 
tables are applicable for solid or hollow-core one-way or 
two-way slabs with flat under surf aces. These tables are 
applicable to slabs that are either cast in place or precast. 
For precast prestressed concrete not covered elsewhere, 
the procedures contained in PCI MNL 124 shall be 
acceptable. 

721.2.3.2 Reinforced beam cover. The minimum thick- 
ness of concrete cover to the positive moment reinforce- 
ment (bottom steel) for reinforced concrete beams is 
shown in Table 721.2.3(3) for fire-resistance ratings of 1 
hour to 4 hours. 



CELLULAR CONCRETE 



4 CONCRETE *■ 




THICKNESS OF CONCRETE BASE SLAB, INCHES 



PERLITE CONCRETE 



4 CONCRETE t 




THICKNESS OF CONCRETE BASE SLAB, INCHES 



VERMICULITE CONCRETE 



W 1% 2 
°6 



CARBONATE BASE 



SILICEOUS BASE 



_ 1hr. ^Os, 







THICKNESS OF CONCRETE BASE SLAB, INCHES 



For 51 : 1 inch = 25.4 mm. 



FIGURE 721.2.2.3(1) 

FIRE-RESISTANCE RATINGS FOR CONCRETE 

ROOF ASSEMBLIES 



^Y\NA\\ MINERAL BOARD ggg 



CARBONATE BASE 




SILICEOUS BASE SAND-LIGHTWEIGHT BASE 
3 u I 1 






"1 hr. 



THICKNESS OF CONCRETE BASE SLAB. INCHES 



721.2.3.3 Prestressed beam cover. The minimum thick- 
ness of concrete cover to the positive moment 
prestressing tendons (bottom steel) for restrained and 
unrestrained prestressed concrete beams and stemmed 
units shall comply with the values shown in Tables 
721.2.3(4) and 721.2.3(5) for fire -resistance ratings of 1 
hour to 4 hours. Values in Table 721.2.3(4) apply to 
beams 8 inches (203 mm) or greater in width. Values in 
Table 721.2.3(5) apply to beams or stems of any width, 
provided the cross-section area is not less than 40 square 
inches (25 806 mm 2 ). In case of differences between the 
values determined from Table 721.2.3(4) or 721.2.3(5), 
it is permitted to use the smaller value. The concrete 
cover shall be calculated in accordance with Section 
721.2.3.3.1. The minimum concrete cover for 
nonprestressed reinforcement in prestressed concrete 
beams shall comply with Section 721.2.3.2. 



STANDARD 3-PLY 
BUILD-UP ROOFING 



mm 



.GLASS FIBER BOARD, 



WML 



SILICEOUS BASE SAND-LIGHTWEIGHT BASE 
3 u \) V I 1 1 3r 




THICKNESS OF CONCRETE BASE SLAB. INCHES 



For 51 : 1 inch = 25.4 mm. 



FIGURE 721.2.2.3(2) 

FIRE-RESISTANCE RATINGS FOR CONCRETE 

ROOF ASSEMBLIES 



2009 INTERNATIONAL BUILDING CODE® 



151 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.2.3(1) 
COVER THICKNESS FOR REINFORCED CONCRETE FLOOR OR ROOF SLABS (inches) 



CONCRETE AGGREGATE TYPE 


FIRE-RESISTANCE RATING (hours) 


Restrained 


Unrestrained 


1 


l\, 


2 


3 


4 


1 


1% 


2 


3 


4 


Siliceous 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


1 


l'/ 4 


1% 


Carbonate 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/4 


3/4 


3/4 


3/4 


l'/ 4 


l'/ 4 


Sand-lightweight or lightweight 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


l'/ 4 


l'/ 4 



For 51: 1 inch = 25.4 mm. 



TABLE 721.2.3(2) 
COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR ROOF SLABS (inches) 



CONCRETE AGGREGATE TYPE 


FIRE-RESISTANCE RATING (hours) 


Restrained 


Unrestrained 


1 


1% 


2 


3 


4 


1 


1% 


2 


3 


4 


Siliceous 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


l'/ 8 


l>/ 2 


1% 


2% 


2% 


Carbonate 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/4 


1 


1% 


l 5 / 8 


2V g 


2'/ 4 


Sand-lightweight or lightweight 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


3/ 4 


1 


1% 


l>/ 2 


2 


2'/ 4 



For 51: 1 inch =25.4i 



TABLE 721.2.3(3) 

MINIMUM COVER FOR MAIN REINFORCING BARS OF REINFORCED CONCRETE BEAMS C 

(APPLICABLE TO ALL TYPES OF STRUCTURAL CONCRETE) 



RESTRAINED OR 
UNRESTRAINED" 


BEAMWIDTH" 
(inches) 


FIRE-RESISTANCE RATING (hours) 


1 


1% 


2 


3 


4 




5 


3/4 


3/4 




3/4 




la 


1 1/ a 

i / 4 


Restrained 


7 


3/ 4 


3/4 




3/4 




3/4 


3/4 




>10 


3/4 


3/4 




3/4 




3/4 


3/4 




5 


3/ 4 


1 




1V 4 








Unrestrained 


7 


3/4 


3/4 




3/4 




1% 


3 




>10 


3/ 4 


3/ 4 




3/ 4 




1 


1% 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover 
of 3/4 inch is adequate for ratings of 4 hours or less. 

b. For beam widths between the tabulated values, the minimum cover thickness can be determined by direct interpolation. 

c . The cover for an individual reinforcing bar is the minimum thickness of concrete between the surface of the bar and the fire-exposed surface of the beam. For beams 
in which several bars are used, the cover for corner bars used in the calculation shall be reduced to one-half of the actual value. The cover for an individual bar must 
be not less than one-half of the value given in Table 721.2.3(3) nor less than 3/ 4 inch. 

TABLE 721.2.3(4) 
MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS 8 INCHES OR GREATER IN WIDTH 



RESTRAINED OR 
UNRESTRAINED 3 


CONCRETE 
AGGREGATE TYPE 


BEAMWIDTH b 
(inches) 


FIRE-RESISTANCE RATING (hours) 




1% 


2 


3 


4 


Restrained 


Carbonate or siliceous 

Carbonate or siliceous 

Sand lightweight 

Sand lightweight 


8 

> 12 
8 

> 12 


lV 2 
lV 2 
lV 2 
iV 2 


1V 2 
1V 2 
1V 2 
1V 2 


l»/ 2 
1V 2 

i'/ 2 
l»/ 2 


1V 2 
l'/ 2 
l»/ 2 


2V 

2 a 

i5, a 

1 7 8 


Unrestrained 


Carbonate or siliceous 

Carbonate or siliceous 

Sand lightweight 

Sand lightweight 


8 

> 12 
8 

> 12 


iV 2 
lV 2 

lV 2 
lV 2 


1% 

1V 2 

1V 2 
1V 2 


2V 2 

i7, a 
1 7 8 

2 

1% 


5 C 

3V 4 

2 


3 

2V 2 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover 
of 3/4 inch is adequate for 4-hour ratings or less. 

b. For beam widths between 8 inches and 12 inches, minimum cover thickness can be determined by direct interpolation. 

c. Not practical for 8-inch-wide beam but shown for purposes of interpolation. 



152 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.2.3(5) 
MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS OF ALL WIDTHS 



RESTRAINED OR 
UNRESTRAINED a 


CONCRETE 
AGGREGATE TYPE 


BEAM AREA b 
A (square inches) 


FIRE-RESISTANCE RATING (hours) 


1 


1V 2 


2 


3 


4 


Restrained 


All 


40<A<150 


iv 2 


1V 2 


2 


2V 2 


- 


Carbonate or 
siliceous 


150<A<300 


IV, 


IV, 


l 1 /, 


1% 

iv 2 


2V 2 

2 


300<A 


iv 2 


iv 2 


1V 2 


Sand lightweight 


150 <A 


iv 2 


iv 2 


1V 2 


iv 2 


2 


Unrestrained 


All 


40<A<150 


2 


2V 2 


- 


- 


- 


Carbonate or 
siliceous 


150<A<300 


l 1 /. 


1% 


2Vo 


. 


. 


300<A 


iv 2 


1V 2 


2 


3 C 


4 c 


Sand lightweight 


150 <A 


iv 2 


iv 2 


2 


3 C 


4 c 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Tabulated values for restrained assemblies apply to beams spaced more than 4 feet on center. For restrained beams spaced 4 feet or less on center, minimum cover 
of 3/ 4 inch is adequate for 4-hour ratings or less. 

b. The cross-sectional area of a stem is permitted to include a portion of the area in the flange, provided the width of the flange used in the calculation does not exceed 
three times the average width of the stem. 

c. U-shaped or hooped stirrups spaced not to exceed the depth of the member and having a minimum cover of 1 inch shall be provided. 



721.2.3.3.1 Calculating concrete cover. The con- 
crete cover for an individual tendon is the minimum 
thickness of concrete between the surface of the ten- 
don and the fire-exposed surface of the beam, except 
that for ungrouted ducts, the assumed cover thick- 
ness is the minimum thickness of concrete between 
the surface of the duct and the fire-exposed surface 
of the beam. For beams in which two or more ten- 
dons are used, the cover is assumed to be the average 
of the minimum cover of the individual tendons. For 
corner tendons (tendons equal distance from the bot- 
tom and side), the minimum cover used in the calcu- 
lation shall be one-half the actual value. For 
stemmed members with two or more prestressing 
tendons located along the vertical centerline of the 
stem, the average cover shall be the distance from the 
bottom of the member to the centroid of the tendons. 
The actual cover for any individual tendon shall not 
be less than one-half the smaller value shown in 
Tables 721.2.3(4) and 721.2.3(5), or 1 inch (25 mm), 
whichever is greater. 

721.2.4 Concrete columns. Concrete columns shall com- 
ply with this section. 

TABLE 721.2.4 
MINIMUM DIMENSION OF CONCRETE COLUMNS (inches) 



TYPES OF 
CONCRETE 


FIRE-RESISTANCE RATING (hours) 


1 


1% 


2 a 


3 a 


4 b 


Siliceous 


8 


9 


10 


12 


14 


Carbonate 


8 


9 


10 


11 


12 


Sand-lightweight 


8 


8V 2 


9 


IOV2 


12 



For 51 : 1 inch = 25 mm. 

a. The minimum dimension is permitted to be reduced to 8 inches for rectangu- 
lar columns with two parallel sides at least 36 inches in length. 

b. The minimum dimension is permitted to be reduced to 10 inches for rectan- 
gular columns with two parallel sides at least 36 inches in length. 



721.2.4.1 Minimum size. The minimum overall dimen- 
sions of reinforced concrete columns for fire-resistance 
ratings of 1 hour to 4 hours for exposure to fire on all 
sides shall comply with this section. 

721.2.4.1.1 Concrete strength less than or equal to 
12,000 psi. For columns made with concrete having a 
specified compressive strength, I'c of less than or 
equal to 12,000 psi (82.7 MPa) , the minimum dimen- 
sion shall comply with Table 721.2.4. 

721.2.4.1.2 Concrete strength greater than 12,000 
psi. For columns made with concrete having a speci- 
fied compressive strength, I'c greater than 12,000 psi 
(82.7 MPa) , for fire-resistance ratings of 1 hour to 4 
hours the minimum dimension shall be 24 inches (610 
mm). 

721.2.4.2 Minimum cover for RIC columns. The mini- 
mum thickness of concrete cover to the main longitudi- 
nal reinforcement in columns, regardless of the type of 
aggregate used in the concrete and the specified com- 
pressive strength of concrete, I'c shall not be less than 1 
inch (25 mm) times the number of hours of required fire 
resistance or 2 inches (51 mm), whichever is less. 

721.2.4.3 Tie and spiral reinforcement. For concrete 
columns made with concrete having a specified com- 
pressive strength, I'c greater than 12,000 psi (82.7 MPa) , 
tie and spiral reinforcement shall comply with the fol- 
lowing: 

1. The free ends of rectangular ties shall terminate 
with a 135-degree (2.4 rad) standard tie hook. 

2. The free ends of circular ties shall terminate with a 
gO-degree (1.6 rad) standard tie hook. 

3. The free ends of spirals, including at lap splices, 
shall terminate with a gO-degree (1.6 rad) standard 
tie hook. 



2009 INTERNATIONAL BUILDING CODE® 



153 



FIRE AND SMOKE PROTECTION FEATURES 



The hook extension at the free end of ties and spirals 
shall be the larger of six bar diameters and the extension 
required by Section 7.1.3 of ACI 318. Hooks shall pro- 
ject into the core of the column. 

721.2.4.4 Columns built into walls. The minimum 
dimensions of Table 721.2.4 do not apply to a reinforced 
concrete column that is built into a concrete or masonry 
wall provided all of the following are met: 

1. The fire-resistance rating for the wall is equal to or 
greater than the required rating of the column; 

2. The main longitudinal reinforcing in the column 
has cover not less than that required by Section 
721.2.4.2; and 

3. Openings in the wall are protected in accordance 
with Table 715.4. 

Where openings in the wall are not protected as 
required by Section 715.4, the minimum dimension of 
columns required to have a fire-resistance rating of 3 
hours or less shall be 8 inches (203 mm), and 10 inches 
(254 mm) for columns required to have a fire-resistance 
rating of 4 hours, regardless of the type of aggregate used 
in the concrete. 

721.2.4.5 Precast cover units for steel columns. See 
Section 721.5.1.4. 

721.3 Concrete masonry. The provisions of this section con- 
tain procedures by which the fire-resistance ratings of concrete 
masonry are established by calculations. 

721.3.1 Equivalent thickness. The equivalent thickness of 
concrete masonry construction shall be determined in 
accordance with the provisions of this section. 

721.3.1.1 Concrete masonry unit plus finishes. The 
equivalent thickness of concrete masonry assemblies, 
Tea' shall be computed as the sum of the equivalent thick- 
ness of the concrete masonry unit, T e , as determined by 
Section 721.3.1.2, 721.3.1.3 or 721.3.1.4, plus the equiv- 
alent thickness of finishes, T efi determined in accordance 



with Section 721.3.2: 



(Equation 7-6) 



721.3.1.2 Ungrouted or partially grouted construc- 
tion. T e shall be the value obtained for the concrete 
masonry unit determined in accordance with ASTM C 
140. 

721.3.1.3 Solid grouted construction. The equivalent 
thickness, T e , of solid grouted concrete masonry units is 
the actual thickness of the unit. 

721.3.1.4 Airspaces and cells filled with loose-fill 
material. The equivalent thickness of completely filled 
hollow concrete masonry is the actual thickness of the 
unit when loose-fill materials are: sand, pea gravel, 
crushed stone, or slag that meet ASTM C 33 require- 
ments; pumice, scoria, expanded shale, expanded clay, 
expanded slate, expanded slag, expanded fly ash, or cin- 
ders that comply with ASTM C 33 1 ; or perlite or vermic- 
ulite meeting the requirements of ASTM C 549 and 
ASTM C 516, respectively. 

721.3.2 Concrete masonry walls. The fire-resistance rat- 
ing of walls and partitions constructed of concrete masonry 
units shall be determined from Table 721.3.2. The rating 
shall be based on the equivalent thickness of the masonry 
and type of aggregate used. 

721.3.2.1 Finish on nonfire-exposed side. Where plas- 
ter or gypsum wallboard is applied to the side of the wall 
not exposed to fire, the contribution of the finish to the 
total fire-resistance rating shall be determined as fol- 
lows: The thickness of gypsum wallboard or plaster shall 
be corrected by multiplying the actual thickness of the 
finish by applicable factor determined from Table 
721.2.1.4(1). This corrected thickness of finish shall be 
added to the equivalent thickness of masonry and the 
fire-resistance rating of the masonry and finish deter- 
mined from Table 721.3.2. 

721.3.2.2 Finish on fire-exposed side. Where plaster or 
gypsum wallboard is applied to the fire-exposed side of 
the wall, the contribution of the finish to the total 
fire-resistance rating shall be determined as follows: The 
time assigned to the finish as established by Table 
721.2.1.4(2) shall be added to the fire-resistance rating 
determined in Section 721.3.2 for the masonry alone, or 



TABLE 721.3.2 
MINIMUM EQUIVALENT THICKNESS (inches) OF BEARING OR NONBEARING CONCRETE MASONRY WALLSa,b,c 


:,d 




TYPE OF AGGREGATE 


FIRE-RESISTANCE RATING (hours) 


V 2 


3/ 4 


1 


1% 


l ! / 2 


1% 


2 


2\ 


l\ 


2\ 


3 


3 ! / 4 


3h 2 


3 3 / 4 


4 


Pumice or expanded slag 


1.5 


1.9 


2.1 


2.5 


2.7 


3.0 


3.2 


3.4 


3.6 


3.8 


4.0 


4.2 


4.4 


4.5 


4.7 


Expanded shale, clay or slate 


1.8 


2.2 


2.6 


2.9 


3.3 


3.4 


3.6 


3.8 


4.0 


4.2 


4.4 


4.6 


4.8 


4.9 


5.1 


Limestone, cinders or unexpanded slag 


1.9 


2.3 


2.7 


3.1 


3.4 


3.7 


4.0 


4.3 


4.5 


4.8 


5.0 


5.2 


5.5 


5.7 


5.9 


Calcareous or siliceous gravel 


2.0 


2.4 


2.8 


3.2 


3.6 


3.9 


4.2 


4.5 


4.8 


5.0 


5.3 


5.5 


5.8 


6.0 


6.2 



For SI: 1 inch = 25.4 mm. 

a. Values between those shown in the table can be determined by direct interpolation. 

b. Where combustible members are framed into the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or between 
members set in from opposite sides, shall not be less than 93 percent of the thickness shewn in the table. 

I c. Requirements of ASTM C 55, ASTM C 73, ASTM C 90 or ASTM C 744 shall apply. 

d. Minimum required equivalent thickness corresponding to the hourly fire-resistance rating for units with a combination of aggregate shall be determined by linear 
interpolation based on the percent by volume of each aggregate used in manufacture. 



154 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



in Section 721.3.2.1 for the masonry and finish on the 
nonfire-exposed side. 

721.3.2.3 Nonsymmetrical assemblies. For a wall hav- 
ing no finish on one side or having different types or 
thicknesses of finish on each side, the calculation proce- 
dures of this section shall be performed twice, assuming 
either side of the wall to be the fire-exposed side. The 
fire-resistance rating of the wall shall not exceed the 
lower of the two values calculated. 

Exception: For exterior walls with afire separation 
distance greater than 5 feet (1524 mm) the fire shall 
be assumed to occur on the interior side only. 

721.3.2.4 Minimum concrete masonry fire-resistance 
rating. Where the finish applied to a concrete masonry 
wall contributes to its fire-resistance rating, the masonry 
alone shall provide not less than one-half the total 
required fire-resistance rating. 



TABLE 721.3.4 

MINIMUM COVER OF LONGITUDINAL 

REINFORCEMENT IN FIRE-RESISTANCE-RATED 

REINFORCED CONCRETE MASONRY LINTELS (inches) 



721.3.2.5 Attachment of finishes, 
ishes shall be as follows: 



Installation of fin- 



1. Gypsum wallboard and gypsum lath applied to 
concrete masonry or concrete walls shall be 
secured to wood or steel furring members spaced 
not more than 16 inches (406mm) on center (o.c). 

2. Gypsum wallboard shall be installed with the long 
dimension parallel to the furring members and 
shall have all joints finished. 

3. Other aspects of the installation of finishes shall 
comply with the applicable provisions of Chapters 

7 and 25. 

721.3.3 Multiwythe masonry walls. The fire-resistance 
rating of wall assemblies constructed of multiple wythes of 
masonry materials shall be permitted to be based on the 
fire-resistance rating period of each wythe and the continu- 
ous airspace between each wythe in accordance with the fol- 
lowing formula: 

R A = (RjO.59 + R 2 o.59 + ... + Rtf)59 + Al + A 2 + ... + Afjl.7 

(Equation 7-7) 



where: 
Ra = 

RpR? 

A/, Ao> 



Fire-resistance rating of the assembly (hours). 

..., R n = Fire-resistance rating of wythes for 1,2, n 
(hours), respectively. 

...., An =0.30, factor for each continuous airspace 
for 1, 2, .. .n, respectively, having a depth of 
i/ 2 inch (12.7 mm) or more between 
wythes. 

721.3.4 Concrete masonry lintels. Fire-resistance ratings for 
concrete masonry lintels shall be determined based upon the 
nominal thickness of the lintel and the minimum thickness of 
concrete masonry or concrete, or any combination thereof, 
covering the main reinforcing bars, as determined accord- 
ing to Table 721.3.4, or by approved alternate methods. 



NOMINAL WIDTH 
OF LINTEL (inches) 


FIRE-RESISTANCE RATING (hours) 


1 


2 


3 


4 


6 


iV 2 


2 






8 


IV, 


1V 2 


l 3 U 


3 


10 or greater 


IV, 


IV, 


IV, 


13/ 

1 / 4 



For 51: 1 inch = 25.4 mini. 

721 .3.5 Concrete masonry columns. The fire-resistance 
rating of concrete masonry columns shall be determined 
based upon the least plan dimension of the column in accor- 
dance with Table 721.3.5 or by approvedalternate methods. 

TABLE 721.3.5 

MINIMUM DIMENSION OF 

CONCRETE MASONRY COLUMNS (inches) 



FIRE-RESISTANCE RATING (hours) 


1 


I 2 | 3 | 


4 


8 inches 


I 10 inches | 12 inches | 


14 inches 



For 51: 1 inch = 25.4 mini. 

721.4 Clay brick and tile masonry. The provisions of this sec- 
tion contain procedures by which the fire-resistance ratings of 
clay brick and tile masonry are established by calculations. 

721 .4.1 Masonry walls. The fire-resistance rating of 
masonry walls shall be based upon the equivalent thickness 
as calculated in accordance with this section. The calcula- 
tion shall take into account finishes applied to the wall and 
airspaces between wythes in multiwythe construction. 

721.4.1.1 Equivalent thickness. The fire-resistance rat- 
ings of walls or partitions constructed of solid or hollow 
clay masonry units shall be determined from Table 
721.4.1 (1) or 721.4.1 (2). The equivalent thickness of the 
clay masonry unit shall be determined by Equation 7-8 
when using Table 721.4.1 (1). The fire-resistance rating 
determined from Table 721.4.1 (1) shall be permitted to 
be used in the calculated fire-resistance rating procedure 
in Section 721.4.2. 

T e =V n /LH (Equation 7-8) 

where: 

T e = The equivalent thickness of the clay masonry unit 
(inches) . 

V n = The net volume of the clay masonry unit (inch 3). 

L = The specified length of the clay masonry unit 
(inches) . 

H = The specified height of the clay masonry unit 
(inches) . 

721.4.1.1.1 Hollow clay units. The equivalent thick- 
ness, T e , shall be the value obtained for hollow clay 
units as determined in accordance with Equation 7-8. 
The net volume, V n , of the units shall be determined 
using the gross volume and percentage of void area 
determined in accordance with ASTM C 67. 



2009 INTERNATIONAL BUILDING CODE® 



155 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.4.1(1) 
FIRE-RESISTANCE PERIODS OF CLAY MASONRY WALLS 



MATERIAL TYPE 


MINIMUM REQUIRED EQUIVALENT THICKNESS FOR FIRE RESISTANCES, c (inches) 


1 hour 


2 hour 


3 hour 


4 hour 


Solid brick of clay or shale d 


2.7 


3.8 


4.9 


6.0 


Hollow brick or tile of clay or shale, unfilled 


2.3 


3.4 


4.3 


5.0 


Hollow brick or tile of clay or shale, grouted or filled with 
materials specified in Section 721.4.1.1.3 


3.0 


4.4 


5.5 


6.6 



For SI: 1 inch = 25.4 mm. 

a. Equivalent thickness as determined from Section 721.4.1.1. 

b. Calculated fire resistance between the hourly increments listed shall be determined by linear interpolation. 

c. Where combustible members are framed in the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or between 
members set in from opposite sides, shall not be less than 93 percent of the thickness shown. 

d. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sec- 
tional area measured in the same plane. 

TABLE 721.4.1 (2) 

FIRE-RESISTANCE RATINGS FOR BEARING STEEL FRAME 

BRICK VENEER WALLS OR PARTITIONS 



WALL OR PARTITION ASSEMBLY 


PLASTER SIDE 
EXPOSED (hours) 


BRICK FACED SIDE 
EXPOSED (hours) 


Outside facing of steel studs : 

i/ 2 " wood fiberboard sheathing next to studs, 3/ 4 " airspace formed with 

3/ 4 " x 1 5/ 8 " wood strips placed over the fiberboard and secured to the studs; 

metal or wire lath nailed to such strips, 3 3 / 4 " brick veneer held in place by filling 3/4" 

airspace between the brick and lath with mortar. Inside facing of studs: 3/ 4 " unsanded 

gypsum plaster on metal or wire lath attached to 5/ 16 " wood strips secured to edges of the 

studs. 


1.5 


4 


Outside facing of steel studs: 

1" insulation board sheathing attached to studs, 1" airspace, and 3 3 / 4 " brick veneer 

attached to steel frame with metal ties every 5th course. Inside facing of studs: 7/ 8 " 

sanded gypsum plaster (1:2 mix) applied on metal or wire lath attached directly to the 

studs. 


1.5 


4 


Same as above except use 7/ 8 " vermiculite-gypsum plaster or 1" sanded gypsum plaster 
(1:2 mix) applied to metal or wire. 


2 


4 


Outside facing of steel studs : 

i/ 2 " gypsum sheathing board, attached to studs, and 3 3 / 4 " brick veneer attached to steel 
frame with metal ties every 5th course. Inside facing of studs: i/ 2 " sanded gypsum plaster 
(1:2 mix) applied to i/ 2 " perforated gypsum lath securely attached to studs and having 
strips of metal lath 3 inches wide applied to all horizontal joints of gypsum lath. 


2 


4 



For SI: 1 inch = 25.4 mm. 



721.4.1.1.2 Solid grouted clay units. The equivalent 
thickness of solid grouted clay masonry units shall be 
taken as the actual thickness of the units. 

721.4.1.1.3 Units with filled cores. The equivalent 
thickness of the hollow clay masonry units is the 
actual thickness of the unit when completely filled 
with loose-fill materials of: sand, pea gravel, crushed 
stone, or slag that meet ASTM C 33 requirements; 
pumice, scoria, expanded shale, expanded clay, 
expanded slate, expanded slag, expanded fly ash, or 
cinders in compliance with ASTM C 33 1 ; or perlite or 
vermiculite meeting the requirements of ASTM C 
549 and ASTM C 516, respectively. 

721.4.1.2 Plaster finishes. Where plaster is applied to 
the wall, the total fire-resistance rating shall be deter- 
mined by the formula: 



where: 

R = The fire-resistance rating of the assembly (hours). 

R n = The fire-resistance rating of the individual wall 
(hours). 

pi = Coefficient for thickness of plaster. 

Values for R n o.59 for use in Equation 7-9 are given in 
Table 721.4.1(3). Coefficients for thickness of plaster 
shall be selected from Table 721.4.1 (4) based on the 
actual thickness of plaster applied to the wall or partition 
and whether one or two sides of the wall are plastered. 

721.4.1.3 Multiwythe walls with airspace. Where a 
continuous airspace separates multiple wythes of the 
wall or partition, the total fire-resistance rating shall be 
determined by the formula: 



R={R n °™ + pl) 1J 



(Equation 7-9) 



R=(Ri° 



-R 2 °- 59 + ...+R n °- 59 +as) u 



(Equation 7-10) 



156 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



where: 

R The fire-resistance rating of the assem- 

bly (hours). 

R P R 2 and R n = The fire-resistance rating of the individ- 
ual wythes (hours). 

as Coefficient for continuous airspace. 

Values for R n o.59 for use in Equation 7-10 are given in 
Table 721.4.1 (3). The coefficient for each continuous 
airspace of V 2 inch to 3V 2 inches (12.7 to 89 mm) separat- 
ing two individual wythes shall be 0.3. 

TABLE 721.4.1 (3) 
VALUES OF R o. 59 



R 0.59 
n 


R(hours) 


1 


1.0 


2 


1.50 


3 


1.91 


4 


2.27 



TABLE 721.4.1 (4) 
COEFFICIENTS FOR PLASTER, pia 


THICKNESS OF 
PLASTER (inch) 


ONE SIDE 


TWO SIDE 


17 2 


0.3 


0.6 


5/ 8 


0.37 


0.75 


3/ 4 


0.45 


0.90 



For 51: 1 inch = 25.4 mm. 

a. Values listed in table are for 1:3 sanded gypsum plaster. 

TABLE 721.4.1 (5) 
REINFORCED MASONRY LINTELS 



NOMINAL 

LINTEL WIDTH 

(inches) 


MINIMUM L 


DNGITUDINAL 
FOR FIRF RFS 


REINFORCEMENT COVER 
STANP.F (inohO 


1 hour 


2hour 


3 hour 


4 hour 


6 


lV 2 


2 


NP 


NP 


8 


1V 2 


1V 2 


1% 


3 


10 or more 


1V 2 


1V 2 


lV 2 


1% 



For 51 : 1 inch = 25.4 mm. 
NP =Not permitted. 



TABLE 721.4.1 (6) 
REINFORCED CLAY MASONRY COLUMNS 



COLUMN SIZE 


FIRE-RESISTANCE RATING 
(hour) 


1 | 2 | 3 | 4 


Minimum column dimension (inches) 


8 i 10 I 12 I 14 



For 51: 1 inch = 25.4 mm. 



721.4.1.4 Nonsymmetrical assemblies. For a wall hav- 
ing no finish on one side or having different types or 
thicknesses of finish on each side, the calculation proce- 
dures of this section shall be performed twice, assuming 



either side to be the fire-exposed side of the wall. The fire 
resistance of the wall shall not exceed the lower of the 
two values determined. 

Exception: For exterior walls with a fire separation 
distance greater than 5 feet (1524 mm), the fire shall 
be assumed to occur on the interior side only. 

721.4.2 Multiwythe walls. The fire-resistance rating for 
walls or partitions consisting of two or more dissimilar 
wythes shall be permitted to be determined by the formula: 



R= (Rf.59 + R 2 o.59 + ... +R n c 



where: 
R 



(Equation 7-11) 



= The fire-resistance rating of the assembly 
(hours). 

Rj, R 2 and R n = The fire-resistance rating of the individual 
wythes (hours). 

Values for R n o.59 for use in Equation 7-11 are given in 
Table 721.4.1 (3). 

121 A. 2.1 Multiwythe walls of different material. For 
walls that consist of two or more wythes of different 
materials (concrete or concrete masonry units) in combi- 
nation with clay masonry units, the, fire-resistance rating 
of the different materials shall be permitted to be deter- 
mined from Table 721.2.1.1 for concrete; Table 721.3.2 
for concrete masonry units or Table 721.4.1 (1) or 
721.4.1 (2) for clay and tile masonry units. 

721.4.3 Reinforced clay masonry lintels. Fire-resistance 
ratings for clay masonry lintels shall be determined based 
on the nominal width of the lintel and the minimum cover- 
ing for the longitudinal reinforcement in accordance with 
Table 721.4.1 (5). 

721.4.4 Reinforced clay masonry columns. The fire-resis- 
tance ratings shall be determined based on the last plan 
dimension of the column in accordance with Table 
721.4.1 (6). The minimum cover for longitudinal reinforce- 
ment shall be 2 inches (51 mm). 

721.5 Steel assemblies. The provisions of this section contain 
procedures by which the fire-resistance ratings of steel assem- 
blies are established by calculations. 

721.5.1 Structural steel columns. The fire-resistance rat- 
ings of steel columns shall be based on the size of the ele- 
ment and the type of protection provided in accordance with 
this section. 

721.5.1.1 General. These procedures establish a basis 
for determining the fire resistance of column assemblies 
as a function of the thickness of fire-resistant material 
and, the weight, Wand heated perimeter, D, of steel col- 
umns. As used in these sections, Wis the average weight 
of a structural steel column in pounds per linear foot. The 
heated perimeter, D, is the inside perimeter of the 
fire-resistant material in inches as illustrated in Figure 
721.5.1 (1). 



2009 INTERNATIONAL BUILDING CODE® 



157 



FIRE AND SMOKE PROTECTION FEATURES 




mm* 



D=4bf+2d-2t w 



D=2(a+d) 



D=2(bf+ d} 



FIGURE 721.5.1(1) 

DETERMINATION OF THE HEATED PERIMETER 

OF STRUCTURAL STEEL COLUMNS 



721.5.1.1.1 Nonload-bearing protection. The appli- 
cation of these procedures shall be limited to column 
assemblies in which the fire-resistant material is not 
designed to carry any of the load acting on the col- 
umn. 

721.5.1.1.2 Embedments. In the absence of substan- 
tiating fire-endurance test results, ducts, conduit, pip- 
ing, and similar mechanical, electrical, and plumbing 
installations shall not be embedded in any required 
fire-resistant materials. 

721.5.1.1.3 Weight-to-perimeter ratio. Table 
721.5.1 (1) contains weight- to-heated-perimeter ratios 
(WID) for both contour and box fire-resistant profiles, 
for the wide flange shapes most often used as columns. 
For different fire-resistant protection profiles or col- 
umn cross sections, the weight-to-heated-perimeter 
ratios (WID) shall be determined in accordance with 
the definitions given in this section. 

721.5.1.2 Gypsum wallboard protection. The fire 
resistance of structural steel columns with weight- 
to-heated-perimeter ratios (WID) less than or equal to 
3.65 and which are protected with Type X gypsum wall- 
board shall be permitted to be determined from the fol- 
lowing expression: 



h(w,D)]0.75 

R=I30 [ 2 



721.5.1.2.1 Attachment. The gypsum wallboard 
shall be supported as illustrated in either Figure 
721.5.1 (2) for fire-resistance ratings of 4 hours or 
less, or Figure 721.5.1 (3) for fire-resistance ratings of 
3 hours or less. 







f 


1> 






f 




^ 






























/ 






■ 


ft 












SHEET STEEL 


A 'b — 

L 5ffl " .i 


I 


7 " 

No.8x112" 


, L i 


-A 


»|jb*J 


c 




\ 




5/16" 
MIN. 




I 

3/4" 




SNAP-LOCK 


PITISBURGH SEAM 
CORNER JOINT DETAILS (A) 


LAP 







(Equation 7-12) 



FIGURE 721.5.1(2) 
GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL 
COLUMNS WITH SHEET STEEL COLUMN COVERS 
For SI: 1 inch = 25.4 mm, 1 foot = 305 mm. 

1. Structural steel column, either wide flange or tubular shapes. 

2. Type X gypsum wallboard in accordance with ASTM C 36. For single-layer 
applications, the wallboard shall be applied vertically with no horizontal 
joints. For multiple-layer applications, horizontal joints are permitted at a 
minimum spacing of 8 feet, provided that the joints in successive layers are 
staggered at least 12 inches. The total required thickness of wallboard shall 
be determined on the basis of the specified fire -resistance rating and the 
weight-to-heated-perimeter ratio (WID) of the column. For fire-resistance 
ratings of 2 hours or less, one of the required layers of gypsum wallboard 
may be applied to the exterior of the sheet steel column covers with 1-inch- 
long Type S screws spaced 1 inch from the wallboard edge and 8 inches on 
center. For such installations, 0.0149-inch minimum thickness galvanized 
steel corner beads with l 1 / 2 -inch legs shall be attached to the wallboard with 
Type S screws spaced 12 inches on center. 

3. For fire-resistance ratings of 3 hours or less, the column covers shall be fabri- 
cated from 0.0239-inch minimum thickness galvanized or stainless steel. 
For 4-hourfire-resistance ratings, the column covers shall be fabricated from 
0.0239-inch minimum thickness stainless steel. The column covers shall be 
erected with the Snap Lock or Pittsburgh joint details. 

For fire-resistance ratings of 2 hours or less, column covers fabricated from 
0.0269-inch minimum thickness galvanized or stainless steel shall be permit- 
ted to be erected with lapjoints. The lap joints shall be permitted to be located 
anywhere around the perimeter of the column cover. The lapjoints shall be 
secured with i/ 2 -inch-Iong No. 8 sheet metal screws spaced 12 inches on cen- 
ter. 

The column covers shall be provided with a minimum expansion clearance 
of i/ 8 inch per linear foot between the ends of the cover and any restraining 
construction. 



where: 
R 
h 
D 



W 



W 



Fire resistance (minutes). 

Total thickness of gypsum wallboard (inches) . 

Heated perimeter of the structural steel column 
(inches) . 

Total weight of the structural steel column and 
gypsum wallboard protection (pounds per linear 
foot). 

W+ 50HD/I44. 



721.5.1.2.2 Gypsum wallboard equivalent to con- 
crete. The determination of the fire resistance of 
structural steel columns from Figure 721.5.1(4) is 
permitted for various thicknesses of gypsum wall- 
board as a function of the weight-to- heated-perimeter 
ratio (WID) of the column. For structural steel col- 
umns with weight-to-heated-perimeter ratios (WID) 
greater than 3.65, the thickness of gypsum wallboard 
required for specified fire -resistance ratings shall be 
the same as the thickness determined for a W14 x 233 
wide flange shape. 



158 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



721.5.1.3 Sprayed fire-resistant materials. The fire 
resistance of wide-flange structural steel columns pro- 
tected with sprayed fire-resistant materials, as illustrated 
in Figure 721.5.1 (5), shall be permitted to be determined 
from the following expression: 

R=\C X (Wl D) + C 2 ] h (Equation 7-13) 

where: 

R = Fire resistance (minutes). 

h = Thickness of sprayed fire-resistant material 
(inches) . 

D = Heated perimeter of the structural steel column 
(inches) . 

Q and Q = Material-dependent constants. 

W = Weight of structural steel columns (pounds per lin- 
ear foot). 

The fire resistance of structural steel columns pro- 
tected with intumescent or mastic fire-resistant coatings 





shall be determined on the basis of fire-resistance tests in 
accordance with Section 703.2. 

721.5.1.3.1 Material-dependent constants. The 

material-dependent constants, Q and C 2 , shall be 
determined for specific fire-resistant materials on the 
basis of standard fire endurance tests in accordance 
with Section 703.2. Unless evidence is submitted to 
the building official substantiating a broader applica- 
tion, this expression shall be limited to determining 
the fire resistance of structural steel columns with 
weight-to-heated-perimeter ratios (WID) between the 
largest and smallest columns for which standard 
fire-resistance test results are available. 



2lfT 



1 






-■«■ 



as 



1.0 



1.5 



3Q 



25 



3*1 



35 



3 LAYERS = 1 7/8" OR 1 1/2" 



4 LAYERS = 21/2" OR 2" 



FIGURE 721.5.1(3) 

GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL 

COLUMNS WITH STEEL STUD/SCREW ATTACHMENT SYSTEM 

For SI: 1 inch = 25.4 mm, 1 foot = -305 mm. 

1. Structural steel column, either wide flange or tubular shapes. 

2. I s / 8 -inch deep studs fabricated from 0.0179-inch minimum thickness galva- 
nized steel with IS/16 or l 7 / 16 -inch legs. The length of the steel studs shall be 
l/zinch less than the height of the assembly. 

3. Type X gypsum wallboard in accordance with ASTM C 36. For single-layer 
applications, the wallboard shall be applied vertically with no horizontal 
joints. For multiple-layer applications, horizontal joints are permitted at a 
minimum spacing of 8 feet, provided that the joints in successive layers are 
staggered at least 12 inches. The total required thickness of wallboard shall 
be determined on the basis of the specified fire-resistance rating and the 
weight-to-heated-perimeter ratio (WID) of the column. 

4. Galvanized 0.0149-inch minimum thickness steel corner beads with 
lV^inch legs attached to the wallboard with 1-inch-Iong Type S screws 
spaced 12 inches on center. 

5. No. 18 SWG steel tie wires spaced 24 inches on center. 

6. Sheet metal angles with 2-inch legs fabricated from 0.0221 -inch minimum 
thickness galvanized steel. 

7. Type S screws, 1 inch long, shall be used for attaching the first layer of wall- 
board to the steel studs and the third layer to the sheet metal angles at 24 inches 
on center. Type S screws l 3 / 4 -inch long shall be used for attaching the second 
layer of wallboard to the steel studs and the fourth layer to the sheet metal 
angles at 12 inches on center. Type S screws 2v 4 inches long shall be used for 
attaching the third layer of wallboard to the steel studs at 12 inches on center. 



For SI: 1 inch = 25.4 mm, 1 pound per linear foot/inch = 0.059 kg/m/mm. 

FIGURE 721.5.1 (4) 

FIRE RESISTANCE OF STRUCTURAL STEEL COLUMNS 

PROTECTED WITH VARIOUS THICKNESSES OF 

TYPE X GYPSUM WALLBOARD 

a. The WID ratios for typical wide flange columns are listed in Table 
721.5 . 1(1) . For other column shapes, the WID ratios shall be determined in 
accordance with Section 720.5.1.1. 




FIGURE 721.5.1(5) 

WIDE FLANGE STRUCTURAL STEEL COLUMNS WITH 

SPRAYED FIRE-RESISTANT MATERIALS 



2009 INTERNATIONAL BUILDING CODE® 



159 



FIRE AND SMOKE PROTECTION FEATURES 



121.5.13.2 Identification. Sprayed fire-resistant 
materials shall be identified by density and thickness 
required for a given fire-resistance rating. 

721.5.1.4 Concrete-protected columns. The fire resis- 
tance of structural steel columns protected with con- 
crete, as illustrated in Figure 721.5.1(6) (a) and (b), shall 
be permitted to be determined from the following expres- 
sion: 

R= R (1 + 0.03 J (Equation 7-14) 

where: 

R = 10 ( W/Dj o.7 + 17 (#-6/jy>.2) x [1 + 26 {H/p cC( h (L + h)}o.«\ 

As used in these expressions: 

R = Fire endurance at equilibrium moisture conditions 
(minutes). 

R = Fire endurance at zero moisture content (minutes). 

m = Equilibrium moisture content of the concrete by 
volume (percent). 

W = Average weight of the steel column (pounds per 
linear foot). 

= Heated perimeter of the steel column (inches). 

= Thickness of the concrete cover (inches). 



: Ambient temperature thermal conductivity of the 
concrete (Btu/hr ft OF). 

H = Ambient temperature thermal capacity of the steel 
column = 0. 1 1 W (Btu/ ft OF). 

Pc = Concrete density (pounds per cubic foot). 

cc = Ambient temperature specific heat of concrete 
(Btu/lb OF). 

L = Interior dimension of one side of a square concrete 
box protection (inches). 

721.5.1.4.1 Reentrant space filled. For wide-flange 
steel columns completely encased in concrete with all 
reentrant spaces filled [Figure 721.5.1 (6) (c)], the 
thermal capacity of the concrete within the reentrant 
spaces shall be permitted to be added to the thermal 
capacity of the steel column, as follows: 



H=0.ll W+ (Pocjl44) (bjd-A) 
where: 



(Equation 7-15) 



b r Flange width of the steel column (inches). 

d Depth of the steel column (inches). 

As Cross-sectional area of the steel column 
(square inches). 

721.5.1.4.2 Concrete properties unknown. If spe- 
cific data on the properties of concrete are not avail- 
able, the values given in Table 721.5.1 (2) are 
permitted. 

721.5.1.4.3 Minimum concrete cover. For structural 
steel column encased in concrete with all reentrant 
spaces filled, Figure 721.5.1(6)(c) and Tables 
721.5.1(7) and 721.5.1(8) indicate the thickness of 



concrete cover required for various fire -resistance 
ratings for typical wide-flange sections. The thick- 
nesses of concrete indicated in these tables also apply 
to structural steel columns larger than those listed. 

721.5.1.4.4 Minimum precast concrete cover. For 
structural steel columns protected with precast con- 
crete column covers as shown in Figure 
721.5. l(6)(a), Tables 721.5.1(9) and 721.5.1(10) 
indicate the thickness of the column covers required 
for various fire-resistance ratings for typical 
wide-flange shapes. The thicknesses of concrete 
given in these tables also apply to structural steel col- 
umns larger than those listed. 



ff*ff 




*m 



tm 



**■ 



wmi—*- 



-A s 



(a) 


(b) 


(c) 


PRECAST 


CONCRETE 


CONCRETE 


CONCRETE 


ENCASED 


ENCASED 


COLUMN 


STRUCTURAL 


WIDE-FLANGE 


COVERS 


TUBE 


SHAPE 



FIGURE 721.5.1(6) 
CONCRETE PROTECTED STRUCTURAL STEEL COLUMNSa,b 

. When the inside perimeter of the concrete protection is not square , L shall be 

taken as the average of L t and L z . When the thickness of concrete cover is not 

constant, h shall be taken as the average of hi and h z . 
». Joints shall be protected with a minimum 1 inch thickness of ceramic fiber 

blanket but in no case less than one-half the thickness of the column cover 

(see Section 720.2.1.3). 

721.5.1.4.5 Masonry protection. The fire resistance 
of structural steel columns protected with concrete 
masonry units or clay masonry units as illustrated in 
Figure 721.5.1(7), shall be permitted to be deter- 
mined from the following expression: 

R= 0.17 (W/D)0.7+ [0.285 (T e h VK° 2 ) ] 

[1.0 + 42.7 { (A/d m T e) i (0.25p + Tj j o.s ] 

(Equation 7-16) 



where: 
R 

W 



K 



Fire-resistance rating of column assembly 
(hours). 

Average weight of steel column (pounds per 
foot) . 

Heated perimeter of steel column (inches) 
[see Figure 721.5.1 (7)]. 

Equivalent thickness of concrete or clay ma- 
sonry unit (inches) (see Table 721.3.2 Note a 
or Section 721.4.1). 

Thermal conductivity of concrete or clay ma- 
sonry unit (Btu/hr ft OF) [see Table 
721.5.1(3)]. 

Cross-sectional area of steel column (square 
inches). 



160 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



Density of the concrete or clay masonry unit 
(pounds per cubic foot). 

Inner perimeter of concrete or clay masonry 
protection (inches) [see Figure 721.5.1 (7)]. 









_ » _ 












1 


1 1 


1 


a 
a 
n 


DDG 




■" 


~ir 


D 


- 


L - 


o 


1 

L 
C 


- 






1 1 


1 


coa 




ii 



_BEfc_ 
STfctLFFFCGfcLiNN - 



For 51 : 1 inch = 25.4 mm. 

FIGURE 721.5.1(7) 

CONCRETE OR CLAY MASONRY PROTECTED 

STRUCTURAL STEEL COLUMNS 

d = Depth of a wide flange column, outside diameter of pipe column, or out- 
side dimension of structural tubing column (inches) . 
t Vfi) = Thickness of web of wide flange column (inches). 
w = Width of flange of wide flange column (inches). 

721.5.1.4.6 Equivalent concrete masonry thick- 
ness. For structural steel columns protected with con- 
crete masonry, Table 721.5.1 (5) gives the equivalent 
thickness of concrete masonry required for various 
fire-resistance ratings for typical column shapes. For 
structural steel columns protected with clay masonry, 
Table 721.5.1 (6) gives the equivalent thickness of 
concrete masonry required for various fire-resistance 
ratings for typical column shapes. 

721.5.2 Structural steel beams and girders. The 
fire-resistance ratings of steel beams and girders shall be 
based upon the size of the element and the type of protection 
provided in accordance with this section. 

721.5.2.1 Determination of fire resistance. These pro- 
cedures establish a basis for determining resistance of 
structural steel beams and girders which differ in size 
from that specified in approved fire-resistance-rated 
assemblies as a function of the thickness of fire-resistant 
material and the weight ( W) and heated perimeter (D) of 
the beam or girder. As used in these sections, Wis the 
average weight of a structural steel member in pounds 
per linear foot (plf). The heated perimeter, D, is the inside 
perimeter of the fire-resistant material in inches as illus- 
trated in Figure 721.5.2. 

721.5.2.1.1 Weight-to-heated perimeter. The 
weight-to-heated-perimeter ratios (WID), for both 
contour and box fire-resistant protection profiles, for 
the wide flange shapes most often used as beams or 
girders are given in Table 721.5.1(4). For different 
shapes, the weight-to-heated-perimeter ratios (WID) 
shall be determined in accordance with the definitions 
given in this section. 




D-at + H^, 



U T / I * fa , 



FIGURE 721.5.2 
DETERMINATION OF THE HEATED PERIMETER 
OF STRUCTURAL STEEL BEAMS AND GIRDERS 

721.5.2.1.2 Beam and girder substitutions. Except 
as provided for in Section 721.5.2.2, structural steel 
beams in approved fire-resistance-rated assemblies 
shall be considered the minimum permissible size. 
Other beam or girder shapes shall be permitted to be 
substituted provided that the weight-to-heated-perim- 
eter ratio (WID) of the substitute beam is equal to or 
greater than that of the beam specified in the approved 
assembly. 

721.5.2.2 Sprayed fire-resistant materials. The provi- 
sions in this section apply to structural steel beams and 
girders protected with sprayed fire-resistant materials. 
Larger or smaller beam and girder shapes shall be per- 
mitted to be substituted for beams specified in approved 
unrestrained or restrained fire-resistance-rated assem- 
blies, provided that the thickness of the fire-resistant 
material is adjusted in accordance with the following 
expression: 

h 2 =h, [(W, I Dj)+ 0.60] / [(W 2 1 D 2) + 0.60] 



(Equation 7-17) 



where: 



h = Thickness of sprayed fire-resistant material in 
inches. 

W = Weight of the structural steel beam or girder in 
pounds per linear foot. 

D = Heated perimeter of the structural steel beam in 
inches. 

Subscript 1 refers to the beam and fire-resistant mate- 
rial thickness in the approved assembly. 

Subscript 2 refers to the substitute beam or girder and 
the required thickness of fire-resistant material. 

The //re resistance of structural steel beams and gird- 
ers protected with intumescent or mastic fire-resistant 
coatings shall be determined on the basis of fire- resis- 
tance tests in accordance with Section 703.2. 



2009 INTERNATIONAL BUILDING CODE® 



161 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (1) 
WID RATIOS FOR STEEL COLUMNS 



STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


W14 x 233 


2.49 


3.65 


WlOx 112 


1.78 


2.57 


x211 


2.28 


3.35 


x 100 


1.61 


2.33 


x 193 


2.10 


3.09 


x 88 


1.43 


2.08 


x 176 


1.93 


2.85 


x 77 


1.26 


1.85 


x 159 


1.75 


2.60 


x 68 


1.13 


1.66 


x 145 


1.61 


2.39 


x 60 


1.00 


1.48 


x 132 


1.52 


2.25 


x 54 


0.91 


1.34 


x 120 


1.39 


2.06 


x 49 


0.83 


1.23 


x 109 


1.27 


1.88 


x 45 


0.87 


1.24 


x 99 


1.16 


1.72 


x 39 


0.76 


1.09 


x 90 


1.06 


1.58 


x 33 


0.65 


0.93 


x 82 


1.20 


1.68 




x 74 


1.09 


1.53 


W8 x67 


1.34 


1.94 


x 68 


1.01 


1.41 


x58 


1.18 


1.71 


x 61 


0.91 


1.28 


x48 


0.995 


1.44 


x 53 


0.89 


1.21 


x40 


0.83 


1.23 


x 48 


0.81 


1.10 


x 35 


0.73 


1.08 


x 43 


0.73 


0.99 


x 31 


0.65 


0.97 




x 28 


0.67 


0.96 


W12 x 190 


2.46 


3.51 


x 24 


0.58 


0.83 


x 170 


2.22 


3.20 


x 21 


0.57 


0.77 


x 152 


2.01 


2.90 


x 18 


0.49 


0.67 


x 136 


1.82 


2.63 




x 120 


1.62 


2.36 


W6x25 


0.69 


1.00 


x 106 


1.44 


2.11 


x20 


0.56 


0.82 


x 96 


1.32 


1.93 


x 16 


0.57 


0.78 


x 87 


1.20 


1.76 


x 15 


0.42 


0.63 


x 79 


1.10 


1.61 


x 12 


0.43 


0.60 


x 72 


1.00 


1.48 


x 9 


0.33 


0.46 


x 65 


0.91 


1.35 




x 58 


0.91 


1.31 


W5 x 19 


0.64 


0.93 


x 53 


0.84 


1.20 


x 16 


0.54 


0.80 


x 50 


0.89 


1.23 




x 45 


0.81 


1.12 


W4x 13 


0.54 


0.79 


x 40 


0.72 


1.00 





For SI: 1 pound per linear foot per inch = 0.059 kg/m/mm. 



162 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (2) 
PROPERTIES OF CONCRETE 



PROPERTY 


NORMAL-WEIGHT CONCRETE 


STRUCTURAL LIGHTWEIGHT CONCRETE 


Thermal conductivity (k) 


0.95 Btu/hr . ft . OF 


0.35 Btu/hr . ft . OF 


Specific heat (cj 


0.20 Btu/lb of 


0.20 Btu/lb of 


Density (P) 


145lb/ft 3 


HOlb/ft 3 


Equilibrium (free) moisture 
content (m) by volume 


4% 


5% 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 lb/ft 3 = 16.0185 kg/m 3 , Btu/hr- ft- of = 1.731 W/(m- K). 



TABLE 721.5.1 (3) 

THERMAL CONDUCTIVITY OF CONCRETE OR CLAY 

MASONRY UNITS 



DENSITY (dj OF UNITS (lb/ft 3 ) 


THERMAL CONDUCTIVITY (K) OF UNITS (Btu/hr .ft . OF) 


Concrete Masonry Units 


80 


0.207 


85 


0.228 


90 


0.252 


95 


0.278 


100 


0.308 


105 


0.340 


110 


0.376 


115 


0.416 


120 


0.459 


125 


0.508 


130 


0.561 


135 


0.620 


140 


0.685 


145 


0.758 


150 


0.837 


Clay Masonry Units 


120 


1.25 


130 


2.25 



For 51: 1 pound per cubic foot = 16.0185 kg/m 3 , Btu per hour- foot- OF = 1.731 W/(m- K). 



2009 INTERNATIONAL BUILDING CODE® 



163 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (4) 

WEIGHT-TO-HEATED-PERIMETER RATIOS (WID) 

FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES 



STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


W36 x 300 


2.47 


3.33 


x 68 


0.92 


1.21 


x280 


2.31 


3.12 


x 62 


0.92 


1.14 


x260 


2.16 


2.92 


x 55 


0.82 


1.02 


x245 


2.04 


2.76 








x230 


1.92 


2.61 


W21 x 147 


1.83 


2.60 


x210 


1.94 


2.45 


x 132 


1.66 


2.35 


x 194 


1.80 


2.28 


x 122 


1.54 


2.19 


x 182 


1.69 


2.15 


xlll 


1.41 


2.01 


x 170 


1.59 


2.01 


x 101 


1.29 


1.84 


x 160 


1.50 


1.90 


x 93 


1.38 


1.80 


x 150 


1.41 


1.79 


x 83 


1.24 


1.62 


x 135 


1.28 


1.63 


x 73 


1.10 


1.44 




x 68 


1.03 


1.35 


W33 x 241 


2.11 


2.86 


x 62 


0.94 


1.23 


x221 


1.94 


2.64 


x 57 


0.93 


1.17 


x201 


1.78 


2.42 


x 50 


0.83 


1.04 


x 152 


1.51 


1.94 


x 44 


0.73 


0.92 


x 141 


1.41 


1.80 




x 130 


1.31 


1.67 


W18 x 119 


1.69 


2.42 


x 118 


1.19 


1.53 


x 106 


1.52 


2.18 




x 97 


1.39 


2.01 


W30x211 


2.00 


2.74 


x 86 


1.24 


1.80 


x 191 


1.82 


2.50 


x 76 


1.11 


1.60 


x 173 


1.66 


2.28 


x 71 


1.21 


1.59 


x 132 


1.45 


1.85 


x 65 


1.11 


1.47 


x 124 


1.37 


1.75 


x 60 


1.03 


1.36 


x 116 


1.28 


1.65 


x 55 


0.95 


1.26 


x 108 


1.20 


1.54 


x 50 


0.87 


1.15 


x 99 


1.10 


1.42 


x 46 


0.86 


1.09 




x 40 


0.75 


0.96 


W27 x 178 


1.85 


2.55 


x 35 


0.66 


0.85 


x 161 


1.68 


2.33 




x 146 


1.53 


2.12 


W16 x 100 


1.56 


2.25 


x 114 


1.36 


1.76 


x 89 


1.40 


2.03 


x 102 


1.23 


1.59 


x 77 


1.22 


1.78 


x 94 


1.13 


1.47 


x 67 


1.07 


1.56 


x 84 


1.02 


1.33 


x 57 


1.07 


1.43 




x 50 


0.94 


1.26 




x 45 


0.85 


1.15 


W24 x 162 


1.85 


2.57 


x 40 


0.76 


1.03 


x 146 


1.68 


2.34 


x 36 


0.69 


0.93 


x 131 


1.52 


2.12 


x 31 


0.65 


0.83 


x 117 


1.36 


1.91 


x 26 


0.55 


0.70 


x 104 


1.22 


1.71 




x 94 


1.26 


1.63 


W14 x 132 


1.83 


3.00 


x 84 


1.13 


1.47 


x 120 


1.67 


2.75 


x 76 


1.03 


1.34 


x 109 


1.53 


2.52 



(continued) 



164 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (4)-continued 

WEIGHT-TO-HEATED-PERIMETER RATIOS (WID) 

FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES 



STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


STRUCTURAL 
SHAPE 


CONTOUR 
PROFILE 


BOX 
PROFILE 


x 99 


1.39 


2.31 


x 30 


0.79 


1.12 


x 90 


1.27 


2.11 


x 26 


0.69 


0.98 


x 82 


1.41 


2.12 


x 22 


0.59 


0.84 


x 74 


1.28 


1.93 


x 19 


0.59 


0.78 


x 68 


1.19 


1.78 


x 17 


0.54 


0.70 


x 61 


1.07 


1.61 


x 15 


0.48 


0.63 


x 53 


1.03 


1.48 


x 12 


0.38 


0.51 


x 48 


0.94 


1.35 




x 43 


0.85 


1.22 


W8 x 67 


1.61 


2.55 


x 38 


0.79 


1.09 


x 58 


1.41 


2.26 


x 34 


0.71 


0.98 


x 48 


1.18 


1.91 


x 30 


0.63 


0.87 


x 40 


1.00 


1.63 


x 26 


0.61 


0.79 


x 35 


0.88 


1.44 


x 22 


0.52 


0.68 


x 31 


0.79 


1.29 




x 28 


0.80 


1.24 


W12 x 87 


1.44 


2.34 


x 24 


0.69 


1.07 


x 79 


1.32 


2.14 


x 21 


0.66 


0.96 


x 72 


1.20 


1.97 


x 18 


0.57 


0.84 


x 65 


1.09 


1.79 


x 15 


0.54 


0.74 


x 58 


1.08 


1.69 


x 13 


0.47 


0.65 


x 53 


0.99 


1.55 


X 10 


0.37 


0.51 


x 50 


1.04 


1.54 




x 45 


0.95 


1.40 


W6 x 25 


0.82 


1.33 


x 40 


0.85 


1.25 


x 20 


0.67 


1.09 


x 35 


0.79 


1.11 


x 16 


0.66 


0.96 


x 30 


0.69 


0.96 


x 15 


0.51 


0.83 


x 26 


0.60 


0.84 


x 12 


0.51 


0.75 


x 22 


0.61 


0.77 


x 9 


0.39 


0.57 


x 19 


0.53 


0.67 




x 16 


0.45 


0.57 


W5 x 19 


0.76 


1.24 


x 14 


0.40 


0.50 


x 16 


0.65 


1.07 






WlOx 112 


2.14 


3.38 


W4 x 13 


0.65 


1.05 


x 100 


1.93 


3.07 




x 88 


1.70 


2.75 


x 77 


1.52 


2.45 


x 68 


1.35 


2.20 


x 60 


1.20 


1.97 


x 54 


1.09 


1.79 


x 49 


0.99 


1.64 


x 45 


1.03 


1.59 


x 39 


0.94 


1.40 


x 33 


0.77 


1.20 









For 51 : Pounds per linear foot per inch = 0.059 kg/m/mm. 



2009 INTERNATIONAL BUILDING CODE® 



165 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (5) 
FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS 



COLUMN 
SIZE 


CONCRETE 

MASONRY DENSITY 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CONCRETE MASONRY 

PRQTEC" 1 " 1 ™ 1 ASSFMRI V T /inrhoc^ 


COLUMN 
SIZE 


CONCRETE 

MASONRY DENSITY 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CONCRETE MASONRY 

PRQTEC" 1 " 1 ™ 1 AQQFMRI V T (\nr*hnc\ 


l-hour 


2-hour 


... ^ . , . e 
3-hour 


4-hour 


l-hour 


2-hour 


3-hour 


4-hour 


W14 x 82 


80 


0.74 


1.61 


2.36 


3.04 


W10 x 68 


80 


0.72 


1.58 


2.33 


3.01 


100 


0.89 


1.85 


2.67 


3.40 


100 


0.87 


1.83 


2.65 


3.38 


110 


0.96 


1.97 


2.81 


3.57 


110 


0.94 


1.95 


2.79 


3.55 


120 


1.03 


2.08 


2.95 


3.73 


120 


1.01 


2.06 


2.94 


3.72 


W14x 68 


80 


0.83 


1.70 


2.45 


3.13 


WlOx 54 


80 


0.88 


1.76 


2.53 


3.21 


100 


0.99 


1.95 


2.76 


3.49 


100 


1.04 


2.01 


2.83 


3.57 


110 


1.06 


2.06 


2.91 


3.66 


110 


1.11 


2.12 


2.98 


3.73 


120 


1.14 


2.18 


3.05 


3.82 


120 


1.19 


2.24 


3.12 


3.90 


W14 x 53 


80 


0.91 


1.81 


2.58 


3.27 


W10 x 45 


80 


0.92 


1.83 


2.60 


3.30 


100 


1.07 


2.05 


2.88 


3.62 


100 


1.08 


2.07 


2.90 


3.64 


110 


1.15 


2.17 


3.02 


3.78 


110 


1.16 


2.18 


3.04 


3.80 


120 


1.22 


2.28 


3.16 


3.94 


120 


1.23 


2.29 


3.18 


3.96 


W14 x 43 


80 


1.01 


1.93 


2.71 


3.41 


W10 x 33 


80 


1.06 


2.00 


2.79 


3.49 


100 


1.17 


2.17 


3.00 


3.74 


100 


1.22 


2.23 


3.07 


3.81 


110 


1.25 


2.28 


3.14 


3.90 


110 


1.30 


2.34 


3.20 


3.96 


120 


1.32 


2.38 


3.27 


4.05 


120 


1.37 


2.44 


3.33 


4.12 


W12 x 72 


80 


0.81 


1.66 


2.41 


3.09 


W8 x40 


80 


0.94 


1.85 


2.63 


3.33 


100 


0.91 


1.88 


2.70 


3.43 


100 


1.10 


2.10 


2.93 


3.67 


110 


0.99 


1.99 


2.84 


3.60 


110 


1.18 


2.21 


3.07 


3.83 


120 


1.06 


2.10 


2.98 


3.76 


120 


1.25 


2.32 


3.20 


3.99 


W12 x 58 


80 


0.88 


1.76 


2.52 


3.21 


W8 x 31 


80 


1.06 


2.00 


2.78 


3.49 


100 


1.04 


2.01 


2.83 


3.56 


100 


1.22 


2.23 


3.07 


3.81 


110 


1.11 


2.12 


2.97 


3.73 


110 


1.29 


2.33 


3.20 


3.97 


120 


1.19 


2.23 


3.11 


3.89 


120 


1.36 


2.44 


3.33 


4.12 


W12 x 50 


80 


0.91 


1.81 


2.58 


3.27 


W8 x 24 


80 


1.14 


2.09 


2.89 


3.59 


100 


1.07 


2.05 


2.88 


3.62 


100 


1.29 


2.31 


3.16 


3.90 


110 


1.15 


2.17 


3.02 


3.78 


110 


1.36 


2.42 


3.28 


4.05 


120 


1.22 


2.28 


3.16 


3.94 


120 


1.43 


2.52 


3.41 


4.20 


W12 x 40 


80 


1.01 


1.94 


2.72 


3.41 


W8 x 18 


80 


1.22 


2.20 


3.01 


3.72 


100 


1.17 


2.17 


3.01 


3.75 


100 


1.36 


2.40 


3.25 


4.01 


110 


1.25 


2.28 


3.14 


3.90 


110 


1.42 


2.50 


3.37 


4.14 


120 


1.32 


2.39 


3.27 


4.06 


120 


1.48 


2.59 


3.49 


4.28 



(continued) 



166 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (5)-continued 
FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS 



NOMINAL TUBE 
SIZE 

(inches) 


CONCRETE MASONRY 

DENSITY, POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED 

EQUIVALENT THICKNESS 

FOR FIRE-RESISTANCE 

RATING OF CONCRETE 

MASONRY PROTECTION 

ASQFMRI V T t\nnhnc\ 


NOMINAL PIPE 
SIZE 

(inches) 


CONCRETE MASONRY 
DENSITY, POUNDS 
PER CUBIC FOOT 


MINIMUM REQUIRED 

EQUIVALENT THICKNESS 

FOR FIRE-RESISTANCE 

RATING OF CONCRETE 

MASONRY PROTECTION 

ASQFMRI V T t\nnhnc\ 


l-hour 


2-hour 


■e v 

3-hour 


4-hour 


l-hour 


2-hour 


■e v 

3-hour 


4-hour 


4 x 4 x i/ 2 wall 
thickness 


80 


0.93 


1.90 


2.71 


3.43 


4 double extra 

strong 0.674 

wall thickness 


80 


0.80 


1.75 


2.56 


3.28 


100 


1.08 


2.13 


2.99 


3.76 


100 


0.95 


1.99 


2.85 


3.62 


110 


1.16 


2.24 


3.13 


3.91 


110 


1.02 


2.10 


2.99 


3.78 


120 


1.22 


2.34 


3.26 


4.06 


120 


1.09 


2.20 


3.12 


3.93 


4 x 4 x 3/ 8 wall 
thickness 


80 


1.05 


2.03 


2.84 


3.57 


4 extra strong 
0.337 wall 
thickness 


80 


1.12 


2.11 


2.93 


3.65 


100 


1.20 


2.25 


3.11 


3.88 


100 


1.26 


2.32 


3.19 


3.95 


110 


1.27 


2.35 


3.24 


4.02 


110 


1.33 


2.42 


3.31 


4.09 


120 


1.34 


2.45 


3.37 


4.17 


120 


1.40 


2.52 


3.43 


4.23 


4 x 4 x i/ 4 wall 
thickness 


80 


1.21 


2.20 


3.01 


3.73 


4 standard 
0.237 wall 
thickness 


80 


1.26 


2.25 


3.07 


3.79 


100 


1.35 


2.40 


3.26 


4.02 


100 


1.40 


2.45 


3.31 


4.07 


110 


1.41 


2.50 


3.38 


4.16 


110 


1.46 


2.55 


3.43 


4.21 


120 


1.48 


2.59 


3.50 


4.30 


120 


1.53 


2.64 


3.54 


4.34 


6 x 6 x i/ 2 wall 
thickness 


80 


0.82 


1.75 


2.54 


3.25 


5 double extra 

strong 0.750 

wall thickness 


80 


0.70 


1.61 


2.40 


3.12 


100 


0.98 


1.99 


2.84 


3.59 


100 


0.85 


1.86 


2.71 


3.47 


110 


1.05 


2.10 


2.98 


3.75 


110 


0.91 


1.97 


2.85 


3.63 


120 


1.12 


2.21 


3.11 


3.91 


120 


0.98 


2.02 


2.99 


3.79 


6 x 6 x 3/ 8 wall 
thickness 


80 


0.96 


1.91 


2.71 


3.42 


5 extra strong 
0.375 wall 
thickness 


80 


1.04 


2.01 


2.83 


3.54 


100 


1.12 


2.14 


3.00 


3.75 


100 


1.19 


2.23 


3.09 


3.85 


110 


1.19 


2.25 


3.13 


3.90 


110 


1.26 


2.34 


3.22 


4.00 


120 


1.26 


2.35 


3.26 


4.05 


120 


1.32 


2.44 


3.34 


4.14 


6 x 6 x i/ 4 wall 
thickness 


80 


1.14 


2.11 


2.92 


3.63 


5 standard 
0.258 wall 
thickness 


80 


1.20 


2.19 


3.00 


3.72 


100 


1.29 


2.32 


3.18 


3.93 


100 


1.34 


2.39 


3.25 


4.00 


110 


1.36 


2.43 


3.30 


4.08 


110 


1.41 


2.49 


3.37 


4.14 


120 


1.42 


2.52 


3.43 


4.22 


120 


1.47 


2.58 


3.49 


4.28 


8 x 8 x i/ 2 wall 
thickness 


80 


0.77 


1.66 


2.44 


3.13 


6 double extra 

strong 0.864 

wall thickness 


80 


0.59 


1.46 


2.23 


2.92 


100 


0.92 


1.91 


2.75 


3.49 


100 


0.73 


1.71 


2.54 


3.29 


110 


1.00 


2.02 


2.89 


3.66 


110 


0.80 


1.82 


2.69 


3.47 


120 


1.07 


2.14 


3.03 


3.82 


120 


0.86 


1.93 


2.83 


3.63 


8 x 8 x 3/ 8 wall 
thickness 


80 


0.91 


1.84 


2.63 


3.33 


6 extra strong 
0.432 wall 
thickness 


80 


0.94 


1.90 


2.70 


3.42 


100 


1.07 


2.08 


2.92 


3.67 


100 


1.10 


2.13 


2.98 


3.74 


110 


1.14 


2.19 


3.06 


3.83 


110 


1.17 


2.23 


3.11 


3.89 


120 


1.21 


2.29 


3.19 


3.98 


120 


1.24 


2.34 


3.24 


4.04 


8 x 8 x i/ 4 wall 
thickness 


80 


1.10 


2.06 


2.86 


3.57 


6 standard 
0.280 wall 
thickness 


80 


1.14 


2.12 


2.93 


3.64 


100 


1.25 


2.28 


3.13 


3.87 


100 


1.29 


2.33 


3.19 


3.94 


110 


1.32 


2.38 


3.25 


4.02 


110 


1.36 


2.43 


3.31 


4.08 


120 


1.39 


2.48 


3.38 


4.17 


120 


1.42 


2.53 


3.43 


4.22 



For 51 : 1 inch = 25.4 mm, 1 pound per cubic feet = 16.02 kglm 3 - 

Note: Tabulated values assume I-inch air gap between masonry and steel section. 



2009 INTERNATIONAL BUILDING CODE® 



167 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (6) 
FIRE RESISTANCE OF CLAY MASONRY PROTECTED STEEL COLUMNS 



COLUMN SIZE 


CLAY 

MASONRY 

DENSITY, 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CLAY MASONRY 

PROTEC TinM A.Q.QPMRI V T fin<-hoc\ 


COLUMN SIZE 


CLAY 

MASONRY 

DENSITY, 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CLAY MASONRY 

PROTEC TinM A.Q.QPMRI V T fin<-hoc\ 


l-hour 


2-hour 


3-hour 


4-hour 


l-hour 


2-hour 


3-hour 


4-hour 


W14 x 82 


120 


1.23 


2.42 


3.41 


4.29 


W10 x 68 


120 


1.27 


2.46 


3.26 


4.35 


130 


1.40 


2.70 


3.78 


4.74 


130 


1.44 


2.75 


3.83 


4.80 


W14 x 68 


120 


1.34 


2.54 


3.54 


4.43 


W10 x 54 


120 


1.40 


2.61 


3.62 


4.51 


130 


1.51 


2.82 


3.91 


4.87 


130 


1.58 


2.89 


3.98 


4.95 


W14 x 53 


120 


1.43 


2.65 


3.65 


4.54 


W10 x 45 


120 


1.44 


2.66 


3.67 


4.57 


130 


1.61 


2.93 


4.02 


4.98 


130 


1.62 


2.95 


4.04 


5.01 


W14 x 43 


120 


1.54 


2.76 


3.77 


4.66 


WlOx 33 


120 


1.59 


2.82 


3.84 


4.73 


130 


1.72 


3.04 


4.13 


5.09 


130 


1.77 


3.10 


4.20 


5.13 


W12 x 72 


120 


1.32 


2.52 


3.51 


4.40 


W8 x40 


120 


1.47 


2.70 


3.71 


4.61 


130 


1.50 


2.80 


3.88 


4.84 


130 


1.65 


2.98 


4.08 


5.04 


W12 x 58 


120 


1.40 


2.61 


3.61 


4.50 


W8 x 31 


120 


1.59 


2.82 


3.84 


4.73 


130 


1.57 


2.89 


3.98 


4.94 


130 


1.77 


3.10 


4.20 


5.17 


W12 x 50 


120 


1.43 


2.65 


3.66 


4.55 


W8 x 24 


120 


1.66 


2.90 


3.92 


4.82 


130 


1.61 


2.93 


4.02 


4.99 


130 


1.84 


3.18 


4.28 


5.25 


W12 x 40 


120 


1.54 


2.77 


3.78 


4.67 


W8 x 18 


120 


1.75 


3.00 


4.01 


4.91 


130 


1.72 


3.05 


4.14 


5.10 


130 


1.93 


3.27 


4.37 


5.34 


STEEL TUBING 


STEEL PIPE 


NOMINAL TUBE 
SIZE (inches) 


CLAY 

MASONRY 

DENSITY, 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CLAY MASONRY 

PROTEC TinM A.Q.QPMRI V T /'inrh»c\ 


NOMINAL PIPE 
SIZE (inches) 


CLAY 

MASONRY 

DENSITY, 

POUNDS PER 

CUBIC FOOT 


MINIMUM REQUIRED EQUIVALENT 

THICKNESS FOR FIRE-RESISTANCE 

RATING OF CLAY MASONRY 

PROTEC TinM A.Q.QPMRI V T (\nnhac\ 


l-hour 


2-hour 


. , . e 

3-hour 


4-hour 


l-hour 


2-hour 


. , . e 

3-hour 


4-hour 


4 x 4 x i/ 2 wall 
thickness 


120 


1.44 


2.72 


3.76 


4.68 


4 double extra 

strong 0.674 

wall thickness 


120 


1.26 


2.55 


3.60 


4.52 


130 


1.62 


3.00 


4.12 


5.11 


130 


1.42 


2.82 


3.96 


4.95 


4 x 4 x 3/ 8 wall 
thickness 


120 


1.56 


2.84 


3.88 


4.78 


4 extra strong 

0.337 
wall thickness 


120 


1.60 


2.89 


3.92 


4.83 


130 


1.74 


3.12 


4.23 


5.21 


130 


1.77 


3.16 


4.28 


5.25 


4 x 4 x i/ 4 wall 
thickness 


120 


1.72 


2.99 


4.02 


4.92 


4 standard 

0.237 

wall thickness 


120 


1.74 


3.02 


4.05 


4.95 


130 


1.89 


3.26 


4.37 


5.34 


130 


1.92 


3.29 


4.40 


5.37 


6 x 6 x i/ 2 wall 
thickness 


120 


1.33 


2.58 


3.62 


4.52 


5 double extra 

strong 0.750 

wall thickness 


120 


1.17 


2.44 


3.48 


4.40 


130 


1.50 


2.86 


3.98 


4.96 


130 


1.33 


2.72 


3.84 


4.83 


6 x 6 x 3/ 8 wall 
thickness 


120 


1.48 


2.74 


3.76 


4.67 


5 extra strong 

0.375 
wall thickness 


120 


1.55 


2.82 


3.85 


4.76 


130 


1.65 


3.01 


4.13 


5.10 


130 


1.72 


3.09 


4.21 


5.18 


6 x 6 x i/ 4 wall 
thickness 


120 


1.66 


2.91 


3.94 


4.84 


5 standard 

0.258 

wall thickness 


120 


1.71 


2.97 


4.00 


4.90 


130 


1.83 


3.19 


4.30 


5.27 


130 


1.88 


3.24 


4.35 


5.32 


8 x 8 x i/ 2 wall 
thickness 


120 


1.27 


2.50 


3.52 


4.42 


6 double extra 

strong 0.864 

wall thickness 


120 


1.04 


2.28 


3.32 


4.23 


130 


1.44 


2.78 


3.89 


4.86 


130 


1.19 


2.60 


3.68 


4.67 


8 x 8 x 3/ 8 wall 
thickness 


120 


1.43 


2.67 


3.69 


4.59 


6 extra strong 

0.432 
wall thickness 


120 


1.45 


2.71 


3.75 


4.65 


130 


1.60 


2.95 


4.05 


5.02 


130 


1.62 


2.99 


4.10 


5.08 


8 x 8 x i/ 4 wall 
thickness 


120 


1.62 


2.87 


3.89 


4.78 


6 standard 

0.280 

wall thickness 


120 


1.65 


2.91 


3.94 


4.84 


130 


1.79 


3.14 


4.24 


5.21 


130 


1.82 


3.19 


4.30 


5.27 



168 



2009 INTERNATIONAL BUILDING CODE® 



TABLE 721.5.1(7) 

MINIMUM COVER (inch) FOR STEEL COLUMNS 

ENCASED IN NORMAL-WEIGHT CONCRETE 3 

[FIGURE 721.5.1 (6)(c)] 



STRUCTURAL 
SHAPE 


FIRE-RESISTANCE RATING (hours) 


1 


l\ 


2 


3 


4 


W14 x233 


1 


1 


1 


iV 2 


2 


x 176 


2 i/ 2 


x 132 


2 


x 90 


lV 2 


x 61 


3 


x 48 


iS, 


2 i/ 2 


x 43 


W12 x 152 


1 


1 


1 


2 


2 i/ 2 


x 96 


x 65 


1% 


lV 2 


3 


x 50 


2 i/ 2 


x 40 


WIO x 88 


1 


1V 2 


iV 2 


2 


3 


x 49 


1 


2 i/ 2 


x 45 


x 39 


3 i/ 2 


x 33 


2 


W8 x 67 


1 


i 


1 l/ 2 


2 i/ 2 


3 


x 58 


x 48 


1V 2 


3 i/ 2 


x 31 


2 


3 


x 21 


x 18 


4 


W6 x 25 


1 


1% 


2 


3 
3 i/ 2 


3 i/ 2 


x 20 


2 


2 i/ 2 


4 


x 16 


x 15 


\\ 


x 9 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1(8) 

MINIMUM COVER (inch) FOR STEEL COLUMNS 

ENCASED IN STRUCTURAL LIGHTWEIGHT CONCRETE 8 

[FIGURE 721.5.1 (6)(c)] 



STRUCTURAL 
SHAPE 


FIRE-RESISTANCE RATING (HOURS) 


1 


l\ 


2 


3 


4 


W14 x233 


1 


1 


1 


1 


1V 2 


x 193 


1 l/ 2 


x 74 


2 


x 61 


2 i/ 2 


x 43 


1V 2 


2 


W12 x 65 


1 


1 


1 


1 i/ 2 


2 


x 53 


2 


2 i/ 2 


x 40 


1V 2 


WIOx 112 


1 


1 


1 


1V 2 


2 


x 88 


x 60 


2 


2 i/ 2 


x 33 


I 1 /, 


W8 x 35 


1 


1 


1V 2 


2 


2 i/ 2 


x 28 


3 


x 24 


2 i/ 2 


x 18 


1V 2 



For 51: 1 inch = 25.4 mm. 

a. The tabulated thicknesses are based upon the assumed properties of struc- 
turallightweight concrete given in Table 721.5.1(2). 



For 51 : 1 inch = 25.4 mm. 

a. The tabulated thicknesses are based upon the assumed properties of nor- 
mal-weight concrete given in Table 721 .5.1(2) . 



2009 INTERNATIONAL BUILDING CODE® 



169 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.5.1 (9) 

MINIMUM COVER (inch) FOR STEEL COLUMNS 

IN NORMAL-WEIGHT PRECAST COVERS a 

[FIGURE 721.5.1 (6)(a)] 



TABLE 721.5.1 (10) 

MINIMUM COVER (inch) FOR STEEL COLUMNS 

IN STRUCTURAL LIGHTWEIGHT PRECAST COVERS a 

[FIGURE 721.5.1 (6)(a)] 



STRUCTURAL 
SHAPE 


FIRE-RESISTANCE RATING (hours) 


1 


l\ 


2 


3 


4 


W14 x 233 


iv 2 


1V 2 


1 l/ 2 


2i/ 2 


3 


x211 


3 i/ 2 


x 176 


2 


x 145 


3 


x 109 


2 


2i/ 2 


x 99 


4 


x 61 


3 i/ 2 


x 43 


4 i/ 2 


W12 x 190 


iv 2 


1V 2 


l\ 


2i/ 2 


3 i/ 2 


x 152 


2 


x 120 


3 


4 


x 96 


x 87 


2 


2i/ 2 


3 i/ 2 


x 58 


4 i/ 2 


x 40 


W10 x 112 


1 l/ 2 


1V 2 


2 


3 


3 i/ 2 


x 88 


4 


x 77 


2 


2i/ 2 


x 54 


3 i/ 2 


x 33 


4 i/ 2 


W8 x 67 


\\ 


1V 2 


2 


3 


4 


x 58 


2 


2i/ 2 


3V 2 


x 48 


x 28 


4 i/ 2 


x 21 


2V 2 


3 


x 18 


4 


W6 x 25 


1 l/ 2 


2 


2i/ 2 


3 i/ 2 


4 i/ 2 


x 20 


2i/ 2 


3 


x 16 


4 


x 12 


2 


x 9 


5 



STRUCTURAL 
SHAPE 


FIRE-RESISTANCE RATING (hours) 


1 


1 '/, 


2 


3 


4 


W14 x 233 


1V 2 


1V 2 


1V 2 


2 


2i/ 2 


x 176 


3 


x 145 


2i/ 2 


x 132 


x 109 


x 99 


2 


x 68 


3 i/ 2 


x 43 


3 


W12 x 190 


1 l/ 2 


1V 2 


1 i/ 2 


2 


2i/ 2 


x 152 


x 136 


3 


x 106 


2i/ 2 


x 96 


3 i/ 2 


x 87 


x 65 


2 


x 40 


3 


WlOx 112 


1V 2 


1 l/ 2 


1V 2 


2 


3 


x 100 


2i/ 2 


x 88 


x 77 


2 


3 i/ 2 


x 60 


x 39 


3 


x 33 


2 


W8 x 67 


1V 2 


1V 2 


1V 2 


2i/ 2 


3 


x 48 


2 


3 


3 i/ 2 


x 35 


x 28 


2 


x 18 


2i/ 2 


4 


W6 x 25 


1V 2 


2 


2 


3 


3 i/ 2 


x 15 


2i/ 2 


4 


x 9 


3 i/ 2 



For SI: 1 inch = 25.4 mm. 

a. The tabulated thicknesses are based upon the assumed properties of nor- 
mal-weight concrete given in Table 721 .5.1(2) . 



For SI: 1 inch = 25.4 mm. 

a. The tabulated thicknesses are based upon the assumed properties of struc- 
turallightweight concrete given in Table 721.5 . 1(2) . 



170 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



721.5.2.2.1 Minimum thickness. The use of Equa- 
tion 7-17 is subject to the following conditions: 

1. The weight-to-heated-perimeter ratio for the 
substitute beam or girder (W/L> 2 ) shall not be 
less than 0.37. 

2. The thickness of fire protection materials calcu- 
lated for the substitute beam or girder (Tj) shall 
not be less than 3/ s inch (9.5 mm). 

3. The unrestrained or restrained beam rating shall 
not be less than 1 hour. 

4. When used to adjust the material thickness for a 
restrained beam, the use of this procedure is 
limited to steel sections classified as compact in 
accordance with the AISC Specification for 
Structural Steel Buildings, (AISC 360-05). 

721.5.2.3 Structural steel trusses. The fire resistance of 
structural steel trusses protected with fire-resistant mate- 
rials sprayed to each of the individual truss elements 
shall be permitted to be determined in accordance with 
this section. The thickness of the fire-resistant material 
shall be determined in accordance with Section 
721.5.1.3. The weight-to-heated-perimeter ratio (WID) 
of truss elements that can be simultaneously exposed to 
fire on all sides shall be determined on the same basis as 
columns, as specified in Section 721.5.1.1. The weight- 
to-heated-perimeter ratio (WID) of truss elements that 
directly support floor or roof assembly shall be deter- 
mined on the same basis as beams and girders, as speci- 
fied in Section 721.5.2.1. 

The fire resistance of structural steel trusses protected 
with intumescent or mastic fire-resistant coatings shall 
be determined on the basis of fire-resistance tests in 
accordance with Section 703.2. 

721.6 Wood assemblies. The provisions of this section contain 
procedures by which the fire-resistance ratings of wood 
assemblies are established by calculations. 

721.6.1 General. This section contains procedures for cal- 
culating the fire-resistance ratings of walls, floor/ceiling 
and roof/ceiling assemblies based in part on the standard 
method of testing referenced in Section 703.2. 

721.6.1.1 Maximum fire-resistance rating. Fire resis- 
tance ratings calculated for assemblies using the meth- 
ods in Section 721 .6 shall be limited to a maximum of 1 
hour. 

721.6.1.2 Dissimilar membranes. Where dissimilar 
membranes are used on a wall assembly, the calculation 
shall be made from the least fire-resistant (weaker) side. 

721.6.2 Walls, floors and roofs. These procedures apply to 
both load-bearing and nonload-bearing assemblies. 

721.6.2.1 Fire-resistance rating of wood frame assem- 
blies. The fire-resistance rating of a wood frame assem- 
bly is equal to the sum of the time assigned to the 
membrane on the fire-exposed side, the time assigned to 
the framing members and the time assigned for addi- 
tional contribution by other protective measures such as 



insulation. The membrane on the unexposed side shall 
not be included in determining the fire resistance of the 
assembly. 

721.6.2.2 Time assigned to membranes. Table 
721.6.2(1) indicates the time assigned to membranes on 
the fire-exposed side. 

721.6.2.3 Exterior walls. For an exterior wallwith afire 
separation distance greater than 5 feet (1524 mm), the 
wall is assigned a rating dependent on the interior mem- 
brane and the framing as described in Tables 721.6.2(1) 
and 721.6.2(2). The membrane on the outside of the 
nonfire-exposed side of exterior walls with afire separa- 
tion distance greater than 5 feet (1524 mm) may consist 
of sheathing, sheathing paper and siding as described in 
Table 721.6.2(3). 

TABLE 721.6.2(1) 
TIME ASSIGNED TO WALLBOARD MEMBRANESa,b,c,d 



DESCRIPTION OF FINISH 


TIME e (minutes) 


i/s-inch wood structural panel bonded with 
exterior glue 


5 


15 / 32 -inch wood structural panel bonded with 
exterior glue 


10 


19 / 32 -inch wo °d structural panel bonded with 
exterior glue 


15 


3/ s -inch gypsum wallboard 


10 


V 2 -inch gypsum wallboard 


15 


5/ s -inch gypsum wallboard 


30 


V 2 -inch Type X gypsum wallboard 


25 


5/s-inch Type X gypsum wallboard 


40 


Double 3/ s -inch gypsum wallboard 


25 


V 2 -inch + 3/ s -inch gypsum wallboard 


35 


Double ll 2 -inch gypsum wallboard 


40 



For 51: 1 inch = 25.4 mm. 

a. These values apply only when membranes are installed on framing members 
which are spaced 16 inches o.c. 

b. Gypsum wallboard installed over framing or furring shall be installed so that 
all edges are supported, except s/8-inch Type X gypsum wallboard shall be 
permitted to be installed horizontally with the horizontaljoints staggered 24 
inches each side and unsupported but finished. 

c. On wood frame floor/ceiling or roof/ceiling assemblies, gypsum board shall 
be installed with the long dimension perpendicular to framing members and 
shall have all joints finished. 

d. The membrane on the unexposed side shall not be included in determining the fire 
resistance of the assembly. When dissimilar membranes are used on a wall assem- 
bly, the calculation shall be made from the least fire-resistant (weaker) side. 

e. The time assigned is not a finished rating. 

721.6.2.4 Floors and roofs. In the case of a floor or roof, 
the standard test provides only for testing for fire expo- 
sure from below. Except as noted in Section 703.3, Item 
5, floor or roof assemblies of wood framing shall have an 
upper membrane consisting of a subfloor and finished 
floor conforming to Table 721.6.2(4) or any other mem- 
brane that has a contribution to fire resistance of at least 
15 minutes in Table 721.6.2(1). 



2009 INTERNATIONAL BUILDING CODE® 



171 



FIRE AND SMOKE PROTECTION FEATURES 



TABLE 721.6.2(2) 
TIME ASSIGNED FOR CONTRIBUTION OF WOOD FRAME a.b.c 



DESCRIPTION 


TIME ASSIGNED TO FRAME (minutes) 


Wood studs 16 inches o.c. 


20 


Wood floor and roof joists 16 inches o.c. 


10 



For SI: 1 inch = 25.4 mm. 

a. This table does not apply to studs orjoists spaced more than 16 inches o.c. 

b. All studs shall be nominal 2x4 and all joists shall have a nominal thickness of at least 2 inches. 

c. Allowable spans for joists shall be determined in accordance with Sections 2308.8,2308.10.2 and 2308.10.3. 



TABLE 721.6.2(3) 
MEMBRANEa ON EXTERIOR FACE OF WOOD STUD WALLS 


SHEATHING 


PAPER 


EXTERIOR FINISH 


5/8-inch T & G lumber 




Lumber siding 


5/j6-inch exterior glue wood structural panel 


Sheathing paper 


Wood shingles and shakes 


V 2 -inch gypsum wallboard 




L/ 4 -inch wood structural panels -exterior type 


5/ 8 -inch gypsum wallboard 




l/4-inch hardboard 


l/ 2 -inch fiberboard 




Metal siding 
Stucco on metal lath 
Masonry veneer 
Vinyl siding 


None 


- 


3^ 8 -inch exterior-grade wood structural panels 



For SI: 1 pound/cubic foot = 16.0185 kg/m 2 - 

a. Any combination of sheathing, paper and exterior finish is permitted. 



TABLE 721.6.2(4) 
FLOORING OR ROOFING OVER WOOD FRAMINGa 



ASSEMBLY 


STRUCTURAL 
MEMBERS 


SUBFLOOR OR ROOF DECK 


FINISHED FLOORING OR ROOFING 


Floor 


Wood 


15 / 32 ~ mc ri wood structural panels or 
111 16 inch T & G softwood 


Hardwood or softwood flooring on building paper resilient 
flooring, parquet floor felted- synthetic fiber floor coverings, 
carpeting, or ceramic tile on 3/ 8 -inch-thick panel-type underlay 

Ceramic tile on 1 V 4 -inch mortar bed 


Roof 


Wood 


15 / 32 -inch wood structural panels or 
111 16 inch T & G softwood 


Finished roofing material with or without insulation 



For SI: 1 inch = 25.4 mm. 

a. This table applies only to wood joist construction. It is not applicable to wood truss construction. 

TABLE 721.6.2(5) 
TIME ASSIGNED FOR ADDITIONAL PROTECTION 



DESCRIPTION OF ADDITIONAL PROTECTION 


FIRE RESISTANCE (minutes) 


Add to the fire-resistance rating of wood stud walls if the spaces between the studs are completely filled 
with glass fiber mineral wool batts weighing not less than 2 pounds per cubic foot (0.6 pound per square 
foot of wall surface) or rockwool or slag material wool batts weighing not less than 3.3 pounds per cubic 
foot (1 pound per square foot of wall surface), or cellulose insulation having a nominal density not less 
than 2.6 pounds per cubic foot. 


15 



For SI: 1 pound/cubic foot = 16.0185 kg/m 3 . 



172 



2009 INTERNATIONAL BUILDING CODE® 



FIRE AND SMOKE PROTECTION FEATURES 



721.6.2.5 Additional protection. Table 721.6.2(5) indi- 
cates the time increments to be added to the fire resis- 
tance where glass fiber, rockwool, slag mineral wool or 
cellulose insulation is incorporated in the assembly. 

721.6.2.6 Fastening. Fastening of wood frame assemblies 
and the fastening of membranes to the wood framing 
members shall be done in accordance with Chapter 23. 

721.6.3 Design of fire-resistant exposed wood members. 
The fire-resistance rating, in minutes, of timber beams and 
columns with a minimum nominal dimension of 6 inches 
(152 mm) is equal to: 

Beams: 2.54Zb [4 -2(b/d)\ for beams which may be 
exposed to fire on four sides. 

(Equation 7-18) 

2.54Zb [4 ~{b/d)\ for beams which may be 
exposed to fire on three sides. 

(Equation 7-19) 

Columns: 2.54Zd [3 -(d/b)] for columns which may be 
exposed to fire on four sides 

(Equation 7-20) 

2.54Zd [3 -(d/2b)] for columns which may be 
exposed to fire on three sides. 

(Equation 7-21) 

where: 

b The breadth (width) of a beam or larger side of a 

column before exposure to fire (inches). 

d The depth of a beam or smaller side of a column 

before exposure to fire (inches). 

Z = Load factor, based on Figure 721.6.3(1). 

721.6.3.1 Equation 7-21. Equation 7-21 applies only 
where the unexposed face represents the smaller side of 
the column. If a column is recessed into a wall, its full 
dimension shall be used for the purpose of these calcula- 
tions. 

721 .6.3.2 Allowable loads. Allowable loads on beams 
and columns are determined using design values given in 
AF&PANDS. 

721.6.3.3 Fastener protection. Where minimum I-hour 
fire resistance is required, connectors and fasteners shall 
be protected from fire exposure by 1V 2 inches (38 mm) of 
wood, or other approve ^covering or coating for a I-hour 
rating. Typical details for commonly used fasteners and 
connectors are shown in AITC Technical Note 7. 

721 .6.3.4 Minimum size. Wood members are limited to 
dimensions of 6 inches (152 mm) nominal or greater. 
Glued-laminated timber beams utilize standard laminat- 
ing combinations except that a core lamination is 
removed. The tension zone is moved inward and the 
equivalent of an extra nominal 2-inch-thick (51 mm) 
outer tension lamination is added. 



1.6Q 



iw 



1,40 



Z 130 



<20 















CCtUMN& K^-s.11 




















RrAMS 


- COLUMNS *N 
11 













































110 



1.0 

40 M BO TO 80 W 100 

LOAD ON MEMBERS AS A PERCEMT OF D£5lG** LOAp 

FIGURE 721.6.3(1) 
LOAD FIGURE 

K e = The effective length factor as noted in Figure 721.6.3(2). 
1 = The unsupported length of columns (inches) . 



BUCKLING MODES 



THEORETICAL Ke VALUE 



RECOMMENDED DESIGN Ke 
WHEN IDEAL CONDITIONS 
APPROXIMATED 



END CONDITION CODE 



2L 



T 



0.5 



0.65 



T 
t 



4 



t 



0.7 



0.80 



J J 



f 



1.0 



1.2 



i 



J 



1.0 



1.0 



T 






2.10 



k 



t 









ROTATION FIXED, TRANSLATION FIXED 
ROTATION FREE, TRANSLATION FIXED 

ROTATION FIXED, TRANSLATION FREE 
ROTATION FREE, TRANSLATION FREE 



FIGURE 721.6.3(2) 
EFFECTIVE LENGTH FACTORS 



2009 INTERNATIONAL BUILDING CODE® 



173 



174 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 8 

INTERIOR FINISHES 



SECTION 801 
GENERAL 

801.1 Scope. Provisions of this chapter shall govern the use of 
materials used as interior finishes, trim and decorative materi- 
als 

801.2 Interior wall and ceiling finish. The provisions of Sec- 
tion 803 shall limit the allowable fire performance and smoke 
development of interior wall and ceiling finish materials based 
on occupancy classification. 

801.3 Interior floor finish. The provisions of Section 804 
shall limit the allowable fire performance of interior floor fin- 
ish materials based on occupancy classification. 

[F] 801.4 Decorative materials and trim. Decorative materi- 
als and trim shall be restricted by combustibility and the flame 
propagation performance criteria of NFPA 701, in accordance 
with Section 806. 

801.5 Applicability. For buildings in flood hazard areas as 
established in Section 1612.3, interior finishes, trim and deco- 
rative materials below the design flood elevation shall be 
flood-damage-resistant materials. 

801.6 Application. Combustible materials shall be permitted 
to be used as finish for walls, ceilings, floors and other interior 
surfaces of buildings. 

801.7 Windows. Show windows in the exterior walls of the 
first story above grade shall be permitted to be of wood or of 
unprotected metal framing. 

801.8 Foam plastics. Foam plastics shall not be used as inte- 
rior finish except as provided in Section 803.4. Foam plastics 
shall not be used as interior trim except as provided in Section 
806.3 or 2604.2. This section shall apply both to exposed foam 
plastics and to foam plastics used in conjunction with a textile 
or vinyl facing or cover. 



measurements of the spread of flame versus time for a material 
tested in accordance with ASTM E 84 or UL 723. 

INTERIOR FINISH. Interior finish includes interior wall 
and ceiling finish and interior floor finish. 

INTERIOR FLOOR FINISH. The exposed floor surfaces of 
buildings including coverings applied over a finished floor or 
stair, including risers. 

[F] INTERIOR FLOOR- WALL BASE. Interior floor finish 
trim used to provide a functional and/or decorative border at the 
intersection of walls and floors. 

INTERIOR WALL AND CEILING FINISH. The exposed 
interior surfaces of buildings, including but not limited to: 
fixed or movable walls and partitions; toilet room privacy parti- 
tions; columns; ceilings; and interior wainscoting, paneling or 
other finish applied structurally or for decoration, acoustical 
correction, surface insulation, structural fire resistance or simi- 
lar purposes, but not including trim. 

SITE-FABRICATED STRETCH SYSTEM. A system, fab 
ricated on site and intended for acoustical, tackable or aesthetic 
purposes, that is comprised of three elements: (a) a frame (con- 
structed of plastic, wood, metal or other material) used to hold 
fabric in place, (b) a core material (infill, with the correct prop- 
erties for the application), and (c) an outside layer, comprised 
of a textile, fabric or vinyl, that is stretched taunt and held in 
place by tension or mechanical fasteners via the frame. 

SMOKE-DEVELOPED INDEX. A comparative measure, 
expressed as a dimensionless number, derived from measure- 
ments of smoke obscuration versus time for a material tested in 
accordance with ASTM E 84. 

TRIM. Picture molds, chair rails, baseboards, handrails, door 
and window frames and similar decorative or protective mate- 
rials used in fixed applications. 



i 



SECTION 802 
DEFINITIONS 

802.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

EXPANDED VINYL WALL COVERING. Wall covering 
consisting of a woven textile backing, an expanded vinyl base 
coat layer and a nonexpanded vinyl skin coat. The expanded 
base coat layer is a homogeneous vinyl layer that contains a 
blowing agent. During processing, the blowing agent decom- 
poses, causing this layer to expand by forming closed cells . The 
total thickness of the wall covering is approximately 0.055 inch 
to 0.070 inch (1.4 mm to 1.78 mm). 

FLAME SPREAD. The propagation of flame over a surface. 

FLAME SPREAD INDEX. A comparative measure, 
expressed as a dimensionless number, derived from visual 



SECTION 803 
WALL AND CEILING FINISHES 

803.1 General. Interior wall and ceiling finish materials shall 
be classified for fire performance and smoke development in 
accordance with Section 803.1.1 or 803.1.2, except as shown in 
Sections 803.2 through 803.13. Materials tested in accordance 
with Section 803.1.2 shall not be required to be tested in accor- 
dance with Section 803.1.1. 

803.1.1 Interior wall and ceiling finish materials. Interior 
wall and ceiling finish materials shall be classified in accor- 
dance with ASTM E 84 or UL 723. Such interior finish 
materials shall be grouped in the following classes in accor- 
dance with their flame spread and smoke-developed 
indexes. 

Class A: Flame spread index 0-25; smoke-developed 
index 0-450. 



2009 INTERNATIONAL BUILDING CODE® 



175 



INTERIOR FINISHES 



Class B: Flame spread index 26-75; smoke-developed 
index 0-450. 

Class C: Flame spread index 76-200; smoke-devel- 
oped index 0-450. 

Exception: Materials tested in accordance with Sec- 
tion 803.1.2. 

803.1.2 Room corner test for interior wall or ceiling fin- 
ish materials. Interior wall or ceiling finish materials shall 
be permitted to be tested in accordance with NFPA 286. 
Interior wall or ceiling finish materials tested in accordance 
with NFPA 286 shall comply with Section 803.1.2.1. 

803.1.2.1 Acceptance criteria for NFPA 286. During 
the 40 kW exposure, the interior finish shall comply with 
Item 1. During the 160 kW exposure, the interior finish 
shall comply with Item 2. During the entire test, the inte- 
rior finish shall comply with Items 3 and 4. 

1. During the 40kW exposure, flames shall not 
spread to the ceiling. 

2. During the 160 kW exposure, the interior finish 
shall comply with the following: 

2.1. Flame shall not spread to the outer extrem- 
ity of the sample on any wall or ceiling. 

2.2. Flashover, as defined in NFPA 286, shall 
not occur. 

3. The peak rate of heat release throughout the NFPA 
286 test shall not exceed 800 kW. 

4. The total smoke released throughout the NFPA 
286 test shall not exceed 1,000 m 2 . 

803.1.3 Room corner test for textile wall coverings and 
expanded vinyl wall coverings. Textile wall coverings and 
expanded vinyl wall coverings shall meet the criteria of Sec- 
tion 803.1.3.1 when tested in the manner intended for use in 
accordance with the Method B protocol ofNFPA 265 using 
the product-mounting system, including adhesive. 

803.1.3.1 Acceptance criteria for NFPA 265. During 
the 40 kW exposure the interior finish shall comply with 
Item 1. During the 150 kW exposure, the interior finish 
shall comply with Item 2. During the entire test, the inte- 
rior finish shall comply with Item 3. 

1. During the 40 kW exposure, flames shall not 
spread to the ceiling. 

2. During the 150 kW exposure, the interior finish 
shall comply with the following: 

2.1. Flame shall not spread to the outer extremi- 
ties of the samples on the 8-foot by 12-foot 
(203 mm by 305 mm) walls. 

2.2. Flashover, as described in NFPA 265, shall 
not occur. 

3. The total smoke released throughout the NFPA 
265 test shall not exceed 1,000 m 2 . 

803.1.4 Acceptance criteria for textile and expanded 
vinyl wall or ceiling coverings tested to ASTM E 84 or 



UL 723. Textile wall and ceiling coverings and expanded 
vinyl wall and ceiling coverings shall have a Class A flame 
spread index in accordance with ASTM E 84 or U L 723 and 
be protected by an automatic sprinkler system installed in 
accordance with Section 903.3.1.1 or 903.3.1.2. Test speci- 
men preparation and mounting shall be in accordance with 
ASTM E 2404. 

803.2 Thickness exemption. Materials having a thickness less 
than 0.036 inch (0.9 mm) applied directly to the surface of 
walls or ceilings shall not be required to be tested. 

803.3 Heavy timber exemption. Exposed portions of struc- 
tural members complying with the requirements for buildings 
of Type IV construction in Section 602.4 shall not be subject to 
interior finish requirements. 

803.4 Foam plastics. Foam plastics shall not be used as inte- 
rior finish except as provided in Section 2603.9. This section 
shall apply both to exposed foam plastics and to foam plastics 
used in conjunction with a textile or vinyl facing or cover. 

803.5 Textile wall coverings. Where used as interior wall fin- 
ish materials, textile wall coverings, including materials having 
woven or nonwoven, napped, tufted, looped or similar surface 
and carpet and similar textile materials, shall be tested in the 
manner intended for use, using the product mounting system, 
including adhesive, and shall comply with the requirements of 
Section 803.1.2, 803.1.3 or 803.1.4. 

803.6 Textile ceiling coverings. Where used as interior ceiling 
finish materials, textile ceiling coverings, including materials 
having woven or nonwoven, napped, tufted, looped or similar 
surface and carpet and similar textile materials, shall be tested 
in the manner intended for use, using the product mounting 
system, including adhesive, and shall comply with the require- 
ments of Section 803.1.2 or 803.1.4. 

803.7 Expanded vinyl wall coverings. Where used as interior 
wall finish materials, expanded vinyl wall coverings shall be 
tested in the manner intended for use, using the product mount- 
ing system, including adhesive, and shall comply with the 
requirements of Section 803.1.2, 803.1.3 or 803.1.4. 

803.8 Expanded vinyl ceiling coverings. Where used as inte- 
rior ceiling finish materials, expanded vinyl ceiling coverings 
shall be tested in the manner intended for use, using the product 
mounting system, including adhesive, and shall comply with 
the requirements of Section 803.1.2 or 803.1.4. 

803.9 Interior finish requirements based on group. Interior 
wall and ceiling finish shall have a flame spread index not 
greater than that specified in Table 803.9 for the group and 
location designated. Interior wall and ceiling finish materials 
tested in accordance with NFPA 286 and meeting the accep- 
tance criteria of Section 803 .1.2.1, shall be permitted to be used 
where a Class A classification in accordance with ASTM E 84 
or U L 723 is required. 

803.10 Stability. Interior finish materials regulated by this 
chapter shall be applied or otherwise fastened in such a manner 
that such materials will not readily become detached where 
subjected to room temperatures of 200°F (93°C) for not less 
than 30 minutes. 



176 



2009 INTERNATIONAL BUILDING CODE® 



INTERIOR FINISHES 



TABLE 803.9 
INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCy k 



GROUP 


SPRINKLEREO 1 


NONSPRINKLEREO 


Exit enclosures and 
exit passagewaysa, b 


Corridors 


Rooms and 
enclosed spaces 


Exit enclosures and 
exit passagewaysa, b 


Corridors 


Rooms and 
enclosed spaces 


A-I & A-2 


B 


B 


c 


A 


Ad 


Be 


A-3 f , A-4, A-5 


B 


B 


c 


A 


Ad 


C 


B,E,M, R-I 


B 


C 


c 


A 


B 


C 


R-4 


B 


C 


c 


A 


B 


B 


F 


C 


C 


c 


B 


C 


C 


H 


B 


B 


eg 


A 


A 


B 


1-1 


B 


C 


c 


A 


B 


B 


1-2 


B 


B 


Bhj 


A 


A 


B 


1-3 


A 


Aj 


C 


A 


A 


B 


1-4 


B 


B 


Bhj 


A 


A 


B 


R-2 


C 


C 


C 


B 


B 


C 


R-3 


C 


C 


C 


C 


C 


C 


S 


C 


C 


c 


B 


B 


C 


U 


No restrictions 


No restrictions 



For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929nr- 

a. Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 1,000 square feet of applied surface area in the grade lobby where 
applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.11 .1. 

b. In exit enclosures of buildings less than three stories above grade plane of other than Group 1-3, Class B interior finish for nonsprinklered buildings and Class C 
interior finish for sprinklered buildings shall be permitted. 

c. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions. Where a fire-resistance rating is required for structural elements, 
the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered enclosing spaces and the rooms or 
spaces on both sides shall be considered one. In determining the applicable requirements for rooms and enclosed spaces, the specific occupancy thereof shall be the 
governing factor regardless of the group classification of the building or structure. 

d. Lobby areas in Group A-I , A-2 and A- 3 occupancies shall not be less than Class B materials. 

e. Class C interior finish materials shall be permitted in places of assembly with an occupant load of 300 persons or less. 

f. For places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be permitted. 

g. Class B material is required where the building exceeds two stories. 

h. Class C interior finish materials shall be permitted in administrative spaces. 

i. Class C interior finish materials shall be permitted in rooms with a capacity of four persons or less. 

j. Class B materials shall be permitted as wainscotting extending not more than 48 inches above the finished floor in corridors, 
k. Finish materials as provided for in other sections of this code. 

1 . Applies when the exit enclosures, exit passageways, corridors or rooms and enclosed spaces are protected by an automatic sprinkler system installed in accordance 
with Section 903.3.1.1 or 903.3.1.2. 



803.11 Application of interior finish materials to fire-resis- 
tance-rated structural elements. Where interior finish mate- 
rials are applied on walls, ceilings or structural elements 
required to have a fire-resistance rating or to be of 
noncombustible construction, they shall comply with the pro- 
visions of this section. 

803.11.1 Direct attachment and furred construction. 
Where walls and ceilings are required by any provision in 
this code to be of fire-resistance-rated or noncombustible 
construction, the interior finish material shall be applied 
directly against such construction or to furring strips not 
exceeding l 3 / 4 inches (44 mm) applied directly against such 
surfaces. The intervening spaces between such furring 
strips shall comply with one of the following: 

1. Be filled with material that is inorganic or non- 
combustible; 



2. Be filled with material that meets the requirements 
of a Class A material in accordance with Section 
803.1.1 or 803.1.2; or 

3. Be fireblocked at a maximum of 8 feet (2438 mm) 
in any direction in accordance with Section 717. 

803.11.2 Set-out construction. Where walls and ceilings 
are required to be offire-resistance-rated or noncombustible 
construction and walls are set out or ceilings are dropped 
distances greater than specified in Section 803.11.1, Class 
A finish materials, in accordance with Section 803.1.1 or 
803.1.2, shall be used except where interior finish materials 
are protected on both sides by an automatic sprinkler system 
in accordance with Section 903.3.1.1 or 903.3.1.2, or 
attached to noncombustible backing or furring strips 
installed as specified in Section 803.11.1. The hangers and 
assembly members of such dropped ceilings that are below 



2009 INTERNATIONAL BUILDING CODE® 



177 



INTERIOR FINISHES 



the main ceiling line shall be of noncombustible materials, 
except that in Types III and V construction, fire-retar- 
dant-treated wood shall be permitted. The construction of 
each set-out wall shall be of fire-resistance-rated construc- 
tion as required elsewhere in this code. 

803.1 1.3 Heavy timber construction. Wall and ceiling fin- 
ishes of all classes as permitted in this chapter that are 
installed directly against the wood decking or planking of 
Type IV construction or to wood furring strips applied 
directly to the wood decking or planking shall be 
fireblocked as specified in Section 803.11.1. 

803. 1 1.4 Materials. An interior wall or ceiling finish that is 
not more than i/ 4 inch (6.4 mm) thick shall be applied 
directly against a noncombustible backing. 

Exceptions: 

1. Noncombustible materials. 

2. Materials where the qualifying tests were made 
with the material suspended or furred out from the 
noncombustible backing. 

803.12 High-density polyethylene (HDPE). Where 
high-density polyethylene is used as an interior finish, it shall 
comply with the requirements of Section 803.1.2. 

803.13 Site-fabricated stretch systems. Where used as inte- 
rior wall or interior ceiling finish materials, site-fabricated 
stretch systems shall be tested in the manner intended for use, 
and shall comply with the requirements of Section 803.1.1 or 
803.1.2. If the materials are tested in accordance with ASTM E 
84 or UL 723, specimen preparation and mounting shall be in 
accordance with ASTM E 2573. 



SECTION 804 
INTERIOR FLOOR FINISH 

804.1 General. Interior floor finish and floor covering materi- 
als shall comply with Sections 804.2 through 804.4.1. 

Exception: Floor finishes and coverings of a traditional 
type, such as wood, vinyl, linoleum or terrazzo, and resilient 
floor covering materials that are not comprised of fibers. 

804.2 Classification. Interior floor finish and floor covering 
materials required by Section 804.4.1 to be of Class I or II 
materials shall be classified in accordance with NFPA 253. The 
classification referred to herein corresponds to the classifica- 
tions determined by NFPA 253 as follows: Class I, 0.45 
watts/cm 2 or greater; Class n, 0.22 watts /cm 2 or greater. 

804.3 Testing and identification. Interior floor finish and 
floor covering materials shall be tested by an agency in accor- 
dance with NFPA 253 and identified by a hang tag or other suit- 
able method so as to identify the manufacturer or supplier and 
style, and shall indicate the interior floor finish or floor cover- 
ing classification according to Section 804.2. Carpet-type floor 
coverings shall be tested as proposed for use, including 
underlayment. Test reports confirming the information pro- 
vided in the manufacturer's product identification shall be fur- 
nished to the building official upon request. 

804.4 Interior floor finish requirements. In all occupancies, 
interior floor finish and floor covering materials in exit enclo- 



sures, exitpassageways, corridors and rooms or spaces not sep- 
arated from corridors by full-height partitions extending from 
the floor to the underside of the ceiling shall withstand a mini- 
mum critical radiant flux as specified in Section 804.4.1. 

804.4.1 Minimum critical radiant flux. Interior floor fin- 
ish and floor covering materials in exit enclosures, exitpas- 
sageways and corridors shall not be less than Class I in 
Groups 1-1,1-2 and 1-3 and not less than Class II in Groups 
A, B, E, H, 1-4, M, R-l, R-2 and S. In all areas, floor cover- 
ing materials shall comply with the DOCFF-1 "pill test" 
(CPSC 16 CFR, Part 1630). 

Exception: Where a building is equipped throughout 
with an automatic sprinkler system in accordance with 
Section 903.3.1.1 or903.3.1.2, Class II materials are per- 
mitted in any area where Class I materials are required, 
and materials complying with the DOC FF-1 "pill test" 
(CPSC 16 CFR, Part 1630) are permitted in any area 
where Class II materials are required. 



SECTION 805 
COMBUSTIBLE MATERIALS IN 
TYPES I AND II CONSTRUCTION 

805.1 Application. Combustible materials installed on or 
embedded in floors of buildings of Type I or II construction 
shall comply with Sections 805.1.1 through 805.1.3. 

Exception: Stages and platforms constructed in accordance 
with Sections 410.3 and 410.4, respectively. 

805.1.1 Sub floor construction. Floor sleepers, bucks and 
nailing blocks shall not be constructed of combustible mate- 
rials, unless the space between the fire-resistance-rated 
floor assembly and the flooring is either solidly filled with 
noncombustible materials or fireblocked in accordance with 
Section 717, and provided that such open spaces shall not 
extend under or through permanent partitions or walls. 

805.1.2 Wood finish flooring. Wood finish flooring is per- 
mitted to be attached directly to the embedded or 
fireblocked wood sleepers and shall be permitted where 
cemented directly to the top surface of fire-resistance-rated 
floor assemblies or directly to a wood subfloor attached to 
sleepers as provided for in Section 805.1.1. 

805.1.3 Insulating boards. Combustible insulating boards 
not more than ;/ 2 inch (12.7 mm) thick and covered with fin- 
ish flooring are permitted where attached directly to a 
noncombustible floor assembly or to wood subflooring 
attached to sleepers as provided for in Section 805.1.1. 



[F] SECTION 806 
DECORATIVE MATERIALS AND TRIM 

[F] 806.1 General requirements. In occupancies in Groups A, 
E, I and R-l and dormitories in Group R-2, curtains, draperies, 
hangings and other decorative materials suspended from walls 
or ceilings shall meet the flame propagation performance crite- 
ria of NFPA 701 in accordance with Section 806.2 or be 
noncombustible. 



178 



2009 INTERNATIONAL BUILDING CODE® 



INTERIOR FINISHES 



In Groups 1-1 and 1-2, combustible decorative materials 
shall meet the flame propagation criteria of NFPA 701 unless 
the decorative materials, including, but not limited to, photo- 
graphs and paintings, are of such limited quantities that a haz- 
ard of fire development or spread is not present. In Group 1-3, 
combustible decorative materials are prohibited. 

Fixed or movable walls and partitions, paneling, wall pads 
and crash pads applied structurally or for decoration, acoustical 
correction, surface insulation or other purposes shall be consid- 
ered interior finish if they cover 10 percent or more of the wall 
or of the ceiling area, and shall not be considered decorative 
materials or furnishings. 

In Group Band M occupancies, fabric partitions suspended 
from the ceiling and not supported by the floor shall meet the 
flame propagation performance criteria in accordance with 
Section 806.2 and NFPA 701 or shall be noncombustible. 

[F] 806.1.1 Noncombustible materials. The permissible 
amount of noncombustible decorative material shall not be 
limited. 

[F] 806.1.2 Combustible decorative materials. The per- 
missible amount of decorative materials meeting the flame 
propagation performance criteria of NFPA 701 shall not 
exceed 10 percent of the specific wall or ceiling area to 
which it is attached. 

Exceptions: 

1. In auditoriums in Group A, the permissible 
amount of decorative material meeting the flame 
propagation performance criteria of NFPA 701 
shall not exceed 75 percent of the aggregate wall 
area where the building is equipped throughout 
with an automatic sprinkler system in accordance 
with Section 903.3.1.1 and where the material is 
installed in accordance with Section 803.11. 

2. The amount of fabric partitions suspended from 
the ceiling and not supported by the floor in Group 
Band M occupancies shall not be limited. 

[F] 806.2 Acceptance criteria and reports. Where required 
by Section 806.1, decorative materials shall be tested by an 
agency and meet the flame propagation performance criteria of 
NFPA 701 or such materials shall be noncombustible. Reports 
of test results shall be prepared in accordance with NFPA 701 
and furnished to the building official upon request. 

[F] 806.3 Foam plastic. Foam plastic used as trim in any occu- 
pancy shall comply with Section 2604.2. 

\F] 806.4 Pyroxylin plastic. Imitation leather or other material 
consisting of or coated with a pyroxylin or similarly hazardous 
base shall not be used in Group A occupancies. 

[F] 806.5 Interior trim. Material, other than foam plastic used 
as interior trim, shall have a minimum Class C flame spread 
and smoke-developed index when tested in accordance with 
ASTM E 84 or UL 723, as described in Section 803.1.1. Com- 
bustible trim, excluding handrails and guardrails, shall not 
exceed 10 percent of the specific wall or ceiling area in which it 
is attached. 

[F] 806.6 Interior floor- wall base. Interior floor-wall base 
that is 6 inches (152 mm) or less in height shall be tested in 



accordance with Section 804.2 and shall not be less than Class 
II. Where a Class I floor finish is required, the floor-wall base 
shall be Class I. 

Exception: Interior trim materials that comply with Section 
806.5. 



SECTION 807 
INSULATION 

807.1 Insulation. Thermal and acoustical insulation shall 
comply with Section 719. 



SECTION 808 
ACOUSTICAL CEILING SYSTEMS 

808.1 Acoustical ceiling systems. The quality, design, fabrica- 
tion and erection of metal suspension systems for acoustical 
tile and lay-in panel ceilings in buildings or structures shall 
conform with generally accepted engineering practice, the pro- 
visions of this chapter and other applicable requirements of this 
code. 

808.1.1 Materials and installation. Acoustical materials 
complying with the interior finish requirements of Section 
803 shall be installed in accordance with the manufacturer's 
recommendations and applicable provisions for applying 
interior finish. 

808.1.1.1 Suspended acoustical ceilings. Suspended 
acoustical ceiling systems shall be installed in accor- 
dance with the provisions of ASTM C 635 and ASTM C 
636. 

808.1.1.2 Fire-resistance-rated construction. Acousti- 
cal ceiling systems that are part of fire-resistance-rated 
construction shall be installed in the same manner used 
in the assembly tested and shall comply with the provi- 
sions of Chapter 7. 



i 



2009 INTERNATIONAL BUILDING CODE® 



179 



180 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 9 

FIRE PROTECTION SYSTEMS 



I 



SECTION 901 
GENERAL 

901 . 1 Scope. The provisions of this chapter shall specify where 
fire protection systems are required and shall apply to the 
design, installation and operation of fire protection systems. 

901.2 Fire protection systems. Fire protection systems shall 
be installed, repaired, operated and maintained in accordance 
with this code and the International Fire Code. 

Any fire protection system for which an exception or reduc- 
tion to the provisions of this code has been granted shall be con- 
sidered to be a required system. 

Exception: Any fire protection system or portion thereof 
not required by this code shall be permitted to be installed 
for partial or complete protection provided that such system 
meets the requirements of this code. 

901.3 Modifications. No person shall remove or modify any 
fire protection system installed or maintained under the provi- 
sions of this code or the International Fire Code without 
approval by the building official. 

901.4 Threads. Threads provided for fire department connec- 
tions to sprinkler systems, standpipes, yard hydrants or any 
other fire hose connection shall be compatible with the connec- 
tions used by the local fire department. 

901.5 Acceptance tests. Fire protection systems shall be tested 
in accordance with the requirements of this code and the Inter- 
national Fire Code. When required, the tests shall be con- 
ducted in the presence of the building official. Tests required by 
this code, the International Fire Code and the standards listed 
in this code shall be conducted at the expense of the owner or 
the owner's representative. It shall be unlawful to occupy por- 
tions of a structure until the required fire protection systems 
within that portion of the structure have been tested and 
approved. 

901.6 Supervisory service. Where required, fire protection 
systems shall be monitored by an supervising station in accor- 
dance with NFPA 72. 

901.6.1 Automatic sprinkler systems. Automatic sprin- 
kler systems shall be monitored by an approvedsupervising 
station. 

Exceptions: 

1. A supervising station is not required for automatic 
sprinkler systems protecting one- and two-family 
dwellings. 

2. Limited area systems serving fewer than 20 sprin- 
klers. 

901.6.2 Fire alarm systems. Fire alarm systems required 
by the provisions of Section 907.2 of this code and Sections 
907.2 and 907.3 of the International Fire Code shall be 



monitored by an approved supervising station in accor- 
dance with Section 907.6.5. 

Exceptions: 

1. Single- and multiple-station smoke alarms 
required by Section 907.2.11. 

2. Smoke detectors in Group 1-3 occupancies. 

3. Supervisory service is not required for automatic 
sprinkler systems in one- and two-family dwell- 
ings. 

901.6.3 Group H. Manual fire alarm, automatic fire-extin- 
guishing and emergency alarm systems in Group H occu- 
pancies shall be monitored by an approved supervising 
station. 

Exception: When approved by the bUilding official, 
on-site monitoring at a constantly attendedlocation shall 
be permitted provided that notifications to the fire 
department will be equal to those provided by an 
app roved supervising station. 

901.7 Fire areas. Where buildings, or portions thereof, are 
divided into fire areas so as not to exceed the limits established 
for requiring a fire protection system in accordance with this 
chapter, swch. fire areas shall be separated by fire barriers con- 
structed in accordance with Section 707 or horizontal assem- 
blies constructed in accordance with Section 712, or both, 
having & fire-resistance rating of not less than that determined 
in accordance with Section 707.3.9. 

SECTION 902 
DEFINITIONS 

902.1 Definitions. The following words and terms shall, for the 
purposes of this chapter, and as used elsewhere in this code, 
have the meanings shown herein. 

[F] ALARM NOTIFICATION APPLIANCE. A fire alarm 
system component such as a bell, horn, speaker, light or text 
display that provides audible, tactile or visible outputs, or any 
combination thereof. 

[F] ALARM SIGNAL. A signal indicating an emergency 
requiring immediate action, such as a signal indicative offire. 

[F] ALARM VERIFICATION FEATURE. A feature of 
automatic fire detection and alarm systems to reduce unwanted 
alarms wherein smoke detectors report alarm conditions for a 
minimum period of time, or confirm alarm conditions within a 
given time period, after being automatically reset, in order to be 
accepted as a valid alarm-initiation signal. 

[F] ANNUNCIATOR. A unit containing one or more indica- 
tor lamps, alphanumeric displays or other equivalent means in 
which each indication provides status information about a cir- 
cuit, condition or location. 



2009 INTERNATIONAL BUILDING CODE® 



181 



FIRE PROTECTION SYSTEMS 



I 



[F] AUDIBLE ALARM NOTIFICATION APPLIANCE. A 

notification appliance that alerts by the sense of hearing. 

[F] AUTOMATIC. As applied to fire protection devices, a 
device or system providing an emergency function without the 
necessity for human intervention and activated as a result of a 
predetermined temperature rise, rate of temperature rise or 
combustion products. 

[F] AUTOMATIC FIRE-EXTINGUISHING SYSTEM. 

An approve ^system of devices and equipment which automat- 
ically detects afire and discharges an approvedfire-extinguish- 
ing agent onto or in the area of a fire. 

[F] AUTOMATIC SMOKE DETECTION SYSTEM. A fire 
alarm system that has initiation devices that utilize smoke 
detectors for protection of an area such as a room or space with 
detectors to provide early warning of fire. 

[F] AUTOMATIC SPRINKLER SYSTEM. An automatic 
sprinkler system, for fire protection purposes, is an integrated 
system of underground and overhead piping designed in accor- 
dance with fire protection engineering standards. The system 
includes a suitable water supply. The portion of the system 
above the ground is a network of specially sized or hydrauli- 
cally designed piping installed in a structure or area, generally 
overhead, and to which automatic sprinklers are connected in a 
systematic pattern. The system is usually activated by heat 
from a fire and discharges water over the fire area. 

[F] AVERAGE AMBIENT SOUND LEVEL. The root mean 
square, A-weighted sound pressure level measured over a 
24-hour period, or the time any person is present, whichever 
time period is less. 

[F] CARBON DIOXIDE EXTINGUISHING SYSTEMS. 
A system supplying carbon dioxide (C0 2 ) from a pressurized 
vessel through fixed pipes and nozzles. The system includes a 
manual- or automatic- actuating mechanism. 

[F] CEILING LIMIT. The maximum concentration of an 
air-borne contaminant to which one may be exposed, as pub- 
lished in DOL 29 CFR Part 1910.1000. 

[F] CLEAN AGENT. Electrically nonconducting, volatile or 
gaseous fire extinguishant that does not leave a residue upon 
evaporation. 

[F] CONSTANTLY ATTENDED LOCATION. A desig- 
nated location at a facility staffed by trained personnel on a 
continuous basis where alarm or supervisory signals are moni- 
tored and facilities are provided for notification of the fire 
department or other emergency services. 

[F] DELUGE SYSTEM. A sprinkler system employing open 
sprinklers attached to a piping system connected to a water sup- 
ply through a valve that is opened by the operation of a detec- 
tion system installed in the same areas as the sprinklers. When 
this valve opens, water flows into the piping system and dis- 
charges from all sprinklers attached thereto. 

I[F] DETECTOR, HEAT. A fire detector that senses heat- 
either abnormally high temperature or rate of rise, or both. 

[F] DRY-CHEMICAL EXTINGUISHING AGENT. A 

powder composed of small particles, usually of sodium bicar- 
bonate, potassium bicarbonate, urea-potassium-based bicar- 



I 



bonate, potassium chloride or mono ammonium phosphate, 
with added particulate material supplemented by special treat- 
ment to provide resistance to packing, resistance to moisture 
absorption (caking) and the proper flow capabilities. 

[F] ELEVATOR GROUP. A grouping of elevators in a build- 
ing located adjacent or directly across from one another that 
responds to a common hall call button(s). 

[F] EMERGENCY ALARM SYSTEM. A system to provide 
indication and warning of emergency situations involving haz- 
ardous materials. 

[F] EMERGENCY VOICE/ALARM COMMUNICA- 
TIONS. Dedicated manual or automatic facilities for originat- 
ing and distributing voice instructions, as well as alert and 
evacuation signals pertaining to a fire emergency, to the occu- 
pants of a building. 

[F] FIRE ALARM BOX, MANUAL. See "Manual fire alarm 
box. " 

[F] FIRE ALARM CONTROL UNIT. A system component 
that receives inputs from automatic and manual fire alarm 
devices and may be capable of supplying power to detection 
devices and transponder(s) or off-premises transmitter (s). The 
control unit may be capable of providing a transfer of power to 
the notification appliances and transfer of condition to relays or 
devices. 

[F] FIRE ALARM SIGNAL. A signal initiated by a fire 
alarm-initiating device such as a manual fire alarm box, auto- 
matic fire detector, waterflow switch or other device whose 
activation is indicative of the presence of a fire or fire signature. 

[F] FIRE ALARM SYSTEM. A system or portion of a com- 
bination system consisting of components and circuits 
arranged to monitor and annunciate the status of fire alarm or 
supervisory signal-initiating devices and to initiate the appro- 
priate response to those signals. 

[F] FIRE AREA. The aggregate floor area enclosed and 
bounded by fire walls, fire barriers, exterior walls or horizon- 
tal assemblies of a building. Areas of the building not provided 
with surrounding walls shall be included in the fire area if such 
areas are included within the horizontal projection of the roof 
or floor next above. 

[F] FIRE COMMAND CENTER. The principal attended or 
unattended location where the status of detection, alarm com- 
munications and control systems is displayed, and from which 
the system(s) can be manually controlled. 

[F] FIRE DETECTOR, AUTOMATIC. A device designed 
to detect the presence of a fire signature and to initiate action. 

[F] FIRE PROTECTION SYSTEM. Approved devices, 
equipment and systems or combinations of systems used to 
detect a fire, activate an alarm, extinguish or control a fire, con- 
trol or manage smoke and products of a fire or any combination 
thereof. 

[F] FIRE SAFETY FUNCTIONS. Building and fire control 
functions that are intended to increase the level of life safety for 
occupants or to control the spread of harmful effects of fire. 



182 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



I 



[F] FOAM-EXTINGUISHING SYSTEM. A special system 
discharging a foam made from concentrates, either mechani- 
cally or chemically, over the area to be protected. 

[F] HALOGENATED EXTINGUISHING SYSTEM. A 

fire-extinguishing system using one or more atoms of an ele- 
ment from the halogen chemical series: fluorine, chlorine, bro- 
mine and iodine. 

\F] INITIATING DEVICE. A system component that origi- 
nates transmission of a change-of- state condition, such as in a 
smoke detector, manual fire alarm box or supervisory switch. 

[F] MANUAL FIRE ALARM BOX. A manually operated 
device used to initiate an alarm signal. 

[F] MULTIPLE-STATION ALARM DEVICE. Two or 
more single- station alarm devices that are capable of intercon- 
nection such that actuation of one causes all integral or separate 
audible alarms to operate. It also can consist of one single-sta- 
tion alarm device having connections to other detectors or to a 
manual fire alarm box. 

[F] MULTIPLE-STATION SMOKE ALARM. Two or more 
single- station alarm devices that are capable of interconnection 
such that actuation of one causes the appropriate alarm signal 
to operate in all interconnected alarms . 

[F] NOTIFICATION ZONE. See "Zone, notification." 

[F] NUISANCE ALARM. An alarm caused by mechanical 
failure, malfunction, improper installation or lack of proper 
maintenance, or an alarm activated by a cause that cannot be 
determined. 

[F] RECORD DRAWINGS. Drawings ("as builts") that doc- 
ument the location of all devices, appliances, wiring 
sequences, wiring methods and connections of the components 
of a fire alarm system as installed. 

[F] SINGLE-STATION SMOKE ALARM. An assembly 
incorporating the detector, the control equipment and the 
alarm -sounding device in one unit, operated from a power sup- 
ply either in the unit or obtained at the point of installation. 

I[F] SMOKE ALARM. A single- or multiple- station alarm 
responsive to smoke. 

\F] SMOKE DETECTOR. A liste d device that senses visible 
or invisible particles of combustion. 

SMOKEPROOF ENCLOSURE. An exit stairway designed 
and constructed so that the movement of the products of com- 
bustion produced by a fire occurring in any part of the building 
into the enclosure is limited. 

[F] STANDPIPE SYSTEM, CLASSES OF. Standpipe 
classes are as follows: 

Class I system. A system providing 2 l i T mch (64 mm) hose 
connections to supply water for use by fire departments and 
those trained in handling heavy fire streams. 

Class II system. A system providing lV 2 -inch (38 mm) 
hose stations to supply water for use primarily by the build- 
ing occupants or by the fire department during initial 
response. 

Class III system. A system providing lV^inch (38 mm) 
hose stations to supply water for use by building occupants 



and 2 1 / T inch (64 mm) hose connections to supply a larger 
volume of water for use by fire departments and those 
trained in handling heavy fire streams. 

[FT STANDPIPE, TYPES OF. Standpipe types are as follows: 

Automatic dry. A dry standpipe system, normally filled 
with pressurized air, that is arranged through the use of a 
device, such as dry pipe valve, to admit water into the sys- 
tem piping automatically upon the opening of a hose valve. 
The water supply for an automatic dry standpipe system 
shall be capable of supplying the system demand. 

Automatic wet. A wet standpipe system that has a water 
supply that is capable of supplying the system demand auto- 
matically. 

Manual dry. A dry standpipe system that does not have a 
permanent water supply attached to the system. Manual dry 
standpipe systems require water from a fire department 
pumper to be pumped into the system through the fire 
department connection in order to meet the system demand. 

Manual wet. A wet standpipe system connected to a water 
supply for the purpose of maintaining water within the sys- 
tem but does not have a water supply capable of delivering 
the system demand attached to the system. Manual-wet 
standpipe systems require water from a fire department 
pumper (or the like) to be pumped into the system in order to 
meet the system demand. 

Semiautomatic dry. A dry standpipe system that is 
arranged through the use of a device, such as a deluge valve, 
to admit water into the system piping upon activation of a 
remote control device located at a hose connection. A 
remote control activation device shall be provided at each 
hose connection. The water supply for a semiautomatic dry 
standpipe system shall be capable of supplying the system 
demand. 

[F] SUPERVISING STATION. A facility that receives sig- 
nals and at which personnel are in attendance at all times to 
respond to these signals. 

[FT SUPERVISORY SERVICE. The service required to 
monitor performance of guard tours and the operative condi- 
tion of fixed suppression systems or other systems for the pro- 
tection of life and property. 

[F] SUPERVISORY SIGNAL. A signal indicating the need 
of action in connection with the supervision of guard tours, the 
fire suppression systems or equipment or the maintenance fea- 
tures of related systems. 

[FT SUPERVISORY SIGNAL-INITIATING DEVICE. An 
initiation device, such as a valve supervisory switch, 
water-level indicator or low-air pressure switch on a dry-pipe 
sprinkler system, whose change of state signals an off-normal 
condition and its restoration to normal of a fire protection or 
life safety system, or a need for action in connection with guard 
tours, fire suppression systems or equipment or maintenance 
features of related systems. 

[F] TIRES, BULK STORAGE OF. Storage of tires where the 
area available for storage exceeds 20,000 cubic feet (566 m 3 ). 



2009 INTERNATIONAL BUILDING CODE® 



183 



FIRE PROTECTION SYSTEMS 



[F] TROUBLE SIGNAL. A signal initiated by the fire alarm 
system or device indicative of a fault in a monitored circuit or 
component. 

[F] VISIBLE ALARM NOTIFICATION APPLIANCE. A 

notification appliance that alerts by the sense of sight. 

[F] WET-CHEMICAL EXTINGUISHING SYSTEM. A 

solution of water and potassium-carbonate-based chemical, 
potassium-acetate-based chemical or a combination thereof, 
forming an extinguishing agent. 

[F] WIRELESS PROTECTION SYSTEM. A system or a 
part of a system that can transmit and receive signals without 
the aid of wire. 

\F] ZONE. A defined area within the protected premises. A 
zone can define an area from which a signal can be received, an 
area to which a signal can be sent or an area in which a form of 
control can be executed. 

[F] ZONE, NOTIFICATION. An area within a building or 
facility covered by notification appliances which are activated 
simultaneously. 



SECTION 903 
AUTOMATIC SPRINKLER SYSTEMS 

[F] 903.1 General. A utomatic sprinkler systems shall comply 
with this section. 

[F] 903.1.1 Alternative protection. Alternative automatic 
fire-extinguishing systems complying with Section 904 
shall be permitted in lieu of automatic sprinkler protection 
where recognized by the applicable standard and approved 
by the fire code official. 

[F] 903.2 Where required. Approved automatic sprinkler sys- 
tems in new buildings and structures shall be provided in the 
locations described in Sections 903.2.1 through 903.2.12. 

Exception: Spaces or areas in telecommunications build- 
ings used exclusively for telecommunications equipment, 
associated electrical power distribution equipment, batter- 
ies and standby engines, provided those spaces or areas are 
equipped throughout with an automatic smoke detection 
system in accordance with Section 907.2 and are separated 
from the remainder of the building by not less than I-hour 
fire barriers constructed in accordance with Section 707 or 
not less than 2-hour horizontal assemblies constructed in 
accordance with Section 712, or both. 

\F] 903.2.1 Group A. An automatic sprinkler system shall 
be provided throughout buildings and portions thereof used 
as Group A occupancies as provided in this section. For 
Group A-I, A-2, A-3 and A-4 occupancies, the automatic 
sprinkler system shall be provided throughout the floor area 
where the Group A-I, A-2, A-3 or A-4 occupancy is 
located, and in all floors from the Group A occupancy to, 
and including, the nearest level of exit discharge serving the 
Group A occupancy. For Group A-5 occupancies, the auto- 
matic sprinkler system shall be provided in the spaces indi- 
cated in Section 903.2.1.5. 



[F] 903.2.1.1 Group A-I. An automatic sprinkler sys- 
tem shall be provided for Group A-I occupancies where 
one of the following conditions exists: 

1. The fire area exceeds 12,000 square feet (1115 



2. The fire area has an occupantloadof 300 or more; 

3. The fire area is located on a floor other than a level 
of exit discharge serving such occupancies; or 

4. The fire area contains a multitheater complex. 

[F] 903.2.1.2 Group A-2. An automatic sprinkler sys- 
tem shall be provided for Group A-2 occupancies where 
one of the following conditions exists: 

1. The fire area exceeds 5,000 square feet (464.5 
m 2 ); 

2. The fire area has an occupantloadof 100 or more; 
or 

3. The fire area is located on a floor other than a level 
of exit discharge serving such occupancies. 

[F] 903.2.1.3 Group A-3. An automatic sprinkler sys- 
tem shall be provided for Group A-3 occupancies where 
one of the following conditions exists: 

1. The fire area exceeds 12,000 square feet (1115 
m 2 ); 

2. The fire area has an occupantloadof 300 or more; 
or 

3. The //re area is located on a floor other than a level 
of exit discharge serving such occupancies. 

[F] 903.2.1.4 Group A-4. An automatic sprinkler sys- 
tem shall be provided for Group A-4 occupancies where 
one of the following conditions exists: 

1. The fire area exceeds 12,000 square feet (1115 



2. The fire area has an occupantloadof 300 or more; 
or 

3. The fire area is located on a floor other than a level 
of exit discharge serving such occupancies. 

\F] 903.2.1.5 Group A-5. An automatic sprinkler sys- 
tem shall be provided for Group A-5 occupancies in the 
following areas: concession stands, retail areas, press 
boxes and other accessory use areas in excess of 1,000 
square feet (93 m 2 ) . 

[F] 903.2.2 Group B ambulatory health care facilities. 
An automatic sprinkler system shall be installed throughout 
all fire areas containing a Group B ambulatory health care 
facility occupancy when either of the following conditions 
exists at any time: 

1. Four or more care recipients are incapable of self- 
preservation. 

2. One or more care recipients who are incapable of self- 
preservation are located at other than the level of exit 
discharge serving such an occupancy. 



184 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 903.2.3 Group E. An automatic sprinkler system shall 
be provided for Group E occupancies as follows: 

1. Throughout all Group E fire areas greater than 
12,000 square feet (1115 m 2 ) in area. 

2. Throughout every portion of educational buildings 
below the lowest level of exit discharge serving that 
portion of the building. 

Exception: An automatic sprinkler system is not 
required in any area below the lowest level of exit 
discharge serving that area where every classroom 
throughout the building has at least one exterior 
exit door at ground level. 

[F] 903.2.4 Group F-l. An automatic sprinkler system 
shall be provided throughout all buildings containing a 
Group F-1 occupancy where one of the following condi- 
tions exists: 

1. A Group F-l fire area exceeds 12,000 square feet 
(1115 m 2 ). 

2. A Group F-l fire area is located more than three sto- 
ries above grade plane. 

3. The combined area of all Group F-l fire areas on all 
floors, including any mezzanines, exceeds 24,000 
square feet (2230 m 2 ). 

[F] 903.2.4.1 Woodworking operations. An automatic 
sprinkler system shall be provided throughout all Group 
F-1 occupancy fire areas that contain woodworking 
operations in excess of 2,500 square feet (232 m 2 ) in area 
which generate finely divided combustible waste or use 
finely divided combustible materials. 

[F] 903.2.5 Group H. Automatic sprinkler systems shall be 
provided in high-hazard occupancies as required in Sec- 
tions 903.2.5.1 through 903.2.5.3. 

[F] 903.2.5.1 General. An automatic sprinkler system 
shall be installed in Group H occupancies. 

[F] 903.2.5.2 Group H-5. An automatic sprinkler sys- 
tem shall be installed throughout buildings containing 
Group H-5 occupancies. The design of the sprinkler sys- 
tem shall not be less than that required by this code for 
the occupancy hazard classifications in accordance with 
Table 903.2.5.2. Where the design area of the sprinkler 
system consists of a corridor protected by one row of 
sprinklers, the maximum number of sprinklers required 
to be calculated is 13 . 

[F] TABLE 903.2.5.2 
GROUP H-5 SPRINKLER DESIGN CRITERIA 



LOCATION 


OCCUPANCY HAZARD 
CLASSIFICATION 


Fabrication areas 


Ordinary Hazard Group 2 


Service corridors 


Ordinary Hazard Group 2 


Storage rooms without dispensing 


Ordinary Hazard Group 2 


Storage rooms with dispensing 


Extra Hazard Group 2 


Corridors 


Ordinary Hazard Group 2 



[F] 903.2.5.3 Pyroxylin plastics. An automatic sprin- 
kler system shall be provided in buildings, or portions 
thereof, where cellulose nitrate film or pyroxylin plastics 
are manufactured, stored or handled in quantities 
exceeding 100 pounds (45 kg). 

[F] 903.2.6 Group I. An automatic sprinkler system shall 
be provided throughout buildings with a Group I fire area. 

Exception: An automatic sprinkler system installed in 
accordance with Section 903.3.1.2 or 903.3.1.3 shall be 
allowed in Group 1-1 facilities. 

[F] 903.2.7 Group M. An automatic sprinkler system shall 
be provided throughout buildings containing a Group M 
occupancy where one of the following conditions exists: 

1. A Group M fire area exceeds 12,000 square feet 
(1115 m 2 ). 

2. A Group Mfire area is located more than three stories 
above grade plane. 

3. The combined area of all Group M fire areas on all 
floors, including any mezzanines, exceeds 24,000 
square feet (2230 m 2 ). 

4. A Group M occupancy is used for the display and sale 
of upholstered furniture. 

[F] 903.2.7.1 High-piled storage. An automatic sprin- 
kler system shall be provided in accordance with the 
International Fire Code in all buildings of Group M 
where storage of merchandise is in high-piled or rack 
storage arrays. 

[F] 903.2.8 Group R. An automatic sprinkler system 
installed in accordance with Section 903.3 shall be provided 
throughout all buildings with a Group R fire area. 

[F] 903.2.9 Group 5-1. An automatic sprinkler system shall 
be provided throughout all buildings containing a Group 
S-l occupancy where one of the following conditions 
exists: 

1. A Group S-l fire area exceeds 12,000 square feet 
(1115 m 2 ). 

2. A Group S-l fire area is located more than three sto- 
ries above grade plane. 

3. The combined area of all Group S-l fire areas on all 
floors, including any mezzanines, exceeds 24,000 
square feet (2230 m 2 ). 

4. A Group S-l fire area used for the storage of com- 
mercial trucks or buses where the fire area exceeds 
5,000 square feet (464 m 2 ). 

[F] 903.2.9.1 Repair garages. An automatic sprinkler 
system shall be provided throughout all buildings used as 
repair garages in accordance with Section 406, as shown: 

1. Buildings having two or more stories above grade 
plane, including basements, with a fire area con- 
taining a repair garage exceeding 10,000 square 
feet (929 m 2 ). 

2. Buildings no more than one story above grade 
plane, with a fire area containing a repair garage 
exceeding 12,000 square feet (1115 m2). 



2009 INTERNATIONAL BUILDING CODE® 



185 



FIRE PROTECTION SYSTEMS 



3. Buildings with repair garages servicing vehicles 
parked in basements. 

4. A Group S-l fire area used for the repair of com- 
mercial trucks or buses where the fire area exceeds 
5,000 square feet (464 m 2 ). 

[F] 903.2.9.2 Bulk storage of tires. Buildings and struc- 
tures where the area for the storage of tires exceeds 
20,000 cubic feet (566 m 3 ) shall be equipped throughout 
with an automatic sprinkler system in accordance with 
Section 903.3.1.1. 

[F] 903.2.10 Group S-2 enclosed parking garages. An 
automatic sprinkler system shall be provided throughout 
buildings classified as enclosed parking garages in accor- 
dance with Section 406.4 as follows: 

1. Where the fire area of the enclosed parking garage 
exceeds 12,000 square feet (1115 m 2 ); or 

2. Where the enclosed parking garage is located beneath 
other groups. 

Exception: Enclosed parking garages located 
beneath Group R-3 occupancies. 

[F] 903.2.10.1 Commercial parking garages. Anauto- 
matic sprinkler system shall be provided throughout 
buildings used for storage of commercial trucks or buses 
where the fire area exceeds 5,000 square feet (464 m 2 ). 

[F] 903.2.11 Specific building areas and hazards. In all 
occupancies an automatic sprinkler system shall be installed 
for building design or hazards in the locations set forth in 
Sections 903.2.11.1 through 903.2.11.6. 

Exception: Groups R-3 and U. 

[F] 903.2.11.1 Stories without openings. An automatic 
sprinkler system shall be installed throughout all stories, 
including basements, of all buildings where the floor 
area exceeds 1,500 square feet (139.4 m 2 ) and where 
there is not provided at least one of the following types of 
exterior wall openings: 

1. Openings below grade that lead directly to ground 
level by an exterior stairway complying with Sec- 
tion 1009 or an outside ramp complying with Sec- 
tion 1010. Openings shall be located in each 50 
linear feet (15 240 mm), or fraction thereof, of 
exterior wall in the story on at least one side. The 
required openings shall be distributed such that the 
lineal distance between adjacent openings does 
not exceed 50 feet (15 240 mm). 

2. Openings entirely above the adjoining ground 
level totaling at least 20 square feet (1.86 m 2 ) in 
each 50 linear feet (15 240 mm), or fraction 
thereof, of exterior wallin the story on at least one 
side. The required openings shall be distributed 
such that the lineal distance between adjacent 
openings does not exceed 50 feet (15 240 mm). 

[F] 903.2.11.1.1 Opening dimensions and access. 
Openings shall have a minimum dimension of not less 
than 30 inches (762 mm). Such openings shall be 
accessible to the fire department from the exterior and 



shall not be obstructed in a manner that fire fighting or 
rescue cannot be accomplished from the exterior. 

[F] 903.2.11.1 .2 Openings on one side only. Where 
openings in a story are provided on only one side and 
the opposite wall of such storyis more than 75 feet (22 
860 mm) from such openings, the story shall be 
equipped throughout with an approved automatic 
sprinkler system, or openings as specified above shall 
be provided on at least two sides of the story. 

[F] 903.2.11.1.3 Basements. Where any portion of a 
basement is located more than 75 feet (22 860 mm) 
from openings required by Section 903.2.11.1, the 
basement shall be equipped throughout with an 
approved automatic sprinkler system. 

[F] 903.2. 11.2 Rubbish and linen chutes. An automatic 
sprinkler system shall be installed at the top of rubbish 
and linen chutes and in their terminal rooms. Chutes 
extending through three or more floors shall have addi- 
tional sprinkler heads installed within such chutes at 
alternate floors. Chute sprinklers shall be accessible for 
servicing. 

[F] 903.2.11.3 Buildings 55 feet or more in height. An 
automatic sprinkler system shall be installed throughout 
buildings with a floor level having an occupant load of 
30 or more that is located 55 feet (16 764 mm) or more 
above the lowest level of fire department vehicle access. 

Exceptions: 

1. Airport control towers. 

2. Open parking structures. 

3. Occupancies in Group F-2. 

[F] 903.2.11.4 Ducts conveying hazardous exhausts. 
Where required by the International Mechanical Code, 
automatic sprinklers shall be provided in ducts convey- 
ing hazardous exhaust, or flammable or combustible 
materials. 

Exception: Ducts in which the largest cross-sectional 
diameter of the duct is less than 10 inches (254 mm). 

[F] 903.2.11.5 Commercial cooking operations. An 
automatic sprinkler system shall be installed in commer- 
cial kitchen exhaust hood and duct system where an 
automatic sprinkler system is used to comply with Sec- 
tion 904. 

[F] 903.2.11.6 Other required suppression systems. In 
addition to the requirements of Section 903.2, the provi- 
sions indicated in Table 903.2.11.6 also require the 
installation of a fire suppression system for certain build- 
ings and areas. 

[F] 903.2.12 During construction. Automatic sprinkler 
systems required during construction, alteration and demo- 
lition operations shall be provided in accordance with Chap- 
ter 14 of the International Fire Code. 

\F] 903.3 Installation requirements. Automatic sprinkler sys- 
tems shall be designed and installed in accordance with Sec- 
tions 903.3.1 through 903.3.6. 



186 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] TABLE 903.2.11.6 
ADDITIONAL REQUIRED SUPPRESSION SYSTEMS 



SECTION 


SUBJECT 


402.9 


Covered malls 


403.2,403.3 


High-rise buildings 


404.3 


Atriums 


405.3 


Underground structures 


407.5 


Group 1-2 


410.6 


Stages 


411.4 


Special amusement buildings 


412.4.6,412.4.6.1, 
412.6.5 


Aircraft hangars 


415.6.2.4 


Group H-2 


416.4 


Flammable finishes 


417.4 


Drying rooms 


507 


Unlimited area buildings 


508.2.5 


Incidental accessory occupancies 


1028.6.2.3 


Smoke-protected assembly seating 


IFC 


Sprinkler system requirements as set forth in 
Section 903.2.11.6 of the International Fire 
Code 



[F] 903.3.1 Standards. Sprinkler systems shall be designed 
and installed in accordance with Section 903.3.1.1, 
903.3.1.2 or 903.3.1.3. 

[F] 903.3.1.1 NFPA 13 sprinkler systems. Where the 
provisions of this code require that a building or portion 
thereof be equipped throughout with an automatic sprin- 
kler system in accordance with this section, sprinklers 
shall be installed throughout in accordance with NFPA 
13 except as provided in Section 903.3.1.1.1. 

[F] 903.3.1.1.1 Exempt locations. Automatic sprin- 
klers shall not be required in the following rooms or 
areas where such rooms or areas are protected with an 
approved automatic fire detection system in accor- 
dance with Section 907.2 that will respond to visible 
or invisible particles of combustion. Sprinklers shall 
not be omitted from any room merely because it is 
damp, of fire-resistance-rated construction or con- 
tains electrical equipment. 

1. Any room where the application of water, or 
flame and water, constitutes a serious life or fire 
hazard. 

2. Any room or space where sprinklers are consid- 
ered undesirable because of the nature of the 
contents, when approvedby the fire code offi- 
cial. 

3. Generator and transformer rooms separated 
from the remainder of the building by walls and 
floor/ceiling or roof/ceiling assemblies having 
afire-resistance rating of notiess than 2 hours. 



4. Rooms or areas that are of noncombustible con- 
struction with wholly noncombustible con- 
tents. 

5. Fire service access elevator machine rooms and 
machinery spaces. 

[F] 903.3.1.2 NFPA 13R sprinkler systems. Where 
allowed in buildings of Group R,up to and including four 
stories in height, automatic sprinkler systems shall be 
installed throughout in accordance with NFPA 13R. 

[F] 903.3.1.2.1 Balconies and decks. Sprinkler pro- 
tection shall be provided for exterior balconies, decks 
and ground floor patios of dwelling units where the 
building is of Type V construction, provided there is a 
roof or deck above. Sidewall sprinklers that are used 
to protect such areas shall be permitted to be located 
such that their deflectors are within 1 inch (25 mm) to 
6 inches (152 mm) below the structural members and 
a maximum distance of 14 inches (356 mm) below the 
deck of the exterior balconies and decks that are con- 
structed of open wood joist construction. 

[F] 903.3.1.3 NFPA 13D sprinkler systems. Where 
allowed, automatic sprinkler systems installed in one- 
and two-family dwellings and townhouses shall be 
installed throughout in accordance with NFPA 13D. 

[F] 903.3.2 Quick-response and residential sprinklers. 
Where automatic sprinkler systems are required by this 
code, quick-response or residential automatic sprinklers 
shall be installed in the following areas in accordance with 
Section 903.3.1 and their listings: 

1. Throughout all spaces within a smoke compartment 
containing patient sleeping units in Group 1-2 in 
accordance with this code. 

2. Dwelling units, and sleeping units in Group Rand 1-1 
occupancies. 

3. Light-hazard occupancies as defined in NFPA 13. 

[F] 903.3.3 Obstructed locations. Automatic sprinklers 
shall be installed with due regard to obstructions that will 
delay activation or obstruct the water distribution pattern. 
Automatic sprinklers shall be installed in or under covered 
kiosks, displays, booths, concession stands, or equipment 
that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot 
(914 mm) clearance shall be maintained between automatic 
sprinklers and the top of piles of combustible fibers. 

Exception: Kitchen equipment under exhaust hoods 
protected with a fire-extinguishing system in accordance 
with Section 904. 

[F] 903.3.4 Actuation. Automatic sprinkler systems shall 
be automatically actuated unless specifically provided for in 
this code. 

[F] 903.3.5 Water supplies. Water supplies for automatic 
sprinkler systems shall comply with this section and the 
standards referenced in Section 903.3.1. The potable water 
supply shall be protected against backflow in accordance 
with the requirements of this section and the International 
Plumbing Code. 



2009 INTERNATIONAL BUILDING CODE® 



187 



FIRE PROTECTION SYSTEMS 



[F] 903.3.5.1 Domestic services. Where the domestic 
service provides the water supply for the automatic 
sprinkler system, the supply shall be in accordance with 
this section. 

[F] 903.3.5.1.1 Limited area sprinkler systems. 
Limited area sprinkler systems serving fewer than 20 
sprinklers on any single connection are permitted to 
be connected to the domestic service where a wet 
automatic standpipe is not available. Limited area 
sprinkler systems connected to domestic water sup- 
plies shall comply with each of the following require- 
ments: 

1. Valves shall not be installed between the 
domestic water riser control valve and the 
sprinklers. 

Exception: An approved indicating control 
valve supervised in the open position in 
accordance with Section 903.4. 

2. The domestic service shall be capable of sup- 
plying the simultaneous domestic demand and 
the sprinkler demand required to be hydrauli- 
cally calculated by NFPA 13, NFPA 13R or 
NFPA 13D. 

\F] 903.3.5.1.2 Residential combination services. A 
single combination water supply shall be allowed pro- 
vided that the domestic demand is added to the sprin- 
kler demand as required by NFPA 13R. 

\F] 903.3.5.2 Secondary water supply. A secondary 
on-site water supply equal to the hydraulically calculated 
sprinkler demand, including the hose stream require- 
ment, shall be provided for high-rise buildings assigned 
to Seismic Design Category C, D, E or F as determined 
by this code. The secondary water supply shall have a 
duration of not less than 30 minutes as determined by the 
occupancy hazard classification in accordance with 
NFPA 13. 

Exception: Existing buildings. 

[F] 903.3.6 Hose threads. Fire hose threads and fittings 
used in connection with automatic sprinkler systems shall 
be as prescribed by the fire code official. 

[F] 903.4 Sprinkler system supervision and alarms. All 
valves controlling the water supply for automatic sprinkler sys- 
tems, pumps, tanks, water levels and temperatures, critical air 
pressures and waterflow switches on all sprinkler systems shall 
be electrically supervised by a listed fire alarm control unit. 



Exceptions: 

1. Automatic sprinkler systems protecting one- 
two-family dwellings. 



and 



Limited area systems serving fewer than 20 sprin- 
klers. 

Automatic sprinkler systems installed in accordance 
with NFPA 13R where a common supply main is used 
to supply both domestic water and the automatic 



sprinkler system, and a separate shutoff valve for the 
automatic sprinkler system is not provided. 

4. Jockey pump control valves that are sealed or locked 
in the open position. 

5. Control valves to commercial kitchen hoods, paint 
spray booths or dip tanks that are sealed or locked in 
the open position. 

6. Valves controlling the fuel supply to fire pump 
engines that are sealed or locked in the open position. 

7. Trim valves to pressure switches in dry, preaction and 
deluge sprinkler systems that are sealed or locked in 
the open position. 

[F] 903.4.1 Monitoring. Alarm, supervisory and trouble 
signals shall be distinctly different and shall be automati- 
cally transmitted to an approved supervising station or, 
when approvedby the fire code official, shall sound an audi- 
ble signal at a constantly attended location. 

Exceptions: 

1. Underground key or hub valves in roadway boxes 
provided by the municipality or public utility are 
not required to be monitored. 

2. Backflow prevention device test valves located in 
limited area sprinkler system supply piping shall 
be locked in the open position. In occupancies 
required to be equipped with a fire alarm system, 
the backflow preventer valves shall be electrically 
supervised by a tamper switch installed in accor- 
dance with NFPA 72 and separately annunciated. 

[F] 903.4.2 Alarms. Approved audible devices shall be con- 
nected to every automatic sprinkler system. Such sprinkler 
waterflow alarm devices shall be activated by waterflow 
equivalent to the flow of a single sprinkler of the smallest 
orifice size installed in the system. Alarm devices shall be 
provided on the exterior of the building in an approvedloca- 
tion. Where a fire alarm system is installed, actuation of the 
automatic sprinkler system shall actuate the building fire 
alarm system. 

[F] 903.4.3 Floor control valves. Approved supervised 
indicating control valves shall be provided at the point of 
connection to the riser on each floor in high-rise buildings. 

[F] 903.5 Testing and maintenance. Sprinkler systems shall 
be tested and maintained in accordance with the International 
Fire Code. 



SECTION 904 

ALTERNATIVE AUTOMATIC 

FIRE-EXTINGUISHING SYSTEMS 

[F] 904.1 General. Automatic fire- extinguishing systems, 
other than automatic sprinkler systems, shall be designed, 
installed, inspected, tested and maintained in accordance with 
the provisions of this section and the applicable referenced 
standards. 

[F] 904.2 Where required. Automatic fire-extinguishing sys- 
tems installed as an alternative to the required automatic sprin- 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



kler systems of Section 903 shall be approvedby the fire code 
official. Automatic fire-extinguishing systems shall not be con- 
sidered alternatives for the purposes of exceptions or reduc- 
tions allowed by other requirements of this code. 

\F] 904.2.1 Commercial hood and duct systems. Each 
required commercial kitchen exhaust hood and duct system 
required by Section 609 of the International Fire Code or 
Chapter 5 of the International Mechanical Code to have a 
Type I hood shall be protected with an approved automatic 
fire-extinguishing system installed in accordance with this 
code. 

[F] 904.3 Installation. Automatic fire-extinguishing systems 
shall be installed in accordance with this section. 

\F] 904.3.1 Electrical wiring. Electrical wiring shall be in 
accordance with NFPA 70. 

\F] 904.3.2 Actuation. Automatic fire-extinguishing sys- 
tems shall be automatically actuated and provided with a 
manual means of actuation in accordance with Section 
904.11.1. 

\F] 904.3.3 System interlocking. Automatic equipment 
interlocks with fuel shutoffs, ventilation controls, door 
closers, window shutters, conveyor openings, smoke and 
heat vents and other features necessary for proper operation 
of the fire-extinguishing system shall be provided as 
required by the design and installation standard utilized for 
the hazard. 

\F] 904.3.4 Alarms and warning signs. Where alarms are 
required to indicate the operation of automatic fire-extin- 
guishing systems, distinctive audible and visible alarms and 
warning signs shall be provided to warn of pending agent 
discharge. Where exposure to automatic-extinguishing 
agents poses a hazard to persons and a delay is required to 
ensure the evacuation of occupants before agent discharge, 
a separate warning signal shall be provided to alert occu- 
pants once agent discharge has begun. Audible signals shall 
be in accordance with Section 907.6.2. 

\F] 904.3.5 Monitoring. Where a building fire alarm sys- 
tem is installed, automatic fire-extinguishing systems shall 
be monitored by the building fire alarm system in accor- 
dance with NFPA 72. 

[F] 904.4 Inspection and testing. Automatic fire-extinguish- 
ing systems shall be inspected and tested in accordance with 
the provisions of this section prior to acceptance. 

[F] 904.4.1 Inspection. Prior to conducting final accep- 
tance tests, the following items shall be inspected: 

1. Hazard specification for consistency with design haz- 
ard. 

2. Type, location and spacing of automatic- and man- 
ual-initiating devices. 

3. Size, placement and position of nozzles or discharge 
orifices. 

4. Location and identification of audible and visible 
alarm devices. 

5. Identification of devices with proper designations. 



6. Operating instructions. 

[F] 904.4.2 Alarm testing. Notification appliances, con- 
nections to fire alarm systems and connections to approved 
supervising stations shall be tested in accordance with this 
section and Section 907 to verify proper operation. 

[F] 904.4.2.1 Audible and visible signals. The audibil- 
ity and visibility of notification appliances signaling 
agent discharge or system operation, where required, 
shall be verified. 

\F] 904.4.3 Monitor testing. Connections to protected pre- 
mises and supervising station fire alarm systems shall be 
tested to verify proper identification and retransmission of 
alarms from automatic fire-extinguishing systems. 

\F] 904.5 Wet-chemical systems. Wet-chemical extinguish- 
ing systems shall be installed, maintained, periodically 
inspected and tested in accordance with NFPA 17A and their 
listing. 

[F] 904.6 Dry-chemical systems. Dry-chemical extinguishing 
systems shall be installed, maintained, periodically inspected 
and tested in accordance with NFPA 17 and their listing. 

[F] 904.7 Foam systems. Foam-extinguishing systems shall be 
installed, maintained, periodically inspected and tested in 
accordance with NFPA 11 and NFPA 16 and their listing. 

[F] 904.8 Carbon dioxide systems. Carbon dioxide extin- 
guishing systems shall be installed, maintained, periodically 
inspected and tested in accordance with NFPA 12 and their list- 
ing. 

[F] 904.9 Halon systems. Halogenated extinguishing systems 
shall be installed, maintained, periodically inspected and tested 
in accordance with NFPA 12A and their listing. 

[F] 904.10 Clean-agent systems. Clean- agent fire-extinguish- 
ing systems shall be installed, maintained, periodically 
inspected and tested in accordance with NFPA 2001 and their 
listing. 

[F] 904.11 Commercial cooking systems. The automatic 
fire-extinguishing system for commercial cooking systems 
shall be of a type recognized for protection of commercial 
cooking equipment and exhaust systems of the type and 
arrangement protected. Preengineered automatic dry- and 
wet-chemical extinguishing systems shall be tested in accor- 
dance with UL 300 and listed and labeled for the intended 
application. Other types of automatic fire-extinguishing sys- 
tems shall be listed and labeled for specific use as protection 
for commercial cooking operations. The system shall be 
installed in accordance with this code, its listing and the manu- 
facturer's installation instructions. Automatic fire-extinguish- 
ing systems of the following types shall be installed in 
accordance with the referenced standard indicated, as follows: 

1. Carbon dioxide extinguishing systems, NFPA 12. 

2. Automatic sprinkler systems, NFPA 13. 

3. Foam-water sprinkler system or foam-water spray sys- 
tems, NFPA 16. 

4. Dry-chemical extinguishing systems, NFPA 17. 



2009 INTERNATIONAL BUILDING CODE® 



189 



FIRE PROTECTION SYSTEMS 



5. Wet-chemical extinguishing systems, NFPA 17A. 

Exception: Factory-built commercial cooking recirculat- 
ing systems that are tested in accordance with UL 71 OB and 
listed, labeled and installed in accordance with Section 
304.1 of the International Mechanical Code. 

[F] 904.11.1 Manual system operation. A manual actua- 
tion device shall be located at or near a means of egress hora 
the cooking area a minimum of 10 feet (3048 mm) and a 
maximum of 20 feet (6096 mm) from the kitchen exhaust 
system. The manual actuation device shall be installed not 
more than 48 inches (1200 mm) or less than 42 inches (1067 
mm) above the floor and shall clearly identify the hazard 
protected. The manual actuation shall require a maximum 
force of 40 pounds (178 N) and a maximum movement of 14 
inches (356 mm) to actuate the fire suppression system. 

Exception: Automatic sprinkler systems shall not be 
required to be equipped with manual actuation means. 

[F] 904.11.2 System interconnection. The actuation of the 
fire suppression system shall automatically shut down the 
fuel or electrical power supply to the cooking equipment. 
The fuel and electrical supply reset shall be manual. 

[F] 904.11.3 Carbon dioxide systems. When carbon diox- 
ide systems are used, there shall be a nozzle at the top of the 
ventilating duct. Additional nozzles that are symmetrically 
arranged to give uniform distribution shall be installed 
within vertical ducts exceeding 20 feet (6096 mm) and hori- 
zontal ducts exceeding 50 feet (15 240 mm). Dampers shall 
be installed at either the top or the bottom of the duct and 
shall be arranged to operate automatically upon activation 
of the fire-extinguishing system. Where the damper is 
installed at the top of the duct, the top nozzle shall be imme- 
diately below the damper. Automatic carbon dioxide 
fire-extinguishing systems shall be sufficiently sized to pro- 
tect against all hazards venting through a common duct 
simultaneously. 

\F] 904.11.3.1 Ventilation system. Commercial-type 
cooking equipment protected by an automatic carbon 
dioxide-extinguishing system shall be arranged to shut 
off the ventilation system upon activation. 

\F] 904.11.4 Special provisions for automatic sprinkler 
systems. Automatic sprinkler systems protecting commer- 
cial-type cooking equipment shall be supplied from a sepa- 
rate, readily accessible, indicating-type control valve that is 
identified. 

[F] 904.11.4.1 Listed sprinklers. Sprinklers used for 
the protection of fryers shall be tested in accordance with 
UL 199E, listed for that application and installed in 
accordance with their listing. 



SECTION 905 
STANDPIPE SYSTEMS 

[F] 905.1 General. Standpipe systems shall be provided in new 
buildings and structures in accordance with this section. Fire 
hose threads used in connection with standpipe systems shall 
be approved and shall be compatible with fire department hose 
threads. The location of fire department hose connections shall 



be approved. In buildings used for high-piled combustible 
storage, fire protection shall be in accordance with the Interna- 
tional Fire Code. 

[F] 905.2 Installation standard. Standpipe systems shall be 
installed in accordance with this section and NFPA 14. 

[F] 905.3 Required installations. Standpipe systems shall be 
installed where required by Sections 905.3.1 through 905.3.7 
and in the locations indicated in Sections 905.4, 905.5 and 
905.6. Standpipe systems are allowed to be combined with 
automatic sprinkler systems. 

Exception: Standpipe systems are not required in Group 
R-3 occupancies. 

[F] 905.3.1 Height. Class III standpipe systems shall be 
installed throughout buildings where the floor level of the 
highest story is located more than 30 feet (9144 mm) above 
the lowest level of fire department vehicle access, or where 
the floor level of the lowest storyis located more than 30 feet 
(9144 mm) below the highest level of fire department vehi- 
cle access. 

Exceptions: 

1. Class I standpipes are allowed in buildings 
equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1 or 
903.3.1.2. 

2. Class I manual standpipes are allowed in open 
parking garages where the highest floor is located 
not more than 150 feet (45 720 mm) above the low- 
est level of fire department vehicle access. 

3. Class I manual dry standpipes are allowed in open 
parking garages that are subject to freezing tem- 
peratures, provided that the hose connections are 
located as required for Class II standpipes in accor- 
dance with Section 905.5. 

4. Class I standpipes are allowed in basements 
equipped throughout with an automatic sprinkler 
system. 

5. In determining the lowest level of fire department 
vehicle access, it shall not be required to consider: 

5.1. Recessed loading docks for four vehicles 
or less; and 

5.2. Conditions where topography makes 
access from the fire department vehicle to 
the building impractical or impossible. 

[F] 905.3.2 Group A. Class I automatic wet standpipes 
shall be provided in nonsprinklered Group A buildings hav- 
ing an occupant loa d exceeding 1,000 persons. 

Exceptions: 

1. Open-air-seating spaces without enclosed spaces. 

2. Class I automatic dry and semiautomatic dry 
standpipes or manual wet standpipes are allowed 
in buildings where the highest floor surface used 
for human occupancy is 75 feet (22 860 mm) or 
less above the lowest level of fire department vehi- 
cle access. 



190 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 905.3.3 Covered mall buildings. A coveredmall build- 
ing shall be equipped throughout with a standpipe system 
where required by Section 905.3.1. Coveredmall buildings 
not required to be equipped with a standpipe system by Sec- 
tion 905.3. 1 shall be equipped with Class I hose connections 
connected to the automatic sprinkler system sized to deliver 
water at 250 gallons per minute (946 A L/min) at the most 
hydraulically remote hose connection while concurrently 
supplying the automatic sprinkler system demand. The 
standpipe system shall be designed not to exceed a 50 
pounds per square inch (psi) (345 kPa) residual pressure 
loss with a flow of 250 gallons per minute (946.4 L/min) 
from the fire department connection to the hydraulically 
most remote hose connection. Hose connections shall be 
provided at each of the following locations: 

1. Within the mall at the entrance to each exit passage- 
way or corridor. 

2. At each floor-level landing within enclosed stairways 
opening directly on the mall. 

3. At exterior public entrances to the mall. 

4. At other locations as necessary so that the distance to 
reach all portions of a tenant space does not exceed 
200 feet (60 960 mm) from a hose connection. 

[F] 905.3.4 Stages. Stages greater than 1,000 square feet in 
area (93 m 2 ) shall be equipped with a Class III wet standpipe 
system with l 1 / 2 -inch and 2 1 / 2 -inch (38 mm and 64 mm) 
hose connections on each side of the stage. 

Exception: Where the building or area is equipped 
throughout with an automatic sprinkler system, a 
l 1 / 2-inch (38 mm) hose connection shall be installed in 
accordance with NFPA 13 or in accordance with NFPA 
14 for Class II or III standpipe s. 

\F] 905.3.4.1 Hose and cabinet. The l 1 / 2 -inch (38 mm) 
hose connections shall be equipped with sufficient 
lengths of l 1 / 2 -inch (38 mm) hose to provide fire protec- 
tion for the stage area. Hose connections shall be 
equipped with an approved adjustable fog nozzle and be 
mounted in a cabinet or on a rack. 

[F] 905.3.5 Underground buildings. Underground build- 
ings shall be equipped throughout with a Class I automatic 
wet or manual wet standpipe system. 

[F] 905.3.6 Helistops and heliports. Buildings with a 
helistop or heliport that are equipped with a standpipe shall 
extend the standpipe to the roof level on which the helistop 
or heliport is located in accordance with Section 1107.5 of 
the International Fire Code. 

[F] 905.3.7 Marinas and boatyards. Standpipes in mari- 
nas and boatyards shall comply with Chapter 45 of the Inter- 
national Fire Code. 

[F] 905.4 Location of Class I standpipe hose connections. 
Class I standpipe hose connections shall be provided in all of 
the following locations: 

1. In every required stairway, a hose connection shall be 
provided for each floor level above or below grade. Hose 
connections shall be located at an intermediate floor 



level landing between floors, unless otherwise approved 
by the fire code official. 

2. On each side of the wall adjacent to the exit opening of a 
horizontal exit. 

Exception: Where floor areas adjacent to a horizon- 
talexit are reachable from exit stairwayhose connec- 
tions by a 30-foot (9144 mm) hose stream from a 
nozzle attached to 100 feet (30 480 mm) of hose, a 
hose connection shall not be required at the horizontal 
exit. 

3. In every exit passageway, at the entrance from the exit 
passageway to other areas of a building. 

Exception: Where floor areas adjacent to an exitpas- 
sageway are reachable from exit stairway hose con- 
nections by a 30-foot (9144 mm) hose stream from a 
nozzle attached to 100 feet (30 480 mm) of hose, a 
hose connection shall not be required at the entrance 
from the exit passageway to other areas of the build- 
ing. 

4. In covered mall buildings, adjacent to each exterior pub- 
lic entrance to the mall and adjacent to each entrance 
from an exzYpassageway or exit corridor to the mall. 

5. Where the roof has a slope less than four units vertical in 
12 units horizontal (33.3-percent slope), each standpipe 
shall be provided with a hose connection located either 
on the roof or at the highest landing of a stairway with 
stair access to the roof. An additional hose connection 
shall be provided at the top of the most hydraulically 
remote standpipe for testing purposes. 

6. Where the most remote portion of a nonsprinklered floor 
or story is more than 150 feet (45 720 mm) from a hose 
connection or the most remote portion of a sprinklered 
floor or story is more than 200 feet (60 960 mm) from a 
hose connection, the fire code official is authorized to 
require that additional hose connections be provided in 
approved locations. 

[F] 905.4.1 Protection. Risers and laterals of Class I 
standpipe systems not located within an enclosed stairway 
or pressurized enclosure shall be protected by a degree of 
fire resistance equal to that required for vertical enclosures 
in the building in which they are located. 

Exception: In buildings equipped throughout with an 
approved automatic sprinkler system, laterals that are 
not located within an enclosed stairway or pressurized 
enclosure are not required to be enclosed within 
fire-resistance-rated construction. 

\F] 905.4.2 Interconnection. In buildings where more than 
one standpipe is provided, the standpipes shall be intercon- 
nected in accordance with NFPA 14. 

[F] 905.5 Location of Class II standpipe hose connections. 
Class II standpipe hose connections shall be accessible and 
located so that all portions of the building are within 30 feet 
(9144 mm) of a nozzle attached to 100 feet (30 480 mm) of 
hose. 

\F] 905.5.1 Groups A-I and A-2. In Group A-I and A-2 
occupancies with occupant loads of more than 1,000, hose 



2009 INTERNATIONAL BUILDING CODE® 



191 



FIRE PROTECTION SYSTEMS 



connections shall be located on each side of any stage, on 
each side of the rear of the auditorium, on each side of the 
balcony and on each tier of dressing rooms. 

[F] 905.5.2 Protection. Fire-resistance-rated protection of 
risers and laterals of Class II standpipe systems is not 
required. 

[F] 905.5.3 Class II system I-inch hose. A minimum 
I-inch (25 mm) hose shall be permitted to be used for hose 
stations in light-hazard occupancies where investigated and 
listed for this service and where approved by the fire code 
official. 

[F] 905.6 Location of Class III standpipe hose connections. 
Class III standpipe systems shall have hose connections 
located as required for Class I standpipes in Section 905.4 and 
shall have Class II hose connections as required in Section 
905.5. 

[F] 905.6.1 Protection. Risers and laterals of Class III 
standpipe systems shall be protected as required for Class I 
systems in accordance with Section 905.4.1. 

[F] 905.6.2 Interconnection. In buildings where more than 
one Class III standpipe is provided, the standpipes shall be 
interconnected in accordance with NFPA 14. 

[F] 905.7 Cabinets. Cabinets containing fire-fighting equip- 
ment such as standpipes, fire hoses, fire extinguishers or fire 
department valves shall not be blocked from use or obscured 
from view. 

[F] 905.7.1 Cabinet equipment identification. Cabinets 
shall be identified in an approved manner by a permanently 
attached sign with letters not less than 2 inches (51 mm) 
high in a color that contrasts with the background color, 
indicating the equipment contained therein. 

Exceptions: 

1. Doors not large enough to accommodate a written 
sign shall be marked with a permanently attached 
pictogram of the equipment contained therein. 

2. Doors that have either an approvedvisual identifi- 
cation clear glass panel or a complete glass door 
panel are not required to be marked. 

[F] 905.7.2 Locking cabinet doors. Cabinets shall be 
unlocked. 

Exceptions: 

1. Visual identification panels of glass or other 
approved transparent frangible material that is 
easily broken and allows access. 

2. Approve d locking arrangements. 

3. Group 1-3. 

[F] 905.8 Dry standpipes. Dry standpipes shall not be 
installed. 

Exception: Where subject to freezing and in accordance 
with NFPA 14. 

[F] 905.9 Valve supervision. Valves controlling water sup- 
plies shall be supervised in the open position so that a change in 
the normal position of the valve will generate a supervisory sig- 



nal at the supervising station required by Section 903.4. Where 
a fire alarm system is provided, a signal shall also be transmit- 
ted to the control unit. 

Exceptions: 

1. Valves to underground key or hub valves in roadway 
boxes provided by the municipality or public utility 
do not require supervision. 

2. Valves locked in the normal position and inspected as 
provided in this code in buildings not equipped with a 
fire alarm system. 

[F] 905.10 During construction. Standpipe systems required 
during construction and demolition operations shall be pro- 
vided in accordance with Section 3311. 



SECTION 906 
PORTABLE FIRE EXTINGUISHERS 

\F] 906.1 Where required. Portable fire extinguishers shall be 
installed in the following locations. 

1. In new and existing Group A, B, E, F, H, I, M, R-I, R-2, 
R-4 and S occupancies. 

Exception: In new and existing Group A, Band E 
occupancies equipped throughout with quick 
response sprinklers, portable fire extinguishers shall 
be required only in locations specified in Items 2 
through 6. 

2. Within 30 feet (9144 mm) of commercial cooking equip- 
ment. 

3. In areas where flammable or combustible liquids are 
stored, used or dispensed. 

4. On each floor of structures under construction, except 
Group R-3 occupancies, in accordance with Section 
1415.1 of the International Fire Code. 

5. Where required by the International Fire Code sections 
indicated in Table 906.1. 

6. Special-hazard areas, including but not limited to labora- 
tories, computer rooms and generator rooms, where 
required by the fire code official. 

[F] TABLE 906.1 

ADDITIONAL REQUIRED PORTABLE FIRE EXTINGUISHERS IN 

THE INTERNATIONAL FIRE CODE 



IFC SECTION 


SUBJECT 


303.5 


Asphalt kettles 


307.5 


Open burning 


308.1.3 


Open flames-torches 


309.4 


Powered industrial trucks 


1105.2 


Aircraft towing vehicles 


1105.3 


Aircraft welding apparatus 


1105.4 


Aircraft fuel-servicing tank vehicles 


1105.5 


Aircraft hydrant fuel-servicing vehicles 


1105.6 


Aircraft fuel-dispensing stations 



(continued) 



192 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] TABLE 906.1 -continued 

ADDITIONAL REQUIRED PORTABLE FIRE EXTINGUISHERS IN 

THE INTERNATIONAL FIRE CODE 



IFC SECTION 


SUBJECT 


1107.7 


Heliports and helistops 


1208.4 


Dry cleaning plants 


1415.1 


Buildings under construction or demolition 


1417.3 


Roofing operations 


1504.4.1 


Spray-finishing operations 


1505.4.2 


Dip-tank operations 


1506.4.2 


Powder-coating areas 


1904.2 


Lumberyards/woodworking facilities 


1908.8 


Recycling facilities 


1909.5 


Exterior lumber storage 


2003.5 


Organic-coating areas 


2106.3 


Industrial ovens 


2205.5 


Motor fuel-dispensing facilities 


2210.6.4 


Marine motor fuel-dispensing facilities 


2211.6 


Repair garages 


2306.1 


Rack storage 


2404.12 


Tents and membrane structures 


2508.2 


Tire rebuilding/storage 


2604.2.6 


Welding and other hot work 


2903.6 


Combustible fibers 


3403.2.1 


Flammable and combustible liquids , general 


3404.3.3.1 


Indoor storage of flammable and combustible 
liquids 


3404.3.7.5.2 


Liquid storage rooms for flammable and 
combustible liquids 


3405.4.9 


Solvent distillation units 


3406.2.7 


Farms and construction sites-flammable and 
combustible liquids storage 


3406.4.10.1 


Bulk plants and terminals for flammable and 
combustible liquids 


3406.5.4.5 


Commercial, industrial, governmental or 
manufacturing establishments-fuel dispensing 


3406.6.4 


Tank vehicles for flammable and combustible 
liquids 


3606.5.7 


Flammable solids 


3808.2 


LP-gas 


4504.4 


Marinas 



\F] 906.2 General requirements. Portable fire extinguishers 
shall be selected, installed and maintained in accordance with 
this section and NFPA 10. 

Exceptions: 

1. The travel distance to reach an extinguisher shall not 
apply to the spectator seating portions of Group A-5 
occupancies. 



2. Thirty-day inspections shall not be required and 
maintenance shall be allowed to be once every three 
years for dry-chemical or halogenated agent portable 
fire extinguishers that are supervised by a listed and 
approved electronic monitoring device, provided that 
all of the following conditions are met: 

2.1. Electronic monitoring shall confirm that 
extinguishers are properly positioned, prop- 
erly charged and unobstructed. 

2.2. Loss of power or circuit continuity to the elec- 
tronic monitoring device shall initiate a trou- 
ble signal. 

2.3. The extinguishers shall be installed inside of a 
building or cabinet in a noncorrosive environ- 
ment. 

2.4. Electronic monitoring devices and supervi- 
sory circuits shall be tested every three years 
when extinguisher maintenance is performed. 

2.5. A written log of required hydrostatic test dates 
for extinguishers shall be maintained by the 
owner to verify that hydrostatic tests are con- 
ducted at the frequency required by NFPA 10. 

3. In Group 1-3, portable fire extinguishers shall be per- 
mitted to be located at staff locations. 

\F] 906.3 Size and distribution. The size and distribution of 
portable fire extinguishers shall be in accordance with Sections 
906.3.1 through 906.3.4. 

[F] 906.3.1 Class A fire hazards. The minimum sizes and 
distribution of portable fire extinguishers for occupancies 
that involve primarily Class A fire hazards shall comply 
with Table 906.3(1). 

[F] TABLE 906.3(1) 
FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS 





LIGHT 

(Low) 

HAZARD 

OCCUPANCY 


ORDINARY 

(Moderate) 

HAZARD 

OCCUPANCY 


EXTRA 

(High) 

HAZARD 

OCCUPANCY 


Minimum Rated Single 
Extinguisher 


2-Ac 


2-A 


4-Aa 


Maximum Floor Area 
Per Unit of A 


3,000 square 
feet 


1,500 square 
feet 


1,000 square 
feet 


Maximum Floor Area for 
Extinguisher 15 


11,250 
square feet 


11,250 
square feet 


11,250 
square feet 


Maximum Travel 
Distance to Extinguisher 


75 feet 


75 feet 


75 feet 



For 51 : I foot = 304.8 mm, I square foot = 0.0929m z , I gallon = 3.785 L. 

a. Two 2 1 / z -gallon water- type extinguishers shall be deemed the equivalent of 
one 4-A rated extinguisher. 

b. Annex E.3.3 of NFPA 10 provides more details concerning application of the 
maximum floor area criteria. 

c. Two water- type extinguishers each with a I -A rating shall be deemed the 
equivalent of one 2-A rated extinguisher for Light (Low) Hazard Occupan- 
cies. 

[F] 906.3.2 Class B fire hazards. Portable fire 
extinguishers for occupancies involving flammable or com- 
bustible liquids with depths less than or equal to 0.25-inch 



2009 INTERNATIONAL BUILDING CODE® 



193 



FIRE PROTECTION SYSTEMS 



(6.35 mm) shall be selected and placed in accordance with 
Table 906.3 (2). 

Portable fire extinguishers for occupancies involving 
flammable or combustible liquids with a depth of greater 
than 0.25-inch (6.35 mm) shall be selected and placed in 
accordance with NFPA 10. 

[F] TABLE 906.3(2) 

FLAMMABLE OR COMBUSTIBLE LIQUIDS WITH 

DEPTHS LESS THAN OR EQUAL TO 0.25 INCH 



TYPE OF 
HAZARD 


BASIC MINIMUM 
EXTINGUISHER RATING 


MAXIMUM TRAVEL DISTANCE 
TO EXTINGUISHERS (feet) 


Light (Low) 


5-B 
10-B 


30 
50 


Ordinary 

(Moderate) 


10-B 

20-B 


30 
50 


Extra (High) 


40-B 
80-B 


30 
50 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

Note: For requirements on water-soluble flammable liquids and alternative 

sizing criteria, see Section 5.5 of NFPA 10. 

\F] 906.3.3 Class C fire hazards. Portable fire 
extinguishers for Class C fire hazards shall be selected and 
placed on the basis of the anticipated Class A or B hazard. 

\F] 906.3.4 Class D fire hazards. Portable fire 
extinguishers for occupancies involving combustible met- 
als shall be selected and placed in accordance with NFPA 
10. 

\F] 906.4 Cooking grease fires. Fire extinguishers provided 
for the protection of cooking grease fires shall be of an 
approved type compatible with the automatic fire-extinguish- 
ing system agent and in accordance with Section 904.11 .5 of 
the International Fire Code. 

[F] 906.5 Conspicuous location. Portable fire extinguishers 
shall be located in conspicuous locations where they will be 
readily accessible and immediately available for use. These 
locations shall be along normal paths of travel, unless the fire 
code official determines that the hazard posed indicates the 
need for placement away from normal paths of travel. 

[F] 906.6 Unobstructed and unobscured. Portable fire 
extinguishers shall not be obstructed or obscured from view. In 
rooms or areas in which visual obstruction cannot be com- 
pletely avoided, means shall be provided to indicate the loca- 
tions of extinguishers. 

[F] 906.7 Hangers and brackets. Hand-held portable fire 
extinguishers, not housed in cabinets, shall be installed on the 
hangers or brackets supplied. Hangers or brackets shall be 
securely anchored to the mounting surface in accordance with 
the manufacturer's installation instructions. 

[F] 906.8 Cabinets. Cabinets used to house portable fire 
extinguishers shall not be locked. 

Exceptions: 

1. Where portable fire extinguishers subject to mali- 
cious use or damage are provided with a means of 
ready access. 



2. In Group 1-3 occupancies and in mental health areas 
in Group 1-2 occupancies, access to portable fire 
extinguishers shall be permitted to be locked or to be 
located in staff locations provided the staff has keys. 

[F] 906.9 Extinguisher installation. The installation of porta- 
ble fire extinguishers shall be in accordance with Sections 
906.9.1 through 906.9.3. 

[F] 906.9.1 Extinguishers weighing 40 pounds or less. 
Portable fire extinguishers having a gross weight not 
exceeding 40 pounds (18 kg) shall be installed so that their 
tops are not more than 5 feet (1524 mm) above the floor. 

[F] 906.9.2 Extinguishers weighing more than 40 
pounds. Hand-held portable fire extinguishers having a 
gross weight exceeding 40 pounds (18 kg) shall be installed 
so that their tops are not more than 3.5 feet (1067 mm) above 
the floor. 

[F] 906.9.3 Floor clearance. The clearance between the 
floor and the bottom of installed hand-held portable fire 
extinguishers shall not be less than 4 inches (102 mm). 

[F] 906.10 Wheeled units. Wheeled fire extinguishers shall be 
conspicuously located in a designated location. 



SECTION 907 
FIRE ALARM AND DETECTION SYSTEMS 

[F] 907.1 General. This section covers the application, instal- 
lation, performance and maintenance of fire alarm systems and 
their components. 

[F] 907.1.1 Construction documents. Construction docu- 
ments fox fire alarm systems shall be of sufficient clarity to 
indicate the location, nature and extent of the work proposed 
and show in detail that it will conform to the provisions of 
this code, the International Fire Code, and relevant laws, 
ordinances, rules and regulations, as determined by the fire 
code official. 

[F] 907.1.2 Fire alarm shop drawings. Shop drawings for 
fire alarm systems shall be submitted for review and 
approval prior to system installation, and shall include, but 
not be limited to, all of the following: 

1. A floor plan that indicates the use of all rooms. 

2. Locations of alarm-initiating devices. 

3. Locations of alarm notification appliances, includ- 
ing candela ratings for visible alarm notification 
appliances. 

4. Location of fire alarm control unit, transponders and 
notification power supplies. 

5. Annunciators. 

6. Power connection. 

7. Battery calculations. 

8. Conductor type and sizes. 

9. Voltage drop calculations. 



194 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



10. Manufacturers' data sheets indicating model num- 
bers and listing information for equipment, devices 
and materials. 

11. Details of ceiling height and construction. 

12. The interface of fire safety control functions. 

13. Classification of the supervising station. 

[F] 907.1.3 Equipment. Systems and components shall be 
listed and approved for the purpose for which they are 
installed. 

[F] 907.2 Where required-new buildings and structures. 
An approved Tire alarm system installed in accordance with the 
provisions of this code and NFPA 72 shall be provided in new 
buildings and structures in accordance with Sections 907.2.1 
through 907.2.23 and provide occupant notification in accor- 
dance with Section 907.5, unless other requirements are pro- 
vided by another section of this code. 

A minimum of one manual fire alarm box shall be provided 
in an approved location to initiate a fire alarm signal for fire 
alarm systems employing automatic fire detectors or waterflow 
detection devices. Where other sections of this code allow 
elimination of fire alarm boxes due to sprinklers, a single fire 
alarm box shall be installed. 

Exceptions: 

1. The manual fire alarm box is not required for fire 
alarm systems dedicated to elevator recall control and 
supervisory service. 

2. The manual fire alarm box is not required for Group 
R-2 occupancies unless required by the fire code offi- 
cial to provide a means for fire watch personnel to ini- 
tiate an alarm during a sprinkler system impairment 
event. Where provided, the manual fire alarm box 
shall not be located in an area that is accessible to the 
public. 

[F] 907.2.1 Group A. A manual fire alarm system that acti- 
vates the occupant notification system in accordance with 
Section 907.5 shall be installed in Group A occupancies 
having an occupant load of 300 or more. Portions of Group 
E occupancies occupied for assembly purposes shall be pro- 
vided with a fire alarm system as required for the Group E 
occupancy. 

Exception: Manual fire alarm boxes are not required 
where the building is equipped throughout with an auto- 
matic sprinkler system installed in accordance with Sec- 
tion 903.3.1.1 and the occupant notification appliances 
will activate throughout the notification zones upon 
sprinkler waterflow. 

[F] 907.2.1.1 System initiation in Group A occupan- 
cies with an occupant load of 1,000 or more. Activa- 
tion of the fire alarm in Group A occupancies with an 
occupant load of 1,000 or more shall initiate a signal 
using an emergency voice/alarm communications sys- 
tem in accordance with Section 907.5.2.2. 

Exception: Where approved, the prerecorded 
announcement is allowed to be manually deactivated 
for a period of time, not to exceed 3 minutes, for the 



sole purpose of allowing a live voice announcement 
from an approved, constantly attended location. 

[F] 907.2.2 Group B. A manual fire alarm system shall be 
installed in Group B occupancies where one of the follow- 
ing conditions exists: 

1. The combined Group B occupant load of all floors is 
500 or more. 

2. The Group B occupant loadis more than 100 persons 
above or below the lowest level of exit discharge. 

3. The Group B fire area contains a Group B ambulatory 
health care facility. 

Exception: Manual fire alarm boxes are not required 
where the building is equipped throughout with an auto- 
matic sprinkler system installed in accordance with Sec- 
tion 903.3.1.1 and the occupant notification appliances 
will activate throughout the notification zones upon 
sprinkler waterflow. 

[F] 907.2.2.1 Group B ambulatory health care facili- 
ties. Fire areas containing Group B ambulatory health 
care facilities shall be provided with an electronically 
supervised automatic smoke detection system installed 
within the ambulatory health care facility and in public 
use areas outside of tenant spaces, including public cor- 
ridors and elevator lobbies. 

Exception: Buildings equipped throughout with an 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1, provided the occupant notification 
appliances will activate throughout the notification 
zones upon sprinkler waterflow. 

[F] 907.2.3 Group E. A manual fire alarm system that acti- 
vates the occupant notification system in accordance with 
Section 907.5 shall be installed in Group E occupancies. 
When automatic sprinkler systems or smoke detectors are 
installed, such systems or detectors shall be connected to the 
building fire alarm system. 

Exceptions: 

1. A manual fire alarm system is not required in Group E 
occupancies with an occupant load of "less than 50. 

2. Manual fire alarm boxes are not required in Group E 
occupancies where all of the following apply: 

2.1. Interior corridors are protected by smoke de- 
tectors. 

2.2. Auditoriums, cafeterias, gymnasiums and 
similar areas are protected by heat detectors 
or other approve d detection devices. 

2.3. Shops and laboratories involving dusts or va- 
pors are protected by heat detectors or other 
approve d detection devices. 

2.4. The capability to activate the evacuation sig- 
nal from a central point is provided. 

2.5. In buildings where normally occupied spaces 
are provided with a two-way communication 
system between such spaces and a constantly 
attended receiving station from where a gen- 



2009 INTERNATIONAL BUILDING CODE® 



195 



FIRE PROTECTION SYSTEMS 



eral evacuation alarm can be sounded, except 
in locations specifically designated by the fire 
code official. 

3. Manual fire alarm boxes shall not be required in 
Group E occupancies where the building is equipped 
throughout with an approved automatic sprinkler 
system installed in accordance with Section 
903.3.1.1, the notification appliances will activate on 
sprinkler waterflow and manual activation is pro- 
vided from a normally occupied location. 

[F] 907.2.4 Group F. A manual fire alarm system that acti- 
vates the occupant notification system in accordance with 
Section 907.5 shall be installed in Group F occupancies 
where both of the following conditions exist: 

1. The Group F occupancy is two or more stories in 
height; and 

2. The Group F occupancy has a combined occupant 
loadof500 or more above or below the lowest level of 
exit discharge. 

Exception: Manual fire alarm boxes are not required 
where the building is equipped throughout with an auto- 
matic sprinkler system installed in accordance with Sec- 
tion 903.3.1.1 and the occupant notification appliances 
will activate throughout the notification zones upon 
sprinkler waterflow. 

[F] 907.2.5 Group H. A manual fire alarm system that acti- 
vates the occupant notification system shall be installed in 
Group H-5 occupancies and in occupancies used for the 
manufacture of organic coatings. An automatic smoke 
detection system that activates the occupant notification 
system shall be installed for highly toxic gases, organic per- 
oxides and oxidizers in accordance with Chapters 37, 39 
and 40, respectively, of the International Fire Code. 

[F] 907.2.6 Group I . A manual fire alarm system that acti- 
vates the occupant notification system shall be installed in 
Group 1 occupancies. An automatic smoke detection system 
that activates the occupant notification system shall be pro- 
vided in accordance with Sections 907.2.6.1, 907.2.6.2 and 
907.2.6.3.3. 

Exceptions: 

1. Manual fire alarm boxes in resident or patient 
sleeping areas of Group 1-1 and 1-2 occupancies 
shall not be required at exits if located at all nurses' 
control stations or other constantly attended staff 
locations, provided such stations are visible and 
continuously accessible and that travel distances 
required in Section 907.4.2 are not exceeded. 

2. Occupant notification systems are not required to 
be activated where private mode signaling 
installed in accordance with NFPA 72 is approved 
by the fire code official. 

[F] 907.2.6.1 Group 1-1. An automatic smoke detection 
system shall be installed in corridors, waiting areas open 
to corridors and habitable spaces other than sleeping 



units and kitchens. The system shall be activated in 
accordance with Section 907.5. 

Exceptions: 

1. Smoke detection in habitable spaces is not 
required where the facility is equipped through- 
out with an automatic sprinkler system installed 
in accordance with Section 903.3.1.1. 

2. Smoke detection is not required for exterior 
balconies. 

[F] 907.2.6.1.1 Smoke alarms. Single- and multi- 
ple-station smoke alarms shall be installed in accor- 
dance with Section 907.2.11. 

[F] 907.2.6.2 Group 1-2. An automatic smoke detection 
system shall be installed in corridors in nursing homes 
(both intermediate care and skilled nursing facilities), 
detoxification facilities and spaces permitted to be open 
to the corridors by Section 407.2. The system shall be 
activated in accordance with Section 907.5. Hospitals 
shall be equipped with smoke detection as required in 
Section 407. 

Exceptions: 

1. Corridor smoke detection is not required in 
smoke compartments that contain patient sleep- 
ing units where such units are provided with 
smoke detectors that comply with UL 268. 
Such detectors shall provide a visual display on 
the corridor side of each patient sleeping unit 
and shall provide an audible and visual alarm at 
the nursing station attending each unit. 

2. Corridor smoke detection is not required in 
smoke compartments that contain patient sleep- 
ing units where patient sleeping unit doors are 
equipped with automatic door-closing devices 
with integral smoke detectors on the unit sides 
installed in accordance with their listing, pro- 
vided that the integral detectors perform the 
required alerting function. 

[F] 907.2.6.3 Group 1-3 occupancies. Group 1-3 occu- 
pancies shall be equipped with a manual fire alarm sys- 
tem and automatic smoke detection system installed for 
alerting staff. 

[F] 907.2.6.3.1 System initiation. Actuation of an 
automatic fire-extinguishing system, a manual fire 
alarm box or a fire detector shall initiate an approved 
fire alarm signal which automatically notifies staff. 

[F] 907.2.6.3.2 Manual fire alarm boxes. Manual 
fire alarm boxes are not required to be located in 
accordance with Section 907.4.2 where the fire alarm 
boxes are provided at staff- attended locations having 
direct supervision over areas where manual fire alarm 
boxes have been omitted. 

907.2.6.3.2.1 Manual fire alarm boxes in 
detainee areas. Manual fire alarm boxes are 
allowed to be locked in areas occupied by detain- 



196 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



ees, provided that staff members are present within 
the subj ect area and have keys readily available to 
operate the manual fire alarm boxes. 

[F] 907.2.6.3.3 Automatic smoke detection system. 
An automatic smoke detection system shall be 
installed throughout resident housing areas, including 
sleeping units and contiguous day rooms, group activ- 
ity spaces and other common spaces normally acces- 
sible to residents. 

Exceptions: 

1. Other approved smoke detection arrange- 
ments providing equivalent protection, 
including, but not limited to, placing detec- 
tors in exhaust ducts from cells or behind 
protective guards listed for the purpose, are 
allowed when necessary to prevent damage 
or tampering. 

2. Sleeping units in Use Conditions 2 and 3 as 
described in Section 308. 

3. Smoke detectors are not required in sleeping 
units with four or fewer occupants in smoke 
compartments that are equipped throughout 
with an automatic sprinkler system installed 
in accordance with Section 903.3.1.1. 

[F] 907.2.7 Group M. A manual fire alarm system that acti- 
vates the occupant notification system in accordance with 
Section 907.5 shall be installed in Group M occupancies 
where one of the following conditions exists: 

1. The combined Group M occupant load of all floors is 
500 or more persons. 

2. The Group M occupantloadis more than 100 persons 
above or below the lowest level of exit discharge. 

Exceptions: 

1. A manual fire alarm system is not required in cov- 
ered mall buildings complying with Section 402. 

2. Manual fire alarm boxes are not required where the 
building is equipped throughout with an automatic 
sprinkler system installed in accordance with Sec- 
tion 903.3.1.1 and the occupant notification appli- 
ances will automatically activate throughout the 
notification zones upon sprinkler waterflow. 

[F] 907.2.7.1 Occupant notification. During times that 
the building is occupied, the initiation of a signal from a 
manual fire alarm box or from a waterflow switch shall 
not be required to activate the alarm notification appli- 
ances when an alarm signal is activated at a constantly 
attended location from which evacuation instructions 
shall be initiated over an emergency voice/alarm com- 
munication system installed in accordance with Section 
907.5.2.2. 

[F] 907.2.8 Group R-l. Fire alarm systems and smoke 
alarms shall be installed in Group R-l occupancies as 
required in Sections 907.2.8.1 through 907.2.8.3. 



[F] 907.2.8.1 Manual fire alarm system. A manual fire 
alarm system that activates the occupant notification sys- 
tem in accordance with Section 907.5 shall be installed in 
Group R-l occupancies. 

Exceptions: 

1. A manual fire alarm system is not required in 
buildings not more than two stories in height 
where all individual sleeping units and contigu- 
ous atticand crawl spaces to those units are sep- 
arated from each other and public or common 
areas by at least I-hour fire partitions and each 
individual sleeping unithas an exit directly to a 
public way, exit court or yard. 

2. Manual fire alarm boxes are not required 
throughout the building when all of the follow- 
ing conditions are met: 

2.1. The building is equipped throughout 
with an automatic sprinkler system 
installed in accordance with Section 
903.3.1.1 or 903.3.1.2; 

2.2. The notification appliances will acti- 
vate upon sprinkler waterflow; and 

2.3. At least one manual fire alarm box is 
installed at an approvediocation. 

[F] 907.2.8.2 Automatic smoke detection system. An 
automatic smoke detection system that activates the 
occupant notification system in accordance with Section 
907.5 shall be installed throughout all interior corridors 
serving sleeping units. 

Exception: An automatic smoke detection system is 
not required in buildings that do not have interior cor- 
ridors serving sleeping units and where each sleeping 
unithas a means of egress door opening directly to an 
exit or to an exterior exit access that leads directly to 
an exit. 

[F] 907.2.8.3 Smoke alarms. Single- and multiple- sta- 
tion smoke alarms shall be installed in accordance with 
Section 907.2.11. 

[F] 907.2.9 Group R-2. Fire alarm systems and smoke 
alarms shall be installed in Group R-2 occupancies as 
required in Sections 907.2.9.1 and 907.9.2. 

[F] 907.2.9.1 Manual fire alarm system. A manual fire 
alarm system that activates the occupant notification sys- 
tem in accordance with Section 907.5 shall be installed in 
Group R-2 occupancies where: 

1. Any dwelling unit or sleeping unit is located three 
or more stories above the lowest level of exit dis- 
charge; 

2. Any dwelling unit or sleeping unit is located more 
than one story below the highest level of exit dis- 
charge of exits serving the dwelling unit or sleep- 
ing unit, or 



2009 INTERNATIONAL BUILDING CODE® 



197 



FIRE PROTECTION SYSTEMS 



3. The building contains more than 16 dwelling units 
or sleeping units. 

Exceptions: 

1. A fire alarm system is not required in buildings 
not more than two stories in height where all 
dwelling units or sleeping units and contiguous 
attic and crawl spaces are separated from each 
other and public or common areas by at least 
I-hour fire partitions and each dwelling unit or 
sleeping unit has an exit directly to a public 
way, exit court or yard. 

2. Manual fire alarm boxes are not required where 
the building is equipped throughout with an 
automatic sprinkler system installed in accor- 
dance with Section 903.3.1.1 or 903.3.1.2 and 
the occupant notification appliances will auto- 
matically activate throughout the notification 
zones upon a sprinkler waterflow. 

3. A fire alarm system is not required in buildings 
that do not have interior corridors serving 
dwelling units and are protected by an approved 
automatic sprinkler system installed in accor- 
dance with Section 903 .3 . 1.1 or 903 .3 .1.2, pro- 
vided that dwelling units either have a means of 
egress door opening directly to an exterior exit 
access that leads directly to the exits or are 
served by open-ended corridors designed in 
accordance with Section 1026.6, Exception 4. 

[F] 907.2.9.2 Smoke alarms. Single- and multiple-sta- 
tion smoke alarms shall be installed in accordance with 
Section 907.2.11. 

\F] 907.2.10 Group R-4. Fire alarm systems and smoke 
alarms shall be installed in Group R-4 occupancies as 
required in Sections 907.2.10.1 through 907.2.10.3. 

[F] 907.2.10.1 Manual fire alarm system. A manual 
fire alarm system that activates the occupant notification 
system in accordance with Section 907.5 shall be 
installed in Group R-4 occupancies. 

Exceptions: 

1. A manual fire alarm system is not required in 
buildings not more than two stories in height 
where all individual sleeping units and contigu- 
ous atticand crawl spaces to those units are sep- 
arated from each other and public or common 
areas by at least I-hour fire partitions and each 
individual sleeping unithas an exit directly to a 
public way, exit court or yard. 

2. Manual fire alarm boxes are not required 
throughout the building when the following 
conditions are met: 

2.1. The building is equipped throughout 
with an automatic sprinkler system 



installed in accordance with Section 
903.3.1.1 or 903.3.1.2; 

2.2. The notification appliances will acti- 
vate upon sprinkler waterflow; and 

2.3. At least one manual fire alarm box is 
installed at an approvedlocation. 

3. Manual fire alarm boxes in resident or patient 
sleeping areas shall not be required at exits 
where located at all nurses' control stations or 
other constantly attended staff locations, pro- 
vided such stations are visible and continuously 
accessible and that travel distances required in 
Section 907.4.2.1 are not exceeded. 

\F] 907.2.10.2 Automatic smoke detection system. An 
automatic smoke detection system that activates the 
occupant notification system in accordance with Section 
907.5 shall be installed in corridors, waiting areas open 
to corridors and habitable spaces other than sleeping 
units and kitchens. 

Exceptions: 

1. Smoke detection in habitable spaces is not 
required where the facility is equipped through- 
out with an automatic sprinkler system installed 
in accordance with Section 903.3.1.1. 

2. An automatic smoke detection system is not 
required in buildings that do not have interior 
corridors serving sleeping units and where 
each sleeping unit has a means of egress door 
opening directly to an exit or to an exterior exit 
access that leads directly to an exit. 

\F] 907.2.10.3 Smoke alarms. Single- and multiple-sta- 
tion smoke alarms shall be installed in accordance with 
Section 907.2.11. 

[F] 907.2.11 Single- and multiple- station smoke alarms. 
Listed single- and multiple-station smoke alarms comply- 
ing with UL 217 shall be installed in accordance with Sec- 
tions 907.2.11.1 through 907.2.11.4 and NFPA 72. 

\F] 907.2.11.1 Group R-l. Single- or multiple-station 
smoke alarms shall be installed in all of the following 
locations in Group R-l: 

1. In sleeping areas. 

2. In every room in the path of the means of egress 
from the sleeping area to the door leading from the 
sleeping unit. 

3. In each story within the sleeping unit, including 
basements. For sleeping units with split levels and 
without an intervening door between the adjacent 
levels, a smoke alarm installed on the upper level 
shall suffice for the adjacent lower level provided 
that the lower level is less than one full storybelow 
the upper level. 



198 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 907.2.11.2 Groups R-2, R-3, R-4 and 1-1. Single- or 
multiple- station smoke alarms shall be installed and 
maintained in Groups R-2, R-3, R-4 and 1-1 regardless of 
occupant load at all of the following locations: 

1. On the ceiling or wall outside of each separate 
sleeping area in the immediate vicinity of bed- 
rooms. 

2. In each room used for sleeping purposes. 

Exception: Single- or multiple- station smoke 
alarms in Group 1-1 shall not be required where 
smoke detectors are provided in the sleeping 
rooms as part of an automatic smoke detection 
system. 

3. In each story within a dwelling unit, including 
basements but not including crawl spaces and 
uninhabitable attics. In dwellings or dwelling units 
with split levels and without an intervening door 
between the adjacent levels, a smoke alarm 
installed on the upper level shall suffice for the 
adjacent lower level provided that the lower level 
is less than one full sto ry below the upper level. 

[F] 907.2.11.3 Interconnection. Where more than one 
smoke alarm is required to be installed within an individ- 
ual dwelling unitor sleeping unitin Group R-l, R-2, R-3 
or R-4, the smoke alarms shall be interconnected in such 
a manner that the activation of one alarm will activate all 
of the alarms in the individual unit. The alarm shall be 
clearly audible in all bedrooms over background noise 
levels with all intervening doors closed. 

[F] 907.2.11.4 Power source. In new construction, 
required smoke alarms shall receive their primary power 
from the building wiring where such wiring is served 
from a commercial source and shall be equipped with a 
battery backup. Smoke alarms with integral strobes that 
are not equipped with battery backup shall be connected 
to an emergency electrical system. Smoke alarms shall 
emit a signal when the batteries are low. Wiring shall be 
permanent and without a disconnecting switch other than 
as required for overcurrent protection. 

Exception: Smoke alarms are not required to be 
equipped with battery backup where they are con- 
nected to an emergency electrical system. 

[F] 907.2.12 Special amusement buildings. An automatic 
smoke detection system shall be provided in special amuse- 
ment buildings in accordance with Sections 907.2.12.1 
through 907.2.12.3. 

[F] 907.2.12.1 Alarm. Activation of any single smoke 
detector, the automatic sprinkler system or any other 
automatic fire detection device shall immediately sound 
an alarm at the building at a constantly attended location 
from which emergency action can be initiated, including 
the capability of manual initiation of requirements in 
Section 907.2.12.2. 

[F] 907.2.12.2 System response. The activation of two 
or more smoke detectors, a single smoke detector 
equipped with an alarm verification feature, the auto- 



matic sprinkler system or other approved fire detection 
device shall automatically: 

1. Cause illumination of the means of egress with 
light of not less than 1 foot-candle (11 lux) at the 
walking surface level; 

2. Stop any conflicting or confusing sounds and 
visual distractions; 

3. Activate an approved directional exzYmarking that 
will become apparent in an emergency; and 

4. Activate a prerecorded message, audible through- 
out the special amusement bUilding, instructing 
patrons to proceed to the nearest exit. Alarm sig- 
nals used in conjunction with the prerecorded mes- 
sage shall produce a sound which is distinctive 
from other sounds used during normal operation. 

[F] 907.2.12.3 Emergency voice/alarm communica- 
tion system. An emergency voice/alarm communication 
system, which is also allowed to serve as a public address 
system, shall be installed in accordance with Section 
907.5.2.2 and be audible throughout the entire special 
amusement bUilding. 

[Fl 907.2.13 High-rise buildings. Buildings with a floor 
used for human occupancy located more than 75 feet (22 
860 mm) above the lowest level of fire department vehicle 
access shall be provided with an automatic smoke detection 
system in accordance with Section 907.2.13.1, afire depart- 
ment communication system in accordance with Section 
907.2.13.2 and an emergency voice/alarm communication 
system in accordance with Section 907.5.2.2. 

Exceptions: 

1. Airport traffic control towers in accordance with 
Sections 907.2.22 and 412. 

2. Open parking garages in accordance with Section 
406.3. 

3. Buildings with an occupancy in Group A-5 in 
accordance with Section 303.1. 

4. Low-hazard special occupancies in accordance 
with Section 503.1.1. 

5. Buildings with an occupancy in Group H-l, H-2 or 
H-3 in accordance with Section 415 . 

6. In Group 1-1 and 1-2 occupancies, the alarm shall 
sound at a constantly attended location and gen- 
eral occupant notification shall be broadcast by the 
emergency voice/alarm communication system. 

[F] 907.2.13.1 Automatic smoke detection. Automatic 
smoke detection in high-rise buildings shall be in accor- 
dance with Sections 907.2.13.1.1 and 907.2.13.1.2. 

[F] 907.2.13.1.1 Area smoke detection. Area smoke 
detectors shall be provided in accordance with this 
section. Smoke detectors shall be connected to an 
automatic fire alarm system. The activation of any 
detector required by this section shall operate the 
emergency voice/alarm communication system in 



2009 INTERNATIONAL BUILDING CODE® 



199 



FIRE PROTECTION SYSTEMS 



accordance with Section 907.5.2.2. Smoke detectors 
shall be located as follows: 

1. In each mechanical equipment, electrical, 
transformer, telephone equipment or similar 
room which is not provided with sprinkler pro- 
tection. 

2. In each elevator machine room and in elevator 
lobbies. 

[F] 907.2.13.1 .2 Duct smoke detection. Duct smoke 
detectors complying with Section 907.3.1 shall be 
located as follows: 

1. In the main return air and exhaust air plenum of 
each air-conditioning system having a capacity 
greater than 2,000 cubic feet per minute (cfm) 
(0.94 m 3 /s). Such detectors shall be located in a 
serviceable area downstream of the last duct 
inlet. 

2. At each connection to a vertical duct or riser 
serving two or more stories from a return air 
duct or plenum of an air-conditioning system. 
In Group R-l and R-2 occupancies, a smoke 
detector is allowed to be used in each return air 
riser carrying not more than 5,000 cfm (2.4 
m 3 /s) and serving not more than 10 air-inlet 
openings. 

[F] 907.2.13.2 Fire department communication sys- 
tem. Where a wired communication system is approved 
in lieu of a radio coverage system in accordance with 
Section 510 of the International Fire Code, the wired fire 
department communication system shall be designed 
and installed in accordance with NFPA 72 and shall oper- 
ate between a fire command center complying with Sec- 
tion 911, elevators, elevator lobbies, emergency and 
standby power rooms, fire pump rooms, areas ofrefuge 
and inside enclosed exit stairways. The fire department 
communication device shall be provided at each floor 
level within the enclosed exit stairway. 

[F] 907.2.14 Atriums connecting more than two stories. 
A fire alarm system shall be installed in occupancies with an 
atrium that connects more than two stories, with smoke 
detection installed throughout the atrium. The system shall 
be activated in accordance with Section 907.5. Such occu- 
pancies in Group A, E or M shall be provided with an emer- 
gency voice/alarm communication system complying with 
the requirements of Section 907.5.2.2. 

[F] 907.2.15 High-piled combustible storage areas. An 
automatic smoke detection system shall be installed 
throughout high-piled combustible storage areas where 
required by Section 2306.5 of the International Fire Code. 

[F] 907.2.16 Aerosol storage uses. Aerosol storage rooms 
and general-purpose warehouses containing aerosols shall 
be provided with an approved manual fire alarm system 
where required by the International Fire Code. 

[F] 907.2.17 Lumber, wood structural panel and veneer 
mills. Lumber, wood structural panel and veneer mills shall 
be provided with a manual fire alarm system. 



[F] 907.2.18 Underground buildings with smoke control 
systems. Where a smoke control system is installed in an 
underground building in accordance with this code, auto- 
matic smoke detectors shall be provided in accordance with 
Section 907.2.18.1. 

[F] 907.2.18.1 Smoke detectors. A minimum of one 
smoke detector listed fox the intended purpose shall be 
installed in the following areas : 

1. Mechanical equipment, electrical, transformer, 
telephone equipment, elevator machine or similar 
rooms. 

2. Elevator lobbies. 

3. The main return and exhaust air plenum of each 
air-conditioning system serving more than one 
story and located in a serviceable area downstream 
of the last duct inlet. 

4. Each connection to a vertical duct or riser serving 
two or more floors from return air ducts or ple- 
nums of heating, ventilating and air-conditioning 
systems, except that in Group R occupancies, a 
listedsmoke detector is allowed to be used in each 
return air riser carrying not more than 5,000 cfm 
(2.4 m 3 /s) and serving not more than 10 air-inlet 
openings. 

\F] 907.2.18.2 Alarm required. Activation of the smoke 
control system shall activate an audible alarm at a con- 
stantly attended location. 

[F] 907.2.19 Deep underground buildings. Where the 
lowest level of a structure is more than 60 feet (18 288 mm) 
below the finished floor of the lowest level of exit discharge, 
the structure shall be equipped throughout with a manual 
fire alarm system, including an emergency voice/alarm 
communication system installed in accordance with Section 
907.5.2.2. 

[F] 907.2.20 Covered mall buildings. Covered mall build- 
ings exceeding 50,000 square feet (4645 m 2 ) in total floor 
area shall be provided with an emergency voice/alarm com- 
munication system. An emergency voice/alarm communi- 
cation system serving a mall, required or otherwise, shall be 
accessible to the fire department. The system shall be pro- 
vided in accordance with Section 907.5.2.2. 

[F] 907.2.21 Residential aircraft hangars. A minimum of 
one single-station smoke alarm shall be installed within a 
residential aircraft hangar as defined in Section 412.3.1 and 
shall be interconnected into the residential smoke alarm or 
other sounding device to provide an alarm which will be 
audible in all sleeping areas of the dwelling. 

[F] 907.2.22 Airport traffic control towers. An automatic 
smoke detection system that activates the occupant notifica- 
tion system in accordance with Section 907.5 shall be pro- 
vided in airport control towers in all occupiable and 
equipment spaces. 

Exception: Audible appliances shall not be installed 
within the control tower cab. 



200 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 907.2.23 Battery rooms. An automatic smoke detec- 
tion system shall be installed in areas containing stationary 
storage battery systems with a liquid capacity of more than 
50 gallons (189 L). 

[F] 907.3 Fire safety functions. Automatic fire detectors uti- 
lized for the purpose of performing fire safety functions shall 
be connected to the building's fire alarm control unit where a 
fire alarm system is required by Section 907.2. Detectors shall, 
upon actuation, perform the intended function and activate the 
alarm notification appliances or activate a visible and audible 
supervisory signal at a constantly attended location. In build- 
ings not equipped with a fire alarm system, the automatic fire 
detector shall be powered by normal electrical service and, 
upon actuation, perform the intended function. The detectors 
shall be located in accordance with NFPA 72 . 

[F] 907.3.1 Duct smoke detectors. Smoke detectors 
installed in ducts shall be listedfor the air velocity, tempera- 
ture and humidity present in the duct. Duct smoke detectors 
shall be connected to the building's fire alarm control unit 
when a fire alarm system is required by Section 907.2. Acti- 
vation of a duct smoke detector shall initiate a visible and 
audible supervisory signal at a constantly attended location 
and shall perform the intended fire safety function in accor- 
dance with this code and the International Mechanical 
Code. Duct smoke detectors shall not be used as a substitute 
for required open area detection. 

Exceptions: 

1. The supervisory signal at a constantly attended 
location is not required where duct smoke detec- 
tors activate the building's alarm notification 
appliances. 

2. In occupancies not required to be equipped with a 
fire alarm system, actuation of a smoke detector 
shall activate a visible and an audible signal in an 
approvediocation. Smoke detector trouble condi- 
tions shall activate a visible or audible signal in an 
approved location and shall be identified as air 
duct detector trouble. 

[F] 907.3.2 Delayed egress locks. Where delayed egress 
locks are installed on means of egress doors in accordance 
with Section 1008.1.9.6, an automatic smoke or heat detec- 
tion system shall be installed as required by that section. 

[F] 907.3.3 Elevator emergency operation. Automatic 
fire detectors installed for elevator emergency operation 
shall be installed in accordance with the provisions of 
ASME A17.1 and NFPA 72. 

[F] 907.3.4 Wiring. The wiring to the auxiliary devices and 
equipment used to accomplish the above fire safety func- 
tions shall be monitored for integrity in accordance with 
NFPA 72. 

[F] 907.4 Initiating devices. Where manual or automatic 
alarm initiation is required as part of a fire alarm system, the 
initiating devices shall be installed in accordance with Sections 
907.4.1 through 907.4.3. 

[F] 907.4.1 Protection of fire alarm control unit. In areas 
that are not continuously occupied, a single smoke detector 



shall be provided at the location of each fire alarm control 
unit, notification appliance circuit power extenders, and 
supervising station transmitting equipment. 

Exceptions: 

1. Where ambient conditions prohibit installation of 
a smoke detector, a heatdetec tor shall be permit- 
ted. 

2. The smoke detector shall not be required where the 
building is equipped throughout with an automatic 
sprinkler system in accordance with Section 
903.3.1.1 or 903.3.1.2. 

[F] 907.4.2 Manual fire alarm boxes. Where a manual fire 
alarm system is required by another section of this code, it 
shall be activated by fire alarm boxes installed in accordance 
with Sections 907.4.2.1 through 907.4.2.5. 

[F] 907.4.2.1 Location. Manual fire alarm boxes shall be 
located not more than 5 feet (1524 mm) from the 
entrance to each exit. Additional manual fire alarm boxes 
shall be located so that travel distance to the nearest box 
does not exceed 200 feet (60 960 mm). 

[F] 907.4.2.2 Height. The height of the manual fire 
alarm boxes shall be a minimum of 42 inches (1067 mm) 
and a maximum of 48 inches (1372 mm) measured verti- 
cally, from the floor level to the activating handle or lever 
of the box. 

[F] 907.4.2.3 Color. Manual fire alarm boxes shall be red 
in color. 

[F] 907.4.2.4 Signs. Where fire alarm systems are not 
monitored by a supervising station, an approved perma- 
nent sign shall be installed adjacent to each manual fire 
alarm box that reads: WHEN ALARM SOUNDS CALL 
FIRE DEPARTMENT. 

Exception: Where the manufacturer has permanently 
provided this information on the manual fire alarm 
box. 

[F] 907.4.2.5 Protective covers. The fire code official is 
authorized to require the installation of listedmanuai fire 
alarm box protective covers to prevent malicious false 
alarms or to provide the manual fire alarm box with pro- 
tection from physical damage. The protective cover shall 
be transparent or red in color with a transparent face to 
permit visibility of the manual fire alarm box. Each cover 
shall include proper operating instructions. A protective 
cover that emits a local alarm signal shall not be installed 
unless approved. Protective covers shall not project more 
than that permitted by Section 1003.3.3. 

[F] 907.4.3 Automatic smoke detection. Where an auto- 
matic smoke detection system is required it shall utilize 
smoke detectors unless ambient conditions prohibit such an 
installation. In spaces where smoke detectors cannot be uti- 
lized due to ambient conditions, approved automatic heat 
detectors shall be permitted. 

907.4.3.1 Automatic sprinkler system. For conditions 
other than specific fire safety functions noted in Section 
907.3, in areas where ambient conditions prohibit the 



2009 INTERNATIONAL BUILDING CODE® 



201 



FIRE PROTECTION SYSTEMS 



installation of smoke detectors, an automatic sprinkler 
system installed in such areas in accordance with Section 

903.3.1.1 or 903.3.1.2 and that is connected to the fire 
alarm system shall be approvedas automatic heat detec- 
tion. 

[F] 907.5 Occupant notification systems. A fire alarm system 
shall annunciate at the panel and shall initiate occupant notifi- 
cation upon activation, in accordance with Sections 907.5.1 
through 907.5.2.3.4. Where a fire alarm system is required by 
another section of this code, it shall be activated by: 

1. Automatic fire detectors. 

2. Sprinkler waterflow devices. 

3. Manual fire alarm boxes. 

4. Automatic fire-extinguishing systems. 

Exception: Where notification systems are allowed else- 
where in Section 907 to annunciate at a constantly attended 
location. 

\F] 907.5.1 Pre signal feature. A presignal feature shall not 
be installed unless approve dby the fire code official and the 
fire department. Where a presignal feature is provided, a 
signal shall be annunciated at a constantly attended location 
approvedby the fire department, in order that occupant noti- 
fication can be activated in the event of fire or other emer- 
gency. 

[F] 907.5.2 Alarm notification appliances. Alarm notifi- 
cation appliances shall be provided and shall be listed for 
their purpose. 

[F] 907.5.2.1 Audible alarms. Audible alarm notifica- 
tion appliances shall be provided and emit a distinctive 
sound that is not to be used for any purpose other than 
that of a fire alarm. 

Exception: Visible alarm notification appliances 
shall be allowed in lieu of audible alarm notification 
appliances in critical care areas of Group 1-2 occupan- 
cies. 

907.5.2.1.1 Average sound pressure. The audible 
alarm notification appliances shall provide a sound 
pressure level of 15 decibels (dBA) above the average 
ambient sound level or 5 dBA above the maximum 
sound level having a duration of at least 60 seconds, 
whichever is greater, in every occupiable space 
within the building. The minimum sound pressure 
levels shall be: 75 dBA in occupancies in Groups R 
and 1-1; 90 dBA in mechanical equipment rooms and 
60 dBA in other occupancies. 

907.5.2.1.2 Maximum sound pressure. The maxi- 
mum sound pressure level for audible alarm notifica- 
tion appliances shall be 110 dBA at the minimum 
hearing distance from the audible appliance. Where 
the average ambient noise is greater than 95 dBA, vis- 
ible alarm notification appliances shall be provided in 
accordance with NFPA 72 and audible alarm notifica- 
tion appliances shall not be required. 

907.5.2.2 Emergency voice/alarm communication 
systems. Emergency voice/alarm communication sys- 



tems required by this code shall be designed and installed 
in accordance with NFPA 72. The operation of any auto- 
matic fire detector, sprinkler waterflow device or manual 
fire alarm box shall automatically sound an alert tone fol- 
lowed by voice instructions giving approved information 
and directions for a general or staged evacuation in 
accordance with the building's fire safety and evacuation 
plans required by Section 404. In high-rise buildings, the 
system shall operate on a minimum of the alarming floor, 
the floor above and the floor below. Speakers shall be 
provided throughout the building by paging zones. At a 
minimum, paging zones shall be provided as follows: 

1. Elevator groups. 

2. Exit stairways. 

3. Each floor. 

4. Areas of refuge as defined in Section 1002.1. 

Exception: In Group 1-1 and 1-2 occupancies, the 
alarm shall sound in a constantly attended area and a 
general occupant notification shall be broadcast over 
the overhead page. 

[F] 907.5.2.2.1 Manual override. A manual override 
for emergency voice communication shall be pro- 
vided on a selective and all-call basis for all paging 
zones. 

[F] 907.5.2.2.2 Live voice messages. The emergency 
voice/alarm communication system shall also have 
the capability to broadcast live voice messages by 
paging zones on a selective and all-call basis. 

[F] 907.5.2.2.3 Alternate uses. The emergency 
voice/alarm communication system shall be allowed 
to be used for other announcements, provided the 
manual fire alarm use takes precedence over any other 
use. 

[F] 907.5.2.2.4 Emergency power. Emergency 
voice/alarm communications systems shall be pro- 
vided with an approved emergency power source. 

[F] 907.5.2.3 Visible alarms. Visible alarm notification 
appliances shall be provided in accordance with Sections 
907.5.2.3.1 through 907.5.2.3.4. 

Exceptions: 

1. Visible alarm notification appliances are not 
required in alterations, except where an exist- 
ing fire alarm system is upgraded or replaced, 
or a new fire alarm system is installed. 

2. Visible alarm notification appliances shall not 
be required in exits as defined in Section 
1002.1. 

3. Visible alarm notification appliances shall not 
be required in elevator cars. 

[F] 907.5.2.3.1 Public and common areas. Visible 
alarm notification appliances shall be provided in 
public areas and common areas. 

[F] 907.5.2.3.2 Employee work areas. Where 
employee work areas have audible alarm coverage, 



202 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



the notification appliance circuits serving the 
employee work areas shall be initially designed with a 
minimum of 20-percent spare capacity to account for 
the potential of adding visible notification appliances 
in the future to accommodate hearing impaired 
employee(s) . 

\F] 907.5.2.3.3 Groups 1-1 and R-l. Group 1-1 and 
R-l dwelling units or sleeping units in accordance 
with Table 907.5.2.3.3 shall be provided with a visible 
alarm notification appliance, activated by both the 
in-room smoke alarm and the building fire alarm sys- 
tem. 

[F] TABLE 907.5.2.3.3 
VISIBLE ALARMS 



NUMBER OF SLEEP UNITS 


SLEEPING ACCOMMODATIONS WITH 
VISIBLE ALARMS 


6 to 25 


2 


26 to 50 


4 


51 to 75 


7 


76 to 100 


9 


101 to 150 


12 


151 to 200 


14 


201 to 300 


17 


301 to 400 


20 


401 to 500 


22 


501 to 1,000 


5% of total 


1,001 and over 


50 plus 3 for each 100 over 1,000 



[F] 907.5.2.3.4 Group R-2. In Group R-2 occupan- 
cies required by Section 907 to have a fire alarm sys- 
tem, all dwelling units and sleeping units shall be 
provided with the capability to support visible alarm 
notification appliances in accordance with ICC 
AI17.1. 

[F] 907.6 Installation. A fire alarm system shall be installed in 
accordance with this section and NFPA 72. 

[F] 907.6.1 Wiring. Wiring shall comply with the require- 
ments of NFPA 70 and NFPA 72. Wireless protection sys- 
tems utilizing radio-frequency transmitting devices shall 
comply with the special requirements for supervision of 
low-power wireless systems in NFPA 72. 

[F] 907.6.2 Power supply. The primary and secondary 
power supply for the fire alarm system shall be provided in 
accordance with NFPA 72. 

Exception: Back-up power for single- station and multi- 
ple-station smoke alarms as required in Section 
907.2.11.4. 

[F] 907.6.3 Zones. Each floor shall be zoned separately and 
a zone shall not exceed 22,500 square feet (2090 m 2 ). The 



length of any zone shall not exceed 300 feet (91 440 mm) in 
any direction. 

Exception: Automatic sprinkler system zones shall not 
exceed the area permitted by NFPA 13. 

[F] 907.6.3.1 Zoning indicator panel. A zoning indica- 
tor panel and the associated controls shall be provided in 
an approved location. The visual zone indication shall 
lock in until the system is reset and shall not be canceled 
by the operation of an audible-alarm silencing switch. 

[F] 907.6.3.2 High-rise buildings. In high-rise build- 
ings, a separate zone by floor shall be provided for each 
of the following types of alarm-initiating devices where 
provided: 

1. Smoke detectors. 

2. Sprinkler waterflow devices. 

3. Manual fire alarm boxes. 

4. Other approved types of automatic fire detection 
devices or suppression systems. 

[F] 907.6.4 Access. Access shall be provided to each fire 
alarm device and notification appliance for periodic inspec- 
tion, maintenance and testing. 

\F] 907.6.5 Monitoring. Fire alarm systems required by 
this chapter or by the International Fire Code shall be moni- 
tored by an approved supervising station in accordance with 
NFPA 72. 

Exception: Monitoring by a supervising station is not 
required for: 

1. Single- and multiple-station smoke alarms 
required by Section 907.2.11. 

2. Smoke detectors in Group 1-3 occupancies. 

3. Automatic sprinkler systems in one- and two-fam- 
ily dwellings. 

[F] 907.6.5.1 Automatic telephone-dialing devices. 
Automatic telephone-dialing devices used to transmit an 
emergency alarm shall not be connected to any fire 
department telephone number unless approved by the 
fire chief. 

[F] 907.7 Acceptance tests and completion. Upon comple- 
tion of the installation, the fire alarm system and all fire alarm 
components shall be tested in accordance with NFPA 72. 

\F] 907.7.1 Single- and multiple-station alarm devices. 
When the installation of the alarm devices is complete, each 
device and interconnecting wiring for multiple- station 
alarm devices shall be tested in accordance with the smoke 
alarm provisions of NFPA 72. 

[F] 907.7.2 Record of completion. A record of completion 
in accordance with NFPA 72 verifying that the system has 
been installed and tested in accordance with the approved 
plans and specifications shall be provided. 

[F] 907.7.3 Instructions. Operating, testing and mainte- 
nance instructions and record drawings ("as-builts") and 



2009 INTERNATIONAL BUILDING CODE® 



203 



FIRE PROTECTION SYSTEMS 



equipment specifications shall be provided at an approved 
location. 

[F] 907.8 Inspection, testing and maintenance. The mainte- 
nance and testing schedules and procedures for fire alarm and 
fire detection systems shall be in accordance with Section 
907.9 of the International Fire Code. 



SECTION 908 
EMERGENCY ALARM SYSTEMS 

[F] 908.1 Group H occupancies. Emergency alarms for the 
detection and notification of an emergency condition in Group 
H occupancies shall be provided in accordance with Section 
414.7. 

[F] 908.2 Group H-5 occupancy. Emergency alarms for noti- 
fication of an emergency condition in an HPM facility shall be 
provided as required in Section 415.8.4.6. A continuous 
gas-detection system shall be provided for HPM gases in 
accordance with Section 415.8.7. 

[F] 908.3 Highly toxic and toxic materials. A gas detection 
system shall be provided to detect the presence of highly toxic 
or toxic gas at or below the permissible exposure limit (PEL) or 
ceiling limit of the gas for which detection is provided. The sys- 
tem shall be capable of monitoring the discharge from the treat- 
ment system at or below one-half the immediately dangerous to 
life and health (IDLH) limit. 

Exception: A gas-detection system is not required for toxic 
gases when the physiological warning threshold level for 
the gas is at a level below the accepted PEL for the gas. 

[F] 908.3.1 Alarms. The gas detection system shall initiate 
a local alarm and transmit a signal to a constantly attended 
control station when a short-term hazard condition is 
detected. The alarm shall be both visible and audible and 
shall provide warning both inside and outside the area 
where gas is detected. The audible alarm shall be distinct 
from all other alarms. 

Exception: Signal transmission to a constantly attended 
control station is not required when not more than one 
cylinder of highly toxic or toxic gas is stored. 

[F] 908.3.2 Shutoff of gas supply. The gas detection sys- 
tem shall automatically close the shutoff valve at the source 
on gas supply piping and tubing related to the system being 
monitored for whichever gas is detected. 

Exception: Automatic shutdown is not required for 
reactors utilized for the production of highly toxic or 
toxic compressed gases where such reactors are: 

1. Operated at pressures less than 15 pounds per 
square inch gauge (psig) (103.4 kPa). 

2. Constantly attended. 

3. Provided with readily accessible emergency shut- 
off valves. 

[F] 908.3.3 Valve closure. The automatic closure of shutoff 
valves shall be in accordance with the following: 

1. When the gas-detection sampling point initiating the 
gas detection system alarm is within a gas cabinet or 



exhausted enclosure, the shutoff valve in the gas cabi- 
net or exhausted enclosure for the specific gas 
detected shall automatically close. 

2. Where the gas-detection sampling point initiating the 
gas detection system alarm is within a gas room and 
compressed gas containers are not in gas cabinets or 
exhausted enclosures, the shutoff valves on all gas 
lines for the specific gas detected shall automatically 
close. 

3. Where the gas-detection sampling point initiating the 
gas detection system alarm is within a piping distribu- 
tion manifold enclosure, the shutoff valve for the 
compressed container of specific gas detected supply- 
ing the manifold shall automatically close. 

Exception: When the gas-detection sampling point initi- 
ating the gas-detection system alarm is at a use location 
or within a gas valve enclosure of a branch line down- 
stream of a piping distribution manifold, the shutoff 
valve in the gas valve enclosure for the branch line 
located in the piping distribution manifold enclosure 
shall automatically close. 

[F] 908.4 Ozone gas-generator rooms. Ozone gas-generator 
rooms shall be equipped with a continuous gas-detection sys- 
tem that will shut off the generator and sound a local alarm 
when concentrations above the PEL occur. 

[F] 908.5 Repair garages. A flammable-gas detection system 
shall be provided in repair garages for vehicles fueled by 
nonodorized gases in accordance with Section 406.6.6. 

[F] 908.6 Refrigerant detector. Machinery rooms shall con- 
tain a refrigerant detector with an audible and visual alarm. The 
detector, or a sampling tube that draws air to the detector, shall 
be located in an area where refrigerant from a leak will concen- 
trate. The alarm shall be actuated at a value not greater than the 
corresponding TLV-TWA values for the refrigerant classifica- 
tion indicated in the International Mechanical Code. Detectors 
and alarms shall be placed in approve d locations. 



SECTION 909 
SMOKE CONTROL SYSTEMS 

[F] 909.1 Scope and purpose. This section applies to mechan- 
ical or passive smoke control systems when they are required 
by other provisions of this code. The purpose of this section is 
to establish minimum requirements for the design, installation 
and acceptance testing of smoke control systems that are 
intended to provide a tenable environment for the evacuation or 
relocation of occupants. These provisions are not intended for 
the preservation of contents, the timely restoration of opera- 
tions or for assistance in fire suppression or overhaul activities. 
Smoke control systems regulated by this section serve a differ- 
ent purpose than the smoke- and heat-venting provisions found 
in Section 910. Mechanical smoke control systems shall not be 
considered exhaust systems under Chapter 5 of the Interna- 
tional Mechanical Code. 

[F] 909.2 General design requirements. Buildings, structures 
or parts thereof required by this code to have a smoke control 
system or systems shall have such systems designed in accor- 



204 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



dance with the applicable requirements of Section 909 and the 
generally accepted and well-established principles of engi- 
neering relevant to the design. The construction documents 
shall include sufficient information and detail to adequately 
describe the elements of the design necessary for the proper 
implementation of the smoke control systems. These docu- 
ments shall be accompanied by sufficient information and 
analysis to demonstrate compliance with these provisions. 

[F] 909.3 Special inspection and test requirements. In addi- 
tion to the ordinary inspection and test requirements which 
buildings, structures and parts thereof are required to undergo, 
smoke control systems subject to the provisions of Section 909 
shall undergo special inspections and tests sufficient to verify 
the proper commissioning of the smoke control design in its 
final installed condition. The design submission accompany- 
ing the construction documents shall clearly detail procedures 
and methods to be used and the items subject to such inspec- 
tions and tests. Such commissioning shall be in accordance 
with generally accepted engineering practice and, where possi- 
ble' based on published standards for the particular testing 
involved. The special inspections and tests required by this sec- 
tion shall be conducted under the same terms in Section 1704. 

[F] 909.4 Analysis. A rational analysis supporting the types of 
smoke control systems to be employed, their methods of opera- 
tion, the systems supporting them and the methods of construc- 
tion to be utilized shall accompany the submitted construction 
documents and shall include, but not be limited to, the items 
indicated in Sections 909.4.1 through 909.4.6. 

[F] 909.4.1 Stack effect. The system shall be designed such 
that the maximum probable normal or reverse stack effect 
will not adversely interfere with the system's capabilities. In 
determining the maximum probable stack effect, altitude, 
elevation, weather history and interior temperatures shall be 
used. 

[F] 909.4.2 Temperature effect of fire. Buoyancy and 
expansion caused by the design fire in accordance with Sec- 
tion 909.9 shall be analyzed. The system shall be designed 
such that these effects do not adversely interfere with the 
system's capabilities. 

[F] 909.4.3 Wind effect. The design shall consider the 
adverse effects of wind. Such consideration shall be consis- 
tent with the wind-loading provisions of Chapter 16. 

[F] 909.4.4 HVAC systems. The design shall consider the 
effects of the heating, ventilating and air-conditioning 
(HVAC) systems on both smoke and fire transport. The 
analysis shall include all permutations of systems status. 
The design shall consider the effects of the fire on the HVAC 
systems. 

[F] 909.4.5 Climate. The design shall consider the effects 
of low temperatures on systems, property and occupants. 
Air inlets and exhausts shall be located so as to prevent snow 
or ice blockage. 

[F] 909.4.6 Duration of operation. All portions of active or 
passive smoke control systems shall be capable of continued 
operation after detection of the fire event for a period of not 
less than either 20 minutes or 1.5 times the calculated egress 
time, whichever is less. 



[F] 909.5 Smoke barrier construction. Smoke barriers shall 
comply with Section 710, and shall be constructed and sealed 
to limit leakage areas exclusive of protected openings. The 
maximum allowable leakage area shall be the aggregate area 
calculated using the following leakage area ratios: 



1. Walls: 

2. Exitenclosures: 

3. All other shafts: 

4. Floors and roofs: 



A/A w = 0.001 00 
A/A w = 0.0003 5 
A/A =0.00150 



where: 

A = Total leakage area, square feet (m 2 ) . 

A F = Unit floor or roof area of barrier, square feet (m 2 ). 

A w = Unit wall area of barrier, square feet (m 2 ). 

The leakage area ratios shown do not include openings due 
to doors, operable windows or similar gaps. These shall be 
included in calculating the total leakage area. 

\F] 909.5.1 Leakage area. The total leakage area of the bar- 
rier is the product of the smoke barrier gross area multiplied 
by the allowable leakage area ratio, plus the area of other 
openings such as gaps and operable windows. Compliance 
shall be determined by achieving the minimum air pressure 
difference across the barrier with the system in the smoke 
control mode for mechanical smoke control systems. Pas- 
sive smoke control systems tested using other approved 
means such as door fan testing shall be as approvedby the 
fire code official. 

[F] 909.5.2 Opening protection. Openings in smoke barri- 
ers shall be protected by automatic-closing devices actuated 
by the required controls for the mechanical smoke control 
system. Door openings shall be protected by fire door 
assemblies complying with Section 715.4.3. 

Exceptions: 

1. Passive smoke control systems with auto- 
matic-closing devices actuated by spot-type 
smoke detectors listed for releasing service 
installed in accordance with Section 907.3. 

2. Fixed openings between smoke zones that are pro- 
tected utilizing the airflow method. 

3. In Group 1 -2, where such doors are installed across 
corridors, a pair of opposite-swinging doors with- 
out a center mullion shall be installed having 
vision panels with fire protection-rated glazing 
materials in fire protection-rated frames, the area 
of which shall not exceed that tested. The doors 
shall be close-fitting within operational tolerances 
and shall not have undercuts, louvers or grilles. 
The doors shall have head and jamb stops, astra- 
gals or rabbets at meeting edges and shall be auto- 
matic-closing by smoke detection in accordance 
with Section 715.4.8.3. Positive-latching devices 
are not required. 

4. Group 1-3. 



2009 INTERNATIONAL BUILDING CODE® 



205 



FIRE PROTECTION SYSTEMS 



5. Openings between smoke zones with clear ceiling 
heights of 14 feet (4267 mm) or greater and 
bank-down capacity of greater than 20 minutes as 
determined by the design fire size. 

\F] 909.5.2.1 Ducts and air transfer openings. Ducts 
and air transfer openings are required to be protected 
with a minimum Class II, 250°F (121 °C) smoke damper 
complying with Section 716. 

\F] 909.6 Pressurization method. The primary mechanical 
means of controlling smoke shall be by pressure differences 
across smoke barriers. Maintenance of a tenable environment 
is not required in the smoke control zone of fire origin. 

\F] 909.6.1 Minimum pressure difference. The minimum 
pressure difference across a smoke barrier shall be 
0.05-inch water gage (0.0124 kPa) in fully sprinklered 
buildings. 

In buildings permitted to be other than fully sprinklered, 
the smoke control system shall be designed to achieve pres- 
sure differences at least two times the maximum calculated 
pressure difference produced by the design fire. 

\F] 909.6.2 Maximum pressure difference. The maxi- 
mum air pressure difference across a smoke barriershall be 
determined by required door-opening or closing forces. The 
actual force required to open exit doors when the system is 
in the smoke control mode shall be in accordance with Sec- 
tion 1008.1.2. Opening and closing forces for other doors 
shall be determined by standard engineering methods for 
the resolution of forces and reactions. The calculated force 
to set a side-hinged, swinging door in motion shall be deter- 
mined by: 



F=F dc + K(WAAP)/2(W-d) 



(Equation 9-1) 



where: 



A = Door area, square feet (m 2 ). 

d = Distance from door handle to latch edge of door, feet 
(m). 

F = Total door opening force, pounds (N). 

F dc = Force required to overcome closing device, pounds 

(N). 

K = Coefficient 5.2 (1.0). 

W = Door width, feet (m) . 

AP= Design pressure difference, inches of water (Pa). 

\F] 909.7 Airflow design method. When approvedby the fire 
code official, smoke migration through openings fixed in a per- 
manently open position, which are located between smoke 
control zones by the use of the airflow method, shall be permit- 
ted. The design airflow shall be in accordance with this section. 
Airflow shall be directed to limit smoke migration from the fire 
zone. The geometry of openings shall be considered to prevent 
flow reversal from turbulent effects . 

[F] 909.7.1 Velocity. The minimum average velocity 
through a fixed opening shall not be less than: 



v= 217.2 [h (T r - W(T r + 460)] 1/2 (Equation 9-2) 

For SI: v= 119.9 [h (T r To)IT}m 

where: 

h = Height of opening, feet (m). 

T r = Temperature of smoke, of (K). 

To = Temperature of ambient air, of (K). 

v = Air velocity, feet per minute (m/minute) . 

[F] 909.7.2 Prohibited conditions. This method shall not 
be employed where either the quantity of air or the velocity 
of the airflow will adversely affect other portions of the 
smoke control system, unduly intensify the fire, disrupt 
plume dynamics or interfere with exiting. In no case shall 
airflow toward the fire exceed 200 feet per minute (1.02 
m/s). Where the formula in Section 909 .7. 1 requires airflow 
to exceed this limit, the airflow method shall not be used. 

\F] 909.8 Exhaust method. When approvedby the fire code 
official, mechanical smoke control for large enclosed volumes, 
such as in atriums or malls, shall be permitted to utilize the 
exhaust method. Smoke control systems using the exhaust 
method shall be designed in accordance with NFPA 92B. 

[F] 909.8.1 Smoke layer. The height of the lowest horizon- 
tal surface of the smoke layer interface shall be maintained 
at least 6 feet (1829 mm) above any walking surface that 
forms a portion of a required egress system within the 
smoke zone. 

\F] 909.9 Design fire. The design fire shall be based on a ratio- 
nal analysis performed by the registered design professional 
and approvedby the fire code official. The design fire shall be 
based on the analysis in accordance with Section 909.4 and this 
section. 

[F] 909.9.1 Factors considered. The engineering analysis 
shall include the characteristics of the fuel, fuel load, effects 
included by the fire and whether the fire is likely to be steady 
or unsteady. 

[F] 909.9.2 Separation distance. Determination of the 
design fire shall include consideration of the type of fuel, 
fuel spacing and configuration. 

\F] 909.9.3 Heat-release assumptions. The analysis shall 
make use of best available data from approved sources and 
shall not be based on excessively stringent limitations of 
combustible material. 

[F] 909.9.4 Sprinkler effectiveness assumptions. A docu- 
mented engineering analysis shall be provided for condi- 
tions that assume fire growth is halted at the time of 
sprinkler activation. 

[F] 909.10 Equipment. Equipment including, but not limited 
to, fans, ducts, automatic dampers and balance dampers, shall 
be suitable for its intended use, suitable for the probable expo- 
sure temperatures that the rational analysis indicates and as 
approvedby the fire code official. 



206 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 909.10.1 Exhaust fans. Components of exhaust fans 
shall be rated and certified by the manufacturer for the prob- 
able temperature rise to which the components will be 
exposed. This temperature rise shall be computed by: 



T s =(Qjmc) + (T) 



(Equation 9-3) 



where: 



c = Specific heat of smoke at smoke layer temperature, 
Btu/lbof (kJ/kg . K). 

m = Exhaust rate, pounds per second (kg/s). 

Qc = Convective heat output of fire, Btu/s (kW). 

T a = Ambient temperature, of (K). 

T s = Smoke temperature, of (K). 

Exception: Reduced T 5 as calculated based on the assur- 
ance of adequate dilution air. 

[F] 909.10.2 Ducts. Duct materials andjoints shall be capa- 
ble of withstanding the probable temperatures and pressures 
to which they are exposed as determined in accordance with 
Section 909.10.1. Ducts shall be constructed and supported 
in accordance with the International Mechanical Code. 
Ducts shall be leak tested to 1.5 times the maximum design 
pressure in accordance with nationally accepted practices. 
Measured leakage shall not exceed 5 percent of design flow. 
Results of such testing shall be a part of the documentation 
procedure. Ducts shall be supported directly from fire-resis- 
tance-rated structural elements of the building by substan- 
tial, noncombustible supports. 

Exception: Flexible connections (for the purpose of 
vibration isolation) complying with the International 
Mechanical Code, that are constructed of approved 
fire-resistance-rated materials. 

[F] 909.10.3 Equipment, inlets and outlets. Equipment 
shall be located so as to not expose uninvolved portions of 
the building to an additional fire hazard. Outside air inlets 
shall be located so as to minimize the potential for introduc- 
ing smoke or flame into the building. Exhaust outlets shall 
be so located as to minimize reintroduction of smoke into 
the building and to limit exposure of the building or adjacent 
buildings to an additional fire hazard. 

[F] 909.10.4 Automatic dampers. Automatic dampers, 
regardless of the purpose for which they are installed within 
the smoke control system, shall be listed and conform to the 
requirements of approved, recognized standards. 

[F] 909.10.5 Fans. In addition to other requirements, 
belt-driven fans shall have 1.5 times the number of belts 
required for the design duty, with the minimum number of 
belts being two. Fans shall be selected for stable perfor- 
mance based on normal temperature and, where applicable, 
elevated temperature. Calculations and manufacturer's fan 
curves shall be part of the documentation procedures. Fans 
shall be supported and restrained by noncombustible 
devices in accordance with the requirements of Chapter 16. 
Motors driving fans shall not be operated beyond their 
nameplate horsepower (kilowatts), as determined from 
measurement of actual current draw, and shall have a mini- 
mum service factor of 1.15. 



[F] 909.11 Power systems. The smoke control system shall be 
supplied with two sources of power. Primary power shall be 
from the normal building power systems. Secondary power 
shall be from an approved standby source complying with 
Chapter 27 of this code. The standby power source and its 
transfer switches shall be in a room separate from the normal 
power transformers and switch gears and ventilated directly to 
and from the exterior. The room shall be enclosed with not less 
than I-hour fire barriers constructed in accordance with Sec- 
tion 707 or horizontal assemblies constructed in accordance 
with Section 712, or both. 

\F] 909.11.1 Power sources and power surges. Elements 
of the smoke management system relying on volatile mem- 
ories or the like shall be supplied with uninterruptable 
power sources of sufficient duration to span a IS -minute pri- 
mary power interruption. Elements of the smoke manage- 
ment system susceptible to power surges shall be suitably 
protected by conditioners, suppressors or other approved 
means. 

[F] 909.12 Detection and control systems. Fire detection sys- 
tems providing control input or output signals to mechanical 
smoke control systems or elements thereof shall comply with 
the requirements of Section 907. Such systems shall be 
equipped with a control unit complying with UL 864 and listed 
as smoke control equipment. 

Control systems for mechanical smoke control systems shall 
include provisions for verification. Verification shall include 
positive confirmation of actuation, testing, manual override, 
the presence of power downstream of all disconnects and, 
through a preprogrammed weekly test sequence, report abnor- 
mal conditions audibly, visually and by printed report. 

[F] 909.12.1 Wiring. In addition to meeting requirements 
ofNFPA 70, all wiring, regardless of voltage, shall be fully 
enclosed within continuous raceways. 

[F] 909.12.2 Activation. Smoke control systems shall be 
activated in accordance with this section. 

[F] 909.12.2.1 Pressurization, airflow or exhaust 
method. Mechanical smoke control systems using the 
pressurization, airflow or exhaust method shall have 
completely automatic control. 

[F] 909.12.2.2 Passive method. Passive smoke control 
systems actuated by approved spot- type detectors listed 
for releasing service shall be permitted. 

[F] 909.12.3 Automatic control. Where completely auto- 
matic control is required or used, the automatic-control 
sequences shall be initiated from an appropriately zoned 
automatic sprinkler system complying with Section 
903.3.1.1, manual controls that are readily accessible to the 
fire department and any smoke detectors required by engi- 
neering analysis. 

[F] 909.13 Control air tubing. Control air tubing shall be of 
sufficient size to meet the required response times. Tubing shall 
be flushed clean and dry prior to final connections and shall be 
adequately supported and protected from damage. Tubing 
passing through concrete or masonry shall be sleeved and pro- 
tected from abrasion and electrolytic action. 



2009 INTERNATIONAL BUILDING CODE® 



207 



FIRE PROTECTION SYSTEMS 



[F] 909.13.1 Materials. Control-air tubing shall be hard- 
drawn copper, Type L, ACR in accordance with ASTM B 
42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM B 251 
and ASTM B 280. Fittings shall be wrought copper or brass, 
solder type in accordance with ASME B 16.18 or ASME 
B 16.22. Changes in direction shall be made with appropri- 
ate tool bends. Brass compression-type fittings shall be used 
at final connection to devices; other joints shall be brazed 
using a BCuP5 brazing alloy with solidus above 1,100°F 
(593°C) and liquids below 1,500°F (816°C). Brazing flux 
shall be used on copper- to-brass joints only. 

Exception: Nonmetallic tubing used within control pan- 
els and at the final connection to devices provided all of 
the following conditions are met: 

1. Tubing shall be listedby an approved agency for 
flame and smoke characteristics. 

2. Tubing and connected devices shall be completely 
enclosed within a galvanized or paint-grade steel 
enclosure having a minimum thickness of 0.0296 
inch (0.7534 mm) (No. 22 gage). Entry to the 
enclosure shall be by copper tubing with a protec- 
tive grommet of neoprene or teflon or by suitable 
brass compression to male barbed adapter. 

3. Tubing shall be identified by appropriately docu- 
mented coding. 

4. Tubing shall be neatly tied and supported within 
the enclosure. Tubing bridging cabinets and doors 
or moveable devices shall be of sufficient length to 
avoid tension and excessive stress. Tubing shall be 
protected against abrasion. Tubing serving 
devices on doors shall be fastened along hinges. 

[F] 909.13.2 Isolation from other functions. Control tub- 
ing serving other than smoke control functions shall be iso- 
lated by automatic isolation valves or shall be an 
independent system. 

[F] 909.13.3 Testing. Control air tubing shall be tested at 
three times the operating pressure for not less than 30 min- 
utes without any noticeable loss in gauge pressure prior to 
final connection to devices. 

[F] 909.14 Marking and identification. The detection and 
control systems shall be clearly marked at all junctions, 
accesses and terminations. 

[F] 909.15 Control diagrams. Identical control diagrams 
showing all devices in the system and identifying their location 
and function shall be maintained current and kept on file with 
the fire code official, the fire department and in the fire com- 
mand center in a format and manner approvedby the fire chief. 

[F] 909.16 Fire-fighter's smoke control panel. A 
fire-fighter's smoke control panel for fire department emer- 
gency response purposes only shall be provided and shall 
include manual control or override of automatic control for 
mechanical smoke control systems. The panel shall be located 
in a fire command center complying with Section 911 in high- 
rise buildings or buildings with smoke-protected assembly 
seating. In all other buildings, the fire-fighter's smoke control 
panel shall be installed in an approved location adjacent to the 



fire alarm control panel. The fire-fighter's smoke control panel 
shall comply with Sections 909.16.1 through 909.16.3. 

[F] 909.16.1 Smoke control systems. Fans within the 
building shall be shown on the fire- fighter's control panel. A 
clear indication of the direction of airflow and the relation- 
ship of components shall be displayed. Status indicators 
shall be provided for all smoke control equipment, annunci- 
ated by fan and zone, and by pilot-lamp-type indicators as 
follows: 

1. Fans, dampers and other operating equipment in their 
normal status-WHITE. 

2. Fans, dampers and other operating equipment in their 
off or closed status-RED. 

3. Fans, dampers and other operating equipment in their 
on or open status-GREEN. 

4. Fans, dampers and other operating equipment in a 
fault status-YELLOW/ AMBER. 

[F] 909.16.2 Smoke control panel. The fire-fighter's con- 
trol panel shall provide control capability over the complete 
smoke-control system equipment within the building as fol- 
lows: 

1. ON-AUTO-OFF control over each individual piece 
of operating smoke control equipment that can also be 
controlled from other sources within the building. 
This includes stairway pressurization fans; smoke 
exhaust fans; supply, return and exhaust fans; eleva- 
tor shaft fans and other operating equipment used or 
intended for smoke control purposes. 

2. OPEN-AUTO-CLOSE control over individual 
dampers relating to smoke control and that are also 
controlled from other sources within the building. 

3. ON-OFF or OPEN-CLOSE control over smoke con- 
trol and other critical equipment associated with a fire 
or smoke emergency and that can only be controlled 
from the fire-fighter' s control panel. 

Exceptions: 

1. Complex systems, where approved, where the 
controls and indicators are combined to control 
and indicate all elements of a single smoke zone as 
a unit. 

2. Complex systems, where approved, where the 
control is accomplished by computer interface 
using approved, plain English commands. 

[F] 909.16.3 Control action and priorities. The fire- 
fighter's control panel actions shall be as follows: 

1. ON-OFF and OPEN-CLOSE control actions shall 
have the highest priority of any control point within 
the building. Once issued from the fire-fighter's con- 
trol panel, no automatic or manual control from any 
other control point within the building shall contra- 
diet the control action. Where automatic means are 
provided to interrupt normal, nonemergency equip- 
ment operation or produce a specific result to safe- 
guard the building or equipment (Le., duct freezestats, 
duct smoke detectors, high-temperature cutouts, tem- 



208 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



perature- actuated linkage and similar devices), such 
means shall be capable of being overridden by the 
fire- fighter's control panel. The last control action as 
indicated by each fire-fighter' s control panel switch 
position shall prevail. In no case shall control actions 
require the smoke control system to assume more 
than one configuration at anyone time. 

Exception: Power disconnects required by NFPA 
70. 

2. Only the AUTO position of each three-position 
fire- fighter's control panel switch shall allow auto- 
matic or manual control action from other control 
points within the building. The AUTO position shall 
be the NORMAL, nonemergency, building control 
position. Where a fire- fighter's control panel is in the 
AUTO position, the actual status of the device (on, 
off, open, closed) shall continue to be indicated by the 
status indicator described above. When directed by an 
automatic signal to assume an emergency condition, 
the NORMAL position shall become the emergency 
condition for that device or group of devices within 
the zone. In no case shall control actions require the 
smoke control system to assume more than one con- 
figuration at anyone time. 

[F] 909.17 System response time. Smoke-control system acti- 
vation shall be initiated immediately after receipt of an appro- 
priate automatic or manual activation command. Smoke 
control systems shall activate individual components (such as 
dampers and fans) in the sequence necessary to prevent physi- 
cal damage to the fans, dampers, ducts and other equipment. 
For purposes of smoke control, the fire-fighter's control panel 
response time shall be the same for automatic or manual smoke 
control action initiated from any other building control point. 
The total response time, including that necessary for detection, 
shutdown of operating equipment and smoke control system 
startup, shall allow for full operational mode to be achieved 
before the conditions in the space exceed the design smoke 
condition. The system response time for each component and 
their sequential relationships shall be detailed in the required 
rational analysis and verification of their installed condition 
reported in the required final report. 

[F] 909.18 Acceptance testing. Devices, equipment, compo- 
nents and sequences shall be individually tested. These tests, in 
addition to those required by other provisions of this code, shall 
consist of determination of function, sequence and, where 
applicable, capacity of their installed condition. 

[F] 909.18.1 Detection devices. Smoke or fire detectors 
that are a part of a smoke control system shall be tested in 
accordance with Chapter 9 in their installed condition. 
When applicable, this testing shall include verification of 
airflow in both minimum and maximum conditions. 

[F] 909.18.2 Ducts. Ducts that are part of a smoke control 
system shall be traversed using generally accepted practices 
to determine actual air quantities. 

[F] 909.18.3 Dampers. Dampers shall be tested for func- 
tion in their installed condition. 



[F] 909.18.4 Inlets and outlets. Inlets and outlets shall be 
read using generally accepted practices to determine air 
quantities. 

[F] 909.18.5 Fans. Fans shall be examined for correct rota- 
tion. Measurements of voltage, amperage, revolutions per 
minute (rpm) and belt tension shall be made. 

[F] 909.18.6 Smoke barriers. Measurements using 
inclined manometers or other approved calibrated measur- 
ing devices shall be made of the pressure differences across 
smoke barriers. Such measurements shall be conducted for 
each possible smoke control condition. 

[F] 909.18.7 Controls. Each smoke zone equipped with an 
automatic- initiation device shall be put into operation by the 
actuation of one such device. Each additional device within 
the zone shall be verified to cause the same sequence with- 
out requiring the operation of fan motors in order to prevent 
damage. Control sequences shall be verified throughout the 
system, including verification of override from the 
fire- fighter's control panel and simulation of standby power 
conditions. 

[F] 909.18.8 Special inspections for smoke control. 

Smoke control systems shall be tested by a special inspector. 

[F] 909.18.8.1 Scope of testing. Special inspections 
shall be conducted in accordance with the following: 

1. During erection of ductwork and prior to conceal- 
ment for the purposes of leakage testing and 
recording of device location. 

2. Prior to occupancy and after sufficient completion 
for the purposes of pressure-difference testing, 
flow measurements, and detection and control ver- 
ification. 

[F] 909.18.8.2 Qualifications. Special inspection agen- 
cies for smoke control shall have expertise in fire protec- 
tion engineering, mechanical engineering and 
certification as air balancers. 

[F] 909.18.8.3 Reports. A complete report of testing 
shall be prepared by the special inspector or special 
inspection agency. The report shall include identification 
of all devices by manufacturer, nameplate data, design 
values, measured values and identification tag or mark. 
The report shall be reviewed by the responsible regis- 
tered design professional and, when satisfied that the 
design intent has been achieved, the responsible regis- 
tered design professional shall seal, sign and date the 
report. 

[F] 909.18.8.3.1 Report filing. A copy of the final 
report shall be filed with the fire code official and an 
identical copy shall be maintained in an approved 
location at the building. 

[F] 909.18.9 Identification and documentation. Charts, 
drawings and other documents identifying and locating 
each component of the smoke control system, and describ- 
ing its proper function and maintenance requirements, shall 
be maintained on file at the building as an attachment to the 



2009 INTERNATIONAL BUILDING CODE® 



209 



FIRE PROTECTION SYSTEMS 



report required by Section 909.18.8.3. Devices shall have an 
approved identifying tag or mark on them consistent with 
the other required documentation and shall be dated indicat- 
ing the last time they were successfully tested and by whom. 

[F] 909.19 System acceptance. Buildings, or portions thereof, 
required by this code to comply with this section shall not be 
issued a certificate of occupancy until such time that the fire 
code official determines that the provisions of this section have 
been fully complied with and that the fire department has 
received satisfactory instruction on the operation, both auto- 
matic and manual, of the system. 

Exception: In buildings of phased construction, a tempo- 
rary certificate of occupancy, as approvedby the fire code 
official, shall be allowed provided that those portions of the 
building to be occupied meet the requirements of this sec- 
tion and that the remainder does not pose a significant haz- 
ard to the safety of the proposed occupants or adjacent 
buildings. 

909.20 Smokeproof enclosures. Where required by Section 
1022.9, a smokeproof enclosure shall be constructed in accor- 
dance with this section. A smokeproof enclosure shall consist 
of an enclosed interior exit stairway that conforms to Section 
1022.1 and an open exterior balcony or ventilated vestibule 
meeting the requirements of this section. Where access to the 
roof is required by the International Fire Code, such access 
shall be from the smokeproof enclosure where a smokeproof 
enclosure is required. 

909.20.1 Access. Access to the stair shall be by way of a 
vestibule or an open exterior balcony. The minimum dimen- 
sion of the vestibule shall not be less than the required width 
of the corridor leading to the vestibule but shall not have a 
width of less than 44 inches (1118 mm) and shall not have a 
length of less than 72 inches (1829 mm) in the direction of 
egress travel. 

909.20.2 Construction. The smokeproof enclosure shall be 
separated from the remainder of the building by not less 
than 2-hour fire barriers constructed in accordance with 
Section 707 or horizontal assemblies constructed in accor- 
dance with Section 712, or both. Openings are not permitted 
other than the required means of egress doors. The vestibule 
shall be separated from the stairwayby not less than 2-hour 
fire barriers constructed in accordance with Section 707 or 
horizontal assemblies constructed in accordance with Sec- 
tion 712, or both. The open exterior balcony shall be con- 
structed in accordance with the fire -resistance rating re- 
quirements for floor assemblies. 

909.20.2.1 Door closers. Doors in a smokeproof enclo- 
sure shall be self- or automatic closing by actuation of a 
smoke detector in accordance with Section 715.4 and 
shall be installed at the floor- side entrance to the 
smokeproof enclosure. The actuation of the smoke 
detector on any door shall activate the closing devices on 
all doors in the smokeproof enclosure at all levels. 
Smoke detectors shall be installed in accordance with 
Section 907.3. 



909.20.3 Natural ventilation alternative. The provisions 
of Sections 909.20.3.1 through 909.20.3.3 shall apply to 
ventilation of smokeproof enclosures by natural means. 

909.20.3.1 Balcony doors. Where access to the stairway 
is by way of an open exterior balcony, the door assembly 
into the enclosure shall be afire door assembly in accor- 
dance with Section 715.4. 

909.20.3.2 Vestibule doors. Where access to the stair- 
way is by way of a vestibule, the door assembly into the 
vestibule shall be a fire door assembly complying with 
Section 715.4. The door assembly from the vestibule to 
the stairway shall have not less than a 20-minutz fire pro- 
tection rating complying with Section 715.4. 

909.20.3.3 Vestibule ventilation. Each vestibule shall 
have a minimum net area of 16 square feet (1.5 m 2 ) of 
opening in a wall facing an outer court, yard or public 
way that is at least 20 feet (6096 mm) in width. 

909.20.4 Mechanical ventilation alternative. The provi- 
sions of Sections 909.20.4.1 through 909.20.4.4 shall apply 
to ventilation of smokeproof enclosures by mechanical 
means. 

909.20.4.1 Vestibule doors. The door assembly from the 
building into the vestibule shall be a fire door assembly 
complying with Section 715.4.3. The door assembly 
from the vestibule to the stairway shall not have less than 
a 20-minute fire protection rating and meet the require- 
ments for a smoke door assembly in accordance with 
Section 715.4.3. The door shall be installed in accor- 
dance with NFPA 105. 

909.20.4.2 Vestibule ventilation. The vestibule shall be 
supplied with not less than one air change per minute and 
the exhaust shall not be less than 150 percent of supply. 
Supply air shall enter and exhaust air shall discharge 
from the vestibule through separate, tightly constructed 
ducts used only for that purpose. Supply air shall enter 
the vestibule within 6 inches (152 mm) of the floor level. 
The top of the exhaust register shall be located at the top 
of the smoke trap but not more than 6 inches (152 mm) 
down from the top of the trap, and shall be entirely within 
the smoke trap area. Doors in the open position shall not 
obstruct duct openings. Duct openings with controlling 
dampers are permitted where necessary to meet the 
design requirements, but dampers are not otherwise 
required. 

909.20.4.2.1 Engineered ventilation system. Where 
a specially engineered system is used, the system 
shall exhaust a quantity of air equal to not less than 90 
air changes per hour from any vestibule in the emer- 
gency operation mode and shall be sized to handle 
three vestibules simultaneously. Smoke detectors 
shall be located at the floor- side entrance to each ves- 
tibule and shall activate the system for the affected 
vestibule. Smoke detectors shall be installed in accor- 
dance with Section 907.3. 

909.20.4.3 Smoke trap. The vestibule ceiling shall be at 
least 20 inches (508 mm) higher than the door opening 



210 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



into the vestibule to serve as a smoke and heat trap and to 
provide an upward-moving air column. The height shall 
not be decreased unless approved and justified by design 
and test. 

909.20.4.4 Stair shaft air movement system. The stair 
shaft shall be provided with a dampered relief opening 
and supplied with sufficient air to maintain a minimum 
positive pressure of 0. 10 inch of water (25 Pa) in the shaft 
relative to the vestibule with all doors closed. 

909.20.5 Stair pressurization alternative. Where the 
building is equipped throughout with an automatic sprin- 
kler systemin accordance with Section 903.3.1.1 , the vesti- 
bule is not required, provided that interior exit stairways are 
pressurized to a minimum of 0.10 inches of water (25 Pa) 
and a maximum of 0.35 inches of water (87 Pa) in the shaft 
relative to the building measured with all stairway doors 
closed under maximum anticipated conditions of stack 
effect and wind effect. 

909.20.6 Ventilating equipment. The activation of venti- 
lating equipment required by the alternatives in Sections 
909.20.4 and 909.20.5 shall be by smoke detectors installed 
at each floor level at an approv edlocation at the entrance to 
the smokeproof enclosure. When the closing device for the 
stair shaft and vestibule doors is activated by smoke detec- 
tion or power failure, the mechanical equipment shall acti- 
vate and operate at the required performance levels. Smoke 
detectors shall be installed in accordance with Section 
907.3. 

909.20.6.1 Ventilation systems. Smokeproof enclosure 
ventilation systems shall be independent of other build- 
ing ventilation systems. The equipment, control wiring, 
power wiring and ductwork shall comply with one of the 
following: 

1. Equipment, control wiring, power wiring and 
ductwork shall be located exterior to the building 
and directly connected to the smokeproof enclo- 
sure or connected to the smokeproof enclosure by 
ductwork enclosed by not less than 2-hour fire 
barriers constructed in accordance with Section 
707 or horizontal assemblies constructed in accor- 
dance with Section 712, or both. 

2. Equipment, control wiring, power wiring and 
ductwork shall be located within the smokeproof 
enclosure with intake or exhaust directly from and 
to the outside or through ductwork enclosed by not 
less than 2-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies 
constructed in accordance with Section 712, or 
both. 

3. Equipment, control wiring, power wiring and 
ductwork shall be located within the building if 
separated from the remainder of the building, 
including other mechanical equipment, by not less 
than 2-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies 



constructed in accordance with Section 712, or 
both. 

Exceptions: 

1. Control wiring and power wiring utilizing a 
2-hour rated cable or cable system. 

2. Where encased with not less than 2 inches (51 
mm) of concrete. 

909.20.6.2 Standby power. Mechanical vestibule and 
stair shaft ventilation systems and automatic fire detec- 
tion systems shall be powered by an approved standby 
power system conforming to Section 403.4.7 and Chap- 
ter 27. 

909.20.6.3 Acceptance and testing. Before the mechan- 
ical equipment is approved, the system shall be tested in 
the presence of the building official to confirm that the 
system is operating in compliance with these require- 
ments. 



SECTION 910 
SMOKE AND HEAT VENTS 

[F] 910.1 General. Where required by this code or otherwise 
installed, smoke and heat vents, or mechanical smoke exhaust 
systems, and draft curtains shall conform to the requirements 
of this section. 

Exceptions: 

1. Frozen food warehouses used solely for storage of 
Class I and II commodities where protected by an 
approved automatic sprinkler system. 

2. Where areas of buildings are equipped with early sup- 
pression fast -response (ESFR) sprinklers, automatic 
smoke and heat vents shall not be required within 
these areas. 

[F] 910.2 Where required. Smoke and heat vents shall be 
installed in the roofs of one-story buildings or portions thereof 
occupied for the uses set forth in Sections 910.2.1 and 910.2.2. 

[F] 910.2.1 Group F-l or S-I. Buildings and portions 
thereof used as a Group F-lor S-l occupancy having more 
than 50,000 square feet (4645 m 2 ) in undivided area. 

Exception: Group S-l aircraft repair hangars. 

[F] 910.2.2 High-piled combustible storage. Buildings 
and portions thereof containing high-piled combustible 
stock or rack storage in any occupancy group in accordance 

with Section 413 and the International Fire Code. 

i 

[F] 910.3 Design and installation. The design and installation 
of smoke and heat vents and draft curtains shall be as specified 
in Sections 910.3.1 through 910.3.5.2 and Table 910.3. 

[F] 910.3.1 Design. Smoke and heat vents shall be listedand 
labeled to indicate compliance with UL 793 . 

[F] 910.3.2 Vent operation. Smoke and heat vents shall be 
capable of being operated by approved automatic and man- 
ual means. Automatic operation of smoke and heat vents 



2009 INTERNATIONAL BUILDING CODE® 



211 



FIRE PROTECTION SYSTEMS 



shall conform to the provisions of Sections 910.3.2.1 
through 910.3.2.3. 

\F] 910.3.2.1 Gravity-operated drop-out vents. Auto- 
matic smoke and heat vents containing heat- sensitive 
glazing designed to shrink and drop out of the vent open- 
ing when exposed to fire shall fully open within 5 min- 
utes after the vent cavity is exposed to a simulated fire, 
represented by a time-temperature gradient that reaches 
an air temperature of 500°F (260°C) within 5 minutes. 

[F] 910.3.2.2 Sprinklered buildings. Where installed in 
buildings provided with an approved automatic sprin- 
kler system, smoke and heat vents shall be designed to 
operate automatically. 

[F] 910.3.2.3 Nonsprinklered buildings. Where 
installed in buildings not provided with an approved 
automatic sprinkler system, smoke and heat vents shall 
operate automatically by actuation of a heat-responsive 
device rated at between 100°F (38°C) and 220°F 
(104°C) above ambient. 

Exception: Gravity-operated drop-out vents comply- 
ing with Section 910.3.2.1. 

[F] 910.3.3 Vent dimensions. The effective venting area 
shall not be less than 16 square feet (1.5 m 2 ) with no dimen- 



sion less than 4 feet (1219 mm), excluding ribs or gutters 
having a total width not exceeding 6 inches (152 mm). 

[F] 910.3.4 Vent locations. Smoke and heat vents shall be 
located 20 feet (6096 mm) or more from adjacent lot lines 
and fire walls and 10 feet (3048 mm) or more from fire bar- 
riers. Vents shall be uniformly located within the roof in the 
areas of the building where the vents are required to be 
installed by Section 910.2 with consideration given to roof 
pitch, draft curtain location, sprinkler location and struc- 
tural members. 

[F] 910.3.5 Draft curtains. Where required by Table 910.3, 
draft curtains shall be installed on the underside of the roof 
in accordance with this section. 

Exception: Where areas of buildings are equipped with 
ESFR sprinklers, draft curtains shall not be provided 
within these areas. Draft curtains shall only be provided 
at the separation between the ESFR sprinklers and the 
non-ESFR sprinklers. 

[F] 910.3.5.1 Construction. Draft curtains shall be con- 
structed of sheet metal, lath and plaster, gypsum board or 
other approve d materials which provide equivalent per- 
formance to resist the passage of smoke. Joints and con- 
nections shall be smoke tight. 



[F] TABLE 910.3 
REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTS 3 



OCCUPANCY GROUP AND 

COMMODITY 

CLASSIFICATION 


DESIGNATED 
STORAGE HEIGHT 

(feet) 


MINIMUM DRAFT 
CURTAIN DEPTH 

(feet) 


MAXIMUM AREA 

FORMED BY DRAFT 

CURTAINS 

(square feet) 


VENT-AREA- 
TO-FLOOR-AREA 
RATIO c 


MAXIMUM 

SPACING OF 

VENT CENTERS 

(feet) 


MAXIMUM 

DISTANCE FROM 

VENTS TO WAN 

OR DRAFT 

CURTAIN b 

(feet) 


Group F-l and S-l 




0.2 x Hd 
but>4 


50,000 


1:100 


120 


60 


High-piled Storage 

(see Section 910.2.2) 

Class I-IV commodities 

(Option 1) 


<20 


6 


10,000 


1:100 


100 


60 


> 20 < 40 


6 


8,000 


1:75 


100 


55 


High-piled Storage 

(see Section 910.2.2) 

Class I-IV commodities 

(Option 2) 


<20 


4 


3,000 


1:75 


100 


55 


> 20 < 40 


4 


3,000 


1:50 


100 


50 


High-piled Storage 

(see Section 910.2.2) 

High- hazard commodities 

(Option 1) 


<20 


6 


6,000 


1:50 


100 


50 


> 20 < 30 


6 


6,000 


1:40 


90 


45 


High-piled Storage 

(see Section 910.2.2) 

High- hazard commodities 

(Option 2) 


<20 


4 


4,000 


1:50 


100 


50 


> 20 < 30 


4 


2,000 


1:30 


75 


40 



For 51 : 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 - 

a. Additional requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23. For solid-piled storage heights in excess of 
those indicated, an approved engineered design shall be used. 

b. Vents adjacent to walls or draft curtains shall be located within a horizontal distance not greater than the maximum distance specified in this column as measured 
perpendicular to the wall or draft curtain that forms the perimeter of the draft curtained area. 

c. Where draft curtains are not required, the vent area to floor area ratio shall be calculated based on a minimum draft curtain depth of 6 feet (Option 1). 

d. "H" is the height of the vent, in feet, above the floor. 



212 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



[F] 910.3.5.2 Location and depth. The location and 
minimum depth of draft curtains shall be in accordance 
with Table 910.3. 

[F] 910.4 Mechanical smoke exhaust. Where approvedby the 
fire code official, engineered mechanical smoke exhaust shall 
be an acceptable alternate to smoke and heat vents. 

[F] 910.4.1 Location. Exhaust fans shall be uniformly 
spaced within each draft-curtained area and the maximum 
distance between fans shall not be greater than 100 feet (30 
480 mm). 

[F] 910.4.2 Size. Fans shall have a maximum individual 
capacity of 30,000 cfm (14.2 m 3 /s). The aggregate capacity 
of smoke exhaust fans shall be determined by the equation: 



C=Ax 300 



where: 



(Equation 9-4) 



C = Capacity of mechanical ventilation required, in cubic 
feet per minute (m 3 /s). 

A = Area of roof vents provided in square feet (m 2 ) in 
accordance with Table 910.3. 

[F] 910.4.3 Operation. Mechanical smoke exhaust fans 
shall be automatically activated by the automatic sprinkler 
system or by heat detectors having operating characteris- 
tics equivalent to those described in Section 910.3.2. Indi- 
vidual manual controls of each fan unit shall also be 
provided. 

[F] 910.4.4 Wiring and control. Wiring for operation and 
control of smoke exhaust fans shall be connected ahead of 
the main disconnect and protected against exposure to tem- 
peratures in excess of 1,000°F (538°C) for a period of not 
less than 15 minutes. Controls shall be located so as to be 
immediately accessible to the fire service from the exterior 
of the building and protected against interior fire exposure 
by not less than I-hour fire barriers constructed in accor- 
dance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. 

[F] 910.4.5 Supply air. Supply air for exhaust fans shall be 
provided at or near the floor level and shall be sized to pro- 
vide a minimum of 50 percent of required exhaust. Open- 
ings for supply air shall be uniformly distributed around the 
periphery of the area served. 

[F] 910.4.6 Interlocks. In combination comfort air-han- 
dling/smoke removal systems or independent comfort 
air-handling systems, fans shall be controlled to shut down 
in accordance with the approved smoke control sequence. 



SECTION 911 
FIRE COMMAND CENTER 

[F] 911.1 General. Where required by other sections of this 
code and in all buildings classified as high-rise buildings by 
this code, a fire command center for fire department operations 
shall be provided and shall comply with Sections 911.1.1 
through 911.1.5. 



[F] 911.1.1 Location and access. The location and accessi- 
bility of the fire command center shall be approvedby the 
fire chief. 

[F] 911.1.2 Separation. The fire command center shall be 
separated from the remainder of the building by not less 
than a I-hour fire barrier constructed in accordance with 
Section 707 or horizontal assembly constructed in accor- 
dance with Section 712, or both. 

[F] 911.1.3 Size. The room shall be a minimum of 200 
square feet (19 m 2 ) with a minimum dimension of 10 feet 
(3048 mm). 

[F] 911.1.4 Layout approval. A layout of the fire command 
center and all features required by this section to be con- 
tained therein shall be submitted for approval prior to instal- 
lation . 

[F] 911.1.5 Required features. The fire command center 
shall comply with NFPA 72 and shall contain the following 
features: 

1. The emergency voice/alarm communication system 
control unit. 

2. The fire department communications system. 

3. Fire detection and alarm system annunciator. 

4. Annunciator unit visually indicating the location of I 
the elevators and whether they are operational. 

5. Status indicators and controls for air distribution 
systems. 

6. The fire-fighter' s control panel required by Section 
909.16 for smoke control systems installed in the 
building. 

7. Controls for unlocking stairway doors simulta- 
neously. 

8. Sprinkler valve and waterflow detector display pan- 
els. 

9. Emergency and standby power status indicators. 

10. A telephone for fire department use with controlled 
access to the public telephone system. 

11. Fire pump status indicators. 

12. Schematic building plans indicating the typical 
floor plan and detailing the building core, means of 
egress, fire protection systems, fire-fighting equip- 
ment and fire department access and the location of 
fire walls, fire barriers, fire partitions, smoke barri- 
ers and smoke partitions. 

13. Work table. 

14. Generator supervision devices, manual start and 
transfer features. 

15. Public address system, where specifically required 
by other sections of this code. 

16. Elevator fire recall switch in accordance with 
ASME A17.1. 



2009 INTERNATIONAL BUILDING CODE® 



213 



FIRE PROTECTION SYSTEMS 



17. Elevator emergency or standby power selector 
s witch (es), where emergency or standby power is 
provided. 



SECTION 912 
FIRE DEPARTMENT CONNECTIONS 

[F] 912.1 Installation. Fire department connections shall be 
installed in accordance with the NFPA standard applicable to 
the system design and shall comply with Sections 912.2 
through 912.5. 

[F] 912.2 Location. With respect to hydrants, driveways, 
buildings and landscaping, fire department connections shall 
be so located that fire apparatus and hose connected to supply 
the system will not obstruct access to the buildings for other fire 
apparatus. The location of fire department connections shall be 
approvedby the fire chief. 

[F] 912.2.1 Visible location. Fire department connections 
shall be located on the street side of buildings, fully visible 
and recognizable from the street or nearest point of fire 
department vehicle access or as otherwise approvedby the 
fire chief. 

[F] 912.2.2 Existing buildings. On existing buildings, 
wherever the fire department connection is not visible to 
approaching fire apparatus, the fire department connection 
shall be indicated by an approvedsign mounted on the street 
front or on the side of the building. Such sign shall have the 
letters "FDC" at least 6 inches (152 mm) high and words in 
letters at least 2 inches (51 mm) high or an arrow to indicate 
the location. All such signs shall be subject to the approval 
of the fire code official. 

[F] 912.3 Access. Immediate access to fire department connec- 
tions shall be maintained at all times and without obstruction 
by fences, bushes, trees, walls or any other fixed or moveable 
object. Access to fire department connections shall be 
approvedby the fire chief. 

Exception: Fences, where provided with an access gate 
equipped with a sign complying with the legend require- 
ments of Section 912.4 and a means of emergency opera- 
tion. The gate and the means of emergency operation shall 
be approvedby the fire chief and maintained operational at 
all times . 

[F] 912.3.1 Locking fire department connection caps. 
The fire code official is authorized to require locking caps 
on fire department connections for water-based fire protec- 
tion systems where the responding fire department carries 
appropriate key wrenches for removal. 

[F] 912.3.2 Clear space around connections. A working 
space of not less than 36 inches (762 mm) in width, 36 
inches (914 mm) in depth and 78 inches (1981 mm) in 
height shall be provided and maintained in front of and to 
the sides of wall- mounted fire department connections and 
around the circumference of free-standing fire department 
connections, except as otherwise required or approvedby 
the fire chief. 

[F] 912.3.3 Physical protection. Where fire department 
connections are subject to impact by a motor vehicle, vehi- 



cle impact protection shall be provided in accordance with 
Section 312 of the International Fire Code. 

\F] 912.4 Signs. A metal sign with raised letters at least 1 inch 
(25 mm) in size shall be mounted on all fire department con- 
nections serving automatic sprinklers, standpipes or fire pump 
connections. Such signs shall read: AUTOMATIC SPRIN- 
KLERS or STANDPIPES or TEST CONNECTION or a com- 
bination thereof as applicable. Where the fire department 
connection does not serve the entire building, a sign shall be 
provided indicating the portions of the building served. 

[P] 912.5 Backflow protection. The potable water supply to 
automatic sprinkler and standpipe systems shall be protected 
against backflow as required by the International Plumbing 
Code. 



SECTION 913 
FIRE PUMPS 

[F] 913.1 General. Where provided, fire pumps shall be 
installed in accordance with this section and NFPA 20. 

[F] 913.2 Protection against interruption of service. The fire 
pump, driver and controller shall be protected in accordance 
with NFPA 20 against possible interruption of service through 
damage caused by explosion, fire, flood, earthquake, rodents, 
insects, windstorm, freezing, vandalism and other adverse con- 
ditions . 

913.2.1 Protection of fire pump rooms. Fire pumps shall 
be located in rooms that are separated from all other areas of 
the building by 2-hour fire barriers constructed in accor- 
dance with Section 707 or 2-hour horizontal assemblies 
constructed in accordance with Section 712, or both. 

Exceptions: 

1. In other than high-rise buildings, separation by 
1-hour fire barriers constructed in accordance 
with Section 707 or I-hour horizontal assemblies 
constructed in accordance with Section 712, or 
both, shall be permitted in buildings equipped 
throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1 or 903.3.1.2. 

2. Separation is not required for fire pumps physi- 
cally separated in accordance with NFPA 20. 

[F] 913.3 Temperature of pump room. Suitable means shall 
be provided for maintaining the temperature of a pump room or 
pump house, where required, above 40°F (SOC) . 

[F] 913.3.1 Engine manufacturer's recommendation. 
Temperature of the pump room, pump house or area where 
engines are installed shall never be less than the minimum 
recommended by the engine manufacturer. The engine 
manufacturer's recommendations for oil heaters shall be 
followed. 

[F] 913.4 Valve supervision. Where provided, the fire pump 
suction, discharge and bypass valves, and isolation valves on 
the backflow prevention device or assembly shall be super- 
vised open by one of the following methods: 

1. Central- station, proprietary or remote- station signaling 
service. 



214 



2009 INTERNATIONAL BUILDING CODE® 



FIRE PROTECTION SYSTEMS 



2. Local signaling service that will cause the sounding of an 
audible signal at a constantly attended location. 

3. Locking valves open. 

4. Sealing of valves and approvedweekly recorded inspec- 
tion where valves are located within fenced enclosures 
under the control of the owner. 

\F] 913.4.1 Test outlet valve supervision. Fire pump test 
outlet valves shall be supervised in the closed position. 

[F] 913.5 Acceptance test. Acceptance testing shall be done in 
accordance with the requirements of NFPA 20. 



SECTION 914 
EMERGENCY RESPONDER SAFETY FEATURES 

[F] 914.1 Shaft way markings. Vertical shafts shall be identi- 
fied as required by Sections 914.1.1 and 914.1.2. 

[F] 914.1.1 Exterior access to shaftways. Outside open- 
ings accessible to the fire department and that open directly 
on a hoistway or shaftway communicating between two or 
more floors in a building shall be plainly marked with the 
word "SHAFTWAY" in red letters at least 6 inches (152 
mm) high on a white background. Such warning signs shall 
be placed so as to be readily discernible from the outside of 
the building. 

[F] 914.1.2 Interior access to shaftways. Door or window 
openings to a hoistway or shaftway from the interior of the 
building shall be plainly marked with the word 
"SHAFTWAY" in red letters at least 6 inches (152 mm) high 
on a white background. Such warning signs shall be placed 
so as to be readily discernible. 

Exception: Markings shall not be required on shaftway 
openings that are readily discernible as openings onto a 
shaftway by the construction or arrangement. 

[F] 914.2 Equipment room identification. Fire protection 
equipment shall be identified in an approved manner. Rooms 
containing controls for air-conditioning systems, sprinkler ris- 
ers and valves or other fire detection, suppression or control 
elements shall be identified for the use of the fire department. 
Approved signs required to identify fire protection equipment 
and equipment location shall be constructed of durable materi- 
als, permanently installed and readily visible. 



SECTION 915 
EMERGENCY RESPONDER RADIO COVERAGE 

[F] 915.1 General. Emergency responder radio coverage shall 
be provided in all new buildings in accordance with Section 
510 of the International Fire Code. 



2009 INTERNATIONAL BUILDING CODE® 215 



216 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 10 
MEANS OF EGRESS 



SECTION 1001 
ADMINISTRATION 

1001.1 General. Buildings or portions thereof shall be pro- 
vided with a means of egress system as required by this chapter. 
The provisions of this chapter shall control the design, con- 
struction and arrangement of means of egress components 
required to provide an approved means of egress from struc- 
tures and portions thereof. 

1001.2 Minimum requirements. It shall be unlawful to alter a 
building or structure in a manner that will reduce the number of 
exits or the capacity of the means of egress to less than required 
by this code. 

[F] 1001.3 Maintenance. Means of egress shall be maintained 
in accordance with the International Fire Code. 



SECTION 1002 
DEFINITIONS 

1002.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

ACCESSIBLE MEANS OF EGRESS. A continuous and 
unobstructed way of egress travel from any accessible point in 
a building or facility to & public way 

AISLE. An unenclosed exit access component that defines and 
provides a path of egress travel. 

AISLE ACCESSWAY. That portion of an exit access that 
leads to an aisle. 

ALTERNATING TREAD DEVICE. A device that has a 
series of steps between 50 and 70 degrees (0.87 and 1.22 rad) 
from horizontal, usually attached to a center support rail in an 
alternating manner so that the user does not have both feet on 
the same level at the same time. 

AREA OF REFUGE. An area where persons unable to use 
stairways can remain temporarily to await instructions or assis- 
tance during emergency evacuation. 

BLEACHERS. Tiered seating supported on a dedicated struc- 
tural system and two or more rows high and is not a building 
element (see" Grandstands"). 

COMMON PATH OF EGRESS TRAVEL. That portion of 
exit access which the occupants are required to traverse before 
two separate and distinct paths of egress travel to two exits are 
available. Paths that merge are common paths of travel. Com- 
mon paths of egress travel shall be included within the permit- 
ted travel distance. 

CORRIDOR. An enclosed exit access component that defines 
and provides a path of egress travel to an exit. 



DOOR, BALANCED. A door equipped with double-pivoted 
hardware so designed as to cause a semicounter balanced 
swing action when opening. 

EGRESS COURT. A court oryardwhich provides access to a 
public way for one or more exits. 

EMERGENCY ESCAPE AND RESCUE OPENING. An 

operable window, door or other similar device that provides for 
a means of escape and access for rescue in the event of an emer- 
gency. 

EXIT. That portion of a means of egress system which is sepa- 
rated from other interior spaces of a building or structure by 
fire-resistance-rated construction and opening protectives as 
required to provide a protected path of egress travel between 
the exit access and the exit discharge. Exits include exterior exit 
doors at the level of exit discharge, vertical exit enclosures, exit 
passageways, exterior exit stairways, exterior exit ramps and 
horizontal exits. 

EXIT ACCESS. That portion of a means of egress system that 
leads from any occupied portion of a building or structure to an 
exit. 

EXIT ACCESS DOORWAY. A door or access point along the 
path of egress travel from an occupied room, area or space 
where the path of egress enters an intervening room, corridor, 
unenclosed exit access stair or unenclosed exit access ramp. 

EXIT DISCHARGE. That portion of a means of egress sys- 
tem between the termination of an exit and & public way 

EXIT DISCHARGE, LEVEL OF. The story at the point at 
which an exit terminates and an exit discharge begins. 

EXIT ENCLOSURE. An exit component that is separated 
from other interior spaces of a building or structure by 
fire-resistance-rated construction and opening protectives, and 
provides for a protected path of egress travel in a vertical or hor- 
izontal direction to the exit discharge or the public way 

EXIT, HORIZONTAL. A path of egress travel from one 
building to an area in another building on approximately the 
same level, or a path of egress travel through or around a wall or 
partition to an area on approximately the same level in the same 
building, which affords safety from fire and smoke from the 
area of incidence and areas communicating therewith. 

EXIT PASSAGEWAY. An exit component that is separated 
from other interior spaces of a building or structure by 
fire-resistance-rated construction and opening protectives, and 
provides for a protected path of egress travel in a horizontal 
direction to the exit discharge or the public way 

FIRE EXIT HARDWARE. Panic hardware that is listed for 
use on fire door assemblies. 

FLIGHT. A continuous run of rectangular treads, winders or 
combination thereof from one landing to another. 



2009 INTERNATIONAL BUILDING CODE® 



217 



MEANS OF EGRESS 



FLOOR AREA, GROSS. The floor area within the inside per- 
imeter of the exterior walls of the building under consideration, 
exclusive of vent shafts and courts, without deduction for corri- 
dors' stairways, closets, the thickness of interior walls, col- 
umns or other features. The floor area of a building, or portion 
thereof, not provided with surrounding exterior walls shall be 
the usable area under the horizontal projection of the roof or 
floor above. The gross floor area shall not include shafts with 
no openings or interior courts. 

FLOOR AREA, NET. The actual occupied area not including 
unoccupied accessory areas such as corridors, stairways, toilet 
rooms, mechanical rooms and closets. 

FOLDING AND TELESCOPIC SEATING. Tiered seating 
having an overall shape and size that is capable of being 
reduced for purposes of moving or storing and is not a building 
element. 

GRANDSTAND. Tiered seating supported on a dedicated 
structural system and two or more rows high and is not a build- 
ing element (see u Bleachers"). 

GUARD. A building component or a system of building com- 
ponents located at or near the open sides of elevated walking 
surfaces that minimizes the possibility of a fall from the walk- 
ing surface to a lower level. 

HANDRAIL. A horizontal or sloping rail intended for grasp- 
ing by the hand for guidance or support. 

MEANS OF EGRESS. A continuous and unobstructed path 
of vertical and horizontal egress travel from any occupied por- 
tion of a building or structure to a public way. A means of 
egress consists of three separate and distinct parts: the exit 
access, the exit and the exit discharge. 

MERCHANDISE PAD. A merchandise pad is an area for dis- 
play of merchandise surrounded by aisles, permanent fixtures 
or walls. Merchandise pads contain elements such as nonfixed 
and moveable fixtures, cases, racks, counters and partitions as 
indicated in Section 105.2 from which customers browse or 
shop. 

NOSING. The leading edge of treads of stairs and of landings 
at the top of stairway flights. 

OCCUPANT LOAD. The number of persons for which the 
means of egress of a building or portion thereof is designed. 

PANIC HARDWARE. A door-latching assembly incorporat- 
ing a device that releases the latch upon the application of a 
force in the direction of egress travel. 

PHOTOLUMINESCENT. Having the property of emitting 
light that continues for a length of time after excitation by visi- 
ble or invisible light has been removed. 

PUBLIC WAY. A street, alley or other parcel of land open to 
the outside air leading to a street, that has been deeded, dedi- 
cated or otherwise permanently appropriated to the public for 
public use and which has a clear width and height of not less 
than 10 feet (3048 mm). 

RAMP. A walking surface that has a running slope steeper than 
one unit vertical in 20 units horizontal (5-percent slope). 



SCISSOR STAIR. Two interlocking stairways providing two 
separate paths of egress located within one stairwell enclosure. 

SELF-LUMINOUS. Illuminated by a self-contained power 
source, other than batteries, and operated independently of 
external power sources. 

SMOKE-PROTECTED ASSEMBLY SEATING. Seating 
served by means of egress that is not subject to smoke accumu- 
lation within or under a structure. 

STAIR. A change in elevation, consisting of one or more ris- 
ers. 

STAIRWAY. One or more flights of stairs, either exterior or 
interior, with the necessary landings and platforms connecting 
them, to form a continuous and uninterrupted passage from one 
level to another. 

STAIRWAY, EXTERIOR. A stairway that is open on at least 
one side, except for required structural columns, beams, hand- 
rails and guards. The adjoining open areas shall be either 
yards, courts or public ways. The other sides of the exterior 
stairway need not be open. 

STAIRWAY, INTERIOR. A stairway noi meeting the defini- 
tion of an exterior stairway 

STAIRWAY, SPIRAL. A stairway having a closed circular 
form in its plan view with uniform section- shaped treads 
attached to and radiating from a minimum-diameter supporting 
column. 

SUITE. A group of patient treatment rooms or patient sleeping 
rooms within Group 1-2 occupancies where staff are in atten- 
dance within the suite, for supervision of all patients within the 
suite and the suite is in compliance with the requirements of 
Sections 1014.2.2 through 1014.2.7. 

WINDER. A tread with nonparallel edges. 



SECTION 1003 
GENERAL MEANS OF EGRESS 

1003.1 Applicability. The general requirements specified in 
Sections 1003 through 1013 shall apply to all three elements of 
the means of egress system, in addition to those specific 
requirements for the exit access, the exit and the exit discharge 
detailed elsewhere in this chapter. 

1003.2 Ceiling height. The means ofegress shall have a ceiling 
height of not less than 7 feet 6 inches (2286 mm) . 

Exceptions: 

1. Sloped ceilings in accordance with Section 1208.2. 

2. Ceilings of dwelling units and sleeping units within 
residential occupancies in accordance with Section 
1208.2. 

3. Allowable projections in accordance with Section 
1003.3. 

4. Stair headroom in accordance with Section 1009.2. 

5. Door height in accordance with Section 1008.1.1. 



218 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



6. Ramp headroom in accordance with Section 
1010.5.2. 

7. The clear height of floor levels in vehicular and 
pedestrian traffic areas in parking garages in accor- 
dance with Section 406.2.2. 

8. Areas above and below mezzanine floors in accor- 
dance with Section 505.1. 

1003.3 Protruding objects. Protruding objects shall comply 
with the requirements of Sections 1003.3.1 through 1003.3.4. 

1003.3.1 Headroom. Protruding objects are permitted to 
extend below the minimum ceiling height required by Sec- 
tion 1003.2 provided a minimum headroom of 80 inches 
(2032 mm) shall be provided for any walking surface, 
including walks, corridors, aisles and passageways. Not 
more than 50 percent of the ceiling area of a means of egress 
shall be reduced in height by protruding objects. 

Exception: Door closers and stops shall not reduce 
headroom to less than 78 inches (1981 mm). 

A barrier shall be provided where the vertical clearance is 
less than 80 inches (2032 mm) high. The leading edge of 
such a barrier shall be located 27 inches (686 mm) maxi- 
mum above the floor. 

1003.3.2 Post-mounted objects. A free-standing object 
mounted on a post or pylon shall not overhang that post or 
pylon more than 4 inches (102 mm) where the lowest point 
of the leading edge is more than 27 inches (686 mm) and 
less than 80 inches (2032 mm) above the walking surface. 
Where a sign or other obstruction is mounted between posts 
or pylons and the clear distance between the posts or pylons 
is greater than 12 inches (305 mm), the lowest edge of such 
sign or obstruction shall be 27 inches (686 mm) maximum 
or 80 inches (2032 mm) minimum above the finished floor 
or ground. 

Exception: These requirements shall not apply to slop- 
ing portions of handrails between the top and bottom 
riser of stairs and above the ramp run. 

1003.3.3 Horizontal projections. Structural elements, fix- 
tures or furnishings shall not project horizontally from 
either side more than 4 inches (102 mm) over any walking 
surface between the heights of 27 inches (686 mm) and 80 
inches (2032 mm) above the walking surface. 

Exception: Handrails are permitted to protrude 4 ! / 2 
inches (114 mm) from the wall. 

1003.3.4 Clear width. Protruding objects shall not reduce 
the minimum clear width of accessible routes. 

1003.4 Floor surface. Walking surfaces of the means ofegress 
shall have a slip-resistant surface and be securely attached. 

1003.5 Elevation change. Where changes in elevation of less 
than 12 inches (305 mm) exist in the means ofegress, sloped 
surfaces shall be used. Where the slope is greater than one unit 
vertical in 20 units horizontal (5-percent slope), ramps com- 
plying with Section 1010 shall be used. Where the difference in 
elevation is 6 inches (152 mm) or less, the ramp shall be 



equipped with either handrails or floor finish materials that 
contrast with adjacent floor finish materials. 

Exceptions: 

1. A single step with a maximum riser height of 7 inches 
(178 mm) is permitted for buildings with occupancies 
in Groups F, H, R-2, R-3, Sand U at exterior doors not 
required to be accessible by Chapter 11. 

2. A stairwith a single riser or with two risers and a tread 
is permitted at locations not required to be accessible 
by Chapter 11, provided that the risers and treads 
comply with Section 1009.4, the minimum depth of 
the tread is 13 inches (330 mm) and at least one hand- 
rail complying with Section 1012 is provided within 
30 inches (762 mm) of the centerline of the normal 
path ofegress travel on the stair. 

3. A step is permitted in aisles serving seating that has a 
difference in elevation less than 12 inches (305 mm) 
at locations not required to be accessible by Chapter 
11, provided that the risers and treads comply with 
Section 1028.11 and the aisle is provided with a hand- 
rail complying with Section 1028.13. 

Throughout a story in a Group 1-2 occupancy, any change in 
elevation in portions of the exit access that serve 
nonambulatory persons shall be by means of a ramp or sloped 
walkway. 

1003.6 Means ofegress continuity. The path ofegress travel 
along a means ofegress shall not be interrupted by any building 
element other than a means ofegress component as specified in 
this chapter. Obstructions shall not be placed in the required 
width of a means ofegress except projections permitted by this 
chapter. The required capacity of a means ofegress system 
shall not be diminished along the path ofegress travel. 

1003.7 Elevators, escalators and moving walks. Elevators, 
escalators and moving walks shall not be used as a component of 
a required means ofegress from any other part of the building. 

Exception: Elevators used as an accessible means ofegress 
in accordance with Section 1007.4. 



SECTION 1004 
OCCUPANT LOAD 

1004.1 Design occupant load. In determining means ofegress 
requirements, the number of occupants for whom means of 
egress facilities shall be provided shall be determined in accor- 
dance with this section. Where occupants from accessory areas 
egress through a primary space, the calculated occupant load 
for the primary space shall include the total occupant load of 
the primary space plus the number of occupants egressing 
through it from the accessory area. 

1004.1.1 Areas without fixed seating. The number of 
occupants shall be computed at the rate of one occupant per 
unit of area as prescribed in Table 1004.1.1. For areas with- 
out fixed seating, the occupant load shall not be less than 
that number determined by dividing the floor area under 



i 



2009 INTERNATIONAL BUILDING CODE® 



219 



MEANS OF EGRESS 



consideration by the occupant per unit of area factor 
assigned to the occupancy as set forth in Table 1004.1.1. 
Where an intended use is not listed in Table 1004.1.1, the 
bUilding official shall establish a use based on a listed use 
that most nearly resembles the intended use. 

Exception: Where approvedby the building official, the 
actual number of occupants for whom each occupied 
space, floor or building is designed, although less than 
those determined by calculation, shall be permitted to be 
used in the determination of the design occupant load. 

1004.2 Increased occupant load. The occupant load permitted 
in any building, or portion thereof, is permitted to be increased 
from that number established for the occupancies in Table 
1004.1.1, provided that all other requirements of the code are 
also met based on such modified number and the occupantload 
does not exceed one occupant per 7 square feet (0.65 m 2 ) of 
occupiable floor space. Where required by the building official, 
an approved aisle, seating or fixed equipment diagram substanti- 
ating any increase in occupant load shall be submitted. Where 
required by the bUilding official, such diagram shall be posted. 

1004.3 Posting of occupant load. Every room or space that is 
an assembly occupancy shall have the occupant load of the 
room or space posted in a conspicuous place, near the main exit 
or exit access doorway from the room or space. Posted signs 
shall be of an approvedlegibiz permanent design and shall be 
maintained by the owner or authorized agent. 

1004.4 Exiting from multiple levels. Where exits serve more 
than one floor, only the occupant load of each floor considered 
individually shall be used in computing the required capacity 
of the exits at that floor, provided that the ^x/?capacity shall not 
decrease in the direction of egress travel. 

1004.5 Egress convergence. Where means of egress from 
floors above and below converge at an intermediate level, the 
capacity of the means of egress from the point of convergence 
shall not be less than the sum of the two floors. 

1004.6 Mezzanine levels. The occupant load of a mezzanine 
level with egress onto a room or area below shall be added to 
that room or area's occupantload, and the capacity of the exits 
shall be designed for the total occupantloadthus established. 

1004.7 Fixed seating. For areas having fixed seats and aisles, 
the occupant load shall be determined by the number of fixed 
seats installed therein. The occupant load for areas in which 
fixed seating is not installed, such as waiting spaces and wheel- 
chair spaces, shall be determined in accordance with Section 
1004.1.1 and added to the number of fixed seats. 

For areas having fixed seating without dividing arms, the 
occupant load shall not be less than the number of seats based 
on one person for each 18 inches (457 mm) of seating length. 

The occupant load of seating booths shall be based on one 
person for each 24 inches (610 mm) of booth seat length mea- 
sured at the backrest of the seating booth. 

1004.8 Outdoor areas. Yards, patios, courts and similar out- 
door areas accessible to and usable by the building occupants 
shall be provided with means ofegress as required by this chap- 
ter. The occupant load of such outdoor areas shall be assigned 
by the bUilding official in accordance with the anticipated use. 



TABLE 1004.1.1 
MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT 



FUNCTION OF SPACE 


FLOOR AREA IN SQ. 
FT PER OCCUPANT 


Accessory storage areas, mechanical 
equipment room 


300 gross 


Agricultural building 


300 gross 


Aircraft hangars 


500 gross 


Airport terminal 
Baggage claim 
Baggage handling 
Concourse 
Waiting areas 


20 gross 
300 gross 
100 gross 

15 gross 


Assembly 

Gaming floors (keno, slots, etc.) 


11 gross 


Assembly with fixed seats 


See Section 1004.7 


Assembly without fixed seats 

Concentrated (chairs only-not fixed) 

Standing space 

Unconcentrated (tables and chairs) 


7 net 
5 net 
15 net 


Bowling centers, allow 5 persons for each 
lane including 15 feet of runway, and for 
additional areas 


7 net 


Business areas 


100 gross 


Courtrooms-other than fixed seating areas 


40 net 


Day care 


35 net 


Dormitories 


50 gross 


Educational 
Classroom area 
Shops and other vocational room areas 


20 net 
50 net 


Exercise rooms 


50 gross 


H-5 Fabrication and manufacturing areas 


200 gross 


Industrial areas 


100 gross 


Institutional areas 

Inpatient treatment areas 
Outpatient areas 
Sleeping areas 


240 gross 
100 gross 
120 gross 


Kitchens, commercial 


200 gross 


Library 

Reading rooms 
Stack area 


50 net 
100 gross 


Locker rooms 


50 gross 


Mercantile 

Areas on other floors 
Basement and grade floor areas 
Storage, stock, shipping areas 


60 gross 
30 gross 
300 gross 


Parking garages 


200 gross 


Residential 


200 gross 


Skating rinks, swimming pools 
Rink and pool 
Decks 


50 gross 
15 gross 


Stages and platforms 


15 net 


Warehouses 


500 gross 



For 51 : 1 square foot = 0.0929 m 2 



220 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



Where outdoor areas are to be used by persons in addition to the 
occupants of the building, and the path of egress travel from the 
outdoor areas passes through the building, means of egress 
requirements for the building shall be based on the sum of the 
occupant loads of the building plus the outdoor areas. 

Exceptions: 

1. Outdoor areas used exclusively for service of the 
building need only have one means of egress. 

2. Both outdoor areas associated with Group R-3 and 
individual dwelling units of Group R-2. 

1004.9 Multiple occupancies. Where a building contains two 
or more occupancies, the means of egress requirements shall 
apply to each portion of the building based on the occupancy of 
that space. Where two or more occupancies utilize portions of 
the same means of egress system, those egress components 
shall meet the more stringent requirements of all occupancies 
that are served. 



SECTION 1005 
EGRESS WIDTH 

1005.1 Minimum required egress width. The means of 
egress width shall not be less than required by this section. The 
total width of means of egress in inches (mm) shall not be less 
than the total occupant load served by the means of egress mul- 
tiplied by 0.3 inches (7.62 mm) per occupant for stairways and 
by 0.2 inches (5.08 mm) per occupant for other egress compo- 
nents. The width shall not be less than specified elsewhere in 
this code. Multiple means of egress shall be sized such that the 
loss of anyone means of egress shall not reduce the available 
capacity to less than 50 percent of the required capacity. The 
maximum capacity required from any story of a building shall 
be maintained to the termination of the means of egress. 

Exception: Means of egress complying with Section 1028. 

1005.2 Door encroachment. Doors, when fully opened, and 
handrails shall not reduce the required means of egress width 
by more than 7 inches (178 mm). Doors in any position shall 
not reduce the required width by more than one-half. Other 
nonstructural projections such as trim and similar decorative 
features shall be permitted to project into the required width a 
maximum of 1V 2 inches (38 mm) on each side. 

Exception: The restrictions on a door swing shall not apply 
to doors within individual dwelling units and sleeping units 
of Group R-2 and dwelling units of Group R-3. 

1005.3 Door hardware encroachment. Surface-mounted 
latch release hardware shall be exempt from inclusion in the 
7-inch (178 mm) maximum projection requirement of Section 
1005.2 when: 

1. The hardware is mounted to the side of the door facing 
the corridor width when the door is in the open position; 
and 

2. The hardware is mounted not less than 34 inches (865 
mm) or more than 48 inches (1220 mm) above the fin- 
ished floor. 



SECTION 1006 
MEANS OF EGRESS ILLUMINATION 

1006.1 Illumination required. The means ofegress, including 
the exit discharge, shall be illuminated at all times the building 
space served by the means ofegress is occupied. 

Exceptions: 

1. Occupancies in Group U. 

2. Aisle acces sways in Group A. 

3. Dwelling units and sleeping units in Groups R-l, R-2 
and R-3. 

4. Sleeping units of Group I occupancies. 

1006.2 Illumination level. The means ofegress illumination 
level shall not be less than 1 foot-candle (11 lux) at the walking 
surface. 

Exception: For auditoriums, theaters, concert or opera halls 
and similar assembly occupancies, the illumination at the 
walking surface is permitted to be reduced during perfor- 
mances to not less than 0.2 foot-candle (2.15 lux), provided 
that the required illumination is automatically restored upon 
activation of a premises' fire alarm system where such sys- 
tem is provided. 

1006.3 Illumination emergency power. The power supply for 
means ofegress illumination shall normally be provided by the 
premises' electrical supply. 

In the event of power supply failure, an emergency electrical 
system shall automatically illuminate all of the following 
areas: 

1. Aisles and unenclosed egress stairways in rooms and 
spaces that require two or more means ofegress. 

2. Corridors, exit enclosures and exit passageways in 
buildings required to have two or more exits. 

3. Exterior egress components at other than their levels of 
exit discharge until exit discharge is accomplished for 
buildings required to have two or more exits. 

4. Interior exit discharge elements, as permitted in Section 
1027.1, in buildings required to have two or more exits. 

5. Exterior landings as required by Section 1008. 1.6 for exit 
discharge doorways in buildings required to have two or 
more exits. 

The emergency power system shall provide power for a 
duration of not less than 90 minutes and shall consist of storage 
batteries, unit equipment or an on-site generator. The installa- 
tion of the emergency power system shall be in accordance 
with Chapter 27. 

1006.4 Performance of system. Emergency lighting facilities 
shall be arranged to provide initial illumination that is at least 
an average of 1 foot-candle (11 lux) and a minimum at any 
point of 0.1 foot-candle (1 lux) measured along the path of 
egress at floor level. Illumination levels shall be permitted to 
decline to 0.6 foot-candle (6 lux) average and a minimum at 
any point of 0.06 foot-candle (0.6 lux) at the end of the emer- 
gency lighting time duration. A maximum-to-minimum illu- 
mination uniformity ratio of 40 to 1 shall not be exceeded. 



i 



2009 INTERNATIONAL BUILDING CODE® 



221 



MEANS OF EGRESS 



SECTION 1007 
ACCESSIBLE MEANS OF EGRESS 

1007.1 Accessible means of egress required. Accessible 
means of egress shall comply with this section. Accessible 
spaces shall be provided with not less than one accessible 
means of egress. Where more than one means of egress are 
required by Section 1015.1 or 1021.1 from any accessible 
space, each accessible portion of the space shall be served by 
not less than two accessible means of egress. 

Exceptions: 

7. Accessible means of egress are not required in alter- 
ations to existing buildings. 

2. One accessible means of egress is required from an 
accessible mezzanine level in accordance with Sec- 
tion 1007.3, 1007.4 or 1007.5. 

3. In assembly areas with sloped or stepped aisles, one 
accessible means of egress is permitted where the 
common path of travel is accessible and meets the 
requirements in Section 1028.8. 

1007.2 Continuity and components. Each required accessi- 
ble means of egress shall be continuous to a public way and 
shall consist of one or more of the following components: 

7. Accessible routes complying with Section 1104. 

12. Interior exit stairways complying with Sections 1007.3 
and 1022. 

3. Exterior exit stairways complying with Sections 1007.3 
and 1026. 

4. Elevators complying with Section 1007.4. 

5. Platform lifts complying with Section 1007.5. 

6. Horizontal exits complying with Section 1025. 

7. Ramps complying with Section 1010. 

8. Areas of refuge complying with Section 1007.6. 
Exceptions: 

1. Where the exit discharge is not accessible, an exterior 
area for assisted rescue must be provided in accor- 
dance with Section 1007.7. 

2. Where the exit stairway is open to the exterior, the 
accessible means of egress shall include either an 
area ofrefuge in accordance with Section 1007.6 or 
an exterior area for assisted rescue in accordance with 
Section 1007.7. 

1007.2.1 Elevators required. In buildings where a required 
accessible floor is four or more stories above or below a 
level of exit discharge, at least one required accessible 
means of egress shall be an elevator complying with Section 
1007.4. 

Exceptions: 

1. In buildings equipped throughout with an auto- 
matic sprinkler system installed in accordance 
with Section 903.3.1.1 or 903.3.1.2, the elevator 
shall not be required on floors provided with a hor- 
izontal exit and located at or above the levels of exit 
discharge. 



2. In buildings equipped throughout with an auto- 
matic sprinkler system installed in accordance 
with Section 903.3.1.1 or 903.3.1.2, the elevator 
shall not be required on floors provided with a 
ramp conforming to the provisions of Section 
1010. 

1007.3 Stairways. In order to be considered part of an accessi- 
ble means of egress, an exit access stairway as permitted by 
Section 1016.1 or exit stairway shall have a clear width of 48 
inches (1219 mm) minimum between handrails and shall either 
incorporate an area ofrefuge within an enlarged floor-level 
landing or shall be accessed from either an area ofrefuge com- 
plying with Section 1007.6 or a horizontal exit. 

Exceptions: 



2. The clear width of 48 inches (1219 mm) between 
handrails is not required at exit access stairway as 
permitted by Section 1016. lor exit stairways in build- 
ings equipped throughout with an automatic sprin- 
kler system installed in accordance with Section 
903.3.1.1 or 903.3.1.2. 

3. Areas ofrefuge are not required at exit stairways in 
buildings equipped throughout with an automatic 
sprinkler system installed in accordance with Section 
903.3.1.1 or 903.3.1.2. 

4. The clear width of 48 inches (1219 mm) between 
handrails is not required for exit stairways accessed 
from a horizontal exit. 

5. Areas ofrefuge are not required at exit stairways serv- 
ing open pa rking garages. 

6. Areas ofrefuge are not required for smoke protected 
seating areas complying with Section 1028.6.2. 

7. The areas ofrefuge are not required in Group R-2 
occupancies. 

1007.4 Elevators. In order to be considered part of an accessi- 
ble means of egress, an elevator shall comply with the emer- 
gency operation and signaling device requirements of Section 
2.27 of ASME A17.1. Standby power shall be provided in 
accordance with Chapter 27 and Section 3003. The elevator 
shall be accessed from either an area ofrefuge complying with 
Section 1007.6 or a horizontal exit. 

Exceptions: 

1. Elevators are not required to be accessed from an area 
ofrefuge or horizontal exitin openparking garages. 

2. Elevators are not required to be accessed from an area 
ofrefuge or horizontal exitin buildings and facilities 
equipped throughout with an automatic sprinkler sys- 
tem installed in accordance with Section 903.3.1.1 or 
903.3.1.2. 



222 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



3. Elevators not required to be located in a shaft in accor- 
dance with Section 708.2 are not required to be 
accessed from an area ofrefuge or horizontal exit. 

4. Elevators are not required to be accessed from an area 
ofrefuge or horizontal exit for smoke protected seat- 
ing areas complying with Section 1028.6.2. 

1007.5 Platform lifts. Platform (wheelchair) lifts shall not 
serve as part of an accessible means of egress, except where 
allowed as part of a required accessible route in Section 
1 109.7, Items 1 through 9. Standby power shall be provided in 
accordance with Chapter 27 for platform lifts permitted to 
serve as part of a means of egress. 

1007.5.1 Openness. Platform lifts on an accessible means 
of egress shall not be installed in a fully enclosed hoistway . 

1007.6 Areas ofrefuge. Every required area ofrefuge shall be 
accessible from the space it serves by an accessible means of 
egress. The maximum travel distance from any accessible 
space to an area ofrefuge shall not exceed the travel distance 
permitted for the occupancy in accordance with Section 
1016.1. Every required area ofrefuge shall have direct access 
to a stairway within an exit enclosure complying with Sections 
1007.3 and 1022 or an elevator complying with Section 
1007.4. Where an elevator lobby is used as an area ofrefuge, 
the shaft and lobby shall comply with Section 1022.9 for 
smokeproof enclosures except where the elevators are in an 
area ofrefuge formed by a horizontal exit or smoke barrier. 

Exceptions: 

1. A st airway serving an area ofrefuge is not required to 
be enclosed where permitted in Sections 1016.1 and 
1022.1. 

2. Smokeproof enclosure is not required for an elevator 
lobby used as an area ofrefuge not required to be 
enclosed. 

1007.6.1 Size. Each area ofrefuge shall be sized to accom- 
modate one wheelchair space of 30 inches by 48 inches 
(762 mm by 1219 mm) for each 200 occupants or portion 
thereof, based on the occupantloadofthe area ofrefuge and 
areas served by the area ofrefuge. Such wheelchair spaces 
shall not reduce the required means of egress width. Access 
to any of the required wheelchair space sin an area ofrefuge 
shall not be obstructed by more than one adjoining wheel- 
chair space. 

1007.6.2 Separation. Each area ofrefuge shall be separated 
from the remainder of the story by a smoke barrier comply- 
ing with Section 710 or a horizontal exit complying with 
Section 1025. Each area ofrefuge shall be designed to mini- 
mize the intrusion of smoke. 

Exception: Areas ofrefuge located within an exit enclo- 
sure. 

1007.6.3 Two-way communication. Areas ofrefuge shall 
be provided with a two-way communication system com- 
plying with Sections 1007.8.1 and 1007.8.2. 

1007.7 Exterior area for assisted rescue. The exterior area for 
assisted rescue must be open to the outside air and meet the 



requirements of Section 1007.6.1. Separation walls shall com- 
ply with the requirements of Section 705 for exterior walls. 
Where walls or openings are between the area for assisted res- 
cue and the interior of the building, the building exterior walls 
within 10 feet (3048 mm) horizontally of a nonrated wall or 
unprotected opening shall have a fire -resistance rating of noi 
less than 1 hour. Openings within such exterior walls shall be 
protected by opening protectives having afire protection rating 
of not less than 3/ 4 hour. This construction shall extend verti- 
cally from the ground to a point 10 feet (3048 mm) above the 
floor level of the area for assisted rescue or to the roof line, 
whichever is lower. 

1007.7.1 Openness. The exterior area for assisted rescue 
shall be at least 50 percent open, and the open area above the 
guards shall be so distributed as to minimize the accumula- 
tion of smoke or toxic gases. 

1007.7.2 Exterior exit stairway. Exterior exit stairways 
that are part of the means of egress for the exterior area for 
assisted rescue shall provide a clear width of 48 inches 
(1219 mm) between handrails. ■ 

1007.8 Two-way communication. A two-way communica- 
tion system shall be provided at the elevator landing on each 
accessible floor that is one or more stories above or below the 
story of exit discharge complying with Sections 1007.8.1 and 
1007.8.2. 

Exceptions: 

1. Two-way communication systems are not required at 
the elevator landing where the two-way communica- 
tion system is provided within areas ofrefuge in 
accordance with Section 1007.6.3. 

2. Two-way communication systems are not required on 
floors provided with exit ramps conforming to the 
provisions of Section 1010. 

1007.8.1 System requirements. Two-way communication 
systems shall provide communication between each 
required location and the fire command center or a central 
control point location approved by the fire department. 
Where the central control point is not constantly attended, a 
two-way communication system shall have a timed auto- 
matic telephone dial-out capability to a monitoring location 
or 911. The two-way communication system shall include 
both audible and visible signals. 

1007.8.2 Directions. Directions for the use of the two-way 
communication system, instructions for summoning assis- 
tance via the two-way communication system and written 
identification of the location shall be posted adjacent to the 
two-way communication system. 

1007.9 Signage. Signage indicating special accessibility pro- 
visions shall be provided as shown: 

1. Each door providing access to an area ofrefuge from an 
adjacent floor area shall be identified by a sign stating: 
AREA OF REFUGE. 

2. Each door providing access to an exterior area for 
assisted rescue shall be identified by a sign stating: 
EXTERIOR AREA FOR ASSISTED RESCUE. 



2009 INTERNATIONAL BUILDING CODE® 



223 



MEANS OF EGRESS 



Signage shall comply with the ICC A 117.1 requirements for 
visual characters and include the International Symbol of 
Accessibility. Where exit sign illumination is required by Sec- 
tion 1011.2, the signs shall be illuminated. Additionally, tactile 
signage complying with ICC All 7.1 shall be located at each 
door to an area ofrefuge and exterior area for assisted rescue in 
accordance with Section 1011.3. 

1007.10 Directional signage. Direction signage indicating the 
location of the other means of egress and which are accessible 
means of egress shall be provided at the following: 

1. At exits serving a required accessible space but not pro- 
viding an approved accessible means of egress. 

2. At elevator landings. 

3. Within areas ofrefuge. 

1007.11 Instructions. In areas ofrefuge and exterior areas for 
assisted rescue, instructions on the use of the area under emer- 
gency conditions shall be posted. The instructions shall include 
all of the following: 

1. Persons able to use the exit stairway do so as soon as pos- 
sible, unless they are assisting others. 

2. Information on planned availability of assistance in the 
use of stairs or supervised operation of elevators and how 
to summon such assistance. 

3. Directions for use of the two-way communications sys- 
tem where provided. 



SECTION 1008 
DOORS, GATES AND TURNSTILES 

1008.1 Doors. Means of egress doors shall meet the require- 
ments of this section. Doors serving a means of egress system 
shall meet the requirements of this section and Section 1020.2. 
Doors provided for egress purposes in numbers greater than 
required by this code shall meet the requirements of this sec- 
tion. 

Means of egress doors shall be readily distinguishable from 
the adjacent construction and finishes such that the doors are 
easily recognizable as doors. Mirrors or similar reflecting 
materials shall not be used on means of egress doors. Means of 
egress doors shall not be concealed by curtains, drapes, decora- 
tions or similar materials. 

1008.1.1 Size of doors. The minimum width of each door 
opening shall be sufficient for the occupant loadthereof "and 
shall provide a clear width of 32 inches (813 mm). Clear 
openings of doorways with swinging doors shall be mea- 
sured between the face of the door and the stop, with the 
door open 90 degrees (1.57 rad). Where this section requires 
a minimum clear width of 32 inches (813 mm) and a door 
opening includes two door leaves without a mullion, one 
leaf shall provide a clear opening width of 32 inches (813 
mm). The maximum width of a swinging door leaf shall be 



48 inches (1219 mm) nominal. Means of egress doors in a 
Group 1-2 occupancy used for the movement of beds shall 
provide a clear width not less than 41 V 2 inches (1054 mm). 
The height of door openings shall not be less than 80 inches 
(2032 mm). 

Exceptions: 

1. The minimum and maximum width shall not apply 
to door openings that are not part of the required 
means of egress in Group R-2 and R-3 occupan- 
cies. 

2. Door openings to resident sleeping units in Group 
1-3 occupancies shall have a clear width of not less 
than 28 inches (711 mm). 

3. Door openings to storage closets less than 10 
square feet (0.93 m 2 ) in area shall not be limited by 
the minimum width. 

4. Width of door leaves in revolving doors that com- 
ply with Section 1008.1.4.1 shall not be limited. 

5. Door openings within a dwelling unit or sleeping 
unit shall not be less than 78 inches (1981 mm) in 
height. 

6. Exterior door openings in dwelling units and 
sleeping units, other than the required exit door, 
shall not be less than 76 inches (1930 mm) in 
height. 

7. In other than Group R-l occupancies, the mini- 
mum widths shall not apply to interior egress doors 
within a dwelling unit or sleeping unit that is not 
required to be an Accessible unit, Type A unit or 
TypeB unit. 

1008.1.1.1 Projections into clear width. There shall not 
be projections into the required clear width lower than 34 
inches (864 mm) above the floor or ground. Projections 
into the clear opening width between 34 inches (864 
mm) and 80 inches (2032 mm) above the floor or ground 
shall not exceed 4 inches (102 mm). 

Exception: Door closers and door stops shall be per- 
mitted to be 78 inches (1980 mm) minimum above the 
floor. 

1008.1.2 Door swing. Egress doors shall be of the pivoted 
or side-hinged swinging type. 

Exceptions: 

1. Private garages, office areas, factory and storage 
areas with an occupant load of 10 or less. 

2. Group 1-3 occupancies used as a place of deten- 
tion. 

3. Critical or intensive care patient rooms within 
suites of health care facilities. 



224 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



I 



4. Doors within or serving a single dwelling unit in 
Groups R-2 and R-3. 

5. In other than Group H occupancies, revolving 
doors complying with Section 1008.1.4.1. 

6. In other than Group H occupancies, horizontal 
sliding doors complying with Section 1008.1.4.3 
are permitted in a means of egress. 

7. Power-operated doors in accordance with Section 
1008.1.4.2. 

8. Doors serving a bathroom within an individual 
sleeping unit in Group R-l. 

9. In other than Group H occupancies, manually 
operated horizontal sliding doors are permitted in a 
means of egress from spaces with an occupant 
load of 10 or less. 

Doors shall swing in the direction of egress travel where 
serving an occupant load of 50 or more persons or a Group 
H occupancy. 

1008.1.3 Door opening force. The force for pushing or 
pulling open interior swinging egress doors, other than fire 
doors, shall not exceed 5 pounds (22 N). For other swinging 
doors, as well as sliding and folding doors, the door latch 
shall release when subjected to a IS -pound (67 N) force. 
The door shall be set in motion when subjected to a 
30-pound (133 N) force. The door shall swing to a full-open 
position when subjected to a IS -pound (67 N) force. 

1008.1.3.1 Location of applied forces. Forces shall be 
applied to the latch side of the door. 

1008.1.4 Special doors. Special doors and security grilles 
shall comply with the requirements of Sections 1008.1.4.1 
through 1008.1.4.5. 

1008.1.4.1 Revolving doors. Revolving doors shall 
comply with the following: 

1. Each revolving door shall be capable of collapsing 
into a bookfold position with parallel egress paths 
providing an aggregate width of 36 inches (914 
mm). 

2. A revolving door shall not be located within 10 
feet (3048 mm) of the foot of or top of stairs or 
escalators. A dispersal area shall be provided 
between the stairs or escalators and the revolving 
doors. 

3. The revolutions per minute (rpm) for a revolving 
door shall not exceed those shown in Table 
1008.1.4.1. 

4. Each revolving door shall have a side-hinged 
swinging door which complies with Section 
1008.1 in the same wall and within 10 feet (3048 
mm) of the revolving door. 

5. Revolving doors shall not be part of an accessible 
route required by Section 1007 and Chapter 11. 



TABLE 1008.1.4.1 
REVOLVING DOOR SPEEDS 



INSIDE DIAMETER 
(feet-inches) 


POWER-DRIVEN-TYPE 

SPEED CONTROL 

(rpm) 


MANUAL-TYPE 

SPEED CONTROL 

(rpm) 


6-6 


11 


12 


7-0 


10 


11 


7-6 


9 


11 


8-0 


9 


10 


8-6 


8 


9 


9-0 


8 


9 


9-6 


7 


8 


10-0 


7 


8 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

1008.1.4.1.1 Egress component. A revolving door 
used as a component of a means of egress shall com- 
ply with Section 1008.1.4.1 and the following three 
conditions: 

1. Revolving doors shall not be given credit for 
more than 50 percent of the required egress 
capacity. 

2. Each revolving door shall be credited with no 
more than a 50-person capacity. 

3. Each revolving door shall be capable of being 
collapsed when a force of not more than 130 
pounds (578 N) is applied within 3 inches (76 
mm) of the outer edge of a wing. 

1008.1.4.1.2 Other than egress component. A 
revolving door used as other than a component of a 
means of egress shall comply with Section 
1008.1.4.1. The collapsing force of a revolving door 
not used as a component of a means ofegress shall not 
be more than 180 pounds (801 N). 

Exception: A collapsing force in excess of 180 
pounds (801 N) is permitted if the collapsing force 
is reduced to not more than 130 pounds (578 N) 
when at least one of the following conditions is sat- 
isfied: 

1. There is a power failure or power is removed 
to the device holding the door wings in posi- 
tion. 

2. There is an actuation of the automatic sprin- 
kler system where such system is provided. 

3. There is an actuation of a smoke detection 
system which is installed in accordance with 
Section 907 to provide coverage in areas 
within the building which are within 75 feet 
(22 860 mm) of the revolving doors. 

4. There is an actuation of a manual control 
switch, in an approvedlocation and clearly 



2009 INTERNATIONAL BUILDING CODE® 



225 



MEANS OF EGRESS 



defined, which reduces the holding force to 
below the 130-pound (578 N) force level. 

1008.1.4.2 Power-operated doors. Where means of 
egress doors are operated by power, such as doors with a 
photoelectric-actuated mechanism to open the door upon 
the approach of a person, or doors with power-assisted 
manual operation, the design shall be such that in the 
event of power failure, the door is capable of being 
opened manually to permit means of egress travel or 
closed where necessary to safeguard means of egress. 
The forces required to open these doors manually shall 
not exceed those specified in Section 1008.1.3, except 
that the force to set the door in motion shall not exceed 50 
pounds (220 N). The door shall be capable of swinging 
from any position to the full width of the opening in 
which such door is installed when a force is applied to the 
door on the side from which egress is made. 
FUll-power-operated doors shall comply with BHMA 
AI56.10. Power-assisted and low-energy doors shall 
comply with B HM A AI5 6 . 1 9 . 

Exceptions: 

1. Occupancies in Group 1-3. 

2. Horizontal sliding doors complying with Sec- 
tion 1008.1.4.3. 

3. For a biparting door in the emergency breakout 
mode, a door leaf located within a multiple-leaf 
opening shall be exempt from the minimum 
32-inch (813 mm) single-leaf requirement of 
Section 1008.1.1, provided a minimum 32-inch 
(813 mm) clear opening is provided when the 
two biparting leaves meeting in the center are 
broken out. 

1008.1.4.3 Horizontal sliding doors. In other than 
Group H occupancies, horizontal sliding doors permitted 
to be a component of a means of egress in accordance 
with Exception 6 to Section 1008.1.2 shall comply with 
all of the following criteria: 

1. The doors shall be power operated and shall be 
capable of being operated manually in the event of 
power failure. 

2. The doors shall be openable by a simple method 
from both sides without special knowledge or 
effort. 

3. The force required to operate the door shall not 
exceed 30 pounds (133 N) to set the door in motion 
and 15 pounds (67 N) to close the door or open it to 
the minimum required width. 

4. The door shall be openable with a force not to 
exceed 15 pounds (67 N) when a force of 250 
pounds (1100 N) is applied perpendicular to the 
door adjacent to the operating device. 

5. The door assembly shall comply with the applica- 
ble fire protection rating and, where rated, shall be 
self-closing or automatic closing by smoke detec- 
tion in accordance with Section 715.4.8.3, shall be 



installed in accordance with NFPA 80 and shall 
comply with Section 715. 

6. The door assembly shall have an integrated 
standby power supply. 

7. The door assembly power supply shall be electri- 
cally supervised. 

8. The door shall open to the minimum required 
width within 10 seconds after activation of the 
operating device. 

1008.1.4.4 Access-controlled egress doors. The 
entrance doors in a means of egress in buildings with an 
occupancy in Group A, B, E, 1-2, M, R-l or R-2 and 
entrance doors to tenant spaces in occupancies in Groups 
A, B, E, 1-2, M, R-l and R-2 are permitted to be equipped 
with an approved entrance and egress access control sys- 
tem which shall be installed in accordance with all of the 
following criteria: 

1. A sensor shall be provided on the egress side 
arranged to detect an occupant approaching the 
doors. The doors shall be arranged to unlock by a 
signal from or loss of power to the sensor. 

2. Loss of power to that part of the access control sys- 
tem which locks the doors shall automatically 
unlock the doors. 

3. The doors shall be arranged to unlock from a man- 
ual unlocking device located 40 inches to 48 
inches (1016 mm to 1219 mm) vertically above the 
floor and within 5 feet (1524 mm) of the secured 
doors. Ready access shall be provided to the man- 
ual unlocking device and the device shall be 
clearly identified by a sign that reads "PUSH TO 
EXIT." When operated, the manual unlocking 
device shall result in direct interruption of power 
to the lock-independent of the access control sys- 
tem electronics-and the doors shall remain 
unlocked for a minimum of 30 seconds. 

4. Activation of the building fire alarm system, if 
provided, shall automatically unlock the doors, 
and the doors shall remain unlocked until the fire 
alarm system has been reset. 

5. Activation of the building automatic sprinkler or 
fire detection system, if provided, shall automati- 
cally unlock the doors. The doors shall remain 
unlocked until the fire alarm system has been reset. 

6. Entrance doors in buildings with an occupancy in 
Group A, B, E or M shall not be secured from the 
egress side during periods that the building is open 
to the general public. 

1008.1.4.5 Security grilles. In Groups B, F, M and S, 
horizontal sliding or vertical security grilles are permit- 
ted at the main exit and shall be openable from the inside 
without the use of a key or special knowledge or effort 
during periods that the space is occupied. The grilles 
shall remain secured in the full-open position during the 
period of occupancy by the general public. Where two or 
more means of egress are required, not more than 



226 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



one-half of the exits or exit access doorways shall be 
equipped with horizontal sliding or vertical security 
grilles. 

1008.1.5 Floor elevation. There shall be a floor or landing 
on each side of a door. Such floor or landing shall be at the 
same elevation on each side of the door. Landings shall be 
level except for exterior landings, which are permitted to 
have a slope not to exceed 0.25 unit vertical in 12 units hori- 
zontal (2-percent slope). 

Exceptions: 

1. Doors serving individual dwelling units in Groups 
R-2 and R-3 where the following apply: 

1.1. A door is permitted to open at the top step 
of an interior flight of stairs, provided the 
door does not swing over the top step. 

1.2. Screen doors and storm doors are permit- 
ted to swing over stairs or landings. 

2. Exterior doors as provided for in Section 1003.5, 
Exception 1, and Section 1020.2, which are not on 
an accessible route. 

3. In Group R-3 occupancies not required to be 
Accessible units, Type A units or Type B units, the 
landing at an exterior doorway shall not be more 
than 7 s / 4 inches (197 mm) below the top of the 
threshold, provided the door, other than an exterior 
storm or screen door, does not swing over the land- 
ing. 

4. Variations in elevation due to differences in finish 
materials, but not more than i/ 2 inch (12.7 mm). 

5. Exterior decks, patios or balconies that are part of 
Type B dwelling units, have impervious surfaces 
and that are not more than 4 inches (102 mm) 
below the finished floor level of the adjacent inte- 
rior space of the dwelling unit. 

1008.1.6 Landings at doors. Landings shall have a width 
not less than the width of the stairway or the door, which- 
ever is greater. Doors in the fully open position shall not 
reduce a required dimension by more than 7 inches (178 
mm). When a landing serves an occupant load of 50 or 
more, doors in any position shall not reduce the landing to 
less than one-half its required width. Landings shall have a 
length measured in the direction of travel of not less than 44 
inches (1118 mm). 

Exception: Landing length in the direction of travel in 
Groups R-3 and U and within individual units of Group 
R-2 need not exceed 36 inches (914 mm). 

1008.1.7 Thresholds. Thresholds at doorways shall not 
exceed Ji 4 inch (19.1 mm) in height for sliding doors serving 
dwelling units or i/ 2 inch (12.7 mm) for other doors. Raised 
thresholds and floor level changes greater than i/ 4 inch (6.4 
mm) at doorways shall be beveled with a slope not greater 
than one unit vertical in two units horizontal (50-percent 
slope). 

Exception: The threshold height shall be limited to 7% 
inches (197 mm) where the occupancy is Group R-2 or 



R-3; the door is an exterior door that is not a component 
of the required means of egress; the door, other than an 
exterior storm or screen door, does not swing over the 
landing or step; and the doorway is not on an accessible 
route as required by Chapter 11 and is not part of an 
Accessible unit, Type A unit or Type B unit. 

1008. 1 .8 Door arrangement. Space between two doors in a 
series shall be 48 inches (1219 mm) minimum plus the 
width of a door swinging into the space. Doors in a series 
shall swing either in the same direction or away from the 
space between the doors. 

Exceptions: 

1. The minimum distance between horizontal sliding 
power-operated doors in a series shall be 48 inches 
(1219 mm). 

2. Storm and screen doors serving individual dwell- 
ing units in Groups R-2 and R-3 need not be spaced 
48 inches (1219 mm) from the other door. 

3. Doors within individual dwelling units in Groups 
R-2 and R-3 other than within Type A dwelling 
units. 

1008. 1.9 Door operations. Except as specifically permitted 
by this section egress doors shall be readily openable from 
the egress side without the use of a key or special knowledge 
or effort. 

1008.1.9.1 Hardware. Door handles, pulls, latches, 
locks and other operating devices on doors required to be 
accessible^ Chapter 11 shall not require tight grasping, 
tight pinching or twisting of the wrist to operate. 

1008.1.9.2 Hardware height. Door handles, pulls, 
latches, locks and other operating devices shall be 
installed 34 inches (864 mm) minimum and 48 inches 
(1219 mm) maximum above the finished floor. Locks 
used only for security purposes and not used for normal 
operation are permitted at any height. 

Exception: Access doors or gates in barrier walls and 
fences protecting pools, spas and hot tubs shall be per- 
mitted to have operable parts of the release of latch on 
self-latching devices at 54 inches (1370 mm) maxi- 
mum above the finished floor or ground, provided the 
self-latching devices are not also self-locking devices 
operated by means of a key, electronic opener or inte- 
gral combination lock. 

1008.1.9.3 Locks and latches. Locks and latches shall 
be permitted to prevent operation of doors where any of 
the following exists: 

1. Places of detention or restraint. 

2. In buildings in occupancy Group A having an 
occupant load oi 300 or less, Groups B, F, M and 
S, and in places of religious worship, the main 
exterior door or doors are permitted to be equipped 
with key-operated locking devices from the egress 
side provided: 

2.1. The locking device is readily distinguish- 
able as locked; 



2009 INTERNATIONAL BUILDING CODE® 



227 



MEANS OF EGRESS 



2.2. A readily visible durable sign is posted on 
the egress side on or adjacent to the door 
stating: THIS DOOR TO REMAIN 
UNLOCKED WHEN BUILDING IS 
OCCUPIED. The sign shall be in letters 1 
inch (25 mm) high on a contrasting back- 
ground; and 

2.3. The use of the key-operated locking device 
is revokable by the building official for due 
cause. 

3. Where egress doors are used in pairs, approved 
automatic flush bolts shall be permitted to be used, 
provided that the door leaf having the automatic 
flush bolts has no doorknob or surface-mounted 
hardware. 

4. Doors from individual dwelling or sleeping units 
of Group R occupancies having an occupant load 
of 10 or less are permitted to be equipped with a 
night latch, dead bolt or security chain, provided 
such devices are openable from the inside without 
the use of a key or tool. 

5. Fire doors after the minimum elevated tempera- 
ture has disabled the unlatching mechanism in 
accordance with listed fire door test procedures. 

1008.1.9.4 Bolt locks. Manually operated flush bolts or 
surface bolts are not permitted. 

Exceptions: 

1. On doors not required for egress in individual 
dwelling units or sleeping units. 

2. Where a pair of doors serves a storage or equip- 
ment room, manually operated edge- or sur- 
face-mounted bolts are permitted on the 
inactive leaf. 

3. Where a pair of doors serves an occupant load 
of less than 50 persons in a Group B, F or S 
occupancy, manually operated edge- or sur- 
face-mounted bolts are permitted on the inac- 
tive leaf. The inactive leaf shall contain no 
doorknobs, panic bars or similar operating 
hardware. 

4. Where a pair of doors serves a Group B, For S 
occupancy, manually operated edge- or sur- 
face-mounted bolts are permitted on the inac- 
tive leaf provided such inactive leaf is not 
needed to meet egress width requirements and 
the building is equipped throughout with an 
automatic sprinkler system in accordance with 
Section 903.3.1.1. The inactive leaf shall con- 
tain no doorknobs, panic bars or similar operat- 
ing hardware. 

5. Where a pair of doors serves patient care rooms 
in Group 1-2 occupancies, self-latching edge- 
or surface-mounted bolts are permitted on the 
inactive leaf provided that the inactive leaf is 
not needed to meet egress width requirements 



and the inactive leaf contains no doorknobs, 
panic bars or similar operating hardware. 

1008.1.9.5 Unlatching. The unlatching of any door or 
leaf shall not require more than one operation. 

Exceptions: 

1. Places of detention or restraint. 

2. Where manually operated bolt locks are permit- 
ted by Section 1008.1.9.4. 

3. Doors with automatic flush bolts as permitted 
by Section 1008.1.9.3, Exception 3. 

4. Doors from individual dwelling units and 
sleeping units of Group R occupancies as per- 
mitted by Section 1008.1.9.3, Exception 4. 

1008.1.9.5.1 Closet and bathroom doors in Group 
R-4 occupancies. In Group R-4 occupancies, closet 
doors that latch in the closed position shall be 
openable from inside the closet, and bathroom doors 
that latch in the closed position shall be capable of 
being unlocked from the ingress side. 

1008.1.9.6 Special locking arrangements in Group 
I -2. Approved delayed egress locks shall be permitted in 
a Group 1-2 occupancy where the clinical needs of per- 
sons receiving care require such locking. Delayed egress 
locks shall be permitted in such occupancies where the 
building is equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1 or 
an approved automatic smoke or heat detection system 
installed in accordance with Section 907, provided that 
the doors unlock in accordance with Items 1 through 6 
below. A building occupant shall not be required to pass 
through more than one door equipped with a delayed 
egress lock before entering an exit. 

1. The doors unlock upon actuation of the automatic 
sprinkler system or automatic fire detection sys- 
tem. 

2. The doors unlock upon loss of power controlling 
the lock or lock mechanism. 

3. The door locks shall have the capability of being 
unlocked by a signal from the fire command cen- 
ter, a nursing station or other approved location. 

4. The procedures for the operation(s) of the unlock- 
ing system shall be described and approved^ part 
of the emergency planning and preparedness 
required by Chapter 4 of the International Fire 
Code. 

5. All clinical staff shall have the keys, codes or other 
means necessary to operate the locking devices. 

6. Emergency lighting shall be provided at the door. 

Exception: Items 1 through 3 shall not apply to doors 
to areas where persons, because of clinical needs, 
require restraint or containment as part of the function 
of a mental hospital. 

1008.1.9.7 Delayed egress locks. Approved, listed, 
delayed egress locks shall be permitted to be installed on 



228 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



doors serving any occupancy except Group A, E and H 
occupancies in buildings that are equipped throughout 
with an automatic sprinkler system in accordance with 
Section 903.3.1.1 or an approved automatic smoke or 
heat detection system installed in accordance with Sec- 
tion 907, provided that the doors unlock in accordance 
with Items 1 through 6 below. A building occupant shall 
not be required to pass through more than one door 
equipped with a delayed egress lock before entering an 
exit. 

1. The doors unlock upon actuation of the automatic 
sprinkler system or automatic fire detection sys- 
tem. 

2. The doors unlock upon loss of power controlling 
the lock or lock mechanism. 

3. The door locks shall have the capability of being 
unlocked by a signal from the fire command cen- 
ter. 

4. The initiation of an irreversible process which will 
release the latch in not more than 15 seconds when 
a force of not more than 15 pounds (67 N) is 
applied for 1 second to the release device. Initia- 
tion of the irreversible process shall activate an 
audible signal in the vicinity of the door. Once the 
door lock has been released by the application of 
force to the releasing device, relocking shall be by 
manual means only. 

Exception: Where approved, a delay of not 
more than 30 seconds is permitted. 

5. A sign shall be provided on the door located above 
and within 12 inches (305 mm) of the release 
device reading: PUSH UNTIL ALARM 
SOUNDS. DOOR CAN BE OPENED IN 15 [30] 
SECONDS. 

6. Emergency lighting shall be provided at the door . 

1008.1.9.8 Electromagnetically locked egress doors. 
Doors in the means of egress that are not otherwise 
required to have panic hardware in buildings with an 
occupancy in Group A, B, E, M, R-l or R-2 and doors to 
tenant spaces in Group A, B, E, M, R-l or R-2 shall be 
permitted to be electromagnetically locked if equipped 
with listed hardware that incorporates a built-in switch 
and meet the requirements below: 

1. The listed hardware that is affixed to the door leaf 
has an obvious method of operation that is readily 
operated under all lighting conditions. 

2. The listed hardware is capable of being operated 
with one hand. 

3. Operation of the listed hardware releases to the 
electromagnetic lock and unlocks the door imme- 
diately. 

4. Loss of power to the //.stedhardware automatically 
unlocks the door. 

1008.1.9.9 Locking arrangements in correctional 
facilities. In occupancies in Groups A-2, A-3, A-4, B, E, 



F, 1-2, 1-3, M and S within correctional and detention 
facilities, doors in means of egress serving rooms or 
spaces occupied by persons whose movements are con- 
trolled for security reasons shall be permitted to be 
locked when equipped with egress control devices which 
shall unlock manually and by at least one of the follow- 
ing means: 

1. Activation of an automatic sprinkler system 
installed in accordance with Section 903.3.1.1 ; 

2. Activation of an approved manual alarm box; or 

3. A signal from a constantly attended location. 

1008.1.9.10 Stairway doors. Interior stairway means of 
egress doors shall be openable from both sides without 
the use of a key or special knowledge or effort. 

Exceptions: 

1. Stairway discharge doors shall be openable 
from the egress side and shall only be locked 
from the opposite side. 

2. This section shall not apply to doors arranged in 
accordance with Section 403.5.3. 

3. In stairways serving not more than four stories, 
doors are permitted to be locked from the side 
opposite the egress side, provided they are 
openable from the egress side and capable of 
being unlocked simultaneously without 
unlatching upon a signal from the fire com- 
mand center, if present, or a signal by emer- 
gency personnel from a single location inside 
the main entrance to the building. 

1008.1.10 Panic and fire exit hardware. Doors serving a 
Group H occupancy and doors serving rooms or spaces with 
an occupantloadof 50 or more in a Group A or E occupancy 
shall not be provided with a latch or lock unless it is panic 
hardware or fire exit hardware. 

Exception: A main exitofa. Group A occupancy in com- 
pliance with Section 1008.1.9.3, Item 2. 

Electrical rooms with equipment rated 1,200 amperes or 
more and over 6 feet (1829 mm) wide that contain 
overcurrent devices, switching devices or control devices 
with exit or exit access doors shall be equipped with panic 
hardware or fire exit hardware. The doors shall swing in the 
direction of egress travel. 

1008.1.10.1 Installation. Where panic or fire exit hard- 
ware is installed, it shall comply with the following: 

1. Panic hardware shall be listed in accordance with 
UL 305; 

2. Fire exit hardware shall be listed in accordance 
with UL 10C and UL 305; 

3. The actuating portion of the releasing device shall 
extend at least one-half of the door leafwidth; and 

4. The maximum unlatching force shall not exceed 
15 pounds (67 N). 

1008.1.10.2 Balanced doors. If balanced doors are 
used and panic hardware is required, the panic hardware 



2009 INTERNATIONAL BUILDING CODE® 



229 



MEANS OF EGRESS 



shall be the push-pad type and the pad shall not extend 
more than one-half the width of the door measured from 
the latch side. 

1008.2 Gates. Gates serving the means of egress system shall 
comply with the requirements of this section. Gates used as a 
component in a means of egress shall conform to the applicable 
requirements for doors. 

Exception: Horizontal sliding or swinging gates exceeding 
the 4-foot (1219 mm) maximum leaf width limitation are 
permitted in fences and walls surrounding a stadium. 

1008.2.1 Stadiums. Panic hardware is not required on gates 
surrounding stadiums where such gates are under constant 
immediate supervision while the public is present, and 
where safe dispersal areas based on 3 square feet (0.28 m 2 ) 
per occupant are located between the fence and enclosed 
space. Such required safe dispersal areas shall not be 
located less than 50 feet (15 240 mm) from the enclosed 
space. See Section 1027.6 for means ofegress fcom safe dis- 
persal areas. 

1008.3 Turnstiles. Turnstiles or similar devices that restrict 
travel to one direction shall not be placed so as to obstruct any 
required means of egress. 

Exception: Each turnstile or similar device shall be credited 
with no more than a 50-person capacity where all of the fol- 
lowing provisions are met: 

1. Each device shall turn free in the direction of egress 
travel when primary power is lost, and upon the man- 
ual release by an employee in the area. 

2. Such devices are not given credit for more than 50 
percent of the required egress capacity. 

3. Each device is not more than 39 inches (991 mm) 
high. 

4. Each device has at least 16 l i 2 inches (419 mm) clear 
width at and below a height of 39 inches (991 mm) 
and at least 22 inches (559 mm) clear width at heights 
above 39 inches (991 mm). 

Where located as part of an accessible route, turnstiles shall 
have at least 36 inches (914 mm) clear at and below a height of 
34 inches (864 mm), at least 32 inches (813 mm) clear width 
between 34 inches (864 mm) and 80 inches (2032 mm) and 
shall consist of a mechanism other than a revolving device. 

1008.3.1 High turnstile. Turnstiles more than 39 inches 
(991 mm) high shall meet the requirements for revolving 
doors. 

1008.3.2 Additional door. Where serving an occupantload 
greater than 300, each turnstile that is not portable shall have 
a side-hinged swinging door which conforms to Section 
1008.1 within 50 feet (15 240 mm). 



SECTION 1009 
STAIRWAYS 

1009.1 Stairway width. The width of stairways shall be deter- 
mined as specified in Section 1005.1, but such width shall not 



be less than 44 inches (1118 mm). See Section 1007.3 for 
accessible means of egress stairways. 

Exceptions: 

1. Stairways serving an occupant load of less than 50 
shall have a width of not less than 36 inches (914 
mm). 

2. Spiral stairways as provided for in Section 1009.9. 

3. Aisle stairs complying with Section 1028. 

4. Where an incline platform lift or stairway chairlift is 
installed on stairways serving occupancies in Group 
R-3, or within dwelling units in occupancies in Group 
R-2, a clear passage width not less than 20 inches (508 
mm) shall be provided. If the seat and platform can be 
folded when not in use, the distance shall be measured 
from the folded position. 

1009.2 Headroom. Stairways shall have a minimum head- 
room clearance of 80 inches (2032 mm) measured vertically 
from a line connecting the edge of the nosings. Such headroom 
shall be continuous above the stairway to the point where the 
line intersects the landing below, one tread depth beyond the 
bottom riser. The minimum clearance shall be maintained the 
full width of the stairway and landing. 

Exceptions: 

1. Spiral stairways complying with Section 1009.9 are 
permitted a 78-inch (1981 mm) headroom clearance. 

2. In Group R-3 occupancies; within dwelling units in 
Group R-2 occupancies; and in Group U occupancies 
that are accessory to a Group R-3 occupancy or acces- 
sory to individual dwelling units in Group R-2 occu- 
pancies; where the nosings of treads at the side of a 
flight extend under the edge of a floor opening 
through which the stairpasses, the floor opening shall 
be allowed to project horizontally into the required 
headroom a maximum of 4 3 / 4 inches (121 mm). 

1009.3 Walkline. The walkline across winder treads shall be 
concentric to the direction of travel through the turn and 
located 12 inches (305 mm) from the side where the winders 
are narrower. The 12-inch (305 mm) dimension shall be mea- 
sured from the widest point of the clear sta/rwidth at the walk- 
ing surface of the winder. If winders are adjacent within the 
flight, the point of the widest clear stair width of the adjacent 
winders shall be used. 

1009.4 Stair treads and risers. Stair treads and risers shall 
comply with Sections 1009.4.1 through 1009.4.5. 

1009.4.1 Dimension reference surfaces. For the purpose 
of this section, all dimensions are exclusive of carpets, rugs 
or runners. 

1009.4.2 Riser height and tread depth. Stair riser heights 
shall be 7 inches (178 mm) maximum and 4 inches (102 
mm) minimum. The riser height shall be measured verti- 
cally between the leading edges of adjacent treads. Rectan- 
gular tread depths shall be 11 inches (279 mm) minimum 
measured horizontally between the vertical planes of the 
foremost projection of adjacent treads and at a right angle to 
the tread's leading edge. Winder treads shall have a mini- 



230 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



mum tread depth of 11 inches (279 mm) measured between 
the vertical planes of the foremost projection of adjacent 
treads at the intersections with the walkline and a minimum 
tread depth of 10 inches (254 mm) within the clear width of 
the stair. 

Exceptions: 

1. Alternating tread devices in accordance with Sec- 
tion 1009.10. 

2. Ship ladders in accordance with Section 1009. 1 1 . 

3. Spiral stairways in accordance with Section 
1009.9. 

4. Aisle stairs in assembly seating areas where the 
stairpitch or slope is set, for sightline reasons, by 
the slope of the adjacent seating area in accordance 
with Section 1028.11.2. 

5. In Group R-3 occupancies; within dwelling units 
in Group R-2 occupancies; and in Group U occu- 
pancies that are accessory to a Group R-3 occu- 
pancy or accessory to individual dwelling units in 
Group R-2 occupancies; the maximum riser height 
shall be 7 3 / 4 inches (197 mm); the minimum tread 
depth shall be 10 inches (254 mm); the minimum 
winder tread depth at the walkline shall be 10 
inches (254 mm); and the minimum winder 'tread 
depth shall be 6 inches (152 mm) . A nosingnot less 
than 3/ 4 inch (19.1 mm) but not more than 1V 4 
inches (32 mm) shall be provided on stairways 
with solid risers where the tread depth is less than 
11 inches (279 mm). 

6. See Section 3404.1 for the replacement of existing 
stairways. 

7. In Group 1-3 facilities, stairways providing access 
to guard towers, observation stations and control 
rooms, not more than 250 square feet (23 m 2 ) in 
area, shall be permitted to have a maximum riser 
height of 8 inches (203 mm) and a minimum tread 
depth of 9 inches (229 mm). 

1009.4.3 Winder treads. Winder treads are not permitted in 
means of egress stairways except within a dwelling unit. 

Exceptions: 

1. Curved stairways in accordance with Section 
1009.8. 

2. Spiral stairways in accordance with Section 
1009.9. 

1009.4.4 Dimensional uniformity. Stair treads and risers 
shall be of uniform size and shape. The tolerance between 
the largest and smallest riser height or between the largest 
and smallest tread depth shall not exceed 3/ 8 inch (9.5 mm) in 
any flight of stairs. The greatest winder tread depth at the 
walkline within any flight of stairs shall not exceed the 
smallest by more than 3/ 8 inch (9.5 mm). 

Exceptions: 

1. Nonuniform riser dimensions of aisle stairs com- 
plying with Section 1028.11.2. 



2. Consistently shaped winders, complying with 
Section 1009.4.2, differing from rectangular 
treads in the same stairway flight. 

Where the bottom or top riser adjoins a sloping public 
way, walkway or driveway having an established grade and 
serving as a landing, the bottom or top riser is permitted to 
be reduced along the slope to less than 4 inches (102 mm) in 
height, with the variation in height of the bottom or top riser 
not to exceed one unit vertical in 12 units horizontal (8-per- 
cent slope) of st airway width. The nosings or leading edges 
of treads at such nonuniform height risers shall have a dis- 
tinctive marking stripe, different from any other nosing 
marking provided on the stair flight. The distinctive mark- 
ing stripe shall be visible in descent of the stair and shall 
have a slip-resistant surface. Marking stripes shall have a 
width of at least 1 inch (25 mm) but not more than 2 inches 
(51 mm). 

1009.4.5 Profile. The radius of curvature at the leading edge 
of the tread shall be not greater than 9/ 16 inch (14.3 mm). 
Beveling of nosings shall not exceed 9/ 16 inch (14.3 mm). 
Risers shall be solid and vertical or sloped under the tread 
above from the underside of the nosingabove at an angle not 
more than 30 degrees (0.52 rad) from the vertical. The lead- 
ing edge (nosings) of treads shall project not more than 1V 4 
inches (32 mm) beyond the tread below and all projections 
of the leading edges shall be of uniform size, including the 
leading edge of the floor at the top of a flight. 

Exceptions: 

1. Solid risers are not required for stairways that are 
not required to comply with Section 1007.3, pro- 
vided that the opening between treads does not 
permit the passage of a sphere with a diameter of 4 
inches (102 mm). 

2. Solid risers are not required for occupancies in 
Group 1-3 or in Group F, Hand S occupancies 
other than areas accessible to the public. There are 
no restrictions on the size of the opening in the 
riser. 

3. Solid risers are not required for spiral stairways 
constructed in accordance with Section 1009.9. 

4. Solid risers are not required for alternating tread 
devices constructed in accordance with Section 
1009.10. 

1009.5 Stairway landings. There shall be a floor or landing at 
the top and bottom of each stairway. The width of landings 
shall not be less than the width of stairways they serve. Every 
landing shall have a minimum dimension measured in the 
direction of travel equal to the width of the stairway. Such 
dimension need not exceed 48 inches (1219 mm) where the 
stairwayhas a straight run. Doors opening onto a landing shall 
not reduce the landing to less than one-half the required width. 
When fully open, the door shall not project more than 7 inches 
(178 mm) into a landing. When wheelchair spaces are required 
on the stairway landing in accordance with Section 1007.6.1, 
the wheelchair space shall not be located in the required width 



2009 INTERNATIONAL BUILDING CODE® 



231 



MEANS OF EGRESS 



I 



I 



of the landing and doors shall not swing over the wheelchair 
spaces. 

Exception: Aisle stairs complying with Section 1028. 

1009.6 Stairway construction. All stairways shall be built of 
materials consistent with the types permitted for the type of 
construction of the building, except that wood handrails shall 
be permitted for all types of construction. 

1009.6.1 Stairway walking surface. The walking surface 
of treads and landings of a stairway shall not be sloped 
steeper than one unit vertical in 48 units horizontal (2-per- 
cent slope) in any direction. Stairway treads and landings 
shall have a solid surface. Finish floor surfaces shall be 
securely attached. 

Exceptions: 

1. Openings in stair walking surfaces shall be a size 
that does not permit the passage of i/ 2 -inch-diame- 
ter (12.7 mm) sphere. Elongated opening shall be 
placed so that the long dimension is perpendicular 
to the direction of travel. 

2. In Group F, Hand S occupancies, other than areas 
of parking structures accessible to the public, 
openings in treads and landings shall not be pro- 
hibited provided a sphere with a diameter of P/ 8 
inches (29 mm) cannot pass through the opening. 

1009.6.2 Outdoor conditions. Outdoor stairways and out- 
door approaches to stairways shall be designed so that water 
will not accumulate on walking surfaces. 

1009.6.3 Enclosures under stairways. The walls and soffits 
within enclosed usable spaces under enclosed and unen- 
closed stairways shall be protected by I-hour fire-resis- 
tance-rated construction or the fire-resistance rating of the 
stairway enclosure, whichever is greater. Access to the 
enclosed space shall not be directly from within the stair 
enclosure. 

Exception: Spaces under stairways serving and con- 
tained within a single residential dwelling unit in Group 
R-2 or R-3 shall be permitted to be protected on the 
enclosed side with i/ 2 -inch (12.7 mm) gypsum board. 

There shall be no enclosed usable space under exterior 
exit stairways unless the space is completely enclosed in 
I-hour fire-resistance-rated construction. The open space 
under exterior stairways shall not be used for any purpose. 

1009.7 Vertical rise. A flight of stairs shall not have a vertical 
rise greater than 12 feet (3658 mm) between floor levels or 
landings. 

Exceptions: 

1. Aisle stairs complying with Section 1028. 

2. Alternating tread devices used as a means of egress 
shall not have a rise greater than 20 feet (6096 mm) 
between floor levels or landings. 

1009.8 Curved stairways. Curved stairways with winder 
treads shall have treads and risers in accordance with Section 



1009.4 and the smallest radius shall not be less than twice the 
required width of the stairway. 

Exception: The radius restriction shall not apply to curved 
stairways fox occupancies in Group R-3 and within individ- 
ual dwelling units in occupancies in Group R-2 . 

1009.9 Spiral stairways. Spiral stairways are permitted to be 
used as a component in the means of egress only within dwell- 
ing units or from a space not more than 250 square feet (23 m 2 ) 
in area and serving not more than five occupants, or from gal- 
leries, catwalks and gridirons in accordance with Section 
1015.6. 

A spiral stairway shall have a 7 1 / 2 -inch (191 mm) minimum 
clear tread depth at a point 12 inches (305 mm) from the narrow 
edge. The risers shall be sufficient to provide a headroom of 78 
inches (1981 mm) minimum, but riser height shall not be more 
than 9 7 / 2 inches (241 mm). The minimum stairway clear width 
at and below the handrail shall be 26 inches (660 mm) . 

1009.10 Alternating tread devices. Alternating tread devices 
are limited to an element of a means of egress in buildings of 
Groups F, Hand S from a mezzanine not more than 250 square 
feet (23 m 2 ) in area and which serves not more than five occu- 
pants; in buildings of Group 1-3 from a guard tower, observa- 
tion station or control room not more than 250 square feet (23 
m 2 ) in area and for access to unoccupied roofs. 

1009.10.1 Handrails of alternating tread devices. Hand- 
rails shall be provided on both sides of alternating tread 
devices and shall comply with Section 1012. 

1009.10.2 Treads of alternating tread devices. Alternat- 
ing tread devices shall have a minimum projected tread of 5 
inches (127 mm), a minimum tread depth of8 1 / 2 inches (216 
mm), a minimum tread width of 7 inches (178 mm) and a 
maximum riser height of 9h 2 inches (241 mm). The pro- 
jected tread depth shall be measured horizontally between 
the vertical planes of the foremost projections of adjacent 
treads. The riser height shall be measured vertically 
between the leading edges of adjacent treads. The combina- 
tion of riser height and projected tread depth provided shall 
result in an alternating tread device angle that complies with 
Section 1002. The initial tread of the device shall begin at 
the same elevation as the platform, landing or floor surface. 

Exception: Alternating tread devices used as an element 
of a means of egress in buildings from a mezzanine area 
not more than 250 square feet (23 m 2 ) in area which 
serves not more than five occupants shall have a mini- 
mum projected tread of : 8 1 / 2 inches (216 mm) with a mini- 
mum tread depth of 10 1 \ inches (267 mm). The rise to 
the next alternating tread surface should not be more than 
8 inches (203 mm). 

1009.11 Ship ladders. Ship ladders are permitted to be used in 
Group 1-3 as a component of ameans ofegress to and from con- 
trol rooms or elevated facility observation stations not more 
than 250 square feet (23 m 2 ) with not more than three occu- 
pants and for access to unoccupied roofs. 

Ship ladders shall have a minimum tread depth of 5 inches 
(127 mm). The tread shall be projected such that the total of the 



232 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



I 



1 



tread depth plus the nosingprojection is no less than 8 V 2 inches 
(216 mm). The maximum riser height shall be 9 V 2 inches (241 
mm). 

Handrails shall be provided on both sides of ship ladders. 
The minimum clear width at and below the handrails shall be 
20 inches (508 mm). 

1009.12 Handrails. Stairways shall have handrails on each 
side and shall comply with Section 1012. Where glass is used 
to provide the handrail, the handrail shall also comply with 
Section 2407. 

Exceptions: 

1. Handrails for aisle stairs are not required where permit- 
ted by Section 1028.13. 

2. Stairways within dwelling units, spiral stairways and 
aisle stairs serving seating only on one side are permitted 
to have a handrail on one side only. 

3. Decks, patios and walkways that have a single change in 
elevation where the landing depth on each side of the 
change of elevation is greater than what is required for a 
landing do not require handrails. 

4. In Group R-3 occupancies, a change in elevation consist- 
ing of a single riser at an entrance or egress door does not 
require handrails. 

Changes in room elevations of three or fewer risers 
within dwelling units and sleeping units in Group R-2 
and R-3 do not require handrails. 

1009.13 Stairway to roof. In buildings four or more stories 
above grade plane, one stairway shall extend to the roof sur- 
face, unless the roof has a slope steeper than four units vertical 
in 12 units horizontal (33-percent slope). In buildings without 
an occupied roof, access to the roof from the top story shall be 
permitted to be by an alternating tread device. 

1009.13.1 Roof access. Where a stairway is provided to a 
roof, access to the roof shall be provided through a pent- 
house complying with Section 1509.2. 

Exception: In buildings without an occupied roof, 
access to the roof shall be permitted to be a roof hatch or 
trap door not less than 16 square feet (1.5 m 2 ) in area and 
having a minimum dimension of 2 feet (610 mm). 

1009.13.2 Protection at roof hatch openings. Where the 
roof hatch opening providing the required access is located 
within 10 feet (3049 mm) of the roof edge, such roof access 
or roof edge shall be protected by guards installed in accor- 
dance with the provisions of Section 1013. 

1009.14 Stairway to elevator equipment. Roofs and pent- 
houses containing elevator equipment that must be accessed 
for maintenance are required to be accessed by a stairway. 



SECTION 1010 
RAMPS 

1010.1 Scope. The provisions of this section shall apply to 
ramps used as a component of a means of egress. 

Exceptions: 

1. Other than ramps that are part of the accessible routes 
providing access in accordance with Sections 1108.2 
through 1108.2.4 and 1108.2.6, ramped a isles within 
assembly rooms or spaces shall conform with the pro- 
visions in Section 1028.11. 

2. Curb ramps shall comply with ICC A117.1. 

3. Vehicle ramps in parking garages for pedestrian exit 
access shall not be required to comply with Sections 
1010.3 through 1010.9 when they are not an accessi- 
ble route serving accessible parking spaces, other 
required accessible elements or part of an accessible 
means of egress. 

1010.2 Slope. Ramps used as part of a means of egress shall 
have a running slope not steeper than one unit vertical in 12 
units horizontal (8-percent slope). The slope of other pedes- 
trian ramps shall not be steeper than one unit vertical in eight 
units horizontal (12.5-percent slope). 

Exception: Aisle ramp slope in occupancies of Group A or 
assembly occupancies accessory to Group E occupancies 
shall comply with Section 1028.11. 

1010.3 Cross slope. The slope measured perpendicular to the 
direction of travel of a ramp shall not be steeper than one unit 
vertical in 48 units horizontal (2-percent slope). 

1010.4 Vertical rise. The rise for any ramp run shall be 30 
inches (762 mm) maximum. 

1010.5 Minimum dimensions. The minimum dimensions of 
means of egress ramps shall comply with Sections 1010.5.1 
through 1010.5.3. 

1010.5.1 Width. The minimum width of a means of egress 
ramp shall not be less than that required for corridors by 
Section 1018.2. The clear width of a ramp between hand- 
rails, if provided, or other permissible projections shall be 
36 inches (914 mm) minimum. 

1010.5.2 Headroom. The minimum headroom in all parts 
of the means of egress ramp shall not be less than 80 inches 
(2032 mm). 

1010.5.3 Restrictions. Means of egress ramps shall not 
reduce in width in the direction of egress travel. Projections 
into the required ramp and landing width are prohibited. 
Doors opening onto a landing shall not reduce the clear 
width to less than 42 inches (1067 mm). 

1010.6 Landings. Ramps shall have landings at the bottom and 
top of each ramp, points of turning, entrance, exits and at doors. 
Landings shall comply with Sections 1010.6.1 through 
1010.6.5. 



2009 INTERNATIONAL BUILDING CODE® 



233 



MEANS OF EGRESS 



1010.6. 1 Slope. Landings shall have a slope not steeper than 
one unit vertical in 48 units horizontal (2-percent slope) in 
any direction. Changes in level are not permitted. 

1010.6.2 Width. The landing shall be at least as wide as the 
widest ramp run adjoining the landing. 

1010.6.3 Length. The landing length shall be 60 inches 
(1525 mm) minimum. 

Exceptions: 

1. In Group R-2 and R-3 individual dwelling and 
sleeping units that are not required to be Accessible 
units, Type A units or Type B units in accordance 
with Section 1107, landings are permitted to be 36 
inches (914 mm) minimum. 

2. Where the ramp is not a part of an accessible route, 
the length of the landing shall not be required to be 
more than 48 inches (1220 mm) in the direction of 
travel. 

1010.6.4 Change in direction. Where changes in direction 
of travel occur at landings provided between ramp runs, the 
landing shall be 60 inches by 60 inches (1524 mm by 1524 
mm) minimum. 

Exception: In Group R-2 and R-3 individual dwelling or 
sleeping units that are not required to be Accessible units, 
Type A units or Type B units in accordance with Section 
1 107, landings are permitted to be 36 inches by 36 inches 
(914 mm by 914 mm) minimum. 

1010.6.5 Doorways. Where doorways are located adjacent 
to a ramp landing, maneuvering clearances required by ICC 
A 117.1 are permitted to overlap the required landing area. 

1010.7 Ramp construction. All ramps shall be built of materi- 
als consistent with the types permitted for the type of construc- 
tion of the building, except that wood handrails shall be 
permitted for all types of construction. Ramps used as an exit 
shall conform to the applicable requirements of Sections 
1022.1 through 1022.6 for exit enclosures. 

1010.7.1 Ramp surface. The surface of ramps shall be of 
slip-resistant materials that are securely attached. 

1010.7.2 Outdoor conditions. Outdoor ramps and outdoor 
approaches to ramps shall be designed so that water will not 
accumulate on walking surfaces. 

1010.8 Handrails. Ramps with a rise greater than 6 inches 
(152 mm) shall have handrails on both sides. Handrails shall 
comply with Section 1012. 

Exception: Handrails for ramped aisles are not required 
where permitted by Section 1028.13. 

1010.9 Edge protection. Edge protection complying with Sec- 
tion 1010.9.1 or 1010.9.2 shall be provided on each side of 
ramp runs and at each side of ramp landings. 

Exceptions: 

1. Edge protection is not required on ramps that are not 
required to have handrails, provided they have flared 
sides that comply with the ICC All 7.1 curb ramp 
provisions. 



2. Edge protection is not required on the sides of ramp 
landings serving an adjoining ramp run or stairway. 

3. Edge protection is not required on the sides of ramp 
landings having a vertical drop off of not more than i/ 2 
inch (12.7 mm) within 10 inches (254 mm) horizon- 
tally of the required landing area. 

4. In assembly spaces with fixed seating, edge proteC- 1 
tion is not required on the sides of ramps where the 
ramps provide access to the adjacent seating and aisle 
accessways. 

1010.9.1 Curb, rail, wall or barrier. A curb, rail, wall or 
barrier shall be provided to serve as edge protection. A curb 
must be a minimum of 4 inches (102 mm) in height. Barriers 
must be constructed so that the barrier prevents the passage 
of a 4-inch-diameter (102 mm) sphere, where any portion of 
the sphere is within 4 inches (102 mm) of the floor or ground 
surface. 

1010.9.2 Extended floor or ground surface. The floor or 
ground surface of the ramp run or landing shall extend 12 
inches (305 mm) minimum beyond the inside face of a 
handrail complying with Section 1012. 

1010.10 Guards. Guards shall be provided where required by 
Section 1013 and shall be constructed in accordance with Sec- 
tion 1013. 



SECTION 1011 
EXIT SIGNS 

1011.1 Where required. Exits and exit access doors shall be 
marked by an approved exit sign readily visible from any direc- 
tion of egress travel. The path of egress travel to exits and 
within exits shall be marked by readily visible exit signs to 
clearly indicate the direction of egress travel in cases where the 
exit or the path of egress travel is not immediately visible to the 
occupants. Intervening means of egress doors within exits shall 
be marked by exit signs. Exit sign placement shall be such that 
no point in an exit access corridor ox exit passageway is more 
than 100 feet (30 480 mm) or the listedvizv/ing distance for the 
sign, whichever is less, from the nearest visible exit sign. 

Exceptions: 

1. Exit signs are not required in rooms or areas that 
require only one exit or exit access. 

2. Main exterior exit doors or gates that are obviously 
and clearly identifiable as exits need not have exit 
signs where approvedby the bUilding official. 

3. Exitsigns are not required in occupancies in Group U 
and individual sleeping units or dwelling units in 
Group R-l, R-2 or R-3. 

4. Exit signs are not required in dayrooms, sleeping 
rooms or dormitories in occupancies in Group 1-3. 

5. In occupancies in Groups A-4 and A-5, exit signs are 
not required on the seating side of vomitories or open- 
ings into seating areas where exitsigns are provided in 
the concourse that are readily apparent from the 
vomitories. Egress lighting is provided to identify 



234 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



each vomitory or opening within the seating area in an 
emergency. 

1011.2 Illumination. Exit signs shall be internally or exter- 
nally illuminated. 

Exception: Tactile signs required by Section 1011.3 need 
not be provided with illumination. 

101 1.3 Tactile exit signs. A tactile sign stating EXIT and com- 
plying with ICC All 7.1 shall be provided adjacent to each 
door to an area ofrefuge, an exterior area for assisted rescue, an 
exit stairway, an exit ramp, an exitpassageway and the exit dis- 
charge. 

1011.4 Internally illuminated exit signs. Electrically pow- 
ered, self-luminous and photolumine scent exit signs shall be 
listed and labeled in accordance with UL 924 and shall be 
installed in accordance with the manufacturer's instructions 
and Chapter 27. Exit signs shall be illuminated at all times. 

1011.5 Externally illuminated exit signs. Externally illumi- 
nated exit signs shall comply with Sections 1011.5.1 through 
1011.5.3. 

1011.5.1 Graphics. Every exitsign and directional exitsign 
shall have plainly legible letters not less than 6 inches (152 
mm) high with the principal strokes of the letters not less 
than 3/ 4 inch (19.1 mm) wide. The word "EXIT" shall have 
letters having a width not less than 2 inches (51 mm) wide, 
except the letter "I," and the minimum spacing between let- 
ters shall not be less than 3/ 8 inch (9.5 mm). Signs larger than 
the minimum established in this section shall have letter 
widths, strokes and spacing in proportion to their height. 

The word "EXIT" shall be in high contrast with the back- 
ground and shall be clearly discernible when the means of 
exit sign illumination is or is not energized. If a chevron 
directional indicator is provided as part of the exitsign, the 
construction shall be such that the direction of the chevron 
directional indicator cannot be readily changed. 

1011.5.2 Exit sign illumination. The face of an exitsign 
illuminated from an external source shall have an intensity 
of not less than 5 foot-candles (54 lux). 

101 1.5.3 Power source. Exitsigns shall be illuminated at all 
times. To ensure continued illumination for a duration of not 
less than 90 minutes in case of primary power loss, the sign 
illumination means shall be connected to an emergency 
power system provided from storage batteries, unit equip- 
ment or an on-site generator. The installation of the emer- 
gency power system shall be in accordance with Chapter 27. 

Exception: Approved exit sign illumination means that 
provide continuous illumination independent of external 
power sources for a duration of not less than 90 minutes, 
in case of primary power loss, are not required to be con- 
nected to an emergency electrical system. 



SECTION 1012 
HANDRAILS 

1012.1 Where required. Handrails for stairways and ramps 
shall be adequate in strength and attachment in accordance 
with Section 1607.7. Handrails required for stairways by Sec- 



tion 1009.12 shall comply with Sections 1012.2 through 
1012.9. Handrails required for ramps by Section 1010.8 shall 
comply with Sections 1012.2 through 1012.8. 

1012.2 Height. Handrail height, measured above stair tread 
nosings, or finish surface of ramp slope, shall be uniform, not 
less than 34 inches (864 mm) and not more than 38 inches (965 
mm). Handrail height of alternating tread devices and ship 
ladders, measured above tread nosings, shall be uniform, not 
less than 30 inches (762 mm) and not more than 34 inches (864 
mm). 

1012.3 Handrail graspability. All required handrails shall 
comply with Section 1012.3.1 or shall provide equivalent 
graspability. 

Exception: In Group R-3 occupancies; within dwelling 
units in Group R-2 occupancies; and in Group U occupan- 
cies that are accessory to a Group R-3 occupancy or acces- 
sory to individual dwelling units in Group R-2 occupancies; 
handrails shall be Type I in accordance with Section 
1012.3.1, Type II in accordance with Section 1012.3.2 or 
shall provide equivalent graspability. 

1012.3.1 Type I. Handrails with a circular cross section 
shall have an outside diameter of at least IV4 inches (32 mm) 
and not greater than 2 inches (51 mm). If the handrail is not 
circular, it shall have a perimeter dimension of at least 4 
inches (102 mm) and not greater than 6V 4 inches (160 mm) 
with a maximum cross-section dimension of 2V 4 inches (57 
mm). Edges shall have a minimum radius of 0.01 inch (0.25 
mm). 

1012.3.2 Type II. Handrails with a perimeter greater than 
6 V 4 inches (160 mm) shall provide a graspable finger recess 
area on both sides of the profile. The finger recess shall 
begin within a distance of 3/ 4 inch (19 mm) measured verti- 
cally from the tallest portion of the profile and achieve a 
depth of at least 5/ 16 inch (8 mm) within 7/ 8 inch (22 mm) 
below the widest portion of the profile. This required depth 
shall continue for at least 3/ 8 inch (10 mm) to a level that is 
not less than l 3 /4 inches (45 mm) below the tallest portion of 
the profile. The minimum width of the handrail above the 
recess shall be IV4 inches (32 mm) to a maximum of 2 3 / 4 
inches (70 mm). Edges shall have a minimum radius of 0.01 
inch (0.25 mm). 

1012.4 Continuity. Handrail- gripping surfaces shall be con- 
tinuous, without interruption by newel posts or other obstruc- 
tions. 

Exceptions: 

1. Handrails within dwelling units are permitted to be 
interrupted by a newel post at a turn or landing. 

2. Within a dwelling unit, the use of a volute, turnout, 
starting easing or starting newel is allowed over the 
lowest tread. 

3. Handrail brackets or balusters attached to the bottom 
surface of the handrail that do not project horizon- 
tally beyond the sides of the handrail within 1V 2 
inches (38 mm) of the bottom of the handrailshaW not 
be considered obstructions. For each i/ 2 inch (12.7 
mm) of additional handrail perimeter dimension 



2009 INTERNATIONAL BUILDING CODE® 



235 



MEANS OF EGRESS 



above 4 inches (102 mm), the vertical clearance 
dimension of 1 h 2 inches (38 mm) shall be permitted to 
be reduced by i/ s inch (3 mm). 

4. Where handrails are provided along walking surfaces 
with slopes not steeper than 1:20, the bottoms of the 
handrail gripping surfaces shall be permitted to be 
obstructed along their entire length where they are 
integral to crash rails or bumper guards. 

1012.5 Fittings. Handrails shall not rotate within their fittings. 

1012.6 Handrail extensions. Handrails shall return to a wall, 
guardor the walking surface or shall be continuous to the hand- 
rail of an adjacent stair flight or ramp run. Where handrails are 
not continuous between flights, the handrails shall extend hori- 
zontally at least 12 inches (305 mm) beyond the top riser and 
continue to slope for the depth of one tread beyond the bottom 
riser. At ramps where handrails are not continuous between 
runs, the handrails shall extend horizontally above the landing 
12 inches (305 mm) minimum beyond the top and bottom of 
ramp runs. The extensions of handrails shall be in the same 
direction of the stair flights at stairways and the ramp runs at 
ramps. 

Exceptions: 

1. Handrails within a dwelling unit that is not required 
to be accessible need extend only from the top riser to 
the bottom riser. 

2. Aisle handrails in Group A and E occupancies in 
accordance with Section 1028.13. 

3. Handrails for alternating tread devices and ship lad- 
ders are permitted to terminate at a location vertically 
above the top and bottom risers. Handrails for alter- 
nating tread devices and ship ladders are not required 
to be continuous between flights or to extend beyond 
the top or bottom risers. 

1012.7 Clearance. Clear space between a handrail and a wall 
or other surface shall be a minimum of 1V 2 inches (38 mm). A 
handrail mid. a wall or other surface adjacent to the handrail 
shall be free of any sharp or abrasive elements. 

1012.8 Projections. On ramps, the clear width between hand- 
rails shall be 36 inches (914 mm) minimum. Projections into 
the required width of stairways and ramps at each handrail 
shall not exceed 4 ! / 2 inches (114 mm) at or below the handrail 
height. Proj ections into the required width shall not be limited 
above the minimum headroom height required in Section 
1009.2. 

1012.9 Intermediate handrails. Stairways shall have inter- 
mediate handrails located in such a manner that all portions of 
the stairway width required for egress capacity are within 30 
inches (762 mm) of a handrail. On monumental stairs, hand- 
rails shall be located along the most direct path of egress travel. 



ment platforms, stairs, ramps and landings that are located 
more than 30 inches (762 mm) measured vertically to the floor 
or grade below at any point within 36 inches (914 mm) hori- 
zontally to the edge of the open side. Guards shall be adequate 
in strength and attachment in accordance with Section 1607.7. 

Exception: Guards are not required for the following loca- 
tions: 

1. On the loading side of loading docks or piers. 

2. On the audience side of stages and raised platforms, 
including steps leading up to the stage and raised plat- 
forms. 

3. On raised stage and platform floor areas, such as run- 
ways, ramps and side stages used for entertainment or 
presentations. 

4. At vertical openings in the performance area of stages 
and platforms. 

5. At elevated walking surfaces appurtenant to stages 
and platforms for access to and utilization of special 
lighting or equipment. 

6. Along vehicle service pits not accessible to the public. 

7. In assembly seating where guards in accordance with 
Section 1028.14 are permitted and provided. 

1013.1.1 Glazing. Where glass is used to provide a guardor 
as a portion of the guardsystem, the guardshall also comply 
with Section 2407. Where the glazing provided does not 
meet the strength and attachment requirements of Section 
1607.7, complying guards shall also be located along 
glazed sides of open-sided walking surfaces. 

1013.2 Height. Required guards shall be not less than 42 
inches (1067 mm) high, measured vertically above the adjacent 
walking surfaces, adjacent fixed seating or the line connecting 
the leading edges of the treads. 

Exceptions: 



1. For occupancies in Group R-3, and within individual 
dwelling units in occupancies in Group R-2, guards 
on the open sides of stairs shall have a height not less 
than 34 inches (864 mm) measured vertically from a 
line connecting the leading edges of the treads. 



1 



SECTION 1013 
GUARDS 

1013.1 Where required. Guards shall be located along 
open- sided walking surfaces, including mezzanines, equip- 



2. For occupancies in Group R-3, and within individual 
dwelling units in occupancies in Group R-2, where 
the top of the guard also serves as a handrail on the 
open sides of stairs, the top of the guard shall not be 
less than 34 inches (864 mm) and not more than 38 
inches (965 mm) measured vertically from a line con- 
necting the leading edges of the treads. 

3. The height in assembly seating areas shall be in accor- 
dance with Section 1028.14. 

4. Along alternating tread devices and ship ladders, 
guards whose top rail also serves as a handrail, shall 
have height not less than 30 inches (762 mm) and not 
more than 34 inches (864 mm), measured vertically 
from the leading edge of the device tread nosing. 



236 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



1013.3 Opening limitations. Required guards shall not have 
openings which allow passage of a sphere 4 inches (102 mm) in 
diameter from the walking surface to the required guardheight. 

Exceptions: 

1. From a height of 36 inches (914 mm) to 42 inches 
(1067 mm), guards shall not have openings which 
allow passage of a sphere 4 3 / 8 inches (111 mm) in 
diameter. 

2. The triangular openings at the open sides of a stair, 
formed by the riser, tread and bottom rail shall not 
allow passage of a sphere 6 inches (152 mm) in diam- 
eter. 

3. At elevated walking surfaces for access to and use of 
electrical, mechanical or plumbing systems or equip- 
ment, guards shall not have openings which allow 
passage of a sphere 21 inches (533 mm) in diameter. 

4. In areas that are not open to the public within occu- 
pancies in Group 1-3, F, H or S, and for alternating 
tread devices and ship ladders, guards shall not have 
openings which allow passage of a sphere 21 inches 
(533 mm) in diameter. 

5. In assembly seating areas, guards at the end of aisles 
where they terminate at a fascia of boxes, balconies 
and galleries shall not have openings which allow 
passage of a sphere 4 inches in diameter (102 mm) up 
to a height of 26 inches (660 mm) . From a height of 26 
inches (660 mm) to 42 inches (1067 mm) above the 
adjacent walking surfaces, guards shall not have 
openings which allow passage of a sphere 8 inches 
(203 mm) in diameter. 

6. Within individual dwelling units and sleeping units in 
Group R-2 and R-3 occupancies, guards on the open 
sides of stairs shall not have openings which allow 
passage of a sphere 4 3 / 8 (111 mm) inches in diameter. 

1013.4 Screen porches. Porches and decks which are enclosed 
with insect screening shall be provided with guards where the 
walking surface is located more than 30 inches (762 mm) above 
the floor or grade below. 

1013.5 Mechanical equipment. Guards shall be provided 
where appliances, equipment, fans, roof hatch openings or 
other components that require service are located within 10 feet 
(3048 mm) of a roof edge or open side of a walking surface and 
such edge or open side is located more than 30 inches (762 mm) 
above the floor, roof or grade below. The guard shall be con- 
structed so as to prevent the passage of a sphere 21 inches (533 
mm) in diameter. The guardshall extend not less than 30 inches 
(762 mm) beyond each end of such appliance, equipment, fan 
or component. 

1013.6 Roof access. Guards shall be provided where the roof 
hatch opening is located within 10 feet (3048 mm) of a roof 
edge or open side of a walking surface and such edge or open 
side is located more than 30 inches (762 mm) above the floor, 
roof or grade below. The guard shall be constructed so as to 



prevent the passage of a sphere 21 inches (533 mm) in diame- 
ter. 



SECTION 1014 
EXIT ACCESS 

1014. 1 General. The exit access shall comply with the apPlica- 1 
ble provisions of Sections 1003 through 1013. Exit access 
arrangement shall comply with Sections 1014 through 1019. 

1014.2 Egress through intervening spaces. Egress through 
intervening spaces shall comply with this section. 

1. Egress from a room or space shall not pass through 
adjoining or intervening rooms or areas, except where 
such adjoining rooms or areas and the area served are 
accessory to one or the other, are not a Group H occu- 
pancy and provide a discernible path of egress travel to 
an exit. 

Exception: Means of egress are not prohibited 
through adjoining or intervening rooms or spaces in a 
Group H, S or F occupancy when the adjoining or 
intervening rooms or spaces are the same or a lesser 
hazard occupancy group. 

2. An exit access shall not pass through a room that can be 
locked to prevent egress. 

3. Means of egress from dwelling units or sleeping areas 
shall not lead through other sleeping areas, toilet rooms 
or bathrooms. 

4. Egress shall not pass through kitchens, storage rooms, 
closets or spaces used for similar purposes. 

Exceptions: 

1. Means of egress are not prohibited through a 
kitchen area serving adjoining rooms constitut- 
ing part of the same dwelling unit or sleeping 
unit. 

2. Means of egress are not prohibited through 
stockrooms in Group M occupancies when all 
of the following are met: 

2.1. The stock is of the same hazard classifi- 
cation as that found in the main retail 
area; 

2.2. Not more than 50 percent of the exit 
access is through the stockroom; 

2.3. The stockroom is not subject to locking 
from the egress side; and 

2.4. There is a demarcated, minimum 
44-inch-wide (1118 mm) aisle defined 
by full- or partial-height fixed walls or 
similar construction that will maintain 
the required width and lead directly 
from the retail area to the exit without 
obstructions. 



2009 INTERNATIONAL BUILDING CODE® 



237 



MEANS OF EGRESS 



1014.2.1 Multiple tenants. Where more than one tenant 
occupies anyone floor of a building or structure, each tenant 
space, dwelling unit and sleeping unit shall be provided with 
access to the required exits without passing through adja- 
cent tenant spaces, dwelling units and sleeping units. 

Exception: The means of egress from a smaller tenant 
space shall not be prohibited from passing through a 
larger adjoining tenant space where such rooms or 
spaces of the smaller tenant occupy less than 10 percent 
of the area of the larger tenant space through which they 
pass; are the same or similar occupancy group; a 
discernable path of egress travel to an exit is provided; 
and the means of egress into the adjoining space is not 
subject to locking from the egress side. A required means 
of egress serving the larger tenant space shall not pass 
through the smaller tenant space or spaces. 

1014.2.2 Group 1-2. Habitable rooms or suites in Group 1-2 
occupancies shall have an exit access door leading directly 
to a corridor. 

Exception: Rooms with exit doors opening directly to 
the outside at ground level. 

1014.2.3 Suites in patient sleeping areas. Patient sleeping 
areas in Group 1-2 occupancies shall be permitted to be 
divided into suites with one intervening room if one of the 
following conditions is met: 

1. The intervening room within the suite is not used as an 
exit access for more than eight patient beds. 

2. The arrangement of the suite allows for direct and 
constant visual supervision by nursing personnel. 

1014.2.3.1 Area. Suites of sleeping rooms shall not 
exceed 5,000 square feet (465 m 2 ). 

1014.2.3.2 Exit access. Any patient sleeping room, or 
any suite that includes patient sleeping rooms, of more 
than 1,000 square feet (93 m 2 ) shall have at least two exit 
access doors remotely located from each other. 

1014.2.3.3 Travel distance. The travel distance between 
any point in a suite of sleeping rooms and an exit access 
door of that suite shall not exceed 100 feet (30 480 mm) . 

1014.2.4 Suites in areas other than patient sleeping 
areas. Areas other than patient sleeping areas in Group 1-2 
occupancies shall be permitted to be divided into suites. 

1014.2.4.1 Area. Suites of rooms, other than patient 
sleeping rooms, shall not exceed 10,000 square feet (929 



the suite to the exit access door is not greater than 100 
feet (30 480 mm). 

1014.2.4.4 Two intervening rooms. For rooms other 
than patient sleeping rooms located within a suite, exit 
access travel from within the suite shall be permitted 
through two intervening rooms where the travel distance 
to the exit access door is not greater than 50 feet (15 240 
mm). 

1014.2.5 Exit access through suites. Exit access from all 
other portions of a building not classified as a suite in a 
Group 1-2 occupancy shall not pass through a suite. 

1014.2.6 Travel distance. The travel distance between any 
point in a Group 1-2 occupancy patient sleeping room and an 
exit access door in that room shall not e. 

1014.2.7 Separation. Suites in Group 1-2 occupancies shall 
be separated from other portions of the building by a smoke 
partition complying with Section 711. 

1014.3 Common path of egress travel. In occupancies other 
than Groups H-l, H-2 and H-3, the common path of egress 
travelshall not exceed 75 feet (22 860 mm). In Group H-l, H-2 
and H-3 occupancies, the common path of egress travel shall 
not exceed 25 feet (7620 mm). For common path of egress 
travel in Group A occupancies and assembly occupancies 
accessory to Group E occupancies having fixed seating, see 
Section 1028.8. 

Exceptions: 

1. The length of a common path of egress travel in 
Group B, F and S occupancies shall not be more than 
100 feet (30 480 mm), provided that the building is 
equipped throughout with an automatic sprinkler sys- 
tem installed in accordance with Section 903.3.1.1 . 

2. Where a tenant space in Group B, Sand U occupan- 
cies has an occupant load of not more than 30, the 
length of a common path of egress travel shall not be 
more than 100 feet (30 480 mm). 

3. The length of a common path of egress travel in a 
Group 1-3 occupancy shall not be more than 100 feet 
(30480 mm). 

4. The length of a common path of egress travel in a 
Group R-2 occupancy shall not be more than 125 feet 
(38 100 mm), provided that the building is protected 
throughout with an approved automatic sprinkler 
system in accordance with Section 903.3.1.1 or 
903.3.1.2. 



1014.2.4.2 Exit access. Any room or suite of rooms, 
other than patient sleeping rooms, of more than 2,500 
square feet (232 m 2 ) shall have at least two exit access 
doors remotely located from each other. 

1014.2.4.3 One intervening room. For rooms other than 
patient sleeping rooms, suites of rooms are permitted to 
have one intervening room if the travel distance within 



SECTION 1015 
EXIT AND EXIT ACCESS DOORWAYS 

1015.1 Exits or exit access doorways from spaces. Two exits 
or exit access doorways from any space shall be provided 
where one of the following conditions exists: 

Exception: Group 1-2 occupancies shall comply with Sec- 
tion 1014.2.2 through 1014.2.7. 



238 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



1. The occupant loadof the space exceeds one of the values 
in Table 1015.1. 

Exception: In Group R-2 and R-3 occupancies, one 
means of egress is permitted within and from individ- 
ual dwelling units with a maximum occupant load of 
20 where the dwelling unit is equipped throughout 
with an automatic sprinkler system in accordance 
with Section 903.3.1.1 or 903.3.1.2. 

2. The common path of egress travel exceeds one of the 
limitations of Section 1014.3. 

3. Where required by Section 1015.3,1015.4,1015.5,1015.6 
or 1015.6.1. 

Where a building contains mixed occupancies, each individ- 
ual occupancy shall comply with the applicable requirements 
for that occupancy. Where applicable, cumulative occupant 
loads from adjacent occupancies shall be considered in accor- 
dance with the provisions of Section 1004.1. 

TABLE 1015.1 
SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY 



OCCUPANCY 


MAXIMUM OCCUPANT LOAD 


A,B, Ea, F, M, U 


49 


H-l, H-2, H-3 


3 


H-4, H-5, 1-1, 1-3, 1-4, R 


10 


S 


29 



a. Day care maximum occupant load is 10. 

1015.1.1 Three or more exits or exit access doorways. 
Three exits or exit access doorways shall be provided from 
any space with an o c cup ant load of 501 to 1,000. Four exits 
or exit access doorways shall be provided from any space 
with an occupant loa d greater than 1,000. 

1015.2 Exit or exit access doorway arrangement. Required 
exits shall be located in a manner that makes their availability 
obvious. Exits shall be unobstructed at all times. Exit and exit 
access doorways shall be arranged in accordance with Sections 
1015.2.1 and 1015.2.2. 

1015.2.1 Two exits or exit access doorways. Where two 
exits or exit access doorways are required from any portion of 
the exit access, the exit doors or exit access doorways shall be 
placed a distance apart equal to not less than one-half of the 
length of the maximum overall diagonal dimension of the 
building or area to be served measured in a straight line 
between exit doors or exit access doorways. Interlocking or 
scissor stairs shall be counted as one exit stairway. 

Exceptions: 

1. Where exit enclosures are provided as a portion 
of the required exit and are interconnected by a 
I-hour fire-resistance-rated corridor conforming 
to the requirements of Section 1018, the required 
exitseparation shall be measured along the short- 
est direct line of travel within the corridor. 

2. Where a building is equipped throughout with an 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1 or 903.3.1.2, the separation distance 



of the exitdoors or exit access doorways shall not be 
less than one-third of the length of the maximum 
overall diagonal dimension of the area served. 

1015.2.2 Three or more exits or exit access doorways. 
Where access to three or more exits is required, at least two 
exit doors or exit access doorways shall be arranged in 
accordance with the provisions of Section 1015.2.1. 

1015.3 Boiler, incinerator and furnace rooms. Two exit 
access doorways are required in boiler, incinerator and furnace 
rooms where the area is over 500 square feet (46 m 2 ) and any 
fuel-fired equipment exceeds 400,000 British thermal units 
(Btu) (422 000 KJ) input capacity. Where two exit access door- 
ways are required, one is permitted to be a fixed ladder or an 
alternating tread device. Exit access doorways shall be sepa- 
rated by a horizontal distance equal to one-half the length of the 
maximum overall diagonal dimension of the room. 

1015.4 Refrigeration machinery rooms. Machinery rooms 
larger than 1,000 square feet (93 m 2 ) shall have not less than 
two exits or exit access doors. Where two exit access doorways 
are required, one such doorway is permitted to be served by a 
fixed ladder or an alternating tread device. Exit access door- 
ways shall be separated by a horizontal distance equal to 
one-half the maximum horizontal dimension of room. 

All portions of machinery rooms shall be within 150 feet (45 
720 mm) of an exitor exit access doorway. An increase in travel 
distance is permitted in accordance with Section 1016.1. 

Doors shall swing in the direction of egress travel, regardless 
of the occupant load served. Doors shall be tight fitting and 
self-closing. 

1015.5 Refrigerated rooms or spaces. Rooms or spaces hav- 
ing a floor area larger than 1,000 square feet (93 m 2 ), contain- 
ing a refrigerant evaporator and maintained at a temperature 
below 68°F (20°C), shall have access to not less than two exits 
or exit access doors. 

Travel distance shall be determined as specified in Section 
1016.1, but all portions of a refrigerated room or space shall be 
within 150 feet (45 720 mm) of an exit or exit access door 
where such rooms are not protected by an approved automatic 
sprinkler system. Egress is allowed through adjoining refriger- 
ated rooms or spaces. 

Exception: Where using refrigerants in quantities limited 
to the amounts based on the volume set forth in the Interna- 
tional Mechanical Code. 

1015.6 Stage means of egress. Where two means of egress are 
required, based on the stage size or occupant load, one means 
of egress shall be provided on each side of the stage. 

1015.6.1 Gallery, gridiron and catwalk means of egress. 
The means of egress from lighting and access catwalks, gal- 
leries and gridirons shall meet the requirements for occu- 
pancies in Group F-2. 

Exceptions: 

1. A minimum width of 22 inches (559 mm) is per- 
mitted for lighting and access catwalks. 

2. Spiral stairs are permitted in the means of egress. 



2009 INTERNATIONAL BUILDING CODE® 



239 



MEANS OF EGRESS 



3. Stairways required by this subsection need not be 
enclosed. 

4. Stairways with a minimum width of 22 inches (559 
mm), ladders or spiral stairs are permitted in the 
means of egress. 

5. A second means of egress is not required from these 
areas where a means of escape to a floor or to a roof 
is provided. Ladders, alternating tread devices or 
spiral stairs are permitted in the means of escape. 

6. Ladders are permitted in the means of egress. 



SECTION 1016 
EXIT ACCESS TRAVEL DISTANCE 

1016.1 Travel distance limitations. Exits shall be so located 
on each story such that the maximum length of exit access 
travel, measured from the most remote point within a story 
along the natural and unobstructed path of egress travel to an 
exterior exit door at the level of exit discharge, an entrance to a 
vertical exit enclosure, an exitpassageway, a horizontal exit, an 
exterior exit stairway or an exterior exit ramp, shall not exceed 
the distances given in Table 1016.1. 

Exceptions: 

1. Travel distance in open parking garages is permitted 
to be measured to the closest riser of open exit stair- 
ways. 

2. In outdoor facilities with open exit access compo- 
nents and open exterior exit stairways or exit ramps, 
travel distance is permitted to be measured to the clos- 
est riser of an exit stairway or the closest slope of the 
exit ramp. 

3. In other than occupancy Groups H and I, the exit 
access travel distance to a maximum of 50 percent of 
the exits is permitted to be measured from the most 
remote point within a building to an exit using unen- 
closed exit access stairways or ramps when connect- 
ing a maximum of two stories. The two connected 
stories shall be provided with at least two means of 
egress. Such interconnected stories shall not be open 
to other stories. 

4. In other than occupancy Groups H and I, exit access 
travel distance is permitted to be measured from the 
most remote point within a building to an exit using 
unenclosed exit access stairways or ramps in the first 
and second stories above grade plane in buildings 
equipped throughout with an automatic sprinkler sys- 
tem in accordance with Section 903.3.1.1. The first 
and second stories above grade plane shall be pro- 
vided with at least two means of egress. Such inter- 
connected stories shall not be open to other stories. 

Where applicable, travel distance on unenclosed exit access 
stairways or ramps and on connecting stories shall also be 
included in the travel distance measurement. The measurement 
along stairways shall be made on a plane parallel and tangent to 
the stair tread nosings in the center of the stairway. 



TABLE 1016.1 
EXIT ACCESS TRAVEL DISTANCE 21 



OCCUPANCY 


WITHOUT SPRINKLER 
SYSTEM 

(feet) 


WITH SPRINKLER 
SYSTEM 

(feet) 


A, E, F-l, M, R, 5-1 


200 


250 b 


1-1 


Not Permitted 


250 e 


B 


200 


300 e 


F-2, 5-2, U 


300 


400 e 


H-l 


Not Permitted 


75 e 


H-2 


Not Permitted 


100 e 


H-3 


Not Permitted 


150 e 


H-4 


Not Permitted 


175 e 


H-5 


Not Permitted 


200 e 


1-2,1-3,1-4 


Not Permitted 


200 e 



For SI: 1 foot = 304.8 mm. 

a. See the following sections for modifications to exit access travel distance 
requirements: 

Section 402.4: For the distance limitation in malls. 

Section 404.9: For the distance limitation through an atrium space. 

Section 407.4: For the distance limitation in Group 1-2. 

Sections 408.6.1 and 408.8.1 : For the distance limitations in Group 1-3. 

Section 411 .4: For the distance limitation in special amusement buildings. 

Section 1014.2.2 : For the distance limitation in Group 1-2 hospital suites . 

Section 1015.4: For the distance limitation in refrigeration machinery 

rooms. 
Section 1015.5: For the distance limitation in refrigerated rooms and spaces. 
Section 1021 .2: For buildings with one exit. 
Section 1028.7: For increased limitation in assembly seating. 
Section 1028.7: For increased limitation for assembly open-air seating. 
Section 3103.4: For temporary structures. 
Section 3104.9: For pedestrian walkways. 

b. Buildings equipped throughout with an automatic sprinkler system in accor- 
dance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies 
where automatic sprinkler systems are permitted in accordance with Section 
903.3.1.2. 

c. Buildings equipped throughout with an automatic sprinkler system in accor- 
dance with Section 903.3.1.1. 

1016.2 Exterior egress balcony increase. Travel distances 
specified in Section 1016.1 shall be increased up to an additional 
100 feet (30 480 mm) provided the last portion of the exit access 
leading to the exit occurs on an exterior egress balcony con- 
structed in accordance with Section 1019. The length of such 
balcony shall not be less than the amount of the increase taken. 



SECTION 1017 
AISLES 

1017.1 General. A isles serving as a portion of the exit access in 
the means of egress system shall comply with the requirements 
of this section. Aisles shall be provided from all occupied por- 
tions of the exit access which contain seats, tables, furnishings, 
displays and similar fixtures or equipment. Aisles serving 
assembly areas shall comply with Section 1028. A isles serving 
reviewing stands, grandstands and bleachers shall also comply 
with Section 1028. The required width of aisles shall be unob- 
structed. 

Exception: Doors complying with Section 1005.2. 



240 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



1017.2 Aisles in Groups Band M. In Group Band M occu- 
pancies, the minimum clear aisle width shall be determined by 
Section 1005.1 for the occupant load served, but shall not be 
less than 36 inches (914 mm). 

Exception: Nonpublic aisles serving less than 50 people 
and not required to be accessible by Chapter 11 need not 
exceed 28 inches (711 mm) in width. 

1017.3 Aisle accessways in Group M. An aisle accessway 
shall be provided on at least one side of each element within the 
merchandise pad. The minimum clear width for an aisle 
accesswaynot required to be accessible shall be 30 inches (762 
mm). The required clear width of the aisle accessway shall be 
measured perpendicular to the elements and merchandise 
within the merchandise pad. The 30-inch (762 mm) minimum 
clear width shall be maintained to provide a path to an adjacent 
aisle or aisle accessway. The common path of travel shall not 
exceed 30 feet (9144 mm) from any point in the merchandise 
pad. 

Exception: For areas serving not more than 50 occupants, 
the common path of travel shall not exceed 75 feet (22 880 
mm). 

1017.4 Seating at tables. Where seating is located at a table or 
counter and is adjacent to an aisle or aisle accessway, the mea- 
surement of required clear width of the aisle or aisle accessway 
shall be made to a line 19 inches (483 mm) away from and par- 
allel to the edge of the table or counter. The 19- inch (483 mm) 
distance shall be measured perpendicular to the side of the table 
or counter. In the case of other side boundaries for aisle or aisle 
accessways, the clear width shall be measured to walls, edges 
of seating and tread edges, except that handrail projections are 
permitted. 

Exception: Where tables or counters are served by fixed 
seats, the width of the aisle accessway shall be measured 
from the back of the seat. 

1017.4.1 Aisle accessway for tables and seating. Aisle 
accessways serving arrangements of seating at tables or 
counters shall have sufficient clear width to conform to the 
capacity requirements of Section 1005.1 but shall not have 
less than the appropriate minimum clear width specified in 
Section 1017.4.2. 



1017.4.2 Table and seating accessway width. Aisle 
accessways shall provide a minimum of 12 inches (305 mm) 
of width plus i/ 2 inch (12.7 mm) of width for each additional 
1 foot (305 mm), or fraction thereof, beyond 12 feet (3658 
mm) of aisle accessway length measured from the center of 
the seat farthest from an aisle. 

Exception: Portions of an aisle accessway having a 
length not exceeding 6 feet (1829 mm) and used by a 
total of not more than four persons. 

1017.4.3 Table and seating aisle accessway length. The 
length of travel along the aisle accessway shall not exceed 
30 feet (9144 mm) from any seat to the point where a person 
has a choice of two or more paths of egress travel to separate 
exits. 



SECTION 1018 
CORRIDORS 

1018.1 Construction. Corridors shall be fire-resistance rated 
in accordance with Table 1018.1. The corri dor walls required 
to be fire-resistance rated shall comply with Section 709 fox fire 
partitions. 

Exceptions: 

1. Afire-resistance rating is not required for corridors in 
an occupancy in Group E where each room that is used 
for instruction has at least one door opening directly to 
the exterior and rooms for assembly purposes have at 
least one-half of the required means of egress doors 
opening directly to the exterior. Exterior doors speci- 
fied in this exception are required to be at ground level. 

2. A fire-resistance rating is not required for corridors 
contained within a dwelling or sleeping unit in an 
occupancy in Group R. 

3. A fire-resistance rating is not required for corridors 
in open parking garages. 

4. A fire-resistance rating is not required for corridors 
in an occupancy in Group B which is a space requiring 
only a single means of egress complying with Section 
1015.1. 



TABLE 1018.1 
CORRIDOR FIRE-RESISTANCE RATING 



OCCUPANCY 


OCCUPANT LOAD SERVED BY CORRIDOR 


REQUIRED FIRE-RESISTANCE RATING (hours) 


Without sprinkler system 


With sprinkler system 


H-l, H-2, H-3 


All 


Not Permitted 


1 


H-4,H-5 


Greater than 30 


Not Permitted 


1 


A, B, E, F, M, S, U 


Greater than 30 


1 





R 


Greater than 10 


Not Permitted 


0.5 


1-2M-4 


All 


Not Permitted 





1-1,1-3 


All 


Not Permitted 


l b 



a. For requirements for occupancies in Group 1-2, see Sections 407.2 and 407.3. 

b. For a reduction in the fire-resistance rating for occupancies in Group 1-3, see Section 408.8. 

c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. 



2009 INTERNATIONAL BUILDING CODE® 



241 



MEANS OF EGRESS 



1 



1018.2 Corridor width. The minimum corridorwidth shall be 
as determined in Section 1005.1, but not less than 44 inches 
(1118 mm). 

Exceptions: 

1. Twenty-four inches (610 mm)-For access to and uti- 
lization of electrical, mechanical or plumbing sys- 
tems or equipment. 

2. Thirty-six inches (914 mm)-With a required occu- 
pant capacity of less than 50. 

3. Thirty-six inches (914 mm) -Within a dwelling unit. 

4. Seventy-two inches (1829 mm)-In Group E with a 
corridor having a required capacity of 100 or more. 

5. Seventy-two inches (1829 mm)-In corridors and 
areas serving gurney traffic in occupancies where 
patients receive outpatient medical care, which 
causes the patient to be not capable of self-preserva- 
tion. 

6. Ninety-six inches (2438 mm)-In Group 1-2 in areas 
where required for bed movement. 

1018.3 Corridor obstruction. The required width of corri- 
dors shall be unobstructed. 

Exception: Doors complying with Section 1005.2. 

1018.4 Dead ends. Where more than one exit or exit access 
doorwayis required, the exit access shall be arranged such that 
there are no dead ends in corridors more than 20 feet (6096 
mm) in length. 

Exceptions: 

1. In occupancies in Group 1-3 of Occupancy Condition 
2, 3 or 4 (see Section 308.4), the dead end in a corri- 
dor shall not exceed 50 feet (15 240 mm). 

2. In occupancies in Groups B, E, F, 1-1, M, R-l, R-2, 
R-4, Sand U, where the building is equipped 
throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1, the length of the 
dead-end corridors shall not exceed 50 feet (15 240 
mm). 

3. A dead-end corridor shall not be limited in length 
where the length of the dead-end corridoris less than 
2.5 times the least width of the dead-end corridor. 

1018.5 Air movement in corridors. Corridors shall not serve 
as supply, return, exhaust, relief or ventilation air ducts. 

Exceptions: 

1. Use of a corridor as a source of makeup air for 
exhaust systems in rooms that open directly onto such 
corridors, including toilet rooms, bathrooms, dress- 
ing rooms, smoking lounges andjanitor closets, shall 
be permitted, provided that each such corridor is 
directly supplied with outdoor air at a rate greater than 
the rate of makeup air taken from the corridor. 

2. Where located within a dwelling unit, the use of corri- 
dorsfor conveying return air shall not be prohibited. 



3. Where located within tenant spaces of 1,000 square 
feet (93 m 2 ) or less in area, utilization of corridors for 
conveying return air is permitted. 

4. Incidental air movement from pressurized rooms 
within health care facilities, provided that the corri- 
doris not the primary source of supply or return to the 
room. 

1018.5.1 Corridor ceiling. Use of the space between the 
corridor ceiling and the floor or roof structure above as a 
return air plenum is permitted for one or more of the follow- 
ing conditions: 

1. The corridor is not required to be of fire-resis- 
tance-rated construction; 

2. The corridor is separated from the plenum by 
fire-resistance-rated construction; 

3. The air-handling system serving the corridoris shut 
down upon activation of the air-handling unit smoke 
detectors required by the International Mechanical 
Code; 

4. The air-handling system serving the corridoris shut 
down upon detection of sprinkler waterflow where 
the building is equipped throughout with an auto- 
matic sprinkler system; or 

5. The space between the corridorceiling and the floor or 
roof structure above the corridoris used as a compo- 
nent of an approved engineered smoke control system. 

1018.6 Corridor continuity. Fire-resistance-rated corridors 
shall be continuous from the point of entry to an exit, and shall 
not be interrupted by intervening rooms. 

Exception: Foyers, lobbies or reception rooms constructed 
as required for corridors shall not be construed as interven- 
ing rooms. 



SECTION 1019 
EGRESS BALCONIES 

1019.1 General. Balconies used for egress purposes shall con- 
form to the same requirements as corridors for width, head- 
room, dead ends and projections. 

1019.2 Wall separation. Exterior egress balconies shall be 
separated from the interior of the building by walls and opening 
protectives as required for corridors. 

Exception: Separation is not required where the exterior 
egress balcony is served by at least two stairs and a dead-end 
travel condition does not require travel past an unprotected 
opening to reach a stair. 

1019.3 Openness. The long side of an egress balcony shall be 
at least 50 percent open, and the open area above the guards 
shall be so distributed as to minimize the accumulation of 
smoke or toxic gases. 



242 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



SECTION 1020 
EXITS 

1020.1 General. Exits shall comply with Sections 1020 
through 1026 and the applicable requirements of Sections 1003 
through 1013. An exit shall not be used for any purpose that 
interferes with its function as a means of egress. Once a given 
level of exit protection is achieved, such level of protection 
shall not be reduced until arrival at the exit discharge. 

1020.2 Exterior exit doors. Buildings or structures used for 
human occupancy shall have at least one exterior door that 
meets the requirements of Section 1008.1.1. 

1020.2.1 Detailed requirements. Exterior exit doors shall 
comply with the applicable requirements of Section 1008.1. 

1020.2.2 Arrangement. Exterior exit doors shall lead 
directly to the exit discharge or the public way 



SECTION 1021 
NUMBER OF EXITS AND CONTINUITY 

1021.1 Exits from stories. All spaces within each story shall 
have access to the minimum number of approved independent 
exits as specified in Table 1021.1 based on the occupant loadof 
the story For the purposes of this chapter, occupied roofs shall 
be provided with exits as required for stories. 

Exceptions: 

1. As modified by Section 403.5.2. 

2. As modified by Section 1021.2. 

3. Exit access stairways and ramps that comply with 
Exception 3 or 4 of Section 1016.1 shall be permitted 
to provide the minimum number of approved inde- 
pendent exits required by Table 1021.1 on each story. 

4. In Group R-2 and R-3 occupancies, one means of 
egress is permitted within and from individual dwell- 
ing units with a maximum occupant load of 20 where 



the dwelling unit is equipped throughout with an 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1 or 903.3.1.2. 

5. Within a story, rooms and spaces complying with 
Section 1015.1 with exits thai discharge directly to the 
exterior at the level of exit discharge, are permitted to 
have one exit. 

TABLE 1021.1 
MINIMUM NUMBER OF EXITS FOR OCCUPANT LOAD 



OCCUPANT LOAD 
(persons per story) 


MINIMUM NUMBER OF EXITS 
(per story) 


1-500 


2 


501-1,000 


3 


More than 1,000 


4 



1021.1.1 Exits maintained. The required number of exits 
from any story shall be maintained until arrival at grade or 
the public way. 

1021.1.2 Parking structures. Parking structures shall not 
have less than two exits from each parking tier, except that 
only one exit is required where vehicles are mechanically 
parked. Vehicle ramps shall not be considered as required 
exits unless pedestrian facilities are provided. 

1021.1.3 Helistops. The means of egress from helistops 
shall comply with the provisions of this chapter, provided 
that landing areas located on buildings or structures shall 
have two or more exits. For landing platforms or roof areas 
less than 60 feet (18288 mm) long, or less than 2,000 square 
feet (186 m 2 ) in area, the second means of egress is permit- 
ted to be a fire escape, alternating tread device or ladder 
leading to the floor below. 

1021.2 Single exits. Only one exit shall be required from 
Group R-3 occupancy buildings or from stories of other build- 
ings as indicated in Table 1021.2. Occupancies shall be permit- 
ted to have a single exitin buildings otherwise required to have 
more than one exit if the areas served by the single exit do not 



TABLE 1021.2 
STORIES WITH ONE EXIT 



STORY 


OCCUPANCY 


MAXIMUM OCCUPANTS (OR DWELLING UNITS) 
PER FLOOR AND TRAVEL DISTANCE 


First story or basement 


A, Bd, Ee, Fd, M, U, Sd 


49 occupants and 75 feet travel distance 


H-2, H-3 


3 occupants and 25 feet travel distance 


H-4,H-5,I, R 


10 occupants and 75 feet travel distance 


sa 


29 occupants and 100 feet travel distance 


Second story 


Bb, F, M,Sa 


29 occupants and 75 feet travel distance 


R-2 


4 dwelling units and 50 feet travel distance 


Third story 


R-2 C 


4 dwelling units and 50 feet travel distance 



For SI: 1 foot = 304.8 mm. 

a. For the required number of exits for parking structures, see Section 1021.1.2. 

b. For the required number of exits for air traffic control towers, see Section 412.3. 

c. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and provided with 
emergency escape and rescue openings in accordance with Section 1029. 

d. Group B, F and S occupancies in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3. 1.1 shall have a maximum 
travel distance of 100 feet. 

e. Day care occupancies shall have a maximum occupant load of 10. 



2009 INTERNATIONAL BUILDING CODE® 



243 



MEANS OF EGRESS 



exceed the limitations of Table 1021.2. Mixed occupancies 
shall be permitted to be served by single exits provided each 
individual occupancy complies with the applicable require- 
ments of Table 1021.2 for that occupancy. Where applicable, 
cumulative occupant loads from adjacent occupancies shall be 
considered in accordance with the provisions of Section 
1004.1. Basements with a single exit shall not be located more 
than one story below grade plane. 

1021.3 Exit continuity. Exits shall be continuous from the 
point of entry into the exit io the exit discharge. 

1021 .4 Exit door arrangement. Exit door arrangement shall 
meet the requirements of Sections 1015.2 through 1015.2.2. 



SECTION 1022 
EXIT ENCLOSURES 

1022.1 Enclosures required. Interior exit stairways and inte- 
rior exit ramps shall be enclosed wiihfire barriers constructed 
in accordance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. Exit enclo- 
sures shall have afire -resistance rating of not less than 2 hours 
where connecting four stories or more and not less than 1 hour 
where connecting less than four stories. The number of stories 
connected by the exit enclosure shall include any basements 
but not any mezzanines. Exit enclosures shall have afire-resis- 
tance rating not less than the floor assembly penetrated, but 
need not exceed 2 hours. Exit enclosures shall lead directly to 
the exterior of the building or shall be extended to the exterior 
of the building with an exit passageway conforming to the 
requirements of Section 1023, except as permitted in Section 
1027.1. An exit enclosure shall not be used for any purpose 
other than means of egress. 

Exceptions: 

1. In all occupancies, other than Group H and I occupan- 
cies, a stairway is not required to be enclosed when 
the s tairway serves an occupant load of less than 10 
and the stairway complies with either Item 1.1 or 1.2. 
In all cases, the maximum number of connecting open 
stories shall not exceed two. 

1.1. The stairway is open to not more than one 
story above its level of exit discharge; or 

1.2. The stairway is open to not more than one 
story below its level of exit discharge. 

2. Exits in buildings of Group A-5 where all portions of 
the means of egress are essentially open to the outside 
need not be enclosed. 

3. Stairways serving and contained within a single resi- 
dential dwelling unit or sleeping unit in Group R-l, 
R-2 or R-3 occupancies are not required to be 
enclosed. 

4. Stairways in open parking structures that serve only 
the parking structure are not required to be enclosed. 

5. Stairways in Group 1-3 occupancies, as provided for 
in Section 408.3.8, are not required to be enclosed. 

6. Means of egress stairways as required by Sections 
410.5.3 and 1015.6.1 are not required to be enclosed. 



7. Means of egress stairways from balconies, galleries 
or press boxes as provided for in Section 1028.5.1 are 
not required to be enclosed. 

1022.2 Termination. Exit enclosures shall terminate at an exit 
discharge or a public way 

Exception: An exit enclosure shall be permitted to termi- 
nate at an exit passageway complying with Section 1023, 
provided the exitpassagewaytermmates at an exit discharge 
or a public way. 

1022.2.1 Extension. Where an exit enclosure is extended to 
an exit discharge or a public way by an exitpassageway, the 
exit enclosure shall be separated from the exitpassageway 
by afire barrier constructed in accordance with Section 707 
or a horizontal assembly constructed in accordance with 
Section 712, or both. The fire -resistance rating shall be at 
least equal to that required for the exit enclosure. Afire door 
assembly complying with Section 715 .4 shall be installed in 
the fire barrier io provide a means of egress from the exit 
enclosure to the exitpassageway Openings in the fire bar- 
rier other than the fire door assembly are prohibited. Pene- 
trations of the fire barrier are prohibited. 

Exception: Penetrations of ih^ fire barrierin accordance 
with Section 1022.4 shall be permitted. 

1022.3 Openings and penetrations. Exit enclosure opening 
protectives shall be in accordance with the requirements of 
Section 715. 

Openings in exit enclosures other than unprotected exterior 
openings shall be limited to those necessary for exit access to 
the enclosure from normally occupied spaces and for egress 
from the enclosure. 

Elevators shall not open into an exit enclosure. 

1022.4 Penetrations. Penetrations into and openings through 
an exit enclosure are prohibited except for required exit doors, 
equipment and ductwork necessary for independent ventilation 
or pressurization, sprinkler piping, standpipes, electrical race- 
way for fire department communication systems and electrical 
raceway serving the exit enclosure and terminating at a steel 
box not exceeding 16 square inches (0.010 m 2 ). Such penetra- 
tions shall be protected in accordance with Section 713. There 
shall be no penetrations or communication openings, whether 
protected or not, between adjacent exit enclosures. 

1022.5 Ventilation. Equipment and ductwork for exit enclo- 
sure ventilation as permitted by Section 1022.4 shall comply 
with one of the following items: 

1. Such equipment and ductwork shall be located exterior 
to the building and shall be directly connected to the exit 
enclosure by ductwork enclosed in construction as 
required for shafts. 

2. Where such equipment and ductwork is located within 
the exit enclosure, the intake air shall be taken directly 
from the outdoors and the exhaust air shall be discharged 
directly to the outdoors, or such air shall be conveyed 
through ducts enclosed in construction as required for 
shafts. 

3. Where located within the building, such equipment and 
ductwork shall be separated from the remainder of the 



244 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



building, including other mechanical equipment, with 
construction as required for shafts. 

In each case, openings into the fire-resistance-rated con- 
struction shall be limited to those needed for maintenance and 
operation and shall be protected by opening protectives in 
accordance with Section 715 for shaft enclosures. 

Exit enclosure ventilation systems shall be independent of 
other building ventilation systems. 

1022.6 Exit enclosure exterior walls. Exterior walls of an exit 
enclosure shall comply with the requirements of Section 705 for 
exterior walls. Where nonrated walls or unprotected openings 
enclose the exterior of the stairway an d the walls or openings are 
exposed by other parts of the building at an angle of less than 180 
degrees (3.14 rad), the building exterior walls within 10 feet 
(3048 mm) horizontally of a nonrated wall or unprotected open- 
ing shall have a fire-resistance rating of not less than 1 hour. 
Openings within such exterior walls shall be protected by open- 
ing protectives having a fire protection rating of not less than 3/ 4 
hour. This construction shall extend vertically from the ground 
to a point 10 feet (3048 mm) above the topmost landing of the 
stairway or to the roof line, whichever is lower. 

1022.7 Discharge identification. A stairway in an exit enclo- 
sure shall not continue below its level of exit discharge unless 
an approved barrier is provided at the level of exit discharge to 
prevent persons from unintentionally continuing into levels 
below. Directional exit signs shall be provided as specified in 
Section 1011. 

1022.8 Floor identification signs. A sign shall be provided at 
each floor landing in exit enclosures connecting more than 
three stories designating the floor level, the terminus of the top 
and bottom of the exit enclosure and the identification of the 
stair or ramp. The signage shall also state the story of, and the 
direction to, the exit discharge and the availability of roof 
access from the enclosure for the fire department. The sign 
shall be located 5 feet (1524 mm) above the floor landing in a 
position that is readily visible when the doors are in the open 
and closed positions. Floor level identification signs in tactile 
characters complying with ICC All 7. 1 shall be located at each 
floor level landing adjacent to the door leading from the enclo- 
sure into the corridor to identify the floor level. 

1022.8.1 Signage requirements. Stairway identification 
signs shall comply with all of the following requirements: 

1. The signs shall be a minimum size of 18 inches (457 
mm) by 12 inches (305 mm). 

2. The letters designating the identification of the stair 
enclosure shall be a minimum of 1V 2 inches (38 mm) 
in height. 

3. The number designating the floor level shall be a min- 
imum of 5 inches (127 mm) in height and located in 
the center of the sign. 

4. All other lettering and numbers shall be a minimum of 
1 inch (25 mm) in height. 

5. Characters and their background shall have a 
nonglare finish. Characters shall contrast with their 
background, with either light characters on a dark 
background or dark characters on a light background. 



6. When signs required by Section 1022.8 are installed 
in interior exit enclosures of buildings subject to Sec- 
tion 1024, the signs shall be made of the same materi- 
als as required by Section 1024.4. 

1022.9 Smokeproof enclosures and pressurized stairways. 
In buildings required to comply with Section 403 or 405, each 
of the exit enclosures serving a story with a floor surface 
located more than 75 feet (22 860 mm) above the lowest level 
of fire department vehicle access or more than 30 feet (9144 
mm) below the finished floor of a level of exit discharge serving 
such stories shall be a smokeproof enclosure or pressurized 
stairway in accordance with Section 909.20. 

1022.9.1 Termination and extension. A smokeproof 
enclosure or pressurized stairway shall terminate at an exit 
discharge or a public way. The smokeproof enclosure or 
pressurized stairway shall be permitted to be extended by an 
exit passageway in accordance with Section 1022.2. The 
exit passageway shall be without openings other than the 
fire door assembly required by Section 1022.2 and those 
necessary for egress from the exitpassageway The exitpas- 
sagewayshall be separated from the remainder of the build- 
ing by 2-hour fire barriers constructed in accordance with 
Section 707 or horizontal assemblies constructed in accor- 
dance with Section 712, or both. 

Exceptions: 

1. Openings in the exit passageway serving a 
smokeproof enclosure are permitted where the exit 
passageway is protected and pressurized in the 
same manner as the smokeproof enclosure, and 
openings are protected as required for access from 
other floors. 

2. Openings in the exitpassageway serving a pres- 
surized stairway are permitted where the exitpas- 
sageway is protected and pressurized in the same 
manner as the pressurized stairway. 

3. The fire barrier separating the smokeproof enclo- 
sure or pressurized stairway from the exitpas- 
sageway is not required, provided the exit 
passageway is protected and pressurized in the 
same manner as the smokeproof enclosure or pres- 
surized stairway. 

4. A smokeproof enclosure or pressurized stairway 
shall be permitted to egress through areas on the 
level of discharge or vestibules as permitted by 
Section 1027. 

1022.9.2 Enclosure access. Access to the stairway within a 
smokeproof enclosure shall be by way of a vestibule or an 
open exterior balcony. 

Exception: Access is not required by way of a vestibule 
or exterior balcony for stairways using the pressurization 
alternative complying with Section 909.20.5. 



SECTION 1023 
EXIT PASSAGEWAYS 

1023.1 Exit passageway. Exitpassageway s serving as an exit 
component in a means of egress system shall comply with the 



2009 INTERNATIONAL BUILDING CODE® 



245 



MEANS OF EGRESS 



requirements of this section. An exit passageway shall not be 
used for any purpose other than as a means of egress. 

1023.2 Width. The width of exit passageways shall be deter- 
mined as specified in Section 1005.1 but such width shall not 
be less than 44 inches (1118 mm), except that exitpassageways 
serving an occupant load of less than 50 shall not be less than 
36 inches (914 mm) in width. The required width of exitpas- 
sageways shall be unobstructed. 

Exception: Doors complying with Section 1005.2. 

1023.3 Construction. Exit passageway enclosures shall have 
walls, floors and ceilings of not less than I-hour fire -resistance 
rating, and not less than that required for any connecting exit 
enclosure. Exitpassageways shall be constructed as fire barri- 
ers in accordance with Section 707 or horizontal assemblies 
constructed in accordance with Section 712, or both. 

1023.4 Termination. Exitpassageways shall terminate at an 
exit discharge or a public way. 

1023.5 Openings and penetrations. Exitpassageway opening 
protectives shall be in accordance with the requirements of 
Section 715. 

Except as permitted in Section 402.4.6, openings in exitpas- 
sageways other than exterior openings shall be limited to those 
necessary for exit access to the exitpassageway from normally 
occupied spaces and for egress from the exitpassageway 

Where an exit enclosure is extended to an exit discharge or a 
public way by an exit passageway, the exitpassageway shall 
also comply with Section 1022.2.1. 

Elevators shall not open into an exitpassageway 

1023.6 Penetrations. Penetrations into and openings through 
an exit passageway are prohibited except for required exit 
doors, equipment and ductwork necessary for independent 
pressurization, sprinkler piping, standpipes, electrical raceway 
for fire department communication and electrical raceway 
serving the exitpassageway and terminating at a steel box not 
exceeding 16 square inches (0.010 m 2 ). Such penetrations shall 
be protected in accordance with Section 713. There shall be no 
penetrations or communicating openings, whether protected or 
not, between adjacent exitpassageways. 



SECTION 1024 
LUMINOUS EGRESS PATH MARKINGS 

1024.1 General. Approved luminous egress path markings 
delineating the exit path shall be provided in buildings of 
Groups A, B, E, I, M and R-l having occupied floors located 
more than 75 feet (22 860 mm) above the lowest level of fire 
department vehicle access in accordance with Sections 1024.1 
through 1024.5. 

Exceptions: 

1. Luminous egress path markings shall not be required 
on the level of exit discharge in lobbies that serve as 
part of the exit path in accordance with Section 
1027.1, Exception 1. 

2. Luminous egress path markings shall not be required 
in areas of open parking garages that serve as part of 



the exit path in accordance with Section 1027.1, 
Exception 3. 

1024.2 Markings within exit enclosures. Egress path mark- 
ings shall be provided in exit enclosures, including vertical exit 
enclosures and exitpassageways, in accordance with Sections 
1024.2.1 through 1024.2.6. 

1024.2.1 Steps. A solid and continuous stripe shall be 
applied to the horizontal leading edge of each step and shall 
extend for the full length of the step. Outlining stripes shall 
have a minimum horizontal width of 1 inch (25 mm) and a 
maximum width of 2 inches (51 mm). The leading edge of 
the stripe shall be placed at a maximum of i/ 2 inch (13 mm) 
from the leading edge of the step and the stripe shall overlap 
the leading edge of the step by not more than i/ 2 inch (13 
mm) down the vertical face of the step. 

Exception: The minimum width of 1 inch (25 mm) shall 
not apply to outlining stripes listed in accordance with 
UL 1994. 

1024.2.2 Landings. The leading edge of landings shall be 
marked with a stripe consistent with the dimensional 
requirements for steps. 

1024.2.3 Handrails. All handrails mid handrail extensions 
shall be marked with a solid and continuous stripe having a 
minimum width of 1 inch (25 mm). The stripe shall be 
placed on the top surface of the handrailfor the entire length 
of the handrail, including extensions and newel post caps. 
Where handrails or handrail extensions bend or turn cor- 
ners, the stripe shall not have a gap of more than 4 inches 
(102 mm). 

Exception: The minimum width of 1 inch (25 mm) shall 
not apply to outlining stripes listed in accordance with 
UL 1994. 

1024.2.4 Perimeter demarcation lines. Stair landings and 
other floor areas within exit enclosures, with the exception 
of the sides of steps, shall be provided with solid and contin- 
uous demarcation lines on the floor or on the walls or a com- 
bination of both. The stripes shall be 1 to 2 inches (25 mm to 
51 mm) wide with interruptions not exceeding 4 inches (102 
mm). 

Exception: The minimum width of 1 inch (25 mm) shall 
not apply to outlining stripes listed in accordance with 
UL 1994. 

1024.2.4.1 Floor-mounted demarcation lines. Perime- 
ter demarcation lines shall be placed within 4 inches (102 
mm) of the wall and shall extend to within 2 inches (51 
mm) of the markings on the leading edge of landings. 
The demarcation lines shall continue across the floor in 
front of all doors. 

Exception: Demarcation lines shall not extend in 
front of exit doors that lead out of an exit enclosure 
and through which occupants must travel to complete 
the exit path. 

1024.2.4.2 Wall-mounted demarcation lines. Perime- 
ter demarcation lines shall be placed on the wall with the 
bottom edge of the stripe no more than 4 inches (102 
mm) above the finished floor. At the top or bottom of the 



246 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



stairs, demarcation lines shall drop vertically to the floor 
within 2 inches (51 mm) of the step or landing edge. 
Demarcation lines on walls shall transition vertically to 
the floor and then extend across the floor where a line on 
the floor is the only practical method of outlining the 
path. Where the wall line is broken by a door, demarca- 
tion lines on walls shall continue across the face of the 
door or transition to the floor and extend across the floor 
in front of such door. 

Exception: Demarcation lines shall not extend in 
front of exit doors that lead out of an exit enclosure 
and through which occupants must travel to complete 
the exit path. 

1024.2.4.3 Transition. Where a wall-mounted demarca- 
tion line transitions to a floor-mounted demarcation line, 
or vice versa, the wall-mounted demarcation line shall 
drop vertically to the floor to meet a complementary 
extension of the floor-mounted demarcation line, thus 
forming a continuous marking. 

1024.2.5 Obstacles. Obstacles at or below 6 feet 6 inches 
(1981 mm) in height and projecting more than 4 inches (102 
mm) into the egress path shall be outlined with markings no 
less than 1 inch (25 mm) in width comprised of a pattern of 
alternating equal bands, of luminescent luminous material 
and black, with the alternating bands no more than 2 inches 
(51 mm) thick and angled at 45 degrees (0.79 rad). Obsta- 
cles shall include, but are not limited to, standpipes, hose 
cabinets, wall projections and restricted height areas. How- 
ever, such markings shall not conceal any required informa- 
tion or indicators including, but not limited to, instructions 
to occupants for the use of standpipes. 

1024.2.6 Doors from exit enclosures. Doors through 
which occupants within an exit enclosure must pass in order 
to complete the exit path shall be provided with markings 
complying with Sections 1024.2.6.1 through 1024.2.6.3. 

1024.2.6.1 Emergency exit symbol. The doors shall be 
identified by a low-location luminous emergency exit 
symbol complying with NFPA 170. The exit symbol 
shall be a minimum of 4 inches (102 mm) in height and 
shall be mounted on the door, centered horizontally, with 
the top of the symbol no higher than 18 inches (457 mm) 
above the finished floor. 

1024.2.6.2 Door hardware markings. Door hardware 
shall be marked with no less than 16 square inches (406 
mm 2 ) of luminous material. This marking shall be 
located behind, immediately adjacent to or on the door 
handle and/or escutcheon. Where a panic bar is installed, 
such material shall be no less than 1 inch (25 mm) wide 
for the entire length of the actuating bar or touchpad. 

1024.2.6.3 Door frame markings. The top and sides of 
the door frame shall be marked with a solid and continu- 
ous 1 inch to 2 inch (25 mm to 51 mm) wide stripe. 
Where the door molding does not provide sufficient flat 
surface on which to locate the stripe, the stripe shall be 
permitted to be located on the wall surrounding the 
frame. 



1024.3 Uniformity. Placement and dimensions of markings 
shall be consistent and uniform throughout the same exit enclo- 
sure. 

1024.4 Self-luminous and photoluminescent. Luminous 
egress path markings shall be permitted to be made of any 
material, including paint, provided that an electrical charge is 
not required to maintain the required luminance. Such materi- 
als shall include, but are not limited to, self-luminous materials 
and photoluminescent materials. Materials shall comply with 
either: 

1. UL 1994; or 

2. ASTM E 2072, except that the charging source shall be 1 
foot-candle (11 lux) of fluorescent illumination for 60 
minutes, and the minimum luminance shall be 30 
millicandelas per square meter at 10 minutes and 5 
millicandelas per square meter after 90 minutes. 

1024.5 Illumination. Exit enclosures where photoluminescent 
exit path markings are installed shall be provided with the mini- 
mum means of egress illumination required by Section 1006 
for at least 60 minutes prior to periods when the building is 
occupied. 



SECTION 1025 
HORIZONTAL EXITS 

1025.1 Horizontal exits. Horizontal exits serving as an exitin 
a means ofegress system shall comply with the requirements of 
this section. A horizontal exit shall not serve as the only exit 
from a portion of a building, and where two or more exits are 
required, not more than one-half of the total number of exits or 
total exit width shall be horizontal exits. 

Exceptions: 

1. Horizontal exits are permitted to comprise two-thirds 
of the required exits from any building or floor area 
for occupancies in Group 1-2. 

2. Horizontal exits are permitted to comprise 100 per- 
cent of the exits required for occupancies in Group 
1-3. At least 6 square feet (0.6 m 2 ) of accessible space 
per occupant shall be provided on each side of the 
horizontal exit for the total number of people in 
adjoining compartments. 

1025.2 Separation. The separation between buildings or ref- 
uge areas connected by a horizontal exit shall be provided by a 
fire wall complying with Section 706; or it shall be provided by 
a fire barrier complying with Section 707 or a horizontal 
assembly complying with Section 712, or both. The minimum 
fire-resistance rating of the separation shall be 2 hours. Open- 
ing protectives in horizontal exits shall also comply with Sec- 
tion 715. Duct and air transfer openings in a fire wall or fire 
barrier that serves as a horizontal exit shall also comply with 
Section 716. The horizontal exit separation shall extend verti- 
cally through all levels of the building unless floor assemblies 
have a fire-resistance rating of not less than 2 hours with no 
unprotected openings. 

Exception: A fire-resistance rating is not required at hori- 
zontal exits between a building area and an above-grade 



2009 INTERNATIONAL BUILDING CODE® 



247 



MEANS OF EGRESS 



pedestrian walkway constructed in accordance with Section 
3104, provided that the distance between connected build- 
ings is more than 20 feet (6096 mm). 

Horizontal exits constructed as fire barriers shall be continu- 
ous from exterior wall to exterior wall so as to divide com- 
pletely the floor served by the horizontal exit. 

1025.3 Opening protectives. Fire doors in horizontal exits 
shall be self-closing or automatic-closing when activated by a 
smoke detector in accordance with Section 715.4.8.3. Doors, 
where located in a cross-corridor condition, shall be auto- 
matic-closing by activation of a smoke detector installed in 
accordance with Section 715.4.8.3. 

1025.4 Capacity of refuge area. The refuge area of a horizon- 
tal exit shall be a space occupied by the same tenant or a public 
area and each such refuge area shall be adequate to accommo- 
date the original occupantloadofthe refuge area plus the occu- 
pant load anticipated from the adjoining compartment. The 
anticipated occupant load from the adjoining compartment 
shall be based on the capacity of the horizontal exit doors enter- 
ing the refuge area. The capacity of the refuge area shall be 
computed based on a net floor area allowance of 3 square feet 
(0.2787 m 2 ) for each occupant to be accommodated therein. 

Exception: The net floor area allowable per occupant shall 
be as follows for the indicated occupancies: 

1. Six square feet (0.6 m 2 ) per occupant for occupancies 
in Group 1-3. 

2. Fifteen square feet (1.4 m 2 ) per occupant for ambula- 
tory occupancies in Group 1-2. 

3. Thirty square feet (2.8 m 2 ) per occupant for 
nonambulatory occupancies in Group 1-2. 

The refuge area into which a horizontal exit leads shall be 
provided with exits adequate to meet the occupant require- 
ments of this chapter, but not including the added occupant 
load imposed by persons entering it through horizontal exits 
from other areas. At least one refuge area exit shall lead directly 
to the exterior or to an exit enclosure. 

Exception: The adjoining compartment shall not be 
required to have a stairway or door leading directly outside, 
provided the refuge area into which a horizontal exit leads 
has stairways or doors leading directly outside and are so 
arranged that egress shall not require the occupants to return 
through the compartment from which egress originates. 



SECTION 1026 
EXTERIOR EXIT RAMPS AND STAIRWAYS 

1026.1 Exterior exit ramps and stairways. Exterior exit 
ramps and stairways serving as an element of a required means 
of egress shall comply with this section. 

Exception: Exterior exit ramps and stairways for outdoor 
stadiums complying with Section 1022.1, Exception 2. 

1026.2 Use in a means of egress. Exterior exit stairways shall 
not be used as an element of a required means of egress for 
Group 1-2 occupancies. For occupancies in other than Group 
1-2, exterior exit ramps and stairways shall be permitted as an 
element of a required means of egress fox buildings not exceed- 



ing six stories above grade plane or having occupied floors 
more than 75 feet (22 860 mm) above the lowest level of fire 
department vehicle access. 

1026.3 Open side. Exterior exit ramps and stairways serving 
as an element of a required means of egress shall be open on at 
least one side. An open side shall have a minimum of 35 square 
feet (3.3 m 2 ) of aggregate open area adjacent to each floor level 
and the level of each intermediate landing. The required open 
area shall be located not less than 42 inches (1067 mm) above 
the adjacent floor or landing level. 

1026.4 Side yards. The open areas adjoining exterior exit 
ramps or stairways shall be either yards, courts ox public ways; 
the remaining sides are permitted to be enclosed by the exterior 
walls of the building. 

1026.5 Location. Exterior exit ramps and stairways shall be 
located in accordance with Section 1027.3. 

1026.6 Exterior ramps and stairway protection. Exterior 
exit ramps and stairways shall be separated from the interior of 
the building as required in Section 1022.1. Openings shall be 
limited to those necessary for egress from normally occupied 
spaces. 

Exceptions: 

1. Separation from the interior of the building is not 
required for occupancies, other than those in Group 
R-l or R-2, in buildings that are no more than two sto- 
ries above grade plane where a level of exit discharge 
serving such occupancies is the first story above 
grade plane. 

2. Separation from the interior of the building is not 
required where the exterior ramp or stairway is 
served by an exterior ramp or balcony that connects 
two remote exterior stairways or other approved 
exits, with a perimeter that is not less than 50 percent 
open. To be considered open, the opening shall be a 
minimum of 50 percent of the height of the enclosing 
wall, with the top of the openings no less than 7 feet 
(2134 mm) above the top of the balcony. 

3. Separation from the interior of the building is not 
required for an exterior ramp or stairway located in a 
building or structure that is permitted to have unen- 
closed interior stairways in accordance with Section 
1022.1. 

4. Separation from the interior of the building is not 
required for exterior ramps or stairways connected to 
open-ended corridors, provided that Items 4.1 
through 4.4 are met: 

4.1. The building, including corridors and ramps 
and stairs, shall be equipped throughout with 
an automatic sprinkler system in accordance 
with Section 903.3.1.1 or 903.3.1.2. 

4.2. The open-ended corridors comply with Sec- 
tion 1018. 

4.3. The open-ended corridors are connected on 
each end to an exterior exit ramp or stairway 
complying with Section 1026. 



248 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



4.4. At any location in an open-ended corridor 
where a change of direction exceeding 45 de- 
grees (0.79 rad) occurs, a clear opening of not 
less than 35 square feet (3.3 m 2 ) or an exterior 
ramp or stairway shall be provided. Where 
clear openings are provided, they shall be lo- 
cated so as to minimize the accumulation of 
smoke or toxic gases. 



SECTION 1027 
EXIT DISCHARGE 

1027.1 General. Exits shall discharge directly to the exterior of 
the building. The exit discharge shall be at grade or shall pro- 
vide direct access to grade. The exit discharge shall not reenter 
a building. The combined use of Exceptions 1 and 2 below shall 
not exceed 50 percent of the number and capacity of the 
required exits. 

Exceptions: 

1. A maximum of 50 percent of the number and capacity 
of the exit enclosures is permitted to egress through 
areas on the level of discharge provided all of the fol- 
lowing are met: 

1.1. Such exit enclosures egress to a free and un- 
obstructed path of travel to an exterior exit 
door and such exitis readily visible and identi- 
fiable from the point of termination of the exit 
enclosure. 

1 .2. The entire area of the level of exit discharge is 
separated from areas below by construction 
conforming to the fire-resistance rating for 
the exit enclosure. 

1.3. The egress path from the exit enclosure on the 
level of exit discharge is protected throughout 
by an approved automatic sprinkler system. 
All portions of the level of exit discharge with 
access to the egress path shall either be pro- 
tected throughout with an automatic sprinkler 
system installed in accordance with Section 
903.3.1.1 or 903.3.1.2, or separated from the 
egress path in accordance with the require- 
ments for the enclosure of exits. 

2. A maximum of 50 percent of the number and capacity 
of the exit enclosures is permitted to egress through a 
vestibule provided all of the following are met: 

2.1. The entire area of the vestibule is separated 
from areas below by construction conforming 
to the fire -resistance rating for the exit enclo- 
sure. 

2.2. The depth from the exterior of the building is 
not greater than 10 feet (3048 mm) and the 
length is not greater than 30 feet (9144 mm) . 

2.3. The area is separated from the remainder of 
the lev el of exit discharge by construction pro- 
viding protection at least the equivalent of ap- 
proved wired glass in steel frames. 



2.4. The area is used only for means of egress and 
exits directly to the outside. 

3. Stairways in open parking garages complying with 
Section 1022.1, Exception 4, are permitted to egress 
through the op en parking garage at their levels of exit 
discharge. 

4. Horizontal exits complying with Section 1025 shall 
not be required to discharge directly to the exterior of 
the building. 

1027.2 Exit discharge capacity. The capacity of the exit dis- 
charge shall be not less than the required discharge capacity of 
the exits being served. 

1027.3 Exit discharge location. Exterior balconies, stairways 
and ramps shall be located at least 10 feet (3048 mm) from 
adjacent lot lines and from other buildings on the s.ame lot 
unless the adjacent building exterior walls and openings are 
protected in accordance with Section 704 based on fire separa- 
tion distance. 

1027.4 Exit discharge components. Exit discharge compo- 
nents shall be sufficiently open to the exterior so as to minimize 
the accumulation of smoke and toxic gases. 

1027.5 Egress courts. Egress courts serving as a portion of the 
exit discharge in the means of egress system shall comply With 
the requirements of Section 1027. 

1027.5.1 Width. The width of egress courts shall be deter- 
mined as specified in Section 1005.1, but such width shall 
not be less than 44 inches (1118 mm), except as specified 
herein. Egress courts serving Group R-3 and U occupancies 
shall not be less than 36 inches (914 mm) in width. The 
required width of egress courts shall be unobstructed to a 
height of 7 feet (2134 mm). 

Exception: Doors complying with Section 1005 .2. 

Where an egress court exceeds the minimum required 
width and the width of such egress court is then reduced 
along the path of exit travel, the reduction in width shall be 
gradual. The transition in width shall be affected by a guard 
not less than 36 inches (914 mm) in height and shall not cre- 
ate an angle of more than 30 degrees (0.52 rad) with respect 
to the axis of the egress courtaiong the path of egress travel. 
In no case shall the width of the egress courtbe less than the 
required minimum. 

1027.5.2 Construction and openings. Where an egress 
court serving a building or portion thereof is less than 10 
feet (3048 mm) in width, the egress court walls shall have 
not less than I-hom fire-resistance-rate d construction for a 
distance of 10 feet (3048 mm) above the floor of the court. 
Openings within such walls shall be protected by opening 
protectives having afire protection rating of not less than 3/ 4 
hour. 

Exceptions: 

1 . Egress courts serving an occupant load of less 
than 10. 

2. Egress courts serving Group R-3. 



2009 INTERNATIONAL BUILDING CODE® 



249 



MEANS OF EGRESS 



1 



1027.6 Access to a public way. The exit discharge shall pro- 
vide a direct and unobstructed access to a public way. 

Exception: Where access to a public way cannot be pro- 
vided, a safe dispersal area shall be provided where all of the 
following are met 

1. The area shall be of a size to accommodate at least 
5 square feet (0.46 m 2 ) for each person. 

2. The area shall be located on the same lot at least 50 
feet (15 240 mm) away from the building requiring 
egress. 

3. The area shall be permanently maintained and 
identified as a safe dispersal area. 

4. The area shall be provided with a safe and unob- 
structed path of travel from the building. 



SECTION 1028 
ASSEMBLY 

1028.1 General. Occupancies in Group A and assembly occu- 
pancies accessory to Group E which contain seats, tables, dis- 
plays, equipment or other material shall comply with this 
section. 

1028.1.1 Bleachers. Bleachers, grandstands and folding 
and telescopic seating, that are not building elements, shall 
comply with ICC 300. 

1028.2 Assembly main exit. Group A occupancies and assem- 
bly occupancies accessory to Group E occupancies that have an 
occupantloadof greater than 300 shall be provided with a main 
exit. The main exitshall be of sufficient width to accommodate 
not less than one-half of the occupantload, but such width shall 
not be less than the total required width of all means of egress 
leading to the exit. Where the building is classified as a Group 
A occupancy, the main exitshall front on at least one street or an 
unoccupied space of not less than 10 feet (3048 mm) in width 
that adjoins a street or public way 

Exception: In assembly occupancies where there is no 
well-defined main exitor where multiple main exits are pro- 
vided, exits shall be permitted to be distributed around the 
perimeter of the building provided that the total width of 
egress is not less than 100 percent of the required width. 

1028.3 Assembly other exits. In addition to having access to a 
main exit, each level in Group A occupancies or assembly 
occupancies accessory to Group E occupancies having an 
occupant load greater than 300, shall be provided with addi- 
tional means of egress that shall provide an egress capacity for 
at least one-half of the total occupant load served by that level 
and comply with Section 1015.2. 

Exception: In assembly occupancies where there is no 
well-defined main exitor where multiple main exits are pro- 
vided, exits shall be permitted to be distributed around the 
perimeter of the building, provided that the total width of 
egress is not less than 100 percent of the required width. 

1028.4 Foyers and lobbies. In Group A-I occupancies, where 
persons are admitted to the building at times when seats are not 
available, such persons shall be allowed to wait in a lobby or 
similar space, provided such lobby or similar space shall not 



encroach upon the required clear width of the means of egress. 
Such foyer, if not directly connected to a public street by all the 
main entrances or exits, shall have a straight and unobstructed 
corridor or path of travel to every such main entrance or exit. 

1028.5 Interior balcony and gallery means of egress. For 
balconies, galleries or press boxes having a seating capacity of 
50 or more located in Group A occupancies, at least two means 
of egress shall be provided, with one from each side of every 
balcony, gallery or press box and at least one leading directly to 
an exit. 

1028.5.1 Enclosure of openings. Interior stairways and 
other vertical openings shall be enclosed in an exit enclosure 
as provided in Section 1022.1, except that stairways are per- 
mitted to be open between the balcony, gallery or press box 
and the main assembly floor in occupancies such as the- 
aters, places of religious worship, auditoriums and sports 
facilities . At least one accessible means of egress is required 
from a balcony, gallery or press box level containing acces- 
sible seating locations in accordance with Section 1007.3 or 
1007.4. 

1028.6 Width of means of egress for assembly. The clear width 
of aisles and other means of egress shall comply with Section 
1028.6.1 where smoke-protected seatingis not provided and with 
Section 1028.6.2 or 1028.6.3 where smoke-protected seating is 
provided. The clear width shall be measured to walls, edges of 
seating and tread edges except for permitted projections. 

1028.6.1 Without smoke protection. The clear width of 
the means of egress shall provide sufficient capacity in 
accordance with all of the following, as applicable: 

1. At least 0.3 inch (7.6 mm) of width for each occupant 
served shall be provided on stairs having riser heights 
7 inches (178 mm) or less and tread depths 11 inches 
(279 mm) or greater, measured horizontally between 
tread nosings. 

2. At least 0.005 inch (0.127 mm) of additional stair 
width for each occupant shall be provided for each 0. 10 
inch (2.5 mm) of riser height above 7 inches (178 mm) . 

3. Where egress requires stair descent, at least 0.075 
inch (1.9 mm) of additional width for each occupant 
shall be provided on those portions of stairwidth hav- 
ing no handrail within a horizontal distance of 30 
inches (762 mm). 

4. Ramped means of egress, where slopes are steeper 
than one unit vertical in 12 units horizontal (8-percent 
slope), shall have at least 0.22 inch (5.6 mm) of clear 
width for each occupant served. Level or ramped 
means of egress, where slopes are not steeper than one 
unit vertical in 12 units horizontal (8-percent slope), 
shall have at least 0.20 inch (5.1 mm) of clear width 
for each occupant served. 

1028.6.2 Smoke-protected seating. The clear width of the 
means of egress for smoke-protected assembly seatingshaW 
not be less than the occupant load served by the egress ele- 
ment multiplied by the appropriate factor in Table 1028.6.2. 
The total number of seats specified shall be those within the 
space exposed to the same smoke-protected environment. 
Interpolation is permitted between the specific values 



250 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



shown. A life safety evaluation, complying with NFPA 101, 
shall be done for a facility utilizing the reduced width 
requirements of Table 1028.6.2 for smoke-protected assem- 
bly seating. 

Exception: For an outdoor smoke-protected assembly 
with an occupant I o ad not greater than 18,000, the clear 
width shall be determined using the factors in Section 
1028.6.3. 

1028.6.2.1 Smoke control. Means of egress serving a 
smoke-pr -otected assembly seating area, shall be provided 
with a smoke control system complying with Section 
909 or natural ventilation designed to maintain the 
smoke level at least 6 feet (1829 mm) above the floor of 
the means of egress. 

1028.6.2.2 Roof height. A smoke-protected assembly 
seating area with a roof shall have the lowest portion of 
the roof deck not less than 15 feet (4572 mm) above the 
highest aisle or aisle accessway. 

Exception: A roof canopy in an outdoor stadium 
shall be permitted to be less than 15 feet (4572 mm) 
above the highest aisle or aisle accessway provided 
that there are no objects less than 80 inches (2032 
mm) above the highest aisle or aisle accessway. 

1028.6.2.3 Automatic sprinklers. Enclosed areas with 
walls and ceilings in buildings or structures containing 
smoke-protected assembly seating shall be protected 
with an approved automatic sprinkler system in accor- 
dance with Section 903.3.1.1. 

Exceptions: 

1. The floor area used for contests, performances 
or entertainment provided the roof construction 
is more than 50 feet (15 240 mm) above the 
floor level and the use is restricted to low fire 
hazard uses. 

2. Press boxes and storage facilities less than 
1,000 square feet (93 m 2 ) in area. 

3. Outdoor seating facilities where seating and the 
means of egress in the seating area are essen- 
tially open to the outside. 



1028.6.3 Width of means of egress for outdoor 
smoke- protected assembly. The clear width in inches 
(mm) of aisles and other means of egress shall be not less 
than the total occupant load served by the egress element 
multiplied by 0.08 (2.0 mm) where egress is by aisles and 
stairs and multiplied by 0.06 (1 .52 mm) where egress is by 
ramps, corridors, tunnels or vomitories . 

Exception: The clear width in inches (mm) of aisles and 
other means of egress shall be permitted to comply with 
Section 1028.6.2 for the number of seats in the outdoor 
smoke-protected assembly where Section 1028.6.2 per- 
mits less width. 

1028.7 Travel distance. Exits and aisles shall be so located that 
the travel distance to an exit door shall not be greater than 200 
feet (60 960 mm) measured along the line of travel in 
nonsprinklered buildings. Travel distance shall not be more 
than 250 feet (76 200 mm) in sprinklered buildings. Where 
aisles are provided for seating, the distance shall be measured 
along the aisles and aisle accessway without travel over or on 
the seats. 

Exceptions: 

1. Smoke-protected assembly seating. The travel dis- 
tance from each seat to the nearest entrance to a 
vomitory or concourse shall not exceed 200 feet (60 
960 mm). The travel distance from the entrance to the 
vomitory or concourse to a stair, ramp or walk on the 
exterior of the building shall not exceed 200 feet (60 
960 mm). 

2. Open-air seating: The travel distance from each seat 
to the building exterior shall not exceed 400 feet (122 
m). The travel distance shall not be limited in facilities 
of Type I or 1 1 construction. 

1028.8 Common path of egress travel. The common path of 
egress travel shall not exceed 30 feet (9144 mm) from any seat 
to a point where an occupant has a choice of two paths of egress 
travel to two exits. 

Exceptions: 

1. For areas serving less than 50 occupants, the common 
path of egress travel shall not exceed 75 feet (22 860 
mm). 



TABLE 1028.6.2 
WIDTH OF AISLES FOR SMOKE-PROTECTED ASSEMBLY 



TOTAL NUMBER OF 
SEATS IN THE SMOKE- 
PROTECTED ASSEMBLY 
OCCUPANCY 


INCHES OF CLEAR WIDTH PER SEAT SERVED 


Stairs and aisle steps with 
handrails within 30 inches 


Stairs and aisle steps 
without handrails 
within 30 inches 


Passageways, doorways 

and ramps not steeper 

than 1 in 10 in slope 


Ramps steeper 
than 1 in 10 in slope 


Equal to or less than 5,000 


0.200 


0.250 


0.150 


0.165 


10,000 


0.130 


0.163 


0.100 


0.110 


15,000 


0.096 


0.120 


0.070 


0.077 


20,000 


0.076 


0.095 


0.056 


0.062 


Equal to or greater than 25,000 


0.060 


0.075 


0.044 


0.048 



For 51 : 1 inch = 25.4 mm. 



2009 INTERNATIONAL BUILDING CODE® 



251 



MEANS OF EGRESS 



2. For smoke-protected assembly seating, the common 
path of egress travel shall not exceed 50 feet (15 240 
mm). 

1028.8.1 Path through adjacent row. Where one of the 
two paths of travel is across the aisle through a row of seats 
to another aisle, there shall be not more than 24 seats 
between the two aisles, and the minimum clear width 
between rows for the row between the two aisles shall be 12 
inches (305 mm) plus 0.6 inch (15.2 mm) for each addi- 
tional seat above seven in the row between aisles. 

Exception: For smoke-protected assembly seating there 
shall not be more than 40 seats between the two aisles 
and the minimum clear width shall be 12 inches (305 
mm) plus 0.3 inch (7.6 mm) for each additional seat. 

1028.9 Assembly aisles are required. Every occupied portion 
of any occupancy in Group A or assembly occupancies acces- 
sory to Group E that contains seats, tables, displays, similar fix- 
tures or equipment shall be provided with aisles leading to exits 
or exit access doorways in accordance with this section. Aisle 
accessways for tables and seating shall comply with Section 
1017.4. 

1028.9.1 Minimum aisle width. The minimum clear width 
for aisles shall be as shown: 

1. Forty-eight inches (1219 mm) for aisle stairs having 
seating on each side. 

Exception: Thirty-six inches (914 mm) where the 
aisle serves less than 50 seats. 

2. Thirty-six inches (914 mm) for aisle stairs having 
seating on only one side. 

3. Twenty-three inches (584 mm) between an aisle stair 
handrail or guard and seating where the aisle is sub- 
divided by a handrail. 

4. Forty-two inches (1067 mm) for level or ramped 
aisles having seating on both sides. 

Exceptions: 

1. Thirty-six inches (914 mm) where the aisle 
serves less that 50 seats. 

2. Thirty inches (762 mm) where the aisle does 
not serve more than 14 seats. 

5. Thirty-six inches (914 mm) for level or ramped aisles 
having seating on only one side. 

Exceptions: 

1. Thirty inches (762 mm) where the aisle does 
not serve more than 14 seats. 

2. Twenty-three inches (584 mm) between an 
aisle stair handrail and seating where an 
aisle does not serve more than five rows on 
one side. 

1028.9.2 Aisle width. The aisle width shall provide suffi- 
cient egress capacity for the number of persons accommo- 
dated by the catchment area served by the aisle. The 
catchment area served by an aisle is that portion of the total 
space that is served by that section of the aisle. In establish- 
ing catchment areas, the assumption shall be made that there 



is a balanced use of all means of egress, with the number of 
persons in proportion to egress capacity. 

1028.9.3 Converging aisles. Where aisles converge to form 
a single path of egress travel, the required egress capacity of 
that path shall not be less than the combined required capac- 
ity of the converging aisles. 

1028.9.4 Uniform width. Those portions of aisles, where 
egress is possible in either of two directions, shall be uni- 
form in required width. 

1028.9.5 Assembly aisle termination. Each end of an aisle 
shall terminate at cross aisle, foyer, doorway, vomitory or 
concourse having access to an exit. 

Exceptions: 

1. Dead-end aisles shall not be greater than 20 feet 
(6096 mm) in length. 

2. Dead-end a isles longer than 20 feet (6096 mm) are 
permitted where seats beyond the 20-foot (6096 
mm) dead-end aisle are no more than 24 seats from 
another aisle, measured along a row of seats hav- 
ing a minimum clear width of 12 inches (305 mm) 
plus 0.6 inch (15.2 mm) for each additional seat 
above seven in the row. 

3. For smoke-protected assembly seating, the 
dead-end aisle length of vertical aisles shall not 
exceed a distance of 21 rows. 

4. For smoke-protected assembly seating, a longer 
dead-end aisle is permitted where seats beyond the 
21 -row dead-end aisle are not more than 40 seats 
from another aisle, measured along a row of seats 
having an aisle accessway with a minimum clear 
width of 12 inches (305 mm) plus 0.3 inch (7.6 
mm) for each additional seat above seven in the 
row. 

1028.9.6 Assembly aisle obstructions. There shall be no 
obstructions in the required width of aisles except for hand- 
rails as provided in Section 1028.13. 

1028.10 Clear width of aisle accessways serving seating. 
Where seating rows have 14 or fewer seats, the minimum clear 
aisle accessway width shall not be less than 12 inches (305 
mm) measured as the clear horizontal distance from the back of 
the row ahead and the nearest projection of the row behind. 
Where chairs have automatic or self-rising seats, the measure- 
ment shall be made with seats in the raised position. Where any 
chair in the row does not have an automatic or self-rising seat, 
the measurements shall be made with the seat in the down posi- 
tion. For seats with folding tablet arms, row spacing shall be 
determined with the tablet arm in the used position. 

Exception: For seats with folding tablet arms, row spacing 
is permitted to be determined with the tablet arm in the 
stored position where the tablet arm when raised manually 
to vertical position in one motion automatically returns to 
the stored position by force of gravity. 

1028.10.1 Dual access. For rows of seating served by aisles 
or doorways at both ends, there shall not be more than 100 
seats per row. The minimum clear width of 12 inches (305 
mm) between rows shall be increased by 0.3 inch (7.6 mm) 



252 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



for every additional seat beyond 14 seats, but the minimum 
clear width is not required to exceed 22 inches (559 mm). 

Exception: For smoke-protected assembly seating, the 
row length limits for a 12-inch- wide (305 mm) aisle 
accessway, beyond which the aisle accessway minimum 
clear width shall be increased, are in Table 1028.10.1. 

TABLE 1028.10.1 

SMOKE-PROTECTED 

ASSEMBLY AISLE ACCESSWAYS 



TOTAL NUMBER OF 
SEATS IN THE SMOKE- 
PROTECTED ASSEMBLY 
OCCUPANCY 


MAXIMUM NUMBER OF SEATS PER ROW 

PERMITTED TO HAVE A MINIMUM 12-INCH 

PI FAR WIDTH AI CI c a^^cooxa/av 


Aisle or doorway at 
both ends of row 


Aisle or doorway at 
one end of row only 


Less than 4,000 


14 


7 


4,000 


15 


7 


7,000 


16 


8 


10,000 


17 


8 


13,000 


18 


9 


16,000 


19 


9 


19,000 


20 


10 


22,000 and greater 


21 


11 



For 51 : 1 inch = 25.4 mm. 

1028.10.2 Single access. For rows of seating served by an 
aisle or doorway at only one end of the row, the minimum 
clear width of 12 inches (305 mm) between rows shall be 
increased by 0.6 inch (15.2 mm) for every additional seat 
beyond seven seats, but the minimum clear width is not 
required to exceed 22 inches (559 mm). 

Exception: For smoke-protected assembly seating, the 
row length limits for a 12-inch- wide (305 mm) aisle 
accessway, beyond which the aisle accessway minimum 
clear width shall be increased, are in Table 1028.10.1. 

1028.11 Assembly aisle walking surfaces. Aisles with a slope 
not exceeding one unit vertical in eight units horizontal 
(12.5-percent slope) shall consist of a ramp having a slip-resis- 
tant walking surface. Aisles with a slope exceeding one unit 
vertical in eight units horizontal (12. 5 -percent slope) shall con- 
sist of a series of risers and treads that extends across the full 
width of aisles and complies with Sections 1028.11.1 through 
1028.11.3. 

1028.11.1 Treads. Tread depths shall be a minimum of 11 
inches (279 mm) and shall have dimensional uniformity. 

Exception: The tolerance between adjacent treads shall 
not exceed 0.188 inch (4.8 mm). 

1028.1 1.2 Risers. Where the gradient of aisle stairs is to be 
the same as the gradient of adjoining seating areas, the riser 
height shall not be less than 4 inches (102 mm) nor more 
than 8 inches (203 mm) and shall be uniform within each 
flight. 

Exceptions: 

1. Riser height nonuniformity shall be limited to the 
extent necessitated by changes in the gradient of 
the adjoining seating area to maintain adequate 



sightlines. Where nonuniformities exceed 0.188 
inch (4.8 mm) between adjacent risers, the exact 
location of such nonuniformities shall be indicated 
with a distinctive marking stripe on each tread at 
the nosing or leading edge adjacent to the nonuni- 
form risers. Such stripe shall be a minimum of 1 
inch (25 mm), and a maximum of 2 inches (51 
mm), wide. The edge marking stripe shall be dis- 
tinctively different from the contrasting marking 
stripe. 

2. Riser heights not exceeding 9 inches (229 mm) 
shall be permitted where they are necessitated by 
the slope of the adjacent seating areas to maintain 
sightlines. 

1028.11.3 Tread contrasting marking stripe. A contrast- 
ing marking stripe shall be provided on each tread at the nos- 
ing or leading edge such that the location of each tread is 
readily apparent when viewed in descent. Such stripe shall 
be a minimum of 1 inch (25 mm), and a maximum of 2 
inches (51 mm), wide. 

Exception: The contrasting marking stripe is permitted 
to be omitted where tread surfaces are such that the loca- 
tion of each tread is readily apparent when viewed in 
descent. 

1028.12 Seat stability. In places of assembly, the seats shall be 
securely fastened to the floor. 

Exceptions: 

1. In places of assembly or portions thereof without 
ramped or tiered floors for seating and with 200 or 
fewer seats, the seats shall not be required to be fas- 
tened to the floor. 

2. In places of assembly or portions thereof with seating 
at tables and without ramped or tiered floors for seat- 
ing, the seats shall not be required to be fastened to the 
floor. 

3. In places of assembly or portions thereof without 
ramped or tiered floors for seating and with greater 
than 200 seats, the seats shall be fastened together in 
groups of not less than three or the seats shall be 
securely fastened to the floor. 

4. In places of assembly where flexibility of the seating 
arrangement is an integral part of the design and func- 
tion of the space and seating is on tiered levels, a max- 
imum of 200 seats shall not be required to be fastened 
to the floor. Plans showing seating, tiers and aisles 
shall be submitted for approval. 

5. Groups of seats within a place of assembly separated 
from other seating by railings, guards, partial height 
walls or similar barriers with level floors and having 
no more than 14 seats per group shall not be required 
to be fastened to the floor. 

6. Seats intended for musicians or other performers and 
separated by railings, guards, partial height walls or 
similar barriers shall not be required to be fastened to 
the floor. 



2009 INTERNATIONAL BUILDING CODE® 



253 



MEANS OF EGRESS 



1028.13 Handrails. Ramped aisles having a slope exceeding 
one unit vertical in 15 units horizontal (6.7 -percent slope) and 
aisle stairs shall be provided with handrails located either at 
the side or within the aisle width. 

Exceptions: 

1. Handrails are not required for ramped aisles having a 
gradient no greater than one unit vertical in eight units 
horizontal (12. 5 -percent slope) and seating on both 
sides. 

2. Handrails are not required if, at the side of the aisle, 
there is a guard that complies with the graspability 
requirements of handrails. 

3. Handrail extensions are not required at the top and 
bottom of aisle stairs and aisle ramp runs to permit 
crossovers within the aisles. 

1028.13.1 Discontinuous handrails. Where there is seat- 
ing on both sides of the aisle, the handrails shall be discon- 
tinuous with gaps or breaks at intervals not exceeding five 
rows to facilitate access to seating and to permit crossing 
from one side of the aisle to the other. These gaps or breaks 
shall have a clear width of at least 22 inches (559 mm) and 
not greater than 36 inches (914 mm), measured horizon- 
tally, and the handrail shall have rounded terminations or 
bends. 

1028.13.2 Intermediate handrails. Where handrails are 
provided in the middle of aisle stairs, there shall be an addi- 
tional intermediate handrailiocatQd approximately 12 inches 
(305 mm) below the main handrail. 

1028.14 Assembly guards. Assembly guards shall comply 
with Sections 1028.14.1 through 1028.14.3. 

1028.14.1 Cross aisles. Cross aisles located more than 30 
inches (762 mm) above the floor or grade below shall have 
guards in accordance with Section 1013. 

Where an elevation change of 30 inches (762 mm) or less 
occurs between a cross aisle and the adjacent floor or grade 
below, guards not less than 26 inches (660 mm) above the 
aisle floor shall be provided. 

Exception: Where the backs of seats on the front of the 
cross aisle project 24 inches (610 mm) or more above the 
adjacent floor of the aisle, aguardneed not be provided. 

1028.14.2 Sightline-constrained guard heights. Unless 
subject to the requirements of Section 1028 . 14.3, a fascia or 
railing system in accordance with the gua ^requirements of 
Section 1013 and having a minimum height of 26 inches 
(660 mm) shall be provided where the floor or footboard 
elevation is more than 30 inches (762 mm) above the floor or 
grade below and the fascia or railing would otherwise inter- 
fere with the sightlines of immediately adjacent seating. At 
bleachers, a guardmust be provided where required by ICC 
300. 

1028.14.3 Guards at the end of aisles. A fascia or railing 
system complying with the guard requirements of Section 
1013 shall be provided for the full width of the aisle where 
the foot of the aisle is more than 30 inches (762 mm) above 
the floor or grade below. The fascia or railing shall be a min- 
imum of 36 inches (914 mm) high and shall provide a mini- 



mum 42 inches (1067 mm) measured diagonally between 
the top of the rail and the nosing of the nearest tread. 

1028.15 Bench seating. Where bench seating is used, the num- 
ber of persons shall be based on one person for each 18 inches 
(457 mm) of length of the bench. 



SECTION 1029 
EMERGENCY ESCAPE AND RESCUE 

1029.1 General. In addition to the means of egress required by 
this chapter, provisions shall be made for emergency escape 
and rescue in Group R and 1-1 occupancies. Basements and 
sleeping rooms below the fourth story above grade plane shall 
have at least one exterior emergency escape and rescue open- 
ing in accordance with this section. Where basements contain 
one or more sleeping rooms, emergency escape and rescue 
openings shall be required in each sleeping room, but shall not 
be required in adjoining areas of the basement. Such openings 
shall open directly into a public way or to a yard or court that 
opens to a public way. 

Exceptions: 

1. In other than Group R-3 occupancies, buildings 
equipped throughout with an approved automatic 
sprinkler system in accordance with Section 
903.3.1.1 or 903.3.1.2. 

2. In other than Group R-3 occupancies, sleeping rooms 
provided with a door to a fire-resistance-rated corri- 
dor having access to two remote exits in opposite 
directions. 

3. The emergency escape and rescue opening is permit- 
ted to open onto a balcony within an atrium in accor- 
dance with the requirements of Section 404, provided 
the balcony provides access to an exit mid the dwell- 
ing unit or sleeping unit has a means of egress that is 
not open to the atrium. 

4. Basements with a ceiling height of less than 80 inches 
(2032 mm) shall not be required to have emergency 
escape and rescue windows. 

5. High-rise bUildings in accordance with Section 403. 

6. Emergency escape and rescue openings are not 
required from basements or sleeping rooms that have 
an exitdoor or exit access door that opens directly into 
a public wy or to a yard, court or exterior exit bal- 
cony that opens to a public way. 

1. Basements without habitable spaces and having no 
more than 200 square feet (18.6 m 2 ) in floor area shall 
not be required to have emergency escape windows. 

1029.2 Minimum size. Emergency escape and rescue open- 
ings shall have a minimum net clear opening of 5.7 square feet 
(0.53 m 2 ). 

Exception: The minimum net clear opening for emergency 
escape and rescue grade-floor openings shall be 5 square 
feet (0.46 m 2 ). 

1029.2.1 Minimum dimensions. The minimum net clear 
opening height dimension shall be 24 inches (610 mm). The 



254 



2009 INTERNATIONAL BUILDING CODE® 



MEANS OF EGRESS 



minimum net clear opening width dimension shall be 20 
inches (508 mm). The net clear opening dimensions shall be 
the result of normal operation of the opening. 

1029.3 Maximum height from floor. Emergency escape and 
rescue openings shall have the bottom of the clear opening not 
greater than 44 inches (1118 mm) measured from the floor. 

1029.4 Operational constraints. Emergency escape and res- 
cue openings shall be operational from the inside of the room 
without the use of keys or tools. Bars, grilles, grates or similar 
devices are permitted to be placed over emergency escape and 
rescue openings provided the minimum net clear opening size 
complies with Section 1029.2 and such devices shall be 
releasable or removable from the inside without the use of a 
key, tool or force greater than that which is required for normal 
operation of the escape and rescue opening. Where such bars, 
grilles, grates or similar devices are installed in existing build- 
ings, smoke alarms shall be installed in accordance with Sec- 
tion 907.2.11 regardless of the valuation of the alteration. 

1029.5 Window wells. An emergency escape andrescue open- 
ing with a finished sill height below the adjacent ground level 
shall be provided with a window well in accordance with Sec- 
tions 1029.5.1 and 1029.5.2. 

1029.5.1 Minimum size. The minimum horizontal area of 
the window well shall be 9 square feet (0.84 m 2 ) , with a min- 
imum dimension of 36 inches (914 mm). The area of the 
window well shall allow the emergency escape and rescue 
opening to be fully opened. 

1029.5.2 Ladders or steps. Window wells with a vertical 
depth of more than 44 inches (1118 mm) shall be equipped 
with an approved permanently affixed ladder or steps. Lad- 
ders or rungs shall have an inside width of at least 12 inches 
(305 mm), shall project at least 3 inches (76 mm) from the 
wall and shall be spaced not more than 18 inches (457 mm) 
on center (o.c.) vertically for the full height of the window 
well. The ladder or steps shall not encroach into the required 
dimensions of the window well by more than 6 inches (152 
mm). The ladder or steps shall not be obstructed by the 
emergency escape and rescue opening. Ladders or steps 
required by this section are exempt from the stairway 
requirements of Section 1009. 



2009 INTERNATIONAL BUILDING CODE® 255 



256 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 11 

ACCESSIBILITY 



SECTION 1101 
GENERAL 

1101.1 Scope. The provisions of this chapter shall control the 
design and construction of facilities for accessibility to physi- 
cally disabled persons. 

1101.2 Design. Buildings and facilities shall be designed and 
constructed to be accessible in accordance with this code and 
ICC A117.1. 



SECTION 1102 
DEFINITIONS 

1102.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in the code, 
have the meanings shown herein: 

ACCESSIBLE. A site, building, facilityor portion thereof that 
complies with this chapter. 

ACCESSIBLE ROUTE. A continuous, unobstructed path 
that complies with this chapter. 

ACCESSIBLE UNIT. A dwelling unit or sleeping unit that 
complies with this code and the provisions for Accessible units 
inICCA117.1. 

CIRCULATION PATH. An exterior or interior way of pas- 
sage from one place to another for pedestrians. 

COMMON USE. Interior or exterior circulation paths, 
rooms, spaces or elements that are not for public use and are 
made available for the shared use of two or more people. 

DETECTABLE WARNING. A standardized surface feature 
built in or applied to walking surfaces or other elements to warn 
visually impaired persons of hazards on a circulation path. 

DWELLING UNIT OR SLEEPING UNIT, MULTI- 
STORY. See definition for" Multistory unit." 

DWELLING UNIT OR SLEEPING UNIT, TYPE A. See 

definition for" Type A unit." 

DWELLING UNIT OR SLEEPING UNIT, TYPE B. See 

definition for" Type B unit." 

EMPLOYEE WORK AREA. All or any portion of a space 
used only by employees and only for work. Corridors, toilet 
rooms, kitchenettes and break rooms are not employee work 
areas. 

FACILITY. All or any portion of buildings, structures, site 
improvements, elements and pedestrian or vehicular routes 
located on a site. 

INTENDED TO BE OCCUPIED AS A RESIDENCE. This 
refers to a dwelling unitox sleeping unitthat can or will be used 
all or part of the time as the occupant's place of abode. 

MULTILEVEL ASSEMBLY SEATING. Seating that is 
arranged in distinct levels where each level is comprised of 



either multiple rows, or a single row of box seats accessed from 
a separate level. 

MULTISTORY UNIT. A dwelling unitox sleeping unitwiih 
habitable space located on more than one story. 

PUBLIC ENTRANCE. An entrance that is not a service 
entrance or a restricted entrance. 

PUBLIC-USE AREAS. Interior or exterior rooms or spaces 
that are made available to the general public. 

RESTRICTED ENTRANCE. An entrance that is made 
available for common use on a controlled basis, but not public 
use, and that is not a service entrance. 

SELF-SERVICE STORAGE FACILITY. Real property 
designed and used for the purpose of renting or leasing individ- 
ual storage spaces to customers for the purpose of storing and 
removing personal property on a self-service basis. 

SERVICE ENTRANCE. An entrance intended primarily for 
delivery of goods or services. 

SITE. A parcel of land bounded by a lot line or a designated 
portion of a public right-of-way. 

TYPE A UNIT. A dwelling unitox sleeping wmY designed and 
constructed for accessibility in accordance with this code and 
the provisions for Type A units in ICC A117.1. 

TYPE B UNIT. A dwelling unitox sleeping unit designed and 
constructed for accessibility in accordance with this code and 
the provisions for Type B units in ICC All 7. 1 , consistent with 
the design and construction requirements of the federal Fair 
Housing Act. 

WHEELCHAIR SPACE. A space for a single wheelchair and 
its occupant. 



SECTION 1103 
SCOPING REQUIREMENTS 

1103.1 Where required. Sites, buildings, structures, facilities, 
elements and spaces, temporary or permanent, shall be accessi- 
ble to persons with physical disabilities. 

1103.2 General exceptions. Sites, buildings, structures, facili- 
ties, elements and spaces shall be exempt from this chapter to 
the extent specified in this section. 

1103.2.1 Specific requirements. Accessibility is not 
required in buildings and facilities, or portions thereof, to 
the extent permitted by Sections 1104 through 1110. 

1103.2.2 Existing buildings. Existing buildings shall com- 
ply with Section 3411. 

1103.2.3 Employee work areas. Spaces and elements 
within employee work areas shall only be required to com- 
ply with Sections 907.5.2.3.2, 1007 and 1104.3.1 and shall 
be designed and constructed so that individuals with disabil- 
ities can approach, enter and exitthe work area. Work areas, 



2009 INTERNATIONAL BUILDING CODE® 



257 



ACCESSIBILITY 



or portions of work areas, other than raised courtroom sta- 
tions, that are less than 300 square feet (30 m 2 ) in area and 
elevated 7 inches (178 mm) or more above the ground or fin- 
ish floor where the elevation is essential to the function of 
the space shall be exempt from all requirements. 

1 103.2.4 Detached dwellings. Detached one- and two-fam- 
ily dwellings and accessory structures, and their associated 
sites and facilities, are not required to be accessible. 

1103.2.5 Utility buildings. Occupancies in Group U are 
exempt from the requirements of this chapter other than the 
following: 

1. In agricultural buildings, access is required to paved 
work areas and areas open to the general public. 

2. Private garages or carports that contain required 
accessible parking. 

1103.2.6 Construction sites. Structures, sites and equip- 
ment directly associated with the actual processes of con- 
struction including, but not limited to, scaffolding, bridging, 
materials hoists, materials storage or construction trailers 
are not required to be accessible. 

1 103.2.7 Raised areas. Raised areas used primarily for pur- 
poses of security, life safety or fire safety including, but not 
limited to, observation galleries, prison guard towers, fire 
towers or lifeguard stands, are not required to be accessible 
or to be served by an accessible route. 

1103.2.8 Limited access spaces. Nonoccupiable spaces 
accessed only by ladders, catwalks, crawl spaces, freight 
elevators or very narrow passageways are not required to be 
accessible. 

1103.2.9 Equipment spaces. Spaces frequented only by 
personnel for maintenance, repair or monitoring of equip- 
ment are not required to be accessible. Such spaces include, 
but are not limited to, elevator pits, elevator penthouses, 
mechanical, electrical or communications equipment 
rooms, piping or equipment catwalks, water or sewage treat- 
ment pump rooms and stations, electric substations and 
transformer vaults, and highway and tunnel utility facilities. 

1103.2.10 Single-occupant structures. Single-occupant 
structures accessed only by passageways below grade or 
elevated above grade including, but not limited to, toll 
booths that are accessed only by underground tunnels, are 
not required to be accessible. 

1103.2.11 Residential Group R-l. Buildings of Group R-l 
containing not more than five sleeping units for rent or hire 
that are also occupied as the residence of the proprietor are 
not required to be accessible. 

1103.2.12 Day care facilities. Where a day care facility 
(Groups A-3, E, 1-4 and R-3) is part of a dwelling unit, only 
the portion of the structure utilized for the day care facility is 
required to be accessible. 

1103.2.13 Live/work units. In live/work units constructed 
in accordance with Section 419, the portion of the unit uti- 
lized for nonresidential use is required to be accessible. The 
residential portion of the live/work unit is required to be 
evaluated separately in accordance with Sections 1107.6.2 
and 1107.7. 



1103.2.14 Detention and correctional facilities. In deten- 
tion and correctional facilities, common use areas that are 
used only by inmates or detainees and security personnel, 
and that do not serve holding cells or housing cells required 
to be accessible, are not required to be accessible or to be 
served by an accessible route. 

1103.2.15 Walk-in coolers and freezers. Walk-in coolers 
and freezers intended for employee use only are not 
required to be accessible. 



SECTION 1104 
ACCESSIBLE ROUTE 

1104.1 Site arrival points. Accessible routes within the site 
shall be provided from public transportation stops; accessible 
parking; accessible passenger loading zones; and public streets 
or sidewalks to the accessible building entrance served. 

Exception: Other than in buildings or facilities containing 
or serving Type B units, an accessible route shall not be 
required between site arrival points and the building or facil- 
ity entrance if the only means of access between them is a 
vehicular way not providing for pedestrian access. 

1104.2 Within a site. At least one accessible route shall con- 
nect accessible buildings, accessible facilities, accessible ele- 
ments and accessible spaces that are on the same site. 

Exception: An accessible route is not required between 
accessible buildings, accessible facilities, accessible ele- 
ments and accessible spaces that have, as the only means of 
access between them, a vehicular way not providing for 
pedestrian access. 

1104.3 Connected spaces. When a building or portion of a 
building is required to be accessible, an accessible route shall 
be provided to each portion of the building, to accessiblebxxild- 
ing entrances connecting accessible pedestrian walkways and 
the public way. 

Exceptions: 

1. In assembly areas with fixed seating, an accessible 
route shall not be required to serve levels where 
wheelchair spaces are not provided. 

2. In Group 1-2 facilities, doors to sleeping units shall be 
exempted from the requirements for maneuvering 
clearance at the room side provided the door is a mini- 
mum of 44 inches (1118 mm) in width. 

1104.3.1 Employee work areas. Common use circulation 
paths within employee work areas shall be accessible 
routes. 

Exceptions: 

1. Common use circulation paths, located within 
employee work areas that are less than 300 square 
feet (27.9 m 2 ) in size and defined by permanently 
installed partitions, counters, casework or furnish- 
ings, shall not be required to be accessible routes. 

2. Common use circulation paths, located within 
employee work areas, that are an integral compo- 



258 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



nent of equipment, shall not be required to be 
accessible routes. 

3. Common use circulation paths, located within 
exterior employee work areas that are fully 
exposed to the weather, shall not be required to be 
accessible routes. 

1104.3.2 Press boxes. Press boxes in assembly areas shall 
be on an accessible route. 

Exceptions: 

1. An accessible route shall not be required to press 
boxes in bleachers that have points of entry at only 
one level, provided that the aggregate area of all 
press boxes is 500 square feet (46 m 2 ) maximum. 

2. An accessible route shall not be required to 
free-standing press boxes that are elevated above 
grade 12 feet (3660 mm) minimum provided that 
the aggregate area of all press boxes is 500 square 
feet (46 m 2 ) maximum. 

1 104.4 Multilevel buildings and facilities. At least one acces- 
sible route shall connect each accessible level, including mez- 
zanines, in multilevel buildings and facilities. 

Exceptions: 

1. An accessible route is not required to stories and mez- 
zanines that have an aggregate area of not more than 
3,000 square feet (278.7 m 2 ) and are located above 
and below accessible levels. This exception shall not 
apply to: 

1.1. Multiple tenant facilities of Group M occu- 
pancies containing five or more tenant spaces; 

1.2. Levels containing offices of health care pro- 
viders (Group B or I); or 

1.3. Passenger transportation facilities and air- 
ports (Group A- 3 or B). 

2. Levels that do not contain accessible elements or 
other spaces as determined by Section 1107 or 1108 
are not required to be served by an accessible route 
from an accessible level. 

3. In air traffic control towers, an accessible route is not 
required to serve the cab and the floor immediately 
below the cab. 

4. Where a two- story building or facility has one story 
with an occupant load of five or fewer persons that 
does not contain public use space, that story shall not 
be required to be connected by an accessible route to 
the story above or below. 

5. Vertical access to elevated employee work stations 
within a courtroom is not required at the time of initial 
construction, provided a ramp, lift or elevator com- 
plying with ICC A117.1 can be installed without 
requiring reconfiguration or extension of the court- 
room or extension of the electrical system. 

1104.5 Location. Accessible routes shall coincide with or be 
located in the same area as a general circulation path. Where 
the circulation path is interior, the accessible route shall also be 



interior. Where only one accessible route is provided, the 
accessible route shall not pass through kitchens, storage 
rooms, restrooms, closets or similar spaces. 

Exceptions: 

1. Accessible routes from parking garages contained 
within and serving Type B units are not required to be 
interior. 

2. A single accessible route is permitted to pass through 
a kitchen or storage room in an Accessible unit, Type 
A unit or Type B unit. 

1104.6 Security barriers. Security barriers including, but not 
limited to, security bollards and security check points shall not 
obstruct a required accessible route or accessible means of 
egress. 

Exception: Where security barriers incorporate elements 
that cannot comply with these requirements, such as certain 
metal detectors, fluoroscopes or other similar devices, the 
accessible route shall be permitted to be provided adjacent 
to security screening devices. The accessible route shall 
permit persons with disabilities passing around security 
barriers to maintain visual contact with their personal items 
to the same extent provided others passing through the secu- 
rity barrier. 



SECTION 1105 
ACCESSIBLE ENTRANCES 

1105.1 Public entrances. In addition to accessible entrances 
required by Sections 1105.1.1 through 1105.1.6, at least 60 
percent of all public entrances shall be accessible. 

Exceptions: 

1. An accessible entrance is not required to areas not 
required to be accessible. 

2. Loading and service entrances that are not the only 
entrance to a tenant space. 

1105.1.1 Parking garage entrances. Where provided, 
direct access for pedestrians from parking structures to 
buildings or facility entrances shall be accessible. 

1105.1.2 Entrances from tunnels or elevated walkways. 
Where direct access is provided for pedestrians from a 
pedestrian tunnel or elevated walkway to a building or facil- 
ity, at least one entrance to the building or facility from each 
tunnel or walkway shall be accessible. 

1105.1.3 Restricted entrances. Where restricted entrances 
are provided to a building or facility, at least one restricted 
entrance to the building or facility shall be accessible. 

1105.1.4 Entrances for inmates or detainees. Where 
entrances used only by inmates or detainees and security 
personnel are provided atjudicial facilities, detention facili- 
ties or correctional facilities, at least one such entrance shall 
be accessible. 

1105.1.5 Service entrances. If a service entrance is the 
only entrance to a building or a tenant space in a facility, that 
entrance shall be accessible. 



2009 INTERNATIONAL BUILDING CODE® 



259 



ACCESSIBILITY 



1105.1.6 Tenant spaces, dwelling units and sleeping 
units. At least one accessible entrance shall be provided to 
each tenant, dwelling unit and sleeping unit in a facility. 

Exceptions: 

1. An accessible entrance is not required to tenants 
that are not required to be accessible. 

2. An accessible entrance is not required to dwelling 
units and sleeping units that are not required to be 
Accessible units, Type A units or Type B units. 



SECTION 1106 
PARKING AND PASSENGER LOADING FACILITIES 

1106.1 Required. Where parking is provided, accessiblepark- 
ing spaces shall be provided in compliance with Table 1 106. 1, 
except as required by Sections 1106.2 through 1106.4. Where 
more than one parking facility is provided on a site, the number 
of parking spaces required to be accessible shall be calculated 
separately for each parking facility. 

Exception: This section does not apply to parking spaces 
used exclusively for buses, trucks, other delivery vehicles, 
law enforcement vehicles or vehicular impound and motor 
pools where lots accessed by the public are provided with an 
accessible passenger loading zone. 

TABLE 1106.1 
ACCESSIBLE PARKING SPACES 



TOTAL PARKING 
SPACES PROVIDED 


REQUIRED MINIMUM NUMBER 
OF ACCESSIBLE SPACES 


lto 25 


1 


26 to 50 


2 


51 to 75 


3 


76 to 100 


4 


101 to 150 


5 


151 to 200 


6 


201 to 300 


7 


301 to 400 


8 


401 to 500 


9 


501 to 1,000 


2% of total 


1,001 and over 


20, plus one for each 100, 
or fraction thereof, over 1,000 



1106.2 Groups R-2 and R-3. At least 2 percent, but not less 
than one, of each type of parking space provided for occupan- 
cies in Groups R-2 and R-3, which are required to have Acces- 
sible, Type A or Type B dwelling or sleeping units, shall be 
accessible. Where parking is provided within or beneath a 
building, accessible parking spaces shall also be provided 
within or beneath the building. 

1106.3 Hospital outpatient facilities. At least 10 percent, but 
not less than one, of patient and visitor parking spaces provided 
to serve hospital outpatient facilities shall be accessible. 

1106.4 Rehabilitation facilities and outpatient physical 
therapy facilities. At least 20 percent, but not less than one, of 
the portion of patient and visitor parking spaces serving reha- 



bilitation facilities specializing in treating conditions that 
affect mobility and outpatient physical therapy facilities shall 
be accessible. 

1106.5 Van spaces. For every six or fraction of six accessible 
parking spaces, at least one shall be a van-accessible parking 
space. 

Exception: In Group R-2 and R-3 occupancies, van-acces- 
sible spaces located within private garages shall be permit- 
ted to have vehicular routes, entrances, parking spaces and 
access aisles with a minimum vertical clearance of 7 feet 
(2134 mm). 

1106.6 Location. Accessible parking spaces shall be located 
on the shortest accessible route of travel from adjacent parking 
to an accessible building entrance. In parking facilities that do 
not serve a particular building, accessible parking spaces shall 
be located on the shortest route to an accessible pedestrian 
entrance to the parking facility. Where buildings have multiple 
accessible entrances with adjacent parking, accessible parking 
spaces shall be dispersed and located near the accessible 
entrances. 

Exceptions: 

1. In multilevel parking structures, van-accessible park- 
ing spaces are permitted on one level. 

2. Accessible parking spaces shall be permitted to be 
located in different parking facilities if substantially 
equivalent or greater accessibility is provided in 
terms of distance from an accessible entrance or 
entrances, parking fee and user convenience. 

1106.7 Passenger loading zones. Passenger loading zones 
shall be designed and constructed in accordance with ICC 
A117.1. 

1106.7.1 Continuous loading zones. Where passenger 
loading zones are provided, one passenger loading zone in 
every continuous 100 linear feet (30.4 m) maximum of load- 
ing zone space shall be accessible. 

1 106.7.2 Medical facilities. A passenger loading zone shall 
be provided at an accessible entrance to licensed medical 
and long-term care facilities where people receive physical 
or medical treatment or care and where the period of stay 
exceeds 24 hours. 

1 106.7.3 Valet parking. A passenger loading zone shall be 
provided at valet parking services. 

1106.7.4 Mechanical access parking garages. MeChani- 1 
cal access parking garages shall provide at least one passen- 
ger loading zone at vehicle drop-off and vehicle pick-up 
areas. 



SECTION 1107 
DWELLING UNITS AND SLEEPING UNITS 

1107.1 General. In addition to the other requirements of this 
chapter, occupancies having dwelling units or sleeping units 
shall be provided with accessible features in accordance with 
this section. 



260 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



I 



1107.2 Design. Dwelling units and sleeping units that are 
required to be Accessible units, Type A units and Type B units 
shall comply with the applicable portions of Chapter 10 of ICC 
A117.1. Units required to be Type A units are permitted to be 
designed and constructed as Accessible units. Units required to 
be Type B units are permitted to be designed and constructed as 
Accessible units or as Type A units. 

1107.3 Accessible spaces. Rooms and spaces available to the 
general public or available for use by residents and serving 
Accessible units, Type A units or Type B units shall be accessi- 
ble. Accessible spaces shall include toilet and bathing rooms, 
kitchen, living and dining areas and any exterior spaces, 
including patios, terraces and balconies. 

Exceptions: 

1. Recreational facilities in accordance with Section 
1109.14. 

2. In Group 1-2 facilities, doors to sleeping units shall be 
exempted from the requirements for maneuvering 
clearance at the room side provided the door is a mini- 
mum of 44 inches (1118 mm) in width. 

1107.4 Accessible route. At least one accessible route shall 
connect accessible building or facility entrances with the pri- 
mary entrance of each Accessible unit, Type A unit Mid Type B 
unit within the building or facility and with those exterior and 
interior spaces and facilities that serve the units. 

Exceptions: 

1. If due to circumstances outside the control of the 
owner, either the slope of the finished ground level 
between accessible facilities and buildings exceeds 
one unit vertical in 12 units horizontal (1: 12), or 
where physical barriers or legal restrictions prevent 
the installation of an accessible route, a vehicular 
route with parking that complies with Section 1 106 at 
each public or common use facility or building is per- 
mitted in place of the accessible route. 

2. Exterior decks, patios or balconies that are part of 
Type B units and have impervious surfaces, and that 
are not more than 4 inches (102 mm) below the fin- 
ished floor level of the adjacent interior space of the 
unit. 

1 107.5 Group I . Accessible units and Type B units shall be pro- 
vided in Group I occupancies in accordance with Sections 
1107.5.1 through 1107.5.5. 

1107.5.1 Group 1-1. Accessible units and Type B units shall 
be provided in Group 1-1 occupancies in accordance with 
Sections 1107.5.1.1 and 1107.5.1.2. 

1107.5.1.1 Accessible units. At least 4 percent, but not 
less than one, of the dwelling units and sleeping units 
shall be Accessible units. 

1 107.5.1.2 Type B units. In structures with four or more 
dwelling units or sleeping units intended to be occupied 



as a residence, every dwelling unit and sleeping unit 
intended to be occupied as a residence shall be a Type B 
unit. 

Exception: The number of Type B units is permitted 
to be reduced in accordance with Section 1107.7. 

1107.5.2 Group 1-2 nursing homes. Accessible units and 
Type B units shall be provided in nursing homes of Group 
1-2 occupancies in accordance with Sections 1107.5.2.1 and 
1107.5.2.2. 

1107.5.2.1 Accessible units. At least 50 percent but not 
less than one of each type of the dwelling units and sleep- 
ing units shall be Accessible units. 

1 107.5.2.2 Type B units. In structures with four or more 
dwelling units or sleeping units intended to be occupied 
as a residence, every dwelling unit and sleeping unit 
intended to be occupied as a residence shall be a Type B 
unit. 

Exception: The number of Type B units is permitted 
to be reduced in accordance with Section 1107.7. 

1107.5.3 Group 1-2 hospitals. Accessible units and Type B 
units shall be provided in general-purpose hospitals, psychi- 
atric facilities, detoxification facilities and residential 
care/assisted living facilities of Group 1-2 occupancies in 
accordance with Sections 1107.5.3.1 and 1107.5.3.2. 

1107.5.3.1 Accessible units. At least 10 percent, but not 
less than one, of the dwelling units and sleeping units 
shall be Accessible units. 

1 107.5.3.2 Type B units. In structures with four or more 
dwelling units or sleeping units intended to be occupied 
as a residence, every dwelling unit and sleeping unit 
intended to be occupied as a residence shall be a Type B 
unit. 

Exception: The number of Type B units is permitted 
to be reduced in accordance with Section 1107.7. 

1107.5.4 Group 1-2 rehabilitation facilities. In hospitals 
and rehabilitation facilities of Group 1-2 occupancies which 
specialize in treating conditions that affect mobility, or units 
within either which specialize in treating conditions that 
affect mobility, 100 percent of the dwelling units and sleep- 
ing units shall be Accessible units. 

1107.5.5 Group 1-3. Accessible units shall be provided in 
Group 1-3 occupancies in accordance with Sections 
1107.5.5.1 through 1107.5.5.3. 

1107.5.5.1 Group 1-3 sleeping units. In Group 1-3 occu- 
pancies, at least 2 percent, but not less than one, of the 
dwelling units and sleeping units shall be Accessible 
units. 

1107.5.5.2 Special holding cells and special housing 
cells or rooms. In addition to the Accessible units required 
by Section 1107.5.5.1, where special holding cells or spe- 



i 



2009 INTERNATIONAL BUILDING CODE® 



261 



ACCESSIBILITY 



cial housing cells or rooms are provided, at least one 
serving each purpose shall be an Accessible unit. Cells or 
rooms subject to this requirement include, but are not lim- 
ited to, those used for purposes of orientation, protective 
custody, administrative or disciplinary detention or segre- 
gation, detoxification and medical isolation. 

Exception: Cells or rooms specially designed with- 
out protrusions and that are used solely for purposes 
of suicide prevention shall not be required to include 
grab bars. 

1107.5.5.3 Medical care facilities. Patient sleeping 
units or cells required to be Accessible units in medical 
care facilities shall be provided in addition to any medi- 
cal isolation cells required to comply with Section 
1107.5.5.2. 

1107.6 Group R. Accessible units, Type A units and Type B 
units shall be provided in Group R occupancies in accordance 
with Sections 1107.6.1 through 1107.6.4. 

1107.6.1 Group R-l. Accessible units and Type B units 
shall be provided in Group R-l occupancies in accordance 
with Sections 1107.6.1.1 and 1107.6.1.2. 

1107.6.1.1 Accessible units. In Group R-l occupancies, 
Accessible dwelling units and sleeping units shall be pro- 
vided in accordance with Table 1107.6.1.1. All R-l units 
on a site shall be considered to determine the total num- 
ber of Accessible units. Accessible units shall be dis- 
persed among the various classes of units. Roll-in 
showers provided in Accessible units shall include a per- 
manently mounted folding shower seat. 

1 107.6.1.2 Type B units. In structures with four or more 
dwelling units or sleeping units intended to be occupied 
as a residence, every dwelling unit and sleeping unit 
intended to be occupied as a residence shall be a Type B 
unit. 

Exception: The number of Type B units is permitted 
to be reduced in accordance with Section 1107.7. 



1107.6.2 Group R-2. Accessible units, Type A units and 
Type B units shall be provided in Group R-2 occupancies in 
accordance with Sections 1107.6.2.1 and 1107.6.2.2. 

1107.6.2.1 Apartment houses, monasteries and con- 
vents. Type A units and Type B units shall be provided in 
apartment houses, monasteries and convents in accor- 
dance with Sections 1107.6.2.1.1 and 1107.6.2.1.2. 

1107.6.2.1.1 Type A units. In Group R-2 occupan- 
cies containing more than 20 dwelling units or sleep- 
ing units, at least 2 percent but not less than one of the 
units shall be a Type A unit. All R-2 units on a site shall 
be considered to determine the total number of units 
and the required number of Type A units. Type A units 
shall be dispersed among the various classes of units. 

Exceptions: 

1. The number of Type A units is permitted to 
be reduced in accordance with Section 
1107.7. 

2. Existing structures on a site shall not con- 
tribute to the total number of units on a site. 

1107.6.2.1.2 Type B units. Where there are four or 
more dwelling units or sleeping units intended to be 
occupied as a residence in a single structure, every 
dwelling unit and sleeping unit intended to be occu- 
pied as a residence shall be a Type B unit. 

Exception: The number of Type B units is permit- 
ted to be reduced in accordance with Section 
1107.7. 

1107.6.2.2 Group R-2 other than apartment houses, 
monasteries and convents. In Group R-2 occupancies, 
other than apartment houses, monasteries and convents, 
Accessible units and Type B units shall be provided in 
accordance with Sections 1107.6.2.2.1 and 1107.6.2.2.2. 



TABLE 1107.6.1.1 
ACCESSIBLE DWELLING AND SLEEPING UNITS 



TOTAL NUMBER OF 
UNITS PROVIDED 


MINIMUM REQUIRED NUMBER OF 

ACCESSIBLE UNITS WITHOUT 

ROLL-IN SHOWERS 


MINIMUM REQUIRED NUMBER OF 

ACCESSIBLE UNITS WITH 

ROLL-IN SHOWERS 


TOTAL NUMBER OF 
REQUIRED ACCESSIBLE UNITS 


lto 25 


1 





1 


26 to 50 


2 





2 


51 to 75 


3 


1 


4 


76 to 100 


4 


1 


5 


101 to 150 


5 


2 


7 


151 to 200 


6 


2 


8 


201 to 300 


7 


3 


10 


301 to 400 


8 


4 


12 


401 to 500 


9 


4 


13 


501 to 1,000 


2% of total 


1% of total 


3% of total 


Over 1,000 


20, plus 1 for each 100, or 
fraction thereof, over 1,000 


10 plus 1 for each 100, or 
fraction thereof, over 1,000 


30 plus 2 for each 100, or 
fraction thereof, over 1,000 



262 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



1107.6.2.2.1 Accessible units. Accessible dwelling 
units and sleeping units shall be provided in accor- 
dance with Table 1107.6.1.1. 

1107.6.2.2.2 Type B units. Where there are four or 
more dwelling units or sleeping units intended to be 
occupied as a residence in a single structure, every 
dwelling unit and every sleeping unit intended to be 
occupied as a residence shall be a Type B unit. 

Exception: The number of Type B units is permit- 
ted to be reduced in accordance with Section 
1107.7. 

1107.6.3 Group R-3. In Group R-3 occupancies where 
there are four or more dwelling units or sleeping units 
intendedto be occupiedas a residence in a single structure, 
every dwelling unit and sleeping unit intended to be occu- 
piedas a residence shall be a Type B unit. 

Exception: The number of Type B units is permitted to 
be reduced in accordance with Section 1107.7. 

1107.6.4 Group R-4. Accessible units and Type B units 
shall be provided in Group R-4 occupancies in accordance 
with Sections 1107.6.4.1 and 1107.6.4.2. 

1 107.6.4.1 Accessible units. At least one of the dwelling 
or sleeping units shall be an Accessible unit. 

1107.6.4.2 Type B units. In structures with four or more 
dwelling units or sleeping units intendedto be occupied 
as a residence, every dwelling unit and sleeping unit 
intendedto be occupiedas a residence shall be a Type B 
unit. 

Exception: The number of Type B units is permitted 
to be reduced in accordance with Section 1107.7. 

1107.7 General exceptions. Where specifically permitted by 
Section 1107.5 or 1107.6, the required number of Type A units 
and Type B units is permitted to be reduced in accordance with 
Sections 1107.7.1 through 1107.7.5. 

1107.7.1 Structures without elevator service. Where no 
elevator service is provided in a structure, only the dwelling 
units and sleeping units that are located on stories indicated 
in Sections 1107.7.1.1 and 1107.7.1.2 are required to be 
Type A units and Type B units, respectively. The number of 
Type A units shall be determined in accordance with Section 
1107.6.2.1.1. 

1107.7.1.1 One story with Type B units required. At 
least one story containing dwelling units or sleeping 
units intendedto be occupiedas a residence shall be pro- 
vided with an accessible entrance from the exterior of the 
structure and all units intendedto be occupiedas a resi- 
dence on that story shall be Type B units. 

1 107.7.1.2 Additional stories with Type B units. On all 
other stories that have a building entrance in proximity to 
arrival points intended to serve units on that story, as 
indicated in Items 1 and 2, all dwelling units and sleeping 
units intended to be occupied as a residence served by 
that entrance on that story shall be Type B units. 

1. Where the slopes of the undisturbed site measured 
between the planned entrance and all vehicular or 



pedestrian arrival points within 50 feet (15 240 
mm) of the planned entrance are 10 percent or less, 
and 

2. Where the slopes of the planned finished grade 
measured between the entrance and all vehicular 
or pedestrian arrival points within 50 feet (15 240 
mm) of the planned entrance are 10 percent or less. 

Where no such arrival points are within 50 feet (15 240 
mm) of the entrance, the closest arrival point shall be 
used unless that arrival point serves the storyrequired by 
Section 1107.7.1.1. 

1107.7.2 Multistory units. A multistory dwelling or sleep- 
ing unit which is not provided with elevator service is not 
required to be a Type B unit. Where a multistory unit is pro- 
vided with external elevator service to only one floor, the 
floor provided with elevator service shall be the primary 
entry to the unit, shall comply with the requirements for a 
Type B unit and a toilet facility shall be provided on that 
floor. 

1107.7.3 Elevator service to the lowest story with units. 
Where elevator service in the building provides an accessi- 
ble route only to the lowest story containing dwelling or 
sleeping units intendedto be occupiedas a residence, only 
the units on that storywhich are intendedto be occupiedas a 
residence are required to be Type B units. 

1107.7.4 Site impracticality. On a site with multiple 
nonelevator buildings, the number of units required by Sec- 
tion 1 107.7.1 to be Type B units is permitted to be reduced to 
a percentage which is equal to the percentage of the entire 
site having grades, prior to development, which are less than 
10 percent, provided that all of the following conditions are 
met: 

1. Not less than 20 percent of the units required by Sec- 
tion 1107.7.1 on the site are Type B units; 

2. Units required by Section 1107.7.1, where the slope 
between the building entrance serving the units on 
that story and a pedestrian or vehicular arrival point is 
no greater than 8.33 percent, are Type B units; 

3. Units required by Section 1107.7.1, where an ele- 
vated walkway is planned between a building 
entrance serving the units on that story and a pedes- 
trian or vehicular arrival point and the slope between 
them is 10 percent or less are Type B units; and 

4. Units served by an elevator in accordance with Sec- 
tion 1107.7.3 are Type B units. 

1107.7.5 Design flood elevation. The required number of 
Type A units and Type B units shall not apply to a site where 
the required elevation of the lowest floor or the lowest hori- 
zontal structural building members of nonelevator buildings 
are at or above the design flood elevation resulting in: 

1. A difference in elevation between the minimum 
required floor elevation at the primary entrances and 
vehicular and pedestrian arrival points within 50 feet 
(15 240 mm) exceeding 30 inches (762 mm), and 

2. A slope exceeding 10 percent between the minimum 
required floor elevation at the primary entrances and 



2009 INTERNATIONAL BUILDING CODE® 



263 



ACCESSIBILITY 



I 



vehicular and pedestrian arrival points within 50 feet 
(15.24 m). 

Where no such arrival points are within 50 feet (15.24 m) 
of the primary entrances, the closest arrival points shall be 
used. 



SECTION 1108 
SPECIAL OCCUPANCIES 

1108.1 General. In addition to the other requirements of this 
chapter, the requirements of Sections 1108.2 through 1108.4 
shall apply to specific occupancies. 

1108.2 Assembly area seating. Assembly areas with fixed 
seating shall comply with Sections 1108.2.1 through 1108.2.8. 
Dining areas shall comply with Section 1108.2.9. In addition, 
lawn seating shall comply with Section 1108.2.6. 

1108.2.1 Services. If a service or facility is provided in an 
area that is not accessible, the same service or facility shall 
be provided on an accessible level and shall be accessible. 

1108.2.2 Wheelchair spaces. In theaters, bleachers, grand- 
stands, stadiums, arenas and other fixed seating assembly 
areas, accessible wheelchair spaces complying with ICC 
A 11 7.1 shall be provided in accordance with Sections 
1108.2.2.1 through 1108.2.2.4. 

1108.2.2.1 General seating. Wheelchair spaces shall be 
provided in accordance with Table 1108.2.2.1. 

1108.2.2.2 Luxury boxes, club boxes and suites. In 
each luxury box, club box, and suite within arenas, stadi- 
ums and grandstands, wheelchair spaces shall be pro- 
vided in accordance with Table 1108.2.2.1. 

1108.2.2.3 Other boxes. In boxes other than those 
required to comply with Section 1108.2.2.2, the total 
number of wheelchair spaces provided shall be deter- 
mined in accordance with Table 1108.2.2.1. Wheelchair 
spaces shall be located in not less than 20 percent of all 
boxes provided. 

TABLE 1108.2.2.1 
ACCESSIBLE WHEELCHAIR SPACES 



CAPACITY OF SEATING 
IN ASSEMBLY AREAS 


MINIMUM REQUIRED NUMBER OF 
WHEELCHAIR SPACES 


4 to 25 


1 


26 to 50 


2 


51 to 100 


4 


101 to 300 


5 


301 to 500 


6 


501 to 5,000 


6, plus 1 for each 150, or fraction 
thereof, between 501 through 5,000 


5,001 and over 


36 plus 1 for each 200, or fraction 
thereof, over 5,000 



1108.2.2.4 Team or player seating. At least one wheel- 
chair space shall be provided in team or player seating 
areas serving areas of sport activity. 

Exception: Wheelchair spaces shall not be required 
in team or player seating areas serving bowling lanes 



that are not required to be located on an accessible 
route in accordance with Section 1109.14.4.1. 

1108.2.3 Companion seats. At least one companion seat 
complying with ICC A117.1 shall be provided for each 
wheelchair space required by Sections 1108.2.2.1 through 
1108.2.2.3. 

1108.2.4 Dispersion of wheelchair spaces in multilevel 
assembly seating areas. In multilevel assembly seating 
areas, wheelchair spaces shall be provided on the main floor 
level and on one of each two additional floor or mezzanine 
levels. Wheelchair spaces shall be provided in each luxury 
box, club box and suite within assembly facilities. 

Exceptions: 

1. In multilevel assembly spaces utilized for worship 
services where the second floor or mezzanine level 
contains 25 percent or less of the total seating 
capacity, wheelchair spaces shall be permitted to 
all be located on the main level. 

2. In multilevel assembly seating where the second 
floor or mezzanine level provides 25 percent or 
less of the total seating capacity and 300 or fewer 
seats, all wheelchair spaces shall be permitted to 
be located on the main level. 

3. Wheelchair spaces in team or player seating serv- 
ing areas of sport activity are not required to be dis- 
persed. 

1108.2.5 Designated aisle seats. At least 5 percent, but not 
less than one, of the total number of aisle seats provided 
shall be designated aisle seats and shall be the aisle seats 
located closest to accessible routes. 

Exception: Designated aisle seats are not required in 
team or player seating serving areas of sport activity. 

1108.2.6 Lawn seating. Lawn seating areas and exterior 
overflow seating areas, where fixed seats are not provided, 
shall connect to an accessible route. 

1108.2.7 Assistive listening systems. Each assembly area 
where audible communications are integral to the use of the 
space shall have an assistive listening system. 

Exception: Other than in courtrooms, an assistive listen- 
ing system is not required where there is no audio ampli- 
fication system. 

1108.2.7.1 Receivers. Receivers shall be provided for 
assistive listening systems in accordance with Table 
1108.2.7.1. 

Exceptions: 

1. Where a building contains more than one 
assembly area, the total number of required 
receivers shall be permitted to be calculated 
according to the total number of seats in the 
assembly areas in the building, provided that all 
receivers are usable with all systems and if 
assembly areas required to provide assistive lis- 
tening are under one management. 



I 



264 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



2. Where all seats in an assembly area are served 
by an induction loop assistive listening system, 
the minimum number of receivers required by 
Table 1108.2.7.1 to be hearing-aid compatible 
shall not be required. 

1108.2.7.2 Public address systems. Where stadiums, 
arenas and grandstands provide audible public 
announcements, they shall also provide equivalent text 
information regarding events and facilities in compli- 
ance with Sections 1108.2.7.2.1 and 1108.2.7.2.2. 

1108.2.7.2.1 Prerecorded text messages. Where 
electronic signs are provided and have the capability to 
display prerecorded text messages containing informa- 
tion that is the same, or substantially equivalent to 
information that is provided audibly, signs shall dis- 
play text that is equivalent to audible announcements. 

Exception: Announcements that cannot be prere- 
corded in advance of the event shall not be required 
to be displayed. 

1108.2.7.2.2 Real-time messages. Where electronic 
signs are provided and have the capability to display 
real-time messages containing information that is the 
same, or substantially equivalent, to information that 
is provided audibly, signs shall display text that is 
equivalent to audible announcements. 

1108.2.8 Performance areas. An accessible route shall 
directly connect the performance area to the assembly seat- 
ing area where a circulation path directly connects a perfor- 
mance area to an assembly seating area. An accessible route 
shall be provided from performance areas to ancillary areas 
or facilities used by performers. 

1108.2.9 Dining areas. In dining areas, the total floor area 
allotted for seating and tables shall be accessible. 

Exceptions: 

1. In buildings or facilities not required to provide an 
accessible route between levels, an accessible 
route to a mezzanine seating area is not required, 
provided that the mezzanine contains less than 25 
percent of the total area and the same services are 
provided in the accessible area. 



2. In sports facilities, tiered dining areas providing 
seating required to be accessible shall be required 
to have accessible routes serving at least 25 per- 
cent of the dining area, provided that accessible 
routes serve accessible seating and where each tier 
is provided with the same services. 

1108.2.9.1 Dining surfaces. Where dining surfaces for 
the consumption of food or drink are provided, at least 5 
percent, but not less than one, of the dining surfaces for 
the seating and standing spaces shall be accessible and 
be distributed throughout the facility and located on a 
level accessed by an accessible route. 

1108.3 Self-service storage facilities. Self-service storage 
facilities shall provide accessible individual self-storage 
spaces in accordance with Table 1108.3. 



TABLE 1108.3 
ACCESSIBLE SELF-SERVICE STORAGE FACILITIES 



TOTAL SPACES IN 
FACILITY 


MINIMUM NUMBER OF REQUIRED ACCESSIBLE 
SPACES 


1 to 200 


5%, but not less than 1 


Over 200 


10, plus 2% of total number of units over 200 



1108.3.1 Dispersion. Accessible individual self-service 
storage spaces shall be dispersed throughout the various 
classes of spaces provided. Where more classes of spaces 
are provided than the number of required accessible spaces, 
the number of accessible spaces shall not be required to 
exceed that required by Table 1 108.3. Accessible spaces are 
permitted to be dispersed in a single building of a 
multibuilding facility. 

1 108.4 Judicial facilities. Judicial facilities shall comply with 
Sections 1108.4.1 through 1108.4.3. 

1108.4.1 Courtrooms. Each courtroom shall be accessible 
and comply with Sections 1108.4.1.1 through 1108.4.1.5. 

1108.4.1.1 Jury box. A wheelchair space complying 
with ICC A 11 7.1 shall be provided within thejury box. 

Exception: Adjacent companion seating is not 
required. 



TABLE 1108.2.7.1 
RECEIVERS FOR ASSISTIVE LISTENING SYSTEMS 



CAPACITY OF SEATING 
IN ASSEMBLY AREAS 


MINIMUM REQUIRED 
NUMBER OF RECEIVERS 


MINIMUM NUMBER OF RECEIVERS 
TO BE HEARING-AID COMPATIBLE 


50 or less 


2 


2 


51 to 200 


2, plus 1 per 25 seats over 50 seats* 


2 


201 to 500 


2, plus 1 per 25 seats over 50 seats* 


1 per 4 receivers * 


501 to 1,000 


20, plus 1 per 33 seats over 500 seats* 


1 per 4 receivers * 


1,001 to 2,000 


35, plus 1 per 50 seats over 1,000 seats* 


1 per 4 receivers * 


Over 2,000 


55, plus 1 per 100 seats over 2,000 seats* 


1 per 4 receivers* 



Note: * = or fraction thereof 



2009 INTERNATIONAL BUILDING CODE® 



265 



ACCESSIBILITY 



1108.4.1.2 Gallery seating. Wheelchair spaces comply- 
ing with ICC A117.1 shall be provided in accordance 
with Table 1108.2.2.1. Designated aisle seats shall be 
provided in accordance with Section 1108.2.5. 

1108.4.1.3 Assistive listening systems. An assistive lis- 
tening system must be provided. Receivers shall be pro- 
vided for the assistive listening system in accordance 
with Section 1108.2.7.1. 

1108.4.1.4 Employee work stations. The judge's 
bench, clerk's station, bailiff's station, deputy clerk's sta- 
tion and court reporter's station shall be located on an 
accessible route. The vertical access to elevated 
employee work stations within a courtroom is not 
required at the time of initial construction, provided a 
ramp, lift or elevator complying with ICC A 1 17.1 can be 
installed without requiring reconfiguration or extension 
of the courtroom or extension of the electrical system. 

1108.4.1.5 Other work stations. The litigant's and 
counsel stations, including the lectern, shall be accessi- 
blein accordance with ICC A117.1. 



1108.4.2 Holding cells, 
court-floor holding cells 
1108.4.2.1 and 1108.4.2.2. 



Central holding cells and 
shall comply with Sections 



1108.4.2.1 Central holding cells. Where separate cen- 
tral holding cells are provided for adult males, juvenile 
males, adult females or juvenile females, one of each 
type shall be accessible. Where central holding cells are 
provided and are not separated by age or sex, at least one 
accessible cell shall be provided. 

1108.4.2.2 Court-floor holding cells. Where separate 
court-floor holding cells are provided for adult males, 
juvenile males, adult females or juvenile females, each 
courtroom shall be served by one accessible cell of each 
type. Where court-floor holding cells are provided and 
are not separated by age or sex, courtrooms shall be 
served by at least one accessible cell. Accessible cells 
shall be permitted to serve more than one courtroom. 

1108.4.3 Visiting areas. Visiting areas shall comply with 
Sections 1108.4.3.1 and 1108.4.3.2. 

1108.4.3.1 Cubicles and counters. At least 5 percent 
but no fewer than one of the cubicles shall be accessible 
on both the visitor and detainee sides. Where counters 
are provided, at least one shall be accessible on both the 
visitor and detainee sides. 

Exception: This requirement shall not apply to the 
detainee side of cubicles or counters at noncontact 
visiting areas not serving accessible holding cells. 

1108.4.3.2 Partitions. Where solid partitions or security 
glazing separate visitors from detainees, at least one of 
each type of cubicle or counter partition shall be accessi- 
ble. 



SECTION 1109 
OTHER FEATURES AND FACILITIES 

1109.1 General. Accessible building features and facilities 
shall be provided in accordance with Sections 1109.2 through 
1109.14. 

Exception: Type A units and Type B units shall comply with 
ICCA117.1. 

1109.2 Toilet and bathing facilities. Each toilet room and 
bathing room shall be accessible. Where a floor level is not 
required to be connected by an accessible route, the only toilet 
rooms or bathing rooms provided within the facility shall not 
be located on the inaccessible floor. At least one of each type of 
fixture, element, control or dispenser in each accessible toilet 
room and bathing room shall be accessible. 

Exceptions: 

1. In toilet rooms or bathing rooms accessed only 
through a private office, not for common or public use 
and intended for use by a single occupant, any of the 
following alternatives are allowed: 

1.1. Doors are permitted to swing into the clear 
floor space, provided the door swing can be 
reversed to meet the requirements in ICC 
AI17.1; 

1.2. The height requirements for the water closet 
in ICC A 117.1 are not applicable; 

1.3. Grab bars are not required to be installed in a 
toilet room, provided that reinforcement has 
been installed in the walls and located so as to 
permit the installation of such grab bars; and 

1.4. The requirement for height, knee and toe 
clearance shall not apply to a lavatory. 

2. This section is not applicable to toilet and bathing 
rooms that serve dwelling units or sleeping units that 
are not required to be accessible by Section 1107. 

3. Where multiple single-user toilet rooms or bathing 
rooms are clustered at a single location, at least 50 
percent but not less than one room for each use at each 
cluster shall be accessible. 

4. Where no more than one urinal is provided in a toilet 
room or bathing room, the urinal is not required to be 
accessible. 

5. Toilet rooms that are part of critical care or intensive 
care patient sleeping rooms are not required to be 
accessible. 

1109.2.1 Family or assisted-use toilet and bathing 
rooms. In assembly and mercantile occupancies, an acces- 
sible family or assisted-use toilet room shall be provided 
where an aggregate of six or more male and female water 
closets is required. In buildings of mixed occupancy, only 
those water closets required for the assembly or mercantile 
occupancy shall be used to determine the family or 
assisted-use toilet room requirement. In recreational facili- 



266 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



ties where separate- sex bathing rooms are provided, an 
accessible family or assisted-use bathing room shall be pro- 
vided. Fixtures located within family or assisted-use toilet 
and bathing rooms shall be included in determining the 
number of fixtures provided in an occupancy. 

Exception: Where each separate-sex bathing room has 
only one shower or bathtub fixture, a family or 
assisted-use bathing room is not required. 

1109.2.1.1 Standard. Family or assisted-use toilet and 
bathing rooms shall comply with Sections 1109.2.1.2 
through 1109.2.1.7 and ICC A117.1. 

1 109.2.1.2 Family or assisted-use toilet rooms. Family 
or assisted-use toilet rooms shall include only one water 
closet and only one lavatory. A family or assisted-use 
bathing room in accordance with Section 1109.2.1.3 
shall be considered a family or assisted-use toilet room. 

Exception: A urinal is permitted to be provided in 
addition to the water closet in a family or assisted-use 
toilet room. 

1109.2.1.3 Family or assisted-use bathing rooms. 
Family or assisted-use bathing rooms shall include only 
one shower or bathtub fixture. Family or assisted-use 
bathing rooms shall also include one water closet and 
one lavatory. Where storage facilities are provided for 
separate-sex bathing rooms, accessible storage facilities 
shall be provided for family or assisted-use bathing 
rooms. 

1109.2.1.4 Location. Family or assisted-use toilet and 
bathing rooms shall be located on an accessible route. 
Family or assisted-use toilet rooms shall be located not 
more than one story above or below separate- sex toilet 
rooms. The accessible route from any separate-sex toilet 
room to a family or assisted-use toilet room shall not 
exceed 500 feet (152m). 

1109.2.1.5 Prohibited location. In passenger transpor- 
tation facilities and airports, the accessible route from 
separate-sex toilet rooms to a family or assisted-use toilet 
room shall not pass through security checkpoints. 

1109.2.1.6 Clear floor space. Where doors swing into a 
family or assisted-use toilet or bathing room, a clear floor 
space not less than 30 inches by 48 inches (762 mm by 
1219 mm) shall be provided, within the room, beyond 
the area of the door swing. 

1109.2.1.7 Privacy. Doors to family or assisted-use toi- 
let and bathing rooms shall be securable from within the 
room. 

1109.2.2 Water closet compartment. Where water closet 
compartments are provided in a toilet room or bathing 
room, at least one wheelchair-accessible compartment shall 
be provided. Where the combined total water closet com- 
partments and urinals provided in a toilet room or bathing 
room is six or more, at least one ambulatory-accessible 
water closet compartment shall be provided in addition to 
the wheelchair-accessible compartment. Wheel- 
chair- accessible and ambulatory-accessible compartments 
shall comply with ICC Al 1 7 . 1 . 



1109.2.3 Lavatories. Where lavatories are provided, at 
least 5 percent, but not less than one, shall be accessible. 
Where the total lavatories provided in a toilet room or bath- 
ing facility is six or more, at least one lavatory with 
enhanced reach ranges in accordance with ICC A117.1, 
shall be provided. 

1109.3 Sinks. Where sinks are provided, at least 5 percent but 
not less than one provided in accessible spaces shall comply 
with ICC A117.1. 

Exception: Mop or service sinks are not required to be 
accessible. 

1109.4 Kitchens and kitchenettes. Where kitchens and kitch- 
enettes are provided in accessible spaces or rooms, they shall 
be accessible in accordance with ICC All 7.1. 

1109.5 Drinking fountains. Where drinking fountains are 
provided on an exterior site, on a floor or within a secured area, 
the drinking fountains shall be provided in accordance with 
Sections 1109.5.1 and 1109.5.2. 

1109.5.1 Minimum number. No fewer than two drinking 
fountains shall be provided. One drinking fountain shall 
comply with the requirements for people who use a wheel- 
chair and one drinking fountain shall comply with the 
requirements for standing persons . 

Exception: A single drinking fountain that complies 
with the requirements for people who use a wheelchair 
and standing persons shall be permitted to be substituted 
for two separate drinking fountains. 

1109.5.2 More than the minimum number. Where more 
than the minimum number of drinking fountains specified 
in Section 1109.5.1 are provided, 50 percent of the total 
number of drinking fountains provided shall comply with 
the requirements for persons who use a wheelchair and 50 
percent of the total number of drinking fountains provided 
shall comply with the requirements for standing persons. 

Exception: Where 50 percent of the drinking fountains 
yields a fraction, 50 percent shall be permitted to be 
rounded up or down, provided that the total number of 
drinking fountains complying with this section equals 
100 percent of the drinking fountains. 

1109.6 Elevators. Passenger elevators on an accessible route 
shall be accessible and comply with Section 3001 .3. 

1109.7 Lifts. Platform (wheelchair) lifts are permitted to be a 
part of a required accessible route in new construction where 
indicated in Items 1 through 10. Platform (wheelchair) lifts 
shall be installed in accordance with ASME A 18.1. 

1. An accessible route to a performing area and speaker 
platforms in Group A occupancies. 

2. An accessible route to wheelchair spaces required to 
comply with the wheelchair space dispersion require- 
ments of Sections 1108.2.2 through 1108.2.6. 

3. An accessible route to spaces that are not open to the 
general public with an o c cup ant load of noi more than 
five. 

4. An accessible route within a dwellingor sleeping unit. 



2009 INTERNATIONAL BUILDING CODE® 



267 



ACCESSIBILITY 



5. An accessible route to wheelchair seating spaces 
located in outdoor dining terraces in Group A-5 occu- 
pancies where the means of egress from the dining ter- 
races to a public way are open to the outdoors. 

6. An accessible route to jury boxes and witness stands; 
raised courtroom stations including judges' benches, 
clerks' stations, bailiffs' stations, deputy clerks' sta- 
tions and court reporters' stations; and to depressed 
areas such as the well of the court. 

7. An accessible route to load and unload areas serving 
amusement rides. 

8. An accessible route to play components or soft con- 
tained play structures. 

9. An accessible route to team or player seating areas 
serving areas of sport activity. 

10. An accessible route where existing exterior site con- 
straints make use of a ramp or elevator infeasible. 

1109.8 Storage. Where fixed or built-in storage elements such 
as cabinets, shelves, medicine cabinets, closets and drawers are 
provided in required accessible spaces, at least one of each type 
shall contain storage space complying with ICC A117.1. 

1109.8.1 Lockers. Where lockers are provided in accessi- 
blespaces, at least five percent, but not less than one, of each 
type shall be accessible. 

1109.8.2 Shelving and display units. Self-service shelves 
and display units shall be located on an accessible route. 
Such shelving and display units shall not be required to 
comply with reach-range provisions. 

1109.8.3 Coat hooks and shelves. Where coat hooks and 
shelves are provided in toilet rooms or toilet compartments 
or in dressing, fitting or locker rooms, at least one of each 
type shall be accessible and shall be provided in accessible 
toilet rooms without toilet compartments, accessible toilet 
compartments and accessible dressing, fitting and locker 
rooms. 

1 109.9 Detectable warnings. Passenger transit platform edges 
bordering a drop-off and not protected by platform screens or 
guards shall have a detectable warning. 

Exception: Detectable warnings are not required at bus 
stops. 

1109.10 Seating at tables, counters and work surfaces. 
Where seating or standing space at fixed or built-in tables, 
counters or work surfaces is provided in accessible spaces, at 
least 5 percent of the seating and standing spaces, but not less 
than one, shall be accessible. In Group 1-3 occupancy visiting 
areas at least 5 percent, but not less than one, cubicle or counter 
shall be accessible on both the visitor and detainee sides. 

Exceptions: 

1. Check-writing surfaces at check-out aisles not 
required to comply with Section 1109.11.2 are not 
required to be accessible. 

2. In Group 1-3 occupancies, the counter or cubicle on 
the detainee side is not required to be accessible at 
noncontact visiting areas or in areas not serving 
accessible holding cells or sleeping units. 



1109.10.1 Dispersion. Accessible fixed or built-in seating 
at tables, counters or work surfaces shall be distributed 
throughout the space or facility containing such elements 
and located on a level accessed by an accessible route. 

1109.11 Service facilities. Service facilities shall provide for 
accessible features in accordance with Sections 1109.11.1 
through 1109.11.5. 

1109.11.1 Dressing, fitting and locker rooms. Where 
dressing rooms, fitting rooms or locker rooms are provided, 
at least 5 percent, but not less than one, of each type of use in 
each cluster provided shall be accessible. 

1109.11.2 Check-out aisles. Where check-out aisles are 
provided, accessible check-out aisles shall be provided in 
accordance with Table 1109.11.2. Where check-out aisles 
serve different functions, at least one accessible check-out 
aisle shall be provided for each function. Where check-out 
aisles serve different functions, accessible check-out aisles 
shall be provided in accordance with Table 1109.11.2 for 
each function. Where check-out aisles are dispersed 
throughout the building or facility, accessible check-out 
aisles shall also be dispersed. Traffic control devices, secu- 
rity devices and turnstiles located in accessible check-out 
aisles or lanes shall be accessible. 

TABLE 1109.11.2 
ACCESSIBLE CHECK-OUT AISLES 



I 



TOTAL CHECK-OUT AISLES OF 
EACH FUNCTION 


MINIMUM NUMBER OF ACCESSIBLE 

CHECK-OUT AISLES OF EACH 

FUNCTION 


lto4 


1 


5 to 8 


2 


9 to 15 


3 


Over 15 


3, plus 20% of additional aisles 



1 109. 1 1 .3 Point of sale and service counters. Where coun- 
ters are provided for sales or distribution of goods or ser- 
vices, at least one of each type provided shall be accessible. 
Where such counters are dispersed throughout the building 
or facility, accessible counters shall also be dispersed. 

1109.11.4 Food service lines. Food service lines shall be 
accessible. Where self-service shelves are provided, at least 
50 percent, but not less than one, of each type provided shall 
be accessible. 

1109.11.5 Queue and waiting lines. Queue and waiting 
lines servicing accessible counters or check-out aisles shall 
be accessible. 

1109.12 Controls, operating mechanisms and hardware. 
Controls, operating mechanisms and hardware intended for 
operation by the occupant, including switches that control 
lighting and ventilation and electrical convenience outlets, in 
accessible spaces, along accessible routes or as parts of acces- 
sible elements shall be accessible. 

Exceptions: 

1. Operable parts that are intended for use only by ser- 
vice or maintenance personnel shall not be required to 
be accessible. 



268 



2009 INTERNATIONAL BUILDING CODE® 



ACCESSIBILITY 



2. Electrical or communication receptacles serving a 
dedicated use shall not be required to be accessible. 

3. Where two or more outlets are provided in a kitchen 
above a length of counter top that is uninterrupted by a 
sink or appliance, one outlet shall not be required to 
be accessible. 

4. Floor electrical receptacles shall not be required to be 
accessible. 

5. HV AC diff users shall not be required to be accessible. 

6. Except for light switches, where redundant controls 
are provided for a single element, one control in each 
space shall not be required to be accessible. 

1. Access doors or gates in barrier walls and fences pro- 
tecting pools, spas and hot tubs shall be permitted to 
have operable parts of the release of latch on 
self-latching devices at 54 inches (1370 mm) maxi- 
mum and 48 inches minimum above the finished floor 
or ground, provided the self-latching devices are not 
also self-locking devices, operated by means of a key, 
electronic opener, or integral combination lock. 

1109.12.1 Operable window. Where operable windows are 
provided in rooms that are required to be accessiblein accor- 
dance with Sections 1107.5.1.1, 1107.5.2.1, 1107.5.3.1, 
1107.5.4, 1107.6.1.1, 1107.6.2.1.1, 1107.6.2.2.1 and 
1107.7.6.4.1, at least one window in each room shall be 
accessible and each required operable window shall be 
accessible. 

Exception: Accessiblewindows are not required in bath- 
rooms and kitchens. 

1109.13 Fuel-dispensing systems. Fuel-dispensing systems 
shall comply with ICC AI 1 7 . 1 . 

1109.14 Recreational and sports facilities. Recreational and 
sports facilities shall be provided with accessible features in 
accordance with Sections 1109.14.1 through 1109.14.4. 

1109.14.1 Facilities serving a single building. In Group 
R-2 and R-3 occupancies where recreational facilities are 
provided serving a single building containing Type A units 
or Type B units, 25 percent, but not less than one, of each 
type of recreational facility shall be accessible. Every recre- 
ational facility of each type on a site shall be considered to 
determine the total number of each type that is required to be 
accessible. 

1109.14.2 Facilities serving multiple buildings. In Group 
R-2 and R-3 occupancies on a single site where multiple 
buildings containing Type A units or Type B units are served 
by recreational facilities, 25 percent, but not less than one, 
of each type of recreational facility serving each building 
shall be accessible. The total number of each type of recre- 
ational facility that is required to be accessible shall be 
determined by considering every recreational facility of 
each type serving each building on the site. 

1109.14.3 Other occupancies. All recreational and sports 
facilities not falling within the purview of Section 
1109.14.1 or 1109.14.2 shall be accessible. 



1109.14.4 Recreational and sports facilities exceptions. 
Recreational and sports facilities required to be accessible 
shall be exempt from this chapter to the extent specified in 
this section. 

1 109.14.4.1 Bowling lanes. An accessible route shall be 
provided to at least 5 percent, but no less than one, of 
each type of bowling lane. 

1109.14.4.2 Court sports. In court sports, at least one 
accessible route shall directly connect both sides of the 
court. 

1109.14.4.3 Raised boxing or wrestling rings. Raised 
boxing or wrestling rings are not required to be accessi- 
ble. 

1109.14.4.4 Raised refereeing, judging and scoring 
areas. Raised structures used solely for refereeing, judg- 
ing or scoring a sport are not required to be accessible. 

1109.14.4.5 Raised diving boards and diving plat- 
forms. Raised diving boards and diving platforms are 
not required to be accessible. 



SECTION 1110 
SIGNAGE 

1110.1 Signs. Required accessible elements shall be identified 
by the International Symbol of Accessibility at the following 
locations: 

1. A ccessible parking spaces required by Section 1106.1 
except where the total number of parking spaces pro- 
vided is four or less. 

2. Accessible passenger loading zones. 

3. Accessible rooms where multiple single-user toilet or 
bathing rooms are clustered at a single location. 

4. Accessible entrances where not all entrances are accessi- 
ble. 

5. Accessible check-out aisles where not all aisles are 
accessible. The sign, where provided, shall be above the 
check-out aisle in the same location as the check-out 
aisle number or type of check-out identification. 

6. Unisex toilet and bathing rooms . 

7. Accessible dressing, fitting and locker rooms where not 
all such rooms are accessible. 

8. Accessible areas of refuge in accordance with Section 
1007.9. 

9. Exterior areas for assisted rescue in accordance with 
Section 1007.9. 

1110.2 Directional signage. Directional signage indicating 
the route to the nearest like accessible element shall be pro- 
vided at the following locations. These directional signs shall 
include the International Symbol of Accessibility: 

1. Inaccessible building entrances. 

2. Inaccessible public toilets and bathing facilities. 

3. Elevators not serving an accessible route. 



2009 INTERNATIONAL BUILDING CODE® 



269 



ACCESSIBILITY 



I 



4. At each separate- sex toilet and bathing room indicating 
the location of the nearest family or assisted-use toilet or 
bathing room where provided in accordance with Sec- 
tion 1109.2.1. 

5. At exits and exit stairways serving a required accessible 
space, but not providing an approved accessible means 
of egress, signage shall be provided in accordance with 
Section 1007.10. 

1110.3 Other signs. Signage indicating special accessibility 
provisions shall be provided as shown: 

1. Each assembly area required to comply with Section 
1108.2.7 shall provide a sign notifying patrons of the 
availability of assistive listening systems. 

Exception: Where ticket offices or windows are pro- 
vided, signs are not required at each assembly area 
provided that signs are displayed at each ticket office 
or window informing patrons of the availability of 
assistive listening systems. 

2. At each door to an area of refuge, an exterior area for 
assisted rescue, an egress stairway, exitpassageway and 
exit discharge, signage shall be provided in accordance 
with Section 1011.3. 

3. At areas of refuge, signage shall be provided in accor- 
dance with Section 1007.11. 

4. At exterior areas for assisted rescue, signage shall be pro- 
vided in accordance with Section 1007.11. 

5. At two-way communication systems, signage shall be 
provided in accordance with Section 1007.8.2. 

6. Within exit enclosures, signage shall be provided in 
accordance with Section 1022.8. 



270 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 12 
INTERIOR ENVIRONMENT 



SECTION 1201 
GENERAL 

1201.1 Scope. The provisions of this chapter shall govern ven- 
tilation, temperature control, lighting, yards and courts, sound 
transmission, room dimensions, surrounding materials and 
rodent proofing associated with the interior spaces of build- 
ings. 



SECTION 1202 
DEFINITIONS 

1202.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

SUNROOM. A one- story structure attached to a building with 
a glazing area in excess of 40 percent of the gross area of the 
structure's exterior walls and roof. 

THERMAL ISOLATION. A separation of conditioned 
spaces, between a sunroom addition and a dwelling unit, con- 
sisting of existing or new wall(s), doors and/or windows. 



SECTION 1203 
VENTILATION 

1203.1 General. Buildings shall be provided with natural ven- 
tilation in accordance with Section 1203.4, or mechanical ven- 
tilation in accordance with the International Mechanical Code. 

1203.2 Attic spaces. Enclosed attics and enclosed rafter 
spaces formed where ceilings are applied directly to the under- 
side of roof framing members shall have cross ventilation for 
each separate space by ventilating openings protected against 
the entrance of rain and snow. Blocking and bridging shall be 
arranged so as not to interfere with the movement of air. A min- 
imum of 1 inch (25 mm) of airspace shall be provided between 
the insulation and the roof sheathing. The net free ventilating 
area shall not be less than l/ 300 of the area of the space venti- 
lated' with 50 percent of the required ventilating area provided 
by ventilators located in the upper portion of the space to be 
ventilated at least 3 feet (914 mm) above eave or cornice vents 
with the balance of the required ventilation provided by eave or 
cornice vents. 

1203.2.1 Openings into attic. Exterior openings into the 
attic space of any building intended for human occupancy 
shall be protected to prevent the entry of birds, squirrels, 
rodents, snakes and other similar creatures. Openings for 
ventilation having a least dimension of i/i6 inch (1.6 mm) 
minimum and i/ 4 inch (6.4 mm) maximum shall be permit- 
ted. Openings for ventilation having a least dimension 
larger than i/ 4 inch (6.4 mm) shall be provided with corro- 
sion-resistant wire cloth screening, hardware cloth, perfo- 
rated vinyl or similar material with openings having a least 
dimension of i/i6 inch (1.6 mm) minimum and i/ 4 inch (6.4 



mm) maximum. Where combustion air is obtained from an 
attic area, it shall be in accordance with Chapter 7 of the 
International Mechanical Code. 

1203.3 Under-floor ventilation. The space between the bot- 
tom of the floor joists and the earth under any building except 
spaces occupied by basements or cellars shall be provided with 
ventilation openings through foundation walls or exterior 
walls. Such openings shall be placed so as to provide cross ven- 
tilation of the under-floor space. 

1203.3.1 Openings for under-floor ventilation. The mini- 
mum net area of ventilation openings shall not be less than 1 
square foot for each 150 square feet (0.67 m 2 for each 100 
m 2 ) of crawl-space area. Ventilation openings shall be cov- 
ered for their height and width with any of the following 
materials, provided that the least dimension of the covering 
shall not exceed i/ 4 inch (6 mm): 

1. Perforated sheet metal plates not less than 0.070 inch 
(1.8 mm) thick. 

2. Expanded sheet metal plates not less than 0.047 inch 
(1.2 mm) thick. 

3. Cast-iron grilles or gratings. 

4. Extruded load-bearing vents. 

5. Hardware cloth of 0.035 inch (0.89 mm) wire or 
heavier. 

6. Corrosion-resistant wire mesh, with the least dimen- 
sion not exceeding i/ 8 inch (3.2 mm). 

1203.3.2 Exceptions. The following are exceptions to Sec- 
tions 1203.3 and 1203.3.1: 

1. Where warranted by climatic conditions, ventilation 
openings to the outdoors are not required if ventila- 
tion openings to the interior are provided. 

2. The total area of ventilation openings is permitted to 
be reduced to 1/1500 of the under-floor area where the 
ground surface' is covered with a Class I vapor 
retarder material and the required openings are placed 
so as to provide cross ventilation of the space. The 
installation of operable louvers shall not be prohib- 
ited. 

3. Ventilation openings are not required where continu- 
ously operated mechanical ventilation is provided at a 
rate of 1.0 cubic foot per minute (cfm) for each 50 
square feet (1.02 L/s for each 10m 2 ) of crawl space 
floor area and the ground surface is covered with a 
Class I vapor retarder. 

4. Ventilation openings are not required when the 
ground surface is covered with a Class I vapor 
retarder, the perimeter walls are insulated and the 
space is conditioned in accordance with the Interna- 
tional Energy Conservation Code. 



1 



2009 INTERNATIONAL BUILDING CODE® 



271 



INTERIOR ENVIRONMENT 



5. For buildings in flood hazard areas as established in 
Section 1612.3, the openings for under- floor ventila- 
tion shall be deemed as meeting the flood opening 
requirements of ASCE 24 provided that the ventila- 
tion openings are designed and installed in accor- 
dance with ASCE 24. 

1203.4 Natural ventilation. Natural ventilation of an occu- 
pied space shall be through windows, doors, louvers or other 
openings to the outdoors. The operating mechanism for such 
openings shall be provided with ready access so that the open- 
ings are readily controllable by the building occupants. 

1203.4.1 Ventilation area required. The minimum 
openable area to the outdoors shall be 4 percent of the floor 
area being ventilated. 

1203.4.1.1 Adjoining spaces. Where rooms and spaces 
without openings to the outdoors are ventilated through 
an adjoining room, the opening to the adjoining room 
shall be unobstructed and shall have an area of not less 
than 8 percent of the floor area of the interior room or 
space, but not less than 25 square feet (2.3 m 2 ). The mini- 
mum openable area to the outdoors shall be based on the 
total floor area being ventilated. 

Exception: Exterior openings required for ventila- 
tion shall be permitted to open into a thermally iso- 
lated sunroom addition or patio cover provided that 
the openable area between the sunroom addition or 
patio cover and the interior room shall have an area of 
not less than 8 percent of the floor area of the interior 
room or space, but not less than 20 square feet (1.86 
m 2 ). The minimum openable area to the outdoors 
shall be based on the total floor area being ventilated. 

1203.4.1.2 Openings below grade. Where openings 
below grade provide required natural ventilation, the 
outside horizontal clear space measured perpendicular to 
the opening shall be one and one-half times the depth of 
the opening. The depth of the opening shall be measured 
from the average adjoining ground level to the bottom of 
the opening. 

1203.4.2 Contaminants exhausted. Contaminant sources 
in naturally ventilated spaces shall be removed in accor- 
dance with the International Mechanical Code and the 
International Fire Code. 

1203.4.2.1 Bathrooms. Rooms containing bathtubs, 
showers, spas and similar bathing fixtures shall be 
mechanically ventilated in accordance with the Interna- 
tional Mechanical Code. 

1203.4.3 Openings on yards or courts. Where natural ven- 
tilation is to be provided by openings onto yards or courts, 
suchyards or courts shall comply with Section 1206. 

1203.5 Other ventilation and exhaust systems. Ventilation 
and exhaust systems for occupancies and operations involving 
flammable or combustible hazards or other contaminant 
sources as covered in the International Mechanical Code or the 
International Fire Code shall be provided as required by both 
codes. 



SECTION 1204 
TEMPERATURE CONTROL 

1204.1 Equipment and systems. Interior spaces intended for 
human occupancy shall be provided with active or passive 
space- heating systems capable of maintaining a minimum 
indoor temperature of 68°F (20°C) at a point 3 feet (914 mm) 
above the floor on the design heating day. 

Exception: Interior spaces where the primary purpose is 
not associated with human comfort. 



SECTION 1205 
LIGHTING 

1205.1 General. Every space intended for human occupancy 
shall be provided with natural light by means of exterior glazed 
openings in accordance with Section 1205.2 or shall be pro- 
vided with artificial light in accordance with Section 1205.3. 
Exterior glazed openings shall open directly onto a public way 
or onto a yard or court in accordance with Section 1206. 

1205.2 Natural light. The minimum net glazed area shall not 
be less than 8 percent of the floor area of the room served. 

1205.2.1 Adjoining spaces. For the purpose of natural 
lighting, any room is permitted to be considered as a portion 
of an adjoining room where one-half of the area of the com- 
mon wall is open and unobstructed and provides an opening 
of not less than one-tenth of the floor area of the interior 
room or 25 square feet (2.32 m 2 ) , whichever is greater. 

Exception: Openings required for natural light shall be 
permitted to open into a thermally isolated sunroom 
addition or patio cover where the common wall provides 
a glazed area of not less than one-tenth of the floor area of 
the interior room or 20 square feet (1.86 m 2 ), whichever 
is greater. 

1205.2.2 Exterior openings. Exterior openings required by 
Section 1205.2 for natural light shall open directly onto a 
public way,yardor court, as set forth in Section 1206. 

Exceptions: 

1. Required exterior openings are permitted to open 
into a roofed porch where the porch: 

1.1. Abuts a public way, yard or court, 

1.2. Has a ceiling height of not less than 7 feet 
(2134 mm); and 

1.3. Has a longer side at least 65 percent open 
and unobstructed. 

2. Skylights are not required to open directly onto a 
public way, yard or court. 

1205.3 Artificial light. Artificial light shall be provided that is 
adequate to provide an average illumination of 10 foot-candles 
(1 07 lux) over the area of the room at a height of 30 inches (762 
mm) above the floor level. 

1205.4 Stairway illumination. Stairways within dwelling 
units and exterior stairways serving a dwelling unit shall have 
an illumination level on tread runs of not less than 1 foot-candle 
(11 lux). Stairs in other occupancies shall be governed by 
Chapter 10. 



272 



2009 INTERNATIONAL BUILDING CODE® 



INTERIOR ENVIRONMENT 



1205.4.1 Controls. The control for activation of the 
required stairway lighting shall be in accordance with 
NFPA 70. 

1205.5 Emergency egress lighting. The means of egress shall 
be illuminated in accordance with Section 1006.1. 



SECTION 1206 
YARDS OR COURTS 

1206.1 General. This section shall apply to yards and courts 
adj acent to exterior openings that provide natural light or venti- 
lation. Such yar ds and courts shall be on the same property as 
the building. 

1206.2 Yards. Yards shall not be less than 3 feet (914 mm) in 
width for buildings two stories or less above grade plane. For 
buildings more than two stories above grade plane, the mini- 
mum width of the yard shall be increased at the rate of 1 foot 
(305 mm) for each additional story. For buildings exceeding 14 
stories above grade plane, the required width of the yard shall 
be computed on the basis of 14 stories above grade plane. 

1206.3 Courts. Courts shall not be less than 3 feet (914 mm) in 
width. Courts having windows opening on opposite sides shall 
not be less than 6 feet (1829 mm) in width. Courts shall not be 
less than 10 feet (3048 mm) in length unless bounded on one 
end by & public way or yard. For buildings more than two sto- 
ries above grade plane, the courtshdll be increased 1 foot (305 
mm) in width and 2 feet (610 mm) in length for each additional 
story. For buildings exceeding 14 stories above grade plane, 
the required dimensions shall be computed on the basis of 14 
stories above grade plane. 

1206.3.1 Court access. Access shall be provided to the bot- 
tom of courts for cleaning purposes. 

1206.3.2 Air intake. Courts more than two stories in height 
shall be provided with a horizontal air intake at the bottom 
not less than 10 square feet (0.93 m 2 ) in area and leading to 
the exterior of the building unless abutting & yar dor public 
way. 

1206.3.3 Court drainage. The bottom of every courtshall 
be properly graded and drained to a public sewer or other 
approved disposal system complying with the International 
Plumbing Code. 



SECTION 1207 
SOUND TRANSMISSION 

1207.1 Scope. This section shall apply to common interior 
walls, partitions and floor/ceiling assemblies between adjacent 
dwelling units or between dwelling units and adjacent public 
areas such as halls, corridors, stairs or service areas. 

1207.2 Air-borne sound. Walls, partitions and floor/ceiling 
assemblies separating dwelling units from each other or from 
public or service areas shall have a sound transmission class 
(STC) of not less than 50 (45 if field tested) for air-borne noise 
when tested in accordance with ASTM E 90. Penetrations or 
openings in construction assemblies for piping; electrical 
devices; recessed cabinets; bathtubs; soffits; or heating, venti- 
lating or exhaust ducts shall be sealed, lined, insulated or other- 



wise treated to maintain the required ratings. This requirement 
shall not apply to dwelling unit entrance doors; however, such 
doors shall be tight fitting to the frame and sill. 

1207.2.1 Masonry. The sound transmission class of con- 
crete masonry and clay masonry assemblies shall be calcu- 
lated in accordance with TMS 0302 or determined through 
testing in accordance with ASTM 90. 

1207.3 Structure-borne sound. Floor/ceiling assemblies 
between dwelling units or between a dwelling unit and a public 
or service area within the structure shall have an impact insula- 
tion class (1IC) rating of not less than 50 (45 if field tested) 
when tested in accordance with ASTM E 492. 



SECTION 1208 
INTERIOR SPACE DIMENSIONS 

1208.1 Minimum room widths. Habitable spaces, other than 
a kitchen, shall not be less than 7 feet (2134 mm) in any plan 
dimension. Kitchens shall have a clear passageway of not less 
than 3 feet (914 mm) between counter fronts and appliances or 
counter fronts and walls. 

1208.2 Minimum ceiling heights. Occupiable spaces, habit- 
able spaces and corridors shall have a ceiling height of not less 
than 7 feet 6 inches (2286 mm). Bathrooms, toilet rooms, kitch- 
ens, storage rooms and laundry rooms shall be permitted to 
have a ceiling height of not less than 7 feet (2134 mm). 

Exceptions: 

1. In one- and two-family dwellings, beams or girders 
spaced not less than 4 feet (1219 mm) on center and 
projecting not more than 6 inches (152 mm) below the 
required ceiling height. 

2. If any room in a building has a sloped ceiling, the pre- 
scribed ceiling height for the room is required in 
one-half the area thereof. Any portion of the room 
measuring less than 5 feet (1524 mm) from the fin- 
ished floor to the ceiling shall not be included in any 
computation of the minimum area thereof. 

3. Mezzanines constructed in accordance with Section 
505.1. 

1208.2.1 Furred ceiling. Any room with a furred ceiling 
shall be required to have the minimum ceiling height in 
two-thirds of the area thereof, but in no case shall the height 
of the furred ceiling be less than 7 feet (2134 mm). 

1208.3 Room area. Every dwelling unit shall have at least one 
room that shall have not less than 120 square feet (13.9 m 2 ) of 
net floor area. Other habitable rooms shall have a net floor area 
of not less than 70 square feet (6.5 m 2 ). 

Exception: Every kitchen in a one- and two-family dwell- 
ingshall have not less than 50 square feet (4.64 m 2 ) of gross 
floor area. 

1208.4 Efficiency dwelling units. An efficiency living unit 
shall conform to the requirements of the code except as modi- 
fied herein: 

1. The unit shall have a living room of not less than 220 
square feet (20.4 m 2 ) of floor area. An additional 100 



2009 INTERNATIONAL BUILDING CODE® 



273 



INTERIOR ENVIRONMENT 



square feet (9.3 m 2 ) of floor area shall be provided for 
each occupant of such unit in excess of two. 

2. The unit shall be provided with a separate closet. 

3. The unit shall be provided with a kitchen sink, cook- 
ing appliance and refrigeration facilities, each having 
a clear working space of not less than 30 inches (762 
mm) in front. Light and ventilation conforming to this 
code shall be provided. 

4. The unit shall be provided with a separate bathroom 
containing a water closet, lavatory and bathtub or 
shower. 



1210.4 Waterproofjoints. Built-in tubs with showers shall 
have waterproofjoints between the tub and adjacent wall. 

1210.5 Toilet rooms. Toilet rooms shall not open directly into a 
room used for the preparation offood for service to the public. 



SECTION 1209 
ACCESS TO UNOCCUPIED SPACES 

1209.1 Crawl spaces. Crawl spaces shall be provided with a 
minimum of one access opening not less than 18 inches by 24 
inches (457 mm by 610 mm). 

1209.2 Attic spaces. An opening not less than 20 inches by 30 
inches (559 mm by 762 mm) shall be provided to any attic area 
having a clear height of over 30 inches (762 mm). A 30-inch 
(762 mm) minimum clear headroom in the attic space shall be 
provided at or above the access opening. 

1209.3 Mechanical appliances. Access to mechanical appli- 
ances installed in under-floor areas, in attic spaces and on roofs 
or elevated structures shall be in accordance with the Interna- 
tional Mechanical Code. 



SECTION 1210 
SURROUNDING MATERIALS 

1210.1 Floors and wall base finish materials. In other than 
dwelling units, toilet, bathing and shower room floor finish 
materials shall have a smooth, hard, nonabsorbent surface. The 
intersections of such floors with walls shall have a smooth, 
hard, nonabsorbent vertical base that extends upward onto the 
walls at least 4 inches (102 mm). 

1210.2 Walls and partitions. Walls and partitions within 2 feet 
(610 mm) of urinals and water closets shall have a smooth, 
hard, nonabsorbent surface, to a height of 4 feet (1219 mm) 
above the floor, and except for structural elements, the materi- 
als used in such walls shall be of a type that is not adversely 
affected by moisture. 

Exceptions: 

1. Dwelling units and sleeping units. 

2. Toilet rooms that are not accessible to the public and 
which have not more than one water closet. 

Accessories such as grab bars, towel bars, paper dispensers 
and soap dishes, provided on or within walls, shall be installed 
and sealed to protect structural elements from moisture. For 
walls and partitions also see Section 2903 . 

1210.3 Showers. Shower compartments and walls above bath- 
tubs with installed shower heads shall be finished with a 
smooth, nonabsorbent surface to a height not less than 70 
inches (1778 mm) above the drain inlet. 



274 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 13 
ENERGY EFFICIENCY 



SECTION 1301 
GENERAL 

1301.1 Scope. This chapter governs the design and construc- 
tion of buildings for energy efficiency. 

1301.1.1 Criteria. Buildings shall be designed and con- 
structed in accordance with the International Energy Con- 
servation Code. 



2009 INTERNATIONAL BUILDING CODE® 275 



276 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 14 
EXTERIOR WALLS 



SECTION 1401 
GENERAL 

1401.1 Scope. The provisions of this chapter shall establish the 
minimum requirements for exterior walls; exterior wall co\ wr- 
ings; exterior wall openings; exterior windows and doors; 
architectural trim; balconies and similar projections; and bay 
and oriel windows. 



SECTION 1402 
DEFINITIONS 

1402.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

ADHERED MASONRY VENEER. Veneer secured and sup 
ported through the adhesion of an approved bonding material 
applied to an approve d backing. 

ANCHORED MASONRY VENEER. Veneer secured with 
approve d mechanical fasteners to an approved backing. 

BACKING. The wall or surface to which the veneer is secured. 

EXTERIOR INSULATION AND FINISH SYSTEMS 

(EIFS). EIFS are nonstructural, nonload-bearing, exterior wall 
cladding systems that consist of an insulation board attached 
either adhesively or mechanically, or both, to the substrate; an 
integrally reinforced base coat and a textured protective finish 
coat. 

EXTERIOR INSULATION AND FINISH SYSTEMS 
(EIFS) WITH DRAINAGE. An EIFS that incorporates a 
means of drainage applied over a water-resistive barrier. 

EXTERIOR WALL. A wall, bearing or nonbearing, that is 
used as an enclosing wall for a building, other than afire wall, 
and that has a slope of 60 degrees (1.05 rad) or greater with the 
horizontal plane. 

EXTERIOR WALL COVERING. A material or assembly of 
materials applied on the exterior side of exterior walls for the 
purpose of providing a weather-resisting barrier, insulation or 
for aesthetics, including but not limited to, veneers, siding, 
exterior insulation and finish systems, architectural trim and 
embellishments such as cornices, soffits, facias, gutters and 
leaders. 

EXTERIOR WALL ENVELOPE. A system or assembly of 
exterior wall components, including exterior wall finish mate- 
rials, that provides protection of the building structural mem- 
bers, including framing and sheathing materials, and 
conditioned interior space, from the detrimental effects of the 
exterior environment. 

FIBER-CEMENT SIDING. A manufactured, fiber-reinforc- 
ing product made with an inorganic hydraulic or calcium sili- 
cate binder formed by chemical reaction and reinforced with 



discrete organic or inorganic nonasbestos fibers, or both. Addi- 
tives that enhance manufacturing or product performance are 
permitted. Fiber-cement siding products have either smooth or 
textured faces and are intended for exterior wall and related 
applications. 

METAL COMPOSITE MATERIAL (MCM). A fac- 
tory-manufactured panel consisting of metal skins bonded to 
both faces of a plastic core. 

METAL COMPOSITE MATERIAL (MCM) SYSTEM. 

An exterior wall covering fabricated using MCM in a specific 
assembly including joints, seams, attachments, substrate, 
framing and other details as appropriate to a particular design. 

VENEER. A facing attached to a wall for the purpose of pro- 
viding ornamentation, protection or insulation, but not counted 
as adding strength to the wall. 

VINYL SIDING. A shaped material, made principally from 
rigid polyvinyl chloride (PVC), that is used as an exterior wall 
covering. 

WATER-RESISTIVE BARRIER. A material behind an exte- 
rior wall covering that is intended to resist liquid water that has 
penetrated behind the exterior covering from further intruding 
into the exterior wall assembly. 



SECTION 1403 
PERFORMANCE REQUIREMENTS 

1403.1 General. The provisions of this section shall apply to 
exterior walls, wall coverings and components thereof. 

1403.2 Weather protection. Exterior walls shall provide the 
building with a weather-resistant exterior wall envelope. The 
exterior wall envelope shall include flashing, as described in 
Section 1405.4. The exterior wall envelope shall be designed 
and constructed in such a manner as to prevent the accumula- 
tion of water within the wall assembly by providing a 
water-resistive barrier behind the exterior veneer, as described 
in Section 1404.2, and a means for draining water that enters 
the assembly to the exterior. Protection against condensation in 
the exterior wall assembly shall be provided in accordance 
with Section 1405.3. 

Exceptions: 

1. A weather-resistant exterior wall envelope shall not 
be required over concrete or masonry walls designed 
in accordance with Chapters 19 and 21, respectively. 

2. Compliance with the requirements for a means of 
drainage, and the requirements of Sections 1404.2 
and 1405.4, shall not be required for an exterior wall 
envelope that has been demonstrated through testing 
to resist wind-driven rain, including joints, penetra- 
tions and intersections with dissimilar materials, in 



2009 INTERNATIONAL BUILDING CODE® 



277 



EXTERIOR WALLS 



accordance with ASTM 
conditions: 



E 331 under the following 



2.1. Exterior wall envelope test assemblies shall 
include at least one opening, one controljoint, 
one wall/eave interface and one wall sill. All 
tested openings and penetrations shall be rep- 
resentative of the intended end-use configura- 
tion. 

2.2. Exterior wall envelope test assemblies shall 
be at least 4 feet by 8 feet (1219 mm by 2438 
mm) in size. 

2.3. Exterior wall envelope assemblies shall be 
tested at a minimum differential pressure of 
6.24 pounds per square foot (psf) (0.297 
kN/m 2 ). 

2.4. Exterior wall envelope assemblies shall be 
subjected to a minimum test exposure dura- 
tion of 2 hours. 

The exterior wall envelope design shall be consid- 
ered to resist wind-driven rain where the results of 
testing indicate that water did not penetrate control 
joints in the exterior wall envelope, joints at the per- 
imeter of openings or intersections of terminations 
with dissimilar materials. 

3. Exterior insulation and finish systems (EIFS) com- 
plying with Section 1408.4.1. 

1403.3 Structural. Exterior walls, and the associated open- 
ings, shall be designed and constructed to resist safely the 
superimposed loads required by Chapter 16. 

1403.4 Fire resistance. Exterior walls shall be fire-resistance 
rated as required by other sections of this code with opening 
protection as required by Chapter 7. 

1403.5 Flood resistance. For buildings in flood hazard areas as 
established in Section 1612.3, exterior walls extending below 
the design flood elevation shall be resistant to water damage. 
Wood shall be pressure-preservative treated in accordance with 
AWPA Vl for the species, product and end use using a preser- 
vative listedin Section 4 of AWPA VI or decay-resistant heart- 
wood of redwood, black locust or cedar. 

1403.6 Flood resistance for high- velocity wave action areas. 
For buildings in flood hazard areas subject to high- velocity 
wave action as established in Section 1612.3, electrical, 
mechanical and plumbing system components shall not be 
mounted on or penetrate through exterior walls that are 
designed to break away under flood loads. 



SECTION 1404 
MATERIALS 

1404.1 General. Materials used for the construction of exterior 
walls shall comply with the provisions of this section. Materi- 
als not prescribed herein shall be permitted, provided that any 
such alternative has been approved. 



1404.2 Water-resistive barrier. A minimum of one layer of 
No.15 asphalt felt, complying with ASTM D 226 for Type 1 
felt or other approve dmaterials, shall be attached to the studs or 
sheathing, with flashing as described in Section 1405.4, in such 
a manner as to provide a continuous water-resistive barrier 
behind the exterior wall veneer. 

1404.3 Wood. Exterior walls of wood construction shall be 
designed and constructed in accordance with Chapter 23. 

1404.3.1 Basic hardboard. Basic hardboard shall conform 
to the requirements of AHA AI35.4. 

1404.3.2 Hardboard siding. Hardboard siding shall con- 
form to the requirements of AHA A 135. 6 and, where used 
structurally, shall be so identified by the label of an 
approved agency. 

1404.4 Masonry. Exterior walls of masonry construction shall 
be designed and constructed in accordance with this section 
and Chapter 21. Masonry units, mortar and metal accessories 
used in anchored and adhered veneer shall meet the physical 
requirements of Chapter 21. The backing of anchored and 
adhered veneer shall be of concrete, masonry, steel framing or 
wood framing. 

1404.5 Metal. Exterior walls of formed steel construction, 
structural steel or lightweight metal alloys shall be designed in 
accordance with Chapters 22 and 20, respectively. 

1404.5.1 Aluminum siding. Aluminum siding shall con- 
form to the requirements of AAMA 1402. 

1404.5.2 Cold-rolled copper. Copper shall conform to the 
requirements of ASTM B 370. 

1404.5.3 Lead-coated copper. Lead-coated copper shall 
conform to the requirements of ASTM B 101. 

1404.6 Concrete. Exterior walls of concrete construction shall 
be designed and constructed in accordance with Chapter 19 . 

1404.7 Glass-unit masonry. Exterior walls of glass-unit 
masonry shall be designed and constructed in accordance with 
Chapter 21. 

1404.8 Plastics. Plastic panel, apron or spandrel walls as 
defined in this code shall not be limited in thickness, provided 
that such plastics and their assemblies conform to the require- 
ments of Chapter 26 and are constructed of approved 
weather-resistant materials of adequate strength to resist the 
wind loads for cladding specified in Chapter 16. 

1404.9 Vinyl siding. Vinyl siding shall be certified and labeled 
as conforming to the requirements of ASTM D 3679 by an 
approved quality control agency. 

1404.10 Fiber-cement siding. Fiber-cement siding shall con- 
form to the requirements of ASTM C 1186, Type A, and shall 
be so identified on labeling listing an approved quality control 
agency. 

1404.11 Exterior insulation and finish systems. Exterior 
insulation and finish systems (EIFS) and exterior insulation 
and finish systems (EIFS) with drainage shall comply with 
Section 1408. 



278 



2009 INTERNATIONAL BUILDING CODE® 



EXTERIOR WALLS 



TABLE 1405.2 
MINIMUM THICKNESS OF WEATHER COVERINGS 



COVERING TYPE 


MINIMUM THICKNESS 
(inches) 


Adhered masonry veneer 


0.25 


Aluminum siding 


0.019 


Anchored masonry veneer 


2.625 


Asbestos-cement boards 


0.125 


Asbestos shingles 


0.156 


Cold-rolled copper d 


0.0216 nominal 


Copper shingles d 


0.0162 nominal 


Exterior plywood (with sheathing) 


0.313 


Exterior plywood (without sheathing) 


See Section 2304.6 


Fiber cement lap siding 


0.25 c 


Fiber cement panel siding 


0.25 c 


Fiberboard siding 


0.5 


Glass-fiber reinforced concrete panels 


0.375 


Hardboard siding 


0.25 


High-yield copper d 


0.0162 nominal 


Lead-coated copper d 


0.0216 nominal 


Lead-coated high-yield copper 


0.0162 nominal 


Marble slabs 


1 


Particleboard (with sheathing) 


See Section 2304.6 


Particleboard (without sheathing) 


See Section 2304.6 


Precast stone facing 


0.625 


Steel (approved corrosion resistant) 


0.0149 


Stone (cast artificial) 


1.5 


Stone (natural) 


2 


Structural glass 


0.344 


Stucco or exterior cement plaster 
Three-coat work over: 
Metal plaster base 
Unit masonry 
Cast-in-place or precast concrete 


0.375 b 
0.625 b 
0.625 b 


Two-coat work over: 
Unit masonry 
Cast-in-place or precast concrete 


0.5 b 
0.375 b 


Terra cotta (anchored) 


1 


Terra cotta (adhered) 


0.25 


Vinyl siding 


0.035 


Wood shingles 


0.375 


Wood siding (without sheathing)a 


0.5 



For SI: 1 inch = 25.4 mm. 

a. Wood siding of thicknesses less than 0.5 inch shall be placed over sheathing 
that conforms to Section 2304.6. 

b. Exclusive of texture. 

c. As measured at the bottom of decorative grooves. 

d. 16 ounces per square foot for cold-rolled copper and lead-coated copper, 12 
ounces per square foot for copper shingles, high-yield copper and 
lead-coated high-yield copper. 



SECTION 1405 
INSTALLATION OF WALL COVERINGS 

1405.1 General. Exterior wall coverings shall be designed and 
constructed in accordance with the applicable provisions of 
this section. 

1405.2 Weather protection. Exterior walls shall provide 
weather protection for the building. The materials of the mini- 
mum nominal thickness specified in Table 1405.2 shall be 
acceptable as approved weather coverings. 

1405.3 Vapor retarders. Class I or II vapor retarders shall be 
provided on the interior side of frame walls in Zones 5,6,7,8 
and Marine 4. 

Exceptions: 

1. Basement walls. 

2. Below-grade portion of any wall. 

3. Construction where moisture or its freezing will not 
damage the materials. 

1405.3.1 Class III vapor retarders. Class III vapor retard- 
ers shall be permitted where anyone of the conditions in 
Table 1405.3.1 is met. 

TABLE 1405.3.1 
CLASS III VAPOR RETARDERS 



ZONE 


CLASS III VAPOR RETARDERS PERMITTED FOR: 3 


Marine 
4 


Vented cladding over OSB 

Vented cladding over plywood 

Vented cladding over fiberboard 

Vented cladding over gypsum 

Insulated sheathing with R-value > R2.5 over 2x4 wall 

Insulated sheathing with R-value > R3.75 over 2x6 wall 


5 


Vented cladding over OSB 

Vented cladding over plywood 

Vented cladding over fiberboard 

Vented cladding over gypsum 

Insulated sheathing with R-value > R5 over 2x4 wall 

Insulated sheathing with R-value > R7.5 over 2x6 wall 


6 


Vented cladding over fiberboard 

Vented cladding over gypsum 

Insulated sheathing with R-value > R7.5 over 2x4 wall 

Insulated sheathing with R-value > RII.25 over 2x6 wall 


7 and 8 


Insulated sheathing with R-value > RIO over 2x4 wall 
Insulated sheathing with R-value > RI5 over 2x6 wall 



For SI: 1 pound per cubic foot = 16 kg/m 3 . 

a. Spray foam with a minimum density of 21bs/ft 3 applied to the interior cavity 
side of OSB, plywood, fiberboard, insulating sheathing or gypsum is 
deemed to meet the insulating sheathing requirement where the spray foam 
R-value meets or exceeds the specified insulating sheathing R-value. 

1405.3.2 Material vapor retarder class. The vapor 
retarder class shall be based on the manufacturer's certified 
testing or a tested assembly. 

The following shall be deemed to meet the class speci- 
fied: 

Class I: Sheet polyethylene, nonperforated aluminum 
foil 



2009 INTERNATIONAL BUILDING CODE® 



279 



EXTERIOR WALLS 



I 



1 



Class II: Kraft-faced fiberglass batts or paint with a 
perm rating greater than 0.1 and less than or 
equal to 1.0 

Class III: Latex or enamel paint 

1405.3.3 Minimum clear airspaces and vented openings 
for vented cladding. For the purposes of this section, 
vented cladding shall include the following minimum clear 
airspaces. 

1. Vinyl lap or horizontal aluminum siding applied over 
a weather-resistive barrier as specified in this chapter. 

2. Brick veneer with a clear airspace as specified in this 
code. 

3. Other approve d vented claddings. 

1405.4 Flashing. Flashing shall be installed in such a manner 
so as to prevent moisture from entering the wall or to redirect it 
to the exterior. Flashing shall be installed at the perimeters of 
exterior door and window assemblies, penetrations and termi- 
nations of exterior wall assemblies, exterior wall intersections 
with roofs, chimneys, porches, decks, balconies and similar 
projections and at built-in gutters and similar locations where 
moisture could enter the wall. Flashing with projecting flanges 
shall be installed on both sides and the ends of copings, under 
sills and continuously above projecting trim. 

1405.4.1 Exterior wall pockets. In exterior walls of build- 
ings or structures, wall pockets or crevices in which mois- 
ture can accumulate shall be avoided or protected with caps 
or drips, or other approved means shall be provided to pre- 
vent water damage. 

1405.4.2 Masonry. Flashing and weep holes in anchored 
veneer shall be located in the first course of masonry above 
finished ground level above the foundation wall or slab, and 
other points of support, including structural floors, shelf 
angles and lintels where anchored veneers are designed in 
accordance with Section 1405.6. 

1405.5 Wood veneers. Wood veneers on exterior walls of 
buildings of Type I, II, III and IV construction shall be not less 
than 1 inch (25 mm) nominal thickness, 0.438-inch (11.1 mm) 
exterior hardboard siding or 0.375-inch (9.5 mm) exterior-type 
wood structural panels or particleboard and shall conform to 
the following: 

1. The veneer shall not exceed 40 feet (1219 mm) in height 
above grade. Where fire-retardant -treated wood is used, 
the height shall not exceed 60 feet (1829 mm) in height 
above grade. 

2. The veneer is attached to or furred from a 
noncombustible backing that is fire-resistance rated as 
required by other provisions of this code. 

3. Where open or spaced wood veneers (without concealed 
spaces) are used, they shall not project more than 24 
inches (610 mm) from the building wall. 

1405.6 Anchored masonry veneer. Anchored masonry 
veneer shall comply with the provisions of Sections 1405.6, 
1405.7, 1405.8 and 1405.9 and Sections 6.1 and 6.2 of TMS 
402/ACI 530/ASCE 5. 



1405.6.1 Tolerances. Anchored masonry veneers in accor- 
dance with Chapter 14 are not required to meet the toler- 
ances in Article 3.3 Gl of TMS 6021 ACI 530.11 ASCE 6. 

1405.6.2 Seismic requirements. Anchored masonry 
veneer located in Seismic Design Category C, D, E or F 
shall conform to the requirements of Section 6.2.2.10 of 
TMS 402/ACI 530/ASCE 5. Anchored masonry veneer 
located in Seismic Design Category D shall also conform to 
the requirements of Section 6.2.2.10.3.3 of TMS 402/ACI 
530/ASCE 5. 

1405.7 Stone veneer. Stone veneer units not exceeding 10 
inches (254 mm) in thickness shall be anchored directly to 
masonry, concrete or to stud construction by one of the follow- 
ing methods: 

1. With concrete or masonry backing, anchor ties shall be 
not less than 0.1055-inch (2.68 mm) corrosion-resistant 
wire, or approve d equal, formed beyond the base of the 
backing. The legs of the loops shall be not less than 6 
inches (152 mm) in length bent at right angles and laid in 
the mortar joint, and spaced so that the eyes or loops are 
12 inches (305 mm) maximum on center (o.c.) in both 
directions. There shall be provided not less than a 
0.1055-inch (2.68 mm) corrosion-resistant wire tie, or 
approved equal, threaded through the exposed loops for 
every 2 square feet (0.2 m 2 ) of stone veneer. This tie shall 
be a loop having legs not less than 15 inches (381 mm) in 
length bent so that it will lie in the stone veneer mortar 
joint. The last 2 inches (51 mm) of each wire leg shall 
have a right-angle bend. One-inch (25 mm) minimum 
thickness of cement grout shall be placed between the 
backing and the stone veneer. 

2. With stud backing, a 2-inch by 2-inch (51 by 51 mm) 
0.0625-inch (1.59 mm) corrosion-resistant wire mesh 
with two layers of water-resistive barrier in accordance 
with Section 1404.2 shall be applied directly to wood 
studs spaced a maximum of 16 inches (406 mm) o.c. On 
studs, the mesh shall be attached with 2-inch-Iong (51 
mm) corrosion-resistant steel wire furring nails at 4 
inches (102 mm) o.c. providing a minimum 1.125-inch 
(29 mm) penetration into each stud and with 8d common 
nails at 8 inches (203 mm) o.c. into top and bottom plates 
or with equivalent wire ties. There shall be not less than a 
0.1055-inch (2.68 mm) corrosion-resistant wire, or 
approved equal, looped through the mesh for every 2 
square feet (0.2 m 2 ) of stone veneer. This tie shall be a 
loop having legs not less than 15 inches (381 mm) in 
length, so bent that it will lie in the stone veneer mortar 
joint. The last 2 inches (51 mm) of each wire leg shall 
have a right-angle bend. One-inch (25 mm) minimum 
thickness of cement grout shall be placed between the 
backing and the stone veneer. 

1405.8 Slab-type veneer. Slab-type veneer units not exceed- 
ing 2 inches (51 mm) in thickness shall be anchored directly to 
masonry, concrete or stud construction. For veneer units of 
marble, travertine, granite or other stone units of slab form ties 
of corrosion-resistant dowels in drilled holes shall be located in 
the middle third of the edge of the units, spaced a maximum of 
24 inches (610 mm) apart around the periphery of each unit 



280 



2009 INTERNATIONAL BUILDING CODE® 



EXTERIOR WALLS 



1 



with not less than four ties per veneer unit. Units shall not 
exceed 20 square feet (1.9 m 2 ) in area. If the dowels are not tight 
fitting, the holes shall be drilled not more than 0.063 inch (1.6 
mm) larger in diameter than the dowel, with the hole counter- 
sunk to a diameter and depth equal to twice the diameter of the 
dowel in order to provide a tight-fitting key of cement mortar at 
the dowel locations when the mortar in the joint has set. Veneer 
ties shall be corrosion-resistant metal capable of resisting, in 
tension or compression, a force equal to two times the weight of 
the attached veneer. If made of sheet metal, veneer ties shall be 
not smaller in area than 0.0336 by 1 inch (0.853 by 25 mm) or, 
if made of wire, not smaller in diameter than 0.1483-inch (3.76 
mm) wire. 

1405.9 Terra cotta. Anchored terra cotta or ceramic units not 
less than 1 5 1 8 inches (41 mm) thick shall be anchored directly to 
masonry, concrete or stud construction. Tied terra cotta or 
ceramic veneer units shall be not less than 1 5 / 8 inches (41 mm) 
thick with projecting dovetail webs on the back surface spaced 
approximately 8 inches (203 mm) o.c. The facing shall be tied 
to the backing wall with corrosion-resistant metal anchors of 
not less than No. 8 gage wire installed at the top of each piece in 
horizontal bedjoints not less than 12 inches (305 mm) nor more 
than 18 inches (457 mm) o.c; these anchors shall be secured to 
1/4-inch (6.4 mm) corrosion-resistant pencil rods that pass 
through the vertical aligned loop anchors in the backing wall. 
The veneer ties shall have sufficient strength to support the full 
weight of the veneer in tension. The facing shall be set with not 
less than a 2-inch (51 mm) space from the backing wall and the 
space shall be filled solidly with portland cement grout and pea 
gravel. Immediately prior to setting, the backing wall and the 
facing shall be drenched with clean water and shall be dis- 
tinctly damp when the grout is poured. 

1405.10 Adhered masonry veneer. Adhered masonry veneer 
shall comply with the applicable requirements of Section 
1405.10.1 and Sections 6.1 and 6.3 of TMS 402/ACI 
530/ASCE 5. 

1405.10.1 Interior adhered masonry veneers. Interior 
adhered masonry veneers shall have a maximum weight of 
20 psf (0.958 kg/m 2 ) and shall be installed in accordance 
with Section 1405.10. Where the interior adhered masonry 
veneer is supported by wood construction, the supporting 
members shall be designed to limit deflection to i/ 600 of the 
span of the supporting members. 

1405.11 Metal veneers. Veneers of metal shall be fabricated 
from approved corrosion-resistant materials or shall be pro- 
tected front and back with porcelain enamel, or otherwise be 
treated to render the metal resistant to corrosion. Such veneers 
shall not be less than 0.0149-inch (0.378 mm) nominal thick- 
ness sheet steel mounted on wood or metal furring strips or 
approved sheathing on the wood construction. 

1405.11.1 Attachment. Exterior metal veneer shall be 
securely attached to the supporting masonry or framing 
members with corrosion-resistant fastenings, metal ties or 
by other approved devices or methods. The spacing of the 
fastenings or ties shall not exceed 24 inches (610 mm) either 
vertically or horizontally, but where units exceed 4 square 
feet (0.4 m 2 ) in area there shall be not less than four attach- 
ments per unit. The metal attachments shall have a 



cross-sectional area not less than provided by W 1.7 wire. 
Such attachments and their supports shall be capable of 
resisting a horizontal force in accordance with the wind 
loads specified in Section 1609, but in no case less than 20 
psf (0.958 kg/m 2 ). 

1405.11.2 Weather protection. Metal supports for exterior 
metal veneer shall be protected by painting, galvanizing or 
by other equivalent coating or treatment. Wood studs, fur- 
ring strips or other wood supports for exterior metal veneer 
shall be approved pressure- treated wood or protected as 
required in Section 1403.2. Joints and edges exposed to the 
weather shall be caulked with approveddmabie waterproof- 
ing material or by other approvedmzans to prevent penetra- 
tion of moisture. 

1405.11.3 Backup. Masonry backup shall not be required 
for metal veneer except as is necessary to meet the fire- resis- 
tance requirements of this code. 

1405.11.4 Grounding. Grounding of metal veneers on 
buildings shall comply with the requirements of Chapter 27 
of this code. 

1405.12 Glass veneer. The area of a single section of thin exte- 
rior structural glass veneer shall not exceed 10 square feet (0.93 
m 2 ) where it is not more than 15 feet (4572 mm) above the level 
of the sidewalk or grade level directly below, and shall not 
exceed 6 square feet (0.56 m 2 ) where it is more than 15 feet 
(4572 mm) above that level. 

1405.12.1 Length and height. The length or height of any 
section of thin exterior structural glass veneer shall not 
exceed 48 inches (1219 mm). 

1405.12.2 Thickness. The thickness of thin exterior struc- 
tural glass veneer shall be not less than 0.344 inch (8.7 mm). 

1405.12.3 Application. Thin exterior structural glass 
veneer shall be set only after backing is thoroughly dry and 
after application of an approvedbond coat uniformly over 
the entire surface of the backing so as to effectively seal the 
surface. Glass shall be set in place with an approved mastic 
cement in sufficient quantity so that at least 50 percent of the 
area of each glass unit is directly bonded to the backing by 
mastic not less than i/ 4 inch (6.4 mm) thick and not more 
than 5l 8 inch (15.9 mm) thick. The bond coat and mastic shall 
be evaluated for compatibility and shall bond firmly 
together. 

1405.12.4 Installation at sidewalk level. Where glass 
extends to a sidewalk surface, each section shall rest in an 
approvedmetal molding, and be set at least i/ 4 inch (6.4 mm) 
above the highest point of the sidewalk. The space between 
the molding and the sidewalk shall be thoroughly caulked 
and made water tight. 

1405.12.4.1 Installation above sidewalk level. Where 
thin exterior structural glass veneer is installed above the 
level of the top of a bulkhead facing, or at a level more 
than 36 inches (914 mm) above the sidewalk level, the 
mastic cement binding shall be supplemented with 
approved nonferrous metal shelf angles located in the 
horizontal joints in every course. Such shelf angles shall 
be not less than 0.0478-inch (1.2 mm) thick and not less 
than 2 inches (51 mm) long and shall be spaced at 



2009 INTERNATIONAL BUILDING CODE® 



281 



EXTERIOR WALLS 



1 



approvedintervals, with not less than two angles for each 
glass unit. Shelf angles shall be secured to the wall or 
backing with expansion bolts, toggle bolts or by other 
approved methods. 

1405.12.5 Joints. Unless otherwise specifically approved 
by the building official, abutting edges of thin exterior struc- 
tural glass veneer shall be ground square. Mitered joints 
shall not be used except where specifically approved for 
wide angles. Joints shall be uniformly buttered with an 
approved]omtmg compound and horizontal joints shall be 
held to not less than 0.063 inch (1.6 mm) by an approved 
nonrigid substance or device. Where thin exterior structural 
glass veneer abuts nonresilient material at sides or top, 
expansionjoints not less than i/ 4 inch (6.4 mm) wide shall be 
provided. 

1405.12.6 Mechanical fastenings. Thin exterior structural 
glass veneer installed above the level of the heads of show 
windows and veneer installed more than 12 feet (3658 mm) 
above sidewalk level shall, in addition to the mastic cement 
and shelf angles, be held in place by the use of fastenings at 
each vertical or horizontal edge, or at the four corners of 
each glass unit. Fastenings shall be secured to the wall or 
backing with expansion bolts, toggle bolts or by other meth- 
ods. Fastenings shall be so designed as to hold the glass 
veneer in a vertical plane independent of the mastic cement. 
Shelf angles providing both support and fastenings shall be 
permitted. 

1405.12.7 Flashing. Exposed edges of thin exterior struc- 
tural glass veneer shall be flashed with overlapping corro- 
sion-resistant metal flashing and caulked with a waterproof 
compound in a manner to effectively prevent the entrance of 
moisture between the glass veneer and the backing. 

1405.13 Exterior windows and doors. Windows and doors 
installed in exterior walls shall conform to the testing and per- 
formance requirements of Section 1715.5. 

1405.13.1 Installation. Windows and doors shall be 
installed in accordance with approved manufacturer's 
instructions. Fastener size and spacing shall be provided in 
such instructions and shall be calculated based on maximum 
loads and spacing used in the tests. 

1405.13.2 Window sills. In Occupancy Groups R-2 and 
R-3, one- and two-family and multiple-family dwellings, 
where the opening of the sill portion of an operable window 
is located more than 72 inches (1829 mm) above the fin- 
ished grade or other surface below, the lowest part of the 
clear opening of the window shall be at a height not less than 
24 inches (610 mm) above the finished floor surface of the 
room in which the window is located. Glazing between the 
floor and a height of 24 inches (610 mm) shall be fixed or 
have openings through which a 4-inch (102 mm) diameter 
sphere cannot pass. 

Exception: Openings that are provided with window 
guards that comply with ASTM F 2006 or F 2090. 

1405.14 Vinyl siding. Vinyl siding conforming to the require- 
ments of this section and complying with ASTM D 3679 shall 
be permitted on exterior walls of buildings located in areas 



where the basic wind speed specified in Chapter 16 does not 
exceed 100 miles per hour (45 m/s) and the bUilding height is 
less than or equal to 40 feet (12 192 mm) in Exposure C. Where 
construction is located in areas where the basic wind speed 
exceeds 100 miles per hour (45 m/s) , or building heights are in 
excess of 40 feet (12 192 mm), tests or calculations indicating 
compliance with Chapter 16 shall be submitted. Vinyl siding 
shall be secured to the building so as to provide weather protec- 
tion for the exterior walls of the building. 

1405.14.1 Application. The siding shall be applied over 
sheathing or materials listed in Section 2304.6. Siding shall 
be applied to conform with the water-resistive barrier 
requirements in Section 1403. Siding and accessories shall 
be installed in accordance with approved manufacturer's 
instructions. Unless otherwise specified in the approved 
manufacturer's instructions, nails used to fasten the siding 
and accessories shall have a minimum 0.313-inch (7.9 mm) 
head diameter and lis-inch (3.18 mm) shank diameter. The 
nails shall be corrosion resistant and shall be long enough to 
penetrate the studs or nailing strip at least 3/ 4 inch (19 mm). 
Where the siding is installed horizontally, the fastener spac- 
ing shall not exceed 16 inches (406 mm) horizontally and 12 
inches (305 mm) vertically. Where the siding is installed 
vertically, the fastener spacing shall not exceed 12 inches 
(305 mm) horizontally and 12 inches (305 mm) vertically. 

1405.15 Cement plaster. Cement plaster applied to exterior 
walls shall conform to the requirements specified in Chapter 

25. 

1405.16 Fiber-cement siding. Fiber-cement siding comply- 
ing with Section 1404. 10 shall be permitted on exterior walls of 
Type I, II, III, IV and V construction for wind pressure resis- 
tance or wind speed exposures as indicated by the manufac- 
turer's listing and label and approve d installation instructions. 
Where specified, the siding shall be installed over sheathing or 
materials listedin Section 2304.6 and shall be installed to con- 
form to the water-resistive barrier requirements in Section 
1403. Siding and accessories shall be installed in accordance 
with approve d manufacturer's instructions. Unless otherwise 
specified in the approved manufacturer's instructions, nails 
used to fasten the siding to wood studs shall be corrosion-resis- 
tant round head smooth shank and shall be long enough to pen- 
etrate the studs at least 1 inch (25 mm) . For metal framing, 
all-weather screws shall be used and shall penetrate the metal 
framing at least three full threads . 

1405.16.1 Panel siding. Fiber-cement panels shall comply 
with the requirements of ASTM C 1186, Type A, minimum 
Grade II. Panels shall be installed with the long dimension 
either parallel or perpendicular to framing. Vertical and hor- 
izontal oints shall occur over framing members and shall be 
sealed with caulking, covered with battens or shall be 
designed to comply with Section 1403.2. Panel siding shall 
be installed with fasteners in accordance with the approved 
manufacturer's instructions. 

1405.16.2 Lap siding. Fiber-cement lap siding having a 
maximum width of 12 inches (305 mm) shall comply with 
the requirements of ASTM C 1186, Type A, minimum 
Grade II. Lap siding shall be lapped a minimum of V/ 4 



282 



2009 INTERNATIONAL BUILDING CODE® 



EXTERIOR WALLS 



inches (32 mm) and lap siding not having tongue-and- 
groove end joints shall have the ends sealed with caulking, 
covered with an H-sectionjoint cover, located over a strip of 
flashing or shall be designed to comply with Section 
1403.2. Lap siding courses shall be installed with the fas- 
tener heads exposed or concealed in accordance with the 
approved manufacturer's instructions. 

1405. 17 Fastening. Weather boarding and wall coverings shall 
be securely fastened with aluminum, copper, zinc, zinc-coated 
or other approved corrosion-resistant fasteners in accordance 
with the nailing schedule in Table 2304.9.1 or the approved 
manufacturer's installation instructions. Shingles and other 
weather coverings shall be attached with appropriate stan- 
dard-shingle nails to furring strips securely nailed to studs, or 
with approved mechanically bonding nails, except where 
sheathing is of wood not less than I-inch (25 mm) nominal 
thickness or of wood structural panels as specified in Table 
2308.9.3(3). 



SECTION 1406 

COMBUSTIBLE MATERIALS ON THE EXTERIOR 

SIDE OF EXTERIOR WALLS 

1406.1 General. Section 1406 shall apply to exterior wall cov- 
erings; balconies and similar projections; and bay and oriel 
windows constructed of combustible materials. 

1406.2 Combustible exterior wall coverings. Combustible 
exterior wall coverings shall comply with this section. 

Exception: Plastics complying with Chapter 26. 

1406.2.1 Ignition resistance. Combustible exterior wall 
coverings shall be tested in accordance with NFPA 268. 

Exceptions: 

1 Wood or wood-based products. 

2. Other combustible materials covered with an exte- 
rior covering other than vinyl sidings listed in 
Table 1405.2. 

3. Aluminum having a minimum thickness of 0.019 
inch (0.48 mm). 

4. Exterior wall coverings on exterior walls of Type 
V construction. 

1406.2.1.1 Fire separation 5 feet or less. Where 
installed on exterior walls having a fire separation dis- 
tance of 5 feet (1524 mm) or less, combustible exterior 
wall coverings shall not exhibit sustained flaming as 
defined in NFPA 268. 

1406.2. 1 .2 Fire separation greater than 5 feet. For fire 
separation distances greater than 5 feet (1524 mm), an 
assembly shall be permitted that has been exposed to a 
reduced level of incident radiant heat flux in accordance 
with the NFPA 268 test method without exhibiting sus- 
tained flaming. The minimum fire separation distance 
required for the assembly shall be determined from Table 
1406.2. 1 .2 based on the maximum tolerable level of inci- 
dent radiant heat flux that does not cause sustained flam- 
ing of the assembly. 



TABLE 1406.2.1.2 
MINIMUM FIRE SEPARATION FOR COMBUSTIBLE VENEERS 



FIRE 


TOLERABLE 


FIRE 


TOLERABLE 


SEPARATION 


LEVEL INCIDENT 


SEPARATION 


LEVEL INCIDENT 


DISTANCE 


RADIANT HEAT 


DISTANCE 


RADIANT HEAT 


(feet) 


ENERGY(kW/m 2 ) 


(feet) 


ENERGY(kW/m 2 ) 


5 


12.5 


16 


5.9 


6 


11.8 


17 


5.5 


7 


11.0 


18 


5.2 


8 


10.3 


19 


4.9 


9 


9.6 


20 


4.6 


10 


8.9 


21 


4.4 


11 


8.3 


22 


4.1 


12 


7.7 


23 


3.9 


13 


7.2 


24 


3.7 


14 


6.7 


25 


3.5 


15 


6.3 







For 51 : 1 foot = 304.8 mm, 1 Btu/Hz x OF = 0.0057 kW/m z x K . 

1406.2.2 Type I, II, III and IV construction. On buildings 
of Type I, II, III and IV construction, exterior wall coverings 
shall be permitted to be constructed of wood in accordance 
with Section 1405.5, or other equivalent combustible mate- 
rial, complying with the following limitations: 

1. Combustible exterior wall coverings shall not exceed 
10 percent of an exterior wall surface area where the 

fire separation distance is 5 feet (1524 mm) or less. 

2. Combustible architectural trim shall be limited to 40 
feet (12 192 mm) in height above grade. 

3. Combustible exterior wall coverings constructed of 
fire-retardant-treated wood complying with Section 
2303.2 for exterior installation shall not be limited in 
wall surface area where the fire separation distance is 
5 feet (1524 mm) or less and shall be permitted up to 
60 feet (18 288 mm) in height above grade regardless 
of the fire separation distance. 

1406.2.3 Location. Where combustible exterior wall cov- 
ering is located along the top of exterior walls, such trim 
shall be completely backed up by the exterior wall and shall 
not extend over or above the top of exterior walls. 

1406.2.4 Fireblocking. Where the combustible exterior 
wall covering is furred from the wall and forms a solid sur- 
face, the distance between the back of the covering and the 
wall shall not exceed ls/ 8 inches (41 mm). Where required 
by Section 717, the space thereby created shall be 
fireblocked. 

1406.3 Balconies and similar projections. Balconies and 
similar projections of combustible construction other than 
fire-retardant-treated wood shall be fire-resistance rated in 
accordance with Table 601 for floor construction or shall be of 
Type IV construction in accordance with Section 602.4. The 
aggregate length shall not exceed 50 percent of the buildings 
perimeter on each floor. 

Exceptions: 

1. On buildings of Type I and II construction, three sto- 
ries or less above grade plane, fire-retardant-treated 
wooJshall be permitted for balconies, porches, decks 
and exterior stairways not used as required exits. 



2009 INTERNATIONAL BUILDING CODE® 



283 



EXTERIOR WALLS 



2. Untreated wood is permitted for pickets and rails or 
similar guardrail devices that are limited to 42 inches 
(1067 mm) in height. 

3. Balconies and similar projections on buildings of 
Type III, IV and V construction shall be permitted to 
be of Type V construction, and shall not be required to 
have a fire-resistance rating where sprinkler protec- 
tion is extended to these areas. 

4. Where sprinkler protection is extended to the balcony 
areas, the aggregate length of the balcony on each 
floor shall not be limited. 

1406.4 Bay windows and oriel windows. Bay and oriel win- 
dows shall conform to the type of construction required for the 
building to which they are attached. 

Exception: Fire-retardant-treated wood shall be permitted 
on buildings three stories or less of Type I, II, III and IV con- 
struction. 



SECTION 1407 
METAL COMPOSITE MATERIALS (MCM) 

1407.1 General. The provisions of this section shall govern the 
materials, construction and quality of metal composite materi- 
als (MCM) for use as exterior wall coverings in addition to 
other applicable requirements of Chapters 14 and 16. 

1407.1.1 Plastic core. The plastic core of the MCM shall 
not contain foam plastic insulation as defined in Section 
2602.1. 

1407.2 Exterior wall finish. MCM used as exterior wall finish 
or as elements of balconies and similar projections and bay and 
oriel windows to provide cladding or weather resistance shall 
comply with Sections 1407.4 through 1407.14. 

1407.3 Architectural trim and embellishments. MCM used 
as architectural trim or embellishments shall comply with Sec- 
tions 1407.7 through 1407.14. 

1407.4 Structural design. MCM systems shall be designed 
and constructed to resist wind loads as required by Chapter 16 
for components and cladding. 

1407.5 Approval. Results of appro ved tests or an engineering 
analysis shall be submitted to the building official to verify 
compliance with the requirements of Chapter 16 for wind 
loads. 

1407.6 Weather resistance. MCM systems shall comply with 
Section 1403 and shall be designed and constructed to resist 
wind and rain in accordance with this section and the manufac- 
turer's installation instructions. 

1407.7 Durability. MCM systems shall be constructed of 
approvedmaterials that maintain the performance characteris- 
tics required in Section 1407 for the duration of use. 

1407.8 Fire-resistance rating. Where MCM systems are used 
on exterior walls required to have a fire-resistance rating in 
accordance with Section 705, evidence shall be submitted to 



the building official that the required fire-resistance rating is 
maintained. 

Exception: MCM systems not containing foam plastic 
insulation, which are installed on the outer surface of a 
fire-resistance-rated exterior wall in a manner such that the 
attachments do not penetrate through the entire exterior 
wall assembly, shall not be required to comply with this sec- 
tion. 

1407.9 Surface-burning characteristics. Unless otherwise 
specified, MCM shall have aflame spread index of 75 or less 
and a smoke-developed index of 450 or less when tested in the 
maximum thickness intended for use in accordance with 
ASTM E 84 or UL 723. 

1407.10 Type I, II, III and IV construction. Where installed 
on buildings of Type I, II, III and IV construction, MCM sys- 
tems shall comply with Sections 1407. 10.1 through 1407.10.4, 
or Section 1407. 11. 

1407.10.1 Surface-burning characteristics. MCM shall 
have aflame spread index of not more than 25 and a smoke- 
developed index of not more than 450 when tested as an 
assembly in the maximum thickness intended for use in 
accordance with ASTM E 84 or UL 723. 

1407.10.2 Thermal barriers. MCM shall be separated 
from the interior of a building by an approve d thermal bar- 
rier consisting of i/ 2 -inch (12.7 mm) gypsum wallboard or 
equivalent thermal barrier material that will limit the aver- 
age temperature rise of the unexposed surface to not more 
than 250°F (121°C) after 15 minutes of fire exposure in 
accordance with the standard time-temperature curve of 
ASTM E 119 or UL 263. The thermal barrier shall be 
installed in such a manner that it will remain in place for not 
less than 15 minutes based on a test conducted in accor- 
dance with UL 1715. 

1407.10.3 Thermal barrier not required. The thermal 
barrier specified for MCM in Section 1407.10.2 is not 
required where: 

1. The MCM system is specifically approved based on 
tests conducted in accordance with UL 1040 or UL 
1715. Such testing shall be performed with the MCM 
in the maximum thickness intended for use. The 
MCM system shall include seams, joints and other 
typical details used in the installation and shall be 
tested in the manner intended for use. 

2. The MCM is used as elements of balconies and simi- 
lar projections, architectural trim or embellishments. 

1407.10.4 Full-scale tests. The MCM system shall be 
tested in accordance with, and comply with, the acceptance 
criteria ofNFPA 285. Such testing shall be performed on the 
MCM system with the MCM in the maximum thickness 
intended for use. 

1407.11 Alternate conditions. MCM and MCM systems shall 
not be required to comply with Sections 1407.10.1 through 



284 



2009 INTERNATIONAL BUILDING CODE® 



EXTERIOR WALLS 



I 



1 



1407.10.4 provided such systems comply with Section 
1407.11.1 or 1407.11.2. 

1407.11.1 Installations up to 40 feet in height. MCM shall 
not be installed more than 40 feet (12 190 mm) in height 
above grade where installed in accordance with Sections 
1407.11.1.1 and 1407.11.1.2. 

1407.11.1.1 Fire separation distance of 5 feet or less. 

Where they're separation distance is 5 feet (1524 mm) or 
less, the area of MCM shall not exceed 10 percent of the 
exterior wall surface. 

1407.11.1.2 Fire separation distance greater than 5 
feet. Where the fire separation distance is greater than 5 
feet (1524 mm), there shall be no limit on the area of exte- 
rior wallsmf zee coverage using MCM. 

1407.11.2 Installations up to 50 feet in height. MCM shall 
not be installed more than 50 feet (15 240 mm) in height 
above grade where installed in accordance with Sections 
1407.11.2.1 and 1407.11.2.2. 

1407.11.2.1 Self-ignition temperature. MCM shall 
have a self-ignition temperature of 650°F (343°C) or 
greater when tested in accordance with ASTM D 1929. 

1407.11.2.2 Limitations. Sections of MCM shall not 
exceed 300 square feet (27.9 m 2 ) in area and shall be sep- 
arated by a minimum of 4 feet (1219 mm) vertically. 

1407.12 Type V construction. MCM shall be permitted to be 
installed on buildings of Type V construction. 

1407.13 Foam plastic insulation. MCM systems containing 
foam plastic insulation shall also comply with the requirements 
of Section 2603. 

1407.14 Labeling. MCM shall be labeled in accordance with 
Section 1703.5. 



2273 and is required on framed walls of Type V construc- 
tion and Group Rl, R2, R3 and R4 occupancies. 

1408.4.1.1 Water-resistive barrier. For EIFS with 
drainage, the water-resistive barrier shall comply with 
Section 1404.2 or ASTM E 2570. 

1408.5 Installation. Installation of the EIFS and EIFS with 
drainage shall be in accordance with the EIFS manufacturer's 
instructions. 

1408.6 Special inspections. EIFS installations shall comply 
with the provisions of Sections 1704.1 and 1704.14. 



SECTION 1408 

EXTERIOR INSULATION AND FINISH SYSTEMS 

(EIFS) 

1408.1 General. The provisions of this section shall govern the 
materials, construction and quality of exterior insulation and 
finish systems (EIFS) for use as exterior wall coverings in addi- 
tion to other applicable requirements of Chapters 7, 14, 16, 17 
and 26. 

1408.2 Performance characteristics. EIFS shall be con- 
structed such that it meets the performance characteristics 
required in ASTM E 2568. 

1408.3 Structural design. The underlying structural framing 
and substrate shall be designed and constructed to resist loads 
as required by Chapter 16. 

1408.4 Weather resistance. EIFS shall comply with Section 
1403 and shall be designed and constructed to resist wind and 
rain in accordance with this section and the manufacturer's 
application instructions. 

1408.4.1 EIFS with drainage. EIFS with drainage shall 
have an average minimum drainage efficiency of 90 percent 
when tested in accordance the requirements of ASTM E 



2009 INTERNATIONAL BUILDING CODE® 



285 



286 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 15 
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



SECTION 1501 
GENERAL 

1501.1 Scope. The provisions of this chapter shall govern the 
design, materials, construction and quality of roof assemblies, 
and rooftop structures. 



SECTION 1502 
DEFINITIONS 

1502.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

AGGREGATE. In roofing, crushed stone, crushed slag or 
water-worn gravel used for surfacing for roof coverings. 

BALLAST. In roofing, ballast comes in the form of large 
stones or paver systems or light-weight interlocking paver sys- 
tems and is used to provide uplift resistance for roofing systems 
that are not adhered or mechanically attached to the roof deck. 

BUILT-UP ROOF COVERING. Two or more layers of felt 
cemented together and surfaced with a cap sheet, mineral 
aggregate, smooth coating or similar surfacing material. 

INTERLAYMENT. A layer of felt or nonbituminous satu- 
rated felt not less than 18 inches (457 mm) wide, shingled 
between each course of a wood-shake roof covering. 

MECHANICAL EQUIPMENT SCREEN. A partially 
enclosed rooftop structure used to aesthetically conceal heat- 
ing' ventilating and air conditioning (HVAC) electrical or 
mechanical equipment from view. 

METAL ROOF PANEL. An interlocking metal sheet having 
a minimum installed weather exposure of 3 square feet (0.279 
m 2 ) per sheet. 

METAL ROOF SHINGLE. An interlocking metal sheet hav- 
ing an installed weather exposure less than 3 square feet (0.279 
m 2 ) per sheet. 

MODIFIED BITUMEN ROOF COVERING. One or more 
layers of polymer-modified asphalt sheets. The sheet materials 
shall be fully adhered or mechanically attached to the substrate 
or held in place with an approvedbaUast layer. 

PENTHOUSE. An enclosed, unoccupied structure above the 
roof of a building, other than a tank, tower, spire, dome cupola 
or bulkhead. 

POSITIVE ROOF DRAINAGE. The drainage condition in 
which consideration has been made for all loading deflections 
of the roof deck, and additional slope has been provided to 
ensure drainage of the roof within 48 hours of precipitation. 



REROOFING. The process of recovering or replacing an 
existing roof covering. See "Roof recover" and "Roof replace- 
ment." 

ROOF ASSEMBLY. A system designed to provide weather 
protection and resistance to design loads. The system consists 
of a roof covering and roof deck or a single component serving 
as both the roof covering and the roof deck. A roof assembly 
includes the roof deck, vapor retarder, substrate or thermal bar- 
rier, insulation, vapor retarder and roof covering. 

The definition of "Roof assembly" is limited in application 
to the provisions of Chapter 15. 

ROOF COVERING. The covering applied to the roof deck 
for weather resistance, fire classification or appearance. 

ROOF COVERING SYSTEM. See Roof assembly. 

ROOF DECK. The flat or sloped surface not including its sup- 
porting members or vertical supports. 

ROOF RECOVER. The process of installing an additional 
roof covering over a prepared existing roof covering without 
removing the existing roof covering. 

ROOF REPAIR. Reconstruction or renewal of any part of an 
existing roof for the purposes of its maintenance. 

ROOF REPLACEMENT. The process of removing the exist- 
ing roof covering, repairing any damaged substrate and install- 
ing a new roof covering. 

ROOF VENTILATION. The natural or mechanical process 
of supplying conditioned or unconditioned air to, or removing 
such air from, attics, cathedral ceilings or other enclosed spaces 
over which a roof assembly is installed. 

ROOFTOP STRUCTURE. An enclosed structure on or 
above the roof of any part of a building. 

SCUPPER. An opening in a wall or parapet that allows water 
to drain from a roof. 

SINGLE-PLY MEMBRANE. A roofing membrane that is 
field applied using one layer of membrane material (either 
homogeneous or composite) rather than multiple layers. 

UNDERLAYMENT. One or more layers of felt, sheathing 
paper, nonbituminous saturated felt or other approv edmaimal 
over which a steep-slope roof covering is applied. 



SECTION 1503 
WEATHER PROTECTION 

1503.1 General. Roof decks shall be covered with approved 
roof coverings secured to the building or structure in accor- 
dance with the provisions of this chapter. Roof coverings shall 
be designed and installed in accordance with this code and the 



2009 INTERNATIONAL BUILDING CODE® 



287 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



I approve d manufacturer's instructions such that the roof cover- 
ing shall serve to protect the building or structure. 

1503.2 Flashing. Flashing shall be installed in such a manner 
so as to prevent moisture entering the wall and roof through 
joints in copings, through moisture-permeable materials and at 
intersections with parapet walls and other penetrations through 
the roof plane. 

1503.2.1 Locations. Flashing shall be installed at wall and 
roof intersections, at gutters, wherever there is a change in 
roof slope or direction and around roof openings. Where 
flashing is of metal, the metal shall be corrosion resistant 
with a thickness of not less than 0.019 inch (0.483 mm) (No. 
26 galvanized sheet). 

1503.3 Coping. Parapet walls shall be properly coped with 
noncombustible, weatherproof materials of a width no less 
than the thickness of the parapet wall. 

[P] 1503.4 Roof drainage. Design and installation of roof 
drainage systems shall comply with Section 1503 and the 
International Plumbing Code. 

1503.4.1 Secondary drainage required. Secondary (emer- 
gency) roof drains or scuppers shall be provided where the 
roof perimeter construction extends above the roof in such a 
manner that water will be entrapped if the primary drains 
allow buildup for any reason. 

1503.4.2 Scuppers. When scuppers are used for secondary 
(emergency overflow) roof drainage, the quantity, size, 
location and inlet elevation of the scuppers shall be sized to 
prevent the depth of ponding water from exceeding that for 
which the roof was designed as determined by Section 
1503.4.1. Scuppers shall not have an opening dimension of 
less than 4 inches (102 mm) . The flow through the primary 
system shall not be considered when locating and sizing 
scuppers. 

1503.4.3 Gutters. Gutters and leaders placed on the outside 
of buildings, other than Group R-3, private garages and 
buildings of Type V construction, shall be of 
noncombustible material or a minimum of Schedule 40 
plastic pipe. 

1503.5 Roof ventilation. Intake and exhaust vents shall be pro- 
vided in accordance with Section 1203.2 and the manufac- 
turer's installation instructions. 

1503.6 Crickets and saddles. A cricket or saddle shall be 
installed on the ridge side of any chimney or penetration 
greater than 30 inches (762 mm) wide as measured perpendicu- 
lar to the slope. Cricket or saddle coverings shall be sheet metal 
or of the same material as the roof covering. 



SECTION 1504 
PERFORMANCE REQUIREMENTS 

1504.1 Wind resistance of roofs. Roof decks and roof cover- 
ings shall be designed for wind loads in accordance with Chap- 
ter 16 and Sections 1504.2, 1504.3 and 1504.4. 

11504.1.1 Wind resistance of asphalt shingles. Asphalt 
shingles shall comply with Section 1507.2.7. 



1504.2 Wind resistance of clay and concrete tile. Wind loads 
on clay and concrete tile roof coverings shall be in accordance 
with Section 1609.5. 

1504.3 Wind resistance of nonballasted roofs. Roof cover- 
ings installed on roofs in accordance with Section 1507 that are 
mechanically attached or adhered to the roof deck shall be 
designed to resist the design wind load pressures for compo- 
nents and cladding in accordance with Section 1609. 

1504.3.1 Other roof systems. Roof systems with built-up, 
modified bitumen, fully adhered or mechanically attached 
single-ply through fastened metal panel roof systems, and 
other types of membrane roof coverings shall also be tested 
in accordance with FM 4474, UL 580 or UL 1897. 

1504.3.2 Metal panel roof systems. Metal panel roof sys- 
tems through fastened or standing seam shall be tested in 
accordance with UL 580 or ASTM E 1592. 

Exception: Metal roofs constructed of cold-formed 
steel, where the roof deck acts as the roof covering and 
provides both weather protection and support for struc- 
turalloads, shall be permitted to be designed and tested 
in accordance with the applicable referenced structural 
design standard in Section 2209.1. 

1504.4 Ballasted low-slope roof systems. Ballasted low-slope 
(roof slope < 2: 12) single-ply roof system coverings installed 
in accordance with Sections 1507.12 and 1507.13 shall be 
designed in accordance with Section 1504.8 and ANSI/SPRI 
RP-4. 

1504.5 Edge securement for low-slope roofs. Low-slope 
membrane roof system metal edge securement, except gutters, 
shall be designed and installed for wind loads in accordance 
with Chapter 16 and tested for resistance in accordance with 
ANSI/SPRI ES-1, except the basic wind speed shall be deter- 
mined from Figure 1609. 

1504.6 Physical properties. Roof coverings installed on 
low-slope roofs (roof slope < 2: 12) in accordance with Section 
1507 shall demonstrate physical integrity over the working life 
of the roof based upon 2,000 hours of exposure to accelerated 
weathering tests conducted in accordance with ASTM G 152, 
ASTM G 155 or ASTM G 154. Those roof coverings that are 
subject to cyclical flexural response due to wind loads shall not 
demonstrate any significant loss of tensile strength for 
unreinforced membranes or breaking strength for reinforced 
membranes when tested as herein required. 

1504.7 Impact resistance. Roof coverings installed on 
low-slope roofs (roof slope < 2: 12) in accordance with Section 
1507 shall resist impact damage based on the results of tests 
conducted in accordance with ASTM D 3746, ASTM D 4272, 
CGSB 37-GP-52M or the "Resistance to Foot Traffic Test" in 
Section 5.5 ofFM 4470. 

1504.8 Aggregate. Aggregate used as surfacing for roof cover- 
ings and aggregate, gravel or stone used as ballast shall not be 
used on the roof of a building located in a hurricane-prone 
region as defined in Section 1609.2, or on any other building 
with a mean roof height exceeding that permitted by Table 
1504.8 based on the exposure category and basic wind speed at 
the site. 



288 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



TABLE 1504.8 

MAXIMUM ALLOWABLE MEAN ROOF HEIGHT PERMITTED FOR 

BUILDINGS WITH AGGREGATE ON THE ROOF IN AREAS 

OUTSIDE A HURRICANE-PRONE REGION 



BASIC WIND SPEED 

FROM FIGURE 1609 

(mph)b 


MAXIMUM MEAN ROOF HEIGHT (ft)a, c 


Exposure category 


B 


c 


D 


85 


170 


60 


30 


90 


110 


35 


15 


95 


75 


20 


NP 


100 


55 


15 


NP 


105 


40 


NP 


NP 


110 


30 


NP 


NP 


115 


20 


NP 


NP 


120 


15 


NP 


NP 


Greater than 120 


NP 


NP 


NP 



I 



For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. 

a. Mean roof height as defined in ASCE 7. 

b. For intermediate values of basic wind speed, the height associated with the 
next higher value of wind speed shall be used, or direct interpolation is per- 
mitted. 

c. NP = gravel and stone not permitted for any roof height. 



SECTION 1505 
FIRE CLASSIFICATION 

1505.1 General. Roof assemblies shall be divided into the 
classes defined below. Class A, Band C roof assemblies and 
roof coverings required to be listed by this section shall be 
tested in accordance with ASTM E 108 or UL 790. In addition, 
fire-retardant-treated wood roof coverings shall be tested in 
accordance with ASTM D 2898. The minimum roof coverings 
installed on buildings shall comply with Table 1505.1 based on 
the type of construction of the building. 

Exception: Skylights and sloped glazing that comply with 
Chapter 24 or Section 2610. 

TABLE 1505.1 a ,b 

MINIMUM ROOF COVERING CLASSIFICATION 

FOR TYPES OF CONSTRUCTION 



IA 


IB 


IIA 


IIB 


IIIA 


IIIB 


IV 


VA 


VB 


B 


B 


B 


C c 


B 


C c 


B 


B 


C c 



For SI : 1 foot = 304 .8 mm, 1 square foot = 0.0929 m 2 - 

a. Unless otherwise required in accordance with the International 
Wildland-Urban Interface Code or due to the location of the building within 
a fire district in accordance with Appendix D. 

b. Nonclassified roof coverings shall be permitted on buildings of Group R-3 
and Group U occupancies, where there is a minimum fire-separation dis- 
tance of 6 feet measured from the leading edge of the roof. 

c. Buildings that are not more than two stories above grade plane and having 
not more than 6,000 square feet of projected roof area and where there is a 
minimum 10-foot fire- separation distance from the leading edge of the roof 
to a lot line on all sides of the building, except for street fronts or public ways , 
shall be permitted to have roofs of No. 1 cedar or redwood shakes and No. 1 
shingles. 

1505.2 Class A roof assemblies. Class A roof assemblies are 
those that are effective against severe fire test exposure. Class 
A roof assemblies and roof coverings shall be listedand identi- 
fied as Class A by an approved testing agency. Class A roof 



assemblies shall be permitted for use in buildings or structures 
of all types of construction. 

Exceptions: 

1. Class A roof assemblies include those with coverings 
of brick, masonry or an exposed concrete roof deck. 

2. Class A roof assemblies also include ferrous or cop- 
per shingles or sheets, metal sheets and shingles, clay 
or concrete roof tile or slate installed on noncombusti- 
ble decks or ferrous, copper or metal sheets installed 
without a roof deck on noncombustible framing. 

1505.3 Class B roof assemblies. Class B roof assemblies are 
those that are effective against moderate fire-test exposure. 
Class B roof assemblies and roof coverings shall be listed and 
identified as Class B by an approved testing agency. 

1505.4 Class C roof assemblies. Class C roof assemblies are 
those that are effective against light fire-test exposure. Class C 
roof assemblies and roof coverings shall be listed and identi- 
fied as Class C by an approved testing agency. 

1505.5 Nonclassified roofing. Nonclassified roofing is 
approved material that is not listed as a Class A, B or C roof 
covering. 

1505.6 Fire-retardant-treated wood shingles and shakes. 
Fire-retardant-treated wood shakes and shingles shall be 
treated by impregnation with chemicals by the full-cell vac- 
uum-pressure process, in accordance with AWPA CI. Each 
bundle shall be marked to identify the manufactured unit and 
the manufacturer, and shall also be labeled to identify the clas- 
sification of the material in accordance with the testing 
required in Section 1505.1, the treating company and the qual- 
ity control agency. 

1505.7 Special purpose roofs. Special purpose wood shingle 
or wood shake roofing shall conform with the grading and 
application requirements of Section 1507.8 or 1507.9. In addi- 
tion, an underlayment of sis-inch (15.9 mm) Type X 
water-resistant gypsum backing board or gypsum sheathing 
shall be placed under minimum nominal 1/^inch-thick (12.7 
mm) wood structural panel solid sheathing or I-inch (25 mm) 
nominal spaced sheathing. 



SECTION 1506 
MATERIALS 

1506.1 Scope. The requirements set forth in this section shall 
apply to the application of roof-covering materials specified 
herein. Roof coverings shall be applied in accordance with this 
chapter and the manufacturer's installation instructions. Instal- 
lation of roof coverings shall comply with the applicable provi- 
sions of Section 1507. 

1506.2 Compatibility of materials. Roofs and roof coverings 
shall be of materials that are compatible with each other and 
with the building or structure to which the materials are 
applied. 

1506.3 Material specifications and physical characteristics. 
Roof-covering materials shall conform to the applicable stan- 
dards listed in this chapter. In the absence of applicable stan- 
dards or where materials are of questionable suitability, testing 



I 



2009 INTERNATIONAL BUILDING CODE® 



289 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



by an approved agency shall be required by the building code 
official to determine the character, quality and limitations of 
application of the materials. 

1506.4 Product identification. Roof-covering materials shall 
be delivered in packages bearing the manufacturer's identify- 
ing marks and approved testing agency labels required in 
accordance with Section 1505. Bulk shipments of materials 
shall be accompanied with the same information issued in the 
form of a certificate or on a bill of lading by the manufacturer. 



SECTION 1507 
REQUIREMENTS FOR ROOF COVERINGS 

1507.1 Scope. Roof coverings shall be applied in accordance 
with the applicable provisions of this section and the manufac- 
turer's installation instructions. 

1507.2 Asphalt shingles. The installation of asphalt shingles 
shall comply with the provisions of this section. 

1507.2.1 Deck requirements. Asphalt shingles shall be fas- 
tened to solidly sheathed decks. 

1507.2.2 Slope. Asphalt shingles shall only be used on roof 
slopes of two units vertical in 12 units horizontal (17 -per- 
cent slope) or greater. For roof slopes from two units vertical 
in 12 units horizontal (17 -percent slope) up to four units ver- 
tical in 12 units horizontal (33-percent slope), double 
underlayment application is required in accordance with 
Section 1507.2.8. 

1507.2.3 Underlayment. Unless otherwise noted, required 
underlayment shall conform to ASTM D 226, Type I, 
ASTM D 4869, Type I, or ASTM D 6757. 

1507.2.4 Self- adhering polymer modified bitumen sheet. 
Self- adhering polymer modified bitumen sheet shall com- 
ply with ASTM D 1970. 

1507.2.5 Asphalt shingles. Asphalt shingles shall comply 
with ASTM D 225 or ASTM D 3462. 

1507.2.6 Fasteners. Fasteners for asphalt shingles shall be 
galvanized, stainless steel, aluminum or copper roofing 
nails, minimum 12 gage [0.105 inch (2.67 mm)] shank with 
a minimum 3/ 8 inch-diameter (9.5 mm) head, of a length to 
penetrate through the roofing materials and a minimum of 
3/ 4 inch (19.1 mm) into the roof sheathing. Where the roof 
sheathing is less than 3/4 inch (19.1 mm) thick, the nails shall 
penetrate through the sheathing. Fasteners shall comply 
with ASTM F 1667. 

1507.2.7 Attachment. Asphalt shingles shall have the min- 
imum number of fasteners required by the manufacturer, but 
not less than four fasteners per strip shingle or two fasteners 
per individual shingle. Where the roof slope exceeds 21 
units vertical in 12 units horizontal (21: 12), shingles shall be 
installed as required by the manufacturer. 

1507.2.7.1 Wind resistance. Asphalt shingles shall be 
tested in accordance with ASTM D 7158. Asphalt shin- 
gles shall meet the classification requirements of Table 
1507.2.7.1 (1) for the appropriate maximum basic wind 
speed. Asphalt shingle packaging shall bear a label to 



indicate compliance with ASTM D 7158 and the 
required classification in Table 1507.2.7.1(1). 

Exception: Asphalt shingles not included in the 
scope of ASTM D 7158 shall be tested and labeled to 
indicate compliance with ASTM D 3161 and the 
required classification in Table 1507.2.7.1(2). 

TABLE 1507.2.7.1(1) 

CLASSIFICATION OF ASPHALT ROOF SHINGLES 

PER ASTM D7158 3 



MAXIMUM BASIC WIND SPEED 
FROM FIGURE 1609 


CLASSIFICATION 
REQUIREMENT 


85 


D, GorH 


90 


D, GorH 


100 


GorH 


110 


GorH 


120 


GorH 


130 


H 


140 


H 


150 


H 



a. The standard calculations contained in ASTM D 7158 assume exposure cat- 
egory B or C and building height of 60 feet (18 288 mm) or less. Additional 
calculations are required for conditions outside of these assumptions. 

TABLE 1507.2.7.1(2) 
CLASSIFICATION OF ASPHALT SHINGLES PER ASTM D 3161 



MAXIMUM BASIC WIND SPEED 
FROM FIGURE 1609 


CLASSIFICATION 
REQUIREMENT 


85 


A, D or F 


90 


A, D or F 


100 


A, D or F 


110 


F 


120 


F 


130 


F 


140 


F 


150 


F 



1507.2.8 Underlayment application. For roof slopes from 
two units vertical in 12 units horizontal (17 -percent slope) 
and up to four units vertical in 12 units horizontal (3 3 -per- 
cent slope), underlayment shall be two layers applied in the 
following manner. Apply a minimum 19-inch- wide (483 
mm) strip of underlayment felt parallel with and starting at 
the eaves, fastened sufficiently to hold in place. Starting at 
the eave, apply 3 6-inch- wide (914 mm) sheets of 
underlayment overlapping successive sheets 19 inches (483 
mm), by fastened sufficiently to hold in place. Distortions in 
the underlayment shall not interfere with the ability of the 
shingles to seal. For roof slopes of four units vertical in 12 
units horizontal (3 3 -percent slope) or greater, underlayment 
shall be one layer applied in the following manner. 
Underlayment shall be applied shingle fashion, parallel to 
and starting from the eave and lapped 2 inches (51 mm), fas- 
tened sufficiently to hold in place. Distortions in the 



290 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



underlayment shall not interfere with the ability of the shin- 
gles to seal. 

1507.2.8.1 High wind attachment. Underlayment 
applied in areas subject to high winds (greater than 110 
mph in accordance with Figure 1609) shall be applied 
with corrosion-resistant fasteners in accordance with the 
manufacturer's instructions. Fasteners are to be applied 
along the overlap at a maximum spacing of 36 inches 
(914 mm) on center. 

1507.2.8.2 Ice barrier. In areas where there has been a 
history of ice forming along the eaves causing a backup 
of water, an ice barrier that consists of at least two layers 
of underlayment cemented together or of a self-adhering 
polymer modified bitumen sheet shall be used in lieu of 
normal underlayment and extend from the lowest edges 
of all roof surfaces to a point at least 24 inches (610 mm) 
inside the exterior wa//line of the building. 

Exception: Detached accessory structures that con- 
tain no conditioned floor area. 

1507.2.9 Flashings. Flashing for asphalt shingles shall 
comply with this section. Flashing shall be applied in accor- 
dance with this section and the asphalt shingle manufac- 
turer's printed instructions. 

1507.2.9.1 Base and cap flashing. Base and cap flash- 
ing shall be installed in accordance with the manufac- 
turer's instructions. Base flashing shall be of either 
corrosion-resistant metal of minimum nominal 
0.019-inch (0.483 mm) thickness or mineral- surfaced 
roll roofing weighing a minimum of 77 pounds per 100 
square feet (3.76 kg/m 2 ). Cap flashing shall be corro- 
sion-resistant metal of minimum nominal 0.019-inch 
(0.483 mm) thickness. 

1507.2.9.2 Valleys. Valley linings shall be installed in 
accordance with the manufacturer's instructions before 



applying shingles. Valley linings of the following types 
shall be permitted: 

1. For open valleys (valley lining exposed) lined with 
metal, the valley lining shall be at least 24 inches 
(610 mm) wide and of any of the corrosion-resis- 
tant metals in Table 1507.2.9.2. 

2. For open valleys, valley lining of two plies of min- 
eral-surfaced roll roofing complying with ASTM 
D 3909 or ASTM D 6380 shall be permitted. The 
bottom layer shall be 18 inches (457 mm) and the 
top layer a minimum of 36 inches (914 mm) wide. 

3. For closed valleys (valleys covered with shingles), 
valley lining of one ply of smooth roll roofing 
complying with ASTM D 6380, and at least 36 
inches (914 mm) wide or types as described in 
Item 1 or 2 above shall be permitted. Self- adhering 
polymer modified bitumen underlayment comply- 
ing with ASTM D 1970 shall be permitted in lieu 
of the lining material. 

1507.2.9.3 Drip edge. Provide drip edge at eaves and 
gables of shingle roofs. Overlap to be a minimum of 2 
inches (51 mm). Eave drip edges shall extend i/ 4 inch (6.4 
mm) below sheathing and extend back on the roof a mini- 
mum of 2 inches (51 mm). Drip edge shall be mechani- 
cally fastened a maximum of 12 inches (305 mm) o.c. 

1507.3 Clay and concrete tile. The installation of clay and 
concrete tile shall comply with the provisions of this section. 

1507.3.1 Deck requirements. Concrete and clay tile shall 
be installed only over solid sheathing or spaced structural 
sheathing boards. 

1507.3.2 Deck slope. Clay and concrete roof tile shall be 
installed on roof slopes of 2^ units vertical in 12 units hori- 
zontal (21 -percent slope) or greater. For roof slopes from 



TABLE 1507.2.9.2 
VALLEY LINING MATERIAL 



MATERIAL 


MINIMUM THICKNESS 


GAGE 


WEIGHT 


Aluminum 


0.024 in. 


- 


- 


Cold-rolled copper 


0.0216 in. 




ASTM B 370, 16 oz. per square ft. 


Copper 






160z 


Galvanized steel 


0.0179 in. 


26 (zinc-coated G90) 




High-yield copper 


0.0162 in. 


- 


ASTM B 370, 12 oz. per square ft. 


Lead 


- 


- 


2.5 pounds 


Lead-coated copper 


0.0216 in. 


- 


ASTM BIOI, 16 oz. per square ft. 


Lead-coated high-yield copper 


0.0162 in. 




ASTM B 101, 12 oz. per square ft. 


Painted terne 






20 pounds 


Stainless steel 


- 


28 


- 


Zinc alloy 


0.027 in. 


- 


- 



For 51: 1 inch = 25.4 mm, 1 pound = 0.454 kg, 1 ounce = 28.35 g, 1 square foot = 0.093m 2 . 



2009 INTERNATIONAL BUILDING CODE® 



291 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



2 V 2 units vertical in 12 units horizontal (21 -percent slope) to 
four units vertical in 12 units horizontal (33-percent slope), 
double underlayment application is required in accordance 
with Section 1507.3.3. 

1507.3.3 Underlayment. Unless otherwise noted, required 
underlayment shall conform to: ASTM D 226, Type II; 
ASTM D 2626 or ASTM D 6380, Class M mineral- surfaced 
roll roofing. 

1507.3.3.1 Low-slope roofs. For roof slopes from 2V 2 
units vertical in 12 units horizontal (21 -percent slope), 
up to four units vertical in 12 units horizontal (3 3 -percent 
slope), underlayment shall be a minimum of two layers 
applied as follows: 

1. Starting at the eave, a 19-inch (483 mm) strip of 
underlayment shall be applied parallel with the 
eave and fastened sufficiently in place. 

2. Starting at the eave, 36-inch- wide (914 mm) strips 
of underlayment felt shall be applied overlapping 
successive sheets 19 inches (483 mm) and fas- 
tened sufficiently in place. 

1507.3.3.2 High-slope roofs. For roof slopes of four 
units vertical in 12 units horizontal (33-percent slope) or 
greater, underlayment shall be a minimum of one layer of 
underlayment felt applied shingle fashion, parallel to, 
and starting from the eaves and lapped 2 inches (51 mm), 
fastened only as necessary to hold in place. 

1507.3.4 Clay tile. Clay roof tile shall comply with ASTM 
C 1167. 

1507.3.5 Concrete tile. Concrete roof tile shall comply 
with ASTM C 1492. 

1507.3.6 Fasteners. Tile fasteners shall be corrosion resis- 
tant and not less than 11 gage, 5/ 16 -inch (8.0 mm) head, and 
of sufficient length to penetrate the deck a minimum of 3/ 4 
inch (19.1 mm) or through the thickness of the deck, which- 
ever is less. Attaching wire for clay or concrete tile shall not 
be smaller than 0.083 inch (2.1 mm). Perimeter fastening 
areas include three tile courses but not less than 36 inches 
(914 mm) from either side of hips or ridges and edges of 
eaves and gable rakes. 

1507.3.7 Attachment. Clay and concrete roof tiles shall be 
fastened in accordance with Table 1507.3.7. 

1507.3.8 Application. Tile shall be applied according to the 
manufacturer's installation instructions, based on the fol- 
lowing: 

1. Climatic conditions. 

2. Roof slope. 

3. Underlayment system. 

4. Type of tile being installed. 



1507.3.9 Flashing. At the juncture of the roof vertical sur- 
faces, flashing and counterflashing shall be provided in 
accordance with the manufacturer's installation instruc- 
tions, and where of metal, shall not be less than 0.019-inch 
(0.48 mm) (No. 26 galvanized sheet gage) corrosion-resis- 
tant metal. The valley flashing shall extend at least 11 inches 
(279 mm) from the centerline each way and have a splash 
diverter rib not less than 1 inch (25 mm) high at the flow line 
formed as part of the flashing. Sections of flashing shall 
have an end lap of not less than 4 inches (102 mm). For roof 
slopes of three units vertical in 12 units horizontal (25-per- 
cent slope) and over, the valley flashing shall have a 
36-inch- wide (914 mm) underlayment of either one layer of 
Type I underlayment running the full length of the valley, or 
a self- adhering polymer- modified bitumen sheet complying 
with ASTM D 1970, in addition to other required 
underlayment. In areas where the average daily temperature 
in January is 25°F (-4°C) or less or where there is a possibil- 
ity of ice forming along the eaves causing a backup of water, 
the metal valley flashing underlayment shall be solid 
cemented to the roofing underlayment for slopes under 
seven units vertical in 12 units horizontal (58-percent slope) 
or self-adhering polymer-modified bitumen sheet shall be 
installed. 

1507.4 Metal roof panels. The installation of metal roof pan- 
els shall comply with the provisions of this section. 

1507.4.1 Deck requirements. Metal roof pan el roof cover- 
ings shall be applied to a solid or closely fitted deck, except 
where the roof covering is specifically designed to be 
applied to spaced supports. 

1507.4.2 Deck slope. Minimum slopes for metal roof pan- 
els shall comply with the following: 

1. The minimum slope for lapped, nonsoldered seam 
metal roofs without applied lap sealant shall be three 
units vertical in 12 units horizontal (25-percent 
slope). 

2. The minimum slope for lapped, nonsoldered seam 
metal roofs with applied lap sealant shall be one-half 
unit vertical in 12 units horizontal (4-percent slope). 
Lap sealants shall be applied in accordance with the 
approve d manufacturer's installation instructions. 

3. The minimum slope for standing seam of roof sys- 
tems shall be one-quarter unit vertical in 12 units hori- 
zontal (2-percent slope). 

1507.4.3 Material standards. Metal-sheet roof covering 
systems that incorporate supporting structural members 
shall be designed in accordance with Chapter 22. 
Metal-sheet roof coverings installed over structural decking 
shall comply with Table 1507.4.3(1). The materials used for 
metal-sheet roof coverings shall be naturally corrosion 
resistant or provided with corrosion resistance in accor- 
dance with the standards and minimum thicknesses shown 
in Table 1507.4.3(2). 



292 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 







TABLE 1507.3.7 
CLAY AND CONCRETE TILE ATTACHMENTa,b,c 




GENERAL - CLAY OR CONCRETE ROOF TILE 


Maximum basic 

wind speed 

(mph) 


Mean roof 
height 
(feet) 


Roof slope up to < 3:12 


Roof slope 3: 12 and over 


85 


0-60 


One fastener per tile. Flat tile 
without vertical laps, two 
fasteners per tile. 


Two fasteners per tile. Only one fastener on slopes of 7: 12 and 
less for tiles with installed weight exceeding 7.5Ibs.lsq. ft. 
having a width no greater than 16 inches. 


100 


0-40 


100 


> 40-60 


The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved 
clips. All rake tiles shall be nailed with two nails. The nose of all ridge, hip and rake tiles shall be 
set in a bead of roofer's mastic. 


110 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


120 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


130 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


All 


>60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS d ,e 
(Installations on spaced/solid sheathing with battens or spaced sheathing) 


Maximum basic 

wind speed 

(mph) 


Mean roof 
height 
(feet) 


Roof slope up to < 5:12 


Roof slope 5:12 < 12:12 


Roof slope 12:12 and over 


85 


0-60 


Fasteners are not required. Tiles 
with installed weight less than 9 
lbs.lsq. ft. require a minimum of 
one fastener per tile. 


One fastener per tile every other 
row. All perimeter tiles require 
one fastener. Tiles with installed 
weight less than 9Ibs./sq. ft. 
require a minimum of one 
fastener per tile. 


One fastener required for 
every tile. Tiles with installed 
weight less than 9 lbs.lsq. ft. 
require a minimum of one 
fastener per tile. 


100 


0-40 


100 


> 40-60 


The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved 
clips. All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be 
set in a bead of roofers's mastic. 


110 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


120 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


130 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


All 


>60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


INTERLOCKING CLAY OR CONCRETE ROOF TILE WITH PROJECTING ANCHOR LUGS 
(Installations on solid sheathing without battens) 


Maximum basic 

wind speed 

(mph) 


Mean roof 
height 
(feet) 


All roof slopes 


85 


0-60 


One fastener per tile. 


100 


0-40 


One fastener per tile. 


100 


> 40-60 


The head of all tiles shall be nailed. The nose of all eave tiles shall be fastened with approved 
clips . All rake tiles shall be nailed with two nails The nose of all ridge, hip and rake tiles shall be 
set in a bead of roofer's mastic. 


110 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


120 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


130 


0-60 


The fastening system shall resist the wind forces in Section 1609.5.3. 


All 


>60 


The fastening system shall resist the wind forces in Section 1609.5.3. 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 mis, 1 pound per square foot = 4.882kg /m z. 

a. Minimum fastener size. Corrosion-resistant nails not less than No. 11 gage with 5/ 16 -inch head. Fasteners shall be long enough to penetrate into the sheathing 3/ 4 
inch or through the thickness of the sheathing, whichever is less. Attaching wire for clay and concrete tile shall not be smaller than 0.083 inch. 

b. Snow areas. A minimum of two fasteners per tile are required or battens and one fastener. 

c. Roof slopes greater than 24:12. The nose of all tiles shall be securely fastened. 

d. Horizontal battens. Battens shall be not less than 1 inch by 2 inch nominal. Provisions shall be made for drainage by a minimum of lis-inch riser at each nail or by 
4-foot-Iong battens with at least a liz-inch separation between battens. Horizontal battens are required for slopes over 7:12. 

e. Perimeter fastening areas include three tile courses but not less than 36 inches from either side of hips or ridges and edges of eaves and gable rakes. 



2009 INTERNATIONAL BUILDING CODE® 



293 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



TABLE 1507.4.3(1) 
METAL ROOF COVERINGS 



ROOF COVERING TYPE 


STANDARD APPLICATION 
RATE/THICKNESS 


Aluminum 


ASTM B 209, 0.024 inch minimum 
thickness for roll-formed panels and 0.019 
inch minimum thickness for press-formed 
shingles. 


Aluminum-zinc alloy 
coated steel 


ASTM A 792 AZ 50 


Cold-rolled copper 


ASTM B 370 minimum 16 oz./sq. ft. and 

12 oz./sq. ft. high yield copper for 

metal-sheet roof covering systems: 

12 oz/sq. ft. for preformed metal shingle 

systems. 


Copper 


16 oz./sq. ft. for metal-sheet roof-covering 
systems; 12 oz./sq. ft. for preformed metal 
shingle systems. 


Galvanized steel 


ASTM A 653 G-90 zinc-coated a . 


Hard lead 


2 lbs./sq. ft. 


Lead-coated copper 


ASTM BIOI 


Prepainted steel 


ASTM A 755 


Soft lead 


3 lbs./sq. ft. 


Stainless steel 


ASTM A 240, 300 Series Alloys 


Steel 


ASTM A 924 


Terne and 
terne-coated stainless 


Terne coating of 40 lbs. per double base 
box, field painted where applicable in 
accordance with manufacturer's 
installation instructions. 


Zinc 


0.027 inch minimum thickness; 99.995% 
electrolytic high grade zinc with alloy 
additives of copper (0.08% - 0.20%), 
titanium (0.07% - 0.12%) and aluminum 
(0.015%). 



For SI: 1 ounce per square foot = 0.0026 kg/m 2 , 

1 pound per square foot = 4.882 kg/m 2 , 

1 inch = 25.4 mm, 1 pound = 0.454 kg. 
a. For Group U buildings, the minimum coating thickness for ASTM A 653 
galvanized steel roofing shall be G-60. 



TABLE 1507.4.3(2) 
MINIMUM CORROSION RESISTANCE 



55% Aluminum-zinc alloy coated steel 


ASTM A 792 AZ 50 


5% Aluminum alloy-coated steel 


ASTM A 875 GF60 


Aluminum-coated steel 


ASTM A 463 T2 65 


Galvanized steel 


ASTM A 653 G-90 


Prepainted steel 


ASTM A 755 a 



a. Paint systems in accordance with ASTM A 755 shall be applied over steel 
products with corrosion resistant coatings complying with ASTM A 792, 
ASTM A 875, ASTM A 463 or ASTM A 653 . 



1507.4.4 Attachment. Metal roof panels shall be secured to 
the supports in accordance with the approved manufac- 
turer's fasteners. In the absence of manufacturer recommen- 
dations, the following fasteners shall be used: 

1. Galvanized fasteners shall be used for steel roofs. 

2. Copper, brass, bronze, copper alloy or 300 series 
stainless-steel fasteners shall be used for copper 
roofs. 

3. Stainless-steel fasteners are acceptable for all types of 
metal roofs. 

1507.5 Metal roof shingles. The installation of metal roof 
shingles shall comply with the provisions of this section. 

1507.5.1 Deck requirements. Metal roof shingles shall be 
applied to a solid or closely fitted deck, except where the 
roof covering is specifically designed to be applied to 
spaced sheathing. 

1507.5.2 Deck slope. Metal roof shingles shall not be 
installed on roof slopes below three units vertical in 12 units 
horizontal (25-percent slope). 

1507.5.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869. 

1507.5.4 Ice barrier. In areas where there has been a history 
of ice forming along the eaves causing a backup of water, an 
ice barrier that consists of at least two layers of 
underlayment cemented together or of a self- adhering poly- 
mer-modified bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all roof 
surfaces to a point at least 24 inches (610 mm) inside the 
exterior wall line of the building. 

Exception: Detached accessory structures that contain 
no conditioned floor area. 

1507.5.5 Material standards. Metal roof shingle roof cov- 
erings shall comply with Table 1507.4.3(1). The materials 
used for metal-roof shingle roof coverings shall be naturally 
corrosion resistant or provided with corrosion resistance in 
accordance with the standards and minimum thicknesses 
specified in the standards listed in Table 1507.4.3(2). 

1507.5.6 Attachment. Metal roof shingles shall be secured 
to the roof in accordance with the approve d manufacturer's 
installation instructions. 

1507.5.7 Flashing. Roof valley flashing shall be of corro- 
sion-resistant metal of the same material as the roof cover- 
ing or shall comply with the standards in Table 1507.4.3(1). 
The valley flashing shall extend at least 8 inches (203 mm) 
from the centerline each way and shall have a splash diverter 
rib not less than 3/ 4 inch (19.1 mm) high at the flow line 
formed as part of the flashing. Sections of flashing shall 
have an end lap of not less than 4 inches (102 mm). In areas 
where the average daily temperature in January is 25 °F 
(-4°C) or less or where there is a possibility of ice forming 
along the eaves causing a backup of water, the metal valley 
flashing shall have a 3 6-inch- wide (914 mm) underlayment 
directly under it consisting of either one layer of 
underlayment running the full length of the valley or a 
self-adhering polymer-modified bitumen sheet complying 
with ASTM D 1970, in addition to underlayment required 



294 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



for metal roof shingles. The metal valley flashing 
underlayment shall be solidly cemented to the roofing 
underlayment for roof slopes under seven units vertical in 
12 units horizontal (58-percent slope) or self- adhering poly- 
mer-modified bitumen sheet shall be installed. 

1507.6 Mineral- surfaced roll roofing. The installation of 
mineral- surfaced roll roofing shall comply with this section. 

1507.6.1 Deck requirements. Mineral- surfaced roll roof- 
ing shall be fastened to solidly sheathed roofs. 

1507.6.2 Deck slope. Mineral- surfaced roll roofing shall 
not be applied on roof slopes below one unit vertical in 12 
units horizontal (8-percent slope). 

1507.6.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869. 

1507.6.4 Ice barrier. In areas where there has been a history 
of ice forming along the eaves causing a backup of water, an 
ice barrier that consists of at least two layers of 
underlayment cemented together or of a self- adhering poly- 
mer-modified bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all roof 
surfaces to a point at least 24 inches (610 mm) inside the 
exterior wall line of the building. 

Exception: Detached accessory structures that contain 
no conditioned floor area. 

1507.6.5 Material standards. Mineral- surfaced roll roof- 
ing shall conform to ASTM D 3909 or ASTM D 6380. 

1507.7 Slate shingles. The installation of slate shingles shall 
comply with the provisions of this section. 

1507.7.1 Deck requirements. Slate shingles shall be fas- 
tened to solidly sheathed roofs. 

1507.7.2 Deck slope. Slate shingles shall only be used on 
slopes of four units vertical in 12 units horizontal (4: 12) or 
greater. 

1507.7.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869. 

1507.7.4 Ice barrier. In areas where the average daily tem- 
perature in January is 25 °F (-4°C) or less or where there is a 
possibility of ice forming along the eaves causing a backup 
of water, an ice barrier that consists of at least two layers of 
underlayment cemented together or of a self- adhering poly- 
mer-modified bitumen sheet shall extend from the lowest 
edges of all roof surfaces to a point at least 24 inches (610 
mm) inside the exterior wall line of the building. 

Exception: Detached accessory structures that contain 
no conditioned floor area. 

1507.7.5 Material standards. Slate shingles shall comply 
with ASTM C 406. 



1507.7.6 Application. Minimum headlap for slate shingles 
shall be in accordance with Table 1507.7.6. Slate shingles 
shall be secured to the roof with two fasteners per slate. 



TABLE 1507.7.6 
SLATE SHINGLE HEADLAP 



SLOPE 


HEADLAP 

(inches) 


4:12 < slope < 8:12 


4 


8:12 < slope < 20:12 


3 


slope > 20:12 


2 



For 51 : 1 inch = 25.4 mm. 

1507.7.7 Flashing. Flashing and counterflashing shall be 
made with sheet metal. Valley flashing shall be a minimum 
of 15 inches (381 mm) wide. Valley and flashing metal shall 
be a minimum uncoated thickness of 0.0179-inch (0.455 
mm) zinc-coated G90. Chimneys, stucco or brick walls 
shall have a minimum of two plies of felt for a cap flashing 
consisting of a 4-inch- wide (102 mm) stripoffeltsetinplas- 
tic cement and extending 1 inch (25 mm) above the first felt 
and a top coating of plastic cement. The felt shall extend 
over the base flashing 2 inches (51 mm). 

1507.8 Wood shingles. The installation of wood shingles shall 
comply with the provisions of this section and Table 1507.8. 

1507.8.1 Deck requirements. Wood shingles shall be 
installed on solid or spaced sheathing. Where spaced 
sheathing is used, sheathing boards shall not be less than 
I-inch by 4-inch (25 mm by 102 mm) nominal dimensions 
and shall be spaced on centers equal to the weather exposure 
to coincide with the placement of fasteners. 

1507.8.1.1 Solid sheathing required. Solid sheathing is 
required in areas where the average daily temperature in 
January is 25 °F (-4°C) or less or where there is a possibil- 
ity of ice forming along the eaves causing a backup of 
water. 

1507.8.2 Deck slope. Wood shingles shall be installed on 
slopes of three units vertical in 12 units horizontal (25-per- 
cent slope) or greater. 

1507.8.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869. 

1507.8.4 Ice barrier. In areas where there has been a history 
of ice forming along the eaves causing a backup of water, an 
ice barrier that consists of at least two layers of 
underlayment cemented together or of a self- adhering poly- 
mer-modified bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all roof 
surfaces to a point at least 24 inches (610 mm) inside the 
exterior wall line of the building. 

Exception: Detached accessory structures that contain 
no conditioned floor area. 



2009 INTERNATIONAL BUILDING CODE® 



295 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



TABLE 1507.8 
WOOD SHINGLE AND SHAKE INSTALLATION 



ROOF ITEM 


WOOD SHINGLES 


WOOD SHAKES 


1. Roof slope 


Wood shingles shall be installed on slopes of 
three units vertical in 12 units horizontal 
(3: 12) or greater. 


Wood shakes shall be installed on slopes of 
four units vertical in 12 units horizontal 
(4 : 12) or greater. 


2. Deck requirement 


Temperate climate 


Shingles shall be applied to roofs with solid 
or spaced sheathing. Where spaced sheathing 
is used, sheathing boards shall not be less 
than 1" x 4" nominal dimensions and shall be 
spaced on center equal to the weather 
exposure to coincide with the placement of 
fasteners . 


Shakes shall be applied to roofs with solid or 
spaced sheathing. Where spaced sheathing is 
used, sheathing boards shall not be less than 
1" x 4" nominal dimensions and shall be 
spaced on center equal to the weather 
exposure to coincide with the placement of 
fasteners. When 1" x 4" spaced sheathing is 
installed at 10 inches, boards must be 
installed between the sheathing boards . 


In areas where the average daily 
temperature in January is 25 °F or less or 
where there is a possibility of ice forming 
along the eaves causing a backup of water. 


Solid sheathing required. 


Solid sheathing is required. 


3 . Interlayment 


No requirements. 


Interlayment shall comply with 
ASTM D 226, Type 1. 


4. Underlayment 


Temperate climate 


Underlayment shall comply with 
ASTM D 226, Type 1. 


Underlayment shall comply with 
ASTM D 226, Type 1. 


In areas where there is a possibility of ice 
forming along the eaves causing a backup 
of water. 


An ice barrier that consists of at least two 
layers of underlayment cemented together or 
of a self-adhering polymer-modified bitumen 
sheet shall extend from the eave's edge to a 
point at least 24 inches inside the exterior 
wall line of the building. 


An ice barrier that consists of at least two 
layers of underlayment cemented together or 
of a self-adhering polymer-modified bitumen 
sheet shall extend from the lowest edges of all 
roof surfaces to a point at least 24 inches 
inside the exterior wall line of the building. 


5. Application 


Attachment 


Fasteners for wood shingles shall be hot- 
dipped galvanized or Type 304 (Type 316 for 
coastal areas) stainless steel with a minimum 
penetration of 0.75 inch into the sheathing. 
For sheathing less than 0.5 inch thick, the 
fasteners shall extend through the sheathing . 


Fasteners for wood shakes shall be hot-dipped 
galvanized or Type 304 (Type 316 for coastal 
areas) with a minimum penetration of 0.75 
inch into the sheathing . For sheathing less 
than 0.5 inch thick, the fasteners shall extend 
through the sheathing. 


No. of fasteners 


Two per shingle. 


Two per shake . 


Exposure 


Weather exposures shall not exceed those set 
forth in Table 1507.8.7. 


Weather exposures shall not exceed those set 
forth in Table 1507.9.8. 


Method 


Shingles shall be laid with a side lap of not 
less than 1.5 inches between joints in courses, 
and no two joints in any three adjacent 
courses shall be in direct alignment. Spacing 
between shingles shall be 0.25 to 0.375 inch. 


Shakes shall be laid with a side lap of not less 
than 1.5 inches between joints in adjacent 
courses. Spacing between shakes shall not be 
less than 0.375 inch or more than 0.625 inch 
for shakes and taper sawn shakes of naturally 
durable wood and shall be 0.25 to 0.375 inch 
for preservative-treated taper sawn shakes. 


Flashing 


In accordance with Section 1507.8.8. 


In accordance with Section 1507.9.9. 



For 51 : 1 inch = 25.4 mm, °C = [(OF) - 32]1 1.8. 



296 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



1507.8.5 Material standards. Wood shingles shall be of 
naturally durable wood and comply with the requirements 
ofTable 1507.8.5. 

TABLE 1507.8.5 
WOOD SHINGLE MATERIAL REQUIREMENTS 



MATERIAL 


APPLICABLE 
MINIMUM GRADES 


GRADING RULES 


Wood shingles of naturally 
durable wood 


1,2 or 3 


eSSB 



CSSB = Cedar Shake and Shingle Bureau 

1507.8.6 Attachment. Fasteners for wood shingles shall be 
corrosion resistant with a minimum penetration of 3/ 4 inch 
(19.1 mm) into the sheathing. For sheathing less than i/ 2 
inch (12.7 mm) in thickness, the fasteners shall extend 
through the sheathing. Each shingle shall be attached with a 
minimum of two fasteners. 

1507.8.7 Application. Wood shingles shall be laid with a 
side lap not less than 1V 2 inches (38 mm) betweenjoints in 
adjacent courses, and not be in direct alignment in alternate 
courses. Spacing between shingles shall be i/ 4 to 3/ 8 inches 
(6.4 to 9.5 mm). Weather exposure for wood shingles shall 
not exceed that set in Table 1507.8.7. 

TABLE 1507.8.7 
WOOD SHINGLE WEATHER EXPOSURE AND ROOF SLOPE 



ROOFING MATERIAL 


LENGTH 

(inches) 


GRADE 


EXPOSURE (inches) 


3:12 pitch 
to < 4:12 


4:12 pitch 
or steeper 


Shingles of naturally 
durable wood 


16 


No.l 

No. 2 

No. 3 


3.75 

3.5 

3 


5 
4 
3.5 


18 


No.l 

No. 2 
No. 3 


4.25 
4 
3.5 


5.5 

4.5 

4 


24 


No. 1 
No. 2 
No. 3 


5.75 

5.5 

5 


7.5 
6.5 

5.5 



For SI: 1 inch = 25.4 mm. 

1507.8.8 Flashing. At the juncture of the roof and vertical 
surfaces, flashing and counterflashing shall be provided in 
accordance with the manufacturer's installation instruc- 
tions, and where of metal, shall not be less than 0.019-inch 
(0.48 mm) (No. 26 galvanized sheet gage) corrosion-resis- 
tant metal. The valley flashing shall extend at least 11 inches 
(279 mm) from the centerline each way and have a splash 
diverter rib not less than 1 inch (25 mm) high at the flow line 
formed as part of the flashing. Sections of flashing shall 
have an end lap of not less than 4 inches (102 mm). For roof 
slopes of three units vertical in 12 units horizontal (25-per- 



cent slope) and over, the valley flashing shall have a 
36-inch-wide (914 mm) underlayment of either one layer of 
Type I underlayment running the full length of the valley or 
a self- adhering pOlymer- modified bitumen sheet complying 
with ASTM D 1970, in addition to other required 
underlayment. In areas where the average daily temperature 
in January is 25°F (-4°C) or less or where there is a possibil- 
ity of ice forming along the eaves causing a backup of water, 
the metal valley flashing underlayment shall be solidly 
cemented to the roofing underlayment for slopes under 
seven units vertical in 12 units horizontal (58-percent slope) 
or self-adhering polymer-modified bitumen sheet shall be 
installed. 

1507.9 Wood shakes. The installation of wood shakes shall 
comply with the provisions of this section and Table 1507.8. 

1507.9.1 Deck requirements. Wood shakes shall only be 
used on solid or spaced sheathing. Where spaced sheathing 
is used, sheathing boards shall not be less than I-inch by 
4-inch (25 mm by 102 mm) nominal dimensions and shall 
be spaced on centers equal to the weather exposure to coin- 
cide with the placement of fasteners. Where I-inch by 
4-inch (25 mm by 102 mm) spaced sheathing is installed at 
10 inches (254 mm) O.C., additional I-inch by 4-inch (25 
mm by 102 mm) boards shall be installed between the 
sheathing boards. 

1507.9.1.1 Solid sheathing required. Solid sheathing is 
required in areas where the average daily temperature in 
January is 25°F (-4°C) or less or where there is a possibil- 
ity of ice forming along the eaves causing a backup of 
water. 

1507.9.2 Deck slope. Wood shakes shall only be used on 
slopes of four units vertical in 12 units horizontal (33-per- 
cent slope) or greater. 

1507.9.3 Underlayment. Underlayment shall comply with 
ASTM D 226, Type I or ASTM D 4869. 

1507.9.4 Ice barrier. In areas where there has been a history 
of ice forming along the eaves causing a backup of water, an 
ice barrier that consists of at least two layers of 
underlayment cemented together or of a self- adhering poly- 
mer-modified bitumen sheet shall be used in lieu of normal 
underlayment and extend from the lowest edges of all roof 
surfaces to a point at least 24 inches (610 mm) inside the 
exterior wall line of the building. 

Exception: Detached accessory structures that contain 
no conditioned floor area. 

1507.9.5 Interlayment. Interlayment shall comply with 
ASTM D 226, Type I. 



2009 INTERNATIONAL BUILDING CODE® 



297 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



1507.9.6 Material standards. Wood shakes shall comply 
with the requirements of Table 1507.9.6. 

TABLE 1507.9.6 
WOOD SHAKE MATERIAL REQUIREMENTS 



MATERIAL 


MINIMUM 
GRADES 


APPLICABLE 

GRADING 

RULES 


Wood shakes of naturally durable wood 


1 


CSSB 


Taper sawn shakes of naturally durable 
wood 


lor 2 


CSSB 


Preservative-treated shakes and shingles of 
naturally durable wood 


1 


CSSB 


Fire-retardant-treated shakes and shingles 
of naturally durable wood 


1 


CSSB 


Preservative-treated taper sawn shakes of 
Southern pine treated in accordance with 
AWPA Ul (Commodity Specification A, 
Use Category 3B and Section 5.6) 


lor 2 


TFS 



CSSB = Cedar Shake and Shingle Bureau. 

TFS = Forest Products Laboratory of the Texas Forest Services. 

1507.9.7 Attachment. Fasteners for wood shakes shall be 
corrosion resistant with a minimum penetration of 3/ 4 inch 
(19.1 mm) into the sheathing. For sheathing less than i/ 2 
inch (12.7 mm) in thickness, the fasteners shall extend 
through the sheathing. Each shake shall be attached with a 
minimum of two fasteners. 

1507.9.8 Application. Wood shakes shall be laid with a side 
lap not less than 1V 2 inches (38 mm) betweenjoints in adja- 
cent courses. Spacing between shakes in the same course 
shall be 3/ 8 to 5/ 8 inches (9.5 to 15.9 mm) for shakes and taper 
sawn shakes of naturally durable wood and shall be i/ 4 to 3/ 8 
inch (6.4 to 9.5 mm) for preservative taper sawn shakes. 
Weather exposure for wood shakes shall not exceed those 
set in Table 1507.9.8. 

TABLE 1507.9.8 
WOOD SHAKE WEATHER EXPOSURE AND ROOF SLOPE 



ROOFING MATERIAL 


LENGTH 
(inches) 


GRADE 


EXPOSURE 

(inches) 
4:12 PITCH 
OR STEEPER 


Shakes of naturally 
durable wood 


18 

24 


No.l 
No.l 


7.5 
loa 


Preservative- treated taper 
sawn shakes of Southern 
yellow pine 


18 

24 


No.l 

No. 1 


7.5 
10 


18 

24 


No. 2 
No. 2 


5.5 
7.5 


Taper sawn shakes of 
naturally durable wood 


18 

24 


No.l 
No.l 


7.5 
10 


18 

24 


No. 2 

No. 2 


5.5 
7.5 



For SI: 1 inch = 25.4 mm. 

a. For 24-inch by 0.375-inch handsplit shakes, the maximum exposure is 7.5 
inches. 

1507.9.9 Flashing. At the juncture of the roof and vertical 
surfaces, flashing and counterflashing shall be provided in 
accordance with the manufacturer's installation instruc- 
tions, and where of metal, shall not be less than 0.019-inch 



(0.48 mm) (No. 26 galvanized sheet gage) corrosion-resis- 
tant metal. The valley flashing shall extend at least 11 inches 
(279 mm) from the centerline each way and have a splash 
diverter rib not less than 1 inch (25 mm) high at the flow line 
formed as part of the flashing. Sections of flashing shall 
have an end lap of not less than 4 inches (102 mm). For roof 
slopes of three units vertical in 12 units horizontal (25-per- 
cent slope) and over, the valley flashing shall have a 
36-inch- wide (914 mm) underlayment of either one layer of 
Type I underlayment running the full length of the valley or 
a self-adhering polymer-modified bitumen sheet complying 
with ASTM D 1970, in addition to other required 
underlayment. In areas where the average daily temperature 
in January is 25°F (-4°C) or less or where there is a possibil- 
ity of ice forming along the eaves causing a backup of water, 
the metal valley flashing underlayment shall be solidly 
cemented to the roofing underlayment for slopes under 
seven units vertical in 12 units horizontal (58-percent slope) 
or self-adhering polymer-modified bitumen sheet shall be 
installed. 

1507.10 Built-up roofs. The installation of built-up roofs shall 
comply with the provisions of this section. 

1507.10. 1 Slope. Built-up roofs shall have a design slope of 
a minimum of one- fourth unit vertical in 12 units horizontal 
(2-percent slope) for drainage, except for coal-tar built-up 
roofs that shall have a design slope of a minimum 
one-eighth unit vertical in 12 units horizontal (I-percent 
slope) . 

1507.10.2 Material standards. Built-up roof covering 
materials shall comply with the standards in Table 
1507.10.2. 

1507.11 Modified bitumen roofing. The installation of modi- 
fied bitumen roofing shall comply with the provisions of this 
section. 

1507.11.1 Slope. Modified bitumen membrane roofs shall 
have a design slope of a minimum of one- fourth unit vertical 
in 12 units horizontal (2-percent slope) for drainage. 

1507.11.2 Material standards. Modified bitumen roof 
coverings shall comply with CGSB 37-GP-56M, ASTM D 
6162, ASTM D 6163, ASTM D 6164, ASTM D 6222, 
ASTM D 6223, ASTM D 6298 or ASTM D 6509. 

1507.12 Thermoset single-ply roofing. The installation of 
thermoset single-ply roofing shall comply with the provisions 
of this section. 

1507.12.1 Slope. Thermoset single-ply membrane roofs 
shall have a design slope of a minimum of one-fourth unit 
vertical in 12 units horizontal (2-percent slope) for drain- 
age. 

1507.12.2 Material standards. Thermoset single-ply roof 
coverings shall comply with ASTM D 4637, ASTM D 5019 
or CGSB 37-GP-52M. 

1507.12.3 Ballasted thermoset low-slope roofs. Ballasted 
thermoset low-slope roofs (roof slope < 2: 12) shall be 
installed in accordance with this section and Section 1504.4. 
Stone used as ballast shall comply with ASTM D 448. 



298 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



TABLE 1507.10.2 
BUILT-UP ROOFING MATERIAL STANDARDS 



MATERIAL STANDARD 


STANDARD 


Acrylic coatings used in roofing 


ASTM D 6083 


Aggregate surfacing 


ASTM D 1863 


Asphalt adhesive used in roofing 


ASTM D 3747 


Asphalt cements used in roofing 


ASTM D 3019; D 2822; 
D4586 


Asphalt-coated glass fiber base sheet 


ASTM D 4601 


Asphalt coatings used in roofing 


ASTM D1227; D 2823; 
D4479 


Asphalt glass felt 


ASTM D 2178 


Asphalt primer used in roofing 


ASTM D 41 


Asphalt-saturated and asphalt-coated 
organic felt base sheet 


ASTM D 2626 


Asphalt-saturated organic felt 
(perforated) 


ASTM D 226 


Asphalt used in roofing 


ASTM D 312 


Coal-tar cements used in roofing 


ASTM D 4022; D 5643 


Coal-tar saturated organic felt 


ASTM D 227 


Coal-tar pitch used in roofing 


ASTM D 450; Type I or II 


Coal-tar primer used in roofing, 
dampproofing and waterproofing 


ASTMD 43 


Glass mat, coal tar 


ASTM D 4990 


Glass mat, venting type 


ASTM D 4897 


Mineral- surfaced inorganic cap sheet 


ASTM D 3909 


Thermoplastic fabrics used in 
roofing 


ASTM D 5665, D 5726 



1507.13 Thermoplastic single-ply roofing. The installation 
of thermoplastic single-ply roofing shall comply with the pro- 
visions of this section. 

1507.13.1 Slope. Thermoplastic single-ply membrane 
roofs shall have a design slope of a minimum of one- fourth 
unit vertical in 12 units horizontal (2-percent slope). 

1507.13.2 Material standards. Thermoplastic single-ply 
roof coverings shall comply with ASTM D 4434, ASTM D 
6754, ASTM D 6878 or CGSB CAN/CGSB 37-54. 

1507.13.3 Ballasted thermoplastic low-slope roofs. Bal- 
lasted thermoplastic low-slope roofs (roof slope < 2: 12) 
shall be installed in accordance with this section and Section 
1504.4. Stone used as ballast shall comply with ASTM 
D448. 

1507.14 Sprayed polyurethane foam roofing. The installa- 
tion of sprayed polyurethane foam roofing shall comply with 
the provisions of this section. 

1507.14.1 Slope. Sprayed polyurethane foam roofs shall 
have a design slope of a minimum of one-fourth unit vertical 
in 12 units horizontal (2-percent slope) for drainage. 



1507.14.2 Material standards. Spray-applied pOlyure- 
thane foam insulation shall comply with Type III or IV as 
defined in ASTM C 1029. 

1507.14.3 Application. Foamed-in-place roof insulation 
shall be installed in accordance with the manufacturer's 
instructions. A liquid-applied protective coating that com- 
plies with Section 1507.15 shall be applied no less than 2 
hours nor more than 72 hours following the application of 
the foam. 

1507.14.4 Foam plastics. Foam plastic materials and instal- 
lation shall comply with Chapter 26. 

1507.15 Liquid-applied coatings. The installation of liq- 
uid-applied coatings shall comply with the provisions of this 
section. 

1507.15.1 Slope. Liquid-applied roofs shall have a design 
slope of a minimum of one-fourth unit vertical in 12 units 
horizontal (2-percent slope). 

1507.15.2 Material standards. Liquid-applied roof coat- 
ings shall comply with ASTM C 836, ASTM C 957, ASTM 
D 1227 or ASTM D 3468, ASTM D 6083, ASTM D 6694 or 
ASTM D 6947. 

1507.16 Roof gardens and landscaped roofs. Roof gardens 
and landscaped roofs shall comply with the requirements of 
this chapter and Sections 1607.11.2.2 and 1607.11.3. 



SECTION 1508 
ROOF INSULATION 

1508.1 General. The use of above-deck thermal insulation 
shall be permitted provided such insulation is covered with an 
approved roof covering and passes the tests ofFM 4450 or UL 
1256 when tested as an assembly. 

Exceptions: 

1. Foam plastic roof insulation shall conform to the 
material and installation requirements of Chapter 26. 

2. Where a concrete roof deck is used and the 
above-deck thermal insulation is covered with an 
approved roof covering. 

1508.1.1 Cellulosic fiberboard. Cellulosic fiberboard roof 
insulation shall conform to the material and installation 
requirements of Chapter 23. 

1508.2 Material standards. Above-deck thermal insulation 
board shall comply with the standards in Table 1508.2. 

TABLE 1508.2 
MATERIAL STANDARDS FOR ROOF INSULATION 



Cellular glass board 


ASTM C 552 


Composite boards 


ASTM C 1289, Type III, 


IV, V or VI 


Expanded polystyrene 


ASTM C 578 


Extruded polystyrene board 


ASTM C 578 


Perlite board 


ASTM C 728 


Polyisocyanurate board 


ASTM C 1289, Type I oi 


* Type II 


Wood fiberboard 


ASTM C 208 



2009 INTERNATIONAL BUILDING CODE® 



299 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



SECTION 1509 
ROOFTOP STRUCTURES 

1509. 1 General. The provisions of this section shall govern the 
construction of rooftop structures. 

1509.2 Penthouses. A. penthouse or penthouses in compliance 
with Sections 1509.2.1 through 1509.2.4 shall be considered as 
a portion of the story below. 

1509.2.1 Height above roof. A penthouse or other projec- 
tion above the roof in structures of other than Type I con- 
struction shall not exceed 28 feet (8534 mm) above the roof 
where used as an enclosure for tanks or for elevators that run 
to the roof and in all other cases shall not extend more than 
18 feet (5486 mm) above the roof. 

1509.2.2 Area limitation. The aggregate area of pent- 
houses and other rooftop structures shall not exceed 
one-third the area of the supporting roof. Such penthouses 
shall not contribute to either the building area or number of 
stories as regulated by Section 503.1. The area of the 
penthouse shall not be included in determining the fire area 
defined in Section 902. 

1509.2.3 Use limitations. A penthouse, bulkhead or any 
other similar projection above the roof shall not be used for 
purposes other than shelter of mechanical equipment or 
shelter of vertical shaft openings in the roof. Provisions such 
as louvers, louver blades or flashing shall be made to protect 
the mechanical equipment and the building interior from the 
elements. Penthouses or bulkheads used for purposes other 
than permitted by this section shall conform to the require- 
ments of this code for an additional story. The restrictions of 
this section shall not prohibit the placing of wood flagpoles 
or similar structures on the roof of any building. 

1509.2.4 Type of construction. Penthouses shall be con- 
structed with walls, floors and roof as required for the build- 
ing. 

Exceptions: 

1. On buildings of Type I construction, the exterior 
walls and roofs of penthouses with & fire separa- 
tion distance of more than 5 feet (1524 mm) and 
less than 20 feet (6096 mm) shall be of at least 
I-hour fire resistance-rated noncombustible con- 
struction. Walls and roofs with a fire separation 
distance of 20 feet (6096 mm) or greater shall be of 
noncombustible construction. Interior framing 
and walls shall be of noncombustible construction. 

2. On buildings of Type I construction two stories 
above grade plane or less in height and Type II 
construction, the exterior walls and roofs of pent- 
houses with afire separation distance of more than 
5 feet (1524 mm) and less than 20 feet (6096 mm) 
shall be of at least I-hour fire-resistance-rated 
noncombustible or fire-retardant-treated wood 
construction. Walls and roofs with a fire separa- 
tion distance of 20 feet (6096 mm) or greater shall 
be of noncombustible or fire-retardant-treated 
wood construction. Interior framing and walls 



shall be of noncombustible or fire retardant- 
treated wood construction. 

3. On buildings of Type III, IV and V construction, 
the exterior walls of penthouses with afire separa- 
tion distance of more than 5 feet (1524 mm) and 
less than 20 feet (6096 mm) shall be at least I-hour 
fire-resistance-rated construction. Walls with a 
fire separation distance of 20 feet (6096 mm) or 
greater from a common property line shall be of 
Type IV construction or noncombustible, or 
fire-retardant-treated wood construction. Roofs 
shall be constructed of materials and fire-resis- 
tance rated as required in Table 601 and Section 
603, Item 25.3. Interior framing and walls shall be 
Type IV construction or noncombustible or 
fire-retardant-treated wood construction. 

4. On buildings of Type I construction, unprotected 
noncombustible enclosures housing only mechan- 
ical equipment and located with a minimum fire 
separation distance of 20 feet (6096 mm) shall be 
permitted. 

5. On buildings of Type I construction two stories or 
less above grade plane in height, or Type II, III, IV 
and V construction, unprotected noncombustible 
or fire-retardant-treated woodenclosures housing 
only mechanical equipment and located with a 
minimum//r£ separation distance of 20 feet (6096 
mm) shall be permitted. 

6. On one-story buildings, combustible unroofed 
mechanical equipment screens, fences or similar 
enclosures are permitted where located with afire 
separation distance of at least 20 feet (6096 mm) 
from adjacent property lines and where not 
exceeding 4 feet (1219 mm) in height above the 
roof surface. 

7. Dormers shall be of the same type of construction 
as the roof on which they are placed, or of the exte- 
rior walls of the building. 

1509.3 Tanks. Tanks having a capacity of more than 500 gal- 
lons (2 m 3 ) placed in or on a building shall be supported on 
masonry, reinforced concrete, steel or Type IV construction 
provided that, where such supports are located in the building 
above the lowest story, the support shall be fire-resistance rated 
as required for Type IA construction. 

1509.3.1 Valve. Such tanks shall have in the bottom or on 
the side near the bottom, a pipe or outlet, fitted with a suit- 
able quick opening valve for discharging the contents in an 
emergency through an adequate drain. 

1509.3.2 Location. Such tanks shall not be placed over or 
near a line of stairs or an elevator shaft, unless there is a solid 
roof or floor underneath the tank. 

1509.3.3 Tank cover. Unenclosed roof tanks shall have cov- 
ers sloping toward the outer edges. 

1509.4 Cooling towers. Cooling towers in excess of 250 
square feet (23.2 m 2 ) in base area or in excess of 15 feet (4572 



300 



2009 INTERNATIONAL BUILDING CODE® 



ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 



1 



mm) high where located on building roofs more than 50 feet 
(15 240 mm) high shall be of noncombustible construction. 
Cooling towers shall not exceed one-third of the supporting 
roof area. 

Exception: Drip boards and the enclosing construction of 
wood not less than 1 inch (25 mm) nominal thickness, pro- 
vided the wood is covered on the exterior of the tower with 
noncombustible material. 

1509.5 Towers, spires, domes and cupolas. Any tower, spire, 
dome or cupola shall be of a type of construction not less in 
fire-resistance rating than required for the building to which it 
is attached, except that any such tower, spire, dome or cupola 
that exceeds 85 feet (25 908 mm) in height above grade plane, 
exceeds 200 square feet (18.6 m 2 ) in horizontal area or is used 
for any purpose other than a belfry or an architectural embel- 
lishment shall be constructed of and supported on Type I or II 
construction. 

1509.5.1 Noncombustible construction required. Any 

tower, spire, dome or cupola that exceeds 60 feet (18 288 
mm) in height above the highest point at which it comes in 
contact with the roof, or that exceeds 200 square feet (18.6 
m 2 ) in area at any horizontal section, or which is intended to 
be used for any purpose other than a belfry or architectural 
embellishment, shall be entirely constructed of and sup- 
ported by noncombustible materials. Such structures shall 
be separated from the building below by construction hav- 
ing a fire-resistance rating of not less than 1.5 hours with 
openings protected with a minimum 1 .5-hour fire protection 
rating. Structures, except aerial supports 12 feet (3658 mm) 
high or less, flagpoles, water tanks and cooling towers, 
placed above the roof of any building more than 50 feet (15 
240 mm) in building height, shall be of noncombustible 
material and shall be supported by construction of 
noncombustible material. 

1509.5.2 Towers and spires. Towers and spires where 
enclosed shall have exterior walls as required for the build- 
ing to which they are attached. The roof covering of spires 
shall be of a class of roof covering as required for the main 
roof of the rest of the structure. 



SECTION 1510 
REROOFING 

1510.1 General. Materials and methods of application used for 
recovering or replacing an existing roof covering shall comply 
with the requirements of Chapter 15. 

Exception: Reroofing shall not be required to meet the min- 
imum design slope requirement of one-quarter unit vertical 
in 12 units horizontal (2-percent slope) in Section 1507 for 
roofs that provide positive roof drainage. 

1510.2 Structural and construction loads. Structural roof 
components shall be capable of supporting the roof-covering 
system and the material and equipment loads that will be 
encountered during installation of the system. 

1510.3 Recovering versus replacement. New roof coverings 
shall not be installed without first removing all existing layers 



of roof coverings down to the roof deck where any of the fol- 
lowing conditions occur: 

1. Where the existing roof or roof covering is water soaked 
or has deteriorated to the point that the existing roof or 
roof covering is not adequate as a base for additional 
roofing. 

2. Where the existing roof covering is wood shake, slate, 
clay, cement or asbestos-cement tile. 

3. Where the existing roof has two or more applications of 
any type of roof covering. 

Exceptions: 

1. Complete and separate roofing systems, such as 
standing-seam metal roof systems, that are designed 
to transmit the roof loads directly to the building's 
structural system and that do not rely on existing roofs 
and roof coverings for support, shall not require the 
removal of existing roof coverings. 

2. Metal panel, metal shingle and concrete and clay tile 
roof coverings shall be permitted to be installed over 
existing wood shake roofs when applied in accor- 
dance with Section 1510.4. 

3. The application of a new protective coating over an 
existing spray polyurethane foam roofing system 
shall be permitted without tear-off of existing roof 
coverings. 

1510.4 Roof recovering. Where the application of a new roof 
covering over wood shingle or shake roofs creates a combusti- 
ble concealed space, the entire existing surface shall be covered 
with gypsum board, mineral fiber, glass fiber or other approved 
materials securely fastened in place. 

1510.5 Reinstallation of materials. Existing slate, clay or 
cement tile shall be permitted for reinstallation, except that 
damaged, cracked or broken slate or tile shall not be reinstalled. 
Existing vent flashing, metal edgings, drain outlets, collars and 
metal counterflashings shall not be reinstalled where rusted, 
damaged or deteriorated. Aggregate surfacing materials shall 
not be reinstalled. 

1510.6 Flashings. Flashings shall be reconstructed in accor- 
dance with app roved manufacturer's installation instructions. 
Metal flashing to which bituminous materials are to be adhered 
shall be primed prior to installation. 



1 



2009 INTERNATIONAL BUILDING CODE® 



301 



302 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 16 
STRUCTURAL DESIGN 



SECTION 1601 
GENERAL 

1601.1 Scope. The provisions of this chapter shall govern the 
structural design of buildings, structures and portions thereof 
regulated by this code. 



SECTION 1602 
DEFINITIONS AND NOTATIONS 

1602.1 Definitions. The following words and terms shall, for 
the purposes of this chapter, have the meanings shown herein. 

ALLOWABLE STRESS DESIGN. A method of proportion- 
ing structural members, such that elastically computed stresses 
produced in the members by nominalloads do not exceed spec- 
ified allowable stresses (also called "working stress design"). 

DEAD LOADS. The weight of materials of construction 
incorporated into the building, including but not limited to 
walls, floors, roofs, ceilings, stairways, built-in partitions, fin- 
ishes, cladding and other similarly incorporated architectural 
and structural items, and the weight of fixed service equipment, 
such as cranes, plumbing stacks and risers, electrical feeders, 
heating, ventilating and air-conditioning systems and 
automatic sprinkler systems. 

DESIGN STRENGTH. The product of the nominal strength 
and a resistance factor (or strength reduction factor). 

DIAPHRAGM. A horizontal or sloped system acting to trans- 
mit lateral forces to the vertical-resisting elements. When the 
term "diaphragm" is used, it shall include horizontal bracing 
systems. 

Diaphragm, blocked. In light-frame construction, a dia- 
phragm in which all sheathing edges not occurring on a 
framing member are supported on and fastened to blocking. 

Diaphragm boundary. In light- frame construction, a loca- 
tion where shear is transferred into or out of the diaphragm 
sheathing. Transfer is either to a boundary element or to 
another force-resisting element. 

Diaphragm chord. A diaphragm boundary element per- 
pendicular to the applied load that is assumed to take axial 
stresses due to the diaphragm moment. 

Diaphragm flexible. A diaphragm is flexible for the pur- 
pose of distribution of story shear and torsional moment 
where so indicated in Section 12.3.1 of ASCE 7, as modified 
in Section 1613.6.1. 

Diaphragm, rigid. A diaphragm is rigid for the purpose of 
distribution of story shear and torsional moment when the 
lateral deformation of the diaphragm is less than or equal to 
two times the average story drift. 

DURATION OF LOAD. The period of continuous applica- 
tion of a given load, or the aggregate of periods of intermittent 
applications of the same load. 



ESSENTIAL FACILITIES. Buildings and other structures 
that are intended to remain operational in the event of extreme 
environmental loading from flood, wind, snow or earthquakes. 

FABRIC PARTITION. A partition consisting of a finished 
surface made of fabric, without a continuous rigid backing, that 
is directly attached to a framing system in which the vertical 
framing members are spaced greater than 4 feet (1219 mm) on 
center. 

FACTORED LOAD. The product of a nominal load and a load 
factor. 

GUARD. See Section 1002.1. 

IMPACT LOAD. The load resulting from moving machinery, 
elevators, craneways, vehicles and other similar forces and 
kinetic loads, pressure and possible surcharge from fixed or 
moving loads. 

LIMIT STATE. A condition beyond which a structure or 
member becomes unfit for service and is judged to be no longer 
useful for its intended function (serviceability limit state) or to 
be unsafe (strength limit state) . 

LIVE LOADS. Those loads produced by the use and occu- 
pancy of the building or other structure and do not include con- 
struction or environmental loads such as wind load, snow load, 
rain load, earthquake load, flood load or dead load. 

LIVE LOADS (ROOF). Those loads produced (1) during 
maintenance by workers, equipment and materials; and (2) 
during the life of the structure by movable objects such as 
planters and by people. 

LOAD AND RESISTANCE FACTOR DESIGN (LRFD). A 

method of proportioning structural members and their connec- 
tions using load and resistance factors such that no applicable 
limit state is reached when the structure is subjected to appro- 
priate load combinations. The term "LRFD" is used in the 
design of steel and wood structures. 

LOAD EFFECTS. Forces and deformations produced in 
structural members by the applied loads. 

LOAD FACTOR. A factor that accounts for deviations of the 
actual load from the nominalload, for uncertainties in the anal- 
ysis that transforms the load into a load effect, and for the prob- 
ability that more than one extreme load will occur 
simultaneously. 

LOADS. Forces or other actions that result from the weight of 
building materials, occupants and their possessions, environ- 
mental effects, differential movement and restrained dimen- 
sional changes. Permanent loads are those loads in which 
variations over time are rare or of small magnitude, such as 
dead loads. All other loads are variable loads (see also" Nomi- 
nalloads ") . 

NOMINAL LOADS. The magnitudes of the loads specified in 
this chapter (dead, live, soil, wind, snow, rain, flood and earth- 
quake). 



2009 INTERNATIONAL BUILDING CODE® 



303 



STRUCTURAL DESIGN 



OCCUPANCY CATEGORY. A category used to determine 
structural requirements based on occupancy. 

OTHER STRUCTURES. Structures, other than buildings, 
for which loads are specified in this chapter. 

PANEL (PART OF A STRUCTURE). The section of a floor, 
wall or roof comprised between the supporting frame of two 
adjacent rows of columns and girders or column bands of floor 
or roof construction. 

RESISTANCE FACTOR. A factor that accounts for devia- 
tions of the actual strength from the nominal strength and the 
manner and consequences of failure (also called "strength 
reduction factor"). 

STRENGTH, NOMINAL. The capacity of a structure or 
member to resist the effects of loads, as determined by compu- 
tations using specified material strengths and dimensions and 
equations derived from accepted principles of structural 
mechanics or by field tests or laboratory tests of scaled models, 
allowing for modeling effects and differences between labora- 
tory and field conditions. 

STRENGTH, REQUIRED. Strength of a member, cross sec- 
tion or connection required to resist factored loads or related 
internal moments and forces in such combinations as stipulated 
by these provisions. 

STRENGTH DESIGN. A method of proportioning structural 
members such that the computed forces produced in the mem- 
bers by factored loads do not exceed the member design 
strength [also called "load and resistance factor design" 
(LRFD)]. The term "strength design" is used in the design of 
concrete and masonry structural elements. 

VEHICLE BARRIER SYSTEM. A system of building com 
ponents near open sides of a garage floor or ramp or building 
walls that act as restraints for vehicles . 

NOTATIONS. 

D Dead load. 

E Combined effect of horizontal and vertical 

earthquake induced forces as defined in Section 
12.4.2 of ASCE 7. 

F Load due to fluids with well-defined pressures and 

maximum heights. 

I Fa = Flood load in accordance with Chapter 5 of ASCE 7. 

H Load due to lateral earth pressures, ground water 

pressure or pressure of bulk materials. 

L Live load, except roof live load, including any per- 

mitted live load reduction. 

L r Roof live load including any permitted live load 

reduction. 

R Rain load. 

S Snow load. 

T Self- straining force arising from contraction or 

expansion resulting from temperature change, 
shrinkage, moisture change, creep in component 



materials, movement due to differential settlement 
or combinations thereof. 

W = Load due to wind pressure. 



SECTION 1603 
CONSTRUCTION DOCUMENTS 

1603.1 General. Construction documents shall show the size, 
section and relative locations of structural members with floor 
levels, column centers and offsets dimensioned. The design 
loads and other information pertinent to the structural design 
required by Sections 1603.1.1 through 1603.1.9 shall be indi- 
cated on the construction documents. 

Exception: Construction documents for buildings con- 
structed in accordance with the conventional light-frame 
construction provisions of Section 2308 shall indicate the 
following structural design information : 

1. Floor and roof live loads. 

2. Ground snow load, Pg. 

3. Basic wind speed (3-second gust), miles per hour 
(mph) (km/hr) and wind exposure. 

4. Seismic design category and site class. 

5. Flood design data, if located in flood hazard areas 
established in Section 1612.3. 

6. Design load-bearing values of soils. 

1603.1.1 Floor live load. The uniformly distributed, con- 
centrated and impact floor live load used in the design shall 
be indicated for floor areas. Use of live load reduction in 
accordance with Section 1607.9 shall be indicated for each 
type of live load used in the design. 

1603.1.2 Roof live load. The roof live load used in the 
design shall be indicated for roof areas (Section 1607.11). 

1603.1.3 Roof snow load. The ground snow load, P shall 
be indicated. In areas where the ground snow load, P 
exceeds 10 pounds per square foot (psf) (0.479 kN/m 2 ) , the 
following additional information shall also be provided, 
regardless of whether snow loads govern the design of the 
roof: 

1. Flat-roof snow load, Pr. 

2. Snow exposure factor, Ceo 

3. Snow load importance factor, 1 

4. Thermal factor, C t . 

1603.1.4 Wind design data. The following information 
related to wind loads shall be shown, regardless of whether 
wind loads govern the design of the lateral- force- resisting 
system of the building: 

1. Basic wind speed (3-second gust), miles per hour 
(km/hr). 

2. Wind importance factor, /, and occupancy category. 

3. Wind exposure. Where more than one wind exposure 
is utilized, the wind exposure and applicable wind 
direction shall be indicated. 



304 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



4. The applicable internal pressure coefficient. 

5. Components and cladding. The design wind pres- 
sures in terms of psf (kN/m 2 ) to be used for the design 
of exterior component and cladding materials not spe- 
cifically designed by the registered design profes- 
sional. 

1603.1.5 Earthquake design data. The following informa- 
tion related to seismic loads shall be shown, regardless of 
whether seismic loads govern the design of the lat- 
eral-force-resisting system of the building: 

1. Seismic importance factor, 1, and occupancy cate- 
gory. 

2. Mapped spectral response accelerations, Ss and SI' 

3. Site class. 

4. Spectral response coefficients, SDS and SD1' 

5. Seismic design category. 

6. Basic seismic-force-resisting system(s). 

7. Design base shear. 

8. Seismic response coefficient(s), C s . 

9. Response modification factor(s), R. 
10. Analysis procedure used. 

1603.1.6 Geotechnical information. The design load- 
bearing values of soils shall be shown on the construction 
documents. 

1 603 .1.7 Flood design data. For buildings located in whole 
or in part in flood hazard areas as established in Section 
1612.3, the documentation pertaining to design, if required 
in Section 1612.5, shall be included and the following infor- 
mation, referenced to the datum on the community's Flood 
Insurance Rate Map (FIRM), shall be shown, regardless of 
whether flood loads govern the design of the building: 

1. In flood hazard areas not subject to high-velocity 
wave action, the elevation of the proposed lowest 
floor, including the basement. 

2. In flood hazard areas not subject to high-velocity 
wave action, the elevation to which any nonresiden- 
tial building will be dry floodproofed. 

3. In flood hazard areas subject to high-velocity wave 
action, the proposed elevation of the bottom of the 
lowest horizontal structural member of the lowest 
floor, including the basement. 

1603.1.8 Special loads. Special loads that are applicable to 
the design of the building, structure or portions thereof shall 
be indicated along with the specified section of this code 
that addresses the special loading condition. 

1603.1.9 Systems and components requiring special 
inspections for seismic resistance. Construction docu- 
ments or specifications shall be prepared for those systems 
and components requiring special inspection for seismic 
resistance as specified in Section 1707.1 by the registered 
design professionalresponsible for their design and shall be 
submitted for approval in accordance with Section 107.1. 



Reference to seismic standards in lieu of detailed drawings 
is acceptable. 



SECTION 1604 
GENERAL DESIGN REQUIREMENTS 

1604.1 General. Building, structures and parts thereof shall be 
designed and constructed in accordance with strength design, 
load and resistance factor design, allowable stress design, 
empirical design or conventional construction methods, as per- 
mitted by the applicable material chapters. 

1604.2 Strength. Buildings and other structures, and parts 
thereof, shall be designed and constructed to support safely the 
factored loads in load combinations defined in this code with- 
out exceeding the appropriate strength limit states for the mate- 
rials of construction. Alternatively, buildings and other 
structures, and parts thereof, shall be designed and constructed 
to support safely the nominal loads in load combinations 
defined in this code without exceeding the appropriate speci- 
fied allowable stresses for the materials of construction. 

Loads and forces for occupancies or uses not covered in this 
chapter shall be subject to the approval of the bUilding official. 

1604.3 Serviceability. Structural systems and members 
thereof shall be designed to have adequate stiffness to limit 
deflections and lateral drift. See Section 12.12.1 of ASCE 7 for 
drift limits applicable to earthquake loading. 

1604.3.1 Deflections. The deflections of structural mem- 
bers shall not exceed the more restrictive of the limitations 
of Sections 1604.3.2 through 1604.3.5 or that permitted by 
Table 1604.3. 

TABLE 1604.3 
DEFLECTION LIMITSa,b, c, h, i 



CONSTRUCTION 


L 


Sor W f 


0+ Ld,g 


Roof members: 6 

Supporting plaster ceiling 
Supporting nonplaster ceiling 
Not supporting ceiling 


1/360 
1/240 
1/180 


1/360 
1/240 
1/180 


1/240 
1/180 
1/120 


Floor members 


1/360 


- 


1/240 


Exterior walls and interior partitions: 
With brittle finishes 
With flexible finishes 




1/240 
1/120 




Farm buildings 






1/180 


Greenhouses 


- 


- 


1/120 



For SI: 1 foot = 304.8 mm. 

a. For structural roofing and siding made of formed metal sheets, the total load 
deflection shall not exceed 1/60. For secondary roof structural members sup- 
porting formed metal roofing, the live load deflection shall not exceed 1/150. 
For secondary wall members supporting formed metal siding, the design 
wind load deflection shall not exceed 1/90. For roofs, this exception only 
applies when the metal sheets have no roof covering. 

b. Interior partitions not exceeding 6 feet in height and flexible, folding and 
portable partitions are not governed by the provisions of this section. The 
deflection criterion for interior partitions is based on the horizontal load 
defined in Section 1607.13. 

c. See Section 2403 for glass supports. 

(Table notes continued) 



2009 INTERNATIONAL BUILDING CODE® 



305 



STRUCTURAL DESIGN 



d. For wood structural members having a moisture content of less than 16 per- 
cent at time of installation and used under dry conditions, the deflection 
resulting from L + 0.5D is permitted to be substituted for the deflection 
resulting from L + D. 

e. The above deflections do not ensure against ponding. Roofs that do not have 
sufficient slope or camber to assure adequate drainage shall be investigated 
for ponding. See Section 1611 for rain and ponding requirements and Sec- 
tion 1503.4 for roof drainage requirements. 

f. The wind load is permitted to be taken as 0.7 times the" component and clad- 
ding" loads for the purpose of determining deflection limits herein. 

g. For steel structural members, the dead load shall be taken as zero. 

h. For aluminum structural members or aluminum panels used in skylights and 
sloped glazing framing, roofs or walls of sunroom additions or patio covers, 
not supporting edge of glass or aluminum sandwich panels, the total load 
deflection shall not exceed 1/60. For continuous aluminum structural mem- 
bers supporting edge of glass, the total load deflection shall not exceed 1/175 
for each glass lite or 1/60 for the entire length of the member, whichever is 
more stringent. For aluminum sandwich panels used in roofs or walls of sun- 
room additions or patio covers, the total load deflection shall not exceed 
1/120. 

i. For cantilever members, lshall be taken as twice the length ofthe cantilever. 

1604.3.2 Reinforced concrete. The deflection of rein- 
forced concrete structural members shall not exceed that 
permitted by ACI 318. 

1604.3.3 Steel. The deflection of steel structural members 
shall not exceed that permitted by AISC 360, AISI S100, 
ASCE 3, ASCE 8, Sjl Cj-l.O, Sjl jG-1.1, Sjl K-l.l or Sjl 
LH/DLH-1.1, as applicable. 

1604.3.4 Masonry. The deflection of masonry structural 
members shall not exceed that permitted by TMS 402/ACI 
530/ASCE 5. 

1604.3.5 Aluminum. The deflection of aluminum struc- 
tural members shall not exceed that permitted by AA 
ADM1. 

1604.3.6 Limits. Deflection of structural members over 
span, 1, shall not exceed that permitted by Table 1604.3. 

1604.4 Analysis. Load effects on structural members and their 
connections shall be determined by methods of structural anal- 
ysis that take into account equilibrium, general stability, geo- 
metric compatibility and both short- and long-term material 
properties. 

Members that tend to accumulate residual deformations 
under repeated service loads shall have included in their analy- 
sis the added eccentricities expected to occur during their ser- 
vice life. 

Any system or method of construction to be used shall be 
based on a rational analysis in accordance with well-estab- 
lished principles of mechanics. Such analysis shall result in a 
system that provides a complete load path capable of transfer- 
ring loads from their point of origin to the load-resisting ele- 
ments. 

The total lateral force shall be distributed to the various verti- 
cal elements ofthe lateral-foree-resisting system in proportion 
to their rigidities, considering the rigidity of the horizontal 
bracing system or diaphragm. Rigid elements assumed not to 
be a part of the lateral-foree-resisting system are permitted to 
be incorporated into buildings provided their effect on the 
action of the system is considered and provided for in the 
design. Except where diaphragms are flexible, or are permitted 
to be analyzed as flexible, provisions shall be made for the 
increased forces induced on resisting elements ofthe structural 



system resulting from torsion due to eccentricity between the 
center of application ofthe lateral forces and the center of rigid- 
ity ofthe lateral-foree-resisting system. 

Every structure shall be designed to resist the overturning 
effects caused by the lateral forces specified in this chapter. See 
Section 1609 for wind loads, Section 1610 for lateral soil loads 
and Section 1613 for earthquake loads. 

1604.5 Occupancy category. Each building and structure 
shall be assigned an occupancy category in accordance with 
Table 1604.5. 

1604.5.1 Multiple occupancies. Where a building or struc- 
ture is occupied by two or more occupancies not included in 
the same occupancy category, it shall be assigned the classi- 
fication ofthe highest occupancy category corresponding to 
the various occupancies. Where buildings or structures have 
two or more portions that are structurally separated, each 
portion shall be separately classified. Where a separated 
portion of a building or structure provides required access 
to, required egress from or shares life safety components 
with another portion having a higher occupancy category, 
both portions shall be assigned to the higher occupancy cat- 
egory. 

1604.6 In-situ load tests. The building officials authorized to 
require an engineering analysis or a load test, or both, of any 
construction whenever there is reason to question the safety of 
the construction for the intended occupancy. Engineering anal- 
ysis and load tests shall be conducted in accordance with Sec- 
tion 1714. 

1604.7 Preconstruction load tests. Materials and methods of 
construction that are not capable of being designed by 
approved engineering analysis or that do not comply with the 
applicable material design standards listed in Chapter 35, or 
alternative test procedures in accordance with Section 1712, 
shall be load tested in accordance with Section 1715. 

1604.8 Anchorage. 

1604.8.1 General. Anchorage ofthe roof to walls and col- 
umns, and of walls and columns to foundations, shall be 
provided to resist the uplift and sliding forces that result 
from the application ofthe prescribed loads. 

1604.8.2 Walls. Walls shall be anchored to floors, roofs and 
other structural elements that provide lateral support for the 
wall. Such anchorage shall provide a positive direct connec- 
tion capable of resisting the horizontal forces specified in 
this chapter but not less than the minimum strength design 
horizontal force specified in Section 11.7.3 of ASCE 7, sub- 
stituted for "E' in the load combinations of Section 1605.2 
or 1605.3. Concrete and masonry walls shall be designed to 
resist bending between anchors where the anchor spacing 
exceeds 4 feet (1219 mm). Required anchors in masonry 
walls of hollow units or cavity walls shall be embedded in a 
reinforced grouted structural element ofthe wall. See Sec- 
tions 1609 for wind design requirements and 1613 for earth- 
quake design requirements. 

1604.8.3 Decks. Where supported by attachment to an exte- 
rior wall, decks shall be positively anchored to the primary 
structure and designed for both vertical and lateral loads as 
applicable. Such attachment shall not be accomplished by 



306 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



the use of toenails or nails subject to withdrawal. Where 
positive connection to the primary building structure cannot 
be verified during inspection, decks shall be self-support- 
ing. Connections of decks with cantilevered framing mem- 
bers to exterior walls or other framing members shall be 
designed for both of the following: 

1. The reactions resulting from the dead load and live 
load specified in Table 1607.1, or the snow load spec- 
ified in Section 1608, in accordance with Section 
1605, acting on all portions of the deck. 

2. The reactions resulting from the dead load and live 
load specified in Table 1607.1, or the snow load spec- 
ified in Section 1608, in accordance with Section 
1605, acting on the cantilevered portion of the deck, 



and no live load or snow load on the remaining por- 
tion of the deck. 

1604.9 Counteracting structural actions. Structural mem- 
bers, systems, components and cladding shall be designed to 
resist forces due to earthquake and wind, with consideration of 
overturning, sliding and uplift. Continuous load paths shall be 
provided for transmitting these forces to the foundation. Where 
sliding is used to isolate the elements, the effects of friction 
between sliding elements shall be included as a force. 

1604.10 Wind and seismic detailing. Lateral-foree-resisting 
systems shall meet seismic detailing requirements and limita- 
tions prescribed in this code and ASCE 7, excluding Chapter 
14 and Appendix 11 A, even when wind load effects are greater 
than seismic load effects. 



TABLE 1604.5 
OCCUPANCY CATEGORY OF BUILDINGS AND OTHER STRUCTURES 



OCCUPANCY 
CATEGORY 


NATURE OF OCCUPANCY 


I 


Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to: 

• Agricultural facilities. 

• Certain temporary facilities . 

• Minor storage facilities. 


II 


Buildings and other structures except those listed in Occupancy Categories I, III and IV 


III 


Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not 
limited to: 

• Buildings and other structures whose primary occupancy is public assembly with an occupant load greater than 300. 

• Buildings and other structures containing elementary school, secondary school or day care facilities with an occupant 
load greater than 250. 

• Buildings and other structures containing adult education facilities, such as colleges and universities with an occupant 
load greater than 500. 

• Group 1-2 occupancies with an occupant load of 50 or more resident patients but not having surgery or emergency 
treatment facilities. 

• Group 1-3 occupancies. 

• Any other occupancy with an occupant load greater than 5,000a. 

• Power-generating stations, water treatment facilities for potable water, waste water treatment facilities and other pub- 
lic utility facilities not included in Occupancy Category IV. 

• Buildings and other structures not included in Occupancy Category IV containing sufficient quantities of toxic or ex- 
plosive substances to be dangerous to the public if released. 


IV 


Buildings and other structures designated as essential facilities, including but not limited to: 

• Group 1-2 occupancies having surgery or emergency treatment facilities. 

• Fire, rescue, ambulance and police stations and emergency vehicle garages. 

• Designated earthquake, hurricane or other emergency shelters. 

• Designated emergency preparedness, communications and operations centers and other facilities required for emer- 
gency response. 

• Power-generating stations and other public utility facilities required as emergency backup facilities for Occupancy 
Category IV structures. 

■ Structures containing highly toxic materials as defined by Section 307 where the quantity of the material exceeds the 
maximum allowable quantities of Table 307.1(2). 

• Aviation control towers, air traffic control centers and emergency aircraft hangars. 

• Buildings and other structures having critical national defense functions. 

• Water storage facilities and pump structures required to maintain water pressure for fire suppression. 



a. For purposes of occupant load calculation, occupancies required by Table 1004.1.1 to use gross floor area calculations shall be permitted to use net floor areas to 
determine the total occupant load. 



2009 INTERNATIONAL BUILDING CODE® 



307 



STRUCTURAL DESIGN 



SECTION 1605 
LOAD COMBINATIONS 

1605.1 General. Buildings and other structures and portions 
thereof shall be designed to resist: 

1. The load combinations specified in Section 1605.2, 
1605.3.1 or 1605.3.2, 

2. The load combinations specified in Chapters 18 through 
23, and 

3. The load combinations with overstrength factor speci- 
fied in Section 12.4.3.2 of ASCE 7 where required by 
Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With 
the simplified procedure of ASCE 7 Section 12.14, the 
load combinations with overstrength factor of Section 
12.14.3.2 or ASCE 7 shall be used. 

Applicable loads shall be considered, including both earth- 
quake and wind, in accordance with the specified load combi- 
nations. Each load combination shall also be investigated with 
one or more of the variable loads set to zero. 

Where the load combinations with overstrength factor in 
Section 12.4.3.2 of ASCE 7 apply, they shall be used as fol- 
lows: 

1. The basic combinations for strength design with 
overstrength factor in lieu of Equations 16-5 and 16-7 in 
Section 1605.2.1. 

2. The basic combinations for allowable stress design with 
overstrength factor in lieu of Equations 16-12, 16-13 and 
16-15 in Section 1605.3.1. 

3. The basic combinations for allowable stress design with 
overstrength factor in lieu of Equations 16-20 and 16-21 
in Section 1605.3.2. 

1605.1.1 Stability. Regardless of which load combinations 
are used to design for strength, where overall structure sta- 
bility (such as stability against overturning, sliding, or buoy- 
ancy) is being verified, use of the load combinations 
specified in Section 1605.2 or 1605.3 shall be permitted. 
Where the load combinations specified in Section 1605.2 
are used, strength reduction factors applicable to soil resis- 
tance shall be provided by a registered design professional. 
The stability of retaining walls shall be verified in accor- 
dance with Section 1807.2.3. 

1605.2 Load combinations using strength design or load 
and resistance factor design. 

1605.2.1 Basic load combinations. Where strength design 
or load and resistance factor design is used, structures and 
portions thereof shall resist the most critical effects from the 
following combinations of factored loads: 

L4(D+ F) (Equation 16-1) 

1.2(D+F+ 1) + 1.6(L + J-1) + 

0.5(L r or Sor R) (Equation 16-2) 

1.2D+ 1.6 (Lror Sor Rj + (/[lor 0.8 Wj (Equation 16-3) 

1.2D+ 1.6 W+ f^L + O^iLrorSorR) (Equation 16-4) 

1.2D+ 1.0E+ f x L + f 2 S (Equation 16-5) 



0.9D+ 1.6W+ 1.6H 
0.9D+ 1.0E+ 1.6H 



where: 



(Equation 16-6) 
(Equation 16-7) 



1 for floors in places of public assembly, for live loads 
in excess of 100 pounds per square foot (4.79 kN/m 2 ) , 
and for parking garage live load, and 

= 0.5 for other live loads. 

f 2 = 0.7 for roof configurations (such as saw tooth) that do 
not shed snow off the structure, and 

= 0.2 for other roof configurations. 

Exception: Where other factored load combinations are 
specifically required by the provisions of this code, such 
combinations shall take precedence. 

1605.2.2 Flood loads. Where flood loads, Fa' are to be con- 
sidered in the design, the load combinations of Section 2.3.3 
ofASCE7shallbeused. 

1605.3 Load combinations using allowable stress design. 

1605.3.1 Basic load combinations. Where allowable stress 
design (working stress design), as permitted by this code, is 
used, structures and portions thereof shall resist the most 
critical effects resulting from the following combinations of 
loads: 



D + F 

D+H+F+L+ T 

D+H+F+ (LrorSorR) 

D+ H+ F+ 0.75(L+ 1) + 
0.75(L r orSorR) 

D+H+F+ (WorOJE) 

D+ H+ F+ 0.7 5( WorOJE) + 
0.75L+0.75(L r orSorR) 

0.6D+ W+H 

0.6D+ 0.7 E+ H 



(Equation 16-8) 

(Equation 16-9) 

(Equation 16-10) 

(Equation 16-11) 
(Equation 16-12) 

(Equation 16-13) 
(Equation 16-14) 
(Equation 16-15) 



Exceptions: 

1. Crane hook loads need not be combined with roof 
live load or with more than three-fourths of the 
snow load or one-half of the wind load. 

2. Flatroof snow loads of 30 psf (1.44 kN/m 2 ) or less 
and roof live loads of 30 psf or less need not be 
combined with seismic loads. Where flat roof 
snow loads exceed 30 psf (1.44 kN/m 2 ), 20 percent 
shall be combined with seismic loads. 

1605.3.1.1 Stress increases. Increases in allowable 
stresses specified in the appropriate material chapter or 
the referenced standards shall not be used with the load 
combinations of Section 1605.3.1, except that increases 
shall be permitted in accordance with Chapter 23. 

1605.3.1.2 Flood loads. Where flood loads, Fa' are to be 
considered in design, the load combinations of Section 
2.4.2 of ASCE 7 shall be used. 



308 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



1605.3.2 Alternative basic load combinations. In lieu of the 
basic load combinations specified in Section 1605.3.1, struc- 
tures and portions thereof shall be permitted to be designed for 
the most critical effects resulting from the following combina- 
tions. When using these alternative basic load combinations 
that include wind or seismic loads, allowable stresses are per- 
mitted to be increased or load combinations reduced where 
permitted by the material chapter of this code or the referenced 
standards. For load combinations that include the counteract- 
ing effects of dead and wind loads, only two-thirds of the mini- 
mum dead load likely to be in place during a design wind event 
shall be used. Where wind loads are calculated in accordance 
with Chapter 6 of ASCE 7, the coefficient (D in the following 
equations shall be taken as 1.3. For other wind loads, go shall be 
taken as 1. When using these alternative load combinations to 
evaluate sliding, overturning and soil bearing at the soil-struc- 
ture interface, the reduction of foundation overturning from 
Section 12.13.4 in ASCE 7 shall not be used. When using these 
alternative basic load combinations for proportioning founda- 
tions for loadings, which include seismic loads, the vertical 
seismic load effect, E^ in Equation 12.4-4 of ASCE 7 is permit- 
ted to be taken equal to zero. 



D+L+ (LrorSOrR) 

D+L+(cdW) 

D+L+ oW+5/2 

D+L+S+coW/2 

D+L+5+E/L4 

0.9D+E/L4 



(Equation 16-16) 
(Equation 16-17) 
(Equation 16-18) 
(Equation 16-19) 
(Equation 16-20) 
(Equation 16-21) 



Exceptions: 

1 . Crane hook loads need not be combined with roof live 
loads or with more than three-fourths of the snow load 
or one-half of the wind load. 

2. Flatroofsnowloadsof30psf (1.44 kN/m 2 ) or less and 
roof live loads of 30 psf or less need not be combined 
with seismic loads. Where flat roof snow loads 
exceed 30 psf (1.44 kN/m 2 ), 20 percent shall be com- 
bined with seismic loads. 

1605.3.2.1 Other loads. Where F, Hoy Tare to be con- 
sidered in the design, each applicable load shall be added 
to the combinations specified in Section 1605.3.2. 

1605.4 Heliports and helistops. Heliport and helistop landing 
areas shall be designed for the following loads, combined in 
accordance with Section 1605: 

1. Dead load, D, plus the gross weight of the helicopter, D h , 
plus snow load, 5. 

2. Dead load, D, plus two single concentrated impact loads, 
L, approximately 8 feet (2438 mm) apart applied any- 
where on the touchdown pad (representing each of the 
helicopter's two main landing gear, whether skid type or 
wheeled type), having a magnitude of 0.75 times the 
gross weight of the helicopter. Both loads acting together 
total 1.5 times the gross weight of the helicopter. 



3. Dead load, D, plus a uniform live load, L, of 100 psf (4.79 
kN/m 2 ). 

Exception: Landing areas designed for helicopters with 
gross weights not exceeding 3,000 pounds (13.34 kN) in 
accordance with Items 1 and 2 shall be permitted to be 
designed using a 40 psf (1.92 kN/m 2 ) uniform live load in 
Item 3, provided the landing area is identified with a 3,000- 
pound (13.34 kN) weight limitation. This 40 psf (1.92 
kN/m 2 ) uniform live load shall not be reduced. The landing 
area weight limitation shall be indicated by the numeral "3" 
(kips) located in the bottom right corner of the landing area 
as viewed from the primary approach path. The indication 
for the landing area weight limitation shall be a minimum 5 
feet (1524 mm) in height. 



SECTION 1606 
DEAD LOADS 

1606.1 General. Dead loads are those loads defined in Section 
1602.1. Dead loads shall be considered permanent loads. 

1606.2 Design dead load. For purposes of design, the actual 
weights of materials of construction and fixed service equip- 
ment shall be used. In the absence of definite information, val- 
ues used shall be subject to the approval of the building official 

SECTION 1607 
LIVE LOADS 

1607.1 General. Live loads are those loads defined in Section 
1602.1. 

1607.2 Loads not specified. For occupancies or uses not des- 
ignated in Table 1607.1, the live load shall be determined in 
accordance with a method approvedby the building official. 

1607.3 Uniform live loads. The live loads used in the design of 
buildings and other structures shall be the maximum loads 
expected by the intended use or occupancy but shall in no case 
be less than the minimum uniformly distributed unit loads 
required by Table 1607.1. 

1607.4 Concentrated loads. Floors and other similar surfaces 
shall be designed to support the uniformly distributed live 
loads prescribed in Section 1607.3 or the concentrated load, in 
pounds (kilonewtons), given in Table 1607.1, whichever pro- 
duces the greater load effects. Unless otherwise specified, the 
indicated concentration shall be assumed to be uniformly dis- 
tributed over an area 2V 2 feet by 2V 2 feet [6V 4 square feet (0.58 
m 2 )] and shall be located so as to produce the maximum load 
effects in the structural members. 

1607.5 Partition loads. In office buildings and in other build- 
ings where partition locations are subject to change, provisions 
for partition weight shall be made, whether or not partitions are 
shown on the construction documents, unless the specified live 
load exceeds 80 psf (3.83 kN/m 2 ). The partition load shall not 
be less than a uniformly distributed live load of 15 psf (0.74 
kN/m 2 ). 



2009 INTERNATIONAL BUILDING CODE® 



309 



STRUCTURAL DESIGN 



TABLE 1607.1 
MINIMUM UNIFORMLY DISTRIBUTED 
MINIMUM CONCENTRATED 



LIVE LOADS, LeY AND 
LIVE LOADS9 



TABLE 1607.1 -continued 
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L Q ' AND I 

MINIMUM CONCENTRATED LIVE LOADS9 





OCCUPANCY OR USE 


UNIFORM 
(pSt) 


CONCENTRATED 
(lbs.) 




1. Apartments (see residential) 








2. Access floor systems 
Office use 
Computer use 


50 
100 


2,000 
2,000 




3. Armories and drill rooms 


150 


- 


I 


4. Assembly areas and theaters 
Fixed seats (fastened to floor) 
Follow spot, projections and control 

rooms 
Lobbies 
Movable seats 
Stages and platforms 
Other assembly areas 


60 

50 
100 
100 
125 
100 




T 


5. Balconies (exterior) and decks h 


Same as 

occupancy 

served 


- 




6. Bowling alleys 


75 


- 




7. Catwalks 


40 


300 




8. Cornices 


60 






9. Corridors , except as otherwise indicated 


100 




• 


10. Dance halls and ballrooms 


100 


- 


11 . Dining rooms and restaurants 


100 


- 




12. Dwellings (see residential) 


- 


- 




13. Elevator machine room grating 
(on area of 4 in 2 ) 




300 




14. Finish light floor plate construction 
(on area of 1 in^) 




200 




15. Fire escapes 

On single-family dwellings only 


100 

40 


- 




16. Garages (passenger vehicles only) 
Trucks and buses 


40 
SeeSe 


Note a 
ction 1607.6 




17. Grandstands 

(see stadium and arena bleachers) 








18. Gymnasiums , main floors and balconies 


100 






19. Handrails, guards and grab bars 


SeeSe 


ction 1607.7 




20. Hospitals 

Corridors above first floor 
Operating rooms, laboratories 
Patient rooms 


80 
60 

40 


1,000 
1,000 
1,000 




21 . Hotels (see residential) 








22. Libraries 

Corridors above first floor 
Reading rooms 
Stack rooms 


80 
60 
150 b 


1,000 
1,000 
1,000 



OCCUPANCY OR USE 


UNIFORM 
(pst) 


CONCENTRATED 
(lbs.) 


23 . Manufacturing 
Heavy 
Light 


250 
125 


3,000 
2,000 


24. Marquees 


75 




25. Office buildings 

Corridors above first floor 

File and computer rooms shall be 
designed for heavier loads based 
on anticipated occupancy 

Lobbies and first-floor corridors 

Offices 


80 

100 
50 


2,000 

2,000 
2,000 


26. Penal institutions 
Cell blocks 
Corridors 


40 
100 




27. Residential 

One- and two-family dwellings 

Uninhabitable attics without storage 1 
Uninhabitable attics with limited 

storagei, j , k 
Habitable attics and sleeping areas 
All other areas 
Hotels and multifamily dwellings 
Private rooms and corridors 

serving them 
Public rooms and corridors serving 
them 


10 
20 

30 

40 

40 
100 


- 


28. Reviewing stands, grandstands and 
bleachers 


Note c 


29. Roofs 

All roof surfaces subject to maintenance 

workers 
Awnings and canopies 

Fabric construction supported by a 

lightweight rigid skeleton structure 

All other construction 

Ordinary flat, pitched, and curved roofs 

Primary roof members, exposed to a 

work floor 

Single panel point of lower chord of 
roof trusses or any point along 
primary structural members 
supporting roofs: 

Over manufacturing, storage 
warehouses, and repair 
garages 
All other occupancies 
Roofs used for other special purposes 
Roofs used for promenade purposes 
Roofs used for roof gardens or 
assembly purposes 


5 

nonreducible 

20 

20 

Note 1 
60 
100 


300 

2,000 

300 

Note 1 


30. Schools 

Classrooms 

Corridors above first floor 

First-floor corridors 


40 
80 
100 


1,000 
1,000 
1,000 


31 . Scuttles, skylight ribs and accessible 
ceilings 




200 


32. Sidewalks, vehicular driveways and 
yards, subject to trucking 


250 d 


8,000e 


33. Skating rinks 


100 


- 



I 



continued 



continued 



310 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



TABLE 1607.1 -continued 
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS, L 
MINIMUM CONCENTRATED LIVE LOADS9 



AND 



OCCUPANCY OR USE 


UNIFORM 
(pst) 


CONCENTRATED 
(lbs.) 


34. Stadiums and arenas 
Bleachers 
Fixed seats (fastened to floor) 


100 e 
60 e 




35. Stairs and exits 

One- and two-family dwellings 
All other 


40 
100 


Notef 


36. Storage warehouses 

(shall be designed for heavier loads if 
required for anticipated storage) 
Heavy 
Light 


250 
125 




37. Stores 

Retail 

First floor 
Upper floors 

Wholesale, all floors 


100 

75 
125 


1,000 
1,000 
1,000 


38. Vehicle barrier systems 


See Section 1607.7.3 


39. Walkways and elevated platforms 
(other than exitways) 


60 


- 


40. Yards and terraces, pedestrians 


100 





I 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm 2 , 
1 square foot = 0.0929 m 2 . 

1 pound per square foot = 0.0479 kN/m 2 , 1 pound = 0.004448 kN, 
1 pound per cubic foot = 16 kg/m 3 

a. Floors in garages or portions of buildings used for the storage of motor vehicles shall be 
designed for the uniformly distributed live loads of Table 1607. 1 or the following con- 
centrated loads: (1) for garages restricted to passenger vehicles accommodating not 
more than nine passengers, 3,000 pounds acting on an area of 4.5 inches by 4.5 inches; 
(2) for mechanical parking structures without slab or deck which are used for storing 
passenger vehicles only, 2,250 pounds per wheel. 

b. The loading applies to stack room floors that support nonmobile, double-faced library 
bookstacks, subject to the following limitations: 

1. The nominal bookstack unit height shall not exceed 90 inches; 

2. The nominal shelf depth shall not exceed 12 inches for each face ; and 

3. Parallel rows of double-faced bookstacks shall be separated by aisles not less 
than 36 inches wide. 

c. Design in accordance with the ICC 300. 

d. Other uniform loads in accordance with an approved method which contains provisions 
for truck loadings shall also be considered where appropriate . 

e. The concentrated wheel load shall be applied on an area of 4.5 inches by 4.5 inches. 

f . Minimum concentrated load on stair treads (on area of 4 square inches) is 300 pounds . 

g. Where snow loads occur that are in excess of the design conditions, the structure shall 
be designed to support the loads due to the increased loads caused by drift buildup or a 
greater snow design determined by the building official (see Section 1608) . For spe- 
Cial-purpose roofs, see Section 1607.11.2.2. 

h. See Section 1604.8.3 for decks attached to exterior walls. 

Attics without storage are those where the maximum clear height between thejoist and 
rafter is less than 42 inches, or where there are not two or more adjacent trusses with the 
same web configuration capable of containing a rectangle 42 inches high by 2 feet 
wide, or greater, located within the plane of the truss . For attics without storage, this live 
load need not be assumed to act concurrently with any other live load requirements, 
j . For attics with limited storage and constructed with trusses, this live load need only be 
applied to those portions of the bottom chord where there are two or more adjacent 
trusses with the same web configuration capable of containing a rectangle 42 inches 
high by 2 feet wide or greater, located within the plane of the truss. The rectangle shall 
fit between the top of the bottom chord and the bottom of any other truss member, pro- 
vided that each of the following criteria is met: 

i. The attic area is accessible by a pull-down stairway or framed opening in accor- 
dance with Section 1209.2, and 
ii. The truss shall have a bottom chord pitch less than 2:12. 

iii. Bottom chords of trusses shall be designed for the greater of actual imposed dead 
load or 10 psf, uniformly distributed over the entire span, 
k. Attic spaces served by a fixed stair shall be designed to support the minimum live load 

specified for habitable attics and sleeping rooms. 
1. Roofs used for other special purposes shall be designed for appropriate loads as 
approved by the building official. 



1607.6 Truck and bus garages. Minimum live loads for 
garages having trucks or buses shall be as specified in Table 
1607.6, but shall not be less than 50 psf (2.40 kN/m 2 ), unless 
other loads are specifically] ustified and approvedby the build- 
ing official Actual loads shall be used where they are greater 
than the loads specified in the table. 

1607.6.1 Truck and bus garage live load application. The 
concentrated load and uniform load shall be uniformly dis- 
tributed over a 10-foot (3048 mm) width on a line normal to 
the centerline of the lane placed within a 12-foot-wide 
(3658 mm) lane. The loads shall be placed within their indi- 
vidual lanes so as to produce the maximum stress in each 
structural member. Single spans shall be designed for the 
uniform load in Table 1607.6 and one simultaneous concen- 
trated load positioned to produce the maximum effect. Mul- 
tiple spans shall be designed for the uniform load in Table 
1607.6 on the spans and two simultaneous concentrated 
loads in two spans positioned to produce the maximum neg- 
ative moment effect. Multiple span design loads, for other 
effects, shall be the same as for single spans. 

TABLE 1607.6 
UNIFORM AND CONCENTRATED LOADS 



LOADING 
CLASS 3 


UNIFORM LOAD 

(pounds/linear 

foot of lane) 


CONCENTRATED LOAD 
(pounds)b 


For moment 
design 


For shear 
design 


H20-44 and HS20-44 


640 


18,000 


26,000 


H15-44 andHS15-44 


480 


13,500 


19,500 



For SI : 1 pound per linear foot = 0.01459 kNIm, 1 pound = 0.004448 kN, 
1 ton = 8.90 kN. 

a. An H loading class designates a two-axle truck with a semitrailer. An HS 
loading class designates a tractor truck with a semitrailer. The numbers fol- 
lowing the letter classification indicate the gross weight in tons of the stan- 
dard truck and the year the loadings were instituted. 

b. See Section 1607.6.1 for the loading of multiple spans. 

1607.7 Loads on handrails, guards, grab bars, seats and 
vehicle barrier systems. Handrails, guards, grab bars, acces- 
sible seats, accessible benches and vehicle barrier systems 
shall be designed and constructed to the structural loading con- 
ditions set forth in this section. 

1607.7.1 Handrails and guards. Handrails and guards 
shall be designed to resist a load of 50 pounds per linear foot 
(plf) (0.73 kN/m) applied in any direction at the top and to 
transfer this load through the supports to the structure. Glass 
handrail assemblies and guards shall also comply with Sec- 
tion 2407. 

Exceptions: 

1. For one- and two-family dwellings, only the single 
concentrated load required by Section 1607.7.1.1 
shall be applied. 

2. In Group 1-3, F, Hand S occupancies, for areas that 
are not accessible to the general public and that 
have an occupant loadless than 50, the minimum 
load shall be 20 pounds per foot (0.29 kN/m). 

1607.7.1.1 Concentrated load. Handrails and guards 
shall be able to resist a single concentrated load of 200 
pounds (0.89 kN), applied in any direction at any point 



i 



2009 INTERNATIONAL BUILDING CODE® 



311 



STRUCTURAL DESIGN 



along the top, and to transfer this load through the sup- 
ports to the structure. This load need not be assumed to 
act concurrently with the loads specified in Section 
1607.7.1. 

1607.7.1.2 Components. Intermediate rails (all those 
except the handrail), balusters and panel fillers shall be 
designed to withstand a horizontally applied normal load 
of 50 pounds (0.22 kN) on an area equal to 1 square foot 
(0.093 m 2 ), including openings and space between rails. 
Reactions due to this loading are not required to be 
superimposed with those of Section 1607.7.1 or 
1607.7.1.1. 

1607.7.2 Grab bars, shower seats and dressing room 
bench seats. Grab bars, shower seats and dressing room 
bench seat systems shall be designed to resist a single con- 
centrated load of 250 pounds (1.11 kN) applied in any direc- 
tion at any point. 

1607.7.3 Vehicle barrier systems. Vehicle barrier systems 
for passenger vehicles shall be designed to resist a single 
load of6,000 pounds (26.70 kN) applied horizontally in any 
direction to the barrier system and shall have anchorage or 
attachment capable of transmitting this load to the structure. 
For design of the system, two loading conditions shall be 
analyzed. The first condition shall apply the load at a height 
of 1 foot, 6 inches (457 mm) above the floor or ramp surface. 
The second loading condition shall apply the load at 2 feet, 3 
inches (686 mm) above the floor or ramp surface. The more 
severe load condition shall govern the design of the barrier 
restraint system. The load shall be assumed to act on an area 
not to exceed 1 square foot (0.0929 m 2 ) , and is not required 
to be assumed to act concurrently with any handrail or guard 
loadings specified in Section 1607.7.1. Garages accommo- 
dating trucks and buses shall be designed in accordance 
with an approv edmethod that contains provisions for traffic 
railings. 

1607.8 Impact loads. The live loads specified in Section 
1607.3 include allowance for impact conditions. Provisions 
shall be made in the structural design for uses and loads that 
involve unusual vibration and impact forces. 

1607.8.1 Elevators. Elevator loads shall be increased by 
100 percent for impact and the structural supports shall be 
designed within the limits of deflection prescribed by 
ASMEA17.1. 

1607.8.2 Machinery. For the purpose of design, the weight 
of machinery and moving loads shall be increased as fol- 
lows to allow for impact: (1) elevator machinery, 100 per- 
cent; (2) light machinery, shaft-or motor-driven, 20 percent; 
(3) reciprocating machinery or power-driven units, 50 per- 
cent; (4) hangers for floors or balconies, 33 percent. Per- 
centages shall be increased where specified by the 
manufacturer. 

1607.9 Reduction in live loads. Except for uniform live loads 
at roofs, all other minimum uniformly distributed live loads, La, 
in Table 1607.1 are permitted to be reduced in accordance with 
Section 1607.9.1 or 1607.9.2. Roof uniform live loads, other 
than special purpose roofs of Section 1607.11.2.2, are permit- 



ted to be reduced in accordance with Section 1607.11.2. Roof 
uniform live loads of special purpose roofs are permitted to be 
reduced in accordance with Section 1607.9.1 or 1607.9.2. 

1607.9.1 General. Subject to the limitations of Sections 
1607.9.1.1 through 1607.9.1.4, members for which a value 
of KLLATis 400 square feet (37.16 m 2 ) or more are permitted 
to be designed for a reduced live load in accordance with the 
following equation: 



I 



L= Lo[0.25 + 



For SI: L = La 



15 



4%kLA% 



(Equation 16-22) 



0.25+ 



4.57 



where: 

L = Reduced design live load per square foot (meter) of 
area supported by the member. 

La = Unreduced design live load per square foot (meter) of 
area supported by the member (see Table 1607.1). 

Ki±= Live load element factor (see Table 1607.9.1). 

AT = Tributary area, in square feet (square meters). 

L shall not be less than 0.50L o for members supporting one 
floor and L shall not be less than 0.40L o for members sup- 
porting two or more floors. 

TABLE 1607.9.1 
LIVE LOAD ELEMENT FACTOR, K^ 



ELEMENT 


Kll 


Interior columns 

Exterior columns without cantilever slabs 


4 
4 


Edge columns with cantilever slabs 


3 


Corner columns with cantilever slabs 
Edge beams without cantilever slabs 
Interior beams 


2 
2 
2 


All other members not identified above including: 
Edge beams with cantilever slabs 
Cantilever beams 
One-way slabs 
Two-way slabs 

Members without provisions for continuous shear 
transfer normal to their span 


1 



1607.9.1.1 One-way slabs. The tributary area, A T , for 
use in Equation 16-22 for one-way slabs shall not exceed 
an area defined by the slab span times a width normal to 
the span of 1.5 times the slab span. 

1607.9.1.2 Heavy live loads. Live loads that exceed 100 
psf (4.79 kN/m 2 ) shall not be reduced. 

Exceptions: 

1. The live loads for members supporting two or 
more floors are permitted to be reduced by a 
maximum of 20 percent, but the live load shall 



312 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



not be less than 
1607.9.1. 



L as calculated in Section 



1 



i 



2. For uses other than storage, where approved, 
additional live load reductions shall be permit- 
ted where shown by the registered design pro- 
fessional that a rational approach has been used 
and that such reductions are warranted. 

1607.9.1.3 Passenger vehicle garages. The live loads 
shall not be reduced in passenger vehicle garages. 

Exception: The live loads for members supporting 
two or more floors are permitted to be reduced by a 
maximum of 20 percent, but the live load shall not be 
less than L as calculated in Section 1607.9.1. 

1607.9.1.4 Group A occupancies. Live loads of lOOpsf 
(4.79 kN/m 2 ) and at areas where fixed seats are located 
shall not be reduced in Group A occupancies. 

1607.9.1.5 Roof members. Live loads of 100 psf (4.79 
kN/m 2 ) or less shall not be reduced for roof members 
except as specified in Section 1607.11.2. 

1607.9.2 Alternate floor live load reduction. As an alter- 
native to Section 1607.9.1, floor live loads are permitted to 
be reduced in accordance with the following provisions. 
Such reductions shall apply to slab systems, beams, girders, 
columns, piers, walls and foundations. 

1. A reduction shall not be permitted in Group A occu- 
pancies. 

2. A reduction shall not be permitted where the live load 
exceeds 100 psf (4.79 kN/m 2 ) except that the design 
live load for members supporting two or more floors 
is permitted to be reduced by 20 percent. 

Exception: For uses other than storage, where 
approved, additional live load reductions shall be 
permitted where shown by the registered design 
professionalthat a rational approach has been used 
and that such reductions are warranted. 

3. A reduction shall not be permitted in passenger vehi- 
cle parking garages except that the live loads for 
members supporting two or more floors are permitted 
to be reduced by a maximum of 20 percent. 

4. For live loads not exceeding 100 psf (4.79 kN/m 2 ) , the 
design live load for any structural member supporting 
150 square feet (13.94 m 2 ) or more is permitted to be 
reduced in accordance with Equation 16-23. 

5. For one-way slabs, the area, A, for use in Equation 
16-23 shall not exceed the product of the slab span 
and a width normal to the span of 0.5 times the slab 
span. 

R =0.08(A -150) (Equation 16-23) 

For SI: R= 0.861 (A - 13.94) 

Such reduction shall not exceed the smallest of: 

1. 40 percent for horizontal members; 

2. 60 percent for vertical members; or 



3. R as determined by the following equation. 
R= 23.1 (1 + D/L a) (Equation 16-24) 



where: 



D 



La 



R 



Area of floor supported by the member, 
square feet (m 2 ). 

Dead load per square foot (m 2 ) of area sup- 
ported. 

Unreduced live load per square foot (m 2 ) of 
area supported. 

Reduction in percent. 



1607. 10 Distribution of floor loads. Where uniform floor live 
loads are involved in the design of structural members arranged 
so as to create continuity, the minimum applied loads shall be 
the full dead loads on all spans in combination with the floor 
live loads on spans selected to produce the greatest effect at 
each location under consideration. It shall be permitted to 
reduce floor live loads in accordance with Section 1607.9. 

1607.11 Roof loads. The structural supports of roofs and mar- 
quees shall be designed to resist wind and, where applicable, 
snow and earthquake loads, in addition to the dead load of con- 
struction and the appropriate live loads as prescribed in this 
section, or as set forth in Table 1607.1. The live loads acting on 
a sloping surface shall be assumed to act vertically on the hori- 
zontal projection of that surface. 

1607.11.1 Distribution of roof loads. Where uniform roof 
live loads are reduced to less than 20 psf (0.96 kN/m 2 ) in 
accordance with Section 1607.11.2.1 and are applied to the 
design of structural members arranged so as to create conti- 
nuity' the reduced roof live load shall be applied to adjacent 
spans or to alternate spans, whichever produces the most 
unfavorable load effect. See Section 1607.11.2 for reduc- 
tions in minimum roof live loads and Section 7.5 of ASCE 7 
for partial snow loading. 

1 607. 11.2 Reduction in roof live loads. The minimum uni- 
formly distributed live loads of roofs and marquees, La' in 
Table 1607. 1 are permitted to be reduced in accordance with 
Section 1607.11.2.1 or 1607.11.2.2. 

1607.11.2.1 Flat, pitched and curved roofs. Ordinary 
flat, pitched and curved roofs, and awnings and canopies 
other than of fabric construction supported by light- 
weight rigid skeleton structures, are permitted to be 
designed for a reduced roof live load as specified in the 
following equations or other controlling combinations of 
loads in Section 1605, whichever produces the greater 
load. In structures such as greenhouses, where special 
scaffolding is used as a work surface for workers and 
materials during maintenance and repair operations, a 
lower roof load than specified in the following equations 
shall not be used unless approvedby the building official. 
Such structures shall be designed for a minimum roof 
live load of 12 psf (0.58 kN/m 2 ). 



L r =L RjR 2 
where: 12</_ r <20 



(Equation 16-25) 



2009 INTERNATIONAL BUILDING CODE® 



313 



STRUCTURAL DESIGN 



For SI: L r = LJZft? 
where: 0.58 < L r < 0.96 

L r = Reduced live load per square foot (m 2 ) of horizon- 
tal projection in pounds per square foot (kN/m 2 ). 

The reduction factors Rj and R 2 shall be determined as 
follows: 



Rj = 1 for At< 200 square feet 
(18.58 m 2 ) 



(Equation 16-26) 



Rj = 1.2 - O.OOIA t for 200 square 

feet < At< 600 square feet (Equation 16-27) 

For SI: 1.2- O.OIIAJor 18.58 square meters < A t < 55.74 
square meters 



Rj = 0.6 for At> 600 square feet 

(55.74 m 2 ) 

where: 



(Equation 16-28) 



At = Tributary area (span length multiplied by effective 
width) in square feet (m 2 ) supported by any struc- 
tural member, and 



R 2 =MorF<4 

R 2 =12- 0.05 Ffor4<F< 12 

R 2 =0.6forF>12 



(Equation 16-29) 
(Equation 16-30) 
(Equation 16-31) 



where: 

F = For a sloped roof, the number of inches of rise per 
foot (for SI: F=0.12 x slope, with slope expressed 
as a percentage), or for an arch or dome, the 
rise-to-span ratio multiplied by 32. 

1607.11.2.2 Special-purpose roofs. Roofs used for 
promenade purposes, roof gardens, assembly purposes 
or other special purposes, and marquees, shall be 
designed for a minimum live load, La' as specified in 
Table 1607.1. Such live loads are permitted to be reduced 
in accordance with Section 1607.9. Live loads of 100 psf 
(4.79 kN/m 2 ) or more at areas of roofs classified as 
Group A occupancies shall not be reduced. 

1607.11.3 Landscaped roofs. Where roofs are to be land- 
scaped' the uniform design live load in the landscaped area 
shall be 20 psf (0.958 kN/m 2 ). The weight of the landscap- 
ing materials shall be considered as dead load and shall be 
computed on the basis of saturation of the soil. 

1607.11.4 Awnings and canopies. Awnings and canopies 
shall be designed for uniform live loads as required in Table 
1607.1 as well as for snow loads and wind loads as specified 
in Sections 1608 and 1609. 

1607.12 Crane loads. The crane live load shall be the rated 
capacity of the crane. Design loads for the runway beams, 
including connections and support brackets, of moving bridge 
cranes and monorail cranes shall include the maximum wheel 



loads of the crane and the vertical impact, lateral and longitudi- 
nal forces induced by the moving crane. 

1607.12.1 Maximum wheel load. The maximum wheel 
loads shall be the wheel loads produced by the weight of the 
bridge, as applicable, plus the sum of the rated capacity and 
the weight of the trolley with the trolley positioned on its 
runway at the location where the resulting load effect is 
maximum. 

1607.12.2 Vertical impact force. The maximum wheel 
loads of the crane shall be increased by the percentages 
shown below to determine the induced vertical impact or 
vibration force: 



Monorail cranes (powered) 

Cab-operated or remotely operated 
bridge cranes (powered)- .... 

Pendant-operated bridge cranes 
(powered) 

Bridge cranes or monorail cranes with 
hand-geared bridge, trolley and hoist . . 



25 percent 



25 percent 
10 percent 

. percent 

1607.12.3 Lateral force. The lateral force on crane runway 
beams with electrically powered trolleys shall be calculated 
as 20 percent of the sum of the rated capacity of the crane 
and the weight of the hoist and trolley. The lateral force shall 
be assumed to act horizontally at the traction surface of a 
runway beam, in either direction perpendicular to the beam, 
and shall be distributed according to the lateral stiffness of 
the runway beam and supporting structure. 

1607.12.4 Longitudinal force. The longitudinal force on 
crane runway beams, except for bridge cranes with 
hand-geared bridges, shall be calculated as 10 percent of the 
maximum wheel loads of the crane. The longitudinal force 
shall be assumed to act horizontally at the traction surface of 
a runway beam, in either direction parallel to the beam. 

1607.13 Interior walls and partitions. Interior walls and par- 
titions that exceed 6 feet (1829 mm) in height, including their 
finish materials, shall have adequate strength to resist the loads 
to which they are subjected but not less than a horizontal load of 
5 psf (0.240 kN/m 2 ). 

Exception: Fabric partitions complying with Section 
1607.13.1 shall not be required to resist the minimum hori- 
zontalload of 5 psf (0.24 kN/m 2 ). 

1607.13.1 Fabric partitions. Fabric partitions that exceed 6 
feet (1829 mm) in height, including their finish materials, 
shall have adequate strength to resist the following load con- 
ditions: 

1. A horizontal distributed load of 5 psf (0.24 kN/m 2 ) 
applied to the partition framing. The total area used to 
determine the distributed load shall be the area of the 
fabric face between the framing members to which 
the fabric is attached. The total distributed load shall 
be uniformly applied to such framing members in 
proportion to the length of each member. 



314 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



2. A concentrated load of 40 pounds (0.176 kN) applied 
to an 8 -inch diameter (203 mm) area [50.3 square 
inches (32 452 mm 2 )] of the fabric face at a height of 
54 inches (1372 mm) above the floor. 



SECTION 1608 
SNOW LOADS 

1608.1 General. Design snow loads shall be determined in 
accordance with Chapter 7 of ASCE 7, but the design roof load 
shall not be less than that determined by Section 1607. 

1608.2 Ground snow loads. The ground snow loads to be used 
in determining the design snow loads for roofs shall be deter- 
mined in accordance with ASCE 7 or Figure 1608.2 for the 
contiguous United States and Table 1608.2 for Alaska. 
Site-specific case studies shall be made in areas designated 
"CS" in Figure 1608.2. Ground snow loads for sites at eleva- 
tions above the limits indicated in Figure 1608.2 and for all 
sites within the CS areas shall be approved. Ground snow load 
determination for such sites shall be based on an extreme value 
statistical analysis of data available in the vicinity of the site 
using a value with a 2-percent annual probability of being 
exceeded (50-year mean recurrence interval). Snow loads are 
zero for Hawaii, except in mountainous regions as approve dby 
the building official. 



SECTION 1609 
WIND LOADS 

1609.1 Applications. Buildings, structures and parts thereof 
shall be designed to withstand the minimum wind loads pre- 



scribed herein. Decreases in wind loads shall not be made for 
the effect of shielding by other structures. 

1609.1.1 Determination of wind loads. Wind loads on 
every building or structure shall be determined in accor- 
dance with Chapter 6 of ASCE 7 or provisions of the alter- 
nate all-heights method in Section 1609.6. The type of 
opening protection required, the basic wind speed and the 
exposure category for a site is permitted to be determined in 
accordance with Section 1609 or ASCE 7. Wind shall be 
assumed to come from any horizontal direction and wind 
pressures shall be assumed to act normal to the surface con- 
sidered. 

Exceptions: 

1. Subject to the limitations of Section 1609.1.1.1, 
the provisions of ICC 600 shall be permitted for 
applicable Group R-2 and R-3 buildings. 

2. Subject to the limitations of Section 1609.1.1.1, 
residential structures using the provisions of the 
AF&PA WFCM. 

3. Subject to the limitations of Section 1609.1.1.1, 
residential structures using the provisions of AISI 
S230. 

4. Designs using NAAMM FP 1001. 

5. Designs using TIA-222 for antenna- supporting 
structures and antennas. 

6. Wind tunnel tests in accordance with Section 6.6 
of ASCE 7, subject to the limitations in Section 
1609.1.1.2. 



i 





TABLE 1608.2 
GROUND SNOW LOADS P . FOR ALASKAN LOCATIONS 




LOCATION 


POUNDS PER 

SQUARE FOOT 


LOCATION 


POUNDS PER 

SQUARE FOOT 


LOCATION 


POUNDS PER 

SQUARE FOOT 


Adak 


30 


Galena 


60 


Petersburg 


150 


Anchorage 


50 


Gulkana 


70 


St. Paul Islands 


40 


Angoon 


70 


Homer 


40 


Seward 


50 


Barrow 


25 


Juneau 


60 


Shemya 


25 


Barter Island 


35 


Kenai 


70 


Sitka 


50 


Bethel 


40 


Kodiak 


30 


Talkeetna 


120 


Big Delta 


50 


Kotzebue 


60 


Unalakleet 


50 


Cold Bay 


25 


McGrath 


70 


Valdez 


160 


Cordova 


100 


Nenana 


80 


Whittier 


300 


Fairbanks 


60 


Nome 


70 


Wrangell 


60 


Fort Yukon 


60 


Palmer 


50 


Yakutat 


150 



For 51 : 1 pound per square foot = 0.0479 kN/m • 



2009 INTERNATIONAL BUILDING CODE® 



315 



STRUCTURAL DESIGN 



(200) 

l io' 

(100) 

9 



10 
(300) 




In CS areas, site-specific Case Studies are required to 
establish ground snow loads. Extreme local variations in 
ground snow loads in these areas preclude mapping at 
this scale. 

Numbers in parentheses represent the upper elevation 
limits in feet for the ground snow load values presented 
below. Site -specific case studies are required to estab- 
lish ground snow loads at elevations not covered. 

To convert Ib/sq ft to kNm 2 , multiply by 0.0479. 

To convert feet to meters, multiply by 0.3048. 



100 



200 



300 miles 



FIGURE 1608.2 
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (pst) 



316 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



(600) 




FIGURE 1608.2-continued 
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (pst) 



2009 INTERNATIONAL BUILDING CODE® 



317 



STRUCTURAL DESIGN 



1609.1.1.1 Applicability. The provisions of ICC 600 are 
applicable only to buildings located within Exposure B 
or C as defined in Section 1609.4. The provisions of ICC 
600, AF&PA WFCM and AISI S230 shall not apply to 
buildings sited on the upper half of an isolated hill, ridge 
or escarpment meeting the following conditions: 

1. The hill, ridge or escarpment is 60 feet (18 288 
mm) or higher if located in Exposure B or 30 feet 
(9144 mm) or higher if located in Exposure C; 

2. The maximum average slope of the hill exceeds 10 
percent; and 

3. The hill, ridge or escarpment is unobstructed 
upwind by other such topographic features for a 
distance from the high point of 50 times the height 
of the hill or 1 mile (1.61 km), whichever is 
greater. 

1609.1.1.2 Wind tunnel test limitations. The lower 
limit on pressures for main wind- force-resisting systems 
and components and cladding shall be in accordance 
with Sections 1609.1.1.2.1 and 1609.1.1.2.2. 

1609.1.1.2.1 Lower limits on main 
wind-foree-resisting system. Base overturning 
moments determined from wind tunnel testing shall 
be limited to not less than 80 percent of the design 
base overturning moments determined in accordance 
with Section 6.5 of ASCE 7, unless specific testing is 
performed that demonstrates it is the aerodynamic 
coefficient of the building, rather than shielding from 
other structures, that is responsible for the lower val- 
ues. The 80-percent limit shall be permitted to be 
adjusted by the ratio of the frame load at critical wind 
directions as determined from wind tunnel testing 
without specific adjacent buildings, but including 
appropriate upwind roughness, to that determined in 
Section 6.5 of ASCE 7. 

1609. 1 . 1 .2.2 Lower limits on components and clad- 
ding. The design pressures for components and clad- 
ding on walls or roofs shall be selected as the greater 
of the wind tunnel test results or 80 percent of the 
pressure obtained for Zone 4 for walls and Zone 1 for 
roofs as determined in Section 6.5 of ASCE 7, unless 
specific testing is performed that demonstrates it is 
the aerodynamic coefficient of the building, rather 
than shielding from nearby structures, that is respon- 
sible for the lower values. Alternatively, limited tests 
at a few wind directions without specific adjacent 
buildings, but in the presence of an appropriate 
upwind roughness, shall be permitted to be used to 
demonstrate that the lower pressures are due to the 
shape of the building and not to shielding. 

1609.1.2 Protection of openings. In wind-borne debris 
regions, glazing in buildings shall be impact resistant or pro- 
tected with an impact-resistant covering meeting the 
requirements of an approved impact-resistant standard or 



ASTM E 1996 and ASTM E 1886 referenced herein as fol- 
lows: 

1. Glazed openings located within 30 feet (9144 mm) of 
grade shall meet the requirements of the large missile 
test of ASTM E 1996. 

2. Glazed openings located more than 30 feet (9144 
mm) above grade shall meet the provisions of the 
small missile test of ASTM E 1996. 

Exceptions: 

1. Wood structural panels with a minimum thickness 
of 7/ 16 inch (11.1 mm) and maximum panel span of 
8 feet (2438 mm) shall be permitted for opening 
protection in one- and two- story buildings classi- 
fied as Group R-3 or R-4 occupancy. Panels shall 
be precut so that they shall be attached to the fram- 
ing surrounding the opening containing the prod- 
uct with the glazed opening. Panels shall be 
predrilled as required for the anchorage method 
and shall be secured with the attachment hardware 
provided. Attachments shall be designed to resist 
the components and cladding loads determined in 
accordance with the provisions of ASCE 7, with 
corrosion-resistant attachment hardware provided 
and anchors permanently installed on the building. 
Attachment in accordance with Table 1609.1.2 
with corrosion-resistant attachment hardware pro- 
vided and anchors permanently installed on the 
building is permitted for buildings with a mean 
roof height of 45 feet (13 716 mm) or less where 
wind speeds do not exceed 140 mph (63 m/s). 

2. Glazing in Occupancy Category I buildings as 
defined in Section 1604.5, including greenhouses 
that are occupied for growing plants on a produc- 
tion or research basis, without public access shall 
be permitted to be unprotected. 

3. Glazing in Occupancy Category II, III or IV build- 
ings located over 60 feet (18 288 mm) above the 
ground and over 30 feet (9144 mm) above aggre- 
gate surface roofs located within 1,500 feet (458 
m) of the building shall be permitted to be unpro- 
tected. 

1609.1.2.1 Louvers. Louvers protecting intake and 
exhaust ventilation ducts not assumed to be open that are 
located within 30 feet (9144 mm) of grade shall meet 
requirements of an approved impact-resisting standard 
or the large missile test of ASTM E 1996. 

1609.1.2.2 Garage doors. Garage door glazed opening 
protection for wind-borne debris shall meet the require- 
ments of an approved impact-resisting standard or 
ANSI/DASMA 115. 

1609.2 Definitions. The following words and terms shall, for 
the purposes of Section 1609, have the meanings shown herein. 



318 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



TABLE 1609.1.2 

WIND-BORNE DEBRIS PROTECTION FASTENING 

SCHEDULE FOR WOOD STRUCTURAL PANELS a ,b,c, d 



FASTENER 
TYPE 


FASTENER SPACING (inches) 


Panel Span 
< 4 feet 


4 feet < Panel 
Span < 6 feet 


6 feet < Panel 
Span < 8 feet 


No. 8 wood-screw-based 
anchor with 2-inch 
embedment length 


16 


10 


8 


No. 10 wood-screw-based 
anchor with 2-inch 
embedment length 


16 


12 


9 


i/ 4 - inch diameter 
lag-screw-based anchor 
with 2-inch embedment 
length 


16 


16 


16 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N, 
1 mile per hour = 0.447 m/s. 

a. This table is based on 140 mph wind speeds and a 45-foot mean roof height. 

b. Fasteners shall be installed at opposing ends of the wood structural panel. 
Fasteners shall be located a minimum of 1 inch from the edge of the panel. 

c. Anchors shall penetrate through the exterior wall covering with an 
embedment length of 2 inches minimum into the building frame. Fasteners 
shall be located a minimum of 2 l / 2 inches from the edge of concrete block or 
concrete. 

d. Where panels are attached to masonry or masonry/stucco, they shall be 
attached using vibration-resistant anchors having a minimum ultimate with- 
drawal capacity of 1,500 pounds. 

HURRICANE-PRONE REGIONS. Areas vulnerable to 
hurricanes defined as: 

1. The U. S. Atlantic Ocean and Gulf of Mexico coasts 
where the basic wind speed is greater than 90 mph (40 
m/s) and 

2. Hawaii, Puerto Rico, Guam, Virgin Islands and Ameri- 
can Samoa. 

WIND-BORNE DEBRIS REGION. Portions of hurri- 
cane-prone regions that are within 1 mile (1.61 km) of the 
coastal mean high water line where the basic wind speed is 1 10 
mph (48 m/s) or greater; or portions of hurricane -prone 
regions where the basic wind speed is 120 mph (53 m/s) or 
greater; or Hawaii. 



1609.3 Basic wind speed. The basic wind speed, in mph, for 
the determination of the wind loads shall be determined by Fig- 
ure 1609. Basic wind speed for the special wind regions indi- 
cated' near mountainous terrain and near gorges shall be in 
accordance with local jurisdiction requirements. Basic wind 
speeds determined by the local jurisdiction shall be in accor- 
dance with Section 6.5.4 of ASCE 7. 

In nonhurricane-prone regions, when the basic wind speed is 
estimated from regional climatic data, the basic wind speed 
shall be not less than the wind speed associated with an annual 
probability of 0.02 (50-year mean recurrence interval), and the 
estimate shall be adjusted for equivalence to a 3-second gust 
wind speed at 33 feet (10m) above ground in Exposure Cate- 
gory C. The data analysis shall be performed in accordance 
with Section 6.5.4.2 of ASCE 7. 

1609.3.1 Wind speed conversion. When required, the 
3-second gust basic wind speeds of Figure 1609 shall be 
converted to fastest -mile wind speeds, V fm , using Table 



1609.3.1 or Equation 16-32. 
(^5 -10.5) 



Vfm=. 



where: 



1.05 



(Equation 16-32) 



V 3S = 3-second gust basic wind speed from Figure 1609. 

1609.4 Exposure category. For each wind direction consid- 
ered, an exposure category that adequately reflects the charac- 
teristics of ground surface irregularities shall be determined for 
the site at which the building or structure is to be constructed. 
Account shall be taken of variations in ground surface rough- 
ness that arise from natural topography and vegetation as well 
as from constructed features. 

1609.4.1 Wind directions and sectors. For each selected 
wind direction at which the wind loads are to be evaluated, 
the exposure of the building or structure shall be determined 
for the two upwind sectors extending 45 degrees (0.79 rad) 
either side of the selected wind direction. The exposures in 
these two sectors shall be determined in accordance with 
Sections 1609.4.2 and 1609.4.3 and the exposure resulting 
in the highest wind loads shall be used to represent winds 
from that direction. 











TABLE 1609.3.1 
EQUIVALENT BASIC WIND SPEEDS 3 , b, 


c 










V 3S 


85 


90 


100 


105 


110 


120 


125 


130 


140 


145 


150 


160 


170 


Vim 


71 


76 


85 


90 


95 


104 


109 


114 


123 


128 


133 


142 


152 



For 51: 1 mile per hour = 0.44 m/s. 

a. Linear interpolation is permitted. 

b. V 3S is the 3-second gust wind speed (mph) . 

c. V fm is the fastest mile wind speed (mph). 



2009 INTERNATIONAL BUILDING CODE® 



319 



STRUCTURAL DESIGN 




"15* -148 



FIGURE 1609 
BASIC WIND SPEED (3-SECOND GUST) 



320 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



110(49) 



120(54) 




90(40| 
100(45) 



130(581 



140(63) 



140(63) 
150(67) 



&0{40) 
100(35) /J130(5E) 
110(49) 12€(54) 



I ,oc nt ion 
Hawaii 
Puerto Rico 
Guam 

Virgin Islands 
American Samoa 



Vmp*i (m/s) 
105 (47) 



145 
170 
145 
125 



(65) 
(76) 
(65) 
[56) 



Notes: 

1. Values are nominal design 3-second gustwind speeds in miles per hour (m/s) 
at 33 ft (10 m) above ground for Exposure C category. 

2. Linear Interpolation between wind contours is permitted. 

3. Islands and coastal areas outside the last contour shall use the last wind 
speed contour of the coastal area. 

4. Mountainous terrain, gorges, ocean promontories, and special wind regions 
shall be examined for unusual wind conditions. 

FIGURE 1609-continued 
BASIC WIND SPEED (3-SECOND GUST) 



2009 INTERNATIONAL BUILDING CODE® 



321 



STRUCTURAL DESIGN 




100:<15;. 



130(58) 
|O|4fl)120{5*) 



1KJ(67) 

Notes: 

1 . Va (Lies are nominal de sign 3-seODn c) gutt wind 

speeds in miles per hour (m.'i) at 31 ft (10 rn) 
above ground for Exposure C category. 

2. Linear interpolation between wind contour* It 
permitted. 

3. Islands and coaGlal areas outside- the fast 
contour shall use the iasl wind speed contour 
of Ihe coastal ar**. 
Mountainous terrain, gorees. wean 
prompntori as, and special wsnd ragronfi shall 
be examined for unusual wind conditions, 



FIGURE 1609-continued 

BASIC WIND SPEED (3-SECOND GUST) 

WESTERN GULF OF MEXICO HURRICANE COASTLINE 



322 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



90(40} 



100(4$} 

110449} 

120^54} 
130(58} 



-\ ^130*58) 




.1tt(») 



Special Wind Region 



Notes: 

1. Values are nominal design Second gust wind 
speeds in miles per hour (rry's) at 33 ft (10 m] 
above ground few Exposure C category. 
Linear Interpolation between wind contours is 
permitted. 

I* lands and coastal area* oulslcfB the last 
contour shall use the lest w\r\d speed contour 
of the coastal area 
Mountainous terrain, gorges, ocean 
promontories, and special wind regions ahall 
be examined for unusual wind conditions. 



150{671 



FIGURE 1609-continued 

BASIC WIND SPEED (3-SECOND GUST) 

EASTERN GULF OF MEXICO AND SOUTHEASTERN U.S. HURRICANE COASTLINE 



2009 INTERNATIONAL BUILDING CODE® 



323 



STRUCTURAL DESIGN 




Special Wind Region 



Notes; 

1. Values arc nominal design 3 -second gust wind 
speeds In miles per hour (mi's) at 33 ft [10 m} 
above around for Exposure G category. 

2. Linear Interpolation between wind contours fcs 
permitted. 

Islands and coastal areas outside the last 
contour shall use Die last wind speed contour 
of the co natal arcu 
Mountainous terrain, gorges, ocean 
promo ntorlos, and special wind regions snail 
be examined for unusual wind conditions, 



FIGURE 1609-continued 

BASIC WIND SPEED (3-SECOND GUST) 

MID AND NORTHERN ATLANTIC HURRICANE COASTLINE 



324 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



1609.4.2 Surface roughness categories. A ground surface 
roughness within each 45-degree (0.79 rad) sector shall be 
determined for a distance upwind of the site as defined in 
Section 1609.4.3 from the categories defined below, for the 
purpose of assigning an exposure category as defined in 
Section 1609.4.3. 

Surface Roughness B. Urban and suburban areas, 
wooded areas or other terrain with numerous closely 
spaced obstructions having the size of single-family 
dwellings or larger. 

Surface Roughness C. Open terrain with scattered 
obstructions having heights generally less than 30 feet 
(9144 mm). This category includes flat open country, 
grasslands, and all water surfaces in hurricane-prone 
regions. 

Surface Roughness D. Flat, unobstructed areas and 
water surfaces outside hurricane-prone regions. This 
category includes smooth mud flats, salt flats and unbro- 
ken ice. 

1609.4.3 Exposure categories. An exposure category shall 
be determined in accordance with the following: 

Exposure B. Exposure B shall apply where the ground 
surface roughness condition, as defined by Surface 
Roughness B, prevails in the upwind direction for a dis- 
tance of at least 2,600 feet (792 m) or 20 times the height 
of the building, whichever is greater. 

Exception: For buildings whose mean roof height is 
less than or equal to 30 feet (9144 mm), the upwind dis- 
tance is permitted to be reduced to 1,500 feet (457 m). 

Exposure C. Exposure C shall apply for all cases where 
Exposures B or D do not apply. 

Exposure D. Exposure D shall apply where the ground 
surface roughness, as defined by Surface Roughness D, 
prevails in the upwind direction for a distance of at least 
5,000 feet (1524 m) or 20 times the height of the build- 
ing, whichever is greater. Exposure D shall extend inland 
from the shoreline for a distance of600 feet (183 m) or 20 
times the height of the building, whichever is greater. 

1609.5 Roof systems. 

1609.5.1 Roof deck. The roof deck shall be designed to 
withstand the wind pressures determined in accordance 
with ASCE 7. 

1609.5.2 Roof coverings. Roof coverings shall comply 
with Section 1609.5.1. 

Exception: Rigid tile roof coverings that are air perme- 
able and installed over a roof deck complying with Sec- 
tion 1609.5.1 are permitted to be designed in accordance 
with Section 1609.5.3. 



Asphalt shingles installed over a roof deck complying 
with Section 1609.5.1 shall comply with the wind-resis- 
tance requirements of Section 1507.2.7.1. 

1609.5.3 Rigid tile. Wind loads on rigid tile roof coverings 
shall be determined in accordance with the following equa- 
tion: 



M a =q h C L bLL a [LO-GC p ] 



(Equation 16-33) 



qhCLbLLJ1.0-GC p ] 
1,000 



For SI. Ma = 



where: 

b Exposed width, feet (mm) of the roof tile. 

C L Lift coefficient. The lift coefficient for concrete and 
clay tile shall be 0.2 or shall be determined by test in 
accordance with Section 1716.2. 

GC p = Roof pressure coefficient for each applicable roof 
zone determined from Chapter 6 of ASCE 7. Roof 
coefficients shall not be adjusted for internal pres- 
sure. 



L 
La 



M a 
qh 



Length, feet (mm) of the roof tile. 

Moment arm, feet (mm) from the axis of rotation to 
the point of uplift on the roof tile. The point of uplift 
shall be taken at 0.76L from the head of the tile and 
the middle of the exposed width. For roof tiles with 
nails or screws (with or without a tail clip), the axis 
of rotation shall be taken as the head of the tile for 
direct deck application or as the top edge of the bat- 
ten for battened applications. For roof tiles fastened 
only by a nail or screw along the side of the tile, the 
axis of rotation shall be determined by testing. For 
roof tiles installed with battens and fastened only by 
a clip near the tail of the tile, the moment arm shall 
be determined about the top edge of the batten with 
consideration given for the point of rotation of the 
tiles based on straight bond or broken bond and the 
tile profile. 

Aerodynamic uplift moment, feet-pounds (N-mm) 
acting to raise the tail of the tile. 

Wind velocity pressure, psf (kN/m 2 ) determined 
from Section 6.5.10 of ASCE 7. 



Concrete and clay roof tiles complying with the following 
limitations shall be designed to withstand the aerodynamic 
uplift moment as determined by this section. 

1. The roof tiles shall be either loose laid on battens, 
mechanically fastened, mortar set or adhesive set. 

2. The roof tiles shall be installed on solid sheathing 
which has been designed as components and clad- 
ding. 



2009 INTERNATIONAL BUILDING CODE® 



325 



STRUCTURAL DESIGN 



3. An underlayment shall be installed in accordance 
with Chapter 15. 

4. The tile shall be single lapped interlocking with a 
minimum head lap of not less than 2 inches (51 mm). 

5. The length of the tile shall be between 1.0 and 1.75 
feet (305 mm and 533 mm). 

6. The exposed width of the tile shall be between 0.67 
and 1.25 feet (204 mm and 381 mm). 

7. The maximum thickness of the tail of the tile shall not 
exceed 1.3 inches (33 mm). 

8. Roof tiles using mortar set or adhesive set systems 
shall have at least two-thirds of the tile's area free of 
mortar or adhesive contact. 

1609.6 Alternate all-heights method. The alternate wind 
design provisions in this section are simplifications of the 
ASCE 7 Method 2-Analytical Procedure. 

1609.6.1 Scope. As an alternative to ASCE 7 Section 6.5, 
the following provisions are permitted to be used to deter- 
mine the wind effects on regularly shaped buildings, or 
other structures that are regularly shaped, which meet all of 
the following conditions: 

1. The building or other structure is less than or equal to 
75 feet (22 860 mm) in height with a height- to-least- 
width ratio of 4 or less, or the building or other struc- 
ture has a fundamental frequency greater than or 
equal to 1 hertz. 

2. The building or other structure is not sensitive to 
dynamic effects. 

3. The building or other structure is not located on a site 
for which channeling effects or buffeting in the wake 
of upwind obstructions warrant special consideration. 

4. The building shall meet the requirements of a simple 
diaphragm building as defined in ASCE 7 Section 
6.2, where wind loads are only transmitted to the main 
wind-force-resisting system (MWFRS) at the dia- 
phragms. 

5. For open buildings, multispan gable roofs, stepped 
roofs, sawtooth roofs, domed roofs, roofs with slopes 
greater than 45 degrees (0.79 rad) , solid free-standing 
walls and solid signs, and rooftop equipment, apply 
ASCE 7 provisions. 

1609.6.1.1 Modifications. The following modifications 
shall be made to certain subsections in ASCE 7: in Sec- 
tion 1609.6.2, symbols and notations that are specific to 
this section are used in conjunction with the symbols and 
notations in ASCE 7 Section 6.3. 



1609.6.2 Symbols and notations. Coefficients and vari- 
ables used in the alternative all-heights method equations 
are as follows: 

C n \ Net-pressure coefficient based on K d uG) (C p ) - 
(GC p )] , in accordance with Table 1609.6.2 (2). 

G Gust effect factor for rigid structures in accordance 

with ASCE 7 Section 6.5.8.1 . 

K d Wind directionality factor in accordance with 

ASCE 7 Table 6-4. 

Pnet Design wind pressure to be used in determination 

of wind loads on buildings or other structures or 
their components and cladding, in psf (kN/m 2 ). 

qs Wind stagnation pressure in psf (kN/m 2 ) in accor- 

dance with Table 1609.6.2(1). 

1609.6.3 Design equations. When using the alternative 
all-heights method, the MWFRS, and components and clad- 
ding of every structure shall be designed to resist the effects 
of wind pressures on the building envelope in accordance 
with Equation 16-34. 



Pnet=QsKC net [IKj 



(Equation 16-34) 



Design wind forces for the MWFRS shall not be less than 
10 psf (0.48 kN/m 2 ) multiplied by the area of the structure 
projected on a plane normal to the assumed wind direction 
(see ASCE 7 Section 6.1.4 for criteria). Design net wind 
pressure for components and cladding shall not be less than 
10 psf (0.48 kN/m 2 ) acting in either direction normal to the 
surface. 

1609.6.4 Design procedure. The MWFRS and the compo- 
nents and cladding of every building or other structure shall 
be designed for the pressures calculated using Equation 
16-34. 

1609.6.4.1 Main wind-foree-resisting systems. The 
MWFRS shall be investigated for the torsional effects 
identified in ASCE 7 Figure 6-9. 

1609.6.4.2 Determination of K z and K zi . Velocity pres- 
sure exposure coefficient, K z , shall be determined in 
accordance with ASCE 7 Section 6.5.6.6 and the topo- 
graphic factor, Ktf shall be determined in accordance 
with ASCE 7 Section 6.5.7. 

1. For the windward side of a structure, A^and K z 
shall be based on height z, 

2. For leeward and sidewalls, and for windward and 
leeward roofs, K# and K z shall be based on mean 
roof height h. 



TABLE 1609.6.2(1) 
WIND VELOCITY PRESSURE (qj AT STANDARD HEIGHT OF 33 FEET a 



BASIC WIND SPEED (mph) 


85 


90 


100 


105 


110 


120 


125 


130 


140 


150 


160 


170 


PRESSURE, qs (pst) 


18.5 


20.7 


25.6 


28.2 


31.0 


36.9 


40.0 


43.3 


50.2 


57.6 


65.5 


74.0 



For 51: 1 foot = 304.8 mm, 1 mph = 0.44 mis, 1 psf = 47.88 Pa. 
a. For basic wind speeds not shown, use qs= 0.00256 V 2 « 



326 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



TABLE 1609.6.2(2) 



STRUCTURE OR 
PART THEREOF 


DESCRIPTION 


CnetFACTOR 


1. Main wind- 
force- resisting 
frames and systems 


Walls: 


Enclosed 


Partially 


enclosed 


+ Internal 
pressure 


-Internal 
pressure 


+ Internal 
pressure 


-Internal 
pressure 


Windward wall 


0.43 


0.73 


0.11 


1.05 


Leeward wall 


-0.51 


-0.21 


-0.83 


0.11 


Sidewall 


-0.66 


-0.35 


-0.97 


-0.04 


Parapet wall 


Windward 


1.28 


1.28 


Leeward 


-0.85 


-0.85 


Roofs: 


Enclosed 


Partially enclosed 


Wind perpendicular to ridge 


+ Internal 
pressure 


-Internal 
pressure 


+ Internal 
pressure 


-Internal 
pressure 


Leeward roof or flat roof 


-0.66 


-0.35 


-0.97 


-0.04 


Windward roof slopes: 


Slope < 2:12 (10°) 


Condition 1 


-1.09 


-0.79 


-1.41 


-0.47 


Condition 2 


-0.28 


0.02 


-0.60 


0.34 


Slope =4:12 (18°) 


Condition 1 


-0.73 


-0.42 


-1.04 


-0.11 


Condition 2 


-0.05 


0.25 


-0.37 


0.57 


Slope = 5:12 (23°) 


Condition 1 


-0.58 


-0.28 


-0.90 


0.04 


Condition 2 


0.03 


0.34 


-0.29 


0.65 


Slope = 6: 12 (27°) 


Condition 1 


-0.47 


-0.16 


-0.78 


0.15 


Condition 2 


0.06 


0.37 


-0.25 


0.68 


Slope = 7: 12 (30°) 


Condition 1 


-0.37 


-0.06 


-0.68 


0.25 


Condition 2 


0.07 


0.37 


-0.25 


0.69 


Slope 9:12 (37°) 


Condition 1 


-0.27 


0.04 


-0.58 


0.35 


Condition 2 


0.14 


0.44 


-0.18 


0.76 


Slope 12: 12 (45°) 


0.14 


0.44 


-0.18 


0.76 


Wind parallel to ridge and flat roofs 


-1.09 


-0.79 


-1.41 


-0.47 


Nonbuilding Structures: Chimneys, Tanks a 


nd Similar Structures 










hiD 


l 


7 


25 


Square (Wind normal to face) 


0.99 


1.07 


1.53 


Square (Wind on diagonal) 


0.77 


0.84 


1.15 


Hexagonal or Octagonal 


0.81 


0.97 


1.13 


Round 


0.65 


0.81 


0.97 


Open signs and lattice frameworks 


Rati 


o of solid to gross 


area 




<0.1 


0.1 to 0.29 


0.3 to 0.7 


Flat 


1.45 


1.30 


1.16 


Round 


0.87 


0.94 


1.08 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



327 



STRUCTURAL DESIGN 



TABLE 1609.6.2(2)-continued 





NET PRESSURE COEFFICIENTS, C net a ,b 










STRUCTURE OR 
PART THEREOF 


DESCRIPTION 


CnetFACTOR 


2. Components and 
cladding not in 
areas of disconti- 
nuity-roofs and 
overhangs 


Roof elements and slopes 


Enclosed 


Partially enclosed 


Gable of hipped configurations (Zone 1) 


Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-11C Zone 1 


Positive 


10 square feet or less 


0.58 


0.89 


100 square feet or more 


0.41 


0.72 


Negative 


10 square feet or less 


-1.00 


-1.32 


100 square feet or more 


-0.92 


-1.23 


Overhang: Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-1 IB Zone 1 


Negative 


10 square feet or less 


-1.45 


100 square feet or more 


-1.36 


500 square feet or more 


-0.94 


6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 6-1 ID Zone 1 


Positive 


10 square feet or less 


0.92 


1.23 


100 square feet or more 


0.83 


1.15 


Negative 


10 square feet or less 


-1.00 


-1.32 


100 square feet or more 


-0.83 


-1.15 


Monosloped configurations (Zone 1) 


Enclosed 


Partially enclosed 


Flat < Slope < 7:12 (30°) See ASCE 7 Figure 6-14B Zone 1 


Positive 


10 square feet or less 


0.49 


0.81 


100 square feet or more 


0.41 


0.72 


Negative 


10 square feet or less 


-1.26 


-1.57 


100 square feet or more 


-1.09 


-1.40 


Tall flat- topped roofs h> 60' 


Enclosed 


Partially enclosed 


Flat < Slope < 2:12 (10°) (Zone 1) See ASCE 7 Figure 6-17 Zone 1 


Negative 


10 square feet or less 


-1.34 


-1.66 


500 square feet or more 


-0.92 


-1.23 



(continued) 



328 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



TABLE 1609.6.2(2)-continued 





NET PRESSURE COEFFICIENTS, C, 


a h 
let ' D 




STRUCTURE OR 
PART THEREOF 


DESCRIPTION 


CnetFACTOR 


3. Components and clad- 
ding in areas of dis- 
continuities-roofs 
and overhangs 


Roof elements and slopes 


Enclosed 


Partially enclosed 


Gable or hipped configurations at ridges, eaves and rakes (Zone 2) 


Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-11C Zone 2 


Positive 


10 square feet or less 


0.58 


0.89 


100 square feet or more 


0.41 


10.72 


Negative 


10 square feet or less 


-1.68 


-2.00 


100 square feet or more 


-1.17 


-1.49 


Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-1 1C Zone 2 


Negative 


10 square feet or less 


-1.87 


100 square feet or more 


-1.87 


6:12 (27°) < Slope < 12:12 (45°) Figure 6-1 ID 


Enclosed 


Partially enclosed 


Positive 


10 square feet or less 


0.92 


1.23 


100 square feet or more 


0.83 


1.15 


Negative 


10 square feet or less 


-1.17 


-1.49 


100 square feet or more 


-1.00 


-1.32 


Overhang for 6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 6-1 ID Zone 2 


Negative 


10 square feet or less 


-1.70 


500 sauare feet or more 


-1.53 


Monosloped configurations at ridges, eaves and rakes (Zone 2) 


Flat < Slope < 7:12 (30°) See ASCE 7 Figure 6-14B Zone 2 


Positive 


10 square feet or less 


0.49 


0.81 


100 square feet or more 


0.41 


0.72 


Negative 


10 square feet or less 


-1.51 


-1.83 


100 square feet or more 


-1.43 


-1.74 


Tall flat topped roofs h> 60' 


Enclosed 


Partially enclosed 


Flat < Slope < 2: 12 (10°) (Zone 2) See ASCE 7 Figure 6-17 Zone 2 


Negative 


10 square feet or less 


-2.11 


-2.42 


500 square feet or more 


-1.51 


-1.83 


Gable or hipped configurations at corners (Zone 3) See ASCE 7 Figure 6-11 C Zone 3 


Flat < Slope < 6:12 (27°) 


Enclosed 


Partially enclosed 


Positive 


10 square feet or less 


0.58 


0.89 


100 square feet or more 


0.41 


0.72 


Negative 


10 square feet or less 


-2.53 


-2.85 


100 square feet or more 


-1.85 


-2.17 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



329 



STRUCTURAL DESIGN 





TABLE 1609.6.2(2)-continued 
NET PRESSURE COEFFICIENTS, C net a , b 




STRUCTURE OR 
PART THEREOF 


DESCRIPTION 


CnetFACTOR 


3 . Components and cladding in 
areas of discontinuity-roofs 
and overhangs 
(continued) 


Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 6-1 1C Zone 3 


Negative 


10 square feet or less 


-3.15 


100 square feet or more 


-2.13 


6:12 (27°) < 12:12 (45°) See ASCE 7 Figure 6-1 ID Zone 3 


Positive 


10 square feet or less 


0.92 


1.23 


100 square feet or more 


0.83 


1.15 


Negative 


10 square feet or less 


-1.17 


-1.49 


100 square feet or more 


-1.00 


-1.32 


Overhang for 6:12 (27°) < Slope < 12:12 (45°) 


Enclosed 


Partially enclosed 


Negative 


10 square feet or less 


-1.70 


100 square feet or more 


-1.53 


Monosloped Configurations at corners (Zone 3) See ASCE 7 Figure 6-14B Zone 3 


Flat < Slope < 7:12 (30°) 


Positive 


10 square feet or less 


0.49 


0.81 


100 square feet or more 


0.41 


0.72 


Negative 


10 square feet or less 


-2.62 


-2.93 


100 square feet or more 


-1.85 


-2.17 


Tall flat topped roofs h> 60' 


Enclosed 


Partially enclosed 


Flat < Slope < 2:12 (100) (Zone 3) See ASCE 7 Figure 6-17 Zone 3 


Negative 


10 square feet or less 


-2.87 


-3.19 


500 square feet or more 


-2.11 


-2.42 


4. Components and cladding not 
in areas of discontinuity-walls 
and parapets 


Wall Elements: h= 60' (Zone 4) Figure 6-11 A 


Enclosed 


Partially enclosed 


Positive 


10 square feetor less 


1.00 


1.32 


500 square feet or more 


0.75 


1.06 


Negative 


10 square feet or less 


-1.09 


-1.40 


500 square feet or more 


-0.83 


-1.15 


Wall Elements: h> 60' (Zone 4) See ASCE 7 Figure 6-17 Zone 4 


Positive 


20 square feet or less 


0.92 


1.23 


500 square feet or more 


0.66 


0.98 


Negative 


20 square feet or less 


-0.92 


-1.23 


500 square feet or more 


-0.75 


-1.06 


Parapet Walls 


Positive 


2.87 


3.19 


Negative 


-1.68 


-2.00 



330 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 







TABLE 1609.6.2(2)-continued 
NET PRESSURE COEFFICIENTS, C, 


let > b 




STRUCTURE OR 
PART THEREOF 


DESCRIPTION 


Cnet FACTOR 


5. Components and cladding 
in areas of discontinuity- 
walls and parapets 


Wall elements: 


h < 60' (Zone 5) Figure 6-11 A 


Enclosed 


Partially enclosed 


Positive 


10 square feet or less 


1.00 


1.32 


500 square feet or more 


0.75 


1.06 


Negative 


10 square feet or less 


-1.34 


-1.66 


500 square feet or more 


-0.83 


-1.15 


Wall elements: 


h> 60' (Zone 5) See ASCE 7 Figure 6-17 Zone 4 




Positive 


20 square feet or less 


0.92 


1.23 


500 square feet or more 


0.66 


0.98 


Negative 


20 square feet or less 


-1.68 


-2.00 


500 square feet or more 


-1.00 


-1.32 


Parapet walls 


Positive 


3.64 


3.95 


Negative 


-2.45 


-2.76 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 , 1 degree = 0.0175 rad. 

a. Linear interpolation between values in the table is permitted. 

b. Some C net values have been grouped together. Less conservative results may be obtained by applying ASCE 7 provisions. 



1609.6.4.3 Determination of net pressure coefficients, 
C ner For the design of the MWFRS and for components 
and cladding, the sum of the internal and external net 
pressure shall be based on the net pressure coefficient, 
r 

1. The pressure coefficient, C neP for walls and roofs 
shall be determined from Table 1609.6.2(2). 

2. Where C net has more than one value, the more 
severe wind load condition shall be used for 
design. 

1609.6.4.4 Application ofwind pressures. When using 
the alternative all-heights method, wind pressures shall 
be applied simultaneously on, and in a direction normal 
to, all building envelope wall and roof surfaces. 

1609.6.4.4.1 Components and cladding. Wind pres- 
sure for each component or cladding element is 
applied as follows using C net values based on the 
effective wind area, A, contained within the zones in 
areas of discontinuity of width and/or length "a," "2a" 
or "4a" at: corners of roofs and walls; edge strips for 
ridges, rakes and eaves; or field areas on walls or roofs 
as indicated in figures in tables in ASCE 7 as refer- 
enced in Table 1609.6.2(2) in accordance with the fol- 
lowing: 

1. Calculated pressures at local discontinuities 
acting over specific edge strips or corner 
boundary areas. 



2. Include "field" (Zone 1, 2 or 4, as applicable) 
pressures applied to areas beyond the bound- 
aries of the areas of discontinuity. 

3. Where applicable, the calculated pressures at 
discontinuities (Zones 2 or 3) shall be com- 
bined with design pressures that apply specifi- 
cally on rakes or eave overhangs. 



SECTION 1610 
SOIL LATERAL LOADS 

1610.1 General. Foundation walls and retaining walls shall be 
designed to resist lateral soil loads. Soil loads specified in Table 
1610.1 shall be used as the minimum design lateral soil loads 
unless determined otherwise by a geotechnical investigation in 
accordance with Section 1803. Foundation walls and other 
walls in which horizontal movement is restricted at the top shall 
be designed for at-rest pressure. Retaining walls free to move 
and rotate at the top shall be permitted to be designed for active 
pressure. Design lateral pressure from surcharge loads shall be 
added to the lateral earth pressure load. Design lateral pressure 
shall be increased if soils at the site are expansive. Foundation 
walls shall be designed to support the weight of the full hydro- 
static pressure of undrained backfill unless a drainage system is 
installed in accordance with Sections 1805.4.2 and 1805.4.3. 

Exception: Foundation walls extending not more than 8 
feet (2438 mm) below grade and laterally supported by the 
top by flexible diaphragms shall be permitted to be designed 
for active pressure. 



2009 INTERNATIONAL BUILDING CODE® 



331 



STRUCTURAL DESIGN 



TABLE 1610.1 
LATERAL SOIL LOAD 



DESCRIPTION OF BACKFILL MATERIAL 


UNIFIED SOIL 
CLASSIFICATION 


DESIGN LATERAL SOIL LOAD a 
(pound per square foot per foot of depth) 


Active pressure 


At-rest pressure 


Well-graded, clean gravels; gravel-sand mixes 


GW 


30 


60 


Poorly graded clean gravels; gravel-sand mixes 


GP 


30 


60 


Silty gravels, poorly graded gravel-sand mixes 


GM 


40 


60 


Clayey gravels, poorly graded gravel-and-clay mixes 


GC 


45 


60 


Well-graded, clean sands; gravelly sand mixes 


SW 


30 


60 


Poorly graded clean sands; sand-gravel mixes 


SP 


30 


60 


Silty sands, poorly graded sand-silt mixes 


SM 


45 


60 


Sand- silt clay mix with plastic fines 


SM-SC 


45 


100 


Clayey sands, poorly graded sand-clay mixes 


SC 


60 


100 


Inorganic silts and clayey silts 


ML 


45 


100 


Mixture of inorganic silt and clay 


ML-CL 


60 


100 


Inorganic clays of low to medium plasticity 


CL 


60 


100 


Organic silts and silt clays, low plasticity 


OL 


Note b 


Note b 


Inorganic clayey silts, elastic silts 


MH 


Noteb 


Noteb 


Inorganic clays of high plasticity 


CH 


Noteb 


Noteb 


Organic clays and silty clays 


OH 


Noteb 


Noteb 



For SI: 1 pound per square foot per foot of depth =0.157 kPalm, 1 foot = 304.8 mm. 

a. Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or satu- 
rated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads. 

b. Unsuitable as backfill material. 

c. The definition and classification of soil materials shall be in accordance with ASTM D 2487. 



SECTION 1611 
RAIN LOADS 

1611.1 Design rain loads. Each portion of a roof shall be 
designed to sustain the load of rainwater that will accumulate 
on it if the primary drainage system for that portion is blocked 
plus the uniform load caused by water that rises above the inlet 
of the secondary drainage system at its design flow. The design 
rainfall shall be based on the 100-year hourly rainfall rate indi- 
cated in Figure 1611.1 or on other rainfall rates determined 
from approved local weather data. 



(Equation 16-35) 



R=5.2(d s + dh) 

For SI: R = 0.0098(d s + dh) 

where: 

d h = Additional depth of water on the undeflected roof 
above the inlet of secondary drainage system at its 
design flow (Le., the hydraulic head), in inches (mm). 

d s = Depth of water on the undeflected roof up to the inlet of 
secondary drainage system when the primary drainage 
system is blocked (Le., the static head), in inches (mm). 



R = Rain load on the undeflected roof, in psf (kN/m 2 ). 
When the phrase "undeflected roof" is used, deflec- 
tions from loads (including dead loads) shall not be 
considered when determining the amount of rain on the 
roof. 

161 1.2 Ponding instability. For roofs with a slope less than i/ 4 
inch per foot [1.19 degrees (0.0208 rad)], the design calcula- 
tions shall include verification of adequate stiffness to preclude 
progressive deflection in accordance with Section 8.4 of ASCE 

7. 

1611.3 Controlled drainage. Roofs equipped with hardware 
to control the rate of drainage shall be equipped with a second- 
ary drainage system at a higher elevation that limits accumula- 
tion of water on the roof above that elevation. Such roofs shall 
be designed to sustain the load of rainwater that will accumu- 
late on them to the elevation of the secondary drainage system 
plus the uniform load caused by water that rises above the inlet 
of the secondary drainage system at its design flow determined 
from Section 1611.1. Such roofs shall also be checked for 
ponding instability in accordance with Section 1611.2. 



332 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 




4.28 -**' 



[P] FIGURE 1611.1 
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES 

For SI: 1 inch = 25.4 mm. 

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC. 



2009 INTERNATIONAL BUILDING CODE® 



333 



STRUCTURAL DESIGN 




[P] FIGURE 1611.1-continued 
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES 

For SI: 1 inch = 25.4 mm. 

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC. 



334 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 




[P] FIGURE 1611.1-continued 
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES 

For SI: 1 inch = 25.4 mm. 

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC. 



2009 INTERNATIONAL BUILDING CODE® 



335 



STRUCTURAL DESIGN 




[P] FIGURE 1611.1-continued 
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA 

For SI: 1 inch = 25.4 mm. 

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC. 



336 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 







§) 


._ «* 


? 


SJ 




in + 




1 3 

y < 




C 1 )^— ^ 


7 



0. 



^1 







ff^/ 


^^ 


m % 













[P] FIGURE 1611.1-continued 
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII 

For SI: 1 inch = 25.4 mm. 

Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC. 



2009 INTERNATIONAL BUILDING CODE® 



337 



STRUCTURAL DESIGN 



SECTION 1612 
FLOOD LOADS 

1612.1 General. Within flood hazard areas as established in 
Section 1612.3, all new construction of buildings, structures 
and portions of buildings and structures, including substantial 
improvement and restoration of substantial damage to build- 
ings and structures, shall be designed and constructed to resist 
the effects of flood hazards and flood loads. For buildings that 
are located in more than one flood hazard area, the provisions 
associated with the most restrictive flood hazard area shall 
apply. 

1612.2 Definitions. The following words and terms shall, for 
the purposes of this section, have the meanings shown herein. 

BASE FLOOD. The flood having a I-percent chance of being 
equaled or exceeded in any given year. 

BASE FLOOD ELEVATION. The elevation of the base 
flood, including wave height, relative to the National Geodetic 
Vertical Datum (NGVD), North American Vertical Datum 
(NAVD) or other datum specified on the Flood Insurance Rate 
Map (FIRM). 

BASEMENT. The portion of a building having its floor 
subgrade (below ground level) on all sides. 

I This definition of "Basement" is limited in application to the 
provisions of Section 1612 (see "Basement" in Section 502.1). 

DESIGN FLOOD. The flood associated with the greater of 
the following two areas: 

1. Area with a flood plain subject to a I-percent or greater 
chance of flooding in any year; or 

2. Area designated as a flood hazard area on a commu- 
nity's flood hazard map, or otherwise legally designated. 

DESIGN FLOOD ELEVATION. The elevation of the 
"design flood, " including wave height, relative to the datum 
specified on the community's legally designated flood hazard 
map. In areas designated as Zone AO, the design flood eleva- 
tion shall be the elevation of the highest existing grade of the 
building's perimeter plus the depth number (in feet) specified 
on the flood hazard map. In areas designated as Zone AO where 
a depth number is not specified on the map, the depth number 
shall be taken as being equal to 2 feet (610 mm). 

DRY FLOODPROOFING. A combination of design modifi- 
cations that results in a building or structure, including the 
attendant utility and sanitary facilities, being water tight with 
walls substantially impermeable to the passage of water and 
with structural components having the capacity to resist loads 
as identified in ASCE 7. 

EXISTING CONSTRUCTION. Any buildings and struc- 
tures for which the "start of construction" commenced before 
the effective date of the community's first flood plain manage- 
ment code, ordinance or standard. "Existing construction" is 
also referred to as "existing structures." 



EXISTING STRUCTURE. See "Existing construction." 

FLOOD or FLOODING. A general and temporary condition 
of partial or complete inundation of normally dry land from: 

1. The overflow of inland or tidal waters. 

2. The unusual and rapid accumulation or runoff of surface 
waters from any source. 

FLOOD DAMAGE-RESISTANT MATERIALS. Any con 

struction material capable of withstanding direct and pro- 
longed contact with floodwaters without sustaining any 
damage that requires more than cosmetic repair. 

FLOOD HAZARD AREA. The greater of the following two 
areas: 

1. The area within a flood plain subject to a I-percent or 
greater chance of flooding in any year. 

2. The area designated as a flood hazard area on a commu- 
nity's flood hazard map, or otherwise legally designated. 

FLOOD HAZARD AREA SUBJECT TO HIGH-VELOC- 
ITY WAVE ACTION. Area within the flood hazard area that 
is subject to high- velocity wave action, and shown on a Flood 
Insurance Rate Map (FIRM) or other flood hazard map as Zone 
V, VO, VEorVI-30. 

FLOOD INSURANCE RATE MAP (FIRM). An official 
map of a community on which the Federal Emergency Man- 
agement Agency (FEMA) has delineated both the special flood 
hazard areas and the risk premium zones applicable to the com- 
munity. 

FLOOD INSURANCE STUDY. The official report provided 
by the Federal Emergency Management Agency containing the 
Flood Insurance Rate Map (FIRM), the Flood Boundary and 
Floodway Map (FBFM), the water surface elevation of the 
base flood and supporting technical data. 

FLOODWAY. The channel of the river, creek or other water- 
course and the adjacent land areas that must be reserved in 
order to discharge the base flood without cumulatively increas- 
ing the water surface elevation more than a designated height. 

LOWEST FLOOR. The floor of the lowest enclosed area, 
including basement, but excluding any unfinished or 
flood-resistant enclosure, usable solely for vehicle parking, 
building access or limited storage provided that such enclosure 
is not built so as to render the structure in violation of this sec- 
tion. 

SPECIAL FLOOD HAZARD AREA. The land area subject 
to flood hazards and shown on a Flood Insurance Rate Map or 
other flood hazard map as Zone A, AE, AI-30, A99, AR, AO, 
AH, V, VO, VEorVI-30. 

START OF CONSTRUCTION. The date of issuance for new 
construction and substantial improvements to existing struc- 
tures, provided the actual start of construction, repair, recon- 
struction, rehabilitation, addition, placement or other 
improvement is within 180 days after the date of issuance. The 



338 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



actual start of construction means the first placement of perma- 
nent construction of a building (including a manufactured 
home) on a site, such as the pouring of a slab or footings, instal- 
lation of pilings or construction of columns. 

Permanent construction does not include land preparation 
(such as clearing, excavation, grading or filling), the installa- 
tion of streets or walkways, excavation for a basement, foot- 
ings' piers or foundations, the erection of temporary forms or 
the installation of accessory buildings such as garages or sheds 
not occupied as dwelling units or not part of the main building. 
For a substantial improvement, the actual "start of construc- 
tion" means the first alteration of any wall, ceiling, floor or 
other structural part of a building, whether or not that alteration 
affects the external dimensions of the building. 

SUBSTANTIAL DAMAGE. Damage of any origin sustained 
by a structure whereby the cost of restoring the structure to its 
before-damaged condition would equal or exceed 50 percent of 
the market value of the structure before the damage occurred. 

SUBSTANTIAL IMPROVEMENT. Any repair, reconstruc- 
tion, rehabilitation, addition or improvement of a building or 
structure, the cost of which equals or exceeds 50 percent of the 
market value of the structure before the improvement or repair 
is started. If the structure has sustained substantial damage, any 
repairs are considered substantial improvement regardless of 
the actual repair work performed. The term does not, however, 
include either: 

1. Any project for improvement of a building required to 
correct existing health, sanitary or safety code violations 
identified by the bUilding official and that are the mini- 
mum necessary to assure safe living conditions. 

2. Any alteration of a historic structure provided that the 
alteration will not preclude the structure's continued 
designation as a historic structure. 

1612.3 Establishment of flood hazard areas. To establish 
flood hazard areas, the applicable governing authority shall 
adopt a flood hazard map and supporting data. The flood haz- 
ard map shall include, at a minimum, areas of special flood haz- 
ard as identified by the Federal Emergency Management 
Agency in an engineering report entitled "The Flood Insurance 
Study for [INSERT NAME OF JURISDICTION] ," dated [INSERT 
DATE OF ISSUANCE], as amended or revised with the accompa- 
nying Flood Insurance Rate Map (FIRM) and Flood Boundary 
and Floodway Map (FBFM) and related supporting data along 
with any revisions thereto. The adopted flood hazard map and 
supporting data are hereby adopted by reference and declared 
to be part of this section. 

1612.3.1 Design flood elevations. Where design flood ele- 
vations are not included in the flood hazard areas estab- 
lished in Section 1612.3, or where floodways are not 
designated, the building official is authorized to require the 
applicant to: 

1. Obtain and reasonably utilize any design flood eleva- 
tion and floodway data available from a federal, state 
or other source; or 



2. Determine the design flood elevation and/or 
floodway in accordance with accepted hydrologic 
and hydraulic engineering practices used to define 
special flood hazard areas. Determinations shall be 
undertaken by a registered design professional who 
shall document that the technical methods used 
reflect currently accepted engineering practice. 

1612.3.2 Determination of impacts. In riverine floo d haz- 
ard areas where design flood elevations are specified but 
floodways have not been designated, the applicant shall pro- 
vide a floodway analysis that demonstrates that the pro- 
posed work will not increase the design flood elevation 
more than 1 foot (305 mm) at any point within the jurisdic- 
tion of the applicable governing authority. 

1612.4 Design and construction. The design and construction 
of buildings and structures located in flood hazard areas, 
including flood hazard areas subject to high-velocity wave 
action, shall be in accordance with Chapter 5 of ASCE 7 and 
with ASCE 24. 

1612.5 Flood hazard documentation. The following docu- 
mentation shall be prepared and sealed by a registered design 
professional and submitted to the bUilding official: 

1. For construction in flood hazard areas not subject to 
high-velocity wave action: 

1.1. The elevation of the lowest floor, including the 
basement, as required by the lowest floor eleva- 
tion inspection in Section 110.3.3. 

1.2. For fully enclosed areas below the design flood 
elevation where provisions to allow for the auto- 
matic entry and exit of floodwaters do not meet 
the minimum requirements in Section 2.6.2.1 of 
ASCE 24, construction documents shall include 
a statement that the design will provide for equal- 
ization of hydrostatic flood forces in accordance 
with Section 2.6.2.2 of ASCE 24. 

1.3. For dry floodproofed nonresidential buildings, 
construction documents shall include a statement 
that the dry floodproofing is designed in accor- 
dance with ASCE 24. 

2. For construction in flood hazard areas subject to 
high-velocity wave action: 

2.1. The elevation of the bottom of the lowest hori- 
zontal structural member as required by the low- 
est floor elevation inspection in Section 1 10.3.3. 

2.2. Construction documents shall include a state- 
ment that the building is designed in accordance 
with ASCE 24, including that the pile or column 
foundation and building or structure to be 
attached thereto is designed to be anchored to 
resist flotation, collapse and lateral movement 
due to the effects of wind and flood loads acting 
simultaneously on all building components, and 
other load requirements of Chapter 16. 



2009 INTERNATIONAL BUILDING CODE® 



339 



STRUCTURAL DESIGN 



2.3. For breakaway walls designed to resist a nominal 
load of less than 10 psf (0.48 kN/m 2 ) or more than 
20 psf (0.96 kN/m 2 ) , construction documents 
shall include a statement that the breakaway wall 
is designed in accordance with ASCE 24. 



SECTION 1613 
EARTHQUAKE LOADS 

1613.1 Scope. Every structure, and portion thereof, including 
nonstructural components that are permanently attached to 
structures and their supports and attachments, shall be 
designed and constructed to resist the effects of earthquake 
motions in accordance with ASCE 7, excluding Chapter 14 and 
Appendix 11 A. The seismic design category for a structure is 
permitted to be determined in accordance with Section 1613 or 
ASCE 7. 

Exceptions: 

1. Detached one- and two-family dwellings, assigned to 
Seismic Design Category A, B or C, or located where 
the mapped short-period spectral response accelera- 
tion, Ss, is less than 0.4 g. 

2. The seismic-force-resisting system of wood-frame 
buildings that conform to the provisions of Section 
2308 are not required to be analyzed as specified in 
this section. 

3. Agricultural storage structures intended only for inci- 
dental human occupancy. 

4. Structures that require special consideration of their 
response characteristics and environment that are not 
addressed by this code or ASCE 7 and for which other 
regulations provide seismic criteria, such as vehicular 
bridges, electrical transmission towers, hydraulic 
structures, buried utility lines and their appurtenances 
and nuclear reactors. 

1613.2 Definitions. The following words and terms shall, for 
the purposes of this section, have the meanings shown herein. 

DESIGN EARTHQUAKE GROUND MOTION. The earth- 
quake ground motion that buildings and structures are specifi- 
cally proportioned to resist in Section 1613. 

MAXIMUM CONSIDERED EARTHQUAKE GROUND 
MOTION. The most severe earthquake effects considered by 
this code. 

MECHANICAL SYSTEMS. For the purposes of determin- 
ing seismic loads in ASCE 7, mechanical systems shall include 
plumbing systems as specified therein. 

ORTHOGONAL. To be in two horizontal directions, at 90 
degrees (1 . 57 rad) to each other. 

SEISMIC DESIGN CATEGORY. A classification assigned 
to a structure based on its occupancy category and the severity 
of the design earthquake ground motion at the site. 



SEISMIC-FORCE-RESISTING SYSTEM. That part of the 
structural system that has been considered in the design to pro- 
vide the required resistance to the prescribed seismic forces. 

SITE CLASS. A classification assigned to a site based on the 
types of soils present and their engineering properties as 
defined in Section 1613.5.2. 

SITE COEFFICIENTS. The values of Fa and F v indicated in 
Tables 1613.5.3(1) and 1613.5.3(2), respectively. 

1613.3 Existing buildings. Additions, alterations, repairs or 
change of occupancy of existing buildings shall be in accor- 
dance with Chapter 34. 

1613.4 Special inspections. Where required by Sections 
1705.3 through 1705.3.5, the statement of special inspections 
shall include the special inspections required by Section 
1705.3.6. 

1613.5 Seismic ground motion values. Seismic ground 
motion values shall be determined in accordance with this sec- 
tion. 

1613.5.1 Mapped acceleration parameters. The parame- 
ters 55 and 51 shall be determined from the 0.2 and I- second 
spectral response accelerations shown on Figures 1613.5(1) 
through 1613.5(14). Where 51 is less than or equal to 0.04 
and 55 is less than or equal to 0.15, the structure is permitted 
to be assigned to Seismic Design Category A. 

1613.5.2 Site class definitions. Based on the site soil prop- 
erties, the site shall be classified as either Site Class A, B, C, 
D, E or F in accordance with Table 1613.5.2. When the soil 
properties are not known in sufficient detail to determine the 
site class, Site Class D shall be used unless the bUilding ojfi- 
cialor geotechnical data determines that Site Class E or F 
soil is likely to be present at the site. 

1613.5.3 Site coefficients and adjusted maximum con- 
sidered earthquake spectral response acceleration 
parameters. The maximum considered earthquake spectral 
response acceleration for short periods, SMS' and at I-second 
period, SMI' adjusted for site class effects shall be deter- 
mined by Equations 16-36 and 16-37, respectively: 



(Equation 16-36) 
(Equation 16-37) 



SMS= FaS s 

SMI = F v Sl 

where: 

Fa = Site coefficient defined in Table 1613.5.3(1). 

F v = Site coefficient defined in Table 1613.5.3(2). 

Ss = The mapped spectral accelerations for short periods 
as determined in Section 1613.5.1. 

51 = The mapped spectral accelerations for a I-second 
period as determined in Section 1613.5.1. 



340 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



TABLE 1613.5.2 
SITE CLASS DEFINITIONS 



SITE 
CLASS 


SOIL PROFILE 
NAME 


AVERAGE PROPERTIES IN TOP 100 feet, SEE SECTION 1613.5.5 


Soil shear wave velocity, vs (ftls) 


Standard penetration resistance, N 


Soil undrained shear strength, s«' (pst) 


A 


Hard rock 


v x > 5,000 


N/A 


N/A 


B 


Rock 


2,500 <v s < 5,000 


N/A 


N/A 


C 


Very dense soil and soft rock 


1,200 <v s < 2,500 


N>50 


s u > 2,000 


D 


Stiff soil profile 


600 <v s < 1,200 


15 < N< 50 


1,000 <s„< 2,000 


E 


Soft soil profile 


v, < 600 


~N<15 


s u < 1,000 


E 




Any profile with more than 10 feet of soil having the following characteristics: 

1. Plasticity index PI> 20, 

2. Moisture content w> 40%, and 

3. Undrained shear strength s u < 500 psf 


F 


- 


Any profile containing soils having one or more of the following characteristics: 

1. Soils vulnerable to potential failure or collapse under seismic loading such as liquefiable 
soils, quick and highly sensitive clays, collapsible weakly cemented soils. 

2. Peats and/or highly organic clays (H> 10 feet of peat and/or highly organic clay where 
H= thickness of soil) 

3. Very high plasticity clays (H> 25 feet with plasticity index PI> 75) 

4. Very thick soft/medium stiff clays (H> 120 feet) 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m , 1 pound per square foot = 0.0479 kPa. N/A = Not applicable 

TABLE 1613.5.3(1) 
VALUES OF SITE COEFFICIENT Fa a 



SITE 
CLASS 


MAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD 


5 S <0.25 


5 S =0.50 


Ss =0.75 


Ss=1.00 


5 S >1.25 


A 


0.8 


0.8 


0.8 


0.8 


0.8 


B 


1.0 


1.0 


1.0 


1.0 


1.0 


C 


1.2 


1.2 


1.1 


1.0 


1.0 


D 


1.6 


1.4 


1.2 


1.1 


1.0 


E 


2.5 


1.7 


1.2 


0.9 


0.9 


F 


Noteb 


Noteb 


Noteb 


Noteb 


Noteb 



a. Use straight- line interpolation for intermediate values of mapped spectral response acceleration at short period, 55 

b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7. 

TABLE 1613.5.3(2) 







VALUES OF SITE COEFFICIENT F v a 






SITE 
CLASS 


MAPPED SPECTRAL RESPONSE ACCELERATION AT 1 -SECOND PERIOD 


S, < 0.1 


51 =0.2 


S1 =0.3 


S1 =0.4 


51 >0.5 


A 


0.8 


0.8 


0.8 


0.8 


0.8 


B 


1.0 


1.0 


1.0 


1.0 


1.0 


C 


1.7 


1.6 


1.5 


1.4 


1.3 


D 


2.4 


2.0 


1.8 


1.6 


1.5 


E 


3.5 


3.2 


2.8 


2.4 


2.4 


F 


Noteb 


Note b 


Noteb 


Noteb 


Note b 



a. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at I-second period, 51. 

b. Values shall be determined in accordance with Section 11.4.7 of ASCE 7. 



2009 INTERNATIONAL BUILDING CODE® 



341 



STRUCTURAL DESIGN 



1613.5.4 Design spectral response acceleration parame- 
ters. Five-percent damped design spectral response acceler- 
ation at short periods, SDS, and at I- second period, SDI, shall 
be determined from Equations 16-38 and 16-39, respec- 
tively: 



SDS= —S MS 

s - 2 S 



where: 



(Equation 16-38) 



(Equation 16-39) 



SMS = The maximum considered earthquake spectral 
response accelerations for short period as deter- 
mined in Section 1613.5.3. 

SM The maximum considered earthquake spectral 
response accelerations for I-second period as 
determined in Section 1613.5.3. 

1613.5.5 Site classification for seismic design. Site classi- 
fication for Site Class C, D or E shall be determined from 
Table 1613.5.5. 

The notations presented below apply to the upper 100 feet 
(30 480 mm) of the site profile. Profiles containing dis- 
tinctly different soil and/or rock layers shall be subdivided 
into those layers designated by a number that ranges from 1 
to n at the bottom where there is a total of n distinct layers in 
the upper 100 feet (30 480 mm). The symbol /then refers to 
anyone of the layers between 1 and n. 

where: 

v sj = The shear wave velocity in feet per second (m/s). 

dj = The thickness of any layer between and 100 feet 



(30480 mm). 



where: 



Z«* 



di 



]£ dj= 100 feet (30 480 mm) 



(Equation 16-40) 



N t is the Standard Penetration Resistance (ASTM D 1586) 
not to exceed 100 blows/foot (328 blows/m) as directly 
measured in the field without corrections. When refusal is 
met for a rock layer, N t shall be taken as 100 blows/foot (328 
blows/m). 



Z4 

N = - M 






(Equation 16-41) 



where A, and d, in Equation 16-41 are for cohesionless soil, 
cohesive soil and rock layers. 



VtN J 



(Equation 16-42) 



where: 

m 

Zrf,=rf, 

i=\ 

Use dj and N t for cohesionless soil layers only in Equation 
16-42. 

d s = The total thickness of cohesionless soil layers in the 
top 100 feet (30 480 mm). 

m = The number of cohesionless soil layers in the top 100 
feet (30 480 mm). 

Suj = The undrained shear strength in psf (kPa), not to 
exceed 5,000 psf (240 kPa), ASTM D 2166 or D 
2850. 



(Equation 16-43) 



de 

Su = — — — 
j=l SUj 

where: 
td t =d e 



de = The total thickness of cohesive soil layers in the top 
100 feet (30 480 mm). 

k = The number of cohesive soil layers in the top 100 feet 
(30480 mm). 

PI = The plasticity index, ASTM D 4318. 



TABLE 1613.5.5 
SITE CLASSIFICATION 3 



SITE CLASS 


vS 


N or~N Ch 


s u 


E 


< 600 ft/s 


< 15 


< 1,000 psf 


D 


600 to 1,200 ftls 


15 to 50 


1,000 to 2,000 psf 


C 


1,200 to 2,500 ftls 


>50 


> 2,000 



For SI: 1 foot per second = 304.8 mm per second, 1 pound per square foot = 0.0479kN/m 2 ^ 

a. If the sumethod is used and the Ndiand sucriteria differ, select the category with the softer soils (for example, use Site Class E instead of D) . 



342 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



I 



w = The moisture content in percent, ASTM D 2216. 

Where a site does not qualify under the criteria for Site 
Class F and there is a total thickness of soft clay greater than 
10 feet (3048 mm) where a soft clay layer is defined by: Su < 
500 psf (24 kPa), w> 40 percent, and PI > 20, it shall be clas- 
sified as Site Class E. 

The shear wave velocity for rock, Site Class B, shall be 
either measured on site or estimated by a geotechnical engi- 
neer or engineering geologist/seismologist for competent 
rock with moderate fracturing and weathering. Softer and 
more highly fractured and weathered rock shall either be 
measured on site for shear wave velocity or classified as Site 
ClassC. 

The hard rock category, Site Class A, shall be supported 
by shear wave velocity measurements either on site or on 
profiles of the same rock type in the same formation with an 
equal or greater degree of weathering and fracturing. Where 
hard rock conditions are known to be continuous to a depth 
of 100 feet (30 480 mm), surficial shear wave velocity mea- 
surements are permitted to be extrapolated to assess Vs. 

The rock categories, Site Classes A and B, shall not be 
used if there is more than 10 feet (3048 mm) of soil between 
the rock surface and the bottom of the spread footing or mat 
foundation. 

1613.5.5.1 Steps for classifying a site. 

1. Check for the four categories of Site Class F 
requiring site- specific evaluation. If the site corre- 
sponds to any of these categories, classify the site 
as Site Class F and conduct a site- specific evalua- 
tion. 

2. Check for the existence of a total thickness of soft 
clay> 10 feet (3048 mm) where a soft clay layer is 
defined by: Su < 500 psf (24 kPa) , w> 40 percent 
and PI> 20. If these criteria are satisfied, classify 
the site as Site Class E. 

3. Categorize the site using one of the following three 
methods with Vs' N, and s«and computed in all 
cases as specified. 

3.1. v s for the top 100 feet (30 480 mm) 
(vsmethod) . 

3.2. N for the top 100 feet (30 480 mm) 
(Nmethod). 

3.3. N ch for cohesionless soil layers (PI< 20) 
in the top 100 feet (30 480 mm) and aver- 
age, 5 y for cohesive soil layers (PI> 20) in 
the top 100 feet (30 480 mm) ( Su method) . 

1613.5.6 Determination of seismic design category. 
Structures classified as Occupancy Category I, II or III that 
are located where the mapped spectral response accelera- 
tion parameter at I- second period, S b is greater than or 



equal to 0.75 shall be assigned to Seismic Design Category 
E. Structures classified as Occupancy Category IN that are 
located where the mapped spectral response acceleration 
parameter at I- second period, S p is greater than or equal to 
0.75 shall be assigned to Seismic Design Category F. All 
other structures shall be assigned to a seismic design cate- 
gory based on their occupancy category and the design 
spectral response acceleration coefficients, sds and S D1 , 
determined in accordance with Section 1613.5.4 or the site- 
specific procedures of ASCE 7. Each building and structure 
shall be assigned to the more severe seismic design category 
in accordance with Table 1613.5.6(1) or 1613.5.6(2), irre- 
spective of the fundamental period of vibration of the struc- 
ture, I 

TABLE 1613.5.6(1) 

SEISMIC DESIGN CATEGORY BASED ON 

SHORT-PERIOD RESPONSE ACCELERATIONS 



VALUE OF 5 DS 


OCCUPANCY CATEGORY 


lor II 


m 


IV 


SDS< 0.167g 


A 


A 


A 


0.167g<SDS<0.33g 


B 


B 


C 


0.33g< sds <QS0g 


c 


C 


D 


QSOg < sds 


D 


D 


D 



TABLE 1613.5.6(2) 

SEISMIC DESIGN CATEGORY BASED ON 

1-SECOND PERIOD RESPONSE ACCELERATION 



VALUE OF 5 D1 


OCCUPANCY CATEGORY 


lor II 


m 


IV 


sdi < 0.067g 


A 


A 


A 


0.067g<SD7<0.133g 


B 


B 


C 


0.133g<SD7<0.20g 


C 


C 


D 


0.20g < sdi 


D 


D 


D 



1613.5.6.1 Alternative seismic design category deter- 
mination. Where SI is less than 0.75, the seismic design 
category is permitted to be determined from Table 
1613.5.6(1) alone when all of the following apply: 

1. In each of the two orthogonal directions, the 
approximate fundamental period of the structure, 
Ta, in each of the two orthogonal directions deter- 
mined in accordance with Section 12.8.2.1 of 
ASCE 7, is less than 0.8 T s determined in accor- 
dance with Section 11.4.5 of ASCE 7. 

2. In each of the two orthogonal directions, the fun- 
damental period of the structure used to calculate 
the story drift is less than T s . 



2009 INTERNATIONAL BUILDING CODE® 



343 



STRUCTURAL DESIGN 



3. Equation 12.8-2 of ASCE 7 is used to determine 
the seismic response coefficient, C s 

4. The diaphragms are rigid as defined in Section 
12.3.1 of ASCE 7 or, for diaphragms that are flexi- 
ble, the distances between vertical elements of the 
seismic- force-resisting system do not exceed 40 
feet (12 192 mm). 

1613.5.6.2 Simplified design procedure. Where the 
alternate simplified design procedure of ASCE 7 is used, 
the seismic design category shall be determined in accor- 
dance with ASCE 7. 

1613.6 Alternatives to ASCE 7. The provisions of Section 
1613.6 shall be permitted as alternatives to the relevant provi- 
sions of ASCE 7. 

1613.6.1 Assumption of flexible diaphragm. Add the fol- 
lowing text at the end of Section 12.3.1.1 of ASCE 7. 

Diaphragms constructed of wood structural panels or 
untopped steel decking shall also be permitted to be ideal- 
ized as flexible, provided all of the following conditions are 
met: 

1. Toppings of concrete or similar materials are not 
placed over wood structural panel diaphragms except 
for nonstructural toppings no greater than 1V 2 inches 
(38 mm) thick. 

2. Each line of vertical elements of the seis- 
mic-foree-resisting system complies with the allow- 
able story drift of Table 12.12-1. 

3. Vertical elements of the seismic-foree-resisting sys- 
tem are light-frame walls sheathed with wood struc- 
tural panels rated for shear resistance or steel sheets. 

4. Portions of wood structural panel diaphragms that 
cantilever beyond the vertical elements of the lat- 
eral-force-resisting system are designed in accor- 
dance with Section 4.2.5.2 of AF&PA SDPWS. 

1613.6.2 Additional seismic-foree-resisting systems for 
seismically isolated structures. Add the following excep- 
tion to the end of Section 17.5.4.2 of ASCE 7: 

Exception: For isolated structures designed in accor- 
dance with this standard, the Structural System Limita- 
tions and the Building Height Limitations in Table 
12.2-1 for ordinary steel concentrically braced frames 
(OCBFs) as defined in Chapter 11 and ordinary moment 
frames (OMFs) as defined in Chapter 11 are permitted to 
be taken as 160 feet (48 768 mm) for structures assigned 
to Seismic Design Category D, E or F, provided that the 
following conditions are satisfied: 

1. The value of R r as defined in Chapter 17 is taken as 
1. 

2. For OMFs and OCBFs, design is in accordance 
with AISC 341. 



1613.6.3 Automatic sprinkler systems. Automatic sprin- 
kler systems designed and installed in accordance with 
NFPA 13 shall be deemed to meet the requirements of Sec- 
tion 13.6.8 of ASCE 7. 

1613.6.4 Autoclaved aerated concrete (AAC) masonry 
shear wall design coefficients and system limitations. 
Add the following text at the end of Section 12.2.1 of ASCE 

7: 

For ordinary reinforced AAC masonry shear walls used 
in the seismic-foree-resisting system of structures, the 
response modification factor, R, shall be permitted to be 
taken as 2, the deflection amplification factor, Cd' shall be 
permitted to be taken as 2 and the system overstrength fac- 
tor, D, , shall be permitted to be taken as 2V 2 , Ordinary rein- 
forced AAC masonry shear walls shall not be limited in 
height for buildings assigned to Seismic Design CategoryB, 
shall be limited in height to 35 feet (10 668 mm) for build- 
ings assigned to Seismic Design CategoryC and are not per- 
mitted for buildings assigned to Seismic Design Categories 
D, E and F. 

For ordinary plain (unreinforced) AAC masonry shear 
walls used in the seismic-foree-resisting system of struc- 
tures, the response modification factor, R, shall be permitted 
to be taken as lV 2 , the deflection amplification factor, Cd' 
shall be permitted to be taken as 1V 2 and the system 
overstrength factor, Q , shall be permitted to be taken as 2V 2 , 
Ordinary plain (unreinforced) AAC masonry shear walls 
shall not be limited in height for buildings assigned to Seis- 
mic Design CategoryB and are not permitted for buildings 
assigned to Seismic Design Categories C, D, E and F. 

1613.6.5 Seismic controls for elevators. Seismic switches 
in accordance with Section 8.4. 10 of ASME A17.1 shall be 
deemed to comply with Section 13.6.10.3 of ASCE 7. 

1613.6.6 Steel plate shear wall height limits. Modify Sec- 
tion 12.2.5.4 of ASCE 7 to read as follows: 

12.2.5.4 Increased building height limit for steel- 
braced frames, special steel plate shear walls and spe- 
cial reinforced concrete shear walls. The height limits 
in Table 12.2-1 are permitted to be increased from 160 
feet (48 768 mm) to 240 feet (75 152 mm) for structures 
assigned to Seismic Design Category D or E and from 
100 feet (30 480 mm) to 160 feet (48 768 mm) for struc- 
tures assigned to Seismic Design Category F that have 
steel-braced frames, special steel plate shear walls or 
special reinforced concrete cast-in-place shear walls and 
that meet both of the following requirements: 

1. The structure shall not have an extreme torsional 
irregularity as defined in Table 12.2-1 (horizontal 
structural irregularity Type lb). 

2. The braced frames or shear walls in anyone plane 
shall resist no more than 60 percent of the total 
seismic forces in each direction, neglecting acci- 
dental torsional effects. 



344 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



1613.6.7 Minimum distance for building separation. All 
buildings and structures shall be separated from adjoining 
structures. Separations shall allow for the maximum inelas- 
tic response displacement (5 M ). 6m shall be determined at 
critical locations with consideration for both translational 
and torsional displacements of the structure using Equation 
16-44. 



<? _ ^ d^max 
OlU — 7 



where: 



(Equation 16-44) 



Cd Deflection amplification factor in Table 12.2-1 of 
ASCE 7. 

8 max = Maximum displacement defined in Section 12.8.4.3 
of ASCE 7. 

/ Importance factor in accordance with Section 1 1 .5. 1 

of ASCE 7. 

Adjacent buildings on the same property shall be sepa- 
rated by a distance not less than 3 MT , determined by Equa- 
tion 16-45. 



5 Mr=V( 5 Mi) 2 +( 5 mz) 2 



(Equation 16-45) 



where: 

5m/' 5/\/ 



The maximum inelastic response displace- 
ments of the adjacent buildings in accordance 
with Equation 16-44. 

Where a structure adjoins a property line not common to a 
public way, the structure shall also be set back from the 
property line by not less than the maximum inelastic 
response displacement, 8m' of that structure. 

Exceptions: 

1. Smaller separations or property line setbacks shall 
be permitted when justified by rational analyses. 

2. Buildings and structures assigned to Seismic 
Design Category A, B or C. 

1613.6.8 HVAC ductwork with l p = 1.5. Seismic supports 
are not required for HVAC ductwork with / = 1.5 if either of 
the following conditions is met for the full length of each 
duct run: 

1. HVAC ducts are suspended from hangers 12 inches 
(305 mm) or less in length with hangers detailed to 
avoid significant bending of the hangers and their 
attachments, or 

2. HVAC ducts have a cross-sectional area of less than 6 
square feet (0.557 m 2 ) .. 

1613.7 ASCE 7, Section 11.7.5. Modify ASCE 7, Section 
11.7.5 to read as follows: 

11.7.5 Anchorage of walls. Walls shall be anchored to the 
roof and all floors and members that provide lateral support 
for the wall or that are supported by the wall. The anchorage 



shall provide a direct connection between the walls and the 
roof or floor construction. The connections shall be capable 
of resisting the forces specified in Section 11.7.3 applied 
horizontally, substituted for Ein load combinations of Sec- 
tion 2.3 or 2.4. 



SECTION 1614 
STRUCTURAL INTEGRITY 

1614.1 General. Buildings classified as high-rise buildings in 
accordance with Section 403 and assigned to Occupancy Cate- 
gory III or IV shall comply with the requirements of this sec- 
tion. Frame structures shall comply with the requirements of 
Section 1614.3. Bearing wall structures shall comply with the 
requirements of Section 1614.4. 

1614.2 Definitions. The following words and terms shall, for 
the purposes of Section 1614, have the meanings shown herein. 

BEARING WALL STRUCTURE. A building or other struc- 
ture in which vertical loads from floors and roofs are primarily 
supported by walls. 

FRAME STRUCTURE. A building or other structure in 
which vertical loads from floors and roofs are primarily sup- 
ported by columns. 

1614.3 Frame structures. Frame structures shall comply with 
the requirements of this section. 

1614.3.1 Concrete frame structures. Frame structures 
constructed primarily of reinforced or prestressed concrete, 
either cast-in-place or precast, or a combination of these, 
shall conform to the requirements of ACI 318 Sections 7.13, 
13.3.8.5, 13.3.8.6, 16.5, 18.12.6, 18.12.7 and 18.12.8 as 
applicable. Where ACI 318 requires that nonprestressed 
reinforcing or prestressing steel pass through the region 
bounded by the longitudinal column reinforcement, that 
reinforcing or prestressing steel shall have a minimum nom- 
inal tensile strength equal to two-thirds of the required 
one-way vertical strength of the connection of the floor or 
roof system to the column in each direction of beam or slab 
reinforcement passing through the column. 

Exception: Where concrete slabs with continuous rein- 
forcing having an area not less than 0.0015 times the con- 
crete area in each of two orthogonal directions are 
present and are either monolithic with or equivalently 
bonded to beams, girders or columns, the longitudinal 
reinforcing or prestressing steel passing through the col- 
umn reinforcement shall have a nominal tensile strength 
of one-third of the required one-way vertical strength of 
the connection of the floor or roof system to the column 
in each direction of beam or slab reinforcement passing 
through the column. 

1614.3.2 Structural steel, open web steel joist or joist 
girder, or composite steel and concrete frame structures. 
Frame structures constructed with a structural steel frame or 
a frame composed of open web steeljoistsjoist girders with 
or without other structural steel elements or a frame com- 



2009 INTERNATIONAL BUILDING CODE® 



345 



STRUCTURAL DESIGN 



posed of composite steel or composite steeljoists and rein- 
forced concrete elements shall conform to the requirements 
of this section. 

1614.3.2.1 Columns. Each column splice shall have the 
minimum design strength in tension to transfer the 
design dead and live load tributary to the column 
between the splice and the splice or base immediately 
below. 

1614.3.2.2 Beams. End connections of all beams and 
girders shall have a minimum nominal axial tensile 
strength equal to the required vertical shear strength for 
allowable stress design (ASD) or two-thirds of the 
required shear strength for load and resistance factor 
design (LRFD) but not less than 10 kips (45 kN). For the 
purpose of this section, the shear force and the axial ten- 
sile force need not be considered to act simultaneously. 

Exception: Where beams, girders, open web joist and 
joist girders support a concrete slab or concrete slab 
on metal deck that is attached to the beam or girder 
with not less than 3/ s -inch-diameter (9.5 mm) headed 
shear studs, at a spacing of not more than 12 inches 
(305 mm) on center, averaged over the length of the 
member, or other attachment having equivalent shear 
strength, and the slab contains continuous distributed 
reinforcement in each of two orthogonal directions 
with an area not less than 0.0015 times the concrete 
area, the nominal axial tension strength of the end 
connection shall be permitted to be taken as half the 
required vertical shear strength for ASD or one-third 
of the required shear strength for LRFD, but not less 
than 10 kips (45 kN). 

1614.4 Bearing wall structures. Bearing wall structures shall 
have vertical ties in all load-bearing walls and longitudinal ties, 
transverse ties and perimeter ties at each floor level in accor- 
dance with this section and as shown in Figure 1614.4. 

1614.4.1 Concrete wall structures. Precast bearing wall 
structures constructed solely of reinforced or prestressed 
concrete, or combinations of these shall conform to the 
requirements of Sections 7.13, 13.3.8.5 and 16.5 of ACI 
318. 

1614.4.2 Other bearing wall structures. Ties in bearing 
wall structures other than those covered in Section 1614.4.1 
shall conform to this section. 

1614.4.2.1 Longitudinal ties. Longitudinal ties shall 
consist of continuous reinforcement in slabs; continuous 
or spliced decks or sheathing; continuous or spliced 
members framing to, within or across walls; or connec- 
tions of continuous framing members to walls. Longitu- 
dinal ties shall extend across interior load-bearing walls 
and shall connect to exterior load-bearing walls and shall 
be spaced at not greater than 10 feet (3038 mm) on cen- 
ter. Ties shall have a minimum nominal tensile strength, 
T T , given by Equation 16-46. For ASD the minimum 
nominal tensile strength shall be permitted to be taken as 



1.5 times the allowable tensile stress times the area of the 
tie. 



T T = wLS<ajS 
where: 



(Equation 16-46) 



L The span of the horizontal element in the direc- 

tion of the tie, between bearing walls, feet (m) . 

w The weight per unit area of the floor or roof in the 

span being tied to or across the wall, psf (N/m 2 ) . 

5 = The spacing between ties, feet (m). 

aT = A coefficient with a value of 1,500 pounds per 
foot (2.25 kN/m) for masonry bearing wall struc- 
tures and a value of 375 pounds per foot (0.6 
kN/m) for structures with bearing walls of 
cold-formed steel light-frame construction. 

1614.4.2.2 Transverse ties. Transverse ties shall consist 
of continuous reinforcement in slabs; continuous or 
spliced decks or sheathing; continuous or spliced mem- 
bers framing to, within or across walls; or connections of 
continuous framing members to walls. Transverse ties 
shall be placed no farther apart than the spacing of load- 
bearing walls. Transverse ties shall have minimum nomi- 
nal tensile strength T T , given by Equation 16-46. For 
ASD the minimum nominal tensile strength shall be per- 
mitted to be taken as 1.5 times the allowable tensile stress 
times the area of the tie. 

1614.4.2.3 Perimeter ties. Perimeter ties shall consist of 
continuous reinforcement in slabs; continuous or spliced 
decks or sheathing; continuous or spliced members 
framing to, within or across walls; or connections of con- 
tinuous framing members to walls. Ties around the per- 
imeter of each floor and roof shall be located within 4 
feet (1219 mm) of the edge and shall provide a nominal 
strength in tension not less than T p , given by Equation 
16-47. For ASD the minimum nominal tensile strength 
shall be permitted to be taken as 1.5 times the allowable 
tensile stress times the area of the tie. 



T p =200w<$ T 

For SI: 

7; = 90.7^<p r 

where: 



(Equation 16-47) 



w 



As defined in Section 1614.4.2.1. 

A coefficient with a value of 16,000 pounds 
(7200 kN) for structures with masonry bearing 
walls and a value of 4,000 pounds (1300 kN) for 
structures with bearing walls of cold-formed 
steel light-frame construction. 

1614.4.3.4 Vertical ties. Vertical ties shall consist of 
continuous or spliced reinforcing, continuous or spliced 
members, wall sheathing or other engineered systems. 
Vertical tension ties shall be provided in bearing walls 



346 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



and shall be continuous over the height of the building. 
The minimum nominal tensile strength for vertical ties 
within a bearing wall shall be equal to the weight of the 
wall within that storyplus the weight of diaphragm tribu- 
tary to the wall in the story below. No fewer than two ties 
shall be provided for each wall. The strength of each tie 
need not exceed 3,000 pounds per foot (450 kN/m) of 
wall tributary to the tie for walls of masonry construction 
or 750 pounds per foot (140 kN/m) of wall tributary to 
the tie for walls of cold-formed steel light-frame con- 
struction. 



2009 INTERNATIONAL BUILDING CODE® 347 



STRUCTURAL DESIGN 




DISCUSSION 

The acceleration values contoured on this map are for 
the random horiwntal component of accelen 

Selected COuntoUlS have been deleted for clarity. 

required 
■ 
prepared a CD-ROM that contains software to allow 
detennination of Site Class B map values by 
latitude-longitude. The software on the CD cc 
coefficients that allow the user to adjust map values for 

different 
scales are also included on the CD. The CD was prepared 
using the same data as that used to prepare the Maximum 
Considered Earthquake Ground Motion maps. 
The National Seismic Hazard Mapping Project Web Site, 
is electronic 
versions of this map and others. Documentation, gridded 
id ArcllNFO coverages used to make 
vailable. 

with the California Geological SUlVey. 

Map prepared by U.S . Geological SUlVey. 



Building Seismic KM, NEHRP Recommended 

Provisions for i 

other Structures, Part 1 - Provisions, FEMA450. 
Building Seismic Safety Council 2004, NEHRP Recommended 

Provisions for ' 

other Structures, Part 2 iMA 450. 

Frankel, A, Petersen, M, Mueller, C, Haller. K, Wheeler, R, 

Leyendecker, E, Wesson. R, Harmsen, S., Cramer, C, 

Perkins, D., and Rukstales, K, 2002. Documentation for the 

2002 Update of the Nation .1 Maps, U.S . 

Geological Survey Open-File Report 02-420. 
Frnnkel, A, Petersen, M, Mueller. C, Haller. K, Wheeler, R, 

■ ::':'-' .. 

Perkins, D., and Rukstales, K, 2004, Seismic-H: 
for the Conterminous United States, Sheet 4 - Horizontal 
Spectral Response Accelei ond Period with 

2% Probability ofExceedance in 50 Years, U.S. Geological 
SUlVey Geologic Investigation Series, scale 1:7,000,000. 
(in progress) 

Leyendecker. L k, 2001, Seismic 

Design Parameters, U.S. Geological SUlVey Open-File 
Report 01-437. 

Leyendecker, E . k, 2004, Seismic 

Design Parameters, U.S. Geological SUlVey Open-File 
Report (in progress). 

National Seismic Hazard Mapping Project Web Site, 
http://eqhazrnaps.usgs.gov, U. S. Geological Sl'lVey. 



- Region 1 is shown enlarged in figure 1 61 3.5(3) 

- Region 2 is shown enlarged in figure 1 61 3.5(5) 

- Region 3 is shown enlarged in figure 1 61 3.5(7) 

- Region 4 is shown enlarged in figure 1 61 3.5(9) 



FIGURE 1613.5(1) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



348 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 




Point value of spectral response 
ofgravity 



Contours of spectral response 

on expressed as a percent 
ofgravity. Hachures point in 
direction of decreasing values. 



100 100 200 300 400 500 600 



FIGURE 1613.5(1)-continued 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



2009 INTERNATIONAL BUILDING CODE® 



349 



STRUCTURAL DESIGN 




DISCUSSION 

The acceleration values contoured on this map are for 
the random horizo acceleration For 

in for the map 
is to be taken as Site Class B. 
Selected COuntoUlS have been deleted for clarity. 
dd be used when additional 
required. 

' a CD-ROM that contains software to allow 
detennination of Site Class B map values by 

■e on the CD contains site 

lap values for 

different Site Classes. Additional maps at different 

scales are also included on the CD. The CD was prep 

Considered Earthquake Ground Motion maps. 

onal Seismic Hazard Mapping Project Web Site, 
s electronic 
s of this map and others. Documentation, gridded 
values, and ArcHNFO coverages used to make 
aiJable. 
The California portion of the map was producedjointly 
with the California Geological Survey. 

Map prepared by U.S. Geological Survey. 



Building Seismic KM, NEHRP Recommended 

Provisions for Seismic Regulations for New Buildings and 
other Structures, Part I - Provisions, FEMA450. 

Building Seismic Safety Council 2004, NEHRP Recommended 
Provisions for Seismic Regulations for New Buildings and 
other Structures, Part 2 - Commentary, FEMA450. 

Frankel, A, Petersen. M, Mueller, C, Haller, K, Wheeler, R, 
Leyendecker, E, Wesson, R, Harmsen, S., Cramer, C, 
Perkins, D., and Rukstales, K, 2002, Docwnentation for the 

mic Hazard Maps, U.S. 
Geological Survey Open-Hie Report 02-420. 

Frankel, A, Petersen, M, Mueller, C, Haller, K, Wheeler, R, 
■,er. E, Wesson. R, Harmsen, S., Cramer, C, 
Perkins, D., and Rukstales, K, 2004, Seismic-Hazan! Maps 
for the Contenninous United States, Sheet 6 - Horizontal 

2% Probability of Exceedance in 50 Years, U.S. Geological 

Survey Geoloi. eries, scale 1:7,000,000 

(in progress). 
Leyendecker. E K. 2001, Seismic 

Design Parameters, U.S. Geological Survey Open-Pile 

Report 01-437. 
Leyendecker, E , K. 2004, Seismic 

".ammeters, U.S. Geological Survey Open-Kle 

Report (in progress). 
National Seismic Hazard Mapping Project Web Site, 
r, U. S. Geological Survey. 



is shown enlarged in figure 1 61 3.5(4) 

- Region 2 is shown enlarged in figure 1 61 3.5(6) 

- Region 3 is shown enlarged in figure 1 61 3.5(8) 

- Region 4 is shown enlarged in figure 1 61 3.5(9) 



FIGURE 1613.5(2) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES 

OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



350 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 








Explanation 




Contour intervals 


,%g 




= 200 = 






- 1 SO- 






- 1 2.S - 






- 1 00- 




ft\\ 


— ~7 .S — 




J ) 


— <S<^> — 
==l- <^> — 

— :3 <^> — 

— ^ ^ — 

— ^<^> — 

— 1 ^ — 

— 1 <z> — 

— ^^. — 

— <s — 






Note: contours are ii 


regularly spaced 

Areas with a constant spectral 
response acceleration of 60% g 




1 1 








+ 
6.2 


Point value of spectral response 
acceleration expressed as a percent 
of gravity 


• J. 






Y 


— 1 O — 


Contoursofspectra 1 resJXlnse 
accelerationexpressed as a percent 
of gravity. Hachures point in 
direction of decreasing values. 



t^wt^ 



HHH 



100 200 300 400 500 600 KILOMEIERS 



FIGURE 1613.5(2)-continued 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR THE CONTERMINOUS UNITED STATES 

OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



2009 INTERNATIONAL BUILDING CODE® 



351 



ho 

o 

& 



-I 
m 
70 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 

8 




</> 
-I 

73 

C 

o 
-I 

c 

r 

O 
m 

<£ 
CD 



FIGURE 1613.5(3) 
MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



ho 

o 

& 



-I 

m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 
O 

O 
m 



■»?■ 




mUL UW- ft pH» ■■* m 4MAHM ^ 



FIGURE 161J.5(J)-continued 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



</> 
-I 

73 

C 

o 
-I 

c 

2 

r 

D 
m 
</> 
CD 



ho 
o 

& 



-I 

m 
73 

z 

> 

O 

z 

> 

r 

00 

c 




-I 

c 
o 
-I 

c 

r 

o 
m 

<£ 
CD 



CD 
O 
O 

o 
m 

® 



FIGURE 1613.5(4) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 

1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



ho 

o 



-I 

m 
73 

z 

> 

-I 

O 

z 

> 

r 

00 

c 



O 
O 



o 
m 

® 



Explanation 
Contour intervals, % g 

- 1 50- 

- 1 2.S - 

- 1 oo- 

- -7 :S — 

60 - 



^l-O 




:3 <z> 


- 


^.^ 


- 


■^cz> 




1 :S 




1 O 





Point value of spectral response 
ofgravity 



Contours of spectral response 
acceleration expressed as a percent 
ofgravity. Hachures point in 
direction of decreasing values. 



Locations offaults (see DISCUSSION). 

median spectral response acceleration 
times 1.5, expressed as a percent of 



DISCUSSION 

A line shown as a fault location is the projection to the earth s 
surface of the edge of the faultmpture area located closest to 
[he earth's sin 

ing design values is shown The number on the fa 

mes 1.5. The 
values on the fault portion si. for interpolation 



Selected contours near faults have been deleted for clarity. I n 
these instances, interpolation may be done using fault values and the 
nearest adjacent contour. 

Refer to the map of Maximum Considered Earthquake Ground 
Motionforthe Ci f 1 .0 sec Spectral 

Response Acceleration (Figure 1613.5(2» for additional 
and references. 




200 KILOMETERS 



FIGURE 1613.5(4)-continued 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 1 OF 

1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



</) 
-I 
73 

C 

o 
-I 

c 

r 

D 
m 
</) 
O 



ho 
o 

& 



-I 

m 
73 

z 

> 

O 

z 

> 

r 

00 

c 




Explanation 
Contour intervals, % g 
-^oo- 

— X 75- 

— X SO- 

— X OO- 

— ^ o — 

— ~7 O — 

— ^ o — 

— :S O — 
-^XO- 



Note: contours are irregularly spaced 



Point value of spectral response 
acceleration expressed as a percent 
of gravity 



Contours of spectral response 
acceleration expressed as a percent 
of gravity. Hachures point in 
direction ofdecreasing values. 



DISCUSSION 



Refer to the map 

Motion for the Contenninou ifo.2 sec Spectral 

Response Ace, 1613.5(1» 

references. 




</> 
-I 

73 

C 

o 
-I 

c 

r 

o 
m 

<£ 
CD 



100 KILOMETERS 



Index map sh< 



CD 
O 
O 

o 
m 

® 



FIGURE 1613.5(5) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 2 OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



ho 

o 



-I 

m 
73 

z 

> 

-I 

O 

z 

> 

r 

00 

c 



O 
O 



o 
m 

® 






Explanation 


Contour intervals 


%g 


- X s o - 




- X :2. 3 - 




- X oo- 




— ^ o — 




— ^ o — 




— :S O - 




— -=X-<^> — 




— S. :S — 




— ^ C3> — 




- 1 :S - 




— 1 O - 




— S 




-6-- 




— -^i 




_^» __ 




— o 




Note: contours are ir 


regularly spaced 


+ 
6.2 


Point value of spectral response 
acceleration expressed as a percent 
ofgraVlty 


- X O- 


Contours of spectral response 
acceleration expressed as a percent 
of gravity. Hachures point in 
direction of decreasing values. 




DISCUSSION 


Refer to the map ofMa lake Ground 
Motion for the Conten ates of 1 .0 sec Spectral 
Response Acceleration (Figure 1613.5(2)) for discussion and 
references. 



100 KILOMETERS 







Index map showing location of study area 



FIGURE 1613.5(6) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 2 OF 

1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



C/> 

-I 
73 

C 

o 
-I 

c 

2 

r 

D 
m 
</) 
O 



ho 
o 

& 



-I 

m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 
O 

o 
m 

® 






Explanation 


Contour interva 


s,%g 


-2.00- 




-175- 




- 1 SO- 




- 1 -^s - 




- 1 00- 




— ^ — 




-8O- 




- -7 » - 




— <^<Z> — 




— ^S O — 




— -4-0 - 




— 13 ;S — 




— 3 <^> — 




- ^2. :S - 




— ^O — 




_ X ;S — 




- X O - 




-5-- 




— «rz» — 




Note: contours are 


\ spaced 

Areas with a constant spectral 
response acceleration of 150% g 


1 1 




+ 
6.2 


Point value of spectral response 
acceleration expressed as a percent 
ofgravity 


- X O- 


Contours of spectral response 

acceleration expressed as a percent 
ofgravity. Hachures point in 
direction of decreasing values. 




DISCUSSION 


Referto the map of Maximum Considered Earthquake Ground 
Motion for the Conten ales of 0.2 sec Spectral 
Response Acceleration (Figure 1613.5(1» for discussion and 
references. 



</) 
-I 

73 

C 

o 
-I 

c 

r 

o 
m 

<£ 
CD 



100 KILOMETERS 




Index map showing location of study ai 



FIGURE 1613.5(7) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 3 OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% PERCENT OF CRITICAL DAMPING), SITE CLASS B 



ho 

o 

& 



-I 
m 
73 

z 

> 

-I 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 

® 




Contour intervals, % 

— 1 30- 

— X 2.S - 

— 1 OO- 

— ^»<Z> — 

— ^7 ^ — 

— <^<Z> — 

— ^S o - 

— ^1- o — 

— 3 CZ> — 



o 



Areas with a constant spectral 
response acceleration of 60% g 



Point value of spectral response 
acceleration expressed as a percent 
of gravity 



Contours of spectral response 

on expressed as a percent 
of gravity. Hachures point i n 
direction of decreasing values. 



Refer to the map of Maximum Considered Earthquake Ground 
Motion for the Conterminous United States ofl.O sec Spectral 
Response Acceleration (Figure 1613.5(2» for discussion and 
references. 



100 KILOMETERS 




rKjUrib I D I O.O(o) Index map showing location of study ai 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 3 OF 
1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



C/> 

-I 
73 

C 

o 
-I 

c 

2 

r 

D 
m 
</) 
O 



STRUCTURAL DESIGN 




0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING) 



Contour intervals, % 




1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING) 






Point value of spectral response 

'. .::■■ 
ofgmvity 



Contours of spectral response 

ofgmvity. Hachures point in 
direction of decreasing values. 



DISCUSSION 

Refer to the maps of Maxim arthquake Ground 

Motion for the Conterminous United States ofo.2 and 1 .0 sec 
Spectral Resp i (Figures 1613.5(1) and 1613.5(2)) 

for discussion and references. 




Index map showing location of study ai 



FIGURE 1613.5(9) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR REGION 4 OF 

0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



360 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 



Contour intervals, % g 




Areas with a constant spectral 
response acceleration ofT50% g 



C3 



Locationsofdetemrinisticzone 
boundaries (see DISCUSSION). 
The number on the boundary and 
inside the zone is the median 
Spectral response acceleration 

percent of gravity. 



0.2 SEC SPECTRAL RESPONSE ACCELERATION (510 OF CRITICAL DAMPING) 

161° 160° 159° 158° 157° 156° _ 155° 154° 



Contour intervals, % g 




ra 



Locations of detemrinistic zone 
boundaries (see DISCUSSION). 
The number on the boundary and 
inside the zone is the median 
spectral response acceleration 
timesl.5,expressed as a 
[gravity. 



1.0 SEC SPEaRAL RESPONSE ACCELERATION (510 OF CRITICAL DAMPING) 



Point value of spectral response 

on expressed as a percent 
of gravity 



ol spectral response 

of gravity. HachuiES point in 
direction of decreasing values 



DISCUSSION 

The acceleration values contoured on this map are for the random horizontal 
component of acce • nee site condition 

for the map is to be taken as Site Class B. 

The two areas shown as zone boWlda; ion to the earth' s 

surface of horizon i I accelerations 

are constant within the boundaries of the zones. The number on the boundary 
mes 1.5. 

Leyendecker. Fran epared a CD-ROM 

that contains soltw B map values by 

latitude-longitude. The software on the CD contains site coefficients that 
allow the user to adjust map values for d es. Additional 

maps at different scales are also included on the CD. The CD was prepared 

GroWld Motion maps. 

' ■ - ■■,■■■■.■ 

• ■ ■ ■ ... ■,■ 

and others. Doc I Arc/ENFO coverages used 

to make the maps are also available. 

Map prepared by U.S. Geological Survey. 



100 KILOMEIERS 



REFERENCES 

isions for Seismic 
Regulations for New Buildings and other Structures, Part 1 - Provisions, FEMA 450. 

.ions for Seismic 
Regulations for New Buildings and other Structures, Part 2 - Commentary, FEMA 450. 
Klein, E, Frankel, A, Mueller, e, Wesson, R andOkubo, P., 2001, Seismic hazard 

. . :■■■.: ■;■,■;-■. 
Bull Seism Soc. Am, v. 91, pp. 479-498. 
Klein, E, Frankel, A, Mueller, e, Wesson, R and Okubo, P., 1998. Seismic-Hazard Maps 
for Hawaii, Sheet 2 - 2' < Piv ak Horizontal 

Acceleration and 1 on for 0.2, 0.3, and 1.0 Second 

Periods U.S. Geological Survey G. on Series 1-2724, scale 1 :2,000,000. 

Leyendecker, R. 1 

Geological Survey Open-File Report 01-437. 
Leyendecker, R, Frankel, A, and Rukstales, K. 2()( n Parameters, U.S. 

rogiess). 

U. S. Geological Survey. 



FIGURE 1613.5(10) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR HAWAII OF 

0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



2009 INTERNATIONAL BUILDING CODE® 



361 



CO 

ho 



Contour intervals 


r < g 


-2.00- 




-175- 




-150- 




- 1 2.S - 




- 1 OO- 





Explar 
+ 



-50- 

-^l-<Z>- 



15- 



ho 
o 

& 



-I 
m 
73 

z 

> 

-I 

O 

z 

> 

r 

00 

c 




Point value of spectral response 
ofgravity 



ContOUIS of spectral response 

o! gravity Hachures point in 
direction of decreasing \ allies. 



Locations of faults (see DISCUSSION). 
The number on the fault is the 
medianspecb: a 1 responseaccelt 

1.5, expressed as a percent of 



DISCUSSION 

The accelemtion values contoured on this map are for the random horizontal 
component of acc< :nce site condition 

for the map is to be taken as Site Class B. 

A line shown as a ill's swface of the 

edge of the fault rupture area locatedclosesttotheearth's surface. Only the 
portion of the fault alues is shown Themunberc 

the fault is the deterministic n xmse accelemtion times 1.5. 

The values on the fault portion shown may be used for interpolation puiposes. 

Selected contours near faults have been deleted for clarity. In these i 
interpolation ma) est adjacent 

Leyendecker, FrankeL and Rukstales (2001, 2004) have prepared a CD-ROM 
that contains software to allow determin; B map values by 

ngitude. The software on the CD con 
the user to adjust map values for different Site Gasses. Additional maps at 

cales are also included on the CD. Tbe CD was prepared using the 
ie data as that used to prepare the Maximum Considered Earthquake Ground 
Motion maps. 

The National Seismic Hazard Mapping Project Web Site, 

'.. s 

and others. Docu id Arc/INPO covemges used 

to make the maps are also available. 



-I 

73 

C 

o 
-I 

c 

r 

o 
m 

<£ 
CD 



tstons for Seismic 
Regulations for New Build ictures, Part 1 - Provisions, FEMA 450. 

:is for Seismic 
Regulations for New Buildi: ntary, FEMA 450. 

Leyendecker, E.Fmnkel, A, and Rukstales, K, 2001, Seismic Design Parameters, U.S. 

Geological Sun -port 01-437. 

Leyendecker, E, Frankel, A , and Rukstales, K, 2004. Seismic Design Parameters, U.S. 
irogress). 

■ 
U. S. Geological Survey. 

R, Frankel, A, Mueller, C, and Harmsen, S., 1999, Probabilistic Seismic Hazard 
Maps of Alaska, U.S. Geological Survey Open-File Report 99-36. 

R, Frankel, A, Muell Seismic-Hazard Maps for 

and the Aleutian Islands, Sheet 2 - 2% Probability of Exceedance in 50 Years 
for Peak Horizontal Acceleni: 1 Spectral Response Accelemtion for 0.2, 

0.3, and 1.0 Second Periods U.S. Geologii ition Series 1-2679, 

scale 1:7.500,000. 



750 KILOMETERS 



CD 
O 
O 

o 
m 

® 



FIGURE 1613.5(11) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR ALASKA OF 

0.2 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



ho 

o 

& 



-I 
m 
73 

z 

> 

-I 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 

® 



Contour intervals, % g 

- X 75- 

- 1 SO- 

- 1 2.S - 

- 1 O O - 

- s»o — 

--75- 

- <SO — 

- so — 



Point value 
accelemtion expressed 
of gravity 



Contours of spectral response 
accelemtion expressed as a percent 
of gravity. Hachures point in 
direction of decreasing values. 



Locations of faults (see DISCUSSION). 
The number on the fault is the 
median spectral response accelemtion 

a percent of 
gravity. 



-40 
— 3 O- 



— A S - 

— A O- 



Note: 
irregularly spaced 




DISCUSSION 

The accelemtion values contoured on this map are for the random horizontal 
component of acceleration For design purposes, the reference site condition 
for the map is to be taken as Site Class B. 

A line shown as a fault location is the projection to the earth' s surface of the 
edge of the fault rupture area located closest to the earth's surface. Only the 
portion of the fault used in detenmmng design values is shown The number c 
the fault is the detenninistic median spectral sesponse acceleration times 1.5. 
The values on the fault portion shown may be used for interpolation purposes. 

Selected contoiu 
interpolation may irest adj acent 

Leyendecker, Frankel, and Rukstales (2001,2004) have prepared a CD-ROM 

lion of Site Class B map values by 
latitude-longitude. The software on the CD cor ients that allow 

the user to adjust i dditional maps at 

different scales I on the CD. The CD was prepared using the 

te data as that used to prepare the Maximum Considered Earthquake Ground 
Motion maps. 

The National Seismic Hazard Mapping Project Web Site, 
http://eqhazmaps.usgs.gov, contains electronic versions of this map 
and others. Documentation, gridded values, and Arc/INR) coverages used 
to make the maps are also available. 



■!.■■.. ■.■■■.■■■■.. : 

Regulations for New Buildings and other Structures. Part 1 - Provisions, FEMA 450. 
Building Seisi I :HRP Recommended Provisions foi 

1 
cker, E., Frankel, A, and Rukstales, K, 2001. Se mmeters, U.S. 

Geological Survey Open-Rle Report 01-437. 
Leyendecker, E, Frankel, A, and Rukstales, K, 2004, Seismic Design Parameters, U.S. 

cal Survey Open-Rle Report (in progress). 
National Seismic Hazard Mapping Project Web Site, http://eqhazmaps.usgs.gov, 

U. S. Geological Survey. 
Wesson, R, Fmnkel, A. i Jeismic Hazard 

Maps of Alaska, U.S. Geological Survey Open-File Report 99-36. 
Wesson, R., Frankel, A, Mueller, C, and Harmsen, S., 1 998, Seismic-Hazard Maps for 
Alaska and the Aleutian Islands, Sheet 2 - 2% Probability of Exceedance in 50 Years 
' . . . ...,::, 

0.3, and 1.0 Second Periods U.S. Geological Survey Geologic Investigation Series 1-2679, 
scale 1:7,500,000. 



750 KILOMETERS 



</) 
-I 

73 

C 

o 
-I 

c 

2 



CO 
CO 



FIGURE 1613.5(12) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR ALASKA OF 

1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



D 
m 
</) 
O 



STRUCTURAL DESIGN 



Contour intervals, % 




0.2 SEC SPECTRAL RESPONSE ACCELERATION (5 OF CRITICAL DAMPING) 



1 so- 

1 25- 
lOO- 

= s>o = 

--? ^ - 
-<3 0- 
= 50 = 
-40- 
-3 0- 

-2:0- 

- 1 S - 

- X O- 




1.0 SEC SPECTRAL RESPONSE ACCELERATION (5 OF CRITICAL DAMPING) 



Point value of spectral response 
acceleration expressed as a percent 
of gravity 



Contours of spectral response 
acceleration expressed as a percent 
of gravity. Hachures point in 
direction of decreasing values. 



DISCUSSION 

The acceleration values contoured on this map are for the random horiwntal 
:nt of acceleration For design pwposes, the reference site condition 
for the map is to be taken as SiteClassB. 

Leyendecker, Frankel, and Rukstales (2001, 2004) have prepared a CD-ROM 
that contains software to allow detennination of Site Class B map values by 
latitude-longitude. The software on the CD contains site coefficients that 
allow the user to adjust map values 'lasses. Additional maps 

at different scales are also included on the CD. The CD was prepared using the 
same data as that used to prepare the Maximwn Considered Earthquake Ground 
Motion maps. 

The National S apping Project Web Site, 

http://eqhazmaps.usgs.gov, contains electronic versions ofthis map 

id An::/INF0 coverages used 
to make the maps are also available. 



Map prepared by U.S. Geological Survey. 



KILOMEIERS 



REFERENCES 

Building Seismic ' « > \. NEHRP Recommeuded Provisions for Seismic 

Regulations for New Buildings and ot irt 1 - Provisions, FEMA 450. 

Building Seis cil 2004, NEHRP Recommended Provisions for Seismic 

:ker. E, Frankel, A, and Rukstales, K, 2001, Seismic Design Parameters, U.S. 
Geological Survey Open-Hie Report 01-437. 
Leyendecker, E, Frankel, A, and Rukstales, K, 2004, Seismic Design Parameters, U.S. 

cal Survey Open-File Report (in progress). 
Mueller, C, Frank*. "ocumentation for 

2003 USGS Seismic Hazard Maps for Puerto Rico and the U.S. Virgin Islands, U.S. 
Geological Survey Open-File Report 03-379. 
Mueller, C, Frankel, A, Petersen, M, and Leyendecker, E, 2004. S. 
for Puerto Rico and the U.S. Virgin Island, Sheet 2 - 2% Probability of 
Exceedance in N 

Response Acceleration for 0.2. 0.3, and 1 .0 Second Periods U.S. Geological Survey 
i progress). 

■/• .■■ 
U.S. Geological Survey. 



FIGURE 1613.5(13) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR PUERTO RICO, CULEBRA, VIEQUES, ST. THOMAS, 

ST. JOHN AND ST. CROIX OF 0.2 AND 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



364 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL DESIGN 








..... 

0.2 Str SPtC.I HA I. RE IPONSt All H E RAI ION {.? % L3 1 C HI t IC Al t JAW* NGI 



«4 






IMS 



60%g 



GUAM 
i Mil-:, >t •.!■.-. 



"TW 






■i . 



ap — 



N«t^ 



«r.S 



40^ g 



?!■• 



ftHLMA 



10 SEX SffCTRAL RES PON St ACCFLiRAD ON (S% OF CRITIGA L »n. 



t i ".¥ " :■ 



FIGURE 1613.5(14) 

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR GUAM AND TUTUILLA OF 

0.2 AND 1 .0 SEC SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B 



2009 INTERNATIONAL BUILDING CODE® 



365 



STRUCTURAL DESIGN 




T = Transverse 

L - Longitudinal 
V = Vertical 

P = Perimeter 



FIGURE 1614.4 
LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES 



366 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 17 
STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



SECTION 1701 
GENERAL 

1701.1 Scope. The provisions of this chapter shall govern the 
quality, workmanship and requirements for materials covered. 
Materials of construction and tests shall conform to the appli- 
cable standards listed in this code. 

1701.2 New materials. New building materials, equipment, 
appliances, systems or methods of construction not provided 
for in this code, and any material of questioned suitability pro- 
posed for use in the construction of a building or structure, shall 
be subjected to the tests prescribed in this chapter and in the 
approve d rules to determine character, quality and limitations 
of use. 

1701.3 Used materials. The use of second-hand materials that 
meet the minimum requirements of this code for new materials 
shall be permitted. 



SECTION 1702 
DEFINITIONS 

1702.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

APPROVED AGENCY. An established and recognized 
agency regularly engaged in conducting tests or furnishing 
inspection services, when such agency has been approved. 

APPROVED FABRICATOR. An established and qualified 
person, firm or corporation approved by the building official 
pursuant to Chapter 17 of this code. 

CERTIFICATE OF COMPLIANCE. A certificate stating 
that materials and products meet specified standards or that 
work was done in compliance with approved construction doc- 
uments. 

DESIGNATED SEISMIC SYSTEM. Those architectural, 
electrical and mechanical systems and their components that 
require design in accordance with Chapter 13 of ASCE 7 and 
for which the component importance factor, I p , is greater than 1 
in accordance with Section 13.1.3 of ASCE 7. 

FABRICATED ITEM. Structural, load-bearing or lateral 
load-resisting assemblies consisting of materials assembled 
prior to installation in a building or structure, or subjected to 
operations such as heat treatment, thermal cutting, cold work- 
ing or reforming after manufacture and prior to installation in a 
building or structure. Materials produced in accordance with 
standard specifications referenced by this code, such as rolled 
structural steel shapes, steel-reinforcing bars, masonry units, 
and wood structural panels or in accordance with a standard, 
listed in Chapter 35 , which provides requirements for quality 
control done under the supervision of a third-party quality con- 
trol agency shall not be considered "fabricated items." 



INSPECTION CERTIFICATE. An identification applied on 
a product by an approved agency containing the name of the 
manufacturer, the function and performance characteristics, 
and the name and identification of an approved agency that 
indicates that the product or material has been inspected and 
evaluated by an approved agency (see Section 1703.5 and 
"Label," "Manufacturer's designation" and "Mark"). 

INTUMESCENT FIRE-RESISTANT COATINGS. Thin 
film liquid mixture applied to substrates by brush, roller, spray 
or trowel which expands into a protective foamed layer to pro- 
vide fire-resistant protection of the substrates when exposed to 
flame or intense heat. 

MAIN WINDFORCE-RESISTING SYSTEM. An assem- 
blage of structural elements assigned to provide support and 
stability for the overall structure. The system generally 
receives wind loading from more than one surface. 

MASTIC FIRE-RESISTANT COATINGS. Liquid mixture 
applied to a substrate by brush, roller, spray or trowel that pro- 
vides fire-resistant protection of a substrate when exposed to 
flame or intense heat. 

SPECIAL INSPECTION. Inspection as herein required of 
the materials, installation, fabrication, erection or placement of 
components and connections requiring special expertise to 
ensure compliance with approved construction documents and 
referenced standards (see Section 1704). 

SPECIAL INSPECTION, CONTINUOUS. The full-time 
observation of work requiring special inspection by an 
approvedspecial inspector who is present in the area where the 
work is being performed. 

SPECIAL INSPECTION, PERIODIC. The part-time or 
intermittent observation of work requiring special inspection 
by an approved special inspector who is present in the area 
where the work has been or is being performed and at the com- 
pletion of the work. 

SPRAYED FIRE-RESISTANT MATERIALS. 

Cementitious or fibrous materials that are sprayed to provide 
fire-resistant protection of the substrates. 

STRUCTURAL OBSERVATION. The visual observation of 
the structural system by a registered design professional for 
general conformance to the approved construction documents. 
Structural observation does not include or waive the responsi- 
bility for the inspection required by Section 110, 1704 or other 
sections of this code. 



SECTION 1703 
APPROVALS 

1703.1 Approved agency. An approved agency shall provide 
all information as necessary for the bUilding official to deter- 
mine that the agency meets the applicable requirements. 



•I 



2009 INTERNATIONAL BUILDING CODE® 



367 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



1703.1.1 Independence. An approved agency shall be 
objective, competent and independent from the contractor 
responsible for the work being inspected. The agency shall 
also disclose possible conflicts of interest so that objectivity 
can be confirmed. 

1703.1.2 Equipment. An approved agency shall have ade- 
quate equipment to perform required tests. The equipment 
shall be periodically calibrated. 

1703.1.3 Personnel. An approved agency shall employ 
experienced personnel educated in conducting, supervising 
and evaluating tests and/or inspections. 

1703.2 Written approval. Any material, appliance, equip- 
ment, system or method of construction meeting the require- 
ments of this code shall be approved in writing after 
satisfactory completion of the required tests and submission of 
required test reports. 

1703.3 Approved record. For any material, appliance, equip- 
ment, system or method of construction that has been 
approved, a record of such approval, including the conditions 
and limitations of the approval, shall be kept on file in the build- 
ing official's office and shall be open to public inspection at 
appropriate times. 

1703.4 Performance. Specific information consisting of test 
reports conducted by an approvedtesting agency in accordance 
with standards referenced in Chapter 35, or other such informa- 
tion as necessary, shall be provided for the building official to 
determine that the material meets the applicable code require- 
ments. 

1703.4.1 Research and investigation. Sufficient technical 
data shall be submitted to the bUilding official to substanti- 
ate the proposed use of any material or assembly. If it is 
determined that the evidence submitted is satisfactory proof 
of performance for the use intended, the building official 
shall approve the use of the material or assembly subject to 
the requirements of this code. The costs, reports and investi- 
gations required under these provisions shall be paid by the 
applicant. 

1703.4.2 Research reports. Supporting data, where neces- 
sary to assist in the approval of materials or assemblies not 
specifically provided for in this code, shall consist of valid 
research reports from approve d sources. 

1703.5 Labeling. Where materials or assemblies are required 
by this code to be labeled, such materials and assemblies shall 
be labeledby an approved agency in accordance with Section 
1703. Products and materials required to be labeled shall be 
labeled in accordance with the procedures set forth in Sections 
1703.5.1 through 1703.5.3. 

1703.5.1 Testing. An approved agency shall test a represen- 
tative sample of the product or material being labeledto the 
relevant standard or standards. The approved agency shall 
maintain a record of the tests performed. The record shall 
provide sufficient detail to verify compliance with the test 
standard. 



1703.5.2 Inspection and identification. The approved 
agency shall periodically perform an inspection, which 
shall be in-plant if necessary, of the product or material that 
is to be labeled. The inspection shall verify that the labeled 
product or material is representative of the product or mate- 
rial tested. 

1703.5.3 Label information. The label shall contain the 
manufacturer's or distributor's identification, model num- 
ber' serial number or definitive information describing the 
product or material's performance characteristics and 
approved agency 's identification. 

1703.6 Evaluation and follow-up inspection services. Where 
structural components or other items regulated by this code are 
not visible for inspection after completion of a prefabricated 
assembly, the applicant shall submit a report of each prefabri- 
cated assembly. The report shall indicate the complete details 
of the assembly, including a description of the assembly and its 
components, the basis upon which the assembly is being evalu- 
ated, test results and similar information and other data as nec- 
essary for the bUilding official to determine conformance to 
this code. Such a report shall be approvedby the bUilding offi- 
cial. 

1703.6.1 Follow-up inspection. The applicant shall pro- 
vide for special inspections of fabricated items in accor- 
dance with Section 1704.2. 

1703.6.2 Test and inspection records. Copies of necessary 
test and inspection records shall be filed with the building 
official. 



SECTION 1704 
SPECIAL INSPECTIONS 

1704.1 General. Where application is made for construction as 
described in this section, the owner or the registered design 
professional in responsible charge acting as the owner's agent 
shall employ one or more approved agencies to perform 
inspections during construction on the types of work listed 
under Section 1704. These inspections are in addition to the 
inspections identified in Section 110. 

The special inspector shall be a qualified person who shall 
demonstrate competence, to the satisfaction of the bUilding 
official, for the inspection of the particular type of construction 
or operation requiring special inspection. The registered 
design professional in responsible charge and engineers of 
record involved in the design of the project are permitted to act 
as the approved agency and their personnel are permitted to act 
as the special inspector for the work designed by them, pro- 
vided those personnel meet the qualification requirements of 
this section to the satisfaction of the bUilding official. The spe- 
cial inspector shall provide written documentation to the build- 
ing official demonstrating his or her competence and relevant 
experience or training. Experience or training shall be consid- 
ered relevant when the documented experience or training is 
related in complexity to the same type of special inspection 
activities for projects of similar complexity and material quali- 



368 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



ties. These qualifications are in addition to qualifications speci- 
fied in other sections of this code. 

Exceptions: 

1. Special inspections are not required for work of a 
minor nature or as warranted by conditions in the 
jurisdiction as approvedby the building official. 

2. Special inspections are not required for building com- 
ponents unless the design involves the practice of pro- 
fessional engineering or architecture as defined by 
applicable state statutes and regulations governing 
the professional registration and certification of engi- 
neers or architects. 

3. Unless otherwise required by the bUilding official, 
special inspections are not required for Group U 
occupancies that are accessory to a residential occu- 
pancy including, but not limited to, those listed in 
Section 312.1. 

1704.1.1 Statement of special inspections. The applicant 
shall submit a statement of special inspections prepared by 
the registered design professional in responsible charge in 
accordance with Section 107.1 as a condition for issuance. 
This statement shall be in accordance with Section 1705. 

Exceptions: 

1. A statement of special inspections is not required 
for structures designed and constructed in accor- 
dance with the conventional construction provi- 
sions of Section 2308. 

2. The statement of special inspections is permitted 
to be prepared by a qualified person approvedby 
the bUilding official for construction not designed 
by a registered design professional. 

1704.1.2 Report requirement. Special inspectors shall 
keep records of inspections. The special inspector shall fur- 
nish inspection reports to the building official, and to the 
registered design professional in responsible charge. 
Reports shall indicate that work inspected was or was not 
completed in conformance to approved construction docu- 
ments. Discrepancies shall be brought to the immediate 
attention of the contractor for correction. If they are not cor- 
rected, the discrepancies shall be brought to the attention of 
the building official and to the registered design profes- 
sional in responsible charge prior to the completion of that 
phase of the work. A final report documenting required spe- 
cialinspections and correction of any discrepancies noted in 
the inspections shall be submitted at a point in time agreed 
upon prior to the start of work by the applicant and the 
bUilding official. 

1704.2 Inspection of fabricators. Where fabrication of struc- 
turalload-bearing members and assemblies is being performed 
on the premises of a fabricator's shop, specialinspection of the 
fabricated items shall be required by this section and as 
required elsewhere in this code. 

1704.2.1 Fabrication and implementation procedures. 

The special inspector shall verify that the fabricator main- 
tains detailed fabrication and quality control procedures that 



provide a basis for inspection control of the workmanship 
and the fabricator's ability to conform to approved con- 
struction documents and referenced standards. The special 
inspector shall review the procedures for completeness and 
adequacy relative to the code requirements for the fabrica- 
tor's scope of work. 

Exception: Special inspections as required by Section 
1704.2 shall not be required where the fabricator is 
approved'm accordance with Section 1704.2.2. 

1704.2.2 Fabricator approval. Special inspections 
required by Section 1704 are not required where the work is 
done on the premises of a fabricator registered and approved 
to perform such work without special inspection. Approval 
shall be based upon review of the fabricator's written proce- 
dural and quality control manuals and periodic auditing of 
fabrication practices by an approved special inspection 
agency. At completion of fabrication, the approved fabrica- 
tor shall submit a certificate of compliance to the building 
official stating that the work was performed in accordance 
with the approved construction documents. 

1704.3 Steel construction. The special inspections for steel 
elements of buildings and structures shall be as required by 
Section 1704.3 and Table 1704.3. 

Exceptions: 

1. Special inspection of the steel fabrication process 
shall not be required where the fabricator does not 
perform any welding, thermal cutting or heating oper- 
ation of any kind as part of the fabrication process. In 
such cases, the fabricator shall be required to submit a 
detailed procedure for material control that demon- 
strates the fabricator's ability to maintain suitable 
records and procedures such that, at any time during 
the fabrication process, the material specification, 
grade and mill test reports for the main stress-carrying 
elements are capable of being determined. 

2. The special inspector need not be continuously pres- 
ent during welding of the following items, provided 
the materials, welding procedures and qualifications 
of welders are verified prior to the start of the work; 
periodic inspections are made of the work in progress 
and a visual inspection of all welds is made prior to 
completion or prior to shipment of shop welding. 

2.1. Single-pass fillet welds not exceeding 5/ 16 inch 
(7.9 mm) in size. 

2.2. Floor and roof deck welding. 

2.3. Welded studs when used for structural dia- 
phragm. 

2.4. Welded sheet steel for cold-formed steel 
members. 

2.5. Welding of stairs and railing systems. 

1704.3.1 Welding. Welding inspection and welding inspec- 
tor qualification shall be in accordance with this section. 



2009 INTERNATIONAL BUILDING CODE® 



369 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 





TABLE 1704.3 
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION 






VERIFICATION AND INSPECTION 


CONTINUOUS 


PERIODIC 


REFERENCED 
STANDARD a 


IBC REFERENCE 




1. Material verification of high- strength bolts, nuts and 
washers : 


1 


a. Identification markings to conform to ASTM 
standards specified in the approved 
construction documents. 


- 


X 


AISC 360, 
Section A3 .3 and 
applicable ASTM 
material standards 






b. Manufacturer's certificate of compliance 
required. 


- 


X 


- 


- 




2. Inspection of high-strength bolting: 




a. Snug-tight j oints . 




X 


AISC 360, 
Section M2 .5 


1704.3.3 


b.Pretensioned and slip-critical joints using 
turn-of-nut with matchmarking , twist-off bolt or 
direct tension indicator methods of installation. 




X 


c.Pretensioned and slip-critical joints using 
turn-of-nut without matchmarking or calibrated 
wrench methods of installation. 


X 


- 


3 . Material verification of structural steel and 
cold-formed steel deck: 


a. For structural steel, identification markings to 
conform to AISC 360. 




X 


AISC 360, 
Section M5 .5 




b. For other steel, identification markings to conform 
to ASTM standards specified in the approved 
construction documents. 


- 


X 


Applicable ASTM 
material standards 


c. Manufacturer's certified test reports. 




X 








4. Material verification of weld filler materials: 


1 


a. Identification markings to conform to AWS 
specification in the approved construction 
documents. 


- 


X 


AISC 360, 

Section A3 .5 and 

applicable AWS 

AS documents 


- 




b. Manufacturer's certificate of compliance required. 


- 


X 


- 


- 




5. Inspection of welding: 




a. Structural steel and cold-formed steel deck: 


I 


1) Complete and partial joint penetration groove 
welds. 


X 


- 


AWS Dl.l 


1704.3.1 




2) Multipass fillet welds. 


X 


- 




3) Single-pass fillet welds> 5/ 16 " 


X 


- 


1 


4) Plug and slot welds . 


X 




5) Single-pass fillet welds < 5/ 16 " 


- 


X 




6) Floor and roof deck welds. 


- 


X 


AWS D1.3 





(continued) 



370 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



TABLE 1704.3-continued 
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION 



VERIFICATION AND INSPECTION 


CONTINUOUS 


PERIODIC 


REFERENCED 
STANDARD a 


IBC 
REFERENCE 


b. Reinforcing steel: 








- 


1) Verification of weldability of reinforcing steel 
other than ASTM A 706 . 


- 


X 


AWS D1.4 ACI 318: Section 3.5.2 


2) Reinforcing steel resisting flexural and axial 
forces in intermediate and special moment 
frames, and boundary elements of special 
structural walls of concrete and shear 
reinforcement. 


X 


- 


3) Shear reinforcement. 


X 




4) Other reinforcing steel. 


- 


X 


6. Inspection of steel frame joint details for compliance: 


a. Details such as bracing and stiffening. 


- 


X 


- 


1704.3.2 


b. Member locations. 


- 


X 


c. Application of joint details at each connection. 




X 



For SI: 1 inch = 25.4 mm. 

a. Where applicable, see also Section 1707.1, Special inspection for seismic resistance. 



I 



1704.3.1.1 Structural steel. Welding inspection and 
welding inspector qualification for structural steel shall 
be in accordance with AWS DLL 

1704.3.1.2 Cold-formed steel. Welding inspection and 
welding inspector qualification for cold-formed steel 
floor and roof decks shall be in accordance with AWS 
D1.3. 

1704.3.1.3 Reinforcing steel. Welding inspection and 
welding inspector qualification for reinforcing steel shall 
be in accordance with AWS D1.4 and ACI 318. 

1704.3.2 Details. The special inspector shall perform an 
inspection of the steel frame to verify compliance with the 
details shown on the approved construction documents, 
such as bracing, stiffening, member locations and proper 
application of joint details at each connection. 

1704.3.3 High-strength bolts. Installation of high-strength 
bolts shall be inspected in accordance with AISC 360. 

1704.3.3.1 General. While the work is in progress, the 
special inspector shall determine that the requirements 
for bolts, nuts, washers and paint; bolted parts and instal- 
lation and tightening in such standards are met. For bolts 
requiring pretensioning, the special inspector shall 
observe the preinstallation testing and calibration proce- 
dures when such procedures are required by the installa- 
tion method or by project plans or specifications; 
determine that all plies of connected materials have been 
drawn together and properly snugged and monitor the 
installation of bolts to verify that the selected procedure 
for installation is properly used to tighten bolts. For 
joints required to be tightened only to the snug-tight con- 



dition, the special inspector need only verify that the con- 
nected materials have been drawn together and properly 
snugged. 

1704.3.3.2 Periodic monitoring. Monitoring of bolt 
installation for pretensioning is permitted to be per- 
formed on a periodic basis when using the turn-of-nut 
method with matchmarking techniques, the direct ten- 
sion indicator method or the alternate design fastener 
(twist-off bolt) method. Joints designated as snug tight 
need be inspected only on a periodic basis. 

1704.3.3.3 Continuous monitoring. Monitoring of bolt 
installation for pretensioning using the calibrated 
wrench method or the turn-of-nut method without 
matchmarking shall be performed on a continuous basis. 

1704.3.4 Cold-formed steel trusses spanning 60 feet or 
greater. Where a cold-formed steel truss clear span is 60 
feet (18 288 mm) or greater, the special inspector shall ver- 
ify that the temporary installation restraint/bracing and the 
permanent individual truss member restraint/bracing are 
installed in accordance with the approved truss submittal 
package. 

1704.4 Concrete construction. The special inspections and 
verifications for concrete construction shall be as required by 
this section and Table 1704.4. 

Exception: Special inspections shall not be required for: 

1. Isolated spread concrete footings of buildings three 
stories or less above grade plane that are fully sup- 
ported on earth or rock. 



2009 INTERNATIONAL BUILDING CODE® 



371 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



2. Continuous concrete footings supporting walls of 
buildings three stories or less above grade plane that 
are fully supported on earth or rock where: 

2.1. The footings support walls of light-frame con- 
struction; 

2.2. The footings are designed in accordance with 
Table 1809.7; or 

2.3. The structural design of the footing is based 
on a specified compressive strength, f' c no 
greater than 2,500 pounds per square inch 



(psi) (17.2 MPa), regardless of the compres- 
sive strength specified in the construction 
documents or used in the footing construction. 

3. Nonstructural concrete slabs supported directly on 
the ground, including prestressed slabs on grade, 
where the effective pre stress in the concrete is less 
than 150 psi (1.03 MPa). 

4. Concrete foundation walls constructed in accordance 
with Table 1807.1.6.2. 

5. Concrete patios, driveways and sidewalks, on grade. 



TABLE 1704.4 
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION 



VERIFICATION AND INSPECTION 


CONTINUOUS 


PERIODIC 


REFERENCED 

STANDARD 3 


IBC REFERENCE 


1. Inspection of reinforcing steel, including 
prestressing tendons, and placement. 


- 


X 


ACI318: 3.5,7.1-7.7 


1913.4 


2. Inspection of reinforcing steel welding in 
accordance with Table 1704.3, Item 5b. 


- 


- 


AWS D1.4 
ACI318: 3.5.2 


- 


3. Inspection of bolts to be installed in concrete 
prior to and during placement of concrete where 
allowable loads have been increased or where 
strength design is used. 


X 


- 


ACI318: 

8.1.3,21.2.8 


1911.5, 
1912.1 


4. Inspection of anchors installed in hardened 
concrete. 


- 


X 


ACI318: 
3.8.6, 8.1.3,21.2.8 


1912.1 


5. Verifying use of required design mix. 


- 


X 


ACI 318: Ch. 4, 5.2-5.4 


1904.2.2, 1913.2, 
1913.3 


6. At the time fresh concrete is sampled to fabricate 
specimens for strength tests, perform slump and 
air content tests, and determine the temperature 
of the concrete. 


X 


- 


ASTM C 172 

ASTM C 31 

ACI 318: 5.6, 5.8 


1913.10 


7. Inspection of concrete and shotcrete placement 
for proper application techniques. 


X 


- 


ACI 318: 5.9, 5.10 


1913.6,1913.7,1913.8 


8 . Inspection for maintenance of specified curing 
temperature and techniques. 


- 


X 


ACI 318: 5.11-5.13 


1913.9 


9. Inspection of prestressed concrete: 

a. Application of prestressing forces. 

b. Grouting of bonded prestressing tendons in 
the seismic-force-resisting system. 


X 
X 


- 


ACI 318: 18.20 
ACI 318: 18.18.4 


- 


10. Erection of precast concrete members. 


- 


X 


ACI 318: Ch. 16 


- 


11 . Verification of in-situ concrete strength, prior to 
stressing of tendons in posttensioned concrete 
and prior to removal of shores and forms from 
beams and structural slabs . 


- 


X 


ACI 318: 6.2 


- 


12. Inspect formwork for shape, location and 
dimensions of the concrete member being 
formed . 




X 


ACI 318: 6.1.1 





For SI: 1 inch = 25.4 mm. 

a. Where applicable, see also Section 1707.1, Special inspection for seismic resistance. 



372 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



1704.4.1 Materials. In the absence of sufficient data or doc- 
umentation providing evidence of conformance to quality 
standards for materials in Chapter 3 of ACI 318, the build- 
ing official shall require testing of materials in accordance 
with the appropriate standards and criteria for the material 
in Chapter 3 of ACI 318. Weldability of reinforcement, 
except that which conforms to ASTM A 706, shall be 
determined in accordance with the requirements of Section 
3.5.2 of ACI 318. 

1704.5 Masonry construction. Masonry construction shall be 
inspected and verified in accordance with the requirements of 
Sections 1704.5.1 through 1704.5.3, depending on the occu- 
pancy category of the building or structure. 

Exception: Special inspections shall not be required for: 

1. Empirically designed masonry, glass unit masonry or 
masonry veneer designed by Section 2109, 2110 or 
Chapter 14, respectively, or by Chapter 5, 6 or 7 of 
TMS 402/ACI 530/ASCE 5, respectively, when they 
are part of structures classified as Occupancy Cate- 
gory I, II or III in accordance with Section 1604.5. 

2. Masonry foundation walls constructed in accordance 
with Table 1807.1.6.3(1), 1807.1.6.3(2), 
1807.1.6.3(3) or 1807.1.6.3(4). 

3. Masonry fireplaces, masonry heaters or masonry 
chimneys installed or constructed in accordance with 
Section 2111, 2112 or 2113, respectively. 

1704.5.1 Empirically designed masonry, glass unit 
masonry and masonry veneer in Occupancy Category 
IV. The minimum special inspection progrmn for empirically 
designed masonry, glass unit masonry or masonry veneer 
designed by Section 2109,21 10 or Chapter 14, respectively, 
or by Chapter 5,6 or 7 ofTMS 402/ACI 530/ASCE 5, respec- 
tively, in structures classified as Occupancy Category IV, in 
accordance with Section 1604.5, shall comply with Table 
1704.5.1. 

1704.5.2 Engineered masonry in Occupancy Category I, 
II or III. The minimum special inspection program for 
masonry designed by Section 2107 or 2108 or by chapters 
other than Chapter 5,6 or 7 ofTMS 402/ACI 530/ASCE 5 in 
structures classified as Occupancy Category I, II or III, in 
accordance with Section 1604.5, shall comply with Table 
1704.5.1. 

1704.5.3 Engineered masonry in Occupancy Category 
IV. The minimum special inspection program for masonry 
designed by Section 2107 or 2108 or by chapters other than 
Chapter 5,6 or 7 ofTMS 402/ACI 530/ASCE 5 in structures 
classified as Occupancy Category IV, in accordance with 
Section 1604.5, shall comply with Table 1704.5.3. 

1704.6 Wood construction. Special inspections of the fabrica- 
tion process of prefabricated wood structural elements and 
assemblies shall be in accordance with Section 1704.2. Special 
inspections of site-built assemblies shall be in accordance with 
this section. 



1704.6.1 High-load diaphragms. High-load diaphragms 
designed in accordance with Table 2306.2.1 (2) shall be 
installed with special inspections as indicated in Section 
1704.1. The special inspector shall inspect the wood struc- 
tural panel sheathing to ascertain whether it is of the grade 
and thickness shown on the approvedbmlding plans. Addi- 
tionally, the special inspector must verify the nominal size 
of framing members at adjoining panel edges, the nail or sta- 
ple diameter and length, the number of fastener lines and 
that the spacing between fasteners in each line and at edge 
margins agrees with the approvedbmlding plans. 

1704.6.2 Metal-plate-connected wood trusses spanning 
60 feet or greater. Where a truss clear span is 60 feet (18 
288 mm) or greater, the special inspector shall verify that the 
temporary installation restraint/bracing and the permanent 
individual truss member restraint/bracing are installed in 
accordance with the approved truss submittal package. 

1704.7 Soils. Special inspections for existing site soil condi- 
tions, fill placement and load-bearing requirements shall be as 
required by this section and Table 1704.7. The approved 
geotechnical report, and the construction documents prepared 
by the registered design professionals shall be used to deter- 
mine compliance. During fill placement, the special inspector 
shall determine that proper materials and procedures are used 
in accordance with the provisions of the approve ^geotechnical 
report. 

Exception: Where Section 1803 does not require reporting 
of materials and procedures for fill placement, the special 
inspector shall verify that the in-place dry density of the 
compacted fill is not less than 90 percent of the maximum 
dry density at optimum moisture content determined in 
accordance with ASTM D 1557. 

1704.8 Driven deep foundations. Special inspections shall be 
performed during installation and testing of driven deep foun- 
dation elements as required by Table 1704.8. The approved 
geotechnical report, and the construction documents prepared 
by the registered design professionals, shall be used to deter- 
mine compliance. 

1704.9 Cast-in-place deep foundations. Special inspections 
shall be performed during installation and testing of 
cast-in-place deep foundation elements as required by Table 
1704.9. The approve d geotechnical report, and the construc- 
tion documents prepared by the registered design profession- 
als, shall be used to determine compliance. 

1704.10 Helical pile foundations. Special inspections shall be 
performed continuously during installation of helical pile 
foundations. The information recorded shall include installa- 
tion equipment used, pile dimensions, tip elevations, final 
depth, final installation torque and other pertinent installation 
data as required by the registered design professional in 
responsible charge. The approved geotechnical report and the 
construction documents prepared by the registered design pro- 
fessional shall be used to determine compliance. 

1704.11 Vertical masonry foundation elements. Special 
inspection shall be performed in accordance with Section 
1704.5 for vertical masonry foundation elements. 



2009 INTERNATIONAL BUILDING CODE® 



373 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



TABLE 1704.5.1 
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION 



VERIFICATION AND INSPECTION 


FREQUENCY OF INSPECTION 


REFERENCE FOR CRITERIA 


CONTINUOUS 


PERIODIC 


IBC SECTION 


TMS 402/ACI 
530/ASCE 5 a 


TMS 602/ACI 
530.1/ASCE6 a 


1. Compliance with required inspection pro- 
visions of the construction documents and 
the approved submittals shall be verified. 




X 






Art. 1.5 


2. Verification of f' m and f' AAC prior to con- 
struction except where specifically 
exempted by this code. 


- 


X 


- 


- 


Art. 1.4B 


3. Verification of slump flow and VSI as 
delivered to the site for self-consolidating 
grout. 


X 








Art. 1.5B.l.b.3 


4. As masonry construction begins, the following shall be verified to ensure compliance: 


a. Proportions of site- prepared mortar. 


- 


X 


- 


- 


Art. 2.6A 


b. Construction of mortar joints. 


- 


X 


- 


- 


Art. 3.3B 


c. Location of reinforcement, 
connectors, prestressing tendons 
and anchorages. 




X 






Art. 3.4, 3.6A 


d. Prestressing technique. 




X 






Art. 3.6B 


e. Grade and size of prestressing 
tendons and anchorages. 


- 


X 


- 


- 


Art. 2.4B, 2.4H 


5. During construction the inspection program shall verify: 


a. Size and location of structural 
elements. 




X 






Art. 3.3F 


b. Type, size and location of anchors, 
including other details of anchorage 
of masonry to structural members , 
frames or other construction. 


- 


X 


- 


Sec. 1.2.2(e), 
1.16.1 


- 


c. Specified size, grade and type of 
reinforcement, anchor bolts, 
prestressing tendons and 
anchorages . 




X 




Sec. 1.15 


Art. 2.4, 3.4 


d. Welding of reinforcing bars. 


X 






Sec. 2.1.9.7.2, 
3.3.3.4(b) 




e. Preparation, construction and 
protection of masonry during cold 
weather (temperature below 40°F) 
or hot weather (temperature above 
90°F). 


- 


X 


Sec. 2104.3, 
2104.4 


- 


Art. 1.8C, 
1.8D 


f. Application and measurement of 
prestressing force . 


X 








Art. 3.6B 



(continued) 



374 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



TABLE 1704.5.1 -continued 
LEVEL 1 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION 



VERIFICATION AND INSPECTION 


FREQUENCY OF INSPECTION 


REFERENCE FOR CRITERIA 


CONTINUOUS 


PERIODIC 


IBC SECTION 


TMS 402/ACI 
530/ASCE 5 a 


TMS 602/ACI 
530.1/ASCE6 a 


6. Prior to grouting, the following shall be verified to ensure compliance: 


a. Grout space is clean. 




X 






Art. 3. 2D 


b. Placement of reinforcement and 
connectors, and prestressing 
tendons and anchorages. 


- 


X 


- 


Sec. 1.13 


Art. 3.4 


c. Proportions of site-prepared grout 
and prestressing grout for bonded 
tendons. 




X 






Art. 2.6B 


d. Construction of mortar joints. 




X 






Art. 3.3B 


7. Grout placement shall be verified to 
ensure compliance : 


X 


- 


- 


- 


Art. 3.5 


a. Grouting of prestressing bonded 
tendons. 


X 


- 


- 


- 


Art. 3.6C 


8. Preparation of any required grout speci- 
mens, mortar specimens and/or prisms 
shall be observed. 




X 


Sec. 2105 .2.2, 
2105.3 




Art. 1.4 



For 51: °C = [((F) - 32]1 1 .8. 

a. The specific standards referenced are those listed in Chapter 35 . 



2009 INTERNATIONAL BUILDING CODE® 



375 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



TABLE 1704.5.3 
LEVEL 2 REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION 



VERIFICATION AND INSPECTION 


CONTINUOUS 


PERIODIC 


REFERENCE FOR CRITERIA 


IBC SECTION 


TMS 402/ACI 
530/ASCE 5 a 


TMS 602/ACI 
530.1/ASCE 6 a 


1. Compliance with required inspection provi- 
sions of the construction documents and the 
approved submittals. 




X 






Art. 1.5 


2. Verification off' m and f MC prior to construc- 
tion and for every 5,000 square feet during 
construction. 


- 


X 


- 


- 


Art. 1.4B 


3. Verification of proportions of materials in 
premixed or preblended mortar and grout as 
delivered to the site. 


- 


X 


- 


- 


Art. 1.5B 


4. Verification of slump flow and VSI as deliv- 
ered to the site for self-consolidating grout. 


X 








Art. 1.5B.l.b.3 


5 . The following shall be verified to ensure compliance : 


a. Proportions of site- prepared mortar, 
grout and prestressing grout for bonded 
tendons. 


- 


X 


- 


- 


Art. 2.6A 


b. Placement of masonry units and 
construction of mortar joints. 




X 






Art. 3.3B 


c. Placement of reinforcement, connectors 
and prestressing tendons and 
anchorages . 




X 




Sec. 1.15 


Art. 3.4,3.6A 


d. Grout space prior to grout. 


X 


- 


- 


- 


Art. 3. 2D 


e. Placement of grout. 


X 


- 


- 


- 


Art. 3.5 


f . Placement of prestressing grout. 


X 








Art. 3.6C 


g. Size and location of structural elements. 




X 






Art. 3.3F 


h. Type, size and location of anchors, 
including other details of anchorage of 
masonry to structural members , frames 
or other construction. 


X 


- 


- 


Sec. 1.2.2(e), 
1.16.1 


- 


i. Specified size, grade and type of 
reinforcement, anchor bolts, 
prestressing tendons and anchorages. 


- 


X 


- 


Sec. 1.15 


Art. 2.4,3.4 


j . Welding of reinforcing bars. 


X 






Sec. 2.1.9.7.2, 
3.3.3.4 (b) 




k. Preparation, construction and protection 
of masonry during cold weather 
(temperature below 40°F) or hot 
weather (temperature above 90°F) . 


- 


X 


Sec. 2104.3, 
2104.4 


- 


Art. 1.8C, 1.8D 


1. Application and measurement of 
prestressing force . 


X 


- 


- 


- 


Art. 3.6B 


6. Preparation of any required grout specimens 
and/or prisms shall be observed. 


X 




Sec. 2105 .2.2, 
2105.3 




Art. 1.4 



For 51: °C = [((F) - 32]/1.8, 1 square foot = 0.0929 m 2 - 

a. The specific standards referenced are those listed in Chapter 35 . 



376 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



TABLE 1704.7 
REQUIRED VERIFICATION AND INSPECTION OF SOILS 



VERIFICATION AND INSPECTION TASK 


CONTINUOUS DURING TASK LISTED 


PERIODICALLY DURING TASK LISTED 


1 . Verify materials below shallow foundations are adequate to 
achieve the design bearing capacity. 


- 


X 


2. Verify excavations are extended to proper depth and have 
reached proper material. 




X 


3. Perform classification and testing of compacted fill 
materials. 


- 


X 


4. Verify use of proper materials, densities and lift thicknesses 
during placement and compaction of compacted fill. 


X 


- 


5. Prior to placement of compacted fill, observe subgrade and 
verify that site has been prepared properly. 




X 



TABLE 1704.8 
REQUIRED VERIFICATION AND INSPECTION OF DRIVEN DEEP FOUNDATION ELEMENTS 



VERIFICATION AND INSPECTION TASK 


CONTINUOUS DURING TASK LISTED 


PERIODICALLY DURING TASK LISTED 


1 . Verify element materials, sizes and lengths comply with the 
requirements . 


X 


- 


2. Determine capacities of test elements and conduct additional 
load tests, as required. 


X 




3. Observe driving operations and maintain complete and 
accurate records for each element. 


X 


- 


4. Verify placement locations and plumbness, confirm type and 
size of hammer, record number of blows per foot of 
penetration, determine required penetrations to achieve design 
capacity, record tip and butt elevations and document 
any damage to foundation element. 


X 




5. For steel elements, perform additional inspections in 
accordance with Section 1704.3. 






6. For concrete elements and concrete-filled elements, perform 
additional inspections in accordance with Section 1704.4. 


- 


- 


7. For specialty elements, perform additional inspections as 
determined by the registered design professional in 
responsible charge. 







TABLE 1704.9 
REQUIRED VERIFICATION AND INSPECTION OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS 



VERIFICATION AND INSPECTION TASK 


CONTINUOUS DURING TASK LISTED 


PERIODICALLY DURING TASK LISTED 


1 . Observe drilling operations and maintain complete and 
accurate records for each element. 


X 


- 


2. Verify placement locations and plumbness, confirm element 
diameters, bell diameters (if applicable), lengths, embedment 
into bedrock (if applicable) and adequate end-bearing strata 
capacity. Record concrete or grout volumes. 


X 




3. For concrete elements, perform additional inspections in 
accordance with Section 1704.4. 


- 


- 



2009 INTERNATIONAL BUILDING CODE® 



377 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



1704.12 Sprayed fire-resistant materials. Special inspec- 
tions for sprayed fire-resistant materials applied to floor, roof 
and wall assemblies and structural members shall be in accor- 
dance with Sections 1704.12.1 through 1704.12.6. Special 
inspections shall be based on the fire-resistance design as des- 
ignated in the approved construction documents. The tests set 
forth in this section shall be based on samplings from specific 
floor, roof and wall assemblies and structural members. Spe- 
cial inspections shall be performed after the rough installation 
of electrical, automatic sprinkler, mechanical and plumbing 
systems and suspension systems for ceilings, where applicable. 

1704.12.1 Physical and visual tests. The special inspec- 
tions shall include the following tests and observations to 
demonstrate compliance with the listing and the fire-resis- 
tance rating: 

1. Condition of substrates. 

2. Thickness of application. 

3. Density in pounds per cubic foot (kg/m 3 ). 

4. Bond strength adhesion/cohesion. 

5. Condition of finished application. 

1704.12.2 Structural member surface conditions. The 
surfaces shall be prepared in accordance with the approved 
fire-resistance design and the written instructions of 
approvedmanufacturers. The prepared surface of structural 
members to be sprayed shall be inspected before the appli- 
cation of the sprayed fire-resistant material. 

1704.12.3 Application. The substrate shall have a mini- 
mum ambient temperature before and after application as 
specified in the written instructions of approved manufac- 
turers. The area for application shall be ventilated during 
and after application as required by the written instructions 
of app roved manufacturers. 

1704.12 .4 Thickness. No more than 10 percent of the thick- 
ness measurements of the sprayed fire-resistant materials 
applied to floor, roof and wall assemblies and structural 
members shall be less than the thickness required by the 
approved fire-resistance design, but in no case less than the 
minimum allowable thickness required by Section 
1704.12.4.1. 

1704.12.4.1 Minimum allowable thickness. For design 
thicknesses 1 inch (25 mm) or greater, the minimum 
allowable individual thickness shall be the design thick- 
ness minus i/ 4 inch (6.4 mm). For design thicknesses less 
than 1 inch (25 mm), the minimum allowable individual 
thickness shall be the design thickness minus 25 percent. 
Thickness shall be determined in accordance with 
ASTM E 605. Samples of the sprayed fire-resistant 
materials shall be selected in accordance with Sections 

1704.12.4.2 and 1704.12.4.3. 

704.12.4.2 Floor, roof and wall assemblies. The thick- 
ness of the sprayed fire-resistant material applied to 
floor, roof and wall assemblies shall be determined in 
accordance with ASTM E 605, making not less than four 
measurements for each 1,000 square feet (93 m 2 ) of the 
sprayed area in each story or portion thereof. 



1704.12.4.2.1 Cellular decks. Thickness measure- 
ments shall be selected from a square area, 12 inches 
by 12 inches (305 mm by 305 mm) in size. A mini- 
mum of four measurements shall be made, located 
symmetrically within the square area. 

1704.12.4.2.2 Fluted decks. Thickness measure- 
ments shall be selected from a square area, 12 inches 
by 12 inches (305 mm by 305 mm) in size. A mini- 
mum of four measurements shall be made, located 
symmetrically within the square area, including one 
each of the following: valley, crest and sides. The 
average of the measurements shall be reported. 

1704.12.4.3 Structural members. The thickness of the 
sprayed fire-resistant material applied to structural mem- 
bers shall be determined in accordance with ASTM E 
605. Thickness testing shall be performed on not less 
than 25 percent of the structural members on each floor. 

1704.12.4.3.1 Beams and girders. At beams and 
girders thickness measurements shall be made at nine 
locations around the beam or girder at each end of a 
12-inch (305 mm) length. 

1704.12.4.3.2 Joists and trusses. At joists and 
trusses, thickness measurements shall be made at 
seven locations around the joist or truss at each end of 
a 12-inch (305 mm) length. 

1704.12.4.3.3 Wide-flanged columns. At 
wide-flanged columns, thickness measurements shall 
be made at 12 locations around the column at each end 
of a 12-inch (305 mm) length. 

1704.12.4.3.4 Hollow structural section and pipe 
columns. At hollow structural section and pipe col- 
umns, thickness measurements shall be made at a 
minimum of four locations around the column at each 
end of a 12-inch (305 mm) length. 

1704.12.5 Density. The density of the sprayed fire-resistant 
material shall not be less than the density specified in the 
approved fire-resistance design. Density of the sprayed 
fire-resistant material shall be determined in accordance 
with ASTM E 605. The test samples for determining the 
density of the sprayed fire-resistant materials shall be 
selected as follows: 

1. From each floor, roof and wall assembly at the rate of 
not less than one sample for every 2,500 square feet 
(232 m 2 ) or portion thereof of the sprayed area in each 
story. 

2. From beams, girders, trusses and columns at the rate 
of not less than one sample for each type of structural 
member for each 2,500 square feet (232 m 2 ) of floor 
area or portion thereof in each story. 

1704.12.6 Bond strength. The cohesive/adhesive bond 
strength of the cured sprayed fire-resistant material applied 
to floor, roof and wall assemblies and structural members 
shall not be less than 150 pounds per square foot (psf) (7.18 
kN/m 2 ) . The cohesive/adhesive bond strength shall be deter- 
mined in accordance with the field test specified in ASTM E 
736 by testing in-place samples of the sprayed fire-resistant 



378 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



I 



material selected in accordance with Sections 1704.12.6.1 
through 1704.12.6.3. 

1704.12.6.1 Floor, roof and wall assemblies. The test 
samples for determining the cohesive/adhesive bond 
strength of the sprayed fire-resistant materials shall be 
selected from each floor, roof and wall assembly at the 
rate of not less than one sample for every 2,500 square 
feet (232 m 2 ) of the sprayed area in each story or portion 
thereof. 

1704.12.6.2 Structural members. The test samples for 
determining the cohesive/adhesive bond strength of the 
sprayed fire-resistant materials shall be selected from 
beams, girders, trusses, columns and other structural 
members at the rate of not less than one sample for each 
type of structural member for each 2,500 square feet 
(232 m 2 ) of floor area or portion thereof in each story. 

1704. 12.6.3 Primer, paint and encapsulant bond tests. 
Bond tests to qualify a primer, paint or encapsulant shall 
be conducted when the sprayed fire-resistant material is 
applied to a primed, painted or encapsulated surface for 
which acceptable bond- strength performance between 
these coatings and the fire-resistant material has not been 
determined. A bonding agent approved by the SFRM 
manufacturer shall be applied to a primed, painted or 
encapsulated surface where the bond strengths are found 
to be less than required values. 

1704.13 Mastic and intumescent fire-resistant coatings. 
Special inspections for mastic and intumescent fire-resistant 
coatings applied to structural elements and decks shall be in 
accordance with AWCI 12-B. Special inspections shall be 
based on the fire-resistance design as designated in the 
approved construction documents. 

1704.14 Exterior insulation and finish systems (EIFS). Spe- 
cial inspections shall be required for all EIFS applications. 

Exceptions: 

1. Special inspections shall not be required for EIFS 
applications installed over a water-resistive barrier 
with a means of draining moisture to the exterior. 

2. Special inspections shall not be required for EIFS 
applications installed over masonry or concrete walls . 

1704.14.1 Water-resistive barrier coating. A water-resis- 
tive barrier coating complying with ASTM E 2570 requires 
special inspection of the water-resistive barrier coating 
when installed over a sheathing substrate. 

1704.15 Special cases. Special inspections shall be required 
for proposed work that is, in the opinion of the bUilding official, 
unusual in its nature, such as, but not limited to, the following 
examples: 

1. Construction materials and systems that are alternatives 
to materials and systems prescribed by this code. 

2. Unusual design applications of materials described in 
this code. 



3. Materials and systems required to be installed in accor- 
dance with additional manufacturer's instructions that 
prescribe requirements not contained in this code or in 
standards referenced by this code. 

[F] 1704.16 Special inspection for smoke control. Smoke 
control systems shall be tested by a special inspector. 

[F] 1704.16.1 Testing scope. The test scope shall be as fol- 
lows: 

1. During erection of ductwork and prior to concealment 
for the purposes of leakage testing and recording of 
device location. 

2. Prior to occupancy and after sufficient completion for 
the purposes of pressure difference testing, flow mea- 
surements and detection and control verification. 

[F] 1704.16.2 Qualifications. Special inspection agencies 
for smoke control shall have expertise in fire protection 
engineering, mechanical engineering and certification as air 
balancers. 



SECTION 1705 
STATEMENT OF SPECIAL INSPECTIONS 

1705.1 General. Where special inspection or testing is 
required by Section 1704, 1707 or 1708, the registered design 
professional in responsible charge shall prepare a statement of 
special inspections in accordance with Section 1705 for 
submittal by the applicant (see Section 1704.1.1). 

1705.2 Content of statement of special inspections. The 
statement of special inspections shall identify the following: 

1. The materials, systems, components and work required 
to have special inspection or testing by the building offi- 
cialor by the registered design professionalresponsible 
for each portion of the work. 

2. The type and extent of each special inspection. 

3. The type and extent of each test. 

4. Additional requirements for special inspection or testing 
for seismic or wind resistance as specified in Section 
1705.3, 1705.4, 1707 or 1708. 

5. For each type of special inspection, identification as to 
whether it will be continuous special inspection or peri- 
odic special inspection. 

1705.3 Seismic resistance. The statement of special inspec- 
tions shall include seismic requirements for cases covered in 
Sections 1705.3.1 through 1705.3.5. 

Exception: Seismic requirements are permitted to be 
excluded from the statement of special inspections for struc- 
tures designed and constructed in accordance with the fol- 
lowing: 

1. The structure consists of light-frame construction; the 
design spectral response acceleration at short periods, 
sds' as determined in Section 1613.5.4, does not 



2009 INTERNATIONAL BUILDING CODE® 



379 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



exceed 0.5g; and the height of the structure does not 
exceed 35 feet (10 668 mm) above grade plane; or 

2. The structure is constructed using a reinforced 
masonry structural system or reinforced concrete 
structural system; the design spectral response accel- 
eration at short periods, SDS' as determined in Section 
1613.5.4, does not exceed 0.5g, and the height of the 
structure does not exceed 25 feet (7620 mm) above 
grade plane; or 

3. Detached one- or two-family dwellings not exceeding 
two stories above grade plane, provided the structure 
does not have any of the following plan or vertical 
irregularities in accordance with Section 12.3.2 of 
ASCE 7: 

3.1. Torsional irregularity. 

3.2. Nonparallel systems. 

3.3. Stiffness irregularity-extreme soft story and 
soft story. 

3.4. Discontinuity in capacity-weak story. 

1705.3.1 Seismic-foree-resisting systems. The seismic- 
force-resisting systems in structures assigned to Seismic 
Design Category C, D, E or F, in accordance with Section 
1613. 

Exception: Requirements for the seismic- force-resist- 
ing system are permitted to be excluded from the state- 
ment of special inspections for steel systems in structures 
assigned to Seismic Design Category C that are not spe- 
cifically detailed for seismic resistance, with a response 
modification coefficient, R, of 3 or less, excluding canti- 
lever column systems. 

1705.3.2 Designated seismic systems. Designated seismic 
systems in structures assigned to Seismic Design Category 
D, E or F. 

1705.3.3 Seismic Design Category C. The following addi- 
tional systems and components in structures assigned to 
Seismic Design CategoryC: 

1. Heating, ventilating and air-conditioning (HVAC) 
ductwork containing hazardous materials and 
anchorage of such ductwork. 

2. Piping systems and mechanical units containing 
flammable, combustible or highly toxic materials. 

3. Anchorage of electrical equipment used for emer- 
gency or standby power systems. 

1705.3.4 Seismic Design Category D. The following addi- 
tional systems and components in structures assigned to 
Seismic Design Category D: 

1. Systems required for Seismic Design Category C. 

2. Exterior wall panels and their anchorage. 

3. Suspended ceiling systems and their anchorage. 



4. Access floors and their anchorage. 

5. Steel storage racks and their anchorage, where the 
importance factor is equal to 1.5 in accordance with 
Section 15.5.3 of ASCE 7. 

1705.3.5 Seismic Design Category E or F. The following 
additional systems and components in structures assigned 
to Seismic Design Category E or F: 

1. Systems required for Seismic Design Categories C 
andD. 

2. Electrical equipment. 

1705.3.6 Seismic requirements in the statement of spe- 
cial inspections. When Sections 1705.3 through 1705.3.5 
specify that seismic requirements be included, the statement 
of special inspections shall identify the following: 

1. The designated seismic systems and seismic- 
force-resisting systems that are subject to special 
inspections in accordance with Sections 1705.3 
through 1705.3.5. 

2. The additional special inspections and testing to be 
provided as required by Sections 1707 and 1708 and 
other applicable sections of this code, including the 
applicable standards referenced by this code. 

1705.4 Wind resistance. The statement of special inspections 
shall include wind requirements for structures constructed in 
the following areas: 

1. In wind Exposure Category B, where the 3-second-gust 
basic wind speed is 120 miles per hour (mph) (52.8 mis) or 
greater. 

2. In wind Exposure Category Cor D, where the 3-second- 
gust basic wind speed is 110 mph (49 m/s) or greater. 

1705.4.1 Wind requirements in the statement of special 
inspections. When Section 1705.4 specifies that wind 
requirements be included, the statement of special inspec- 
tions shall identify the main wind-force- resisting systems 
and wind-resisting components subject to special inspec- 
tions as specified in Section 1705.4.2. 

1705.4.2 Detailed requirements. The statement of special 
inspections shall include at least the following systems and 
components: 

1. Roof cladding and roof framing connections. 

2. Wall connections to roof and floor diaphragms and 
framing. 

3. Roof and floor diaphragm systems, including collec- 
tors, drag struts and boundary elements. 

4. Vertical wind-force-resisting systems, including 
braced frames, moment frames and shear walls. 

5. Wind-force-resisting system connections to the foun- 
dation. 



380 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



6. Fabrication and installation of systems or compo- 
nents required to meet the impact-resistance require- 
ments of Section 1609.1.2. 

Exception: Fabrication of manufactured systems or 
components that have a label indicating compliance with 
the wind-load and impact-resistance requirements of this 
code. 



SECTION 1706 

SPECIAL INSPECTIONS FOR 

WIND REQUIREMENTS 

1706.1 Special inspections for wind requirements. Special 
inspections itemized in Sections 1706.2through 1706.4, unless 
exempted by the exceptions to Section 1704. 1, are required for 
buildings and structures constructed in the following areas: 

1. In wind Exposure Category B, where the 3-second-gust 
basic wind speed is 120 miles per hour (52.8 m/sec) or 
greater. 

2. In wind Exposure Categories C or D, where the 3-sec- 
ond-gust basic wind speed is 110 mph (49 m/sec) or 
greater. 

1706.2 Structural wood. Continuous special inspection is 
required during field gluing operations of elements of the main 
windforce-resisting system. Periodic special inspection is 
required for nailing, bolting, anchoring and other fastening of 
components within the main windforce-resisting system, 
including wood shear walls, wood diaphragms, drag struts, 
braces and hold-downs. 

Exception: Special inspection is not required for wood 
shear walls, shear panels and diaphragms, including nailing, 
bolting, anchoring and other fastening to other components 
of the main windforce-resisting system, where the fastener 
spacing of the sheathing is more than 4 inches (102 mm) on 
center. 

1706.3 Cold-formed steel light-frame construction. Peri- 
odic special inspection is required during welding operations 
of elements of the main windforce-resisting system. Periodic 
special inspection is required for screw attachment, bolting, 
anchoring and other fastening of components within the main 
windforce-resisting system, including shear walls, braces, dia- 
phragms, collectors (drag struts) and hold-downs. 

Exception: Special inspection is not required for 
cold-formed steel light-frame shear walls, braces, dia- 
phragms, collectors (drag struts) and hold-downs where 
either of the following apply: 

1. The sheathing is gypsum board or fiberboard. 

2. The sheathing is wood structural panel or steel sheets 
on only one side of the shear wall, shear panel or dia- 
phragm assembly and the fastener spacing of the 
sheathing is more than 4 inches (102 mm) on center 
(o.c). 



1706.4 Wind-resisting components. Periodic special inspeC- 1 
tion is required for the following systems and components: 

1. Roof cladding. 

2. Wall cladding. 



SECTION 1707 

SPECIAL INSPECTIONS FOR 

SEISMIC RESISTANCE 

1707.1 Special inspections for seismic resistance. Special 
inspections itemized in Sections 1707.2 through 1707.9, unless 
exempted by the exceptions of Section 1704.1, 1705.3, or 
1705.3.1, are required for the following: 

1. The seismic-foree-resisting systems in structures 
assigned to Seismic Design Category C, D, E or F, as 
determined in Section 1613. 

2. Designated seismic systems in structures assigned to 
Seismic Design Category D, E or F. 

3. Architectural, mechanical and electrical components in 
structures assigned to Seismic Design CategoryC, D, E 
or F that are required in Sections 1707.6 and 1707.7. 

1707.2 Structural steel. Special inspection for structural steel 
shall be in accordance with the quality assurance plan require- 
ments of AISC 341. 

Exceptions: 

1. Special inspections of structural steel in structures 
assigned to Seismic Design Category C that are not 
specifically detailed for seismic resistance, with a 
response modification coefficient, R, of 3 or less, 
excluding cantilever column systems. 

2. For ordinary moment frames, ultrasonic and mag- 
netic particle testing of complete joint penetration 
groove welds are only required for demand critical 
welds. 

1707.3 Structural wood. Continuous special inspection is 
required during field gluing operations of elements of the seis- 
mic-foree-resisting system. Periodic special inspection is 
required for nailing, bolting, anchoring and other fastening of 
components within the seismic-foree-resisting system, includ- 
ing wood shear walls, wood diaphragms, drag struts, braces, 
shear panels and hold-downs. 

Exception: Special inspection is not required for wood 
shear walls, shear panels and diaphragms, including nailing, 
bolting, anchoring and other fastening to other components 
of the seismic-foree-resisting system, where the fastener 
spacing of the sheathing is more than 4 inches (102 mm) on 
center (o.c). 

1707.4 Cold-formed steel light-frame construction. Peri- 
odic special inspection is required during welding operations 
of elements of the seismic-foree-resisting system. Periodic 
special inspection is required for screw attachment, bolting, 
anchoring and other fastening of components within the seis- 



2009 INTERNATIONAL BUILDING CODE® 



381 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



mic-force-resisting system, including shear walls, braces, dia- 
phragms, collectors (drag struts) and hold-downs. 

Exception: Special inspection is not required for 
cold-formed steel light-frame shear walls, braces, dia- 
phragms, collectors (drag struts) and hold-downs where 
either of the following apply: 

1. The sheathing is gypsum board or fiberboard. 

2. The sheathing is wood structural panel or steel sheets 
on only one side of the shear wall, shear panel or dia- 
phragm assembly and the fastener spacing of the 
sheathing is more than 4 inches (102 mm) o.c. 

1707.5 Storage racks and access floors. Periodic special 
inspection is required during the anchorage of access floors 
and storage racks 8 feet (2438 mm) or greater in height in struc- 
tures assigned to Seismic Design Category D, E or F. 

1707.6 Architectural components. Periodic special inspec- 
tion during the erection and fastening of exterior cladding, inte- 
rior and exterior nonbearing walls and interior and exterior 
veneer in structures assigned to Seismic Design CategoryD, E 
or F. 

Exceptions: 

1. Special inspection is not required for exterior clad- 
ding, interior and exterior nonbearing walls and inte- 
rior and exterior veneer 30 feet (9144 mm) or less in 
height above grade or walking surface. 

2. Special inspection is not required for exterior clad- 
ding and interior and exterior veneer weighing 5 psf 
(24.5 N/m 2 ) or less. 

3. Special inspection is not required for interior 
nonbearing walls weighing 15 psf (73.5 N/m 2 ) or less. 

1707.7 Mechanical and electrical components. Special 
inspection for mechanical and electrical equipment shall be as 
follows: 

1. Periodic special inspection is required during the anchor- 
age of electrical equipment for emergency or standby 
power systems in structures assigned to Seismic Design 
CategoryC, D, E or F; 

2. Periodic special inspection is required during the instal- 
lation of anchorage of other electrical equipment in 
structures assigned to Seismic Design Category E or F; 

3. Periodic special inspection is required during installation 
of piping systems intended to carry flammable, combus- 
tible or highly toxic contents and their associated 
mechanical units in structures assigned to Seismic 
Design CategoryC, D, E or F; 

4. Periodic special inspection is required during the instal- 
lation of HVAC ductwork that will contain hazardous 
materials in structures assigned to Seismic Design Cate- 
goryC, D, E or F; and 

5. Periodic special inspection is required during the instal- 
lation of vibration isolation systems in structures 
assigned to Seismic Design CategoryC, D, E or F where 
the construction documents require a nominal clearance 
of i/ 4 inch (6.4 mm) or less between the equipment sup- 
port frame and restraint. 



1707.8 Designated seismic system verifications. The special 
inspector shall examine designated seismic systems requiring 
seismic qualification in accordance with Section 1708.4 and 
verify that the label, anchorage or mounting conforms to the 
certificate of compliance. 

1707.9 Seismic isolation system. Periodic special inspection 
is required during the fabrication and installation of isolator 
units and energy dissipation devices that are part of the seismic 
isolation system. 



SECTION 1708 

STRUCTURAL TESTING FOR 

SEISMIC RESISTANCE 



1. The seismic-force-resisting systems in structures 
assigned to Seismic Design Category C, D, E or F, as 
determined in Section 1613 shall meet the requirements 
of Sections 1708.2 and 1708.3, as applicable. 

2. Designated seismic systems in structures assigned to 
Seismic Design CategoryC, D, E or F subject to the spe- 
cial certification requirements of ASCE 7 Section 13.2.2 
are required to be tested in accordance with Section 
1708.4. 

3. Architectural, mechanical and electrical components in 
structures assigned to Seismic Design CategoryC, D, E 
or F with an / = 1.0 are required to be tested in accor- 
dance with Section 1708.4 where the general design 
requirements of ASCE 7 Section 13.2.1, Item 2 for man- 
ufacturer's certification are satisfied by testing. 

4. The seismic isolation system in seismically isolated 
structures shall meet the testing requirements of Section 
1708.5. 

1708.2 Concrete reinforcement. Where reinforcement com- 
plying with ASTM A 615 is used to resist earthquake-induced 
llexural and axial forces in special moment frames, special 
structural walls and coupling beams connecting special struc- 
tural walls, in structures assigned to Seismic Design Category 
B, C, D, E or F as determined in Section 1613, the reinforce- 
ment shall comply with Section 21.1.5.2 of ACI 318. Certified 
mill test reports shall be provided for each shipment of such 
reinforcement. Where reinforcement complying with ASTM 
A 615 is to be welded, chemical tests shall be performed to 
determine weldability in accordance with Section 3.5.2 of ACI 
318. 

1708.3 Structural steel. Testing for structural steel shall be in 
accordance with the quality assurance plan requirements of 
AISC 341. 

Exceptions: 

1. Testing for structural steel in structures assigned to 
Seismic Design Category C that are not specifically 
detailed for seismic resistance, with a response modi- 



382 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



fication coefficient, R, of 3 or less, excluding cantile- 
ver column systems. 

2. For ordinary moment frames, ultrasonic and mag- 
netic particle testing of complete joint penetration 
groove welds are only required for demand critical 
welds. 

1708.4 Seismic certification of nonstructural components. 
The registered design professional shall state the applicable 
seismic certification requirements for nonstructural compo- 
nents and designated seismic systems on the construction doc- 
uments. 

1. The manufacturer of each designated seismic system 
components subject to the provisions of ASCE 7 Section 
13.2.2 shall test or analyze the component and its mount- 
ing system or anchorage and submit a certificate of com- 
pliance for review and acceptance by the registered 
design prof essionahesponsible for the design of the des- 
ignated seismic system and for approval by the building 
official. Certification shall be based on an actual test on a 
shake table, by three-dimensional shock tests, by an ana- 
lytical method using dynamic characteristics and forces, 
by the use of experience data (Le., historical data demon- 
strating acceptable seismic performance) or by more rig- 
orous analysis providing for equivalent safety. 

2. Manufacturer's certification of compliance for the gen- 
eral design requirements of ASCE 7 Section 13.2.1 shall 
be based on analysis, testing or experience data. 

1708.5 Seismically isolated structures. For required system 
tests, see Section 17.8 of ASCE 7. 



SECTION 1709 
CONTRACTOR RESPONSIBILITY 

1709.1 Contractor responsibility. Each contractor responsi- 
ble for the construction of a main wind-or seismic-force-resist- 
ing system, designated seismic system or a wind- or 
seismic-resisting component listed in the statement of special 
inspections shall submit a written statement of responsibility to 
the bUilding official and the owner prior to the commencement 
of work on the system or component. The contractor's state- 
ment of responsibility shall contain acknowledgement of 
awareness of the special requirements contained in the state- 
ment of special inspection. 



SECTION 1710 
STRUCTURAL OBSERVATIONS 

1710.1 General. Where required by the provisions of Section 

1710.2 or 1710.3, the owner shall employ a registered design 
professional to perform structural observations as defined in 
Section 1702. 

Prior to the commencement of observations, the structural 
observer shall submit to the building official a written state- 
ment identifying the frequency and extent of structural obser- 
vations. 

At the conclusion of the work included in the permit, the 
structural observer shall submit to the bUilding officials written 



statement that the site visits have been made and identify any 
reported deficiencies which, to the best of the structural 
observer's knowledge, have not been resolved. 

1710.2 Structural observations for seismic resistance. 
Structural observations shall be provided for those structures 
assigned to Seismic Design Category D, E or F, as determined 
in Section 1613, where one or more of the following conditions 
exist: 

1. The structure is classified as Occupancy Category III or 
IV in accordance with Table 1604.5. 

2. The height of the structure is greater than 75 feet (22 860 
mm) above the base. 

3. The structure is assigned to Seismic Design CategoryE, 
is classified as Occupancy Category! or II in accordance 
with Table 1604.5, and is greater than two stories above 
grade plane. 

4. When so designated by the registered design profes- 
sional responsible for the structural design. 

5. When such observation is specifically required by the 
bUilding official. 

1710.3 Structural observations for wind requirements. 
Structural observations shall be provided for those structures 
sited where the basic wind speed exceeds 110 mph (49 m/sec) 
determined from Figure 1609, where one or more of the fol- 
lowing conditions exist: 

1. The structure is classified as Occupancy Categorylll or 
IV in accordance with Table 1604.5. 

2. The bUilding height of the structure is greater than 75 feet 
(22 860 mm). 

3. When so designated by the registered design profes- 
sional responsible for the structural design. 

4. When such observation is specifically required by the 
building official. 



SECTION 1711 
DESIGN STRENGTHS OF MATERIALS 

1711 .1 Conformance to standards. The design strengths and 
permissible stresses of any structural material that are identi- 
fied by a manufacturer's designation as to manufacture and 
grade by mill tests, or the strength and stress grade is otherwise 
confirmed to the satisfaction of the building official, shall con- 
form to the specifications and methods of design of accepted 
engineering practice or the approved rules in the absence of 
applicable standards. 

1711.2 New materials. For materials that are not specifically 
provided for in this code, the design strengths and permissible 
stresses shall be established by tests as provided for in Section 
1712. 



SECTION 1712 
ALTERNATIVE TEST PROCEDURE 

1712.1 General. In the absence of approved rules or other 
approvedstandards, the bUilding off /c/a/shall make, or cause to 



2009 INTERNATIONAL BUILDING CODE® 



383 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



be made, the necessary tests and investigations; or the building 
official shall accept duly authenticated reports from approved 
agencies in respect to the quality and manner of use of new 
materials or assemblies as provided for in Section 104.11. The 
cost of all tests and other investigations required under the pro- 
visions of this code shall be borne by the applicant. 



SECTION 1713 
TEST SAFE LOAD 

1713.1 Where required. Where proposed construction is not 
capable of being designed by approved engineering analysis, 
or where proposed construction design method does not com- 
ply with the applicable material design standard, the system of 
construction or the structural unit and the connections shall be 
subjected to the tests prescribed in Section 1715. The building 
officialshaU accept certified reports of such tests conducted by 
an approved testing agency, provided that such tests meet the 
requirements of this code and approve d procedures. 



SECTION 1714 
IN-SITU LOAD TESTS 

1714.1 General. Whenever there is a reasonable doubt as to the 
stability or load-bearing capacity of a completed building, 
structure or portion thereof for the expected loads, an engineer- 
ing assessment shall be required. The engineering assessment 
shall involve either a structural analysis or an in-situ load test, 
or both. The structural analysis shall be based on actual mate- 
rial properties and other as-built conditions that affect stability 
or load-bearing capacity, and shall be conducted in accordance 
with the applicable design standard. If the structural assess- 
ment determines that the load-bearing capacity is less than that 
required by the code, load tests shall be conducted in accor- 
dance with Section 1714.2. If the building, structure or portion 
thereof is found to have inadequate stability or load-bearing 
capacity for the expected loads, modifications to ensure struc- 
tural adequacy or the removal of the inadequate construction 
shall be required. 

1714.2 Test standards. Structural components and assemblies 
shall be tested in accordance with the appropriate material stan- 
dards listed in Chapter 35. In the absence of a standard that con- 
tains an applicable load test procedure, the test procedure shall 
be developed by a registereddesignprofessionaland approved. 
The test procedure shall simulate loads and conditions of appli- 
cation that the completed structure or portion thereof will be 
subjected to in normal use. 

1714.3 In-situ load tests. In-situ load tests shall be conducted 
in accordance with Section 1714.3.1 or 1714.3.2 and shall be 
supervised by a registered design professional. The test shall 
simulate the applicable loading conditions specified in Chapter 
16 as necessary to address the concerns regarding structural 
stability of the building, structure or portion thereof. 

1714.3.1 Load test procedure specified. Where a standard 
listed in Chapter 35 contains an applicable load test proce- 
dure and acceptance criteria, the test procedure and accep- 
tance criteria in the standard shall apply. In the absence of 
specific load factors or acceptance criteria, the load factors 
and acceptance criteria in Section 1714.3.2 shall apply. 



1714.3.2 Load test procedure not specified. In the absence 
of applicable load test procedures contained within a stan- 
dard referenced by this code or acceptance criteria for a spe- 
cific material or method of construction, such existing 
structure shall be subjected to a test procedure developed by 
a registered design professional that simulates applicable 
loading and deformation conditions. For components that 
are not a part of the seismic-load-resisting system, the test 
load shall be equal to two times the unfactored design loads . 
The test load shall be left in place for a period of 24 hours. 
The structure shall be considered to have successfully met 
the test requirements where the following criteria are satis- 
fied: 

1. Under the design load, the deflection shall not exceed 
the limitations specified in Section 1604.3. 

2. Within 24 hours after removal of the test load, the 
structure shall have recovered not less than 75 percent 
of the maximum deflection. 

3. During and immediately after the test, the structure 
shall not show evidence of failure. 



SECTION 1715 
PRECONSTRUCTION LOAD TESTS 

1715.1 General. In evaluating the physical properties of mate- 
rials and methods of construction that are not capable of being 
designed by approved engineering analysis or do not comply 
with applicable material design standards listed in Chapter 35, 
the structural adequacy shall be predetermined based on the 
load test criteria established in this section. 

1715.2 Load test procedures specified. Where specific load 
test procedures, load factors and acceptance criteria are 
included in the applicable design standards listed in Chapter 
35, such test procedures, load factors and acceptance criteria 
shall apply. In the absence of specific test procedures, load fac- 
tors or acceptance criteria, the corresponding provisions in 
Section 1715.3 shall apply. 

1715.3 Load test procedures not specified. Where load test 
procedures are not specified in the applicable design standards 
listed in Chapter 35, the load-bearing and deformation capacity 
of structural components and assemblies shall be determined 
on the basis of a test procedure developed by a registered 
design professional that simulates applicable loading and 
deformation conditions. For components and assemblies that 
are not a part of the seismic-force-resisting system, the test 
shall be as specified in Section 1715.3.1. Load tests shall simu- 
late the applicable loading conditions specified in Chapter 16. 

1715.3.1 Test procedure. The test assembly shall be sub- 
jected to an increasing superimposed load equal to not less 
than two times the superimposed design load. The test load 
shall be left in place for a period of 24 hours. The tested 
assembly shall be considered to have successfully met the 
test requirements if the assembly recovers not less than 75 
percent of the maximum deflection within 24 hours after the 
removal of the test load. The test assembly shall then be 
reloaded and subjected to an increasing superimposed load 
until either structural failure occurs or the superimposed 
load is equal to two and one-half times the load at which the 



384 



2009 INTERNATIONAL BUILDING CODE® 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



deflection limitations specified in Section 1715.3.2 were 
reached, or the load is equal to two and one-half times the 
superimposed design load. In the case of structural compo- 
nents and assemblies for which deflection limitations are 
not specified in Section 1715.3.2, the test specimen shall be 
subjected to an increasing superimposed load until struc- 
tural failure occurs or the load is equal to two and one-half 
times the desired superimposed design load. The allowable 
superimposed design load shall be taken as the lesser of: 

1. The load at the deflection limitation given in Section 
1715.3.2. 

2. The failure load divided by 2.5. 

3. The maximum load applied divided by 2.5. 

1715.3.2 Deflection. The deflection of structural members 
under the design load shall not exceed the limitations in Sec- 
tion 1604.3. 

1715.4 Wall and partition assemblies. Load-bearing wall 
and partition assemblies shall sustain the test load both with 
and without window framing. The test load shall include all 
design load components. Wall and partition assemblies shall be 
tested both with and without door and window framing. 

1715.5 Exterior window and door assemblies. The design 
pressure rating of exterior windows and doors in buildings 
shall be determined in accordance with Section 1715.5.1 or 
1715.5.2. 

Exception: Structural wind load design pressures for win- 
dow units smaller than the size tested in accordance with 
Section 1715.5.1 or 1715.5.2 shall be permitted to be higher 
than the design value of the tested unit provided such higher 
pressures are determined by accepted engineering analysis. 
All components of the small unit shall be the same as the 
tested unit. Where such calculated design pressures are 
used, they shall be validated by an additional test of the win- 
dow unit having the highest allowable design pressure. 

1715.5.1 Exterior windows and doors. Exterior windows 
and sliding doors shall be tested and labeled as conforming 
to AAMA/WDMA/CSA101/I.S.2/A440. The label shall 
state the name of the manufacturer, the approved labeling 
agency and the product designation as specified in AAMAI 
WDMA/CSA101/LS.2/A440 . Exterior side-hinged doors 
shall be tested and labeled as conforming to 
AAMA/WDMA/CSA101/LS.2/A440 or comply with Sec- 
tion 1715.5.2. Products tested and labeled as conforming to 
AAMA/WDMA/CSA 101/LS.2/A440 shall not be subject 
to the requirements of Sections 2403.2 and 2403.3. 

1715.5.2 Exterior windows and door assemblies not pro- 
vided for in Section 1715.5.1. Exterior window and door 
assemblies shall be tested in accordance with ASTM E 330. 
Structural performance of garage doors shall be determined 
in accordance with either ASTM E 330 or ANSI/DASMA 
108, and shall meet the acceptance criteria of 
ANSI/DASMA 108. Exterior window and door assemblies 
containing glass shall comply with Section 2403. The 
design pressure for testing shall be calculated in accordance 
with Chapter 16. Each assembly shall be tested for 10 sec- 
onds at a load equal to 1.5 times the design pressure. 



1715.6 Test specimens. Test specimens and construction shall 
be representative of the materials, workmanship and details 
normally used in practice. The properties of the materials used 
to construct the test assembly shall be determined on the basis 
of tests on samples taken from the load assembly or on repre- 
sentative samples of the materials used to construct the load test 
assembly. Required tests shall be conducted or witnessed by an 
approved agency. 



SECTION 1716 
MATERIAL AND TEST STANDARDS 

1716.1 Test standards for joist hangers and connectors. 

1716.1.1 Test standards for joist hangers. The vertical 
load-bearing capacity, torsional moment capacity and 
deflection characteristics of joist hangers shall be deter- 
mined in accordance with ASTM D 1761 using lumber hav- 
ing a specific gravity of 0.49 or greater, but not greater than 
0.55, as determined in accordance with AF&PA NDS for 
the joist and headers. 

Exception: The joist length shall not be required to 
exceed 24 inches (610 mm). 

1716.1.2 Vertical load capacity for j oist hangers. The ver- 
tical load capacity for the joist hanger shall be determined 
by testing a minimum of three joist hanger assemblies as 
specified in ASTM D 1761 . If the ultimate vertical load for 
anyone of the tests varies more than 20 percent from the 
average ultimate vertical load, at least three additional tests 
shall be conducted. The allowable vertical load of the joist 
hanger shall be the lowest value determined from the fol- 
lowing: 

1. The lowest ultimate vertical load for a single hanger 
from any test divided by three (where three tests are 
conducted and each ultimate vertical load does not 
vary more than 20 percent from the average ultimate 
vertical load) . 

2. The average ultimate vertical load for a single hanger 
from all tests divided by three (where six or more tests 
are conducted). 

3. The average from all tests of the vertical loads that 
produce a vertical movement of the joist with respect 
to the header of i/ 8 inch (3.2 mm). 

4. The sum of the allowable design loads for nails or 
other fasteners utilized to secure the joist hanger to the 
wood members and allowable bearing loads that con- 
tribute to the capacity of the hanger. 

5. The allowable design load for the wood members 
forming the connection. 

1716.1.3 Torsional moment capacity for joist hangers. 

The torsional moment capacity for the joist hanger shall be 
determined by testing at least three joist hanger assemblies 
as specified in ASTM D 1761. The allowable torsional 
moment of the joist hanger shall be the average torsional 
moment at which the lateral movement of the top or bottom 
of the joist with respect to the original position of the joist is 
i/ 8 inch (3.2 mm). 



2009 INTERNATIONAL BUILDING CODE® 



385 



STRUCTURAL TESTS AND SPECIAL INSPECTIONS 



1716.1.4 Design value modifications for joist hangers. 
Allowable design values for joist hangers that are deter- 
mined by Item 4 or 5 in Section 1716.1.2 shall be permitted 
to be modified by the appropriate duration of loading factors 
as specified in AF&PA NDS but shall not exceed the direct 
loads as determined by Item 1, 2 or 3 in Section 1716.1.2. 
Allowable design values determined by Item 1, 2 or 3 in 
Section 1716.1.2 shall not be modified by duration of load- 
ing factors. 

1716.2 Concrete and clay roof tiles. 

1716.2.1 Overturning resistance. Concrete and clay roof 
tiles shall be tested to determine their resistance to overturn- 
ing due to wind in accordance with SBCCI SSTD 11 and 
Chapter 15. 

1716.2.2 Wind tunnel testing. When roof tiles do not sat- 
isfy the limitations in Chapter 16 for rigid tile, a wind tunnel 
test shall be used to determine the wind characteristics of the 
concrete or clay tile roof covering in accordance with 
SBCCI SSTD 11 and Chapter 15. 



386 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 18 
SOILS AND FOUNDATIONS 

This chapter has been revised in its entirety; there will be no marginal markings. 



SECTION 1801 
GENERAL 

1801.1 Scope. The provisions of this chapter shall apply to 
building and foundation systems. 

1801.2 Design basis. Allowable bearing pressures, allowable 
stresses and design formulas provided in this chapter shall be 
used with the allowable stress design load combinations speci- 
fied in Section 1605 .3. The quality and design of materials used 
structurally in excavations and foundations shall comply with 
the requirements specified in Chapters 16, 19,21,22 and 23 of 
this code. Excavations and fills shall also comply with Chapter 
33. 



SECTION 1802 
DEFINITIONS 

1802.1 Definitions. The following words and terms shall, for 
the purposes of this chapter, have the meanings shown herein. 

DEEP FOUNDATION. A deep foundation is a foundation 
element that does not satisfy the definition of a shallow founda- 
tion. 

DRILLED SHAFT. A drilled shaft is a cast-in-place deep 
foundation element constructed by drilling a hole (with or 
without permanent casing) into soil or rock and filling it with 
fluid concrete. 

Socketed drilled shaft. A socketed drilled shaft is a drilled 
shaft with a permanent pipe or tube casing that extends 
down to bedrock and an uncased socket drilled into the bed- 
rock. 

HELICAL PILE. Manufactured steel deep foundation ele- 
ment consisting of a central shaft and one or more helical bear- 
ing plates. A helical pile is installed by rotating it into the 
ground. Each helical bearing plate is formed into a screw thread 
with a uniform defined pitch. 

MICROPILE. A micropile is a bored, grouted-in-place deep 
foundation element that develops its load-carrying capacity by 
means of a bond zone in soil, bedrock or a combination of soil 
and bedrock. 

SHALLOW FOUNDATION. A shallow foundation is an 
individual or strip footing, a mat foundation, a slab-on-grade 
foundation or a similar foundation element. 



SECTION 1803 
GEOTECHNICAL INVESTIGATIONS 

1803.1 General. Geotechnical investigations shall be con- 
ducted in accordance with Section 1803.2 and reported in 
accordance with Section 1803.6. Where required by the build- 



ing official or where geotechnical investigations involve in-situ 
testing, laboratory testing or engineering calculations, such 
investigations shall be conducted by a registered design profes- 
sional. 

1803.2 Investigations required. Geotechnical investigations 
shall be conducted in accordance with Sections 1803 .3 through 
1803.5. 

Exception: The building officialshall be permitted to waive 
the requirement for a geotechnical investigation where sat- 
isfactory data from adjacent areas is available that demon- 
strates an investigation is not necessary for any of the 
conditions in Sections 1803.5.1 through 1803.5.6 and Sec- 
tions 1803.5.10 and 1803.5.11. 

1803.3 Basis of investigation. Soil classification shall be 
based on observation and any necessary tests of the materials 
disclosed by borings, test pits or other subsurface exploration 
made in appropriate locations. Additional studies shall be 
made as necessary to evaluate slope stability, soil strength, 
position and adequacy of load-bearing soils, the effect of mois- 
ture variation on soil-bearing capacity, compressibility, lique- 
faction and expansiveness. 

1803.3.1 Scope of investigation. The scope of the 
geotechnical investigation including the number and types 
of borings or soundings, the equipment used to drill or sam- 
ple, the in-situ testing equipment and the laboratory testing 
program shall be determined by a registered design profes- 
sional. 

1803.4 Qualified representative. The investigation procedure 
and apparatus shall be in accordance with generally accepted 
engineering practice. The registered design professional shall 
have a fully qualified representative on site during all boring or 
sampling operations. 

1803.5 Investigated conditions. Geotechnical investigations 
shall be conducted as indicated in Sections 1803.5.1 through 
1803.5.12. 

1803.5.1 Classification. Soil materials shall be classified in 
accordance with ASTM D 2487. 

1803.5.2 Questionable soil. Where the classification, 
strength or compressibility of the soil is in doubt or where a 
load-bearing value superior to that specified in this code is 
claimed, the building official shall be permitted to require 
that a geotechnical investigation be conducted. 

1803.5.3 Expansive soil. In areas likely to have expansive 
soil, the building official shall require soil tests to determine 
where such soils do exist. 

Soils meeting all four of the following provisions shall be 
considered expansive, except that tests to show compliance 



2009 INTERNATIONAL BUILDING CODE® 



387 



SOILS AND FOUNDATIONS 



with Items 1, 2 and 3 shall not be required if the test pre- 
scribed in Item 4 is conducted: 

1. Plasticity index (PI) of 15 or greater, determined in 
accordance with ASTM D 4318. 

2. More than 10 percent of the soil particles pass a No. 
200 sieve (75 (am), determined in accordance with 
ASTM D 422. 

3. More than 10 percent of the soil particles are less than 
5 micrometers in size, determined in accordance with 
ASTM D 422. 

4. Expansion index greater than 20, determined in 
accordance with ASTM D 4829. 

1803.5.4 Ground-water table. A subsurface soil investiga- 
tion shall be performed to determine whether the existing 
ground-water table is above or within 5 feet (1524 mm) 
below the elevation of the lowest floor level where such 
floor is located below the finished ground level adjacent to 
the foundation. 

Exception: A subsurface soil investigation to determine 
the location of the ground-water table shall not be 
required where waterproofing is provided in accordance 
with Section 1805. 

1803.5.5 Deep foundations. Where deep foundations will 
be used, a geotechnical investigation shall be conducted and 
shall include all of the following, unless sufficient data upon 
which to base the design and installation is otherwise avail- 
able: 

1. Recommended deep foundation types and installed 
capacities. 

2. Recommended center-to-center spacing of deep 
foundation elements. 

3. Driving criteria. 

4. Installation procedures. 

5. Field inspection and reporting procedures (to include 
procedures for verification of the installed bearing 
capacity where required). 

6. Load test requirements. 

7. Suitability of deep foundation materials for the 
intended environment. 

8. Designation of bearing stratum or strata. 

9. Reductions for group action, where necessary. 

1803.5.6 Rock strata. Where subsurface explorations at the 
project site indicate variations or doubtful characteristics in 
the structure of the rock upon which foundations are to be 
constructed, a sufficient number of borings shall be made to 
a depth of not less than 10 feet (3048 mm) below the level of 
the foundations to provide assurance of the soundness of the 
foundation bed and its load-bearing capacity. 

1803.5.7 Excavation near foundations. Where excavation 
will remove lateral support from any foundation, an investi- 
gation shall be conducted to assess the potential conse- 
quences and address mitigation measures. 



1803.5.8 Compacted fill material. Where shallow founda- 
tions will bear on compacted fill material more than 12 
inches (305 mm) in depth, a geotechnical investigation shall 
be conducted and shall include all of the following: 

1. Specifications for the preparation of the site prior to 
placement of compacted fill material. 

2. Specifications for material to be used as compacted 
fill. 

3. Test methods to be used to determine the maximum 
dry density and optimum moisture content of the 
material to be used as compacted fill. 

4. Maximum allowable thickness of each lift of com- 
pacted fill material. 

5. Field test method for determining the in-place dry 
density of the compacted fill. 

6. Minimum acceptable in-place dry density expressed 
as a percentage of the maximum dry density deter- 
mined in accordance with Item 3. 

7. Number and frequency of field tests required to deter- 
mine compliance with Item 6. 

1803.5.9 Controlled low-strength material (CLSM). 
Where shallow foundations will bear on controlled 
low- strength material (CLSM), a geotechnical investigation 
shall be conducted and shall include all of the following: 

1. Specifications for the preparation of the site prior to 
placement of the CLSM. 

2. Specifications for the CLSM. 

3. Laboratory or field test method(s) to be used to deter- 
mine the compressive strength or bearing capacity of 
the CLSM. 

4. Test methods for determining the acceptance of the 
CLSM in the field. 

5. Number and frequency of field tests required to deter- 
mine compliance with Item 4. 

1803.5.10 Alternate setback and clearance. Where set- 
backs or clearances other than those required in Section 
1808.7 are desired, the bUilding officialshaU be permitted to 
require a geotechnical investigation by a registered design 
professionalto demonstrate that the intent of Section 1808.7 
would be satisfied. Such an investigation shall include con- 
sideration of material, height of slope, slope gradient, load 
intensity and erosion characteristics of slope material. 

1803.5.11 Seismic Design Categories C through F. For 
structures assigned to Seismic Design CategoryC, D, E or F 
in accordance with Section 1613, a geotechnical investiga- 
tion shall be conducted, and shall include an evaluation of 
all of the following potential geologic and seismic hazards : 

1. Slope instability. 

2. Liquefaction. 

3. Differential settlement. 

4. Surface displacement due to faulting or lateral 
spreading. 



388 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



1803.5.12 Seismic Design Categories D through F. For 
structures assigned to Seismic Design CategoryD, E or F in 
accordance with Section 1613, the geotechnical investiga- 
tion required by Section 1803.5.11, shall also include: 

1. The determination of lateral pressures on foundation 
walls and retaining walls due to earthquake motions. 

2. The potential for liquefaction and soil strength loss 
evaluated for site peak ground accelerations, magni- 
tudes and source characteristics consistent with the 
design earthquake ground motions. Peak ground 
acceleration shall be permitted to be determined 
based on a site-specific study taking into account soil 
amplification effects, as specified in Chapter 21 of 
ASCE 7, or, in the absence of such a study, peak 
ground accelerations shall be assumed equal to 
SDj2. 5, where SDS is determined in accordance with 
Section 1613.5.4. 

3. An assessment of potential consequences of liquefac- 
tion and soil strength loss, including estimation of dif- 
ferential settlement, lateral movement, lateral loads 
on foundations, reduction in foundation soil-bearing 
capacity, increases in lateral pressures on retaining 
walls and flotation of buried structures. 

4. Discussion of mitigation measures such as, but not 
limited to, ground stabilization, selection of appropri- 
ate foundation type and depths, selection of appropri- 
ate structural systems to accommodate anticipated 
displacements and forces, or any combination of 
these measures and how they shall be considered in 
the design of the structure. 

1803.6 Reporting. Where geotechnical investigations are 
required, a written report of the investigations shall be submit- 
ted to the building officialby the owner or authorized agent at 
the time of permit application. This geotechnical report shall 
include, but need not be limited to, the following information: 

1. A plot showing the location of the soil investigations. 

2. A complete record of the soil boring and penetration 
test logs and soil samples. 

3. A record of the soil profile. 

4. Elevation of the water table, if encountered. 

5. Recommendations for foundation type and design cri- 
teria' including but not limited to : bearing capacity of 
natural or compacted soil; provisions to mitigate the 
effects of expansive soils; mitigation of the effects of 
liquefaction, differential settlement and varying soil 
strength; and the effects of adjacent loads. 

6. Expected total and differential settlement. 

7. Deep foundation information in accordance with Sec- 
tion 1803.5.5. 

8. Special design and construction provisions for founda- 
tions of structures founded on expansive soils, as nec- 
essary. 

9. Compacted fill material properties and testing in accor- 
dance with Section 1803.5.8. 



10. Controlled low- strength material properties and testing 
in accordance with Section 1803.5.9. 



SECTION 1804 
EXCAVATION, GRADING AND FILL 

1804.1 Excavation near foundations. Excavation for any pur- 
pose shall not remove lateral support from any foundation 
without first underpinning or protecting the foundation against 
settlement or lateral translation. 

1804.2 Placement of backfill. The excavation outside the 
foundation shall be backfilled with soil that is free of organic 
material, construction debris, cobbles and boulders or with a 
controlled low- strength material (CLSM). The backfill shall be 
placed in lifts and compacted in a manner that does not damage 
the foundation or the waterproofing or dampproofing material. 

Exception: CLSM need not be compacted. 

1804.3 Site grading. The ground immediately adjacent to the 
foundation shall be sloped away from the building at a slope of 
not less than one unit vertical in 20 units horizontal (5-percent 
slope) for a minimum distance of 10 feet (3048 mm) measured 
perpendicular to the face of the wall. If physical obstructions or 
lot lines prohibit 10 feet (3048 mm) of horizontal distance, a 
5 -percent slope shall be provided to an approved alternative 
method of diverting water away from the foundation. Swales 
used for this purpose shall be sloped a minimum of 2 percent 
where located within 10 feet (3048 mm) of the building foun- 
dation. Impervious surfaces within 10 feet (3048 mm) of the 
building foundation shall be sloped a minimum of 2 percent 
away from the building. 

Exception: Where climatic or soil conditions warrant, the 
slope of the ground away from the building foundation shall 
be permitted to be reduced to not less than one unit vertical 
in 48 units horizontal (2-percent slope) . 

The procedure used to establish the final ground level adja- 
cent to the foundation shall account for additional settlement of 
the backfill. 

1804.4 Grading and fill in flood hazard areas. In flood haz- 
ard areas established in Section 1612.3, grading and/or fill 
shall not be approved: 

1. Unless such fill is placed, compacted and sloped to mini- 
mize shifting, slumping and erosion during the rise and 
fall of flood water and, as applicable, wave action. 

2. In rloodways, unless it has been demonstrated through 
hydrologic and hydraulic analyses performed by a regis- 
tered design professional in accordance with standard 
engineering practice that the proposed grading or fill, or 
both, will not result in any increase in flood levels during 
the occurrence of the design flood. 

3. In flood hazard areas subject to high- velocity wave 
action, unless such fill is conducted and/or placed to 
avoid diversion of water and waves toward any building 
or structure. 

4. Where design flood elevations are specified but 
floodways have not been designated, unless it has been 
demonstrated that the cumulative effect of the proposed 



2009 INTERNATIONAL BUILDING CODE® 



389 



SOILS AND FOUNDATIONS 



flood hazard area encroachment, when combined with 
all other existing and anticipated flood hazard area 
encroachment, will not increase the design flood eleva- 
tion more than 1 foot (305 mm) at any point. 

1804.5 Compacted fill material. Where shallow foundations 
will bear on compacted fill material, the compacted fill shall 
comply with the provisions of an approvedgeotechnical report, 
as set forth in Section 1803. 

Exception: Compacted fill material 12 inches (305 mm) in 
depth or less need not comply with an approved report, pro- 
vided the in-place dry density is not less than 90 percent of 
the maximum dry density at optimum moisture content 
determined in accordance with ASTM D 1557. The com- 
paction shall be verified by special inspection in accordance 
with Section 1704.7. 

1804.6 Controlled low-strength material (CLSM). Where 
shallow foundations will bear on controlled low- strength mate- 
rial (CLSM), the CLSM shall comply with the provisions of an 
approved geotechnical report, as set forth in Section 1803. 



SECTION 1805 
DAMPPROOFING AND WATERPROOFING 

1805.1 General. Walls or portions thereof that retain earth and 
enclose interior spaces and floors below grade shall be water- 
proofed and dampproofed in accordance with this section, with 
the exception of those spaces containing groups other than resi- 
dential and institutional where such omission is not detrimental 
to the building or occupancy. 

Ventilation for crawl spaces shall comply with Section 
1203.4. 

1805.1.1 Story above grade plane. Where a basement is 
considered a story above grade plane and the finished 
ground level adjacent to the basement wall is below the 
basement floor elevation for 25 percent or more of the per- 
imeter, the floor and walls shall be dampproofed in accor- 
dance with Section 1805.2 and a foundation drain shall be 
installed in accordance with Section 1805.4.2. The founda- 
tion drain shall be installed around the portion of the perim- 
eter where the basement floor is below ground level. The 
provisions of Sections 1803.5.4, 1805.3 and 1805.4.1 shall 
not apply in this case. 

1805.1.2 Under-floor space. The finished ground level of 
an under-floor space such as a crawl space shall not be 
located below the bottom of the footings. Where there is evi- 
dence that the ground-water table rises to within 6 inches 
(152 mm) of the ground level at the outside building perime- 
ter, or that the surface water does not readily drain from the 
building site, the ground level of the under-floor space shall 
be as high as the outside finished ground level, unless an 
approved drainage system is provided. The provisions of 
Sections 1803.5.4, 1805.2, 1805.3 and 1805.4 shall not 
apply in this case. 

1805.1.2.1 Flood hazard areas. For buildings and struc- 
tures in flood hazard areas as established in Section 
1612.3, the finished ground level of an under-floor space 



such as a crawl space shall be equal to or higher than the 
outside finished ground level on at least one side. 

Exception: Under-floor spaces of Group R-3 build- 
ings that meet the requirements ofFEMA/FIA-TB-11. 

1805.1.3 Ground- water control. Where the ground-water 
table is lowered and maintained at an elevation not less than 
6 inches (152 mm) below the bottom of the lowest floor, the 
floor and walls shall be dampproofed in accordance with 
Section 1805.2. The design of the system to lower the 
ground-water table shall be based on accepted principles of 
engineering that shall consider, but not necessarily be lim- 
ited to, permeability of the soil, rate at which water enters 
the drainage system, rated capacity of pumps, head against 
which pumps are to operate and the rated capacity of the dis- 
posal area of the system. 

1805.2 Dampproofing. Where hydrostatic pressure will not 
occur as determined by Section 1803.5.4, floors and walls for 
other than wood foundation systems shall be dampproofed in 
accordance with this section. Wood foundation systems shall 
be constructed in accordance with AF&PA PWF. 

1805.2.1 Floors. Dampproofing materials for floors shall 
be installed between the floor and the base course required 
by Section 1805.4.1, except where a separate floor is pro- 
vided above a concrete slab. 

Where installed beneath the slab, dampproofing shall 
consist of not less than 6-mil (0.006 inch; 0.152 mm) poly- 
ethylene withjoints lapped not less than 6 inches (152 mm), 
or other approved methods or materials. Where permitted to 
be installed on top of the slab, dampproofing shall consist of 
mopped-on bitumen, not less than 4-mil (0.004 inch; 0.102 
mm) polyethylene, or other approvedmzthods or materials. 
Joints in the membrane shall be lapped and sealed in accor- 
dance with the manufacturer's installation instructions. 

1805.2.2 Walls. Dampproofing materials for walls shall be 
installed on the exterior surface of the wall, and shall extend 
from the top of the footing to above ground level. 

Dampproofing shall consist of a bituminous material, 3 
pounds per square yard (16 N/m 2 ) of acrylic modified 
cement, i/ 8 inch (3.2 mm) coat of surface-bonding mortar 
complying with ASTM C 887, any of the materials permit- 
ted for waterproofing by Section 1805.3.2 or other 
approved methods or materials. 

1805.2.2.1 Surface preparation of walls. Prior to appli- 
cation of dampproofing materials on concrete walls, 
holes and recesses resulting from the removal of form 
ties shall be sealed with a bituminous material or other 
approvedmethods or materials. Unit masonry walls shall 
be parged on the exterior surface below ground level with 
not less than j/ s inch (9.5 mm) of portland cement mortar. 
The parging shall be coved at the footing. 

Exception: Parging of unit masonry walls is not 
required where a material is approvedfor direct appli- 
cation to the masonry. 

1805.3 Waterproofing. Where the ground- water investigation 
required by Section 1803.5.4 indicates that a hydrostatic pres- 
sure condition exists, and the design does not include a 



390 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



ground- water control system as described in Section 1805.1.3, 
walls and floors shall be waterproofed in accordance with this 
section. 

1805.3.1 Floors. Floors required to be waterproofed shall 
be of concrete and designed and constructed to withstand 
the hydrostatic pressures to which the floors will be sub- 
jected. 

Waterproofing shall be accomplished by placing a mem- 
brane of rubberized asphalt, butyl rubber, fully adhered/fully 
bonded HDPE or polyolefin composite membrane or not less 
than 6-mil [0.006 inch (0.152 mm)] polyvinyl chloride with 
joints lapped not less than 6 inches (152 mm) or other 
approved materials under the slab. Joints in the membrane 
shall be lapped and sealed in accordance with the manufac- 
turer's installation instructions. 

1805.3.2 Walls. Walls required to be waterproofed shall be 
of concrete or masonry and shall be designed and con- 
structed to withstand the hydrostatic pressures and other lat- 
eralloads to which the walls will be subjected. 

Waterproofing shall be applied from the bottom of the 
wall to not less than 12 inches (305 mm) above the maxi- 
mum elevation of the ground- water table. The remainder of 
the wall shall be dampproofed in accordance with Section 
1805.2.2. Waterproofing shall consist of two-ply 
hot-mopped felts, not less than 6-mil (0.006 inch; 0.152 
mm) polyvinyl chloride, 40-mil (0.040 inch; 1.02 mm) 
polymer-modified asphalt, 6-mil (0.006 inch; 0.152 mm) 
polyethylene or other approve d methods or materials capa- 
ble of bridging nonstructural cracks. Joints in the membrane 
shall be lapped and sealed in accordance with the manufac- 
turer's installation instructions. 

1805.3.2.1 Surface preparation of walls. Prior to the 
application of waterproofing materials on concrete or 
masonry walls, the walls shall be prepared in accordance 
with Section 1805.2.2.1. 

1805.3.3 Joints and penetrations. Joints in walls and 
floors, joints between the wall and floor and penetrations of 
the wall and floor shall be made water-tight utilizing 
approved methods and materials. 

1805.4 Subsoil drainage system. Where a hydrostatic pres- 
sure condition does not exist, dampproofing shall be provided 
and a base shall be installed under the floor and a drain installed 
around the foundation perimeter. A subsoil drainage system 
designed and constructed in accordance with Section 1805.1.3 
shall be deemed adequate for lowering the ground- water table. 

1805.4.1 Floor base course. Floors of basements, except as 
provided for in Section 1805.1.1, shall be placed over a floor 
base course not less than 4 inches (102 mm) in thickness that 
consists of gravel or crushed stone containing not more than 
10 percent of material that passes through a No . 4 (4 .75 mm) 
sieve. 

Exception: Where a site is located in well-drained gravel 
or sand/gravel mixture soils, a floor base course is not 
required. 



1805.4.2 Foundation drain. A drain shall be placed around 
the perimeter of a foundation that consists of gravel or 
crushed stone containing not more than 10-percent material 
that passes through a No. 4 (4.75 mm) sieve. The drain shall 
extend a minimum of 12 inches (305 mm) beyond the out- 
side edge of the footing. The thickness shall be such that the 
bottom of the drain is not higher than the bottom of the base 
under the floor, and that the top of the drain is not less than 6 
inches (152 mm) above the top of the footing . The top of the 
drain shall be covered with an approved filter membrane 
material. Where a drain tile or perforated pipe is used, the 
invert of the pipe or tile shall not be higher than the floor ele- 
vation. The top of joints or the top of perforations shall be 
protected with an approved filter membrane material. The 
pipe or tile shall be placed on not less than 2 inches (51 mm) 
of gravel or crushed stone complying with Section 
1805.4.1, and shall be covered with not less than 6 inches 
(152 mm) of the same material. 

1805.4.3 Drainage discharge. The floor base and founda- 
tion perimeter drain shall discharge by gravity or mechani- 
cal means into an approved drainage system that complies 
with the International Plumbing Code. 

Exception: Where a site is located in well-drained gravel 
or sand/gravel mixture soils, a dedicated drainage system 
is not required. 



SECTION 1806 
PRESUMPTIVE LOAD-BEARING VALUES OF SOILS 

1806.1 Load combinations. The presumptive load-bearing 
values provided in Table 1806.2 shall be used with the allow- 
able stress design load combinations specified in Section 
1605.3. The values of vertical foundation pressure and lateral 
bearing pressure given in Table 1806.2 shall be permitted to be 
increased by one-third where used with the alternative basic 
load combinations of Section 1605.3.2 that include wind or 
earthquake loads. 

1806.2 Presumptive load-bearing values. The load-bearing 
values used in design for supporting soils near the surface shall 
not exceed the values specified in Table 1806.2 unless data to 
substantiate the use of higher values are submitted and 
approved. Where the building officialhas reason to doubt the 
classification, strength or compressibility of the soil, the 
requirements of Section 1803.5.2 shall be satisfied. 

Presumptive load-bearing values shall apply to materials 
with similar physical characteristics and dispositions. Mud, 
organic silt, organic clays, peat or unprepared fill shall not be 
assumed to have a presumptive load-bearing capacity unless 
data to substantiate the use of such a value are submitted. 

Exception: A presumptive load-bearing capacity shall be 
permitted to be used where the building official deems the 
load-bearing capacity of mud, organic silt or unprepared fill 
is adequate for the support of lightweight or temporary 
structures. 

1806.3 Lateral load resistance. Where the presumptive val- 
ues of Table 1806.2 are used to determine resistance to lateral 



2009 INTERNATIONAL BUILDING CODE® 



391 



SOILS AND FOUNDATIONS 



loads, the calculations shall be in accordance with Sections 
1806.3.1 through 1806.3.4. 

1806.3.1 Combined resistance. The total resistance to lat- 
eralloads shall be permitted to be determined by combining 
the values derived from the lateral bearing pressure and the 
lateral sliding resistance specified in Table 1806.2. 

1806.3.2 Lateral sliding resistance limit. For clay, sandy 
clay, silty clay, clayey silt, silt and sandy silt, in no case shall 
the lateral sliding resistance exceed one-half the dead load. 

1806.3.3 Increase for depth. The lateral bearing pressures 
specified in Table 1806.2 shall be permitted to be increased 
by the tabular value for each additional foot (305 mm) of 
depth to a maximum of 15 times the tabular value. 

1806.3.4 Increase for poles. Isolated poles for uses such as 
flagpoles or signs and poles used to support buildings that 
are not adversely affected by a i/ 2 inch (12.7 mm) motion at 
the ground surface due to short-term lateral loads shall be 
permitted to be designed using lateral bearing pressures 
equal to two times the tabular values. 



SECTION 1807 

FOUNDATION WALLS, RETAINING WALLS AND 

EMBEDDED POSTS AND POLES 

1807.1 Foundation walls. Foundation walls shall be designed 
and constructed in accordance with Sections 1807.1.1 through 
1807.1.6. Foundation walls shall be supported by foundations 
designed in accordance with Section 1808. 



1807.1.1 Design lateral soil loads. Foundation walls shall 
be designed for the lateral soil loads set forth in Section 
1610. 

1807.1.2 Unbalanced backfill height. Unbalanced backfill 
height is the difference in height between the exterior finish 
ground level and the lower of the top of the concrete footing 
that supports the foundation wall or the interior finish 
ground level. Where an interior concrete slab on grade is 
provided and is in contact with the interior surface of the 
foundation wall, the unbalanced backfill height shall be per- 
mitted to be measured from the exterior finish ground level 
to the top of the interior concrete slab. 

1807.1.3 Rubble stone foundation walls. Foundation 
walls of rough or random rubble stone shall not be less than 
16 inches (406 mm) thick. Rubble stone shall not be used for 
foundation walls of structures assigned to Seismic Design 
CategoryC, D, E or F. 

1807.1.4 Permanent wood foundation systems. Perma- 
nent wood foundation systems shall be designed and 
installed in accordance with AF&PA PWF. Lumber and ply- 
wood shall be treated in accordance with AWPA Ul (Com- 
modity Specification A, Use Category 4B and Section 5.2) 
and shall be identified in accordance with Section 
2303.1.8.1. 

1807.1.5 Concrete and masonry foundation walls. Con- 
crete and masonry foundation walls shall be designed in 
accordance with Chapter 19 or 21, as applicable. 

Exception: Concrete and masonry foundation walls shall 
be permitted to be designed and constructed in accordance 
with Section 1807.1.6. 



TABLE 1806.2 
PRESUMPTIVE LOAD-BEARING VALUES 



CLASS OF MATERIALS 


VERTICAL FOUNDATION 
PRESSURE (pst) 


LATERAL BEARING 

PRESSURE 

(psf/f be\ow natural grade) 


LATERAL SLIDING RESISTANCE 


Coefficient of friction a 


Cohesion (psf)b 


1 . Crystalline bedrock 


12,000 


1,200 


0.70 


- 


2. Sedimentary and foli- 
ated rock 


4,000 


400 


0.35 




3. Sandy gravel and/or 
gravel (GW and GP) 


3,000 


200 


0.35 




4. Sand, silty sand, clayey 
sand, silty gravel and 
clayey gravel (SW, SP, 
SM, SC, GM and GC) 


2,000 


150 


0.25 


- 


5. Clay, sandy clay, silty 
clay, clayey silt, silt and 
sandy silt (CL, ML, 
MH and CH) 


1,500 


100 




130 



For SI: 1 pound per square foot = 0.0479 kPa, 1 pound per square foot per foot = 0. 157 kPa/m. 

a. Coefficient to be multiplied by the dead load. 

b. Cohesion value to be multiplied by the contact area, as limited by Section 1806.3.2. 



392 



2009 INTERNATIONAL BUILDING CODE® 



1807.1.6 Prescriptive design of concrete and masonry 
foundation walls. Concrete and masonry foundation walls 
that are laterally supported at the top and bottom shall be 
permitted to be designed and constructed in accordance 
with this section. 

1807.1.6.1 Foundation wall thickness. The thickness 
of prescriptively designed foundation walls shall not be 
less than the thickness of the wall supported, except that 
foundation walls of at least 8-inch (203 mm) nominal 
width shall be permitted to support brick-veneered frame 
walls and 10-inch- wide (254 mm) cavity walls provided 
the requirements of Section 1807.1.6.2 or 1807.1.6.3 are 
met. 



SOILS AND FOUNDATIONS 



1807.1.6.2 Concrete foundation walls. Concrete foun- 
dation walls shall comply with the following: 

1. The thickness shall comply with the requirements 
ofTable 1807.1.6.2. 

2. The size and spacing of vertical reinforcement 
shown in Table 1807.1.6.2 is based on the use of 
reinforcement with a minimum yield strength of 
60,000 pounds per square inch (psi) (414 MPa). 
Vertical reinforcement with a minimum yield 
strength of 40,000 psi (276 MPa) or 50,000 psi 
(345 MPa) shall be permitted, provided the same 
size bar is used and the spacing shown in the table 
is reduced by multiplying the spacing by 0.67 or 
0.83, respectively. 



TABLE 1807.1.6.2 
CONCRETE FOUNDATION WALLSb,c 



MAXIMUM 
WALL 
HEIGHT 

(feet) 


MAXIMUM 
UNBALANCED 

BACKFILL 
HEIGHT 6 (feet) 


MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) 


Design lateral soil load a (psf per foot of depth) 


30 d 


45 d 


60 


Minimum wall thinknp.QQ finr.hp.q'i 


7.5 


9.5 


11.5 


7.5 


9.5 


11.5 


7.5 


9.5 


11.5 


5 


4 
5 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


PC 
PC 


6 


4 
5 
6 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


PC 
PC 
PC 


7 


4 
5 
6 

7 


PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 


PC 
PC 
PC 

#5 at 46 


PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 


PC 
PC 

#5 at 48 
#6 at 48 


PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 


8 


4 
5 
6 

7 
8 


PC 
PC 
PC 
PC 

#5 at 47 


PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 

#5 at 41 
#6 at 43 


PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 
PC 


PC 
PC 

#5 at 43 
#6 at 43 
#6 at 32 


PC 
PC 
PC 
PC 

#6 at 44 


PC 
PC 
PC 
PC 
PC 


9 


4 
5 
6 
7 
8 


PC 
PC 
PC 
PC 

#5 at 41 
#6 at 46 


PC 
PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 

#5 at 37 
#6 at 38 
#7 at 41 


PC 
PC 
PC 
PC 

#5 at 37 
#6 at 41 


PC 
PC 
PC 
PC 
PC 
PC 


PC 
PC 

#5 at 39 
#6 at 38 
#7 at 39 
#7 at 31 


PC 
PC 
PC 

#5 at 37 
#6 at 39 
#7 at 41 


PC 
PC 
PC 
PC 

#4 at 48 
#6 at 39 


10 


4 
5 
6 
7 
8 
3 d 
10 d 


PC 
PC 
PC 
PC 

#5 at 38 
#6 at 41 
#7 at 45 


PC 

PC 

PC 

PC 

PC 
#4 at 48 
#6 at 45 


PC 
PC 
PC 
PC 
PC 
PC 
PC 


PC 
PC 
PC 

#6 at 48 
#7 at 47 
#7 at 37 
#7 at 31 


PC 
PC 
PC 
PC 

#6 at 47 
#7 at 48 
#7 at 40 


PC 

PC 

PC 

PC 

PC 
#4 at 48 
#6 at 38 


PC 
PC 

#5 at 37 
#6 at 35 
#7 at 35 
#6 at 22 
#6 at 22 


PC 
PC 
PC 

#6 at 48 
#7 at 47 
#7 at 37 
#7 at 30 


PC 
PC 
PC 
PC 

#6 at 45 
#7 at 47 
#7 at 38 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0. 157 kPa/m. 

a. For design lateral soil loads, see Section 1610. 

b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.2. 

c. "PC" means plain concrete. 

d. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610.1 are used, the requirements for 30 and 45 psf per foot of depth are 
not applicable (see Section 1610). 

e. For height of unbalanced backfill, see Section 1807.1.2. 



2009 INTERNATIONAL BUILDING CODE® 



393 



SOILS AND FOUNDATIONS 



3. Vertical reinforcement, when required, shall be 
placed nearest the inside face of the wall a dis- 
tance, d, from the outside face (soil face) of the 
wall. The distance, d, is equal to the wall thickness, 
t, minus 1.25 inches (32 mm) plus one-half the bar 
diameter, db' [d= t- (1.25 + df/2) ]. The reinforce- 
ment shall be placed within a tolerance of ± 3/8 inch 
(9.5 mm) where dis less than or equal to 8 inches 
(203 mm) or ± i/ 2 inch (12.7 mm) where dis greater 
than 8 inches (203 mm). 

4. In lieu of the reinforcement shown in Table 
1807.1.6.2, smaller reinforcing bar sizes with 
closer spacings that provide an equivalent 
cross-sectional area of reinforcement per unit 
length shall be permitted. 

5. Concrete cover for reinforcement measured from 
the inside face of the wall shall not be less than 3/ 4 
inch (19.1 mm). Concrete cover for reinforcement 
measured from the outside face of the wall shall 
not be less than 1V 2 inches (38 mm) for No. 5 bars 
and smaller, and not less than 2 inches (51 mm) for 
larger bars. 

6. Concrete shall have a specified compressive 
strength, fc of not less than 2,500 psi (17.2 MPa). 

7. The unfactored axial load per linear foot of wall 
shall not exceed 1.2 t f\ where f is the specified 
wall thickness in inches. 



1807.1.6.2.1 Seismic requirements. Based on the 
seismic design category assigned to the structure in 
accordance with Section 1613, concrete foundation 
walls designed using Table 1807.1.6.2 shall be sub- 
ject to the following limitations: 

1. Seismic Design Categories A and B. No addi- 
tional seismic requirements, except provide 
reinforcement around openings in accordance 
with Section 1909.6.3. 

2. Seismic DeSign Categories C, D, E and F. 
Tables shall not be used except as allowed for 
plain concrete members in Section 1908.1.8. 

1807.1.6.3 Masonry foundation walls. Masonry foun- 
dation walls shall comply with the following: 

1. The thickness shall comply with the require- 
ments of Table 1807.1.6.3(1) for plain masonry 
walls or Table 1807.1.6.3(2), 1807.1.6.3(3) or 
1807.1.6.3(4) for masonry walls with reinforce- 
ment. 

2. Vertical reinforcement shall have a minimum 
yield strength of 60,000 psi (414 MPa). 

3. The specified location of the reinforcement shall 
equal or exceed the effective depth distance, d, 
noted in Tables 1807.1.6.3(2), 1807.1.6.3(3) and 
1807.1.6.3(4) and shall be measured from the 
face of the exterior (soil) side of the wall to the 



TABLE 1807.1.6.3(1) 
PLAIN MASONRY FOUNDATION WALLSa,b,c 



MAXIMUM WALL HEIGHT 

(feet) 


MAXIMUM UNBALANCED 
BACKFILL HEIGHTe(feet) 


MINIMUM NOMINAL WALL THICKNESS (inches) 


Design lateral soil load 3 (psf per foot of depth) 


3& 


4S l 


60 


7 


4 (or less) 
5 
6 

7 


8 
8 
10 
12 


8 

10 

12 

10 (solid ) 


8 

10 
10 (solid ) 
10 (solid ) 


8 


4 (or less) 
5 
6 

7 
8 


8 
8 
10 
12 
10 (solid ) 


8 

10 

12 
12 (solid ) 
12 (solid ) 


8 

12 

12 (solid ) 

Note d 

Note d 


9 


4 (or less) 
5 
6 
7 
8 

gf 


8 

8 

12 

12 (solid ) 

12 (solid ) 

Note d 


8 
10 
12 

12 (solid ) 
Note d 
Note d 


8 
12 

12 (solid ) 
Note d 
Note d 
Note d 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot =0.157 kPa/m. 

a. For design lateral soil loads, see Section 1610. 

b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3. 

c. Solid grouted hollow units or solid masonry units. 

d. A design in compliance with Chapter 21 or reinforcement in accordance with Table 1807.1.6.3(2) is required. 

e. For height of unbalanced backfill, see Section 1807.1.2. 

f. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610. 1 are used, the requirements for 30 and 45 psf per foot of depth are 
not applicable (see Section 1610). 



394 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



center of the vertical reinforcement. The rein- 
forcement shall be placed within the tolerances 
specified in TMS 602/ACI 530.1/ASCE 6, Arti- 
cle 3.3.B.8 of the specified location. 

4. Grout shall comply with Section 2103.12. 

5. Concrete masonry units shall comply with 
ASTM C 90. 

6. Clay masonry units shall comply with ASTM C 
652 for hollow brick, except compliance with 
ASTM C 62 or ASTM C 216 shall be permitted 
where solid masonry units are installed in accor- 
dance with Table 1807.1.6.3(1) for plain 
masonry. 



7. Masonry units shall be laid in running bond and 
installed with Type M or S mortar in accordance 
with Section 2103.8. 

8. The unfactored axial load per linear foot of wall 
shall not exceed 1.2 t\'\\\ where tis the specified 
wall thickness in inches and Till is the specified 
compressive strength of masonry in pounds per 
square inch. 

9. At least 4 inches (102 mm) of solid masonry shall 
be provided at girder supports at the top of hol- 
low masonry unit foundation walls. 

10. Corbeling of masonry shall be in accordance 
with Section 2104.2. Where an 8-inch (203 mm) 
wall is corbeled, the top corbel shall not extend 



TABLE 1807.1.6.3(2) 
8-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 5 INCHES a ,b,c 



MAXIMUM WALL HEIGHT 


MAXIMUM UNBALANCED 
BACKFILL HEIGHT d 


MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) 


Design lateral soil load a (psf per foot of depth) 








(feet-inches) 


(feet-inches) 


30 e 


4S e 


60 




4-0 (or less) 


#4 at 48 


#4 at 48 


#4 at 48 


7-4 


5-0 


#4 at 48 


#4 at 48 


#4 at 48 


6-0 


#4 at 48 


#5 at 48 


#5 at 48 




7-4 


#5 at 48 


#6 at 48 


#7 at 48 


8-0 


4-0 (or less) 


#4 at 48 


#4 at 48 


#4 at 48 




5-0 


#4 at 48 


#4 at 48 


#4 at 48 




6-0 


#4 at 48 


#5 at 48 


#5 at 48 




7-0 


#5 at 48 


#6 at 48 


#7 at 48 




8-0 


#5 at 48 


#6 at 48 


#7 at 48 




4-0 (or less) 


#4 at 48 


#4 at 48 


#4 at 48 




5-0 


#4 at 48 


#4 at 48 


#5 at 48 


8-8 


6-0 


#4 at 48 


#5 at 48 


#6 at 48 




7-0 


#5 at 48 


#6 at 48 


#7 at 48 




8-8 e 


#6 at 48 


#7 at 48 


#8 at 48 




4-0 (or less) 


#4 at 48 


#4 at 48 


#4 at 48 




5-0 


#4 at 48 


#4 at 48 


#5 at 48 


9-4 


6-0 

7-0 


#4 at 48 
#5 at 48 


#5 at 48 
#6 at 48 


#6 at 48 
#7 at 48 




8-0 


#6 at 48 


#7 at 48 


#8 at 48 




9-4 e 


#7 at 48 


#8 at 48 


#9 at 48 




4-0 (or less) 


#4 at 48 


#4 at 48 


#4 at 48 




5-0 


#4 at 48 


#4 at 48 


#5 at 48 




6-0 


#4 at 48 


#5 at 48 


#6 at 48 


10-0 


7-0 


#5 at 48 


#6 at 48 


#7 at 48 




8-0 


#6 at 48 


#7 at 48 


#8 at 48 




9-0 e 


#7 at 48 


#8 at 48 


#9 at 48 




lo-oe 


#7 at 48 


#9 at 48 


#9 at 48 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0. 157 kPa/m. 

a. For design lateral soil loads, see Section 1610. 

b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3. 

c. For alternative reinforcement, see Section 1807.1.6.3.1. 

d. For height of unbalanced backfill, see Section 1807.1.2. 

e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610.1 are used, the requirements for 30 and 45 psf per foot of depth are 
not applicable. See Section 1610. 



2009 INTERNATIONAL BUILDING CODE® 



395 



SOILS AND FOUNDATIONS 



higher than the bottom of the floor framing and 
shall be a full course of headers at least 6 inches 
(152 mm) in length or the top course bed joint 
shall be tied to the vertical wall projection. The 
tie shall be W2.8 (4.8 mm) and spaced at a maxi- 
mum horizontal distance of 36 inches (914 mm) . 
The hollow space behind the corbelled masonry 
shall be filled with mortar or grout. 

1807.1.6.3.1 Alternative foundation wall rein- 
forcement. In lieu of the reinforcement provisions for 
masonry foundation walls in Table 1807.1.6.3(2), 
1807.1.6.3(3) or 1807.1.6.3(4), alternative reinforc- 
ing bar sizes and spacings having an equivalent 
cross-sectional area of reinforcement per linear foot 



(mm) of wall shall be permitted to be used, provided 
the spacing of reinforcement does not exceed 72 
inches (1829 mm) and reinforcing bar sizes do not 
exceed No. 11. 

1807.1.6.3.2 Seismic requirements. Based on the 
seismic design category assigned to the structure in 
accordance with Section 1613, masonry foundation 
walls designed using Tables 1807.1.6.3(1) through 
1807.1.6.3(4) shall be subject to the following limita- 
tions: 

1. Seismic Design Categories A and B. No addi- 
tional seismic requirements. 

2. Seismic Design Category C. A design using 
Tables 1807.1.6.3(1) through 1807.1.6.3(4) is 



TABLE 1807.1.6.3(3) 
10-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 6.75 INCHES a,b,c 



MAXIMUM WALL HEIGHT 


MAXIMUM UNBALANCED 
BACKFILL HEIGHT d 


MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) 


Design lateral soil load a (psf per foot of depth) 








(feet-inches) 


(feet-inches) 


30 e 


4S e 


60 




4-0 (or less) 


#4 at 56 


#4 at 56 


#4 at 56 


7-4 


5-0 
6-0 


#4 at 56 
#4 at 56 


#4 at 56 
#4 at 56 


#4 at 56 
#5 at 56 




7-4 


#4 at 56 


#5 at 56 


#6 at 56 




4-0 (or less) 


#4 at 56 


#4 at 56 


#4 at 56 




5-0 


#4 at 56 


#4 at 5 


#4 at 56 


8-0 


6-0 


#4 at 56 


#4 at 56 


#5 at 56 




7-0 


#4 at 56 


#5 at 56 


#6 at 56 




8-0 


#5 at 56 


#6 at 56 


#7 at 56 




4-0 (or less) 


#4 at 56 


#4 at 56 


#4 at 56 




5-0 


#4 at 56 


#4 at 56 


#4 at 56 


8-8 


6-0 


#4 at 56 


#4 at 56 


#5 at 56 




7-0 


#4 at 56 


#5 at 56 


#6 at 56 




8-8 e 


#5 at 56 


#7 at 56 


#8 at 56 




4-0 (or less) 


#4 at 56 


#4 at 56 


#4 at 56 




5-0 


#4 at 56 


#4 at 56 


#4 at 56 


9-4 


6-0 


#4 at 56 


#5 at 56 


#5 at 56 


7-0 


#4 at 56 


#5 at 56 


#6 at 56 




8-0 


#5 at 56 


#6 at 56 


#7 at 56 




9-4 e 


#6 at 56 


#7 at 56 


#7 at 56 




4-0 (or less) 


#4 at 56 


#4 at 56 


#4 at 56 




5-0 


#4 at 56 


#4 at 56 


#4 at 56 




6-0 


#4 at 56 


#5 at 56 


#5 at 56 


10-0 


7-0 


#5 at 56 


#6 at 56 


#7 at 56 




8-0 


#5 at 56 


#7 at 56 


#8 at 56 




9-0 e 


#6 at 56 


#7 at 56 


#9 at 56 




lo-oe 


#7 at 56 


#8 at 56 


#9 at 56 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8, 1 pound per square foot per foot = 1.157 kPa/m. 

a. For design lateral soil loads, see Section 1610. 

b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3. 

c. For alternative reinforcement, see Section 1807.1.6.3.1. 

d. For height of unbalanced backfill, See Section 1807.1.2. 

e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610. 1 are used, the requirements for 30 and 45 psf per foot of depth are 
not applicable. See Section 1610. 



396 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



subject to the seismic requirements of Section 

1.17.4.3 ofTMS 402/ACI 530/ASCE 5. 

3. Seismic Design Category D. A design using 
Tables 1807.1.6.3(2) through 1807.1.6.3(4) is 
subject to the seismic requirements of Section 

1.17.4.4 ofTMS 402/ACI 530/ASCE 5. 

4. Seismic Design Categories E and F. A design 
using Tables 1807.1.6.3(2) through 
1807.1.6.3(4) is subject to the seismic require- 
ments of Section 1.17.4.5 of TMS 402/ACI 
530/ASCE 5. 

1807.2 Retaining walls. Retaining walls shall be designed in 
accordance with Sections 1807.2.1 through 1807.2.3. 

1807.2.1 General. Retaining walls shall be designed to 
ensure stability against overturning, sliding, excessive foun- 



dation pressure and water uplift. Where a keyway is 
extended below the wall base with the intent to engage pas- 
sive pressure and enhance sliding stability, lateral soil pres- 
sures on both sides of the keyway shall be considered in the 
sliding analysis. 

1807.2.2 Design lateral soil loads. Retaining walls shall be 
designed for the lateral soil loads set forth in Section 1610. 

1807.2.3 Safety factor. Retaining walls shall be designed to 
resist the lateral action of soil to produce sliding and over- 
turning with a minimum safety factor of 1.5 in each case. 
The load combinations of Section 1605 shall not apply to 
this requirement. Instead, design shall be based on 0.7 times 
nominal earthquake loads, 1.0 times other nominalloads, 
and investigation with one or more of the variable loads set 
to zero. The safety factor against lateral sliding shall be 
taken as the available soil resistance at the base of the retain- 



TABLE 1807.1.6.3(4) 
12-INCH MASONRY FOUNDATION WALLS WITH REINFORCEMENT WHERE d > 8.75 INCHES a ,b,< 



MAXIMUM WALL HEIGHT 


MAXIMUM UNBALANCED 
BACKFILL HEIGHT d 


MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches) 


Design lateral snil lnad a Cnsf ner font nf rienth^ 








(feet-inches) 


(feet-inches) 


30 e 


45 e 


60 




4 (or less) 


#4 at 72 


#4 at 72 


#4 at 72 


7-4 


5-0 
6-0 


#4 at 72 
#4 at 72 


#4 at 72 
#4 at 72 


#4 at 72 
#5 at 72 




7-4 


#4 at 72 


#5 at 72 


#6 at 72 




4 (or less) 


#4 at 72 


#4 at 72 


#4 at 72 




5-0 


#4 at 72 


#4 at 72 


#4 at 72 


8-0 


6-0 


#4 at 72 


#4 at 72 


#5 at 72 




7-0 


#4 at 72 


#5 at 72 


#6 at 72 




8-0 


#5 at 72 


#6 at 72 


#8 at 72 




4 (or less) 


#4 at 72 


#4 at 72 


#4 at 72 




5-0 


#4 at 72 


#4 at 72 


#4 at 72 


8-8 


6-0 


#4 at 72 


#4 at 72 


#5 at 72 




7-0 


#4 at 72 


#5 at 72 


#6 at 72 




8-8 e 


#5 at 72 


#7 at 72 


#8 at 72 




4 (or less) 


#4 at 72 


#4 at 72 


#4 at 72 




5-0 


#4 at 72 


#4 at 72 


#4 at 72 


9-4 


6-0 
7-0 


#4 at 72 
#4 at 72 


#5 at 72 
#5 at 72 


#5 at 72 
#6 at 72 




8-0 


#5 at 72 


#6 at 72 


#7 at 72 




9-4 e 


#6 at 72 


#7 at 72 


#8 at 72 




4 (or less) 


#4 at 72 


#4 at 72 


#4 at 72 




5-0 


#4 at 72 


#4 at 72 


#4 at 72 




6-0 


#4 at 72 


#5 at 72 


#5 at 72 


10-0 


7-0 


#4 at 72 


#6 at 72 


#6 at 72 




8-0 


#5 at 72 


#6 at 72 


#7 at 72 




9-0 e 


#6 at 72 


#7 at 72 


#8 at 72 




lo-oe 


#7 at 72 


#8 at 72 


#9 at 72 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot =0.157 kPa/m. 

a. For design lateral soil loads, see Section 1610. 

b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3. 

c. For alternative reinforcement, see Section 1807.1.6.3.1. 

d. For height of unbalanced backfill, see Section 1807.1.2. 

e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610. 1 are used, the requirements for 30 and 45 psf per foot of depth are 
not applicable. See Section 1610. 



2009 INTERNATIONAL BUILDING CODE® 



397 



SOILS AND FOUNDATIONS 



ing wall foundation divided by the net lateral force applied 
to the retaining wall. 

Exception: Where earthquake loads are included, the 
minimum safety factor for retaining wall sliding and 
overturning shall be 1.1. 

1807.3 Embedded posts and poles. Designs to resist both 
axial and lateral loads employing posts or poles as columns 
embedded in earth or in concrete footings in earth shall be in 
accordance with Sections 1807.3.1 through 1807.3.3. 

1807.3.1 Limitations. The design procedures outlined in 
this section are subject to the following limitations: 

1. The frictional resistance for structural walls and slabs 
on silts and clays shall be limited to one-half of the 
normal force imposed on the soil by the weight of the 
footing or slab. 

2. Posts embedded in earth shall not be used to provide 
lateral support for structural or nonstructural materi- 
als such as plaster, masonry or concrete unless brac- 
ing is provided that develops the limited deflection 
required. 

Wood poles shall be treated in accordance with AWPA 
Ul for sawn timber posts (Commodity Specification A, Use 
Category 4B) and for round timber posts (Commodity 
Specification B, Use Category 4B). 

1807.3.2 Design criteria. The depth to resist lateral loads 
shall be determined using the design criteria established in 
Sections 1807.3.2.1 through 1807.3.2.3, or by other meth- 
ods approvedby the bUilding official. 

1807.3.2.1 Nonconstrained. The following formula 
shall be used in determining the depth of embedment 
required to resist lateral loads where no lateral constraint 
is provided at the ground surface, such as by a rigid floor 
or rigid ground surface pavement, and where no lateral 
constraint is provided above the ground surface, such as 
by a structural diaphragm. 



resist lateral loads where lateral constraint is provided at 
the ground surface, such as by a rigid floor or pavement. 



d= 0.5A{1 + [1 + (4.36h/A)]U2l 



(Equation 18-1) 



where: 
A 

b 



2.34P/S, b. 

Diameter of round post or footing or diagonal 
dimension of square post or footing, feet (m). 

d Depth of embedment in earth in feet (m) but not 

over 12 feet (3658 mm) for purpose of comput- 
ing lateral pressure. 

h Distance in feet (m) from ground surface to point 

of application of "P. " 

P Applied lateral force in pounds (kN). 

S1 Allowable lateral soil-bearing pressure as set 

forth in Section 1806.2 based on a depth of 
one-third the depth of embedment in pounds per 
square foot (psf) (kPa). 

1807.3.2.2 Constrained. The following formula shall be 
used to determine the depth of embedment required to 



4.25/% 



or alternatively 



4= 



4.25M„ 



(Equation 18-2) 



(Equation 18-3) 



where: 



M s = 



Moment in the post at grade, in foot-pounds 
(kN-m). 

S3 = Allowable lateral soil-bearing pressure as set 
forth in Section 1806.2 based on a depth equal to 
the depth of embedment in pounds per square 
foot (kPa). 

1807.3.2.3 Vertical load. The resistance to vertical loads 
shall be determined using the vertical foundation pres- 
sure set forth in Table 1806.2. 

1807.3.3 Backfill. The backfill in the annular space around 
columns not embedded in poured footings shall be by one of 
the following methods: 

1. Backfill shall be of concrete with a specified com- 
pressive strength of not less than 2,000 psi (13.8 
MPa). The hole shall not be less than 4 inches (102 
mm) larger than the diameter of the column at its bot- 
tom or 4 inches (102 mm) larger than the diagonal 
dimension of a square or rectangular column. 

2. Backfill shall be of clean sand. The sand shall be thor- 
oughly compacted by tamping in layers not more than 
8 inches (203 mm) in depth. 

3. Backfill shall be of controlled low-strength material 
(CLSM). 



SECTION 1808 
FOUNDATIONS 

1808.1 General. Foundations shall be designed and con- 
structed in accordance with Sections 1808.2 through 1808.9. 
Shallow foundations shall also satisfy the requirements of Sec- 
tion 1809. Deep foundations shall also satisfy the requirements 
of Section 1810. 

1808.2 Design for capacity and settlement. Foundations 
shall be so designed that the allowable bearing capacity of the 
soil is not exceeded, and that differential settlement is mini- 
mized. Foundations in areas with expansive soils shall be 
designed in accordance with the provisions of Section 1808.6. 

1808.3 Design loads. Foundations shall be designed for the 
most unfavorable effects due to the combinations of loads spec- 
ified in Section 1605.2 or 1605.3. The dead load is permitted to 
include the weight of foundations and overlying fill. Reduced 
live loads, as specified in Sections 1607.9 and 1607.11, shall be 
permitted to be used in the design of foundations. 



398 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



1808.3.1 Seismic overturning. Where foundations are pro- 
portioned using the load combinations of Section 1605.2 or 
1605.3.1, and the computation of seismic overturning 
effects is by equivalent lateral force analysis or modal anal- 
ysis, the proportioning shall be in accordance with Section 
12.13.4 of ASCE 7. 

1808.4 Vibratory loads. Where machinery operations or other 
vibrations are transmitted through the foundation, consider- 
ation shall be given in the foundation design to prevent detri- 
mental disturbances of the soil. 

1808.5 Shifting or moving soils. Where it is known that the 
shallow subsoils are of a shifting or moving character, founda- 
tions shall be carried to a sufficient depth to ensure stability. 

1808.6 Design for expansive soils. Foundations for buildings 
and structures founded on expansive soils shall be designed in 
accordance with Section 1808.6.1 or 1808.6.2. 

Exception: Foundation design need not comply with Sec- 
tion 1808.6.1 or 1808.6.2 where one of the following condi- 
tions is satisfied: 

1. The soil is removed in accordance with Section 
1808.6.3; or 

2. The building official approves stabilization of the soil 
in accordance with Section 1808.6.4. 

1808.6.1 Foundations. Foundations placed on or within the 
active zone of expansive soils shall be designed to resist dif- 
ferential volume changes and to prevent structural damage 
to the supported structure. Deflection and racking of the 
supported structure shall be limited to that which will not 
interfere with the usability and serviceability of the struc- 
ture. 

Foundations placed below where volume change occurs 
or below expansive soil shall comply with the following 
provisions: 

1. Foundations extending into or penetrating expansive 
soils shall be designed to prevent uplift of the sup- 
ported structure. 

2. Foundations penetrating expansive soils shall be 
designed to resist forces exerted on the foundation 
due to soil volume changes or shall be isolated from 
the expansive soil. 

1808.6.2 Slab-on-ground foundations. Moments, shears 
and deflections for use in designing slab-on-ground, mat or 
raft foundations on expansive soils shall be determined in 
accordance with WRJICRSJ Design of Slab -on-Ground 
Foundations or PT J Standard Requirements for Analysis of 
Shallow Concrete Foundations on Expansive Soils. Using 
the moments, shears and deflections determined above, 
nonprestressed slabs-on-ground, mat or raft foundations on 
expansive soils shall be designed in accordance with 
WRJICRSJ Design of Slab -on-Ground Foundations and 
post-tensioned slab-on-ground, mat or raft foundations on 
expansive soils shall be designed in accordance with PTJ 
Standard Requirements for Design of Shallow 
Post- Tensioned Concrete Foundations on Expansive Soils. 
It shall be permitted to analyze and design such slabs by 
other methods that account for soil- structure interaction, the 



deformed shape of the soil support, the plate or stiffened 
plate action of the slab as well as both center lift and edge lift 
conditions. Such alternative methods shall be rational and 
the basis for all aspects and parameters of the method shall 
be available for peer review. 

1808.6.3 Removal of expansive soil. Where expansive soil 
is removed in lieu of designing foundations in accordance 
with Section 1808.6.1 or 1808.6.2, the soil shall be removed 
to a depth sufficient to ensure a constant moisture content in 
the remaining soil. Fill material shall not contain expansive 
soils and shall comply with Section 1804.5 or 1804.6. 

Exception: Expansive soil need not be removed to the 
depth of constant moisture, provided the confining pres- 
sure in the expansive soil created by the fill and sup- 
ported structure exceeds the swell pressure. 

1808.6.4 Stabilization. Where the active zone of expansive 
soils is stabilized in lieu of designing foundations in accor- 
dance with Section 1808.6.1 or 1808.6.2, the soil shall be 
stabilized by chemical, dewatering, presaturation or equiva- 
lent techniques. 

1808.7 Foundations on or adjacent to slopes. The placement 
of buildings and structures on or adjacent to slopes steeper than 
one unit vertical in three units horizontal (33.3-percent slope) 
shall comply with Sections 1808.7.1 through 1808.7.5. 

1808.7.1 Building clearance from ascending slopes. In 
general, buildings below slopes shall be set a sufficient dis- 
tance from the slope to provide protection from slope drain- 
age, erosion and shallow failures. Except as provided in 
Section 1808.7.5 and Figure 1808.7.1, the following criteria 
will be assumed to provide this protection. Where the exist- 
ing slope is steeper than one unit vertical in one unit hori- 
zontal (100-percent slope), the toe of the slope shall be 
assumed to be at the intersection of a horizontal plane drawn 
from the top of the foundation and a plane drawn tangent to 
the slope at an angle of 45 degrees (0.79 rad) to the horizon- 
tal. Where a retaining wall is constructed at the toe of the 
slope, the height of the slope shall be measured from the top 
of the wall to the top of the slope. 

1808.7.2 Foundation setback from descending slope sur- 
face. Foundations on or adjacent to slope surfaces shall be 
founded in firm material with an embedment and set back 
from the slope surface sufficient to provide vertical and lat- 
eral support for the foundation without detrimental settle- 
ment. Except as provided for in Section 1808.7.5 and Figure 
1808.7.1, the following setback is deemed adequate to meet 
the criteria. Where the slope is steeper than 1 unit vertical in 
1 unit horizontal (100-percent slope), the required setback 
shall be measured from an imaginary plane 45 degrees (0.79 
rad) to the horizontal, projected upward from the toe of the 
slope. 

1808.7.3 Pools. The setback between pools regulated by 
this code and slopes shall be equal to one-half the building 
footing setback distance required by this section. That por- 
tion of the pool wall within a horizontal distance of 7 feet 
(2134 mm) from the top of the slope shall be capable of sup- 
porting the water in the pool without soil support. 



2009 INTERNATIONAL BUILDING CODE® 



399 



SOILS AND FOUNDATIONS 



PACE OF 

FOOTiMG 



FACE OF 
STRUCTURE 




For 51: 1 foot = 304.8 mm. 



AT LEAST THE SMALLER OF W2 AND *5 FEET 



FIGURE 1808.7.1 
FOUNDATION CLEARANCES FROM SLOPES 



1808.7.4 Foundation elevation. On graded sites, the top of 
any exterior foundation shall extend above the elevation of 
the street gutter at point of discharge or the inlet of an 
approved drainage device a minimum of 12 inches (305 
mm) plus 2 percent. Alternate elevations are permitted sub- 
ject to the approval of the building official, provided it can 
be demonstrated that required drainage to the point of dis- 
charge and away from the structure is provided at alloca- 
tions on the site. 

1808.7.5 Alternate setback and clearance. Alternate set- 
backs and clearances are permitted, subject to the approval 
of the building official. The building officialshaW be permit- 
ted to require a geotechnical investigation as set forth in Sec- 
tion 1803.5.10. 

1808.8 Concrete foundations. The design, materials and con- 
struction of concrete foundations shall comply with Sections 
1808.8.1 through 1808.8.6 and the provisions of Chapter 19. 

Exception: Where concrete footings supporting walls of 
light-frame construction are designed in accordance with 
Table 1809.7, a specific design in accordance with Chapter 
19 is not required. 

1808.8.1 Concrete or grout strength and mix propor- 
tioning. Concrete or grout in foundations shall have a speci- 
fied compressive strength (f) not less than the largest 
applicable value indicated in Table 1808.8.1. 

Where concrete is placed through a funnel hopper at the 
top of a deep foundation element, the concrete mix shall be 
designed and proportioned so as to produce a cohesive 
workable mix having a slump of not less than 4 inches (102 
mm) and not more than 8 inches (204 mm). Where concrete 
or grout is to be pumped, the mix design including slump 
shall be adjusted to produce a pump able mixture. 

1808.8.2 Concrete cover. The concrete cover provided for 
prestressed and nonprestressed reinforcement in founda- 
tions shall be no less than the largest applicable value speci- 
fied in Table 1808.8.2. Longitudinal bars spaced less than 
l 1 / 2 inches (38 mm) clear distance apart shall be considered 
bundled bars for which the concrete cover provided shall 
also be no less than that required by Section 7.7.4 of ACI 
318. Concrete cover shall be measured from the concrete 
surface to the outermost surface of the steel to which the 



cover requirement applies. Where concrete is placed in a 
temporary or permanent casing or a mandrel, the inside face 
of the casing or mandrel shall be considered the concrete 
surface. 

1808.8.3 Placement of concrete. Concrete shall be placed 
in such a manner as to ensure the exclusion of any foreign 
matter and to secure a full-size foundation. Concrete shall 
not be placed through water unless a tremie or other method 
approved by the building official is used. Where placed 
under or in the presence of water, the concrete shall be 
deposited by approved means to ensure minimum segrega- 
tion of the mix and negligible turbulence of the water. 
Where depositing concrete from the top of a deep founda- 
tion element, the concrete shall be chuted directly into 
smooth- sided pipes or tubes or placed in a rapid and contin- 
uous operation through a funnel hopper centered at the top 
of the element. 

1808.8.4 Protection of concrete. Concrete foundations 
shall be protected from freezing during depositing and for a 
period of not less than five days thereafter. Water shall not 
be allowed to flow through the deposited concrete. 

1808.8.5 Forming of concrete. Concrete foundations are 
permitted to be cast against the earth where, in the opinion 
of the building official, soil conditions do not require 
formwork. Where formwork is required, it shall be in accor- 
dance with Chapter 6 of ACI 318. 

1808.8.6 Seismic requirements. See Section 1908 for 
additional requirements for foundations of structures 
assigned to Seismic Design CategoryC, D, E or F. 

For structures assigned to Seismic Design CategoryD, E 
or F, provisions of ACI 318, Sections 21.12.1 through 
21.12.4, shall apply where not in conflict with the provi- 
sions of Sections 1808 through 1810. 

Exceptions: 

1. Detached one- and two-family dwellings of 
light-frame construction and two stories or less 
above grade plane are not required to comply with 
the provisions of ACI 318, Sections 21.12.1 
through 21.12.4. 

2. Section 21.12.4.4(a) of ACI 318 shall not apply. 



400 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



TABLE 1808.8.1 
MINIMUM SPECIFIED COMPRESSIVE STRENGTH ('cOF CONCRETE OR GROUT 



FOUNDATION ELEMENT OR CONDITION 


SPECIFIED COMPRESSIVE 
STRENGTH, fie 


1. Foundations for structures assigned to Seismic Design Category A, B or C 


2,500 psi 


2a. Foundations for Group R or U occupancies of light-frame construction, two stories or less in height, 
assigned to Seismic Design Category D, E or F 


2,500 psi 


2b. Foundations for other structures assigned to Seismic Design Category D, E or F 


3,000 psi 


3. Precast nonprestressed drived piles 


4,000 psi 


4. Socketed drilled shafts 


4,000 psi 


5. Micropiles 


4,000 psi 


6. Precast prestressed driven piles 


5,000 psi 



For 51 : 1 pound per square inch = 0.00689 MPa. 



TABLE 1808.8.2 
MINIMUM CONCRETE COVER 



FOUNDATION ELEMENT OR CONDITION 


MINIMUM COVER 


1. Shallow foundations 


In accordance with Section 7.7 of ACI 318 


2. Precast nonprestressed deep foundation elements 
Exposed to seawater 
Not manufactured under plant conditions 
Manufactured under plant control conditions 


3 inches 
2 inches 
In accordance with Section 7.7.3 of ACI 318 


3. Precast prestressed deep foundation elements 
Exposed to seawater 
Other 


2.5 inches 

In accordance with Section 7.7.3 of ACI 318 


4. Cast-in-place deep foundation elements not enclosed by a steel pipe, tube or permanent 
casing 


2.5 inches 


5. Cast-in-place deep foundation elements enclosed by a steel pipe, tube or permanent casing 


1 inch 


6. Structural steel core within a steel pipe, tube or permanent casing 


2 inches 


7. Cast-in-place drilled shafts enclosed by a stable rock socket 


1.5 inches 



For 51 : 1 inch = 25.4 mm. 



2009 INTERNATIONAL BUILDING CODE® 



401 



SOILS AND FOUNDATIONS 



1808.9 Vertical masonry foundation elements. Vertical 
masonry foundation elements that are not foundation piers as 
defined in Section 2102.1 shall be designed as piers, walls or 
columns, as applicable, in accordance with TMS 4021 ACI 
530/ASCE 5. 



SECTION 1809 
SHALLOW FOUNDATIONS 

1809.1 General. Shallow foundations shall be designed and 
constructed in accordance with Sections 1809.2 through 
1809.13. 

1809.2 Supporting soils. Shallow foundations shall be built on 
undisturbed soil, compacted fill material or controlled 
low-strength material (CLSM). Compacted fill material shall 
be placed in accordance with Section 1804.5. CLSM shall be 
placed in accordance with Section 1804.6. 

1809.3 Stepped footings. The top surface of footings shall be 
level. The bottom surface of footings shall be permitted to have 
a slope not exceeding one unit vertical in 10 units horizontal 
(1 0-percent slope). Footings shall be stepped where it is neces- 
sary to change the elevation of the top surface of the footing or 
where the surface of the ground slopes more than one unit verti- 
cal in 10 units horizontal (10- percent slope) . 

1809.4 Depth and width of footings. The minimum depth of 
footings below the undisturbed ground surface shall be 12 
inches (305 mm). Where applicable, the requirements of Sec- 
tion 1809.5 shall also be satisfied. The minimum width of foot- 
ings shall be 12 inches (305 mm). 

1809.5 Frost protection. Except where otherwise protected 
from frost, foundations and other permanent supports of build- 
ings and structures shall be protected from frost by one or more 
of the following methods: 

1. Extending below the frost line of the locality; 

2. Constructing in accordance with ASCE 32; or 

3. Erecting on solid rock. 

Exception: Free-standing buildings meeting all of the fol- 
lowing conditions shall not be required to be protected: 

1. Assigned to Occupancy Category I, in accordance 
with Section 1604.5; 

2. Area of 600 square feet (56 m 2 ) or less for light-frame 
construction or 400 square feet (37 m 2 ) or less for 
other than light-frame construction ; and 

3. Eave height of 10 feet (3048 mm) or less. 

Shallow foundations shall not bear on frozen soil unless such 
frozen condition is of a permanent character. 

1809.6 Location of footings. Footings on granular soil shall be 
so located that the line drawn between the lower edges of 
adjoining footings shall not have a slope steeper than 30 
degrees (0.52 rad) with the horizontal, unless the material sup- 
porting the higher footing is braced or retained or otherwise lat- 
erally supported in an approved manner or a greater slope has 
been properly established by engineering analysis. 



1809.7 Prescriptive footings for light-frame construction. 
Where a specific design is not provided, concrete or 
masonry-unit footings supporting walls of light-frame con- 
struction shall be permitted to be designed in accordance with 
Table 1809.7. 

TABLE 1809.7 

PRESCRIPTIVE FOOTINGS SUPPORTING WALLS OF 

LIGHT-FRAME CONSTRUCTION*, b,c,d,e 



NUMBER OF FLOORS 

SUPPORTED BY THE 

FOOTING f 


WIDTH OF FOOTING 

(inches) 


THICKNESS OF 
FOOTING (inches) 


1 


12 


6 


2 


15 


6 


3 


18 


8§ 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Depth of footings shall be in accordance with Section 1809.4. 

b. The ground under the floor shall be permitted to be excavated to the elevation 
of the top of the footing. 

c. Interior stud-bearing walls shall be permitted to be supported by isolated 
footings . The footing width and length shall be twice the width shown in this 
table, and footings shall be spaced not more than 6 feet on center. 

d. See Section 1908 for additional requirements for concrete footings of struc- 
tures assigned to Seismic DeSign Category C, D, E or F. 

e. For thickness of foundation walls, see Section 1807.1.6. 

f. Footings shall be permitted to support a roof in addition to the stipulated 
number of floors . Footings supporting roof only shall be as required for sup- 
porting one floor. 

g. Plain concrete footings for Group R-3 occupancies shall be permitted to be 6 
inches thick. 

1809.8 Plain concrete footings. The edge thickness of plain 
concrete footings supporting walls of other than light-frame 
construction shall not be less than 8 inches (203 mm) where 
placed on soil or rock. 

Exception: For plain concrete footings supporting Group 
R-3 occupancies, the edge thickness is permitted to be 6 
inches (152 mm), provided that the footing does not extend 
beyond a distance greater than the thickness of the footing 
on either side of the supported wall. 

1809.9 Masonry-unit footings. The design, materials and 
construction of masonry-unit footings shall comply with Sec- 
tions 1809.9.1 and 1809.9.2, and the provisions of Chapter 21. 

Exception: Where a specific design is not provided, 
masonry-unit footings supporting walls of light-frame con- 
struction shall be permitted to be designed in accordance 
with Table 1809.7. 

1809.9.1 Dimensions. Mansonry-unit footings shall be laid 
in Type M or S mortar complying with Section 2103.8 and 
the depth shall not be less than twice the projection beyond 
the wall, pier or column. The width shall not be less than 8 
inches (203 mm) wider than the wall supported thereon. 

1809.9.2 Offsets. The maximum offset of each course in 
brick foundation walls stepped up from the footings shall be 

V/ 2 inches (38 mm) where laid in single courses, and 3 
inches (76 mm) where laid in double courses. 

1809.10 Pier and curtain wall foundations. Except in Seis- 
mic DeSign Categories D, E and F, pier and curtain wall foun- 
dations shall be permitted to be used to support light-frame 



402 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



construction not more than two stories above grade plane, pro- 
vided the following requirements are met: 

1. All load-bearing walls shall be placed on continuous 
concrete footings bonded integrally with the exterior 
wall footings. 

2. The minimum actual thickness of a load-bearing 
masonry wall shall not be less than 4 inches (102 mm) 
nominal or 3 5 /8 inches (92 mm) actual thickness, and 
shall be bonded integrally with piers spaced 6 feet (1829 
mm) on center (o.c). 

3. Piers shall be constructed in accordance with Chapter 21 
and the following: 

3.1. The unsupported height of the masonry piers 
shall not exceed 10 times their least dimension. 

3.2. Where structural clay tile or hollow concrete 
masonry units are used for piers supporting 
beams and girders, the cellular spaces shall be 
filled solidly with concrete or Type M or S mor- 
tar. 

Exception: Unfilled hollow piers shall be permitted 
where the unsupported height of the pier is not more 
than four times its least dimension. 

3.3. Hollow piers shall be capped with 4 inches 
(102 mm) of solid masonry or concrete or the 
cavities of the top course shall be filled with 
concrete or grout. 

4. The maximum height of a 4-inch (102 mm) load-bearing 
masonry foundation wall supporting wood frame walls 
and floors shall not be more than 4 feet (1219 mm) in 
height. 

5. The unbalanced fill for 4-inch (102 mm) foundation 
walls shall not exceed 24 inches (610 mm) for solid 
masonry, nor 12 inches (305 mm) for hollow masonry. 

1809.11 Steel grillage footings. Grillage footings of structural 
steel shapes shall be separated with approved steel spacers and 
be entirely encased in concrete with at least 6 inches (152 mm) 
on the bottom and at least 4 inches (102 mm) at all other points. 
The spaces between the shapes shall be completely filled with 
concrete or cement grout. 

1809.12 Timber footings. Timber footings shall be permitted 
for buildings of Type V construction and as otherwise 
approvedby the building official. Such footings shall be treated 
in accordance with AWPA Ul (Commodity Specification A, 
Use Category 4B). Treated timbers are not required where 
placed entirely below permanent water level, or where used as 
capping for wood piles that project above the water level over 
submerged or marsh lands. The compressive stresses perpen- 
dicular to grain in untreated timber footings supported upon 
treated piles shall not exceed 70 percent of the allowable 
stresses for the species and grade of timber as specified in the 
AF&PANDS. 

1809.13 Footing seismic ties. Where a structure is assigned to 
Seismic Design CategoryY), E or F in accordance with Section 
1613, individual spread footings founded on soil defined in 
Section 1613.5.2 as Site Class E or F shall be interconnected by 
ties. Unless it is demonstrated that equivalent restraint is pro- 



vided by reinforced concrete beams within slabs on grade or 
reinforced concrete slabs on grade, ties shall be capable of car- 
rying, in tension or compression, a force equal to the lesser of 
the product of the larger footing design gravity load times the 
seismic coefficient, S)S' divided by 10 and 25 percent of the 
smaller footing design gravity load. 



SECTION 1810 
DEEP FOUNDATIONS 

1810.1 General. Deep foundations shall be analyzed, 
designed, detailed and installed in accordance with Sections 

1810.1 through 1810.4. 

1810.1.1 Geotechnical investigation. Deep foundations 
shall be designed and installed on the basis of a geotechnical 
investigation as set forth in Section 1803. 

1810.1.2 Use of existing deep foundation elements. Deep 
foundation elements left in place where a structure has been 
demolished shall not be used for the support of new con- 
struction unless satisfactory evidence is submitted to the 
bUilding official, which indicates that the elements are 
sound and meet the requirements of this code. Such ele- 
ments shall be load tested or redriven to verify their capaci- 
ties. The design load applied to such elements shall be the 
lowest allowable load as determined by tests or redriving 
data. 

1810.1.3 Deep foundation elements classified as col- 
umns. Deep foundation elements standing unbraced in air, 
water or fluid soils shall be classified as columns and 
designed as such in accordance with the provisions of this 
code from their top down to the point where adequate lateral 
support is provided in accordance with Section 1810.2.1. 

Exception: Where the unsupported height to least hori- 
zontal dimension of a cast-in-place deep foundation ele- 
ment does not exceed three, it shall be permitted to 
design and construct such an element as a pedestal in 
accordance with ACI 318. 

1810.1.4 Special types of deep foundations. The use of 

types of deep foundation elements not specifically men- 
tioned herein is permitted, subject to the approval of the 
building official, upon the submission of acceptable test 
data, calculations and other information relating to the 
structural properties and load capacity of such elements. 
The allowable stresses for materials shall not in any case 
exceed the limitations specified herein. 

1810.2 Analysis. The analysis of deep foundations for design 
shall be in accordance with Sections 1810.2.1 through 
1810.2.5. 

1810.2.1 Lateral support. Any soil other than fluid soil 
shall be deemed to afford sufficient lateral support to pre- 
vent buckling of deep foundation elements and to permit the 
design of the elements in accordance with accepted engi- 
neering practice and the applicable provisions of this code. 

Where deep foundation elements stand unbraced in air, 
water or fluid soils, it shall be permitted to consider them 
laterally supported at a point 5 feet (1524 mm) into stiff soil 
or 10 feet (3048 mm) into soft soil unless otherwise 



2009 INTERNATIONAL BUILDING CODE® 



403 



SOILS AND FOUNDATIONS 



approvedby the building officialon the basis of a geotechni- 
cal investigation by a registered design professional. 

1810.2.2 Stability. Deep foundation elements shall be 
braced to provide lateral stability in all directions. Three or 
more elements connected by a rigid cap shall be considered 
braced, provided that the elements are located in radial 
directions from the centroid of the group not less than 60 
degrees (1 rad) apart. A two-element group in a rigid cap 
shall be considered to be braced along the axis connecting 
the two elements. Methods used to brace deep foundation 
elements shall be subject to the approval of the bUilding offi- 
cial 

Deep foundation elements supporting walls shall be 
placed alternately in lines spaced at least 1 foot (305 mm) 
apart and located symmetrically under the center of gravity 
of the wall load carried, unless effective measures are taken 
to provide for eccentricity and lateral forces, or the founda- 
tion elements are adequately braced to provide for lateral 
stability. 

Exceptions: 

1. Isolated cast-in-place deep foundation elements 
without lateral bracing shall be permitted where 
the least horizontal dimension is no less than 2 feet 
(610 mm), adequate lateral support in accordance 
with Section 1810.2.1 is provided for the entire 
height and the height does not exceed 12 times the 
least horizontal dimension. 

2. A single row of deep foundation elements without 
lateral bracing is permitted for one- and two- fam- 
ily dwellings and lightweight construction not 
exceeding two stories above grade plane or 35 feet 
(10 668 mm) in building height, provided the cen- 
ters of the elements are located within the width of 
the supported wall. 

1810.2.3 Settlement. The settlement of a single deep foun- 
dation element or group thereof shall be estimated based on 
approved methods of analysis. The predicted settlement 
shall cause neither harmful distortion of, nor instability in, 
the structure, nor cause any element to be loaded beyond its 
capacity. 

1810.2.4 Lateral loads. The moments, shears and lateral 
deflections used for design of deep foundation elements 
shall be established considering the nonlinear interaction of 
the shaft and soil, as determined by a registered design pro- 
fessional. Where the ratio of the depth of embedment of the 
element to its least horizontal dimension is less than or equal 
to six, it shall be permitted to assume the element is rigid. 

1810.2.4.1 Seismic Design Categories D through F. 
For structures assigned to Seismic Design CategoryD, E 
or F, deep foundation elements on Site Class E or F sites, 
as determined in Section 1613.5.2, shall be designed and 
constructed to withstand maximum imposed curvatures 
from earthquake ground motions and structure response. 
Curvatures shall include free-field soil strains modified 
for soil-foundation-structure interaction coupled with 



foundation element deformations associated with earth- 
quake loads imparted to the foundation by the structure. 

Exception: Deep foundation elements that satisfy the 
following additional detailing requirements shall be 
deemed to comply with the curvature capacity 
requirements of this section. 

1. Precast prestressed concrete piles detailed in 
accordance with Section 1810.3.8.3.3. 

2. Cast-in-place deep foundation elements with a 
minimum longitudinal reinforcement ratio of 
0.005 extending the full length of the element 
and detailed in accordance with Sections 
21.6.4.2, 21.6.4.3 and 21.6.4.4 of ACI 318 as 
required by Section 1810.3.9.4.2.2. 

1810.2.5 Group effects. The analysis shall include group 
effects on lateral behavior where the center-to-center spac- 
ing of deep foundation elements in the direction of lateral 
force is less than eight times the least horizontal dimension 
of an element. The analysis shall include group effects on 
axial behavior where the center-to-center spacing of deep 
foundation elements is less than three times the least hori- 
zontal dimension of an element. 

1810.3 Design and detailing. Deep foundations shall be 
designed and detailed in accordance with Sections 1810.3.1 
through 1810.3.12. 

1810.3.1 Design conditions. Design of deep foundations 
shall include the design conditions specified in Sections 
1810.3.1.1 through 1810.3.1.6, as applicable. 

1810.3.1.1 Design methods for concrete elements. 
Where concrete deep foundations are laterally supported 
in accordance with Section 1810.2.1 for the entire height 
and applied forces cause bending moments no greater 
than those resulting from accidental eccentricities, struc- 
tural design of the element using the load combinations 
of Section 1605.3 and the allowable stresses specified in 
this chapter shall be permitted. Otherwise, the structural 
design of concrete deep foundation elements shall use 
the load combinations of Section 1605.2 and approved 
strength design methods. 

1810.3.1.2 Composite elements. Where a single deep 
foundation element comprises two or more sections of 
different materials or different types spliced together, 
each section of the composite assembly shall satisfy the 
applicable requirements of this code, and the maximum 
allowable load in each section shall be limited by the 
structural capacity of that section. 

1810.3.1.3 Mislocation. The foundation or superstruc- 
ture shall be designed to resist the effects of the 
mislocation of any deep foundation element by no less 
than 3 inches (76 mm). To resist the effects of 
mislocation, compressive overload of deep foundation 
elements to 110 percent of the allowable design load 
shall be permitted. 

1810.3.1.4 Driven piles. Driven piles shall be designed 
and manufactured in accordance with accepted engineer- 



404 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



ing practice to resist all stresses induced by handling, 
driving and service loads. 

1810.3.1.5 Helical piles. Helical piles shall be designed 
and manufactured in accordance with accepted engineer- 
ing practice to resist all stresses induced by installation 
into the ground and service loads. 

1810.3.1.6 Casings. Temporary and permanent casings 
shall be of steel and shall be sufficiently strong to resist 
collapse and sufficiently water tight to exclude any for- 
eign materials during the placing of concrete. Where a 
permanent casing is considered reinforcing steel, the 
steel shall be protected under the conditions specified in 
Section 1810.3.2.5. Horizontal joints in the casing shall 
be spliced in accordance with Section 1810.3.6. 

1810.3.2 Materials. The materials used in deep foundation 
elements shall satisfy the requirements of Sections 
1810.3.2.1 through 1810.3.2.8, as applicable. 

1810.3.2.1 Concrete. Where concrete is cast in a steel 
pipe or where an enlarged base is formed by compacting 
concrete, the maximum size for coarse aggregate shall be 
3/ 4 inch (19.1 mm). Concrete to be compacted shall have 
a zero slump. 

1810.3.2.1.1 Seismic hooks. For structures assigned 
to Seismic Design Category C, D, E or F in accor- 
dance with Section 1613, the ends of hoops, spirals 
and ties used in concrete deep foundation elements 
shall be terminated with seismic hooks, as defined in 
ACI 318, and shall be turned into the confined con- 
crete core. 

1810.3.2.1.2 ACI 318 Equation (10-5). Where this 
chapter requires detailing of concrete deep founda- 
tion elements in accordance with Section 21.6.4.4 of 
ACI 318, compliance with Equation (10-5) of ACI 
318 shall not be required. 

1810.3.2.2 Prestressing steel. Prestressing steel shall 
conform to ASTM A 416. 

1810.3.2.3 Structural steel. Structural steel piles, steel 
pipe and fully welded steel piles fabricated from plates 
shall conform to ASTM A 36, ASTM A 252, ASTM A 
283, ASTM A 572, ASTM A 588, ASTM A 690, ASTM 
A 913 or ASTM A 992. 

1810.3.2.4 Timber. Timber deep foundation elements 
shall be designed as piles or poles in accordance with 
AF&PA NDS. Round timber elements shall conform to 
ASTM D 25. Sawn timber elements shall conform to 
DOC PS-20. 

1810.3.2.4.1 Preservative treatment. Timber deep 
foundation elements used to support permanent struc- 
tures shall be treated in accordance with this section 
unless it is established that the tops of the untreated 
timber elements will be below the lowest 
ground-water level assumed to exist during the life of 
the structure. Preservative and minimum final reten- 
tion shall be in accordance with AWPA Ul (Com- 
modity Specification E, Use Category 4C) for round 
timber elements and AWPA Ul (Commodity Specifi- 



cation A, Use Category 4B) for sawn timber elements. 
Preservative-treated timber elements shall be subject 
to a quality control program administered by an 
approved agency. Element cutoffs shall be treated in 
accordance with AWPA M4. 

1810.3.2.5 Protection of materials. Where boring 
records or site conditions indicate possible deleterious 
action on the materials used in deep foundation elements 
because of soil constituents, changing water levels or 
other factors, the elements shall be adequately protected 
by materials, methods or processes approved by the 
bUilding official. Protective materials shall be applied to 
the elements so as not to be rendered ineffective by 
installation. The effectiveness of such protective mea- 
sures for the particular purpose shall have been thor- 
oughly established by satisfactory service records or 
other evidence. 

1810.3.2.6 Allowable stresses. The allowable stresses 
for materials used in deep foundation elements shall not 
exceed those specified in Table 1810.3.2.6. 

1810.3.2.7 Increased allowable compressive stress for 
cased cast-in-place elements. The allowable compres- 
sive stress in the concrete shall be permitted to be 
increased as specified in Table 1810.3.2.6 for those por- 
tions of permanently cased cast-in-place elements that 
satisfy all of the following conditions: 

1. The design shall not use the casing to resist any 
portion of the axial load imposed. 

2. The casing shall have a sealed tip and be mandrel 
driven. 

3. The thickness of the casing shall not be less than 
manufacturer's standard gage No. 14 (0.068 inch) 
(1.75 mm). 

4. The casing shall be seamless or provided with 
seams of strength equal to the basic material and be 
of a configuration that will provide confinement to 
the cast-in-place concrete. 

5. The ratio of steel yield strength (FJ) to specified 
compressive strength (f) shall not be less than 
six. 

6. The nominal diameter of the element shall not be 
greater than 16 inches (406 mm). 

1810.3.2.8 Justification of higher allowable stresses. 
Use of allowable stresses greater than those specified in 
Section 1810.3.2.6 shall be permitted where supporting 
datajustifying such higher stresses is filed with the build- 
ing official. Such substantiating data shall include: 

1. A geotechnical investigation in accordance with 
Section 1803; and 

2. Load tests in accordance with Section 
1810.3.3.1.2, regardless of the load supported by 
the element. 

The design and installation of the deep foundation ele- 
ments shall be under the direct supervision of a regis- 
tered design professional knowledgeable in the field of 



2009 INTERNATIONAL BUILDING CODE® 



405 



SOILS AND FOUNDATIONS 



TABLE 1810.3.2.6 
ALLOWABLE STRESSES FOR MATERIALS USED IN DEEP FOUNDATION ELEMENTS 



MATERIAL TYPE AND CONDITION 


MAXIMUM ALLOWABLE STRESS a 


1. Concrete or grout in compression 

Cast-in-place with a permanent casing in accordance with Section 1810.3.2.7 
Cast-in-place in a pipe, tube, other permanent casing or rock 
Cast-in-place without a permanent casing 
Precast nonprestressed 
Precast prestressed 


0.4 ['e 
0.33 ['e 

0.3 f'e 
0.33 ['e 

0.33 [V 0.27 f pc 


2. Nonprestressed reinforcement in compression 


0.4 f y < 30,000 psi 


3. Structural steel in compression 

Cores within concrete-filled pipes or tubes 

Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8 

Pipes or tubes for micropiles 

Other pipes, tubes or H-piles 

Helical piles 


0.5 F < 32,000 psi 
0.5 Fy< 32,000 psi 
0.4 F y < 32,000 psi 
0.35 F y < 16,000 psi 
0.6 F y < 0.5 F u 


4. Nonprestressed reinforcement in tension 
Within micropiles 
Other conditions 


0.6 f y 
0.5 f y < 24,000 psi 


5. Structural steel in tension 

Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8 
Other pipes, tubes or H-piles 
Helical piles 


0.5 F y < 32,000 psi 

0.35 F y < 16,000 psi 

0.6 F y < 0.5 F u 


6. Timber 


In accordance with the AF&PA NDS 



a. [ ' cis the specified compressive strength of the concrete or grout; f is the compressive stress on the gross concrete section due to effective prestress forces only; f is 
the specified yield strength of reinforcement; F is the specified minimum yield stress of structural steel; F u is the specified minimum tensile stress of structural 
steel. 

b. The stresses specified apply to the gross cross-sectional area within the concrete surf ace. Where a temporary or permanent casing is used, the inside face of the cas- 
ing shall be considered the concrete surface. 



soil mechanics and deep foundations who shall submit a 
report to the building official stating that the elements as 
installed satisfy the design criteria. 

1810.3.3 Determination of allowable loads. The allow- 
able axial and lateral loads on deep foundation elements 
shall be determined by an approved formula, load tests or 
method of analysis. 

1810.3.3.1 Allowable axial load. The allowable axial 
load on a deep foundation element shall be determined in 
accordance with Sections 1810.3.3.1.1 through 
1810.3.3.1.9. 

1810.3.3.1.1 Driving criteria. The allowable com- 
pressive load on any driven deep foundation element 
where determined by the application of an approved 
driving formula shall not exceed 40 tons (356 kN). 
For allowable loads above 40 tons (356 kN), the wave 
equation method of analysis shall be used to estimate 
driveability for both driving stresses and net displace- 
ment per blow at the ultimate load. Allowable loads 
shall be verified by load tests in accordance with Sec- 
tion 1810.3.3.1.2. The formula or wave equation load 
shall be determined for gravity-drop or power-actu- 
ated hammers and the hammer energy used shall be 
the maximum consistent with the size, strength and 



weight of the driven elements. The use of a follower is 
permitted only with the approval of the building offi- 
cial. The introduction of fresh hammer cushion or pile 
cushion material just prior to final penetration is not 
permitted. 

1810.3.3.1.2 Load tests. Where design compressive 
loads are greater than those determined using the 
allowable stresses specified in Section 1810.3.2.6, 
where the design load for any deep foundation ele- 
ment is in doubt, or where cast-in-place deep founda- 
tion elements have an enlarged base formed either by 
compacting concrete or by driving a precast base, 
control test elements shall be tested in accordance 
with ASTM D 1143 or ASTM D 4945. At least one 
element shall be load tested in each area of uniform 
subsoil conditions. Where required by the bUilding 
official, additional elements shall be load tested where 
necessary to establish the safe design capacity. The 
resulting allowable loads shall not be more than 
one-half of the ultimate axial load capacity of the test 
element as assessed by one of the published methods 
listed in Section 1810.3.3.1.3 with consideration for 
the test type, duration and subsoil. The ultimate axial 
load capacity shall be determined by a registered 
design professional with consideration given to toler- 



406 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



able total and differential settlements at design load in 
accordance with Section 1810.2.3. In subsequent 
installation of the balance of deep foundation ele- 
ments, all elements shall be deemed to have a support- 
ing capacity equal to that of the control element where 
such elements are of the same type, size and relative 
length as the test element; are installed using the same 
or comparable methods and equipment as the test ele- 
ment; are installed in similar subsoil conditions as the 
test element; and, for driven elements, where the rate 
of penetration (e.g., net displacement per blow) of 
such elements is equal to or less than that of the test 
element driven with the same hammer through a com- 
parable driving distance. 

1810.3.3.1.3 Load test evaluation methods. It shall 
be permitted to evaluate load tests of deep foundation 
elements using any of the following methods: 

1. Davis son Offset Limit. 

2. Brinch-Hansen 90% Criterion. 

3. Butler-Hoy Criterion. 

4. Other methods approved by the bUilding offi- 
cial. 

1810.3.3.1.4 Allowable frictional resistance. The 
assumed frictional resistance developed by any 
uncased cast-in-place deep foundation element shall 
not exceed one-sixth of the bearing value of the soil 
material at minimum depth as set forth in Table 
1806.2, up to a maximum of 500 psf (24 kPa) , unless a 
greater value is allowed by the bUilding official on the 
basis of a geotechnical investigation as specified in 
Section 1803 or a greater value is substantiated by a 
load test in accordance with Section 1810.3.3.1.2. 
Frictional resistance and bearing resistance shall not 
be assumed to act simultaneously unless determined 
by a geotechnical investigation in accordance with 
Section 1803. 

1810.3.3.1.5 Uplift capacity of a single deep foun- 
dation element. Where required by the design, the 
uplift capacity of a single deep foundation element 
shall be determined by an approved method of analy- 
sis based on a minimum factor of safety of three or by 
load tests conducted in accordance with ASTM D 
3689. The maximum allowable uplift load shall not 
exceed the ultimate load capacity as determined in 
Section 1810.3.3.1.2, using the results of load tests 
conducted in accordance with ASTM D 3689, divided 
by a factor of safety of two. 

Exception: Where uplift is due to wind or seismic 
loading, the minimum factor of safety shall be two 
where capacity is determined by an analysis and 
one and one-half where capacity is determined by 
load tests. 

1810.3.3.1.6 Uplift capacity of grouped deep foun- 
dation elements. For grouped deep foundation ele- 
ments subjected to uplift, the allowable working uplift 
load for the group shall be calculated by an approved 
method of analysis where the deep foundation ele- 



ments in the group are placed at a center-to-center 
spacing of at least 2.5 times the least horizontal 
dimension of the largest single element, the allowable 
working uplift load for the group is permitted to be 
calculated as the lesser of: 

1. The proposed individual uplift working load 
times the number of elements in the group. 

2. Two-thirds of the effective weight of the group 
and the soil contained within a block defined by 
the perimeter of the group and the length of the 
element. 

1810.3.3.1.7 Load-bearing capacity. Deep founda- 
tion elements shall develop ultimate load capacities of 
at least twice the design working loads in the desig- 
nated load-bearing layers. Analysis shall show that no 
soil layer underlying the designated load-bearing lay- 
ers causes the load-bearing capacity safety factor to 
be less than two. 

1810.3.3.1.8 Bent deep foundation elements. The 
load-bearing capacity of deep foundation elements 
discovered to have a sharp or sweeping bend shall be 
determined by an approved method of analysis or by 
load testing a representative element. 

1810.3.3.1.9 Helical piles. The allowable axial 
design load, P a , of helical piles shall be determined as 
follows: 

P a =0.5P u (Equation 18-4) 

where P u is the least value of: 

1. Sum of the areas of the helical bearing plates 
times the ultimate bearing capacity of the soil or 
rock comprising the bearing stratum. 

2. Ultimate capacity determined from well-docu- 
mented correlations with installation torque. 

3. Ultimate capacity determined from load tests. 

4. Ultimate axial capacity of pile shaft. 

5. Ultimate axial capacity of pile shaft couplings. 

6. Sum of the ultimate axial capacity of helical 
bearing plates affixed to pile. 

1810.3.3.2 Allowable lateral load. Where required by 
the design, the lateral load capacity of a single deep foun- 
dation element or a group thereof shall be determined by 
an approv edmethod of analysis or by lateral load tests to 
at least twice the proposed design working load. The 
resulting allowable load shall not be more than one-half 
of the load that produces a gross lateral movement of 1 
inch (25 mm) at the lower of the top of foundation ele- 
ment and the ground surface, unless it can be shown that 
the predicted lateral movement shall cause neither harm- 
ful distortion of, nor instability in, the structure, nor 
cause any element to be loaded beyond its capacity. 

1810.3.4 Subsiding soils. Where deep foundation elements 
are installed through subsiding fills or other subsiding strata 
and derive support from underlying firmer materials, con- 
sideration shall be given to the downward frictional forces 



2009 INTERNATIONAL BUILDING CODE® 



407 



SOILS AND FOUNDATIONS 



that may be imposed on the elements by the subsiding upper 
strata. 

Where the influence of subsiding fills is considered as 
imposing loads on the element, the allowable stresses speci- 
fied in this chapter shall be permitted to be increased where 
satisfactory substantiating data are submitted. 

1810.3.5 Dimensions of deep foundation elements. The 

dimensions of deep foundation elements shall be in accor- 
dance with Sections 1810.3.5.1 through 1810.3.5.3, as 
applicable. 

1810.3.5.1 Precast. The minimum lateral dimension of 
precast concrete deep foundation elements shall be 8 
inches (203 mm). Corners of square elements shall be 
chamfered. 

1810.3.5.2 Cast-in-place or grouted-in-place. 

Cast-in-place and grouted-in-place deep foundation ele- 
ments shall satisfy the requirements of this section. 

1810.3.5.2.1 Cased. Cast-in-place deep foundation 
elements with a permanent casing shall have a nomi- 
nal outside diameter of not less than 8 inches (203 
mm). 

1810.3.5.2.2 Uncased. Cast-in-place deep founda- 
tion elements without a permanent casing shall have a 
diameter of not less than 12 inches (305 mm). The ele- 
ment length shall not exceed 30 times the average 
diameter. 

Exception: The length of the element is permitted 
to exceed 30 times the diameter, provided the 
design and installation of the deep foundations are 
under the direct supervision of a registered design 
professional knowledgeable in the field of soil 
mechanics and deep foundations. The registered 
design professional shall submit a report to the 
building official stating that the elements were 
installed in compliance with the approved con- 
struction documents. 

1810.3.5.2.3 Micropiles. Micropiles shall have an 
outside diameter of 12 inches (305 mm) or less. The 
minimum diameter set forth elsewhere in Section 
1810.3.5 shall not apply to micropiles. 

1810.3.5.3 Steel. Steel deep foundation elements shall 
satisfy the requirements of this section. 

1810.3.5.3.1 H-piles. Sections of H-piles shall com- 
ply with the following: 

1. The flange projections shall not exceed 14 
times the minimum thickness of metal in either 
the flange or the web and the flange widths shall 
not be less than 80 percent of the depth of the 
section. 

2. The nominal depth in the direction of the web 
shall not be less than 8 inches (203 mm). 

3. Flanges and web shall have a minimum nomi- 
nal thickness of 3/ 8 inch (9.5 mm). 

1810.3.5.3.2 Steel pipes and tubes. Steel pipes and 
tubes used as deep foundation elements shall have a 



nominal outside diameter of not less than 8 inches 
(203 mm). Where steel pipes or tubes are driven open 
ended, they shall have a minimum of 0.34 square inch 
(219 mm 2 ) of steel in cross section to resist each 1,000 
foot-pounds (1356 Nm) of pile hammer energy, or 
shall have the equivalent strength for steels having a 
yield strength greater than 35,000 psi (241 MPa) or 
the wave equation analysis shall be permitted to be 
used to assess compression stresses induced by driv- 
ing to evaluate if the pile section is appropriate for the 
selected hammer. Where a pipe or tube with wall 
thickness less than 0.179 inch (4.6 mm) is driven open 
ended, a suitable cutting shoe shall be provided. Con- 
crete-filled steel pipes or tubes in structures assigned 
to Seismic Design CategoryC, D, E or F shall have a 
wall thickness of not less than 3/ 16 inch (5 mm). The 
pipe or tube casing for socketed drilled shafts shall 
have a nominal outside diameter of not less than 18 
inches (457 mm), a wall thickness of not less than 3/ 8 
inch (9.5 mm) and a suitable steel driving shoe welded 
to the bottom; the diameter of the rock socket shall be 
approximately equal to the inside diameter of the cas- 
ing. 

Exceptions: 

1. There is no minimum diameter for steel 
pipes or tubes used in micropiles. 

2. For mandrel-driven pipes or tubes, the mini- 
mum wall thickness shall be 1/ 10 inch (2.5 
mm). 

1810.3.5.3.3 Helical piles. Dimensions of the central 
shaft and the number, size and thickness of helical 
bearing plates shall be sufficient to support the design 
loads. 

1810.3.6 Splices. Splices shall be constructed so as to pro- 
vide and maintain true alignment and position of the compo- 
nent parts of the deep foundation element during installation 
and subsequent thereto and shall be designed to resist the 
axial and shear forces and moments occurring at the loca- 
tion of the splice during driving and for design load combi- 
nations. Where deep foundation elements of the same type 
are being spliced, splices shall develop not less than 50 per- 
cent of the bending strength of the weaker section. Where 
deep foundation elements of different materials or different 
types are being spliced, splices shall develop the full com- 
pressive strength and not less than 50 percent of the tension 
and bending strength of the weaker section. Where struc- 
tural steel cores are to be spliced, the ends shall be milled or 
ground to provide full contact and shall be full-depth 
welded. 

Splices occurring in the upper 10 feet (3048 mm) of the 
embedded portion of an element shall be designed to resist 
at allowable stresses the moment and shear that would result 
from an assumed eccentricity of the axial load of 3 inches 
(76 mm), or the element shall be braced in accordance with 
Section 1810.2.2 to other deep foundation elements that do 
not have splices in the upper 10 feet (3048 mm) of 
embedment. 



408 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



1810.3.6.1 Seismic Design Categories C through F. 
For structures assigned to Seismic Design CategoryC, D, 
E or F splices of deep foundation elements shall develop 
the lesser of the following: 

1. The full strength of the deep foundation element; 
and 

2. The axial and shear forces and moments from the 
load combinations with overstrength factor in Sec- 
tion 12.4.3.2 of ASCE 7. 

1810.3.7 Top of element detailing at cutoffs. Where a 
minimum length for reinforcement or the extent of closely 
spaced confinement reinforcement is specified at the top of 
a deep foundation element, provisions shall be made so that 
those specified lengths or extents are maintained after cut- 
off. 

1810.3.8 Precast concrete piles. Precast concrete piles 
shall be designed and detailed in accordance with Sections 
1810.3.8.1 through 1810.3.8.3. 

1810.3.8.1 Reinforcement. Longitudinal steel shall be 
arranged in a symmetrical pattern and be laterally tied 
with steel ties or wire spiral spaced center to center as fol- 
lows: 

1. At not more than 1 inch (25 mm) for the first five 
ties or spirals at each end; then 

2. At not more than 4 inches (102 mm), for the 
remainder of the first 2 feet (610 mm) from each 
end; and then 

3. At not more than 6 inches (152 mm) elsewhere. 
The size of ties and spirals shall be as follows: 

1. For piles having a least horizontal dimension of 16 
inches (406 mm) or less, wire shall not be smaller 
than 0.22 inch (5.6 mm) (No. 5 gage). 

2. For piles having a least horizontal dimension of 
more than 16 inches (406 mm) and less than 20 
inches (508 mm), wire shall not be smaller than 
0.238 inch (6 mm) (No. 4 gage). 

3. For piles having a least horizontal dimension of 20 
inches (508 mm) and larger, wire shall not be 
smaller than i/ 4 inch (6.4 mm) round or 0.259 inch 
(6.6 mm) (No. 3 gage). 

1810.3.8.2 Precast nonprestressed piles. Precast 
nonprestressed concrete piles shall comply with the 
requirements of Sections 1810.3.8.2.1 through 
1810.3.8.2.3. 

1810.3.8.2.1 Minimum reinforcement. Longitudi- 
nal reinforcement shall consist of at least four bars 
with a minimum longitudinal reinforcement ratio of 
0.008. 

1810.3.8.2.2 Seismic reinforcement in Seismic 
Design Categories C through F. For structures 
assigned to Seismic Design CategoryC, D, E or F in 
accordance with Section 1613, precast nonpre- 
stressed piles shall be reinforced as specified in this 



section. The minimum longitudinal reinforcement 
ratio shall be 0.01 throughout the length. Transverse 
reinforcement shall consist of closed ties or spirals 
with a minimum 3/ 8 inch (9.5 mm) diameter. Spacing 
of transverse reinforcement shall not exceed the 
smaller of eight times the diameter of the smallest lon- 
gitudinal bar or 6 inches (152 mm) within a distance 
of three times the least pile dimension from the bot- 
tom of the pile cap. Spacing of transverse reinforce- 
ment shall not exceed 6 inches (152 mm) throughout 
the remainder of the pile. 

1810.3.8.2.3 Additional seismic reinforcement in 
Seismic Design Categories D through F. For struc- 
tures assigned to Seismic Design Category D, E or F 
in accordance with Section 1613, transverse rein- 
forcement shall be in accordance with Section 
1810.3.9.4.2. 

1810.3.8.3 Precast prestressed piles. Precast pre- 
stressed concrete piles shall comply with the require- 
ments of Sections 1810.3.8.3.1 through 1810.3.8.3.3. 

1810.3.8.3.1 Effective prestress. The effective pre- 
stress in the pile shall not be less than 400 psi (2.76 
MPa) for piles up to 30 feet (9144 mm) in length, 550 
psi (3.79 MPa) for piles up to 50 feet (15 240 mm) in 
length and 700 psi (4.83 MPa) for piles greater than 
50 feet (15 240 mm) in length. 

Effective prestress shall be based on an assumed 
loss of 30,000 psi (207 MPa) in the prestressing steel. 
The tensile stress in the prestressing steel shall not 
exceed the values specified in ACI 318. 

1810.3.8.3.2 Seismic reinforcement in Seismic 
Design Category C. For structures assigned to Seis- 
mic Design Category C in accordance with Section 
1613, precast prestressed piles shall have transverse 
reinforcement in accordance with this section. The 
volumetric ratio of spiral reinforcement shall not be 
less than the amount required by the following for- 
mula for the upper 20 feet (6096 mm) of the pile. 



p,=0.12/V& 

where: 

/'c 



(Equation 18-5) 



fyh 



Ps 



= Specified compressive strength of concrete, 
psi (MPa). 

= Yield strength of spiral reinforcement 
< 85,000 psi (586 MPa). 

= Spiral reinforcement index (vol. spiral/vol. 
core). 

At least one-half the volumetric ratio required by 
Equation 18-5 shall be provided below the upper 20 
feet (6096 mm) of the pile. 

1810.3.8.3.3 Seismic reinforcement in Seismic 
Design Categories D through F. For structures 
assigned to Seismic Design Category D, E or F in 
accordance with Section 1613, precast prestressed 



2009 INTERNATIONAL BUILDING CODE® 



409 



SOILS AND FOUNDATIONS 



piles shall have transverse reinforcement in accor- 
dance with the following: 

1. Requirements in ACI 318, Chapter 21, need not 
apply, unless specifically referenced. 

2. Where the total pile length in the soil is 35 feet 
(10 668 mm) or less, the lateral transverse rein- 
forcement in the ductile region shall occur 
through the length of the pile. Where the pile 
length exceeds 35 feet (10 668 mm), the ductile 
pile region shall be taken as the greater of 35 
feet (10 668 mm) or the distance from the 
underside of the pile cap to the point of zero cur- 
vature plus three times the least pile dimension. 

3. In the ductile region, the center-to-center spac- 
ing of the spirals or hoop reinforcement shall 
not exceed one-fifth of the least pile dimension, 
six times the diameter of the longitudinal strand 
or 8 inches (203 mm), whichever is smallest. 

4. Circular spiral reinforcement shall be spliced 
by lapping one full turn and bending the end of 
each spiral to a 90-degree hook or by use of a 
mechanical or welded splice complying with 
Section 12.14.3 of ACI 318. 

5. Where the transverse reinforcement consists of 
circular spirals, the volumetric ratio of spiral 
transverse reinforcement in the ductile region 
shall comply with the following: 

p s =0.25 (feig(A g IAeh- 1.0) 
[0.5 + 1.4PI(f*A g)] 



(Equation 18-6) 



but not less than: 



p s =0.12(f'Jf yh ) [0.5 + L4PI(fsA d 



>0.12 f\,f yh 



and need not exceed: 



ps= 0.021 



(Equation 18-7) 



(Equation 18-8) 



where: 

A g =Pile cross-sectional area, square inches 
(mm 2 ) . 

Ag/j = Core area defined by spiral outside diam- 
eter, square inches (mm 2 ). 

f'e = Specified compressive strength of con- 
crete, psi (MPa) 

f yh = Yield strength of spiral reinforcement 
< 85,000 psi (586 MPa). 

P = Axial load on pile, pounds (kN) , as deter- 
mined from Equations 16-5 and 16-7. 

Ps= Volumetric ratio (vol. spirall vol. core). 



This required amount of spiral reinforcement 
is permitted to be obtained by providing an 
inner and outer spiral. 

Where transverse reinforcement consists of 
rectangular hoops and cross ties, the total 
cross-sectional area of lateral transverse rein- 
forcement in the ductile region with spacing, 5, 
and perpendicular dimension, he' shall conform 
to: 



Ash =035he(felfJ(A g IA eh - 
[0.5 + 1.4PI(fcA g)] 



1.0) 



(Equation 18-9) 

but not less than: 

Ash = 0.125 /ze (f'JQ [0.5 + L4PI(f,A g)] 



(Equation 18-10) 



where: 



*yh 

he 



= < 70,000 psi (483 MPa). 

= Cross-sectional dimension of pile core 
measured center to center of hoop rein- 
forcement, inch (mm). 

5 = Spacing of transverse reinforcement 
measured along length of pile, inch 
(mm). 

Ash = Cross-sectional area of tranverse rein- 
forcement, square inches (mm 2). 

f'e = Specified compressive strength of con- 
crete, psi (MPa). 

The hoops and cross ties shall be equivalent to 
deformed bars not less than No. 3 in size. Rectangular 
hoop ends shall terminate at a corner with seismic 
hooks. 

Outside of the length of the pile requiring trans- 
verse confinement reinforcing, the spiral or hoop 
reinforcing with a volumetric ratio not less than 
one-half of that required for transverse confinement 
reinforcing shall be provided. 

1810.3.9 Cast-in-place deep foundations. Cast-in-place 
deep foundation elements shall be designed and detailed in 
accordance with Sections 1810.3.9.1 through 1810.3.9.6. 

1810.3.9.1 Design cracking moment. The design 
cracking moment (^M) for a cast-in-place deep founda- 
tion element not enclosed by a structural steel pipe or 
tube shall be determined using the following equation: 



Wn =?>^m 



(Equation 18-11) 



where: 

f'e = Specified compressive strength of concrete or 
grout, psi (MPa) 

Sm = Elastic section modulus, neglecting reinforce- 
ment and casing, cubic inches (mm 3 ) 



410 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



1810.3.9.2 Required reinforcement. Where subject to 
uplift or where the required moment strength determined 
using the load combinations of Section 1605.2 exceeds 
the design cracking moment determined in accordance 
with Section 1810.3.9.1, cast-in-place deep foundations 
not enclosed by a structural steel pipe or tube shall be 
reinforced. 

1810.3.9.3 Placement of reinforcement. Reinforce- 
ment where required shall be assembled and tied 
together and shall be placed in the deep foundation ele- 
ment as a unit before the reinforced portion of the ele- 
ment is filled with concrete. 

Exceptions: 

1. Steel dowels embedded 5 feet (1524 mm) or 
less shall be permitted to be placed after con- 
creting' while the concrete is still in a semifluid 
state. 

2. For deep foundation elements installed with a 
hollow- stem auger, tied reinforcement shall be 
placed after elements are concreted, while the 
concrete is still in a semifluid state. Longitudi- 
nal reinforcement without lateral ties shall be 
placed either through the hollow stem of the 
auger prior to concreting or after concreting, 
while the concrete is still in a semifluid state. 

3. For Group R-3 and U occupancies not exceed- 
ing two stories of light-frame construction, 
reinforcement is permitted to be placed after 
concreting, while the concrete is still in a semi- 
fluid state, and the concrete cover requirement 
is permitted to be reduced to 2 inches (51 mm), 
provided the construction method can be dem- 
onstrated to the satisfaction of the building offi- 
cial. 

1810.3.9.4 Seismic reinforcement. Where a structure is 
assigned to Seismic Design Category C, reinforcement 
shall be provided in accordance with Section 
1810.3.9.4.1. Where a structure is assigned to Seismic 
Design Category D, E or F, reinforcement shall be pro- 
vided in accordance with Section 1810.3.9.4.2. 

Exceptions: 

1. Isolated deep foundation elements supporting 
posts of Group R-3 and U occupancies not 
exceeding two stories of light-frame construc- 
tion shall be permitted to be reinforced as 
required by rational analysis but with not less 
than one No. 4 bar, without ties or spirals, 
where detailed so the element is not subject to 
lateral loads and the soil provides adequate lat- 
eral support in accordance with Section 
1810.2.1. 

2. Isolated deep foundation elements supporting 
posts and bracing from decks and patios appur- 
tenant to Group R-3 and U occupancies not 
exceeding two stories of light-frame construc- 



tion shall be permitted to be reinforced as 
required by rational analysis but with not less 
than one No. 4 bar, without ties or spirals, 
where the lateral load, E, to the top of the ele- 
ment does not exceed 200 pounds (890 N) and 
the soil provides adequate lateral support in 
accordance with Section 1810.2.1. 

3. Deep foundation elements supporting the con- 
crete foundation wall of Group R-3 and U occu- 
pancies not exceeding two stories of 
light-frame construction shall be permitted to 
be reinforced as required by rational analysis 
but with not less than two No. 4 bars, without 
ties or spirals, where the design cracking 
moment determined in accordance with Section 
1810.3.9.1 exceeds the required moment 
strength determined using the load combina- 
tions with overstrength factor in Section 
12.4.3.2 of ASCE 7 and the soil provides ade- 
quate lateral support in accordance with Sec- 
tion 1810.2.1. 

4. Closed ties or spirals where required by Section 
1810.3.9.4.2 shall be permitted to be limited to 
the top 3 feet (914 mm) of deep foundation ele- 
ments 10 feet (3048 mm) or less in depth sup- 
porting Group R-3 and U occupancies of 
Seismic Design CategoryD, not exceeding two 
stories of light-frame construction. 

1810.3.9.4.1 Seismic reinforcement in Seismic 
Design Category C. For structures assigned to Seis- 
mic Design Category C in accordance with Section 
1613, cast-in-place deep foundation elements shall be 
reinforced as specified in this section. Reinforcement 
shall be provided where required by analysis. 

A minimum of four longitudinal bars, with a mini- 
mum longitudinal reinforcement ratio of 0.0025, shall 
be provided for throughout the minimum reinforced 
length of the element as defined below starting at the 
top of the element. The minimum reinforced length of 
the element shall be taken as the greatest of the fol- 
lowing: 

1. One-third of the element length; 

2. A distance of 10 feet (3048 mm); 

3. Three times the least element dimension; and 

4. The distance from the top of the element to the 
point where the design cracking moment deter- 
mined in accordance with Section 1810.3.9.1 
exceeds the required moment strength deter- 
mined using the load combinations of Section 
1605.2. 

Transverse reinforcement shall consist of closed 
ties or spirals with a minimum 3/ 8 inch (9.5 mm) diam- 
eter. Spacing of transverse reinforcement shall not 
exceed the smaller of6 inches (152 mm) or 8-longitu- 
dinal-bar diameters, within a distance of three times 



2009 INTERNATIONAL BUILDING CODE® 



411 



SOILS AND FOUNDATIONS 



the least element dimension from the bottom of the 
pile cap. Spacing of transverse reinforcement shall 
not exceed 16 longitudinal bar diameters throughout 
the remainder of the reinforced length. 

Exceptions: 

1. The requirements of this section shall not 
apply to concrete cast in structural steel 
pipes or tubes. 

2. A spiral-welded metal casing of a thickness 
not less than manufacturer's standard gage 
No. 14 gage (0.068 inch) is permitted to pro- 
vide concrete confinement in lieu of the 
closed ties or spirals. Where used as such, 
the metal casing shall be protected against 
possible deleterious action due to soil con- 
stituents, changing water levels or other fac- 
tors indicated by boring records of site 
conditions. 

1810.3.9.4.2 Seismic reinforcement in Seismic 
Design Categories D through F. For structures 
assigned to Seismic Design Category D, E or F in 
accordance with Section 1613, cast-in-place deep 
foundation elements shall be reinforced as specified 
in this section. Reinforcement shall be provided 
where required by analysis. 

A minimum of four longitudinal bars, with a mini- 
mum longitudinal reinforcement ratio of 0.005, shall 
be provided throughout the minimum reinforced 
length of the element as defined below starting at the 
top of the element. The minimum reinforced length of 
the element shall be taken as the greatest of the fol- 
lowing: 

1. One-half of the element length; 

2. A distance of 10 feet (3048 mm); 

3. Three times the least element dimension; and 

4. The distance from the top of the element to the 
point where the design cracking moment deter- 
mined in accordance with Section 1810.3.9.1 
exceeds the required moment strength deter- 
mined using the load combinations of Section 
1605.2. 

Transverse reinforcement shall consist of closed 
ties or spirals no smaller than No. 3 bars for elements 
with a least dimension up to 20 inches (508 mm), and 
No. 4 bars for larger elements. Throughout the 
remainder of the reinforced length outside the regions 
with transverse confinement reinforcement, as speci- 
fied in Section 1810.3.9.4.2.1 or 1810.3.9.4.2.2, the 
spacing of transverse reinforcement shall not exceed 
the least of the following: 

1. 12 longitudinal bar diameters; 

2. One-half the least dimension of the element; 
and 



3. 12 inches (305 mm). 
Exceptions: 

1. The requirements of this section shall not 
apply to concrete cast in structural steel 
pipes or tubes. 

2. A spiral-welded metal casing of a thickness 
not less than manufacturer's standard gage 
No. 14 gage (0.068 inch) is permitted to pro- 
vide concrete confinement in lieu of the 
closed ties or spirals. Where used as such, 
the metal casing shall be protected against 
possible deleterious action due to soil con- 
stituents, changing water levels or other fac- 
tors indicated by boring records of site 
conditions. 

1810.3.9.4.2.1 Site Classes A through D. For Site 
Class A, B, C or D sites, transverse confinement 
reinforcement shall be provided in the element in 
accordance with Sections 21.6.4.2, 21.6.4.3 and 
21.6.4.4 of ACI 318 within three times the least 
element dimension of the bottom of the pile cap. A 
transverse spiral reinforcement ratio of not less 
than one-half of that required in Section 
21.6.4.4(a) of ACI 318 shall be permitted. 

1810.3.9.4.2.2 Site Classes E and F. For Site 
Class E or F sites, transverse confinement rein- 
forcement shall be provided in the element in 
accordance with Sections 21.6.4.2, 21.6.4.3 and 
21.6.4.4 of ACI 318 within seven times the least 
element dimension of the pile cap and within seven 
times the least element dimension of the interfaces 
of strata that are hard or stiff and strata that are 
liquefiable or are composed of soft-to medium- 
stiff clay. 

1810.3.9.5 Belled drilled shafts. Where drilled shafts 
are belled at the bottom, the edge thickness of the bell 
shall not be less than that required for the edge of foot- 
ings. Where the sides of the bell slope at an angle less 
than 60 degrees (1 rad) from the horizontal, the effects of 
vertical shear shall be considered. 

1810.3.9.6 Socketed drilled shafts. Socketed drilled 
shafts shall have a permanent pipe or tube casing that 
extends down to bedrock and an uncased socket drilled 
into the bedrock, both filled with concrete. Socketed 
drilled shafts shall have reinforcement or a structural 
steel core for the length as indicated by an approved 
method of analysis. 

The depth of the rock socket shall be sufficient to 
develop the full load-bearing capacity of the element 
with a minimum safety factor of two, but the depth shall 
not be less than the outside diameter of the pipe or tube 
casing. The design of the rock socket is permitted to be 
predicated on the sum of the allowable load-bearing 



412 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



pressure on the bottom of the socket plus bond along the 
sides of the socket. 

Where a structural steel core is used, the gross 
cross-sectional area of the core shall not exceed 25 per- 
cent of the gross area of the drilled shaft. 

1810.3.10 Micropiles. Micropiles shall be designed and 
detailed in accordance with Sections 1810.3.10.1 through 
1810.3.10.4. 

1810.3.10.1 Construction. Micropiles shall develop 
their load-carrying capacity by means of a bond zone in 
soil, bedrock or a combination of soil and bedrock. 
Micropiles shall be grouted and have either a steel pipe or 
tube or steel reinforcement at every section along the 
length. It shall be permitted to transition from deformed 
reinforcing bars to steel pipe or tube reinforcement by 
extending the bars into the pipe or tube section by at least 
their development length in tension in accordance with 
AC1318. 

1810.3.10.2 Materials. Reinforcement shall consist of 
deformed reinforcing bars in accordance with ASTM A 
615 Grade 60 or 75 or ASTM A 722 Grade 150. 

The steel pipe or tube shall have a minimum wall 
thickness of 3 / 16 inch (4.8 mm). Splices shall comply with 
Section 1810.3.6. The steel pipe or tube shall have a min- 
imum yield strength of 45,000 psi (310 MPa) and a mini- 
mum elongation of 15 percent as shown by mill 
certifications or two coupon test samples per 40,000 
pounds (18 160 kg) of pipe or tube. 

1810.3.10.3 Reinforcement. For micropiles or portions 
thereof grouted inside a temporary or permanent casing 
or inside a hole drilled into bedrock or a hole drilled with 
grout, the steel pipe or tube or steel reinforcement shall 
be designed to carry at least 40 percent of the design 
compression load. Micropiles or portions thereof 
grouted in an open hole in soil without temporary or per- 
manent casing and without suitable means of verifying 
the hole diameter during grouting shall be designed to 
carry the entire compression load in the reinforcing steel. 
Where a steel pipe or tube is used for reinforcement, the 
portion of the grout enclosed within the pipe is permitted 
to be included in the determination of the allowable 
stress in the grout. 

1810.3.10.4 Seismic reinforcement. For structures 
assigned to Seismic Design Category C, a permanent 
steel casing shall be provided from the top of the 
micropile down to the point of zero curvature. For struc- 
tures assigned to Seismic Design CategoryD, E or F, the 
micropile shall be considered as an alternative system in 
accordance with Section 104.11. The alternative system 
design, supporting documentation and test data shall be 
submitted to the building official for review and 
approval. 

1810.3.11 Pile caps. Pile caps shall be of reinforced con- 
crete, and shall include all elements to which vertical deep 
foundation elements are connected, including grade beams 
and mats. The soil immediately below the pile cap shall not 
be considered as carrying any vertical load. The tops of ver- 



tical deep foundation elements shall be embedded not less 
than 3 inches (76 mm) into pile caps and the caps shall 
extend at least 4 inches (102 mm) beyond the edges of the 
elements. The tops of elements shall be cut or chipped back 
to sound material before capping. 

1810.3.11.1 Seismic Design Categories C through F. 
For structures assigned to Seismic Design Category C, D, 
E or F in accordance with Section 1613, concrete deep 
foundation elements shall be connected to the pile cap by 
embedding the element reinforcement or field-placed 
dowels anchored in the element into the pile cap for a dis- 
tance equal to their development length in accordance 
with ACI 318. It shall be permitted to connect precast 
prestressed piles to the pile cap by developing the ele- 
ment prestressing strands into the pile cap provided the 
connection is ductile. For deformed bars, the develop- 
ment length is the full development length for compres- 
sion, or tension in the case of uplift, without reduction for 
excess reinforcement in accordance with Section 12.2.5 
of ACI 318. Alternative measures for laterally confining 
concrete and maintaining toughness and ductile-like 
behavior at the top of the element shall be permitted pro- 
vided the design is such that any hinging occurs in the 
confined region. 

The minimum transverse steel ratio for confinement 
shall not be less than one-half of that required for col- 
umns. 

For resistance to uplift forces, anchorage of steel 
pipes, tubes or H-piles to the pile cap shall be made by 
means other than concrete bond to the bare steel section. 
Concrete- filled steel pipes or tubes shall have reinforce- 
ment of not less than 0.01 times the cross-sectional area 
of the concrete fill developed into the cap and extending 
into the fill a length equal to two times the required cap 
embedment, but not less than the development length in 
tension of the reinforcement. 

1810.3.11.2 Seismic Design Categories D through F. 
For structures assigned to Seismic Design CategoryD, E 
or F in accordance with Section 1613, deep foundation 
element resistance to uplift forces or rotational restraint 
shall be provided by anchorage into the pile cap, 
designed considering the combined effect of axial forces 
due to uplift and bending moments due to fixity to the 
pile cap. Anchorage shall develop a minimum of 25 per- 
cent of the strength of the element in tension. Anchorage 
into the pile cap shall be capable of developing the fol- 
lowing: 

1. In the case of uplift, the least of the following: 
nominal tensile strength of the longitudinal rein- 
forcement in a concrete element; the nominal ten- 
sile strength of a steel element; the frictional force 
developed between the element and the soil multi- 
plied by 1.3; and the axial tension force resulting 
from the load combinations with overstrength fac- 
tor in Section 12.4.3.2 of ASCE 7. 

2. In the case of rotational restraint, the lesser of the 
following: the axial force, shear forces and bend- 
ing moments resulting from the load combinations 



2009 INTERNATIONAL BUILDING CODE® 



413 



SOILS AND FOUNDATIONS 



with overstrength factor in Section 12.4.3.2 of 
ASCE 7 or development of the full axial, bending 
and shear nominal strength of the element. 

Where the vertical lateral-foree-resisting elements are 
columns, the pile cap flexural strengths shall exceed the 
column flexural strength. The connection between batter 
piles and pile caps shall be designed to resist the nominal 
strength of the pile acting as a short column. Batter piles 
and their connection shall be capable of resisting forces 
and moments from the load combinations with 
overstrength factor in Section 12.4.3.2 of ASCE 7. 

1810.3.12 Grade beams. For structures assigned to Seismic 
Design CategoryD, E or Fin accordance with Section 1613, 
grade beams shall comply with the provisions in Section 
21.12.3 of ACI 318 for grade beams, except where they have 
the capacity to resist the forces from the load combinations 
with overstrength factor in Section 12.4.3.2 of ASCE 7. 

1810.3.13 Seismic ties. For structures assigned to Seismic 
Design Category C, D, E or F in accordance with Section 
1613, individual deep foundations shall be interconnected 
by ties. Unless it can be demonstrated that equivalent 
restraint is provided by reinforced concrete beams within 
slabs on grade or reinforced concrete slabs on grade or con- 
finement by competent rock, hard cohesive soils or very 
dense granular soils, ties shall be capable of carrying, in ten- 
sion or compression, a force equal to the lesser of the prod- 
uct of the larger pile cap or column design gravity load times 
the seismic coefficient, SDS' divided by 10, and 25 percent of 
the smaller pile or column design gravity load. 

Exception: In Group R-3 and U occupancies of 
light-frame construction, deep foundation elements sup- 
porting foundation walls, isolated interior posts detailed 
so the element is not subj ect to lateral loads or exterior 
decks and patios are not subject to interconnection where 
the soils are of adequate stiffness, subject to the approval 
of the building official. 

1810.4 Installation. Deep foundations shall be installed in 
accordance with Section 1810.4. Where a single deep founda- 
tion element comprises two or more sections of different mate- 
rials or different types spliced together, each section shall 
satisfy the applicable conditions of installation. 

1810.4.1 Structural integrity. Deep foundation elements 
shall be installed in such a manner and sequence as to pre- 
vent distortion or damage that may adversely affect the 
structural integrity of adjacent structures or of foundation 
elements being installed or already in place and as to avoid 
compacting the surrounding soil to the extent that other 
foundation elements cannot be installed properly. 

1810.4.1.1 Compressive strength of precast concrete 
piles. A precast concrete pile shall not be driven before the 
concrete has attained a compressive strength of at least 75 
percent of the specified compressive strength (f ), but not 
less than the strength sufficient to withstand handling and 
driving forces. 

1810.4.1.2 Casing. Where cast-in-place deep founda- 
tion elements are formed through unstable soils and con- 
crete is placed in an open-drilled hole, a casing shall be 



inserted in the hole prior to placing the concrete. Where 
the casing is withdrawn during concreting, the level of 
concrete shall be maintained above the bottom of the cas- 
ing at a sufficient height to offset any hydrostatic or lat- 
eral soil pressure. Driven casings shall be mandrel driven 
their full length in contact with the surrounding soil. 

1810.4.1.3 Driving near uncased concrete. Deep foun- 
dation elements shall not be driven within six element 
diameters center to center in granular soils or within 
one-half the element length in cohesive soils of an 
uncased element filled with concrete less than 48 hours 
old unless approvedby the bUilding official. If the con- 
crete surface in any completed element rises or drops, the 
element shall be replaced. Driven uncased deep founda- 
tion elements shall not be installed in soils that could 
cause heave. 

1810.4.1.4 Driving near cased concrete. Deep founda- 
tion elements shall not be driven within four and one- half 
average diameters of a cased element filled with concrete 
less than 24 hours old unless approvedby the bUilding 
official. Concrete shall not be placed in casings within 
heave range of driving. 

1810.4.1.5 Defective timber piles. Any substantial sud- 
den increase in rate of penetration of a timber pile shall 
be investigated for possible damage. If the sudden 
increase in rate of penetration cannot be correlated to soil 
strata, the pile shall be removed for inspection or 
rejected. 

1810.4.2 Identification. Deep foundation materials shall be 
identified for conformity to the specified grade with this 
identity maintained continuously from the point of manu- 
facture to the point of installation or shall be tested by an 
approved agency to determine conformity to the specified 
grade. The approved agency shall furnish an affidavit of 
compliance to the building official. 

1810.4.3 Location plan. A plan showing the location and 
designation of deep foundation elements by an identifica- 
tion system shall be filed with the bUilding official prior to 
installation of such elements. Detailed records for elements 
shall bear an identification corresponding to that shown on 
the plan. 

1810.4.4 Preexcavation. The use of jetting, augering or 
other methods of preexcavation shall be subject to the 
approval of the building official. Where permitted, 
preexcavation shall be carried out in the same manner as 
used for deep foundation elements subject to load tests and 
in such a manner that will not impair the carrying capacity of 
the elements already in place or damage adjacent structures. 
Element tips shall be driven below the preexcavated depth 
until the required resistance or penetration is obtained. 

1810.4.5 Vibratory driving. Vibratory drivers shall only be 
used to install deep foundation elements where the element 
load capacity is verified by load tests in accordance with 
Section 1810.3.3.1.2. The installation of production ele- 
ments shall be controlled according to power consumption, 
rate of penetration or other approve d means that ensure ele- 
ment capacities equal or exceed those of the test elements. 



414 



2009 INTERNATIONAL BUILDING CODE® 



SOILS AND FOUNDATIONS 



1810.4.6 Heaved elements. Deep foundation elements that 
have heaved during the driving of adjacent elements shall be 
redriven as necessary to develop the required capacity and 
penetration, or the capacity of the element shall be verified 
by load tests in accordance with Section 1810.3.3.1.2. 

1810.4.7 Enlarged base cast-in-place elements. Enlarged 
bases for cast-in-place deep foundation elements formed by 
compacting concrete or by driving a precast base shall be 
formed in or driven into granular soils. Such elements shall 
be constructed in the same manner as successful prototype 
test elements driven for the project. Shafts extending 
through peat or other organic soil shall be encased in a per- 
manent steel casing. Where a cased shaft is used, the shaft 
shall be adequately reinforced to resist column action or the 
annular space around the shaft shall be filled sufficiently to 
reestablish lateral support by the soil. Where heave occurs, 
the element shall be replaced unless it is demonstrated that 
the element is undamaged and capable of carrying twice its 
design load. 

1810.4.8 Hollow-stem angered, cast-in-place elements. 

Where concrete or grout is placed by pumping through a 
hollow- stem auger, the auger shall be permitted to rotate in a 
clockwise direction during withdrawal. As the auger is 
withdrawn at a steady rate or in increments not to exceed 1 
foot (305 mm), concreting or grouting pumping pressures 
shall be measured and maintained high enough at all times 
to offset hydrostatic and lateral earth pressures. Concrete or 
grout volumes shall be measured to ensure that the volume 
of concrete or grout placed in each element is equal to or 
greater than the theoretical volume of the hole created by the 
auger. Where the installation process of any element is inter- 
rupted or a loss of concreting or grouting pressure occurs, 
the element shall be redrilled to 5 feet (1524 mm) below the 
elevation of the tip of the auger when the installation was 
interrupted or concrete or grout pressure was lost and 
reformed. Augered cast-in-place elements shall not be 
installed within six diameters center to center of an element 
filled with concrete or grout less than 12 hours old, unless 
approved by the bUilding official. If the concrete or grout 
level in any completed element drops due to installation of 
an adjacent element, the element shall be replaced. 

1810.4.9 Socketed drilled shafts. The rock socket and pipe 
or tube casing of socketed drilled shafts shall be thoroughly 
cleaned of foreign materials before filling with concrete. 
Steel cores shall be bedded in cement grout at the base of the 
rock socket. 

1810.4.10 Micropiles. Micropile deep foundation elements 
shall be permitted to be formed in holes advanced by rotary 
or percussive drilling methods, with or without casing. The 
elements shall be grouted with a fluid cement grout. The 
grout shall be pumped through a tremie pipe extending to 
the bottom of the element until grout of suitable quality 
returns at the top of the element. The following require- 
ments apply to specific installation methods: 

1. For micropiles grouted inside a temporary casing, the 
reinforcing bars shall be inserted prior to withdrawal 
of the casing. The casing shall be withdrawn in a con- 
trolled manner with the grout level maintained at the 



top of the element to ensure that the grout completely 
fills the drill hole. During withdrawal of the casing, 
the grout level inside the casing shall be monitored to 
verify that the flow of grout inside the casing is not 
obstructed. 

2. For a micropile or portion thereof grouted in an open 
drill hole in soil without temporary casing, the mini- 
mum design diameter of the drill hole shall be verified 
by a suitable device during grouting. 

3. For micropiles designed for end bearing, a suitable 
means shall be employed to verify that the bearing 
surface is properly cleaned prior to grouting. 

4. Subsequent micropiles shall not be drilled near ele- 
ments that have been grouted until the grout has had 
sufficient time to harden. 

5. Micropiles shall be grouted as soon as possible after 
drilling is completed. 

6. For micropiles designed with a full-length casing, the 
casing shall be pulled back to the top of the bond zone 
and reinserted or some other suitable means 
employed to assure grout coverage outside the casing. 

1810.4.11 Helical piles. Helical piles shall be installed to 
specified embedment depth and torsional resistance criteria 
as determined by a registered design professional. The 
torque applied during installation shall not exceed the maxi- 
mum allowable installation torque of the helical pile. 

1810.4.12 Special inspection. Special inspections in accor- 
dance with Sections 1704.8 and 1704.9 shall be provided 
for driven and cast-in-place deep foundation elements, 
respectively. Special inspections in accordance with Section 
1704.10 shall be provided for helical piles. 



2009 INTERNATIONAL BUILDING CODE® 



415 



416 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 19 
CONCRETE 

Italics are used for text within Sections 1903 through 1908 of this code to indicate provisions that differ from ACI318. 



SECTION 1901 
GENERAL 

1901.1 Scope. The provisions of this chapter shall govern the 
materials, quality control, design and construction of concrete 
used in structures. 

1901.2 Plain and reinforced concrete. Structural concrete 
shall be designed and constructed in accordance with the 
requirements of this chapter and ACI 318 as amended in Sec- 
tion 1908 of this code. Except for the provisions of Sections 
1904 and 1910, the design and construction of slabs on grade 
shall not be governed by this chapter unless they transmit verti- 
cal loads or lateral forces from other parts of the structure to the 
soil. 

1901.3 Source and applicability. The format and subject mat- 
ter of Sections 1902 through 1907 of this chapter are patterned 
after, and in general conformity with, the provisions for struc- 
tural concrete in ACI 318. 

1901.4 Construction documents. The construction docu- 
ments for structural concrete construction shall include: 

1. The specified compressive strength of concrete at the 
stated ages or stages of construction for which each 
concrete element is designed. 

2. The specified strength or grade of reinforcement. 

3. The size and location of structural elements, reinforce- 
ment and anchors. 

4. Provision for dimensional changes resulting from 
creep, shrinkage and temperature. 

5. The magnitude and location of prestressing forces. 

6. Anchorage length of reinforcement and location and 
length of lap splices. 

7. Type and location of mechanical and welded splices of 
reinforcement. 

8. Details and location of contraction or isolation joints 
specified for plain concrete. 

9. Minimum concrete compressive strength at time of 
posttensioning. 

10. Stressing sequence for posttensioning tendons. 

11. For structures assigned to Seismic Design CategoryD, 
E or F, a statement if slab on grade is designed as a 
structural diaphragm (see Section 21.12.3.4 of ACI 
318). 

1901.5 Special inspection. The special inspection of concrete 
elements of buildings and structures and concreting operations 
shall be as required by Chapter 17. 



SECTION 1902 
DEFINITIONS 

1902.1 General. The words and terms defined in ACI 318 1 
shall, for the purposes of this chapter and as used elsewhere in 
this code for concrete construction, have the meanings shown 
in ACI 318 as modified by Section 1908.1.1. 



SECTION 1903 
SPECIFICATIONS FOR TESTS AND MATERIALS 

1903.1 General. Materials used to produce concrete, concrete 
itself and testing thereof shall comply with the applicable stan- 
dards listed in ACI 318. Where required, special inspections 
and tests shall be in accordance with Chapter 17. 

1903.2 Glass fiber reinforced concrete. Glass fiber rein- 
forced concrete (GFRC) and the materials used in such con- 
crete shall be in accordance with thePCIMNL 128 standard. 



SECTION 1904 
DURABILITY REQUIREMENTS 

1904.1 Water-cementitious materials ratio. Where maximum 
water-cementitious materials ratios are specified in ACI 318, 
they shall be calculated in accordance with ACI 318, Section 4.1. 

1904.2 Exposure categories and classes. Concrete shall be 
assigned to exposure classes in accordance with ACI 318, Sec- 
tion 4.2, based on: 

1. Exposure to freezing and thawing in a moist condition or 
deicer chemicals; 

2. Exposure to sulfates in water or soil; 

3. Exposure to water where the concrete is intended to have 
low permeability; and 

4. Exposure to chlorides from deicing chemicals, salt, 
saltwater, brackish water, seawater or spray from these 
sources, where the concrete has steel reinforcement. 

1904.3 Concrete properties. Concrete mixtures shall conform 
to the most restrictive maximum water-cementitious materials 
ratios and minimum specified concrete compressive strength 
requirements of ACI 318, Section 4.3, based on the exposure 
classes assigned in Section 1904.2. 

Exception: For occupancies and appurtenances thereto in 
Group R occupancies that are in buildings less than four 
stories above grade plane, normal-weight aggregate con- 
crete is permitted to comply with the requirements of Table 
1904.3 basedon the weathering classification (freezing and 
thawing) determined from Figure 1904.3 in lieu of the 
requirements of ACI 318, Table 4.3.1. 



2009 INTERNATIONAL BUILDING CODE® 



417 



CONCRETE 



TABLE 1904.3 
MINIMUM SPECIFIED COMPRESSIVE STRENGTH (f) 



TYPE OR LOCATION OF CONCRETE CONSTRUCTION 


MINIMUM SPECIFIED COMPRESSIVE STRENGTH (Teat 28 days, psi) 


Negligible exposure 


Moderate exposure 


Severe exposure 


Basement walls and foundations not exposed to the weather 


2,500 


2,500 


2,500 a 


Basement slabs and interior slabs on grade, except garage floor 
slabs 


2,500 


2,500 


2,500 a 


Basement walls , foundation walls, exterior walls and other 
vertical concrete surfaces exposed to the weather 


2,500 


3,000b 


3,000b 


Driveways, curbs, walks, patios, porches, carport slabs, steps and 
other flatwork exposed to the weather, and garage floor slabs 


2,500 


3,000b, d 


3,500b, d 



For SI: 1 pound per square inch = 0.00689 MPa. 

a. Concrete in these locations that can be subjected to freezing and thawing during construction shall be of air-entrained concrete in accordance with Section 
1904.2.1. 

b. Concrete shall be air entrained in accordance with Section 1904.4.1. 

c. Structural plain concrete basement walls are exempt from the requirements for exposure conditions of Section 1904.3 (see Section 1909.6.1). 

d. For garage floor slabs where a steel trowel finish is used, the total air content required by Section 1904.4. 1 is permitted to be reduced to not less than 3 percent, pro- 
vided the minimum specified compressive strength of the concrete is increased to 4,000 psi. 




NEGLIGIBLE 



FIGURE 1904.3 
WEATHERING PROBABILITY MAP FOR CONCRETE 3 , b, c 

a. Lines defining areas are approximate only. Local areas can be more or less severe than indicated by the region classification. 

b. A "severe" classification is where weather conditions encourage or require the use of deicing chemicals or where there is potential for a continuous presence of 
moisture during frequent cycles of freezing and thawing. A "moderate " classification is where weather conditions occasionally expose concrete in the presence of 
moisture to freezing and thawing, but where deicing chemicals are not generally used. A "negligible " classification is where weather conditions rarely expose con- 
crete in the presence of moisture to freezing and thawing. 

c. Alaska and Hawaii are classified as severe and negligible, respectively. 



418 



2009 INTERNATIONAL BUILDING CODE® 



CONCRETE 



1904.4 Freezing and thawing exposures. Concrete that will 
be exposed to freezing and thawing, in the presence of mois- 
ture, with or without deicing chemicals being present, shall 
comply with Sections 1904.4.1 and 1904.4.2. 

1904.4.1 Air entrainment. Concrete exposed to freezing 
and thawing while moist shall be air entrained in accordance 
with ACI 318, Section 4.4.1. 

1904.4.2 Deicing chemicals. For concrete exposed to freez- 
ing and thawing in the presence of moisture and deicing 
chemicals, the maximum weight of fly ash, other pozzolans, 
silica fume or slag that is included in the concrete shall not 
exceed the percentages of the total weight of cementitious 
materials permitted by ACI 318, Section 4.4.2. 

1904.5 Alternative cementitious materials for sulfate expo- 
sure. Alternative combinations of cementitious materials for 
use in sulfate-resistant concrete to those listed in ACI 318, 
Table 4.3.1 shall be permitted in accordance with ACI 318, 
Section 4.5.1. 



SECTION 1905 
CONCRETE QUALITY, MIXING AND PLACING 

1905.1 General. The required strength and durability of con- 
crete shall be determined by compliance with the proportion- 
ing' testing, mixing and placing provisions of Sections 
1905.1.1 through 1905.13. 

1905.1.1 Strength. Concrete shall be proportioned to pro- 
vide an average compressive strength as prescribed in Sec- 
tion 1905.3 and shall satisfy the durability criteria of 
Section 1904. Concrete shall be produced to minimize the 
frequency of strengths below i ' c as prescribed in Section 
1905.6.3. For concrete designed and constructed in accor- 
dance with this chapter, i ' c shall not be less than 2,500 psi 
(17.22 MPa). No maximum specified compressive strength 
shall apply unless restricted by a specific provision of this 
code or ACI 318. 

1905.2 Selection of concrete proportions. Concrete propor- 
tions shall be determined in accordance with the provisions of 
ACI 318, Section 5.2. 

1905.3 Proportioning on the basis of field experience 
and/or trial mixtures. Concrete proportioning determined on 
the basis of field experience and/or trial mixtures shall be done 
in accordance with ACI 318, Section 5.3. 

1905.4 Proportioning without field experience or trial mix- 
tures. Concrete proportioning determined without field expe- 
rience or trial mixtures shall be done in accordance with ACI 
318, Section 5.4. 

1905.5 Average strength reduction. As data become avail- 
able during construction, it is permissible to reduce the amount 
by which the average compressive strength (Tj is required to 
exceed the specified value of z ' c in accordance with ACI 318, 
Section 5.5. 



1905.6 Evaluation and acceptance of concrete. The criteria 
for evaluation and acceptance of concrete shall be as specified 
in Sections 1905.6.2 through 1905.6.5. 

1905 .6.1 Qualified technicians. Concrete shall be tested in 
accordance with the requirements in Sections 1905.6.2 
through 1905.6.5. Qualified field testing technicians shall 
perform tests on fresh concrete atthejob site, prepare speci- 
mens required for curing under field conditions, prepare 
specimens required for testing in the laboratory and record 
the temperature of the fresh concrete when preparing speci- 
mens for strength tests. Qualified laboratory technicians 
shall perform all required laboratory tests. 

1905.6.2 Frequency of testing. The frequency of conduct- 
ing strength tests of concrete and the minimum number of 
tests shall be as specified in ACI 318, Section 5.6.2. 

Exception: When the total volume of a given class of 
concrete is less than 50 cubic yards (38 m 3 ), strength tests 
are not required when evidence of satisfactory strength is 
submitted to and approved by the building official. 

1905.6.3 Strength test specimens. Specimens prepared for 
acceptance testing of concrete in accordance with Section 
1905.6.2 and strength test acceptance criteria shall comply 
with the provisions of ACI 318, Section 5.6.3. 

1905.6.4 Field-cured specimens. Where required by the 
building official to determine adequacy of curing and pro- 
tection of concrete in the structure, specimens shall be pre- 
pared, cured, tested and test results evaluated for acceptance 
in accordance with ACI 318, Section 5.6.4. 

1905.6.5 Low-strength test results. Where any strength 
test (see ACI 318, Section 5.6.2.4) falls below the specified 
value of/ 'c the provisions of ACI 318, Section 5.6.5, shall 
apply. 

1905.7 Preparation of equipment and place of deposit. Prior 
to concrete being placed, the space to receive the concrete and 
the equipment used to deposit it shall comply with ACI 318, 
Section 5.7. 

1905.8 Mixing. Mixing of concrete shall be performed in 
accordance with ACI 318, Section 5.8. 

1905.9 Conveying. The method and equipment for conveying 
concrete to the place of deposit shall comply with ACI 318, 
Section 5.9. 

1905.10 Depositing. The depositing of concrete shall comply 
with the provisions of ACI 318, Section 5.10. 

1905.11 Curing. The length of time, temperature and moisture 
conditions for curing of concrete shall be in accordance with 
ACI 318, Section 5.11. 

1905.12 Cold weather requirements. Concrete to be placed 
during freezing or near- freezing weather shall comply with the 
requirements of ACI 318, Section 5.12. 

1905.13 Hot weather requirements. Concrete to be placed 
during hot weather shall comply with the requirements of ACI 
318, Section 5.13. 



2009 INTERNATIONAL BUILDING CODE® 



419 



CONCRETE 



SECTION 1906 

FORMWORK, EMBEDDED PIPES AND 

CONSTRUCTION JOINTS 

1906.1 Formwork. The design, fabrication and erection of 
forms shall comply with ACI 318, Section 6.1. 

1906.2 Removal of forms, shores and reshores. The removal 
of forms and shores, including from slabs and beams (except 
where cast on the ground), and the installation of reshores shall 
comply with ACI 318, Section 6.2. 

1906.3 Conduits and pipes embedded in concrete. Conduits, 
pipes and sleeves of any material not harmful to concrete and 
within the limitations of ACI 318, Section 6.3, are permitted to 
be embedded in concrete with approval of the registered design 
professional. 

1906.4 Construction joints. Construction joints, including 
their location, shall comply with the provisions of ACI 318, 
Section 6.4. 



SECTION 1907 
DETAILS OF REINFORCEMENT 

1907.1 Hooks. Standard hooks on reinforcing bars used in 
concrete construction shall comply with ACI 318, Section 7.1. 

1907.2 Minimum bend diameters. Minimum reinforcement 
bend diameters utilized in concrete construction shall comply 
with ACI 318, Section 7.2. 

1907.3 Bending. The bending of reinforcement shall comply 
with ACI 318, Section 7.3. 

1907.4 Surface conditions of reinforcement. The surface 
conditions of reinforcement shall comply with the provisions 
of ACI 318, Section 7.4. 

1907.5 Placing reinforcement. The placement of reinforce- 
ment, including tolerances on depth and cover, shall comply 
with the provisions of ACI 318, Section 7.5. Reinforcement 
shall be accurately placed and adequately supported before 
concrete is placed. 

1907.6 Spacing limits for reinforcement. The clear distance 
between reinforcing bars, bundled bars, tendons and ducts 
shall comply with ACI 318, Section 7.6. 

1907.7 Concrete protection for reinforcement. The mini- 
mum specified concrete cover for reinforcement shall comply 
with Sections 1907.7.1 through 1907.7.8. 

1907.7.1 Cast-in-place concrete (nonprestressed). Mini- 
mum specified concrete cover shall be provided for rein- 
forcement in nonprestressed, cast-in-place concrete 
construction in accordance with ACI 318, Section 7.7.1. 

1907.7.2 Cast-in-place concrete (pre stressed). The mini- 
mum specified concrete cover for prestressed and 
nonprestressed reinforcement, ducts and end fittings in 
cast-in-place prestressed concrete shall comply with ACI 
318, Section 7.7.2. 

1907.7.3 Precast concrete (manufactured under plant 
control conditions). The minimum specified concrete 
cover for prestressed and nonprestressed reinforcement, 
ducts and end fittings in precast concrete manufactured 



under plant control conditions shall comply with ACI 318, 
Section 7.7.3. 

1907.7.4 Bundled bars. The minimum specified concrete 
cover for bundled bars shall comply with ACI 318, Section 
7.7.4. 

1907.7.5 Headed shear stud reinforcement. For headed 
shear stud reinforcement, the minimum specified concrete 
cover shall comply with ACI 318, Section 7.7.5. 

1907.7.6 Corrosive environments. In corrosive environ- 
ments or other severe exposure conditions, prestressed and 
nonprestressed reinforcement shall be provided with addi- 
tional protection in accordance with ACI 318, Section 7.7.6. 

1907.7.7 Future extensions. Exposed reinforcement, 
inserts and plates intended for bonding with future exten- 
sions shall be protected from corrosion. 

1907.7.8 Fire protection. When this code requires a thick- 
ness of cover for fire protection greater than the minimum 
concrete cover in Section 1907.7, such greater thickness 
shall be specified. 

1907.8 Special reinforcement details for columns. Offset 
bent longitudinal bars in columns and load transfer in structural 
steel cores of composite compression members shall comply 
with the provisions of ACI 318, Section 7.8. 

1907.9 Connections. Connections between concrete framing 
members shall comply with the provisions of ACI 318, Section 
7.9. 

1907.10 Lateral reinforcement for compression members. 
Lateral reinforcement for concrete compression members shall 
comply with the provisions of ACI 318, Section 7.10. 

1907.11 Lateral reinforcement for flexural members. Lat- 
eral reinforcement for compression reinforcement in concrete 
flexural members shall comply with the provisions of ACI 318, 
Section 7.11. 

1907.12 Shrinkage and temperature reinforcement. Rein- 
forcement for shrinkage and temperature stresses in concrete 
members shall comply with the provisions of ACI 318, Section 
7.12. 

1907.13 Requirements for structural integrity. The detail- 
ing of reinforcement and connections between concrete mem- 
bers shall comply with the provisions of ACI 318, Section 7. 13, 
to improve structural integrity. 



SECTION 1908 
MODIFICATIONS TO ACI31 8 

1908.1 General. The text of ACI 318 shall be modified as indi- 
cated in Sections 1908.1.1 through 1908.1.10. 4 

1908.1.1 ACI 318, Section 2.2. Modify existing definitions 
and add the following definitions to ACI 318, Section 2.2. 

DESIGN DISPLACEMENT. Total lateral displacement 
expected for the design-basis earthquake, as specified by 
Section 12.8.6 ofASCE 7. 



420 



2009 INTERNATIONAL BUILDING CODE® 



CONCRETE 



DETAILEDPLAINCONCRETESTRUCTURALWALL. 

A wall complying with the requirements of Chapter 22, 
including 22.6.1. 

ORDINARYPRECASTSTRUCTURAL WALL. A precast 
wall complying with the requirements of Chapters 1 through 
18. 

ORDINARY REINFORCED CONCRETE STRUC- 
TURAL WALL. A cast-in-place wall complying with the 
requirements of Chapters 1 through 18. 

ORDINARY STRUCTURAL PLAIN CONCRETE 
WALL. A wall complying with the requirements of Chapter 

22, excluding 22.6.7. 

SPECIAL STRUCTURAL WALL. A cast-in-place or 
precast wall complying with the requirements of 21.1.3 
through 21.1.7,21.9 and 21.10, as applicable, in addition to 
the requirements for ordinary reinforced concrete structural 
walls or ordinary precast structural walls, as applicable. 
Where ASCE 1 refers to a "special reinforced concrete 
structural wall, " it shall be deemed to mean a "special 
structural wall. " 

WALL PIER. A wall segment with a horizontal length- 
to-thickness ratio of at least 2.5, but not exceeding 6, whose 
clear height is at least two times its horizontal length. 

1908.1.2 ACI 318, Section 21.1.1. Modify ACI 318 Sec- 
tions 21.1.1.3 and 21.1.1.7 to read as follows: 

21.1.1.3 - Structures assigned to Seismic Design Cate- 
gory A shall satisfy requirements of Chapters 1 to 19 and 
22,. Chapter 21 does not apply. Structures assigned to 
Seismic Design CategoryB, C, D, E or F also shall satisfy 

21.1.1.4 through 21.1.1.8, as applicable. Except for 
structural elements of plain concrete complying with 
Section 1908.1.8 of the International Building Code, 
structural elements of plain concrete are prohibited in 
structures assigned to Seismic Design Category C, D, E 
orF 

21.1.1.7 - Structural systems designated as part of the 
seismic- force-resisting system shall be restricted to 
those permitted by ASCE 7. Except for Seismic Design 
Category A, for which Chapter 21 does not apply, the fol- 
lowing provisions shall be satisfied for each structural 
system designated as part of the seismic-foree-resisting 
system, regardless of the Seismic Design Category: 

(a) Ordinary moment frames shall satisfy 21.2. 

(b) Ordinary reinforced concrete structural walls 
and ordinary precast structural walls need not 
satisfy any provisions in Chapter 21. 

(c) Intermediate moment frames shall satisfy 21.3. 

(d) Intermediate precast structuralwalls shall satisfy 
21.4. 

(e) Special moment frames shall satisfy 21 .5 
through 21.8. 

(f) Special structural walls shall satisfy 21.9. 



(g) Special structural walls constructed using pre- I 
cast concrete shall satisfy 21.10. 

All special moment frames and special structural 
walls shall also satisfy 21.1.3 through 21.1.7. • 

1908.1.3 ACI 318, Section 21.4. Modify ACI 318, Section 
21.4, by renumbering Section 21.4.3 to become 21.4.4 and 
adding new Sections 21.4.3, 21.4.5 and 21.4.6 to read as fol- 
lows: 

21.4.3 - Connections that are designed to yield shall be 
capable of maintaining 80 percent of their design 
strength at the deformation induced by the design dis- 
placement or shall use Type 2 mechanical splices. 

21.4.4 - Elements of the connection that are not designed 
to yield shall develop at least 1.5 Sy. 

21.4.5 - Wall piers not designed as part of a moment 
frame shall have transverse reinforcement designed to 
resist the shear forces determined from 21.3.3. Spacing 
of transverse reinforcement shall not exceed 8 inches 
(203 mm). Transverse reinforcement shall be extended 
beyond the pier clear height for at least 12 inches (305 
mm). 

Exceptions: 

1. Wall piers that satisfy 21.13. 

2. Wall piers along a wall line within a story 
where other shear wall segments provide lat- 
eral support to the wall piers and such seg- 
ments have a total stiffness of at least six times 
the sum of the stiffnesses of all the wallpiers. 

21.4.6- Wall segments with a horizontallength-to -thick- 
ness ratio less than 2.5 shall be designed as columns. 

1908.1.4 ACI 318, Section 21.9. Modify ACI 318, Section 
21.9, by adding new Section 21.9.10 to read as follows: 

21.9.10 - Wallpiers and wall segments. 

21.9.10.1 - Wall piers not designed as apart of a special 
moment frame shall have transverse reinforcement 
designed to satisfy the requirements in 21.9.10.2. 

Exceptions: 

1. Wallpiers that satisfy 21.13. 

2. Wall piers along a wall line within a story 
where other shear wall segments provide lat- 
eral support to the wall piers and such seg- 
ments have a total stiffness of at least six times 
the sum of the stiffnesses of all the wallpiers. 

21.9.10.2 - Transverse reinforcement with seismic hooks 
at both ends shall be designed to resist the shear forces 
determined from 21.6.5.1. Spacing of transverse rein- 
forcement shall not exceed 6 inches (152 mm). Trans- 
verse reinforcement shall be extended beyond the pier 
clear height for at least \2inches (305 mm). 

21.9.10.3 - Wall segments with a horizontallength-to - 
thickness ratio less than 2.5 shall be designed as col- 
umns. 



2009 INTERNATIONAL BUILDING CODE® 



421 



CONCRETE 



1908.1.5 ACI 318, Section 21.10. Modify ACI 318, Section 
21.10.2, to read as follows: 

21.10.2 - Special structural walls constructed using pre- 
cast concrete shall satisfy all the requirements of 21.9 for 
cast-in-place special structural walls in addition to Sec- 
tions 21.4.2 through 21.4.4. 

1908.1.6 ACI 318, Section 21.12.1.1. Modify ACI 318, 
Section 21.12.1.1, to read as follows: 

21.12.1.1 - Foundations resisting earthquake-induced 
forces or transferring earthquake-induced forces between 
a structure and ground shall comply with the requirements 
of Section 21.12 and other applicable provisions of ACI 
318 unless modified by Chapter 18 of the International 
Building Code. 

1908.1.7 ACI 318, Section 22.6. Modify ACI 318, Section 
22.6, by adding new Section 22.6.7 to read as follows: 

22.6. 7 - Detailedplain concrete structural walls. 

22.6. 7.1 - Detailedplain concrete structural walls are 
walls conforming to the requirements of ordinary struc- 
tural plain concrete walls and 22. 6.7. 2. 

22.6.7.2 - Reinforcement shall be provided as follows: 

(a) Vertical reinforcement of at least 0.20 square 
inch (129 mm 2 ) in cross-sectional area shall be 
provided continuously from support to support at 
each corner, at each side of each opening and at 
the ends of walls. The continuous vertical bar 
required beside an opening is permitted to sub- 
stitute for one of the two No. 5 bars required by 
22.6.6.5. 

(b) Horizontal reinforcement at least 0.20 square 
inch (129 mm 2 ) in cross-sectional area shall be 
provided: 

1. Continuously at structurally connected roof 
and floor levels and at the top of walls; 

2. At the bottom oflo ad- bearing walls or in the 
top of foundations where doweled to the 
wall; and 

3. At a maximum spacing of 120 inches (3048 
mm). 

Reinforcement at the top and bottom of open- 
ings, where used in determining the maximum 
spacing specified in Item 3 above, shall be con- 
tinuous in the wall. 

1908.1.8 ACI 318, Section 22.10. Delete ACI 318, Section 
22.10, and replace with the following: 

22.10 - Plain concrete in structures assigned to Seismic 
Design Category C, D, EorF 

22.10.1 - Structures assigned to Seismic Design Cate- 
gory C, D, E or F shall not have elements of structural 
plain concrete, except as follows: 

(a) Structural plain concrete basement, foundation 
or other walls below the base are permitted in 
detached one- and two-family dwellings three 
stories or less in height constructed with 



stud-bearing walls. In dwellings assigned to 
Seismic Design Category D or E, the height of the 
wall shallnot exceeds feet (2438 mm ), the thick- 
ness shall not be less than 7 ] / 2 inches (190 mm), 
and the wall shall retain no more than 4 feet 
(1219 mm) of unbalanced fill. Walls shall have 
reinforcement in accordance with 22.6.6.5. 

(b) Isolated footings of plain concrete supporting 
pedestals or columns are permitted, provided the 
projection of the footing beyond the face of the 
supported member does not exceed the footing 
thickness. 

Exception: In detached one- and two-family 
dwellings three stories or less in height, the pro- 
jection of the footing beyond the face of the sup- 
ported member is permitted to exceed the 
footing thickness. 

(c) Plain concrete footings supporting walls are per- 
mitted, provided the footings have at least two 
continuous longitudinal reinforcing bars. Bars 
shall not be smaller than No. 4 and shall have a 
total area of not less than 0.002 times the gross 
cross-sectional area of the footing. For footings 
that exceed 8 inches (203 mm) in thickness, a min- 
imum of one bar shall be provided at the top and 
bottom ofthe footing. Continuity ofreinforcement 
shall be provided at corners and intersections. 

Exceptions: 

1. In detached one- and two-family dwell- 
ings three stories or less in height and 
constructed with stud-bearing walls, 
plain concrete footings without longitu- 
dinal reinforcement supporting walls are 
permitted. 

2. For foundation systems consisting of a 
plain concrete footing and a plain con- 
crete stemwall, a minimum of one bar 
shall be provided at the top ofthe 
stemwall and at the bottom ofthe footing. 

3. Where a slab on ground is cast 
monolithic ally with the footing, one No. 5 
barispermittedto be located at either the 
top ofthe slab or bottom of the footing. 

1908.1.9 ACI 318, Section D.3.3. Modify ACI 318, Sec- 
tions D.3.3.4 and D.3.3. 5 to read as follows: 

D.3.3. 4 - Anchors shall be designed to be governed by 
the steel strength of a ductile steel element as determined 
in accordance with D. 5.1 and D. 6.1, unless either 
D.3.3.5 or D.3.3.6 is satisfied. 

Exceptions: 

1. Anchors in concrete designed to support non- 
structural components in accordance with 
ASCE 1 Section 13 A.lneednot satisfy Section 
D.3.3.4. 

2. Anchors designed to resist wall out-ofplane 
forces with design strengths equal to or greater 



422 



2009 INTERNATIONAL BUILDING CODE® 



CONCRETE 



than the force determined in accordance with 
ASCE1 Equation 12.11-1 or 12.14-lOneednot 
sa tisfy Section D.3.3.4. 

D.3.3.5 - Instead of D.3.3.4, the attachment that the 
anchor is connecting to the structure shall be designed so 
that the attachment will undergo ductile yielding at a 
force level corresponding to anchor forces no greater 
than the design strength of anchors specified in D.3.3.3 . 

Exceptions: 

1. Anchors in concrete designed to support 
nonstructural components in accordance with 
ASCE1 Section 13 A.lneednot satisfy Section 
D.3.3.5. 

2. Anchors designed to resist wall out-of-plane 
forces with design strengths equal to or greater 
than the force determined in accordance with 
AS CE1 Equation 12.11-1 or 12.14-10neednot 
satisfy Section A 3. 3. 5. 

1908.1.10 ACI 318, Section D.4.2.2. Delete ACI 318, Sec- 
tion D.4.2.2, and replace with the following: 

D.4.2.2 - The concrete breakout strength requirements for 
anchors in tension shall be considered satisfied by the 
design procedure of D. 5. 2 provided Equation D-8 is not 
used for anchor embedments exceeding 25 inches. The con- 
crete breakout strength requirements for anchors in shear 
with diameters not exceeding 2 inches shall be considered 
satisfied by the design procedure of D. 6.2. For anchors in 
shear with diameters exceeding! inches, shear anchor rein- 
forcement shall be provided in accordance with the proce- 
dures ofD.6.2.9. 



SECTION 1909 
STRUCTURAL PLAIN CONCRETE 

1909.1 Scope. The design and construction of structural plain 
concrete, both cast-in-place and precast, shall comply with the 
minimum requirements of Section 1909 and ACI 318, Chapter 
22, as modified in Section 1908. 

1909.1.1 Special structures. For special structures, such as 
arches, underground utility structures, gravity walls and 
shielding walls, the provisions of this section shall govern 
where applicable. 

1909.2 Limitations. The use of structural plain concrete shall 
be limited to: 

1. Members that are continuously supported by soil, such 
as walls and footings, or by other structural members 
capable of providing continuous vertical support. 

2. Members for which arch action provides compression 
under all conditions of loading. 

3. Walls and pedestals. 

The use of structural plain concrete columns and structural 
plain concrete footings on piles is not permitted. See Section 



1908.1.8 for additional limitations on the use of structural plain 
concrete. 

1909.3 Joints. Contraction or isolation joints shall be provided 
to divide structural plain concrete members into flexurally dis- 
continuous elements in accordance with ACI 318, Section 22.3. 

1909.4 Design. Structural plain concrete walls, footings and 
pedestals shall be designed for adequate strength in accordance 
with ACI 318, Sections 22.4 through 22.8. 

Exception: For Group R-3 occupancies and buildings of 
other occupancies less than two stories above grade plane 
of light-frame construction, the required edge thickness of 
ACI 318 is permitted to be reduced to 6 inches (152 mm), 
provided that the footing does not extend more than 4 inches 
(102 mm) on either side of the supported wall. 

1909.5 Precast members. The design, fabrication, transporta- 
tion and erection of precast, structural plain concrete elements 
shall be in accordance with ACI 318, Section 22.9. 

1909.6 Walls. In addition to the requirements of this section, 
structural plain concrete walls shall comply with the applicable 
requirements of ACI 318, Chapter 22. 

1909.6.1 Basement walls. The thickness of exterior base- I 
ment walls and foundation walls shall be not less than 7V 2 
inches (191 mm). 

1909.6.2 Other walls. Except as provided for in Section 
1909.6.1, the thickness of bearing walls shall be not less 
than 1/24 me unsupported height or length, whichever is 



shorter, but not less than 5V 2 inches (140 mm). 

1909.6.3 Openings in walls. Not less than one No. 5 bar 
shall be provided around window, door and similar sized 
openings. The bar shall be anchored to develop f y in tension 
at the corners of openings. 



SECTION 1910 
MINIMUM SLAB PROVISIONS 

1910.1 General. The thickness of concrete floor slabs supported 
directly on the ground shall not be less than 3 V 2 inches (89 mm). 
A 6-mil (0.006 inch; 0.15 mm) polyethylene vapor retarder with 
joints lapped not less than 6 inches (152 mm) shall be placed 
between the base course or subgrade and the concrete floor slab, 
or other approved equivalent methods or materials shall be used 
to retard vapor transmission through the floor slab. 

Exception: A vapor retarder is not required: 

1. For detached structures accessory to occupancies in 
Group R-3, such as garages, utility buildings or other 
unheated facilities. 

2. For unheated storage rooms having an area of less 
than 70 square feet (6.5 m 2 ) and carports attached to 
occupancies in Group R-3. 

3. For buildings of other occupancies where migration 
of moisture through the slab from below will not be 
detrimental to the intended occupancy of the building. 



i 



2009 INTERNATIONAL BUILDING CODE® 



423 



CONCRETE 



4. For driveways, walks, patios and other flatwork 
which will not be enclosed at a later date. 

5. Where approve d based on local site conditions. 



SECTION 1911 
ANCHORAGE TO CONCRETE- 
ALLOWABLE STRESS DESIGN 

1911.1 Scope. The provisions of this section shall govern the 
allowable stress design of headed bolts and headed stud 
anchors cast in normal- weight concrete for purposes of trans- 
mitting structural loads from one connected element to the 
other. These provisions do not apply to anchors installed in 
hardened concrete or where load combinations include earth- 
quake loads or effects. The bearing area of headed anchors 
shall be not less than one and one-half times the shank area. 
Where strength design is used, or where load combinations 
include earthquake loads or effects, the design strength of 
anchors shall be determined in accordance with Section 1912. 
Bolts shall conform to ASTM A 307 or an approved equivalent 

191 1.2 Allowable service load. The allowable service load for 
headed anchors in shear or tension shall be as indicated in Table 
1911.2. Where anchors are subject to combined shear and ten- 
sion, the following relationship shall be satisfied: 

(Psi P t )5/s + (VJ V t ) 5/3 < 1 (Equation 19-1) 

where: 

P s = Applied tension service load, pounds (N). 

P t = Allowable tension service load from Table 1911.2, 
pounds (N). 

V s = Applied shear service load, pounds (N). 

V t = Allowable shear service load from Table 1911.2, 
pounds (N). 



1911.3 Required edge distance and spacing. The allowable 
service loads in tension and shear specified in Table 191 1.2 are 
for the edge distance and spacing specified. The edge distance 
and spacing are permitted to be reduced to 50 percent of the val- 
ues specified with an equal reduction in allowable service load. 
Where edge distance and spacing are reduced less than 50 per- 
cent, the allowable service load shall be determined by linear 
interpolation. 

1911.4 Increase in allowable load. Increase of the values in 
Table 1911.2 by one-third is permitted where the provisions of 
Section 1605.3.2 permit an increase in allowable stress for 
wind loading. 

1911.5 Increase for special inspection. Where specialinspec- 
tion is provided for the installation of anchors, a 100-percent 
increase in the allowable tension values of Table 191 1.2 is per- 
mitted. No increase in shear value is permitted. 



SECTION 1912 
ANCHORAGE TO CONCRETE- 
STRENGTH DESIGN 

1912.1 Scope. The provisions of this section shall govern the 
strength design of anchors installed in concrete for purposes of 
transmitting structural loads from one connected element to the 
other. Headed bolts, headed studs and hooked (J - or L-) bolts cast 
in concrete and expansion anchors and undercut anchors installed 
in hardened concrete shall be designed in accordance with Appen- 
dix D of ACI 318 as modified by Sections 1908.1.9 and 
1908.1.10, provided they are within the scope of Appendix D. 

The strength design of anchors that are not within the scope 
of Appendix D of ACI 318, and as amended in Sections 
1908.1.9 and 1908.1.10, shall be in accordance with an 
app roved procedure. 



TABLE 1911.2 
ALLOWABLE SERVICE LOAD ON EMBEDDED BOLTS (pounds) 



BOLT 

DIAMETER 

(inches) 


MINIMUM 

EMBEDMENT 

(inches) 


EDGE 

DISTANCE 

(inches) 


SPACING 

(inches) 


MINIMUM CONCRETE STRENGTH (psi) 


fie =?, 500 


fie =?, 000 


fie =4 000 


Tension 


Shear 


Tension 


Shear 


Tension 


Shear 


l U 


2V 2 


1V 2 


3 


200 


500 


200 


500 


200 


500 


3/ 8 


3 


2% 


4V 2 


500 


1,100 


500 


1,100 


500 


1,100 


ll 2 


4 
4 


3 
5 


6 
6 


950 
1,450 


1,250 
1,600 


950 
1,500 


1,250 
1,650 


950 
1,550 


1,250 
1,750 


5/ 8 


4V 2 
4V 2 


3 3 / 4 
6V 4 


1\ 
7V 2 


1,500 
2,125 


2,750 
2,950 


1,500 
2,200 


2,750 
3,000 


1,500 
2,400 


2,750 
3,050 


3/ 4 


5 
5 


4V 2 
1\ 


9 
9 


2,250 

2,825 


3,250 
4,275 


2,250 
2,950 


3,560 
4,300 


2,250 
3,200 


3,560 
4,400 


7/ 8 


6 


5V 4 


10V 2 


2,550 


3,700 


2,550 


4,050 


2,550 


4,050 


1 


7 


6 


12 


3,050 


4,125 


3,250 


4,500 


3,650 


5,300 


l\ 


8 


6 3 / 4 


13 h 2 


3,400 


4,750 


3,400 


4,750 


3,400 


4,750 


iv 4 


9 


1\ 


15 


4,000 


5,800 


4,000 


5,800 


4,000 


5,800 



For 51: 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa, 1 pound = 4.45 N. 



424 



2009 INTERNATIONAL BUILDING CODE® 



CONCRETE 



SECTION 1913 
SHOTCRETE 

1913.1 General. Shotcrete is mortar or concrete that is pneu- 
matically projected at high velocity onto a surface. Except as 
specified in this section, shotcrete shall conform to the require- 
ments of this chapter for plain or reinforced concrete. 

1913.2 Proportions and materials. Shotcrete proportions 
shall be selected that allow suitable placement procedures 
using the delivery equipment selected and shall result in fin- 
ished in-place hardened shotcrete meeting the strength require- 
ments of this code. 

1913.3 Aggregate. Coarse aggregate, if used, shall not exceed 
3/ 4 inch (19.1 mm). 

1913.4 Reinforcement. Reinforcement used in shotcrete con- 
struction shall comply with the provisions of Sections 1913.4.1 
through 1913.4.4. 

1913.4.1 Size. The maximum size of reinforcement shall be 
No. 5 bars unless it is demonstrated by preconstruction tests 
that adequate encasement of larger bars will be achieved. 

1913.4.2 Clearance. When No. 5 or smaller bars are used, 
there shall be a minimum clearance between parallel rein- 
forcement bars of 2V 2 inches (64 mm). When bars larger 
than No. 5 are permitted, there shall be a minimum clear- 
ance between parallel bars equal to six diameters of the bars 
used. When two curtains of steel are provided, the curtain 
nearer the nozzle shall have a minimum spacing equal to 12 
bar diameters and the remaining curtain shall have a mini- 
mum spacing of six bar diameters. 

Exception: Subject to the approval of the bUilding offi- 
cial, required clearances shall be reduced where it is 
demonstrated by preconstruction tests that adequate 
encasement of the bars used in the design will be 
achieved. 

1913.4.3 Splices. Lap splices of reinforcing bars shall uti- 
lize the noncontact lap splice method with a minimum clear- 
ance of 2 inches (51 mm) between bars. The use of contact 
lap splices necessary for support of the reinforcing is per- 
mitted when approve dby the bUilding official, based on sat- 
isfactory preconstruction tests that show that adequate 
encasement of the bars will be achieved, and provided that 
the splice is oriented so that a plane through the center of the 
spliced bars is perpendicular to the surface of the shotcrete. 

1913.4.4 Spirally tied columns. Shotcrete shall not be 
applied to spirally tied columns. 

1913.5 Preconstruction tests. When required by the bUilding 
official, a test panel shall be shot, cured, cored or sawn, exam- 
ined and tested prior to commencement of the project. The 
sample panel shall be representative of the project and simulate 
job conditions as closely as possible. The panel thickness and 
reinforcing shall reproduce the thickest and most congested 
area specified in the structural design. It shall be shot at the 
same angle, using the same nozzleman and with the same con- 
crete mix design that will be used on the project. The equip- 
ment used in preconstruction testing shall be the same 
equipment used in the work requiring such testing, unless sub- 
stitute equipment is approvedby the bUilding official. 



1913.6 Rebound. Any rebound or accumulated loose aggre- 
gate shall be removed from the surfaces to be covered prior to 
placing the initial or any succeeding layers of shotcrete. 
Rebound shall not be used as aggregate. 

1913.7 Joints. Except where permitted herein, unfinished 
work shall not be allowed to stand for more than 30 minutes 
unless edges are sloped to a thin edge. For structural elements 
that will be under compression and for construction joints 
shown on the approved construction documents, square joints 
are permitted. Before placing additional material adjacent to 
previously applied work, sloping and square edges shall be 
cleaned and wetted. 

1913.8 Damage. In-place shotcrete that exhibits sags, sloughs, 
segregation, honeycombing, sand pockets or other obvious 
defects shall be removed and replaced. Shotcrete above sags 
and sloughs shall be removed and replaced while still plastic. 

1913.9 Curing. During the curing periods specified herein, 
shotcrete shall be maintained above 40°F (4°C) and in moist 
condition. 

1913.9.1 Initial curing. Shotcrete shall be kept continu- 
ously moist for 24 hours after shotcreting is complete or 
shall be sealed with an approved curing compound. 

1913.9.2 Final curing. Final curing shall continue for seven 
days after shotcreting, or for three days if high- 
early -strength cement is used, or until the specified strength 
is obtained. Final curing shall consist of the initial curing 
process or the shotcrete shall be covered with an approved 
moisture-retaining cover. 

1913.9.3 Natural curing. Natural curing shall not be used 
in lieu of that specified in this section unless the relative 
humidity remains at or above 85 percent, and is authorized 
by the registered design professional and approvedby the 
building official. 

1913.10 Strength tests. Strength tests for shotcrete shall be 
made by an approved agency on specimens that are representa- 
tive of the work and which have been water soaked for at least 
24 hours prior to testing. When the maximum- size aggregate is 
larger than 3/ 8 inch (9.5 mm) , specimens shall consist of not less 
than three 3 -inch-diameter (76 mm) cores or 3 -inch (76 mm) 
cubes. When the maximum- size aggregate is 3/ 8 inch (9.5 mm) 
or smaller, specimens shall consist of not less than 
2-inch-diameter (51 mm) cores or 2-inch (51 mm) cubes. 

1913.10.1 Sampling. Specimens shall be taken from the 
in-place work or from test panels, and shall be taken at least 
once each shift, but not less than one for each 50 cubic yards 
(38.2 m 3 ) of shotcrete. 

1913.10.2 Panel criteria. When the maximum-size aggre- 
gate is larger than 3/ 8 inch (9.5 mm), the test panels shall 
have minimum dimensions of 18 inches by 18 inches (457 
mm by 457 mm). When the maximum size aggregate is 3/ 8 
inch (9.5 mm) or smaller, the test panels shall have mini- 
mum dimensions of 12 inches by 12 inches (305 mm by 305 
mm). Panels shall be shot in the same position as the work, 
during the course of the work and by the nozzlemen doing 
the work. The conditions under which the panels are cured 
shall be the same as the work. 



2009 INTERNATIONAL BUILDING CODE® 



425 



CONCRETE 



1913.10.3 Acceptance criteria. The average compressive 
strength of three cores from the in-place work or a single test 
panel shall equal or exceed 0.85 i ' c with no single core less 
than 0.75 i ' c The average compressive strength of three 
cubes taken from the in-place work or a single test panel 
shall equal or exceed i r c with no individual cube less than 
0.88 i ' c . To check accuracy, locations represented by erratic 
core or cube strengths shall be retested. 



SECTION 1914 
REINFORCED GYPSUM CONCRETE 

1914.1 General. Reinforced gypsum concrete shall comply 
with the requirements of ASTM C 317 and ASTM C 956. 

1914.2 Minimum thickness. The minimum thickness of rein- 
forced gypsum concrete shall be 2 inches (51 mm) except the 
minimum required thickness shall be reduced to 1V 2 inches (38 
mm), provided the following conditions are satisfied: 

1. The overall thickness, including the formboard, is not 
less than 2 inches (51 mm). 

2. The clear span of the gypsum concrete between supports 
does not exceed 33 inches (838 mm). 

3. Diaphragm action is not required. 

4. The design live load does not exceed 40 pounds per 
square foot (psf) (1915 Pa). 



shell shall not be included in the calculations for strength of the 
column section. The minimum diameter of pipe columns shall 
be 4 inches (102 mm) except that in structures of Type V con- 
struction not exceeding three stories above grade plane or 40 
feet (12 192 mm) in bUilding height, pipe columns used in 
basements and as secondary steel members shall have a mini- 
mum diameter of 3 inches (76 mm). 

1915.6 Approvals. Details of column connections and splices 
shall be shop fabricated by approved methods and shall be 
approved only after tests in accordance with the approved 
rules. Shop-fabricated concrete-filled pipe columns shall be 
inspected by the bUilding officialor by an approvedrepresenta- 
tive of the manufacturer at the plant. 



1 



SECTION 1915 
CONCRETE-FILLED PIPE COLUMNS 

1915.1 General. Concrete-filled pipe columns shall be manu- 
factured from standard, extra- strong or double-extra- strong 
steel pipe or tubing that is filled with concrete so placed and 
manipulated as to secure maximum density and to ensure com- 
plete filling of the pipe without voids. 

1915.2 Design. The safe supporting capacity of concrete-filled 
pipe columns shall be computed in accordance with the 
approve d rules or as determined by a test. 

1915.3 Connections. Caps, base plates and connections shall 
be of approved types and shall be positively attached to the 
shell and anchored to the concrete core. Welding of brackets 
without mechanical anchorage shall be prohibited. Where the 
pipe is slotted to accommodate webs of brackets or other con- 
nections, the integrity of the shell shall be restored by welding 
to ensure hooping action of the composite section. 

1915.4 Reinforcement. To increase the safe load- supporting 
capacity of concrete-filled pipe columns, the steel reinforce- 
ment shall be in the form of rods, structural shapes or pipe 
embedded in the concrete core with sufficient clearance to 
ensure the composite action of the section, but not nearer than 1 
inch (25 mm) to the exterior steel shell. Structural shapes used 
as reinforcement shall be milled to ensure bearing on cap and 
base plates. 

1915.5 Fire-resistance-rating protection. Pipe columns shall 
be of such size or so protected as to develop the required 
fire-resistance ratings specified in Table 601. Where an outer 
steel shell is used to enclose the fire protective covering, the 



426 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 20 

ALUMINUM 



SECTION 2001 
GENERAL 

2001.1 Scope. This chapter shall govern the quality, design, 
fabrication and erection of aluminum. 



SECTION 2002 
MATERIALS 

2002.1 General. Aluminum used for structural purposes in 
buildings and structures shall comply with AA ASM 35 and 
AA ADM 1. The nominalloads shall be the minimum design 
loads required by Chapter 16. 



2009 INTERNATIONAL BUILDING CODE® 427 



428 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 21 

MASONRY 



SECTION 2101 
GENERAL 

2101.1 Scope. This chapter shall govern the materials, design, 
construction and quality of masonry. 

2101.2 Design methods. Masonry shall comply with the pro- 
visions of one of the following design methods in this chapter 
as well as the requirements of Sections 2101 through 2104. 
Masonry designed by the allowable stress design provisions of 
Section 2101.2.1, the strength design provisions of Section 

2101.2.2 or the prestressed masonry provisions of Section 

2101.2.3 shall comply with Section 2105. 

2101.2.1 Allowable stress design. Masonry designed by 
the allowable stress design method shall comply with the 
provisions of Sections 2106 and 2107. 

2101.2.2 Strength design. Masonry designed by the 
strength design method shall comply with the provisions of 
Sections 2106 and 2108, except that autoclaved aerated con- 
crete (AAC) masonry shall comply with the provisions of 
Section 2106, Section 1613.6.4 and Chapter 1 and Appen- 
dix A ofTMS 402/ACI 530/ASCE 5. 

2101.2.3 Prestressed masonry. Prestressed masonry shall 
be designed in accordance with Chapters 1 and 4 of TMS 
4021 ACI 5301 ASCE 5 and Section 2106. Special inspection 
during construction shall be provided as set forth in Section 
1704.5. 

2101.2.4 Empirical design. Masonry designed by the 
empirical design method shall comply with the provisions 
of Sections 2106 and 2109 or Chapter 5 of TMS 402/ACI 
530/ASCE 5. 

2101.2.5 Glass unit masonry. Glass unit masonry shall 
comply with the provisions of Section 2110 or Chapter 7 of 
TMS 402/ACI 530/ASCE 5. 

2101.2.6 Masonry veneer. Masonry veneer shall comply 
with the provisions of Chapter 14 or Chapter 6 of TMS 
402/ACI 530/ASCE 5. 

2101.3 Construction documents. The construction docu- 
ments shall show all of the items required by this code includ- 
ing the following: 

1. Specified size, grade, type and location of reinforce- 
ment, anchors and wall ties. 

2. Reinforcing bars to be welded and welding procedure. 

3. Size and location of structural elements. 

4. Provisions for dimensional changes resulting from elas- 
tic deformation, creep, shrinkage, temperature and mois- 
ture. 

5. Loads used in the design of masonry. 

6. Specified compressive strength of masonry at stated ages 
or stages of construction for which masonry is designed, 
except where specifically exempted by this code. 



7. Details of anchorage of masonry to structural members, 
frames and other construction, including the type, size 
and location of connectors. 

8. Size and location of conduits, pipes and sleeves. 

9. The minimum level of testing and inspection as defined 
in Chapter 17, or an itemized testing and inspection pro- 
gram that meets or exceeds the requirements of Chapter 
17. 

2101.3.1 Fireplace drawings. The construction documents 
shall describe in sufficient detail the location, size and con- 
struction of masonry fireplaces. The thickness and charac- 
teristics of materials and the clearances from walls, 
partitions and ceilings shall be indicated. 



SECTION 2102 
DEFINITIONS AND NOTATIONS 

2102.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

AAC MASONRY. Masonry made of autoclaved aerated con- 
crete (AAC) units, manufactured without internal reinforce- 
ment and bonded together using thin- or thick-bed mortar. 

ADOBE CONSTRUCTION. Construction in which the exte- 
rior load-bearing and nonload-bearing walls and partitions are 
of unfired clay masonry units, and floors, roofs and interior 
framing are wholly or partly of wood or other approvedmateri- 

also 

Adobe, stabilized. Unfired clay masonry units to which 
admixtures, such as emulsified asphalt, are added during the 
manufacturing process to limit the units' water absorption 
so as to increase their durability. 

Adobe, unstabilized. Unfired clay masonry units that do 
not meet the definition of "Adobe, stabilized." 

ANCHOR. Metal rod, wire or strap that secures masonry to its 
structural support. 

ARCHITECTURAL TERRA COTTA. Plain or ornamental 
hard-burned modified clay units, larger in size than brick, with 
glazed or unglazed ceramic finish. 

AREA. 

Bedded. The area of the surface of a masonry unit that is in 
contact with mortar in the plane of the joint. 

Gross cross-sectional. The area delineated by the out- 
to-out specified dimensions of masonry in the plane under 
consideration. 

Net cross-sectional. The area of masonry units, grout and 
mortar crossed by the plane under consideration based on 
out-to-out specified dimensions. 



2009 INTERNATIONAL BUILDING CODE® 



429 



MASONRY 



AUTOCLAVED AERATED CONCRETE (AAC). Low- 
density cementitious product of calcium silicate hydrates, 
whose material specifications are defined in ASTM C 1386. 

BED JOINT. The horizontal layer of mortar on which a 
masonry unit is laid. 

BOND BEAM. A horizontal grouted element within masonry 
in which reinforcement is embedded. 

BRICK. 

Calcium silicate (sand lime brick). A masonry unit made 
of sand and lime. 

Clay or shale. A masonry unit made of clay or shale, usu- 
ally formed into a rectangular prism while in the plastic state 
and burned or fired in a kiln. 

Concrete. A masonry unit having the approximate shape of 
a rectangular prism and composed of inert aggregate parti- 
cles embedded in a hardened cementitious matrix. 

CAST STONE. A building stone manufactured from portland 
cement concrete precast and used as a trim, veneer or facing on 
or in buildings or structures. 

CELL. A void space having a gross cross-sectional area 
greater than 1V 2 square inches (967 mm 2 ). 

CHIMNEY. A primarily vertical enclosure containing one or 
more passageways for conveying flue gases to the outside 
atmosphere. 

CHIMNEY TYPES. 

High-heat appliance type. An approved chimney for 
removing the products of combustion from fuel-burning, 
high-heat appliances producing combustion gases in excess 
of 2,000°F (1093°C) measured at the appliance flue outlet 
(see Section 2113.11.3). 

Low-heat appliance type. An approved chimney for 
removing the products of combustion from fuel-burning, 
low-heat appliances producing combustion gases not in 
excess of 1,000°F (538°C) under normal operating condi- 
tions, but capable of producing combustion gases of 
1,400°F (760°C) during intermittent forces firing for peri- 
ods up to 1 hour. Temperatures shall be measured at the 
appliance flue outlet. 

Masonry type. A field-constructed chimney of solid 
masonry units or stones. 

Medium-heat appliance type. An approved chimney for 
removing the products of combustion from fuel-burning, 
medium-heat appliances producing combustion gases not 
exceeding 2,000°F (1093°C) measured at the appliance flue 
outlet (see Section 2113.11.2). 

CLEANOUT. An opening to the bottom of a grout space of 
sufficient size and spacing to allow the removal of debris. 

COLLAR JOINT. Verticallongitudinaljoint between wythes 
of masonry or between masonry and backup construction that 
is permitted to be filled with mortar or grout. 

COMPRESSIVE STRENGTH OF MASONRY. Maximum 
compressive force resisted per unit of net cross-sectional area 



of masonry, determined by the testing of masonry prisms or a 
function of individual masonry units, mortar and grout. 

CONNECTOR. A mechanical device for securing two or 
more pieces, parts or members together, including anchors, 
wall ties and fasteners. 

COVER. Distance between surface of reinforcing bar and 
edge of member. i 

DIMENSIONS. 

Actual. The measured dimension of a masonry unit or ele- 
ment. 

Nominal. The specified dimension plus an allowance for 
the joints with which the units are to be laid. Thickness is 
given first, followed by height and then length. 

Specified. The dimensions specified for the manufacture or 
construction of masonry, masonry units, joints or any other 
component of a structure. i 

FIREPLACE. A hearth and fire chamber or similar prepared 
place in which a fire may be made and which is built in con- 
junction with a chimney. 

FIREPLACE THROAT. The opening between the top of the 
firebox and the smoke chamber. 

FOUNDATION PIER. An isolated vertical foundation mem- 
ber whose horizontal dimension measured at right angles to its 
thickness does not exceed three times its thickness and whose 
height is equal to or less than four times its thickness. 

GROUTED MASONRY. 

Grouted hollow-unit masonry. That form of grouted 
masonry construction in which certain designated cells of 
hollow units are continuously filled with grout. 

Grouted multiwythe masonry. That form of grouted 
masonry construction in which the space between the 
wythes is solidly or periodically filled with grout. 

HEAD JOINT. Vertical mortar joint placed between masonry 
units within the wythe at the time the masonry units are laid. 

HEIGHT, WALLS. The vertical distance from the foundation 
wall or other immediate support of such wall to the top of the 
wall. 

MASONRY. A built-up construction or combination of build- 
ing units or materials of clay, shale, concrete, glass, gypsum, 
stone or other approv edunits bonded together with or without 
mortar or grout or other accepted methods ofjoining. 

Ashlar masonry. Masonry composed of various-sized rect- 
angular units having sawed, dressed or squared bed sur- 
faces, properly bonded and laid in mortar. 

Coursed ashlar. Ashlar masonry laid in courses of stone of 
equal height for each course, although different courses 
shall be permitted to be of varying height. 

Glass unit masonry. Masonry composed of glass units 
bonded by mortar. 

Plain masonry. Masonry in which the tensile resistance of 
the masonry is taken into consideration and the effects of 
stresses in reinforcement are neglected. 



430 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



Random ashlar. Ashlar masonry laid in courses of stone set 
without continuous joints and laid up without drawn pat- 
terns. When composed of material cut into modular heights, 
discontinuous but aligned horizontaljoints are discernible. 

Reinforced masonry. Masonry construction in which rein- 
forcement acting in conjunction with the masonry is used to 
resist forces. 

Solid masonry. Masonry consisting of solid masonry units 
laid contiguously with the joints between the units filled 
with mortar. 

Unreinforced (plain) masonry. Masonry in which the ten- 
sile resistance of masonry is taken into consideration and 
the resistance of the reinforcing steel, if present, is 
neglected. 

MASONRY UNIT. Brick, tile, stone, glass block or concrete 
block conforming to the requirements specified in Section 
2103. 

Clay. A building unit larger in size than a brick, composed 
of burned clay, shale, fired clay or mixtures thereof. 

Concrete. A building unit or block larger in size than 12 
inches by 4 inches by 4 inches (305 mm by 102 mm by 102 
mm) made of cement and suitable aggregates. 

Hollow. A masonry unit whose net cross-sectional area in 
any plane parallel to the load-bearing surface is less than 75 
percent of its gross cross-sectional area measured in the 
same plane. 

Solid. A masonry unit whose net cross-sectional area in 
every plane parallel to the load-bearing surface is 75 percent 
or more of its gross cross-sectional area measured in the 
same plane. 

MORTAR. A plastic mixture of app roved cementitious mate- 
rials, fine aggregates and water used to bond masonry or other 
structural units. 

MORTAR, SURFACE-BONDING. A mixture to bond con- 
crete masonry units that contains hydraulic cement, glass fiber 
reinforcement with or without inorganic fillers or organic mod- 
ifiers and water. 

PRESTRESSED MASONRY. Masonry in which internal 
stresses have been introduced to counteract potential tensile 
stresses in masonry resulting from applied loads. 

PRISM. An assemblage of masonry units and mortar with or 
without grout used as a test specimen for determining proper- 
ties of the masonry. 

RUBBLE MASONRY. Masonry composed of roughly 
shaped stones. 

Coursed rubble. Masonry composed of roughly shaped 
stones fitting approximately on level beds and well bonded. 

Random rubble. Masonry composed of roughly shaped 
stones laid without regularity of coursing but well bonded 
and fitted together to form well- divided joints. 

Rough or ordinary rubble. Masonry composed of 
unsquared field stones laid without regularity of coursing 
but well bonded. 



RUNNING BOND. The placement of masonry units such that 
headjoints in successive courses are horizontally offset at least 
one-quarter the unit length. 

SHEAR WALL. 

Detailed plain masonry shear wall. A masonry shear wall 
designed to resist lateral forces neglecting stresses in rein- 
forcement' and designed in accordance with Section 
2106.1. 

Intermediate prestressed masonry shear wall. A pre- 
stressed masonry shear wall designed to resist lateral forces 
considering stresses in reinforcement, and designed in 
accordance with Section 2106.1. 

Intermediate reinforced masonry shear wall. A masonry 
shear wall designed to resist lateral forces considering 
stresses in reinforcement, and designed in accordance with 
Section 2106.1. 

Ordinary plain masonry shear wall. A masonry shear 
wall designed to resist lateral forces neglecting stresses in 
reinforcement, and designed in accordance with Section 
2106.1. 

Ordinary plain prestressed masonry shear wall. A pre- 
stressed masonry shear wall designed to resist lateral forces 
considering stresses in reinforcement, and designed in 
accordance with Section 2106.1. 

Ordinary reinforced masonry shear wall. A masonry 
shear wall designed to resist lateral forces considering 
stresses in reinforcement, and designed in accordance with 
Section 2106.1. 

Special prestressed masonry shear wall. A prestressed 
masonry shear wall designed to resist lateral forces consid- 
ering stresses in reinforcement and designed in accordance 
with Section 2106.1 except that only grouted, laterally 
restrained tendons are used. 

Special reinforced masonry shear wall. A masonry shear 
wall designed to resist lateral forces considering stresses in 
reinforcement, and designed in accordance with Section 
2106.1. 

SHELL. The outer portion of a hollow masonry unit as placed 
in masonry. 

SPECIFIED. Required by construction documents. 

SPECIFIED COMPRESSIVE STRENGTH OF 
MASONRY, ['m. Minimum compressive strength, expressed 
as force per unit of net cross-sectional area, required of the 
masonry used in construction by the construction documents, 
and upon which the project design is based. Whenever the 
quantity ['ill is under the radical sign, the square root of numeri- 
cal value only is intended and the result has units of pounds per 
square inch (psi) (MPa). 

STACK BOND. The placement of masonry units in a bond 
pattern is such that headjoints in successive courses are verti- 
cally aligned. For the purpose of this code, requirements for 
stack bond shall apply to masonry laid in other than running 
bond. 



2009 INTERNATIONAL BUILDING CODE® 



431 



MASONRY 



STONE MASONRY. Masonry composed offield, quarried or 
cast stone units bonded by mortar. 

Ashlar stone masonry. Stone masonry composed of rect- 
angular units having sawed, dressed or squared bed surfaces 
and bonded by mortar. 

Rubble stone masonry. Stone masonry composed of irreg- 
ular-shaped units bonded by mortar. 

STRENGTH. 

Design strength. Nominal strength multiplied by a strength 
reduction factor. 

Nominal strength. Strength of a member or cross section 
calculated in accordance with these provisions before appli- 
cation of any strength-reduction factors . 

Required strength. Strength of a member or cross section 
required to resist factored loads. 

THIN-BED MORTAR. Mortar for use in construction of 
AAC unit masonry withjoints 0.06 inch (1.5 mm) or less. 

TIE, LATERAL. Loop of reinforcing bar or wire enclosing 
longitudinal reinforcement. 

TIE, WALL. A connector that connects wythes of masonry 
walls together. 

TILE. A ceramic surface unit, usually relatively thin in relation 
to facial area, made from clay or a mixture of clay or other 
ceramic materials, called the body of the tile, having either a 
"glazed" or "unglazed" face and fired above red heat in the 
course of manufacture to a temperature sufficiently high 
enough to produce specific physical properties and characteris- 
tics. 

TILE, STRUCTURAL CLAY. A hollow masonry unit com- 
posed of burned clay, shale, fire clay or mixture thereof, and 
having parallel cells . 

WALL. A vertical element with a horizontallength-to-thick- 
ness ratio greater than three, used to enclose space. 

Cavity wall. A wall built of masonry units or of concrete, or 
a combination of these materials, arranged to provide an air- 
space within the wall, and in which the inner and outer parts 
of the wall are tied together with metal ties. 

Composite wall. A wall built of a combination of two or 
more masonry units bonded together, one forming the 
backup and the other forming the facing elements. 

Dry-stacked, surface-bonded wall. A wall built of con- 
crete masonry units where the units are stacked dry, without 
mortar on the bed or headjoints, and where both sides of the 
wall are coated with a surface-bonding mortar. 

Masonry-bonded hollow wall. A wall built of masonry 
units so arranged as to provide an airspace within the wall, 
and in which the facing and backing of the wall are bonded 
together with masonry units . 

Parapet wall. The part of any wall entirely above the roof 
line. 

WEB. An interior solid portion of a hollow masonry unit as 
placed in masonry. 



WYTHE. Each continuous, vertical section of a wall, one 
masonry unit in thickness. 

NOTATIONS. 

db = Diameter of reinforcement, inches (mm). 

F s = Allowable tensile or compressive stress in reinforce- 
ment, psi (MPa) . 

f r = Modulus of rupture, psi (MPa). 

f' MC = Specified compressive strength of AAC masonry, the 
minimum compressive strength for a class of AAC 
masonry as specified in ASTM C 1386, psi (MPa). 

f' m = Specified compressive strength of masonry at age of 28 
days, psi (MPa). 

['mi = Specified compressive strength of masonry at the time 
of prestress transfer, psi (MPa). 

K = The lesser of the masonry cover, clear spacing between 
adjacent reinforcement, or five times db' inches (mm). 

Is = Distance between supports, inches (mm). 

Id = Required development length or lap length of rein- 
forcement, inches (mm). 

P = The applied load at failure, pounds (N). 

Sf = Thickness of the test specimen measured parallel to the 
direction of load, inches (mm). 

Sw = Width of the test specimen measured parallel to the 
loading cylinder, inches (mm). 



SECTION 2103 
MASONRY CONSTRUCTION MATERIALS 

2103.1 Concrete masonry units. Concrete masonry units 
shall conform to the following standards: ASTM C 55 for con- 
crete brick; ASTM C 73 for calcium silicate face brick; ASTM 
C 90 for load-bearing concrete masonry units or ASTM C 744 
for prefaced concrete and calcium silicate masonry units. 

2103.2 Clay or shale masonry units. Clay or shale masonry 
units shall conform to the following standards: ASTM C 34 for 
structural clay load-bearing wall tile; ASTM C 56 for struc- 
tural clay nonload-bearing wall tile; ASTM C 62 for building 
brick (solid masonry units made from clay or shale) ; ASTM C 
1088 for solid units of thin veneer brick; ASTM C 126 for 
ceramic-glazed structural clay facing tile, facing brick and 
solid masonry units; ASTM C 212 for structural clay facing 
tile; ASTM C 216 for facing brick (solid masonry units made 
from clay or shale); ASTM C 652 for hollow brick (hollow 
masonry units made from clay or shale) or ASTM C 1405 for 
glazed brick (single-fired solid brick units). 

Exception: Structural clay tile for nonstructural use in fire- 
proofing of structural members and in wall furring shall not 
be required to meet the compressive strength specifications. 
The fire-resistance rating shall be determined in accordance 
with ASTM E 119 or UL 263 and shall comply with the 
requirements of Table 602. 

2103.3 AAC masonry. AAC masonry units shall conform to 
ASTM C 1386 for the strength class specified. 



432 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



.1 



2103.4 Stone masonry units. Stone masonry units shall con- 
form to the following standards: ASTM C 503 for marble 
building stone (exterior); ASTM C 568 for limestone building 
stone; ASTM C 615 for granite building stone; ASTM C 616 
for sandstone building stone; or ASTM C 629 for slate building 
stone. 

2103.5 Ceramic tile. Ceramic tile shall be as defined in, and 
shall conform to the requirements of, ANSI AI37.1. 

2103.6 Glass unit masonry. Hollow glass units shall be par- 
tially evacuated and have a minimum average glass face thick- 
ness of 3/ 16 inch (4.8 mm). Solid glass-block units shall be 
provided when required. The surfaces of units intended to be in 
contact with mortar shall be treated with a polyvinyl butyral 
coating or latex-based paint. Reclaimed units shall not be used. 

2103.7 Second-hand units. Second-hand masonry units shall 
not be reused unless they conform to the requirements of new 
units. The units shall be of whole, sound materials and free 
from cracks and other defects that will interfere with proper 
laying or use. Old mortar shall be cleaned from the unit before 
reuse. 

2103.8 Mortar. Mortar for use in masonry construction shall 
conform to ASTM C 270 and Articles 2.1 and 2.6 A ofTMS 
602/ACI 530.1/ASCE 6, except for mortars listed in Sections 
2103.9,2103.10 and 2103.11. Type S or N mortar conforming 
to ASTM C 270 shall be used for glass unit masonry. 

2103.9 Surface-bonding mortar. Surface-bonding mortar 
shall comply with ASTM C 887. Surface bonding of concrete 
masonry units shall comply with ASTM C 946. 

2103.10 Mortars for ceramic wall and floor tile. Portland 
cement mortars for installing ceramic wall and floor tile shall 
comply with ANSI AI08.IA and ANSI AI08.IB and be of the 
compositions indicated in Table 2103.10. 

TABLE 2103.10 
CERAMIC TILE MORTAR COMPOSITIONS 



LOCATION 


MORTAR 


COMPOSITION 


Walls 


Scratchcoat 


1 cement; i/ 5 hydrated lime; 
4 dry or 5 damp sand 


Setting bed and 
leveling coat 


1 cement; i/ 2 hydrated lime; 

5 damp sand to 1 cement 
1 hydrated lime, 7 damp sand 


Floors 


Setting bed 


1 cement; i/ 10 hydrated lime; 

5 dry or 6 damp sand; or 1 

cement; 5 dry or 6 damp sand 


Ceilings 


Scratchcoat and 
sand bed 


1 cement; i/ 2 hydrated lime; 
2h 2 dry sand or 3 damp sand 



2103.10.1 Dry-set portland cement mortars. Premixed 
prepared portland cement mortars, which require only the 
addition of water and are used in the installation of ceramic 
tile, shall comply with ANSI AII8.1. The shear bond 
strength for tile set in such mortar shall be as required in 
accordance with ANSI A 118.1. Tile set in dry-set portland 
cement mortar shall be installed in accordance with ANSI 
AI08.5. 

2103.10.2 Latex-modified portland cement mortar. 

Latex-modified portland cement thin- set mortars in which 
latex is added to dry- set mortar as a replacement for all or 



part of the gauging water that are used for the installation of 
ceramic tile shall comply with ANSI All 8. 4. Tile set in 
latex-modified portland cement shall be installed in accor- 
dance with ANSI AI08. 5. 

2103.10.3 Epoxy mortar. Ceramic tile set and grouted with 
chemical-resistant epoxy shall comply with ANSI AII8.3. 
Tile set and grouted with epoxy shall be installed in accor- 
dance with ANSI AI08. 6. 

2103.10.4 Furan mortar and grout. Chemical-resistant 
furan mortar and grout that are used to install ceramic tile 
shall comply with ANSI All 8. 5. Tile set and grouted with 
furan shall be installed in accordance with ANSI AI08.8. 

2103.10.5 Modified epoxy-emulsion mortar and grout. 

Modified epoxy-emulsion mortar and grout that are used to 
install ceramic tile shall comply with ANSI AII8.8. Tile set 
and grouted with modified epoxy-emulsion mortar and 
grout shall be installed in accordance with ANSI AI08.9. 

2103.10.6 Organic adhesives. Water-resistant organic 
adhesives used for the installation of ceramic tile shall com- 
ply with ANSI AI36. 1 . The shear bond strength after water 
immersion shall not be less than 40 psi (275 kPa) for Type I 
adhesive and not less than 20 psi (138 kPa) for Type II adhe- 
sive when tested in accordance with ANSI AI36.I. Tile set 
in organic adhesives shall be installed in accordance with 
ANSIAI08.4. 

2103.10.7 Portland cement grouts. Portland cement 
grouts used for the installation of ceramic tile shall comply 
with ANSI All 8. 6. Portland cement grouts for tile work 
shall be installed in accordance with ANSI AI08.IO. 

2103.11 Mortar for AAC masonry. Thin-bed mortar for AAC 
masonry shall comply with Article 2.1 C.I ofTMS 602/ACI 
530.1/ASCE 6. Mortar used for the leveling courses of AAC 
masonry shall comply with Article 2.1 C.2 ofTMS 602/ACI 
530.1/ASCE 6. 

2103.12 Grout. Grout shall comply with Article 2.2 ofTMS 
602/ACI 530.1/ASCE 6. 

2103.13 Metal reinforcement and accessories. Metal rein- 
forcement and accessories shall conform to Article 2.4 ofTMS 
602/ACI 530.1/ASCE 6. Where unidentified reinforcement is 
approvedfor use, not less than three tension and three bending 
tests shall be made on representative specimens of the rein- 
forcement from each shipment and grade of reinforcing steel 
proposed for use in the work. 



SECTION 2104 
CONSTRUCTION 

2104.1 Masonry construction. Masonry construction shall 
comply with the requirements of Sections 2104.1.1 through 
2104.4 and with TMS 602/ACI 530.1/ASCE 6. 

2104.1.1 Tolerances. Masonry, except masonry veneer, 
shall be constructed within the tolerances specified in TMS 
602/ACI 530.1/ASCE 6. 

2104.1.2 Placing mortar and units. Placement of mortar, 
grout, and clay, concrete, glass, and AAC masonry units 
shall comply with TMS 602/ACI 530.1/ASCE 6. 



1 



2009 INTERNATIONAL BUILDING CODE® 



433 



MASONRY 



1 



1 



X 



2104.1.3 Installation of wall ties. Wall ties shall be 
installed in accordance with TMS 6021 ACl 530. 1 7ASCE 6. 

2104.1.4 Chases and recesses. Chases and recesses shall be 
constructed as masonry units are laid. Masonry directly 
above chases or recesses wider than 12 inches (305 mm) 
shall be supported on lintels . 

2104.1.5 Lintels. The design for lintels shall be in accor- 
dance with the masonry design provisions of either Section 
2107 or 2108. 

2104.1.6 Support on wood. Masonry shall not be sup- 
ported on wood girders or other forms of wood construction 
except as permitted in Section 2304.12. 

2104.2 Corbeled masonry. Corbeled masonry shall comply 
with the requirements of Section 1.12 of TMS 4021 ACl 
530/ASCE 5. 

2104.2.1 Molded cornices. Unless structural support and 
anchorage are provided to resist the overturning moment, 
the center of gravity of projecting masonry or molded cor- 
nices shall lie within the middle one-third of the supporting 
wall. Terra cotta and metal cornices shall be provided with a 
structural frame of approved noncombustible material 
anchored in an approved manner. 

2104.3 Cold weather construction. The cold weather con- 
struction provisions of TMS 6021 ACl 530.11ASCE 6, Article 
1.8 C, shall be implemented when the ambient temperature 
falls below 40°F (4°C). 

2104.4 Hot weather construction. The hot weather construc- 
tion provisions ofTMS 602/ ACl 530. 1/ASCE 6, Article 1.8 D, 
shall be implemented when the ambient air temperature 
exceeds 100°F (37.8°C), or90°F (32.2°C) with a wind velocity 
greater than 8 mph (12.9 km/hr). 



SECTION 2105 
QUALITY ASSURANCE 

2105.1 General. A quality assurance program shall be used to 
ensure that the constructed masonry is in compliance with the 
construction documents. 

The quality assurance program shall comply with the 
inspection and testing requirements of Chapter 17. 

2105.2 Acceptance relative to strength requirements. 

2105.2.1 Compliance with ['m and ['aac. Compressive 
strength of masonry shall be considered satisfactory if the 
compressive strength of each masonry wythe and grouted 
collar joint equals or exceeds the value of I'm for clay and 
concrete masonry and 7 'aac for AAC masonry. For partially 
grouted clay and concrete masonry, the compressive 
strength of both the grouted and ungrouted masonry shall 
equal or exceed the applicable I'm. At the time of prestress, 
the compressive strength of the masonry shall equal or 
exceed Tmi' which shall be less than or equal to I'm. 

2105.2.2 Determination of compressive strength. The 
compressive strength for each wythe shall be determined by 
the unit strength method or by the prism test method as spec- 
ified herein. 



2105.2.2.1 Unit strength method. 

2105.2.2.1.1 Clay masonry. The compressive 
strength of masonry shall be determined based on the 
strength of the units and the type of mortar specified 
using Table 2105.2.2.1.1, provided: 

1. Units are sampled and tested to verify compli- 
ancewithASTM C 62, ASTM C 216 or ASTM 
C652. 

2. Thickness of bedjoints does not exceed 5/ s inch 
(15.9 mm). 

3. For grouted masonry, the grout meets one of the 
following requirements: 

3.1. Grout conforms to Article 2.2 of TMS 
602/ACI 530.1/ASCE 6. 

3.2. Minimum grout compressive strength 
equals or exceeds I'm but not less than 
2,000 psi (13.79 MPa). The compressive 
strength of grout shall be determined in 
accordance with ASTM C 1019. 

TABLE 2105.2.2.1.1 
COMPRESSIVE STRENGTH OF CLAY MASONRY 



NET AREA COMPRESSIVE STRENGTH 
OF CLAY MASONRY UNITS (psi) 


NET AREA COMPRESSIVE 
STRENGTH OF MASONRY 

(psi) 


Type M or S mortar 


Type N mortar 


1,700 


2,100 


1,000 


3,350 


4,150 


1,500 


4,950 


6,200 


2,000 


6,600 


8,250 


2,500 


8,250 


10,300 


3,000 


9,900 




3,500 


11,500 


- 


4,000 



For 51 : 1 pound per square inch = 0.00689 MPa. 

2105.2.2.1.2 Concrete masonry. The compressive 
strength of masonry shall be determined based on the 
strength of the unit and type of mortar specified using 
Table 2105.2.2.1.2, provided: 

1. Units are sampled and tested to verify 
compliance with ASTM C 55 or ASTM C 90. 

2. Thickness of bedjoints does not exceed 5/yinch 
(15.9 mm). 

3. For grouted masonry, the grout meets one of the 
following requirements: 

3.1. Grout conforms to Article 2.2 of TMS 
602/ACI 530.1/ASCE 6. 

3.2. Minimum grout compressive strength 
equals or exceeds I'm but not less than 
2,000 psi (13.79 MPa). The compres- 
sive strength of grout shall be deter- 
mined in accordance with ASTM C 
1019. 



i 



434 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



TABLE 2105.2.2.1.2 
COMPRESSIVE STRENGTH OF CONCRETE MASONRY 



NET AREA COMPRESSIVE STRENGTH OF 
CONCRETE MASONRY UNITS (psi) 


NET AREA 
COMPRESSIVE 
STRENGTH OF 
MASONRY (psi)a 


Type M or S mortar 


Type N mortar 


1,250 


1,300 


1,000 


1,900 


2,150 


1,500 


2,800 


3,050 


2,000 


3,750 


4,050 


2,500 


4,800 


5,250 


3,000 



For 51 : 1 inch = 25.4 mm, 1 pound per square inch = 0.00689 MPa. 
a. For units less than 4 inches in height, 85 percent of the values listed. 

2105.2.2.1.3 AAC masonry. The compressive 
strength of AAC masonry shall be based on the 
strength of the AAC masonry unit only and the fol- 
lowing shall be met: 

1. Units conform to ASTM C 1386. 

2. Thickness of bedjoints does not exceed Us inch 
(3.2 mm). 

3. For grouted masonry, the grout meets one of the 
following requirements : 

3.1. Grout conforms to Article 2.2 of TMS 
602/ACI 530.1/ASCE 6. 

3.2. Minimum grout compressive strength 
equals or exceeds f AAcbut not less than 
2,000 psi (13.79 MPa). The compres- 
sive strength of grout shall be deter- 
mined in accordance with ASTM C 
1019. 

2105.2.2.2 Prism test method. 

2105.2.2.2.1 General. The compressive strength of 
clay and concrete masonry shall be determined by the 
prism test method: 

1. Where specified in the construction documents. 

2. Where masonry does not meet the requirements 
for application of the unit strength method in 
Section 2105.2.2.1. 

2105.2.2.2.2 Number of prisms per test. A prism 
test shall consist of three prisms constructed and 
tested in accordance with ASTM C 1314. 

2105.3 Testing prisms from constructed masonry. When 
approvedby the bUilding official, acceptance of masonry that 
does not meet the requirements of Section 2105.2.2.1 or 
2105.2.2.2 shall be permitted to be based on tests of prisms cut 
from the masonry construction in accordance with Sections 
2105.3.1, 2105.3.2 and 2105.3.3. 

2105.3.1 Prism sampling and removal. A set of three 
masonry prisms that are at least 28 days old shall be saw cut 
from the masonry for each 5,000 square feet (465 m 2 ) of the 
wall area that is in question but not less than one set of three 
masonry prisms for the project. The length, width and 
height dimensions of the prisms shall comply with the 



requirements of ASTM C 1314. Transporting, preparation 
and testing of prisms shall be in accordance with ASTM C 
1314. 

2105.3.2 Compressive strength calculations. The com- 
pressive strength of prisms shall be the value calculated in 
accordance ASTM C 1314, except that the net cross-sec- 
tional area of the prism shall be based on the net mortar bed- 
ded area. 

2105.3.3 Compliance. Compliance with the requirement 
for the specified compressive strength of masonry, fm, shall 
be considered satisfied provided the modified compressive 
strength equals or exceeds the specified fm. Additional test- 
ing of specimens cut from locations in question shall be per- 
mitted. 



SECTION 2106 
SEISMIC DESIGN 

2106.1 Seismic design requirements for masonry. Masonry 
structures and components shall comply with the requirements 
in Section 1.17 of TMS 402/ACI 530/ASCE 5 depending on 
the structure's seismic design category as determined in Sec- 
tion 1613. 



SECTION 2107 
ALLOWABLE STRESS DESIGN 

2107.1 General. The design of masonry structures using 
allowable stress design shall comply with Section 2106 and the 
requirements of Chapters 1 and 2 ofTMS 402/ACI 530/ASCE 
5 except as modified by Sections 2107.2 through 2107.5. 

2107.2 TMS 402/ACI 530/ASCE 5, Section 2.1.2, load com- 
binations. Delete Section 2.1.2.1. 

2107.3 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7.1.1, lap 
splices. Modify Section 2.1.9.7.1.1 as follows: 

2.1.7.1.1 The minimum length of lap splices for reinforcing 
bars in tension or compression, Id' shall be 



ld= 0.002d b f s 



(Equation 21-1) 



0.29d b f s 



For SI: Id-- 

but not less than 12 inches (305 mm). In no case shall the 
length of the lapped splice be less than 40 bar diameters. 

where: 

db = Diameter of reinforcement, inches (mm). 

f s = Computed stress in reinforcement due to design 
loads, psi (MPa). 

In regions of moment where the design tensile stresses in 
the reinforcement are greater than 80 percent of the allow- 
able steel tension stress, F s , the lap length of splices shall be 
increased not less than 50 percent of the minimum required 
length. Other equivalent means of stress transfer to accom- 
plish the same 50 percent increase shall be permitted. Where 
epoxy coated bars are used, lap length shall be increased by 
50 percent. 



2009 INTERNATIONAL BUILDING CODE® 



435 



MASONRY 



2107.4 TMS 402/ACI 530/ASCE 5, Section 2.1.9.7, splices 
of reinforcement. Modify Section 2.1.9.7 as follows: 

2.1.9.7 Splices of reinforcement. Lap splices, welded 
splices or mechanical splices are permitted in accordance 
with the provisions of this section. All welding shall conform 
to AWS D1.4. Welded splices shall be of ASTM A706 steel 
reinforcement. Reinforcement larger than No. 9 (M #29) 
shall be spliced using mechanical connections in accordance 
with Section 2.1.9.7.3. 

2107.5 TMS 402/ACI 530/ASCE 5, Section 2.3.6, maximum 
bar size. Add the following to Chapter 2: 

2.3.6 Maximum bar size. The bar diameter shall not exceed 
one-eighth of the nominal wall thickness and shall not 
exceed one-quarter of the least dimension of the cell, course 
or collar joint in which it is placed. 



SECTION 2108 
STRENGTH DESIGN OF MASONRY 

2108.1 General. The design of masonry structures using 
strength design shall comply with Section 2106 and the 
requirements of Chapters 1 and 3 ofTMS 402/ACI 530/ASCE 
5, except as modified by Sections 2108.2 through 2108.3. 

Exception: AAC masonry shall comply with the require- 
ments of Chapter 1 and Appendix A of TMS 4021 ACl 
530/ASCE 5. 

2108.2 TMS 402/ACI 530/ASCE 5, Section 3.3.3.3 develop- 
ment. Modify the second paragraph of Section 3.3.3.3 as follows: 

The required development length of reinforcement shall 
be determined by Equation (3-16), but shall not be less than 
12 inches (305 mm) and need not be greater than 72 db. 

2108.3 TMS 402/ACI 530/ASCE 5, Section 3.3.3.4, splices. 
Modify items (b) and (c) of Section 3.3.3.4 as follows: 

3.3.3.4 (b). A welded splice shall have the bars butted and 
welded to develop at least 125 percent of the yield strength, 
f , of the bar in tension or compression, as required. Welded 
splices shall be of ASTM A 706 steel reinforcement. 
Welded splices shall not be permitted in plastic hinge zones 
of intermediate or special reinforced walls or special 
moment frames of masonry. 

3.3.3.4 (c). Mechanical splices shall be classified as Type 1 
or 2 according to Section 21.2.6.1 of ACI 318. Type 1 
mechanical splices shall not be used within a plastic hinge 
zone or within a beam-columnjoint of intermediate or spe- 
cial reinforced masonry shear walls or special moment 
frames. Type 2 mechanical splices are permitted in any loca- 
tion within a member. 



SECTION 2109 
EMPIRICAL DESIGN OF MASONRY 

2109.1 General. Empirically designed masonry shall conform 
to the requirements of Chapter 5 of TMS 4021 ACl 5301 ASCE 
5, except where otherwise noted in this section. 

2109.1.1 Limitations. The use of empirical design of 
masonry shall be limited as noted in Section 5.1.2 of TMS 



402/ACI 530/ASCE 5. The use of dry-stacked, surface- 
bonded masonry shall be prohibited in Occupancy Category 
IV structures. In buildings that exceed one or more of the 
limitations of Section 5.1.2 of TMS 4021 ACl 5301 ASCE 5, 
masonry shall be designed in accordance with the engi- 
neered design provisions of Section 2101.2.1, 2101.2.2 or 
2101.2.3 or the foundation wall provisions of Section 
1807.1.5. 

2109.2 Surface-bonded walls. Dry-stacked, surface-bonded 
concrete masonry walls shall comply with the requirements of 
Chapter 5 of TMS 402/ACI 530/ASCE 5, except where other- 
wise noted in this section. 

2109.2.1 Strength. Dry-stacked, surface-bonded concrete 
masonry walls shall be of adequate strength and proportions 
to support all superimposed loads without exceeding the 
allowable stresses listed in Table 2109.2.1. Allowable 
stresses not specified in Table 2109.2.1 shall comply with 
the requirements ofTMS 402/ACI 530/ASCE 5. 

TABLE 2109.2.1 

ALLOWABLE STRESS GROSS CROSS-SECTIONAL 

AREA FOR DRY-STACKED, SURFACE-BONDED 

CONCRETE MASONRY WALLS 



DESCRIPTION 


MAXIMUM ALLOWABLE STRESS 
(psi) 


Compression standard block 


45 


Flexural tension 
Horizontal span 
Vertical span 


30 
18 


Shear 


10 



For 51 : 1 pound per square inch = 0.006895 MPa. 

2109.2.2 Construction. Construction of dry- stacked, sur- 
face-bonded masonry walls, including stacking and level- 
ing of units, mixing and application of mortar and curing 
and protection shall comply with ASTM C 946. 

2109.3 Adobe construction. Adobe construction shall comply 
with this section and shall be subject to the requirements of this 
code for Type V construction, Chapter 5 of TMS 4021 ACl 
5301 ASCE 5, and this section. 

2109.3.1 Unstabilized adobe. 

2109.3.1.1 Compressive strength. Adobe units shall 
have an average compressive strength of 300 psi (2068 
kPa) when tested in accordance with ASTM C 67. Five 
samples shall be tested and no individual unit is permit- 
ted to have a compressive strength of less than 250 psi 
(1724 kPa). 

2109.3.1.2 Modulus of rupture. Adobe units shall have 
an average modulus of rupture of 50 psi (345 kPa) when 
tested in accordance with the following procedure. Five 
samples shall be tested and no individual unit shall have a 
modulus of rupture of less than 35 psi (241 kPa). 

2109.3.1.2.1 Support conditions. A cured unit shall 
be simply supported by 2-inch-diameter (51 mm) 
cylindrical supports located 2 inches (51 mm) in from 
each end and extending the full width of the unit. 



436 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



2109.3.1.2.2 Loading conditions. A 2-inch-diameter 
(51 mm) cylinder shall be placed at midspan parallel 
to the supports. 

2109.3.1.2.3 Testing procedure. A vertical load shall 
be applied to the cylinder at the rate of 500 pounds per 
minute (37 N/s) until failure occurs. 

2109.3.1.2.4 Modulus of rupture determination. 
The modulus of rupture shall be determined by the 
equation: 



TABLE 2109.3.3.1 
ALLOWABLE SHEAR ON BOLTS IN ADOBE MASONRY 



f=ZPL s l2S w {S?) 



(Equation 21-2) 



where, for the purposes of this section only: 

Sw= Width of the test specimen measured parallel to 
the loading cylinder, inches (mm). 

f r - Modulus of rupture, psi (MPa). 

Is = Distance between supports, inches (mm). 

St = Thickness of the test specimen measured paral- 
lel to the direction of load, inches (mm). 

P = The applied load at failure, pounds (N). 

2109.3.1.3 Moisture content requirements. Adobe 
units shall have a moisture content not exceeding 4 per- 
cent by weight. 

2109.3.1.4 Shrinkage cracks. Adobe units shall not 
contain more than three shrinkage cracks and any single 
shrinkage crack shall not exceed 3 inches (76 mm) in 
length or lis inch (3.2 mm) in width. 

2109.3.2 Stabilized adobe. 

2109.3.2.1 Material requirements. Stabilized adobe 
shall comply with the material requirements of 
unstabilized adobe in addition to Sections 2109.3.2.1.1 
and 2109.3.2.1.2. 

2109.3.2.1.1 Soil requirements. Soil used for stabi- 
lized adobe units shall be chemically compatible with 
the stabilizing material. 

2109.3.2.1.2 Absorption requirements. A 4-inch 
(102 mm) cube, cut from a stabilized adobe unit dried 
to a constant weight in a ventilated oven at 212°F to 
239°F (100°C to 115°C), shall not absorb more than 
V\ percent moisture by weight when placed upon a 
constantly water-saturated, porous surface for seven 
days. A minimum of five specimens shall be tested 
and each specimen shall be cut from a separate unit. 

2109.3.3 Allowable stress. The allowable compressive 
stress based on gross cross-sectional area of adobe shall not 
exceed 30 psi (207 kPa). 

2109.3.3.1 Bolts. Bolt values shall not exceed those set 
forth in Table 2109.3.3.1. 

2109.3.4 Construction. 

2109.3.4.1 General. Adobe construction shall be limited 
as stated in Sections 2109.3.4.1.1 through 2109.3.4.1.4. 

2109.3.4.1.1 Height restrictions. Adobe construc- 
tion shall be limited to buildings not exceeding one 



DIAMETER OF BOLTS 
(inches) 


MINIMUM EMBEDMENT 
(inches) 


SHEAR 

(pounds) 


i/ , 


. 


. 


5/, 


12 


200 


3/ 4 


15 


300 


7/ S 


18 


400 


1 


21 


500 


l'/ S 


24 


600 



For 51 : 1 inch = 25.4 mm, 1 pound = 4.448 N. 

story, except that two-story construction is allowed 
when designed by a registered design professional. 

2109.3.4.1.2 Mortar restrictions. Mortar for stabi- 
lized adobe units shall comply with Chapter 21 or 
adobe soil. Adobe soil used as mortar shall comply 
with material requirements for stabilized adobe. Mor- 
tar for unstabilized adobe shall be portland cement 
mortar. 

2109.3.4.1.3 Mortarjoints. Adobe units shall be laid 
with full head and bedjoints and in full running bond. 

2109.3.4.1.4 Parapet walls. Parapet walls con- 
structed of adobe units shall be waterproofed. 

2109.3.4.2 Wall thickness. The minimum thickness of 
exterior walls in one- story buildings shall be 10 inches 
(254 mm). The walls shall be laterally supported at inter- 
vals not exceeding 24 feet (7315 mm). The minimum 
thickness of interior load-bearing walls shall be 8 inches 
(203 mm). In no case shall the unsupported height of any 
wall constructed of adobe units exceed 10 times the 
thickness of such wall. 

2109.3.4.3 Foundations. Foundations for adobe con- 
struction shall be in accordance with Sections 
2109.3.4.3.1 and 2109.3.4.3.2. 

2109.3.4.3.1 Foundation support. Walls and parti- 
tions constructed of adobe units shall be supported by 
foundations or footings that extend not less than 6 
inches (152 mm) above adjacent ground surfaces and 
are constructed of solid masonry (excluding adobe) or 
concrete. Footings and foundations shall comply with 
Chapter 18. 

2109.3.4.3.2 Lower course requirements. Stabi- 
lized adobe units shall be used in adobe walls for the 
first 4 inches (102 mm) above the finished first-floor 
elevation. 

2109.3.4.4 Isolated piers or columns. Adobe units shall 
not be used for isolated piers or columns in a load-bear- 
ing capacity. Walls less than 24 inches (610 mm) in 
length shall be considered isolated piers or columns. 

2109.3.4.5 Tie beams. Exterior walls and interior 
load-bearing walls constructed of adobe units shall have 
a continuous tie beam at the level of the floor or roof 
bearing and meeting the following requirements. 



2009 INTERNATIONAL BUILDING CODE® 



437 



MASONRY 



2109.3.4.5.1 Concrete tie beams. Concrete tie 
beams shall be a minimum depth of 6 inches (152 
mm) and a minimum width of 10 inches (254 mm). 
Concrete tie beams shall be continuously reinforced 
with a minimum of two No. 4 reinforcing bars. The 
specifed compressive strength of concrete shall be at 
least 2,500 psi (17.2 MPa). 

2109.3.4.5.2 Wood tie beams. Wood tie beams shall be 
solid or built up of lumber having a minimum nominal 
thickness of 1 inch (25 mm), and shall have a minimum 
depth of 6 inches (152 mm) and a minimum width of 10 
inches (254 mm). Joints in wood tie beams shall be 
spliced a minimum of 6 inches (152 mm). No splices 
shall be allowed within 12 inches (305 mm) of an open- 
ing. Wood used in tie beams shall be approvednatmaMy 
decay-resistant or preservative-treated wood. 

2109.3.4.6 Exterior finish. Exterior walls constructed 
of unstabilized adobe units shall have their exterior sur- 
face covered with a minimum of two coats of portland 
cement plaster having a minimum thickness of 31 4 inch 
(19.1 mm) and conforming to ASTM C 926. Lathing 
shall comply with ASTM C 1063. Fasteners shall be 
spaced at 16 inches (406 mm) o.c. maximum. Exposed 
wood surfaces shall be treated with an approved wood 
preservative or other protective coating prior to lath 
application. 

2109.3.4.7 Lintels. Lintels shall be considered structural 
members and shall be designed in accordance with the 
applicable provisions of Chapter 16. 



SECTION 2110 
GLASS UNIT MASONRY 

2110.1 General. Glass unit masonry construction shall comply 
with Chapter 7 ofTMS 4021 ACI 5301 ASCE 5 and this section. 

2110.1.1 Limitations. Solid or hollow approved glass 
block shall not be used in fire walls, party walls, fire barri- 
ers, fire partitions or smoke barriers, or for load-bearing 
construction. Such blocks shall be erected with mortar and 
reinforcement in metal channel-type frames, structural 
frames, masonry or concrete recesses, embedded panel 
anchors as provided for both exterior and interior walls or 
other approvedjoint materials. Wood strip framing shall not 
be used in walls required to have a fire-resistance rating by 
other provisions of this code. 

Exceptions: 

1. Glass-block assemblies having a fire protection 
rating of not less than ]\ 4 hour shall be permitted as 
opening protectives in accordance with Section 
715 in fire barriers, fire partitions and smoke barri- 
ers that have a required fire-resistance rating of 1 
hour or less and do not enclose exit stairways, exit 
ramps or exit passageways. 

2. Glass-block assemblies as permitted in Section 
404.6, Exception 2. 



SECTION 2111 
MASONRY FIREPLACES 

2111.1 Definition. A masonry fireplace is a fireplace con- 
structed of concrete or masonry. Masonry fireplaces shall be 
constructed in accordance with this section. 

2111.2 Footings and foundations. Footings for masonry fire- 
places and their chimneys shall be constructed of concrete or 
solid masonry at least 12 inches (305 mm) thick and shall 
extend at least 6 inches (153 mm) beyond the face of the fire- 
place or foundation wall on all sides. Footings shall be founded 
on natural undisturbed earth or engineered fill below frost 
depth. In areas not subjected to freezing, footings shall be at 
least 12 inches (305 mm) below finished grade. 

2111.2.1 Ash dump cleanout. Cleanout openings, located 
within foundation walls below fireboxes, when provided, 
shall be equipped with ferrous metal or masonry doors and 
frames constructed to remain tightly closed, except when in 
use. Cleanouts shall be accessible and located so that ash 
removal will not create a hazard to combustible materials. 

2111.3 Seismic reinforcing. Masonry or concrete fireplaces 
shall be constructed, anchored, supported and reinforced as 
required in this chapter. In Seismic Design Category C or D, 
masonry and concrete fireplaces shall be reinforced and 
anchored as detailed in Sections 2111.3.1, 2111.3.2, 2111.4 
and 2111.4.1 for chimneys serving fireplaces. In Seismic 
Design Category A or B, reinforcement and seismic anchorage 
is not required. In Seismic Design Category E or F, masonry 
and concrete chimneys shall be reinforced in accordance with 
the requirements of Sections 2101 through 2108. 

2111.3.1 Vertical reinforcing. For fireplaces with chim- 
neys up to 40 inches (1016 mm) wide, four No. 4 continuous 
vertical bars, anchored in the foundation, shall be placed in 
the concrete between wythes of solid masonry or within the 
cells of hollow unit masonry and grouted in accordance with 
Section 2103.12. For fireplaces with chimneys greater than 
40 inches (1016 mm) wide, two additional No. 4 vertical 
bars shall be provided for each additional 40 inches (1016 
mm) in width or fraction thereof. 

2111.3.2 Horizontal reinforcing. Vertical reinforcement 
shall be placed enclosed within 1/4-inch (6.4 mm) ties or 
other reinforcing of equivalent net cross-sectional area, 
spaced not to exceed 18 inches (457 mm) on center in con- 
crete; or placed in the bedjoints of unit masonry at a mini- 
mum of every 18 inches (457 mm) of vertical height. Two 
such ties shall be provided at each bend in the vertical bars. 

2111.4 Seismic anchorage. Masonry and concrete chimneys 
in Seismic Design Category C or D shall be anchored at each 
floor, ceiling or roof line more than 6 feet (1829 mm) above 
grade, except where constructed completely within the exterior 
walls. Anchorage shall conform to the following requirements. 

2111.4.1 Anchorage. Two 3/i6-inch by I-inch (4.8 mm by 
25.4 mm) straps shall be embedded a minimum of 12 inches 
(305 mm) into the chimney. Straps shall be hooked around 
the outer bars and extend 6 inches (152 mm) beyond the 
bend. Each strap shall be fastened to a minimum of four 
floor joists with two liz-inch (12.7 mm) bolts. 



438 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



2111.5 Firebox walls. Masonry fireboxes shall be constructed 
of solid masonry units, hollow masonry units grouted solid, 
stone or concrete. When a lining of firebrick at least 2 inches 
(51 mm) in thickness or other approv ediming is provided, the 
minimum thickness of back and sidewalls shall each be 8 
inches (203 mm) of solid masonry, including the lining. The 
width of joints between firebricks shall not be greater than i/ 4 
inch (6.4 mm). When no lining is provided, the total minimum 
thickness of back and sidewalls shall be 10 inches (254 mm) of 
solid masonry. Firebrick shall conform to ASTM C 27 or 
ASTM C 1261 and shall be laid with medium-duty refractory 
mortar conforming to ASTM C 199. 

2111.5.1 Steel fireplace units. Steel fireplace units are per- 
mitted to be installed with solid masonry to form a masonry 
fireplace provided they are installed according to either the 
requirements of their listing or the requirements of this sec- 
tion. Steel fireplace units incorporating a steel firebox lining 
shall be constructed with steel not less than i/ 4 inch (6.4 mm) 
in thickness, and an air-circulating chamber which is ducted 
to the interior of the building. The firebox lining shall be 
encased with solid masonry to provide a total thickness at the 
back and sides of not less than 8 inches (203 mm), of which 
not less than 4 inches (102 mm) shall be of solid masonry or 
concrete. Circulating air ducts employed with steel fireplace 
units shall be constructed of metal or masonry. 

2111.6 Firebox dimensions. The firebox of a concrete or 
masonry fireplace shall have a minimum depth of 20 inches 
(508 mm). The throat shall not be less than 8 inches (203 mm) 
above the fireplace opening. The throat opening shall not be 
less than 4 inches (102 mm) in depth. The cross-sectional area 
of the passageway above the firebox, including the throat, 
damper and smoke chamber, shall not be less than the 
cross-sectional area of the flue. 

Exception: Rumford fireplaces shall be permitted provided 
that the depth of the fireplace is at least 12 inches (305 mm) and 
at least one- third of the width of the fireplace opening, and the 
throat is at least 12 inches (305 mm) above the lintel, and at 
least i/ 20 the cross-sectional area of the fireplace opening. 

2111.7 Lintel and throat. Masonry over a fireplace opening 
shall be supported by a lintel of noncombustible material. The 
minimum required bearing length on each end of the fireplace 
opening shall be 4 inches (102 mm) . The fireplace throat or 
damper shall be located a minimum of 8 inches (203 mm) 
above the top of the fireplace opening. 

2111.7.1 Damper. Masonry fireplaces shall be equipped 
with a ferrous metal damper located at least 8 inches (203 
mm) above the top of the fireplace opening. Dampers shall 
be installed in the fireplace or at the top of the flue venting 
the fireplace, and shall be operable from the room contain- 
ing the fireplace. Damper controls shall be permitted to be 
located in the fireplace. 

2111.8 Smoke chamber walls. Smoke chamber walls shall be 
constructed of solid masonry units, hollow masonry units 
grouted solid, stone or concrete. The total minimum thickness 
of front, back and sidewalls shall be 8 inches (203 mm) of solid 
masonry. The inside surface shall be parged smooth with 
refractory mortar conforming to ASTM C 199. When a lining 
of firebrick at least 2 inches (51 mm) thick, or a lining of vitri- 



fied clay at least 5/yinch (15.9 mm) thick, is provided, the total 
minimum thickness of front, back and sidewalls shall be 6 
inches (152 mm) of solid masonry, including the lining. Fire- 
brick shall conform to ASTM C 1261 and shall be laid with 
refractory mortar conforming to ASTM C 199. Vitrified clay 
linings shall conform to ASTM C 315. 

2111.8.1 Smoke chamber dimensions. The inside height of 
the smoke chamber from the fireplace throat to the beginning 
of the flue shall not be greater than the inside width of the fire- 
place opening. The inside surface of the smoke chamber shall 
not be inclined more than 45 degrees (0.76 rad) from vertical 
when prefabricated smoke chamber linings are used or when 
the smoke chamber walls are rolled or sloped rather than 
corbeled. When the inside surface of the smoke chamber is 
formed by corbeled masonry, the walls shall not be corbeled 
more than 30 degrees (0.52 rad) from vertical. 

2111.9 Hearth and hearth extension. Masonry fireplace 
hearths and hearth extensions shall be constructed of concrete 
or masonry, supported by noncombustible materials, and rein- 
forced to carry their own weight and all imposed loads. No 
combustible material shall remain against the underside of 
hearths or hearth extensions after construction. 

2111.9.1 Hearth thickness. The minimum thickness of 
fireplace hearths shall be 4 inches (102 mm). 

2111.9.2 Hearth extension thickness. The minimum 
thickness of hearth extensions shall be 2 inches (51 mm). 

Exception: When the bottom of the firebox opening is 
raised at least 8 inches (203 mm) above the top of the 
hearth extension, a hearth extension of not less than 
3/ s -inch-thick (9.5 mm) brick, concrete, stone, tile or 
other approved noncombustible material is permitted. 

2111.10 Hearth extension dimensions. Hearth extensions 
shall extend at least 16 inches (406 mm) in front of, and at least 
8 inches (203 mm) beyond, each side of the fireplace opening. 
Where the fireplace opening is 6 square feet (0.557 m 2 ) or 
larger, the hearth extension shall extend at least 20 inches (508 
mm) in front of, and at least 12 inches (305 mm) beyond, each 
side of the fireplace opening. 

2111.11 Fireplace clearance. Any portion of a masonry fire- 
place located in the interior of a building or within the exterior 
wall of a building shall have a clearance to combustibles of not 
less than 2 inches (51 mm) from the front faces and sides of 
masonry fireplaces and not less than 4 inches (102 mm) from the 
back faces of masonry fireplaces. The airspace shall not be filled, 
except to provide fireblocking in accordance with Section 
2111.12. 

Exceptions: 

1. Masonry fireplaces listedand labeled for use in contact 
with combustibles in accordance with UL 127 and 
installed in accordance with the manufacturer's instal- 
lation instructions are permitted to have combustible 
material in contact with their exterior surfaces. 

2. When masonry fireplaces are constructed as part of 
masonry or concrete walls, combustible materials 
shall not be in contact with the masonry or concrete 



2009 INTERNATIONAL BUILDING CODE® 



439 



MASONRY 



walls less than 12 inches (306 mm) from the inside 
surface of the nearest firebox lining. 

Exposed combustible trim and the edges of sheathing 
materials, such as wood siding, flooring and drywall, 
are permitted to abut the masonry fireplace sidewalls 
and hearth extension, in accordance with Figure 
2111.11, provided such combustible trim or sheath- 
ing is a minimum of 12 inches (306 mm) from the 
inside surface of the nearest firebox lining. 

Exposed combustible mantels or trim is permitted to be 
placed directly on the masonry fireplace front sur- 
rounding the fireplace opening, provided such com- 
bustible materials shall not be placed within 6 inches 
(153 mm) of a fireplace opening. Combustible material 
directly above and within 12 inches (305 mm) of the 
fireplace opening shall not project more than i/ 8 inch 
(3.2 mm) for each I-inch (25 mm) distance from such 
opening. Combustible materials located along the 
sides of the fireplace opening that project more than 
V/ 2 inches (38 mm) from the face of the fireplace shall 
have an additional clearance equal to the projection. 



COMBUSTIOLE 5HCAFHNG 
EDGt MUniNG h¥EQHm 




g- CLEARANCE |*JF&=*GE.| 
-^TOCOMftj STieU FRAMNS 



FRAME WAJ 



For 51 : 1 inch = 25.4 mm 

FIGURE 2111.11 

ILLUSTRATION OF EXCEPTION TO 

FIREPLACE CLEARANCE PROVISION 

2111.12 Fireplace fireblocking. All spaces between fireplaces 
and floors and ceilings through which fireplaces pass shall be 
fireblocked with noncombustible material securely fastened in 
place. The fireblocking of spaces between woodjoists, beams or 
headers shall be to a depth of 1 inch (25 mm) and shall only be 
placed on strips of metal or metal lath laid across the spaces 
between combustible material and the chimney. 

2111.13 Exterior air. Factory-built or masonry fireplaces cov- 
ered in this section shall be equipped with an exterior air supply 
to ensure proper fuel combustion unless the room is mechani- 
cally ventilated and controlled so that the indoor pressure is 
neutral or positive. 

2111.13.1 Factory-built fireplaces. Exterior combustion 
air ducts for factory-built fireplaces shall be listed compo- 
nents of the fireplace, and installed according to the fire- 
place manufacturer's instructions. 

2111.13.2 Masonry fireplaces. Listedcombustion air ducts 
for masonry fireplaces shall be installed according to the 
terms of their listing and manufacturer's instructions. 



2111.13.3 Exterior air intake. The exterior air intake shall 
be capable of providing all combustion air from the exterior 
of the dwelling. The exterior air intake shall not be located 
within a garage, attic, basement or crawl space of the dwell- 
ing nor shall the air intake be located at an elevation higher 
than the firebox. The exterior air intake shall be covered 
with a corrosion-resistant screen of 1/4-inch (6.4 mm) mesh. 

2111.13.4 Clearance. Unlisted combustion air ducts shall 
be installed with a minimum I-inch (25 mm) clearance to 
combustibles for all parts of the duct within 5 feet (1524 
mm) of the duct outlet. 

2111.13.5 Passageway. The combustion air passageway 
shall be a minimum of 6 square inches (3870 mm 2 ) and not 
more than 55 square inches (0.035 m 2 ), except that combus- 
tion air systems for listed fireplaces or for fireplaces tested 
for emissions shall be constructed according to the fireplace 
manufacturer's instructions. 

2111.13.6 Outlet. The exterior air outlet is permitted to be 
located in the back or sides of the firebox chamber or within 
24 inches (610 mm) of the firebox opening on or near the 
floor. The outlet shall be closable and designed to prevent 
burning material from dropping into concealed combustible 
spaces. 



SECTION 2112 
MASONRY HEATERS 

2112.1 Definition. A masonry heater is a heating appliance 
constructed of concrete or solid masonry, hereinafter referred 
to as "masonry," which is designed to absorb and store heat 
from a solid fuel fire built in the firebox by routing the exhaust 
gases through internal heat exchange channels in which the 
flow path downstream of the firebox may include flow in a hor- 
izontal or downward direction before entering the chimney and 
which delivers heat by radiation from the masonry surface of 
the heater. 

21 12.2 Installation. Masonry heaters shall be installed in accor- 
dance with this section and comply with one of the following: 

1. Masonry heaters shall comply with the requirements of 
ASTM E 1602; or 

2. Masonry heaters shall be listed and labeled in accor- 
dance with UL 1482 and installed in accordance with the 
manufacturer's installation instructions. 

2112.3 Footings and foundation. The firebox floor of a 
masonry heater shall be a minimum thickness of 4 inches (102 
mm) of noncombustible material and be supported on a 
noncombustible footing and foundation in accordance with 
Section 2113.2. 

2112.4 Seismic reinforcing. In Seismic Design Category D, E 
and F, masonry heaters shall be anchored to the masonry foun- 
dation in accordance with Section 2113.3. Seismic reinforcing 
shall not be required within the body of a masonry heater with a 
height that is equal to or less than 3.5 times its body width and 
where the masonry chimney serving the heater is not supported 
by the body of the heater. Where the masonry chimney shares a 
common wall with the facing of the masonry heater, the chim- 



440 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



ney portion of the structure shall be reinforced in accordance 
with Section 2113. 

2112.5 Masonry heater clearance. Combustible materials 
shall not be placed within 36 inches (765 mm) of the outside 
surface of a masonry heater in accordance with NFPA 211, 
Section 8-7 (clearances for solid fuel-burning appliances), and 
the required space between the heater and combustible material 
shall be fully vented to permit the free flow of air around all 
heater surfaces. 

Exceptions: 

1. When the masonry heater wall thickness is at least 8 
inches (203 mm) thick of solid masonry and the wall 
thickness of the heat exchange channels is at least 5 
inches (127 mm) thick of solid masonry, combustible 
materials shall not be placed within 4 inches (102 
mm) of the outside surface of a masonry heater. A 
clearance of at least 8 inches (203 mm) shall be pro- 
vided between the gas-tight capping slab of the heater 
and a combustible ceiling. 

2. Masonry heaters listed and labeled in accordance 
with UL 1482 and installed in accordance with the 
manufacturer's instructions. 



SECTION 2113 
MASONRY CHIMNEYS 

2113.1 Definition. A masonry chimney is a chimney con- 
structed of concrete or masonry, hereinafter referred to as 
"masonry." Masonry chimneys shall be constructed, anchored, 
supported and reinforced as required in this chapter. 

2113.2 Footings and foundations. Footings for masonry 
chimneys shall be constructed of concrete or solid masonry at 
least 12 inches (305 mm) thick and shall extend at least 6 inches 
(152 mm) beyond the face of the foundation or support wall on 
all sides. Footings shall be founded on natural undisturbed 
earth or engineered fill below frost depth. In areas not subjected 
to freezing, footings shall be at least 12 inches (305 mm) below 
finished grade. 

2113.3 Seismic reinforcing. Masonry or concrete chimneys 
shall be constructed, anchored, supported and reinforced as 
required in this chapter. In Seismic Design Category C or D, 
masonry and concrete chimneys shall be reinforced and 
anchored as detailed in Sections 2113.3.1, 2113.3.2 and 
2113.4. In Seismic Design Category A or B, reinforcement and 
seismic anchorage is not required. In Seismic Design Category 
E or F, masonry and concrete chimneys shall be reinforced in 
accordance with the requirements of Sections 2101 through 
2108. 

2113.3.1 Vertical reinforcing. For chimneys up to 40 
inches (1016 mm) wide, four No. 4 continuous vertical bars 
anchored in the foundation shall be placed in the concrete 
between wythes of solid masonry or within the cells of hol- 
low unit masonry and grouted in accordance with Section 
2103.12. Grout shall be prevented from bonding with the 
flue liner so that the flue liner is free to move with thermal 



expansion. For chimneys greater than 40 inches (1016 mm) 
wide, two additional No. 4 vertical bars shall be provided for 
each additional 40 inches (1016 mm) in width or fraction 
thereof. 

2113.3.2 Horizontal reinforcing. Vertical reinforcement 
shall be placed enclosed within i/ 4 -inch (6.4 mm) ties, or 
other reinforcing of equivalent net cross-sectional area, 
spaced not to exceed 18 inches (457 mm) o.c. in concrete, or 
placed in the bed joints of unit masonry, at a minimum of 
every 18 inches (457 mm) of vertical height. Two such ties 
shall be provided at each bend in the vertical bars. 

2113.4 Seismic anchorage. Masonry and concrete chimneys 
and foundations in Seismic Design Category C or D shall be 
anchored at each floor, ceiling or roof line more than 6 feet 
(1829 mm) above grade, except where constructed completely 
within the exterior walls. Anchorage shall conform to the fol- 
lowing requirements. 

2113.4.1 Anchorage. Two 3/ 16 -inch by I-inch (4.8 mm by 
25 mm) straps shall be embedded a minimum of 12 inches 
(305 mm) into the chimney. Straps shall be hooked around 
the outer bars and extend 6 inches (152 mm) beyond the 
bend. Each strap shall be fastened to a minimum of four 
floor joists with two i/ 2 -inch (12.7 mm) bolts. 

2113.5 Corbeling. Masonry chimneys shall not be corbeled 
more than half of the chimney's wall thickness from a wall or 
foundation, nor shall a chimney be corbeled from a wall or 
foundation that is less than 12 inches (305 mm) in thickness 
unless it projects equally on each side of the wall, except that on 
the second story of a two-story dwelling, corbeling of chim- 
neys on the exterior of the enclosing walls is permitted to equal 
the wall thickness. The projection of a single course shall not 
exceed one-half the unit height or one-third of the unit bed 
depth, whichever is less. 

2113.6 Changes in dimension. The chimney wall or chimney 
flue lining shall not change in size or shape within 6 inches 
(152 mm) above or below where the chimney passes through 
floor components, ceiling components or roof components. 

2113.7 Offsets. Where a masonry chimney is constructed with 
a fireclay flue liner surrounded by one wythe of masonry, the 
maximum offset shall be such that the centerline of the flue 
above the offset does not extend beyond the center of the chim- 
ney wall below the offset. Where the chimney offset is sup- 
ported by masonry below the offset in an approvedmrnmer, the 
maximum offset limitations shall not apply. Each individual 
corbeled masonry course of the offset shall not exceed the pro- 
jection limitations specified in Section 2113.5. 

2113.8 Additional load. Chimneys shall not support loads 
other than their own weight unless they are designed and con- 
structed to support the additional load. Masonry chimneys are 
permitted to be constructed as part of the masonry walls or con- 
crete walls of the building. 

2113.9 Termination. Chimneys shall extend at least 2 feet 
(610 mm) higher than any portion of the building within 10 feet 
(3048 mm), but shall not be less than 3 feet (914 mm) above the 
highest point where the chimney passes through the roof. 



2009 INTERNATIONAL BUILDING CODE® 



441 



MASONRY 



2113.9.1 Spark arrestors. Where a spark arrestor is 
installed on a masonry chimney, the spark arrestor shall 
meet all of the following requirements: 

1. The net free area of the arrestor shall not be less than 
four times the net free area of the outlet of the chim- 
ney flue it serves. 

2. The arrestor screen shall have heat and corrosion 
resistance equivalent to 19-9age galvanized steel or 
24-gage stainless steel. 

3. Openings shall not permit the passage of spheres hav- 
ing a diameter greater than i/ 2 inch (13 mm) nor block 
the passage of spheres having a diameter less than 3/ 8 
inch (11 mm). 

4. The spark arrestor shall be accessible for cleaning and 
the screen or chimney cap shall be removable to allow 
for cleaning of the chimney flue. 

2113.10 Wall thickness. Masonry chimney walls shall be con- 
structed of concrete, solid masonry units or hollow masonry 
units grouted solid with not less than 4 inches (102 mm) nomi- 
nal thickness. 

2113.10.1 Masonry veneer chimneys. Where masonry is 
used as veneer for a framed chimney, through flashing and 
weep holes shall be provided as required by Chapter 14. 

2113.11 Flue lining (material). Masonry chimneys shall be 
lined. The lining material shall be appropriate for the type of 
appliance connected, according to the terms of the appliance 
listing and the manufacturer's instructions. 

2113.11.1 Residential-type appliances (general). Flue 
lining systems shall comply with one of the following: 

1. Clay flue lining complying with the requirements of 
ASTM C 315. 

2. Listed chimney lining systems complying with UL 

1777. 

3. Factory-built chimneys or chimney units listed for 
installation within masonry chimneys. 

4. Other approved materials that will resist corrosion, 
erosion, softening or cracking from flue gases and 
condensate at temperatures up to 1,800°F (982°C). 

2113.11.1.1 Flue linings for specific appliances. Flue 
linings other than those covered in Section 2113.11.1 
intended for use with specific appliances shall comply 
with Sections 2113.11.1.2 through 2113.11.1.4 and Sec- 
tions 2113.11.2 and 2113.11.3. 

2113.11.1.2 Gas appliances. Flue lining systems for gas 
appliances shall be in accordance with the International 
Fuel Gas Code. 

2113.11.1.3 Pellet fuel-burning appliances. Flue lining 
and vent systems for use in masonry chimneys with pel- 
let fuel-burning appliances shall be limited to flue lining 
systems complying with Section 2113.11.1 and pellet 
vents listed for installation within masonry chimneys 
(see Section 2113.11.1.5 for marking). 

2113.11.1.4 Oil-fired appliances approved for use 
with L-vent. Flue lining and vent systems for use in 



masonry chimneys with oil-fired appliances approved 
for use with Type L vent shall be limited to flue lining 
systems complying with Section 2113.11.1 and listed 
chimney liners complying with UL 641 (see Section 
2113.11.1.5 for marking). 

2113.11.1.5 Notice of usage. When a flue is relined with 
a material not complying with Section 2113.11.1, the 
chimney shall be plainly and permanently identified by a 
label attached to a wall, ceiling or other conspicuous 
location adjacent to where the connector enters the chim- 
ney. The label shall include the following message or 
equivalent language: "This chimney is for use only with 
(type or category of appliance) that burns (type of fuel). 
Do not connect other types of appliances." 

2113.11.2 Concrete and masonry chimneys for medium- 
heat appliances. 

2113.11.2.1 General. Concrete and masonry chimneys 
for medium-heat appliances shall comply with Sections 
2113.1 through 2113.5. 

2113.11.2.2 Construction. Chimneys for medium-heat 
appliances shall be constructed of solid masonry units or 
of concrete with walls a minimum of 8 inches (203 mm) 
thick, or with stone masonry a minimum of 12 inches 
(305 mm) thick. 

2113.11.2.3 Lining. Concrete and masonry chimneys 
shall be lined with an approvedmedium-duty refractory 
brick a minimum of 4 l / 2 inches (114 mm) thick laid on 
the 4 1 / 2 -inch bed (114 mm) in an app roved medium- 
duty refractory mortar. The lining shall start 2 feet (610 
mm) or more below the lowest chimney connector 
entrance. Chimneys terminating 25 feet (7620 mm) or 
less above a chimney connector entrance shall be lined 
to the top. 

2113.11.2.4 Multiple passageway. Concrete and 
masonry chimneys containing more than one passage- 
way shall have the liners separated by a minimum 
4-inch-thick (102 mm) concrete or solid masonry wall. 

2113.11.2.5 Termination height. Concrete and 
masonry chimneys for medium-heat appliances shall 
extend a minimum of 10 feet (3048 mm) higher than any 
portion of any building within 25 feet (7620 mm). 

2113.11.2.6 Clearance. A minimum clearance of 4 
inches (102 mm) shall be provided between the exterior 
surfaces of a concrete or masonry chimney for 
medium-heat appliances and combustible material. 

2113.11.3 Concrete and masonry chimneys for 
high-heat appliances. 

2113.11.3.1 General. Concrete and masonry chimneys 
for high-heat appliances shall comply with Sections 
2113.1 through 2113.5. 

2113.11.3.2 Construction. Chimneys for high-heat 
appliances shall be constructed with double walls of 
solid masonry units or of concrete, each wall to be a mini- 
mum of 8 inches (203 mm) thick with a minimum air- 
space of 2 inches (51 mm) between the walls. 



442 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



2113.11.3.3 Lining. The inside of the interior wall shall 
be lined with an approved high-duty refractory brick, a 
minimum of 4 J 1 2 inches (114 mm) thick laid on the 
4 1 / 2 -inch bed (114 mm) in an approvedhigh-duty refrac- 
tory mortar. The lining shall start at the base of the chim- 
ney and extend continuously to the top. 

2113.11.3.4 Termination height. Concrete and 
masonry chimneys for high-heat appliances shall extend 
a minimum of 20 feet (6096 mm) higher than any portion 
of any building within 50 feet (15 240 mm). 

2113.11.3.5 Clearance. Concrete and masonry chim- 
neys for high-heat appliances shall have approved clear- 
ance from buildings and structures to prevent 
overheating combustible materials, permit inspection 
and maintenance operations on the chimney and prevent 
danger of burns to persons. 

2113.12 Clay flue lining (installation). Clay flue liners shall 
be installed in accordance with ASTM C 1283 and extend from 
a point not less than 8 inches (203 mm) below the lowest inlet 
or, in the case of fireplaces, from the top of the smoke chamber 
to a point above the enclosing walls. The lining shall be carried 
up vertically, with a maximum slope no greater than 30 degrees 
(0.52 rad) from the vertical. 

Clay flue liners shall be laid in medium-duty refractory mor- 
tar conforming to ASTM C 199 with tight mortar joints left 
smooth on the inside and installed to maintain an air space or 
insulation not to exceed the thickness of the flue liner separat- 
ing the flue liners from the interior face of the chimney 
masonry walls. Flue lining shall be supported on all sides. Only 
enough mortar shall be placed to make the joint and hold the 
liners in position. 

2113.13 Additional requirements. 

2113.13.1 Listed materials. Liste d materials used as flue 
linings shall be installed in accordance with the terms of 
their listings and the manufacturer's instructions. 

2113.13.2 Space around lining. The space surrounding a 
chimney lining system or vent installed within a masonry 
chimney shall not be used to vent any other appliance. 

Exception: This shall not prevent the installation of a 
separate flue lining in accordance with the manufac- 
turer's instructions. 

2113.14 Multiple flues. When two or more flues are located 
in the same chimney, masonry wythes shall be built between 
adjacent flue linings. The masonry wythes shall be at least 4 
inches (102 mm) thick and bonded into the walls of the chim- 
ney. 

Exception: When venting only one appliance, two flues are 
permitted to adjoin each other in the same chimney with 
only the flue lining separation between them. The joints of 



the adjacent flue linings shall be staggered at least 4 inches 
(102 mm). 

2113.15 Flue area (appliance). Chimney flues shall not be 
smaller in area than the area of the connector from the appli- 
ance. Chimney flues connected to more than one appliance 
shall not be less than the area of the largest connector plus 50 
percent of the areas of additional chimney connectors. 

Exceptions: 

1. Chimney flues serving oil-fired appliances sized in 
accordance with NFPA 31. 

2. Chimney flues serving gas-fired appliances sized in 
accordance with the International Fuel Gas Code. 

2113.16 Flue area (masonry fireplace). Flue sizing for chim- 
neys serving fireplaces shall be in accordance with Section 
2113.16.1 or 2113.16.2. 

2113.16.1 Minimum area. Round chimney flues shall have 
a minimum net cross-sectional area of at least 1/ 12 of the fire- 
place opening. Square chimney flues shall have a minimum 
net cross-sectional area of at least i/ 10 of the fireplace open- 
ing. Rectangular chimney flues with an aspect ratio less than 
2 to 1 shall have a minimum net cross-sectional area of at 
least i/ 10 of the fireplace opening. Rectangular chimney 
flues with an aspect ratio of 2 to 1 or more shall have a mini- 
mum net cross-sectional area of at least i/ 8 of the fireplace 
opening. 

2113.16.2 Determination of minimum area. The mini- 
mum net cross-sectional area of the flue shall be determined 
in accordance with Figure 2113.16. A flue size providing at 
least the equivalent net cross-sectional area shall be used. 
Cross-sectional areas of clay flue linings are as provided in 
Tables 2113.16(1) and 2113.16(2) or as provided by the 
manufacturer or as measured in the field. The height of the 
chimney shall be measured from the firebox floor to the top 
of the chimney flue. 

TABLE 2113.16(1) 
NET CROSS-SECTIONAL AREA OF ROUND FLUE SIZES a 



FLUE SIZE, INSIDE DIAMETER 
(inches) 


CROSS-SECTIONAL AREA 
(square inches) 


6 


28 


7 


38 


8 


50 


10 


78 


10 3 / 4 


90 


12 


113 


15 


176 


18 


254 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm • 
a. Flue sizes are based on ASTM C 315. 



2009 INTERNATIONAL BUILDING CODE® 



443 



MASONRY 



TABLE 2113.16(2) 

NET CROSS-SECTIONAL AREA OF SQUARE 

AND RECTANGULAR FLUE SIZES 



FLUE SIZE, OUTSIDE NOMINAL DIMENSIONS 
(inches) 


CROSS-SECTIONAL AREA 
(square inches) 


4.5x8.5 


23 


4.5 x 13 


34 


8x8 


42 


8.5x8.5 


49 


8x 12 


67 


8.5 x 13 


76 


12 x 12 


102 


8.5 x 18 


101 


13 x 13 


127 


12 x 16 


131 


13 x 18 


173 


16 x 16 


181 


16x20 


222 


18 x 18 


233 


20x20 


298 


20x24 


335 


24x24 


431 



2113.17 Inlet. Inlets to masonry chimneys shall enter from 
the side. Inlets shall have a thimble of fireclay, rigid refrac- 
tory material or metal that will prevent the connector from 
pulling out of the inlet or from extending beyond the wall of 
the liner. 

2113.18 Masonry chimney cleanout openings. Cleanout 
openings shall be provided within 6 inches (152 mm) of the 
base of each flue within every masonry chimney. The upper 
edge of the cleanout shall be located at least 6 inches (152 
mm) below the lowest chimney inlet opening. The height of 
the opening shall be at least 6 inches (152 mm). The cleanout 
shall be provided with a noncombustible cover. 

Exception: Chimney flues serving masonry fireplaces, 
where cleaning is possible through the fireplace opening. 

2113.19 Chimney clearances. Any portion of a masonry 
chimney located in the interior of the building or within the 
exterior wall of the building shall have a minimum airspace 
clearance to combustibles of 2 inches (51 mm). Chimneys 
located entirely outside the exterior walls of the building, 
including chimneys that pass through the soffit or cornice, 
shall have a minimum airspace clearance of 1 inch (25 mm). 



For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm • 




Li 

§ 

5 



9Q <r. -l 



lElGHT MEASURED FROM Fl 



i&-i 



For SI: 1 inch = 25.4 mm, 1 square inch = 645 mm ■ 



FIGURE 2113.16 
FLUE SIZES FOR MASONRY CHIMNEYS 



444 



2009 INTERNATIONAL BUILDING CODE® 



MASONRY 



The airspace shall not be filled, except to provide 
fireblocking in accordance with Section 2113.20. 

Exceptions: 

1. Masonry chimneys equipped with a chimney lining 
system listed and labeled for use in chimneys in con- 
tact with combustibles in accordance with UL 1777, 
and installed in accordance with the manufacturer's 
instructions, are permitted to have combustible mate- 
rial in contact with their exterior surfaces. 

2. Where masonry chimneys are constructed as part of 
masonry or concrete walls, combustible materials 
shall not be in contact with the masonry or concrete 
wall less than 12 inches (305 mm) from the inside sur- 
face of the nearest flue lining. 

3. Exposed combustible trim and the edges of sheathing 
materials, such as wood siding, are permitted to abut 
the masonry chimney sidewalls, in accordance with 
Figure 2113.19, provided such combustible trim or 
sheathing is a minimum of 12 inches (305 mm) from 
the inside surface of the nearest flue lining. Combusti- 
ble material and trim shall not overlap the corners of 
the chimney by more than 1 inch (25 mm). 



Y///V//JMM ZZ&., 



JSI 




mm mm. 



H / « H 



yi fMEOOT* ABUTRN& 






For 51: 1 inch = 25.4 mm. 



FIGURE 2113.19 

ILLUSTRATION OF EXCEPTION THREE 

CHIMNEY CLEARANCE PROVISION 

2113.20 Chimney fireblocking. All spaces between chimneys 
and floors and ceilings through which chimneys pass shall be 
fireblocked with noncombustible material securely fastened in 
place. The fireblocking of spaces between wood joists, beams 
or headers shall be to a depth of 1 inch (25 mm) and shall only 
be placed on strips of metal or metal lath laid across the spaces 
between combustible material and the chimney. 



2009 INTERNATIONAL BUILDING CODE® 



445 



446 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 22 

STEEL 



SECTION 2201 
GENERAL 

2201.1 Scope. The provisions of this chapter govern the qual- 
ity, design, fabrication and erection of steel used structurally in 
buildings or structures. 



SECTION 2202 
DEFINITIONS 

2202.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in this code, 
have the meaning shown herein. 

STEEL CONSTRUCTION, COLD-FORMED. That type 
of construction made up entirely or in part of steel structural 
members cold formed to shape from sheet or strip steel such as 
roof deck, floor and wall panels, studs, floor joists, roofjoists 
and other structural elements. 

STEEL JOIST. Any steel structural member of a building or 
structure made of hot-rolled or cold-formed solid or open- web 
sections, or riveted or welded bars, strip or sheet steel mem- 
bers, or slotted and expanded, or otherwise deformed rolled 
sections. 

STEEL MEMBER, STRUCTURAL. Any steel structural 
member of a building or structure consisting of a rolled steel struc- 
tural shape other than cold-formed steel, or steel joist members. 



SECTION 2203 

IDENTIFICATION AND PROTECTION 

OF STEEL FOR STRUCTURAL PURPOSES 

2203.1 Identification. Identification of structural steel mem- 
bers shall comply with the requirements contained in AISC 
360. Identification of cold-formed steel members shall comply 
with the requirements contained in AISI S 100. Identification of 
cold-formed steel light-frame construction shall also comply 
with the requirements contained in AISI S200. Other steel fur- 
nished for structural load-carrying purposes shall be properly 
identified for conformity to the ordered grade in accordance 
with the specified ASTM standard or other specification and 
the provisions of this chapter. Steel that is not readily identifi- 
able as to grade from marking and test records shall be tested to 
determine conformity to such standards. 

2203.2 Protection. Painting of structural steel members shall 
comply with the requirements contained in AISC 360. Painting 
of open-web steeljoists andjoist girders shall comply with the 
requirements of Sjl Cj-1.0, Sjl jG-1.1, Sjl K-l.l and Sjl 
LH/DLH-1.1. Individual structural members and assembled 
panels of cold-formed steel construction shall be protected 
against corrosion in accordance with the requirements con- 
tained in AISI S 100. Protection of cold-formed steel light- 
frame construction shall also comply with the requirements 
contained in AISI S200. 



SECTION 2204 
CONNECTIONS 

2204.1 Welding. The details of design, workmanship and tech- 
nique for welding, inspection of welding and qualification of 
welding operators shall conform to the requirements of the 
specifications listed in Sections 2205, 2206, 2207, 2209 and 
2210. Special inspection of welding shall be provided where 
required by Section 1704. 

2204.2 Bolting. The design, installation and inspection of bolts 
shall be in accordance with the requirements of the specifica- 
tions listed in Sections 2205, 2206, 2209 and 2210. Special 
inspection of the installation of high- strength bolts shall be pro- 
vided where required by Section 1704. 

2204.2.1 Anchor rods. Anchor rods shall be set accurately 
to the pattern and dimensions called for on the plans. The 
protrusion of the threaded ends through the connected mate- 
rial shall be sufficient to fully engage the threads of the nuts, 
but shall not be greater than the length of the threads on the 
bolts. 



SECTION 2205 
STRUCTURAL STEEL 

2205.1 General. The design, fabrication and erection of struc- 
tural steel for buildings and structures shall be in accordance 
with AISC 360. Where required, the seismic design of steel 
structures shall be in accordance with the additional provisions 
of Section 2205.2. 

2205.2 Seismic requirements for steel structures. The 
design of structural steel structures to resist seismic forces shall 
be in accordance with the provisions of Section 2205.2.1 or 
2205.2.2 for the appropriate seismic design category. 

2205.2.1 Seismic Design Category A, B or C. Structural 
steel structures assigned to Seismic Design Category A, B or 
C shall be of any construction permitted in Section 2205. An 
R factor as set forth in Section 12.2.1 of ASCE 7 for the 
appropriate steel system is permitted where the structure is 
designed and detailed in accordance with the provisions of 
AISC 341, Part I. Systems not detailed in accordance with 
the above shall use the R factor in Section 12.2.1 of ASCE 7 
designated for "structural steel systems not specifically 
detailed for seismic resistance." 

2205.2.2 Seismic Design Category D, E or F. Structural 
steel structures assigned to Seismic Design CategoryD, E or 
F shall be designed and detailed in accordance with AISC 
341, Part I. 

2205.3 Seismic requirements for composite construction. 
The design, construction and quality of composite steel and 
concrete components that resist seismic forces shall conform to 
the requirements of the AISC 360 and ACI 318. An Ri 'actor as 
set forth in Section 12.2.1 of ASCE 7 for the appropriate com- 
posite steel and concrete system is permitted where the struc- 



2009 INTERNATIONAL BUILDING CODE® 



447 



STEEL 



ture is designed and detailed in accordance with the provisions 
of AISC 341, Part II. In Seismic Design CategoryB or above, 
the design of such systems shall conform to the requirements of 
AISC 341, Part II. 

2205.3.1 Seismic Design Categories D, E and F. Compos- 
ite structures are permitted in Seismic Design Categories!) , 
E and F, subject to the limitations in Section 12.2.1 of ASCE 
7, where substantiating evidence is provided to demonstrate 
that the proposed system will perform as intended by AISC 
341, Part H The substantiating evidence shall be subject to 
bUilding official approval. Where composite elements or 
connections are required to sustain inelastic deformations, 
the substantiating evidence shall be based on cyclic testing. 



SECTION 2206 
STEEL JOISTS 

2206.1 General. The design, manufacture and use of open web 
steeljoists and joist girders shall be in accordance with one of 
the following Steel joist Institute (Sjl) specifications: 

I 1. SjlCj-1.0 

2. SjlK-1.1 

3. SjlLH/DLH-1.1 

4. SjljG-1.1 

Where required, the seismic design of buildings shall be in 
accordance with the additional provisions of Section 2205.2 or 
2210.5. 

2206.2 Design. The registered design professional shall indi- 
cate on the construction documents the steel joist and/or steel 
joist girder designations from the specifications listed in Sec- 
tion 2206.1 and shall indicate the requirements for joist and 
joist girder design, layout, end supports, anchorage, non-Sjl 
standard bridging, bridging termination connections and bear- 
ing connection design to resist uplift and lateral loads. These 
documents shall indicate special requirements as follows : 

1. Special loads including: 

1.1. Concentrated loads; 

1.2. Nonuniform loads; 

1.3. Net uplift loads; 

1.4. Axial loads; 

1.5. End moments; and 

1.6. Connection forces. 

2. Special considerations including: 

2.1. Profiles for nonstandard joist and joist girder 
configurations (standard joist and joist girder 
configurations are as indicated in the Sjl cata- 
log); 

2.2. Oversized or other nonstandard web openings; 
and 

2.3. Extended ends. 

3. Deflection criteria for live and total loads for non-Sjl 
standardjoists. 



2206.3 Calculations. The steeljoist andjoist girder manufac- 
turer shall design the steeljoists and/or steeljoist girders in 
accordance with the current Sjl specifications and load tables 
to support the load requirements of Section 2206.2. The regis- 
tered design professional may require submission of the steel 

joist andjoist girder calculations as prepared by a registered 
design professional responsible for the product design. If 
requested by the registered design professional, the steeljoist 
manufacturer shall submit design calculations with a cover let- 
ter bearing the seal and signature of the joist manufacturer's 
registered design professional. In addition to standard calcula- 
tions under this seal and signature, submittal of the following 
shall be included: 

1. Non-Sjl standard bridging details (e.g. for cantilevered 
conditions, net uplift, etc.) . 

2. Connection details for: 

2.1. Non-Sjl standard connections (e.g. flush-framed 
or framed connections); 

2.2. Field splices; and 

2.3. joist headers. 

2206.4 Steeljoist drawings. Steeljoist placement plans shall 
be provided to show the steeljoist products as specified on the 
construction documents and are to be utilized for field installa- 
tion in accordance with specific project requirements as stated 
in Section 2206.2. Steel placement plans shall include, at a 
minimum, the following: 

1. Listing of all applicable loads as stated in Section 2206.2 
and used in the design of the steeljoists andjoist girders 
as specified in the construction documents. 

2. Profiles for nonstandard joist andjoist girder configura- 
tions (standardjoist andjoist girder configurations are as 
indicated in the Sjl catalog). 

3. Connection requirements for: 

3.1. joist supports; 

3.2. joist girder supports; 

3.3. Field splices; and 

3.4. Bridging attachments. 

4. Deflection criteria for live and total loads for non-Sjl 
standardjoists. 

5. Size, location and connections for all bridging. 

6. joist headers. 

Steeljoist placement plans do not require the seal and signa- 
ture of thejoist manufacturer's registered design professional. 

2206.5 Certification. At completion of manufacture, the steel 
joist manufacturer shall submit a certificate of compliance in 
accordance with Section 1704.2.2 stating that work was per- 
formed in accordance with approved construction documents 
and with Sjl standard specifications. 



448 



2009 INTERNATIONAL BUILDING CODE® 



STEEL 



SECTION 2207 
STEEL CABLE STRUCTURES 

2207.1 General. The design, fabrication and erection includ- 
ing related connections, and protective coatings of steel cables 
for buildings shall be in accordance with ASCE 19. 

2207.2 Seismic requirements for steel cable. The design 
strength of steel cables shall be determined by the provisions of 
ASCE 19 except as modified by these provisions. 

1. A load factor of 1.1 shall be applied to the prestress force 
included in T 3 and T 4 as defined in Section 3.12. 

2. In Section 3.2.1, Item (c) shall be replaced with" 1.5 T 3 - 
and Item (d) shall be replaced with" 1.5 T A ." 



SECTION 2208 
STEEL STORAGE RACKS 

2208.1 Storage racks. The design, testing and utilization of 
industrial steel storage racks made of cold- formed or hot-rolled 
steel structural members, shall be in accordance with the 
RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic 
design of storage racks shall be in accordance with the provi- 
sions of Section 15.5.3 of ASCE 7, except that items (1), (2) 
and (3) of Section 15.5.3 of ASCE 7 do not apply when the rack 
design satisfies RMI/ANSI MH 16.1. 



SECTION 2209 
COLD-FORMED STEEL 

2209.1 General. The design of cold-formed carbon and 
low- alloy steel structural members shall be in accordance with 
AISI S100. The design of cold-formed stainless-steel struc- 
tural members shall be in accordance with ASCE 8. 
Cold-formed steel light-frame construction shall also comply 
with Section 2210. 

2209.2 Steel decks. The design and construction of 
cold-formed steel decks shall be in accordance with this sec- 
tion. 

2209.2.1 Composite slabs on steel decks. Composite slabs 
of concrete and steel deck shall be designed and constructed 
in accordance with ASCE 3. 

2209.2.2 Noncomposite steel floor decks. Noncomposite 
steel floor decks shall be permitted to be designed and con- 
structed in accordance with ANSI/SDI-NC1 .0, as modified 
in Section 2209.2.2.1. 

2209.9.2.2.1 ANSI/SDI-NC1.0 Section 2.4B1. Replace 
Section 2.4B1 of ANSI/SDI-NC1.0 with the following: 

1. General: The design of the concrete slabs shall be 
done in accordance with the ACI BUilding Code 
Requirements for Reinforced Concrete. The mini- 
mum concrete thickness above the top of the deck 
shall be 1V 2 inches (38 mm). 

2209.2.3 Steel roof deck. Steel roof decks shall be permit- 
ted to be designed and constructed in accordance with 
ANSI/SBI-RD1.0. 



SECTION 2210 

COLD-FORMED STEEL 

LIGHT-FRAME CONSTRUCTION 

2210.1 General. The design and installation of structural 
members and nonstructural members utilized in cold-formed 
steel light-frame construction where the specified minimum 
base steel thickness is between 0.0179 inches (0.455 mm) and 
0.1180 inches (2.997 mm) shall be in accordance with AISI 
S200 and Sections 2210.2 through 2210.7, as applicable. 

2210.2 Header design. Headers, including box and 
back-to-back headers, and double and single L-headers shall 
be designed in accordance with AISI S212 or AISI S100. 

2210.3 Trusses. 

2210.3.1 Design. Cold-formed steel trusses shall be 
designed in accordance with AISI S214, Sections 2210.3.1 
through 2210.3.5 and accepted engineering practice. 

2210.3.2 Truss design drawings. The truss design draw- 
ings shall conform to the requirements of Section B2.3 of 
AISI S214 and shall be provided with the shipment of 
trusses delivered to the job site. The truss design drawings 
shall include the details of permanent individual truss mem- 
ber restraint/bracing in accordance with Section B6(a) or 
B6(c) of AISI S214 where these methods are utilized to pro- 
vide restraint/bracing. 

2210.3.3 Deferred submittals. AISI Section B4.2 shall be 
deleted. 

2210.3.4 Trussses spanning 60 feet or greater. The owner 
shall contract with a registered design professional for the 
design of the temporary installation restraint/bracing and 
the permanent individual truss member restraint/bracing for 
trusses with clear spans 60 feet (18 288 mm) or greater. Spe- 
cial inspection of trusses over 60 feet (18 288 mm) in length 
shall conform to Section 1704. 

2210.3.5 Truss quality assurance. Trusses not part of a 
manufacturing process that provides requirements for qual- 
ity control done under the supervision of a third-party qual- 
ity control agency, shall be manufactured in compliance 
with Sections 1704.2 and 1704.3, as applicable. 

2210.4 Wall stud design. Wall studs shall be designed in 
accordance with either AISI S211 or AISI S 100. 

2210.5 Floor and roof system design. Framing for floor and 
roof systems in buildings shall be designed in accordance with 
either AISI S210 or AISI S100. 

2210.6 Lateral design. Light-frame shear walls, diagonal 
strap bracing that is part of a structural wall and diaphragms 
used to resist wind, seismic and other in-plane lateral loads 
shall be designed in accordance with AISI S213. 

2210.7 Prescriptive framing. Detached one- and two-family 
dwellings and townhouses, less than or equal to three stories 
above grade plane, shall be permitted to be constructed in 
accordance with AISI S230 subject to the limitations therein. 



2009 INTERNATIONAL BUILDING CODE® 



449 



450 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 23 

WOOD 



SECTION 2301 
GENERAL 

2301.1 Scope. The provisions of this chapter shall govern the 
materials, design, construction and quality of wood members 
and their fasteners. 

2301.2 General design requirements. The design of struc- 
tural elements or systems, constructed partially or wholly of 
wood or wood-based products, shall be in accordance with one 
of the following methods: 

1. Allowable stress design in accordance with Sections 
2304,2305 and 2306. 

2. Load and resistance factor design in accordance with 
Sections 2304, 2305 and 2307. 

3. Conventional light-frame construction in accordance 
with Sections 2304 and 2308. 

Exception: Buildings designed in accordance with 
the provisions of the AF&PA WFCM shall be deemed 
to meet the requirements of the provisions of Section 
2308. 

4. The design and construction of log structures shall be in 
accordance with the provisions of ICC 400. 

2301.3 Nominal sizes. For the purposes of this chapter, where 
dimensions of lumber are specified, they shall be deemed to be 
nominal dimensions unless specifically designated as actual 
dimensions (see Section 2304.2) . 



SECTION 2302 
DEFINITIONS 

2302.1 Definitions. The following words and terms shall, for 
the purposes of this chapter, have the meanings shown herein. 

ACCREDITATION BODY. An approved, third-party organi- 
zation that is independent of the grading and inspection agen- 
cies, and the lumber mills, and that initially accredits and 
subsequently monitors, on a continuing basis, the competency 
and performance of a grading or inspection agency related to 
carrying out specific tasks. 

BRACED WALL LINE. A series of braced wall panels in a 
single story that meets the requirements of Section 2308.3 or 
2308.12.4. 

BRACED WALL PANEL. A section of wall braced in accor- 
dance with Section 2308.9.3 or 2308.12.4. 

COLLECTOR. A horizontal diaphragm element parallel and 
in line with the applied force that collects and transfers dia- 
phragm shear forces to the vertical elements of the lat- 
eral-force-resisting system and/or distributes forces within the 
diaphragm. 

CONVENTIONAL LIGHT-FRAME CONSTRUCTION. 

A type of construction whose primary structural elements are 



formed by a system of repetitive wood-framing members. See 
Section 2308 for conventional light-frame construction provi- 
sions. 

CRIPPLE WALL. A framed stud wall extending from the top 
of the foundation to the underside of floor framing for the low- 
est occupied floor level. 

DIAPHRAGM, UNBLOCKED. A diaphragm that has edge 
nailing at supporting members only. Blocking between sup- 
porting structural members at panel edges is not included. Dia- 
phragm panels are field nailed to supporting members. 

DRAG STRUT. See "Collector." 

FIBERBOARD. A fibrous, homogeneous panel made from 
lignocellulosic fibers (usually wood or cane) and having a den- 
sity of less than 31 pounds per cubic foot (pcf) (497 kg/m 3 ) but 
more than 10 pcf (160 kg/m 3 ). 

GLUED BUILT-UP MEMBER. A structural element, the 
section of which is composed of built-up lumber, wood struc- 
tural panels or wood structural panels in combination with lum- 
ber, all parts bonded together with structural adhesives. 

GRADE (LUMBER). The classification of lumber in regard 
to strength and utility in accordance with American Softwood 
Lumber Standard DOC PS 20 and the grading rules of an 
app roved lumber rules- writing agency. 

HARDBOARD. A fibrous-felted, homogeneous panel made 
from lignocellulosic fibers consolidated under heat and pres- 
sure in a hot press to a density not less than 31 pcf (497 kg/m 3 ). 

NAILING, BOUNDARY. A special nailing pattern required 
by design at the boundaries of diaphragms. 

NAILING, EDGE. A special nailing pattern required by 
design at the edges of each panel within the assembly of a dia- 
phragm or shear wall. 

NAILING, FIELD. Nailing required between the sheathing 
panels and framing members at locations other than boundary 
nailing and edge nailing. 

NATURALLY DURABLE WOOD. The heartwood of the 
following species with the exception that an occasional piece 
with corner sap wood is permitted if 90 percent or more of the 
width of each side on which it occurs is heartwood. 

Decay resistant. Redwood, cedar, black locust and black 
walnut. 

Termite resistant. Redwood, Alaska yellow -cedar, Eastern 
redcedar and both heartwood and all sapwood of Western 
redcedar. 

NOMINAL SIZE (LUMBER). The commercial size desig- 
nation of width and depth, in standard sawn lumber and 
glued-laminated lumber grades; somewhat larger than the stan- 
dard net size of dressed lumber, in accordance with DOC PS 20 
for sawn lumber and with the AF&PA NDS for glued-lami- 
nated lumber. 



i 



2009 INTERNATIONAL BUILDING CODE® 



451 



WOOD 



PARTICLEBOARD. A generic term for a panel primarily 
composed of cellulosic materials (usually wood), generally in 
the form of discrete pieces or particles, as distinguished from 
fibers. The cellulosic material is combined with synthetic resin 
or other suitable bonding system by a process in which the 
interparticle bond is created by the bonding system under heat 
and pressure. 

PREFABRICATED WOOD I-JOIST. Structural member 
manufactured using sawn or structural composite lumber 
flanges and wood structural panel webs bonded together with 
exterior exposure adhesives, which forms an "I" cross-sec- 
tional shape. 

SHEAR WALL. A wall designed to resist lateral forces paral- 
lel to the plane of a wall. 

Shear wall, perforated. A wood structural panel sheathed 
wall with openings, that has not been specifically designed 
and detailed for force transfer around openings. 

Shear wall segment, perforated. A section of shear wall 
with full-height sheathing that meets the height-to-width 
ratio limits of Section 4.3.4 of AF&PA SDPWS. 

STRUCTURAL COMPOSITE LUMBER. Structural mem- 
ber manufactured using wood elements bonded together with 
exterior adhesives. Examples of structural composite lumber 
are: 

Laminated veneer lumber (LVL). A composite of wood 
veneer sheet elements with wood fibers primarily oriented 
along the length of the member. 

Parallel strand lumber (PSL). A composite of wood 
strand elements with wood fibers primarily oriented along 
the length of the member. 

STRUCTURAL GLUED-LAMINATED TIMBER. An 

engineered, stress-rated product of a timber laminating plant, 
comprised of assemblies of specially selected and prepared 
wood laminations in which the grain of all laminations is 
approximately parallel longitudinally and the laminations are 
bonded with adhesives. 

SUBDIAPHRAGM. A portion of a larger wood diaphragm 
designed to anchor and transfer local forces to primary dia- 
phragm struts and the main diaphragm. 

TIE-DOWN (HOLD-DOWN). A device used to resist uplift 
of the chords of shear walls. 

TREATED WOOD. Wood and wood-based materials that use 
vacuum-pressure impregnation processes to enhance fire retar- 
dant or preservative properties. 

Fire-retardant-treated wood. Pressure-treated lumber 
and plywood that exhibit reduced surface-burning charac- 
teristics and resist propagation of fire. 

Preservative-treated wood. Pressure- treated wood prod- 
ucts that exhibit reduced susceptibility to damage by fungi, 
insects or marine borers. 

WOOD SHEAR PANEL. A wood floor, roof or wall compo- 
nent sheathed to act as a shear wall or diaphragm. 

WOOD STRUCTURAL PANEL. A panel manufactured 
from veneers, wood strands or wafers or a combination of 



veneer and wood strands or wafers bonded together with water- 
proof synthetic resins or other suitable bonding systems. 
Examples of wood structural panels are: 

Composite panels. A wood structural panel that is com- 
prised of wood veneer and reconstituted wood-based mate- 
rial and bonded together with waterproof adhesive; 

Oriented strand board (OSB). A mat-formed wood struc- 
tural panel comprised of thin rectangular wood strands 
arranged in cross-aligned layers with surface layers nor- 
mally arranged in the long panel direction and bonded with 
waterproof adhesive; or 

Plywood. A wood structural panel comprised of plies of 
wood veneer arranged in cross-aligned layers. The plies are 
bonded with waterproof adhesive that cures on application 
of heat and pressure. 



SECTION 2303 
MINIMUM STANDARDS AND QUALITY 

2303.1 General. Structural sawn lumber; end-jointed lumber; 
prefabricated wood I-joists; structural glued-laminated timber; 
wood structural panels, fiberboard sheathing (when used struc- 
turally); hardboard siding (when used structurally); 
particleboard; preservative-treated wood; structural log mem- 
bers; structural composite lumber; round timber poles and 
piles; fire-retardant-treated wood; hardwood plywood; wood 
trusses; joist hangers; nails; and staples shall conform to the 
applicable provisions of this section. 

2303.1.1 Sawn lumber. Sawn lumber used for load-sup- 
porting purposes, including end-jointed or edge-glued lum- 
ber, machine stress-rated or machine-evaluated lumber, 
shall be identified by the grade mark of a lumber grading or 
inspection agency that has been approved by an accredita- 
tion body that complies with DOC PS 20 or equivalent. 
Grading practices and identification shall comply with rules 
published by an agency approved in accordance with the 
procedures of DOC PS 20 or equivalent procedures. In lieu 
of a grade markon the material, a certificate of inspection as 
to species and grade issued by a lumber grading or inspec- 
tion agency meeting the requirements of this section is per- 
mitted to be accepted for precut, remanufactured or 
rough- sawn lumber and for sizes larger than 3 inches (76 
mm) nominal thickness. 

Approved end-jointed lumber is permitted to be used 
interchangeably with solid-sawn members of the same spe- 
cies and grade. 

2303.1.2 Prefabricated wood I-joists. Structural capaci- 
ties and design provisions for prefabricated wood I-joists 
shall be established and monitored in accordance with 
ASTM D 5055. 

2303.1.3 Structural glued-laminated timber. GlUed-lam- I 
inated timbers shall be manufactured and identified as 
required in ANSI/AITC A 190.1 and ASTM D 3737. 

2303.1.4 Wood structural panels. Wood structural panels, 
when used structurally (including those used for siding, roof 
and wall sheathing, subflooring, diaphragms and built-up 
members), shall conform to the requirements for their type 



452 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



in DOC PS 1 or PS 2. Each panel or member shall be identi- 
fied for grade and glue type by the trademarks of an 
approv edtQsting and grading agency. Wood structural panel 
components shall be designed and fabricated in accordance 
with the applicable standards listed in Section 2306.1 and 
identified by the trademarks of an approved testing and 
inspection agency indicating conformance with the applica- 
ble standard. In addition, wood structural panels when per- 
manently exposed in outdoor applications shall be of 
exterior type, except that wood structural panel roof sheath- 
ing exposed to the outdoors on the underside is permitted to 
be interior type bonded with exterior glue, Exposure 1. 

2303.1.5 Fiberboard. Fiberboard for its various uses shall 
conform to ASTM C 208. Fiberboard sheathing, when used 
structurally, shall be identified by an approved agency as 
conforming to ASTM C 208 . 

2303.1.5.1 Jointing. To ensure tight-fitting assemblies, 
edges shall be manufactured with square, shiplapped, 
beveled, tongue-and-groove or U-shapedjoints. 

2303.1.5.2 Roof insulation. Where used as roof insula- 
tion in all types of construction, fiberboard shall be pro- 
tected with an approved roof covering. 

2303.1.5.3 Wall insulation. Where installed and 
fireblocked to comply with Chapter 7, fiberboards are 
permitted as wall insulation in all types of construction. 
In fire walls and fire barriers, unless treated to comply 
with Section 803.1 for Class A materials, the boards shall 
be cemented directly to the concrete, masonry or other 
noncombustible base and shall be protected with an 
approved noncombustible veneer anchored to the base 
without intervening airspaces. 

2303.1.5.3.1 Protection. Fiberboard wall insulation 
applied on the exterior of foundation walls shall be 
protected below ground level with a bituminous coat- 
ing. 

2303.1.6 Hardboard. Hardboard siding used structurally 
shall be identified by an approved agency conforming to 
CPA/ANSI AI35.6. Hardboard underlay ment shall meet 
the strength requirements of 7/ 32 -inch (5.6 mm) or i/ 4 -inch 
(6.4 mm) service class hardboard planed or sanded on one 
side to a uniform thickness of not less than 0.200 inch (5.1 
mm) . Prefinished hardboard paneling shall meet the 
requirements of CPA/ANSI AI35 .5. Other basic hardboard 
products shall meet the requirements of CPA/ANSI AI35 .4. 
Hardboard products shall be installed in accordance with 
manufacturer's recommendations. 

2303.1.7 Particleboard. Particleboard shall conform to 
ANSI A208.1. Particleboard shall be identified by the grade 
mark or certificate of inspection issued by an approved 
agency. Particleboard shall not be utilized for applications 
other than indicated in this section unless the particleboard 
complies with the provisions of Section 2306.5. 

2303.1.7.1 Floor underlayment. Particleboard floor 
underlayment shall conform to Type PBU of ANSI 
A208.1. Type PBU underlayment shall not be less than 
1/4-inch (6.4 mm) thick and shall be installed in accor- 



dance with the instructions of the Composite Panel 
Association. 

2303.1.8 Preservative-treated wood. Lumber, timber, ply- 
wood, piles and poles supporting permanent structures 
required by Section 2304. 11 to be preservative treated shall 
conform to the requirements of the applicable AWPA Stan- 
dard Uland M4 for the species, product, preservative and 
end use. Preservatives shall be listed in Section 4 of AWPA 
U 1. Lumber and plywood used in wood foundation systems 
shall conform to Chapter 18. 

2303.1.8.1 Identification. Wood required by Section 
2304.11 to be preservative treated shall bear the quality 
mark of an inspection agency that maintains continuing 
supervision, testing and inspection over the quality of the 
preservative -treated wood. Inspection agencies for pre- 
servative-treatedwoodshaU be listedby an accreditation 
body that complies with the requirements of the Ameri- 
can Lumber Standards Treated Wood Program, or equiv- 
alent. The quality mark shall be on a stamp or label 
affixed to the preservative-treated wood, and shall 
include the following information: 

1. Identification of treating manufacturer. 

2. Type of preservative used. 

3. Minimum preservative retention (pcf). 

4. End use for which the product is treated. 

5. AWPA standard to which the product was treated. 

6. Identity of the accredited inspection agency. 

2303.1.8.2 Moisture content. Where preserva- 
tive-treated wood is used in enclosed locations where 
drying in service cannot readily occur, such wood shall 
be at a moisture content of 19 percent or less before being 
covered with insulation, interior wall finish, floor cover- 
ing or other materials. 

2303.1.9 Structural composite lumber. Structural capaci- 
ties for structural composite lumber shall be established and 
monitored in accordance with ASTM D 5456. 

2303.1.10 Structural log members. Stress grading of 
structural log members of nonrectangular shape, as typi- 
cally used in log buildings, shall be in accordance with 
ASTM D 3957. Such structural log members shall be identi- 
fied by the grade mark of an approved lumber grading or 
inspection agency. In lieu of a grade mark on the material, a 
certificate of inspection as to species and grade issued by a 
lumber grading or inspection agency meeting the require- 
ments of this section shall be permitted. 

2303.1.11 Round timber poles and piles. Round timber 
poles and piles shall comply with ASTM D 3200 and ASTM 
D 25, respectively. 

2303.2 Fire-retardant-treated wood. Fire-retardant-treated 
wood is any wood product which, when impregnated with 
chemicals by a pressure process or other means during manu- 
facture, shall have, when tested in accordance with ASTM E 84 
or UL 723, a liste Jflame spread index of 25 or less and show no 
evidence of significant progressive combustion when the test is 
continued for an additional20-minute period. Additionally, the 



2009 INTERNATIONAL BUILDING CODE® 



453 



WOOD 



flame front shall not progress more than 10 V 2 feet (3200 mm) 
beyond the centerline of the burners at any time during the test. 

2303.2.1 Pressure process. For wood products impreg- 
nated with chemicals by a pressure process, the process 
shall be performed in closed vessels under pressures not less 
than 50 pounds per square inch gauge (psig) (345 kPa). 

2303.2.2 Other means during manufacture. For wood 
products produced by other means during manufacture, the 
treatment shall be an integral part of the manufacturing pro- 
cess of the wood product. The treatment shall provide per- 
manent protection to all surfaces of the wood product. 

2303.2.3 Testing. For wood products produced by other 
means during manufacture, other than a pressure process, 
all sides of the wood product shall be tested in accordance 
with and produce the results required in Section 2303.2. 
Wood structural panels shall be permitted to test only the 
front and back faces . 

2303.2.4 Labeling. Fire-retardant- treated lumber and wood 
structural panels shall be labeled. The label shall contain the 
following items: 

1. The identification mark of an approved agency in 
accordance with Section 1703.5. 

2. Identification of the treating manufacturer. 

3. The name of the fire-retardant treatment. 

4. The species of wood treated. 

5. Flame spread and smoke-developed index. 

6. Method of drying after treatment. 

7. Conformance with appropriate standards in accor- 
dance with Sections 2303.2.2 through 2303.2.5. 

8. For fire-retardant-treated woo d exposed to weather, 
damp or wet locations, include the words "No 
increase in the liste d classification when subjected to 
the Standard Rain Test" (ASTM D 2898). 

2303.2.5 Strength adjustments. Design values for 
untreated lumber and wood structural panels, as specified 
in Section 2303.1, shall be adjusted for fire-retar- 
dant-treated wood. Adjustments to design values shall be 
based on an approved method of investigation that takes 
into consideration the effects of the anticipated tempera- 
ture and humidity to which the fire-retardant-treated wood 
will be subjected, the type of treatment and redrying proce- 
dures. 

2303.2.5.1 Wood structural panels. The effect of 
treatment and the method of redrying after treatment, 
and exposure to high temperatures and high humidities 
on the flexure properties of fire-retardant-treated soft- 
wood plywood shall be determined in accordance with 
ASTM D 5516. The test data developed by ASTM D 
5516 shall be used to develop adjustment factors, maxi- 
mum loads and spans, or both, for untreated plywood 
design values in accordance with ASTM D 6305. Each 
manufacturer shall publish the allowable maximum 
loads and spans for service as floor and roof sheathing 
for its treatment. 



2303.2.5.2 Lumber. For each species of wood that is 
treated, the effects of the treatment, the method of 
redrying after treatment and exposure to high tempera- 
tures and high humidities on the allowable design prop- 
erties of fire-retardant-treated lumber shall be 
determined in accordance with ASTM D 5664. The test 
data developed by ASTM D 5664 shall be used to 
develop modification factors for use at or near room tem- 
perature and at elevated temperatures and humidity in 
accordance with ASTM D 6841. Each manufacturer 
shall publish the modification factors for service at tem- 
peratures of not less than 80°F (27°C) and for roof fram- 
ing. The roof framing modification factors shall take into 
consideration the climatological location. 

2303.2.6 Exposure to weather, damp or wet locations. 
Where fire-retardant-treated woodis exposed to weather, 
or damp or wet locations, it shall be identified as "Exte- 
rior" to indicate there is no increase in the listed flame 
spread index as defined in Section 2303.2 when subjected 
to ASTM D 2898. 

2303.2.7 Interior applications. Interior fire-retar- 
dant-treated woo d shall have moisture content of not over 
28 percent when tested in accordance with ASTM D 3201 
procedures at 92-percent relative humidity. Interior 
fire-retardant-treated wood shall be tested in accordance 
with Section 2303.2.5.1 or 2303.2.5.2. Interior fire-retar- 
dant-treated woo d designated as Type A shall be tested in 
accordance with the provisions of this section. 

2303.2.8 Moisture content. Fire-retardant-treated wood 
shall be dried to a moisture content of 19 percent or less for 
lumber and 15 percent or less for wood structural panels 
before use. For wood kiln dried after treatment (KDAT), 
the kiln temperatures shall not exceed those used in kiln 
drying the lumber and plywood submitted for the tests 
described in Section 2303.2.5.1 for plywood and 
2303.2.5.2 for lumber. 

2303.2.9 Type I and II construction applications. See 
Section 603.1 for limitations on the use of fire-retar- 
dant-treated woodin buildings of Type lor II construction. 

2303.3 Hardwood and plywood. Hardwood and decorative 
plywood shall be manufactured and identified as required in 
HPVA HP-1. 

2303.4 Trusses. 

2303.4.1 Design. Wood trusses shall be designed in accor- 
dance with the provisions of this code and accepted engi- 
neering practice. Members are permitted to be joined by 
nails, glue, bolts, timber connectors, metal connector plates 
or other approved framing devices. 

2303.4.1.1 Truss design drawings. The written, graphic 
and pictorial depiction of each individual truss shall be 
provided to the building official for approval prior to 
installation. Truss design drawings shall also be pro- 
vided with the shipment of trusses delivered to the job 
site. Truss design drawings shall include, at a minimum, 
the information specified below: 

1. Slope or depth, span and spacing; 



454 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2. Location of all joints and support locations; 

3. Number of plies if greater than one; 

4. Required bearing widths; 

5. Design loads as applicable, including; 

5.1. Top chord live load; 

5.2. Top chord dead load; 

5.3. Bottom chord live load; 

5.4. Bottom chord dead load; 

5.5. Additional loads and locations; and 

5.6. Environmental design criteria and loads 
(wind, rain, snow, seismic, etc.). 

6. Other lateral loads, including drag strut loads; 

7. Adjustments to wood member and metal connec- 
tor plate design value for conditions of use; 

8. Maximum reaction force and direction, includ- 
ing maximum uplift reaction forces where appli- 
cable; 

9. Metal-connector-plate type, size and thickness or 
gage, and the dimensioned location of each metal 
connector plate except where symmetrically 
located relative to the joint interface; 

10. Size, species and grade for each wood member; 

11. Truss-to-truss connections and truss field assem- 
bly requirements; 

12. Calculated span-to-deflection ratio and maxi- 
mum vertical and horizontal deflection for live 
and total load as applicable; 

13. Maximum axial tension and compression forces 
in the truss members; and 

14. Required permanent individual truss member 
restraint location and the method and details of 
restraint/bracing to be used in accordance with 
Section 2303.4.1.2. 

2303.4.1.2 Permanent individual truss member 
restraint. Where permanent restraint of truss members 
is required on the truss design drawings, it shall be 
accomplished by one of the following methods: 

1. Permanent individual truss member restraint/brac- 
ing shall be installed using standard industry lat- 
eral restraint/bracing details in accordance with 
generally accepted engineering practice. Loca- 
tions for lateral restraint shall be identified on the 
truss design drawing. 

2. The trusses shall be designed so that the buckling 
of any individual truss member is resisted inter- 
nally by the individual truss through suitable 
means (i.e., buckling reinforcement by T -rein- 
forcement or L-reinforcement, proprietary rein- 
forcement, etc.). The buckling reinforcement of 
individual members of the trusses shall be installed 
as shown on the truss design drawing or on supple- 



mental truss member buckling reinforcement 
details provided by the truss designer. 

3. A project-specific permanent individual truss 
member restraint/bracing design shall be permit- 
ted to be specified by any registered design profes- 
sional. 

2303.4.1.3 Trusses spanning 60 feet or greater. The 
owner shall contract with any qualified registered design 
professional for the design of the temporary installation 
restraint/bracing and the permanent individual truss 
member restraint/bracing for all trusses with clear spans 
60 feet (18 288 mm) or greater. 

2303.4.1.4 Truss designer. The individual or organiza- 
tion responsible for the design of trusses. 

2303.4.1.4.1 Truss design drawings. Where 
required by the registered design professional, the 
building official or the statutes of the jurisdiction in 
which the project is to be constructed, each individual 
truss design drawing shall bear the seal and signature 
of the truss designer. 

Exceptions: 

1. Where a cover sheet and truss index sheet 
are combined into a single sheet and 
attached to the set of truss design drawings, 
the single cover/truss index sheet is the only 
document required to be signed and sealed 
by the truss designer. 

2. When a cover sheet and a truss index sheet 
are separately provided and attached to the 
set of truss design drawings, the cover sheet 
and the truss index sheet are the only docu- 
ments required to be signed and sealed by 
the truss designer. 

2303.4.2 Truss placement diagram. The truss manufac- 
turer shall provide a truss placement diagram that identifies 
the proposed location for each individually designated truss 
and references the corresponding truss design drawing. The 
truss placement diagram shall be provided as part of the 
truss submittal package, and with the shipment of trusses 
delivered to the job site. Truss placement diagrams that 
serve only as a guide for installation and do not deviate from 
the permit submittal drawings shall not be required to bear 
the seal or signature of the truss designer. 

2303.4.3 Truss submittal package. The truss submittal 
package provided by the truss manufacturer shall consist of 
each individual truss design drawing, the truss placement 
diagram, the permanent individual truss member 
restraint/bracing method and details and any other structural 
details germane to the trusses; and, as applicable, the 
cover/truss index sheet. 

2303.4.4 Anchorage. The design for the transfer of loads 
and anchorage of each truss to the supporting structure is the 
responsibility of the registered design professional. 

2303.4.5 Alterations to trusses. Truss members and com- 
ponents shall not be cut, notched, drilled, spliced or other- 
wise altered in any way without written concurrence and 



2009 INTERNATIONAL BUILDING CODE® 



455 



WOOD 



approval of a registered design professional. Alterations 
resulting in the addition of loads to any member (e.g., 
HVAC equipment, piping, additional roofing or insulation, 
etc.) shall not be permitted without verification that the truss 
is capable of supporting such additional loading. 

2303.4.6 TPI 1 specifications. In addition to Sections 
2303.4.1 through 2303.4.5, the design, manufacture and 
quality assurance of metal-plate-connected wood trusses 
shall be in accordance with TPI 1. Job- site inspections shall 
be in compliance with Section 110.4, as applicable. 

2303.4.7 Truss quality assurance. Trusses not part of a 
manufacturing process in accordance with either Section 
2303.4.6 or a standard listed in Chapter 35, which provides 
requirements for quality control done under the supervision 
of a third-party quality control agency, shall be manufac- 
tured in compliance with Sections 1704.2 and 1704.6, as 
applicable. 

2303.5 Test standard forjoist hangers and connectors. For 
the required test standards forjoist hangers and connectors, see 
Section 1716.1. 

2303.6 Nails and staples. Nails and staples shall conform to 
requirements of ASTM F 1667. Nails used for framing and 
sheathing connections shall have minimum average bending 
yield strengths as follows: 80 kips per square inch (ksi) (551 
MPa) for shank diameters larger than 0.1 77 inch (4.50 mm) but 
not larger than 0.254 inch (6.45 mm), 90 ksi (620 MPa) for 
shank diameters larger than 0.142 inch (3.61 mm) but not 
larger than 0.177 inch (4.50 mm) and 100 ksi (689 MPa) for 
shank diameters of at least 0.099 inch (2.51 mm) but not larger 
than 0.142 inch (3.61 mm). 

2303.7 Shrinkage. Consideration shall be given in design to 
the possible effect of cross-grain dimensional changes consid- 
ered vertically which may occur in lumber fabricated in a green 
condition. 



SECTION 2304 
GENERAL CONSTRUCTION REQUIREMENTS 

2304.1 General. The provisions of this section apply to design 
methods specified in Section 2301.2. 



2304.2 Size of structural members. Computations to deter- 
mine the required sizes of members shall be based on the net 
dimensions (actual sizes) and not nominal sizes. 

2304.3 Wall framing. The framing of exterior and interior 
walls shall be in accordance with the provisions specified in 
Section 2308 unless a specific design is furnished. 

2304.3.1 Bottom plates. Studs shall have full bearing on a 
2-inch-thick (actual l 1 / 2 -inch, 38 mm) or larger plate or sill 
having a width at least equal to the width of the studs. 

2304.3.2 Framing over openings. Headers, double joists, 
trusses or other approved assemblies that are of adequate 
size to transfer loads to the vertical members shall be pro- 
vided over window and door openings in load-bearing walls 
and partitions. 

2304.3.3 Shrinkage. Wood walls and bearing partitions 
shall not support more than two floors and a roof unless an 
analysis satisfactory to the building official shows that 
shrinkage of the wood framing will not have adverse effects 
on the structure or any plumbing, electrical or mechanical 
systems, or other equipment installed therein due to exces- 
sive shrinkage or differential movements caused by shrink- 
age. The analysis shall also show that the roof drainage 
system and the foregoing systems or equipment will not be 
adversely affected or, as an alternate, such systems shall be 
designed to accommodate the differential shrinkage or 
movements. 

2304.4 Floor and roof framing. The framing ofwood-joisted 
floors and wood framed roofs shall be in accordance with the 
provisions specified in Section 2308 unless a specific design is 
furnished. 

2304.5 Framing around flues and chimneys. Combustible 
framing shall be a minimum of 2 inches (51 mm), but shall not 
be less than the distance specified in Sections 2111 and 2113 
and the International Mechanical Code, from flues, chimneys 
and fireplaces, and 6 inches (152 mm) away from flue open- 
ings. 

2304.6 Wall sheathing. Except as provided for in Section 1405 
for weatherboarding or where stucco construction that com- 
plies with Section 2510 is installed, enclosed buildings shall be 
sheathed with one of the materials of the nominal thickness 
specified in Table 2304.6 or any other approved material of 
equivalent strength or durability. 



TABLE 2304.6 
MINIMUM THICKNESS OF WALL SHEATHING 



SHEATHING TYPE 


MINIMUM THICKNESS 


MAXIMUM WALL STUD SPACING 


Wood boards 


5/ s inch 


24 inches on center 


Fiberboard 


i/ 2 inch 


16 inches on center 


Wood structural panel 


In accordance with Tables 2308.9.3(2) and 2308.9.3(3) 




M-S "Exterior Glue" and M-2 
"Exterior Glue" Particleboard 


In accordance with Tables 2306.5 and 2308.9.3(4) 




Gypsum sheathing 


i/ 2 inch 


16 inches on center 


Gypsum wallboard 


i/ 2 inch 


24 inches on center 


Reinforced cement mortar 


1 inch 


24 inches on center 



For 51: 1 inch = 25.4 mini. 



456 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2304.6.1 Wood structural panel sheathing. Where wood 
structural panel sheathing is used as the exposed finish on 
the exterior of outside walls, it shall have an exterior expo- 
sure durability classification. Where wood structural panel 
sheathing is used elsewhere, but not as the exposed finish, it 
shall be of a type manufactured with exterior glue (Exposure 
1 or Exterior). Wood structural panel wall sheathing or sid- 
ing used as structural sheathing shall be capable of resisting 
wind pressures in accordance with Section 1609. Maximum 
wind speeds for wood structural panel sheathing used to 
resist wind pressures shall be in accordance with Table 

2304.6.1 for enclosed buildings with a mean roof height not 
greater than 30 feet (9144 mm), an importance factor (1) of 
1.0 and a topographic factor (K,) of 1.0. 

2304.6.2 Interior paneling. Softwood wood structural 
panels used for interior paneling shall conform to the pro- 
visions of Chapter 8 and shall be installed in accordance 
with Table 2304.9.1 . Panels shall comply with DOC PS 1 
or PS 2. Prefinished hardboard paneling shall meet the 



requirements of CPA/ANSI A135.5. Hardwood plywood 
shall conform to HPVA HP-1. 

2304.7 Floor and roof sheathing. 

2304.7.1 Structural floor sheathing. Structural floor 
sheathing shall be designed in accordance with the general 
provisions of this code and the special provisions in this sec- 
tion. 

Floor sheathing conforming to the provisions of Table 
2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(4) shall be 
deemed to meet the requirements of this section. 

2304.7.2 Structural roof sheathing. Structural roof sheath- 
ing shall be designed in accordance with the general provi- 
sions of this code and the special provisions in this section. 

Roof sheathing conforming to the provisions of Table 
2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(5) shall be 
deemed to meet the requirements of this section. Wood struc- 
tural panel roof sheathing shall be bonded by exterior glue. 



TABLE 2304.6.1 

MAXIMUM BASIC WIND SPEED (mph) (3-SECOND GUST) PERMITTED FOR 

WOOD STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND PRESSURES a ,b,c 



MINIMUM NAM 


MINIMUM WOOD 

STRUCTURAL 

PANEL SPAN 

RATING 


MINIMUM 

NOMINAL PANEL 

THICKNESS 

(inches) 


MAXIMUM 

WAN STUD 

SPACING 

(inches) 


PANEL NAM SPACING 


MAXIMUM WIND SPEED (MPH) 


Size 


Penetration 
(inches) 


Edges 
(inches o.c.) 


Field 
(inches o.c.) 




B 


c 


D 


6d common 
(2.0" x 0.113") 


1.5 


24/0 


3/ R 


16 


6 


12 


110 


90 


85 


24/16 


7/ 16 


16 


6 


12 


110 


100 


90 


6 


150 


125 


110 


8d common 
(2.5" x 0.131") 


1.75 


24/16 


7/ 16 


16 


6 


12 


130 


110 


105 


6 


150 


125 


110 


24 


6 


12 


110 


90 


85 


6 


110 


90 


85 



For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 rn/s. 

a. Panel strength axis shall be parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied 
with panel strength axis perpendicular to supports. 

b. The table is based on wind pressures acting toward and away from building surfaces in accordance with Section 6.4.2.2 of ASCE 7. Lateral requirements shall be in 
accordance with Section 2305 or 2308. 

c. Wood structural panels with span ratings ofwall-16 or wall-24 shall be permitted as an alternative to panels with a 24/0 span rating. Plywood siding rated 16 o.c. or 
24 o.c. shall be permitted as an alternative to panels with a 24/16 span rating. Wall- 16 and plywood siding 16 o.c. shall be used with studs spaced a maximum of 16 
inches o.c. 

TABLE 2304.7(1) 
ALLOWABLE SPANS FOR LUMBER FLOOR AND ROOF SHEATHING 3 , b 



SPAN (inches) 


MINIMUM NET THICKNESS (inches) OF IUMBER PLACED 


Perpendicu 


lar to supports | Diagonally to supports 


Surfaced dryc 


1 Surfaced unseasoned | Surfaced dryc | Surfaced unseasoned 


Floors 


24 
16 


3/ 4 
5/ S 


25/ 32 3/ 4 25/ 32 
1 U/ 16 1 5/ 8 1 U/ 16 


Roofs 


24 


SI. 


1 Ul m 1 3 U 1 25/ 37 



For SI: 1 inch = 25.4 mm. 

a. Installation details shall conform to Sections 2304.7.1 and 2304.7.2 for floor and roof sheathing, respectively. 

b. Floor or roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7. 

c. Maximum 19-percent moisture content. 



2009 INTERNATIONAL BUILDING CODE® 



457 



WOOD 



TABLE 2304.7(2) 
SHEATHING LUMBER, MINIMUM GRADE REQUIREMENTS: BOARD GRADE 



SOLID FLOOR OR ROOF SHEATHING 


SPACED ROOF SHEATHING 


GRADING RULES 


Utility 


Standard 


NLGA, WCLIB, WWPA 


4 common or utility 


3 common or standard 


NLGA, WCLIB, WWPA, NSLB or NELMA 


No. 3 


No. 2 


SPIB 


Merchantable 


Construction common 


RIS 



TABLE 2304.7(3) 

ALLOWABLE SPANS AND LOADS FOR WOOD STRUCTURAL PANEL SHEATHING AND 

SINGLE-FLOOR GRADES CONTINUOUS OVER TWO OR MORE SPANS WITH 

STRENGTH AXIS PERPENDICULAR TO SUPPORTS a ,b 





SHEATHING GRADES 


ROOF 


c 


FLOOR d 




Panel span rating 
roof/floor span 


Panel thickness 
(inches) 


Maximum span (inches) 


Load 6 (pst) 


Maximum span 
(inches) 


• 


With edge support 1 


Without edge support 


Total load 


Live load 


16/0 


3/ s 


16 


16 


40 


30 





1 


20/0 


3/ s 


20 


20 


40 


30 







24/0 


3/ s < 7/ 16 , l/ 2 


24 


20§ 


40 


30 







24/16 


7/ 16 ,l/ 2 


24 


24 


50 


40 


16 




32/16 


15/ 32 , l/ 2 , 5/ s 


32 


28 


40 


30 


16 h 




40/20 


19/ 32 , 5/S' 3/ 4 , 7/S 


40 


32 


40 


30 


20h,i 




48/24 


23/ 32 ,3/ 4 ,7/ s 


48 


36 


45 


35 


24 




54/32 


7/ s ' 1 


54 


40 


45 


35 


32 




60/32 


7/ S ' l^S 


60 


48 


45 


35 


32 




SINGLE FLOOR GRADES 


ROOF 


c 


FLOOR d 




Panel span rating 


Panel thickness 
(inches) 


Maximum span (inches) 


Load 6 (pst) 


Maximum span 
(inches) 




With edge support 1 


Without edge support 


Total load 


Live load 




16 o.c. 


l/ 2 , 19/ 32 , 5/ s 


24 


24 


50 


40 


16 h 




20o.c. 


19/ 32 , 5/ s ' 3/ 4 


32 


32 


40 


30 


20h,i 




24 o.c. 


23/ 32 , 3/ 4 


48 


36 


35 


25 


24 




32 o.c. 


7/ s ' 1 


48 


40 


50 


40 


32 




48 o.c. 


i 3 / 32 , iV s 


60 


48 


50 


40 


48 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m z . 

a. Applies to panels 24 inches or wider. 

b. Floor and roof sheathing conforming with this table shall be deemed to meet the design criteria ofSection 2304.7. 

c. Uniform load deflection limitations u 180 of span under live load plus dead load, u z40 under live load only. 

d. Panel edges shall have approved tongue-and-groovejoints or shall be supported with blocking unless i/ 4 -inch minimum thickness underlayment or )V z inches of 
approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/ 4 -inch wood strip. Allowable uniform load based on deflection of i/ m of 
span is 100 pounds per square foot except the span rating of 48 inches on center is based on a total load of 65 pounds per square foot. 

e. Allowable load at maximum span. 

f. Tongue-and-groove edges , panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center) , lumber block- 
ing or other. Only lumber blocking shall satisfy blocked diaphragm requirements. 

g. For liz-inch panel, maximum span shall be 24 inches. 

h. Span is permitted to be 24 inches on center where 3/ 4 -inch wood strip flooring is installed at right angles to joist. 

i. Span is permitted to be 24 inches on center for floors where f/ z inches of cellular or lightweight concrete is applied over the panels. 



458 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



TABLE 2304.7(4) 

ALLOWABLE SPAN FOR WOOD STRUCTURAL PANEL COMBINATION SUBFLOOR-UNDERLAYMENT (SINGLE FLOOR)a, b 

(Panels Continuous Over Two or More Spans and Strength Axis Perpendicular to Supports) 



IDENTIFICATION 


MAXIMUM SPACING OF JOISTS (inches) 


16 


20 


24 


32 


48 


Species groupe 


Thickness (inches) 


1 


i/ 2 


5/ 8 


3/4 






2,3 


5/ 8 


3/ 4 


7/ 8 






4 


^4 


7/ 8 


1 


- 


- 


Single floor span rating d 


16 o.c. 


20 o.c. 


24 o.c. 


32 o.c. 


48 o.c. 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m 2 > 

a. Spans limited to value shown because of possible effects of concentrated loads. Allowable uniform loads based on deflection of 11 360 of span is 100 pounds per 
square foot except allowable total uniform load for ^/^inch wood structural panels overjoists spaced 48 inches on center is 65 pounds per square foot. Panel edges 
shall have approved tongue-and-groovejoints or shall be supported with blocking, unless i/ 4 -inch minimum thickness underlayment or 1 ] / 2 inches of approved cel- 
lular or lightweight concrete is placed over the sub floor, or finish floor is 3/ 4 -inch wood strip. 

b. Floor panels conforming with this table shall be deemed to meet the design criteria of Section 2304.7. 

c. Applicable to all grades of sanded exterior-type plywood. See DOC PS 1 for plywood species groups. 

d. Applicable to Underlayment grade, C-C (Plugged) plywood, and Single Floor grade wood structural panels. 



TABLE 2304.7(5) 

ALLOWABLE LOAD (PSF) FOR WOOD STRUCTURAL PANEL ROOF SHEATHING CONTINUOUS OVER 

TWO OR MORE SPANS AND STRENGTH AXIS PARALLEL TO SUPPORTS 

(Plywood Structural Panels Are Five-Ply, Five-Layer Unless Otherwise Noted)a, b 



PANEL GRADE 


THICKNESS (inch) 


MAXIMUM SPAN (inches) 


LOAD AT MAXIMUM SPAN (pst) 


Live 


Total 




7/ 16 


24 


20 


30 




15/ 32 


24 


35 c 


45 c 


Structural I sheathing 


ll 2 


24 


40 c 


SOc 




19/^, 5/ g 


24 


70 


80 




23/ 32 ,3/ 4 


24 


90 


100 




7/ 16 


16 


40 


50 




15/ 32 


24 


20 


25 


Sheathing, other grades 


17 2 


24 


25 


30 


covered in DOC PS 1 or 










DOC PS 2 


19/ 32 


24 


40 c 


SOc 




5/ 8 


24 


45 c 


sse 




23/ 32 ,3/ 4 


24 


60 c 


65 c 



For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kN/m 2 > 

a. Roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7. 

b. Uniform load deflection limitations i/ 180 of span under live load plus dead load, i/ 240 under live load only. Edges shall be blocked with lumber or other approved type 
of edge supports. 

c. For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds per square foot. 



2009 INTERNATIONAL BUILDING CODE® 



459 



WOOD 



2304.8 Lumber decking. 

2304.8.1 General. Lumber decking shall be designed and 
installed in accordance with the general provisions of this 
code and Section 2304.8. Each piece shall be square end 
trimmed. When random lengths are furnished, each piece 
shall be square end trimmed across the face so that at least 
90 percent of the pieces are within 0.5 degrees (0.00873 rad) 
of square. The ends of the pieces shall be permitted to be 
beveled up to 2 degrees (0.0349 rad) from the vertical with 
the exposed face of the piece slightly longer than the oppo- 
site face of the piece. Tongue-and-groove decking shall be 
installed with the tongues up on sloped or pitched roofs with 
pattern faces down. 

2304.8.2 Layup patterns. Lumber decking is permitted to 
be laid up following one of five standard patterns as defined 
in Sections 2304.8.2.1 through 2304.8.2.5. Other patterns 
are permitted to be used provided they are substantiated 
through engineering analysis. 

2304.8.2.1 Simple span pattern. All pieces shall be sup- 
ported on their ends (i.e., by two supports). 

2304.8.2.2 Two-span continuous pattern. All pieces 
shall be supported by three supports, and all end joints 
shall occur in line on alternating supports. Supporting 
members shall be designed to accommodate the load 
redistribution caused by this pattern. 

2304.8.2.3 Combination simple and two-span contin- 
uous pattern. Courses in end spans shall be alternating 
simple-span pattern and two-span continuous pattern. 
End joints shall be staggered in adjacent courses and 
shall bear on supports. 

2304.8.2.4 Cantilevered pieces intermixed pattern. 
The decking shall extend across a minimum of three 
spans. Pieces in each starter course and every third 
course shall be simple span pattern. Pieces in other 
courses shall be cantilevered over the supports with end 
joints at alternating quarter or third points of the spans. 
Each piece shall bear on at least one support. 

2304.8.2.5 Controlled random pattern. The decking 
shall extend across a minimum of three spans. Endjoints 
of pieces within 6 inches (152 mm) of the endjoints of 
the adjacent pieces in either direction shall be separated 
by at least two intervening courses. In the end bays, each 
piece shall bear on at least one support. Where an end 
joint occurs in an end bay, the next piece in the same 
course shall continue over the first inner support for at 
least 24 inches (610 mm). The details of the controlled 
random pattern shall be as specified for each decking 
material in Section 2304.8.3.3,2304.8.4.3 or 2304.8.5.3. 

Decking that cantilevers beyond a support for a hori- 
zontal distance greater than 18 inches (457 mm), 24 
inches (610 mm) or 36 inches (914 mm) for 2-inch (51 
mm), 3-inch (76 mm) and 4-inch (102 mm) nominal 
thickness decking, respectively, shall comply with the 
following: 

1. The maximum cantilevered length shall be 30 per- 
cent of the length of the first adjacent interior span. 



2. A structural fascia shall be fastened to each deck- 
ing piece to maintain a continuous, straight line. 

3. There shall be no endjoints in the decking between 
the cantilevered end of the decking and the center- 
line of the first adjacent interior span. 

2304.8.3 Mechanically laminated decking. 

2304.8.3.1 General. Mechanically laminated decking 
consists of square-edged dimension lumber laminations 
set on edge and nailed to the adjacent pieces and to the 
supports. 

2304.8.3.2 Nailing. The length of nails connecting lami- 
nations shall not be less than two and one-half times the 
net thickness of each lamination. Where decking sup- 
ports are 48 inches (1219 mm) on center (o.c.) or less, 
side nails shall be installed not more than 30 inches (762 
mm) o.c. alternating between top and bottom edges, and 
staggered one-third of the spacing in adjacent lamina- 
tions. Where supports are spaced more than 48 inches 
(1219 mm) o.c, side nails shall be installed not more 
than 18 inches (457 mm) o.c. alternating between top and 
bottom edges and staggered one-third of the spacing in 
adjacent laminations. Two side nails shall be installed at 
each end of butt -jointed pieces. 

Laminations shall be toenailed to supports with 20d or 
larger common nails. Where the supports are 48 inches 
(1219 mm) o.c. or less, alternate laminations shall be 
toenailed to alternate supports; where supports are 
spaced more than 48 inches (1219 mm) o.c, alternate 
laminations shall be toenailed to every support. 

2304.8.3.3 Controlled random pattern. There shall be 
a minimum distance of 24 inches (610 mm) between end 
joints in adjacent courses. The pieces in the first and sec- 
ond courses shall bear on at least two supports with end 
joints in these two courses occurring on alternate sup- 
ports. A maximum of seven intervening courses shall be 
permitted before this pattern is repeated. 

2304.8.4 Two-inch sawn tongue-and-groove decking. 

2304.8.4.1 General. Two-inch (51 mm) decking shall have 
a maximum moisture content of 15 percent. Decking shall 
be machined with a single tongue-and-groove pattern. Each 
decking piece shall be nailed to each support. 

2304.8.4.2 Nailing. Each piece of decking shall be 
toenailed at each support with one 16d common nail 
through the tongue and face-nailed with one 16d com- 
mon nail. 

2304.8.4.3 Controlled random pattern. There shall be 
a minimum distance of 24 inches (610 mm) between end 
joints in adjacent courses. The pieces in the first and sec- 
ond courses shall bear on at least two supports with end 
joints in these two courses occurring on alternate sup- 
ports. A maximum of seven intervening courses shall be 
permitted before this pattern is repeated. 

2304.8.5 Three- and 4-inch sawn tongue-and-groove 
decking. 



460 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2304.8.5.1 General. Three-inch (76 mm) and 4-inch 
(102 mm) decking shall have a maximum moisture con- 
tent of 19 percent. Decking shall be machined with a 
double tongue-and-groove pattern. Decking pieces shall 
be interconnected and nailed to the supports. 

2304.8.5.2 Nailing. Each piece shall be toenailed at each 
support with one 40d common nail and face-nailed with 
one 60d common nail. Courses shall be spiked to each other 
with 8-inch (203 mm) spikes at maximum intervals of 30 
inches (762 mm) through predrilled edge holes penetrating 
to a depth of approximately 4 inches (102 mm). One spike 
shall be installed at a distance not exceeding 10 inches (254 
mm) from the end of each piece. 

2304.8.5.3 Controlled random pattern. There shall be 
a minimum distance of 48 inches (1219 mm) between 
end joints in adjacent courses. Pieces not bearing on a 
support are permitted to be located in interior bays pro- 
vided the adjacent pieces in the same course continue 
over the support for at least 24 inches (610 mm). This 
condition shall not occur more than once in every six 
courses in each interior bay. 

2304.9 Connections and fasteners. 

2304.9.1 Fastener requirements. Connections for wood 
members shall be designed in accordance with the appropri- 
ate methodology in Section 2301.2. The number and size of 
fasteners connecting wood members shall not be less than 
that set forth in Table 2304.9.1. 

2304.9.2 Sheathing fasteners. Sheathing nails or other 
approved sheathing connectors shall be driven so that their 
head or crown is flush with the surface of the sheathing. 

2304.9.3 Joist hangers and framing anchors. Connec- 
tions depending on joist hangers or framing anchors, ties 
and other mechanical fastenings not otherwise covered are 
permitted where approved. The vertical load-bearing capac- 
ity, torsional moment capacity and deflection characteris- 
tics ofjoist hangers shall be determined in accordance with 
Section 1716.1. 

2304.9.4 Other fasteners. Clips, staples, glues and other 
approved methods of fastening are permitted where 
approved. 

2304.9.5 Fasteners and connectors in contact with pre- 
servative-treated and fire-retardant-treated wood. Fas- 
teners and connectors in contact with preservative-treated 
mid fire-retardant-treated wood shall be in accordance with 
Sections 2304.9.5.1 through 2304.9.5.4. The coating 
weights for zinc-coated fasteners shall be in accordance 
with ASTM A 153. 

2304.9.5.1 Fasteners and connectors for preserva- 
tive-treated wood. Fasteners in contact with preserva- 
tive-treated wood shall be of hot-dipped zinc-coated 
galvanized steel, stainless steel, silicon bronze or copper. 
Fasteners other than nails, timber rivets, wood screws 
and lag screws shall be permitted to be of mechanically 
deposited zinc-coated steel with coating weights in 
accordance with ASTM B 695, Class 55 minimum. Con- 
nectors that are used in exterior applications and in con- 



tact with preservative-treated wood shall have coating 
types and weights in accordance with the treated wood or 
connector manufacturer's recommendations. In the 
absence of manufacturer's recommendations, a mini- 
mum of ASTM A 653, type G185 zinc-coated galva- 
nized steel, or equivalent, shall be used. 

Exception: Plain carbon steel fasteners in SBX/DOT 
and zinc borate preservative-treated wood in an inte- 
rior, dry environment shall be permitted. 

2304.9.5.2 Fastenings for wood foundations. Fasten- 
ings for wood foundations shall be as required in AF&PA 
PWF. 

2304.9.5.3 Fasteners for fire-retardant-treated wood 
used in exterior applications or wet or damp loca- 
tions. Fasteners fox fire-retardant-treated wood used in 
exterior applications or wet or damp locations shall be of 
hot-dipped zinc-coated galvanized steel, stainless steel, 
silicon bronze or copper. Fasteners other than nails, tim- 
ber rivets, wood screws and lag screws shall be permitted 
to be of mechanically deposited zinc-coated steel with 
coating weights in accordance with ASTM B 695, Class 
55 minimum. 

2304.9.5.4 Fasteners for fire-retardant-treated wood 
used in interior applications. Fasteners for fire-retar- 
dant-treated wood used in interior locations shall be in 
accordance with the manufacturer's recommendations. 
In the absence of manufacturer's recommendations, Sec- 
tion 2304.9.5.3 shall apply. 

2304.9.6 Load path. Where wall framing members are not 
continuous from foundation sill to roof, the members shall 
be secured to ensure a continuous load path. Where 
required, sheet metal clamps, ties or clips shall be formed of 
galvanized steel or other approve dcorrosion-resistant mate- 
rial not less than 0.040 inch (1.01 mm) nominal thickness. 

2304.9.7 Framing requirements. Wood columns and posts 
shall be framed to provide full end bearing. Alternatively, 
column-and-post end connections shall be designed to resist 
the full compressive loads, neglecting end-bearing capacity. 
Column-and-post end connections shall be fastened to resist 
lateral and net induced uplift forces . 

2304.10 Heavy timber construction. 

2304.10.1 Columns. Columns shall be continuous or super- 
imposed throughout all stories by means of reinforced con- 
crete or metal caps with brackets, or shall be connected by 
properly designed steel or iron caps, with pintles and base 
plates, or by timber splice plates affixed to the columns by 
metal connectors housed within the contact faces, or by 
other approved methods. 

2304.10.1.1 Column connections. Girders and beams 
shall be closely fitted around columns and adjoining 
ends shall be cross tied to each other, or intertied by caps 
or ties, to transfer horizontal loads across joints. Wood 
bolsters shall not be placed on tops of columns unless the 
columns support roof loads only. 



2009 INTERNATIONAL BUILDING CODE® 



461 



WOOD 



TABLE 2304.9.1 
FASTENING SCHEDULE 



CONNECTION 


FASTENING 3 , m 


LOCATION 


I. ] oist to sill or girder 


3 -8d common (2V 2 " x 0.131") 
3 -3" x 0.131" nails 
3 - 3" 14 gage staples 


toenail 


2. Bridging tojoist 


2 -8d common (2 1 / 2 n x 0.131") 
2-3" x 0.131" nails 
2-3" 14 gage staples 


toenail each end 


3. 1" x 6" subfloor or less to eachjoist 


2 - 8d common (2 V x 0.131") 


face nail 


4. Wider than 1" x 6" subfloor to eachjoist 


3 - 8d common (2V 2 " x 0.131") 


face nail 


5. 2" subfloor tojoist or girder 


2 - 16d common (3 V x 0.162") 


blind and face nail 


6. Sale plate tojoist or blocking 

Sale plate tojoist or blocking at braced 
wall panel 


16d (3 V x 0.135") at 16" o.c. 
3" x 0.131" nails at 8" o.c. 
3" 14 gage staples at 12" o.c. 

3- 16d (3 V x 0.135") at 16" o.c. 
4-3" x 0.131" nails at 16" o.c. 
4 - 3" 14 gage staples at 16" o.c. 


typical face nail 
braced wall panels 


7. Top plate to stud 


2 - 16d common (3 V x 0.162") 

3 -3" x 0.131" nails 
3 - 3" 14 gage staples 


end nail 


8. Stud to sale plate 


4 -8d common (2 1 / 2 " x 0.131") 
4-3" x 0.131" nails 
3-3" 14 gage staples 

2 - 16d common (3 V x 0.162") 

3 -3" x 0.131" nails 
3-3" 14 gage staples 


toenail 
end nail 


9. Double studs 


16d (3 V x 0.135") at 24" o.c. 
3" x 0.131" nail at 8" o.c. 
3" 14 gage staple at 8" o.c. 


face nail 


10. Double top plates 
Double top plates 


16d (3 V x 0.135") at 16" o.c. 
3" x 0.131" nail at 12" o.c. 
3" 14 gage staple at 12" o.c. 

8 - 16d common (3 V x 0.162") 
12-3" x 0.131" nails 
12 - 3" 14 gage staples 


typical face nail 
lap splice 


II. Blocking between joists or rafters to top plate 


3 - 8d common (2 V x 0.131") 
3 - 3" x 0.131" nails 
3 - 3" 14 gage staples 


toenail 


12. Rim joist to top plate 


8d (2 V x 0.131") at 6" o.c. 
3" x 0.131" nail at 6" o.c. 
3" 14 gage staple at 6" o.c. 


toenail 


13. Top plates, laps and intersections 


2 - 16d common (3 V x 0.162") 

3 - 3" x 0.131" nails 
3 - 3" 14 gage staples 


face nail 


14. Continuous header, two pieces 


16d common (3 V x 0.162") 


16" o.c. along edge 


15. Ceilingjoists to plate 


3 -8d common (2 1 / 2 " x 0.131") 
5 -3" x 0.131" nails 
5-3" 14 gage staples 


toenail 


16. Continuous header to stud 


4 -8d common (2 1 / 2 " x 0.131") 


toenail 



(continued) 



462 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 





TABLE 2304.9.1-continued 
FASTENING SCHEDULE 




CONNECTION 


FASTENING 3 , m 


LOCATION 


17. Ceilingjoists, laps over partitions 

(see Section 2308.1004.1, Table 2308.1004.1) 


3 - 16d common (3 1 / 2 " x 0.162") minimum, 
Table 2308.1004.1 

4-3" x 0.131" nails 

4 - 3" 14 gage staples 


face nail 


18. Ceilingjoists to parallel rafters 

(see Section 2308. 1004.1, Table 2308.1004.1) 


3 - 16d common (3 1 / 2 " x 0.162") minimum, 
Table 2308.1004.1 

4-3" x 0.131" nails 

4 - 3" 14 gage staples 


face nail 


19. Rafter to plate 

(see Section 2308.10.1, Table 2308.10.1) 


3 - 8d common (2 1 / 2 " x 0.131") 
3 - 3" x 0.131" nails 
3 - 3" 14 gage staples 


toenail 


20. 1" diagonal brace to each stud and plate 


2 - 8d common (2 1 / 2 " x 0.131") 
2-3" x 0.131" nails 

3 - 3" 14 gage staples 


face nail 


21. 1" x 8" sheathing to each bearing 


3 - 8d common (2h 2 « x 0.131") 


face nail 


22. Wider than 1" x 8" sheathing to each bearing 


3 - 8d common (2V 2 " x 0.131") 


face nail 


23. Built-up corner studs 


16d common (3 1 / 2 M x 0.162") 
3" x 0.131" nails 
3" 14 gage staples 


24" o.c. 
16" o.c. 
16" o.c. 


24. Built-up girder and beams 


20d common (4" x 0.192") 32" o.c. 
3" x 0.131" nail at 24" o.c. 
3" 14 gage staple at 24" o.c. 

2 - 20d common (4" x 0.192") 

3 -3" x 0.131" nails 
3 - 3" 14 gage staples 


face nail at top and bottom staggered 
on opposite sides 

face nail at ends and at each splice 


25. 2" planks 


16d common (3 1 / 2 M x 0.162") 


at each bearing 


26. Collar tie to rafter 


3 - lOd common (3" x 0.148") 
4-3" x 0.131" nails 

4 - 3" 14 gage staples 


face nail 


27 . Jack rafter to hip 


3 - lOd common (3" x 0.148") 
4-3" x 0.131" nails 

4 - 3" 14 gage staples 

2 - 16d common (3V 2 " x 0.162") 

3 - 3" x 0.131" nails 
3 - 3" 14 gage staples 


toenail 
face nail 


28. Roof rafter to 2-by ridge beam 


2 - 16d common (3V 2 " x 0.162") 

3 -3" x 0.131" nails 
3 - 3" 14 gage staples 

2 -16d common (3 1 / 2 " x 0.162") 

3 -3" x 0.131" nails 
3 - 3" 14 gage staples 


toenail 
face nail 


29. Joist to band joist 


3 - 16d common (3 1 / 2 M x 0.162") 
4-3" x 0.131" nails 

4 - 3" 14 gage staples 


face nail 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



463 



WOOD 



TABLE 2304.9.1 -continued 
FASTENING SCHEDULE 



CONNECTION 


FASTENINGa, m 


LOCATION 


30. Ledger strip 


3 - 16d common Q, 1 /^ x 0.162") 
4-3" x 0.131" nails 

4 - 3" 14 gage staples 


face nail at each joist 


31. Wood structural panels and particleboard b 
Subfloor, roof and wall sheathing (to framing) 

Single floor (combination subfloor-underlayment 
to framing) 


i/ 2 " and less 6dC l 

2 3 / 8 " x 0.113" nail n 

l 3 / 4 " 16gageO 
i9/ 32 " to 3/ 4 " 8dd or 6d e 

2 3 / 8 " x 0.113" nail? 

2" 16 gage? 
7/ 8 " to 1" 8d c 
lV 8 " to 1V4" 10d d or8d e 

3/4" and less 6d e 
7/ 8 " to 1" 8d e 
lV to 1V4" 10d d or8d e 




32. Panel siding (to framing) 


i/ 2 " or less 6d f 
5/ R " 8d f 




33. Fiberboard sheathing 8 


1/ 2 No. 11 gage roofing nail h 

6d common nail (2" x 0.113") 

No. 16 gage staple' 
25/ 32 " No. 11 gage roofing nail h 

8d common nail (2 1 / 2 " x 0.131") 

No. 16 gage staple' 




34. Interior paneling 


1/4" 4dJ 
3/ R " 6d k 





For SI: 1 inch = 25.4 mm. 

a. Common or box nails are permitted to be used except where otherwise stated. 

b. Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports except 6 inches at supports where spans are 48 inches or more. For nailing of wood 
structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing. 

c. Common or deformed shank (6d - 2" x 0.113"; 8d - 27 2 " x 0.131"; lOd - 3" x 0.148"). 

d. Common (6d - 2" x 0.113"; 8d - 27 2 " x 0.131"; lOd - 3" x 0.148"). 

e. Deformed shank (6d - 2" x 0.113"; 8d - 27 2 " x 0.131"; lOd - 3" x 0.148"). 

f. Corrosion-resistant siding (6d - f/ 8 " x 0.106"; 8d - 2 3 / 8 " x 0.128") or casing (6d - 2" x 0.099"; 8d - 27 2 " x 0.113") nail. 

g. Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate supports, when used as structural sheathing. Spacing shall be 6 inches 
on center on the edges and 12 inches on center at intermediate supports for nonstructural applications. 

h. Corrosion-resistant roofing nails with 7/ 16 -inch-diameter head and lV z -inch length for liz-inch sheathing and l7 4 -inch length for z5/3z-inch sheathing. 

i. Corrosion-resistant staples with nominal 1 i 16 -inch crown or I-inch crown and l 1 / 4 -inch length for liz-inch sheathing and lV^inch length for z5/3z-inch sheathing. 
Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked). 

j. Casing (11/ £ x 0.080") or finish (lV 2 " x 0.072") nails spaced 6 inches on panel edges, 12 inches at intermediate supports. 

k. Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, 12 inches at intermediate supports. 

1. For roof sheathing applications, 8d nails (2 1 //' x 0.113") are the minimum required for wood structural panels. 

m. Staples shall have a minimum crown width of 7/ 76 inch. 

n. For roof sheathing applications, fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports. 

o. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor and wall sheathing and 3 inches on center at edges, 6 inches at interme- 
diate supports for roof sheathing. 

p. Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports. 



464 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2304.10.2 Floor framing. Approve d wall plate boxes or 
hangers shall be provided where wood beams, girders or 
trusses rest on masonry or concrete walls. Where intermedi- 
ate beams are used to support a floor, they shall rest on top of 
girders, or shall be supported by ledgers or blocks securely 
fastened to the sides of the girders, or they shall be sup- 
ported by an approvedmztai hanger into which the ends of 
the beams shall be closely fitted. 

2304.10.3 Roof framing. Every roof girder and at least 
every alternate roof beam shall be anchored to its supporting 
member; and every monitor and every sawtooth construc- 
tion shall be anchored to the main roof construction. Such 
anchors shall consist of steel or iron bolts of sufficient 
strength to resist vertical uplift of the roof. 

2304.10.4 Floor decks. Floor decks and covering shall not 
extend closer than i/ 2 inch (12.7 mm) to walls. Such i/ 2 -inch 
(12.7 mm) spaces shall be covered by a molding fastened to 
the wall either above or below the floor and arranged such 
that the molding will not obstruct the expansion or contrac- 
tion movements of the floor. Corbeling of masonry walls 
under floors is permitted in place of such molding. 

2304.10.5 Roof decks. Where supported by a wall, roof 
decks shall be anchored to walls to resist uplift forces deter- 
mined in accordance with Chapter 16. Such anchors shall 
consist of steel or iron bolts of sufficient strength to resist 
vertical uplift of the roof. 

2304.11 Protection against decay and termites. 

2304.11.1 General. Where required by this section, protec- 
tion from decay and termites shall be provided by the use of 
naturally durable or preservative-treated wood. 

2304.11.2 Wood used above ground. Wood used above 
ground in the locations specified in Sections 2304.11.2.1 
through 2304.11.2.7, 2304.11.3 and 2304.11.5 shall be nat- 
urally durable wood or preservative-treated wood using 
water-borne preservatives, in accordance with AWPA Ul 
(Commodity Specifications A or F) for above-ground use. 

2304.11.2.1 Joists, girders and subfloor. Where wood 
joists or the bottom of a wood structural floor withoutjoists 
are closer than 18 inches (457 mm), or wood girders are 
closer than 12 inches (305 mm) to the exposed ground in 
crawl spaces orunexcavated areas located within the perim- 
eter of the building foundation, the floor construction 
(including posts, girders, joists and subfloor) shall be of 
naturally durable or preservative-treated wood. 

2304.11.2.2 Wood supported by exterior foundation 
walls. Wood framing members, including wood sheath- 
ing, that rest on exterior foundation walls and are less 
than 8 inches (203 mm) from exposed earth shall be of 
naturally durable or pre servative -treated wood. 

2304.11.2.3 Exterior walls below grade. Wood fram- 
ing members and furring strips attached directly to the 
interior of exterior masonry or concrete walls below 
grade shall be of appro vednaturally durable or preserva- 
tive-treated wood. 



2304.11.2.4 Sleepers and sills. Sleepers and sills on a 
concrete or masonry slab that is in direct contact with earth 
shall be of naturally durable or preservative-treatedwood. 

2304.11.2.5 Girder ends. The ends of wood girders 
entering exterior masonry or concrete walls shall be pro- 
vided with a i/ 2 -inch (12.7 mm) air space on top, sides 
and end, unless naturally durable ox preservative-treated 
woodis used. 

2304.1 1.2.6 Wood siding. Clearance between wood sid- 
ing and earth on the exterior of a building shall not be less 
than 6 inches (152 mm) or less than 2 inches (51 mm) 
vertical from concrete steps, porch slabs, patio slabs and 
similar horizontal surfaces exposed to the weather except 
where siding, sheathing and wall framing are of naturally 
durable or preservative-treated wood. 

2304.11.2.7 Posts or columns. Posts or columns sup- 
porting permanent structures and supported by a con- 
crete or masonry slab or footing that is in direct contact 
with the earth shall be of naturally durable or preserva- 
tive-treated wood. 

Exceptions: 

1. Posts or columns that are either exposed to the 
weather or located in basements or cellars, sup- 
ported by concrete piers or metal pedestals pro- 
jected at least 1 inch (25 mm) above the slab or 
deck and 6 inches (152 mm) above exposed 
earth, and are separated therefrom by an imper- 
vious moisture barrier. 

2. Posts or columns in enclosed crawl spaces or 
unexcavated areas located within the periphery of 
the building, supported by a concrete pier or metal 
pedestal at a height greater than 8 inches (203 
mm) from exposed ground, and are separated 
therefrom by an impervious moisture barrier. 

2304.11.3 Laminated timbers. The portions ofglued-lam- 
inated timbers that form the structural supports of a building 
or other structure and are exposed to weather and not fully 
protected from moisture by a roof, eave or similar covering 
shall be pressure treated with preservative or be manufac- 
tured from naturally durable or preservative-treatedwood. 

2304. 1 1 .4 Wood in contact with the ground or fresh water. 
Wood used in contact with the ground (exposed earth) in the 
locations specified in Sections 2304.11 .4.1 and 2304.11 .4.2 
shall be naturally durable (species for both decay and termite 
resistance) or preservative treated using water-borne preser- 
vatives in accordance with AWPA Ul (Commodity Specifi- 
cations A or F) for soil or fresh water use. 

Exception: Untreated wood is permitted where such 
wood is continuously and entirely below the ground- 
water level or submerged in fresh water. 

2304.11.4.1 Posts or columns. Posts and columns sup- 
porting permanent structures that are embedded in con- 
crete that is in direct contact with the earth, embedded in 
concrete that is exposed to the weather or in direct con- 
tact with the earth shall be of preservative-treatedwood. 



2009 INTERNATIONAL BUILDING CODE® 



465 



WOOD 



2304.11.4.2 Wood structural members. Wood struc- 
tural members that support moisture-permeable floors or 
roofs that are exposed to the weather, such as concrete or 
masonry slabs, shall be of naturally durable or preserva- 
tive-treated wood unless separated from such floors or 
roofs by an impervious moisture barrier. 

2304.11.5 Supporting member for permanent appurte- 
nances. Naturally durable or preservative-treated wood 
shall be utilized for those portions of wood members that 
form the structural supports of buildings, balconies, porches 
or similar permanent building appurtenances where such 
members are exposed to the weather without adequate pro- 
tection from a roof, eave, overhang or other covering to pre- 
vent moisture or water accumulation on the surface or at 
joints between members. 

Exception: When a building is located in a geographical 
region where experience has demonstrated that climatic 
conditions preclude the need to use durable materials 
where the structure is exposed to the weather. 

2304.11.6 Termite protection. In geographical areas 
where hazard of termite damage is known to be very heavy, 
wood floor framing shall be of naturally durable species 
(termite resistant) or preservative treated in accordance with 
AWPA VI for the species, product preservative and end use 
or provided with approve d methods of termite protection. 

2304.11.7 Wood used in retaining walls and cribs. Wood 
installed in retaining or crib walls shall be preservative 
treated in accordance with AWPA VI (Commodity Specifi- 
cations A or F) for soil and fresh water use. 

2304.11.8 Attic ventilation. For attic ventilation, see Sec- 
tion 1203.2. 

2304.11.9 Under-floor ventilation (crawl space). For 
under-floor ventilation (crawl space), see Section 1203.3. 

2304.12 Long-term loading. Wood members supporting con- 
crete, masonry or similar materials shall be checked for the 
effects of long-term loading using the provisions of the 
AF&PA NDS. The total deflection, including the effects of 
long-term loading, shall be limited in accordance with Section 
1604.3.1 for these supported materials. 

Exception: Horizontal wood members supporting masonry 
or concrete nonstructural floor or roof surfacing not more 
than 4 inches (102 mm) thick need not be checked for 
long-term loading. 



SECTION 2305 

GENERAL DESIGN REQUIREMENTS FOR 

LATERAL-FORCE-RESISTING SYSTEMS 

2305.1 General. Structures using wood shear walls and 
diaphragms to resist wind, seismic and other lateral loads 
shall be designed and constructed in accordance with 
AF&PA SDPWS and the provisions of Sections 2305,2306 
and 2307. 

2305.1.1 Openings in shear panels. Openings in shear 
panels that materially affect their strength shall be 



detailed on the plans, and shall have their edges ade- 
quately reinforced to transfer all shearing stresses. 

2305.2 Diaphragm deflection. The deflection (A) of a 
blocked wood structural panel diaphragm uniformly fas- 
tened throughout with staples is permitted to be calculated 
by using the following equation. If not uniformly fastened, 
the constant 0.188 (For SI: 1/1627) in the third term shall be 
modified accordingly. 



5vL + vL +0.188Le + E ( A ^) 



8EAb 4Gt 



2b 



(Equation 23-1) 



^ _ A 0.052vL 3 vL Len M^ C X) 

For SI: A + + + — 

EAb 4Gt 1627 2b 



where: 

A 
B 

E 



Area of chord cross section, in square inches (mm 2 ). 

Diaphragm width, in feet (mm). 

Elastic modulus of chords, in pounds per square 
inch (N/mm 2 ). 

Staple deformation, in inches (mm) [see Table 
2305.2(1)]. 

Panel rigidity through the thickness, in pounds per 
inch (N/mm) of panel width or depth [see Table 
2305.2(2)]. 

Diaphragm length, in feet (mm). 

Maximum shear due to design loads in the direction 
under consideration, in pounds per linear foot (plf) 
(N/mm). 

The calculated deflection, in inches (mm) . 

Sum of individual chord-splice slip values on both 
sides of the diaphragm, each multiplied by its dis- 
tance to the nearest support. 

TABLE 2305.2(1) I 

en VALUES (inches) FOR USE IN CALCULATING DIAPHRAGM 
AND SHEAR WALL DEFLECTION DUE TO FASTENER SLIP 
(Structural I)a, c 



Gt 

L 
v 

A 
I(A^ 



LOAD PER FASTENER b 
(pounds) 


FASTENER DESIGNATIONS 


14-Ga staple x 2 inches long 


60 


0.011 


80 


0.018 


100 


0.028 


120 


0.04 


140 


0.053 


160 


0.068 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N. 

a. Increase en values 20 percent for plywood grades other than Structural I. 

b. Load per fastener = maximum shear per foot divided by the number of fas- 
teners per foot at interior panel edges. 

c. Decrease en values 50 percent for seasoned lumber (moisture content < 19 
percent). 



466 



2009 INTERNATIONAL BUILDING CODE® 



2305.3 Shear wall deflection. The deflection (A) of a blocked 
wood structural panel shear wall uniformly fastened through- 
out with staples is permitted to be calculated by the use of the 
following equation: 



A= 



8vh 



h 



_ +vh + 0.75he + d 
EAb Gt rrttfc* 



(Equation 23-2) 



For SI: A = 



vh | vh + hen 
3 EAb Gt 407.6 



-d h 
a b 



where 
A 



= Area of boundary element cross section in square 
inches (mm 2 ) (vertical member at shear wall bound- 
ary). 

= Wall width, in feet (mm). 



WOOD 



d a = Vertical elongation of overturning anchorage 
(including fastener slip, device elongation, anchor 
rod elongation, etc.) at the design shear load (v). 

E = Elastic modulus of boundary element (vertical mem- 
ber at shear wall boundary), in pounds per square inch 
(N/mm 2 ) . 

en = Staple deformation, in inches (mm) [see Table 
2305.2(1)]. 

Gt = Panel rigidity through the thickness, in pounds per 
inch (N/mm) of panel width or depth [see Table 
2305.2(2)]. 

h = Wall height, in feet (mm). 

v = Maximum shear due to design loads at the top of the 
wall, in pounds per linear foot (N/mm) . 

A = The calculated deflection, in inches (mm). 



TABLE 2305.2(2) 
VALUES OF Gt FOR USE IN CALCULATING DEFLECTION OF WOOD STRUCTURAL PANEL SHEAR WALLS AND DIAPHRAGMS 


PANEL 
TYPE 


SPAN 
RATING 


VALUES OF Gt (lb/in. panel depth or width) 


OTHER 


STRUCTURAL I 


3-ply 

Plywood 


4-ply 
Plywood 


S-ply 
Plywood a 


OSB 


3-piy 
Plywood 


4-ply 
Plywood 


S-ply 
Plywood a 


OSB 


Sheathing 


24/0 


25,000 


32,500 


37,500 


77,500 


32,500 


42,500 


41,500 


77,500 


24/16 


27,000 


35,000 


40,500 


83,500 


35,000 


45,500 


44,500 


83,500 


32/16 


27,000 


35,000 


40,500 


83,500 


35,000 


45,500 


44,500 


83,500 


40/20 


28,500 


37,000 


43,000 


88,500 


37,000 


48,000 


47,500 


88,500 


48/24 


31,000 


40,500 


46,500 


96,000 


40,500 


52,500 


51,000 


96,000 


Single Floor 


16 0.c. 


27,000 


35,000 


40,500 


83,500 


35,000 


45,500 


44,500 


83,500 


20 Qc. 


28,000 


36,500 


42,000 


87,000 


36,500 


47,500 


46,000 


87,000 


24 O.c. 


30,000 


39,000 


45,000 


93,000 


39,000 


50,500 


49,500 


93,000 


32 O.c. 


36,000 


47,000 


54,000 


110,000 


47,000 


61 ,000 


59,500 


110,000 


48 O.c. 


50,500 


65,500 


76,000 


155,000 


65,500 


85,000 


83,500 


155,000 







OTHER 


STRUCTURAL I 


Thickness 
(in.) 


A-A, 
A-C 


Marine 


All Other 
Grades 


A-A, 
A-C 


Marine 


All Other 
Grades 


Sanded 
Plywood 


"4 


24,000 


31 ,000 


24,000 


31 ,000 


31 ,000 


31 ,000 


n/ n 


25,500 


33,000 


25,500 


33,000 


33,000 


33,000 


*s 


26,000 


34,000 


26,000 


34,000 


34,000 


34,000 


W /J2 


38,000 


49,500 


38,000 


49,500 


49,500 


49,500 


"2 


38,500 


50,000 


38,500 


50,000 


50,000 


50,000 


K 'Jl 


49,000 


63,500 


49,000 


63,500 


63,500 


63,500 


5/ 8 


49,500 


64,500 


49,500 


64,500 


64,500 


64,500 


B /n 


50,500 


65,500 


50,500 


65,500 


65,500 


65,500 


*4 


51 ,000 


66,500 


51 ,000 


66,500 


66,500 


66,500 


7/ 8 


52,500 


68,500 


52,500 


68,500 


68,500 


68,500 


1 


73,500 


95,500 


73,500 


95,500 


95,500 


95,500 


'% 


75,000 


97,500 


75,000 


97,500 


97,500 


97,500 



For 51 : 1 inch = 25.4 mm, 1 poundlinch = 0.1751 N/mm. 

a. Applies to plywood with five or more layers; for five-ply /three-layer plywood, use values for four 



ply. 



2009 INTERNATIONAL BUILDING CODE® 



467 



WOOD 



SECTION 2306 
ALLOWABLE STRESS DESIGN 

2306.1 Allowable stress design. The structural analysis and 
construction of wood elements in structures using allowable 
stress design shall be in accordance with the following applica- 
ble standards: 

American Forest & Paper Association. 

NDS National Design Specification for Wood Construction 

SDPWS Special Design Provisions for Wind and Seismic 

American Institute of Timber Construction. 



AITC 104 
AITC 110 

AITC 113 

AITC 117 

AITC 119 

ANSI/ 
AITC A190.1 



Typical Construction Details 

Standard Appearance Grades for Structural 
Glued Laminated Timber 

Standard for Dimensions of Structural Glued 
Laminated Timber 

Standard Specifications for Structural Glued 
Laminated Timber of Softwood Species 

Standard Specifications for Structural Glued 
Laminated Timber of Hardwood Species 



Structural Glued Laminated Timber 

AITC 200 Inspection Manual 

American Society of Agricultural Engineers. 

ASAE EP 484.2 Diaphragm Design of Metal-clad, Post- 
Frame Rectangular Buildings 

ASAE EP 486.1 Shallow Post Foundation Design 

ASAE 559 Design Requirements and Bending Properties 

for Mechanically Laminated Columns 

APA-The Engineered Wood Association. 

Panel Design Specification 

Plywood Design Specification Supplement 1 - 
Design & Fabrication of Plywood Curved Panel 

Plywood Design Specification Supplement 2 - 

Design & Fabrication of Glued Plywood-lumber Beams 

Plywood Design Specification Supplement 3 - 

Design & Fabrication of Plywood Stressed-skin Panels 

Plywood Design Specification Supplement 4 - 

Design & Fabrication of Plywood Sandwich Panels 

Plywood Design Specification Supplement 5 - 
Design & Fabrication of All-plywood Beams 

EWS T300 Glulam Connection Details 

EWS S560 Field Notching and Drilling of Glued Lami- 
nated Timber Beams 

EWS S475 Glued Laminated Beam Design Tables 

EWS X450 Glulam in Residential Construction 

EWS X440 Product and Application Guide: Glulam 

EWS R540 Builders Tips: Proper Storage and Handling of 
Glulam Beams 



Truss Plate Institute, Inc. 

TPI 1 National Design Standard for Metal Plate Connected 
Wood Truss Construction 

2306.1.1 Joists and rafters. The design of rafter spans is 
permitted to be in accordance with the AF&PA Span Tables 
for Joists and Rafters. 

2306.1.2 Plank and beam flooring. The design of plank 
and beam flooring is permitted to be in accordance with the 
AF&PA Wood Construction Data No. 4. 

2306.1.3 Treated wood stress adjustments. The allowable 
unit stresses for preservative-treated wood need no adjust- 
ment for treatment, but are subject to other adjustments. 

The allowable unit stresses for fire-retardant-treated 
wood, including fastener values, shall be developed from an 
approvedmethod of investigation that considers the effects of 
anticipated temperature and humidity to which the fire-retar- 
dant-treated wood will be subjected, the type of treatment 
and the redrying process. Other adjustments are applicable 
except that the impact load duration shall not apply. 

2306.1.4 Lumber decking. The capacity of lumber decking 
arranged according to the patterns described in Section 
2304.8.2 shall be the lesser of the capacities determined for 
flexure and deflection according to the formulas in Table 
2306.1.4. i 

TABLE 2306.1.4 
ALLOWABLE LOADS FOR LUMBER DECKING 



PATTERN 


ALLOWABLE AREA LOAD a ,b 


Flexure 


Deflection 


Simple span 


8F'd 2 

°b / 6 


384AF d 3 
° A = 5/ 12 


Two-span continuous 


8F'd 2 

(7 = b 

° b f 6 


185A£" d 3 
° A = / 12 


Combination simple- and 
two-span continuous 


8F'd 2 

a = - b _ 
b / 6 


131AE' d 3 

° A ~ / 12 


Cantilevered pieces intermixed 


20F'd 2 

b 37 2 6 


105A£" d 3 
° A ~ / 12 


Controlled random layup 


Mechanically laminated decking 


20F'd 2 
b 3/ 6 


100AF d 3 
° A = / 12 


2-inch decking 


20F'd 2 
b 37 2 6 


100A£" d 3 
° A = / 12 


3 -inch and 4-inch decking 


20F'd 2 
b 3/ 6 


116A£'d J 
° A = f 12 



For SI: 1 inch = 25.4 mm. 

= Allowable total uniform load limited by bending. 
= Allowable total uniform load limited by deflection. 

= Actual decking thickness. 

= Span of decking. 
= Allowable bending stress adjusted by applicable factors. 

= Modulus of elasticity adjusted by applicable factors . 



Ob 

d 

1 

n 

E' 



468 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



1 



2306.2 Wood diaphragms. 

2306.2.1 Wood structural panel diaphragms. Wood 
structural panel diaphragms shall be designed and con- 
structed in accordance with AF&PA SDPWS. Wood struc- 
tural panel diaphragms are permitted to resist horizontal 
forces using the allowable shear capacities set forth in Table 

2306.2.1 (1) or 2306.2.1 (2). The allowable shear capacities 

in Tables 2306.2.1 (1) and 2306.2.1 (2) are permitted to be 

increased 40 percent for wind design. 
i 

2306.2.2 Single diagonally sheathed lumber dia- 
phragms. Single diagonally sheathed lumber diaphragms 
shall be designed and constructed in accordance with 
AF&PA SDPWS. 

2306.2.3 Double diagonally sheathed lumber dia- 
phragms. Double diagonally sheathed lumber diaphragms 
shall be designed and constructed in accordance with 
AF&PA SDPWS. 

2306.2.4 Gypsum board diaphragm ceilings. Gypsum 
board diaphragm ceilings shall be in accordance with Sec- 
tion 2508.5. 

2306.3 Wood structural panel shear walls. Wood structural 
panel shear walls shall be designed and constructed in accor- 
dance with AF&PA SDPWS. Wood structural panel shear 
walls are permitted to resist horizontal forces using the allow- 
able capacities set forth in Table 2306.3. Allowable capacities 
in Table 2306.3 are permitted to be increased 40 percent for 
wind design. 

2306.4 Lumber sheathed shear walls. Single and double 
diagonally sheathed lumber shear walls shall be designed and 
constructed in accordance with AF&PA SDPWS. Single and 
double diagonally sheathed lumber walls shall not be used to 
resist seismic forces in structures assigned to Seismic Design 
Category E or F. 

2306.5 Particleboard shear walls. Particleboard shear walls 
shall be designed and constructed in accordance with AF&PA 
SDPWS. Particleboard shear walls shall be permitted to resist 
horizontal forces using the allowable shear capacities set forth 
in Table 2306.5. Allowable capacities in Table 2306.5 are per- 
mitted to be increased 40 percent for wind design. 
Particleboard shall not be used to resist seismic forces in struc- 
tures assigned to Seismic Design Category D, E or F. 

2306.6 Fiberboard shear walls. Fiberboard shear walls shall 
be designed and constructed in accordance with AF&PA 
SDPWS. Fiberboard shear walls are permitted to resist hori- 
zontal forces using the allowable shear capacities set forth in 
Table 2306.6. Allowable capacities in Table 2306.6 are permit- 
ted to be increased 40 percent for wind design. Fiberboard shall 
not be used to resist seismic forces in structures assigned to 
Seismic Design Category D, E or F. 

2306.7 Shear walls sheathed with other materials. Shear 
walls sheathed with portland cement plaster, gypsum lath, gyp- 



sum sheathing or gypsum board shall be designed and con- 
structed in accordance with AF&PA SDPWS. Shear walls 
sheathed with these materials are permitted to resist horizontal 
forces using the allowable shear capacities set forth in Table 
2306.7. Shear walls sheathed with portland cement plaster, 
gypsum lath, gypsum sheathing or gypsum board shall not be 
used to resist seismic forces in structures assigned to Seismic 
Design Category E or F. 



SECTION 2307 
LOAD AND RESISTANCE FACTOR DESIGN 

2307.1 Load and resistance factor design. The structural 
analysis and construction of wood elements and structures 
using load and resistance factor design shall be in accordance 
with AF&PA NDS and AF&PA SDPWS. 

2307.1.1 Wood structural panel shear walls. In Seismic 
Design Category D, E or F, where shear design values 
exceed 490 pounds per foot (7154 N/m) , all framing mem- 
bers receiving edge nailing from abutting panels shall not be 
less than a single 3 -inch (76 mm) nominal member or two 
2-inch (51 mm) nominal members fastened together in 
accordance with AF&PA NDS to transfer the design shear 
value between framing members. Wood structural panel 
joint and sill plate nailing shall be staggered at all panel 
edges. See Sections 4.3.6.1 and 4.3.6.4.3 of AF&PA 
SDPWS for sill plate size and anchorage requirements. 



SECTION 2308 
CONVENTIONAL LIGHT-FRAME CONSTRUCTION 

2308.1 General. The requirements of this section are intended 
for conventional light-frame construction. Other methods are 
permitted to be used, provided a satisfactory design is submit- 
ted showing compliance with other provisions of this code. 
Interior nonload-bearing partitions, ceilings and curtain walls 
of conventional light-frame construction are not subject to the 
limitations of this section. Alternatively, compliance with 
AF&PA WFCM shall be permitted subject to the limitations 
therein and the limitations of this code. Detached one- and 
two-family dwellings and multiple single-family dwellings 
(townhouses) not more than three stories above grade plane in 
height with a separate means of egress and their accessory 
structures shall comply with the International Residential 
Code. 

2308.1.1 Portions exceeding limitations of conventional 
construction. When portions of a building of otherwise 
conventional construction exceed the limits of Section 
2308.2, these portions and the supporting load path shall be 
designed in accordance with accepted engineering practice 
and the provisions of this code. For the purposes of this sec- 
tion, the term "portions" shall mean parts of buildings con- 
taining volume and area such as a room or a series of rooms. 



2009 INTERNATIONAL BUILDING CODE® 



469 



TABLE 2306.2.1 (1) 

ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL DIAPHRAGMS WITH 

FRAMING OF DOUGLAS FIR-LARCH, OR SOUTHERN PINE a FOR WIND OR SEISMIC LOADING h 



O 
O 

O 



ho 

o 
o 

CD 



-I 

m 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 
O 

o 
m 



PANEL 
GRADE 


COMMON NAIL 

SIZE OR STAPLE f 

LENGTH AND 

GAGE 


MINIMUM 

FASTENER 

PENETRATION 

IN FRAMING 

(inches) 


MINIMUM 

NOMINAL 

PANEL 

THICKNESS 

(inch) 


MINIMUM 
NOMINAL 
WIDTH OF 
FRAMING 
MEMBERS AT 
ADJOINING 

PANEL 

EDGES AND 

BOUNDARIES9 

(inches) 


BLOCKED DIAPHRAGMS 


UNBLOCKED DIAPHRAGMS 


Fastener spacing (inches) at diaphragm boundaries (all cases) 

at continuous panel edges parallel to load 

(Cases 3, 4), and at all panel edges (Cases 5, 6)b 


Fasteners spaced 6" max. at supported edges 


6 | 4 | 27,c | 2 C 


Case 1 

(No unblocked edges 

or continuousjoints 

parallel to load) 


All other 

configurations 

(Cases 2, 3, 4, 5 and 6) 


Fastener spacing (inches) at other panel edges 


6 


6 


4 


3 


Structural I 
grades 


8d(2 1 / 2 -x0.131) 


1% 


3/ 8 


2 


270 


360 


530 


600 


240 


180 


3 


300 


400 


600 


675 


265 


200 


1V 2 16 Gage 


1 


2 


175 


235 


350 


400 


155 


115 


3 


200 


265 


395 


450 


175 


130 


10d d (3" x 0.148") 


iv 2 


15/ 32 


2 


320 


425 


640 


730 


285 


215 


3 


360 


480 


720 


820 


320 


240 


1V 2 16 Gage 


1 


2 


175 


235 


350 


400 


155 


120 


3 


200 


265 


395 


450 


175 


130 


Sheathing, single 
floor and other 

grades covered in 

DOC PS land 

PS2 


6d e (2"x0.113) 


1V 4 


3/ 8 


2 


185 


250 


375 


420 


165 


125 


3 


210 


280 


420 


475 


185 


140 


2 


240 


320 


480 


545 


215 


160 


3 


270 


360 


540 


610 


240 


180 


1V 2 16 Gage 


1 


2 


160 


210 


315 


360 


140 


105 


3 


180 


235 


355 


400 


160 


120 


8d(2 1 / 2 ,, x0.13r') 


1% 


7/16 


2 


255 


340 


505 


575 


230 


170 


3 


285 


380 


570 


645 


255 


190 


1V 2 16 Gage 


1 


2 


165 


225 


335 


380 


150 


110 


3 


190 


250 


375 


425 


165 


125 


8d(2 1 / 2 "x0.131") 


1% 


15/ 32 


2 


270 


360 


530 


600 


240 


180 


3 


300 


400 


600 


675 


265 


200 


10d d (3"x 0.148") 


1V2 


2 


290 


385 


575 


655 


255 


190 


3 


325 


430 


650 


735 


290 


215 


1V 2 16 Gage 


1 


2 


160 


210 


315 


360 


140 


105 


3 


180 


235 


355 


405 


160 


120 


10d d (3" x 0.148") 


1V 2 


19/ 32 


2 


320 


425 


640 


730 


285 


215 


3 


360 


480 


720 


820 


320 


240 


1% 16 Gage 


1 


2 


175 


235 


350 


400 


155 


115 


3 


200 


265 


395 


450 


175 


130 



continued 



WOOD 



TABLE 2306.2.1 (l)-continued 

ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL 

PANEL DIAPHRAGMS WITH FRAMING OF DOUGLAS FIR-LARCH, 

OR SOUTHERN PINE a FOR WIND OR SEISMIC LOADING 11 



LOAD 



liU 



FRAN 



CASE1 



1 ■ ' i ' i U HW H 



= F E T =L T 



T~n~ 



kJdi 



CASE 2 



BLOCKING 
IF USED 



DIAPHRAGM BOUNDARY 



P 



1 



q^f. 



CASE 3 



Ml 



CASE 4 



^ 



^ 



-7* 






A -- 



CONTINUOUS PANELJOINTS 



BLOCKING 
CASE 6 IF USED 



FRAMING 



! + 3 * ^ 

r_ 

____ 

- 



CONTINUOUS PANELJOINTS 



/ 



\ 


- T 


1 


CASES 

4 






V i 








T_ 








\i 








\ 








\ 








f 



CONTINUOUS PANE 



L JOINTS / 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. 

a. For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS . (2) For staples find shear value from table above for Structural I 
panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find 
shear value from table above for nail size for actual grade and multiply value by the following adjustment factor : Specific Gravity Adjustment Factor = [l-(0.5 - 
SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1. 

b. Space fasteners maximum 12 inches o.c. along intermediate framing members (6 inches o.c. where supports are spaced 48 inches o.c). 

c. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 2 ! / 2 
inches o.c. or less. 

d. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met: 
(1) lOd nails having penetration into framing of more than lV 2 inches and (2) panel edge nailing is specified at 3 inches o.c. or less. 

e. 8d is recommended minimum for roofs due to negative pressures of high winds. 

f. Staples shall have a minimum crown width of 7/ 16 inch and shall be installed with their crowns parallel to the long dimension of the framing members. 

g. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches. 

h. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively. 



1 



2009 INTERNATIONAL BUILDING CODE® 



471 



WOOD 



TABLE 2306.2.1 (2) 

ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS 

UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF 

DOUGLAS FIR-LARCH OR SOUTHERN PINE a FOR WIND OR SEISMIC LOADINGb,g,h 



PANEL 
GRADE C 


COMMON 

NAIL SIZE OR 

STAPLE f 

GAGE 


MINIMUM 

FASTENER 

PENETRATION 

IN FRAMING 

(inches) 


MINIMUM 

NOMINAL 

PANEL 

THICKNESS 

(inch) 


MINIMUM 

NOMINAL 

WIDTH OF 

FRAMING 

MEMBER AT 

ADJOINING 

PANEL EDGES 

AND 
BOUNDARIES 6 


LINES OF 
FASTENERS 


BLOCKED DIAPHRAGMS 


Cases 1 and 2 d 


Fastener Spacing Per Line at Boundaries 
(inches) 


4 I 2 1 /. 1 2 


Fastener Spacing Per Line at Other Panel Edges 
(inches) 


6 


4 


4 


3 


3 


2 


Structural I 
grades 


lOd 
common nails 


i'/ 2 


15/ 32 


3 
4 
4 


2 
2 
3 


605 
700 

875 


815 
915 
1,220 


875 
1,005 
1,285 


1,150 
1,290 
1,395 


- 


- 


19/ 32 


3 
4 
4 


2 
2 
3 


670 
780 
965 


880 
990 
1,320 


965 
1,110 
1,405 


1,255 
1,440 
1,790 






23/ 32 


3 
4 
4 


2 
2 
3 


730 
855 
1,050 


955 
1,070 
1,430 


1,050 
1,210 
1,525 


1,365 
1,565 
1,800 


- 


- 


14 gage 
staples 


2 


15/ 32 


3 
4 


2 
3 


600 
860 


600 
900 


860 
1,160 


960 
1,295 


1,060 
1,295 


1,200 
1,400 


19, 32 


3 
4 


2 
3 


600 

875 


600 
900 


875 
1,175 


960 
1,440 


1,075 
1,475 


1,200 
1,795 


Sheathing single 
floor and other 
grades covered in 
DOC PS 1 and 
PS 2 


lOd 
common nails 


l'/ 2 


15/ 32 


3 
4 
4 


2 
2 
3 


525 
605 
765 


725 
815 
1,085 


765 
875 
1,130 


1,010 
1,105 
1,195 


- 


- 


19/ 32 


3 
4 
4 


2 
2 
3 


650 

755 
935 


860 
965 
1,290 


935 
1,080 
1,365 


1,225 
1,370 
1,485 


- 


- 


23/ 32 


3 
4 
4 


2 
2 
3 


710 
825 
1.020 


935 
1,050 
1.400 


1,020 
1,175 
1.480 


1,335 
1,445 
1.565 






14 gage 
staples 


2 


15/ 32 


3 
4 


2 
3 


540 
735 


540 
810 


735 
1,005 


865 
1,105 


915 
1,105 


1,080 
1,195 


32 


3 
4 


2 
3 


600 
865 


600 
900 


865 
1,130 


960 
1,430 


1,065 
1,370 


1,200 
1,485 


32 


4 


3 


865 


900 


1,130 


1,490 


1,430 


1,545 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. 

a. For framing of other species : (1) Find specific gravity for species of framing lumber in AF&PA NDS . (2) For staples, find shear value from table above for Struc- 
tural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails, 
find shear value from table above for nail size of actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [ 1- (0.5 
- SG)], where SG = Specific gravity of the framing lumber. This adjustment factor shall not be greater than 1. 

b. Fastening along intermediate framing members : Space fasteners a maximum of 12 inches on center, except 6 inches on center for spans greater than 32 inches . 

c. Panels conforming to PS 1 or PS 2. 

d. This table gives shear values for Cases 1 and 2 as shown in Table 2306 .2. 1 (1 ) . The values shown are applicable to Cases 3,4,5 and 6 as shown in Table 2306 .2.1(1), 
providing fasteners at all continuous panel edges are spaced in accordance with the boundary iastener spacing. 

e. The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or 
adjoining panel edges shall be 2 inches. 

f. Staples shall have a minimum crown width of 7/ 16 inch, and shall be installed with their crowns parallel to the long dimension of the framing members. 

g. High load diaphragms shall be subject to special inspection in accordance with Section 1704.6.1. 

h. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively. 



472 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



TABLE 2306.2.1 (2)-continued 

ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS 

UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF 

DOUGLAS FIR-LARCH OR SOUTHERN PINE FOR WIND OR SEISMIC LOADING 











1 % — 




, 


7 V7* 


1 w 


il:_ 

.,._, 




; # 






• 


\i--r. 


■-, 








£ t/Z 


i w 


:j« ^ 








a* 














1 < 


> 






A 








TABL£ 





< .-PANEL JOIMT 











V 




J 1/2 


:-!--i 








-% 




, *j 






_—. 


- 


;vf 


> 






t^yr 


Sf< 




















* .J 


' 




A_ 










**B.E 






SPACING 





LJ I T 



3"NOMNAl^-T\YOLINE5 



4' NOMINAL— THREE LINES 











1 * 




31/2' 


!3W 


1/7 
3/4' 


* 


* 


< 

* 


> 


i ;v4" 


W^ 








3/4" 








> < 










-■' 






A 










TABLE 







, PANEL WQ 



fANtL JOIHT 




/■ 



SftACNO 
Ml NAL-fWti LINES 



TABLE 
SPACING 

TVPICAL BOUNDARY FASTENING 
(Show, is f\wo l : net iiag-gered.f 



NOTE. SPACE PANEL END AND EDGE JQ!NT 1/8- INCH. REDUCE SPACI N G B E7WE E N JNES OF MAILS AS NECESSARY TO 
MAINTAIN MINIMUM 3/fi IMC H FASTENER EDGE MARGINS, MINIMUM SPACING BETWEEN LINES IS 3/8 INCH 



2009 INTERNATIONAL BUILDING CODE® 



473 



TABLE 2306.3 

ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL SHEAR WALLS WITH 

FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINE a FOR WIND OR SEISMIC LOADING", h, i,j, i 



O 
O 

O 



ho 
o 

& 



-I 

m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



PANEL GRADE 


MINIMUM NOMINAL PANEL 
THICKNESS (inch) 


MINIMUM FASTENER 
PENETRATION IN 
FRAMING (inches) 


PANELS APPLIED DIRECT TO FRAMING 


PANELS APPLIED OVER 72" OR 5/^* GYPSUM SHEATHING 


NAIL (common or galvanized box) 
or staple size k 




NAIL (common or galvanized box) 
or staple size k 




6 


4 


3 


2 e 


6 


4 


3 


2 e 


Structural I 
sheathing 


3/ 8 


1% 


8d (2 / 2 " x 0.131" common, 
2 72" x 0.113" galvanized box) 


230 d 


360 d 


460 d 


610 d 


10d(3" x 0.148" common, 
3" x 0.128" galvanized box) 


280 


430 


550 f 


730 


1 


1^2 16 Gage 


155 


235 


315 


400 


216 Gage 


155 


235 


310 


400 


7/ 16 


l 3 /8 


8d (2 / 2 " x 0.131" common, 
2 72" x 0.113" galvanized box) 


255 d 


395 d 


505 d 


670 d 


10d(3" x 0.148" common, 
3" x 0.128" galvanized box) 


280 


430 


550 f 


730 


1 


1^2 16 Gage 


170 


260 


345 


440 


216 Gage 


155 


235 


310 


400 


15/ 32 


> 3 /8 


8d (2 / 2 " x 0.131" common, 
272" x 0.113" galvanized box) 


280 


430 


550 


730 


10d(3" x 0.148" common, 
3" x 0.1218" galvanized box) 


280 


430 


550 f 


730 


1 


1^2 16 Gage 


185 


280 


375 


475 


216 Gage 


155 


235 


300 


400 


iV 2 


10d(3" x 0.148" common, 
3" x 0.128" galvanized box) 


340 


510 


665 f 


870 


10d(3" x 0.148" common, 
3" x 0.128" galvanized box) 


- 


- 


- 


- 


Sheathing, 
plywood siding 8 
except Group 5 
Species 


%«%< 


1V 4 


6d (2" x 0.113" common, 
2" x 0.099" galvanized box) 


180 


270 


350 


450 


8d (2 / 2 " x 0.131" common, 
2 / 2 " x 0.113" galvanized box) 


180 


270 


350 


450 


1 


1 79 16 Gage 


145 


220 


295 


375 


216 Gage 


110 


165 


220 


285 


5/ 16< 


A 


6d (2" x 0.099") 


140 


210 


275 


360 


8d (272"x 0.113") 


140 


210 


275 


360 


% 


! 3 /R 


8d(2V/'x 0.113") 


160 


240 


310 


410 


10d(3" x 0.128") 


160 


240 


310 f 


410 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. 

a. For framing of other species: (1) Find specific gravity for species of lumber in AF&PANDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 
0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table above for nail size for actual grade and multiply value by the following adjustment factor: 
Specific Gravity Adjustment Factor = [l-(0.5 - SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1. 

b. Panel edges backed with 2-inch nominal or wider framing. Install panels either horizontally or vertically. Space fasteners maximum 6 inches on center along intermediate framing members for 3/g-inch and 7/}(,-inch panels 
installed on studs spaced 24 inches on center. For other conditions and panel thickness, space fasteners maximum 12 inches on center on intermediate supports. 

c. 318-inch panel thickness or siding with a span rating of 16 inches on center is the minimum recommended where applied directly to framing as exterior siding. For grooved panel siding, the nominal panel thickness 
is the thickness of the panel measured at the point of nailing. 

d. Allowable shear values are permitted to be increased to values shown for 15/32-inch sheathing with same nailing provided (a) studs are spaced a maximum of 16 inches on center, or (b) panels are applied with long 
dimension across studs. 

e. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 2 inches on center or less. 

f. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met (1) lOd (3" x 0.148") nails having penetration into 
framing of more than P/ 2 inches and (2) panel edge nailing is specified at 3 inches on center or less. 

g. Values apply to all-veneer plywood. Thickness at point of fastening on panel edges governs shear values. 

h. Where panels are applied on both faces of a wall and nail spacing is less than 6 inches o.c. on either side, paneljoints shall be offset to fall on different framing members. Or framing shall be 3 -inch nominal or thicker 

at adjoining panel edges and nails at all panel edges shall be staggered, 
i. In Seismic Design Category D, E or F, where shear design values exceed 350 pounds per linear foot, all framing members receiving edge nailing from abutting panels shall not be less than a Single 3-inch nominal 

member, or two 2-inch nominal members fastened together in accordance with Section 2306. 1 to transfer the design shear value between framing members . Wood structural panelj oint and sill plate nailing shall be 

staggered at all panel edges. See Sections 4.3.6.1 and 4.3.6.4.3 of AF&PA SDPWS for sill plate size and anchorage requirements, 
j. Galvanized nails shall be hot dipped or tumbled. 

k. Staples shall have a minimum crown width of 7/ 16 inch and shall be installed with their crowns parallel to the long dimension of the framing members. 
1. For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively. 



CD 
O 
O 

o 
m 

® 



WOOD 



TABLE 2306.5 
ALLOWABLE SHEAR FOR PARTICLEBOARD SHEAR WALL SHEATHING b 



PANEL GRADE 


MINIMUM NOMINAL 
PANEL THICKNESS 

(inch) 


MINIMUM NAIL 

PENETRATION IN 

FRAMING 

(inches) 


PANELS APPLIED DIRECT TO FRAMING 


Nail size (common or 
galvanized box) 


Allowable shear (pounds per foot) nail spacing at 
panel edges (inches)a 


6 


4 


3 


2 


M-S "Exterior Glue" 

and M-2 "Exterior 

Glue" 


3/ 8 


i> /2 


6d 


120 


180 


230 


300 


3/ s 


1'<2 


8d 


no 


190 


240 


315 


U 2 


140 


210 


270 


350 


l/ n 


1 5 <8 


lOd 


185 


275 


360 


460 


5/ 8 


200 


305 


395 


520 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. 

a. Values are not permitted in Seismic Design Category D, E or F. 

b. Galvanized nails shall be hot-dipped or tumbled. 



TABLE 2306.6 

ALLOWABLE SHEAR VALUES (pit) FOR WIND OR SEISMIC LOADING ON 

SHEAR WALLS OF FIBERBOARD SHEATHING BOARD CONSTRUCTION FOR TYPE V CONSTRUCTION ONLya,b,c,d,e 



THICKNESS AND 
GRADE 


FASTENER SIZE 


ALLOWABLE SHEAR VALUE 

(pounds per linear foot) 

NAIL SPACING AT PANEL EDGES (inches) 


a 


4 


3 


2 


i/ 2 " or 25 / 32 " 
Structural 


No. 11 gage galvanized 
roofing nail I 1 // long for 25 /s2" with 


3i 8 " head 


170 


230 


260 


No. 11 gage galvanized staple, 7/ 16 ' 


crown f 


150 


200 


225 


No. 11 gage galvanized staple, 1" 


crown f 


220 


290 


325 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. 

a. Fiberboard sheathing shall not be used to brace concrete or masonry walls. 

b. Panel edges shall be backed with 2-inch or wider framing of Douglas fir-larch or Southern pine. For framing of other species : (1) Find specific gravity for species of 
framing lumber in AF&PA NDS . (2) For staples, multiply the shear value from the table above by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for 
all other species. (3) Fornails, multiply the shear value from the table above by the following adjustment factor: specific gravity adjustment factor = [1- (0.5-SG)], 
where SG = Specific gravity of the framing lumber. 

c. Values shown are for fiberboard sheathing on one side only with long panel dimension either parallel or perpendicular to studs. 

d. Fastener shall be spaced 6 inches on center along intermediate framing members. 

e. Values are not permitted in Seismic Design Category D, E or F. 

f. Staple length shall not be less than l/ z inches for z5/3z-inch sheathing or 1 ] / 4 inches for liz-inch sheathing. 



2009 INTERNATIONAL BUILDING CODE® 



475 



WOOD 



TABLE 2306.7 

ALLOWABLE SHEAR FOR WIND OR SEISMIC FORCES FOR SHEAR WALLS OF LATH 

AND PLASTER OR GYPSUM BOARD WOOD FRAMED WALL ASSEMBLIES 



TYPE OF MATERIAL 


THICKNESS 
OF MATERIAL 


WALL 
CONSTRUCTION 


FASTENER SPACING b 
MAXIMUM (inches) 


SHEAR VALUE 3 e 

(pit) 


MINIMUM 
FASTENER SIZE c ,dj,k 


1. Expanded metal or woven wire 
lath and portland cement plaster 


7/ S " 


Unblocked 


6 


180 


No. 11 gage lV 2 " long, 71 i£" head 
No. 16 gage galv. staple, 7 8 " legs 


2. Gypsum lath, plain or perforated 
with vertical joints staggered 


3/ 8 " lath and 
V 2 " plaster 


Unblocked 


5 


180 


No. 13 gage galv. lV 8 " long, 19 / 64 " 
head, plasterboard nail 


3. Gypsum lath, plain or perforated 


31 8 " lath and 
11 2 " plaster 


Unblocked 


5 


100 


No. 16 gage galv. staple, 1 / 8 " long, 
0.120" nail, min. 3/ 8 " head, l l / 4 " 
long 


4. Gypsum board, gypsum veneer 
base or water-resistant gypsum 
backing board 


7/ 2 << 


Unblocked f 


7 


75 


5d cooler (15/ 8 " x 0.086") or 
wallboard 0.120" nail, min. 3/ 8 " 
head, 1 / 2 " long 
No. 16 gage galv. staple, 1 / 2 " long 


Unblocked f 


4 


110 


Unblocked 


7 


100 


Unblocked 


4 


125 


Blocked 8 


7 


125 


Blocked 8 


4 


150 


Unblocked 


8/12 h 


60 


No. 6 — 1/ 4 " screws' 


Blocked 8 


4/16 h 


160 


Blocked f , g 


4112 h 


155 


Blocked 8 


8112 h 


70 


Blocked 8 


6112 h 


90 


5/,» 


Unblocked f 


7 


115 


6d cooler (17/ 8 " x 0.092") or 

wallboard 

0.120" nail, min. 3/ 8 " head, l 3 / 4 " long 

No. 16 gage galv. staple, 1 / 2 " legs, 

l 5 / 8 " long 


4 


145 


Blocked 8 


7 


145 


4 


175 


Blocked 8 
Two-ply 


Base ply: 9 
Face ply: 7 


250 


Base ply-6d cooler (17/ 8 x 0.092") 

or wallboard l 3 // x 0.120" nail, 

min. 3/ 8 " head Vl 8 " 16 gage galv. 

staple 

l 5 7 s " 16 gage galv. staple 

Face ply-8d cooler (2%" x 0.113") 

or wallboard 

0.120" nail, min. 3/ 8 " head, 2 3 / 8 " long 

No. 15 gage galv. staple, 2 / 4 " long 


Unblocked 


8/J2 h 


70 


No. 6-1 / 4 " screws' 


Blocked 8 


8112 h 


90 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per foot = 14.5939 N/m. 

a. These shear walls shall not be used to resist loads imposed by masonry or concrete walls (see Section 4.1.5 of AF & PA SDPWS) . Values shown are for short-term 
loading due to wind or seismic loading. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7. Values shown shall be reduced 
25 percent for normal loading. 

b. Applies to fastening at studs, top and bottom plates and blocking. 

c. Alternate fasteners are permitted to be used if their dimensions are not less than the specified dimensions. Dry wall screws are permitted to substitute for the 5d 
(15/ 8 » x 0.086") , and 6d (77// x 0.092")(cooler) nails listed above, and No. 6 lh 4 inch Type S or W screws for 6d (l 7 / 8 " x 0.092) (cooler) nails. 

d. For properties of cooler nails, see ASTM C 514. 

e. Except as noted, shear values are based on a maximum framing spacing of 16 inches on center. 

f. Maximum framing spacing of 24 inches on center. 

g. All edges are blocked, and edge fastening is provided at all supports and all panel edges. 

h. First number denotes fastener spacing at the edges; second number denotes fastener spacing at intermediate framing members, 
i. Screws are Type W or S. 

j . Staples shall have a minimum crown width of 7 / 16 inch, measured outside the legs, and shall be installed with their crowns parallel to the long dimension of the fram- 
ing members, 
k. Staples for the attachment of gypsum lath and woven- wire lath shall have a minimum crown width of 3/ 4 inch, measured outside the legs. 



476 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



I 



2308.2 Limitations. Buildings are permitted to be constructed 
in accordance with the provisions of conventional light-frame 
construction, subject to the following limitations, and to fur- 
ther limitations of Sections 2308.11 and 2308.12. 

1. Buildings shall be limited to a maximum of three stories 
above grade plane. For the purposes of this section, for 
buildings in Seismic Design Category D or E as deter- 
mined in Section 1613, cripple stud walls shall be con- 
sidered to be a story. 

Exception: Solid blocked cripple walls not exceeding 
14 inches (356 mm) in height need not be considered a 
story. 

2. Maximum floor-to-floor height shall not exceed 11 feet, 
7 inches (3531 mm). Bearing wall height shall not 
exceed a stud height of 10 feet (3048 mm). 

3. Loads as determined in Chapter 16 shall not exceed the 
following : 

3.1. Average dead loads shall not exceed 15 psf (718 
N/m 2 ) for combined roof and ceiling, exterior 
walls, floors and partitions. 

Exceptions: 

1. Subject to the limitations of Sections 
2308.11.2 and 2308.12.2, stone or masonry 
veneer up to the lesser of 5 inches (127 mm) 
thick or 50 psf (2395 N/m 2 ) and installed in 
accordance with Chapter 14 is permitted to a 
height of 30 feet (9144 mm) above a 
noncombustible foundation, with an addi- 
tional 8 feet (2438 mm) permitted for gable 
ends. 

2. Concrete or masonry fireplaces, heaters and 
chimneys shall be permitted in accordance 
with the provisions of this code. 

3.2. Live loads shall not exceed 40 psf (1916 N/m 2 ) 
for floors. 

3.3. Ground snow loads shall not exceed 50 psf (2395 
N/m 2 ). 

4. Wind speeds shall not exceed 100 miles per hour (mph) 
(44 m/s) (3 -second gust). 

Exception: Wind speeds shall not exceed 110 mph 
(48.4 m/s) (3-second gust) for buildings in Exposure 
Category B that are not located in a hurricane -prone 
region. 

5. Roof trusses and rafters shall not span more than 40 feet 
(12 192 mm) between points of vertical support. 

6. The use of the provisions for conventional light-frame 
construction in this section shall not be permitted for 
Occupancy Category IV buildings assigned to Seismic 
Design Category B, C, D, E or F, as determined in Sec- 
tion 1613. 

7. Conventional light-frame construction is limited in 
irregular structures in Seismic Design Category D or E, 
as specified in Section 2308.12.6. 



2308.2.1 Basic wind speed greater than 100 mph (3-seC- 
ond gust). Where the basic wind speed exceeds 100 mph 
(3-second gust), the provisions of either AF&PA WFCM or 
ICC 600 are permitted to be used. 

2308.2.2 Buildings in Seismic Design Category B, C, D or 
E. Buildings of conventional light-frame construction in 
Seismic Design Category B or C, as determined in Section 
1613, shall comply with the additional requirements in Sec- 
tion 2308.11. 

Buildings of conventional light-frame construction in 
Seismic Design Category D or E, as determined in Section 
1613, shall comply with the additional requirements in Sec- 
tion 2308.12. 

2308.3 Braced wall lines. Buildings shall be provided with 
exterior and interior braced wall lines as described in Section 
2308.9.3 and installed in accordance with Sections 2308.3.1 
through 2308.3.4. 

2308.3.1 Spacing. Spacing of braced wall lines shall not 
exceed 35 feet (10668 mm) o.c. in both the longitudinal and 
transverse directions in each story. 

2308.3.2 Braced wall line connections. Wind and seismic 
lateral forces shall be transferred from the roofs and floors 
to braced wall lines and from the braced wall lines in upper 
stories to the braced wall lines in the story below in accor- 
dance with is section. 

Braced wall line top plates shall be fastened to joists, raf- 
ters or full-depth blocking above in accordance with Table 
2304.9.1, Items 11, 12, 15 or 19 as applicable based on the 
orientation of the joists or rafters to the braced wall line. 
Braced wall line bottom plates shall be connected to joists or 
blocking below in accordance with Table 2304.9.1, Item 6, 
or to foundations in accordance with Section 2308.3.3. At 
exterior gable end walls, braced wall panel sheathing in the 
top story shall be extended and fastened to roof framing 
where the spacing between parallel exterior braced wall 
lines is greater than 50 feet (15 240 mm). 

Exception: Where roof trusses are used and are installed 
perpendicular to an exterior braced wall line, lateral 
forces shall be transferred from the roof diaphragm to the 
braced wall by blocking of the ends of the trusses or by 
other approved methods providing equivalent lateral 
force transfer. Blocking shall be a minimum of 2 inches 
(51 mm) nominal in thickness and equal to the depth of 
the truss at the wall line and shall be fastened to the 
braced wall line top plate as specified in Table 2304.9.1, 
Item 11. 

2308.3.3 Sill anchorage. Where foundations are required 
by Section 2308.3.4, braced wall line sills shall be anchored 
to concrete or masonry foundations. Such anchorage shall 
conform to the requirements of Section 2308.6 except that 
such anchors shall be spaced at not more than 4 feet (1219 
mm) o.c. for structures over two stories above grade plane. 
The anchors shall be distributed along the length of the 
braced wall line . Other anchorage devices having equivalent 
capacity are permitted. 

2308.3.3.1 Anchorage to all- wood foundations. Where 
all-wood foundations are used, the force transfer from 



2009 INTERNATIONAL BUILDING CODE® 



477 



WOOD 



the braced wall lines shall be determined based on calcu- 
lation and shall have a capacity greater than or equal to 
the connections required by Section 2308.3.3. 

2308.3.4 Braced wall line support. Braced wall lines shall 
be supported by continuous foundations. 

Exception: For structures with a maximum plan dimen- 
sion not over 50 feet (15 240 mm), continuous founda- 
tions are required at exterior walls only. 

2308.4 Design of elements. Combining of engineered ele- 
ments or systems and conventionally specified elements or sys- 
tems is permitted subject to the following limits: 

2308.4.1 Elements exceeding limitations of conven- 
tional construction. When a building of otherwise con- 
ventional construction contains structural elements 
exceeding the limits of Section 2308.2, these elements and 
the supporting load path shall be designed in accordance 
with accepted engineering practice and the provisions of 
this code. 

2308.4.2 Structural elements or systems not described 
herein. When a building of otherwise conventional con- 
struction contains structural elements or systems not 
described in Section 2308, these elements or systems shall 
be designed in accordance with accepted engineering 
practice and the provisions of this code. The extent of such 
design need only demonstrate compliance of the 
nonconventional elements with other applicable provi- 
sions of this code and shall be compatible with the perfor- 
mance of the conventionally framed system. 

2308.5 Connections and fasteners. Connections and fasten- 
ers used in conventional construction shall comply with the 
requirements of Section 2304.9. 

2308.6 Foundation plates or sills. Foundations and footings 
shall be as specified in Chapter 18. Foundation plates or sills 
resting on concrete or masonry foundations shall comply with 
Section 2304.3.1. Foundation plates or sills shall be bolted or 
anchored to the foundation with not less than i/ 2 -inch-diameter 
(12.7 mm) steel bolts or approved anchors spaced to provide 
equivalent anchorage as the steel bolts. Bolts shall be embed- 
ded at least 7 inches (178 mm) into concrete or masonry, and 
spaced not more than 6 feet (1829 mm) apart. There shall be a 
minimum of two bolts or anchor straps per piece with one bolt 
or anchor strap located not more than 12 inches (305 mm) or 
less than 4 inches (102 mm) from each end of each piece. A 
properly sized nut and washer shall be tightened on each bolt to 
the plate. 

2308.7 Girders. Girders for single-story construction or gird- 
ers supporting loads from a single floor shall not be less than 4 
inches by 6 inches (102 mm by 152 mm) for spans 6 feet 
(1829 mm) or less, provided that girders are spaced not more 
than 8 feet (2438 mm) o.c. Spans for built-up 2-inch (51 mm) 
girders shall be in accordance with Table 2308.9.5 or 
2308.9.6. Other girders shall be designed to support the loads 
specified in this code. Girder end joints shall occur over sup- 
ports. 



Where a girder is spliced over a support, an adequate tie shall 
be provided. The ends of beams or girders supported on 
masonry or concrete shall not have less than 3 inches (76 mm) 
of bearing. 

2308.8 Floor joists. Spans for floor joists shall be in accor- 
dance with Table 2308.8(1) or 2308.8(2). For other grades and 
or species, refer to the AF&PA Span Tables for Joists and Raf- 
ters. 

2308.8.1 Bearing. Except where supported on a I-inch by 
4-inch (25.4 mm by 102 mm) ribbon strip and nailed to the 
adjoining stud, the ends of eachjoist shall not have less than 
1V 2 inches (38 mm) of bearing on wood or metal, or less 
than 3 inches (76 mm) on masonry. 

2308.8.2 Framing details. Joists shall be supported later- 
ally at the ends and at each support by solid blocking except 
where the ends of the joists are nailed to a header, band or 
rim joist or to an adjoining stud or by other means. Solid 
blocking shall not be less than 2 inches (51 mm) in thickness 
and the full depth of the joist. Notches on the ends of joists 
shall not exceed one-fourth the joist depth. Holes bored in 
joists shall not be within 2 inches (51 mm) of the top or bot- 
tom of the joist, and the diameter of any such hole shall not 
exceed one-third the depth of the joist. Notches in the top or 
bottom of joists shall not exceed one- sixth the depth and 
shall not be located in the middle third of the span. 

Joist framing from opposite sides of a beam, girder or 
partition shall be lapped at least 3 inches (76 mm) or the 
opposingjoists shall be tied together in an approved manner. 

Joists framing into the side of a wood girder shall be sup- 
ported by framing anchors or on ledger strips not less than 2 
inches by 2 inches (51 mm by 51 mm). 

2308.8.2.1 Engineered wood products. Cuts, notches 
and holes bored in trusses, structural composite lumber, 
structural glue-laminated members or I-joists are not 
permitted except where permitted by the manufacturer's 
recommendations or where the effects of such alterations 
are specifically considered in the design of the member 
by a registered design professional. 

2308.8.3 Framing around openings. Trimmer and header 
joists shall be doubled, or of lumber of equivalent cross sec- 
tion, where the span of the header exceeds 4 feet (1219 mm) . 
The ends of header joists more than 6 feet (1829 mm) long 
shall be supported by framing anchors or joist hangers 
unless bearing on a beam, partition or wall. Tail joists over 
12 feet (3658 mm) long shall be supported at the header by 
framing anchors or on ledger strips not less than 2 inches by 
2 inches (51 mm by 51 mm). 

2308.8.4 Supporting bearing partitions. Bearing parti- 
tions parallel tojoists shall be supported on beams, girders, 
doubled joists, walls or other bearing partitions. Bearing 
partitions perpendicular tojoists shall not be offset from 
supporting girders, walls or partitions more than the joist 
depth unless such joists are of sufficient size to carry the 
additional load. 



478 



2009 INTERNATIONAL BUILDING CODE® 



ho 

o 



TABLE 2308.8(1) 
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES 
(Residential Sleeping Areas, Live Load =30 psf, L/A =360) 



JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 Dsf 


DEAD LOAD =20 Dsf 


2x6 2x8 2xl0 2x12 


2x6 2x8 2x10 2x12 


Maximum floor ioist SDans 


(ft. - in.) 


(ft. - in.) 


(ft.-in.) 


(ft. - in.) 


(ft.-in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


12 


Douglas Fir-Larch SS 
Douglas Fir-Larch #1 
Douglas Fir-Larch #2 
Douglas Fir-Larch #3 


12-6 
12-0 
11-10 
9-8 


16-6 
15-10 

15-7 
12-4 


21-0 
20-3 
19-10 
15-0 


25-7 
24-8 
23-0 
17-5 


12-6 
12-0 
11-6 
8-8 


16-6 

15-7 
14-7 
11-0 


21-0 
19-0 
17-9 
13-5 


25-7 
22-0 
20-7 
15-7 


Hem-Fir SS 
Hem-Fir #1 
Hem-Fir #2 
Hem-Fir #3 


11-10 
11-7 
11-0 
9-8 


15-7 
15-3 
14-6 
12-4 


19-10 
19-5 
18-6 
15-0 


24-2 
23-7 
22-6 
17-5 


11-10 
11-7 
11-0 
8-8 


15-7 
15-2 
14-4 
11-0 


19-10 
18-6 
17-6 
13-5 


24-2 
21-6 
20-4 
15-7 


Southern Pine SS 
Southern Pine #1 
Southern Pine #2 
Southern Pine #3 


12-3 
12-0 
11-10 
10-5 


16-2 
15-10 
15-7 
13-3 


20-8 
20-3 
19-10 
15-8 


25-1 
24-8 
24-2 
18-8 


12-3 
12-0 
11-10 
9-4 


16-2 
15-10 
15-7 
11-11 


20-8 
20-3 
18-7 
14-0 


25-1 
24-8 
21-9 
16-8 


Spruce-Pine-Fir SS 
Spruce-Pine-Fir #1 
Spruce-Pine-Fir #2 
Soruce-Pine-Fir #3 


11-7 
11-3 
11-3 
9-8 


15-3 
14-11 
14-11 
12-4 


19-5 
19-0 
19-0 
15-0 


23-7 
23-0 
23-0 
17-5 


11-7 
11-3 
11-3 
8-8 


15-3 
14-7 
14-7 
11-0 


19-5 
17-9 
17-9 
13-5 


23-7 
20-7 
20-7 
15-7 


16 


Douglas Fir-Larch SS 
Douglas Fir-Larch #1 
Douglas Fir-Larch #2 
Douglas Fir-Larch #3 


11-4 
10-11 
10-9 
8-5 


15-0 
14-5 
14-1 
10-8 


19-1 
18-5 
17-2 
13-0 


23-3 
21-4 
19-11 
15-1 


11-4 
10-8 
9-11 
7-6 


15-0 
13-6 
12-7 
9-6 


19-1 
16-5 
15-5 
11-8 


23-0 
19-1 
17-10 
13-6 


Hem-Fir SS 
Hem-Fir #1 
Hem-Fir #2 
Hpm-Fir #^ 


10-9 
10-6 
10-0 
8-5 


14-2 
13-10 
13-2 
10-8 


18-0 
17-8 
16-10 
13-0 


21-11 
20-9 
19-8 
15-1 


10-9 
10-4 
9-10 
7-6 


14-2 
13-1 
12-5 
9-6 


18-0 
16-0 

15-2 
11-8 


21-11 
18-7 
17-7 
13-6 


Southern Pine SS 
Southern Pine #1 
Southern Pine #2 
Southern Pine #3 


11-2 
10-11 
10-9 
9-0 


14-8 
14-5 
14-2 
11-6 


18-9 
18-5 
18-0 
13-7 


22-10 
22-5 
21-1 
16-2 


11-2 
10-11 
10-5 
8-1 


14-8 
14-5 
13-6 
10-3 


18-9 
17-11 
16-1 

12-2 


22-10 
21-4 

18-10 
14-6 


Spruce-Pine-Fir SS 
Spruce-Pine-Fir #1 
Spruce-Pine-Fir #2 
Spruce-Pine-Fir #3 


10-6 
10-3 
10-3 
8-5 


13-10 
13-6 
13-6 
10-8 


17-8 
17-2 
17-2 
13-0 


21-6 
19-11 
19-11 
15-1 


10-6 
9-11 
9-11 
7-6 


13-10 
12-7 
12-7 
9-6 


17-8 
15-5 
15-5 
11-8 


21-4 
17-10 
17-10 
13-6 



(continued) 



O 
O 

D 



TABLE 2308.8(1 )-continued 
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES 
(Residential Sleeping Areas, Live Load = 30 pSf, L/A = 360) 



JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 psf 


DEAD LOAD =20 psf 


2x6 2x8 2x10 2x12 


2x6 2x8 2x10 2x12 


Maximum floor ioist SDans 


(ft. - in.) 


(ft. - in.) 


(ft- in.) 


(ft- in.) 


(ft. - in.) 


(ft. - in.) 


(ft.- in.) 


(ft- in.) 


19.2 


Douglas Fir-Larch SS 
Douglas Fir-Larch #1 
Douglas Fir-Larch #2 
Douglas Fir-Larch #3 


10-8 
10-4 
10-1 

7-8 


14-1 
13-7 
12-10 
9-9 


18-0 
16-9 
15-8 
11-10 


21-10 
19-6 
18-3 
13-9 


10-8 
9-8 
9-1 
6-10 


14-1 
12-4 
11-6 

8-8 


18-0 
15-0 
14-1 
10-7 


21-0 
17-5 
16-3 
12-4 


Hem-Fir SS 
Hem-Fir #1 
Hem-Fir #2 
Hem-Fir #3 


10-1 
9-10 
9-5 

7-8 


13-4 
13-0 
12-5 
9-9 


17-0 
16-4 
15-6 
11-10 


20-8 
19-0 
17-1 
13-9 


10-1 
9-6 
8-11 
6-10 


13-4 
12-0 
11-4 

8-8 


17-0 
14-8 
13-10 
10-7 


20-7 
17-0 
16-1 
12-4 


Southern Pine SS 
Southern Pine #1 
Southern Pine #2 
Southern Pine #3 


10-6 
10-4 
10-1 

8-3 


13-10 
13-7 
13-4 
10-6 


17-8 
17-4 
16-5 
12-5 


21-6 
21-1 
19-3 
14-9 


10-6 
10-4 
9-6 

7-4 


13-10 
13-7 
12-4 
9-5 


17-8 
16-4 
14-8 
11-1 


21-6 
19-6 

17-2 
13-2 


Spruce-Pine-Fir SS 
Spruce-Pine-Fir #1 
Spruce-Pine-Fir #2 
Soruce-Pine-Fir #3 


9-10 
9-8 
9-8 

7-8 


13-0 
12-9 
12-9 
9-9 


16-7 
15-8 
15-8 
11-10 


20-2 
18-3 
18-3 
13-9 


9-10 
9-1 
9-1 
6-10 


13-0 
11-6 
11-6 

8-8 


16-7 
14-1 
14-1 
10-7 


19-6 
16-3 
16-3 
12-4 


24 


Douglas Fir-Larch SS 
Douglas Fir-Larch #1 
Douglas Fir-Larch #2 
Douglas Fir-Larch #3 


9-11 
9-7 
9-1 
6-10 


13-1 
12-4 
11-6 

8-8 


16-8 
15-0 
14-1 
10-7 


20-3 
17-5 
16-3 
12-4 


9-11 
8-8 
8-1 
6-2 


13-1 
11-0 
10-3 
7-9 


16-2 
13-5 
12-7 
9-6 


18-9 
15-7 
14-7 
11-0 


Hem-Fir SS 
Hem-Fir #1 
Hem-Fir #2 


9-4 
9-2 
8-9 
6-10 


12-4 
12-0 
11-4 

8-8 


15-9 
14-8 
13-10 
10-7 


19-2 
17-0 
16-1 
12-4 


9-4 
8-6 
8-0 
6-2 


12-4 
10-9 
10-2 
7-9 


15-9 
13-1 
12-5 
9-6 


18-5 
15-2 
14-4 
11-0 


Southern Pine SS 
Southern Pine #1 
Southern Pine #2 
Southern Pine #3 


9-9 
9-7 
9-4 

7-4 


12-10 
12-7 
12-4 
9-5 


16-5 
16-1 
14-8 
11-1 


19-11 
19-6 

17-2 
13-2 


9-9 
9-7 
8-6 
6-7 


12-10 
12-4 
11-0 

8-5 


16-5 
14-7 
13-1 
9-11 


19-11 
17-5 
15-5 
11-10 


Spruce-Pine-Fir SS 
Spruce-Pine-Fir #1 
Spruce-Pine-Fir #2 
Spruce-Pine-Fir #3 


9-2 
8-11 
8-11 
6-10 


12-1 
11-6 
11-6 

8-8 


15-5 
14-1 
14-1 
10-7 


18-9 
16-3 
16-3 
12-4 


9-2 
8-1 
8-1 
6-2 


12-1 
10-3 
10-3 
7-9 


15-0 

12-7 
12-7 
9-6 


17-5 
14-7 
14-7 
11-0 



o 
o 

D 



Check sources for availability of lumber in lengths 
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 



greater than 20 feet. 

pound per square foot = 47. £ 



ho 

o 



TABLE 2308.8(2) 
FLOOR JOIST SPANS FOR COMMON 
(Residential Living Areas, Live Load 



LUMBER SPECIES 
=40 psf, L/A =360) 



JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x6 


2x8 


2x10 


2x12 


2x6 


2x8 


2x10 


2x12 


Maximum floor ioist soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft.-in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 




Douglas Fir-Larch 


SS 


11-4 


15-0 


19-1 


23-3 


11-4 


15-0 


19-1 


23-3 




Douglas Fir-Larch 


#1 


10-11 


14-5 


18-5 


22-0 


10-11 


14-2 


17-4 


20-1 




Douglas Fir-Larch 


#2 


10-9 


14-2 


17-9 


20-7 


10-6 


13-3 


16-3 


18-10 




Douglas Fir-Larch 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 


Hem-Fir 


SS 


10-9 


14-2 


18-0 


21-11 


10-9 


14-2 


18-0 


21-11 




Hem-Fir 


#1 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


16-11 


19-7 




Hem-Fir 


#2 


10-0 


13-2 


16-10 


20-4 


10-0 


13-1 


16-0 


18-6 


12 


Hem-Fir 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 


Southern Pine 


SS 


11-2 


14-8 


18-9 


22-10 


11-2 


14-8 


18-9 


22-10 




Southern Pine 


#1 


10-11 


14-5 


18-5 


22-5 


10-11 


14-5 


18-5 


22-5 




Southern Pine 


#2 


10-9 


14-2 


18-0 


21-9 


10-9 


14-2 


16-11 


19-10 




Southern Pine 


#3 


9-4 


11-11 


14-0 


16-8 


8-6 


10-10 


12-10 


15-3 


Spruce-Pine-Fir 


SS 


10-6 


13-10 


17-8 


21-6 


10-6 


13-10 


17-8 


21-6 




Spruce-Pine-Fir 


#1 


10-3 


13-6 


17-3 


20-7 


10-3 


13-3 


16-3 


18-10 




Spruce-Pine-Fir 


#2 


10-3 


13-6 


17-3 


20-7 


10-3 


13-3 


16-3 


18-10 




Spruce-Pine-Fir 


#3 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 




Douglas Fir-Larch 


SS 


10-4 


13-7 


17-4 


21-1 


10-4 


13-7 


17-4 


21-0 




Douglas Fir-Larch 


#1 


9-11 


13-1 


16-5 


19-1 


9-8 


12-4 


15-0 


17-5 




Douglas Fir-Larch 


#2 


9-9 


12-7 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Douglas Fir-Larch 


#3 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 


Hem-Fir 


SS 


9-9 


12-10 


16-5 


19-11 


9-9 


12-10 


16-5 


19-11 




Hem-Fir 


#1 


9-6 


12-7 


16-0 


18-7 


9-6 


12-0 


14-8 


17-0 




Hem-Fir 


#2 


9-1 


12-0 


15-2 


17-7 


8-11 


11-4 


13-10 


16-1 


16 




#?, 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 


Southern Pine 


SS 


10-2 


13-4 


17-0 


20-9 


10-2 


13-4 


17-0 


20-9 




Southern Pine 


#1 


9-11 


13-1 


16-9 


20-4 


9-11 


13-1 


16-4 


19-6 




Southern Pine 


#2 


9-9 


12-10 


16-1 


18-10 


9-6 


12-4 


14-8 


17-2 




Southern Pine 


#3 


8-1 


10-3 


12-2 


14-6 


7-4 


9-5 


11-1 


13-2 


Spruce-Pine-Fir 


SS 


9-6 


12-7 


16-0 


19-6 


9-6 


12-7 


16-0 


19-6 




Spruce-Pine-Fir 


#1 


9-4 


12-3 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Spruce-Pine-Fir 


#2 


9-4 


12-3 


15-5 


17-10 


9-1 


11-6 


14-1 


16-3 




Spruce-Pine-Fir 


#3 


7-6 


9-6 


11-8 


13-6 


6-10 


8-8 


10-7 


12-4 



(continued) 



O 
O 

D 



TABLE 2308.8(2)-continued 
FLOOR JOIST SPANS FOR COMMON LUMBER SPECIES 
(Residential Living Areas, Live Load = 40 psf, L/A = 360) 



JOIST 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 psf 


DEAD LOAD = 20 psf 


2x6 


2x8 


2x10 


2x12 


2x6 


2x8 


2x10 


2x12 


Maximum floor ioist soans 


(ft., in.) 


(ft.- in,) 


(ft.- in.) 


(ft- in.) 


(ft., in,) 


(ft.- in.) 


(ft- in,) 


(ft- in.) 




Douglas Fir-Larch 


SS 


9-8 


12-10 


16-4 


19-10 


9-8 


12-10 


16-4 


19-2 




Douglas Fir-Larch 


#1 


9-4 


12-4 


15-0 


17-5 


8-10 


11-3 


13-8 


15-11 




Douglas Fir-Larch 


#2 


9-1 


11-6 


14-1 


16-3 


8-3 


10-6 


12-10 


14-10 




Douglas Fir-Larch 


#3 


6-10 


8-8 


10-7 


12-4 


6-3 


7-11 


9-8 


11-3 


Hem-Fir 


SS 


9-2 


12-1 


15-5 


18-9 


9-2 


12-1 


15-5 


18-9 




Hem-Fir 


#1 


9-0 


11-10 


14-8 


17-0 


8-8 


10-11 


13-4 


15-6 




Hem-Fir 


#2 


8-7 


11-3 


13-10 


16-1 


8-2 


10-4 


12-8 


14-8 


19.2 


Hem-Fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-3 


7-11 


9-8 


11-3 


Southern Pine 


SS 


9-6 


12-7 


16-0 


19-6 


9-6 


12-7 


16-0 


19-6 




Southern Pine 


#1 


9-4 


12-4 


15-9 


19-2 


9-4 


12-4 


14-11 


17-9 




Southern Pine 


#2 


9-2 


12-1 


14-8 


17-2 


8-8 


11-3 


13-5 


15-8 




Southern Pine 


#3 


7-4 


9-5 


11-1 


13-2 


6-9 


8-7 


10-1 


12-1 


Spruce-Pine-Fir 


SS 


9-0 


11-10 


15-1 


18-4 


9-0 


11-10 


15-1 


17-9 




Spruce-Pine-Fir 


#1 


8-9 


11-6 


14-1 


16-3 


8-3 


10-6 


12-10 


14-10 




Spruce-Pine-Fir 


#2 


8-9 


11-6 


14-1 


16-3 


8-3 


10-6 


12-10 


14-10 




Soruce-Pine-Fir 


#3 


6-10 


8-8 


10-7 


12-4 


6-3 


7-11 


9-8 


11-3 




Douglas Fir-Larch 


SS 


9-0 


11-11 


15-2 


18-5 


9-0 


11-11 


14-9 


17-1 




Douglas Fir-Larch 


#1 


8-8 


11-0 


13-5 


15-7 


7-11 


10-0 


12-3 


14-3 




Douglas Fir-Larch 


#2 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Douglas Fir-Larch 


#3 


6-2 


7-9 


9-6 


11-0 


5-7 


7-1 


8-8 


10-1 


Hem-Fir 


SS 


8-6 


11-3 


14-4 


17-5 


8-6 


11-3 


14-4 


16-10 a 




Hem-Fir 


#1 


8-4 


10-9 


13-1 


15-2 


7-9 


9-9 


11-11 


13-10 




Hem-Fir 


#2 


7-11 


10-2 


12-5 


14-4 


7-4 


9-3 


11-4 


13-1 


24 




#^ 


6-2 


7-9 


9-6 


11-0 


5-7 


7-1 


8-8 


10-1 


Southern Pine 


SS 


8-10 


11-8 


14-11 


18-1 


8-10 


11-8 


14-11 


18-1 




Southern Pine 


#1 


8-8 


11-5 


14-7 


17-5 


8-8 


11-3 


13-4 


15-11 




Southern Pine 


#2 


8-6 


11-0 


13-1 


15-5 


7-9 


10-0 


12-0 


14-0 




Southern Pine 


#3 


6-7 


8-5 


9-11 


11-10 


6-0 


7-8 


9-1 


10-9 


Spruce-Pine-Fir 


SS 


8-4 


11-0 


14-0 


17-0 


8-4 


11-0 


13-8 


15-11 




Spruce-Pine-Fir 


#1 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Spruce-Pine-Fir 


#2 


8-1 


10-3 


12-7 


14-7 


7-5 


9-5 


11-6 


13-4 




Spruce-Pine-Fir 


#3 


6-2 


7-9 


9-6 


11-0 


5-7 


7-1 


8-8 


10-1 



o 
o 

D 



Check sources for availability of lumber in lengths greater than 20 feet. 

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47. £ 

a. End bearing length shall be increased to 2 inches. 



WOOD 



2308.8.5 Lateral support. Floor, attic and roof framing 
with a nominal depth-to-thickness ratio greater than or 
equal to 5: 1 shall have one edge held in line for the entire 
span. Where the nominal depth-to-thickness ratio of the 
framing member exceeds 6: 1, there shall be one line of 
bridging for each 8 feet (2438 mm) of span, unless both 
edges of the member are held in line. The bridging shall 
consist of not less than I-inch by 3-inch (25 mm by 76 mm) 
lumber, double nailed at each end, of equivalent metal 
bracing of equal rigidity, full-depth solid blocking or other 
approved means. A line of bridging shall also be required 
at supports where equivalent lateral support is not other- 
wise provided. 

2308.8.6 Structural floor sheathing. Structural floor 
sheathing shall comply with the provisions of Section 
2304.7.1. 

2308.8.7 Under-floor ventilation. For under-floor ventila- 
tion, see Section 1203.3. 

2308.9 Wall framing. 

2308.9.1 Size, height and spacing. The size, height and 
spacing of studs shall be in accordance with Table 2308.9.1 
except that utility-grade studs shall not be spaced more than 
16 inches (406 mm) o.c, or support more than a roof and 
ceiling, or exceed 8 feet (2438 mm) in height for exterior 
walls and load-bearing walls or 10 feet (3048 mm) for inte- 
rior nonload-bearing walls. Studs shall be continuous from 
a support at the sole plate to a support at the top plate to resist 
loads perpendicular to the wall. The support shall be a foun- 
dation or floor, ceiling or roof diaphragm or shall be 
designed in accordance with accepted engineering practice. 

Exception: Jack studs, trimmer studs and cripple studs 
at openings in walls that comply with Table 2308.9.5. 

2308.9.2 Framing details. Studs shall be placed with their 
wide dimension perpendicular to the wall. Not less than three 
studs shall be installed at each corner of an exterior wall 

Exception: At corners, two studs are permitted, provided 
wood spacers or backup cleats of 3/ s -inch-thick (9.5 mm) 



wood structural panel, 3/ s -inch (9.5 mm) Type M "Exterior 
Glue" particleboard, 1-inch-thick (25 mm) lumber or 
other approved devices that will serve as an adequate 
backing for the attachment of facing materials are used. 
Where fire-resistance ratings or shear values are involved, 
wood spacers, backup cleats or other devices shall not be 
used unless specifically approvedfox such use. 

2308.9.2.1 Top plates. Bearing and exterior wall studs 
shall be capped with double top plates installed to pro- 
vide overlapping at corners and at intersections with 
other partitions. End joints in double top plates shall be 
offset at least 48 inches (1219 mm), and shall be nailed 
with not less than eight 16d face nails on each side of the 
joint. Plates shall be a nominal 2 inches (51 mm) in depth 
and have a width at least equal to the width of the studs. 

Exception: A single top plate is permitted, provided 
the plate is adequately tied atjoints, corners and inter- 
secting walls by at least the equivalent of 3-inch by 
6-inch (76 mm by 152 mm) by 0.036-inch-thick 
(0.914 mm) galvanized steel that is nailed to each wall 
or segment of wall by six 8d nails or equivalent, pro- 
vided the rafters, joists or trusses are centered over the 
studs with a tolerance of no more than 1 inch (25 mm). 

2308.9.2.2 Top plates for studs spaced at 24 inches 
(610 mm). Where bearing studs are spaced at 24-inch 
(610 mm) intervals and top plates are less than two 
2-inch by 6-inch (51 mm by 152 mm) or two 3 -inch by 
4-inch (76 mm by 102 mm) members and where the floor 
joists, floor trusses or roof trusses that they support are 
spaced at more than 16-inch (406 mm) intervals, such 
joists or trusses shall bear within 5 inches (127 mm) of 
the studs beneath or a third plate shall be installed. 

2308.9.2.3 Nonbearing walls and partitions. In 
nonbearing walls and partitions, studs shall be spaced not 
more than 28 inches (711 mm) o.c. and are permitted to 
be set with the long dimension parallel to the wall. Inte- 
rior nonbearing partitions shall be capped with no less 
than a single top plate installed to provide overlapping at 



TABLE 2308.9.1 
SIZE, HEIGHT AND SPACING OF WOOD STUDS 



STUD SIZE 
(inches) 


BEARING WALLS 


NONBEARING WALLS 


Laterally unsupported 

stud height 3 

(feet) 


Supporting roof 
and ceiling only 


Supporting one 
floor, roof 
and ceiling 


Supporting two floors, 

roof 

and ceiling 


Laterally unsupported 

stud height 3 

(feet) 


Spacing 
(inches) 


Spacing 
(inches) 


2x3 b 


- 


- 


- 


- 


10 


16 


2x4 


10 


24 


16 


- 


14 


24 


3x4 


10 


24 


24 


16 


14 


24 


2x5 


10 


24 


24 




16 


24 


2x6 


10 


24 


24 


16 


20 


24 



For 51: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where 
justified by an analysis. 

b. Shall not be used in exterior walls. 



2009 INTERNATIONAL BUILDING CODE® 



483 



WOOD 



corners and at intersections with other walls and parti- 
tions. The plate shall be continuously tied at joints by 
solid blocking at least 16 inches (406 mm) in length and 
equal in size to the plate or by V 2 -inch by lV 2 -inch (12.7 
mm by 38 mm) metal ties with spliced sections fastened 
with two 16d nails on each side of the joint. 

2308.9.2.4 Plates or sills. Studs shall have full bearing 
on a plate or sill not less than 2 inches (51 mm) in thick- 
ness having a width not less than that of the wall studs. 

2308.9.3 Bracing. Braced wall lines shall consist of braced 
wall panels that meet the requirements for location, type and 
amount of bracing as shown in Figure 2308.9.3, specified in 
Table 2308.9.3(1) and are in line or offset from each other 
by not more than 4 feet (1219 mm). Braced wall panels shall 
start not more than 12h 2 feet (3810 mm) from each end of a 
braced wall line. Braced wall panels shall be clearly indi- 
cated on the plans. Construction of braced wall panels shall 
be by one of the following methods: 

1. Nominal I-inch by 4-inch (25 mm by 102 mm) con- 
tinuous diagonal braces let into top and bottom plates 
and intervening studs, placed at an angle not more 
than 60 degrees (1.0 rad) or less than 45 degrees (0.79 
rad) from the horizontal and attached to the framing in 
conformance with Table 2304.9.1. 

2. Wood boards of 5/ s inch (15.9 mm) net minimum 
thickness applied diagonally on studs spaced not over 
24 inches (610 mm) o.c. 

3. Wood structural panel sheathing with a thickness not 
less than 37s inch (9.5 mm) for 16- inch (406 mm) or 
24-inch (610 mm) stud spacing in accordance with 
Tables 2308.9.3(2) and 2308.9.3(3). 

4. Fiberboard sheathing panels not less than i/ 2 inch 
(12.7 mm) thick applied vertically or horizontally on 
studs spaced not over 16 inches (406 mm) o.c. where 
installed with fasteners in accordance with Section 
2306.6 and Table 2306.6. 

5. Gypsum board [sheathing i/ 2 -inch-thick (12.7 mm) 
by 4-feet-wide (1219 mm) wallboard or veneer base] 
on studs spaced not over 24 inches (610 mm) o.c. and 
nailed at 7 inches (178 mm) o.c. with nails as required 
by Table 2306.7. 

6. Particleboard wall sheathing panels where installed in 
accordance with Table 2308.9.3(4). 

7. Portland cement plaster on studs spaced 16 inches 
(406 mm) o.c. installed in accordance with Section 
2510. 

8. Hardboard panel siding where installed in accordance 
with Section 2303.1.6 and Table 2308.9.3(5). 

For cripple wall bracing, see Section 2308.9.4.1. For 
Methods 2, 3, 4, 6, 7 and 8, each panel must be at least 48 
inches (1219 mm) in length, covering three stud spaces 
where studs are spaced 16 inches (406 mm) apart and cover- 
ing two stud spaces where studs are spaced 24 inches (610 
mm) apart. 



For Method 5, each panel must be at least 96 inches (2438 
mm) in length where applied to one face of a panel and 48 
inches (1219 mm) where applied to both faces. All vertical 
joints of panel sheathing shall occur over studs and adjacent 
panel joints shall be nailed to common framing members. 
Horizontaljoints shall occur over blocking or other framing 
equal in size to the studding except where waived by the 
installation requirements for the specific sheathing materi- 
als. Sole plates shall be nailed to the floor framing and top 
plates shall be connected to the framing above in accordance 
with Section 2308.3.2. Where joists are perpendicular to 
braced wall lines above, blocking shall be provided under 
and in line with the braced wall panels. 

2308.9.3.1 Alternative bracing. Any bracing required 
by Section 2308.9.3 is permitted to be replaced by the 
following: 

1. In one-story buildings, each panel shall have a 
length of not less than 2 feet 8 inches (813 mm) and 
a height of not more than 10 feet (3048 mm). Each 
panel shall be sheathed on one face with 
3/ s -inch-minimum- thickness (9.5 mm) wood struc- 
tural panel sheathing nailed with 8d common or gal- 
vanized box nails in accordance with Table 
2304.9.1 and blocked at wood structural panel 
edges. Two anchor bolts installed in accordance 
with Section 2308.6 shall be provided in each panel. 
Anchor bolts shall be placed at each panel outside 
quarter points. Each panel end stud shall have a 
tie-down device fastened to the foundation, capable 
of providing an approveduplift capacity of not less 
than 1,800 pounds (8006 N). The tie-down device 
shall be installed in accordance with the manufac- 
turer's recommendations. The panels shall be sup- 
ported directly on a foundation or on floor framing 
supported directly on a foundation that is continu- 
ous across the entire length of the braced wall line. 
This foundation shall be reinforced with not less 
than one No. 4 bar top and bottom. 

Where the continuous foundation is required to 
have a depth greater than 12 inches (305 mm), a 
minimum 12-inch by 12-inch (305 mm by 305 
mm) continuous footing or turned down slab edge 
is permitted at door openings in the braced wall 
line. This continuous footing or turned down slab 
edge shall be reinforced with not less than one No. 
4 bar top and bottom. This reinforcement shall be 
lapped 15 inches (381 mm) with the reinforcement 
required in the continuous foundation located 
directly under the braced wall line. 

2. In the first story of two- story buildings, each wall 
panel shall be braced in accordance with Section 
2308.9.3.1, Item 1, except that the wood structural 
panel sheathing shall be provided on both faces, 
three anchor bolts shall be placed at one-quarter 
points, and tie-down device uplift capacity shall 
not be less than 3,000 pounds (13 344 N). 



484 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



SEISMIC DESIGN CATEGORY 


MAXIMUM WALL SPACING (feet) 


REQUIRED BRACING LENGTH, b 


A, Band C 


35'-0" 


Table 2308.9.3(1) and Section 2308.9.3 


DandE 


25'-0" 


Table 2308.12.4 



UPTCH'-O* 

OFFSET ALLOWED IK 

BRACED WALL LINE 



BRACED WML 
LINE NO. A 



n 6" MM TO 

FIRST BRACED 
WALL PANEL 



BRACED 

WALL 

UNENO.l 



BRACfD WALL 

UNE NO. 3 



BRACED WALL LlMt X 




BRACED 
^ WALL 
UNEY 



BRACED 

WALL 

PANFLS 



BRACED 
WAIL LINE Z 



BRACED WALL 
LINE NO.? DOES 
NOT NEED TO 
ALIGN WITH NO.3 
AS LONG AS IT 
HAS A BRACED 
WAIL PANEL 
AT EACH END 



BRACED WALL UNE 
NO? 



BRACED 

WALL LINE 



BRACED WALL 
LINE NO. 1 

EKtEfclOR 
BRACED WALL 
PANELS ARE 
IN ONE PLANE 
N'ERTICALLY 
EXCEPT AS 
PROVIDED FOR 
IN SECTION 
33D3.ia.fi 




UP TO 4'- IF 

OFFSJET ALLOWED IN 

BRACED WALL LINE 



NOTES: 

I T j SUM Of BRACED WAU PANEL 
LENGTHS FOH BRACED WALL 
UNE MO- 1 = ** + ^ + ^ 



CONTINUOUS 
FOUNDATION AMD 
BRACED CRIPPLE 
WALL RECOMMENDED 
UNDER LOWER STORr 
BRACED WALL FWE13 

BEACfD 
WALL 
PANELS - b 



BRACED PANEL ABOVE MAY EXTEND UP TO 
l'-P OVER WINDOW OR DOOR BELOW 



For 51: 1 foot =304.8 



FIGURE 2308.9.3 
BASIC COMPONENTS OF THE LATERAL BRACING SYSTEM 



2009 INTERNATIONAL BUILDING CODE® 



485 



WOOD 



TABLE 2308.9.3(1) 
BRACED WALL PANELsa 



SEISMIC DESIGN 
CATEGORY 


CONDITION 


CONSTRUCTION METHODS' 5 , c 


BRACED PANEL LOCATION 
AND LENGTH d 


1 


2 


3 


4 


5 


6 


7 


8 


AandB 


One story, top of two or 
three story 


X 


X 


X 


X 


X 


X 


X 


X 


Located in accordance with 
Section 2308.9.3 and not 
more than 25 feet on center. 


First story of two story or 
second story of three story 


X 


X 


X 


X 


X 


X 


X 


X 


First story of three story 


- 


X 


X 


X 


xe 


X 


X 


X 


C 


One story or top of two 
story 


- 


X 


X 


X 


X 


X 


X 


X 


Located in accordance with 
Section 2308.9.3 and not 
more than 25 feet on center. 


First story of two story 




X 


X 


X 


xe 


X 


X 


X 


Located in accordance with 
Section 2308.9.3 and not 
more than 25 feet on center, 
but total length shall not be 
less than 25% of building 
length f 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. This table specifies minimum requirements for braced panels that form interior or exterior braced wall lines. 

b. See Section 2308.9.3 for full description. 

c. See Sections 2308.9.3.1 and 2308.9.3.2 for alternative braced panel requirements. 

d. Building length is the dimension parallel to the braced wall length. 

e. Gypsum wallboard applied to framing supports that are spaced at 16 inches on center 

f. The required lengths shall be doubled for gypsum board applied to only one face of a braced wall panel. 



TABLE 2308.9.3(2) 
EXPOSED PLYWOOD PANEL SIDING 



MINIMUM THICKNESS 3 
(inch) 


MINIMUM NUMBER OF PLIES 


STUD SPACING 

(inches) 

Plywood siding applied directly 

to studs or over sheathing 


3/ 8 


3 


16 b 


17 2 


4 


24 



For SI: 1 inch = 25.4 mm. 

a. Thickness of grooved panels is measured at bottom of grooves. 

b. Spans are permitted to be 24 inches if ply wood siding applied with face grain perpendicular to studs or over one of the following: (1 ) I-inch board sheathing, (2) 7/ 16 
-inch wood structural panel sheathing or (3) 3^ s -inch wood structural panel sheathing with strength axis (which is the long direction of the panel unless otherwise 
marked) of sheathing perpendicular to studs. 



TABLE 2308.9.3(3) 

WOOD STRUCTURAL PANEL WALL SHEATHING b 

(Not Exposed to the Weather, Strength Axis Parallel or Perpendicular to Studs Except as Indicated Below) 



MINIMUM THICKNESS 
(inch) 


PANEL SPAN RATING 


STUD SPACING (inches) 


Siding nailed to studs 


Nailable sheathing 


Sheathing parallel to studs 


Sheathing perpendicular to studs 


3/ 8 , 15/ 32 , l/ 2 


16/0, 20/0, 24/0, 32/16 
Wall-24" o.c. 


24 


16 


24 


11 W 15/ 32' l/ 2 


24/0, 24/16, 32/16 
Wall-24" o.c. 


24 


24 a 


24 



For SI: 1 inch = 25.4 mm. 

a. Plywood shall consist of four or more plies. 

b. Blocking of horizontal joints shall not be required except as specified in Sections 2306.3 and 2308.12.4. 



486 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



TABLE 2308.9.3(4) 

ALLOWABLE SPANS FOR PARTICLEBOARD WALL SHEATHING 

(Not Exposed to the Weather, Long Dimension of the Panel Parallel or Perpendicular to Studs) 



GRADE 


THICKNESS 
(inch) 


STUD SPACING (inches) 


Siding nailed 
to studs 


Sheathing under coverings specified in 
Section 2308.9.3 parallel or perpendicular to studs 


M-S "Exterior Glue" 
and M- 2 "Exterior Glue" 


3/ 8 


16 




17 2 


16 


16 



For SI: 1 inch = 25.4 mm. 



TABLE 2308.9.3(5) 
HARDBOARD SIDING 



SIDING 


MINIMUM NOMINAL 

THICKNESS 

(inch) 


2 x 4 FRAMING 
MAXIMUM SPACING 


NAIL 
SIZEa, b, d 


NAIL SPACING 


General 


Bracing panels 


1. Lap siding 


Direct to studs 


3/ 8 


16" o.c. 


8d 


16" o.c. 


Not applicable 


Over sheathing 


3/ 8 


16" o.c. 


lOd 


16" o.c. 


Not applicable 


2. Square edge panel siding 


Direct to studs 


3/ 8 


24" o.c. 


6d 


6" o.c. edges; 

12" o.c. at intermediate supports 


4" o.c. edges; 

8" o.c. at intermediate supports 


Over sheathing 


3/ 8 


24" o.c. 


8d 


6" o.c. edges; 

12" o.c. at intermediate supports 


4" o.c. edges; 

8" o.c. at intermediate supports 


3. Shiplap edge panel siding 


Direct to studs 


3/ 8 


16" o.c. 


6d 


6" o.c. edges; 

12" o.c. at intermediate supports 


4" o.c. edges; 

8" o.c. at intermediate supports 


Over sheathing 


3/ 8 


16" o.c. 


8d 


6" o.c. edges; 

12" o.c. at intermediate supports 


4" o.c. edges; 

8" o.c. at intermediate supports 



For SI: 1 inch = 25.4 mm. 

a. Nails shall be corrosion resistant. 

b. Minimum acceptable nail dimensions : 





Panel Siding 
(inch) 


Lap Siding 
(inch) 


Shank diameter 
Head diameter 


0.092 

0.225 


0.099 

0.240 



c. Where used to comply with Section 2308.9.3. 

d. Nail length must accommodate the sheathing and penetrate framing lV 2 inches. 



2009 INTERNATIONAL BUILDING CODE® 



487 



WOOD 



2308.9.3.2 Alternate bracing wall panel adjacent to a 
door or window opening. Any bracing required by Sec- 
tion 2308.9.3 is permitted to be replaced by the following 
when used adjacent to a door or window opening with a 
full-length header: 

1. In one-story buildings, each panel shall have a 
length of not less than 16 inches (406 mm) and a 
height of not more than 10 feet (3048 mm). Each 
panel shall be sheathed on one face with a single 
layer of 3/ 8 inch (9.5 mm) minimum thickness 
wood structural panel sheathing nailed with 8d 
common or galvanized box nails in accordance 
with Figure 2308.9.3.2. The wood structural panel 
sheathing shall extend up over the solid sawn or 
glued-laminated header and shall be nailed in 
accordance with Figure 2308.9.3.2. A built-up 
header consisting of at least two 2 x 12s and fas- 
tened in accordance with Item 24 of Table 
2304.9.1 shall be permitted to be used. A spacer, if 
used, shall be placed on the side of the built-up 
beam opposite the wood structural panel sheath- 
ing. The header shall extend between the inside 
faces of the first full-length outer studs of each 
panel. The clear span of the header between the 
inner studs of each panel shall be not less than 6 
feet (1829 mm) and not more than 18 feet (5486 
mm) in length. A strap with an uplift capacity of 
not less than 1,000 pounds (4,400 N) shall fasten 



the header to the inner studs opposite the sheath- 
ing. One anchor bolt not less than 5/ 8 inch (15.9 
mm) diameter and installed in accordance with 
Section 2308.6 shall be provided in the center of 
each sill plate. The studs at each end of the panel 
shall have a tie-down device fastened to the foun- 
dation with an uplift capacity of not less than 4,200 
pounds (18 480 N). 

Where a panel is located on one side of the open- 
ing, the header shall extend between the inside face 
of the first full-length stud of the panel and the bear- 
ing studs at the other end of the opening. A strap 
with an uplift capacity of not less than 1,000 pounds 
(4400 N) shall fasten the header to the bearing 
studs. The bearing studs shall also have a tie-down 
device fastened to the foundation with an uplift 
capacity of not less than 1,000 pounds (4400 N). 

The tie-down devices shall be an embedded 
strap type, installed in accordance with the manu- 
facturer's recommendations. The panels shall be 
supported directly on a foundation that is continu- 
ous across the entire length of the braced wall line. 
This foundation shall be reinforced with not less 
than one No. 4 bar top and bottom. 

Where the continuous foundation is required to 
have a depth greater than 12 inches (305 mm), a 
minimum 12-inch by 12-inch (305 mm by 305 




EKTEWT DF HEADEH 

KXWf FOffrrai FFWUf fnao swceo m«Ll pawm* 



©fTEWTOf nC*StR 
Stftfk£ *OflTAL FRAME tC** GftftCED WALL FttYEL.' 



tytw 3." 1 n Jtfl" NjfT HfcAjRlfcM 



fTOW 



> \ 



r^STTN TOP Pi AiT TQ ICADEH MWIH TWB 
W5 OF 'flD &HKER fcAJLS AT T Q. WR 

IM0 1ft STRAP OPPOSITE SHFAJHiM 



SIMP 



f-Ain E 4 3HE1THING ID HEADEH WITH BD CCMWJN DP 

QHwMfm HO* NWLS in r i>&ii *AiT£*m ** S*G**N aNTi 

T &E IN AH FRAMINn ilRTiJCCJ, BvEKlH**! AND JStl Ri TVT 
MJft WDT>* »rFWtC*jf STQfl* STnuCTuPf S 

Mill WC TV--**' -CAUSE IN THE FlRSTQf TWO 

an oft STftutnuRea 



MM. Z»*f HAVING 

SI'MIti IHtCfcAHSifc'ClOL. 
STRUCTURAL PANEl BHEATHIND 



DOUflLE 



CONCtfE TE AND HMi£D INfO F RAMING1 



•:ifl:SfCT>C*J?IWa.9Jja 



* t 



For 51: 1 foot = 304 .8 mm; 1 inch = 25.4 mm; 1 pound = 4.448 N. 



I 



FRAME 
CtWSTfiUCTJOft 

^«A*MJEL5FUOE 



•■ 



aLCEKE!3,AIC? OCCUR 

WTHM&rQf i#Ci- 

fCHMTOHErKWOf 

rvp shiatwm&to. 

FPUMH:< NJVLHGn 

praoineo 

iPJWei»3*iCiS 

ustij. tme zw a vuai 

■f NAiLGDIXXWTOH 

wiTTBaiaqwNWFH 

UP« 4WLE 

TIEGOWI 

DEVICE 



t 




FIGURE 2308.9.3.2 
ALTERNATE BRACED WALL PANEL ADJACENT TO A DOOR OR WINDOW OPENING 



488 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



mm) continuous footing or turned down slab edge 
is permitted at door openings in the braced wall 
line. This continuous footing or turned down slab 
edge shall be reinforced with not less than one No. 
4 bar top and bottom. This reinforcement shall be 
lapped not less than 15 inches (381 mm) with the 
reinforcement required in the continuous founda- 
tion located directly under the braced wall line. 

2. In the first story of two-story buildings, each wall 
panel shall be braced in accordance with Item 1 
above, except that each panel shall have a length of 
not less than 24 inches (610 mm). 

2308.9.4 Cripple walls. Foundation cripple walls shall be 
framed of studs not less in size than the studding above with 
a minimum length of 14 inches (356 mm), or shall be framed 
of solid blocking. Where exceeding 4 feet (1219 mm) in 
height, such walls shall be framed of studs having the size 
required for an additional story. 

2308.9.4.1 Bracing. For the purposes of this section, 
cripple walls having a stud height exceeding 14 inches 
(356 mm) shall be considered a story and shall be braced 
in accordance with Table 2308.9.3(1) for Seismic Design 
Category A, B or C. See Section 2308.12.4 for Seismic 
Design Category D or E. 

2308.9.4.2 Nailing of bracing. Spacing of edge nailing 
for required wall bracing shall not exceed 6 inches (152 
mm) o.c. along the foundation plate and the top plate of 
the cripple wall. Nail size, nail spacing for field nailing 
and more restrictive boundary nailing requirements shall 
be as required elsewhere in the code for the specific brac- 
ing material used. 

2308.9.5 Openings in exterior walls. 

2308.9.5.1 Headers. Headers shall be provided over 
each opening in exterior-bearing walls. The spans in 
Table 2308.9.5 are permitted to be used for one- and 
two- family dwellings. Headers for other buildings shall 
be designed in accordance with Section 2301.2, Item 1 or 
2. Headers shall be of two pieces of nominal 2-inch (51 
mm) framing lumber set on edge as permitted by Table 
2308.9.5 and nailed together in accordance with Table 
2304.9.1 or of solid lumber of equivalent size. 

2308.9.5.2 Header support. Wall studs shall support the 
ends of the header in accordance with Table 2308.9.5. 
Each end of a lintel or header shall have a length of bear- 
ing of not less than 1V 2 inches (38 mm) for the full width 
of the lintel. 

2308.9.6 Openings in interior bearing partitions. Head- 
ers shall be provided over each opening in interior bearing 
partitions as required in Section 2308.9.5. The spans in 
Table 2308.9.6 are permitted to be used. Wall studs shall 
support the ends of the header in accordance with Table 
2308.9.5 or 2308.9.6, as appropriate. 

2308.9.7 Openings in interior nonbearing partitions. 
Openings in nonbearing partitions are permitted to be 
framed with single studs and headers. Each end of a lintel or 



header shall have a length of bearing of not less than 1V 2 
inches (38 mm) for the full width of the lintel. 

2308.9.8 Pipes in walls. Stud partitions containing 
plumbing, heating or other pipes shall be so framed and 
the joists underneath so spaced as to give proper clear- 
ance for the piping. Where a partition containing such 
piping runs parallel to the floor joists, the joists under- 
neath such partitions shall be doubled and spaced to per- 
mitthe passage of such pipes and shall be bridged. Where 
plumbing, heating or other pipes are placed in or partly in 
a partition, necessitating the cutting of the soles or plates, 
a metal tie not less than 0.058 inch (1.47 mm) (16 galva- 
nized gage) and 1V 2 inches (38 mm) wide shall be fas- 
tened to each plate across and to each side of the opening 
with not less than six 16d nails. 

2308.9.9 Bridging. Unless covered by interior or exterior 
wall coverings or sheathing meeting the minimum require- 
ments of this code, stud partitions or walls with studs hav- 
ing a height-to-least-thickness ratio exceeding 50 shall 
have bridging not less than 2 inches (51 mm) in thickness 
and of the same width as the studs fitted snugly and nailed 
thereto to provide adequate lateral support. Bridging shall 
be placed in every stud cavity and at a frequency such that 
no stud so braced shall have a height-to-least-thickness 
ratio exceeding 50 with the height of the stud measured 
between horizontal framing and bridging or between 
bridging, whichever is greater. 

2308.9.10 Cutting and notching. In exterior walls and 
bearing partitions, any wood stud is permitted to be cut or 
notched to a depth not exceeding 25 percent of its width. 
Cutting or notching of studs to a depth not greater than 40 
percent of the width of the stud is permitted in nonbearing 
partitions supporting no loads other than the weight of the 
partition. 

2308.9.11 Bored holes. A hole not greater in diameter 
than 40 percent of the stud width is permitted to be bored 
in any wood stud. Bored holes not greater than 60 percent 
of the width of the stud are permitted in nonbearing parti- 
tions or in any wall where each bored stud is doubled, pro- 
vided not more than two such successive doubled studs 
are so bored. 

In no case shall the edge of the bored hole be nearer than 
5/ 8 inch (15.9 mm) to the edge of the stud. 

Bored holes shall not be located at the same section of 
stud as a cut or notch. 

2308.10 Roof and ceiling framing. The framing details 
required in this section apply to roofs having a minimum 
slope of three units vertical in 12 units horizontal (25-percent 
slope) or greater. Where the roof slope is less than three units 
vertical in 12 units horizontal (25-percent slope), members 
supporting rafters and ceilingjoists such as ridge board, hips 
and valleys shall be designed as beams. 

2308.10.1 Wind uplift. The roof construction shall have 
rafter and truss ties to the wall below. Resultant uplift 
loads shall be transferred to the foundation using a con- 
tinuous load path. The rafter or truss to wall connection 
shall comply with Tables 2304.9.1 and 2308.10.1. 



2009 INTERNATIONAL BUILDING CODE® 



489 



TABLE 2308.9.5 

HEADER AND GIRDER SPANS 3 FOR EXTERIOR BEARING WALLS 

(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Pine-Fir b and Required Number of Jack Studs) 



ho 

o 

& 



-I 
m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 
O 

o 
m 



HEADERS 
SUPPORTING 


SIZE 


GROUND SNOW LOAD (psf)e 


30 


50 


Building width* (feet) 


20 


28 


36 


20 


28 


36 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Roof & Ceiling 


2-2x4 


3-6 


1 


3-2 


1 


2-10 


1 


3-2 


1 


2-9 


1 


2-6 


1 


2-2x6 


5-5 


1 


4-8 


1 


4-2 


1 


4-8 


1 


4-1 


1 


3-8 


2 


2-2x8 


6-10 


1 


5-11 


2 


5-4 


2 


5-11 


2 


5-2 


2 


4-7 


2 


2-2 x 10 


8-5 


2 


7-3 


2 


6-6 


2 


7-3 


2 


6-3 


2 


5-7 


2 


2-2 x 12 


9-9 


2 


8-5 


2 


7-6 


2 


8-5 


2 


7-3 


2 


6-6 


2 


3-2x8 


8-4 


1 


7-5 


1 


6-8 


1 


7-5 


1 


6-5 


2 


5-9 


2 


3-2 x 10 


10-6 


1 


9-1 


2 


8-2 


2 


9-1 


2 


7-10 


2 


7-0 


2 


3-2 x 12 


12-2 


2 


10-7 


2 


9-5 


2 


10-7 


2 


9-2 


2 


8-2 


2 


4-2x8 


9-2 


1 


8-4 


1 


7-8 


1 


8-4 


1 


7-5 


1 


6-8 


1 


4-2 x 10 


11-8 


1 


10-6 


1 


9-5 


2 


10-6 


1 


9-1 


2 


8-2 


2 


4-2 x 12 


14-1 


1 


12-2 


2 


10-11 


2 


12-2 


2 


10-7 


2 


9-5 


2 


Roof, Ceiling & 1 
Center-Bearing Floor 


2-2x4 


3-1 


1 


2-9 


1 


2-5 


1 


2-9 


1 


2-5 


1 


2-2 


1 


2-2 x 6 


4-6 


1 


4-0 


1 


3-7 


2 


4-1 


1 


3-7 


2 


3-3 


2 


2-2 x 8 


5-9 


2 


5-0 


2 


4-6 


2 


5-2 


2 


4-6 


2 


4-1 


2 


2-2 x 10 


7-0 


2 


6-2 


2 


5-6 


2 


6-4 


2 


5-6 


2 


5-0 


2 


2-2 x 12 


8-1 


2 


7-1 


2 


6-5 


2 


7-4 


2 


6-5 


2 


5-9 


3 


3-2x8 


7-2 


1 


6-3 


2 


5-8 


2 


6-5 


2 


5-8 


2 


5-1 


2 


3-2 x 10 


8-9 


2 


7-8 


2 


6-11 


2 


7-11 


2 


6-11 


2 


6-3 


2 


3-2 x 12 


10-2 


2 


8-11 


2 


8-0 


2 


9-2 


2 


8-0 


2 


7-3 


2 


4-2x8 


8-1 


1 


7-3 


1 


6-7 


1 


7-5 


1 


6-6 


1 


5-11 


2 


4-2 x 10 


10-1 


1 


8-10 


2 


8-0 


2 


9-1 


2 


8-0 


2 


7-2 


2 


4-2 x 12 


11-9 


2 


10-3 


2 


9-3 


2 


10-7 


2 


9-3 


2 


8-4 


2 


Roof, Ceiling & 1 Clear 
Span Floor 


2-2x4 


2-8 


1 


2-4 


1 


2-1 


1 


2-7 


1 


2-3 


1 


2-0 


1 


2-2x6 


3-11 


1 


3-5 


2 


3-0 


2 


3-10 


2 


3-4 


2 


3-0 


2 


2-2x8 


5-0 


2 


4-4 


2 


3-10 


2 


4-10 


2 


4-2 


2 


3-9 


2 


2-2 x 10 


6-1 


2 


5-3 


2 


4-8 


2 


5-11 


2 


5-1 


2 


4-7 


3 


2-2 x 12 


7-1 


2 


6-1 


3 


5-5 


3 


6-10 


2 


5-11 


3 


5-4 


3 


3-2x8 


6-3 


2 


5-5 


2 


4-10 


2 


6-1 


2 


5-3 


2 


4-8 


2 


3-2 x 10 


7-7 


2 


6-7 


2 


5-11 


2 


7-5 


2 


6-5 


2 


5-9 


2 


3-2 x 12 


8-10 


2 


7-8 


2 


6-10 


2 


8-7 


2 


7-5 


2 


6-8 


2 


4-2x8 


7-2 


1 


6-3 


2 


5-7 


2 


7-0 


1 


6-1 


2 


5-5 


2 


4-2 x 10 


8-9 


2 


7-7 


2 


6-10 


2 


8-7 


2 


7-5 


2 


6-7 


2 


4-2 x 12 


10-2 


2 


8-10 


2 


7-11 


2 


9-11 


2 


8-7 


2 


7-8 


2 



o 
o 

O 



(continued) 



ho 

o 

& 



-I 
m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 



TABLE 2308.9.5-continued 

HEADER AND GIRDER SPANS 3 FOR EXTERIOR BEARING WALLS 

(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Pine-Fir b and Required Number of Jack Studs) 



HEADERS 
SUPPORTING 


SIZE 


GROUND SNOW LOAD (psf) e 


30 


50 


Building width c (feet) 


20 


28 


36 


20 


28 


36 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


Roof, Ceiling & 2 

Center-Bearing 

Floors 


2-2x4 


2-7 


1 


2-3 


1 


2-0 


1 


2-6 


1 


2-2 


1 


1-11 


1 


2-2x6 


3-9 


2 


3-3 


2 


2-11 


2 


3-8 


2 


3-2 


2 


2-10 


2 


2-2x8 


4-9 


2 


4-2 


2 


3-9 


2 


4-7 


2 


4-0 


2 


3-8 


2 


2-2 x 10 


5-9 


2 


5-1 


2 


4-7 


3 


5-8 


2 


4-11 


2 


4-5 


3 


2-2 x 12 


6-8 


2 


5-10 


3 


5-3 


3 


6-6 


2 


5-9 


3 


5-2 


3 


3-2x8 


5-11 


2 


5-2 


2 


4-8 


2 


5-9 


2 


5-1 


2 


4-7 


2 


3-2 x 10 


7-3 


2 


6-4 


2 


5-8 


2 


7-1 


2 


6-2 


2 


5-7 


2 


3-2 x 12 


8-5 


2 


7-4 


2 


6-7 


2 


8-2 


2 


7-2 


2 


6-5 


3 


4-2x8 


6-10 


1 


6-0 


2 


5-5 


2 


6-8 


1 


5-10 


2 


5-3 


2 


4-2 x 10 


8-4 


2 


7-4 


2 


6-7 


2 


8-2 


2 


7-2 


2 


6-5 


2 


4-2 x 12 


9-8 


2 


8-6 


2 


7-8 


2 


9-5 


2 


8-3 


2 


7-5 


2 


Roof, Ceiling & 2 
Clear Span Floors 


2-2x4 


2-1 


1 


1-8 


1 


1-6 


2 


2-0 


1 


1-8 


1 


1-5 


2 


2-2x6 


3-1 


2 


2-8 


2 


2-4 


2 


3-0 


2 


2-7 


2 


2-3 


2 


2-2x8 


3-10 


2 


3-4 


2 


3-0 


3 


3-10 


2 


3-4 


2 


2-11 


3 


2-2 x 10 


4-9 


2 


4-1 


3 


3-8 


3 


4-8 


2 


4-0 


3 


3-7 


3 


2-2 x 12 


5-6 


3 


4-9 


3 


4-3 


3 


5-5 


3 


4-8 


3 


4-2 


3 


3-2x8 


4-10 


2 


4-2 


2 


3-9 


2 


4-9 


2 


4-1 


2 


3-8 


2 


3-2 x 10 


5-11 


2 


5-1 


2 


4-7 


3 


5-10 


2 


5-0 


2 


4-6 


3 


3-2 x 12 


6-10 


2 


5-11 


3 


5-4 


3 


6-9 


2 


5-10 


3 


5-3 


3 


4-2x8 


5-7 


2 


4-10 


2 


4-4 


2 


5-6 


2 


4-9 


2 


4-3 


2 


4-2 x 10 


6-10 


2 


5-11 


2 


5-3 


2 


6-9 


2 


5-10 


2 


5-2 


2 


4-2 x 12 


7-11 


2 


6-10 


2 


6-2 


3 


7-9 


2 


6-9 


2 


6-0 


3 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m • 

a. Spans are given in feet and inches (ft-in). 

b. Tabulated values are for No. 2 grade lumber. 

c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated. 

d. NJ - Number ofj ack studs required to support each end. Where the number of requiredj ack studs equals one, the header is permitted to be supported by an approvedframing anchor attached to the full-height wall 
stud and to the header. 

e. Use 30 pounds per square foot ground snow load for cases in which ground snow load is less than 30 pounds per square foot and the roof live load is equal to or less than 20 pounds per square foot. 



s 

o 
o 

D 



WOOD 



TABLE 2308.9.6 

HEADER AND GIRDER SPANS 3 FOR INTERIOR BEARING WALLS 

(Maximum Spans for Douglas Fir-Larch, Hem-Fir, Southern Pine and Spruce-Pine-Fir b and Required Number of Jack Studs) 



HEADERS AND GIRDERS 
SUPPORTING 


SIZE 


BUILDING WIDTH (feet) 


20 


28 


36 


Span 


NJ d 


Span 


NJ d 


Span 


NJ d 


One Floor Only 


2-2 x4 


3-1 


1 


2-8 


1 


2-5 


1 


2-2 x 6 


4-6 


1 


3-11 


1 


3-6 


1 


2-2 x 8 


5-9 


1 


5-0 


2 


4-5 


2 


2-2 xlO 


7-0 


2 


6-1 


2 


5-5 


2 


2-2 xl2 


8-1 


2 


7-0 


2 


6-3 


2 


3-2 x 8 


7-2 


1 


6-3 


1 


5-7 


2 


3-2 xlO 


8-9 


1 


7-7 


2 


6-9 


2 


3-2 xl2 


10-2 


2 


8-10 


2 


7-10 


2 


4-2 x 8 


9-0 


1 


7-8 


1 


6-9 


1 


4-2 xlO 


10-1 


1 


8-9 


1 


7-10 


2 


4-2 xl2 


11-9 


1 


10-2 


2 


9-1 


2 


Two Floors 


2-2 x4 


2-2 


1 


1-10 


1 


1-7 


1 


2-2 x 6 


3-2 


2 


2-9 


2 


2-5 


2 


2-2 x 8 


4-1 


2 


3-6 


2 


3-2 


2 


2-2 xlO 


4-11 


2 


4-3 


2 


3-10 


3 


2-2 xl2 


5-9 


2 


5-0 


3 


4-5 


3 


3-2 x 8 


5-1 


2 


4-5 


2 


3-11 


2 


3-2 xlO 


6-2 


2 


5-4 


2 


4-10 


2 


3-2 xl2 


7-2 


2 


6-3 


2 


5-7 


3 


4-2 x 8 


6-1 


1 


5-3 


2 


4-8 


2 


4-2 xlO 


7-2 


2 


6-2 


2 


5-6 


2 


4-2 xl2 


8-4 


2 


7-2 


2 


6-5 


2 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Spans are given in feet and inches (ft-in) . 

b. Tabulated values are for No. 2 grade lumber. 

c. Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated. 

d. N] - Number of jack studs required to support each end. Where the number of required jack studs equals one, the headers are permitted to be supported by an 
approved framing anchor attached to the full -height wall stud and to the header. 



492 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 





TABLE 2308.10.1 
REQUIRED RATING OF APPROVED UPLIFT CONNECTORS (pounds)a, b,c,e,f >s 


,h 




BASIC WIND SPEED 
(3-second gust) 


ROOF SPAN (feet) 


OVERHANGS 

(pounds/feet)d 


12 


20 


24 


28 


32 


36 


40 


85 


-72 


-120 


-145 


-169 


-193 


-217 


-241 


-38.55 


90 


-91 


-151 


-181 


-212 


-242 


-272 


-302 


-43.22 


100 


-131 


-281 


-262 


-305 


-349 


-393 


-436 


-53.36 


110 


-175 


-292 


-351 


-409 


-467 


-526 


-584 


-64.56 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 1.61 km/hr, 1 pound = 0.454 Kg, 1 pound/foot = 14.5939 N/m. 

a. The uplift connection requirements are based on a 30-foot mean roof height located in Exposure B . For Exposure Cor D and for other mean roof heights, multiply 
the above loads by the adjustment coefficients below. 





Mean Roof Heiqht (feet) 


EXPOSURE 


15 


20 


25 


30 


35 


40 


45 


50 


55 


60 


B 


1.00 


1.00 


1.00 


1.00 


1.05 


1.09 


1.12 


1.16 


1.19 


1.22 


C 


1.21 


1.29 


1.35 


1.40 


1.45 


1.49 


1.53 


1.56 


1.59 


1.62 


D 


1.47 


1.55 


1.61 


1.66 


1.70 


1.74 


1.78 


1.81 


1.84 


1.87 



b. The uplift connection requirements are based on the framing being spaced 24 inches on center. Multiply by 0.67 for framing spaced 16 inches on center and multi- 
ply by 0.5 for framing spaced 12 inches on center. 

c. The uplift connection requirements include an allowance for 10 pounds of dead load. 

d. The uplift connection requirements do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads 
found in the table. The overhang loads are also based on framing spaced 24 inches on center. The overhang loads given shall be multiplied by the overhang projec- 
tion and added to the roof uplift value in the table. 

e. The uplift connection requirements are based upon wind loading on end zones as defined in Figure 6-2 of ASCE 7. Connection loads for connections located a dis- 
tance of 20 percent of the least horizontal dimension of the building from the corner of the building are permitted to be reduced by multiplying the table connection 
value by 0.7 and multiplying the overhang load by 0.8. 

f. For wall-to-wall and wall-to-foundation connections, the capacity of the uplift connector is permitted to be reduced by 100 pounds for each full wall above. (For 
example, if a 500-pound rated connector is used on the roof framing, a 400-pound rated connector is permitted at the nert floor level down) . 

g. Interpolation is permitted for intermediate values of basic wind speeds and roof spans. 

h. The rated capacity of approved tie-down devices is permitted to include up to a 60-percent increase for wind effects where allowed by material specifications. 



2308.10.2 Ceilingjoist spans. Allowable spans for ceiling 
joists shall be in accordance with Table 2308.10.2(1) or 
2308.10.2(2). For other grades and species, refer to the 
AF&PA Span Tables for Joists and Rafters. 

2308.10.3 Rafter spans. Allowable spans for rafters shall 
be in accordance with Table 2308.10.3(1), 2308.10.3(2), 
2308. 10.3(3),2308.10.3(4),2308. 10.3(5) or 2308.10.3(6). 
For other grades and species, refer to the AF&PA Span 
Tables fo r Jo is ts and Rafte rs. 

2308.10.4 Ceilingjoist and rafter framing. Rafters 
shall be framed directly opposite each other at the ridge. 
There shall be a ridge board at least I-inch (25 mm) nomi- 
nal thickness at ridges and not less in depth than the cut 
end of the rafter. At valleys and hips, there shall be a sin- 
gle valley or hip rafter not less than 2-inch (51 mm) nomi- 
nal thickness and not less in depth than the cut end of the 
rafter. 

2308.10.4.1 Ceilingjoist and rafter connections. Ceil- 
ingjoists and rafters shall be nailed to each other and the 
assembly shall be nailed to the top wall plate in accor- 
dance with Tables 2304.9.1 and 2308.10.1. Ceilingjoists 
shall be continuous or securely joined where they meet 
over interior partitions and fastened to adjacent rafters in 
accordance with Tables 2308.10.4.1 and 2304.9.1 to pro- 
vide a continuous rafter tie across the building where such 
joists are parallel to the rafters. Ceilingjoists shall have a 



bearing surface of not less than 1V 2 inches (38 mm) on the 
top plate at each end. 

Where ceilingjoists are not parallel to rafters, an equiv- 
alent rafter tie shall be installed in a manner to provide a 
continuous tie across the building, at a spacing of not more 
than 4 feet (1219 mm) o.c. The connections shall be in 
accordance with Tables 2308.10.4.1 and 2304.9.1, or con- 
nections of equivalent capacities shall be provided. Where 
ceilingjoists or rafter ties are not provided at the top of the 
rafter support walls, the ridge formed by these rafters shall 
also be supported by a girder conforming to Section 
2308.4. 

Rafter ties shall be spaced not more than 4 feet (1219 
mm) o.c. Rafter tie connections shall be based on the 
equivalent rafter spacing in Table 2308.10.4.1. Where 
rafter ties are spaced at 32 inches (813 mm) o.c, the 
number of 16d common nails shall be two times the num- 
ber specified for rafters spaced 16 inches (406 mm) o.c, 
with a minimum of four 16d common nails where no 
snow loads are indicated. Where rafter ties are spaced at 
48 inches (1219 mm) o.c, the number of 16d common 
nails shall be two times the number specified for rafters 
spaced 24 inches (610 mm) o.c, with a minimum of six 
16d common nails where no snow loads are indicated. 
Rafter/ceiling joist connections and rafter/tie connec- 
tions shall be of sufficient size and number to prevent 
splitting from nailing. 



2009 INTERNATIONAL BUILDING CODE® 



493 



TABLE 2308.10.2(1) 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable Attics Without Storage, Live Load =10 pounds psf, L/A =240) 



O 
O 

O 



ho 
o 
o 

CD 



-I 

m 

z 

> 

O 

z 

> 

r 

00 

c 



CD 
O 
O 

o 
m 



CEILING JOIST SPACING 

(inches) 


SPECIES AND GRADE 


DEAD LOAD =5 pounds per square foot 


2x4 2x6 2x8 2x10 


Maximum ceilinq joist spans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


12 


Douglas Fir-Larch SS 


13-2 


20-8 


Note a 


Note a 


Douglas Fir-Larch #1 


12-8 


19-11 


Note a 


Note a 


Douglas Fir-Larch #2 


12-5 


19-6 


25-8 


Note a 


Douglas Fir-Larch #3 


10-10 


15-10 


20-1 


24-6 


Hem-Fir SS 


12-5 


19-6 


25-8 


Note a 


Hem-Fir #1 


12-2 


19-1 


25-2 


Note a 


Hem-Fir #2 


11-7 


18-2 


24-0 


Note a 


Hem-Fir #3 


10-10 


15-10 


20-1 


24-6 


Southern Pine SS 


12-11 


20-3 


Note a 


Note a 


Southern Pine #1 


12-8 


19-11 


Note a 


Note a 


Southern Pine #2 


12-5 


19-6 


25-8 


Note a 


Southern Pine #3 


11-6 


17-0 


21-8 


25-7 


Spruce-Pine-Fir SS 


12-2 


19-1 


25-2 


Note a 


Spruce-Pine-Fir #1 


11-10 


18-8 


24-7 


Note a 


Spruce-Pine-Fir #2 


11-10 


18-8 


24-7 


Note a 


Spruce-Pine-Fir #3 


10-10 


15-10 


20-1 


24-6 


16 


Douglas Fir-Larch SS 


11-11 


18-9 


24-8 


Note a 


Douglas Fir-Larch #1 


11-6 


18-1 


23-10 


Note a 


Douglas Fir-Larch #2 


11-3 


17-8 


23-0 


Note a 


Douglas Fir-Larch #3 


9-5 


13-9 


17-5 


21-3 


Hem-Fir SS 


11-3 


17-8 


23-4 


Note a 


Hem-Fir #1 


11-0 


17-4 


22-10 


Note a 


Hem-Fir #2 


10-6 


16-6 


21-9 


Note a 


Hem -Fir #^ 


9-5 


13-9 


17-5 


21-3 


Southern Pine SS 


11-9 


18-5 


24-3 


Note a 


Southern Pine #1 


11-6 


18-1 


23-1 


Note a 


Southern Pine #2 


11-3 


17-8 


23-4 


Note a 


Southern Pine #3 


10-0 


14-9 


18-9 


22-2 


Spruce-Pine-Fir SS 


11-0 


17-4 


22-10 


Note a 


Spruce-Pine-Fir #1 


10-9 


16-11 


22-4 


Note a 


Spruce-Pine-Fir #2 


10-9 


16-11 


22-4 


Note a 


Spruce-Pine-Fir #3 


9-5 


13-9 


17-5 


21-3 



(continued) 



ho 

o 

& 



-I 
m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 



TABLE 2308.10.2(1)-continued 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable Attics Without Storage, Live Load =10 pounds psf, L/A =240) 



CEILING JOIST SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD =5 Dounds per sauare foot 


2x4 2x6 2x8 2x10 


Maximum ceilina ioist spans 


(ft. - in.) 


(ft. in.) 


(ft. - in.) 


(ft in.) 


19.2 


Douglas Fir-Larch SS 


11-3 


17-8 


23-3 


Note a 


Douglas Fir-Larch #1 


10-10 


17-0 


22-5 


Note a 


Douglas Fir-Larch #2 


10-7 


16-7 


21-0 


25-8 


Douglas Fir-Larch #3 


8-7 


12-6 


15-10 


19-5 


Hem-Fir SS 


10-7 


16-8 


21-11 


Note a 


Hem-Fir #1 


10-4 


16-4 


21-6 


Note a 


Hem-Fir #2 


9-11 


15-7 


20-6 


25-3 


Hem-Fir #3 


8-7 


12-6 


15-10 


19-5 


Southern Pine SS 


11-0 


17-4 


22-10 


Note a 


Southern Pine #1 


10-10 


17-0 


22-5 


Note a 


Southern Pine #2 


10-7 


16-8 


21-11 


Note a 


Southern Pine #3 


9-1 


13-6 


17-2 


20-3 


Spruce-Pine-Fir SS 


10-4 


16-4 


21-6 


Note a 


Spruce-Pine-Fir #1 


10-2 


15-11 


21-0 


25-8 


Spruce-Pine-Fir #2 


10-2 


15-11 


21-0 


25-8 


Snruce-Pine-Fir #3 


8-7 


12-6 


15-10 


19-5 


24 


Douglas Fir-Larch SS 


10-5 


16-4 


21-7 


Note a 


Douglas Fir-Larch #1 


10-0 


15-9 


20-1 


24-6 


Douglas Fir-Larch #2 


9-10 


14-10 


18-9 


22-11 


Douglas Fir-Larch #3 


7-8 


11-2 


14-2 


17-4 


Hem-Fir SS 


9-10 


15-6 


20-5 


Note a 


Hem-Fir #1 


9-8 


15-2 


19-7 


23-11 


Hem-Fir #2 


9-2 


14-5 


18-6 


22-7 


Rem -Fir #3 


7-8 


11-2 


14-2 


17-4 


Southern Pine SS 


10-3 


16-1 


21-2 


Note a 


Southern Pine #1 


10-0 


15-9 


20-10 


Note a 


Southern Pine #2 


9-10 


15-6 


20-1 


23-11 


Southern Pine #3 


8-2 


12-0 


15-4 


18-1 


Spruce-Pine-Fir SS 


9-8 


15-2 


19-11 


25-5 


Spruce-Pine-Fir #1 


9-5 


14-9 


18-9 


22-11 


Spruce-Pine-Fir #2 


9-5 


14-9 


18-9 


22-11 


Spruce-Pine-Fir #3 


7-8 


11-2 


14-2 


17-4 



For SI: 1 inch = 25.4 mm, 1 
a. Span exceeds 26 feet in leng 



foot = 304.8 mm, 1 pound per square foot = 47.8 N/m • 

;th. Check sources for availability of lumber in lengths greater than 20 feet. 



o 
o 

D 



TABLE 2308.10.2(2) 
CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 



ho 
o 
o 

CD 



-I 

m 

z 

> 

O 

z 

> 

r 

00 

c 





(Uninhabitable Attics With Limited Storage, Live Load = 20 pounds per square foot, L/A = 240) 




CEILING JOIST SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD =10 Dounds oer sauare foot 


2x4 


2x6 2x8 


2x 10 


Maximum ceilina ioist soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. in.) 


12 


Douglas Fir-Larch SS 


10-5 


16-4 


21-7 


Note a 


Douglas Fir-Larch #1 


10-0 


15-9 


20-1 


24-6 


Douglas Fir-Larch #2 


9-10 


14-10 


18-9 


22-11 


Douglas Fir-Larch #3 


7-8 


11-2 


14-2 


17-4 


Hem-Fir SS 


9-10 


15-6 


20-5 


Note a 


Hem-Fir #1 


9-8 


15-2 


19-7 


23-11 


Hem-Fir #2 


9-2 


14-5 


18-6 


22-7 


Hem-Fir #^ 


7-8 


11-2 


14-2 


17-4 


Southern Pine SS 


10-3 


16-1 


21-2 


Note a 


Southern Pine #1 


10-0 


15-9 


20-10 


Note a 


Southern Pine #2 


9-10 


15-6 


20-1 


23-11 


Southern Pine #3 


8-2 


12-0 


15-4 


18-1 


Spruce-Pine-Fir SS 


9-8 


15-2 


19-11 


25-5 


Spruce-Pine-Fir #1 


9-5 


14-9 


18-9 


22-11 


Spruce-Pine-Fir #2 


9-5 


14-9 


18-9 


22-11 


Snruce-Pine-Fir #3 


7-8 


11-2 


14-2 


17-4 


16 


Douglas Fir-Larch SS 


9-6 


14-11 


19-7 


25-0 


Douglas Fir-Larch #1 


9-1 


13-9 


17-5 


21-3 


Douglas Fir-Larch #2 


8-9 


12-10 


16-3 


19-10 


Douglas Fir-Larch #3 


6-8 


9-8 


12-4 


15-0 


Hem-Fir SS 


8-11 


14-1 


18-6 


23-8 


Hem-Fir #1 


8-9 


13-5 


16-10 


20-8 


Hem-Fir #2 


8-4 


12-8 


16-0 


19-7 


Hem-Fir #3 


6-8 


9-8 


12-4 


15-0 


Southern Pine SS 


9-4 


14-7 


19-3 


24-7 


Southern Pine #1 


9-1 


14-4 


18-11 


23-1 


Southern Pine #2 


8-11 


13-6 


17-5 


20-9 


Southern Pine #3 


7-1 


10-5 


13-3 


15-8 


Spruce-Pine-Fir SS 


8-9 


13-9 


18-1 


23-1 


Spruce-Pine-Fir #1 


8-7 


12-10 


16-3 


19-10 


Spruce-Pine-Fir #2 


8-7 


12-10 


16-3 


19-10 


Spruce-Pine-Fir #3 


6-8 


9-8 


12-4 


15-0 



o 
o 

O 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 

& 



-I 
m 
73 

z 

> 

O 

z 

> 

r 

00 

c 



O 
O 
O 

o 
m 



TABLE 2308.10.2(2)-continued 

CEILING JOIST SPANS FOR COMMON LUMBER SPECIES 

(Uninhabitable Attics With Limited Storage, Live Load = 20 pounds per square foot, L/A = 240) 



CEILING JOIST SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 Dounds per sauare foot 


2x4 2x6 2x8 2x10 


Maximum ceilina ioist spans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. in.) 


19.2 


Douglas Fir-Larch SS 


8-11 


14-0 


18-5 


23-4 


Douglas Fir-Larch #1 


8-7 


12-6 


15-10 


19-5 


Douglas Fir-Larch #2 


8-0 


11-9 


14-10 


18-2 


Douglas Fir-Larch #3 


6-1 


8-10 


11-3 


13-8 


Hem-Fir SS 


8-5 


13-3 


17-5 


22-3 


Hem-Fir #1 


8-3 


12-3 


15-6 


18-11 


Hem-Fir #2 


7-10 


11-7 


14-8 


17-10 


Hem-Fir #3 


6-1 


8-10 


11-3 


13-8 


Southern Pine SS 


8-9 


13-9 


18-1 


23-1 


Southern Pine #1 


8-7 


13-6 


17-9 


21-1 


Southern Pine #2 


8-5 


12-3 


15-10 


18-11 


Southern Pine #3 


6-5 


9-6 


12-1 


14-4 


Spruce-Pine-Fir SS 


8-3 


12-11 


17-1 


21-8 


Spruce-Pine-Fir #1 


8-0 


11-9 


14-10 


18-2 


Spruce-Pine-Fir #2 


8-0 


11-9 


14-10 


18-2 


Soruce-Pine-Fir #3 


6-1 


8-10 


11-3 


13-8 


24 


Douglas Fir-Larch SS 


8-3 


13-0 


17-1 


20-11 


Douglas Fir-Larch #1 


7-8 


11-2 


14-2 


17-4 


Douglas Fir-Larch #2 


7-2 


10-6 


13-3 


16-3 


Douglas Fir-Larch #3 


5-5 


7-11 


10-0 


12-3 


Hem-Fir SS 


7-10 


12-3 


16-2 


20-6 


Hem-Fir #1 


7-6 


10-11 


13-10 


16-11 


Hem-Fir #2 


7-1 


10-4 


13-1 


16-0 


Hem-Fir #3 


5-5 


7-11 


10-0 


12-3 


Southern Pine SS 


8-1 


12-9 


16-10 


21-6 


Southern Pine #1 


8-0 


12-6 


15-10 


18-10 


Southern Pine #2 


7-8 


11-0 


14-2 


16-11 


Southern Pine #3 


5-9 


8-6 


10-10 


12-10 


Spruce-Pine-Fir SS 


7-8 


12-0 


15-10 


19-5 


Spruce-Pine-Fir #1 


7-2 


10-6 


13-3 


16-3 


Spruce-Pine-Fir #2 


7-2 


10-6 


13-3 


16-3 


Spruce-Pine-Fir #3 


5-5 


7-11 


10-0 


12-3 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m • 

a. Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet. 



o 
o 

D 



TABLE 2308.10.3(1) 
RAFTER SPANS FOR COMMON LUMBER SPECIES 
(Roof Live Load = 20 pounds per square foot, Ceiling Not Attached to Rafters, LIA = 



180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 Dounds Der sauare foot 


DEAD LOAD - 20 Dounds Der sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter SDans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


12 


Douglas Fir-Larch SS 


11-6 


18-0 


23-9 


Note a 


Note a 


11-6 


18-0 


23-5 


Note a 


Note a 


Douglas Fir-Larch #1 


11-1 


17-4 


22-5 


Note a 


Note a 


10-6 


15-4 


19-5 


23-9 


Note a 


Douglas Fir-Larch #2 


10-10 


16-7 


21-0 


25-8 


Note a 


9-10 


14-4 


18-2 


22-3 


25-9 


Douglas Fir-Larch #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Hem-Fir SS 


10-10 


17-0 


22-5 


Note a 


Note a 


10-10 


17-0 


22-5 


Note a 


Note a 


Hem-Fir #1 


10-7 


16-8 


21-10 


Note a 


Note a 


10-3 


14-11 


18-11 


23-2 


Note a 


Hem-Fir #2 


10-1 


15-11 


20-8 


25-3 


Note a 


9-8 


14-2 


17-11 


21-11 


25-5 


Hem-Fir #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Southern Pine SS 


11-3 


17-8 


23-4 


Note a 


Note a 


11-3 


17-8 


23-4 


Note a 


Note a 


Southern Pine #1 


11-1 


17-4 


22-11 


Note a 


Note a 


11-1 


17-3 


21-9 


25-10 


Note a 


Southern Pine #2 


10-10 


17-0 


22-5 


Note a 


Note a 


10-6 


15-1 


19-5 


23-2 


Note a 


Southern Pine #3 


9-1 


13-6 


17-2 


20-3 


24-1 


7-11 


11-8 


14-10 


17-6 


20-11 


Spruce-Pine-Fir SS 


10-7 


16-8 


21-11 


Note a 


Note a 


10-7 


16-8 


21-9 


Note a 


Note a 


Spruce-Pine-Fir #1 


10-4 


16-3 


21-0 


25-8 


Note a 


9-10 


14-4 


18-2 


22-3 


25-9 


Spruce-Pine-Fir #2 


10-4 


16-3 


21-0 


25-8 


Note a 


9-10 


14-4 


18-2 


22-3 


25-9 


Spruce-Pine-Fir #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


16 


Douglas Fir-Larch SS 


10-5 


16-4 


21-7 


Note a 


Note a 


10-5 


16-0 


20-3 


24-9 


Note a 


Douglas Fir-Larch #1 


10-0 


15-4 


19-5 


23-9 


Note a 


9-1 


13-3 


16-10 


20-7 


23-10 


Douglas Fir-Larch #2 


9-10 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Douglas Fir-Larch #3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Hem-Fir SS 


9-10 


15-6 


20-5 


Note a 


Note a 


9-10 


15-6 


19-11 


24-4 


Note a 


Hem-Fir #1 


9-8 


14-11 


18-11 


23-2 


Note a 


8-10 


12-11 


16-5 


20-0 


23-3 


Hem-Fir #2 


9-2 


14-2 


17-11 


21-11 


25-5 


8-5 


12-3 


15-6 


18-11 


22-0 


Hsm-Fir #1 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Southern Pine SS 


10-3 


16-1 


21-2 


Note a 


Note a 


10-3 


16-1 


21-2 


Note a 


Note a 


Southern Pine #1 


10-0 


15-9 


20-10 


25-10 


Note a 


10-0 


15-0 


18-10 


22-4 


Note a 


Southern Pine #2 


9-10 


15-1 


19-5 


23-2 


Note a 


9-1 


13-0 


16-10 


20-1 


23-7 


Southern Pine #3 


7-11 


11-8 


14-10 


17-6 


20-11 


6-10 


10-1 


12-10 


15-2 


18-1 


Spruce-Pine-Fir SS 


9-8 


15-2 


19-11 


25-5 


Note a 


9-8 


14-10 


18-10 


23-0 


Note a 


Spruce-Pine-Fir #1 


9-5 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Spruce-Pine-Fir #2 


9-5 


14-4 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Spruce-Pine-Fir #3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 



o 
o 

O 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 



TABLE 2308.10.3(1)-continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof Live Load =20 pounds per square foot, Ceiling Not Attached to Rafters, L/A =180) 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 






Maximum rafter soans 


Ift. - in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


Ift. - in.) 


Ift. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


19.2 


Douglas Fir-Larch SS 


9-10 


15-5 


20-4 


25-11 


Note a 


9-10 


14-7 


18-6 


22-7 


Note a 


Douglas Fir-Larch #1 


9-5 


14-0 


17-9 


21-8 


25-2 


8-4 


12-2 


15-4 


18-9 


21-9 


Douglas Fir-Larch #2 


8-11 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Douglas Fir-Larch #3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Hem-Fir SS 


9-3 


14-7 


19-2 


24-6 


Note a 


9-3 


14-4 


18-2 


22-3 


25-9 


Hem-Fir #1 


9-1 


13-8 


17-4 


21-1 


24-6 


8-1 


11-10 


15-0 


18-4 


21-3 


Hem-Fir #2 


8-8 


12-11 


16-4 


20-0 


23-2 


7-8 


11-2 


14-2 


17-4 


20-1 


Hem-Fir #3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Southern Pine SS 


9-8 


15-2 


19-11 


25-5 


Note a 


9-8 


15-2 


19-11 


25-5 


Note a 


Southern Pine #1 


9-5 


14-10 


19-7 


23-7 


Note a 


9-3 


13-8 


17-2 


20-5 


24-4 


Southern Pine #2 


9-3 


13-9 


17-9 


21-2 


24-10 


8-4 


11-11 


15-4 


18-4 


21-6 


Southern Pine #3 


7-3 


10-8 


13-7 


16-0 


19-1 


6-3 


9-3 


11-9 


13-10 


16-6 


Spruce-Pine-Fir SS 


9-1 


14-3 


18-9 


23-11 


Note a 


9-1 


13-7 


17-2 


21-0 


24-4 


Spruce-Pine-Fir #1 


8-10 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Spruce-Pine-Fir #2 


8-10 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Soruce-Pine-Fir #3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


24 


Douglas Fir-Larch SS 


9-1 


14-4 


18-10 


23-4 


Note a 


8-11 


13-1 


16-7 


20-3 


23-5 


Douglas Fir-Larch #1 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Douglas Fir-Larch #2 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Douglas Fir-Larch #3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 


Hem-Fir SS 


8-7 


13-6 


17-10 


22-9 


Note a 


8-7 


12-10 


16-3 


19-10 


23-0 


Hem-Fir #1 


8-4 


12-3 


15-6 


18-11 


21-11 


7-3 


10-7 


13-5 


16-4 


19-0 


Hem-Fir #2 


7-11 


11-7 


14-8 


17-10 


20-9 


6-10 


10-0 


12-8 


15-6 


17-11 


Hsm-Fir #1 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 


Southern Pine SS 


8-11 


14-1 


18-6 


23-8 


Note a 


8-11 


14-1 


18-6 


22-11 


Note a 


Southern Pine #1 


8-9 


13-9 


17-9 


21-1 


25-2 


8-3 


12-3 


15-4 


18-3 


21-9 


Southern Pine #2 


8-7 


12-3 


15-10 


18-11 


22-2 


7-5 


10-8 


13-9 


16-5 


19-3 


Southern Pine #3 


6-5 


9-6 


12-1 


14-4 


17-1 


5-7 


8-3 


10-6 


12-5 


14-9 


Spruce-Pine-Fir SS 


8-5 


13-3 


17-5 


21-8 


25-2 


8-4 


12-2 


15-4 


18-9 


21-9 


Spruce-Pine-Fir #1 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Spruce-Pine-Fir #2 


8-0 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Spruce-Pine-Fir #3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 
a. Span exceeds 26 feet in length. Check sources 



1 pound per square foot = 
for availability of lumber 



47.9 N/m • 

in lengths greater than 20 feet. 



o 
o 

D 



TABLE 2308.10.3(2) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof Live Load = 20 pounds per square foot, Ceiling Not Attached to Rafters, L/A = 240) 



O 
O 

O 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 oounds oer sauare foot 


DEAD LOAD =20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


12 


Douglas Fir-Larch SS 


10-5 


16-4 


21-7 


Note a 


Note a 


10-5 


16-4 


21-7 


Note a 


Note a 


Douglas Fir-Larch #1 


10-0 


15-9 


20-10 


Note a 


Note a 


10-0 


15-4 


19-5 


23-9 


Note a 


Douglas Fir-Larch #2 


9-10 


15-6 


20-5 


25-8 


Note a 


9-10 


14-4 


18-2 


22-3 


25-9 


Douglas Fir-Larch #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Hem-Fir SS 


9-10 


15-6 


20-5 


Note a 


Note a 


9-10 


15-6 


20-5 


Note a 


Note a 


Hem-Fir #1 


9-8 


15-2 


19-11 


25-5 


Note a 


9-8 


14-11 


18-11 


23-2 


Note a 


Hem-Fir #2 


9-2 


14-5 


19-0 


24-3 


Note a 


9-2 


14-2 


17-11 


21-11 


25-5 


Hem -Fir #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Southern Pine SS 


10-3 


16-1 


21-2 


Note a 


Note a 


10-3 


16-1 


21-2 


Note a 


Note a 


Southern Pine #1 


10-0 


15-9 


20-10 


Note a 


Note a 


10-0 


15-9 


20-10 


25-10 


Note a 


Southern Pine #2 


9-10 


15-6 


20-5 


Note a 


Note a 


9-10 


15-1 


19-5 


23-2 


Note a 


Southern Pine #3 


9-1 


13-6 


17-2 


20-3 


24-1 


7-11 


11-8 


14-10 


17-6 


20-11 


Spruce-Pine-Fir SS 


9-8 


15-2 


19-11 


25-5 


Note a 


9-8 


15-2 


19-11 


25-5 


Note a 


Spruce-Pine-Fir #1 


9-5 


14-9 


19-6 


24-10 


Note a 


9-5 


14-4 


18-2 


22-3 


25-9 


Spruce-Pine-Fir #2 


9-5 


14-9 


19-6 


24-10 


Note a 


9-5 


14-4 


18-2 


22-3 


25-9 


Soruce-Pine-Fir #3 


8-7 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


16 


Douglas Fir-Larch SS 


9-6 


14-11 


19-7 


25-0 


Note a 


9-6 


14-11 


19-7 


24-9 


Note a 


Douglas Fir-Larch #1 


9-1 


14-4 


18-11 


23-9 


Note a 


9-1 


13-3 


16-10 


20-7 


23-10 


Douglas Fir-Larch #2 


8-11 


14-1 


18-2 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Douglas Fir-Larch #3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Hem-Fir SS 


8-11 


14-1 


18-6 


23-8 


Note a 


8-11 


14-1 


18-6 


23-8 


Note a 


Hem-Fir #1 


8-9 


13-9 


18-1 


23-1 


Note a 


8-9 


12-11 


16-5 


20-0 


23-3 


Hem-Fir #2 


8-4 


13-1 


17-3 


21-11 


25-5 


8-4 


12-3 


15-6 


18-11 


22-0 


Hem -Fir W 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 


Southern Pine SS 


9-4 


14-7 


19-3 


24-7 


Note a 


9-4 


14-7 


19-3 


24-7 


Note a 


Southern Pine #1 


9-1 


14-4 


18-11 


24-1 


Note a 


9-1 


14-4 


18-10 


22-4 


Note a 


Southern Pine #2 


8-11 


14-1 


18-6 


23-2 


Note a 


8-11 


13-0 


16-10 


20-1 


23-7 


Southern Pine #3 


7-11 


11-8 


14-10 


17-6 


20-11 


6-10 


10-1 


12-10 


15-2 


18-1 


Spruce-Pine-Fir SS 


8-9 


13-9 


18-1 


23-1 


Note a 


8-9 


13-9 


18-1 


23-0 


Note a 


Spruce-Pine-Fir #1 


8-7 


13-5 


17-9 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Spruce-Pine-Fir #2 


8-7 


13-5 


17-9 


22-3 


25-9 


8-6 


12-5 


15-9 


19-3 


22-4 


Spruce-Pine-Fir #3 


7-5 


10-10 


13-9 


16-9 


19-6 


6-5 


9-5 


11-11 


14-6 


16-10 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 



TABLE 2308.1 0.3(2)-continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Roof Live Load =20 pounds per square foot, Ceiling Not Attached to Rafters, L/A =240) 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 


2x6 


2x8 2x10 


2x 12 


2x4 


2x6 


2x8 2x10 


2x12 


















(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


19.2 


Douglas Fir-Larch 


SS 


8-11 


14-0 


18-5 


23-7 


Note a 


8-11 


14-0 


18-5 


22-7 


Note a 


Douglas Fir-Larch 


#1 


8-7 


13-6 


17-9 


21-8 


25-2 


8-4 


12-2 


15-4 


18-9 


21-9 


Douglas Fir-Larch 


#2 


8-5 


13-1 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Douglas Fir-Larch 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Hem-Fir 


SS 


8-5 


13-3 


17-5 


22-3 


Note a 


8-5 


13-3 


17-5 


22-3 


25-9 


Hem-Fir 


#1 


8-3 


12-11 


17-1 


21-1 


24-6 


8-1 


11-10 


15-0 


18-4 


21-3 


Hem-Fir 


#2 


7-10 


12-4 


16-3 


20-0 


23-2 


7-8 


11-2 


14-2 


17-4 


20-1 


Hem-Fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


Southern Pine 


SS 


8-9 


13-9 


18-1 


23-1 


Note a 


8-9 


13-9 


18-1 


23-1 


Note a 


Southern Pine 


#1 


8-7 


13-6 


17-9 


22-8 


Note a 


8-7 


13-6 


17-2 


20-5 


24-4 


Southern Pine 


#2 


8-5 


13-3 


17-5 


21-2 


24-10 


8-4 


11-11 


15-4 


18-4 


21-6 


Southern Pine 


#3 


7-3 


10-8 


13-7 


16-0 


19-1 


6-3 


9-3 


11-9 


13-10 


16-6 


Spruce-Pine-Fir 


SS 


8-3 


12-11 


17-1 


21-9 


Note a 


8-3 


12-11 


17-1 


21-0 


24-4 


Spruce-Pine-Fir 


#1 


8-1 


12-8 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Spruce-Pine-Fir 


#2 


8-1 


12-8 


16-7 


20-3 


23-6 


7-9 


11-4 


14-4 


17-7 


20-4 


Soruce-Pine-Fir 


#3 


6-9 


9-11 


12-7 


15-4 


17-9 


5-10 


8-7 


10-10 


13-3 


15-5 


24 


Douglas Fir-Larch 


SS 


8-3 


13-0 


17-2 


21-10 


Note a 


8-3 


13-0 


16-7 


20-3 


23-5 


Douglas Fir-Larch 


#1 


8-0 


12-6 


15-10 


19-5 


22-6 


7-5 


10-10 


13-9 


16-9 


19-6 


Douglas Fir-Larch 


#2 


7-10 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Douglas Fir-Larch 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 


Hem-Fir 


SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


19-10 


23-0 


Hem-Fir 


#1 


7-8 


12-0 


15-6 


18-11 


21-11 


7-3 


10-7 


13-5 


16-4 


19-0 


Hem-Fir 


#2 


7-3 


11-5 


14-8 


17-10 


20-9 


6-10 


10-0 


12-8 


15-6 


17-11 




#1 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


H-Q 


Southern Pine 


SS 


8-1 


12-9 


16-10 


21-6 


Note a 


8-1 


12-9 


16-10 


21-6 


Note a 


Southern Pine 


#1 


8-0 


12-6 


16-6 


21-1 


25-2 


8-0 


12-3 


15-4 


18-3 


21-9 


Southern Pine 


#2 


7-10 


12-3 


15-10 


18-11 


22-2 


7-5 


10-8 


13-9 


16-5 


19-3 


Southern Pine 


#3 


6-5 


9-6 


12-1 


14-4 


17-1 


5-7 


8-3 


10-6 


12-5 


14-9 


Spruce-Pine-Fir 


SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-4 


18-9 


21-9 


Spruce-Pine-Fir 


#1 


7-6 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Spruce-Pine-Fir 


#2 


7-6 


11-9 


14-10 


18-2 


21-0 


6-11 


10-2 


12-10 


15-8 


18-3 


Spruce-Pine-Fir 


#3 


6-1 


8-10 


11-3 


13-8 


15-11 


5-3 


7-8 


9-9 


11-10 


13-9 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.9 N/m 2 - 

a. Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet. 



8 



o 
o 

D 



TABLE 2308.10.3(3) 
RAFTER SPANS FOR COMMON LUMBER SPECIES 
(Ground Snow Load =30 pounds per square foot, Ceiling Not Attached to Rafters, UA - 



:180) 



O 
O 

O 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


12 


Douglas Fir-Larch SS 


10-0 


15-9 


20-9 


Note a 


Note a 


10-0 


15-9 


20-1 


24-6 


Note a 


Douglas Fir-Larch #1 


9-8 


14-9 


18-8 


22-9 


Note a 


9-0 


13-2 


16-8 


20-4 


23-7 


Douglas Fir-Larch #2 


9-5 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 


Douglas Fir-Larch #3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Hem-Fir SS 


9-6 


14-10 


19-7 


25-0 


Note a 


9-6 


14-10 


19-7 


24-1 


Note a 


Hem-Fir #1 


9-3 


14-4 


18-2 


22-2 


25-9 


8-9 


12-10 


16-3 


19-10 


23-0 


Hem-Fir #2 


8-10 


13-7 


17-2 


21-0 


24-4 


8-4 


12-2 


15-4 


18-9 


21-9 


Hem -Fir #3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Southern Pine SS 


9-10 


15-6 


20-5 


Note a 


Note a 


9-10 


15-6 


20-5 


Note a 


Note a 


Southern Pine #1 


9-8 


15-2 


20-0 


24-9 


Note a 


9-8 


14-10 


18-8 


22-2 


Note a 


Southern Pine #2 


9-6 


14-5 


18-8 


22-3 


Note a 


9-0 


12-11 


16-8 


19-11 


23-4 


Southern Pine #3 


7-7 


11-2 


14-3 


16-10 


20-0 


6-9 


10-0 


12-9 


15-1 


17-11 


Spruce-Pine-Fir SS 


9-3 


14-7 


19-2 


24-6 


Note a 


9-3 


14-7 


18-8 


22-9 


Note a 


Spruce-Pine-Fir #1 


9-1 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 


Spruce-Pine-Fir #2 


9-1 


13-9 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 


Soruce-Pine-Fir #3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


16 


Douglas Fir-Larch SS 


9-1 


14-4 


18-10 


23-9 


Note a 


9-1 


13-9 


17-5 


21-3 


24-8 


Douglas Fir-Larch #1 


8-9 


12-9 


16-2 


19-9 


22-10 


7-10 


11-5 


14-5 


17-8 


20-5 


Douglas Fir-Larch #2 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Douglas Fir-Larch #3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Hem-Fir SS 


8-7 


13-6 


17-10 


22-9 


Note a 


8-7 


13-6 


17-1 


20-10 


24-2 


Hem-Fir #1 


8-5 


12-5 


15-9 


19-3 


22-3 


7-7 


11-1 


14-1 


17-2 


19-11 


Hem-Fir #2 


8-0 


11-9 


14-11 


18-2 


21-1 


7-2 


10-6 


13-4 


16-3 


18-10 


Hem-Fir #3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Southern Pine SS 


8-11 


14-1 


18-6 


23-8 


Note a 


8-11 


14-1 


18-6 


23-8 


Note a 


Southern Pine #1 


8-9 


13-9 


18-1 


21-5 


25-7 


8-8 


12-10 


16-2 


19-2 


22-10 


Southern Pine #2 


8-7 


12-6 


16-2 


19-3 


22-7 


7-10 


11-2 


14-5 


17-3 


20-2 


Southern Pine #3 


6-7 


9-8 


12-4 


14-7 


17-4 


5-10 


8-8 


11-0 


13-0 


15-6 


Spruce-Pine-Fir SS 


8-5 


13-3 


17-5 


22-1 


25-7 


8-5 


12-9 


16-2 


19-9 


22-10 


Spruce-Pine-Fir #1 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Spruce-Pine-Fir #2 


8-2 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Spruce-Pine-Fir #3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 



TABLE 2308.1 0.3(3)-continued 
RAFTER SPANS FOR COMMON LUMBER SPECIES 
(Ground Snow Load =30 pounds per square foot, Ceiling Not Attached to Rafters, L/A = 



= 180) 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 






Maximum rafter soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


19.2 


Douglas Fir-Larch SS 


8-7 


13-6 


17-9 


21-8 


25-2 


8-7 


12-6 


15-10 


19-5 


22-6 


Douglas Fir-Larch #1 


7-11 


11-8 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 


Douglas Fir-Larch #2 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Douglas Fir-Larch #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Hem-Fir SS 


8-1 


12-9 


16-9 


21-4 


24-8 


8-1 


12-4 


15-7 


19-1 


22-1 


Hem-Fir #1 


7-9 


11-4 


14-4 


17-7 


20-4 


6-11 


10-2 


12-10 


15-8 


18-2 


Hem-Fir #2 


7-4 


10-9 


13-7 


16-7 


19-3 


6-7 


9-7 


12-2 


14-10 


17-3 


Hem-Fir #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Southern Pine SS 


8-5 


13-3 


17-5 


22-3 


Note a 


8-5 


13-3 


17-5 


22-0 


25-9 


Southern Pine #1 


8-3 


13-0 


16-6 


19-7 


23-4 


7-11 


11-9 


14-9 


17-6 


20-11 


Southern Pine #2 


7-11 


11-5 


14-9 


17-7 


20-7 


7-1 


10-2 


13-2 


15-9 


18-5 


Southern Pine #3 


6-0 


8-10 


11-3 


13-4 


15-10 


5-4 


7-11 


10-1 


11-11 


14-2 


Spruce-Pine-Fir SS 


7-11 


12-5 


16-5 


20-2 


23-4 


7-11 


11-8 


14-9 


18-0 


20-11 


Spruce-Pine-Fir #1 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Spruce-Pine-Fir #2 


7-5 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Soruce-Pine-Fir #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


24 


Douglas Fir-Larch SS 


7-11 


12-6 


15-10 


19-5 


22-6 


7-8 


11-3 


14-2 


17-4 


20-1 


Douglas Fir-Larch #1 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Douglas Fir-Larch #2 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Douglas Fir-Larch #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Hem-Fir SS 


7-6 


11-10 


15-7 


19-1 


22-1 


7-6 


11-0 


13-11 


17-0 


19-9 


Hem-Fir #1 


6-11 


10-2 


12-10 


15-8 


18-2 


6-2 


9-1 


11-6 


14-0 


16-3 


Hem-Fir #2 


6-7 


9-7 


12-2 


14-10 


17-3 


5-10 


8-7 


10-10 


13-3 


15-5 


Hsm-Fir #1 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Southern Pine SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


19-8 


23-0 


Southern Pine #1 


7-8 


11-9 


14-9 


17-6 


20-11 


7-1 


10-6 


13-2 


15-8 


18-8 


Southern Pine #2 


7-1 


10-2 


13-2 


15-9 


18-5 


6-4 


9-2 


11-9 


14-1 


16-6 


Southern Pine #3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-9 


7-1 


9-0 


10-8 


12-8 


Spruce-Pine-Fir SS 


7-4 


11-7 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #1 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Spruce-Pine-Fir #2 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Spruce-Pine-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 
a. Span exceeds 26 feet in length. Check sources 



1 pound per square foot = 
for availability of lumber 



47.9 N/m ■ 

in lengths greater than 20 feet. 



s 

o 
o 

D 



TABLE 2308.10.3(4) 
RAFTER SPANS FOR COMMON LUMBER SPECIES 
(Ground Snow Load = 50 pounds per square foot, Ceiling Not Attached to Rafters, L/A = 



180) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 Dounds Der sauare foot 


DEAD LOAD - 20 Dounds Der sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter SDans 


Ift. - in.) 


(ft. - in.) 


(ft. in.) 


Ift. - in.) 


Ift. - in.) 


Ift. in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


Ift. - in.) 


12 


Douglas Fir-Larch SS 


8-5 


13-3 


17-6 


22-4 


26-0 


8-5 


13-3 


17-0 


20-9 


24-10 


Douglas Fir-Larch #1 


8-2 


12-0 


15-3 


18-7 


21-7 


7-7 


11-2 


14-1 


17-3 


20-0 


Douglas Fir-Larch #2 


7-8 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 


Douglas Fir-Larch #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Hem-Fir SS 


8-0 


12-6 


16-6 


21-1 


25-6 


8-0 


12-6 


16-6 


20-4 


23-7 


Hem-Fir #1 


7-10 


11-9 


14-10 


18-1 


21-0 


7-5 


10-10 


13-9 


16-9 


19-5 


Hem-Fir #2 


7-5 


11-1 


14-0 


17-2 


19-11 


7-0 


10-3 


13-0 


15-10 


18-5 


Hem-Fir #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Southern Pine SS 


8-4 


13-0 


17-2 


21-11 


Note a 


8-4 


13-0 


17-2 


21-11 


Note a 


Southern Pine #1 


8-2 


12-10 


16-10 


20-3 


24-1 


8-2 


12-6 


15-9 


18-9 


22-4 


Southern Pine #2 


8-0 


11-9 


15-3 


18-2 


21-3 


7-7 


10-11 


14-1 


16-10 


19-9 


Southern Pine #3 


6-2 


9-2 


11-8 


13-9 


16-4 


5-9 


8-5 


10-9 


12-9 


15-2 


Spruce-Pine-Fir SS 


7-10 


12-3 


16-2 


20-8 


24-1 


7-10 


12-3 


15-9 


19-3 


22-4 


Spruce-Pine-Fir #1 


7-8 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #2 


7-8 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


16 


Douglas Fir-Larch SS 


7-8 


12-1 


15-10 


19-5 


22-6 


7-8 


11-7 


14-8 


17-11 


20-10 


Douglas Fir-Larch #1 


7-1 


10-5 


13-2 


16-1 


18-8 


6-7 


9-8 


12-2 


14-11 


17-3 


Douglas Fir-Larch #2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Douglas Fir-Larch #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Hem-Fir SS 


7-3 


11-5 


15-0 


19-1 


22-1 


7-3 


11-5 


14-5 


17-8 


20-5 


Hem-Fir #1 


6-11 


10-2 


12-10 


15-8 


18-2 


6-5 


9-5 


11-11 


14-6 


16-10 


Hem-Fir #2 


6-7 


9-7 


12-2 


14-10 


17-3 


6-1 


8-11 


11-3 


13-9 


15-11 


Hem-Fir #1 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Southern Pine SS 


7-6 


11-10 


15-7 


19-11 


24-3 


7-6 


11-10 


15-7 


19-11 


23-10 


Southern Pine #1 


7-5 


11-7 


14-9 


17-6 


20-11 


7-4 


10-10 


13-8 


16-2 


19-4 


Southern Pine #2 


7-1 


10-2 


13-2 


15-9 


18-5 


6-7 


9-5 


12-2 


14-7 


17-1 


Southern Pine #3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-11 


7-4 


9-4 


11-0 


13-1 


Spruce-Pine-Fir SS 


7-1 


11-2 


14-8 


18-0 


20-11 


7-1 


10-9 


13-8 


16-8 


19-4 


Spruce-Pine-Fir #1 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Spruce-Pine-Fir #2 


6-8 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Spruce-Pine-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 



o 
o 

O 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 
o 



TABLE 2308.10.3(4)-continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground Snow Load =50 pounds per square foot, Ceiling Not Attached to Rafters, L/A =180) 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


19.2 


Douglas Fir-Larch SS 


7-3 


11-4 


14-6 


17-8 


20-6 


7-3 


10-7 


13-5 


16-5 


19-0 


Douglas Fir-Larch #1 


6-6 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 


Douglas Fir-Larch #2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Douglas Fir-Larch #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Hem-Fir SS 


6-10 


10-9 


14-2 


17-5 


20-2 


6-10 


10-5 


13-2 


16-1 


18-8 


Hem-Fir #1 


6-4 


9-3 


11-9 


14-4 


16-7 


5-10 


8-7 


10-10 


13-3 


15-5 


Hem-Fir #2 


6-0 


8-9 


11-1 


13-7 


15-9 


5-7 


8-1 


10-3 


12-7 


14-7 


Hem-Fir #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Southern Pine SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18-7 


21-9 


Southern Pine #1 


7-0 


10-8 


13-5 


16-0 


19-1 


6-8 


9-11 


12-5 


14-10 


17-8 


Southern Pine #2 


6-6 


9-4 


12-0 


14-4 


16-10 


6-0 


8-8 


11-2 


13-4 


15-7 


Southern Pine #3 


4-11 


7-3 


9-2 


10-10 


12-11 


4-6 


6-8 


8-6 


10-1 


12-0 


Spruce-Pine-Fir SS 


6-8 


10-6 


13-5 


16-5 


19-1 


6-8 


9-10 


12-5 


15-3 


17-8 


Spruce-Pine-Fir #1 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Spruce-Pine-Fir #2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Soruce-Pine-Fir #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


24 


Douglas Fir-Larch SS 


6-8 


10-3 


13-0 


15-10 


18-4 


6-6 


9-6 


12-0 


14-8 


17-0 


Douglas Fir-Larch #1 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Douglas Fir-Larch #2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Douglas Fir-Larch #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Hem-Fir SS 


6-4 


9-11 


12-9 


15-7 


18-0 


6-4 


9-4 


11-9 


14-5 


16-8 


Hem-Fir #1 


5-8 


8-3 


10-6 


12-10 


14-10 


5-3 


7-8 


9-9 


11-10 


13-9 


Hem-Fir #2 


5-4 


7-10 


9-11 


12-1 


14-1 


4-11 


7-3 


9-2 


11-3 


13-0 


Hem -Fir #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Southern Pine SS 


6-7 


10-4 


13-8 


17-5 


21-0 


6-7 


10-4 


13-8 


16-7 


19-5 


Southern Pine #1 


6-5 


9-7 


12-0 


14-4 


17-1 


6-0 


8-10 


11-2 


13-3 


15-9 


Southern Pine #2 


5-10 


8-4 


10-9 


12-10 


15-1 


5-5 


7-9 


10-0 


11-11 


13-11 


Southern Pine #3 


4-4 


6-5 


8-3 


9-9 


11-7 


4-1 


6-0 


7-7 


9-0 


10-8 


Spruce-Pine-Fir SS 


6-2 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 


Spruce-Pine-Fir #1 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Spruce-Pine-Fir #2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Spruce-Pine-Fir #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.9 N/m~- 

a. Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet. 



o 
o 

D 



TABLE 2308.10.3(5) 
RAFTER SPANS FOR COMMON LUMBER SPECIES 









(Ground Snow Load = 30 pounds per square foot, Ceiling Attached to Rafters, L/A = 240) 








RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 oounds oer sauare foot 


DEAD LOAD - 20 oounds oer sauare foot 


2x4 


2x6 2x8 2x10 


2x 12 


2x4 


2x6 


2x8 


2x 10 


2x 12 


Maximum rafter soans 


Ift. - in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


Ift. - in.) 


Ift. in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


Ift. - in.) 


12 


Douglas Fir-Larch 


SS 


9-1 


14-4 


18-10 


24-1 


Note a 


9-1 


14-4 


18-10 


24-1 


Note a 


Douglas Fir-Larch 


#1 


8-9 


13-9 


18-2 


22-9 


Note a 


8-9 


13-2 


16-8 


20-4 


23-7 


Douglas Fir-Larch 


#2 


8-7 


13-6 


17-5 


21-4 


24-8 


8-5 


12-4 


15-7 


19-1 


22-1 


Douglas Fir-Larch 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Hem-Fir 


SS 


8-7 


13-6 


17-10 


22-9 


Note a 


8-7 


13-6 


17-10 


22-9 


Note a 


Hem-Fir 


#1 


8-5 


13-3 


17-5 


22-2 


25-9 


8-5 


12-10 


16-3 


19-10 


23-0 


Hem-Fir 


#2 


8-0 


12-7 


16-7 


21-0 


24-4 


8-0 


12-2 


15-4 


18-9 


21-9 


Hem-Fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Southern Pine 


SS 


8-11 


14-1 


18-6 


23-8 


Note a 


8-11 


14-1 


18-6 


23-8 


Note a 


Southern Pine 


#1 


8-9 


13-9 


18-2 


23-2 


Note a 


8-9 


13-9 


18-2 


22-2 


Note a 


Southern Pine 


#2 


8-7 


13-6 


17-10 


22-3 


Note a 


8-7 


12-11 


16-8 


19-11 


23-4 


Southern Pine 


#3 


7-7 


11-2 


14-3 


16-10 


20-0 


6-9 


10-0 


12-9 


15-1 


17-11 


Spruce-Pine-Fir 


SS 


8-5 


13-3 


17-5 


22-3 


Note a 


8-5 


13-3 


17-5 


22-3 


Note a 


Spruce-Pine-Fir 


#1 


8-3 


12-11 


17-0 


21-4 


24-8 


8-3 


12-4 


15-7 


19-1 


22-1 


Spruce-Pine-Fir 


#2 


8-3 


12-11 


17-0 


21-4 


24-8 


8-3 


12-4 


15-7 


19-1 


22-1 


Spruce-Pine-Fir 


#3 


7-1 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


16 


Douglas Fir-Larch 


SS 


8-3 


13-0 


17-2 


21-10 


Note a 


8-3 


13-0 


17-2 


21-3 


24-8 


Douglas Fir-Larch 


#1 


8-0 


12-6 


16-2 


19-9 


22-10 


7-10 


11-5 


14-5 


17-8 


20-5 


Douglas Fir-Larch 


#2 


7-10 


11-11 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Douglas Fir-Larch 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Hem-Fir 


SS 


7-10 


12-3 


16-2 


20-8 


25-1 


7-10 


12-3 


16-2 


20-8 


24-2 


Hem-Fir 


#1 


7-8 


12-0 


15-9 


19-3 


22-3 


7-7 


11-1 


14-1 


17-2 


19-11 


Hem-Fir 


#2 


7-3 


11-5 


14-11 


18-2 


21-1 


7-2 


10-6 


13-4 


16-3 


18-10 




#1 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 


Southern Pine 


SS 


8-1 


12-9 


16-10 


21-6 


Note a 


8-1 


12-9 


16-10 


21-6 


Note a 


Southern Pine 


#1 


8-0 


12-6 


16-6 


21-1 


25-7 


8-0 


12-6 


16-2 


19-2 


22-10 


Southern Pine 


#2 


7-10 


12-3 


16-2 


19-3 


22-7 


7-10 


11-2 


14-5 


17-3 


20-2 


Southern Pine 


#3 


6-7 


9-8 


12-4 


14-7 


17-4 


5-10 


8-8 


11-0 


13-0 


15-6 


Spruce-Pine-Fir 


SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-10 


19-9 


22-10 


Spruce-Pine-Fir 


#1 


7-6 


11-9 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Spruce-Pine-Fi 


#2 


7-6 


11-9 


15-1 


18-5 


21-5 


7-3 


10-8 


13-6 


16-6 


19-2 


Spruce-Pine-Fi 


#3 


6-2 


9-0 


11-5 


13-11 


16-2 


5-6 


8-1 


10-3 


12-6 


14-6 



o 
o 

O 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 



TABLE 2308.10.3(5)-continued 
RAFTER SPANS FOR COMMON LUMBER SPECIES 
(Ground Snow Load = 30 pounds per square foot, Ceiling Attached to Rafters, UA - 



240) 



RAFTER 
SPACING 
Cinches) 


SPECIES AND GRADE 


DEAD LOAD = 10 oounds oer sauare foot 


DEAD LOAD = 20 oounds oer sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter soans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


19.2 


Douglas Fir-Larch SS 


7-9 


12-3 


16-1 


20-7 


25-0 


7-9 


12-3 


15-10 


19-5 


22-6 


Douglas Fir-Larch #1 


7-6 


11-8 


14-9 


18-0 


20-11 


7-1 


10-5 


13-2 


16-1 


18-8 


Douglas Fir-Larch #2 


7-4 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Douglas Fir-Larch #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Hem-Fir SS 


7-4 


11-7 


15-3 


19-5 


23-7 


7-4 


11-7 


15-3 


19-1 


22-1 


Hem-Fir #1 


7-2 


11-4 


14-4 


17-7 


20-4 


6-11 


10-2 


12-10 


15-8 


18-2 


Hem-Fir #2 


6-10 


10-9 


13-7 


16-7 


19-3 


6-7 


9-7 


12-2 


14-10 


17-3 


Hem-Fir #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


Southern Pine SS 


7-8 


12-0 


15-10 


20-2 


24-7 


7-8 


12-0 


15-10 


20-2 


24-7 


Southern Pine #1 


7-6 


11-9 


15-6 


19-7 


23-4 


7-6 


11-9 


14-9 


17-6 


20-11 


Southern Pine #2 


7-4 


11-5 


14-9 


17-7 


20-7 


7-1 


10-2 


13-2 


15-9 


18-5 


Southern Pine #3 


6-0 


8-10 


11-3 


13-4 


15-10 


5-4 


7-11 


10-1 


11-11 


14-2 


Spruce-Pine-Fir SS 


7-2 


11-4 


14-11 


19-0 


23-1 


7-2 


11-4 


14-9 


18-0 


20-11 


Spruce-Pine-Fir #1 


7-0 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Spruce-Pine-Fir #2 


7-0 


10-11 


13-9 


16-10 


19-6 


6-8 


9-9 


12-4 


15-1 


17-6 


Soruce-Pine-Fir #3 


5-7 


8-3 


10-5 


12-9 


14-9 


5-0 


7-4 


9-4 


11-5 


13-2 


24 


Douglas Fir-Larch SS 


7-3 


11-4 


15-0 


19-1 


22-6 


7-3 


11-3 


14-2 


17-4 


20-1 


Douglas Fir-Larch #1 


7-0 


10-5 


13-2 


16-1 


18-8 


6-4 


9-4 


11-9 


14-5 


16-8 


Douglas Fir-Larch #2 


6-8 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Douglas Fir-Larch #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Hem-Fir SS 


6-10 


10-9 


14-2 


18-0 


21-11 


6-10 


10-9 


13-11 


17-0 


19-9 


Hem-Fir #1 


6-8 


10-2 


12-10 


15-8 


18-2 


6-2 


9-1 


11-6 


14-0 


16-3 


Hem-Fir #2 


6-4 


9-7 


12-2 


14-10 


17-3 


5-10 


8-7 


10-10 


13-3 


15-5 


Hem-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 


Southern Pine SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18-9 


22-10 


Southern Pine #1 


7-0 


10-11 


14-5 


17-6 


20-11 


7-0 


10-6 


13-2 


15-8 


18-8 


Southern Pine #2 


6-10 


10-2 


13-2 


15-9 


18-5 


6-4 


9-2 


11-9 


14-1 


16-6 


Southern Pine #3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-9 


7-1 


9-0 


10-8 


12-8 


Spruce-Pine-Fir SS 


6-8 


10-6 


13-10 


17-8 


20-11 


6-8 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #1 


6-6 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Spruce-Pine-Fir #2 


6-6 


9-9 


12-4 


15-1 


17-6 


5-11 


8-8 


11-0 


13-6 


15-7 


Spruce-Pine-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-6 


6-7 


8-4 


10-2 


11-10 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 
a. Span exceeds 26 feet in length. Check sources 



1 pound per square foot = 
for availability of lumber 



47.9 N/m". 

in lengths greater than 20 feet. 



o 
o 

D 



TABLE 2308.10.3(6) 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground Snow Load = 50 pounds per square foot, Ceiling Attached to Rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD =10 Dounds Der sauare foot 


DEAD LOAD - 20 Dounds Der sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter SDans 


Ift. - in.) 


(ft. - in.) 


(ft. in.) 


Ift. - in.) 


Ift. - in.) 


Ift. in.) 


(ft. - in.) 


(ft. - in.) 


Ift. - in.) 


Ift. - in.) 


12 


Douglas Fir-Larch SS 


7-8 


12-1 


15-11 


20-3 


24-8 


7-8 


12-1 


15-11 


20-3 


24-0 


Douglas Fir-Larch #1 


7-5 


11-7 


15-3 


18-7 


21-7 


7-5 


11-2 


14-1 


17-3 


20-0 


Douglas Fir-Larch #2 


7-3 


11-3 


14-3 


17-5 


20-2 


7-1 


10-5 


13-2 


16-1 


18-8 


Douglas Fir-Larch #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Hem-Fir SS 


7-3 


11-5 


15-0 


19-2 


23-4 


7-3 


11-5 


15-0 


19-2 


23-4 


Hem-Fir #1 


7-1 


11-2 


14-8 


18-1 


21-0 


7-1 


10-10 


13-9 


16-9 


19-5 


Hem-Fir #2 


6-9 


10-8 


14-0 


17-2 


19-11 


6-9 


10-3 


13-0 


15-10 


18-5 


Hem-Fir #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Southern Pine SS 


7-6 


11-0 


15-7 


19-11 


24-3 


7-6 


11-10 


15-7 


19-11 


24-3 


Southern Pine #1 


7-5 


11-7 


15-4 


19-7 


23-9 


7-5 


11-7 


15-4 


18-9 


22-4 


Southern Pine #2 


7-3 


11-5 


15-0 


18-2 


21-3 


7-3 


10-11 


14-1 


16-10 


19-9 


Southern Pine #3 


6-2 


9-2 


11-8 


13-9 


16-4 


5-9 


8-5 


10-9 


12-9 


15-2 


Spruce-Pine-Fir SS 


7-1 


11-2 


14-8 


18-9 


22-10 


7-1 


11-2 


14-8 


18-9 


22-4 


Spruce-Pine-Fir #1 


6-11 


10-11 


14-3 


17-5 


20-2 


6-11 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #2 


6-11 


10-11 


14-3 


17-5 


20-2 


6-11 


10-5 


13-2 


16-1 


18-8 


Spruce-Pine-Fir #3 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


16 


Douglas Fir-Larch SS 


7-0 


11-0 


14-5 


18-5 


22-5 


7-0 


11-0 


14-5 


17-11 


20-10 


Douglas Fir-Larch #1 


6-9 


10-5 


13-2 


16-1 


18-8 


6-7 


9-8 


12-2 


14-11 


17-3 


Douglas Fir-Larch #2 


6-7 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Douglas Fir-Larch #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Hem-Fir SS 


6-7 


10-4 


13-8 


17-5 


21-2 


6-7 


10-4 


13-8 


17-5 


20-5 


Hem-Fir #1 


6-5 


10-2 


12-10 


15-8 


18-2 


6-5 


9-5 


11-11 


14-6 


16-10 


Hem-Fir #2 


6-2 


9-7 


12-2 


14-10 


17-3 


6-1 


8-11 


11-3 


13-9 


15-11 


Hem-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 


Southern Pine SS 


6-10 


10-9 


14-2 


18-1 


22-0 


6-10 


10-9 


14-2 


18-1 


22-0 


Southern Pine #1 


6-9 


10-7 


13-11 


17-6 


20-11 


6-9 


10-7 


13-8 


16-2 


19-4 


Southern Pine #2 


6-7 


10-2 


13-2 


15-9 


18-5 


6-7 


9-5 


12-2 


14-7 


17-1 


Southern Pine #3 


5-4 


7-11 


10-1 


11-11 


14-2 


4-11 


7-4 


9-4 


11-0 


13-1 


Spruce-Pine-Fir SS 


6-5 


10-2 


13-4 


17-0 


20-9 


6-5 


10-2 


13-4 


16-8 


19-4 


Spruce-Pine-Fir #1 


6-4 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Spruce-Pine-Fir #2 


6-4 


9-9 


12-4 


15-1 


17-6 


6-2 


9-0 


11-5 


13-11 


16-2 


Spruce-Pine-Fir #3 


5-0 


7-4 


9-4 


11-5 


13-2 


4-8 


6-10 


8-8 


10-6 


12-3 



o 
o 

O 



CD 
O 
O 

o 
m 

® 



(continued) 



ho 

o 



TABLE 2308.10.3(6)-continued 

RAFTER SPANS FOR COMMON LUMBER SPECIES 

(Ground Snow Load = 50 pounds per square foot, Ceiling Attached to Rafters, L/A = 240) 



RAFTER 
SPACING 
(inches) 


SPECIES AND GRADE 


DEAD LOAD = 10 pounds per sauare foot 


DEAD LOAD = 20 pounds per sauare foot 


2x4 2x6 2x8 2x10 2x12 


2x4 2x6 2x8 2x10 2x12 


Maximum rafter spans 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


(ft. - in.) 


19.2 


Douglas Fir-Larch SS 


6-7 


10-4 


13-7 


17-4 


20-6 


6-7 


10-4 


13-5 


16-5 


19-0 


Douglas Fir-Larch #1 


6-4 


9-6 


12-0 


14-8 


17-1 


6-0 


8-10 


11-2 


13-7 


15-9 


Douglas Fir-Larch #2 


6-1 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Douglas Fir-Larch #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Hem-Fir SS 


6-2 


9-9 


12-10 


16-5 


19-11 


6-2 


9-9 


12-10 


16-1 


18-8 


Hem-Fir #1 


6-1 


9-3 


11-9 


14-4 


16-7 


5-10 


8-7 


10-10 


13-3 


15-5 


Hem-Fir #2 


5-9 


8-9 


11-1 


13-7 


15-9 


5-7 


8-1 


10-3 


12-7 


14-7 


Hem-Fir #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


Southern Pine SS 


6-5 


10-2 


13-4 


17-0 


20-9 


6-5 


10-2 


13-4 


17-0 


20-9 


Southern Pine #1 


6-4 


9-11 


13-1 


16-0 


19-1 


6-4 


9-11 


12-5 


14-10 


17-8 


Southern Pine #2 


6-2 


9-4 


12-0 


14-4 


16-10 


6-0 


8-8 


11-2 


13-4 


15-7 


Southern Pine #3 


4-11 


7-3 


9-2 


10-10 


12-11 


4-6 


6-8 


8-6 


10-1 


12-0 


Spruce-Pine-Fir SS 


6-1 


9-6 


12-7 


16-0 


19-1 


6-1 


9-6 


12-5 


15-3 


17-8 


Spruce-Pine-Fir #1 


5-11 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Spruce-Pine-Fir #2 


5-11 


8-11 


11-3 


13-9 


15-11 


5-7 


8-3 


10-5 


12-9 


14-9 


Spruce-Pine-Fir #3 


4-7 


6-9 


8-6 


10-5 


12-1 


4-3 


6-3 


7-11 


9-7 


11-2 


24 


Douglas Fir-Larch SS 


6-1 


9-7 


12-7 


15-10 


18-4 


6-1 


9-6 


12-0 


14-8 


17-0 


Douglas Fir-Larch #1 


5-10 


8-6 


10-9 


13-2 


15-3 


5-5 


7-10 


10-0 


12-2 


14-1 


Douglas Fir-Larch #2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Douglas Fir-Larch #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Hem-Fir SS 


5-9 


9-1 


11-11 


15-12 


18-0 


5-9 


9-1 


11-9 


14-5 


16-8 


Hem-Fir #1 


5-8 


8-3 


10-6 


12-10 


14-10 


5-3 


7-8 


9-9 


11-10 


13-9 


Hem-Fir #2 


5-4 


7-10 


9-11 


12-1 


14-1 


4-11 


7-3 


9-2 


11-3 


13-0 


Hem-Fir #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 


Southern Pine SS 


6-0 


9-5 


12-5 


15-10 


19-3 


6-0 


9-5 


12-5 


15-10 


19-3 


Southern Pine #1 


5-10 


9-3 


12-0 


14-4 


17-1 


5-10 


8-10 


11-2 


13-3 


15-9 


Southern Pine #2 


5-9 


8-4 


10-9 


12-10 


15-1 


5-5 


7-9 


10-0 


11-11 


13-11 


Southern Pine #3 


4-4 


6-5 


8-3 


9-9 


11-7 


4-1 


6-0 


7-7 


9-0 


10-8 


Spruce-Pine-Fir SS 


5-8 


8-10 


11-8 


14-8 


17-1 


5-8 


8-10 


11-2 


13-7 


15-9 


Spruce-Pine-Fir #1 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Spruce-Pine-Fir #2 


5-5 


7-11 


10-1 


12-4 


14-3 


5-0 


7-4 


9-4 


11-5 


13-2 


Spruce-Pine-Fir #3 


4-1 


6-0 


7-7 


9-4 


10-9 


3-10 


5-7 


7-1 


8-7 


10-0 



ForSI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.9 N/m • 



o 
o 

D 



WOOD 











TABLE 2308.10.4.1 
RAFTER TIE CONNECTIONS9 














RAFTER 
SLOPE 


TIE SPACING 

(inches) 


NO SNOW LOAD 


GROUND SNOW LOAD (pound per square foot) 


30 pounds per square foot 


50 pounds per square foot 


Roof span (feet) 


12 


20 


28 


36 


12 20 28 36 12 20 28 


36 






Requirec 


number of 16d common (3 1 / 2 M x 0.162") nails a ,b per connection , d,e,f 




3:12 


12 


4 


6 


8 


10 


4 


6 


8 


11 


5 


8 


12 


15 


16 


5 


7 


10 


13 


5 


8 


11 


14 


6 


11 


15 


20 


24 


7 


11 


15 


19 


7 


11 


16 


21 


9 


16 


23 


30 


32 


10 


14 


19 


25 


10 


16 


22 


28 


12 


27 


30 


40 


48 


14 


21 


29 


37 


14 


32 


36 


42 


18 


32 


46 


60 


4:12 


12 


3 


4 


5 


6 


3 


5 


6 


8 


4 


6 


9 


11 


16 


3 


5 


7 


8 


4 


6 


8 


11 


5 


8 


12 


15 


24 


4 


7 


10 


12 


5 


9 


12 


16 


7 


12 


17 


22 


32 


6 


9 


13 


16 


8 


12 


16 


22 


10 


16 


24 


30 


48 


8 


14 


19 


24 


10 


18 


24 


32 


14 


24 


34 


44 


5:12 


12 


3 


3 


4 


5 


3 


4 


5 


7 


3 


5 


7 


9 


16 


3 


4 


5 


7 


3 


5 


7 


9 


4 


7 


9 


12 


24 


4 


6 


8 


10 


4 


7 


10 


13 


6 


10 


14 


18 


32 


5 


8 


10 


13 


6 


10 


14 


18 


8 


14 


18 


24 


48 


7 


11 


15 


20 


8 


14 


20 


26 


12 


20 


28 


36 


7:12 


12 


3 


3 


3 


4 


3 


3 


4 


5 


3 


4 


5 


7 


16 


3 


3 


4 


5 


3 


4 


5 


6 


3 


5 


7 


9 


24 


3 


4 


6 


7 


3 


5 


7 


9 


4 


7 


10 


13 


32 


4 


6 


8 


10 


4 


8 


10 


12 


6 


10 


14 


18 


48 


5 


8 


11 


14 


6 


10 


14 


18 


9 


14 


20 


26 


9:12 


12 


3 


3 


3 


3 


3 


3 


3 


4 


3 


3 


4 


5 


16 


3 


3 


3 


4 


3 


3 


4 


5 


3 


4 


5 


7 


24 


3 


3 


5 


6 


3 


4 


6 


7 


3 


6 


8 


10 


32 


3 


4 


6 


8 


4 


6 


8 


10 


5 


8 


10 


14 


48 


4 


6 


9 


11 


5 


8 


12 


14 


7 


12 


16 


20 


12:12 


12 


3 


3 


3 


3 


3 


3 


3 


3 


3 


3 


3 


4 


16 


3 


3 


3 


3 


3 


3 


3 


4 


3 


3 


4 


5 


24 


3 


3 


3 


4 


3 


3 


4 


6 


3 


4 


6 


8 


32 


3 


3 


4 


5 


3 


5 


6 


8 


4 


6 


8 


10 


48 


3 


4 


6 


7 


4 


7 


8 


12 


6 


8 


12 


16 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47 .8 N/hi 2 . 

a. 40d box (5" x 0.162") or 16d sinker (3 1 / 4 n x 0.148") nails are permitted to be substituted for 16d common (37 2 " x 0.16") nails. 

b. Nailing requirements are permitted to be reduced 25 percent if nails are clinched. 

c. Rafter tie heel joint connections are not required where the ridge is supported by a load-bearing wall, header or ridge beam. 

d. When intermediate support of the rafter is provided by vertical struts or purlins to a load-bearing wall, the tabulated heeljoint connection requirements are permit- 
ted to be reduced proportionally to the reduction in span. 

e. Equivalent nailing patterns are required for ceilingjoist to ceilingjoist lap splices. 

f. Connected members shall be of sufficient size to prevent splitting due to nailing. 

g. For snow loads less than 30 pounds per square foot, the required number of nails is permitted to be reduced by multiplying by the ratio of actual snow load plus 10 
divided by 40, but not less than the number required for no snow load. 



510 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2308.10.4.2 Notches and holes. Notching at the ends 
of rafters or ceiling joists shall not exceed one-fourth 
the depth. Notches in the top or bottom of the rafter or 
ceiling joist shall not exceed one-sixth the depth and 
shall not be located in the middle one-third of the span, 
except that a notch not exceeding one-third of the depth 
is permitted in the top of the rafter or ceiling joist not 
further from the face of the support than the depth of the 
member. 

Holes bored in rafters or ceiling joists shall not be 
within 2 inches (51 mm) of the top and bottom and their 
diameter shall not exceed one-third the depth of the 
member. 

2308.10.4.3 Framing around openings. Trimmer and 
header rafters shall be doubled, or of lumber of equiva- 
lent cross section, where the span of the header exceeds 4 
feet (1219 mm). The ends of header rafters more than 6 
feet (1829 mm) long shall be supported by framing 
anchors or rafter hangers unless bearing on abeam, parti- 
tion or wall. 

2308.10.5 Purlins. Purlins to support roof loads are permit- 
ted to be installed to reduce the span of rafters within allow- 
able limits and shall be supported by struts to bearing walls. 
The maximum span of 2-inch by 4-inch (51 mm by 102 mm) 
purlins shall be 4 feet (1219 mm). The maximum span of the 
2-inch by 6-inch (51 mm by 152 mm) purlin shall be 6 feet 
(1829 mm), but in no case shall the purlin be smaller than 
the supported rafter. Struts shall not be smaller than 2-inch 
by 4-inch (51 mm by 102 mm) members. The unbraced 
length of struts shall not exceed 8 feet (2438 mm) and the 
minimum slope of the struts shall not be less than 45 degrees 
(0.79 rad) from the horizontal. 

2308.10.6 Blocking. Roof rafters and ceilingjoists shall be 
supported laterally to prevent rotation and lateral displace- 
ment in accordance with the provisions of Section 2308 .8 .5. 

2308.10.7 Engineered wood products. Prefabricated 
wood I-joists, structural glued-laminated timber and struc- 
tural composite lumber shall not be notched or drilled 
except where permitted by the manufacturer's recommen- 
dations or where the effects of such alterations are specifi- 
cally considered in the design of the member by a registered 
design professional. 

2308.10.8 Roof sheathing. Roof sheathing shall be in 
accordance with Tables 2304.7(3) and 2304.7(5) for wood 
structural panels, and Tables 2304.7(1) and 2304.7(2) for 
lumber and shall comply with Section 2304.7.2. 

2308.10.8.1 Joints. Joints in lumber sheathing shall 
occur over supports unless approved end-matched lum- 
ber is used, in which case each piece shall bear on at least 
two supports. 

2308.10.9 Roof planking. Planking shall be designed in 
accordance with the general provisions of this code. 

In lieu of such design, 2-inch (51 mm) tongue-and- 
groove planking is permitted in accordance with Table 
2308.10.9. Joints in such planking are permitted to be ran- 
domly spaced, provided the system is applied to not less 
than three continuous spans, planks are center matched and 



end matched or splined, each plank bears on at least one sup- 
port, andjoints are separated by at least 24 inches (610 mm) 
in adjacent pieces. 

2308.10.10 Wood trusses. Wood trusses shall be designed 
in accordance with Section 2303.4. 

2308.10.11 Attic ventilation. For atticventilation, see Sec- 
tion 1203.2. 

2308.11 Additional requirements for conventional con- 
struction in Seismic Design Category B or C. Structures of 
conventional light-frame construction in Seismic Design Cate- 
gory B or C, as determined in Section 1613, shall comply with 
Sections 2308.11.1 through 2308.11.3, in addition to the provi- 
sions of Sections 2308.1 through 2308.10. 

2308.11.1 Number of stories. Structures of conventional 
light-frame construction shall not exceed two stories above 
grade plane in Seismic Design Category C. 

2308.11.2 Concrete or masonry. Concrete or masonry 
walls and stone or masonry veneer shall not extend above a 
basement. 

Exceptions: 

1. Stone and masonry veneer is permitted to be used 
in the first two stories above grade plane or the 
first three stories above grade plane where the 
lowest story has concrete or masonry walls in Seis- 
mic Design Category B, provided that structural 
use panel wall bracing is used and the length of 
bracing provided is one- and one-half times the 
required length as determined in Table 
2308.9.3(1). 

2. Stone and masonry veneer is permitted to be used 
in the first story above grade plane or the first two 
stories above grade plane where the lowest story 
has concrete or masonry walls in Seismic Design 
Category B or C. 

3. Stone and masonry veneer is permitted to be used 
in both stories of buildings with two stories above 
grade plane in Seismic Design Categories Band 
C, provided the following criteria are met: 

3.1. Type of brace per Section 2308.9.3 shall be 
Method 3 and the allowable shear capacity 
in accordance with Table 2306.3 shall be a 
minimum of 350 plf (5108 N/m). 

3.2. Braced wall panels in the second story 
shall be located in accordance with Section 
2308.9.3 and not more than 25 feet (7620 
mm) on center, and the total length of 
braced wall panels shall be not less than 25 
percent of the braced wall line length. 
Braced wall panels in the first story shall be 
located in accordance with Section 
2308.9.3 and not more than 25 feet (7620 
mm) on center, and the total length of 
braced wall panels shall be not less than 45 
percent of the braced wall line length. 

3.3. Hold-down connectors shall be provided at 
the ends of each braced wall panel for the 



2009 INTERNATIONAL BUILDING CODE® 



511 



WOOD 



allowable design of 2,000 pounds (8896 
N). Hold-down connectors shall be pro- 
vided at the ends of each braced wall panel 
for the first story to foundation connection 
with an allowable capactiy of 3,900 
pounds (17 347 N). In all cases, the 



hold-down connector force shall be trans- I 
ferred to the foundation. 

3.4. Cripple walls shall not be permitted. 

2308.11.3 Framing and connection details. Framing and 
connection details shall conform to Sections 2308.11.3.1 
through 2308.11.3.3. 



TABLE 2308.10.9 
ALLOWABLE SPANS FOR 2-INCH TONGUE-AND-GROOVE DECKING 



SPAN a 

(feet) 


LIVE LOAD 
(pound per square foot) 


DEFLECTION LIMIT 


BENDING STRESS (1) 
(pound per square inch) 


MODULUS OF ELASTICITY (E) 
(pound per square inch) 


Roofs 


4 


20 


1/240 
1/360 


160 


170,000 
256,000 


30 


1/240 
1/360 


210 


256,000 
384,000 


40 


1/240 
1/360 


270 


340,000 
512,000 


4.5 


20 


1/240 
1/360 


200 


242,000 
305,000 


30 


1/240 
1/360 


270 


363,000 
405,000 


40 


1/240 
1/360 


350 


484,000 
725,000 


5.0 


20 


1/240 
1/360 


250 


332,000 
500,000 


30 


1/240 
1/360 


330 


495,000 
742,000 


40 


1/240 
1/360 


420 


660,000 
1,000,000 


5.5 


20 


1/240 
1/360 


300 


442,000 
660,000 


30 


1/240 
1/360 


400 


662,000 
998,000 


40 


1/240 
1/360 


500 


884,000 
1,330,000 


6.0 


20 


1/240 
1/360 


360 


575,000 
862,000 


30 


1/240 
1/360 


480 


862,000 
1,295,000 


40 


1/240 
1/360 


600 


1,150,000 
1,730,000 


6.5 


20 


1/240 
1/360 


420 


595,000 
892,000 


30 


1/240 
1/360 


560 


892,000 
1,340,000 


40 


1/240 
1/360 


700 


1,190,000 
1,730,000 



(continued) 



512 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



TABLE 2308.1 0.9-continued 
ALLOWABLE SPANS FOR 2-INCH TONGUE-AND-GROOVE DECKING 



SPAN a 

(feet) 


LIVE LOAD 
(pound per square foot) 


DEFLECTION LIMIT 


BENDING STRESS (1) 
(pound per square inch) 


MODULUS OF ELASTICITY (E) 
(pound per square inch) 


Roofs 


7.0 


20 


1/240 
1/360 


490 


910,000 
1,360,000 


30 


1/240 
1/360 


650 


1,370,000 
2,000,000 


40 


1/240 
1/360 


810 


1,820,000 
2,725,000 


7.5 


20 


1/240 
1/360 


560 


1,125,000 
1,685,000 


30 


1/240 
1/360 


750 


1,685,000 
2,530,000 


40 


1/240 
1/360 


930 


2,250,000 
3,380,000 


8.0 


20 


1/240 
1/360 


640 


1,360,000 
2,040,000 


30 


1/240 
1/360 


850 


2,040,000 
3,060,000 


Floors 


4 

4.5 
5.0 


40 


1/360 


840 
950 
1,060 


1,000,000 
1,300,000 
1,600,000 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.0479kN/m 2 , 1 pound per square inch = 0.00689 N/mm 2 - 

a. Spans are based on simple beam action with 10 pounds per square foot dead load and provisions for a 300-pound concentrated load on a 12-inch width of decking. 
Random layup is permitted in accordance with the provisions of Section 2308.10.9. Lumber thickness is l ! / 2 inches nominal. 



2308.11.3.1 Anchorage. Braced wall lines shall be 
anchored in accordance with Section 2308.6 at founda- 
tions. 

2308.11.3.2 Stepped footings. Where the height of a 
required braced wall panel extending from foundation to 
floor above varies more than 4 feet (1219 mm), the fol- 
lowing construction shall be used: 

1. Where the bottom of the footing is stepped and the 
lowest floor framing rests directly on a sill bolted 
to the footings, the sill shall be anchored as 
required in Section 2308.3.3. 

2. Where the lowest floor framing rests directly on a 
sill bolted to a footing not less than 8 feet (2438 
mm) in length along a line of bracing, the line shall 
be considered to be braced. The double plate of the 
cripple stud wall beyond the segment of footing 
extending to the lowest framed floor shall be spliced 
to the sill plate with metal ties, one on each side of 
the sill and plate . The metal ties shall not be less than 
0.058 inch [1.47 mm (16 galvanized gage)] by 1V 2 
inches (38 mm) wide by 48 inches (1219 mm) with 
eight 16d common nails on each side of the splice 
location (see Figure 2308.11.3.2). The metal tie 
shall have a minimum yield of 33,000 pounds per 
square inch (psi) (227 MPa). 



3. Where cripple walls occur between the top of the 
footing and the lowest floor framing, the bracing 
requirements for a story shall apply. 

2308.11.3.3 Openings in horizontal diaphragms. 
Openings in horizontal diaphragms with a dimension per- 
pendicular to thejoist that is greater than 4 feet (1219 mm) 
shall be constructed in accordance with the following: 

1. Blocking shall be provided beyond headers. 

2. Metal ties not less than 0.058 inch [1.47 mm (16 
galvanized gage)] by 1V 2 inches (38 mm) wide 
with eight 16d common nails on each side of the 
header-joist intersection shall be provided (see 
Figure 2308.11.3.3). The metal ties shall have a 
minimum yield of 33,000 psi (227 MPa). 

2308.12 Additional requirements for conventional construc- 
tion in Seismic Design Category D or E. Structures of conven- 
tionallight-frame construction in Seismic Design CategoryD or 
E, as determined in Section 1613, shall conform to Sections 
2308.12.1 through 2308.12.9, in addition to the requirements 
for Seismic Design Category B or Cin Section 2308.11. 

2308.12.1 Number of stories. Structures of conventional 
light-frame construction shall not exceed one story above 
grade plane in Seismic Design Category D or E. 



i 



2009 INTERNATIONAL BUILDING CODE® 



513 



WOOD 



2x SILL PLATE 






/'-0 MIN. 
SPLICE — 



CONCRETE 
STEPPED FOOTING 



Wh 



WHERE FOOTING SECTION "A" IS MORE THAN 8-0" 

OVIDE METALTIE 16GAx1 1/2"x4'-0 u MIN., EACH SIDE 
8-1 6d COMMON NAILS 

EACH SIDE OF SPLICE 

2-2x PLATE 



£ 




\V/A'^///a 



FOOTING SECTION ItA" 



"XNXV/ s\\VA\\\'/\\\\'/> 



2x CRIPPLE 
STUD WALL 



Wa'/////// 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



NOTE: WHERE FOOTING SECTION flAil 
IS LESS THAN 8'-0" LONG IN A 
25'-on TOTAL LENGTH WALL, PROVIDE 
BRACING AT CRIPPLE STUD WALL 



FIGURE 2308.11.3.2 
STEPPED FOOTING CONNECTION DETAILS 



PLYWOOD SHEATHING 

DIAPHRAGM OPENING 




METALTIE 16GA. x1 1l2 ll x4 l _0" MIN., (4 TOTAL) 
W/1 6-1 6d COMMON NAILS AS SHOWN 

-OR» 



METALTIE 16GA.X1 1/2" x (OPENING WIDTH + 4 , _0") MIN., 
(2TOTAL) W/24-16d COMMON NAILS 



For 51 : 1 inch = 25.4 mm, 1 foot = 304.8 mm. 



FIGURE 2308.11.3.3 
OPENINGS IN HORIZONTAL DIAPHRAGMS 



514 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



2308.12.2 Concrete or masonry. Concrete or masonry 
walls and stone or masonry veneer shall not extend above a 
basement. 

Exception: Stone and masonry veneer is permitted to be 
used in the first story above grade plane in Seismic Design 
Category D, provided the following criteria are met: 

1. Type of brace in accordance with Section 2308.9.3 
shall be Method 3 and the allowable shear capacity 
in accordance with Table 2306.3 shall be a mini- 
mum of 350 plf (5108 N/m). 

2. The bracing of the first story shall be located at 
each end and at least every 25 feet (7620 mm) o.c. 
but not less than 45 percent of the braced wall line. 

3. Hold-down connectors shall be provided at the 
ends of braced walls for the first floor to founda- 
tion with an allowable capacity of 2,100 pounds 
(9341 N). 

4. Cripple walls shall not be permitted. 

2308.12.3 Braced wall line spacing. Spacing between inte- 
rior and exterior braced wall lines shall not exceed 25 feet 
(7620 mm). 

2308.12.4 Braced wall line sheathing. Braced wall lines 
shall be braced by one of the types of sheathing prescribed by 
Table 2308.12.4 as shown in Figure 2308.9.3. The sum of 
lengths of braced wall panels at each braced wall line shall 
conform to Table 2308.12.4. Braced wall panels shall be dis- 
tributed along the length of the braced wall line and start at 
not more than 8 feet (2438 mm) from each end of the braced 
wall line. Panel sheathing joints shall occur over studs or 
blocking. Sheathing shall be fastened to studs, top and bot- 
tom plates and at panel edges occurring over blocking. Wall 
framing to which sheathing used for bracing is applied shall 
be nominal 2 inch wide [actual 1V 2 inch (38 mm)] or larger 
members. 

Cripple walls having a stud height exceeding 14 inches 
(356 mm) shall be considered a story for the purpose of this 
section and shall be braced as required for braced wall lines 
in accordance with Table 2308.12.4. Where interior braced 



wall lines occur without a continuous foundation below, the 
length of parallel exterior cripple wall bracing shall be one 
and one-halftimes the lengths required by Table 2308.12.4. 
Where the cripple wall sheathing type used is Type S-Wand 
this additional length of bracing cannot be provided, the 
capacity of Type S-W sheathing shall be increased by reduc- 
ing the spacing of fasteners along the perimeter of each 
piece of sheathing to 4 inches (102 mm) o.c. 

2308.12.5 Attachment of sheathing. Fastening of braced 
wall panel sheathing shall not be less than that prescribed in 
Table 2308.12.4 or 2304.9.1. Wall sheathing shall not be 
attached to framing members by adhesives. 

2308.12.6 Irregular structures. Conventional light-frame 
construction shall not be used in irregular portions of struc- 
tures in Seismic Design CategoryD or E. Such irregular por- 
tions of structures shall be designed to resist the forces 
specified in Chapter 16 to the extent such irregular features 
affect the performance of the conventional framing system. 
A portion of a structure shall be considered to be irregular 
where one or more of the conditions described in Items 1 
through 6 below are present. 

1. Where exterior braced wall panels are not in one plane 
vertically from the foundation to the uppermost story 
in which they are required, the structure shall be con- 
sidered to be irregular [see Figure 2308.12.6(1)] . 

Exception: Floors with cantilevers or setbacks not 
exceeding four times the nominal depth of the 
floorjoists [see Figure 2308. 12.6(2)] are permitted 
to support braced wall panels provided: 

1. Floorjoists are 2 inches by 10 inches (51 mm 
by 254 mm) or larger and spaced not more 
than 16 inches (406 mm) o.c. 

2. The ratio of the back span to the cantilever is 
at least 2: 1. 

3. Floorjoists at ends of braced wall panels are 
doubled. 

4. A continuous rim joist is connected to the 
ends of cantilevered joists. The rim joist is 



TABLE 2308.12.4 

WALL BRACING IN SEISMIC DESIGN CATEGORIES D AND E 

(Minimum Length of Wall Bracing per each 25 Linear Feet of Braced Wall Linea) 



CONDITION 


SHEATHING TYPE b 


5 OS <0.50 


0.50 <5 0S < 0.75 


0.75<S DS < 1.00 


5 OS >1.00 


One story 


G-pc 


10 feet 8 inches 


14 feet 8 inches 


18 feet 8 inches 


25 feet inches 


S-W 


5 feet 4 inches 


8 feet inches 


9 feet 4 inches 


12 feet inches 



For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. 

a. Minimum length of panel bracing of one face of the wall for S-W sheathing or both faces of the wall for G-P sheathing; hlw ratio shall not exceed 2:1. For S-W 
panel bracing of the same material on two faces of the wall, the minimum length is permitted to be one-half the tabulated value but the hlw ratio shall not exceed 2: 1 
and design for uplift is required. 

b. G-P = gypsum board, fiberboard, particleboard, lath and plaster or gypsum sheathing boards; S-W = wood structural panels and diagonal wood sheathing. 

c. Nailing as specified below shall occur at all panel edges at studs, at top and bottom plates and, where occurring, at blocking: 
For liz-inch gypsum board, 5d (0.113 inch diameter) cooler nails at 7 inches on center; 

For 5/ 8 -inch gypsum board, No. 11 gage (0.120 inch diameter) at 7 inches on center; 

For gypsum sheathing board, f/ 4 inches long by 7/15-inch head, diamond point galvanized nails at 4 inches on center; 

For gypsum lath, No. 13 gage (0.092 inch) by f/ 8 inches long, 19/64-inch head, plasterboard at 5 inches on center; 

For Portland cement plaster, No. 11 gage (0.120 inch) by l 1 / z inches long, 11 16 - inch head at 6 inches on center; 

For fiberboard and particleboard, No. 11 gage (0.120 inch) by /^inches long, 7/^-inch head, galvanized nails at 3 inches on center. 



2009 INTERNATIONAL BUILDING CODE® 



515 



WOOD 



permitted to be spliced using a metal tie not 
less than 0.058 inch (1.47 mm) (16 galva- 
nized gage) and 1V 2 inches (38 mm) wide 
fastened with six 16d common nails on each 
side. The metal tie shall have a minimum 
yield of 33,000 psi (227 MPa) . 

5. Joists at setbacks or the end of cantilevered 
joists shall not carry gravity loads from more 
than a single sto ry having uniform wall and 
roof loads, nor carry the reactions from 
headers having a span of 8 feet (2438 mm) or 
more. 

2. Where a section of floor or roof is not laterally sup- 
ported by braced wall lines on all edges, the structure 
shall be considered to be irregular [see Figure 
2308.12.6(3)]. 

Exception: Portions of roofs or floors that do not 
support braced wall panels above are permitted to 
extend up to 6 feet (1829 mm) beyond a braced 
wall line [see Figure 2308.12.6(4)]. 

3. Where the end of a required braced wall panel extends 
more than 1 foot (305 mm) over an opening in the wall 
below, the structure shall be considered to be irregu- 
lar. This requirement is applicable to braced wall pan- 
els offset in plane and to braced wall panels offset out 
of plane as permitted by the exception to Item 1 above 
in this section [see Figure 2308.12.6(5)] . 

Exception: Braced wall panels are permitted to 
extend over an opening not more than 8 feet (2438 
mm) in width where the header is a 4-inch by 
12-inch (102 mm by 305 mm) or larger member. 

4. Where portions of a floor level are vertically offset 
such that the framing members on either side of the 
offset cannot be lapped or tied together in an 
approvedmarmer, the structure shall be considered to 
be irregular [see Figure 2308.12.6(6)]. 

Exception: Framing supported directly by foun- 
dations need not be lapped or tied directly together. 



5. Where braced wall lines are not perpendicular to each 
other, the structure shall be considered to be irregular 
[see Figure 2308.12.6(7)]. 

6. Where openings in floor and roof diaphragms having 
a maximum dimension greater than 50 percent of the 
distance between lines of bracing or an area greater 
than 25 percent of the area between orthogonal pairs 
of braced wall lines are present, the structure shall be 
considered to be irregular [see Figure 2308. 12.6 (8)]. 

2308.12.7 Anchorage of exterior means of egress compo- 
nents. Exterior egress balconies, exterior exit stairways and 
similar means of egress components shall be positively 
anchored to the primary structure at not over 8 feet (2438 
mm) o.c. or shall be designed for lateral forces. Such attach- 
ment shall not be accomplished by use of toenails or nails 
subject to withdrawal. 

2308.12.8 Sill plate anchorage. Sill plates shall be 
anchored with anchor bolts with steel plate washers 
between the foundation sill plate and the nut, or approved 
anchor straps load rated in accordance with Section 1716.1. 
Such washers shall be a minimum of 0.229 inch by 3 inches 
by 3 inches (5.82 mm by 76 mm by 76 mm) in size. The hole 
in the plate washer is permitted to be diagonally slotted with 
a width of up to 3/ 16 inch (4.76 mm) larger than the bolt diam- 
eter and a slot length not to exceed l 3 / 4 inches (44 mm), pro- 
vided a standard cut washer is placed between the plate 
washer and the nut. 

2308.12.9 Sill plate anchorage in Seismic Design Cate- 
gory E. Steel bolts with a minimum nominal diameter of 5/ s 
inch (15.9 mm) or app roved foundation anchor straps load 
rated in accordance with Section 1716.1 and spaced to pro- 
vide equivalent anchorage shall be used in Seismic Design 
C ate gory E. 




OUT OF PLANE 
OFFSET IN EXTERIOR 
BRACED WALL PANELS 



SECTION VIEW 



SECTION VIEW 



FIGURE 2308.12.6(1) 
BRACED WALL PANELS OUT OF PLANE 



516 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 




CANTILEVER/SET BACK 
SHALL ONLY SUPPORT ROOF 
AND WALL WEIGHT 



4'-0" 
w/2x 12 





















4'-0 n 


J 




w/2 x 12 









SECTION THRU CANTILEVER 



SECTION THRU SET BACK 



For 51: 1 foot = 304.8 mm. 



FIGURE 2308.12.6(2) 
BRACED WALL PANELS SUPPORTED BY CANTILEVER OR SET BACK 




DASHED LINE INDICATES BRACED 
WALL LINE BELOW 



THERE IS NO BRACED WALL LINE 
ON THIS EDGE OF THE ROOF 



PLAN VIEW 



FIGURE 2308.12.6(3) 
FLOOR OR ROOF NOT SUPPORTED ON ALL EDGES 



L 


I 








~ 






H 1 



















ROOF OR FLOOR SHALL BE PERMITIED 
TO EXTEND UP TO 6' BEYOND 
THE BRACED WALL LINE 



PLAN VIEW 



NO BRACED WALL PANEL ABOVE 
PERMITIED AT THIS LOCATION 



For 51: 1 foot = 304.8 mm. 



FIGURE 2308.12.6(4) 
ROOF OR FLOOR EXTENSION BEYOND BRACED WALL LINE 



2009 INTERNATIONAL BUILDING CODE® 



517 



WOOD 



[ 



HI 



"T 1 'TnO 1 



REQUIRED BRACED 
WALL PANEL 



MORE THAN 1'-0" 



FV 



_L 



EXTERIOR ELEVATION 

For 51: 1 foot = 304.8 mm. 



EXTERIOR ISOMETRIC 



FIGURE 2308.12.6(5) 
BRACED WALL PANEL EXTENSION OVER OPENING 



^^^ 




\ 










\ \ 


1 ^ 


r 




— , — , — 


















FLOOR JOISTS 
CANNOT BE 
TIED DIRECTLY 
TOGETHER 



SECTION VIEW 



SECTION VIEW 



FIGURE 2308.12.6(6) 
PORTIONS OF FLOOR LEVEL OFFSET VERTICALLY 




BRACED WALL LINES ARE NOT 
PERPENDICULAR 



PLAN VIEW 

FIGURE 2308.12.6(7) 
BRACED WALL LINES NOT PERPENDICULAR 



518 



2009 INTERNATIONAL BUILDING CODE® 



WOOD 



1- 

1 



F- 



MORE THAN b1/2 

IS IRREGULAR 



"K 



MORE THAN b2/2 
IS IRREGULAR 



-I 




=1 



PLAN VIEW 



PLAN VIEW 



FIGURE 2308.12.6(8) 
OPENING LIMITATIONS FOR FLOOR AND ROOF DIAPHRAGMS 



2009 INTERNATIONAL BUILDING CODE® 



519 



520 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 24 

GLASS AND GLAZING 



SECTION 2401 
GENERAL 

2401.1 Scope. The provisions of this chapter shall govern the 
materials, design, construction and quality of glass, light- 
transmitting ceramic and light-transmitting plastic panels for 
exterior and interior use in both vertical and sloped applica- 
tions in buildings and structures. 

2401.2 Glazing replacement. The installation of replacement 
glass shall be as required for new installations. 



SECTION 2402 
DEFINITIONS 

2402.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

DALLE GLASS. A decorative composite glazing material 
made of individual pieces of glass that are embedded in a cast 
matrix of concrete or epoxy. 

DECORATIVE GLASS. A carved, leaded or Dalle glass or 
glazing material whose purpose is decorative or artistic, not 
functional; whose coloring, texture or other design qualities or 
components cannot be removed without destroying the glazing 
material and whose surface, or assembly into which it is incor- 
porated, is divided into segments. 



SECTION 2403 
GENERAL REQUIREMENTS FOR GLASS 

2403.1 Identification. Each pane shall bear the manufacturer's 
ma redesignating the type and thickness of the glass or glazing 
material. The identification shall not be omitted unless 
approvedand an affidavit is furnished by the glazing contractor 
certifying that each light is glazed in accordance with approved 
construction documents that comply with the provisions of this 
chapter. Safety glazing shall be identified in accordance with 
Section 2406.2. 

Each pane of tempered glass, except tempered spandrel 
glass, shall be permanently identified by the manufacturer. The 
identification mark shall be acid etched, sand blasted, ceramic 
fired, laser etched, embossed or of a type that, once applied, 
cannot be removed without being destroyed. 

Tempered spandrel glass shall be provided with a removable 
paper marking by the manufacturer. 

2403.2 Glass supports. Where one or more sides of any pane 
of glass are not firmly supported, or are subjected to unusual 
load conditions, detailed construction documents, detailed 
shop drawings and analysis or test data assuring safe perfor- 
mance for the specific installation shall be prepared by a regis- 
tered design professional. 



2403.3 Framing. To be considered firmly supported, the fram- 
ing members for each individual pane of glass shall be 
designed so the deflection of the edge of the glass perpendicu- 
lar to the glass pane shall not exceed i/ 175 of the glass edge 
length or 3/ 4 inch (19.1 mm), whichever is less, when subjected 
to the larger of the positive or negative load where loads are 
combined as specified in Section 1605. 

2403.4 Interior glazed areas. Where interior glazing is 
installed adjacent to a walking surface, the differential deflec- 
tion of two adjacent unsupported edges shall not be greater than 
the thickness of the panels when a force of 50 pounds per linear 
foot (plf) (730 N/m) is applied horizontally to one panel at any 
point up to 42 inches (1067 mm) above the walking surface. 

2403.5 Louvered windows orjalousies. Float, wired and pat- 
terned glass in louvered windows andjalousies shall be no thin- 
ner than nominal 3/ 16 inch (4.8 mm) and no longer than 48 
inches (1219 mm). Exposed glass edges shall be smooth. 

Wired glass with wire exposed on longitudinal edges shall 
not be used in louvered windows orjalousies. 

Where other glass types are used, the design shall be submit- 
ted to the building official for approval. 



SECTION 2404 

WIND, SNOW, SEISMIC 

AND DEAD LOADS ON GLASS 

2404.1 Vertical glass. Glass sloped 15 degrees (0.26 rad) or 
less from vertical in windows, curtain and window walls, doors 
and other exterior applications shall be designed to resist the 
wind loads in Section 1609 for components and cladding. 
Glass in glazed curtain walls, glazed storefronts and glazed 
partitions shall meet the seismic requirements of ASCE 7, Sec- 
tion 13.5.9. The load resistance of glass under uniform load 
shall be determined in accordance with ASTM E 1300. 

The design of vertical glazing shall be based on the follow- 
ing equation: 



where: 



(Equation 24-1) 



Fgw = Wind load on the glass computed in accordance with 
Section 1609. 

Fga = Short duration load on the glass as determined in accor- 
dance with ASTM E 1300. 

2404.2 Sloped glass. Glass sloped more than 15 degrees (0.26 
rad) from vertical in skylights, sunrooms, sloped roofs and 
other exterior applications shall be designed to resist the most 
critical of the following combinations of loads. 



F g =W -D 

F = W r +D + 0.5S 



(Equation 24-2) 
(Equation 24-3) 



2009 INTERNATIONAL BUILDING CODE® 



521 



GLASS AND GLAZING 



(Equation 24-4) 



F g =0.5W t + D + S 

where: 

D = Glass dead load psf (kN/m 2 ). 

For glass sloped 30 degrees (0.52 rad) or less from hori- 
zontal, 

= 13 tg(ForSI: 0.0245 t g ). 

For glass sloped more than 30 degrees (0.52 rad) from 
horizontal, 

= 13 t g cos 8 (For SI: 0.0245 t g cos 8). 

= Total load, psf (kN/m 2 ) on glass. 

= Snow load, psf (kN/m 2 ) as determined in Section 1608. 

t g = Total glass thickness, inches (mm) of glass panes and 
plies. 

W t = Inward wind force, psf (kN/m 2 ) as calculated in Section 
1609. 

W = Outward wind force, psf (kN/m 2 ) as calculated in Sec- 
tion 1609. 

8 = Angle of slope from horizontal. 

Exception: Unit skylights shall be designed in accordance 
with Section 2405.5. 

The design of sloped glazing shall be based on the following 
equation: 



S 



where: 



(Equation 24-5) 



F g = Total load on the glass determined from the load com- 
binations above. 

Fga = Short duration load resistance of the glass as deter- 
mined according to ASTM E 1300 for Equations 24-2 
and 24-3; or the long duration load resistance of the 
glass as determined according to ASTM E 1300 for 
Equation 24-4. 

2404.3 Wired, patterned and sandblasted glass. 

2404.3.1 Vertical wired glass. Wired glass sloped 15 
degrees (0.26 rad) or less from vertical in windows, curtain 
and window walls, doors and other exterior applications 
shall be designed to resist the wind loads in Section 1609 for 
components and cladding according to the following 
equation: 

F gw < 0.5 F ge (Equation 24-6) 

where: 

F gw = Is the wind load on the glass computed per Section 
1609. 

F ge = Nonfactored load from ASTM E 1300 using a thick- 
ness designation for monolithic glass that is not 
greater than the thickness of wired glass. 

2404.3.2 Sloped wired glass. Wired glass sloped more than 
15 degrees (0.26 rad) from vertical in skylights, sunspaces, 
sloped roofs and other exterior applications shall be 
designed to resist the most critical of the combinations of 
loads from Section 2404.2. 



For Equations 24-2 and 24-3: 

F g < 0.5 F ge (Equation 24-7) 

For Equation 24-4: 

F g < 0.3 F ge (Equation 24-8) 

where: 

F g = Total load on the glass. 

F ge = Nonfactored load from ASTM E 1300. 

2404.3.3 Vertical patterned glass. Patterned glass sloped 
15 degrees (0.26 rad) or less from vertical in windows, cur- 
tain and window walls, doors and other exterior applications 
shall be designed to resist the wind loads in Section 1609 for 
components and cladding according to the following 
equation: 



F gw <1.0F ge 
where: 



(Equation 24-9) 



F gw = Wind load on the glass computed per Section 1609. 

F ge = Nonfactored load from ASTM E 1300. The value for 
patterned glass shall be based on the thinnest part of 
the glass. Interpolation between nonfactored load 
charts in ASTM E 1300 shall be permitted. 

2404.3.4 Sloped patterned glass. Patterned glass sloped 
more than 15 degrees (0.26 rad) from vertical in skylights, 
sunspaces, sloped roofs and other exterior applications shall 
be designed to resist the most critical of the combinations of 
loads from Section 2404.2. 



For Equations 24-2 and 24-3: 



(Equation 24-10) 



(Equation 24-11) 



F g <L0F ge 

For Equation 24-4: 

F g <0.6F ge 

where 

F g = Total load on the glass. 

F ge = Nonfactored load from ASTM E 1300. The value for 
patterned glass shall be based on the thinnest part of 
the glass. Interpolation between the nonfactored load 
charts in ASTM E 1300 shall be permitted. 

2404.3.5 Vertical sandblasted glass. Sandblasted glass 
sloped 15 degrees (0.26 rad) or less from vertical in win- 
dows, curtain and window walls, doors, and other exterior 
applications shall be designed to resist the wind loads in 
Section 1609 for components and cladding according to the 
following equation: 



(Equation 24-12) 



F g < 0.5 F ge 

where: 

F g = Total load on the glass. 

F ge = Nonfactored load from ASTM E 1300. The value for 
sandblasted glass is for moderate levels of sandblast- 
ing. 



522 



2009 INTERNATIONAL BUILDING CODE® 



GLASS AND GLAZING 



2404.4 Other designs. For designs outside the scope of this 
section, an analysis or test data for the specific installation shall 
be prepared by a registered design professional. 



SECTION 2405 
SLOPED GLAZING AND SKYLIGHTS 

2405.1 Scope. This section applies to the installation of glass 
and other transparent, translucent or opaque glazing material 
installed at a slope more than 15 degrees (0.26 rad) from the 
vertical plane, including glazing materials in skylights, roofs 
and sloped walls. 

2405.2 Allowable glazing materials and limitations. Sloped 
glazing shall be any of the following materials, subject to the 
listed limitations. 

1. For monolithic glazing systems, the glazing material of 
the single light or layer shall be laminated glass with a 
minimum 30-mil (0.76 mm) polyvinyl butyral (or equiv- 
alent) interlayer, wired glass, light-transmitting plastic 
materials meeting the requirements of Section 2607, 
heat-strengthened glass or fully tempered glass. 

2. For multiple-layer glazing systems, each light or layer 
shall consist of any of the glazing materials specified in 
Item 1 above. 

Annealed glass is permitted to be used as specified within 
Exceptions 2 and 3 of Section 2405.3. 

For additional requirements for plastic skylights, see Section 
2610. Glass-block construction shall conform to the require- 
ments of Section 2101.2.5. 

2405.3 Screening. Where used in monolithic glazing systems, 
heat- strengthened glass and fully tempered glass shall have 
screens installed below the glazing material. The screens and 
their fastenings shall: (1) be capable of supporting twice the 
weight of the glazing; (2) be firmly and substantially fastened 
to the framing members and (3) be installed within 4 inches 
(102 mm) of the glass. The screens shall be constructed of a 
noncombustible material not thinner than No. 12 B&S gage 
(0.0808 inch) with mesh not larger than 1 inch by 1 inch (25 
mm by 25 mm). In a corrosive atmosphere, structurally equiva- 
lent noncorrosive screen materials shall be used. Heat- 
strengthened glass, fully tempered glass and wired glass, when 
used in multiple-layer glazing systems as the bottom glass 
layer over the walking surface, shall be equipped with screen- 
ing that conforms to the requirements for monolithic glazing 
systems. 

Exception: In monolithic and multiple-layer sloped glazing 
systems, the following applies: 

1. Fully tempered glass installed without protective 
screens where glazed between intervening floors at a 
slope of 30 degrees (0.52 rad) or less from the vertical 
plane shall have the highest point of the glass 10 feet 
(3048 mm) or less above the walking surface. 

2. Screens are not required below any glazing material, 
including annealed glass, where the walking surface 
below the glazing material is permanently protected 
from the risk of falling glass or the area below the 
glazing material is not a walking surface. 



Any glazing material, including annealed glass, is 
permitted to be installed without screens in the sloped 
glazing systems of commercial or detached 
noncombustible greenhouses used exclusively for 
growing plants and not open to the public, provided 
that the height of the greenhouse at the ridge does not 
exceed 30 feet (9144 mm) above grade. 



4. Screens shall not be required within individual dwell- 
ing units in Groups R-2, R-3 and R-4 where fully tem- 
pered glass is used as single glazing or as both panes 
in an insulating glass unit, and the following condi- 
tions are met: 

4.1. Each pane of the glass is 16 square feet (1.5 
m 2 ) or less in area. 

4.2. The highest point of the glass is 12 feet (3658 
mm) or less above any walking surface or 
other accessible area. 

4.3. The glass thickness is 3/ 16 inch (4.8 mm) or 
less. 

5. Screens shall not be required for laminated glass with 
a 15 -mil (0.38 mm) polyvinyl butyral (or equivalent) 
interlayer used within individual dwelling units in 
Groups R-2, R-3 and R-4 within the following limits: 

5.1. Each pane of glass is 16 square feet (1.5 m 2 ) or 
less in area. 

5.2. The highest point of the glass is 12 feet (3658 
mm) or less above a walking surface or other 
accessible area. 

2405.4 Framing. In Type I and II construction, sloped glazing 
and skylight frames shall be constructed of noncombustible 
materials. In structures where acid fumes deleterious to metal 
are incidental to the use of the buildings, approved pres- 
sure-treated wood or other approved noncorrosive materials 
are permitted to be used for sash and frames. Framing support- 
ing sloped glazing and skylights shall be designed to resist the 
tributary roof loads in Chapter 16. Skylights set at an angle of 
less than 45 degrees (0.79 rad) from the horizontal plane shall 
be mounted at least 4 inches (102 mm) above the plane of the 
roof on a curb constructed as required for the frame. Skylights 
shall not be installed in the plane of the roof where the roof 
pitch is less than 45 degrees (0.79 rad) from the horizontal. 

Exception: Installation of a skylight without a curb shall be 
permitted on roofs with a minimum slope of 14 degrees 
(three units vertical in 12 units horizontal) in Group R-3 
occupancies. All unit skylights installed in a roof with a 
pitch flatter than 14 degrees (0.25 rad) shall be mounted at 
least 4 inches (102 mm) above the plane of the roof on a curb 
constructed as required for the frame unless otherwise spec- 
ified in the manufacturer's installation instructions. 

2405.5 Unit skylights. Unit skylights shall be tested and 
labeled as complying with AAMA/WDMA/CSA IOII 
LS.2/A440. The label shall state the name of the manufacturer, 
the approve dldfozYmg agency, the product designation and the 
performance grade rating as specified in AAMA/WDMA/CSA 
101/I.S.2/A440. If the product manufacturer has chosen to 
have the performance grade of the skylight rated separately for 



2009 INTERNATIONAL BUILDING CODE® 



523 



GLASS AND GLAZING 



positive and negative design pressure, then the label shall state 
both performance grade ratings as specified in 
AAMA/WDMA/CSA 101/I.S.2/A440 and the skylight shall 
comply with Section 2405.5.2. If the skylight is not rated sepa- 
rately for positive and negative pressure, then the performance 
grade rating shown on the label shall be the performance grade 
rating determined in accordance with AAMA/WDMA/CSA 
101/I.S.2/A440 for both positive and negative design pressure 
and the skylight shall conform to Section 2405.5.1. 

2405.5.1 Unit skylights rated for the same performance 
grade for both positive and negative design pressure. 
The design of unit skylights shall be based on the following 
equation: 



F g <PG 
where: 



PC 



(Equation 24-13) 



Maximum load on the skylight determined 
from Equations 24-2 through 24-4 in Section 
2404.2. 



Performance grade rating of the skylight. 

2405.5.2 Unit skylights rated for separate performance 
grades for positive and negative design pressure. The 
design of unit skylights rated for performance grade for both 
positive and negative design pressures shall be based on the 
following equations: 



F gi < PCpos 

where: 
PCpos 



(Equation 24-14) 
(Equation 24-15) 



Performance grade rating of the skylight under 
positive design pressure; 

PCty Performance grade rating of the skylight under 
negative design pressure; and 

Fgand Fg^are determined in accordance with the following : 

For W > D, 
where: 

W Outward wind force, psf (kN/m 2 ) as calculated in 

Section 1609. 

D The dead weight of the glazing, psf (kN/m 2 ) as 

determined in Section 2404.2 for glass, or by the 
weight of the plastic, psf (kN/m 2 ) for plastic glaz- 
ing. 



For W 
where: 



Maximum load on the skylight determined from 
Equations 24-3 and 24-4 in Section 2404.2. 

Maximum load on the skylight determined from 
Equation 24-2. 

D, 

Is the outward wind force, psf (kN/m 2 ) as calcu- 
lated in Section 1609. 

The dead weight of the glazing, psf (kN/m 2 ) as 
determined in Section 2404.2 for glass, or by the 
weight of the plastic for plastic glazing. 

Maximum load on the skylight determined from 
Equations 24-2 through 24-4 in Section 2404.2. 

0. 



SECTION 2406 
SAFETY GLAZING 

2406.1 Human impact loads. Individual glazed areas, includ- 
ing glass mirrors, in hazardous locations as defined in Section 
2406.4 shall comply with Sections 2406. 1. 1 through 2406. 1.4. 

2406.1.1 Impact test. Except as provided in Sections 

2406.1.2 through 2406.1.4, all glazing shall pass the impact 
test requirements of Section 2406.2. 

2406.1.2 Plastic glazing. Plastic glazing shall meet the 
weathering requirements of ANSI Z97.1. 

2406.1.3 Glass block. Glass-block walls shall comply with 
Section 2101.2.5. 

2406.1.4 Louvered windows and jalousies. Louvered 
windows andjalousies shall comply with Section 2403.5. 

2406.2 Impact test. Where required by other sections of this 
code, glazing shall be tested in accordance with CPSC 16 CFR 
1201. Glazing shall comply with the test criteria for Category I 
or II as indicated in Table 2406.2(1). 

Exception: Glazing not in doors or enclosures for hot tubs, 
whirlpools, saunas, steam rooms, bathtubs and showers 
shall be permitted to be tested in accordance with ANSI 
Z97.1. Glazing shall comply with the test criteria for Class 
A or B as indicated in Table 2406.2 (2). 

2406.3 Identification of safety glazing. Except as indicated in 
Section 2406.3.1, each pane of safety glazing installed in haz- 



TABLE 2406.2(1) 
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING CPSC 16 CFR 1201 



EXPOSED SURFACE 

AREA OF ONE SIDE 

OF ONE LITE 


GLAZING IN 
STORM OR 

COMBINATION 
DOORS 

(Category class) 


GLAZING IN 

DOORS 

(Category class) 


GLAZED PANELS 
REGULATED BY 

ITEM 7 OF 
SECTION 2406.4 
(Category class) 


GLAZED PANELS 
REGULATED BY 

ITEM 6 OF 
SECTION 2406.4 
(Category class) 


DOORS AND 

ENCLOSURES 

REGULATED BY ITEM 

5 OF SECTION 2406.4 

(Category class) 


SLIDING GLASS 

DOORS PATIO TYPE 

(Category class) 


9 square feet or less 


I 


I 


No requirement 


I 


II 


II 


More than 9 square feet 


II 


II 


II 


II 


II 


II 



For 51: 1 square foot = 0.0929 m 2 . 



524 



2009 INTERNATIONAL BUILDING CODE® 



GLASS AND GLAZING 



TABLE 2406.2(2) 
MINIMUM CATEGORY CLASSIFICATION OF GLAZING USING ANSI Z97.1 



EXPOSED SURFACE AREA OF 
ONE SIDE OF ONE LITE 


GLAZED PANELS REGULATED 

BY ITEM 7 OF SECTION 2406.4 

(Category class) 


GLAZED PANELS REGULATED 

BY ITEM 6 OF SECTION 2406.4 

(Category class) 


DOORS AND ENCLOSURES REGULATED 

BY ITEM 5 OF SECTION 2406.4 3 

(Category class) 


9 square feet or less 


No requirement 


B 


A 


More than 9 square feet 


A 


A 


A 



For SI : 1 square foot = 0.0929 m 2 - 

a. Use is only permitted by the exception to Section 2406.2. 

ardous locations shall be identified by a manufacturer's desig- 
nation specifying who applied the designation, the 
manufacturer or installer and the safety glazing standard with 
which it complies, as well as the information specified in Sec- 
tion 2403. 1 . The designation shall be acid etched, sand blasted, 
ceramic fired, laser etched, embossed or of a type that once 
applied, cannot be removed without being destroyed. A label as 
defined in Section 202.1 and meeting the requirements of this 
section shall be permitted in lieu of the manufacturer's designa- 
tion. 

Exceptions: 

1. For other than tempered glass, manufacturer's designa- 
tions are not required, provided the building official 
approves the use of a certificate, affidavit or other evi- 
dence confirming compliance with this code. 

2. Tempered spandrel glass is permitted to be identified by 
the manufacturer with a removable paper designation 

2406.3.1 Multi-pane assemblies. Multi-pane glazed 
assemblies having individual panes not exceeding 1 square 
foot (0.09 m 2 ) in exposed areas shall have at least one pane 
in the assembly marked as indicated in Section 2406.3. 
Other panes in the assembly shall be marked "CPSC 16 
CFR 1201" or "ANSI Z97.1," as appropriate. 

2406.4 Hazardous locations. The following shall be consid- 
ered specific hazardous locations requiring safety glazing 
materials: 

1. Glazing in swinging doors except jalousies (see Sec- 
tion 2406.4.1). 

2. Glazing in fixed and sliding panels of sliding door 
assemblies and panels in sliding and bifold closet door 
assemblies. 

3. Glazing in storm doors. 

4. Glazing in unframed swinging doors. 

5. Glazing in doors and enclosures for hot tubs, whirl- 
pools, saunas, steam rooms, bathtubs and showers. 
Glazing in any portion of a building wall enclosing 
these compartments where the bottom exposed edge of 
the glazing is less than 60 inches (1524 mm) above a 
standing surface. 

6. Glazing in an individual fixed or operable panel adja- 
cent to a door where the nearest exposed edge of the 
glazing is within a 24- inch (610 mm) arc of either verti- 
cal edge of the door in a closed position and where the 
bottom exposed edge of the glazing is less than 60 
inches (1524 mm) above the walking surface. 



Exceptions: 

1. Panels where there is an intervening wall or 
other permanent barrier between the door and 
glazing. 

2. Where access through the door is to a closet or 
storage area 3 feet (914 mm) or less in depth. 
Glazing in this application shall comply with 
Section 2406.4, Item 7. 

3. Glazing in walls perpendicular to the plane of 
the door in a closed position, other than the 
wall towards which the door swings when 
opened, in one- and two-family dwellings or 
within dwelling units in Group R-2. 

7. Glazing in an individual fixed or operable panel, other 
than in those locations described in preceding Items 5 
and 6, which meets all of the following conditions: 

7.1. Exposed area of an individual pane greater than 9 
square feet (0.84 m 2 ); 

7.2. Exposed bottom edge less than 18 inches (457 
mm) above the floor; 

7.3. Exposed top edge greater than 36 inches (914 
mm) above the floor; and 

7.4. One or more walking surface(s) within 36 inches 
(914 mm) horizontally of the plane of the glaz- 
ing. 

Exception: Safety glazing for Item 7 is not 
required for the following installations: 

1. A protective bar lV 2 inches (38 mm) or 
more in height, capable of withstanding a 
horizontal load of 50 pounds plf (730 
N/m) without contacting the glass, is 
installed on the accessible sides of the 
glazing 34 inches to 38 inches (864 mm 
to 965 mm) above the floor. 

2. The outboard pane in insulating glass 
units or multiple glazing where the bot- 
tom exposed edge of the glass is 25 feet 
(7620 mm) or more above any grade, 
roof, walking surface or other horizontal 
or sloped (within 45 degrees of horizon- 
tal) (0.78 rad) surface adjacent to the 
glass exterior. 

8. Glazing in guards and railings, including structural 
baluster panels and nonstructural in-fill panels, regard- 
less of area or height above a walking surface. 



2009 INTERNATIONAL BUILDING CODE® 



525 



GLASS AND GLAZING 



9. Glazing in walls and fences enclosing indoor and out- 
door swimming pools, hot tubs and spas where all of 
the following conditions are present: 

9.1. The bottom edge of the glazing on the pool or spa 
side is less than 60 inches (1524 mm) above a 
walking surface on the pool or spa side of the 
glazing; and 

9.2. The glazing is within 60 inches (1524 mm) hori- 
zontally of the water's edge of a swimming pool 
or spa. 

10. Glazing adjacent to stairways, landings and ramps 
within 36 inches (914 mm) horizontally of a walking 
surface; when the exposed surface of the glass is less 
than 60 inches (1524 mm) above the plane of the adja- 
cent walking surface. 

11. Glazing adjacent to stairways within 60 inches (1524 
mm) horizontally of the bottom tread of a stairway in 
any direction when the exposed surface of the glass is 
less than 60 inches (1524 mm) above the nose of the 
tread. 

Exception: Safety glazing for Item 10 or 11 is not 
required for the following installations where: 

1. The side of a stairway, landing or ramp which 
has a guard or handrail, including balusters or 
in-fill panels, complying with the provisions of 
Sections 1013 and 1607.7; and 

2. The plane of the glass is greater than 18 inches 
(457 mm) from the railing. 

2406.4.1 Exceptions. The following products, materials 
and uses shall not be considered specific hazardous loca- 
tions: 

1. Openings in doors through which a 3 -inch (76 mm) 
sphere is unable to pass. 

2. Decorative glass in Section 2406.4, Item 1,6 or 7. 

3. Glazing materials used as curved glazed panels in 
revolving doors. 

4. Commercial refrigerated cabinet glazed doors. 

5. Glass-block panels complying with Section 2101.2.5. 

6. Louvered windows and jalousies complying with the 
requirements of Section 2403.5. 

7. Mirrors and other glass panels mounted or hung on a 
surface that provides a continuous backing support. 

2406.5 Fire department access panels. Fire department glass 
access panels shall be of tempered glass. For insulating glass 
units, all panes shall be tempered glass. 



SECTION 2407 
GLASS IN HANDRAILS AND GUARDS 

2407.1 Materials. Glass used as a handrail assembly or a 
guard section shall be constructed of either single fully tem- 
pered glass, laminated fully tempered glass or laminated heat- 
strengthened glass. Glazing in railing in-fill panels shall be of 
an approvedsafety glazing material that conforms to the provi- 



sions of Section 2406.1.1. For all glazing types, the minimum 
nominal thickness shall be i/ 4 inch (6.4 mm). Fully tempered 
glass and laminated glass shall comply with Category II of 
CPSC 16 CFR 1201 or Class A of ANSI Z97.1, listed in Chap- 
ter 35. 

2407.1.1 Loads. The panels and their support system shall 
be designed to withstand the loads specified in Section 
1607.7. A safety factor of four shall be used. 

2407.1.2 Support. Each handrail or guard section shall be 
supported by a minimum of three glass balusters or shall be 
otherwise supported to remain in place should one baluster 
panel fail. Glass balusters shall not be installed without an 
attached handrail or guard. 

Exception: A top rail shall not be required where the 
glass balusters are laminated glass with two or more 
glass plies of equal thickness and the same glass type 
when approvedby the building official. The panels shall 
be designed to withstand the loads specified in Section 
1607.7. 

2407.1.3 Parking garages. Glazing materials shall not be 
installed in handrails or guards in parking garages except 
for pedestrian areas not exposed to impact from vehicles. 

2407.1.4 Glazing in wind-borne debris regions. Glazing 
installed in in-fill panels or balusters in wind-borne debris 
regions shall comply with the following: 

2407.1.4.1 Ballusters and in-fill panels. Glass installed 
in exterior railing in-fill panels or balusters shall be lami- 
nated glass complying with Category II of CPSC 16 CFR 
1201 or Class A of ANSI Z97.1. 

2407.1.4.2 Glass supporting top rail. When the top rail 
is supported by glass, the assembly shall be tested 
according to the impact requirements of Section 
1609.1.2. The top rail shall remain in place after impact. 



SECTION 2408 
GLAZING IN ATHLETIC FACILITIES 

2408.1 General. Glazing in athletic facilities and similar uses 
subject to impact loads, which forms whole or partial wall sec- 
tions or which is used as a door or part of a door, shall comply 
with this section. 

2408.2 Racquetball and squash courts. 

2408.2.1 Testing. Test methods and loads for individual 
glazed areas in racquetball and squash courts subject to 
impact loads shall conform to those of CPSC 16 CFR or 
ANSI Z97.1, listed in Chapter 35, with impacts being 
applied at a height of 59 inches (1499 mm) above the play- 
ing surface to an actual or simulated glass wall installation 
with fixtures, fittings and methods of assembly identical to 
those used in practice. 

Glass walls shall comply with the following conditions: 

1. A glass wall in a racquetball or squash court, or simi- 
lar use subject to impact loads, shall remain intact fol- 
lowing a test impact. 



526 



2009 INTERNATIONAL BUILDING CODE® 



GLASS AND GLAZING 



2. The deflection of such walls shall not be greater than 
P/ 2 inches (38 mm) at the point of impact for a drop 
height of 48 inches (1219 mm). 

Glass doors shall comply with the following conditions: 

1. Glass doors shall remain intact following a test impact 
at the prescribed height in the center of the door. 

2. The relative deflection between the edge of a glass 
door and the adjacent wall shall not exceed the thick- 
ness of the wall plus i/ 2 inch (12.7 mm) for a drop 
height of 48 inches (1219 mm). 

2408.3 Gymnasiums and basketball courts. Glazing in mul- 
tipurpose gymnasiums, basketball courts and similar athletic 
facilities subject to human impact loads shall comply with Cat- 
egory II of CPSC 16 CFR 1201 or Class A of ANSI Z97.1, 
listed in Chapter 35. 



SECTION 2409 

GLASS IN ELEVATOR HOISTWAYS 

AND ELEVATOR CARS 

2409.1 Glass in elevator hoistway enclosures. Glass in eleva- 
tor hoistway enclosures and hoistway doors shall be laminated 
glass conforming to ANSI Z97.1 or CPSC 16CFRPart 1201. 

2409.1.1 Fire-resistance-rated hoistways. Glass installed 
in hoistways and hoistway doors where the hoistway is 
required to have a fire-resistance rating shall also comply 
with Section 715. 

2409.1.2 Glass hoistway doors. The glass in glass 
hoistway doors shall be not less than 60 percent of the total 
visible door panel surface area as seen from the landing side. 

2409.2 Glass visions panels. Glass in vision panels in elevator 
hoistway doors shall be permitted to be any transparent glazing 
material not less than i/ 4 inches (0.64 mm) in thickness con- 
forming to Class A in accordance with ANSI Z97.1 or Cate- 
gory II in accordance with CPSC 16 CFR Part 1201. The area 
of any single vision panel shall not be less than 24 square 
inches (15 484 mm 2 ) and the total area of one or more vision 
panels in any hoistway door shall be not more than 85 square 
inches (54 839 mm 2 ). 



2409.3 Glass in elevator cars. 

2409.3.1 Glass types. Glass in elevator car enclosures, 
glass elevator car doors and glass used for lining walls and 
ceilings of elevator cars shall be laminated glass conforming 
to Class A in accordance with ANSI Z97.1 or Category II in 
accordance with CPSC 16 CFR Part 1201. 

Exception: Tempered glass shall be permitted to be used 
for lining walls and ceilings of elevator cars provided: 

1. The glass is bonded to a nonpolymeric coating, 
sheeting or film backing having a physical integ- 
rity to hold the fragments when the glass breaks. 

2. The glass is not subjected to further treatment such 
as sandblasting; etching; heat treatment or painting 
that could alter the original properties of the glass. 

3. The glass is tested to the acceptance criteria for 
laminated glass as specified for Class A in accor- 
dance with ANSI Z97.1 or Category II in accor- 
dance with CPSC 16 CFR Part 1201. 

2409.3.2 Surface area. The glass in glass elevator car doors 
shall be not less than 60 percent of the total visible door 
panel surface area as seen from the car side of the doors. 



2009 INTERNATIONAL BUILDING CODE® 



527 



528 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 25 

GYPSUM BOARD AND PLASTER 



SECTION 2501 
GENERAL 



2501.1 Scope. 



2501.1.1 General. Provisions of this chapter shall govern 
the materials, design, construction and quality of gypsum 
board, lath, gypsum plaster and cement plaster. 

2501.1.2 Performance. Lathing, plastering and gypsum 
board construction shall be done in the manner and with the 
materials specified in this chapter, and when required for 
fire protection, shall also comply with the provisions of 
Chapter 7. 

2501.1.3 Other materials. Other approvedwall or ceiling 
coverings shall be permitted to be installed in accordance 
with the recommendations of the manufacturer and the con- 
ditions of approval. 



SECTION 2502 
DEFINITIONS 

2502.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

CEMENT PLASTER. A mixture of portland or blended 
cement, portland cement or blended cement and hydrated lime, 
masonry cement or plastic cement and aggregate and other 
app roved materials as specified in this code. 

EXTERIOR SURFACES. Weather-exposed surfaces. 

GYPSUM BOARD. Gypsum wallboard, gypsum sheathing, 
gypsum base for gypsum veneer plaster, exterior gypsum soffit 
board, predecorated gypsum board or water-resistant gypsum 
backing board complying with the standards listed in Tables 
2506.2, 2507.2 and Chapter 35. 

GYPSUM PLASTER. A mixture of calcined gypsum or cal- 
cined gypsum and lime and aggregate and other approved 
materials as specified in this code. 

GYPSUM VENEER PLASTER. Gypsum plaster applied to 
an approvedbase in one or more coats normally not exceeding 



i/ 4 inch (6.4 mm) in total thickness. 

INTERIOR SURFACES. Surfaces other than weather- 
exposed surfaces. 

WEATHER-EXPOSED SURFACES. Surfaces of walls, 
ceilings, floors, roofs, soffits and similar surfaces exposed to 
the weather except the following: 

1. Ceilings and roof soffits enclosed by walls, fascia, bulk- 
heads or beams that extend a minimum of 12 inches (305 
mm) below such ceiling or roof soffits. 

2. Walls or portions of walls beneath an unenclosed roof 
area, where located a horizontal distance from an open 



exterior opening equal to at least twice the height of the 
opening. 

3. Ceiling and roof soffits located a minimum horizontal 
distance of 10 feet (3048 mm) from the outer edges of the 
ceiling or roof soffits. 

WIRE BACKING. Horizontal strands of tautened wire 
attached to surfaces of vertical supports which, when covered 
with the building paper, provide a backing for cement plaster. 



SECTION 2503 
INSPECTION 

2503.1 Inspection. Lath and gypsum board shall be inspected 
in accordance with Section 109.3.5. 



SECTION 2504 
VERTICAL AND HORIZONTAL ASSEMBLIES 

2504.1 Scope. The following requirements shall be met where 
construction involves gypsum board, lath and plaster in vertical 
and horizontal assemblies. 

2504.1.1 Wood framing. Wood supports for lath or gypsum 
board, as well as wood stripping or furring, shall not be less 
than 2 inches (51 mm) nominal thickness in the least dimen- 
sion. 

Exception: The minimum nominal dimension of wood 
furring strips installed over solid backing shall not be less 
than 1 inch by 2 inches (25 mm by 51 mm). 

2504.1.2 Studless partitions. The minimum thickness of 
vertically erected studless solid plaster partitions of 3/ s -inch 
(9.5 mm) and 3/4-inch (19.1 mm) rib metal lath or 
1/z-inch-thick (12.7 mm) long-length gypsum lath and gyp- 
sum board partitions shall be 2 inches (51 mm). 



SECTION 2505 
SHEAR WALL CONSTRUCTION 

2505.1 Resistance to shear (wood framing). Wood-framed 
shear walls sheathed with gypsum board, lath and plaster shall 
be designed and constructed in accordance with Section 
2306.7 and are permitted to resist wind and seismic loads. 
Walls resisting seismic loads shall be subject to the limitations 
in Section 12.2.1 of ASCE 7. 

2505.2 Resistance to shear (steel framing). Cold-formed 
steel-framed shear walls sheathed with gypsum board and con- 
structed in accordance with the materials and provisions of 
Section 2210.6 are permitted to resist wind and seismic loads. 
Walls resisting seismic loads shall be subject to the limitations 
in Section 12.2.1 of ASCE 7. 



2009 INTERNATIONAL BUILDING CODE® 



529 



GYPSUM BOARD AND PLASTER 



SECTION 2506 
GYPSUM BOARD MATERIALS 

2506.1 General. Gypsum board materials and accessories 
shall be identified by the manufacturer's designation to indi- 
cate compliance with the appropriate standards referenced in 
this section and stored to protect such materials from the 
weather. 

2506.2 Standards. Gypsum board materials shall conform to 
the appropriate standards listed in Table 2506.2 and Chapter 35 
and, where required for fire protection, shall conform to the 
provisions of Chapter 7. 

TABLE 2506.2 
GYPSUM BOARD MATERIALS AND ACCESSORIES 



MATERIAL 


STANDARD 


Accessories for gypsum board 


ASTM C 1047 


Adhesives for fastening gypsum 
wallboard 


ASTM C 557 


Elastomeric joint sealants 


ASTM C 920 


Exterior soffit board 


ASTM C 931 


Fiber-reinforced gypsum panels 


ASTM C 1278 


Glass mat gypsum backing panel 


ASTMC 1178 


Glass mat gypsum panel 


ASTM C 1658 


Glass mat gypsum substrate 


ASTMC 1177 


Gypsum backing board and gypsum 
shaftliner board 


ASTM C 442 


Gypsum ceiling board 


ASTM C 1395 


Gypsum sheathing 


ASTM C 79 


Gypsum wallboard 


ASTM C 36 


] oint reinforcing tape and compound 


ASTM C 474; C 475 


Nails for gypsum boards 


ASTMC 514, 
F 547, F 1667 


Predecorated gypsum board 


ASTM C 960 


Steel screws 


ASTM C 954; C 1002 


Steel studs, load-bearing 


ASTM C 955 


Steel studs, nonload-bearing 


ASTM C 645 


Standard specification for gypsum board 


ASTM C 1396 


Testing gypsum and gypsum products 


ASTM C 22; C 472; 
C473 


Water-resistant gypsum backing board 


ASTM C 630 



2506.2.1 Other materials. Metal suspension systems for 
acoustical and lay-in panel ceilings shall conform with 
ASTM C 635 listed in Chapter 35 and Section 13.5.6 of 
ASCE 7 for installation in high seismic areas. 



SECTION 2507 
LATHING AND PLASTERING 

2507.1 General. Lathing and plastering materials and accesso- 
ries shall be marked by the manufacturer's designation to indi- 
cate compliance with the appropriate standards referenced in 



this section and stored in such a manner to protect them from 
the weather. 

2507.2 Standards. Lathing and plastering materials shall con- 
form to the standards listed in Table 2507.2 and Chapter 35 
and, where required for fire protection, shall also conform to 
the provisions of Chapter 7. 

TABLE 2507.2 
LATH, PLASTERING MATERIALS AND ACCESSORIES 



MATERIAL 


STANDARD 


Accessories for gypsum veneer base 


ASTM C 1047 


Blended cement 


ASTM C 595 


Exterior plaster bonding compounds 


ASTM C 932 


Gypsum base for veneer plasters 


ASTM C 588 


Gypsum casting and molding plaster 


ASTM C 59 


Gypsum Keene's cement 


ASTM C 61 


Gypsum lath 


ASTM C 37 


Gypsum plaster 


ASTM C 28 


Gypsum veneer plaster 


ASTM C 587 


Interior bonding compounds, gypsum 


ASTM C 631 


Lime plasters 


ASTM C 5; C 206 


Masonry cement 


ASTM C 91 


Metal lath 


ASTM C 847 


Plaster aggregates 
Sand 
Perlite 
Vermiculite 


ASTM C 35; C 897 
ASTM C 35 
ASTM C 35 


Plastic cement 


ASTM C 1328 


Portland cement 


ASTM C 150 


Steel screws 


ASTM C 1002; C 954 


Steel studs and track 


ASTM C 645; C 955 


Welded wire lath 


ASTM C 933 


Woven wire plaster base 


ASTM C 1032 



SECTION 2508 
GYPSUM CONSTRUCTION 

2508.1 General. Gypsum board and gypsum plaster construc- 
tion shall be of the materials listed in Tables 2506.2 and 2507.2. 
These materials shall be assembled and installed in compliance 
with the appropriate standards listed in Tables 2508.1 and 
2511.1.1, and Chapter 35. 

TABLE 2508.1 
INSTALLATION OF GYPSUM CONSTRUCTION 



MATERIAL 


STANDARD 


Gypsum board 


GA-216; ASTM C 840 


Gypsum sheathing 


ASTM C 1280 


Gypsum veneer base 


ASTM C 844 


Interior lathing and furring 


ASTM C 841 


Steel framing for gypsum boards 


ASTM C 754; C 1007 



530 



2009 INTERNATIONAL BUILDING CODE® 



GYPSUM BOARD AND PLASTER 



2508.2 Limitations. Gypsum wallboard or gypsum plaster 
shall not be used in any exterior surface where such gypsum 
construction will be exposed directly to the weather. Gypsum 
wallboard shall not be used where there will be direct exposure 
to water or continuous high humidity conditions. Gypsum 
sheathing shall be installed on exterior surfaces in accordance 
withASTMC 1280. 

2508.2.1 Weather protection. Gypsum wallboard, gypsum 
lath or gypsum plaster shall not be installed until weather 
protection for the installation is provided. 

2508.3 Single-ply application. Edges and ends of gypsum 
board shall occur on the framing members, except those edges 
and ends that are perpendicular to the framing members. Edges 
and ends of gypsum board shall be in moderate contact except 
in concealed spaces where fire-resistance-rated construction, 
shear resistance or diaphragm action is not required. 

2508.3.1 Floating angles. Fasteners at the top and bottom 
plates of vertical assemblies, or the edges and ends of hori- 
zontal assemblies perpendicular to supports, and at the wall 
line are permitted to be omitted except on shear resisting 
elements or fire-resistance-rated assemblies. Fasteners shall 
be applied in such a manner as not to fracture the face paper 
with the fastener head. 

2508.4 Joint treatment. Gypsum board fire-resistance-rated 
assemblies shall have joints and fasteners treated. 

Exception: Joint and fastener treatment need not be pro- 
vided where any of the following conditions occur: 

1. Where the gypsum board is to receive a decorative 
finish such as wood paneling, battens, acoustical fin- 
ishes or any similar application that would be equiva- 
lent to j oint treatment. 

2. On single-layer systems where joints occur over 
wood framing members . 

3. Square edge or tongue-and-groove edge gypsum 
board (V-edge), gypsum backing board or gypsum 
sheathing. 

4. On multilayer systems where the joints of adjacent 
layers are offset from one to another. 

5. Assemblies tested without joint treatment. 



2508.5 Horizontal gypsum board diaphragm ceilings. Gyp- 
sum board shall be permitted to be used on woodjoists to create 
a horizontal diaphragm ceiling in accordance with Table 
2508.5. 

2508.5.1 Diaphragm proportions. The maximum allow- 
able diaphragm proportions shall be 1 1 / 2 :1 between shear 
resisting elements. Rotation or cantilever conditions shall 
not be permitted. 

2508.5.2 Installation. Gypsum board used in a horizontal 
diaphragm ceiling shall be installed perpendicular to ceiling 
framing members. Endjoints of adjacent courses of gypsum 
board shall not occur on the samejoist. 

2508.5.3 Blocking of perimeter edges. All perimeter edges 
shall be blocked using a wood member not less than 2-inch 
by 6-inch (51 mm by 159 mm) nominal dimension. Block- 
ing material shall be installed flat over the top plate of the 
wall to provide a nailing surface not less than 2 inches (51 
mm) in width for the attachment of the gypsum board. 

2508.5.4 Fasteners. Fasteners used for the attachment of 
gypsum board to a horizontal diaphragm ceiling shall be as 
defined in Table 2508.5. Fasteners shall be spaced not more 
than 7 inches (178 mm) on center (o.c.) at all supports, 
including perimeter blocking, and not more than 3/s inch 
(9.5 mm) from the edges and ends of the gypsum board. 

2508.5.5 Lateral force restrictions. Gypsum board shall 
not be used in diaphragm ceilings to resist lateral forces 
imposed by masonry or concrete construction. 



SECTION 2509 

GYPSUM BOARD IN SHOWERS 

AND WATER CLOSETS 

2509.1 Wet areas. Showers and public toilet walls shall con- 
form to Sections 1210.2 and 1210.3. 

2509.2 Base for tile. Glass mat water-resistant gypsum back- 
ing panels, discrete nonasbestos fiber-cement interior substrate 
sheets or nonasbestos fiber-mat reinforced cement substrate 
sheets in compliance with ASTM C 1178, C 1288 or C 1325 
and installed in accordance with manufacturer recommenda- 
tions shall be used as a base for wall tile in tub and shower areas 



TABLE 2508.5 
SHEAR CAPACITY FOR HORIZONTAL WOOD FRAMED GYPSUM BOARD DIAPHRAGM CEILING ASSEMBLIES 



MATERIAL 


THICKNESS OF MATERIAL 
(MINIMUM) (inches) 


SPACING OF FRAMING MEMBERS 
(MAXIMUM) (inches) 


SHEAR VALUE a ,b 
(plf of ceiling) 


MIMIMUM FASTENER SIZE 


Gypsum board 


l/ 2 


16 o.c. 


90 


5d cooler or wallboard nail; 

ISis-inch long; 0.086-inch shank; 

15 / M -inch head c 


Gypsum board 


U 2 


24 o.c. 


70 


5d cooler or wallboard nail; 

ISis-inch long; 0.086-inch shank; 

15 / M -inch head c 



For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.59 N/m. 

a. Values are not cumulative with other horizontal diaphragm values and are for short-term loading due to wind or seismic loading. Values shall be reduced 25 percent 



for normal loading. 

b. Values shall be reduced 50 percent in Seismic Design Categories D, E and F. 

c. I 1 / 4-inch, No. 6 Type S or W screws are permitted to be substituted for the listed nails. 



2009 INTERNATIONAL BUILDING CODE® 



531 



GYPSUM BOARD AND PLASTER 



and wall and ceiling panels in shower areas. Water-resistant 
gypsum backing board shall be used as a base for tile in water 
closet compartment walls when installed in accordance with 
GA-216 or ASTM C 840 and manufacturer recommendations. 
Regular gypsum wallboard is permitted under tile or wall pan- 
els in other wall and ceiling areas when installed in accordance 
with GA-216 or ASTM C 840. 

2509.3 Limitations. Water-resistant gypsum backing board 
shall not be used in the following locations: 

1. Over a vapor retarder in shower or bathtub compart- 
ments. 

2. Where there will be direct exposure to water or in areas 
subject to continuous high humidity. 

3. On ceilings where frame spacing exceeds 12 inches (305 
mm) o.c. for l/ r inch-thick (12.7 mm) water-resistant 
gypsum backing board and more than 16 inches (406 
mm) o.c. for 5/ s -inch-thick (15.9 mm) water-resistant 
gypsum backing board. 



SECTION 2510 
LATHING AND FURRING FOR 
CEMENT PLASTER (STUCCO) 

2510.1 General. Exterior and interior cement plaster and lath- 
ing shall be done with the appropriate materials listed in Table 

2507.2 and Chapter 35. 

2510.2 Weather protection. Materials shall be stored in such a 
manner as to protect such materials from the weather. 

2510.3 Installation. Installation of these materials shall be in 
compliance with ASTM C 926 and ASTM C 1063. 

2510.4 Corrosion resistance. Metal lath and lath attachments 
shall be of corrosion-resistant material. 

2510.5 Backing. Backing or a lath shall provide sufficient 
rigidity to permit plaster applications. 

2510.5.1 Support of lath. Where lath on vertical surfaces 
extends between rafters or other similar projecting mem- 
bers, solid backing shall be installed to provide support for 
lath and attachments. 

2510.5.2 Use of gypsum backing board. 

2510.5.2.1 Use of gypsum board as a backing board. 

Gypsum lath or gypsum wallboard shall not be used as a 
backing for cement plaster. 

Exception: Gypsum lath or gypsum wallboard is per- 
mitted, with a water-resistive barrier, as a backing for 
self-furred metal lath or self-furred wire fabric lath 
and cement plaster where either of the following con- 
ditions occur: 

1. On horizontal supports of ceilings or roof sof- 
fits. 

2. On interior walls. 

2510.5.2.2 Use of gypsum sheathing backing. Gypsum 
sheathing is permitted as a backing for metal or wire fab- 
ric lath and cement plaster on walls. A water-resistive 



barrier shall be provided in accordance with Section 
2510.6. 

2510.5.3 Backing not required. Wire backing is not 
required under expanded metal lath or paperbacked wire 
fabric lath. 

2510.6 Water-resistive barriers. Water-resistive barriers 
shall be installed as required in Section 1404.2 and, where 
applied over wood-based sheathing, shall include a 
water-resistive vapor-permeable barrier with a performance at 
least equivalent to two layers of Grade D paper. 

Exception: Where the water-resistive barrier that is 
applied over wood-based sheathing has a water resistance 
equal to or greater than that of 60-minute Grade D paper and 
is separated from the stucco by an intervening, substantially 
nonwater-absorbing layer or drainage space. 

2510.7 Preparation of masonry and concrete. Surfaces shall 
be clean, free from efflorescence, sufficiently damp and rough 
for proper bond. If the surface is insufficiently rough, approved 
bonding agents or a portland cement dash bond coat mixed in 
proportions of not more than two parts volume of sand to one 
part volume of portland cement or plastic cement shall be 
applied. The dash bond coat shall be left undisturbed and shall 
be moist cured not less than 24 hours. 



SECTION 2511 
INTERIOR PLASTER 

2511.1 General. Plastering gypsum plaster or cement plaster 
shall not be less than three coats where applied over metal lath 
or wire fabric lath and not less than two coats where applied 
over other bases permitted by this chapter. 

Exception: Gypsum veneer plaster and cement plaster spe- 
cifically designed and approved for one-coat applications. 

2511.1.1 Installation. Installation of lathing and plaster 
materials shall conform with Table 2511.1.1 and Section 

2507. 

TABLE 2511.1.1 
INSTALLATION OF PLASTER CONSTRUCTION 



MATERIAL 


STANDARD 


Cement plaster 


ASTM C 926 


Gypsum plaster 


ASTM C 842 


Gypsum veneer plaster 


ASTM C 843 


Interior lathing and furring 
(gypsum plaster) 


ASTM C 841 


Lathing and furring (cement plaster) 


ASTM C 1063 


Steel framing 


ASTM C 754; C 1007 



2511.2 Limitations. Plaster shall not be applied directly to 
fiber insulation board. Cement plaster shall not be applied 
directly to gypsum lath or gypsum plaster except as specified in 
Sections 2510.5.1 and 2510.5.2. 

2511.3 Grounds. Where installed, grounds shall ensure the 
minimum thickness of plaster as set forth in ASTM C 842 and 
ASTM C 926. Plaster thickness shall be measured from the 
face of lath and other bases. 



532 



2009 INTERNATIONAL BUILDING CODE® 



GYPSUM BOARD AND PLASTER 



2511.4 Interior masonry or concrete. Condition of surfaces 
shall be as specified in Section 2510.7. Approv edspeciaWy pre- 
pared gypsum plaster designed for application to concrete sur- 
faces or approved acoustical plaster is permitted. The total 
thickness of base coat plaster applied to concrete ceilings shall 
be as set forth in ASTM C 842 or ASTM C 926. Should ceiling 
surfaces require more than the maximum thickness permitted 
in ASTM C 842 or ASTM C 926, metal lath or wire fabric lath 
shall be installed on such surfaces before plastering. 

2511.5 Wet areas. Showers and public toilet walls shall con- 
form to Sections 1210.2 and 1210.3. When wood frame walls 
and partitions are covered on the interior with cement plaster or 
tile of similar material and are subject to water splash, the fram- 
ing shall be protected with an approve d moisture barrier. 



SECTION 2512 
EXTERIOR PLASTER 

2512.1 General. Plastering with cement plaster shall be not 
less than three coats when applied over metal lath or wire fabric 
lath or gypsum board backing as specified in Section 2510.5 
and shall be not less than two coats when applied over masonry 
or concrete . If the plaster surface is to be completely covered by 
veneer or other facing material, or is completely concealed by 
another wall, plaster application need only be two coats, pro- 
vided the total thickness is as set forth in ASTM C 926. 

2512.1.1 On-grade floor slab. On wood framed or steel 
stud construction with an on-grade concrete floor slab sys- 
tem, exterior plaster shall be applied in such a manner as to 
cover, but not to extend below, the lath and paper. The appli- 
cation of lath, paper and flashing or drip screeds shall com- 
ply with ASTM C 1063. 

2512.1.2 Weep screeds. A minimum 0.019-inch (0.48 mm) 
(No. 26 galvanized sheet gage), corrosion-resistant weep 
screed with a minimum vertical attachment flange of 3 ! / 2 
inches (89 mm) shall be provided at or below the foundation 
plate line on exterior stud walls in accordance with ASTM C 
926. The weep screed shall be placed a minimum of 4 inches 
(102 mm) above the earth or 2 inches (51 mm) above paved 
areas and be of a type that will allow trapped water to drain 
to the exterior of the building. The water-resistive barrier 
shall lap the attachment flange. The exterior lath shall cover 
and terminate on the attachment flange of the weep screed. 

2512.2 Plasticity agents. Only approvedplasticity agents and 
approve d amounts thereof shall be added to portland cement or 
blended cements. When plastic cement or masonry cement is 
used, no additional lime or plasticizers shall be added. 
Hydrated lime or the equivalent amount of lime putty used as a 
plasticizer is permitted to be added to cement plaster or cement 
and lime plaster in an amount not to exceed that set forth in 
ASTM C 926. 

2512.3 Limitations. Gypsum plaster shall not be used on exte- 
rior surfaces. 

2512.4 Cement plaster. Plaster coats shall be protected from 
freezing for a period of not less than 24 hours after set has 
occurred. Plaster shall be applied when the ambient tempera- 
ture is higher than 40°F (4°C), unless provisions are made to 



keep cement plaster work above 40°F (4°C) during application 
and 48 hours thereafter. 

2512.5 Second-coat application. The second coat shall be 
brought out to proper thickness, rodded and floated sufficiently 
rough to provide adequate bond for the finish coat. The second 
coat shall have no variation greater than i/ 4 inch (6.4 mm) in any 
direction under a 5 -foot (1524 mm) straight edge. 

2512.6 Curing and interval. First and second coats of cement 
plaster shall be applied and moist cured as set forth in ASTM C 
926 and Table 2512.6. 

TABLE 2512.6 
CEMENT PLASTERS a 



COAT 


MINIMUM PERIOD MOIST 
CURING 


MINIMUM INTERVAL 
BETWEEN COATS 


First 


48 hours a 


48 hours b 


Second 


48 hours 


7 daysc 


Finish 




Note c 



a. The first two coats shall be as required for the first coats of exterior plaster, 
except that the moist-curing time period between the first and second coats 
shall not be less than 24 hours. Moist curing shall not be required where job 
and weather conditions are favorable to the retention of moisture in the 
cement plaster for the required time period. 

b. Twenty-four-hour minimum interval between coats of interior cement plas- 
ter. For alternate method of application, see Section 2512.8. 

c. Finish coat plaster is permitted to be applied to interior cement plaster base 
coats after a 48-hour period. 

2512.7 Application to solid backings. Where applied over 
gypsum backing as specified in Section 2510.5 or directly to 
unit masonry surfaces, the second coat is permitted to be 
applied as soon as the first coat has attained sufficient hardness. 

2512.8 Alternate method of application. The second coat is 
permitted to be applied as soon as the first coat has attained suf- 
ficiently rigidity to receive the second coat. 

2512.8.1 Admixtures. When using this method of applica- 
tion, calcium aluminate cement up to 15 percent of the 
weight of the portland cement is permitted to be added to the 
mix. 

2512.8.2 Curing. Curing of the first coat is permitted to be 
omitted and the second coat shall be cured as set forth in 
ASTM C 926 and Table 2512.6. 

2512.9 Finish coats. Cement plaster finish coats shall be 
applied over base coats that have been in place for the time peri- 
ods set forth in ASTM C 926. The third or finish coat shall be 
applied with sufficient material and pressure to bond and to 
cover the brown coat and shall be of sufficient thickness to con- 
ceal the brown coat. 



SECTION 2513 
EXPOSED AGGREGATE PLASTER 

2513.1 General. Exposed natural or integrally colored aggre- 
gate is permitted to be partially embedded in a natural or col- 
ored bedding coat of cement plaster or gypsum plaster, subject 
to the provisions of this section. 

2513 .2 Aggregate. The aggregate shall be applied manually or 
mechanically and shall consist of marble chips, pebbles or sim- 



2009 INTERNATIONAL BUILDING CODE® 



533 



GYPSUM BOARD AND PLASTER 



ilar durable, moderately hard (three or more on the Mohs hard- 
ness scale), nonreactive materials. 

2513.3 Bedding coat proportions. The bedding coat for inte- 
rior or exterior surfaces shall be composed of one part portland 
cement and one part Type S lime; or one part blended cement 
and one part Type S lime; or masonry cement; or plastic 
cement, and a maximum of three parts of graded white or natu- 
ral sand by volume. The bedding coat for interior surfaces shall 
be composed of 100 pounds (45.4 kg) of neat gypsum plaster 
and a maximum of 200 pounds (90.8 kg) of graded white sand. 
A factory-prepared bedding coat for interior or exterior use is 
permitted. The bedding coat for exterior surfaces shall have a 
minimum compressive strength of 1,000 pounds per square 
inch (psi) (6895 kPa). 

2513.4 Application. The bedding coat is permitted to be 
applied directly over the first (scratch) coat of plaster, provided 
the ultimate overall thickness is a minimum of 7/ 8 inch (22 mm) , 
including lath. Over concrete or masonry surfaces, the overall 
thickness shall be a minimum of i/ 2 inch (12.7 mm). 

2513.5 Bases. Exposed aggregate plaster is permitted to be 
applied over concrete, masonry, cement plaster base coats or 
gypsum plaster base coats installed in accordance with Section 
2511 or 2512. 

2513.6 Preparation of masonry and concrete. Masonry and 
concrete surfaces shall be prepared in accordance with the pro- 
visions of Section 2510.7. 

2513.7 Curing of base coats. Cement plaster base coats shall 
be cured in accordance with ASTM C 926. Cement plaster bed- 
ding coats shall retain sufficient moisture for hydration (hard- 
ening) for 24 hours minimum or, where necessary, shall be kept 
damp for 24 hours by light water spraying. 



534 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 26 

PLASTIC 



SECTION 2601 
GENERAL 

2601.1 Scope. These provisions shall govern the materials, 
design, application, construction and installation of foam plas- 
tic, foam plastic insulation, plastic veneer, interior plastic finish 
and trim and light-transmitting plastics. See Chapter 14 for 
requirements for exterior wall finish and trim. 



SECTION 2602 
DEFINITIONS 

2602.1 General. The following words and terms shall, for the 
purposes of this chapter and as used elsewhere in this code, 
have the meanings shown herein. 

FIBER REINFORCED POLYMER. A polymeric compos 
ite material consisting of reinforcement fibers impregnated 
with a fiber-binding polymer which is then molded and hard- 
ened. 

FIBERGLASS REINFORCED POLYMER. A polymeric 
composite material consisting of glass reinforcement fibers 
impregnated with a fiber-binding polymer which is then 
molded and hardened. 

FOAM PLASTIC INSULATION. A plastic that is intention- 
ally expanded by the use of a foaming agent to produce a 
reduced-density plastic containing voids consisting of open or 
closed cells distributed throughout the plastic for thermal insu- 
lating or acoustical purposes and that has a density less than 20 
pounds per cubic foot (pcf) (320 kg/m 3 ). 

LIGHT-DIFFUSING SYSTEM. Construction consisting in 
whole or in part of lenses, panels, grids or baffles made with 
light-transmitting plastics positioned below independently 
mounted electrical light sources, skylights or light-transmitting 
plastic roof panels. Lenses, panels, grids and baffles that are 
part of an electrical fixture shall not be considered as a 
light-diffusing system. 

LIGHT-TRANSMITTING PLASTIC ROOF PANELS. 

Structural plastic panels other than skylights that are fastened 
to structural members, or panels or sheathing and that are used 
as light-transmitting media in the plane of the roof. 

LIGHT-TRANSMITTING PLASTIC WALL PANELS. 

Plastic materials that are fastened to structural members, or to 
structural panels or sheathing, and that are used as light-trans- 
mitting media in exterior walls. 

PLASTIC, APPROVED. Any thermoplastic, thermosetting 
or reinforced thermosetting plastic material that conforms to 
combustibility classifications specified in the section applica- 
ble to the application and plastic type. 

PLASTIC GLAZING. Plastic materials that are glazed or set 
in frame or sash and not held by mechanical fasteners that pass 
through the glazing material. 



THERMOPLASTIC MATERIAL. A plastic material that is 
capable of being repeatedly softened by increase of tempera- 
ture and hardened by decrease of temperature. 

THERMOSETTING MATERIAL. A plastic material that is 
capable of being changed into a substantially nonreformable 
product when cured. 



SECTION 2603 
FOAM PLASTIC INSULATION 

2603.1 General. The provisions of this section shall govern the 
requirements and uses of foam plastic insulation in buildings 
and structures. 

2603.2 Labeling and identification. Packages and containers 
of foam plastic insulation and foam plastic insulation compo- 
nents delivered to the job site shall bear the label of an 
approved agency showing the manufacturer's name, product 
listing, product identification and information sufficient to 
determine that the end use will comply with the code require- 
ments. 

2603.3 Surface-burning characteristics. Unless otherwise 
indicated in this section, foam plastic insulation and foam plas- 
tic cores of manufactured assemblies shall have a flame spread 
index of not more than 75 and a smoke-developed index of not 
more than 450 where tested in the maximum thickness 
intended for use in accordance with ASTM E 84 or UL 723. 
Loose fill-type foam plastic insulation shall be tested as board 
stock for the flame spread and smoke-developed indexes. 

Exceptions: 

1. Smoke-developed index for interior trim as provided 
for in Section 2604.2. 

2. In cold storage buildings, ice plants, food plants, food 
processing rooms and similar areas, foam plastic 
insulation where tested in a thickness of 4 inches (102 
mm) shall be permitted in a thickness up to 10 inches 
(254 mm) where the building is equipped throughout 
with an automatic fire sprinkler system in accordance 
with Section 903.3.1.1. The approved automatic 
sprinkler system shall be provided in both the room 
and that part of the building in which the room is 
located. 

3. Foam plastic insulation that is a part of a Class A, B or 
C roof-covering assembly provided the assembly 
with the foam plastic insulation satisfactorily passes 
FM 4450 or UL 1256. The smoke-developed index 
shall not be limited for roof applications. 

4. Foam plastic insulation greater than 4 inches (102 
mm) in thickness shall have a maximum flame spread 
index of 75 and a smoke-developed index of 450 
where tested at a minimum thickness of 4 inches (102 
mm), provided the end use is approved in accordance 



2009 INTERNATIONAL BUILDING CODE® 



535 



PLASTIC 



with Section 2603.9 using the thickness and density 
intended for use. 

5. Flame spread and smoke-developed indexes for foam 
plastic interior signs in covered mall bUildings pro- 
vided the signs comply with Section 402.15. 

2603.4 Thermal barrier. Except as provided for in Sections 
2603.4.1 and 2603.9, foam plastic shall be separated from the 
interior of a building by an approved thermal barrier of i/ 2 -inch 
(12.7 mm) gypsum wallboard or equivalent thermal barrier 
material that will limit the average temperature rise of the unex- 
posed surface to not more than 250°F (120°C) after 15 minutes 
of fire exposure, complying with the standard time-tempera- 
ture curve of ASTM E 1 19 or UL 263. The thermal barrier shall 
be installed in such a manner that it will remain in place for 15 
minutes based on FM 4880, UL 1040, NFPA 286 or UL 1715. 
Combustible concealed spaces shall comply with Section 71 7. 

2603.4.1 Thermal barrier not required. The thermal bar- 
rier specified in Section 2603.4 is not required under the 
conditions set forth in Sections 2603.4.1.1 through 
2603.4.1.13. 

2603.4.1.1 Masonry or concrete construction. A ther- 
mal barrier is not required for foam plastic installed in a 
masonry or concrete wall, floor or roof system where the 
foam plastic insulation is covered on each face by a mini- 
mum of 1 inch (25 mm) thickness of masonry or con- 
crete. 

2603.4.1.2 Cooler and freezer walls. Foam plastic 
installed in a maximum thickness of 10 inches (254 mm) 
in cooler and freezer walls shall: 

1. Have a flame spread index of 25 or less and a 
smoke-developed index of not more than 450, 
where tested in a minimum 4 inch (102 mm) thick- 
ness. 

2. Have flash ignition and self-ignition temperatures 
of not less than 600°F and 800°F (316°C and 
427°C), respectively. 

3. Have a covering of not less than 0.032-inch (0.8 
mm) aluminum or corrosion-resistant steel having 
a base metal thickness not less than 0.0160 inch 
(0.4 mm) at any point. 

4. Be protected by an automatic sprinkler system in 
accordance with Section 903.3.1.1. Where the 
cooler or freezer is within a building, both the 
cooler or freezer and that part of the building in 
which it is located shall be sprinklered. 

2603.4.1.3 Walk-in coolers. In nonsprinklered build- 
ings, foam plastic having a thickness that does not 
exceed 4 inches (102 mm) and a maximum flame spread 
index of 75 is permitted in walk-in coolers or freezer 
units where the aggregate floor area does not exceed 400 
square feet (37 m 2 ) and the foam plastic is covered by a 
metal facing not less than 0.032-inch-thick (0.81 mm) 
aluminum or corrosion-resistant steel having a minimum 
base metal thickness of 0.016 inch (0.41 mm). A thick- 
ness of up to 10 inches (254 mm) is permitted where pro- 
tected by a thermal barrier. 



2603.4.1.4 Exterior walls-one-story buildings. For 
one-story buildings, foam plastic having a flame spread 
index of 25 or less, and a smoke-developed index of not 
more than 450, shall be permitted without thermal barri- 
ers in or on exterior walls in a thickness not more than 4 
inches (102 mm) where the foam plastic is covered by a 
thickness of not less than 0.032-inch-thick (0.81 mm) 
aluminum or corrosion-resistant steel having a base 
metal thickness of 0.0160 inch (0.41 mm) and the build- 
ing is equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1. 

2603.4. 1 .5 Roofing. Foam plastic insulation under a roof 
assembly or roof covering that is installed in accordance 
with the code and the manufacturer's instructions shall 
be separated from the interior of the building by wood 
structural panel sheathing not less than 0.47 inch (11.9 
mm) in thickness bonded with exterior glue, with edges 
supported by blocking, tongue-and-groove joints or 
other approved type of edge support, or an equivalent 
material. A thermal barrier is not required for foam plas- 
tic insulation that is a part of a Class A, B or C roof-cover- 
ing assembly, provided the assembly with the foam 
plastic insulation satisfactorily passes FM 4450 or UL 
1256. 

2603.4.1.6 Attics and crawl spaces. Within an attic or 
crawl space where entry is made only for service of utili- 
ties, foam plastic insulation shall be protected against 
ignition by 1 ^-inch-thick (38 mm) mineral fiber insula- 
tion; 1/4-inch-thick (6.4 mm) wood structural panel, 
particleboard or hardboard; 3/ s -inch (9.5 mm) gypsum 
wallboard, corrosion-resistant steel having a base metal 
thickness of 0.016 inch (0.4 mm) or other approved 
material installed in such a manner that the foam plastic 
insulation is not exposed. The protective covering shall 
be consistent with the requirements for the type of con- 
struction. 

2603.4.1.7 Doors not required to have a fire protec- 
tion rating. Where pivoted or side-hinged doors are per- 
mitted without a fire protection rating, foam plastic 
insulation, having a flame spread index of 75 or less and a 
smoke-developed index of not more than 450, shall be 
permitted as a core material where the door facing is of 
metal having a minimum thickness of 0.032-inch (0.8 
mm) aluminum or steel having a base metal thickness of 
not less than 0.016 inch (0.4 mm) at any point. 

2603.4.1.8 Exterior doors in buildings of Group R-2 
or R-3. In occupancies classified as Group R-2 or R-3, 
foam-filled exterior entrance doors to individual dwell- 
ing units that do not require a fire-resistance rating shall 
be faced with wood or other approved materials. 

2603.4.1.9 Garage doors. Where garage doors are per- 
mitted without a fire-resistance rating and foam plastic is 
used as a core material, the door facing shall be metal 
having a minimum thickness ofO. 032-inch (0.8 mm) alu- 
minum or 0.010-inch (0.25 mm) steel or the facing shall 
be minimum 0.125-inch-thick (3.2 mm) wood. Garage 
doors having facings other than those described above 



536 



2009 INTERNATIONAL BUILDING CODE® 



PLASTIC 



shall be tested in accordance with, and meet the accep- 
tance criteria of, DASMA 107. 

Exception: Garage doors using foam plastic insula- 
tion complying with Section 2603.3 in detached and 
attached garages associated with one- and two-family 
dwellings need not be provided with a thermal barrier. 

2603.4.1.10 Siding backer board. Foam plastic insula- 
tion of not more than 2,000 British thermal units per 
square feet (Btu/sq. ft.) (22.7 m]/m 2 ) as determined by 
NFPA 259 shall be permitted as a siding backer board 
with a maximum thickness of i/ 2 inch (12.7 mm), pro- 
vided it is separated from the interior of the building by 
not less than 2 inches (51 mm) of mineral fiber insulation 
or equivalent or where applied as insulation with residing 
over existing wall construction. 

2603.4.1.11 Interior trim. Foam plastic used as interior 
trim in accordance with Section 2604 shall be permitted 
without a thermal barrier. 

2603.4.1.12 Interior signs. Foam plastic used for inte- 
rior signs in covered mall bUildings in accordance with 
Section 402.16 shall be permitted without a thermal bar- 
rier. Foam plastic signs that are not affixed to interior 
building surfaces shall comply with Chapter 8 of the 
International Fire Code. 

2603.4.1.13 Type V construction. Foam plastic spray 
applied to a sill plate and header of Type V construction 
is subject to all of the following: 

1. The maximum thickness of the foam plastic shall 
be 3V 4 inches (82.6 mm). 

2. The density of the foam plastic shall be in the range 
of 1.5 to 2.0 pcf (24 to 32 kg/m 3 ). 

3. The foam plastic shall have a flame spread index of 
25 or less and an accompanying smoke-developed 
index of 450 or less when tested in accordance 
with ASTM E 84 or UL 723. 

2603.5 Exterior walls of buildings of any height. Exterior 
walls of buildings of Type I, II, III or IV construction of any 
height shall comply with Sections 2603.5.1 through 2603.5.7. 
Exterior walls of cold storage buildings required to be con- 
structed of noncombustible materials, where the building is 
more than one storyin height, shall also comply with the provi- 
sions of Sections 2603.5.1 through 2603.5.7. Exterior walls of 
buildings of Type V construction shall comply with Sections 
2603.2,2603.3 and 2603.4. 

2603.5.1 Fire-resistance-rated walls. Where the wall is 
required to have a fire-resistance rating, data based on tests 
conducted in accordance with ASTM E 119 or UL 263 shall 
be provided to substantiate that the fire-resistance rating is 
maintained. 

2603.5.2 Thermal barrier. Any foam plastic insulation 
shall be separated from the building interior by a thermal 
barrier meeting the provisions of Section 2603.4, unless 
special approval is obtained on the basis of Section 2603.9. 

Exception: One-story buildings complying with Section 
2603.4.1.4. 



2603.5.3 Potential heat. The potential heat of foam plastic 
insulation in any portion of the wall or panel shall not 
exceed the potential heat expressed in Btu per square feet 
(m]/m 2 ) of the foam plastic insulation contained in the wall 
assembly tested in accordance with Section 2603.5.5. The 
potential heat of the foam plastic insulation shall be deter- 
mined by tests conducted in accordance with NFPA 259 and 
the results shall be expressed in Btu per square feet (m]/m 2 ) . 

Exception: One- story buildings complying with Section 
2603.4.1.4. 

2603.5.4 Flame spread and smoke-developed indexes. 
Foam plastic insulation, exterior coatings and facings shall 
be tested separately in the thickness intended for use, but not 
to exceed 4 inches (102 mm), and shall each have a flame 
spread index of 25 or less and a smoke-developed index of 
450 or less as determined in accordance with ASTM E 84 or 
UL 723. 

Exception: Prefabricated or factory -manufactured pan- 
els having minimum 0.020-inch (0.51 mm) aluminum 
facings and a total thickness of i/ 4 inch (6.4 mm) or less 
are permitted to be tested as an assembly where the foam 
plastic core is not exposed in the course of construction. 

2603.5.5 Test standard. The wall assembly shall be tested 
in accordance with and comply with the acceptance criteria 
ofNFPA 285. 

Exception: One-story buildings complying with Section 
2603.4.1.4. 

2603.5.6 Label required. The edge or face of each piece of 
foam plastic insulation shall bear the label of an approved 
agency. The label shall contain the manufacturer's or dis- 
tributor's identification, model number, serial number or 
definitive information describing the product or materials' 
performance characteristics and approved agency's identi- 
fication . 

2603.5.7 Ignition. Exterior walls shall not exhibit sustained 
flaming where tested in accordance with NFPA 268. Where 
a material is intended to be installed in more than one thick- 
ness, tests of the minimum and maximum thickness 
intended for use shall be performed. 

Exception: Assemblies protected on the outside with 
one of the following: 

1. A thermal barrier complying with Section 2603.4. 

2. A minimum 1 inch (25 mm) thickness of concrete 
or masonry. 

3. Glass-fiber-reinforced concrete panels of a mini- 
mum thickness of 3/ 8 inch (9.5 mm). 

4. Metal-faced panels having minimum 0.019- 
inch- thick (0.48 mm) aluminum or 0.016-inch- 
thick (0.41 mm) corrosion-resistant steel outer fac- 
ings. 

5. A minimum 7/ 8 inch (22.2 mm) thickness of stucco 
complying with Section 2510. 

2603.6 Roofing. Foam plastic insulation meeting the require- 
ments of Sections 2603.2, 2603.3 and 2603.4 shall be permit- 
ted as part of a roof-covering assembly, provided the assembly 



2009 INTERNATIONAL BUILDING CODE® 



537 



PLASTIC 



I 



with the foam plastic insulation is a Class A, B or C roofing 
assembly where tested in accordance with ASTM E 108 or UL 
790. 

2603.7 Plenums. Foam plastic insulation shall not be used as 
interior wall or ceiling finish in plenums except as permitted in 
Section 2604 or when protected by a thermal barrier in accor- 
dance with Section 2603.4. 

2603.8 Protection against termites. In areas where the proba- 
bility of termite infestation is very heavy in accordance with 
Figure 2603.8, extruded and expanded polystyrene, 
polyisocyanurate and other foam plastics shall not be installed 
on the exterior face or under interior or exterior foundation 
walls or slab foundations located below grade. The clearance 
between foam plastics installed above grade and exposed earth 
shall be at least 6 inches (152 mm). 

Exceptions: 

1. Buildings where the structural members of walls, 
floors, ceilings and roofs are entirely of non- 
combustible materials or preservative-treated wood. 

2. An approved method of protecting the foam plastic 
and structure from subterranean termite damage is 
provided. 

3. On the interior side of basement walls. 



2603.9 Special approval. Foam plastic shall not be required to 
comply with the requirements of Sections 2603.4 through 
2603.7 where specifically approved based on large-scale tests 
such as, but not limited to, NFPA 286 (with the acceptance cri- 
teria of Section 803.2), FM 4880, UL 1040 or UL 1715. Such 
testing shall be related to the actual end-use configuration and 
be performed on the finished manufactured foam plastic 
assembly in the maximum thickness intended for use. Foam 
plastics that are used as interior finish on the basis of special 
tests shall also conform to the flame spread requirements of 
Chapter 8. Assemblies tested shall include seams, joints and 
other typical details used in the installation of the assembly and 
shall be tested in the manner intended for use. 



SECTION 2604 
INTERIOR FINISH AND TRIM 

2604.1 General. Plastic materials installed as interior finish or 
trim shall comply with Chapter 8. Foam plastics shall only be 
installed as interior finish where approved in accordance with 
the special provisions of Section 2603.9. Foam plastics that are 
used as interior finish shall also meet the flame-spread index 
requirements for interior finish in accordance with Chapter 8. 
Foam plastics installed as interior trim shall comply with Sec- 
tion 2604.2. 




VERY HEAVY 
MODERATE TO HEAVY 
SLIGHT TO MODERATE 
NONE TO SLIGHT 



FIGURE 2603.8 
TERMITE INFESTATION PROBABILITY MAP 



538 



2009 INTERNATIONAL BUILDING CODE® 



PLASTIC 



[F] 2604.2 Interior trim. Foam plastic used as interior trim 
shall comply with Sections 2604.2.1 through 2604.2.4. 

[F] 2604.2.1 Density. The minimum density of the interior 
trim shall be 20 pcf (320 kg/m 3 ). 

[F] 2604.2.2 Thickness. The maximum thickness of the 
interior trim shall be i/ 2 inch (12.7 mm) and the maximum 
width shall be 8 inches (204 mm). 

[F] 2604.2.3 Area limitation. The interior trim shall not 
constitute more than 10 percent of the specific wall or ceil- 
ing areas to which it is attached. 

[F] 2604.2.4 Flame spread. The flame spread index shall 
not exceed 75 where tested in accordance with ASTM E 84 
or UL 723. The smoke-developed index shall not be limited. 

Exception: When the interior trim material has been 
tested as an interior finish in accordance with NFPA 286 
and complies with the acceptance criteria in Section 
803.1.2.1, it shall not be required to be tested for flame 
spread index in accordance with ASTM E 84 or UL 723. 



SECTION 2605 
PLASTIC VENEER 

2605.1 Interior use. Where used within a building, plastic 
veneer shall comply with the interior finish requirements of 
Chapter 8. 

2605.2 Exterior use. Exterior plastic veneer, other than plastic 
siding, shall be permitted to be installed on the exterior walls of 
buildings of any type of construction in accordance with all of 
the following requirements: 

1. Plastic veneer shall comply with Section 2606.4. 

2. Plastic veneer shall not be attached to any exterior wall to 
a height greater than 50 feet (15 240 mm) above grade. 

3. Sections of plastic veneer shall not exceed 300 square 
feet (27.9 m 2 ) in area and shall be separated by a mini- 
mum of 4 feet (1219 mm) vertically. 

Exception: The area and separation requirements and 
the smoke-density limitation are not applicable to 
plastic veneer applied to buildings constructed of 
Type VB construction, provided the walls are not 
required to have a fire-resistance rating. 

12605.3 Plastic siding. Plastic siding shall comply with the 
requirements of Sections 1404 and 1405. 



1 



SECTION 2606 
LIGHT-TRANSMITTING PLASTICS 

2606.1 General. The provisions of this section and Sections 
2607 through 2611 shall govern the quality and methods of 
application of light-transmitting plastics for use as light-trans- 
mitting materials in buildings and structures. Foam plastics 
shall comply with Section 2603. Light- transmitting plastic 
materials that meet the other code requirements for walls and 
roofs shall be permitted to be used in accordance with the other 
applicable chapters of the code. 



2606.2 Approval for use. Sufficient technical data shall be 
submitted to substantiate the proposed use of any light-trans- 
mitting material, as approved by the bUilding official and sub- 
ject to the requirements of this section. 

2606.3 Identification. Each unit or package of light-transmit- 
ting plastic shall be identified with a mark or decal satisfactory 
to the building official, which includes identification as to the 
material classification. 

2606.4 Specifications. Light-transmitting plastics, including 
thermoplastic, thermosetting or reinforced thermosetting plas- 
tic material, shall have a self-ignition temperature of 650°F 
(343°C) or greater where tested in accordance with ASTM D 
1929; a smoke-developed index not greater than 450 where 
tested in the manner intended for use in accordance with 
ASTM E 84 or UL 723, or a maximum average smoke density 
rating not greater than 75 where tested in the thickness intended 
for use in accordance with ASTM D 2843 and shall conform to 
one of the following combustibility classifications: 

Class CC 1: Plastic materials that have a burning extent of 1 
inch (25 mm) or less where tested at a nominal thickness of 
0.060 inch (1.5 mm), or in the thickness intended for use, in 
accordance with ASTM D 635. 

Class CC2: Plastic materials that have a burning rate of 2 7 / 2 
inches per minute (1.06 mm/s) or less where tested at a nom- 
inal thickness of 0.060 inch (1.5 mm), or in the thickness 
intended for use, in accordance with ASTM D 635. 

2606.5 Structural requirements. Light-transmitting plastic 
materials in their assembly shall be of adequate strength and 
durability to withstand the loads indicated in Chapter 16. Tech- 
nical data shall be submitted to establish stresses, maximum 
unsupported spans and such other information for the various 
thicknesses and forms used as deemed necessary by the build- 
ing official. 

2606.6 Fastening. Fastening shall be adequate to withstand the 
loads in Chapter 16. Proper allowance shall be made for expan- 
sion and contraction of light-transmitting plastic materials in 
accordance with accepted data on the coefficient of expansion 
of the material and other material in conjunction with which it 
is employed. 

2606.7 Light-diffusing systems. Unless the building is 
equipped throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1, light-diffusing systems 
shall not be installed in the following occupancies and loca- 
tions: 

1. Group A with an occupant load of 1,000 or more. 

2. Theaters with a stage and proscenium opening and an 
occupant load of 700 or more. 

3. Group 1-2. 

4. Group 1-3. 

5. Vertical exit enclosures and exit passageways. 

2606.7.1 Support. Light-transmitting plastic diffusers shall 
be supported directly or indirectly from ceiling or roof con- 
struction by use of noncombustible hangers. Hangers shall 
be at least No. 12 steel- wire gage (0.106 inch) galvanized 
wire or equivalent. 



2009 INTERNATIONAL BUILDING CODE® 



539 



PLASTIC 



2606.7.2 Installation. Light-transmitting plastic diffusers 
shall comply with Chapter 8 unless the light-transmitting 
plastic diffusers will fall from the mountings before ignit- 
ing' at an ambient temperature of at least 200°F (111°C) 
below the ignition temperature of the panels. The panels 
shall remain in place at an ambient room temperature of 
175°F (79°C) for a period of not less than 15 minutes. 

2606.7.3 Size limitations. Individual panels or units shall 
not exceed 10 feet (3048 mm) in length nor 30 square feet 
(2.79 m 2 ) in area. 

2606.7.4 Fire suppression system. In buildings that are 
equipped throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1, plastic light-diffusing 
systems shall be protected both above and below unless the 
sprinkler system has been specifically approved for installa- 
tion only above the light-diffusing system. Areas of 
light-diffusing systems that are protected in accordance 
with this section shall not be limited. 

2606.7.5 Electrical luminaires. Light-transmitting plastic 
panels and light-diffuser panels that are installed in 
approved electrical luminaires shall comply with the 
requirements of Chapter 8 unless the light-transmitting 
plastic panels conform to the requirements of Section 
2606.7.2. The area of approved light-transmitting plastic 
materials that are used in required exits or corridors shall 
not exceed 30 percent of the aggregate area of the ceiling in 
which such panels are installed, unless the building is 
equipped throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1. 

2606.8 Partitions. Light-transmitting plastics used in or as 
partitions shall comply with the requirements of Chapters 6 
and 8. 

2606.9 Bathroom accessories. Light-transmitting plastics 
shall be permitted as glazing in shower stalls, shower doors, 
bathtub enclosures and similar accessory units. Safety glazing 
shall be provided in accordance with Chapter 24. 

2606.10 Awnings, patio covers and similar structures. Awn- 
ings constructed of light-transmitting plastics shall be con- 
structed in accordance with the provisions specified in Section 
3105 and Chapter 32 for projections. Patio covers constructed 
of light-transmitting plastics shall comply with Section 2606. 
Light-transmitting plastics used in canopies at motor fuel-dis- 
pensing facilities shall comply with Section 2606, except as 
modified by Section 406.5.3. 

2606.11 Greenhouses. Light-transmitting plastics shall be 
permitted in lieu of plain glass in greenhouses. 

2606.12 Solar collectors. Light-transmitting plastic covers on 
solar collectors having noncombustible sides and bottoms shall 
be permitted on buildings not over three stories above grade 
plane or 9,000 square feet (836.1 m 2 ) in total floor area, pro- 
vided the light- transmitting plastic cover does not exceed 33.33 
percent of the roof area for CC 1 materials or 25 percent of the 
roof area for CC2 materials. 

Exception: Light-transmitting plastic covers having a 
thickness of 0.010 inch (0.3 mm) or less or shall be permit- 



ted to be of any plastic material provided the area of the solar 
collectors does not exceed 33.33 percent of the roof area. 



SECTION 2607 
LIGHT-TRANSMITTING PLASTIC WALL PANELS 

2607.1 General. Light-transmitting plastics shall not be used 
as wall panels in exterior walls in occupancies in Groups A-I, 
A-2, H, 1-2 and 1-3. In other groups, light-transmitting plastics 
shall be permitted to be used as wall panels in exterior walls, 
provided that the walls are not required to have a fire-resistance 
rating and the installation conforms to the requirements of this 
section. Such panels shall be erected and anchored on a founda- 
tion, waterproofed or otherwise protected from moisture 
absorption and sealed with a coat of mastic or other approved 
waterproof coating. Light-transmitting plastic wall panels shall 
also comply with Section 2606. 

2607.2 Installation. Exterior wa//panels installed as provided 
for herein shall not alter the type of construction classification 
of the building. 

2607.3 Height limitation. Light-transmitting plastics shall not 
be installed more than 75 feet (22 860 mm) above grade plane, 
except as allowed by Section 2607.5. 

2607.4 Area limitation and separation. The maximum area 
of a single wall panel and minimum vertical and horizontal sep- 
aration requirements for exterior light-transmitting plastic wall 
panels shall be as provided for in Table 2607.4. The maximum 
percentage of wall area of any storyin light-transmitting plastic 
wall panels shall not exceed that indicated in Table 2607.4 or 
the percentage of unprotected openings permitted by Section 
705.8, whichever is smaller. 

Exceptions: 

1. In structures provided with approved flame barriers 
extending 30 inches (760 mm) beyond the exterior 
wall in the plane of the floor, a vertical separation is 
not required at the floor except that provided by the 
vertical thickness of the flame barrier projection. 

2. Veneers of approved weather-resistant light-transmit- 
ting plastics used as exterior siding in buildings of 
Type V construction in compliance with Section 1406. 

3. The area of light-transmitting plastic wall panels in 
exterior walls of greenhouses shall be exempt from 
the area limitations of Table 2607.4 but shall be lim- 
ited as required for unprotected openings in accor- 
dance with Section 704.8. 

2607.5 Automatic sprinkler system. Where the building is 
equipped throughout with an automatic sprinkler system in 
accordance with Section 903.3.1.1, the maximum percentage 
area of exterior wall in any story in light-transmitting plastic 
wall panels and the maximum square footage of a single area 
given in Table 2607.4 shall be increased 100 percent, but the 
area of light-transmitting plastic wall panels shall not exceed 
50 percent of the wall area in any story, or the area permitted by 
Section 704.8 for unprotected openings, whichever is smaller. 
These installations shall be exempt from height limitations. 



540 



2009 INTERNATIONAL BUILDING CODE® 



PLASTIC 



TABLE 2607.4 

AREA LIMITATION AND SEPARATION REQUIREMENTS FOR 

LIGHT-TRANSMITTING PLASTIC WALL PANELS a 



FIRE SEPARATION DISTANCE 

(feet) 


CLASS OF 
PLASTIC 


MAXIMUM PERCENTAGE 

AREA OF EXTERIOR WALL IN 

PLASTIC WALL PANELS 


MAXIMUM SINGLE AREA 

OF PLASTIC WALL PANELS 

(square feet) 


MINIMUM SEPARATION OF 
PI ASTIC WAI 1 damci c /f Q a+\ 


Vertical 


Horizontal 


Less than 6 


. 


Not Permitted 


Not Permitted 


_ 


_ 


6 or more but less than 11 


CC1 


10 


50 


8 


4 


CC2 


Not Permitted 


Not Permitted 


_ 


_ 


liar more but less than or equal to 30 


CC1 


25 


90 


6 


4 


CC2 


15 


70 


8 


4 


Over 30 


CC1 


50 


Not Limited 


3 b 





CC2 


50 


100 


6 b 


3 



For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2 

a. For combinations of plastic glazing and plastic wall panel areas permitted, see Section 2607.6. 

b. For reductions in vertical separation allowed, see Section 2607.4. 



2607.6 Combinations of glazing and wall panels. Combina- 
tions of light-transmitting plastic glazing and light-transmit- 
ting plastic wall panels shall be subject to the area, height and 
percentage limitations and the separation requirements appli- 
cable to the class of light-transmitting plastic as prescribed for 
light-transmitting plastic wall panel installations. 



SECTION 2608 
LIGHT-TRANSMITTING PLASTIC GLAZING 

2608.1 Buildings of Type VB construction. Openings in the 
exterior walls of buildings of Type VB construction, where not 
required to be protected by Section 704, shall be permitted to be 
glazed or equipped with light-transmitting plastic. Light-trans- 
mitting plastic glazing shall also comply with Section 2606. 

2608.2 Buildings of other types of construction. Openings in 
the exterior walls of buildings of types of construction other 
than Type VB, where not required to be protected by Section 
704, shall be permitted to be glazed or equipped with 
light-transmitting plastic in accordance with Section 2606 and 
all of the following: 

1. The aggregate area of light-transmitting plastic glazing 
shall not exceed 25 percent of the area of any wall face of 
the storyin which it is installed. The area of a single pane 
of glazing installed above the first story above grade 
plane shall not exceed 16 square feet (1 .5 m 2 ) and the 
vertical dimension of a single pane shall not exceed 4 feet 
(1219 mm). 

Exception: Where an automatic sprinkler system is 
provided throughout in accordance with Section 
903.3.1.1, the area of allowable glazing shall be 
increased to a maximum of 50 percent of the wall face of 
the storyin which it is installed with no limit on the max- 
imum dimension or area of a single pane of glazing. 

2. Approved flame barriers extending 30 inches (762 mm) 
beyond the exterior wallin the plane of the floor, or verti- 
cal panels not less than 4 feet (1219 mm) in height, shall be 
installed between glazed units located in adjacent stories. 



Exception: Buildings equipped throughout with an 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1. 

Light-transmitting plastics shall not be installed more 
than 75 feet (22 860 mm) above grade level. 

Exception: Buildings equipped throughout with an 
automatic sprinkler system in accordance with Sec- 
tion 903.3.1.1. 



SECTION 2609 
LIGHT-TRANSMITTING PLASTIC ROOF PANELS 

2609.1 General. Light-transmitting plastic roof panels shall 
comply with this section and Section 2606. Light-transmitting 
plastic roof panels shall not be installed in Groups H, 1-2 and 
1-3. In all other groups, light-transmitting plastic roof panels 
shall comply with anyone of the following conditions: 

1. The building is equipped throughout with an automatic 
sprinkler system in accordance with Section 903.3.1.1. 

2. The roof construction is not required to have a fire-resis- 
tance rating by Table 601. 

3. The roof panels meet the requirements for roof coverings 
in accordance with Chapter 15. 

2609.2 Separation. Individual roof panels shall be separated 
from each other by a distance of not less than 4 feet (1219 mm) 
measured in a horizontal plane. 

Exceptions: 

1. The separation between roof panels is not required in a 
building equipped throughout with an automatic sprin- 
kler system in accordance with Section 903.3.1.1. 

2. The separation between roof panels is not required in 
low-hazard occupancy buildings complying with the 
conditions of Section 2609.4, Exception 2 or 3. 

2609.3 Location. Where exterior wa//openings are required to 
be protected by Section 705.8, a roof panel shall not be 
installed within 6 feet (1829 mm) of such exterior wall 

2609 .4 Area limitations. Roof panels shall be limited in area 
and the aggregate area of panels shall be limited by a percent- 



2009 INTERNATIONAL BUILDING CODE® 



541 



PLASTIC 



age of the floor area of the room or space sheltered in accor- 
dance with Table 2609.4. 

Exceptions: 

1. The area limitations of Table 2609.4 shall be permit- 
ted to be increased by 100 percent in buildings 
equipped throughout with an automatic sprinkler sys- 
tem in accordance with Section 903.3.1.1. 

2. Low-hazard occupancy buildings, such as swimming 
pool shelters, shall be exempt from the area limitations 
of Table 2609.4, provided that the buildings do not 
exceed 5,000 square feet (465 m 2 ) in area and have a 
minimum fire separation distance of 10 feet (3048 
mm). 

3. Greenhouses that are occupied for growing plants on 
a production or research basis, without public access, 
shall be exempt from the area limitations of Table 
2609.4 provided they have a minimum fire separation 
distance of 4 feet (1220 mm). 

4. Roof coverings over terraces and patios in occupan- 
cies in Group R-3 shall be exempt from the area limi- 
tations of Table 2609.4 and shall be permitted with 
light-transmitting plastics. 

TABLE 2609.4 

AREA LIMITATIONS FOR LIGHT-TRANSMITTING 

PLASTIC ROOF PANELS 



CLASS 

OF 
PLASTIC 


MAXIMUM AREA OF 

INDIVIDUAL ROOF PANELS 

(square feet) 


MAXIMUM AGGREGATE 

AREA OF ROOF PANELS 

(percent of floor area) 


CCI 


300 


30 


CC2 


100 


25 



For SI: 1 square foot = 0.0929 m 2 



SECTION 2610 

LIGHT-TRANSMITTING PLASTIC 

SKYLIGHT GLAZING 

2610.1 Light-transmitting plastic glazing of skylight 
assemblies. Skylight assemblies glazed with light-transmitting 
plastic shall conform to the provisions of this section and Sec- 
tion 2606. Unit skylights glazed with light-transmitting plastic 
shall also comply with Section 2405.5. 

Exception: Skylights in which the light-transmitting plastic 
conforms to the required roof-covering class in accordance 
with Section 1505. 

2610.2 Mounting. The light-transmitting plastic shall be 
mounted above the plane of the roof on a curb constructed in 
accordance with the requirements for the type of construction 
classification, but at least 4 inches (102 mm) above the plane of the 
roof. Edges of light-transmitting plastic skylights or domes shall 
be protected by metal or other approved noncombustible material, 
or the light-transmitting plastic dome or skylight shall be shown to 
be able to resist ignition where exposed at the edge to a flame from 
a Class B brand as described in ASTM E 108 or UL 790. 

Exceptions: 

1. Curbs shall not be required for skylights used on roofs 
having a minimum slope of three units vertical in 12 



units horizontal (25 -percent slope) in occupancies in 
Group R-3 and on buildings with a nonclassified roof 
covering. 

2. The metal or noncombustible edge material is not 
required where nonclassified roof coverings are per- 
mitted. 

2610.3 Slope. Flat or corrugated light-transmitting plastic sky- 
lights shall slope at least four units vertical in 12 units horizon- 
tal (4: 12). Dome-shaped skylights shall rise above the 
mounting flange a minimum distance equal to 10 percent of the 
maximum span of the dome but not less than 3 inches (76 mm) . 

Exception: Skylights that pass the Class B Burning Brand 
Test specified in ASTM E 108 or UL 790. 

2610.4 Maximum area of skylights. Each skylight shall have 
a maximum area within the curb of 100 square feet (9.3 m 2 ). 

Exception: The area limitation shall not apply where the 
building is equipped throughout with an automatic sprin- 
kler system in accordance with Section 903.3.1.1 or the 
building is equipped with smoke and heat vents in accor- 
dance with Section 910. 

2610.5 Aggregate area of skylights. The aggregate area of 
skylights shall not exceed 33 V 3 percent of the floor area of the 
room or space sheltered by the roof in which such skylights are 
installed where Class CC 1 materials are utilized, and 25 per- 
cent where Class CC2 materials are utilized. 

Exception: The aggregate area limitations of light-trans- 
mitting plastic skylights shall be increased 100 percent 
beyond the limitations set forth in this section where the 
building is equipped throughout with an automatic sprin- 
kler system in accordance with Section 903.3.1.1 or the 
building is equipped with smoke and heat vents in accor- 
dance with Section 910. 

2610.6 Separation. Skylights shall be separated from each 
other by a distance of not less than 4 feet (1219 mm) measured 
in a horizontal plane. 

Exceptions: 

1. Buildings equipped throughout with an automatic 
sprinkler system in accordance with Section 
903.3.1.1. 

2. In Group R-3, multiple skylights located above the 
same room or space with a combined area not exceed- 
ing the limits set forth in Section 2610.4. 

2610.7 Location. Where exterior wall openings are required to 
be protected in accordance with Section 705, a skylight shall 
not be installed within 6 feet (1829 mm) of such exterior wall. 

2610.8 Combinations of roof panels and skylights. Combi- 
nations of light-transmitting plastic roof panels and skylights 
shall be subject to the area and percentage limitations and sepa- 
ration requirements applicable to roof panel installations. 



SECTION 2611 
LIGHT-TRANSMITTING PLASTIC INTERIOR SIGNS 

2611.1 General. Light-transmitting plastic interior wall signs 
shall be limited as specified in Sections 261 1.2 through 261 1.4. 



542 



2009 INTERNATIONAL BUILDING CODE® 



PLASTIC 



Light-transmitting plastic interior wall signs in covered mall 
bUildings shall comply with Section 402.16. Light-transmit- 
ting plastic interior signs shall also comply with Section 2606. 

2611.2 Aggregate area. The sign shall not exceed 20 percent 
of the wall area. 

2611.3 Maximum area. The sign shall not exceed 24 square 
feet (2.23 m 2 ). 

2611.4 Encasement. Edges and backs of the sign shall be fully 
encased in metal. 



SECTION 2612 

FIBER REINFORCED POLYMER AND 

FIBERGLASS REINFORCED POLYMER 

2612.1 General. The provisions of this section shall govern the 
requirements and uses of fiber reinforced polymer or fiberglass 
reinforced polymer in and on buildings and structures. 

2612.2 Labeling and identification. Packages and containers 
of fiber reinforced polymer or fiberglass reinforced polymer 
and their components delivered to the job site shall bear the 
labelofan approved agency showing the manufacturer's name, 
product listing, product identification and information suffi- 
cient to determine that the end use will comply with the code 
requirements. 

2612.3 Interior finish. Fiber reinforced polymer or fiberglass 
reinforced polymer used as interior finish shall comply with 
Chapter 8. 

2612.4 Decorative materials and trim. Fiber reinforced poly- 
mer or fiberglass reinforced polymer used as decorative mate- 
rials or trim shall comply with Section 806. 

2612.5 Light-transmitting materials. Fiber reinforced poly- 
mer or fiberglass reinforced polymer used as light-transmitting 
materials shall comply with Sections 2606 through 2611 as 
required for the specific application. 

2612.6 Exterior use. Fiber reinforced polymer or fiberglass 
reinforced polymer shall be permitted to be installed on the 
exterior walls of buildings of any type of construction when 
such polymers meet the requirements of Section 2603.5 and is 
fireblocked in accordance with Section 717. The fiber rein- 
forced polymer or the fiberglass reinforced polymer shall be 
designed for uniform live loads as required in Table 1607.1 as 
well as for snow loads, wind loads and earthquake loads as 
specified in Sections 1608, 1609 and 1613, respectively. 

Exceptions: 

1. When all of the following conditions are met: 

1.1. When the area of the fiber reinforced polymer 
or the fiberglass reinforced polymer does not 
exceed 20 percent of the respective wall area, 
the fiber reinforced polymer or the fiberglass 
reinforced polymer shall have a flame spread 
index of 25 or less or when the area of the fiber 
reinforced polymer or the fiberglass reinforced 
polymer does not exceed 10 percent of the re- 



spective wall area, the fiber reinforced polymer 
or the fiberglass reinforced polymer shall have a 
flame spread index of 75 or less. The flame 
spread index requirement shall not be required 
for coatings or paints having a thickness of less 
than 0.036 inch (0.9 mm) that are applied di- 
rectly to the surface of the fiber reinforced poly- 
mer or the fiberglass reinforced polymer. 

1.2. Fireblocking complying with Section 717.2.6 
shall be installed. 

1.3. The fiber reinforced polymer or the fiberglass 
reinforced polymer shall be installed directly 
to a noncombustible substrate or be separated 
from the exterior wallby one of the following 
materials: corrosion-resistant steel having a 
minimum base metal thickness of 0.016 inch 
(0.41 mm) at any point, aluminum having a 
minimum thickness of 0.019 inch (0.5 mm) or 
other approved noncombustible material. 

1.4. The fiber reinforced polymer or the fiberglass 
reinforced polymer shall be designed for uni- 
form live loads as required in Table 1607.1 as 
well as for snow loads, wind loads and earth- 
quake loads as specified in Sections 1608, 
1609 and 1613, respectively. 

2. When installed on buildings that are 40 feet (12 190 
mm) or less above grade, the fiber reinforced polymer 
or the fiberglass reinforced polymer shall meet the 
requirements of Section 1406.2 and shall comply 
with all of the following conditions: 

2.1. Where the fire separation distance is 5 feet 
(1524 mm) or less, the area of the fiber rein- 
forced polymer or the fiberglass reinforced 
polymer shall not exceed 10 percent of the 
wall area. Where the fire separation distance 
is greater than 5 feet (1524 mm), there shall be 
no limit on the area of the exterior wall cover- 
age using fiber reinforced polymer or the fi- 
berglass reinforced polymer. 

2.2. The fiber reinforced polymer or the fiberglass 
reinforced polymer shall have a flame spread 
index of 200 or less. The flame spread index 
requirement shall not be required for coatings 
or paints having a thickness of less than 0.036 
inch (0.9 mm) that are applied directly to the 
surface of the fiber reinforced polymer or the 
fiberglass reinforced polymer. 

2.3. Fireblocking complying with Section 717.2.6 
shall be installed. 

2.4. The fiber reinforced polymer or the fiberglass 
reinforced polymer shall be designed for uni- 
form live loads as required in Table 1607. 1 as 
well as for snow loads, wind loads and earth- 
quake loads as specified in Sections 1608, 
1609 and 1613, respectively. 



2009 INTERNATIONAL BUILDING CODE® 



543 



PLASTIC 



SECTION 2613 
REFLECTIVE PLASTIC CORE INSULATION 

2613.1 General. The provisions of this section shall govern the 
requirements and uses of reflective plastic core insulation in 
buildings and structures. Reflective plastic core insulation shall 
comply with the requirements of Section 2613 .2 and of one of 
the following: Section 2613.3 or 2613.4. 

2613.2 Identification. Packages and containers of reflective 
plastic core insulation delivered to the job site shall show the 
manufacturer's or supplier's name, product identification and 
information sufficient to determine that the end use will com- 
ply with the code requirements. 

2613.3 Surface-burning characteristics. Reflective plastic 
core insulation shall have a flame spread index of not more than 
25 and a smoke-developed index of not more than 450 when 
tested in accordance with ASTM E 84 or UL 723. The reflec- 
tive plastic core insulation shall be tested at the maximum 
thickness intended for use and shall be tested using one of the 
mounting methods in Section 2613.3.1 or 2613.3.2. 

2613.3.1 Mounting of test specimen. The test specimen 
shall be mounted on 2-inch-high (51 mm) metal frames so 
as to create an air space between the unexposed face of the 
reflective plastic core insulation and the lid of the test appa- 
ratus. 

2613.3.2 Specific testing. A set of specimen preparation 
and mounting procedures shall be used which are specific to 
the testing of reflective plastic core insulation. 

2613.4 Room corner test heat release. Reflective plastic core 
insulation shall comply with the acceptance criteria of Section 
803.1.2.1 when tested in accordance with NFPA 286 or UL 
1715 in the manner intended for use and at the maximum thick- 
ness intended for use. 



544 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 27 

ELECTRICAL 



SECTION 2701 
GENERAL 

2701.1 Scope. This chapter governs the electrical components, 
equipment and systems used in buildings and structures cov- 
ered by this code. Electrical components, equipment and sys- 
tems shall be designed and constructed in accordance with the 
provisions of NFPA 70. 



[F] SECTION 2702 
EMERGENCY AND STANDBY POWER SYSTEMS 

[F] 2702.1 Installation. Emergency and standby power sys- 
tems required by this code or the International Fire Code shall 
be installed in accordance with this code, NFPA 110 and 111. 

[F] 2702.1.1 Stationary generators. Stationary emergency 
and standby power generators required by this code shall be 
listed in accordance with UL 2200. 

[F] 2702.2 Where required. Emergency and standby power 
systems shall be provided where required by Sections 2702.2.1 
through 2702.2.20. 

[F] 2702.2.1 Group A occupancies. Emergency power 
shall be provided for emergency voice/alarm communica- 
tion systems in Group A occupancies in accordance with 
Section 907.5.2.2.4. 

\F] 2702.2.2 Smoke control systems. Standby power shall 
be provided for smoke control systems in accordance with 
Section 909.11. 

[F] 2702.2.3 Exit signs. Emergency power shall be pro- 
vided for exit signs in accordance with Section 1011.5.3. 

[F] 2702.2.4 Means of egress illumination. Emergency 
power shall be provided for means of egress illumination in 
accordance with Section 1006.3. 

[F] 2702.2.5 Accessible means of egress elevators. 
Standby power shall be provided for elevators that are part 
of an accessible means of egress in accordance with Section 
1007.4. 

[F] 2702.2.6 Accessible means of egress platform lifts. 
Standby power in accordance with this section or ASME A 
18.1 shall be provided for platform lifts that are part of an 
accessible means of egress in accordance with Section 
1007.5. 

[F] 2702.2.7 Horizontal sliding doors. Standby power 
shall be provided for horizontal sliding doors in accordance 
with Section 1008.1.4.3. 

[F] 2702.2.8 Semiconductor fabrication facilities. Emer- 
gency power shall be provided for semiconductor fabrica- 
tion facilities in accordance with Section 415.8.10. 



\F] 2702.2.9 Membrane structures. Standby power shall 
be provided for auxiliary inflation systems in accordance 
with Section 3102.8.2. Emergency power shall be provided 
for exit signs in temporary tents and membrane structures in 
accordance with the International Fire Code. 

[F] 2702.2.10 Hazardous materials. Emergency or stand- 
by power shall be provided in occupancies with hazardous 
materials in accordance with Section 414.5.4. 

[F] 2702.2.11 Highly toxic and toxic materials. Emer- 
gency power shall be provided for occupancies with highly 
toxicor toxic materials in accordance with the International 
Fire Code. 

[F] 2702.2.12 Organic peroxides. Standby power shall be 
provided for occupancies with silane gas in accordance with 
the International Fire Code. 

[F] 2702.2.13 Pyrophoric materials. Emergency power 
shall be provided for occupancies with silane gas in accor- 
dance with the International Fire Code. 

\F] 2702.2.14 Covered mall buildings. Standby power 
shall be provided for voice/alarm communication systems 
in covered mall buildings in accordance with Section 
402.14. 

[F] 2702.2.15 High-rise buildings. Emergency and stand- 
by power shall be provided in high-rise buildings in accor- 
dance with Sections 403.4.7 and 403.4.8. 

[F] 2702.2.16 Underground buildings. Emergency and 
standby power shall be provided in underground buildings 
in accordance with Sections 405.8 and 405.9. 

[F] 2702.2.17 Group 1-3 occupancies. Emergency power 
shall be provided for doors in Group 1-3 occupancies in 
accordance with Section 408.4.2. 

\F] 2702.2.18 Airport traffic control towers. Standby 
power shall be provided in airport traffic control towers in 
accordance with Section 412.3.5. 

[F] 2702.2.19 Elevators. Standby power for elevators shall 
be provided as set forth in Sections 3003.1, 3007.7 and 
3008.15. 

[F] 2702.2.20 Smokeproof enclosures. Standby power 
shall be provided for smokeproof enclosures as required by 
Section 909.20.6.2. 

[F] 2702.3 Maintenance. Emergency and standby power sys- 
tems shall be maintained and tested in accordance with the 
International Fire Code. 



2009 INTERNATIONAL BUILDING CODE® 



545 



546 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 28 

MECHANICAL SYSTEMS 



SECTION 2801 
GENERAL 

2801.1 Scope. Mechanical appliances, equipment and systems 
shall be constructed, installed and maintained in accordance 
with the International Mechanical Code and the International 
Fuel Gas Code. Masonry chimneys, fireplaces and barbecues 
shall comply with the International Mechanical Code and 
Chapter 21 of this code. 



2009 INTERNATIONAL BUILDING CODE® 547 



548 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 29 

PLUMBING SYSTEMS 



SECTION 2901 
GENERAL 

[P] 2901.1 Scope. The provisions of this chapter and the Inter- 
national Plumbing Code shall govern the erection, installation, 
alteration, repairs, relocation, replacement, addition to, use or 
maintenance of plumbing equipment and systems. Plumbing 
systems and equipment shall be constructed, installed and 
maintained in accordance with the International Plumbing 
Code. Private sewage disposal systems shall conform to the 
International Private Sewage Disposal Code. 



SECTION 2902 
MINIMUM PLUMBING FACILITIES 

[P] 2902.1 Minimum number of fixtures. Plumbing fixtures 
shall be provided for the type of occupancy and in the mini- 
mum number shown in Table 2902.1. Types of occupancies not 
shown in Table 2902.1 shall be considered individually by the 
bUilding official. The number of occupants shall be determined 
by this code. Occupancy classification shall be determined in 
accordance with Chapter 3. 



[P] TABLE 2902.1 
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES 3 
(See Sections 2902.2 and 2902.3) 



CLASSIFICATION 



OCCUPANCY 



DESCRIPTION 



WATER CLOSETS 
(URINALS SEE SECTION 419.2 OF 
THE INTERNATIONAL PLUMBING 
CODE) 



MALE 



FEMALE 



LAVATORIES 



BATHTUBSI 
SHOWERS 



DRINKING 
FOUNTAINS 65 ' f 

(SEE SECTION 

410.1 OF THE 

INTERNA TIONAL 

PLUMBING CODE) 



A-l d 



A-2 d 



Assembly 



A-3 d 



A-4 



A-5 



Theaters and other 
buildings for the 
performing arts and 
motion pictures 



1 per 125 



1 per 65 



1 per 200 



1 per 500 



Nightclubs , bars , 
taverns, dance halls and 
buildings for similar 
purposes 

Restaurants, banquet 
halls and food courts 



1 per 40 



1 per 75 



1 per 40 



1 per 75 



1 per 75 



1 per 200 



1 per 500 



1 per 500 



Auditoriums without 
permanent seating, art 
galleries, exhibition 
halls , museums , lecture 
halls, libraries, arcades 
and gymnasiums 



1 per 125 



1 per 65 



1 per 200 



1 per 500 



Passenger terminals and 
transportation facilities 



1 per 500 



1 per 500 



1 per 750 



1 per 1,000 



Places of worship and 
other religious services 



1 per 150 



1 per 75 



1 per 200 



1 per 1,000 



Coliseums, arenas, 
skating rinks, pools and 
tennis courts for indoor 
sporting events and 
activities 



1 per 75 for the 
first 1,500 and 
1 per 120 for 
the remainder 
exceeding 
1,500 



1 per 40 for the 
first 1,520 and 
1 per 60 for the 
remainder 
exceeding 
1,520 



1 per 200 



Stadiums, amusement 
parks , bleachers and 
grandstands for outdoor 
sporting events and 
activities 



1 per 75 for the 
first 1,500 and 
1 per 120 for 
the remainder 
exceeding 
1,500 



1 per 40 for the 
first 1,520 and 
1 per 60 for the 
remainder 
exceeding 
1,520 



1 per 200 



1 per 150 



1 per 1,000 



1 per 150 



1 per 1,000 



service 
sink 



service 
sink 



service 
sink 



service 
sink 



service 
sink 



service 
sink 



service 
sink 



service 
sink 



(continued) 



2009 INTERNATIONAL BUILDING CODE® 



549 



PLUMBING SYSTEMS 



[P] TABLE 2902.1-continued 
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES 3 



No. 


CLASSIFICATION 


OCCUPANCY 


DESCRIPTION 


WATER CLOSETS 

(URINALS SEE SECTION 419.2 OF 

THE INTERNATIONAL PLUMBING 

CODE) 


LAVATORIES 


BATHTUBS 

OR 
SHOWERS 


DRINKING 

FOUNTAINS 6 ' f 

(SEE SECTION 

410.1 OF THE 

INTERNA TIONAL 

PLUMBING CODE) 


OTHER 


MALE | FEMALE 


MALE 1 FEMALE 


2 


Business 


B 


Buildings for the 
transaction of 
business, professional 
services, other 
services involving 
merchandise, office 
buildings, banks, 
light industrial and 
similar uses 


1 per 25 for the first 50 and 1 
per 50 for the remainder 
exceeding 50 


1 per 40 for the first 
80 and 1 per 80 for 
the remainder 
exceeding 80 




1 per 100 


1 service 
sink 


3 


Educational 


E 


Educational facilities 


1 per 50 


1 per 50 


- 


1 per 100 


1 service 
sink 


4 


Factory and 
industrial 


F-l and F-2 


Structures in which 
occupants are 
engaged in work 
fabricating, assembly 
or processing of 
products or materials 


1 per 100 


1 per 100 


See Section 
411 of the 
International 
Plumbing 
Code 


1 per 400 


1 service 
sink 


5 


Institutional 


1-1 


Residential care 


1 per 10 


1 per 10 


lper8 


1 per 100 


1 service 
sink 


1-2 


Hospitals, 
ambulatory nursing 
home patients 


1 per per room c 


1 per per room c 


1 per 15 


1 per 100 


1 service 
sink 




Employees, other 
than residential careb 


1 per 25 


1 per 35 




1 per 100 






Visitors, other than 
residential care 


1 per 75 


1 per 100 


- 


1 per 500 


- 


1-3 


Prisons 


1 per cell 


1 per cell 


1 per 15 


1 per 100 


1 service 
sink 


1-3 


Reformatories, 
detention centers and 
correctional centers 


1 per 15 


1 per 15 


1 per 15 


1 per 100 


1 service 
sink 


Employees 


1 per 25 


1 per 35 




1 per 100 




1-4 


Adult day care and 
child care 


1 per 15 


1 per 15 


1 


1 per 100 


1 service 
sink 


6 


Mercantile 


M 


Retail stores, service 
stations, shops, 
salesrooms, markets 
and shopping centers 


1 per 500 


1 per 750 


- 


1 per 1,000 


1 service 
sink 


7 


Residential 


R-l 


Hotels, motels, 
boarding houses 
(transient) 


1 per sleeping unit 


1 per sleeping unit 


1 per sleeping 
unit 




1 service 
sink 


R-2 


Dormitories, 
fraternities, sororities 
and boarding houses 
(not transient) 


1 per 10 


1 per 10 


lper8 


1 per 100 


1 service 
sink 


R-2 


Apartment house 


1 per dwelling unit 


1 per dwelling unit 


1 per 
dwelling unit 




1 kitchen 

sink per 

dwelling 

unit; 1 

automatic 

clothes 

washer 

connection 

per 20 

dwelling 

units 



(continued) 



550 



2009 INTERNATIONAL BUILDING CODE® 



PLUMBING SYSTEMS 









[P] TABLE 2902.1 -continued 
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES 21 








No. 


CLASSIFICATION 


OCCUPANCY 


DESCRIPTION 


WATER CLOSETS 

(URINALS SEE SECTION 419.2 OF 

THE INTERNATIONAL PLUMBING 

CODE) 


LAVATORIES 


BATHTUBSI 
SHOWERS 


DRINKING 
FOUNTAINS 6 ' f 

(SEE SECTION 

410.1 OF THE 

INTERNATIONAL 

PLUMBING CODE) 


OTHER 


MALE | FEMALE 


MALE 1 FEMALE 


7 


Residential 


R-3 


Congregate living 
facilities with 16 or 


1 per 10 


1 per 10 


lper8 


1 per 100 


1 service 
sink 


R-4 


Residential 
care/assisted living 
facilities 


1 per 10 


1 per 10 


lper8 


1 per 100 


1 service 
sink 


8 


Storage 


S-l 

S-2 


Structures for the 
storage of goods, 
warehouses, 
storehouses and 
freight depots , low 
and moderate hazard 


1 per 100 


1 per 100 


See Section 
411 of the 
International 
Plumbing 
Code 


1 per 1,000 


1 service 
sink 



a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. 
The number of occupants shall be determined by this code. 

b. Toilet facilities for employees shall be separate from facilities for inmates or patients. 

c. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted where such room 
is provided with direct access from each patient sleeping unit and with provisions for privacy. 

d. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of Bcilities required. 

e. The minimum number of required drinking fountains shall comply with Table 2902.1 and Chapter 11 . 

f. Drinking fountains are not required for an occupant load of 15 or fewer. 



[P] 2902.1.1 Fixture calculations. To determine the occu- 
pant load of each sex, the total occupant load shall be 
divided in half. To determine the required number of fix- 
tures, the fixture ratio or ratios for each fixture type shall be 
applied to the o c cup ant I o ad of each sex in accordance with 
Table 2902.1. Fractional numbers resulting from applying 
the fixture ratios of Table 2902.1 shall be rounded up to the 
next whole number. For calculations involving multiple 
occupancies, such fractional numbers for each occupancy 
shall first be summed and then rounded up to the next whole 
number. 

Exception: The total occupant loadshaW not be required 
to be divided in half where approvedstatistical data indi- 
cate a distribution of the sexes of other than 50 percent of 
each sex. 

2902.1.2 Family or assisted use toilet and bath fixtures. 
Fixtures located within family or assisted use toilet and 
bathing rooms required by Section 1109.2.1 are permitted 
to be included in the number of required fixtures for either 
the male or female occupants in assembly and mercantile 
occupancies. 

[P] 2902.2 Separate facilities. Where plumbing fixtures are 
required, separate facilities shall be provided for each sex. 

Exceptions: 

1. Separate facilities shall not be required for dwelling 
units and sleeping units. 

2. Separate facilities shall not be required in structures 
or tenant spaces with a total occupant load, including 
both employees and customers, of 15 or less. 

3. Separate facilities shall not be required in mercantile 
occupancies in which the maximum occupant load is 
50 or less. 



[P] 2902.3 Required public toilet facilities. Customers, 
patrons and visitors shall be provided with public toilet facili- 
ties in structures and tenant spaces intended for public utiliza- 
tion. The number of plumbing fixtures located within the 
required toilet facilities shall be provided in accordance with 
Section 2902.1 for all users. Employees shall be provided with 
toilet facilities in all occupancies. Employee toilet facilities 
shall either be separate or combined employee and public toilet 
facilities . 

[PI 2902.3.1 Access. The route to the public toilet facilities 
required by Section 2902.3 shall not pass through kitchens, 
storage rooms or closets. Access to the required facilities 
shall be from within the building or from the exterior of the 
building. All routes shall comply with the accessibility 
requirements of this code. The public shall have access to 
the required toilet facilities at all times that the building is 
occupied. 

[P] 2902.3.2 Location of toilet facilities in occupancies 
other than covered mall buildings. In occupancies other 
than covered mall buildings, the required public and 
employee toilet facilities shall be located not more than one 
story above or below the space required to be provided with 
toilet facilities and the path of travel to such facilities shall 
not exceed a distance of 500 feet (152 400 mm). 

Exception: The location and maximum travel distances 
to required employee facilities in factory and industrial 
occupancies are permitted to exceed that required by this 
section, provided that the location and maximum travel 
distance are approved. 

[P] 2902.3.3 Location of toilet facilities in covered mall 
buildings. In covered mall buildings, the required public 
and employee toilet facilities shall be located not more than 
one story above or below the space required to be provided 
with toilet facilities, and the path of travel to such facilities 



2009 INTERNATIONAL BUILDING CODE® 



551 



PLUMBING SYSTEMS 



shall not exceed a distance of 300 feet (91 440 mm). In cov- 
er edmall buildings, the required facilities shall be based on 
total square footage, and facilities shall be installed in each 
individual store or in a central toilet area located in accor- 
dance with this section. The maximum travel distance to the 
central toilet facilities in covered mall buildings shall be 
measured from the main entrance of any store or tenant 
space. In covered mall buildings, where employees' toilet 
facilities are not provided in the individual store, the maxi- 
mum travel distance shall be measured from the employees' 
work area of the store or tenant space. 

[P] 2902.3.4 Pay facilities. Where pay facilities are 
installed, such facilities shall be in excess of the required 
minimum facilities. Required facilities shall be free of 
charge. 

[P] 2902.4 Signage. A legible sign designating the sex shall be 
provided in a readily visible location near the entrance to each 
toilet facility. Signs for accessible toilet facilities shall comply 
with ICC AI17.1. 

2902.4.1 Directional signage. Directional signage indicat- 
ing the route to the public facilities shall be posted in accor- 
dance with Section 3107. Such signage shall be located in a 
corridor ox aisle, at the entrance to the facilities for custom- 
ers and visitors. 



2. Toilet rooms located in day care and child care facili- 
ties and containing two or more urinals shall be per- 
mitted to have one urinal without partitions. 

[P] 2903.3 Interior Finish. Interior finish surfaces of toilet 
rooms shall comply with Section 1210. 



SECTION 2903 
TOILET ROOM REQUIREMENTS 

[P] 2903.1 Water closet compartment. Each water closet uti- 
lized by the public or employees shall occupy a separate com- 
partment with walls or partitions and a door enclosing the 
fixtures to ensure privacy. 

Exceptions: 

1. Water closet compartments shall not be required in a 
single-occupant toilet room with a lockable door. 

2. Toilet rooms located in day care and child care facili- 
ties and containing two or more water closets shall be 
permitted to have one water closet without an enclos- 
ing compartment. 

3. This provision is not applicable to toilet areas located 
within Group 1-3 housing areas. 

[P] 2903.2 Urinal partitions. Each urinal utilized by the pub- 
lic or employees shall occupy a separate area with walls or par- 
titions to provide privacy. The walls or partitions shall begin at 
a height not more than 12 inches (305 mm) from and extend not 
less than 60 inches (1524 mm) above the finished floor surface. 
The walls or partitions shall extend from the wall surface at 
each side of the urinal a minimum of 18 inches (457 mm) or to a 
point not less than 6 inches (152 mm) beyond the outermost 
front lip of the urinal measured from the finished back wall sur- 
face, whichever is greater. 

Exceptions: 

1. Urinal partitions shall not be required in a single occu- 
pant or family or assisted use toilet room with a 
lockable door. 



552 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 30 

ELEVATORS AND CONVEYING SYSTEMS 



SECTION 3001 
GENERAL 

3001.1 Scope. This chapter governs the design, construction, 
installation, alteration and repair of elevators and conveying 
systems and their components. 

3001.2 Referenced standards. Except as otherwise provided 
for in this code, the design, construction, installation, alter- 
ation, repair and maintenance of elevators and conveying sys- 
tems and their components shall conform to ASME 
AI7.1/CSA B44, ASME A90.1, ASME B20.1, ALI ALCTV, 
and ASCE 24 for construction in flood hazard areas established 
in Section 1612.3. 

3001.3 Accessibility. Passenger elevators required to be acces- 
sible by Chapter 11 shall conform to ICC A117.1. 

3001.4 Change in use. A change in use of an elevator from 
freight to passenger, passenger to freight, or from one freight 
class to another freight class shall comply with Section 8.7 of 
ASMEAI7.1/CSAB44. 



SECTION 3002 
HOISTWAY ENCLOSURES 

3002.1 Hoistway enclosure protection. Elevator, dumbwaiter 
and other hoistway enclosures shall be shaft enclosures com- 
plying with Section 708. 

3002.1.1 Opening protectives. Openings in hoistway 
enclosures shall be protected as required in Chapter 7. 

Exception: The elevator car doors and the associated 
hoistway enclosure doors at the floor level designated for 
recall in accordance with Section 3003.2 shall be permit- 
ted to remain open during Phase I Emergency Recall 
Operation. 

3002.1.2 Hardware. Hardware on opening protectives 
shall be of an approved type installed as tested, except that 
approved interlocks, mechanical locks and electric con- 
tacts, door and gate electric contacts and door-operating 
mechanisms shall be exempt from the fire test requirements. 

3002.2 Number of elevator cars in a hoistway. Where four or 
more elevator cars serve all or the same portion of a building, 
the elevators shall be located in at least two separate hoistways. 
Not more than four elevator cars shall be located in any single 
hoistway enclosure. 

3002.3 Emergency signs. An approvedpictorial sign of a stan- 
dardized design shall be posted adjacent to each elevator call 
station on all floors instructing occupants to use the exit stair- 
ways and not to use the elevators in case of fire. The sign shall 



read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. 
USE EXIT STAIRS. 

Exceptions: 

1. The emergency sign shall not be required for elevators 
that are part of an accessible means of egress complying 
with Section 1007.4. 

2. The emergency sign shall not be required for elevators 
that are used for occupant self-evacuation in accordance 
with Section 3008. 

3002.4 Elevator car to accommodate ambulance stretcher. 
Where elevators are provided in buildings four or more stories 
above, or four or more stories below, grade plane, at least one 
elevator shall be provided for fire department emergency 
access to all floors. The elevator car shall be of such a size and 
arrangement to accommodate an ambulance stretcher 24 
inches by 84 inches (610 mm by 2134 mm) with not less than 
5-inch (127 mm) radius corners, in the horizontal, open posi- 
tion and shall be identified by the international symbol for 
emergency medical services (star of life). The symbol shall not 
be less than 3 inches (76 mm) high and shall be placed inside on 
both sides of the hoistway door frame. 

3002.5 Emergency doors. Where an elevator is installed in a 
single blind hoistway or on the outside of a building, there shall 
be installed in the blind portion of the hoistway or blank face of 
the building, an emergency door in accordance with ASME 
AI7.1/CSAB44. 

3002.6 Prohibited doors. Doors, other than hoistway doors 
and the elevator car door, shall be prohibited at the point of 
access to an elevator car unless such doors are readily openable 
from the car side without a key, tool, special knowledge or 
effort. 

3002.7 Common enclosure with stairway. Elevators shall not 
be in a common shaft enclosure with a stairway. 

Exception: Open parking garages. 

3002.8 Glass in elevator enclosures. Glass in elevator enclo- 
sures shall comply with Section 2409.1. 



[F] SECTION 3003 
EMERGENCY OPERATIONS 

[F] 3003.1 Standby power. In buildings and structures where 
standby power is required or furnished to operate an elevator, 
the operation shall be in accordance with Sections 3003.1.1 
through 3003.1.4. 

[F] 3003.1.1 Manual transfer. Standby power shall be 
manually transferable to all elevators in each bank. 



2009 INTERNATIONAL BUILDING CODE® 



553 



ELEVATORS AND CONVEYING SYSTEMS 



[F] 3003.1.2 One elevator. Where only one elevator is 
installed, the elevator shall automatically transfer to standby 
power within 60 seconds after failure of normal power. 

\F] 3003.1.3 Two or more elevators. Where two or more 
elevators are controlled by a common operating system, all 
elevators shall automatically transfer to standby power 
within 60 seconds after failure of normal power where the 
standby power source is of sufficient capacity to operate all 
elevators at the same time. Where the standby power source 
is not of sufficient capacity to operate all elevators at the 
same time, all elevators shall transfer to standby power in 
sequence, return to the designated landing and disconnect 
from the standby power source. After all elevators have 
been returned to the designated level, at least one elevator 
shall remain operable from the standby power source. 

\F] 3003 . 1 .4 Venting. Where standby power is connected to 
elevators, the machine room ventilation or air conditioning 
shall be connected to the standby power source. 

[F] 3003.2 Fire-fighters' emergency operation. Elevators 
shall be provided with Phase I emergency recall operation and 
Phase II emergency in-car operation in accordance with AS ME 
AI7. 1/CSAB44. 



SECTION 3004 
HOISTWAY VENTING 

3004.1 Vents required. Hoistways of elevators and dumbwait- 
ers penetrating more than three stories shall be provided with a 
means for venting smoke and hot gases to the outer air in case 
of fire. 

Exceptions: 

1. In occupancies of other than Groups R-l, R-2, 1-1, 1-2 
and similar occupancies with overnight sleeping 
units, venting of hoistways is not required where the 
building is equipped throughout with an approved 
automatic sprinkler system installed in accordance 
with Section 903.3.1.1 or 903.3.1.2. 

2. Sidewalk elevator hoistways are not required to be 
vented. 

3. Elevators contained within and serving open parking 
garages only. 

4. Elevators within individual residential dwelling units. 

3004.2 Location of vents. Vents shall be located at the top the 
hoistway and shall open either directly to the outer air or 
through noncombustible ducts to the outer air. Noncombustible 
ducts shall be permitted to pass through the elevator machine 
room, provided that portions of the ducts located outside the 
hoistway or machine room are enclosed by construction having 
not less than the fire-resistance rating required for the 
hoistway. Holes in the machine room floors for the passage of 
ropes, cables or other moving elevator equipment shall be lim- 
ited as not to provide greater than 2 inches (51 mm) of clear- 
ance on all sides. 

3004.3 Area of vents. Except as provided for in Section 
3004.3. 1, the area of the vents shall not be less than 3 1 / 2 percent 



of the area of the hoistway nor less than 3 square feet (0.28 m 2 ) 
for each elevator car, and not less than 3 1 \ percent nor less than 
0.5 square feet (0.047 m 2 ) for each dumbwaiter car in the 
hoistway, whichever is greater. Of the total required vent area, 
not less than one-third shall be permanently open. Closed por- 
tions of the required vent area shall consist of openings glazed 
with annealed glass not greater than i/ 8 inch (3.2 mm) in thick- 
ness. 

Exception: The total required vent area shall not be 
required to be permanently open where all the vent openings 
automatically open upon detection of smoke in the elevator 
lobbies or hoistway, upon power failure and upon activation 
of a manual override control. The manual override control 
shall be capable of opening and closing the vents and shall 
be located in an approve d\oc&\ion. 

3004.3.1 Reduced vent area. Where mechanical ventila- 
tion conforming to the International Mechanical Code is 
provided, a reduction in the required vent area is allowed 
provided that all of the following conditions are met: 

1. The occupancy is not in Group R-l, R-2, 1-1 or 1-2 or 
of a similar occupancy with overnight sleeping units. 

2. The vents required by Section 3004.2 do not have out- 
side exposure. 

3. The hoistway does not extend to the top of the build- 
ing. 

4. The hoistway and machine room exhaust fan is auto- 
matically reactivated by thermostatic means. 

5. Equivalent venting of the hoistway is accomplished. 

3004.4 Plumbing and mechanical systems. Plumbing and 
mechanical systems shall not be located in an elevator shaft. 

Exception: Floor drains, sumps and sump pumps shall be 
permitted at the base of the shaft provided they are indirectly 
connected to the plumbing system. 



SECTION 3005 
CONVEYING SYSTEMS 

3005.1 General. Escalators, moving walks, conveyors, per- 
sonnel hoists and material hoists shall comply with the provi- 
sions of this section. 

3005.2 Escalators and moving walks. Escalators and moving 
walks shall be constructed of approved noncombustible and 
fire-retardant materials. This requirement shall not apply to 
electrical equipment, wiring, wheels, handrails and the use of 
i/ 28 -inch (0.9 mm) wood veneers on balustrades backed up with 
noncombustible materials. 

3005.2.1 Enclosure. Escalator floor openings shall be 
enclosed with shaft enclosures complying with Section 708 . 

3005.2.2 Escalators. Where provided in below-grade trans- 
portation stations, escalators shall have a clear width of 32 
inches (815 mm) minimum. 

Exception: The clear width is not required in existing 
facilities undergoing alterations. 



554 



2009 INTERNATIONAL BUILDING CODE® 



ELEVATORS AND CONVEYING SYSTEMS 



3005.3 Conveyors. Conveyors and conveying systems shall 
comply with ASME B20. 1 . 

3005.3.1 Enclosure. Conveyors and related equipment con- 
necting successive floors or levels shall be enclosed with 
shaft enclosures complying with Section 708. 

3005.3.2 Conveyor safeties. Power-operated conveyors, 
belts and other material-moving devices shall be equipped 
with automatic limit switches which will shut off the power 
in an emergency and automatically stop all operation of the 
device. 

3005.4 Personnel and material hoists. Personnel and mate- 
rial hoists shall be designed utilizing an approved method that 
accounts for the conditions imposed during the intended opera- 
tion of the hoist device. The design shall include, but is not lim- 
ited to, anticipated loads, structural stability, impact, vibration, 
stresses and seismic restraint. The design shall account for the 
construction, installation, operation and inspection of the hoist 
tower, car, machinery and control equipment, guide members 
and hoisting mechanism. Additionally, the design of personnel 
hoists shall include provisions for field testing and mainte- 
nance which will demonstrate that the hoist device functions in 
accordance with the design. Field tests shall be conducted upon 
the completion of an installation or following a major alter- 
ation of a personnel hoist. 



SECTION 3006 
MACHINE ROOMS 

3006.1 Access. An approve dmeans of access shall be provided 
to elevator machine rooms and overhead machinery spaces. 

3006.2 Venting. Elevator machine rooms that contain 
solid-state equipment for elevator operation shall be provided 
with an independent ventilation or air-conditioning system to 
protect against the overheating of the electrical equipment. The 
system shall be capable of maintaining temperatures within the 
range established for the elevator equipment. 

3006.3 Pressurization. The elevator machine room serving a 
pressurized elevator hoistway shall be pressurized upon activa- 
tion of a heat or smoke detector located in the elevator machine 
room. 

3006.4 Machine rooms and machinery spaces. Elevator 
machine rooms and machinery spaces shall be enclosed with 
fire barriers constructed in accordance with Section 707 or 
horizontal assemblies constructed in accordance with Section 
712, or both. The fire-resistance rating shall not be less than the 
required rating of the hoistway enclosure served by the 
machinery. Openings in ihtfire barriers shall be protected with 
assemblies having a fire protection rating not less than that 
required for the hoistway enclosure doors. 

Exceptions: 

1. Where machine rooms and machinery spaces do not 
abut and have no openings to the hoistway enclosure 
they serve the fire barriers constructed in accordance 
with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both, shall 
be permitted to be reduced to a l-hom fire -resistance 
rating. 



2. In buildings four stories or less above grade plane 
when machine room and machinery spaces do not 
abut and have no openings to the hoistway enclosure 
they serve, the machine room and machinery spaces 
are not required to be fire-resistance rated. 

3006.5 Shunt trip. Where elevator hoistway s or elevator 
machine rooms containing elevator control equipment are pro- 
tected with automatic sprinklers, a means installed in accor- 
dance with NFPA 72, Section 6. 16.4, Elevator Shutdown, shall 
be provided to disconnect automatically the main line power 
supply to the affected elevator prior to the application of water. 
This means shall not be self-resetting. The activation of sprin- 
klers outside the hoistway or machine room shall not discon- 
nect the main line power supply. 

3006.6 Plumbing systems. Plumbing systems shall not be 
located in elevator equipment rooms. 



SECTION 3007 
FIRE SERVICE ACCESS ELEVATOR 

3007.1 General. Where required by Section 403.6.1, every 
floor of the building shall be served by a fire service access ele- 
vator. Except as modified in this section, the fire service access 
elevator shall be installed in accordance with this chapter and 
ASME AI7.1/CSAB44. 

3007.2 Hoistway enclosures protection. The fire service 
access elevator shall be located in a shaft enclosure complying 
with Section 708. 

3007.3 Hoistway lighting. When firefighters' emergency 
operation is active, the entire height of the hoistway shall be 
illuminated at not less than 1 foot-candle (11 lux) as measured 
from the top of the car of each fire service access elevator. 

3007.4 Fire service access elevator lobby. The fire service 
access elevator shall open into a fire service access elevator 
lobby in accordance with Sections 3007.4.1 through 3007.4.4. 

Exception: Where a fire service access elevator has two 
entrances onto a floor, the second entrance shall be permit- 
ted to open into an elevator lobby in accordance with Sec- 
tion 708.14.1. 

3007.4.1 Access. The fire service access elevator lobby 
shall have direct access to an exit enclosure. 

3007.4.2 Lobby enclosure. The fire service access elevator 
lobby shall be enclosed with a smoke barrierhaving a mini- 
mum I-hom fire-resistance rating, except that lobby door- 
ways shall comply with Section 3007.4.3. 

Exception: Enclosed fire service access elevator lobbies 
are not required at the street floor. 

3007.4.3 Lobby doorways. Each fire service access eleva- 
tor lobby shall be provided with a doorway that is protected 
with a 3/4-hour fire door assembly complying with Section 
715.4. The fire door assembly shall also comply with the 
smoke and draft control door assembly requirements of 
Section 715.4.3.1 with the UL 1784 test conducted without 
the artificial bottom seat. 



2009 INTERNATIONAL BUILDING CODE® 



555 



ELEVATORS AND CONVEYING SYSTEMS 



3007.4.4 Lobby size. Each enclosed fire service access ele- 
vator lobby shall be a minimum of 150 square feet (14 m 2 ) in 
an area with a minimum dimension of 8 feet (2440 mm). 

3007.5 Standpipe hose connection. A Class I standpipe hose 
connection in accordance with Section 905 shall be provided in 
the exit enclosure having direct access from the fire service 
access elevator lobby. 

3007.6 Elevator system monitoring. The fire service access 
elevator shall be continuously monitored at the fire command 
center by a standard emergency service interface system meet- 
ing the requirements of NFPA 72. 

3007.7 Electrical power. The following features serving each 
fire service access elevator shall be supplied by both normal 
power and Type 60/Class 2/Level 1 standby power: 

1. Elevator equipment. 

2. Elevator hoistway lighting. 

3. Elevator machine room ventilation and cooling equip- 
ment. 

4. Elevator controller cooling equipment. 

3007.7.1 Protection of wiring or cables. Wires or cables 
that provide normal and standby power, control signals, 
communication with the car, lighting, heating, air condi- 
tioning' ventilation and fire-detecting systems to fire service 
access elevators shall be protected by construction having a 
minimum I-hour fire-resistance rating or shall be circuit 
integrity cable having a minimum I-hour fire-resistance 
rating. 



SECTION 3008 
OCCUPANT EVACUATION ELEVATORS 

3008.1 General. Where elevators are to be used for occupant 
self-evacuation during fires, all passenger elevators for general 
public use shall comply with this section. Where other eleva- 
tors are used for occupant self-evacuation, they shall also com- 
ply with this section. 

3008.2 Fire safety and evacuation plan. The building shall 
have an approvedfire safety and evacuation plan in accordance 
with the applicable requirements of Section 404 of the Interna- 
tional Fire Code. The fire safety and evacuation plan shall 
incorporate specific procedures for the occupants using evacu- 
ation elevators. 

3008.3 Operation. The occupant evacuation elevators shall be 
used for occupant self-evacuation only in the normal elevator 
operating mode prior to Phase I Emergency Recall Operation 
in accordance with the requirements in ASME A17.1/CSA 
B44 and the building's fire safety and evacuation plan. 

3008.4 Additional exit stairway. Where an additional means 
of egress is required in accordance with Section 403.5.2, an 
additional exit stairway shall not be required to be installed in 
buildings having elevators used for occupant self-evacuation in 
accordance with this section. 



3008.5 Emergency voice/alarm communication system. 
The building shall be provided with an emergency voice/alarm 
communication system. The emergency voice/alarm commu- 
nication system shall be accessible to the fire department. The 
system shall be provided in accordance with Section 907.5.2.2. 

3008.5.1 Notification appliances. A minimum of one audi- 
ble and one visible notification appliance shall be installed 
within each occupant evacuation elevator lobby. 

3008.6 Automatic sprinkler system. The building shall be 
protected throughout by an approved, electrically- supervised 
automatic sprinkler system in accordance with Section 
903.3.1.1, except as otherwise permitted by Section 
903.3.1.1.1 and as prohibited by Section 3008.6.1. 

3008.6.1 Prohibited locations. Automatic sprinklers shall 
not be installed in elevator machine rooms and elevator 
machine spaces for occupant evacuation elevators. 

3008.6.2 Sprinkler system monitoring. The sprinkler sys- 
tem shall have a sprinkler control valve supervisory switch 
and waterflow-initiating device provided for each floor that 
is monitored by the building's fire alarm system. 

3008.7 High-hazard content areas. No building areas shall 
contain high-hazard contents exceeding the maximum allow- 
able quantities per control area as addressed in Section 414.2. 

3008.8 Shunt trip. Means for elevator shutdown in accordance 
with Section 3006.5 shall not be installed on elevator systems 
used for occupant evacuation elevators. 

3008.9 Hoistway enclosure protection. The occupant evacua- 
tion elevators shall be located in hoistway enclosure(s) com- 
plying with Section 708. 

3008.10 Water protection. The occupant evacuation elevator 
hoistway shall be designed utilizing an approved method to 
prevent water from the operation of the automatic sprinkler 
system from infiltrating into the hoistway enclosure. 

3008.11 Occupant evacuation elevator lobby. The occupant 
evacuation elevators shall open into an elevator lobby in accor- 
dance with Sections 3008.11.1 through 3008.11.4. 

3008.11.1 Access. The occupant evacuation elevator lobby 
shall have direct access to an exit enclosure. 

3008.11.2 Lobby enclosure. The occupant evacuation ele- 
vator lobby shall be enclosed with a smoke barrierhaving a 
minimum I-hour fire-resistance rating, except that lobby 
doorways shall comply with Section 3008.11.5. 

Exception: Enclosed occupant evacuation elevator lob- 
bies are not required at the level(s) of exit discharge. 

3008.11.3 Lobby doorways. Each occupant evacuation 
elevator lobby shall be provided with a doorway that is pro- 
tected with a 3 A 
Section 715.4 



4 -hour fire door assembly complying with 



3008.11.3.1 Vision panel. A vision panel shall be 
installed in each fire door assembly protecting the lobby 
doorway. The vision panel shall consist of fire-protec- 
tion-rated glazing and shall be located to furnish clear 
vision of the occupant evacuation elevator lobby. 



556 



2009 INTERNATIONAL BUILDING CODE® 



ELEVATORS AND CONVEYING SYSTEMS 



3008.11.3.2 Door closing. Each fire door assembly ^pro- 
tecting the lobby doorway shall be automatic-closing 
upon receipt of any fire alarm signal from the emergency 
voice/alarm communication system serving the build- 
ing. 

3008.11.4 Lobby size. Each occupant evacuation elevator 
lobby shall have minimum floor area as follows : 

1. The occupant evacuation elevator lobby floor area 
shall accommodate, at 3 square feet (0.28 m 2 ) per per- 
son, a minimum of25 percent of the occupant loadof 
the floor area served by the lobby. 

2. The occupant evacuation elevator lobby floor area 
also shall accommodate one wheelchair space of 30 
inches by 48 inches (760 mm by 1220 mm) for each 
50 persons, or portion thereof , of the occupantloadof 
the floor area served by the lobby. 

Exception: The size of lobbies serving multiple 
banks of elevators shall have the minimum floor 
area approved on an individual basis and shall be 
consistent with the building's fire safety and evac- 
uation plan. 

3008.11.5 Signage. An approved sign indicating elevators 
are suitable for occupant self-evacuation shall be posted on 
all floors adjacent to each elevator call station serving occu- 
pant evacuation elevators. 

3008.12 Lobby status indicator. Each occupant evacuation 
elevator lobby shall be equipped with a status indicator 
arranged to display all of the following information: 

1. An illuminated green light and the message, "Elevators 
available for occupant evacuation" when the elevators 
are operating in normal service and the fire alarm system 
is indicating an alarm in the building. 

2. An illuminated red light and the message, "Elevators out 
of service, use exit stairs" when the elevators are in 
Phase I emergency recall operation in accordance with 
the requirements inASMEAl7.1/CSA B44. 

3. No illuminated light or message when the elevators are 
operating in normal service. 

3008.13 Two-way communication system. A two-way com- 
munication system shall be provided in each occupant evacua- 
tion elevator lobby for the purpose of initiating communication 
with the fire command center or an alternative location 
approvedby the fire department. 

3008.13.1 Design and installation. The two-way com- 
munication system shall include audible and visible sig- 
nals and shall be designed and installed in accordance 
with the requirements of ICC A 11 7.1. 

3008.13.2 Instructions. Instructions for the use of the 
two-way communication system along with the location 
of the station shall be permanently located adjacent to 
each station. Signage shall comply with the ICC A117.1 
requirements for visual characters. 

3008.14 Elevator system monitoring. The occupant evacua- 
tion elevators shall be continuously monitored at the fire com- 
mand center or a central control point approved by the fire 



department and arranged to display all of the following infor- 
mation: 

1. Floor location of each elevator car. 

2. Direction of travel of each elevator car. 

3. Status of each elevator car with respect to whether it is 
occupied. 

4. Status of normal power to the elevator equipment, eleva- 
tor controller cooling equipment, and elevator machine 
room ventilation and cooling equipment. 

5. Status of standby or emergency power system that pro- 
vides backup power to the elevator equipment, elevator 
controller cooling equipment, and elevator machine 
room ventilation and cooling equipment. 

6. Activation of any fire alarm-initiating device in any ele- 
vator lobby, elevator machine room or machine space, or 
elevator hoistway. 

3008.14.1 Elevator recall. The fire command center or an 
alternative location approvedby the fire department shall be 
provided with the means to manually initiate a Phase I 
Emergency Recall of the occupant evacuation elevators in 
accordance with ASME AI7.1/CSA B44. 

3008.15 Electrical power. The following features serving 
each occupant evacuation elevator shall be supplied by both 
normal power and Type 60/Class 2/Level 1 standby power: 

1. Elevator equipment. 

2. Elevator machine room ventilation and cooling equip- 
ment. 

3. Elevator controller cooling equipment. 

3008.15.1 Protection of wiring or cables. Wires or cables 
that provide normal and standby power, control signals, 
communication with the car, lighting, heating, air condi- 
tioning' ventilation and fire-detecting systems to occupant 
evacuation elevators shall be protected by construction hav- 
ing a minimum I-hour fire -resistance rating or shall be cir- 
cuit integrity cable having a minimum I-hour fire- 
resistance rating. 



2009 INTERNATIONAL BUILDING CODE® 



557 



558 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 31 

SPECIAL CONSTRUCTION 



I 



SECTION 3101 
GENERAL 

3101.1 Scope. The provisions of this chapter shall govern spe- 
cial building construction including membrane structures, 
temporary structures, pedestrian walkways and tunnels, auto- 
matic vehicular gates, awnings and canopies, marquees, signs, 
and towers and antennas. 



SECTION 3102 
MEMBRANE STRUCTURES 

3102.1 General. The provisions of this section shall apply to 
air-supported, air-inflated, membrane-covered cable and 
membrane-covered frame structures, collectively known as 
membrane structures, erected for a period of 180 days or lon- 
ger. Those erected for a shorter period of time shall comply 
with the International Fire Code. Membrane structures cover- 
ing water storage facilities, water clarifiers, water treatment 
plants, sewage treatment plants, greenhouses and similar facili- 
ties not used for human occupancy are required to meet only 
the requirements of Sections 3102.3.1 and 3102.7. Membrane 
structures erected on a building, balcony, deck or other struc- 
ture for any period of time shall comply with this section. 

3102.2 Definitions. The following words and terms shall, for 
the purposes of this section and as used elsewhere in this code, 
have the meanings shown herein. 

AIR-INFLATED STRUCTURE. A structure that uses 
air-pressurized membrane beams, arches or other elements to 
enclose space. Occupants of such a structure do not occupy the 
pressurized area used to support the structure. 

AIR-SUPPORTED STRUCTURE. A building wherein the 
shape of the structure is attained by air pressure and occupants 
of the structure are within the elevated pressure area. Air-sup- 
ported structures are of two basic types: 

Double skin. Similar to a single skin, but with an attached 
liner that is separated from the outer skin and provides an 
airspace which serves for insulation, acoustic, aesthetic or 
similar purposes. 

Single skin. Where there is only the single outer skin and 
the air pressure is directly against that skin. 

CABLE-RESTRAINED, AIR-SUPPORTED STRUC- 
TURE. A structure in which the uplift is resisted by cables or 
webbings which are anchored to either foundations or dead 
men. Reinforcing cable or webbing is attached by various 
methods to the membrane or is an integral part of the mem- 
brane. This is not a cable- supported structure. 

MEMBRANE-COVERED CABLE STRUCTURE. A 

nonpressurized structure in which a mast and cable system pro- 
vides support and tension to the membrane weather barrier and 
the membrane imparts stability to the structure. 



MEMBRANE-COVERED FRAME STRUCTURE. A 

nonpressurized building wherein the structure is composed of a 
rigid framework to support a tensioned membrane which pro- 
vides the weather barrier. 

NONCOMBUSTIBLE MEMBRANE STRUCTURE. A 
membrane structure in which the membrane and all component 
parts of the structure are noncombustible. 

3102.3 Type of construction. Noncombustible membrane 
structures shall be classified as Type 1IB construction. 
Noncombustible frame or cable-supported structures covered 
by an approved membrane in accordance with Section 
3102.3.1 shall be classified as Type LIB construction. Heavy 
timber frame- supported structures covered by an approved 
membrane in accordance with Section 3102.3.1 shall be classi- 
fied as Type IV construction. Other membrane structures shall 
be classified as Type V construction. 

Exception: Plastic less than 30 feet (9144 mm) above any 
floor used in greenhouses, where occupancy by the general 
public is not authorized, and for aquaculture pond covers is 
not required to meet the fire propagation performance crite- 
ria ofNFP A 701. 

3102.3.1 Membrane and interior liner material. Mem- 
branes and interior liners shall be either noncombustible as 
set forth in Section 703.4 or meet the fire propagation per- 
formance criteria of NFPA 701 and the manufacturer's test 
protocol. 

Exception: Plastic less than 20 mil (0.5 mm) in thickness 
used in greenhouses, where occupancy by the general 
public is not authorized, and for aquaculture pond covers 
is not required to meet the fire propagation performance 
criteria of NFPA 701. 

3102.4 Allowable floor areas. The area of a membrane struc- 
ture shall not exceed the limitations set forth in Table 503, 
except as provided in Section 506. 

3102.5 Maximum height. Membrane structures shall not 
exceed one story nor shall such structures exceed the height 
limitations in feet set forth in Table 503. 

Exception: Noncombustible membrane structures serving 
as roofs only. 

3102.6 Mixed construction. Membrane structures shall be 
permitted to be utilized as specified in this section as a portion 
of buildings of other types of construction. Height and area 
limits shall be as specified for the type of construction and 
occupancy of the building. 

3102.6.1 Noncombustible membrane. A noncombustible 
membrane shall be permitted for use as the roof or as a sky- 
light of any building or atrium of a building of any type of 
construction provided it is at least 20 feet (6096 mm) above 
any floor, balcony or gallery. 



2009 INTERNATIONAL BUILDING CODE® 



559 



SPECIAL CONSTRUCTION 



3102.6.1.1 Membrane. A membrane meeting the fire 
propagation performance criteria of NFPA 701 shall be 
permitted to be used as the roof or as a skylight on build- 
ings of Types 1IB, III, IV and V construction, provided it 
is at least 20 feet (6096 mm) above any floor, balcony or 
gallery. 

3102.7 Engineering design. The structure shall be designed 
and constructed to sustain dead loads; loads due to tension or 
inflation; live loads including wind, snow or flood and seismic 
loads and in accordance with Chapter 16. 

3102.8 Inflation systems. Air-supported and air-inflated 
structures shall be provided with primary and auxiliary infla- 
tion systems to meet the minimum requirements of Sections 
3102.8.1 through 3102.8.3. 

3102.8.1 Equipment requirements. This inflation system 
shall consist of one or more blowers and shall include provi- 
sions for automatic control to maintain the required infla- 
tion pressures. The system shall be so designed as to prevent 
overpressurization of the system. 

3102.8.1.1 Auxiliary inflation system. In addition to 
the primary inflation system, in buildings exceeding 
1,500 square feet (140 m 2 ) in area, an auxiliary inflation 
system shall be provided with sufficient capacity to 
maintain the inflation of the structure in case of primary 
system failure. The auxiliary inflation system shall oper- 
ate automatically when there is a loss of internal pressure 
and when the primary blower system becomes inopera- 
tive. 

3102.8.1.2 Blower equipment. Blower equipment shall 
meet all of the following requirements: 

1. Blowers shall be powered by continuous-rated 
motors at the maximum power required for any 
flow condition as required by the structural design. 

2. Blowers shall be provided with inlet screens, belt 
guards and other protective devices as required by 
the building official to provide protection from 
injury. 

3. Blowers shall be housed within a weather-protect- 
ing structure. 

4. Blowers shall be equipped with backdraft check 
dampers to minimize air loss when inoperative. 

5. Blower inlets shall be located to provide protection 
from air contamination. The location of inlets shall 
be approved. 

3102.8.2 Standby power. Wherever an auxiliary inflation 
system is required, an approved standby power-generating 
system shall be provided. The system shall be equipped with 
a suitable means for automatically starting the generator set 
upon failure of the normal electrical service and for auto- 
matic transfer and operation of all of the required electrical 
functions at full power within 60 seconds of such service 
failure. Standby power shall be capable of operating inde- 
pendently for a minimum of 4 hours. 

3102.8.3 Support provisions. A system capable of sup- 
porting the membrane in the event of deflation shall be pro- 
vided for in air- supported and air-inflated structures having 



an occupant load of 50 or more or where covering a swim- 
ming pool regardless of occupant load. The support system 
shall be capable of maintaining membrane structures used 
as a roof for Type I construction not less than 20 feet (6096 
mm) above floor or seating areas. The support system shall 
be capable of maintaining other membranes at least 7 feet 
(2134 mm) above the floor, seating area or surface of the 
water. 



SECTION 3103 
TEMPORARY STRUCTURES 

3103.1 General. The provisions of this section shall apply to 
structures erected for a period of less than 180 days. Tents and 
other membrane structures erected for a period of less than 180 
days shall comply with the International Fire Code. Those 
erected for a longer period of time shall comply with applicable 
sections of this code. 

3103.1.1 Permit required. Temporary structures that cover 
an area in excess of 120 square feet (11.16 m 2 ), including 
connecting areas or spaces with a common means of egress 
or entrance which are used or intended to be used for the 
gathering together of 10 or more persons, shall not be 
erected, operated or maintained for any purpose without 
obtaining a permit from the building official. 

3103.2 Construction documents. A permit application and 
construction documents shall be submitted for each installation 
of a temporary structure. The construction documents shall 
include a site plan indicating the location of the temporary 
structure and information delineating the means of egress and 
the occupant load. 

3103.3 Location. Temporary structures shall be located in 
accordance with the requirements of Table 602 based on the 
fire -resistance rating of the exterior walls for the proposed type 
of construction. 

3103.4 Means of egress. Temporary structures shall conform 
to the means of egress requirements of Chapter 10 and shall 
have a maximum exit access travel distance of 100 feet (30 480 
mm). 



SECTION 3104 
PEDESTRIAN WALKWAYS AND TUNNELS 

3104.1 General. This section shall apply to connections 
between buildings such as pedestrian walkways or tunnels, 
located at, above or below grade level, that are used as a means 
of travel by persons. The pedestrian walkway shall not contrib- 
ute to the bUilding area or the number of stories or height of 
connected buildings. 

3104.2 Separate structures. Connected buildings shall be 
considered to be separate structures. 

Exceptions: 

1. Buildings on the same lot in accordance with Section 
503.1.2. 

2. For purposes of calculating the number of Type B 
units required by Chapter 11, structurally connected 



560 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL CONSTRUCTION 



buildings and buildings with multiple wings shall be 
considered one structure. 

3104.3 Construction. The pedestrian walkway shall be of 
noncombustible construction. 

Exceptions: 

1. Combustible construction shall be permitted where 
connected buildings are of combustible construction. 

2. Fire-retardant-treated wood, in accordance with 
Section 603.1, Item 25.3, shall be permitted for the 
roof construction of the pedestrian walkway where 
connected buildings are a minimum of Type I or II 
construction. 

3104.4 Contents. Only materials and decorations approvedby 
the building officialshall be located in the pedestrian walkway. 

3104.5 Fire barriers between pedestrian walkways and 
buildings. Walkways shall be separated from the interior of the 
building by not less than 2-hour fire barriers constructed in 
accordance with Section 707 or horizontal assemblies con- 
structed in accordance with Section 712, or both. This protec- 
tion shall extend vertically from a point 10 feet (3048 mm) 
above the walkway roof surface or the connected building roof 
line, whichever is lower, down to a point 10 feet (3048 mm) 
below the walkway and horizontally 10 feet (3048 mm) from 
each side of the pedestrian walkway. Openings within the 
10- foot (3048 mm) horizontal extension of the protected walls 
beyond the walkway shall be equipped with devices providing 
a 3/4-hour fire protection ratingin accordance with Section 715. 

Exception: The walls separating the pedestrian walkway 
from a connected building and the openings within the 10- 
foot (3048 mm) horizontal extension of the protected walls 
beyond the walkway are not required to have a fire-resis- 
tance ratingby this section where any of the following con- 
ditions exist: 

1. The distance between the connected buildings is more 
than 10 feet (3048 mm). The pedestrian walkway and 
connected buildings, except for open parking 
garages, are equipped throughout with an automatic 
sprinkler system in accordance with Section 
903.3.1.1. The wall is capable of resisting the passage 
of smoke or is constructed of a tempered, wired or 
laminated glass wall and doors subject to the follow- 
ing: 

1.1. The wall or glass separating the interior of the 
building from the pedestrian walkway shall be 
protected by an automatic sprinkler system in 
accordance with Section 903.3.1.1 and the 
sprinkler system shall completely wet the en- 
tire surface of interior sides of the wall or glass 
when actuated; 

1.2. The glass shall be in a gasketed frame and in- 
stalled in such a manner that the framing sys- 
tem will deflect without breaking (loading) 
the glass before the sprinkler operates; and 

1.3. Obstructions shall not be installed between 
the sprinkler heads and the wall or glass. 



2. The distance between the connected buildings is more 
than 10 feet (3048 mm) and both sidewalls of the 
pedestrian walkway are at least 50 percent open with 
the open area uniformly distributed to prevent the 
accumulation of smoke and toxic gases. 

3. Buildings are on the same lot in accordance with Sec- 
tion 503.1.2. 

4. Where exterior walls of connected buildings are 
required by Section 705 to have a fire-resistance rat- 
ing greater than 2 hours, the walkway shall be 
equipped throughout with an automatic sprinkler sys- 
tem installed in accordance with Section 903.3.1.1. 

The previous exception shall apply to pedestrian walkways 
having a maximum height above grade of three stories or 40 
feet (12 192 mm), or five stories or 55 feet (16 764 mm) where 
sprinklered. 

3104.6 Public way. Pedestrian walkways over & public way 
shall also comply with Chapter 32. 

3104.7 Egress. Access shall be provided at all times to ^pedes- 
trian walkway that serves as a required exit. 

3104.8 Width. The unobstructed width of pedestrian walk- 
ways shall not be less than 36 inches (914 mm). The total width 
shall not exceed 30 feet (9144 mm). 

3104.9 Exit access travel. The length of exit access travel shall 
not exceed 200 feet (60 960 mm). 

Exceptions: 

1. Exit access travel distance on a pedestrian walkway 
equipped throughout with an automatic sprinkler sys- 
tem in accordance with Section 903.3.1.1 shall not 
exceed 250 feet (76 200 mm). 

2. Exit access travel distance on a pedestrian walkway 
constructed with both sides at least 50 percent open 
shall not exceed 300 feet (91 440 mm). 

3. Exit access travel distance on a pedestrian walkway 
constructed with both sides at least 50 percent open, 
and equipped throughout with an automatic sprinkler 
system in accordance with Section 903 .3 . 1.1, shall not 
exceed 400 feet (122 m). 

3104.10 Tunneled walkway. Separation between the tunneled 
walkway and the building to which it is connected shall not be 
less than 2-hour fire-resistant construction and openings 
therein shall be protected in accordance with Table 715.4. 



SECTION 3105 
AWNINGS AND CANOPIES 

3105.1 General. Awnings or canopies shall comply with the 
requirements of this section and other applicable sections of 
this code. 

3105.2 Definition. The following term shall, for the purposes 
of this section and as used elsewhere in this code, have the 
meaning shown herein. 

RETRACTABLE AWNING. A retractable awning is a cover 
with a frame that retracts against a building or other structure to 
which it is entirely supported. 



2009 INTERNATIONAL BUILDING CODE® 



561 



SPECIAL CONSTRUCTION 



3105.3 Design and construction. Awnings and canopies shall 
be designed and constructed to withstand wind or other lateral 
loads and live loads as required by Chapter 16 with due allow- 
ance for shape, open construction and similar features that 
relieve the pressures or loads. Structural members shall be pro- 
tected to prevent deterioration. Awnings shall have frames of 
noncombustible material, fire-retardant-treated wood, wood 
of Type IV size, or I-hour construction with combustible or 
noncombustible covers and shall be either fixed, retractable, 
folding or collapsible. 

3105.4 Canopy materials. Canopies shall be constructed of a 
rigid framework with an approved covering that meets the fire 
propagation performance criteria of NFPA 701 or has aflame 
spread index not greater than 25 when tested in accordance 
with ASTM E 84 or UL 723. 



SECTION 3106 
MARQUEES 

3106.1 General. Marquees shall comply with this section and 
other applicable sections of this code. 

3106.2 Thickness. The maximum height or thickness of a mar- 
quee measured vertically from its lowest to its highest point 
shall not exceed 3 feet (914 mm) where the marquee projects 
more than two-thirds of the distance from the property line to 
the curb line, and shall not exceed 9 feet (2743 mm) where the 
marquee is less than two-thirds of the distance from the prop- 
erty line to the curb line. 

3106.3 Roof construction. Where the roof or any part thereof 
is a skylight, the skylight shall comply with the requirements of 
Chapter 24. Every roof and skylight of a marquee shall be 
sloped to downspouts that shall conduct any drainage from the 
marquee in such a manner so as not to spill over the sidewalk. 

3106.4 Location prohibited. Every marquee shall be so 
located as not to interfere with the operation of any exterior 
standpipe, and such that the marquee does not obstruct the clear 
passage of stairways or exit discharge from the building or the 
installation or maintenance of street lighting. 

3106.5 Construction. A marquee shall be supported entirely 
from the building and constructed of noncombustible materi- 
als. Marquees shall be designed as required in Chapter 16. 
Structural members shall be protected to prevent deterioration. 



SECTION 3107 
SIGNS 

3107.1 General. Signs shall be designed, constructed and 
maintained in accordance with this code. 



SECTION 3108 

TELECOMMUNICATION AND 

BROADCAST TOWERS 

3108.1 General. Towers shall be designed and constructed in 
accordance with the provisions of TIA-222. 

Exception: Single free-standing poles used to support 
antennas not greater than 75 feet (22 860 mm), measured 



from the top of the pole to grade, shall not be required to be 
noncombustible. 

3108.2 Location and access. Towers shall be located such that 
guy wires and other accessories shall not cross or encroach 
upon any street or other public space, or over above-ground 
electric utility lines, or encroach upon any privately owned 
property without the written consent of the owner of the 
encroached-upon property, space or above-ground electric 
utility lines. Towers shall be equipped with climbing and work- 
ing facilities in compliance with TIA-222. Access to the tower 
sites shall be limited as required by applicable OSHA, FCC and 
EPA regulations. 



SECTION 3109 

SWIMMING POOL ENCLOSURES AND 

SAFETY DEVICES 

3109.1 General. Swimming pools shall comply with the 
requirements of this section and other applicable sections of 
this code. 

3109.2 Definition. The following word and term shall, for the 
purposes of this section and as used elsewhere in this code, 
have the meaning shown herein. 

SWIMMING POOLS. Any structure intended for swimming, 
recreational bathing or wading that contains water over 24 
inches (610 mm) deep. This includes in-ground, above-ground 
and on-ground pools; hot tubs; spas and fixed-in-place wading 
pools. 

3109.3 Public swimming pools. Public swimming pools shall 
be completely enclosed by a fence at least 4 feet (1290 mm) in 
height or a screen enclosure. Openings in the fence shall not 
permitthe passage of a 4-inch-diameter (102 mm) sphere. The 
fence or screen enclosure shall be equipped with self-closing 
and self-latching gates. 

3109.4 Residential swimming pools. Residential swimming 
pools shall comply with Sections 3109.4.1 through 3109.4.3. 

Exception: A swimming pool with a power safety cover or 
a spa with a safety cover complying with ASTM F 1346. 

3109.4.1 Barrier height and clearances. The top of the 
barrier shall be at least 48 inches (1219 mm) above grade 
measured on the side of the barrier that faces away from the 
swimming pool. The maximum vertical clearance between 
grade and the bottom of the barrier shall be 2 inches (51 
mm) measured on the side of the barrier that faces away 
from the swimming pool. Where the top of the pool struc- 
ture is above grade, the barrier is authorized to be at ground 
level or mounted on top of the pool structure, and the maxi- 
mum vertical clearance between the top of the pool structure 
and the bottom of the barrier shall be 4 inches (102 mm). 

3109.4.1.1 Openings. Openings in the barrier shall not 
allow passage of a 4-inch-diameter (102 mm) sphere. 

3109.4.1.2 Solid barrier surfaces. Solid barriers which 
do not have openings shall not contain indentations or 
protrusions except for normal construction tolerances 
and tooled masonry joints. 



562 



2009 INTERNATIONAL BUILDING CODE® 



SPECIAL CONSTRUCTION 



3109.4.1.3 Closely spaced horizontal members. 
Where the barrier is composed of horizontal and vertical 
members and the distance between the tops of the hori- 
zontal members is less than 45 inches (1143 mm), the 
horizontal members shall be located on the swimming 
pool side of the fence. Spacing between vertical mem- 
bers shall not exceed l 3 / 4 inches (44 mm) in width. 
Where there are decorative cutouts within vertical mem- 
bers, spacing within the cutouts shall not exceed l 3 / 4 
inches (44 mm) in width. 

3109.4.1.4 Widely spaced horizontal members. 
Where the barrier is composed of horizontal and vertical 
members and the distance between the tops of the hori- 
zontal members is 45 inches (1143 mm) or more, spacing 
between vertical members shall not exceed 4 inches (102 
mm). Where there are decorative cutouts within vertical 
members, spacing within the cutouts shall not exceed l 3 / 4 
inches (44 mm) in width. 

3109.4.1.5 Chain link dimensions. Maximum mesh 
size for chain link fences shall be a 2 l / 4 inch square (57 
mm square) unless the fence is provided with slats fas- 
tened at the top or the bottom which reduce the openings 
to no more than l 3 / 4 inches (44 mm). 

3109.4.1.6 Diagonal members. Where the barrier is 
composed of diagonal members, the maximum opening 
formed by the diagonal members shall be no more than 



located at 54 inches (1372 mm) maximum and 48 
inches (1219 mm) minimum above the threshold 
of the door. 

2. The pool shall be equipped with a power safety 
cover that complies with ASTM F 1346. 

3. Other means of protection, such as self-closing 
doors with self-latching devices, which are 
approved, shall be accepted so long as the degree 
of protection afforded is not less than the protec- 
tion afforded by Section 3109.4.1.8, Item 1 or 2. 

3109.4.1.9 Pool structure as barrier. Where an above- 
ground pool structure is used as a barrier or where the 
barrier is mounted on top of the pool structure, and the 
means of access is a ladder or steps, then the ladder or 
steps either shall be capable of being secured, locked or 
removed to prevent access, or the ladder or steps shall be 
surrounded by a barrier which meets the requirements of 
Sections 3109.4.1.1 through 3109.4.1.8. When the lad- 
der or steps are secured, locked or removed, any opening 
created shall not allow the passage of a 4-inch-diameter 
(102 mm) sphere. 

3109.4.2 Indoor swimming pools. Walls surrounding 
indoor swimming pools shall not be required to comply 
with Section 3109.4.1.8. 



3109.4.1.7 Gates. Access doors or gates shall comply 
with the requirements of Sections 3109.4.1.1 through 
3109.4.1.6 and shall be equipped to accommodate a 
locking device. Pedestrian access doors or gates shall 
open outward away from the pool and shall be self-clos- 
ing and have a self-latching device. Doors or gates other 
than pedestrian access doors or gates shall have a 
self-latching device. Release mechanisms shall be in 
accordance with Sections 1008.1.9 and 1109.12. Where 
the release mechanism of the self-latching device is 
located less than 54 inches (1372 mm) from the bottom 
of the door or gate, the release mechanism shall be 
located on the pool side of the door or gate at least 3 
inches (76 mm) below the top of the door or gate, and the 
door or gate and barrier shall have no opening greater 
than i/ 2 inch (12.7 mm) within 18 inches (457 mm) of the 
release mechanism. 

3109.4. 1.8 Dwelling wall as a barrier. Where a wall of a 
dwelling serves as part of the barrier, one of the following 
shall apply: 

1. Doors with direct access to the pool through that 
wall shall be equipped with an alarm that produces 
an audible warning when the door and/or its 
screen, if present, are opened. The alarm shall be 
listed and labeled in accordance with UL 201 7. In 
dwellings not required to be Accessible units, Type 
A units or Type B units, the deactivation switch 
shall be located 54 inches (1372 mm) or more 
above the threshold of the door. In dwellings 
required to be Accessible units, Type A units or 
Type B units, the deactivation switch(es) shall be 



3109.4.3 Prohibited locations. Barriers shall be located so 
as to prohibit permanent structures, equipment or similar 
objects from being used to climb the barriers. 

3109.5 Entrapment avoidance. Suction outlets shall 
designed and installed in accordance with ANSI/APSP-7. 



SECTION 3110 
AUTOMATIC VEHICULAR GATES 

3110.1 General. Automatic vehicular gates shall comply with 
the requirements of this section and other applicable sections of 
this code. 

31 10.2 Definitions. The following word and term shall, for the 
purposes of this section and as used elsewhere in this code, 
have the meaning shown herein. 

VEHICULAR GATE. A gate that is intended for use at a 
vehicular entrance or exit to a facility, building or portion 
thereof, and that is not intended for use by pedestrian traffic. 

3110.3 Vehicular gates intended for automation. Vehicular 
gates intended for automation shall be designed, constructed 
and installed to comply with the requirements of ASTM F 
2200. 

3110.4 Vehicular gate openers. Vehicular gate openers, when 
provided, shall be listed in accordance with UL 325. 



2009 INTERNATIONAL BUILDING CODE® 



563 



564 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 32 

ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY 



SECTION 3201 
GENERAL 

3201.1 Scope. The provisions of this chapter shall govern the 
encroachment of structures into the public right-of-way. 

3201.2 Measurement. The projection of any structure or por- 
tion thereof shall be the distance measured horizontally from 
the lot line to the outermost point of the projection. 

3201.3 Other laws. The provisions of this chapter shall not be 
construed to permit the violation of other laws or ordinances 
regulating the use and occupancy of public property. 

3201.4 Drainage. Drainage water collected from a roof, awn- 
ing, canopy or marquee, and condensate from mechanical 
equipment shall not flow over a public walking surface. 



SECTION 3202 
ENCROACHMENTS 

3202.1 Encroachments below grade. Encroachments below 
grade shall comply with Sections 3202.1.1 through 3202.1.3. 

3202.1.1 Structural support. A part of a building erected 
below grade that is necessary for structural support of the 
building or structure shall not project beyond the lot lines, 
except that the footings of street walls or their supports 
which are located at least 8 feet (2438 mm) below grade 
shall not project more than 12 inches (305 mm) beyond the 
street lot line. 

3202.1.2 Vaults and other enclosed spaces. The construc- 
tion and utilization of vaults and other enclosed spaces 
below grade shall be subject to the terms and conditions of 
the applicable governing authority. 

3202.1.3 Areaways. Areaways shall be protected by grates, 
guards or other approved means. 

3202.2 Encroachments above grade and below 8 feet in 
height. Encroachments into the public right-of-way above 
grade and below 8 feet (2438 mm) in height shall be prohibited 
except as provided for in Sections 3202.2.1 through 3202.2.3. 
Doors and windows shall not open or project into the public 
right-of-way. 

3202.2.1 Steps. Steps shall not project more than 12 inches 
(305 mm) and shall be guarded by approved devices not less 
than 3 feet (914 mm) high, or shall be located between col- 
umns or pilasters. 

3202.2.2 Architectural features. Columns or pilasters, 
including bases and moldings shall not project more than 12 
inches (305 mm). Belt courses, lintels, sills, architraves, 
pediments and similar architectural features shall not pro- 
ject more than 4 inches (102 mm). 

3202.2.3 Awnings. The vertical clearance from the public 
right-of-way to the lowest part of any awning, including 
valances, shall be 7 feet (2134 mm) minimum. 



3202.3 Encroachments 8 feet or more above grade. 
Encroachments 8 feet (2438 mm) or more above grade shall 
comply with Sections 3202.3.1 through 3202.3.4. 

3202.3.1 Awnings, canopies, marquees and signs. Awn- 
ings, canopies, marquees and signs shall be constructed so 
as to support applicable loads as specified in Chapter 16. 
Awnings, canopies, marquees and signs with less than 15 
feet (4572 mm) clearance above the sidewalk shall not 
extend into or occupy more than two-thirds the width of the 
sidewalk measured from the building. Stanchions or col- 
umns that support awnings, canopies, marquees and signs 
shall be located not less than 2 feet (610 mm) in from the 
curb line. 

3202.3.2 Windows, balconies, architectural features and 
mechanical equipment. Where the vertical clearance 
above grade to projecting windows, balconies, architectural 
features or mechanical equipment is more than 8 feet (2438 
mm), linch (25 mm) of encroachment is permitted for each 
additional 1 inch (25 mm) of clearance above 8 feet (2438 
mm), but the maximum encroachment shall be 4 feet (1219 
mm). 

3202.3.3 Encroachments 15 feet or more above grade. 
Encroachments 15 feet (4572 mm) or more above grade 
shall not be limited. 

3202.3.4 Pedestrian walkways. The installation of a 
pedestrian walkway over a public right-of-way shall be sub- 
ject to the approval of the applicable governing authority. 
The vertical clearance from the public right-of-way to the 
lowest part of a pedestrian walkway shall be 15 feet (4572 
mm) minimum. 

3202 .4 Temporary encroachments. Where allowed by the 
applicable governing authority, vestibules and storm enclo- 
sures shall not be erected for a period of time exceeding seven 
months in anyone year and shall not encroach more than 3 feet 
(914 mm) nor more than one-fourth of the width of the side- 
walk beyond the street lot line. Temporary entrance awnings 
shall be erected with a minimum clearance of 7 feet (2134 mm) 
to the lowest portion of the hood or awningwhere supported on 
removable steel or other approved noncombustible support. 



2009 INTERNATIONAL BUILDING CODE® 



565 



566 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 33 

SAFEGUARDS DURING CONSTRUCTION 



SECTION 3301 
GENERAL 

3301.1 Scope. The provisions of this chapter shall govern 
safety during construction and the protection of adjacent public 
and private properties. 

3301.2 Storage and placement. Construction equipment and 
materials shall be stored and placed so as not to endanger the 
public, the workers or adjoining property for the duration of the 
construction project. 



SECTION 3302 
CONSTRUCTION SAFEGUARDS 

3302.1 Remodeling and additions. Required exits, existing 
structural elements, fire protection devices and sanitary safe- 
guards shall be maintained at all times during remodeling, 
alterations, repairs or additions to any building or structure. 

Exceptions: 

1. When such required elements or devices are being 
remodeled, altered or repaired, adequate substitute 
provisions shall be made. 

2. When the existing building is not occupied. 

3302.2 Manner of removal. Waste materials shall be removed 
in a manner which prevents injury or damage to persons, 
adjoining properties and public rights-of-way. 



SECTION 3303 
DEMOLITION 

3303.1 Construction documents. Construction documents 
and a schedule for demolition must be submitted when 
required by the bUilding official. Where such information is 
required, no work shall be done until such construction docu- 
ments or schedule, or both, are approved. 

3303.2 Pedestrian protection. The work of demolishing any 
building shall not be commenced until pedestrian protection is 
in place as required by this chapter. 

3303.3 Means of egress. A party wall balcony or horizontal 
exitshall not be destroyed unless and until a substitute means of 
egress has been provided and approved. 

3303.4 Vacant lot. Where a structure has been demolished or 
removed, the vacant lot shall be filled and maintained to the 
existing grade or in accordance with the ordinances of thejuris- 
diction having authority. 

3303.5 Water accumulation. Provision shall be made to pre- 
vent the accumulation of water or damage to any foundations 
on the premises or the adjoining property. 



3303.6 Utility connections. Service utility connections shall 
be discontinued and capped in accordance with the approved 
rules and the requirements of the applicable governing author- 
ity. 



SECTION 3304 
SITE WORK 

3304.1 Excavation and fill. Excavation and fill for buildings 
and structures shall be constructed or protected so as not to 
endanger life or property. Stumps and roots shall be removed 
from the soil to a depth of at least 12 inches (305 mm) below the 
surface of the ground in the area to be occupied by the building. 
Wood forms which have been used in placing concrete, if 
within the ground or between foundation sills and the ground, 
shall be removed before a building is occupied or used for any 
purpose. Before completion, loose or casual wood shall be 
removed from direct contact with the ground under the build- 
ing. 

3304.1.1 Slope limits. Slopes for permanent fill shall not be 
steeper than one unit vertical in two units horizontal 
(50-percent slope). Cut slopes for permanent excavations 
shall not be steeper than one unit vertical in two units hori- 
zontal (50-percent slope). Deviation from the foregoing 
limitations for cut slopes shall be permitted only upon the 
presentation of a soil investigation report acceptable to the 
building official. 

3304.1.2 Surcharge. No fill or other surcharge loads shall 
be placed adjacent to any building or structure unless such 
building or structure is capable of withstanding the addi- 
tional loads caused by the fill or surcharge. Existing foot- 
ings or foundations which can be affected by any excavation 
shall be underpinned adequately or otherwise protected 
against settlement and shall be protected against later move- 
ment. 

3304.1.3 Footings on adjacent slopes. For footings on 
adjacent slopes, see Chapter 18. 

3304.1.4 Fill supporting foundations. Fill to be used to 
support the foundations of any building or structure shall 
comply with Section 1804.5. Special inspections of com- 
pacted fill shall be in accordance with Section 1704.7. 



SECTION 3305 
SANITARY 

3305.1 Facilities required. Sanitary facilities shall be pro- 
vided during construction, remodeling or demolition activities 
in accordance with the International Plumbing Code. 



2009 INTERNATIONAL BUILDING CODE® 



567 



SAFEGUARDS DURING CONSTRUCTION 



SECTION 3306 
PROTECTION OF PEDESTRIANS 

3306.1 Protection required. Pedestrians shall be protected 
during construction, remodeling and demolition activities as 
required by this chapter and Table 3306.1 . Signs shall be pro- 
vided to direct pedestrian traffic. 

3306.2 Walkways. A walkway shall be provided for pedes- 
trian travel in front of every construction and demolition site 
unless the applicable governing authority authorizes the side- 
walk to be fenced or closed. Walkways shall be of sufficient 
width to accommodate the pedestrian traffic, but in no case 
shall they be less than 4 feet (1219 mm) in width. Walkways 
shall be provided with a durable walking surface. Walkways 
shall be accessible in accordance with Chapter 11 and shall be 
designed to support all imposed loads and in no case shall the 
design live load be less than 150 pounds per square foot (psf) 
(7.2 kN/m 2 ). 

3306.3 Directional barricades. Pedestrian traffic shall be pro- 
tected by a directional barricade where the walkway extends 
into the street. The directional barricade shall be of sufficient 
size and construction to direct vehicular traffic away from the 
pedestrian path. 

3306.4 Construction railings. Construction railings shall be 
at least 42 inches (1067 mm) in height and shall be sufficient to 
direct pedestrians around construction areas. 

3306.5 Barriers. Barriers shall be a minimum of 8 feet (2438 
mm) in height and shall be placed on the side of the walkway 
nearest the construction. Barriers shall extend the entire length 
of the construction site. Openings in such barriers shall be pro- 
tected by doors which are normally kept closed. 

3306.6 Barrier design. Barriers shall be designed to resist 
loads required in Chapter 16 unless constructed as follows : 

1. Barriers shall be provided with 2-inch by 4-inch (51 mm 
by 102 mm) top and bottom plates. 

2. The barrier material shall be a minimum of 3 / 4 -inch (19.1 
mm) boards or i/ 4 -inch (6.4 mm) wood structural use 
panels. 

3. Wood structural use panels shall be bonded with an 
adhesive identical to that for exterior wood structural use 
panels. 



4. Wood structural use panels i/ 4 inch (6.4 mm) or 5/ 16 inch 
(23.8 mm) in thickness shall have studs spaced not more 
than 2 feet (610 mm) on center (o.c). 

5. Wood structural use panels 3/ 8 inch (9.5 mm) or i/ 2 inch 
(12.7 mm) in thickness shall have studs spaced not more 
than 4 feet (1219 mm) on center provided a 2-inch by 
4-inch (51 mm by 102 mm) stiff ener is placed horizon- 
tally at midheight where the stud spacing exceeds 2 feet 
(610 mm) o.c. 

6. Wood structural use panels 5/ s inch (15.9 mm) or thicker 
shall not span over 8 feet (2438 mm). 

3306.7 Covered walkways. Covered walkways shall have a 
minimum clear height of 8 feet (2438 mm) as measured from 
the floor surface to the canopy overhead. Adequate lighting 
shall be provided at all times. Covered walkways shall be 
designed to support all imposed loads. In no case shall the 
design live load be less than 150 psf (7.2 kN/m 2 ) for the entire 
structure. 

Exception: Roofs and supporting structures of covered 
walkways for new, light-frame construction not exceeding 
two stories above grade plane are permitted to be designed 
for a live load of 75 psf (3.6kN/m 2 ) or the loads imposed on 
them, whichever is greater. In lieu of such designs, the roof 
and supporting structure of a covered walkway are permit- 
ted to be constructed as follows: 

1. Footings shall be continuous 2-inch by 6- inch (51 mm 
by 152 mm) members. 

2. Posts not less than 4 inches by 6 inches (102 mm by 
152 mm) shall be provided on both sides of the roof 
and spaced not more than 12 feet (3658 mm) on cen- 
ter. 

3. Stringers not less than 4 inches by 12 inches (102 mm 
by 305 mm) shall be placed on edge upon the posts. 

4. Joists resting on the stringers shall be at least 2 inches 
by 8 inches (51 mm by 203 mm) and shall be spaced 
not more than 2 feet (610 mm) on center. 

5. The deck shall be planks at least 2 inches (51 mm) 
thick or wood structural panels with an exterior expo- 
sure durability classification at least 23 / 32 inch (18.3 
mm) thick nailed to the joists. 



TABLE 3306.1 
PROTECTION OF PEDESTRIANS 



HEIGHT OF 
CONSTRUCTION 


DISTANCE FROM CONSTRUCTION TO LOT LINE 


TYPE OF PROTECTION REQUIRED 


8 feet or less 


Less than 5 feet 


Construction railings 


5 feet or more 


None 


More than 8 feet 


Less than 5 feet 


Barrier and covered walkway 


5 feet or more, but not more than one-fourth the height of construction 


Barrier and covered walkway 


5 feet or more, but between one-fourth and one-half the height of construction 


Barrier 


5 feet or more, but exceeding one-half the height of construction 


None 



For 51: 1 foot =304.1 



568 



2009 INTERNATIONAL BUILDING CODE® 



SAFEGUARDS DURING CONSTRUCTION 



6. Each post shall be knee braced to joists and stringers 
by 2-inch by 4-inch (51 mm by 102 mm) minimum 
members 4 feet (1219 mm) long. 

7. A 2-inch by 4-inch (51 mm by 102 mm) minimum 
curb shall be set on edge along the outside edge of the 
deck. 

3306.8 Repair, maintenance and removal. Pedestrian protec- 
tion required by this chapter shall be maintained in place and 
kept in good order for the entire length of time pedestrians may 
be endangered. The owner or the owner's agent, upon the com- 
pletion of the construction activity, shall immediately remove 
walkways, debris and other obstructions and leave such public 
property in as good a condition as it was before such work was 
commenced. 

3306.9 Adjacent to excavations. Every excavation on a site 
located 5 feet (1524 mm) or less from the street lot line shall be 
enclosed with a barrier not less than 6 feet (1829 mm) high. 
Where located more than 5 feet (1524 mm) from the street lot 
line, a barrier shall be erected when required by the bUilding 
official. Barriers shall be of adequate strength to resist wind 
pressure as specified in Chapter 16. 



SECTION 3307 
PROTECTION OF ADJOINING PROPERTY 

3307.1 Protection required. Adjoining public and private 
property shall be protected from damage during construction, 
remodeling and demolition work. Protection must be provided 
for footings, foundations, party walls, chimneys, skylights and 
roofs. Provisions shall be made to control water runoff and ero- 
sion during construction or demolition activities. The person 
making or causing an excavation to be made shall provide writ- 
ten notice to the owners of adjoining buildings advising them 
that the excavation is to be made and that the adjoining build- 
ings should be protected. Said notification shall be delivered 
not less than 10 days prior to the scheduled starting date of the 
excavation. 



SECTION 3308 

TEMPORARY USE OF STREETS, ALLEYS AND 

PUBLIC PROPERTY 

3308.1 Storage and handling of materials. The temporary 
use of streets or public property for the storage or handling of 
materials or of equipment required for construction or demoli- 
tion' and the protection provided to the public shall comply 
with the provisions of the applicable governing authority and 
this chapter. 

3308.1.1 Obstructions. Construction materials and equip- 
ment shall not be placed or stored so as to obstruct access to 
fire hydrants, standpipes, fire or police alarm boxes, catch 
basins or manholes, nor shall such material or equipment be 
located within 20 feet (6096 mm) of a street intersection, or 
placed so as to obstruct normal observations of traffic sig- 
nals or to hinder the use of public transit loading platforms. 

3308.2 Utility fixtures. Building materials, fences, sheds or 
any obstruction of any kind shall not be placed so as to obstruct 
free approach to any fire hydrant, fire department connection, 



utility pole, manhole, fire alarm box or catch basin, or so as to 
interfere with the passage of water in the gutter. Protection 
against damage shall be provided to such utility fixtures during 
the progress of the work, but sight of them shall not be 
obstructed. 



SECTION 3309 
FIRE EXTINGUISHERS 

[F] 3309.1 Where required. All structures under construction, 
alteration or demolition shall be provided with not less than 
one approved portable fire extinguisher in accordance with 
Section 906 and sized for not less than ordinary hazard as fol- 
lows: 

1. At each stairway on all floor levels where combustible 
materials have accumulated. 

2. In every storage and construction shed. 

3. Additional portable fire extinguishers shall be provided 
where special hazards exist, such as the storage and use 
of flammable and combustible liquids. 

3309.2 Fire hazards. The provisions of this code and the Inter- 
national Fire Code shall be strictly observed to safeguard 
against all fire hazards attendant upon construction operations . 



SECTION 3310 
MEANS OF EGRESS 

3310.1 Stairways required. Where a building has been con- 
structed to a bUilding height of 50 feet (15 240 mm) or four sto- 
ries, or where an existing building exceeding 50 feet (15 240 
mm) in bUilding height is altered, at least one temporary lighted 
stairway shall be provided unless one or more of the permanent 
stairways are erected as the construction progresses. 

3310.2 Maintenance of means of egress. Required means of 
egress shall be maintained at all times during construction, 
demolition, remodeling or alterations and additions to any 
building. 

Exception: Approve d temporary means of egress systems 
and facilities. 



SECTION 3311 
STANDPIPES 

[F] 3311.1 Where required. In buildings required to have 
standpipes by Section 905.3.1, not less than one standpipe shall 
be provided for use during construction. Such standpipes shall 
be installed when the progress of construction is not more than 
40 feet (12 192 mm) in height above the lowest level of fire 
department vehicle access. Such standpipe shall be provided 
with fire department hose connections at accessible locations 
adjacent to usable stairs. Such standpipes shall be extended as 
construction progresses to within one floor of the highest point 
of construction having secured decking or flooring. 

[F] 3311.2 Buildings being demolished. Where a building is 
being demolished and a standpipe exists within such a build- 
ing, such standpipe shall be maintained in an operable condi- 
tion so as to be available for use by the fire department. Such 



2009 INTERNATIONAL BUILDING CODE® 



569 



SAFEGUARDS DURING CONSTRUCTION 



standpipe shall be demolished with the building but shall not be 
demolished more than one floor below the floor being demol- 
ished. 

3311.3 Detailed requirements. Standpipes shall be installed 
in accordance with the provisions of Chapter 9. 

Exception: Standpipes shall be either temporary or perma- 
nent in nature, and with or without a water supply, provided 
that such standpipes conform to the requirements of Section 
905 as to capacity, outlets and materials. 

3311.4 Water supply. Water supply for fire protection, either 
temporary or permanent, shall be made available as soon as 
combustible material accumulates. 



SECTION 3312 
AUTOMATIC SPRINKLER SYSTEM 

[F] 3312.1 Completion before occupancy. In buildings where 
an automatic sprinkler system is required by this code, it shall 
be unlawful to occupy any portion of a building or structure 
until the automatic sprinkler system installation has been tested 
and approved, except as provided in Section 111.3. 

[F] 3312.2 Operation of valves. Operation of sprinkler control 
valves shall be permitted only by properly authorized person- 
nel and shall be accompanied by notification of duly desig- 
nated parties. When the sprinkler protection is being regularly 
turned off and on to facilitate connection of newly completed 
segments, the sprinkler control valves shall be checked at the 
end of each work period to ascertain that protection is in ser- 
vice. 



570 2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 34 

EXISTING STRUCTURES 



SECTION 3401 
GENERAL 

3401.1 Scope. The provisions of this chapter shall control the 
alteration, repair, addition and change of occupancy of exist- 
ing structures. 

Exception: Existing bleachers, grandstands and folding 
and telescopic seating shall comply with ICC 300-02. 

3401.2 Maintenance. Buildings and structures, and parts 
thereof, shall be maintained in a safe and sanitary condition. 
Devices or safeguards which are required by this code shall be 
maintained in conformance with the code edition under which 
installed. The owner or the owner's designated agent shall be 
responsible for the maintenance of buildings and structures. To 
determine compliance with this subsection, the building offi- 
cial shall have the authority to require a building or structure to 
be reinspected. The requirements of this chapter shall not pro- 
vide the basis for removal or abrogation of fire protection and 
safety systems and devices in existing structures. 

3401.3 Compliance. Alterations, repairs, additions and 
changes of occupancy to existing structures shall comply with 
the provisions for alterations, repairs, additions and changes of 
occupancy in the International Fire Code, International Fuel 
Gas Code, International Mechanical Code, International 
Plumbing Code, International Property Maintenance Code, 
International Private Sewage Disposal Code, International 
Residential Code and NFPA 70. 

3401.4 Building materials. Building materials shall comply 
with the requirements of this section. 

3401.4.1 Existing materials. Materials already in use in a 
building in compliance with requirements or approvals in 
effect at the time of their erection or installation shall be per- 
mitted to remain in use unless determined by the building 
code official to be dangerous to life, health or safety. Where 
such conditions are determined to be dangerous to life, 
health or safety, they shall be mitigated or made safe. 

3401.4.2 New and replacement materials. Except as oth- 
erwise required or permitted by this code, materials permit- 
ted by the applicable code for new construction shall be 
used. Like materials shall be permitted for repairs and alter- 
ations, provided no hazard to life, health or property is cre- 
ated. Hazardous materials shall not be used where the code 
for new construction would not/?erraz7their use in buildings 
of similar occupancy, purpose and location. 

3401.4 Alternative compliance. Work performed in accor- 
dance with the International Existing Building Code shall be 
deemed to comply with the provisions of this chapter. 



SECTION 3402 
DEFINITIONS 

3402.1 Definitions. The following words and terms shall, for 
the purposes of this chapter and as used elsewhere in the code, 
have the meanings shown herein. 

DANGEROUS. Any building or structure or portion thereof 
that meets any of the conditions described below shall be 
deemed dangerous: 

1. The building or structure has collapsed, partially col- 
lapsed, moved off its foundation or lacks the support of 
ground necessary to support it. 

2. There exists a significant risk of collapse, detachment or dis- 
lodgment of any portion, member, appurtenance or orna- 
mentation of the building or structure under service loads. 

EXISTING STRUCTURE. A structure erected prior to the 
date of adoption of the appropriate code, or one for which a 
legal building permit has been issued. 

PRIMARY FUNCTION. A primary function is a major activ- 
ity for which the facility is intended. Areas that contain a pri- 
mary Junction include, but are not limited to, the customer 
service lobby of a bank, the dining area of a cafeteria, the meet- 
ing rooms in a conference center, as well as offices and other 
work areas in which the activities of the public accommodation 
or other private entity using the facility are carried out. Mechani- 
cal rooms, boiler rooms, supply storage rooms, employee 
lounges or locker rooms, janitorial closets, entrances, corridors 
and restrooms are not areas containing a primary function. 

SUBSTANTIAL STRUCTURAL DAMAGE. A condition where: 

1. In any story, the vertical elements of the lateral 
force-resisting system have suffered damage such that 
the lateral load-carrying capacity of the structure in any 
horizontal direction has been reduced by more than 20 
percent from its pre-damage condition; or 

2. The capacity of any vertical gravity load-carrying com- 
ponent' or any group of such components, that supports 
more than 30 percent of the total area of the structure's 
floor(s) and roof(s) has been reduced more than 20 per- 
cent from its pre-damage condition and the remaining 
capacity of such affected elements, with respect to all 
dead and live loads, is less than 75 percent of that 
required by this code for new buildings of similar struc- 
ture, purpose and location. 

TECHNICALLY INFEASIBLE. An alteration of a building 
or a facility that has little likelihood of being accomplished 
because the existing structural conditions require the removal 
or alteration of a load-bearing member that is an essential part 
of the structural frame, or because other existing physical or 
site constraints prohibit modification or addition of elements, 
spaces or features which are in full and strict compliance with 
the minimum requirements for new construction and which are 
necessary to provide accessibility. 



2009 INTERNATIONAL BUILDING CODE® 



571 



EXISTING STRUCTURES 



SECTION 3403 
ADDITIONS 

3403.1 General. Additions to any building or structure shall 
comply with the requirements of this code for new construc- 
tion. Alterations to the existing building or structure shall be 
made to ensure that the existing building or structure together 
with the addition are no less conforming with the provisions of 
this code than the existing building or structure was prior to the 
addition. An existing building together with its additions shall 
comply with the height and area provisions of Chapter 5. 

3403.2 Flood hazard areas. For buildings and structures in 
flood hazard areas established in Section 1612.3, any addition 
that constitutes substantial improvement of the existing struc- 
ture, as defined in Section 1612.2, shall comply with the flood 
design requirements for new construction, and all aspects of 
the existing structure shall be brought into compliance with the 
requirements for new construction for flood design. 

For buildings and structures in flood hazard areas estab- 
lished in Section 1612.3, any additions that do not constitute 
substantial improvement or substantial damage of the existing 
structure, as defined in Section 1612.2, are not required to 
comply with the flood design requirements for new construc- 
tion. 

3403.3 Existing structural elements carrying gravity load. 
Any existing gravity load -carrying structural element for 
which an addition and its related alterations cause an increase 
in design gravity load of more than 5 percent shall be strength- 
ened' supplemented, replaced or otherwise altered as needed to 
carry the increased load required by this code for new struc- 
tures. Any existing gravity load-carrying structural element 
whose gravity load-carrying capacity is decreased shall be con- 
sidered an altered element subject to the requirements of Sec- 
tion 3404.3. Any existing element that will form part of the 
lateral load path for any part of the addition shall be considered 
an existing lateral load-carrying structural element subject to 
the requirements of Section 3403.4. 

3403.3.1 Design live load. Where the addition does not 
result in increased design live load, existing gravity 
load-carrying structural elements shall be permitted to be 
evaluated and designed for live loads approved prior to the 
addition. If the approvedliw load is less than that required 
by Section 1607, the area designed for the nonconforming 
live load shall be posted with placards of approved design 
indicating the approvedlive load. Where the addition does 
result in increased design live load, the live load required by 
Section 1607 shall be used. 

3403.4 Existing structural elements carrying lateral load. 
Where the addition is structurally independent of the existing 
structure, existing lateral load -carrying structural elements 
shall be permitted to remain unaltered. Where the addition is 
not structurally independent of the existing structure, the exist- 
ing structure and its addition acting together as a single struc- 
ture shall be shown to meet the requirements of Sections 1609 
and 1613. 

Exception: Any existing lateral load-carrying structural 
element whose demand-capacity ratio with the addition 
considered is no more than 10 percent greater than its 
demand-capacity ratio with the addition ignored shall be 



permitted to remain unaltered. For purposes of calculating 
demand-capacity ratios, the demand shall consider applica- 
ble load combinations with design lateral loads or forces in 
accordance with Sections 1609 and 1613. For purposes of 
this exception, comparisons of demand-capacity ratios and 
calculation of design lateral loads, forces and capacities 
shall account for the cumulative effects of additions and 
alterations since original construction. 

3403.4.1 Seismic. Seismic requirements for alterations 
shall be in accordance with this section. Where the existing 
seismic force-resisting system is a type that can be desig- 
nated ordinary, values ofR, Q and Of for the existing seis- 
mic force-resisting system shall be those specified by this 
code for an ordinary system unless it is demonstrated that 
the existing system will provide performance equivalent to 
that of a detailed intermediate or special system. 



SECTION 3404 
ALTERATIONS 

3404.1 General. Except as provided by Section 3401.4 or this 
section, alterations to any building or structure shall comply 
with the requirements of the code for new construction. Alter- 
ations shall be such that the existing building or structure is no 
less complying with the provisions of this code than the exist- 
ing building or structure was prior to the alteration. 

Exceptions: 

1. An existing stairway shall not be required to comply 
with the requirements of Section 1009 where the 
existing space and construction does not allow a 
reduction in pitch or slope. 

2. Handrails otherwise required to comply with Section 
1009.12 shall not be required to comply with the 
requirements of Section 1012.6 regarding full exten- 
sion of the handrails where such extensions would be 
hazardous due to plan configuration. 

3404.2 Flood hazard areas. For buildings and structures in 
flood hazard areas established in Section 1612.3, any alter- 
ation that constitutes substantial improvement of the existing 
structure, as defined in Section 1612.2, shall comply with the 
flood design requirements for new construction, and all aspects 
of the existing structure shall be brought into compliance with 
the requirements for new construction for flood design. 

For buildings and structures in flood hazard areas estab- 
lished in Section 1612.3, any alterations that do not constitute 
substantial improvement or substantial damage of the existing 
structure, as defined in Section 1612.2, are not required to com- 
ply with the flood design requirements for new construction. 

3404.3 Existing structural elements carrying gravity load. 
Any existing gravity load -carrying structural element for 
which an alteration causes an increase in design gravity load of 
more than 5 percent shall be strengthened, supplemented, 
replaced or otherwise altered as needed to carry the increased 
gravity load required by this code for new structures. Any 
existing gravity load-carrying structural element whose grav- 
ity load-carrying capacity is decreased as part of the alteration 



572 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



shall be shown to have the capacity to resist the applicable 
design gravity loads required by this code for new structures. 

3404.3.1 Design live load. Where the alteration does not 
result in increased design live load, existing gravity 
load-carrying structural elements shall be permitted to be 
evaluated and designed for live loads approved prior to the 
alteration. If the approvedlive load is less than that required 
by Section 1607, the area designed for the nonconforming 
live load shall be posted with placards of approved design 
indicating the approvedlive load. Where the alteration does 
result in increased design live load, the live load required by 
Section 1607 shall be used. 

3404.4 Existing structural elements carrying lateral load. 
Except as permitted by Section 3404.5, where the alteration 
increases design lateral loads in accordance with Section 1609 
or 1613, or where the alteration results in a structural irregular- 
ity as defined in ASCE 7, or where the alteration decreases the 
capacity of any existing lateral load-carrying structural ele- 
ment, the structure of the altered building or structure shall be 
shown to meet the requirements of Sections 1609 and 1613. 

Exception: Any existing lateral load-carrying structural 
element whose demand-capacity ratio with the alteration 
considered is no more than 10 percent greater than its 
demand-capacity ratio with the alteration ignored shall be 
permitted to remain unaltered. For purposes of calculating 
demand-capacity ratios, the demand shall consider applica- 
ble load combinations with design lateral loads or forces per 
Sections 1609 and 1613. For purposes of this exception, 
comparisons of demand-capacity ratios and calculation of 
design lateral loads, forces, and capacities shall account for 
the cumulative effects of additions and alterations since 
original construction. 

3404.4.1 Seismic. Seismic requirements for alterations 
shall be in accordance with this section. Where the existing 
seismic force-resisting system is a type that can be desig- 
nated ordinary, values ofR, Q and Cd for the existing seis- 
mic force-resisting system shall be those specified by this 
code for an ordinary system unless it is demonstrated that 
the existing system will provide performance equivalent to 
that of a detailed intermediate or special system. 

3404.5 Voluntary seismic improvements. Alterations to 
existing structural elements or additions of new structural ele- 
ments that are not otherwise required by this chapter and are 
initiated for the purpose of improving the performance of the 
seismic force-resisting system of an existing structure or the 
performance of seismic bracing or anchorage of existing 
nonstructural elements shall be permitted, provided that an 
engineering analysis is submitted demonstrating the following: 

1. The altered structure and the altered nonstructural ele- 
ments are no less in compliance with the provisions of 
this code with respect to earthquake design than they 
were prior to the alteration. 

2. New structural elements are detailed and connected to 
the existing structural elements as required by Chapter 
16. 



3. New or relocated nonstructural elements are detailed and 
connected to existing or new structural elements as 
required by Chapter 16. 

4. The alterations do not create a structural irregularity as 
defined in ASCE 7 or make an existing structural irregu- 
larity more severe. 

3404.6 Means of egress capacity factors. Alterations to any 
existing building or structure shall not be affected by the egress 
width factors in Section 1005.1 for new construction in deter- 
mining the minimum egress widths or the minimum number of 
exits in an existing building or structure. The minimum egress 
widths for the components of the means of egress shall be based 
on the means of egress width factors in the building code under 
which the building was constructed, and shall be considered as 
complying means of egress for any alteration if, in the opinion 
of the building code official, they do not constitute a distinct 
hazard to life. 



SECTION 3405 
REPAIRS 

3405.1 General. Buildings and structures, and parts thereof, 
shall be repaired in compliance with Section 3401.2. Work on 
nondamaged components that is necessary for the required 
repair of damaged components shall be considered part of the 
repair and shall not be subject to the requirements for alter- 
ations in this chapter. Routine maintenance required by Section 
3401.2, ordinary repairs exempt from permit in accordance 
with Section 105.2, and abatement of wear due to normal ser- 
vice conditions shall not be subject to the requirements for 
repairs in this section. 

3405.1.1 Dangerous conditions. Regardless of the extent 
of structural or nonstructural damage, the building code 
official shall have the authority to require the elimination of 
conditions deemed dangerous. 

3405.2 Substantial structural damage to vertical elements 
of the lateral force-resisting system. A building that has sus- 
tained substantial structural damage to the vertical elements of 
its lateral force-resisting system shall be evaluated and repaired 
in accordance with the applicable provisions of Sections 
3405.2.1 through 3405.2.3. 

3405.2.1 Evaluation. The building shall be evaluated by a 
registered design professional, and the evaluation findings 
shall be submitted to the code official. The evaluation shall 
establish whether the damaged building, if repaired to its 
predamage state, would comply with the provisions of this 
code for wind and earthquake loads. Evaluation for earth- 
quake loads shall be required if the substantial structural 
damage was caused by or related to earthquake effects or if 
the building is in Seismic Design Category C, D, E or F. 

Wind loads for this evaluation shall be those prescribed in 
Section 1609. Earthquake loads for this evaluation, if 
required, shall be permitted to be 75 percent of those pre- 
scribed in Section 1613 . Values of R, Woand Cd fox the exist- 
ing seismic force-resisting system shall be those specified 
by this code for an ordinary system unless it is demonstrated 
that the existing system will provide performance equiva- 
lent to that of an intermediate or special system. 



2009 INTERNATIONAL BUILDING CODE® 



573 



EXISTING STRUCTURES 



3405.2.2 Extent of repair for compliant buildings. If the 
evaluation establishes compliance of the predamage build- 
ing in accordance with Section 3405.2.1, then repairs shall 
be permitted that restore the building to its predamage state 
using materials and strengths that existed prior to the dam- 
age. 

3405.2.3 Extent of repair for noncompliant buildings. If 
the evaluation does not establish compliance of the predam- 
age building in accordance with Section 3405.2.1, then the 
building shall be rehabilitated to comply with applicable 
provisions of this code for load combinations, including 
wind or seismic loads. The wind loads for the repair shall be 
as required by the building code in effect at the time of origi- 
nal construction, unless the damage was caused by wind, in 
which case the wind loads shall be as required by the code in 
effect at the time of original construction or as required by 
this code, whichever are greater. Earthquake loads for this 
rehabilitation design shall be those required for the design 
of the predamage building, but not less than 75 percent of 
those prescribed in Section 1613. New structural members 
and connections required by this rehabilitation design shall 
comply with the detailing provisions of this code for new 
buildings of similar structure, purpose and location. 

3405.3 Substantial structural damage to gravity load-car- 
rying components. Gravity load-carrying components that 
have sustained substantial structural damage shall be rehabili- 
tated to comply with the applicable provisions of this code for 
dead and live loads. Snow loads shall be considered if the sub- 
stantial structural damage was caused by or related to snow 
load effects. Existing gravity load-carrying structural elements 
shall be permitted to be designed for live loads approved prior 
to the damage. Nondamaged gravity load-carrying compo- 
nents that receive dead, live or snow loads from rehabilitated 
components shall also be rehabilitated or shown to have the 
capacity to carry the design loads of the rehabilitation design. 
New structural members and connections required by this 
rehabilitation design shall comply with the detailing provisions 
of this code for new buildings of similar structure, purpose and 
location. 

3405.3.1 Lateral force-resisting elements. Regardless of 
the level of damage to vertical elements of the lateral 
force-resisting system, if substantial structural damage to 
gravity load-carrying components was caused primarily by 
wind or earthquake effects, then the building shall be evalu- 
ated in accordance with Section 3405.2. 1 and, ifnoncompli- 
ant, rehabilitated in accordance with Section 3404.2.3. 

3405.4 Less than substantial structural damage. For dam- 
age less than substantial structural damage, repairs shall be 
allowed that restore the building to its predamage state using 
materials and strengths that existed prior to the damage. New 
structural members and connections used for this repair shall 
comply with the detailing provisions of this code for new build- 
ings of similar structure, purpose and location. 

3405.5 Flood hazard areas. For buildings and structures in 
flood hazard areas established in Section 1612.3, any repair 
that constitutes substantial improvement of the existing struc- 
ture, as defined in Section 1612.2, shall comply with the flood 
design requirements for new construction, and all aspects of 



the existing structure shall be brought into compliance with the 
requirements for new construction for flood design. 

For buildings and structures in flood hazard areas estab- 
lished in Section 1612.3, any repairs that do not constitute sub- 
stantial improvement or substantial damage of the existing 
structure, as defined in Section 1612.2, are not required to 
comply with the flood design requirements for new construc- 
tion. 



SECTION 3406 
FIRE ESCAPES 

3406.1 Where permitted. Fire escapes shall be permitted only 
as provided for in Sections 3406.1.1 through 3406.1.4. 

3406.1.1 New buildings. Fire escapes shall not constitute 
any part of the required means of egress in new buildings. 

3406.1.2 Existing fire escapes. Existing fire escapes shall 
be continued to be accepted as a component in the means of 
egress in existing buildings only. 

3406.1.3 New fire escapes. New fire escapes for existing 
buildings shall be permitted only where exterior stairs can- 
not be utilized due to lot lines limiting stairsize or due to the 
sidewalks, alleys or roads at grade level. New fire escapes 
shall not incorporate ladders or access by windows. 

3406.1.4 Limitations. Fire escapes shall comply with this 
section and shall not constitute more than 50 percent of the 
required number of exits nor more than 50 percent of the 
required exit capacity. 

3406.2 Location. Where located on the front of the building 
and where projecting beyond the building line, the lowest land- 
ing shall not be less than 7 feet (2134 mm) or more than 12 feet 
(3658 mm) above grade, and shall be equipped with a counter- 
balanced stairway to the street. In alleyways and thoroughfares 
less than 30 feet (9144 mm) wide, the clearance under the low- 
est landing shall not be less than 12 feet (3658 mm). 

3406.3 Construction. The fire escape shall be designed to sup- 
port a live load of 100 pounds per square foot (4788 Pa) and 
shall be constructed of steel or other a/?/?rov£<inoncombustible 
materials. Fire escapes constructed of wood not less than nomi- 
nal inches (51 mm) thick are permitted on buildings of Type 5 
construction. Walkways and railings located over or supported 
by combustible roofs in buildings of Type 3 and 4 construction 
are permitted to be of wood not less than nominal 2 inches (51 
mm) thick. 

3406.4 Dimensions. Stairs shall be at least 22 inches (559 mm) 
wide with risers not more than, and treads not less than, 8 
inches (203 mm) and landings at the foot of stairs not less than 
40 inches (1016 mm) wide by 36 inches (914 mm) long, 
located not more than 8 inches (203 mm) below the door. 

3406.5 Opening protectives. Doors and windows along the 
fire escape shall be protected with 3/4-hour opening protectives. 



574 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



SECTION 3407 
GLASS REPLACEMENT 

3407.1 Conformance. The installation or replacement of glass 
shall be as required for new installations. 



SECTION 3408 
CHANGE OF OCCUPANCY 

3408.1 Conformance. No change shall be made in the use or 
occupancy of any building that would place the building in a 
different division of the same group of occupancies or in a dif- 
ferent group of occupancies, unless such building is made to 
comply with the requirements of this code for such division or 
group of occupancies. Subject to the approval of the building 
official, the use or occupancy of existing buildings shall be per- 
mitted to be changed and the building is allowed to be occupied 
for purposes in other groups without conforming to all the 
requirements of this code for those groups, provided the new or 
proposed use is less hazardous, based on life and fire risk, than 
the existing use. 

3408.2 Certificate of occupancy. A certificate of occupancy 
shall be issued where it has been determined that the require- 
ments for the new occupancy classification have been met. 

3408.3 Stairways. Existing stairways in an existing structure 
shall not be required to comply with the requirements of a new 
stairway as outlined in Section 1009 where the existing space 
and construction will not allow a reduction in pitch or slope. 

3408.4 Change of occupancy. When a change of occupancy 
results in a structure being reclassified to a higher occupancy 
category, the structure shall conform to the seismic require- 
ments for a new structure of the higher occupancy category. 
Where the existing seismic force-resisting system is a type that 
can be designated ordinary, values of R, Q^and Cd fox the exist- 
ing seismic force-resisting system shall be those specified by 
this code for an ordinary system unless it is demonstrated that 
the existing system will provide performance equivalent to that 
of a detailed, intermediate or special system. 

Exceptions: 

1. Specific seismic detailing requirements of this code 
or Section 1613 for a new structure shall not be 
required to be met where it can be shown that the level 
of performance and seismic safety is equivalent to 
that of a new structure. Such analysis shall consider 
the regularity, over strength, redundancy and ductility 
of the structure within the context of the existing and 
retrofit (if any) detailing provided. 

2. When a change of use results in a structure being 
reclassified from Occupancy Category I or II to Occu- 
pancy Category III and the structure is located in a 
seismic map area where sds< 0.33, compliance with 
the seismic requirements of this code and Section 
1613 are not required. 



SECTION 3409 
HISTORIC BUILDINGS 

3409.1 Historic buildings. The provisions of this code relating 
to the construction, repair, alteration, addition, restoration and 
movement of structures, and change of occupancy shall not be 
mandatory for historic buildings where such buildings are 
judged by the building official to not constitute a distinct life 
safety hazard. 

3409.2 Flood hazard areas. Within flood hazard areas estab- 
lished in accordance with Section 1612.3, where the work pro- 
posed constitutes substantial improvement as defined in 
Section 1612.2, the building shall be brought into compliance 
with Section 1612. 

Exception: Historic buildings that are: 

1. Listed or preliminarily determined to be eligible for 
listing in the National Register of Historic Places; 

2. Determined by the Secretary of the U.S. Department 
of Interior as contributing to the historical signifi- 
cance of a registered historic district or a district pre- 
liminarily determined to qualify as an historic district; 
or 

3. Designated as historic under a state or local historic 
preservation program that is approvedby the Depart- 
ment of Interior. 



SECTION 3410 
MOVED STRUCTURES 

3410.1 Conformance. Structures moved into or within the 
jurisdiction shall comply with the provisions of this code for 
new structures. 



SECTION 3411 
ACCESSIBILITY FOR EXISTING BUILDINGS 

3411.1 Scope. The provisions of Sections 3411.1 through 
3411.9 apply to maintenance, change of occupancy, additions 
and alterations to existing buildings, including those identified 
as historic buildings. 

Exception: Type B dwelling or sleeping units required by 
Section 1107 of this code are not required to be provided in 
existing buildings and facilities being altered or undergoing 
a change of occupancy. 

3411.2 Maintenance of facilities. A building, facility or ele- 
ment that is constructed or altered to be accessible shall be 
maintained accessible during occupancy. 

341 1.3 Extent of application. An alteration of an existing ele- 
ment, space or area of a building or facility shall not impose a 
requirement for greater accessibility than that which would be 
required for new construction. 

Alterations shall not reduce or have the effect of reducing 
accessibility of a building, portion of a building or facility. 



2009 INTERNATIONAL BUILDING CODE® 



575 



EXISTING STRUCTURES 



3411.4 Change of occupancy. Existing buildings that undergo 
a change of group or occupancy shall comply with this section. 

3411.4.1 Partial change in occupancy. Where a portion of 
the building is changed to a new occupancy classification, 
any alterations shall comply with Sections 3411.6, 3411 .7 
and 3411.8. 

3411.4.2 Complete change of occupancy. Where an entire 
building undergoes a change of occupancy, it shall comply 
with Section 3411.4.1 and shall have all of the following 
accessible features: 

1. At least one accessible building entrance. 

2. At least one accessible route from an accessible 
building entrance to primary function areas. 

3. Signage complying with Section 1110. 

4. Accessible parking, where parking is being provided. 

5. At least one accessible passenger loading zone, when 
loading zones are provided. 

6. At least one accessible route connecting accessible 
parking and accessible passenger loading zones to an 
accessible entrance. 

Where it is technically infeasible to comply with the new 
construction standards for any of these requirements for a 
change of group or occupancy, the above items shall con- 
form to the requirements to the maximum extent technically 
feasible. 

3411.5 Additions. Provisions for new construction shall apply 
to additions. An addition that affects the accessibility to, or 
contains an area of, a primary function shall comply with the 
requirements in Section 3411.7. 

3411.6 Alterations. A building, facility or element that is 
altered shall comply with the applicable provisions in Chapter 
11 of this code and ICC A117.1, unless technically infeasible. 
Where compliance with this section is technically infeasible, 
the alteration shall provide access to the maximum extent tech- 
nically feasible. 

Exceptions: 

1. The altered element or space is not required to be on 
an accessible route, unless required by Section 
3411.7. 

2. Accessiblemeans of egress required by Chapter 10 are 
not required to be provided in existing buildings and 
facilities. 

3. The alteration to Type A individually owned dwelling 
units within a Group R-2 occupancy shall meet the 
provision for a Type B dwelling unit and shall comply 
with the applicable provisions in Chapter 11 and ICC 
A117.1. 

3411.7 Alterations affecting an area containing a primary 
function. Where an alteration affects the accessibility to, or 
contains an area of primary function, the route to the primary 
function area shall be accessible. The accessible route to the 



primary function area shall include toilet facilities or drinking 
fountains serving the area of primary function. 

Exceptions: 

1. The costs of providing the accessible route are not 
required to exceed 20 percent of the costs of the alter- 
ations affecting the area of primary function. 

2. This provision does not apply to alterations limited 
solely to windows, hardware, operating controls, 
electrical outlets and signs. 

3. This provision does not apply to alterations limited 
solely to mechanical systems, electrical systems, 
installation or alteration of fire protection systems 
and abatement of hazardous materials. 

4. This provision does not apply to alterations under- 
taken for the primary purpose of increasing the acces- 
sibility of an existing building, facility or element. 

3411.8 Scoping for alterations. The provisions of Sections 
3411.8.1 through 3411.8.14 shall apply to alterations to exist- 
ing buildings and facilities. 

341 1.8.1 Entrances. Accessible entrances shall be provided 
in accordance with Section 1105. 

Exception: Where an alteration includes alterations to 
an entrance, and the building or facility has an accessible 
entrance, the altered entrance is not required to be acces- 
sible, unless required by Section 3411.7. Signs comply- 
ing with Section 1110 shall be provided. 

3411.8.2 Elevators. Altered elements of existing elevators 
shall comply with ASMEA17.1 and ICC A117.1. Such ele- 
ments shall also be altered in elevators programmed to 
respond to the same hall call control as the altered elevator. 

3411.8.3 Platform lifts. Platform (wheelchair) lifts com- 
plying with ICC All 7.1 and installed in accordance with 
ASME A18.1 shall be permitted as a component of an 
accessible route. 

3411.8.4 Stairs and escalators in existing buildings. In 
alterations, change of occupancy or additions where an 
escalator or stair is added where none existed previously 
and major structural modifications are necessary for instal- 
lation, an accessible route shall be provided between the 
levels served by the escalator or stairs in accordance with 
Sections 1104.4 and 1104.5. 

3411.8.5 Ramps. Where slopes steeper than allowed by 
Section 1010.2 are necessitated by space limitations, the 
slope of ramps in or providing access to existing buildings 
or facilities shall comply with Table 3411.8.5. 

TABLE 3411.8.5 
RAMPS 



SLOPE 


MAXIMUM RISE 


Steeper than 1: 10 but not steeper than 1:8 


3 inches 


Steeper than 1: 12 but not steeper than 1: 10 


6 inches 



For 51: 1 inch = 25.4 mini. 



576 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



3411.8.6 Performance areas. Where it is technically infea- 
sible to alter performance areas to be on an accessible route, 
at least one of each type of performance area shall be made 
accessible. 

3411.8.7 Accessible dwelling or sleeping units. Where 
Group 1-1, 1-2, 1-3, R-l, R-2 or R-4 dwelling or sleeping 
units are being altered or added, the requirements of Section 
1107 for Accessible units apply only to the quantity of 
spaces being altered or added. 

3411.8.8 Type A dwelling or sleeping units. Where more 
than 20 Group R-2 dwelling or sleeping units are being 
added, the requirements of Section 1107 for Type A units 
apply only to the quantity of the spaces being added. 

341 1.8.9 Type B dwelling or sleeping units. Where four or 
more Group 1-1,1-2, R-l, R-2, R-3 or R-4 dwellingor sleep- 
ing units are being added, the requirements of Section 1107 
for Type B units apply only to the quantity of the spaces 
being added. 

3411.8.10 Jury boxes and witness stands. In alterations, 
accessible wheelchair spaces are not required to be located 
within the defined area of raised jury boxes or witness 
stands and shall be permitted to be located outside these 
spaces where the ramp or lift access restricts or projects into 
the means of egress. 

3411.8.11 Toilet rooms. Where it is technically infeasible 
to alter existing toilet and bathing facilities to be accessible, 
an accessible family or assisted-use toilet or bathing facility 
constructed in accordance with Section 1109.2.1 is permit- 
ted. The family or assisted-use facility shall be located on 
the same floor and in the same area as the existing facilities. 

3411.8.12 Dressing, fitting and locker rooms. Where it is 
technically infeasible to provide accessible dressing, fitting 
or locker rooms at the same location as similar types of 
rooms, one accessible room on the same level shall be pro- 
vided. Where separate- sex facilities are provided, accessi- 
ble rooms for each sex shall be provided. Separate-sex 
facilities are not required where only unisex rooms are pro- 
vided. 

3411.8.13 Fuel dispensers. Operable parts of replacement 
fuel dispensers shall be permitted to be 54 inches (1370 
mm) maximum measured from the surface of the vehicular 
way where fuel dispensers are installed on existing curbs. 

3411.8.14 Thresholds. The maximum height of thresholds 
at doorways shall be 3/ 4 inch (19.1 mm). Such thresholds 
shall have beveled edges on each side. 

3411.9 Historic buildings. These provisions shall apply to 
buildings and facilities designated as historic structures that 
undergo alterations or a change of occupancy, unless techni- 
cally infeasible. Where compliance with the requirements for 
accessible routes, entrances or toilet facilities would threaten 
or destroy the historic significance of the building or facility, as 
determined by the applicable governing authority, the alterna- 
tive requirements of Sections 3411.9.1 through 3411.9.4 for 
that element shall be permitted. 



3411.9.1 Site arrival points. At least one accessible route 
from a site arrival point to an accessible entrance shall be 
provided. 

3411.9.2 Multilevel buildings and facilities. An accessi- 
bleroute from an accessible entrance to public spaces on the 
level of the accessible entrance shall be provided. 

3411.9.3 Entrances. At least one main entrance shall be 
accessible. 

Exceptions: 

1. If a main entrance cannot be made accessible, an 
accessible nonpublic entrance that is unlocked 
while the building is occupied shall be provided; or 

2. If a main entrance cannot be made accessible, a. 
locked accessible entrance with a notification sys- 
tem or remote monitoring shall be provided. 

Signs complying with Section 1110 shall be provided at 
the primary entrance and the accessible entrance. 

3411.9.4 Toilet and bathing facilities. Where toilet rooms 
are provided, at least one accessible family or assisted-use 
toilet room complying with Section 1109.2.1 shall be pro- 
vided. 



SECTION 3412 
COMPLIANCE ALTERNATIVES 

3412.1 Compliance. The provisions of this section are 
intended to maintain or increase the current degree of public 
safety, health and general welfare in existing buildings while 
permitting repair, alteration, addition and change of occu- 
pancy without requiring full compliance with Chapters 2 
through 33, or Sections 3401.3, and 3403 through 3409, except 
where compliance with other provisions of this code is specifi- 
cally required in this section. 

3412.2 Applicability. Structures existing prior to [DATE TO BE 
INSERTED BY THE JURISDICTION. NOTE: IT IS RECOMMENDED 
THAT THIS DATE COINCIDE WITH THE EFFECTIVE DATE OF BUILD- 
ING CODES WITHIN THE JURISDICTION], in which there is work 
involving additions, alterations or changes of occupancy shall 
be made to comply with the requirements of this section or the 
provisions of Sections 3403 through 3409. The provisions in 
Sections 3412.2.1 through 3412.2.5 shall apply to existing 
occupancies that will continue to be, or are proposed to be, in 
Groups A, B, E, F, M, R, Sand U. These provisions shall not 
apply to buildings with occupancies in Group H or I. 

3412.2.1 Change in occupancy. Where an existing build- 
ing is changed to a new occupancy classification and this 
section is applicable, the provisions of this section for the 
new occupancy shall be used to determine compliance with 
this code. 

3412.2.2 Partial change in occupancy. Where a portion of 
the building is changed to a new occupancy classification, 
and that portion is separated from the remainder of the 
building with fire barriers or horizontal assemblies having a 
fire-resistance rating as required by Table 508.4 for the sep- 
arate occupancies, or with approved compliance alterna- 



2009 INTERNATIONAL BUILDING CODE® 



577 



EXISTING STRUCTURES 



tives, the portion changed shall be made to comply with the 
provisions of this section. 

Where a portion of the building is changed to a new occu- 
pancy classification, and that portion is not separated from 
the remainder of the building with fire barriers or horizontal 
assemblies having a fire-resistance rating as required by 
Table 508.4 for the separate occupancies, or with approved 
compliance alternatives, the provisions of this section 
which apply to each occupancy shall apply to the entire 
building. Where there are conflicting provisions, those 
requirements which secure the greater public safety shall 
apply to the entire building or structure. 

3412.2.3 Additions. Additions to existing buildings shall 
comply with the requirements of this code for new construc- 
tion. The combined height and area of the existing building 
and the new addition shall not exceed the height and area 
allowed by Chapter 5. Where afire wa//that complies with 
Section 706 is provided between the addition and the exist- 
ing building, the addition shall be considered a separate 
building. 

3412.2.4 Alterations and repairs. An existing building or 
portion thereof, which does not comply with the require- 
ments of this code for new construction, shall not be altered 
or repaired in such a manner that results in the building 
being less safe or sanitary than such building is currently. If, 
in the alteration or repair, the current level of safety or sani- 
tation is to be reduced, the portion altered or repaired shall 
conform to the requirements of Chapters 2 through 12 and 
Chapters 14 through 33. 

3412.2.4.1 Flood hazard areas. For existing buildings 
located in flood hazard areas established in Section 
1612.3, if the alterations and repairs constitute substan- 
tial improvement of the existing building, the existing 
building shall be brought into compliance with the 
requirements for new construction for flood design. 

3412.2.5 Accessibility requirements. All portions of the 
buildings proposed for change of occupancy shall conform 
to the accessibility provisions of Section 3411. 

3412.3 Acceptance. For repairs, alterations, additions and 
changes of occupancy to existing buildings that are evaluated 
in accordance with this section, compliance with this section 
shall be accepted by the building official. 

3412.3.1 Hazards. Where the building official determines 
that an unsafe condition exists, as provided for in Section 
116, such unsafe condition shall be abated in accordance 
with Section 116. 

3412.3.2 Compliance with other codes. Buildings that are 
evaluated in accordance with this section shall comply with 
the International Fire Code and the International Property 
Maintenance Code. 

3412.4 Investigation and evaluation. For proposed work cov- 
ered by this section, the building owner shall cause the existing 
building to be investigated and evaluated in accordance with 
the provisions of this section. 

3412.4.1 Structural analysis. The owner shall have a struc- 
tural analysis of the existing building made to determine 



adequacy of structural systems for the proposed alteration, 
addition or change of occupancy. The analysis shall demon- 
strate that the building with the work completed is capable 
of resisting the loads specified in Chapter 16. 

3412.4.2 Submittal. The results of the investigation and 
evaluation as required in Section 3412.4, along with pro- 
posed compliance alternatives, shall be submitted to the 
building official. 

3412.4.3 Determination of compliance. The building offi- 
cial shall determine whether the existing building, with the 
proposed addition, alteration or change of occupancy, com- 
plies with the provisions of this section in accordance with 
the evaluation process in Sections 3412.5 through 3412.9. 

3412.5 Evaluation. The evaluation shall be comprised of three 
categories: fire safety, means of egress and general safety, as 
defined in Sections 3412.5.1 through 3412.5.3. 

3412.5.1 Fire safety. Included within the fire safety cate- 
gory are the structural fire resistance, automatic fire detec- 
tion, fire alarm and fire suppression system features of the 
facility. 

3412.5.2 Means of egress. Included within the means of 
egress category are the configuration, characteristics and 
support features for means of egress in the facility. 

3412.5.3 General safety. Included within the general safety 
category are the fire safety parameters and the means of 
egress parameters. 

3412.6 Evaluation process. The evaluation process specified 
herein shall be followed in its entirety to evaluate existing 
buildings. Table 3412.7 shall be utilized for tabulating the 
results of the evaluation. References to other sections of this 
code indicate that compliance with those sections is required in 
order to gain credit in the evaluation herein outlined. In apply- 
ing this section to a building with mixed occupancies, where 
the separation between the mixed occupancies does not qualify 
for any category indicated in Section 3412.6.16, the score for 
each occupancy shall be determined and the lower score deter- 
mined for each section of the evaluation process shall apply to 
the entire building. 

Where the separation between mixed occupancies qualifies 
for any category indicated in Section 3412.6.16, the score for 
each occupancy shall apply to each portion of the building 
based on the occupancy of the space. 

3412.6.1 Building height. The value for building height 
shall be the lesser value determined by the formula in Sec- 
tion 3412.6.1.1. Chapter 5 shall be used to determine the 
allowable height of the building, including allowable 
increases due to automatic sprinklers as provided for in Sec- 
tion 504.2. Subtract the actual building height in feet from 
the allowable and divide by 12 i/ 2 feet. Enter the height value 
and its sign (positive or negative) in Table 3412.7 under 
Safety Parameter 3412.6.1, Building Height, for fire safety, 
means of egress and general safety. The maximum score for 
a building shall be 10. 

3412.6.1.1 Height formula. The following formulas 
shall be used in computing the building height value. 



i 



578 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



Height value, feet: 



(AH)-(EBH) 



CF 



12.5 



Height value, stories =(AS - 



where: 



EBS) x CF 

(Equation 34-1) 



AH = Allowable height in feet from Table 503. 

EBH= Existing building height in feet. 

AS Allowable height in stories from Table 503. 

EBS = Existing building height in stories. 

CF 1 if {AH) - (EBI!) is positive. 

CF Construction-type factor shown in Table 

3412.6.6(2) if (AH) - (EBI!) is negative. 

Note: Where mixed occupancies are separated and indi- 
vidually evaluated as indicated in Section 3412.6, the 
values AH, AS, EBH and EBS shall be based on the 
height of the occupancy being evaluated. 

3412.6.2 Building area. The value for building area shall be 
determined by the formula in Section 3412.6.2.2. Section 
503 and the formula in Section 3412.6.2.1 shall be used to 
determine the allowable area of the building. This shall 
include any allowable increases due to frontage and auto- 
matic sprinklers as provided for in Section 506. Subtract the 
actual building area in square feet from the allowable area 
and divide by 1,200 square feet. Enter the area value and its 
sign (positive or negative) in Table 3412.7 under Safety 
Parameter 3412.6.2, Building Area, for fire safety, means of 
egress and general safety. In determining the area value, the 
maximum permitted positive value for area is 50 percent of 
the fire safety score as listed in Table 3412.8, Mandatory 
Safety Scores. 

3412.6.2.1 Allowable area formula. The following for- 
mula shall be used in computing allowable area: 



4=(i+i /+ yx4 

where: 

A n = Allowable area. 



(Equation 34-2) 



At Tabular area per story in accordance with Table 
503 (square feet) 

Is Area increase factor for sprinklers (Section 

506.3). 

If = Area increase factor for frontage (Section 506.2). 

3412.6.2.2 Area formula. The following formula shall 
be used in computing the area value. Determine the area 
value for each occupancy floor area on a floor-by-floor 
basis. For each occupancy, choose the minimum area 
value of the set of values obtained for the particular occu- 
pancy. 



Area value / = 



A%g#ible [ 
i 1 

1,200 square feet 



[ Ac^a 1 . Afi&al ] ] 

i +...+ n 

Allowable Allowable 

area j area n 



(Equation 34-3) 



where: 

i = Value for an individual separated occupancy on a 
floor. 

n = Number of separated occupancies on a floor. 

3412.6.3 Compartmentation. Evaluate the compartments 
created by fire barriers or horizontal assemblies which 
comply with Sections 3412.6.3.1 and 3412.6.3.2 and which 
are exclusive of the wall elements considered under Sec- 
tions 3412.6.4 and 3412.6.5. Conforming compartments 
shall be figured as the net area and do not include shafts, 
chases, stairways, walls or columns. Using Table 3412.6.3, 
determine the appropriate compartmentation value (CV) 
and enter that value into Table 3412.7 under Safety Parame- 
ter 3412.6.3, Compartmentation, for fire safety, means of 
egress and general safety. 

3412.6.3.1 Wall construction. A wall used to create sep- 
arate compartments shall be afire barrier conforming to 
Section 707 with afire-resistance rating of "not less than 2 
hours. Where the building is not divided into more than 
one compartment, the compartment size shall be taken as 



TABLE 3412.6.3 
COMPARTMENTATION VALUES 



OCCUPANCY 


CATEGORIES 3 


a 

Compartment size 

equal to or greater than 

15,000 square feet 


b 

Compartment 

size of 

10,000 square feet 


c 

Compartment 

size of 

7,500 square feet 


d 

Compartment 

size of 

5,000 square feet 


e 

Compartment 

size of 

2,500 square feet or 

less 


A-I, A-3 





6 


10 


14 


18 


A-2 





4 


10 


14 


18 


A-4, B, E, 5-2 





5 


10 


15 


20 


F, M, R, 5-1 





4 


10 


16 


22 



For 51: 1 square foot = 0.093 m 2 . 

a. For areas between categories, the compartmentation value shall be obtained by linear interpolation. 



2009 INTERNATIONAL BUILDING CODE® 



579 



EXISTING STRUCTURES 



the total floor area on all floors. Where there is more than 
one compartment within a story, each compartmented 
area on such storyshall be provided with a horizontal exit 
conforming to Section 1025. The fire door serving as the 
horizontal exit between compartments shall be so 
installed, fitted and gasketed that such fire door wi\\ pro- 
vide a substantial barrier to the passage of smoke. 

3412.6.3.2 Floor/ceiling construction. A floor/ceiling 
assembly used to create compartments shall conform to 
Section 712 and shall have afire-resistance rating of "not 
less than 2 hours. 

3412.6.4 Tenant and dwelling unit separations. Evaluate 
the fire -resistance rating of floors and walls separating ten- 
ants, including dwelling units, and not evaluated under Sec- 
tions 3412.6.3 and 3412.6.5. Under the categories and 
occupancies in Table 3412.6.4, determine the appropriate 
value and enter that value in Table 3412.7 under Safety 
Parameter 3412.6.4, Tenant and Dwelling Unit Separations, 
for fire safety, means of egress and general safety. 

TABLE 3412.6.4 
SEPARATION VALUES 



OCCUPANCY 


CATEGORIES 


a 


b 


c 


d 


e 


A-I 














1 


A-2 


-5 


-3 





1 


3 


A-3, A-4, B, E, F, M, 5-1 


-4 


-3 





2 


4 


R 


-4 


-2 





2 


4 


5-2 


-5 


-2 





2 


4 



3412.6.4.1 Categories. The categories for tenant and 
dwelling unit separations are: 

1. Category a-No fire partitions; incomplete fire 
partitions; no doors; doors not self-closing or 
automatic-closing. 

2. Category h>- Fire partitions or floor assemblies 
with less than a l-hour fire -resistance rating ox not 
constructed in accordance with Sections 709 or 
712, respectively. 

3. Category c-Fire partitions with a I-hour or 
greater fire -resistance rating constructed in accor- 
dance with Section 709 and floor assemblies with a 
I-hour but less than 2-hour fire-resistance rating 
constructed in accordance with Section 712, or 
with only one tenant within the floor area. 

4. Category d-Fire barriers with a I-hour but less 
than 2-hour fire-resistance rating constructed in 
accordance with Section 707 and floor assemblies 
with a 2-hour or greater fire -resistance rating con- 
structed in accordance with Section 712. 

5. Category e-Fire barriers and floor assemblies 
with a 2-hour or greater fire -resistance rating and 
constructed in accordance with Sections 707 and 
712, respectively. 



3412.6.5 Corridor walls. Evaluate the fire -resistance rat- 
ing and degree of completeness of walls which create corri- 
dors serving the floor, and constructed in accordance with 
Section 1018. This evaluation shall not include the wall ele- 
ments considered under Sections 3412.6.3 and 3412.6.4. 
Under the categories and groups in Table 3412.6.5, deter- 
mine the appropriate value and enter that value into Table 
3412.7 under Safety Parameter 3412.6.5, Corridor Walls, 
for fire safety, means of egress and general safety. 

TABLE 3412.6.5 
CORRIDOR WALL VALUES 



OCCUPANCY 


CATEGORIES 


a 


b 


c a 


d a 


A-I 


-10 


-4 





2 


A-2 


-30 


-12 





2 


A-3, F, M, R, 5-1 


-7 


-3 





2 


A-4, B, E, 5-2 


-5 


-2 





5 



a. Corridors not providing at least one-half the travel distance for all occupants 
on a floor shall use Category b. 

3412.6.5.1 Categories. The categories for Corridor 
Walls are: 

1. Category a- No fire partitions; incomplete fire 
partitions; no doors; or doors not self-closing. 

2. Category b-Less than I-hour fire -resistance rat- 
ing or not constructed in accordance with Section 

709.4. 

3. Category c- 1-hour to less than 2-hour fire -resis- 
tance rating, with doors conforming to Section 
715 or without corridors as permitted by Section 
1018. 

4. Category d- 2-hour or greater fire-resistance rat- 
ing, with doors conforming to Section 715. 

3412.6.6 Vertical openings. Evaluate the fire-resistance 
rating of exit enclosures, hoistways, escalator openings and 
other shaft enclosures within the building, and openings 
between two or more floors. Table 3412.6.6(1) contains the 
appropriate protection values. Multiply that value by the 
construction type factor found in Table 3412.6.6(2). Enter 
the vertical opening value and its sign (positive or negative) 
in Table 3412.7 under Safety Parameter 3412.6.6, Vertical 
Openings, for fire safety, means of egress, and general 
safety. If the structure is a one- story building or if all the 
unenclosed vertical openings within the building conform 
to the requirements of Section 708, enter a value of 2. The 
maximum positive value for this requirement shall be 2. 

3412.6.6.1 Vertical opening formula. The following 
formula shall be used in computing vertical opening 
value. 

VO=PVx CF (Equation 34-4) 

VO Vertical opening value. 

PV Protection value [Table 3412.6.6(1)]. 

CF Construction type factor [Table 3412.6.6(2)]. 



580 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



TABLE 3412.6.6(1) 
VERTICAL OPENING PROTECTION VALUE 



PROTECTION 


VALUE 


None (unprotected opening) 


-2 times number floors connected 


Less than 1 hour 


-1 times number floors connected 


1 to less than 2 hours 


1 


2 hours or more 


2 



TABLE 3412.6.6(2) 
CONSTRUCTION-TYPE FACTOR 



FACTOR 


TYPE OF CONSTRUCTION 


IA 


IB 


IIA 


1IB 


I1IA 


IIIB 


IV 


VA 


VB 


1.2 


1.5 


2.2 


3.5 


2.5 


3.5 


2.3 


3.3 


7 



3412.6.7 HVAC systems. Evaluate the ability of the HVAC 
system to resist the movement of smoke and fire beyond the 
point of origin. Under the categories in Section 3412.6.7.1, 
determine the appropriate value and enter that value into 
Table 3412.7 under Safety Parameter 3412.6.7, HVAC Sys- 
tems, for fire safety, means of egress and general safety. 

3412.6.7.1 Categories. The categories for HVAC sys- 
tems are: 

1. Category a-Plenums not in accordance with Sec- 
tion 602 of the International Mechanical Code. 
-10 points. 

2. Category b- Air movement in egress elements not 
in accordance with Section 1018.5. -5 points. 

3. Category c-Both categories a and b are applica- 
ble. -15 points. 

4. Category d-Compliance of the HVAC system 
with Section 1018.5 and Section 602 of the Inter- 
national Mechanical Code. points. 

5. Category e-Systems serving one story, or a cen- 
tral boiler/chiller system without ductwork con- 
necting two or more stories. 5 points. 

3412.6.8 Automatic fire detection. Evaluate the smoke 
detection capability based on the location and operation of 
automatic fire detectors in accordance with Section 907 and 
the International Mechanical Code. Under the categories 
and occupancies in Table 3412.6.8, determine the appropri- 
ate value and enter that value into Table 3412.7 under Safety 
Parameter 3412.6.8, Automatic Fire Detection, for fire 
safety, means of egress and general safety. 

TABLE 3412.6.8 
AUTOMATIC FIRE DETECTION VALUES 



OCCUPANCY 


CATEGORIES 


a 


b 


c 


d 


e 


A-I, A-3, F, 
M, R, S-l 


-10 


-5 





2 


6 


A-2 


-25 


-5 





5 


9 


A-4, B, E, S-2 


-4 


-2 





4 


8 



3412.6.8.1 Categories. The categories for automatic fire 
detection are: 

1. Categorya-None. 

2. Category b-Existing smoke detectors in HVAC 
systems and maintained in accordance with the 
International Fire Code. 

3. Category c- Smoke detectors in HVAC systems. 
The detectors are installed in accordance with the 
requirements for new buildings in the Interna- 
tional Mechanical Code. 

4. Category d- Smoke detectors throughout all floor 
areas other than individual sleeping units, tenant 
spaces and dwelling units. 

5. Category e- Smoke detectors installed through- 
out the floor area. 

3412.6.9 Fire alarm systems. Evaluate the capability of the 
fire alarm system in accordance with Section 907. Under the 
categories and occupancies in Table 3412.6.9, determine 
the appropriate value and enter that value into Table 3412.7 
under Safety Parameter 3412.6.9, Fire Alarm Systems, for 
fire safety, means of egress and general safety. 

TABLE 3412.6.9 
FIRE ALARM SYSTEM VALUES 



OCCUPANCY 


CATEGORIES 


a 


b a 


c 


d 


A-I, A-2, A-3, A-4, B, E, R 


-10 


-5 





5 


F,M,S 





5 


10 


15 



a. For buildings equipped throughout with an automatic sprinkler system, add 
2 points for activation by a sprinkler waterflow device. 

3412.6.9.1 Categories. The categories for fire alarm sys- 
tems are: 

1. Categorya-None. 

2. Category b-Fire alarm system with manual fire 
alarm boxes in accordance with Section 907.3 and 
alarm notification appliances in accordance with 
Section 907.9. 

3. Category c-Fire alarm system in accordance with 
Section 907. 

4. Category d-Category c plus a required emer- 
gency voice/alarm communications system and a 
fire command center that conforms to Section 
403.4.5 and contains the emergency voice/alarm 
communications system controls, fire department 
communication system controls and any other 
controls specified in Section 911 where those sys- 
tems are provided. 

3412.6.10 Smoke control. Evaluate the ability of a natural 
or mechanical venting, exhaust or pressurization system to 
control the movement of smoke from a fire. Under the cate- 
gories and occupancies in Table 3412.6.10, determine the 
appropriate value and enter that value into Table 3412.7 
under Safety Parameter 3412.6.10, Smoke Control, for 
means of egress and general safety. 



2009 INTERNATIONAL BUILDING CODE® 



581 



EXISTING STRUCTURES 



TABLE 3412.6.10 
SMOKE CONTROL VALUES 



OCCUPANCY 


CATEGORIES 


a 


b 


c 


d 


e 


f 


A-I, A-2, A-3 





1 


2 


3 


6 


6 


A-4, E 











1 


3 


5 


B,M,R 





2 a 


3 a 


3 a 


3 a 


4 a 


F,S 





2 a 


2 a 


3 a 


3 a 


3 a 



a. This value shall be if compliance with Category d or e in Section 
3412.6.8.1 has not been obtained. 

3412.6.10.1 Categories. The categories for smoke con- 
trol are: 

1. Categorya-None. 

2. Category t> -The building is equipped throughout 
with an automatic sprinkler system. Openings are 
provided in exterior walls at the rate of 20 square 
feet (1.86 m 2 ) per 50 linear feet (15 240 mm) of 
exterior wall in each story said distributed around 
the building perimeter at intervals not exceeding 
50 feet (15 240 mm). Such openings shall be 
readily openable from the inside without a key or 
separate tool and shall be provided with ready 
access thereto. In lieu of operable openings, 
clearly and permanently marked tempered glass 
panels shall be used. 

3. Category c-One enclosed exit stairway, with 
ready access thereto, from each occupied floor of 
the building. The stairway has operable exterior 
windows and the building has openings in accor- 
dance with Category b. 

4. Category d-One smokeproof enclosure and the 
building has openings in accordance with Cate- 
gory b. 

5. Category e -The building is equipped throughout 
with an automatic sprinkler system. Each floor 
area is provided with a mechanical air-handling 
system designed to accomplish smoke contain- 
ment. Return and exhaust air shall be moved 
directly to the outside without recirculation to 
other floor areas of the building under fire condi- 
tions. The system shall exhaust not less than six air 



changes per hour from the floor area. Supply air by 
mechanical means to the floor area is not required. 
Containment of smoke shall be considered as con- 
fining smoke to the fire area involved without 
migration to other floor areas. Any other tested and 
approved design which will adequately accom- 
plish smoke containment is permitted. 

6. Category f-Each stairwayshall be one of the fol- 
lowing: a smokeproof enclosure in accordance 
with Section 1022.9; pressurized in accordance 
with Section 909.20.5 or shall have operable exte- 
rior windows. 

3412.6.11 Means of egress capacity and number. Evalu- 
ate the means of egress capacity and the number of exits 
available to the building occupants . In applying this section, 
the means of egress are required to conform to the following 
sections of this code: 1003.7, 1004, 1005.1, 1014.2, 1014.3, 
1015.2, 1021, 1025.1, 1027.2, 1027.6, 1028.2, 1028.3, 
1028.4 and 1029 [except that the minimum width required 
by this section shall be determined solely by the width for 
the required capacity in accordance with Table 
3412.6.11 (1)]. The number of exits credited is the number 
that is available to each occupant of the area being evalu- 
ated. Existing fire escapes shall be accepted as a component 
in the means of egress when conforming to Section 3406. 
Under the categories and occupancies in Table 
3412.6.1 1 (2), determine the appropriate value and enter that 
value into Table 3412.7 under Safety Parameter 3412.6.11, 
Means of Egress Capacity, for means of egress and general 
safety. 



TABLE 3412.6.11(2) 
MEANS OF EGRESS VALUES 



OCCUPANCY 


CATEGORIES 


aa 


b 


c 


d 


e 


A-I, A-2, A-3, A-4, E 


-10 





2 


8 


10 


B,F,S 


-1 














M 


-3 





1 


2 


4 


R 


-3 















a. The values indicated are for buildings six stories or less in height. For build- 
ings over six stories above grade plane, add an additional-10 points. 



TABLE 3412.6.11(1) 
EGRESS WIDTH PER OCCUPANT SERVED 



OCCUPANCY 


WITHOUT SPRINKLER SYSTEM 


WITH SPRINKLER SYSTEM 3 


Stairways 
(inches per occupant) 


Other egress components 
(inches per occupant) 


Stairways 
(inches per occupant) 


Other egress components 
(inches per occupant) 


Occupancies other than those listed 
below 


0.3 


0.2 


0.2 


0.15 


Hazardous: H-l, H-2, H-3 and H-4 


Not Permitted 


Not Permitted 


0.3 


0.2 


Institutional: 1-2 


Not Permitted 


Not Permitted 


0.3 


0.2 



For SI: 1 inch = 25.4 mm. 

a. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. 



582 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



3412.6.11.1 Categories. The categories for Means of 
Egress Capacity and number of exits are: 

1. Category a-Compliance with the minimum 
required means of egress capacity or number of 
exits is achieved through the use of a fire escape in 
accordance with Section 3406. 

2. Category b- Capacity of the means of egress com- 
plies with Section 1004 and the number of exits 
complies with the minimum number required by 
Section 1021. 

3. Category c- Capacity of the means of egress is 
equal to or exceeds 125 percent of the required 
means of egress capacity, the means of egress 
complies with the minimum required width 
dimensions specified in the code and the number 
of exits complies with the minimum number 
required by Section 1021. 

4. Category cl-The number of exits provided 
exceeds the number of exits required by Section 
1021. Exits shall be located a distance apart from 
each other equal to not less than that specified in 
Section 1015.2. 

5. Category e-The area being evaluated meets both 
Categories c and d. 

3412.6.12 Dead ends. In spaces required to be served by 
more than one means of egress, evaluate the length of the 
exit access travel path in which the building occupants are 
confined to a single path of travel. Under the categories and 
occupancies in Table 3412.6.12, determine the appropriate 
value and enter that value into Table 3412.7 under Safety 
Parameter 3412.6.12, Dead Ends, for means of egress and 
general safety. 

TABLE 3412.6.12 
DEAD-END VALUES 



OCCUPANCY 


CATEGORIES 3 


a 


b 


c 


A-I,A-3,A-4,B, E,F,M,R, S 


-2 





2 


A-2, E 


-2 





2 



a. For dead-end distances between categories, the dead-end value shall be 
obtained by linear interpolation. 

3412.6.12.1 Categories. The categories for dead ends 
are: 

1. Category a-Dead end of 35 feet (10 670 mm) in 
nonsprinklered buildings or 70 feet (21 340 mm) 
in sprinklered buildings. 

2. Category b-Dead end of20 feet (6096 mm); or 50 
feet (15 240 mm) in Group B in accordance with 
Section 1018.4, exception 2. 

3. Category c - No dead ends; or ratio of length to 
width (I/w) is less than 2.5:1. 

3412.6.13 Maximum exit access travel distance. Evaluate 
the length of exit access travel to an approved exit. Deter- 



mine the appropriate points in accordance with the follow- 
ing equation and enter that value into Table 3412.7 under 
Safety Parameter 3412.6.13, Maximum Exit Access Travel 
Distance, for means of egress and general safety. The maxi- 
mum allowable exit access travel distance shall be deter- 
mined in accordance with Section 1016.1. 



Points = 20 x 



Maximum allowable Maximum actual 

travel distance travel distance 

Max. allowable travel distance 



3412.6.14 Elevator control. Evaluate the passenger eleva- 
tor equipment and controls that are available to the fire de- 
partment to reach all occupied floors. Elevator recall 
controls shall be provided in accordance with the Interna- 
tional Fire Code. Under the categories and occupancies in 
Table 3412.6.14, determine the appropriate value and enter 
that value into Table 3412.7 under Safety Parameter 
3412.6.14, Elevator Control, for fire safety, means of egress 
and general safety. The values shall be zero for a sin- 
gle-story building. 

TABLE 3412.6.14 
ELEVATOR CONTROL VALUES 



ELEVATOR 
TRAVEL 


CATEGORIES 


a 


b 


c 


d 


Less than 25 feet of travel 
above or below the primary 
level of elevator access for 
emergency fire-fighting or 
rescue personnel 


-2 








+2 


Travel of 25 feet or more above 
or below the primary level of 
elevator access for emergency 
fire- fighting or rescue 
personnel 


-4 


NP 





+4 



For 51: 1 foot = 304.8 mm. 

3412.6.14.1 Categories. The categories for elevator 
controls are: 

1. Category a- No elevator. 

2. Category h>-Any elevator without Phase I and II 
recall. 

3. Category c-All elevators with Phase I and II 
recall as required by the International Fire Code. 

4. Category d-All meet Category c; or Category b 
where permitted to be without recall; and at least 
one elevator that complies with new construction 
requirements serves all occupied floors. 

3412.6.15 Means of egress emergency lighting. Evaluate 
the presence of and reliability of means ofegress emergency 
lighting. Under the categories and occupancies in Table 
3412.6.15, determine the appropriate value and enter that 
value into Table 3412.7 under Safety Parameter 3412.6.15, 
Means of Egress Emergency Lighting, for means ofegress 
and general safety. 



2009 INTERNATIONAL BUILDING CODE® 



583 



EXISTING STRUCTURES 



TABLE 3412.6.15 
MEANS OF EGRESS EMERGENCY LIGHTING VALUES 



NUMBER OF EXITS 
REQUIRED BY 
SECTION 1014 


CATEGORIES 


a 


b 


c 


Two or more exits 


NP 





4 


Minimum of one exit 





1 


1 



3412.6.15.1 Categories. The categories for means of 
egress emergency lighting are: 

1. Category a- Means of egress lighting and exit 
signs not provided with emergency power in 
accordance with Chapter 27. 

2. Category b-Means of egress lighting and exit 
signs provided with emergency power in accor- 
dance with Chapter 27. 

3. Category c- Emergency power provided to 
means of egress lighting and exit signs which pro- 
vides protection in the event of power failure to the 
site or building. 

3412.6.16 Mixed occupancies. Where a building has two 
or more occupancies that are not in the same occupancy 
classification, the separation between the mixed occupan- 
cies shall be evaluated in accordance with this section. 
Where there is no separation between the mixed occupan- 
cies or the separation between mixed occupancies does not 
qualify for any of the categories indicated in Section 
3412.6.16.1, the building shall be evaluated as indicated in 
Section 3412.6 and the value for mixed occupancies shall be 
zero. Under the categories and occupancies in Table 
3410.6.16, determine the appropriate value and enter that 
value into Table 3412.7 under Safety Parameter 3412.6.16, 
Mixed Occupancies, for fire safety and general safety. For 
buildings without mixed occupancies, the value shall be 
zero. 

TABLE 3412.6.16 
MIXED OCCUPANCY VALUES 3 



OCCUPANCY 


CATEGORIES 


a 


b 


c 


A-I, A-2, R 


-10 





10 


A-3, A-4, B, E, F, M, 5 


-5 





5 



a. For fire-resistance ratings between categories, the value shall be obtained by 
linear interpolation. 

3412.6.16.1 Categories. The categories for mixed occu- 
pancies are: 

1. Category a-Occupancies separated by minimum 
I-hour fire barriers or minimum I-hour horizontal 
assemblies, or both. 

2. Category b-Separations between occupancies in 
accordance with Section 508.4. 



3. Category c-Separations between occupancies 
having a fire-resistance rating of not less than 
twice that required by Section 508.3.3. 

3412.6.17 Automatic sprinklers. Evaluate the ability to 
suppress a fire based on the installation of an automatic 
sprinkler system in accordance with Section 903.3.1.1. 
"Required sprinklers" shall be based on the requirements of 
this code. Under the categories and occupancies in Table 
3412.6.17, determine the appropriate value and enter that 
value into Table 3412.7 under Safety Parameter 3412.6.17, 
Automatic Sprinklers, for fire safety, means of egress 
divided by 2 and general safety. 

TABLE 3412.6.17 
SPRINKLER SYSTEM VALUES 



OCCUPANCY 


CATEGORIES 


a 


b 


c 


d 


e 


f 


A-I, A-3, F, M, R, 5-1 


-6 


-3 





2 


4 


6 


A-2 


-4 


-2 





1 


2 


4 


A-4, B, E, 5-2 


-12 


-6 





3 


6 


12 



3412.6.17.1 Categories. The categories for automatic 
sprinkler system protection are: 

1. Category a-Sprinklers are required throughout; 
sprinkler protection is not provided or the sprin- 
kler system design is not adequate for the hazard 
protected in accordance with Section 903. 

2. Category b-Sprinklers are required in a portion 
of the building; sprinkler protection is not pro- 
vided or the sprinkler system design is not ade- 
quate for the hazard protected in accordance with 
Section 903. 

3. Category c-Sprinklers are not required; none are 
provided. 

4. Category d- Sprinklers are required in a portion 
of the building; sprinklers are provided in such 
portion; the system is one which complied with the 
code at the time of installation and is maintained 
and supervised in accordance with Section 903. 

5. Category e-Sprinklers are required throughout; 
sprinklers are provided throughout in accordance 
with Chapter 9. 

6. Category f- Sprinklers are not required through- 
out; sprinklers are provided throughout in accor- 
dance with Chapter 9. 

3412.6.18 Standpipes. Evaluate the ability to initiate attack 
on a fire by making a supply of water available readily 
through the installation of standpipes in accordance with 
Section 905. Required standpipes shall be based on the 
requirements of this code. Under the categories and occu- 
pancies in Table 3412.6.18, determine the appropriate value 
and enter that value into Table 3412 .7 under Safety Parame- 
ter 3412.6.18, Standpipes, for fire safety, means of egress 
and general safety. 



584 



2009 INTERNATIONAL BUILDING CODE® 



EXISTING STRUCTURES 



3412.6.18 
STANDPIPE SYSTEM VALUES 



OCCUPANCY 


CATEGORIES 


aa 


b 


c 


d 


A-I, A-3, F, M, R, S-l 


-6 





4 


6 


A-2 


-4 





2 


4 


A-4, B, E, S-2 


-12 





6 


12 



score for any category is less than zero, the building is not in 
compliance with the requirements of this section. 



a. This option cannot be taken if Category a or b in Section 34 12 .6.1 7 is used. 

3412.6.18.1 Standpipe. The categories for standpipe 
systems are: 

1. Category a-Standpipes are required; standpipe is 
not provided or the standpipe system design is not 
in compliance with Section 905.3. 

2. Category b-Standpipes are not required; none are 
provided. 

3. Category c-Standpipes are required; standpipes 
are provided in accordance with Section 905. 

4. Category d-Standpipes are not required; 
standpipes are provided in accordance with Sec- 
tion 905. 

3412.6.19 Incidental accessory occupancy. Evaluate the 
protection of incidental accessory occupancies in accor- 
dance with Section 508.2.5. Do not include those where this 
code requires suppression throughout the buildings, includ- 
ing covered mall buildings, high-rise buildings, public 
garages and unlimited area buildings. Assign the lowest 
score from Table 3412.6.19 for the building or floor area 
being evaluated and enter that value into Table 3412.7 under 
Safety Parameter 3412.6.19, Incidental Accessory Occu- 
pancy' for fire safety, means of egress and general safety. If 
there are no specific occupancy areas in the building or floor 
area being evaluated, the value shall be zero. 

3412.7 Building score. After determining the appropriate data 
from Section 3412.6, enter those data in Table 3412.7 and total 
the building score. 

3412.8 Safety scores. The values in Table 3412.8 are the 
required mandatory safety scores for the evaluation process 
listed'm Section 3412.6. 

3412.9 Evaluation of building safety. The mandatory safety 
score in Table 3412.8 shall be subtracted from the building score 
in Table 3412.7 for each category. Where the final score for any 
category equals zero or more, the building is in compliance with 
the requirements of this section for that category. Where the final 



TABLE 3412.6.19 
INCIDENTAL ACCESSORY OCCUPANCY AREA VALUEsa 


PROTECTION 
REQUIRED BY 
TABLE 508.2.5 


PROTECTION PROVIDED 


None 


1 
Hour 


AFSS 


AFSS 
with 
SP 


1 

Hour 

and 

AFSS 


2 
Hours 


2 

Hours 

and 

AFSS 


2 Hours and AFSS 


-4 


-3 


-2 


-2 


-1 


-2 





2 Hours, or 1 Hour 
and AFSS 


-3 


-2 


-1 


-1 











1 Hour and AFSS 


-3 


-2 


-1 


-1 





-1 





lHour 


-1 





-1 














lHour, or AFSS 
with SP 


-1 





-1 














AFSS with SP 


-1 


-1 


-1 








-1 





1 Hour or AFSS 


-1 





















a. AFSS = Automatic fire suppression system; SP = Smoke partitions (See 

Section 508.2.5). 
Note: For Table 3412.7, see next page. 

TABLE 3412.8 
MANDATORY SAFETY SCORES 3 



OCCUPANCY 


FIRE 

SAFETY 

(MFS) 


MEANS OF 

EGRESS 

(MME) 


GENERAL 

SAFETY 

(MGS) 


A-I 


16 


27 


27 


A-2 


19 


30 


30 


A-3 


18 


29 


29 


A-4, E 


23 


34 


34 


B 


24 


34 


34 


F 


20 


30 


30 


M 


19 


36 


36 


R 


17 


34 


34 


S-l 


15 


25 


25 


S-2 


23 


33 


33 



a. MFS = Mandatory Fire Safety; 

MME = Mandatory Means of Egress; 
MGS = Mandatory General Safety. 



a. FS = Fire Safety 

ME = Means of Egress 
GS = General Safety 



TABLE 3412.9 
EVALUATION FORMULAS 3 



FORMULA 


T.3410.7 




T.3410.8 


SCORE 


PASS 


FAIL 


FS-MFS > 


__ 


(FS) 


(MFS)= 








ME-MME > 




(ME) 


(MME) = 








GS-MGS > 




(GS) 


(MGS)= 









MFS = Mandatory Fire Safety 
MME = Mandatory Means of Egress 
MGS = Mandatory General Safety 



2009 INTERNATIONAL BUILDING CODE® 



585 



EXISTING STRUCTURES 



3412.9.1 Mixed occupancies. For mixed occupancies, the 
following provisions shall apply: 

1. Where the separation between mixed occupancies 
does not qualify for any category indicated in Section 
3412.6.16, the mandatory safety scores for the occu- 
pancy with the lowest general safety score in Table 
3412.8 shall be utilized (see Section 3412.6.) 



Where the separation between mixed occupancies 
qualifies for any category indicated in Section 
3412.6.16, the mandatory safety scores for each occu- 
pancy shall be placed against the evaluation scores for 
the appropriate occupancy. 



TABLE 3412.7 
SUMMARY SHEET - BUILDING CODE 



Existing occupancy : Proposedoccupancy: 

Year building was constructed: _ Number of stories: _ Height in feet 

Type of construction : Area ner floor: 


Percentage of open perimeter increase: % 
Completely suppressed: Yes No 
Compartmentation: Yes No 

Fire-resistance rating of vertical opening enclosures 

Type of HVAC system: 

Automatic fire detection: Yes No 
Fire alarm system: Yes No 


Corridor wall rating: 

Required door closers: Yes No _ 

,servingnumberof floors: 

Type and location: 
Tvne* 


Smoke control: Yes No 
Adequate exit routes : Yes No 


Type: _- 

Dead ends: Yes 


No 


Maximum exit access travel distance: _ Elevator controls: Yes 
Means of egress emergency lighting: Yes No Mixed occupancies: Yes 


No 
No 


SAFETY PARAMETERS 


FIRE SAFETY (FS) 


MEANS OF EGRESS (ME) 


GENERAL SAFETY (GS) 


3412.6.1 Building Height 

3412.6.2 Building Area 

3412.6.3 Compartmentation 








3412.6.4 Tenant and Dwelling Unit Separations 

3412.6.5 Corridor Walls 

3412.6.6 Vertical Openings 








3412.6.7 HVAC Systems 

3412.6.8 Automatic Fire Detection 

3412.6.9 Fire Alarm Systems 








3412.6.10 Smoke Control 

3412.6.11 Means of Egress Capacity 

3412.6.12 Dead Ends 


* * * * 

* * * * 

* * * * 






3412.6.13 Maximum Exit Access Travel Distance 

3412.6.14 Elevator Control 

3412.6.15 Means of Egress Emergency Lighting 


* * * * 

* * * * 






3412.6.16 Mixed Occupancies 

3412.6.17 Automatic Sprinklers 

3412.6.18 Standpipes 

3412.6.19 Incidental Accessory Occupancy 




* * * * 

+ 2 = 




Building score - total value 









*No applicable value to be inserted. 



586 



2009 INTERNATIONAL BUILDING CODE® 



CHAPTER 35 

REFERENCED STANDARDS 



This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the 
promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this 
document that reference the standard. The application of the referenced standards shall be as specified in Section 102.4. 



AA 



AAMA 



Aluminum Association 

1525 Wilson Boulevard, Suite 600 

Arlington, VA 22209 



Standard 
reference 
number 


Title 


Referenced 

in code 

section number 


ADM1-05 
ASM 35-00 


Aluminum Design Manual: Part I-A Specification for Aluminum Structures, Allowable Stress Design; 
and Part 1-B- Aluminum Structures, Load and Resistance Factor Design 

Aluminum Sheet Metal Work in Building Construction (Fourth Edition) 


1604.3.5,2002.1 
2002.1 



American Architectural Manufacturers Association 
1827 Waldon Office Square, Suite 550 
Schaumburg, IL 60173 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 


1402-86 


Standard Specifications for Aluminum Siding, Soffit and Fascia 


1404.5.1 


AAMA/WDMA/CSA 






1011I.S.2/A440-08 


North American Fenestration Standard/Specifications for Windows, Doors and Skylights 


1715.5.1, 2405.5 



ACI 



American Concrete Institute 
38800 Country Club Drive 
Farmington Hills, MI 48331 



Standard 
reference 
number 

216.1-07 
318-08 



530-08 



530.1-08 



Title 

Standard Method for Determining Fire Resistance of Concrete and 
Masonry Construction Assemblies 

Building Code Requirements for Structural Concrete 



Referenced 

in code 

section number 



Table 720.1 (2), 721.1 

1604.3.2, 1614.3.1, 1614.4.1, 1704.3.1.3, Table 1704.3, 

1704.4.1, Table 1704.4, 1708. 2, 

1808.8.2, Table 1808.8.2, 1808.8.5, 1808.8.6, 1810.2.4.1, 1810.3.2.1.1, 

1810.3.2.1.2,1810.3.8.3.1,1810.3.8.3.3, 1810.3.9.4.2.1, 1810.3.9.4.2.2, 1810.3.11.1, 1901.2, 

1901.3, 1901.4, 1902.1, 1903.1, 1904.1,1904.2,1904.3, 1904.4.1, 1904.4.2, 1904.5, 1905.1.1, 1905.2, 

1905.3, 1905.4, 1905.5, 1905.6.2, 1905.6.3, 1905.6.4, 1905.6.5, 1905.7, 1905.8, 1905.9, 

1905.10,1905.11,1905.12,1905.13,1906.1,1906.2, 1906.3, 1906.4, 1907.1, 1907.2, 1907.3, 

1907.4, 1907.5, 1907.6, 1907.7.1, 1907.7.2, 1907.7.3, 1907.7.4, 1907.7.5, 1907.7.6, 1907.8, 1907.9, 1907.10, 

1907.11,1907.12,1907.13,1908.1,1908.1.1, 1908.1.2, 1908.1.3, 1908.1.4, 1908.1.5, 1908.1.6, 

1908.1.7, 1908.1.8, 1908.1.9, 1908.1.10,1909.1, 1909.3, 1909.4, 1909.5, 1909.6, 1912.1,2108.3,2205.3 



Building Code Requirements for Masonry Structures 



Specifications for Masonry Structures 



1405.5, 1405.5.2, 1405.9, 1604.3.4, 

1704.5, 1704.5.1, Table 1704.5.1, 1704.5.2, 1704.5.3, 

Table 1704.5.3, 1807.1.6.3.2, 1808.9,2101.2.2,2101.2.3, 

2101.2.4,2101.2.5,2101.2.6,2103.1.3.6,2106.1, 

2107.1,2107.2,2107.3,2107.4,2107.5,2108.1, 2108.2, 2108.3, 

2109.1,2109.1.1,2109.2,2109.2.1,2109.3,2110.1 

1405.5.1, Table 1704.5.1, Table 1704.5.3, 1807.1.6.3,2103.8, 
2103.11,2103.12,2103.13,2104.1,2104.1.1, 2104.1.2, 2104.1.3, 
2104.2, 2104.3, 2104.4, 2105.2.2.1.1, 2105.2.2.1.2, 2105.2.2.1.3 



2009 INTERNATIONAL BUILDING CODE® 



587 



REFERENCED STANDARDS 



AF&PA 



American Forest & Paper Association 
1111 19th St, NW Suite 800 
Washington, DC 20036 



Standard 
reference 

number 

WCD No. 4-89 

WFCM-Ol 

NDS-05 



AF&PA-93 
ANSIIAF&PA PWF-07 
ANSIIAF&PA SDPWS-08 



Referenced 
in code 

Title section number 

Wood Construction Data-Plank and Beam Framing for Residential Buildings 2306.1.2 

Wood Frame Construction Manual for One- and Two-family Dwellings 1609.1.1,1609.1.1.1,2301.2,2308.1,2308.2.1 

National Design Specification (NDS) for Wood Construction with 2005 Supplement. 721.6.3.2, 1716.1.1, 

1716.1.4, 1809.12,1810.3.2.4, Table 1810.3.2.6, 2302.1, 2304.12, 2306.1, 

Table 2306.2.1(1), Table 2306.2.1(2), Table 2306.3, Table 2306.6,2307.1,2307.1.1 

Span Tables for Joists and Rafters 2306.1.1, 2308.8, 2308.10.2, 2308.10.3 

Permanent Wood Foundation Design Specification 1805.2, 1807.1.4,2304.9.5.2 

Special Design Provisions for Wind and Seismic 1613.6.1, 2305.1, 2306.1, 2306.2.1, 2306.2.2,2306.2.3,2306.3, 

Table 2306.3,2306.4,2306.5,2306.6,2306.7, Table 2306.7,2307.1,2307.1.1 



AISC 



American Institute of Steel Construction 
One East Wacker Drive, Suite 700 
Chicago, IL 60601-18021 



Standard 


Referenced 


reference 


in code 


number 


Title section number 


341-05 


Seismic Provisions for Structural Steel Buildings, including Supplement No. 1 dated 2005 1613.6.2, 1707.2, 




1708.3,2205.2.1,2205.2.2,2205.3,2205.3.1 


360-05 


Specification for Structural Steel Buildings 1604.3.3, Table 1704.3, 1704.3.3,2203.1,2203.2,2205.1,2205.3 



AKI 



S100-07 

S200-07 
S210-07 
S211-07 
S212-07 
S213-07 
S214-07 

S230-07 



American Iron and Steel Institute 
1 140 Connecticut Avenue, 705 
Suite 705 
Washington, DC 20036 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



North American Specification for the Design of Cold-formed 

Steel Structural Members 1604.3.3,2203.1,2203.2,2209.1,2210.2,2210.4,2210.5 

North American Standard for Cold-formed Steel Framing-General Provisions 2203.1,2203.2,2210.1 

North American Standard for Cold-formed Steel Framing-Floor and Roof System Design 2210.5 

North American Standard for Cold-formed Steel Framing-Wall Stud Design 2210.4 

North American Standard for Cold-formed Steel Framing-Header Design 2210.2 

North American Standard for Cold-formed Steel Framing-Lateral Design 2210.6 
North American Standard for Cold-formed Steel Framing-Truss 

Design, with Supplement 2, dated 2008 2210.3.11 
Standard for Cold-formed Steel Framing-Prescriptive Method for One- and 

Two-family Dwellings, with Supplement 2, dated 2008 1609.1.1,1609.1.1.1,2210.7 



AITC 



AITC Technical 
Note 7-96 
AITC 104-03 
AITC 110-01 
AITC 113-01 
AITC 117-04 
AITC 119-96 



American Institute of Timber Construction 

Suite 140 

7012 S. Revere Parkway 

Englewood, CO 80112 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Calculation of Fire Resistance of Glued Laminated Timbers 

Typical Construction Details 

Standard Appearance Grades for Structural Glued Laminated Timber 

Standard for Dimensions of Structural Glued Laminated Timber 

Standard Specifications for Structural Glued Laminated Timber of Softwood Species 

Standard Specifications for Structural Glued Laminated Timber of Hardwood Species 



721.6.3.3 
2306.1 
2306.1 
2306.1 
2306.1 
2306.1 



588 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



AITC 200-04 
ANSIIAITC A 190.1-07 



AITC-continued 

Manufacturing Quality Control Systems Manual for Structural Glued Laminated limber 
Structural Glued Laminated Timber 



2306.1 
2303.1.3, 2306.1 



ALI 



Automotive Lift Institute 
P.O. Box 85 
Courtland, NY 13045 



Standard 
reference 
number 

ALI ALCTV-2006 



Title 

Standard for Automobile Lifts- Safety Requirements for Construction, Testing and Validation (ANSI) 



Referenced 

in code 

section number 

3001.2 



ANSI 



American National Standards Institute 
25 West 43rd Street, Fourth Floor 
New York, NY 10036 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



A13.1-96 
(Reaffirmed 2002) 
A108.1A-99 
A108.1B-99 

A108.4-99 

A108.5-99 

A108.6-99 

A108.8-99 

A108.9-99 

A108. 10-99 

A118.1-99 

A118.3-99 

A118.4-99 
A118.5-99 
A118.6-99 
A118.8-99 
A136.1-99 
A137.1-88 
A208.1-99 
Z97.1-04 



Scheme for the Identification of Piping Systems 

Installation of Ceramic Tile in the Wet-set Method, with Portland Cement Mortar 

Installation of Ceramic Tile, quarry Tile on a Cured Portland Cement Mortar Setting Bed with 

Dry- set or Latex-portland Mortar 
Installation of Ceramic Tile with Organic Adhesives or Water- cleanable Tile-setting Epoxy Adhesive 
Installation of Ceramic Tile with Dry-set Portland Cement Mortar or Latex-portland Cement Mortar 
Installation of Ceramic Tile with Chemical-resistant, Water Cleanable Tile-setting and -grouting Epoxy 
Installation of Ceramic Tile with Chemical-resistant Furan Resin Mortar and Grout 
Installation of Ceramic Tile with Modified Epoxy Emulsion Mortar/Grout. 
Installation of Grout in Tilework 

American National Standard Specifications for Dry-set Portland Cement Mortar 
American National Standard Specifications for Chemical-resistant, Water-cleanable Tile-setting and 

-grouting Epoxy and Water Cleanable Tile-setting Epoxy Adhesive 

American National Standard Specifications for Latex-portland Cement Mortar 

American National Standard Specifications for Chemical Resistant Furan Mortar and Grouts for Tile Installation 
American National Standard Specifications for Cement Grouts for The Installation 
American National Standard Specifications for Modified Epoxy Emulsion Mortar/Grout 
American National Standard Specifications for Organic Adhesives for Installation of Ceramic Tile 
American National Standard Specifications for Ceramic Tile 
Particleboard 

Safety Glazing Materials Used in Buildings-Safety Performance 
Specifications and Methods of Test. 



.415.8.6.4 
2103.10 

2103.10 
2103.10.6 
2103.10.1,2103.10.2 
2103.10.3 
2103.10.4 
2103.10.5 
2103.10.7 
2103.10.1 

2103.10.3 
2103.10.2 
2103.10.4 
2103.10.7 
2103.10.5 
2103.10.6 
2103.5 
2303.1.7, 2303.1.7.1 

2406.1.2,2406.2, Table 2406.2(2),2406.3. 1,2407.1, 
2407.1.4.1,2408.2.1,2408.3,2409.1,2409.2,2409.3.1 



APA 



APA - Engineered Wood Association 
7011 South 19th 
Tacoma, WA 98466 



Standard 
reference 
number 

APAPDS-04 

APAPDS 
Supplement 1-90 

APAPDS 
Supplement 2-92 

APAPDS 
Supplement 3-90 

APAPDS 

Supplement 4-90 



Title 

Panel Design Specification 



Design and Fabrication of Plywood Curved Panels (revised 1995) 
Design and Fabrication of Plywood-lumber Beams (revised 1998) 
Design and Fabrication of Plywood Stressed-skin Panels (revised 1996) 
Design and Fabrication of Plywood Sandwich Panels (revised 1993) 

2009 INTERNATIONAL BUILDING CODE® 



Referenced 

in code 

section number 

2306.1 
2306.1 
2306.1 
2306.1 
2306.1 

589 



REFERENCED STANDARDS 



APAPDS 
Supplement 5-95 
EWS R540-02 
EWS S475-01 
EWS S560-03 
EWS T300-05 
EWS X440-03 
EWS X450-01 



APA-continued 

Design and Fabrication of All-plywood Beams (revised 1995) 

Builders Tips: Proper Storage and Handling of Glulam Beams 

Glued Laminated Beam Design Tables 

Field Notching and Drilling of Glued Laminated Timber Beams 

Glulam Connection Details 

Product Guide-Glulam 

Glulam in Residential Construction-Western Edition 



2306.1 
2306.1 
2306.1 
2306.1 
2306.1 
2306.1 
2306.1 



APSP 



The Association of Pool & Spa Professionals 
2111 Eisenhower Avenue 
Alexandria, VA 22314 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



ANSI1APSP 7-06 



Standard for Suction Entrapment Avoidance in Swimming Pools, Wading Pools, Spas, Hot Tubs and Catch Basins 3109.5 



ASABE 



Standard 
reference 
number 



American Society of Agricultural and Biological Engineers 
2950 Niles Road 
St. Joseph, MI 49085 



Title 



Referenced 

in code 

section number 



EP 484.2 (2003) 
EP 486.1 (2000) 
EP 559 (1997) 



Diaphragm Design of Metal-clad, Post-frame Rectangular Buildings 

Shallow-post Foundation Design 

Design Requirements and Bending Properties for Mechanically Laminated Columns 



2306.1 
2306.1 
2306.1 



ASCE/SEI 



American Society of Civil Engineers 
Structural Engineering Institute 
1801 Alexander Bell Drive 
Reston, VA 20191-4400 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



3-91 
5-08 



6-08 



7-05 



8-02 

19-96 

24-05 

29-05 

32-01 



Structural Design of Composite Slabs 

Building Code Requirements for Masonry Structures 



Specification for Masonry Structures 



1604.3.3, 2209.2.1 

1405.6, 1405.6.2, 1405.10, 1604.3.4, 

1704.5, 1704.5.1, Table 1704.5.1, 1704.5.2, 1704.5.3, 

Table 1704.5.3, 1807.1.6.3.2, 1808.9,2101.2.2,2101.2.3, 

2101.2.4,2101.2.5,2101.2.6,2103.1.3.6,2106.1, 

2107.1,2107.2,2107.3,2107.4,2107.5,2108.1, 2108.2, 2108.3, 

2109.1,2109.1.1,2109.2,2109.2.1,2109.3,2110.1 

1405.6.1, Table 1704.5.1, Table 1704.5.3, 1807.1.6.3, 2103.8, 2103.11, 

2103.12,2103.13,2104.1,2104.1.1,2104.1.2, 2104.1.3, 2104.2, 

2104.3,2104.4,2105.2.2.1.1,2105.2.2.1.2,2105.2.2.1.3 

Minimum Design Loads for Buildings and Other Structures including 

Supplements No.l and 2, excluding Chapter 14 and Appendix 11A Table 1504.8, 1602.1, 1604.3, 1604.8.2, 

1604.10,1605.1,1605.2.2,1605.3.1.2,1605.3.2,1607.11.1, 

1608.1,1608.2,1609.1.1,1609.1.1.2.1,1609.1.1.2.2, 1609.1.2, 1609.3, 1609.4.4, 

1609.5.1,1609.5.3,1609.6,1609.6.1, 1609.6.1.1, 1609.6.2,Table 1609.6.2(2), 1609.6.3, 

1609.6.4.1,1609.6.4.2,1611.2,1612.2,1612.4, 1613.1, 1613.2,Table 1613.5.3(1), Table 1613.5.3(2), 

1613.5.6, 1613.5.6.1, 1613.5.6.2, 1613.6, 1613.6.1, 1613.6.2, 1613.6.3, 1613.6.4, 1613.6.5, 

1613.6.6,1613.6.7,1613.7,1702.1,1705.3.4, 1708.1, 1708.5, 1808.3.1, 1810.3.6.1, 

1810.3.9.4, 1810.3.11.2, 1810.3.12, 1908.1.1, 1908.1.2, 1908.1.9, 2205.2.1, 2205.3, 2205.3.1, 2208.1, 

Table 2304.6.1, Table 2306.7, Table 2308.10.1,2404.1,2505.1,2505.2,3404.4,3404.5 

Standard Specification for the Design of Cold-formed Stainless Steel Structural Members 1604.3.3, 2209.1 

Structural Applications of Steel Cables for Buildings 2207.1, 2207.2 

Flood Resistant Design and Construction 1203.3.2,1612.4,1612.5,3001.2, G103.1, G401.3, G401.4 

Standard Calculation Methods for Structural Fire Protection 721 . 1 

Design and Construction of Frost Protected Shallow Foundations 1809.5 



590 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



ASME 



A17.1ICSAB44-2007 

A18. 1-2005 
A90.1-03 

B16. 18-2001 
(Reaffirmed 2005) 
B16. 22-2001 
(Reaffirmed 2005) 

B20. 1-2006 
B31. 3-2004 



American Society of Mechanical Engineers 

Three Park Avenue 

New York, NY 10016-5990 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Safety Code for Elevators and Escalators 

Safety Standard for Platform Lifts and Stairway Chairlifts 
Safety Standard for Belt Manlifts 

Cast Copper Alloy Solder Joint Pressure Fittings 



907.3.3,911.1.5, 1007.4, 1607.8.1,1613.6.5,3001.2,3001.4, 

3002.5,3003.2,3007.1,3008.3,3008.12,3008.14.1,3411.8.2 

1109.7, 2702.2.6, 3411.8.3 

3001.2 

909.13.1 



Wrought Copper and Copper Alloy Solder Joint Pressure Fittings 
Safety Standard for Conveyors and Related Equipment 
Process Piping 



909.13.1 

3001.2, 3005.3 

415.8.6.1 



ASTM 



ASTM International 

100 Barr Harbor Drive 

West Conshohocken, PA 19428-2959 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



A 36/A 36M-OS 
A 153/A 153M-OS 
A 240/A 240M-07 

A 252-98 (2002) 
A 283/A 283M-03 
A 307-04eOl 
A416/A416M-06 
A 463/A 463M-05 
A 572/A 572M-07 
A588/A588M-05 

A615/A615M-04a 
A653/A653M-07 

A 690/A 690M-07 

A 706/A 706M-05a 

A 722/A 722M-07 
A 755/A 755M-07 

A 792/A 792M-06a 

A 875/A 875M-06 
A913/A913M-04 

A 924/A 924M-07 

A 992/A 992M-06a 
B 42-02eOl 
B 43-98(2004) 
B 68-02 
B 88-03 
B 101-02 

B 209-06 
B 251-02eOl 



Specification for Carbon Structural Steel 1810.3.2.3 

Specification for Zinc Coating (Hot-dip) on Iron and Steel Hardware 2304.9.5 
Standard Specification for Chromium and Chromium-nickel Stainless Steel Plate, 

Sheet and Strip for Pressure Vessels and for General Applications Table 1507.4.3(1) 

Specification for Welded and Seamless Steel Pipe Piles 1810.3.2.3 

Specification for Low and Intermediate Tensile Strength Carbon Steel Plates 1810.3.2.3 

Specification for Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength 1911.1 

Specification for Steel Strand, Uncoated Seven-wire for Prestressed Concrete 1810.3.2.2 

Standard Specification for Steel Sheet, Aluminum-coated, by the Hot-dip Process Table 1507.4.3(2) 

Specification for High-strength Low-alloy Columbium-vanadium Structural Steel 1810.3.2.3 

Specification for High-strength Low-alloy Structural Steel with 50 ksi (345 MPa) 

Minimum Yield Point to 4 inches (100 mm) Thick 1810.3.2.3 

Specification for Deformed and Plain Billet-steel Bars for Concrete Reinforcement. 1708.2, 1810.3.10.2 
Specification for Steel Sheet, Zinc-coated Galvanized or Zinc-iron Alloy-coated 

Galvannealed by the Hot-dip Process Table 1507.4.3(1), Table 1507.4.3(2), 2304.9.5.1 

Standard Specification for High-strength Low-alloy Nickel, Copper, Phosphorus Steel H-piles and 

Sheet Piling with Atmospheric Corrosion Resistance for Use in Marine EINironments 1810.3.2.3 

Specification for Low-alloy Steel Deformed and Plain Bars for 

Concrete Reinforcement Table 1704.3, 1704.4.1,2107.4,2108.3 

Specification for Uncoated High-strength Steel Bar for Prestressing Concrete 1810.3.10.2 

Specification for Steel Sheet, Metallic-coated by the Hot-dip Process and Prepainted by the 

Coil-coating Process for Exterior Exposed Building Products Table 1507.4.3(1), Table 1507.4.3(2) 

Specification for Steel Sheet, 55% Aluminum-zinc Alloy-coated by the 

Hot-dip Process Table 1507.4.3(1), Table 1507.4.3(2) 

Standard Specification for Steel Sheet Zinc-5 percent, Aluminum Alloy-coated by the Hot-dip Process Table 1507.4.3(2) 

Specification for High-strength Low-alloy Steel Shapes of Structural Quality, 

Produced by Quenching and Self-tempering Process (QST) 1810.3.2.3 

Standard Specification for General Requirements for Steel Sheet, 

Metallic-coated by the Hot-dip Process Table 1507.4.3(1) 

Standard Specification for Structural Shapes 1810.3.2.3 

Specification for Seamless Copper Pipe, Standard Sizes 909.13.1 

Specification for Seamless Red Brass Pipe, Standard Sizes 909.13.1 

Specification for Seamless Copper Tube, Bright Annealed (Metric) 909.13.1 

Specification for Seamless Copper Water Tube 909.13.1 

Specification for Lead-coated Copper Sheet and Strip for Building Construction Table 1404.5.3, 

Table 1507.2.9.2, Table 1507.4.3(1) 

Specification for Aluminum and Aluminum Alloy Steel and Plate Table 1507.4.3(1) 

Specification for General Requirements for Wrought Seamless Copper and Copper-alloy Tube 909.13.1 



2009 INTERNATIONAL BUILDING CODE® 



591 



REFERENCED STANDARDS 



B 280-03 
B 370-03 

B 695-04 

C5-03 

C 22/C 22M-00 (2005)eOl 

C 27-98 (2002) 

C28/C28M-00 (2005) 

C311C 31M-06 

C 33-03 

C 34-03 

C 35-01(2005) 

C36/C36M-03 

C37/C37M-01 

C55-06eOl 

C 56-05 

C59/C59M-00 (2006) 

C611C 61M-00 (2006) 

C 62-05 

C 67-07 

C 73-05 

C79-04a 

C90-06b 

C91-05 

C94C94M-07 

C 126-99 (2005) 

C 140-07 

C 150-07 

C 172-04 

C 199-84 (2005) 

C 206-03 

C 208-95 (2001) 

C 212-00 (2006) 

C 216-07 

C 270-07 

C315-07 

C 31 7/C 3 17M-00 (2005) 

C 330-05 

C331-05 

C406-06eOl 

C 442/C 442M-04 

C 472-99 (2004) 

C473-06a 
C 474-05 
C 475-05 
C 503-05 
C 514-04 

C516-02 

C 547-06 

C 549-06 

C 552-03 

C557-03eOl 

C 568-03 

C 578-07 

C 587-04 

C5&5/C588M-01 

C 595-07 

C615-03 



ASTM-continued 

Specification for Seamless Copper Tube for Air Conditioning and Refrigeration Field Service 909.13.1 

Specification for Cold-rolled Copper Sheet and 

Strip for Building Construction 1404.5.2, Table 1507.2.9.2, Table 1507.4.3(1) 



Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel. 

Specification for Quicklime for Structural Purposes 

Specification for Gypsum 

Specification for Standard Classification of Fireclay and High-alumina Refractory Brick 

Specification for Gypsum Plasters 

Practice for Making and Curing Concrete Test Specimens in the Field 

Specification for Concrete Aggregates 

Specification for Structural Clay Load-bearing Wall Tile 

Specification for Inorganic Aggregates for Use in Gypsum Plaster 

Specification for Gypsum Wallboard 

Specification for Gypsum Lath 

Specification for Concrete Building Brick 

Specification for Structural Clay Nonload Bearing Tile 

Specification for Gypsum Casting and Molding Plaster 

Specification for Gypsum Keene's Cement 

Specification for Building Brick (Solid Masonry Units Made from Clay or Shale) 

Test Methods of Sampling and Testing Brick and Structural Clay Tile 

Specification for Calcium Silicate Face Brick (Sand-lime Brick) 

Specification for Treated Core and Nontreated Core Gypsum Sheathing Board 

Specification for Loadbearing Concrete Masonry Units 

Specification for Masonry Cement 

Specification for Ready-mixed Concrete 

Specification for Ceramic Glazed Structural Clay Facing Tile, Facing Brick and Solid Masonry Units 

Test Method Sampling and Testing Concrete Masonry Units and Related Units 

Specification for Portland Cement 

Practice for Sampling Freshly Mixed Concrete 

Test Method for Pier Test for Refractory Mortars 

Specification for Finishing Hydrated Lime 

Specification for Cellulosic Fiber Insulating Board 

Specification for Structural Clay Facing Tile 

Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale) 

Specification for Mortar for Unit Masonry 

Specification for Clay Flue Liners and Chimney Pots 

Specification for Gypsum Concrete 

Specification for Lightweight Aggregates for Structural Concrete 

Specification for Lightweight Aggregates for Concrete Masonry Units 

Specification for Roofing Slate 



Specification for Gypsum Backing Board and Coreboard and Gypsum Shaftliner Board 
Specification for Standard Test Methods for Physical Testing of Gypsum, 

Gypsum Plasters and Gypsum Concrete 
Test Method for Physical Testing of Gypsum Panel Products 
Test Methods for Joint Treatment Materials for Gypsum Board Construction 
Specification for Joint Compound and Joint Tape for Finishing Gypsum Wallboard 
Specification for Marble Dimension Stone (Exterior) 
Specification for Nails for the Application of Gypsum Board 

Specifications for Vermiculite Loose Fill Thermal Insulation 

Specification for Mineral Fiber Pipe Insulation 

Specification for Perlite Loose Fill Insulation 

Standard Specification for Cellular Glass Thermal Insulation 

Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing 

Specification for Limestone Dimension Stone 

Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation 

Specification for Gypsum Veneer Plaster 

Specification for Gypsum Base for Veneer Plasters 

Specification for Blended Hydraulic Cements 

Specification for Granite Dimension Stone 



2304.9.5.1, 2304.9.5.3 

Table 2507.2 

Table 2506.2 

2111.5 

Table 2507.2 

Table 1704.4 

721.3.1.4,721.4.1.1.3 

2103.2 

Table 2507.2 

Figure 721.5.1(2), Figure 721.5.1(3), Table 2506.2 

Table 2507.2 

Table 721.3.2,2103.1,2105.2.2.1.2 

2103.2 

Table 2507.2 

Table 2507.2 

1807.1.6.3, 2103.2, 2105.2.2.1.1 

721.4.1.1.1,2109.3.1.1 

Table 721.3.2,2103.1 

Table 2506.2 

Table 721.3.2, 1807.1.6.3,2103.1 

Table 2507.2 

110.3.1 

2103.2 

721.3.1.2 

Table 2507.2 

Table 1704.4 

2111.5, 2111.8, 2113.12 

Table 2507.2 

Table 1508.2, 2303.1.5 

2103.2 

1807.1.6.3, 2103.2, 2105.2.2.1.1 

2103.8 

2111.8,2113.11, Table 2113.16(1) 

1914.1 

721.1.1 

721.3.1.4,721.4.1.1.3 

1507.7.5 

Table 2506.2 



Table 2506.2 

Table 2506.2 

Table 2506.2 

Table 2506.2 

2103.4 

Table 720.1 (2), Table 720.1 (3), 

Table 2306.7, Table 2506.2 

721.3.1.4,721.4.1.1.3 

Table 720.1 (2), Table 720.1 (3) 

721.3.1.4, 721.4.1.1.3 

Table 1508.2 

Table 2506.2 

2103.4 

Table 1508.2 

Table 2507.2 

Table 2507.2 

Table 2507.2 

2103.4 



592 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



C 616-03 
C 629-03 
C6301C 630M-O3 
C 631 -95a (2004) 
C 635-06 

C 636/C 636M-06 
C 645-07 
C652-05a 

C 728-05 
C 744-05 
C 754-04 

C 836-06 

C 840-07 

C 841-03 

C 842-05 

C 843-99 (2006) 

C 844-04 

C 847-06 

C 887-05 

C 897-05 

C 920-05 

C926-98a (2005) 

C9311C931M-04 

C 932-06 

C 933-05 

C 946-91 (2001) 

C 954-04 



C 955-06 



C 956-04 
C 957-06 

C 960-04 
C 1002-04 

C 1007-04 

C 1019-05 
C 1029-05a 
C 1032-06 
C 1047-05 
C 1063-06 

C 1088-07a 

C 1167-03 

C 1177/C 1177M-06 

C 1178/C 1178M-06 

C 1186-07 

C 1261-07 

C 1278/C 1278M-06 

C 1280-04 

C 1283-07 

C 1288-99 (2004) 

C 1289-07 



ASTM-continued 

Specification for Quartz Dimension Stone 

Specification for Slate Dimension Stone 

Specification for Water-resistant Gypsum Backing Board 

Specification for Bonding Compounds for Interior Gypsum Plastering 

Specification for the Manufacture, Performance and Testing of Metal Suspension 

Systems for Acoustical Tile and Lay-in Panel Ceilings 8( 

Practice for Installation of Metal Ceiling Suspension Systems for Acousticalllle and Lay-in Panels 
Specification for Nonstructural Steel Framing Members 
Specification for Hollow Brick (Hollow Masonry Units Made from Clay or Shale) 



2103.4 

2103.4 

Table 2506.2 

Table 2507.2 



.1.1,2506.2.1, 



Standard Specification for Perlite Thermal Insulation Board 
Specification for Prefaced Concrete and Calcium Silicate Masonry Units 
Specification for Installation of Steel Framing Members to Receive Screw-attached 

Gypsum Panel Products 
Specification for High-solids Content, Cold Liquid-applied Elastomeric 

Waterproofing Membrane for Use with Separate Wearing Course 
Specification for Application and Finishing of Gypsum Board 
Specification for Installation of Interior Lathing and Furring 
Specification for Application of Interior Gypsum Plaster. 
Specification for Application of Gypsum Veneer Plaster 

Specification for Application of Gypsum Base to Receive Gypsum Veneer Plaster 
Specification for Metal Lath 

Specification for Packaged, Dry Combined Materials for Surface Bonding Mortar 
Specification for Aggregate for Job-mixed Portland Cement-based Plaster. 
Standard for Specification for Elastomeric Joint Sealants 
Specification for Application of Portland Cement-based Plaster 



H107.1.1 

808.1.1 

Table 2506.2, Table 2507.2 

1807.1.6.3, 

2103.2, 2105.2.2.1.1 

Table 1508.2 

Table 721.3.2,2103.1 

Table 2508.1, Table 2511.1.1 



Specification for Exterior Gypsum Soffit Board 

Specification for Surface-applied Bonding Compounds Agents for Exterior Plastering 

Specification for Welded Wire Lath 

Specification for Practice for Construction of Dry-stacked, Surface-bonded Walls 

Specification for Steel Drill Screws for the Application of 

Gypsum Panel Products or Metal Plaster Bases to 

Steel Studs from 0.033 inch (0.84 mm) to 0.112 inch (2.84 mm) in Thickness 
Standard Specification for Load-bearing Transverse and Axial Steel Studs, 

Runners Tracks, and Bracing or Bridging, for Screw Application of 

Gypsum Panel Products and Metal Plaster Bases 
Specification for Installation of Cast-in-place Reinforced Gypsum Concrete 
Specification for High-solids Content, Cold Liquid-applied Elastomeric 

Waterproofing Membrane with Integral Wearing Surface 
Specification for Predecorated Gypsum Board 
Specification for Steel Self-piercing Tapping Screws for the Application of 

Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs 
Specification for Installation of Load Bearing (Transverse and Axial) Steel Studs and 

Related Accessories 
Test Method of Sampling and Testing Grout 

Specification for Spray-applied Rigid Cellular Polyurethane Thermal Insulation 
Specification for Woven Wire Plaster Base 

Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base 
Specification for Installation of Lathing and Furring to Receive Interior and 

Exterior Portland Cement-based Plaster 
Specification for Thin Veneer Brick Units Made from Clay or Shale 
Specification for Clay Roof Tiles 

Specification for Glass Mat Gypsum Substrate for Use as Sheathing 
Specification for Coated Mat Water-resistant Gypsum Backing Panel 
Specification for Flat Nonasbestos Fiber Cement Sheets 
Specification for Firebox Brick for Residential Fireplaces 
Specification for Fiber-reinforced Gypsum Panels 
Specification for Application of Gypsum Sheathing 
Practice for Installing Clay Flue Lining 

Standard Specification for Discrete Nonasbestos Fiber-cement Interior Substrate Sheets 
Standard Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation Board 



1507.15.2 
Table 2508.1, 2509.2 
Table 2508.1, Table 2511.1.1 
Table 2511.1.1,2511.3,2511.4 
Table 2511.1.1 
Table 2508.1 
Table 2507.2 
1805.2.2, 2103.9 
Table 2507.2 
Table 2506.2 
2109.3.4.6,2510.3, Table 2511.1.1,2511.3,2511.4,2512.1, 
2512.1.2,2512.2,2512.6,2512.8.2,2512.9,2513.7 

Table 2506.2 



Table 2507.2 

Table 2507.2 

2103.9,2109.2.2 

Table 2506.2, Table 2507.2 



Table 2506.2, Table 2507.2 
1914.1 

1507.15.2 
Table 2506.2 

Table 2506.2, Table 2507.2 

Table 2508.1, Table 2511.1.1 

2105.2.2.1.1,2105.2.2.1.2,2105.2.2.1.3 

1507.14.2 

Table 2507.2 

Table 2506.2, Table 2507.2 

2109.3.4.6,2510.3, Table 2511.1.1,2512.1.1 

Table 720.1 (2),2103.2 

1507.3.4 

Table 2506.2 

Table 2506.2, 2509.2 

1404.10 

2111.5, 2111.8 

Table 2506.2 

Table 2508.1, 2508.2 

2113.12 

2509.2 

Table 1508.2 



2009 INTERNATIONAL BUILDING CODE® 



593 



REFERENCED STANDARDS 



C 1314-07 

C 1325-04 

C 1328-05 

C 1386-07 

C 1395/C 1395M-06a 

C 1396M-06a 

C 1405-07 

C 1492-03 

C 1629/C 1629M-06 

C 1658/C 1658M-06 

D 25-99 (2005) 

D41-05 

D 43-00 (2006) 

D 56-05 

D86-07a 

D 93-07 

D 225-04 

D 226-06 



D 227-03 

D 312-00 (2006) 

D 422-63 (2002)eOI 

D448-03a 

D 450-07 

D 635-06 

D 1143/D 1143M-07 
D 1227-95 (2007) 
D 1557-02eOI 

D 1586-99 

D 1761-06 

D 1863-05 

D 1929-96 (2001)eOI 

D 1970-01 



D 2166-06 

D 2178-04 

D 2216-05 

D 2487-06 

D 2626-04 

D 2822-05 

D 2823-05 

D 2843-99 (2004)eOI 

D2850-03a 

D 2898-04 

D 3019-94 (2007) 

D 3161-06 

D 3200-74 (2005) 

D 3201-07 

D 3278-(2004)eOI 

D 3462-07 

D 3468-99 (2006)eOI 

D3679-06a 

D 3689-90 (1995) 



ASTM-continued 

Test Method for Compressive Strength of Masonry Prisms 2105.2.2.2.2, 2105.3.1, 2105.3.2 

Standard Specification for Nonasbestos Fiber-mat Reinforced Cement Interior Substrate Sheets 2509.2 



Specification for Plastic (Stucco Cement) 

Specification for Precast Autoclaved Aerated Concrete (AAC) Wall Construction Units 

Specification for Gypsum Ceiling Board 

Specification for Gypsum Board 

Standard Specification for Glazed Brick (Single Fired, Solid Brick Units) 

Standard Specification for Concrete Roof Tile 

Standard Classification for Abuse-resistant Nondecorated Interior Gypsum Panel 

Products and Fiber-reinforced Cement Panels 
Standard Specification for Glass Mat Gypsum Panels 
Specification for Round Timber Piles 

Specification for Asphalt Primer Used in Roofing, Dampproofing and Waterproofing 
Specification for Coal Tar Primer Used in Roofing, Dampproofing and Waterproofing 
Test Method for Flash Point By Tag Closed Tester 

Test Method for Distillation of Petroleum Products at Atmospheric Pressure 
Test Method for Flash Point By Pensky-Martens Closed Cup Tester. 
Specification for Asphalt Shingles (Organic Felt) Surfaced with Mineral Granules 
Specification for Asphalt-saturated Organic Felt Used in Roofing and Waterproofing 



Table 2507.2 

2102.1,2103.3,2105.2.2.1.3 

Table 2506.2 

Table 2506.2 

2103.2 

1507.3.5 



403.2.3.1, 403.2.3.2, 403.2.3.4 
1810.3.2.4, Table 2506.2 
2303.1.11 
Table 1507.10.2 
Table 1507.10.2 
307.2 
307.2 
307.2 
1507.2.5 
1404.2, 1507.2.3, 1507.3.3, 
1507.5.3, 1507.6.3, 1507.7.3, Table 1507.8, 
1507.8.3, 1507.9.3, 1507.9.5, Table 1507.10.2 



Specification for Coal-tar-saturated Organic Felt Used in Roofing and Waterproofing 

Specification for Asphalt Used in Roofing 

Test Method for Particle-size Analysis of Soils 

Standard Classification for Sizes of Aggregate for Road and Bridge Construction 

Specification for Coal-tar Pitch Used in Roofing, Dampproofing and Waterproofing 

Test Method for Rate of Burning and/or Extent and Time of Burning of 

Self-supporting Plastics in a Horizontal Position 
Test Method for Piles Under Static Axial Compressive Load 
Specification for Emulsified Asphalt Used as a Protective Coating for Roofing 
Test Method for Laboratory Compaction Characteristics of Soil Using 

Modified Effort [56,000 ft-Ib/fr (2,700 KN m/m 3 )] 
Specification for Penetration Test and Split-barrel Sampling of Soils 
Test Method for Mechanical Fasteners in Wood 
Specification for Mineral Aggregate Used on Built-up Roofs 
Test Method for Determining Ignition Properties of Plastics 
Specification for Self-adhering Polymer Modified Bituminous Sheet Materials 

Used as Steep Roof Underlayment for Ice Dam Protection 



Test Method for Unconfined Compressive Strength of Cohesive Soil 
Specification for Asphalt Glass Felt Used in Roofing and Waterproofing 

Test Method for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass 
Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System) 
Specification for Asphalt Saturated and Coated Organic Felt Base Sheet Used in Roofing 
Specification for Asphalt Roof Cement 
Specification for Asphalt Roof Coatings 

Test for Density of Smoke from the Burning or Decomposition of Plastics 
Test Method for Unconsolidated, Undrained Triaxial Compression Test on Cohesive Soils 
Test Methods for Accelerated Weathering of Fire-retardant-treated Wood for Fire Testing 
Specification for Lap Cement Used with Asphalt Roll Roofing, Nonfibered, Asbestos Fibered and 
Nonasbestos Fibered 



Table 1507.10.2 

Table 1507.10.2 

1803.5.3 

1507.12.3, 1507.13.3 

Table 1507.10.2 

2606.4, HI07. 1.1 

1810.3.3.1.2 

Table 1507.10.2, 1507.15.2 

1704.7, 1804.5, JI07. 6 

1613.5.5 

1716.1.1, 1716.1.2, 1716.1.3 

Table 1507.10.2 

402.16.4,406.5.3,1407.11.2.1,2606.4 

1507.2.4, 1507.2.9.2, 1507.3.9, 
1507.5.7, 1507.8.8, 1507.9.9 
1613.5.5 
Table 1507.10.2 
1613.5.5 
Table 1610.1, 1802.3.1 
1507.3.3, Table 1507.10.2 
Table 1507.10.2 
Table 1507.10.2 
2606.4 
1613.5.5 
1505.1,2303.2.4,2303.2.6 



Test Method for a Wind Resistance of Asphalt Shingles (Fan Induced Method) 

Standard Specification and Test Method for Establishing Recommended Design Stresses for 

Round Timber Construction Poles 
Test Method for Hygroscopic Properties of Fire-retardant-treated Wood and Wood-based Products 
Test Methods for Flash Point of Liquids by Small Scale Closed-cup Apparatus 
Specification for Asphalt Shingles Made from Glass Felt and Surfaced with Mineral Granules 
Specification for Liquid-applied Neoprene and Chlorosulfonated Polyethylene Used in 

Roofing and Waterproofing 
Specification for Rigid Poly [Vinyl Chloride (PVC) Siding] 
Method for Testing Individual Piles Under Static Axial Tensile Load 



Table 1507.10.2 
1507.2.7.1, Table 1507.2.7.1 (2) 



2303.1.11 

2303.2.7 

307.2 

1507.2.5 

1507.15.2 

1404.9, 1405.14 

1810.3.3.1.5 



594 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



D 3737-07 

D 3746-85 (2002) 

D 3747-79 (2007) 

D 3909-97b (2004)eOI 

D 3957-06 

D 4022-07 

D 4272-03 

D 4318-05 

D 4434-06 

D 4479-07 

D 4586-00 

D 4601-04 

D 4637-04 

D 4829-07 

D4869-05eOl 

D 4897-01 

D 4945-00 

D 4990-97a (2005)eOI 

D 5019-07 

D 5055-05 

D5456-05a 

D 5516-03 

D 5643-06 
D 5664-02 

D 5665-99a (2006) 
D 5726-98 (2005) 
D6083-05eOl 
D6162-00A 

D6163-00eOl 

D 6164-05 

D 6222-02eOI 

D 6223-02 

D 6298-05 

D6305-02eOl 

D 6380-03 
D 6509-00 

D 6694-07 
D 6754-02 
D 6757-07 
D 6841-03 
D6878-06a 
D 6947-07 

D 7158-07 

E 84-07 

E 90-04 

E 96/E 96M-05 



ASTM-continued 

Practice for Establishing Allowable Properties for Structural Glued Laminated Timber (Glulam) 
Test Method for Impact Resistance of Bituminous Roofing Systems 
Specification for Emulsified Asphalt Adhesive for Adhering Roof Insulation 



2303.1.3 

1504.7 

Table 1507.10.2 



Specification for Asphalt Roll Roofing (Glass Felt) Surfaced with Mineral Granules 1507.2.9.2, 1507.6.5, Table 1507.10.2 
Standard Practices for Establishing Stress Grades for Structural Members Used in Log Buildings 2303.1.10 

Specification for Coal Tar Roof Cement, Asbestos Containing Table 1507.10.2 

Test Method for Total Energy Impact of Plastic Films by Dart Drop 1504.7 

Test Methods for Liquid Limit, Plastic Limit and Plasticity Index of Soils 1613.5.5, 1803.5.3 

Specification for Poly (Vinyl Chloride) Sheet Roofing 1507.13.2 

Specification for Asphalt Roof Coatings- Asbestos-free Table 1507.10.2 

Specification for Asphalt Roof Cement- Asbestos-free Table 1507.10.2 

Specification for Asphalt-coated Glass Fiber Base Sheet Used in Roofing Table 1507.10.2 

Specification for EPDM Sheet Used in Single-ply Roof Membrane 1507.12.2 

Test Method for Expansion Index of Soils 1803.5.3 

Specification for Asphalt-saturated (Organic Felt) Underlayment Used in 

Steep Slope Roofing 1507.2.3, 1507.5.3, 1507.6.3, 1507.7.3, 1507.8.3, 1507.9.3 

Specification for Asphalt-coated Glass Fiber Venting Base Sheet Used in Roofing Table 1507.10.2 

Test Method for High-strain Dynamic Testing of Piles 1810.3.3.1.2 

Specification for Coal Tar Glass Felt Used in Roofing and Waterproofing Table 1507.10.2 

Specification for Reinforced Nonvulcanized Polymeric Sheet Used in Roofing Membrane 1507.12.2 

Specification for Establishing and Monitoring Structural Capacities of Prefabricated Wood I-joists 2303.1.2 

Specification for Evaluation of Structural Composite Lumber Products 2303.1.9 

Test Method of Evaluating the Flexural Properties of Fire-retardant-treated 

Softwood Plywood Exposed to the Elevated Temperatures 
Specification for Coal Tar Roof Cement, Asbestos-free 
Test Methods for Evaluating the Effects of Fire-retardant Treatment and 

Elevated Temperatures on Strength Properties of Fire-retardant-treated Lumber 
Specification for Thermoplastic Fabrics Used in Cold-applied Roofing and Waterproofing 
Specification for Thermoplastic Fabrics Used in Hot-applied Roofing and Waterproofing 
Specification for Liquid Applied Acrylic Coating Used in Roofing 
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous 

Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements 
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous 

Sheet Materials Using Glass Fiber Reinforcements 
Specification for Styrene-butadiene-styrene (SBS) Modified Bituminous 

Sheet Metal Materials Using Polyester Reinforcements 
Specification for Atactic Polypropylene (APP) Modified Bituminous 

Sheet Materials Using Polyester Reinforcements 
Specification for Atactic Polypropylene (APP) Modified Bituminous 

Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements 
Specification for Fiberglass Reinforced Styrene-butadiene-styrene (SBS) 

Modified Bituminous Sheets with a Factory Applied Metal Surface 
Practice for Calculating Bending Strength Design Adjustment Factors for Fire-retardant-treated 

Plywood Roof Sheathing 
Standard Specification for Asphalt Roll Roofing (Organic) Felt 
Standard Specification for Atactic Polypropylene (APP) Modified Bituminous base 

Sheet Materials Using Glass Fiber Reinforcements 
Standard Specification for Liquid-applied Silicone Coating Used in Spray Polyurethane Foam Roofing 
Standard Specification for Ketone Ethylene Ester Based Sheet Roofing 

Standard Specification for Inorganic Underlayment for Use with Steep Slope Roofing Products 
Standard Practice for Calculating Design Value Treatment Adjustment Factors for Fire-retardant-treated Lumber 
Standard Specification for Thermoplastic Polyolefin Based Sheet Roofing 
Standard Specification for Liquuid Applied Moisture Cured Polyurethane Coating 

Used in Spray Polyurethane Foam Roofing System 1507.15.2 

Standard Test Method for Wind Resistance of Sealed Asphalt Shingles 

(Uplift Force/Uplift Resistance Method) ' 1507.2.7.1, Table 1507.2.7.1 (1) 

Test Methods for Surface Burning Characteristics of Building Materials 402.11, 402.16.4, 406.5.3, 

703.4.2,719.1,719.4,802.1,803.1.1,803.9,806.5, 
1407.9,1407.10.1,2303.2,2603.3,2603.4.1.13, 2603.5.4, 2604.2.4, 2606.4,3105.4, DI02.2.8 
Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of 

Building Partitions and Elements 1207.2, 1207.2.1 

Test Method for Water Vapor Transmission of Materials 202,1203.2 



2303.2.5.1 
Table 1507.10.2 

2303.2.5.2 

Table 1507.10.2 

Table 1507.10.2 

Table 1507.10.2, 1507.15.2 

1507.11.2 

1507.11.2 



1507.11.2 



1507.11.2 



1507.11.2 



1507.11.2 



2303.2.5.1 
1507.2.9.2, 1507.3.3, 1507.6.5 



1507.11.2 
1507.15.2 
1507.13.2 
1507.2.3 
2303.2.5.2 
1507.13.2 



2009 INTERNATIONAL BUILDING CODE® 



595 



REFERENCED STANDARDS 



E 108-07a 
E 119-07 



E 136-04 
E 330-02 

E331-00 

E 492-04 

E 605-93 (2006) 

E681-04 

E 736-00 (2006) 

E 814-06 
E 970-00 

E 1300-04eOl 

E 1354-04a 

E 1592-01 

E 1602-03 
E 1886-06 

E 1966-01 
E 1996-06 

E 2072-04 
E 2273-03 

E2307-04eOl 

E2404-07a 

E 2568-07 
E 2570-07 

E 2573-07 

F 547-01 

F 1346-91 (2003) 

F 1667-05 

F 2006-00 (2005) 

F 2090-0 la (2007) 
F 2200-05 
G 152-06 
G 154-05 
G 155-05a 



ASTM-continued 

Test Methods for Fire Tests of Roof Coverings 

Test Methods for Fire Tests of Building Construction and Materials 



1505.1, 2603.6, 2610.2, 2610.3 

703.2, 703.2.1, 703.2.3, 703.3, 

703.5,704.12,705.7,705.8.5,707.6,712.3.2, 

713.3.1,713.4.1.1,714.1,715.2,715.4.5,716.5.2, 716.5.3, 716.6.1, 

716.6.2.1, Table 720.1(1), 1407. 10.2,2103. 2,2603.4,2603. 5.1 



Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C 

Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by 
Uniform Static Air Pressure Difference 

Test Method for Water Penetration of Exterior Windows, Skylights, Doors and Curtain Walls by 
Uniform Static Air Pressure Difference 

Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-ceiling 
Assemblies Using the Tapping Machine 

Test Method for Thickness and Density of Sprayed Fire-resistive Material (SFRM) 
Applied to Structural Members 



Test Methods for Concentration Limits ofFlammability of Chemical Vapors and Gases 
Test Method for Cohesion/Adhesion of Sprayed Fire-resistive Materials Applied to 

Structural Members 
Test Method of Fire Tests of Through-penetration Firestops 
Test Method for Critical Radiant Flux of Exposed Attic Floor Insulation Using 



703.4.1 

1715.5.2 

1403.2 

1207.3 

1704.12.4.1, 1704.12.4.2, 

1704.12.4.3, 1704.12.5 

307.2 



704.13.2, 1704.12.6 
702.1,713.3.1.2,713.3.2,713.4.1.1.2 



a Radiant Heat Energy Source 
Practice for Determining Load Resistance of Glass in Buildings 



719.3.1 

2404.1, 2404.2, 2404.3.1, 
2404.3.2, 2404.3.3, 2404.3.4, 2404.3.5 

Standard Test Method for Heat and Visible Smoke Release Rates for Materials and Products 

Using an Oxygen Consumption Calorimeter. .402.12.1 

Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by 
Uniform Static Air Pressure Difference 



Guide for Construction of Solid Fuel- burning Masonry Heaters 

Test Method for Performance of Exterior Windows, Curtain Walls, Doors and 

Storm Shutters Impacted by Missiles and Exposed to Cyclic Pressure Differentials 

Test Method for Fire-resistant Joint Systems 

Specification for Performance of Exterior Windows, Glazed Curtain Walls, 

Doors and Impact Protective Systems Impacted by Windborne Debris in Hurricanes 

Standard Specification for Photoluminescent (Phosphorescent) Safety Markings 

Standard Test Method for Determining the Drainage Efficiency of Exterior Insulation and 
Finish Systems (EIFS) Clad Wall Assemblies 

Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems 
Using Intermediate-scale, Multistory Test Apparatus 

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Vinyl Wall or 
Ceiling Coverings to Assess Surface Burning Characteristics 

Standard Specification for PB Exterior Insulation and Finish Systems (EIFS) 

Standard Test Method for Evaluating Water-resistive Barrier (WRB) Coatings Used 
Under Exterior Insulation and Finish Systems (EIFS) for EIFS with Drainage 

Standard Practice for Specimen Preparation and Mounting of Site-fabricated Stretch 
Systems to Assess Surface Burning Characteristics 

Terminology of Nails for Use with Wood and Wood-based Materials 

Performance Specification for Safety Covers and Labeling Requirements for All Covers for 
Swimming Pools, Spas and Hot Tubs 

Specification for Driven Fasteners: Nails, Spikes and Staples 



1504.3.2 
2112.2 

1609.1.2 

702.1,714.3 

1609.1.2, 1609.1.2.1 

1024.4 

1408.4.1 

714.4 

803.1.4 
1408.2 

1408.4.1.1, 1704.12.1 

803.9 
Table 2506.2 



3109.4,3109.4.1.8 
Table 720.1 (2), Table 720.1 (3), 
1507.2.6, 2303.6, Table 2506.2 

Standard/Safety Specification for Window Fall Prevention Devices for 

Nonemergency Escape (Egress) and Rescue (Ingress) Windows 1405.13.2 

Specification for Window Fall Prevention Devices with Emergency Escape (Egress) Release Mechanisms 1405.13.2 

Standard Specification for Automated Vehicular Gate Construction 3110.3 

Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Nonmetallic Materials 1504.6 

Practice for Operating Fluorescent Light Apparatus for UV Exposure of Nonmetallic Materials 1504.6 

Practice for Operating Xenon Arc Light Apparatus for Exposure of Nonmetallic Materials 1504.6 



596 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



AWCI 



Standard 
reference 
number 



Association of the Wall and Ceiling Industry 
513 West Broad Street, Suite 210 
Falls Church, VA 22046 



Title 



Referenced 

in code 

section number 



12-B-98 



Technical Manual 12-B Standard Practice for the Testing and Inspection of 

Field Applied Thin Film Intumescent Fire-resistive Materials; an Annotated Guide, First Edition 



1704.13 



AWPA 



American Wood Protection Association 
P.O. Box 361784 
Birmingham, AL 35236-1784 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



C 1 -03 All Timber Products-Preservative Treatment by Pressure Processes 1505.6 

M4-06 Standard for the Care of Preservative-treated Wood Products 1810.3.2.4.1,2303.1.8 

U 1 -07 USE CATEGORY SYSTEM: User Specification for Treated Wood Except Section 6, 

Commodity Specification H 1403.5, Table 1507.9.6, 

1807.1.4, 1807.3.1, 1809.12, 1810.3.2.4.1,2303.1.8, 
2304.11.2, 2304.11.4, 2304.11.6, 2304.11.7 



AWS 

Standard 
reference 
number 



American Welding Society 
550 N.W. Lejeune Road 
Miami, FL 33126 



Title 



Referenced 

in code 

section number 



Dl.1-04 


Structural Welding Code-Steel 


Table 1704.3, 1704.3.1.1 


Dl.3-98 


Structural Welding Code- Sheet Steel 


Table 1704.3, 1704.3.1.2 


Dl.4-98 


Structural Welding Code-Reinforcing Steel 


Table 1704.3, 1704.3.1.3, Table 1704.4,2107.4 



BHMA 



Standard 
reference 
number 



Builders Hardware Manufacturers' Association 
355 Lexington Avenue, 17th Floor 
New York, NY 10017-6603 



Title 



Referenced 

in code 

section number 



A 156.10-06 
A 156.19-02 



Power Operated Pedestrian Doors 

Standard for Power Assist and Low Energy Operated Doors 



1008.1.4.2 
1008.1.4.2 



CGSB 



Standard 
reference 
number 



Canadian General Standards Board 

Place du Portage 111, 6B1 

11 Laurier Street 

Gatineau, Quebec, Canada KIA 1G6 



Title 



Referenced 

in code 

section number 



37-GP-52M (1984) 
37-GP-56M (1980) 

CAN/CGSB 37.54-95 



Roofing and Waterproofing Membrane, Sheet Applied, Elastomeric 
Membrane, Modified, Bituminous, Prefabricated and Reinforced for 

Roofing-with December 1985 Amendment 
Polyvinyl Chloride Roofing and Waterproofing Membrane 



1504.7, 1507.12.2 



1507.11.2 
1507.13.2 



CPA 



Composite Panel Association 
19465 Deerfield Avenue, Suite 306 
Leesburg, VA 20176 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



ANSI A135. 4-2004 Basic Hardboard 

2009 INTERNATIONAL BUILDING CODE® 



.1404.3.1, 2303.1.6 



597 



REFERENCED STANDARDS 



ANSI A135. 5-2004 
ANSI A135. 6-1998 



CPA-continued 



Prefinished Hardboard Paneling 
Hardboard Siding 



2303.1.6, 2304.6.2 
1404.3.2, 2303.1.6 



CPSC 



Consumer Product Safety Commission 
4330 East West Highway 
Bethesda, MD 20814-4408 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



16 CFR Part 1201 (1977) 

16 CFR Part 1209 (1979) 
16 CFR Part 1404 (1979) 
16 CFR Part 1500 (1991) 
16 CFR Part 1500.44 (2001) 
16 CFR Part 1507 (2001) 
16 CFR Part 1630 (2000) 



Safety Standard for Architectural Glazing Material 2406.2, Table 2406.2(1), 2406.3.1, 2407.1, 

2407.1.4.1, 2408.2.1, 2408.3, 2409.1, 2409.2, 2409.3.1 

Interim Safety Standard for Cellulose Insulation 719.6 

Cellulose Insulation 719.6 

Hazardous Substances and Articles; Administration and Enforcement Regulations 307.2 

Method for Determining Extremely Flammable and Flammable Solids 307.2 

Fireworks Devices 307.2 

Standard for the Surface Flammability of Carpets and Rugs 804.4.1 



CSA 



Canadian Standards Association 

5060 Spectrum Way 

Mississauga, Ontario Canada L4W 5N6 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



1011I.S.2/A440-08 



Specifications for Windows, Doors and Unit Skylights 



1715.5.1, 2405.5 



CSSB 



Cedar Shake and Shingle Bureau 

P.O. Box 1178 

Sumas, WA 98295-1178 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



CSSB-97 



Grading and Packing Rules for Western Red Cedar Shakes and Western Red Shingles 
of the Cedar Shake and Shingle Bureau 



Table 1507.8.5, Table 1507.9.6 



DASMA 



Door and Access Systems Manufacturers Association International 
1300 Summer Avenue 
Cleveland, OH 44115-2851 



Standard 
reference 

number 

ANSI/DASMA 107-1997 

(R2004) 

108-05 

115-05 



Title 



Room Fire Test Standard for Garage Doors Using Foam Plastic Insulation 
Standard Method for Testing Sectional Garage Doors and Rolling Doors: 

Determination of Structural Performance Under Uniform Static Air Pressure Difference 
Standard Method for Testing Sectional Garage Doors and Rolling Doors: 

Determination of Structural Performance Under Missile Impact and Cyclic Wind Pressure 



Referenced 

in code 

section number 

2603.4.1.9 

1715.5.2 

1609.1.2.2 



DOC 



PS-1-07 
PS-2-04 
PS 20-05 



U.S. Department of Commerce 
National Institute of Standards and Technology 
1401 Constitution Avenue NW 
Washington, DC 20230 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Structural Plywood 

Performance Standard for Wood-based Structural-use Panels 

American Softwood Lumber Standard 



2303.1.4, 2304.6.2, Table 2304.7(4), Table 2304.7(5), 

Table 2306.2.1 (1), Table 2306.2.1 (2) 

2303.1.4, 2304.6.2, 

Table 2304.7(5), Table 2306.2.1(1), Table 2306.2.1(2) 

1810.3.2.4, 2302.1, 2303.1.1 



598 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



DO 



u.s. Department of Justice 

950 Pennsylvania Avenue, NW 

Civil Rights Division, Disability Rights Section- NY A 

Washington, DC 20530 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



DOJ36CFRPart 1192 



American with Disabilities Act (ADA) Accessibility Guidelines for 
Transportation Vehicles (ADAAG) Department of Justice, 1991 



E109.2.4 



DOL 



u.S. Department of Labor 
c/o Superintendent of Documents 
U.S. Government Printing Office 
Washington, DC 20402-9325 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



29CFRPart 1910.1000 

(1974) 



Air Contaminants 



902.1 



DOTo 



u.S. Department of Transportation 
c/o Superintendent of Documents 
1200 New Jersey Avenue, SE 
Washington, DC 20402-9325 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



49 CFR Parts 100-185-2005 

49 CFR Parts 173.137 
(2005) 

49CFR-1998 



Hazardous Materials Regulations 

Shippers-General Requirements for Shipments and Packaging-Class 8-Assignment of Packing Group 

Specification of Transportation of Explosive and Other Dangerous Articles, 
UN 0335, UN 0336 Shipping Containers 



307.2 
307.2 
307.2 



EN 

Standard 
reference 
number 



European Committee for Standardization (EN) 
Central Secretariat 
Rue de Stassart 36 
B-10 50 Brussels 



Title 



Referenced 

in code 

section number 



EN 1081-98 



Resilient Floor Coverings-Determination of the Electrical Resistance 



406.5.2 



FEMA 



Federal Emergency Management Agency 
Federal Center Plaza 
500 C Street S.W. 
Washington, DC 20472 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



FIA-TB11-01 



Crawlspace Construction for Buildings Located in Special Flood Hazard Areas 



1805.1.2.1 



2009 INTERNATIONAL BUILDING CODE® 



599 



REFERENCED STANDARDS 



FM 



4450 (1989) 

4470 (1992) 
4474 (04) 

4880 (2005) 



Factory Mutual Global Research 
Standards Laboratories Department 
1301 Atwood Avenue, P.O. Box 7500 
Johnson, RI 02919 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Approval Standard for Class 1 Insulated Steel Deck Roofs-with 

Supplements through July 1992 
Approval Standard for Class 1 Roof Covers 
Evaluating the Simulated Wind Uplift Resistance of Roof Assemblies 

Using Static Positive and/or Negative Differential Pressures 
American National Standard for Evaluating Insulated Wall or Wall and Roof/ 

Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, 

Wall/Ceiling Coating Systems, Interior and Exterior Finish Systems 



1508.1, 2603.3, 2603.4.1.5 
1504.7 



1504.3.1 



2603.4, 2603.9 



GA 



Gypsum Association 
810 First Street N.E. #510 
Washington, DC 20002-4268 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



GA 216-07 
GA 600-06 



Application and Finishing of Gypsum Panel Products 
Fire-resistance Design Manual, 18th Edition 



Table 2508.1, 2509.2 
Table 720.1(1), Table 720.1(2), Table 720.1(3) 



HPVA 



Hardwood Plywood Veneer Association 
1825 Michael Faraday Drive 
Reston, VA 20190 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



HP-1-2004 



Standard for Hardwood and Decorative Plywood 



2303.3, 2304.6.2 



Hun 



U.S. Department of Housing and Urban Development 
451 7th Street, SW 
Washington, DC 20410 



Standard 

reference 

number 

HUD 24 CFR Part 3280 (1994) 



Title 

Manufactured Home Construction and Safety Standards 



Referenced 

in code 

section number 

G201 



ICC 



International Code Council, 
500 New Jersey Ave, NW 
6th Floor 
Washington, DC 20001 



Inc. 



Standard 
reference 

number 

ICC/ANSI All 7. 1-03 



ICC 300-07 
ICC 400-07 
ICC 500-08 
ICC 600-08 
IECC-09 



Title 

Accessible and Usable Buildings and Facilities 



Referenced 
in code 

section number 

406.2.2,907.5.2.3.4, 1007.9, 1010.1, 1010.6.5, 

1010.9,1011.3,1022.8,1101.2,1102.1,1104.4,1106.7,1107.2, 

1108.2.2,1108.2.3,1108.4.1.1,1108.4.1.2, 1108.4.1.4, 1108.4.1.5, 1109.1, 

1109.2, 1109.2.1.1, 1109.2.2, 1109.2.3, 1109.3, 1109.4, 1109.8, 1109.13, 

2902.4,3001.3,3008.13.1,3008.13.2,3411.6,3411.8.2, 3411.8.3, E101.2, E104.2, 

E104.2.1, E104.3, E104.3.4, E105.1, E105.2.1, E105.2.2, E105.3, E105.4, E105.6, 

E106.2, E106.3, E106.4, E106.4.9, E106.5, E107.2, E107.3, E108.3, E108.4, E109.2.1, 

E109.2.2.1, E109.2.2.2, E109.2.2.3, E109.2.3, E109.2.5, E109.2.6, E109.2.8, E110.2, E110.4 

1028.1.1, Table 1607.1, 3401.1 

2301.2 

423.1,423.2 

1609.1.1, 1609.1.1.1,2308.2.1 

101.4.6,1203.3.2,1301.1.1 



ICC Standard on Bleachers, Folding and Telescopic Seating and Grandstands 
Standard on Design and Construction of Log Structures 
ICC/NSSA Standard on the Design and Construction of Storm Shelters 
Standard for Residential Construction in High Wind Regions 
International Energy Conservation Code® 



600 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



IFC-09 



International Fire Code® 



IFGC-09 
IMC-09 



International Fuel Gas Code® 
International Mechanical Code® 



IPC-09 



IPMC-09 
IPSDC-09 
IRC-09 
IWUIC-09 
SBCCISSTD 11-97 



International Plumbing Code® 



ICC-continued 

101.4.5,102.6,201.3,307.1, Table 307.1(1), Table 307. 1(2), 307. 1.1,307.2, 

403.4.4,404.2,406.5.1,406.6.1,410.3.6,411.1, 412.1, 412.6.1, 413.1, 

414.1.1,414.1.2,414.1.2.1,414.2,414.2.5, Table 414.2.5(1), Table 414.2.5(2),414.3, 

414.5,414.5.1, Table 414.5.1,414.5.2,414.5.4,414.5.5,414.6,415.1, 415.2,415.3, 

415.3.1 , Table 415.3.1 , Table 415.3.2, 415.6, 415.6.1 , 415.6.1.4, 415.6.2, 415.6.2.3, 

415.6.2.5, 415.6.2.7, 415.6.2.8, 415.6.2.9, 415.6.3, 415.6.4, 415.7, 

415.8.1, 415.8.2.7, 415.8.5.1, 415.8.7.2, 415.8.9.3, 415.8.10.1, 416.1, 421.1 , 421.7, 

507.3, 707.1, 901.2, 901.3, 901.5, 901.6.2, 903.2.7. l,Table 903.2.11.6, 903.2.12 

903.5, 904.2.1 , 905.1, 905.3.6, 906.1 , 907.1.8, 907.2.5, 907.2.13.2, 907.2.15, 907.2.16, 

907.6.5, 907.8, 909.20, 910.2.2, 1001.3, 1203.4.2, 1203.5, 2702.1, 

2702.2.9, 2702.2.11, 2702.2.12, 2702.2.13, 2702.3, 3102.1, 3103.1, 3309.2, 

3401.3,3412.3.2,3412.6.8.1,3412.6.14,3412.6.14.1 

101.4.1,201.3, Table 307.1(1), 

415.6.3,2113.11.1.2,2113.15,2801.1,3401.3, A101.2 

101.4.2,201.3,307.1, Table 307.1 (1),406.4. 2,406.6.3, 

406.6.5, 409.3,412.6.6, 414.1.2, 414.3, 415.6.1.4, 415.6.2, 415.6.2.8, 

415.6.3,415.6.4,415.8.11.1,416.3,421.5,603.1,603.1.1,603.1.2, 

708.2, 716.2.2,716.5.4, 716.6.1,716.6.2, 716.6.3, 717.5, 719.1 , 719.7, 

903.2.11.4, 904.2.1,904.11, 908.6,909.1,909.10.2, 1015.5, 1018.5.1, 

1203.1, 1203.2.1, 1203.4.2, 1203.4.2.1, 1203.5, 1209.3,2304.5,2801.1, 

3004.3.1,3401.3,3412.6.7.1,3412.6.8,3412.6.8.1, A101.2 

101.4.3, 201.3, 415.6.4, 717.5, 903.3.5, 
912.5, 1206.3.3, 1503.4, 1805.4.3, 

2901.1, Table 2902.1,3305.1,3401.3, A101.2 

101.4.4, 102.6, 103.3,3401.3,3412.3.2 
101.4.3,2901.1,3401.3 

101.2,308.2,308.5,310.1,2308.1,3401.3 



International Property Maintenance Code® 

International Private Sewage Disposal Code® 

International Residential Code® 

International Wildland-Urban Interface Code™ 

Test Standard for Determining Wind Resistance of Concrete or Clay Roof Tiles 



Table 1505.1 
1716.2.1, 1716.2.2 



ISO 

Standard 
reference 
number 



International Organization for Standardization 
ISO Central Secretariat 
1 ch, de la Voie-Creuse, Case Postale 56 
CH-1211 Geneva 20, Switzerland 



Title 



Referenced 

in code 

section number 



ISO 8115-86 



Cotton Bales-Dimensions and Density 



Table 415.8.2.1.1 



National Association of Architectural Metal Manufacturers 



1VT A A lV/riV/l' 80 ° Roosevelt Road ' Bld §- C ' Suite 312 



Glen Ellyn, IL 60137 



Standard 
reference 
number 

FP 1001-97 



Title 

Guide Specifications for Design of Metal Flag Poles 



Referenced 

in code 

section number 

1609.1.1 



NCMA 



Standard 
reference 
number 



National Concrete Masonry Association 
13750 Sunrise Valley 
Herndon, VA 22071-4662 



Title 



Referenced 

in code 

section number 



TEK 5-84 (1996) 



Details for Concrete Masonry Fire Walls 



Table 720.1(2) 



2009 INTERNATIONAL BUILDING CODE® 



601 



REFERENCED STANDARDS 



NFPA 



National Fire Protection Association 
1 Battery march Park 
Quincy, MA 02169-7471 



Standard 
reference 

number 

10-07 

11-05 

12-05 

12A-04Halon 1301 

13-07 

13D-07 

13R-07 

14-07 

16-07 

17-02 

17A-02 

20-07 

30-08 

31-06 

32-07 

40-07 

58-08 

61-08 

70-08 

72-07 

80-07 

85-07 

92B-05 

99-05 

101-06 

105-07 

110-05 

111-05 

120-04 

170-06 

211-06 

252-03 

253-06 

257-07 
259-03 
265-07 

268-07 



285- 


-06 


286 


-06 


288- 


-07 


409 


-04 


418 


-06 


484- 


-06 



Title 

Portable Fire Extinguishers 

Low Expansion Foam 

Carbon Dioxide Extinguishing Systems 

Halon 1301 Fire Extinguishing Systems 

Installation of Sprinkler Systems 

Installation of Sprinkler Systems in One- and Two-family Dwellings 

and Manufactured Homes 
Installation of Sprinkler Systems in Residential Occupancies Up to and 

Including Four Stories in Height 
Installation of Standpipe and Hose System 

Installation of Foam-water Sprinkler and Foam-water Spray Systems 
Dry Chemical Extinguishing Systems 
Wet Chemical Extinguishing Systems 
Installation of Stationary Pumps for Fire Protection 
Flammable and Combustible Liquids Code 
Installation of Oil-burning Equipment 
Dry Cleaning Plants 

Storage and Handling of Cellulose Nitrate Film 
Liquefied Petroleum Gas Code 
Prevention of Fires and Dust Explosions in Agricultural and Food Product Facilities 



Referenced 
in code 

section number 

906.2,906.3.2,906.3.4, Table 906.3(1), Table 906.3(2) 

904.7 

904.8, 904.11 

904.9 

708.2, 903.3.1.1, 903.3.2, 903.3.5.1.1, 

903.3.5.2,904.11,905.3.4,907.6.3,1613.6.3 



903.3.1.3, 903.3.5.1.1 

903.3.1.2, 903.3.5.1.1, 903.3.5.1.2, 903.4 

905.2, 905.3.4, 905.4.2, 905.6.2, 905.8 

904.7,904.11 

904.6, 904.11 

904.5, 904.11 

913.1,913.2.1,913.5 

.415.3 

2113.15 

415.6.4 

.409.1 

.415.6.3 

415.6.1 



National Electrical Code 



National Fire Alarm Code 



Fire Doors and Other Opening Protectives 



108.3, 415.8.2.8.2, 904.3.1, 907.6.1, 909.12.1, 

909.16.3,1205.4.1,2701.1,3401.3, H106.1, H106.2, K101, Klll.l 

901.6,903.4.1,904.3.5,907.2,907.2.5,907.2.11, 

907.2.13.2,907.3,907.3.3,907.3.4,907.5.2.1.2, 

907.5.2.2,907.6,907.6.1,907.6.5,907.7, 907.7.1, 907.7.2, 911.1.5, 3006.5, 3007.6 

410.3.5,508.2.5.2,715.4,715.4.5, 
715.4.6,715.4.7.1,715.4.8.2,715.5,715.5.5,1008.1.4.3 

.415.6.1 



Boiler and Combustion System Hazards Code 

(Note: NFPA 8503 has been incorporated into NFPA 85) 
Smoke Management Systems in Malls, Atria and Large Spaces 
Standard for Health Care Facilities 
Life Safety Code 

Standard for the Installation of Smoke Door Assemblies 
Emergency and Standby Power Systems 

Stored Electrical Energy Emergency and Standby Power Systems 
Coal Preparation Plants 

Standard for Fire Safety and Emergency Symbols 
Chimneys, Fireplaces, Vents and Solid Fuel-burning Appliances 
Standard Methods of Fire Tests of Door Assemblies 
Test for Critical Radiant Flux of Floor Covering Systems Using a 

Radiant Heat Energy Source 
Standard for Fire Test for Window and Glass Block Assemblies 
Test Method for Potential Heat of Building Materials 
Method of Fire Tests for Evaluating Room Fire Growth Contribution of 

Textile Wall Coverings on Full Height Panels and Walls 
Standard Test Method for Determining Ignitibility of 

Exterior Wall Assemblies Using a Radiant Heat Energy Source 1406.2.1, 1406.2.1.1, 1406.2.1.2,2603.5.7, D105.1 

Standard Method of Test for the Evaluation of Flammability Characteristics of 

Exterior Nonload-bearingWall Assemblies Containing Combustible Components 
Standard Method of Fire Test for Evaluating Contribution of Wall and 

Ceiling Interior Finish to Room Fire Growth 
Standard Method of Fire Tests of Floor Fire Door Assemblies 

Installed Horizontally in Fire-resistance-rated Floor Systems 712.8 

Aircraft Hangars .412.4.6, Table 412.4.6, 412.4.6.1, 412.6.5 

Standard for Heliports .412.7.4 

Combustible Metals 415.6.1 



909.8 

.407.9 

1028.6.2 

405.4.2,715.4.3.1,909.20.4.1 

2702.1 

2702.1 

.415.6.1 

1024.2.6.1 

2112.5 

715.3,715.4.1,715.4.2,715.4.3,715.4.7.3.1 

402.12.1,406.6.4,804.2,804.3 

715.3,715.4.3.2,715.5,715.5.1,715.5.2,715.5.9.1 

2603.4.1.10,2603.5.3 

803.1.3, 803.1.3.1 



1407.10.4, 2603.5.5 



402.16.4,803.1.2,803.1.2.1,803.9,2603.4,2603.9 



602 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



654-06 

655-07 
664-07 
701-04 



704-07 

1124-06 

2001-08 



NFPA-continued 

Prevention of Fire & Dust Explosions from the Manufacturing, 

Processing and Handling of Combustible Particulate Solids 415.6.1 

Prevention of Sulfur Fires and Explosions .415.6.1 

Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities 415.6.1 

Standard Methods of Fire Tests for Flame-propagation of Textiles and Films 402.12.1,410.3.6,801.1.4,806.1, 

806.1.2,806.2,3102.3,3102.3.1, 
3102.6.1.1,3105.4, D102.2.8, H106.1.1 

Standard System for the Identification of the Hazards of Materials for Emergency Response 414.7.2,415.2 

Manufacture, Transportation and Storage of Fireworks and Pyrotechnic Articles 415.3.1 

Clean Agent Fire Extinguishing Systems 904.10 



PCI 



Precast Prestressed Concrete Institute 
209 W. Jackson Boulevard, Suite 500 
Chicago, IL 60606-6938 



Standard 
reference 

number 

MNL 124-89 
MNL 128-01 



Title 

Design for Fire Resistance of Precast Prestressed Concrete 
Recommended Practice for Glass Fiber Reinforced Concrete Panels 



Referenced 

in code 

section number 

721.2.3.1 
1903.2 



PTL 

Standard 
reference 
number 



Post-Tensioning Institute 

8601 North Black Canyon Highway, Suite 103 

Phoenix, AZ 85021 



Title 



Referenced 

in code 

section number 



PTI-2007 
PTI-2007 



Standard Requirements for Analysis of Shallow Concrete Foundations on Expansive Soils, Third Edition 
Standard Requirements for Design of Shallow Post-tensioned Concrete Foundation on 
Expansive Soils, Second Edition 



18 



S.6.2 



16.2 



RMI 



Rack Manufacturers Institute 
8720 Red Oak Boulevard, Suite 201 
Charlotte, NC 28217 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



ANSI/MH16.1-08 



Specification for Design, Testing and Utilization of Industrial Steel Storage Racks 



2208.1 



SDI 



Steel Deck Institute 

P. O. Box 25 

Fox River Grove, IL 60021 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



ANSI/NCI. 0-06 
ANSI/RD 1.0-06 



Standard for Noncomposite Steel Floor Deck 
Standard for Steel Roof Deck. 



2209.2.2,2209.2.2.1 
2209.2.3 



S I 



CJ-1.0-06 
JG-1.1-05 
K-l.1-05 
LH/DLH-1.1-05 



Steel Joist Institute 

1173B London Links Drive 

Forest, VA 24551 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Standard Specification for Composite Steel Joists, CJ-series 
Standard Specification for Joist Girders 
Standard Specification for Open Web Steel Joists, K-series 
Standard Specification for Longspan Steel Joists, LH-series 
and Deep Longspan Steel Joists, DLH-series 



1604.3.3,2203.2,2206.1 
1604.3.3,2203.2,2206.1 
1604.3.3, 2203.2, 2206.1 

1604.3.3,2203.2,2206.1 



2009 INTERNATIONAL BUILDING CODE® 



603 



REFERENCED STANDARDS 



SPRI 



Single- Ply Roofing Institute 

411 Waverly Oaks Road, Suite 33 IB 

Waltham, MA 02452 



Standard 
reference 

number 

SPRIIANSIIES-I-03 
RP-4-02 



Title 

Wind Design Standard for Edge Systems Used with Low Slope Roofing Systems 
Wind Design Guide for Ballasted Single-ply Roofing Systems 



Referenced 

in code 

section number 

1504.5 

1504.4 



TIA 



Telecommunications Industry Association 
2500 Wilson Boulevard 
Arlington, VA 22201-3834 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



TIA-222-G-05 



Structural Standards for Steel Antenna Towers and Antenna Supporting 
Structures including-Addendum 1, 222-G-l, Dated 2007 



1609.1.1,3108.1,3108.2 



TMS 



0216-97 



0302-07 
402-08 



602-08 



The Masonry Society 
3970 Broadway, Unit 201-D 
Boulder, CO 80304-1135 



Standard 




Referenced 


reference 




in code 


number 


Title 


section number 



Standard Method for Determining Fire Resistance of Concrete and 

Masonry Construction Assemblies Table 720.1 (2), 721.1 

Standard Method for Determining the Sound Transmission Class Rating for Masonry Walls 1207.2.1 

Building Code Requirements for Masonry Structures 1405.6, 1405.6.2, 1405.10, 1604.3.4, Table 1703.4.5.3, 

1704.5, 1704.5.1, Table 1704.5.1, 1704.5.2, 1704.5.3, 

1807.1.6.3.2, 1808.9,2101.2.2,2101.2.3,2101.2.4,2101.2.5, 

2101.2.6,2103.1.3.6,2106.1,2107.1,2107.2,2107.3,2107.4, 

2107.5,2108.1,2108.2,2108.3,2109.1,2109.1.1, 2109.2, 2109.2.1, 2109.3, 2110.1 

Specification for Masonry Structures 1405.6.1, Table 1704.5.1, Table 1704.5.3, 1807.1.6.3, 

2103.8,2103.11,2103.12,2103.13,2104.1,2104.1.1,2104.1.2 
2104.1.3,2104.2,2104.3,2104.4,2105.2.2.1.1, 2105.2.2.1.2, 2105.2.2.1.3 



TPI 



Truss Plate Institute 

218 N. Lee Street, Suite 312 

Alexandria, VA 22314 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



TPII-2007 



National Design Standards for Metal-plate-connected Wood Truss Construction 



2303.4.6, 2306.1 



UL 

Standard 
reference 
number 



Underwriters Laboratories, Inc. 
333 Pfingsten Road 
Northbrook, IL 60062-2096 



Title 



Referenced 

in code 

section number 



9-2000 
10A-98 
10B-97 
10C-98 
14B-98 

14C-06 
103-01 

127-96 



Fire Tests ofWindow Assemblies-with Revisions through April 2005 715.3,715.4.3.2,715.5,715.5.1,715.5.2,715.5.9.1 
Tin Clad Fire Doors-with Revisions through March 2003 715.4 
Fire Tests of Door Assemblies-with Revisions through October 2001. 715.4.2 
Positive Pressure Fire Tests of Door Assemblies-with Revisions through November 2001 715.4.1,715.4.3 
Sliding Hardware for Standard Horizontally-mounted Tin Clad Fire Doors- 
with Revisions through July 2000 715.4 
Swinging Hardware for Standard Tin Clad Fire Doors Mounted Singly and in Pairs 715.4 
Factory-built Chimneys, for Residential Type and Building Heating Appliances- 

with Revisions through June 2006 717.2.5.1 

Factory-built Fireplaces-with Revisions through November 2006 717.2.5.1,2111.11 



604 



2009 INTERNATIONAL BUILDING CODE® 



REFERENCED STANDARDS 



199E-04 



217-06 
263-03 



268-06 
300-05 
305-07 
325-02 

555-2006 

555C-2006 

555S-99 

580-2006 

641-95 

710B-04 

723-03 



790-04 
793-03 

864-03 

924-06 

1040-96 

1256-02 

1479-03 

1482-96 

1715-97 

1777-04 

1784-01 

1897-04 
1975-06 
1994-04 

2017-2000 

2079-04 
2200-04 



UL-continued 

Outline of Investigation for Fire Testing of Sprinklers and Water Spray Nozzles for 
Protection of Deep Fat Fryers 

Single and Multiple Station Smoke Alarms-with Revisions through August 2005 

Standard for Fire Test of Building Construction and Materials 



904.11.4.1 

907.2.11 

703.2, 703.2.1, 703.2.3, 703.3, 703.5, 



704.12,705.7,707.7,712.3.2,713.3.1,713.4.1.1, 

714.1,715.2,716.5.2,716.5.3,716.6.1, Table 716.6.2(1), 

Table 720.1(1), 1407. 10.2,2103. 2,2603.4,2603. 5.1 

Smoke Detectors for Fire Protective Signaling Systems-with Revisions through January 1999 407.7,907.2.6.2 

Fire Testing of Fire Extinguishing Systems for Protection of Restaurant Cooking Areas 904.11 

Panic Hardware 1008.1.10 

Door, Drapery, Gate, Louver and Window Operations and Systems- 
with Revisions through February 2006 .406. 1 .5, 3 1 10.4 

Fire Dampers 716.3 

Ceiling Dampers 716.3, 716.6.2 

Smoke Dampers-with Revisions through July 2006 716.3,716.3.1.1 

Test for Uplift Resistance of Roof Assemblies 1504.3.1, 1504.3.2 

Type L Low-temperature Venting Systems-with Revisions through August 2005 2113.11.1.4 

Recirculating Systems-with Revisions through April 2006 904.11 

Standard for Test for Surface Burning Characteristics of Building Materials- 

with Revisions through May 2005 402.11,402.16.4,406.5.3,703.4.2,719.1, 

719.4,802.1,803.1.1,803.9,806.5,1407.9, 1407.10.1,2303.2,2603.3, 
2603.4.1.13,2603.5.4,2604.2.4,2606.4,3105.4, D102.2.8 

1505.1, 2603.6, 2610.2, 2610.3 

910.3.1 

909.12 

1011.4 

1407.10.3, 2603.4, 2603.9 

1508.1, 2603.3, 2603.4.1.5 

702.1, 713.3.1.2, 713.3.2, 713.4.1.1.2 

2112.2,2112.5 

1407.10.2,1407.10.3,2603.4,2603.9 

2113.11.1, 2113.19 

708.14.1,711.5.2, 

715.4.3.1, 715.4.6.1, 715.4.6.3,3007.4.3 

1504.3.1 

402.11, 402.12.1, 402.16.5 

411.7, 1024.2.1, 

1024.2.3, 1024.2.4, 1024.4 



Standard Test Methods for Fire Tests of Roof Coverings 

Standards for Automatically Operated Roof Vents for Smoke and Heat- 
with Revisions through April 2004 

Standards for Control Units and Accessories for Fire Alarm Systems- 
with Revisions through March 2006 

Standard for Safety Emergency Lighting and Power Equipment. 

Fire Test of Insulated Wall Construction-with Revisions through June 2001. 

Fire Test of Roof Deck Construction-with Revisions through January 2007 

Fire Tests of Through-penetration Firestops-with Revisions through April 2007 

Solid-fuel-type Room Heater-with Revisions through November 2006 

Fire Test of Interior Finish Material- with Revisions through March 2004 

Chimney Liners 

Air Leakage Tests of Door Assemblies- with Revisions through December 2004 



Uplift Tests for Roof Covering Systems 

Fire Test of Foamed Plastics Used for Decorative Purposes 

Standard for Luminous Egress Path Marking Systems-with Revisions through February 2005 



Standards for General-purpose Signaling Devices and Systems- 
with Revisions through August 2005 

Tests for Fire Resistance of Building Joint Systems-with Revisions through March 2006 

Stationary Engine Generator Assemblies-with Revisions through July 2004 



3109.4.1.8 

702.1,714.3,714.6 

2702.1.1 



ULC 



Underwriters Laboratories of Canada 

7 Underwriters Road 

Toronto, Ontario, Canada M1R3B4 



Standard 
reference 
number 


Title 


Referenced 

in code 

section number 


CAN/ULCS102. 2-1988 


Standard Method of Test for Surface Burning Characteristics of Flooring, 

Floor Coverings and Miscellaneous Materials and Assemblies-with 2000 Revisions 


719.4 



2009 INTERNATIONAL BUILDING CODE® 



605 



REFERENCED STANDARDS 



use 



United States Code 
c/o Superintendent of Documents 
U.S. Government Printing Office 
Washington, DC 20402-9325 



Standard 
reference 
number 



Title 



Referenced 

in code 

section number 



18 USC Part 1, Ch.40 



Importation, Manufacture, Distribution and Storage of Explosive Materials 



307.2 



WDMA 



Standard 
reference 
number 



Window and Door Manufacturers Association 
1400 East Touhy Avenue #470 
Des Plaines, IL 60018 



Title 



Referenced 

in code 

section number 



AAMA/WDMA/CSA 
1011I.S.2/A440-08 



Specifications for Windows, Doors and Unit Skylights 



1715.5.1, 2405.5 



WRI 

Standard 
reference 
number 



Wire Reinforcement Institute, Inc. 
942 Main Street, Suite 300 
Hartford, CT 06103 



Title 



Referenced 

in code 

section number 



WRI/CRSI-81 



Design of Slab-on-ground Foundations-with 1996 Update 



1808.6.2 



606 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX A 

EMPLOYEE QUALIFICATIONS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION A101 
BUILDING OFFICIAL QUALIFICATIONS 

AIOI.I Building official. The bUilding official shall have at 
least 10 years' experience or equivalent as an architect, engi- 
neer' inspector, contractor or superintendent of construction, or 
any combination of these, five years of which shall have been 
supervisory experience. The building official should be certi- 
fied as a building official through a recognized certification 
program. The building official shall be appointed or hired by 
the applicable governing authority. 

AIOI.2 Chief inspector. The bUilding official can designate 
supervisors to administer the provisions of the International 
Building, Mechanical and Plumbing Codes and International 
Fuel Gas Code. Each supervisor shall have at least 10 years' 
experience or equivalent as an architect, engineer, inspector, 
contractor or superintendent of construction, or any combina- 
tion of these, five years of which shall have been in a supervi- 
sory capacity. They shall be certified through a recognized 
certification program for the appropriate trade. 

AIOI.3 Inspector and plans examiner. The bUilding official 
shall appoint or hire such number of officers, inspectors, assis- 
tants and other employees as shall be authorized by the juris- 
diction. A person shall not be appointed or hired as inspector of 
construction or plans examiner who has not had at least 5 years' 
experience as a contractor, engineer, architect, or as a superin- 
tendent, foreman or competent mechanic in charge of construc- 
tion. The inspector or plans examiner shall be certified through 
a recognized certification program for the appropriate trade. 

AIOI.4 Termination of employment. Employees in the posi- 
tion of bUilding official, chief inspector or inspector shall not be 
removed from office except for cause after full opportunity has 
been given to be heard on specific charges before such applica- 
ble governing authority. 



SECTION A102 
REFERENCED STANDARDS 

IBC-09 International Building Code AI01.2 

IMC-09 International Mechanical Code AI01.2 

IPC-09 International Plumbing Code AI01.2 

IFGC-09 International Fuel Gas Code AI01 .2 



2009 INTERNATIONAL BUILDING CODE® 607 



608 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX B 

BOARD OF APPEALS 



The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION 8101 
GENERAL 

BI01.1 Application. The application for appeal shall be filed 
on a form obtained from the bUilding official within 20 days 
after the notice was served. 

BI01.2 Membership of board. The board of appeals shall 
consist of persons appointed by the chief appointing authority 
as follows: 

1 . One for five years ; one for four years ; one for three years ; 
one for two years; and one for one year. 

2. Thereafter, each new member shall serve for five years 
or until a successor has been appointed. 

The bUilding official shall be an ex officio member of said 
board but shall have no vote on any matter before the board. 

BIOL 2.1 Alternate members. The chief appointing 
authority shall appoint two alternate members who shall be 
called by the board chairperson to hear appeals during the 
absence or disqualification of a member. Alternate mem- 
bers shall possess the qualifications required for board 
membership and shall be appointed for five years, or until a 
successor has been appointed. 

BIOL 2. 2 Qualifications. The board of appeals shall consist 
of five individuals, one from each of the following profes- 
sions or disciplines: 

1. Registered design professional with architectural 
experience or a builder or superintendent of building 
construction with at least ten years' experience, five 
of which shall have been in responsible charge of 
work. 

2. Registered design professional with structural engi- 
neering experience 

3. Registered design professional with mechanical and 
plumbing engineering experience or a mechanical 
contractor with at least ten years' experience, five of 
which shall have been in responsible charge of work. 

4. Registered design professional with electrical engi- 
neering experience or an electrical contractor with at 
least ten years' experience, five of which shall have 
been in responsible charge of work. 

5. Registered design professional with fire protection 
engineering experience or a fire protection contractor 
with at least ten years' experience, five of which shall 
have been in responsible charge of work. 

BIOL 2. 3 Rules and procedures. The board is authorized 
to establish policies and procedures necessary to carry out 
its duties. 



BI01.2.4 Chairperson. The board shall annually select one 
of its members to serve as chairperson. 

BIOL 2. 5 Disqualification of member. A member shall not 
hear an appeal in which that member has a personal, profes- 
sional or financial interest. 

BI01.2.6 Secretary. The chief administrative officer shall 
designate a qualified clerk to serve as secretary to the board. 
The secretary shall file a detailed record of all proceedings 
in the office of the chief administrative officer. 

BI01.2.7 Compensation of members. Compensation of 
members shall be determined by law. 

BIOL 3 Notice of meeting. The board shall meet upon notice 
from the chairperson, within 10 days of the filing of an appeal 
or at stated periodic meetings. 

BI01.3.1 Open hearing. All hearings before the board 
shall be open to the public. The appellant, the appellant's 
representative, the building official and any person whose 
interests are affected shall be given an opportunity to be 
heard. 

BIOL 3. 2 Procedure. The board shall adopt and make avail- 
able to the public through the secretary procedures under 
which a hearing will be conducted. The procedures shall not 
require compliance with strict rules of evidence, but shall 
mandate that only relevant information be received. 

BIOL 3. 3 Postponed hearing. When five members are not 
present to hear an appeal, either the appellant or the appel- 
lant's representative shall have the right to request a post- 
ponement of the hearing. 

BIOL 4 Board decision. The board shall modify or reverse the 
decision of the bUilding official by a concurring vote of 
two-thirds of its members. 

BIOL 4. 1 Resolution. The decision of the board shall be by 
resolution. Certified copies shall be furnished to the appel- 
lant and to the building official. 

BI01.4.2 Administration. The building official shall take 
immediate action in accordance with the decision of the 
board. 



2009 INTERNATIONAL BUILDING CODE® 



609 



610 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX C 

GROUP U-AGRICULTURAL BUILDINGS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION C101 
GENERAL 

CIOI.I Scope. The provisions of this appendix shall apply 
exclusively to agricultural buildings. Such buildings shall be 
classified as Group U and shall include the following uses : 

1. Livestock shelters or buildings, including shade struc- 
tures and milking barns. 

2. Poultry buildings or shelters. 

3. Barns. 

4. Storage of equipment and machinery used exclusively in 
agriculture. 

5. Horticultural structures, including detached production 
greenhouses and crop protection shelters. 

6. Sheds. 

7. Grain silos. 

8. Stables. 



SECTION C102 
ALLOWABLE HEIGHT AND AREA 

CI02. 1 General. Buildings classified as Group U Agricultural 
shall not exceed the area or height limits specified in Table 
CI02.1. 

C 102.2 One-story unlimited area. The area of a one-story 
Group U agricultural building shall not be limited if the build- 



ing is surrounded and adjoined by public ways or yards not less 
than 60 feet (18 288 mm) in width. 

CI02.3 Two-story unlimited area. The area of a two-story 
Group U agricultural building shall not be limited if the build- 
ing is surrounded and adjoined by public ways oxyardsnoi less 
than 60 feet (18 288 mm) in width and is provided with an 
approved automatic sprinkler system throughout in accordance 
with Section 903.3.1.1. 



SECTION C103 
MIXED OCCUPANCIES 

C 103.1 Mixed occupancies. Mixed occupancies shall be pro- 
tected in accordance with Section 508 . 



SECTION C104 
EXITS 

C 104.1 Exit facilities. Exits shall be provided in accordance 
with Chapters 10 and 11. 

Exceptions: 

1. The maximum travel distance from any point in the 
building to an approved exit shall not exceed 300 feet (91 
440 mm). 

2. One exit is required for each 15,000 square feet (1393.5 
m 2 ) of area or fraction thereof. 



TABLE C1 02.1 -BASIC ALLOWABLE AREA FOR A GROUP U, 
ONE STORY IN HEIGHT AND MAXIMUM HEIGHT OF SUCH OCCUPANCY 









II | III and IV 






V 




A | 


B 


1 A 


1 B | III A and IV | 


IIIB 


1 A 


1 


B 


ALLOWABLE AREA (square feet)a 


Unlimited | 


60,000 


1 27,100 


1 18,000 | 27,100 | 


18,000 


1 21,100 


1 


12,000 


MAXIMUM HEIGHT IN STORIES 


Unlimited | 


12 


1 4 


1 2 , 4 , 


2 


1 3 


1 


2 


MAXIMUM HEIGHT IN FEET 


Unlimited | 


160 


65 


1 55 | 65 | 


55 


50 


1 


40 



For SI : 1 square foot = 0.0929 m 2 - 

a. See Section C102 for unlimited area under certain conditions. 



2009 INTERNATIONAL BUILDING CODE® 



611 



612 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX D 

FIRE DISTRICTS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION 0101 
GENERAL 

DIOl.l Scope. The fire district shall include such territory or 
portion as outlined in an ordinance or law entitled "An Ordi- 
nance (Resolution) Creating and Establishing a Fire District." 
Wherever, in such ordinance creating and establishing a fire 
district, reference is made to the fire district, it shall be con- 
strued to mean the fire district designated and referred to in this 
appendix. 

DIOl.1.1 Mapping. The fire district complying with the 
provisions of Section D 101.1 shall be shown on a map that 
shall be available to the public. 

DI01.2 Establishment of area. For the purpose of this code, 
the fire district shall include that territory or area as described in 
Sections D 101. 2.1 through D101.2.3. 

DIOl.2.1 Adjoining blocks. Two or more adjoining blocks, 
exclusive of intervening streets, where at least 50 percent of 
the ground area is built upon and more than 50 percent of the 
built-on area is devoted to hotels and motels of Group R-l ; 
Group B occupancies; theaters, nightclubs, restaurants of 
Group A-I and A-2 occupancies; garages, express and 
freight depots, warehouses and storage buildings used for 
the storage of finished products (not located with and form- 
ing a part of a manufactured or industrial plant); or Group S 
occupancy. Where the average height of a building is two 
and one-half stories or more, a block should be considered if 
the ground area built upon is at least 40 percent. 

DIOl.2.2 Buffer zone. Where four contiguous blocks or 
more comprise a fire district, there shall be a buffer zone of 
200 feet (60 960 mm) around the perimeter of such district. 
Streets, rights-of-way and other open spaces not subject to 
building construction can be included in the 200-foot (60 
960 mm) buffer zone. 

DIOl.2.3 Developed blocks. Where blocks adjacent to the 
fire district have developed to the extent that at least 25 per- 
cent of the ground area is built upon and 40 percent or more 
of the built-on area is devoted to the occupancies specified 
in Section D 101. 2.1, they can be considered for inclusion in 
the fire district, and can form all or a portion of the 200- foot 
(60 960 mm) buffer zone required in Section D 101. 2. 2. 



SECTION 0102 
BUILDING RESTRICTIONS 

D 102.1 Types of construction permitted. Within the fire dis- 
trict every building hereafter erected shall be either Type I, II, 
III or IV, except as permitted in Section D104. 



DI02.2 Other specific requirements. 

DI02.2.1 Exterior walls. Exterior walls of buildings 
located in the fire district shall comply with the require- 
ments in Table 601 except as required in Section D 102. 2. 6. 

DI02.2.2 Group H prohibited. Group H occupancies shall 
be prohibited from location within the fire district. 

DI02.2.3 Construction type. Every building shall be con- 
structed as required based on the type of construction indi- 
cated in Chapter 6. 

DI02.2.4 Roof covering. Roof covering in the fire district 
shall conform to the requirements of Class A or B roof cov- 
erings as defined in Section 1505. 

DI02.2.5 Structural fire rating. Walls, floors, roofs and 
their supporting structural members shall be a minimum of 
I-hour fire-resistance-rated construction. 

Exceptions: 

1. Buildings of Type IV construction. 

2 Buildings equipped throughout with an automatic 
sprinkler system in accordance with Section 
903.3.1.1. 

3. Automobile parking structures. 

4. Buildings surrounded on all sides by a permanently 
open space of not less than 30 feet (9144 mm). 

5. Partitions complying with Section 603.1, Item 10. 

DI02.2.6 Exterior walls. Exterior load-bearing walls of 
Type II buildings shall have a fire-resistance rating of 2 
hours or more where such walls are located within 30 feet 
(9144 mm) of a common property line or an assumed prop- 
erty line. Exterior nonload-bearing walls of Type II build- 
ings located within 30 feet (9144 mm) of a common 
property line or an assumed property line shall have 
fireresistance ratings as required by Table 601, but not less 
than 1 hour. Exterior walls located more than 30 feet (9144 
mm) from a common property line or an assumed property 
line shall comply with Table 601. 

Exception: In the case of one-story buildings that are 
2,000 square feet (186 m 2 ) or less in area, exterior walls 
located more than 15 feet (4572 mm) from a common 
property line or an assumed property line need only com- 
ply with Table 601. 

DI02.2.7 Architectural trim. Architectural trim on build- 
ings located in the fire district shall be constructed of 
approved noncombustible materials or fire-retardant- 
treated wood. 



2009 INTERNATIONAL BUILDING CODE® 



613 



APPENDIX D 



DI02.2.8 Permanent canopies. Permanent canopies are 
permitted to extend over adjacent open spaces provided all 
of the following are met: 

1. The canopy and its supports shall be of noncombusti- 
ble material, fire-retardant-treated wood, Type IV 
construction or of I-hour fire-resistance-rated con- 
struction. 

Exception: Any textile covering for the canopy 
shall be flame resistant as determined by tests con- 
ducted in accordance with NFPA 701 after both 
accelerated water leaching and accelerated weath- 
ering. 

2. Any canopy covering, other than textiles, shall have a 
flame spreadindexnot greater than 25 when tested in 
accordance with ASTM E 84 or UL 723 in the form 
intended for use. 

3. The canopy shall have at least one long side open. 

4. The maximum horizontal width of the canopy shall 
not exceed 15 feet (4572 mm). 

5. The fire resistance of exterior walls shall not be 
reduced. 

DI02.2.9 Roof structures. Structures, except aerial sup- 
ports 12 feet (3658 mm) high or less, flagpoles, water tanks 
and cooling towers, placed above the roof of any building 
within the fire district shall be of noncombustible material 
and shall be supported by construction of noncombustible 
material. 

DI02.2.10 Plastic signs. The use of plastics complying 
with Section 2611 for signs is permitted provided the struc- 
ture of the sign in which the plastic is mounted or installed is 
noncombustible. 

DI02.2. 1 1 Plastic veneer. Exterior plastic veneer is not per- 
mitted in the fire district. 



SECTION D103 
CHANGES TO BUILDINGS 

D 103.1 Existing buildings within the fire district. An exist- 
ing building shall not hereafter be increased in height or area 
unless it is of a type of construction permitted for new buildings 
within the fire district or is altered to comply with the require- 
ments for such type of construction. Nor shall any existing 
building be hereafter extended on any side, nor square footage 
or floors added within the existing building unless such modifi- 
cations are of a type of construction permitted for new build- 
ings within the fire district. 

DI03.2 Other alterations. Nothing in Section D103.1 shall 
prohibit other alterations within the fire district provided there 
is no change of occupancy that is otherwise prohibited and the 
fire hazard is not increased by such alteration. 

DI03.3 Moving buildings. Buildings shall not hereafter be 
moved into the fire district or to another lot in the fire district 



unless the building is of a type of construction permitted in the 
fire district. 



SECTION D104 

BUILDINGS LOCATED PARTIALLY 

IN THE FIRE DISTRICT 

D 104.1 General. Any building located partially in the fire dis- 
trict shall be of a type of construction required for the fire dis- 
trict, unless the major portion of such building lies outside of 
the fire district and no part is more than 10 feet (3048 mm) 
inside the boundaries of the fire district. 



SECTION D105 

EXCEPTIONS TO RESTRICTIONS 

IN FIRE DISTRICT 

DI05.1 General. The preceding provisions of this appendix 
shall not apply in the following instances: 

1. Temporary buildings used in connection with duly 
authorized construction. 

2. A private garage used exclusively as such, not more 
than one story in height, nor more than 650 square feet 
(60 m 2 ) in area, located on the same lot with a dwelling. 

3. Fences not over 8 feet (2438 mm) high. 

4. Coal tipples, material bins and trestles of Type IV con- 
struction. 

5. Water tanks and cooling towers conforming to Sections 
1509.3 and 1509.4. 

6. Greenhouses less than 15 feet (4572 mm) high. 

7. Porches on dwellings not over one story in height, and 
not over 10 feet (3048 mm) wide from the face of the 
building, provided such porch does not come within 5 
feet (1524 mm) of any property line. 

8. Sheds open on a long side not over 15 feet (4572 mm) 
high and 500 square feet (46 m 2 ) in area. 

9. One- and two-family dwellings where of a type of con- 
struction not permitted in the fire district can be 
extended 25 percent of the floor area existing at the 
time of inclusion in the fire district by any type of con- 
struction permitted by this code. 

10. Wood decks less than 600 square feet (56 m 2 ) where 
constructed of 2-inch (51 mm) nominal wood, pressure 
treated for exterior use. 

11. Wood veneers on exterior walls conforming to Section 
1405.5. 

12. Exterior plastic veneer complying with Section 2605.2 
where installed on exterior walls required to have a 
fire-resistance rating not less than 1 hour, provided the 
exterior plastic veneer does not exhibit sustained flam- 
ing as defined in NFPA 268. 



514 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX D 



SECTION D106 
REFERENCED STANDARDS 



ASTM E 84-04 



Test Method for Surface 
Burning Characteristics of 
Building Materials 



DI02.2.8 



NFPA 268-01 Test Method for Determining 
Ignitability of Exterior Wall 
Assemblies Using a Radiant 
Heat Energy Source 



DI0S.1 



NFPA 701-99 Methods of Fire Tests for 

Flame-Propagation of Textiles 
and Films 



DI02.2.8 



I UL 723-03 



Standard for Test for 
Surface Burning Characteristics of 
Building Materials, with Revisions 
through May 2005 



DI02.2.8 



2009 INTERNATIONAL BUILDING CODE® 



615 



616 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX E 

SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION E101 
GENERAL 

EIOl.l Scope. The provisions of this appendix shall control 
the supplementary requirements for the design and construc- 
tion of facilities for accessibility to physically disabled per- 
sons. 

EI01.2 Design. Technical requirements for items herein shall 
comply with this code and ICC A117.1. 



SECTION E102 
DEFINITIONS 

EI02.1 General. The following words and terms shall, for the 
purposes of this appendix, have the meanings shown herein. 

CLOSED-CIRCUIT TELEPHONE. A telephone with a 
dedicated line such as a house phone, courtesy phone or phone 
that must be used to gain entrance to a facility. 

MAILBOXES. Receptacles for the receipt of documents, 
packages or other deliverable matter. Mailboxes include, but 
are not limited to, post office boxes and receptacles provided by 
commercial mail-receiving agencies, apartment houses and 
schools. 

TRANSIENT LODGING. A building, facility or portion 
thereof, excluding inpatient medical care facilities and 
long-term care facilities, that contains one or more dwelling 
units or sleeping units. Examples of transient lodging include, 
but are not limited to, resorts, group homes, hotels, motels, dor- 
mitories, homeless shelters, halfway houses and social service 
lodging. 



SECTION E103 
ACCESSIBLE ROUTE 

EI03. 1 Raised platforms. In banquet rooms or spaces where a 
head table or speaker's lectern is located on a raised platform, 
an accessible route shall be provided to the platform. 



SECTION E104 
SPECIAL OCCUPANCIES 

EI04. 1 General. Transient lodging facilities shall be provided 
with accessible features in accordance with Sections E104.2 
and E104.3. Group 1-3 occupancies shall be provided with 
accessible features in accordance with Sections E104.3 and 
E104.4. 



EI04.2 Accessible beds. In rooms or spaces having more than 
25 beds, 5 percent of the beds shall have a clear floor space 
complying with ICC A117.1. 

EI04.2.1 Sleeping areas. A clear floor space complying 
with ICC All 7.1 shall be provided on both sides of the 
accessible bed. The clear floor space shall be positioned for 
parallel approach to the side of the bed. 

Exception: This requirement shall not apply where a 
single clear floor space complying with ICC All 7.1 
positioned for parallel approach is provided between two 
beds. 

EI04.3 Communication features. Communication features 
complying with ICC All 7.1 shall be provided in accordance 
with Sections E104.3.1 through E104.3.4. 

EI04.3.1 Transient lodging. In transient lodging facilities, 
sleeping units with accessible communication features shall 
be provided in accordance with Table E104.3.1. Units 
required to comply with Table E104.3.1 shall be dispersed 
among the various classes of units. 

EI04.3.2 Group 1-3. In Group 1-3 occupancies at least 2 
percent, but no fewer than one of the total number of general 
holding cells and general housing cells equipped with audi- 
ble emergency alarm systems and permanently installed 
telephones within the cell, shall comply with Section 
E104.3.4. 

EI04.3.3 Dwelling units and sleeping units. Where dwell- 
ing units and sleeping units are altered or added, the require- 
ments of Section E104.3 shall apply only to the units being 
altered or added until the number of units with accessible 
communication features complies with the minimum num- 
ber required for new construction. 

EI04.3.4 Notification devices. Visual notification devices 
shall be provided to alert room occupants of incoming tele- 
phone calls and a door knock or bell. Notification devices 
shall not be connected to visual alarm signal appliances. 
Permanently installed telephones shall have volume con- 
trols and an electrical outlet complying with ICC All 7.1 
located within 48 inches (1219 mm) of the telephone to 
facilitate the use of a TTY. 

EI04.4 Partitions. Solid partitions or security glazing that 
separates visitors from detainees in Group 1-3 occupancies 
shall provide a method to facilitate voice communication. Such 
methods are permitted to include, but are not limited to, grilles, 
slats, talk-through baffles, intercoms or telephone handset 



2009 INTERNATIONAL BUILDING CODE® 



617 



APPENDIX E 



devices. The method of communication shall be accessible to 
individuals who use wheelchairs and individuals who have dif- 
ficulty bending or stooping. Hand-operable communication 
devices, if provided, shall comply with Section El 06.3. 



SECTION E105 
OTHER FEATURES AND FACILITIES 

EI05.1 Portable toilets and bathing rooms. Where multiple 
single-user portable toilet or bathing units are clustered at a sin- 
gle location, at least 5 percent, but not less than one toilet unit or 
bathing unit at each cluster, shall comply with ICC A117.1. 
Signs containing the International Symbol of Accessibility and 
complying with ICC A 117.1 shall identify accessible portable 
toilets and bathing units. 

Exception: Portable toilet units provided for use exclu- 
sively by construction personnel on a construction site. 

EI05.2 Laundry equipment. Where provided in spaces 
required to be accessible, washing machines and clothes dryers 
shall comply with this section. 

EI05.2.1 Washing machines. Where three or fewer wash- 
ing machines are provided, at least one shall comply with 
ICC All 7.1. Where more than three washing machines are 
provided, at least two shall comply with ICC All 7.1. 

EI05.2.2 Clothes dryers. Where three or fewer clothes 
dryers are provided, at least one shall comply with ICC 
All 7.1. Where more than three clothes dryers are provided, 
at least two shall comply with ICC A117.1. 

EI05.3 Depositories, vending machines, change machines 
and similar equipment. Where provided, at least one of each 
type of depository, vending machine, change machine and sim- 
ilar equipment shall comply with ICC A117.1. 

Exception: Drive-up-only depositories are not required to 
comply with this section. 



EI05.4 Mailboxes. Where mailboxes are provided in an inte- 
rior location, at least 5 percent, but not less than one, of each 
type shall comply with ICC A117.1. In residential and institu- 
tional facilities, where mailboxes are provided for each dwell- 
ing unit or sleeping unit, mailboxes complying with ICC 
All 7.1 shall be provided for each unit required to be an Acces- 
sible unit. 

EI05.5 Automatic teller machines and fare machines. 
Where automatic teller machines or self-service fare vending, 
collection or adjustment machines are provided, at least one 
machine of each type at each location where such machines are 
provided shall be accessible. Where bins are provided for enve- 
lopes, wastepaper or other purposes, at least one of each type 
shall be accessible. 

EI05.6 Two-way communication systems. Where two-way 
communication systems are provided to gain admittance to a 
building or facility or to restricted areas within a building or 
facility, the system shall comply with ICC A117.1. 



SECTION E106 
TELEPHONES 

EI06.1 General. Where coin-operated public pay telephones, 
coinless public pay telephones, public closed-circuit tele- 
phones, courtesy phones or other types of public telephones are 
provided, accessible public telephones shall be provided in 
accordance with Sections El 06.2 through El 06 .5 for each type 
of public telephone provided. For purposes of this section, a 
bank of telephones shall be considered two or more adjacent 
telephones. 

EI06.2 Wheelchair- accessible telephones. Where public 
telephones are provided, wheelchair-accessible telephones 
complying with ICC All 7.1 shall be provided in accordance 
with Table E106. 2. 

Exception: Drive-up-only public telephones are not 
required to be accessible. 



TABLE E104.3.1 
DWELLING OR SLEEPING UNITS WITH ACCESSIBLE COMMUNICATION FEATURES 



TOTAL NUMBER OF DWELLING OR 
SLEEPING UNITS PROVIDED 


MINIMUM REQUIRED NUMBER OF DWELLING OR SLEEPING 
UNITS WITH ACCESSIBLE COMMUNICATION FEATURES 


1 


1 


2 to 25 


2 


26 to 50 


4 


51 to 75 


7 


76 to 100 


9 


101 to 150 


12 


151 to 200 


14 


201 to 300 


17 


301 to 400 


20 


401 to 500 


22 


501 to 1,000 


5% of total 


1,001 and over 


50 plus 3 for each 100 over 1,000 



618 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX E 



TABLE E106.2 
WHEELCHAIR-ACCESSIBLE TELEPHONES 



NUMBER OF TELEPHONES PROVIDED 
ON A FLOOR, LEVEL OR EXTERIOR SITE 


MINIMUM REQUIRED NUMBER OF 
WHEELCHAIR-ACCESSIBLE TELEPHONES 


1 or more single unit 


1 per floor, level and exterior site 


1 bank 


1 per floor, level and exterior site 


2 or more banks 


1 per bank 



EI06.3 Volume controls. All public telephones provided shall 
have volume control complying with ICC A117.1. 

EI06.4 TTYs. TTYs complying with ICC A117. 1 shall be pro- 
vided in accordance with Sections E106.4.1 through E106.4.9. 

EI06.4.1 Bank requirement. Where four or more public 
pay telephones are provided at a bank of telephones, at least 
one public TTY shall be provided at that bank. 

Exception: TTYs are not required at banks of telephones 
located within 200 feet (60 960 mm) of, and on the same 
floor as, a bank containing a public TTY. 

EI06.4.2 Floor requirement. Where four or more public 
pay telephones are provided on a floor of a privately owned 
building, at least one public TTY shall be provided on that 
floor. Where at least one public pay telephone is provided on 
a floor of a publicly owned building, at least one public TTY 
shall be provided on that floor. 

EI06.4.3 Building requirement. Where four or more pub- 
lic pay telephones are provided in a privately owned build- 
ing, at least one public TTY shall be provided in the 
building. Where at least one public pay telephone is pro- 
vided in a publicly owned building, at least one public TTY 
shall be provided in the building. 

EI06.4.4 Site requirement. Where four or more public pay 
telephones are provided on a site, at least one public TTY 
shall be provided on the site. 

EI06.4.5 Rest stops, emergency road stops, and service 
plazas. Where a public pay telephone is provided at a public 
rest stop, emergency road stop or service plaza, at least one 
public TTY shall be provided. 

EI06.4.6 Hospitals. Where a public pay telephone is pro- 
vided in or adjacent to a hospital emergency room, hospital 
recovery room or hospital waiting room, at least one public 
TTY shall be provided at each such location. 

EI06.4.7 Transportation facilities. Transportation facili- 
ties shall be provided with TTYs in accordance with Sec- 
tions E109.2.5 and El 10.2 in addition to the TTYs required 
by Sections E106.4.1 through E106.4.4. 

EI06.4.8 Detention and correctional facilities. In deten- 
tion and correctional facilities, where a public pay telephone 
is provided in a secured area used only by detainees or 
inmates and security personnel, then at least one TTY shall 
be provided in at least one secured area. 

EI06.4.9 Signs. Public TTYs shall be identified by the 
International Symbol of TTY complying with ICC All 7. 1 . 
Directional signs indicating the location of the nearest pub- 



lic TTY shall be provided at banks of public pay telephones 
not containing a public TTY. Additionally, where signs pro- 
vide direction to public pay telephones, they shall also pro- 
vide direction to public TTYs. Such signs shall comply with 
ICC All 7.1 and shall include the International Symbol of 
TTY. 

EI06.5 Shelves for portable TTYs. Where a bank of tele- 
phones in the interior of a building consists of three or more 
public pay telephones, at least one public pay telephone at the 
bank shall be provided with a shelf and an electrical outlet in 
accordance with ICC All 7.1. 

Exceptions: 

1. In secured areas of detention and correctional facili- 
ties, if shelves and outlets are prohibited for purposes 
of security or safety shelves and outlets for TTYs are 
not required to be provided. 

2. The shelf and electrical outlet shall not be required at 
a bank of telephones with a TTY. 



SECTION E107 
SIGNAGE 

EI07. 1 Signs. Required accessible portable toilets and bathing 
facilities shall be identified by the International Symbol of 
Accessibility. 

EI07.2 Designations. Interior and exterior signs identifying 
permanent rooms and spaces shall be tactile. Where 
pictograms are provided as designations of interior rooms and 
spaces, the pictograms shall have tactile text descriptors. Signs 
required to provide tactile characters and pictograms shall 
comply with ICC All 7.1. 

Exceptions: 

1. Exterior signs that are not located at the door to the 
space they serve are not required to comply. 

2. Building directories, menus, seat and row designa- 
tions in assembly areas, occupant names, building 
addresses and company names and logos are not 
required to comply. 

3. Signs in parking facilities are not required to comply. 

4. Temporary (seven days or less) signs are not required 
to comply. 

5. In detention and correctional facilities, signs not 
located in public areas are not required to comply. 

EI07.3 Directional and informational signs. Signs that pro- 
vide direction to, or information about, permanent interior 



2009 INTERNATIONAL BUILDING CODE® 



619 



APPENDIX E 



spaces of the site and facilities shall contain visual characters 
complying with ICC AI17.1. 

Exception: Building directories, personnel names, com- 
pany or occupant names and logos, menus and temporary 
(seven days or less) signs are not required to comply with 
ICCAI17.1. 

EI07.4 Other signs. Signage indicating special accessibility 
provisions shall be provided as follows: 

1. At bus stops and terminals, signage must be provided in 
accordance with Section E 108.4. 

2. At fixed facilities and stations, signage must be provided 
in accordance with Sections EI09.2.2 through 
EI09.2.2.3. 

3. At airports, terminal information systems must be pro- 
vided in accordance with Section Ell 0.3. 



SECTION E108 
BUS STOPS 

EI08. 1 General. Bus stops shall comply with Sections EI08.2 
through EI08.5. 

EI08.2 Bus boarding and alighting areas. Bus boarding and 
alighting areas shall comply with Sections EI08.2.1 through 
EI08.2.4. 

EI08.2.1 Surface. Bus boarding and alighting areas shall 
have a firm, stable surface. 

EI08.2.2 Dimensions. Bus boarding and alighting areas 
shall have a clear length of 96 inches (2440 mm) minimum, 
measured perpendicular to the curb or vehicle roadway 
edge, and a clear width of 60 inches (1525 mm) minimum, 
measured parallel to the vehicle roadway. 

EI08.2.3 Connection. Bus boarding and alighting areas 
shall be connected to streets, sidewalks or pedestrian paths 
by an accessible route complying with Section 1104. 

EI08.2.4 Slope. Parallel to the roadway, the slope of the bus 
boarding and alighting area shall be the same as the road- 
way, to the maximum extent practicable. For water drain- 
age, a maximum slope of 1 :48 perpendicular to the roadway 
is allowed. 

EI08.3 Bus shelters. Where provided, new or replaced bus 
shelters shall provide a minimum clear floor or ground space 
complying with ICC All 7.1, Section 305, entirely within the 
shelter. Such shelters shall be connected by an accessible route 
to the boarding area required by Section EI08.2. 

EI08.4 Signs. New bus route identification signs shall have 
finish and contrast complying with ICC AI17.1. Additionally, 
to the maximum extent practicable, new bus route identifica- 
tion signs shall provide visual characters complying with ICC 
AI17.1. 

Exception: Bus schedules, timetables and maps that are 
posted at the bus stop or bus bay are not required to meet this 
requirement. 

EI08.5 Bus stop siting. Bus stop sites shall be chosen such 
that, to the maximum extent practicable, the areas where lifts or 



ramps are to be deployed comply with Sections EI08.2 and 
EI08.3. 



SECTION E109 
TRANSPORTATION FACILITIES AND STATIONS 

EI09.1 General. Fixed transportation facilities and stations 
shall comply with the applicable provisions of Section E 109.2. 

EI09.2 New construction. New stations in rapid rail, light rail, 
commuter rail, intercity rail, high speed rail and other fixed 
guideway systems shall comply with Sections E 109.2.1 
through EI09.2.8. 

EI09.2. 1 Station entrances. Where different entrances to a 
station serve different transportation fixed routes or groups 
of fixed routes, at least one entrance serving each group or 
route shall comply with Section 1104 and ICC A 11 7.1. 

EI09.2.2 Signs. Signage in fixed transportation facilities 
and stations shall comply with Sections EI09.2.2.1 through 
EI09.2.2.3. 

EI09.2.2.1 Tactile signs. Where signs are provided at 
entrances to stations identifying the station or the 
entrance, or both, at least one sign at each entrance shall 
be tactile. A minimum of one tactile sign identifying the 
specific station shall be provided on each platform or 
boarding area. Such signs shall be placed in uniform 
locations at entrances and on platforms or boarding areas 
within the transit system to the maximum extent practi- 
cable. Tactile signs shall comply with ICC AI17.1. 

Exceptions: 

1. Where the station has no defined entrance but 
signs are provided, the tactile signs shall be 
placed in a central location. 

2. Signs are not required to be tactile where audi- 
ble signs are remotely transmitted to hand-held 
receivers, or are user or proximity actuated. 

EI09.2.2.2 Identification signs. Stations covered by 
this section shall have identification signs containing 
visual characters complying with ICC AI17.1. Signs 
shall be clearly visible and within the sightlines of a 
standing or sitting passenger from within the train on 
both sides when not obstructed by another train. 

EI09.2.2.3 Informational signs. Lists of stations, 
routes and destinations served by the station which are 
located on boarding areas, platforms or mezzanines shall 
provide visual characters complying with ICC A117.1 
Signs covered by this provision shall, to the maximum 
extent practicable, be placed in uniform locations within 
the transit system. 

EI09.2.3 Fare machines. Self-service fare vending, collec- 
tion and adjustment machines shall comply with ICC 
AI17.1, Section 707. Where self-service fare vending, col- 
lection or adjustment machines are provided for the use of 
the general public, at least one accessible machine of each 
type provided shall be provided at each accessible point of 
entry and exit. 



620 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX E 



EI09.2.4 Rail-to-platform height. Station platforms shall 
be positioned to coordinate with vehicles in accordance 
with the applicable provisions of 36 CFR, Part 1192. 
Low-level platforms shall be 8 inches (250 mm) minimum 
above top of rail. 

Exception: Where vehicles are boarded from sidewalks 
or street level, low-level platforms shall be permitted to 
be less than 8 inches (250 mm). 

EI09.2.5 TTYs. Where a public pay telephone is provided 
in a transit facility (as defined by the Department of Trans- 
portation) at least one public TTY complying with ICC 
A117.1, Section 704.4, shall be provided in the station. In 
addition, where one or more public pay telephones serve a 
particular entrance to a transportation facility, at least one 
TTY telephone complying with ICC A 1 17.1, Section 704.4, 
shall be provided to serve that entrance. 

EI09.2.6 Track crossings. Where a circulation path serv- 
ing boarding platforms crosses tracks, an accessible route 
complying with ICC A 117.1 shall be provided. 

Exception: Openings for wheel flanges shall be permit- 
ted to be 2V 2 inches (64 mm) maximum. 

EI09.2.7 Public address systems. Where public address 
systems convey audible information to the public, the same 
or equivalent information shall be provided in a visual for- 
mat. 

EI09.2.8 Clocks. Where clocks are provided for use by the 
general public, the clock face shall be uncluttered so that its 
elements are clearly visible. Hands, numerals and digits 
shall contrast with the background either light-on-dark or 
dark-on-light. Where clocks are mounted overhead, numer- 
als and digits shall comply with ICC Al 17. 1, Section 703.2. 



DO] 36 

CFR Part 1192 



ICC/ANSI 
AI17.1-03 



SECTION E111 
REFERENCED STANDARDS 

Americans with Disabilities Act 
(ADA) Accessibility Guidelines 
for Transportation Vehicles 
(ADAAG). Washington, D.C.: 
Department of Justice, 1991 



EI09.2.4 



Accessible and Usable 
Buildings and Facilities 



EI01.2, EI04.2, 

EI04.2.1, EI04.3, 

EI04.3.4, EI0S.1, 

EIOS.2.1, EIOS.2.2, 

EI0S.3, EI0S.4, 

EI0S.6, EI06.2, 

EI06.3, EI06.4, 

EI06.4.9, EI06.S, 

EI07.2, EI07.3, 

EI08.3, EI08.4, 

EI09.2.1, EI09.2.2.1, 

EI09.2.2.2, EI09.2.2.3, 

EI09.2.3 



SECTION E110 
AIRPORTS 

EIIO.I New construction. New construction of airports shall 
comply with Sections El 10.2 through El 10.4. 

EIIO.2 TTYs. Where public pay telephones are provided, at 
least one TTY shall be provided in compliance with ICC 
A 117.1, Section 704.4. Additionally, if four or more public pay 
telephones are located in a main terminal outside the security 
areas, a concourse within the security areas or a baggage claim 
area in a terminal, at least one public TTY complying with ICC 
A117.1, Section 704.4, shall also be provided in each such 
location. 

EIIO.3 Terminal information systems. Where terminal 
information systems convey audible information to the public, 
the same or equivalent information shall be provided in a visual 
format. 

EIIO.4 Clocks. Where clocks are provided for use by the gen- 
eral public, the clock face shall be uncluttered so that its ele- 
ments are clearly visible. Hands, numerals and digits shall 
contrast with their background either light-on-dark or 
dark-on-light. Where clocks are mounted overhead, numerals 
and digits shall comply with ICC A117.1, Section 703.2. 



2009 INTERNATIONAL BUILDING CODE® 



621 



622 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX F 

RODENTPROOFING 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION F101 
GENERAL 

F 101.1 General. Buildings or structures and the walls enclos- 
ing habitable or occupiable rooms and spaces in which persons 
live, sleep or work, or in which feed, food or foodstuffs are 
stored, prepared, processed, served or sold, shall be con- 
structed in accordance with the provisions of this section. 

F 101.2 Foundation wall ventilation openings. Foundation 
wall ventilator openings shall be covered for their height and 
width with perforated sheet metal plates no less than 0.070 inch 
(1.8 mm) thick, expanded sheet metal plates not less than 0.047 
inch (1.2 mm) thick, cast iron grills or grating, extruded alumi- 
num load-bearing vents or with hardware cloth of 0.035 inch 
(0.89 mm) wire or heavier. The openings therein shall not 
exceed i/ 4 inch (6.4 mm). 

F101.3 Foundation and exterior wall sealing. Annular 
spaces around pipes, electric cables, conduits, or other open- 
ings in the walls shall be protected against the passage of 
rodents by closing such openings with cement mortar, concrete 
masonry or noncorrosive metal. 

F 101.4 Doors. Doors on which metal protection has been 
applied shall be hinged so as to be free swinging. When closed, 
the maximum clearance between any door, doorjambs and sills 
shall not be greater than 3/ 8 inch (9.5 mm). 

F101.5 Windows and other openings. Windows and other 
openings for the purpose of light or ventilation located in exte- 
rior walls within 2 feet (610 mm) above the existing ground 
level immediately below such opening shall be covered for 
their entire height and width, including frame, with hardware 
cloth of at least 0.035 inch (0.89 mm) wire or heavier. 

F 101. 5.1 Rodent- accessible openings. Windows and other 
openings for the purpose of light and ventilation in the exte- 
rior walls not covered in this chapter, accessible to rodents 
by way of exposed pipes, wires, conduits and other appurte- 
nances, shall be covered with wire cloth of at least 0.035 
inch (0.89 mm) wire. In lieu of wire cloth covering, said 
pipes, wires, conduits and other appurtenances shall be 
blocked from rodent usage by installing solid sheet metal 
guards 0.024 inch (0.61 mm) thick or heavier. Guards shall 
be fitted around pipes, wires, conduits or other appurte- 
nances. In addition, they shall be fastened securely to and 
shall extend perpendicularly from the exterior wall for a 
minimum distance of 12 inches (305 mm) beyond and on 
either side of pipes, wires, conduits or appurtenances. 

F101.6 Pier and wood construction. 

F 101. 6.1 Sill less than 12 inches above ground. Buildings 
not provided with a continuous foundation shall be provided 
with protection against rodents at grade by providing either 



an apron in accordance with Section FIO 1.6.1.1 or a floor 
slab in accordance with Section F101.6.1.2. 

F 101.6.1.1 Apron. Where an apron is provided, the 
apron shall not be less than 8 inches (203 mm) above, nor 
less than 24 inches (610 mm) below, grade. The apron 
shall not terminate below the lower edge of the siding 
material. The apron shall be constructed of an approved 
nondecayable, water-resistant rodentproofing material 
of required strength and shall be installed around the 
entire perimeter of the building. Where constructed of 
masonry or concrete materials, the apron shall not be less 
than 4 inches (102 mm) in thickness. 

F101.6.1.2 Grade floors. Where continuous concrete 
grade floor slabs are provided, open spaces shall not be 
left between the slab and walls, and openings in the slab 
shall be protected. 

F101.6.2 Sill at or above 12 inches above ground. Build- 
ings not provided with a continuous foundation and which 
have sills 12 or more inches (305 mm) above the ground 
level shall be provide with protection against rodents at 
grade in accordance with any of the following: 

1. Section F101.6.1.1 or F101.6.1.2; 

2. By installing solid sheet metal collars at least 0.024 
inch (0.6 mm) thick at the top of each pier or pile and 
around each pipe, cable, conduit, wire or other item 
which provides a continuous pathway from the 
ground to the floor; or 

3. By encasing the pipes, cables, conduits or wires in an 
enclosure constructed in accordance with Section 
F101.6.1.1. 



2009 INTERNATIONAL BUILDING CODE® 



623 



624 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX G 

FLOOD-RESISTANT CONSTRUCTION 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION G101 
ADMINISTRATION 

GI01.1 Purpose. The purpose of this appendix is to promote 
the public health, safety and general welfare and to minimize 
public and private losses due to flood conditions in specific 
flood hazard areas through the establishment of comprehen- 
sive regulations for management of flood hazard areas 
designed to: 

1. Prevent unnecessary disruption of commerce, access and 
public service during times of flooding, 

2. Manage the alteration of natural flood plains, stream 
channels and shorelines; 

3. Manage filling, grading, dredging and other develop- 
ment which may increase flood damage or erosion poten- 
tial; 

4. Prevent or regulate the construction of flood barriers 
which will divert floodwaters or which can increase 
flood hazards; and 

5. Contribute to improved construction techniques in the 
flood plain. 

G 101.2 Objectives. The objectives of this appendix are to pro- 
tect human life, minimize the expenditure of public money for 
floo d control projects, minimize the need for rescue and relief 
efforts associated with flooding, minimize prolonged business 
interruption, minimize damage to public facilities and utilities, 
help maintain a stable tax base by providing for the sound use 
and development of flood-prone areas, contribute to improved 
construction techniques in the flood plain and ensure that 
potential owners and occupants are notified that property is 
within flood hazard areas. 

G 101.3 Scope. The provisions of this appendix shall apply to 
all proposed development in a flood hazard area established in 
Section 1612 of this code, including certain building work 
exempt from permit under Section 105.2. 

G 101.4 Violations. Any violation of a provision of this appen- 
dix, or failure to comply with a permit or variance issued pursu- 
ant to this appendix or any requirement of this appendix, shall 
be handled in accordance with Section 114. 



SECTION G102 
APPLICABILITY 

G 102.1 General. This appendix, in conjunction with the Inter- 
national Building Code, provides minimum requirements for 
development located in flood hazard areas, including the subdi- 
vision of land; installation of utilities; placement and replace- 
ment of manufactured homes; new construction and repair, 
reconstruction, rehabilitation or additions to new construction; 



substantial improvement of existing buildings and structures, 
including restoration after damage, temporary structures, and 
temporary or permanent storage, utility and miscellaneous 
Group U buildings and structures, and certain building work 
exempt from permit under Section 105.2. 

G 102.2 Establishment of flood hazard areas. Flood hazard 
areas are established in Section 1612.3 of the International 
Building Code, adopted by the applicable governing authority 
on [INSERT DATE] . 



SECTION G103 
POWERS AND DUTIES 

G 103.1 Permit applications. The bUilding official shall 
review all permit applications to determine whether proposed 
development sites will be reasonably safe from flooding. If a 
proposed development site is in a flood hazard area, all site 
development activities (including grading, filling, utility 
installation and drainage modification), all new construction 
and substantial improvements (including the placement of pre- 
fabricated buildings and manufactured homes) and certain 
building work exempt from permitunder Section 105.2 shall be 
designed and constructed with methods, practices and materi- 
als that minimize flood damage and that are in accordance with 
this code and ASCE 24. 

G 103.2 Other permits. It shall be the responsibility of the 
building officialto assure that approval of a proposed develop- 
ment shall not be given until proof that necessary permits have 
been granted by federal or state agencies having jurisdiction 
over such development. 

G 103.3 Determination of design flood elevations. If design 
flood elevations are not specified, the bUilding officialis autho- 
rized to require the applicant to: 

1. Obtain, review and reasonably utilize data available 
from a federal, state or other source, or 

2. Determine the design flood elevation in accordance with 
accepted hydrologic and hydraulic engineering tech- 
niques. Such analyses shall be performed and sealed by a 
registered design professional. Studies, analyses and 
computations shall be submitted in sufficient detail to 
allow review and approval by the bUilding official. The 
accuracy of data submitted for such determination shall 
be the responsibility of the applicant. 

G 103.4 Activities in riverine flood hazard areas. In riverine 
flood hazard areas where design flood elevations are specified 
but floodways have not been designated, the building official 
shall not permit any new construction, substantial improve- 
ment or other development, including fill, unless the applicant 
demonstrates that the cumulative effect of the proposed devel- 



2009 INTERNATIONAL BUILDING CODE® 



625 



APPENDIX G 



opment, when combined with all other existing and anticipated 
flood hazard area encroachment, will not increase the design 
flood elevation more than 1 foot (305 mm) at any point within 
the community. 

G 103.5 Floodway encroachment. Prior to issuing apermitfor 
any floodway encroachment, including fill, new construction, 
substantial improvements and other development or land-dis- 
turbing activity, the building official shall require submission 
of a certification, along with supporting technical data, that 
demonstrates that such development will not cause any 
increase of the level of the base flood. 

G 103.5.1 Floodway revisions. IK floodway encroachment 
that increases the level of the base floo d is authorized if the 
applicant has applied for a conditional Flood Insurance Rate 
Map (FIRM) revision and has received the approval of the 
Federal Emergency Management Agency (FEMA) . 

G 103.6 Watercourse alteration. Prior to issuing a permit for 
any alteration or relocation of any watercourse, the building 
official shall require the applicant to provide notification of the 
proposal to the appropriate authorities of all affected adjacent 
governmentjurisdictions, as well as appropriate state agencies. 
A copy of the notification shall be maintained in the permit 
records and submitted to FEMA. 

G103.6.1 Engineering analysis. The building official shall 
require submission of an engineering analysis which dem- 
onstrates that the flood-carrying capacity of the altered or 
relocated portion of the watercourse will not be decreased. 
Such watercourses shall be maintained in a manner which 
preserves the channel's flood-carrying capacity. 

G 103.7 Alterations in coastal areas. Prior to issuing a permit 
for any alteration of sand dunes and mangrove stands in flood 
hazard areas subject to high velocity wave action, the building 
official shall require submission of an engineering analysis 
which demonstrates that the proposed alteration will not 
increase the potential for flood damage. 

G103.8 Records. The building official shall maintain a perma- 
nent record of all permits issued in flood hazard areas, includ- 
ing copies of inspection reports and certifications required in 
Section 1612. 



SECTION G104 
PERMITS 

G 104.1 Required. Any person, owner or authorized agent who 
intends to conduct any development in a flood hazard area shall 
first make application to the bUilding official and shall obtain 
the required permit. 

G 104.2 Application for permit. The applicant shall file an 
application in writing on a form furnished by the bUilding offi- 
cial. Such application shall: 

1. Identify and describe the development to be covered by 
the permit. 

2. Describe the land on which the proposed development is 
to be conducted by legal description, street address or 



similar description that will readily identify and defi- 
nitely locate the site. 

3. Include a site plan showing the delineation of flood haz- 
ard areas, floodway boundaries, flood zones, design 
flood elevations, ground elevations, proposed fill and 
excavation and drainage patterns and facilities. 

4. Indicate the use and occupancy for which the proposed 
development is intended. 

5. Be accompanied by construction documents, grading 
and filling plans and other information deemed appropri- 
ate by the building official. 

6. State the valuation of the proposed work. 

7. Be signed by the applicant or the applicant's authorized 
agent. 

G 104.3 Validity of permit. The issuance of apermitunder this 
appendix shall not be construed to be a permit for, or approval 
of, any violation of this appendix or any other ordinance of the 
jurisdiction. The issuance of apermitbased on submitted docu- 
ments and information shall not prevent the bUilding official 
from requiring the correction of errors. The bUilding official is 
authorized to prevent occupancy or use of a structure or site 
which is in violation of this appendix or other ordinances of this 
jurisdiction. 

G 104.4 Expiration. A permit shall become invalid if the pro- 
posed development is not commenced within 180 days after its 
issuance, or if the work authorized is suspended or abandoned 
for a period of 180 days after the work commences. Extensions 
shall be requested in writing and justifiable cause demon- 
strated. The bUilding official is authorized to grant, in writing, 
one or more extensions of time, for periods not more than 180 
days each. 

G 104.5 Suspension or revocation. The building official is 
authorized to suspend or revoke a permit issued under this 
appendix wherever the permit is issued in error or on the basis 
of incorrect, inaccurate or incomplete information, or in viola- 
tion of any ordinance or code of this jurisdiction. 



SECTION G105 
VARIANCES 

G 105.1 General. The boar do f appeals established pursuant to 
Section 112 shall hear and decide requests for variances. The 
boar do f appeals shall base its determination on technicaljusti- 
fications, and has the right to attach such conditions to vari- 
ances as it deems necessary to further the purposes and 
objectives of this appendix and Section 1612. 

G 105.2 Records. The building official shall maintain a perma- 
nent record of all variance actions, including justification for 
their issuance. 

G 105.3 Historic structures. A variance is authorized to be 
issued for the repair or rehabilitation of a historic structure 
upon a determination that the proposed repair or rehabilitation 
will not preclude the structure's continued designation as a his- 



626 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX G 



toric structure, and the variance is the minimum necessary to 
preserve the historic character and design of the structure. 

Exception: Within flood hazard areas, historic structures 
that are not: 

1. Listed or preliminarily determined to be eligible for 
listing in the National Register of Historic Places; or 

2. Determined by the Secretary of the U.S. Department 
of Interior as contributing to the historical signifi- 
cance of a registered historic district or a district pre- 
liminarily determined to qualify as an historic district; 
or 

3. Designated as historic under a state or local historic 
preservation program that is approved by the Depart- 
ment of Interior. 

G 105.4 Functionally dependent facilities. A variance is 
authorized to be issued for the construction or substantial 
improvement of a functionally dependent facility provided the 
criteria in Section 1612.1 are met and the variance is the mini- 
mum necessary to allow the construction or substantial 
improvement, and that all due consideration has been given to 
methods and materials that minimize flood damages during the 
design flood and create no additional threats to public safety. 

G105.5 Restrictions. The board of appeals shall not issue a 
variance for any proposed development in a lloodway if any 
increase in flood levels would result during the base flood dis- 
charge. 

G 105.6 Considerations. In reviewing applications for vari- 
ances, the board of appeals shall consider all technical evalua- 
tions, all relevant factors, all other portions of this appendix and 
the following: 

1. The danger that materials and debris may be swept onto 
other lands resulting in further injury or damage; 

2. The danger to life and property due to flooding or ero- 
sion damage; 

3. The susceptibility of the proposed development, 
including contents, to flood damage and the effect of 
such damage on current and future owners; 

4. The importance of the services provided by the pro- 
posed development to the community; 

5. The availability of alternate locations for the proposed 
development that are not subj ect to flooding or erosion; 

6. The compatibility of the proposed development with 
existing and anticipated development; 

7. The relationship of the proposed development to the 
comprehensive plan and flood plain management pro- 
gram for that area; 

8. The safety of access to the property in times of flood for 
ordinary and emergency vehicles; 

9. The expected heights, velocity, duration, rate of rise 
and debris and sediment transport of the floodwaters 
and the effects of wave action, if applicable, expected at 
the site; and 

10. The costs of providing governmental services during 
and after flood conditions including maintenance and 



repair of public utilities and facilities such as sewer, 
gas, electrical and water systems, streets and bridges. 

G105.7 Conditions for issuance. Variances shall only be 
issued by the board of appeals upon: 

1. A technical showing of good and sufficient cause that the 
unique characteristics of the size, configuration or 
topography of the site renders the elevation standards 
inappropriate; 

2. A determination that failure to grant the variance would 
result in exceptional hardship by rendering the lot 
undevelopable; 

3. A determination that the granting of a variance will not 
result in increased flood heights, additional threats to 
public safety, extraordinary public expense, nor create 
nuisances, cause fraud on or victimization of the public 
or conflict with existing local laws or ordinances; 

4. A determination that the variance is the minimum neces- 
sary, considering the flood hazard, to afford relief; and 

5. Notification to the applicant in writing over the signature 
of the building official that the issuance of a variance to 
construct a structure below the base flood level will 
result in increased premium rates for flood insurance up 
to amounts as high as $25 for $100 of insurance cover- 
age, and that such construction below the base flood 
level increases risks to life and property. 



SECTION G201 
DEFINITIONS 

G201.1 General. The following words and terms shall, for the 
purposes of this appendix, have the meanings shown herein. 
Refer to Chapter 2 for general definitions. 

G201.2 Definitions. 

DEVELOPMENT. Any manmade change to improved or 
unimproved real estate, including but not limited to, buildings 
or other structures, temporary structures, temporary or perma- 
nent storage of materials, mining, dredging, filling, grading, 
paving, excavations, operations and other land-disturbing 
activities. 

FUNCTIONALLY DEPENDENT FACILITY. A facility 
which cannot be used for its intended purpose unless it is 
located or carried out in close proximity to water, such as a 
docking or port facility necessary for the loading or unloading 
of cargo or passengers, shipbuilding or ship repair. The term 
does not include long-term storage, manufacture, sales or ser- 
vice facilities. 

MANUFACTURED HOME. A structure that is transportable 
in one or more sections, built on a permanent chassis, designed 
for use with or without a permanent foundation when attached 
to the required utilities, and constructed to the Federal Mobile 
Home Construction and Safety Standards and rules and regula- 
tions promulgated by the U.S. Department of Housing and 
Urban Development. The term also includes mobile homes, 
park trailers, travel trailers and similar transportable structures 
that are placed on a site for 180 consecutive days or longer. 



2009 INTERNATIONAL BUILDING CODE® 



627 



APPENDIX G 



MANUFACTURED HOME PARK OR SUBDIVISION. A 

parcel (or contiguous parcels) of land divided into two or more 
manufactured home lots for rent or sale. 

RECREATIONAL VEHICLE. A vehicle that is built on a 
single chassis, 400 square feet (37.16 m 2 ) or less when mea- 
sured at the largest horizontal projection, designed to be 
self-propelled or permanently towable by a light-duty truck, 
and designed primarily not for use as a permanent dwelling but 
as temporary living quarters for recreational, camping, travel 
or seasonal use. A recreational vehicle is ready for highway use 
if it is on its wheels or jacking system, is attached to the site 
only by quick disconnect-type utilities and security devices and 
has no permanently attached additions. 

VARIANCE. A grant of relief from the requirements of this 
section which permits construction in a manner otherwise pro- 
hibited by this section where specific enforcement would result 
in unnecessary hardship. 

VIOLATION. A development that is not fully compliant with 
this appendix or Section 1612, as applicable. 



SECTION G301 
SUBDIVISIONS 

G301.1 General. Any subdivision proposal, including propos- 
als for manufactured home parks and subdivisions, or other 
proposed new development in a flood hazard area shall be 
reviewed to assure that: 

1. All such proposals are consistent with the need to mini- 
mize flood damage; 

2. All public utilities and facilities, such as sewer, gas, elec- 
tric and water systems are located and constructed to 
minimize or eliminate flood damage; and 

3. Adequate drainage is provided to reduce exposure to 
flood hazards. 

G301.2 Subdivision requirements. The following require- 
ments shall apply in the case of any proposed subdivision, 
including proposals for manufactured home parks and subdivi- 
sions, any portion of which lies within a flood hazard area: 

1. The flood hazard area, including floodways and areas 
subject to high velocity wave action, as appropriate, shall 
be delineated on tentative and final subdivision plats; 

2. Design flood elevations shall be shown on tentative and 
final subdivision plats; 

3. Residential building lots shall be provided with adequate 
buildable area outside the floodway; and 

4. The design criteria for utilities and facilities set forth in 
this appendix and appropriate International Codes shall 
be met. 



tice that the proposed encroachment will not result in any 
increase in the level of the base flood. 

G401.2 Flood hazard areas subject to high-velocity wave 
action. In flood hazard areas subject to high- velocity wave 
action: 

1. New buildings and buildings that are substantially 
improved shall only be authorized landward of the reach 
of mean high tide. 

2. The use of fill for structural support of buildings is pro- 
hibited. 

G401.3 Sewer facilities. All new or replaced sanitary sewer 
facilities, private sewage treatment plants (including all pump- 
ing stations and collector systems) and on-site waste disposal 
systems shall be designed in accordance with Chapter 8, ASCE 
24, to minimize or eliminate infiltration of floodwaters into the 
facilities and discharge from the facilities into floodwaters, or 
impairment of the facilities and systems. 

G401.4 Water facilities. All new or replacement water facili- 
ties shall be designed in accordance with the provisions of 
Chapter 8, ASCE 24, to minimize or eliminate infiltration of 
floodwaters into the systems. 

G401.5 Storm drainage. Storm drainage shall be designed to 
convey the flow of surface waters to minimize or eliminate 
damage to persons or property. 

G401.6 Streets and sidewalks. Streets and sidewalks shall be 
designed to minimize potential for increasing or aggravating 
flood levels. 



SECTION G501 
MANUFACTURED HOMES 

G501.1 Elevation. All new and replacement manufactured 
homes to be placed or substantially improved in a. flood hazard 
area shall be elevated such that the lowest floor of the manufac- 
tured home is elevated to or above the design flood elevation. 

G501.2 Foundations. All new and replacement manufactured 
homes, including substantial improvement of existing manu- 
factured homes, shall be placed on a permanent, reinforced 
foundation that is designed in accordance with Section 1612. 

G501.3 Anchoring. All new and replacement manufactured 
homes to be placed or substantially improved in a. flood hazard 
area shall be installed using methods and practices which mini- 
mize flood damage. Manufactured homes shall be securely 
anchored to an adequately anchored foundation system to 
resist flotation, collapse and lateral movement. Methods of 
anchoring are authorized to include, but are not limited to, use 
of over-the-top or frame ties to ground anchors. This require- 
ment is in addition to applicable state and local anchoring 
requirements for resisting wind forces . 



SECTION G401 
SITE IMPROVEMENT 

G401.1 Development in floodways. Development or land dis- 
turbing activity shall not be authorized in the floodwayunless it 
has been demonstrated through hydrologic and hydraulic anal- 
yses performed in accordance with standard engineering prac- 



SECTION G601 
RECREATIONAL VEHICLES 

G601.1 Placement prohibited. The placement of recreational 
vehicles shall not be authorized in flood hazard are as subject to 
high velocity wave action and in floodways. 



628 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX G 



G601.2 Temporary placement. Recreational vehicles in flood 
hazardareas shall be fully licensed and ready for highway use, 
and shall be placed on a site for less than 180 consecutive days. 

G601.3 Permanent placement. Recreational vehicles that are 
not fully licensed and ready for highway use, or that are to be 
placed on a site for more than 180 consecutive days, shall meet 
the requirements of Section G501 for manufactured homes. 



SECTION G701 
TANKS 

G701.1 Underground tanks. Underground tanks in floodhaz- 
ardareas shall be anchored to prevent flotation, collapse or lat- 
eral movement resulting from hydrostatic loads, including the 
effects of buoyancy, during conditions of the design flood. 

G701.2 Above-ground tanks. Above-ground tanks in flood 
hazard areas shall be elevated to or above the design flood ele- 
vation or shall be anchored or otherwise designed and con- 
structed to prevent flotation, collapse or lateral movement 
resulting from hydrodynamic and hydrostatic loads, including 
the effects of buoyancy, during conditions of the design flood. 

G701.3 Tank inlets and vents. In flood hazard areas, tank 
inlets, fill openings, outlets and vents shall be: 

1. At or above the design flood elevation or fitted with cov- 
ers designed to prevent the inflow of floodwater or out- 
flow of the contents of the tanks during conditions of the 
design flood. 

2. Anchored to prevent lateral movement resulting from 
hydrodynamic and hydrostatic loads, including the 
effects of buoyancy, during conditions of the design 
flood. 



SECTION G801 
OTHER BUILDING WORK 

G801.1 Detached accessory structures. Detached accessory 
structures shall be anchored to prevent flotation, collapse or lat- 
eral movement resulting from hydrostatic loads, including the 
effects of bouyancy, during conditions of the design flood. 
Fully enclosed accessory structures shall have flood openings 
to allow for the automatic entry and exit of flood waters. 

G801.2 Fences. Fences in floodways that may block the pas- 
sage of floodwaters, such as stockade fences and wire mesh 
fences, shall meet the requirement of Section G 103.5. 

G801.3 Oil derricks. Oil derricks located in flood hazard 
areas shall be designed in conformance with the flood loads in 
Sections 1603.1.7 and 1612. 

G801.4 Retaining walls, sidewalks and driveways. Retain- 
ing walls, sidewalks and driveways shall meet the requirements 
of Section 1803.4. 

G801.5 Prefabricated swimming pools. Prefabricated swim- 
ming pools in floodways shall meet the requirements of Section 
GI03.5. 



SECTION G901 

TEMPORARY STRUCTURES AND TEMPORARY 

STORAGE 

G901.1 Temporary structures. Temporary structures shall be 
erected for a period of less than 180 days. Temporary structures 
shall be anchored to prevent flotation, collapse or lateral move- 
ment resulting from hydrostatic loads, including the effects of 
buoyancy, during conditions of the design flood. Fully 
enclosed temporary structures shall have flood openings to 
allow for the automatic entry and exit of floodwaters. 

G901.2 Temporary storage. Temporary storage includes stor- 
age of goods and materials for a period of less than 180 days. 
Stored materials shall not include hazardous materials. 

G901.3 Floodway encroachment. Temporary structures and 
temporary storage in floodways shall meet the requirements of 
GI03.5. 



SECTION G1001 
UTILITY AND MISCELLANEOUS GROUP U 

G 1001.1 Utility and miscellaneous Group U. Utility and mis- 
cellaneous Group U includes buildings that are accessory in 
character and miscellaneous structures not classified in any 
specific occupancy in the International Building Code, includ- 
ing, but not limited to, agricultural buildings, aircraft hangars 
(accessory to a one- or two-family residence), barns, carports, 
fences more than 6 feet (1829 mm) high, grain silos (accessory 
to a residential occupancy), greenhouses, livestock shelters, 
private garages, retaining walls, sheds, stables and towers. 

G 1001.2 Flood loads. Utility and miscellaneous Group U 
buildings and structures, including substantial improvement of 
such buildings and structures, shall be anchored to prevent flo- 
tation, collapse or lateral movement resulting from flood loads, 
including the effects of buoyancy, during conditions of the 
design flood. 

G 1001.3 Elevation. Utility and miscellaneous Group U build- 
ings and structures, including substantial improvement of such 
buildings and structures, shall be elevated such that the lowest 
floor, including basement, is elevated to or above the design 
flood elevation in accordance with Section 1612 of the Interna- 
tional Building Code. 

G 1001.4 Enclosures below design flood elevation. Fully 
enclosed areas below the design flood elevation shall be at or 
above grade on all sides and conform to the following: 

1. In flood hazardareas not subject to high- velocity wave 
action, enclosed areas shall have flood openings to allow 
for the automatic inflow and outflow of floodwaters. 

2. In flood hazard areas subject to high-velocity wave 
action, enclosed areas shall have walls below the design 
flood elevation that are designed to break away or col- 
lapse from a water load less than that which would occur 
during the design flood, without causing collapse, dis- 
placement or other structural damage to the building or 
structure. 

G 1001.5 Flood-damage-resistant materials. Flood-dam- 
age-resistant materials shall be used below the design floodele- 
vation. 



2009 INTERNATIONAL BUILDING CODE® 



629 



APPENDIX G 



G 1001.6 Protection of mechanical, plumbing and electrical 
systems. Mechanical, plumbing and electrical systems, includ- 
ing plumbing fixtures, shall be elevated to or above the design 
flood elevation. 

Exception: Electrical systems, equipment and components, 
and heating, ventilating, air conditioning, and plumbing 
appliances, plumbing fixtures, duct systems and other ser- 
vice equipment shall be permitted to be located below the 
design flood elevation provided that they are designed and 
installed to prevent water from entering or accumulating 
within the components and to resist hydrostatic and hydro- 
dynamic loads and stresses, including the effects of buoy- 
ancy, during the occurrence of flooding to the design flood 
elevation in compliance with the flood-resistant construc- 
tion requirements of this code. Electrical wiring systems 
shall be permitted to be located below the design flood ele- 
vation provided they conform to the provisions ofNFPA 70. 



SECTION G1101 
REFERENCED STANDARDS 

ASCE 24-05 Flood Resistance Design 
and Construction 



G 103.1, 
G401.3, 
G401.4 



HUD 24 CFR Manufactured Home 
Part 3280 Construction and Safety 

(1994) Standards 



G201 



IBC-06 International Building Code GI02.2 

I NFPA 70-08 National Electrical Code GI001.6 



630 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX H 

SIGNS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION H101 
GENERAL 

HI01.1 General. A sign shall not be erected in a manner that 
would confuse or obstruct the view of or interfere with exit 
signs required by Chapter 10 or with official traffic signs, sig- 
nals or devices. Signs and sign support structures, together with 
their supports, braces, guys and anchors, shall be kept in repair 
and in proper state of preservation. The display surfaces of 
signs shall be kept neatly painted or posted at all times. 

HI01.2 Signs exempt from permits. The following signs are 
exempt from the requirements to obtain a permit before erec- 
tion: 

1. Painted nonilluminated signs. 

2. Temporary signs announcing the sale or rent of property . 

3. Signs erected by transportation authorities. 

4. Projecting signs not exceeding 2.5 square feet (0.23 m 2 ) . 

5. The changing of moveable parts of an approved sign that 
is designed for such changes, or the repainting or reposi- 
tioning of display matter shall not be deemed an alter- 
ation. 



SECTION H102 
DEFINITIONS 

HI02.1 General. Unless otherwise expressly stated, the fol- 
lowing words and terms shall, for the purposes of this appen- 
dix, have the meanings shown herein. Refer to Chapter 2 of the 
International Building Code for general definitions. 

COMBINATION SIGN. A sign incorporating any combina- 
tion of the features of pole, projecting and roof signs. 

DISPLAY SIGN. The area made available by the sign struc- 
ture for the purpose of displaying the advertising message. 

ELECTRIC SIGN. A sign containing electrical wiring, but 
not including signs illuminated by an exterior light source. 

GROUND SIGN. A billboard or similar type of sign which is 
supported by one or more uprights, poles or braces in or upon 
the ground other than a combination sign or pole sign, as 
defined by this code. 

POLE SIGN. A sign wholly supported by a sign structure in 
the ground. 

PORTABLE DISPLAY SURFACE. A display surface tem- 
porarily fixed to a standardized advertising structure which is 
regularly moved from structure to structure at periodic inter- 
vals. 



PROJECTING SIGN. A sign other than a wall sign, which 
projects from and is supported by a wall of a building or struc- 
ture. 

ROOF SIGN. A sign erected upon or above a roof or parapet 
of a building or structure. 

SIGN. Any letter, figure, character, mark, plane, point, mar- 
quee sign, design, poster, pictorial, picture, stroke, stripe, line, 
trademark, reading matter or illuminated service, which shall 
be constructed, placed, attached, painted, erected, fastened or 
manufactured in any manner whatsoever, so that the same shall 
be used for the attraction of the public to any place, subject, per- 
son, firm, corporation, public performance, article, machine or 
merchandise, whatsoever, which is displayed in any manner 
outdoors. Every sign shall be classified and conform to the 
requirements of that classification as set forth in this chapter. 

SIGN STRUCTURE. Any structure which supports or is 
capable of supporting a sign as defined in this code. A sign 
structure is permitted to be a single pole and is not required to 
be an integral part of the building. 

WALL SIGN. Any sign attached to or erected against the wall 
of a building or structure, with the exposed face of the sign in a 
plane parallel to the plane of said wall. 



SECTION H103 
LOCATION 

HI03.1 Location restrictions. Signs shall not be erected, con- 
structed or maintained so as to obstruct any fire escape or any 
window or door or opening used as a means of egress or so as to 
prevent free passage from one part of a roof to any other part 
thereof. A sign shall not be attached in any form, shape or man- 
ner to a fire escape, nor be placed in such manner as to interfere 
with any opening required for ventilation. 



SECTION H104 
IDENTIFICATION 

HI04. 1 Identification. Every outdoor advertising display sign 
hereafter erected, constructed or maintained, for which a per- 
mit is required shall be plainly marked with the name of the per- 
son, firm or corporation erecting and maintaining such sign and 
shall have affixed on the front thereof the permit number issued 
for said sign or other method of identification approvedby the 
bUilding official. 



2009 INTERNATIONAL BUILDING CODE® 



631 



APPENDIX H 



SECTION H105 
DESIGN AND CONSTRUCTION 

HI05.1 General requirements. Signs shall be designed and 
constructed to comply with the provisions of this code for use 
of materials, loads and stresses. 

HI05.2 Permits, drawings and specifications. Where a per- 
mit is required, as provided in Chapter 1, construction docu- 
ments shall be required. These documents shall show the 
dimensions, material and required details of construction, 
including loads, stresses and anchors. 

HI05.3 Wind load. Signs shall be designed and constructed to 
withstand wind pressure as provided for in Chapter 16. 

HI05.4 Seismic load. Signs designed to withstand wind pres- 
sures shall be considered capable of withstanding earthquake 
loads, except as provided for in Chapter 16. 

HI05.5 Working stresses. In outdoor advertising display 
signs, the allowable working stresses shall conform to the 
requirements of Chapter 16. The working stresses of wire rope 
and its fastenings shall not exceed 25 percent of the ultimate 
strength of the rope or fasteners. 

Exceptions: 

1. The allowable working stresses for steel and wood 
shall be in accordance with the provisions of Chapters 

22 and 23. 

2. The working strength of chains, cables, guys or steel 
rods shall not exceed one-fifth of the ultimate strength 
of such chains, cables, guys or steel. 

HI05.6 Attachment. Signs attached to masonry, concrete or 
steel shall be safely and securely fastened by means of metal 
anchors, bolts or approved expansion screws of sufficient size 
and anchorage to safely support the loads applied. 



of 2 seconds or less and a burning extent of 5.9 inches (150 
mm) or less for 10 specimens. 

HI06.2 Electrical service. Signs that require electrical service 
shall comply with NFPA 70. 



SECTION H107 
COMBUSTIBLE MATERIALS 

HI07.1 Use of combustibles. Wood, approved plastic or plas- 
tic veneer panels as provided for in Chapter 26, or other materi- 
als of combustible characteristics similar to wood, used for 
moldings, cappings, nailing blocks, letters and latticing, shall 
comply with Section HI 09.1, and shall not be used for other 
ornamental features of signs, unless approved. 

HI07.1.1 Plastic materials. Notwithstanding any other 
provisions of this code, plastic materials which burn at a rate 
no faster than 2.5 inches per minute (64 mm/s) when tested 
in accordance with ASTM D 635 shall be deemed approved 
plastics and can be used as the display surface material and 
for the letters, decorations and facings on signs and outdoor 
display structures. 

HI07.1.2 Electric sign faces. Individual plastic facings of 
electric signs shall not exceed 200 square feet (18.6 m 2 ) in 
area. 

HI07.1.3 Area limitation. If the area of a display surface 
exceeds 200 square feet (18.6 m 2 ), the area occupied or cov- 
ered by approved plastics shall be limited to 200 square feet 
(18.6 m 2 ) plus 50 percent of the difference between 200 
square feet (18.6 m 2 ) and the area of display surface. The 
area of plastic on a display surface shall not in any case 
exceed 1,100 square feet (102 m 2 ). 

HI07.1.4 Plastic appurtenances. Letters and decorations 
mounted on an approved plastic facing or display surface 
can be made of approved plastics. 



SECTION H106 
ELECTRICAL 

HI06. 1 Illumination. A sign shall not be illuminated by other 
than electrical means, and electrical devices and wiring shall be 
installed in accordance with the requirements ofNFPA 70. Any 
open spark or flame shall not be used for display purposes 
unless specifically approved. 

HI06. 1 . 1 Internally illuminated signs. Except as provided 
for in Sections 402.16 and 2611, where internally illumi- 
nated signs have facings of wood or approved plastic, the 
area of such facing section shall not be more than 120 square 
feet (11.16 m 2 ) and the wiring for electric lighting shall be 
entirely enclosed in the sign cabinet with a clearance of not 
less than 2 inches (51 mm) from the facing material. The 
dimensional limitation of 120 square feet (11.16 m 2 ) shall 
not apply to sign facing sections made from flame- resis- 
tant-coated fabric (ordinarily known as "flexible sign face 
plastic") that weighs less than 20 ounces per square yard 
(678 g/m 2 ) and that, when tested in accordance with NFPA 
701, meets the fire propagation performance requirements 
of both Test 1 and Test 2 or that when tested in accordance 
with an approved test method, exhibits an average burn time 



SECTION H108 
ANIMATED DEVICES 

HI08. 1 Fail-safe device. Signs that contain moving sections or 
ornaments shall have fail-safe provisions to prevent the section 
or ornament from releasing and falling or shifting its center of 
gravity more than 15 inches (381 mm). The fail-safe device 
shall be in addition to the mechanism and the mechanism's 
housing which operate the movable section or ornament. The 
fail-safe device shall be capable of supporting the full dead 
weight of the section or ornament when the moving mechanism 
releases. 



SECTION H109 
GROUND SIGNS 

HI09.1 Height restrictions. The structural frame of ground 
signs shall not be erected of combustible materials to a height 
of more than 35 feet (10668 mm) above the ground. Ground 
signs constructed entirely of noncombustible material shall not 
be erected to a height of greater than 100 feet (30 480 mm) 
above the ground. Greater heights are permitted where 



632 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX H 



approved and located so as not to create a hazard or danger to 
the public. 

HI09.2 Required clearance. The bottom coping of every 
ground sign shall be not less than 3 feet (914 mm) above the 
ground or street level, which space can be filled with platform 
decorative trim or light wooden construction. 

HI09.3 Wood anchors and supports. Where wood anchors or 
supports are embedded in the soil, the wood shall be pressure 
treated with an approved preservative. 



SECTION H110 
ROOF SIGNS 

HII0.1 General. Roof signs shall be constructed entirely of 
metal or other approved noncombustible material except as 
provided for in Sections HI06.1.1 and HI07.1. Provisions 
shall be made for electric grounding of metallic parts. Where 
combustible materials are permitted in letters or other orna- 
mental features, wiring and tubing shall be kept free and insu- 
lated therefrom. Roof signs shall be so constructed as to leave a 
clear space of not less than 6 feet (1829 mm) between the roof 
level and the lowest part of the sign and shall have at least 5 feet 
(1524 mm) clearance between the vertical supports thereof. No 
portion of any roof sign structure shall project beyond an exte- 
rior wall. 

Exception: Signs on flat roofs with every part of the roof 
accessible. 

HII0.2 Bearing plates. The bearing plates of roof signs shall 
distribute the load directly to or upon masonry walls, steel roof 
girders, columns or beams. The building shall be designed to 
avoid overstress of these members. 

HII0.3 Height of solid signs. A roof sign having a solid sur- 
face shall not exceed, at any point, a height of 24 feet (7315 
mm) measured from the roof surface. 

HII0.4 Height of open signs. Open roof signs in which the 
uniform open area is not less than 40 percent of total gross area 
shall not exceed a height of 75 feet (22 860 mm) on buildings of 
Type 1 or Type 2 construction. On buildings of other construc- 
tion types, the height shall not exceed 40 feet (12 192 mm). 
Such signs shall be thoroughly secured to the building upon 
which they are installed, erected or constructed by iron, metal 
anchors, bolts, supports, chains, stranded cables, steel rods or 
braces and they shall be maintained in good condition. 

HII0.5 Height of closed signs. A closed roof sign shall not be 
erected to a height greater than 50 feet (15 240 mm) above the 
roof of buildings of Type 1 or Type 2 construction, nor more 
than 35 feet (10668 mm) above the roof of buildings of Type 3, 
4 or 5 construction. 



SECTION H111 
WALL SIGNS 

H 111.1 Materials. Wall signs which have an area exceeding 
40 square feet (3.72 m 2 ) shall be constructed of metal or other 
approved noncombustible material, except for nailing rails and 
as provided for in Sections HI06.1.1 and HI07.1. 



Hill. 2 Exterior wall mounting details. Wall signs attached 
to exterior walls of solid masonry, concrete or stone shall be 
safely and securely attached by means of metal anchors, bolts 
or expansion screws of not less than 3/ s mch (9.5 mm) diameter 
and shall be embedded at least 5 inches (127 mm). Wood 
blocks shall not be used for anchorage, except in the case of 
wall signs attached to buildings with walls of wood. A wall sign 
shall not be supported by anchorages secured to an unbraced 
parapet wall. 

H 1 1 1.3 Extension. Wall signs shall not extend above the top of 
the wall, nor beyond the ends of the wall to which the signs are 
attached unless such signs conform to the requirements for roof 
signs, projecting signs or ground signs. 



SECTION H112 
PROJECTING SIGNS 

HI 12.1 General. Projecting signs shall be constructed entirely 
of metal or other noncombustible material and securely 
attached to a building or structure by metal supports such as 
bolts, anchors, supports, chains, guys or steel rods. Staples or 
nails shall not be used to secure any projecting sign to any 
building or structure. The deadloadof projecting signs not par- 
allel to the building or structure and the load due to wind pres- 
sure shall be supported with chains, guys or steel rods having 
net cross-sectional dimension of not less than j/yinch (9.5 mm) 
diameter. Such supports shall be erected or maintained at an 
angle of at least 45 percent (0.78 rad) with the horizontal to 
resist the dead load and at angle of 45 percent (0.78 rad) or 
more with the face of the sign to resist the specified wind pres- 
sure. If such projecting sign exceeds 30 square feet (2.8 m 2 ) in 
one facial area, there shall be provided at least two such sup- 
ports on each side not more than 8 feet (2438 mm) apart to 
resist the wind pressure. 

HI 12.2 Attachment of supports. Supports shall be secured to 
a bolt or expansion screw that will develop the strength of the 
supporting chains, guys or steel rods, with a minimum 5/ s -inch 
(15.9 mm) bolt or lag screw, by an expansion shield. Turn buck- 
les shall be placed in chains, guys or steel rods supporting pro- 
jecting signs. 

HI 12.3 Wall mounting details. Chains, cables, guys or steel 
rods used to support the live or dead load of projecting signs are 
permitted to be fastened to solid masonry walls with expansion 
bolts or by machine screws in iron supports, but such supports 
shall not be attached to an unbraced parapet wall. Where the 
supports must be fastened to walls made of wood, the support- 
ing anchor bolts must go through the wall and be plated or fas- 
tened on the inside in a secure manner. 

HI 12.4 Height limitation. A projecting sign shall not be 
erected on the wall of any building so as to project above the 
roof or cornice wall or above the roof level where there is no 
cornice wall; except that a sign erected at a right angle to the 
building, the horizontal width of which sign is perpendicular to 
such a wall and does not exceed 18 inches (457 mm), is permit- 
ted to be erected to a height not exceeding 2 feet (610 mm) 
above the roof or cornice wall or above the roof level where 
there is no cornice wall. A sign attached to a corner of a build- 



2009 INTERNATIONAL BUILDING CODE® 



633 



APPENDIX H 



ing and parallel to the vertical line of such corner shall be 
deemed to be erected at a right angle to the building wall. 

HI 12.5 Additional loads. Projecting sign structures which 
will be used to support an individual on a ladder or other ser- 
vicing device, whether or not specifically designed for the 
servicing device, shall be capable of supporting the antici- 
pated additional load, but not less than a 100-pound (445 N) 
concentrated horizontal load and a 300-pound (1334 N) con- 
centrated vertical load applied at the point of assumed or 
most eccentric loading. The building component to which 
the projecting sign is attached shall also be designed to sup- 
port the additional loads. 



TABLE 4-B 
THICKNESS OF PROJECTION SIGN 



PROJECTION 

(feet) 


MAXIMUM THICKNESS 
(feet) 


5 


2 


4 


2.5 


3 


3 


2 


3.5 


1 


4 



For 51 : 1 foot = 304.8 mm. 



SECTION H113 
MARQUEE SIGNS 

HI 13.1 Materials. Marquee signs shall be constructed entirely 
of metal or other approved noncombustible material except as 
provided for in Sections H106.1.1 and H107.1. 

HI 13.2 Attachment. Marquee signs shall be attached to 
approved marquees that are constructed in accordance with 
Section 3106. 

HI 13.3 Dimensions. Marquee signs, whether on the front or 
side, shall not project beyond the perimeter of the marquee. 

HI 13.4 Height limitation. Marquee signs shall not extend 
more than 6 feet (1829 mm) above, nor 1 foot (305 mm) below 
such marquee, but under no circumstances shall the sign or 
signs have a vertical dimension greater than 8 feet (2438 mm). 



SECTION H115 
REFERENCED STANDARDS 

ASTM D 635-03 Test Method for 

Rate of Burning and/or 
Extent and Time of 
Burning of Self-Supporting 
Plastics in a Horizontal Position 



HI07.1.1 



NFPA 70-08 



National Electrical Code HI06.1, HI06.2 



NFPA 701-99 Methods of Fire Test for HI06.1.1 

Flame Propagation of Textiles 
and Films 



SECTION H114 
PORTABLE SIGNS 

HI 14.1 General. Portable signs shall conform to requirements 
for ground, roof, projecting, flat and temporary signs where 
such signs are used in a similar capacity. The requirements of 
this section shall not be construed to require portable signs to 
have connections to surfaces, tie-downs or foundations where 
provisions are made by temporary means or configuration of 
the structure to provide stability for the expected duration of 
the installation. 



TABLE 4-A 
SIZE, THICKNESS AND TYPE OF GLASS PANELS IN SIGNS 


MAXIMUM SIZE OF 
EXPOSED PANEL 


MINIMUM 
THICKNESS 
OF GLASS 

(inches) 


TYPE OF GLASS 


Any dimension 
(inches) 


Area 
(square inches) 


30 


500 


17 8 


Plain, plate or wired 


45 


700 


3/ 16 


Plain, plate or wired 


144 


3,600 


17 4 


Plain, plate or wired 


>144 


> 3,600 


17 4 


Wired glass 



For 51: 1 inch = 25.4 mm, 1 square inch = 645 . 16 mm 2 * 



634 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX I 

PATIO COVERS 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION 1101 (89 mm) thick and further provided that the columns do not 

GENERAL support loads in excess of 750 pounds (3.36 kN) per column. 

1101.1 General. Patio covers shall be permitted to be detached 
from or attached to dwelling units. Patio covers shall be used 
only for recreational, outdoor living purposes and not as car- 
ports, garages, storage rooms or habitable rooms. Openings 
shall be permitted to be enclosed with insect screening, 
approved translucent or transparent plastic not more that 0.125 
inch (3.2 mm) in thickness, glass conforming to the provisions 
of Chapter 24 or any combination of the foregoing. 

SECTION 1102 
DEFINITIONS 

1102.1 General. The following word and term shall, for the 
purposes of this appendix, have the meaning shown herein. 

PATIO COVERS. One story structures not exceeding 12 feet 
(3657 mm) in height. Enclosure walls shall be permitted to be 
of any configuration, provided the open or glazed area of the 
longer wall and one additional wall is equal to at least 65 per- 
cent of the area below a minimum of 6 feet 8 inches (2032 mm) 
of each wall, measured from the floor. 

SECTION 1103 
EXTERIOR OPENINGS 

1103.1 Light, ventilation and emergency egress. Exterior 
openings required for light and ventilation shall be permitted to 
open into a patio structure. However, the patio structure shall be 
unenclosed if such openings are serving as emergency egress 
or rescue openings from sleeping rooms. Where such exterior 
openings serve as an exit from the dwelling unit, the patio 
structure, unless unenclosed, shall be provided with exits con- 
forming to the provision of Chapter 10. 

SECTION 1104 
STRUCTURAL PROVISIONS 

1104.1 Design loads. Patio covers shall be designed and con- 
structed to sustain, within the stress limits of this code, all dead 
loads plus a minimum vertical live load of 10 pounds per square 
foot (0.48 kN/m 2 ) except that snow loads shall be used where 
such snow loads exceed this minimum. Such patio covers shall 
be designed to resist the minimum wind and seismic loads set 
forth in this code. 

1104.2 Footings. In areas with a frost depth of zero, a patio 
cover shall be permitted to be supported on a concrete slab on 
grade without footings, provided the slab conforms to the pro- 
visions of Chapter 19 of this code, is not less than 3V 2 inches 

2009 INTERNATIONAL BUILDING CODE® 635 



636 2009 INTERNATIONAL BUILDING CODE® 



APPENDIX J 

GRADING 

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance. 



SECTION J101 
GENERAL 

JI01.1 Scope. The provisions of this chapter apply to grading, 
excavation and earthwork construction, including fills and 
embankments. Where conflicts occur between the technical 
requirements of this chapter and the geotechnical report, the 
geotechnical report shall govern. 

JI01.2 Flood hazard areas. The provisions of this chapter shall 
not apply to grading, excavation and earthwork construction, 
including fills and embankments, in floodwayswithin flood haz- 
ardareas established in Section 1612.3 or in flood hazard areas 
where design flood elevations are specified but floodways have 
not been designated, unless it has been demonstrated through 
hydrologic and hydraulic analyses performed in accordance 
with standard engineering practice that the proposed work will 
not result in any increase in the level of the base flood. 



SECTION J102 
DEFINITIONS 

JI02.1 Definitions. For the purposes of this appendix chapter, 
the terms, phrases and words listed in this section and their 
derivatives shall have the indicated meanings. 

BENCH. A relatively level step excavated into earth material 
on which fill is to be placed. 

COMPACTION. The densification of a fill by mechanical 
means. 

CUT. See Excavation. 

DOWN DRAIN. A device for collecting water from a swale or 
ditch located on or above a slope, and safely delivering it to an 
approved drainage facility 

EROSION. The wearing away of the ground surface as a result 
of the movement of wind, water or ice. 

EXCAVATION. The removal of earth material by artificial 
means, also referred to as a cut. 

FILL. Deposition of earth materials by artificial means. 

GRADE. The vertical location of the ground surface. 

GRADE, EXISTING. The grade prior to grading. 

GRADE, FINISHED. The grade of the site at the conclusion 
of all grading efforts. 

GRADING. An excavation or fill or combination thereof. 

KEY. A compacted fill placed in a trench excavated in earth 
material beneath the toe of a slope. 

SLOPE. An inclined surface, the inclination of which is 
expressed as a ratio of horizontal distance to vertical distance. 



TERRACE. A relatively level step constructed in the face of a 
graded slope for drainage and maintenance purposes. 



SECTION J103 
PERMITS REQUIRED 

JI03.1 Permits required. Except as exempted in Section 
J 103. 2, no grading shall be performed without first having 
obtained aperra/nherefor from the building official. A grading 
permit does not include the construction of retaining walls or 
other structures. 

JI03 .2 Exemptions. A grading permit shall not be required for 
the following: 

1. Grading in an isolated, self-contained area, provided 
there is no danger to the public, and that such grading 
will not adversely affect adjoining properties. 

2. Excavation for construction of a structure permitted 
under this code. 

3. Cemetery graves. 

4. Refuse disposal sites controlled by other regulations. 

5. Excavations for wells, or trenches for utilities. 

6. Mining, quarrying, excavating, processing or stockpil- 
ing rock, sand, gravel, aggregate or clay controlled by 
other regulations, provided such operations do not affect 
the lateral support of, or significantly increase stresses 
in, soil on adjoining properties. 

7. Exploratory excavations performed under the direction 
of a registered design professional. 

Exemption from the permit requirements of this appendix 
shall not be deemed to grant authorization for any work to be 
done in any manner in violation of the provisions of this code or 
any other laws or ordinances of this jurisdiction. 



SECTION J104 
PERMIT APPLICATION AND SUBMITTALS 

JI04. 1 Submittal requirements. In addition to the provisions 
of Section 105.3, the applicant shall state the estimated quanti- 
ties of excavation and fill. 

JI04.2 Site plan requirements. In addition to the provisions of 
Section 107, a grading plan shall show the existing grade and fin- 
ished grade in contour intervals of sufficient clarity to indicate 
the nature and extent of the work and show in detail that it com- 
plies with the requirements of this code. The plans shall show the 
existing grade on adjoining properties in sufficient detail to iden- 
tify how grade changes will conform to the requirements of this 
code. 



2009 INTERNATIONAL BUILDING CODE® 



637 



APPENDIX J 



JI04.3 Geotechnical report. A geotechnical report prepared 
by a registered design professional shall be provided. The 
report shall contain at least the following: 

1. The nature and distribution of existing soils; 

2. Conclusions and recommendations for grading proce- 
dures; 

3. Soil design criteria for any structures or embankments 
required to accomplish the proposed grading; and 

4. Where necessary, slope stability studies, and recommen- 
dations and conclusions regarding site geology. 

Exception: A geotechnical report is not required where the 
building code official determines that the nature of the work 
applied for is such that a report is not necessary. 

JI04.4 Liquefaction study. For sites with mapped maximum 
considered earthquake spectral response accelerations at short 
periods (S) greater than 0.5g as determined by Section 1613, a 
study of the liquefaction potential of the site shall be provided, 
and the recommendations incorporated in the plans. 

Exception: A liquefaction study is not required where the 
building official determines from established local data that 
the liquefaction potential is low. 



SECTION J105 
INSPECTIONS 

JI05. 1 General. Inspections shall be governed by Section 109 
of this code. 

JI05.2 Special inspections. The special inspection require- 
ments of Section 1704.7 shall apply to work performed under a 
grading permit where required by the bUilding official. 



SECTION J1 07 
FILLS 

J 107.1 General. Unless otherwise recommended in the 
geotechnical report, fills shall comply with the provisions of 
this section. 

JI07.2 Surface preparation. The ground surface shall be pre- 
pared to receive fill by removing vegetation, topsoil and other 
unsuitable materials, and scarifying the ground to provide a 
bond with the fill material. 

J 107.3 Benching. Where existing grade is at a slope steeper than 
five units horizontal to one unit vertical (20-percent slope) and 
the depth of the fill exceeds 5 feet (1524 mm) benching shall be 
provided in accordance with Figure J 107. 3. A key shall be pro- 
vided which is at least 10 feet (3048 mm) in width and 2 feet (610 
mm) in depth. 

JI07.4 Fill material. Fill material shall not include organic, 
frozen or other deleterious materials. No rock or similar irre- 
ducible material greater than 12 inches (305 mm) in any dimen- 
sion shall be included in fills. 

JI07.5 Compaction. All fill material shall be compacted to 90 
percent of maximum density as determined by ASTM D 1557, 
Modified Proctor, in lifts not exceeding 12 inches (305 mm) in 
depth. 

JI07.6 Maximum slope. The slope of fill surfaces shall be no 
steeper than is safe for the intended use. Fill slopes steeper than 
two units horizontal to one unit vertical (50-percent slope) shall 
be justified by a geotechnical report or engineering data. 



SECTION J106 
EXCAVATIONS 

JI06. 1 Maximum slope. The slope of cut surfaces shall be no 
steeper than is safe for the intended use, and shall be no steeper 
than two units horizontal to one unit vertical (50-percent slope) 
unless the owner or authorized agent furnishes a geotechnical 
reportjustifying a steeper slope. 

Exceptions: 

1. A cut surface shall be permitted to be at a slope of 1.5 
units horizontal to one unit vertical (67 -percent slope) 
provided that all of the following are met: 

1.1. It is not intended to support structures or sur- 
charges. 

1.2. It is adequately protected against erosion. 

1.3. It is no more than 8 feet (2438 mm) in height. 

1.4. It is approved by the building code official. 

1.5. Ground water is not encountered. 

2. A cut surface in bedrock shall be permitted to be at a 
slope of one unit horizontal to one unit vertical 
(100-percent slope). 



SECTION J108 
SETBACKS 

JI08. 1 General. Cut and fill slopes shall be set back from the 
property lines in accordance with this section. Setback dimen- 
sions shall be measured perpendicular to the property line and 
shall be as shown in Figure J 108.1, unless substantiating data is 
submittedjustifying reduced setbacks. 

JI08.2 Top of slope. The setback at the top of a cut slope shall 
not be less than that shown in Figure J 108.1, or than is required 
to accommodate any required interceptor drains, whichever is 
greater. 

JI08.3 Slope protection. Where required to protect adjacent 
properties at the toe of a slope from adverse effects of the grad- 
ing' additional protection, approved by the bUilding official, 
shall be included. Such protection may include but shall not be 
limited to : 

1. Setbacks greater than those required by Figure J 108 . 1. 

2. Provisions for retaining walls or similar construction. 

3. Erosion protection of the fill slopes. 

4. Provision for the control of surface waters. 



638 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX J 



TOP OF FILL 




REMOVE UNSUITABLE 
MATERIAL 



For 51: 1 foot =304.8 mm. 



FIGURE J107.3 
BENCHING DETAILS 



Property 
Line 



HIS but 2 ft. (61 mm) minimum 
and need not exceed 
10ft. (3048 mm) maximum 



Top of 
Slope 



Property 
Line 



HIS but 2 ft. (61 mm) minimum 

and need not exceed 

20 ft. (6096 mm) maximum 



Top of 
Slope 



Cut or Fill 
Slope 





Natural or 
Finish Grade 



T 




Interceptor Drain 
(if required) 



Natural or 
Finish Grade 



For 51: 1 foot = 304.8 mm. 



FIGURE J108.1 
DRAINAGE DIMENSIONS 



2009 INTERNATIONAL BUILDING CODE® 



639 



APPENDIX J 



SECTION J109 
DRAINAGE AND TERRACING 

JI09.1 General. Unless otherwise recommended by a regis- 
tered design professional, drainage facilities and terracing 
shall be provided in accordance with the requirements of this 
section. 

Exception: Drainage facilities and terracing need not be 
provided where the ground slope is not steeper than 3 hori- 
zontal to 1 vertical (33 percent). 

JI09.2 Terraces. Terraces at least 6 feet (1829 mm) in width 
shall be established at not more than 30-foot (9144 mm) verti- 
cal intervals on all cut or fill slopes to control surface drainage 
and debris. Suitable access shall be provided to allow for clean- 
ing and maintenance. 

Where more than two terraces are required, one terrace, 
located at approximately mid-height, shall be at least 12 feet 
(3658 mm) in width. 

Swales or ditches shall be provided on terraces. They shall 
have a minimum gradient of 20 horizontal to 1 vertical (5 per- 
cent) and shall be paved with concrete not less than 3 inches (76 
mm) in thickness, or with other materials suitable to the appli- 
cation. They shall have a minimum depth of 12 inches (305 
mm) and a minimum width of 5 feet (1524 mm). 

A single run of swale or ditch shall not collect runoff from a 
tributary area exceeding 13,500 square feet (1256 m 2 ) (pro- 
jected) without discharging into a down drain. 

JI09.3 Interceptor drains. Interceptor drains shall be 
installed along the top of cut slopes receiving drainage from a 
tributary width greater than 40 feet (12 192 mm), measured 
horizontally. They shall have a minimum depth of 1 foot (305 
mm) and a minimum width of 3 feet (915 mm) . The slope shall 
be approved by the building official, but shall not be less than 
50 horizontal to 1 vertical (2 percent). The drain shall be paved 
with concrete not less than 3 inches (76 mm) in thickness, or by 
other materials suitable to the application. Discharge from the 
drain shall be accomplished in a manner to prevent erosion and 
shall be approved by the building official. 

JI09.4 Drainage across property lines. Drainage across 
property lines shall not exceed that which existed prior to grad- 
ing. Excess or concentrated drainage shall be contained on site 
or directed to an approved drainage facility. Erosion of the 
ground in the area of discharge shall be prevented by installa- 
tion of nonerosive down drains or other devices. 



JII0.2 Other devices. Where necessary, check dams, crib- 
bing, riprap or other devices or methods shall be employed to 
control erosion and provide safety. 



SECTION J111 
REFERENCED STANDARDS 

ASTMD Test Method for Laboratory J107.6 

1557-eOl Compaction Characteristics 

of Soil Using Modified Effort 
[56,000 ft-lb/ft 3 (2,700kN-m/m 3 )]. 



SECTION J110 
EROSION CONTROL 

JII0.1 General. The faces of cut and fill slopes shall be pre- 
pared and maintained to control erosion. This control shall be 
permitted to consist of effective planting. 

Exception: Erosion control measures need not be provided 
on cut slopes not subject to erosion due to the erosion-resis- 
tant character of the materials. 

Erosion control for the slopes shall be installed as soon as 
practicable and prior to calling for final inspection. 



640 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX K 

ADMINISTRATIVE PROVISIONS 



The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance 



With the exception of Section Kill, this appendix contains 
only administrative provisions that are intended to be used by a 
jurisdiction to implement and enforce NFPA 70, the National 
Electrical Code. Annex H of NFPA 70 also contains adminis- 
trative and enforcement provisions, and these provisions may 
or may not be completely compatible with or consistent with 
Chapter 1 ofthe IEC, whereas the provisions in IEC Appendix 
Kare compatible and consistent with Chapter 1 ofthe IEC and 
other ICC codes. Section Kill contains technical provisions 
that are unique to this appendix and are in addition to those of 
NFPA 70. 

The provisions of Appendix K are specific to what might be 
designated as an Electrical Department of Inspection and 
Code Enforcement and couldbe implemented where other such 
provisions are not adopted. 



SECTION K101 
GENERAL 

KIOI.I Purpose. A purpose of this code is to establish mini- 
mum requirements to safeguard public health, safety and gen- 
eral welfare by regulating and controlling the design, 
construction, installation, quality of materials, location, opera- 
tion and maintenance or use of electrical systems and equip- 
ment. 

KIOI.2 Scope. This code applies to the design, construction, 
installation, alteration, repairs, relocation, replacement, addi- 
tion to, use or maintenance of electrical systems and equip- 
ment. 



SECTION K102 
APPLICABILITY 

KI02.1 General. The provisions of this code apply to all mat- 
ters affecting or relating to structures and premises, as set forth 
in Section KIOI . 

KI02.2 Existing installations. Except as otherwise provided 
for in this chapter, a provision in this code shall not require the 
removal, alteration or abandonment of, nor prevent the contin- 
ued utilization and maintenance of, existing electrical systems 
and equipment lawfully in existence at the time ofthe adoption 
of this code. 

KI02.3 Maintenance. Electrical systems, equipment, materi- 
als and appurtenances, both existing and new, and parts thereof 
shall be maintained in proper operating condition in accor- 
dance with the original design and in a safe, hazard-free condi- 
tion. Devices or safeguards that are required by this code shall 
be maintained in compliance with the code edition under which 
installed. The owner or the owner's designated agent shall be 
responsible for the maintenance of the electrical systems and 
equipment. To determine compliance with this provision, the 



building official shall have the authority to require that the elec- 
trical systems and equipment be reinspected. 
KI02.4 Additions, alterations and repairs. Additions, alter- 
ations, renovations and repairs to electrical systems and equip- 
ment shall conform to that required for new electrical systems 
and equipment without requiring that the existing electrical 
systems or equipment comply with all ofthe requirements of 
this code. Additions, alterations and repairs shall not cause 
existing electrical systems or equipment to become unsafe, 
hazardous or overloaded. 

Minor additions, alterations, renovations and repairs to 
existing electrical systems and equipment shall meet the provi- 
sions for new construction, except where such work is per- 
formed in the same manner and arrangement as was in the 
existing system, is not hazardous and is approved. 

KI02.5 Subjects not regulated by this code. Where no appli- 
cable standards or requirements are set forth in this code, or are 
contained within other laws, codes, regulations, ordinances or 
bylaws adopted by thejurisdiction, compliance with applicable 
standards of nationally recognized standards as are approved 
shall be deemed as prima facie evidence of compliance with the 
intent of this code. Nothing herein shall derogate from the 
authority ofthe bUilding official to determine compliance with 
codes or standards for those activities or installations within the 
building official'sjurisdiction or responsibility. 



SECTION K103 
PERMITS 

KI03.1 Types of permits. An owner, authorized agent or con- 
tractor who desires to construct, enlarge, alter, repair, move, 
demolish or change the occupancy of a building or structure, or 
to erect, install, enlarge, alter, repair, remove, convert or 
replace electrical systems or equipment, the installation of 
which is regulated by this code, or to cause such work to be 
done, shall first make application to the building official and 
obtain the required permit for the work. 

Exception: Where repair or replacement of electrical sys- 
tems or equipment must be performed in an emergency situ- 
ation, the permit application shall be submitted within the 
next working business day of the department of electrical 
inspection. 

KI03.2 Work exempt from permit. The following work shall 
be exempt from the requirement for a. permit 

1. Listed cord- and plug-connected temporary decora- 
tive lighting. 

2. Reinstallation of attachment plug receptacles, but not 
the outlets therefor. 

3. Replacement of branch circuit overcurrent devices of 
the required capacity in the same location. 



2009 INTERNATIONAL BUILDING CODE® 



641 



APPENDIX K 



4. Temporary wiring for experimental purposes in suit- 
able experimental laboratories. 

5. Electrical wiring, devices, appliances, apparatus or 
equipment operating at less than 25 volts and not 
capable of supplying more than 50 watts of energy. 

Exemption from the permit requirements of this code shall 
not be deemed to grant authorization for work to be done in vio- 
lation of the provisions of this code or other laws or ordinances 
of this j urisdiction . 



SECTION K104 
CONSTRUCTION DOCUMENTS 

KI04.1 Information on construction documents. Construc- 
tion documents shall be drawn to scale upon suitable material. 
Electronic media documents are permitted to be submitted 
where approved by the building official. Construction docu- 
ments shall be of sufficient clarity to indicate the location, 
nature and extent of the work proposed and show in detail that 
such work will conform to the provisions of this code and rele- 
vant laws, ordinances, rules and regulations, as determined by 
the bUilding official. 

KI04.2 Penetrations. Construction documents shall indicate 
where penetrations will be made for electrical systems and 
shall indicate the materials and methods for maintaining 
required structural safety, fire-resistance rating and fireblock- 
ing. 

KI04.3 Load calculations. Where an addition or alteration is 
made to an existing electrical system, an electrical load calcula- 
tion shall be prepared to determine if the existing electrical ser- 
vice has the capacity to serve the added load. 



SECTION K105 
ALTERNATIVE ENGINEERED DESIGN 

KI05.1 General. The design, documentation, inspection, test- 
ing and approval of an alternative engineered design electrical 
system shall comply with this section. 

KI05.2 Design criteria. An alternative engineered design 
shall conform to the intent of the provisions of this code and 
shall provide an equivalent level of quality, strength, effective- 
ness, fire -resistance, durability and safety. Materials, equip- 
ment or components shall be designed and installed in 
accordance with the manufacturer's installation instructions. 

KI05.3 Submittal. The registered design professional shall 
indicate on the permit application that the electrical system is 
an alternative engineered design. The permit and permanent 
permit records shall indicate that an alternative engineered 
design was part of the approved installation. 

KI05.4 Technical data. The registered design professional 
shall submit sufficient technical data to substantiate the pro- 
posed alternative engineered design and to prove that the per- 
formance meets the intent of this code. 

KI05.5 Construction documents. The registered design pro- 
fessional shall submit to the bUilding officialtwo complete sets 
of signed and sealed construction documents for the alternative 



engineered design. The construction documents shall include 
floor plans and a diagram of the work. 

KI05.6 Design approval. Where the bUilding offic ial deter- 
mines that the alternative engineered design conforms to the 
intent of this code, the electrical system shall be approved. If 
the alternative engineered design is not approved, the building 
official shall notify the registered design professional in writ- 
ing' stating the reasons therefor. 

KI05.7 Inspection and testing. The alternative engineered 
design shall be tested and inspected in accordance with the 
requirements of this code. 



SECTION K106 
REQUIRED INSPECTIONS 

KI06.1 General. The building official, upon notification, shall 
make the inspections set forth in this section. 

KI06.2 Underground. Underground inspection shall be made 
after trenches or ditches are excavated and bedded, piping and 
conductors installed, and before backfill is put in place. Where 
excavated soil contains rocks, broken concrete, frozen chunks 
and other rubble that would damage or break the raceway, cable 
or conductors, or where corrosive action will occur, protection 
shall be provided in the form of granular or selected material, 
app roved running boards, sleeves or other means. 

KI06.3 Rough-in. Rough-in inspection shall be made after the 
roof, framing, fireblocking and bracing are in place and all wir- 
ing and other components to be concealed are complete, and 
prior to the installation of wall or ceiling membranes. 

KI06.4 Contractors' responsibilities. It shall be the responsi- 
bility of every contractor who enters into contracts for the 
installation or repair of electrical systems for which apermitis 
required to comply with adopted state and local rules and regu- 
lations concerning licensing. 



SECTION K107 
PREFABRICATED CONSTRUCTION 

KI07.1 Prefabricated construction. Prefabricated construc- 
tion is subject to Sections KI07.2 through KI07.5. 

KI07.2 Evaluation and follow-up inspection services. Prior 
to the approval of a prefabricated construction assembly hav- 
ing concealed electrical work and the issuance of an electrical 
permit, the building official shall require the submittal of an 
evaluation report on each prefabricated construction assembly, 
indicating the complete details of the electrical system, includ- 
ing a description of the system and its components, the basis 
upon which the system is being evaluated, test results and simi- 
lar information, and other data as necessary for the bUilding 
official to determine conformance to this code. 

KI07.3 Evaluation service. The building official shall desig- 
nate the evaluation service of an approved agency as the evalu- 
ation agency, and review such agency's evaluation report for 
adequacy and conformance to this code. 

KI07.4 Follow-up inspection. Except where ready access is 
provided to electrical systems, service equipment and accesso- 
ries for complete inspection at the site without disassembly or 



642 



2009 INTERNATIONAL BUILDING CODE® 



APPENDIX K 



dismantling, the building official shall conduct the in-plant 
inspections as frequently as necessary to ensure conformance 
to the approved evaluation report or shall designate an inde- 
pendent, appro ved inspection agency to conduct such inspec- 
tions. The inspection agency shall furnish the bililding official 
with the follow-up inspection manual and a report of inspec- 
tions upon request, and the electrical system shall have an iden- 
tifying label permanently affixed to the system indicating that 
factory inspections have been performed. 

K107.5 Test and inspection records. Required test and 
inspection records shall be available to the bUilding official 'at 
all times during the fabrication of the electrical system and the 
erection of the building; or such records as the bUilding official 
designates shall be filed. 



SECTION K108 
TESTING 

K108.1 Testing. Electrical work shall be tested as required in 
this code. Tests shall be performed by the permit holder and 
observed by the bUilding official. 

K108.1.1 Apparatus, material and labor for tests. Appa- 
ratus, material and labor required for testing an electrical 
system or part thereof shall be furnished by the permit 
holder. 

K108.1.2 Reinspection and testing. Where any work or 
installation does not pass an initial test or inspection, the 
necessary corrections shall be made so as to achieve compli- 
ance with this code. The work or installation shall then be 
resubmitted to the bUilding official fox inspection and test- 
ing. 



SECTION K109 
RECONNECTION 

K 109.1 Connection after order to disconnect. A person shall 
not make utility service or energy source connections to sys- 
tems regulated by this code, which have been disconnected or 
ordered to be disconnected by the bUilding official, or the use of 
which has been ordered to be discontinued by the bUilding offi- 
c/a/until the bUilding official authorizes the reconnection and 
use of such systems. 



immediate danger to life or property, such disconnection shall 
be made immediately without such notice. 



SECTION K111 
ELECTRICAL PROVISIONS 

Klll.l Adoption. Electrical systems and equipment shall be 
designed, constructed and installed in accordance with the 
International Residential Code or NFPA 70 as applicable, 
except as otherwise provided in this code. 

[F] Kill. 2 Abatement of electrical hazards. All identified 
electrical hazards shall be abated. All identified hazardous 
electrical conditions in permanent wiring shall be brought to 
the attention of the b Uilding official responsible for enforce- 
ment of this code. Electrical wiring, devices, appliances and 
other equipment which is modified or damaged and constitutes 
an electrical shock or fire hazard shall not be used. 

\F] Kill. 3 Appliance and fixture listing. Electrical appli- 
ances and fixtures shall be tested and listedin published reports 
of inspected electrical equipment by an appro ved agency and 
installed in accordance with all instructions included as part of 
such listing. 

Kill. 4 Nonmetallic-sheathed cable. The use of Type NM, 
NMC and NMS (nonmetallic sheathed) cable wiring methods 
shall not be limited based on height, number of stories or con- 
struction type of the building or structure. 

Kill. 5 Cutting, notching and boring. The cutting, notching 
and boring of wood and steel framing members, structural 
members and engineered wood products shall be in accordance 
with this code. 

Kill. 6 Smoke alarm circuits. Single- and multiple- station 
smoke alarms required by this code and installed within dwell- 
ing units shall not be connected as the only load on a branch cir- 
cuit. Such alarms shall be supplied by branch circuits having 
lighting loads consisting of lighting outlets in habitable spaces. 

Kill. 7 Equipment and door labeling. Doors into electrical 
control panel rooms shall be marked with a plainly visible and 
legible sign stating ELECTRICAL ROOM or similar approved 
wording. The disconnecting means for each service, feeder or 
branch circuit originating on a switchboard or panelboard shall 
be legibly and durably marked to indicate its purpose unless 
such purpose is clearly evident. 



SECTION K110 
CONDEMNING ELECTRICAL SYSTEMS 

KllO.l Authority to condemn electrical systems. Wherever 
the bUilding official determines that any electrical system, or 
portion thereof, regulated by this code has become hazardous 
to life, health or property, the bUilding official shall order in 
writing that such electrical systems either be removed or 
restored to a safe condition. A time limit for compliance with 
such order shall be specified in the written notice. A person 
shall not use or maintain a defective electrical system or equip- 
ment after receiving such notice. 

Where such electrical system is to be disconnected, written 
notice as prescribed in this code shall be given. In cases of 



2009 INTERNATIONAL BUILDING CODE® 



643 



644 2009 INTERNATIONAL BUILDING CODE® 



INDEX 



ACCESS OPENINGS 

Attic 1209.2 

Crawl space 1209.1 

Doors 712.3.2 

Fire damper 716.4 

Fire department 402.17 

Mechanical appliances 1209.3 

Refuse/laundry chutes 708.1 3.3 

ACCESSIBILITY 1007, Chapter 11, 

3411 , Appendix E 
Airports 412.3.6, E11 

Assembly seating 1 1 08.2, 1 1 09.1 

Bus stops E1 08 

Controls 1109.12 

Detectable warnings 1 1 09.9 

Detention and correctional facilities 1103.2.14, 

1107.5.5, 1108.4.2, 
3411.8.7, E104.1 
Dining areas 1109.10 

Drinking fountains 1 1 09.5 

Dwelling units 1107, 3411.1, 

3411.8.7,3411.8.8,3411.8.9 
Egress (see ACCESSIBLE MEANS 

OF EGRESS) 1007 

Elevators 1007.2.1, 1007.4, 

1109.6, 3001.3, 3411.8.2 
Employee work areas 907.5.2.3.2, 

1103.2.3, 1104.3.1 
Entrances 1 1 05, 341 1 .8.1 , 341 1 .9.3 

Escalators 341 1 .8.4 

Existing buildings 1007.1, 1103.2.2, 

3411,3412.2.5 
Fuel dispensing 1109.13, 3411.8.13 

Historic buildings 341 1 .9 

Judicial facilities 1108.4, 3411.8.7, 3411.8.10 

Kitchens 1109.4 

Laundry E105.2 

Lifts 1007.5,1109.7,3411.8.3 

Live/work unit. 419.7, 1103.2.13 

Maintenance 3411.2 

Parking and passenger loading facilities 1 106 

Performance areas 1 1 08.2.8, 341 1 .8.6 

Platform 1 1 04.4, 1 1 08.2.8, 341 1 .8.6, E1 03.1 

Ramps 1010,3411.8.5 

Recreational facilities 1109.14 

Route 1104, 1107.4,3411.7,3411.9.1,3411.9.2 

Scoping 108.2,116.1,1101, 

1103.1, 3411 .1, E101 .1 
Seating 1108.2, 1109.10 

Service facility 1109.11, 3411.8.12 

Signage 1110, E107 

Sleeping units 1 1 07,341 1 .8.7, 

3411.8.8, 3411.8.9 
Storage 1108.3, 1109.8 

Telephone E1 06 



Toilet and bathing facilities 1 1 09.2, 1 1 09.3, 

3411.8.11,3411.9.4, E105.1 

Train and light rail stations E109 

Transient lodging .... 11 03.2.1 1,11 07.6.1 , 341 1 .8.7, 

3411.8.9, E104.2, E104.3 

ACCESSIBLE MEANS OF EGRESS 1007 

Areas of refuge (see AREA OF REFUGE) 
Assembly 1007.1,1028.8 

Elevators 1007.2.1, 1007.4, 1007.8 

Existing building 1 007.1 ,341 1 .6 

Exterior area for assisted rescue (see EXTERIOR 

AREA FOR ASSISTED RESCUE) 
Horizontal exit (see HORIZONTAL EXIT) 
Mezzanine 505,1007.1 

Platform lift 1007.5 

Required 1007.1 

Stairs 1007.3 

Signage 1 007.8 through 1 007.1 1 , 3002.3 

ACCESSORY OCCUPANCIES ... 303.1, 305.1, 508.2 
Incidental accessory occupancies .. 508.2.5,707.3.6 

ADDITION 3403,0103.1 

Accessibility 3411.5 

Means of egress 3302.1 , 331 

ADMINISTRATION Chapter 1 

ADOBE CONSTRUCTION 2102.1,2109.3 

AEROSOLS 307.1 ,307.2,31 1 .2, 

414.1.2.1,414.2.5,907.2.16 

AGRICULTURAL BUILDINGS 

(see GROUP U) 312.1,1103.2.5, Appendix C 

AIR CONDITIONING 
(see MECHANICAL) 101.4.2, 2801.1, 3006.2 

AIR INTAKES (see YARDS OR COURTS) 1206.3.2 

AIRCRAFT HANGARS 412.4 

Aircraft paint hangars 412.6, 507.9 

Basements 412.4.2 

Construction 412.4.1, 412.6.2 

Fire area 412.4.6.2 

Fire suppression system 412.4.6,412.6.5 

Heliports and helistops 412.7 

Residential 412.5,907.2.21 

Unlimited height and area 504.1, 507.9 

AIRCRAFT-RELATED OCCUPANCIES 412, E110 

Airport traffic control towers 41 2.3,907.2.22 

Construction type 412.3.2 

Egress 412.3.3 

Fire detection systems, automatic 412.3.4, 

907.2.22 
Standby power 412.3.5, 2702.2.18 

Traffic control towers 412.3 

Type of construction 41 2.3.2 

AISLE 

Assembly seating 1 028.6 

Bleachers 1028.1.1 

Check-out 1109.11.2 



2009 INTERNATIONAL BUILDING CODE® 



645 



INDEX 



Converging 1028.9.3 

Egress 101 7 

Folding and telescopic seating 1028.1.1 

Grandstands 1028.1.1 

Obstructions 1028.9.6 

Tents 3103.4 

Walking surfaces 1028.11 

Width 1028.9 

ALARM SYSTEMS, EMERGENCY 908 

ALARMS, FIRE (see FIRE ALARM AND SMOKE 
DETECTION SYSTEMS) 

ALARMS, VISIBLE 

Common areas 

Employee work areas 

Group 1-1 

Group R-1 

Group R-2 

Public areas 
ALARMS, VOICE 

Amusement buildings, special 

Covered mall buildings 



High-rise buildings 

Special amusement buildings 

Underground buildings 



ALLOWABLE STRESS DESIGN 

Load combinations 

Masonry design 

Wood design 
ALTERATIONS 

Accessibility 

Compliance alternatives 

Means of egress 
ALTERNATIVE MATERIALS, 
DESIGN AND METHODS 

ALTERNATING TREAD DEVICES 
Construction 
Equipment platform 
Galleries, catwalks and gridirons 
Heliports 



907.5.2.3 

907.5.2.3.1 

907.2.5.3.2 

907.5.2.3.3 

907.5.2.3.3 

907.5.2.3.4 

907.5.2.3.1 

907.5.2.2 

411.6, 2702.2.1 

402.14, 402.15, 

907.2.20,2702.2.14 

403.4.3,907.2.13 

411.6 

405.9.1, 

907.2.18,907.2.19 

1602.1 

1605.3 

2101.2.1, 2107 

2301.2, 2306 

3404,0103.1 

3411.6, 3411.7, 3411.9 

3412 

3302.1, 3310.2, 3411.6 



104.11 

1009.10 

1009.10.2 

505.5 

410.5.3, 1015.6.1 

412.7.3 



ALUMINUM 1404.5.1, 1604.3.5, Chapter 20 

AMBULATORY HEALTH CARE FACILITIES 422 

Fire alarm and smoke detection 907.2.2.1 

Smoke compartment 422.2, 422.4 

AMUSEMENT BUILDING, SPECIAL 411 

Classification 411.1 

Emergency voice/alarm 

communications system 411 .6, 907.2.12 

Exit marking 411.7 

Fire detection 41 1 .3, 41 1 .5, 907.2.1 2 

Interior finish 411.8 

Smoke detection system 411.3, 411.5, 907.2.12 

Sprinklers 411.4 

AMUSEMENT PARK STRUCTURES 303 

ANCHOR STORE (see COVERED MALL 
AND OPEN MALL BUILDINGS) 402 

Construction type 402.6 



Means of egress 
Occupant load 
Separation 
Sprinkler 
ANCHORAGE 

Braced wall line sills 
Concrete 

Conventional light-frame 
construction 



402.4.3.1 

402.4.1.1, 402.4.1.3 

402.7.1, 402.7.3 

402.9 

1604.8 

2308.3.3 

1911, 1912 

2308.11.3.1, 2308.12.7, 
2308.12.8, 2308.12.9 
1604.8.3 



Decks 

Seismic anchorage for masonry chimneys 
Seismic anchorage for masonry fireplaces 
Walls 

Wood sill plates 
APARTMENT HOUSES 



2113.4 

2111.4 

1604.8.2 

2308.3.3 

310.1 

113 



APPEALS 

ARCHITECT (see definition for REGISTERED 

DESIGN PROFESSIONAL) 
ARCHITECTURAL TRIM 603.1,1406.2.2,0102.2.7 



AREA, BUILDING 
Aircraft control towers 
Aircraft hangars, residential 
Covered mall building 
Enclosed parking garage 

Limitations 

Membrane structures 

Mezzanines 

Mixed construction types 

Mixed occupancy 

Modifications 

Open mall building 

Open parking garage 



Chapter 5 

412.3.2 

412.5.5 

402.6 

509.2, 509.3, 

509.4, 509.9 

503, 505 

3102.4 

505.2, 505.5 

3102.6 

508 

506, 509 

402.6 

406.3.6,406.3.7, 

509.2, 509.3, 509.4, 

509.7, 509.8, 509.9 

406.1.1 ,406.1.2 

503.1.3, 506.2.1, 507 



Private garages and carports 

Unlimited area 
AREA FOR ASSISTED RESCUE, EXTERIOR 

(see EXTERIOR AREAS FOR ASSISTED RESCUE) 
AREA OF REFUGE 

(see ACCESSIBLE MEANS OF EGRESS) 

Requirements 1007.6, 1007.6.1, 1007.6.2 

Signage 1007.9,1007.10,1007.11 

Two-way communication 1007.6.3, 

1007.8, 1007.11 

Where required 1007.2,1007.3,1007.4 

ASSEMBLY OCCUPANCY (GROUP A) 303, 1028 

Accessory 508.2 

Aisles 1017.4,1028.9 

Amusement buildings, special 411 

Area 503,505,506,507,508 

Bleachers (see BLEACHERS) 

Egress, special provisions 

Fire alarms 

Folding and telescopic seating 

Guards 

Grandstands (see GRANDSTANDS) 

Height 503,504,505,506,508,509 



1008.1.10, 1028.3 
907.2.1 
1028.1.1 
1013.1,1028.14 



646 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



High-rise 403.1 

Interior finishes Table 803.9,804 

Live load Table 1607.1,1607.9.1.4,1607.11.2.2 

Motion picture theaters 409, 507.11 

Occupancy category Table 1604.5 

Panic hardware 1008.1.10, 1008.2.1 

Parking beneath or above 509.2,509.7.509.9 

Plumbing fixtures 2902 

Seating, fixed (see SEATING, FIXED) 
Seating, smoke-protected 1028.6.2 

Special occupancy separation 303.1 , 

Table 508.2.5, Table 508.4 

Sprinklers 507.3, 507.6, 507.7, 507.11, 903.2.1 

Stages and platforms 410 

Standby power systems 2702.2.1 

Standpipes 905.3.2, 905.5.1 

Travel distance 1014.3, 1016.1, 1021.2, 1028.7 

Unlimited area 507.3,507.6,507.7,507.1 1 



B 



ASSISTED LIVING (see RESIDENTIAL 
CARE/ASSISTED LIVING FACILITIES) 

ATRIUM 
Automatic sprinkler protection 
Enclosure 



Fire alarm system 

Interior finish 

Smoke control 

Standby power 

Travel distance 

Use 
ATTIC 

Access 

Combustible storage 

Draftstopping 

Insulation 

Live load 

Unusable space fire protection 

Ventilation 
AUDITORIUM 

Accessibility 

Foyers and lobbies 

Interior balconies and galleries 

Motion picture projection rooms 

Stages and platforms 
AUTOMOBILE PARKING GARAGE 

AUTOMOBILE PARKING) 

AWNINGS 

Design and construction 

Drainage, water 

Encroachment, public right-of-way 



404 

404.3 

404.6,707.3.5 

404.4,907.2.14 

404.8 

404.5,909 

404.7 



404.9, 1014.3, 1016.1, 



1021.2 
404.2 



1209.2 

413.2 

717.4 

719.3.1 

Table 1607.1 

712.3.3 

1203.2 

303.1 

1108.2 

1028.4 

1028.5 

409 

410 

(see GARAGE, 

406 

3105 

3105.3 

3201.4 

3202.2.3, 



3202.3.1,3202.4 
Fire district D1 02.2.8 

Live load Table 1607.1, 1607.11.2.1, 1607.11.4 

Materials 3105.4 

Motor vehicle service stations 406.5.3 

Permanent D1 02.2.8 

Plastic 2606.10 



BALCONIES 




Accessibility 


1108.2.4 


Assembly 


1028.5 


Construction, exterior. 


1406.3 


Egress, means of 


1016.2, 1019, 1028.5 


Emergency escape 


1029.1 


Exterior egress 


1016.2 


Guards 


1013.1 


Live load 


Table 1607.1 


Projection 


705.2, 1406.3 


Public right-of-way encroachments 3202.3.2, 




3202.3.3 


Travel distance 


1016.2 


BARBECUES 


2801 



BARRIERS 

Fire (see FIRE BARRIER) 

Pedestrian protection 3306 

Smoke (see SMOKE BARRIER) 

Vehicle 406.2.4,1602.1,1607.7.3 

BASEMENT (see UNDERGROUND BUILDINGS) 
Aircraft hangars 412.4.2 

Area modification 506.4, 506.5 

Considered a story 502.1 

Emergency escape 1029.1 

Flood loads 1612.2, 1612.5 

Height modifications for 509.5 

Prohibited ... 415.1, 415.4, 415.5, 415.8.5.2.2, 418.1 



Rodentproofing 


Appendix F 


Sprinklers 


903.2.11.1 


Waterproofing and dampproofing 


1805 


BASEMENT WALLS 




Concrete Table 1904.3, 1909.6.1 


Soil loads 


1610.1 


Waterproofing and dampproofing 


1805 


BASIC WIND SPEED 


1609.3 


BAY AND ORIEL WINDOWS 


1406.4 


Public right-of-way encroachments 


3202.3.2, 




3202.3.3 


BLEACHERS 303.1, 


1028.1.1, 3401.1 


Accessibility 


1108.2 


Egress 


1028.1.1 


Live load 


Table 1607.1 


Occupant load 


1004.7 


BLOCK (see CONCRETE BLOCK 




AND GLASS UNIT MASONRY) 




BOARD OF APPEALS 


113, Appendix B 


Application for appeal 


B1 01.1 


Alternate members 


B1 01.2.1 


Board decision 


B1 01.4 


Limitations on authority 


113.2 


Membership of board 


B1 01.2 


Notice of meeting 


B1 01.3 


Qualifications 


113.3, B101.2.2 



2009 INTERNATIONAL BUILDING CODE® 



647 



INDEX 



BOILER ROOM 




Exits 


1015.3 


BOLTS 


2204.2 


Anchors 


1911, 1912, 2204.2.1 


High strength, steel. 


1704.3.3 


BONDING, MASONRY 


2103.9,2109.2 


BRACED WALL LINE 


2302.1, 2308.3 


Bracing 


2309.3 


Seismic requirements 


2308.12.2, 




2308.12.4, 2308.12.6 


Sill anchorage 


2308.3.3 


Spacing 


2308.3.1 


Support 


2308.3.4 


BRACED WALL PANEL 


2302.1, 2308.9.3 


Alternative bracing 


2308.9.3.1, 2308.9.3.2 


Connections 


2308.3.2 


BRICK (see MASONRY) 




BUILDING 




Access, fire department 


402.17 


Area (see AREA, BUILDING) 


502.1, 503, 




505, 506, 507, 508, 509 


Demolition 


3303 


Existing 


Chapter 34 


Fire walls 


706.1 


Height (see HEIGHT, BUILDING) 502.1, 




503, 504, 505, 




506, 508, 509 


Occupancy classification 


Chapter 3 


Party walls 


706.1.1 


BUILDING DEPARTMENT 


103 


BUILDING OFFICIAL 




Duties and powers 


104 


Qualifications 


A101.1 


Records 


104.7 


Termination 


A101.4 



BUILT-UP ROOFS 



1507.10 



BUSINESS OCCUPANCY (GROUP B) 304 

Accessory 508.2 

Aisles 1017.2 

Ambulatory health care facilities 422 

Area 503,505,506,507,508 

Assembly 303.1 

Educational 303.1, 304.1 

Fire alarm 907.2.2 

Height 503,504,505,506,508,509 

Interior finishes Table 803.9,804 

Live load Table 1607.1 

Parking under or above .. 509.2,509.7,509.8,509.9 
Plumbing fixtures 2902 

Special occupancy separation .. 303.1, Table 508.2.5 
Travel distance 1014.3, 1016.1, 1021.2 

Unlimited area 507.3, 507.4 



CANOPIES 




3105 


Design and construction 


3105.3 


Drainage, water 




3201.4 


Encroachment, public 


right-of-way 


3202.3.1 


Fire district 




0102.2.8 


Live load 




Table 1607.1, 




1607.11.2.1,1607.11.4 


Materials 




3105.4 


Motor vehicle service 


stations 


406.5.3 


Permanent 




0102.2.8 


Plastic 




2606.10 


CARE FACILITIES (see 


HEALTH CARE) 


CARPET 






Floor covering 




804.2 


Textile ceiling finish 




803.6 


Textile wall coverings 




803.5 


CATWALKS 






Live loads 




Table 1607.1 


Means of egress 




410.3.2, 1015.6.1 


Sprinklers 




410.6 


CEILING 






Acoustical 




808 


Height 409.2, 909.20.4. 3 ; 


, 1205.2.2, 1208.2 


Interior finish 




803 



Penetration of fire resistant assemblies 



Suspended acoustical. 
CELLULOSE NITRATE FILM 
CERAMIC TILE 

Material requirements 

Mortar 
CERTIFICATE OF OCCUPANCY 
CHANGE OF OCCUPANCY 

Accessibility 
CHILD CARE (see DAY CARE) 



713.4, 
716.2, 716.6 
808.1.1 
409.1, 903.2.5.3 



CABLES, STEEL STRUCTURAL 
CALCULATED FIRE RESISTANCE 
(see FIRE RESISTANCE, CALCULATED) 



2207 



2103.5 

2103.10 

106.2, 111, 3408.2 

3408,0103.2 

3411.4, 3412.2.5 

305.2,308.3.1, 
308.5.2, 310.1 

CHIMNEYS 2102.1,2111,2112,2113 

Factory-built 717.2.5 

Flashing 1503.6 

Protection from adjacent construction 3307.1 

CHURCHES 

(see RELIGIOUS WORSHIP, PLACES OF) 
CIRCULAR STAIRS (see CURVED STAIRWAYS) 

CLAY ROOF TILE 1507.3 

Testing 1716.2 

CLINIC 

Hospital 308.3 

Outpatient (see AMBULATORY 

HEALTH CARE FACILITIES) 304.1.1,422 

COAL POCKETS 415.6.1.6 

CODES 101.2,101.4,102.3, 

102.4, 102.6, Chapter 35 

COLD STORAGE (see FOAM PLASTIC INSULATION) 

COLD-FORMED STEEL 2202.1 ,2209 

Light-frame construction 2210 

Special inspection 1704.3.1.2, 1704.3.4, 

1706.3, 1707.4 



648 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



COMBUSTIBLE DUSTS 
COMBUSTIBLE LIQUIDS 



415.6.1 
307.4,307.5,415.6.2 



COMBUSTIBLE MATERIAL 




Concealed spaces 


413.2, 717.5 


Exterior side of exterior wall 


1406 


High-pile stock or rack storage 


413.1, 910.2.2 


Type I and Type II 


603, 805 


COMBUSTIBLE PROJECTIONS 


705.2, 1406.3 


COMBUSTIBLE STORAGE 


413, 910.2.2 


COMMON PATH OF EGRESS TRAVEL 1014.3 


COMPARTMENTATION 




Ambulatory Health Care Facilities 422.2 


Group 1-2 


407.4 


Group 1-3 


408.6 


Underground buildings 


405.4 


Values 


3412.6.3 


COMPLIANCE ALTERNATIVES 


3412 


COMPRESSED GAS 


307.2,415.8.7.2.2 


CONCEALED SPACES 


413.2, 717 


CONCRETE 


Chapter 19 


ACI 318 modifications 


1901.2, 1901.3, 




1902.1, 1903.1, 1908 


Anchorage 


1911, 1912 


Calculated fire resistance 


721.2 


Conduits 


1906 


Construction documents 


1901 .4 


Construction joints 


1906 


Curing 


1905.11 


Durability 


1904 


Exposure conditions 


1904 


Footings 


1809 


Formwork 


1906 


Foundation walls 


1807.1.5,1808.8 


Materials 


1704.4.1, 1903 


Mixing 


1905.8 


Pipe columns, concrete-filled 


1915 


Pipes 


1906 


Placing 


1905 


Plain, structural 


1909 


Proportioning 


1905.2 


Quality 


1905 


Reinforced gypsum concrete 


1914 


Reinforcement. 


1907 


Rodentproofing 


Appendix F 


Roof tile 


1507.3, 1716.2 


Shotcrete 


1913 


Slab, minimum 


1910 


Special inspections 


1704.4, Table 1704.4 


Specifications 


1903 


Strength testing 


1704.4.1, 1905.6 


Wood support 


2304.12 


CONCRETE MASONRY 




Calculated fire resistance 


721.3 


Construction 


2104 


Design 


2101.2, 2108, 2109 


Materials 


2103.1 


Surface bonding 


2109.2 


Testing 


2105.2.2.2, 2105.3 



Wood support 
CONCRETE ROOF TILE 
Wind resistance 



2304.12 

1507.3 
1609.5.3, 1716.2 



CONDOMINIUM (see APARTMENT HOUSES) 

CONDUIT, PENETRATION PROTECTION 713.3, 

1022.4 

CONFLICTS IN CODE 102.1 

CONGREGATE LIVING FACILITIES 310 

CONSTRUCTION (see SAFEGUARDS DURING 
CONSTRUCTION) 



CONSTRUCTION DOCUMENTS 


5 107, 1603 


Concrete construction 


1901.4 


Design load bearing capacity 


1803.6 


Fire alarm and detection syste 


ms 907.1.1 


Fire-resistant-joint systems 


714 


Flood 


1603.1.7 


Floor live load 


1603.1.1 


Geotechnical. 


1603.1.6 


Masonry 


2101.3 


Means of egress 


107.2.3 


Penetrations 


71 3 


Permit application 


105.1 


Retention 


107.5 


Review 


107.3 


Roof assemblies 


1503 


Roof live load 


1603.1.2 


Roof snow load 


1603.1.3 


Seismic 


1603.1.5, 1603.1.9 


Site plan 


107.2.5 


Soil classification 


1803.6 


Special inspections 


1703, 1705 


Special loads 


1603.1.8 


Structural tests 


1703 


Systems and components 


1603.1.9 


Temporary structures 


3103.2 


Wind load 


1603.1.4 


CONSTRUCTION JOINTS 




Concrete 


1906.4 


Shotcrete 


1913.7 


CONSTRUCTION TYPES 


Chapter 6 


Aircraft related 


412.3.2 


Automobile parking garage 


Table 406.3.3, 




509.2, 509.3, 509.4, 




509.7,509.8,509.9 


Classification 


602 


Combustible material in 




Type I and Type II construction 603,805 


Covered mall and open mall buildings 402.6 


Fire district 


0102.2.3 


Fire resistance 


Table 601, Table 602 


High-rise 


403.2 


Type I 


Table 601, 602.2, 603 


Type II 


Table 601, 602.2, 603 


Type III 


Table 601,602.3 


Type IV 


Table 601, 602.4 


Type V 


Table 601 , 602.5 


Underground buildings 


405.2 



CONTRACTOR'S RESPONSIBILITIES 901.5, 1706 



2009 INTERNATIONAL BUILDING CODE® 



649 



INDEX 



CONTROL AREA 414.2,707.3.7 

Fire-resistance rating 414.2.4 

Number 414.2.3 

CONVENTIONAL LIGHT-FRAME 
CONSTRUCTION 2301.2, 2302.1, 2308 

Additional seismic requirements 2308.11, 2308.12 

Braced wall lines 2308.3 

Connections and fasteners 2308.5 

Design of elements 2308.4 

Floorjoists 2308.8 

Foundation plates or sills 2308.6 

Girders 2308.7 

Limitations 2308.2 

Roof and ceiling framing 2308.10 

Wall framing 2308.9 

CONVEYING SYSTEMS 3005 

CORNICES 

Draftstopping 717.2.6 

Live load Table 1607.1 

Masonry 2104.2.1 

Projection 705.2, 1406.3 

Public right-of-way encroachments 3202.3.2, 

3202.3.3 

CORRIDOR (see CORRIDOR PROTECTION, 
EXIT ACCESS and FIRE PARTITIONS) 1018 

Continuity 1018.6 

Deadend 1018.4 

Elevation change 1003.5 

Group 1-2 407.2 

Hazardous 415.8.2.2,415.8.2.7, 

415.8.3, 415.8.4, 415.8.6, 415.8.7.1.4 
Headroom 1003.2,1003.3 

HPM service 903.2.5.2 

Live load Table 1607.1 

Walls 709.1, 1018.1 

Width 108.3,1018.2 

CORRIDOR PROTECTION, EXIT ACCESS 
Construction, fire protection 709.1, 

Table 1018.1,1018.6 
Doors 715.4 

Glazing 715.5 

Group 1-2 407.3 

Interior finish Table 803.9, 804.4 

Opening protection 715, 716.5.4.1 

Ventilation 1018.5, 1018.5.1 

CORROSIVES 307.6, Table 414. 2. 5(1), 414. 3, 

415.7.3,Table 415.8.2.1.1 

COURTS (see YARDS OR COURTS) 1206 

COVERED MALL AND 
OPEN MALL BUILDINGS 402 

Construction type 402.6 

Fire department 402.3, 402.17 

Fire detection/alarm system 402.4.5.1, 402.11, 

402.12.2, 402.15, 
907.2.20,2702.2.14 
Interior finish 402.8 

Kiosk 402.11 

Means of egress 402.4, 402.5, 402.13 

Occupant load 402.4.1 



Playground structures 
Separation 
Signs 

Smoke control 
Sprinklers 
Standby power 
Standpipe system 
Travel distance 



402.1 2 

402.7 

402.16 

402.10 

402.9 

402.14, 2702.2.14 

402.9.1, 905.3.3 

402.4, 1014.3, 1016.1, 1021.2 

3306.7 



COVERED WALKWAY 

CRAWLSPACE 

Access 1209.1 

Drainage 1805.1.2 

Unusable space fire protection 712.3.3 

Ventilation 1203.3 

CRIPPLE WALL 2302.1, 2308.9.4 

CRYOGENIC Table 307.1 ,Table 414.5.1 , 

Table 415.8.2.1.1 

D 

DAMPERS (see FIRE DAMPERS 
AND SMOKE DAMPERS) 716.2 through 716.5 

DAMPPROOFING AND WATERPROOFING .... 1805 
Required 1805.2, 1805.3 

Subsoil drainage system 1805.4 

DAY CARE 305.2,308.5,310.1 

Adult care 308.5.1 

Child care 308.5.2,310.1 

Egress 308.5.2, Table 1004.1.1, 

Table 1015.1, Table 1021.2 

DAY SURGERY CENTER (see AMBULATORY 
HEALTH CARE FACILITIES) 

DEAD END 1018.4 

DEAD LOAD 1602.1, 1606 

Foundation design load 1808.3 

DECK 
Anchorage 1604.8.3 

Live loads Table 1607.1 

DEFLECTIONS 1604.3.1 

Framing supporting glass 2403.3 

Preconstruction load tests 1715.3.2 

Wood diaphragms 2305 

Wood shear walls 2305 

DEMOLITION 3303 

DESIGN STRENGTH 1602.1,2102.1 

Conformance to standards 1711 .1 

New materials 1711 .2 

DESIGNATED SEISMIC SYSTEM 1702.1 

Seismic qualification 1708.4 

Special inspection 1707.8 

DIAPHRAGMS 1602.1, 2302.1 

Flexible 1613.6.1 
Special inspection 1704.6.1,1706.2,1707.3 

Wood 2305, 2306.2 

DOORS 1008 

Access-controlled 1 008. 1 .4.4 

Emergency escape 1029.1 



650 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Fire (see OPENING PROTECTIVES) 715.4, 

1022.3, 1022.4 
Glazing 715.4.7,715.5,1405.13 

Hazardous storage 415.8.5.6 

Hardware (see LOCKS AND LATCHES) 1005.3, 

1008.1.4.4, 
1008.1.9, 1008.1.10 
Horizontal sliding 1008.1.4.3 

Hydrogen cutoff rooms 421 .4.1 

Landings 1008.1.5, 1008.1.6 

Operation 1008.1.3,1008.1.9 

Panic and fire exit hardware 1 008.1 .1 

Power operated 1008.1.4.2 

Revolving 1008.1.4.1 

Security grilles 1008.1.4.5 

Side swinging 1008.1.2 

Smoke 710.5,711.5 

Stairways 1008.1.9.10 

Stairways, high-rise 403.5.3 

Structural testing, exterior 1715.5 

Thresholds 1003.5, 1008.1.5, 1008.1.7, 3411.8.14 
Vestibule 1008.1.7 

Width 1008.1.1, 1008.1.1.1 

DRAFTSTOPPING 
Attics 717.4 

Floor-ceiling assemblies 717.3 

DRY CLEANING PLANTS 415.6.4 

DRYING ROOMS 417 

DUCTS AND AIR TRANSFER OPENINGS 
(see MECHANICAL) 

DUMBWAITERS 708.14 

DWELLING UNITS 202 

Accessibility 1102, 1103.2.4, 1103.2.12, 

1105.1.6,1106.2,1107 
Accessibility, existing 3411.1, 3411.8.7, 

3411.8.8, 3411.8.9 
Area 1208.3, 1208.4 

Group R 310 

Live/work units (see LIVE/WORK UNITS) 
Scoping 101.2 

Separation 420.2, 420.3 

Sound transmission 1207 



EARTHQUAKE LOADS (see SEISMIC) 1613 

EAVES (see COMBUSTIBLE PROJECTIONS 

AND CORNICES) 
EDUCATIONAL OCCUPANCY (GROUP E) 305 

Accessory 508.2 

Accessory assembly spaces 303.1 

Area 503,505,506,507,508 

Corridors 1018.1, 1018.2 

Daycare 305.2, 308.5, 310.1 

Education for students above the 12th grade 304 

Egress, special provisions 1008.1.10 

Fire alarm and detection 907.2.3 

Gyms 303.1 

Height 503,504,505,506,508 



Interior finishes 

Live load 

Manual fire alarm boxes 

Occupancy category 

Panic hardware 

Plumbing fixtures 

Religious facilities 



Table 803.9,804 

Table 1607.1 

907.2.3,907.4.2 

Table 1604.5 

1008.1.10 

2902 

303.1 



Special occupancy separation .. 303.1, Table 508.2.5 
Sprinkler system 903.2.3 

Stages and platforms 410 

Travel distance 1014.3, 1016.1, 1021.2 

Unlimited area 507.10 

EGRESS (see MEANS OF EGRESS) Chapter 10 

ELECTRICAL 105.2, 112, Chapter 27, Appendix K 

ELEVATOR Chapter 30 

Accessibility 1007.2.1, 1007.4, 

1007.8, 1109.6, 3001.3, 3411.8.2 
Car size 3001.3, 3002.4 

Construction 708.14, 1607.8.1 

Control values 3412.6.14 

Conveying systems 3005 

Emergency operations 3002.3, 3002.5, 

3003, 3007, 3008 
Fire service access 403.6.1, 3007 

Glass 2409, 3002.8 

High-rise 403.2.3,403.4.7,403.4.8,403.6 

Hoistwayenclosures 403.2.3, 708, 

1022.3,3002,3005.3.1 
Hoistway venting 3004 

Lobby .... 708.14.1, 709.1, 1007.4, 3007.4, 3008.11 
Machine rooms Table 1607.1, 1607.8, 3006 

Means of egress 403.6,1003.7, 

1007.2.1,1007.4,3008 
Number of elevator cars in hoistway 3002.2 

Occupant evacuation elevators 403.6.2, 3008 

Personnel and material hoists 3005.4 

Roof access 1009.14 

Seismic controls 1613.6.5 

Shaft enclosure 708.14 

Signs 914,1007.8.2,3002.3,3008.11.5 

Standards 3001 

Standby power 2702.2.5, 2702.2.19 

Underground 405.4.3 

EMERGENCY COMMUNICATIONS 

Accessible means of egress 1007.8 
Alarms (see FIRE ALARMS) 

Elevators, occupant evacuation 3008.5 

Fire command center 403.4.5, 911 

Radio coverage 403.4.4,915 

EMERGENCY EGRESS OPENINGS 1029 

Required Table 1021.2, 1029.1 

Window wells 1029.5 

EMERGENCY LIGHTING 1006,1205.5 

EMERGENCY POWER 2702.1 ,2702.3 

Exit signs 1011.5.3,2702.2.3,2702.2.9 

Group A 2702.2.1 

Group 1-3 408.4.2, 2702.2.17 

Hazardous 414.5.4, 415.8.10, 2702.2.8, 

2702.2.10, 2702.2.11, 2702.2.13 



2009 INTERNATIONAL BUILDING CODE® 



651 



INDEX 



High-rise 

Means of egress illumination 
Semiconductor fabrication 
Underground buildings 
EMERGENCY RESPONDERS 
Additional exit stairway 
Elevators 

Fire command center 

Fire department access 

Radio coverage 

Roof access 

Safety features 
EMPIRICAL DESIGN OF MASONRY 

Adobe construction 

General 

Special inspection 

Surface-bonded 
EMPLOYEE 

Accessibility for work areas 907.5.2.3.2, 

1103.2.3, 1104.3.1 

Qualifications A101 

Termination of employment A101.4 

ENCROACHMENTS INTO THE 
PUBLIC RIGHT-OF- WAY Chapter 32 

END-JOINTED LUMBER 2303.1.1 

ENERGY EFFICIENCY .. 101.4.6, 110.3.7, Chapter 13 

ENGINEER (see definition for REGISTERED 
DESIGN PROFESSIONAL) 

EQUIVALENT OPENING FACTOR 

ESCALATORS 

Accessibility 

Floor opening protection 

Means of egress 
ESSENTIAL FACILITIES (see OCCUPANCY 

CATEGORY) 1602.1 

EXCAVATION, GRADING AND FILL 1804, 3304 

EXISTING BUILDING 102.6, Chapter 34 

Accessibility 1103.2.2, 3411 

Additions 3403, 0103.1 

Alteration 3404, 0103.1 

Change of occupancy 3408,01 03.2 



403.4.8, 2702.2.15 


Luminous 403.5.5, 411 .7.1, 1024 


1006.3, 2702.2.4 


Mezzanines 505.3,505.4,1004.6 


415.8.10, 2702.2.8 


Number, minimum 403.5, 1015.1, 1021 


405.9, 2702.2.16 


Passageway 1 023 




Ramps, exterior. 1026 


403.5.2 


Refrigerated rooms or spaces 1015.5 


403.6,1007.2.1,3002.4, 


Refrigeration machinery rooms 1015.4 


3003, 3007, 3008 


Signs 1011 


403.4.5, 911 


Stairs, exterior 1026 


402.17 


Travel distance 104.2.2,402.4,404.9,407.4, 


403.4.4,915 


408.6.1, 408.8.1, 411.4, 1014.3, 


1009.13 


1015.5, 1016, 1021.2, 1028.7 


914 


Underground buildings 405.7 


ONRY.. 2101.2.4,2109 


EXIT ACCESS 


2109.3 


(see MEANS OF EGRESS) 1014 through 1019 


2109.1 


Aisles 1017 


1704.5 


Balconies 1016.2, 1019 


2109.2 


Common path 1014.3 




Corridors 1018 



Figure 705.7 

3005 

3411.8.4 

708.2 

1003.7 



Flood resistant. 



Historic 

Moved structures 

Repairs 

Rodentproofing 

EXIT (see MEANS OF EGRESS) 
Boiler rooms 
Construction 
Enclosure 
Fire resistance 
Furnace rooms 
Group H 
Horizontal 
Incinerator rooms 
Interior finish 



3401.2, 3403.2, 3404.2, 3405.5, 
3409.2, 3412.2.4.1, Appendix G 
3409, 3411.9 
3410,0103.3 
3405 
Appendix F 

. 1020 through 1026 

1015.3 

708.2 

707.3.2,1022.1 

707.3, 1022 

1015.3 

415.8.4.4, 415.8.5.5 

707.3.3,1025 

1015.3 

Table 803.9,804 



Ooors 1005.2,1008,1015,1020.2 

Intervening space 1014.2 

Path of egress travel, common 1014.3 

Seating at tables 1017.3 

Single exit 1015.1.1, 1021.2 

Travel distance 402.4,404.9,407.4, 

408.6.1, 408.8.1, 411.4, 1014.2.2, 
1014.3, 1015.5, 1016, 1021.2, 1028.7 

EXIT DISCHARGE (see MEANS OF EGRESS) .. 1027 

Courts 1027.5 

Horizontal exit 1027.1 

Lobbies 1027.1 

Marquees 3106.4 

Open parking garage 1027.1 

Public way 1027.6 

Termination 1022.2 

Vestibules 1027.1 



EXIT PASSAGEWAY 
(see MEANS OF EGRESS) 

EXIT SIGNS 
Accessibility 

Illumination 1011. 

Required 
Special amusement buildings 

EXPLOSIVES 

Table 415. 

EXPOSURE CATEGORY (see WIND 

EXTERIOR AREAS FOR ASSISTED 
Requirements 

Signage 1007.9, 

Where required 

EXTERIOR INSULATION AND 
FINISH SYSTEMS (EIFS) 
Special inspection 

EXTERIOR WALLS 
(see WALLS, EXTERIOR) 



707.3.3,1023 

1011 

1011.3 

2, 1011.4, 1011.5 

1011.1 

411.7 

Table 414.5.1 , 
3.1, Table 415.3.2 

LOAD) .. 1609.4 

RESCUE 

1007.7 
1007.10,1007.11 

1007.2 

1408 
1704.14 

Table 601, 602, 
705, Chapter 14 



652 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



FACTORY OCCUPANCY (GROUP F) 306 

Accessory 508.2 

Area 403.1, 503, 503.1.1, 

505, 506, 507, 508 
Dead end corridor 1018.4 

Fire alarm and detection 907.2.4 

Height 503,504,505,506,508 

Interior finishes Table 803.9,804 

Live load Table 1607.1 

Low hazard occupancy 306.3 

Moderate hazard occupancy 306.2 

Plumbing fixtures 2902 

Smoke and heat vents 910.2 

Special occupancy separation Table 508.2.5 

Travel distance 1014.3, 1015.4, 

1015.5, 1016.1, 1021.2 
Unlimited area 507.2,507.3,507.4 

FARM BUILDINGS Appendix C 

FEES, PERMIT 109 

Refunds 109.6 

Related fees 109.5 

Work commencing before issuance 109.4 

FENCES 105.2, 312.1 

FIBERBOARD 2302.1, 2303.1.5 

Shear wall 2306.6 

FILL MATERIAL 1804, 3304 

FINGER-JOINTED LUMBER 
(see END-JOINTED LUMBER) 

FIRE ALARM AND SMOKE DETECTION SYSTEMS 
Aerosol storage 907.2.16 

Aircraft hangars, residential 907.2.21 

Airport traffic control towers 41 2.3.4 

Ambulatory care facilities 422.6, 907.2.2.1 

Assembly 907.2.1 

Atriums 907.2.14 

Audible alarm 907.9.2 

Battery room 907.2.23 

Construction documents 907.1.1 

Covered mall and open mall 402.4.5.1, 402.11, 

402.12.2,402.15,907.2.20 
Education 907.2.3 

Emergency system 908 

Factory 907.2.4 

Group H 907.2.5, 907.2.15 

Group I 907.2.6,907.5.2.3.3 

Group M 907.2.7 

Group R 907.2.8, 907.2.9, 907.2.10, 

907.2.11,907.5.2.3.3,907.5.2.3.4 
High-rise 403.4.2, 907.2.13 

Institutional occupancy 407.2.1 ,407.2.3,407.6 

Live/work 419.5,907.2.9 

Lumber mills 907.2.17 

Occupancy requirements 907.2 

Special amusement buildings 41 1 .3,41 1 .5, 

907.2.12 
Underground buildings 907.2.18,907.2.19 



Visible alarm 






907.5.2.3 


FIRE ALARM BOX, 


MANUAL 


907.4.2 


FIRE AREA 






901.7 


Ambulatory health 


care 


facilities 


903.2.2, 907.2.2 


Assembly 






903.2.1 


Education 






903.2.3 


Factory 






903.2.4 


Institutional 






903.2.6 


Mercantile 






903.2.7 


Residential 






903.2.8 


Storage 






903.2.9, 903.2.10 


FIRE BARRIERS 






110.3.6,707,708 


Continuity 






707.5, 708.4 



Exterior walls Table 602, 707.4, 708.6 

Fire-resistance rating of walls 603.1 (21), 

603.1 (22), 603.1 (25), 
703,707.3,708.3 
Glazing, rated 715.5 

Incidental accessory occupancies 508.2.5.1 

Joints ' 707.8, 708.9, 714, 2508.4 

Marking 703.6 

Materials 707.2, 708.3 

Opening protection 707.6,707.9,708.7, 

708.10, 713.3, 715, 716.5.2 
Penetrations 707.7,708.8 

Shaft enclosure 708.1 

Special provisions 
Aircraft hangars 412.4.4 

Atriums 404.3, 404.6 

Covered malls 402.4.6,402.7.1,402.7.3 

Fire pumps 913.2.1 

Flammable finishes 416.2 

Group H-2 415.6.1.2, 415.6.2.2 

Group H-3 and H-4 415.7 

Group H-5 415.8.2.2, 415.8.2.5, 

415.8.5.2, 415.8.6.3 

Group 1-3 408.5,408.7 

Hazardous materials 414.2 

High-rise 403.2.1.2, 403.3, 403.4.7.1 

Hydrogen cutoff rooms 421 .4 

Organic coating 418.4, 418.5, 418.6 

Stages and platforms 410.5.1, 410.5.2 

FIRE COMMAND CENTER 403.4.5, 911 

FIRE DAMPERS 716.2 through 716.5 

FIRE DEPARTMENT (see EMERGENCY 

RESPONDERS) 
FIRE DETECTION SYSTEM (see FIRE ALARM 

AND SMOKE DETECTION SYSTEMS) 
FIRE DISTRICT Appendix D 

FIRE DOOR (see OPENING 

PROTECTIVES) 715,1022.3,1022.4 

FIRE ESCAPE 412.7.3,3406 

FIRE EXTINGUISHERS, PORTABLE 906, 3309 



FIRE EXTINGUISHING SYSTEMS 

FIRE PARTITION 
Continuity 



416.5, 

417.4,903,904 

110.3.6, 709 

709.4 



2009 INTERNATIONAL BUILDING CODE® 



653 



INDEX 



Table 602, 709.5 

603.1 (21), 603.1 (22), 

603.1 (25), 703, 709.3 

715.5 

2508.4 

709.8, 714 

703.6 

709.2 

709.6, 713.3, 715, 716.5.4 

709.7, 709.9, 713, 716 



Exterior walls 
Fire-resistance rating 

Glazing, rated 

Joint treatment gypsum 

Joints 

Marking 

Materials 

Opening protection 

Penetrations 

Special provisions 

Covered mall 

Group 1-3 

Group 1-1, R-1, R-2, R-3 

FIRE PREVENTION 

FIRE PROTECTION 

Explosion control 



Fire extinguishers, portable 
Glazing, rated 
Smoke and heat vents 
Smoke control systems 
Sprinkler systems, automatic 

FIRE PROTECTION SYSTEMS 

FIRE PUMPS 

FIRE RESISTANCE 

Calculated 721 

Conditions of restraint. 703.2.3 

Ducts and air transfer openings 716 
Exterior walls Table 602,705.5,709.5 
Fire district 0102.2.5 

High-rise 403.2 

Joint systems 714 

Prescriptive 720 
Ratings Chapter 6,703,705.5,707.3.9 

Roof assemblies 1505 

Structural members 704 

Tests 703 

Thermal and sound insulating materials 719.1 

FIRE RESISTANCE, CALCULATED 721 

Clay brick and tile masonry 721.4 

Concrete assemblies 721.2 

Concrete masonry 721.3 

Steel assemblies 721.5 

Wood assemblies 721.6 



402.7.2 
408.7 
420.2 

101.4.5 

414.5.1, 415.6.1.4, 
415.8.5.4, 421.7 
906 
715.2 
910 
909 
903 

Chapter 9 
Table 508.2.5,913,914.2 



RE-RETARDANT-TREATED WOOD 


2302.1, 




2303.2 


Awnings 


3105.3 


Balconies 


1406.3 


Canopies 


3105.3 


Concealed spaces 


717.5 


Fastening 


2304.9.5 


Fire wall vertical continuity 


706.6 


Partitions 


603.1 


Platforms 


410.4 


Projections 


705.2.3 


Roof construction Table 601 , 705.1 1 , 


706.6, 1505 


Shakes and shingles 


1505.6 



Type I and II construction 

Type III construction 

Type IV construction 

Veneer 
FIRE SEPARATION DISTANCE 

Exterior walls 
FIRE SERVICE 

ACCESS ELEVATORS 
FIRE SHUTTER (see OPENING 

PROTECTIVES) 

FIRE WALLS 
Aircraft. 

Combustible framing 
Continuity 
Exterior walls 
Fire-resistance rating 
Glazing, rated 
Inspection 
Joints 
Marking 
Materials 
Opening protection 

Penetration 
Special provisions 
Aircraft hangars 
Covered malls 
Group H-5 

Private garages and carports 
Structural stability 
FIRE WINDOWS (see OPENING PROTECTIVES) 
FIREBLOCKING 717.2 

Chimneys 717.2.5, 2113.20 

Fireplaces 2111.12 

Wood construction 717.2.1,717.2.7,1406.2.4 

Wood stairs 717.2.4 

FIREPLACES, FACTORy-BUiLT 2111.14.1 

FIREPLACES, MASONRY 2102.1 

Combustibles 2111.11 

General provisions 2111 

Hearth extension 21 1 1 .9, 2111.10 

Steel units 2111.5.1 

FIREWORKS 307.2,307.3,307.5 

FLAMESPREAD 802, 803.1.1, Table 803.9 

FLAMMABLE FINISHES 307.1,416 

FLAMMABLE LIQUIDS 307.4,307.5,406, 

412,414,415 
FLAMMABLE SOLIDS 307.5, 415 

FLASHING 

Roof 1503.2, 1503.6, 1507.2.9, 

1507.3.9,1507.5.7,1507.7.7, 

1507.8.8,1507.9.9,1510.6 

Wall, veneer 1405.4, 1405.12.7 

FLOOD-RESISTANT CONSTRUCTION 

Accessibility 1107.7.5 

Administration G1 01 through G1 05 



603.1 (10), 603.1 (25) 

602.3 

602.4 

1405.5 

Table 602, 702 

1406.2.1.1 

403.6.1, 3007 

715.4, 715.4.9, 
715.4.10, 715.5 

706 

412.6.2 

706.7 

706.5, 706.6 

Table 602, 706.5.1 

703, 706.4 

715.5 

110.3.6 

706.10, 714 

703.6 

706.3 

706.8, 706.11, 

713.3, 715, 716.5.1 

706.9, 713.3, 713.4 

412.4.6.2 
402.7.3 

415.8.2.6 
406.1 .2 
706.2 



654 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Elevation certificate 
Existing 

Flood elevation 
Flood loads 



3405 



Flood resistance 

Flood resistant construction 

Grading and fill 

Historic buildings 

Interior finishes 

Manufacturered homes 

Recreational vehicles 

Site improvements 

Site plan 

Subdivisions 

Tanks 

Temporary 

Utility 

Ventilation, under floor 



110.3.3 
3403.2, 3404.2, 
5, 3409.2, 3412.2.4.1 
107.2.5.1, 1612 
1603.1, 1603.1.7, 
1612,3001.2,3102.7 
1403.5, 1403.6 
Appendix G 
1804.4, 1805.1.2.1 
G105.3 
801.1.3 
G501 
G601 
G401 
107.2.5 
G301 
G701 
G901 
G1001 
1203.3.2 



FLOOR/CEILING (see FLOOR CONSTRUCTION) 

FLOOR CONSTRUCTION (see FLOOR 
CONSTRUCTION, WOOD) 

Draftstopping 717.3 

Finishes 804, 805, 1003.4, 1210.1 

Fire resistance Table 601, 712 

Loads (see FLOOR LOADS) 

Materials Chapter 6 

Penetration of fire-resistant assemblies .. 712, 713.4, 

716.2, 716.6 

FLOOR CONSTRUCTION, WOOD 
Beams and girders 2304.1 1 .2.1 , 2308.7 

Bridging/blocking 2308.8.5, 2308.10.6 

Diaphragms 2305.1 

Fastening schedule 2304.9.1 

Framing Table 602.4, 602.4.2, 602.4.4, 2304.4 

Joists 2308.8 

Sheathing 2304.7 

FLOOR LEVEL 1003.5,1008.1.5 

FLOOR LOADS 
Construction documents 107.2 

Live 1603.1.1, 1607 

Posting 106.1 

FLOOR OPENING PROTECTION (see VERTICAL 
OPENING PROTECTION) 

FOAM PLASTICS 
Attics 719.1, 2603.4.1.6 

Cold storage 2603.3, 2603.4.1.2, 2603.5 

Concealed 603 

Covered mall and open mall buildings 402.16.5 

Crawl space 2603.4.1.6 

Doors 2603.4.1 .7 through 2603.4.1 .9 

Exterior walls of multistory buildings 2603.5 

Interior finish 801.2.2, 2603.9, 2604 

Label/identification 2603.2 

Metal composite materials (MCM) 1407.1.1, 

1407.13 
Roofing 2603.4.1.5 



Siding backer board 
Stages and platform scenery 
Surface burning characteristics 
Thermal barrier requirements 
Trim 

Type I and II construction 
Walk-in coolers 
FOLDING AND TELESCOPIC SEATING 



Accessibility 

Egress 

Live load 

Occupant load 
FOOD COURT 

Occupant load 
FOOTBOARDS 
FORMWORK, CONCRETE 
FOUNDATION (see FOUNDATION, DEEP 

and FOUNDATION, SHALLOW) Chapter 18 

Basement 1610, 1805.1.1, 1806.3, 1807 

Concrete 1808.8, 1809.8, 1810.3.2.1 



2603.4.1.10 

410.3.6 

2603.3 

2603.5.2 

806.3, 2604.2 

603.1 (1), 603.1 (2) 

2603.4.1.3 

1028.1.1, 

3401.1 

1108.2 

1028.1.1 

Table 1607.1 

1004.7 

402.2 

402.4.1.4 

1028.14.2 

1906 



Dampproofing 

Encroachment, public right-of-way 
Formwork 1906 ; 

Geotechnical investigation 

(see SOILS AND FOUNDATIONS) 
Inspection 

Load-bearing value 1806, 

Masonry 

Pedestrian protection 
Pier (see FOUNDATION, SHALLOW) 
Pile (see FOUNDATION, DEEP) 
Plates or sills 
Protection from adjacent 

construction 
Rodentproofing 
Special inspections 



1805.2 
3202.1 
3304.1 



1803 

110.3.1 

1808, 1810 

1808.9 

3306.9 



2308.6 



3303.5, 3307.1 

Appendix F 

1704.4, 1704.8, 

1704.9, 1704.10, 1704.11 

1809.11, 1810.3.2.2, 1018.3.2.3 

1809.12, 1810.3.2.4 

1805.3 

1802.1, 1810 

1802.1 

1810.10.1.2 

1803.5.5 

1810.3.12 

1802.1, 1810.3.1.5, 

Table 1810.3.2.6, 1810.3.3.1.9, 

1810.3.5.3.3, 1810.4.11, 1810.4.12 

1802.1, Table 1808.8.1, 

Table 1810.3.2.6,1810.3.5.2.3, 

1810.3.10,1810.4.10 

Table 1808.8.1, 1809.12, 

1810,1810.3.1.4 

FOUNDATION, SHALLOW 1802.1, 1809 

Piers and curtain wall 1809.10 

Slab-on-grade 1808.6.2 

Strip footing 1808.8, 1809 



Steel 
Timber 

Waterproofing 
FOUNDATION, DEEP 
Drilled shaft 
Existing 

Geotechnical investigation 
Grade beams 
Helical pile 



Micropile 



Piles 



2009 INTERNATIONAL BUILDING CODE® 



655 



INDEX 



FOYERS 






Guards 


1013.1.1, 2406.4, 2407 


Assembly occupancy 




1028.4, 1028.9.5 


Handrail 


1009.12, 2407 


Corridors 




1018.6 


Identification 


2403.1, 2406.3 


Covered mall and open 


mall 


402.1 


Impact loads .. 2406.1 


, 2407.1.4.2, 2408.2.1, 2408.3 


FRAME INSPECTION 




110.3.4 


Impact resistant 


1609.1.2 


FRATERNITIES 




310 


Jalousies 
Label/identification 


2403.5 
715.4.6.1, 715.4.7.3, 715.5.9 


FROST PROTECTION 




1809.5 


Loads 


2404 


FURNACE ROOMS 




1015.3 


Louvered windows 
Opening protection 


2403.5 
715.2 




G 




Replacement 


2401.2, 3407 






Safety 


715.4.7.4,2406 


GALLERIES 






Security 


408.7 


Means of egress 


410.3.2, 1015.6.1, 1028.5 


Skylights 


2405 


Sprinklers 




410.6 


Sloped 


2404.2, 2405 


GARAGE, AUTOMOBILE PARKING (see PARKING 


Supports 


2403.2 


GARAGES) 






Swimming pools 
Testing 


2406.4 
1715.5, 2406.1.1, 2408.2.1 


GARAGE, REPAIR 




406.6 


Veneer 


1405.12 


Floor surface 




406.6.4 


Vertical 


2404.1 


Gas detection system 




406.6.6, 908.5 


Wired 


715.5.4 


Sprinklers 




903.2.9.1 






Ventilation 




406.6.3 


GRADE, LUMBER (see 


LUMBER) 2302.1 


GARAGES, TRUCK AND BUS 




GRADE PLANE 


502 


Live load 




1607.6,1607.7.3 


GRAIN ELEVATORS 


415.6.1.5 


Sprinklers 




903.2.10.1 


GRANDSTANDS 


303.1, 1028.1.1, 3401.1 


GARAGES AND CARPORTS, 


PRIVATE 406.1 


Accessibility 


1108.2 


Area limitations 




406.1.2 


Exit sign exemptions 


1011 .1 


Separation 




406.1.4 


Live load 


Table 1607.1 


GAS 




101.4.1, 105.2, 112 


Occupant load 


1004.7 


Accessibility 




1109.13, 3411.8.13 


GREENHOUSES 


312.1 


Gas detection system 




406.6.6, 415.8.7, 


Area 


503,505,506,507,508 






421.6,908 


Deflections 


Table 1604.3 


Hydrogen cutoff room 




421 .6 


Live load 


1607.11.2.1 


Motor fuel dispensing 




406.5 


Membrane structure 


3102.1 


GATES 




1008.2 


Plastic 


2606.11 


Vehicular 




3110 


Sloped glazing 


2405 


GIFT SHOPS 




407.2.4 


Wind load 


1609.1.2 


GIRDERS 






GRIDIRON 


410.2 


Fire resistance 




Table 601 


Means of egress 


410.3.2, 1015.6.1 


Materials 




Chapter 6 


Sprinklers 


410.6 


Wood construction 




2304.11.2.1, 2308.7 


GRINDING ROOMS 


415.6.1.2 



GLASS (see GLAZING) 

GLASS BLOCK (see GLASS UNIT MASONRY) 

GLASS UNIT MASONRY 2102.1, 2110 

Atrium enclosure 404.5 

Design method 2101.2.5 

Fire resistance 2110.1.1 

Hazardous locations 2406.1.3 

Material requirements 2103.6 

GLAZING 

Athletic facilities 2408 

Doors 705.8, 710.5, 711.5, 

715.4.3.2, 1405.13, 1715.5 

Elevator hoistway and car 2409 

Fire doors 715.4.4, 715.4.7 

Fire resistant walls 715.4.3.2 

Fire windows 703.5,715.5 

Group 1-3 408.7 



GROSS LEASABLE AREA 
(see COVERED MALL AND 
OPEN MALL BUILDINGS) 402.2,402.4.1 .1 

GROUT 713.3.1,713.4.1.1,2103.12 



GUARDS 






1013 


Assembly seating 


1028.1. 1 : 


, 1028.14 


Equipment platform 






505.5.3 


Exceptions 






1013.1 


Glazing 1013.1.1, 


1303.1, 


2406.4, 2407 


Height. 






1013.2 


Loads 






1607.7 


Mechanical equipment. 






1013.5 


Opening limitations 






1013.3 


Parking garage 






406.2.4 


Ramps 






1010.10 


Residential 






1013.2 


Roof access 






1013.6 



656 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Screen porches 




1013.4 


Stairs 




1013.1 


Vehicle barrier 




1607.7.3 


GUTTERS 




1503.4.3 


GYMNASIUMS 




303.1 


Group E 




303.1 (4) 


Live load 




Table 1607.1 


Occupant load 




1004.1 


GYPSUM 




Chapter 25 


Aggregate, exposed 




2513 


Board 




Chapter 25 


Ceiling diaphragms 




2508.5 


Concrete, reinforced 




1914 


Construction 




2508 


Draftstopping 




717.3.1 


Exterior soffit 




Table 2506.2 


Fastening 


Table 2306.7,2508.1 


Fire resistance 


718, 


721.2.1.4, 721.6.2 


Fire-resistantjoint treatment 




2508.4 


Inspection 




2503 


Lath 




2507, 2510 


Lathing and furring for cement plaster 718, 2510 


Lathing and plastering 




2507 


Materials 




2506 


Plaster, exterior 




251 2 


Plaster, interior 




2511 


Shear wall construction 


2306.7,2308.9.3,2505 


Sheathing 




Table 2304.6 


Showers and water closets 




2509 


Stucco 




2510 


Veneer base 




2507.2 


Veneer plaster 




2507.2 


Vertical and horizontal assemblies 


2504 


Wallboard 




Table 2506.2 


Water-resistant backing boarc 


I 


2506.2, 2509.2 



H 



HANDRAILS 


1012 


Alternating tread devices 1009.10.1 


Assembly aisles 


1028.13 


Construction 


1012.4, 1012.5, 1012.6 


Extensions 


1012.6 


Glazing 


2407 


Graspability 


1012.3 


Guards 


1013.2 


Height. 


1012.2 


Loads 


1607.7 


Location 


1012.1,1012.7,1012.8,1012.9 


Ramps 


1010.8 


Stairs 


1009.12 


HARDBOARD 


1404.3.2,2302.1,2303.1.6 



HARDWARE (see DOORS and LOCKS AND 
LATCHES) 

HARDWOOD 

Fastening 2304.9 

Quality 2303.1.8.1,2303.3 

Veneer 1404.3.2 



HAZARDOUS MATERIALS 307,414,415 

Control areas 414.2 

Explosion control 414.5.1, Table 414.5.1, 

415.6.1.4, 415.8.5.4 

Special provisions 415.4, 415.5 

Sprinklers Table 41 4.2.5(1 ), Table 41 4.2.5(2), 

415.5.2, 415.6.2.4, 415.8.11, 903.2.7.1 

Ventilation 414.3, 414.5.4, 415.6.1.4, 

415.6.2.8, 415.8.2.6, 415.8.2.8.2, 

415.8.4.3,415.8.5.7,415.8.6.3,415.8.7, 

415.8.9.3, 415.8.10, 1203.5 

Weather protection 414.6.1 

HEAD JOINT, MASONRY 2102.1 

HEADROOM 406.2.2,505.1,1003.2, 

1003.3, 1008.1 .1, 1008.1.1.1 , 
1009.2, 1010.5.2, 1208.2 

HEALTH CARE (see INSTITUTIONAL 1-1 
AND INSTITUTIONAL 1-2) 

Ambulatory health care facilities 422 

Clinics, outpatient 304 

Hospitals 308.3 

HEALTH-HAZARD MATERIALS 307.2, 

Table 414.2.5(1), 415.2, 415.4, 

Table 415.8.2.1.1, 415.8.6.2 

HEAT VENTS 910 

HEATING (see MECHANICAL) 101.4.2 

Aircraft hangars 412.4.4 

Fire pump rooms 913.3 

Fireplace 2111 

Masonry heaters 21 1 2 

Parking garages 406.2.8 

Repair garages 406.6.5 

HEIGHT, BUILDING 503,504,505,506,508,509 

Limitations 503 

Mixed construction types 509 

Modifications 504 

Roof structures 504.3 

HIGH PILED COMBUSTIBLE STORAGE 413, 

907.2.15,910.2.2 

HIGH-HAZARD OCCUPANCY (GROUP H) 307, 

414,415 
Accessory 508.2 

Area 503,505,506,507,508 

Classification 307 

Combustible liquids 307.4, 307.5, 

414.2.5, 414.5.4, 415.6.2 
Control areas 414.2 

Conveyors 415.6.1.3 

Corrosives 307.6, Table 414.2.5(1), 

414.3,415.7.3, Table 415.8.2.1.1 
Cryogenic Table 307.1 , 

Table 414.5.1, Table 415.8.2.1.1 

Dispensing 414.1,414.5,414.6,414.7.2,415.3 

Dry cleaning (see DRY CLEANING PLANTS) 
Emergency alarm systems 414.7,415.8.3, 

415.8.4.6, 415.8.5.8, 908.1, 908.2 
Exceptions 307.1 

Exempt 307.1 



2009 INTERNATIONAL BUILDING CODE® 



657 



INDEX 



Explosives 

Factory industrial F-1 moderate 

hazard occupancy 
Factory industrial F-2 low 

hazard occupancy 
Fire alarm and detection 



307.3, Table 414.5.1, 
Table 415.3.1 

306.2 



Fire district 
Flammable liquids 
Flammable solids 
Grinding rooms 
Group H-1 

Group H-2 

Group H-3 



306.3 

414.7.2, 415.8.8, 

901.6.3,907.2.5 

0102.2.2 

307.4,307.5,415.6.2 

307.5,415.1 

415.6.1.2 

307.3,403.1,415.3.1, 

415.3.2, 415.4 

307.4, 403.1, 412.6.1, 

415.3,415.5,415.6 

307.5, 403.1, 415.3, 

415.5,415.6.2,415.7 

Group H-4 307.6,415.4,415.7 

Group H-5 307.7,415.8 

Health-hazard materials 307.2, Table 414.2.5(1), 

415.2, 415.4, Table 415.8.2.1.1, 

415.8.6.2,415.8.7.2 

Height 415.4,415.5,415.6.1.1, 

415.6.1.6,415.6.2.1.1,503, 

504, 505, 506, 508 

Interior finishes 416.2.1, 416.3.1, 

Table 803.9, 804 
Irritants Table 414.2.5(1), 

Table 415.8.2.1.1 
Liquid, highly toxic and toxic 307.6, 

Table 414.2.5(1), 
415.7.3,415.7.4, 
Table 415.8.2.1.1, 908.3 
Live load Table 1607.1 

Location on property 414.6.1.2, 415.3 

Multiple hazards 307.8 

Organic peroxides Table 414.5.1 , 

Table 415.3.2, 415.4.1, 

415.5.1, Table 415.8.2.1.1,418 

Oxidizers, liquid and solid Table 414.2.5(1), 

Table 414.5.1,415.5.1, 

Table 415.3.2, 

Table 415.8.2.1.1 

Pyrophoric materials 307.4, Table 307.1(1), 

Table 414.5.1,415.4.1, 
Table 415.3.2, 415.5.1, 
Table 415.8.2.1.1 
Sensitizers Table 415.8.2.1.1 

Separation from other 
occupancies 415.3.1, 508.2.4, 

Table 508.2.5, 508.3.3, 508.4 
Solids, highly toxic 
and toxic 307.6, Table 414.2.5(1), 

415.7.3,415.7.4, 

Table 415.8.2.1.1, 908.3 

Smoke and heat vents 910.2 

Sprinklers 415.5.2, 415.6.2.4, 

415.8.6.3, 415.8.9, 415.8.10.1, 

415.8.11, 705.8.1, 903.2.5 



Standby power systems 414.5.4, 2702.2.8, 

2702.2.10 through 2702.2.13 

Storage 413,414.1,414.2.5, 

414.5,414.6,414.7.1,415.2, 

415.3, Table 415.3.2, 415.4.1, 

415.5,415.6.1,415.6.2 

Tanks 415.6.2 

Travel distance 1014.3, 1016.1, 1021.2 

Unlimited area 507.8 

Unstable materials 307.3, Table 414.2.5(1), 

Table 414.5.1, Table 415.3.2, 

415.4.1,415.5.1, 

Table 415.8.2.1.1 

Water-reactive materials Table 414.5.1, 

Table 415.3.2,415.5, 

415.5.1,415.5.2,415.8, 

Table 415.8.2.1.1 



HIGH-RISE BUILDINGS 
Application 
Construction 
Elevators 

Emergency power 
Emergency systems 
Fire alarm 



403 

403.1 

403.2 

403.6,1007.2.1,3007,3008 

403.4.8,2702.2.15 

403.4 

403.4.2 



Fire alarm and detection 
Fire command station 
Fire department communication 
Fire service elevators 
Occupant evacuation elevators 
Smoke removal 
Smokeproof enclosure 



403.4.1, 907.2.13 

403.4.5 

403.4.3, 403.4.4 

403.6.1, 3007 

403.6.2, 3008 
403.4.6 

403.5.4, 1022.9 



Sprayed fire-resistant materials (SFRM) 403.2.4 

Sprinklers 403.3,903.2.1 1 .3 

Stairways 403.5 

Standby power 403.4.7, 2702.2.5, 2702.2.15 

Structural integrity 403.2.3, 1614 

Super high-rise (over 420 feet) 403.2.1 , 403.2.3, 

403.2.4, 403.3.1, 403.5.2 
Voice alarm 403.4.3, 907.2.13 

Zones 907.6.3.2 



HISTORIC BUILDINGS 

Accessible 

Flood provisions 
HORIZONTAL ASSEMBLY 



3409 

3411 .9 

G105.3 

712 



Continuity 508.2.5.1, 712.4, 708.11, 708.12 

Fire-resistance rating 603.1 (21), 603.1 (22), 

603.1 (25), 703, 707. 3. 9, 712. 3 

Glazing, rated 715.5 

Group 1-1 420.3 

Group R 420.3 

Incidental accessory occupancies 508.2.5.1 

Insulation 719, 807, 808 

Joints 714, 2508.4 

Opening protection 712.8, 713.4, 715, 716.6 

Shaft enclosure 708.1 
Special provisions 

Aircraft hangars 412.4.4 

Atrium 404.3, 404.6 

Covered mall 402.4.6, 402.7.1 

Fire pumps 913.2.1 



658 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



416.2 

415.6.1.2, 415.6.2.2 

415.7 

415.8.2.2, 415.8.5.2 

407.4.3 

420.3 

414.2 

403.2.1,403.3,403.4.7.1 

421.4 

418.4,418.5,418.6 

410.5.1, 410.5.2 

1025 



Flammable finishes 
Group H-2 
Group H-3 and H-4 
Group H-5 
Group 1-2 

Groups 1-1, R-1, R-2, R-3 
Hazardous materials 
High-rise 
Hydrogen cutoff 
Organic coating 
Stages and platforms 
HORIZONTAL EXIT 
Accessible means of egress 1007.2, 1007.2.1, 

1007.3,1007.4,1007.6,1007.6.2 
Doors 1025.3 

Exit discharge 1027.1 

Fire resistance 1025.2 

Institutional 1-2 occupancy 407.4, 1025.1 

Institutional 1-3 occupancy 408.2, 1025.1 

Refuge area (see REFUGE AREAS) 
HORIZONTAL FIRE SEPARATION 
(see HORIZONTAL ASSEMBLY) 
HOSE CONNECTIONS 

(see STANDPIPES, REQUIRED) 
HOSPITAL 

(see INSTITUTIONAL GROUP 1-2) 308.3, 407 

HURRICANE-PRONE REGIONS 

(see WIND LOADS) 1609.2 

HURRICANE SHELTER (see STORM SHELTER) 
HURRICANE SHUTTERS 1609.1.2 

HYDROGEN CUTOFF ROOMS 421, Table 508.2.5 

I 

IDENTIFICATION, REQUIREMENTS FOR 

Fire barriers 703.6 

Fire partitions 703.6 

Fire wall 703.6 

Glazing 2403.1,2406.3 

Inspection certificate 1702.1 

Labeling 1703.5 

Preservative-treated wood 2303.1.8.1 

Smoke barrier 703.6 

Smoke partition 703.6 

Steel 2203.1 

IMPACT LOAD 1602.1,1603.1.1,1607.8 

INCIDENTAL USE AREAS 

(see ACCESSORY OCCUPANCIES) 

INCINERATOR ROOMS 1015.3 

INDUSTRIAL (see FACTORY OCCUPANCY) 

INSPECTIONS 110, 1704, 1705, 1706, 1707 

Alternative methods and materials 1704.15 

Approval required 110.6 

Atrium buildings 909.3 

Concrete construction 110.3.1, 110.3.2, 

110.3.9, 1704.4 
Concrete slab 110.3.2 

Continuous 1702.1 



EIFS 

Energy efficiency 

Fabricators 

Fees 

Final 

Fire-resistant materials 

Fire-resistant penetrations 

Footing or foundation 



110.3.9, 1704.14 

110.3.7 

1704.2 

109 

110.3.10 

110.3.9, 1704.12, 1704.13 

110.3.6 

110.3.1, 110.3.9, 

1704.4, 1704.5, 1704.8, 

1704.9, 1704.10, 1704.11 

110.3.4 

110.3.5,2503 

104.8 

110.3.9, 1704.5, 1704.11 

1702.1 

110.2 

110.3 

104.6 

1707 

104.16, 1704.16 

110.3.9, 1704.7 



Frame 

Lath or gypsum board 

Liability 

Masonry 

Periodic 

Preliminary 

Required 

Right of entry 

Seismic 

Smoke control. 

Soils 

Special 

(see STRUCTURAL TESTS AND 

SPECIAL INSPECTIONS) 1 10.3.9, 

1704,1706,1707 
Sprayed fire-resistant materials 1704.12 

Sprinklers, automatic 904.4 

Steel. 110.3.4, 110.3.9, 1704.3 

Third party 110.4 

Welding 110.3.9, 1704.3, 2204.1 

Wind 110.3.9, 1706 

Wood, structural. 110.3.9, 1704.6 

INSTITUTIONAL 1-1 [see INSTITUTIONAL 
OCCUPANCY (GROUP I)] 308.2 

Accessibility 1106.7.2, 1107.5.1 

Combustible decorations 806.1 

Emergency escape and rescue 1029 

Fire alarm and detection 907.2.6.1, 

907.2.11.2,907.5.2.3.2 
Special occupancy separation 420, 508.2.4, 

Table 508.2.5, 508.3.3 
Sprinklers 903.2.6, 903.3.2 

Travel distance 1014.3, 1016.1, 1021.2 

Visible alarms 907.5.2.3.3 

INSTITUTIONAL 1-2 [see INSTITUTIONAL 
OCCUPANCY (GROUP I)] 308.3, 407 

Accessibility 1106.4, 1106.7.2, 

1107.5.2,1107.5.3, 
1107.5.4, E106.4.6 
Combustible decorations 806.1 

Corridors 407.2,407.3, 1 01 8.2 

Doors 1008.1.9.6 

Exterior exit stair 1026.2 

Fire alarm and detection 407.6,407.7,907.2.6.2 

Hardware 1008.1.9.6 

Hyperbaric facilities 407.9 

Occupancy category Table 1604.5 

Smoke barriers 407.4 

Smoke compartment 407.2.1 ,407.2.3, 

407.4,407.5 



2009 INTERNATIONAL BUILDING CODE® 



659 



INDEX 



Smoke partitions 407.3 

Special occupancy separation Table 508.2.5 

Sprinklers 407.5,903.2.6,903.3.2 

Suites 1014.2.2 through 1014.2.7 

Travel distance 407.4,1014.2.3.3, 

1014.2.4.3, 1014.2.4.4, 

1014.2.6, 1014.3, 1016.1, 1021.2 

Yards 407.8 

INSTITUTIONAL 1-3 [see INSTITUTIONAL 

OCCUPANCY (GROUP I)] 308.4,408 

Accessibility 1103.2.14, 1107.5.5, 

1108.4.2,3411.8.7, E104.3, 
E104.4, E106.4.8 



Combustible decorations 

Exit sign exemption 

Fire alarm and detection 

Hardware 

Means of egress 

Occupancy category 

Security glazing 

Separation 

Smoke barrier 

Smoke compartment 

Special occupancy separation 

Sprinklers 

Travel distance 



806.1 
1011 .1 
408.10,907.2.6.3 
408.4,1008.1.9.9 
408.2, 408.3, 408.4 
Table 1604.5 
408.7 
408.5, 408.8 
408.6 
408.4.1,408.6,408.9 
Table 508.2.5 
903.2.6 
408.6.1, 408.8.1 , 
1014.3,1016.1,1021.2 

INSTITUTIONAL 1-4 [see INSTITUTIONAL 
OCCUPANCY (GROUP I)] 308.3.1 ,308.5 

Accessibility 1103.2.12 

Corridor rating 1018.1 

Fire alarm 907.2.6 

Sprinklers 903.2.6 

Travel distance 1014.3, 1016.1, 1021.2 

INSTITUTIONAL OCCUPANCY (GROUP I) 308 

Accessory 508.2 

Adult care 308.5.1 

Area 503,505,506,507,508 

Child care 308.3.1, 308.5.2, 310.1 

Group 1-1 308.2 

Group 1-2 308.3, 407 

Group 1-3 308.4, 408 

Group 1-4 day care facilities 308.3.1, 308.5, 310.1 
Height 503,504,505,506,508 

Interior finishes Table 803.9,804 

Live load Table 1607.1 

Plumbing fixtures 2902 

Special occupancy separation 420, 508.2.4, 

Table 508.2.5, 508.3.3 

INSULATION 
Concealed 719.2 

Duct insulation 719.1 

Exposed 719.3 

Fiberboard 719.1, 1508.1.1, 

2303.1.5.2, 2303.1.5.3 
Foam plastic (see FOAM PLASTICS) 719.1 

Loose fill 719.4, 719.6 

Pipe insulation 719.1,719.7 

Reflective plastic core 2613 

Roof 719.5, 1508 



Sound 
Thermal. 

INTERIOR ENVIRONMENT 

Lighting 

Rodentproofing 

Sound transmission 

Space dimensions 

Temperature control 

Ventilation 409.3, 

Yards or courts 
INTERIOR FINISHES 

Acoustical ceiling systems 

Application 

Atriums 

Decorative materials 

Floor finish 

Foam plastic insulation 

Foam plastic trim 

Insulation 

Light-transmitting plastics 

Signs 

Trim 

Wall and ceiling finishes 

Wet location 
INTERPRETATION, CODE 



719,807,1207 
719,807,1508 

1205 
Appendix F 
1207 
1208 
1204 
414.3, 415.8.2.6, 1203.4 

1206.2, 1206.3 
Chapter 8 

807,808 

803.10, 804.4 

404.8 

801.1.2, 806 

804, 805 

2603.3, 2603.4 
806.3, 2604.2 

807 

2606 

402.16, 2611 

806.5, 806.6 

803 

1210, 2903 

104.1 



JAILS (see INSTITUTIONAL 1-3) 308.3,408 

JOINT 

Concrete construction joints 1 906.4 

Gypsum board 2508.4 

Lumber sheathing 2308.10.8.1 

Shotcrete 1913.7 

Structural plain concrete 1909.3 

Waterproofing 1805.3.3 

JOINTS, FIRE-RESISTANT SYSTEMS 714 



K 



KIOSKS 

KITCHENS 
Accessibility 
Dimensions 
Means of egress 
Occupant load 
Rooms openings 



402.11 

Table 508.4(d) 

1109.4 

1208 

1014.2 

Table 1004.1.1 
1210.5 



LABORATORIES 
Classification of 304.1 

Hazardous materials 414, 415 

Incidental accessory occupancies Table 508.2.5 

LADDERS 
Boiler, incinerator and furnace rooms 1015.3 

Construction 1009.4.2, 1012.2, 

1012.6, 1013.2, 1013.3 
Emergency escape window wells 1 029.5.2 



660 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Group 1-3 


408.3.5, 1009.11 


Impact 


1602.1,1607.8 


Heliport 


412.7.3, 1021.1.3 


Live 


419.6,1603.1.1,1607 


Refrigeration machinery room 


1015.4 


Rain 


1611 


Stage 


410.5.3, 1015.6.1 


Seismic 


1603.1.5, 1613 


LAMINATED TIMBER, 




Snow 


1603.1.3, 1608 


STRUCTURAL GLUED 


602.4, 2303.1, 


Soil lateral 


1610 




2304.11.3, 2306.1, 


Wind 


1603.1.4, 1609 


2308.8.2.1,2308.10.7 


LOBBIES 




LANDINGS 




Assembly occupancy 


1028.4 


Doors 


1008.1.6 


Elevator 


708.14.1, 1007.2.1, 


Ramp 
Stair 


1010.6 




1007.4, 3007.4, 3008.11 


1009.5 


Exit discharge 


1027.1 


LATH, METAL OR WIRE 


Table 2507.2 


LOCKS AND LATCHES 


1008.1.9,1008.1.10 


LAUNDRIES 304.1, 


306.2, Table 508.2.5 


Access-controlled egress 
Delayed egress locks 


1008.1.4.4 
1008.1.9.7 


LAUNDRY CHUTE 


708.13, 903.2.11.2 


Electromagnetically locked 


1008.1.9.8 


LEGAL 




Group 1-2 


1008.1.9.6 


Federal and state authority 


102.2 


Group 1-3 


408.4,1008.1.9.9 


Liability 


104.8 


Group R-4 


1008.1.9.5.1 


Notice of violation 


114.2, 116.3 


High-rise 


403.5.3 


Registered design professional 


107.1, 107.3.4 


LUMBER 




Right of entry 


104.6 


General provisions 


Chapter 23 


Unsafe buildings or systems 


116 


Quality standards 


2303 


Violation penalties 


114.4 






LIBRARIES 




M 




Classification, other than school 


303.1 




Classification, school 


305.1 


MAINTENANCE 




Live load 


Table 1607.1 


Accessibility 


3411.2 


LIGHT, REQUIRED 


1205 


Means of egress 


3310.2 


Artificial 


1205.3 


MALL (see COVERED MALL AND OPEN MALL 


Emergency (see EMERGENCY LIGHTING) 


BUILDINGS) 




Natural 


1205.2 


MANUAL FIRE ALARM BOX 


907.4.2 


Stairways 
Yards and courts 


1205.4 
1206 


MANUFACTURED HOMES 
Flood resistant 


G501 


LIGHTS, PLASTIC CEILING DIFFUSERS 2606.7 


MARqUEES 


3106, H113 


LINTEL 




Drainage, water 


3201.4 


Adobe 


2109.3.4.7 


Live load 


Table 1607.1,1607.11 


Fire resistance 


704.11 


MASONRY 




Masonry 


2104.1.5 


Adhered veneer 


1405.10 


Masonry, wood support 


2304.12 


Adobe 


2109.3 


LIQUEFIED PETROLEUM GAS 


415.6.3 


Anchorage 


1604.8.2 


LIVE LOADS 


1602.1, 1607 


Anchored veneer 


1405.6 


Construction documents 


107.2, 1603.1.1 


Ashlar stone 


2102.1 


Posting of 


106.1 


Autoclaved aerated concrete 


(AAC) .. 2102.1, 2103.3 


LIVE/WORK UNITS 


310.1,419 


Calculated fire resistance 


721.4 


Separation 


508.1 


Chimneys 


2113 


LOAD AND RESISTANCE 
FACTOR DESIGN (LRFD) 


1602.1 


Cold weather construction 
Construction 
Construction documents 


2104.3 

2104, 2109.2.2 

2101.3 


Load combinations 
Wood design 


1605.2 
2301.2, 2307 


Corbelled 

Dampproofing 


21 04.2 

1805.2.2 


LOAD COMBINATIONS 


1605 


Design, methods 2101.2, 2107 through 2109 


Allowable stress design 


1605.3 


Fire resistance, calculated 


721.3.2, 721.3.4 


Load and resistance factor desig 


n 1605.2 


Fireplaces 


2101.3.1, 2111 


Strength design 


1605.2 


Floor anchorage 


1604.8.2 


LOADS 


106, 1602.1 


Foundation walls 


1807.1.5 


Combinations 


1605 


Foundations, adobe 


2109.3.4.3 


Dead 


1602.1, 1606 


Glass unit. 


2101.2.5, 2103.6, 2110 


Flood 


1603.1 .7, 1612 


Grouted 


2102.1 



2009 INTERNATIONAL BUILDING CODE® 



661 



INDEX 



, MASONRY) 2109.2 

2112 
2104.4 
1704.5 
2103.13 
2103 
71 3 
2105 
Appendix F 
1604.8.1 
2102.1 
2106 
1604.3.4 
2103.4, 2109.2 
2304.12 
2103.9 
2105.2.2.2, 2105.3 
2104.1.3 
405.10, 2101.2.6, 2308.11.2 
2102.1 
2102.1 
1604.8.2 
1805.3.2 
2102.1 

104.11 
Chapter 20 
Chapter 19 
Chapter 24 
Chapter 25 
Chapter 21 
703.4 
Chapter 26 
Chapter 22 
1716 
Chapter 23 

Chapter 10 

1007,2702.2.5, 

2702.2.6, 3411.6, 3411.8.10 

Aircraft related 412.3.3, 412.5.2 

Alternating tread device 412.7.3, 505.5, 

1009.10, 1015.3, 1015.4 
Ambulatory care facilities 422.4 

Assembly 1007.1,1028 

Atrium 404.9,707.3.5 

Capacity 1005.1 

Child care facilities (see Day care facilities) 
Ceiling height 1003.2 

Construction drawings 107.2.3 

Covered mall and open mall buildings 402.4, 

402.5,402.13 

Day care facilities 308.5, 310.1, Table 1004.1.1, 

Table 1015.1 (a), Table 1021.2(e) 
Doors 1005.2, 1008, 1015, 1020.2, 2702.2.7 

During construction 3303.3, 3310 

Elevation change 1003.5 

Elevators 403.5.2,403.6.2,1003.7,1007,3008 

Emergency escape and rescue 1029 

Equipment platform 505.5 

Escalators 1003.7 



Headers (see BONDING, 

Heaters 

Hot weather construction 

Inspection, special 

Joint reinforcement 

Materials 

Penetrations 

Quality assurance 

Rodentproofing 

Roof anchorage 

Rubble stone 

Seismic provisions 

Serviceability 

Stone 

Support 

Surface bonding 

Test procedures 

Tie, wall. 

Veneer 1405.6, 1 

Wall, composite 

Wall, hollow 

Wall anchorage 

Waterproofing 

Wythe 

MATERIALS 
Alternates 
Aluminum 
Concrete 
Glass and glazing 
Gypsum 
Masonry 
Noncombustible 
Plastic 
Steel 

Testing (see TESTING) 
Wood 

MEANS OF EGRESS 
Accessible 



Existing buildings 



1007.1,3310,3404.6, 
3406.1,3411.6,3412.5,3412.6.11 
1020 through 1026 



Exit (see EXIT) 
Exit access 

(see EXIT ACCESS) 1 01 4 through 1019 

Exit discharge (see EXIT DISCHARGE) 1027 

Exit enclosures 1022.1 

Exit signs 1011, 2702.2.3, 2702.2.9 

Fire escapes 3406 

Floor surface 804, 1003.4 

Gates 1008.2 

Group 1-2 407.4 

Group 1-3 408.2, 408.3, 408.4, 408.6 

Guards 1013 

Handrails 1012 

Hazardous materials 414.6.1.2, 

415.8.4.4, 415.8.5.5 

Headroom 1003.2, 1003.3 

Helistops 412.7.3, 1021.1.3 

High hazard Group H 415.8.4.4, 415.8.5.5 

High-rise 403.5, 403.6 

Illumination 1006, 2702.2.4, 3412.6.15 

Interior finish 803.9, 804 
Ladders (see LADDERS) 



101 



Live loads 

Live/work units 

Mezzanines 

Moving walk 

Occupant load 

Parking 

Protruding objects 

Ramps 

Scoping 

Seating, fixed 

Special amusement 

Stages 

Stairways 

Temporary structures 

Travel distance 

(see TRAVEL DISTANCE) 
Turnstile 

Underground buildings 
Width 1005.1 

1010.5.1, 



Table 1607.1 

419.3 

505.3,505.4,1004.6,1007.1 

1003.7 

1004.1, 1004.1.1, 1004.2 

406.3.8 

1003.3, 1005.2 

1010, 1026 

3, 105.2.2, 108.2, 1001.1 

1007.1, 1028 

411.7 

410.3.3, 410.5.3, 1015.6 

403.5, 1009, 1022.1, 1026 

3103.4 



1014.3,1016 

1008.3 

405.5.1, 405.7 

, Table 1005.1, 1009.1, 

1018.2, 1028.6, 1028.8 



MECHANICAL (see AIR CONDITIONING, HEATING, 
REFRIGERATION, AND VENTILATION) .... 101 .4.2 
Access 1009.13, 1009.14, 1209.3 

Air transfer openings 705.10, 706.11, 

707. 9, 708. 2(7), 708. 10, 709. 9, 
710.8,711.7,712.7,713.1.1,713.4.1.3,716 
Chimneys (see CHIMNEYS) 

Code Chapter 28 

Disconnected 3303.6 

Ducts 704.8, 705.10, 706.11, 

707.9, 708.2(4), 708.2(15), 

708.10, 709.9, 710.8, 711.7, 

712.7,713.1.1,713.4.1.3,716 

Encroachment, public right-of-way 3202.3.2 

Equipment on roof 1509, 1510.2 

Equipment platforms 505.5 



662 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Factory-built fireplace 

Fireplaces 

Motion picture projection room 

Permit required 

Roof access 

Room separation 

Seismic inspection and testing 



2111.14.1 

2111 

409.3 

105.1, 105.2 

1009.13 

Table 508.2.5 

1707.7, 

1707.8,1708.4 

Smoke control systems 909 

Systems 1 61 3.2, Chapter 28 

MECHANICALLY LAMINATED DECKING 2304.8.3 
MEMBRANE ROOF COVERINGS 1507.11, 

1507.12, 1507.13 

MEMBRANE STRUCTURES 2702.2.9,3102 

MENTAL HOSPITALS 308.3 

MERCANTILE OCCUPANCY (GROUP M) 
Accessory 508.2 

Aisles 1017.2,1017.3 

Area 503,505,506,507,508 

Classification 309 

Fire alarm and detection 907.2.7 

Height 503,504,505,506,508,509 

Interior finishes Table 803.9,804 

Live load Table 1607.1 

Parking beneath or above 509.2,509.7, 

509.8, 509.9 
Plumbing fixtures 2902 

Special occupancy separation .. 309.1, Table 508.2.5 
Sprinkler system, automatic 903.2.7 

Travel distance 402.4, 1014.3, 1016.1, 1021.2 

Unlimited area 507.3,507.4,507.12 

METAL 

Aluminum Chapter 20 

Roof coverings 1504.3.2, 1507.5 

Steel Chapter 22 

Veneer 1404.5 



MEZZANINES 
Accessibility 
Area limitations 
Egress 

Equipment platforms 
Guards 
Height 

Occupant load 
Stairs 

MIRRORS 



505 

1104.4, 1108.2.4, 1108.2.9 

505.2,505.5.1 

505.3,505.4,1004.6,1007.1 

505.5 

505.5.3, 1013.1 

505.1, 1003.2 

1004.6 

708.2(9), 1009.10, 1022.1 

1008.1,2406.1,2406.4.1 (7) 



MIXED OCCUPANCY (see OCCUPANCY 
SEPARATION) 

MOISTURE PROTECTION 1210, 1403.2, 

1503, 2303.2.4, 2304.11 



MONASTERIES 

MORTAR 
Ceramic tile 
Dampproofing 
Fire resistance 
Glass unit masonry 
Masonry 
Rodentproofing 



310.1 

2102.1 

2103.5 

1805.2.2 

713.3.1, 713.4.1.1 

2110.1 .1 

2103.8, 2103.9 

Appendix F 



MOTELS 310.1 

MOTION PICTURE PROJECTION ROOMS 409 

Construction 409.2 

Exhaust air 409.3.2, 409.3.3 

Lighting control 409.4 

Projection room 409.3 

Supply air 409.3.1 

Ventilation 409.3 

MOTOR FUEL-DISPENSING SYSTEM 406.5 

Accessibility 1109.13, 3411.8.13 

MOTOR VEHICLE FACILITIES 304, 311, 406 

MOVING, BUILDINGS 3410,0103.3 

MOVING WALKS 3005.2 

Means of egress 1 003.7 

N 

NAILING 2302.1, 2303.6, 2304.9 

NONCOMBUSTIBLE BUILDING MATERIAL ... 703.4 

NURSING HOMES 
(see INSTITUTIONAL, GROUP 1-2) 308.3, 407 



OCCUPANCY 
Accessory 508.2 

Atriums 404.2 

Certificates (see CERTIFICATE OF OCCUPANCY) 
Change (see CHANGE OF OCCUPANCY) 
Floor loads Table 1607.1 

Special Chapter 4 

OCCUPANCY CATEGORY 
(Seismic Design) 1602.1, 1604.5 

Multiple occupancies 1604.5.1 

OCCUPANCY CLASSIFICATION 302 

Covered mall and open mall buildings 402 

HPM 415.8 

Mixed 508.3 

Mixed occupancy values 508, 3412.6.16 

Special Chapter 4 

OCCUPANCY SEPARATION 
Accessory 508.2 

Aircraft related 412.4.4, 412.5.1 

Covered mall and open mall building 402.7 

Incidental accessory occupancies .. 508.2.5,707.3.6 
Mixed occupancy 508, 509, 707.3.8 

Parking garages 406.1.4, 406.2.7, 

Table 508.3.3(c) 
Repair garages 406.6.2 

Required fire resistance Table 508.4, 509 

Stages 410.5.1, 410.5.2 

OCCUPANT EVACUATION ELEVATORS .... 403.5.2, 

403.6.2, 3008 

OCCUPANT LOAD 

Actual 1004.1.1 

Certificate of occupancy 111 

Covered mall and open mall building 402.4.1 

Determination of 1004.1, 1004.1.1 



2009 INTERNATIONAL BUILDING CODE® 



663 



INDEX 



Increased 1004.2 

Outdoors 1004.8 

Seating, fixed 1004.7 

Signs 1004.3 

OFFICE BUILDINGS 
Classification 304 

Live loads Table 1 607. 1 , 1 607.5 

OPEN MALL BUILDINGS (see COVERED MALL 
AND OPEN MALL BUILDINGS) 

OPENING PROTECTION, EXTERIOR WALLS .. 705.8 

OPENING PROTECTION, FLOORS 
(see VERTICAL OPENING PROTECTION) 

OPENING PROTECTIVES 705.8, 706.8, 

707.6, 708.7, 709.6, 

710.5, 712.8, 715 

Automatic closing devices 715.4.8, 909.5.2 

Fire door and shutter assemblies 705.8.2, 

712.8, 715.4 
Fire windows 715.5 

Glazing 715.5 

Glass unit masonry 

(see GLASS UNIT MASONRy) 2110.1.1 

Self-closing 715.4.7 

ORGANIC COATINGS 418 

ORGANIC PEROXIDES 307.4,307.5 

OXIDIZERS, LIQUID AND SOLID 307.2 



PANIC HARDWARE 
PARAPET, EXTERIOR WALL 

Construction 

Fire wall 

Height 
PARKING, ACCESSIBLE 



1008.1.10 
705.11,2109.3.4.1.4 
705.11.1 
706.6 
705.11.1 
1106, 1110.1, 
3411.4,3411.7 
406.2 
1105.1.1,1106.1,1110.1 
406.2.4,1602.1,1607.7.3 
311, 406.2.1 
406.3.3, Table 503, Table 601 



PARKING GARAGES 
Accessibility 
Barriers, vehicle 
Classification 
Construction type 
Enclosed 

(see PARKING GARAGE, ENCLOSED) 406.4 

Gates 3110 

Guards 406.2.3, 2407.1.3 

Height, clear 406.2.2 

Live loads Table 1607.1,1607.9.1.3 

Occupancy separation 406.2.7,508,509 

Open (see PARKING GARAGE, OPEN) 406.3 

Special provisions 509 

Sprinklers 903.2.10 

Underground 405 

PARKING GARAGES, ENCLOSED 406.4 

Area and height [see STORAGE 

OCCUPANCY (GROUP S)] 406.4.1 

Means of egress 1003.2, 1010.1, 1021.1.2 

Ventilation 406.4.2 



PARKING GARAGES, OPEN 403.1, 406.3 

Area and height [see STORAGE 

OCCUPANCY (GROUP S)] 406.3.5,406.3.6 

Construction type 406.3.3 

Means of egress 406.3.8,1003.2,1007.3, 

1007.4, 1010.1, 1016.1, 1018.1, 
1021.1.2, 1022.1, 1024.1, 1027.1 
Occupancy separation 406.3.4 

Standpipes 406.3.9 

Ventilation 406.3.12 

PARTICLEBOARD 2302.1 

Draftstopping 717.3.1 

Moisture protection 1403.2, 1405.2 

Quality 2303.1.7 

Shear walls 2306.5 

Veneer 1405.5 

Wall bracing 2308.9.3 

PARTITIONS 

Fire (see FIRE PARTITION) 

Live loads 1607.5, 1607.13 

Materials 602.4.6, 603.1 (10), 603.1 (25) 

Occupancy, specific 709.1 

Smoke (see SMOKE PARTITION) 

Toilets 2903 

PARTY WALLS 

(see FIRE WALLS) 706.1.1, Table 715.5 

PASSAGEWAY, EXIT (see EXIT) 1023.1 

PASSENGER STATIONS 303 

PATIO COVERS 2606.10, Appendix I 

PEDESTRIAN 

Protection at construction site 3303.2, 3306 

Walkways and tunnels 31 04,3202.3.4 

PENALTIES 114.4 

PENETRATION-FIRESTOP SYSTEM 

Fire-rated walls 713.3.2 

Fire-rated horizontal assemblies 713.4.1.2 

PENETRATIONS 713, 716 
Fire-resistant assemblies 

Exterior wall 705.10 

Fire barrier 707.7,707.9 

Fire partition 709.7,709.9 

Firewall 706.9, 706.11 

Horizontal assemblies 712.5, 712.7, 713.4 

Shaft enclosures 708.1, 708.2, 708.8, 708.10 

Smoke barriers 710.6,71 0.8,71 3.5 

Smoke partitions 711.6, 711.7 

Walls 713.3 

Nonfire-resistant assemblies 713.4.2 

PERLITE Table 720.1(1), Table 2507.2 

PERMITS 105 

Application for 104.2, 105.1, 105.3 

Drawings and specifications 107.2.1 

Expiration 105.5 

Fees 1 09 

Liability for issuing 104.8 

Placement of permit 105.7 



664 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Plan review 

Suspension or revocation 
Time limitations 



104.2,107.3 

105.6 

105.3.2,105.5 



PIER FOUNDATIONS 
(see FOUNDATION, SHALLOW) 

PILE FOUNDATIONS (see FOUNDATION, 

PIPES 



DEEP) 



Embedded in concrete 




1906.3 


Embedded in fire protection 




704.8 


Insulation covering 




719.1, 719.7 


Penetration protection 




713, 1022.4 


Under platform 




410.4 


PLAIN CONCRETE (see CONCRETE) 


1909 


PLAN REVIEW 




107.3 


PLASTER 






Fire-resistance requirements 




718 


Gypsum 




718.1, 718.2 


Inspection 




110.3.5 


Portland cement 




718.5, 


Table 2507.2, 


Table 2511.1.1 


PLASTIC 




Chapter 26 


Approval for use 




2606.2 


Core insulation, reflective plastic 




2613 


Fiber reinforced polymer 




2612 


Fiberglass-reinforced polymer 




2612 


Finish and trim, interior 




2604 


Light-transmitting panels 




2401.1, 2607 


Roof panels 




2609 


Signs 




402.16, 2611, 




0102.2.10, H107.1.1 


Thermal barrier 




2603.4 


Veneer 1404.8,2605,0102.2.11 


Walls, exterior 


2603.4.1.4, 2603.5 



PLASTIC, FOAM 

Insulation (see FOAM PLASTICS) 2603 

Interior finish 803.4, 2603.9 

Malls 402.11, 402.12.1, 402.16.5 



PLATFORM LIFTS, WHEELCHAIR 
Accessible means of egress 



1007.2,1007.5, 
1009.1,2702.2.6 
1109.7, 3411.8.3 



2302.1 

2303.1.8.1 

720 

2302.1 

2304.9.5 

2303.1.8 

1403.5, 2304.11 

1507.9.6, 1507.9.8 



Accessibility 
PLUMBING (see TOILET AND 

TOILET ROOMS) 1 01 .4.3, 1 05.2, Chapter 29 

Aircraft hangars, residential 412.5.4 

Facilities, minimum 2902, 3305.1 

Fixtures Table 2902.1 

Room requirements 1210, 2406.2, 

2406.4, 2606.9, 2903 
PLYWOOD 

(see WOOD STRUCTURAL PANELS) 

Preservative-treated 
PRESCRIPTIVE FIRE RESISTANCE 
PRESERVATIVE-TREATED WOOD 

Fastenings 

Quality 

Required 

Shakes, roof covering 
PROJECTION ROOMS 

Motion picture 409 

PROJECTIONS, COMBUSTIBLE 705.2.3, 1406.3 

PROPERTY LINE (see FIRE SEPARATION 

DISTANCE) 705.3 

PROPERTY MAINTENANCE 101.4.4 

PROSCENIUM 

Opening protection 410.3.5 

Wall 410.3.4 

PUBLIC ADDRESS SYSTEM (see EMERGENCY 

COMMUNICATIONS) 

Covered mall and open mall building 402.15, 

907.2.20,2702.2.14 

Special amusement buildings 41 1 .6 

PUBLIC PROPERTY Chapter 32, Chapter 33 

PUBLIC RIGHT-OF-WAY 

Encroachments Chapter 32 



Stages and platforms 




410.3.6 


PYROPHORIC MATERIALS Table 307.1 (1), 307.4 


PLASTIC, LIGHT-TRANSMITTING 








Awnings and patio covers 




2606.10 


R 


Bathroom accessories 




2606.9 


Exterior wall panels 




2607 


RAILING (see GUARDS AND HANDRAILS) 


Fiber reinforced polymer 




2612.5 


RAMPS 1010 


Fiberglass-reinforced polymer 




2612.5 


Assembly occupancy 1028.1 1 


Glazing 




2608 


Construction 1010.2 through 1 01 0.5.3, 


Greenhouses 




2606.11 


1010.7,1010.9 


Light-diffusing systems 




2606.7 


Existing buildings 3411.8.5 


Roof panels 




2609 


Exterior 1026, 3201.4 


Signs, interior 




2611 


Guards 1010.10,1013,1607.7 


Skylight 




2610 


Handrails 1010.8, 1012, 1607.7 


Solar collectors 




2606.12 


Landings 1010.6 


Structural requirements 




2606.5 


Parking garage 406.2.5 


Unprotected openings 


2608.1, 2608.2 


Slope 1010.2,3411.8.5 


Veneer, exterior 603.1 (14), 


603.1 


(16), 2605 


REFERENCED STANDARDS Chapter 35 


Wall panels 




2607 


Applicability 102.3, 102.4 


PLATFORM (see STAGES AND PLATFORMS) 410 


Fire resistance 703.2 


Construction 




410.4 


List. Chapter 35 


Temporary 




410.4.1 


Organizations Chapter 35 



2009 INTERNATIONAL BUILDING CODE® 



665 



INDEX 



REFORMATORIES 308.4 

REFRIGERATION (see MECHANICAL) 101.4.2 

Machinery room 1015.4 

REFUGE AREAS 
(see HORIZONTAL EXIT, SMOKE 
COMPARTMENTS, STORM SHELTERS) . . . 407.4.1 , 

408.4.1,408.6, 
422.3, 423.1.1, 1025.4 

REFUSE CHUTE 708.13 

REINFORCED CONCRETE (see CONCRETE) 
General 1901.2 

Inspections 1704.4 

REINFORCEMENT 
Concrete 1907, 1913.4, 1915.4 

Masonry 2103.13 

RELIGIOUS WORSHIP, PLACES OF 

Balcony 1028.5, 1108.2.4 

Classification 303, 305.1 

Door operations 1008.1.9.3 

Egress 1028 

Fire alarm 907.2.1 

Interior finishes Table 803.9,804 

Special occupancy separation .. 303.1, Table 508.2.5 
Unlimited area 507.6, 507.7 

REPAIRS, BUILDING 3405 

Compliance alternatives 3412.1, 3412.2.4, 3412.3 
Flood 1612.1, 1612.2, 3405.5 

Minor 105.2.2 

Permit required 105.1 

Scope 101.2, 1613.3, 3401.1, 

3401.3, 3409.1, 3411.2 

RESIDENTIAL CARE/ASSISTED 
LIVING FACILITIES 308.1 

Accessibility 1107.5.1, 1107.5.2, 

1107.6.4,3411.8.7,3411.8.9 
Fire alarms 907.2.6,907.5.2.3.3 

Separations Table 508.2.5, Table 508.4 

Smoke alarms 907.2.11.2 

Sprinklers 903.2.6, 903.3.2 

RESIDENTIAL OCCUPANCY (GROUP R) 310 

Accessibility 1106.2, 1107.6, 

3411.8.7,3411.8.8, 
3411.8.9, E104.2, E104.3 
Accessory 508.2, G801.1 

Area 503,505,506,507,508 

Corridors 1018.1, 1018.2 

Doors 1008.1.1 

Draftstopping 717.3.2, 717.4.2 

Emergency escape and rescue 1029.1 

Exit sign exemptions 1011 .1 

Fire alarm and detection 907.2.8, 

907.2.9,907.2.10 
Group R-1 310.1 

GroupR-2 310.1 

GroupR-3 310.1 

Group R-4 310.1, 1008.1.9.5.1 

Height 503,504,505,506,508,509 

Interior finishes Table 803.9,804 

Live load Table 1607.1 



Parking, private 

Parking beneath or above 

Partitions 

Plumbing fixtures 

Smoke alarms 

Special occupancy separation. 



406.1 

509 

420, 709.1 

2902 

907.2.11 

419, 420, 508.2.4, 



Special provisions 
Sprinklers 
Swimming pools 
Travel distance 
Visible alarms 



Table 508.2.5, 508.3.3 

509.5,509.6 

903.2.8, 903.3.2 

3109.4 

1014.3, 1016.1, 1021.2 

907.5.2.3.3,907.5.2.3.4 



RETAINING WALLS 1807.2,2304.11.7 

Flood provisions G801.4 

Seismic 1803.5.12 

REVIEWING STANDS (see BLEACHERS AND 
GRANDSTANDS) 1028.1.1 

Live load Table 1607.1 

RISERS, STAIR (see STAIRWAY CONSTRUCTION) 
Alternating tread device 1 009. 1 0.2 

Assembly 1028.5.1, 1028.6, 

1028.7, 1028.9, 1028.11 
Closed 1009.4.5 

General 1009.4 

Spiral 1009.9 

Uniformity 1009.4.4 

RODENTPROOFING Appendix F 

ROLL ROOFING 1507.6 

ROOF ACCESS 1009.13, 1009.14 

ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 
Cooling towers 1509.4 

Drainage 1503.4, 3201.4 

Fire classification 1505 

Fire district 0102.2.9 

Height modifications 504.3 

Impact resistance 1 504.7 

Materials 1506 

Parapet walls 1503.3, 1503.6 

Penthouses 1509.2 

Tanks 1509.3 

Towers, spires, domes and cupolas 1509.5 

Weather protection 1503 

Wind resistance 1504.1, 1609.5 

ROOF CONSTRUCTION 
Construction walkways 3306.7 

Coverings (see ROOF COVERINGS) 1609.5.2 

Deck 1609.5.1 

Draftstopping 717.4 

Fire resistance Table 601 

Fireblocking 717.2 

Live loads Table 1 607. 1 , 1 607. 1 1 

Materials Chapter 6 

Penetration of fire resistant assemblies 713 

Protection from adjacent construction 3307.1 

Rain loads 1611 

Roof structures 504.3, 1509, 0102.2.9 

Signs, roof mounted H110 

Slope, minimum Chapter 15 

Snow load 1608 



666 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



Trusses 2210.3, 2303.4, 2308.10.10 

Wood (see ROOF CONSTRUCTION, WOOD) 

ROOF CONSTRUCTION, WOOD 602.4.3, 602.4.5 

Anchorage to walls 1 604.8.2 

Attic access 1209.2 

Ceilingjoists 2308.10.2 

Diaphragms 2305.1, 2306.2 

Fastening schedule 2304.9 
Fire-retardant-treated Table 601, 603.1 (25) 

Framing 2304.10.3,2308.10 

Rafters 2306.1 .1 

Sheathing 2304.7,2308.10.8 

Trusses 2303.4,2308.10.10 

Ventilation, attic 1203.2 

Wind uplift 2308.10.1 

ROOF COVERINGS 1507 

Asphalt shingles 1507.2 

Built up 1507.10 

Clay tile 1507.3 

Concrete tile 1507.3 

Fire district 0102.2.4 

Fire resistance 603.1 (3), 1505 
Flashing 1503.2, 1503.6, 1507.2.9, 
1507.3.9,1507.5.7,1507.7.7, 
1507.8.8,1507.9.9,1510.6 

Impact resistance 1 504.7 

Insulation 1508 

Liquid applied coating 1507.15 

Membrane 3102 

Metal panels 1507.4 

Metal shingles 1507.5 

Modified bitumen 1507.11 

Plastics, light-transmitting panels 2609 

Replacement/recovering 1510.3 

Reroofing 1510 

Roll 1507.6 

Single-ply 1507.12 

Slate shingles 1507.7 

Sprayed polyurethane foam 1507.14 

Thermoplastic single-ply 1507.1 3 

Wind loads ' 1504.1, 1609.5 

Wood shakes 1507.9 

Wood shingles 1507.8 

ROOF DRAINAGE 1503.4 

ROOF REPLACEMENT/RECOVERING 1510.3 
ROOF STRUCTURE (see ROOF ASSEMBLIES AND 

ROOFTOP STRUCTURES) 

ROOM DIMENSIONS 1208 

ROOMING HOUSE 310 



SAFEGUARDS DURING 
CONSTRUCTION 
Adjoining property protection 
Construction 
Demolition 
Evacuations 
Fire extinguishers 



Chapter 33 
3307 
3302 
3303 
1804.1 
3309 



Means of egress 3310 

Protection of pedestrians 3306 

Sanitary facilities 3305 

Site work 3304 

Sprinkler system, automatic 3312 

Standpipes 3308.1.1, 3311 

Temporary use of streets, alleys 
and public property 3308 

SAFETY GLAZING 715.4.7.4,2406 

SCHOOLS (see EDUCATIONAL OCCUPANCY) 
SEATING, FIXED 1028 

Accessibility 1108.2, 1109.10 

Aisles 1017.4,1028.9 

Bleachers (see BLEACHERS) 
Grandstands (see GRANDSTANDS) 
Live load Table 1607.1 

Occupant load 1004.7 

Temporary 108 

SECURITY GLAZING 408.7 

SECURITY GRILLES 1008.1.4.5 

SEISMIC 1613 

Construction documents 107, 1603.1.5, 

1603.1.9, 1709 
Existing building 3403.4.1, 3404.4.1, 

3404.5, 3405.2, 3408.4 
Fire-resistance 704. 1 2 

Geotechnical investigation 1803.5.11, 1803.5.12 

Glazing 2404 

Loads 1613 

Masonry 2106 

Membrane structure 3102.7 

Seismic design category 1613.2, 1613.5.6 

Seismic detailing 1 604.1 

Site class 1613.2, 1613.5.2, 1613.5.5 

Site classification for seismic design 1613.5.5 

Site coefficients 1 613.2, 1 61 3.5.3 

Statement of special inspections 1705.3 

Steel 2205 

Structural observations 1707, 1710 

Structural testing 1708 

Wood 2305,2308.11,2308.12 

SERVICE STATION 
(see MOTOR FUEL-DISPENSING FACILITIES) 

SHAFT (see SHAFT ENCLOSURE 
AND VERTICAL OPENING PROTECTION) .... 702 

SHAFT ENCLOSURE (see VERTICAL 
OPENING PROTECTION) 708 

Continuity 708.5, 708.11, 708.12 

Elevators 708.14 

Exceptions 708.2, 1016.1, 1022.1 

Exterior walls 708.6 

Fire-resistance rating 707.3.1, 708.4 

Group 1-3 408.5 

High-rise buildings 403.2.1.2, 403.2.3, 

403.3.1.1, 403.5.1 
Joints 708.9, 714 

Materials 708.3 

Opening protection 708.8, 708.10, 713, 716.5.3 

Penetrations 708.8 



2009 INTERNATIONAL BUILDING CODE® 



667 



INDEX 



Refuse and laundry chutes 708.13 

Required 708.2 

SHEAR WALL 
Gypsum board and plaster 2505 

Masonry 2102.1 

Wood 2302.1, 2305.1, 2306.3 through 2306.7 

SHEATHING 

Clearance from earth 2304.1 1 .2.2 

Fastening 2304.9 

Fiberboard 2306.6 

Floor 2304.7, 2308.8.6 

Gypsum 2306.2.4 

Moisture protection 2304.1 1 .2.2 

Particleboard 2306.5 

Roof 2304.7 

Roof sheathing 2308.10.8 

Wall 2304.6.1, 2308.9.3 

Wood structural panels 2303.1.4, 2211.3 

SHOPPING CENTERS 309 

SHOTCRETE 1913 

SHUTTERS, FIRE 
(see OPENING PROTECTIVES) 715.4 

SIDEWALKS 105.2(6), G801.4 

Live loads Table 1607.1 

SIGNS 3107, Appendix H 

Accessibility 1011.3, 1110, 

E106.4.9, E107, E109.2.2 
Accessible means of egress 1007.8.2, 

1007.9 through 1007.11 
Animated devices H108 

Construction H105, H107 

Covered mall and open mall building 402.16 

Doors 1008.1.4.4, 1008.1.9.3, 1008.1.9.7 

Electrical. H106 

Elevators 1109.6, 1110.2, 3002.3, 3008.11.5 

Encroachment, public right-of-way 3202.3.1 

Exit 1011, 2702.2.3, 2702.2.9 

Floor loads 106.1 

Ground H109 

Height limitation H1 09.1, H112.4 

Illumination H106.1 

Luminous 403.5.5, 1011.4, 1024 

Marquee H113 

Obstruction 1003.3.2,1003.3.3, H103 

Occupant load, assembly 1004.3 

Parking spaces 1110.1 

Plastic 2611, 0102.2.10 

Portable H114 

Projecting H112 

Protruding objects 1003.3 

Roof H110 

Stair identification 1 022.7, 1 022.8, 1 1 1 0.2, 1110.3 
Standpipe control valve 905.7.1 

Walls 703.6, H111 

SITE DRAWINGS 107.2.5 

SITE WORK 3304 

SKYLIGHTS 2405,3106.3 

Light, required 1205.2 



Loads 2404 

Plastic 2610 

Protection from adjacent construction 3307.1 

SLAB, COMPOSITE 

STEEL DECK/CONCRETE 2209.2.1 

SLAB ON GROUND, CONCRETE.. 1910, 2304.11.2.3 
SLATE SHINGLES 1507.7 

SLEEPING UNITS 202 

Accessibility 1102, 1103.2.11, 

1105.1.6,1106.2,1106.7.2,1107 

Accessibility, existing 3411.1, 3411.8.7, 

3411.8.8, 3411.8.9 
Group I 308 

Group R 310 

Scoping 101.2 

Separation 420.2, 420.3 

SMOKE ALARMS 

Live/work unit 907.2.11.2 

Multiple-station 907.2.11 

Residential aircraft hangars 412.5.3, 

412.5.4, 907.2.21 

Residential occupancies 907.2.1 1 .1 ,907.2.1 1 .2 

Single-station 907.2.11 

SMOKE BARRIERS 710 

Ambulatory care facilities 422.2 

Construction 407.4.3, 710.4,909.5 

Doors 710.5, 715.4.3, 909.5.2 

Fire-resistance rating 703, 710.3 

Glazing, rated 715.5 

Horizontal assemblies 712.9 

Inspection 1 10.3.6 

Joints 71 0.7, 71 4 

Marking 703.6 

Materials 710.2 

Opening protection 710.5, 713.3, 713.5, 

715, 716.5.5, 909.5.2 

Penetrations 710.6, 713 

Smoke control 909.5 

Special provisions 

Ambulatory care facilities 422 

Group 1-2 407.4 

Group 1-3 408.6,408.7 

Underground 405.4.2, 405.4.3 

SMOKE COMPARTMENT 407,408,422 
Refuge area (see REFUGE AREA) 

SMOKE CONTROL 909 

Amusement buildings, special 411.1 

Atrium buildings 404.5 

Covered mall and open mall building 402.10 

Group 1-3 408.9 

High-rise 403.4.6,403.5.4,1022.9 

Special inspections 1704.16 

Stages 410.3.7.2 

Standby power systems 909.20.6.2, 2702.2.2 

Systems 909 

Underground buildings 405.5 

Values 3412.6.10.1 



SMOKE DAMPERS 



716.2 through 716.5 



668 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



SMOKE DETECTION SYSTEM (see FIRE ALARM 

AND SMOKE DETECTION SYSTEMS) 907 

SMOKE DETECTORS 



Membrane structures 

STRUCTURES) 
Pedestrian walkways and tunnels 



see MEMBRANE 

3102 
see WALKWAYS 



Covered mall and open mall 


402.4.5.1,907.2.20 


High-rise buildings 


403.4.1,907.2.13 


HPM 


415.8.9.3 


Institutional 1-2 


407.7 


Smoke activated doors 


715.4.8.3 


Special amusement buildings 


411.5 


Underground buildings 


907.2.18,907.2.19 


SMOKE-DEVELOPEMENT 


802, 


. 


803.1.1, Table 803.9 


SMOKE EXHAUST SYSTEMS 




Underground buildings 405.5,907.2.18,909.2 


SMOKE PARTITIONS 


711 


Continuity 


711.4 


Doors 


711.5 


Ducts and air transfer openings 


711 .7 


Fire-resistance rating 


711.3 


Inspection 


110.3.6 


Joints 


711.6 


Marking 


703.6 


Materials 


711.2 


Opening protection 


711.5, 716.5.7 


Penetrations 


711 .6 


Special provisions 




Atriums 


404.6 


Group 1-2 


407.3 


SMOKE REMOVAL 


403.4.6 


SMOKE VENTS 


410.3.7.1,910 


SMOKEPROOF ENCLOSURES 


403.5.4, 1022.9 


Design 


909.20 


SNOW LOAD 


1608 


Glazing 


2404 


SOILS AND FOUNDATIONS 




(see FOUNDATION) 


Chapter 18 


Depth of footings 


1809.4 


Excavation, grading and fill. .. 1804, 3304, J1 06, J1 07 


Expansive 


1803.5.3, 1808.6 


Flood hazard 


1808.4 


Footings and foundations 


1808 


Footings on or adjacent to slopes 


.. 1808.7, 3304.1.3 


Foundation walls 


1807.1.5, 3304.1.4 


Geotechnical investigation 


1803 


Grading 


1804.3, Appendix J 


Loadbearing values 


1806 


Soil boring and sampling 


1803.4 


Soil lateral load 


1610 


Special inspection 


1704.7 


SORORITIES 


310.1 


SOUND-INSULATING MATERIALS 


(see INSULATION) 


719 


SOUND TRANSMISSION 


1207 


SPECIAL CONSTRUCTION 


Chapter 31 


Automatic vehicular gates 


3110 


Awnings and canopies (see AWNINGS and 


CANOPIES) 


3105 


Marquees (see MARQUEE) 


3106 



and TUNNELED WALKWAYS) 3104 

Signs (see SIGNS) 3107 

Swimming pools enclosures and safety devices 

(see SWIMMING POOL) 3109 

Telecommunication and broadcast towers 

(see TOWERS) 3108 

Temporary structures 

(see TEMPORARY STRUCTURES) 3103 

SPECIAL INSPECTIONS (see INSPECTIONS and 
STRUCTURAL TESTS AND SPECIAL 
INSPECTIONS) 



SPIRAL STAIRS 
Construction 
Exceptions 1009.4.2, 



1009.9 

1009.1,1009.2,1009.9 

1009.4.3, 1009.4.5, 1009.12 



Group 1-3 


408.3.4 


Live/work 


419.3.3 


Stages 


410.5.3, 1015.6.1 


SPRAY-APPLIED FIRE RESISTANT 




MATERIALS 


1702.1 


Inspection 


1704.12, 1704.13 


Steel column calculated fire resistance 721.5.2.2 


SPRINKLER SYSTEMS, AUTOMATIC 903, 3312 


Exempt locations 


903.3.1.1.1 


Fire department location 


912 


Seismic design 


1613.6.3 


Signs 


914.2 


Substitute for fire rating 


Table 601 (4) 


Values 


3412.6.17 


SPRINKLERS, REQUIRED 


903 


Aircraft related 


412.4.6, 412.6.5 


Ambulatory health care facilities 


422.5, 903.2.2 


Amusement buildings, special 


411.4 


Area increase 


506.3 


Assembly 903.2.1, 903.2.11.5, 1028.6.2.3 


Atrium building 


404.3 


Basements 


903.2.11.1 


Combustible storage 


413 


Construction 


903.2.12 


Covered mall and open mall building 402.9 


Drying rooms 


417.4 


Education 


903.2.3 


Exempt locations 


903.3.1.1.1 


Factory 


903.2.4 


Fire areas 


707.3.9 



Garages 406.3.10,903.2.9.1,903.2.10.1 

Hazardous materials Table 414.2.5(1), 

Table 414.2.5(2), 903.2.11.4 

Hazardous occupancies 415.5.2, 415.6.2.4, 

415.8.6.3, 415.8.11, 

705.8.1,903.2.5 

Height increase 504.2 

High-rise buildings 403.2, 403.3, 903.2.11.3 

Incidental accessory occupancies Table 508.2.5 

Institutional. ' 407.5,903.2.6,903.3.2 

Laundry chutes, refuse chutes, termination 
rooms and incinerator rooms ... 708.13, 903.2.11.2 



2009 INTERNATIONAL BUILDING CODE® 



669 



INDEX 



Live/work units 

Mercantile 

Mezzanines 

Multistory buildings 

Residential 

Special amusement buildings 

Spray finishing booth 

Stages 

Storage 

Supervision 
(see SPRINKLERS, SUPERVISION) 

Underground buildings 

Unlimited area 
SPRINKLERS, SUPERVISION 

Service 

Underground buildings 
STAGES AND PLATFORMS 

Dressing rooms 

Egress 

Fire barrier wall 

Floor finish and floor covering 

Horizontal assembly 
Platform, temporary 
Platform construction 
Proscenium curtain 
Proscenium wall 
Roof vents 
Scenery 
Smoke control 
Sprinkler system 
Stage construction 
Standpipes 
Ventilation 

STAIRWAY (see ALTERNATING TREAD DEVICES, 
SPIRAL STAIRS, STAIRWAY CONSTRUCTION and 
STAIRWAY ENCLOSURE) 

STAIRWAY CONSTRUCTION 



419.5, 903.2.8 


Roof access 


1009.13,1009.14 


903.2.7 


Seismic anchorage 


2308.12.7 


505.4, 505.5.2 


Spiral (see SPIRAL STAIRS) 


408.3.4, 


903.2.11.3 




410.5.3,419.3.3,1009.9 


903.2.8, 903.3.2 


Treads and risers 


1009.3, 1009.4 


411.4 


Width 


1009.1 


416.5 


Winders 


1009.3, 1009.4.2, 


410.6 


1009.4.3,1009.4.4,1009.8 


903.2.9, 903.2.10 


STAIRWAY ENCLOSURE 


708.2,1022.1 


\\ 1 \ O/^O A 


Access 


1022.1.9.2 


)N) 903.4 


Construction 


1022.4 


405.3, 903.2.11.1 
507 


Discharge 


1027.1 


Doors 


715.4.8, 1008.1.9.10 


903.4 


Elevators within 


1022.3,3002.7 


901.6 


Exterior walls 


705.2, 707.4, 708.6, 


405.3 




709.5, 1022, 1026.6 


303, 410 


Fire-resistant construction 


1022.1 


410.5 


Group 1-3 


408.3.8 


410.5.3, 1015.6 


High-rise 


403.5 


410.5.1, 410.5.2 


Penetrations 


1022.4 


410.3, 410.4, 


Pressurization 


909.6, 909.20.5 


804.4,805.1 


Space below, use 


1009.6.3 


410.5.1,410.5.2 


Ventilation 


1022.5 


410.4.1 


STANDARDS (see REFERENCED STANDARDS) 


410.4, 603.1 (11) 






410.3.5 


STANDBY POWER 


2702.1, 2702.3 


410.3.4 


Aircraft traffic control towers 


412.3.5, 2702.2.18 


410.3.7.1 


Atriums 


404.7,2702.2.2 


410.3.6 


Covered mall and open mall 


building 402.14, 


410.3.7.2 




2702.2.14 


410.6 


Elevators 1007.4, 2702.2.5, 2702.2.19, 


410.3, 603.1 (11) 




3003.1,3007.7,3008.15 


410.7,905.3.4 


Hazardous occupancy 


414.5.4, 421.8, 


410.3.7 




2702.2.10,2702.2.12 



Aisle 


1028.9 


Alterations 


3404.1 


Alternating tread 


1009.10 


Circular (see Curved) 




Construction 


1009.6 


Curved 


1009.3,1009.8 


Discharge barrier 


1022.7 


During construction 


3310.1 


Elevators 


1009.14,1022.3,3002.7 


Enclosure under 


1009.6.3 


Existing 


3404.1, 3408.3 


Exterior exitway 


1026.1, 1027.1 


Fireblocking 


717.2.4 


Guards 


1013.1,1013.2,1607.7 


Handrails 


1009.12, 1012, 1607.7 


Headroom 


1009.2 


Illumination 


1006.1, 1205.4, 1205.5 


Ladders 


1009.11 


Landings 


1009.5, 1009.7 


Live load 


Table 1607.1,1607.7 


Luminous 


403.5.5, 411.7.1, 1024 



High-rise 

Horizontal sliding doors 
Membrane structures 
Platform lifts 
Smoke control 
Smokeproof enclosure 
Underground buildings 

STANDPIPE AND HOSE SYSTEMS 
STANDPIPES, REQUIRED) 



403.4.7,2702.2.15 

1008.1.4.3, 2702.2.7 

2702.2.9,3102.8.2 

1007.5, 2702.2.6 

909.11, 2702.2.2 

909.20.6.2, 2702.2.20 

405.8, 2702.2.16 



Cabinet locks 

Dry 

Hose connection location 



(see 

905,3106.4, 
3308.1.1,3311 
905.7.2 
905.8 
905.1, 
905.4 through 905.6, 912 

STANDPIPES, REQUIRED 
Assembly 905.3.2,905.5.1 

Covered mall and open mall buildings 402.9.1, 

905.3.3 
During construction 
Elevators, fire service access 
Helistops 
Marinas 

Parking garages 
Stages 
Underground buildings 



905.10 

3007.5 

905.3.6 

905.3.7 

406.3.6, 406.3.9 

410.7,905.3.4 

405.10, 905.3.5 



670 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



STATE LAW 


102.2 


STEEL 


Chapter 22 


Bolting 


2204.2 


Cable structures 


2207 


Calculated fire resistance 


721.5 


Cold-formed 


2202.1, 2209, 2210 


Conditions of restraint. 


703.2.3 


Decks 


2209.2 


Identification and protection 


2203 


Joists 


2202.1, 2206 


Open webjoist 


2206 


Parapet walls 


1503.3, 1503.6 


Reinforcement, concrete 


1907 


Seismic provisions 


2205 


Special inspections 


1704.3 


Storage racks 


2208 


Welding 


2204.1 


STONE VENEER 


1405.7 


Slab-type 


1405.8 


STOP WORK ORDERS 


115 



STORAGE OCCUPANCY (GROUP S) 311 

Accessory 508.2 

Area 406.3.5, 406.3.6, 

406.4.1 ,503,505,506,507,508 
Automobile parking garage 406 

Hazard storage, low, Group S-2 311.3 

Hazard storage, moderate, Group S-1 311.2 

Height 406.3.5, 406.4.1, 503, 

504, 505, 506, 508, 509 



Alternative test procedure 

Approvals 

Contractor responsibilities 

Design strengths of materials 

General 

In-situ load tests 

Material and test standards 

Preconstruction load tests 

Special inspections 

Statement of special inspections 

Structural observations 

Structural testing 

Test safe load 

STRUCTURAL OBSERVATION 

STUCCO 2512 

SWIMMING POOL 3109 

Flood provisions G801.5 

Gates, access 3109.4.1.7 

Glass 2406.4 

Indoor 3109.4.2 

Public 3109.3 

Residential 3109.4 



171 2 
1703 
1709 
1711 
1701 
1714 
1716 
1715 
1704, 1706, 1707 
1705 
1710 
1708 
1713 

1702.1,1710 



TELEPHONE EXCHANGES 

TELESCOPIC SEATING (see FOLDING AND 



304 



High-piled combustible 




413 


TELESCOPIC SEATING) 






Interior finishes 


Table 803.9,804 


TEMPORARY STRUCTURES 




3103 


Live loads 




Table 1607.1 


Certificate of occupancy 




108.3 


Parking garages 406.1 


, 406.2, 406.3, 406.4 


Conformance 




108.2 


Plumbing fixtures 




2902 


Construction documents 




3103.2 


Smoke and heat vents 




910.2 


Encroachment, public right-of-ways 




3202.3 


Special occupancy separation .. 


309.' 


I, Table 508.2.5 


Flood provisions 




G901 


Sprinkler system, automatic 




903.2.10 


Means of egress 




3103.4 


Travel distance 1014.3, 


1016.1, 1021.2 


Permit. 


108.1, 


3103.1.1 


Unlimited area 


507.2,507.3,507.4 


Power, temporary 




108.3 


STORM SHELTER 




423 


Termination of approval 




108.4 


Refuge area (see REFUGE AREA) 




TENANT SEPARATION 






STRENGTH 






Covered mall buildings 


402.7,709.1 


Design requirements 

Masonry 

Nominal 




1604.2 

2102.1 

1602.1 


TENTS 

Standby and emergency power 




2702.2.9 


Required 




1602.1 


TERMITES, PROTECTION FROM 




2304.11 


STRENGTH DESIGN 




1602.1,1604.1 


TERRACOTTA 




1405.9 


Masonry 




2101.2.2, 2108 


TESTING 






STRUCTURAL DESIGN 




Chapter 16 


Building official required 




104.11.1 


Aluminum 




Chapter 20 


Concrete 




1905.6 


Concrete 




Chapter 19 


Fire-resistant materials 




703.2 


Foundations 




Chapter 18 


Glazing 


2406, 


2408.2.1 


Masonry 




Chapter 21 


Roof tile 




1716.2 


Steel 




Chapter 22 


Seismic 




1708 


Wood 




Chapter 23 


Smoke control 




909.3 


STRUCTURAL TESTS AND 






Soils 




1803 


SPECIAL INSPECTIONS 






Sprinklers 




904.4 


(see INSPECTIONS AND TESTING) 


110.3.9, 


Structural (see STRUCTURAL TESTS AND 








Chapter 17 


SPECIAL INSPECTIONS) 







2009 INTERNATIONAL BUILDING CODE® 



671 



INDEX 



THEATERS [see ASSEMBLY OCCUPANCY 
(GROUP A, PROJECTION ROOMS and 
STAGES AND PLATFORMS)] 

THERMAL BARRIER, 

FOAM PLASTIC INSULATION .... 2603.4 

THERMAL-INSULATING MATERIALS 

(see INSULATION) 
TILE 

Ceramic (see CERAMIC TILE) 

Fire resistance, clay or shale 
TOILETS and TOILET ROOMS 

Accessible 

Construction/materials 

Family- or assisted-use 

Fixture count 



303 

2603.5.2 

719 
2102.1 



Grab bar live loads 

Location 

Partitions 

Public facilities 

Rooms openings 

Signs 

Ventilation 



720.1 
Chapter 29,3305 
1109.2, 1607.7.2 
1210, 2903 
,. 1109.2.1, 2902.1.2, 2902.2 
Table 2902.1 
1607.7.2 
2902.3.2, 2902.3.3, 



2902.3.4 

2903 

2902.3 

1210.5 

1110.1, 1110.2 

1203.4.3 

TORNADO SHELTER (see STORM SHELTER) 
TOWERS 
Airport traffic control 
Cooling 

Location and access 
Radio 
Television 
TOXIC MATERIALS [see HIGH-HAZARD 
OCCUPANCY (GROUP H)] 
Classification 
Gas detection system 
TRAVEL DISTANCE 
Area of refuge 
Assembly seating 
Atrium 

Balcony, exterior 
Common path of travel. 
Mall 

Measurement 
Refrigeration machinery/ 

refrigerated rooms 1015.4 

Smoke compartments (Group 1-2 and 1-3) ... 

408.6.1, 
Special amusement building 
Stories with one exit. 
Suites (Group 1-2) 1014.2.3.3, 1014.2.4.3, 

1014.2.4.4, 1014.2.6 
TREADS, STAIR (see STAIRWAY CONSTRUCTION) 

Concentrated live load Table 1607.1 

TREATED WOOD 2302.1 

Fire-retardant treated wood 2303.2 

Pressure-treated wood 2303.1 .8 

Stress adjustments 2306.1 .3 

TRUSSES 
Cold-formed steel 2210.3 

Fire resistance 704.5 



412.3 

1509.4 

3108.2 

3108 

3108 



307.6,414,415 
415.8.7,421.6,908.3 

1007.6 
1028.7 
404.9 
1016.2 
1014.3 
402.4.2, 402.4.4 
1016.1 



1015.5 

. 407.4, 

408.8.1 

411 .4 

1021 .2 



Materials 

Metal-plate-connected wood 
Wood 

TUNNELED WALKWAY 

TURNSTILES 



u 

UNDERGROUND BUILDINGS 
Compartmentation 
Construction type 
Elevators 

Emergency power loads 
Exits 

Fire alarm systems 
Smoke barrier 
Smoke exhaust/control 
Smokeproof enclosure 
Sprinkler system 
Standby power 
Standpipe system 

UNLIMITED AREA BUILDINGS 



Chapter 6 

2303.4.6 

2303.4 

3104,3202.1 

1008.3 



405 

405.4 

405.2 

405.4.3 

405.10, 2702.2.16 

405.8 

405.6 

405.4.2, 405.4.3 

405.5 

405.7.2,1022.9 

405.3 

405.8, 2702.2.16 

405.11, 905.3.5 

507 



UNSAFE STRUCTURES AND EQUIPMENT 

(see STRUCTURES, UNSAFE) 115 

Appeals 113, Appendix B 

Restoration 115.5 

Revocation of permit 105.6 

Stop work orders 11 5 

Utilities disconnection 1 1 2.3 

UNSTABLE MATERIALS 307.3, Table 414.2.5(1), 

Table 414.5.1, Table 415.3.2, 
415.5.1,415.8 



UNUSABLE SPACE 



712.3.3 



USE AND OCCUPANCY 




Chapter 3 


Accessory 




508.2 


Incidental accessory occupancy 




508.2.5, 
Table 508.2.5 


Mixed 




508.3.508.4 


UTILITIES 




112 


Service connection 




11 2.1 


Service disconnection 




112.3 


Temporary connection 




112.2 


UTILITY AND MISCELLANEOUS 






OCCUPANCY (GROUP U) 




312 


Accessibility 


1103.2.5, 1104.3.1 


Accessory 




508.2, G801.1 


Agricultural buildings 




Appendix C 


Area 503,505,506,507,508 


Egress illumination 




1006.1 


Flood provisions 




G1001 


Height 503,504,505,506,508,509 


Live loads 




Table 1607.1 


Special occupancy separation 




Table 508.2.5 


Sprinkler system, automatic 




903.2.11 


Travel distance 1014.3, 


1016.1, 1021.2 



672 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



V 

VALUATION OR VALUE (see FEES, PERMIT) .. 109.3 
VEHICLE BARRIER SYSTEMS 406.2.4, 

1602.1, 1607.7.3 

VEHICLE SHOW ROOMS 304 

VEHICULAR FUELING 406.5.2 

VEHICULAR GATES 3110 



VENEER 




Cement plaster 


1405.15 


Fastening 


1405.17 


Fiber cement siding 


1405.16 


Glazing 


1405.12 


Masonry, adhered 


1405.10 


Masonry, anchored 


1405.6 


Metal 


1405.11 


Plastic 


2605 


Slab-type 


1405.8 


Stone 


1405.7 


Terra cotta 


1405.9 


Vinyl 


1405.14 


Wood 


1405.5 


VENTILATION (see MECHANICAL) 


101.4.2 


Attic 


1203.2 


Aircraft hangars, residential 


412.5.4 


Aircraft paint hangars 


412.6.6 


Bathrooms 


1203.4.2.1 


Crawl space 


1203.3 


Elevator hoistways 


3004 


Exhaust, hazardous 


1203.5 


Exhaust, HPM 


415.8.10 


Exit enclosure 


1022.5 


Fabrication areas, HPM 


415.8.2.6 


Hazardous 414.3, 414.5.4, 


415.6.1.4, 



415.6.2.8, 415.8.2.8.2, 415.8.5.7, 
415.8.6.3, 415.8.7, 415.8.9.3 
High-rise 1022.9 

HPM service corridors 415.8.4.3 

Live/work unit 419.8 

Mechanical 1203.1 

Natural 1203.4 

Parking 406.3.12, 406.4.2 

Projection rooms 409.3 

Repair garages 406.6.3 

Roof 1203.2, 1503.5 

Smokeproof enclosures 909.20.3, 

909.20.4, 909.20.6 
Spray rooms and spaces 416.2.1,416.3 

Stages 410.3.7 

Under-floor ventilation 1 203.3 

VENTS, PENETRATION PROTECTION 713 



VERMICULITE, FIRE RESISTANT 

VERTICAL OPENING PROTECTION 
Atriums 

Duct penetrations 
Elevators 
Exceptions 
Group 1-3 
High-rise 



720 

404.6 

716.1 

708.14 

708.2, 1022.1 

408.5 

403.2.1.2, 403.2.3, 403.3.1.1, 403.5.1 



Shaft enclosure 708, 1016.1, 1022.1 

Value 3412.6.6.1 

VESTIBULES, EXIT DISCHARGE 1027.1 

VINYL 

Expanded 802,803.7,803.8 

Rigid 1405.14 

VIOLATIONS 114 

VOICE ALARM (see ALARMS, VOICE) 



W 



3104 

3306 

3202.3.4 

Table 601 

Table 1607.1 

Chapter 6 

715, 716 

705 

Chapter 6 

1405 



WALKWAY 

During construction 

Encroachment, public right-of-way 

Fire resistance 

Live load 

Materials per construction type 

Opening protection 

WALL, EXTERIOR 
Bearing 
Coverings 
Exterior Insulation and 

Finish Systems (EIFS) 1408 

Exterior structural members 704.10 

Fire district 0102.1, 0102.2.6 

Fire-resistance ratings Table 602, 703, 705.5, 

706.5.1,707.4,1403.4 
Flashing, veneered walls 1405.4 

Foam plastic insulation 2603.4.1.4, 2603.5 

Glazing, rated 715.5 

Joints 705.9, 714 

Light-transmitting plastic panels 2607 

Materials ^ 705.4, 1406 

Metal Composite Materials (MCM) 1407 

Nonbearing Chapter 6 

Opening protection 705.8, 705.10, 716.5.6 

Parapets 705.11 

Projections 705.2 

Structural stability 705.6 

Veneer (see VENEER) 

Weather resistance 1403.2, 1405.2, 

1407.6,1408.4 
Weather resistant barriers 1405.2 

WALL, FIRE (see FIRE WALLS) 
WALL, FOUNDATION (see FOUNDATION) 

WALL, INTERIOR 

Finishes 803, 1210.2, 1210.3 

Opening protection 715, 716 

WALL, INTERIOR NONBEARING (see PARTITIONS) 

WALL, MASONRY 2102.1 

Wood contact 2304.1 1 .2.3, 2304.1 1 .2.5 

WALL, PARAPET 705.11, 1503.3, 

1503.6, 2109.3.4.1.4 
WALL, PARTY (see FIRE WALLS) 
WALL, PENETRATIONS 713.3 

WALL, RETAINING (see RETAINING WALL) 
WALL, VENEERED (see VENEER) Chapter 14 



2009 INTERNATIONAL BUILDING CODE® 



673 



INDEX 



WALL, WOOD CONSTRUCTION 

Bracing 2308.9.3 

Cutting, notching, boring 2308.9.10 

Exterior framing 2308.9 

Fastening schedule 2304.9 

Framing 2304.3, 2308.9 

Interior bearing partition 2308.9.1 

Interior nonbearing partition 2308.9.2.3 
Openings *" 2308.9.5,2308.9.6,2308.9.7 
Shear walls 2305.1 ,2306.3 through 2306.7 
Sheathing (see SHEATHING) 

Studs 2308.9.1 

Top plates 2308.9.2.1 

WATER-REACTIVE MATERIALS Table 307.1 (1) 

WEATHER, COLD 

Concrete construction 1905.12 

Masonry construction 2104.3 

WEATHER, HOT 

Concrete construction 1905.13 

Masonry construction 21 04.4 

WEATHER PROTECTION 

Exterior walls 1405.2 

Roofs 1 503 



WELDING 

Materials, verification of 

steel reinforcement 
Special inspections 
Splices of reinforcement in masonry 
Structural testing 

WIND LOAD 
Alternate all-heights method 
Basic wind speed 
Construction documents 
Exposure category 
Glass block 
Glazing 

Hurricane-prone regions 
Provisions for walls 
Roofs 

Seismic detailing required 
Special inspection 
Statement of special inspections 
Wind-borne debris region 



2204.1 

1704.4.1 
1704.3.1,1707.2,1707.4 
2107.4 
1708.2, 1708.3 

1609 
1609.6 
1609.3 
107, 1603.1.4, 1709 
1609.4 
2110 
1609.1.2, 2404 
1609.2 
2306.2 
1504.1, 1609.5, 2308.10.1 
1604.10 
1706 
1705.4 
1609.2 
Wind tunnel testing 1609.1.1.2, 1716.2.2 

WINDERS, STAIR (see STAIRWAY CONSTRUCTION) 

WINDOW 
Accessibility 
Emergency egress 
Exterior, structural testing 
Fire (see OPENING PROTECTIVES) 



Glass (see GLAZiNG) 
Required light. 
Wells 

WIRES, PENETRATION PROTECTION 

WOOD 
Allowable stress design 
Bracing, walls 



1109.13.1 

1029 

1715.5 

715.4.9, 

715.4.10 

1405.13 

1205.2 

1029.5 

713 

Chapter 23 

2306 

2308.9.3 



721.6 

2308.10 

2304.9 

2304.11.4 

2304.11 

2305.2, 2306.2 

717.3, 717.4 

2303.1.1 

2303.1.5, 2306.6 

2303.2 



Calculated fire resistance 

Ceiling framing 

Connections and fasteners 

Contacting concrete, masonry or earth 

Decay, protection against. 

Diaphragms 2305.1 

Draftstopping 

End-jointed lumber 

Fiberboard 

Fire-retardant treated 

Fireblocking 717.2 

Floor and roof framing 

(see FLOOR CONSTRUCTION, WOOD) .. 2304.4 
Floor sheathing 2304.7 

Foundation 1807.1.4,2308.3.3.1 

Grade, lumber 2303.1.1 

Hardboard 2303.1.6 

Heavy timber construction 2304.1 

Hurricane shutters 1609.1 .2 

l-joist 2303.1.2 

Inspection, special. 1704.6, 1706.2, 1707.3 

Lateral force-resisting systems 2305 

Light-frame construction, conventional. 2308 

Load and resistance factor design 2307 

Moisture content 2303.1 .8.2,2303.2.6 

Nails and staples 2303.6 

Particleboard shear walls 2306.5 

Plywood, hardwood 2303.3 

Preservative treated 1403.5, 1403.6, 2303.1.8 

Roof framing 

(see ROOF CONSTRUCTION, WOOD) 2304.4 

Roof sheathing 2304.7 

Seismic provisions 2305, 2306, 2308.11, 2308.12 



Shear walls 



2305, 2306.3 through 2306.7 



Standards and quality, minimum 

Structural panels 

Supporting concrete or masonry 

Termite, protection against 

Trusses 

Veneer 

Wall framing 

(see WALL, WOOD CONSTRUCTION) 
Wall sheathing 



2303 

2302.1, 2303.1.4 

2304.12 

2304.11 

2303.4 

Chapter 14 



2304.3 
2304.6 



WOOD SHINGLES AND SHAKES 

WOOD STRUCTURAL PANELS 
(see WOOD) 
Bracing 
Decorative 
Design requirements 
Diaphragms 
Fastening 

Fire-retardant-treated 
Quality 

Roof sheathing 
Seismic shear panels 
Shear walls 
Sheathing 
Standards 
Subfloors 
Veneer 



1507.8,1507.9 

2302.1, 2303.1.4 

2308.9.3 

2303.3 

2301 

2305.1, 2306.2 

2304.9 

2303.2 

2303.1.4 

2304.7,2308.10.8 

2305.1, 2308.12.4 

2306.3 

2304.6.1 

2306.1 

804.4 

1405.5 



674 



2009 INTERNATIONAL BUILDING CODE® 



INDEX 



YARDS OR COURTS 1206 

Group 1-2 407.8 
Group 1-3 408.3.6, 408.6 

Light, natural 1205 

Motor fuel-dispensing facilities 406.5.3 

Occupant load 1004.8 

Parking garage, open 406.3.6 



2009 INTERNATIONAL BUILDING CODE® 675 



676 2009 INTERNATIONAL BUILDING CODE®